Special Notices
April 4, 2025 – AEP Transmission Facility Ratings (Updated 5.9.2025)
On 3.26.2025, AEP provided PJM with updated ratings on multiple transmission facilities following comprehensive system inspections, including the ratings on the 345 kV Eugene – Bunsonville, 765/500 kV Broadford T6 transformer, and 765/500 kV Jacksons Ferry 1 transformer. AEP is developing a plan for the impacted transmission facilities. More information will be posted as it becomes available.
Update 4.23.2025: The mitigation work on the 345 kV Eugene – Bunsonville will begin in on Thursday, April 24, 2025 and will restore the ratings at the completion of eDART ticket # 1244977.
The 345 kV Eugene – Bunsonville ratings below are expected to be applicable at the completion of eDART #1244977 but verifications are still being performed.
Update 4.24.2025: The 345 kV Eugene – Bunsonville ratings below have been verified and confirmed by AEP as applicable upon completion of eDART #1244977.
Update 5.9.2025: The mitigation work on the 765/500 kV Broadford T6 Transformer has been completed, and the updated ratings are listed below.
Update 6.26.2025: The mitigation work on the 765/500 kV Broadford T6 Transformer has been completed, and the updated ratings are listed below.
| |
345 kV Eugene - Bunsonville Tie Line |
| |
Normal |
Long Term |
Short Term |
Load Dump |
| Temp |
Day/Night |
Day/Night |
Day/Night |
Day/Night |
| 95 |
1739 |
1739 |
1739 |
1792 |
| 86 |
1739 |
1739 |
1739 |
1792 |
| 77 |
1739 |
1739 |
1739 |
1792 |
| 68 |
1739 |
1739 |
1739 |
1792 |
| 59 |
1739 |
1739 |
1739 |
1792 |
| 50 |
1739 |
1739 |
1739 |
1792 |
| 41 |
1739 |
1739 |
1739 |
1792 |
| 32 |
1739 |
1739 |
1739 |
1792 |
| |
765/500 kV Broadford T6 Transformer |
| |
Normal |
Long Term |
Short Term |
Load Dump |
| Temp |
Day/Night |
Day/Night |
Day/Night |
Day/Night |
| 95 |
1812 |
1919 |
1919 |
1996 |
| 86 |
1863 |
1968 |
1968 |
2047 |
| 77 |
1914 |
2017 |
2017 |
2098 |
| 68 |
1966 |
2066 |
2066 |
2149 |
| 59 |
2017 |
2114 |
2114 |
2199 |
| 50 |
2068 |
2163 |
2163 |
2250 |
| 41 |
2119 |
2212 |
2212 |
2301 |
| 32 |
2171 |
2261 |
2261 |
2352 |
| |
765/500 kV Jacksons Ferry 1 Transformer |
| |
Normal |
Long Term |
Short Term |
Load Dump |
| Temp |
Day/Night |
Day/Night |
Day/Night |
Day/Night |
| 95 |
1790 |
1897 |
1897 |
1996 |
| 86 |
1841 |
1945 |
1945 |
2047 |
| 77 |
1892 |
1993 |
1993 |
2097 |
| 68 |
1943 |
2042 |
2042 |
2149 |
| 59 |
1993 |
2090 |
2090 |
2199 |
| 50 |
2044 |
2138 |
2138 |
2250 |
| 41 |
2095 |
2186 |
2186 |
2300 |
| 32 |
2146 |
2235 |
2235 |
2352 |
6.26.2025
Elmont – Ladysmith 574 Outage
The Elmont – Ladysmith 574 500kV line in DOM zone is scheduled to be out of service from October – December 2024 under eDART ticket 819852. This outage is the first of multiple outages scheduled over the next two years to wreck and rebuild due to Dominion’s End of Life criteria. The upgrade is under RTEP b3020 which has a required in-service date of May 29, 2026.
In order to meet the RTEP in-service requirement date of May 29, 2026, PJM has approved this outage request as it does not jeopardize reliability or pose any significant risk to the system.
10.2.2024
Conastone #2 500/230 kV Transformer Restoration Update (Updated 8.12.2024)
On July 2, 2024 BG&E removed the Conastone 500-2 500/230kV transformer from service due to an identified gassing issue under eDART ticket 1191308. Upon further investigation by BG&E and the transformer manufacturer, it was confirmed a phase of the 500-2 transformer is damaged beyond repair and will need to be replaced. BG&E is currently utilizing one on-site spare phase on the Conastone 500-4 transformer and is in the process of installing the replacement “C” phase in Conastone 500-4. Once all equipment is in place, BG&E will need to take following actions to restore the system to normal:
- Remove the Conastone 500-4 transformer from service under eDART ticket 1194991 on 08/16
- Creating a scenario where both Conastone 500/230kV transformers are out of service simultaneously
- Reconfigure the substation to reconnect the spare transformer currently utilized on the Conastone 500-4 and connect
it to Conastone 500-2
- Return the Conastone 500-2 transformer to service on 08/19 under eDART ticket 1191308
- Connect the newly delivered spare to the Conastone 500-4 transformer
- Return the Conastone 500-4 transformer to service on 08/25 (eDART ticket 1194993) to return the system to normal
configuration
PJM has reviewed and approved the plan. The schedule provided above is subject to change based on system conditions, forecasted demand, unscheduled generation and transmission outages. The plan timeline will shift into September if projected system conditions identify reliability issues.
The end date of eDART ticket 1191308 for the Conastone 500-2 500/230kV transformer was changed in error on 08/10 13:52. The end date was reverted back to 8/19 at 18:00 after confirmation from BG&E.
8.12.2024
December 6, 2023 (updated July 5,2024)
In an effort to enhance transparency, PJM System Operations is sharing its internal Operating Memo (OM) PDF that is used for guidance to commit long lead generation for transmission congestion in light of recent unit deactivation notifications in the Baltimore Gas & Electric (BGE) transmission zone.
7.5.2024
November 22, 2023 - DPL Transmission Facility Ratings (updated 12.8.2023)
On 11.17.2023, DPL provided PJM with updated ratings on multiple transmission facilities following comprehensive system inspections, including the ratings on the Piney Grove 230/138kV transformer and New Church – Oak Hall 13765 138kV line. DPL is developing a plan for the impacted transmission facilities, beginning with the New Church – Oak Hall 13765 138kV line and Piney Grove 230/138kV transformer. DPL will implement the actions for the New Church – Oak Hall 13765 138kV line and will restore the permanent ratings at the completion of eDART 1146804. The mitigation work on the Piney Grove transformer will begin in mid-December and will partially restore the ratings at the completion of eDART ticket # 1148478.
The Piney Grove AT20 ratings below will be applicable at the completion of eDART 1148478.
| |
Piney Grove AT20 |
| |
Normal |
|
Long Term |
Short Term |
Load Dump |
|
|
|
| Temp |
Day |
Night |
Day |
Night |
Day |
Night |
Day |
Night |
| 95 |
280 |
280 |
348 |
348 |
348 |
348 |
401 |
401 |
| 86 |
280 |
280 |
348 |
348 |
348 |
348 |
401 |
401 |
| 77 |
280 |
280 |
348 |
348 |
348 |
348 |
401 |
401 |
| 68 |
280 |
280 |
348 |
348 |
348 |
348 |
401 |
401 |
| 59 |
280 |
280 |
348 |
348 |
348 |
348 |
401 |
401 |
| 50 |
318 |
318 |
389 |
389 |
389 |
389 |
447 |
447 |
| 41 |
318 |
318 |
389 |
389 |
389 |
389 |
447 |
447 |
| 32 |
318 |
318 |
389 |
389 |
389 |
389 |
447 |
447 |
12.8.2023
January 11, 2022 (updated 2.22.2022)
November 2, 2021
First Energy Bulk Ratings Change
First Energy recently completed a comprehensive review of BES facility ratings for all its 5 operating zones: ME, JC, PN, FE, APS. The review included field walkdowns of installed equipment, back-office reviews of prints and other source documentation, and verification of all BES substation equipment and transmission ratings against established company equipment and facility methodologies. Implementation schedule for the new ratings is as follows:
November 3, 2021: FE-East (ME, JC, PN) XLS
November 10, 2021: FE-West (FE) XLS
November 17, 2021: FE-South (APS) XLS
11.2.2021
May 17, 2021
PEPCO Holdings
Pepco Holdings recently completed a comprehensive review of BES facility ratings for all its 3 operating companies: Pepco, Delmarva Power, and Atlantic City Electric. The review included field walkdowns of installed equipment, back-office reviews of prints and other source documentation, and verification of all BES substation equipment and transmission ratings against established company equipment and facility methodologies. The review results were presented to the PJM Planning Committee meeting on May 11, 2021 and the Operating Committee meeting on May 14, 2021.
List of PHI Facilities Affected by This Review and Their New Ratings
5.17.2021
December 12, 2020
ComEd Switching to Ambient Ratings
ComEd will stop using seasonal ratings and begin using ambient ratings. The changeover is scheduled to occur on Monday, December 21, 2020 at 10:00 EST. Please refer to the Ratings Information page to view the ambient ratings for the ComEd facilities. The 50-Day rating will be used to represent the seasonal Winter rating, until the changeover occurs on Monday, December 21, 2020.
12.9.2020
July 13, 2020
On Monday July 13, 2020 both MISO and PJM will disable constraint relaxation for Market to Market coordinated flowgates in accordance with the MISO-PJM Joint Operating Agreement. This date is subject to rescheduling based on system conditions on July 13th.
6.24.2020
March 27, 2020
Effective 12:00:01 EPT (or 16:00:01 GMT) on April 1, 2020 both MISO and PJM will disable constraint relaxation for Market to Market coordinated flowgates in accordance with the MISO-PJM Joint Operating agreement.
3.27.2020
July 2, 2019
Dynamic Transfers - Electrical Distance Test
This document describes the methodology followed to evaluate external resources against the PJM Pseudo-Tie Electrical Distance Qualification Test.
Dynamic Transfers - Market-to-Market Flowgate Test
This document describes the methodology followed to evaluate external resources against the PJM Pseudo-Tie M2M Qualification Test.
Additional pseudo-tie information
7.2.2019
March 8, 2019
EKPC Spurlock Area Line Changes
The Spurlock–Renaker, Spurlock-Stanley Parker, Spurlock-Stuart, and Spurlock-Meldahl Dam lines in EKPC zone are scheduled to be out of service in March and/or April 2019 under eDART tickets 797401 and 797407. These outages, in conjunction with tickets 701460 and 701476, are needed for clearance to relocate and decouple the double-circuited Spurlock - Maysville Industrial Tap 138 kV & Spurlock - Flemingsburg 138 kV line segments. The upgrade is under RTEP b2614 which has a required in-service date of June 1, 2019.
eDART tickets 797401 and 797407 are currently not “on-time” due to the timing of the outage submittal. In order to meet the RTEP in-service requirement date of June 1, 2019, these two tickets are marked as emergency outages under Manual-03 Section 4.2.9.1. PJM is approving the outage requests associated with RTEP b2614 upgrade in order to complete the upgrade by the required in-service date. 2019 RTEP Status
For questions, please email Transmission Operations or call (610) 666-8289.
3.8.2019
February 7, 2019
PJM Pseudo-Tie M2M Qualification Preliminary Results
The following document pertains solely to the PJM Pseudo-Tie M2M Qualification Test and contains preliminary results as of February 7th, 2019. Results identify physical external resources that pass the preliminary M2M Qualification Test and do not represent a list of resources that qualify as a PJM Pseudo-Tie resource. Additional criteria and information pertaining to Pseudo-Tie resources can be found on the PJM Dynamic Transfers web page.
2.7.2019
January 24, 2019
PPL Siegfried Configuration
PPL is in the process of upgrading the Siegfried substation. The work is under a supplemental project to install a new GIS bus. As part of the upgrade, the Siegfried 230/69 transformers are also being replaced with new transformers. Once the new transformers are in service connected to the new 230 kV bus, the old transformers will eventually be removed from service and retired. The work at Siegfried are under various outages posted on the OASIS Outage Information page
1.24.2019
October 1, 2018
AEP Facilities De-rates
AEP has performed a comprehensive review of its transmission facilities ratings within the PJM footprint and determined that certain facilities should be de-rated. Please see the list of affected transmission facilities below. The revised ratings will be effective on October 3, 2018. Please refer to the Ratings Information page for the current ratings in effect for all facilities including these de-rated AEP facilities.
10.1.2018
February 22, 2018
Spurlock - Stuart & Spurlock - Meldahl Dam 345 kV Line Outages
The Spurlock - Stuart and Spurlock - Meldahl Dam 345 kV lines are scheduled to be out of service from March 20, 2018 to June 12, 2018 under eDART tickets 714775, 715816 and 715014. These outages are needed to reconductor a portion of the Stuart - Spurlock 345 kV line and to replace a wave trap in order to increase the line ratings. The upgrades are under RTEP b2879.1 and b2879.2, which have a required in-service date of June 1, 2018. The projects are expected to provide the rating increases as shown below:
|
Normal |
Emergency |
| Current Ratings |
1240 |
1374 |
| RTEP b2879.1 |
1240 |
1532 |
| RTEP b2879.2 |
1466 |
1710 |
RTEP Status | TEAC Report PDF
Background
The Killen and Stuart owners notified PJM on March 20, 2017 of their plan to deactivate both plants on June 1, 2018. As a result, PJM performed deactivation studies and determined that several system upgrades are required. These upgrades are listed in the RTEP plan with the driver as generator deactivation of the Killen and Stuart plants. The PJM Board of Managers approved these upgrade projects on July 25, 2017. EKPC accepted construction responsibility for project b2879.2 on August 25, 2018 and subsequently submitted the required transmission outages to PJM in September 2017.
Due to the timing of the generation retirement announcement and the development of the planning criteria violation mitigation plan, the required transmission outages could not have been submitted in accordance with PJM’s on-time transmission outage submittal rules as outlined in Manual 3, Section 4. Therefore, PJM is approving the outage requests associated with the Stuart-Spurlock 345 kV line to expedite these particular system upgrades.
For questions, please email Transmission Operations or call (610) 666-8289.
2.22.2018
|
|
|