AF1-123 Phase I Study Report
v1.00 released 2024-05-16 00:11
Oceana 230 kV
267.5 MW Capacity / 880.0 MW Energy
Introduction
This Phase I System Impact Study Report (PH1) has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, sections 307 and 308 for New Service Requests (projects) in Transition Cycle #1. The Project Developer/Eligible Customer (developer) is Virginia Electric & Power Company, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Virginia Electric and Power Company.
Preface
The Phase I System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle executive summary format and (ii) an individual project-level basis. The Phase I System Impact Study Results (for both the executive summary and individual reports) will be publicly available on PJM’s website. Developers must obtain the results from the website.
In accordance with PJM Manual 14H, section 4.3, PJM takes the following actions during the Phase I System Impact Study:
- PJM studies each New Service Request on a summer peak, winter peak[1] and light load RTEP base case study. The case year is dependent on the new services cycle under study. PJM will identify the base case year to be used in the study of a specific cycle on its website.
- PJM will only perform load flow analysis during the Phase I System Impact Study.
- In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with Affected System impacts and provides each Affected System Operator with a list of New Service Request in the Cycle with potential impacts to their respective system.
- PJM will create both the short circuit and stability base cases to be used in the Phase II System Impact Study.
- The Phase I System Impact Study results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.
The Transmission Owner takes the following actions during the Phase I System Impact Study:
- Identify required Interconnection Facilities to accommodate the New Service Request.
- Identify required Network Upgrades to mitigate system violations from the Phase I System Impact Study.
- Provide planning-level preliminary estimates of Interconnection Facilities and Network Upgrades including scope, cost and elapsed time to complete the work.
Decision Point I Requirements
At the close of Phase I System Impact Study, PJM will initiate Decision Point I (DP1). During DP1, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.A.1. Additional information on these elements is available in PJM Manual 14H sections 4.4, 6, and 7.
Allowable project modifications at Decision Point I are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.
General
The developer has proposed a Offshore Wind generating facility located in the Virginia Electric and Power Company zone — City of Chesapeake County, Virginia. The installed facilities will have a total capability of 880.0 MW with 267.5 MW of this output being recognized by PJM as Capacity.
| Project Information | |
|---|---|
| New Service Request Number | AF1-123 |
| Project Name | Oceana 230 kV |
| Developer Name | Virginia Electric & Power Company |
| State | Virginia |
| County | City of Chesapeake |
| Transmission Owner | Virginia Electric and Power Company |
| MFO | 880.0 MW |
| MWE | 880.0 MW |
| MWC | 267.5 MW |
| Fuel Type | Offshore Wind |
| Basecase Study Year | 2027 |
Point of Interconnection
AF1-123 will interconnect on the Dominion transmission system at the Oceana 230 kV Substation.
Cost Summary
The table below shows a summary of the total planning level cost estimates for this New Service Request project. These network upgrade costs are subject to change as a result of a facility study performed by the TO during the Phase II or Phase III System Impact Study.
Based on the Phase I SIS results, the AF1-123 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit are also shown below.
| Cost Summary | |||
|---|---|---|---|
| Description | Cost Allocated to AF1-123 | Cost Subject to Readiness* | |
| Transmission Owner Interconnection Facilities (TOIF) | $4,833,333 | $0 | |
| Physical Interconnection Network Upgrades | |||
| Stand Alone Network Upgrades | $263,300,000 | $263,300,000 | |
| Network Upgrades | $0 | $0 | |
| System Reliability Network Upgrades | |||
| Steady State Thermal & Voltage (SP & LL) | $217,174,869 | $217,174,869 | |
| Transient Stability | $0 | $0 | |
| Short Circuit | $0 | $0 | |
| Transmission Owner Analysis | |||
| SubRegional | $0 | $0 | |
| Distribution | $0 | $0 | |
| Affected System Study Reinforcements | $0 | $0 | |
| Total | $485,308,203 | $480,474,869 | |
* Contributes to calculation for Readiness Deposit #2 (RD2). See Readiness Deposit section of report for additional detail.
Definitions
Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.
Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.
Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.
Notes
Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.
Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.
Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.
Readiness Deposit
Per Tariff Part VII, Subpart D, section 309 (Decision Point I) A.1.a.i and PJM Manual 14H, section 6.2, Readiness Deposit #2 (RD2) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below and not used to fund studies nor to offset Security.
During Decision Point I (DP1), the Project Developer or Eligible Customer is required to submit Readiness Deposit #2, which is calculated as 10% of cost allocation for required Phase I Network Upgrades minus Readiness Deposit #1.
Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.
Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))
Note 3: Readiness Deposit #2 can be zero, but may not be a negative number.
Readiness Deposit #2 Due for Project AF1-123
Readiness Deposit #2 has been calculated for the project based on the Phase I System Impact Study results and is shown in the table below. This Readiness Deposit #2 must be provided at Decision Point I through either a wire transfer or letter of credit per Manual 14H, Section 6.2.
| Readiness Deposit | |||
|---|---|---|---|
| Project ID | 10% of cost allocation for Phase I Network Upgrades | Readiness Deposit #1 Received (RD1) | Readiness Deposit #2 (RD2) for AF1-123 Project due at DP1 |
| A | B | A - B | |
| AF1-123 | $48,047,487 | $3,520,000 | $44,527,487 |
Note: Failure to provide an acceptable form of Readiness Deposit #2 by the end of Decision Point I will result in withdrawal and termination of the New Service Request.
For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.
Transmission Owner Scope of Work
The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.
| Transmission Owner Interconnection Facilities | |||
|---|---|---|---|
| RTEP ID | Description | Total Cost ($USD) | Allocated Cost ($USD) |
| (Pending) | Install nine (9) Export Circuits to the point of interconnection ("POI"), metering, and associated protection equipment. |
$14,500,000 | $4,833,333 (See Note 1) |
| Stand-Alone Network Upgrades | |||
|---|---|---|---|
| RTEP ID | Description | Total Cost ($USD) | Allocated Cost ($USD) |
| (Pending) | Build a new Harpers 230 kV substation. Add three (3) 300 MVAR STATCOMs. |
$228,300,000 | $76,100,000 (See Note 1) |
| (Pending) | Install three (3) new 230 kV lines beween New Fentress and Harpers. |
$304,500,000 | $101,500,000 (See Note 1) |
| (Pending) | Build a New Fentress 230 kV double breaker double bus substation. |
$99,600,000 | $33,200,000 (See Note 1) |
| (Pending) | Upgrade the Fentress 500 kV substation to be a double breaker double bus substation. Install three (3) new 230/500 kV transformers. |
$157,500,000 | $52,500,000 (See Note 1) |
Based on the scope of work for the Interconnection Facilities, it is expected to take a range of 36 to 40 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.
The schedule for any required Network Impact Reinforcements will be more clearly identified in the Phase II and Phase III System Impact Studies.
Note 1: A Common Use Upgrade is a Network Upgrade that is needed for the interconnection of Generating Facilities or Merchant Transmission Facilities of more than one Project Developer or Eligible Customer and which is the shared responsibility of each Project Developer or Eligible Customer. If multiple Project Developers request to connect to the same interconnection substation, the Transmission Owner will determine the cost to accommodate all the requests at the substation. The cost for the interconnection will be allocated in proportion to the number of required terminations into the substation.
It is estimated to take 36 to 40 months to complete this work upon execution of the Generator Interconnection Agreement (GIA).This estimated time to complete is dependent on major equipment lead times. These preliminary cost estimates are based on typical engineering costs. A more detailed engineering cost estimates are normally done when the Project Developer provides an exact site plan location for the generation substation during a future study phase. As shown in the one line diagram, this Interconnection Request is sharing the Point of Interconnection (POI) and Interconnection Facilities with one or more other Interconnection Requests. Should other requests withdraw from Transition Cycle 1, the cost allocation for Transmission Owner Interconnection Facilities, Stand Alone Network Upgrades, and applicable Network Upgrades identified in the study report will be updated for the remaining project(s). Refer to the one line for other Interconnection Requests at this POI.
Note that the TO findings were made from a conceptual review of this project. A more detailed review of the connection facilities and their cost will be identified in a future study phase. Further note that the cost estimate data provided should be considered high level estimates since it was produced without a detailed engineering review. The Project Developer will be responsible for the actual cost of construction. TO herein reserves the right to return to any issues in this document and, upon appropriate justification, request additional monies to complete any reinforcements to the transmission systems.
Remote Terminal Work: During Phase 2 of the PJM interconnection process, TO’s System Protection Engineering Department will review transmission line protection as well as anti-islanding required to accommodate the new generation and interconnection substation. System Protection Engineering will determine the minimal acceptable protection requirements to reliably interconnect the proposed generating facility with the transmission system. The review is based on maintaining system reliability by reviewing TO’s protection requirements with the known transmission system configuration which includes generating facilities in the area. This review may determine that transmission line protection and communication upgrades are required at remote substations.
Transmission Owner Analysis
PJM performed a power flow analysis of the transmission system using a 2027 load flow model and the results were verified by Dominion.
Developer Requirements
System Protection
The Project Developer must design its Generating Facility in accordance with all applicable standards, including the standards in Dominion’s “Dominion Energy Electric Transmission Generator Interconnection Requirements” documented in Dominion’s Facility Interconnection Requirements located at: https://www.pjm.com/-/media/planning/plan-standards/private-dominion/facility-connection-requirements1.ashx. Preliminary Protection requirements will be provided as part of the Facilities Study. Detailed Protection Requirements will be provided once the project enters the construction phase.
Compliance Issues and Project Developer Requirements
The proposed Generating Facility must be designed in accordance with Dominion’s “Dominion’s Facility Interconnection Requirements” document located at: https://www.pjm.com/-/media/planning/plan-standards/private-dominion/facility-connection-requirements1.ashx.
In particular, the Project Developer is responsible for the following:
- The purchase and installation of a fully rated protection device (circuit breaker, circuit switcher, fuse) to protect the Project Developer’s GSU transformer(s).
- The purchase and installation of the minimum required Dominion generation interconnection relaying and control facilities as described in the System Protection section noted above. This includes over/under voltage protection, over/under frequency protection, and zero sequence voltage protection relays.
- The purchase and installation of supervisory control and data acquisition (“SCADA”) equipment to provide information in a compatible format to the Dominion Transmission System Control Center.
- Compliance with the Dominion and PJM generator power factor and voltage control requirements. The GSU(s) associated with the Project Developer New Service Request Project shall meet the grounding requirements as noted in Dominion’s “Dominion’s Facility Interconnection Requirements” document located at: https://www.pjm.com/-/media/planning/plan-standards/private-dominion/facility-connection-requirements1.ashx.
- IBR Resources are required to meet Dominion’s Ride-Through Requirements for Bulk Power System (BPS) Generators
The Project Developer will also be required to meet all PJM, SERC, and NERC reliability criteria and operating procedures for standards compliance. For example, the Project Developer will need to properly locate and report the over and under voltage and over and under frequency system protection elements for its units as well as the submission of the generator model and protection data required to satisfy the PJM and SERC audits. Failure to comply with these requirements may result in a disconnection of service if the violation is found to compromise the reliability of the Dominion system.
Power Factor Requirements
The Project Developer shall design its non-synchronous Generator Facility with the ability to maintain a power factor of at least 0.95 leading (absorbing VARs) to 0.95 lagging (supplying VARs) measured at the high-side of the facility substation transformer(s) connected to the Dominion transmission system.
Revenue Metering and SCADA Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.Meteorological Data Reporting Requirement
The wind generation facility shall provide the Transmission Provider with site-specific meteorological data including:Transmission Owner Requirements
- Wind speed (meters/second) - (Required)
- Wind direction (decimal degrees from true north) - (Required)
- Ambient air temperature (Fahrenheit) - (Required)
- Air Pressure (Hectopascals) - (Required)
- Humidity (Percent) - (Accepted, not required)
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.
Summer Peak Analysis
The New Service Request project was evaluated as a 880.0 MW (Capacity 267.5 MW) injection in the Dominion area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential summer peak period network impacts were as follows:
Note: The capacity portion of New Service Requests are evaluated for single or N-1 contingencies. The full energy output of New Service Requests are evaluated for multiple facility contingencies (double circuit tower line, fault with a stuck breaker, and bus fault).
| Summer Peak Analysis | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Final Cycle Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | ||
| DVP |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
314287 to 314276 ckt 1 |
DVP_P1-2: LN 563_SRT-S-1
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S-1' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA 500.0 - AE2-051 TP 500.0 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TP 500.0 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TP 500.0 SET PRECONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA 500.0 - AE2-051 TP 500.0 END |
Single | AC | 168.82 % | 663.64 | B | 1120.36 | 15.97 | ||
| DVP |
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
314934 to 314916 ckt 1 |
DVP_P1-2: LN 575_SRT-S-1
CONTINGENCY 'DVP_P1-2: LN 575_SRT-S-1' OPEN BRANCH FROM BUS 314911 TO BUS 962840 CKT 1 /*8LADYSMITH 500.0 - AG1-133 TP 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH 500.0 - 8POSSUM 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH 500.0 - 8POSSUM 500.0 END |
Single | AC | 139.37 % | 3220.44 | B | 4488.27 | 42.16 | ||
| DVP |
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
314934 to 314916 ckt 1 |
DVP_P1-2: LN 575_SRT-S-2
CONTINGENCY 'DVP_P1-2: LN 575_SRT-S-2' OPEN BRANCH FROM BUS 962840 TO BUS 314918 CKT 1 /*AG1-133 TP 500.0 - 8NO ANNA 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH 500.0 - 8POSSUM 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH 500.0 - 8POSSUM 500.0 END |
Single | AC | 139.07 % | 3220.44 | B | 4478.58 | 42.16 | ||
| DVP |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
314914 to 314918 ckt 1 |
DVP_P1-2: LN 574_SRT-S
CONTINGENCY 'DVP_P1-2: LN 574_SRT-S' OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE 500.0 - 8LADYSMITH 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE 500.0 - 8LADYSMITH 500.0 END |
Single | AC | 136.87 % | 3220.44 | B | 4407.84 | 73.2 | ||
| DVP |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
314908 to 314911 ckt 1 |
DVP_P1-2: LN 576_SRT-A
CONTINGENCY 'DVP_P1-2: LN 576_SRT-A' OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN 500.0 - 8NO ANNA 500.0 END |
Single | AC | 133.6 % | 4070.2 | B | 5437.98 | 85.41 | ||
| DVP |
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
314918 to 314934 ckt 1 |
DVP_P1-2: LN 575_SRT-S-1
CONTINGENCY 'DVP_P1-2: LN 575_SRT-S-1' OPEN BRANCH FROM BUS 314911 TO BUS 962840 CKT 1 /*8LADYSMITH 500.0 - AG1-133 TP 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH 500.0 - 8POSSUM 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH 500.0 - 8POSSUM 500.0 END |
Single | AC | 133.53 % | 3220.44 | B | 4300.2 | 43.23 | ||
| DVP |
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
314918 to 314934 ckt 1 |
DVP_P1-2: LN 575_SRT-S-2
CONTINGENCY 'DVP_P1-2: LN 575_SRT-S-2' OPEN BRANCH FROM BUS 962840 TO BUS 314918 CKT 1 /*AG1-133 TP 500.0 - 8NO ANNA 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH 500.0 - 8POSSUM 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH 500.0 - 8POSSUM 500.0 END |
Single | AC | 132.25 % | 3220.44 | B | 4259.06 | 43.23 | ||
| DVP |
AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line
962840 to 314911 ckt 1 |
DVP_P1-2: LN 573_SRT-A
CONTINGENCY 'DVP_P1-2: LN 573_SRT-A' OPEN BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA 500.0 - 8SPOTSYL 500.0 END |
Single | AC | 131.42 % | 3220.44 | B | 4232.21 | 36.01 | ||
| DVP |
8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line
314918 to 962840 ckt 1 |
DVP_P1-2: LN 573_SRT-A
CONTINGENCY 'DVP_P1-2: LN 573_SRT-A' OPEN BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA 500.0 - 8SPOTSYL 500.0 END |
Single | AC | 129.78 % | 3220.44 | B | 4179.52 | 36.01 | ||
| DVP |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
314902 to 314914 ckt 1 |
DVP_P1-2: LN 574_SRT-S
CONTINGENCY 'DVP_P1-2: LN 574_SRT-S' OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE 500.0 - 8LADYSMITH 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE 500.0 - 8LADYSMITH 500.0 END |
Single | AC | 129.59 % | 3220.44 | B | 4173.53 | 66.06 | ||
| DVP |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
314914 to 314322 ckt 1 |
DVP_P1-2: LN 576_SRT-A
CONTINGENCY 'DVP_P1-2: LN 576_SRT-A' OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN 500.0 - 8NO ANNA 500.0 END |
Single | AC | 125.87 % | 1058.16 | B | 1331.91 | 20.22 | ||
| DVP |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
314924 to 314903 ckt 1 |
DVP_P1-2: LN 563_SRT-S-1
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S-1' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA 500.0 - AE2-051 TP 500.0 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TP 500.0 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TP 500.0 SET PRECONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA 500.0 - AE2-051 TP 500.0 END |
Single | AC | 121.55 % | 2442.12 | B | 2968.32 | 79.3 | ||
| DVP |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
314902 to 314914 ckt 1 |
DVP_P1-2: LN 557_SRT-S
CONTINGENCY 'DVP_P1-2: LN 557_SRT-S' OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1 /*8CHCKAHM 500.0 - 8ELMONT 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 END |
Single | AC | 119.58 % | 3220.44 | B | 3850.88 | 69.59 | ||
| DVP |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer
314218 to 314908 ckt 2 |
DVP_P1-2: LN 557_SRT-S
CONTINGENCY 'DVP_P1-2: LN 557_SRT-S' OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1 /*8CHCKAHM 500.0 - 8ELMONT 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 END |
Single | AC | 117.94 % | 879.84 | B | 1037.67 | 29.27 | ||
| DVP |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer
314218 to 314908 ckt 1 |
DVP_P1-2: LN 557_SRT-S
CONTINGENCY 'DVP_P1-2: LN 557_SRT-S' OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1 /*8CHCKAHM 500.0 - 8ELMONT 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 END |
Single | AC | 117.11 % | 888.3 | B | 1040.26 | 29.34 | ||
| DVP |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
314908 to 314911 ckt 1 |
DVP_P1-2: LN 563_SRT-S-1
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S-1' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA 500.0 - AE2-051 TP 500.0 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TP 500.0 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TP 500.0 SET PRECONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA 500.0 - AE2-051 TP 500.0 END |
Single | AC | 116.86 % | 4070.2 | B | 4756.36 | 73.89 | ||
| DVP |
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
314911 to 314922 ckt 1 |
DVP_P1-2: LN 581_SRT-S
CONTINGENCY 'DVP_P1-2: LN 581_SRT-S' OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2 /*3CHANCE 115.0 - 8CHANCE 500.0 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE 500.0 - 8LADYSMITH 500.0 SET POSTCONTRATING 2831 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER 500.0 - 8CHANCE 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 SET PRECONTRATING 2552 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER 500.0 - 8CHANCE 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 END |
Single | AC | 111.8 % | 3220.44 | B | 3600.5 | 42.16 | ||
| DVP |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
314914 to 314918 ckt 1 |
DVP_P1-2: LN 557_SRT-S
CONTINGENCY 'DVP_P1-2: LN 557_SRT-S' OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1 /*8CHCKAHM 500.0 - 8ELMONT 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 END |
Single | AC | 111.07 % | 3220.44 | B | 3576.8 | 69.41 | ||
| DVP |
6CHESTF A-6IRON208 230.0 kV Ckt 1 line
314286 to 314309 ckt 1 |
DVP_P1-2: LN 557_SRT-S
CONTINGENCY 'DVP_P1-2: LN 557_SRT-S' OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1 /*8CHCKAHM 500.0 - 8ELMONT 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 END |
Single | AC | 110.35 % | 663.64 | B | 732.33 | 15.38 | ||
| DVP |
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
314911 to 314922 ckt 1 |
DVP_P1-2: LN 552_SRT-S
CONTINGENCY 'DVP_P1-2: LN 552_SRT-S' OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1 /*3CHANCE 115.0 - 8CHANCE 500.0 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER 500.0 - 8CHANCE 500.0 SET POSTCONTRATING 2831 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE 500.0 - 8LADYSMITH 500.0 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER 500.0 - 8MORRSVL 500.0 SET PRECONTRATING 2552 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE 500.0 - 8LADYSMITH 500.0 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER 500.0 - 8MORRSVL 500.0 END |
Single | AC | 110.35 % | 3220.44 | B | 3553.69 | 42.04 | ||
| DVP |
8OX-8CLIFTON 500.0 kV Ckt 1 line
314919 to 314904 ckt 1 |
DVP_P1-2: LN 569_SRT-S
CONTINGENCY 'DVP_P1-2: LN 569_SRT-S' OPEN BRANCH FROM BUS 314913 TO BUS 314916 CKT 1 /*8LOUDOUN 500.0 - 8MORRSVL 500.0 SET POSTCONTRATING 3118 BRANCH FROM BUS 314916 TO BUS 314929 CKT 1 /*8MORRSVL 500.0 - 8FRONT ROYAL 500.0 SET PRECONTRATING 2858 BRANCH FROM BUS 314916 TO BUS 314929 CKT 1 /*8MORRSVL 500.0 - 8FRONT ROYAL 500.0 END |
Single | AC | 108.62 % | 2686.52 | B | 2918.03 | 28.98 | ||
| DVP |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
314924 to 314903 ckt 1 |
DVP_P1-2: LN 576_SRT-A
CONTINGENCY 'DVP_P1-2: LN 576_SRT-A' OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN 500.0 - 8NO ANNA 500.0 END |
Single | AC | 107.54 % | 2442.12 | B | 2626.33 | 75.66 | ||
| DVP |
6IRON208-6SOUWEST 230.0 kV Ckt 1 line
314309 to 314338 ckt 1 |
DVP_P1-2: LN 557_SRT-S
CONTINGENCY 'DVP_P1-2: LN 557_SRT-S' OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1 /*8CHCKAHM 500.0 - 8ELMONT 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 END |
Single | AC | 103.64 % | 663.64 | B | 687.83 | 15.36 | ||
| DVP |
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
314934 to 314916 ckt 1 |
Base Case | Single | AC | 102.55 % | 3220.44 | A | 3302.58 | 38.7 | ||
| DVP |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line
314287 to 314260 ckt 1 |
DVP_P1-2: LN 563_SRT-S-1
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S-1' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA 500.0 - AE2-051 TP 500.0 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TP 500.0 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TP 500.0 SET PRECONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA 500.0 - AE2-051 TP 500.0 END |
Single | AC | 102.03 % | 984.18 | B | 1004.18 | 14.83 | ||
| DVP |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line
314260 to 314225 ckt 1 |
DVP_P1-2: LN 563_SRT-S-1
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S-1' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA 500.0 - AE2-051 TP 500.0 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TP 500.0 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TP 500.0 SET PRECONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA 500.0 - AE2-051 TP 500.0 END |
Single | AC | 102.01 % | 984.18 | B | 1003.96 | 14.83 | ||
| DVP |
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
314905 to 314900 ckt 1 |
DVP_P1-2: LN 594_SRT-S
CONTINGENCY 'DVP_P1-2: LN 594_SRT-S' OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1 /*8MORRSVL 500.0 - 8SPOTSYL 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER 500.0 - 8MORRSVL 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER 500.0 - 8MORRSVL 500.0 END |
Single | AC | 101.78 % | 4070.2 | B | 4142.78 | 51.8 | ||
| DVP |
8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
314911 to 314905 ckt 1 |
DVP_P1-2: LN 573_SRT-A
CONTINGENCY 'DVP_P1-2: LN 573_SRT-A' OPEN BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA 500.0 - 8SPOTSYL 500.0 END |
Single | AC | 101.62 % | 4070.2 | B | 4136.33 | 52.82 | ||
| DVP |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
314902 to 314914 ckt 1 |
Base Case | Single | AC | 101.53 % | 3220.44 | A | 3269.62 | 53.38 | ||
| DVP |
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer
314322 to 314914 ckt 1 |
DVP_P1-2: LN 563_SRT-S-1
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S-1' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA 500.0 - AE2-051 TP 500.0 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TP 500.0 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TP 500.0 SET PRECONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA 500.0 - AE2-051 TP 500.0 END |
Single | AC | 100.99 % | 1058.16 | B | 1068.58 | 20.36 | ||
| DVP |
8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
314911 to 314905 ckt 1 |
DVP_P1-2: LN 594_SRT-S
CONTINGENCY 'DVP_P1-2: LN 594_SRT-S' OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1 /*8MORRSVL 500.0 - 8SPOTSYL 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER 500.0 - 8MORRSVL 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER 500.0 - 8MORRSVL 500.0 END |
Single | AC | 100.78 % | 4070.2 | B | 4101.97 | 50.84 | ||
| DVP |
8SEPTA-8SURRY 500.0 kV Ckt 1 line
314923 to 314924 ckt 1 |
DVP_P1-2: LN 563_SRT-S-1
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S-1' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA 500.0 - AE2-051 TP 500.0 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TP 500.0 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TP 500.0 SET PRECONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA 500.0 - AE2-051 TP 500.0 END |
Single | AC | 100.29 % | 2442.12 | B | 2449.18 | 50.14 | ||
| DVP |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer
314218 to 314908 ckt 1 |
DVP_P4-2: H2T557_SRT-S
CONTINGENCY 'DVP_P4-2: H2T557_SRT-S' OPEN BRANCH FROM BUS 314218 TO BUS 314908 CKT 2 /*6ELMONT 230.0 - 8ELMONT 500.0 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1 /*8CHCKAHM 500.0 - 8ELMONT 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT 500.0 - 8CUNINGHAM 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT 500.0 - 8CUNINGHAM 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 END |
Breaker | AC | 172.23 % | 1065.0 | C | 1834.24 | 146.92 | ||
| DVP |
8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer
314902 to 314282 ckt 2 |
DVP_P4-2: 56372_SRT-S
CONTINGENCY 'DVP_P4-2: 56372_SRT-S' OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1 /*6CARSON 230.0 - 8CARSON 500.0 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TP 500.0 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TP 500.0 END |
Breaker | AC | 159.34 % | 1056.8 | C | 1683.95 | 62.28 | ||
| DVP |
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer
314214 to 314903 ckt 2 |
DVP_P4-2: H1T567_SRT-A
CONTINGENCY 'DVP_P4-2: H1T567_SRT-A' OPEN BRANCH FROM BUS 314214 TO BUS 314903 CKT 1 /*6CHCKAHM 230.0 - 8CHCKAHM 500.0 OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1 /*8CHCKAHM 500.0 - 8SURRY 500.0 END |
Breaker | AC | 124.85 % | 1107.1 | C | 1382.24 | 96.28 | ||
| DVP |
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
314934 to 314916 ckt 1 |
DVP_P4-2: 568T575_SRT-A
CONTINGENCY 'DVP_P4-2: 568T575_SRT-A' OPEN BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH 500.0 - 8POSSUM 500.0 OPEN BRANCH FROM BUS 314911 TO BUS 962840 CKT 1 /*8LADYSMITH 500.0 - AG1-133 TP 500.0 END |
Breaker | AC | 123.51 % | 3940.0 | C | 4866.16 | 147.35 | ||
| DVP |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
314914 to 314918 ckt 1 |
DVP_P4-2: H2T574_SRT-S
CONTINGENCY 'DVP_P4-2: H2T574_SRT-S' OPEN BRANCH FROM BUS 314196 TO BUS 314911 CKT 2 /*6LADYSMITH 230.0 - 8LADYSMITH 500.0 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE 500.0 - 8LADYSMITH 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH 500.0 - 8POSSUM 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE 500.0 - 8LADYSMITH 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH 500.0 - 8POSSUM 500.0 END |
Breaker | AC | 123.05 % | 3940.0 | C | 4848.2 | 243.43 | ||
| DVP |
AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line
962840 to 314911 ckt 1 |
DVP_P4-2: SPOTS H1T594_SRT-S
CONTINGENCY 'DVP_P4-2: SPOTS H1T594_SRT-S' OPEN BRANCH FROM BUS 314755 TO BUS 314934 CKT 1 /*3SPOTSYL 115.0 - 8SPOTSYL 500.0 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1 /*8MORRSVL 500.0 - 8SPOTSYL 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER 500.0 - 8MORRSVL 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER 500.0 - 8MORRSVL 500.0 END |
Breaker | AC | 119.9 % | 3940.0 | C | 4724.16 | 117.61 | ||
| DVP |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
314914 to 314918 ckt 1 |
DVP_P4-2: 557T574_SRT-S
CONTINGENCY 'DVP_P4-2: 557T574_SRT-S' OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1 /*8CHCKAHM 500.0 - 8ELMONT 500.0 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE 500.0 - 8LADYSMITH 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE 500.0 - 8LADYSMITH 500.0 END |
Breaker | DC | 119.17 % | 3940.0 | C | 4695.26 | 260.6 | ||
| DVP |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
314902 to 314914 ckt 1 |
DVP_P4-2: 557T574_SRT-S
CONTINGENCY 'DVP_P4-2: 557T574_SRT-S' OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1 /*8CHCKAHM 500.0 - 8ELMONT 500.0 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE 500.0 - 8LADYSMITH 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE 500.0 - 8LADYSMITH 500.0 END |
Breaker | DC | 119.09 % | 3940.0 | C | 4692.14 | 245.83 | ||
| DVP |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
314924 to 314903 ckt 1 |
DVP_P4-2: 563T576_SRT-S
CONTINGENCY 'DVP_P4-2: 563T576_SRT-S' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN 500.0 - 8NO ANNA 500.0 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TP 500.0 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TP 500.0 END |
Breaker | AC | 118.25 % | 3144.0 | C | 3717.81 | 265.31 | ||
| DVP |
8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line
314916 to 314913 ckt 1 |
DVP_P4-2: 559T584_SRT-S
CONTINGENCY 'DVP_P4-2: 559T584_SRT-S' OPEN BRANCH FROM BUS 314904 TO BUS 314930 CKT 1 /*8CLIFTON 500.0 - 8MOSBY 500.0 OPEN BRANCH FROM BUS 314913 TO BUS 314930 CKT 1 /*8LOUDOUN 500.0 - 8MOSBY 500.0 SET POSTCONTRATING 2809 BRANCH FROM BUS 314913 TO BUS 314916 CKT 1 /*8LOUDOUN 500.0 - 8MORRSVL 500.0 SET PRECONTRATING 2538 BRANCH FROM BUS 314913 TO BUS 314916 CKT 1 /*8LOUDOUN 500.0 - 8MORRSVL 500.0 END |
Breaker | AC | 118.23 % | 2809.0 | C | 3321.05 | 67.42 | ||
| DVP |
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
314918 to 314934 ckt 1 |
DVP_P4-2: 568T575_SRT-A
CONTINGENCY 'DVP_P4-2: 568T575_SRT-A' OPEN BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH 500.0 - 8POSSUM 500.0 OPEN BRANCH FROM BUS 314911 TO BUS 962840 CKT 1 /*8LADYSMITH 500.0 - AG1-133 TP 500.0 END |
Breaker | AC | 118.23 % | 3940.0 | C | 4658.24 | 149.77 | ||
| DVP |
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer
314214 to 314903 ckt 1 |
DVP_P4-2: H4T567_SRT-A
CONTINGENCY 'DVP_P4-2: H4T567_SRT-A' OPEN BRANCH FROM BUS 314214 TO BUS 314903 CKT 2 /*6CHCKAHM 230.0 - 8CHCKAHM 500.0 OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1 /*8CHCKAHM 500.0 - 8SURRY 500.0 END |
Breaker | AC | 118.13 % | 1107.1 | C | 1307.85 | 96.22 | ||
| DVP |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
314924 to 314903 ckt 1 |
DVP_P4-2: 56372_SRT-S
CONTINGENCY 'DVP_P4-2: 56372_SRT-S' OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1 /*6CARSON 230.0 - 8CARSON 500.0 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TP 500.0 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TP 500.0 END |
Breaker | AC | 118.04 % | 3144.0 | C | 3711.09 | 264.55 | ||
| DVP |
8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line
314918 to 962840 ckt 1 |
DVP_P4-2: SPOTS H1T594_SRT-S
CONTINGENCY 'DVP_P4-2: SPOTS H1T594_SRT-S' OPEN BRANCH FROM BUS 314755 TO BUS 314934 CKT 1 /*3SPOTSYL 115.0 - 8SPOTSYL 500.0 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1 /*8MORRSVL 500.0 - 8SPOTSYL 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER 500.0 - 8MORRSVL 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER 500.0 - 8MORRSVL 500.0 END |
Breaker | AC | 117.88 % | 3940.0 | C | 4644.38 | 117.61 | ||
| DVP |
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
314934 to 314916 ckt 1 |
DVP_P4-2: H1T575_SRT-S
CONTINGENCY 'DVP_P4-2: H1T575_SRT-S' OPEN BRANCH FROM BUS 314196 TO BUS 314911 CKT 1 /*6LADYSMITH 230.0 - 8LADYSMITH 500.0 OPEN BRANCH FROM BUS 314911 TO BUS 962840 CKT 1 /*8LADYSMITH 500.0 - AG1-133 TP 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE 500.0 - 8LADYSMITH 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH 500.0 - 8POSSUM 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE 500.0 - 8LADYSMITH 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH 500.0 - 8POSSUM 500.0 END |
Breaker | AC | 117.87 % | 3940.0 | C | 4644.19 | 138.82 | ||
| DVP |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
314902 to 314914 ckt 1 |
DVP_P4-2: H2T574_SRT-S
CONTINGENCY 'DVP_P4-2: H2T574_SRT-S' OPEN BRANCH FROM BUS 314196 TO BUS 314911 CKT 2 /*6LADYSMITH 230.0 - 8LADYSMITH 500.0 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE 500.0 - 8LADYSMITH 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH 500.0 - 8POSSUM 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE 500.0 - 8LADYSMITH 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH 500.0 - 8POSSUM 500.0 END |
Breaker | DC | 116.9 % | 3940.0 | C | 4605.89 | 218.8 | ||
| DVP |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line
314481 to 314486 ckt 1 |
DVP_P4-2: 231T2128_SRT-S
CONTINGENCY 'DVP_P4-2: 231T2128_SRT-S' OPEN BRANCH FROM BUS 314466 TO BUS 314508 CKT 1 /*6FENTRES 230.0 - 6THRASHER 230.0 OPEN BRANCH FROM BUS 314481 TO BUS 314502 CKT 1 /*6LANDSTN 230.0 - 6STUMPY 230.0 OPEN BRANCH FROM BUS 314502 TO BUS 314508 CKT 1 /*6STUMPY 230.0 - 6THRASHER 230.0 OPEN BUS 314502 /*6STUMPY 230.0 SET POSTCONTRATING 1166 BRANCH FROM BUS 314480 TO BUS 314508 CKT 1 /*6HUNTSMN 230.0 - 6THRASHER 230.0 SET PRECONTRATING 1051 BRANCH FROM BUS 314480 TO BUS 314508 CKT 1 /*6HUNTSMN 230.0 - 6THRASHER 230.0 END |
Breaker | AC | 113.9 % | 830.0 | C | 945.39 | 56.54 | ||
| DVP |
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
314918 to 314934 ckt 1 |
DVP_P4-2: H1T575_SRT-S
CONTINGENCY 'DVP_P4-2: H1T575_SRT-S' OPEN BRANCH FROM BUS 314196 TO BUS 314911 CKT 1 /*6LADYSMITH 230.0 - 8LADYSMITH 500.0 OPEN BRANCH FROM BUS 314911 TO BUS 962840 CKT 1 /*8LADYSMITH 500.0 - AG1-133 TP 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE 500.0 - 8LADYSMITH 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH 500.0 - 8POSSUM 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE 500.0 - 8LADYSMITH 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH 500.0 - 8POSSUM 500.0 END |
Breaker | AC | 112.65 % | 3940.0 | C | 4438.32 | 142.36 | ||
| DVP |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
314908 to 314911 ckt 1 |
DVP_P4-2: 57602_SRT-S
CONTINGENCY 'DVP_P4-2: 57602_SRT-S' OPEN BRANCH FROM BUS 314232 TO BUS 314918 CKT 1 /*6NO ANNA 230.0 - 8NO ANNA 500.0 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN 500.0 - 8NO ANNA 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 962840 TO BUS 314918 CKT 1 /*AG1-133 TP 500.0 - 8NO ANNA 500.0 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA 500.0 - 8SPOTSYL 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 962840 TO BUS 314918 CKT 1 /*AG1-133 TP 500.0 - 8NO ANNA 500.0 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA 500.0 - 8SPOTSYL 500.0 END |
Breaker | AC | 112.22 % | 5011.0 | C | 5623.44 | 280.86 | ||
| DVP |
AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line
962840 to 314911 ckt 1 |
DVP_P4-2: H1T573_SRT-A
CONTINGENCY 'DVP_P4-2: H1T573_SRT-A' OPEN BRANCH FROM BUS 314755 TO BUS 314934 CKT 1 /*3SPOTSYL 115.0 - 8SPOTSYL 500.0 OPEN BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA 500.0 - 8SPOTSYL 500.0 END |
Breaker | AC | 111.72 % | 3940.0 | C | 4401.9 | 118.82 | ||
| DVP |
AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line
962840 to 314911 ckt 1 |
DVP_P4-2: 515T573_SRT-A
CONTINGENCY 'DVP_P4-2: 515T573_SRT-A' OPEN BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA 500.0 - 8SPOTSYL 500.0 OPEN BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL 500.0 - 8SPOTSYL EC 500.0 OPEN BUS 314944 /*8SPOTSYL EC 500.0 END |
Breaker | AC | 111.55 % | 3940.0 | C | 4395.24 | 118.45 | ||
| DVP |
8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line
314918 to 962840 ckt 1 |
DVP_P4-2: H1T573_SRT-A
CONTINGENCY 'DVP_P4-2: H1T573_SRT-A' OPEN BRANCH FROM BUS 314755 TO BUS 314934 CKT 1 /*3SPOTSYL 115.0 - 8SPOTSYL 500.0 OPEN BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA 500.0 - 8SPOTSYL 500.0 END |
Breaker | AC | 109.72 % | 3940.0 | C | 4322.98 | 118.82 | ||
| DVP |
8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line
314918 to 962840 ckt 1 |
DVP_P4-2: 515T573_SRT-A
CONTINGENCY 'DVP_P4-2: 515T573_SRT-A' OPEN BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA 500.0 - 8SPOTSYL 500.0 OPEN BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL 500.0 - 8SPOTSYL EC 500.0 OPEN BUS 314944 /*8SPOTSYL EC 500.0 END |
Breaker | AC | 109.55 % | 3940.0 | C | 4316.23 | 118.45 | ||
| DVP |
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
314911 to 314922 ckt 1 |
DVP_P4-2: 545T552_SRT-S
CONTINGENCY 'DVP_P4-2: 545T552_SRT-S' OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1 /*3CHANCE 115.0 - 8CHANCE 500.0 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER 500.0 - 8CHANCE 500.0 OPEN BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER 500.0 - 8MORRSVL 500.0 SET POSTCONTRATING 2831 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE 500.0 - 8LADYSMITH 500.0 SET POSTCONTRATING 3118 BRANCH FROM BUS 314916 TO BUS 314934 CKT 1 /*8MORRSVL 500.0 - 8SPOTSYL 500.0 SET PRECONTRATING 2552 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE 500.0 - 8LADYSMITH 500.0 SET PRECONTRATING 2858 BRANCH FROM BUS 314916 TO BUS 314934 CKT 1 /*8MORRSVL 500.0 - 8SPOTSYL 500.0 END |
Breaker | AC | 108.38 % | 3940.0 | C | 4270.18 | 144.41 | ||
| DVP |
6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line
314537 to 314525 ckt 1 |
DVP_P4-2: 531T582_SRT-A
CONTINGENCY 'DVP_P4-2: 531T582_SRT-A' OPEN BRANCH FROM BUS 314924 TO BUS 314928 CKT 1 /*8SURRY 500.0 - 8SUFFOLK 500.0 OPEN BRANCH FROM BUS 314924 TO BUS 314931 CKT 1 /*8SURRY 500.0 - 8SKIFF CREEK 500.0 END |
Breaker | AC | 104.63 % | 830.0 | C | 868.43 | 56.26 | ||
| DVP |
6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer
314537 to 314928 ckt 2 |
DVP_P4-2: H7T565_SRT-A
CONTINGENCY 'DVP_P4-2: H7T565_SRT-A' OPEN BRANCH FROM BUS 314537 TO BUS 314928 CKT 1 /*6SUFFOLK 230.0 - 8SUFFOLK 500.0 OPEN BRANCH FROM BUS 314927 TO BUS 314928 CKT 1 /*8YADKIN 500.0 - 8SUFFOLK 500.0 END |
Breaker | AC | 102.54 % | 1004.3 | C | 1029.79 | 84.36 | ||
| DVP |
6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line
314525 to 314522 ckt 1 |
DVP_P4-2: 531T582_SRT-A
CONTINGENCY 'DVP_P4-2: 531T582_SRT-A' OPEN BRANCH FROM BUS 314924 TO BUS 314928 CKT 1 /*8SURRY 500.0 - 8SUFFOLK 500.0 OPEN BRANCH FROM BUS 314924 TO BUS 314931 CKT 1 /*8SURRY 500.0 - 8SKIFF CREEK 500.0 END |
Breaker | AC | 102.43 % | 830.0 | C | 850.15 | 56.22 | ||
| DVP |
8BRISTER-8OX 500.0 kV Ckt 1 line
314900 to 314919 ckt 1 |
DVP_P4-2: 541T569_SRT-S
CONTINGENCY 'DVP_P4-2: 541T569_SRT-S' OPEN BRANCH FROM BUS 314913 TO BUS 314916 CKT 1 /*8LOUDOUN 500.0 - 8MORRSVL 500.0 OPEN BRANCH FROM BUS 314916 TO BUS 314929 CKT 1 /*8MORRSVL 500.0 - 8FRONT ROYAL 500.0 END |
Breaker | AC | 100.98 % | 3940.0 | C | 3978.51 | 127.02 | ||
| DVP |
8OX-8CLIFTON 500.0 kV Ckt 1 line
314919 to 314904 ckt 1 |
DVP_P7-1: LN 2101-569_SRT-S
CONTINGENCY 'DVP_P7-1: LN 2101-569_SRT-S' OPEN BRANCH FROM BUS 313712 TO BUS 313716 CKT 1 /*6VINTHIL TP 230.0 - 6VINTHIL DP 230.0 OPEN BRANCH FROM BUS 313712 TO BUS 314119 CKT 1 /*6VINTHIL TP 230.0 - 6NOKESVL 230.0 OPEN BRANCH FROM BUS 313712 TO BUS 314125 CKT 1 /*6VINTHIL TP 230.0 - 6VINTHIL 230.0 OPEN BRANCH FROM BUS 314119 TO BUS 314130 CKT 1 /*6NOKESVL 230.0 - 6BRISTER 230.0 OPEN BRANCH FROM BUS 314913 TO BUS 314916 CKT 1 /*8LOUDOUN 500.0 - 8MORRSVL 500.0 OPEN BUS 313712 /*6VINTHIL TP 230.0 OPEN BUS 313716 /*6VINTHIL DP 230.0 OPEN BUS 314119 /*6NOKESVL 230.0 SET POSTCONTRATING 3118 BRANCH FROM BUS 314916 TO BUS 314929 CKT 1 /*8MORRSVL 500.0 - 8FRONT ROYAL 500.0 SET PRECONTRATING 2858 BRANCH FROM BUS 314916 TO BUS 314929 CKT 1 /*8MORRSVL 500.0 - 8FRONT ROYAL 500.0 END |
Tower | AC | 106.64 % | 3144.0 | C | 3352.73 | 71.72 | ||
| Details for 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 961671 | AG1-007 C | Adder | 0.35 MW | 0.3 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 961941 | AG1-037 C | Adder | 0.2 MW | 0.17 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 962331 | AG1-082 C | Adder | 0.78 MW | 0.67 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 962341 | AG1-083 C | Adder | 0.78 MW | 0.67 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963041 | AG1-153 C | Adder | 2.05 MW | 1.74 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963111 | AG1-160 C | Adder | 2.08 MW | 1.76 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963301 | AG1-179 C | Adder | 2.21 MW | 1.88 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 964801 | AG1-343 C | Adder | 2.36 MW | 2.01 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 966801 | AG1-551 C | Adder | 0.78 MW | 0.66 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 966811 | AG1-552 C | Adder | 0.83 MW | 0.71 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965291 | AG1-394 C | Adder | 0.81 MW | 0.69 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 966361 | AG1-505 C | Adder | 5.98 MW | 5.08 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 966371 | AG1-506 C | Adder | 5.98 MW | 5.08 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 966621 | AG1-532 C | 80/20 | 0.63 MW | 0.63 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 313506 | AB1-173 C OP | 80/20 | 0.41 MW | 0.41 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315131 | 1EDGECMA | Adder | 5.78 MW | 4.92 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315136 | 1ROSEMG1 | 80/20 | 0.75 MW | 0.75 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315137 | 1ROSEMS1 | 80/20 | 0.46 MW | 0.46 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315138 | 1ROSEMG2 | 80/20 | 0.35 MW | 0.35 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315139 | 1GASTONA | 80/20 | 1.14 MW | 1.14 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 934521 | AD1-076 C | Adder | 4.52 MW | 3.84 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 942931 | AE2-313 C | Adder | 13.26 MW | 11.28 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 944011 | AF1-069 C | 80/20 | 4.84 MW | 4.84 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 960081 | AF2-299 C | 80/20 | 1.17 MW | 1.17 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 940571 | AE2-044 C | Adder | 1.62 MW | 1.37 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 941031 | AE2-094 C | 80/20 | 14.82 MW | 14.82 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 946281 | AF1-292 C | 80/20 | 0.7 MW | 0.7 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 957481 | AF2-042 C | Adder | 17.62 MW | 14.98 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 957521 | AF2-046 C | Adder | 6.63 MW | 5.64 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 957531 | AF2-047 C | Adder | 6.24 MW | 5.3 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 957861 | AF2-080 C | Adder | 2.82 MW | 2.4 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 938771 | AE1-103 C | Adder | 1.15 MW | 0.97 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 314314 | 3LOCKS | 80/20 | 0.88 MW | 0.88 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 314507 | 3THOMPSN | Adder | 0.7 MW | 0.6 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315065 | 1CHESTF6 | 80/20 | 26.23 MW | 26.23 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315073 | 1STONECA | 80/20 | 4.77 MW | 4.77 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315076 | 1HOPPOLC | 80/20 | 0.89 MW | 0.89 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315077 | 1HOPHCF1 | 80/20 | 1.42 MW | 1.42 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315078 | 1HOPHCF2 | 80/20 | 1.42 MW | 1.42 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315079 | 1HOPHCF3 | 80/20 | 1.42 MW | 1.42 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315080 | 1HOPHCF4 | 80/20 | 2.16 MW | 2.16 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 942341 | AE2-247 C | 80/20 | 0.71 MW | 0.71 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 943461 | AF1-017 C | 80/20 | 0.64 MW | 0.64 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 944871 | AF1-152 C | Adder | 1.87 MW | 1.59 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315116 | 1SURRY 1 | 80/20 | 9.29 MW | 9.29 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315117 | 1GRAVELC | 80/20 | 0.32 MW | 0.32 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315119 | 1GRAVEL3 | 80/20 | 0.94 MW | 0.94 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315120 | 1GRAVEL4 | 80/20 | 0.95 MW | 0.95 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315121 | 1GRAVEL5 | 80/20 | 0.94 MW | 0.94 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315122 | 1GRAVEL6 | 80/20 | 0.95 MW | 0.95 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315141 | 1GASTONB | 80/20 | 1.14 MW | 1.14 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315260 | 1GOSPORTA | Adder | 0.74 MW | 0.63 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315261 | 1GOSPORTB | Adder | 0.95 MW | 0.81 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315262 | 1GOSPORTC | Adder | 0.81 MW | 0.69 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315611 | 6Z1-036WIND | Adder | 2.43 MW | 2.06 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316108 | AB2-160 C | 80/20 | 2.68 MW | 2.68 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316132 | AB2-190 C | 80/20 | 2.41 MW | 2.41 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 941501 | AE2-147 C | Adder | 5.6 MW | 4.76 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 942001 | AE2-212 C | 80/20 | 2.35 MW | 2.35 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 957871 | AF2-081 C | Adder | 3.43 MW | 2.92 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 958161 | AF2-110 C | Adder | 0.53 MW | 0.45 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 926071 | AC1-086 C | 80/20 | 9.29 MW | 9.29 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 927021 | AC1-189 C | Adder | 3.11 MW | 2.64 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 939411 | AE1-173 C | Adder | 32.68 MW | 27.78 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 934011 | AD1-025 C | 80/20 | 9.39 MW | 9.39 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 933981 | AD1-022 C | Adder | 3.27 MW | 2.78 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 960331 | AF2-324 C | Adder | 2.6 MW | 2.21 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 961681 | AG1-008 C | Adder | 6.64 MW | 5.65 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 962571 | AG1-106 C | 80/20 | 2.58 MW | 2.58 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316011 | AB1-132 C OP | 80/20 | 0.87 MW | 0.87 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316023 | AB2-100 C2 | 80/20 | 0.4 MW | 0.4 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316210 | AC1-098 C | Adder | 2.37 MW | 2.01 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316212 | AC1-099 C | Adder | 0.79 MW | 0.67 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316233 | AE1-074 C | Adder | -0.86 MW | -0.73 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316236 | AE1-162 C | 80/20 | 0.12 MW | 0.12 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316240 | AF1-291 C | 80/20 | 2.78 MW | 2.78 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316263 | AC1-034 C | Adder | 2.47 MW | 2.1 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316274 | AC1-208 C | Adder | 3.5 MW | 2.98 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316301 | AE2-228 C | 80/20 | 2.71 MW | 2.71 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316315 | AB2-025 C | 80/20 | 0.2 MW | 0.2 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316336 | AC2-165 C | Adder | -3.15 MW | -2.68 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316365 | AB2-100 C1 | 80/20 | 0.4 MW | 0.4 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316369 | AC1-216 C | 80/20 | 0.75 MW | 0.75 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963221 | AG1-171 C | 80/20 | 1.2 MW | 1.2 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963231 | AG1-172 C | 80/20 | 1.2 MW | 1.2 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963241 | AG1-173 C | 80/20 | 1.2 MW | 1.2 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963251 | AG1-174 C | 80/20 | 1.2 MW | 1.2 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316181 | AB2-040 GEN | 80/20 | 3.23 MW | 3.23 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316033 | AB2-134 GEN | 80/20 | 0.99 MW | 0.99 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316083 | AB2-161 C | 80/20 | 0.28 MW | 0.28 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316087 | AB2-174 C | 80/20 | 0.43 MW | 0.43 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316311 | AC2-079 C | 80/20 | 2.67 MW | 2.67 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316381 | AD1-082 C | 80/20 | 0.65 MW | 0.65 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316349 | AD2-085 C | 80/20 | 1.64 MW | 1.64 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 961611 | AG1-000B C | 80/20 | 7.56 MW | 7.56 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 941291 | AE2-123 C | Adder | 10.08 MW | 8.56 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 941301 | AE2-124 C | Adder | 9.15 MW | 7.78 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 941591 | AE2-156 C | Adder | 6.24 MW | 5.3 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 942371 | AE2-250 C | 80/20 | 4.76 MW | 4.76 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 942551 | AE2-270 C | 80/20 | 14.94 MW | 14.94 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 944581 | AF1-123 C | Adder | 15.97 MW | 13.57 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 944591 | AF1-124 C | Adder | 15.97 MW | 13.57 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 944601 | AF1-125 C | Adder | 15.97 MW | 13.57 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 946011 | AF1-266 C | 80/20 | 7.74 MW | 7.74 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 957711 | AF2-065 C | 80/20 | 7.62 MW | 7.62 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 961711 | AG1-011 C | 80/20 | 15.95 MW | 15.95 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 962271 | AG1-075 C | 80/20 | 8.21 MW | 8.21 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963291 | AG1-178 C | 80/20 | 23.44 MW | 23.44 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963311 | AG1-180 C | Adder | 1.07 MW | 0.91 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963351 | AG1-184 C | 80/20 | 12.63 MW | 12.63 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 964951 | AG1-359 C | Adder | 7.79 MW | 6.62 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965001 | AG1-364 C | Adder | 2.5 MW | 2.12 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965281 | AG1-393 C | 80/20 | 1.06 MW | 1.06 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965601 | AG1-428 C | Adder | 1.84 MW | 1.56 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965691 | AG1-437 C | Adder | 3.8 MW | 3.23 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965701 | AG1-438 C | Adder | 3.8 MW | 3.23 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965711 | AG1-439 C | Adder | 8.72 MW | 7.41 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965741 | AG1-442 C | Adder | 2.22 MW | 1.89 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965751 | AG1-443 C | Adder | 2.22 MW | 1.89 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965761 | AG1-444 C | Adder | 4.65 MW | 3.95 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965811 | AG1-449 C | Adder | 8.59 MW | 7.3 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 966611 | AG1-531 C | Adder | 1.99 MW | 1.7 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 313764 | 3SOCKMAN | 80/20 | 0.3 MW | 0.3 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 932631 | AC2-084 C | Adder | 2.53 MW | 2.15 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 934321 | AD1-056 C | Adder | 2.52 MW | 2.14 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 934331 | AD1-057 C | Adder | 1.4 MW | 1.19 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 934501 | AD1-074 C | Adder | 12.45 MW | 10.58 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 934511 | AD1-075 C | Adder | 3.11 MW | 2.65 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 935161 | AD1-151 C | 80/20 | 9.44 MW | 9.44 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 938531 | AE1-072 C | Adder | 6.05 MW | 5.14 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 939191 | AE1-149 C | 80/20 | 7.55 MW | 7.55 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 940431 | AE2-027 C | 80/20 | 5.35 MW | 5.35 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 940481 | AE2-033 C | 80/20 | 9.24 MW | 9.24 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 940541 | AE2-040 C | 80/20 | 1.67 MW | 1.67 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 940641 | AE2-051 C | 80/20 | 6.36 MW | 6.36 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 940651 | AE2-052 C | 80/20 | 2.52 MW | 2.52 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 941101 | AE2-104 C | Adder | 1.3 MW | 1.11 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 941281 | AE2-122 C | Adder | 9.8 MW | 8.33 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 944141 | AF1-082 C | Adder | 1.04 MW | 0.88 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 944641 | AF1-129 C | 80/20 | 136.8 MW | 136.8 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 945811 | AF1-246 C | Adder | 2.47 MW | 2.1 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 9.76 MW | 9.76 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 7.0 MW | 7.0 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 30.68 MW | 30.68 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | NY | PJM->LTFIMP_NY | CLTF | 0.48 MW | 0.48 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.39 MW | 0.39 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | WEC | LTFEXP_WEC->PJM | CLTF | 0.2 MW | 0.2 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | CPLE | LTFEXP_CPLE->PJM | CLTF | 3.75 MW | 3.75 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | TVA | LTFEXP_TVA->PJM | CLTF | 1.9 MW | 1.9 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | MEC | LTFEXP_MEC->PJM | CLTF | 1.23 MW | 1.23 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | LAGN | LTFEXP_LAGN->PJM | CLTF | 2.41 MW | 2.41 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.08 MW | 0.08 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.79 MW | 1.79 MW |
| Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 961791 | AG1-021 C | Adder | 1.71 MW | 1.45 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 961891 | AG1-030 C | Adder | 12.84 MW | 10.91 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 961941 | AG1-037 C | Adder | 0.44 MW | 0.38 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 962331 | AG1-082 C | Adder | 1.76 MW | 1.5 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 962341 | AG1-083 C | Adder | 1.76 MW | 1.5 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 963041 | AG1-153 C | 80/20 | 5.55 MW | 5.55 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 963111 | AG1-160 C | 80/20 | 5.62 MW | 5.62 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 963171 | AG1-166 C | Adder | 1.71 MW | 1.45 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 963181 | AG1-167 C | Adder | 1.71 MW | 1.45 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 963191 | AG1-168 C | Adder | 1.71 MW | 1.45 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 963201 | AG1-169 C | Adder | 1.71 MW | 1.45 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 963211 | AG1-170 C | Adder | 1.71 MW | 1.45 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 963301 | AG1-179 C | Adder | 5.08 MW | 4.32 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 964111 | AG1-272 C | Adder | 2.22 MW | 1.88 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 964121 | AG1-273 C | Adder | 2.22 MW | 1.88 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 964131 | AG1-274 C | Adder | 2.22 MW | 1.88 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 964801 | AG1-343 C | Adder | 5.24 MW | 4.45 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 966811 | AG1-552 C | Adder | 1.81 MW | 1.54 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 965191 | AG1-384 C | Adder | 2.22 MW | 1.88 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 965291 | AG1-394 C | Adder | 1.8 MW | 1.53 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 965591 | AG1-427 C | Adder | 10.31 MW | 8.76 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 965721 | AG1-440 C | Adder | 6.57 MW | 5.59 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 965731 | AG1-441 C | Adder | 6.57 MW | 5.59 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 966361 | AG1-505 C | 80/20 | 16.54 MW | 16.54 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 966371 | AG1-506 C | 80/20 | 16.54 MW | 16.54 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 966621 | AG1-532 C | Adder | 1.25 MW | 1.06 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 313853 | 3PONTONDP | Adder | 0.57 MW | 0.48 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315153 | 1CLOVER1 | 80/20 | 10.04 MW | 10.04 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315154 | 1CLOVER2 | 80/20 | 9.95 MW | 9.95 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 934521 | AD1-076 C | Adder | 10.66 MW | 9.06 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 942931 | AE2-313 C | 80/20 | 36.01 MW | 36.01 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 944011 | AF1-069 C | 80/20 | 13.05 MW | 13.05 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 958801 | AF2-171 C | Adder | 12.8 MW | 10.88 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 959311 | AF2-222 C | Adder | 14.34 MW | 12.19 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 960081 | AF2-299 C | Adder | 2.31 MW | 1.97 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 939181 | AE1-148 C | Adder | 7.86 MW | 6.68 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 941031 | AE2-094 C | 80/20 | 39.95 MW | 39.95 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 941791 | AE2-182 C | Adder | 1.77 MW | 1.5 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 946281 | AF1-292 C | Adder | 1.38 MW | 1.17 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 946301 | AF1-294 C | Adder | 3.5 MW | 2.97 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 957481 | AF2-042 C | 80/20 | 51.2 MW | 51.2 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 957521 | AF2-046 C | Adder | 14.81 MW | 12.59 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 957531 | AF2-047 C | Adder | 14.9 MW | 12.67 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 958211 | AF2-115 C | Adder | 2.13 MW | 1.81 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 938771 | AE1-103 C | Adder | 2.56 MW | 2.18 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 314250 | 6ROCKVILLE | Adder | 1.59 MW | 1.35 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 314295 | 6BIRDNECK | 80/20 | 0.03 MW | 0.03 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 314314 | 3LOCKS | Adder | 1.46 MW | 1.24 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 314507 | 3THOMPSN | Adder | 1.76 MW | 1.49 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315083 | 1SPRUNCA | Adder | 7.55 MW | 6.42 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315084 | 1SPRUNCB | Adder | 7.55 MW | 6.42 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 934861 | AD1-115 C | Adder | 2.85 MW | 2.42 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 942341 | AE2-247 C | Adder | 1.3 MW | 1.1 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 943461 | AF1-017 C | Adder | 1.17 MW | 1.0 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 944871 | AF1-152 C | Adder | 4.61 MW | 3.92 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315102 | 1BRUNSWICKG1 | 80/20 | 6.91 MW | 6.91 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315103 | 1BRUNSWICKG2 | 80/20 | 6.91 MW | 6.91 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315104 | 1BRUNSWICKG3 | 80/20 | 6.91 MW | 6.91 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315105 | 1BRUNSWICKS1 | 80/20 | 14.36 MW | 14.36 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315108 | 1ELIZAR1 | 80/20 | 2.35 MW | 2.35 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315109 | 1ELIZAR2 | 80/20 | 2.31 MW | 2.31 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315110 | 1ELIZAR3 | 80/20 | 2.38 MW | 2.38 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315172 | 1LOISA A | 80/20 | 2.28 MW | 2.28 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315173 | 1LOISA B | 80/20 | 2.29 MW | 2.29 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315174 | 1LOISA C | 80/20 | 2.29 MW | 2.29 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315175 | 1LOISA D | 80/20 | 2.29 MW | 2.29 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315176 | 1LOISA E | 80/20 | 4.67 MW | 4.67 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315177 | 1S ANNAG1 | 80/20 | 2.24 MW | 2.24 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315178 | 1S ANNAS1 | 80/20 | 1.15 MW | 1.15 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315179 | 1S ANNAG2 | 80/20 | 2.24 MW | 2.24 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315180 | 1S ANNAS2 | 80/20 | 1.15 MW | 1.15 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315225 | 1N ANNA1 | 80/20 | 75.42 MW | 75.42 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315226 | 1N ANNA2 | 80/20 | 75.42 MW | 75.42 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315241 | 1Z1-086 GT1 | 80/20 | 8.85 MW | 8.85 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315242 | 1Z1-086 GT2 | 80/20 | 8.86 MW | 8.86 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315243 | 1Z1-086 GT3 | 80/20 | 8.86 MW | 8.86 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315244 | 1Z1-086 ST | 80/20 | 15.42 MW | 15.42 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315260 | 1GOSPORTA | Adder | 1.85 MW | 1.58 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315261 | 1GOSPORTB | Adder | 2.37 MW | 2.01 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315262 | 1GOSPORTC | Adder | 2.01 MW | 1.71 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315611 | 6Z1-036WIND | Adder | 5.93 MW | 5.04 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 316108 | AB2-160 C | Adder | 4.44 MW | 3.77 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 946371 | AF1-301 C | 80/20 | 18.11 MW | 18.11 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 964271 | AG1-288 C | 80/20 | 33.73 MW | 33.73 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 966001 | AG1-469 C | 80/20 | 1.96 MW | 1.96 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 941501 | AE2-147 C | Adder | 13.83 MW | 11.75 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 942001 | AE2-212 C | Adder | 1.81 MW | 1.54 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 957871 | AF2-081 C | Adder | 8.72 MW | 7.42 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 958161 | AF2-110 C | Adder | 1.19 MW | 1.01 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 966331 | AG1-502 C | 80/20 | 14.27 MW | 14.27 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 966341 | AG1-503 C | 80/20 | 3.57 MW | 3.57 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 926071 | AC1-086 C | Adder | 18.51 MW | 15.74 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 936261 | AD2-033 C | Adder | 11.23 MW | 9.55 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 933291 | AC2-141 C | 80/20 | 26.51 MW | 26.51 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 934621 | AD1-088 C | Adder | 10.88 MW | 9.25 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 939411 | AE1-173 C | 80/20 | 88.02 MW | 88.02 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 933981 | AD1-022 C | Adder | 7.63 MW | 6.49 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 961681 | AG1-008 C | Adder | 14.84 MW | 12.62 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 962571 | AG1-106 C | Adder | 5.15 MW | 4.38 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 208900 | BRIS G1 | 80/20 | -2.23 MW | -2.23 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 208901 | BRIS G2 | 80/20 | -2.64 MW | -2.64 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 316023 | AB2-100 C2 | 80/20 | 0.73 MW | 0.73 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 316164 | AC1-076_C | 80/20 | 0.94 MW | 0.94 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 316170 | AC1-121 C | 80/20 | 2.72 MW | 2.72 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 316185 | AD1-033 C | 80/20 | 0.91 MW | 0.91 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 316192 | AB2-158 C | 80/20 | 3.09 MW | 3.09 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 316233 | AE1-074 C | 80/20 | 2.4 MW | 2.4 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 316240 | AF1-291 C | Adder | 1.73 MW | 1.47 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 316254 | AC1-120 C | 80/20 | 7.92 MW | 7.92 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 316257 | AC1-043 C | Adder | 5.69 MW | 4.84 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 316258 | AE1-075 C | 80/20 | 0.29 MW | 0.29 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 316294 | AC1-161 C | 80/20 | 3.66 MW | 3.66 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 316301 | AE2-228 C | Adder | 1.74 MW | 1.48 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 316313 | AB2-026 C | 80/20 | 0.32 MW | 0.32 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 316315 | AB2-025 C | 80/20 | 0.32 MW | 0.32 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 316316 | AC1-027 C | 80/20 | 0.23 MW | 0.23 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 316336 | AC2-165 C | 80/20 | 9.51 MW | 9.51 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 316365 | AB2-100 C1 | 80/20 | 0.73 MW | 0.73 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 316405 | AF2-144 C | 80/20 | 0.25 MW | 0.25 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 316181 | AB2-040 GEN | Adder | 6.66 MW | 5.67 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 316044 | AC1-158 C1 | 80/20 | 16.55 MW | 16.55 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 316045 | AC1-158 C2 | 80/20 | 16.55 MW | 16.55 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 316311 | AC2-079 C | Adder | 4.98 MW | 4.24 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 316349 | AD2-085 C | Adder | 2.99 MW | 2.54 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 316388 | AE2-253 GEN | 80/20 | 1.45 MW | 1.45 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 961611 | AG1-000B C | Adder | 12.82 MW | 10.9 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 940661 | AE2-053 C | Adder | 2.91 MW | 2.48 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 941291 | AE2-123 C | 80/20 | 25.5 MW | 25.5 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 941301 | AE2-124 C | 80/20 | 23.19 MW | 23.19 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 941591 | AE2-156 C | Adder | 15.59 MW | 13.25 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 942371 | AE2-250 C | Adder | 7.88 MW | 6.7 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 944581 | AF1-123 C | 80/20 | 42.16 MW | 42.16 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 944591 | AF1-124 C | 80/20 | 42.16 MW | 42.16 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 944601 | AF1-125 C | 80/20 | 42.16 MW | 42.16 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 946011 | AF1-266 C | 80/20 | 12.43 MW | 12.43 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 957431 | AF2-037 C | 80/20 | 23.79 MW | 23.79 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 957691 | AF2-063 C | 80/20 | 37.96 MW | 37.96 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 962271 | AG1-075 C | Adder | 13.6 MW | 11.56 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 962491 | AG1-098 C | Adder | 9.79 MW | 8.32 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 962841 | AG1-133 C | 80/20 | 44.26 MW | 44.26 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 963291 | AG1-178 C | 80/20 | 62.96 MW | 62.96 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 963311 | AG1-180 C | Adder | 2.47 MW | 2.1 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 963321 | AG1-181 C | Adder | 14.55 MW | 12.37 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 963351 | AG1-184 C | 80/20 | 33.92 MW | 33.92 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 963361 | AG1-185 C | Adder | 7.04 MW | 5.98 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 964241 | AG1-285 C | Adder | 10.86 MW | 9.23 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 964281 | AG1-289 C | 80/20 | 18.65 MW | 18.65 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 964421 | AG1-305 C | 80/20 | 29.86 MW | 29.86 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 964951 | AG1-359 C | 80/20 | 19.95 MW | 19.95 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 965001 | AG1-364 C | Adder | 6.23 MW | 5.3 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 965281 | AG1-393 C | Adder | 1.75 MW | 1.49 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 965601 | AG1-428 C | Adder | 4.24 MW | 3.6 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 965691 | AG1-437 C | Adder | 8.83 MW | 7.5 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 965701 | AG1-438 C | Adder | 8.83 MW | 7.5 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 965741 | AG1-442 C | Adder | 5.15 MW | 4.38 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 965751 | AG1-443 C | Adder | 5.15 MW | 4.38 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 965771 | AG1-445 C | Adder | 3.8 MW | 3.23 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 965781 | AG1-446 C | Adder | 3.8 MW | 3.23 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 965811 | AG1-449 C | 80/20 | 23.32 MW | 23.32 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 313764 | 3SOCKMAN | Adder | 0.63 MW | 0.54 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 934501 | AD1-074 C | Adder | 29.36 MW | 24.96 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 934511 | AD1-075 C | Adder | 7.34 MW | 6.24 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 934611 | AD1-087 C | 80/20 | 0.99 MW | 0.99 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 937481 | AD2-202 C | 80/20 | 0.29 MW | 0.29 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 938531 | AE1-072 C | Adder | 15.34 MW | 13.04 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 939191 | AE1-149 C | Adder | 9.21 MW | 7.83 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 940431 | AE2-027 C | Adder | 10.37 MW | 8.81 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 940481 | AE2-033 C | 80/20 | 14.85 MW | 14.85 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 940541 | AE2-040 C | 80/20 | 2.64 MW | 2.64 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 940641 | AE2-051 C | 80/20 | 17.3 MW | 17.3 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 940651 | AE2-052 C | Adder | 3.07 MW | 2.61 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 941101 | AE2-104 C | Adder | 2.92 MW | 2.48 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 941281 | AE2-122 C | 80/20 | 24.81 MW | 24.81 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 945811 | AF1-246 C | 80/20 | 7.17 MW | 7.17 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 316303 | AF2-085 | 80/20 | 4.16 MW | 4.16 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 21.64 MW | 21.64 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 18.37 MW | 18.37 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 83.3 MW | 83.3 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | NY | PJM->LTFIMP_NY | CLTF | 2.54 MW | 2.54 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.96 MW | 0.96 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | WEC | LTFEXP_WEC->PJM | CLTF | 0.47 MW | 0.47 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | CPLE | LTFEXP_CPLE->PJM | CLTF | 9.94 MW | 9.94 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | TVA | LTFEXP_TVA->PJM | CLTF | 5.17 MW | 5.17 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | MEC | LTFEXP_MEC->PJM | CLTF | 3.03 MW | 3.03 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | LAGN | LTFEXP_LAGN->PJM | CLTF | 6.5 MW | 6.5 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.19 MW | 0.19 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 4.74 MW | 4.74 MW |
| Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 961791 | AG1-021 C | Adder | 1.71 MW | 1.45 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 961891 | AG1-030 C | Adder | 12.84 MW | 10.91 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 961941 | AG1-037 C | Adder | 0.44 MW | 0.38 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 962331 | AG1-082 C | Adder | 1.76 MW | 1.5 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 962341 | AG1-083 C | Adder | 1.76 MW | 1.5 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 963041 | AG1-153 C | 80/20 | 5.55 MW | 5.55 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 963111 | AG1-160 C | 80/20 | 5.62 MW | 5.62 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 963171 | AG1-166 C | Adder | 1.71 MW | 1.45 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 963181 | AG1-167 C | Adder | 1.71 MW | 1.45 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 963191 | AG1-168 C | Adder | 1.71 MW | 1.45 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 963201 | AG1-169 C | Adder | 1.71 MW | 1.45 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 963211 | AG1-170 C | Adder | 1.71 MW | 1.45 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 963301 | AG1-179 C | Adder | 5.08 MW | 4.32 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 964111 | AG1-272 C | Adder | 2.22 MW | 1.88 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 964121 | AG1-273 C | Adder | 2.22 MW | 1.88 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 964131 | AG1-274 C | Adder | 2.22 MW | 1.88 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 964801 | AG1-343 C | Adder | 5.24 MW | 4.45 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 966811 | AG1-552 C | Adder | 1.81 MW | 1.54 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 965191 | AG1-384 C | Adder | 2.22 MW | 1.88 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 965291 | AG1-394 C | Adder | 1.8 MW | 1.53 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 965591 | AG1-427 C | Adder | 10.31 MW | 8.76 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 965721 | AG1-440 C | Adder | 6.57 MW | 5.59 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 965731 | AG1-441 C | Adder | 6.57 MW | 5.59 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 966361 | AG1-505 C | 80/20 | 16.54 MW | 16.54 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 966371 | AG1-506 C | 80/20 | 16.54 MW | 16.54 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 966621 | AG1-532 C | Adder | 1.25 MW | 1.06 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 313853 | 3PONTONDP | Adder | 0.57 MW | 0.48 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315153 | 1CLOVER1 | 80/20 | 10.04 MW | 10.04 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315154 | 1CLOVER2 | 80/20 | 9.95 MW | 9.95 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 934521 | AD1-076 C | Adder | 10.66 MW | 9.06 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 942931 | AE2-313 C | 80/20 | 36.01 MW | 36.01 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 944011 | AF1-069 C | 80/20 | 13.05 MW | 13.05 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 958801 | AF2-171 C | Adder | 12.8 MW | 10.88 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 959311 | AF2-222 C | Adder | 14.34 MW | 12.19 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 960081 | AF2-299 C | Adder | 2.31 MW | 1.97 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 939181 | AE1-148 C | Adder | 7.86 MW | 6.68 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 941031 | AE2-094 C | 80/20 | 39.95 MW | 39.95 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 941791 | AE2-182 C | Adder | 1.77 MW | 1.5 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 946281 | AF1-292 C | Adder | 1.38 MW | 1.17 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 946301 | AF1-294 C | Adder | 3.5 MW | 2.97 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 957481 | AF2-042 C | 80/20 | 51.2 MW | 51.2 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 957521 | AF2-046 C | Adder | 14.81 MW | 12.59 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 957531 | AF2-047 C | Adder | 14.9 MW | 12.67 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 958211 | AF2-115 C | Adder | 2.13 MW | 1.81 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 938771 | AE1-103 C | Adder | 2.56 MW | 2.18 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 314250 | 6ROCKVILLE | Adder | 1.59 MW | 1.35 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 314295 | 6BIRDNECK | 80/20 | 0.03 MW | 0.03 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 314314 | 3LOCKS | Adder | 1.46 MW | 1.24 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 314507 | 3THOMPSN | Adder | 1.76 MW | 1.49 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315083 | 1SPRUNCA | Adder | 7.55 MW | 6.42 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315084 | 1SPRUNCB | Adder | 7.55 MW | 6.42 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 934861 | AD1-115 C | Adder | 2.85 MW | 2.42 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 942341 | AE2-247 C | Adder | 1.3 MW | 1.1 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 943461 | AF1-017 C | Adder | 1.17 MW | 1.0 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 944871 | AF1-152 C | Adder | 4.61 MW | 3.92 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315102 | 1BRUNSWICKG1 | 80/20 | 6.91 MW | 6.91 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315103 | 1BRUNSWICKG2 | 80/20 | 6.91 MW | 6.91 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315104 | 1BRUNSWICKG3 | 80/20 | 6.91 MW | 6.91 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315105 | 1BRUNSWICKS1 | 80/20 | 14.36 MW | 14.36 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315108 | 1ELIZAR1 | 80/20 | 2.35 MW | 2.35 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315109 | 1ELIZAR2 | 80/20 | 2.31 MW | 2.31 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315110 | 1ELIZAR3 | 80/20 | 2.38 MW | 2.38 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315172 | 1LOISA A | 80/20 | 2.28 MW | 2.28 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315173 | 1LOISA B | 80/20 | 2.29 MW | 2.29 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315174 | 1LOISA C | 80/20 | 2.29 MW | 2.29 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315175 | 1LOISA D | 80/20 | 2.29 MW | 2.29 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315176 | 1LOISA E | 80/20 | 4.67 MW | 4.67 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315177 | 1S ANNAG1 | 80/20 | 2.24 MW | 2.24 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315178 | 1S ANNAS1 | 80/20 | 1.15 MW | 1.15 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315179 | 1S ANNAG2 | 80/20 | 2.24 MW | 2.24 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315180 | 1S ANNAS2 | 80/20 | 1.15 MW | 1.15 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315225 | 1N ANNA1 | 80/20 | 75.42 MW | 75.42 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315226 | 1N ANNA2 | 80/20 | 75.42 MW | 75.42 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315241 | 1Z1-086 GT1 | 80/20 | 8.85 MW | 8.85 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315242 | 1Z1-086 GT2 | 80/20 | 8.86 MW | 8.86 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315243 | 1Z1-086 GT3 | 80/20 | 8.86 MW | 8.86 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315244 | 1Z1-086 ST | 80/20 | 15.42 MW | 15.42 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315260 | 1GOSPORTA | Adder | 1.85 MW | 1.58 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315261 | 1GOSPORTB | Adder | 2.37 MW | 2.01 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315262 | 1GOSPORTC | Adder | 2.01 MW | 1.71 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315611 | 6Z1-036WIND | Adder | 5.93 MW | 5.04 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 316108 | AB2-160 C | Adder | 4.44 MW | 3.77 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 946371 | AF1-301 C | 80/20 | 18.11 MW | 18.11 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 964271 | AG1-288 C | 80/20 | 33.73 MW | 33.73 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 966001 | AG1-469 C | 80/20 | 1.96 MW | 1.96 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 941501 | AE2-147 C | Adder | 13.83 MW | 11.75 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 942001 | AE2-212 C | Adder | 1.81 MW | 1.54 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 957871 | AF2-081 C | Adder | 8.72 MW | 7.42 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 958161 | AF2-110 C | Adder | 1.19 MW | 1.01 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 966331 | AG1-502 C | 80/20 | 14.27 MW | 14.27 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 966341 | AG1-503 C | 80/20 | 3.57 MW | 3.57 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 926071 | AC1-086 C | Adder | 18.51 MW | 15.74 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 936261 | AD2-033 C | Adder | 11.23 MW | 9.55 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 933291 | AC2-141 C | 80/20 | 26.51 MW | 26.51 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 934621 | AD1-088 C | Adder | 10.88 MW | 9.25 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 939411 | AE1-173 C | 80/20 | 88.02 MW | 88.02 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 933981 | AD1-022 C | Adder | 7.63 MW | 6.49 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 961681 | AG1-008 C | Adder | 14.84 MW | 12.62 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 962571 | AG1-106 C | Adder | 5.15 MW | 4.38 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 208900 | BRIS G1 | 80/20 | -2.23 MW | -2.23 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 208901 | BRIS G2 | 80/20 | -2.64 MW | -2.64 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 316023 | AB2-100 C2 | 80/20 | 0.73 MW | 0.73 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 316164 | AC1-076_C | 80/20 | 0.94 MW | 0.94 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 316170 | AC1-121 C | 80/20 | 2.72 MW | 2.72 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 316185 | AD1-033 C | 80/20 | 0.91 MW | 0.91 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 316192 | AB2-158 C | 80/20 | 3.09 MW | 3.09 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 316233 | AE1-074 C | 80/20 | 2.4 MW | 2.4 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 316240 | AF1-291 C | Adder | 1.73 MW | 1.47 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 316254 | AC1-120 C | 80/20 | 7.92 MW | 7.92 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 316257 | AC1-043 C | Adder | 5.69 MW | 4.84 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 316258 | AE1-075 C | 80/20 | 0.29 MW | 0.29 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 316294 | AC1-161 C | 80/20 | 3.66 MW | 3.66 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 316301 | AE2-228 C | Adder | 1.74 MW | 1.48 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 316313 | AB2-026 C | 80/20 | 0.32 MW | 0.32 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 316315 | AB2-025 C | 80/20 | 0.32 MW | 0.32 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 316316 | AC1-027 C | 80/20 | 0.23 MW | 0.23 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 316336 | AC2-165 C | 80/20 | 9.51 MW | 9.51 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 316365 | AB2-100 C1 | 80/20 | 0.73 MW | 0.73 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 316405 | AF2-144 C | 80/20 | 0.25 MW | 0.25 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 316181 | AB2-040 GEN | Adder | 6.66 MW | 5.67 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 316044 | AC1-158 C1 | 80/20 | 16.55 MW | 16.55 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 316045 | AC1-158 C2 | 80/20 | 16.55 MW | 16.55 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 316311 | AC2-079 C | Adder | 4.98 MW | 4.24 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 316349 | AD2-085 C | Adder | 2.99 MW | 2.54 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 316388 | AE2-253 GEN | 80/20 | 1.45 MW | 1.45 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 961611 | AG1-000B C | Adder | 12.82 MW | 10.9 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 940661 | AE2-053 C | Adder | 2.91 MW | 2.48 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 941291 | AE2-123 C | 80/20 | 25.5 MW | 25.5 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 941301 | AE2-124 C | 80/20 | 23.19 MW | 23.19 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 941591 | AE2-156 C | Adder | 15.59 MW | 13.25 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 942371 | AE2-250 C | Adder | 7.88 MW | 6.7 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 944581 | AF1-123 C | 80/20 | 42.16 MW | 42.16 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 944591 | AF1-124 C | 80/20 | 42.16 MW | 42.16 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 944601 | AF1-125 C | 80/20 | 42.16 MW | 42.16 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 946011 | AF1-266 C | 80/20 | 12.43 MW | 12.43 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 957431 | AF2-037 C | 80/20 | 23.79 MW | 23.79 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 957691 | AF2-063 C | 80/20 | 37.96 MW | 37.96 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 962271 | AG1-075 C | Adder | 13.6 MW | 11.56 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 962491 | AG1-098 C | Adder | 9.79 MW | 8.32 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 963291 | AG1-178 C | 80/20 | 62.96 MW | 62.96 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 963311 | AG1-180 C | Adder | 2.47 MW | 2.1 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 963321 | AG1-181 C | Adder | 14.55 MW | 12.37 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 963351 | AG1-184 C | 80/20 | 33.92 MW | 33.92 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 963361 | AG1-185 C | Adder | 7.04 MW | 5.98 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 964241 | AG1-285 C | Adder | 10.86 MW | 9.23 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 964281 | AG1-289 C | 80/20 | 18.65 MW | 18.65 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 964421 | AG1-305 C | 80/20 | 29.86 MW | 29.86 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 964951 | AG1-359 C | 80/20 | 19.95 MW | 19.95 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 965001 | AG1-364 C | Adder | 6.23 MW | 5.3 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 965281 | AG1-393 C | Adder | 1.75 MW | 1.49 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 965601 | AG1-428 C | Adder | 4.24 MW | 3.6 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 965691 | AG1-437 C | Adder | 8.83 MW | 7.5 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 965701 | AG1-438 C | Adder | 8.83 MW | 7.5 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 965741 | AG1-442 C | Adder | 5.15 MW | 4.38 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 965751 | AG1-443 C | Adder | 5.15 MW | 4.38 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 965771 | AG1-445 C | Adder | 3.8 MW | 3.23 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 965781 | AG1-446 C | Adder | 3.8 MW | 3.23 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 965811 | AG1-449 C | 80/20 | 23.32 MW | 23.32 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 313764 | 3SOCKMAN | Adder | 0.63 MW | 0.54 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 934501 | AD1-074 C | Adder | 29.36 MW | 24.96 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 934511 | AD1-075 C | Adder | 7.34 MW | 6.24 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 934611 | AD1-087 C | 80/20 | 0.99 MW | 0.99 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 937481 | AD2-202 C | 80/20 | 0.29 MW | 0.29 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 938531 | AE1-072 C | Adder | 15.34 MW | 13.04 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 939191 | AE1-149 C | Adder | 9.21 MW | 7.83 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 940431 | AE2-027 C | Adder | 10.37 MW | 8.81 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 940481 | AE2-033 C | 80/20 | 14.85 MW | 14.85 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 940541 | AE2-040 C | 80/20 | 2.64 MW | 2.64 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 940641 | AE2-051 C | 80/20 | 17.3 MW | 17.3 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 940651 | AE2-052 C | Adder | 3.07 MW | 2.61 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 941101 | AE2-104 C | Adder | 2.92 MW | 2.48 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 941281 | AE2-122 C | 80/20 | 24.81 MW | 24.81 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 944641 | AF1-129 C | Adder | 41.2 MW | 35.02 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 945811 | AF1-246 C | 80/20 | 7.17 MW | 7.17 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 316303 | AF2-085 | 80/20 | 4.16 MW | 4.16 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 21.64 MW | 21.64 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 18.37 MW | 18.37 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 83.3 MW | 83.3 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | NY | PJM->LTFIMP_NY | CLTF | 2.54 MW | 2.54 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.96 MW | 0.96 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | WEC | LTFEXP_WEC->PJM | CLTF | 0.47 MW | 0.47 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | CPLE | LTFEXP_CPLE->PJM | CLTF | 9.94 MW | 9.94 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | TVA | LTFEXP_TVA->PJM | CLTF | 5.17 MW | 5.17 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | MEC | LTFEXP_MEC->PJM | CLTF | 3.03 MW | 3.03 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | LAGN | LTFEXP_LAGN->PJM | CLTF | 6.5 MW | 6.5 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.19 MW | 0.19 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 4.74 MW | 4.74 MW |
| Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 961941 | AG1-037 C | Adder | 0.75 MW | 0.64 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 962331 | AG1-082 C | Adder | 2.99 MW | 2.54 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 962341 | AG1-083 C | Adder | 2.99 MW | 2.54 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 963041 | AG1-153 C | 80/20 | 8.84 MW | 8.84 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 963111 | AG1-160 C | 80/20 | 8.95 MW | 8.95 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 963301 | AG1-179 C | Adder | 8.25 MW | 7.01 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 964801 | AG1-343 C | Adder | 8.87 MW | 7.54 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 966801 | AG1-551 C | Adder | 3.08 MW | 2.62 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 966811 | AG1-552 C | Adder | 3.01 MW | 2.56 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 965291 | AG1-394 C | Adder | 3.04 MW | 2.59 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 965721 | AG1-440 C | Adder | 10.6 MW | 9.01 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 965731 | AG1-441 C | Adder | 10.6 MW | 9.01 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 966361 | AG1-505 C | 80/20 | 26.3 MW | 26.3 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 966371 | AG1-506 C | 80/20 | 26.3 MW | 26.3 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 966621 | AG1-532 C | Adder | 2.06 MW | 1.75 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 934521 | AD1-076 C | Adder | 18.24 MW | 15.5 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 942931 | AE2-313 C | 80/20 | 57.24 MW | 57.24 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 944011 | AF1-069 C | 80/20 | 20.76 MW | 20.76 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 960081 | AF2-299 C | Adder | 3.82 MW | 3.25 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 941031 | AE2-094 C | 80/20 | 63.54 MW | 63.54 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 946281 | AF1-292 C | Adder | 2.28 MW | 1.94 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 957481 | AF2-042 C | Adder | 81.3 MW | 69.11 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 957521 | AF2-046 C | Adder | 25.08 MW | 21.32 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 957531 | AF2-047 C | Adder | 25.57 MW | 21.74 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 938771 | AE1-103 C | Adder | 4.4 MW | 3.74 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 314250 | 6ROCKVILLE | Adder | 2.82 MW | 2.39 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 314295 | 6BIRDNECK | 80/20 | 0.06 MW | 0.06 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 314314 | 3LOCKS | Adder | 2.58 MW | 2.19 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 314507 | 3THOMPSN | Adder | 3.06 MW | 2.6 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 315060 | 1CHESTF5 | Adder | 83.08 MW | 70.61 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 315065 | 1CHESTF6 | Adder | 27.73 MW | 23.57 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 315073 | 1STONECA | Adder | 9.6 MW | 8.16 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 315083 | 1SPRUNCA | Adder | 13.17 MW | 11.19 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 315084 | 1SPRUNCB | Adder | 13.17 MW | 11.19 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 315092 | 1YORKTN3 | Adder | 196.05 MW | 166.64 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 942341 | AE2-247 C | Adder | 2.25 MW | 1.91 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 943461 | AF1-017 C | Adder | 2.03 MW | 1.73 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 944871 | AF1-152 C | Adder | 7.97 MW | 6.78 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 315098 | 1CHESPKA | 80/20 | 0.56 MW | 0.56 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 315099 | 1CHESPKB | 80/20 | 0.93 MW | 0.93 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 315102 | 1BRUNSWICKG1 | 80/20 | 11.02 MW | 11.02 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 315103 | 1BRUNSWICKG2 | 80/20 | 11.02 MW | 11.02 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 315104 | 1BRUNSWICKG3 | 80/20 | 11.02 MW | 11.02 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 315105 | 1BRUNSWICKS1 | 80/20 | 22.89 MW | 22.89 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 315108 | 1ELIZAR1 | 80/20 | 4.1 MW | 4.1 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 315109 | 1ELIZAR2 | 80/20 | 4.03 MW | 4.03 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 315110 | 1ELIZAR3 | 80/20 | 4.15 MW | 4.15 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 315241 | 1Z1-086 GT1 | 80/20 | 14.1 MW | 14.1 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 315242 | 1Z1-086 GT2 | 80/20 | 14.11 MW | 14.11 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 315243 | 1Z1-086 GT3 | 80/20 | 14.11 MW | 14.11 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 315244 | 1Z1-086 ST | 80/20 | 24.56 MW | 24.56 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 315260 | 1GOSPORTA | 80/20 | 3.23 MW | 3.23 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 315261 | 1GOSPORTB | 80/20 | 4.12 MW | 4.12 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 315262 | 1GOSPORTC | 80/20 | 3.5 MW | 3.5 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 315611 | 6Z1-036WIND | Adder | 10.24 MW | 8.7 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 316108 | AB2-160 C | Adder | 7.85 MW | 6.67 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 941501 | AE2-147 C | Adder | 23.92 MW | 20.34 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 942001 | AE2-212 C | Adder | 3.16 MW | 2.69 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 957871 | AF2-081 C | Adder | 15.14 MW | 12.87 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 958161 | AF2-110 C | Adder | 2.07 MW | 1.76 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 926071 | AC1-086 C | Adder | 30.92 MW | 26.28 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 933291 | AC2-141 C | 80/20 | 46.31 MW | 46.31 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 939411 | AE1-173 C | 80/20 | 144.21 MW | 144.21 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 934011 | AD1-025 C | Adder | 24.03 MW | 20.42 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 933981 | AD1-022 C | Adder | 13.03 MW | 11.08 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 961681 | AG1-008 C | Adder | 25.13 MW | 21.36 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 962571 | AG1-106 C | Adder | 8.6 MW | 7.31 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 316036 | AC1-147 C | 80/20 | 0.47 MW | 0.47 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 316185 | AD1-033 C | 80/20 | 1.57 MW | 1.57 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 316210 | AC1-098 C | Adder | 8.93 MW | 7.59 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 316212 | AC1-099 C | Adder | 2.99 MW | 2.54 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 316233 | AE1-074 C | 80/20 | 3.92 MW | 3.92 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 316240 | AF1-291 C | Adder | 3.08 MW | 2.61 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 316274 | AC1-208 C | Adder | 13.11 MW | 11.15 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 316294 | AC1-161 C | 80/20 | 6.39 MW | 6.39 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 316301 | AE2-228 C | Adder | 3.08 MW | 2.62 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 316304 | AE2-227 C | Adder | 2.89 MW | 2.45 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 316315 | AB2-025 C | 80/20 | 0.52 MW | 0.52 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 316316 | AC1-027 C | 80/20 | 0.41 MW | 0.41 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 316336 | AC2-165 C | Adder | 13.92 MW | 11.83 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 963221 | AG1-171 C | Adder | 3.06 MW | 2.6 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 963231 | AG1-172 C | Adder | 3.06 MW | 2.6 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 963241 | AG1-173 C | Adder | 3.06 MW | 2.6 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 963251 | AG1-174 C | Adder | 3.06 MW | 2.6 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 316181 | AB2-040 GEN | Adder | 11.04 MW | 9.38 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 316375 | AC2-012 C | 80/20 | 1.74 MW | 1.74 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 316311 | AC2-079 C | Adder | 8.64 MW | 7.34 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 316349 | AD2-085 C | Adder | 5.18 MW | 4.4 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 961611 | AG1-000B C | Adder | 22.98 MW | 19.53 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 941291 | AE2-123 C | 80/20 | 44.35 MW | 44.35 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 941301 | AE2-124 C | 80/20 | 40.34 MW | 40.34 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 941591 | AE2-156 C | 80/20 | 27.15 MW | 27.15 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 942371 | AE2-250 C | Adder | 13.94 MW | 11.85 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 942551 | AE2-270 C | Adder | 38.26 MW | 32.52 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 944581 | AF1-123 C | 80/20 | 73.2 MW | 73.2 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 944591 | AF1-124 C | 80/20 | 73.2 MW | 73.2 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 944601 | AF1-125 C | 80/20 | 73.2 MW | 73.2 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 944631 | AF1-128 C | Adder | 51.98 MW | 44.18 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 945361 | AF1-201 C | Adder | 21.36 MW | 18.16 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 946011 | AF1-266 C | 80/20 | 20.57 MW | 20.57 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 957711 | AF2-065 C | Adder | 19.51 MW | 16.59 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 961711 | AG1-011 C | Adder | 40.81 MW | 34.69 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 962271 | AG1-075 C | Adder | 24.06 MW | 20.45 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 963291 | AG1-178 C | 80/20 | 101.1 MW | 101.1 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 963311 | AG1-180 C | Adder | 4.01 MW | 3.4 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 963351 | AG1-184 C | 80/20 | 54.47 MW | 54.47 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 964951 | AG1-359 C | 80/20 | 34.66 MW | 34.66 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 965001 | AG1-364 C | 80/20 | 10.86 MW | 10.86 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 965281 | AG1-393 C | Adder | 3.1 MW | 2.63 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 965601 | AG1-428 C | Adder | 6.88 MW | 5.85 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 965691 | AG1-437 C | Adder | 15.05 MW | 12.79 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 965701 | AG1-438 C | Adder | 15.05 MW | 12.79 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 965741 | AG1-442 C | Adder | 8.78 MW | 7.46 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 965751 | AG1-443 C | Adder | 8.78 MW | 7.46 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 965771 | AG1-445 C | Adder | 6.12 MW | 5.21 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 965781 | AG1-446 C | Adder | 6.12 MW | 5.21 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 965811 | AG1-449 C | 80/20 | 37.07 MW | 37.07 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 966611 | AG1-531 C | Adder | 8.25 MW | 7.01 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 313764 | 3SOCKMAN | Adder | 1.04 MW | 0.89 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 932631 | AC2-084 C | Adder | 9.55 MW | 8.12 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 934321 | AD1-056 C | Adder | 7.83 MW | 6.65 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 934501 | AD1-074 C | Adder | 50.21 MW | 42.68 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 934511 | AD1-075 C | Adder | 12.55 MW | 10.67 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 935161 | AD1-151 C | Adder | 22.86 MW | 19.43 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 938531 | AE1-072 C | Adder | 26.61 MW | 22.62 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 939191 | AE1-149 C | Adder | 15.99 MW | 13.59 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 940431 | AE2-027 C | Adder | 18.44 MW | 15.67 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 940481 | AE2-033 C | 80/20 | 24.58 MW | 24.58 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 940541 | AE2-040 C | 80/20 | 4.37 MW | 4.37 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 940641 | AE2-051 C | 80/20 | 27.89 MW | 27.89 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 940651 | AE2-052 C | Adder | 5.33 MW | 4.53 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 941101 | AE2-104 C | Adder | 5.06 MW | 4.3 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 941281 | AE2-122 C | 80/20 | 43.16 MW | 43.16 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 944641 | AF1-129 C | Adder | 144.61 MW | 122.92 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 945811 | AF1-246 C | Adder | 11.38 MW | 9.68 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 316303 | AF2-085 | 80/20 | 6.48 MW | 6.48 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 65.43 MW | 65.43 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 40.39 MW | 40.39 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 145.15 MW | 145.15 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | NY | PJM->LTFIMP_NY | CLTF | 3.18 MW | 3.18 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | LGEE | LTFEXP_LGEE->PJM | CLTF | 2.6 MW | 2.6 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | WEC | LTFEXP_WEC->PJM | CLTF | 1.34 MW | 1.34 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | CPLE | LTFEXP_CPLE->PJM | CLTF | 16.79 MW | 16.79 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | TVA | LTFEXP_TVA->PJM | CLTF | 10.51 MW | 10.51 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | MEC | LTFEXP_MEC->PJM | CLTF | 7.66 MW | 7.66 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | LAGN | LTFEXP_LAGN->PJM | CLTF | 13.19 MW | 13.19 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.49 MW | 0.49 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 8.01 MW | 8.01 MW |
| Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 961941 | AG1-037 C | Adder | 0.83 MW | 0.7 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 962331 | AG1-082 C | Adder | 3.31 MW | 2.82 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 962341 | AG1-083 C | Adder | 3.31 MW | 2.82 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963041 | AG1-153 C | Adder | 8.4 MW | 7.14 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963111 | AG1-160 C | Adder | 8.49 MW | 7.21 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963301 | AG1-179 C | Adder | 8.69 MW | 7.38 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964801 | AG1-343 C | Adder | 9.87 MW | 8.39 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 966801 | AG1-551 C | Adder | 3.39 MW | 2.88 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 966811 | AG1-552 C | Adder | 3.24 MW | 2.75 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965291 | AG1-394 C | Adder | 3.39 MW | 2.88 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 966361 | AG1-505 C | Adder | 25.07 MW | 21.31 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 966371 | AG1-506 C | Adder | 25.07 MW | 21.31 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 966621 | AG1-532 C | Adder | 2.19 MW | 1.86 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 934521 | AD1-076 C | Adder | 20.6 MW | 17.51 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 942931 | AE2-313 C | Adder | 54.1 MW | 45.99 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944011 | AF1-069 C | Adder | 19.58 MW | 16.64 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 960081 | AF2-299 C | Adder | 4.06 MW | 3.45 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941031 | AE2-094 C | Adder | 59.93 MW | 50.94 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 946281 | AF1-292 C | Adder | 2.42 MW | 2.06 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 957481 | AF2-042 C | Adder | 78.93 MW | 67.09 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 957521 | AF2-046 C | Adder | 27.88 MW | 23.69 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 957531 | AF2-047 C | Adder | 29.1 MW | 24.73 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 938771 | AE1-103 C | Adder | 5.02 MW | 4.27 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 314229 | 6MT RD221 | 80/20 | 0.19 MW | 0.19 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 314236 | 6NRTHEST | 80/20 | 0.28 MW | 0.28 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 314250 | 6ROCKVILLE | Adder | 3.55 MW | 3.02 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 314309 | 6IRON208 | 80/20 | 0.68 MW | 0.68 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 314314 | 3LOCKS | Adder | 3.18 MW | 2.71 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 314421 | 6WINCHST | 80/20 | 0.2 MW | 0.2 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 314507 | 3THOMPSN | Adder | 3.6 MW | 3.06 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315060 | 1CHESTF5 | 80/20 | 117.22 MW | 117.22 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315061 | 1CHESTG7 | 80/20 | 6.04 MW | 6.04 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315062 | 1CHESTS7 | 80/20 | 2.77 MW | 2.77 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315063 | 1CHESTG8 | 80/20 | 5.94 MW | 5.94 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315064 | 1CHESTS8 | 80/20 | 3.06 MW | 3.06 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315065 | 1CHESTF6 | Adder | 35.06 MW | 29.8 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315067 | 1DARBY 1 | 80/20 | 3.96 MW | 3.96 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315068 | 1DARBY 2 | 80/20 | 3.96 MW | 3.96 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315069 | 1DARBY 3 | 80/20 | 3.98 MW | 3.98 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315070 | 1DARBY 4 | 80/20 | 3.98 MW | 3.98 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315073 | 1STONECA | 80/20 | 12.53 MW | 12.53 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315076 | 1HOPPOLC | 80/20 | 2.35 MW | 2.35 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315077 | 1HOPHCF1 | 80/20 | 3.73 MW | 3.73 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315078 | 1HOPHCF2 | 80/20 | 3.73 MW | 3.73 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315079 | 1HOPHCF3 | 80/20 | 3.73 MW | 3.73 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315080 | 1HOPHCF4 | 80/20 | 5.67 MW | 5.67 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315083 | 1SPRUNCA | Adder | 16.04 MW | 13.64 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315084 | 1SPRUNCB | Adder | 16.04 MW | 13.64 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315092 | 1YORKTN3 | 80/20 | 259.0 MW | 259.0 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 936591 | AD2-074 C | Adder | 9.01 MW | 7.66 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 942341 | AE2-247 C | Adder | 2.63 MW | 2.23 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 943461 | AF1-017 C | Adder | 2.38 MW | 2.02 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 943741 | AF1-042 C | Adder | 4.71 MW | 4.01 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944871 | AF1-152 C | Adder | 9.24 MW | 7.86 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 961951 | AG1-038 C | Adder | 5.21 MW | 4.43 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 966661 | AG1-536 C | Adder | 8.51 MW | 7.23 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 966871 | AG1-558 C | Adder | 4.14 MW | 3.52 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315116 | 1SURRY 1 | 80/20 | 37.63 MW | 37.63 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315120 | 1GRAVEL4 | 80/20 | 3.87 MW | 3.87 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315122 | 1GRAVEL6 | 80/20 | 3.87 MW | 3.87 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315233 | 1SURRY 2 | 80/20 | 38.96 MW | 38.96 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315260 | 1GOSPORTA | Adder | 3.8 MW | 3.23 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315261 | 1GOSPORTB | Adder | 4.85 MW | 4.12 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315262 | 1GOSPORTC | Adder | 4.12 MW | 3.5 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315611 | 6Z1-036WIND | Adder | 11.79 MW | 10.02 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 316075 | AC2-137 C | 80/20 | 0.6 MW | 0.6 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 316108 | AB2-160 C | Adder | 9.68 MW | 8.23 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 316132 | AB2-190 C | 80/20 | 7.16 MW | 7.16 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 957601 | AF2-054 C | Adder | 3.67 MW | 3.12 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 962531 | AG1-102 C | Adder | 1.96 MW | 1.67 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 962861 | AG1-135 C | Adder | 9.65 MW | 8.2 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 962971 | AG1-146 C | Adder | 5.06 MW | 4.3 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 962981 | AG1-147 C | Adder | 11.82 MW | 10.05 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964211 | AG1-282 C | Adder | 3.1 MW | 2.63 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941501 | AE2-147 C | Adder | 27.73 MW | 23.57 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 942001 | AE2-212 C | Adder | 3.8 MW | 3.23 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 957831 | AF2-077 C | Adder | 3.83 MW | 3.25 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 957871 | AF2-081 C | Adder | 17.66 MW | 15.02 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 958161 | AF2-110 C | Adder | 2.41 MW | 2.05 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 926071 | AC1-086 C | Adder | 33.29 MW | 28.3 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 933291 | AC2-141 C | 80/20 | 54.66 MW | 54.66 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 939411 | AE1-173 C | Adder | 147.12 MW | 125.06 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 934011 | AD1-025 C | 80/20 | 30.56 MW | 30.56 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 927041 | AC1-191 C | Adder | 16.6 MW | 14.11 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 933981 | AD1-022 C | Adder | 14.67 MW | 12.47 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 961681 | AG1-008 C | Adder | 27.93 MW | 23.74 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 962571 | AG1-106 C | Adder | 9.26 MW | 7.87 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 316004 | AC1-112 C | 80/20 | 0.52 MW | 0.52 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 316159 | AE1-175 C | 80/20 | 0.62 MW | 0.62 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 316169 | AC1-164 GEN | 80/20 | 10.63 MW | 10.63 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 316210 | AC1-098 C | Adder | 9.7 MW | 8.24 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 316212 | AC1-099 C | Adder | 3.25 MW | 2.76 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 316233 | AE1-074 C | Adder | 4.15 MW | 3.52 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 316240 | AF1-291 C | Adder | 3.84 MW | 3.27 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 316274 | AC1-208 C | Adder | 14.16 MW | 12.04 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 316294 | AC1-161 C | 80/20 | 7.54 MW | 7.54 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 316301 | AE2-228 C | Adder | 3.84 MW | 3.26 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 316304 | AE2-227 C | 80/20 | 3.98 MW | 3.98 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 316312 | AB1-027 C | 80/20 | 0.83 MW | 0.83 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 316369 | AC1-216 C | 80/20 | 2.45 MW | 2.45 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 316382 | AG1-145 C | 80/20 | 0.56 MW | 0.56 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963221 | AG1-171 C | 80/20 | 3.89 MW | 3.89 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963231 | AG1-172 C | 80/20 | 3.89 MW | 3.89 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963241 | AG1-173 C | 80/20 | 3.89 MW | 3.89 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963251 | AG1-174 C | 80/20 | 3.89 MW | 3.89 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 316201 | AC1-065 C | Adder | 17.68 MW | 15.03 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 316181 | AB2-040 GEN | Adder | 11.81 MW | 10.04 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 316033 | AB2-134 GEN | 80/20 | 3.21 MW | 3.21 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 316311 | AC2-079 C | Adder | 10.09 MW | 8.58 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 316349 | AD2-085 C | Adder | 6.06 MW | 5.15 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 961611 | AG1-000B C | 80/20 | 28.77 MW | 28.77 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941291 | AE2-123 C | Adder | 51.99 MW | 44.19 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941301 | AE2-124 C | Adder | 47.27 MW | 40.18 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941591 | AE2-156 C | Adder | 31.92 MW | 27.14 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 942371 | AE2-250 C | Adder | 17.19 MW | 14.62 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 942551 | AE2-270 C | 80/20 | 48.66 MW | 48.66 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944581 | AF1-123 C | Adder | 85.41 MW | 72.6 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944591 | AF1-124 C | Adder | 85.41 MW | 72.6 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944601 | AF1-125 C | Adder | 85.41 MW | 72.6 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944631 | AF1-128 C | 80/20 | 73.34 MW | 73.34 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 945361 | AF1-201 C | Adder | 29.01 MW | 24.66 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 946011 | AF1-266 C | Adder | 21.72 MW | 18.46 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 957711 | AF2-065 C | 80/20 | 24.82 MW | 24.82 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 958261 | AF2-120 C | Adder | 9.89 MW | 8.4 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 961711 | AG1-011 C | 80/20 | 51.9 MW | 51.9 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 962271 | AG1-075 C | Adder | 29.68 MW | 25.22 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963291 | AG1-178 C | Adder | 97.82 MW | 83.14 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963311 | AG1-180 C | Adder | 4.22 MW | 3.58 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963351 | AG1-184 C | Adder | 52.7 MW | 44.79 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964951 | AG1-359 C | Adder | 40.54 MW | 34.45 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965001 | AG1-364 C | Adder | 12.77 MW | 10.85 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965281 | AG1-393 C | Adder | 3.82 MW | 3.25 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965601 | AG1-428 C | Adder | 7.25 MW | 6.16 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965691 | AG1-437 C | Adder | 16.9 MW | 14.37 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965701 | AG1-438 C | Adder | 16.9 MW | 14.37 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965741 | AG1-442 C | Adder | 9.86 MW | 8.38 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965751 | AG1-443 C | Adder | 9.86 MW | 8.38 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965811 | AG1-449 C | Adder | 35.04 MW | 29.78 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 966611 | AG1-531 C | 80/20 | 10.56 MW | 10.56 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 313764 | 3SOCKMAN | Adder | 1.12 MW | 0.95 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 932631 | AC2-084 C | Adder | 10.37 MW | 8.81 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 934501 | AD1-074 C | Adder | 56.71 MW | 48.2 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 934511 | AD1-075 C | Adder | 14.18 MW | 12.05 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 935161 | AD1-151 C | 80/20 | 29.23 MW | 29.23 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 938531 | AE1-072 C | Adder | 31.03 MW | 26.37 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 939191 | AE1-149 C | Adder | 18.89 MW | 16.05 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 939601 | AE1-190 C | Adder | 3.72 MW | 3.17 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 940431 | AE2-027 C | Adder | 22.99 MW | 19.54 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 940481 | AE2-033 C | Adder | 25.94 MW | 22.05 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 940541 | AE2-040 C | Adder | 4.61 MW | 3.92 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 940551 | AE2-041 C | Adder | 12.58 MW | 10.69 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 940641 | AE2-051 C | Adder | 27.24 MW | 23.16 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 940651 | AE2-052 C | Adder | 6.3 MW | 5.35 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941101 | AE2-104 C | Adder | 5.9 MW | 5.01 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941281 | AE2-122 C | Adder | 50.59 MW | 43.0 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 943471 | AF1-018 C | Adder | 12.58 MW | 10.69 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944641 | AF1-129 C | Adder | 182.84 MW | 155.41 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 945811 | AF1-246 C | Adder | 11.05 MW | 9.39 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 84.56 MW | 84.56 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 48.88 MW | 48.88 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 157.94 MW | 157.94 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | NY | PJM->LTFIMP_NY | CLTF | 4.15 MW | 4.15 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | LGEE | LTFEXP_LGEE->PJM | CLTF | 3.37 MW | 3.37 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | WEC | LTFEXP_WEC->PJM | CLTF | 1.73 MW | 1.73 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | CPLE | LTFEXP_CPLE->PJM | CLTF | 17.77 MW | 17.77 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | TVA | LTFEXP_TVA->PJM | CLTF | 12.47 MW | 12.47 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | MEC | LTFEXP_MEC->PJM | CLTF | 9.6 MW | 9.6 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | LAGN | LTFEXP_LAGN->PJM | CLTF | 15.54 MW | 15.54 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.62 MW | 0.62 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 8.48 MW | 8.48 MW |
| Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 961891 | AG1-030 C | Adder | 13.1 MW | 11.14 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 961941 | AG1-037 C | Adder | 0.45 MW | 0.39 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 962331 | AG1-082 C | Adder | 1.81 MW | 1.54 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 962341 | AG1-083 C | Adder | 1.81 MW | 1.54 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 963041 | AG1-153 C | 80/20 | 5.72 MW | 5.72 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 963111 | AG1-160 C | 80/20 | 5.79 MW | 5.79 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 963301 | AG1-179 C | Adder | 5.22 MW | 4.43 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 964111 | AG1-272 C | Adder | 2.26 MW | 1.93 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 964121 | AG1-273 C | Adder | 2.26 MW | 1.93 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 964131 | AG1-274 C | Adder | 2.26 MW | 1.93 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 964801 | AG1-343 C | Adder | 5.38 MW | 4.57 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 966811 | AG1-552 C | Adder | 1.86 MW | 1.58 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 965191 | AG1-384 C | Adder | 2.26 MW | 1.93 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 965291 | AG1-394 C | Adder | 1.85 MW | 1.57 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 965591 | AG1-427 C | Adder | 10.56 MW | 8.97 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 965721 | AG1-440 C | Adder | 6.75 MW | 5.74 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 965731 | AG1-441 C | Adder | 6.75 MW | 5.74 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 966361 | AG1-505 C | 80/20 | 17.04 MW | 17.04 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 966371 | AG1-506 C | 80/20 | 17.04 MW | 17.04 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 966621 | AG1-532 C | Adder | 1.28 MW | 1.09 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315153 | 1CLOVER1 | 80/20 | 10.33 MW | 10.33 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315154 | 1CLOVER2 | 80/20 | 10.24 MW | 10.24 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 934521 | AD1-076 C | Adder | 10.95 MW | 9.31 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 942931 | AE2-313 C | 80/20 | 37.11 MW | 37.11 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 944011 | AF1-069 C | 80/20 | 13.46 MW | 13.46 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 959311 | AF2-222 C | Adder | 14.66 MW | 12.46 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 960081 | AF2-299 C | Adder | 2.38 MW | 2.02 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 939181 | AE1-148 C | Adder | 8.07 MW | 6.86 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 941031 | AE2-094 C | 80/20 | 41.18 MW | 41.18 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 941791 | AE2-182 C | Adder | 1.81 MW | 1.54 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 946281 | AF1-292 C | Adder | 1.42 MW | 1.2 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 957481 | AF2-042 C | 80/20 | 52.7 MW | 52.7 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 957521 | AF2-046 C | Adder | 15.21 MW | 12.93 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 957531 | AF2-047 C | Adder | 15.3 MW | 13.01 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 938771 | AE1-103 C | Adder | 2.63 MW | 2.23 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 314250 | 6ROCKVILLE | Adder | 1.63 MW | 1.38 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 314295 | 6BIRDNECK | 80/20 | 0.03 MW | 0.03 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 314314 | 3LOCKS | Adder | 1.49 MW | 1.27 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 314507 | 3THOMPSN | Adder | 1.8 MW | 1.53 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315065 | 1CHESTF6 | Adder | 11.99 MW | 10.19 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315083 | 1SPRUNCA | Adder | 7.71 MW | 6.56 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315084 | 1SPRUNCB | Adder | 7.71 MW | 6.56 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 942341 | AE2-247 C | Adder | 1.33 MW | 1.13 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 943461 | AF1-017 C | Adder | 1.2 MW | 1.02 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 944871 | AF1-152 C | Adder | 4.73 MW | 4.02 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315102 | 1BRUNSWICKG1 | 80/20 | 7.12 MW | 7.12 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315103 | 1BRUNSWICKG2 | 80/20 | 7.12 MW | 7.12 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315104 | 1BRUNSWICKG3 | 80/20 | 7.12 MW | 7.12 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315105 | 1BRUNSWICKS1 | 80/20 | 14.8 MW | 14.8 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315108 | 1ELIZAR1 | 80/20 | 2.41 MW | 2.41 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315109 | 1ELIZAR2 | 80/20 | 2.37 MW | 2.37 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315110 | 1ELIZAR3 | 80/20 | 2.44 MW | 2.44 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315172 | 1LOISA A | 80/20 | 2.01 MW | 2.01 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315173 | 1LOISA B | 80/20 | 2.02 MW | 2.02 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315174 | 1LOISA C | 80/20 | 2.02 MW | 2.02 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315175 | 1LOISA D | 80/20 | 2.02 MW | 2.02 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315176 | 1LOISA E | 80/20 | 4.12 MW | 4.12 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315177 | 1S ANNAG1 | 80/20 | 2.0 MW | 2.0 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315178 | 1S ANNAS1 | 80/20 | 1.03 MW | 1.03 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315179 | 1S ANNAG2 | 80/20 | 2.0 MW | 2.0 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315180 | 1S ANNAS2 | 80/20 | 1.03 MW | 1.03 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315225 | 1N ANNA1 | 80/20 | 78.55 MW | 78.55 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315226 | 1N ANNA2 | 80/20 | 78.56 MW | 78.56 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315241 | 1Z1-086 GT1 | 80/20 | 9.13 MW | 9.13 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315242 | 1Z1-086 GT2 | 80/20 | 9.13 MW | 9.13 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315243 | 1Z1-086 GT3 | 80/20 | 9.13 MW | 9.13 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315244 | 1Z1-086 ST | 80/20 | 15.89 MW | 15.89 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315260 | 1GOSPORTA | Adder | 1.9 MW | 1.61 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315261 | 1GOSPORTB | Adder | 2.43 MW | 2.06 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315262 | 1GOSPORTC | Adder | 2.06 MW | 1.75 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 315611 | 6Z1-036WIND | Adder | 6.09 MW | 5.17 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 316108 | AB2-160 C | Adder | 4.54 MW | 3.86 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 946371 | AF1-301 C | 80/20 | 16.76 MW | 16.76 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 966001 | AG1-469 C | Adder | 1.44 MW | 1.22 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 941501 | AE2-147 C | Adder | 14.18 MW | 12.06 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 942001 | AE2-212 C | Adder | 1.85 MW | 1.57 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 957871 | AF2-081 C | Adder | 8.94 MW | 7.6 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 958161 | AF2-110 C | Adder | 1.22 MW | 1.04 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 926071 | AC1-086 C | Adder | 19.03 MW | 16.18 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 936261 | AD2-033 C | Adder | 11.49 MW | 9.76 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 933291 | AC2-141 C | 80/20 | 27.17 MW | 27.17 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 934621 | AD1-088 C | Adder | 11.12 MW | 9.45 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 939411 | AE1-173 C | 80/20 | 90.57 MW | 90.57 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 933981 | AD1-022 C | Adder | 7.84 MW | 6.67 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 961681 | AG1-008 C | Adder | 15.24 MW | 12.96 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 962571 | AG1-106 C | Adder | 5.29 MW | 4.5 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 208900 | BRIS G1 | 80/20 | -2.17 MW | -2.17 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 208901 | BRIS G2 | 80/20 | -2.57 MW | -2.57 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 316023 | AB2-100 C2 | 80/20 | 0.75 MW | 0.75 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 316185 | AD1-033 C | 80/20 | 0.93 MW | 0.93 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 316192 | AB2-158 C | 80/20 | 3.03 MW | 3.03 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 316210 | AC1-098 C | Adder | 5.48 MW | 4.65 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 316212 | AC1-099 C | Adder | 1.84 MW | 1.56 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 316233 | AE1-074 C | 80/20 | 2.46 MW | 2.46 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 316240 | AF1-291 C | Adder | 1.77 MW | 1.5 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 316258 | AE1-075 C | 80/20 | 0.3 MW | 0.3 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 316274 | AC1-208 C | Adder | 8.06 MW | 6.85 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 316294 | AC1-161 C | 80/20 | 3.75 MW | 3.75 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 316301 | AE2-228 C | Adder | 1.78 MW | 1.51 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 316313 | AB2-026 C | 80/20 | 0.32 MW | 0.32 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 316315 | AB2-025 C | 80/20 | 0.33 MW | 0.33 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 316316 | AC1-027 C | 80/20 | 0.24 MW | 0.24 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 316336 | AC2-165 C | 80/20 | 9.68 MW | 9.68 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 316365 | AB2-100 C1 | 80/20 | 0.75 MW | 0.75 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 316405 | AF2-144 C | 80/20 | 0.25 MW | 0.25 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 316181 | AB2-040 GEN | Adder | 6.85 MW | 5.82 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 316311 | AC2-079 C | Adder | 5.11 MW | 4.34 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 316349 | AD2-085 C | Adder | 3.06 MW | 2.6 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 316388 | AE2-253 GEN | 80/20 | 1.48 MW | 1.48 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 961611 | AG1-000B C | Adder | 13.11 MW | 11.14 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 940661 | AE2-053 C | Adder | 2.99 MW | 2.54 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 941291 | AE2-123 C | 80/20 | 26.14 MW | 26.14 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 941301 | AE2-124 C | 80/20 | 23.78 MW | 23.78 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 941591 | AE2-156 C | 80/20 | 15.98 MW | 15.98 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 942371 | AE2-250 C | Adder | 8.06 MW | 6.85 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 944581 | AF1-123 C | 80/20 | 43.23 MW | 43.23 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 944591 | AF1-124 C | 80/20 | 43.23 MW | 43.23 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 944601 | AF1-125 C | 80/20 | 43.23 MW | 43.23 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 946011 | AF1-266 C | 80/20 | 12.78 MW | 12.78 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 957431 | AF2-037 C | 80/20 | 23.95 MW | 23.95 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 957691 | AF2-063 C | 80/20 | 38.21 MW | 38.21 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 962271 | AG1-075 C | Adder | 13.91 MW | 11.82 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 962491 | AG1-098 C | Adder | 10.01 MW | 8.51 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 962561 | AG1-105 C | Adder | 7.86 MW | 6.68 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 962841 | AG1-133 C | 80/20 | 46.09 MW | 46.09 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 963291 | AG1-178 C | 80/20 | 64.85 MW | 64.85 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 963311 | AG1-180 C | Adder | 2.53 MW | 2.15 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 963321 | AG1-181 C | Adder | 14.88 MW | 12.65 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 963351 | AG1-184 C | 80/20 | 34.94 MW | 34.94 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 963361 | AG1-185 C | Adder | 7.2 MW | 6.12 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 964241 | AG1-285 C | Adder | 11.12 MW | 9.45 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 964421 | AG1-305 C | 80/20 | 30.06 MW | 30.06 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 964951 | AG1-359 C | 80/20 | 20.45 MW | 20.45 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 965001 | AG1-364 C | Adder | 6.39 MW | 5.43 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 965281 | AG1-393 C | Adder | 1.79 MW | 1.52 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 965601 | AG1-428 C | Adder | 4.35 MW | 3.7 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 965691 | AG1-437 C | Adder | 9.07 MW | 7.71 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 965701 | AG1-438 C | Adder | 9.07 MW | 7.71 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 965741 | AG1-442 C | Adder | 5.29 MW | 4.5 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 965751 | AG1-443 C | Adder | 5.29 MW | 4.5 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 965771 | AG1-445 C | Adder | 3.9 MW | 3.31 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 965781 | AG1-446 C | Adder | 3.9 MW | 3.31 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 965811 | AG1-449 C | 80/20 | 24.03 MW | 24.03 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 313764 | 3SOCKMAN | Adder | 0.65 MW | 0.55 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 932631 | AC2-084 C | Adder | 5.85 MW | 4.98 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 934501 | AD1-074 C | Adder | 30.15 MW | 25.63 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 934511 | AD1-075 C | Adder | 7.54 MW | 6.41 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 934611 | AD1-087 C | 80/20 | 1.02 MW | 1.02 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 935171 | AD1-152 C | 80/20 | 1.05 MW | 1.05 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 937481 | AD2-202 C | 80/20 | 0.29 MW | 0.29 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 938531 | AE1-072 C | Adder | 15.73 MW | 13.37 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 939191 | AE1-149 C | Adder | 9.43 MW | 8.02 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 940431 | AE2-027 C | Adder | 10.6 MW | 9.01 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 940481 | AE2-033 C | 80/20 | 15.27 MW | 15.27 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 940541 | AE2-040 C | 80/20 | 2.72 MW | 2.72 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 940641 | AE2-051 C | 80/20 | 17.82 MW | 17.82 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 940651 | AE2-052 C | Adder | 3.14 MW | 2.67 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 941101 | AE2-104 C | Adder | 3.0 MW | 2.55 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 941281 | AE2-122 C | 80/20 | 25.44 MW | 25.44 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 944641 | AF1-129 C | Adder | 82.55 MW | 70.17 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 945811 | AF1-246 C | 80/20 | 7.38 MW | 7.38 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | 316303 | AF2-085 | 80/20 | 4.28 MW | 4.28 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 24.95 MW | 24.95 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 19.77 MW | 19.77 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 86.39 MW | 86.39 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | NY | PJM->LTFIMP_NY | CLTF | 2.46 MW | 2.46 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | LGEE | LTFEXP_LGEE->PJM | CLTF | 1.07 MW | 1.07 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | WEC | LTFEXP_WEC->PJM | CLTF | 0.53 MW | 0.53 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | CPLE | LTFEXP_CPLE->PJM | CLTF | 10.27 MW | 10.27 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | TVA | LTFEXP_TVA->PJM | CLTF | 5.48 MW | 5.48 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | MEC | LTFEXP_MEC->PJM | CLTF | 3.35 MW | 3.35 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | LAGN | LTFEXP_LAGN->PJM | CLTF | 6.9 MW | 6.9 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.21 MW | 0.21 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 4.9 MW | 4.9 MW |
| Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 961891 | AG1-030 C | Adder | 13.1 MW | 11.14 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 961941 | AG1-037 C | Adder | 0.45 MW | 0.39 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 962331 | AG1-082 C | Adder | 1.81 MW | 1.54 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 962341 | AG1-083 C | Adder | 1.81 MW | 1.54 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 963041 | AG1-153 C | 80/20 | 5.72 MW | 5.72 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 963111 | AG1-160 C | 80/20 | 5.79 MW | 5.79 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 963301 | AG1-179 C | Adder | 5.22 MW | 4.43 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 964111 | AG1-272 C | Adder | 2.26 MW | 1.93 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 964121 | AG1-273 C | Adder | 2.26 MW | 1.93 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 964131 | AG1-274 C | Adder | 2.26 MW | 1.93 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 964801 | AG1-343 C | Adder | 5.38 MW | 4.57 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 966811 | AG1-552 C | Adder | 1.86 MW | 1.58 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 965191 | AG1-384 C | Adder | 2.26 MW | 1.93 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 965291 | AG1-394 C | Adder | 1.85 MW | 1.57 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 965591 | AG1-427 C | Adder | 10.56 MW | 8.97 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 965721 | AG1-440 C | Adder | 6.75 MW | 5.74 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 965731 | AG1-441 C | Adder | 6.75 MW | 5.74 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 966361 | AG1-505 C | 80/20 | 17.04 MW | 17.04 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 966371 | AG1-506 C | 80/20 | 17.04 MW | 17.04 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 966621 | AG1-532 C | Adder | 1.28 MW | 1.09 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315153 | 1CLOVER1 | 80/20 | 10.33 MW | 10.33 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315154 | 1CLOVER2 | 80/20 | 10.24 MW | 10.24 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 934521 | AD1-076 C | Adder | 10.95 MW | 9.31 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 942931 | AE2-313 C | 80/20 | 37.11 MW | 37.11 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 944011 | AF1-069 C | 80/20 | 13.46 MW | 13.46 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 958801 | AF2-171 C | Adder | 9.27 MW | 7.88 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 959311 | AF2-222 C | Adder | 14.66 MW | 12.46 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 960081 | AF2-299 C | Adder | 2.38 MW | 2.02 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 939181 | AE1-148 C | Adder | 8.07 MW | 6.86 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 941031 | AE2-094 C | 80/20 | 41.18 MW | 41.18 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 941791 | AE2-182 C | Adder | 1.81 MW | 1.54 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 946281 | AF1-292 C | Adder | 1.42 MW | 1.2 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 957481 | AF2-042 C | 80/20 | 52.7 MW | 52.7 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 957521 | AF2-046 C | Adder | 15.21 MW | 12.93 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 957531 | AF2-047 C | Adder | 15.3 MW | 13.01 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 938771 | AE1-103 C | Adder | 2.63 MW | 2.23 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 314250 | 6ROCKVILLE | Adder | 1.63 MW | 1.38 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 314295 | 6BIRDNECK | 80/20 | 0.03 MW | 0.03 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 314314 | 3LOCKS | Adder | 1.49 MW | 1.27 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 314507 | 3THOMPSN | Adder | 1.8 MW | 1.53 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315065 | 1CHESTF6 | Adder | 15.83 MW | 13.46 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315083 | 1SPRUNCA | Adder | 7.71 MW | 6.56 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315084 | 1SPRUNCB | Adder | 7.71 MW | 6.56 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 942341 | AE2-247 C | Adder | 1.33 MW | 1.13 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 943461 | AF1-017 C | Adder | 1.2 MW | 1.02 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 944871 | AF1-152 C | Adder | 4.73 MW | 4.02 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315102 | 1BRUNSWICKG1 | 80/20 | 7.12 MW | 7.12 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315103 | 1BRUNSWICKG2 | 80/20 | 7.12 MW | 7.12 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315104 | 1BRUNSWICKG3 | 80/20 | 7.12 MW | 7.12 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315105 | 1BRUNSWICKS1 | 80/20 | 14.8 MW | 14.8 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315108 | 1ELIZAR1 | 80/20 | 2.41 MW | 2.41 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315109 | 1ELIZAR2 | 80/20 | 2.37 MW | 2.37 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315110 | 1ELIZAR3 | 80/20 | 2.44 MW | 2.44 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315172 | 1LOISA A | 80/20 | 2.01 MW | 2.01 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315173 | 1LOISA B | 80/20 | 2.02 MW | 2.02 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315174 | 1LOISA C | 80/20 | 2.02 MW | 2.02 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315175 | 1LOISA D | 80/20 | 2.02 MW | 2.02 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315176 | 1LOISA E | 80/20 | 4.12 MW | 4.12 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315177 | 1S ANNAG1 | 80/20 | 2.0 MW | 2.0 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315178 | 1S ANNAS1 | 80/20 | 1.03 MW | 1.03 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315179 | 1S ANNAG2 | 80/20 | 2.0 MW | 2.0 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315180 | 1S ANNAS2 | 80/20 | 1.03 MW | 1.03 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315225 | 1N ANNA1 | 80/20 | 78.55 MW | 78.55 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315226 | 1N ANNA2 | 80/20 | 78.56 MW | 78.56 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315241 | 1Z1-086 GT1 | 80/20 | 9.13 MW | 9.13 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315242 | 1Z1-086 GT2 | 80/20 | 9.13 MW | 9.13 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315243 | 1Z1-086 GT3 | 80/20 | 9.13 MW | 9.13 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315244 | 1Z1-086 ST | 80/20 | 15.89 MW | 15.89 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315260 | 1GOSPORTA | Adder | 1.9 MW | 1.61 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315261 | 1GOSPORTB | Adder | 2.43 MW | 2.06 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315262 | 1GOSPORTC | Adder | 2.06 MW | 1.75 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 315611 | 6Z1-036WIND | Adder | 6.09 MW | 5.17 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 316108 | AB2-160 C | Adder | 4.54 MW | 3.86 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 946371 | AF1-301 C | 80/20 | 16.76 MW | 16.76 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 966001 | AG1-469 C | Adder | 1.44 MW | 1.22 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 941501 | AE2-147 C | Adder | 14.18 MW | 12.06 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 942001 | AE2-212 C | Adder | 1.85 MW | 1.57 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 957871 | AF2-081 C | Adder | 8.94 MW | 7.6 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 958161 | AF2-110 C | Adder | 1.22 MW | 1.04 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 926071 | AC1-086 C | Adder | 19.03 MW | 16.18 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 936261 | AD2-033 C | Adder | 11.49 MW | 9.76 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 933291 | AC2-141 C | 80/20 | 27.17 MW | 27.17 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 934621 | AD1-088 C | Adder | 11.12 MW | 9.45 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 939411 | AE1-173 C | 80/20 | 90.57 MW | 90.57 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 933981 | AD1-022 C | Adder | 7.84 MW | 6.67 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 961681 | AG1-008 C | Adder | 15.24 MW | 12.96 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 962571 | AG1-106 C | Adder | 5.29 MW | 4.5 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 208900 | BRIS G1 | 80/20 | -2.17 MW | -2.17 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 208901 | BRIS G2 | 80/20 | -2.57 MW | -2.57 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 316023 | AB2-100 C2 | 80/20 | 0.75 MW | 0.75 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 316185 | AD1-033 C | 80/20 | 0.93 MW | 0.93 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 316192 | AB2-158 C | 80/20 | 3.03 MW | 3.03 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 316210 | AC1-098 C | Adder | 5.48 MW | 4.65 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 316212 | AC1-099 C | Adder | 1.84 MW | 1.56 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 316233 | AE1-074 C | 80/20 | 2.46 MW | 2.46 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 316240 | AF1-291 C | Adder | 1.77 MW | 1.5 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 316258 | AE1-075 C | 80/20 | 0.3 MW | 0.3 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 316274 | AC1-208 C | Adder | 8.06 MW | 6.85 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 316294 | AC1-161 C | 80/20 | 3.75 MW | 3.75 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 316301 | AE2-228 C | Adder | 1.78 MW | 1.51 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 316313 | AB2-026 C | 80/20 | 0.32 MW | 0.32 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 316315 | AB2-025 C | 80/20 | 0.33 MW | 0.33 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 316316 | AC1-027 C | 80/20 | 0.24 MW | 0.24 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 316336 | AC2-165 C | 80/20 | 9.68 MW | 9.68 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 316365 | AB2-100 C1 | 80/20 | 0.75 MW | 0.75 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 316405 | AF2-144 C | 80/20 | 0.25 MW | 0.25 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 316181 | AB2-040 GEN | Adder | 6.85 MW | 5.82 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 316311 | AC2-079 C | Adder | 5.11 MW | 4.34 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 316349 | AD2-085 C | Adder | 3.06 MW | 2.6 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 316388 | AE2-253 GEN | 80/20 | 1.48 MW | 1.48 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 961611 | AG1-000B C | Adder | 13.11 MW | 11.14 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 940661 | AE2-053 C | Adder | 2.99 MW | 2.54 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 941291 | AE2-123 C | 80/20 | 26.14 MW | 26.14 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 941301 | AE2-124 C | 80/20 | 23.78 MW | 23.78 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 941591 | AE2-156 C | 80/20 | 15.98 MW | 15.98 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 942371 | AE2-250 C | Adder | 8.06 MW | 6.85 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 944581 | AF1-123 C | 80/20 | 43.23 MW | 43.23 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 944591 | AF1-124 C | 80/20 | 43.23 MW | 43.23 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 944601 | AF1-125 C | 80/20 | 43.23 MW | 43.23 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 946011 | AF1-266 C | 80/20 | 12.78 MW | 12.78 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 957431 | AF2-037 C | 80/20 | 23.95 MW | 23.95 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 957691 | AF2-063 C | 80/20 | 38.21 MW | 38.21 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 962271 | AG1-075 C | Adder | 13.91 MW | 11.82 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 962491 | AG1-098 C | Adder | 10.01 MW | 8.51 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 962561 | AG1-105 C | Adder | 7.86 MW | 6.68 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 963291 | AG1-178 C | 80/20 | 64.85 MW | 64.85 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 963311 | AG1-180 C | Adder | 2.53 MW | 2.15 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 963321 | AG1-181 C | Adder | 14.88 MW | 12.65 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 963351 | AG1-184 C | 80/20 | 34.94 MW | 34.94 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 963361 | AG1-185 C | Adder | 7.2 MW | 6.12 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 964241 | AG1-285 C | Adder | 11.12 MW | 9.45 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 964421 | AG1-305 C | 80/20 | 30.06 MW | 30.06 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 964951 | AG1-359 C | 80/20 | 20.45 MW | 20.45 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 965001 | AG1-364 C | Adder | 6.39 MW | 5.43 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 965281 | AG1-393 C | Adder | 1.79 MW | 1.52 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 965601 | AG1-428 C | Adder | 4.35 MW | 3.7 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 965691 | AG1-437 C | Adder | 9.07 MW | 7.71 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 965701 | AG1-438 C | Adder | 9.07 MW | 7.71 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 965741 | AG1-442 C | Adder | 5.29 MW | 4.5 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 965751 | AG1-443 C | Adder | 5.29 MW | 4.5 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 965771 | AG1-445 C | Adder | 3.9 MW | 3.31 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 965781 | AG1-446 C | Adder | 3.9 MW | 3.31 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 965811 | AG1-449 C | 80/20 | 24.03 MW | 24.03 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 313764 | 3SOCKMAN | Adder | 0.65 MW | 0.55 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 932631 | AC2-084 C | Adder | 5.85 MW | 4.98 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 934501 | AD1-074 C | Adder | 30.15 MW | 25.63 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 934511 | AD1-075 C | Adder | 7.54 MW | 6.41 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 934611 | AD1-087 C | 80/20 | 1.02 MW | 1.02 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 935171 | AD1-152 C | 80/20 | 1.05 MW | 1.05 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 937481 | AD2-202 C | 80/20 | 0.29 MW | 0.29 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 938531 | AE1-072 C | Adder | 15.73 MW | 13.37 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 939191 | AE1-149 C | Adder | 9.43 MW | 8.02 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 940431 | AE2-027 C | Adder | 10.6 MW | 9.01 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 940481 | AE2-033 C | 80/20 | 15.27 MW | 15.27 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 940541 | AE2-040 C | 80/20 | 2.72 MW | 2.72 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 940641 | AE2-051 C | 80/20 | 17.82 MW | 17.82 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 940651 | AE2-052 C | Adder | 3.14 MW | 2.67 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 941101 | AE2-104 C | Adder | 3.0 MW | 2.55 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 941281 | AE2-122 C | 80/20 | 25.44 MW | 25.44 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 944641 | AF1-129 C | Adder | 82.55 MW | 70.17 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 945811 | AF1-246 C | 80/20 | 7.38 MW | 7.38 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | 316303 | AF2-085 | 80/20 | 4.28 MW | 4.28 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 24.95 MW | 24.95 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 19.77 MW | 19.77 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 86.39 MW | 86.39 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | NY | PJM->LTFIMP_NY | CLTF | 2.46 MW | 2.46 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | LGEE | LTFEXP_LGEE->PJM | CLTF | 1.07 MW | 1.07 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | WEC | LTFEXP_WEC->PJM | CLTF | 0.53 MW | 0.53 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | CPLE | LTFEXP_CPLE->PJM | CLTF | 10.27 MW | 10.27 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | TVA | LTFEXP_TVA->PJM | CLTF | 5.48 MW | 5.48 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | MEC | LTFEXP_MEC->PJM | CLTF | 3.35 MW | 3.35 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | LAGN | LTFEXP_LAGN->PJM | CLTF | 6.9 MW | 6.9 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.21 MW | 0.21 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S-2 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 4.9 MW | 4.9 MW |
| Details for AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 961791 | AG1-021 C | Adder | 1.61 MW | 1.37 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 961891 | AG1-030 C | Adder | 12.15 MW | 10.33 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 961941 | AG1-037 C | Adder | 0.39 MW | 0.33 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 962331 | AG1-082 C | Adder | 1.57 MW | 1.34 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 962341 | AG1-083 C | Adder | 1.57 MW | 1.34 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 963041 | AG1-153 C | 80/20 | 5.4 MW | 5.4 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 963111 | AG1-160 C | 80/20 | 5.47 MW | 5.47 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 963171 | AG1-166 C | Adder | 1.61 MW | 1.37 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 963181 | AG1-167 C | Adder | 1.61 MW | 1.37 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 963191 | AG1-168 C | Adder | 1.61 MW | 1.37 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 963201 | AG1-169 C | Adder | 1.61 MW | 1.37 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 963211 | AG1-170 C | Adder | 1.61 MW | 1.37 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 963301 | AG1-179 C | 80/20 | 4.71 MW | 4.71 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 964111 | AG1-272 C | Adder | 2.1 MW | 1.78 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 964121 | AG1-273 C | Adder | 2.1 MW | 1.78 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 964131 | AG1-274 C | Adder | 2.1 MW | 1.78 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 964791 | AG1-342 C | Adder | 3.37 MW | 2.87 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 964801 | AG1-343 C | Adder | 4.65 MW | 3.95 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 966811 | AG1-552 C | Adder | 1.65 MW | 1.4 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 965191 | AG1-384 C | Adder | 2.1 MW | 1.78 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 965291 | AG1-394 C | Adder | 1.6 MW | 1.36 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 965591 | AG1-427 C | 80/20 | 9.74 MW | 9.74 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 965721 | AG1-440 C | 80/20 | 6.16 MW | 6.16 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 965731 | AG1-441 C | 80/20 | 6.16 MW | 6.16 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 966361 | AG1-505 C | 80/20 | 16.08 MW | 16.08 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 966371 | AG1-506 C | 80/20 | 16.08 MW | 16.08 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 966621 | AG1-532 C | 80/20 | 1.14 MW | 1.14 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 313506 | AB1-173 C OP | 80/20 | 0.77 MW | 0.77 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 313853 | 3PONTONDP | Adder | 0.54 MW | 0.46 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 314704 | 3LAWRENC | 80/20 | 0.21 MW | 0.21 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315153 | 1CLOVER1 | 80/20 | 9.69 MW | 9.69 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315154 | 1CLOVER2 | 80/20 | 9.6 MW | 9.6 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315158 | 1KERR 1 | 80/20 | 0.28 MW | 0.28 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315159 | 1KERR 2 | 80/20 | 0.8 MW | 0.8 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315160 | 1KERR 3 | 80/20 | 0.8 MW | 0.8 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315161 | 1KERR 4 | 80/20 | 0.8 MW | 0.8 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315162 | 1KERR 5 | 80/20 | 0.8 MW | 0.8 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 934521 | AD1-076 C | Adder | 9.37 MW | 7.96 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 942931 | AE2-313 C | 80/20 | 35.08 MW | 35.08 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 944011 | AF1-069 C | 80/20 | 12.73 MW | 12.73 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 958801 | AF2-171 C | Adder | 12.11 MW | 10.29 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 959311 | AF2-222 C | Adder | 13.57 MW | 11.53 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 960061 | AF2-297 C | Adder | 6.31 MW | 5.36 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 960081 | AF2-299 C | 80/20 | 2.12 MW | 2.12 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315163 | 1KERR 6 | 80/20 | 0.8 MW | 0.8 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315164 | 1KERR 7 | 80/20 | 0.8 MW | 0.8 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316129 | AC1-054 C | 80/20 | 0.84 MW | 0.84 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316131 | AB2-060 C | 80/20 | 1.03 MW | 1.03 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 938371 | AE1-056 C | Adder | 5.2 MW | 4.42 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 939181 | AE1-148 C | 80/20 | 7.42 MW | 7.42 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 941031 | AE2-094 C | 80/20 | 38.95 MW | 38.95 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 941791 | AE2-182 C | 80/20 | 1.69 MW | 1.69 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 946281 | AF1-292 C | 80/20 | 1.26 MW | 1.26 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 946301 | AF1-294 C | Adder | 3.31 MW | 2.81 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 957481 | AF2-042 C | 80/20 | 49.51 MW | 49.51 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 957521 | AF2-046 C | Adder | 13.17 MW | 11.2 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 957531 | AF2-047 C | Adder | 13.01 MW | 11.06 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 958211 | AF2-115 C | Adder | 2.02 MW | 1.72 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 938771 | AE1-103 C | Adder | 2.22 MW | 1.89 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 314507 | 3THOMPSN | Adder | 1.49 MW | 1.26 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 942341 | AE2-247 C | Adder | 1.1 MW | 0.93 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 943461 | AF1-017 C | Adder | 0.99 MW | 0.84 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 944871 | AF1-152 C | Adder | 3.96 MW | 3.37 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315102 | 1BRUNSWICKG1 | 80/20 | 6.73 MW | 6.73 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315103 | 1BRUNSWICKG2 | 80/20 | 6.73 MW | 6.73 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315104 | 1BRUNSWICKG3 | 80/20 | 6.73 MW | 6.73 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315105 | 1BRUNSWICKS1 | 80/20 | 13.97 MW | 13.97 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315172 | 1LOISA A | 80/20 | 2.6 MW | 2.6 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315173 | 1LOISA B | 80/20 | 2.62 MW | 2.62 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315174 | 1LOISA C | 80/20 | 2.62 MW | 2.62 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315175 | 1LOISA D | 80/20 | 2.62 MW | 2.62 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315176 | 1LOISA E | 80/20 | 5.34 MW | 5.34 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315177 | 1S ANNAG1 | 80/20 | 2.57 MW | 2.57 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315178 | 1S ANNAS1 | 80/20 | 1.32 MW | 1.32 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315179 | 1S ANNAG2 | 80/20 | 2.57 MW | 2.57 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315180 | 1S ANNAS2 | 80/20 | 1.32 MW | 1.32 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315225 | 1N ANNA1 | 80/20 | 90.64 MW | 90.64 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315226 | 1N ANNA2 | 80/20 | 90.65 MW | 90.65 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315241 | 1Z1-086 GT1 | 80/20 | 8.62 MW | 8.62 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315242 | 1Z1-086 GT2 | 80/20 | 8.63 MW | 8.63 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315243 | 1Z1-086 GT3 | 80/20 | 8.63 MW | 8.63 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315244 | 1Z1-086 ST | 80/20 | 15.01 MW | 15.01 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315260 | 1GOSPORTA | Adder | 1.57 MW | 1.33 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315261 | 1GOSPORTB | Adder | 2.01 MW | 1.71 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315262 | 1GOSPORTC | Adder | 1.7 MW | 1.45 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315611 | 6Z1-036WIND | Adder | 5.13 MW | 4.36 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 946371 | AF1-301 C | 80/20 | 21.01 MW | 21.01 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 966001 | AG1-469 C | 80/20 | 1.98 MW | 1.98 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 941501 | AE2-147 C | Adder | 11.88 MW | 10.1 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 957871 | AF2-081 C | Adder | 7.45 MW | 6.33 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 958161 | AF2-110 C | Adder | 1.02 MW | 0.87 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 926071 | AC1-086 C | Adder | 16.82 MW | 14.3 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 936261 | AD2-033 C | 80/20 | 10.62 MW | 10.62 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 933291 | AC2-141 C | Adder | 22.46 MW | 19.09 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 934621 | AD1-088 C | 80/20 | 10.4 MW | 10.4 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 939411 | AE1-173 C | 80/20 | 82.28 MW | 82.28 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 933981 | AD1-022 C | Adder | 6.73 MW | 5.72 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 961681 | AG1-008 C | Adder | 13.2 MW | 11.22 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 962571 | AG1-106 C | Adder | 4.68 MW | 3.98 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 208900 | BRIS G1 | 80/20 | -2.05 MW | -2.05 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 208901 | BRIS G2 | 80/20 | -2.42 MW | -2.42 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316023 | AB2-100 C2 | 80/20 | 0.66 MW | 0.66 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316192 | AB2-158 C | 80/20 | 3.64 MW | 3.64 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316210 | AC1-098 C | Adder | 4.83 MW | 4.11 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316212 | AC1-099 C | Adder | 1.62 MW | 1.38 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316233 | AE1-074 C | 80/20 | 2.16 MW | 2.16 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316237 | AB2-079 C O1 | 80/20 | 0.23 MW | 0.23 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316238 | AB2-078 C O1 | 80/20 | 0.23 MW | 0.23 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316239 | AB2-077 C O1 | 80/20 | 0.23 MW | 0.23 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316258 | AE1-075 C | 80/20 | 0.28 MW | 0.28 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316274 | AC1-208 C | Adder | 7.14 MW | 6.07 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316313 | AB2-026 C | 80/20 | 0.3 MW | 0.3 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316315 | AB2-025 C | 80/20 | 0.29 MW | 0.29 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316336 | AC2-165 C | 80/20 | 9.11 MW | 9.11 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316365 | AB2-100 C1 | 80/20 | 0.66 MW | 0.66 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316405 | AF2-144 C | 80/20 | 0.24 MW | 0.24 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316181 | AB2-040 GEN | 80/20 | 6.09 MW | 6.09 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 313527 | AB2-043 C | 80/20 | 0.36 MW | 0.36 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316087 | AB2-174 C | 80/20 | 0.81 MW | 0.81 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316311 | AC2-079 C | Adder | 4.23 MW | 3.6 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316349 | AD2-085 C | Adder | 2.54 MW | 2.16 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 940661 | AE2-053 C | 80/20 | 2.75 MW | 2.75 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 941291 | AE2-123 C | Adder | 21.68 MW | 18.43 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 941301 | AE2-124 C | Adder | 19.72 MW | 16.77 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 941591 | AE2-156 C | Adder | 13.21 MW | 11.23 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 944581 | AF1-123 C | Adder | 36.0 MW | 30.6 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 944591 | AF1-124 C | Adder | 36.0 MW | 30.6 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 944601 | AF1-125 C | Adder | 36.0 MW | 30.6 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 946011 | AF1-266 C | 80/20 | 11.36 MW | 11.36 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 957431 | AF2-037 C | 80/20 | 28.29 MW | 28.29 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 957691 | AF2-063 C | 80/20 | 45.14 MW | 45.14 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 962491 | AG1-098 C | 80/20 | 9.37 MW | 9.37 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 962561 | AG1-105 C | Adder | 7.26 MW | 6.17 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 962841 | AG1-133 C | 80/20 | 57.44 MW | 57.44 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 963291 | AG1-178 C | 80/20 | 60.54 MW | 60.54 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 963311 | AG1-180 C | 80/20 | 2.28 MW | 2.28 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 963321 | AG1-181 C | 80/20 | 13.76 MW | 13.76 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 963351 | AG1-184 C | 80/20 | 32.62 MW | 32.62 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 963361 | AG1-185 C | 80/20 | 6.66 MW | 6.66 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 964241 | AG1-285 C | 80/20 | 10.26 MW | 10.26 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 964421 | AG1-305 C | 80/20 | 35.51 MW | 35.51 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 964951 | AG1-359 C | Adder | 17.0 MW | 14.45 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 965001 | AG1-364 C | Adder | 5.28 MW | 4.49 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 965601 | AG1-428 C | 80/20 | 3.93 MW | 3.93 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 965641 | AG1-432 C | Adder | 15.94 MW | 13.55 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 965691 | AG1-437 C | Adder | 7.79 MW | 6.62 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 965701 | AG1-438 C | Adder | 7.79 MW | 6.62 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 965741 | AG1-442 C | Adder | 4.55 MW | 3.86 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 965751 | AG1-443 C | Adder | 4.55 MW | 3.86 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 965771 | AG1-445 C | 80/20 | 3.56 MW | 3.56 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 965781 | AG1-446 C | 80/20 | 3.56 MW | 3.56 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 965811 | AG1-449 C | 80/20 | 22.72 MW | 22.72 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 965831 | AG1-451 C | Adder | 2.66 MW | 2.26 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 313764 | 3SOCKMAN | 80/20 | 0.57 MW | 0.57 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 932631 | AC2-084 C | Adder | 5.16 MW | 4.39 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 934321 | AD1-056 C | Adder | 4.96 MW | 4.21 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 934331 | AD1-057 C | Adder | 2.77 MW | 2.35 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 934501 | AD1-074 C | Adder | 25.8 MW | 21.93 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 934511 | AD1-075 C | Adder | 6.45 MW | 5.48 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 934611 | AD1-087 C | 80/20 | 0.95 MW | 0.95 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 935171 | AD1-152 C | 80/20 | 0.98 MW | 0.98 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 937481 | AD2-202 C | 80/20 | 0.28 MW | 0.28 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 938531 | AE1-072 C | Adder | 13.1 MW | 11.14 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 939191 | AE1-149 C | Adder | 7.69 MW | 6.53 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 940481 | AE2-033 C | 80/20 | 13.57 MW | 13.57 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 940541 | AE2-040 C | 80/20 | 2.42 MW | 2.42 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 940641 | AE2-051 C | 80/20 | 16.56 MW | 16.56 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 940651 | AE2-052 C | Adder | 2.56 MW | 2.18 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 941101 | AE2-104 C | Adder | 2.5 MW | 2.12 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 941281 | AE2-122 C | Adder | 21.09 MW | 17.93 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 942461 | AE2-259 C | Adder | 7.97 MW | 6.77 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 945811 | AF1-246 C | 80/20 | 6.93 MW | 6.93 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316303 | AF2-085 | 80/20 | 4.03 MW | 4.03 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 22.04 MW | 22.04 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 17.57 MW | 17.57 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 78.17 MW | 78.17 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | NY | PJM->LTFIMP_NY | CLTF | 2.29 MW | 2.29 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.94 MW | 0.94 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | WEC | LTFEXP_WEC->PJM | CLTF | 0.47 MW | 0.47 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | CPLE | LTFEXP_CPLE->PJM | CLTF | 9.34 MW | 9.34 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | TVA | LTFEXP_TVA->PJM | CLTF | 4.88 MW | 4.88 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | MEC | LTFEXP_MEC->PJM | CLTF | 2.97 MW | 2.97 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | LAGN | LTFEXP_LAGN->PJM | CLTF | 6.15 MW | 6.15 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.18 MW | 0.18 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 4.45 MW | 4.45 MW |
| Details for 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 961791 | AG1-021 C | Adder | 1.61 MW | 1.37 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 961891 | AG1-030 C | Adder | 12.15 MW | 10.33 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 961941 | AG1-037 C | Adder | 0.39 MW | 0.33 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 962331 | AG1-082 C | Adder | 1.57 MW | 1.34 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 962341 | AG1-083 C | Adder | 1.57 MW | 1.34 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 963041 | AG1-153 C | 80/20 | 5.4 MW | 5.4 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 963111 | AG1-160 C | 80/20 | 5.47 MW | 5.47 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 963171 | AG1-166 C | Adder | 1.61 MW | 1.37 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 963181 | AG1-167 C | Adder | 1.61 MW | 1.37 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 963191 | AG1-168 C | Adder | 1.61 MW | 1.37 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 963201 | AG1-169 C | Adder | 1.61 MW | 1.37 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 963211 | AG1-170 C | Adder | 1.61 MW | 1.37 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 963301 | AG1-179 C | 80/20 | 4.71 MW | 4.71 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 964111 | AG1-272 C | Adder | 2.1 MW | 1.78 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 964121 | AG1-273 C | Adder | 2.1 MW | 1.78 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 964131 | AG1-274 C | Adder | 2.1 MW | 1.78 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 964791 | AG1-342 C | Adder | 3.37 MW | 2.87 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 964801 | AG1-343 C | Adder | 4.65 MW | 3.95 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 966801 | AG1-551 C | Adder | 1.63 MW | 1.39 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 966811 | AG1-552 C | Adder | 1.65 MW | 1.4 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 965191 | AG1-384 C | Adder | 2.1 MW | 1.78 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 965291 | AG1-394 C | Adder | 1.6 MW | 1.36 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 965591 | AG1-427 C | 80/20 | 9.74 MW | 9.74 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 965721 | AG1-440 C | 80/20 | 6.16 MW | 6.16 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 965731 | AG1-441 C | 80/20 | 6.16 MW | 6.16 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 966361 | AG1-505 C | 80/20 | 16.08 MW | 16.08 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 966371 | AG1-506 C | 80/20 | 16.08 MW | 16.08 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 966621 | AG1-532 C | 80/20 | 1.14 MW | 1.14 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 313506 | AB1-173 C OP | 80/20 | 0.77 MW | 0.77 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 313853 | 3PONTONDP | Adder | 0.54 MW | 0.46 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 314704 | 3LAWRENC | 80/20 | 0.21 MW | 0.21 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315153 | 1CLOVER1 | 80/20 | 9.69 MW | 9.69 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315154 | 1CLOVER2 | 80/20 | 9.6 MW | 9.6 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315158 | 1KERR 1 | 80/20 | 0.28 MW | 0.28 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315159 | 1KERR 2 | 80/20 | 0.8 MW | 0.8 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315160 | 1KERR 3 | 80/20 | 0.8 MW | 0.8 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315161 | 1KERR 4 | 80/20 | 0.8 MW | 0.8 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315162 | 1KERR 5 | 80/20 | 0.8 MW | 0.8 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 934521 | AD1-076 C | Adder | 9.37 MW | 7.96 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 942931 | AE2-313 C | 80/20 | 35.08 MW | 35.08 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 944011 | AF1-069 C | 80/20 | 12.73 MW | 12.73 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 958801 | AF2-171 C | Adder | 12.11 MW | 10.29 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 959311 | AF2-222 C | Adder | 13.57 MW | 11.53 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 960061 | AF2-297 C | Adder | 6.31 MW | 5.36 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 960081 | AF2-299 C | 80/20 | 2.12 MW | 2.12 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315163 | 1KERR 6 | 80/20 | 0.8 MW | 0.8 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315164 | 1KERR 7 | 80/20 | 0.8 MW | 0.8 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316129 | AC1-054 C | 80/20 | 0.84 MW | 0.84 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316131 | AB2-060 C | 80/20 | 1.03 MW | 1.03 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 938371 | AE1-056 C | Adder | 5.2 MW | 4.42 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 939181 | AE1-148 C | 80/20 | 7.42 MW | 7.42 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 941031 | AE2-094 C | 80/20 | 38.95 MW | 38.95 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 941791 | AE2-182 C | 80/20 | 1.69 MW | 1.69 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 946281 | AF1-292 C | 80/20 | 1.26 MW | 1.26 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 946301 | AF1-294 C | Adder | 3.31 MW | 2.81 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 957481 | AF2-042 C | 80/20 | 49.51 MW | 49.51 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 957521 | AF2-046 C | Adder | 13.17 MW | 11.2 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 957531 | AF2-047 C | Adder | 13.01 MW | 11.06 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 958211 | AF2-115 C | Adder | 2.02 MW | 1.72 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 938771 | AE1-103 C | Adder | 2.22 MW | 1.89 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 314507 | 3THOMPSN | Adder | 1.49 MW | 1.26 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 942341 | AE2-247 C | Adder | 1.1 MW | 0.93 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 943461 | AF1-017 C | Adder | 0.99 MW | 0.84 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 944871 | AF1-152 C | Adder | 3.96 MW | 3.37 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315102 | 1BRUNSWICKG1 | 80/20 | 6.73 MW | 6.73 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315103 | 1BRUNSWICKG2 | 80/20 | 6.73 MW | 6.73 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315104 | 1BRUNSWICKG3 | 80/20 | 6.73 MW | 6.73 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315105 | 1BRUNSWICKS1 | 80/20 | 13.97 MW | 13.97 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315172 | 1LOISA A | 80/20 | 2.6 MW | 2.6 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315173 | 1LOISA B | 80/20 | 2.62 MW | 2.62 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315174 | 1LOISA C | 80/20 | 2.62 MW | 2.62 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315175 | 1LOISA D | 80/20 | 2.62 MW | 2.62 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315176 | 1LOISA E | 80/20 | 5.34 MW | 5.34 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315177 | 1S ANNAG1 | 80/20 | 2.57 MW | 2.57 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315178 | 1S ANNAS1 | 80/20 | 1.32 MW | 1.32 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315179 | 1S ANNAG2 | 80/20 | 2.57 MW | 2.57 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315180 | 1S ANNAS2 | 80/20 | 1.32 MW | 1.32 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315225 | 1N ANNA1 | 80/20 | 90.64 MW | 90.64 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315226 | 1N ANNA2 | 80/20 | 90.65 MW | 90.65 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315241 | 1Z1-086 GT1 | 80/20 | 8.62 MW | 8.62 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315242 | 1Z1-086 GT2 | 80/20 | 8.63 MW | 8.63 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315243 | 1Z1-086 GT3 | 80/20 | 8.63 MW | 8.63 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315244 | 1Z1-086 ST | 80/20 | 15.01 MW | 15.01 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315260 | 1GOSPORTA | Adder | 1.57 MW | 1.33 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315261 | 1GOSPORTB | Adder | 2.01 MW | 1.71 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315262 | 1GOSPORTC | Adder | 1.7 MW | 1.45 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315611 | 6Z1-036WIND | Adder | 5.13 MW | 4.36 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 946371 | AF1-301 C | 80/20 | 21.01 MW | 21.01 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 966001 | AG1-469 C | 80/20 | 1.98 MW | 1.98 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 941501 | AE2-147 C | Adder | 11.88 MW | 10.1 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 957871 | AF2-081 C | Adder | 7.45 MW | 6.33 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 958161 | AF2-110 C | Adder | 1.02 MW | 0.87 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 926071 | AC1-086 C | Adder | 16.82 MW | 14.3 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 936261 | AD2-033 C | 80/20 | 10.62 MW | 10.62 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 933291 | AC2-141 C | Adder | 22.46 MW | 19.09 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 934621 | AD1-088 C | 80/20 | 10.4 MW | 10.4 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 939411 | AE1-173 C | 80/20 | 82.28 MW | 82.28 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 933981 | AD1-022 C | Adder | 6.73 MW | 5.72 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 961681 | AG1-008 C | Adder | 13.2 MW | 11.22 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 962571 | AG1-106 C | Adder | 4.68 MW | 3.98 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 208900 | BRIS G1 | 80/20 | -2.05 MW | -2.05 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 208901 | BRIS G2 | 80/20 | -2.42 MW | -2.42 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316023 | AB2-100 C2 | 80/20 | 0.66 MW | 0.66 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316192 | AB2-158 C | 80/20 | 3.64 MW | 3.64 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316210 | AC1-098 C | Adder | 4.83 MW | 4.11 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316212 | AC1-099 C | Adder | 1.62 MW | 1.38 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316222 | AC1-221 C | Adder | 6.41 MW | 5.45 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316233 | AE1-074 C | 80/20 | 2.16 MW | 2.16 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316237 | AB2-079 C O1 | 80/20 | 0.23 MW | 0.23 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316238 | AB2-078 C O1 | 80/20 | 0.23 MW | 0.23 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316239 | AB2-077 C O1 | 80/20 | 0.23 MW | 0.23 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316258 | AE1-075 C | 80/20 | 0.28 MW | 0.28 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316274 | AC1-208 C | Adder | 7.14 MW | 6.07 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316313 | AB2-026 C | 80/20 | 0.3 MW | 0.3 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316315 | AB2-025 C | 80/20 | 0.29 MW | 0.29 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316336 | AC2-165 C | 80/20 | 9.11 MW | 9.11 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316365 | AB2-100 C1 | 80/20 | 0.66 MW | 0.66 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316405 | AF2-144 C | 80/20 | 0.24 MW | 0.24 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316181 | AB2-040 GEN | 80/20 | 6.09 MW | 6.09 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 313527 | AB2-043 C | 80/20 | 0.36 MW | 0.36 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316087 | AB2-174 C | 80/20 | 0.81 MW | 0.81 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316311 | AC2-079 C | Adder | 4.23 MW | 3.6 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316349 | AD2-085 C | Adder | 2.54 MW | 2.16 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 940661 | AE2-053 C | 80/20 | 2.75 MW | 2.75 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 941291 | AE2-123 C | Adder | 21.68 MW | 18.43 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 941301 | AE2-124 C | Adder | 19.72 MW | 16.77 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 941591 | AE2-156 C | Adder | 13.21 MW | 11.23 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 944581 | AF1-123 C | Adder | 36.0 MW | 30.6 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 944591 | AF1-124 C | Adder | 36.0 MW | 30.6 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 944601 | AF1-125 C | Adder | 36.0 MW | 30.6 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 946011 | AF1-266 C | 80/20 | 11.36 MW | 11.36 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 957431 | AF2-037 C | 80/20 | 28.29 MW | 28.29 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 957691 | AF2-063 C | 80/20 | 45.14 MW | 45.14 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 962491 | AG1-098 C | 80/20 | 9.37 MW | 9.37 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 962561 | AG1-105 C | Adder | 7.26 MW | 6.17 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 963291 | AG1-178 C | 80/20 | 60.54 MW | 60.54 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 963311 | AG1-180 C | 80/20 | 2.28 MW | 2.28 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 963321 | AG1-181 C | 80/20 | 13.76 MW | 13.76 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 963351 | AG1-184 C | 80/20 | 32.62 MW | 32.62 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 963361 | AG1-185 C | 80/20 | 6.66 MW | 6.66 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 964241 | AG1-285 C | 80/20 | 10.26 MW | 10.26 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 964421 | AG1-305 C | 80/20 | 35.51 MW | 35.51 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 964951 | AG1-359 C | Adder | 17.0 MW | 14.45 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 965001 | AG1-364 C | Adder | 5.28 MW | 4.49 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 965601 | AG1-428 C | 80/20 | 3.93 MW | 3.93 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 965641 | AG1-432 C | Adder | 15.94 MW | 13.55 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 965691 | AG1-437 C | Adder | 7.79 MW | 6.62 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 965701 | AG1-438 C | Adder | 7.79 MW | 6.62 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 965741 | AG1-442 C | Adder | 4.55 MW | 3.86 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 965751 | AG1-443 C | Adder | 4.55 MW | 3.86 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 965771 | AG1-445 C | 80/20 | 3.56 MW | 3.56 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 965781 | AG1-446 C | 80/20 | 3.56 MW | 3.56 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 965811 | AG1-449 C | 80/20 | 22.72 MW | 22.72 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 965831 | AG1-451 C | Adder | 2.66 MW | 2.26 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 313764 | 3SOCKMAN | 80/20 | 0.57 MW | 0.57 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 932631 | AC2-084 C | Adder | 5.16 MW | 4.39 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 934321 | AD1-056 C | Adder | 4.96 MW | 4.21 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 934331 | AD1-057 C | Adder | 2.77 MW | 2.35 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 934501 | AD1-074 C | Adder | 25.8 MW | 21.93 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 934511 | AD1-075 C | Adder | 6.45 MW | 5.48 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 934611 | AD1-087 C | 80/20 | 0.95 MW | 0.95 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 935171 | AD1-152 C | 80/20 | 0.98 MW | 0.98 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 937481 | AD2-202 C | 80/20 | 0.28 MW | 0.28 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 938531 | AE1-072 C | Adder | 13.1 MW | 11.14 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 939191 | AE1-149 C | Adder | 7.69 MW | 6.53 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 940481 | AE2-033 C | 80/20 | 13.57 MW | 13.57 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 940541 | AE2-040 C | 80/20 | 2.42 MW | 2.42 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 940641 | AE2-051 C | 80/20 | 16.56 MW | 16.56 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 940651 | AE2-052 C | Adder | 2.56 MW | 2.18 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 941101 | AE2-104 C | Adder | 2.5 MW | 2.12 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 941281 | AE2-122 C | Adder | 21.09 MW | 17.93 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 942461 | AE2-259 C | Adder | 7.97 MW | 6.77 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 945811 | AF1-246 C | 80/20 | 6.93 MW | 6.93 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316303 | AF2-085 | 80/20 | 4.03 MW | 4.03 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 22.04 MW | 22.04 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 17.57 MW | 17.57 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 78.17 MW | 78.17 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | NY | PJM->LTFIMP_NY | CLTF | 2.29 MW | 2.29 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.94 MW | 0.94 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | WEC | LTFEXP_WEC->PJM | CLTF | 0.47 MW | 0.47 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | CPLE | LTFEXP_CPLE->PJM | CLTF | 9.34 MW | 9.34 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | TVA | LTFEXP_TVA->PJM | CLTF | 4.88 MW | 4.88 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | MEC | LTFEXP_MEC->PJM | CLTF | 2.97 MW | 2.97 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | LAGN | LTFEXP_LAGN->PJM | CLTF | 6.15 MW | 6.15 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.18 MW | 0.18 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 4.45 MW | 4.45 MW |
| Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 961671 | AG1-007 C | Adder | 1.26 MW | 1.07 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 961941 | AG1-037 C | Adder | 0.68 MW | 0.57 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 962331 | AG1-082 C | Adder | 2.71 MW | 2.3 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 962341 | AG1-083 C | Adder | 2.71 MW | 2.3 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 963041 | AG1-153 C | 80/20 | 9.27 MW | 9.27 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 963111 | AG1-160 C | 80/20 | 9.42 MW | 9.42 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 963301 | AG1-179 C | Adder | 7.3 MW | 6.21 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 964111 | AG1-272 C | Adder | 2.65 MW | 2.25 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 964121 | AG1-273 C | Adder | 2.65 MW | 2.25 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 964131 | AG1-274 C | Adder | 2.65 MW | 2.25 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 964791 | AG1-342 C | Adder | 5.11 MW | 4.34 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 964801 | AG1-343 C | Adder | 7.96 MW | 6.77 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 966801 | AG1-551 C | Adder | 2.83 MW | 2.4 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 966811 | AG1-552 C | Adder | 2.73 MW | 2.32 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 965191 | AG1-384 C | Adder | 2.65 MW | 2.25 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 965291 | AG1-394 C | Adder | 2.73 MW | 2.32 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 965591 | AG1-427 C | Adder | 13.44 MW | 11.43 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 965721 | AG1-440 C | Adder | 9.54 MW | 8.11 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 965731 | AG1-441 C | Adder | 9.54 MW | 8.11 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 966361 | AG1-505 C | 80/20 | 27.25 MW | 27.25 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 966371 | AG1-506 C | 80/20 | 27.25 MW | 27.25 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 966621 | AG1-532 C | Adder | 1.86 MW | 1.58 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 315131 | 1EDGECMA | Adder | 20.73 MW | 17.62 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 315153 | 1CLOVER1 | 80/20 | 15.65 MW | 15.65 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 315154 | 1CLOVER2 | 80/20 | 15.5 MW | 15.5 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 934521 | AD1-076 C | Adder | 16.5 MW | 14.02 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 942931 | AE2-313 C | 80/20 | 60.28 MW | 60.28 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 944011 | AF1-069 C | 80/20 | 21.98 MW | 21.98 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 959311 | AF2-222 C | Adder | 4.68 MW | 3.98 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 960061 | AF2-297 C | Adder | 9.97 MW | 8.47 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 960081 | AF2-299 C | Adder | 3.45 MW | 2.93 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 939181 | AE1-148 C | Adder | 11.17 MW | 9.5 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 940571 | AE2-044 C | Adder | 5.8 MW | 4.93 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 941031 | AE2-094 C | 80/20 | 67.26 MW | 67.26 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 941791 | AE2-182 C | Adder | 2.14 MW | 1.82 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 946281 | AF1-292 C | Adder | 2.05 MW | 1.75 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 957481 | AF2-042 C | 80/20 | 81.0 MW | 81.0 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 957521 | AF2-046 C | Adder | 22.61 MW | 19.22 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 957531 | AF2-047 C | Adder | 23.07 MW | 19.61 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 957861 | AF2-080 C | Adder | 10.24 MW | 8.71 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 938771 | AE1-103 C | Adder | 3.9 MW | 3.31 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 314295 | 6BIRDNECK | 80/20 | 0.05 MW | 0.05 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 314507 | 3THOMPSN | Adder | 2.71 MW | 2.3 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 315092 | 1YORKTN3 | Adder | 152.9 MW | 129.97 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 942341 | AE2-247 C | Adder | 1.9 MW | 1.61 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 943461 | AF1-017 C | Adder | 1.72 MW | 1.46 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 944871 | AF1-152 C | Adder | 7.14 MW | 6.07 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 315098 | 1CHESPKA | 80/20 | 0.49 MW | 0.49 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 315099 | 1CHESPKB | 80/20 | 0.82 MW | 0.82 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 315102 | 1BRUNSWICKG1 | 80/20 | 11.56 MW | 11.56 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 315103 | 1BRUNSWICKG2 | 80/20 | 11.56 MW | 11.56 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 315104 | 1BRUNSWICKG3 | 80/20 | 11.56 MW | 11.56 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 315105 | 1BRUNSWICKS1 | 80/20 | 24.01 MW | 24.01 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 315108 | 1ELIZAR1 | 80/20 | 3.64 MW | 3.64 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 315109 | 1ELIZAR2 | 80/20 | 3.58 MW | 3.58 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 315110 | 1ELIZAR3 | 80/20 | 3.69 MW | 3.69 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 315241 | 1Z1-086 GT1 | 80/20 | 14.83 MW | 14.83 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 315242 | 1Z1-086 GT2 | 80/20 | 14.84 MW | 14.84 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 315243 | 1Z1-086 GT3 | 80/20 | 14.84 MW | 14.84 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 315244 | 1Z1-086 ST | 80/20 | 25.83 MW | 25.83 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 315260 | 1GOSPORTA | 80/20 | 2.86 MW | 2.86 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 315261 | 1GOSPORTB | 80/20 | 3.65 MW | 3.65 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 315262 | 1GOSPORTC | 80/20 | 3.1 MW | 3.1 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 315611 | 6Z1-036WIND | Adder | 9.19 MW | 7.81 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 941501 | AE2-147 C | Adder | 21.41 MW | 18.2 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 942001 | AE2-212 C | Adder | 2.14 MW | 1.82 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 957871 | AF2-081 C | 80/20 | 13.55 MW | 13.55 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 958161 | AF2-110 C | Adder | 1.82 MW | 1.54 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 926071 | AC1-086 C | Adder | 28.22 MW | 23.98 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 927021 | AC1-189 C | Adder | 11.28 MW | 9.59 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 936261 | AD2-033 C | Adder | 13.77 MW | 11.7 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 933291 | AC2-141 C | 80/20 | 42.27 MW | 42.27 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 934621 | AD1-088 C | Adder | 13.18 MW | 11.2 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 939411 | AE1-173 C | 80/20 | 145.52 MW | 145.52 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 934011 | AD1-025 C | Adder | 16.76 MW | 14.24 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 933981 | AD1-022 C | Adder | 11.8 MW | 10.03 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 960331 | AF2-324 C | Adder | 9.33 MW | 7.93 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 961681 | AG1-008 C | Adder | 22.66 MW | 19.26 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 962571 | AG1-106 C | Adder | 7.85 MW | 6.67 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 316036 | AC1-147 C | 80/20 | 0.42 MW | 0.42 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 316185 | AD1-033 C | 80/20 | 1.41 MW | 1.41 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 316210 | AC1-098 C | Adder | 8.18 MW | 6.96 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 316212 | AC1-099 C | Adder | 2.74 MW | 2.33 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 316222 | AC1-221 C | Adder | 10.51 MW | 8.93 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 316263 | AC1-034 C | Adder | 8.86 MW | 7.53 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 316274 | AC1-208 C | Adder | 12.02 MW | 10.22 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 316294 | AC1-161 C | 80/20 | 5.83 MW | 5.83 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 316315 | AB2-025 C | 80/20 | 0.48 MW | 0.48 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 316316 | AC1-027 C | 80/20 | 0.36 MW | 0.36 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 963221 | AG1-171 C | Adder | 2.13 MW | 1.81 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 963231 | AG1-172 C | Adder | 2.13 MW | 1.81 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 963241 | AG1-173 C | Adder | 2.13 MW | 1.81 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 963251 | AG1-174 C | Adder | 2.13 MW | 1.81 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 316017 | AA1-139 ULT1 | 80/20 | 1.24 MW | 1.24 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 316018 | AA1-139 ULT2 | 80/20 | 1.24 MW | 1.24 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 316181 | AB2-040 GEN | Adder | 9.99 MW | 8.49 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 316375 | AC2-012 C | 80/20 | 1.54 MW | 1.54 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 316311 | AC2-079 C | Adder | 7.34 MW | 6.24 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 316349 | AD2-085 C | Adder | 4.38 MW | 3.72 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 316388 | AE2-253 GEN | 80/20 | 2.25 MW | 2.25 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 961611 | AG1-000B C | Adder | 17.28 MW | 14.69 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 940661 | AE2-053 C | Adder | 4.14 MW | 3.52 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 941291 | AE2-123 C | 80/20 | 39.52 MW | 39.52 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 941301 | AE2-124 C | 80/20 | 35.96 MW | 35.96 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 941591 | AE2-156 C | 80/20 | 24.07 MW | 24.07 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 942551 | AE2-270 C | Adder | 26.7 MW | 22.69 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 944581 | AF1-123 C | 80/20 | 66.06 MW | 66.06 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 944591 | AF1-124 C | 80/20 | 66.06 MW | 66.06 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 944601 | AF1-125 C | 80/20 | 66.06 MW | 66.06 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 945361 | AF1-201 C | Adder | 15.84 MW | 13.46 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 946011 | AF1-266 C | 80/20 | 18.72 MW | 18.72 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 957711 | AF2-065 C | Adder | 13.61 MW | 11.57 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 961711 | AG1-011 C | Adder | 28.46 MW | 24.19 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 962491 | AG1-098 C | Adder | 11.93 MW | 10.14 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 962561 | AG1-105 C | Adder | 10.89 MW | 9.26 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 963291 | AG1-178 C | 80/20 | 105.71 MW | 105.71 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 963311 | AG1-180 C | Adder | 3.55 MW | 3.01 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 963321 | AG1-181 C | Adder | 17.73 MW | 15.07 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 963351 | AG1-184 C | 80/20 | 56.95 MW | 56.95 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 963361 | AG1-185 C | Adder | 8.58 MW | 7.29 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 964241 | AG1-285 C | Adder | 14.04 MW | 11.93 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 964951 | AG1-359 C | 80/20 | 31.03 MW | 31.03 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 965001 | AG1-364 C | 80/20 | 9.62 MW | 9.62 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 965601 | AG1-428 C | Adder | 6.09 MW | 5.18 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 965691 | AG1-437 C | Adder | 13.64 MW | 11.59 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 965701 | AG1-438 C | Adder | 13.64 MW | 11.59 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 965711 | AG1-439 C | Adder | 31.53 MW | 26.8 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 965741 | AG1-442 C | Adder | 7.96 MW | 6.76 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 965751 | AG1-443 C | Adder | 7.96 MW | 6.76 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 965761 | AG1-444 C | Adder | 16.82 MW | 14.29 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 965771 | AG1-445 C | Adder | 5.51 MW | 4.68 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 965781 | AG1-446 C | Adder | 5.51 MW | 4.68 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 965811 | AG1-449 C | 80/20 | 39.03 MW | 39.03 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 966611 | AG1-531 C | Adder | 6.4 MW | 5.44 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 313764 | 3SOCKMAN | Adder | 0.95 MW | 0.8 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 932631 | AC2-084 C | Adder | 8.75 MW | 7.44 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 934321 | AD1-056 C | Adder | 8.38 MW | 7.13 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 934331 | AD1-057 C | Adder | 4.68 MW | 3.98 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 934501 | AD1-074 C | Adder | 45.43 MW | 38.61 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 934511 | AD1-075 C | Adder | 11.36 MW | 9.65 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 934611 | AD1-087 C | 80/20 | 1.54 MW | 1.54 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 935161 | AD1-151 C | Adder | 15.49 MW | 13.17 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 935171 | AD1-152 C | 80/20 | 1.58 MW | 1.58 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 937481 | AD2-202 C | 80/20 | 0.45 MW | 0.45 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 938531 | AE1-072 C | 80/20 | 23.83 MW | 23.83 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 939191 | AE1-149 C | Adder | 12.14 MW | 10.32 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 940481 | AE2-033 C | 80/20 | 22.36 MW | 22.36 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 940541 | AE2-040 C | 80/20 | 3.98 MW | 3.98 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 940641 | AE2-051 C | 80/20 | 29.05 MW | 29.05 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 940651 | AE2-052 C | Adder | 4.05 MW | 3.44 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 941101 | AE2-104 C | Adder | 4.45 MW | 3.78 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 941281 | AE2-122 C | 80/20 | 38.46 MW | 38.46 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 944141 | AF1-082 C | Adder | 3.73 MW | 3.17 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | 945811 | AF1-246 C | 80/20 | 11.34 MW | 11.34 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 55.36 MW | 55.36 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 35.61 MW | 35.61 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 136.66 MW | 136.66 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | NY | PJM->LTFIMP_NY | CLTF | 2.56 MW | 2.56 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | LGEE | LTFEXP_LGEE->PJM | CLTF | 2.19 MW | 2.19 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | WEC | LTFEXP_WEC->PJM | CLTF | 1.14 MW | 1.14 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | CPLE | LTFEXP_CPLE->PJM | CLTF | 16.06 MW | 16.06 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | TVA | LTFEXP_TVA->PJM | CLTF | 9.37 MW | 9.37 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | MEC | LTFEXP_MEC->PJM | CLTF | 6.6 MW | 6.6 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | LAGN | LTFEXP_LAGN->PJM | CLTF | 11.83 MW | 11.83 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.42 MW | 0.42 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 7.66 MW | 7.66 MW |
| Details for 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 961671 | AG1-007 C | Adder | 0.41 MW | 0.35 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 961941 | AG1-037 C | Adder | 0.21 MW | 0.18 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 962331 | AG1-082 C | Adder | 0.83 MW | 0.71 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 962341 | AG1-083 C | Adder | 0.83 MW | 0.71 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 963041 | AG1-153 C | 80/20 | 3.73 MW | 3.73 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 963111 | AG1-160 C | 80/20 | 3.8 MW | 3.8 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 963301 | AG1-179 C | Adder | 2.13 MW | 1.81 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 964791 | AG1-342 C | Adder | 1.55 MW | 1.32 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 964801 | AG1-343 C | Adder | 2.41 MW | 2.05 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 966801 | AG1-551 C | Adder | 0.9 MW | 0.77 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 966811 | AG1-552 C | Adder | 0.84 MW | 0.72 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 965291 | AG1-394 C | Adder | 0.82 MW | 0.7 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 965721 | AG1-440 C | Adder | 2.89 MW | 2.46 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 965731 | AG1-441 C | Adder | 2.89 MW | 2.46 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 966361 | AG1-505 C | 80/20 | 10.75 MW | 10.75 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 966371 | AG1-506 C | 80/20 | 10.75 MW | 10.75 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 966621 | AG1-532 C | Adder | 0.57 MW | 0.48 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 315131 | 1EDGECMA | Adder | 6.79 MW | 5.77 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 315136 | 1ROSEMG1 | 80/20 | 0.73 MW | 0.73 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 315137 | 1ROSEMS1 | 80/20 | 0.45 MW | 0.45 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 315138 | 1ROSEMG2 | 80/20 | 0.34 MW | 0.34 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 315139 | 1GASTONA | 80/20 | 1.08 MW | 1.08 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 315153 | 1CLOVER1 | 80/20 | 5.64 MW | 5.64 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 315154 | 1CLOVER2 | 80/20 | 5.59 MW | 5.59 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 934521 | AD1-076 C | Adder | 5.07 MW | 4.31 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 942931 | AE2-313 C | 80/20 | 24.37 MW | 24.37 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 944011 | AF1-069 C | 80/20 | 8.95 MW | 8.95 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 960061 | AF2-297 C | Adder | 3.28 MW | 2.79 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 960081 | AF2-299 C | Adder | 1.05 MW | 0.9 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 939181 | AE1-148 C | Adder | 3.3 MW | 2.8 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 940491 | AE2-034 C | 80/20 | 0.4 MW | 0.4 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 940571 | AE2-044 C | Adder | 1.9 MW | 1.61 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 941011 | AE2-092 C | Adder | -4.78 MW | -4.06 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 941031 | AE2-094 C | 80/20 | 27.4 MW | 27.4 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 946281 | AF1-292 C | Adder | 0.63 MW | 0.53 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 957481 | AF2-042 C | 80/20 | 30.0 MW | 30.0 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 957521 | AF2-046 C | Adder | 6.9 MW | 5.86 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 957531 | AF2-047 C | 80/20 | 7.05 MW | 7.05 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 957861 | AF2-080 C | Adder | 3.31 MW | 2.81 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 938771 | AE1-103 C | Adder | 1.14 MW | 0.97 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 313526 | AB2-022 C | 80/20 | 0.13 MW | 0.13 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 314295 | 6BIRDNECK | 80/20 | 0.01 MW | 0.01 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 314507 | 3THOMPSN | Adder | 0.79 MW | 0.67 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 942341 | AE2-247 C | Adder | 0.49 MW | 0.42 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 943461 | AF1-017 C | Adder | 0.44 MW | 0.38 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 944871 | AF1-152 C | 80/20 | 2.14 MW | 2.14 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 315098 | 1CHESPKA | 80/20 | 0.14 MW | 0.14 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 315099 | 1CHESPKB | 80/20 | 0.24 MW | 0.24 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 315102 | 1BRUNSWICKG1 | 80/20 | 4.64 MW | 4.64 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 315103 | 1BRUNSWICKG2 | 80/20 | 4.64 MW | 4.64 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 315104 | 1BRUNSWICKG3 | 80/20 | 4.64 MW | 4.64 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 315105 | 1BRUNSWICKS1 | 80/20 | 9.65 MW | 9.65 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 315108 | 1ELIZAR1 | 80/20 | 1.07 MW | 1.07 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 315109 | 1ELIZAR2 | 80/20 | 1.05 MW | 1.05 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 315110 | 1ELIZAR3 | 80/20 | 1.09 MW | 1.09 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 315141 | 1GASTONB | 80/20 | 1.08 MW | 1.08 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 315241 | 1Z1-086 GT1 | 80/20 | 5.99 MW | 5.99 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 315242 | 1Z1-086 GT2 | 80/20 | 5.99 MW | 5.99 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 315243 | 1Z1-086 GT3 | 80/20 | 5.99 MW | 5.99 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 315244 | 1Z1-086 ST | 80/20 | 10.43 MW | 10.43 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 315260 | 1GOSPORTA | 80/20 | 0.84 MW | 0.84 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 315261 | 1GOSPORTB | 80/20 | 1.07 MW | 1.07 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 315262 | 1GOSPORTC | 80/20 | 0.91 MW | 0.91 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 315605 | 6W1-029WIND | 80/20 | 0.27 MW | 0.27 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 315611 | 6Z1-036WIND | 80/20 | 2.78 MW | 2.78 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 941501 | AE2-147 C | 80/20 | 6.42 MW | 6.42 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 957871 | AF2-081 C | 80/20 | 4.07 MW | 4.07 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 958161 | AF2-110 C | Adder | 0.52 MW | 0.44 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 926071 | AC1-086 C | 80/20 | 8.84 MW | 8.84 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 927021 | AC1-189 C | Adder | 3.64 MW | 3.1 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 933291 | AC2-141 C | 80/20 | 13.27 MW | 13.27 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 939411 | AE1-173 C | 80/20 | 55.1 MW | 55.1 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 933981 | AD1-022 C | Adder | 3.64 MW | 3.09 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 960331 | AF2-324 C | Adder | 3.06 MW | 2.6 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 961681 | AG1-008 C | Adder | 6.91 MW | 5.88 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 962571 | AG1-106 C | 80/20 | 2.46 MW | 2.46 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 316011 | AB1-132 C OP | 80/20 | 0.83 MW | 0.83 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 316023 | AB2-100 C2 | 80/20 | 0.34 MW | 0.34 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 316036 | AC1-147 C | 80/20 | 0.12 MW | 0.12 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 316185 | AD1-033 C | 80/20 | 0.42 MW | 0.42 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 316210 | AC1-098 C | Adder | 2.59 MW | 2.2 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 316212 | AC1-099 C | Adder | 0.87 MW | 0.74 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 316222 | AC1-221 C | 80/20 | 3.64 MW | 3.64 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 316233 | AE1-074 C | Adder | -3.05 MW | -2.59 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 316246 | AF1-032 C | 80/20 | 0.1 MW | 0.1 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 316263 | AC1-034 C | Adder | 2.9 MW | 2.47 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 316274 | AC1-208 C | Adder | 3.8 MW | 3.23 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 316294 | AC1-161 C | 80/20 | 1.83 MW | 1.83 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 316304 | AE2-227 C | Adder | -0.78 MW | -0.67 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 316305 | AF2-043 C | 80/20 | 0.12 MW | 0.12 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 316315 | AB2-025 C | 80/20 | 0.15 MW | 0.15 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 316316 | AC1-027 C | 80/20 | 0.11 MW | 0.11 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 316320 | Y1-086 C | 80/20 | 0.08 MW | 0.08 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 316321 | Z2-027 C | 80/20 | 0.12 MW | 0.12 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 316336 | AC2-165 C | Adder | -11.14 MW | -9.47 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 316365 | AB2-100 C1 | 80/20 | 0.34 MW | 0.34 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 316017 | AA1-139 ULT1 | 80/20 | 0.37 MW | 0.37 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 316018 | AA1-139 ULT2 | 80/20 | 0.37 MW | 0.37 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 315614 | AA2-178 C | 80/20 | 0.55 MW | 0.55 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 316181 | AB2-040 GEN | Adder | 3.07 MW | 2.61 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 316375 | AC2-012 C | 80/20 | 0.45 MW | 0.45 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 316311 | AC2-079 C | Adder | 1.93 MW | 1.64 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 316349 | AD2-085 C | Adder | 1.14 MW | 0.96 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 316388 | AE2-253 GEN | 80/20 | 0.68 MW | 0.68 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 940661 | AE2-053 C | Adder | 1.22 MW | 1.04 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 941291 | AE2-123 C | 80/20 | 11.74 MW | 11.74 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 941301 | AE2-124 C | 80/20 | 10.7 MW | 10.7 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 941591 | AE2-156 C | 80/20 | 7.06 MW | 7.06 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 944581 | AF1-123 C | 80/20 | 20.22 MW | 20.22 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 944591 | AF1-124 C | 80/20 | 20.22 MW | 20.22 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 944601 | AF1-125 C | 80/20 | 20.22 MW | 20.22 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 946011 | AF1-266 C | 80/20 | 5.83 MW | 5.83 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 962561 | AG1-105 C | Adder | 3.24 MW | 2.76 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 963291 | AG1-178 C | 80/20 | 42.3 MW | 42.3 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 963311 | AG1-180 C | Adder | 1.03 MW | 0.88 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 963351 | AG1-184 C | 80/20 | 22.79 MW | 22.79 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 964951 | AG1-359 C | 80/20 | 9.32 MW | 9.32 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 965001 | AG1-364 C | 80/20 | 2.82 MW | 2.82 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 965601 | AG1-428 C | Adder | 1.78 MW | 1.51 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 965691 | AG1-437 C | Adder | 4.21 MW | 3.58 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 965701 | AG1-438 C | Adder | 4.21 MW | 3.58 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 965711 | AG1-439 C | Adder | 10.22 MW | 8.69 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 965741 | AG1-442 C | Adder | 2.45 MW | 2.09 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 965751 | AG1-443 C | Adder | 2.45 MW | 2.09 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 965761 | AG1-444 C | Adder | 5.45 MW | 4.63 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 965771 | AG1-445 C | Adder | 1.67 MW | 1.42 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 965781 | AG1-446 C | Adder | 1.67 MW | 1.42 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 965811 | AG1-449 C | 80/20 | 15.78 MW | 15.78 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 313764 | 3SOCKMAN | Adder | 0.29 MW | 0.25 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 932631 | AC2-084 C | Adder | 2.77 MW | 2.35 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 934321 | AD1-056 C | Adder | 2.7 MW | 2.29 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 934331 | AD1-057 C | Adder | 1.5 MW | 1.28 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 934501 | AD1-074 C | Adder | 13.97 MW | 11.88 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 934511 | AD1-075 C | Adder | 3.49 MW | 2.97 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 934611 | AD1-087 C | 80/20 | 0.56 MW | 0.56 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 935171 | AD1-152 C | 80/20 | 0.56 MW | 0.56 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 936161 | AD2-022 C | Adder | 3.2 MW | 2.72 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 936171 | AD2-023 C | Adder | 1.87 MW | 1.59 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 937481 | AD2-202 C | 80/20 | 0.16 MW | 0.16 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 938531 | AE1-072 C | 80/20 | 7.16 MW | 7.16 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 938821 | AE1-108 C | Adder | -4.9 MW | -4.16 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 940481 | AE2-033 C | 80/20 | 6.96 MW | 6.96 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 940541 | AE2-040 C | 80/20 | 1.24 MW | 1.24 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 940641 | AE2-051 C | 80/20 | 11.56 MW | 11.56 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 941101 | AE2-104 C | Adder | 1.28 MW | 1.08 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 941281 | AE2-122 C | 80/20 | 11.43 MW | 11.43 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 944141 | AF1-082 C | Adder | 1.22 MW | 1.04 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 945811 | AF1-246 C | 80/20 | 4.2 MW | 4.2 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 14.42 MW | 14.42 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 10.32 MW | 10.32 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 45.7 MW | 45.7 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | NY | PJM->LTFIMP_NY | CLTF | 0.56 MW | 0.56 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.56 MW | 0.56 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | WEC | LTFEXP_WEC->PJM | CLTF | 0.3 MW | 0.3 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | CPLE | LTFEXP_CPLE->PJM | CLTF | 5.54 MW | 5.54 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | TVA | LTFEXP_TVA->PJM | CLTF | 2.79 MW | 2.79 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | MEC | LTFEXP_MEC->PJM | CLTF | 1.81 MW | 1.81 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | LAGN | LTFEXP_LAGN->PJM | CLTF | 3.57 MW | 3.57 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.11 MW | 0.11 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.64 MW | 2.64 MW |
| Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 961671 | AG1-007 C | Adder | 1.05 MW | 0.89 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 961941 | AG1-037 C | Adder | 0.63 MW | 0.54 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 962331 | AG1-082 C | Adder | 2.52 MW | 2.14 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 962341 | AG1-083 C | Adder | 2.52 MW | 2.14 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963041 | AG1-153 C | Adder | 6.62 MW | 5.63 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963111 | AG1-160 C | Adder | 6.72 MW | 5.71 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963301 | AG1-179 C | Adder | 5.56 MW | 4.73 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 964791 | AG1-342 C | Adder | 3.7 MW | 3.14 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 964801 | AG1-343 C | Adder | 7.46 MW | 6.34 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 966801 | AG1-551 C | Adder | 2.57 MW | 2.18 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 966811 | AG1-552 C | Adder | 2.27 MW | 1.93 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965291 | AG1-394 C | Adder | 2.56 MW | 2.17 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965591 | AG1-427 C | Adder | 9.9 MW | 8.42 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965721 | AG1-440 C | Adder | 7.27 MW | 6.18 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965731 | AG1-441 C | Adder | 7.27 MW | 6.18 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 966361 | AG1-505 C | Adder | 19.45 MW | 16.53 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 966371 | AG1-506 C | Adder | 19.45 MW | 16.53 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 966621 | AG1-532 C | Adder | 1.44 MW | 1.23 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315131 | 1EDGECMA | Adder | 16.75 MW | 14.24 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 934521 | AD1-076 C | 80/20 | 16.61 MW | 16.61 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 942931 | AE2-313 C | 80/20 | 42.99 MW | 42.99 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 944011 | AF1-069 C | 80/20 | 15.67 MW | 15.67 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 960061 | AF2-297 C | Adder | 7.11 MW | 6.04 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 960081 | AF2-299 C | Adder | 2.67 MW | 2.27 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 939181 | AE1-148 C | Adder | 8.34 MW | 7.09 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 940491 | AE2-034 C | 80/20 | 1.36 MW | 1.36 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 940571 | AE2-044 C | Adder | 4.69 MW | 3.99 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 941031 | AE2-094 C | 80/20 | 47.95 MW | 47.95 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 946281 | AF1-292 C | Adder | 1.59 MW | 1.35 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 957481 | AF2-042 C | Adder | 57.97 MW | 49.27 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 957521 | AF2-046 C | Adder | 21.12 MW | 17.95 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 957531 | AF2-047 C | 80/20 | 23.95 MW | 23.95 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 957861 | AF2-080 C | Adder | 8.8 MW | 7.48 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 938771 | AE1-103 C | 80/20 | 3.98 MW | 3.98 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 313526 | AB2-022 C | 80/20 | 0.49 MW | 0.49 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 314295 | 6BIRDNECK | 80/20 | 0.06 MW | 0.06 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 314421 | 6WINCHST | 80/20 | 0.14 MW | 0.14 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 314507 | 3THOMPSN | 80/20 | 3.17 MW | 3.17 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315092 | 1YORKTN3 | 80/20 | 178.95 MW | 178.95 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 942341 | AE2-247 C | 80/20 | 1.89 MW | 1.89 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 943461 | AF1-017 C | 80/20 | 1.71 MW | 1.71 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 944871 | AF1-152 C | 80/20 | 7.97 MW | 7.97 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315098 | 1CHESPKA | 80/20 | 0.58 MW | 0.58 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315099 | 1CHESPKB | 80/20 | 0.96 MW | 0.96 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315108 | 1ELIZAR1 | 80/20 | 4.28 MW | 4.28 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315109 | 1ELIZAR2 | 80/20 | 4.21 MW | 4.21 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315110 | 1ELIZAR3 | 80/20 | 4.34 MW | 4.34 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315115 | 1S HAMPT1 | 80/20 | 1.66 MW | 1.66 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315233 | 1SURRY 2 | 80/20 | 43.66 MW | 43.66 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315241 | 1Z1-086 GT1 | 80/20 | 10.58 MW | 10.58 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315242 | 1Z1-086 GT2 | 80/20 | 10.59 MW | 10.59 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315243 | 1Z1-086 GT3 | 80/20 | 10.59 MW | 10.59 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315244 | 1Z1-086 ST | 80/20 | 18.43 MW | 18.43 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315260 | 1GOSPORTA | 80/20 | 3.35 MW | 3.35 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315261 | 1GOSPORTB | 80/20 | 4.28 MW | 4.28 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315262 | 1GOSPORTC | 80/20 | 3.63 MW | 3.63 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315605 | 6W1-029WIND | 80/20 | 0.99 MW | 0.99 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315611 | 6Z1-036WIND | 80/20 | 10.02 MW | 10.02 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 962531 | AG1-102 C | Adder | 0.92 MW | 0.78 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 941501 | AE2-147 C | 80/20 | 23.91 MW | 23.91 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 957831 | AF2-077 C | Adder | 1.79 MW | 1.52 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 957871 | AF2-081 C | 80/20 | 15.79 MW | 15.79 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 958161 | AF2-110 C | 80/20 | 1.97 MW | 1.97 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 926071 | AC1-086 C | Adder | 22.96 MW | 19.52 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 927021 | AC1-189 C | Adder | 9.69 MW | 8.23 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 933291 | AC2-141 C | 80/20 | 56.41 MW | 56.41 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 939411 | AE1-173 C | 80/20 | 127.89 MW | 127.89 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 934011 | AD1-025 C | Adder | 13.62 MW | 11.58 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 933981 | AD1-022 C | 80/20 | 11.71 MW | 11.71 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 960331 | AF2-324 C | Adder | 7.54 MW | 6.41 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 961681 | AG1-008 C | Adder | 21.16 MW | 17.98 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 962571 | AG1-106 C | Adder | 6.39 MW | 5.43 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316036 | AC1-147 C | 80/20 | 0.49 MW | 0.49 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316072 | AD1-144 C | 80/20 | 0.34 MW | 0.34 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316185 | AD1-033 C | 80/20 | 1.66 MW | 1.66 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316210 | AC1-098 C | Adder | 7.0 MW | 5.95 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316212 | AC1-099 C | Adder | 2.34 MW | 1.99 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316222 | AC1-221 C | Adder | 7.52 MW | 6.39 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316236 | AE1-162 C | 80/20 | 0.38 MW | 0.38 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316246 | AF1-032 C | 80/20 | 0.37 MW | 0.37 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316263 | AC1-034 C | Adder | 7.16 MW | 6.09 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316274 | AC1-208 C | Adder | 10.07 MW | 8.56 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316294 | AC1-161 C | 80/20 | 7.78 MW | 7.78 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316305 | AF2-043 C | 80/20 | 0.45 MW | 0.45 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316316 | AC1-027 C | 80/20 | 0.42 MW | 0.42 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316320 | Y1-086 C | 80/20 | 0.29 MW | 0.29 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316321 | Z2-027 C | 80/20 | 0.47 MW | 0.47 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963221 | AG1-171 C | Adder | 1.74 MW | 1.48 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963231 | AG1-172 C | Adder | 1.74 MW | 1.48 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963241 | AG1-173 C | Adder | 1.74 MW | 1.48 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963251 | AG1-174 C | Adder | 1.74 MW | 1.48 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316017 | AA1-139 ULT1 | 80/20 | 1.44 MW | 1.44 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316018 | AA1-139 ULT2 | 80/20 | 1.44 MW | 1.44 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315614 | AA2-178 C | 80/20 | 1.85 MW | 1.85 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316181 | AB2-040 GEN | Adder | 7.99 MW | 6.79 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316375 | AC2-012 C | 80/20 | 1.81 MW | 1.81 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316311 | AC2-079 C | 80/20 | 7.38 MW | 7.38 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316349 | AD2-085 C | 80/20 | 4.36 MW | 4.36 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316388 | AE2-253 GEN | 80/20 | 2.63 MW | 2.63 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 961611 | AG1-000B C | Adder | 16.43 MW | 13.96 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 940661 | AE2-053 C | Adder | 3.09 MW | 2.62 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 941291 | AE2-123 C | 80/20 | 46.45 MW | 46.45 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 941301 | AE2-124 C | 80/20 | 42.28 MW | 42.28 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 941591 | AE2-156 C | 80/20 | 28.26 MW | 28.26 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 942551 | AE2-270 C | Adder | 21.72 MW | 18.47 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 944581 | AF1-123 C | 80/20 | 79.3 MW | 79.3 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 944591 | AF1-124 C | 80/20 | 79.3 MW | 79.3 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 944601 | AF1-125 C | 80/20 | 79.3 MW | 79.3 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 945361 | AF1-201 C | Adder | 15.82 MW | 13.44 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 946011 | AF1-266 C | Adder | 13.41 MW | 11.4 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 957711 | AF2-065 C | Adder | 11.08 MW | 9.42 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 961711 | AG1-011 C | Adder | 23.13 MW | 19.66 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 962561 | AG1-105 C | Adder | 7.9 MW | 6.71 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963291 | AG1-178 C | 80/20 | 81.54 MW | 81.54 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963311 | AG1-180 C | Adder | 2.7 MW | 2.29 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963351 | AG1-184 C | 80/20 | 43.93 MW | 43.93 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 964241 | AG1-285 C | Adder | 10.34 MW | 8.79 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 964951 | AG1-359 C | 80/20 | 36.6 MW | 36.6 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965001 | AG1-364 C | 80/20 | 11.3 MW | 11.3 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965601 | AG1-428 C | Adder | 4.64 MW | 3.94 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965691 | AG1-437 C | Adder | 13.38 MW | 11.38 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965701 | AG1-438 C | Adder | 13.38 MW | 11.38 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965711 | AG1-439 C | Adder | 26.69 MW | 22.69 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965741 | AG1-442 C | Adder | 7.81 MW | 6.64 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965751 | AG1-443 C | Adder | 7.81 MW | 6.64 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965761 | AG1-444 C | Adder | 14.24 MW | 12.1 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965771 | AG1-445 C | Adder | 4.2 MW | 3.57 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965781 | AG1-446 C | Adder | 4.2 MW | 3.57 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965811 | AG1-449 C | 80/20 | 27.84 MW | 27.84 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 966611 | AG1-531 C | Adder | 6.89 MW | 5.85 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 313764 | 3SOCKMAN | Adder | 0.77 MW | 0.66 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 932631 | AC2-084 C | Adder | 7.48 MW | 6.36 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 934321 | AD1-056 C | Adder | 6.79 MW | 5.77 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 934331 | AD1-057 C | Adder | 3.79 MW | 3.22 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 934501 | AD1-074 C | 80/20 | 45.73 MW | 45.73 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 934511 | AD1-075 C | 80/20 | 11.43 MW | 11.43 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 938531 | AE1-072 C | 80/20 | 27.64 MW | 27.64 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 939191 | AE1-149 C | Adder | 8.7 MW | 7.39 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 940481 | AE2-033 C | Adder | 16.02 MW | 13.62 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 940541 | AE2-040 C | Adder | 2.82 MW | 2.4 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 940641 | AE2-051 C | 80/20 | 23.29 MW | 23.29 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 940651 | AE2-052 C | Adder | 2.9 MW | 2.46 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 941101 | AE2-104 C | 80/20 | 4.83 MW | 4.83 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 941281 | AE2-122 C | 80/20 | 45.2 MW | 45.2 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 944141 | AF1-082 C | Adder | 3.01 MW | 2.56 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 945811 | AF1-246 C | Adder | 8.12 MW | 6.9 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 27.45 MW | 27.45 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 20.83 MW | 20.83 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 95.18 MW | 95.18 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | NY | PJM->LTFIMP_NY | CLTF | 1.57 MW | 1.57 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | LGEE | LTFEXP_LGEE->PJM | CLTF | 1.1 MW | 1.1 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | WEC | LTFEXP_WEC->PJM | CLTF | 0.57 MW | 0.57 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | CPLE | LTFEXP_CPLE->PJM | CLTF | 11.68 MW | 11.68 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | TVA | LTFEXP_TVA->PJM | CLTF | 5.71 MW | 5.71 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | MEC | LTFEXP_MEC->PJM | CLTF | 3.56 MW | 3.56 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | LAGN | LTFEXP_LAGN->PJM | CLTF | 7.28 MW | 7.28 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.22 MW | 0.22 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 5.57 MW | 5.57 MW |
| Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 961671 | AG1-007 C | Adder | 1.27 MW | 1.08 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 961941 | AG1-037 C | Adder | 0.69 MW | 0.59 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962331 | AG1-082 C | Adder | 2.76 MW | 2.35 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962341 | AG1-083 C | Adder | 2.76 MW | 2.35 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963041 | AG1-153 C | 80/20 | 9.44 MW | 9.44 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963111 | AG1-160 C | 80/20 | 9.6 MW | 9.6 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963301 | AG1-179 C | Adder | 7.28 MW | 6.19 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 964111 | AG1-272 C | Adder | 2.57 MW | 2.19 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 964121 | AG1-273 C | Adder | 2.57 MW | 2.19 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 964131 | AG1-274 C | Adder | 2.57 MW | 2.19 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 964791 | AG1-342 C | Adder | 5.05 MW | 4.29 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 964801 | AG1-343 C | Adder | 8.14 MW | 6.92 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 966801 | AG1-551 C | Adder | 2.87 MW | 2.44 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 966811 | AG1-552 C | Adder | 2.75 MW | 2.34 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965191 | AG1-384 C | Adder | 2.57 MW | 2.19 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965291 | AG1-394 C | Adder | 2.79 MW | 2.37 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965591 | AG1-427 C | Adder | 13.19 MW | 11.21 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965721 | AG1-440 C | Adder | 9.5 MW | 8.08 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965731 | AG1-441 C | Adder | 9.5 MW | 8.08 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 966361 | AG1-505 C | 80/20 | 27.7 MW | 27.7 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 966371 | AG1-506 C | 80/20 | 27.7 MW | 27.7 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 966621 | AG1-532 C | Adder | 1.87 MW | 1.59 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315131 | 1EDGECMA | Adder | 20.8 MW | 17.68 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315153 | 1CLOVER1 | 80/20 | 15.75 MW | 15.75 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315154 | 1CLOVER2 | 80/20 | 15.6 MW | 15.6 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 934521 | AD1-076 C | Adder | 16.99 MW | 14.45 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 942931 | AE2-313 C | 80/20 | 61.47 MW | 61.47 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944011 | AF1-069 C | 80/20 | 22.43 MW | 22.43 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 959311 | AF2-222 C | Adder | 8.02 MW | 6.82 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 960061 | AF2-297 C | Adder | 9.86 MW | 8.38 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 960081 | AF2-299 C | Adder | 3.46 MW | 2.94 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 939181 | AE1-148 C | Adder | 11.09 MW | 9.43 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 940571 | AE2-044 C | Adder | 5.82 MW | 4.95 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941031 | AE2-094 C | 80/20 | 68.65 MW | 68.65 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941791 | AE2-182 C | Adder | 2.09 MW | 1.78 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 946281 | AF1-292 C | Adder | 2.06 MW | 1.75 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957481 | AF2-042 C | 80/20 | 81.78 MW | 81.78 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957521 | AF2-046 C | Adder | 23.09 MW | 19.63 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957531 | AF2-047 C | Adder | 23.85 MW | 20.27 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957861 | AF2-080 C | Adder | 10.34 MW | 8.79 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 938771 | AE1-103 C | Adder | 4.02 MW | 3.42 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314295 | 6BIRDNECK | 80/20 | 0.05 MW | 0.05 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314507 | 3THOMPSN | Adder | 2.85 MW | 2.42 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315092 | 1YORKTN3 | Adder | 163.96 MW | 139.37 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 942341 | AE2-247 C | Adder | 1.95 MW | 1.66 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 943461 | AF1-017 C | Adder | 1.76 MW | 1.5 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944871 | AF1-152 C | Adder | 7.45 MW | 6.33 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315098 | 1CHESPKA | 80/20 | 0.52 MW | 0.52 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315099 | 1CHESPKB | 80/20 | 0.86 MW | 0.86 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315102 | 1BRUNSWICKG1 | 80/20 | 11.77 MW | 11.77 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315103 | 1BRUNSWICKG2 | 80/20 | 11.77 MW | 11.77 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315104 | 1BRUNSWICKG3 | 80/20 | 11.77 MW | 11.77 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315105 | 1BRUNSWICKS1 | 80/20 | 24.45 MW | 24.45 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315108 | 1ELIZAR1 | 80/20 | 3.82 MW | 3.82 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315109 | 1ELIZAR2 | 80/20 | 3.76 MW | 3.76 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315110 | 1ELIZAR3 | 80/20 | 3.87 MW | 3.87 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315241 | 1Z1-086 GT1 | 80/20 | 15.12 MW | 15.12 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315242 | 1Z1-086 GT2 | 80/20 | 15.13 MW | 15.13 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315243 | 1Z1-086 GT3 | 80/20 | 15.13 MW | 15.13 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315244 | 1Z1-086 ST | 80/20 | 26.32 MW | 26.32 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315260 | 1GOSPORTA | 80/20 | 3.0 MW | 3.0 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315261 | 1GOSPORTB | 80/20 | 3.84 MW | 3.84 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315262 | 1GOSPORTC | 80/20 | 3.26 MW | 3.26 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315611 | 6Z1-036WIND | Adder | 9.56 MW | 8.13 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962531 | AG1-102 C | Adder | 1.1 MW | 0.94 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941501 | AE2-147 C | Adder | 22.35 MW | 19.0 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 942001 | AE2-212 C | Adder | 2.02 MW | 1.71 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957831 | AF2-077 C | Adder | 2.15 MW | 1.83 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957871 | AF2-081 C | 80/20 | 14.22 MW | 14.22 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 958161 | AF2-110 C | Adder | 1.89 MW | 1.6 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 926071 | AC1-086 C | Adder | 28.45 MW | 24.18 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 927021 | AC1-189 C | Adder | 11.39 MW | 9.68 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 936261 | AD2-033 C | Adder | 13.4 MW | 11.39 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 933291 | AC2-141 C | 80/20 | 45.02 MW | 45.02 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 934621 | AD1-088 C | Adder | 12.86 MW | 10.93 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 939411 | AE1-173 C | 80/20 | 150.36 MW | 150.36 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 934011 | AD1-025 C | Adder | 16.8 MW | 14.28 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 933981 | AD1-022 C | Adder | 12.14 MW | 10.32 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 960331 | AF2-324 C | Adder | 9.36 MW | 7.96 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 961681 | AG1-008 C | Adder | 23.14 MW | 19.67 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962571 | AG1-106 C | Adder | 7.91 MW | 6.72 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316036 | AC1-147 C | 80/20 | 0.44 MW | 0.44 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316185 | AD1-033 C | 80/20 | 1.48 MW | 1.48 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316210 | AC1-098 C | Adder | 8.27 MW | 7.03 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316212 | AC1-099 C | Adder | 2.77 MW | 2.36 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316222 | AC1-221 C | Adder | 10.43 MW | 8.86 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316263 | AC1-034 C | Adder | 8.89 MW | 7.56 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316274 | AC1-208 C | Adder | 12.12 MW | 10.31 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316294 | AC1-161 C | 80/20 | 6.21 MW | 6.21 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316315 | AB2-025 C | 80/20 | 0.48 MW | 0.48 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316316 | AC1-027 C | 80/20 | 0.38 MW | 0.38 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963221 | AG1-171 C | Adder | 2.14 MW | 1.82 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963231 | AG1-172 C | Adder | 2.14 MW | 1.82 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963241 | AG1-173 C | Adder | 2.14 MW | 1.82 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963251 | AG1-174 C | Adder | 2.14 MW | 1.82 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316017 | AA1-139 ULT1 | 80/20 | 1.3 MW | 1.3 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316018 | AA1-139 ULT2 | 80/20 | 1.3 MW | 1.3 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316181 | AB2-040 GEN | Adder | 10.04 MW | 8.54 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316375 | AC2-012 C | 80/20 | 1.62 MW | 1.62 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316311 | AC2-079 C | Adder | 7.55 MW | 6.41 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316349 | AD2-085 C | Adder | 4.5 MW | 3.82 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316388 | AE2-253 GEN | 80/20 | 2.36 MW | 2.36 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 961611 | AG1-000B C | Adder | 17.68 MW | 15.03 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 940661 | AE2-053 C | Adder | 4.11 MW | 3.49 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941291 | AE2-123 C | 80/20 | 41.52 MW | 41.52 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941301 | AE2-124 C | 80/20 | 37.79 MW | 37.79 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941591 | AE2-156 C | 80/20 | 25.28 MW | 25.28 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 942551 | AE2-270 C | Adder | 26.77 MW | 22.76 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944581 | AF1-123 C | 80/20 | 69.59 MW | 69.59 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944591 | AF1-124 C | 80/20 | 69.59 MW | 69.59 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944601 | AF1-125 C | 80/20 | 69.59 MW | 69.59 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 945361 | AF1-201 C | Adder | 17.02 MW | 14.47 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 946011 | AF1-266 C | Adder | 18.75 MW | 15.94 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957711 | AF2-065 C | Adder | 13.65 MW | 11.61 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 961711 | AG1-011 C | Adder | 28.54 MW | 24.26 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962491 | AG1-098 C | Adder | 11.65 MW | 9.9 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962561 | AG1-105 C | Adder | 10.76 MW | 9.14 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963291 | AG1-178 C | 80/20 | 108.5 MW | 108.5 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963311 | AG1-180 C | Adder | 3.54 MW | 3.0 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963321 | AG1-181 C | Adder | 17.25 MW | 14.66 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963351 | AG1-184 C | 80/20 | 58.45 MW | 58.45 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963361 | AG1-185 C | Adder | 8.35 MW | 7.09 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 964241 | AG1-285 C | Adder | 13.76 MW | 11.7 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 964951 | AG1-359 C | 80/20 | 32.62 MW | 32.62 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965001 | AG1-364 C | 80/20 | 10.11 MW | 10.11 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965601 | AG1-428 C | Adder | 6.08 MW | 5.16 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965691 | AG1-437 C | Adder | 14.01 MW | 11.91 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965701 | AG1-438 C | Adder | 14.01 MW | 11.91 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965711 | AG1-439 C | Adder | 31.8 MW | 27.03 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965741 | AG1-442 C | Adder | 8.17 MW | 6.95 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965751 | AG1-443 C | Adder | 8.17 MW | 6.95 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965761 | AG1-444 C | Adder | 16.96 MW | 14.41 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965771 | AG1-445 C | Adder | 5.49 MW | 4.67 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965781 | AG1-446 C | Adder | 5.49 MW | 4.67 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965811 | AG1-449 C | 80/20 | 39.8 MW | 39.8 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 966611 | AG1-531 C | Adder | 6.71 MW | 5.71 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 313764 | 3SOCKMAN | Adder | 0.95 MW | 0.81 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 932631 | AC2-084 C | Adder | 8.84 MW | 7.52 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 934321 | AD1-056 C | Adder | 8.43 MW | 7.16 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 934331 | AD1-057 C | Adder | 4.7 MW | 4.0 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 934501 | AD1-074 C | Adder | 46.79 MW | 39.77 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 934511 | AD1-075 C | Adder | 11.7 MW | 9.94 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 934611 | AD1-087 C | 80/20 | 1.55 MW | 1.55 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 935161 | AD1-151 C | Adder | 15.41 MW | 13.1 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 937481 | AD2-202 C | 80/20 | 0.45 MW | 0.45 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 938531 | AE1-072 C | 80/20 | 24.99 MW | 24.99 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 939191 | AE1-149 C | Adder | 11.96 MW | 10.17 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 940481 | AE2-033 C | Adder | 22.4 MW | 19.04 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 940541 | AE2-040 C | 80/20 | 3.98 MW | 3.98 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 940641 | AE2-051 C | 80/20 | 29.88 MW | 29.88 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 940651 | AE2-052 C | Adder | 3.99 MW | 3.39 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941101 | AE2-104 C | Adder | 4.63 MW | 3.93 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941281 | AE2-122 C | 80/20 | 40.4 MW | 40.4 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944141 | AF1-082 C | Adder | 3.74 MW | 3.18 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 945811 | AF1-246 C | 80/20 | 11.45 MW | 11.45 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 44.55 MW | 44.55 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 31.12 MW | 31.12 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 131.45 MW | 131.45 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | NY | PJM->LTFIMP_NY | CLTF | 2.2 MW | 2.2 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | LGEE | LTFEXP_LGEE->PJM | CLTF | 1.77 MW | 1.77 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | WEC | LTFEXP_WEC->PJM | CLTF | 0.92 MW | 0.92 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CPLE | LTFEXP_CPLE->PJM | CLTF | 15.79 MW | 15.79 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | TVA | LTFEXP_TVA->PJM | CLTF | 8.37 MW | 8.37 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | MEC | LTFEXP_MEC->PJM | CLTF | 5.53 MW | 5.53 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | LAGN | LTFEXP_LAGN->PJM | CLTF | 10.62 MW | 10.62 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.34 MW | 0.34 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 7.53 MW | 7.53 MW |
| Details for 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 961941 | AG1-037 C | Adder | 0.27 MW | 0.23 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 962331 | AG1-082 C | Adder | 1.09 MW | 0.93 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 962341 | AG1-083 C | Adder | 1.09 MW | 0.93 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 963041 | AG1-153 C | Adder | 2.52 MW | 2.14 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 963111 | AG1-160 C | Adder | 2.55 MW | 2.17 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 964801 | AG1-343 C | Adder | 3.29 MW | 2.8 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 966811 | AG1-552 C | Adder | 1.04 MW | 0.89 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 965291 | AG1-394 C | Adder | 1.13 MW | 0.96 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 966361 | AG1-505 C | Adder | 7.49 MW | 6.36 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 966371 | AG1-506 C | Adder | 7.49 MW | 6.36 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 966621 | AG1-532 C | Adder | 0.72 MW | 0.61 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 934521 | AD1-076 C | Adder | 6.85 MW | 5.82 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 942931 | AE2-313 C | Adder | 16.36 MW | 13.91 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 944011 | AF1-069 C | Adder | 5.94 MW | 5.05 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 960081 | AF2-299 C | Adder | 1.34 MW | 1.14 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 941031 | AE2-094 C | Adder | 18.18 MW | 15.45 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 946281 | AF1-292 C | Adder | 0.8 MW | 0.68 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 957521 | AF2-046 C | Adder | 9.23 MW | 7.85 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 957531 | AF2-047 C | Adder | 9.76 MW | 8.3 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 938771 | AE1-103 C | Adder | 1.73 MW | 1.47 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 314229 | 6MT RD221 | 80/20 | 0.12 MW | 0.12 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 314236 | 6NRTHEST | 80/20 | 0.15 MW | 0.15 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 314250 | 6ROCKVILLE | 80/20 | 1.95 MW | 1.95 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 314309 | 6IRON208 | 80/20 | 0.33 MW | 0.33 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 314314 | 3LOCKS | Adder | 1.41 MW | 1.2 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 314507 | 3THOMPSN | Adder | 1.25 MW | 1.07 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 315050 | 1FOURRIVERG | 80/20 | 3.92 MW | 3.92 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 315060 | 1CHESTF5 | 80/20 | 53.18 MW | 53.18 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 315061 | 1CHESTG7 | 80/20 | 2.74 MW | 2.74 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 315062 | 1CHESTS7 | 80/20 | 1.26 MW | 1.26 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 315063 | 1CHESTG8 | 80/20 | 2.69 MW | 2.69 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 315064 | 1CHESTS8 | 80/20 | 1.39 MW | 1.39 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 315065 | 1CHESTF6 | Adder | 16.3 MW | 13.86 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 315067 | 1DARBY 1 | 80/20 | 2.08 MW | 2.08 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 315068 | 1DARBY 2 | 80/20 | 2.08 MW | 2.08 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 315069 | 1DARBY 3 | 80/20 | 2.08 MW | 2.08 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 315070 | 1DARBY 4 | 80/20 | 2.09 MW | 2.09 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 315073 | 1STONECA | Adder | 5.53 MW | 4.7 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 315083 | 1SPRUNCA | 80/20 | 7.67 MW | 7.67 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 315084 | 1SPRUNCB | 80/20 | 7.67 MW | 7.67 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 315092 | 1YORKTN3 | Adder | 96.9 MW | 82.36 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 934781 | AD1-105 C | 80/20 | 7.08 MW | 7.08 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 936591 | AD2-074 C | Adder | 3.99 MW | 3.39 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 942341 | AE2-247 C | Adder | 0.96 MW | 0.82 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 943461 | AF1-017 C | Adder | 0.87 MW | 0.74 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 943741 | AF1-042 C | Adder | 2.09 MW | 1.77 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 944871 | AF1-152 C | Adder | 3.17 MW | 2.69 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 960091 | AF2-300 C | Adder | 1.12 MW | 0.95 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 961951 | AG1-038 C | Adder | 2.31 MW | 1.96 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 966661 | AG1-536 C | Adder | 3.83 MW | 3.25 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 966871 | AG1-558 C | 80/20 | 2.68 MW | 2.68 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 966881 | AG1-559 C | Adder | 1.24 MW | 1.05 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 315260 | 1GOSPORTA | Adder | 1.32 MW | 1.12 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 315261 | 1GOSPORTB | Adder | 1.69 MW | 1.44 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 315262 | 1GOSPORTC | Adder | 1.43 MW | 1.22 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 315611 | 6Z1-036WIND | Adder | 4.01 MW | 3.41 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 316075 | AC2-137 C | 80/20 | 0.28 MW | 0.28 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 316108 | AB2-160 C | Adder | 4.28 MW | 3.64 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 957411 | AF2-035 C | Adder | 4.48 MW | 3.81 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 957601 | AF2-054 C | Adder | 1.55 MW | 1.32 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 962531 | AG1-102 C | Adder | 0.78 MW | 0.66 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 962851 | AG1-134 C | 80/20 | 9.56 MW | 9.56 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 962861 | AG1-135 C | Adder | 4.33 MW | 3.68 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 962971 | AG1-146 C | Adder | 2.22 MW | 1.89 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 962981 | AG1-147 C | Adder | 5.18 MW | 4.4 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 963611 | AG1-210 C | Adder | 0.46 MW | 0.39 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 964211 | AG1-282 C | Adder | 1.42 MW | 1.21 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 941501 | AE2-147 C | Adder | 9.51 MW | 8.08 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 942001 | AE2-212 C | Adder | 1.67 MW | 1.42 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 957831 | AF2-077 C | Adder | 1.52 MW | 1.29 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 957871 | AF2-081 C | Adder | 6.08 MW | 5.17 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 958161 | AF2-110 C | Adder | 0.84 MW | 0.72 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 926071 | AC1-086 C | Adder | 10.95 MW | 9.31 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 933291 | AC2-141 C | Adder | 18.4 MW | 15.64 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 939411 | AE1-173 C | Adder | 47.16 MW | 40.08 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 934011 | AD1-025 C | Adder | 12.56 MW | 10.68 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 315085 | 1SPRUNCC | 80/20 | 0.12 MW | 0.12 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 315086 | 1SPRUNCD | 80/20 | 0.12 MW | 0.12 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 927041 | AC1-191 C | 80/20 | 10.76 MW | 10.76 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 933981 | AD1-022 C | Adder | 4.87 MW | 4.14 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 961681 | AG1-008 C | Adder | 9.25 MW | 7.87 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 962571 | AG1-106 C | Adder | 3.04 MW | 2.59 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 316004 | AC1-112 C | 80/20 | 0.28 MW | 0.28 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 316233 | AE1-074 C | Adder | 1.82 MW | 1.55 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 316240 | AF1-291 C | Adder | 1.76 MW | 1.5 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 316301 | AE2-228 C | Adder | 1.75 MW | 1.49 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 316304 | AE2-227 C | 80/20 | 1.93 MW | 1.93 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 316312 | AB1-027 C | 80/20 | 0.45 MW | 0.45 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 963221 | AG1-171 C | Adder | 1.6 MW | 1.36 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 963231 | AG1-172 C | Adder | 1.6 MW | 1.36 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 963241 | AG1-173 C | Adder | 1.6 MW | 1.36 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 963251 | AG1-174 C | Adder | 1.6 MW | 1.36 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 315051 | AA1-145 CT1 | 80/20 | 4.01 MW | 4.01 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 315052 | AA1-145 CT2 | 80/20 | 4.01 MW | 4.01 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 316201 | AC1-065 C | Adder | 7.53 MW | 6.4 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 316427 | AG1-213 C | Adder | 0.37 MW | 0.32 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 315043 | 1FOUR RIVERA | 80/20 | 2.52 MW | 2.52 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 315044 | 1FOUR RIVERB | 80/20 | 2.52 MW | 2.52 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 315045 | 1FOUR RIVERC | 80/20 | 3.07 MW | 3.07 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 315046 | 1FOUR RIVERD | 80/20 | 2.48 MW | 2.48 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 315047 | 1FOUR RIVERE | 80/20 | 2.48 MW | 2.48 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 315048 | 1FOUR RIVERF | 80/20 | 3.03 MW | 3.03 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 316181 | AB2-040 GEN | Adder | 3.85 MW | 3.27 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 316311 | AC2-079 C | Adder | 3.68 MW | 3.12 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 316349 | AD2-085 C | Adder | 2.22 MW | 1.89 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 961611 | AG1-000B C | Adder | 11.3 MW | 9.6 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 941291 | AE2-123 C | Adder | 18.01 MW | 15.31 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 941301 | AE2-124 C | Adder | 16.37 MW | 13.91 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 941591 | AE2-156 C | Adder | 11.12 MW | 9.45 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 942371 | AE2-250 C | Adder | 7.61 MW | 6.47 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 942551 | AE2-270 C | Adder | 20.0 MW | 17.0 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 944581 | AF1-123 C | Adder | 29.26 MW | 24.88 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 944591 | AF1-124 C | Adder | 29.26 MW | 24.88 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 944601 | AF1-125 C | Adder | 29.26 MW | 24.88 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 944631 | AF1-128 C | Adder | 33.28 MW | 28.29 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 945361 | AF1-201 C | Adder | 11.27 MW | 9.58 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 946011 | AF1-266 C | Adder | 7.66 MW | 6.51 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 957711 | AF2-065 C | Adder | 10.2 MW | 8.67 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 958261 | AF2-120 C | Adder | 4.45 MW | 3.78 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 961711 | AG1-011 C | Adder | 21.33 MW | 18.13 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 962271 | AG1-075 C | Adder | 13.14 MW | 11.16 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 963291 | AG1-178 C | Adder | 30.5 MW | 25.93 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 963351 | AG1-184 C | Adder | 16.43 MW | 13.97 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 964951 | AG1-359 C | Adder | 13.98 MW | 11.88 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 965001 | AG1-364 C | Adder | 4.45 MW | 3.78 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 965281 | AG1-393 C | Adder | 1.69 MW | 1.44 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 965691 | AG1-437 C | Adder | 5.6 MW | 4.76 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 965701 | AG1-438 C | Adder | 5.6 MW | 4.76 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 965741 | AG1-442 C | Adder | 3.26 MW | 2.77 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 965751 | AG1-443 C | Adder | 3.26 MW | 2.77 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 965811 | AG1-449 C | Adder | 10.6 MW | 9.01 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 966611 | AG1-531 C | Adder | 4.02 MW | 3.41 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 313764 | 3SOCKMAN | Adder | 0.36 MW | 0.31 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 934501 | AD1-074 C | Adder | 18.86 MW | 16.03 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 934511 | AD1-075 C | Adder | 4.72 MW | 4.01 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 935161 | AD1-151 C | Adder | 12.2 MW | 10.37 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 938531 | AE1-072 C | Adder | 10.68 MW | 9.08 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 939191 | AE1-149 C | Adder | 7.65 MW | 6.5 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 939601 | AE1-190 C | Adder | 1.58 MW | 1.34 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 940431 | AE2-027 C | Adder | 10.29 MW | 8.75 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 940481 | AE2-033 C | Adder | 9.16 MW | 7.78 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 940541 | AE2-040 C | Adder | 1.64 MW | 1.39 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 940551 | AE2-041 C | Adder | 5.32 MW | 4.52 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 940641 | AE2-051 C | Adder | 8.51 MW | 7.23 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 940651 | AE2-052 C | Adder | 2.55 MW | 2.17 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 941101 | AE2-104 C | Adder | 2.07 MW | 1.76 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 941281 | AE2-122 C | Adder | 17.53 MW | 14.9 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 942191 | AE2-231 C | Adder | 2.46 MW | 2.09 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 943471 | AF1-018 C | Adder | 5.32 MW | 4.52 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 944641 | AF1-129 C | Adder | 85.02 MW | 72.26 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 2.31 MW | 2.31 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 5.04 MW | 5.04 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 34.57 MW | 34.57 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | NY | PJM->LTFIMP_NY | CLTF | 0.72 MW | 0.72 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.12 MW | 0.12 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | WEC | LTFEXP_WEC->PJM | CLTF | 0.06 MW | 0.06 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | CPLE | LTFEXP_CPLE->PJM | CLTF | 4.48 MW | 4.48 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | TVA | LTFEXP_TVA->PJM | CLTF | 1.59 MW | 1.59 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | MEC | LTFEXP_MEC->PJM | CLTF | 0.61 MW | 0.61 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | LAGN | LTFEXP_LAGN->PJM | CLTF | 2.06 MW | 2.06 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.03 MW | 0.03 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.13 MW | 2.13 MW |
| Details for 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 961941 | AG1-037 C | Adder | 0.27 MW | 0.23 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 962331 | AG1-082 C | Adder | 1.09 MW | 0.93 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 962341 | AG1-083 C | Adder | 1.09 MW | 0.93 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 963041 | AG1-153 C | Adder | 2.53 MW | 2.15 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 963111 | AG1-160 C | Adder | 2.56 MW | 2.18 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 964801 | AG1-343 C | Adder | 3.3 MW | 2.8 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 966811 | AG1-552 C | Adder | 1.05 MW | 0.89 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 965291 | AG1-394 C | Adder | 1.13 MW | 0.96 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 966361 | AG1-505 C | Adder | 7.51 MW | 6.38 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 966371 | AG1-506 C | Adder | 7.51 MW | 6.38 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 966621 | AG1-532 C | Adder | 0.72 MW | 0.62 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 934521 | AD1-076 C | Adder | 6.87 MW | 5.84 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 942931 | AE2-313 C | Adder | 16.4 MW | 13.94 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 944011 | AF1-069 C | Adder | 5.96 MW | 5.06 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 960081 | AF2-299 C | Adder | 1.34 MW | 1.14 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 941031 | AE2-094 C | Adder | 18.22 MW | 15.49 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 946281 | AF1-292 C | Adder | 0.8 MW | 0.68 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 957521 | AF2-046 C | Adder | 9.26 MW | 7.87 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 957531 | AF2-047 C | Adder | 9.79 MW | 8.32 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 938771 | AE1-103 C | Adder | 1.73 MW | 1.47 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 314229 | 6MT RD221 | 80/20 | 0.12 MW | 0.12 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 314236 | 6NRTHEST | 80/20 | 0.15 MW | 0.15 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 314250 | 6ROCKVILLE | 80/20 | 1.95 MW | 1.95 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 314309 | 6IRON208 | 80/20 | 0.33 MW | 0.33 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 314314 | 3LOCKS | Adder | 1.41 MW | 1.2 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 314507 | 3THOMPSN | Adder | 1.26 MW | 1.07 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 315050 | 1FOURRIVERG | 80/20 | 3.92 MW | 3.92 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 315060 | 1CHESTF5 | 80/20 | 53.31 MW | 53.31 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 315061 | 1CHESTG7 | 80/20 | 2.75 MW | 2.75 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 315062 | 1CHESTS7 | 80/20 | 1.26 MW | 1.26 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 315063 | 1CHESTG8 | 80/20 | 2.7 MW | 2.7 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 315064 | 1CHESTS8 | 80/20 | 1.39 MW | 1.39 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 315065 | 1CHESTF6 | Adder | 16.34 MW | 13.89 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 315067 | 1DARBY 1 | 80/20 | 2.08 MW | 2.08 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 315068 | 1DARBY 2 | 80/20 | 2.08 MW | 2.08 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 315069 | 1DARBY 3 | 80/20 | 2.09 MW | 2.09 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 315070 | 1DARBY 4 | 80/20 | 2.09 MW | 2.09 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 315073 | 1STONECA | Adder | 5.54 MW | 4.71 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 315083 | 1SPRUNCA | 80/20 | 7.69 MW | 7.69 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 315084 | 1SPRUNCB | 80/20 | 7.69 MW | 7.69 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 315092 | 1YORKTN3 | Adder | 97.14 MW | 82.57 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 934781 | AD1-105 C | 80/20 | 7.09 MW | 7.09 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 936591 | AD2-074 C | Adder | 4.0 MW | 3.4 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 942341 | AE2-247 C | Adder | 0.96 MW | 0.82 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 943461 | AF1-017 C | Adder | 0.87 MW | 0.74 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 943741 | AF1-042 C | Adder | 2.09 MW | 1.78 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 944871 | AF1-152 C | Adder | 3.18 MW | 2.7 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 960091 | AF2-300 C | Adder | 1.12 MW | 0.95 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 961951 | AG1-038 C | Adder | 2.31 MW | 1.97 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 966661 | AG1-536 C | Adder | 3.84 MW | 3.26 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 966871 | AG1-558 C | 80/20 | 2.69 MW | 2.69 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 966881 | AG1-559 C | Adder | 1.24 MW | 1.06 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 315260 | 1GOSPORTA | Adder | 1.33 MW | 1.13 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 315261 | 1GOSPORTB | Adder | 1.69 MW | 1.44 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 315262 | 1GOSPORTC | Adder | 1.44 MW | 1.22 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 315611 | 6Z1-036WIND | Adder | 4.02 MW | 3.42 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 316075 | AC2-137 C | 80/20 | 0.28 MW | 0.28 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 316108 | AB2-160 C | Adder | 4.3 MW | 3.65 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 957411 | AF2-035 C | Adder | 4.49 MW | 3.81 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 957601 | AF2-054 C | Adder | 1.55 MW | 1.32 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 962531 | AG1-102 C | Adder | 0.78 MW | 0.66 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 962851 | AG1-134 C | 80/20 | 9.58 MW | 9.58 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 962861 | AG1-135 C | Adder | 4.34 MW | 3.69 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 962971 | AG1-146 C | Adder | 2.23 MW | 1.89 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 962981 | AG1-147 C | Adder | 5.19 MW | 4.42 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 963611 | AG1-210 C | Adder | 0.46 MW | 0.39 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 964211 | AG1-282 C | Adder | 1.43 MW | 1.21 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 941501 | AE2-147 C | Adder | 9.53 MW | 8.1 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 942001 | AE2-212 C | Adder | 1.67 MW | 1.42 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 957831 | AF2-077 C | Adder | 1.52 MW | 1.29 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 957871 | AF2-081 C | Adder | 6.1 MW | 5.18 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 958161 | AF2-110 C | Adder | 0.85 MW | 0.72 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 926071 | AC1-086 C | Adder | 10.98 MW | 9.33 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 933291 | AC2-141 C | Adder | 18.44 MW | 15.68 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 939411 | AE1-173 C | Adder | 47.27 MW | 40.18 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 934011 | AD1-025 C | Adder | 12.59 MW | 10.7 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 315085 | 1SPRUNCC | 80/20 | 0.12 MW | 0.12 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 315086 | 1SPRUNCD | 80/20 | 0.12 MW | 0.12 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 927041 | AC1-191 C | 80/20 | 10.79 MW | 10.79 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 933981 | AD1-022 C | Adder | 4.88 MW | 4.15 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 961681 | AG1-008 C | Adder | 9.28 MW | 7.88 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 962571 | AG1-106 C | Adder | 3.05 MW | 2.59 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 316004 | AC1-112 C | 80/20 | 0.28 MW | 0.28 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 316233 | AE1-074 C | Adder | 1.82 MW | 1.55 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 316240 | AF1-291 C | Adder | 1.77 MW | 1.5 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 316301 | AE2-228 C | Adder | 1.76 MW | 1.49 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 316304 | AE2-227 C | 80/20 | 1.93 MW | 1.93 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 316312 | AB1-027 C | 80/20 | 0.45 MW | 0.45 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 963221 | AG1-171 C | Adder | 1.6 MW | 1.36 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 963231 | AG1-172 C | Adder | 1.6 MW | 1.36 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 963241 | AG1-173 C | Adder | 1.6 MW | 1.36 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 963251 | AG1-174 C | Adder | 1.6 MW | 1.36 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 315051 | AA1-145 CT1 | 80/20 | 4.02 MW | 4.02 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 315052 | AA1-145 CT2 | 80/20 | 4.02 MW | 4.02 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 316201 | AC1-065 C | Adder | 7.55 MW | 6.42 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 316427 | AG1-213 C | Adder | 0.37 MW | 0.32 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 315043 | 1FOUR RIVERA | 80/20 | 2.52 MW | 2.52 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 315044 | 1FOUR RIVERB | 80/20 | 2.52 MW | 2.52 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 315045 | 1FOUR RIVERC | 80/20 | 3.08 MW | 3.08 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 315046 | 1FOUR RIVERD | 80/20 | 2.49 MW | 2.49 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 315047 | 1FOUR RIVERE | 80/20 | 2.49 MW | 2.49 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 315048 | 1FOUR RIVERF | 80/20 | 3.04 MW | 3.04 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 316181 | AB2-040 GEN | Adder | 3.86 MW | 3.28 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 316311 | AC2-079 C | Adder | 3.69 MW | 3.13 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 316349 | AD2-085 C | Adder | 2.22 MW | 1.89 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 961611 | AG1-000B C | Adder | 11.33 MW | 9.63 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 941291 | AE2-123 C | Adder | 18.06 MW | 15.35 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 941301 | AE2-124 C | Adder | 16.41 MW | 13.95 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 941591 | AE2-156 C | Adder | 11.14 MW | 9.47 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 942371 | AE2-250 C | Adder | 7.63 MW | 6.49 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 942551 | AE2-270 C | Adder | 20.04 MW | 17.04 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 944581 | AF1-123 C | Adder | 29.34 MW | 24.94 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 944591 | AF1-124 C | Adder | 29.34 MW | 24.94 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 944601 | AF1-125 C | Adder | 29.34 MW | 24.94 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 944631 | AF1-128 C | Adder | 33.36 MW | 28.36 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 945361 | AF1-201 C | Adder | 11.29 MW | 9.6 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 946011 | AF1-266 C | Adder | 7.68 MW | 6.53 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 957711 | AF2-065 C | Adder | 10.22 MW | 8.69 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 958261 | AF2-120 C | Adder | 4.46 MW | 3.79 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 961711 | AG1-011 C | Adder | 21.39 MW | 18.18 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 962271 | AG1-075 C | Adder | 13.17 MW | 11.19 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 963291 | AG1-178 C | Adder | 30.58 MW | 25.99 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 963351 | AG1-184 C | Adder | 16.47 MW | 14.0 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 964951 | AG1-359 C | Adder | 14.02 MW | 11.91 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 965001 | AG1-364 C | Adder | 4.46 MW | 3.79 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 965281 | AG1-393 C | Adder | 1.7 MW | 1.44 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 965691 | AG1-437 C | Adder | 5.61 MW | 4.77 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 965701 | AG1-438 C | Adder | 5.61 MW | 4.77 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 965741 | AG1-442 C | Adder | 3.27 MW | 2.78 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 965751 | AG1-443 C | Adder | 3.27 MW | 2.78 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 965811 | AG1-449 C | Adder | 10.62 MW | 9.03 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 966611 | AG1-531 C | Adder | 4.03 MW | 3.42 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 313764 | 3SOCKMAN | Adder | 0.36 MW | 0.31 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 934501 | AD1-074 C | Adder | 18.91 MW | 16.07 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 934511 | AD1-075 C | Adder | 4.73 MW | 4.02 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 935161 | AD1-151 C | Adder | 12.23 MW | 10.4 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 938531 | AE1-072 C | Adder | 10.71 MW | 9.1 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 939191 | AE1-149 C | Adder | 7.67 MW | 6.52 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 939601 | AE1-190 C | Adder | 1.58 MW | 1.35 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 940431 | AE2-027 C | Adder | 10.32 MW | 8.77 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 940481 | AE2-033 C | Adder | 9.18 MW | 7.8 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 940541 | AE2-040 C | Adder | 1.64 MW | 1.39 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 940551 | AE2-041 C | Adder | 5.34 MW | 4.54 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 940641 | AE2-051 C | Adder | 8.53 MW | 7.25 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 940651 | AE2-052 C | Adder | 2.56 MW | 2.17 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 941101 | AE2-104 C | Adder | 2.08 MW | 1.76 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 941281 | AE2-122 C | Adder | 17.57 MW | 14.94 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 942191 | AE2-231 C | Adder | 2.47 MW | 2.1 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 943471 | AF1-018 C | Adder | 5.34 MW | 4.54 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | 944641 | AF1-129 C | Adder | 85.23 MW | 72.44 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 2.32 MW | 2.32 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 5.06 MW | 5.06 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 34.65 MW | 34.65 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | NY | PJM->LTFIMP_NY | CLTF | 0.72 MW | 0.72 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.12 MW | 0.12 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | WEC | LTFEXP_WEC->PJM | CLTF | 0.06 MW | 0.06 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | CPLE | LTFEXP_CPLE->PJM | CLTF | 4.5 MW | 4.5 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | TVA | LTFEXP_TVA->PJM | CLTF | 1.59 MW | 1.59 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | MEC | LTFEXP_MEC->PJM | CLTF | 0.61 MW | 0.61 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | LAGN | LTFEXP_LAGN->PJM | CLTF | 2.06 MW | 2.06 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.03 MW | 0.03 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.14 MW | 2.14 MW |
| Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 961941 | AG1-037 C | Adder | 0.7 MW | 0.6 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 962331 | AG1-082 C | Adder | 2.82 MW | 2.4 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 962341 | AG1-083 C | Adder | 2.82 MW | 2.4 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963041 | AG1-153 C | Adder | 7.13 MW | 6.06 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963111 | AG1-160 C | Adder | 7.21 MW | 6.13 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963301 | AG1-179 C | Adder | 7.19 MW | 6.11 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 964801 | AG1-343 C | Adder | 8.39 MW | 7.13 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 966801 | AG1-551 C | Adder | 2.89 MW | 2.46 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 966811 | AG1-552 C | Adder | 2.73 MW | 2.32 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965291 | AG1-394 C | Adder | 2.88 MW | 2.45 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 966361 | AG1-505 C | Adder | 21.2 MW | 18.02 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 966371 | AG1-506 C | Adder | 21.2 MW | 18.02 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 966621 | AG1-532 C | Adder | 1.84 MW | 1.56 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 934521 | AD1-076 C | Adder | 17.63 MW | 14.99 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 942931 | AE2-313 C | Adder | 45.92 MW | 39.03 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 944011 | AF1-069 C | Adder | 16.64 MW | 14.15 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 960081 | AF2-299 C | Adder | 3.4 MW | 2.89 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 941031 | AE2-094 C | Adder | 50.94 MW | 43.3 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 946281 | AF1-292 C | Adder | 2.03 MW | 1.72 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 957481 | AF2-042 C | Adder | 66.12 MW | 56.2 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 957521 | AF2-046 C | Adder | 23.7 MW | 20.15 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 957531 | AF2-047 C | Adder | 24.95 MW | 21.21 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 938771 | AE1-103 C | Adder | 4.29 MW | 3.65 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 314229 | 6MT RD221 | 80/20 | 0.15 MW | 0.15 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 314295 | 6BIRDNECK | 80/20 | 0.06 MW | 0.06 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 314314 | 3LOCKS | Adder | 2.59 MW | 2.2 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 314421 | 6WINCHST | 80/20 | 0.18 MW | 0.18 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 314507 | 3THOMPSN | 80/20 | 3.1 MW | 3.1 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315060 | 1CHESTF5 | 80/20 | 96.25 MW | 96.25 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315061 | 1CHESTG7 | 80/20 | 4.96 MW | 4.96 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315062 | 1CHESTS7 | 80/20 | 2.28 MW | 2.28 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315063 | 1CHESTG8 | 80/20 | 4.88 MW | 4.88 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315064 | 1CHESTS8 | 80/20 | 2.51 MW | 2.51 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315065 | 1CHESTF6 | Adder | 28.2 MW | 23.97 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315073 | 1STONECA | Adder | 10.28 MW | 8.74 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315083 | 1SPRUNCA | Adder | 10.9 MW | 9.27 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315084 | 1SPRUNCB | Adder | 10.9 MW | 9.27 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315092 | 1YORKTN3 | 80/20 | 225.05 MW | 225.05 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 936591 | AD2-074 C | Adder | 7.77 MW | 6.61 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 942341 | AE2-247 C | Adder | 2.23 MW | 1.9 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 943461 | AF1-017 C | Adder | 2.02 MW | 1.72 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 943741 | AF1-042 C | Adder | 4.07 MW | 3.46 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 944871 | AF1-152 C | Adder | 7.96 MW | 6.76 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 961951 | AG1-038 C | Adder | 4.5 MW | 3.82 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 966661 | AG1-536 C | Adder | 7.34 MW | 6.24 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 966871 | AG1-558 C | Adder | 3.44 MW | 2.93 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315098 | 1CHESPKA | 80/20 | 0.57 MW | 0.57 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315099 | 1CHESPKB | 80/20 | 0.94 MW | 0.94 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315108 | 1ELIZAR1 | 80/20 | 4.16 MW | 4.16 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315109 | 1ELIZAR2 | 80/20 | 4.08 MW | 4.08 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315110 | 1ELIZAR3 | 80/20 | 4.21 MW | 4.21 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315233 | 1SURRY 2 | 80/20 | 34.23 MW | 34.23 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315260 | 1GOSPORTA | 80/20 | 3.28 MW | 3.28 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315261 | 1GOSPORTB | 80/20 | 4.18 MW | 4.18 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315262 | 1GOSPORTC | 80/20 | 3.55 MW | 3.55 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315611 | 6Z1-036WIND | Adder | 10.14 MW | 8.62 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316075 | AC2-137 C | 80/20 | 0.51 MW | 0.51 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316108 | AB2-160 C | Adder | 7.87 MW | 6.69 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 957601 | AF2-054 C | Adder | 3.18 MW | 2.7 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 962531 | AG1-102 C | 80/20 | 1.7 MW | 1.7 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 962861 | AG1-135 C | Adder | 8.33 MW | 7.08 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 962971 | AG1-146 C | Adder | 4.37 MW | 3.72 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 962981 | AG1-147 C | Adder | 10.2 MW | 8.67 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963611 | AG1-210 C | Adder | 0.86 MW | 0.73 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 964211 | AG1-282 C | Adder | 2.67 MW | 2.27 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 941501 | AE2-147 C | Adder | 23.87 MW | 20.29 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 942001 | AE2-212 C | Adder | 3.08 MW | 2.62 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 957831 | AF2-077 C | 80/20 | 3.32 MW | 3.32 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 957871 | AF2-081 C | Adder | 15.25 MW | 12.96 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 958161 | AF2-110 C | Adder | 2.06 MW | 1.75 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 926071 | AC1-086 C | Adder | 28.09 MW | 23.87 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 933291 | AC2-141 C | 80/20 | 47.63 MW | 47.63 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 939411 | AE1-173 C | Adder | 126.14 MW | 107.22 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 934011 | AD1-025 C | Adder | 25.56 MW | 21.73 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 927041 | AC1-191 C | Adder | 13.82 MW | 11.75 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 933981 | AD1-022 C | Adder | 12.55 MW | 10.67 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 961681 | AG1-008 C | Adder | 23.75 MW | 20.19 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 962571 | AG1-106 C | Adder | 7.81 MW | 6.64 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316004 | AC1-112 C | 80/20 | 0.45 MW | 0.45 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316036 | AC1-147 C | 80/20 | 0.48 MW | 0.48 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316159 | AE1-175 C | 80/20 | 0.54 MW | 0.54 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316169 | AC1-164 GEN | 80/20 | 9.24 MW | 9.24 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316185 | AD1-033 C | 80/20 | 1.59 MW | 1.59 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316210 | AC1-098 C | Adder | 8.22 MW | 6.99 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316212 | AC1-099 C | Adder | 2.75 MW | 2.34 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316236 | AE1-162 C | 80/20 | 0.46 MW | 0.46 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316240 | AF1-291 C | Adder | 3.1 MW | 2.63 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316274 | AC1-208 C | Adder | 11.98 MW | 10.19 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316294 | AC1-161 C | 80/20 | 6.57 MW | 6.57 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316301 | AE2-228 C | Adder | 3.1 MW | 2.63 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316304 | AE2-227 C | Adder | 3.1 MW | 2.63 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316312 | AB1-027 C | 80/20 | 0.71 MW | 0.71 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316314 | AB2-024 C | 80/20 | 0.38 MW | 0.38 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316316 | AC1-027 C | 80/20 | 0.41 MW | 0.41 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316382 | AG1-145 C | 80/20 | 0.48 MW | 0.48 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963221 | AG1-171 C | Adder | 3.26 MW | 2.77 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963231 | AG1-172 C | Adder | 3.26 MW | 2.77 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963241 | AG1-173 C | Adder | 3.26 MW | 2.77 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963251 | AG1-174 C | Adder | 3.26 MW | 2.77 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316201 | AC1-065 C | Adder | 15.23 MW | 12.95 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316181 | AB2-040 GEN | Adder | 9.91 MW | 8.43 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316375 | AC2-012 C | 80/20 | 1.77 MW | 1.77 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316311 | AC2-079 C | Adder | 8.59 MW | 7.3 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316349 | AD2-085 C | Adder | 5.15 MW | 4.38 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 961611 | AG1-000B C | Adder | 24.34 MW | 20.69 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 941291 | AE2-123 C | 80/20 | 44.88 MW | 44.88 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 941301 | AE2-124 C | 80/20 | 40.81 MW | 40.81 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 941591 | AE2-156 C | 80/20 | 27.55 MW | 27.55 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 942371 | AE2-250 C | Adder | 13.98 MW | 11.88 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 942551 | AE2-270 C | Adder | 40.7 MW | 34.59 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 944581 | AF1-123 C | 80/20 | 73.89 MW | 73.89 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 944591 | AF1-124 C | 80/20 | 73.89 MW | 73.89 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 944601 | AF1-125 C | 80/20 | 73.89 MW | 73.89 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 944631 | AF1-128 C | 80/20 | 60.22 MW | 60.22 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 945361 | AF1-201 C | 80/20 | 25.17 MW | 25.17 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 946011 | AF1-266 C | Adder | 18.17 MW | 15.44 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 957711 | AF2-065 C | Adder | 20.76 MW | 17.64 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 958261 | AF2-120 C | Adder | 8.53 MW | 7.25 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 961711 | AG1-011 C | Adder | 43.41 MW | 36.9 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 962271 | AG1-075 C | Adder | 24.13 MW | 20.51 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963291 | AG1-178 C | Adder | 83.48 MW | 70.95 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963311 | AG1-180 C | Adder | 3.49 MW | 2.97 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963351 | AG1-184 C | Adder | 44.97 MW | 38.23 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 964951 | AG1-359 C | Adder | 35.01 MW | 29.76 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965001 | AG1-364 C | 80/20 | 11.02 MW | 11.02 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965281 | AG1-393 C | Adder | 3.11 MW | 2.64 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965601 | AG1-428 C | Adder | 6.0 MW | 5.1 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965691 | AG1-437 C | Adder | 14.45 MW | 12.28 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965701 | AG1-438 C | Adder | 14.45 MW | 12.28 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965741 | AG1-442 C | Adder | 8.43 MW | 7.16 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965751 | AG1-443 C | Adder | 8.43 MW | 7.16 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965811 | AG1-449 C | Adder | 29.74 MW | 25.28 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 966611 | AG1-531 C | 80/20 | 9.06 MW | 9.06 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 313764 | 3SOCKMAN | Adder | 0.94 MW | 0.8 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 932631 | AC2-084 C | Adder | 8.79 MW | 7.47 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 934501 | AD1-074 C | Adder | 48.55 MW | 41.27 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 934511 | AD1-075 C | Adder | 12.14 MW | 10.32 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 935161 | AD1-151 C | Adder | 24.35 MW | 20.7 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 938531 | AE1-072 C | Adder | 26.78 MW | 22.76 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 939191 | AE1-149 C | Adder | 15.65 MW | 13.3 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 939601 | AE1-190 C | Adder | 3.21 MW | 2.73 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 940431 | AE2-027 C | Adder | 18.66 MW | 15.86 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 940481 | AE2-033 C | Adder | 21.7 MW | 18.45 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 940541 | AE2-040 C | Adder | 3.85 MW | 3.27 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 940551 | AE2-041 C | Adder | 10.88 MW | 9.25 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 940641 | AE2-051 C | Adder | 23.29 MW | 19.8 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 940651 | AE2-052 C | Adder | 5.22 MW | 4.43 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 941101 | AE2-104 C | Adder | 5.06 MW | 4.3 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 941281 | AE2-122 C | 80/20 | 43.67 MW | 43.67 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 943471 | AF1-018 C | Adder | 10.88 MW | 9.25 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 944641 | AF1-129 C | Adder | 147.06 MW | 125.0 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 945811 | AF1-246 C | Adder | 9.26 MW | 7.87 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 74.35 MW | 74.35 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 42.53 MW | 42.53 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 135.16 MW | 135.16 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | NY | PJM->LTFIMP_NY | CLTF | 3.61 MW | 3.61 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | LGEE | LTFEXP_LGEE->PJM | CLTF | 2.96 MW | 2.96 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | WEC | LTFEXP_WEC->PJM | CLTF | 1.52 MW | 1.52 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | CPLE | LTFEXP_CPLE->PJM | CLTF | 15.13 MW | 15.13 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | TVA | LTFEXP_TVA->PJM | CLTF | 10.81 MW | 10.81 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | MEC | LTFEXP_MEC->PJM | CLTF | 8.4 MW | 8.4 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | LAGN | LTFEXP_LAGN->PJM | CLTF | 13.47 MW | 13.47 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.55 MW | 0.55 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 7.22 MW | 7.22 MW |
| Details for 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 963041 | AG1-153 C | Adder | 4.28 MW | 3.64 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 963111 | AG1-160 C | Adder | 4.32 MW | 3.68 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 964801 | AG1-343 C | Adder | 4.96 MW | 4.22 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 965291 | AG1-394 C | Adder | 1.7 MW | 1.45 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 966361 | AG1-505 C | Adder | 12.81 MW | 10.89 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 966371 | AG1-506 C | Adder | 12.81 MW | 10.89 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 934521 | AD1-076 C | Adder | 10.3 MW | 8.75 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 942931 | AE2-313 C | Adder | 27.58 MW | 23.44 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 944011 | AF1-069 C | Adder | 9.97 MW | 8.47 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 941031 | AE2-094 C | Adder | 30.51 MW | 25.94 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 957531 | AF2-047 C | Adder | 14.51 MW | 12.34 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 938771 | AE1-103 C | Adder | 2.51 MW | 2.13 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 314229 | 6MT RD221 | 80/20 | 0.1 MW | 0.1 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 314236 | 6NRTHEST | 80/20 | 0.15 MW | 0.15 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 314250 | 6ROCKVILLE | 80/20 | 1.86 MW | 1.86 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 314314 | 3LOCKS | Adder | 1.62 MW | 1.38 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 314507 | 3THOMPSN | Adder | 1.78 MW | 1.51 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 315039 | 1LDYSMT3 | 80/20 | 3.74 MW | 3.74 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 315040 | 1LDYSMT4 | 80/20 | 3.75 MW | 3.75 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 315041 | 1LDYSMT5 | 80/20 | 3.76 MW | 3.76 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 315060 | 1CHESTF5 | Adder | 58.49 MW | 49.72 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 315065 | 1CHESTF6 | Adder | 17.85 MW | 15.17 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 315067 | 1DARBY 1 | 80/20 | 2.01 MW | 2.01 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 315068 | 1DARBY 2 | 80/20 | 2.01 MW | 2.01 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 315069 | 1DARBY 3 | 80/20 | 2.02 MW | 2.02 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 315070 | 1DARBY 4 | 80/20 | 2.02 MW | 2.02 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 315073 | 1STONECA | Adder | 6.3 MW | 5.35 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 315083 | 1SPRUNCA | Adder | 8.27 MW | 7.03 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 315084 | 1SPRUNCB | Adder | 8.27 MW | 7.03 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 315092 | 1YORKTN3 | Adder | 127.17 MW | 108.09 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 936591 | AD2-074 C | Adder | 4.75 MW | 4.04 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 942341 | AE2-247 C | Adder | 1.31 MW | 1.11 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 943461 | AF1-017 C | Adder | 1.18 MW | 1.01 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 943741 | AF1-042 C | Adder | 2.49 MW | 2.11 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 944871 | AF1-152 C | Adder | 4.58 MW | 3.9 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 960091 | AF2-300 C | 80/20 | 2.07 MW | 2.07 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 961951 | AG1-038 C | Adder | 2.75 MW | 2.34 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 966661 | AG1-536 C | Adder | 4.55 MW | 3.87 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 966871 | AG1-558 C | Adder | 2.21 MW | 1.88 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 966881 | AG1-559 C | 80/20 | 2.29 MW | 2.29 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 315225 | 1N ANNA1 | 80/20 | 22.09 MW | 22.09 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 315226 | 1N ANNA2 | 80/20 | 22.09 MW | 22.09 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 315260 | 1GOSPORTA | Adder | 1.88 MW | 1.59 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 315261 | 1GOSPORTB | Adder | 2.4 MW | 2.04 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 315262 | 1GOSPORTC | Adder | 2.03 MW | 1.73 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 315611 | 6Z1-036WIND | Adder | 5.86 MW | 4.98 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 316075 | AC2-137 C | 80/20 | 0.3 MW | 0.3 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 316108 | AB2-160 C | Adder | 4.92 MW | 4.18 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 957411 | AF2-035 C | 80/20 | 8.27 MW | 8.27 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 957601 | AF2-054 C | Adder | 1.86 MW | 1.58 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 962531 | AG1-102 C | Adder | 0.98 MW | 0.83 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 962861 | AG1-135 C | Adder | 5.15 MW | 4.38 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 962971 | AG1-146 C | Adder | 2.65 MW | 2.25 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 962981 | AG1-147 C | Adder | 6.18 MW | 5.26 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 963051 | AG1-154 C | 80/20 | 3.4 MW | 3.4 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 941501 | AE2-147 C | Adder | 13.75 MW | 11.69 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 942001 | AE2-212 C | Adder | 1.93 MW | 1.64 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 957831 | AF2-077 C | Adder | 1.91 MW | 1.62 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 957871 | AF2-081 C | Adder | 8.74 MW | 7.43 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 958161 | AF2-110 C | Adder | 1.2 MW | 1.02 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 933291 | AC2-141 C | Adder | 26.82 MW | 22.8 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 939411 | AE1-173 C | Adder | 73.88 MW | 62.8 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 934011 | AD1-025 C | Adder | 15.26 MW | 12.97 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 927041 | AC1-191 C | Adder | 8.86 MW | 7.53 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 933981 | AD1-022 C | Adder | 7.34 MW | 6.24 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 316004 | AC1-112 C | 80/20 | 0.26 MW | 0.26 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 316169 | AC1-164 GEN | 80/20 | 5.17 MW | 5.17 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 316233 | AE1-074 C | Adder | 2.17 MW | 1.84 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 316240 | AF1-291 C | Adder | 1.96 MW | 1.66 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 316301 | AE2-228 C | Adder | 1.95 MW | 1.66 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 316304 | AE2-227 C | Adder | 2.01 MW | 1.71 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 316312 | AB1-027 C | 80/20 | 0.42 MW | 0.42 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 963221 | AG1-171 C | Adder | 1.94 MW | 1.65 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 963231 | AG1-172 C | Adder | 1.94 MW | 1.65 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 963241 | AG1-173 C | Adder | 1.94 MW | 1.65 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 963251 | AG1-174 C | Adder | 1.94 MW | 1.65 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 315037 | 1LDYSMT1 | 80/20 | 3.6 MW | 3.6 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 315038 | 1LDYSMT2 | 80/20 | 3.65 MW | 3.65 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 315051 | AA1-145 CT1 | 80/20 | 4.0 MW | 4.0 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 315052 | AA1-145 CT2 | 80/20 | 3.99 MW | 3.99 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 226921 | AE1-013 C | Adder | -0.05 MW | -0.05 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 316201 | AC1-065 C | Adder | 8.92 MW | 7.58 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 316427 | AG1-213 C | 80/20 | 0.69 MW | 0.69 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 315043 | 1FOUR RIVERA | 80/20 | 2.51 MW | 2.51 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 315044 | 1FOUR RIVERB | 80/20 | 2.51 MW | 2.51 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 315045 | 1FOUR RIVERC | 80/20 | 3.06 MW | 3.06 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 315046 | 1FOUR RIVERD | 80/20 | 2.47 MW | 2.47 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 315047 | 1FOUR RIVERE | 80/20 | 2.47 MW | 2.47 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 315048 | 1FOUR RIVERF | 80/20 | 3.02 MW | 3.02 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 316311 | AC2-079 C | Adder | 5.03 MW | 4.28 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 316349 | AD2-085 C | Adder | 3.02 MW | 2.57 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 961611 | AG1-000B C | Adder | 14.31 MW | 12.16 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 941291 | AE2-123 C | Adder | 25.69 MW | 21.84 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 941301 | AE2-124 C | Adder | 23.36 MW | 19.85 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 941591 | AE2-156 C | Adder | 15.78 MW | 13.41 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 942371 | AE2-250 C | Adder | 8.73 MW | 7.42 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 942551 | AE2-270 C | Adder | 24.3 MW | 20.65 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 944581 | AF1-123 C | Adder | 42.16 MW | 35.84 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 944591 | AF1-124 C | Adder | 42.16 MW | 35.84 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 944601 | AF1-125 C | Adder | 42.16 MW | 35.84 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 944631 | AF1-128 C | Adder | 36.6 MW | 31.11 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 945361 | AF1-201 C | Adder | 14.38 MW | 12.22 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 946011 | AF1-266 C | Adder | 11.04 MW | 9.38 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 957711 | AF2-065 C | Adder | 12.39 MW | 10.53 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 958261 | AF2-120 C | Adder | 5.29 MW | 4.5 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 961711 | AG1-011 C | Adder | 25.92 MW | 22.03 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 962271 | AG1-075 C | Adder | 15.07 MW | 12.81 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 962841 | AG1-133 C | 80/20 | 15.67 MW | 15.67 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 963291 | AG1-178 C | Adder | 49.51 MW | 42.08 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 963351 | AG1-184 C | Adder | 26.67 MW | 22.67 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 964951 | AG1-359 C | Adder | 20.03 MW | 17.02 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 965001 | AG1-364 C | Adder | 6.31 MW | 5.36 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 965281 | AG1-393 C | Adder | 1.94 MW | 1.65 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 965691 | AG1-437 C | Adder | 8.47 MW | 7.2 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 965701 | AG1-438 C | Adder | 8.47 MW | 7.2 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 965741 | AG1-442 C | Adder | 4.94 MW | 4.2 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 965751 | AG1-443 C | Adder | 4.94 MW | 4.2 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 965811 | AG1-449 C | Adder | 17.86 MW | 15.18 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 966611 | AG1-531 C | Adder | 5.22 MW | 4.43 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 934501 | AD1-074 C | Adder | 28.36 MW | 24.1 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 934511 | AD1-075 C | Adder | 7.09 MW | 6.03 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 935161 | AD1-151 C | Adder | 14.62 MW | 12.42 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 938531 | AE1-072 C | Adder | 15.35 MW | 13.05 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 939191 | AE1-149 C | Adder | 9.53 MW | 8.1 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 939261 | AE1-157 C | 80/20 | 13.34 MW | 13.34 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 939601 | AE1-190 C | Adder | 1.88 MW | 1.6 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 940431 | AE2-027 C | Adder | 11.68 MW | 9.93 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 940481 | AE2-033 C | Adder | 13.19 MW | 11.21 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 940541 | AE2-040 C | Adder | 2.34 MW | 1.99 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 940551 | AE2-041 C | Adder | 6.32 MW | 5.37 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 940641 | AE2-051 C | Adder | 13.76 MW | 11.7 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 940651 | AE2-052 C | Adder | 3.18 MW | 2.7 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 941101 | AE2-104 C | Adder | 2.93 MW | 2.49 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 941281 | AE2-122 C | Adder | 25.0 MW | 21.25 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 942191 | AE2-231 C | 80/20 | 4.55 MW | 4.55 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 943471 | AF1-018 C | Adder | 6.32 MW | 5.37 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 944641 | AF1-129 C | Adder | 93.09 MW | 79.13 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | 963622 | AG1-213 E | 80/20 | 0.69 MW | 0.69 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 45.75 MW | 45.75 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 25.95 MW | 25.95 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 81.66 MW | 81.66 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | NY | PJM->LTFIMP_NY | CLTF | 2.84 MW | 2.84 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | LGEE | LTFEXP_LGEE->PJM | CLTF | 1.82 MW | 1.82 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | WEC | LTFEXP_WEC->PJM | CLTF | 0.94 MW | 0.94 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | CPLE | LTFEXP_CPLE->PJM | CLTF | 9.13 MW | 9.13 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | TVA | LTFEXP_TVA->PJM | CLTF | 6.57 MW | 6.57 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | MEC | LTFEXP_MEC->PJM | CLTF | 5.15 MW | 5.15 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | LAGN | LTFEXP_LAGN->PJM | CLTF | 8.19 MW | 8.19 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.33 MW | 0.33 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 4.36 MW | 4.36 MW |
| Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 961671 | AG1-007 C | Adder | 1.24 MW | 1.06 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 961941 | AG1-037 C | Adder | 0.69 MW | 0.59 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962331 | AG1-082 C | Adder | 2.77 MW | 2.35 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962341 | AG1-083 C | Adder | 2.77 MW | 2.35 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963041 | AG1-153 C | 80/20 | 8.44 MW | 8.44 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963111 | AG1-160 C | 80/20 | 8.55 MW | 8.55 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963301 | AG1-179 C | Adder | 7.55 MW | 6.42 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 964801 | AG1-343 C | Adder | 8.22 MW | 6.99 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 966801 | AG1-551 C | Adder | 2.85 MW | 2.42 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 966811 | AG1-552 C | Adder | 2.77 MW | 2.36 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965291 | AG1-394 C | Adder | 2.82 MW | 2.4 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965721 | AG1-440 C | Adder | 9.71 MW | 8.26 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965731 | AG1-441 C | Adder | 9.71 MW | 8.26 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 966361 | AG1-505 C | 80/20 | 25.02 MW | 25.02 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 966371 | AG1-506 C | 80/20 | 25.02 MW | 25.02 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 966621 | AG1-532 C | Adder | 1.89 MW | 1.61 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 934521 | AD1-076 C | Adder | 17.01 MW | 14.46 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 942931 | AE2-313 C | 80/20 | 54.75 MW | 54.75 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944011 | AF1-069 C | 80/20 | 19.89 MW | 19.89 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 960081 | AF2-299 C | Adder | 3.51 MW | 2.98 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 939181 | AE1-148 C | Adder | 11.48 MW | 9.76 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941031 | AE2-094 C | 80/20 | 60.86 MW | 60.86 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941791 | AE2-182 C | Adder | 2.44 MW | 2.07 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 946281 | AF1-292 C | Adder | 2.09 MW | 1.78 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957481 | AF2-042 C | Adder | 76.49 MW | 65.01 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957521 | AF2-046 C | Adder | 23.26 MW | 19.77 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957531 | AF2-047 C | Adder | 23.91 MW | 20.32 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957861 | AF2-080 C | Adder | 10.19 MW | 8.66 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 938771 | AE1-103 C | Adder | 4.1 MW | 3.48 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314295 | 6BIRDNECK | 80/20 | 0.05 MW | 0.05 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314314 | 3LOCKS | Adder | 2.19 MW | 1.86 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314507 | 3THOMPSN | 80/20 | 2.88 MW | 2.88 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315065 | 1CHESTF6 | Adder | 22.82 MW | 19.4 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315073 | 1STONECA | Adder | 8.16 MW | 6.93 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315083 | 1SPRUNCA | Adder | 10.68 MW | 9.08 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315084 | 1SPRUNCB | Adder | 10.68 MW | 9.08 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315092 | 1YORKTN3 | Adder | 182.58 MW | 155.19 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 942341 | AE2-247 C | Adder | 2.07 MW | 1.76 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 943461 | AF1-017 C | Adder | 1.87 MW | 1.59 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944871 | AF1-152 C | Adder | 7.5 MW | 6.38 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315098 | 1CHESPKA | 80/20 | 0.53 MW | 0.53 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315099 | 1CHESPKB | 80/20 | 0.87 MW | 0.87 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315102 | 1BRUNSWICKG1 | 80/20 | 10.51 MW | 10.51 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315103 | 1BRUNSWICKG2 | 80/20 | 10.51 MW | 10.51 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315104 | 1BRUNSWICKG3 | 80/20 | 10.51 MW | 10.51 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315105 | 1BRUNSWICKS1 | 80/20 | 21.84 MW | 21.84 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315108 | 1ELIZAR1 | 80/20 | 3.87 MW | 3.87 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315109 | 1ELIZAR2 | 80/20 | 3.8 MW | 3.8 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315110 | 1ELIZAR3 | 80/20 | 3.92 MW | 3.92 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315241 | 1Z1-086 GT1 | 80/20 | 13.47 MW | 13.47 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315242 | 1Z1-086 GT2 | 80/20 | 13.48 MW | 13.48 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315243 | 1Z1-086 GT3 | 80/20 | 13.48 MW | 13.48 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315244 | 1Z1-086 ST | 80/20 | 23.46 MW | 23.46 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315260 | 1GOSPORTA | 80/20 | 3.04 MW | 3.04 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315261 | 1GOSPORTB | 80/20 | 3.89 MW | 3.89 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315262 | 1GOSPORTC | 80/20 | 3.3 MW | 3.3 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315611 | 6Z1-036WIND | Adder | 9.61 MW | 8.17 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316108 | AB2-160 C | Adder | 6.66 MW | 5.66 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962531 | AG1-102 C | Adder | 1.31 MW | 1.11 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941501 | AE2-147 C | Adder | 22.5 MW | 19.13 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 942001 | AE2-212 C | Adder | 2.69 MW | 2.29 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957831 | AF2-077 C | Adder | 2.55 MW | 2.17 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957871 | AF2-081 C | Adder | 14.3 MW | 12.15 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 958161 | AF2-110 C | Adder | 1.93 MW | 1.64 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 926071 | AC1-086 C | Adder | 28.48 MW | 24.21 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 927021 | AC1-189 C | Adder | 11.22 MW | 9.54 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 933291 | AC2-141 C | 80/20 | 44.34 MW | 44.34 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 934621 | AD1-088 C | Adder | 15.0 MW | 12.75 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 939411 | AE1-173 C | 80/20 | 138.05 MW | 138.05 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 934011 | AD1-025 C | Adder | 21.22 MW | 18.04 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 933981 | AD1-022 C | Adder | 12.15 MW | 10.32 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 961681 | AG1-008 C | Adder | 23.31 MW | 19.81 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962571 | AG1-106 C | Adder | 7.92 MW | 6.73 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316036 | AC1-147 C | 80/20 | 0.45 MW | 0.45 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316185 | AD1-033 C | 80/20 | 1.49 MW | 1.49 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316210 | AC1-098 C | Adder | 8.24 MW | 7.0 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316212 | AC1-099 C | Adder | 2.76 MW | 2.35 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316233 | AE1-074 C | Adder | 3.34 MW | 2.84 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316240 | AF1-291 C | Adder | 2.55 MW | 2.17 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316274 | AC1-208 C | Adder | 12.07 MW | 10.26 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316294 | AC1-161 C | 80/20 | 6.12 MW | 6.12 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316301 | AE2-228 C | Adder | 2.57 MW | 2.18 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316315 | AB2-025 C | 80/20 | 0.48 MW | 0.48 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316316 | AC1-027 C | 80/20 | 0.38 MW | 0.38 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316336 | AC2-165 C | Adder | 11.9 MW | 10.11 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963221 | AG1-171 C | Adder | 2.7 MW | 2.3 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963231 | AG1-172 C | Adder | 2.7 MW | 2.3 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963241 | AG1-173 C | Adder | 2.7 MW | 2.3 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963251 | AG1-174 C | Adder | 2.7 MW | 2.3 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316181 | AB2-040 GEN | Adder | 10.15 MW | 8.63 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316375 | AC2-012 C | 80/20 | 1.64 MW | 1.64 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316311 | AC2-079 C | Adder | 7.97 MW | 6.78 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316349 | AD2-085 C | Adder | 4.77 MW | 4.06 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316388 | AE2-253 GEN | 80/20 | 2.37 MW | 2.37 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 961611 | AG1-000B C | Adder | 20.74 MW | 17.63 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 940661 | AE2-053 C | Adder | 4.25 MW | 3.62 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941291 | AE2-123 C | 80/20 | 41.88 MW | 41.88 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941301 | AE2-124 C | 80/20 | 38.09 MW | 38.09 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941591 | AE2-156 C | 80/20 | 25.61 MW | 25.61 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 942371 | AE2-250 C | Adder | 11.83 MW | 10.05 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 942551 | AE2-270 C | Adder | 33.8 MW | 28.73 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944581 | AF1-123 C | 80/20 | 69.41 MW | 69.41 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944591 | AF1-124 C | 80/20 | 69.41 MW | 69.41 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944601 | AF1-125 C | 80/20 | 69.41 MW | 69.41 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 945361 | AF1-201 C | Adder | 19.74 MW | 16.78 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 946011 | AF1-266 C | Adder | 18.9 MW | 16.06 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957711 | AF2-065 C | Adder | 17.24 MW | 14.65 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 961711 | AG1-011 C | Adder | 36.04 MW | 30.64 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962271 | AG1-075 C | Adder | 20.42 MW | 17.35 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962491 | AG1-098 C | Adder | 13.53 MW | 11.5 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962561 | AG1-105 C | Adder | 0.96 MW | 0.81 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963291 | AG1-178 C | 80/20 | 97.03 MW | 97.03 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963311 | AG1-180 C | Adder | 3.66 MW | 3.12 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963351 | AG1-184 C | 80/20 | 52.27 MW | 52.27 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 964951 | AG1-359 C | 80/20 | 32.77 MW | 32.77 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965001 | AG1-364 C | 80/20 | 10.24 MW | 10.24 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965281 | AG1-393 C | Adder | 2.63 MW | 2.23 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965601 | AG1-428 C | Adder | 6.3 MW | 5.35 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965691 | AG1-437 C | Adder | 14.02 MW | 11.91 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965701 | AG1-438 C | Adder | 14.02 MW | 11.91 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965711 | AG1-439 C | Adder | 31.3 MW | 26.6 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965741 | AG1-442 C | Adder | 8.18 MW | 6.95 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965751 | AG1-443 C | Adder | 8.18 MW | 6.95 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965761 | AG1-444 C | Adder | 16.69 MW | 14.19 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965771 | AG1-445 C | Adder | 5.61 MW | 4.77 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965781 | AG1-446 C | Adder | 5.61 MW | 4.77 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965811 | AG1-449 C | 80/20 | 35.45 MW | 35.45 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 966611 | AG1-531 C | Adder | 7.59 MW | 6.45 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 313764 | 3SOCKMAN | Adder | 0.96 MW | 0.82 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 932631 | AC2-084 C | Adder | 8.81 MW | 7.49 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 934321 | AD1-056 C | Adder | 8.34 MW | 7.09 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 934331 | AD1-057 C | Adder | 4.65 MW | 3.95 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 934501 | AD1-074 C | Adder | 46.84 MW | 39.81 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 934511 | AD1-075 C | Adder | 11.71 MW | 9.95 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 935161 | AD1-151 C | Adder | 20.03 MW | 17.03 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 938531 | AE1-072 C | Adder | 25.12 MW | 21.35 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 939191 | AE1-149 C | Adder | 14.15 MW | 12.03 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 940431 | AE2-027 C | Adder | 15.55 MW | 13.21 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 940481 | AE2-033 C | Adder | 22.58 MW | 19.19 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 940541 | AE2-040 C | Adder | 4.02 MW | 3.41 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 940641 | AE2-051 C | 80/20 | 26.79 MW | 26.79 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 940651 | AE2-052 C | Adder | 4.72 MW | 4.01 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941101 | AE2-104 C | Adder | 4.74 MW | 4.03 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941281 | AE2-122 C | 80/20 | 40.75 MW | 40.75 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944641 | AF1-129 C | Adder | 119.01 MW | 101.16 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 945811 | AF1-246 C | Adder | 10.71 MW | 9.1 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316303 | AF2-085 | 80/20 | 5.77 MW | 5.77 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 46.29 MW | 46.29 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 31.37 MW | 31.37 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 126.94 MW | 126.94 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | NY | PJM->LTFIMP_NY | CLTF | 2.42 MW | 2.42 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | LGEE | LTFEXP_LGEE->PJM | CLTF | 1.85 MW | 1.85 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | WEC | LTFEXP_WEC->PJM | CLTF | 0.96 MW | 0.96 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CPLE | LTFEXP_CPLE->PJM | CLTF | 15.11 MW | 15.11 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | TVA | LTFEXP_TVA->PJM | CLTF | 8.38 MW | 8.38 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | MEC | LTFEXP_MEC->PJM | CLTF | 5.67 MW | 5.67 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | LAGN | LTFEXP_LAGN->PJM | CLTF | 10.59 MW | 10.59 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.35 MW | 0.35 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 7.21 MW | 7.21 MW |
| Details for 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314184 | 3SHACKLE | 80/20 | 0.2 MW | 0.2 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314314 | 3LOCKS | Adder | 0.53 MW | 0.45 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314421 | 6WINCHST | 80/20 | 0.05 MW | 0.05 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314507 | 3THOMPSN | Adder | 0.68 MW | 0.58 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315060 | 1CHESTF5 | 80/20 | 78.55 MW | 78.55 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315061 | 1CHESTG7 | 80/20 | 4.04 MW | 4.04 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315062 | 1CHESTS7 | 80/20 | 1.86 MW | 1.86 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315063 | 1CHESTG8 | 80/20 | 3.98 MW | 3.98 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315064 | 1CHESTS8 | 80/20 | 2.05 MW | 2.05 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315073 | 1STONECA | 80/20 | 4.58 MW | 4.58 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315076 | 1HOPPOLC | 80/20 | 0.86 MW | 0.86 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315077 | 1HOPHCF1 | 80/20 | 1.36 MW | 1.36 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315078 | 1HOPHCF2 | 80/20 | 1.36 MW | 1.36 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315079 | 1HOPHCF3 | 80/20 | 1.36 MW | 1.36 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315080 | 1HOPHCF4 | 80/20 | 2.07 MW | 2.07 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315092 | 1YORKTN3 | 80/20 | 57.3 MW | 57.3 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 936591 | AD2-074 C | 80/20 | 2.39 MW | 2.39 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 942341 | AE2-247 C | Adder | 0.49 MW | 0.42 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 943461 | AF1-017 C | Adder | 0.45 MW | 0.38 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 943741 | AF1-042 C | 80/20 | 1.25 MW | 1.25 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944871 | AF1-152 C | Adder | 1.65 MW | 1.4 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 961951 | AG1-038 C | 80/20 | 1.38 MW | 1.38 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 966661 | AG1-536 C | Adder | 2.29 MW | 1.95 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315116 | 1SURRY 1 | 80/20 | 9.69 MW | 9.69 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315117 | 1GRAVELC | 80/20 | 0.34 MW | 0.34 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315119 | 1GRAVEL3 | 80/20 | 0.98 MW | 0.98 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315120 | 1GRAVEL4 | 80/20 | 1.0 MW | 1.0 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315121 | 1GRAVEL5 | 80/20 | 0.98 MW | 0.98 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315122 | 1GRAVEL6 | 80/20 | 0.99 MW | 0.99 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315260 | 1GOSPORTA | Adder | 0.72 MW | 0.61 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315261 | 1GOSPORTB | Adder | 0.92 MW | 0.78 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315262 | 1GOSPORTC | Adder | 0.78 MW | 0.67 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315611 | 6Z1-036WIND | Adder | 2.06 MW | 1.75 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316108 | AB2-160 C | Adder | 1.62 MW | 1.37 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316132 | AB2-190 C | 80/20 | 2.36 MW | 2.36 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316156 | AD2-030 C | 80/20 | 0.14 MW | 0.14 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957601 | AF2-054 C | 80/20 | 0.93 MW | 0.93 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962531 | AG1-102 C | 80/20 | 0.46 MW | 0.46 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962861 | AG1-135 C | Adder | 2.59 MW | 2.2 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962971 | AG1-146 C | 80/20 | 1.33 MW | 1.33 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962981 | AG1-147 C | 80/20 | 3.11 MW | 3.11 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963611 | AG1-210 C | Adder | 0.28 MW | 0.23 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 964211 | AG1-282 C | Adder | 0.86 MW | 0.73 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941501 | AE2-147 C | Adder | 4.96 MW | 4.21 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957831 | AF2-077 C | 80/20 | 0.9 MW | 0.9 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957871 | AF2-081 C | Adder | 3.22 MW | 2.74 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 958161 | AF2-110 C | Adder | 0.44 MW | 0.38 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 933291 | AC2-141 C | Adder | 9.37 MW | 7.96 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 934011 | AD1-025 C | 80/20 | 9.36 MW | 9.36 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316059 | AD1-063 C | 80/20 | 0.1 MW | 0.1 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316159 | AE1-175 C | 80/20 | 0.15 MW | 0.15 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316169 | AC1-164 GEN | 80/20 | 2.95 MW | 2.95 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316233 | AE1-074 C | Adder | -1.88 MW | -1.6 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316236 | AE1-162 C | 80/20 | 0.12 MW | 0.12 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316304 | AE2-227 C | Adder | -6.36 MW | -5.41 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316314 | AB2-024 C | 80/20 | 0.12 MW | 0.12 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316369 | AC1-216 C | 80/20 | 0.75 MW | 0.75 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316382 | AG1-145 C | 80/20 | 0.13 MW | 0.13 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 939611 | AE1-191 C | 80/20 | 0.51 MW | 0.51 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963221 | AG1-171 C | 80/20 | 1.19 MW | 1.19 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963231 | AG1-172 C | 80/20 | 1.19 MW | 1.19 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963241 | AG1-173 C | 80/20 | 1.19 MW | 1.19 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963251 | AG1-174 C | 80/20 | 1.19 MW | 1.19 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316201 | AC1-065 C | 80/20 | 4.45 MW | 4.45 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316033 | AB2-134 GEN | 80/20 | 0.98 MW | 0.98 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316311 | AC2-079 C | Adder | 1.89 MW | 1.6 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316280 | AD1-041 C | 80/20 | 0.32 MW | 0.32 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316349 | AD2-085 C | Adder | 1.14 MW | 0.96 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 961611 | AG1-000B C | 80/20 | 7.78 MW | 7.78 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941291 | AE2-123 C | Adder | 9.69 MW | 8.24 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941301 | AE2-124 C | Adder | 8.79 MW | 7.47 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941591 | AE2-156 C | Adder | 6.06 MW | 5.15 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 942371 | AE2-250 C | Adder | 2.87 MW | 2.44 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 942551 | AE2-270 C | 80/20 | 14.89 MW | 14.89 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944581 | AF1-123 C | Adder | 15.38 MW | 13.07 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944591 | AF1-124 C | Adder | 15.38 MW | 13.07 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944601 | AF1-125 C | Adder | 15.38 MW | 13.07 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944631 | AF1-128 C | 80/20 | 49.15 MW | 49.15 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 945361 | AF1-201 C | 80/20 | 6.7 MW | 6.7 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957711 | AF2-065 C | 80/20 | 7.59 MW | 7.59 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 958261 | AF2-120 C | Adder | 2.66 MW | 2.26 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 961711 | AG1-011 C | 80/20 | 15.9 MW | 15.9 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962271 | AG1-075 C | Adder | 4.95 MW | 4.21 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 964951 | AG1-359 C | Adder | 7.45 MW | 6.33 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965001 | AG1-364 C | Adder | 2.42 MW | 2.06 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965281 | AG1-393 C | Adder | 0.64 MW | 0.54 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 966611 | AG1-531 C | 80/20 | 2.54 MW | 2.54 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 935161 | AD1-151 C | 80/20 | 9.32 MW | 9.32 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 938531 | AE1-072 C | Adder | 5.65 MW | 4.8 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 939191 | AE1-149 C | Adder | 3.76 MW | 3.19 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 939601 | AE1-190 C | 80/20 | 0.94 MW | 0.94 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 940431 | AE2-027 C | Adder | 3.82 MW | 3.24 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 940551 | AE2-041 C | 80/20 | 3.27 MW | 3.27 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 940651 | AE2-052 C | Adder | 1.25 MW | 1.06 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941101 | AE2-104 C | Adder | 1.08 MW | 0.92 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941281 | AE2-122 C | Adder | 9.43 MW | 8.02 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 943471 | AF1-018 C | 80/20 | 3.27 MW | 3.27 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 1.4 MW | 1.4 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 2.14 MW | 2.14 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 13.48 MW | 13.48 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | NY | PJM->LTFIMP_NY | CLTF | 0.3 MW | 0.3 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.07 MW | 0.07 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | WEC | LTFEXP_WEC->PJM | CLTF | 0.03 MW | 0.03 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CPLE | LTFEXP_CPLE->PJM | CLTF | 1.74 MW | 1.74 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | TVA | LTFEXP_TVA->PJM | CLTF | 0.65 MW | 0.65 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | MEC | LTFEXP_MEC->PJM | CLTF | 0.28 MW | 0.28 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | LAGN | LTFEXP_LAGN->PJM | CLTF | 0.84 MW | 0.84 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.02 MW | 0.02 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.83 MW | 0.83 MW |
| Details for 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 963041 | AG1-153 C | Adder | 4.28 MW | 3.63 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 963111 | AG1-160 C | Adder | 4.32 MW | 3.67 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 964801 | AG1-343 C | Adder | 4.95 MW | 4.21 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 965291 | AG1-394 C | Adder | 1.7 MW | 1.45 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 966361 | AG1-505 C | Adder | 12.79 MW | 10.88 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 966371 | AG1-506 C | Adder | 12.79 MW | 10.88 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 934521 | AD1-076 C | Adder | 10.27 MW | 8.73 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 942931 | AE2-313 C | Adder | 27.53 MW | 23.4 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 944011 | AF1-069 C | Adder | 9.95 MW | 8.46 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 941031 | AE2-094 C | Adder | 30.46 MW | 25.89 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 957531 | AF2-047 C | Adder | 14.48 MW | 12.3 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 938771 | AE1-103 C | Adder | 2.5 MW | 2.13 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 314229 | 6MT RD221 | 80/20 | 0.1 MW | 0.1 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 314236 | 6NRTHEST | 80/20 | 0.14 MW | 0.14 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 314250 | 6ROCKVILLE | 80/20 | 1.85 MW | 1.85 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 314314 | 3LOCKS | Adder | 1.61 MW | 1.37 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 314507 | 3THOMPSN | Adder | 1.77 MW | 1.51 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 315039 | 1LDYSMT3 | 80/20 | 3.71 MW | 3.71 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 315040 | 1LDYSMT4 | 80/20 | 3.72 MW | 3.72 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 315041 | 1LDYSMT5 | 80/20 | 3.73 MW | 3.73 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 315060 | 1CHESTF5 | Adder | 58.26 MW | 49.52 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 315065 | 1CHESTF6 | Adder | 17.79 MW | 15.12 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 315067 | 1DARBY 1 | 80/20 | 2.0 MW | 2.0 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 315068 | 1DARBY 2 | 80/20 | 2.0 MW | 2.0 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 315069 | 1DARBY 3 | 80/20 | 2.01 MW | 2.01 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 315070 | 1DARBY 4 | 80/20 | 2.01 MW | 2.01 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 315073 | 1STONECA | Adder | 6.27 MW | 5.33 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 315083 | 1SPRUNCA | Adder | 8.24 MW | 7.0 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 315084 | 1SPRUNCB | Adder | 8.24 MW | 7.0 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 315092 | 1YORKTN3 | Adder | 126.71 MW | 107.7 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 936591 | AD2-074 C | Adder | 4.73 MW | 4.02 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 942341 | AE2-247 C | Adder | 1.31 MW | 1.11 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 943461 | AF1-017 C | Adder | 1.18 MW | 1.0 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 943741 | AF1-042 C | Adder | 2.47 MW | 2.1 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 944871 | AF1-152 C | Adder | 4.57 MW | 3.88 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 960091 | AF2-300 C | 80/20 | 2.05 MW | 2.05 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 961951 | AG1-038 C | Adder | 2.74 MW | 2.33 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 966661 | AG1-536 C | Adder | 4.53 MW | 3.85 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 966871 | AG1-558 C | Adder | 2.2 MW | 1.87 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 966881 | AG1-559 C | 80/20 | 2.28 MW | 2.28 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 315225 | 1N ANNA1 | 80/20 | 22.18 MW | 22.18 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 315226 | 1N ANNA2 | 80/20 | 22.18 MW | 22.18 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 315260 | 1GOSPORTA | Adder | 1.87 MW | 1.59 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 315261 | 1GOSPORTB | Adder | 2.39 MW | 2.03 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 315262 | 1GOSPORTC | Adder | 2.03 MW | 1.72 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 315611 | 6Z1-036WIND | Adder | 5.84 MW | 4.97 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 316075 | AC2-137 C | 80/20 | 0.3 MW | 0.3 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 316108 | AB2-160 C | Adder | 4.9 MW | 4.17 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 957411 | AF2-035 C | 80/20 | 8.22 MW | 8.22 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 957601 | AF2-054 C | Adder | 1.85 MW | 1.57 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 962531 | AG1-102 C | Adder | 0.97 MW | 0.83 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 962861 | AG1-135 C | Adder | 5.12 MW | 4.35 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 962971 | AG1-146 C | Adder | 2.64 MW | 2.24 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 962981 | AG1-147 C | Adder | 6.16 MW | 5.23 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 963051 | AG1-154 C | 80/20 | 3.37 MW | 3.37 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 941501 | AE2-147 C | Adder | 13.71 MW | 11.66 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 942001 | AE2-212 C | Adder | 1.93 MW | 1.64 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 957831 | AF2-077 C | Adder | 1.9 MW | 1.61 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 957871 | AF2-081 C | Adder | 8.71 MW | 7.4 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 958161 | AF2-110 C | Adder | 1.19 MW | 1.01 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 933291 | AC2-141 C | Adder | 26.74 MW | 22.73 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 939411 | AE1-173 C | Adder | 73.72 MW | 62.66 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 934011 | AD1-025 C | Adder | 15.21 MW | 12.93 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 927041 | AC1-191 C | Adder | 8.81 MW | 7.49 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 933981 | AD1-022 C | Adder | 7.33 MW | 6.23 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 316004 | AC1-112 C | 80/20 | 0.26 MW | 0.26 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 316169 | AC1-164 GEN | 80/20 | 5.15 MW | 5.15 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 316233 | AE1-074 C | Adder | 2.16 MW | 1.84 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 316240 | AF1-291 C | Adder | 1.95 MW | 1.66 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 316301 | AE2-228 C | Adder | 1.95 MW | 1.66 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 316304 | AE2-227 C | Adder | 2.01 MW | 1.71 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 316312 | AB1-027 C | 80/20 | 0.42 MW | 0.42 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 963221 | AG1-171 C | Adder | 1.94 MW | 1.65 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 963231 | AG1-172 C | Adder | 1.94 MW | 1.65 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 963241 | AG1-173 C | Adder | 1.94 MW | 1.65 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 963251 | AG1-174 C | Adder | 1.94 MW | 1.65 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 315037 | 1LDYSMT1 | 80/20 | 3.57 MW | 3.57 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 315038 | 1LDYSMT2 | 80/20 | 3.62 MW | 3.62 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 315051 | AA1-145 CT1 | 80/20 | 3.97 MW | 3.97 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 315052 | AA1-145 CT2 | 80/20 | 3.97 MW | 3.97 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 226921 | AE1-013 C | Adder | -0.05 MW | -0.05 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 316201 | AC1-065 C | Adder | 8.88 MW | 7.55 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 316427 | AG1-213 C | 80/20 | 0.69 MW | 0.69 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 315043 | 1FOUR RIVERA | 80/20 | 2.49 MW | 2.49 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 315044 | 1FOUR RIVERB | 80/20 | 2.49 MW | 2.49 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 315045 | 1FOUR RIVERC | 80/20 | 3.05 MW | 3.05 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 315046 | 1FOUR RIVERD | 80/20 | 2.46 MW | 2.46 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 315047 | 1FOUR RIVERE | 80/20 | 2.46 MW | 2.46 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 315048 | 1FOUR RIVERF | 80/20 | 3.0 MW | 3.0 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 316311 | AC2-079 C | Adder | 5.02 MW | 4.26 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 316349 | AD2-085 C | Adder | 3.01 MW | 2.56 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 961611 | AG1-000B C | Adder | 14.26 MW | 12.12 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 941291 | AE2-123 C | Adder | 25.62 MW | 21.77 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 941301 | AE2-124 C | Adder | 23.29 MW | 19.8 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 941591 | AE2-156 C | Adder | 15.73 MW | 13.37 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 942371 | AE2-250 C | Adder | 8.7 MW | 7.4 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 942551 | AE2-270 C | Adder | 24.21 MW | 20.58 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 944581 | AF1-123 C | Adder | 42.04 MW | 35.73 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 944591 | AF1-124 C | Adder | 42.04 MW | 35.73 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 944601 | AF1-125 C | Adder | 42.04 MW | 35.73 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 944631 | AF1-128 C | Adder | 36.46 MW | 30.99 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 945361 | AF1-201 C | Adder | 14.32 MW | 12.17 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 946011 | AF1-266 C | Adder | 11.01 MW | 9.36 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 957711 | AF2-065 C | Adder | 12.35 MW | 10.5 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 958261 | AF2-120 C | Adder | 5.26 MW | 4.47 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 961711 | AG1-011 C | Adder | 25.83 MW | 21.95 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 962271 | AG1-075 C | Adder | 15.02 MW | 12.77 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 962841 | AG1-133 C | 80/20 | 15.65 MW | 15.65 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 963291 | AG1-178 C | Adder | 49.41 MW | 41.99 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 963351 | AG1-184 C | Adder | 26.62 MW | 22.62 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 964951 | AG1-359 C | Adder | 19.97 MW | 16.98 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 965001 | AG1-364 C | Adder | 6.29 MW | 5.35 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 965281 | AG1-393 C | Adder | 1.93 MW | 1.64 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 965811 | AG1-449 C | Adder | 17.83 MW | 15.15 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 966611 | AG1-531 C | Adder | 5.2 MW | 4.42 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 934501 | AD1-074 C | Adder | 28.28 MW | 24.04 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 934511 | AD1-075 C | Adder | 7.07 MW | 6.01 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 935161 | AD1-151 C | Adder | 14.56 MW | 12.38 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 938531 | AE1-072 C | Adder | 15.31 MW | 13.01 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 939191 | AE1-149 C | Adder | 9.5 MW | 8.08 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 939261 | AE1-157 C | 80/20 | 13.24 MW | 13.24 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 939601 | AE1-190 C | Adder | 1.87 MW | 1.59 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 940431 | AE2-027 C | Adder | 11.64 MW | 9.89 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 940481 | AE2-033 C | Adder | 13.15 MW | 11.18 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 940541 | AE2-040 C | Adder | 2.34 MW | 1.99 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 940551 | AE2-041 C | Adder | 6.29 MW | 5.35 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 940641 | AE2-051 C | Adder | 13.73 MW | 11.67 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 940651 | AE2-052 C | Adder | 3.17 MW | 2.69 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 941101 | AE2-104 C | Adder | 2.92 MW | 2.48 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 941281 | AE2-122 C | Adder | 24.93 MW | 21.19 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 942191 | AE2-231 C | 80/20 | 4.52 MW | 4.52 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 943471 | AF1-018 C | Adder | 6.29 MW | 5.35 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 944641 | AF1-129 C | Adder | 92.77 MW | 78.86 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | 963622 | AG1-213 E | 80/20 | 0.69 MW | 0.69 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 45.74 MW | 45.74 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 25.93 MW | 25.93 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 81.55 MW | 81.55 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | NY | PJM->LTFIMP_NY | CLTF | 2.84 MW | 2.84 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | LGEE | LTFEXP_LGEE->PJM | CLTF | 1.82 MW | 1.82 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | WEC | LTFEXP_WEC->PJM | CLTF | 0.94 MW | 0.94 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | CPLE | LTFEXP_CPLE->PJM | CLTF | 9.12 MW | 9.12 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | TVA | LTFEXP_TVA->PJM | CLTF | 6.57 MW | 6.57 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | MEC | LTFEXP_MEC->PJM | CLTF | 5.15 MW | 5.15 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | LAGN | LTFEXP_LAGN->PJM | CLTF | 8.18 MW | 8.18 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.33 MW | 0.33 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 4.35 MW | 4.35 MW |
| Details for 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 942931 | AE2-313 C | Adder | 1.72 MW | 1.47 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 944011 | AF1-069 C | Adder | 6.94 MW | 5.9 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 941031 | AE2-094 C | Adder | 21.24 MW | 18.06 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 938771 | AE1-103 C | Adder | 1.72 MW | 1.46 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 314131 | 6ARNOLDS | 80/20 | 0.16 MW | 0.16 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 314250 | 6ROCKVILLE | Adder | 1.28 MW | 1.09 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 314314 | 3LOCKS | Adder | 1.12 MW | 0.95 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 314507 | 3THOMPSN | Adder | 1.22 MW | 1.04 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 315001 | 1OMF A | 80/20 | 0.74 MW | 0.74 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 315002 | 1OMF B | 80/20 | 0.74 MW | 0.74 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 315007 | 1POSSM 5 | 80/20 | 104.64 MW | 104.64 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 315008 | 1POSSM6A | 80/20 | 3.21 MW | 3.21 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 315009 | 1POSSM6B | 80/20 | 3.21 MW | 3.21 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 315010 | 1POSSM6S | 80/20 | 5.01 MW | 5.01 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 315015 | 1POSSMC1 | 80/20 | 0.71 MW | 0.71 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 315018 | 1POSSMC2 | 80/20 | 0.71 MW | 0.71 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 315033 | 1BIRCHWDA | 80/20 | 32.67 MW | 32.67 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 315039 | 1LDYSMT3 | 80/20 | 3.13 MW | 3.13 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 315040 | 1LDYSMT4 | 80/20 | 3.14 MW | 3.14 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 315041 | 1LDYSMT5 | 80/20 | 3.15 MW | 3.15 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 315060 | 1CHESTF5 | Adder | 40.3 MW | 34.26 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 315065 | 1CHESTF6 | Adder | 12.31 MW | 10.46 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 315073 | 1STONECA | Adder | 4.34 MW | 3.69 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 315083 | 1SPRUNCA | Adder | 5.74 MW | 4.88 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 315084 | 1SPRUNCB | Adder | 5.74 MW | 4.88 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 315092 | 1YORKTN3 | Adder | 88.28 MW | 75.04 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 934781 | AD1-105 C | Adder | 5.55 MW | 4.72 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 934861 | AD1-115 C | Adder | 1.95 MW | 1.66 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 936591 | AD2-074 C | Adder | 3.88 MW | 3.3 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 942341 | AE2-247 C | Adder | 0.9 MW | 0.77 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 943461 | AF1-017 C | Adder | 0.82 MW | 0.69 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 943741 | AF1-042 C | Adder | 2.03 MW | 1.73 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 944491 | AF1-114 C | 80/20 | 5.41 MW | 5.41 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 944871 | AF1-152 C | Adder | 3.14 MW | 2.67 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 960091 | AF2-300 C | 80/20 | 1.61 MW | 1.61 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 961951 | AG1-038 C | Adder | 2.25 MW | 1.91 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 966661 | AG1-536 C | Adder | 3.82 MW | 3.25 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 966871 | AG1-558 C | Adder | 1.6 MW | 1.36 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 966881 | AG1-559 C | 80/20 | 1.79 MW | 1.79 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 315225 | 1N ANNA1 | 80/20 | 18.01 MW | 18.01 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 315226 | 1N ANNA2 | 80/20 | 18.01 MW | 18.01 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 315260 | 1GOSPORTA | Adder | 1.29 MW | 1.1 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 315261 | 1GOSPORTB | Adder | 1.65 MW | 1.4 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 315262 | 1GOSPORTC | Adder | 1.4 MW | 1.19 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 315611 | 6Z1-036WIND | Adder | 4.0 MW | 3.4 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 316108 | AB2-160 C | Adder | 3.4 MW | 2.89 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 946371 | AF1-301 C | Adder | 7.21 MW | 6.13 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 957411 | AF2-035 C | 80/20 | 6.46 MW | 6.46 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 957601 | AF2-054 C | Adder | 1.39 MW | 1.18 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 962531 | AG1-102 C | Adder | 0.7 MW | 0.6 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 962851 | AG1-134 C | Adder | 7.5 MW | 6.38 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 962861 | AG1-135 C | Adder | 4.3 MW | 3.65 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 962971 | AG1-146 C | Adder | 2.13 MW | 1.81 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 962981 | AG1-147 C | Adder | 4.97 MW | 4.23 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 963051 | AG1-154 C | 80/20 | 2.85 MW | 2.85 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 963611 | AG1-210 C | Adder | 0.48 MW | 0.41 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 964211 | AG1-282 C | Adder | 1.44 MW | 1.23 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 964271 | AG1-288 C | 80/20 | 12.66 MW | 12.66 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 965441 | AG1-412 C | 80/20 | 11.36 MW | 11.36 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 941501 | AE2-147 C | Adder | 9.42 MW | 8.01 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 942001 | AE2-212 C | Adder | 1.34 MW | 1.14 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 957831 | AF2-077 C | Adder | 1.37 MW | 1.17 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 957871 | AF2-081 C | Adder | 6.0 MW | 5.1 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 957971 | AF2-091 C | 80/20 | 1.84 MW | 1.84 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 958161 | AF2-110 C | Adder | 0.82 MW | 0.7 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 966331 | AG1-502 C | Adder | 7.08 MW | 6.02 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 966341 | AG1-503 C | Adder | 1.77 MW | 1.5 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 933291 | AC2-141 C | Adder | 18.41 MW | 15.65 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 939411 | AE1-173 C | Adder | 51.33 MW | 43.63 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 934011 | AD1-025 C | Adder | 10.52 MW | 8.94 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 927041 | AC1-191 C | Adder | 6.42 MW | 5.45 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 316170 | AC1-121 C | Adder | 1.47 MW | 1.25 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 316233 | AE1-074 C | Adder | 1.52 MW | 1.29 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 316240 | AF1-291 C | Adder | 1.35 MW | 1.15 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 316254 | AC1-120 C | Adder | 4.28 MW | 3.64 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 316257 | AC1-043 C | Adder | 3.9 MW | 3.32 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 316301 | AE2-228 C | Adder | 1.35 MW | 1.15 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 316304 | AE2-227 C | Adder | 1.39 MW | 1.18 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 963221 | AG1-171 C | Adder | 1.34 MW | 1.14 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 963231 | AG1-172 C | Adder | 1.34 MW | 1.14 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 963241 | AG1-173 C | Adder | 1.34 MW | 1.14 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 963251 | AG1-174 C | Adder | 1.34 MW | 1.14 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 315037 | 1LDYSMT1 | 80/20 | 3.02 MW | 3.02 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 315038 | 1LDYSMT2 | 80/20 | 3.06 MW | 3.06 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 315051 | AA1-145 CT1 | 80/20 | 2.85 MW | 2.85 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 316201 | AC1-065 C | Adder | 6.6 MW | 5.61 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 316427 | AG1-213 C | 80/20 | 0.54 MW | 0.54 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 316411 | AF1-147_GEN1 | Adder | -5.23 MW | -4.45 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 316415 | AF1-147_GEN2 | Adder | -5.23 MW | -4.45 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 316044 | AC1-158 C1 | 80/20 | 3.26 MW | 3.26 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 316045 | AC1-158 C2 | 80/20 | 3.26 MW | 3.26 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 316311 | AC2-079 C | Adder | 3.46 MW | 2.94 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 316349 | AD2-085 C | Adder | 2.08 MW | 1.77 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 961611 | AG1-000B C | Adder | 9.87 MW | 8.39 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 941291 | AE2-123 C | Adder | 17.66 MW | 15.01 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 941301 | AE2-124 C | Adder | 16.06 MW | 13.65 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 941591 | AE2-156 C | Adder | 10.85 MW | 9.22 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 942371 | AE2-250 C | Adder | 6.05 MW | 5.14 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 942551 | AE2-270 C | Adder | 16.75 MW | 14.24 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 944581 | AF1-123 C | Adder | 28.98 MW | 24.63 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 944591 | AF1-124 C | Adder | 28.98 MW | 24.63 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 944601 | AF1-125 C | Adder | 28.98 MW | 24.63 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 944631 | AF1-128 C | Adder | 25.22 MW | 21.43 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 945361 | AF1-201 C | Adder | 10.22 MW | 8.69 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 946011 | AF1-266 C | Adder | 7.61 MW | 6.47 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 957431 | AF2-037 C | Adder | 6.81 MW | 5.79 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 957691 | AF2-063 C | Adder | 10.87 MW | 9.24 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 957711 | AF2-065 C | Adder | 8.54 MW | 7.26 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 958261 | AF2-120 C | Adder | 4.45 MW | 3.78 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 961711 | AG1-011 C | Adder | 17.87 MW | 15.19 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 961781 | AG1-019 C | 80/20 | 13.34 MW | 13.34 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 962271 | AG1-075 C | Adder | 10.44 MW | 8.87 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 962841 | AG1-133 C | 80/20 | 10.92 MW | 10.92 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 963291 | AG1-178 C | Adder | 34.55 MW | 29.37 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 963351 | AG1-184 C | Adder | 18.62 MW | 15.82 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 964281 | AG1-289 C | 80/20 | 7.0 MW | 7.0 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 964421 | AG1-305 C | Adder | 8.55 MW | 7.27 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 964951 | AG1-359 C | Adder | 13.76 MW | 11.7 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 965001 | AG1-364 C | Adder | 4.34 MW | 3.69 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 965281 | AG1-393 C | Adder | 1.34 MW | 1.14 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 966611 | AG1-531 C | Adder | 3.61 MW | 3.06 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 935161 | AD1-151 C | Adder | 10.08 MW | 8.56 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 938531 | AE1-072 C | Adder | 10.54 MW | 8.96 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 939191 | AE1-149 C | Adder | 6.58 MW | 5.59 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 939261 | AE1-157 C | 80/20 | 10.69 MW | 10.69 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 939601 | AE1-190 C | Adder | 1.4 MW | 1.19 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 940431 | AE2-027 C | Adder | 8.09 MW | 6.88 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 940481 | AE2-033 C | Adder | 9.09 MW | 7.72 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 940541 | AE2-040 C | Adder | 1.62 MW | 1.37 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 940551 | AE2-041 C | Adder | 4.67 MW | 3.97 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 940641 | AE2-051 C | Adder | 9.6 MW | 8.16 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 940651 | AE2-052 C | Adder | 2.19 MW | 1.86 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 941101 | AE2-104 C | Adder | 2.01 MW | 1.71 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 941281 | AE2-122 C | Adder | 17.18 MW | 14.61 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 942191 | AE2-231 C | 80/20 | 3.55 MW | 3.55 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 943471 | AF1-018 C | Adder | 4.67 MW | 3.97 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 944641 | AF1-129 C | Adder | 64.21 MW | 54.58 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 957191 | AF2-013 C | 80/20 | 13.34 MW | 13.34 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | 963622 | AG1-213 E | 80/20 | 0.54 MW | 0.54 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 6.05 MW | 6.05 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 8.88 MW | 8.88 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 47.28 MW | 47.28 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | NY | PJM->LTFIMP_NY | CLTF | 1.78 MW | 1.78 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.36 MW | 0.36 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | WEC | LTFEXP_WEC->PJM | CLTF | 0.15 MW | 0.15 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | CPLE | LTFEXP_CPLE->PJM | CLTF | 5.67 MW | 5.67 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | TVA | LTFEXP_TVA->PJM | CLTF | 2.71 MW | 2.71 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | MEC | LTFEXP_MEC->PJM | CLTF | 1.23 MW | 1.23 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | LAGN | LTFEXP_LAGN->PJM | CLTF | 3.38 MW | 3.38 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.08 MW | 0.08 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 569_SRT-S | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.71 MW | 2.71 MW |
| Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 961671 | AG1-007 C | Adder | 0.98 MW | 0.83 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 961941 | AG1-037 C | Adder | 0.59 MW | 0.5 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 962331 | AG1-082 C | Adder | 2.37 MW | 2.02 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 962341 | AG1-083 C | Adder | 2.37 MW | 2.02 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963041 | AG1-153 C | Adder | 5.85 MW | 4.97 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963111 | AG1-160 C | Adder | 5.93 MW | 5.04 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963301 | AG1-179 C | Adder | 5.21 MW | 4.43 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964791 | AG1-342 C | Adder | 3.43 MW | 2.92 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964801 | AG1-343 C | Adder | 7.04 MW | 5.98 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 966801 | AG1-551 C | Adder | 2.4 MW | 2.04 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 966811 | AG1-552 C | Adder | 2.12 MW | 1.8 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965291 | AG1-394 C | Adder | 2.42 MW | 2.05 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965591 | AG1-427 C | Adder | 9.47 MW | 8.05 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965721 | AG1-440 C | Adder | 6.78 MW | 5.76 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965731 | AG1-441 C | Adder | 6.78 MW | 5.76 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 966361 | AG1-505 C | Adder | 17.25 MW | 14.66 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 966371 | AG1-506 C | Adder | 17.25 MW | 14.66 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 966621 | AG1-532 C | Adder | 1.34 MW | 1.14 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315131 | 1EDGECMA | Adder | 15.5 MW | 13.17 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 934521 | AD1-076 C | 80/20 | 15.71 MW | 15.71 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 942931 | AE2-313 C | Adder | 37.92 MW | 32.23 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944011 | AF1-069 C | Adder | 13.8 MW | 11.73 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 960061 | AF2-297 C | Adder | 6.51 MW | 5.54 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 960081 | AF2-299 C | Adder | 2.49 MW | 2.11 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 939181 | AE1-148 C | Adder | 7.8 MW | 6.63 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 940491 | AE2-034 C | 80/20 | 1.29 MW | 1.29 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 940571 | AE2-044 C | Adder | 4.34 MW | 3.69 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941031 | AE2-094 C | Adder | 42.23 MW | 35.9 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941791 | AE2-182 C | Adder | 1.5 MW | 1.28 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 946281 | AF1-292 C | Adder | 1.48 MW | 1.26 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 957481 | AF2-042 C | Adder | 52.06 MW | 44.25 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 957521 | AF2-046 C | Adder | 19.9 MW | 16.92 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 957531 | AF2-047 C | 80/20 | 22.7 MW | 22.7 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 957861 | AF2-080 C | Adder | 8.19 MW | 6.96 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 938771 | AE1-103 C | 80/20 | 3.79 MW | 3.79 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 313526 | AB2-022 C | 80/20 | 0.47 MW | 0.47 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 314295 | 6BIRDNECK | 80/20 | 0.06 MW | 0.06 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 314421 | 6WINCHST | 80/20 | 0.14 MW | 0.14 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 314507 | 3THOMPSN | 80/20 | 3.04 MW | 3.04 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315092 | 1YORKTN3 | 80/20 | 175.49 MW | 175.49 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 942341 | AE2-247 C | 80/20 | 1.81 MW | 1.81 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 943461 | AF1-017 C | 80/20 | 1.64 MW | 1.64 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944871 | AF1-152 C | 80/20 | 7.59 MW | 7.59 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315098 | 1CHESPKA | 80/20 | 0.55 MW | 0.55 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315099 | 1CHESPKB | 80/20 | 0.92 MW | 0.92 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315108 | 1ELIZAR1 | 80/20 | 4.09 MW | 4.09 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315109 | 1ELIZAR2 | 80/20 | 4.02 MW | 4.02 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315110 | 1ELIZAR3 | 80/20 | 4.15 MW | 4.15 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315115 | 1S HAMPT1 | 80/20 | 1.57 MW | 1.57 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315233 | 1SURRY 2 | 80/20 | 42.45 MW | 42.45 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315260 | 1GOSPORTA | 80/20 | 3.21 MW | 3.21 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315261 | 1GOSPORTB | 80/20 | 4.09 MW | 4.09 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315262 | 1GOSPORTC | 80/20 | 3.48 MW | 3.48 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315605 | 6W1-029WIND | 80/20 | 0.94 MW | 0.94 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315611 | 6Z1-036WIND | 80/20 | 9.53 MW | 9.53 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 962531 | AG1-102 C | Adder | 0.92 MW | 0.78 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941501 | AE2-147 C | 80/20 | 22.77 MW | 22.77 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 957831 | AF2-077 C | Adder | 1.79 MW | 1.52 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 957871 | AF2-081 C | 80/20 | 15.07 MW | 15.07 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 958161 | AF2-110 C | 80/20 | 1.88 MW | 1.88 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 926071 | AC1-086 C | Adder | 21.39 MW | 18.18 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 927021 | AC1-189 C | Adder | 9.02 MW | 7.67 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 933291 | AC2-141 C | 80/20 | 53.95 MW | 53.95 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 934621 | AD1-088 C | Adder | 9.25 MW | 7.87 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 939411 | AE1-173 C | 80/20 | 116.73 MW | 116.73 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 934011 | AD1-025 C | Adder | 13.79 MW | 11.72 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 933981 | AD1-022 C | 80/20 | 11.07 MW | 11.07 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 960331 | AF2-324 C | Adder | 6.97 MW | 5.93 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 961681 | AG1-008 C | Adder | 19.94 MW | 16.95 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 962571 | AG1-106 C | Adder | 5.95 MW | 5.06 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 316036 | AC1-147 C | 80/20 | 0.47 MW | 0.47 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 316072 | AD1-144 C | 80/20 | 0.33 MW | 0.33 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 316185 | AD1-033 C | 80/20 | 1.59 MW | 1.59 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 316210 | AC1-098 C | Adder | 6.53 MW | 5.55 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 316212 | AC1-099 C | Adder | 2.19 MW | 1.86 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 316222 | AC1-221 C | Adder | 6.83 MW | 5.81 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 316236 | AE1-162 C | 80/20 | 0.37 MW | 0.37 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 316246 | AF1-032 C | 80/20 | 0.35 MW | 0.35 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 316263 | AC1-034 C | Adder | 6.62 MW | 5.63 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 316274 | AC1-208 C | Adder | 9.39 MW | 7.98 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 316294 | AC1-161 C | 80/20 | 7.44 MW | 7.44 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 316305 | AF2-043 C | 80/20 | 0.43 MW | 0.43 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 316316 | AC1-027 C | 80/20 | 0.4 MW | 0.4 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 316320 | Y1-086 C | 80/20 | 0.27 MW | 0.27 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 316321 | Z2-027 C | 80/20 | 0.45 MW | 0.45 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963221 | AG1-171 C | Adder | 1.76 MW | 1.49 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963231 | AG1-172 C | Adder | 1.76 MW | 1.49 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963241 | AG1-173 C | Adder | 1.76 MW | 1.49 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963251 | AG1-174 C | Adder | 1.76 MW | 1.49 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 316017 | AA1-139 ULT1 | 80/20 | 1.38 MW | 1.38 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 316018 | AA1-139 ULT2 | 80/20 | 1.38 MW | 1.38 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315614 | AA2-178 C | 80/20 | 1.76 MW | 1.76 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 316181 | AB2-040 GEN | Adder | 7.46 MW | 6.34 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 316375 | AC2-012 C | 80/20 | 1.73 MW | 1.73 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 316311 | AC2-079 C | 80/20 | 7.09 MW | 7.09 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 316349 | AD2-085 C | 80/20 | 4.18 MW | 4.18 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 316388 | AE2-253 GEN | 80/20 | 2.51 MW | 2.51 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 961611 | AG1-000B C | Adder | 16.24 MW | 13.8 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 940661 | AE2-053 C | Adder | 2.89 MW | 2.45 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941291 | AE2-123 C | 80/20 | 44.38 MW | 44.38 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941301 | AE2-124 C | 80/20 | 40.4 MW | 40.4 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941591 | AE2-156 C | 80/20 | 27.03 MW | 27.03 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 942551 | AE2-270 C | Adder | 21.99 MW | 18.69 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944581 | AF1-123 C | 80/20 | 75.66 MW | 75.66 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944591 | AF1-124 C | 80/20 | 75.66 MW | 75.66 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944601 | AF1-125 C | 80/20 | 75.66 MW | 75.66 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 945361 | AF1-201 C | Adder | 15.66 MW | 13.31 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 946011 | AF1-266 C | Adder | 12.39 MW | 10.53 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 957711 | AF2-065 C | Adder | 11.21 MW | 9.53 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 961711 | AG1-011 C | Adder | 23.42 MW | 19.91 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 962491 | AG1-098 C | Adder | 8.36 MW | 7.11 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 962561 | AG1-105 C | Adder | 7.36 MW | 6.26 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963291 | AG1-178 C | 80/20 | 72.76 MW | 72.76 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963311 | AG1-180 C | Adder | 2.53 MW | 2.15 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963351 | AG1-184 C | 80/20 | 39.2 MW | 39.2 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964241 | AG1-285 C | Adder | 9.92 MW | 8.43 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964951 | AG1-359 C | 80/20 | 34.95 MW | 34.95 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965001 | AG1-364 C | 80/20 | 10.81 MW | 10.81 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965601 | AG1-428 C | Adder | 4.35 MW | 3.7 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965691 | AG1-437 C | 80/20 | 12.63 MW | 12.63 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965701 | AG1-438 C | 80/20 | 12.63 MW | 12.63 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965711 | AG1-439 C | Adder | 24.82 MW | 21.1 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965741 | AG1-442 C | 80/20 | 7.37 MW | 7.37 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965751 | AG1-443 C | 80/20 | 7.37 MW | 7.37 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965761 | AG1-444 C | Adder | 13.24 MW | 11.25 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965771 | AG1-445 C | Adder | 3.92 MW | 3.33 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965781 | AG1-446 C | Adder | 3.92 MW | 3.33 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965811 | AG1-449 C | Adder | 24.56 MW | 20.87 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 966611 | AG1-531 C | 80/20 | 6.76 MW | 6.76 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 313764 | 3SOCKMAN | Adder | 0.72 MW | 0.61 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 932631 | AC2-084 C | Adder | 6.98 MW | 5.93 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 934321 | AD1-056 C | Adder | 6.3 MW | 5.35 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 934331 | AD1-057 C | Adder | 3.51 MW | 2.99 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 934501 | AD1-074 C | 80/20 | 43.24 MW | 43.24 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 934511 | AD1-075 C | 80/20 | 10.81 MW | 10.81 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 935161 | AD1-151 C | Adder | 12.04 MW | 10.23 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 938531 | AE1-072 C | 80/20 | 26.38 MW | 26.38 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 939191 | AE1-149 C | Adder | 8.56 MW | 7.28 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 940481 | AE2-033 C | Adder | 14.8 MW | 12.58 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 940541 | AE2-040 C | Adder | 2.6 MW | 2.21 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 940641 | AE2-051 C | 80/20 | 20.89 MW | 20.89 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 940651 | AE2-052 C | Adder | 2.85 MW | 2.42 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941101 | AE2-104 C | 80/20 | 4.61 MW | 4.61 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941281 | AE2-122 C | 80/20 | 43.19 MW | 43.19 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944141 | AF1-082 C | Adder | 2.79 MW | 2.37 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 945811 | AF1-246 C | Adder | 7.29 MW | 6.2 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 25.09 MW | 25.09 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 19.03 MW | 19.03 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 86.57 MW | 86.57 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | NY | PJM->LTFIMP_NY | CLTF | 1.5 MW | 1.5 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | LGEE | LTFEXP_LGEE->PJM | CLTF | 1.01 MW | 1.01 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | WEC | LTFEXP_WEC->PJM | CLTF | 0.52 MW | 0.52 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | CPLE | LTFEXP_CPLE->PJM | CLTF | 10.62 MW | 10.62 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | TVA | LTFEXP_TVA->PJM | CLTF | 5.22 MW | 5.22 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | MEC | LTFEXP_MEC->PJM | CLTF | 3.26 MW | 3.26 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | LAGN | LTFEXP_LAGN->PJM | CLTF | 6.64 MW | 6.64 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.2 MW | 0.2 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 5.06 MW | 5.06 MW |
| Details for 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 938771 | AE1-103 C | Adder | 0.86 MW | 0.73 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314309 | 6IRON208 | 80/20 | 0.97 MW | 0.97 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314314 | 3LOCKS | Adder | 0.53 MW | 0.45 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314507 | 3THOMPSN | Adder | 0.68 MW | 0.58 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315060 | 1CHESTF5 | 80/20 | 78.52 MW | 78.52 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315061 | 1CHESTG7 | 80/20 | 4.04 MW | 4.04 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315062 | 1CHESTS7 | 80/20 | 1.86 MW | 1.86 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315063 | 1CHESTG8 | 80/20 | 3.98 MW | 3.98 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315064 | 1CHESTS8 | 80/20 | 2.05 MW | 2.05 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315073 | 1STONECA | 80/20 | 4.58 MW | 4.58 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315076 | 1HOPPOLC | 80/20 | 0.86 MW | 0.86 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315077 | 1HOPHCF1 | 80/20 | 1.36 MW | 1.36 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315078 | 1HOPHCF2 | 80/20 | 1.36 MW | 1.36 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315079 | 1HOPHCF3 | 80/20 | 1.36 MW | 1.36 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315080 | 1HOPHCF4 | 80/20 | 2.07 MW | 2.07 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315092 | 1YORKTN3 | Adder | 57.24 MW | 48.65 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 936591 | AD2-074 C | Adder | 2.39 MW | 2.03 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 942341 | AE2-247 C | Adder | 0.49 MW | 0.42 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 943461 | AF1-017 C | Adder | 0.44 MW | 0.38 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 943741 | AF1-042 C | Adder | 1.25 MW | 1.06 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944871 | AF1-152 C | Adder | 1.65 MW | 1.4 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 961951 | AG1-038 C | Adder | 1.38 MW | 1.17 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 966661 | AG1-536 C | Adder | 2.29 MW | 1.95 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315116 | 1SURRY 1 | 80/20 | 9.68 MW | 9.68 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315117 | 1GRAVELC | 80/20 | 0.34 MW | 0.34 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315119 | 1GRAVEL3 | 80/20 | 0.98 MW | 0.98 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315120 | 1GRAVEL4 | 80/20 | 0.99 MW | 0.99 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315121 | 1GRAVEL5 | 80/20 | 0.98 MW | 0.98 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315122 | 1GRAVEL6 | 80/20 | 0.99 MW | 0.99 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315260 | 1GOSPORTA | Adder | 0.72 MW | 0.61 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315261 | 1GOSPORTB | Adder | 0.92 MW | 0.78 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315262 | 1GOSPORTC | Adder | 0.78 MW | 0.66 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315611 | 6Z1-036WIND | Adder | 2.06 MW | 1.75 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316108 | AB2-160 C | Adder | 1.61 MW | 1.37 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316132 | AB2-190 C | 80/20 | 2.36 MW | 2.36 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957601 | AF2-054 C | Adder | 0.93 MW | 0.79 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962531 | AG1-102 C | Adder | 0.46 MW | 0.39 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962861 | AG1-135 C | Adder | 2.59 MW | 2.2 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962971 | AG1-146 C | Adder | 1.33 MW | 1.13 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962981 | AG1-147 C | Adder | 3.1 MW | 2.64 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963611 | AG1-210 C | Adder | 0.28 MW | 0.23 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 964211 | AG1-282 C | Adder | 0.86 MW | 0.73 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941501 | AE2-147 C | Adder | 4.95 MW | 4.21 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957831 | AF2-077 C | Adder | 0.9 MW | 0.77 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957871 | AF2-081 C | Adder | 3.22 MW | 2.73 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 958161 | AF2-110 C | Adder | 0.44 MW | 0.37 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 933291 | AC2-141 C | Adder | 9.36 MW | 7.95 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 934011 | AD1-025 C | 80/20 | 9.35 MW | 9.35 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316059 | AD1-063 C | 80/20 | 0.1 MW | 0.1 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316159 | AE1-175 C | 80/20 | 0.15 MW | 0.15 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316169 | AC1-164 GEN | 80/20 | 2.95 MW | 2.95 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316233 | AE1-074 C | Adder | -1.88 MW | -1.6 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316304 | AE2-227 C | 80/20 | 5.64 MW | 5.64 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316314 | AB2-024 C | 80/20 | 0.12 MW | 0.12 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316369 | AC1-216 C | 80/20 | 0.75 MW | 0.75 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316382 | AG1-145 C | 80/20 | 0.13 MW | 0.13 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963221 | AG1-171 C | 80/20 | 1.19 MW | 1.19 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963231 | AG1-172 C | 80/20 | 1.19 MW | 1.19 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963241 | AG1-173 C | 80/20 | 1.19 MW | 1.19 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963251 | AG1-174 C | 80/20 | 1.19 MW | 1.19 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316201 | AC1-065 C | Adder | 4.44 MW | 3.77 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316033 | AB2-134 GEN | 80/20 | 0.98 MW | 0.98 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316311 | AC2-079 C | Adder | 1.88 MW | 1.6 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316349 | AD2-085 C | Adder | 1.13 MW | 0.96 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 961611 | AG1-000B C | 80/20 | 7.77 MW | 7.77 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941291 | AE2-123 C | Adder | 9.68 MW | 8.23 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941301 | AE2-124 C | Adder | 8.78 MW | 7.46 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941591 | AE2-156 C | Adder | 6.05 MW | 5.14 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 942371 | AE2-250 C | Adder | 2.86 MW | 2.44 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 942551 | AE2-270 C | 80/20 | 14.88 MW | 14.88 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944581 | AF1-123 C | Adder | 15.36 MW | 13.05 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944591 | AF1-124 C | Adder | 15.36 MW | 13.05 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944601 | AF1-125 C | Adder | 15.36 MW | 13.05 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944631 | AF1-128 C | 80/20 | 49.13 MW | 49.13 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 945361 | AF1-201 C | Adder | 6.69 MW | 5.69 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957711 | AF2-065 C | 80/20 | 7.59 MW | 7.59 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 958261 | AF2-120 C | Adder | 2.66 MW | 2.26 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 961711 | AG1-011 C | 80/20 | 15.88 MW | 15.88 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962271 | AG1-075 C | Adder | 4.94 MW | 4.2 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 964951 | AG1-359 C | Adder | 7.44 MW | 6.32 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965001 | AG1-364 C | Adder | 2.42 MW | 2.06 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965281 | AG1-393 C | Adder | 0.64 MW | 0.54 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 966611 | AG1-531 C | Adder | 2.54 MW | 2.16 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 935161 | AD1-151 C | 80/20 | 9.31 MW | 9.31 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 938531 | AE1-072 C | Adder | 5.64 MW | 4.79 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 939191 | AE1-149 C | Adder | 3.75 MW | 3.19 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 939601 | AE1-190 C | Adder | 0.94 MW | 0.8 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 940431 | AE2-027 C | Adder | 3.81 MW | 3.24 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 940551 | AE2-041 C | 80/20 | 3.26 MW | 3.26 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 940651 | AE2-052 C | Adder | 1.25 MW | 1.06 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941101 | AE2-104 C | Adder | 1.08 MW | 0.92 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941281 | AE2-122 C | Adder | 9.42 MW | 8.01 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 943471 | AF1-018 C | 80/20 | 3.26 MW | 3.26 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 1.26 MW | 1.26 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 2.09 MW | 2.09 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 13.4 MW | 13.4 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | NY | PJM->LTFIMP_NY | CLTF | 0.31 MW | 0.31 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.06 MW | 0.06 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | WEC | LTFEXP_WEC->PJM | CLTF | 0.03 MW | 0.03 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CPLE | LTFEXP_CPLE->PJM | CLTF | 1.74 MW | 1.74 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | TVA | LTFEXP_TVA->PJM | CLTF | 0.64 MW | 0.64 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | MEC | LTFEXP_MEC->PJM | CLTF | 0.27 MW | 0.27 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | LAGN | LTFEXP_LAGN->PJM | CLTF | 0.83 MW | 0.83 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.01 MW | 0.01 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.83 MW | 0.83 MW |
| Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 963041 | AG1-153 C | 80/20 | 4.36 MW | 4.36 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 963111 | AG1-160 C | 80/20 | 4.42 MW | 4.42 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 964801 | AG1-343 C | Adder | 4.61 MW | 3.92 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 965291 | AG1-394 C | Adder | 1.58 MW | 1.35 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 966361 | AG1-505 C | 80/20 | 13.02 MW | 13.02 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 966371 | AG1-506 C | 80/20 | 13.02 MW | 13.02 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 966621 | AG1-532 C | Adder | 1.06 MW | 0.9 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 934521 | AD1-076 C | Adder | 9.5 MW | 8.07 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 942931 | AE2-313 C | 80/20 | 28.25 MW | 28.25 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 944011 | AF1-069 C | 80/20 | 10.24 MW | 10.24 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 960081 | AF2-299 C | Adder | 1.96 MW | 1.67 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 941031 | AE2-094 C | 80/20 | 31.33 MW | 31.33 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 946281 | AF1-292 C | Adder | 1.17 MW | 0.99 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 957481 | AF2-042 C | Adder | 40.56 MW | 34.47 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 957531 | AF2-047 C | Adder | 13.37 MW | 11.36 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 938771 | AE1-103 C | Adder | 2.31 MW | 1.96 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 314250 | 6ROCKVILLE | 80/20 | 1.62 MW | 1.62 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 314314 | 3LOCKS | Adder | 1.43 MW | 1.22 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 314507 | 3THOMPSN | Adder | 1.62 MW | 1.38 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 315060 | 1CHESTF5 | Adder | 48.57 MW | 41.28 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 315065 | 1CHESTF6 | Adder | 15.59 MW | 13.25 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 315073 | 1STONECA | Adder | 5.43 MW | 4.61 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 315083 | 1SPRUNCA | 80/20 | 7.36 MW | 7.36 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 315084 | 1SPRUNCB | 80/20 | 7.36 MW | 7.36 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 315092 | 1YORKTN3 | Adder | 109.68 MW | 93.23 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 942341 | AE2-247 C | Adder | 1.2 MW | 1.02 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 943461 | AF1-017 C | Adder | 1.08 MW | 0.92 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 944871 | AF1-152 C | Adder | 4.21 MW | 3.58 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 315098 | 1CHESPKA | 80/20 | 0.3 MW | 0.3 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 315099 | 1CHESPKB | 80/20 | 0.49 MW | 0.49 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 315102 | 1BRUNSWICKG1 | 80/20 | 5.44 MW | 5.44 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 315103 | 1BRUNSWICKG2 | 80/20 | 5.44 MW | 5.44 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 315104 | 1BRUNSWICKG3 | 80/20 | 5.44 MW | 5.44 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 315105 | 1BRUNSWICKS1 | 80/20 | 11.3 MW | 11.3 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 315108 | 1ELIZAR1 | 80/20 | 2.17 MW | 2.17 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 315109 | 1ELIZAR2 | 80/20 | 2.14 MW | 2.14 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 315110 | 1ELIZAR3 | 80/20 | 2.2 MW | 2.2 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 315225 | 1N ANNA1 | 80/20 | 40.28 MW | 40.28 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 315226 | 1N ANNA2 | 80/20 | 40.29 MW | 40.29 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 315241 | 1Z1-086 GT1 | 80/20 | 6.96 MW | 6.96 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 315242 | 1Z1-086 GT2 | 80/20 | 6.96 MW | 6.96 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 315243 | 1Z1-086 GT3 | 80/20 | 6.96 MW | 6.96 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 315244 | 1Z1-086 ST | 80/20 | 12.12 MW | 12.12 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 315260 | 1GOSPORTA | Adder | 1.71 MW | 1.46 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 315261 | 1GOSPORTB | 80/20 | 2.19 MW | 2.19 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 315262 | 1GOSPORTC | Adder | 1.86 MW | 1.58 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 315611 | 6Z1-036WIND | Adder | 5.38 MW | 4.58 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 316108 | AB2-160 C | Adder | 4.36 MW | 3.7 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 962531 | AG1-102 C | Adder | 0.83 MW | 0.7 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 964271 | AG1-288 C | 80/20 | 26.5 MW | 26.5 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 941501 | AE2-147 C | Adder | 12.62 MW | 10.73 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 942001 | AE2-212 C | 80/20 | 1.73 MW | 1.73 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 957831 | AF2-077 C | Adder | 1.62 MW | 1.37 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 957871 | AF2-081 C | Adder | 8.01 MW | 6.81 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 958161 | AF2-110 C | Adder | 1.1 MW | 0.93 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 966331 | AG1-502 C | 80/20 | 9.23 MW | 9.23 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 966341 | AG1-503 C | 80/20 | 2.31 MW | 2.31 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 933291 | AC2-141 C | 80/20 | 24.52 MW | 24.52 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 939411 | AE1-173 C | 80/20 | 72.92 MW | 72.92 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 934011 | AD1-025 C | Adder | 13.35 MW | 11.35 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 315085 | 1SPRUNCC | 80/20 | 0.11 MW | 0.11 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 315086 | 1SPRUNCD | 80/20 | 0.11 MW | 0.11 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 933981 | AD1-022 C | Adder | 6.78 MW | 5.76 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 961681 | AG1-008 C | Adder | 1.5 MW | 1.27 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 316036 | AC1-147 C | 80/20 | 0.25 MW | 0.25 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 316164 | AC1-076_C | 80/20 | 0.69 MW | 0.69 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 316192 | AB2-158 C | 80/20 | 1.56 MW | 1.56 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 316233 | AE1-074 C | 80/20 | 2.08 MW | 2.08 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 316240 | AF1-291 C | Adder | 1.72 MW | 1.46 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 316294 | AC1-161 C | 80/20 | 3.38 MW | 3.38 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 316301 | AE2-228 C | Adder | 1.72 MW | 1.46 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 316304 | AE2-227 C | Adder | 1.69 MW | 1.43 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 316336 | AC2-165 C | Adder | 7.54 MW | 6.41 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 963221 | AG1-171 C | Adder | 1.7 MW | 1.45 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 963231 | AG1-172 C | Adder | 1.7 MW | 1.45 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 963241 | AG1-173 C | Adder | 1.7 MW | 1.45 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 963251 | AG1-174 C | Adder | 1.7 MW | 1.45 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 316044 | AC1-158 C1 | 80/20 | 12.55 MW | 12.55 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 316045 | AC1-158 C2 | 80/20 | 12.55 MW | 12.55 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 316375 | AC2-012 C | 80/20 | 0.92 MW | 0.92 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 316311 | AC2-079 C | Adder | 4.6 MW | 3.91 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 316349 | AD2-085 C | Adder | 2.76 MW | 2.35 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 961611 | AG1-000B C | Adder | 12.63 MW | 10.74 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 941291 | AE2-123 C | Adder | 23.51 MW | 19.99 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 941301 | AE2-124 C | Adder | 21.38 MW | 18.17 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 941591 | AE2-156 C | 80/20 | 14.41 MW | 14.41 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 942371 | AE2-250 C | Adder | 7.74 MW | 6.58 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 942551 | AE2-270 C | Adder | 21.25 MW | 18.07 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 944581 | AF1-123 C | 80/20 | 38.7 MW | 38.7 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 944591 | AF1-124 C | 80/20 | 38.7 MW | 38.7 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 944601 | AF1-125 C | 80/20 | 38.7 MW | 38.7 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 944631 | AF1-128 C | Adder | 30.39 MW | 25.83 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 945361 | AF1-201 C | Adder | 12.26 MW | 10.42 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 946011 | AF1-266 C | Adder | 10.59 MW | 9.0 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 957431 | AF2-037 C | 80/20 | 12.33 MW | 12.33 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 957691 | AF2-063 C | 80/20 | 19.67 MW | 19.67 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 957711 | AF2-065 C | Adder | 10.84 MW | 9.21 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 961711 | AG1-011 C | Adder | 22.67 MW | 19.27 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 962271 | AG1-075 C | Adder | 13.35 MW | 11.35 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 962841 | AG1-133 C | 80/20 | 18.78 MW | 18.78 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 963291 | AG1-178 C | 80/20 | 50.29 MW | 50.29 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 963351 | AG1-184 C | 80/20 | 27.09 MW | 27.09 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 964281 | AG1-289 C | 80/20 | 14.66 MW | 14.66 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 964421 | AG1-305 C | 80/20 | 15.47 MW | 15.47 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 964951 | AG1-359 C | Adder | 18.35 MW | 15.6 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 965001 | AG1-364 C | 80/20 | 5.77 MW | 5.77 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 965281 | AG1-393 C | Adder | 1.72 MW | 1.46 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 965811 | AG1-449 C | 80/20 | 18.3 MW | 18.3 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 966611 | AG1-531 C | Adder | 4.56 MW | 3.88 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 934501 | AD1-074 C | Adder | 26.16 MW | 22.23 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 934511 | AD1-075 C | Adder | 6.54 MW | 5.56 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 935161 | AD1-151 C | Adder | 12.74 MW | 10.83 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 938531 | AE1-072 C | Adder | 14.07 MW | 11.96 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 939191 | AE1-149 C | 80/20 | 8.65 MW | 8.65 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 940431 | AE2-027 C | Adder | 10.29 MW | 8.74 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 940481 | AE2-033 C | Adder | 12.66 MW | 10.76 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 940541 | AE2-040 C | Adder | 2.25 MW | 1.91 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 940641 | AE2-051 C | 80/20 | 13.91 MW | 13.91 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 940651 | AE2-052 C | 80/20 | 2.88 MW | 2.88 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 941101 | AE2-104 C | Adder | 2.68 MW | 2.28 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 941281 | AE2-122 C | Adder | 22.88 MW | 19.45 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 944641 | AF1-129 C | Adder | 81.31 MW | 69.12 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 945811 | AF1-246 C | Adder | 5.68 MW | 4.83 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 316303 | AF2-085 | 80/20 | 3.29 MW | 3.29 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 18.2 MW | 18.2 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 15.53 MW | 15.53 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 69.25 MW | 69.25 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | NY | PJM->LTFIMP_NY | CLTF | 2.06 MW | 2.06 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.82 MW | 0.82 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | WEC | LTFEXP_WEC->PJM | CLTF | 0.4 MW | 0.4 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | CPLE | LTFEXP_CPLE->PJM | CLTF | 8.21 MW | 8.21 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | TVA | LTFEXP_TVA->PJM | CLTF | 4.38 MW | 4.38 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | MEC | LTFEXP_MEC->PJM | CLTF | 2.56 MW | 2.56 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | LAGN | LTFEXP_LAGN->PJM | CLTF | 5.48 MW | 5.48 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.16 MW | 0.16 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 3.91 MW | 3.91 MW |
| Details for 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 961671 | AG1-007 C | Adder | 0.32 MW | 0.27 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 961941 | AG1-037 C | Adder | 0.18 MW | 0.15 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 962331 | AG1-082 C | Adder | 0.73 MW | 0.62 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 962341 | AG1-083 C | Adder | 0.73 MW | 0.62 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963041 | AG1-153 C | Adder | 1.89 MW | 1.61 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963111 | AG1-160 C | Adder | 1.92 MW | 1.63 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963301 | AG1-179 C | Adder | 2.1 MW | 1.79 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 964801 | AG1-343 C | Adder | 2.19 MW | 1.86 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 966801 | AG1-551 C | Adder | 0.72 MW | 0.61 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 966811 | AG1-552 C | Adder | 0.77 MW | 0.66 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965291 | AG1-394 C | Adder | 0.75 MW | 0.64 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965721 | AG1-440 C | Adder | 2.32 MW | 1.97 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965731 | AG1-441 C | Adder | 2.32 MW | 1.97 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 966361 | AG1-505 C | Adder | 5.57 MW | 4.73 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 966371 | AG1-506 C | Adder | 5.57 MW | 4.73 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 966621 | AG1-532 C | 80/20 | 0.58 MW | 0.58 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 313506 | AB1-173 C OP | 80/20 | 0.38 MW | 0.38 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315131 | 1EDGECMA | Adder | 5.36 MW | 4.55 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315136 | 1ROSEMG1 | 80/20 | 0.69 MW | 0.69 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315137 | 1ROSEMS1 | 80/20 | 0.43 MW | 0.43 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315138 | 1ROSEMG2 | 80/20 | 0.32 MW | 0.32 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315139 | 1GASTONA | 80/20 | 1.05 MW | 1.05 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 934521 | AD1-076 C | Adder | 4.19 MW | 3.56 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 942931 | AE2-313 C | Adder | 12.24 MW | 10.41 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 944011 | AF1-069 C | 80/20 | 4.46 MW | 4.46 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 960081 | AF2-299 C | 80/20 | 1.08 MW | 1.08 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 940571 | AE2-044 C | Adder | 1.5 MW | 1.27 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 941031 | AE2-094 C | 80/20 | 13.64 MW | 13.64 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 946281 | AF1-292 C | 80/20 | 0.65 MW | 0.65 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 957481 | AF2-042 C | Adder | 16.8 MW | 14.28 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 957521 | AF2-046 C | Adder | 6.15 MW | 5.22 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 957531 | AF2-047 C | Adder | 5.78 MW | 4.91 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 957861 | AF2-080 C | Adder | 2.62 MW | 2.22 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 938771 | AE1-103 C | Adder | 1.06 MW | 0.9 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 314314 | 3LOCKS | 80/20 | 1.0 MW | 1.0 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 314507 | 3THOMPSN | Adder | 0.65 MW | 0.56 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315065 | 1CHESTF6 | 80/20 | 22.43 MW | 22.43 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315073 | 1STONECA | 80/20 | 4.29 MW | 4.29 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315076 | 1HOPPOLC | 80/20 | 0.81 MW | 0.81 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315077 | 1HOPHCF1 | 80/20 | 1.28 MW | 1.28 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315078 | 1HOPHCF2 | 80/20 | 1.28 MW | 1.28 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315079 | 1HOPHCF3 | 80/20 | 1.28 MW | 1.28 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315080 | 1HOPHCF4 | 80/20 | 1.94 MW | 1.94 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 934781 | AD1-105 C | Adder | -2.76 MW | -2.35 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 942341 | AE2-247 C | 80/20 | 0.65 MW | 0.65 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 943461 | AF1-017 C | 80/20 | 0.59 MW | 0.59 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 944871 | AF1-152 C | Adder | 1.73 MW | 1.47 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315116 | 1SURRY 1 | 80/20 | 8.56 MW | 8.56 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315117 | 1GRAVELC | 80/20 | 0.3 MW | 0.3 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315119 | 1GRAVEL3 | 80/20 | 0.87 MW | 0.87 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315120 | 1GRAVEL4 | 80/20 | 0.88 MW | 0.88 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315121 | 1GRAVEL5 | 80/20 | 0.87 MW | 0.87 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315122 | 1GRAVEL6 | 80/20 | 0.88 MW | 0.88 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315141 | 1GASTONB | 80/20 | 1.05 MW | 1.05 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315260 | 1GOSPORTA | Adder | 0.69 MW | 0.59 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315261 | 1GOSPORTB | Adder | 0.88 MW | 0.75 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315262 | 1GOSPORTC | Adder | 0.75 MW | 0.64 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315611 | 6Z1-036WIND | Adder | 2.25 MW | 1.91 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316108 | AB2-160 C | 80/20 | 3.05 MW | 3.05 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316132 | AB2-190 C | 80/20 | 2.18 MW | 2.18 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 941501 | AE2-147 C | Adder | 5.2 MW | 4.42 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 942001 | AE2-212 C | 80/20 | 2.05 MW | 2.05 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 957871 | AF2-081 C | Adder | 3.19 MW | 2.71 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 958161 | AF2-110 C | Adder | 0.49 MW | 0.42 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 926071 | AC1-086 C | 80/20 | 8.53 MW | 8.53 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 927021 | AC1-189 C | Adder | 2.88 MW | 2.45 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 939411 | AE1-173 C | Adder | 30.11 MW | 25.6 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 934011 | AD1-025 C | 80/20 | 8.54 MW | 8.54 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 933981 | AD1-022 C | Adder | 3.02 MW | 2.57 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 960331 | AF2-324 C | Adder | 2.41 MW | 2.05 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 961681 | AG1-008 C | Adder | 6.16 MW | 5.24 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 962571 | AG1-106 C | 80/20 | 2.37 MW | 2.37 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316011 | AB1-132 C OP | 80/20 | 0.8 MW | 0.8 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316023 | AB2-100 C2 | 80/20 | 0.37 MW | 0.37 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316210 | AC1-098 C | Adder | 2.2 MW | 1.87 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316212 | AC1-099 C | Adder | 0.74 MW | 0.62 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316236 | AE1-162 C | 80/20 | 0.11 MW | 0.11 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316240 | AF1-291 C | 80/20 | 2.38 MW | 2.38 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316263 | AC1-034 C | Adder | 2.28 MW | 1.94 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316274 | AC1-208 C | Adder | 3.25 MW | 2.76 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316301 | AE2-228 C | 80/20 | 2.33 MW | 2.33 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316315 | AB2-025 C | 80/20 | 0.18 MW | 0.18 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316365 | AB2-100 C1 | 80/20 | 0.37 MW | 0.37 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316369 | AC1-216 C | 80/20 | 0.69 MW | 0.69 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963221 | AG1-171 C | 80/20 | 1.09 MW | 1.09 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963231 | AG1-172 C | 80/20 | 1.09 MW | 1.09 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963241 | AG1-173 C | 80/20 | 1.09 MW | 1.09 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963251 | AG1-174 C | 80/20 | 1.09 MW | 1.09 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316181 | AB2-040 GEN | 80/20 | 3.0 MW | 3.0 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316033 | AB2-134 GEN | 80/20 | 0.9 MW | 0.9 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316083 | AB2-161 C | 80/20 | 0.26 MW | 0.26 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316087 | AB2-174 C | 80/20 | 0.4 MW | 0.4 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316311 | AC2-079 C | 80/20 | 2.45 MW | 2.45 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316381 | AD1-082 C | 80/20 | 0.59 MW | 0.59 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316349 | AD2-085 C | 80/20 | 1.5 MW | 1.5 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 961611 | AG1-000B C | 80/20 | 6.94 MW | 6.94 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 941291 | AE2-123 C | Adder | 9.35 MW | 7.95 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 941301 | AE2-124 C | Adder | 8.49 MW | 7.22 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 941591 | AE2-156 C | Adder | 5.78 MW | 4.92 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 942371 | AE2-250 C | 80/20 | 5.41 MW | 5.41 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 942551 | AE2-270 C | 80/20 | 13.59 MW | 13.59 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 944581 | AF1-123 C | Adder | 14.83 MW | 12.6 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 944591 | AF1-124 C | Adder | 14.83 MW | 12.6 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 944601 | AF1-125 C | Adder | 14.83 MW | 12.6 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 946011 | AF1-266 C | 80/20 | 6.99 MW | 6.99 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 957711 | AF2-065 C | 80/20 | 6.93 MW | 6.93 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 961711 | AG1-011 C | 80/20 | 14.51 MW | 14.51 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 962271 | AG1-075 C | 80/20 | 9.34 MW | 9.34 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963291 | AG1-178 C | 80/20 | 21.54 MW | 21.54 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963311 | AG1-180 C | Adder | 1.02 MW | 0.87 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963351 | AG1-184 C | 80/20 | 11.6 MW | 11.6 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 964951 | AG1-359 C | Adder | 7.23 MW | 6.14 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965001 | AG1-364 C | Adder | 2.31 MW | 1.97 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965281 | AG1-393 C | 80/20 | 1.2 MW | 1.2 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965601 | AG1-428 C | Adder | 1.75 MW | 1.49 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965691 | AG1-437 C | Adder | 3.52 MW | 2.99 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965701 | AG1-438 C | Adder | 3.52 MW | 2.99 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965711 | AG1-439 C | Adder | 8.08 MW | 6.87 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965741 | AG1-442 C | Adder | 2.05 MW | 1.75 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965751 | AG1-443 C | Adder | 2.05 MW | 1.75 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965761 | AG1-444 C | Adder | 4.31 MW | 3.66 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965771 | AG1-445 C | Adder | 1.34 MW | 1.14 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965781 | AG1-446 C | Adder | 1.34 MW | 1.14 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965811 | AG1-449 C | Adder | 7.93 MW | 6.74 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 966611 | AG1-531 C | Adder | 1.89 MW | 1.61 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 313764 | 3SOCKMAN | 80/20 | 0.28 MW | 0.28 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 932631 | AC2-084 C | Adder | 2.35 MW | 2.0 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 934321 | AD1-056 C | Adder | 2.32 MW | 1.97 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 934331 | AD1-057 C | Adder | 1.29 MW | 1.1 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 934501 | AD1-074 C | Adder | 11.53 MW | 9.8 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 934511 | AD1-075 C | Adder | 2.88 MW | 2.45 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 935161 | AD1-151 C | 80/20 | 8.56 MW | 8.56 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 938531 | AE1-072 C | Adder | 5.62 MW | 4.77 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 939191 | AE1-149 C | 80/20 | 6.86 MW | 6.86 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 940431 | AE2-027 C | 80/20 | 6.65 MW | 6.65 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 940481 | AE2-033 C | 80/20 | 8.35 MW | 8.35 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 940541 | AE2-040 C | 80/20 | 1.51 MW | 1.51 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 940641 | AE2-051 C | Adder | 5.84 MW | 4.97 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 940651 | AE2-052 C | 80/20 | 2.29 MW | 2.29 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 941101 | AE2-104 C | Adder | 1.2 MW | 1.02 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 941281 | AE2-122 C | Adder | 9.1 MW | 7.73 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 944141 | AF1-082 C | Adder | 0.96 MW | 0.82 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 944641 | AF1-129 C | 80/20 | 117.0 MW | 117.0 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 945811 | AF1-246 C | Adder | 2.35 MW | 2.0 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 9.14 MW | 9.14 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 6.56 MW | 6.56 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 28.68 MW | 28.68 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | NY | PJM->LTFIMP_NY | CLTF | 0.47 MW | 0.47 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.36 MW | 0.36 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | WEC | LTFEXP_WEC->PJM | CLTF | 0.19 MW | 0.19 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | CPLE | LTFEXP_CPLE->PJM | CLTF | 3.5 MW | 3.5 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | TVA | LTFEXP_TVA->PJM | CLTF | 1.78 MW | 1.78 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | MEC | LTFEXP_MEC->PJM | CLTF | 1.15 MW | 1.15 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | LAGN | LTFEXP_LAGN->PJM | CLTF | 2.26 MW | 2.26 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.07 MW | 0.07 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.67 MW | 1.67 MW |
| Details for 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 961671 | AG1-007 C | Adder | 0.32 MW | 0.27 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 961941 | AG1-037 C | Adder | 0.18 MW | 0.15 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 962331 | AG1-082 C | Adder | 0.73 MW | 0.62 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 962341 | AG1-083 C | Adder | 0.73 MW | 0.62 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963041 | AG1-153 C | Adder | 1.89 MW | 1.61 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963111 | AG1-160 C | Adder | 1.92 MW | 1.63 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963301 | AG1-179 C | Adder | 2.1 MW | 1.79 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 964801 | AG1-343 C | Adder | 2.19 MW | 1.86 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 966801 | AG1-551 C | Adder | 0.72 MW | 0.61 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 966811 | AG1-552 C | Adder | 0.77 MW | 0.66 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965291 | AG1-394 C | Adder | 0.75 MW | 0.64 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965721 | AG1-440 C | Adder | 2.32 MW | 1.97 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965731 | AG1-441 C | Adder | 2.32 MW | 1.97 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 966361 | AG1-505 C | Adder | 5.57 MW | 4.73 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 966371 | AG1-506 C | Adder | 5.57 MW | 4.73 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 966621 | AG1-532 C | 80/20 | 0.58 MW | 0.58 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 313506 | AB1-173 C OP | 80/20 | 0.38 MW | 0.38 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315131 | 1EDGECMA | Adder | 5.36 MW | 4.55 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315136 | 1ROSEMG1 | 80/20 | 0.69 MW | 0.69 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315137 | 1ROSEMS1 | 80/20 | 0.43 MW | 0.43 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315138 | 1ROSEMG2 | 80/20 | 0.32 MW | 0.32 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315139 | 1GASTONA | 80/20 | 1.05 MW | 1.05 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 934521 | AD1-076 C | Adder | 4.19 MW | 3.56 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 942931 | AE2-313 C | Adder | 12.24 MW | 10.41 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 944011 | AF1-069 C | 80/20 | 4.46 MW | 4.46 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 960081 | AF2-299 C | 80/20 | 1.08 MW | 1.08 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 940571 | AE2-044 C | Adder | 1.5 MW | 1.27 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 941031 | AE2-094 C | 80/20 | 13.64 MW | 13.64 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 946281 | AF1-292 C | 80/20 | 0.65 MW | 0.65 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 957481 | AF2-042 C | Adder | 16.8 MW | 14.28 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 957521 | AF2-046 C | Adder | 6.15 MW | 5.22 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 957531 | AF2-047 C | Adder | 5.78 MW | 4.91 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 957861 | AF2-080 C | Adder | 2.62 MW | 2.22 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 938771 | AE1-103 C | Adder | 1.06 MW | 0.9 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 314314 | 3LOCKS | 80/20 | 1.0 MW | 1.0 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 314507 | 3THOMPSN | Adder | 0.65 MW | 0.56 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315065 | 1CHESTF6 | 80/20 | 22.43 MW | 22.43 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315073 | 1STONECA | 80/20 | 4.29 MW | 4.29 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315076 | 1HOPPOLC | 80/20 | 0.81 MW | 0.81 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315077 | 1HOPHCF1 | 80/20 | 1.28 MW | 1.28 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315078 | 1HOPHCF2 | 80/20 | 1.28 MW | 1.28 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315079 | 1HOPHCF3 | 80/20 | 1.28 MW | 1.28 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315080 | 1HOPHCF4 | 80/20 | 1.94 MW | 1.94 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 934781 | AD1-105 C | Adder | -2.76 MW | -2.35 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 942341 | AE2-247 C | 80/20 | 0.65 MW | 0.65 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 943461 | AF1-017 C | 80/20 | 0.59 MW | 0.59 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 944871 | AF1-152 C | Adder | 1.73 MW | 1.47 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315116 | 1SURRY 1 | 80/20 | 8.56 MW | 8.56 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315117 | 1GRAVELC | 80/20 | 0.3 MW | 0.3 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315119 | 1GRAVEL3 | 80/20 | 0.87 MW | 0.87 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315120 | 1GRAVEL4 | 80/20 | 0.88 MW | 0.88 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315121 | 1GRAVEL5 | 80/20 | 0.87 MW | 0.87 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315122 | 1GRAVEL6 | 80/20 | 0.88 MW | 0.88 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315141 | 1GASTONB | 80/20 | 1.05 MW | 1.05 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315260 | 1GOSPORTA | Adder | 0.69 MW | 0.59 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315261 | 1GOSPORTB | Adder | 0.88 MW | 0.75 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315262 | 1GOSPORTC | Adder | 0.75 MW | 0.64 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315611 | 6Z1-036WIND | Adder | 2.25 MW | 1.91 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316108 | AB2-160 C | 80/20 | 3.05 MW | 3.05 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316132 | AB2-190 C | 80/20 | 2.18 MW | 2.18 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 941501 | AE2-147 C | Adder | 5.2 MW | 4.42 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 942001 | AE2-212 C | 80/20 | 2.05 MW | 2.05 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 957871 | AF2-081 C | Adder | 3.19 MW | 2.71 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 958161 | AF2-110 C | Adder | 0.49 MW | 0.42 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 926071 | AC1-086 C | 80/20 | 8.53 MW | 8.53 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 927021 | AC1-189 C | Adder | 2.88 MW | 2.45 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 939411 | AE1-173 C | Adder | 30.11 MW | 25.6 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 934011 | AD1-025 C | 80/20 | 8.54 MW | 8.54 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 933981 | AD1-022 C | Adder | 3.02 MW | 2.57 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 960331 | AF2-324 C | Adder | 2.41 MW | 2.05 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 961681 | AG1-008 C | Adder | 6.16 MW | 5.24 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 962571 | AG1-106 C | 80/20 | 2.37 MW | 2.37 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316011 | AB1-132 C OP | 80/20 | 0.8 MW | 0.8 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316023 | AB2-100 C2 | 80/20 | 0.37 MW | 0.37 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316210 | AC1-098 C | Adder | 2.2 MW | 1.87 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316212 | AC1-099 C | Adder | 0.74 MW | 0.62 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316236 | AE1-162 C | 80/20 | 0.11 MW | 0.11 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316240 | AF1-291 C | 80/20 | 2.38 MW | 2.38 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316263 | AC1-034 C | Adder | 2.28 MW | 1.94 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316274 | AC1-208 C | Adder | 3.25 MW | 2.76 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316301 | AE2-228 C | 80/20 | 2.33 MW | 2.33 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316315 | AB2-025 C | 80/20 | 0.18 MW | 0.18 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316365 | AB2-100 C1 | 80/20 | 0.37 MW | 0.37 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316369 | AC1-216 C | 80/20 | 0.69 MW | 0.69 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963221 | AG1-171 C | 80/20 | 1.09 MW | 1.09 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963231 | AG1-172 C | 80/20 | 1.09 MW | 1.09 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963241 | AG1-173 C | 80/20 | 1.09 MW | 1.09 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963251 | AG1-174 C | 80/20 | 1.09 MW | 1.09 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316181 | AB2-040 GEN | 80/20 | 3.0 MW | 3.0 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316033 | AB2-134 GEN | 80/20 | 0.9 MW | 0.9 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316083 | AB2-161 C | 80/20 | 0.26 MW | 0.26 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316087 | AB2-174 C | 80/20 | 0.4 MW | 0.4 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316311 | AC2-079 C | 80/20 | 2.45 MW | 2.45 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316381 | AD1-082 C | 80/20 | 0.59 MW | 0.59 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316349 | AD2-085 C | 80/20 | 1.5 MW | 1.5 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 961611 | AG1-000B C | 80/20 | 6.94 MW | 6.94 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 941291 | AE2-123 C | Adder | 9.35 MW | 7.95 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 941301 | AE2-124 C | Adder | 8.49 MW | 7.22 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 941591 | AE2-156 C | Adder | 5.78 MW | 4.92 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 942371 | AE2-250 C | 80/20 | 5.41 MW | 5.41 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 942551 | AE2-270 C | 80/20 | 13.59 MW | 13.59 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 944581 | AF1-123 C | Adder | 14.83 MW | 12.6 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 944591 | AF1-124 C | Adder | 14.83 MW | 12.6 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 944601 | AF1-125 C | Adder | 14.83 MW | 12.6 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 946011 | AF1-266 C | 80/20 | 6.99 MW | 6.99 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 957711 | AF2-065 C | 80/20 | 6.93 MW | 6.93 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 961711 | AG1-011 C | 80/20 | 14.51 MW | 14.51 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 962271 | AG1-075 C | 80/20 | 9.34 MW | 9.34 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963291 | AG1-178 C | 80/20 | 21.54 MW | 21.54 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963311 | AG1-180 C | Adder | 1.02 MW | 0.87 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963351 | AG1-184 C | 80/20 | 11.6 MW | 11.6 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 964951 | AG1-359 C | Adder | 7.23 MW | 6.14 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965001 | AG1-364 C | Adder | 2.31 MW | 1.97 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965281 | AG1-393 C | 80/20 | 1.2 MW | 1.2 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965601 | AG1-428 C | Adder | 1.75 MW | 1.49 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965691 | AG1-437 C | Adder | 3.52 MW | 2.99 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965701 | AG1-438 C | Adder | 3.52 MW | 2.99 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965711 | AG1-439 C | Adder | 8.08 MW | 6.87 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965741 | AG1-442 C | Adder | 2.05 MW | 1.75 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965751 | AG1-443 C | Adder | 2.05 MW | 1.75 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965761 | AG1-444 C | Adder | 4.31 MW | 3.66 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965771 | AG1-445 C | Adder | 1.34 MW | 1.14 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965781 | AG1-446 C | Adder | 1.34 MW | 1.14 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965811 | AG1-449 C | Adder | 7.93 MW | 6.74 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 966611 | AG1-531 C | Adder | 1.89 MW | 1.61 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 313764 | 3SOCKMAN | 80/20 | 0.28 MW | 0.28 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 932631 | AC2-084 C | Adder | 2.35 MW | 2.0 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 934321 | AD1-056 C | Adder | 2.32 MW | 1.97 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 934331 | AD1-057 C | Adder | 1.29 MW | 1.1 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 934501 | AD1-074 C | Adder | 11.53 MW | 9.8 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 934511 | AD1-075 C | Adder | 2.88 MW | 2.45 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 935161 | AD1-151 C | 80/20 | 8.56 MW | 8.56 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 938531 | AE1-072 C | Adder | 5.62 MW | 4.77 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 939191 | AE1-149 C | 80/20 | 6.86 MW | 6.86 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 940431 | AE2-027 C | 80/20 | 6.65 MW | 6.65 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 940481 | AE2-033 C | 80/20 | 8.35 MW | 8.35 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 940541 | AE2-040 C | 80/20 | 1.51 MW | 1.51 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 940641 | AE2-051 C | Adder | 5.84 MW | 4.97 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 940651 | AE2-052 C | 80/20 | 2.29 MW | 2.29 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 941101 | AE2-104 C | Adder | 1.2 MW | 1.02 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 941281 | AE2-122 C | Adder | 9.1 MW | 7.73 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 944141 | AF1-082 C | Adder | 0.96 MW | 0.82 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 944641 | AF1-129 C | 80/20 | 117.0 MW | 117.0 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 945811 | AF1-246 C | Adder | 2.35 MW | 2.0 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 9.14 MW | 9.14 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 6.56 MW | 6.56 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 28.68 MW | 28.68 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | NY | PJM->LTFIMP_NY | CLTF | 0.47 MW | 0.47 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.36 MW | 0.36 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | WEC | LTFEXP_WEC->PJM | CLTF | 0.19 MW | 0.19 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | CPLE | LTFEXP_CPLE->PJM | CLTF | 3.5 MW | 3.5 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | TVA | LTFEXP_TVA->PJM | CLTF | 1.78 MW | 1.78 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | MEC | LTFEXP_MEC->PJM | CLTF | 1.15 MW | 1.15 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | LAGN | LTFEXP_LAGN->PJM | CLTF | 2.26 MW | 2.26 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.07 MW | 0.07 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.67 MW | 1.67 MW |
| Details for 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 961941 | AG1-037 C | Adder | 0.51 MW | 0.43 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 962331 | AG1-082 C | Adder | 2.03 MW | 1.73 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 962341 | AG1-083 C | Adder | 2.03 MW | 1.73 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 963041 | AG1-153 C | Adder | 5.36 MW | 4.56 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 963111 | AG1-160 C | Adder | 5.42 MW | 4.61 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 964801 | AG1-343 C | Adder | 6.06 MW | 5.15 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 965291 | AG1-394 C | Adder | 2.08 MW | 1.77 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 966361 | AG1-505 C | Adder | 16.01 MW | 13.61 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 966371 | AG1-506 C | Adder | 16.01 MW | 13.61 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 966621 | AG1-532 C | Adder | 1.37 MW | 1.16 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 934521 | AD1-076 C | Adder | 12.56 MW | 10.68 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 942931 | AE2-313 C | Adder | 34.63 MW | 29.44 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 944011 | AF1-069 C | Adder | 12.54 MW | 10.66 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 960081 | AF2-299 C | Adder | 2.53 MW | 2.15 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 941031 | AE2-094 C | Adder | 38.38 MW | 32.62 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 946281 | AF1-292 C | Adder | 1.51 MW | 1.28 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 957481 | AF2-042 C | Adder | 17.5 MW | 14.87 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 957521 | AF2-046 C | Adder | 17.1 MW | 14.53 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 957531 | AF2-047 C | Adder | 17.73 MW | 15.07 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 938771 | AE1-103 C | Adder | 3.07 MW | 2.61 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 314229 | 6MT RD221 | 80/20 | 0.12 MW | 0.12 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 314236 | 6NRTHEST | 80/20 | 0.17 MW | 0.17 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 314250 | 6ROCKVILLE | 80/20 | 2.27 MW | 2.27 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 314314 | 3LOCKS | Adder | 1.98 MW | 1.68 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 314507 | 3THOMPSN | Adder | 2.18 MW | 1.86 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315039 | 1LDYSMT3 | 80/20 | 4.56 MW | 4.56 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315040 | 1LDYSMT4 | 80/20 | 4.57 MW | 4.57 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315041 | 1LDYSMT5 | 80/20 | 4.59 MW | 4.59 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315060 | 1CHESTF5 | Adder | 70.7 MW | 60.09 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315065 | 1CHESTF6 | Adder | 21.77 MW | 18.5 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315067 | 1DARBY 1 | 80/20 | 2.42 MW | 2.42 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315068 | 1DARBY 2 | 80/20 | 2.42 MW | 2.42 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315069 | 1DARBY 3 | 80/20 | 2.43 MW | 2.43 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315070 | 1DARBY 4 | 80/20 | 2.43 MW | 2.43 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315073 | 1STONECA | Adder | 7.66 MW | 6.51 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315083 | 1SPRUNCA | Adder | 10.13 MW | 8.61 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315084 | 1SPRUNCB | Adder | 10.13 MW | 8.61 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315092 | 1YORKTN3 | Adder | 154.89 MW | 131.65 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 934781 | AD1-105 C | Adder | 7.64 MW | 6.49 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 936591 | AD2-074 C | Adder | 5.97 MW | 5.08 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 942341 | AE2-247 C | Adder | 1.61 MW | 1.37 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 943461 | AF1-017 C | Adder | 1.45 MW | 1.24 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 943741 | AF1-042 C | Adder | 3.13 MW | 2.66 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 944871 | AF1-152 C | Adder | 5.62 MW | 4.78 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 960091 | AF2-300 C | 80/20 | 2.5 MW | 2.5 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 961951 | AG1-038 C | Adder | 3.45 MW | 2.94 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 966661 | AG1-536 C | Adder | 5.76 MW | 4.9 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 966871 | AG1-558 C | Adder | 2.67 MW | 2.27 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 966881 | AG1-559 C | 80/20 | 2.77 MW | 2.77 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315225 | 1N ANNA1 | 80/20 | 34.09 MW | 34.09 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315226 | 1N ANNA2 | 80/20 | 34.1 MW | 34.1 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315260 | 1GOSPORTA | Adder | 2.3 MW | 1.96 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315261 | 1GOSPORTB | Adder | 2.94 MW | 2.5 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315262 | 1GOSPORTC | Adder | 2.5 MW | 2.12 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315611 | 6Z1-036WIND | Adder | 7.17 MW | 6.09 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 316075 | AC2-137 C | 80/20 | 0.36 MW | 0.36 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 316108 | AB2-160 C | Adder | 6.01 MW | 5.11 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 957411 | AF2-035 C | 80/20 | 9.99 MW | 9.99 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 957601 | AF2-054 C | Adder | 2.29 MW | 1.95 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 962531 | AG1-102 C | Adder | 1.2 MW | 1.02 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 962851 | AG1-134 C | Adder | 10.32 MW | 8.77 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 962861 | AG1-135 C | Adder | 6.5 MW | 5.53 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 962971 | AG1-146 C | Adder | 3.32 MW | 2.82 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 962981 | AG1-147 C | Adder | 7.74 MW | 6.58 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 963051 | AG1-154 C | 80/20 | 4.14 MW | 4.14 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 963611 | AG1-210 C | Adder | 0.7 MW | 0.6 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 964211 | AG1-282 C | Adder | 2.14 MW | 1.81 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 964271 | AG1-288 C | 80/20 | 25.01 MW | 25.01 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 965441 | AG1-412 C | Adder | 14.28 MW | 12.13 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 941501 | AE2-147 C | Adder | 16.86 MW | 14.33 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 942001 | AE2-212 C | Adder | 2.37 MW | 2.01 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 957831 | AF2-077 C | Adder | 2.33 MW | 1.98 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 957871 | AF2-081 C | Adder | 10.72 MW | 9.11 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 958161 | AF2-110 C | Adder | 1.47 MW | 1.25 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 933291 | AC2-141 C | Adder | 32.94 MW | 28.0 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 939411 | AE1-173 C | Adder | 92.3 MW | 78.45 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 934011 | AD1-025 C | Adder | 18.6 MW | 15.81 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 927041 | AC1-191 C | Adder | 10.71 MW | 9.1 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 933981 | AD1-022 C | Adder | 8.95 MW | 7.61 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 961681 | AG1-008 C | Adder | 17.13 MW | 14.56 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 316004 | AC1-112 C | 80/20 | 0.31 MW | 0.31 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 316169 | AC1-164 GEN | 80/20 | 6.19 MW | 6.19 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 316233 | AE1-074 C | Adder | 2.7 MW | 2.29 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 316240 | AF1-291 C | Adder | 2.39 MW | 2.03 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 316301 | AE2-228 C | Adder | 2.39 MW | 2.03 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 316304 | AE2-227 C | Adder | 2.44 MW | 2.07 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 316312 | AB1-027 C | 80/20 | 0.5 MW | 0.5 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 963221 | AG1-171 C | Adder | 2.37 MW | 2.01 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 963231 | AG1-172 C | Adder | 2.37 MW | 2.01 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 963241 | AG1-173 C | Adder | 2.37 MW | 2.01 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 963251 | AG1-174 C | Adder | 2.37 MW | 2.01 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315037 | 1LDYSMT1 | 80/20 | 4.39 MW | 4.39 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315038 | 1LDYSMT2 | 80/20 | 4.45 MW | 4.45 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315051 | AA1-145 CT1 | 80/20 | 4.77 MW | 4.77 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315052 | AA1-145 CT2 | 80/20 | 4.77 MW | 4.77 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 316201 | AC1-065 C | Adder | 10.94 MW | 9.3 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 316427 | AG1-213 C | 80/20 | 0.83 MW | 0.83 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315043 | 1FOUR RIVERA | 80/20 | 2.99 MW | 2.99 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315044 | 1FOUR RIVERB | 80/20 | 2.99 MW | 2.99 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315045 | 1FOUR RIVERC | 80/20 | 3.66 MW | 3.66 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315046 | 1FOUR RIVERD | 80/20 | 2.95 MW | 2.95 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315047 | 1FOUR RIVERE | 80/20 | 2.95 MW | 2.95 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315048 | 1FOUR RIVERF | 80/20 | 3.6 MW | 3.6 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 316044 | AC1-158 C1 | 80/20 | 6.28 MW | 6.28 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 316045 | AC1-158 C2 | 80/20 | 6.28 MW | 6.28 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 316311 | AC2-079 C | Adder | 6.17 MW | 5.25 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 316349 | AD2-085 C | Adder | 3.71 MW | 3.15 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 961611 | AG1-000B C | Adder | 17.47 MW | 14.85 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 941291 | AE2-123 C | Adder | 31.54 MW | 26.81 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 941301 | AE2-124 C | Adder | 28.68 MW | 24.38 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 941591 | AE2-156 C | Adder | 19.37 MW | 16.46 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 942371 | AE2-250 C | Adder | 10.68 MW | 9.08 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 942551 | AE2-270 C | Adder | 29.62 MW | 25.18 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 944581 | AF1-123 C | Adder | 51.8 MW | 44.03 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 944591 | AF1-124 C | Adder | 51.8 MW | 44.03 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 944601 | AF1-125 C | Adder | 51.8 MW | 44.03 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 944631 | AF1-128 C | Adder | 44.24 MW | 37.6 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 945361 | AF1-201 C | Adder | 17.56 MW | 14.93 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 946011 | AF1-266 C | Adder | 13.65 MW | 11.6 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 957431 | AF2-037 C | Adder | 10.22 MW | 8.69 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 957691 | AF2-063 C | Adder | 16.32 MW | 13.87 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 957711 | AF2-065 C | Adder | 15.11 MW | 12.84 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 958261 | AF2-120 C | Adder | 6.7 MW | 5.69 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 961711 | AG1-011 C | Adder | 31.6 MW | 26.86 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 962271 | AG1-075 C | Adder | 18.44 MW | 15.67 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 962841 | AG1-133 C | 80/20 | 20.87 MW | 20.87 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 963291 | AG1-178 C | Adder | 62.27 MW | 52.93 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 963351 | AG1-184 C | Adder | 33.55 MW | 28.52 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 964281 | AG1-289 C | 80/20 | 13.83 MW | 13.83 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 964421 | AG1-305 C | Adder | 12.84 MW | 10.91 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 964951 | AG1-359 C | Adder | 24.6 MW | 20.91 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 965001 | AG1-364 C | Adder | 7.75 MW | 6.58 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 965281 | AG1-393 C | Adder | 2.37 MW | 2.02 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 965691 | AG1-437 C | Adder | 10.32 MW | 8.77 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 965701 | AG1-438 C | Adder | 10.32 MW | 8.77 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 965741 | AG1-442 C | Adder | 6.02 MW | 5.12 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 965751 | AG1-443 C | Adder | 6.02 MW | 5.12 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 965811 | AG1-449 C | Adder | 22.43 MW | 19.06 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 966611 | AG1-531 C | Adder | 6.36 MW | 5.41 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 934501 | AD1-074 C | Adder | 34.58 MW | 29.39 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 934511 | AD1-075 C | Adder | 8.65 MW | 7.35 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 935161 | AD1-151 C | Adder | 17.81 MW | 15.14 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 938531 | AE1-072 C | Adder | 18.84 MW | 16.01 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 939191 | AE1-149 C | Adder | 11.7 MW | 9.94 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 939261 | AE1-157 C | 80/20 | 16.16 MW | 16.16 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 939601 | AE1-190 C | Adder | 2.31 MW | 1.96 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 940431 | AE2-027 C | Adder | 14.27 MW | 12.13 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 940481 | AE2-033 C | Adder | 16.3 MW | 13.86 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 940541 | AE2-040 C | Adder | 2.9 MW | 2.46 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 940551 | AE2-041 C | Adder | 7.74 MW | 6.58 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 940641 | AE2-051 C | Adder | 17.29 MW | 14.69 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 940651 | AE2-052 C | Adder | 3.9 MW | 3.31 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 941101 | AE2-104 C | Adder | 3.59 MW | 3.06 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 941281 | AE2-122 C | Adder | 30.7 MW | 26.09 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 942191 | AE2-231 C | 80/20 | 5.49 MW | 5.49 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 943471 | AF1-018 C | Adder | 7.74 MW | 6.58 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 944641 | AF1-129 C | Adder | 113.52 MW | 96.49 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 963622 | AG1-213 E | 80/20 | 0.83 MW | 0.83 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 29.77 MW | 29.77 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 22.29 MW | 22.29 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 90.58 MW | 90.58 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | NY | PJM->LTFIMP_NY | CLTF | 2.73 MW | 2.73 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | LGEE | LTFEXP_LGEE->PJM | CLTF | 1.29 MW | 1.29 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | WEC | LTFEXP_WEC->PJM | CLTF | 0.63 MW | 0.63 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | CPLE | LTFEXP_CPLE->PJM | CLTF | 10.58 MW | 10.58 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | TVA | LTFEXP_TVA->PJM | CLTF | 6.11 MW | 6.11 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | MEC | LTFEXP_MEC->PJM | CLTF | 3.89 MW | 3.89 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | LAGN | LTFEXP_LAGN->PJM | CLTF | 7.63 MW | 7.63 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.25 MW | 0.25 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 5.04 MW | 5.04 MW |
| Details for 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 961941 | AG1-037 C | Adder | 0.52 MW | 0.44 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 962331 | AG1-082 C | Adder | 2.07 MW | 1.76 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 962341 | AG1-083 C | Adder | 2.07 MW | 1.76 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 963041 | AG1-153 C | Adder | 5.46 MW | 4.64 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 963111 | AG1-160 C | Adder | 5.52 MW | 4.69 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 964801 | AG1-343 C | Adder | 6.17 MW | 5.25 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 965291 | AG1-394 C | Adder | 2.12 MW | 1.8 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 966361 | AG1-505 C | Adder | 16.29 MW | 13.85 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 966371 | AG1-506 C | Adder | 16.29 MW | 13.85 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 966621 | AG1-532 C | Adder | 1.39 MW | 1.18 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 934521 | AD1-076 C | Adder | 12.8 MW | 10.88 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 942931 | AE2-313 C | Adder | 35.26 MW | 29.97 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 944011 | AF1-069 C | Adder | 12.77 MW | 10.85 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 960081 | AF2-299 C | Adder | 2.58 MW | 2.19 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 941031 | AE2-094 C | Adder | 39.08 MW | 33.21 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 946281 | AF1-292 C | Adder | 1.54 MW | 1.31 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 957481 | AF2-042 C | Adder | 50.99 MW | 43.34 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 957521 | AF2-046 C | Adder | 17.42 MW | 14.8 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 957531 | AF2-047 C | Adder | 18.07 MW | 15.36 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 938771 | AE1-103 C | Adder | 3.13 MW | 2.66 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 314229 | 6MT RD221 | 80/20 | 0.12 MW | 0.12 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 314236 | 6NRTHEST | 80/20 | 0.18 MW | 0.18 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 314250 | 6ROCKVILLE | 80/20 | 2.31 MW | 2.31 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 314314 | 3LOCKS | Adder | 2.02 MW | 1.72 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 314507 | 3THOMPSN | Adder | 2.23 MW | 1.89 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315039 | 1LDYSMT3 | 80/20 | 4.7 MW | 4.7 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315040 | 1LDYSMT4 | 80/20 | 4.71 MW | 4.71 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315041 | 1LDYSMT5 | 80/20 | 4.72 MW | 4.72 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315060 | 1CHESTF5 | Adder | 72.17 MW | 61.34 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315065 | 1CHESTF6 | Adder | 22.2 MW | 18.87 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315067 | 1DARBY 1 | 80/20 | 2.47 MW | 2.47 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315068 | 1DARBY 2 | 80/20 | 2.47 MW | 2.47 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315069 | 1DARBY 3 | 80/20 | 2.48 MW | 2.48 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315070 | 1DARBY 4 | 80/20 | 2.48 MW | 2.48 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315073 | 1STONECA | Adder | 7.81 MW | 6.64 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315083 | 1SPRUNCA | Adder | 10.33 MW | 8.78 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315084 | 1SPRUNCB | Adder | 10.33 MW | 8.78 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315092 | 1YORKTN3 | Adder | 158.08 MW | 134.37 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 934781 | AD1-105 C | Adder | 7.83 MW | 6.66 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 936591 | AD2-074 C | Adder | 6.11 MW | 5.19 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 942341 | AE2-247 C | Adder | 1.64 MW | 1.39 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 943461 | AF1-017 C | Adder | 1.48 MW | 1.26 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 943741 | AF1-042 C | Adder | 3.2 MW | 2.72 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 944871 | AF1-152 C | Adder | 5.73 MW | 4.87 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 960091 | AF2-300 C | 80/20 | 2.56 MW | 2.56 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 961951 | AG1-038 C | Adder | 3.53 MW | 3.0 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 966661 | AG1-536 C | Adder | 5.9 MW | 5.01 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 966871 | AG1-558 C | Adder | 2.73 MW | 2.32 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 966881 | AG1-559 C | 80/20 | 2.84 MW | 2.84 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315225 | 1N ANNA1 | 80/20 | 34.63 MW | 34.63 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315226 | 1N ANNA2 | 80/20 | 34.64 MW | 34.64 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315260 | 1GOSPORTA | Adder | 2.35 MW | 2.0 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315261 | 1GOSPORTB | Adder | 3.0 MW | 2.55 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315262 | 1GOSPORTC | Adder | 2.55 MW | 2.17 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315611 | 6Z1-036WIND | Adder | 7.31 MW | 6.21 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316075 | AC2-137 C | 80/20 | 0.36 MW | 0.36 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316108 | AB2-160 C | Adder | 6.13 MW | 5.21 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 957411 | AF2-035 C | 80/20 | 10.25 MW | 10.25 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 957601 | AF2-054 C | Adder | 2.34 MW | 1.99 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 962531 | AG1-102 C | Adder | 1.22 MW | 1.04 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 962851 | AG1-134 C | Adder | 10.58 MW | 9.0 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 962861 | AG1-135 C | Adder | 6.66 MW | 5.66 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 962971 | AG1-146 C | Adder | 3.39 MW | 2.88 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 962981 | AG1-147 C | Adder | 7.92 MW | 6.73 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 963051 | AG1-154 C | 80/20 | 4.26 MW | 4.26 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 963611 | AG1-210 C | Adder | 0.72 MW | 0.61 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 964211 | AG1-282 C | Adder | 2.19 MW | 1.86 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 965441 | AG1-412 C | Adder | 14.72 MW | 12.51 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 941501 | AE2-147 C | Adder | 17.18 MW | 14.61 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 942001 | AE2-212 C | Adder | 2.42 MW | 2.05 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 957831 | AF2-077 C | Adder | 2.38 MW | 2.02 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 957871 | AF2-081 C | Adder | 10.93 MW | 9.29 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 958161 | AF2-110 C | Adder | 1.5 MW | 1.27 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 926071 | AC1-086 C | Adder | 20.97 MW | 17.82 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 933291 | AC2-141 C | Adder | 33.59 MW | 28.55 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 939411 | AE1-173 C | Adder | 94.04 MW | 79.94 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 934011 | AD1-025 C | Adder | 18.98 MW | 16.13 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 927041 | AC1-191 C | Adder | 10.95 MW | 9.3 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 933981 | AD1-022 C | Adder | 9.13 MW | 7.76 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 961681 | AG1-008 C | Adder | 17.45 MW | 14.83 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 962571 | AG1-106 C | Adder | 5.83 MW | 4.96 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316004 | AC1-112 C | 80/20 | 0.32 MW | 0.32 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316169 | AC1-164 GEN | 80/20 | 6.33 MW | 6.33 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316233 | AE1-074 C | Adder | 2.75 MW | 2.33 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316240 | AF1-291 C | Adder | 2.44 MW | 2.07 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316301 | AE2-228 C | Adder | 2.43 MW | 2.07 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316304 | AE2-227 C | Adder | 2.49 MW | 2.12 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316312 | AB1-027 C | 80/20 | 0.51 MW | 0.51 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 963221 | AG1-171 C | Adder | 2.42 MW | 2.06 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 963231 | AG1-172 C | Adder | 2.42 MW | 2.06 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 963241 | AG1-173 C | Adder | 2.42 MW | 2.06 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 963251 | AG1-174 C | Adder | 2.42 MW | 2.06 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315037 | 1LDYSMT1 | 80/20 | 4.52 MW | 4.52 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315038 | 1LDYSMT2 | 80/20 | 4.58 MW | 4.58 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315051 | AA1-145 CT1 | 80/20 | 4.88 MW | 4.88 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315052 | AA1-145 CT2 | 80/20 | 4.88 MW | 4.88 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316201 | AC1-065 C | Adder | 11.18 MW | 9.5 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316427 | AG1-213 C | 80/20 | 0.85 MW | 0.85 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315043 | 1FOUR RIVERA | 80/20 | 3.06 MW | 3.06 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315044 | 1FOUR RIVERB | 80/20 | 3.06 MW | 3.06 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315045 | 1FOUR RIVERC | 80/20 | 3.74 MW | 3.74 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315046 | 1FOUR RIVERD | 80/20 | 3.02 MW | 3.02 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315047 | 1FOUR RIVERE | 80/20 | 3.02 MW | 3.02 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315048 | 1FOUR RIVERF | 80/20 | 3.69 MW | 3.69 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316181 | AB2-040 GEN | Adder | 7.47 MW | 6.35 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316311 | AC2-079 C | Adder | 6.3 MW | 5.35 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316349 | AD2-085 C | Adder | 3.78 MW | 3.21 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 961611 | AG1-000B C | Adder | 17.82 MW | 15.15 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 941291 | AE2-123 C | Adder | 32.17 MW | 27.34 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 941301 | AE2-124 C | Adder | 29.24 MW | 24.86 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 941591 | AE2-156 C | Adder | 19.75 MW | 16.79 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 942371 | AE2-250 C | Adder | 10.9 MW | 9.26 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 942551 | AE2-270 C | Adder | 30.22 MW | 25.69 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 944581 | AF1-123 C | Adder | 52.82 MW | 44.9 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 944591 | AF1-124 C | Adder | 52.82 MW | 44.9 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 944601 | AF1-125 C | Adder | 52.82 MW | 44.9 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 944631 | AF1-128 C | Adder | 45.16 MW | 38.38 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 945361 | AF1-201 C | Adder | 17.94 MW | 15.24 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 946011 | AF1-266 C | Adder | 13.9 MW | 11.82 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 957691 | AF2-063 C | Adder | 4.58 MW | 3.89 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 957711 | AF2-065 C | Adder | 15.41 MW | 13.1 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 958261 | AF2-120 C | Adder | 6.85 MW | 5.83 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 961711 | AG1-011 C | Adder | 32.24 MW | 27.4 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 962271 | AG1-075 C | Adder | 18.81 MW | 15.99 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 962841 | AG1-133 C | 80/20 | 21.28 MW | 21.28 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 963291 | AG1-178 C | Adder | 63.43 MW | 53.91 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 963351 | AG1-184 C | Adder | 34.17 MW | 29.05 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 964951 | AG1-359 C | Adder | 25.08 MW | 21.32 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 965001 | AG1-364 C | Adder | 7.9 MW | 6.71 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 965281 | AG1-393 C | Adder | 2.42 MW | 2.06 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 965691 | AG1-437 C | Adder | 10.52 MW | 8.94 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 965701 | AG1-438 C | Adder | 10.52 MW | 8.94 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 965741 | AG1-442 C | Adder | 6.13 MW | 5.21 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 965751 | AG1-443 C | Adder | 6.13 MW | 5.21 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 965811 | AG1-449 C | Adder | 22.83 MW | 19.41 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 966611 | AG1-531 C | Adder | 6.49 MW | 5.52 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 313764 | 3SOCKMAN | Adder | 0.71 MW | 0.6 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 934501 | AD1-074 C | Adder | 35.24 MW | 29.96 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 934511 | AD1-075 C | Adder | 8.81 MW | 7.49 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 935161 | AD1-151 C | Adder | 18.17 MW | 15.45 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 938531 | AE1-072 C | Adder | 19.21 MW | 16.33 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 939191 | AE1-149 C | Adder | 11.93 MW | 10.14 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 939261 | AE1-157 C | 80/20 | 16.6 MW | 16.6 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 939601 | AE1-190 C | Adder | 2.36 MW | 2.01 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 940431 | AE2-027 C | Adder | 14.56 MW | 12.38 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 940481 | AE2-033 C | Adder | 16.61 MW | 14.12 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 940541 | AE2-040 C | Adder | 2.95 MW | 2.51 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 940551 | AE2-041 C | Adder | 7.91 MW | 6.72 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 940641 | AE2-051 C | Adder | 17.61 MW | 14.97 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 940651 | AE2-052 C | Adder | 3.98 MW | 3.38 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 941101 | AE2-104 C | Adder | 3.66 MW | 3.11 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 941281 | AE2-122 C | Adder | 31.3 MW | 26.61 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 942191 | AE2-231 C | 80/20 | 5.64 MW | 5.64 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 943471 | AF1-018 C | Adder | 7.91 MW | 6.72 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 944641 | AF1-129 C | Adder | 115.8 MW | 98.43 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 945811 | AF1-246 C | Adder | 7.14 MW | 6.07 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 963622 | AG1-213 E | 80/20 | 0.85 MW | 0.85 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 31.31 MW | 31.31 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 22.98 MW | 22.98 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 92.33 MW | 92.33 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | NY | PJM->LTFIMP_NY | CLTF | 2.68 MW | 2.68 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | LGEE | LTFEXP_LGEE->PJM | CLTF | 1.34 MW | 1.34 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | WEC | LTFEXP_WEC->PJM | CLTF | 0.66 MW | 0.66 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | CPLE | LTFEXP_CPLE->PJM | CLTF | 10.77 MW | 10.77 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | TVA | LTFEXP_TVA->PJM | CLTF | 6.27 MW | 6.27 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | MEC | LTFEXP_MEC->PJM | CLTF | 4.04 MW | 4.04 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | LAGN | LTFEXP_LAGN->PJM | CLTF | 7.83 MW | 7.83 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.26 MW | 0.26 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 5.14 MW | 5.14 MW |
| Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 961671 | AG1-007 C | Adder | 1.06 MW | 0.9 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 961941 | AG1-037 C | Adder | 0.56 MW | 0.47 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 962331 | AG1-082 C | Adder | 2.24 MW | 1.9 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 962341 | AG1-083 C | Adder | 2.24 MW | 1.9 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 963041 | AG1-153 C | 80/20 | 8.28 MW | 8.28 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 963111 | AG1-160 C | 80/20 | 8.42 MW | 8.42 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 963301 | AG1-179 C | Adder | 6.14 MW | 5.22 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 964111 | AG1-272 C | Adder | 2.18 MW | 1.85 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 964121 | AG1-273 C | Adder | 2.18 MW | 1.85 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 964131 | AG1-274 C | Adder | 2.18 MW | 1.85 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 964791 | AG1-342 C | Adder | 4.35 MW | 3.7 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 964801 | AG1-343 C | Adder | 6.56 MW | 5.58 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 966801 | AG1-551 C | Adder | 2.35 MW | 2.0 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 966811 | AG1-552 C | Adder | 2.28 MW | 1.94 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 965191 | AG1-384 C | Adder | 2.18 MW | 1.85 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 965291 | AG1-394 C | Adder | 2.25 MW | 1.91 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 965591 | AG1-427 C | Adder | 11.24 MW | 9.55 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 965721 | AG1-440 C | Adder | 8.08 MW | 6.87 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 965731 | AG1-441 C | Adder | 8.08 MW | 6.87 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 966361 | AG1-505 C | 80/20 | 24.27 MW | 24.27 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 966371 | AG1-506 C | 80/20 | 24.27 MW | 24.27 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 966621 | AG1-532 C | 80/20 | 1.56 MW | 1.56 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 315131 | 1EDGECMA | Adder | 17.47 MW | 14.85 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 315153 | 1CLOVER1 | 80/20 | 13.73 MW | 13.73 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 315154 | 1CLOVER2 | 80/20 | 13.6 MW | 13.6 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 934521 | AD1-076 C | Adder | 13.53 MW | 11.5 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 942931 | AE2-313 C | 80/20 | 53.93 MW | 53.93 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 944011 | AF1-069 C | 80/20 | 19.69 MW | 19.69 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 959311 | AF2-222 C | Adder | 13.84 MW | 11.77 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 960061 | AF2-297 C | Adder | 8.56 MW | 7.28 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 960081 | AF2-299 C | 80/20 | 2.9 MW | 2.9 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 939181 | AE1-148 C | Adder | 9.48 MW | 8.05 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 940571 | AE2-044 C | Adder | 4.89 MW | 4.16 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 941031 | AE2-094 C | 80/20 | 60.25 MW | 60.25 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 941791 | AE2-182 C | Adder | 1.79 MW | 1.52 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 946281 | AF1-292 C | 80/20 | 1.73 MW | 1.73 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 957481 | AF2-042 C | 80/20 | 71.39 MW | 71.39 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 957521 | AF2-046 C | Adder | 18.66 MW | 15.86 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 957531 | AF2-047 C | Adder | 18.84 MW | 16.02 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 957861 | AF2-080 C | Adder | 8.57 MW | 7.29 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 938771 | AE1-103 C | Adder | 3.16 MW | 2.69 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 313526 | AB2-022 C | 80/20 | 0.35 MW | 0.35 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 314295 | 6BIRDNECK | 80/20 | 0.04 MW | 0.04 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 314507 | 3THOMPSN | Adder | 2.17 MW | 1.85 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 315092 | 1YORKTN3 | Adder | 110.42 MW | 93.86 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 942341 | AE2-247 C | Adder | 1.51 MW | 1.28 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 943461 | AF1-017 C | Adder | 1.36 MW | 1.16 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 944871 | AF1-152 C | Adder | 5.77 MW | 4.91 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 315098 | 1CHESPKA | 80/20 | 0.4 MW | 0.4 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 315099 | 1CHESPKB | 80/20 | 0.66 MW | 0.66 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 315102 | 1BRUNSWICKG1 | 80/20 | 10.32 MW | 10.32 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 315103 | 1BRUNSWICKG2 | 80/20 | 10.32 MW | 10.32 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 315104 | 1BRUNSWICKG3 | 80/20 | 10.32 MW | 10.32 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 315105 | 1BRUNSWICKS1 | 80/20 | 21.44 MW | 21.44 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 315108 | 1ELIZAR1 | 80/20 | 2.92 MW | 2.92 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 315109 | 1ELIZAR2 | 80/20 | 2.87 MW | 2.87 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 315110 | 1ELIZAR3 | 80/20 | 2.96 MW | 2.96 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 315241 | 1Z1-086 GT1 | 80/20 | 13.26 MW | 13.26 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 315242 | 1Z1-086 GT2 | 80/20 | 13.27 MW | 13.27 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 315243 | 1Z1-086 GT3 | 80/20 | 13.27 MW | 13.27 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 315244 | 1Z1-086 ST | 80/20 | 23.09 MW | 23.09 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 315260 | 1GOSPORTA | 80/20 | 2.29 MW | 2.29 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 315261 | 1GOSPORTB | 80/20 | 2.93 MW | 2.93 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 315262 | 1GOSPORTC | 80/20 | 2.48 MW | 2.48 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 315611 | 6Z1-036WIND | Adder | 7.46 MW | 6.34 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 941501 | AE2-147 C | Adder | 17.32 MW | 14.72 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 957871 | AF2-081 C | 80/20 | 10.93 MW | 10.93 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 958161 | AF2-110 C | Adder | 1.46 MW | 1.24 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 926071 | AC1-086 C | Adder | 23.64 MW | 20.1 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 927021 | AC1-189 C | Adder | 9.44 MW | 8.02 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 936261 | AD2-033 C | Adder | 11.37 MW | 9.67 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 933291 | AC2-141 C | 80/20 | 34.08 MW | 34.08 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 934621 | AD1-088 C | Adder | 11.0 MW | 9.35 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 939411 | AE1-173 C | 80/20 | 126.48 MW | 126.48 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 933981 | AD1-022 C | Adder | 9.69 MW | 8.24 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 960331 | AF2-324 C | Adder | 7.86 MW | 6.68 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 961681 | AG1-008 C | Adder | 18.69 MW | 15.89 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 962571 | AG1-106 C | Adder | 6.58 MW | 5.59 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 316023 | AB2-100 C2 | 80/20 | 0.93 MW | 0.93 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 316036 | AC1-147 C | 80/20 | 0.34 MW | 0.34 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 316185 | AD1-033 C | 80/20 | 1.14 MW | 1.14 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 316210 | AC1-098 C | Adder | 6.84 MW | 5.82 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 316212 | AC1-099 C | Adder | 2.29 MW | 1.95 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 316222 | AC1-221 C | Adder | 9.06 MW | 7.71 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 316246 | AF1-032 C | 80/20 | 0.26 MW | 0.26 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 316263 | AC1-034 C | Adder | 7.47 MW | 6.35 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 316274 | AC1-208 C | Adder | 10.07 MW | 8.56 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 316294 | AC1-161 C | 80/20 | 4.7 MW | 4.7 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 316305 | AF2-043 C | 80/20 | 0.32 MW | 0.32 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 316315 | AB2-025 C | 80/20 | 0.4 MW | 0.4 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 316316 | AC1-027 C | 80/20 | 0.29 MW | 0.29 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 316320 | Y1-086 C | 80/20 | 0.2 MW | 0.2 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 316321 | Z2-027 C | 80/20 | 0.34 MW | 0.34 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 316365 | AB2-100 C1 | 80/20 | 0.93 MW | 0.93 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 316017 | AA1-139 ULT1 | 80/20 | 1.0 MW | 1.0 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 316018 | AA1-139 ULT2 | 80/20 | 1.0 MW | 1.0 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 316181 | AB2-040 GEN | Adder | 8.37 MW | 7.12 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 316375 | AC2-012 C | 80/20 | 1.24 MW | 1.24 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 316311 | AC2-079 C | Adder | 5.84 MW | 4.96 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 316349 | AD2-085 C | Adder | 3.48 MW | 2.96 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 316388 | AE2-253 GEN | 80/20 | 1.81 MW | 1.81 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 961611 | AG1-000B C | Adder | 12.75 MW | 10.84 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 940661 | AE2-053 C | Adder | 3.51 MW | 2.98 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 941291 | AE2-123 C | 80/20 | 31.77 MW | 31.77 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 941301 | AE2-124 C | 80/20 | 28.92 MW | 28.92 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 941591 | AE2-156 C | 80/20 | 19.29 MW | 19.29 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 944581 | AF1-123 C | 80/20 | 53.38 MW | 53.38 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 944591 | AF1-124 C | 80/20 | 53.38 MW | 53.38 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 944601 | AF1-125 C | 80/20 | 53.38 MW | 53.38 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 946011 | AF1-266 C | 80/20 | 15.8 MW | 15.8 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 962491 | AG1-098 C | Adder | 9.97 MW | 8.47 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 962561 | AG1-105 C | Adder | 9.26 MW | 7.87 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 963291 | AG1-178 C | 80/20 | 93.87 MW | 93.87 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 963311 | AG1-180 C | Adder | 2.98 MW | 2.53 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 963321 | AG1-181 C | Adder | 14.63 MW | 12.44 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 963351 | AG1-184 C | 80/20 | 50.57 MW | 50.57 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 963361 | AG1-185 C | Adder | 7.08 MW | 6.02 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 964241 | AG1-285 C | Adder | 11.72 MW | 9.96 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 964951 | AG1-359 C | 80/20 | 25.0 MW | 25.0 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 965001 | AG1-364 C | 80/20 | 7.71 MW | 7.71 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 965601 | AG1-428 C | Adder | 5.12 MW | 4.35 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 965691 | AG1-437 C | Adder | 11.22 MW | 9.53 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 965701 | AG1-438 C | Adder | 11.22 MW | 9.53 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 965711 | AG1-439 C | Adder | 26.44 MW | 22.47 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 965741 | AG1-442 C | Adder | 6.54 MW | 5.56 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 965751 | AG1-443 C | Adder | 6.54 MW | 5.56 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 965761 | AG1-444 C | Adder | 14.1 MW | 11.98 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 965771 | AG1-445 C | Adder | 4.67 MW | 3.97 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 965781 | AG1-446 C | Adder | 4.67 MW | 3.97 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 965811 | AG1-449 C | 80/20 | 34.92 MW | 34.92 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 966611 | AG1-531 C | Adder | 4.71 MW | 4.0 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 313764 | 3SOCKMAN | Adder | 0.79 MW | 0.67 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 932631 | AC2-084 C | Adder | 7.31 MW | 6.22 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 934321 | AD1-056 C | Adder | 7.05 MW | 5.99 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 934331 | AD1-057 C | Adder | 3.93 MW | 3.34 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 934501 | AD1-074 C | Adder | 37.26 MW | 31.67 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 934511 | AD1-075 C | Adder | 9.31 MW | 7.92 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 934611 | AD1-087 C | 80/20 | 1.35 MW | 1.35 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 935171 | AD1-152 C | 80/20 | 1.38 MW | 1.38 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 936161 | AD2-022 C | Adder | 8.06 MW | 6.85 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 936171 | AD2-023 C | Adder | 4.7 MW | 4.0 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 937481 | AD2-202 C | 80/20 | 0.39 MW | 0.39 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 938531 | AE1-072 C | 80/20 | 19.22 MW | 19.22 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 939191 | AE1-149 C | Adder | 9.3 MW | 7.91 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 940481 | AE2-033 C | 80/20 | 18.88 MW | 18.88 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 940541 | AE2-040 C | 80/20 | 3.36 MW | 3.36 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 940641 | AE2-051 C | 80/20 | 25.71 MW | 25.71 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 940651 | AE2-052 C | Adder | 3.1 MW | 2.63 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 941101 | AE2-104 C | Adder | 3.57 MW | 3.04 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 941281 | AE2-122 C | 80/20 | 30.91 MW | 30.91 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 944141 | AF1-082 C | Adder | 3.14 MW | 2.67 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 945811 | AF1-246 C | 80/20 | 9.99 MW | 9.99 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 41.71 MW | 41.71 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 28.11 MW | 28.11 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 114.72 MW | 114.72 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | NY | PJM->LTFIMP_NY | CLTF | 1.88 MW | 1.88 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | LGEE | LTFEXP_LGEE->PJM | CLTF | 1.65 MW | 1.65 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | WEC | LTFEXP_WEC->PJM | CLTF | 0.86 MW | 0.86 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | CPLE | LTFEXP_CPLE->PJM | CLTF | 13.67 MW | 13.67 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | TVA | LTFEXP_TVA->PJM | CLTF | 7.49 MW | 7.49 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | MEC | LTFEXP_MEC->PJM | CLTF | 5.08 MW | 5.08 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | LAGN | LTFEXP_LAGN->PJM | CLTF | 9.5 MW | 9.5 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.32 MW | 0.32 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 6.52 MW | 6.52 MW |
| Details for 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 961791 | AG1-021 C | Adder | 1.12 MW | 0.95 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 961801 | AG1-022 C | Adder | 1.01 MW | 0.85 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 961891 | AG1-030 C | Adder | 8.17 MW | 6.95 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 963171 | AG1-166 C | Adder | 1.12 MW | 0.95 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 963181 | AG1-167 C | Adder | 1.12 MW | 0.95 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 963191 | AG1-168 C | Adder | 1.12 MW | 0.95 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 963201 | AG1-169 C | Adder | 1.12 MW | 0.95 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 963211 | AG1-170 C | Adder | 1.12 MW | 0.95 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 963301 | AG1-179 C | Adder | 2.65 MW | 2.25 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 964111 | AG1-272 C | Adder | 1.34 MW | 1.14 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 964121 | AG1-273 C | Adder | 1.34 MW | 1.14 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 964131 | AG1-274 C | Adder | 1.34 MW | 1.14 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 965191 | AG1-384 C | Adder | 1.34 MW | 1.14 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 965591 | AG1-427 C | Adder | 5.8 MW | 4.93 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 966621 | AG1-532 C | Adder | 0.63 MW | 0.54 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 313853 | 3PONTONDP | Adder | 0.37 MW | 0.32 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 942931 | AE2-313 C | Adder | 14.3 MW | 12.16 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 944011 | AF1-069 C | Adder | 5.13 MW | 4.36 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 958801 | AF2-171 C | Adder | 8.36 MW | 7.11 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 959311 | AF2-222 C | Adder | 8.76 MW | 7.45 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 960081 | AF2-299 C | Adder | 1.17 MW | 1.0 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 960111 | AF2-302 C | Adder | 1.01 MW | 0.85 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 938371 | AE1-056 C | Adder | 3.7 MW | 3.14 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 941011 | AE2-092 C | Adder | 6.79 MW | 5.77 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 941031 | AE2-094 C | Adder | 15.7 MW | 13.35 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 941791 | AE2-182 C | Adder | 1.04 MW | 0.89 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 946281 | AF1-292 C | Adder | 0.7 MW | 0.59 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 946301 | AF1-294 C | Adder | 2.29 MW | 1.95 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 946591 | AF1-323 C | Adder | 2.76 MW | 2.35 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 958211 | AF2-115 C | Adder | 1.4 MW | 1.19 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 938771 | AE1-103 C | Adder | 1.3 MW | 1.1 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 961061 | AF2-397 C | Adder | 8.32 MW | 7.07 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 314236 | 6NRTHEST | 80/20 | 0.1 MW | 0.1 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 314250 | 6ROCKVILLE | 80/20 | 2.31 MW | 2.31 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 314309 | 6IRON208 | 80/20 | 0.27 MW | 0.27 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 314314 | 3LOCKS | Adder | 1.07 MW | 0.91 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 314507 | 3THOMPSN | Adder | 0.87 MW | 0.74 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 315060 | 1CHESTF5 | Adder | 37.84 MW | 32.16 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 315061 | 1CHESTG7 | 80/20 | 1.95 MW | 1.95 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 315062 | 1CHESTS7 | 80/20 | 0.9 MW | 0.9 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 315063 | 1CHESTG8 | 80/20 | 1.92 MW | 1.92 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 315064 | 1CHESTS8 | 80/20 | 0.99 MW | 0.99 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 315065 | 1CHESTF6 | 80/20 | 12.34 MW | 12.34 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 315067 | 1DARBY 1 | 80/20 | 1.36 MW | 1.36 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 315068 | 1DARBY 2 | 80/20 | 1.36 MW | 1.36 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 315069 | 1DARBY 3 | 80/20 | 1.36 MW | 1.36 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 315070 | 1DARBY 4 | 80/20 | 1.37 MW | 1.37 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 315073 | 1STONECA | Adder | 4.03 MW | 3.43 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 315083 | 1SPRUNCA | 80/20 | 9.34 MW | 9.34 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 315084 | 1SPRUNCB | 80/20 | 9.34 MW | 9.34 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 315092 | 1YORKTN3 | Adder | 60.48 MW | 51.41 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 942341 | AE2-247 C | Adder | 0.7 MW | 0.6 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 943461 | AF1-017 C | Adder | 0.63 MW | 0.54 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 944871 | AF1-152 C | Adder | 2.27 MW | 1.93 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 966871 | AG1-558 C | Adder | 1.25 MW | 1.07 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 315191 | 1BEARGRDN G1 | 80/20 | 3.38 MW | 3.38 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 315192 | 1BEARGRDN G2 | 80/20 | 3.38 MW | 3.38 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 315260 | 1GOSPORTA | Adder | 0.92 MW | 0.78 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 315261 | 1GOSPORTB | Adder | 1.18 MW | 1.0 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 315262 | 1GOSPORTC | Adder | 1.0 MW | 0.85 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 316108 | AB2-160 C | Adder | 3.25 MW | 2.76 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 962531 | AG1-102 C | Adder | 0.47 MW | 0.4 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 941501 | AE2-147 C | Adder | 6.82 MW | 5.79 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 942001 | AE2-212 C | Adder | 1.28 MW | 1.09 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 957831 | AF2-077 C | Adder | 0.91 MW | 0.78 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 957871 | AF2-081 C | Adder | 4.28 MW | 3.64 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 958161 | AF2-110 C | Adder | 0.61 MW | 0.52 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 936261 | AD2-033 C | Adder | 6.66 MW | 5.66 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 934621 | AD1-088 C | Adder | 6.42 MW | 5.46 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 939411 | AE1-173 C | Adder | 36.8 MW | 31.28 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 934011 | AD1-025 C | Adder | 8.95 MW | 7.61 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 315085 | 1SPRUNCC | 80/20 | 0.14 MW | 0.14 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 315086 | 1SPRUNCD | 80/20 | 0.14 MW | 0.14 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 927041 | AC1-191 C | Adder | 5.04 MW | 4.28 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 315193 | 1BEARGRDN S1 | 80/20 | 4.37 MW | 4.37 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 316233 | AE1-074 C | 80/20 | 3.71 MW | 3.71 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 316240 | AF1-291 C | 80/20 | 1.34 MW | 1.34 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 316258 | AE1-075 C | 80/20 | 0.43 MW | 0.43 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 316301 | AE2-228 C | 80/20 | 1.33 MW | 1.33 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 316304 | AE2-227 C | 80/20 | 1.59 MW | 1.59 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 316313 | AB2-026 C | 80/20 | 0.47 MW | 0.47 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 316322 | AB2-045 C | 80/20 | 0.18 MW | 0.18 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 316336 | AC2-165 C | 80/20 | 13.6 MW | 13.6 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 316405 | AF2-144 C | 80/20 | 0.37 MW | 0.37 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 963221 | AG1-171 C | Adder | 1.14 MW | 0.97 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 963231 | AG1-172 C | Adder | 1.14 MW | 0.97 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 963241 | AG1-173 C | Adder | 1.14 MW | 0.97 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 963251 | AG1-174 C | Adder | 1.14 MW | 0.97 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 316201 | AC1-065 C | Adder | 4.41 MW | 3.75 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 316181 | AB2-040 GEN | Adder | 3.36 MW | 2.86 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 316311 | AC2-079 C | Adder | 2.68 MW | 2.27 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 316349 | AD2-085 C | Adder | 1.62 MW | 1.38 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 961611 | AG1-000B C | Adder | 7.92 MW | 6.74 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 941291 | AE2-123 C | Adder | 12.58 MW | 10.69 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 941301 | AE2-124 C | Adder | 11.43 MW | 9.71 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 941591 | AE2-156 C | Adder | 7.75 MW | 6.58 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 942371 | AE2-250 C | Adder | 5.77 MW | 4.9 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 942551 | AE2-270 C | Adder | 14.25 MW | 12.11 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 944581 | AF1-123 C | Adder | 20.36 MW | 17.3 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 944591 | AF1-124 C | Adder | 20.36 MW | 17.3 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 944601 | AF1-125 C | Adder | 20.36 MW | 17.3 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 944631 | AF1-128 C | Adder | 23.68 MW | 20.12 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 945361 | AF1-201 C | Adder | 6.86 MW | 5.83 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 946011 | AF1-266 C | Adder | 6.28 MW | 5.34 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 946291 | AF1-293 C | Adder | 10.62 MW | 9.03 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 957711 | AF2-065 C | Adder | 7.27 MW | 6.18 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 961711 | AG1-011 C | Adder | 15.2 MW | 12.92 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 962271 | AG1-075 C | Adder | 9.96 MW | 8.46 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 962491 | AG1-098 C | Adder | 5.76 MW | 4.89 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 963291 | AG1-178 C | Adder | 25.07 MW | 21.31 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 963311 | AG1-180 C | Adder | 1.29 MW | 1.09 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 963321 | AG1-181 C | Adder | 8.66 MW | 7.36 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 963351 | AG1-184 C | Adder | 13.51 MW | 11.48 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 963361 | AG1-185 C | Adder | 4.19 MW | 3.56 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 964231 | AG1-284 C | 80/20 | 4.58 MW | 4.58 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 964241 | AG1-285 C | Adder | 6.16 MW | 5.23 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 964951 | AG1-359 C | Adder | 9.77 MW | 8.3 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 965001 | AG1-364 C | Adder | 3.1 MW | 2.63 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 965281 | AG1-393 C | Adder | 1.28 MW | 1.09 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 965581 | AG1-426 C | Adder | 1.55 MW | 1.32 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 965601 | AG1-428 C | Adder | 2.21 MW | 1.88 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 965641 | AG1-432 C | Adder | 12.15 MW | 10.33 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 965811 | AG1-449 C | Adder | 9.26 MW | 7.87 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 965831 | AG1-451 C | Adder | 2.03 MW | 1.72 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 966611 | AG1-531 C | Adder | 2.67 MW | 2.27 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 935161 | AD1-151 C | Adder | 8.74 MW | 7.43 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 938531 | AE1-072 C | Adder | 7.52 MW | 6.39 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 938821 | AE1-108 C | Adder | 8.17 MW | 6.95 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 939191 | AE1-149 C | Adder | 5.77 MW | 4.91 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 939601 | AE1-190 C | Adder | 0.92 MW | 0.78 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 940431 | AE2-027 C | Adder | 7.78 MW | 6.61 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 940481 | AE2-033 C | Adder | 7.5 MW | 6.38 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 940541 | AE2-040 C | Adder | 1.34 MW | 1.14 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 940551 | AE2-041 C | Adder | 3.04 MW | 2.58 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 940641 | AE2-051 C | Adder | 6.91 MW | 5.87 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 940651 | AE2-052 C | Adder | 1.92 MW | 1.64 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 941101 | AE2-104 C | Adder | 1.49 MW | 1.26 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 941281 | AE2-122 C | Adder | 12.24 MW | 10.4 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 942461 | AE2-259 C | Adder | 6.08 MW | 5.17 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 943471 | AF1-018 C | Adder | 3.04 MW | 2.58 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 944641 | AF1-129 C | 80/20 | 64.37 MW | 64.37 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | 316303 | AF2-085 | 80/20 | 7.01 MW | 7.01 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 18.1 MW | 18.1 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 11.24 MW | 11.24 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 40.18 MW | 40.18 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | NY | PJM->LTFIMP_NY | CLTF | 0.95 MW | 0.95 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.73 MW | 0.73 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | WEC | LTFEXP_WEC->PJM | CLTF | 0.37 MW | 0.37 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | CPLE | LTFEXP_CPLE->PJM | CLTF | 4.64 MW | 4.64 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | TVA | LTFEXP_TVA->PJM | CLTF | 2.93 MW | 2.93 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | MEC | LTFEXP_MEC->PJM | CLTF | 2.13 MW | 2.13 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | LAGN | LTFEXP_LAGN->PJM | CLTF | 3.67 MW | 3.67 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.14 MW | 0.14 MW |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S-1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.21 MW | 2.21 MW |
| Details for 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 961941 | AG1-037 C | Adder | 0.5 MW | 0.42 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 962331 | AG1-082 C | Adder | 1.99 MW | 1.69 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 962341 | AG1-083 C | Adder | 1.99 MW | 1.69 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 963041 | AG1-153 C | Adder | 5.23 MW | 4.45 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 963111 | AG1-160 C | Adder | 5.29 MW | 4.5 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 964801 | AG1-343 C | Adder | 5.94 MW | 5.04 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 965291 | AG1-394 C | Adder | 2.04 MW | 1.73 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 966361 | AG1-505 C | Adder | 15.61 MW | 13.27 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 966371 | AG1-506 C | Adder | 15.61 MW | 13.27 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 966621 | AG1-532 C | Adder | 1.34 MW | 1.14 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 934521 | AD1-076 C | Adder | 12.31 MW | 10.46 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 942931 | AE2-313 C | Adder | 33.79 MW | 28.72 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 944011 | AF1-069 C | Adder | 12.23 MW | 10.4 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 960081 | AF2-299 C | Adder | 2.48 MW | 2.1 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 941031 | AE2-094 C | Adder | 37.44 MW | 31.82 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 946281 | AF1-292 C | Adder | 1.48 MW | 1.25 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 957481 | AF2-042 C | Adder | 48.91 MW | 41.57 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 957521 | AF2-046 C | Adder | 16.74 MW | 14.23 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 957531 | AF2-047 C | Adder | 17.38 MW | 14.77 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 938771 | AE1-103 C | Adder | 3.01 MW | 2.56 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 314229 | 6MT RD221 | 80/20 | 0.11 MW | 0.11 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 314236 | 6NRTHEST | 80/20 | 0.17 MW | 0.17 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 314250 | 6ROCKVILLE | 80/20 | 2.23 MW | 2.23 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 314314 | 3LOCKS | Adder | 1.94 MW | 1.65 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 314507 | 3THOMPSN | Adder | 2.14 MW | 1.82 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315039 | 1LDYSMT3 | 80/20 | 4.58 MW | 4.58 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315040 | 1LDYSMT4 | 80/20 | 4.59 MW | 4.59 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315041 | 1LDYSMT5 | 80/20 | 4.61 MW | 4.61 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315060 | 1CHESTF5 | Adder | 69.73 MW | 59.27 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315065 | 1CHESTF6 | Adder | 21.42 MW | 18.2 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315067 | 1DARBY 1 | 80/20 | 2.39 MW | 2.39 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315068 | 1DARBY 2 | 80/20 | 2.39 MW | 2.39 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315069 | 1DARBY 3 | 80/20 | 2.4 MW | 2.4 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315070 | 1DARBY 4 | 80/20 | 2.4 MW | 2.4 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315073 | 1STONECA | Adder | 7.54 MW | 6.41 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315083 | 1SPRUNCA | Adder | 9.96 MW | 8.46 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315084 | 1SPRUNCB | Adder | 9.96 MW | 8.46 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315092 | 1YORKTN3 | Adder | 152.52 MW | 129.65 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 934781 | AD1-105 C | Adder | 7.59 MW | 6.45 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 936591 | AD2-074 C | Adder | 5.91 MW | 5.02 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 942341 | AE2-247 C | Adder | 1.58 MW | 1.34 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 943461 | AF1-017 C | Adder | 1.43 MW | 1.21 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 943741 | AF1-042 C | Adder | 3.09 MW | 2.63 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 944871 | AF1-152 C | Adder | 5.51 MW | 4.68 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 960091 | AF2-300 C | 80/20 | 2.5 MW | 2.5 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 961951 | AG1-038 C | Adder | 3.42 MW | 2.9 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 966661 | AG1-536 C | Adder | 5.7 MW | 4.85 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 966871 | AG1-558 C | Adder | 2.64 MW | 2.25 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 966881 | AG1-559 C | 80/20 | 2.77 MW | 2.77 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315225 | 1N ANNA1 | 80/20 | 32.38 MW | 32.38 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315226 | 1N ANNA2 | 80/20 | 32.38 MW | 32.38 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315260 | 1GOSPORTA | Adder | 2.26 MW | 1.92 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315261 | 1GOSPORTB | Adder | 2.89 MW | 2.46 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315262 | 1GOSPORTC | Adder | 2.45 MW | 2.08 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315611 | 6Z1-036WIND | Adder | 7.03 MW | 5.98 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 316075 | AC2-137 C | 80/20 | 0.35 MW | 0.35 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 316108 | AB2-160 C | Adder | 5.91 MW | 5.03 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 957411 | AF2-035 C | 80/20 | 9.99 MW | 9.99 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 957601 | AF2-054 C | Adder | 2.26 MW | 1.92 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 962531 | AG1-102 C | Adder | 1.18 MW | 1.0 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 962851 | AG1-134 C | Adder | 10.26 MW | 8.72 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 962861 | AG1-135 C | Adder | 6.44 MW | 5.47 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 962971 | AG1-146 C | Adder | 3.28 MW | 2.79 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 962981 | AG1-147 C | Adder | 7.66 MW | 6.51 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 963051 | AG1-154 C | 80/20 | 4.16 MW | 4.16 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 963611 | AG1-210 C | Adder | 0.69 MW | 0.59 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 964211 | AG1-282 C | Adder | 2.11 MW | 1.8 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 965441 | AG1-412 C | Adder | 14.36 MW | 12.21 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 941501 | AE2-147 C | Adder | 16.54 MW | 14.06 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 942001 | AE2-212 C | Adder | 2.33 MW | 1.98 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 957831 | AF2-077 C | Adder | 2.3 MW | 1.96 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 957871 | AF2-081 C | Adder | 10.52 MW | 8.95 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 958161 | AF2-110 C | Adder | 1.44 MW | 1.22 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 926071 | AC1-086 C | Adder | 18.29 MW | 15.55 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 933291 | AC2-141 C | Adder | 32.33 MW | 27.48 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 939411 | AE1-173 C | Adder | 90.26 MW | 76.72 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 934011 | AD1-025 C | Adder | 18.3 MW | 15.56 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 927041 | AC1-191 C | Adder | 10.6 MW | 9.01 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 933981 | AD1-022 C | Adder | 8.78 MW | 7.46 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 961681 | AG1-008 C | Adder | 16.78 MW | 14.26 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 316004 | AC1-112 C | 80/20 | 0.31 MW | 0.31 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 316169 | AC1-164 GEN | 80/20 | 6.12 MW | 6.12 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 316233 | AE1-074 C | Adder | 2.64 MW | 2.25 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 316240 | AF1-291 C | Adder | 2.35 MW | 2.0 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 316301 | AE2-228 C | Adder | 2.35 MW | 2.0 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 316304 | AE2-227 C | Adder | 2.4 MW | 2.04 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 316312 | AB1-027 C | 80/20 | 0.49 MW | 0.49 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 963221 | AG1-171 C | Adder | 2.33 MW | 1.98 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 963231 | AG1-172 C | Adder | 2.33 MW | 1.98 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 963241 | AG1-173 C | Adder | 2.33 MW | 1.98 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 963251 | AG1-174 C | Adder | 2.33 MW | 1.98 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315037 | 1LDYSMT1 | 80/20 | 4.41 MW | 4.41 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315038 | 1LDYSMT2 | 80/20 | 4.47 MW | 4.47 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315051 | AA1-145 CT1 | 80/20 | 4.74 MW | 4.74 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315052 | AA1-145 CT2 | 80/20 | 4.74 MW | 4.74 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 316201 | AC1-065 C | Adder | 10.81 MW | 9.19 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 316427 | AG1-213 C | 80/20 | 0.83 MW | 0.83 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315043 | 1FOUR RIVERA | 80/20 | 2.98 MW | 2.98 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315044 | 1FOUR RIVERB | 80/20 | 2.98 MW | 2.98 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315045 | 1FOUR RIVERC | 80/20 | 3.63 MW | 3.63 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315046 | 1FOUR RIVERD | 80/20 | 2.93 MW | 2.93 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315047 | 1FOUR RIVERE | 80/20 | 2.93 MW | 2.93 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315048 | 1FOUR RIVERF | 80/20 | 3.58 MW | 3.58 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 316181 | AB2-040 GEN | Adder | 7.17 MW | 6.1 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 316044 | AC1-158 C1 | 80/20 | 5.61 MW | 5.61 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 316045 | AC1-158 C2 | 80/20 | 5.61 MW | 5.61 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 316311 | AC2-079 C | Adder | 6.06 MW | 5.15 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 316349 | AD2-085 C | Adder | 3.64 MW | 3.09 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 961611 | AG1-000B C | Adder | 17.18 MW | 14.61 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 941291 | AE2-123 C | Adder | 30.96 MW | 26.32 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 941301 | AE2-124 C | Adder | 28.15 MW | 23.93 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 941591 | AE2-156 C | Adder | 19.01 MW | 16.16 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 942371 | AE2-250 C | Adder | 10.5 MW | 8.93 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 942551 | AE2-270 C | Adder | 29.14 MW | 24.77 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 944581 | AF1-123 C | Adder | 50.84 MW | 43.21 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 944591 | AF1-124 C | Adder | 50.84 MW | 43.21 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 944601 | AF1-125 C | Adder | 50.84 MW | 43.21 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 944631 | AF1-128 C | Adder | 43.63 MW | 37.09 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 945361 | AF1-201 C | Adder | 17.31 MW | 14.72 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 946011 | AF1-266 C | Adder | 13.35 MW | 11.35 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 957711 | AF2-065 C | Adder | 14.86 MW | 12.63 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 958261 | AF2-120 C | Adder | 6.63 MW | 5.63 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 961711 | AG1-011 C | Adder | 31.09 MW | 26.42 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 962271 | AG1-075 C | Adder | 18.13 MW | 15.41 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 962841 | AG1-133 C | 80/20 | 20.28 MW | 20.28 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 963291 | AG1-178 C | Adder | 60.81 MW | 51.69 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 963351 | AG1-184 C | Adder | 32.76 MW | 27.85 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 964951 | AG1-359 C | Adder | 24.14 MW | 20.52 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 965001 | AG1-364 C | Adder | 7.6 MW | 6.46 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 965281 | AG1-393 C | Adder | 2.33 MW | 1.98 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 965691 | AG1-437 C | Adder | 10.11 MW | 8.6 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 965701 | AG1-438 C | Adder | 10.11 MW | 8.6 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 965741 | AG1-442 C | Adder | 5.9 MW | 5.01 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 965751 | AG1-443 C | Adder | 5.9 MW | 5.01 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 965811 | AG1-449 C | Adder | 21.88 MW | 18.6 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 966611 | AG1-531 C | Adder | 6.26 MW | 5.32 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 934501 | AD1-074 C | Adder | 33.89 MW | 28.81 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 934511 | AD1-075 C | Adder | 8.47 MW | 7.2 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 935161 | AD1-151 C | Adder | 17.53 MW | 14.9 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 938531 | AE1-072 C | Adder | 18.49 MW | 15.71 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 939191 | AE1-149 C | Adder | 11.49 MW | 9.76 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 939261 | AE1-157 C | 80/20 | 16.19 MW | 16.19 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 939601 | AE1-190 C | Adder | 2.28 MW | 1.94 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 940431 | AE2-027 C | Adder | 14.04 MW | 11.93 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 940481 | AE2-033 C | Adder | 15.95 MW | 13.56 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 940541 | AE2-040 C | Adder | 2.84 MW | 2.41 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 940551 | AE2-041 C | Adder | 7.65 MW | 6.5 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 940641 | AE2-051 C | Adder | 16.89 MW | 14.35 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 940651 | AE2-052 C | Adder | 3.83 MW | 3.25 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 941101 | AE2-104 C | Adder | 3.53 MW | 3.0 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 941281 | AE2-122 C | Adder | 30.13 MW | 25.61 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 942191 | AE2-231 C | 80/20 | 5.49 MW | 5.49 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 943471 | AF1-018 C | Adder | 7.65 MW | 6.5 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 944641 | AF1-129 C | Adder | 111.69 MW | 94.94 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 945811 | AF1-246 C | Adder | 6.85 MW | 5.82 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 963622 | AG1-213 E | 80/20 | 0.83 MW | 0.83 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 29.09 MW | 29.09 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 21.76 MW | 21.76 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 88.42 MW | 88.42 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | NY | PJM->LTFIMP_NY | CLTF | 2.65 MW | 2.65 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | LGEE | LTFEXP_LGEE->PJM | CLTF | 1.26 MW | 1.26 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | WEC | LTFEXP_WEC->PJM | CLTF | 0.62 MW | 0.62 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | CPLE | LTFEXP_CPLE->PJM | CLTF | 10.33 MW | 10.33 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | TVA | LTFEXP_TVA->PJM | CLTF | 5.96 MW | 5.96 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | MEC | LTFEXP_MEC->PJM | CLTF | 3.8 MW | 3.8 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | LAGN | LTFEXP_LAGN->PJM | CLTF | 7.45 MW | 7.45 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.24 MW | 0.24 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 4.92 MW | 4.92 MW |
| Details for 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 961671 | AG1-007 C | Adder | 0.74 MW | 0.63 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 961791 | AG1-021 C | Adder | 1.22 MW | 1.04 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 961891 | AG1-030 C | Adder | 9.59 MW | 8.15 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 961941 | AG1-037 C | Adder | 0.36 MW | 0.3 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 962331 | AG1-082 C | Adder | 1.44 MW | 1.22 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 962341 | AG1-083 C | Adder | 1.44 MW | 1.22 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963041 | AG1-153 C | 80/20 | 6.64 MW | 6.64 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963111 | AG1-160 C | 80/20 | 6.75 MW | 6.75 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963171 | AG1-166 C | Adder | 1.22 MW | 1.04 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963181 | AG1-167 C | Adder | 1.22 MW | 1.04 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963191 | AG1-168 C | Adder | 1.22 MW | 1.04 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963201 | AG1-169 C | Adder | 1.22 MW | 1.04 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963211 | AG1-170 C | Adder | 1.22 MW | 1.04 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963301 | AG1-179 C | Adder | 4.54 MW | 3.86 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 964111 | AG1-272 C | Adder | 1.77 MW | 1.51 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 964121 | AG1-273 C | Adder | 1.77 MW | 1.51 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 964131 | AG1-274 C | Adder | 1.77 MW | 1.51 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 964791 | AG1-342 C | Adder | 3.44 MW | 2.92 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 964801 | AG1-343 C | Adder | 4.09 MW | 3.48 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 966801 | AG1-551 C | Adder | 1.59 MW | 1.35 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 966811 | AG1-552 C | Adder | 1.58 MW | 1.35 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965191 | AG1-384 C | Adder | 1.77 MW | 1.51 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965291 | AG1-394 C | Adder | 1.4 MW | 1.19 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965591 | AG1-427 C | Adder | 8.94 MW | 7.6 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965721 | AG1-440 C | Adder | 6.14 MW | 5.22 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965731 | AG1-441 C | Adder | 6.14 MW | 5.22 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 966361 | AG1-505 C | 80/20 | 19.48 MW | 19.48 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 966371 | AG1-506 C | 80/20 | 19.48 MW | 19.48 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 966621 | AG1-532 C | Adder | 1.12 MW | 0.95 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 313853 | 3PONTONDP | Adder | 0.41 MW | 0.35 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315131 | 1EDGECMA | Adder | 12.47 MW | 10.6 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315153 | 1CLOVER1 | 80/20 | 11.01 MW | 11.01 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315154 | 1CLOVER2 | 80/20 | 10.91 MW | 10.91 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 934521 | AD1-076 C | Adder | 8.84 MW | 7.51 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 942931 | AE2-313 C | 80/20 | 43.33 MW | 43.33 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 944011 | AF1-069 C | 80/20 | 15.81 MW | 15.81 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 958801 | AF2-171 C | Adder | 9.2 MW | 7.82 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 959311 | AF2-222 C | Adder | 11.31 MW | 9.61 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 960061 | AF2-297 C | Adder | 6.77 MW | 5.75 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 960081 | AF2-299 C | Adder | 2.06 MW | 1.75 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 939181 | AE1-148 C | Adder | 7.36 MW | 6.26 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 940571 | AE2-044 C | Adder | 3.49 MW | 2.97 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 941031 | AE2-094 C | 80/20 | 48.4 MW | 48.4 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 941791 | AE2-182 C | Adder | 1.49 MW | 1.27 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 946281 | AF1-292 C | Adder | 1.23 MW | 1.05 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 946301 | AF1-294 C | Adder | 2.51 MW | 2.13 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 957481 | AF2-042 C | 80/20 | 57.29 MW | 57.29 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 957521 | AF2-046 C | Adder | 11.8 MW | 10.03 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 957531 | AF2-047 C | Adder | 12.37 MW | 10.52 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 957861 | AF2-080 C | Adder | 5.93 MW | 5.04 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 958211 | AF2-115 C | Adder | 1.53 MW | 1.3 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 938771 | AE1-103 C | Adder | 1.76 MW | 1.5 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 314295 | 6BIRDNECK | 80/20 | 0.03 MW | 0.03 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 314507 | 3THOMPSN | Adder | 1.8 MW | 1.53 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 936591 | AD2-074 C | Adder | -3.56 MW | -3.02 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 943741 | AF1-042 C | Adder | -1.86 MW | -1.58 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 944871 | AF1-152 C | Adder | 3.71 MW | 3.16 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315098 | 1CHESPKA | 80/20 | 0.33 MW | 0.33 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315099 | 1CHESPKB | 80/20 | 0.55 MW | 0.55 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315102 | 1BRUNSWICKG1 | 80/20 | 8.27 MW | 8.27 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315103 | 1BRUNSWICKG2 | 80/20 | 8.27 MW | 8.27 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315104 | 1BRUNSWICKG3 | 80/20 | 8.27 MW | 8.27 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315105 | 1BRUNSWICKS1 | 80/20 | 17.19 MW | 17.19 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315108 | 1ELIZAR1 | 80/20 | 2.48 MW | 2.48 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315109 | 1ELIZAR2 | 80/20 | 2.44 MW | 2.44 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315110 | 1ELIZAR3 | 80/20 | 2.52 MW | 2.52 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315241 | 1Z1-086 GT1 | 80/20 | 10.64 MW | 10.64 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315242 | 1Z1-086 GT2 | 80/20 | 10.64 MW | 10.64 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315243 | 1Z1-086 GT3 | 80/20 | 10.64 MW | 10.64 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315244 | 1Z1-086 ST | 80/20 | 18.52 MW | 18.52 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315260 | 1GOSPORTA | 80/20 | 1.91 MW | 1.91 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315261 | 1GOSPORTB | 80/20 | 2.43 MW | 2.43 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315262 | 1GOSPORTC | 80/20 | 2.06 MW | 2.06 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315611 | 6Z1-036WIND | Adder | 4.93 MW | 4.19 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 941501 | AE2-147 C | Adder | 11.14 MW | 9.47 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 957871 | AF2-081 C | Adder | 8.85 MW | 7.52 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 926071 | AC1-086 C | Adder | 16.4 MW | 13.94 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 927021 | AC1-189 C | Adder | 6.53 MW | 5.55 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 936261 | AD2-033 C | Adder | 9.19 MW | 7.81 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 933291 | AC2-141 C | 80/20 | 86.98 MW | 86.98 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 934621 | AD1-088 C | Adder | 9.19 MW | 7.81 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 939411 | AE1-173 C | 80/20 | 87.2 MW | 87.2 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 933981 | AD1-022 C | Adder | 6.29 MW | 5.35 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 960331 | AF2-324 C | Adder | 5.61 MW | 4.77 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 961681 | AG1-008 C | Adder | 11.82 MW | 10.05 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 962571 | AG1-106 C | Adder | 4.56 MW | 3.88 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316036 | AC1-147 C | 80/20 | 0.28 MW | 0.28 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316185 | AD1-033 C | 80/20 | 0.96 MW | 0.96 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316210 | AC1-098 C | Adder | 4.69 MW | 3.99 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316212 | AC1-099 C | Adder | 1.57 MW | 1.34 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316222 | AC1-221 C | Adder | 7.11 MW | 6.05 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316263 | AC1-034 C | Adder | 5.33 MW | 4.53 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316274 | AC1-208 C | Adder | 6.99 MW | 5.94 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316294 | AC1-161 C | 80/20 | 12.0 MW | 12.0 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316316 | AC1-027 C | 80/20 | 0.24 MW | 0.24 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316181 | AB2-040 GEN | Adder | 5.89 MW | 5.01 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316375 | AC2-012 C | 80/20 | 1.03 MW | 1.03 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316388 | AE2-253 GEN | 80/20 | 1.49 MW | 1.49 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 940661 | AE2-053 C | Adder | 2.73 MW | 2.32 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 941291 | AE2-123 C | 80/20 | 26.51 MW | 26.51 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 941301 | AE2-124 C | 80/20 | 24.13 MW | 24.13 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 941591 | AE2-156 C | 80/20 | 16.25 MW | 16.25 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 944581 | AF1-123 C | 80/20 | 50.14 MW | 50.14 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 944591 | AF1-124 C | 80/20 | 50.14 MW | 50.14 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 944601 | AF1-125 C | 80/20 | 50.14 MW | 50.14 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 946011 | AF1-266 C | Adder | 11.29 MW | 9.6 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 962491 | AG1-098 C | Adder | 8.32 MW | 7.07 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 962561 | AG1-105 C | Adder | 7.32 MW | 6.22 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963291 | AG1-178 C | 80/20 | 71.78 MW | 71.78 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963311 | AG1-180 C | Adder | 2.2 MW | 1.87 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963321 | AG1-181 C | Adder | 11.84 MW | 10.07 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963351 | AG1-184 C | 80/20 | 38.67 MW | 38.67 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963361 | AG1-185 C | Adder | 5.73 MW | 4.87 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 964241 | AG1-285 C | Adder | 9.34 MW | 7.94 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 964951 | AG1-359 C | 80/20 | 21.32 MW | 21.32 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965001 | AG1-364 C | 80/20 | 6.49 MW | 6.49 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965601 | AG1-428 C | Adder | 3.78 MW | 3.22 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965691 | AG1-437 C | Adder | 7.24 MW | 6.16 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965701 | AG1-438 C | Adder | 7.24 MW | 6.16 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965711 | AG1-439 C | Adder | 18.42 MW | 15.66 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965741 | AG1-442 C | Adder | 4.23 MW | 3.59 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965751 | AG1-443 C | Adder | 4.23 MW | 3.59 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965761 | AG1-444 C | Adder | 9.82 MW | 8.35 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965771 | AG1-445 C | Adder | 3.55 MW | 3.02 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965781 | AG1-446 C | Adder | 3.55 MW | 3.02 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965811 | AG1-449 C | 80/20 | 28.06 MW | 28.06 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 313764 | 3SOCKMAN | Adder | 0.55 MW | 0.47 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 932631 | AC2-084 C | Adder | 5.02 MW | 4.26 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 934321 | AD1-056 C | Adder | 4.97 MW | 4.23 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 934331 | AD1-057 C | Adder | 2.77 MW | 2.36 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 934501 | AD1-074 C | Adder | 24.34 MW | 20.69 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 934511 | AD1-075 C | Adder | 6.09 MW | 5.17 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 934611 | AD1-087 C | 80/20 | 1.08 MW | 1.08 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 935171 | AD1-152 C | 80/20 | 1.1 MW | 1.1 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 936161 | AD2-022 C | Adder | 6.16 MW | 5.24 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 936171 | AD2-023 C | Adder | 3.59 MW | 3.06 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 937481 | AD2-202 C | 80/20 | 0.31 MW | 0.31 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 938531 | AE1-072 C | Adder | 15.31 MW | 13.01 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 939601 | AE1-190 C | Adder | -1.34 MW | -1.14 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 940481 | AE2-033 C | Adder | 13.48 MW | 11.46 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 940541 | AE2-040 C | Adder | 2.4 MW | 2.04 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 940641 | AE2-051 C | 80/20 | 26.57 MW | 26.57 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 941281 | AE2-122 C | 80/20 | 25.79 MW | 25.79 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 944141 | AF1-082 C | Adder | 2.24 MW | 1.91 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 945811 | AF1-246 C | 80/20 | 8.02 MW | 8.02 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 32.67 MW | 32.67 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 21.51 MW | 21.51 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 87.22 MW | 87.22 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | NY | PJM->LTFIMP_NY | CLTF | 1.13 MW | 1.13 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | LGEE | LTFEXP_LGEE->PJM | CLTF | 1.27 MW | 1.27 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | WEC | LTFEXP_WEC->PJM | CLTF | 0.67 MW | 0.67 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | CPLE | LTFEXP_CPLE->PJM | CLTF | 10.38 MW | 10.38 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | TVA | LTFEXP_TVA->PJM | CLTF | 5.7 MW | 5.7 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | MEC | LTFEXP_MEC->PJM | CLTF | 3.93 MW | 3.93 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | LAGN | LTFEXP_LAGN->PJM | CLTF | 7.24 MW | 7.24 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.24 MW | 0.24 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 4.95 MW | 4.95 MW |
| Details for 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 314229 | 6MT RD221 | 50/50 | 0.18 MW | 0.18 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 314236 | 6NRTHEST | 50/50 | 0.24 MW | 0.24 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 314250 | 6ROCKVILLE | 50/50 | 2.97 MW | 2.97 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 314314 | 3LOCKS | Adder | 2.15 MW | 1.83 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 314331 | 6POE | Adder | 1.45 MW | 1.24 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 314507 | 3THOMPSN | Adder | 1.91 MW | 1.63 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 314525 | 6KINGFORK | Adder | 0.98 MW | 0.83 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 315060 | 1CHESTF5 | Adder | 81.16 MW | 68.98 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 315065 | 1CHESTF6 | Adder | 24.88 MW | 21.14 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 315067 | 1DARBY 1 | 50/50 | 3.17 MW | 3.17 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 315068 | 1DARBY 2 | 50/50 | 3.17 MW | 3.17 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 315069 | 1DARBY 3 | 50/50 | 3.18 MW | 3.18 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 315070 | 1DARBY 4 | 50/50 | 3.19 MW | 3.19 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 315073 | 1STONECA | Adder | 8.44 MW | 7.17 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 315083 | 1SPRUNCA | Adder | 11.7 MW | 9.95 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 315084 | 1SPRUNCB | Adder | 11.7 MW | 9.95 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 315092 | 1YORKTN3 | Adder | 147.87 MW | 125.69 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 925865 | AC1-065 E | Adder | 18.95 MW | 16.11 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 926412 | AC1-112 E | 50/50 | 1.74 MW | 1.74 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 926662 | AC1-147 E | Adder | 1.26 MW | 1.07 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 927226 | AC1-216 E | Adder | 8.77 MW | 7.46 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 934392 | AD1-063 E | Adder | 1.22 MW | 1.04 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 934781 | AD1-105 C | Adder | 10.8 MW | 9.18 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 934782 | AD1-105 E | Adder | 7.2 MW | 6.12 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 935112 | AD1-144 E | Adder | 0.91 MW | 0.77 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 936591 | AD2-074 C | Adder | 6.08 MW | 5.17 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 936592 | AD2-074 E | Adder | 9.93 MW | 8.44 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 942152 | AE2-227 E | Adder | 1.96 MW | 1.67 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 942162 | AE2-228 E | Adder | 1.78 MW | 1.52 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 942341 | AE2-247 C | Adder | 1.47 MW | 1.25 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 942342 | AE2-247 E | Adder | 2.03 MW | 1.72 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 943461 | AF1-017 C | Adder | 1.33 MW | 1.13 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 943462 | AF1-017 E | Adder | 2.17 MW | 1.84 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 943741 | AF1-042 C | Adder | 3.18 MW | 2.71 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 943742 | AF1-042 E | Adder | 5.19 MW | 4.42 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 961951 | AG1-038 C | Adder | 3.52 MW | 2.99 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 961952 | AG1-038 E | Adder | 4.86 MW | 4.13 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 966661 | AG1-536 C | Adder | 5.84 MW | 4.96 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 966662 | AG1-536 E | Adder | 7.85 MW | 6.67 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 966871 | AG1-558 C | 50/50 | 4.09 MW | 4.09 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 966872 | AG1-558 E | 50/50 | 2.06 MW | 2.06 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 315260 | 1GOSPORTA | Adder | 2.02 MW | 1.72 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 315261 | 1GOSPORTB | Adder | 2.58 MW | 2.19 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 315262 | 1GOSPORTC | Adder | 2.19 MW | 1.86 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 316076 | AC2-137 E | Adder | 1.77 MW | 1.5 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 316078 | AC2-138 E | Adder | 0.99 MW | 0.84 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 316108 | AB2-160 C | Adder | 6.54 MW | 5.56 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 316109 | AB2-160 E | Adder | 10.67 MW | 9.07 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 316157 | AD2-030 E | Adder | 1.33 MW | 1.13 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 916192 | Z1-068 E | Adder | 1.77 MW | 1.5 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 923842 | AB2-024 E | Adder | 2.06 MW | 1.75 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 930122 | AB1-027 E | 50/50 | 2.13 MW | 2.13 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 938552 | AE1-074 E | Adder | 1.4 MW | 1.19 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 939312 | AE1-162 E | Adder | 1.46 MW | 1.24 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 946262 | AF1-291 E | Adder | 1.79 MW | 1.52 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 957601 | AF2-054 C | Adder | 2.36 MW | 2.01 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 957602 | AF2-054 E | Adder | 1.58 MW | 1.34 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 962531 | AG1-102 C | Adder | 1.19 MW | 1.01 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 962532 | AG1-102 E | Adder | 2.47 MW | 2.1 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 962851 | AG1-134 C | Adder | 14.59 MW | 12.4 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 962852 | AG1-134 E | Adder | 9.73 MW | 8.27 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 962861 | AG1-135 C | Adder | 6.6 MW | 5.61 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 962862 | AG1-135 E | Adder | 4.4 MW | 3.74 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 962962 | AG1-145 E | Adder | 1.6 MW | 1.36 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 962971 | AG1-146 C | Adder | 3.39 MW | 2.88 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 962972 | AG1-146 E | Adder | 2.26 MW | 1.92 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 962981 | AG1-147 C | Adder | 7.91 MW | 6.72 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 962982 | AG1-147 E | Adder | 5.27 MW | 4.48 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 963611 | AG1-210 C | Adder | 0.7 MW | 0.6 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 963612 | AG1-210 E | Adder | 1.06 MW | 0.9 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 964211 | AG1-282 C | Adder | 2.17 MW | 1.84 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 964212 | AG1-282 E | Adder | 1.45 MW | 1.23 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 925332 | AB2-190 E | Adder | 9.44 MW | 8.03 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 925522 | AC1-027 E | Adder | 1.15 MW | 0.97 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 942001 | AE2-212 C | Adder | 2.54 MW | 2.16 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 942002 | AE2-212 E | Adder | 1.7 MW | 1.44 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 957831 | AF2-077 C | Adder | 2.31 MW | 1.97 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 957832 | AF2-077 E | Adder | 1.54 MW | 1.31 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 958161 | AF2-110 C | Adder | 1.29 MW | 1.1 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 958162 | AF2-110 E | Adder | 2.05 MW | 1.74 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 313811 | 6ELKO L286 | Adder | 1.84 MW | 1.57 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 314181 | 3NORNECK | Adder | 0.94 MW | 0.8 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 934011 | AD1-025 C | Adder | 19.17 MW | 16.29 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 934012 | AD1-025 E | Adder | 11.36 MW | 9.65 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 927041 | AC1-191 C | 50/50 | 16.42 MW | 16.42 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 927042 | AC1-191 E | 50/50 | 8.18 MW | 8.18 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 313053 | 6PAPERMILL | Adder | 7.61 MW | 6.46 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 316004 | AC1-112 C | 50/50 | 0.43 MW | 0.43 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 316160 | AE1-175 E | Adder | 1.32 MW | 1.12 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 316233 | AE1-074 C | Adder | 2.78 MW | 2.36 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 316240 | AF1-291 C | Adder | 2.69 MW | 2.29 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 316301 | AE2-228 C | Adder | 2.67 MW | 2.27 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 316304 | AE2-227 C | Adder | 2.94 MW | 2.5 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 316312 | AB1-027 C | 50/50 | 0.69 MW | 0.69 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 926785 | AC1-164_E | Adder | 22.43 MW | 19.07 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 934065 | AD1-033 E | Adder | 4.69 MW | 3.99 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 939612 | AE1-191 E | Adder | 6.43 MW | 5.46 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 963221 | AG1-171 C | Adder | 2.44 MW | 2.08 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 963222 | AG1-171 E | Adder | 1.63 MW | 1.38 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 963231 | AG1-172 C | Adder | 2.44 MW | 2.08 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 963232 | AG1-172 E | Adder | 1.63 MW | 1.38 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 963241 | AG1-173 C | Adder | 2.44 MW | 2.08 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 963242 | AG1-173 E | Adder | 1.63 MW | 1.38 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 963251 | AG1-174 C | Adder | 2.44 MW | 2.08 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 963252 | AG1-174 E | Adder | 1.63 MW | 1.38 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 315051 | AA1-145 CT1 | 50/50 | 6.12 MW | 6.12 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 316201 | AC1-065 C | Adder | 11.5 MW | 9.77 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 939246 | AE1-155 E | Adder | 9.46 MW | 8.04 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 924814 | AB2-134 E | Adder | 14.37 MW | 12.21 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 316084 | AB2-161 E | Adder | 5.78 MW | 4.91 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 932046 | AC2-012 E | Adder | 12.42 MW | 10.56 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 316311 | AC2-079 C | Adder | 5.61 MW | 4.77 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 932596 | AC2-079 E | Adder | 9.15 MW | 7.78 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 934146 | AD1-041 E | Adder | 4.02 MW | 3.42 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 934576 | AD1-082 E | Adder | 4.6 MW | 3.91 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 316349 | AD2-085 C | Adder | 3.38 MW | 2.88 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 936666 | AD2-085 E | Adder | 5.52 MW | 4.69 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 961611 | AG1-000B C | Adder | 17.24 MW | 14.65 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 941291 | AE2-123 C | Adder | 27.49 MW | 23.37 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 941292 | AE2-123 E | Adder | 107.2 MW | 91.12 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 941301 | AE2-124 C | Adder | 24.98 MW | 21.23 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 941302 | AE2-124 E | Adder | 109.6 MW | 93.16 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 941591 | AE2-156 C | Adder | 16.97 MW | 14.42 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 942371 | AE2-250 C | Adder | 11.61 MW | 9.87 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 942372 | AE2-250 E | Adder | 6.13 MW | 5.21 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 942551 | AE2-270 C | Adder | 30.51 MW | 25.94 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 944581 | AF1-123 C | Adder | 44.66 MW | 37.96 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 944582 | AF1-123 E | Adder | 102.26 MW | 86.92 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 944591 | AF1-124 C | Adder | 25.67 MW | 21.82 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 944592 | AF1-124 E | Adder | 58.78 MW | 49.96 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 944601 | AF1-125 C | Adder | 44.66 MW | 37.96 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 944602 | AF1-125 E | Adder | 102.26 MW | 86.92 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 944631 | AF1-128 C | Adder | 50.78 MW | 43.16 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 945361 | AF1-201 C | Adder | 17.19 MW | 14.62 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 945362 | AF1-201 E | Adder | 11.46 MW | 9.74 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 957711 | AF2-065 C | Adder | 15.56 MW | 13.23 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 957712 | AF2-065 E | Adder | 14.95 MW | 12.71 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 958261 | AF2-120 C | Adder | 6.79 MW | 5.77 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 958262 | AF2-120 E | Adder | 4.53 MW | 3.85 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 961711 | AG1-011 C | Adder | 32.56 MW | 27.68 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 962271 | AG1-075 C | Adder | 20.05 MW | 17.04 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 962272 | AG1-075 E | Adder | 12.22 MW | 10.38 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 964951 | AG1-359 C | Adder | 21.34 MW | 18.14 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 965001 | AG1-364 C | Adder | 6.79 MW | 5.77 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 965002 | AG1-364 E | Adder | 10.18 MW | 8.65 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 965281 | AG1-393 C | Adder | 2.58 MW | 2.19 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 965282 | AG1-393 E | Adder | 1.72 MW | 1.46 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 966611 | AG1-531 C | Adder | 6.13 MW | 5.21 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 966612 | AG1-531 E | Adder | 4.09 MW | 3.47 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 935161 | AD1-151 C | Adder | 18.62 MW | 15.83 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 935162 | AD1-151 E | Adder | 12.41 MW | 10.55 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 939191 | AE1-149 C | Adder | 11.67 MW | 9.92 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 939192 | AE1-149 E | Adder | 7.78 MW | 6.62 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 939601 | AE1-190 C | Adder | 2.41 MW | 2.05 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 939602 | AE1-190 E | Adder | 1.61 MW | 1.37 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 940431 | AE2-027 C | Adder | 15.71 MW | 13.35 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 940432 | AE2-027 E | Adder | 10.47 MW | 8.9 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 940551 | AE2-041 C | Adder | 8.12 MW | 6.9 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 940651 | AE2-052 C | Adder | 3.89 MW | 3.31 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 941101 | AE2-104 C | Adder | 3.16 MW | 2.69 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 941102 | AE2-104 E | Adder | 5.02 MW | 4.27 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 941281 | AE2-122 C | Adder | 26.75 MW | 22.74 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 941282 | AE2-122 E | Adder | 107.94 MW | 91.75 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 943471 | AF1-018 C | Adder | 8.12 MW | 6.9 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | 944641 | AF1-129 C | Adder | 129.74 MW | 110.28 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 3.53 MW | 3.53 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 7.7 MW | 7.7 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 52.75 MW | 52.75 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 2.23 MW | 2.23 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | NY | PJM->LTFIMP_NY | CLTF | 1.1 MW | 1.1 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.19 MW | 0.19 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | WEC | LTFEXP_WEC->PJM | CLTF | 0.09 MW | 0.09 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | CPLE | LTFEXP_CPLE->PJM | CLTF | 6.84 MW | 6.84 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | TVA | LTFEXP_TVA->PJM | CLTF | 2.42 MW | 2.42 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | MEC | LTFEXP_MEC->PJM | CLTF | 0.93 MW | 0.93 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | LAGN | LTFEXP_LAGN->PJM | CLTF | 3.14 MW | 3.14 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.05 MW | 0.05 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 14.23 MW | 14.23 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-S | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 3.26 MW | 3.26 MW |
| Details for 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 963041 | AG1-153 C | 50/50 | 4.79 MW | 4.79 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 963042 | AG1-153 E | 50/50 | 7.18 MW | 7.18 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 963111 | AG1-160 C | 50/50 | 4.91 MW | 4.91 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 963112 | AG1-160 E | 50/50 | 7.36 MW | 7.36 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 966361 | AG1-505 C | 50/50 | 13.87 MW | 13.87 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 966362 | AG1-505 E | 50/50 | 9.25 MW | 9.25 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 966371 | AG1-506 C | 50/50 | 13.87 MW | 13.87 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 966372 | AG1-506 E | 50/50 | 9.25 MW | 9.25 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 314572 | 3EMPORIA | Adder | -0.34 MW | -0.29 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 315153 | 1CLOVER1 | 50/50 | 7.03 MW | 7.03 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 315154 | 1CLOVER2 | 50/50 | 6.97 MW | 6.97 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 926274 | AC1-105 E | Adder | 1.03 MW | 0.88 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 942931 | AE2-313 C | 50/50 | 31.78 MW | 31.78 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 942932 | AE2-313 E | 50/50 | 21.18 MW | 21.18 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 943902 | AF1-058 E | Adder | 0.57 MW | 0.49 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 944011 | AF1-069 C | 50/50 | 11.69 MW | 11.69 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 944012 | AF1-069 E | 50/50 | 4.54 MW | 4.54 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 960061 | AF2-297 C | Adder | 3.44 MW | 2.92 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 960062 | AF2-297 E | Adder | 2.29 MW | 1.95 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 941031 | AE2-094 C | 50/50 | 35.77 MW | 35.77 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 941032 | AE2-094 E | 50/50 | 16.02 MW | 16.02 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 941791 | AE2-182 C | Adder | 0.8 MW | 0.68 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 941792 | AE2-182 E | Adder | 0.37 MW | 0.32 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 957481 | AF2-042 C | 50/50 | 37.94 MW | 37.94 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 957482 | AF2-042 E | 50/50 | 25.29 MW | 25.29 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 314550 | 6HICKORY | Adder | 0.75 MW | 0.64 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 926755 | AC1-161 E | Adder | 6.35 MW | 5.4 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 315102 | 1BRUNSWICKG1 | 50/50 | 5.97 MW | 5.97 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 315103 | 1BRUNSWICKG2 | 50/50 | 5.97 MW | 5.97 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 315104 | 1BRUNSWICKG3 | 50/50 | 5.97 MW | 5.97 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 315105 | 1BRUNSWICKS1 | 50/50 | 12.4 MW | 12.4 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 315241 | 1Z1-086 GT1 | 50/50 | 7.73 MW | 7.73 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 315242 | 1Z1-086 GT2 | 50/50 | 7.74 MW | 7.74 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 315243 | 1Z1-086 GT3 | 50/50 | 7.74 MW | 7.74 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 315244 | 1Z1-086 ST | 50/50 | 13.46 MW | 13.46 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 916192 | Z1-068 E | Adder | 0.1 MW | 0.09 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 942001 | AE2-212 C | Adder | -2.88 MW | -2.45 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 926071 | AC1-086 C | Adder | -14.33 MW | -12.18 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 933291 | AC2-141 C | Adder | 14.88 MW | 12.64 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 933292 | AC2-141 E | Adder | 6.35 MW | 5.4 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 934621 | AD1-088 C | Adder | 4.94 MW | 4.2 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 934622 | AD1-088 E | Adder | 2.33 MW | 1.98 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 939411 | AE1-173 C | 50/50 | 67.7 MW | 67.7 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 939412 | AE1-173 E | 50/50 | 45.13 MW | 45.13 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 316222 | AC1-221 C | Adder | 3.79 MW | 3.22 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 316240 | AF1-291 C | Adder | -2.29 MW | -1.94 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 316301 | AE2-228 C | Adder | -2.36 MW | -2.01 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 316304 | AE2-227 C | Adder | -0.84 MW | -0.71 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 927255 | AC1-221 E | Adder | 1.77 MW | 1.5 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 927264 | AC1-222 E | Adder | 1.75 MW | 1.49 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 932763 | AC2-100 E | Adder | 1.19 MW | 1.01 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 934065 | AD1-033 E | Adder | 1.75 MW | 1.49 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 316181 | AB2-040 GEN | Adder | -4.81 MW | -4.09 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 941291 | AE2-123 C | Adder | 9.92 MW | 8.43 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 941292 | AE2-123 E | Adder | 38.69 MW | 32.89 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 941301 | AE2-124 C | Adder | 9.05 MW | 7.69 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 941302 | AE2-124 E | Adder | 39.71 MW | 33.76 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 944581 | AF1-123 C | Adder | 18.93 MW | 16.09 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 944582 | AF1-123 E | Adder | 43.35 MW | 36.85 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 944591 | AF1-124 C | Adder | 18.93 MW | 16.09 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 944592 | AF1-124 E | Adder | 43.35 MW | 36.85 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 944601 | AF1-125 C | Adder | 18.93 MW | 16.09 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 944602 | AF1-125 E | Adder | 43.35 MW | 36.85 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 962491 | AG1-098 C | Adder | 4.49 MW | 3.81 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 962492 | AG1-098 E | Adder | 2.99 MW | 2.54 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 963291 | AG1-178 C | 50/50 | 54.61 MW | 54.61 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 963351 | AG1-184 C | 50/50 | 29.42 MW | 29.42 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 964951 | AG1-359 C | Adder | 8.0 MW | 6.8 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 965811 | AG1-449 C | 50/50 | 20.58 MW | 20.58 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 313764 | 3SOCKMAN | Adder | -0.36 MW | -0.31 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 934611 | AD1-087 C | 50/50 | 0.69 MW | 0.69 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 934612 | AD1-087 E | 50/50 | 2.36 MW | 2.36 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 935171 | AD1-152 C | 50/50 | 0.67 MW | 0.67 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 935172 | AD1-152 E | 50/50 | 3.28 MW | 3.28 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 937481 | AD2-202 C | 50/50 | 0.2 MW | 0.2 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 937482 | AD2-202 E | 50/50 | 0.69 MW | 0.69 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 939191 | AE1-149 C | Adder | -11.3 MW | -9.6 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 940431 | AE2-027 C | Adder | -14.19 MW | -12.06 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 940641 | AE2-051 C | 50/50 | 15.02 MW | 15.02 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 940642 | AE2-051 E | 50/50 | 10.01 MW | 10.01 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 941281 | AE2-122 C | Adder | 9.66 MW | 8.21 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 941282 | AE2-122 E | Adder | 38.96 MW | 33.12 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 945811 | AF1-246 C | 50/50 | 5.31 MW | 5.31 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | 945812 | AF1-246 E | 50/50 | 7.33 MW | 7.33 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 15.52 MW | 15.52 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 10.05 MW | 10.05 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 38.94 MW | 38.94 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 1.15 MW | 1.15 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | NY | PJM->LTFIMP_NY | CLTF | 0.52 MW | 0.52 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.6 MW | 0.6 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | WEC | LTFEXP_WEC->PJM | CLTF | 0.32 MW | 0.32 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | CPLE | LTFEXP_CPLE->PJM | CLTF | 4.33 MW | 4.33 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | TVA | LTFEXP_TVA->PJM | CLTF | 2.65 MW | 2.65 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | MEC | LTFEXP_MEC->PJM | CLTF | 1.85 MW | 1.85 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | LAGN | LTFEXP_LAGN->PJM | CLTF | 3.36 MW | 3.36 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.12 MW | 0.12 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 7.28 MW | 7.28 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.07 MW | 2.07 MW |
| Details for 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 314184 | 3SHACKLE | 50/50 | 0.51 MW | 0.51 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 314314 | 3LOCKS | Adder | 1.13 MW | 0.96 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 314507 | 3THOMPSN | Adder | 1.26 MW | 1.07 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 314525 | 6KINGFORK | Adder | 0.66 MW | 0.56 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 314550 | 6HICKORY | Adder | 1.33 MW | 1.13 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 315060 | 1CHESTF5 | Adder | 62.59 MW | 53.2 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 315073 | 1STONECA | Adder | 5.25 MW | 4.47 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 315092 | 1YORKTN3 | Adder | 121.55 MW | 103.32 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 925865 | AC1-065 E | 50/50 | 19.08 MW | 19.08 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 926412 | AC1-112 E | Adder | 0.97 MW | 0.82 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 926472 | AC1-118 E | Adder | 1.07 MW | 0.91 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 926662 | AC1-147 E | Adder | 0.83 MW | 0.7 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 926755 | AC1-161 E | Adder | 7.87 MW | 6.69 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 927226 | AC1-216 E | Adder | 5.7 MW | 4.84 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 934392 | AD1-063 E | 50/50 | 1.29 MW | 1.29 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 935112 | AD1-144 E | Adder | 0.62 MW | 0.52 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 936582 | AD2-073 E | Adder | 1.15 MW | 0.97 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 936591 | AD2-074 C | 50/50 | 6.3 MW | 6.3 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 936592 | AD2-074 E | 50/50 | 10.28 MW | 10.28 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 942152 | AE2-227 E | Adder | 1.12 MW | 0.96 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 942341 | AE2-247 C | Adder | 0.84 MW | 0.72 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 942342 | AE2-247 E | Adder | 1.25 MW | 1.07 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 943462 | AF1-017 E | Adder | 1.34 MW | 1.14 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 943612 | AF1-032 E | Adder | 0.57 MW | 0.48 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 943741 | AF1-042 C | 50/50 | 3.29 MW | 3.29 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 943742 | AF1-042 E | 50/50 | 5.38 MW | 5.38 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 944491 | AF1-114 C | Adder | 4.97 MW | 4.23 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 944492 | AF1-114 E | Adder | 6.87 MW | 5.84 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 961951 | AG1-038 C | 50/50 | 3.64 MW | 3.64 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 961952 | AG1-038 E | 50/50 | 5.03 MW | 5.03 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 966661 | AG1-536 C | 50/50 | 6.09 MW | 6.09 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 966662 | AG1-536 E | 50/50 | 8.19 MW | 8.19 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 315260 | 1GOSPORTA | Adder | 1.33 MW | 1.13 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 315261 | 1GOSPORTB | Adder | 1.7 MW | 1.44 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 315262 | 1GOSPORTC | Adder | 1.44 MW | 1.23 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 316075 | AC2-137 C | 50/50 | 0.39 MW | 0.39 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 316076 | AC2-137 E | 50/50 | 1.6 MW | 1.6 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 316078 | AC2-138 E | Adder | 1.04 MW | 0.89 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 316108 | AB2-160 C | Adder | 3.43 MW | 2.92 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 316109 | AB2-160 E | Adder | 5.6 MW | 4.76 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 316156 | AD2-030 C | 50/50 | 0.36 MW | 0.36 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 316157 | AD2-030 E | 50/50 | 1.34 MW | 1.34 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 916192 | Z1-068 E | Adder | 1.16 MW | 0.99 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 923842 | AB2-024 E | 50/50 | 2.24 MW | 2.24 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 930122 | AB1-027 E | Adder | 1.19 MW | 1.01 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 939312 | AE1-162 E | Adder | 0.98 MW | 0.83 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 957492 | AF2-043 E | Adder | 0.88 MW | 0.74 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 957601 | AF2-054 C | 50/50 | 2.39 MW | 2.39 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 957602 | AF2-054 E | 50/50 | 1.59 MW | 1.59 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 962531 | AG1-102 C | Adder | 1.09 MW | 0.92 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 962532 | AG1-102 E | Adder | 2.26 MW | 1.93 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 962861 | AG1-135 C | 50/50 | 6.87 MW | 6.87 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 962862 | AG1-135 E | 50/50 | 4.58 MW | 4.58 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 962962 | AG1-145 E | 50/50 | 1.55 MW | 1.55 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 962971 | AG1-146 C | 50/50 | 3.49 MW | 3.49 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 962972 | AG1-146 E | 50/50 | 2.33 MW | 2.33 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 962981 | AG1-147 C | 50/50 | 8.15 MW | 8.15 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 962982 | AG1-147 E | 50/50 | 5.43 MW | 5.43 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 963611 | AG1-210 C | Adder | 0.74 MW | 0.63 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 963612 | AG1-210 E | Adder | 1.12 MW | 0.95 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 964211 | AG1-282 C | 50/50 | 2.33 MW | 2.33 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 964212 | AG1-282 E | 50/50 | 1.55 MW | 1.55 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 925332 | AB2-190 E | Adder | 6.03 MW | 5.13 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 925522 | AC1-027 E | Adder | 0.75 MW | 0.64 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 957831 | AF2-077 C | Adder | 2.12 MW | 1.8 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 957832 | AF2-077 E | Adder | 1.41 MW | 1.2 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 957871 | AF2-081 C | Adder | 6.08 MW | 5.17 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 957872 | AF2-081 E | Adder | 2.61 MW | 2.21 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 957971 | AF2-091 C | Adder | 1.69 MW | 1.44 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 957972 | AF2-091 E | Adder | 2.34 MW | 1.99 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 313811 | 6ELKO L286 | 50/50 | 1.67 MW | 1.67 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 314181 | 3NORNECK | Adder | 0.99 MW | 0.84 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 933291 | AC2-141 C | Adder | 18.43 MW | 15.67 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 933292 | AC2-141 E | Adder | 7.87 MW | 6.69 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 934011 | AD1-025 C | Adder | 12.46 MW | 10.59 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 934012 | AD1-025 E | Adder | 7.38 MW | 6.27 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 313053 | 6PAPERMILL | 50/50 | 8.23 MW | 8.23 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 316059 | AD1-063 C | 50/50 | 0.27 MW | 0.27 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 316159 | AE1-175 C | 50/50 | 0.36 MW | 0.36 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 316160 | AE1-175 E | 50/50 | 1.28 MW | 1.28 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 316169 | AC1-164 GEN | 50/50 | 8.29 MW | 8.29 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 316304 | AE2-227 C | Adder | 1.69 MW | 1.43 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 316314 | AB2-024 C | 50/50 | 0.31 MW | 0.31 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 316382 | AG1-145 C | 50/50 | 0.32 MW | 0.32 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 926785 | AC1-164_E | 50/50 | 27.0 MW | 27.0 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 934065 | AD1-033 E | Adder | 3.08 MW | 2.62 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 937226 | AE2-253 E | Adder | 3.56 MW | 3.03 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 939611 | AE1-191 C | 50/50 | 1.31 MW | 1.31 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 939612 | AE1-191 E | 50/50 | 6.49 MW | 6.49 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 963221 | AG1-171 C | Adder | 1.59 MW | 1.35 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 963222 | AG1-171 E | Adder | 1.06 MW | 0.9 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 963231 | AG1-172 C | Adder | 1.59 MW | 1.35 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 963232 | AG1-172 E | Adder | 1.06 MW | 0.9 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 963241 | AG1-173 C | Adder | 1.59 MW | 1.35 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 963242 | AG1-173 E | Adder | 1.06 MW | 0.9 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 963251 | AG1-174 C | Adder | 1.59 MW | 1.35 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 963252 | AG1-174 E | Adder | 1.06 MW | 0.9 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 316201 | AC1-065 C | 50/50 | 11.58 MW | 11.58 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 316404 | AE1-155 C | 50/50 | 2.03 MW | 2.03 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 939246 | AE1-155 E | 50/50 | 9.86 MW | 9.86 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 919153 | AA1-139 E2 | Adder | 2.49 MW | 2.11 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 919152 | AA1-139 E1 | Adder | 2.49 MW | 2.11 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 924814 | AB2-134 E | Adder | 9.34 MW | 7.93 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 316084 | AB2-161 E | Adder | 3.37 MW | 2.86 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 932046 | AC2-012 E | Adder | 8.18 MW | 6.95 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 316280 | AD1-041 C | 50/50 | 0.83 MW | 0.83 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 934146 | AD1-041 E | 50/50 | 4.05 MW | 4.05 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 934576 | AD1-082 E | Adder | 2.68 MW | 2.28 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 316349 | AD2-085 C | Adder | 2.09 MW | 1.78 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 936666 | AD2-085 E | Adder | 3.42 MW | 2.9 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 961611 | AG1-000B C | Adder | 11.52 MW | 9.79 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 941291 | AE2-123 C | Adder | 18.07 MW | 15.36 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 941292 | AE2-123 E | Adder | 70.45 MW | 59.88 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 941301 | AE2-124 C | Adder | 16.41 MW | 13.95 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 941302 | AE2-124 E | Adder | 72.01 MW | 61.21 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 941591 | AE2-156 C | Adder | 11.17 MW | 9.49 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 942371 | AE2-250 C | Adder | 6.09 MW | 5.18 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 942372 | AE2-250 E | Adder | 3.22 MW | 2.73 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 942551 | AE2-270 C | Adder | 19.83 MW | 16.86 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 944581 | AF1-123 C | Adder | 29.27 MW | 24.88 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 944582 | AF1-123 E | Adder | 67.01 MW | 56.96 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 944591 | AF1-124 C | Adder | 29.27 MW | 24.88 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 944592 | AF1-124 E | Adder | 67.01 MW | 56.96 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 944601 | AF1-125 C | Adder | 29.27 MW | 24.88 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 944602 | AF1-125 E | Adder | 67.01 MW | 56.96 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 944631 | AF1-128 C | Adder | 39.16 MW | 33.29 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 945361 | AF1-201 C | Adder | 15.2 MW | 12.92 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 945362 | AF1-201 E | Adder | 10.14 MW | 8.62 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 957711 | AF2-065 C | Adder | 10.11 MW | 8.6 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 957712 | AF2-065 E | Adder | 9.72 MW | 8.26 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 958261 | AF2-120 C | 50/50 | 7.08 MW | 7.08 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 958262 | AF2-120 E | 50/50 | 4.72 MW | 4.72 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 961711 | AG1-011 C | Adder | 21.16 MW | 17.98 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 962271 | AG1-075 C | Adder | 10.52 MW | 8.94 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 962272 | AG1-075 E | Adder | 6.41 MW | 5.45 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 964951 | AG1-359 C | Adder | 14.0 MW | 11.9 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 965001 | AG1-364 C | Adder | 4.47 MW | 3.8 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 965002 | AG1-364 E | Adder | 6.7 MW | 5.7 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 965281 | AG1-393 C | Adder | 1.35 MW | 1.15 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 965282 | AG1-393 E | Adder | 0.9 MW | 0.77 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 966611 | AG1-531 C | Adder | 4.55 MW | 3.86 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 966612 | AG1-531 E | Adder | 3.03 MW | 2.58 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 935161 | AD1-151 C | Adder | 11.99 MW | 10.19 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 935162 | AD1-151 E | Adder | 7.99 MW | 6.79 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 938531 | AE1-072 C | Adder | 10.67 MW | 9.07 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 938532 | AE1-072 E | Adder | 5.56 MW | 4.73 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 939191 | AE1-149 C | Adder | 6.54 MW | 5.55 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 939192 | AE1-149 E | Adder | 4.36 MW | 3.7 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 939601 | AE1-190 C | 50/50 | 2.43 MW | 2.43 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 939602 | AE1-190 E | 50/50 | 1.62 MW | 1.62 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 940431 | AE2-027 C | Adder | 8.26 MW | 7.02 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 940432 | AE2-027 E | Adder | 5.5 MW | 4.68 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 940551 | AE2-041 C | 50/50 | 8.61 MW | 8.61 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 940651 | AE2-052 C | Adder | 2.18 MW | 1.85 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 941281 | AE2-122 C | Adder | 17.58 MW | 14.94 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 941282 | AE2-122 E | Adder | 70.94 MW | 60.3 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | 943471 | AF1-018 C | 50/50 | 8.61 MW | 8.61 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 3.46 MW | 3.46 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 5.07 MW | 5.07 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 31.66 MW | 31.66 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 1.34 MW | 1.34 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | NY | PJM->LTFIMP_NY | CLTF | 0.65 MW | 0.65 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.16 MW | 0.16 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | WEC | LTFEXP_WEC->PJM | CLTF | 0.08 MW | 0.08 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | CPLE | LTFEXP_CPLE->PJM | CLTF | 4.07 MW | 4.07 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | TVA | LTFEXP_TVA->PJM | CLTF | 1.54 MW | 1.54 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | MEC | LTFEXP_MEC->PJM | CLTF | 0.68 MW | 0.68 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | LAGN | LTFEXP_LAGN->PJM | CLTF | 1.99 MW | 1.99 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.04 MW | 0.04 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 8.53 MW | 8.53 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T567_SRT-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.94 MW | 1.94 MW |
| Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 963041 | AG1-153 C | Adder | 5.79 MW | 4.92 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 963042 | AG1-153 E | Adder | 8.69 MW | 7.39 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 963111 | AG1-160 C | Adder | 5.87 MW | 4.99 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 963112 | AG1-160 E | Adder | 8.8 MW | 7.48 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 966361 | AG1-505 C | Adder | 17.28 MW | 14.68 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 966362 | AG1-505 E | Adder | 11.52 MW | 9.79 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 966371 | AG1-506 C | Adder | 17.28 MW | 14.68 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 966372 | AG1-506 E | Adder | 11.52 MW | 9.79 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 942931 | AE2-313 C | Adder | 37.58 MW | 31.94 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 942932 | AE2-313 E | Adder | 25.05 MW | 21.29 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 944011 | AF1-069 C | Adder | 13.62 MW | 11.58 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 944012 | AF1-069 E | Adder | 5.29 MW | 4.5 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 941031 | AE2-094 C | Adder | 41.69 MW | 35.44 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 941032 | AE2-094 E | Adder | 18.67 MW | 15.87 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 957481 | AF2-042 C | Adder | 53.55 MW | 45.52 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 957482 | AF2-042 E | Adder | 35.7 MW | 30.35 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 933502 | AC2-165 E | Adder | 7.5 MW | 6.37 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 314331 | 6POE | Adder | 1.28 MW | 1.09 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 314550 | 6HICKORY | Adder | 2.02 MW | 1.72 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 926755 | AC1-161 E | Adder | 12.03 MW | 10.23 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 958502 | AF2-144 E | Adder | 1.25 MW | 1.06 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 315173 | 1LOISA B | 50/50 | 2.32 MW | 2.32 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 315174 | 1LOISA C | 50/50 | 2.32 MW | 2.32 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 315175 | 1LOISA D | 50/50 | 2.32 MW | 2.32 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 315176 | 1LOISA E | 50/50 | 4.73 MW | 4.73 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 315177 | 1S ANNAG1 | 50/50 | 2.27 MW | 2.27 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 315178 | 1S ANNAS1 | 50/50 | 1.17 MW | 1.17 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 315179 | 1S ANNAG2 | 50/50 | 2.27 MW | 2.27 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 315180 | 1S ANNAS2 | 50/50 | 1.17 MW | 1.17 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 315225 | 1N ANNA1 | 50/50 | 75.87 MW | 75.87 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 315226 | 1N ANNA2 | 50/50 | 75.88 MW | 75.88 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 923852 | AB2-025 E | Adder | 1.13 MW | 0.96 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 923862 | AB2-026 E | Adder | 1.27 MW | 1.08 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 925022 | AB2-158 E | 50/50 | 9.71 MW | 9.71 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 938552 | AE1-074 E | Adder | 1.27 MW | 1.08 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 938562 | AE1-075 E | Adder | 1.08 MW | 0.92 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 946371 | AF1-301 C | 50/50 | 18.32 MW | 18.32 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 946372 | AF1-301 E | 50/50 | 12.3 MW | 12.3 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 964271 | AG1-288 C | 50/50 | 34.24 MW | 34.24 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 966001 | AG1-469 C | Adder | 1.98 MW | 1.69 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 966002 | AG1-469 E | Adder | 0.99 MW | 0.84 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 966331 | AG1-502 C | 50/50 | 14.5 MW | 14.5 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 966332 | AG1-502 E | 50/50 | 3.62 MW | 3.62 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 966341 | AG1-503 C | 50/50 | 3.62 MW | 3.62 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 966342 | AG1-503 E | 50/50 | 0.91 MW | 0.91 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 933291 | AC2-141 C | Adder | 28.18 MW | 23.95 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 933292 | AC2-141 E | Adder | 12.03 MW | 10.23 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 939411 | AE1-173 C | Adder | 92.38 MW | 78.52 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 939412 | AE1-173 E | Adder | 61.58 MW | 52.35 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 208900 | BRIS G1 | 50/50 | -2.41 MW | -2.41 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 208901 | BRIS G2 | 50/50 | -2.85 MW | -2.85 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 316164 | AC1-076_C | 50/50 | 0.96 MW | 0.96 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 316170 | AC1-121 C | Adder | 2.77 MW | 2.35 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 316192 | AB2-158 C | 50/50 | 3.12 MW | 3.12 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 316233 | AE1-074 C | Adder | 2.53 MW | 2.15 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 316254 | AC1-120 C | Adder | 8.05 MW | 6.85 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 316336 | AC2-165 C | Adder | 9.96 MW | 8.47 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 924516 | AB2-100 E1 | Adder | 2.74 MW | 2.33 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 924517 | AB2-100 E2 | Adder | 2.74 MW | 2.33 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 934065 | AD1-033 E | Adder | 4.65 MW | 3.96 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 926004 | AC1-076_E | 50/50 | 6.48 MW | 6.48 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 926486 | AC1-120 E | Adder | 4.15 MW | 3.53 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 926502 | AC1-121 E | Adder | 1.3 MW | 1.11 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 316044 | AC1-158 C1 | 50/50 | 16.61 MW | 16.61 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 316045 | AC1-158 C2 | 50/50 | 16.61 MW | 16.61 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 926739 | AC1-158 E1 | 50/50 | 50.96 MW | 50.96 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 926740 | AC1-158 E2 | 50/50 | 50.96 MW | 50.96 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 941291 | AE2-123 C | Adder | 27.1 MW | 23.04 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 941292 | AE2-123 E | Adder | 105.69 MW | 89.84 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 941301 | AE2-124 C | Adder | 24.65 MW | 20.95 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 941302 | AE2-124 E | Adder | 108.17 MW | 91.94 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 944581 | AF1-123 C | Adder | 44.79 MW | 38.07 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 944582 | AF1-123 E | Adder | 102.56 MW | 87.17 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 944591 | AF1-124 C | Adder | 44.79 MW | 38.07 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 944592 | AF1-124 E | Adder | 102.56 MW | 87.17 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 944601 | AF1-125 C | Adder | 44.79 MW | 38.07 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 944602 | AF1-125 E | Adder | 102.56 MW | 87.17 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 946011 | AF1-266 C | Adder | 13.1 MW | 11.13 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 957431 | AF2-037 C | 50/50 | 23.97 MW | 23.97 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 957432 | AF2-037 E | 50/50 | 15.98 MW | 15.98 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 957691 | AF2-063 C | 50/50 | 38.25 MW | 38.25 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 957692 | AF2-063 E | 50/50 | 25.5 MW | 25.5 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 962841 | AG1-133 C | 50/50 | 44.52 MW | 44.52 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 962842 | AG1-133 E | 50/50 | 29.68 MW | 29.68 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 963291 | AG1-178 C | Adder | 65.81 MW | 55.94 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 963351 | AG1-184 C | Adder | 35.45 MW | 30.14 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 964281 | AG1-289 C | 50/50 | 18.93 MW | 18.93 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 964421 | AG1-305 C | 50/50 | 30.09 MW | 30.09 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 964422 | AG1-305 E | 50/50 | 20.06 MW | 20.06 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 964951 | AG1-359 C | Adder | 21.2 MW | 18.02 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 965811 | AG1-449 C | Adder | 24.33 MW | 20.68 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 934612 | AD1-087 E | Adder | 3.54 MW | 3.0 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 937482 | AD2-202 E | Adder | 1.03 MW | 0.88 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 940481 | AE2-033 C | Adder | 15.65 MW | 13.3 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 940482 | AE2-033 E | Adder | 10.55 MW | 8.96 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 940541 | AE2-040 C | Adder | 2.78 MW | 2.37 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 940641 | AE2-051 C | Adder | 18.1 MW | 15.39 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 940642 | AE2-051 E | Adder | 12.07 MW | 10.26 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 941281 | AE2-122 C | Adder | 7.54 MW | 6.41 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 941282 | AE2-122 E | Adder | 106.42 MW | 90.46 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 945811 | AF1-246 C | Adder | 7.5 MW | 6.37 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 945812 | AF1-246 E | Adder | 10.35 MW | 8.8 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 316303 | AF2-085 | 50/50 | 4.34 MW | 4.34 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 24.91 MW | 24.91 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 20.12 MW | 20.12 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 88.36 MW | 88.36 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 5.78 MW | 5.78 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | NY | PJM->LTFIMP_NY | CLTF | 2.72 MW | 2.72 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | LGEE | LTFEXP_LGEE->PJM | CLTF | 1.09 MW | 1.09 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | WEC | LTFEXP_WEC->PJM | CLTF | 0.54 MW | 0.54 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | CPLE | LTFEXP_CPLE->PJM | CLTF | 10.49 MW | 10.49 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | TVA | LTFEXP_TVA->PJM | CLTF | 5.6 MW | 5.6 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | MEC | LTFEXP_MEC->PJM | CLTF | 3.39 MW | 3.39 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | LAGN | LTFEXP_LAGN->PJM | CLTF | 7.04 MW | 7.04 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.21 MW | 0.21 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 36.83 MW | 36.83 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 5.0 MW | 5.0 MW |
| Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 963041 | AG1-153 C | 50/50 | 8.9 MW | 8.9 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 963042 | AG1-153 E | 50/50 | 13.35 MW | 13.35 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 963111 | AG1-160 C | 50/50 | 9.01 MW | 9.01 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 963112 | AG1-160 E | 50/50 | 13.52 MW | 13.52 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 966361 | AG1-505 C | 50/50 | 26.47 MW | 26.47 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 966362 | AG1-505 E | 50/50 | 17.65 MW | 17.65 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 966371 | AG1-506 C | 50/50 | 26.47 MW | 26.47 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 966372 | AG1-506 E | 50/50 | 17.65 MW | 17.65 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 942931 | AE2-313 C | 50/50 | 57.61 MW | 57.61 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 942932 | AE2-313 E | 50/50 | 38.41 MW | 38.41 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 944011 | AF1-069 C | 50/50 | 20.9 MW | 20.9 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 944012 | AF1-069 E | 50/50 | 8.12 MW | 8.12 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 941031 | AE2-094 C | 50/50 | 63.95 MW | 63.95 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 941032 | AE2-094 E | 50/50 | 28.64 MW | 28.64 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 957481 | AF2-042 C | Adder | 81.86 MW | 69.58 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 957482 | AF2-042 E | Adder | 0.29 MW | 0.24 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 314331 | 6POE | 50/50 | 2.09 MW | 2.09 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 314507 | 3THOMPSN | Adder | 3.09 MW | 2.63 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 314550 | 6HICKORY | Adder | 3.34 MW | 2.84 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 926662 | AC1-147 E | Adder | 2.03 MW | 1.73 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 926755 | AC1-161 E | 50/50 | 19.98 MW | 19.98 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 315102 | 1BRUNSWICKG1 | 50/50 | 11.09 MW | 11.09 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 315103 | 1BRUNSWICKG2 | 50/50 | 11.09 MW | 11.09 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 315104 | 1BRUNSWICKG3 | 50/50 | 11.09 MW | 11.09 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 315105 | 1BRUNSWICKS1 | 50/50 | 23.04 MW | 23.04 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 315108 | 1ELIZAR1 | 50/50 | 4.14 MW | 4.14 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 315110 | 1ELIZAR3 | 50/50 | 4.2 MW | 4.2 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 315241 | 1Z1-086 GT1 | 50/50 | 14.19 MW | 14.19 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 315242 | 1Z1-086 GT2 | 50/50 | 14.21 MW | 14.21 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 315243 | 1Z1-086 GT3 | 50/50 | 14.21 MW | 14.21 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 315244 | 1Z1-086 ST | 50/50 | 24.72 MW | 24.72 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 315260 | 1GOSPORTA | Adder | 3.26 MW | 2.77 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 315261 | 1GOSPORTB | Adder | 4.17 MW | 3.54 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 315262 | 1GOSPORTC | Adder | 3.54 MW | 3.01 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 916192 | Z1-068 E | Adder | 2.88 MW | 2.45 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 923852 | AB2-025 E | 50/50 | 1.78 MW | 1.78 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 938552 | AE1-074 E | 50/50 | 2.0 MW | 2.0 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 925522 | AC1-027 E | Adder | 1.87 MW | 1.59 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 957871 | AF2-081 C | Adder | 15.31 MW | 13.01 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 957872 | AF2-081 E | Adder | 6.56 MW | 5.58 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 933291 | AC2-141 C | 50/50 | 46.81 MW | 46.81 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 933292 | AC2-141 E | 50/50 | 19.98 MW | 19.98 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 939411 | AE1-173 C | 50/50 | 145.36 MW | 145.36 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 939412 | AE1-173 E | 50/50 | 96.91 MW | 96.91 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 316185 | AD1-033 C | 50/50 | 1.59 MW | 1.59 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 316233 | AE1-074 C | 50/50 | 3.96 MW | 3.96 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 316294 | AC1-161 C | 50/50 | 6.46 MW | 6.46 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 316315 | AB2-025 C | 50/50 | 0.53 MW | 0.53 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 934065 | AD1-033 E | 50/50 | 7.7 MW | 7.7 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 937226 | AE2-253 E | Adder | 8.95 MW | 7.61 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 919153 | AA1-139 E2 | Adder | 6.26 MW | 5.32 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 919152 | AA1-139 E1 | Adder | 6.26 MW | 5.32 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 932046 | AC2-012 E | Adder | 20.09 MW | 17.07 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 941291 | AE2-123 C | Adder | 44.84 MW | 38.12 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 941292 | AE2-123 E | Adder | 174.88 MW | 148.64 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 941301 | AE2-124 C | Adder | 40.78 MW | 34.67 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 941302 | AE2-124 E | Adder | 178.95 MW | 152.11 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 941591 | AE2-156 C | Adder | 27.45 MW | 23.34 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 944581 | AF1-123 C | 50/50 | 74.0 MW | 74.0 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 944582 | AF1-123 E | 50/50 | 169.43 MW | 169.43 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 944591 | AF1-124 C | 50/50 | 74.0 MW | 74.0 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 944592 | AF1-124 E | 50/50 | 169.43 MW | 169.43 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 944601 | AF1-125 C | 50/50 | 74.0 MW | 74.0 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 944602 | AF1-125 E | 50/50 | 169.43 MW | 169.43 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 946011 | AF1-266 C | 50/50 | 20.77 MW | 20.77 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 963291 | AG1-178 C | 50/50 | 101.8 MW | 101.8 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 963351 | AG1-184 C | 50/50 | 54.84 MW | 54.84 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 964951 | AG1-359 C | 50/50 | 35.05 MW | 35.05 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 965001 | AG1-364 C | Adder | 10.98 MW | 9.33 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 965002 | AG1-364 E | Adder | 16.47 MW | 14.0 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 965811 | AG1-449 C | 50/50 | 37.31 MW | 37.31 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 940481 | AE2-033 C | 50/50 | 24.81 MW | 24.81 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 940482 | AE2-033 E | 50/50 | 16.73 MW | 16.73 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 940541 | AE2-040 C | 50/50 | 4.41 MW | 4.41 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 940641 | AE2-051 C | 50/50 | 28.09 MW | 28.09 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 940642 | AE2-051 E | 50/50 | 18.73 MW | 18.73 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 941281 | AE2-122 C | Adder | 43.64 MW | 37.09 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 941282 | AE2-122 E | Adder | 176.08 MW | 149.67 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 316303 | AF2-085 | 50/50 | 6.53 MW | 6.53 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 65.77 MW | 65.77 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 40.66 MW | 40.66 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 146.25 MW | 146.25 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 7.11 MW | 7.11 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | NY | PJM->LTFIMP_NY | CLTF | 3.23 MW | 3.23 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | LGEE | LTFEXP_LGEE->PJM | CLTF | 2.62 MW | 2.62 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | WEC | LTFEXP_WEC->PJM | CLTF | 1.35 MW | 1.35 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | CPLE | LTFEXP_CPLE->PJM | CLTF | 16.92 MW | 16.92 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | TVA | LTFEXP_TVA->PJM | CLTF | 10.58 MW | 10.58 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | MEC | LTFEXP_MEC->PJM | CLTF | 7.7 MW | 7.7 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | LAGN | LTFEXP_LAGN->PJM | CLTF | 13.28 MW | 13.28 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.49 MW | 0.49 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 45.18 MW | 45.18 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 8.07 MW | 8.07 MW |
| Details for AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 961791 | AG1-021 C | Adder | 1.6 MW | 1.36 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 961792 | AG1-021 E | Adder | 1.07 MW | 0.91 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 961891 | AG1-030 C | Adder | 12.06 MW | 10.26 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 961892 | AG1-030 E | Adder | 8.04 MW | 6.84 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 963041 | AG1-153 C | Adder | 5.37 MW | 4.56 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 963042 | AG1-153 E | Adder | 8.05 MW | 6.84 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 963111 | AG1-160 C | Adder | 5.44 MW | 4.63 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 963112 | AG1-160 E | Adder | 8.16 MW | 6.94 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 963171 | AG1-166 C | Adder | 1.6 MW | 1.36 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 963172 | AG1-166 E | Adder | 1.07 MW | 0.91 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 963181 | AG1-167 C | Adder | 1.6 MW | 1.36 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 963182 | AG1-167 E | Adder | 1.07 MW | 0.91 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 963191 | AG1-168 C | Adder | 1.6 MW | 1.36 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 963192 | AG1-168 E | Adder | 1.07 MW | 0.91 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 963201 | AG1-169 C | Adder | 1.6 MW | 1.36 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 963202 | AG1-169 E | Adder | 1.07 MW | 0.91 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 963211 | AG1-170 C | Adder | 1.6 MW | 1.36 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 963212 | AG1-170 E | Adder | 1.07 MW | 0.91 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 963301 | AG1-179 C | Adder | 4.67 MW | 3.97 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 964111 | AG1-272 C | Adder | 2.08 MW | 1.77 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 964112 | AG1-272 E | Adder | 0.62 MW | 0.53 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 964121 | AG1-273 C | Adder | 2.08 MW | 1.77 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 964122 | AG1-273 E | Adder | 0.62 MW | 0.53 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 964131 | AG1-274 C | Adder | 2.08 MW | 1.77 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 964132 | AG1-274 E | Adder | 0.62 MW | 0.53 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 964791 | AG1-342 C | Adder | 3.35 MW | 2.85 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 964792 | AG1-342 E | Adder | 2.63 MW | 2.24 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 966811 | AG1-552 C | Adder | 1.63 MW | 1.39 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 966812 | AG1-552 E | Adder | 0.78 MW | 0.66 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 965191 | AG1-384 C | Adder | 2.08 MW | 1.77 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 965192 | AG1-384 E | Adder | 0.62 MW | 0.53 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 965591 | AG1-427 C | Adder | 9.67 MW | 8.22 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 965592 | AG1-427 E | Adder | 6.45 MW | 5.48 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 965721 | AG1-440 C | Adder | 6.12 MW | 5.2 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 965722 | AG1-440 E | Adder | 4.08 MW | 3.47 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 965731 | AG1-441 C | Adder | 6.12 MW | 5.2 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 965732 | AG1-441 E | Adder | 4.08 MW | 3.47 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 966361 | AG1-505 C | Adder | 15.99 MW | 13.59 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 966362 | AG1-505 E | Adder | 10.66 MW | 9.06 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 966371 | AG1-506 C | Adder | 15.99 MW | 13.59 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 966372 | AG1-506 E | Adder | 10.66 MW | 9.06 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 966621 | AG1-532 C | Adder | 1.14 MW | 0.97 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 966622 | AG1-532 E | Adder | 0.76 MW | 0.64 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 313853 | 3PONTONDP | Adder | 0.53 MW | 0.45 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 314572 | 3EMPORIA | Adder | 0.35 MW | 0.3 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 314713 | 3PAMPLIN | Adder | 0.8 MW | 0.68 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 918492 | AA1-063AE OP | Adder | 3.21 MW | 2.73 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 919692 | AA2-053 E OP | Adder | 3.34 MW | 2.84 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 925785 | AC1-054 E | Adder | 2.77 MW | 2.36 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 942931 | AE2-313 C | Adder | 34.9 MW | 29.66 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 942932 | AE2-313 E | Adder | 23.27 MW | 19.78 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 944011 | AF1-069 C | 50/50 | 12.66 MW | 12.66 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 944012 | AF1-069 E | 50/50 | 4.92 MW | 4.92 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 958801 | AF2-171 C | Adder | 12.03 MW | 10.22 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 958802 | AF2-171 E | Adder | 8.02 MW | 6.82 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 959311 | AF2-222 C | Adder | 13.47 MW | 11.45 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 959312 | AF2-222 E | Adder | 9.03 MW | 7.67 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 960081 | AF2-299 C | Adder | 2.1 MW | 1.79 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 960082 | AF2-299 E | Adder | 1.4 MW | 1.19 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 923263 | AB1-132 E OP | Adder | 4.86 MW | 4.13 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 923573 | AB1-173 E OP | Adder | 2.64 MW | 2.24 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 924162 | AB2-060 E OP | Adder | 3.49 MW | 2.97 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 924302 | AB2-077 E O1 | Adder | 1.09 MW | 0.93 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 924312 | AB2-078 E O1 | Adder | 1.09 MW | 0.93 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 924322 | AB2-079 E O1 | Adder | 1.09 MW | 0.93 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 925612 | AC1-036 E | Adder | 0.7 MW | 0.59 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 938371 | AE1-056 C | Adder | 5.17 MW | 4.39 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 938372 | AE1-056 E | Adder | 2.82 MW | 2.4 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 939181 | AE1-148 C | Adder | 7.36 MW | 6.26 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 939182 | AE1-148 E | Adder | 4.91 MW | 4.17 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 941031 | AE2-094 C | 50/50 | 38.75 MW | 38.75 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 941032 | AE2-094 E | 50/50 | 17.36 MW | 17.36 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 941791 | AE2-182 C | Adder | 1.68 MW | 1.43 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 941792 | AE2-182 E | Adder | 0.78 MW | 0.66 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 946281 | AF1-292 C | Adder | 1.25 MW | 1.07 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 946282 | AF1-292 E | Adder | 0.84 MW | 0.71 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 946301 | AF1-294 C | Adder | 3.29 MW | 2.79 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 946302 | AF1-294 E | Adder | 2.19 MW | 1.86 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 957481 | AF2-042 C | Adder | 49.22 MW | 41.83 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 957482 | AF2-042 E | Adder | 32.81 MW | 27.89 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 958211 | AF2-115 C | Adder | 2.0 MW | 1.7 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 958212 | AF2-115 E | Adder | 1.34 MW | 1.14 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 933502 | AC2-165 E | Adder | 6.82 MW | 5.79 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 314331 | 6POE | Adder | 1.03 MW | 0.88 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 926755 | AC1-161 E | Adder | 9.52 MW | 8.09 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 958502 | AF2-144 E | Adder | 1.14 MW | 0.97 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 315172 | 1LOISA A | 50/50 | 2.61 MW | 2.61 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 315173 | 1LOISA B | 50/50 | 2.63 MW | 2.63 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 315174 | 1LOISA C | 50/50 | 2.63 MW | 2.63 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 315175 | 1LOISA D | 50/50 | 2.63 MW | 2.63 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 315176 | 1LOISA E | 50/50 | 5.36 MW | 5.36 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 315177 | 1S ANNAG1 | 50/50 | 2.58 MW | 2.58 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 315178 | 1S ANNAS1 | 50/50 | 1.33 MW | 1.33 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 315179 | 1S ANNAG2 | 50/50 | 2.58 MW | 2.58 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 315180 | 1S ANNAS2 | 50/50 | 1.33 MW | 1.33 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 315225 | 1N ANNA1 | 50/50 | 90.54 MW | 90.54 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 315226 | 1N ANNA2 | 50/50 | 90.55 MW | 90.55 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 923852 | AB2-025 E | Adder | 0.97 MW | 0.82 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 923862 | AB2-026 E | Adder | 1.16 MW | 0.98 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 925022 | AB2-158 E | 50/50 | 11.37 MW | 11.37 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 938552 | AE1-074 E | Adder | 1.08 MW | 0.92 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 938562 | AE1-075 E | Adder | 0.99 MW | 0.84 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 946371 | AF1-301 C | 50/50 | 21.05 MW | 21.05 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 946372 | AF1-301 E | 50/50 | 14.14 MW | 14.14 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 966001 | AG1-469 C | 50/50 | 2.0 MW | 2.0 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 966002 | AG1-469 E | 50/50 | 1.0 MW | 1.0 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 314722 | 3TWITTYS | Adder | 0.77 MW | 0.66 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 926071 | AC1-086 C | Adder | 16.7 MW | 14.19 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 926072 | AC1-086 E | Adder | 7.6 MW | 6.46 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 936261 | AD2-033 C | Adder | 10.54 MW | 8.96 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 936262 | AD2-033 E | Adder | 7.03 MW | 5.97 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 933291 | AC2-141 C | Adder | 22.3 MW | 18.96 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 933292 | AC2-141 E | Adder | 9.13 MW | 7.76 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 934621 | AD1-088 C | Adder | 10.33 MW | 8.78 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 934622 | AD1-088 E | Adder | 4.86 MW | 4.13 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 939411 | AE1-173 C | Adder | 81.83 MW | 69.55 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 939412 | AE1-173 E | Adder | 54.55 MW | 46.37 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 962572 | AG1-106 E | Adder | 2.11 MW | 1.79 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 962571 | AG1-106 C | Adder | 4.64 MW | 3.95 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 208900 | BRIS G1 | 50/50 | -2.11 MW | -2.11 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 208901 | BRIS G2 | 50/50 | -2.5 MW | -2.5 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 316192 | AB2-158 C | 50/50 | 3.65 MW | 3.65 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 316233 | AE1-074 C | Adder | 2.14 MW | 1.82 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 316336 | AC2-165 C | Adder | 9.06 MW | 7.7 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 924516 | AB2-100 E1 | Adder | 2.35 MW | 2.0 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 924517 | AB2-100 E2 | Adder | 2.35 MW | 2.0 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 316181 | AB2-040 GEN | Adder | 6.04 MW | 5.14 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 923994 | AB2-040_E | Adder | 4.94 MW | 4.2 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 924022 | AB2-043 E O1 | Adder | 4.23 MW | 3.6 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 316088 | AB2-174 E | Adder | 5.25 MW | 4.46 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 316044 | AC1-158 C1 | 50/50 | 16.68 MW | 16.68 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 316045 | AC1-158 C2 | 50/50 | 16.68 MW | 16.68 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 926739 | AC1-158 E1 | 50/50 | 51.19 MW | 51.19 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 926740 | AC1-158 E2 | 50/50 | 51.19 MW | 51.19 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 940661 | AE2-053 C | Adder | 2.73 MW | 2.32 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 944581 | AF1-123 C | Adder | 35.75 MW | 30.39 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 944582 | AF1-123 E | Adder | 81.86 MW | 69.58 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 944591 | AF1-124 C | Adder | 35.75 MW | 30.39 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 944592 | AF1-124 E | Adder | 81.86 MW | 69.58 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 944601 | AF1-125 C | Adder | 35.75 MW | 30.39 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 944602 | AF1-125 E | Adder | 81.86 MW | 69.58 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 946011 | AF1-266 C | Adder | 11.28 MW | 9.59 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 957431 | AF2-037 C | 50/50 | 28.28 MW | 28.28 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 957432 | AF2-037 E | 50/50 | 18.86 MW | 18.86 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 957691 | AF2-063 C | 50/50 | 45.13 MW | 45.13 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 957692 | AF2-063 E | 50/50 | 30.09 MW | 30.09 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 962491 | AG1-098 C | Adder | 9.31 MW | 7.91 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 962492 | AG1-098 E | Adder | 6.2 MW | 5.27 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 962561 | AG1-105 C | Adder | 7.21 MW | 6.12 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 962562 | AG1-105 E | Adder | 4.8 MW | 4.08 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 962841 | AG1-133 C | 50/50 | 57.38 MW | 57.38 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 962842 | AG1-133 E | 50/50 | 38.25 MW | 38.25 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 963291 | AG1-178 C | Adder | 60.23 MW | 51.2 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 963311 | AG1-180 C | Adder | 2.27 MW | 1.93 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 963321 | AG1-181 C | Adder | 13.66 MW | 11.61 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 963351 | AG1-184 C | Adder | 32.45 MW | 27.58 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 963361 | AG1-185 C | Adder | 6.61 MW | 5.62 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 964241 | AG1-285 C | Adder | 10.19 MW | 8.66 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 964242 | AG1-285 E | Adder | 6.79 MW | 5.77 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 964421 | AG1-305 C | 50/50 | 35.51 MW | 35.51 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 964422 | AG1-305 E | 50/50 | 23.67 MW | 23.67 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 965601 | AG1-428 C | Adder | 3.9 MW | 3.31 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 965602 | AG1-428 E | Adder | 2.6 MW | 2.21 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 965771 | AG1-445 C | Adder | 3.54 MW | 3.0 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 965781 | AG1-446 C | Adder | 3.54 MW | 3.0 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 965811 | AG1-449 C | Adder | 22.6 MW | 19.21 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 313764 | 3SOCKMAN | Adder | 0.57 MW | 0.48 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 934612 | AD1-087 E | Adder | 3.24 MW | 2.75 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 935172 | AD1-152 E | Adder | 4.75 MW | 4.04 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 937482 | AD2-202 E | Adder | 0.95 MW | 0.81 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 940481 | AE2-033 C | Adder | 13.48 MW | 11.46 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 940482 | AE2-033 E | Adder | 9.09 MW | 7.72 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 940541 | AE2-040 C | Adder | 2.4 MW | 2.04 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 940641 | AE2-051 C | Adder | 16.48 MW | 14.01 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 940642 | AE2-051 E | Adder | 10.99 MW | 9.34 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 945811 | AF1-246 C | Adder | 6.89 MW | 5.86 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 945812 | AF1-246 E | Adder | 9.52 MW | 8.09 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 316303 | AF2-085 | 50/50 | 4.01 MW | 4.01 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 19.77 MW | 19.77 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 16.72 MW | 16.72 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 76.98 MW | 76.98 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 5.07 MW | 5.07 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | NY | PJM->LTFIMP_NY | CLTF | 2.38 MW | 2.38 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.86 MW | 0.86 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | WEC | LTFEXP_WEC->PJM | CLTF | 0.43 MW | 0.43 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | CPLE | LTFEXP_CPLE->PJM | CLTF | 9.24 MW | 9.24 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | TVA | LTFEXP_TVA->PJM | CLTF | 4.7 MW | 4.7 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | MEC | LTFEXP_MEC->PJM | CLTF | 2.76 MW | 2.76 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | LAGN | LTFEXP_LAGN->PJM | CLTF | 5.93 MW | 5.93 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.17 MW | 0.17 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 32.27 MW | 32.27 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 4.4 MW | 4.4 MW |
| Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 963041 | AG1-153 C | 50/50 | 9.26 MW | 9.26 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 963042 | AG1-153 E | 50/50 | 13.89 MW | 13.89 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 963111 | AG1-160 C | 50/50 | 9.38 MW | 9.38 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 963112 | AG1-160 E | 50/50 | 14.06 MW | 14.06 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 966361 | AG1-505 C | 50/50 | 27.52 MW | 27.52 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 966362 | AG1-505 E | 50/50 | 18.35 MW | 18.35 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 966371 | AG1-506 C | 50/50 | 27.52 MW | 27.52 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 966372 | AG1-506 E | 50/50 | 18.35 MW | 18.35 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 942931 | AE2-313 C | 50/50 | 59.96 MW | 59.96 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 942932 | AE2-313 E | 50/50 | 39.98 MW | 39.98 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 944011 | AF1-069 C | 50/50 | 21.75 MW | 21.75 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 944012 | AF1-069 E | 50/50 | 8.45 MW | 8.45 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 941031 | AE2-094 C | 50/50 | 66.58 MW | 66.58 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 941032 | AE2-094 E | 50/50 | 29.82 MW | 29.82 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 314295 | 6BIRDNECK | 50/50 | 0.06 MW | 0.06 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 314507 | 3THOMPSN | Adder | 3.31 MW | 2.81 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 314550 | 6HICKORY | Adder | 3.57 MW | 3.04 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 926662 | AC1-147 E | Adder | 2.17 MW | 1.85 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 926755 | AC1-161 E | 50/50 | 21.53 MW | 21.53 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 315102 | 1BRUNSWICKG1 | 50/50 | 11.54 MW | 11.54 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 315103 | 1BRUNSWICKG2 | 50/50 | 11.54 MW | 11.54 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 315104 | 1BRUNSWICKG3 | 50/50 | 11.54 MW | 11.54 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 315105 | 1BRUNSWICKS1 | 50/50 | 23.97 MW | 23.97 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 315108 | 1ELIZAR1 | 50/50 | 4.43 MW | 4.43 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 315109 | 1ELIZAR2 | 50/50 | 4.36 MW | 4.36 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 315110 | 1ELIZAR3 | 50/50 | 4.49 MW | 4.49 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 315241 | 1Z1-086 GT1 | 50/50 | 14.77 MW | 14.77 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 315242 | 1Z1-086 GT2 | 50/50 | 14.78 MW | 14.78 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 315243 | 1Z1-086 GT3 | 50/50 | 14.78 MW | 14.78 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 315244 | 1Z1-086 ST | 50/50 | 25.72 MW | 25.72 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 315260 | 1GOSPORTA | Adder | 3.49 MW | 2.97 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 315261 | 1GOSPORTB | Adder | 4.46 MW | 3.79 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 315262 | 1GOSPORTC | Adder | 3.78 MW | 3.22 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 916192 | Z1-068 E | 50/50 | 3.08 MW | 3.08 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 923852 | AB2-025 E | Adder | 1.85 MW | 1.57 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 938552 | AE1-074 E | 50/50 | 2.0 MW | 2.0 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 925522 | AC1-027 E | 50/50 | 2.0 MW | 2.0 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 957871 | AF2-081 C | Adder | 16.36 MW | 13.9 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 957872 | AF2-081 E | Adder | 7.01 MW | 5.96 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 933291 | AC2-141 C | 50/50 | 50.43 MW | 50.43 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 933292 | AC2-141 E | 50/50 | 21.53 MW | 21.53 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 939411 | AE1-173 C | 50/50 | 153.01 MW | 153.01 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 939412 | AE1-173 E | 50/50 | 102.01 MW | 102.01 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 316185 | AD1-033 C | 50/50 | 1.7 MW | 1.7 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 316233 | AE1-074 C | 50/50 | 3.98 MW | 3.98 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 316294 | AC1-161 C | 50/50 | 6.96 MW | 6.96 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 316316 | AC1-027 C | 50/50 | 0.44 MW | 0.44 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 934065 | AD1-033 E | 50/50 | 8.23 MW | 8.23 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 937226 | AE2-253 E | Adder | 9.57 MW | 8.13 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 919153 | AA1-139 E2 | Adder | 6.69 MW | 5.68 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 919152 | AA1-139 E1 | Adder | 6.69 MW | 5.68 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 932046 | AC2-012 E | Adder | 21.48 MW | 18.26 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 941291 | AE2-123 C | 50/50 | 47.95 MW | 47.95 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 941292 | AE2-123 E | 50/50 | 187.0 MW | 187.0 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 941301 | AE2-124 C | 50/50 | 43.61 MW | 43.61 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 941302 | AE2-124 E | 50/50 | 191.36 MW | 191.36 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 941591 | AE2-156 C | Adder | 29.36 MW | 24.95 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 944581 | AF1-123 C | 50/50 | 79.22 MW | 79.22 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 944582 | AF1-123 E | 50/50 | 181.38 MW | 181.38 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 944591 | AF1-124 C | 50/50 | 79.22 MW | 79.22 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 944592 | AF1-124 E | 50/50 | 181.38 MW | 181.38 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 944601 | AF1-125 C | 50/50 | 79.22 MW | 79.22 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 944602 | AF1-125 E | 50/50 | 181.38 MW | 181.38 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 963291 | AG1-178 C | 50/50 | 106.46 MW | 106.46 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 963351 | AG1-184 C | 50/50 | 57.35 MW | 57.35 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 964951 | AG1-359 C | 50/50 | 37.48 MW | 37.48 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 965001 | AG1-364 C | Adder | 11.74 MW | 9.98 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 965002 | AG1-364 E | Adder | 17.61 MW | 14.97 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 965811 | AG1-449 C | 50/50 | 38.83 MW | 38.83 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 938531 | AE1-072 C | Adder | 28.74 MW | 24.43 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 938532 | AE1-072 E | Adder | 8.11 MW | 6.89 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 940541 | AE2-040 C | Adder | 4.58 MW | 3.89 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 940641 | AE2-051 C | 50/50 | 29.42 MW | 29.42 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 940642 | AE2-051 E | 50/50 | 19.62 MW | 19.62 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 941281 | AE2-122 C | 50/50 | 46.66 MW | 46.66 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 941282 | AE2-122 E | 50/50 | 188.29 MW | 188.29 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 316303 | AF2-085 | 50/50 | 6.56 MW | 6.56 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 64.57 MW | 64.57 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 40.64 MW | 40.64 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 149.88 MW | 149.88 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 7.08 MW | 7.08 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | NY | PJM->LTFIMP_NY | CLTF | 3.23 MW | 3.23 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | LGEE | LTFEXP_LGEE->PJM | CLTF | 2.57 MW | 2.57 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | WEC | LTFEXP_WEC->PJM | CLTF | 1.33 MW | 1.33 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | CPLE | LTFEXP_CPLE->PJM | CLTF | 17.46 MW | 17.46 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | TVA | LTFEXP_TVA->PJM | CLTF | 10.63 MW | 10.63 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | MEC | LTFEXP_MEC->PJM | CLTF | 7.63 MW | 7.63 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | LAGN | LTFEXP_LAGN->PJM | CLTF | 13.37 MW | 13.37 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.48 MW | 0.48 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 45.05 MW | 45.05 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 8.33 MW | 8.33 MW |
| Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 963041 | AG1-153 C | 50/50 | 9.88 MW | 9.88 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 963042 | AG1-153 E | 50/50 | 14.81 MW | 14.81 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 963111 | AG1-160 C | 50/50 | 10.03 MW | 10.03 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 963112 | AG1-160 E | 50/50 | 15.04 MW | 15.04 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 966361 | AG1-505 C | 50/50 | 29.01 MW | 29.01 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 966362 | AG1-505 E | 50/50 | 19.34 MW | 19.34 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 966371 | AG1-506 C | 50/50 | 29.01 MW | 29.01 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 966372 | AG1-506 E | 50/50 | 19.34 MW | 19.34 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 315153 | 1CLOVER1 | 50/50 | 16.64 MW | 16.64 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 315154 | 1CLOVER2 | 50/50 | 16.49 MW | 16.49 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 942931 | AE2-313 C | 50/50 | 64.2 MW | 64.2 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 942932 | AE2-313 E | 50/50 | 42.8 MW | 42.8 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 944011 | AF1-069 C | 50/50 | 23.41 MW | 23.41 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 944012 | AF1-069 E | 50/50 | 9.09 MW | 9.09 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 941031 | AE2-094 C | 50/50 | 71.64 MW | 71.64 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 941032 | AE2-094 E | 50/50 | 32.09 MW | 32.09 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 957481 | AF2-042 C | 50/50 | 86.19 MW | 86.19 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 957482 | AF2-042 E | 50/50 | 57.46 MW | 57.46 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 314295 | 6BIRDNECK | 50/50 | 0.06 MW | 0.06 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 314550 | 6HICKORY | 50/50 | 3.35 MW | 3.35 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 926755 | AC1-161 E | 50/50 | 20.58 MW | 20.58 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 315102 | 1BRUNSWICKG1 | 50/50 | 12.3 MW | 12.3 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 315103 | 1BRUNSWICKG2 | 50/50 | 12.3 MW | 12.3 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 315104 | 1BRUNSWICKG3 | 50/50 | 12.3 MW | 12.3 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 315105 | 1BRUNSWICKS1 | 50/50 | 25.56 MW | 25.56 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 315108 | 1ELIZAR1 | 50/50 | 4.12 MW | 4.12 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 315110 | 1ELIZAR3 | 50/50 | 4.17 MW | 4.17 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 315241 | 1Z1-086 GT1 | 50/50 | 15.8 MW | 15.8 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 315242 | 1Z1-086 GT2 | 50/50 | 15.81 MW | 15.81 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 315243 | 1Z1-086 GT3 | 50/50 | 15.81 MW | 15.81 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 315244 | 1Z1-086 ST | 50/50 | 27.51 MW | 27.51 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 916192 | Z1-068 E | 50/50 | 2.87 MW | 2.87 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 925522 | AC1-027 E | 50/50 | 1.86 MW | 1.86 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 957871 | AF2-081 C | 50/50 | 15.3 MW | 15.3 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 957872 | AF2-081 E | 50/50 | 6.56 MW | 6.56 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 933291 | AC2-141 C | 50/50 | 48.21 MW | 48.21 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 933292 | AC2-141 E | 50/50 | 20.58 MW | 20.58 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 939411 | AE1-173 C | 50/50 | 158.19 MW | 158.19 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 939412 | AE1-173 E | 50/50 | 105.46 MW | 105.46 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 316185 | AD1-033 C | 50/50 | 1.59 MW | 1.59 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 316294 | AC1-161 C | 50/50 | 6.65 MW | 6.65 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 316316 | AC1-027 C | 50/50 | 0.41 MW | 0.41 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 934065 | AD1-033 E | 50/50 | 7.7 MW | 7.7 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 937226 | AE2-253 E | 50/50 | 8.95 MW | 8.95 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 316017 | AA1-139 ULT1 | 50/50 | 1.4 MW | 1.4 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 316018 | AA1-139 ULT2 | 50/50 | 1.4 MW | 1.4 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 919153 | AA1-139 E2 | 50/50 | 6.26 MW | 6.26 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 919152 | AA1-139 E1 | 50/50 | 6.26 MW | 6.26 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 316388 | AE2-253 GEN | 50/50 | 2.54 MW | 2.54 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 941291 | AE2-123 C | 50/50 | 44.7 MW | 44.7 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 941292 | AE2-123 E | 50/50 | 174.33 MW | 174.33 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 941301 | AE2-124 C | 50/50 | 40.68 MW | 40.68 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 941302 | AE2-124 E | 50/50 | 178.49 MW | 178.49 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 944581 | AF1-123 C | 50/50 | 74.73 MW | 74.73 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 944582 | AF1-123 E | 50/50 | 171.1 MW | 171.1 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 944591 | AF1-124 C | 50/50 | 74.73 MW | 74.73 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 944592 | AF1-124 E | 50/50 | 171.1 MW | 171.1 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 944601 | AF1-125 C | 50/50 | 74.73 MW | 74.73 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 944602 | AF1-125 E | 50/50 | 171.1 MW | 171.1 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 963291 | AG1-178 C | 50/50 | 113.44 MW | 113.44 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 963351 | AG1-184 C | 50/50 | 61.11 MW | 61.11 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 964951 | AG1-359 C | 50/50 | 35.09 MW | 35.09 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 965811 | AG1-449 C | 50/50 | 41.57 MW | 41.57 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 934611 | AD1-087 C | 50/50 | 1.64 MW | 1.64 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 934612 | AD1-087 E | 50/50 | 5.6 MW | 5.6 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 937481 | AD2-202 C | 50/50 | 0.47 MW | 0.47 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 937482 | AD2-202 E | 50/50 | 1.64 MW | 1.64 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 940641 | AE2-051 C | 50/50 | 31.26 MW | 31.26 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 940642 | AE2-051 E | 50/50 | 20.84 MW | 20.84 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 941281 | AE2-122 C | 50/50 | 43.5 MW | 43.5 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 941282 | AE2-122 E | 50/50 | 175.53 MW | 175.53 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 945811 | AF1-246 C | 50/50 | 12.07 MW | 12.07 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | 945812 | AF1-246 E | 50/50 | 16.66 MW | 16.66 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 54.12 MW | 54.12 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 35.97 MW | 35.97 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 143.46 MW | 143.46 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 5.7 MW | 5.7 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | NY | PJM->LTFIMP_NY | CLTF | 2.62 MW | 2.62 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | LGEE | LTFEXP_LGEE->PJM | CLTF | 2.15 MW | 2.15 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | WEC | LTFEXP_WEC->PJM | CLTF | 1.12 MW | 1.12 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | CPLE | LTFEXP_CPLE->PJM | CLTF | 17.02 MW | 17.02 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | TVA | LTFEXP_TVA->PJM | CLTF | 9.55 MW | 9.55 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | MEC | LTFEXP_MEC->PJM | CLTF | 6.56 MW | 6.56 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | LAGN | LTFEXP_LAGN->PJM | CLTF | 12.08 MW | 12.08 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.41 MW | 0.41 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 36.3 MW | 36.3 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 8.12 MW | 8.12 MW |
| Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 934521 | AD1-076 C | Adder | 16.96 MW | 14.41 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 934522 | AD1-076 E | Adder | 8.64 MW | 7.35 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 942931 | AE2-313 C | Adder | 43.93 MW | 37.34 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 942932 | AE2-313 E | Adder | 5.26 MW | 4.47 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 944011 | AF1-069 C | Adder | 16.01 MW | 13.61 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 944012 | AF1-069 E | Adder | 6.22 MW | 5.29 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 940492 | AE2-034 E | Adder | 4.41 MW | 3.75 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 941031 | AE2-094 C | Adder | 48.99 MW | 41.64 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 941032 | AE2-094 E | Adder | 21.94 MW | 18.65 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 957531 | AF2-047 C | Adder | 24.44 MW | 20.77 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 957532 | AF2-047 E | Adder | 12.29 MW | 10.45 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 314539 | 3UNCAMP | Adder | 8.34 MW | 7.09 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 916042 | Z1-036 E | Adder | 43.1 MW | 36.63 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 938771 | AE1-103 C | Adder | 4.07 MW | 3.46 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 938772 | AE1-103 E | Adder | 5.62 MW | 4.78 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 314295 | 6BIRDNECK | 50/50 | 0.06 MW | 0.06 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 314507 | 3THOMPSN | Adder | 3.23 MW | 2.75 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 314525 | 6KINGFORK | Adder | 1.49 MW | 1.27 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 314550 | 6HICKORY | 50/50 | 3.54 MW | 3.54 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 926662 | AC1-147 E | Adder | 2.12 MW | 1.8 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 926755 | AC1-161 E | 50/50 | 24.43 MW | 24.43 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 935112 | AD1-144 E | Adder | 1.39 MW | 1.18 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 943612 | AF1-032 E | Adder | 1.44 MW | 1.22 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 944871 | AF1-152 C | Adder | 8.12 MW | 6.9 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 944872 | AF1-152 E | Adder | 5.41 MW | 4.6 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 315099 | 1CHESPKB | 50/50 | 0.98 MW | 0.98 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 315108 | 1ELIZAR1 | 50/50 | 4.36 MW | 4.36 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 315109 | 1ELIZAR2 | 50/50 | 4.28 MW | 4.28 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 315110 | 1ELIZAR3 | 50/50 | 4.42 MW | 4.42 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 315233 | 1SURRY 2 | 50/50 | 44.22 MW | 44.22 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 315260 | 1GOSPORTA | Adder | 3.41 MW | 2.9 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 315261 | 1GOSPORTB | Adder | 4.36 MW | 3.7 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 315262 | 1GOSPORTC | Adder | 3.7 MW | 3.14 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 315611 | 6Z1-036WIND | Adder | 10.22 MW | 8.69 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 913392 | Y1-086 E | Adder | 3.46 MW | 2.94 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 916192 | Z1-068 E | 50/50 | 3.04 MW | 3.04 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 923832 | AB2-022 E | Adder | 1.95 MW | 1.66 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 939312 | AE1-162 E | Adder | 1.89 MW | 1.61 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 957492 | AF2-043 E | Adder | 2.21 MW | 1.88 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 901082 | W1-029 E | Adder | 48.99 MW | 41.64 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 917122 | Z2-027 E | Adder | 2.1 MW | 1.78 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 925522 | AC1-027 E | 50/50 | 1.97 MW | 1.97 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 941501 | AE2-147 C | Adder | 24.36 MW | 20.71 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 941502 | AE2-147 E | Adder | 16.24 MW | 13.8 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 957871 | AF2-081 C | 50/50 | 16.07 MW | 16.07 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 957872 | AF2-081 E | 50/50 | 6.89 MW | 6.89 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 958161 | AF2-110 C | Adder | 2.01 MW | 1.71 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 958162 | AF2-110 E | Adder | 3.2 MW | 2.72 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 933291 | AC2-141 C | 50/50 | 57.23 MW | 57.23 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 933292 | AC2-141 E | 50/50 | 24.43 MW | 24.43 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 939411 | AE1-173 C | Adder | 130.32 MW | 110.78 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 939412 | AE1-173 E | Adder | 86.88 MW | 73.85 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 314594 | 6PLYMOUTH TP | Adder | 0.45 MW | 0.38 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 314632 | 6AYDLETT TAP | Adder | 2.17 MW | 1.84 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 316185 | AD1-033 C | 50/50 | 1.69 MW | 1.69 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 316294 | AC1-161 C | 50/50 | 7.89 MW | 7.89 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 316316 | AC1-027 C | 50/50 | 0.43 MW | 0.43 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 934065 | AD1-033 E | 50/50 | 8.17 MW | 8.17 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 937226 | AE2-253 E | 50/50 | 9.43 MW | 9.43 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 316017 | AA1-139 ULT1 | 50/50 | 1.47 MW | 1.47 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 316018 | AA1-139 ULT2 | 50/50 | 1.47 MW | 1.47 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 919153 | AA1-139 E2 | 50/50 | 6.57 MW | 6.57 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 919152 | AA1-139 E1 | 50/50 | 6.57 MW | 6.57 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 920692 | AA2-178 E | Adder | 5.88 MW | 5.0 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 316375 | AC2-012 C | 50/50 | 1.84 MW | 1.84 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 932046 | AC2-012 E | 50/50 | 21.0 MW | 21.0 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 316311 | AC2-079 C | Adder | 7.56 MW | 6.43 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 932596 | AC2-079 E | Adder | 12.34 MW | 10.49 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 316388 | AE2-253 GEN | 50/50 | 2.68 MW | 2.68 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 941291 | AE2-123 C | 50/50 | 47.28 MW | 47.28 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 941292 | AE2-123 E | 50/50 | 184.38 MW | 184.38 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 941301 | AE2-124 C | 50/50 | 43.04 MW | 43.04 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 941302 | AE2-124 E | 50/50 | 188.84 MW | 188.84 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 941591 | AE2-156 C | 50/50 | 28.77 MW | 28.77 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 944581 | AF1-123 C | 50/50 | 80.65 MW | 80.65 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 944582 | AF1-123 E | 50/50 | 184.66 MW | 184.66 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 944591 | AF1-124 C | 50/50 | 80.65 MW | 80.65 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 944592 | AF1-124 E | 50/50 | 184.66 MW | 184.66 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 944601 | AF1-125 C | 50/50 | 80.65 MW | 80.65 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 944602 | AF1-125 E | 50/50 | 184.66 MW | 184.66 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 963291 | AG1-178 C | Adder | 83.2 MW | 70.72 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 963351 | AG1-184 C | Adder | 44.82 MW | 38.1 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 964951 | AG1-359 C | 50/50 | 37.25 MW | 37.25 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 965001 | AG1-364 C | 50/50 | 11.5 MW | 11.5 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 965002 | AG1-364 E | 50/50 | 17.25 MW | 17.25 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 934501 | AD1-074 C | Adder | 46.69 MW | 39.69 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 934502 | AD1-074 E | Adder | 23.77 MW | 20.2 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 934511 | AD1-075 C | Adder | 11.67 MW | 9.92 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 934512 | AD1-075 E | Adder | 5.94 MW | 5.05 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 938531 | AE1-072 C | Adder | 28.14 MW | 23.92 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 938532 | AE1-072 E | Adder | 14.67 MW | 12.47 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 940641 | AE2-051 C | Adder | 23.74 MW | 20.18 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 940642 | AE2-051 E | Adder | 15.83 MW | 13.46 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 941101 | AE2-104 C | Adder | 4.93 MW | 4.19 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 941102 | AE2-104 E | Adder | 7.83 MW | 6.66 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 941281 | AE2-122 C | 50/50 | 46.01 MW | 46.01 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | 941282 | AE2-122 E | 50/50 | 185.66 MW | 185.66 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 28.65 MW | 28.65 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 21.57 MW | 21.57 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 97.84 MW | 97.84 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 3.49 MW | 3.49 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | NY | PJM->LTFIMP_NY | CLTF | 1.64 MW | 1.64 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | LGEE | LTFEXP_LGEE->PJM | CLTF | 1.15 MW | 1.15 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | WEC | LTFEXP_WEC->PJM | CLTF | 0.6 MW | 0.6 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | CPLE | LTFEXP_CPLE->PJM | CLTF | 11.99 MW | 11.99 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | TVA | LTFEXP_TVA->PJM | CLTF | 5.91 MW | 5.91 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | MEC | LTFEXP_MEC->PJM | CLTF | 3.7 MW | 3.7 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | LAGN | LTFEXP_LAGN->PJM | CLTF | 7.53 MW | 7.53 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.23 MW | 0.23 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 22.22 MW | 22.22 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576_SRT-S | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 5.72 MW | 5.72 MW |
| Details for 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 314250 | 6ROCKVILLE | Adder | 1.27 MW | 1.08 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 314314 | 3LOCKS | Adder | 1.12 MW | 0.95 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 314331 | 6POE | Adder | 0.84 MW | 0.71 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 315021 | 1REMNGT1 | 50/50 | 3.55 MW | 3.55 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 315022 | 1REMNGT2 | 50/50 | 3.59 MW | 3.59 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 315023 | 1REMNGT3 | 50/50 | 4.04 MW | 4.04 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 315024 | 1REMNGT4 | 50/50 | 3.6 MW | 3.6 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 315028 | 1M RUN A | 50/50 | 4.01 MW | 4.01 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 315029 | 1M RUN B | 50/50 | 3.98 MW | 3.98 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 315030 | 1M RUN C | 50/50 | 4.0 MW | 4.0 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 315060 | 1CHESTF5 | Adder | 39.36 MW | 33.45 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 315065 | 1CHESTF6 | Adder | 12.24 MW | 10.4 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 315073 | 1STONECA | Adder | 4.3 MW | 3.65 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 315083 | 1SPRUNCA | Adder | 5.72 MW | 4.87 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 315084 | 1SPRUNCB | Adder | 5.72 MW | 4.87 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 315092 | 1YORKTN3 | Adder | 87.06 MW | 74.0 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 926412 | AC1-112 E | Adder | 0.69 MW | 0.59 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 926755 | AC1-161 E | Adder | 7.97 MW | 6.78 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 927226 | AC1-216 E | Adder | 4.79 MW | 4.07 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 934861 | AD1-115 C | 50/50 | 3.22 MW | 3.22 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 934862 | AD1-115 E | 50/50 | 5.25 MW | 5.25 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 942152 | AE2-227 E | Adder | 0.91 MW | 0.77 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 942162 | AE2-228 E | Adder | 0.9 MW | 0.76 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 960091 | AF2-300 C | Adder | 1.35 MW | 1.15 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 960092 | AF2-300 E | Adder | 0.9 MW | 0.76 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 966681 | AG1-538 C | Adder | 5.25 MW | 4.46 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 966682 | AG1-538 E | Adder | 7.06 MW | 6.0 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 966871 | AG1-558 C | Adder | 1.48 MW | 1.26 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 966872 | AG1-558 E | Adder | 0.74 MW | 0.63 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 966881 | AG1-559 C | Adder | 1.49 MW | 1.27 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 966882 | AG1-559 E | Adder | 0.75 MW | 0.64 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 316076 | AC2-137 E | Adder | 0.82 MW | 0.7 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 316108 | AB2-160 C | Adder | 3.4 MW | 2.89 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 316109 | AB2-160 E | Adder | 5.54 MW | 4.71 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 925022 | AB2-158 E | Adder | 4.19 MW | 3.56 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 930122 | AB1-027 E | Adder | 0.85 MW | 0.72 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 938552 | AE1-074 E | Adder | 0.78 MW | 0.66 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 939312 | AE1-162 E | Adder | 0.88 MW | 0.75 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 946262 | AF1-291 E | Adder | 0.9 MW | 0.76 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 946371 | AF1-301 C | Adder | 10.51 MW | 8.94 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 946372 | AF1-301 E | Adder | 7.06 MW | 6.0 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 957411 | AF2-035 C | Adder | 5.39 MW | 4.58 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 957412 | AF2-035 E | Adder | 2.7 MW | 2.29 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 962962 | AG1-145 E | Adder | 0.89 MW | 0.76 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 963031 | AG1-152 C | 50/50 | 6.89 MW | 6.89 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 963032 | AG1-152 E | 50/50 | 10.33 MW | 10.33 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 963051 | AG1-154 C | Adder | 2.23 MW | 1.9 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 963052 | AG1-154 E | Adder | 3.35 MW | 2.84 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 964271 | AG1-288 C | 50/50 | 17.19 MW | 17.19 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 966001 | AG1-469 C | Adder | 1.41 MW | 1.2 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 966002 | AG1-469 E | Adder | 0.71 MW | 0.6 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 925332 | AB2-190 E | Adder | 5.02 MW | 4.26 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 925672 | AC1-043 E | 50/50 | 10.51 MW | 10.51 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 942001 | AE2-212 C | Adder | 1.34 MW | 1.14 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 942002 | AE2-212 E | Adder | 0.89 MW | 0.76 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 966331 | AG1-502 C | 50/50 | 10.77 MW | 10.77 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 966332 | AG1-502 E | 50/50 | 2.69 MW | 2.69 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 966341 | AG1-503 C | 50/50 | 2.69 MW | 2.69 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 966342 | AG1-503 E | 50/50 | 0.67 MW | 0.67 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 313811 | 6ELKO L286 | Adder | 0.86 MW | 0.73 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 933291 | AC2-141 C | Adder | 18.67 MW | 15.87 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 933292 | AC2-141 E | Adder | 7.97 MW | 6.78 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 939411 | AE1-173 C | Adder | 53.23 MW | 45.25 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 939412 | AE1-173 E | Adder | 35.49 MW | 30.17 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 923892 | AB2-029 E | 50/50 | 2.1 MW | 2.1 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 934011 | AD1-025 C | Adder | 10.47 MW | 8.9 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 934012 | AD1-025 E | Adder | 6.2 MW | 5.27 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 927041 | AC1-191 C | Adder | 5.94 MW | 5.05 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 927042 | AC1-191 E | Adder | 2.96 MW | 2.52 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 316160 | AE1-175 E | Adder | 0.73 MW | 0.62 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 316164 | AC1-076_C | 50/50 | 0.57 MW | 0.57 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 316170 | AC1-121 C | 50/50 | 2.29 MW | 2.29 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 316233 | AE1-074 C | Adder | 1.55 MW | 1.32 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 316240 | AF1-291 C | Adder | 1.34 MW | 1.14 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 316254 | AC1-120 C | 50/50 | 6.68 MW | 6.68 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 316257 | AC1-043 C | 50/50 | 6.44 MW | 6.44 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 316301 | AE2-228 C | Adder | 1.34 MW | 1.14 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 316304 | AE2-227 C | Adder | 1.36 MW | 1.16 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 926785 | AC1-164_E | Adder | 11.11 MW | 9.45 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 963221 | AG1-171 C | Adder | 1.33 MW | 1.13 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 963222 | AG1-171 E | Adder | 0.89 MW | 0.76 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 963231 | AG1-172 C | Adder | 1.33 MW | 1.13 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 963232 | AG1-172 E | Adder | 0.89 MW | 0.76 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 963241 | AG1-173 C | Adder | 1.33 MW | 1.13 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 963242 | AG1-173 E | Adder | 0.89 MW | 0.76 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 963251 | AG1-174 C | Adder | 1.33 MW | 1.13 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 963252 | AG1-174 E | Adder | 0.89 MW | 0.76 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 926004 | AC1-076_E | 50/50 | 3.85 MW | 3.85 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 926486 | AC1-120 E | 50/50 | 3.44 MW | 3.44 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 926502 | AC1-121 E | 50/50 | 1.08 MW | 1.08 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 926615 | AC1-143 E | 50/50 | 3.23 MW | 3.23 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 316006 | AB2-029 C | 50/50 | 0.18 MW | 0.18 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 316267 | AC1-143 C | 50/50 | 7.07 MW | 7.07 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 316427 | AG1-213 C | Adder | 0.45 MW | 0.38 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 316411 | AF1-147_GEN1 | Adder | -4.37 MW | -3.71 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 316415 | AF1-147_GEN2 | Adder | -4.37 MW | -3.71 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 924814 | AB2-134 E | Adder | 7.85 MW | 6.67 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 316044 | AC1-158 C1 | 50/50 | 4.8 MW | 4.8 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 316045 | AC1-158 C2 | 50/50 | 4.8 MW | 4.8 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 926739 | AC1-158 E1 | 50/50 | 14.74 MW | 14.74 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 926740 | AC1-158 E2 | 50/50 | 14.74 MW | 14.74 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 961611 | AG1-000B C | Adder | 9.86 MW | 8.38 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 942371 | AE2-250 C | Adder | 6.03 MW | 5.13 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 942372 | AE2-250 E | Adder | 3.18 MW | 2.71 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 942551 | AE2-270 C | Adder | 16.68 MW | 14.18 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 944582 | AF1-123 E | Adder | 67.42 MW | 57.31 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 944591 | AF1-124 C | Adder | 29.45 MW | 25.03 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 944592 | AF1-124 E | Adder | 67.42 MW | 57.31 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 944601 | AF1-125 C | Adder | 26.71 MW | 22.7 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 944602 | AF1-125 E | Adder | 67.42 MW | 57.31 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 944631 | AF1-128 C | Adder | 24.62 MW | 20.93 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 957431 | AF2-037 C | Adder | 8.83 MW | 7.51 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 957432 | AF2-037 E | Adder | 5.89 MW | 5.0 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 957691 | AF2-063 C | Adder | 14.09 MW | 11.98 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 957692 | AF2-063 E | Adder | 9.39 MW | 7.99 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 957711 | AF2-065 C | Adder | 8.5 MW | 7.23 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 957712 | AF2-065 E | Adder | 8.17 MW | 6.95 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 961711 | AG1-011 C | Adder | 17.79 MW | 15.12 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 962271 | AG1-075 C | Adder | 10.41 MW | 8.85 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 962272 | AG1-075 E | Adder | 6.34 MW | 5.39 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 962841 | AG1-133 C | Adder | 11.75 MW | 9.99 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 962842 | AG1-133 E | Adder | 7.83 MW | 6.66 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 963291 | AG1-178 C | Adder | 36.13 MW | 30.71 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 963351 | AG1-184 C | Adder | 19.47 MW | 16.55 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 964281 | AG1-289 C | 50/50 | 9.5 MW | 9.5 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 964421 | AG1-305 C | Adder | 11.08 MW | 9.42 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 964422 | AG1-305 E | Adder | 7.39 MW | 6.28 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 965281 | AG1-393 C | Adder | 1.34 MW | 1.14 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 965282 | AG1-393 E | Adder | 0.89 MW | 0.76 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 966611 | AG1-531 C | Adder | 3.58 MW | 3.05 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 966612 | AG1-531 E | Adder | 2.39 MW | 2.03 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 935161 | AD1-151 C | Adder | 10.02 MW | 8.52 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 935162 | AD1-151 E | Adder | 6.68 MW | 5.68 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 938291 | AE1-044 C | 50/50 | 22.06 MW | 22.06 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 938292 | AE1-044 E | 50/50 | 17.41 MW | 17.41 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 939191 | AE1-149 C | Adder | 6.64 MW | 5.64 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 939192 | AE1-149 E | Adder | 4.43 MW | 3.76 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 939221 | AE1-153 C | 50/50 | 14.67 MW | 14.67 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 939222 | AE1-153 E | 50/50 | 9.78 MW | 9.78 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 939261 | AE1-157 C | Adder | 8.72 MW | 7.41 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 939262 | AE1-157 E | Adder | 4.73 MW | 4.02 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 940431 | AE2-027 C | Adder | 8.05 MW | 6.84 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 940432 | AE2-027 E | Adder | 5.37 MW | 4.56 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 940641 | AE2-051 C | Adder | 10.02 MW | 8.52 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 940642 | AE2-051 E | Adder | 6.68 MW | 5.68 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 940651 | AE2-052 C | Adder | 2.21 MW | 1.88 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 942191 | AE2-231 C | Adder | 2.97 MW | 2.52 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 942192 | AE2-231 E | Adder | 1.98 MW | 1.68 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 944641 | AF1-129 C | Adder | 63.84 MW | 54.27 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | 963622 | AG1-213 E | Adder | 0.53 MW | 0.45 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 24.95 MW | 24.95 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 16.05 MW | 16.05 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 56.79 MW | 56.79 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 5.2 MW | 5.2 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | NY | PJM->LTFIMP_NY | CLTF | 2.38 MW | 2.38 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | LGEE | LTFEXP_LGEE->PJM | CLTF | 1.04 MW | 1.04 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | WEC | LTFEXP_WEC->PJM | CLTF | 0.52 MW | 0.52 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | CPLE | LTFEXP_CPLE->PJM | CLTF | 6.46 MW | 6.46 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | TVA | LTFEXP_TVA->PJM | CLTF | 4.22 MW | 4.22 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | MEC | LTFEXP_MEC->PJM | CLTF | 3.01 MW | 3.01 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | LAGN | LTFEXP_LAGN->PJM | CLTF | 5.26 MW | 5.26 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.19 MW | 0.19 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 33.07 MW | 33.07 MW |
| 8MORRSVL-8LOUDOUN 500.0 kV Ckt 1 line l/o DVP_P4-2: 559T584_SRT-S | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 3.08 MW | 3.08 MW |
| Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 963041 | AG1-153 C | 50/50 | 5.93 MW | 5.93 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 963042 | AG1-153 E | 50/50 | 8.9 MW | 8.9 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 963111 | AG1-160 C | 50/50 | 6.01 MW | 6.01 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 963112 | AG1-160 E | 50/50 | 9.01 MW | 9.01 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 966361 | AG1-505 C | 50/50 | 17.68 MW | 17.68 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 966362 | AG1-505 E | 50/50 | 11.79 MW | 11.79 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 966371 | AG1-506 C | 50/50 | 17.68 MW | 17.68 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 966372 | AG1-506 E | 50/50 | 11.79 MW | 11.79 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 942931 | AE2-313 C | 50/50 | 38.48 MW | 38.48 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 942932 | AE2-313 E | 50/50 | 25.65 MW | 25.65 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 944011 | AF1-069 C | 50/50 | 13.95 MW | 13.95 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 944012 | AF1-069 E | 50/50 | 5.42 MW | 5.42 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 941031 | AE2-094 C | 50/50 | 42.7 MW | 42.7 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 941032 | AE2-094 E | 50/50 | 19.12 MW | 19.12 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 957481 | AF2-042 C | Adder | 54.75 MW | 46.54 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 957482 | AF2-042 E | Adder | 36.5 MW | 31.02 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 933502 | AC2-165 E | Adder | 7.58 MW | 6.45 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 314331 | 6POE | Adder | 1.3 MW | 1.11 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 314550 | 6HICKORY | Adder | 2.06 MW | 1.75 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 926755 | AC1-161 E | Adder | 12.22 MW | 10.39 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 958502 | AF2-144 E | Adder | 1.27 MW | 1.08 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 315102 | 1BRUNSWICKG1 | 50/50 | 7.39 MW | 7.39 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 315103 | 1BRUNSWICKG2 | 50/50 | 7.39 MW | 7.39 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 315104 | 1BRUNSWICKG3 | 50/50 | 7.39 MW | 7.39 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 315105 | 1BRUNSWICKS1 | 50/50 | 15.36 MW | 15.36 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 315174 | 1LOISA C | 50/50 | 2.04 MW | 2.04 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 315176 | 1LOISA E | 50/50 | 4.17 MW | 4.17 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 315177 | 1S ANNAG1 | 50/50 | 2.03 MW | 2.03 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 315178 | 1S ANNAS1 | 50/50 | 1.04 MW | 1.04 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 315179 | 1S ANNAG2 | 50/50 | 2.03 MW | 2.03 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 315180 | 1S ANNAS2 | 50/50 | 1.04 MW | 1.04 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 315225 | 1N ANNA1 | 50/50 | 78.94 MW | 78.94 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 315226 | 1N ANNA2 | 50/50 | 78.95 MW | 78.95 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 315241 | 1Z1-086 GT1 | 50/50 | 9.47 MW | 9.47 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 315242 | 1Z1-086 GT2 | 50/50 | 9.47 MW | 9.47 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 315243 | 1Z1-086 GT3 | 50/50 | 9.47 MW | 9.47 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 315244 | 1Z1-086 ST | 50/50 | 16.48 MW | 16.48 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 923852 | AB2-025 E | Adder | 1.15 MW | 0.98 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 923862 | AB2-026 E | Adder | 1.29 MW | 1.09 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 925022 | AB2-158 E | 50/50 | 9.53 MW | 9.53 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 938552 | AE1-074 E | 50/50 | 1.3 MW | 1.3 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 938562 | AE1-075 E | Adder | 1.1 MW | 0.93 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 946371 | AF1-301 C | 50/50 | 16.94 MW | 16.94 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 946372 | AF1-301 E | 50/50 | 11.38 MW | 11.38 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 933291 | AC2-141 C | Adder | 28.63 MW | 24.34 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 933292 | AC2-141 E | Adder | 12.22 MW | 10.39 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 939411 | AE1-173 C | 50/50 | 94.37 MW | 94.37 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 939412 | AE1-173 E | 50/50 | 62.91 MW | 62.91 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 208900 | BRIS G1 | 50/50 | -2.33 MW | -2.33 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 316192 | AB2-158 C | 50/50 | 3.06 MW | 3.06 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 316233 | AE1-074 C | 50/50 | 2.58 MW | 2.58 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 316336 | AC2-165 C | Adder | 10.08 MW | 8.56 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 924516 | AB2-100 E1 | Adder | 2.79 MW | 2.38 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 924517 | AB2-100 E2 | Adder | 2.79 MW | 2.38 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 934065 | AD1-033 E | Adder | 4.73 MW | 4.02 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 941292 | AE2-123 E | Adder | 66.78 MW | 56.76 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 941301 | AE2-124 C | Adder | 25.05 MW | 21.29 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 941302 | AE2-124 E | Adder | 109.92 MW | 93.44 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 944581 | AF1-123 C | Adder | 45.53 MW | 38.7 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 944582 | AF1-123 E | Adder | 104.24 MW | 88.61 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 944591 | AF1-124 C | Adder | 45.53 MW | 38.7 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 944592 | AF1-124 E | Adder | 104.24 MW | 88.61 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 944601 | AF1-125 C | Adder | 45.53 MW | 38.7 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 944602 | AF1-125 E | Adder | 104.24 MW | 88.61 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 946011 | AF1-266 C | Adder | 13.36 MW | 11.36 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 957431 | AF2-037 C | 50/50 | 24.11 MW | 24.11 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 957432 | AF2-037 E | 50/50 | 16.07 MW | 16.07 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 957691 | AF2-063 C | 50/50 | 38.47 MW | 38.47 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 957692 | AF2-063 E | 50/50 | 25.64 MW | 25.64 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 962841 | AG1-133 C | 50/50 | 46.33 MW | 46.33 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 962842 | AG1-133 E | 50/50 | 30.88 MW | 30.88 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 963291 | AG1-178 C | 50/50 | 67.34 MW | 67.34 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 963351 | AG1-184 C | 50/50 | 36.28 MW | 36.28 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 964421 | AG1-305 C | 50/50 | 30.26 MW | 30.26 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 964422 | AG1-305 E | 50/50 | 20.17 MW | 20.17 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 964951 | AG1-359 C | Adder | 21.55 MW | 18.31 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 965811 | AG1-449 C | 50/50 | 24.92 MW | 24.92 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 934612 | AD1-087 E | Adder | 3.61 MW | 3.07 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 937482 | AD2-202 E | Adder | 1.06 MW | 0.9 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 940481 | AE2-033 C | Adder | 15.96 MW | 13.57 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 940482 | AE2-033 E | Adder | 10.76 MW | 9.14 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 940541 | AE2-040 C | Adder | 2.84 MW | 2.41 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 940641 | AE2-051 C | 50/50 | 18.52 MW | 18.52 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 940642 | AE2-051 E | 50/50 | 12.35 MW | 12.35 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 941282 | AE2-122 E | Adder | 108.15 MW | 91.93 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 945811 | AF1-246 C | Adder | 7.66 MW | 6.51 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 945812 | AF1-246 E | Adder | 10.58 MW | 9.0 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | 316303 | AF2-085 | 50/50 | 4.44 MW | 4.44 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 27.81 MW | 27.81 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 21.3 MW | 21.3 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 90.81 MW | 90.81 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 5.58 MW | 5.58 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | NY | PJM->LTFIMP_NY | CLTF | 2.62 MW | 2.62 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | LGEE | LTFEXP_LGEE->PJM | CLTF | 1.19 MW | 1.19 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | WEC | LTFEXP_WEC->PJM | CLTF | 0.59 MW | 0.59 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | CPLE | LTFEXP_CPLE->PJM | CLTF | 10.76 MW | 10.76 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | TVA | LTFEXP_TVA->PJM | CLTF | 5.86 MW | 5.86 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | MEC | LTFEXP_MEC->PJM | CLTF | 3.67 MW | 3.67 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | LAGN | LTFEXP_LAGN->PJM | CLTF | 7.37 MW | 7.37 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.23 MW | 0.23 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 35.54 MW | 35.54 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T575_SRT-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 5.13 MW | 5.13 MW |
| Details for 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 314184 | 3SHACKLE | 50/50 | 0.51 MW | 0.51 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 314314 | 3LOCKS | Adder | 1.13 MW | 0.96 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 314507 | 3THOMPSN | Adder | 1.26 MW | 1.07 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 314525 | 6KINGFORK | Adder | 0.66 MW | 0.56 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 314550 | 6HICKORY | Adder | 1.33 MW | 1.13 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 315060 | 1CHESTF5 | Adder | 62.55 MW | 53.17 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 315073 | 1STONECA | Adder | 5.25 MW | 4.46 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 315092 | 1YORKTN3 | Adder | 121.48 MW | 103.26 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 925865 | AC1-065 E | 50/50 | 19.07 MW | 19.07 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 926412 | AC1-112 E | Adder | 0.97 MW | 0.82 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 926472 | AC1-118 E | Adder | 1.07 MW | 0.91 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 926662 | AC1-147 E | Adder | 0.83 MW | 0.7 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 926755 | AC1-161 E | Adder | 7.86 MW | 6.68 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 927226 | AC1-216 E | Adder | 5.7 MW | 4.84 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 934392 | AD1-063 E | 50/50 | 1.29 MW | 1.29 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 935112 | AD1-144 E | Adder | 0.61 MW | 0.52 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 936582 | AD2-073 E | Adder | 1.14 MW | 0.97 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 936591 | AD2-074 C | 50/50 | 6.29 MW | 6.29 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 936592 | AD2-074 E | 50/50 | 10.27 MW | 10.27 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 942152 | AE2-227 E | Adder | 1.12 MW | 0.95 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 942341 | AE2-247 C | Adder | 0.02 MW | 0.02 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 942342 | AE2-247 E | Adder | 1.25 MW | 1.06 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 943462 | AF1-017 E | Adder | 1.34 MW | 1.14 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 943612 | AF1-032 E | Adder | 0.57 MW | 0.48 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 943741 | AF1-042 C | 50/50 | 3.29 MW | 3.29 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 943742 | AF1-042 E | 50/50 | 5.37 MW | 5.37 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 944491 | AF1-114 C | Adder | 4.97 MW | 4.22 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 944492 | AF1-114 E | Adder | 6.86 MW | 5.83 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 961951 | AG1-038 C | 50/50 | 3.64 MW | 3.64 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 961952 | AG1-038 E | 50/50 | 5.03 MW | 5.03 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 966661 | AG1-536 C | 50/50 | 6.09 MW | 6.09 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 966662 | AG1-536 E | 50/50 | 8.18 MW | 8.18 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 315260 | 1GOSPORTA | Adder | 1.33 MW | 1.13 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 315261 | 1GOSPORTB | Adder | 1.7 MW | 1.44 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 315262 | 1GOSPORTC | Adder | 1.44 MW | 1.22 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 316075 | AC2-137 C | 50/50 | 0.39 MW | 0.39 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 316076 | AC2-137 E | 50/50 | 1.6 MW | 1.6 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 316078 | AC2-138 E | Adder | 1.04 MW | 0.89 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 316108 | AB2-160 C | Adder | 3.43 MW | 2.91 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 316109 | AB2-160 E | Adder | 5.59 MW | 4.75 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 316156 | AD2-030 C | 50/50 | 0.36 MW | 0.36 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 316157 | AD2-030 E | 50/50 | 1.34 MW | 1.34 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 916192 | Z1-068 E | Adder | 1.16 MW | 0.99 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 923842 | AB2-024 E | 50/50 | 2.24 MW | 2.24 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 930122 | AB1-027 E | Adder | 1.19 MW | 1.01 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 939312 | AE1-162 E | Adder | 0.98 MW | 0.83 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 957492 | AF2-043 E | Adder | 0.87 MW | 0.74 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 957601 | AF2-054 C | 50/50 | 2.39 MW | 2.39 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 957602 | AF2-054 E | 50/50 | 1.59 MW | 1.59 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 962531 | AG1-102 C | Adder | 1.09 MW | 0.92 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 962532 | AG1-102 E | Adder | 2.26 MW | 1.92 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 962861 | AG1-135 C | 50/50 | 6.87 MW | 6.87 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 962862 | AG1-135 E | 50/50 | 4.58 MW | 4.58 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 962962 | AG1-145 E | 50/50 | 1.55 MW | 1.55 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 962971 | AG1-146 C | 50/50 | 3.49 MW | 3.49 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 962972 | AG1-146 E | 50/50 | 2.33 MW | 2.33 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 962981 | AG1-147 C | 50/50 | 8.15 MW | 8.15 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 962982 | AG1-147 E | 50/50 | 5.43 MW | 5.43 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 963611 | AG1-210 C | Adder | 0.74 MW | 0.63 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 963612 | AG1-210 E | Adder | 1.12 MW | 0.95 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 964211 | AG1-282 C | 50/50 | 2.33 MW | 2.33 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 964212 | AG1-282 E | 50/50 | 1.55 MW | 1.55 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 925332 | AB2-190 E | Adder | 6.03 MW | 5.12 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 925522 | AC1-027 E | Adder | 0.75 MW | 0.64 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 957831 | AF2-077 C | Adder | 2.12 MW | 1.8 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 957832 | AF2-077 E | Adder | 1.41 MW | 1.2 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 957871 | AF2-081 C | Adder | 6.08 MW | 5.17 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 957872 | AF2-081 E | Adder | 2.6 MW | 2.21 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 957971 | AF2-091 C | Adder | 1.69 MW | 1.44 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 957972 | AF2-091 E | Adder | 2.33 MW | 1.98 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 313811 | 6ELKO L286 | 50/50 | 1.67 MW | 1.67 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 314181 | 3NORNECK | Adder | 0.99 MW | 0.84 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 933291 | AC2-141 C | Adder | 18.42 MW | 15.66 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 933292 | AC2-141 E | Adder | 7.86 MW | 6.68 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 934011 | AD1-025 C | Adder | 12.45 MW | 10.58 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 934012 | AD1-025 E | Adder | 7.37 MW | 6.27 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 313053 | 6PAPERMILL | 50/50 | 8.23 MW | 8.23 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 314632 | 6AYDLETT TAP | Adder | 0.82 MW | 0.7 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 316059 | AD1-063 C | 50/50 | 0.27 MW | 0.27 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 316159 | AE1-175 C | 50/50 | 0.36 MW | 0.36 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 316160 | AE1-175 E | 50/50 | 1.28 MW | 1.28 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 316169 | AC1-164 GEN | 50/50 | 8.29 MW | 8.29 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 316304 | AE2-227 C | Adder | 1.69 MW | 1.43 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 316314 | AB2-024 C | 50/50 | 0.31 MW | 0.31 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 316382 | AG1-145 C | 50/50 | 0.32 MW | 0.32 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 926785 | AC1-164_E | 50/50 | 26.98 MW | 26.98 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 934065 | AD1-033 E | Adder | 3.08 MW | 2.62 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 937226 | AE2-253 E | Adder | 3.56 MW | 3.03 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 939611 | AE1-191 C | 50/50 | 1.31 MW | 1.31 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 939612 | AE1-191 E | 50/50 | 6.48 MW | 6.48 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 963221 | AG1-171 C | Adder | 1.59 MW | 1.35 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 963222 | AG1-171 E | Adder | 1.06 MW | 0.9 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 963231 | AG1-172 C | Adder | 1.59 MW | 1.35 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 963232 | AG1-172 E | Adder | 1.06 MW | 0.9 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 963241 | AG1-173 C | Adder | 1.59 MW | 1.35 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 963242 | AG1-173 E | Adder | 1.06 MW | 0.9 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 963251 | AG1-174 C | Adder | 1.59 MW | 1.35 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 963252 | AG1-174 E | Adder | 1.06 MW | 0.9 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 316201 | AC1-065 C | 50/50 | 11.57 MW | 11.57 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 316404 | AE1-155 C | 50/50 | 2.03 MW | 2.03 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 939246 | AE1-155 E | 50/50 | 9.85 MW | 9.85 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 919153 | AA1-139 E2 | Adder | 2.48 MW | 2.11 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 919152 | AA1-139 E1 | Adder | 2.48 MW | 2.11 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 924814 | AB2-134 E | Adder | 9.33 MW | 7.93 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 316084 | AB2-161 E | Adder | 3.36 MW | 2.86 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 932046 | AC2-012 E | Adder | 8.17 MW | 6.95 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 316280 | AD1-041 C | 50/50 | 0.83 MW | 0.83 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 934146 | AD1-041 E | 50/50 | 4.05 MW | 4.05 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 934576 | AD1-082 E | Adder | 2.68 MW | 2.28 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 316349 | AD2-085 C | Adder | 2.09 MW | 1.78 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 936666 | AD2-085 E | Adder | 3.42 MW | 2.9 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 961611 | AG1-000B C | Adder | 11.52 MW | 9.79 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 941291 | AE2-123 C | Adder | 18.06 MW | 15.35 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 941292 | AE2-123 E | Adder | 70.41 MW | 59.85 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 941301 | AE2-124 C | Adder | 16.4 MW | 13.94 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 941302 | AE2-124 E | Adder | 71.97 MW | 61.17 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 941591 | AE2-156 C | Adder | 11.16 MW | 9.49 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 942371 | AE2-250 C | Adder | 6.09 MW | 5.18 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 942372 | AE2-250 E | Adder | 3.21 MW | 2.73 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 942551 | AE2-270 C | Adder | 19.82 MW | 16.85 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 944581 | AF1-123 C | Adder | 29.25 MW | 24.86 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 944582 | AF1-123 E | Adder | 66.97 MW | 56.93 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 944591 | AF1-124 C | Adder | 29.25 MW | 24.86 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 944592 | AF1-124 E | Adder | 66.97 MW | 56.93 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 944601 | AF1-125 C | Adder | 29.25 MW | 24.86 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 944602 | AF1-125 E | Adder | 66.97 MW | 56.93 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 944631 | AF1-128 C | Adder | 39.14 MW | 33.27 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 945361 | AF1-201 C | Adder | 15.2 MW | 12.92 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 945362 | AF1-201 E | Adder | 10.13 MW | 8.61 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 957711 | AF2-065 C | Adder | 10.11 MW | 8.59 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 957712 | AF2-065 E | Adder | 9.71 MW | 8.26 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 958261 | AF2-120 C | 50/50 | 7.08 MW | 7.08 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 958262 | AF2-120 E | 50/50 | 4.72 MW | 4.72 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 961711 | AG1-011 C | Adder | 21.14 MW | 17.97 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 962271 | AG1-075 C | Adder | 10.51 MW | 8.93 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 962272 | AG1-075 E | Adder | 6.41 MW | 5.45 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 964951 | AG1-359 C | Adder | 13.99 MW | 11.89 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 965001 | AG1-364 C | Adder | 4.46 MW | 3.79 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 965002 | AG1-364 E | Adder | 6.7 MW | 5.69 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 965281 | AG1-393 C | Adder | 1.35 MW | 1.15 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 965282 | AG1-393 E | Adder | 0.9 MW | 0.77 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 966611 | AG1-531 C | Adder | 4.54 MW | 3.86 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 966612 | AG1-531 E | Adder | 3.03 MW | 2.57 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 935161 | AD1-151 C | Adder | 11.98 MW | 10.18 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 935162 | AD1-151 E | Adder | 7.99 MW | 6.79 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 938531 | AE1-072 C | Adder | 10.66 MW | 9.06 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 938532 | AE1-072 E | Adder | 5.56 MW | 4.72 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 939191 | AE1-149 C | Adder | 6.53 MW | 5.55 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 939192 | AE1-149 E | Adder | 4.35 MW | 3.7 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 939601 | AE1-190 C | 50/50 | 2.43 MW | 2.43 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 939602 | AE1-190 E | 50/50 | 1.62 MW | 1.62 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 940431 | AE2-027 C | Adder | 8.25 MW | 7.01 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 940432 | AE2-027 E | Adder | 5.5 MW | 4.68 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 940551 | AE2-041 C | 50/50 | 8.61 MW | 8.61 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 940651 | AE2-052 C | Adder | 2.18 MW | 1.85 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 941281 | AE2-122 C | Adder | 17.57 MW | 14.93 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 941282 | AE2-122 E | Adder | 70.9 MW | 60.26 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | 943471 | AF1-018 C | 50/50 | 8.61 MW | 8.61 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 3.46 MW | 3.46 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 5.07 MW | 5.07 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 31.64 MW | 31.64 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 1.33 MW | 1.33 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | NY | PJM->LTFIMP_NY | CLTF | 0.65 MW | 0.65 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.16 MW | 0.16 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | WEC | LTFEXP_WEC->PJM | CLTF | 0.08 MW | 0.08 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | CPLE | LTFEXP_CPLE->PJM | CLTF | 4.07 MW | 4.07 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | TVA | LTFEXP_TVA->PJM | CLTF | 1.54 MW | 1.54 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | MEC | LTFEXP_MEC->PJM | CLTF | 0.68 MW | 0.68 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | LAGN | LTFEXP_LAGN->PJM | CLTF | 1.99 MW | 1.99 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.04 MW | 0.04 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 8.52 MW | 8.52 MW |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H4T567_SRT-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.94 MW | 1.94 MW |
| Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 963111 | AG1-160 C | Adder | 7.01 MW | 5.96 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 963112 | AG1-160 E | Adder | 10.51 MW | 8.93 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 942931 | AE2-313 C | Adder | 44.86 MW | 38.13 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 942932 | AE2-313 E | Adder | 29.91 MW | 25.42 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 944011 | AF1-069 C | Adder | 16.36 MW | 13.9 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 944012 | AF1-069 E | Adder | 6.35 MW | 5.4 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 940492 | AE2-034 E | Adder | 4.34 MW | 3.69 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 941031 | AE2-094 C | Adder | 50.06 MW | 42.55 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 941032 | AE2-094 E | Adder | 22.42 MW | 19.06 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 957531 | AF2-047 C | Adder | 24.06 MW | 20.45 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 957532 | AF2-047 E | Adder | 12.1 MW | 10.29 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 314539 | 3UNCAMP | Adder | 8.15 MW | 6.93 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 916042 | Z1-036 E | Adder | 42.61 MW | 36.22 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 938771 | AE1-103 C | Adder | 3.98 MW | 3.38 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 938772 | AE1-103 E | Adder | 5.5 MW | 4.67 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 314295 | 6BIRDNECK | 50/50 | 0.06 MW | 0.06 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 314507 | 3THOMPSN | Adder | 3.21 MW | 2.73 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 314525 | 6KINGFORK | Adder | 1.48 MW | 1.26 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 314550 | 6HICKORY | 50/50 | 3.52 MW | 3.52 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 926662 | AC1-147 E | Adder | 2.11 MW | 1.79 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 926755 | AC1-161 E | 50/50 | 24.45 MW | 24.45 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 935112 | AD1-144 E | Adder | 1.37 MW | 1.17 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 943612 | AF1-032 E | Adder | 1.42 MW | 1.21 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 944871 | AF1-152 C | Adder | 8.04 MW | 6.84 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 944872 | AF1-152 E | Adder | 5.36 MW | 4.56 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 315099 | 1CHESPKB | 50/50 | 0.97 MW | 0.97 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 315108 | 1ELIZAR1 | 50/50 | 4.34 MW | 4.34 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 315109 | 1ELIZAR2 | 50/50 | 4.26 MW | 4.26 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 315110 | 1ELIZAR3 | 50/50 | 4.39 MW | 4.39 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 315233 | 1SURRY 2 | 50/50 | 44.11 MW | 44.11 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 315260 | 1GOSPORTA | Adder | 3.39 MW | 2.88 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 315261 | 1GOSPORTB | Adder | 4.33 MW | 3.68 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 315262 | 1GOSPORTC | Adder | 3.68 MW | 3.12 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 315611 | 6Z1-036WIND | Adder | 10.1 MW | 8.59 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 913392 | Y1-086 E | Adder | 3.43 MW | 2.92 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 916192 | Z1-068 E | 50/50 | 3.02 MW | 3.02 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 923832 | AB2-022 E | Adder | 1.94 MW | 1.65 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 939312 | AE1-162 E | Adder | 1.86 MW | 1.58 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 957492 | AF2-043 E | Adder | 2.19 MW | 1.86 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 901082 | W1-029 E | Adder | 48.54 MW | 41.26 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 917122 | Z2-027 E | Adder | 2.08 MW | 1.77 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 925522 | AC1-027 E | 50/50 | 1.96 MW | 1.96 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 941501 | AE2-147 C | Adder | 24.13 MW | 20.51 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 941502 | AE2-147 E | Adder | 16.09 MW | 13.68 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 957871 | AF2-081 C | 50/50 | 15.98 MW | 15.98 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 957872 | AF2-081 E | 50/50 | 6.85 MW | 6.85 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 958161 | AF2-110 C | Adder | 1.98 MW | 1.68 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 958162 | AF2-110 E | Adder | 3.15 MW | 2.68 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 933291 | AC2-141 C | 50/50 | 57.28 MW | 57.28 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 933292 | AC2-141 E | 50/50 | 24.45 MW | 24.45 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 939411 | AE1-173 C | Adder | 131.88 MW | 112.1 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 939412 | AE1-173 E | Adder | 87.92 MW | 74.73 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 314594 | 6PLYMOUTH TP | Adder | 0.44 MW | 0.38 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 314632 | 6AYDLETT TAP | Adder | 2.16 MW | 1.83 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 316185 | AD1-033 C | 50/50 | 1.68 MW | 1.68 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 316294 | AC1-161 C | 50/50 | 7.9 MW | 7.9 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 316316 | AC1-027 C | 50/50 | 0.43 MW | 0.43 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 934065 | AD1-033 E | 50/50 | 8.13 MW | 8.13 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 937226 | AE2-253 E | 50/50 | 9.38 MW | 9.38 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 316017 | AA1-139 ULT1 | 50/50 | 1.46 MW | 1.46 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 316018 | AA1-139 ULT2 | 50/50 | 1.46 MW | 1.46 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 919153 | AA1-139 E2 | 50/50 | 6.53 MW | 6.53 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 919152 | AA1-139 E1 | 50/50 | 6.53 MW | 6.53 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 920692 | AA2-178 E | Adder | 5.78 MW | 4.92 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 316375 | AC2-012 C | 50/50 | 1.83 MW | 1.83 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 932046 | AC2-012 E | 50/50 | 20.88 MW | 20.88 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 316388 | AE2-253 GEN | 50/50 | 2.66 MW | 2.66 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 941291 | AE2-123 C | 50/50 | 47.03 MW | 47.03 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 941292 | AE2-123 E | 50/50 | 183.42 MW | 183.42 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 941301 | AE2-124 C | 50/50 | 42.81 MW | 42.81 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 941302 | AE2-124 E | 50/50 | 187.86 MW | 187.86 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 941591 | AE2-156 C | 50/50 | 28.61 MW | 28.61 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 944581 | AF1-123 C | 50/50 | 80.42 MW | 80.42 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 944582 | AF1-123 E | 50/50 | 184.13 MW | 184.13 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 944591 | AF1-124 C | 50/50 | 80.42 MW | 80.42 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 944592 | AF1-124 E | 50/50 | 184.13 MW | 184.13 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 944601 | AF1-125 C | 50/50 | 80.42 MW | 80.42 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 944602 | AF1-125 E | 50/50 | 184.13 MW | 184.13 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 963291 | AG1-178 C | Adder | 84.76 MW | 72.04 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 963351 | AG1-184 C | Adder | 45.66 MW | 38.81 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 964951 | AG1-359 C | 50/50 | 37.07 MW | 37.07 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 965001 | AG1-364 C | 50/50 | 11.44 MW | 11.44 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 965002 | AG1-364 E | 50/50 | 17.16 MW | 17.16 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 965811 | AG1-449 C | Adder | 29.05 MW | 24.69 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 934501 | AD1-074 C | Adder | 45.83 MW | 38.96 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 934502 | AD1-074 E | Adder | 16.18 MW | 13.75 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 938531 | AE1-072 C | Adder | 27.97 MW | 23.78 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 938532 | AE1-072 E | Adder | 14.58 MW | 12.39 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 940641 | AE2-051 C | Adder | 24.17 MW | 20.55 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 940642 | AE2-051 E | Adder | 16.11 MW | 13.7 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 941101 | AE2-104 C | Adder | 4.85 MW | 4.12 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 941102 | AE2-104 E | Adder | 7.71 MW | 6.56 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 941281 | AE2-122 C | 50/50 | 45.77 MW | 45.77 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | 941282 | AE2-122 E | 50/50 | 184.69 MW | 184.69 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 28.36 MW | 28.36 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 21.42 MW | 21.42 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 97.48 MW | 97.48 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 3.42 MW | 3.42 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | NY | PJM->LTFIMP_NY | CLTF | 1.6 MW | 1.6 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | LGEE | LTFEXP_LGEE->PJM | CLTF | 1.13 MW | 1.13 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | WEC | LTFEXP_WEC->PJM | CLTF | 0.59 MW | 0.59 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | CPLE | LTFEXP_CPLE->PJM | CLTF | 11.94 MW | 11.94 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | TVA | LTFEXP_TVA->PJM | CLTF | 5.87 MW | 5.87 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | MEC | LTFEXP_MEC->PJM | CLTF | 3.67 MW | 3.67 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | LAGN | LTFEXP_LAGN->PJM | CLTF | 7.48 MW | 7.48 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.23 MW | 0.23 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 21.77 MW | 21.77 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 5.69 MW | 5.69 MW |
| Details for 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 961791 | AG1-021 C | Adder | 1.6 MW | 1.36 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 961792 | AG1-021 E | Adder | 1.07 MW | 0.91 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 961891 | AG1-030 C | Adder | 12.06 MW | 10.26 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 961892 | AG1-030 E | Adder | 8.04 MW | 6.84 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 963041 | AG1-153 C | Adder | 5.37 MW | 4.56 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 963042 | AG1-153 E | Adder | 8.05 MW | 6.84 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 963111 | AG1-160 C | Adder | 5.44 MW | 4.63 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 963112 | AG1-160 E | Adder | 8.16 MW | 6.94 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 963171 | AG1-166 C | Adder | 1.6 MW | 1.36 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 963172 | AG1-166 E | Adder | 1.07 MW | 0.91 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 963181 | AG1-167 C | Adder | 1.6 MW | 1.36 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 963182 | AG1-167 E | Adder | 1.07 MW | 0.91 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 963191 | AG1-168 C | Adder | 1.6 MW | 1.36 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 963192 | AG1-168 E | Adder | 1.07 MW | 0.91 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 963201 | AG1-169 C | Adder | 1.6 MW | 1.36 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 963202 | AG1-169 E | Adder | 1.07 MW | 0.91 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 963211 | AG1-170 C | Adder | 1.6 MW | 1.36 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 963212 | AG1-170 E | Adder | 1.07 MW | 0.91 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 963301 | AG1-179 C | Adder | 4.67 MW | 3.97 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 964111 | AG1-272 C | Adder | 2.08 MW | 1.77 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 964112 | AG1-272 E | Adder | 0.62 MW | 0.53 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 964121 | AG1-273 C | Adder | 2.08 MW | 1.77 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 964122 | AG1-273 E | Adder | 0.62 MW | 0.53 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 964131 | AG1-274 C | Adder | 2.08 MW | 1.77 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 964132 | AG1-274 E | Adder | 0.62 MW | 0.53 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 964791 | AG1-342 C | Adder | 3.35 MW | 2.85 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 964792 | AG1-342 E | Adder | 2.63 MW | 2.24 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 966811 | AG1-552 C | Adder | 1.63 MW | 1.39 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 966812 | AG1-552 E | Adder | 0.78 MW | 0.66 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 965191 | AG1-384 C | Adder | 2.08 MW | 1.77 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 965192 | AG1-384 E | Adder | 0.62 MW | 0.53 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 965591 | AG1-427 C | Adder | 9.67 MW | 8.22 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 965592 | AG1-427 E | Adder | 6.45 MW | 5.48 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 965721 | AG1-440 C | Adder | 6.12 MW | 5.2 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 965722 | AG1-440 E | Adder | 4.08 MW | 3.47 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 965731 | AG1-441 C | Adder | 6.12 MW | 5.2 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 965732 | AG1-441 E | Adder | 4.08 MW | 3.47 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 966361 | AG1-505 C | Adder | 15.99 MW | 13.59 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 966362 | AG1-505 E | Adder | 10.66 MW | 9.06 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 966371 | AG1-506 C | Adder | 15.99 MW | 13.59 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 966372 | AG1-506 E | Adder | 10.66 MW | 9.06 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 966621 | AG1-532 C | Adder | 1.14 MW | 0.97 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 966622 | AG1-532 E | Adder | 0.76 MW | 0.64 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 313853 | 3PONTONDP | Adder | 0.53 MW | 0.45 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 314572 | 3EMPORIA | Adder | 0.35 MW | 0.3 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 314713 | 3PAMPLIN | Adder | 0.8 MW | 0.68 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 918492 | AA1-063AE OP | Adder | 3.21 MW | 2.73 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 919692 | AA2-053 E OP | Adder | 3.34 MW | 2.84 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 925785 | AC1-054 E | Adder | 2.77 MW | 2.36 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 942931 | AE2-313 C | Adder | 34.9 MW | 29.66 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 942932 | AE2-313 E | Adder | 23.27 MW | 19.78 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 944011 | AF1-069 C | 50/50 | 12.66 MW | 12.66 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 944012 | AF1-069 E | 50/50 | 4.92 MW | 4.92 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 958801 | AF2-171 C | Adder | 12.03 MW | 10.22 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 958802 | AF2-171 E | Adder | 8.02 MW | 6.82 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 959311 | AF2-222 C | Adder | 13.47 MW | 11.45 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 959312 | AF2-222 E | Adder | 9.03 MW | 7.67 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 960081 | AF2-299 C | Adder | 2.1 MW | 1.79 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 960082 | AF2-299 E | Adder | 1.4 MW | 1.19 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 923263 | AB1-132 E OP | Adder | 4.86 MW | 4.13 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 923573 | AB1-173 E OP | Adder | 2.64 MW | 2.24 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 924162 | AB2-060 E OP | Adder | 3.49 MW | 2.97 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 924302 | AB2-077 E O1 | Adder | 1.09 MW | 0.93 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 924312 | AB2-078 E O1 | Adder | 1.09 MW | 0.93 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 924322 | AB2-079 E O1 | Adder | 1.09 MW | 0.93 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 925612 | AC1-036 E | Adder | 0.7 MW | 0.59 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 938371 | AE1-056 C | Adder | 5.17 MW | 4.39 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 938372 | AE1-056 E | Adder | 2.82 MW | 2.4 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 939181 | AE1-148 C | Adder | 7.36 MW | 6.26 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 939182 | AE1-148 E | Adder | 4.91 MW | 4.17 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 941031 | AE2-094 C | 50/50 | 38.75 MW | 38.75 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 941032 | AE2-094 E | 50/50 | 17.36 MW | 17.36 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 941791 | AE2-182 C | Adder | 1.68 MW | 1.43 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 941792 | AE2-182 E | Adder | 0.78 MW | 0.66 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 946281 | AF1-292 C | Adder | 1.25 MW | 1.07 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 946282 | AF1-292 E | Adder | 0.84 MW | 0.71 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 946301 | AF1-294 C | Adder | 3.29 MW | 2.79 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 946302 | AF1-294 E | Adder | 2.19 MW | 1.86 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 957481 | AF2-042 C | Adder | 49.22 MW | 41.83 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 957482 | AF2-042 E | Adder | 32.81 MW | 27.89 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 958211 | AF2-115 C | Adder | 2.0 MW | 1.7 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 958212 | AF2-115 E | Adder | 1.34 MW | 1.14 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 933502 | AC2-165 E | Adder | 6.82 MW | 5.79 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 314331 | 6POE | Adder | 1.03 MW | 0.88 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 926755 | AC1-161 E | Adder | 9.52 MW | 8.09 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 958502 | AF2-144 E | Adder | 1.14 MW | 0.97 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 315172 | 1LOISA A | 50/50 | 2.61 MW | 2.61 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 315173 | 1LOISA B | 50/50 | 2.63 MW | 2.63 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 315174 | 1LOISA C | 50/50 | 2.63 MW | 2.63 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 315175 | 1LOISA D | 50/50 | 2.63 MW | 2.63 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 315176 | 1LOISA E | 50/50 | 5.36 MW | 5.36 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 315177 | 1S ANNAG1 | 50/50 | 2.58 MW | 2.58 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 315178 | 1S ANNAS1 | 50/50 | 1.33 MW | 1.33 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 315179 | 1S ANNAG2 | 50/50 | 2.58 MW | 2.58 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 315180 | 1S ANNAS2 | 50/50 | 1.33 MW | 1.33 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 315225 | 1N ANNA1 | 50/50 | 90.54 MW | 90.54 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 315226 | 1N ANNA2 | 50/50 | 90.55 MW | 90.55 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 923852 | AB2-025 E | Adder | 0.97 MW | 0.82 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 923862 | AB2-026 E | Adder | 1.16 MW | 0.98 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 925022 | AB2-158 E | 50/50 | 11.37 MW | 11.37 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 938552 | AE1-074 E | Adder | 1.08 MW | 0.92 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 938562 | AE1-075 E | Adder | 0.99 MW | 0.84 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 946371 | AF1-301 C | 50/50 | 21.05 MW | 21.05 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 946372 | AF1-301 E | 50/50 | 14.14 MW | 14.14 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 966001 | AG1-469 C | 50/50 | 2.0 MW | 2.0 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 966002 | AG1-469 E | 50/50 | 1.0 MW | 1.0 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 314722 | 3TWITTYS | Adder | 0.77 MW | 0.66 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 926071 | AC1-086 C | Adder | 16.7 MW | 14.19 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 926072 | AC1-086 E | Adder | 7.6 MW | 6.46 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 936261 | AD2-033 C | Adder | 10.54 MW | 8.96 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 936262 | AD2-033 E | Adder | 7.03 MW | 5.97 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 933291 | AC2-141 C | Adder | 22.3 MW | 18.96 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 933292 | AC2-141 E | Adder | 9.52 MW | 8.09 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 934621 | AD1-088 C | Adder | 10.33 MW | 8.78 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 934622 | AD1-088 E | Adder | 4.86 MW | 4.13 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 939411 | AE1-173 C | Adder | 81.83 MW | 69.55 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 939412 | AE1-173 E | Adder | 54.55 MW | 46.37 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 962572 | AG1-106 E | Adder | 2.11 MW | 1.79 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 962571 | AG1-106 C | Adder | 4.64 MW | 3.95 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 208900 | BRIS G1 | 50/50 | -2.11 MW | -2.11 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 208901 | BRIS G2 | 50/50 | -2.5 MW | -2.5 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 316192 | AB2-158 C | 50/50 | 3.65 MW | 3.65 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 316233 | AE1-074 C | Adder | 2.14 MW | 1.82 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 316336 | AC2-165 C | Adder | 9.06 MW | 7.7 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 924516 | AB2-100 E1 | Adder | 2.35 MW | 2.0 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 924517 | AB2-100 E2 | Adder | 2.35 MW | 2.0 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 934065 | AD1-033 E | Adder | 2.66 MW | 2.26 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 316181 | AB2-040 GEN | Adder | 6.04 MW | 5.14 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 923994 | AB2-040_E | Adder | 4.94 MW | 4.2 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 924022 | AB2-043 E O1 | Adder | 4.23 MW | 3.6 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 316088 | AB2-174 E | Adder | 5.25 MW | 4.46 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 316044 | AC1-158 C1 | 50/50 | 16.68 MW | 16.68 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 316045 | AC1-158 C2 | 50/50 | 16.68 MW | 16.68 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 926739 | AC1-158 E1 | 50/50 | 51.19 MW | 51.19 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 926740 | AC1-158 E2 | 50/50 | 51.19 MW | 51.19 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 940661 | AE2-053 C | Adder | 2.73 MW | 2.32 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 944581 | AF1-123 C | Adder | 35.75 MW | 30.39 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 944582 | AF1-123 E | Adder | 81.86 MW | 69.58 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 944591 | AF1-124 C | Adder | 35.75 MW | 30.39 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 944592 | AF1-124 E | Adder | 81.86 MW | 69.58 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 944601 | AF1-125 C | Adder | 35.75 MW | 30.39 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 944602 | AF1-125 E | Adder | 81.86 MW | 69.58 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 946011 | AF1-266 C | Adder | 11.28 MW | 9.59 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 957431 | AF2-037 C | 50/50 | 28.28 MW | 28.28 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 957432 | AF2-037 E | 50/50 | 18.86 MW | 18.86 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 957691 | AF2-063 C | 50/50 | 45.13 MW | 45.13 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 957692 | AF2-063 E | 50/50 | 30.09 MW | 30.09 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 962491 | AG1-098 C | Adder | 9.31 MW | 7.91 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 962492 | AG1-098 E | Adder | 6.2 MW | 5.27 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 962561 | AG1-105 C | Adder | 7.21 MW | 6.12 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 962562 | AG1-105 E | Adder | 4.8 MW | 4.08 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 963291 | AG1-178 C | Adder | 60.23 MW | 51.2 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 963311 | AG1-180 C | Adder | 2.27 MW | 1.93 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 963321 | AG1-181 C | Adder | 13.66 MW | 11.61 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 963351 | AG1-184 C | Adder | 32.45 MW | 27.58 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 963361 | AG1-185 C | Adder | 6.61 MW | 5.62 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 964241 | AG1-285 C | Adder | 10.19 MW | 8.66 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 964242 | AG1-285 E | Adder | 6.79 MW | 5.77 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 964421 | AG1-305 C | 50/50 | 35.51 MW | 35.51 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 964422 | AG1-305 E | 50/50 | 23.67 MW | 23.67 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 964951 | AG1-359 C | Adder | 16.88 MW | 14.35 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 965601 | AG1-428 C | Adder | 3.9 MW | 3.31 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 965602 | AG1-428 E | Adder | 2.6 MW | 2.21 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 965771 | AG1-445 C | Adder | 3.54 MW | 3.0 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 965781 | AG1-446 C | Adder | 3.54 MW | 3.0 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 965811 | AG1-449 C | Adder | 22.6 MW | 19.21 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 313764 | 3SOCKMAN | Adder | 0.57 MW | 0.48 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 934612 | AD1-087 E | Adder | 3.24 MW | 2.75 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 935172 | AD1-152 E | Adder | 4.75 MW | 4.04 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 937482 | AD2-202 E | Adder | 0.95 MW | 0.81 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 940481 | AE2-033 C | Adder | 13.48 MW | 11.46 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 940482 | AE2-033 E | Adder | 9.09 MW | 7.72 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 940541 | AE2-040 C | Adder | 2.4 MW | 2.04 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 940641 | AE2-051 C | Adder | 16.48 MW | 14.01 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 940642 | AE2-051 E | Adder | 10.99 MW | 9.34 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 945811 | AF1-246 C | Adder | 6.89 MW | 5.86 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 945812 | AF1-246 E | Adder | 9.52 MW | 8.09 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | 316303 | AF2-085 | 50/50 | 4.01 MW | 4.01 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 19.77 MW | 19.77 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 16.72 MW | 16.72 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 76.98 MW | 76.98 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 5.07 MW | 5.07 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | NY | PJM->LTFIMP_NY | CLTF | 2.38 MW | 2.38 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.86 MW | 0.86 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | WEC | LTFEXP_WEC->PJM | CLTF | 0.43 MW | 0.43 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | CPLE | LTFEXP_CPLE->PJM | CLTF | 9.24 MW | 9.24 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | TVA | LTFEXP_TVA->PJM | CLTF | 4.7 MW | 4.7 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | MEC | LTFEXP_MEC->PJM | CLTF | 2.76 MW | 2.76 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | LAGN | LTFEXP_LAGN->PJM | CLTF | 5.93 MW | 5.93 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.17 MW | 0.17 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 32.27 MW | 32.27 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 4.4 MW | 4.4 MW |
| Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 963041 | AG1-153 C | Adder | 5.55 MW | 4.72 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 963042 | AG1-153 E | Adder | 8.33 MW | 7.08 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 963111 | AG1-160 C | Adder | 5.62 MW | 4.78 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 963112 | AG1-160 E | Adder | 8.43 MW | 7.17 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 966361 | AG1-505 C | Adder | 16.55 MW | 14.07 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 966362 | AG1-505 E | Adder | 11.03 MW | 9.38 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 966371 | AG1-506 C | Adder | 16.55 MW | 14.07 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 966372 | AG1-506 E | Adder | 11.03 MW | 9.38 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 942931 | AE2-313 C | Adder | 36.02 MW | 30.62 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 942932 | AE2-313 E | Adder | 24.02 MW | 20.41 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 944011 | AF1-069 C | Adder | 13.06 MW | 11.1 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 944012 | AF1-069 E | Adder | 5.07 MW | 4.31 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 941031 | AE2-094 C | Adder | 39.97 MW | 33.98 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 941032 | AE2-094 E | Adder | 17.9 MW | 15.22 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 957481 | AF2-042 C | Adder | 51.23 MW | 43.55 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 957482 | AF2-042 E | Adder | 34.15 MW | 29.03 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 933502 | AC2-165 E | Adder | 7.16 MW | 6.09 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 314331 | 6POE | Adder | 1.21 MW | 1.03 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 314550 | 6HICKORY | Adder | 1.9 MW | 1.62 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 926755 | AC1-161 E | Adder | 11.32 MW | 9.62 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 958502 | AF2-144 E | Adder | 1.19 MW | 1.01 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 315172 | 1LOISA A | 50/50 | 2.28 MW | 2.28 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 315173 | 1LOISA B | 50/50 | 2.29 MW | 2.29 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 315174 | 1LOISA C | 50/50 | 2.29 MW | 2.29 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 315175 | 1LOISA D | 50/50 | 2.29 MW | 2.29 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 315176 | 1LOISA E | 50/50 | 4.67 MW | 4.67 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 315177 | 1S ANNAG1 | 50/50 | 2.24 MW | 2.24 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 315178 | 1S ANNAS1 | 50/50 | 1.15 MW | 1.15 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 315179 | 1S ANNAG2 | 50/50 | 2.24 MW | 2.24 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 315180 | 1S ANNAS2 | 50/50 | 1.15 MW | 1.15 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 315225 | 1N ANNA1 | 50/50 | 75.41 MW | 75.41 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 315226 | 1N ANNA2 | 50/50 | 75.42 MW | 75.42 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 923852 | AB2-025 E | Adder | 1.07 MW | 0.91 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 923862 | AB2-026 E | Adder | 1.21 MW | 1.03 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 925022 | AB2-158 E | 50/50 | 9.63 MW | 9.63 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 938552 | AE1-074 E | Adder | 1.21 MW | 1.03 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 938562 | AE1-075 E | Adder | 1.04 MW | 0.88 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 946371 | AF1-301 C | 50/50 | 18.11 MW | 18.11 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 946372 | AF1-301 E | 50/50 | 12.16 MW | 12.16 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 964271 | AG1-288 C | 50/50 | 33.71 MW | 33.71 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 966001 | AG1-469 C | 50/50 | 1.96 MW | 1.96 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 966002 | AG1-469 E | 50/50 | 0.98 MW | 0.98 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 966331 | AG1-502 C | 50/50 | 14.26 MW | 14.26 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 966332 | AG1-502 E | 50/50 | 3.56 MW | 3.56 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 966341 | AG1-503 C | 50/50 | 3.56 MW | 3.56 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 966342 | AG1-503 E | 50/50 | 0.89 MW | 0.89 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 933291 | AC2-141 C | Adder | 26.53 MW | 22.55 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 933292 | AC2-141 E | Adder | 11.32 MW | 9.62 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 939411 | AE1-173 C | Adder | 88.07 MW | 74.86 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 939412 | AE1-173 E | Adder | 58.71 MW | 49.91 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 208900 | BRIS G1 | 50/50 | -2.23 MW | -2.23 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 208901 | BRIS G2 | 50/50 | -2.64 MW | -2.64 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 316164 | AC1-076_C | 50/50 | 0.94 MW | 0.94 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 316170 | AC1-121 C | Adder | 2.72 MW | 2.31 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 316192 | AB2-158 C | 50/50 | 3.09 MW | 3.09 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 316233 | AE1-074 C | Adder | 2.4 MW | 2.04 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 316254 | AC1-120 C | Adder | 7.92 MW | 6.73 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 316336 | AC2-165 C | Adder | 9.51 MW | 8.09 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 924516 | AB2-100 E1 | Adder | 2.6 MW | 2.21 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 924517 | AB2-100 E2 | Adder | 2.6 MW | 2.21 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 934065 | AD1-033 E | Adder | 4.38 MW | 3.73 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 926004 | AC1-076_E | 50/50 | 6.38 MW | 6.38 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 926486 | AC1-120 E | Adder | 4.08 MW | 3.47 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 926502 | AC1-121 E | Adder | 1.28 MW | 1.09 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 316044 | AC1-158 C1 | 50/50 | 16.55 MW | 16.55 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 316045 | AC1-158 C2 | 50/50 | 16.55 MW | 16.55 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 926739 | AC1-158 E1 | 50/50 | 50.77 MW | 50.77 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 926740 | AC1-158 E2 | 50/50 | 50.77 MW | 50.77 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 941291 | AE2-123 C | Adder | 25.52 MW | 21.69 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 941292 | AE2-123 E | Adder | 99.52 MW | 84.59 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 941301 | AE2-124 C | Adder | 23.21 MW | 19.73 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 941302 | AE2-124 E | Adder | 101.86 MW | 86.58 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 944581 | AF1-123 C | Adder | 42.2 MW | 35.87 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 944582 | AF1-123 E | Adder | 96.62 MW | 82.13 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 944591 | AF1-124 C | Adder | 42.2 MW | 35.87 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 944592 | AF1-124 E | Adder | 96.62 MW | 82.13 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 944601 | AF1-125 C | Adder | 42.2 MW | 35.87 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 944602 | AF1-125 E | Adder | 96.62 MW | 82.13 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 946011 | AF1-266 C | Adder | 12.44 MW | 10.58 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 957431 | AF2-037 C | 50/50 | 23.78 MW | 23.78 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 957432 | AF2-037 E | 50/50 | 15.86 MW | 15.86 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 957691 | AF2-063 C | 50/50 | 37.95 MW | 37.95 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 957692 | AF2-063 E | 50/50 | 25.3 MW | 25.3 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 962841 | AG1-133 C | 50/50 | 44.25 MW | 44.25 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 962842 | AG1-133 E | 50/50 | 29.5 MW | 29.5 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 963291 | AG1-178 C | Adder | 62.99 MW | 53.54 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 963351 | AG1-184 C | Adder | 33.94 MW | 28.85 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 964281 | AG1-289 C | 50/50 | 18.64 MW | 18.64 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 964421 | AG1-305 C | 50/50 | 29.85 MW | 29.85 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 964422 | AG1-305 E | 50/50 | 19.9 MW | 19.9 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 964951 | AG1-359 C | Adder | 19.97 MW | 16.97 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 965811 | AG1-449 C | Adder | 23.33 MW | 19.83 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 934612 | AD1-087 E | Adder | 3.38 MW | 2.87 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 937482 | AD2-202 E | Adder | 0.99 MW | 0.84 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 940481 | AE2-033 C | Adder | 14.86 MW | 12.63 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 940482 | AE2-033 E | Adder | 10.02 MW | 8.52 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 940541 | AE2-040 C | Adder | 2.64 MW | 2.25 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 940641 | AE2-051 C | Adder | 17.31 MW | 14.72 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 940642 | AE2-051 E | Adder | 11.54 MW | 9.81 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 941281 | AE2-122 C | Adder | 7.7 MW | 6.55 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 941282 | AE2-122 E | Adder | 100.21 MW | 85.18 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 945811 | AF1-246 C | Adder | 7.17 MW | 6.1 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 945812 | AF1-246 E | Adder | 9.9 MW | 8.42 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 21.6 MW | 21.6 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 18.36 MW | 18.36 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 83.32 MW | 83.32 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 5.37 MW | 5.37 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | NY | PJM->LTFIMP_NY | CLTF | 2.54 MW | 2.54 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.96 MW | 0.96 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | WEC | LTFEXP_WEC->PJM | CLTF | 0.47 MW | 0.47 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | CPLE | LTFEXP_CPLE->PJM | CLTF | 9.94 MW | 9.94 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | TVA | LTFEXP_TVA->PJM | CLTF | 5.17 MW | 5.17 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | MEC | LTFEXP_MEC->PJM | CLTF | 3.03 MW | 3.03 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | LAGN | LTFEXP_LAGN->PJM | CLTF | 6.5 MW | 6.5 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.19 MW | 0.19 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 34.2 MW | 34.2 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 4.74 MW | 4.74 MW |
| Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 963041 | AG1-153 C | 50/50 | 9.31 MW | 9.31 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 963042 | AG1-153 E | 50/50 | 13.96 MW | 13.96 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 963111 | AG1-160 C | 50/50 | 9.45 MW | 9.45 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 963112 | AG1-160 E | 50/50 | 14.17 MW | 14.17 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 966361 | AG1-505 C | 50/50 | 27.34 MW | 27.34 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 966362 | AG1-505 E | 50/50 | 18.23 MW | 18.23 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 966371 | AG1-506 C | 50/50 | 27.34 MW | 27.34 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 966372 | AG1-506 E | 50/50 | 18.23 MW | 18.23 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 315153 | 1CLOVER1 | 50/50 | 15.71 MW | 15.71 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 315154 | 1CLOVER2 | 50/50 | 15.56 MW | 15.56 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 942931 | AE2-313 C | 50/50 | 60.49 MW | 60.49 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 942932 | AE2-313 E | 50/50 | 40.32 MW | 40.32 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 944011 | AF1-069 C | 50/50 | 22.05 MW | 22.05 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 944012 | AF1-069 E | 50/50 | 8.57 MW | 8.57 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 941031 | AE2-094 C | 50/50 | 67.49 MW | 67.49 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 941032 | AE2-094 E | 50/50 | 30.23 MW | 30.23 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 957481 | AF2-042 C | 50/50 | 81.31 MW | 81.31 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 957482 | AF2-042 E | 50/50 | 54.2 MW | 54.2 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 314295 | 6BIRDNECK | 50/50 | 0.05 MW | 0.05 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 314550 | 6HICKORY | 50/50 | 2.98 MW | 2.98 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 926755 | AC1-161 E | 50/50 | 18.16 MW | 18.16 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 315102 | 1BRUNSWICKG1 | 50/50 | 11.6 MW | 11.6 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 315103 | 1BRUNSWICKG2 | 50/50 | 11.6 MW | 11.6 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 315104 | 1BRUNSWICKG3 | 50/50 | 11.6 MW | 11.6 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 315105 | 1BRUNSWICKS1 | 50/50 | 24.09 MW | 24.09 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 315110 | 1ELIZAR3 | 50/50 | 3.71 MW | 3.71 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 315241 | 1Z1-086 GT1 | 50/50 | 14.88 MW | 14.88 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 315242 | 1Z1-086 GT2 | 50/50 | 14.9 MW | 14.9 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 315243 | 1Z1-086 GT3 | 50/50 | 14.9 MW | 14.9 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 315244 | 1Z1-086 ST | 50/50 | 25.92 MW | 25.92 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 916192 | Z1-068 E | 50/50 | 2.56 MW | 2.56 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 923852 | AB2-025 E | 50/50 | 1.62 MW | 1.62 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 925522 | AC1-027 E | 50/50 | 1.66 MW | 1.66 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 957871 | AF2-081 C | 50/50 | 13.65 MW | 13.65 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 957872 | AF2-081 E | 50/50 | 5.85 MW | 5.85 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 933291 | AC2-141 C | 50/50 | 42.55 MW | 42.55 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 933292 | AC2-141 E | 50/50 | 18.16 MW | 18.16 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 939411 | AE1-173 C | 50/50 | 146.16 MW | 146.16 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 939412 | AE1-173 E | 50/50 | 97.44 MW | 97.44 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 314632 | 6AYDLETT TAP | 50/50 | 1.85 MW | 1.85 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 316185 | AD1-033 C | 50/50 | 1.42 MW | 1.42 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 316294 | AC1-161 C | 50/50 | 5.87 MW | 5.87 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 316315 | AB2-025 C | 50/50 | 0.48 MW | 0.48 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 316316 | AC1-027 C | 50/50 | 0.36 MW | 0.36 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 934065 | AD1-033 E | 50/50 | 6.86 MW | 6.86 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 937226 | AE2-253 E | 50/50 | 7.98 MW | 7.98 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 316017 | AA1-139 ULT1 | 50/50 | 1.25 MW | 1.25 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 316018 | AA1-139 ULT2 | 50/50 | 1.25 MW | 1.25 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 919153 | AA1-139 E2 | 50/50 | 5.58 MW | 5.58 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 919152 | AA1-139 E1 | 50/50 | 5.58 MW | 5.58 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 316388 | AE2-253 GEN | 50/50 | 2.27 MW | 2.27 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 941291 | AE2-123 C | 50/50 | 39.8 MW | 39.8 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 941292 | AE2-123 E | 50/50 | 155.19 MW | 155.19 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 941301 | AE2-124 C | 50/50 | 36.21 MW | 36.21 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 941302 | AE2-124 E | 50/50 | 158.9 MW | 158.9 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 944581 | AF1-123 C | 50/50 | 66.51 MW | 66.51 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 944582 | AF1-123 E | 50/50 | 152.29 MW | 152.29 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 944591 | AF1-124 C | 50/50 | 66.51 MW | 66.51 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 944592 | AF1-124 E | 50/50 | 152.29 MW | 152.29 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 944601 | AF1-125 C | 50/50 | 66.51 MW | 66.51 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 944602 | AF1-125 E | 50/50 | 152.29 MW | 152.29 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 946011 | AF1-266 C | 50/50 | 18.83 MW | 18.83 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 963291 | AG1-178 C | 50/50 | 106.11 MW | 106.11 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 963351 | AG1-184 C | 50/50 | 57.17 MW | 57.17 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 964951 | AG1-359 C | 50/50 | 31.25 MW | 31.25 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 965811 | AG1-449 C | 50/50 | 39.17 MW | 39.17 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 934611 | AD1-087 C | 50/50 | 1.54 MW | 1.54 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 934612 | AD1-087 E | 50/50 | 5.28 MW | 5.28 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 937481 | AD2-202 C | 50/50 | 0.45 MW | 0.45 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 937482 | AD2-202 E | 50/50 | 1.55 MW | 1.55 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 938531 | AE1-072 C | 50/50 | 23.99 MW | 23.99 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 938532 | AE1-072 E | 50/50 | 12.51 MW | 12.51 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 940481 | AE2-033 C | 50/50 | 22.49 MW | 22.49 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 940482 | AE2-033 E | 50/50 | 15.16 MW | 15.16 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 940541 | AE2-040 C | 50/50 | 4.0 MW | 4.0 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 940641 | AE2-051 C | 50/50 | 29.16 MW | 29.16 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 940642 | AE2-051 E | 50/50 | 19.44 MW | 19.44 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 941281 | AE2-122 C | 50/50 | 38.72 MW | 38.72 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 941282 | AE2-122 E | 50/50 | 156.26 MW | 156.26 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 945811 | AF1-246 C | 50/50 | 11.38 MW | 11.38 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | 945812 | AF1-246 E | 50/50 | 15.72 MW | 15.72 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 55.55 MW | 55.55 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 35.76 MW | 35.76 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 137.28 MW | 137.28 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 5.65 MW | 5.65 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | NY | PJM->LTFIMP_NY | CLTF | 2.58 MW | 2.58 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | LGEE | LTFEXP_LGEE->PJM | CLTF | 2.2 MW | 2.2 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | WEC | LTFEXP_WEC->PJM | CLTF | 1.14 MW | 1.14 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | CPLE | LTFEXP_CPLE->PJM | CLTF | 16.14 MW | 16.14 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | TVA | LTFEXP_TVA->PJM | CLTF | 9.41 MW | 9.41 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | MEC | LTFEXP_MEC->PJM | CLTF | 6.62 MW | 6.62 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | LAGN | LTFEXP_LAGN->PJM | CLTF | 11.88 MW | 11.88 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.42 MW | 0.42 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 35.95 MW | 35.95 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 7.7 MW | 7.7 MW |
| Details for 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | 916042 | Z1-036 E | Adder | 10.38 MW | 8.82 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | 313526 | AB2-022 C | 50/50 | 0.21 MW | 0.21 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | 314507 | 3THOMPSN | Adder | -1.34 MW | -1.14 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | 314550 | 6HICKORY | 50/50 | 2.21 MW | 2.21 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | 944871 | AF1-152 C | Adder | 1.86 MW | 1.58 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | 944872 | AF1-152 E | Adder | 1.24 MW | 1.05 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | 315611 | 6Z1-036WIND | Adder | 2.46 MW | 2.09 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | 913392 | Y1-086 E | 50/50 | 1.47 MW | 1.47 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | 923832 | AB2-022 E | 50/50 | 0.83 MW | 0.83 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | 901082 | W1-029 E | Adder | 11.22 MW | 9.54 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | 917122 | Z2-027 E | 50/50 | 0.78 MW | 0.78 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | 925522 | AC1-027 E | 50/50 | 0.79 MW | 0.79 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | 941501 | AE2-147 C | Adder | 5.58 MW | 4.74 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | 941502 | AE2-147 E | Adder | 3.72 MW | 3.16 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | 957871 | AF2-081 C | 50/50 | 9.05 MW | 9.05 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | 957872 | AF2-081 E | 50/50 | 3.88 MW | 3.88 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | 314632 | 6AYDLETT TAP | 50/50 | 1.14 MW | 1.14 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | 316185 | AD1-033 C | 50/50 | 1.29 MW | 1.29 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | 316316 | AC1-027 C | 50/50 | 0.17 MW | 0.17 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | 316320 | Y1-086 C | 50/50 | 0.12 MW | 0.12 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | 316321 | Z2-027 C | 50/50 | 0.18 MW | 0.18 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | 934065 | AD1-033 E | 50/50 | 6.22 MW | 6.22 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | 937226 | AE2-253 E | 50/50 | 5.54 MW | 5.54 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | 316017 | AA1-139 ULT1 | 50/50 | 0.83 MW | 0.83 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | 316018 | AA1-139 ULT2 | 50/50 | 0.83 MW | 0.83 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | 919153 | AA1-139 E2 | 50/50 | 3.7 MW | 3.7 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | 919152 | AA1-139 E1 | 50/50 | 3.7 MW | 3.7 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | 316388 | AE2-253 GEN | 50/50 | 1.57 MW | 1.57 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | 941291 | AE2-123 C | 50/50 | 26.67 MW | 26.67 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | 941292 | AE2-123 E | 50/50 | 104.0 MW | 104.0 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | 941301 | AE2-124 C | 50/50 | 57.0 MW | 57.0 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | 941302 | AE2-124 E | 50/50 | 250.11 MW | 250.11 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | 944581 | AF1-123 C | Adder | 17.19 MW | 14.61 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | 944582 | AF1-123 E | Adder | 39.36 MW | 33.45 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | 944591 | AF1-124 C | Adder | 17.19 MW | 14.61 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | 944592 | AF1-124 E | Adder | 39.36 MW | 33.45 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | 944601 | AF1-125 C | Adder | 17.19 MW | 14.61 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | 944602 | AF1-125 E | Adder | 39.36 MW | 33.45 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | 964951 | AG1-359 C | 50/50 | 24.07 MW | 24.07 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | 938531 | AE1-072 C | 50/50 | 15.12 MW | 15.12 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | 938532 | AE1-072 E | 50/50 | 7.88 MW | 7.88 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | 941281 | AE2-122 C | 50/50 | 25.95 MW | 25.95 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | 941282 | AE2-122 E | 50/50 | 104.72 MW | 104.72 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 1.12 MW | 1.12 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 0.62 MW | 0.62 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 2.23 MW | 2.23 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 0.02 MW | 0.02 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | NY | PJM->LTFIMP_NY | CLTF | 0.01 MW | 0.01 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.04 MW | 0.04 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | WEC | LTFEXP_WEC->PJM | CLTF | 0.02 MW | 0.02 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | CPLE | LTFEXP_CPLE->PJM | CLTF | 0.28 MW | 0.28 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | TVA | LTFEXP_TVA->PJM | CLTF | 0.16 MW | 0.16 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | MEC | LTFEXP_MEC->PJM | CLTF | 0.12 MW | 0.12 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | LAGN | LTFEXP_LAGN->PJM | CLTF | 0.2 MW | 0.2 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.01 MW | 0.01 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 0.14 MW | 0.14 MW |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128_SRT-S | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.13 MW | 0.13 MW |
| Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 963041 | AG1-153 C | 50/50 | 5.72 MW | 5.72 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 963042 | AG1-153 E | 50/50 | 8.58 MW | 8.58 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 963111 | AG1-160 C | 50/50 | 5.8 MW | 5.8 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 963112 | AG1-160 E | 50/50 | 8.7 MW | 8.7 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 966361 | AG1-505 C | 50/50 | 17.05 MW | 17.05 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 966362 | AG1-505 E | 50/50 | 11.37 MW | 11.37 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 966371 | AG1-506 C | 50/50 | 17.05 MW | 17.05 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 966372 | AG1-506 E | 50/50 | 11.37 MW | 11.37 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 942931 | AE2-313 C | 50/50 | 37.13 MW | 37.13 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 942932 | AE2-313 E | 50/50 | 24.75 MW | 24.75 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 944011 | AF1-069 C | 50/50 | 13.46 MW | 13.46 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 944012 | AF1-069 E | 50/50 | 5.23 MW | 5.23 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 941031 | AE2-094 C | 50/50 | 41.21 MW | 41.21 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 941032 | AE2-094 E | 50/50 | 18.46 MW | 18.46 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 957481 | AF2-042 C | Adder | 52.73 MW | 44.82 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 957482 | AF2-042 E | Adder | 35.15 MW | 29.88 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 933502 | AC2-165 E | Adder | 7.29 MW | 6.2 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 314331 | 6POE | Adder | 1.24 MW | 1.05 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 314550 | 6HICKORY | Adder | 1.95 MW | 1.66 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 926755 | AC1-161 E | Adder | 11.61 MW | 9.87 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 958502 | AF2-144 E | Adder | 1.22 MW | 1.04 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 315102 | 1BRUNSWICKG1 | 50/50 | 7.13 MW | 7.13 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 315103 | 1BRUNSWICKG2 | 50/50 | 7.13 MW | 7.13 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 315104 | 1BRUNSWICKG3 | 50/50 | 7.13 MW | 7.13 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 315105 | 1BRUNSWICKS1 | 50/50 | 14.81 MW | 14.81 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 315175 | 1LOISA D | 50/50 | 2.02 MW | 2.02 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 315176 | 1LOISA E | 50/50 | 4.11 MW | 4.11 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 315177 | 1S ANNAG1 | 50/50 | 2.0 MW | 2.0 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 315178 | 1S ANNAS1 | 50/50 | 1.03 MW | 1.03 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 315179 | 1S ANNAG2 | 50/50 | 2.0 MW | 2.0 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 315180 | 1S ANNAS2 | 50/50 | 1.03 MW | 1.03 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 315225 | 1N ANNA1 | 50/50 | 78.54 MW | 78.54 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 315226 | 1N ANNA2 | 50/50 | 78.55 MW | 78.55 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 315241 | 1Z1-086 GT1 | 50/50 | 9.13 MW | 9.13 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 315242 | 1Z1-086 GT2 | 50/50 | 9.14 MW | 9.14 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 315243 | 1Z1-086 GT3 | 50/50 | 9.14 MW | 9.14 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 315244 | 1Z1-086 ST | 50/50 | 15.9 MW | 15.9 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 923852 | AB2-025 E | Adder | 1.1 MW | 0.94 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 923862 | AB2-026 E | Adder | 1.24 MW | 1.05 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 925022 | AB2-158 E | 50/50 | 9.45 MW | 9.45 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 938552 | AE1-074 E | Adder | 1.24 MW | 1.05 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 938562 | AE1-075 E | Adder | 1.06 MW | 0.9 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 946371 | AF1-301 C | 50/50 | 16.75 MW | 16.75 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 946372 | AF1-301 E | 50/50 | 11.25 MW | 11.25 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 933291 | AC2-141 C | Adder | 27.19 MW | 23.11 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 933292 | AC2-141 E | Adder | 11.61 MW | 9.87 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 939411 | AE1-173 C | 50/50 | 90.63 MW | 90.63 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 939412 | AE1-173 E | 50/50 | 60.42 MW | 60.42 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 316192 | AB2-158 C | 50/50 | 3.03 MW | 3.03 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 316233 | AE1-074 C | Adder | 2.46 MW | 2.09 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 316336 | AC2-165 C | Adder | 9.69 MW | 8.23 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 924516 | AB2-100 E1 | Adder | 2.67 MW | 2.27 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 924517 | AB2-100 E2 | Adder | 2.67 MW | 2.27 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 934065 | AD1-033 E | Adder | 4.5 MW | 3.82 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 941292 | AE2-123 E | Adder | 64.01 MW | 54.41 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 941301 | AE2-124 C | Adder | 23.8 MW | 20.23 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 941302 | AE2-124 E | Adder | 104.44 MW | 88.77 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 944581 | AF1-123 C | Adder | 43.27 MW | 36.78 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 944582 | AF1-123 E | Adder | 99.08 MW | 84.22 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 944591 | AF1-124 C | Adder | 43.27 MW | 36.78 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 944592 | AF1-124 E | Adder | 99.08 MW | 84.22 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 944601 | AF1-125 C | Adder | 43.27 MW | 36.78 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 944602 | AF1-125 E | Adder | 99.08 MW | 84.22 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 946011 | AF1-266 C | Adder | 12.79 MW | 10.87 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 957431 | AF2-037 C | 50/50 | 23.94 MW | 23.94 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 957432 | AF2-037 E | 50/50 | 15.96 MW | 15.96 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 957691 | AF2-063 C | 50/50 | 38.2 MW | 38.2 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 957692 | AF2-063 E | 50/50 | 25.47 MW | 25.47 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 962841 | AG1-133 C | 50/50 | 46.09 MW | 46.09 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 962842 | AG1-133 E | 50/50 | 30.72 MW | 30.72 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 963291 | AG1-178 C | 50/50 | 64.9 MW | 64.9 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 963351 | AG1-184 C | 50/50 | 34.96 MW | 34.96 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 964421 | AG1-305 C | 50/50 | 30.05 MW | 30.05 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 964422 | AG1-305 E | 50/50 | 20.04 MW | 20.04 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 964951 | AG1-359 C | Adder | 20.47 MW | 17.4 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 965811 | AG1-449 C | 50/50 | 24.04 MW | 24.04 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 934612 | AD1-087 E | Adder | 3.48 MW | 2.96 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 937482 | AD2-202 E | Adder | 1.02 MW | 0.86 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 940481 | AE2-033 C | Adder | 15.28 MW | 12.99 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 940482 | AE2-033 E | Adder | 10.3 MW | 8.76 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 940541 | AE2-040 C | Adder | 2.72 MW | 2.31 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 940641 | AE2-051 C | 50/50 | 17.83 MW | 17.83 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 940642 | AE2-051 E | 50/50 | 11.89 MW | 11.89 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 941282 | AE2-122 E | Adder | 102.75 MW | 87.33 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 945811 | AF1-246 C | Adder | 7.38 MW | 6.28 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 945812 | AF1-246 E | Adder | 10.19 MW | 8.66 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | 316303 | AF2-085 | 50/50 | 4.29 MW | 4.29 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 24.9 MW | 24.9 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 19.76 MW | 19.76 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 86.41 MW | 86.41 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 5.22 MW | 5.22 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | NY | PJM->LTFIMP_NY | CLTF | 2.46 MW | 2.46 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | LGEE | LTFEXP_LGEE->PJM | CLTF | 1.07 MW | 1.07 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | WEC | LTFEXP_WEC->PJM | CLTF | 0.53 MW | 0.53 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | CPLE | LTFEXP_CPLE->PJM | CLTF | 10.28 MW | 10.28 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | TVA | LTFEXP_TVA->PJM | CLTF | 5.48 MW | 5.48 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | MEC | LTFEXP_MEC->PJM | CLTF | 3.35 MW | 3.35 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | LAGN | LTFEXP_LAGN->PJM | CLTF | 6.89 MW | 6.89 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.21 MW | 0.21 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 33.25 MW | 33.25 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T575_SRT-S | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 4.9 MW | 4.9 MW |
| Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 314229 | 6MT RD221 | 50/50 | 0.19 MW | 0.19 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 314236 | 6NRTHEST | 50/50 | 0.28 MW | 0.28 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 314250 | 6ROCKVILLE | Adder | 3.55 MW | 3.02 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 314314 | 3LOCKS | Adder | 3.18 MW | 2.71 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 314507 | 3THOMPSN | Adder | 3.6 MW | 3.06 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 314525 | 6KINGFORK | Adder | 1.81 MW | 1.54 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 314550 | 6HICKORY | Adder | 3.86 MW | 3.28 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 315060 | 1CHESTF5 | 50/50 | 117.16 MW | 117.16 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 315061 | 1CHESTG7 | 50/50 | 6.03 MW | 6.03 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 315062 | 1CHESTS7 | 50/50 | 2.77 MW | 2.77 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 315063 | 1CHESTG8 | 50/50 | 5.94 MW | 5.94 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 315064 | 1CHESTS8 | 50/50 | 3.06 MW | 3.06 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 315065 | 1CHESTF6 | Adder | 35.04 MW | 29.79 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 315067 | 1DARBY 1 | 50/50 | 3.96 MW | 3.96 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 315068 | 1DARBY 2 | 50/50 | 3.96 MW | 3.96 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 315069 | 1DARBY 3 | 50/50 | 3.98 MW | 3.98 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 315070 | 1DARBY 4 | 50/50 | 3.98 MW | 3.98 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 315073 | 1STONECA | Adder | 12.52 MW | 10.64 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 315083 | 1SPRUNCA | Adder | 16.04 MW | 13.63 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 315084 | 1SPRUNCB | Adder | 16.04 MW | 13.63 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 315092 | 1YORKTN3 | Adder | 258.88 MW | 220.04 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 926412 | AC1-112 E | 50/50 | 2.1 MW | 2.1 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 926662 | AC1-147 E | Adder | 2.36 MW | 2.01 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 926755 | AC1-161 E | Adder | 23.32 MW | 19.82 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 927226 | AC1-216 E | Adder | 13.97 MW | 11.88 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 934392 | AD1-063 E | Adder | 1.89 MW | 1.6 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 935112 | AD1-144 E | Adder | 1.68 MW | 1.43 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 942152 | AE2-227 E | Adder | 2.65 MW | 2.25 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 942162 | AE2-228 E | Adder | 2.56 MW | 2.17 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 315233 | 1SURRY 2 | 50/50 | 38.94 MW | 38.94 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 315260 | 1GOSPORTA | Adder | 3.8 MW | 3.23 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 315261 | 1GOSPORTB | Adder | 4.85 MW | 4.12 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 315262 | 1GOSPORTC | Adder | 4.11 MW | 3.5 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 316075 | AC2-137 C | 50/50 | 0.6 MW | 0.6 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 316076 | AC2-137 E | 50/50 | 2.51 MW | 2.51 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 316108 | AB2-160 C | Adder | 9.68 MW | 8.22 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 316109 | AB2-160 E | Adder | 15.79 MW | 13.42 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 916192 | Z1-068 E | Adder | 3.34 MW | 2.84 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 923842 | AB2-024 E | Adder | 3.18 MW | 2.71 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 930122 | AB1-027 E | 50/50 | 2.58 MW | 2.58 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 939312 | AE1-162 E | Adder | 2.57 MW | 2.19 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 946262 | AF1-291 E | Adder | 2.56 MW | 2.18 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 957492 | AF2-043 E | Adder | 1.08 MW | 0.92 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 962531 | AG1-102 C | Adder | 1.96 MW | 1.67 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 962532 | AG1-102 E | Adder | 4.09 MW | 3.48 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 962962 | AG1-145 E | 50/50 | 2.69 MW | 2.69 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 925332 | AB2-190 E | Adder | 14.62 MW | 12.43 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 925522 | AC1-027 E | Adder | 2.16 MW | 1.84 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 942001 | AE2-212 C | Adder | 3.8 MW | 3.23 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 942002 | AE2-212 E | Adder | 2.53 MW | 2.15 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 957831 | AF2-077 C | Adder | 3.82 MW | 3.25 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 957832 | AF2-077 E | Adder | 2.55 MW | 2.17 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 957871 | AF2-081 C | Adder | 17.66 MW | 15.01 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 957872 | AF2-081 E | Adder | 7.57 MW | 6.43 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 313811 | 6ELKO L286 | 50/50 | 2.62 MW | 2.62 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 933291 | AC2-141 C | Adder | 54.64 MW | 46.44 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 933292 | AC2-141 E | Adder | 23.32 MW | 19.82 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 934011 | AD1-025 C | Adder | 30.54 MW | 25.96 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 934012 | AD1-025 E | Adder | 18.09 MW | 15.38 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 313053 | 6PAPERMILL | Adder | 11.74 MW | 9.98 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 314632 | 6AYDLETT TAP | Adder | 2.39 MW | 2.03 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 316004 | AC1-112 C | 50/50 | 0.52 MW | 0.52 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 316159 | AE1-175 C | 50/50 | 0.62 MW | 0.62 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 316160 | AE1-175 E | 50/50 | 2.22 MW | 2.22 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 316169 | AC1-164 GEN | 50/50 | 10.63 MW | 10.63 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 316240 | AF1-291 C | Adder | 3.84 MW | 3.27 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 316301 | AE2-228 C | Adder | 3.84 MW | 3.26 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 316304 | AE2-227 C | Adder | 3.98 MW | 3.38 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 316312 | AB1-027 C | 50/50 | 0.83 MW | 0.83 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 316382 | AG1-145 C | 50/50 | 0.56 MW | 0.56 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 926785 | AC1-164_E | 50/50 | 34.6 MW | 34.6 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 934065 | AD1-033 E | Adder | 8.9 MW | 7.57 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 937226 | AE2-253 E | Adder | 10.33 MW | 8.78 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 963221 | AG1-171 C | Adder | 3.89 MW | 3.31 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 963222 | AG1-171 E | Adder | 2.59 MW | 2.21 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 963231 | AG1-172 C | Adder | 3.89 MW | 3.31 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 963232 | AG1-172 E | Adder | 2.59 MW | 2.21 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 963241 | AG1-173 C | Adder | 3.89 MW | 3.31 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 963242 | AG1-173 E | Adder | 2.59 MW | 2.21 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 963251 | AG1-174 C | Adder | 3.89 MW | 3.31 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 963252 | AG1-174 E | Adder | 2.59 MW | 2.21 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 919153 | AA1-139 E2 | Adder | 7.22 MW | 6.14 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 919152 | AA1-139 E1 | Adder | 7.22 MW | 6.14 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 924814 | AB2-134 E | Adder | 22.89 MW | 19.46 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 932046 | AC2-012 E | Adder | 23.35 MW | 19.85 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 961611 | AG1-000B C | Adder | 28.76 MW | 24.45 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 941291 | AE2-123 C | Adder | 51.97 MW | 44.17 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 941292 | AE2-123 E | Adder | 202.66 MW | 172.26 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 941301 | AE2-124 C | Adder | 47.25 MW | 40.16 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 941302 | AE2-124 E | Adder | 207.32 MW | 176.22 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 941591 | AE2-156 C | Adder | 31.91 MW | 27.12 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 942371 | AE2-250 C | Adder | 17.19 MW | 14.61 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 942372 | AE2-250 E | Adder | 9.07 MW | 7.71 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 942551 | AE2-270 C | Adder | 48.64 MW | 41.34 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 944581 | AF1-123 C | Adder | 85.38 MW | 72.57 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 944582 | AF1-123 E | Adder | 195.48 MW | 166.16 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 944591 | AF1-124 C | Adder | 85.38 MW | 72.57 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 944592 | AF1-124 E | Adder | 195.48 MW | 166.16 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 944601 | AF1-125 C | Adder | 85.38 MW | 72.57 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 944602 | AF1-125 E | Adder | 195.48 MW | 166.16 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 944631 | AF1-128 C | 50/50 | 73.31 MW | 73.31 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 945361 | AF1-201 C | Adder | 28.99 MW | 24.64 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 945362 | AF1-201 E | Adder | 19.33 MW | 16.43 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 957711 | AF2-065 C | Adder | 24.8 MW | 21.08 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 957712 | AF2-065 E | Adder | 23.83 MW | 20.26 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 961711 | AG1-011 C | Adder | 51.88 MW | 44.1 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 962271 | AG1-075 C | Adder | 29.66 MW | 25.21 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 962272 | AG1-075 E | Adder | 18.08 MW | 15.37 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 964951 | AG1-359 C | Adder | 40.52 MW | 34.44 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 965001 | AG1-364 C | Adder | 12.76 MW | 10.85 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 965002 | AG1-364 E | Adder | 19.15 MW | 16.27 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 965281 | AG1-393 C | Adder | 3.82 MW | 3.25 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 965282 | AG1-393 E | Adder | 2.55 MW | 2.16 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 966611 | AG1-531 C | Adder | 10.55 MW | 8.97 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 966612 | AG1-531 E | Adder | 7.04 MW | 5.98 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 935161 | AD1-151 C | Adder | 29.22 MW | 24.83 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 935162 | AD1-151 E | Adder | 19.48 MW | 16.55 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 938531 | AE1-072 C | Adder | 31.02 MW | 26.36 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 938532 | AE1-072 E | Adder | 16.17 MW | 13.74 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 939191 | AE1-149 C | Adder | 18.88 MW | 16.05 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 939192 | AE1-149 E | Adder | 12.58 MW | 10.7 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 940431 | AE2-027 C | Adder | 22.98 MW | 19.53 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 940432 | AE2-027 E | Adder | 15.32 MW | 13.02 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 940551 | AE2-041 C | Adder | 12.57 MW | 10.68 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 940651 | AE2-052 C | Adder | 6.29 MW | 5.35 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 941281 | AE2-122 C | Adder | 50.57 MW | 42.98 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 941282 | AE2-122 E | Adder | 204.06 MW | 173.45 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 943471 | AF1-018 C | Adder | 12.57 MW | 10.68 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | 944641 | AF1-129 C | Adder | 182.76 MW | 155.34 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 84.62 MW | 84.62 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 48.91 MW | 48.91 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 157.97 MW | 157.97 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 9.26 MW | 9.26 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | NY | PJM->LTFIMP_NY | CLTF | 4.15 MW | 4.15 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | LGEE | LTFEXP_LGEE->PJM | CLTF | 3.37 MW | 3.37 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | WEC | LTFEXP_WEC->PJM | CLTF | 1.73 MW | 1.73 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | CPLE | LTFEXP_CPLE->PJM | CLTF | 17.77 MW | 17.77 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | TVA | LTFEXP_TVA->PJM | CLTF | 12.47 MW | 12.47 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | MEC | LTFEXP_MEC->PJM | CLTF | 9.61 MW | 9.61 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | LAGN | LTFEXP_LAGN->PJM | CLTF | 15.55 MW | 15.55 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.62 MW | 0.62 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 58.81 MW | 58.81 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 8.48 MW | 8.48 MW |
| Details for AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 961791 | AG1-021 C | Adder | 1.62 MW | 1.38 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 961792 | AG1-021 E | Adder | 1.08 MW | 0.92 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 961891 | AG1-030 C | Adder | 12.19 MW | 10.36 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 961892 | AG1-030 E | Adder | 8.13 MW | 6.91 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 963041 | AG1-153 C | Adder | 5.41 MW | 4.6 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 963042 | AG1-153 E | Adder | 8.11 MW | 6.9 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 963111 | AG1-160 C | Adder | 5.48 MW | 4.66 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 963112 | AG1-160 E | Adder | 8.23 MW | 6.99 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 963171 | AG1-166 C | Adder | 1.62 MW | 1.38 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 963172 | AG1-166 E | Adder | 1.08 MW | 0.92 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 963181 | AG1-167 C | Adder | 1.62 MW | 1.38 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 963182 | AG1-167 E | Adder | 1.08 MW | 0.92 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 963191 | AG1-168 C | Adder | 1.62 MW | 1.38 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 963192 | AG1-168 E | Adder | 1.08 MW | 0.92 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 963201 | AG1-169 C | Adder | 1.62 MW | 1.38 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 963202 | AG1-169 E | Adder | 1.08 MW | 0.92 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 963211 | AG1-170 C | Adder | 1.62 MW | 1.38 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 963212 | AG1-170 E | Adder | 1.08 MW | 0.92 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 963301 | AG1-179 C | Adder | 4.72 MW | 4.01 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 964111 | AG1-272 C | Adder | 2.1 MW | 1.79 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 964112 | AG1-272 E | Adder | 0.62 MW | 0.53 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 964121 | AG1-273 C | Adder | 2.1 MW | 1.79 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 964122 | AG1-273 E | Adder | 0.62 MW | 0.53 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 964131 | AG1-274 C | Adder | 2.1 MW | 1.79 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 964132 | AG1-274 E | Adder | 0.62 MW | 0.53 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 964791 | AG1-342 C | Adder | 3.38 MW | 2.88 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 964792 | AG1-342 E | Adder | 2.66 MW | 2.26 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 966811 | AG1-552 C | Adder | 1.65 MW | 1.4 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 966812 | AG1-552 E | Adder | 0.78 MW | 0.67 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 965191 | AG1-384 C | Adder | 2.1 MW | 1.79 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 965192 | AG1-384 E | Adder | 0.62 MW | 0.53 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 965591 | AG1-427 C | Adder | 9.77 MW | 8.3 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 965592 | AG1-427 E | Adder | 6.51 MW | 5.54 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 965721 | AG1-440 C | Adder | 6.18 MW | 5.25 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 965722 | AG1-440 E | Adder | 4.12 MW | 3.5 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 965731 | AG1-441 C | Adder | 6.18 MW | 5.25 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 965732 | AG1-441 E | Adder | 4.12 MW | 3.5 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 966361 | AG1-505 C | Adder | 16.11 MW | 13.7 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 966362 | AG1-505 E | Adder | 10.74 MW | 9.13 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 966371 | AG1-506 C | Adder | 16.11 MW | 13.7 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 966372 | AG1-506 E | Adder | 10.74 MW | 9.13 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 966621 | AG1-532 C | Adder | 1.15 MW | 0.97 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 966622 | AG1-532 E | Adder | 0.76 MW | 0.65 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 313853 | 3PONTONDP | Adder | 0.54 MW | 0.46 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 314572 | 3EMPORIA | Adder | 0.35 MW | 0.3 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 314713 | 3PAMPLIN | Adder | 0.8 MW | 0.68 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 918492 | AA1-063AE OP | Adder | 3.24 MW | 2.76 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 919692 | AA2-053 E OP | Adder | 3.38 MW | 2.87 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 925785 | AC1-054 E | Adder | 2.8 MW | 2.38 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 942931 | AE2-313 C | Adder | 35.16 MW | 29.89 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 942932 | AE2-313 E | Adder | 23.44 MW | 19.92 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 944011 | AF1-069 C | 50/50 | 12.76 MW | 12.76 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 944012 | AF1-069 E | 50/50 | 4.96 MW | 4.96 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 958801 | AF2-171 C | Adder | 12.15 MW | 10.33 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 958802 | AF2-171 E | Adder | 8.1 MW | 6.88 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 959311 | AF2-222 C | Adder | 13.61 MW | 11.57 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 959312 | AF2-222 E | Adder | 9.12 MW | 7.75 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 960081 | AF2-299 C | Adder | 2.12 MW | 1.81 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 960082 | AF2-299 E | Adder | 1.42 MW | 1.2 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 923263 | AB1-132 E OP | Adder | 4.91 MW | 4.17 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 923573 | AB1-173 E OP | Adder | 2.66 MW | 2.26 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 924162 | AB2-060 E OP | Adder | 3.52 MW | 3.0 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 924302 | AB2-077 E O1 | Adder | 1.1 MW | 0.94 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 924312 | AB2-078 E O1 | Adder | 1.1 MW | 0.94 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 924322 | AB2-079 E O1 | Adder | 1.1 MW | 0.94 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 925612 | AC1-036 E | Adder | 0.7 MW | 0.6 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 938371 | AE1-056 C | Adder | 5.22 MW | 4.44 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 938372 | AE1-056 E | Adder | 2.85 MW | 2.42 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 939181 | AE1-148 C | Adder | 7.44 MW | 6.32 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 939182 | AE1-148 E | Adder | 4.96 MW | 4.21 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 941031 | AE2-094 C | 50/50 | 39.04 MW | 39.04 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 941032 | AE2-094 E | 50/50 | 17.48 MW | 17.48 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 941791 | AE2-182 C | Adder | 1.7 MW | 1.44 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 941792 | AE2-182 E | Adder | 0.79 MW | 0.67 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 946281 | AF1-292 C | Adder | 1.27 MW | 1.08 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 946282 | AF1-292 E | Adder | 0.84 MW | 0.72 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 946301 | AF1-294 C | Adder | 3.32 MW | 2.82 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 946302 | AF1-294 E | Adder | 2.21 MW | 1.88 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 957481 | AF2-042 C | Adder | 49.63 MW | 42.18 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 957482 | AF2-042 E | Adder | 33.09 MW | 28.12 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 958211 | AF2-115 C | Adder | 2.02 MW | 1.72 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 958212 | AF2-115 E | Adder | 1.35 MW | 1.15 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 933502 | AC2-165 E | Adder | 6.88 MW | 5.84 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 314331 | 6POE | Adder | 1.04 MW | 0.89 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 314550 | 6HICKORY | Adder | 1.63 MW | 1.38 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 926755 | AC1-161 E | Adder | 9.62 MW | 8.18 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 958502 | AF2-144 E | Adder | 1.15 MW | 0.98 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 315172 | 1LOISA A | 50/50 | 2.63 MW | 2.63 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 315173 | 1LOISA B | 50/50 | 2.64 MW | 2.64 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 315174 | 1LOISA C | 50/50 | 2.64 MW | 2.64 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 315175 | 1LOISA D | 50/50 | 2.64 MW | 2.64 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 315176 | 1LOISA E | 50/50 | 5.39 MW | 5.39 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 315177 | 1S ANNAG1 | 50/50 | 2.6 MW | 2.6 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 315178 | 1S ANNAS1 | 50/50 | 1.33 MW | 1.33 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 315179 | 1S ANNAG2 | 50/50 | 2.6 MW | 2.6 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 315180 | 1S ANNAS2 | 50/50 | 1.33 MW | 1.33 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 315225 | 1N ANNA1 | 50/50 | 90.72 MW | 90.72 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 315226 | 1N ANNA2 | 50/50 | 90.73 MW | 90.73 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 923852 | AB2-025 E | Adder | 0.98 MW | 0.83 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 923862 | AB2-026 E | Adder | 1.17 MW | 0.99 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 925022 | AB2-158 E | 50/50 | 11.41 MW | 11.41 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 938552 | AE1-074 E | Adder | 1.09 MW | 0.93 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 938562 | AE1-075 E | Adder | 1.0 MW | 0.85 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 946371 | AF1-301 C | 50/50 | 21.15 MW | 21.15 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 946372 | AF1-301 E | 50/50 | 14.2 MW | 14.2 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 966001 | AG1-469 C | 50/50 | 2.02 MW | 2.02 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 966002 | AG1-469 E | 50/50 | 1.01 MW | 1.01 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 957871 | AF2-081 C | Adder | 6.41 MW | 5.45 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 314722 | 3TWITTYS | Adder | 0.78 MW | 0.66 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 926071 | AC1-086 C | Adder | 16.87 MW | 14.34 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 926072 | AC1-086 E | Adder | 7.68 MW | 6.53 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 936261 | AD2-033 C | Adder | 10.65 MW | 9.05 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 936262 | AD2-033 E | Adder | 7.1 MW | 6.04 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 933291 | AC2-141 C | Adder | 22.54 MW | 19.16 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 933292 | AC2-141 E | Adder | 9.62 MW | 8.18 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 934621 | AD1-088 C | Adder | 10.43 MW | 8.87 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 934622 | AD1-088 E | Adder | 4.91 MW | 4.17 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 939411 | AE1-173 C | Adder | 82.49 MW | 70.12 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 939412 | AE1-173 E | Adder | 54.99 MW | 46.74 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 962572 | AG1-106 E | Adder | 2.13 MW | 1.81 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 962571 | AG1-106 C | Adder | 4.69 MW | 3.99 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 208900 | BRIS G1 | 50/50 | -2.05 MW | -2.05 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 208901 | BRIS G2 | 50/50 | -2.43 MW | -2.43 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 316192 | AB2-158 C | 50/50 | 3.66 MW | 3.66 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 316233 | AE1-074 C | Adder | 2.16 MW | 1.84 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 316336 | AC2-165 C | Adder | 9.14 MW | 7.76 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 924516 | AB2-100 E1 | Adder | 2.38 MW | 2.02 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 924517 | AB2-100 E2 | Adder | 2.38 MW | 2.02 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 934065 | AD1-033 E | Adder | 3.74 MW | 3.18 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 937226 | AE2-253 E | Adder | 4.37 MW | 3.71 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 316181 | AB2-040 GEN | Adder | 6.1 MW | 5.19 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 923994 | AB2-040_E | Adder | 4.99 MW | 4.25 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 924022 | AB2-043 E O1 | Adder | 4.27 MW | 3.63 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 316088 | AB2-174 E | Adder | 5.31 MW | 4.51 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 940661 | AE2-053 C | Adder | 2.76 MW | 2.34 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 944581 | AF1-123 C | Adder | 36.12 MW | 30.7 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 944582 | AF1-123 E | Adder | 82.7 MW | 70.3 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 944591 | AF1-124 C | Adder | 36.12 MW | 30.7 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 944592 | AF1-124 E | Adder | 82.7 MW | 70.3 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 944601 | AF1-125 C | Adder | 36.12 MW | 30.7 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 944602 | AF1-125 E | Adder | 82.7 MW | 70.3 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 946011 | AF1-266 C | Adder | 11.39 MW | 9.68 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 957431 | AF2-037 C | 50/50 | 28.36 MW | 28.36 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 957432 | AF2-037 E | 50/50 | 18.91 MW | 18.91 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 957691 | AF2-063 C | 50/50 | 45.26 MW | 45.26 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 957692 | AF2-063 E | 50/50 | 30.17 MW | 30.17 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 962491 | AG1-098 C | Adder | 9.4 MW | 7.99 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 962492 | AG1-098 E | Adder | 6.26 MW | 5.32 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 962561 | AG1-105 C | Adder | 7.28 MW | 6.19 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 962562 | AG1-105 E | Adder | 4.85 MW | 4.12 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 962841 | AG1-133 C | 50/50 | 57.48 MW | 57.48 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 962842 | AG1-133 E | 50/50 | 38.32 MW | 38.32 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 963291 | AG1-178 C | Adder | 60.68 MW | 51.58 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 963311 | AG1-180 C | Adder | 2.29 MW | 1.95 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 963321 | AG1-181 C | Adder | 13.8 MW | 11.73 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 963351 | AG1-184 C | Adder | 32.69 MW | 27.79 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 963361 | AG1-185 C | Adder | 6.68 MW | 5.67 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 964241 | AG1-285 C | Adder | 10.29 MW | 8.75 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 964242 | AG1-285 E | Adder | 6.86 MW | 5.83 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 964421 | AG1-305 C | 50/50 | 35.6 MW | 35.6 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 964422 | AG1-305 E | 50/50 | 23.73 MW | 23.73 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 964951 | AG1-359 C | Adder | 17.05 MW | 14.49 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 965601 | AG1-428 C | Adder | 3.94 MW | 3.35 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 965602 | AG1-428 E | Adder | 2.62 MW | 2.23 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 965771 | AG1-445 C | Adder | 3.57 MW | 3.04 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 965781 | AG1-446 C | Adder | 3.57 MW | 3.04 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 965811 | AG1-449 C | Adder | 22.77 MW | 19.35 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 313764 | 3SOCKMAN | Adder | 0.58 MW | 0.49 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 934612 | AD1-087 E | Adder | 3.27 MW | 2.78 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 935172 | AD1-152 E | Adder | 4.8 MW | 4.08 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 937482 | AD2-202 E | Adder | 0.96 MW | 0.81 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 940481 | AE2-033 C | Adder | 13.6 MW | 11.56 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 940482 | AE2-033 E | Adder | 9.17 MW | 7.79 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 940541 | AE2-040 C | Adder | 2.42 MW | 2.06 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 940641 | AE2-051 C | Adder | 16.6 MW | 14.11 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 940642 | AE2-051 E | Adder | 11.07 MW | 9.41 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 945811 | AF1-246 C | Adder | 6.95 MW | 5.91 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 945812 | AF1-246 E | Adder | 9.6 MW | 8.16 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 316303 | AF2-085 | 50/50 | 4.04 MW | 4.04 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 22.11 MW | 22.11 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 17.63 MW | 17.63 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 78.39 MW | 78.39 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 4.92 MW | 4.92 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | NY | PJM->LTFIMP_NY | CLTF | 2.3 MW | 2.3 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.94 MW | 0.94 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | WEC | LTFEXP_WEC->PJM | CLTF | 0.47 MW | 0.47 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | CPLE | LTFEXP_CPLE->PJM | CLTF | 9.37 MW | 9.37 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | TVA | LTFEXP_TVA->PJM | CLTF | 4.89 MW | 4.89 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | MEC | LTFEXP_MEC->PJM | CLTF | 2.98 MW | 2.98 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | LAGN | LTFEXP_LAGN->PJM | CLTF | 6.17 MW | 6.17 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.18 MW | 0.18 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 31.34 MW | 31.34 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 4.46 MW | 4.46 MW |
| Details for AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 961791 | AG1-021 C | Adder | 1.61 MW | 1.37 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 961792 | AG1-021 E | Adder | 1.08 MW | 0.92 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 961891 | AG1-030 C | Adder | 12.15 MW | 10.33 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 961892 | AG1-030 E | Adder | 8.1 MW | 6.89 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 963041 | AG1-153 C | Adder | 5.4 MW | 4.59 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 963042 | AG1-153 E | Adder | 8.1 MW | 6.88 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 963111 | AG1-160 C | Adder | 5.47 MW | 4.65 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 963112 | AG1-160 E | Adder | 8.21 MW | 6.98 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 963171 | AG1-166 C | Adder | 1.61 MW | 1.37 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 963172 | AG1-166 E | Adder | 1.08 MW | 0.92 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 963181 | AG1-167 C | Adder | 1.61 MW | 1.37 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 963182 | AG1-167 E | Adder | 1.08 MW | 0.92 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 963191 | AG1-168 C | Adder | 1.61 MW | 1.37 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 963192 | AG1-168 E | Adder | 1.08 MW | 0.92 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 963201 | AG1-169 C | Adder | 1.61 MW | 1.37 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 963202 | AG1-169 E | Adder | 1.08 MW | 0.92 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 963211 | AG1-170 C | Adder | 1.61 MW | 1.37 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 963212 | AG1-170 E | Adder | 1.08 MW | 0.92 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 963301 | AG1-179 C | Adder | 4.71 MW | 4.0 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 964111 | AG1-272 C | Adder | 2.1 MW | 1.78 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 964112 | AG1-272 E | Adder | 0.62 MW | 0.53 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 964121 | AG1-273 C | Adder | 2.1 MW | 1.78 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 964122 | AG1-273 E | Adder | 0.62 MW | 0.53 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 964131 | AG1-274 C | Adder | 2.1 MW | 1.78 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 964132 | AG1-274 E | Adder | 0.62 MW | 0.53 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 964791 | AG1-342 C | Adder | 3.37 MW | 2.87 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 964792 | AG1-342 E | Adder | 2.65 MW | 2.25 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 966811 | AG1-552 C | Adder | 1.65 MW | 1.4 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 966812 | AG1-552 E | Adder | 0.78 MW | 0.67 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 965191 | AG1-384 C | Adder | 2.1 MW | 1.78 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 965192 | AG1-384 E | Adder | 0.62 MW | 0.53 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 965291 | AG1-394 C | Adder | 1.6 MW | 1.36 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 965292 | AG1-394 E | Adder | 1.06 MW | 0.9 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 965591 | AG1-427 C | Adder | 9.74 MW | 8.28 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 965592 | AG1-427 E | Adder | 6.5 MW | 5.52 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 965721 | AG1-440 C | Adder | 6.16 MW | 5.24 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 965722 | AG1-440 E | Adder | 4.11 MW | 3.49 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 965731 | AG1-441 C | Adder | 6.16 MW | 5.24 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 965732 | AG1-441 E | Adder | 4.11 MW | 3.49 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 966361 | AG1-505 C | Adder | 16.08 MW | 13.66 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 966362 | AG1-505 E | Adder | 10.72 MW | 9.11 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 966371 | AG1-506 C | Adder | 16.08 MW | 13.66 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 966372 | AG1-506 E | Adder | 10.72 MW | 9.11 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 966621 | AG1-532 C | Adder | 1.14 MW | 0.97 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 966622 | AG1-532 E | Adder | 0.76 MW | 0.65 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 313853 | 3PONTONDP | Adder | 0.54 MW | 0.46 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 314572 | 3EMPORIA | Adder | 0.35 MW | 0.3 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 314713 | 3PAMPLIN | Adder | 0.8 MW | 0.68 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 918492 | AA1-063AE OP | Adder | 3.23 MW | 2.75 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 919692 | AA2-053 E OP | Adder | 3.37 MW | 2.86 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 925785 | AC1-054 E | Adder | 2.79 MW | 2.38 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 942931 | AE2-313 C | Adder | 35.08 MW | 29.82 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 942932 | AE2-313 E | Adder | 23.39 MW | 19.88 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 944011 | AF1-069 C | 50/50 | 12.73 MW | 12.73 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 944012 | AF1-069 E | 50/50 | 4.94 MW | 4.94 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 958801 | AF2-171 C | Adder | 12.11 MW | 10.29 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 958802 | AF2-171 E | Adder | 8.08 MW | 6.86 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 959311 | AF2-222 C | Adder | 13.57 MW | 11.53 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 959312 | AF2-222 E | Adder | 9.09 MW | 7.73 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 960081 | AF2-299 C | Adder | 2.12 MW | 1.8 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 960082 | AF2-299 E | Adder | 1.41 MW | 1.2 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 923263 | AB1-132 E OP | Adder | 4.9 MW | 4.16 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 923573 | AB1-173 E OP | Adder | 2.66 MW | 2.26 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 924162 | AB2-060 E OP | Adder | 3.51 MW | 2.99 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 924302 | AB2-077 E O1 | Adder | 1.1 MW | 0.93 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 924312 | AB2-078 E O1 | Adder | 1.1 MW | 0.93 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 924322 | AB2-079 E O1 | Adder | 1.1 MW | 0.93 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 925612 | AC1-036 E | Adder | 0.7 MW | 0.59 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 938371 | AE1-056 C | Adder | 5.2 MW | 4.42 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 938372 | AE1-056 E | Adder | 2.84 MW | 2.42 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 939181 | AE1-148 C | Adder | 7.42 MW | 6.3 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 939182 | AE1-148 E | Adder | 4.94 MW | 4.2 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 941031 | AE2-094 C | 50/50 | 38.95 MW | 38.95 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 941032 | AE2-094 E | 50/50 | 17.45 MW | 17.45 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 941791 | AE2-182 C | Adder | 1.69 MW | 1.44 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 941792 | AE2-182 E | Adder | 0.79 MW | 0.67 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 946281 | AF1-292 C | Adder | 1.26 MW | 1.07 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 946282 | AF1-292 E | Adder | 0.84 MW | 0.72 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 946301 | AF1-294 C | Adder | 3.31 MW | 2.81 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 946302 | AF1-294 E | Adder | 2.21 MW | 1.88 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 957481 | AF2-042 C | Adder | 49.51 MW | 42.08 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 957482 | AF2-042 E | Adder | 33.01 MW | 28.05 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 958211 | AF2-115 C | Adder | 2.02 MW | 1.72 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 958212 | AF2-115 E | Adder | 1.35 MW | 1.14 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 933502 | AC2-165 E | Adder | 6.85 MW | 5.83 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 314331 | 6POE | Adder | 1.04 MW | 0.88 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 314550 | 6HICKORY | Adder | 1.62 MW | 1.38 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 926755 | AC1-161 E | Adder | 9.59 MW | 8.15 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 958502 | AF2-144 E | Adder | 1.14 MW | 0.97 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 315172 | 1LOISA A | 50/50 | 2.6 MW | 2.6 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 315173 | 1LOISA B | 50/50 | 2.62 MW | 2.62 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 315174 | 1LOISA C | 50/50 | 2.62 MW | 2.62 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 315175 | 1LOISA D | 50/50 | 2.62 MW | 2.62 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 315176 | 1LOISA E | 50/50 | 5.34 MW | 5.34 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 315177 | 1S ANNAG1 | 50/50 | 2.57 MW | 2.57 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 315178 | 1S ANNAS1 | 50/50 | 1.32 MW | 1.32 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 315179 | 1S ANNAG2 | 50/50 | 2.57 MW | 2.57 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 315180 | 1S ANNAS2 | 50/50 | 1.32 MW | 1.32 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 315225 | 1N ANNA1 | 50/50 | 90.64 MW | 90.64 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 315226 | 1N ANNA2 | 50/50 | 90.65 MW | 90.65 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 923852 | AB2-025 E | Adder | 0.98 MW | 0.83 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 923862 | AB2-026 E | Adder | 1.17 MW | 0.99 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 925022 | AB2-158 E | 50/50 | 11.36 MW | 11.36 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 938552 | AE1-074 E | Adder | 1.09 MW | 0.92 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 938562 | AE1-075 E | Adder | 0.99 MW | 0.84 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 946371 | AF1-301 C | 50/50 | 21.01 MW | 21.01 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 946372 | AF1-301 E | 50/50 | 14.11 MW | 14.11 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 966001 | AG1-469 C | 50/50 | 1.98 MW | 1.98 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 966002 | AG1-469 E | 50/50 | 0.99 MW | 0.99 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 957871 | AF2-081 C | Adder | 3.73 MW | 3.17 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 314722 | 3TWITTYS | Adder | 0.78 MW | 0.66 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 926071 | AC1-086 C | Adder | 16.82 MW | 14.3 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 926072 | AC1-086 E | Adder | 7.66 MW | 6.51 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 936261 | AD2-033 C | Adder | 10.62 MW | 9.03 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 936262 | AD2-033 E | Adder | 7.08 MW | 6.02 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 933291 | AC2-141 C | Adder | 22.46 MW | 19.09 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 933292 | AC2-141 E | Adder | 9.59 MW | 8.15 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 934621 | AD1-088 C | Adder | 10.4 MW | 8.84 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 934622 | AD1-088 E | Adder | 4.9 MW | 4.16 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 939411 | AE1-173 C | Adder | 82.29 MW | 69.94 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 939412 | AE1-173 E | Adder | 54.86 MW | 46.63 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 962572 | AG1-106 E | Adder | 2.12 MW | 1.8 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 962571 | AG1-106 C | Adder | 4.68 MW | 3.98 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 208900 | BRIS G1 | 50/50 | -2.05 MW | -2.05 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 208901 | BRIS G2 | 50/50 | -2.42 MW | -2.42 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 316192 | AB2-158 C | 50/50 | 3.64 MW | 3.64 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 316233 | AE1-074 C | Adder | 2.16 MW | 1.83 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 316336 | AC2-165 C | Adder | 9.11 MW | 7.74 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 924516 | AB2-100 E1 | Adder | 2.37 MW | 2.01 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 924517 | AB2-100 E2 | Adder | 2.37 MW | 2.01 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 934065 | AD1-033 E | Adder | 3.73 MW | 3.17 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 937226 | AE2-253 E | Adder | 4.35 MW | 3.7 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 316181 | AB2-040 GEN | Adder | 6.09 MW | 5.17 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 923994 | AB2-040_E | Adder | 4.98 MW | 4.23 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 924022 | AB2-043 E O1 | Adder | 4.26 MW | 3.62 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 316088 | AB2-174 E | Adder | 5.29 MW | 4.5 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 940661 | AE2-053 C | Adder | 2.75 MW | 2.33 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 944581 | AF1-123 C | Adder | 36.0 MW | 30.6 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 944582 | AF1-123 E | Adder | 82.44 MW | 70.08 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 944591 | AF1-124 C | Adder | 36.0 MW | 30.6 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 944592 | AF1-124 E | Adder | 82.44 MW | 70.08 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 944601 | AF1-125 C | Adder | 36.0 MW | 30.6 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 944602 | AF1-125 E | Adder | 82.44 MW | 70.08 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 946011 | AF1-266 C | Adder | 11.36 MW | 9.65 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 957431 | AF2-037 C | 50/50 | 28.29 MW | 28.29 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 957432 | AF2-037 E | 50/50 | 18.86 MW | 18.86 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 957691 | AF2-063 C | 50/50 | 45.14 MW | 45.14 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 957692 | AF2-063 E | 50/50 | 30.09 MW | 30.09 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 962491 | AG1-098 C | Adder | 9.37 MW | 7.96 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 962492 | AG1-098 E | Adder | 6.24 MW | 5.31 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 962561 | AG1-105 C | Adder | 7.26 MW | 6.17 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 962562 | AG1-105 E | Adder | 4.84 MW | 4.11 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 962841 | AG1-133 C | 50/50 | 57.44 MW | 57.44 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 962842 | AG1-133 E | 50/50 | 38.29 MW | 38.29 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 963291 | AG1-178 C | Adder | 60.54 MW | 51.46 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 963311 | AG1-180 C | Adder | 2.28 MW | 1.94 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 963321 | AG1-181 C | Adder | 13.76 MW | 11.69 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 963351 | AG1-184 C | Adder | 32.62 MW | 27.73 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 963361 | AG1-185 C | Adder | 6.66 MW | 5.66 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 964241 | AG1-285 C | Adder | 10.26 MW | 8.72 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 964242 | AG1-285 E | Adder | 6.84 MW | 5.82 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 964421 | AG1-305 C | 50/50 | 35.51 MW | 35.51 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 964422 | AG1-305 E | 50/50 | 23.67 MW | 23.67 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 964951 | AG1-359 C | Adder | 17.0 MW | 14.45 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 965601 | AG1-428 C | Adder | 3.93 MW | 3.34 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 965602 | AG1-428 E | Adder | 2.62 MW | 2.23 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 965771 | AG1-445 C | Adder | 3.56 MW | 3.03 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 965781 | AG1-446 C | Adder | 3.56 MW | 3.03 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 965811 | AG1-449 C | Adder | 22.72 MW | 19.31 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 313764 | 3SOCKMAN | Adder | 0.57 MW | 0.49 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 934612 | AD1-087 E | Adder | 3.26 MW | 2.77 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 935172 | AD1-152 E | Adder | 4.79 MW | 4.07 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 937482 | AD2-202 E | Adder | 0.95 MW | 0.81 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 940481 | AE2-033 C | Adder | 13.57 MW | 11.53 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 940482 | AE2-033 E | Adder | 9.15 MW | 7.78 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 940541 | AE2-040 C | Adder | 2.42 MW | 2.05 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 940641 | AE2-051 C | Adder | 16.56 MW | 14.08 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 940642 | AE2-051 E | Adder | 11.04 MW | 9.39 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 945811 | AF1-246 C | Adder | 6.93 MW | 5.89 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 945812 | AF1-246 E | Adder | 9.57 MW | 8.14 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 316303 | AF2-085 | 50/50 | 4.03 MW | 4.03 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 22.04 MW | 22.04 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 17.57 MW | 17.57 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 78.17 MW | 78.17 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 4.91 MW | 4.91 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | NY | PJM->LTFIMP_NY | CLTF | 2.29 MW | 2.29 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.94 MW | 0.94 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | WEC | LTFEXP_WEC->PJM | CLTF | 0.47 MW | 0.47 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | CPLE | LTFEXP_CPLE->PJM | CLTF | 9.34 MW | 9.34 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | TVA | LTFEXP_TVA->PJM | CLTF | 4.88 MW | 4.88 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | MEC | LTFEXP_MEC->PJM | CLTF | 2.97 MW | 2.97 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | LAGN | LTFEXP_LAGN->PJM | CLTF | 6.15 MW | 6.15 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.18 MW | 0.18 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 31.24 MW | 31.24 MW |
| AG1-133 TP-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 4.45 MW | 4.45 MW |
| Details for 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 961791 | AG1-021 C | Adder | 1.62 MW | 1.38 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 961792 | AG1-021 E | Adder | 1.08 MW | 0.92 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 961891 | AG1-030 C | Adder | 12.19 MW | 10.36 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 961892 | AG1-030 E | Adder | 8.13 MW | 6.91 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 963041 | AG1-153 C | Adder | 5.41 MW | 4.6 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 963042 | AG1-153 E | Adder | 8.11 MW | 6.9 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 963111 | AG1-160 C | Adder | 5.48 MW | 4.66 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 963112 | AG1-160 E | Adder | 8.23 MW | 6.99 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 963171 | AG1-166 C | Adder | 1.62 MW | 1.38 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 963172 | AG1-166 E | Adder | 1.08 MW | 0.92 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 963181 | AG1-167 C | Adder | 1.62 MW | 1.38 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 963182 | AG1-167 E | Adder | 1.08 MW | 0.92 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 963191 | AG1-168 C | Adder | 1.62 MW | 1.38 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 963192 | AG1-168 E | Adder | 1.08 MW | 0.92 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 963201 | AG1-169 C | Adder | 1.62 MW | 1.38 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 963202 | AG1-169 E | Adder | 1.08 MW | 0.92 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 963211 | AG1-170 C | Adder | 1.62 MW | 1.38 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 963212 | AG1-170 E | Adder | 1.08 MW | 0.92 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 963301 | AG1-179 C | Adder | 4.72 MW | 4.01 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 964111 | AG1-272 C | Adder | 2.1 MW | 1.79 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 964112 | AG1-272 E | Adder | 0.62 MW | 0.53 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 964121 | AG1-273 C | Adder | 2.1 MW | 1.79 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 964122 | AG1-273 E | Adder | 0.62 MW | 0.53 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 964131 | AG1-274 C | Adder | 2.1 MW | 1.79 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 964132 | AG1-274 E | Adder | 0.62 MW | 0.53 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 964791 | AG1-342 C | Adder | 3.38 MW | 2.88 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 964792 | AG1-342 E | Adder | 2.66 MW | 2.26 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 966811 | AG1-552 C | Adder | 1.65 MW | 1.4 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 966812 | AG1-552 E | Adder | 0.78 MW | 0.67 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 965191 | AG1-384 C | Adder | 2.1 MW | 1.79 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 965192 | AG1-384 E | Adder | 0.62 MW | 0.53 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 965291 | AG1-394 C | Adder | 1.6 MW | 1.36 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 965292 | AG1-394 E | Adder | 1.07 MW | 0.91 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 965591 | AG1-427 C | Adder | 9.77 MW | 8.3 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 965592 | AG1-427 E | Adder | 6.51 MW | 5.54 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 965721 | AG1-440 C | Adder | 6.18 MW | 5.25 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 965722 | AG1-440 E | Adder | 4.12 MW | 3.5 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 965731 | AG1-441 C | Adder | 6.18 MW | 5.25 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 965732 | AG1-441 E | Adder | 4.12 MW | 3.5 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 966361 | AG1-505 C | Adder | 16.11 MW | 13.7 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 966362 | AG1-505 E | Adder | 10.74 MW | 9.13 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 966371 | AG1-506 C | Adder | 16.11 MW | 13.7 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 966372 | AG1-506 E | Adder | 10.74 MW | 9.13 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 966621 | AG1-532 C | Adder | 1.15 MW | 0.97 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 966622 | AG1-532 E | Adder | 0.76 MW | 0.65 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 313853 | 3PONTONDP | Adder | 0.54 MW | 0.46 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 314572 | 3EMPORIA | Adder | 0.35 MW | 0.3 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 314713 | 3PAMPLIN | Adder | 0.8 MW | 0.68 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 918492 | AA1-063AE OP | Adder | 3.24 MW | 2.76 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 919692 | AA2-053 E OP | Adder | 3.38 MW | 2.87 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 920042 | AA2-088 E OP | Adder | 7.05 MW | 5.99 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 925785 | AC1-054 E | Adder | 2.8 MW | 2.38 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 942931 | AE2-313 C | Adder | 35.16 MW | 29.89 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 942932 | AE2-313 E | Adder | 23.44 MW | 19.92 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 944011 | AF1-069 C | 50/50 | 12.76 MW | 12.76 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 944012 | AF1-069 E | 50/50 | 4.96 MW | 4.96 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 958801 | AF2-171 C | Adder | 12.15 MW | 10.33 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 958802 | AF2-171 E | Adder | 8.1 MW | 6.88 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 959311 | AF2-222 C | Adder | 13.61 MW | 11.57 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 959312 | AF2-222 E | Adder | 9.12 MW | 7.75 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 960081 | AF2-299 C | Adder | 2.12 MW | 1.81 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 960082 | AF2-299 E | Adder | 1.42 MW | 1.2 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 923263 | AB1-132 E OP | Adder | 4.91 MW | 4.17 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 923573 | AB1-173 E OP | Adder | 2.66 MW | 2.26 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 924162 | AB2-060 E OP | Adder | 3.52 MW | 3.0 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 924302 | AB2-077 E O1 | Adder | 1.1 MW | 0.94 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 924312 | AB2-078 E O1 | Adder | 1.1 MW | 0.94 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 924322 | AB2-079 E O1 | Adder | 1.1 MW | 0.94 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 925612 | AC1-036 E | Adder | 0.7 MW | 0.6 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 938371 | AE1-056 C | Adder | 5.22 MW | 4.44 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 938372 | AE1-056 E | Adder | 2.85 MW | 2.42 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 939181 | AE1-148 C | Adder | 7.44 MW | 6.32 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 939182 | AE1-148 E | Adder | 4.96 MW | 4.21 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 941031 | AE2-094 C | 50/50 | 39.04 MW | 39.04 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 941032 | AE2-094 E | 50/50 | 17.48 MW | 17.48 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 941791 | AE2-182 C | Adder | 1.7 MW | 1.44 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 941792 | AE2-182 E | Adder | 0.79 MW | 0.67 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 946281 | AF1-292 C | Adder | 1.27 MW | 1.08 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 946282 | AF1-292 E | Adder | 0.84 MW | 0.72 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 946301 | AF1-294 C | Adder | 3.32 MW | 2.82 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 946302 | AF1-294 E | Adder | 2.21 MW | 1.88 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 957481 | AF2-042 C | Adder | 49.63 MW | 42.18 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 957482 | AF2-042 E | Adder | 33.09 MW | 28.12 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 958211 | AF2-115 C | Adder | 2.02 MW | 1.72 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 958212 | AF2-115 E | Adder | 1.35 MW | 1.15 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 933502 | AC2-165 E | Adder | 6.88 MW | 5.84 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 314331 | 6POE | Adder | 1.04 MW | 0.89 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 314550 | 6HICKORY | Adder | 1.63 MW | 1.38 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 926755 | AC1-161 E | Adder | 9.62 MW | 8.18 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 958502 | AF2-144 E | Adder | 1.15 MW | 0.98 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 315172 | 1LOISA A | 50/50 | 2.63 MW | 2.63 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 315173 | 1LOISA B | 50/50 | 2.64 MW | 2.64 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 315174 | 1LOISA C | 50/50 | 2.64 MW | 2.64 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 315175 | 1LOISA D | 50/50 | 2.64 MW | 2.64 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 315176 | 1LOISA E | 50/50 | 5.39 MW | 5.39 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 315177 | 1S ANNAG1 | 50/50 | 2.6 MW | 2.6 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 315178 | 1S ANNAS1 | 50/50 | 1.33 MW | 1.33 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 315179 | 1S ANNAG2 | 50/50 | 2.6 MW | 2.6 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 315180 | 1S ANNAS2 | 50/50 | 1.33 MW | 1.33 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 315225 | 1N ANNA1 | 50/50 | 90.72 MW | 90.72 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 315226 | 1N ANNA2 | 50/50 | 90.73 MW | 90.73 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 923852 | AB2-025 E | Adder | 0.98 MW | 0.83 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 923862 | AB2-026 E | Adder | 1.17 MW | 0.99 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 925022 | AB2-158 E | 50/50 | 11.41 MW | 11.41 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 938552 | AE1-074 E | Adder | 1.09 MW | 0.93 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 938562 | AE1-075 E | Adder | 1.0 MW | 0.85 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 946371 | AF1-301 C | 50/50 | 21.15 MW | 21.15 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 946372 | AF1-301 E | 50/50 | 14.2 MW | 14.2 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 966001 | AG1-469 C | 50/50 | 2.02 MW | 2.02 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 966002 | AG1-469 E | 50/50 | 1.01 MW | 1.01 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 957871 | AF2-081 C | Adder | 7.47 MW | 6.35 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 957872 | AF2-081 E | Adder | 3.2 MW | 2.72 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 314722 | 3TWITTYS | Adder | 0.78 MW | 0.66 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 926071 | AC1-086 C | Adder | 16.87 MW | 14.34 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 926072 | AC1-086 E | Adder | 7.68 MW | 6.53 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 936261 | AD2-033 C | Adder | 10.65 MW | 9.05 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 936262 | AD2-033 E | Adder | 7.1 MW | 6.04 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 933291 | AC2-141 C | Adder | 22.54 MW | 19.16 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 933292 | AC2-141 E | Adder | 9.62 MW | 8.18 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 934621 | AD1-088 C | Adder | 10.43 MW | 8.87 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 934622 | AD1-088 E | Adder | 4.91 MW | 4.17 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 939411 | AE1-173 C | Adder | 82.49 MW | 70.12 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 939412 | AE1-173 E | Adder | 54.99 MW | 46.74 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 962572 | AG1-106 E | Adder | 2.13 MW | 1.81 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 962571 | AG1-106 C | Adder | 4.69 MW | 3.99 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 208900 | BRIS G1 | 50/50 | -2.05 MW | -2.05 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 208901 | BRIS G2 | 50/50 | -2.43 MW | -2.43 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 316192 | AB2-158 C | 50/50 | 3.66 MW | 3.66 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 316233 | AE1-074 C | Adder | 2.16 MW | 1.84 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 316336 | AC2-165 C | Adder | 9.14 MW | 7.76 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 924516 | AB2-100 E1 | Adder | 2.38 MW | 2.02 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 924517 | AB2-100 E2 | Adder | 2.38 MW | 2.02 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 934065 | AD1-033 E | Adder | 3.74 MW | 3.18 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 937226 | AE2-253 E | Adder | 4.37 MW | 3.71 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 919153 | AA1-139 E2 | Adder | 3.06 MW | 2.6 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 919152 | AA1-139 E1 | Adder | 3.06 MW | 2.6 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 316181 | AB2-040 GEN | Adder | 6.1 MW | 5.19 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 923994 | AB2-040_E | Adder | 4.99 MW | 4.25 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 924022 | AB2-043 E O1 | Adder | 4.27 MW | 3.63 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 316088 | AB2-174 E | Adder | 5.31 MW | 4.51 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 940661 | AE2-053 C | Adder | 2.76 MW | 2.34 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 944581 | AF1-123 C | Adder | 36.12 MW | 30.7 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 944582 | AF1-123 E | Adder | 82.7 MW | 70.3 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 944591 | AF1-124 C | Adder | 36.12 MW | 30.7 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 944592 | AF1-124 E | Adder | 82.7 MW | 70.3 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 944601 | AF1-125 C | Adder | 36.12 MW | 30.7 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 944602 | AF1-125 E | Adder | 82.7 MW | 70.3 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 946011 | AF1-266 C | Adder | 11.39 MW | 9.68 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 957431 | AF2-037 C | 50/50 | 28.36 MW | 28.36 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 957432 | AF2-037 E | 50/50 | 18.91 MW | 18.91 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 957691 | AF2-063 C | 50/50 | 45.26 MW | 45.26 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 957692 | AF2-063 E | 50/50 | 30.17 MW | 30.17 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 962491 | AG1-098 C | Adder | 9.4 MW | 7.99 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 962492 | AG1-098 E | Adder | 6.26 MW | 5.32 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 962561 | AG1-105 C | Adder | 7.28 MW | 6.19 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 962562 | AG1-105 E | Adder | 4.85 MW | 4.12 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 963291 | AG1-178 C | Adder | 60.68 MW | 51.58 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 963311 | AG1-180 C | Adder | 2.29 MW | 1.95 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 963321 | AG1-181 C | Adder | 13.8 MW | 11.73 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 963351 | AG1-184 C | Adder | 32.69 MW | 27.79 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 963361 | AG1-185 C | Adder | 6.68 MW | 5.67 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 964241 | AG1-285 C | Adder | 10.29 MW | 8.75 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 964242 | AG1-285 E | Adder | 6.86 MW | 5.83 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 964421 | AG1-305 C | 50/50 | 35.6 MW | 35.6 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 964422 | AG1-305 E | 50/50 | 23.73 MW | 23.73 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 964951 | AG1-359 C | Adder | 17.05 MW | 14.49 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 965601 | AG1-428 C | Adder | 3.94 MW | 3.35 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 965602 | AG1-428 E | Adder | 2.62 MW | 2.23 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 965771 | AG1-445 C | Adder | 3.57 MW | 3.04 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 965781 | AG1-446 C | Adder | 3.57 MW | 3.04 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 965811 | AG1-449 C | Adder | 22.77 MW | 19.35 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 313764 | 3SOCKMAN | Adder | 0.58 MW | 0.49 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 934612 | AD1-087 E | Adder | 3.27 MW | 2.78 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 935172 | AD1-152 E | Adder | 4.8 MW | 4.08 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 937482 | AD2-202 E | Adder | 0.96 MW | 0.81 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 940481 | AE2-033 C | Adder | 13.6 MW | 11.56 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 940482 | AE2-033 E | Adder | 9.17 MW | 7.79 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 940541 | AE2-040 C | Adder | 2.42 MW | 2.06 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 940641 | AE2-051 C | Adder | 16.6 MW | 14.11 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 940642 | AE2-051 E | Adder | 11.07 MW | 9.41 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 945811 | AF1-246 C | Adder | 6.95 MW | 5.91 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 945812 | AF1-246 E | Adder | 9.6 MW | 8.16 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | 316303 | AF2-085 | 50/50 | 4.04 MW | 4.04 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 22.11 MW | 22.11 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 17.63 MW | 17.63 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 78.39 MW | 78.39 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 4.92 MW | 4.92 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | NY | PJM->LTFIMP_NY | CLTF | 2.3 MW | 2.3 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.94 MW | 0.94 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | WEC | LTFEXP_WEC->PJM | CLTF | 0.47 MW | 0.47 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | CPLE | LTFEXP_CPLE->PJM | CLTF | 9.37 MW | 9.37 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | TVA | LTFEXP_TVA->PJM | CLTF | 4.89 MW | 4.89 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | MEC | LTFEXP_MEC->PJM | CLTF | 2.98 MW | 2.98 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | LAGN | LTFEXP_LAGN->PJM | CLTF | 6.17 MW | 6.17 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.18 MW | 0.18 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 31.34 MW | 31.34 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 4.46 MW | 4.46 MW |
| Details for 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 961791 | AG1-021 C | Adder | 1.61 MW | 1.37 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 961792 | AG1-021 E | Adder | 1.08 MW | 0.92 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 961891 | AG1-030 C | Adder | 12.15 MW | 10.33 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 961892 | AG1-030 E | Adder | 8.1 MW | 6.89 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 963041 | AG1-153 C | Adder | 5.4 MW | 4.59 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 963042 | AG1-153 E | Adder | 8.1 MW | 6.88 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 963111 | AG1-160 C | Adder | 5.47 MW | 4.65 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 963112 | AG1-160 E | Adder | 8.21 MW | 6.98 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 963171 | AG1-166 C | Adder | 1.61 MW | 1.37 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 963172 | AG1-166 E | Adder | 1.08 MW | 0.92 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 963181 | AG1-167 C | Adder | 1.61 MW | 1.37 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 963182 | AG1-167 E | Adder | 1.08 MW | 0.92 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 963191 | AG1-168 C | Adder | 1.61 MW | 1.37 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 963192 | AG1-168 E | Adder | 1.08 MW | 0.92 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 963201 | AG1-169 C | Adder | 1.61 MW | 1.37 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 963202 | AG1-169 E | Adder | 1.08 MW | 0.92 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 963211 | AG1-170 C | Adder | 1.61 MW | 1.37 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 963212 | AG1-170 E | Adder | 1.08 MW | 0.92 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 963301 | AG1-179 C | Adder | 4.71 MW | 4.0 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 964111 | AG1-272 C | Adder | 2.1 MW | 1.78 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 964112 | AG1-272 E | Adder | 0.62 MW | 0.53 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 964121 | AG1-273 C | Adder | 2.1 MW | 1.78 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 964122 | AG1-273 E | Adder | 0.62 MW | 0.53 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 964131 | AG1-274 C | Adder | 2.1 MW | 1.78 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 964132 | AG1-274 E | Adder | 0.62 MW | 0.53 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 964791 | AG1-342 C | Adder | 3.37 MW | 2.87 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 964792 | AG1-342 E | Adder | 2.65 MW | 2.25 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 966811 | AG1-552 C | Adder | 1.65 MW | 1.4 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 966812 | AG1-552 E | Adder | 0.78 MW | 0.67 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 965191 | AG1-384 C | Adder | 2.1 MW | 1.78 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 965192 | AG1-384 E | Adder | 0.62 MW | 0.53 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 965291 | AG1-394 C | Adder | 1.6 MW | 1.36 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 965292 | AG1-394 E | Adder | 1.06 MW | 0.9 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 965591 | AG1-427 C | Adder | 9.74 MW | 8.28 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 965592 | AG1-427 E | Adder | 6.5 MW | 5.52 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 965721 | AG1-440 C | Adder | 6.16 MW | 5.24 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 965722 | AG1-440 E | Adder | 4.11 MW | 3.49 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 965731 | AG1-441 C | Adder | 6.16 MW | 5.24 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 965732 | AG1-441 E | Adder | 4.11 MW | 3.49 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 966361 | AG1-505 C | Adder | 16.08 MW | 13.66 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 966362 | AG1-505 E | Adder | 10.72 MW | 9.11 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 966371 | AG1-506 C | Adder | 16.08 MW | 13.66 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 966372 | AG1-506 E | Adder | 10.72 MW | 9.11 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 966621 | AG1-532 C | Adder | 1.14 MW | 0.97 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 966622 | AG1-532 E | Adder | 0.76 MW | 0.65 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 313853 | 3PONTONDP | Adder | 0.54 MW | 0.46 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 314572 | 3EMPORIA | Adder | 0.35 MW | 0.3 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 314713 | 3PAMPLIN | Adder | 0.8 MW | 0.68 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 918492 | AA1-063AE OP | Adder | 3.23 MW | 2.75 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 919692 | AA2-053 E OP | Adder | 3.37 MW | 2.86 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 920042 | AA2-088 E OP | Adder | 7.03 MW | 5.97 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 925785 | AC1-054 E | Adder | 2.79 MW | 2.38 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 942931 | AE2-313 C | Adder | 35.08 MW | 29.82 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 942932 | AE2-313 E | Adder | 23.39 MW | 19.88 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 944011 | AF1-069 C | 50/50 | 12.73 MW | 12.73 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 944012 | AF1-069 E | 50/50 | 4.94 MW | 4.94 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 958801 | AF2-171 C | Adder | 12.11 MW | 10.29 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 958802 | AF2-171 E | Adder | 8.08 MW | 6.86 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 959311 | AF2-222 C | Adder | 13.57 MW | 11.53 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 959312 | AF2-222 E | Adder | 9.09 MW | 7.73 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 960081 | AF2-299 C | Adder | 2.12 MW | 1.8 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 960082 | AF2-299 E | Adder | 1.41 MW | 1.2 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 923263 | AB1-132 E OP | Adder | 4.9 MW | 4.16 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 923573 | AB1-173 E OP | Adder | 2.66 MW | 2.26 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 924162 | AB2-060 E OP | Adder | 3.51 MW | 2.99 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 924302 | AB2-077 E O1 | Adder | 1.1 MW | 0.93 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 924312 | AB2-078 E O1 | Adder | 1.1 MW | 0.93 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 924322 | AB2-079 E O1 | Adder | 1.1 MW | 0.93 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 925612 | AC1-036 E | Adder | 0.7 MW | 0.59 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 938371 | AE1-056 C | Adder | 5.2 MW | 4.42 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 938372 | AE1-056 E | Adder | 2.84 MW | 2.42 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 939181 | AE1-148 C | Adder | 7.42 MW | 6.3 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 939182 | AE1-148 E | Adder | 4.94 MW | 4.2 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 941031 | AE2-094 C | 50/50 | 38.95 MW | 38.95 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 941032 | AE2-094 E | 50/50 | 17.45 MW | 17.45 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 941791 | AE2-182 C | Adder | 1.69 MW | 1.44 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 941792 | AE2-182 E | Adder | 0.79 MW | 0.67 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 946281 | AF1-292 C | Adder | 1.26 MW | 1.07 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 946282 | AF1-292 E | Adder | 0.84 MW | 0.72 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 946301 | AF1-294 C | Adder | 3.31 MW | 2.81 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 946302 | AF1-294 E | Adder | 2.21 MW | 1.88 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 957481 | AF2-042 C | Adder | 49.51 MW | 42.08 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 957482 | AF2-042 E | Adder | 33.01 MW | 28.05 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 958211 | AF2-115 C | Adder | 2.02 MW | 1.72 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 958212 | AF2-115 E | Adder | 1.35 MW | 1.14 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 933502 | AC2-165 E | Adder | 6.85 MW | 5.83 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 314331 | 6POE | Adder | 1.04 MW | 0.88 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 314550 | 6HICKORY | Adder | 1.62 MW | 1.38 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 926755 | AC1-161 E | Adder | 9.59 MW | 8.15 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 958502 | AF2-144 E | Adder | 1.14 MW | 0.97 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 315172 | 1LOISA A | 50/50 | 2.6 MW | 2.6 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 315173 | 1LOISA B | 50/50 | 2.62 MW | 2.62 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 315174 | 1LOISA C | 50/50 | 2.62 MW | 2.62 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 315175 | 1LOISA D | 50/50 | 2.62 MW | 2.62 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 315176 | 1LOISA E | 50/50 | 5.34 MW | 5.34 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 315177 | 1S ANNAG1 | 50/50 | 2.57 MW | 2.57 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 315178 | 1S ANNAS1 | 50/50 | 1.32 MW | 1.32 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 315179 | 1S ANNAG2 | 50/50 | 2.57 MW | 2.57 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 315180 | 1S ANNAS2 | 50/50 | 1.32 MW | 1.32 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 315225 | 1N ANNA1 | 50/50 | 90.64 MW | 90.64 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 315226 | 1N ANNA2 | 50/50 | 90.65 MW | 90.65 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 923852 | AB2-025 E | Adder | 0.98 MW | 0.83 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 923862 | AB2-026 E | Adder | 1.17 MW | 0.99 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 925022 | AB2-158 E | 50/50 | 11.36 MW | 11.36 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 938552 | AE1-074 E | Adder | 1.09 MW | 0.92 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 938562 | AE1-075 E | Adder | 0.99 MW | 0.84 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 946371 | AF1-301 C | 50/50 | 21.01 MW | 21.01 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 946372 | AF1-301 E | 50/50 | 14.11 MW | 14.11 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 966001 | AG1-469 C | 50/50 | 1.98 MW | 1.98 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 966002 | AG1-469 E | 50/50 | 0.99 MW | 0.99 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 957871 | AF2-081 C | Adder | 7.45 MW | 6.33 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 957872 | AF2-081 E | Adder | 3.19 MW | 2.71 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 314722 | 3TWITTYS | Adder | 0.78 MW | 0.66 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 926071 | AC1-086 C | Adder | 16.82 MW | 14.3 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 926072 | AC1-086 E | Adder | 7.66 MW | 6.51 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 936261 | AD2-033 C | Adder | 10.62 MW | 9.03 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 936262 | AD2-033 E | Adder | 7.08 MW | 6.02 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 933291 | AC2-141 C | Adder | 22.46 MW | 19.09 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 933292 | AC2-141 E | Adder | 9.59 MW | 8.15 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 934621 | AD1-088 C | Adder | 10.4 MW | 8.84 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 934622 | AD1-088 E | Adder | 4.9 MW | 4.16 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 939411 | AE1-173 C | Adder | 82.29 MW | 69.94 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 939412 | AE1-173 E | Adder | 54.86 MW | 46.63 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 962572 | AG1-106 E | Adder | 2.12 MW | 1.8 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 962571 | AG1-106 C | Adder | 4.68 MW | 3.98 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 208900 | BRIS G1 | 50/50 | -2.05 MW | -2.05 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 208901 | BRIS G2 | 50/50 | -2.42 MW | -2.42 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 316192 | AB2-158 C | 50/50 | 3.64 MW | 3.64 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 316233 | AE1-074 C | Adder | 2.16 MW | 1.83 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 316336 | AC2-165 C | Adder | 9.11 MW | 7.74 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 924516 | AB2-100 E1 | Adder | 2.37 MW | 2.01 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 924517 | AB2-100 E2 | Adder | 2.37 MW | 2.01 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 934065 | AD1-033 E | Adder | 3.73 MW | 3.17 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 937226 | AE2-253 E | Adder | 4.35 MW | 3.7 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 919153 | AA1-139 E2 | Adder | 3.05 MW | 2.59 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 919152 | AA1-139 E1 | Adder | 3.05 MW | 2.59 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 316181 | AB2-040 GEN | Adder | 6.09 MW | 5.17 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 923994 | AB2-040_E | Adder | 4.98 MW | 4.23 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 924022 | AB2-043 E O1 | Adder | 4.26 MW | 3.62 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 316088 | AB2-174 E | Adder | 5.29 MW | 4.5 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 940661 | AE2-053 C | Adder | 2.75 MW | 2.33 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 944581 | AF1-123 C | Adder | 36.0 MW | 30.6 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 944582 | AF1-123 E | Adder | 82.44 MW | 70.08 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 944591 | AF1-124 C | Adder | 36.0 MW | 30.6 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 944592 | AF1-124 E | Adder | 82.44 MW | 70.08 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 944601 | AF1-125 C | Adder | 36.0 MW | 30.6 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 944602 | AF1-125 E | Adder | 82.44 MW | 70.08 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 946011 | AF1-266 C | Adder | 11.36 MW | 9.65 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 957431 | AF2-037 C | 50/50 | 28.29 MW | 28.29 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 957432 | AF2-037 E | 50/50 | 18.86 MW | 18.86 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 957691 | AF2-063 C | 50/50 | 45.14 MW | 45.14 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 957692 | AF2-063 E | 50/50 | 30.09 MW | 30.09 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 962491 | AG1-098 C | Adder | 9.37 MW | 7.96 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 962492 | AG1-098 E | Adder | 6.24 MW | 5.31 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 962561 | AG1-105 C | Adder | 7.26 MW | 6.17 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 962562 | AG1-105 E | Adder | 4.84 MW | 4.11 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 963291 | AG1-178 C | Adder | 60.54 MW | 51.46 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 963311 | AG1-180 C | Adder | 2.28 MW | 1.94 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 963321 | AG1-181 C | Adder | 13.76 MW | 11.69 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 963351 | AG1-184 C | Adder | 32.62 MW | 27.73 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 963361 | AG1-185 C | Adder | 6.66 MW | 5.66 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 964241 | AG1-285 C | Adder | 10.26 MW | 8.72 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 964242 | AG1-285 E | Adder | 6.84 MW | 5.82 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 964421 | AG1-305 C | 50/50 | 35.51 MW | 35.51 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 964422 | AG1-305 E | 50/50 | 23.67 MW | 23.67 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 964951 | AG1-359 C | Adder | 17.0 MW | 14.45 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 965601 | AG1-428 C | Adder | 3.93 MW | 3.34 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 965602 | AG1-428 E | Adder | 2.62 MW | 2.23 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 965771 | AG1-445 C | Adder | 3.56 MW | 3.03 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 965781 | AG1-446 C | Adder | 3.56 MW | 3.03 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 965811 | AG1-449 C | Adder | 22.72 MW | 19.31 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 313764 | 3SOCKMAN | Adder | 0.57 MW | 0.49 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 934612 | AD1-087 E | Adder | 3.26 MW | 2.77 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 935172 | AD1-152 E | Adder | 4.79 MW | 4.07 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 937482 | AD2-202 E | Adder | 0.95 MW | 0.81 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 940481 | AE2-033 C | Adder | 13.57 MW | 11.53 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 940482 | AE2-033 E | Adder | 9.15 MW | 7.78 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 940541 | AE2-040 C | Adder | 2.42 MW | 2.05 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 940641 | AE2-051 C | Adder | 16.56 MW | 14.08 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 940642 | AE2-051 E | Adder | 11.04 MW | 9.39 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 945811 | AF1-246 C | Adder | 6.93 MW | 5.89 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 945812 | AF1-246 E | Adder | 9.57 MW | 8.14 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | 316303 | AF2-085 | 50/50 | 4.03 MW | 4.03 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 22.04 MW | 22.04 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 17.57 MW | 17.57 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 78.17 MW | 78.17 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 4.91 MW | 4.91 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | NY | PJM->LTFIMP_NY | CLTF | 2.29 MW | 2.29 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.94 MW | 0.94 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | WEC | LTFEXP_WEC->PJM | CLTF | 0.47 MW | 0.47 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | CPLE | LTFEXP_CPLE->PJM | CLTF | 9.34 MW | 9.34 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | TVA | LTFEXP_TVA->PJM | CLTF | 4.88 MW | 4.88 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | MEC | LTFEXP_MEC->PJM | CLTF | 2.97 MW | 2.97 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | LAGN | LTFEXP_LAGN->PJM | CLTF | 6.15 MW | 6.15 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.18 MW | 0.18 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 31.24 MW | 31.24 MW |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 4.45 MW | 4.45 MW |
| Details for 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 314229 | 6MT RD221 | 50/50 | 0.1 MW | 0.1 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 314236 | 6NRTHEST | 50/50 | 0.15 MW | 0.15 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 314250 | 6ROCKVILLE | Adder | 1.93 MW | 1.64 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 314314 | 3LOCKS | Adder | 1.68 MW | 1.43 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 314331 | 6POE | Adder | 1.24 MW | 1.05 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 314507 | 3THOMPSN | Adder | 1.85 MW | 1.57 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 315060 | 1CHESTF5 | Adder | 60.39 MW | 51.33 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 315065 | 1CHESTF6 | Adder | 18.5 MW | 15.72 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 315067 | 1DARBY 1 | 50/50 | 2.07 MW | 2.07 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 315068 | 1DARBY 2 | 50/50 | 2.07 MW | 2.07 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 315069 | 1DARBY 3 | 50/50 | 2.08 MW | 2.08 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 315070 | 1DARBY 4 | 50/50 | 2.08 MW | 2.08 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 315073 | 1STONECA | Adder | 6.52 MW | 5.54 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 315083 | 1SPRUNCA | Adder | 8.58 MW | 7.29 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 315084 | 1SPRUNCB | Adder | 8.58 MW | 7.29 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 315092 | 1YORKTN3 | Adder | 131.6 MW | 111.86 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 926412 | AC1-112 E | 50/50 | 1.09 MW | 1.09 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 926662 | AC1-147 E | Adder | 1.22 MW | 1.03 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 926755 | AC1-161 E | Adder | 11.92 MW | 10.13 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 927226 | AC1-216 E | Adder | 7.24 MW | 6.15 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 942152 | AE2-227 E | Adder | 1.39 MW | 1.18 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 942162 | AE2-228 E | Adder | 1.35 MW | 1.15 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 960091 | AF2-300 C | Adder | 2.07 MW | 1.76 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 960092 | AF2-300 E | Adder | 1.38 MW | 1.18 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 966871 | AG1-558 C | Adder | 2.26 MW | 1.92 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 966872 | AG1-558 E | Adder | 1.14 MW | 0.97 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 966881 | AG1-559 C | Adder | 2.3 MW | 1.95 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 966882 | AG1-559 E | Adder | 1.16 MW | 0.98 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 315225 | 1N ANNA1 | 50/50 | 24.23 MW | 24.23 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 315226 | 1N ANNA2 | 50/50 | 24.24 MW | 24.24 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 315260 | 1GOSPORTA | Adder | 1.95 MW | 1.66 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 315261 | 1GOSPORTB | Adder | 2.49 MW | 2.12 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 315262 | 1GOSPORTC | Adder | 2.12 MW | 1.8 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 316076 | AC2-137 E | Adder | 1.28 MW | 1.09 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 316108 | AB2-160 C | Adder | 5.1 MW | 4.33 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 316109 | AB2-160 E | Adder | 8.32 MW | 7.07 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 916192 | Z1-068 E | Adder | 1.72 MW | 1.46 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 930122 | AB1-027 E | 50/50 | 1.34 MW | 1.34 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 938552 | AE1-074 E | Adder | 1.14 MW | 0.97 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 939312 | AE1-162 E | Adder | 1.32 MW | 1.13 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 946262 | AF1-291 E | Adder | 1.35 MW | 1.15 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 957411 | AF2-035 C | Adder | 8.29 MW | 7.05 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 957412 | AF2-035 E | Adder | 4.15 MW | 3.52 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 962962 | AG1-145 E | Adder | 1.36 MW | 1.16 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 963051 | AG1-154 C | Adder | 3.36 MW | 2.86 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 963052 | AG1-154 E | Adder | 5.04 MW | 4.28 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 925332 | AB2-190 E | Adder | 7.59 MW | 6.45 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 925522 | AC1-027 E | Adder | 1.11 MW | 0.95 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 942001 | AE2-212 C | Adder | 2.01 MW | 1.71 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 942002 | AE2-212 E | Adder | 1.34 MW | 1.14 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 313811 | 6ELKO L286 | Adder | 1.33 MW | 1.13 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 933291 | AC2-141 C | Adder | 27.91 MW | 23.73 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 933292 | AC2-141 E | Adder | 11.92 MW | 10.13 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 934011 | AD1-025 C | Adder | 15.82 MW | 13.45 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 934012 | AD1-025 E | Adder | 9.37 MW | 7.96 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 927041 | AC1-191 C | Adder | 9.06 MW | 7.7 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 927042 | AC1-191 E | Adder | 4.51 MW | 3.83 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 316004 | AC1-112 C | 50/50 | 0.27 MW | 0.27 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 316160 | AE1-175 E | Adder | 1.12 MW | 0.95 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 316233 | AE1-074 C | Adder | 2.26 MW | 1.92 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 316240 | AF1-291 C | Adder | 2.03 MW | 1.72 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 316301 | AE2-228 C | Adder | 2.03 MW | 1.72 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 316304 | AE2-227 C | Adder | 2.08 MW | 1.77 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 316312 | AB1-027 C | 50/50 | 0.43 MW | 0.43 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 926785 | AC1-164_E | Adder | 17.32 MW | 14.72 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 963221 | AG1-171 C | Adder | 2.02 MW | 1.71 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 963222 | AG1-171 E | Adder | 1.34 MW | 1.14 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 963231 | AG1-172 C | Adder | 2.02 MW | 1.71 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 963232 | AG1-172 E | Adder | 1.34 MW | 1.14 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 963241 | AG1-173 C | Adder | 2.02 MW | 1.71 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 963242 | AG1-173 E | Adder | 1.34 MW | 1.14 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 963251 | AG1-174 C | Adder | 2.02 MW | 1.71 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 963252 | AG1-174 E | Adder | 1.34 MW | 1.14 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 315051 | AA1-145 CT1 | 50/50 | 4.06 MW | 4.06 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 315052 | AA1-145 CT2 | 50/50 | 4.06 MW | 4.06 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 316427 | AG1-213 C | Adder | 0.69 MW | 0.59 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 315043 | 1FOUR RIVERA | 50/50 | 2.55 MW | 2.55 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 315044 | 1FOUR RIVERB | 50/50 | 2.55 MW | 2.55 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 315045 | 1FOUR RIVERC | 50/50 | 3.12 MW | 3.12 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 315046 | 1FOUR RIVERD | 50/50 | 2.51 MW | 2.51 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 315047 | 1FOUR RIVERE | 50/50 | 2.51 MW | 2.51 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 315048 | 1FOUR RIVERF | 50/50 | 3.07 MW | 3.07 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 924814 | AB2-134 E | Adder | 11.86 MW | 10.08 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 316084 | AB2-161 E | Adder | 5.08 MW | 4.32 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 932046 | AC2-012 E | Adder | 12.02 MW | 10.21 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 934576 | AD1-082 E | Adder | 4.05 MW | 3.44 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 961611 | AG1-000B C | Adder | 14.85 MW | 12.62 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 941291 | AE2-123 C | Adder | 26.74 MW | 22.73 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 941292 | AE2-123 E | Adder | 104.29 MW | 88.65 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 941302 | AE2-124 E | Adder | 100.15 MW | 85.13 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 941591 | AE2-156 C | Adder | 16.42 MW | 13.96 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 942371 | AE2-250 C | Adder | 9.06 MW | 7.7 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 942372 | AE2-250 E | Adder | 4.78 MW | 4.06 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 942551 | AE2-270 C | Adder | 25.19 MW | 21.41 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 944581 | AF1-123 C | Adder | 43.9 MW | 37.31 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 944582 | AF1-123 E | Adder | 100.51 MW | 85.43 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 944591 | AF1-124 C | Adder | 43.9 MW | 37.31 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 944592 | AF1-124 E | Adder | 100.51 MW | 85.43 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 944601 | AF1-125 C | Adder | 43.9 MW | 37.31 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 944602 | AF1-125 E | Adder | 100.51 MW | 85.43 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 944631 | AF1-128 C | Adder | 37.78 MW | 32.12 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 945361 | AF1-201 C | Adder | 14.84 MW | 12.61 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 945362 | AF1-201 E | Adder | 9.89 MW | 8.41 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 957711 | AF2-065 C | Adder | 12.84 MW | 10.92 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 957712 | AF2-065 E | Adder | 12.34 MW | 10.49 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 961711 | AG1-011 C | Adder | 26.87 MW | 22.84 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 962271 | AG1-075 C | Adder | 15.63 MW | 13.29 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 962272 | AG1-075 E | Adder | 9.53 MW | 8.1 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 962841 | AG1-133 C | 50/50 | 16.56 MW | 16.56 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 962842 | AG1-133 E | 50/50 | 11.04 MW | 11.04 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 965001 | AG1-364 C | Adder | 6.57 MW | 5.58 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 965002 | AG1-364 E | Adder | 9.85 MW | 8.37 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 965281 | AG1-393 C | Adder | 2.01 MW | 1.71 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 965282 | AG1-393 E | Adder | 1.34 MW | 1.14 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 966611 | AG1-531 C | Adder | 5.41 MW | 4.59 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 966612 | AG1-531 E | Adder | 3.6 MW | 3.06 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 935161 | AD1-151 C | Adder | 15.15 MW | 12.88 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 935162 | AD1-151 E | Adder | 10.1 MW | 8.58 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 939191 | AE1-149 C | Adder | 9.91 MW | 8.42 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 939192 | AE1-149 E | Adder | 6.61 MW | 5.62 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 939261 | AE1-157 C | Adder | 13.3 MW | 11.31 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 939262 | AE1-157 E | Adder | 7.22 MW | 6.13 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 940431 | AE2-027 C | Adder | 12.11 MW | 10.29 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 940432 | AE2-027 E | Adder | 8.07 MW | 6.86 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 940651 | AE2-052 C | Adder | 3.3 MW | 2.81 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 941281 | AE2-122 C | Adder | 26.02 MW | 22.12 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 941282 | AE2-122 E | Adder | 105.01 MW | 89.26 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 942191 | AE2-231 C | Adder | 4.56 MW | 3.88 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 942192 | AE2-231 E | Adder | 3.04 MW | 2.58 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 944641 | AF1-129 C | Adder | 96.48 MW | 82.01 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | 963622 | AG1-213 E | Adder | 0.81 MW | 0.69 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 51.24 MW | 51.24 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 28.42 MW | 28.42 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 86.99 MW | 86.99 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 7.07 MW | 7.07 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | NY | PJM->LTFIMP_NY | CLTF | 3.12 MW | 3.12 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | LGEE | LTFEXP_LGEE->PJM | CLTF | 2.02 MW | 2.02 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | WEC | LTFEXP_WEC->PJM | CLTF | 1.05 MW | 1.05 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | CPLE | LTFEXP_CPLE->PJM | CLTF | 9.67 MW | 9.67 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | TVA | LTFEXP_TVA->PJM | CLTF | 7.14 MW | 7.14 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | MEC | LTFEXP_MEC->PJM | CLTF | 5.71 MW | 5.71 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | LAGN | LTFEXP_LAGN->PJM | CLTF | 8.9 MW | 8.9 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.37 MW | 0.37 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 44.87 MW | 44.87 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 4.62 MW | 4.62 MW |
| Details for 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 961671 | AG1-007 C | Adder | 0.35 MW | 0.29 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 961672 | AG1-007 E | Adder | 0.2 MW | 0.17 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 961941 | AG1-037 C | Adder | 0.27 MW | 0.23 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 961942 | AG1-037 E | Adder | 0.18 MW | 0.15 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 962331 | AG1-082 C | Adder | 1.08 MW | 0.92 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 962332 | AG1-082 E | Adder | 0.72 MW | 0.61 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 962341 | AG1-083 C | Adder | 1.08 MW | 0.92 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 962342 | AG1-083 E | Adder | 0.72 MW | 0.61 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 964801 | AG1-343 C | Adder | 3.36 MW | 2.85 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 964802 | AG1-343 E | Adder | 2.64 MW | 2.24 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 966801 | AG1-551 C | Adder | 1.0 MW | 0.85 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 966802 | AG1-551 E | Adder | 0.53 MW | 0.45 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 966811 | AG1-552 C | Adder | 0.72 MW | 0.62 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 966812 | AG1-552 E | Adder | 0.34 MW | 0.29 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 965291 | AG1-394 C | Adder | 1.16 MW | 0.98 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 965292 | AG1-394 E | Adder | 0.77 MW | 0.65 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 314541 | 3WATKINS | 50/50 | 0.46 MW | 0.46 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 918492 | AA1-063AE OP | Adder | 1.78 MW | 1.51 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 918532 | AA1-067 E | Adder | 0.32 MW | 0.27 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 919692 | AA2-053 E OP | Adder | 1.62 MW | 1.38 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 920042 | AA2-088 E OP | Adder | 6.13 MW | 5.21 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 927146 | AC1-208 E | Adder | 1.48 MW | 1.26 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 934521 | AD1-076 C | 50/50 | 7.23 MW | 7.23 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 934522 | AD1-076 E | 50/50 | 3.68 MW | 3.68 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 943172 | AE2-346 E | Adder | 0.32 MW | 0.28 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 316141 | AB2-099 E | Adder | 0.14 MW | 0.12 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 900672 | V4-068 E | Adder | 0.2 MW | 0.17 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 940491 | AE2-034 C | 50/50 | 0.59 MW | 0.59 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 940492 | AE2-034 E | 50/50 | 1.89 MW | 1.89 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 957521 | AF2-046 C | Adder | 9.31 MW | 7.91 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 957522 | AF2-046 E | Adder | 4.68 MW | 3.98 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 957531 | AF2-047 C | 50/50 | 10.47 MW | 10.47 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 957532 | AF2-047 E | 50/50 | 5.27 MW | 5.27 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 957861 | AF2-080 C | Adder | 3.1 MW | 2.63 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 957862 | AF2-080 E | Adder | 1.37 MW | 1.17 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 314539 | 3UNCAMP | 50/50 | 4.33 MW | 4.33 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 916042 | Z1-036 E | 50/50 | 18.6 MW | 18.6 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 938771 | AE1-103 C | 50/50 | 2.17 MW | 2.17 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 938772 | AE1-103 E | 50/50 | 2.99 MW | 2.99 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 314550 | 6HICKORY | Adder | 0.87 MW | 0.74 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 936591 | AD2-074 C | Adder | -2.74 MW | -2.33 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 942341 | AE2-247 C | 50/50 | 0.98 MW | 0.98 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 942342 | AE2-247 E | 50/50 | 1.35 MW | 1.35 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 943461 | AF1-017 C | 50/50 | 0.88 MW | 0.88 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 943462 | AF1-017 E | 50/50 | 1.44 MW | 1.44 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 943612 | AF1-032 E | 50/50 | 0.9 MW | 0.9 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 943741 | AF1-042 C | Adder | -1.43 MW | -1.22 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 944871 | AF1-152 C | 50/50 | 3.72 MW | 3.72 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 944872 | AF1-152 E | 50/50 | 2.48 MW | 2.48 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 315115 | 1S HAMPT1 | 50/50 | 0.84 MW | 0.84 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 315605 | 6W1-029WIND | 50/50 | 0.46 MW | 0.46 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 315611 | 6Z1-036WIND | 50/50 | 4.41 MW | 4.41 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 913392 | Y1-086 E | Adder | 1.21 MW | 1.03 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 916192 | Z1-068 E | Adder | 0.63 MW | 0.54 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 923832 | AB2-022 E | Adder | 0.68 MW | 0.58 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 957492 | AF2-043 E | 50/50 | 1.39 MW | 1.39 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 901082 | W1-029 E | 50/50 | 22.42 MW | 22.42 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 917122 | Z2-027 E | 50/50 | 0.79 MW | 0.79 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 925522 | AC1-027 E | Adder | 0.4 MW | 0.34 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 941501 | AE2-147 C | 50/50 | 11.15 MW | 11.15 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 941502 | AE2-147 E | 50/50 | 7.43 MW | 7.43 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 957871 | AF2-081 C | Adder | 4.46 MW | 3.79 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 957872 | AF2-081 E | Adder | 1.91 MW | 1.62 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 958161 | AF2-110 C | 50/50 | 1.19 MW | 1.19 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 958162 | AF2-110 E | 50/50 | 1.89 MW | 1.89 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 917512 | Z2-088 E OP1 | Adder | 1.88 MW | 1.6 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 927021 | AC1-189 C | Adder | 3.41 MW | 2.9 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 927022 | AC1-189 E | Adder | 1.7 MW | 1.44 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 934011 | AD1-025 C | Adder | -11.46 MW | -9.74 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 933981 | AD1-022 C | Adder | 5.12 MW | 4.36 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 933982 | AD1-022 E | Adder | 2.79 MW | 2.37 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 961681 | AG1-008 C | Adder | 9.33 MW | 7.93 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 961682 | AG1-008 E | Adder | 4.66 MW | 3.96 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 314594 | 6PLYMOUTH TP | 50/50 | 0.19 MW | 0.19 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 314632 | 6AYDLETT TAP | Adder | 0.64 MW | 0.55 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 316210 | AC1-098 C | Adder | 2.45 MW | 2.08 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 316212 | AC1-099 C | Adder | 0.82 MW | 0.7 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 316246 | AF1-032 C | 50/50 | 0.23 MW | 0.23 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 316274 | AC1-208 C | Adder | 3.34 MW | 2.83 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 316305 | AF2-043 C | 50/50 | 0.29 MW | 0.29 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 316321 | Z2-027 C | 50/50 | 0.18 MW | 0.18 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 917332 | KELFORD E | Adder | 0.8 MW | 0.68 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 926206 | AC1-098 E | Adder | 1.46 MW | 1.24 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 926214 | AC1-099 E | Adder | 0.48 MW | 0.41 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 934065 | AD1-033 E | Adder | 1.89 MW | 1.61 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 937226 | AE2-253 E | Adder | 2.5 MW | 2.12 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 918512 | AA1-065 E OP | Adder | 3.15 MW | 2.67 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 919153 | AA1-139 E2 | Adder | 1.82 MW | 1.55 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 919152 | AA1-139 E1 | Adder | 1.82 MW | 1.55 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 919710 | AA2-057 E | Adder | 1.4 MW | 1.19 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 315614 | AA2-178 C | 50/50 | 0.81 MW | 0.81 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 920692 | AA2-178 E | 50/50 | 2.52 MW | 2.52 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 316084 | AB2-161 E | Adder | 1.8 MW | 1.53 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 925122 | AB2-169 E | Adder | 3.01 MW | 2.56 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 316311 | AC2-079 C | 50/50 | 3.91 MW | 3.91 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 932596 | AC2-079 E | 50/50 | 6.38 MW | 6.38 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 934576 | AD1-082 E | Adder | 1.43 MW | 1.22 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 316349 | AD2-085 C | 50/50 | 2.25 MW | 2.25 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 936666 | AD2-085 E | 50/50 | 3.67 MW | 3.67 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 941291 | AE2-123 C | Adder | 10.05 MW | 8.54 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 941292 | AE2-123 E | Adder | 39.18 MW | 33.3 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 941301 | AE2-124 C | Adder | 9.4 MW | 7.99 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 941302 | AE2-124 E | Adder | 41.23 MW | 35.04 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 944581 | AF1-123 C | Adder | 17.1 MW | 14.54 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 944582 | AF1-123 E | Adder | 39.16 MW | 33.29 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 944591 | AF1-124 C | Adder | 17.1 MW | 14.54 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 944592 | AF1-124 E | Adder | 39.16 MW | 33.29 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 944601 | AF1-125 C | Adder | 17.1 MW | 14.54 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 944602 | AF1-125 E | Adder | 39.16 MW | 33.29 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 964951 | AG1-359 C | Adder | 8.72 MW | 7.41 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 965691 | AG1-437 C | Adder | 5.88 MW | 5.0 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 965692 | AG1-437 E | Adder | 3.92 MW | 3.33 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 965701 | AG1-438 C | Adder | 5.88 MW | 5.0 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 965702 | AG1-438 E | Adder | 3.92 MW | 3.33 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 965711 | AG1-439 C | Adder | 9.06 MW | 7.7 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 965712 | AG1-439 E | Adder | 6.04 MW | 5.13 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 965741 | AG1-442 C | Adder | 3.43 MW | 2.92 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 965751 | AG1-443 C | Adder | 3.43 MW | 2.92 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 965761 | AG1-444 C | Adder | 4.83 MW | 4.11 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 932631 | AC2-084 C | Adder | 2.62 MW | 2.23 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 932632 | AC2-084 E | Adder | 1.29 MW | 1.1 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 934501 | AD1-074 C | 50/50 | 19.9 MW | 19.9 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 934502 | AD1-074 E | 50/50 | 10.13 MW | 10.13 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 934511 | AD1-075 C | 50/50 | 4.97 MW | 4.97 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 934512 | AD1-075 E | 50/50 | 2.53 MW | 2.53 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 938531 | AE1-072 C | Adder | 8.19 MW | 6.96 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 938532 | AE1-072 E | Adder | 4.27 MW | 3.63 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 939601 | AE1-190 C | Adder | -1.11 MW | -0.95 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 941101 | AE2-104 C | 50/50 | 2.91 MW | 2.91 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 941102 | AE2-104 E | 50/50 | 4.63 MW | 4.63 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 941281 | AE2-122 C | Adder | 9.78 MW | 8.31 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 941282 | AE2-122 E | Adder | 39.45 MW | 33.53 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 9.58 MW | 9.58 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 5.61 MW | 5.61 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 20.88 MW | 20.88 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 0.35 MW | 0.35 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | NY | PJM->LTFIMP_NY | CLTF | 0.15 MW | 0.15 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.36 MW | 0.36 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | WEC | LTFEXP_WEC->PJM | CLTF | 0.19 MW | 0.19 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | CPLE | LTFEXP_CPLE->PJM | CLTF | 2.58 MW | 2.58 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | TVA | LTFEXP_TVA->PJM | CLTF | 1.44 MW | 1.44 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | MEC | LTFEXP_MEC->PJM | CLTF | 1.08 MW | 1.08 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | LAGN | LTFEXP_LAGN->PJM | CLTF | 1.82 MW | 1.82 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.07 MW | 0.07 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 2.23 MW | 2.23 MW |
| 6SUFFOLK-6KINGFORK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.23 MW | 1.23 MW |
| Details for 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 961671 | AG1-007 C | Adder | 0.55 MW | 0.47 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 961672 | AG1-007 E | Adder | 0.31 MW | 0.26 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 961941 | AG1-037 C | 50/50 | 0.51 MW | 0.51 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 961942 | AG1-037 E | 50/50 | 0.34 MW | 0.34 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 962331 | AG1-082 C | 50/50 | 2.04 MW | 2.04 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 962332 | AG1-082 E | 50/50 | 1.36 MW | 1.36 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 962341 | AG1-083 C | 50/50 | 2.04 MW | 2.04 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 962342 | AG1-083 E | 50/50 | 1.36 MW | 1.36 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 964801 | AG1-343 C | 50/50 | 6.47 MW | 6.47 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 964802 | AG1-343 E | 50/50 | 5.08 MW | 5.08 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 966801 | AG1-551 C | 50/50 | 1.78 MW | 1.78 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 966802 | AG1-551 E | 50/50 | 0.94 MW | 0.94 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 966811 | AG1-552 C | Adder | 1.18 MW | 1.0 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 966812 | AG1-552 E | Adder | 0.56 MW | 0.48 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 965291 | AG1-394 C | 50/50 | 2.23 MW | 2.23 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 965292 | AG1-394 E | 50/50 | 1.49 MW | 1.49 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 314541 | 3WATKINS | 50/50 | 0.94 MW | 0.94 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 918492 | AA1-063AE OP | 50/50 | 3.17 MW | 3.17 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 918532 | AA1-067 E | Adder | 0.55 MW | 0.47 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 919692 | AA2-053 E OP | Adder | 2.74 MW | 2.33 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 920042 | AA2-088 E OP | 50/50 | 11.93 MW | 11.93 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 927146 | AC1-208 E | Adder | 2.4 MW | 2.04 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 934521 | AD1-076 C | 50/50 | 14.07 MW | 14.07 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 934522 | AD1-076 E | 50/50 | 7.17 MW | 7.17 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 943171 | AE2-346 C | 50/50 | 0.19 MW | 0.19 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 943172 | AE2-346 E | 50/50 | 0.61 MW | 0.61 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 316140 | AB2-099 C | 50/50 | 0.08 MW | 0.08 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 316141 | AB2-099 E | 50/50 | 0.26 MW | 0.26 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 900672 | V4-068 E | 50/50 | 0.38 MW | 0.38 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 917342 | Z2-044 E | Adder | 0.3 MW | 0.26 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 923263 | AB1-132 E OP | Adder | 3.14 MW | 2.67 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 923573 | AB1-173 E OP | Adder | 1.47 MW | 1.25 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 940491 | AE2-034 C | 50/50 | 1.17 MW | 1.17 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 940492 | AE2-034 E | 50/50 | 3.73 MW | 3.73 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 957521 | AF2-046 C | 50/50 | 17.77 MW | 17.77 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 957522 | AF2-046 E | 50/50 | 8.94 MW | 8.94 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 957531 | AF2-047 C | 50/50 | 20.67 MW | 20.67 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 957532 | AF2-047 E | 50/50 | 10.4 MW | 10.4 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 957861 | AF2-080 C | Adder | 5.14 MW | 4.37 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 957862 | AF2-080 E | Adder | 2.28 MW | 1.94 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 314539 | 3UNCAMP | 50/50 | 8.86 MW | 8.86 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 916042 | Z1-036 E | 50/50 | 37.52 MW | 37.52 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 938771 | AE1-103 C | 50/50 | 4.46 MW | 4.46 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 938772 | AE1-103 E | 50/50 | 6.16 MW | 6.16 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 313526 | AB2-022 C | 50/50 | 0.35 MW | 0.35 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 314295 | 6BIRDNECK | 50/50 | 0.03 MW | 0.03 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 314507 | 3THOMPSN | Adder | 1.4 MW | 1.19 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 314525 | 6KINGFORK | 50/50 | 1.71 MW | 1.71 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 314550 | 6HICKORY | 50/50 | 1.7 MW | 1.7 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 926662 | AC1-147 E | Adder | 0.89 MW | 0.76 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 935112 | AD1-144 E | 50/50 | 1.58 MW | 1.58 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 942341 | AE2-247 C | 50/50 | 2.18 MW | 2.18 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 942342 | AE2-247 E | 50/50 | 3.01 MW | 3.01 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 943461 | AF1-017 C | 50/50 | 1.97 MW | 1.97 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 943462 | AF1-017 E | 50/50 | 3.22 MW | 3.22 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 943612 | AF1-032 E | 50/50 | 1.9 MW | 1.9 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 944871 | AF1-152 C | 50/50 | 7.6 MW | 7.6 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 944872 | AF1-152 E | 50/50 | 5.07 MW | 5.07 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 315115 | 1S HAMPT1 | 50/50 | 1.69 MW | 1.69 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 315260 | 1GOSPORTA | Adder | 1.46 MW | 1.24 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 315261 | 1GOSPORTB | Adder | 1.86 MW | 1.58 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 315262 | 1GOSPORTC | Adder | 1.58 MW | 1.34 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 315292 | 1DOMTR78 | 50/50 | 1.23 MW | 1.23 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 315605 | 6W1-029WIND | 50/50 | 0.94 MW | 0.94 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 315607 | 3AA1-063SOLA | 50/50 | 0.92 MW | 0.92 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 315608 | 3AA2-088SOLA | 50/50 | 1.01 MW | 1.01 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 315611 | 6Z1-036WIND | 50/50 | 8.89 MW | 8.89 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 913392 | Y1-086 E | 50/50 | 2.44 MW | 2.44 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 916192 | Z1-068 E | 50/50 | 1.41 MW | 1.41 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 923832 | AB2-022 E | 50/50 | 1.37 MW | 1.37 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 939312 | AE1-162 E | Adder | 0.88 MW | 0.74 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 957492 | AF2-043 E | 50/50 | 2.93 MW | 2.93 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 901082 | W1-029 E | 50/50 | 45.87 MW | 45.87 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 917122 | Z2-027 E | 50/50 | 1.6 MW | 1.6 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 925522 | AC1-027 E | 50/50 | 0.91 MW | 0.91 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 941501 | AE2-147 C | 50/50 | 22.81 MW | 22.81 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 941502 | AE2-147 E | 50/50 | 15.21 MW | 15.21 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 957871 | AF2-081 C | 50/50 | 8.83 MW | 8.83 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 957872 | AF2-081 E | 50/50 | 3.79 MW | 3.79 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 958161 | AF2-110 C | 50/50 | 2.52 MW | 2.52 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 958162 | AF2-110 E | 50/50 | 4.01 MW | 4.01 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 917512 | Z2-088 E OP1 | Adder | 3.05 MW | 2.59 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 926071 | AC1-086 C | Adder | 10.8 MW | 9.18 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 926072 | AC1-086 E | Adder | 4.91 MW | 4.18 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 927021 | AC1-189 C | Adder | 5.66 MW | 4.81 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 927022 | AC1-189 E | Adder | 2.82 MW | 2.4 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 933981 | AD1-022 C | 50/50 | 9.93 MW | 9.93 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 933982 | AD1-022 E | 50/50 | 5.4 MW | 5.4 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 962572 | AG1-106 E | Adder | 1.36 MW | 1.16 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 961681 | AG1-008 C | 50/50 | 17.81 MW | 17.81 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 961682 | AG1-008 E | 50/50 | 8.9 MW | 8.9 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 962571 | AG1-106 C | Adder | 3.0 MW | 2.55 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 314594 | 6PLYMOUTH TP | 50/50 | 0.37 MW | 0.37 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 314632 | 6AYDLETT TAP | 50/50 | 1.28 MW | 1.28 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 316072 | AD1-144 C | 50/50 | 0.4 MW | 0.4 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 316185 | AD1-033 C | 50/50 | 0.78 MW | 0.78 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 316210 | AC1-098 C | Adder | 4.12 MW | 3.5 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 316212 | AC1-099 C | Adder | 1.38 MW | 1.17 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 316246 | AF1-032 C | 50/50 | 0.49 MW | 0.49 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 316274 | AC1-208 C | Adder | 5.41 MW | 4.6 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 316305 | AF2-043 C | 50/50 | 0.6 MW | 0.6 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 316316 | AC1-027 C | 50/50 | 0.2 MW | 0.2 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 316317 | KELFORD C | 50/50 | 0.27 MW | 0.27 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 316318 | V4-068 C | 50/50 | 0.07 MW | 0.07 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 316320 | Y1-086 C | 50/50 | 0.21 MW | 0.21 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 316321 | Z2-027 C | 50/50 | 0.37 MW | 0.37 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 917332 | KELFORD E | 50/50 | 1.45 MW | 1.45 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 926206 | AC1-098 E | Adder | 2.45 MW | 2.09 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 926214 | AC1-099 E | Adder | 0.81 MW | 0.69 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 934065 | AD1-033 E | 50/50 | 3.75 MW | 3.75 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 937226 | AE2-253 E | 50/50 | 4.93 MW | 4.93 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 315602 | 1HOLLOMANSOL | 50/50 | 1.69 MW | 1.69 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 918512 | AA1-065 E OP | 50/50 | 6.01 MW | 6.01 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 316017 | AA1-139 ULT1 | 50/50 | 0.81 MW | 0.81 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 316018 | AA1-139 ULT2 | 50/50 | 0.81 MW | 0.81 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 919153 | AA1-139 E2 | 50/50 | 3.61 MW | 3.61 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 919152 | AA1-139 E1 | 50/50 | 3.61 MW | 3.61 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 919710 | AA2-057 E | Adder | 2.18 MW | 1.85 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 315614 | AA2-178 C | 50/50 | 1.6 MW | 1.6 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 920692 | AA2-178 E | 50/50 | 4.97 MW | 4.97 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 316181 | AB2-040 GEN | Adder | 3.36 MW | 2.86 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 923994 | AB2-040_E | Adder | 2.75 MW | 2.34 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 316083 | AB2-161 C | 50/50 | 0.41 MW | 0.41 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 316084 | AB2-161 E | 50/50 | 4.83 MW | 4.83 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 316174 | AB2-169_C | 50/50 | 0.86 MW | 0.86 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 925122 | AB2-169 E | 50/50 | 5.59 MW | 5.59 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 932046 | AC2-012 E | Adder | 8.79 MW | 7.47 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 316311 | AC2-079 C | 50/50 | 8.65 MW | 8.65 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 932596 | AC2-079 E | 50/50 | 14.12 MW | 14.12 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 316381 | AD1-082 C | 50/50 | 0.93 MW | 0.93 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 934576 | AD1-082 E | 50/50 | 3.85 MW | 3.85 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 316349 | AD2-085 C | 50/50 | 5.03 MW | 5.03 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 936666 | AD2-085 E | 50/50 | 8.2 MW | 8.2 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 316388 | AE2-253 GEN | 50/50 | 1.4 MW | 1.4 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 961611 | AG1-000B C | Adder | 8.83 MW | 7.51 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 941291 | AE2-123 C | 50/50 | 22.09 MW | 22.09 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 941292 | AE2-123 E | 50/50 | 86.13 MW | 86.13 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 941301 | AE2-124 C | 50/50 | 20.3 MW | 20.3 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 941302 | AE2-124 E | 50/50 | 89.08 MW | 89.08 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 941591 | AE2-156 C | Adder | 11.72 MW | 9.96 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 942551 | AE2-270 C | Adder | 1.26 MW | 1.07 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 944581 | AF1-123 C | Adder | 25.64 MW | 21.8 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 944582 | AF1-123 E | Adder | 58.72 MW | 49.91 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 944591 | AF1-124 C | Adder | 25.64 MW | 21.8 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 944592 | AF1-124 E | Adder | 58.72 MW | 49.91 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 944601 | AF1-125 C | Adder | 25.64 MW | 21.8 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 944602 | AF1-125 E | Adder | 58.72 MW | 49.91 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 964951 | AG1-359 C | 50/50 | 17.02 MW | 17.02 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 965001 | AG1-364 C | Adder | 4.71 MW | 4.0 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 965002 | AG1-364 E | Adder | 7.06 MW | 6.0 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 965691 | AG1-437 C | 50/50 | 11.35 MW | 11.35 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 965692 | AG1-437 E | 50/50 | 7.56 MW | 7.56 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 965701 | AG1-438 C | 50/50 | 11.35 MW | 11.35 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 965702 | AG1-438 E | 50/50 | 7.56 MW | 7.56 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 965711 | AG1-439 C | Adder | 14.64 MW | 12.45 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 965712 | AG1-439 E | Adder | 9.76 MW | 8.3 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 965741 | AG1-442 C | 50/50 | 6.62 MW | 6.62 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 965751 | AG1-443 C | 50/50 | 6.62 MW | 6.62 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 965761 | AG1-444 C | Adder | 7.81 MW | 6.64 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 313764 | 3SOCKMAN | Adder | 0.37 MW | 0.31 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 932631 | AC2-084 C | Adder | 4.4 MW | 3.74 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 932632 | AC2-084 E | Adder | 2.17 MW | 1.84 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 934321 | AD1-056 C | Adder | 3.03 MW | 2.57 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 934322 | AD1-056 E | Adder | 1.64 MW | 1.4 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 934331 | AD1-057 C | Adder | 1.69 MW | 1.44 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 934332 | AD1-057 E | Adder | 0.88 MW | 0.75 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 934501 | AD1-074 C | 50/50 | 38.73 MW | 38.73 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 934502 | AD1-074 E | 50/50 | 19.72 MW | 19.72 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 934511 | AD1-075 C | 50/50 | 9.68 MW | 9.68 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 934512 | AD1-075 E | 50/50 | 4.93 MW | 4.93 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 938531 | AE1-072 C | 50/50 | 16.27 MW | 16.27 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 938532 | AE1-072 E | 50/50 | 8.48 MW | 8.48 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 939191 | AE1-149 C | Adder | 5.03 MW | 4.28 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 939192 | AE1-149 E | Adder | 3.35 MW | 2.85 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 940651 | AE2-052 C | Adder | 1.68 MW | 1.43 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 941101 | AE2-104 C | 50/50 | 6.18 MW | 6.18 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 941102 | AE2-104 E | 50/50 | 9.82 MW | 9.82 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 941281 | AE2-122 C | 50/50 | 21.49 MW | 21.49 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | 941282 | AE2-122 E | 50/50 | 86.72 MW | 86.72 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 2.52 MW | 2.52 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 2.23 MW | 2.23 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 12.42 MW | 12.42 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 0.45 MW | 0.45 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | NY | PJM->LTFIMP_NY | CLTF | 0.21 MW | 0.21 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.1 MW | 0.1 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | WEC | LTFEXP_WEC->PJM | CLTF | 0.05 MW | 0.05 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | CPLE | LTFEXP_CPLE->PJM | CLTF | 1.86 MW | 1.86 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | TVA | LTFEXP_TVA->PJM | CLTF | 0.63 MW | 0.63 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | MEC | LTFEXP_MEC->PJM | CLTF | 0.36 MW | 0.36 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | LAGN | LTFEXP_LAGN->PJM | CLTF | 0.81 MW | 0.81 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.02 MW | 0.02 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 2.84 MW | 2.84 MW |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-2: H7T565_SRT-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.89 MW | 0.89 MW |
| Details for 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 961671 | AG1-007 C | Adder | 0.35 MW | 0.29 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 961672 | AG1-007 E | Adder | 0.2 MW | 0.17 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 961941 | AG1-037 C | Adder | 0.27 MW | 0.23 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 961942 | AG1-037 E | Adder | 0.18 MW | 0.15 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 962331 | AG1-082 C | Adder | 1.08 MW | 0.92 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 962332 | AG1-082 E | Adder | 0.72 MW | 0.61 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 962341 | AG1-083 C | Adder | 1.08 MW | 0.92 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 962342 | AG1-083 E | Adder | 0.72 MW | 0.61 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 964801 | AG1-343 C | Adder | 3.35 MW | 2.85 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 964802 | AG1-343 E | Adder | 2.63 MW | 2.24 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 966801 | AG1-551 C | Adder | 1.0 MW | 0.85 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 966802 | AG1-551 E | Adder | 0.52 MW | 0.45 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 966811 | AG1-552 C | Adder | 0.72 MW | 0.62 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 966812 | AG1-552 E | Adder | 0.34 MW | 0.29 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 965291 | AG1-394 C | Adder | 1.15 MW | 0.98 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 965292 | AG1-394 E | Adder | 0.77 MW | 0.65 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 314541 | 3WATKINS | 50/50 | 0.46 MW | 0.46 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 918492 | AA1-063AE OP | Adder | 1.78 MW | 1.51 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 918532 | AA1-067 E | Adder | 0.32 MW | 0.27 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 919692 | AA2-053 E OP | Adder | 1.62 MW | 1.38 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 920042 | AA2-088 E OP | Adder | 6.13 MW | 5.21 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 927146 | AC1-208 E | Adder | 1.48 MW | 1.26 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 934521 | AD1-076 C | 50/50 | 7.22 MW | 7.22 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 934522 | AD1-076 E | 50/50 | 3.68 MW | 3.68 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 943172 | AE2-346 E | Adder | 0.32 MW | 0.28 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 316141 | AB2-099 E | Adder | 0.14 MW | 0.12 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 900672 | V4-068 E | Adder | 0.2 MW | 0.17 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 917342 | Z2-044 E | Adder | 0.2 MW | 0.17 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 923263 | AB1-132 E OP | Adder | 1.96 MW | 1.67 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 940491 | AE2-034 C | 50/50 | 0.59 MW | 0.59 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 940492 | AE2-034 E | 50/50 | 1.89 MW | 1.89 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 957521 | AF2-046 C | Adder | 9.3 MW | 7.91 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 957522 | AF2-046 E | Adder | 4.68 MW | 3.98 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 957531 | AF2-047 C | 50/50 | 10.46 MW | 10.46 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 957532 | AF2-047 E | 50/50 | 5.26 MW | 5.26 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 957861 | AF2-080 C | Adder | 3.1 MW | 2.63 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 957862 | AF2-080 E | Adder | 1.37 MW | 1.17 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 314539 | 3UNCAMP | 50/50 | 4.33 MW | 4.33 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 916042 | Z1-036 E | 50/50 | 18.6 MW | 18.6 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 938771 | AE1-103 C | 50/50 | 2.17 MW | 2.17 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 938772 | AE1-103 E | 50/50 | 2.99 MW | 2.99 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 314525 | 6KINGFORK | 50/50 | 1.86 MW | 1.86 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 314550 | 6HICKORY | Adder | 0.87 MW | 0.74 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 935112 | AD1-144 E | 50/50 | 1.73 MW | 1.73 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 936591 | AD2-074 C | Adder | -2.74 MW | -2.33 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 942341 | AE2-247 C | 50/50 | 0.98 MW | 0.98 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 942342 | AE2-247 E | 50/50 | 1.35 MW | 1.35 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 943461 | AF1-017 C | 50/50 | 0.88 MW | 0.88 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 943462 | AF1-017 E | 50/50 | 1.44 MW | 1.44 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 943612 | AF1-032 E | 50/50 | 0.9 MW | 0.9 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 943741 | AF1-042 C | Adder | -1.43 MW | -1.22 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 944871 | AF1-152 C | 50/50 | 3.71 MW | 3.71 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 944872 | AF1-152 E | 50/50 | 2.48 MW | 2.48 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 315115 | 1S HAMPT1 | 50/50 | 0.84 MW | 0.84 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 315605 | 6W1-029WIND | 50/50 | 0.46 MW | 0.46 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 315611 | 6Z1-036WIND | 50/50 | 4.41 MW | 4.41 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 913392 | Y1-086 E | Adder | 1.21 MW | 1.03 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 916192 | Z1-068 E | Adder | 0.63 MW | 0.54 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 923832 | AB2-022 E | Adder | 0.68 MW | 0.58 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 957492 | AF2-043 E | 50/50 | 1.39 MW | 1.39 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 901082 | W1-029 E | 50/50 | 22.41 MW | 22.41 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 917122 | Z2-027 E | 50/50 | 0.79 MW | 0.79 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 925522 | AC1-027 E | Adder | 0.4 MW | 0.34 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 941501 | AE2-147 C | 50/50 | 11.14 MW | 11.14 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 941502 | AE2-147 E | 50/50 | 7.43 MW | 7.43 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 957871 | AF2-081 C | Adder | 4.46 MW | 3.79 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 957872 | AF2-081 E | Adder | 1.91 MW | 1.62 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 958161 | AF2-110 C | 50/50 | 1.19 MW | 1.19 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 958162 | AF2-110 E | 50/50 | 1.89 MW | 1.89 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 917512 | Z2-088 E OP1 | Adder | 1.88 MW | 1.6 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 926071 | AC1-086 C | Adder | 6.75 MW | 5.74 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 926072 | AC1-086 E | Adder | 3.07 MW | 2.61 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 927021 | AC1-189 C | Adder | 3.41 MW | 2.9 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 927022 | AC1-189 E | Adder | 1.7 MW | 1.44 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 934011 | AD1-025 C | Adder | -11.47 MW | -9.75 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 933981 | AD1-022 C | Adder | 5.12 MW | 4.35 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 933982 | AD1-022 E | Adder | 2.79 MW | 2.37 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 962572 | AG1-106 E | Adder | 0.85 MW | 0.72 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 961681 | AG1-008 C | Adder | 9.32 MW | 7.92 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 961682 | AG1-008 E | Adder | 4.66 MW | 3.96 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 962571 | AG1-106 C | Adder | 1.88 MW | 1.59 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 314594 | 6PLYMOUTH TP | 50/50 | 0.19 MW | 0.19 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 314632 | 6AYDLETT TAP | Adder | 0.64 MW | 0.55 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 316072 | AD1-144 C | 50/50 | 0.44 MW | 0.44 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 316210 | AC1-098 C | Adder | 2.45 MW | 2.08 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 316212 | AC1-099 C | Adder | 0.82 MW | 0.7 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 316246 | AF1-032 C | 50/50 | 0.23 MW | 0.23 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 316274 | AC1-208 C | Adder | 3.33 MW | 2.83 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 316305 | AF2-043 C | 50/50 | 0.29 MW | 0.29 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 316321 | Z2-027 C | 50/50 | 0.18 MW | 0.18 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 917332 | KELFORD E | Adder | 0.8 MW | 0.68 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 926206 | AC1-098 E | Adder | 1.46 MW | 1.24 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 926214 | AC1-099 E | Adder | 0.48 MW | 0.41 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 934065 | AD1-033 E | Adder | 1.89 MW | 1.61 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 937226 | AE2-253 E | Adder | 2.5 MW | 2.12 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 918512 | AA1-065 E OP | Adder | 3.14 MW | 2.67 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 919153 | AA1-139 E2 | Adder | 1.82 MW | 1.55 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 919152 | AA1-139 E1 | Adder | 1.82 MW | 1.55 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 919710 | AA2-057 E | Adder | 1.4 MW | 1.19 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 315614 | AA2-178 C | 50/50 | 0.81 MW | 0.81 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 920692 | AA2-178 E | 50/50 | 2.52 MW | 2.52 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 316084 | AB2-161 E | Adder | 1.8 MW | 1.53 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 925122 | AB2-169 E | Adder | 3.0 MW | 2.55 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 316311 | AC2-079 C | 50/50 | 3.91 MW | 3.91 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 932596 | AC2-079 E | 50/50 | 6.37 MW | 6.37 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 934576 | AD1-082 E | Adder | 1.43 MW | 1.22 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 316349 | AD2-085 C | 50/50 | 2.25 MW | 2.25 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 936666 | AD2-085 E | 50/50 | 3.67 MW | 3.67 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 941291 | AE2-123 C | Adder | 10.04 MW | 8.53 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 941292 | AE2-123 E | Adder | 39.14 MW | 33.27 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 941301 | AE2-124 C | Adder | 9.39 MW | 7.98 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 941302 | AE2-124 E | Adder | 41.19 MW | 35.01 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 944581 | AF1-123 C | Adder | 17.09 MW | 14.53 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 944582 | AF1-123 E | Adder | 39.13 MW | 33.26 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 944591 | AF1-124 C | Adder | 17.09 MW | 14.53 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 944592 | AF1-124 E | Adder | 39.13 MW | 33.26 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 944601 | AF1-125 C | Adder | 17.09 MW | 14.53 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 944602 | AF1-125 E | Adder | 39.13 MW | 33.26 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 964951 | AG1-359 C | Adder | 8.71 MW | 7.41 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 965691 | AG1-437 C | Adder | 5.88 MW | 5.0 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 965692 | AG1-437 E | Adder | 3.92 MW | 3.33 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 965701 | AG1-438 C | Adder | 5.88 MW | 5.0 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 965702 | AG1-438 E | Adder | 3.92 MW | 3.33 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 965711 | AG1-439 C | Adder | 9.05 MW | 7.7 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 965712 | AG1-439 E | Adder | 6.04 MW | 5.13 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 965741 | AG1-442 C | Adder | 3.43 MW | 2.91 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 965751 | AG1-443 C | Adder | 3.43 MW | 2.91 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 965761 | AG1-444 C | Adder | 4.83 MW | 4.11 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 313764 | 3SOCKMAN | Adder | 0.23 MW | 0.2 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 932631 | AC2-084 C | Adder | 2.62 MW | 2.23 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 932632 | AC2-084 E | Adder | 1.29 MW | 1.1 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 934501 | AD1-074 C | 50/50 | 19.89 MW | 19.89 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 934502 | AD1-074 E | 50/50 | 10.12 MW | 10.12 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 934511 | AD1-075 C | 50/50 | 4.97 MW | 4.97 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 934512 | AD1-075 E | 50/50 | 2.53 MW | 2.53 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 938531 | AE1-072 C | Adder | 8.18 MW | 6.96 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 938532 | AE1-072 E | Adder | 4.27 MW | 3.63 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 939601 | AE1-190 C | Adder | -1.12 MW | -0.95 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 941101 | AE2-104 C | 50/50 | 2.91 MW | 2.91 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 941102 | AE2-104 E | 50/50 | 4.63 MW | 4.63 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 941281 | AE2-122 C | Adder | 9.77 MW | 8.3 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | 941282 | AE2-122 E | Adder | 39.41 MW | 33.5 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 9.49 MW | 9.49 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 5.58 MW | 5.58 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 20.83 MW | 20.83 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 0.36 MW | 0.36 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | NY | PJM->LTFIMP_NY | CLTF | 0.15 MW | 0.15 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.36 MW | 0.36 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | WEC | LTFEXP_WEC->PJM | CLTF | 0.19 MW | 0.19 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | CPLE | LTFEXP_CPLE->PJM | CLTF | 2.58 MW | 2.58 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | TVA | LTFEXP_TVA->PJM | CLTF | 1.43 MW | 1.43 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | MEC | LTFEXP_MEC->PJM | CLTF | 1.07 MW | 1.07 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | LAGN | LTFEXP_LAGN->PJM | CLTF | 1.81 MW | 1.81 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.07 MW | 0.07 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 2.27 MW | 2.27 MW |
| 6KINGFORK-6CHCKTUK 230.0 kV Ckt 1 line l/o DVP_P4-2: 531T582_SRT-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.23 MW | 1.23 MW |
| Details for 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 314250 | 6ROCKVILLE | Adder | 1.66 MW | 1.41 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 314314 | 3LOCKS | Adder | 1.45 MW | 1.24 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 314331 | 6POE | Adder | 1.1 MW | 0.93 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 314507 | 3THOMPSN | Adder | 1.62 MW | 1.38 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 315021 | 1REMNGT1 | 50/50 | 5.32 MW | 5.32 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 315022 | 1REMNGT2 | 50/50 | 5.37 MW | 5.37 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 315023 | 1REMNGT3 | 50/50 | 6.04 MW | 6.04 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 315024 | 1REMNGT4 | 50/50 | 5.39 MW | 5.39 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 315028 | 1M RUN A | 50/50 | 5.95 MW | 5.95 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 315029 | 1M RUN B | 50/50 | 5.91 MW | 5.91 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 315030 | 1M RUN C | 50/50 | 5.95 MW | 5.95 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 315060 | 1CHESTF5 | Adder | 50.89 MW | 43.25 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 315065 | 1CHESTF6 | Adder | 15.94 MW | 13.54 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 315073 | 1STONECA | Adder | 5.58 MW | 4.74 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 315083 | 1SPRUNCA | Adder | 7.47 MW | 6.35 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 315084 | 1SPRUNCB | Adder | 7.47 MW | 6.35 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 926412 | AC1-112 E | Adder | 0.89 MW | 0.75 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 926662 | AC1-147 E | Adder | 1.07 MW | 0.91 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 926755 | AC1-161 E | Adder | 10.46 MW | 8.89 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 927226 | AC1-216 E | Adder | 6.24 MW | 5.3 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 934861 | AD1-115 C | 50/50 | 4.79 MW | 4.79 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 934862 | AD1-115 E | 50/50 | 7.82 MW | 7.82 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 942152 | AE2-227 E | Adder | 1.17 MW | 1.0 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 942162 | AE2-228 E | Adder | 1.17 MW | 0.99 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 966681 | AG1-538 C | Adder | 7.73 MW | 6.57 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 966682 | AG1-538 E | Adder | 10.39 MW | 8.83 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 315260 | 1GOSPORTA | Adder | 1.71 MW | 1.46 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 315261 | 1GOSPORTB | Adder | 2.19 MW | 1.86 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 315262 | 1GOSPORTC | Adder | 1.86 MW | 1.58 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 316076 | AC2-137 E | Adder | 1.06 MW | 0.9 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 316108 | AB2-160 C | Adder | 4.42 MW | 3.76 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 316109 | AB2-160 E | Adder | 7.21 MW | 6.13 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 916192 | Z1-068 E | Adder | 1.51 MW | 1.28 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 925022 | AB2-158 E | Adder | 5.93 MW | 5.04 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 930122 | AB1-027 E | Adder | 1.09 MW | 0.93 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 938552 | AE1-074 E | Adder | 1.03 MW | 0.87 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 939312 | AE1-162 E | Adder | 1.15 MW | 0.98 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 946262 | AF1-291 E | Adder | 1.17 MW | 0.99 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 946371 | AF1-301 C | Adder | 15.01 MW | 12.76 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 946372 | AF1-301 E | Adder | 10.08 MW | 8.56 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 963031 | AG1-152 C | 50/50 | 10.3 MW | 10.3 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 963032 | AG1-152 E | 50/50 | 15.45 MW | 15.45 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 964271 | AG1-288 C | 50/50 | 25.96 MW | 25.96 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 966001 | AG1-469 C | Adder | 2.03 MW | 1.73 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 966002 | AG1-469 E | Adder | 1.02 MW | 0.86 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 925332 | AB2-190 E | Adder | 6.52 MW | 5.54 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 925522 | AC1-027 E | Adder | 0.98 MW | 0.83 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 925672 | AC1-043 E | 50/50 | 15.64 MW | 15.64 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 942001 | AE2-212 C | Adder | 1.75 MW | 1.49 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 942002 | AE2-212 E | Adder | 1.17 MW | 0.99 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 958251 | AF2-119 C | Adder | 8.26 MW | 7.02 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 958252 | AF2-119 E | Adder | 5.51 MW | 4.68 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 966331 | AG1-502 C | 50/50 | 16.01 MW | 16.01 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 966332 | AG1-502 E | 50/50 | 4.0 MW | 4.0 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 966341 | AG1-503 C | 50/50 | 4.0 MW | 4.0 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 966342 | AG1-503 E | 50/50 | 1.0 MW | 1.0 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 313811 | 6ELKO L286 | Adder | 1.1 MW | 0.94 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 933291 | AC2-141 C | Adder | 24.5 MW | 20.83 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 933292 | AC2-141 E | Adder | 10.46 MW | 8.89 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 939411 | AE1-173 C | Adder | 70.24 MW | 59.7 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 939412 | AE1-173 E | Adder | 46.82 MW | 39.8 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 923892 | AB2-029 E | 50/50 | 3.14 MW | 3.14 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 934011 | AD1-025 C | Adder | 13.63 MW | 11.58 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 934012 | AD1-025 E | Adder | 8.07 MW | 6.86 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 316164 | AC1-076_C | 50/50 | 0.85 MW | 0.85 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 316170 | AC1-121 C | 50/50 | 3.41 MW | 3.41 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 316233 | AE1-074 C | Adder | 2.04 MW | 1.73 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 316240 | AF1-291 C | Adder | 1.75 MW | 1.49 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 316254 | AC1-120 C | 50/50 | 9.93 MW | 9.93 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 316257 | AC1-043 C | 50/50 | 9.59 MW | 9.59 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 316301 | AE2-228 C | Adder | 1.75 MW | 1.49 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 316304 | AE2-227 C | Adder | 1.76 MW | 1.5 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 926785 | AC1-164_E | Adder | 14.28 MW | 12.14 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 963221 | AG1-171 C | Adder | 1.74 MW | 1.48 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 963222 | AG1-171 E | Adder | 1.16 MW | 0.98 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 963231 | AG1-172 C | Adder | 1.74 MW | 1.48 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 963232 | AG1-172 E | Adder | 1.16 MW | 0.98 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 963241 | AG1-173 C | Adder | 1.74 MW | 1.48 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 963242 | AG1-173 E | Adder | 1.16 MW | 0.98 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 963251 | AG1-174 C | Adder | 1.74 MW | 1.48 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 963252 | AG1-174 E | Adder | 1.16 MW | 0.98 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 926004 | AC1-076_E | 50/50 | 5.76 MW | 5.76 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 926486 | AC1-120 E | 50/50 | 5.12 MW | 5.12 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 926502 | AC1-121 E | 50/50 | 1.6 MW | 1.6 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 926615 | AC1-143 E | 50/50 | 4.81 MW | 4.81 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 316006 | AB2-029 C | 50/50 | 0.27 MW | 0.27 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 316267 | AC1-143 C | 50/50 | 10.55 MW | 10.55 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 924814 | AB2-134 E | Adder | 10.21 MW | 8.68 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 316044 | AC1-158 C1 | 50/50 | 6.77 MW | 6.77 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 316045 | AC1-158 C2 | 50/50 | 6.77 MW | 6.77 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 926739 | AC1-158 E1 | 50/50 | 20.79 MW | 20.79 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 926740 | AC1-158 E2 | 50/50 | 20.79 MW | 20.79 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 932046 | AC2-012 E | Adder | 10.55 MW | 8.96 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 961611 | AG1-000B C | Adder | 12.84 MW | 10.91 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 941591 | AE2-156 C | Adder | 14.41 MW | 12.25 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 942371 | AE2-250 C | Adder | 7.85 MW | 6.67 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 942372 | AE2-250 E | Adder | 4.14 MW | 3.52 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 942551 | AE2-270 C | Adder | 21.7 MW | 18.44 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 944581 | AF1-123 C | Adder | 38.61 MW | 32.82 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 944582 | AF1-123 E | Adder | 88.41 MW | 75.15 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 944591 | AF1-124 C | Adder | 38.61 MW | 32.82 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 944592 | AF1-124 E | Adder | 88.41 MW | 75.15 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 944601 | AF1-125 C | Adder | 38.61 MW | 32.82 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 944602 | AF1-125 E | Adder | 88.41 MW | 75.15 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 944631 | AF1-128 C | Adder | 31.84 MW | 27.06 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 957431 | AF2-037 C | Adder | 12.44 MW | 10.57 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 957432 | AF2-037 E | Adder | 8.29 MW | 7.05 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 957691 | AF2-063 C | Adder | 19.85 MW | 16.88 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 957692 | AF2-063 E | Adder | 13.24 MW | 11.25 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 957711 | AF2-065 C | Adder | 11.07 MW | 9.41 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 957712 | AF2-065 E | Adder | 10.63 MW | 9.04 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 961711 | AG1-011 C | Adder | 23.15 MW | 19.67 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 962271 | AG1-075 C | Adder | 13.55 MW | 11.52 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 962272 | AG1-075 E | Adder | 8.26 MW | 7.02 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 962841 | AG1-133 C | Adder | 16.3 MW | 13.85 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 962842 | AG1-133 E | Adder | 10.87 MW | 9.24 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 963291 | AG1-178 C | Adder | 47.79 MW | 40.62 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 963351 | AG1-184 C | Adder | 25.74 MW | 21.88 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 964281 | AG1-289 C | 50/50 | 14.36 MW | 14.36 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 964421 | AG1-305 C | Adder | 15.62 MW | 13.28 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 964422 | AG1-305 E | Adder | 10.41 MW | 8.85 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 965001 | AG1-364 C | Adder | 5.76 MW | 4.9 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 965002 | AG1-364 E | Adder | 8.65 MW | 7.35 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 965281 | AG1-393 C | Adder | 1.74 MW | 1.48 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 965282 | AG1-393 E | Adder | 1.16 MW | 0.99 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 935161 | AD1-151 C | Adder | 13.03 MW | 11.08 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 935162 | AD1-151 E | Adder | 8.69 MW | 7.38 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 938291 | AE1-044 C | 50/50 | 32.3 MW | 32.3 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 938292 | AE1-044 E | 50/50 | 25.49 MW | 25.49 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 939191 | AE1-149 C | Adder | 8.68 MW | 7.37 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 939192 | AE1-149 E | Adder | 5.78 MW | 4.92 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 939221 | AE1-153 C | 50/50 | 21.6 MW | 21.6 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 939222 | AE1-153 E | 50/50 | 14.4 MW | 14.4 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 940431 | AE2-027 C | Adder | 10.46 MW | 8.89 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 940432 | AE2-027 E | Adder | 6.98 MW | 5.93 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 940641 | AE2-051 C | Adder | 13.25 MW | 11.26 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 940642 | AE2-051 E | Adder | 8.83 MW | 7.51 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 940651 | AE2-052 C | Adder | 2.89 MW | 2.46 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 941282 | AE2-122 E | Adder | 90.48 MW | 76.91 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | 944641 | AF1-129 C | Adder | 83.11 MW | 70.64 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 31.78 MW | 31.78 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 20.57 MW | 20.57 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 73.89 MW | 73.89 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 5.91 MW | 5.91 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | NY | PJM->LTFIMP_NY | CLTF | 2.7 MW | 2.7 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | LGEE | LTFEXP_LGEE->PJM | CLTF | 1.32 MW | 1.32 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | WEC | LTFEXP_WEC->PJM | CLTF | 0.66 MW | 0.66 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | CPLE | LTFEXP_CPLE->PJM | CLTF | 8.45 MW | 8.45 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | TVA | LTFEXP_TVA->PJM | CLTF | 5.42 MW | 5.42 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | MEC | LTFEXP_MEC->PJM | CLTF | 3.83 MW | 3.83 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | LAGN | LTFEXP_LAGN->PJM | CLTF | 6.76 MW | 6.76 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.25 MW | 0.25 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 37.56 MW | 37.56 MW |
| 8BRISTER-8OX 500.0 kV Ckt 1 line l/o DVP_P4-2: 541T569_SRT-S | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 4.03 MW | 4.03 MW |
| Details for 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 314250 | 6ROCKVILLE | Adder | 1.39 MW | 1.18 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 314314 | 3LOCKS | Adder | 1.21 MW | 1.03 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 314331 | 6POE | Adder | 0.89 MW | 0.76 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 314507 | 3THOMPSN | Adder | 1.32 MW | 1.12 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 315007 | 1POSSM 5 | Adder | 102.17 MW | 86.85 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 315008 | 1POSSM6A | 50/50 | 3.14 MW | 3.14 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 315009 | 1POSSM6B | 50/50 | 3.14 MW | 3.14 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 315010 | 1POSSM6S | 50/50 | 4.89 MW | 4.89 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 315033 | 1BIRCHWDA | Adder | 33.43 MW | 28.42 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 315039 | 1LDYSMT3 | 50/50 | 3.31 MW | 3.31 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 315040 | 1LDYSMT4 | 50/50 | 3.32 MW | 3.32 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 315041 | 1LDYSMT5 | 50/50 | 3.33 MW | 3.33 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 315060 | 1CHESTF5 | Adder | 43.42 MW | 36.91 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 315065 | 1CHESTF6 | Adder | 13.28 MW | 11.29 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 315073 | 1STONECA | Adder | 4.68 MW | 3.98 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 315083 | 1SPRUNCA | Adder | 6.19 MW | 5.26 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 315084 | 1SPRUNCB | Adder | 6.19 MW | 5.26 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 315092 | 1YORKTN3 | Adder | 95.17 MW | 80.9 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 925865 | AC1-065 E | Adder | 11.66 MW | 9.91 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 926412 | AC1-112 E | Adder | 0.78 MW | 0.66 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 926472 | AC1-118 E | Adder | 0.89 MW | 0.76 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 926662 | AC1-147 E | Adder | 0.87 MW | 0.74 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 926755 | AC1-161 E | Adder | 8.49 MW | 7.22 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 927226 | AC1-216 E | Adder | 5.19 MW | 4.41 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 934392 | AD1-063 E | Adder | 0.75 MW | 0.64 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 934781 | AD1-105 C | Adder | 5.87 MW | 4.99 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 934782 | AD1-105 E | Adder | 3.91 MW | 3.33 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 936582 | AD2-073 E | Adder | 0.86 MW | 0.73 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 936591 | AD2-074 C | Adder | 4.14 MW | 3.52 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 936592 | AD2-074 E | Adder | 6.76 MW | 5.74 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 942152 | AE2-227 E | Adder | 1.0 MW | 0.85 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 942162 | AE2-228 E | Adder | 0.97 MW | 0.82 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 943741 | AF1-042 C | Adder | 2.17 MW | 1.84 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 943742 | AF1-042 E | Adder | 3.54 MW | 3.0 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 944491 | AF1-114 C | Adder | 5.64 MW | 4.79 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 944492 | AF1-114 E | Adder | 7.78 MW | 6.62 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 960091 | AF2-300 C | 50/50 | 1.72 MW | 1.72 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 960092 | AF2-300 E | 50/50 | 1.14 MW | 1.14 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 961951 | AG1-038 C | Adder | 2.39 MW | 2.04 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 961952 | AG1-038 E | Adder | 3.31 MW | 2.81 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 966661 | AG1-536 C | Adder | 4.07 MW | 3.46 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 966662 | AG1-536 E | Adder | 5.47 MW | 4.65 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 966871 | AG1-558 C | Adder | 1.71 MW | 1.46 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 966872 | AG1-558 E | Adder | 0.86 MW | 0.73 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 966881 | AG1-559 C | 50/50 | 1.9 MW | 1.9 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 966882 | AG1-559 E | 50/50 | 0.96 MW | 0.96 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 315225 | 1N ANNA1 | 50/50 | 19.65 MW | 19.65 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 315226 | 1N ANNA2 | 50/50 | 19.65 MW | 19.65 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 315260 | 1GOSPORTA | Adder | 1.39 MW | 1.19 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 315261 | 1GOSPORTB | Adder | 1.78 MW | 1.51 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 315262 | 1GOSPORTC | Adder | 1.51 MW | 1.28 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 316076 | AC2-137 E | Adder | 0.92 MW | 0.78 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 316078 | AC2-138 E | Adder | 0.72 MW | 0.61 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 316108 | AB2-160 C | Adder | 3.67 MW | 3.12 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 316109 | AB2-160 E | Adder | 5.99 MW | 5.09 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 316157 | AD2-030 E | Adder | 0.84 MW | 0.71 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 923842 | AB2-024 E | Adder | 1.25 MW | 1.06 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 925022 | AB2-158 E | Adder | 3.33 MW | 2.83 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 930122 | AB1-027 E | Adder | 0.95 MW | 0.81 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 938552 | AE1-074 E | Adder | 0.83 MW | 0.7 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 939312 | AE1-162 E | Adder | 0.95 MW | 0.81 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 946262 | AF1-291 E | Adder | 0.97 MW | 0.82 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 957411 | AF2-035 C | 50/50 | 6.86 MW | 6.86 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 957412 | AF2-035 E | 50/50 | 3.43 MW | 3.43 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 957601 | AF2-054 C | Adder | 1.49 MW | 1.27 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 957602 | AF2-054 E | Adder | 0.99 MW | 0.84 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 962531 | AG1-102 C | Adder | 0.76 MW | 0.64 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 962532 | AG1-102 E | Adder | 1.58 MW | 1.34 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 962851 | AG1-134 C | Adder | 7.93 MW | 6.74 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 962852 | AG1-134 E | Adder | 5.29 MW | 4.49 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 962861 | AG1-135 C | Adder | 4.58 MW | 3.89 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 962862 | AG1-135 E | Adder | 3.05 MW | 2.59 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 962962 | AG1-145 E | Adder | 0.98 MW | 0.83 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 962971 | AG1-146 C | Adder | 2.28 MW | 1.93 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 962972 | AG1-146 E | Adder | 1.52 MW | 1.29 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 962981 | AG1-147 C | Adder | 5.31 MW | 4.51 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 962982 | AG1-147 E | Adder | 3.54 MW | 3.01 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 963051 | AG1-154 C | 50/50 | 3.01 MW | 3.01 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 963052 | AG1-154 E | 50/50 | 4.51 MW | 4.51 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 963611 | AG1-210 C | Adder | 0.51 MW | 0.44 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 963612 | AG1-210 E | Adder | 0.77 MW | 0.65 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 964211 | AG1-282 C | Adder | 1.54 MW | 1.3 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 964212 | AG1-282 E | Adder | 1.02 MW | 0.87 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 964271 | AG1-288 C | 50/50 | 13.91 MW | 13.91 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 965441 | AG1-412 C | 50/50 | 11.91 MW | 11.91 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 965442 | AG1-412 E | 50/50 | 17.87 MW | 17.87 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 925332 | AB2-190 E | Adder | 5.45 MW | 4.63 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 942001 | AE2-212 C | Adder | 1.44 MW | 1.23 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 942002 | AE2-212 E | Adder | 0.96 MW | 0.82 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 957831 | AF2-077 C | Adder | 1.47 MW | 1.25 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 957832 | AF2-077 E | Adder | 0.98 MW | 0.83 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 957971 | AF2-091 C | Adder | 1.92 MW | 1.63 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 957972 | AF2-091 E | Adder | 2.65 MW | 2.25 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 958251 | AF2-119 C | 50/50 | 7.88 MW | 7.88 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 958252 | AF2-119 E | 50/50 | 5.25 MW | 5.25 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 966331 | AG1-502 C | Adder | 7.66 MW | 6.51 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 966332 | AG1-502 E | Adder | 1.91 MW | 1.63 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 966341 | AG1-503 C | Adder | 1.91 MW | 1.63 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 966342 | AG1-503 E | Adder | 0.48 MW | 0.41 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 313811 | 6ELKO L286 | Adder | 0.96 MW | 0.81 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 314181 | 3NORNECK | Adder | 0.68 MW | 0.58 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 933291 | AC2-141 C | Adder | 19.9 MW | 16.91 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 933292 | AC2-141 E | Adder | 8.49 MW | 7.22 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 934011 | AD1-025 C | Adder | 11.35 MW | 9.65 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 934012 | AD1-025 E | Adder | 6.72 MW | 5.71 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 927041 | AC1-191 C | Adder | 6.88 MW | 5.85 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 927042 | AC1-191 E | Adder | 3.43 MW | 2.91 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 313053 | 6PAPERMILL | Adder | 4.64 MW | 3.94 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 316160 | AE1-175 E | Adder | 0.81 MW | 0.69 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 316233 | AE1-074 C | Adder | 1.64 MW | 1.4 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 316240 | AF1-291 C | Adder | 1.46 MW | 1.24 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 316301 | AE2-228 C | Adder | 1.46 MW | 1.24 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 316304 | AE2-227 C | Adder | 1.5 MW | 1.27 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 926785 | AC1-164_E | Adder | 12.44 MW | 10.58 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 939612 | AE1-191 E | Adder | 4.0 MW | 3.4 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 963221 | AG1-171 C | Adder | 1.45 MW | 1.23 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 963222 | AG1-171 E | Adder | 0.96 MW | 0.82 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 963231 | AG1-172 C | Adder | 1.45 MW | 1.23 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 963232 | AG1-172 E | Adder | 0.96 MW | 0.82 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 963241 | AG1-173 C | Adder | 1.45 MW | 1.23 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 963242 | AG1-173 E | Adder | 0.96 MW | 0.82 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 963251 | AG1-174 C | Adder | 1.45 MW | 1.23 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 963252 | AG1-174 E | Adder | 0.96 MW | 0.82 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 926004 | AC1-076_E | Adder | 2.93 MW | 2.49 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 315037 | 1LDYSMT1 | 50/50 | 3.19 MW | 3.19 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 315038 | 1LDYSMT2 | 50/50 | 3.23 MW | 3.23 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 316201 | AC1-065 C | Adder | 7.08 MW | 6.01 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 316427 | AG1-213 C | 50/50 | 0.57 MW | 0.57 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 316411 | AF1-147_GEN1 | Adder | -5.72 MW | -4.86 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 316415 | AF1-147_GEN2 | Adder | -5.72 MW | -4.86 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 939246 | AE1-155 E | Adder | 6.59 MW | 5.6 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 924814 | AB2-134 E | Adder | 8.51 MW | 7.23 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 316084 | AB2-161 E | Adder | 3.64 MW | 3.09 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 316044 | AC1-158 C1 | 50/50 | 3.61 MW | 3.61 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 316045 | AC1-158 C2 | 50/50 | 3.61 MW | 3.61 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 926739 | AC1-158 E1 | 50/50 | 11.08 MW | 11.08 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 926740 | AC1-158 E2 | 50/50 | 11.08 MW | 11.08 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 932046 | AC2-012 E | Adder | 8.58 MW | 7.29 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 934146 | AD1-041 E | Adder | 2.5 MW | 2.12 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 934576 | AD1-082 E | Adder | 2.9 MW | 2.47 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 961611 | AG1-000B C | Adder | 10.65 MW | 9.05 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 941591 | AE2-156 C | Adder | 11.72 MW | 9.96 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 942371 | AE2-250 C | Adder | 6.52 MW | 5.55 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 942372 | AE2-250 E | Adder | 3.44 MW | 2.93 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 942551 | AE2-270 C | Adder | 18.07 MW | 15.36 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 944582 | AF1-123 E | Adder | 47.52 MW | 40.39 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 944592 | AF1-124 E | Adder | 71.72 MW | 60.96 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 944631 | AF1-128 C | Adder | 27.17 MW | 23.09 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 945361 | AF1-201 C | Adder | 11.0 MW | 9.35 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 945362 | AF1-201 E | Adder | 7.33 MW | 6.23 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 957431 | AF2-037 C | Adder | 7.39 MW | 6.28 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 957432 | AF2-037 E | Adder | 4.93 MW | 4.19 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 957691 | AF2-063 C | Adder | 11.79 MW | 10.02 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 957692 | AF2-063 E | Adder | 7.86 MW | 6.68 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 957711 | AF2-065 C | Adder | 9.22 MW | 7.83 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 957712 | AF2-065 E | Adder | 8.86 MW | 7.53 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 958261 | AF2-120 C | Adder | 4.73 MW | 4.02 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 958262 | AF2-120 E | Adder | 3.16 MW | 2.68 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 961711 | AG1-011 C | Adder | 19.28 MW | 16.39 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 961781 | AG1-019 C | Adder | 13.76 MW | 11.7 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 962271 | AG1-075 C | Adder | 11.26 MW | 9.57 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 962272 | AG1-075 E | Adder | 6.86 MW | 5.83 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 962841 | AG1-133 C | 50/50 | 11.86 MW | 11.86 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 962842 | AG1-133 E | 50/50 | 7.91 MW | 7.91 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 964281 | AG1-289 C | 50/50 | 7.69 MW | 7.69 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 964421 | AG1-305 C | Adder | 9.27 MW | 7.88 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 964422 | AG1-305 E | Adder | 6.18 MW | 5.26 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 965001 | AG1-364 C | Adder | 4.69 MW | 3.98 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 965002 | AG1-364 E | Adder | 7.03 MW | 5.98 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 965281 | AG1-393 C | Adder | 1.45 MW | 1.23 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 965282 | AG1-393 E | Adder | 0.97 MW | 0.82 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 966611 | AG1-531 C | Adder | 3.89 MW | 3.31 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 966612 | AG1-531 E | Adder | 2.59 MW | 2.2 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 935161 | AD1-151 C | Adder | 10.87 MW | 9.24 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 935162 | AD1-151 E | Adder | 7.25 MW | 6.16 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 939191 | AE1-149 C | Adder | 7.11 MW | 6.04 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 939192 | AE1-149 E | Adder | 4.74 MW | 4.03 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 939261 | AE1-157 C | 50/50 | 11.34 MW | 11.34 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 939262 | AE1-157 E | 50/50 | 6.15 MW | 6.15 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 939601 | AE1-190 C | Adder | 1.5 MW | 1.27 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 939602 | AE1-190 E | Adder | 1.0 MW | 0.85 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 940431 | AE2-027 C | Adder | 8.73 MW | 7.42 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 940432 | AE2-027 E | Adder | 5.82 MW | 4.95 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 940551 | AE2-041 C | Adder | 5.01 MW | 4.26 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 940651 | AE2-052 C | Adder | 2.37 MW | 2.01 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 942191 | AE2-231 C | 50/50 | 3.77 MW | 3.77 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 942192 | AE2-231 E | 50/50 | 2.52 MW | 2.52 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 943471 | AF1-018 C | Adder | 5.01 MW | 4.26 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 944641 | AF1-129 C | Adder | 69.27 MW | 58.88 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 957191 | AF2-013 C | Adder | 13.76 MW | 11.7 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | 963622 | AG1-213 E | 50/50 | 0.57 MW | 0.57 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 8.73 MW | 8.73 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 10.4 MW | 10.4 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 52.02 MW | 52.02 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 3.99 MW | 3.99 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | NY | PJM->LTFIMP_NY | CLTF | 1.97 MW | 1.97 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.47 MW | 0.47 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | WEC | LTFEXP_WEC->PJM | CLTF | 0.21 MW | 0.21 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | CPLE | LTFEXP_CPLE->PJM | CLTF | 6.2 MW | 6.2 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | TVA | LTFEXP_TVA->PJM | CLTF | 3.1 MW | 3.1 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | MEC | LTFEXP_MEC->PJM | CLTF | 1.53 MW | 1.53 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | LAGN | LTFEXP_LAGN->PJM | CLTF | 3.86 MW | 3.86 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.1 MW | 0.1 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 25.52 MW | 25.52 MW |
| 8OX-8CLIFTON 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2101-569_SRT-S | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.96 MW | 2.96 MW |
Summer Potential Congestion due to Local Energy Deliverability
PJM also studied the delivery of the energy portion of this interconnection request. Any problems identified below are likely to result in operational restrictions to the project under study. The developer can proceed with network upgrades to eliminate the operational restriction at their discretion by submitting an Upgrade Request into the New Service Request process.
Note: Only the most severely overloaded conditions are listed below. There is no guarantee of full delivery of energy for this project by fixing only the conditions listed in this section. With an Upgrade Request, a subsequent analysis will be performed which shall study all overload conditions associated with the overloaded element(s) identified.
| Summer Potential Congestion due to Local Energy Deliverability | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Final Cycle Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | ||
| DVP |
6FENTRES-6THRASHER 230.0 kV Ckt 1 line
314466 to 314508 ckt 1 |
DVP_P1-2: LN 588_SRT-A
CONTINGENCY 'DVP_P1-2: LN 588_SRT-A' OPEN BRANCH FROM BUS 314909 TO BUS 314927 CKT 1 /*8FENTRES 500.0 - 8YADKIN 500.0 END |
OP | AC | 330.1 % | 678.68 | B | 2240.3 | 499.84 | ||
| DVP |
6THRASHER-6YADKIN 230.0 kV Ckt 1 line
314508 to 314514 ckt 1 |
DVP_P1-2: LN 588_SRT-A
CONTINGENCY 'DVP_P1-2: LN 588_SRT-A' OPEN BRANCH FROM BUS 314909 TO BUS 314927 CKT 1 /*8FENTRES 500.0 - 8YADKIN 500.0 END |
OP | AC | 207.73 % | 818.74 | B | 1700.78 | 312.77 | ||
| DVP |
6POCATY-6LANDSTN 230.0 kV Ckt 1 line
316171 to 314481 ckt 1 |
DVP_P1-2: LN 588_SRT-A
CONTINGENCY 'DVP_P1-2: LN 588_SRT-A' OPEN BRANCH FROM BUS 314909 TO BUS 314927 CKT 1 /*8FENTRES 500.0 - 8YADKIN 500.0 END |
OP | AC | 177.66 % | 678.68 | B | 1205.72 | 253.56 | ||
| DVP |
6FENTRES-6POCATY 230.0 kV Ckt 1 line
314466 to 316171 ckt 1 |
DVP_P1-2: LN 588_SRT-A
CONTINGENCY 'DVP_P1-2: LN 588_SRT-A' OPEN BRANCH FROM BUS 314909 TO BUS 314927 CKT 1 /*8FENTRES 500.0 - 8YADKIN 500.0 END |
OP | AC | 170.72 % | 678.68 | B | 1158.65 | 253.76 | ||
| DVP |
AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line
316099 to 313902 ckt 1 |
DVP_P1-2: LN 2197_SRT-A-2
CONTINGENCY 'DVP_P1-2: LN 2197_SRT-A-2' OPEN BRANCH FROM BUS 935160 TO BUS 314303 CKT 1 /*AD1-151 TP 230.0 - 6HOPEWLL 230.0 END |
OP | AC | 158.1 % | 678.68 | B | 1072.98 | 59.45 | ||
| DVP |
6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line
313902 to 314303 ckt 1 |
DVP_P1-2: LN 2197_SRT-A-2
CONTINGENCY 'DVP_P1-2: LN 2197_SRT-A-2' OPEN BRANCH FROM BUS 935160 TO BUS 314303 CKT 1 /*AD1-151 TP 230.0 - 6HOPEWLL 230.0 END |
OP | AC | 158.06 % | 678.68 | B | 1072.74 | 59.45 | ||
| DVP |
6CHESTF A-6IRON208 230.0 kV Ckt 1 line
314286 to 314309 ckt 1 |
DVP_P1-2: LN 557_SRT-S
CONTINGENCY 'DVP_P1-2: LN 557_SRT-S' OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1 /*8CHCKAHM 500.0 - 8ELMONT 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 END |
OP | AC | 151.01 % | 663.64 | B | 1002.17 | 50.59 | ||
| DVP |
6IRON208-6SOUWEST 230.0 kV Ckt 1 line
314309 to 314338 ckt 1 |
DVP_P1-2: LN 557_SRT-S
CONTINGENCY 'DVP_P1-2: LN 557_SRT-S' OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1 /*8CHCKAHM 500.0 - 8ELMONT 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 END |
OP | AC | 146.2 % | 663.64 | B | 970.23 | 50.52 | ||
| DVP |
6LIGH209-6LANEXA 230.0 kV Ckt 1 line
314391 to 314388 ckt 1 |
DVP_P1-2: LN 567_SRT-A
CONTINGENCY 'DVP_P1-2: LN 567_SRT-A' OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1 /*8CHCKAHM 500.0 - 8SURRY 500.0 END |
OP | AC | 146.07 % | 663.64 | B | 969.39 | 82.66 | ||
| DVP |
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
314914 to 314322 ckt 1 |
DVP_P1-2: LN 576_SRT-A
CONTINGENCY 'DVP_P1-2: LN 576_SRT-A' OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN 500.0 - 8NO ANNA 500.0 END |
OP | AC | 145.21 % | 1058.16 | B | 1536.52 | 66.52 | ||
| DVP |
AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line
942550 to 316099 ckt 2 |
DVP_P1-2: LN 2197_SRT-A-2
CONTINGENCY 'DVP_P1-2: LN 2197_SRT-A-2' OPEN BRANCH FROM BUS 935160 TO BUS 314303 CKT 1 /*AD1-151 TP 230.0 - 6HOPEWLL 230.0 END |
OP | AC | 141.39 % | 678.68 | B | 959.56 | 59.95 | ||
| DVP |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer
314218 to 314908 ckt 2 |
DVP_P1-2: LN 557_SRT-S
CONTINGENCY 'DVP_P1-2: LN 557_SRT-S' OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1 /*8CHCKAHM 500.0 - 8ELMONT 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 END |
OP | AC | 136.44 % | 879.84 | B | 1200.43 | 96.27 | ||
| DVP |
6NRTHEST-6ELMONT 230.0 kV Ckt 1 line
314236 to 314218 ckt 1 |
DVP_P1-2: LN 557_SRT-S
CONTINGENCY 'DVP_P1-2: LN 557_SRT-S' OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1 /*8CHCKAHM 500.0 - 8ELMONT 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 END |
OP | AC | 132.03 % | 678.68 | B | 896.07 | 65.2 | ||
| DVP |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line
314303 to 314286 ckt 1 |
DVP_P1-2: LN 567_SRT-A
CONTINGENCY 'DVP_P1-2: LN 567_SRT-A' OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1 /*8CHCKAHM 500.0 - 8SURRY 500.0 END |
OP | AC | 129.97 % | 984.18 | B | 1279.11 | 65.67 | ||
| DVP |
6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line
314209 to 314413 ckt 1 |
DVP_P1-2: LN 567_SRT-A
CONTINGENCY 'DVP_P1-2: LN 567_SRT-A' OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1 /*8CHCKAHM 500.0 - 8SURRY 500.0 END |
OP | AC | 128.41 % | 678.68 | B | 871.51 | 71.58 | ||
| DVP |
8FENTRES-6FENTRES 500.0/230.0 kV Ckt 1 transformer
314909 to 314466 ckt 1 |
DVP_P1-2: LN 588_SRT-A
CONTINGENCY 'DVP_P1-2: LN 588_SRT-A' OPEN BRANCH FROM BUS 314909 TO BUS 314927 CKT 1 /*8FENTRES 500.0 - 8YADKIN 500.0 END |
OP | AC | 124.4 % | 1115.59 | B | 1387.75 | 442.73 | ||
| DVP |
8SEPTA-8SURRY 500.0 kV Ckt 1 line
314923 to 314924 ckt 1 |
DVP_P1-2: LN 563_SRT-S-1
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S-1' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA 500.0 - AE2-051 TP 500.0 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TP 500.0 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TP 500.0 SET PRECONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA 500.0 - AE2-051 TP 500.0 END |
OP | AC | 124.28 % | 2442.12 | B | 3034.97 | 164.94 | ||
| DVP |
8FENTRES-6FENTRES 500.0/230.0 kV Ckt 2 transformer
314909 to 314466 ckt 2 |
DVP_P1-2: LN 588_SRT-A
CONTINGENCY 'DVP_P1-2: LN 588_SRT-A' OPEN BRANCH FROM BUS 314909 TO BUS 314927 CKT 1 /*8FENTRES 500.0 - 8YADKIN 500.0 END |
OP | AC | 124.23 % | 1103.28 | B | 1370.64 | 437.27 | ||
| DVP |
6ELIZ R-6YADKIN 230.0 kV Ckt 1 line
314465 to 314514 ckt 1 |
DVP_P1-2: LN 588_SRT-A
CONTINGENCY 'DVP_P1-2: LN 588_SRT-A' OPEN BRANCH FROM BUS 314909 TO BUS 314927 CKT 1 /*8FENTRES 500.0 - 8YADKIN 500.0 END |
OP | AC | 121.68 % | 548.02 | B | 666.85 | 87.97 | ||
| DVP |
6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line
314390 to 314214 ckt 1 |
DVP_P1-2: LN 567_SRT-A
CONTINGENCY 'DVP_P1-2: LN 567_SRT-A' OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1 /*8CHCKAHM 500.0 - 8SURRY 500.0 END |
OP | AC | 121.16 % | 678.68 | B | 822.27 | 71.46 | ||
| DVP |
6WALR285-6LIGH285 230.0 kV Ckt 1 line
314413 to 314390 ckt 1 |
DVP_P1-2: LN 567_SRT-A
CONTINGENCY 'DVP_P1-2: LN 567_SRT-A' OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1 /*8CHCKAHM 500.0 - 8SURRY 500.0 END |
OP | AC | 120.59 % | 678.68 | B | 818.45 | 71.58 | ||
| DVP |
6CHCKAHM-6ELKO 230.0 kV Ckt 1 line
314214 to 314258 ckt 1 |
DVP_P1-2: LN 557_SRT-S
CONTINGENCY 'DVP_P1-2: LN 557_SRT-S' OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1 /*8CHCKAHM 500.0 - 8ELMONT 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 END |
OP | AC | 118.3 % | 678.68 | B | 802.87 | 53.09 | ||
| DVP |
AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line
961610 to 942550 ckt 2 |
DVP_P1-2: LN 2197_SRT-A-2
CONTINGENCY 'DVP_P1-2: LN 2197_SRT-A-2' OPEN BRANCH FROM BUS 935160 TO BUS 314303 CKT 1 /*AD1-151 TP 230.0 - 6HOPEWLL 230.0 END |
OP | AC | 117.44 % | 678.68 | B | 797.05 | 59.95 | ||
| DVP |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
314902 to 314914 ckt 1 |
Base Case | OP | DC | 115.71 % | 3220.44 | A | 3726.4 | 175.62 | ||
| DVP |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line
314209 to 314386 ckt 1 |
DVP_P1-2: LN 567_SRT-A
CONTINGENCY 'DVP_P1-2: LN 567_SRT-A' OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1 /*8CHCKAHM 500.0 - 8SURRY 500.0 END |
OP | AC | 114.27 % | 984.18 | B | 1124.62 | 82.66 | ||
| DVP |
6SURRY-AG1-000B TP 230.0 kV Ckt 2 line
314538 to 961610 ckt 2 |
DVP_P1-2: LN 2197_SRT-A-2
CONTINGENCY 'DVP_P1-2: LN 2197_SRT-A-2' OPEN BRANCH FROM BUS 935160 TO BUS 314303 CKT 1 /*AD1-151 TP 230.0 - 6HOPEWLL 230.0 END |
OP | AC | 112.74 % | 678.68 | B | 765.13 | 59.95 | ||
| DVP |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line
314386 to 314296 ckt 1 |
DVP_P1-2: LN 567_SRT-A
CONTINGENCY 'DVP_P1-2: LN 567_SRT-A' OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1 /*8CHCKAHM 500.0 - 8SURRY 500.0 END |
OP | AC | 110.93 % | 984.18 | B | 1091.71 | 82.66 | ||
| DVP |
8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line
314927 to 314928 ckt 1 |
DVP_P1-2: LN 579_SRT-S-1
CONTINGENCY 'DVP_P1-2: LN 579_SRT-S-1' OPEN BRANCH FROM BUS 314923 TO BUS 314927 CKT 1 /*8SEPTA 500.0 - 8YADKIN 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 940640 TO BUS 314902 CKT 1 /*AE2-051 TP 500.0 - 8CARSON 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 940640 TO BUS 314923 CKT 1 /*AE2-051 TP 500.0 - 8SEPTA 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 940640 TO BUS 314902 CKT 1 /*AE2-051 TP 500.0 - 8CARSON 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 940640 TO BUS 314923 CKT 1 /*AE2-051 TP 500.0 - 8SEPTA 500.0 END |
OP | AC | 110.35 % | 2442.12 | B | 2694.93 | 609.06 | ||
| DVP |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line
314296 to 314415 ckt 1 |
DVP_P1-2: LN 567_SRT-A
CONTINGENCY 'DVP_P1-2: LN 567_SRT-A' OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1 /*8CHCKAHM 500.0 - 8SURRY 500.0 END |
OP | AC | 109.2 % | 984.18 | B | 1074.74 | 82.66 | ||
| DVP |
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
314934 to 314916 ckt 1 |
Base Case | OP | AC | 106.05 % | 3220.44 | A | 3415.13 | 127.32 | ||
| DVP |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
314924 to 314903 ckt 1 |
Base Case | OP | AC | 105.39 % | 2442.12 | A | 2573.65 | 210.5 | ||
| DVP |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line
314287 to 314260 ckt 1 |
DVP_P1-2: LN 557_SRT-S
CONTINGENCY 'DVP_P1-2: LN 557_SRT-S' OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1 /*8CHCKAHM 500.0 - 8ELMONT 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 END |
OP | AC | 105.31 % | 984.18 | B | 1036.39 | 51.75 | ||
| DVP |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line
314260 to 314225 ckt 1 |
DVP_P1-2: LN 557_SRT-S
CONTINGENCY 'DVP_P1-2: LN 557_SRT-S' OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1 /*8CHCKAHM 500.0 - 8ELMONT 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 END |
OP | AC | 105.27 % | 984.18 | B | 1036.03 | 51.75 | ||
| DVP |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
314914 to 314918 ckt 1 |
Base Case | OP | DC | 104.82 % | 3193.18 | A | 3347.18 | 173.38 | ||
| DVP |
AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line
316099 to 313902 ckt 1 |
Base Case | OP | AC | 104.32 % | 678.68 | A | 708.03 | 44.16 | ||
| DVP |
6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line
313902 to 314303 ckt 1 |
Base Case | OP | AC | 104.29 % | 678.68 | A | 707.79 | 44.16 | ||
| DVP |
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
314905 to 314900 ckt 1 |
DVP_P1-2: LN 594_SRT-S
CONTINGENCY 'DVP_P1-2: LN 594_SRT-S' OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1 /*8MORRSVL 500.0 - 8SPOTSYL 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER 500.0 - 8MORRSVL 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER 500.0 - 8MORRSVL 500.0 END |
OP | AC | 104.11 % | 4070.2 | B | 4237.54 | 170.41 | ||
| DVP |
6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line
314241 to 314242 ckt 1 |
DVP_P1-2: LN 557_SRT-S
CONTINGENCY 'DVP_P1-2: LN 557_SRT-S' OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1 /*8CHCKAHM 500.0 - 8ELMONT 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 END |
OP | AC | 104.02 % | 898.64 | B | 934.76 | 69.28 | ||
| DVP |
8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
314911 to 314905 ckt 1 |
DVP_P1-2: LN 573_SRT-A
CONTINGENCY 'DVP_P1-2: LN 573_SRT-A' OPEN BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA 500.0 - 8SPOTSYL 500.0 END |
OP | AC | 103.99 % | 4070.2 | B | 4232.55 | 173.77 | ||
| DVP |
6WALR209-6LIGH209 230.0 kV Ckt 1 line
314415 to 314391 ckt 1 |
DVP_P1-2: LN 567_SRT-A
CONTINGENCY 'DVP_P1-2: LN 567_SRT-A' OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1 /*8CHCKAHM 500.0 - 8SURRY 500.0 END |
OP | AC | 103.05 % | 984.18 | B | 1014.15 | 82.66 | ||
| DVP |
6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line
314225 to 314227 ckt 1 |
DVP_P1-2: LN 557_SRT-S
CONTINGENCY 'DVP_P1-2: LN 557_SRT-S' OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1 /*8CHCKAHM 500.0 - 8ELMONT 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 END |
OP | AC | 101.68 % | 984.18 | B | 1000.73 | 51.75 | ||
| Details for 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 934521 | AD1-076 C | 50/50 | 8.19 MW | 8.19 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 934522 | AD1-076 E | 50/50 | 4.17 MW | 4.17 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 940491 | AE2-034 C | 50/50 | 0.83 MW | 0.83 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 940492 | AE2-034 E | 50/50 | 2.63 MW | 2.63 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 957531 | AF2-047 C | 50/50 | 14.59 MW | 14.59 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 957532 | AF2-047 E | 50/50 | 7.34 MW | 7.34 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 916042 | Z1-036 E | 50/50 | 33.27 MW | 33.27 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 313526 | AB2-022 C | 50/50 | 0.65 MW | 0.65 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 314295 | 6BIRDNECK | 50/50 | 0.02 MW | 0.02 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 314550 | 6HICKORY | 50/50 | 6.67 MW | 6.67 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944871 | AF1-152 C | 50/50 | 6.03 MW | 6.03 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944872 | AF1-152 E | 50/50 | 4.02 MW | 4.02 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 315605 | 6W1-029WIND | 50/50 | 0.75 MW | 0.75 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 315611 | 6Z1-036WIND | 50/50 | 7.89 MW | 7.89 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 913392 | Y1-086 E | 50/50 | 4.5 MW | 4.5 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 916192 | Z1-068 E | 50/50 | 1.18 MW | 1.18 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 923832 | AB2-022 E | 50/50 | 2.54 MW | 2.54 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 901082 | W1-029 E | 50/50 | 36.36 MW | 36.36 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 917122 | Z2-027 E | 50/50 | 2.41 MW | 2.41 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 925522 | AC1-027 E | 50/50 | 0.76 MW | 0.76 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 941501 | AE2-147 C | 50/50 | 18.08 MW | 18.08 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 941502 | AE2-147 E | 50/50 | 12.05 MW | 12.05 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 957871 | AF2-081 C | 50/50 | 27.39 MW | 27.39 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 957872 | AF2-081 E | 50/50 | 11.74 MW | 11.74 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 933981 | AD1-022 C | Adder | 4.96 MW | 4.21 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 933982 | AD1-022 E | Adder | 2.7 MW | 2.29 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 314594 | 6PLYMOUTH TP | 50/50 | 0.23 MW | 0.23 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 314632 | 6AYDLETT TAP | 50/50 | 3.48 MW | 3.48 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 316185 | AD1-033 C | 50/50 | 2.88 MW | 2.88 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 316316 | AC1-027 C | 50/50 | 0.17 MW | 0.17 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 316320 | Y1-086 C | 50/50 | 0.38 MW | 0.38 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 316321 | Z2-027 C | 50/50 | 0.55 MW | 0.55 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 934065 | AD1-033 E | 50/50 | 13.9 MW | 13.9 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 937226 | AE2-253 E | 50/50 | 16.73 MW | 16.73 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 316017 | AA1-139 ULT1 | 50/50 | 2.5 MW | 2.5 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 316018 | AA1-139 ULT2 | 50/50 | 2.5 MW | 2.5 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 919153 | AA1-139 E2 | 50/50 | 11.2 MW | 11.2 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 919152 | AA1-139 E1 | 50/50 | 11.2 MW | 11.2 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 315614 | AA2-178 C | 50/50 | 1.13 MW | 1.13 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 920692 | AA2-178 E | 50/50 | 3.51 MW | 3.51 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 925122 | AB2-169 E | Adder | 2.71 MW | 2.3 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 316388 | AE2-253 GEN | 50/50 | 4.75 MW | 4.75 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 941291 | AE2-123 C | 50/50 | 20.86 MW | 20.86 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 941292 | AE2-123 E | 50/50 | 81.35 MW | 81.35 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 941301 | AE2-124 C | 50/50 | 22.47 MW | 22.47 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 941302 | AE2-124 E | 50/50 | 98.61 MW | 98.61 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944581 | AF1-123 C | 50/50 | 151.94 MW | 151.94 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944582 | AF1-123 E | 50/50 | 347.9 MW | 347.9 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944591 | AF1-124 C | 50/50 | 151.94 MW | 151.94 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944592 | AF1-124 E | 50/50 | 347.9 MW | 347.9 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944601 | AF1-125 C | 50/50 | 151.94 MW | 151.94 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944602 | AF1-125 E | 50/50 | 347.9 MW | 347.9 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 964951 | AG1-359 C | 50/50 | 72.42 MW | 72.42 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 965691 | AG1-437 C | Adder | 4.9 MW | 4.16 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 965692 | AG1-437 E | Adder | 3.26 MW | 2.77 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 965701 | AG1-438 C | Adder | 4.9 MW | 4.16 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 965702 | AG1-438 E | Adder | 3.26 MW | 2.77 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 965741 | AG1-442 C | Adder | 2.86 MW | 2.43 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 965751 | AG1-443 C | Adder | 2.86 MW | 2.43 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 934501 | AD1-074 C | 50/50 | 22.55 MW | 22.55 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 934502 | AD1-074 E | 50/50 | 11.48 MW | 11.48 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 934511 | AD1-075 C | 50/50 | 5.64 MW | 5.64 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 934512 | AD1-075 E | 50/50 | 2.87 MW | 2.87 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 938531 | AE1-072 C | 50/50 | 45.87 MW | 45.87 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 938532 | AE1-072 E | 50/50 | 23.91 MW | 23.91 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 941281 | AE2-122 C | 50/50 | 20.3 MW | 20.3 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 941282 | AE2-122 E | 50/50 | 81.92 MW | 81.92 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 1.33 MW | 1.33 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 1.05 MW | 1.05 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 5.26 MW | 5.26 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 0.17 MW | 0.17 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | NY | PJM->LTFIMP_NY | CLTF | 0.08 MW | 0.08 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.05 MW | 0.05 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | WEC | LTFEXP_WEC->PJM | CLTF | 0.03 MW | 0.03 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | CPLE | LTFEXP_CPLE->PJM | CLTF | 0.73 MW | 0.73 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | TVA | LTFEXP_TVA->PJM | CLTF | 0.29 MW | 0.29 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | MEC | LTFEXP_MEC->PJM | CLTF | 0.18 MW | 0.18 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | LAGN | LTFEXP_LAGN->PJM | CLTF | 0.37 MW | 0.37 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.01 MW | 0.01 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 1.1 MW | 1.1 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.35 MW | 0.35 MW |
| Details for 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 961941 | AG1-037 C | Adder | 0.19 MW | 0.16 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 961942 | AG1-037 E | Adder | 0.13 MW | 0.11 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 962331 | AG1-082 C | Adder | 0.75 MW | 0.64 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 962332 | AG1-082 E | Adder | 0.5 MW | 0.43 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 962341 | AG1-083 C | Adder | 0.75 MW | 0.64 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 962342 | AG1-083 E | Adder | 0.5 MW | 0.43 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 966801 | AG1-551 C | Adder | 0.84 MW | 0.72 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 966802 | AG1-551 E | Adder | 0.44 MW | 0.38 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 314541 | 3WATKINS | Adder | 0.26 MW | 0.22 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 920042 | AA2-088 E OP | Adder | 3.6 MW | 3.06 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 934521 | AD1-076 C | 50/50 | 8.13 MW | 8.13 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 934522 | AD1-076 E | 50/50 | 4.14 MW | 4.14 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 943172 | AE2-346 E | Adder | 0.23 MW | 0.19 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 316141 | AB2-099 E | Adder | 0.09 MW | 0.08 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 900672 | V4-068 E | Adder | 0.12 MW | 0.11 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 940491 | AE2-034 C | 50/50 | 0.76 MW | 0.76 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 940492 | AE2-034 E | 50/50 | 2.41 MW | 2.41 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 957521 | AF2-046 C | Adder | 5.97 MW | 5.08 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 957522 | AF2-046 E | Adder | 3.0 MW | 2.55 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 957531 | AF2-047 C | 50/50 | 13.38 MW | 13.38 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 957532 | AF2-047 E | 50/50 | 6.73 MW | 6.73 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 314539 | 3UNCAMP | Adder | 2.41 MW | 2.05 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 916042 | Z1-036 E | 50/50 | 28.08 MW | 28.08 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 938771 | AE1-103 C | Adder | 1.19 MW | 1.01 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 938772 | AE1-103 E | Adder | 1.65 MW | 1.4 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 313526 | AB2-022 C | 50/50 | 0.46 MW | 0.46 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 314295 | 6BIRDNECK | 50/50 | 0.05 MW | 0.05 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 314507 | 3THOMPSN | Adder | 0.92 MW | 0.78 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 314525 | 6KINGFORK | Adder | 0.38 MW | 0.32 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 314550 | 6HICKORY | 50/50 | 4.21 MW | 4.21 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 935112 | AD1-144 E | Adder | 0.35 MW | 0.3 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 942341 | AE2-247 C | Adder | 0.53 MW | 0.45 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 942342 | AE2-247 E | Adder | 0.74 MW | 0.63 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 943461 | AF1-017 C | Adder | 0.48 MW | 0.41 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 943462 | AF1-017 E | Adder | 0.79 MW | 0.67 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 943612 | AF1-032 E | Adder | 0.48 MW | 0.4 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944871 | AF1-152 C | 50/50 | 5.28 MW | 5.28 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944872 | AF1-152 E | 50/50 | 3.52 MW | 3.52 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 315605 | 6W1-029WIND | 50/50 | 0.66 MW | 0.66 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 315611 | 6Z1-036WIND | 50/50 | 6.66 MW | 6.66 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 913392 | Y1-086 E | 50/50 | 3.15 MW | 3.15 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 916192 | Z1-068 E | 50/50 | 2.7 MW | 2.7 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 923832 | AB2-022 E | 50/50 | 1.78 MW | 1.78 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 957492 | AF2-043 E | Adder | 0.73 MW | 0.62 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 901082 | W1-029 E | 50/50 | 31.84 MW | 31.84 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 917122 | Z2-027 E | 50/50 | 1.76 MW | 1.76 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 925522 | AC1-027 E | 50/50 | 1.7 MW | 1.7 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 941501 | AE2-147 C | 50/50 | 15.83 MW | 15.83 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 941502 | AE2-147 E | 50/50 | 10.56 MW | 10.56 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 957871 | AF2-081 C | 50/50 | 17.72 MW | 17.72 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 957872 | AF2-081 E | 50/50 | 7.59 MW | 7.59 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 958161 | AF2-110 C | Adder | 0.63 MW | 0.54 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 958162 | AF2-110 E | Adder | 1.01 MW | 0.85 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 933981 | AD1-022 C | 50/50 | 5.27 MW | 5.27 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 933982 | AD1-022 E | 50/50 | 2.87 MW | 2.87 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 961681 | AG1-008 C | Adder | 5.98 MW | 5.09 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 961682 | AG1-008 E | Adder | 2.99 MW | 2.54 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 314594 | 6PLYMOUTH TP | 50/50 | 0.22 MW | 0.22 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 314632 | 6AYDLETT TAP | 50/50 | 2.29 MW | 2.29 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 316185 | AD1-033 C | 50/50 | 2.01 MW | 2.01 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 316316 | AC1-027 C | 50/50 | 0.37 MW | 0.37 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 316320 | Y1-086 C | 50/50 | 0.27 MW | 0.27 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 316321 | Z2-027 C | 50/50 | 0.4 MW | 0.4 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 934065 | AD1-033 E | 50/50 | 9.7 MW | 9.7 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 937226 | AE2-253 E | 50/50 | 10.71 MW | 10.71 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 918512 | AA1-065 E OP | Adder | 2.34 MW | 1.99 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 316017 | AA1-139 ULT1 | 50/50 | 1.62 MW | 1.62 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 316018 | AA1-139 ULT2 | 50/50 | 1.62 MW | 1.62 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 919153 | AA1-139 E2 | 50/50 | 7.25 MW | 7.25 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 919152 | AA1-139 E1 | 50/50 | 7.25 MW | 7.25 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 315614 | AA2-178 C | 50/50 | 1.03 MW | 1.03 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 920692 | AA2-178 E | 50/50 | 3.22 MW | 3.22 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 925122 | AB2-169 E | Adder | 2.94 MW | 2.5 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 316311 | AC2-079 C | Adder | 2.13 MW | 1.81 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 932596 | AC2-079 E | Adder | 3.47 MW | 2.95 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 316349 | AD2-085 C | Adder | 1.23 MW | 1.05 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 936666 | AD2-085 E | Adder | 2.01 MW | 1.71 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 316388 | AE2-253 GEN | 50/50 | 3.04 MW | 3.04 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 941291 | AE2-123 C | 50/50 | 44.94 MW | 44.94 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 941292 | AE2-123 E | 50/50 | 175.23 MW | 175.23 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 941301 | AE2-124 C | 50/50 | 45.04 MW | 45.04 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 941302 | AE2-124 E | 50/50 | 197.63 MW | 197.63 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944581 | AF1-123 C | 50/50 | 95.08 MW | 95.08 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944582 | AF1-123 E | 50/50 | 217.7 MW | 217.7 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944591 | AF1-124 C | 50/50 | 95.08 MW | 95.08 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944592 | AF1-124 E | 50/50 | 217.7 MW | 217.7 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944601 | AF1-125 C | 50/50 | 95.08 MW | 95.08 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944602 | AF1-125 E | 50/50 | 217.7 MW | 217.7 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 964951 | AG1-359 C | 50/50 | 45.32 MW | 45.32 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 965691 | AG1-437 C | Adder | 5.59 MW | 4.75 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 965692 | AG1-437 E | Adder | 3.73 MW | 3.17 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 965701 | AG1-438 C | Adder | 5.59 MW | 4.75 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 965702 | AG1-438 E | Adder | 3.73 MW | 3.17 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 965741 | AG1-442 C | Adder | 3.26 MW | 2.77 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 965751 | AG1-443 C | Adder | 3.26 MW | 2.77 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 934501 | AD1-074 C | 50/50 | 22.38 MW | 22.38 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 934502 | AD1-074 E | 50/50 | 11.39 MW | 11.39 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 934511 | AD1-075 C | 50/50 | 5.59 MW | 5.59 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 934512 | AD1-075 E | 50/50 | 2.85 MW | 2.85 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 938531 | AE1-072 C | 50/50 | 30.04 MW | 30.04 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 938532 | AE1-072 E | 50/50 | 15.66 MW | 15.66 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 941101 | AE2-104 C | Adder | 1.55 MW | 1.32 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 941102 | AE2-104 E | Adder | 2.46 MW | 2.09 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 941281 | AE2-122 C | 50/50 | 43.73 MW | 43.73 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 941282 | AE2-122 E | 50/50 | 176.44 MW | 176.44 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 2.78 MW | 2.78 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 1.83 MW | 1.83 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 8.0 MW | 8.0 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 0.19 MW | 0.19 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | NY | PJM->LTFIMP_NY | CLTF | 0.09 MW | 0.09 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.11 MW | 0.11 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | WEC | LTFEXP_WEC->PJM | CLTF | 0.06 MW | 0.06 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | CPLE | LTFEXP_CPLE->PJM | CLTF | 1.09 MW | 1.09 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | TVA | LTFEXP_TVA->PJM | CLTF | 0.48 MW | 0.48 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | MEC | LTFEXP_MEC->PJM | CLTF | 0.33 MW | 0.33 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | LAGN | LTFEXP_LAGN->PJM | CLTF | 0.62 MW | 0.62 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.02 MW | 0.02 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 1.22 MW | 1.22 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.52 MW | 0.52 MW |
| Details for 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 934521 | AD1-076 C | Adder | 4.6 MW | 3.91 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 934522 | AD1-076 E | Adder | 2.35 MW | 2.0 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 940492 | AE2-034 E | Adder | 1.45 MW | 1.23 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 957531 | AF2-047 C | Adder | 8.04 MW | 6.83 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 957532 | AF2-047 E | Adder | 4.04 MW | 3.44 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 916042 | Z1-036 E | 50/50 | 17.96 MW | 17.96 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 313526 | AB2-022 C | 50/50 | 0.34 MW | 0.34 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 314507 | 3THOMPSN | Adder | -0.89 MW | -0.75 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 314550 | 6HICKORY | 50/50 | 3.39 MW | 3.39 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944871 | AF1-152 C | 50/50 | 3.28 MW | 3.28 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944872 | AF1-152 E | 50/50 | 2.19 MW | 2.19 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 315605 | 6W1-029WIND | 50/50 | 0.41 MW | 0.41 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 315611 | 6Z1-036WIND | 50/50 | 4.26 MW | 4.26 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 913392 | Y1-086 E | 50/50 | 2.33 MW | 2.33 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 923832 | AB2-022 E | 50/50 | 1.32 MW | 1.32 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 901082 | W1-029 E | 50/50 | 19.8 MW | 19.8 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 917122 | Z2-027 E | 50/50 | 1.26 MW | 1.26 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 941501 | AE2-147 C | 50/50 | 9.85 MW | 9.85 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 941502 | AE2-147 E | 50/50 | 6.56 MW | 6.56 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 957871 | AF2-081 C | 50/50 | 13.98 MW | 13.98 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 957872 | AF2-081 E | 50/50 | 5.99 MW | 5.99 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 933981 | AD1-022 C | Adder | 2.84 MW | 2.41 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 933982 | AD1-022 E | Adder | 1.55 MW | 1.31 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 314594 | 6PLYMOUTH TP | Adder | 0.13 MW | 0.11 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 314632 | 6AYDLETT TAP | 50/50 | 1.78 MW | 1.78 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 316185 | AD1-033 C | 50/50 | 2.12 MW | 2.12 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 316320 | Y1-086 C | 50/50 | 0.2 MW | 0.2 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 316321 | Z2-027 C | 50/50 | 0.29 MW | 0.29 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 934065 | AD1-033 E | 50/50 | 10.26 MW | 10.26 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 937226 | AE2-253 E | 50/50 | 8.53 MW | 8.53 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 316017 | AA1-139 ULT1 | 50/50 | 1.28 MW | 1.28 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 316018 | AA1-139 ULT2 | 50/50 | 1.28 MW | 1.28 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 919153 | AA1-139 E2 | 50/50 | 5.72 MW | 5.72 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 919152 | AA1-139 E1 | 50/50 | 5.72 MW | 5.72 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 920692 | AA2-178 E | Adder | 1.93 MW | 1.64 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 316388 | AE2-253 GEN | 50/50 | 2.42 MW | 2.42 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944581 | AF1-123 C | 50/50 | 77.08 MW | 77.08 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944582 | AF1-123 E | 50/50 | 176.48 MW | 176.48 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944591 | AF1-124 C | 50/50 | 77.08 MW | 77.08 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944592 | AF1-124 E | 50/50 | 176.48 MW | 176.48 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944601 | AF1-125 C | 50/50 | 77.08 MW | 77.08 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944602 | AF1-125 E | 50/50 | 176.48 MW | 176.48 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 964951 | AG1-359 C | 50/50 | 36.74 MW | 36.74 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 934501 | AD1-074 C | Adder | 12.68 MW | 10.78 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 934502 | AD1-074 E | Adder | 6.46 MW | 5.49 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 934511 | AD1-075 C | Adder | 3.17 MW | 2.69 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 934512 | AD1-075 E | Adder | 1.61 MW | 1.37 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 938531 | AE1-072 C | 50/50 | 23.47 MW | 23.47 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 938532 | AE1-072 E | 50/50 | 12.23 MW | 12.23 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 1.12 MW | 1.12 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 0.77 MW | 0.77 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 3.5 MW | 3.5 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 0.09 MW | 0.09 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | NY | PJM->LTFIMP_NY | CLTF | 0.04 MW | 0.04 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.04 MW | 0.04 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | WEC | LTFEXP_WEC->PJM | CLTF | 0.02 MW | 0.02 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | CPLE | LTFEXP_CPLE->PJM | CLTF | 0.48 MW | 0.48 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | TVA | LTFEXP_TVA->PJM | CLTF | 0.21 MW | 0.21 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | MEC | LTFEXP_MEC->PJM | CLTF | 0.14 MW | 0.14 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | LAGN | LTFEXP_LAGN->PJM | CLTF | 0.27 MW | 0.27 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.01 MW | 0.01 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 0.59 MW | 0.59 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.23 MW | 0.23 MW |
| Details for 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 934521 | AD1-076 C | Adder | 4.62 MW | 3.93 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 934522 | AD1-076 E | Adder | 2.36 MW | 2.0 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 940492 | AE2-034 E | Adder | 1.45 MW | 1.24 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 957531 | AF2-047 C | Adder | 8.06 MW | 6.85 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 957532 | AF2-047 E | Adder | 4.05 MW | 3.45 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 916042 | Z1-036 E | 50/50 | 18.0 MW | 18.0 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 313526 | AB2-022 C | 50/50 | 0.34 MW | 0.34 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 314507 | 3THOMPSN | Adder | -0.88 MW | -0.75 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 314550 | 6HICKORY | 50/50 | 3.39 MW | 3.39 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944871 | AF1-152 C | 50/50 | 3.29 MW | 3.29 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944872 | AF1-152 E | 50/50 | 2.19 MW | 2.19 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 315605 | 6W1-029WIND | 50/50 | 0.41 MW | 0.41 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 315611 | 6Z1-036WIND | 50/50 | 4.27 MW | 4.27 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 913392 | Y1-086 E | 50/50 | 2.34 MW | 2.34 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 923832 | AB2-022 E | 50/50 | 1.32 MW | 1.32 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 901082 | W1-029 E | 50/50 | 19.84 MW | 19.84 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 917122 | Z2-027 E | 50/50 | 1.26 MW | 1.26 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 941501 | AE2-147 C | 50/50 | 9.87 MW | 9.87 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 941502 | AE2-147 E | 50/50 | 6.58 MW | 6.58 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 957871 | AF2-081 C | 50/50 | 13.99 MW | 13.99 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 957872 | AF2-081 E | 50/50 | 6.0 MW | 6.0 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 933981 | AD1-022 C | Adder | 2.85 MW | 2.42 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 933982 | AD1-022 E | Adder | 1.55 MW | 1.32 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 314594 | 6PLYMOUTH TP | Adder | 0.13 MW | 0.11 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 314632 | 6AYDLETT TAP | 50/50 | 1.78 MW | 1.78 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 316320 | Y1-086 C | 50/50 | 0.2 MW | 0.2 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 316321 | Z2-027 C | 50/50 | 0.29 MW | 0.29 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 937226 | AE2-253 E | 50/50 | 8.53 MW | 8.53 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 316017 | AA1-139 ULT1 | 50/50 | 1.28 MW | 1.28 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 316018 | AA1-139 ULT2 | 50/50 | 1.28 MW | 1.28 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 919153 | AA1-139 E2 | 50/50 | 5.72 MW | 5.72 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 919152 | AA1-139 E1 | 50/50 | 5.72 MW | 5.72 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 920692 | AA2-178 E | Adder | 1.94 MW | 1.65 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 316388 | AE2-253 GEN | 50/50 | 2.42 MW | 2.42 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944581 | AF1-123 C | 50/50 | 77.14 MW | 77.14 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944582 | AF1-123 E | 50/50 | 176.62 MW | 176.62 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944591 | AF1-124 C | 50/50 | 77.14 MW | 77.14 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944592 | AF1-124 E | 50/50 | 176.62 MW | 176.62 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944601 | AF1-125 C | 50/50 | 77.14 MW | 77.14 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944602 | AF1-125 E | 50/50 | 176.62 MW | 176.62 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 964951 | AG1-359 C | 50/50 | 36.77 MW | 36.77 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 934501 | AD1-074 C | Adder | 12.72 MW | 10.82 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 934502 | AD1-074 E | Adder | 6.48 MW | 5.51 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 934511 | AD1-075 C | Adder | 3.18 MW | 2.7 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 934512 | AD1-075 E | Adder | 1.62 MW | 1.38 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 938531 | AE1-072 C | 50/50 | 23.49 MW | 23.49 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 938532 | AE1-072 E | 50/50 | 12.25 MW | 12.25 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 1.5 MW | 1.5 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 0.92 MW | 0.92 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 3.73 MW | 3.73 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 0.07 MW | 0.07 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | NY | PJM->LTFIMP_NY | CLTF | 0.03 MW | 0.03 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.06 MW | 0.06 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | WEC | LTFEXP_WEC->PJM | CLTF | 0.03 MW | 0.03 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | CPLE | LTFEXP_CPLE->PJM | CLTF | 0.5 MW | 0.5 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | TVA | LTFEXP_TVA->PJM | CLTF | 0.24 MW | 0.24 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | MEC | LTFEXP_MEC->PJM | CLTF | 0.17 MW | 0.17 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | LAGN | LTFEXP_LAGN->PJM | CLTF | 0.3 MW | 0.3 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.01 MW | 0.01 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 0.44 MW | 0.44 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.24 MW | 0.24 MW |
| Details for AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 916042 | Z1-036 E | Adder | 10.33 MW | 8.78 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 314507 | 3THOMPSN | Adder | 1.02 MW | 0.87 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 314525 | 6KINGFORK | Adder | 0.56 MW | 0.48 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 314550 | 6HICKORY | Adder | 0.92 MW | 0.78 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 315092 | 1YORKTN3 | Adder | 50.86 MW | 43.23 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 926662 | AC1-147 E | Adder | 0.67 MW | 0.57 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 927226 | AC1-216 E | 50/50 | 10.84 MW | 10.84 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 935112 | AD1-144 E | Adder | 0.52 MW | 0.44 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 943612 | AF1-032 E | Adder | 0.38 MW | 0.32 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 944871 | AF1-152 C | Adder | 2.03 MW | 1.72 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 944872 | AF1-152 E | Adder | 1.35 MW | 1.15 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 315116 | 1SURRY 1 | 50/50 | 29.29 MW | 29.29 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 315117 | 1GRAVELC | 50/50 | 1.02 MW | 1.02 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 315119 | 1GRAVEL3 | 50/50 | 2.98 MW | 2.98 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 315120 | 1GRAVEL4 | 50/50 | 3.01 MW | 3.01 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 315121 | 1GRAVEL5 | 50/50 | 2.98 MW | 2.98 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 315122 | 1GRAVEL6 | 50/50 | 3.01 MW | 3.01 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 315260 | 1GOSPORTA | Adder | 1.08 MW | 0.92 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 315261 | 1GOSPORTB | Adder | 1.38 MW | 1.17 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 315262 | 1GOSPORTC | Adder | 1.17 MW | 1.0 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 315611 | 6Z1-036WIND | Adder | 2.45 MW | 2.08 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 316132 | AB2-190 C | 50/50 | 14.24 MW | 14.24 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 913392 | Y1-086 E | Adder | 0.87 MW | 0.74 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 916192 | Z1-068 E | Adder | 0.87 MW | 0.74 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 923832 | AB2-022 E | Adder | 0.49 MW | 0.42 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 939312 | AE1-162 E | 50/50 | 1.52 MW | 1.52 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 957492 | AF2-043 E | Adder | 0.58 MW | 0.49 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 901082 | W1-029 E | Adder | 12.23 MW | 10.39 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 917122 | Z2-027 E | Adder | 0.53 MW | 0.45 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 925332 | AB2-190 E | 50/50 | 29.1 MW | 29.1 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 925522 | AC1-027 E | Adder | 0.57 MW | 0.48 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 941501 | AE2-147 C | Adder | 6.08 MW | 5.17 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 941502 | AE2-147 E | Adder | 4.05 MW | 3.45 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 957871 | AF2-081 C | Adder | 4.14 MW | 3.52 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 957872 | AF2-081 E | Adder | 1.77 MW | 1.51 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 934011 | AD1-025 C | 50/50 | 23.68 MW | 23.68 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 934012 | AD1-025 E | 50/50 | 14.03 MW | 14.03 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 314632 | 6AYDLETT TAP | Adder | 0.56 MW | 0.47 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 316236 | AE1-162 C | 50/50 | 0.31 MW | 0.31 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 316240 | AF1-291 C | Adder | -0.82 MW | -0.69 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 316301 | AE2-228 C | Adder | -0.79 MW | -0.68 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 316369 | AC1-216 C | 50/50 | 1.9 MW | 1.9 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 934065 | AD1-033 E | Adder | 2.15 MW | 1.83 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 937226 | AE2-253 E | Adder | 2.44 MW | 2.07 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 963221 | AG1-171 C | 50/50 | 3.02 MW | 3.02 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 963222 | AG1-171 E | 50/50 | 2.01 MW | 2.01 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 963231 | AG1-172 C | 50/50 | 3.02 MW | 3.02 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 963232 | AG1-172 E | 50/50 | 2.01 MW | 2.01 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 963241 | AG1-173 C | 50/50 | 3.02 MW | 3.02 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 963242 | AG1-173 E | 50/50 | 2.01 MW | 2.01 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 963251 | AG1-174 C | 50/50 | 3.02 MW | 3.02 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 963252 | AG1-174 E | 50/50 | 2.01 MW | 2.01 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 919153 | AA1-139 E2 | Adder | 1.69 MW | 1.44 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 919152 | AA1-139 E1 | Adder | 1.69 MW | 1.44 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 316033 | AB2-134 GEN | 50/50 | 2.49 MW | 2.49 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 924814 | AB2-134 E | 50/50 | 17.75 MW | 17.75 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 932046 | AC2-012 E | Adder | 6.66 MW | 5.66 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 961611 | AG1-000B C | 50/50 | 28.59 MW | 28.59 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 941291 | AE2-123 C | Adder | 13.42 MW | 11.41 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 941292 | AE2-123 E | Adder | 52.35 MW | 44.5 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 941301 | AE2-124 C | Adder | 12.08 MW | 10.26 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 941302 | AE2-124 E | Adder | 52.98 MW | 45.04 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 941591 | AE2-156 C | Adder | 9.01 MW | 7.66 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 942551 | AE2-270 C | 50/50 | 77.5 MW | 77.5 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 944581 | AF1-123 C | Adder | 18.07 MW | 15.36 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 944582 | AF1-123 E | Adder | 41.38 MW | 35.17 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 944591 | AF1-124 C | Adder | 18.07 MW | 15.36 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 944592 | AF1-124 E | Adder | 41.38 MW | 35.17 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 944601 | AF1-125 C | Adder | 18.07 MW | 15.36 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 944602 | AF1-125 E | Adder | 41.38 MW | 35.17 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 957711 | AF2-065 C | 50/50 | 39.53 MW | 39.53 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 957712 | AF2-065 E | 50/50 | 37.98 MW | 37.98 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 961711 | AG1-011 C | 50/50 | 40.22 MW | 40.22 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 964951 | AG1-359 C | Adder | 9.7 MW | 8.24 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 965001 | AG1-364 C | Adder | 3.61 MW | 3.07 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 965002 | AG1-364 E | Adder | 5.42 MW | 4.6 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 966611 | AG1-531 C | 50/50 | 5.38 MW | 5.38 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 966612 | AG1-531 E | 50/50 | 3.58 MW | 3.58 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 935161 | AD1-151 C | 50/50 | 22.63 MW | 22.63 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 935162 | AD1-151 E | 50/50 | 15.08 MW | 15.08 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 938531 | AE1-072 C | Adder | 7.22 MW | 6.14 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 938532 | AE1-072 E | Adder | 3.77 MW | 3.2 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 941281 | AE2-122 C | Adder | 13.06 MW | 11.1 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 941282 | AE2-122 E | Adder | 52.71 MW | 44.8 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 0.85 MW | 0.85 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 7.23 MW | 7.23 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 0.46 MW | 0.46 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | NY | PJM->LTFIMP_NY | CLTF | 0.23 MW | 0.23 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.0 MW | 0.0 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | CPLE | LTFEXP_CPLE->PJM | CLTF | 0.98 MW | 0.98 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | TVA | LTFEXP_TVA->PJM | CLTF | 0.3 MW | 0.3 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | TRIMBLE | PJM->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | MEC | LTFEXP_MEC->PJM | CLTF | 0.07 MW | 0.07 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | LAGN | LTFEXP_LAGN->PJM | CLTF | 0.38 MW | 0.38 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.0 MW | 0.0 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 2.94 MW | 2.94 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.47 MW | 0.47 MW |
| Details for 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 916042 | Z1-036 E | Adder | 10.33 MW | 8.78 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 314507 | 3THOMPSN | Adder | 1.02 MW | 0.87 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 314525 | 6KINGFORK | Adder | 0.56 MW | 0.48 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 314550 | 6HICKORY | Adder | 0.92 MW | 0.78 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 315092 | 1YORKTN3 | Adder | 50.86 MW | 43.23 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 926662 | AC1-147 E | Adder | 0.67 MW | 0.57 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 927226 | AC1-216 E | 50/50 | 10.84 MW | 10.84 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 935112 | AD1-144 E | Adder | 0.52 MW | 0.44 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 943612 | AF1-032 E | Adder | 0.38 MW | 0.32 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 944871 | AF1-152 C | Adder | 2.03 MW | 1.72 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 944872 | AF1-152 E | Adder | 1.35 MW | 1.15 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 315116 | 1SURRY 1 | 50/50 | 29.29 MW | 29.29 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 315117 | 1GRAVELC | 50/50 | 1.02 MW | 1.02 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 315119 | 1GRAVEL3 | 50/50 | 2.98 MW | 2.98 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 315120 | 1GRAVEL4 | 50/50 | 3.01 MW | 3.01 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 315121 | 1GRAVEL5 | 50/50 | 2.98 MW | 2.98 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 315122 | 1GRAVEL6 | 50/50 | 3.01 MW | 3.01 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 315260 | 1GOSPORTA | Adder | 1.08 MW | 0.92 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 315261 | 1GOSPORTB | Adder | 1.38 MW | 1.17 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 315262 | 1GOSPORTC | Adder | 1.17 MW | 1.0 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 315611 | 6Z1-036WIND | Adder | 2.45 MW | 2.08 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 316132 | AB2-190 C | 50/50 | 14.24 MW | 14.24 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 913392 | Y1-086 E | Adder | 0.87 MW | 0.74 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 916192 | Z1-068 E | Adder | 0.87 MW | 0.74 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 923832 | AB2-022 E | Adder | 0.49 MW | 0.42 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 939312 | AE1-162 E | 50/50 | 1.52 MW | 1.52 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 957492 | AF2-043 E | Adder | 0.58 MW | 0.49 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 901082 | W1-029 E | Adder | 12.23 MW | 10.39 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 917122 | Z2-027 E | Adder | 0.53 MW | 0.45 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 925332 | AB2-190 E | 50/50 | 29.1 MW | 29.1 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 925522 | AC1-027 E | Adder | 0.57 MW | 0.48 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 941501 | AE2-147 C | Adder | 6.08 MW | 5.17 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 941502 | AE2-147 E | Adder | 4.05 MW | 3.45 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 957871 | AF2-081 C | Adder | 4.14 MW | 3.52 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 957872 | AF2-081 E | Adder | 1.77 MW | 1.51 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 934011 | AD1-025 C | 50/50 | 23.68 MW | 23.68 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 934012 | AD1-025 E | 50/50 | 14.03 MW | 14.03 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 314632 | 6AYDLETT TAP | Adder | 0.56 MW | 0.47 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 316236 | AE1-162 C | 50/50 | 0.31 MW | 0.31 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 316240 | AF1-291 C | Adder | -0.82 MW | -0.69 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 316301 | AE2-228 C | Adder | -0.79 MW | -0.68 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 316369 | AC1-216 C | 50/50 | 1.9 MW | 1.9 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 934065 | AD1-033 E | Adder | 2.15 MW | 1.83 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 937226 | AE2-253 E | Adder | 2.44 MW | 2.07 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 963221 | AG1-171 C | 50/50 | 3.02 MW | 3.02 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 963222 | AG1-171 E | 50/50 | 2.01 MW | 2.01 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 963231 | AG1-172 C | 50/50 | 3.02 MW | 3.02 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 963232 | AG1-172 E | 50/50 | 2.01 MW | 2.01 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 963241 | AG1-173 C | 50/50 | 3.02 MW | 3.02 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 963242 | AG1-173 E | 50/50 | 2.01 MW | 2.01 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 963251 | AG1-174 C | 50/50 | 3.02 MW | 3.02 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 963252 | AG1-174 E | 50/50 | 2.01 MW | 2.01 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 919153 | AA1-139 E2 | Adder | 1.69 MW | 1.44 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 919152 | AA1-139 E1 | Adder | 1.69 MW | 1.44 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 316033 | AB2-134 GEN | 50/50 | 2.49 MW | 2.49 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 924814 | AB2-134 E | 50/50 | 17.75 MW | 17.75 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 932046 | AC2-012 E | Adder | 6.66 MW | 5.66 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 961611 | AG1-000B C | 50/50 | 28.59 MW | 28.59 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 941291 | AE2-123 C | Adder | 13.42 MW | 11.41 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 941292 | AE2-123 E | Adder | 52.35 MW | 44.5 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 941301 | AE2-124 C | Adder | 12.08 MW | 10.26 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 941302 | AE2-124 E | Adder | 52.98 MW | 45.04 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 941591 | AE2-156 C | Adder | 9.01 MW | 7.66 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 942551 | AE2-270 C | 50/50 | 77.5 MW | 77.5 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 944581 | AF1-123 C | Adder | 18.07 MW | 15.36 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 944582 | AF1-123 E | Adder | 41.38 MW | 35.17 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 944591 | AF1-124 C | Adder | 18.07 MW | 15.36 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 944592 | AF1-124 E | Adder | 41.38 MW | 35.17 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 944601 | AF1-125 C | Adder | 18.07 MW | 15.36 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 944602 | AF1-125 E | Adder | 41.38 MW | 35.17 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 957711 | AF2-065 C | 50/50 | 39.53 MW | 39.53 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 957712 | AF2-065 E | 50/50 | 37.98 MW | 37.98 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 961711 | AG1-011 C | 50/50 | 40.22 MW | 40.22 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 964951 | AG1-359 C | Adder | 9.7 MW | 8.24 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 965001 | AG1-364 C | Adder | 3.61 MW | 3.07 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 965002 | AG1-364 E | Adder | 5.42 MW | 4.6 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 966611 | AG1-531 C | 50/50 | 5.38 MW | 5.38 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 966612 | AG1-531 E | 50/50 | 3.58 MW | 3.58 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 935161 | AD1-151 C | 50/50 | 22.63 MW | 22.63 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 935162 | AD1-151 E | 50/50 | 15.08 MW | 15.08 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 938531 | AE1-072 C | Adder | 7.22 MW | 6.14 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 938532 | AE1-072 E | Adder | 3.77 MW | 3.2 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 941281 | AE2-122 C | Adder | 13.06 MW | 11.1 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 941282 | AE2-122 E | Adder | 52.71 MW | 44.8 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 0.85 MW | 0.85 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 7.23 MW | 7.23 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 0.46 MW | 0.46 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | NY | PJM->LTFIMP_NY | CLTF | 0.23 MW | 0.23 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.0 MW | 0.0 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | CPLE | LTFEXP_CPLE->PJM | CLTF | 0.98 MW | 0.98 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | TVA | LTFEXP_TVA->PJM | CLTF | 0.3 MW | 0.3 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | TRIMBLE | PJM->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | MEC | LTFEXP_MEC->PJM | CLTF | 0.07 MW | 0.07 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | LAGN | LTFEXP_LAGN->PJM | CLTF | 0.38 MW | 0.38 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.0 MW | 0.0 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 2.94 MW | 2.94 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2197_SRT-A-2 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.47 MW | 0.47 MW |
| Details for 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314507 | 3THOMPSN | Adder | 0.68 MW | 0.58 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314525 | 6KINGFORK | Adder | 0.36 MW | 0.3 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314550 | 6HICKORY | Adder | 0.71 MW | 0.6 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315060 | 1CHESTF5 | 50/50 | 78.55 MW | 78.55 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315061 | 1CHESTG7 | 50/50 | 4.04 MW | 4.04 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315062 | 1CHESTS7 | 50/50 | 1.86 MW | 1.86 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315063 | 1CHESTG8 | 50/50 | 3.98 MW | 3.98 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315064 | 1CHESTS8 | 50/50 | 2.05 MW | 2.05 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315073 | 1STONECA | 50/50 | 4.58 MW | 4.58 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315076 | 1HOPPOLC | 50/50 | 0.86 MW | 0.86 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315077 | 1HOPHCF1 | 50/50 | 1.36 MW | 1.36 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315078 | 1HOPHCF2 | 50/50 | 1.36 MW | 1.36 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315079 | 1HOPHCF3 | 50/50 | 1.36 MW | 1.36 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315080 | 1HOPHCF4 | 50/50 | 2.07 MW | 2.07 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315092 | 1YORKTN3 | Adder | 57.3 MW | 48.7 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 925865 | AC1-065 E | Adder | 7.33 MW | 6.23 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 926472 | AC1-118 E | Adder | 0.38 MW | 0.33 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 926662 | AC1-147 E | Adder | 0.45 MW | 0.38 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 926755 | AC1-161 E | Adder | 4.0 MW | 3.4 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 927226 | AC1-216 E | Adder | 4.28 MW | 3.64 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 934392 | AD1-063 E | Adder | 0.49 MW | 0.42 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 935112 | AD1-144 E | Adder | 0.33 MW | 0.28 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 936582 | AD2-073 E | Adder | 0.42 MW | 0.35 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 936591 | AD2-074 C | Adder | 2.39 MW | 2.03 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 936592 | AD2-074 E | Adder | 3.9 MW | 3.31 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 942341 | AE2-247 C | Adder | 0.49 MW | 0.42 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 942342 | AE2-247 E | Adder | 0.68 MW | 0.58 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 943461 | AF1-017 C | Adder | 0.45 MW | 0.38 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 943462 | AF1-017 E | Adder | 0.73 MW | 0.62 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 943612 | AF1-032 E | Adder | 0.3 MW | 0.26 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 943741 | AF1-042 C | Adder | 1.25 MW | 1.06 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 943742 | AF1-042 E | Adder | 2.04 MW | 1.73 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944871 | AF1-152 C | Adder | 0.6 MW | 0.51 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 961951 | AG1-038 C | Adder | 1.38 MW | 1.17 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 961952 | AG1-038 E | Adder | 1.91 MW | 1.62 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 966661 | AG1-536 C | Adder | 2.29 MW | 1.95 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 966662 | AG1-536 E | Adder | 3.08 MW | 2.62 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315260 | 1GOSPORTA | Adder | 0.72 MW | 0.61 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315261 | 1GOSPORTB | Adder | 0.92 MW | 0.78 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315262 | 1GOSPORTC | Adder | 0.78 MW | 0.67 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316076 | AC2-137 E | Adder | 0.5 MW | 0.42 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316078 | AC2-138 E | Adder | 0.39 MW | 0.33 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316132 | AB2-190 C | 50/50 | 2.36 MW | 2.36 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316157 | AD2-030 E | Adder | 0.52 MW | 0.44 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 913392 | Y1-086 E | Adder | 0.7 MW | 0.59 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 916192 | Z1-068 E | Adder | 0.62 MW | 0.53 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 923832 | AB2-022 E | Adder | 0.39 MW | 0.33 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 923842 | AB2-024 E | Adder | 0.84 MW | 0.71 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 939312 | AE1-162 E | Adder | 0.6 MW | 0.51 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957492 | AF2-043 E | Adder | 0.46 MW | 0.39 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957601 | AF2-054 C | Adder | 0.93 MW | 0.79 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957602 | AF2-054 E | Adder | 0.62 MW | 0.53 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962531 | AG1-102 C | Adder | 0.46 MW | 0.39 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962532 | AG1-102 E | Adder | 0.97 MW | 0.82 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962861 | AG1-135 C | Adder | 2.59 MW | 2.2 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962862 | AG1-135 E | Adder | 1.73 MW | 1.47 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962962 | AG1-145 E | Adder | 0.64 MW | 0.55 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962971 | AG1-146 C | Adder | 1.33 MW | 1.13 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962972 | AG1-146 E | Adder | 0.89 MW | 0.75 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962981 | AG1-147 C | Adder | 3.11 MW | 2.64 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962982 | AG1-147 E | Adder | 2.07 MW | 1.76 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963611 | AG1-210 C | Adder | 0.28 MW | 0.23 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963612 | AG1-210 E | Adder | 0.41 MW | 0.35 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 964211 | AG1-282 C | Adder | 0.86 MW | 0.73 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 964212 | AG1-282 E | Adder | 0.57 MW | 0.49 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 901082 | W1-029 E | Adder | 9.97 MW | 8.47 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 917122 | Z2-027 E | Adder | 0.42 MW | 0.36 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 925332 | AB2-190 E | 50/50 | 4.82 MW | 4.82 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 925522 | AC1-027 E | Adder | 0.4 MW | 0.34 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941501 | AE2-147 C | Adder | 4.96 MW | 4.21 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941502 | AE2-147 E | Adder | 3.3 MW | 2.81 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957831 | AF2-077 C | Adder | 0.9 MW | 0.77 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957832 | AF2-077 E | Adder | 0.6 MW | 0.51 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957871 | AF2-081 C | Adder | 3.22 MW | 2.74 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957872 | AF2-081 E | Adder | 1.38 MW | 1.17 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 958161 | AF2-110 C | Adder | 0.44 MW | 0.38 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 958162 | AF2-110 E | Adder | 0.7 MW | 0.6 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 313811 | 6ELKO L286 | Adder | 0.52 MW | 0.44 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314181 | 3NORNECK | Adder | 0.37 MW | 0.31 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 933291 | AC2-141 C | Adder | 9.37 MW | 7.96 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 933292 | AC2-141 E | Adder | 4.0 MW | 3.4 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 934011 | AD1-025 C | Adder | 9.36 MW | 7.96 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 934012 | AD1-025 E | Adder | 5.54 MW | 4.71 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 313053 | 6PAPERMILL | Adder | 3.09 MW | 2.62 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314632 | 6AYDLETT TAP | Adder | 0.44 MW | 0.37 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316160 | AE1-175 E | Adder | 0.53 MW | 0.45 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316233 | AE1-074 C | Adder | -1.88 MW | -1.6 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316304 | AE2-227 C | Adder | -6.36 MW | -5.41 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 926785 | AC1-164_E | Adder | 9.62 MW | 8.18 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 934065 | AD1-033 E | Adder | 1.64 MW | 1.39 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 937226 | AE2-253 E | Adder | 1.89 MW | 1.61 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 939612 | AE1-191 E | Adder | 2.5 MW | 2.13 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963221 | AG1-171 C | Adder | 1.19 MW | 1.01 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963222 | AG1-171 E | Adder | 0.8 MW | 0.68 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963231 | AG1-172 C | Adder | 1.19 MW | 1.01 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963232 | AG1-172 E | Adder | 0.8 MW | 0.68 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963241 | AG1-173 C | Adder | 1.19 MW | 1.01 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963242 | AG1-173 E | Adder | 0.8 MW | 0.68 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963251 | AG1-174 C | Adder | 1.19 MW | 1.01 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963252 | AG1-174 E | Adder | 0.8 MW | 0.68 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316201 | AC1-065 C | Adder | 4.44 MW | 3.78 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 939246 | AE1-155 E | Adder | 3.71 MW | 3.15 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 919153 | AA1-139 E2 | Adder | 1.32 MW | 1.12 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 919152 | AA1-139 E1 | Adder | 1.32 MW | 1.12 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 924814 | AB2-134 E | Adder | 7.01 MW | 5.96 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316084 | AB2-161 E | Adder | 1.89 MW | 1.61 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 932046 | AC2-012 E | Adder | 4.44 MW | 3.78 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316311 | AC2-079 C | Adder | 1.89 MW | 1.6 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 932596 | AC2-079 E | Adder | 3.08 MW | 2.62 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 934146 | AD1-041 E | Adder | 1.57 MW | 1.33 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 934576 | AD1-082 E | Adder | 1.51 MW | 1.28 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316349 | AD2-085 C | Adder | 1.14 MW | 0.96 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 936666 | AD2-085 E | Adder | 1.85 MW | 1.57 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 961611 | AG1-000B C | Adder | 7.78 MW | 6.61 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941291 | AE2-123 C | Adder | 9.69 MW | 8.24 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941292 | AE2-123 E | Adder | 37.79 MW | 32.12 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941301 | AE2-124 C | Adder | 8.79 MW | 7.47 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941302 | AE2-124 E | Adder | 38.58 MW | 32.8 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941591 | AE2-156 C | Adder | 6.06 MW | 5.15 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 942551 | AE2-270 C | Adder | 14.89 MW | 12.66 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944581 | AF1-123 C | Adder | 15.38 MW | 13.07 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944582 | AF1-123 E | Adder | 35.21 MW | 29.93 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944591 | AF1-124 C | Adder | 15.38 MW | 13.07 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944592 | AF1-124 E | Adder | 35.21 MW | 29.93 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944601 | AF1-125 C | Adder | 15.38 MW | 13.07 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944602 | AF1-125 E | Adder | 35.21 MW | 29.93 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944631 | AF1-128 C | 50/50 | 49.15 MW | 49.15 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 945361 | AF1-201 C | Adder | 6.7 MW | 5.69 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 945362 | AF1-201 E | Adder | 4.47 MW | 3.8 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957711 | AF2-065 C | Adder | 7.6 MW | 6.46 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957712 | AF2-065 E | Adder | 7.3 MW | 6.2 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 958261 | AF2-120 C | Adder | 2.66 MW | 2.26 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 958262 | AF2-120 E | Adder | 1.78 MW | 1.51 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 961711 | AG1-011 C | Adder | 15.9 MW | 13.51 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 964951 | AG1-359 C | Adder | 7.45 MW | 6.33 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965001 | AG1-364 C | Adder | 2.42 MW | 2.06 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965002 | AG1-364 E | Adder | 3.64 MW | 3.09 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 966611 | AG1-531 C | Adder | 2.54 MW | 2.16 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 966612 | AG1-531 E | Adder | 1.69 MW | 1.44 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 935161 | AD1-151 C | 50/50 | 9.32 MW | 9.32 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 935162 | AD1-151 E | 50/50 | 6.21 MW | 6.21 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 938531 | AE1-072 C | Adder | 5.65 MW | 4.8 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 938532 | AE1-072 E | Adder | 2.94 MW | 2.5 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 939191 | AE1-149 C | Adder | 3.76 MW | 3.19 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 939192 | AE1-149 E | Adder | 2.5 MW | 2.13 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 939601 | AE1-190 C | Adder | 0.94 MW | 0.8 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 939602 | AE1-190 E | Adder | 0.63 MW | 0.53 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 940551 | AE2-041 C | Adder | 3.27 MW | 2.78 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 940651 | AE2-052 C | Adder | 1.25 MW | 1.06 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941101 | AE2-104 C | Adder | 1.08 MW | 0.92 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941102 | AE2-104 E | Adder | 1.72 MW | 1.46 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941281 | AE2-122 C | Adder | 9.43 MW | 8.02 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941282 | AE2-122 E | Adder | 38.06 MW | 32.35 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 943471 | AF1-018 C | Adder | 3.27 MW | 2.78 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 1.4 MW | 1.4 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 2.14 MW | 2.14 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 13.48 MW | 13.48 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 0.62 MW | 0.62 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | NY | PJM->LTFIMP_NY | CLTF | 0.3 MW | 0.3 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.07 MW | 0.07 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | WEC | LTFEXP_WEC->PJM | CLTF | 0.03 MW | 0.03 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CPLE | LTFEXP_CPLE->PJM | CLTF | 1.74 MW | 1.74 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | TVA | LTFEXP_TVA->PJM | CLTF | 0.65 MW | 0.65 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | MEC | LTFEXP_MEC->PJM | CLTF | 0.28 MW | 0.28 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | LAGN | LTFEXP_LAGN->PJM | CLTF | 0.84 MW | 0.84 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.02 MW | 0.02 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 3.95 MW | 3.95 MW |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.83 MW | 0.83 MW |
| Details for 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314309 | 6IRON208 | 50/50 | 0.97 MW | 0.97 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314507 | 3THOMPSN | Adder | 0.68 MW | 0.58 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314525 | 6KINGFORK | Adder | 0.36 MW | 0.3 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314550 | 6HICKORY | Adder | 0.71 MW | 0.6 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315060 | 1CHESTF5 | 50/50 | 78.52 MW | 78.52 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315061 | 1CHESTG7 | 50/50 | 4.04 MW | 4.04 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315062 | 1CHESTS7 | 50/50 | 1.86 MW | 1.86 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315063 | 1CHESTG8 | 50/50 | 3.98 MW | 3.98 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315064 | 1CHESTS8 | 50/50 | 2.05 MW | 2.05 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315073 | 1STONECA | Adder | 4.58 MW | 3.89 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315077 | 1HOPHCF1 | 50/50 | 1.36 MW | 1.36 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315078 | 1HOPHCF2 | 50/50 | 1.36 MW | 1.36 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315079 | 1HOPHCF3 | 50/50 | 1.36 MW | 1.36 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315080 | 1HOPHCF4 | 50/50 | 2.07 MW | 2.07 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315092 | 1YORKTN3 | Adder | 57.24 MW | 48.65 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 925865 | AC1-065 E | Adder | 7.32 MW | 6.22 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 926472 | AC1-118 E | Adder | 0.38 MW | 0.33 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 926662 | AC1-147 E | Adder | 0.45 MW | 0.38 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 926755 | AC1-161 E | Adder | 3.99 MW | 3.39 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 927226 | AC1-216 E | Adder | 4.28 MW | 3.64 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 934392 | AD1-063 E | Adder | 0.49 MW | 0.42 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 935112 | AD1-144 E | Adder | 0.33 MW | 0.28 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 936582 | AD2-073 E | Adder | 0.42 MW | 0.35 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 936591 | AD2-074 C | Adder | 2.39 MW | 2.03 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 936592 | AD2-074 E | Adder | 3.89 MW | 3.31 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 942152 | AE2-227 E | 50/50 | 3.76 MW | 3.76 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 942341 | AE2-247 C | Adder | 0.49 MW | 0.42 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 942342 | AE2-247 E | Adder | 0.68 MW | 0.58 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 943461 | AF1-017 C | Adder | 0.44 MW | 0.38 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 943462 | AF1-017 E | Adder | 0.73 MW | 0.62 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 943612 | AF1-032 E | Adder | 0.3 MW | 0.26 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 943741 | AF1-042 C | Adder | 1.25 MW | 1.06 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 943742 | AF1-042 E | Adder | 2.04 MW | 1.73 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944871 | AF1-152 C | Adder | 1.65 MW | 1.4 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944872 | AF1-152 E | Adder | 1.1 MW | 0.94 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 961951 | AG1-038 C | Adder | 1.38 MW | 1.17 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 961952 | AG1-038 E | Adder | 1.91 MW | 1.62 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 966661 | AG1-536 C | Adder | 2.29 MW | 1.95 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 966662 | AG1-536 E | Adder | 3.08 MW | 2.61 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315260 | 1GOSPORTA | Adder | 0.72 MW | 0.61 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315261 | 1GOSPORTB | Adder | 0.92 MW | 0.78 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315262 | 1GOSPORTC | Adder | 0.78 MW | 0.66 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316076 | AC2-137 E | Adder | 0.5 MW | 0.42 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316078 | AC2-138 E | Adder | 0.39 MW | 0.33 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316157 | AD2-030 E | Adder | 0.52 MW | 0.44 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 913392 | Y1-086 E | Adder | 0.7 MW | 0.59 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 916192 | Z1-068 E | Adder | 0.62 MW | 0.53 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 923832 | AB2-022 E | Adder | 0.39 MW | 0.33 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 923842 | AB2-024 E | Adder | 0.84 MW | 0.71 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 939312 | AE1-162 E | Adder | 0.6 MW | 0.51 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957492 | AF2-043 E | Adder | 0.46 MW | 0.39 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957601 | AF2-054 C | Adder | 0.93 MW | 0.79 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957602 | AF2-054 E | Adder | 0.62 MW | 0.53 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962531 | AG1-102 C | Adder | 0.46 MW | 0.39 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962532 | AG1-102 E | Adder | 0.96 MW | 0.82 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962861 | AG1-135 C | Adder | 2.59 MW | 2.2 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962862 | AG1-135 E | Adder | 1.72 MW | 1.47 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962962 | AG1-145 E | Adder | 0.64 MW | 0.55 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962971 | AG1-146 C | Adder | 1.33 MW | 1.13 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962972 | AG1-146 E | Adder | 0.89 MW | 0.75 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962981 | AG1-147 C | Adder | 3.1 MW | 2.64 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962982 | AG1-147 E | Adder | 2.07 MW | 1.76 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963611 | AG1-210 C | Adder | 0.28 MW | 0.23 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963612 | AG1-210 E | Adder | 0.41 MW | 0.35 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 964211 | AG1-282 C | Adder | 0.86 MW | 0.73 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 964212 | AG1-282 E | Adder | 0.57 MW | 0.49 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 901082 | W1-029 E | Adder | 9.95 MW | 8.46 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 917122 | Z2-027 E | Adder | 0.42 MW | 0.36 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 925332 | AB2-190 E | Adder | 4.82 MW | 4.1 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 925522 | AC1-027 E | Adder | 0.4 MW | 0.34 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941501 | AE2-147 C | Adder | 4.95 MW | 4.21 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941502 | AE2-147 E | Adder | 3.3 MW | 2.81 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957831 | AF2-077 C | Adder | 0.9 MW | 0.77 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957832 | AF2-077 E | Adder | 0.6 MW | 0.51 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957871 | AF2-081 C | Adder | 3.22 MW | 2.73 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957872 | AF2-081 E | Adder | 1.38 MW | 1.17 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 958161 | AF2-110 C | Adder | 0.44 MW | 0.37 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 958162 | AF2-110 E | Adder | 0.7 MW | 0.59 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 313811 | 6ELKO L286 | Adder | 0.52 MW | 0.44 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314181 | 3NORNECK | Adder | 0.37 MW | 0.31 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 933291 | AC2-141 C | Adder | 9.36 MW | 7.95 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 933292 | AC2-141 E | Adder | 3.99 MW | 3.39 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 934011 | AD1-025 C | Adder | 9.35 MW | 7.95 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 934012 | AD1-025 E | Adder | 5.54 MW | 4.71 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 313053 | 6PAPERMILL | Adder | 3.08 MW | 2.62 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314632 | 6AYDLETT TAP | Adder | 0.44 MW | 0.37 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316160 | AE1-175 E | Adder | 0.53 MW | 0.45 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316233 | AE1-074 C | Adder | -1.88 MW | -1.6 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316304 | AE2-227 C | 50/50 | 5.64 MW | 5.64 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 926785 | AC1-164_E | Adder | 9.61 MW | 8.17 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 934065 | AD1-033 E | Adder | 1.64 MW | 1.39 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 937226 | AE2-253 E | Adder | 1.89 MW | 1.6 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 939612 | AE1-191 E | Adder | 2.5 MW | 2.13 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963221 | AG1-171 C | Adder | 1.19 MW | 1.01 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963222 | AG1-171 E | Adder | 0.79 MW | 0.68 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963231 | AG1-172 C | Adder | 1.19 MW | 1.01 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963232 | AG1-172 E | Adder | 0.79 MW | 0.68 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963241 | AG1-173 C | Adder | 1.19 MW | 1.01 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963242 | AG1-173 E | Adder | 0.79 MW | 0.68 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963251 | AG1-174 C | Adder | 1.19 MW | 1.01 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963252 | AG1-174 E | Adder | 0.79 MW | 0.68 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316201 | AC1-065 C | Adder | 4.44 MW | 3.77 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 939246 | AE1-155 E | Adder | 3.7 MW | 3.15 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 919153 | AA1-139 E2 | Adder | 1.32 MW | 1.12 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 919152 | AA1-139 E1 | Adder | 1.32 MW | 1.12 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 924814 | AB2-134 E | Adder | 7.01 MW | 5.96 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316084 | AB2-161 E | Adder | 1.89 MW | 1.6 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 932046 | AC2-012 E | Adder | 4.44 MW | 3.77 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316311 | AC2-079 C | Adder | 1.88 MW | 1.6 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 932596 | AC2-079 E | Adder | 3.07 MW | 2.61 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 934146 | AD1-041 E | Adder | 1.56 MW | 1.33 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 934576 | AD1-082 E | Adder | 1.5 MW | 1.28 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316349 | AD2-085 C | Adder | 1.13 MW | 0.96 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 936666 | AD2-085 E | Adder | 1.85 MW | 1.57 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 961611 | AG1-000B C | Adder | 7.77 MW | 6.6 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941291 | AE2-123 C | Adder | 9.68 MW | 8.23 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941292 | AE2-123 E | Adder | 37.74 MW | 32.08 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941301 | AE2-124 C | Adder | 8.78 MW | 7.46 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941302 | AE2-124 E | Adder | 38.53 MW | 32.75 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941591 | AE2-156 C | Adder | 6.05 MW | 5.14 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 942551 | AE2-270 C | Adder | 14.88 MW | 12.65 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944581 | AF1-123 C | Adder | 15.36 MW | 13.05 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944582 | AF1-123 E | Adder | 35.16 MW | 29.89 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944591 | AF1-124 C | Adder | 15.36 MW | 13.05 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944592 | AF1-124 E | Adder | 35.16 MW | 29.89 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944601 | AF1-125 C | Adder | 15.36 MW | 13.05 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944602 | AF1-125 E | Adder | 35.16 MW | 29.89 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944631 | AF1-128 C | 50/50 | 49.13 MW | 49.13 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 945361 | AF1-201 C | Adder | 6.69 MW | 5.69 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 945362 | AF1-201 E | Adder | 4.46 MW | 3.79 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957711 | AF2-065 C | Adder | 7.59 MW | 6.45 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957712 | AF2-065 E | Adder | 7.29 MW | 6.2 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 958261 | AF2-120 C | Adder | 2.66 MW | 2.26 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 958262 | AF2-120 E | Adder | 1.77 MW | 1.51 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 961711 | AG1-011 C | Adder | 15.88 MW | 13.5 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962271 | AG1-075 C | Adder | 1.68 MW | 1.43 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 964951 | AG1-359 C | Adder | 7.44 MW | 6.32 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965001 | AG1-364 C | Adder | 2.42 MW | 2.06 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965002 | AG1-364 E | Adder | 3.63 MW | 3.09 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 966611 | AG1-531 C | Adder | 2.54 MW | 2.16 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 966612 | AG1-531 E | Adder | 1.69 MW | 1.44 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 935161 | AD1-151 C | Adder | 9.31 MW | 7.92 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 935162 | AD1-151 E | Adder | 6.21 MW | 5.28 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 938531 | AE1-072 C | Adder | 5.64 MW | 4.79 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 938532 | AE1-072 E | Adder | 2.94 MW | 2.5 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 939191 | AE1-149 C | Adder | 3.75 MW | 3.19 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 939192 | AE1-149 E | Adder | 2.5 MW | 2.12 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 939601 | AE1-190 C | Adder | 0.94 MW | 0.8 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 939602 | AE1-190 E | Adder | 0.63 MW | 0.53 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 940551 | AE2-041 C | Adder | 3.26 MW | 2.77 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 940651 | AE2-052 C | Adder | 1.25 MW | 1.06 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941101 | AE2-104 C | Adder | 1.08 MW | 0.92 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941102 | AE2-104 E | Adder | 1.71 MW | 1.46 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941281 | AE2-122 C | Adder | 9.42 MW | 8.01 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941282 | AE2-122 E | Adder | 38.0 MW | 32.3 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 943471 | AF1-018 C | Adder | 3.26 MW | 2.77 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 1.26 MW | 1.26 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 2.09 MW | 2.09 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 13.4 MW | 13.4 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 0.63 MW | 0.63 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | NY | PJM->LTFIMP_NY | CLTF | 0.31 MW | 0.31 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.06 MW | 0.06 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | WEC | LTFEXP_WEC->PJM | CLTF | 0.03 MW | 0.03 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CPLE | LTFEXP_CPLE->PJM | CLTF | 1.74 MW | 1.74 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | TVA | LTFEXP_TVA->PJM | CLTF | 0.64 MW | 0.64 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | MEC | LTFEXP_MEC->PJM | CLTF | 0.27 MW | 0.27 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | LAGN | LTFEXP_LAGN->PJM | CLTF | 0.83 MW | 0.83 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.01 MW | 0.01 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 4.0 MW | 4.0 MW |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.83 MW | 0.83 MW |
| Details for 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 964801 | AG1-343 C | Adder | 2.24 MW | 1.9 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 964802 | AG1-343 E | Adder | 1.76 MW | 1.49 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965291 | AG1-394 C | Adder | 0.77 MW | 0.65 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965292 | AG1-394 E | Adder | 0.51 MW | 0.43 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314541 | 3WATKINS | Adder | 0.28 MW | 0.24 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 920042 | AA2-088 E OP | Adder | 4.02 MW | 3.42 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934521 | AD1-076 C | Adder | 5.16 MW | 4.38 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934522 | AD1-076 E | Adder | 2.63 MW | 2.23 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 900672 | V4-068 E | Adder | 0.13 MW | 0.11 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 940492 | AE2-034 E | Adder | 1.36 MW | 1.16 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957521 | AF2-046 C | Adder | 6.32 MW | 5.37 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957522 | AF2-046 E | Adder | 3.18 MW | 2.7 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957531 | AF2-047 C | Adder | 7.54 MW | 6.41 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957532 | AF2-047 E | Adder | 3.79 MW | 3.22 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314539 | 3UNCAMP | Adder | 2.57 MW | 2.18 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 916042 | Z1-036 E | Adder | 13.59 MW | 11.55 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 938771 | AE1-103 C | Adder | 1.26 MW | 1.07 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 938772 | AE1-103 E | Adder | 1.74 MW | 1.48 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314421 | 6WINCHST | 50/50 | 0.1 MW | 0.1 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314507 | 3THOMPSN | Adder | 1.04 MW | 0.88 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314525 | 6KINGFORK | Adder | 0.55 MW | 0.47 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314550 | 6HICKORY | Adder | 1.12 MW | 0.95 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315092 | 1YORKTN3 | 50/50 | 139.18 MW | 139.18 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 926662 | AC1-147 E | Adder | 0.68 MW | 0.58 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 926755 | AC1-161 E | 50/50 | 7.36 MW | 7.36 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 935112 | AD1-144 E | Adder | 0.51 MW | 0.43 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 936591 | AD2-074 C | Adder | -4.75 MW | -4.04 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 942341 | AE2-247 C | Adder | 0.58 MW | 0.5 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 942342 | AE2-247 E | Adder | 0.81 MW | 0.69 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 943461 | AF1-017 C | Adder | 0.53 MW | 0.45 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 943462 | AF1-017 E | Adder | 0.86 MW | 0.73 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 943612 | AF1-032 E | Adder | 0.47 MW | 0.4 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 943741 | AF1-042 C | Adder | -2.49 MW | -2.12 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944871 | AF1-152 C | Adder | 2.6 MW | 2.21 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944872 | AF1-152 E | Adder | 1.73 MW | 1.47 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315233 | 1SURRY 2 | 50/50 | 13.85 MW | 13.85 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315260 | 1GOSPORTA | Adder | 1.09 MW | 0.93 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315261 | 1GOSPORTB | Adder | 1.4 MW | 1.19 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315262 | 1GOSPORTC | Adder | 1.18 MW | 1.01 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315611 | 6Z1-036WIND | Adder | 3.22 MW | 2.74 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 913392 | Y1-086 E | Adder | 1.1 MW | 0.93 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 916192 | Z1-068 E | Adder | 0.97 MW | 0.82 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 923832 | AB2-022 E | Adder | 0.62 MW | 0.53 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 939312 | AE1-162 E | Adder | 0.68 MW | 0.58 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957492 | AF2-043 E | Adder | 0.73 MW | 0.62 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 962962 | AG1-145 E | 50/50 | 0.91 MW | 0.91 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 901082 | W1-029 E | Adder | 15.66 MW | 13.31 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 917122 | Z2-027 E | Adder | 0.67 MW | 0.57 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 925522 | AC1-027 E | Adder | 0.63 MW | 0.53 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941501 | AE2-147 C | Adder | 7.78 MW | 6.62 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941502 | AE2-147 E | Adder | 5.19 MW | 4.41 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957871 | AF2-081 C | Adder | 5.09 MW | 4.32 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957872 | AF2-081 E | Adder | 2.18 MW | 1.85 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 958161 | AF2-110 C | Adder | 0.65 MW | 0.55 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 958162 | AF2-110 E | Adder | 1.03 MW | 0.87 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 933291 | AC2-141 C | 50/50 | 17.24 MW | 17.24 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 933292 | AC2-141 E | 50/50 | 7.36 MW | 7.36 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 939411 | AE1-173 C | Adder | 34.53 MW | 29.35 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 939412 | AE1-173 E | Adder | 23.02 MW | 19.57 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 933981 | AD1-022 C | Adder | 3.61 MW | 3.07 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 933982 | AD1-022 E | Adder | 1.97 MW | 1.67 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 961681 | AG1-008 C | Adder | 6.33 MW | 5.38 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 961682 | AG1-008 E | Adder | 2.99 MW | 2.54 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314594 | 6PLYMOUTH TP | Adder | 0.14 MW | 0.12 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314632 | 6AYDLETT TAP | Adder | 0.69 MW | 0.58 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 316159 | AE1-175 C | 50/50 | 0.21 MW | 0.21 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 316160 | AE1-175 E | 50/50 | 0.75 MW | 0.75 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 316294 | AC1-161 C | 50/50 | 2.38 MW | 2.38 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 316382 | AG1-145 C | 50/50 | 0.19 MW | 0.19 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934065 | AD1-033 E | Adder | 2.58 MW | 2.2 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 937226 | AE2-253 E | Adder | 2.98 MW | 2.54 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 918512 | AA1-065 E OP | Adder | 2.14 MW | 1.82 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 919153 | AA1-139 E2 | Adder | 2.08 MW | 1.77 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 919152 | AA1-139 E1 | Adder | 2.08 MW | 1.77 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 920692 | AA2-178 E | Adder | 1.81 MW | 1.54 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 932046 | AC2-012 E | Adder | 6.72 MW | 5.71 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 316311 | AC2-079 C | Adder | 2.3 MW | 1.96 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 932596 | AC2-079 E | Adder | 3.76 MW | 3.19 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 316349 | AD2-085 C | Adder | 1.35 MW | 1.15 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 936666 | AD2-085 E | Adder | 2.2 MW | 1.87 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 961611 | AG1-000B C | Adder | 6.39 MW | 5.43 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941291 | AE2-123 C | Adder | 15.04 MW | 12.79 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941292 | AE2-123 E | Adder | 58.66 MW | 49.86 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941301 | AE2-124 C | Adder | 13.68 MW | 11.63 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941302 | AE2-124 E | Adder | 60.04 MW | 51.04 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941591 | AE2-156 C | Adder | 9.2 MW | 7.82 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944581 | AF1-123 C | Adder | 25.12 MW | 21.36 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944582 | AF1-123 E | Adder | 57.53 MW | 48.9 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944591 | AF1-124 C | Adder | 25.12 MW | 21.36 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944592 | AF1-124 E | Adder | 57.53 MW | 48.9 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944601 | AF1-125 C | Adder | 25.12 MW | 21.36 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944602 | AF1-125 E | Adder | 57.53 MW | 48.9 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 945361 | AF1-201 C | Adder | 7.52 MW | 6.39 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 945362 | AF1-201 E | Adder | 5.02 MW | 4.26 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 964951 | AG1-359 C | Adder | 11.77 MW | 10.01 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965001 | AG1-364 C | Adder | 3.68 MW | 3.13 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965002 | AG1-364 E | Adder | 5.52 MW | 4.69 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965691 | AG1-437 C | Adder | 4.11 MW | 3.49 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965692 | AG1-437 E | Adder | 2.74 MW | 2.33 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965701 | AG1-438 C | Adder | 4.11 MW | 3.49 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965702 | AG1-438 E | Adder | 2.74 MW | 2.33 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965741 | AG1-442 C | Adder | 2.4 MW | 2.04 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965751 | AG1-443 C | Adder | 2.4 MW | 2.04 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 966611 | AG1-531 C | 50/50 | 4.09 MW | 4.09 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 966612 | AG1-531 E | 50/50 | 2.73 MW | 2.73 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934501 | AD1-074 C | Adder | 14.2 MW | 12.07 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934502 | AD1-074 E | Adder | 7.23 MW | 6.14 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934511 | AD1-075 C | Adder | 3.55 MW | 3.02 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934512 | AD1-075 E | Adder | 1.81 MW | 1.54 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 938531 | AE1-072 C | Adder | 8.91 MW | 7.58 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 938532 | AE1-072 E | Adder | 4.65 MW | 3.95 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 939601 | AE1-190 C | Adder | -1.6 MW | -1.36 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 940641 | AE2-051 C | Adder | 5.83 MW | 4.96 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 940642 | AE2-051 E | Adder | 3.89 MW | 3.3 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941101 | AE2-104 C | Adder | 1.58 MW | 1.34 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941102 | AE2-104 E | Adder | 2.52 MW | 2.14 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941281 | AE2-122 C | Adder | 14.64 MW | 12.44 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941282 | AE2-122 E | Adder | 59.07 MW | 50.21 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 7.31 MW | 7.31 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 5.39 MW | 5.39 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 24.17 MW | 24.17 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 0.85 MW | 0.85 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | NY | PJM->LTFIMP_NY | CLTF | 0.4 MW | 0.4 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.29 MW | 0.29 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | WEC | LTFEXP_WEC->PJM | CLTF | 0.15 MW | 0.15 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | CPLE | LTFEXP_CPLE->PJM | CLTF | 2.98 MW | 2.98 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | TVA | LTFEXP_TVA->PJM | CLTF | 1.47 MW | 1.47 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | MEC | LTFEXP_MEC->PJM | CLTF | 0.93 MW | 0.93 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | LAGN | LTFEXP_LAGN->PJM | CLTF | 1.87 MW | 1.87 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.06 MW | 0.06 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 5.41 MW | 5.41 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.42 MW | 1.42 MW |
| Details for 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 963041 | AG1-153 C | 50/50 | 3.73 MW | 3.73 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 963042 | AG1-153 E | 50/50 | 5.59 MW | 5.59 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 963111 | AG1-160 C | 50/50 | 3.8 MW | 3.8 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 963112 | AG1-160 E | 50/50 | 5.7 MW | 5.7 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 966361 | AG1-505 C | 50/50 | 10.75 MW | 10.75 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 966362 | AG1-505 E | 50/50 | 7.17 MW | 7.17 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 966371 | AG1-506 C | 50/50 | 10.75 MW | 10.75 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 966372 | AG1-506 E | 50/50 | 7.17 MW | 7.17 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 942931 | AE2-313 C | 50/50 | 24.37 MW | 24.37 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 942932 | AE2-313 E | 50/50 | 16.25 MW | 16.25 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 944011 | AF1-069 C | 50/50 | 8.95 MW | 8.95 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 944012 | AF1-069 E | 50/50 | 3.48 MW | 3.48 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 923263 | AB1-132 E OP | Adder | 2.57 MW | 2.19 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 941031 | AE2-094 C | 50/50 | 27.4 MW | 27.4 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 941032 | AE2-094 E | 50/50 | 12.27 MW | 12.27 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 957481 | AF2-042 C | 50/50 | 30.0 MW | 30.0 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 957482 | AF2-042 E | 50/50 | 20.0 MW | 20.0 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 314550 | 6HICKORY | Adder | 0.89 MW | 0.76 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 926755 | AC1-161 E | Adder | 5.67 MW | 4.82 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 315102 | 1BRUNSWICKG1 | 50/50 | 4.64 MW | 4.64 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 315103 | 1BRUNSWICKG2 | 50/50 | 4.64 MW | 4.64 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 315104 | 1BRUNSWICKG3 | 50/50 | 4.64 MW | 4.64 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 315105 | 1BRUNSWICKS1 | 50/50 | 9.65 MW | 9.65 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 315241 | 1Z1-086 GT1 | 50/50 | 5.99 MW | 5.99 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 315242 | 1Z1-086 GT2 | 50/50 | 5.99 MW | 5.99 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 315243 | 1Z1-086 GT3 | 50/50 | 5.99 MW | 5.99 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 315244 | 1Z1-086 ST | 50/50 | 10.43 MW | 10.43 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 913392 | Y1-086 E | Adder | 0.89 MW | 0.76 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 916192 | Z1-068 E | Adder | 0.75 MW | 0.64 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 923832 | AB2-022 E | Adder | 0.5 MW | 0.43 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 923852 | AB2-025 E | Adder | 0.5 MW | 0.42 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 901082 | W1-029 E | Adder | 4.38 MW | 3.73 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 917122 | Z2-027 E | Adder | 0.55 MW | 0.46 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 925522 | AC1-027 E | Adder | 0.49 MW | 0.41 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 957871 | AF2-081 C | Adder | 4.07 MW | 3.46 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 957872 | AF2-081 E | Adder | 1.75 MW | 1.48 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 926071 | AC1-086 C | Adder | 8.84 MW | 7.51 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 926072 | AC1-086 E | Adder | 4.02 MW | 3.42 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 933291 | AC2-141 C | Adder | 13.27 MW | 11.28 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 933292 | AC2-141 E | Adder | 5.67 MW | 4.82 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 939411 | AE1-173 C | 50/50 | 55.1 MW | 55.1 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 939412 | AE1-173 E | 50/50 | 36.73 MW | 36.73 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 962572 | AG1-106 E | Adder | 1.12 MW | 0.95 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 962571 | AG1-106 C | Adder | 2.46 MW | 2.09 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 314632 | 6AYDLETT TAP | Adder | 0.55 MW | 0.47 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 316233 | AE1-074 C | Adder | -3.05 MW | -2.59 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 316336 | AC2-165 C | Adder | -11.14 MW | -9.47 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 924516 | AB2-100 E1 | Adder | 1.22 MW | 1.04 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 924517 | AB2-100 E2 | Adder | 1.22 MW | 1.04 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 934065 | AD1-033 E | Adder | 2.04 MW | 1.74 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 937226 | AE2-253 E | Adder | 2.38 MW | 2.02 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 919153 | AA1-139 E2 | Adder | 1.67 MW | 1.42 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 919152 | AA1-139 E1 | Adder | 1.67 MW | 1.42 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 941291 | AE2-123 C | Adder | 11.74 MW | 9.98 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 941292 | AE2-123 E | Adder | 45.8 MW | 38.93 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 941301 | AE2-124 C | Adder | 10.7 MW | 9.1 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 941302 | AE2-124 E | Adder | 46.96 MW | 39.92 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 944581 | AF1-123 C | Adder | 20.22 MW | 17.19 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 944582 | AF1-123 E | Adder | 46.3 MW | 39.35 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 944591 | AF1-124 C | Adder | 20.22 MW | 17.19 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 944592 | AF1-124 E | Adder | 46.3 MW | 39.35 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 944601 | AF1-125 C | Adder | 20.22 MW | 17.19 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 944602 | AF1-125 E | Adder | 46.3 MW | 39.35 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 946011 | AF1-266 C | Adder | 5.82 MW | 4.95 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 963291 | AG1-178 C | 50/50 | 42.3 MW | 42.3 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 963351 | AG1-184 C | 50/50 | 22.79 MW | 22.79 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 964951 | AG1-359 C | Adder | 9.32 MW | 7.92 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 965811 | AG1-449 C | 50/50 | 15.78 MW | 15.78 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 934612 | AD1-087 E | Adder | 1.9 MW | 1.61 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 935172 | AD1-152 E | Adder | 2.74 MW | 2.33 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 937482 | AD2-202 E | Adder | 0.56 MW | 0.47 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 938531 | AE1-072 C | Adder | 7.16 MW | 6.09 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 938532 | AE1-072 E | Adder | 3.73 MW | 3.17 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 940481 | AE2-033 C | Adder | 6.96 MW | 5.92 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 940482 | AE2-033 E | Adder | 4.69 MW | 3.99 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 940541 | AE2-040 C | Adder | 1.24 MW | 1.05 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 940641 | AE2-051 C | 50/50 | 11.56 MW | 11.56 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 940642 | AE2-051 E | 50/50 | 7.71 MW | 7.71 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 941281 | AE2-122 C | Adder | 11.43 MW | 9.71 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 941282 | AE2-122 E | Adder | 46.11 MW | 39.2 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 945811 | AF1-246 C | 50/50 | 4.2 MW | 4.2 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | 945812 | AF1-246 E | 50/50 | 5.8 MW | 5.8 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 14.42 MW | 14.42 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 10.32 MW | 10.32 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 45.7 MW | 45.7 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 1.21 MW | 1.21 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | NY | PJM->LTFIMP_NY | CLTF | 0.56 MW | 0.56 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.56 MW | 0.56 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | WEC | LTFEXP_WEC->PJM | CLTF | 0.3 MW | 0.3 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | CPLE | LTFEXP_CPLE->PJM | CLTF | 5.54 MW | 5.54 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | TVA | LTFEXP_TVA->PJM | CLTF | 2.79 MW | 2.79 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | MEC | LTFEXP_MEC->PJM | CLTF | 1.81 MW | 1.81 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | LAGN | LTFEXP_LAGN->PJM | CLTF | 3.57 MW | 3.57 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.11 MW | 0.11 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 7.72 MW | 7.72 MW |
| 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.64 MW | 2.64 MW |
| Details for AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 916042 | Z1-036 E | Adder | 10.42 MW | 8.86 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 314507 | 3THOMPSN | Adder | 1.03 MW | 0.88 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 314525 | 6KINGFORK | Adder | 0.57 MW | 0.48 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 314550 | 6HICKORY | Adder | 0.93 MW | 0.79 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 315092 | 1YORKTN3 | Adder | 51.3 MW | 43.6 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 926662 | AC1-147 E | Adder | 0.68 MW | 0.58 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 927226 | AC1-216 E | 50/50 | 10.86 MW | 10.86 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 935112 | AD1-144 E | Adder | 0.53 MW | 0.45 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 943612 | AF1-032 E | Adder | 0.38 MW | 0.32 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 944871 | AF1-152 C | Adder | 2.04 MW | 1.74 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 944872 | AF1-152 E | Adder | 1.36 MW | 1.16 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 315116 | 1SURRY 1 | 50/50 | 29.35 MW | 29.35 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 315117 | 1GRAVELC | 50/50 | 1.02 MW | 1.02 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 315119 | 1GRAVEL3 | 50/50 | 2.98 MW | 2.98 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 315120 | 1GRAVEL4 | 50/50 | 3.02 MW | 3.02 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 315121 | 1GRAVEL5 | 50/50 | 2.98 MW | 2.98 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 315122 | 1GRAVEL6 | 50/50 | 3.02 MW | 3.02 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 315260 | 1GOSPORTA | Adder | 1.09 MW | 0.93 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 315261 | 1GOSPORTB | Adder | 1.39 MW | 1.18 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 315262 | 1GOSPORTC | Adder | 1.18 MW | 1.0 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 315611 | 6Z1-036WIND | Adder | 2.47 MW | 2.1 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 913392 | Y1-086 E | Adder | 0.88 MW | 0.75 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 916192 | Z1-068 E | Adder | 0.88 MW | 0.74 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 923832 | AB2-022 E | Adder | 0.5 MW | 0.42 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 939312 | AE1-162 E | 50/50 | 1.52 MW | 1.52 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 957492 | AF2-043 E | Adder | 0.58 MW | 0.5 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 901082 | W1-029 E | Adder | 12.33 MW | 10.48 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 917122 | Z2-027 E | Adder | 0.53 MW | 0.45 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 925522 | AC1-027 E | Adder | 0.57 MW | 0.49 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 941501 | AE2-147 C | Adder | 6.13 MW | 5.21 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 941502 | AE2-147 E | Adder | 4.09 MW | 3.47 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 957871 | AF2-081 C | Adder | 4.17 MW | 3.54 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 957872 | AF2-081 E | Adder | 1.79 MW | 1.52 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 958161 | AF2-110 C | Adder | 0.46 MW | 0.39 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 958162 | AF2-110 E | Adder | 0.74 MW | 0.63 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 934011 | AD1-025 C | 50/50 | 23.73 MW | 23.73 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 934012 | AD1-025 E | 50/50 | 14.06 MW | 14.06 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 314632 | 6AYDLETT TAP | Adder | 0.56 MW | 0.48 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 316236 | AE1-162 C | 50/50 | 0.32 MW | 0.32 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 316240 | AF1-291 C | Adder | -0.81 MW | -0.69 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 316301 | AE2-228 C | Adder | -0.79 MW | -0.67 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 316369 | AC1-216 C | 50/50 | 1.9 MW | 1.9 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 934065 | AD1-033 E | Adder | 2.17 MW | 1.84 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 937226 | AE2-253 E | Adder | 2.46 MW | 2.09 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 963221 | AG1-171 C | 50/50 | 3.02 MW | 3.02 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 963222 | AG1-171 E | 50/50 | 2.02 MW | 2.02 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 963231 | AG1-172 C | 50/50 | 3.02 MW | 3.02 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 963232 | AG1-172 E | 50/50 | 2.02 MW | 2.02 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 963241 | AG1-173 C | 50/50 | 3.02 MW | 3.02 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 963242 | AG1-173 E | 50/50 | 2.02 MW | 2.02 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 963251 | AG1-174 C | 50/50 | 3.02 MW | 3.02 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 963252 | AG1-174 E | 50/50 | 2.02 MW | 2.02 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 919153 | AA1-139 E2 | Adder | 1.71 MW | 1.45 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 919152 | AA1-139 E1 | Adder | 1.71 MW | 1.45 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 316033 | AB2-134 GEN | 50/50 | 2.5 MW | 2.5 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 924814 | AB2-134 E | 50/50 | 17.79 MW | 17.79 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 932046 | AC2-012 E | Adder | 6.7 MW | 5.7 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 961611 | AG1-000B C | 50/50 | 28.64 MW | 28.64 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 941291 | AE2-123 C | Adder | 13.52 MW | 11.49 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 941292 | AE2-123 E | Adder | 52.71 MW | 44.8 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 941301 | AE2-124 C | Adder | 12.16 MW | 10.34 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 941302 | AE2-124 E | Adder | 53.35 MW | 45.35 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 941591 | AE2-156 C | Adder | 9.07 MW | 7.71 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 942551 | AE2-270 C | 50/50 | 77.59 MW | 77.59 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 944581 | AF1-123 C | Adder | 18.22 MW | 15.49 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 944582 | AF1-123 E | Adder | 41.72 MW | 35.46 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 944591 | AF1-124 C | Adder | 18.22 MW | 15.49 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 944592 | AF1-124 E | Adder | 41.72 MW | 35.46 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 944601 | AF1-125 C | Adder | 18.22 MW | 15.49 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 944602 | AF1-125 E | Adder | 41.72 MW | 35.46 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 957711 | AF2-065 C | 50/50 | 39.57 MW | 39.57 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 957712 | AF2-065 E | 50/50 | 38.02 MW | 38.02 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 961711 | AG1-011 C | 50/50 | 40.31 MW | 40.31 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 964951 | AG1-359 C | Adder | 9.77 MW | 8.3 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 965001 | AG1-364 C | Adder | 3.63 MW | 3.09 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 965002 | AG1-364 E | Adder | 5.45 MW | 4.63 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 966611 | AG1-531 C | 50/50 | 5.39 MW | 5.39 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 966612 | AG1-531 E | 50/50 | 3.6 MW | 3.6 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 935161 | AD1-151 C | 50/50 | 22.68 MW | 22.68 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 935162 | AD1-151 E | 50/50 | 15.12 MW | 15.12 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 938531 | AE1-072 C | Adder | 7.28 MW | 6.19 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 938532 | AE1-072 E | Adder | 3.8 MW | 3.23 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 941101 | AE2-104 C | Adder | 1.13 MW | 0.96 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 941102 | AE2-104 E | Adder | 1.8 MW | 1.53 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 941281 | AE2-122 C | Adder | 13.15 MW | 11.18 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 941282 | AE2-122 E | Adder | 53.07 MW | 45.11 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 0.73 MW | 0.73 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 1.22 MW | 1.22 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 7.81 MW | 7.81 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 0.4 MW | 0.4 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | NY | PJM->LTFIMP_NY | CLTF | 0.2 MW | 0.2 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.04 MW | 0.04 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | WEC | LTFEXP_WEC->PJM | CLTF | 0.02 MW | 0.02 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | CPLE | LTFEXP_CPLE->PJM | CLTF | 1.03 MW | 1.03 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | TVA | LTFEXP_TVA->PJM | CLTF | 0.37 MW | 0.37 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | MEC | LTFEXP_MEC->PJM | CLTF | 0.16 MW | 0.16 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | LAGN | LTFEXP_LAGN->PJM | CLTF | 0.48 MW | 0.48 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.01 MW | 0.01 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 2.56 MW | 2.56 MW |
| AE2-270 TP-AB2-190 TAP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.49 MW | 0.49 MW |
| Details for 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 314229 | 6MT RD221 | 50/50 | 0.12 MW | 0.12 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 314236 | 6NRTHEST | 50/50 | 0.15 MW | 0.15 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 314250 | 6ROCKVILLE | 50/50 | 1.95 MW | 1.95 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 314314 | 3LOCKS | Adder | 1.41 MW | 1.2 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 314331 | 6POE | Adder | 0.95 MW | 0.81 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 314507 | 3THOMPSN | Adder | 1.25 MW | 1.07 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 314525 | 6KINGFORK | Adder | 0.64 MW | 0.55 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 315060 | 1CHESTF5 | Adder | 53.18 MW | 45.2 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 315065 | 1CHESTF6 | Adder | 16.3 MW | 13.86 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 315067 | 1DARBY 1 | 50/50 | 2.08 MW | 2.08 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 315068 | 1DARBY 2 | 50/50 | 2.08 MW | 2.08 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 315069 | 1DARBY 3 | 50/50 | 2.08 MW | 2.08 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 315070 | 1DARBY 4 | 50/50 | 2.09 MW | 2.09 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 315073 | 1STONECA | Adder | 5.53 MW | 4.7 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 315083 | 1SPRUNCA | Adder | 7.67 MW | 6.52 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 315084 | 1SPRUNCB | Adder | 7.67 MW | 6.52 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 315092 | 1YORKTN3 | Adder | 96.9 MW | 82.36 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 925865 | AC1-065 E | Adder | 12.42 MW | 10.56 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 926412 | AC1-112 E | 50/50 | 1.14 MW | 1.14 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 926662 | AC1-147 E | Adder | 0.82 MW | 0.7 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 927226 | AC1-216 E | Adder | 5.75 MW | 4.88 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 934392 | AD1-063 E | Adder | 0.8 MW | 0.68 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 934781 | AD1-105 C | Adder | 7.08 MW | 6.01 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 934782 | AD1-105 E | Adder | 4.72 MW | 4.01 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 935112 | AD1-144 E | Adder | 0.6 MW | 0.51 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 936591 | AD2-074 C | Adder | 3.99 MW | 3.39 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 936592 | AD2-074 E | Adder | 6.5 MW | 5.53 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 942152 | AE2-227 E | Adder | 1.29 MW | 1.09 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 942162 | AE2-228 E | Adder | 1.17 MW | 0.99 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 942341 | AE2-247 C | Adder | 0.96 MW | 0.82 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 942342 | AE2-247 E | Adder | 1.33 MW | 1.13 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 943461 | AF1-017 C | Adder | 0.87 MW | 0.74 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 943462 | AF1-017 E | Adder | 1.42 MW | 1.21 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 943741 | AF1-042 C | Adder | 2.09 MW | 1.77 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 943742 | AF1-042 E | Adder | 3.4 MW | 2.89 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 961951 | AG1-038 C | Adder | 2.31 MW | 1.96 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 961952 | AG1-038 E | Adder | 3.18 MW | 2.71 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 966661 | AG1-536 C | Adder | 3.83 MW | 3.25 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 966662 | AG1-536 E | Adder | 5.14 MW | 4.37 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 966871 | AG1-558 C | 50/50 | 2.68 MW | 2.68 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 966872 | AG1-558 E | 50/50 | 1.35 MW | 1.35 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 315260 | 1GOSPORTA | Adder | 1.32 MW | 1.12 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 315261 | 1GOSPORTB | Adder | 1.69 MW | 1.44 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 315262 | 1GOSPORTC | Adder | 1.43 MW | 1.22 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 316076 | AC2-137 E | Adder | 1.16 MW | 0.98 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 316078 | AC2-138 E | Adder | 0.65 MW | 0.55 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 316108 | AB2-160 C | Adder | 4.28 MW | 3.64 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 316109 | AB2-160 E | Adder | 6.99 MW | 5.94 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 316157 | AD2-030 E | Adder | 0.87 MW | 0.74 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 916192 | Z1-068 E | Adder | 1.16 MW | 0.98 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 923842 | AB2-024 E | Adder | 1.35 MW | 1.15 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 930122 | AB1-027 E | 50/50 | 1.4 MW | 1.4 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 938552 | AE1-074 E | Adder | 0.92 MW | 0.78 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 939312 | AE1-162 E | Adder | 0.96 MW | 0.81 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 946262 | AF1-291 E | Adder | 1.18 MW | 1.0 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 957601 | AF2-054 C | Adder | 1.55 MW | 1.32 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 957602 | AF2-054 E | Adder | 1.03 MW | 0.88 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 962531 | AG1-102 C | Adder | 0.78 MW | 0.66 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 962532 | AG1-102 E | Adder | 1.62 MW | 1.38 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 962851 | AG1-134 C | Adder | 9.56 MW | 8.13 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 962852 | AG1-134 E | Adder | 6.37 MW | 5.42 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 962861 | AG1-135 C | Adder | 4.33 MW | 3.68 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 962862 | AG1-135 E | Adder | 2.88 MW | 2.45 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 962962 | AG1-145 E | Adder | 1.05 MW | 0.89 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 962971 | AG1-146 C | Adder | 2.22 MW | 1.89 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 962972 | AG1-146 E | Adder | 1.48 MW | 1.26 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 962981 | AG1-147 C | Adder | 5.18 MW | 4.4 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 962982 | AG1-147 E | Adder | 3.45 MW | 2.94 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 963611 | AG1-210 C | Adder | 0.46 MW | 0.39 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 963612 | AG1-210 E | Adder | 0.69 MW | 0.59 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 964211 | AG1-282 C | Adder | 1.42 MW | 1.21 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 964212 | AG1-282 E | Adder | 0.95 MW | 0.81 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 925332 | AB2-190 E | Adder | 6.19 MW | 5.26 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 925522 | AC1-027 E | Adder | 0.75 MW | 0.64 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 942001 | AE2-212 C | Adder | 1.67 MW | 1.42 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 942002 | AE2-212 E | Adder | 1.11 MW | 0.94 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 957831 | AF2-077 C | Adder | 1.52 MW | 1.29 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 957832 | AF2-077 E | Adder | 1.01 MW | 0.86 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 958161 | AF2-110 C | Adder | 0.84 MW | 0.72 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 958162 | AF2-110 E | Adder | 1.34 MW | 1.14 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 313811 | 6ELKO L286 | Adder | 1.21 MW | 1.03 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 314181 | 3NORNECK | Adder | 0.62 MW | 0.52 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 934011 | AD1-025 C | Adder | 12.56 MW | 10.68 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 934012 | AD1-025 E | Adder | 7.44 MW | 6.32 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 927041 | AC1-191 C | 50/50 | 10.76 MW | 10.76 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 927042 | AC1-191 E | 50/50 | 5.36 MW | 5.36 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 313053 | 6PAPERMILL | Adder | 4.98 MW | 4.24 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 316004 | AC1-112 C | 50/50 | 0.28 MW | 0.28 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 316160 | AE1-175 E | Adder | 0.87 MW | 0.74 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 316233 | AE1-074 C | Adder | 1.82 MW | 1.55 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 316240 | AF1-291 C | Adder | 1.76 MW | 1.5 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 316301 | AE2-228 C | Adder | 1.75 MW | 1.49 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 316304 | AE2-227 C | Adder | 1.93 MW | 1.64 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 316312 | AB1-027 C | 50/50 | 0.45 MW | 0.45 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 926785 | AC1-164_E | Adder | 14.7 MW | 12.49 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 934065 | AD1-033 E | Adder | 3.07 MW | 2.61 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 939612 | AE1-191 E | Adder | 4.21 MW | 3.58 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 963221 | AG1-171 C | Adder | 1.6 MW | 1.36 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 963222 | AG1-171 E | Adder | 1.07 MW | 0.91 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 963231 | AG1-172 C | Adder | 1.6 MW | 1.36 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 963232 | AG1-172 E | Adder | 1.07 MW | 0.91 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 963241 | AG1-173 C | Adder | 1.6 MW | 1.36 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 963242 | AG1-173 E | Adder | 1.07 MW | 0.91 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 963251 | AG1-174 C | Adder | 1.6 MW | 1.36 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 963252 | AG1-174 E | Adder | 1.07 MW | 0.91 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 315051 | AA1-145 CT1 | 50/50 | 4.01 MW | 4.01 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 316201 | AC1-065 C | Adder | 7.53 MW | 6.4 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 939246 | AE1-155 E | Adder | 6.2 MW | 5.27 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 924814 | AB2-134 E | Adder | 9.41 MW | 8.0 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 316084 | AB2-161 E | Adder | 3.79 MW | 3.22 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 932046 | AC2-012 E | Adder | 8.14 MW | 6.92 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 316311 | AC2-079 C | Adder | 3.68 MW | 3.12 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 932596 | AC2-079 E | Adder | 6.0 MW | 5.1 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 934146 | AD1-041 E | Adder | 2.63 MW | 2.24 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 934576 | AD1-082 E | Adder | 3.02 MW | 2.56 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 316349 | AD2-085 C | Adder | 2.22 MW | 1.89 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 936666 | AD2-085 E | Adder | 3.62 MW | 3.08 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 961611 | AG1-000B C | Adder | 11.3 MW | 9.6 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 941291 | AE2-123 C | Adder | 18.01 MW | 15.31 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 941292 | AE2-123 E | Adder | 70.24 MW | 59.71 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 941301 | AE2-124 C | Adder | 16.37 MW | 13.91 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 941302 | AE2-124 E | Adder | 71.82 MW | 61.04 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 941591 | AE2-156 C | Adder | 11.12 MW | 9.45 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 942371 | AE2-250 C | Adder | 7.61 MW | 6.47 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 942372 | AE2-250 E | Adder | 4.02 MW | 3.41 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 942551 | AE2-270 C | Adder | 20.0 MW | 17.0 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 944581 | AF1-123 C | Adder | 29.26 MW | 24.88 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 944582 | AF1-123 E | Adder | 67.01 MW | 56.96 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 944591 | AF1-124 C | Adder | 16.82 MW | 14.3 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 944592 | AF1-124 E | Adder | 38.52 MW | 32.74 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 944601 | AF1-125 C | Adder | 29.26 MW | 24.88 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 944602 | AF1-125 E | Adder | 67.01 MW | 56.96 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 944631 | AF1-128 C | Adder | 33.28 MW | 28.29 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 945361 | AF1-201 C | Adder | 11.27 MW | 9.58 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 945362 | AF1-201 E | Adder | 7.51 MW | 6.38 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 957711 | AF2-065 C | Adder | 10.2 MW | 8.67 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 957712 | AF2-065 E | Adder | 9.8 MW | 8.33 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 958261 | AF2-120 C | Adder | 4.45 MW | 3.78 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 958262 | AF2-120 E | Adder | 2.97 MW | 2.52 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 961711 | AG1-011 C | Adder | 21.33 MW | 18.13 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 962271 | AG1-075 C | Adder | 13.14 MW | 11.16 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 962272 | AG1-075 E | Adder | 8.0 MW | 6.8 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 964951 | AG1-359 C | Adder | 13.98 MW | 11.88 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 965001 | AG1-364 C | Adder | 4.45 MW | 3.78 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 965002 | AG1-364 E | Adder | 6.67 MW | 5.67 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 965281 | AG1-393 C | Adder | 1.69 MW | 1.44 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 965282 | AG1-393 E | Adder | 1.13 MW | 0.96 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 966611 | AG1-531 C | Adder | 4.02 MW | 3.41 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 966612 | AG1-531 E | Adder | 2.68 MW | 2.28 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 935161 | AD1-151 C | Adder | 12.2 MW | 10.37 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 935162 | AD1-151 E | Adder | 8.14 MW | 6.92 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 939191 | AE1-149 C | Adder | 7.65 MW | 6.5 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 939192 | AE1-149 E | Adder | 5.1 MW | 4.33 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 939601 | AE1-190 C | Adder | 1.58 MW | 1.34 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 939602 | AE1-190 E | Adder | 1.05 MW | 0.9 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 940431 | AE2-027 C | Adder | 10.29 MW | 8.75 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 940432 | AE2-027 E | Adder | 6.86 MW | 5.83 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 940551 | AE2-041 C | Adder | 5.32 MW | 4.52 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 940651 | AE2-052 C | Adder | 2.55 MW | 2.17 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 941101 | AE2-104 C | Adder | 2.07 MW | 1.76 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 941102 | AE2-104 E | Adder | 3.29 MW | 2.8 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 941281 | AE2-122 C | Adder | 17.53 MW | 14.9 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 941282 | AE2-122 E | Adder | 70.73 MW | 60.12 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 943471 | AF1-018 C | Adder | 5.32 MW | 4.52 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | 944641 | AF1-129 C | Adder | 85.02 MW | 72.26 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 2.31 MW | 2.31 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 5.04 MW | 5.04 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 34.57 MW | 34.57 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 1.46 MW | 1.46 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | NY | PJM->LTFIMP_NY | CLTF | 0.72 MW | 0.72 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.12 MW | 0.12 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | WEC | LTFEXP_WEC->PJM | CLTF | 0.06 MW | 0.06 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | CPLE | LTFEXP_CPLE->PJM | CLTF | 4.48 MW | 4.48 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | TVA | LTFEXP_TVA->PJM | CLTF | 1.59 MW | 1.59 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | MEC | LTFEXP_MEC->PJM | CLTF | 0.61 MW | 0.61 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | LAGN | LTFEXP_LAGN->PJM | CLTF | 2.06 MW | 2.06 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.03 MW | 0.03 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 9.33 MW | 9.33 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.13 MW | 2.13 MW |
| Details for 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314236 | 6NRTHEST | 50/50 | 0.34 MW | 0.34 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314314 | 3LOCKS | Adder | 1.03 MW | 0.88 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314331 | 6POE | Adder | 0.65 MW | 0.56 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314507 | 3THOMPSN | Adder | 0.85 MW | 0.72 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314525 | 6KINGFORK | Adder | 0.43 MW | 0.37 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315060 | 1CHESTF5 | Adder | 30.84 MW | 26.22 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315065 | 1CHESTF6 | Adder | 11.33 MW | 9.63 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315067 | 1DARBY 1 | 50/50 | 4.23 MW | 4.23 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315068 | 1DARBY 2 | 50/50 | 4.23 MW | 4.23 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315069 | 1DARBY 3 | 50/50 | 4.25 MW | 4.25 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315070 | 1DARBY 4 | 50/50 | 4.25 MW | 4.25 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315073 | 1STONECA | Adder | 3.57 MW | 3.04 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315083 | 1SPRUNCA | 50/50 | 10.34 MW | 10.34 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315084 | 1SPRUNCB | 50/50 | 10.34 MW | 10.34 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315092 | 1YORKTN3 | Adder | 66.86 MW | 56.83 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 925865 | AC1-065 E | Adder | 8.78 MW | 7.46 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 926662 | AC1-147 E | Adder | 0.56 MW | 0.47 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 926755 | AC1-161 E | Adder | 5.35 MW | 4.54 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 927226 | AC1-216 E | Adder | 3.77 MW | 3.21 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 934392 | AD1-063 E | Adder | 0.56 MW | 0.48 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 935112 | AD1-144 E | Adder | 0.4 MW | 0.34 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 936591 | AD2-074 C | Adder | 2.72 MW | 2.31 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 936592 | AD2-074 E | Adder | 4.43 MW | 3.77 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 942162 | AE2-228 E | Adder | 0.81 MW | 0.69 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 942341 | AE2-247 C | Adder | 0.65 MW | 0.56 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 942342 | AE2-247 E | Adder | 0.9 MW | 0.77 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 943461 | AF1-017 C | Adder | 0.59 MW | 0.5 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 943462 | AF1-017 E | Adder | 0.96 MW | 0.82 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 943741 | AF1-042 C | Adder | 1.42 MW | 1.21 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 943742 | AF1-042 E | Adder | 2.32 MW | 1.97 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 961951 | AG1-038 C | Adder | 1.57 MW | 1.33 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 961952 | AG1-038 E | Adder | 2.17 MW | 1.84 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 966661 | AG1-536 C | Adder | 2.59 MW | 2.2 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 966662 | AG1-536 E | Adder | 3.48 MW | 2.96 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315260 | 1GOSPORTA | Adder | 0.89 MW | 0.76 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315261 | 1GOSPORTB | Adder | 1.14 MW | 0.97 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315262 | 1GOSPORTC | Adder | 0.97 MW | 0.82 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316075 | AC2-137 C | 50/50 | 0.35 MW | 0.35 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316076 | AC2-137 E | 50/50 | 1.48 MW | 1.48 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316078 | AC2-138 E | Adder | 0.43 MW | 0.37 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316108 | AB2-160 C | Adder | 3.13 MW | 2.66 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316109 | AB2-160 E | Adder | 5.1 MW | 4.34 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316157 | AD2-030 E | Adder | 0.61 MW | 0.52 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 916192 | Z1-068 E | Adder | 0.78 MW | 0.67 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 923842 | AB2-024 E | Adder | 0.95 MW | 0.81 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 939312 | AE1-162 E | Adder | 0.64 MW | 0.55 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 946262 | AF1-291 E | Adder | 0.82 MW | 0.69 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957601 | AF2-054 C | Adder | 1.08 MW | 0.92 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957602 | AF2-054 E | Adder | 0.72 MW | 0.61 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962531 | AG1-102 C | Adder | 0.54 MW | 0.46 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962532 | AG1-102 E | Adder | 1.12 MW | 0.96 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962861 | AG1-135 C | Adder | 2.93 MW | 2.49 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962862 | AG1-135 E | Adder | 1.95 MW | 1.66 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962962 | AG1-145 E | Adder | 0.74 MW | 0.63 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962971 | AG1-146 C | Adder | 1.52 MW | 1.29 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962972 | AG1-146 E | Adder | 1.01 MW | 0.86 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962981 | AG1-147 C | Adder | 3.55 MW | 3.02 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962982 | AG1-147 E | Adder | 2.36 MW | 2.01 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963611 | AG1-210 C | Adder | 0.31 MW | 0.26 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963612 | AG1-210 E | Adder | 0.46 MW | 0.39 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 964211 | AG1-282 C | Adder | 0.96 MW | 0.81 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 964212 | AG1-282 E | Adder | 0.64 MW | 0.54 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 925332 | AB2-190 E | Adder | 4.04 MW | 3.43 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 925522 | AC1-027 E | Adder | 0.51 MW | 0.43 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 942001 | AE2-212 C | Adder | 1.16 MW | 0.98 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 942002 | AE2-212 E | Adder | 0.77 MW | 0.66 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957831 | AF2-077 C | Adder | 1.05 MW | 0.89 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957832 | AF2-077 E | Adder | 0.7 MW | 0.6 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 958161 | AF2-110 C | Adder | 0.57 MW | 0.49 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 958162 | AF2-110 E | Adder | 0.91 MW | 0.77 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 313811 | 6ELKO L286 | 50/50 | 1.54 MW | 1.54 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314181 | 3NORNECK | Adder | 0.41 MW | 0.35 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 933291 | AC2-141 C | Adder | 12.52 MW | 10.64 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 933292 | AC2-141 E | Adder | 5.35 MW | 4.54 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 934011 | AD1-025 C | Adder | 8.25 MW | 7.01 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 934012 | AD1-025 E | Adder | 4.89 MW | 4.15 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315085 | 1SPRUNCC | 50/50 | 0.16 MW | 0.16 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315086 | 1SPRUNCD | 50/50 | 0.16 MW | 0.16 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 313053 | 6PAPERMILL | Adder | 3.51 MW | 2.98 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316160 | AE1-175 E | Adder | 0.61 MW | 0.52 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316169 | AC1-164 GEN | 50/50 | 3.25 MW | 3.25 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316240 | AF1-291 C | Adder | 1.22 MW | 1.04 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316301 | AE2-228 C | Adder | 1.22 MW | 1.04 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 926785 | AC1-164_E | 50/50 | 10.58 MW | 10.58 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 934065 | AD1-033 E | Adder | 2.08 MW | 1.77 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 939612 | AE1-191 E | Adder | 2.96 MW | 2.52 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963221 | AG1-171 C | Adder | 1.05 MW | 0.89 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963222 | AG1-171 E | Adder | 0.7 MW | 0.6 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963231 | AG1-172 C | Adder | 1.05 MW | 0.89 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963232 | AG1-172 E | Adder | 0.7 MW | 0.6 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963241 | AG1-173 C | Adder | 1.05 MW | 0.89 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963242 | AG1-173 E | Adder | 0.7 MW | 0.6 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963251 | AG1-174 C | Adder | 1.05 MW | 0.89 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963252 | AG1-174 E | Adder | 0.7 MW | 0.6 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316201 | AC1-065 C | Adder | 5.32 MW | 4.53 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 939246 | AE1-155 E | Adder | 4.19 MW | 3.56 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 924814 | AB2-134 E | Adder | 6.18 MW | 5.25 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316084 | AB2-161 E | Adder | 2.58 MW | 2.19 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 932046 | AC2-012 E | Adder | 5.5 MW | 4.68 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316311 | AC2-079 C | Adder | 2.5 MW | 2.12 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 932596 | AC2-079 E | Adder | 4.07 MW | 3.46 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 934146 | AD1-041 E | Adder | 1.85 MW | 1.57 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 934576 | AD1-082 E | Adder | 2.05 MW | 1.75 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316349 | AD2-085 C | Adder | 1.51 MW | 1.28 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 936666 | AD2-085 E | Adder | 2.46 MW | 2.09 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 961611 | AG1-000B C | Adder | 7.5 MW | 6.38 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941291 | AE2-123 C | Adder | 12.18 MW | 10.36 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941292 | AE2-123 E | Adder | 47.51 MW | 40.38 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941301 | AE2-124 C | Adder | 11.07 MW | 9.41 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941302 | AE2-124 E | Adder | 48.58 MW | 41.29 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941591 | AE2-156 C | Adder | 7.51 MW | 6.39 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 942371 | AE2-250 C | Adder | 5.56 MW | 4.72 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 942372 | AE2-250 E | Adder | 2.93 MW | 2.49 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 942551 | AE2-270 C | Adder | 13.13 MW | 11.16 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944581 | AF1-123 C | Adder | 11.4 MW | 9.69 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944582 | AF1-123 E | Adder | 26.11 MW | 22.2 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944591 | AF1-124 C | Adder | 19.82 MW | 16.85 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944592 | AF1-124 E | Adder | 45.38 MW | 38.57 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944601 | AF1-125 C | Adder | 19.82 MW | 16.85 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944602 | AF1-125 E | Adder | 45.38 MW | 38.57 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944631 | AF1-128 C | Adder | 19.3 MW | 16.41 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 945361 | AF1-201 C | Adder | 7.8 MW | 6.63 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 945362 | AF1-201 E | Adder | 5.2 MW | 4.42 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957711 | AF2-065 C | Adder | 6.7 MW | 5.69 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957712 | AF2-065 E | Adder | 6.44 MW | 5.47 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 958261 | AF2-120 C | Adder | 3.01 MW | 2.56 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 958262 | AF2-120 E | Adder | 2.0 MW | 1.7 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 961711 | AG1-011 C | Adder | 14.01 MW | 11.91 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962271 | AG1-075 C | Adder | 9.59 MW | 8.15 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962272 | AG1-075 E | Adder | 5.85 MW | 4.97 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 964951 | AG1-359 C | Adder | 9.46 MW | 8.04 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965001 | AG1-364 C | Adder | 3.01 MW | 2.56 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965002 | AG1-364 E | Adder | 4.51 MW | 3.83 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965281 | AG1-393 C | Adder | 1.24 MW | 1.05 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965282 | AG1-393 E | Adder | 0.82 MW | 0.7 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 966611 | AG1-531 C | Adder | 2.72 MW | 2.31 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 966612 | AG1-531 E | Adder | 1.81 MW | 1.54 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 935161 | AD1-151 C | Adder | 7.99 MW | 6.79 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 935162 | AD1-151 E | Adder | 5.32 MW | 4.53 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 939191 | AE1-149 C | Adder | 5.22 MW | 4.43 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 939192 | AE1-149 E | Adder | 3.48 MW | 2.96 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 939601 | AE1-190 C | Adder | 1.11 MW | 0.94 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 939602 | AE1-190 E | Adder | 0.74 MW | 0.63 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 940431 | AE2-027 C | Adder | 7.6 MW | 6.46 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 940432 | AE2-027 E | Adder | 5.07 MW | 4.31 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 940551 | AE2-041 C | Adder | 3.74 MW | 3.18 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 940651 | AE2-052 C | Adder | 1.74 MW | 1.48 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941101 | AE2-104 C | Adder | 1.4 MW | 1.19 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941102 | AE2-104 E | Adder | 2.23 MW | 1.9 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941281 | AE2-122 C | Adder | 11.86 MW | 10.08 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941282 | AE2-122 E | Adder | 47.84 MW | 40.66 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 943471 | AF1-018 C | Adder | 3.74 MW | 3.18 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944641 | AF1-129 C | Adder | 59.11 MW | 50.24 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 5.22 MW | 5.22 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 4.82 MW | 4.82 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 24.92 MW | 24.92 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 1.02 MW | 1.02 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | NY | PJM->LTFIMP_NY | CLTF | 0.49 MW | 0.49 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.22 MW | 0.22 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | WEC | LTFEXP_WEC->PJM | CLTF | 0.11 MW | 0.11 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CPLE | LTFEXP_CPLE->PJM | CLTF | 3.12 MW | 3.12 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | TVA | LTFEXP_TVA->PJM | CLTF | 1.38 MW | 1.38 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | MEC | LTFEXP_MEC->PJM | CLTF | 0.76 MW | 0.76 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | LAGN | LTFEXP_LAGN->PJM | CLTF | 1.76 MW | 1.76 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.04 MW | 0.04 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 6.53 MW | 6.53 MW |
| 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.49 MW | 1.49 MW |
| Details for 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314541 | 3WATKINS | Adder | 0.3 MW | 0.25 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314539 | 3UNCAMP | Adder | 2.67 MW | 2.27 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 916042 | Z1-036 E | Adder | 12.23 MW | 10.4 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 938771 | AE1-103 C | Adder | 1.3 MW | 1.11 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 938772 | AE1-103 E | Adder | 1.8 MW | 1.53 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314331 | 6POE | Adder | 0.87 MW | 0.74 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314507 | 3THOMPSN | Adder | 0.98 MW | 0.83 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314525 | 6KINGFORK | Adder | 0.51 MW | 0.44 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314550 | 6HICKORY | Adder | 0.96 MW | 0.82 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315065 | 1CHESTF6 | Adder | 15.3 MW | 13.01 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315073 | 1STONECA | 50/50 | 13.61 MW | 13.61 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315076 | 1HOPPOLC | 50/50 | 2.55 MW | 2.55 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315077 | 1HOPHCF1 | 50/50 | 4.06 MW | 4.06 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315078 | 1HOPHCF2 | 50/50 | 4.06 MW | 4.06 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315079 | 1HOPHCF3 | 50/50 | 4.06 MW | 4.06 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315080 | 1HOPHCF4 | 50/50 | 6.16 MW | 6.16 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 926662 | AC1-147 E | Adder | 0.64 MW | 0.55 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 927226 | AC1-216 E | 50/50 | 10.91 MW | 10.91 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 935112 | AD1-144 E | Adder | 0.48 MW | 0.41 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 942162 | AE2-228 E | Adder | 1.06 MW | 0.91 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 942341 | AE2-247 C | Adder | 0.85 MW | 0.72 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 942342 | AE2-247 E | Adder | 1.18 MW | 1.0 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 943461 | AF1-017 C | Adder | 0.77 MW | 0.66 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 943462 | AF1-017 E | Adder | 1.26 MW | 1.07 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 943612 | AF1-032 E | Adder | 0.41 MW | 0.35 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944871 | AF1-152 C | Adder | 2.3 MW | 1.95 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944872 | AF1-152 E | Adder | 1.53 MW | 1.3 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315116 | 1SURRY 1 | 50/50 | 19.86 MW | 19.86 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315119 | 1GRAVEL3 | 50/50 | 2.02 MW | 2.02 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315120 | 1GRAVEL4 | 50/50 | 2.04 MW | 2.04 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315121 | 1GRAVEL5 | 50/50 | 2.02 MW | 2.02 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315122 | 1GRAVEL6 | 50/50 | 2.04 MW | 2.04 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315260 | 1GOSPORTA | Adder | 1.04 MW | 0.88 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315261 | 1GOSPORTB | Adder | 1.32 MW | 1.12 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315262 | 1GOSPORTC | Adder | 1.12 MW | 0.95 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315611 | 6Z1-036WIND | Adder | 2.9 MW | 2.46 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 316132 | AB2-190 C | 50/50 | 6.45 MW | 6.45 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 913392 | Y1-086 E | Adder | 0.96 MW | 0.82 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 916192 | Z1-068 E | Adder | 0.87 MW | 0.74 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 923832 | AB2-022 E | Adder | 0.54 MW | 0.46 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 923852 | AB2-025 E | Adder | 0.48 MW | 0.41 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 939312 | AE1-162 E | Adder | 1.11 MW | 0.94 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 946262 | AF1-291 E | Adder | 1.1 MW | 0.94 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957492 | AF2-043 E | Adder | 0.64 MW | 0.54 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 901082 | W1-029 E | Adder | 13.87 MW | 11.79 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 917122 | Z2-027 E | Adder | 0.59 MW | 0.5 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 925332 | AB2-190 E | 50/50 | 13.18 MW | 13.18 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 925522 | AC1-027 E | Adder | 0.57 MW | 0.48 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941501 | AE2-147 C | Adder | 6.9 MW | 5.86 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941502 | AE2-147 E | Adder | 4.6 MW | 3.91 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 942001 | AE2-212 C | Adder | 1.41 MW | 1.2 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 942002 | AE2-212 E | Adder | 0.94 MW | 0.8 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957871 | AF2-081 C | Adder | 4.41 MW | 3.75 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957872 | AF2-081 E | Adder | 1.89 MW | 1.6 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 958161 | AF2-110 C | Adder | 0.65 MW | 0.56 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 958162 | AF2-110 E | Adder | 1.04 MW | 0.88 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934011 | AD1-025 C | 50/50 | 23.84 MW | 23.84 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934012 | AD1-025 E | 50/50 | 14.12 MW | 14.12 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314632 | 6AYDLETT TAP | Adder | 0.6 MW | 0.51 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 316240 | AF1-291 C | Adder | 1.65 MW | 1.4 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 316301 | AE2-228 C | Adder | 1.6 MW | 1.36 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 316304 | AE2-227 C | Adder | -2.34 MW | -1.99 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 316369 | AC1-216 C | 50/50 | 1.91 MW | 1.91 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934065 | AD1-033 E | Adder | 2.24 MW | 1.9 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 937226 | AE2-253 E | Adder | 2.58 MW | 2.19 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 963221 | AG1-171 C | 50/50 | 3.04 MW | 3.04 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 963222 | AG1-171 E | 50/50 | 2.02 MW | 2.02 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 963231 | AG1-172 C | 50/50 | 3.04 MW | 3.04 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 963232 | AG1-172 E | 50/50 | 2.02 MW | 2.02 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 963241 | AG1-173 C | 50/50 | 3.04 MW | 3.04 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 963242 | AG1-173 E | 50/50 | 2.02 MW | 2.02 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 963251 | AG1-174 C | 50/50 | 3.04 MW | 3.04 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 963252 | AG1-174 E | 50/50 | 2.02 MW | 2.02 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 919153 | AA1-139 E2 | Adder | 1.8 MW | 1.53 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 919152 | AA1-139 E1 | Adder | 1.8 MW | 1.53 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 316033 | AB2-134 GEN | 50/50 | 2.51 MW | 2.51 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 924814 | AB2-134 E | 50/50 | 17.87 MW | 17.87 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 316084 | AB2-161 E | Adder | 3.94 MW | 3.35 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 932046 | AC2-012 E | Adder | 6.37 MW | 5.42 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 316311 | AC2-079 C | Adder | 3.2 MW | 2.72 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 932596 | AC2-079 E | Adder | 5.23 MW | 4.45 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934576 | AD1-082 E | Adder | 3.14 MW | 2.67 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 316349 | AD2-085 C | Adder | 1.96 MW | 1.67 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 936666 | AD2-085 E | Adder | 3.2 MW | 2.72 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 961611 | AG1-000B C | 50/50 | 17.1 MW | 17.1 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941291 | AE2-123 C | Adder | 13.5 MW | 11.47 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941292 | AE2-123 E | Adder | 52.63 MW | 44.74 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941301 | AE2-124 C | Adder | 12.21 MW | 10.38 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941302 | AE2-124 E | Adder | 53.56 MW | 45.53 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941591 | AE2-156 C | Adder | 8.66 MW | 7.36 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 942551 | AE2-270 C | 50/50 | 37.91 MW | 37.91 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944581 | AF1-123 C | Adder | 19.96 MW | 16.97 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944582 | AF1-123 E | Adder | 45.71 MW | 38.85 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944591 | AF1-124 C | Adder | 19.96 MW | 16.97 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944592 | AF1-124 E | Adder | 45.71 MW | 38.85 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944601 | AF1-125 C | Adder | 19.96 MW | 16.97 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944602 | AF1-125 E | Adder | 45.71 MW | 38.85 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 946011 | AF1-266 C | Adder | 5.56 MW | 4.73 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957711 | AF2-065 C | 50/50 | 19.33 MW | 19.33 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957712 | AF2-065 E | 50/50 | 18.57 MW | 18.57 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 961711 | AG1-011 C | 50/50 | 40.49 MW | 40.49 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 964951 | AG1-359 C | Adder | 10.13 MW | 8.61 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965001 | AG1-364 C | Adder | 3.47 MW | 2.95 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965002 | AG1-364 E | Adder | 5.2 MW | 4.42 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 966611 | AG1-531 C | Adder | 3.6 MW | 3.06 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 966612 | AG1-531 E | Adder | 2.4 MW | 2.04 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 935161 | AD1-151 C | 50/50 | 24.7 MW | 24.7 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 935162 | AD1-151 E | 50/50 | 16.47 MW | 16.47 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 938531 | AE1-072 C | Adder | 7.74 MW | 6.58 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 938532 | AE1-072 E | Adder | 4.03 MW | 3.43 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 939191 | AE1-149 C | Adder | 8.7 MW | 7.39 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 939192 | AE1-149 E | Adder | 5.8 MW | 4.93 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 940481 | AE2-033 C | Adder | 6.64 MW | 5.65 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 940482 | AE2-033 E | Adder | 4.48 MW | 3.81 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 940541 | AE2-040 C | Adder | 1.19 MW | 1.01 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 940651 | AE2-052 C | Adder | 2.9 MW | 2.46 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941101 | AE2-104 C | Adder | 1.6 MW | 1.36 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941102 | AE2-104 E | Adder | 2.55 MW | 2.17 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941281 | AE2-122 C | Adder | 13.13 MW | 11.16 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941282 | AE2-122 E | Adder | 52.99 MW | 45.05 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944641 | AF1-129 C | Adder | 79.8 MW | 67.83 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 5.21 MW | 5.21 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 4.58 MW | 4.58 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 23.16 MW | 23.16 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 0.91 MW | 0.91 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | NY | PJM->LTFIMP_NY | CLTF | 0.43 MW | 0.43 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.21 MW | 0.21 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | WEC | LTFEXP_WEC->PJM | CLTF | 0.11 MW | 0.11 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | CPLE | LTFEXP_CPLE->PJM | CLTF | 2.92 MW | 2.92 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | TVA | LTFEXP_TVA->PJM | CLTF | 1.29 MW | 1.29 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | MEC | LTFEXP_MEC->PJM | CLTF | 0.74 MW | 0.74 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | LAGN | LTFEXP_LAGN->PJM | CLTF | 1.66 MW | 1.66 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.04 MW | 0.04 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 5.8 MW | 5.8 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.39 MW | 1.39 MW |
| Details for 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 961941 | AG1-037 C | Adder | 0.16 MW | 0.14 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 961942 | AG1-037 E | Adder | 0.11 MW | 0.09 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 962331 | AG1-082 C | Adder | 0.64 MW | 0.55 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 962332 | AG1-082 E | Adder | 0.43 MW | 0.36 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 962341 | AG1-083 C | Adder | 0.64 MW | 0.55 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 962342 | AG1-083 E | Adder | 0.43 MW | 0.36 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 964801 | AG1-343 C | Adder | 1.92 MW | 1.63 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 964802 | AG1-343 E | Adder | 1.5 MW | 1.28 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965291 | AG1-394 C | Adder | 0.66 MW | 0.56 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965292 | AG1-394 E | Adder | 0.44 MW | 0.37 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314541 | 3WATKINS | Adder | 0.24 MW | 0.21 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 920042 | AA2-088 E OP | Adder | 3.45 MW | 2.93 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934521 | AD1-076 C | Adder | 4.44 MW | 3.77 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934522 | AD1-076 E | Adder | 2.26 MW | 1.92 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 943172 | AE2-346 E | Adder | 0.19 MW | 0.16 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 316141 | AB2-099 E | Adder | 0.08 MW | 0.07 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 900672 | V4-068 E | Adder | 0.11 MW | 0.1 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 940492 | AE2-034 E | Adder | 1.17 MW | 1.0 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957521 | AF2-046 C | Adder | 5.41 MW | 4.6 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957522 | AF2-046 E | Adder | 2.72 MW | 2.31 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957531 | AF2-047 C | Adder | 6.5 MW | 5.52 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957532 | AF2-047 E | Adder | 3.27 MW | 2.78 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314539 | 3UNCAMP | Adder | 2.21 MW | 1.88 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 916042 | Z1-036 E | Adder | 11.74 MW | 9.98 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 938771 | AE1-103 C | Adder | 1.09 MW | 0.92 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 938772 | AE1-103 E | Adder | 1.5 MW | 1.27 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314421 | 6WINCHST | 50/50 | 0.09 MW | 0.09 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314507 | 3THOMPSN | Adder | 0.9 MW | 0.76 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314525 | 6KINGFORK | Adder | 0.48 MW | 0.41 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314550 | 6HICKORY | Adder | 0.97 MW | 0.82 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315092 | 1YORKTN3 | 50/50 | 124.63 MW | 124.63 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 926662 | AC1-147 E | Adder | 0.59 MW | 0.5 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 926755 | AC1-161 E | Adder | 6.39 MW | 5.43 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 935112 | AD1-144 E | Adder | 0.44 MW | 0.38 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 942341 | AE2-247 C | Adder | 0.5 MW | 0.42 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 942342 | AE2-247 E | Adder | 0.69 MW | 0.59 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 943461 | AF1-017 C | Adder | 0.45 MW | 0.38 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 943462 | AF1-017 E | Adder | 0.74 MW | 0.63 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 943612 | AF1-032 E | Adder | 0.41 MW | 0.35 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944871 | AF1-152 C | Adder | 2.24 MW | 1.91 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944872 | AF1-152 E | Adder | 1.5 MW | 1.27 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315233 | 1SURRY 2 | 50/50 | 12.07 MW | 12.07 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315260 | 1GOSPORTA | Adder | 0.94 MW | 0.8 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315261 | 1GOSPORTB | Adder | 1.21 MW | 1.02 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315262 | 1GOSPORTC | Adder | 1.02 MW | 0.87 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315611 | 6Z1-036WIND | Adder | 2.78 MW | 2.37 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 913392 | Y1-086 E | Adder | 0.95 MW | 0.81 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 916192 | Z1-068 E | Adder | 0.84 MW | 0.71 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 923832 | AB2-022 E | Adder | 0.54 MW | 0.46 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 939312 | AE1-162 E | Adder | 0.58 MW | 0.49 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957492 | AF2-043 E | Adder | 0.63 MW | 0.54 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 962531 | AG1-102 C | Adder | 0.58 MW | 0.49 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 962532 | AG1-102 E | Adder | 1.2 MW | 1.02 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 901082 | W1-029 E | Adder | 13.54 MW | 11.51 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 917122 | Z2-027 E | Adder | 0.58 MW | 0.49 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 925522 | AC1-027 E | Adder | 0.54 MW | 0.46 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941501 | AE2-147 C | Adder | 6.73 MW | 5.72 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941502 | AE2-147 E | Adder | 4.49 MW | 3.81 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957831 | AF2-077 C | Adder | 1.12 MW | 0.95 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957832 | AF2-077 E | Adder | 0.75 MW | 0.64 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957871 | AF2-081 C | Adder | 4.4 MW | 3.74 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957872 | AF2-081 E | Adder | 1.89 MW | 1.6 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 958161 | AF2-110 C | Adder | 0.56 MW | 0.47 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 958162 | AF2-110 E | Adder | 0.89 MW | 0.75 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 933291 | AC2-141 C | Adder | 14.98 MW | 12.73 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 933292 | AC2-141 E | Adder | 6.39 MW | 5.43 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 939411 | AE1-173 C | Adder | 29.68 MW | 25.23 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 939412 | AE1-173 E | Adder | 19.79 MW | 16.82 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 933981 | AD1-022 C | Adder | 3.11 MW | 2.64 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 933982 | AD1-022 E | Adder | 1.69 MW | 1.44 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 961681 | AG1-008 C | Adder | 5.42 MW | 4.61 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 961682 | AG1-008 E | Adder | 2.71 MW | 2.31 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314594 | 6PLYMOUTH TP | Adder | 0.12 MW | 0.1 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314632 | 6AYDLETT TAP | Adder | 0.59 MW | 0.51 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934065 | AD1-033 E | Adder | 2.24 MW | 1.9 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 937226 | AE2-253 E | Adder | 2.58 MW | 2.19 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 918512 | AA1-065 E OP | Adder | 1.84 MW | 1.56 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 919153 | AA1-139 E2 | Adder | 1.8 MW | 1.53 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 919152 | AA1-139 E1 | Adder | 1.8 MW | 1.53 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 920692 | AA2-178 E | Adder | 1.56 MW | 1.33 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 925122 | AB2-169 E | Adder | 1.9 MW | 1.61 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 932046 | AC2-012 E | Adder | 5.81 MW | 4.94 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 316311 | AC2-079 C | Adder | 1.97 MW | 1.68 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 932596 | AC2-079 E | Adder | 3.22 MW | 2.73 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 316349 | AD2-085 C | Adder | 1.15 MW | 0.98 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 936666 | AD2-085 E | Adder | 1.88 MW | 1.6 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 961611 | AG1-000B C | Adder | 5.4 MW | 4.59 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941291 | AE2-123 C | Adder | 13.01 MW | 11.06 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941292 | AE2-123 E | Adder | 50.75 MW | 43.14 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941301 | AE2-124 C | Adder | 11.84 MW | 10.06 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941302 | AE2-124 E | Adder | 51.94 MW | 44.15 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941591 | AE2-156 C | Adder | 7.95 MW | 6.76 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944581 | AF1-123 C | Adder | 21.76 MW | 18.49 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944582 | AF1-123 E | Adder | 49.82 MW | 42.35 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944591 | AF1-124 C | Adder | 21.76 MW | 18.49 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944592 | AF1-124 E | Adder | 49.82 MW | 42.35 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944601 | AF1-125 C | Adder | 21.76 MW | 18.49 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944602 | AF1-125 E | Adder | 49.82 MW | 42.35 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 945361 | AF1-201 C | 50/50 | 10.39 MW | 10.39 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 945362 | AF1-201 E | 50/50 | 6.93 MW | 6.93 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 963291 | AG1-178 C | Adder | 1.27 MW | 1.08 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 964951 | AG1-359 C | Adder | 10.19 MW | 8.66 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965001 | AG1-364 C | Adder | 3.18 MW | 2.7 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965002 | AG1-364 E | Adder | 4.77 MW | 4.05 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965691 | AG1-437 C | Adder | 3.53 MW | 3.0 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965692 | AG1-437 E | Adder | 2.35 MW | 2.0 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965701 | AG1-438 C | Adder | 3.53 MW | 3.0 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965702 | AG1-438 E | Adder | 2.35 MW | 2.0 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965741 | AG1-442 C | Adder | 2.06 MW | 1.75 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965751 | AG1-443 C | Adder | 2.06 MW | 1.75 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 966611 | AG1-531 C | 50/50 | 3.58 MW | 3.58 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 966612 | AG1-531 E | 50/50 | 2.39 MW | 2.39 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934501 | AD1-074 C | Adder | 12.22 MW | 10.39 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934502 | AD1-074 E | Adder | 6.22 MW | 5.29 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934511 | AD1-075 C | Adder | 3.06 MW | 2.6 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934512 | AD1-075 E | Adder | 1.56 MW | 1.32 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 938531 | AE1-072 C | Adder | 7.71 MW | 6.55 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 938532 | AE1-072 E | Adder | 4.02 MW | 3.42 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 940641 | AE2-051 C | Adder | 4.99 MW | 4.24 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 940642 | AE2-051 E | Adder | 3.33 MW | 2.83 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941101 | AE2-104 C | Adder | 1.37 MW | 1.16 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941102 | AE2-104 E | Adder | 2.17 MW | 1.84 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941281 | AE2-122 C | Adder | 12.66 MW | 10.76 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941282 | AE2-122 E | Adder | 51.1 MW | 43.43 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 5.54 MW | 5.54 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 4.3 MW | 4.3 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 20.16 MW | 20.16 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 0.67 MW | 0.67 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | NY | PJM->LTFIMP_NY | CLTF | 0.32 MW | 0.32 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.22 MW | 0.22 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | WEC | LTFEXP_WEC->PJM | CLTF | 0.12 MW | 0.12 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | CPLE | LTFEXP_CPLE->PJM | CLTF | 2.51 MW | 2.51 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | TVA | LTFEXP_TVA->PJM | CLTF | 1.18 MW | 1.18 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | MEC | LTFEXP_MEC->PJM | CLTF | 0.73 MW | 0.73 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | LAGN | LTFEXP_LAGN->PJM | CLTF | 1.51 MW | 1.51 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.04 MW | 0.04 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 4.3 MW | 4.3 MW |
| 6SKIFF CREEK-6WALR285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.19 MW | 1.19 MW |
| Details for 8FENTRES-6FENTRES 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 588_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8FENTRES-6FENTRES 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 588_SRT-A | 944581 | AF1-123 C | 50/50 | 134.58 MW | 134.58 MW |
| 8FENTRES-6FENTRES 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 588_SRT-A | 944582 | AF1-123 E | 50/50 | 308.15 MW | 308.15 MW |
| 8FENTRES-6FENTRES 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 588_SRT-A | 944591 | AF1-124 C | 50/50 | 134.58 MW | 134.58 MW |
| 8FENTRES-6FENTRES 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 588_SRT-A | 944592 | AF1-124 E | 50/50 | 308.15 MW | 308.15 MW |
| 8FENTRES-6FENTRES 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 588_SRT-A | 944601 | AF1-125 C | 50/50 | 134.58 MW | 134.58 MW |
| 8FENTRES-6FENTRES 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 588_SRT-A | 944602 | AF1-125 E | 50/50 | 308.15 MW | 308.15 MW |
| Details for 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963041 | AG1-153 C | 50/50 | 6.64 MW | 6.64 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963042 | AG1-153 E | 50/50 | 9.96 MW | 9.96 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963111 | AG1-160 C | 50/50 | 6.75 MW | 6.75 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963112 | AG1-160 E | 50/50 | 10.13 MW | 10.13 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 966361 | AG1-505 C | 50/50 | 19.48 MW | 19.48 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 966362 | AG1-505 E | 50/50 | 12.99 MW | 12.99 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 966371 | AG1-506 C | 50/50 | 19.48 MW | 19.48 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 966372 | AG1-506 E | 50/50 | 12.99 MW | 12.99 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315153 | 1CLOVER1 | 50/50 | 11.0 MW | 11.0 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315154 | 1CLOVER2 | 50/50 | 10.9 MW | 10.9 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 942931 | AE2-313 C | 50/50 | 43.33 MW | 43.33 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 942932 | AE2-313 E | 50/50 | 28.89 MW | 28.89 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 944011 | AF1-069 C | 50/50 | 15.81 MW | 15.81 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 944012 | AF1-069 E | 50/50 | 6.14 MW | 6.14 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 941031 | AE2-094 C | 50/50 | 48.4 MW | 48.4 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 941032 | AE2-094 E | 50/50 | 21.68 MW | 21.68 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 957481 | AF2-042 C | 50/50 | 57.29 MW | 57.29 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 957482 | AF2-042 E | 50/50 | 38.2 MW | 38.2 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 314550 | 6HICKORY | 50/50 | 2.01 MW | 2.01 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 926755 | AC1-161 E | 50/50 | 37.13 MW | 37.13 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315102 | 1BRUNSWICKG1 | 50/50 | 8.27 MW | 8.27 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315103 | 1BRUNSWICKG2 | 50/50 | 8.27 MW | 8.27 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315104 | 1BRUNSWICKG3 | 50/50 | 8.27 MW | 8.27 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315105 | 1BRUNSWICKS1 | 50/50 | 17.18 MW | 17.18 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315108 | 1ELIZAR1 | 50/50 | 2.48 MW | 2.48 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315110 | 1ELIZAR3 | 50/50 | 2.52 MW | 2.52 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315241 | 1Z1-086 GT1 | 50/50 | 10.64 MW | 10.64 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315242 | 1Z1-086 GT2 | 50/50 | 10.64 MW | 10.64 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315243 | 1Z1-086 GT3 | 50/50 | 10.64 MW | 10.64 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 315244 | 1Z1-086 ST | 50/50 | 18.52 MW | 18.52 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 916192 | Z1-068 E | Adder | 1.7 MW | 1.45 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 933291 | AC2-141 C | 50/50 | 86.98 MW | 86.98 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 933292 | AC2-141 E | 50/50 | 37.13 MW | 37.13 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 939411 | AE1-173 C | 50/50 | 87.2 MW | 87.2 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 939412 | AE1-173 E | 50/50 | 58.13 MW | 58.13 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316185 | AD1-033 C | 50/50 | 0.96 MW | 0.96 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 316294 | AC1-161 C | 50/50 | 12.0 MW | 12.0 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 934065 | AD1-033 E | 50/50 | 4.66 MW | 4.66 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 941291 | AE2-123 C | Adder | 26.51 MW | 22.53 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 941292 | AE2-123 E | Adder | 103.37 MW | 87.86 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 941301 | AE2-124 C | Adder | 24.13 MW | 20.51 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 941302 | AE2-124 E | Adder | 105.88 MW | 90.0 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 941591 | AE2-156 C | Adder | 16.25 MW | 13.81 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 944581 | AF1-123 C | 50/50 | 50.14 MW | 50.14 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 944582 | AF1-123 E | 50/50 | 114.81 MW | 114.81 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 944591 | AF1-124 C | 50/50 | 50.14 MW | 50.14 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 944592 | AF1-124 E | 50/50 | 114.81 MW | 114.81 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 944601 | AF1-125 C | 50/50 | 50.14 MW | 50.14 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 944602 | AF1-125 E | 50/50 | 114.81 MW | 114.81 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963291 | AG1-178 C | 50/50 | 71.78 MW | 71.78 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 963351 | AG1-184 C | 50/50 | 38.67 MW | 38.67 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 964951 | AG1-359 C | 50/50 | 21.32 MW | 21.32 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965002 | AG1-364 E | Adder | 8.12 MW | 6.91 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 965811 | AG1-449 C | 50/50 | 28.06 MW | 28.06 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 934611 | AD1-087 C | 50/50 | 1.08 MW | 1.08 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 934612 | AD1-087 E | 50/50 | 3.7 MW | 3.7 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 935171 | AD1-152 C | 50/50 | 1.1 MW | 1.1 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 935172 | AD1-152 E | 50/50 | 5.38 MW | 5.38 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 937481 | AD2-202 C | 50/50 | 0.31 MW | 0.31 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 937482 | AD2-202 E | 50/50 | 1.08 MW | 1.08 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 940641 | AE2-051 C | 50/50 | 26.57 MW | 26.57 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 940642 | AE2-051 E | 50/50 | 17.71 MW | 17.71 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 941281 | AE2-122 C | Adder | 25.79 MW | 21.92 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 941282 | AE2-122 E | Adder | 104.08 MW | 88.47 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 945811 | AF1-246 C | 50/50 | 8.02 MW | 8.02 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | 945812 | AF1-246 E | 50/50 | 11.08 MW | 11.08 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 32.67 MW | 32.67 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 21.51 MW | 21.51 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 87.22 MW | 87.22 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 2.48 MW | 2.48 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | NY | PJM->LTFIMP_NY | CLTF | 1.13 MW | 1.13 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | LGEE | LTFEXP_LGEE->PJM | CLTF | 1.27 MW | 1.27 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | WEC | LTFEXP_WEC->PJM | CLTF | 0.67 MW | 0.67 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | CPLE | LTFEXP_CPLE->PJM | CLTF | 10.38 MW | 10.38 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | TVA | LTFEXP_TVA->PJM | CLTF | 5.7 MW | 5.7 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | MEC | LTFEXP_MEC->PJM | CLTF | 3.93 MW | 3.93 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | LAGN | LTFEXP_LAGN->PJM | CLTF | 7.24 MW | 7.24 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.24 MW | 0.24 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 15.8 MW | 15.8 MW |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S-1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 4.95 MW | 4.95 MW |
| Details for 8FENTRES-6FENTRES 500.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 588_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8FENTRES-6FENTRES 500.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 588_SRT-A | 944581 | AF1-123 C | 50/50 | 132.92 MW | 132.92 MW |
| 8FENTRES-6FENTRES 500.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 588_SRT-A | 944582 | AF1-123 E | 50/50 | 304.35 MW | 304.35 MW |
| 8FENTRES-6FENTRES 500.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 588_SRT-A | 944591 | AF1-124 C | 50/50 | 132.92 MW | 132.92 MW |
| 8FENTRES-6FENTRES 500.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 588_SRT-A | 944592 | AF1-124 E | 50/50 | 304.35 MW | 304.35 MW |
| 8FENTRES-6FENTRES 500.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 588_SRT-A | 944601 | AF1-125 C | 50/50 | 132.92 MW | 132.92 MW |
| 8FENTRES-6FENTRES 500.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 588_SRT-A | 944602 | AF1-125 E | 50/50 | 304.35 MW | 304.35 MW |
| Details for 6ELIZ R-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6ELIZ R-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 314295 | 6BIRDNECK | 50/50 | 0.03 MW | 0.03 MW |
| 6ELIZ R-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 314507 | 3THOMPSN | 50/50 | 1.39 MW | 1.39 MW |
| 6ELIZ R-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 314550 | 6HICKORY | Adder | 1.18 MW | 1.0 MW |
| 6ELIZ R-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 315108 | 1ELIZAR1 | 50/50 | 12.48 MW | 12.48 MW |
| 6ELIZ R-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 315109 | 1ELIZAR2 | 50/50 | 12.26 MW | 12.26 MW |
| 6ELIZ R-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 315110 | 1ELIZAR3 | 50/50 | 12.64 MW | 12.64 MW |
| 6ELIZ R-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 315260 | 1GOSPORTA | Adder | 0.81 MW | 0.69 MW |
| 6ELIZ R-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 315261 | 1GOSPORTB | Adder | 1.03 MW | 0.88 MW |
| 6ELIZ R-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 315262 | 1GOSPORTC | Adder | 0.87 MW | 0.74 MW |
| 6ELIZ R-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 913392 | Y1-086 E | Adder | 0.86 MW | 0.73 MW |
| 6ELIZ R-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 916192 | Z1-068 E | 50/50 | 1.68 MW | 1.68 MW |
| 6ELIZ R-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 923832 | AB2-022 E | Adder | 0.48 MW | 0.41 MW |
| 6ELIZ R-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 917122 | Z2-027 E | Adder | 0.47 MW | 0.4 MW |
| 6ELIZ R-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 925522 | AC1-027 E | 50/50 | 1.01 MW | 1.01 MW |
| 6ELIZ R-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 957871 | AF2-081 C | Adder | 4.93 MW | 4.19 MW |
| 6ELIZ R-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 957872 | AF2-081 E | Adder | 2.11 MW | 1.8 MW |
| 6ELIZ R-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 314632 | 6AYDLETT TAP | Adder | 0.63 MW | 0.54 MW |
| 6ELIZ R-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 316185 | AD1-033 C | 50/50 | 0.62 MW | 0.62 MW |
| 6ELIZ R-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 316316 | AC1-027 C | 50/50 | 0.22 MW | 0.22 MW |
| 6ELIZ R-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 934065 | AD1-033 E | 50/50 | 2.98 MW | 2.98 MW |
| 6ELIZ R-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 937226 | AE2-253 E | Adder | 2.99 MW | 2.54 MW |
| 6ELIZ R-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 919153 | AA1-139 E2 | Adder | 2.02 MW | 1.72 MW |
| 6ELIZ R-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 919152 | AA1-139 E1 | Adder | 2.02 MW | 1.72 MW |
| 6ELIZ R-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 941291 | AE2-123 C | 50/50 | 24.69 MW | 24.69 MW |
| 6ELIZ R-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 941292 | AE2-123 E | 50/50 | 96.27 MW | 96.27 MW |
| 6ELIZ R-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 941301 | AE2-124 C | 50/50 | 20.33 MW | 20.33 MW |
| 6ELIZ R-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 941302 | AE2-124 E | 50/50 | 89.2 MW | 89.2 MW |
| 6ELIZ R-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944581 | AF1-123 C | Adder | 26.74 MW | 22.73 MW |
| 6ELIZ R-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944582 | AF1-123 E | Adder | 61.23 MW | 52.04 MW |
| 6ELIZ R-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944591 | AF1-124 C | Adder | 26.74 MW | 22.73 MW |
| 6ELIZ R-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944592 | AF1-124 E | Adder | 61.23 MW | 52.04 MW |
| 6ELIZ R-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944601 | AF1-125 C | Adder | 26.74 MW | 22.73 MW |
| 6ELIZ R-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944602 | AF1-125 E | Adder | 61.23 MW | 52.04 MW |
| 6ELIZ R-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 964951 | AG1-359 C | Adder | 12.74 MW | 10.83 MW |
| 6ELIZ R-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 938531 | AE1-072 C | Adder | 8.33 MW | 7.08 MW |
| 6ELIZ R-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 938532 | AE1-072 E | Adder | 4.34 MW | 3.69 MW |
| 6ELIZ R-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 941281 | AE2-122 C | 50/50 | 24.02 MW | 24.02 MW |
| 6ELIZ R-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 941282 | AE2-122 E | 50/50 | 96.93 MW | 96.93 MW |
| 6ELIZ R-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 0.31 MW | 0.31 MW |
| 6ELIZ R-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 0.21 MW | 0.21 MW |
| 6ELIZ R-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | NY | PJM->LTFIMP_NY | CLTF | 0.11 MW | 0.11 MW |
| 6ELIZ R-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | COTTONWOOD | PJM->LTFIMP_COTTONWOOD | CLTF | 0.15 MW | 0.15 MW |
| 6ELIZ R-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | CPLE | LTFEXP_CPLE->PJM | CLTF | 0.11 MW | 0.11 MW |
| 6ELIZ R-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | PRAIRIE | PJM->LTFIMP_PRAIRIE | CLTF | 0.26 MW | 0.26 MW |
| 6ELIZ R-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | TRIMBLE | PJM->LTFIMP_TRIMBLE | CLTF | 0.06 MW | 0.06 MW |
| 6ELIZ R-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | BlueGrass | PJM->LTFIMP_BlueG | CLTF | 0.2 MW | 0.2 MW |
| 6ELIZ R-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 1.34 MW | 1.34 MW |
| 6ELIZ R-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | MDU | PJM->LTFIMP_MDU | CLTF | 0.01 MW | 0.01 MW |
| 6ELIZ R-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.05 MW | 0.05 MW |
| 6ELIZ R-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.11 MW | 0.11 MW |
| Details for 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 961941 | AG1-037 C | Adder | 0.16 MW | 0.14 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 961942 | AG1-037 E | Adder | 0.11 MW | 0.09 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 962331 | AG1-082 C | Adder | 0.64 MW | 0.55 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 962332 | AG1-082 E | Adder | 0.43 MW | 0.36 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 962341 | AG1-083 C | Adder | 0.64 MW | 0.55 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 962342 | AG1-083 E | Adder | 0.43 MW | 0.36 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 964801 | AG1-343 C | Adder | 1.91 MW | 1.62 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 964802 | AG1-343 E | Adder | 1.5 MW | 1.28 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965291 | AG1-394 C | Adder | 0.66 MW | 0.56 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965292 | AG1-394 E | Adder | 0.44 MW | 0.37 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314541 | 3WATKINS | Adder | 0.24 MW | 0.21 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 920042 | AA2-088 E OP | Adder | 3.44 MW | 2.92 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934521 | AD1-076 C | Adder | 4.43 MW | 3.76 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934522 | AD1-076 E | Adder | 2.26 MW | 1.92 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 943172 | AE2-346 E | Adder | 0.19 MW | 0.16 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 316141 | AB2-099 E | Adder | 0.08 MW | 0.07 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 900672 | V4-068 E | Adder | 0.11 MW | 0.1 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 940492 | AE2-034 E | Adder | 1.17 MW | 0.99 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957521 | AF2-046 C | Adder | 5.4 MW | 4.59 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957522 | AF2-046 E | Adder | 2.72 MW | 2.31 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957531 | AF2-047 C | Adder | 6.49 MW | 5.51 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957532 | AF2-047 E | Adder | 3.26 MW | 2.77 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314539 | 3UNCAMP | Adder | 2.2 MW | 1.87 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 916042 | Z1-036 E | Adder | 11.72 MW | 9.96 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 938771 | AE1-103 C | Adder | 1.08 MW | 0.92 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 938772 | AE1-103 E | Adder | 1.5 MW | 1.27 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314421 | 6WINCHST | 50/50 | 0.09 MW | 0.09 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314507 | 3THOMPSN | Adder | 0.89 MW | 0.76 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314525 | 6KINGFORK | Adder | 0.48 MW | 0.41 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314550 | 6HICKORY | Adder | 0.97 MW | 0.82 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315092 | 1YORKTN3 | 50/50 | 124.53 MW | 124.53 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 926662 | AC1-147 E | Adder | 0.59 MW | 0.5 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 926755 | AC1-161 E | Adder | 6.38 MW | 5.43 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 935112 | AD1-144 E | Adder | 0.44 MW | 0.38 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 942341 | AE2-247 C | Adder | 0.5 MW | 0.42 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 942342 | AE2-247 E | Adder | 0.69 MW | 0.58 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 943461 | AF1-017 C | Adder | 0.45 MW | 0.38 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 943462 | AF1-017 E | Adder | 0.74 MW | 0.62 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 943612 | AF1-032 E | Adder | 0.41 MW | 0.35 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944871 | AF1-152 C | Adder | 2.24 MW | 1.9 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944872 | AF1-152 E | Adder | 1.49 MW | 1.27 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315233 | 1SURRY 2 | 50/50 | 12.05 MW | 12.05 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315260 | 1GOSPORTA | Adder | 0.94 MW | 0.8 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315261 | 1GOSPORTB | Adder | 1.2 MW | 1.02 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315262 | 1GOSPORTC | Adder | 1.02 MW | 0.87 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315611 | 6Z1-036WIND | Adder | 2.78 MW | 2.36 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 913392 | Y1-086 E | Adder | 0.95 MW | 0.81 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 916192 | Z1-068 E | Adder | 0.84 MW | 0.71 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 923832 | AB2-022 E | Adder | 0.53 MW | 0.45 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 939312 | AE1-162 E | Adder | 0.58 MW | 0.49 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957492 | AF2-043 E | Adder | 0.63 MW | 0.54 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 962531 | AG1-102 C | Adder | 0.58 MW | 0.49 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 962532 | AG1-102 E | Adder | 1.2 MW | 1.02 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 962962 | AG1-145 E | 50/50 | 3.29 MW | 3.29 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 901082 | W1-029 E | Adder | 13.51 MW | 11.49 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 917122 | Z2-027 E | Adder | 0.57 MW | 0.49 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 925522 | AC1-027 E | Adder | 0.54 MW | 0.46 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941501 | AE2-147 C | Adder | 6.72 MW | 5.71 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941502 | AE2-147 E | Adder | 4.48 MW | 3.81 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957831 | AF2-077 C | Adder | 1.12 MW | 0.95 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957832 | AF2-077 E | Adder | 0.75 MW | 0.64 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957871 | AF2-081 C | Adder | 4.39 MW | 3.73 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957872 | AF2-081 E | Adder | 1.88 MW | 1.6 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 958161 | AF2-110 C | Adder | 0.56 MW | 0.47 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 958162 | AF2-110 E | Adder | 0.88 MW | 0.75 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 933291 | AC2-141 C | Adder | 14.95 MW | 12.71 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 933292 | AC2-141 E | Adder | 6.38 MW | 5.43 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 939411 | AE1-173 C | Adder | 29.62 MW | 25.18 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 939412 | AE1-173 E | Adder | 19.74 MW | 16.78 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 933981 | AD1-022 C | Adder | 3.1 MW | 2.64 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 933982 | AD1-022 E | Adder | 1.69 MW | 1.44 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 961681 | AG1-008 C | Adder | 5.41 MW | 4.6 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 961682 | AG1-008 E | Adder | 2.7 MW | 2.3 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314594 | 6PLYMOUTH TP | Adder | 0.12 MW | 0.1 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314632 | 6AYDLETT TAP | Adder | 0.59 MW | 0.5 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 316159 | AE1-175 C | 50/50 | 0.75 MW | 0.75 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 316160 | AE1-175 E | 50/50 | 2.71 MW | 2.71 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 316382 | AG1-145 C | 50/50 | 0.68 MW | 0.68 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934065 | AD1-033 E | Adder | 2.23 MW | 1.9 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 937226 | AE2-253 E | Adder | 2.58 MW | 2.19 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 918512 | AA1-065 E OP | Adder | 1.83 MW | 1.56 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 919153 | AA1-139 E2 | Adder | 1.8 MW | 1.53 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 919152 | AA1-139 E1 | Adder | 1.8 MW | 1.53 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 920692 | AA2-178 E | Adder | 1.56 MW | 1.33 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 925122 | AB2-169 E | Adder | 1.89 MW | 1.61 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 932046 | AC2-012 E | Adder | 5.8 MW | 4.93 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 316311 | AC2-079 C | Adder | 1.97 MW | 1.67 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 932596 | AC2-079 E | Adder | 3.21 MW | 2.73 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 316349 | AD2-085 C | Adder | 1.15 MW | 0.98 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 936666 | AD2-085 E | Adder | 1.88 MW | 1.59 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 961611 | AG1-000B C | Adder | 5.38 MW | 4.58 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941291 | AE2-123 C | Adder | 12.99 MW | 11.04 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941292 | AE2-123 E | Adder | 50.66 MW | 43.06 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941301 | AE2-124 C | Adder | 11.82 MW | 10.04 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941302 | AE2-124 E | Adder | 51.86 MW | 44.08 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941591 | AE2-156 C | Adder | 7.94 MW | 6.75 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944581 | AF1-123 C | Adder | 21.72 MW | 18.46 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944582 | AF1-123 E | Adder | 49.74 MW | 42.28 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944591 | AF1-124 C | Adder | 21.72 MW | 18.46 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944592 | AF1-124 E | Adder | 49.74 MW | 42.28 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944601 | AF1-125 C | Adder | 21.72 MW | 18.46 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944602 | AF1-125 E | Adder | 49.74 MW | 42.28 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 945361 | AF1-201 C | 50/50 | 10.38 MW | 10.38 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 945362 | AF1-201 E | 50/50 | 6.92 MW | 6.92 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 963291 | AG1-178 C | Adder | 0.06 MW | 0.05 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 964951 | AG1-359 C | Adder | 10.17 MW | 8.65 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965001 | AG1-364 C | Adder | 3.17 MW | 2.7 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965002 | AG1-364 E | Adder | 4.76 MW | 4.05 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965691 | AG1-437 C | Adder | 3.52 MW | 3.0 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965692 | AG1-437 E | Adder | 2.35 MW | 2.0 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965701 | AG1-438 C | Adder | 3.52 MW | 3.0 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965702 | AG1-438 E | Adder | 2.35 MW | 2.0 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965741 | AG1-442 C | Adder | 2.06 MW | 1.75 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965751 | AG1-443 C | Adder | 2.06 MW | 1.75 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 966611 | AG1-531 C | 50/50 | 3.58 MW | 3.58 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 966612 | AG1-531 E | 50/50 | 2.38 MW | 2.38 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934501 | AD1-074 C | Adder | 12.19 MW | 10.37 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934502 | AD1-074 E | Adder | 6.21 MW | 5.28 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934511 | AD1-075 C | Adder | 3.05 MW | 2.59 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934512 | AD1-075 E | Adder | 1.55 MW | 1.32 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 938531 | AE1-072 C | Adder | 7.7 MW | 6.54 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 938532 | AE1-072 E | Adder | 4.01 MW | 3.41 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 940641 | AE2-051 C | Adder | 4.98 MW | 4.23 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 940642 | AE2-051 E | Adder | 3.32 MW | 2.82 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941101 | AE2-104 C | Adder | 1.36 MW | 1.16 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941102 | AE2-104 E | Adder | 2.17 MW | 1.84 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941281 | AE2-122 C | Adder | 12.64 MW | 10.74 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941282 | AE2-122 E | Adder | 51.01 MW | 43.36 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 5.31 MW | 5.31 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 4.21 MW | 4.21 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 20.02 MW | 20.02 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 0.69 MW | 0.69 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | NY | PJM->LTFIMP_NY | CLTF | 0.33 MW | 0.33 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.21 MW | 0.21 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | WEC | LTFEXP_WEC->PJM | CLTF | 0.11 MW | 0.11 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | CPLE | LTFEXP_CPLE->PJM | CLTF | 2.49 MW | 2.49 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | TVA | LTFEXP_TVA->PJM | CLTF | 1.17 MW | 1.17 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | MEC | LTFEXP_MEC->PJM | CLTF | 0.71 MW | 0.71 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | LAGN | LTFEXP_LAGN->PJM | CLTF | 1.49 MW | 1.49 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.04 MW | 0.04 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 4.39 MW | 4.39 MW |
| 6LIGH285-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.19 MW | 1.19 MW |
| Details for 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 961941 | AG1-037 C | Adder | 0.16 MW | 0.14 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 961942 | AG1-037 E | Adder | 0.11 MW | 0.09 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 962331 | AG1-082 C | Adder | 0.64 MW | 0.55 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 962332 | AG1-082 E | Adder | 0.43 MW | 0.36 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 962341 | AG1-083 C | Adder | 0.64 MW | 0.55 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 962342 | AG1-083 E | Adder | 0.43 MW | 0.36 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 964801 | AG1-343 C | Adder | 1.92 MW | 1.63 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 964802 | AG1-343 E | Adder | 1.5 MW | 1.28 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965291 | AG1-394 C | Adder | 0.66 MW | 0.56 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965292 | AG1-394 E | Adder | 0.44 MW | 0.37 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314541 | 3WATKINS | Adder | 0.24 MW | 0.21 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 920042 | AA2-088 E OP | Adder | 3.45 MW | 2.93 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934521 | AD1-076 C | Adder | 4.44 MW | 3.77 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934522 | AD1-076 E | Adder | 2.26 MW | 1.92 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 943172 | AE2-346 E | Adder | 0.19 MW | 0.16 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 316141 | AB2-099 E | Adder | 0.08 MW | 0.07 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 900672 | V4-068 E | Adder | 0.11 MW | 0.1 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 940492 | AE2-034 E | Adder | 1.17 MW | 1.0 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957521 | AF2-046 C | Adder | 5.41 MW | 4.6 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957522 | AF2-046 E | Adder | 2.72 MW | 2.31 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957531 | AF2-047 C | Adder | 6.5 MW | 5.52 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957532 | AF2-047 E | Adder | 3.27 MW | 2.78 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314539 | 3UNCAMP | Adder | 2.21 MW | 1.88 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 916042 | Z1-036 E | Adder | 11.74 MW | 9.98 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 938771 | AE1-103 C | Adder | 1.09 MW | 0.92 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 938772 | AE1-103 E | Adder | 1.5 MW | 1.27 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314421 | 6WINCHST | 50/50 | 0.09 MW | 0.09 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314507 | 3THOMPSN | Adder | 0.9 MW | 0.76 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314525 | 6KINGFORK | Adder | 0.48 MW | 0.41 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314550 | 6HICKORY | Adder | 0.97 MW | 0.82 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315092 | 1YORKTN3 | 50/50 | 124.63 MW | 124.63 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 926662 | AC1-147 E | Adder | 0.59 MW | 0.5 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 926755 | AC1-161 E | Adder | 6.39 MW | 5.43 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 935112 | AD1-144 E | Adder | 0.44 MW | 0.38 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 942341 | AE2-247 C | Adder | 0.5 MW | 0.42 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 942342 | AE2-247 E | Adder | 0.69 MW | 0.59 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 943461 | AF1-017 C | Adder | 0.45 MW | 0.38 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 943462 | AF1-017 E | Adder | 0.74 MW | 0.63 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 943612 | AF1-032 E | Adder | 0.41 MW | 0.35 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944871 | AF1-152 C | Adder | 2.24 MW | 1.91 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944872 | AF1-152 E | Adder | 1.5 MW | 1.27 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315233 | 1SURRY 2 | 50/50 | 12.07 MW | 12.07 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315260 | 1GOSPORTA | Adder | 0.94 MW | 0.8 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315261 | 1GOSPORTB | Adder | 1.21 MW | 1.02 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315262 | 1GOSPORTC | Adder | 1.02 MW | 0.87 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315611 | 6Z1-036WIND | Adder | 2.78 MW | 2.37 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 913392 | Y1-086 E | Adder | 0.95 MW | 0.81 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 916192 | Z1-068 E | Adder | 0.84 MW | 0.71 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 923832 | AB2-022 E | Adder | 0.54 MW | 0.46 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 939312 | AE1-162 E | Adder | 0.58 MW | 0.49 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957492 | AF2-043 E | Adder | 0.63 MW | 0.54 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 962531 | AG1-102 C | Adder | 0.58 MW | 0.49 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 962532 | AG1-102 E | Adder | 1.2 MW | 1.02 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 901082 | W1-029 E | Adder | 13.54 MW | 11.51 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 917122 | Z2-027 E | Adder | 0.58 MW | 0.49 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 925522 | AC1-027 E | Adder | 0.54 MW | 0.46 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941501 | AE2-147 C | Adder | 6.73 MW | 5.72 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941502 | AE2-147 E | Adder | 4.49 MW | 3.81 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957831 | AF2-077 C | Adder | 1.12 MW | 0.95 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957832 | AF2-077 E | Adder | 0.75 MW | 0.64 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957871 | AF2-081 C | Adder | 4.4 MW | 3.74 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957872 | AF2-081 E | Adder | 1.89 MW | 1.6 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 958161 | AF2-110 C | Adder | 0.56 MW | 0.47 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 958162 | AF2-110 E | Adder | 0.89 MW | 0.75 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 933291 | AC2-141 C | Adder | 14.98 MW | 12.73 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 933292 | AC2-141 E | Adder | 6.39 MW | 5.43 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 939411 | AE1-173 C | Adder | 29.68 MW | 25.23 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 939412 | AE1-173 E | Adder | 19.79 MW | 16.82 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 933981 | AD1-022 C | Adder | 3.11 MW | 2.64 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 933982 | AD1-022 E | Adder | 1.69 MW | 1.44 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 961681 | AG1-008 C | Adder | 5.42 MW | 4.61 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 961682 | AG1-008 E | Adder | 2.71 MW | 2.31 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314594 | 6PLYMOUTH TP | Adder | 0.12 MW | 0.1 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314632 | 6AYDLETT TAP | Adder | 0.59 MW | 0.51 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934065 | AD1-033 E | Adder | 2.24 MW | 1.9 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 937226 | AE2-253 E | Adder | 2.58 MW | 2.19 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 918512 | AA1-065 E OP | Adder | 1.84 MW | 1.56 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 919153 | AA1-139 E2 | Adder | 1.8 MW | 1.53 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 919152 | AA1-139 E1 | Adder | 1.8 MW | 1.53 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 920692 | AA2-178 E | Adder | 1.56 MW | 1.33 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 925122 | AB2-169 E | Adder | 1.9 MW | 1.61 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 932046 | AC2-012 E | Adder | 5.81 MW | 4.94 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 316311 | AC2-079 C | Adder | 1.97 MW | 1.68 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 932596 | AC2-079 E | Adder | 3.22 MW | 2.73 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 316349 | AD2-085 C | Adder | 1.15 MW | 0.98 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 936666 | AD2-085 E | Adder | 1.88 MW | 1.6 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 961611 | AG1-000B C | Adder | 5.4 MW | 4.59 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941291 | AE2-123 C | Adder | 13.01 MW | 11.06 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941292 | AE2-123 E | Adder | 50.75 MW | 43.14 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941301 | AE2-124 C | Adder | 11.84 MW | 10.06 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941302 | AE2-124 E | Adder | 51.94 MW | 44.15 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941591 | AE2-156 C | Adder | 7.95 MW | 6.76 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944581 | AF1-123 C | Adder | 21.76 MW | 18.49 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944582 | AF1-123 E | Adder | 49.82 MW | 42.35 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944591 | AF1-124 C | Adder | 21.76 MW | 18.49 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944592 | AF1-124 E | Adder | 49.82 MW | 42.35 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944601 | AF1-125 C | Adder | 21.76 MW | 18.49 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944602 | AF1-125 E | Adder | 49.82 MW | 42.35 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 945361 | AF1-201 C | 50/50 | 10.39 MW | 10.39 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 945362 | AF1-201 E | 50/50 | 6.93 MW | 6.93 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 963291 | AG1-178 C | Adder | 1.27 MW | 1.08 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 964951 | AG1-359 C | Adder | 10.19 MW | 8.66 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965001 | AG1-364 C | Adder | 3.18 MW | 2.7 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965002 | AG1-364 E | Adder | 4.77 MW | 4.05 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965691 | AG1-437 C | Adder | 3.53 MW | 3.0 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965692 | AG1-437 E | Adder | 2.35 MW | 2.0 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965701 | AG1-438 C | Adder | 3.53 MW | 3.0 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965702 | AG1-438 E | Adder | 2.35 MW | 2.0 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965741 | AG1-442 C | Adder | 2.06 MW | 1.75 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965751 | AG1-443 C | Adder | 2.06 MW | 1.75 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 966611 | AG1-531 C | 50/50 | 3.58 MW | 3.58 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 966612 | AG1-531 E | 50/50 | 2.39 MW | 2.39 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934501 | AD1-074 C | Adder | 12.22 MW | 10.39 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934502 | AD1-074 E | Adder | 6.22 MW | 5.29 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934511 | AD1-075 C | Adder | 3.06 MW | 2.6 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934512 | AD1-075 E | Adder | 1.56 MW | 1.32 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 938531 | AE1-072 C | Adder | 7.71 MW | 6.55 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 938532 | AE1-072 E | Adder | 4.02 MW | 3.42 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 940641 | AE2-051 C | Adder | 4.99 MW | 4.24 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 940642 | AE2-051 E | Adder | 3.33 MW | 2.83 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941101 | AE2-104 C | Adder | 1.37 MW | 1.16 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941102 | AE2-104 E | Adder | 2.17 MW | 1.84 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941281 | AE2-122 C | Adder | 12.66 MW | 10.76 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941282 | AE2-122 E | Adder | 51.1 MW | 43.43 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 5.54 MW | 5.54 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 4.3 MW | 4.3 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 20.16 MW | 20.16 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 0.67 MW | 0.67 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | NY | PJM->LTFIMP_NY | CLTF | 0.32 MW | 0.32 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.22 MW | 0.22 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | WEC | LTFEXP_WEC->PJM | CLTF | 0.12 MW | 0.12 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | CPLE | LTFEXP_CPLE->PJM | CLTF | 2.51 MW | 2.51 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | TVA | LTFEXP_TVA->PJM | CLTF | 1.18 MW | 1.18 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | MEC | LTFEXP_MEC->PJM | CLTF | 0.73 MW | 0.73 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | LAGN | LTFEXP_LAGN->PJM | CLTF | 1.51 MW | 1.51 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.04 MW | 0.04 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 4.3 MW | 4.3 MW |
| 6WALR285-6LIGH285 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.19 MW | 1.19 MW |
| Details for 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 916042 | Z1-036 E | Adder | 8.51 MW | 7.24 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314184 | 3SHACKLE | 50/50 | 0.29 MW | 0.29 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314507 | 3THOMPSN | Adder | 0.67 MW | 0.57 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314525 | 6KINGFORK | Adder | 0.34 MW | 0.29 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314550 | 6HICKORY | Adder | 0.72 MW | 0.61 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315034 | 1NORNECKC1 | 50/50 | 0.37 MW | 0.37 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315060 | 1CHESTF5 | Adder | 24.62 MW | 20.93 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315092 | 1YORKTN3 | Adder | 71.74 MW | 60.98 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 925865 | AC1-065 E | 50/50 | 10.65 MW | 10.65 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 926412 | AC1-112 E | Adder | 0.38 MW | 0.33 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 926472 | AC1-118 E | Adder | 0.62 MW | 0.53 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 926662 | AC1-147 E | Adder | 0.44 MW | 0.37 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 926755 | AC1-161 E | Adder | 4.76 MW | 4.04 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 934392 | AD1-063 E | 50/50 | 0.76 MW | 0.76 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 935112 | AD1-144 E | Adder | 0.32 MW | 0.27 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 936582 | AD2-073 E | Adder | 0.67 MW | 0.57 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 936591 | AD2-074 C | 50/50 | 3.66 MW | 3.66 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 936592 | AD2-074 E | 50/50 | 5.97 MW | 5.97 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 943612 | AF1-032 E | Adder | 0.3 MW | 0.25 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 943741 | AF1-042 C | 50/50 | 1.91 MW | 1.91 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 943742 | AF1-042 E | 50/50 | 3.12 MW | 3.12 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944491 | AF1-114 C | Adder | 2.86 MW | 2.43 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944492 | AF1-114 E | Adder | 3.95 MW | 3.36 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944871 | AF1-152 C | Adder | 1.63 MW | 1.39 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944872 | AF1-152 E | Adder | 1.09 MW | 0.93 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 961951 | AG1-038 C | 50/50 | 2.12 MW | 2.12 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 961952 | AG1-038 E | 50/50 | 2.92 MW | 2.92 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 966661 | AG1-536 C | 50/50 | 3.54 MW | 3.54 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 966662 | AG1-536 E | 50/50 | 4.76 MW | 4.76 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315260 | 1GOSPORTA | Adder | 0.71 MW | 0.6 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315261 | 1GOSPORTB | Adder | 0.9 MW | 0.77 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315262 | 1GOSPORTC | Adder | 0.77 MW | 0.65 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315611 | 6Z1-036WIND | Adder | 2.02 MW | 1.72 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316078 | AC2-138 E | Adder | 0.61 MW | 0.52 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316156 | AD2-030 C | 50/50 | 0.21 MW | 0.21 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316157 | AD2-030 E | 50/50 | 0.77 MW | 0.77 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 913392 | Y1-086 E | Adder | 0.7 MW | 0.59 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 916192 | Z1-068 E | Adder | 0.62 MW | 0.53 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 923832 | AB2-022 E | Adder | 0.39 MW | 0.33 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 923842 | AB2-024 E | 50/50 | 1.32 MW | 1.32 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 930122 | AB1-027 E | Adder | 0.47 MW | 0.4 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 939312 | AE1-162 E | Adder | 0.46 MW | 0.39 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957492 | AF2-043 E | Adder | 0.46 MW | 0.39 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957601 | AF2-054 C | 50/50 | 1.38 MW | 1.38 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957602 | AF2-054 E | 50/50 | 0.92 MW | 0.92 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962531 | AG1-102 C | Adder | 0.63 MW | 0.54 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962532 | AG1-102 E | Adder | 1.32 MW | 1.12 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962861 | AG1-135 C | 50/50 | 4.0 MW | 4.0 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962862 | AG1-135 E | 50/50 | 2.67 MW | 2.67 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962962 | AG1-145 E | 50/50 | 0.94 MW | 0.94 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962971 | AG1-146 C | 50/50 | 2.03 MW | 2.03 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962972 | AG1-146 E | 50/50 | 1.35 MW | 1.35 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962981 | AG1-147 C | 50/50 | 4.73 MW | 4.73 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962982 | AG1-147 E | 50/50 | 3.15 MW | 3.15 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963611 | AG1-210 C | Adder | 0.44 MW | 0.37 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963612 | AG1-210 E | Adder | 0.65 MW | 0.56 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 964211 | AG1-282 C | 50/50 | 1.37 MW | 1.37 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 964212 | AG1-282 E | 50/50 | 0.91 MW | 0.91 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 901082 | W1-029 E | Adder | 9.86 MW | 8.38 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 917122 | Z2-027 E | Adder | 0.42 MW | 0.36 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 925522 | AC1-027 E | Adder | 0.4 MW | 0.34 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941501 | AE2-147 C | Adder | 4.9 MW | 4.17 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941502 | AE2-147 E | Adder | 3.27 MW | 2.78 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957831 | AF2-077 C | Adder | 1.23 MW | 1.05 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957832 | AF2-077 E | Adder | 0.82 MW | 0.7 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957871 | AF2-081 C | Adder | 3.25 MW | 2.77 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957872 | AF2-081 E | Adder | 1.39 MW | 1.19 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957971 | AF2-091 C | Adder | 0.97 MW | 0.83 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957972 | AF2-091 E | Adder | 1.34 MW | 1.14 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 958161 | AF2-110 C | Adder | 0.4 MW | 0.34 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 958162 | AF2-110 E | Adder | 0.64 MW | 0.55 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314181 | 3NORNECK | Adder | 0.58 MW | 0.49 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 933291 | AC2-141 C | Adder | 11.14 MW | 9.47 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 933292 | AC2-141 E | Adder | 4.76 MW | 4.04 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 313053 | 6PAPERMILL | 50/50 | 4.84 MW | 4.84 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314632 | 6AYDLETT TAP | Adder | 0.44 MW | 0.37 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316059 | AD1-063 C | 50/50 | 0.16 MW | 0.16 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316159 | AE1-175 C | 50/50 | 0.21 MW | 0.21 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316160 | AE1-175 E | 50/50 | 0.78 MW | 0.78 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316169 | AC1-164 GEN | 50/50 | 5.0 MW | 5.0 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316314 | AB2-024 C | 50/50 | 0.18 MW | 0.18 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316382 | AG1-145 C | 50/50 | 0.19 MW | 0.19 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 926785 | AC1-164_E | 50/50 | 16.27 MW | 16.27 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 934065 | AD1-033 E | Adder | 1.66 MW | 1.41 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 937226 | AE2-253 E | Adder | 1.91 MW | 1.62 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 939611 | AE1-191 C | 50/50 | 0.74 MW | 0.74 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 939612 | AE1-191 E | 50/50 | 3.67 MW | 3.67 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316201 | AC1-065 C | 50/50 | 6.46 MW | 6.46 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316404 | AE1-155 C | 50/50 | 1.18 MW | 1.18 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 939246 | AE1-155 E | 50/50 | 5.74 MW | 5.74 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 919153 | AA1-139 E2 | Adder | 1.33 MW | 1.13 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 919152 | AA1-139 E1 | Adder | 1.33 MW | 1.13 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 932046 | AC2-012 E | Adder | 4.35 MW | 3.7 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316280 | AD1-041 C | 50/50 | 0.47 MW | 0.47 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 934146 | AD1-041 E | 50/50 | 2.29 MW | 2.29 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 961611 | AG1-000B C | Adder | 4.72 MW | 4.01 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941291 | AE2-123 C | Adder | 9.68 MW | 8.23 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941292 | AE2-123 E | Adder | 37.77 MW | 32.1 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941301 | AE2-124 C | Adder | 8.8 MW | 7.48 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941302 | AE2-124 E | Adder | 38.64 MW | 32.84 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941591 | AE2-156 C | Adder | 5.95 MW | 5.06 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944581 | AF1-123 C | Adder | 16.14 MW | 13.72 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944582 | AF1-123 E | Adder | 36.95 MW | 31.41 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944591 | AF1-124 C | Adder | 16.14 MW | 13.72 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944592 | AF1-124 E | Adder | 36.95 MW | 31.41 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944601 | AF1-125 C | Adder | 16.14 MW | 13.72 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944602 | AF1-125 E | Adder | 36.95 MW | 31.41 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944631 | AF1-128 C | Adder | 15.41 MW | 13.1 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 945361 | AF1-201 C | Adder | 8.9 MW | 7.56 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 945362 | AF1-201 E | Adder | 5.93 MW | 5.04 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 958261 | AF2-120 C | 50/50 | 4.12 MW | 4.12 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 958262 | AF2-120 E | 50/50 | 2.75 MW | 2.75 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 964951 | AG1-359 C | Adder | 7.56 MW | 6.43 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965001 | AG1-364 C | Adder | 2.38 MW | 2.02 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965002 | AG1-364 E | Adder | 3.57 MW | 3.03 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 966611 | AG1-531 C | Adder | 2.33 MW | 1.98 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 966612 | AG1-531 E | Adder | 1.56 MW | 1.32 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 938531 | AE1-072 C | Adder | 5.69 MW | 4.84 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 938532 | AE1-072 E | Adder | 2.97 MW | 2.52 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 939601 | AE1-190 C | 50/50 | 1.38 MW | 1.38 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 939602 | AE1-190 E | 50/50 | 0.92 MW | 0.92 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 940551 | AE2-041 C | 50/50 | 5.04 MW | 5.04 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941101 | AE2-104 C | Adder | 0.99 MW | 0.84 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941102 | AE2-104 E | Adder | 1.58 MW | 1.34 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941281 | AE2-122 C | Adder | 9.42 MW | 8.01 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941282 | AE2-122 E | Adder | 38.03 MW | 32.33 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 943471 | AF1-018 C | 50/50 | 5.04 MW | 5.04 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 2.82 MW | 2.82 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 2.52 MW | 2.52 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 13.01 MW | 13.01 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 0.45 MW | 0.45 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | NY | PJM->LTFIMP_NY | CLTF | 0.21 MW | 0.21 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.12 MW | 0.12 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | WEC | LTFEXP_WEC->PJM | CLTF | 0.06 MW | 0.06 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CPLE | LTFEXP_CPLE->PJM | CLTF | 1.64 MW | 1.64 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | TVA | LTFEXP_TVA->PJM | CLTF | 0.71 MW | 0.71 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | MEC | LTFEXP_MEC->PJM | CLTF | 0.4 MW | 0.4 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | LAGN | LTFEXP_LAGN->PJM | CLTF | 0.92 MW | 0.92 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.02 MW | 0.02 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 2.85 MW | 2.85 MW |
| 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.78 MW | 0.78 MW |
| Details for AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 916042 | Z1-036 E | Adder | 10.42 MW | 8.86 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 314507 | 3THOMPSN | Adder | 1.03 MW | 0.88 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 314525 | 6KINGFORK | Adder | 0.57 MW | 0.48 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 314550 | 6HICKORY | Adder | 0.93 MW | 0.79 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 315092 | 1YORKTN3 | Adder | 51.3 MW | 43.6 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 926662 | AC1-147 E | Adder | 0.68 MW | 0.58 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 927226 | AC1-216 E | 50/50 | 10.86 MW | 10.86 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 935112 | AD1-144 E | Adder | 0.53 MW | 0.45 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 943612 | AF1-032 E | Adder | 0.38 MW | 0.32 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 944871 | AF1-152 C | Adder | 2.04 MW | 1.74 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 944872 | AF1-152 E | Adder | 1.36 MW | 1.16 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 315116 | 1SURRY 1 | 50/50 | 29.35 MW | 29.35 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 315117 | 1GRAVELC | 50/50 | 1.02 MW | 1.02 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 315119 | 1GRAVEL3 | 50/50 | 2.98 MW | 2.98 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 315120 | 1GRAVEL4 | 50/50 | 3.02 MW | 3.02 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 315121 | 1GRAVEL5 | 50/50 | 2.98 MW | 2.98 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 315122 | 1GRAVEL6 | 50/50 | 3.02 MW | 3.02 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 315260 | 1GOSPORTA | Adder | 1.09 MW | 0.93 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 315261 | 1GOSPORTB | Adder | 1.39 MW | 1.18 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 315262 | 1GOSPORTC | Adder | 1.18 MW | 1.0 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 315611 | 6Z1-036WIND | Adder | 2.47 MW | 2.1 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 913392 | Y1-086 E | Adder | 0.88 MW | 0.75 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 916192 | Z1-068 E | Adder | 0.88 MW | 0.74 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 923832 | AB2-022 E | Adder | 0.5 MW | 0.42 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 939312 | AE1-162 E | 50/50 | 1.52 MW | 1.52 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 957492 | AF2-043 E | Adder | 0.58 MW | 0.5 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 901082 | W1-029 E | Adder | 12.33 MW | 10.48 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 917122 | Z2-027 E | Adder | 0.53 MW | 0.45 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 925522 | AC1-027 E | Adder | 0.57 MW | 0.49 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 941501 | AE2-147 C | Adder | 6.13 MW | 5.21 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 941502 | AE2-147 E | Adder | 4.09 MW | 3.47 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 957871 | AF2-081 C | Adder | 4.17 MW | 3.54 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 957872 | AF2-081 E | Adder | 1.79 MW | 1.52 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 958161 | AF2-110 C | Adder | 0.46 MW | 0.39 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 958162 | AF2-110 E | Adder | 0.74 MW | 0.63 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 934011 | AD1-025 C | 50/50 | 23.73 MW | 23.73 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 934012 | AD1-025 E | 50/50 | 14.06 MW | 14.06 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 314632 | 6AYDLETT TAP | Adder | 0.56 MW | 0.48 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 316236 | AE1-162 C | 50/50 | 0.32 MW | 0.32 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 316240 | AF1-291 C | Adder | -0.81 MW | -0.69 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 316301 | AE2-228 C | Adder | -0.79 MW | -0.67 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 316304 | AE2-227 C | Adder | -0.69 MW | -0.59 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 316369 | AC1-216 C | 50/50 | 1.9 MW | 1.9 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 934065 | AD1-033 E | Adder | 2.17 MW | 1.84 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 937226 | AE2-253 E | Adder | 2.46 MW | 2.09 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 963221 | AG1-171 C | 50/50 | 3.02 MW | 3.02 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 963222 | AG1-171 E | 50/50 | 2.02 MW | 2.02 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 963231 | AG1-172 C | 50/50 | 3.02 MW | 3.02 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 963232 | AG1-172 E | 50/50 | 2.02 MW | 2.02 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 963241 | AG1-173 C | 50/50 | 3.02 MW | 3.02 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 963242 | AG1-173 E | 50/50 | 2.02 MW | 2.02 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 963251 | AG1-174 C | 50/50 | 3.02 MW | 3.02 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 963252 | AG1-174 E | 50/50 | 2.02 MW | 2.02 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 919153 | AA1-139 E2 | Adder | 1.71 MW | 1.45 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 919152 | AA1-139 E1 | Adder | 1.71 MW | 1.45 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 316033 | AB2-134 GEN | 50/50 | 2.5 MW | 2.5 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 924814 | AB2-134 E | 50/50 | 17.79 MW | 17.79 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 932046 | AC2-012 E | Adder | 6.7 MW | 5.7 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 961611 | AG1-000B C | 50/50 | 28.64 MW | 28.64 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 941291 | AE2-123 C | Adder | 13.52 MW | 11.49 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 941292 | AE2-123 E | Adder | 52.71 MW | 44.8 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 941301 | AE2-124 C | Adder | 12.16 MW | 10.34 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 941302 | AE2-124 E | Adder | 53.35 MW | 45.35 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 941591 | AE2-156 C | Adder | 9.07 MW | 7.71 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 944581 | AF1-123 C | Adder | 18.22 MW | 15.49 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 944582 | AF1-123 E | Adder | 41.72 MW | 35.46 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 944591 | AF1-124 C | Adder | 18.22 MW | 15.49 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 944592 | AF1-124 E | Adder | 41.72 MW | 35.46 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 944601 | AF1-125 C | Adder | 18.22 MW | 15.49 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 944602 | AF1-125 E | Adder | 41.72 MW | 35.46 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 961711 | AG1-011 C | 50/50 | 40.31 MW | 40.31 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 964951 | AG1-359 C | Adder | 9.77 MW | 8.3 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 965001 | AG1-364 C | Adder | 3.63 MW | 3.09 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 965002 | AG1-364 E | Adder | 5.45 MW | 4.63 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 966611 | AG1-531 C | 50/50 | 5.39 MW | 5.39 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 966612 | AG1-531 E | 50/50 | 3.6 MW | 3.6 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 935161 | AD1-151 C | 50/50 | 22.68 MW | 22.68 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 935162 | AD1-151 E | 50/50 | 15.12 MW | 15.12 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 938531 | AE1-072 C | Adder | 7.28 MW | 6.19 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 938532 | AE1-072 E | Adder | 3.8 MW | 3.23 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 941101 | AE2-104 C | Adder | 1.13 MW | 0.96 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 941102 | AE2-104 E | Adder | 1.8 MW | 1.53 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 941281 | AE2-122 C | Adder | 13.15 MW | 11.18 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 941282 | AE2-122 E | Adder | 53.07 MW | 45.11 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 0.73 MW | 0.73 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 1.22 MW | 1.22 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 7.81 MW | 7.81 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 0.4 MW | 0.4 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | NY | PJM->LTFIMP_NY | CLTF | 0.2 MW | 0.2 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.04 MW | 0.04 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | WEC | LTFEXP_WEC->PJM | CLTF | 0.02 MW | 0.02 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | CPLE | LTFEXP_CPLE->PJM | CLTF | 1.03 MW | 1.03 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | TVA | LTFEXP_TVA->PJM | CLTF | 0.37 MW | 0.37 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | MEC | LTFEXP_MEC->PJM | CLTF | 0.16 MW | 0.16 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | LAGN | LTFEXP_LAGN->PJM | CLTF | 0.48 MW | 0.48 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.01 MW | 0.01 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 2.56 MW | 2.56 MW |
| AG1-000B TP-AE2-270 TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.49 MW | 0.49 MW |
| Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 963041 | AG1-153 C | 50/50 | 8.28 MW | 8.28 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 963042 | AG1-153 E | 50/50 | 12.42 MW | 12.42 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 963111 | AG1-160 C | 50/50 | 8.42 MW | 8.42 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 963112 | AG1-160 E | 50/50 | 12.62 MW | 12.62 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 966361 | AG1-505 C | 50/50 | 24.27 MW | 24.27 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 966362 | AG1-505 E | 50/50 | 16.18 MW | 16.18 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 966371 | AG1-506 C | 50/50 | 24.27 MW | 24.27 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 966372 | AG1-506 E | 50/50 | 16.18 MW | 16.18 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 315153 | 1CLOVER1 | 50/50 | 13.72 MW | 13.72 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 315154 | 1CLOVER2 | 50/50 | 13.6 MW | 13.6 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 942931 | AE2-313 C | 50/50 | 53.93 MW | 53.93 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 942932 | AE2-313 E | 50/50 | 35.95 MW | 35.95 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 944011 | AF1-069 C | 50/50 | 19.69 MW | 19.69 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 944012 | AF1-069 E | 50/50 | 7.65 MW | 7.65 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 941031 | AE2-094 C | 50/50 | 60.25 MW | 60.25 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 941032 | AE2-094 E | 50/50 | 26.99 MW | 26.99 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 957481 | AF2-042 C | 50/50 | 71.39 MW | 71.39 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 957482 | AF2-042 E | 50/50 | 47.6 MW | 47.6 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 313526 | AB2-022 C | 50/50 | 0.35 MW | 0.35 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 314295 | 6BIRDNECK | 50/50 | 0.04 MW | 0.04 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 314550 | 6HICKORY | 50/50 | 2.38 MW | 2.38 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 926755 | AC1-161 E | 50/50 | 14.55 MW | 14.55 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 315102 | 1BRUNSWICKG1 | 50/50 | 10.32 MW | 10.32 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 315103 | 1BRUNSWICKG2 | 50/50 | 10.32 MW | 10.32 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 315104 | 1BRUNSWICKG3 | 50/50 | 10.32 MW | 10.32 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 315105 | 1BRUNSWICKS1 | 50/50 | 21.43 MW | 21.43 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 315110 | 1ELIZAR3 | 50/50 | 2.96 MW | 2.96 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 315241 | 1Z1-086 GT1 | 50/50 | 13.26 MW | 13.26 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 315242 | 1Z1-086 GT2 | 50/50 | 13.26 MW | 13.26 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 315243 | 1Z1-086 GT3 | 50/50 | 13.26 MW | 13.26 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 315244 | 1Z1-086 ST | 50/50 | 23.09 MW | 23.09 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 913392 | Y1-086 E | 50/50 | 2.4 MW | 2.4 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 916192 | Z1-068 E | 50/50 | 2.04 MW | 2.04 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 923832 | AB2-022 E | 50/50 | 1.36 MW | 1.36 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 923852 | AB2-025 E | 50/50 | 1.36 MW | 1.36 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 925522 | AC1-027 E | 50/50 | 1.32 MW | 1.32 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 957871 | AF2-081 C | 50/50 | 10.93 MW | 10.93 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 957872 | AF2-081 E | 50/50 | 4.68 MW | 4.68 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 933291 | AC2-141 C | 50/50 | 34.08 MW | 34.08 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 933292 | AC2-141 E | 50/50 | 14.55 MW | 14.55 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 939411 | AE1-173 C | 50/50 | 126.48 MW | 126.48 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 939412 | AE1-173 E | 50/50 | 84.32 MW | 84.32 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 314632 | 6AYDLETT TAP | 50/50 | 1.48 MW | 1.48 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 316023 | AB2-100 C2 | 50/50 | 0.93 MW | 0.93 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 316185 | AD1-033 C | 50/50 | 1.14 MW | 1.14 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 316294 | AC1-161 C | 50/50 | 4.7 MW | 4.7 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 316315 | AB2-025 C | 50/50 | 0.4 MW | 0.4 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 316316 | AC1-027 C | 50/50 | 0.29 MW | 0.29 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 316320 | Y1-086 C | 50/50 | 0.2 MW | 0.2 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 316365 | AB2-100 C1 | 50/50 | 0.93 MW | 0.93 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 924516 | AB2-100 E1 | 50/50 | 3.3 MW | 3.3 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 924517 | AB2-100 E2 | 50/50 | 3.3 MW | 3.3 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 934065 | AD1-033 E | 50/50 | 5.48 MW | 5.48 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 937226 | AE2-253 E | 50/50 | 6.39 MW | 6.39 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 316017 | AA1-139 ULT1 | 50/50 | 1.0 MW | 1.0 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 316018 | AA1-139 ULT2 | 50/50 | 1.0 MW | 1.0 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 919153 | AA1-139 E2 | 50/50 | 4.47 MW | 4.47 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 919152 | AA1-139 E1 | 50/50 | 4.47 MW | 4.47 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 316388 | AE2-253 GEN | 50/50 | 1.81 MW | 1.81 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 941291 | AE2-123 C | 50/50 | 31.77 MW | 31.77 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 941292 | AE2-123 E | 50/50 | 123.89 MW | 123.89 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 941301 | AE2-124 C | 50/50 | 28.92 MW | 28.92 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 941302 | AE2-124 E | 50/50 | 126.89 MW | 126.89 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 944581 | AF1-123 C | 50/50 | 53.38 MW | 53.38 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 944582 | AF1-123 E | 50/50 | 122.23 MW | 122.23 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 944591 | AF1-124 C | 50/50 | 53.38 MW | 53.38 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 944592 | AF1-124 E | 50/50 | 122.23 MW | 122.23 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 944601 | AF1-125 C | 50/50 | 53.38 MW | 53.38 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 944602 | AF1-125 E | 50/50 | 122.23 MW | 122.23 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 946011 | AF1-266 C | 50/50 | 15.8 MW | 15.8 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 963291 | AG1-178 C | 50/50 | 93.87 MW | 93.87 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 963351 | AG1-184 C | 50/50 | 50.57 MW | 50.57 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 964951 | AG1-359 C | 50/50 | 25.0 MW | 25.0 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 965811 | AG1-449 C | 50/50 | 34.92 MW | 34.92 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 934611 | AD1-087 C | 50/50 | 1.35 MW | 1.35 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 934612 | AD1-087 E | 50/50 | 4.62 MW | 4.62 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 935171 | AD1-152 C | 50/50 | 1.38 MW | 1.38 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 935172 | AD1-152 E | 50/50 | 6.74 MW | 6.74 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 937481 | AD2-202 C | 50/50 | 0.39 MW | 0.39 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 937482 | AD2-202 E | 50/50 | 1.35 MW | 1.35 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 938531 | AE1-072 C | 50/50 | 19.22 MW | 19.22 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 938532 | AE1-072 E | 50/50 | 10.02 MW | 10.02 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 940481 | AE2-033 C | 50/50 | 18.88 MW | 18.88 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 940482 | AE2-033 E | 50/50 | 12.72 MW | 12.72 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 940541 | AE2-040 C | 50/50 | 3.36 MW | 3.36 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 940641 | AE2-051 C | 50/50 | 25.71 MW | 25.71 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 940642 | AE2-051 E | 50/50 | 17.14 MW | 17.14 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 941281 | AE2-122 C | 50/50 | 30.91 MW | 30.91 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 941282 | AE2-122 E | 50/50 | 124.74 MW | 124.74 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 945811 | AF1-246 C | 50/50 | 9.99 MW | 9.99 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | 945812 | AF1-246 E | 50/50 | 13.8 MW | 13.8 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 41.71 MW | 41.71 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 28.11 MW | 28.11 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 114.72 MW | 114.72 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 4.08 MW | 4.08 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | NY | PJM->LTFIMP_NY | CLTF | 1.88 MW | 1.88 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | LGEE | LTFEXP_LGEE->PJM | CLTF | 1.65 MW | 1.65 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | WEC | LTFEXP_WEC->PJM | CLTF | 0.86 MW | 0.86 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | CPLE | LTFEXP_CPLE->PJM | CLTF | 13.67 MW | 13.67 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | TVA | LTFEXP_TVA->PJM | CLTF | 7.49 MW | 7.49 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | MEC | LTFEXP_MEC->PJM | CLTF | 5.08 MW | 5.08 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | LAGN | LTFEXP_LAGN->PJM | CLTF | 9.5 MW | 9.5 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.32 MW | 0.32 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 25.98 MW | 25.98 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 6.52 MW | 6.52 MW |
| Details for 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 964801 | AG1-343 C | Adder | 2.24 MW | 1.9 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 964802 | AG1-343 E | Adder | 1.76 MW | 1.49 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965291 | AG1-394 C | Adder | 0.77 MW | 0.65 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965292 | AG1-394 E | Adder | 0.51 MW | 0.43 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314541 | 3WATKINS | Adder | 0.28 MW | 0.24 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 920042 | AA2-088 E OP | Adder | 4.02 MW | 3.42 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934521 | AD1-076 C | Adder | 5.16 MW | 4.38 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934522 | AD1-076 E | Adder | 2.63 MW | 2.23 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 900672 | V4-068 E | Adder | 0.13 MW | 0.11 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 940492 | AE2-034 E | Adder | 1.36 MW | 1.16 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957521 | AF2-046 C | Adder | 6.32 MW | 5.37 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957522 | AF2-046 E | Adder | 3.18 MW | 2.7 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957531 | AF2-047 C | Adder | 7.54 MW | 6.41 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957532 | AF2-047 E | Adder | 3.79 MW | 3.22 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314539 | 3UNCAMP | Adder | 2.57 MW | 2.18 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 916042 | Z1-036 E | Adder | 13.59 MW | 11.55 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 938771 | AE1-103 C | Adder | 1.26 MW | 1.07 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 938772 | AE1-103 E | Adder | 1.74 MW | 1.48 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314421 | 6WINCHST | 50/50 | 0.1 MW | 0.1 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314507 | 3THOMPSN | Adder | 1.04 MW | 0.88 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314525 | 6KINGFORK | Adder | 0.55 MW | 0.47 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314550 | 6HICKORY | Adder | 1.12 MW | 0.95 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315092 | 1YORKTN3 | 50/50 | 139.18 MW | 139.18 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 926662 | AC1-147 E | Adder | 0.68 MW | 0.58 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 926755 | AC1-161 E | 50/50 | 7.36 MW | 7.36 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 935112 | AD1-144 E | Adder | 0.51 MW | 0.43 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 936591 | AD2-074 C | Adder | -4.75 MW | -4.04 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 942341 | AE2-247 C | Adder | 0.58 MW | 0.5 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 942342 | AE2-247 E | Adder | 0.81 MW | 0.69 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 943461 | AF1-017 C | Adder | 0.53 MW | 0.45 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 943462 | AF1-017 E | Adder | 0.86 MW | 0.73 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 943612 | AF1-032 E | Adder | 0.47 MW | 0.4 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 943741 | AF1-042 C | Adder | -2.49 MW | -2.12 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944871 | AF1-152 C | Adder | 2.6 MW | 2.21 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944872 | AF1-152 E | Adder | 1.73 MW | 1.47 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315233 | 1SURRY 2 | 50/50 | 13.85 MW | 13.85 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315260 | 1GOSPORTA | Adder | 1.09 MW | 0.93 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315261 | 1GOSPORTB | Adder | 1.4 MW | 1.19 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315262 | 1GOSPORTC | Adder | 1.18 MW | 1.01 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315611 | 6Z1-036WIND | Adder | 3.22 MW | 2.74 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 913392 | Y1-086 E | Adder | 1.1 MW | 0.93 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 916192 | Z1-068 E | Adder | 0.97 MW | 0.82 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 923832 | AB2-022 E | Adder | 0.62 MW | 0.53 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 939312 | AE1-162 E | Adder | 0.68 MW | 0.58 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957492 | AF2-043 E | Adder | 0.73 MW | 0.62 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 962962 | AG1-145 E | 50/50 | 0.91 MW | 0.91 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 901082 | W1-029 E | Adder | 15.66 MW | 13.31 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 917122 | Z2-027 E | Adder | 0.67 MW | 0.57 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 925522 | AC1-027 E | Adder | 0.63 MW | 0.53 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941501 | AE2-147 C | Adder | 7.78 MW | 6.62 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941502 | AE2-147 E | Adder | 5.19 MW | 4.41 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957871 | AF2-081 C | Adder | 5.09 MW | 4.32 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957872 | AF2-081 E | Adder | 2.18 MW | 1.85 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 958161 | AF2-110 C | Adder | 0.65 MW | 0.55 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 958162 | AF2-110 E | Adder | 1.03 MW | 0.87 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 933291 | AC2-141 C | 50/50 | 17.24 MW | 17.24 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 933292 | AC2-141 E | 50/50 | 7.36 MW | 7.36 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 939411 | AE1-173 C | Adder | 34.53 MW | 29.35 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 939412 | AE1-173 E | Adder | 23.02 MW | 19.57 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 933981 | AD1-022 C | Adder | 3.61 MW | 3.07 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 933982 | AD1-022 E | Adder | 1.97 MW | 1.67 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 961681 | AG1-008 C | Adder | 6.33 MW | 5.38 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 961682 | AG1-008 E | Adder | 2.99 MW | 2.54 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314594 | 6PLYMOUTH TP | Adder | 0.14 MW | 0.12 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314632 | 6AYDLETT TAP | Adder | 0.69 MW | 0.58 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 316159 | AE1-175 C | 50/50 | 0.21 MW | 0.21 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 316160 | AE1-175 E | 50/50 | 0.75 MW | 0.75 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 316294 | AC1-161 C | 50/50 | 2.38 MW | 2.38 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 316382 | AG1-145 C | 50/50 | 0.19 MW | 0.19 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934065 | AD1-033 E | Adder | 2.58 MW | 2.2 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 937226 | AE2-253 E | Adder | 2.98 MW | 2.54 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 918512 | AA1-065 E OP | Adder | 2.14 MW | 1.82 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 919153 | AA1-139 E2 | Adder | 2.08 MW | 1.77 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 919152 | AA1-139 E1 | Adder | 2.08 MW | 1.77 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 920692 | AA2-178 E | Adder | 1.81 MW | 1.54 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 932046 | AC2-012 E | Adder | 6.72 MW | 5.71 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 316311 | AC2-079 C | Adder | 2.3 MW | 1.96 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 932596 | AC2-079 E | Adder | 3.76 MW | 3.19 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 316349 | AD2-085 C | Adder | 1.35 MW | 1.15 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 936666 | AD2-085 E | Adder | 2.2 MW | 1.87 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 961611 | AG1-000B C | Adder | 6.39 MW | 5.43 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941291 | AE2-123 C | Adder | 15.04 MW | 12.79 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941292 | AE2-123 E | Adder | 58.66 MW | 49.86 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941301 | AE2-124 C | Adder | 13.68 MW | 11.63 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941302 | AE2-124 E | Adder | 60.04 MW | 51.04 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941591 | AE2-156 C | Adder | 9.2 MW | 7.82 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944581 | AF1-123 C | Adder | 25.12 MW | 21.36 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944582 | AF1-123 E | Adder | 57.53 MW | 48.9 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944591 | AF1-124 C | Adder | 25.12 MW | 21.36 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944592 | AF1-124 E | Adder | 57.53 MW | 48.9 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944601 | AF1-125 C | Adder | 25.12 MW | 21.36 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944602 | AF1-125 E | Adder | 57.53 MW | 48.9 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 945361 | AF1-201 C | Adder | 7.52 MW | 6.39 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 945362 | AF1-201 E | Adder | 5.02 MW | 4.26 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 964951 | AG1-359 C | Adder | 11.77 MW | 10.01 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965001 | AG1-364 C | Adder | 3.68 MW | 3.13 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965002 | AG1-364 E | Adder | 5.52 MW | 4.69 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965691 | AG1-437 C | Adder | 4.11 MW | 3.49 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965692 | AG1-437 E | Adder | 2.74 MW | 2.33 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965701 | AG1-438 C | Adder | 4.11 MW | 3.49 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965702 | AG1-438 E | Adder | 2.74 MW | 2.33 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965741 | AG1-442 C | Adder | 2.4 MW | 2.04 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965751 | AG1-443 C | Adder | 2.4 MW | 2.04 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 966611 | AG1-531 C | 50/50 | 4.09 MW | 4.09 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 966612 | AG1-531 E | 50/50 | 2.73 MW | 2.73 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934501 | AD1-074 C | Adder | 14.2 MW | 12.07 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934502 | AD1-074 E | Adder | 7.23 MW | 6.14 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934511 | AD1-075 C | Adder | 3.55 MW | 3.02 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934512 | AD1-075 E | Adder | 1.81 MW | 1.54 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 938531 | AE1-072 C | Adder | 8.91 MW | 7.58 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 938532 | AE1-072 E | Adder | 4.65 MW | 3.95 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 939601 | AE1-190 C | Adder | -1.6 MW | -1.36 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 940641 | AE2-051 C | Adder | 5.83 MW | 4.96 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 940642 | AE2-051 E | Adder | 3.89 MW | 3.3 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941101 | AE2-104 C | Adder | 1.58 MW | 1.34 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941102 | AE2-104 E | Adder | 2.52 MW | 2.14 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941281 | AE2-122 C | Adder | 14.64 MW | 12.44 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941282 | AE2-122 E | Adder | 59.07 MW | 50.21 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 7.31 MW | 7.31 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 5.39 MW | 5.39 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 24.17 MW | 24.17 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 0.85 MW | 0.85 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | NY | PJM->LTFIMP_NY | CLTF | 0.4 MW | 0.4 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.29 MW | 0.29 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | WEC | LTFEXP_WEC->PJM | CLTF | 0.15 MW | 0.15 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | CPLE | LTFEXP_CPLE->PJM | CLTF | 2.98 MW | 2.98 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | TVA | LTFEXP_TVA->PJM | CLTF | 1.47 MW | 1.47 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | MEC | LTFEXP_MEC->PJM | CLTF | 0.93 MW | 0.93 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | LAGN | LTFEXP_LAGN->PJM | CLTF | 1.87 MW | 1.87 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.06 MW | 0.06 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 5.41 MW | 5.41 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.42 MW | 1.42 MW |
| Details for 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 916042 | Z1-036 E | Adder | 10.42 MW | 8.86 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 314507 | 3THOMPSN | Adder | 1.03 MW | 0.88 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 314525 | 6KINGFORK | Adder | 0.57 MW | 0.48 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 314550 | 6HICKORY | Adder | 0.93 MW | 0.79 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 315092 | 1YORKTN3 | Adder | 51.3 MW | 43.6 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 926662 | AC1-147 E | Adder | 0.68 MW | 0.58 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 927226 | AC1-216 E | 50/50 | 10.86 MW | 10.86 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 935112 | AD1-144 E | Adder | 0.53 MW | 0.45 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 943612 | AF1-032 E | Adder | 0.38 MW | 0.32 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 944871 | AF1-152 C | Adder | 2.04 MW | 1.74 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 944872 | AF1-152 E | Adder | 1.36 MW | 1.16 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 315116 | 1SURRY 1 | 50/50 | 29.35 MW | 29.35 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 315117 | 1GRAVELC | 50/50 | 1.02 MW | 1.02 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 315119 | 1GRAVEL3 | 50/50 | 2.98 MW | 2.98 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 315120 | 1GRAVEL4 | 50/50 | 3.02 MW | 3.02 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 315121 | 1GRAVEL5 | 50/50 | 2.98 MW | 2.98 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 315122 | 1GRAVEL6 | 50/50 | 3.02 MW | 3.02 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 315260 | 1GOSPORTA | Adder | 1.09 MW | 0.93 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 315261 | 1GOSPORTB | Adder | 1.39 MW | 1.18 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 315262 | 1GOSPORTC | Adder | 1.18 MW | 1.0 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 315611 | 6Z1-036WIND | Adder | 2.47 MW | 2.1 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 913392 | Y1-086 E | Adder | 0.88 MW | 0.75 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 916192 | Z1-068 E | Adder | 0.88 MW | 0.74 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 923832 | AB2-022 E | Adder | 0.5 MW | 0.42 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 939312 | AE1-162 E | 50/50 | 1.52 MW | 1.52 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 957492 | AF2-043 E | Adder | 0.58 MW | 0.5 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 901082 | W1-029 E | Adder | 12.33 MW | 10.48 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 917122 | Z2-027 E | Adder | 0.53 MW | 0.45 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 925522 | AC1-027 E | Adder | 0.57 MW | 0.49 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 941501 | AE2-147 C | Adder | 6.13 MW | 5.21 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 941502 | AE2-147 E | Adder | 4.09 MW | 3.47 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 957871 | AF2-081 C | Adder | 4.17 MW | 3.54 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 957872 | AF2-081 E | Adder | 1.79 MW | 1.52 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 934011 | AD1-025 C | 50/50 | 23.73 MW | 23.73 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 934012 | AD1-025 E | 50/50 | 14.06 MW | 14.06 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 314632 | 6AYDLETT TAP | Adder | 0.56 MW | 0.48 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 316236 | AE1-162 C | 50/50 | 0.32 MW | 0.32 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 316240 | AF1-291 C | Adder | -0.81 MW | -0.69 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 316301 | AE2-228 C | Adder | -0.79 MW | -0.67 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 316369 | AC1-216 C | 50/50 | 1.9 MW | 1.9 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 934065 | AD1-033 E | Adder | 2.17 MW | 1.84 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 937226 | AE2-253 E | Adder | 2.46 MW | 2.09 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 963221 | AG1-171 C | 50/50 | 3.02 MW | 3.02 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 963222 | AG1-171 E | 50/50 | 2.02 MW | 2.02 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 963231 | AG1-172 C | 50/50 | 3.02 MW | 3.02 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 963232 | AG1-172 E | 50/50 | 2.02 MW | 2.02 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 963241 | AG1-173 C | 50/50 | 3.02 MW | 3.02 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 963242 | AG1-173 E | 50/50 | 2.02 MW | 2.02 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 963251 | AG1-174 C | 50/50 | 3.02 MW | 3.02 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 963252 | AG1-174 E | 50/50 | 2.02 MW | 2.02 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 919153 | AA1-139 E2 | Adder | 1.71 MW | 1.45 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 919152 | AA1-139 E1 | Adder | 1.71 MW | 1.45 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 316033 | AB2-134 GEN | 50/50 | 2.5 MW | 2.5 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 924814 | AB2-134 E | 50/50 | 17.79 MW | 17.79 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 932046 | AC2-012 E | Adder | 6.7 MW | 5.7 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 941291 | AE2-123 C | Adder | 13.52 MW | 11.49 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 941292 | AE2-123 E | Adder | 52.71 MW | 44.8 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 941301 | AE2-124 C | Adder | 12.16 MW | 10.34 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 941302 | AE2-124 E | Adder | 53.35 MW | 45.35 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 941591 | AE2-156 C | Adder | 9.07 MW | 7.71 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 944581 | AF1-123 C | Adder | 18.22 MW | 15.49 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 944582 | AF1-123 E | Adder | 41.72 MW | 35.46 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 944591 | AF1-124 C | Adder | 18.22 MW | 15.49 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 944592 | AF1-124 E | Adder | 41.72 MW | 35.46 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 944601 | AF1-125 C | Adder | 18.22 MW | 15.49 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 944602 | AF1-125 E | Adder | 41.72 MW | 35.46 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 961711 | AG1-011 C | 50/50 | 40.31 MW | 40.31 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 964951 | AG1-359 C | Adder | 9.77 MW | 8.3 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 965001 | AG1-364 C | Adder | 3.63 MW | 3.09 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 965002 | AG1-364 E | Adder | 5.45 MW | 4.63 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 966611 | AG1-531 C | 50/50 | 5.39 MW | 5.39 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 966612 | AG1-531 E | 50/50 | 3.6 MW | 3.6 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 935161 | AD1-151 C | 50/50 | 22.68 MW | 22.68 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 935162 | AD1-151 E | 50/50 | 15.12 MW | 15.12 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 938531 | AE1-072 C | Adder | 7.28 MW | 6.19 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 938532 | AE1-072 E | Adder | 3.8 MW | 3.23 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 941281 | AE2-122 C | Adder | 13.15 MW | 11.18 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | 941282 | AE2-122 E | Adder | 53.07 MW | 45.11 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 0.73 MW | 0.73 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 1.22 MW | 1.22 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 7.81 MW | 7.81 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 0.4 MW | 0.4 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | NY | PJM->LTFIMP_NY | CLTF | 0.2 MW | 0.2 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.04 MW | 0.04 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | WEC | LTFEXP_WEC->PJM | CLTF | 0.02 MW | 0.02 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | CPLE | LTFEXP_CPLE->PJM | CLTF | 1.03 MW | 1.03 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | TVA | LTFEXP_TVA->PJM | CLTF | 0.37 MW | 0.37 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | MEC | LTFEXP_MEC->PJM | CLTF | 0.16 MW | 0.16 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | LAGN | LTFEXP_LAGN->PJM | CLTF | 0.48 MW | 0.48 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.01 MW | 0.01 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 2.56 MW | 2.56 MW |
| 6SURRY-AG1-000B TP 230.0 kV Ckt 2 line l/o DVP_P1-2: LN 2197_SRT-A-2 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.49 MW | 0.49 MW |
| Details for 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 964801 | AG1-343 C | Adder | 2.24 MW | 1.9 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 964802 | AG1-343 E | Adder | 1.76 MW | 1.49 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965291 | AG1-394 C | Adder | 0.77 MW | 0.65 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965292 | AG1-394 E | Adder | 0.51 MW | 0.43 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314541 | 3WATKINS | Adder | 0.28 MW | 0.24 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 920042 | AA2-088 E OP | Adder | 4.02 MW | 3.42 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934521 | AD1-076 C | Adder | 5.16 MW | 4.38 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934522 | AD1-076 E | Adder | 2.63 MW | 2.23 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 900672 | V4-068 E | Adder | 0.13 MW | 0.11 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 940492 | AE2-034 E | Adder | 1.36 MW | 1.16 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957521 | AF2-046 C | Adder | 6.32 MW | 5.37 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957522 | AF2-046 E | Adder | 3.18 MW | 2.7 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957531 | AF2-047 C | Adder | 7.54 MW | 6.41 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957532 | AF2-047 E | Adder | 3.79 MW | 3.22 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314539 | 3UNCAMP | Adder | 2.57 MW | 2.18 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 916042 | Z1-036 E | Adder | 13.59 MW | 11.55 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 938771 | AE1-103 C | Adder | 1.26 MW | 1.07 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 938772 | AE1-103 E | Adder | 1.74 MW | 1.48 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314421 | 6WINCHST | 50/50 | 0.1 MW | 0.1 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314507 | 3THOMPSN | Adder | 1.04 MW | 0.88 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314525 | 6KINGFORK | Adder | 0.55 MW | 0.47 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314550 | 6HICKORY | Adder | 1.12 MW | 0.95 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315092 | 1YORKTN3 | 50/50 | 139.18 MW | 139.18 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 926662 | AC1-147 E | Adder | 0.68 MW | 0.58 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 926755 | AC1-161 E | 50/50 | 7.36 MW | 7.36 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 935112 | AD1-144 E | Adder | 0.51 MW | 0.43 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 936591 | AD2-074 C | Adder | -4.75 MW | -4.04 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 942341 | AE2-247 C | Adder | 0.58 MW | 0.5 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 942342 | AE2-247 E | Adder | 0.81 MW | 0.69 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 943461 | AF1-017 C | Adder | 0.53 MW | 0.45 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 943462 | AF1-017 E | Adder | 0.86 MW | 0.73 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 943612 | AF1-032 E | Adder | 0.47 MW | 0.4 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 943741 | AF1-042 C | Adder | -2.49 MW | -2.12 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944871 | AF1-152 C | Adder | 2.6 MW | 2.21 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944872 | AF1-152 E | Adder | 1.73 MW | 1.47 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315233 | 1SURRY 2 | 50/50 | 13.85 MW | 13.85 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315260 | 1GOSPORTA | Adder | 1.09 MW | 0.93 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315261 | 1GOSPORTB | Adder | 1.4 MW | 1.19 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315262 | 1GOSPORTC | Adder | 1.18 MW | 1.01 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315611 | 6Z1-036WIND | Adder | 3.22 MW | 2.74 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 913392 | Y1-086 E | Adder | 1.1 MW | 0.93 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 916192 | Z1-068 E | Adder | 0.97 MW | 0.82 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 923832 | AB2-022 E | Adder | 0.62 MW | 0.53 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 939312 | AE1-162 E | Adder | 0.68 MW | 0.58 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957492 | AF2-043 E | Adder | 0.73 MW | 0.62 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 962962 | AG1-145 E | 50/50 | 0.91 MW | 0.91 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 901082 | W1-029 E | Adder | 15.66 MW | 13.31 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 917122 | Z2-027 E | Adder | 0.67 MW | 0.57 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 925522 | AC1-027 E | Adder | 0.63 MW | 0.53 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941501 | AE2-147 C | Adder | 7.78 MW | 6.62 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941502 | AE2-147 E | Adder | 5.19 MW | 4.41 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957871 | AF2-081 C | Adder | 5.09 MW | 4.32 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957872 | AF2-081 E | Adder | 2.18 MW | 1.85 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 958161 | AF2-110 C | Adder | 0.65 MW | 0.55 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 958162 | AF2-110 E | Adder | 1.03 MW | 0.87 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 933291 | AC2-141 C | 50/50 | 17.24 MW | 17.24 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 933292 | AC2-141 E | 50/50 | 7.36 MW | 7.36 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 939411 | AE1-173 C | Adder | 34.53 MW | 29.35 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 939412 | AE1-173 E | Adder | 23.02 MW | 19.57 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 933981 | AD1-022 C | Adder | 3.61 MW | 3.07 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 933982 | AD1-022 E | Adder | 1.97 MW | 1.67 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 961681 | AG1-008 C | Adder | 6.33 MW | 5.38 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 961682 | AG1-008 E | Adder | 2.99 MW | 2.54 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314594 | 6PLYMOUTH TP | Adder | 0.14 MW | 0.12 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314632 | 6AYDLETT TAP | Adder | 0.69 MW | 0.58 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 316159 | AE1-175 C | 50/50 | 0.21 MW | 0.21 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 316160 | AE1-175 E | 50/50 | 0.75 MW | 0.75 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 316294 | AC1-161 C | 50/50 | 2.38 MW | 2.38 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 316382 | AG1-145 C | 50/50 | 0.19 MW | 0.19 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934065 | AD1-033 E | Adder | 2.58 MW | 2.2 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 937226 | AE2-253 E | Adder | 2.98 MW | 2.54 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 918512 | AA1-065 E OP | Adder | 2.14 MW | 1.82 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 919153 | AA1-139 E2 | Adder | 2.08 MW | 1.77 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 919152 | AA1-139 E1 | Adder | 2.08 MW | 1.77 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 920692 | AA2-178 E | Adder | 1.81 MW | 1.54 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 932046 | AC2-012 E | Adder | 6.72 MW | 5.71 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 316311 | AC2-079 C | Adder | 2.3 MW | 1.96 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 932596 | AC2-079 E | Adder | 3.76 MW | 3.19 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 316349 | AD2-085 C | Adder | 1.35 MW | 1.15 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 936666 | AD2-085 E | Adder | 2.2 MW | 1.87 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 961611 | AG1-000B C | Adder | 6.39 MW | 5.43 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941291 | AE2-123 C | Adder | 15.04 MW | 12.79 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941292 | AE2-123 E | Adder | 58.66 MW | 49.86 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941301 | AE2-124 C | Adder | 13.68 MW | 11.63 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941302 | AE2-124 E | Adder | 60.04 MW | 51.04 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941591 | AE2-156 C | Adder | 9.2 MW | 7.82 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944581 | AF1-123 C | Adder | 25.12 MW | 21.36 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944582 | AF1-123 E | Adder | 57.53 MW | 48.9 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944591 | AF1-124 C | Adder | 25.12 MW | 21.36 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944592 | AF1-124 E | Adder | 57.53 MW | 48.9 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944601 | AF1-125 C | Adder | 25.12 MW | 21.36 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944602 | AF1-125 E | Adder | 57.53 MW | 48.9 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 945361 | AF1-201 C | Adder | 7.52 MW | 6.39 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 945362 | AF1-201 E | Adder | 5.02 MW | 4.26 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 964951 | AG1-359 C | Adder | 11.77 MW | 10.01 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965001 | AG1-364 C | Adder | 3.68 MW | 3.13 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965002 | AG1-364 E | Adder | 5.52 MW | 4.69 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965691 | AG1-437 C | Adder | 4.11 MW | 3.49 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965692 | AG1-437 E | Adder | 2.74 MW | 2.33 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965701 | AG1-438 C | Adder | 4.11 MW | 3.49 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965702 | AG1-438 E | Adder | 2.74 MW | 2.33 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965741 | AG1-442 C | Adder | 2.4 MW | 2.04 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965751 | AG1-443 C | Adder | 2.4 MW | 2.04 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 966611 | AG1-531 C | 50/50 | 4.09 MW | 4.09 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 966612 | AG1-531 E | 50/50 | 2.73 MW | 2.73 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934501 | AD1-074 C | Adder | 14.2 MW | 12.07 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934502 | AD1-074 E | Adder | 7.23 MW | 6.14 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934511 | AD1-075 C | Adder | 3.55 MW | 3.02 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934512 | AD1-075 E | Adder | 1.81 MW | 1.54 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 938531 | AE1-072 C | Adder | 8.91 MW | 7.58 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 938532 | AE1-072 E | Adder | 4.65 MW | 3.95 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 939601 | AE1-190 C | Adder | -1.6 MW | -1.36 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 940641 | AE2-051 C | Adder | 5.83 MW | 4.96 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 940642 | AE2-051 E | Adder | 3.89 MW | 3.3 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941101 | AE2-104 C | Adder | 1.58 MW | 1.34 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941102 | AE2-104 E | Adder | 2.52 MW | 2.14 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941281 | AE2-122 C | Adder | 14.64 MW | 12.44 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941282 | AE2-122 E | Adder | 59.07 MW | 50.21 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 7.31 MW | 7.31 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 5.39 MW | 5.39 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 24.17 MW | 24.17 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 0.85 MW | 0.85 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | NY | PJM->LTFIMP_NY | CLTF | 0.4 MW | 0.4 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.29 MW | 0.29 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | WEC | LTFEXP_WEC->PJM | CLTF | 0.15 MW | 0.15 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | CPLE | LTFEXP_CPLE->PJM | CLTF | 2.98 MW | 2.98 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | TVA | LTFEXP_TVA->PJM | CLTF | 1.47 MW | 1.47 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | MEC | LTFEXP_MEC->PJM | CLTF | 0.93 MW | 0.93 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | LAGN | LTFEXP_LAGN->PJM | CLTF | 1.87 MW | 1.87 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.06 MW | 0.06 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 5.41 MW | 5.41 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.42 MW | 1.42 MW |
| Details for 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 934521 | AD1-076 C | Adder | 10.89 MW | 9.26 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 934522 | AD1-076 E | Adder | 5.55 MW | 4.72 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 940492 | AE2-034 E | Adder | 3.35 MW | 2.84 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 957531 | AF2-047 C | Adder | 18.55 MW | 15.77 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 957532 | AF2-047 E | Adder | 9.33 MW | 7.93 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 916042 | Z1-036 E | Adder | 40.44 MW | 34.37 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 314507 | 3THOMPSN | Adder | 6.44 MW | 5.48 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 314550 | 6HICKORY | Adder | 6.84 MW | 5.81 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 926662 | AC1-147 E | 50/50 | 4.3 MW | 4.3 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 927226 | AC1-216 E | Adder | 6.8 MW | 5.78 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 944871 | AF1-152 C | Adder | 7.52 MW | 6.39 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 944872 | AF1-152 E | Adder | 5.02 MW | 4.26 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 315098 | 1CHESPKA | 50/50 | 1.2 MW | 1.2 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 315099 | 1CHESPKB | 50/50 | 1.98 MW | 1.98 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 315108 | 1ELIZAR1 | 50/50 | 9.04 MW | 9.04 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 315109 | 1ELIZAR2 | 50/50 | 8.88 MW | 8.88 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 315110 | 1ELIZAR3 | 50/50 | 9.16 MW | 9.16 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 315260 | 1GOSPORTA | Adder | 6.85 MW | 5.83 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 315261 | 1GOSPORTB | Adder | 8.75 MW | 7.44 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 315262 | 1GOSPORTC | Adder | 7.43 MW | 6.31 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 315611 | 6Z1-036WIND | Adder | 9.59 MW | 8.15 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 913392 | Y1-086 E | Adder | 4.9 MW | 4.17 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 916192 | Z1-068 E | Adder | 5.95 MW | 5.05 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 923832 | AB2-022 E | Adder | 2.77 MW | 2.35 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 939312 | AE1-162 E | Adder | 2.96 MW | 2.52 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 901082 | W1-029 E | Adder | 45.39 MW | 38.58 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 917122 | Z2-027 E | Adder | 2.68 MW | 2.28 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 925522 | AC1-027 E | Adder | 3.84 MW | 3.27 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 941501 | AE2-147 C | Adder | 22.57 MW | 19.18 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 941502 | AE2-147 E | Adder | 15.05 MW | 12.79 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 957871 | AF2-081 C | Adder | 28.48 MW | 24.21 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 957872 | AF2-081 E | Adder | 12.21 MW | 10.38 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 934011 | AD1-025 C | Adder | 14.86 MW | 12.63 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 934012 | AD1-025 E | Adder | 8.8 MW | 7.48 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 933981 | AD1-022 C | Adder | 6.88 MW | 5.84 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 933982 | AD1-022 E | Adder | 3.74 MW | 3.18 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 314594 | 6PLYMOUTH TP | Adder | 0.3 MW | 0.25 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 314632 | 6AYDLETT TAP | Adder | 3.65 MW | 3.1 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 316036 | AC1-147 C | 50/50 | 1.01 MW | 1.01 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 934065 | AD1-033 E | Adder | 16.16 MW | 13.73 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 937226 | AE2-253 E | Adder | 17.3 MW | 14.71 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 963221 | AG1-171 C | Adder | 1.89 MW | 1.61 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 963222 | AG1-171 E | Adder | 1.26 MW | 1.07 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 963231 | AG1-172 C | Adder | 1.89 MW | 1.61 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 963232 | AG1-172 E | Adder | 1.26 MW | 1.07 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 963241 | AG1-173 C | Adder | 1.89 MW | 1.61 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 963242 | AG1-173 E | Adder | 1.26 MW | 1.07 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 963251 | AG1-174 C | Adder | 1.89 MW | 1.61 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 963252 | AG1-174 E | Adder | 1.26 MW | 1.07 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 919153 | AA1-139 E2 | Adder | 11.65 MW | 9.9 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 919152 | AA1-139 E1 | Adder | 11.65 MW | 9.9 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 920692 | AA2-178 E | Adder | 4.46 MW | 3.79 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 924814 | AB2-134 E | Adder | 11.13 MW | 9.46 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 316375 | AC2-012 C | 50/50 | 3.73 MW | 3.73 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 932046 | AC2-012 E | 50/50 | 42.55 MW | 42.55 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 961611 | AG1-000B C | Adder | 18.63 MW | 15.84 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 941291 | AE2-123 C | Adder | 92.31 MW | 78.46 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 941292 | AE2-123 E | Adder | 359.97 MW | 305.97 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 941301 | AE2-124 C | Adder | 83.72 MW | 71.16 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 941302 | AE2-124 E | Adder | 367.34 MW | 312.24 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 941591 | AE2-156 C | 50/50 | 59.02 MW | 59.02 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 942551 | AE2-270 C | Adder | 23.7 MW | 20.15 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 944581 | AF1-123 C | 50/50 | 185.14 MW | 185.14 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 944582 | AF1-123 E | 50/50 | 423.92 MW | 423.92 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 944591 | AF1-124 C | 50/50 | 185.14 MW | 185.14 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 944592 | AF1-124 E | 50/50 | 423.92 MW | 423.92 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 944601 | AF1-125 C | 50/50 | 185.14 MW | 185.14 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 944602 | AF1-125 E | 50/50 | 423.92 MW | 423.92 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 957711 | AF2-065 C | Adder | 12.09 MW | 10.28 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 957712 | AF2-065 E | Adder | 11.62 MW | 9.87 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 961711 | AG1-011 C | Adder | 25.23 MW | 21.45 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 964951 | AG1-359 C | Adder | 73.91 MW | 62.83 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 965001 | AG1-364 C | 50/50 | 23.55 MW | 23.55 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 965002 | AG1-364 E | 50/50 | 35.32 MW | 35.32 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 966611 | AG1-531 C | Adder | 4.45 MW | 3.79 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 966612 | AG1-531 E | Adder | 2.97 MW | 2.52 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 934501 | AD1-074 C | Adder | 29.99 MW | 25.49 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 934502 | AD1-074 E | Adder | 15.26 MW | 12.97 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 934511 | AD1-075 C | Adder | 7.5 MW | 6.37 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 934512 | AD1-075 E | Adder | 3.82 MW | 3.24 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 935161 | AD1-151 C | Adder | 12.57 MW | 10.68 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 935162 | AD1-151 E | Adder | 8.38 MW | 7.12 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 938531 | AE1-072 C | Adder | 48.03 MW | 40.83 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 938532 | AE1-072 E | Adder | 25.04 MW | 21.28 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 941281 | AE2-122 C | Adder | 89.82 MW | 76.35 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | 941282 | AE2-122 E | Adder | 362.45 MW | 308.09 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 0.47 MW | 0.47 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | NY | PJM->LTFIMP_NY | CLTF | 0.24 MW | 0.24 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | COTTONWOOD | PJM->LTFIMP_COTTONWOOD | CLTF | 0.52 MW | 0.52 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | HAMLET | PJM->LTFIMP_HAMLET | CLTF | 0.03 MW | 0.03 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | CPLE | LTFEXP_CPLE->PJM | CLTF | 0.26 MW | 0.26 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | CATAWBA | PJM->LTFIMP_CATAWBA | CLTF | 0.05 MW | 0.05 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | PRAIRIE | PJM->LTFIMP_PRAIRIE | CLTF | 0.76 MW | 0.76 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | TRIMBLE | PJM->LTFIMP_TRIMBLE | CLTF | 0.18 MW | 0.18 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | BlueGrass | PJM->LTFIMP_BlueG | CLTF | 0.55 MW | 0.55 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 3.02 MW | 3.02 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | MDU | PJM->LTFIMP_MDU | CLTF | 0.03 MW | 0.03 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.12 MW | 0.12 MW |
| 8YADKIN-8SUFFOLK 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 579_SRT-S-1 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.31 MW | 0.31 MW |
| Details for 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 964801 | AG1-343 C | Adder | 2.24 MW | 1.9 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 964802 | AG1-343 E | Adder | 1.76 MW | 1.49 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965291 | AG1-394 C | Adder | 0.77 MW | 0.65 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965292 | AG1-394 E | Adder | 0.51 MW | 0.43 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314541 | 3WATKINS | Adder | 0.28 MW | 0.24 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 920042 | AA2-088 E OP | Adder | 4.02 MW | 3.42 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934521 | AD1-076 C | Adder | 5.16 MW | 4.38 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934522 | AD1-076 E | Adder | 2.63 MW | 2.23 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 900672 | V4-068 E | Adder | 0.13 MW | 0.11 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 940492 | AE2-034 E | Adder | 1.36 MW | 1.16 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957521 | AF2-046 C | Adder | 6.32 MW | 5.37 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957522 | AF2-046 E | Adder | 3.18 MW | 2.7 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957531 | AF2-047 C | Adder | 7.54 MW | 6.41 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957532 | AF2-047 E | Adder | 3.79 MW | 3.22 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314539 | 3UNCAMP | Adder | 2.57 MW | 2.18 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 916042 | Z1-036 E | Adder | 13.59 MW | 11.55 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 938771 | AE1-103 C | Adder | 1.26 MW | 1.07 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 938772 | AE1-103 E | Adder | 1.74 MW | 1.48 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314421 | 6WINCHST | 50/50 | 0.1 MW | 0.1 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314507 | 3THOMPSN | Adder | 1.04 MW | 0.88 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314525 | 6KINGFORK | Adder | 0.55 MW | 0.47 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314550 | 6HICKORY | Adder | 1.12 MW | 0.95 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315092 | 1YORKTN3 | 50/50 | 139.18 MW | 139.18 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 926662 | AC1-147 E | Adder | 0.68 MW | 0.58 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 926755 | AC1-161 E | 50/50 | 7.36 MW | 7.36 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 935112 | AD1-144 E | Adder | 0.51 MW | 0.43 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 936591 | AD2-074 C | Adder | -4.75 MW | -4.04 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 942341 | AE2-247 C | Adder | 0.58 MW | 0.5 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 942342 | AE2-247 E | Adder | 0.81 MW | 0.69 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 943461 | AF1-017 C | Adder | 0.53 MW | 0.45 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 943462 | AF1-017 E | Adder | 0.86 MW | 0.73 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 943612 | AF1-032 E | Adder | 0.47 MW | 0.4 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 943741 | AF1-042 C | Adder | -2.49 MW | -2.12 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944871 | AF1-152 C | Adder | 2.6 MW | 2.21 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944872 | AF1-152 E | Adder | 1.73 MW | 1.47 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315233 | 1SURRY 2 | 50/50 | 13.85 MW | 13.85 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315260 | 1GOSPORTA | Adder | 1.09 MW | 0.93 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315261 | 1GOSPORTB | Adder | 1.4 MW | 1.19 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315262 | 1GOSPORTC | Adder | 1.18 MW | 1.01 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315611 | 6Z1-036WIND | Adder | 3.22 MW | 2.74 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 913392 | Y1-086 E | Adder | 1.1 MW | 0.93 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 916192 | Z1-068 E | Adder | 0.97 MW | 0.82 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 923832 | AB2-022 E | Adder | 0.62 MW | 0.53 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 939312 | AE1-162 E | Adder | 0.68 MW | 0.58 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957492 | AF2-043 E | Adder | 0.73 MW | 0.62 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 962962 | AG1-145 E | 50/50 | 0.91 MW | 0.91 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 901082 | W1-029 E | Adder | 15.66 MW | 13.31 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 917122 | Z2-027 E | Adder | 0.67 MW | 0.57 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 925522 | AC1-027 E | Adder | 0.63 MW | 0.53 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941501 | AE2-147 C | Adder | 7.78 MW | 6.62 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941502 | AE2-147 E | Adder | 5.19 MW | 4.41 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957871 | AF2-081 C | Adder | 5.09 MW | 4.32 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957872 | AF2-081 E | Adder | 2.18 MW | 1.85 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 958161 | AF2-110 C | Adder | 0.65 MW | 0.55 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 958162 | AF2-110 E | Adder | 1.03 MW | 0.87 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 933291 | AC2-141 C | 50/50 | 17.24 MW | 17.24 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 933292 | AC2-141 E | 50/50 | 7.36 MW | 7.36 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 939411 | AE1-173 C | Adder | 34.53 MW | 29.35 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 939412 | AE1-173 E | Adder | 23.02 MW | 19.57 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 933981 | AD1-022 C | Adder | 3.61 MW | 3.07 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 933982 | AD1-022 E | Adder | 1.97 MW | 1.67 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 961681 | AG1-008 C | Adder | 6.33 MW | 5.38 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 961682 | AG1-008 E | Adder | 2.99 MW | 2.54 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314594 | 6PLYMOUTH TP | Adder | 0.14 MW | 0.12 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314632 | 6AYDLETT TAP | Adder | 0.69 MW | 0.58 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 316159 | AE1-175 C | 50/50 | 0.21 MW | 0.21 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 316160 | AE1-175 E | 50/50 | 0.75 MW | 0.75 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 316294 | AC1-161 C | 50/50 | 2.38 MW | 2.38 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 316382 | AG1-145 C | 50/50 | 0.19 MW | 0.19 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934065 | AD1-033 E | Adder | 2.58 MW | 2.2 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 937226 | AE2-253 E | Adder | 2.98 MW | 2.54 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 918512 | AA1-065 E OP | Adder | 2.14 MW | 1.82 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 919153 | AA1-139 E2 | Adder | 2.08 MW | 1.77 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 919152 | AA1-139 E1 | Adder | 2.08 MW | 1.77 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 920692 | AA2-178 E | Adder | 1.81 MW | 1.54 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 932046 | AC2-012 E | Adder | 6.72 MW | 5.71 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 316311 | AC2-079 C | Adder | 2.3 MW | 1.96 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 932596 | AC2-079 E | Adder | 3.76 MW | 3.19 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 316349 | AD2-085 C | Adder | 1.35 MW | 1.15 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 936666 | AD2-085 E | Adder | 2.2 MW | 1.87 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 961611 | AG1-000B C | Adder | 6.39 MW | 5.43 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941291 | AE2-123 C | Adder | 15.04 MW | 12.79 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941292 | AE2-123 E | Adder | 58.66 MW | 49.86 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941301 | AE2-124 C | Adder | 13.68 MW | 11.63 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941302 | AE2-124 E | Adder | 60.04 MW | 51.04 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941591 | AE2-156 C | Adder | 9.2 MW | 7.82 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944581 | AF1-123 C | Adder | 25.12 MW | 21.36 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944582 | AF1-123 E | Adder | 57.53 MW | 48.9 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944591 | AF1-124 C | Adder | 25.12 MW | 21.36 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944592 | AF1-124 E | Adder | 57.53 MW | 48.9 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944601 | AF1-125 C | Adder | 25.12 MW | 21.36 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944602 | AF1-125 E | Adder | 57.53 MW | 48.9 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 945361 | AF1-201 C | Adder | 7.52 MW | 6.39 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 945362 | AF1-201 E | Adder | 5.02 MW | 4.26 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 964951 | AG1-359 C | Adder | 11.77 MW | 10.01 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965001 | AG1-364 C | Adder | 3.68 MW | 3.13 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965002 | AG1-364 E | Adder | 5.52 MW | 4.69 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965691 | AG1-437 C | Adder | 4.11 MW | 3.49 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965692 | AG1-437 E | Adder | 2.74 MW | 2.33 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965701 | AG1-438 C | Adder | 4.11 MW | 3.49 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965702 | AG1-438 E | Adder | 2.74 MW | 2.33 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965741 | AG1-442 C | Adder | 2.4 MW | 2.04 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965751 | AG1-443 C | Adder | 2.4 MW | 2.04 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 966611 | AG1-531 C | 50/50 | 4.09 MW | 4.09 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 966612 | AG1-531 E | 50/50 | 2.73 MW | 2.73 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934501 | AD1-074 C | Adder | 14.2 MW | 12.07 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934502 | AD1-074 E | Adder | 7.23 MW | 6.14 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934511 | AD1-075 C | Adder | 3.55 MW | 3.02 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934512 | AD1-075 E | Adder | 1.81 MW | 1.54 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 938531 | AE1-072 C | Adder | 8.91 MW | 7.58 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 938532 | AE1-072 E | Adder | 4.65 MW | 3.95 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 939601 | AE1-190 C | Adder | -1.6 MW | -1.36 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 940641 | AE2-051 C | Adder | 5.83 MW | 4.96 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 940642 | AE2-051 E | Adder | 3.89 MW | 3.3 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941101 | AE2-104 C | Adder | 1.58 MW | 1.34 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941102 | AE2-104 E | Adder | 2.52 MW | 2.14 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941281 | AE2-122 C | Adder | 14.64 MW | 12.44 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941282 | AE2-122 E | Adder | 59.07 MW | 50.21 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 7.31 MW | 7.31 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 5.39 MW | 5.39 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 24.17 MW | 24.17 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 0.85 MW | 0.85 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | NY | PJM->LTFIMP_NY | CLTF | 0.4 MW | 0.4 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.29 MW | 0.29 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | WEC | LTFEXP_WEC->PJM | CLTF | 0.15 MW | 0.15 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | CPLE | LTFEXP_CPLE->PJM | CLTF | 2.98 MW | 2.98 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | TVA | LTFEXP_TVA->PJM | CLTF | 1.47 MW | 1.47 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | MEC | LTFEXP_MEC->PJM | CLTF | 0.93 MW | 0.93 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | LAGN | LTFEXP_LAGN->PJM | CLTF | 1.87 MW | 1.87 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.06 MW | 0.06 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 5.41 MW | 5.41 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.42 MW | 1.42 MW |
| Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 963041 | AG1-153 C | Adder | 4.36 MW | 3.71 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 963042 | AG1-153 E | Adder | 6.54 MW | 5.56 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 963111 | AG1-160 C | 50/50 | 4.42 MW | 4.42 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 963112 | AG1-160 E | 50/50 | 6.62 MW | 6.62 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 966361 | AG1-505 C | Adder | 13.02 MW | 11.07 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 966362 | AG1-505 E | Adder | 8.68 MW | 7.38 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 966371 | AG1-506 C | Adder | 13.02 MW | 11.07 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 966372 | AG1-506 E | Adder | 8.68 MW | 7.38 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 942931 | AE2-313 C | 50/50 | 28.25 MW | 28.25 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 942932 | AE2-313 E | 50/50 | 18.84 MW | 18.84 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 944011 | AF1-069 C | 50/50 | 10.24 MW | 10.24 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 944012 | AF1-069 E | 50/50 | 3.98 MW | 3.98 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 941031 | AE2-094 C | 50/50 | 31.33 MW | 31.33 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 941032 | AE2-094 E | 50/50 | 14.03 MW | 14.03 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 314250 | 6ROCKVILLE | Adder | 1.62 MW | 1.38 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 314331 | 6POE | Adder | 1.1 MW | 0.94 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 314507 | 3THOMPSN | Adder | 1.62 MW | 1.38 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 315083 | 1SPRUNCA | 50/50 | 7.36 MW | 7.36 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 315084 | 1SPRUNCB | 50/50 | 7.36 MW | 7.36 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 926662 | AC1-147 E | Adder | 1.07 MW | 0.91 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 926755 | AC1-161 E | Adder | 10.47 MW | 8.9 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 315225 | 1N ANNA1 | 50/50 | 40.27 MW | 40.27 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 315226 | 1N ANNA2 | 50/50 | 40.28 MW | 40.28 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 315241 | 1Z1-086 GT1 | 50/50 | 6.96 MW | 6.96 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 315242 | 1Z1-086 GT2 | 50/50 | 6.96 MW | 6.96 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 315243 | 1Z1-086 GT3 | 50/50 | 6.96 MW | 6.96 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 315244 | 1Z1-086 ST | 50/50 | 12.12 MW | 12.12 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 315260 | 1GOSPORTA | Adder | 1.71 MW | 1.46 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 315261 | 1GOSPORTB | Adder | 2.19 MW | 1.86 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 315262 | 1GOSPORTC | Adder | 1.86 MW | 1.58 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 916192 | Z1-068 E | Adder | 1.51 MW | 1.28 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 925022 | AB2-158 E | 50/50 | 4.88 MW | 4.88 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 938552 | AE1-074 E | 50/50 | 1.05 MW | 1.05 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 964271 | AG1-288 C | 50/50 | 26.5 MW | 26.5 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 925522 | AC1-027 E | Adder | 0.98 MW | 0.83 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 942001 | AE2-212 C | Adder | 1.73 MW | 1.47 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 942002 | AE2-212 E | Adder | 1.16 MW | 0.98 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 966331 | AG1-502 C | Adder | 9.23 MW | 7.85 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 966332 | AG1-502 E | Adder | 2.31 MW | 1.96 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 966341 | AG1-503 C | Adder | 2.31 MW | 1.96 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 966342 | AG1-503 E | Adder | 0.58 MW | 0.49 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 933291 | AC2-141 C | Adder | 24.52 MW | 20.84 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 933292 | AC2-141 E | Adder | 10.47 MW | 8.9 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 939411 | AE1-173 C | 50/50 | 72.92 MW | 72.92 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 939412 | AE1-173 E | 50/50 | 48.61 MW | 48.61 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 315085 | 1SPRUNCC | 50/50 | 0.11 MW | 0.11 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 315086 | 1SPRUNCD | 50/50 | 0.11 MW | 0.11 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 316164 | AC1-076_C | 50/50 | 0.69 MW | 0.69 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 316192 | AB2-158 C | 50/50 | 1.56 MW | 1.56 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 316233 | AE1-074 C | 50/50 | 2.08 MW | 2.08 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 926004 | AC1-076_E | 50/50 | 4.68 MW | 4.68 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 316044 | AC1-158 C1 | 50/50 | 12.55 MW | 12.55 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 316045 | AC1-158 C2 | 50/50 | 12.55 MW | 12.55 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 926739 | AC1-158 E1 | 50/50 | 38.52 MW | 38.52 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 926740 | AC1-158 E2 | 50/50 | 38.52 MW | 38.52 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 932046 | AC2-012 E | Adder | 10.55 MW | 8.97 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 941291 | AE2-123 C | Adder | 23.51 MW | 19.99 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 941292 | AE2-123 E | Adder | 91.69 MW | 77.94 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 941301 | AE2-124 C | Adder | 21.38 MW | 18.17 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 941302 | AE2-124 E | Adder | 93.81 MW | 79.74 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 941591 | AE2-156 C | Adder | 14.42 MW | 12.25 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 944581 | AF1-123 C | Adder | 38.7 MW | 32.9 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 944582 | AF1-123 E | Adder | 88.62 MW | 75.32 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 944591 | AF1-124 C | Adder | 38.7 MW | 32.9 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 944592 | AF1-124 E | Adder | 88.62 MW | 75.32 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 944601 | AF1-125 C | Adder | 38.7 MW | 32.9 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 944602 | AF1-125 E | Adder | 88.62 MW | 75.32 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 957431 | AF2-037 C | 50/50 | 12.33 MW | 12.33 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 957432 | AF2-037 E | 50/50 | 8.22 MW | 8.22 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 957691 | AF2-063 C | 50/50 | 19.67 MW | 19.67 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 957692 | AF2-063 E | 50/50 | 13.11 MW | 13.11 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 962841 | AG1-133 C | 50/50 | 18.78 MW | 18.78 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 962842 | AG1-133 E | 50/50 | 12.52 MW | 12.52 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 963291 | AG1-178 C | 50/50 | 50.29 MW | 50.29 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 963351 | AG1-184 C | 50/50 | 27.09 MW | 27.09 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 964281 | AG1-289 C | 50/50 | 14.66 MW | 14.66 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 964421 | AG1-305 C | 50/50 | 15.47 MW | 15.47 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 964422 | AG1-305 E | 50/50 | 10.32 MW | 10.32 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 964951 | AG1-359 C | Adder | 8.91 MW | 7.58 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 965001 | AG1-364 C | Adder | 5.77 MW | 4.9 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 965002 | AG1-364 E | Adder | 8.65 MW | 7.35 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 965811 | AG1-449 C | 50/50 | 18.3 MW | 18.3 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 939191 | AE1-149 C | Adder | 8.65 MW | 7.35 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 939192 | AE1-149 E | Adder | 5.76 MW | 4.9 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 940641 | AE2-051 C | 50/50 | 13.91 MW | 13.91 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 940642 | AE2-051 E | 50/50 | 9.27 MW | 9.27 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 940651 | AE2-052 C | Adder | 2.88 MW | 2.45 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 941281 | AE2-122 C | Adder | 22.88 MW | 19.45 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 941282 | AE2-122 E | Adder | 92.32 MW | 78.47 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | 316303 | AF2-085 | 50/50 | 3.29 MW | 3.29 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 18.2 MW | 18.2 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 15.53 MW | 15.53 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 69.25 MW | 69.25 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 4.3 MW | 4.3 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | NY | PJM->LTFIMP_NY | CLTF | 2.06 MW | 2.06 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.82 MW | 0.82 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | WEC | LTFEXP_WEC->PJM | CLTF | 0.4 MW | 0.4 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | CPLE | LTFEXP_CPLE->PJM | CLTF | 8.21 MW | 8.21 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | TVA | LTFEXP_TVA->PJM | CLTF | 4.38 MW | 4.38 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | MEC | LTFEXP_MEC->PJM | CLTF | 2.56 MW | 2.56 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | LAGN | LTFEXP_LAGN->PJM | CLTF | 5.48 MW | 5.48 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.16 MW | 0.16 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 27.41 MW | 27.41 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 3.91 MW | 3.91 MW |
| Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 314541 | 3WATKINS | Adder | 0.69 MW | 0.59 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 934521 | AD1-076 C | Adder | 12.73 MW | 10.82 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 934522 | AD1-076 E | Adder | 6.49 MW | 5.51 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 940492 | AE2-034 E | Adder | 3.34 MW | 2.84 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 957531 | AF2-047 C | Adder | 18.55 MW | 15.77 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 957532 | AF2-047 E | Adder | 9.33 MW | 7.93 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 314539 | 3UNCAMP | Adder | 6.28 MW | 5.33 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 916042 | Z1-036 E | Adder | 33.26 MW | 28.27 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 938771 | AE1-103 C | Adder | 3.08 MW | 2.61 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 938772 | AE1-103 E | Adder | 4.25 MW | 3.61 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 314295 | 6BIRDNECK | 50/50 | 0.05 MW | 0.05 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 314507 | 3THOMPSN | Adder | 2.55 MW | 2.17 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 314525 | 6KINGFORK | Adder | 1.17 MW | 0.99 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 314550 | 6HICKORY | 50/50 | 2.8 MW | 2.8 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 315092 | 1YORKTN3 | Adder | 147.28 MW | 125.19 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 926662 | AC1-147 E | Adder | 1.68 MW | 1.43 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 926755 | AC1-161 E | 50/50 | 19.91 MW | 19.91 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 935112 | AD1-144 E | Adder | 1.08 MW | 0.92 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 942341 | AE2-247 C | Adder | 1.46 MW | 1.24 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 942342 | AE2-247 E | Adder | 2.01 MW | 1.71 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 943461 | AF1-017 C | Adder | 1.32 MW | 1.12 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 943462 | AF1-017 E | Adder | 2.15 MW | 1.83 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 943612 | AF1-032 E | Adder | 1.12 MW | 0.95 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 944871 | AF1-152 C | Adder | 6.31 MW | 5.37 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 944872 | AF1-152 E | Adder | 4.21 MW | 3.58 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 315099 | 1CHESPKB | 50/50 | 0.77 MW | 0.77 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 315108 | 1ELIZAR1 | 50/50 | 3.44 MW | 3.44 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 315109 | 1ELIZAR2 | 50/50 | 3.38 MW | 3.38 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 315110 | 1ELIZAR3 | 50/50 | 3.49 MW | 3.49 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 315233 | 1SURRY 2 | 50/50 | 37.89 MW | 37.89 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 315260 | 1GOSPORTA | Adder | 2.69 MW | 2.29 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 315261 | 1GOSPORTB | Adder | 3.44 MW | 2.92 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 315262 | 1GOSPORTC | Adder | 2.92 MW | 2.48 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 315611 | 6Z1-036WIND | Adder | 7.88 MW | 6.7 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 913392 | Y1-086 E | Adder | 2.7 MW | 2.3 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 916192 | Z1-068 E | 50/50 | 2.4 MW | 2.4 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 923832 | AB2-022 E | Adder | 1.53 MW | 1.3 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 939312 | AE1-162 E | Adder | 1.47 MW | 1.25 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 957492 | AF2-043 E | Adder | 1.73 MW | 1.47 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 901082 | W1-029 E | Adder | 38.09 MW | 32.38 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 917122 | Z2-027 E | Adder | 1.64 MW | 1.39 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 925522 | AC1-027 E | 50/50 | 1.55 MW | 1.55 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 941501 | AE2-147 C | Adder | 18.94 MW | 16.1 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 941502 | AE2-147 E | Adder | 12.63 MW | 10.73 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 957871 | AF2-081 C | Adder | 12.65 MW | 10.75 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 957872 | AF2-081 E | Adder | 5.42 MW | 4.61 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 958161 | AF2-110 C | Adder | 1.55 MW | 1.32 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 958162 | AF2-110 E | Adder | 2.47 MW | 2.1 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 933291 | AC2-141 C | 50/50 | 46.63 MW | 46.63 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 933292 | AC2-141 E | 50/50 | 19.91 MW | 19.91 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 939411 | AE1-173 C | Adder | 91.61 MW | 77.87 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 939412 | AE1-173 E | Adder | 61.07 MW | 51.91 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 933981 | AD1-022 C | Adder | 8.93 MW | 7.59 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 933982 | AD1-022 E | Adder | 4.86 MW | 4.13 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 314594 | 6PLYMOUTH TP | Adder | 0.34 MW | 0.29 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 314632 | 6AYDLETT TAP | Adder | 1.7 MW | 1.45 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 316185 | AD1-033 C | 50/50 | 1.33 MW | 1.33 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 316294 | AC1-161 C | 50/50 | 6.43 MW | 6.43 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 316316 | AC1-027 C | 50/50 | 0.34 MW | 0.34 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 934065 | AD1-033 E | 50/50 | 6.45 MW | 6.45 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 937226 | AE2-253 E | 50/50 | 7.43 MW | 7.43 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 919153 | AA1-139 E2 | Adder | 5.17 MW | 4.4 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 919152 | AA1-139 E1 | Adder | 5.17 MW | 4.4 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 920692 | AA2-178 E | Adder | 4.46 MW | 3.79 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 316375 | AC2-012 C | 50/50 | 1.45 MW | 1.45 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 932046 | AC2-012 E | 50/50 | 16.58 MW | 16.58 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 316311 | AC2-079 C | Adder | 5.71 MW | 4.85 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 932596 | AC2-079 E | Adder | 9.32 MW | 7.92 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 316349 | AD2-085 C | Adder | 3.36 MW | 2.85 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 936666 | AD2-085 E | Adder | 5.48 MW | 4.66 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 316388 | AE2-253 GEN | 50/50 | 2.11 MW | 2.11 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 941291 | AE2-123 C | 50/50 | 37.34 MW | 37.34 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 941292 | AE2-123 E | 50/50 | 145.6 MW | 145.6 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 941301 | AE2-124 C | 50/50 | 33.98 MW | 33.98 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 941302 | AE2-124 E | 50/50 | 149.12 MW | 149.12 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 941591 | AE2-156 C | 50/50 | 22.72 MW | 22.72 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 944581 | AF1-123 C | 50/50 | 63.99 MW | 63.99 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 944582 | AF1-123 E | 50/50 | 146.52 MW | 146.52 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 944591 | AF1-124 C | 50/50 | 63.99 MW | 63.99 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 944592 | AF1-124 E | 50/50 | 146.52 MW | 146.52 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 944601 | AF1-125 C | 50/50 | 63.99 MW | 63.99 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 944602 | AF1-125 E | 50/50 | 146.52 MW | 146.52 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 964951 | AG1-359 C | 50/50 | 29.43 MW | 29.43 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 965001 | AG1-364 C | 50/50 | 9.08 MW | 9.08 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 965002 | AG1-364 E | 50/50 | 13.63 MW | 13.63 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 965691 | AG1-437 C | Adder | 10.17 MW | 8.64 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 965701 | AG1-438 C | Adder | 10.17 MW | 8.64 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 965702 | AG1-438 E | Adder | 1.3 MW | 1.1 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 966611 | AG1-531 C | Adder | 5.54 MW | 4.71 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 966612 | AG1-531 E | Adder | 3.69 MW | 3.14 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 934501 | AD1-074 C | Adder | 35.05 MW | 29.79 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 934502 | AD1-074 E | Adder | 17.84 MW | 15.16 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 934511 | AD1-075 C | Adder | 8.76 MW | 7.45 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 934512 | AD1-075 E | Adder | 4.46 MW | 3.79 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 938531 | AE1-072 C | Adder | 22.13 MW | 18.81 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 938532 | AE1-072 E | Adder | 11.54 MW | 9.81 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 940641 | AE2-051 C | Adder | 15.91 MW | 13.53 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 940642 | AE2-051 E | Adder | 10.61 MW | 9.02 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 941101 | AE2-104 C | Adder | 3.8 MW | 3.23 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 941102 | AE2-104 E | Adder | 6.05 MW | 5.14 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 941281 | AE2-122 C | 50/50 | 36.33 MW | 36.33 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | 941282 | AE2-122 E | 50/50 | 146.61 MW | 146.61 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 15.49 MW | 15.49 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 12.76 MW | 12.76 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 62.28 MW | 62.28 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 2.18 MW | 2.18 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | NY | PJM->LTFIMP_NY | CLTF | 1.03 MW | 1.03 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.63 MW | 0.63 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | WEC | LTFEXP_WEC->PJM | CLTF | 0.33 MW | 0.33 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | CPLE | LTFEXP_CPLE->PJM | CLTF | 7.76 MW | 7.76 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | TVA | LTFEXP_TVA->PJM | CLTF | 3.56 MW | 3.56 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | MEC | LTFEXP_MEC->PJM | CLTF | 2.1 MW | 2.1 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | LAGN | LTFEXP_LAGN->PJM | CLTF | 4.56 MW | 4.56 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.13 MW | 0.13 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 13.88 MW | 13.88 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o Base Case | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 3.7 MW | 3.7 MW |
| Details for 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 961941 | AG1-037 C | Adder | 0.18 MW | 0.15 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 961942 | AG1-037 E | Adder | 0.12 MW | 0.1 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962331 | AG1-082 C | Adder | 0.71 MW | 0.61 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962332 | AG1-082 E | Adder | 0.48 MW | 0.4 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962341 | AG1-083 C | Adder | 0.71 MW | 0.61 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962342 | AG1-083 E | Adder | 0.48 MW | 0.4 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 964801 | AG1-343 C | Adder | 2.16 MW | 1.84 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 964802 | AG1-343 E | Adder | 1.7 MW | 1.45 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 966811 | AG1-552 C | Adder | 0.74 MW | 0.63 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 966812 | AG1-552 E | Adder | 0.35 MW | 0.3 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965291 | AG1-394 C | Adder | 0.74 MW | 0.63 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965292 | AG1-394 E | Adder | 0.5 MW | 0.42 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 966621 | AG1-532 C | Adder | 0.56 MW | 0.47 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 966622 | AG1-532 E | Adder | 0.37 MW | 0.32 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314541 | 3WATKINS | Adder | 0.25 MW | 0.22 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314572 | 3EMPORIA | Adder | 0.17 MW | 0.14 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 918492 | AA1-063AE OP | Adder | 1.47 MW | 1.25 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 919692 | AA2-053 E OP | Adder | 1.51 MW | 1.29 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 920042 | AA2-088 E OP | Adder | 3.86 MW | 3.28 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 943172 | AE2-346 E | Adder | 0.21 MW | 0.18 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 960081 | AF2-299 C | Adder | 1.03 MW | 0.87 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 960082 | AF2-299 E | Adder | 0.69 MW | 0.58 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316141 | AB2-099 E | Adder | 0.09 MW | 0.08 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 900672 | V4-068 E | Adder | 0.13 MW | 0.11 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 923263 | AB1-132 E OP | Adder | 2.37 MW | 2.02 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 923573 | AB1-173 E OP | Adder | 1.24 MW | 1.06 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 946281 | AF1-292 C | Adder | 0.61 MW | 0.52 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 946282 | AF1-292 E | Adder | 0.41 MW | 0.35 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957521 | AF2-046 C | Adder | 6.06 MW | 5.15 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957522 | AF2-046 E | Adder | 3.05 MW | 2.59 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957531 | AF2-047 C | Adder | 5.86 MW | 4.99 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957532 | AF2-047 E | Adder | 0.28 MW | 0.24 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314539 | 3UNCAMP | Adder | 2.24 MW | 1.91 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 916042 | Z1-036 E | Adder | 9.81 MW | 8.34 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 938771 | AE1-103 C | Adder | 1.08 MW | 0.92 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 938772 | AE1-103 E | Adder | 1.5 MW | 1.27 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314314 | 3LOCKS | Adder | 1.04 MW | 0.88 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314331 | 6POE | 50/50 | 1.04 MW | 1.04 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314507 | 3THOMPSN | Adder | 0.7 MW | 0.59 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314525 | 6KINGFORK | Adder | 0.36 MW | 0.31 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314550 | 6HICKORY | Adder | 0.73 MW | 0.62 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315065 | 1CHESTF6 | 50/50 | 22.86 MW | 22.86 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315073 | 1STONECA | 50/50 | 4.57 MW | 4.57 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315076 | 1HOPPOLC | 50/50 | 0.86 MW | 0.86 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315077 | 1HOPHCF1 | 50/50 | 1.36 MW | 1.36 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315078 | 1HOPHCF2 | 50/50 | 1.36 MW | 1.36 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315079 | 1HOPHCF3 | 50/50 | 1.36 MW | 1.36 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315080 | 1HOPHCF4 | 50/50 | 2.07 MW | 2.07 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 926662 | AC1-147 E | Adder | 0.46 MW | 0.39 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 927226 | AC1-216 E | Adder | 4.2 MW | 3.57 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 935112 | AD1-144 E | Adder | 0.34 MW | 0.28 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 942162 | AE2-228 E | 50/50 | 1.58 MW | 1.58 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 942341 | AE2-247 C | Adder | 0.67 MW | 0.57 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 942342 | AE2-247 E | Adder | 0.93 MW | 0.79 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 943461 | AF1-017 C | Adder | 0.61 MW | 0.52 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 943462 | AF1-017 E | Adder | 0.99 MW | 0.84 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 943612 | AF1-032 E | Adder | 0.32 MW | 0.27 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944871 | AF1-152 C | Adder | 1.8 MW | 1.53 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944872 | AF1-152 E | Adder | 1.2 MW | 1.02 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315260 | 1GOSPORTA | Adder | 0.73 MW | 0.62 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315261 | 1GOSPORTB | Adder | 0.94 MW | 0.8 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315262 | 1GOSPORTC | Adder | 0.8 MW | 0.68 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315611 | 6Z1-036WIND | Adder | 2.32 MW | 1.98 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316108 | AB2-160 C | 50/50 | 3.15 MW | 3.15 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316109 | AB2-160 E | 50/50 | 5.13 MW | 5.13 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316132 | AB2-190 C | 50/50 | 2.33 MW | 2.33 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 913392 | Y1-086 E | Adder | 0.74 MW | 0.63 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 916192 | Z1-068 E | Adder | 0.64 MW | 0.54 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 923832 | AB2-022 E | Adder | 0.42 MW | 0.36 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 923852 | AB2-025 E | Adder | 0.58 MW | 0.49 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 939312 | AE1-162 E | Adder | 0.58 MW | 0.49 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 946262 | AF1-291 E | 50/50 | 1.61 MW | 1.61 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957492 | AF2-043 E | Adder | 0.49 MW | 0.42 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 901082 | W1-029 E | Adder | 10.89 MW | 9.26 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 917122 | Z2-027 E | Adder | 0.46 MW | 0.39 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 925332 | AB2-190 E | 50/50 | 4.77 MW | 4.77 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 925522 | AC1-027 E | Adder | 0.41 MW | 0.35 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941501 | AE2-147 C | Adder | 5.42 MW | 4.6 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941502 | AE2-147 E | Adder | 3.61 MW | 3.07 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 942001 | AE2-212 C | 50/50 | 2.07 MW | 2.07 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 942002 | AE2-212 E | 50/50 | 1.38 MW | 1.38 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957871 | AF2-081 C | Adder | 3.36 MW | 2.86 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957872 | AF2-081 E | Adder | 1.44 MW | 1.23 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 958161 | AF2-110 C | Adder | 0.51 MW | 0.43 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 958162 | AF2-110 E | Adder | 0.81 MW | 0.69 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 926071 | AC1-086 C | Adder | 8.15 MW | 6.93 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 926072 | AC1-086 E | Adder | 3.71 MW | 3.15 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 934011 | AD1-025 C | Adder | 9.17 MW | 7.8 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 934012 | AD1-025 E | Adder | 5.43 MW | 4.62 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962572 | AG1-106 E | Adder | 1.03 MW | 0.87 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 961681 | AG1-008 C | Adder | 6.07 MW | 5.16 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 961682 | AG1-008 E | Adder | 3.04 MW | 2.58 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962571 | AG1-106 C | Adder | 2.27 MW | 1.93 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314632 | 6AYDLETT TAP | Adder | 0.46 MW | 0.39 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316240 | AF1-291 C | 50/50 | 2.42 MW | 2.42 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316301 | AE2-228 C | 50/50 | 2.37 MW | 2.37 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 924516 | AB2-100 E1 | Adder | 1.25 MW | 1.07 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 924517 | AB2-100 E2 | Adder | 1.25 MW | 1.07 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 934065 | AD1-033 E | Adder | 1.68 MW | 1.43 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 937226 | AE2-253 E | Adder | 1.96 MW | 1.67 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963221 | AG1-171 C | Adder | 1.17 MW | 0.99 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963222 | AG1-171 E | Adder | 0.78 MW | 0.66 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963231 | AG1-172 C | Adder | 1.17 MW | 0.99 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963232 | AG1-172 E | Adder | 0.78 MW | 0.66 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963241 | AG1-173 C | Adder | 1.17 MW | 0.99 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963242 | AG1-173 E | Adder | 0.78 MW | 0.66 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963251 | AG1-174 C | Adder | 1.17 MW | 0.99 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963252 | AG1-174 E | Adder | 0.78 MW | 0.66 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 918512 | AA1-065 E OP | Adder | 1.93 MW | 1.64 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 919153 | AA1-139 E2 | Adder | 1.38 MW | 1.17 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 919152 | AA1-139 E1 | Adder | 1.38 MW | 1.17 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316181 | AB2-040 GEN | Adder | 2.85 MW | 2.42 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 923994 | AB2-040_E | Adder | 2.33 MW | 1.98 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 924814 | AB2-134 E | Adder | 6.87 MW | 5.84 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316084 | AB2-161 E | Adder | 3.14 MW | 2.67 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316088 | AB2-174 E | Adder | 2.51 MW | 2.13 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 932046 | AC2-012 E | Adder | 4.51 MW | 3.83 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316311 | AC2-079 C | Adder | 2.53 MW | 2.15 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 932596 | AC2-079 E | Adder | 4.13 MW | 3.51 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 934576 | AD1-082 E | Adder | 2.5 MW | 2.13 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316349 | AD2-085 C | Adder | 1.55 MW | 1.32 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 936666 | AD2-085 E | Adder | 2.53 MW | 2.15 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 961611 | AG1-000B C | Adder | 7.5 MW | 6.38 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941291 | AE2-123 C | Adder | 9.92 MW | 8.43 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941292 | AE2-123 E | Adder | 38.69 MW | 32.89 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941301 | AE2-124 C | Adder | 9.01 MW | 7.66 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941302 | AE2-124 E | Adder | 39.53 MW | 33.6 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941591 | AE2-156 C | Adder | 6.15 MW | 5.23 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 942371 | AE2-250 C | 50/50 | 5.59 MW | 5.59 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 942372 | AE2-250 E | 50/50 | 2.95 MW | 2.95 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 942551 | AE2-270 C | Adder | 14.59 MW | 12.4 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944581 | AF1-123 C | Adder | 15.73 MW | 13.37 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944582 | AF1-123 E | Adder | 36.02 MW | 30.61 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944591 | AF1-124 C | Adder | 15.73 MW | 13.37 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944592 | AF1-124 E | Adder | 36.02 MW | 30.61 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944601 | AF1-125 C | Adder | 15.73 MW | 13.37 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944602 | AF1-125 E | Adder | 36.02 MW | 30.61 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 946011 | AF1-266 C | Adder | 6.65 MW | 5.65 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957711 | AF2-065 C | Adder | 7.44 MW | 6.33 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957712 | AF2-065 E | Adder | 7.15 MW | 6.08 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 961711 | AG1-011 C | Adder | 15.58 MW | 13.24 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962271 | AG1-075 C | 50/50 | 9.65 MW | 9.65 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962272 | AG1-075 E | 50/50 | 5.88 MW | 5.88 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 964951 | AG1-359 C | Adder | 7.66 MW | 6.51 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965001 | AG1-364 C | Adder | 2.46 MW | 2.09 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965002 | AG1-364 E | Adder | 3.69 MW | 3.14 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965281 | AG1-393 C | 50/50 | 1.24 MW | 1.24 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965282 | AG1-393 E | 50/50 | 0.83 MW | 0.83 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 966611 | AG1-531 C | Adder | 2.16 MW | 1.84 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 966612 | AG1-531 E | Adder | 1.44 MW | 1.23 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 313764 | 3SOCKMAN | Adder | 0.26 MW | 0.22 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 935161 | AD1-151 C | Adder | 9.17 MW | 7.8 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 935162 | AD1-151 E | Adder | 6.12 MW | 5.2 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 938531 | AE1-072 C | Adder | 5.92 MW | 5.03 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 938532 | AE1-072 E | Adder | 3.09 MW | 2.62 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 939191 | AE1-149 C | 50/50 | 6.96 MW | 6.96 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 939192 | AE1-149 E | 50/50 | 4.64 MW | 4.64 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 940431 | AE2-027 C | Adder | 6.92 MW | 5.89 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 940432 | AE2-027 E | Adder | 4.62 MW | 3.92 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 940481 | AE2-033 C | Adder | 7.94 MW | 6.75 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 940482 | AE2-033 E | Adder | 5.36 MW | 4.55 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 940541 | AE2-040 C | Adder | 1.43 MW | 1.22 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 940651 | AE2-052 C | 50/50 | 2.32 MW | 2.32 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941101 | AE2-104 C | Adder | 1.25 MW | 1.07 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941102 | AE2-104 E | Adder | 2.0 MW | 1.7 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941281 | AE2-122 C | Adder | 9.65 MW | 8.21 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941282 | AE2-122 E | Adder | 38.96 MW | 33.11 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944641 | AF1-129 C | 50/50 | 119.22 MW | 119.22 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 6.63 MW | 6.63 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 5.23 MW | 5.23 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 24.7 MW | 24.7 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 0.88 MW | 0.88 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | NY | PJM->LTFIMP_NY | CLTF | 0.41 MW | 0.41 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.27 MW | 0.27 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | WEC | LTFEXP_WEC->PJM | CLTF | 0.14 MW | 0.14 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CPLE | LTFEXP_CPLE->PJM | CLTF | 3.07 MW | 3.07 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | TVA | LTFEXP_TVA->PJM | CLTF | 1.45 MW | 1.45 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | MEC | LTFEXP_MEC->PJM | CLTF | 0.88 MW | 0.88 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | LAGN | LTFEXP_LAGN->PJM | CLTF | 1.85 MW | 1.85 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.05 MW | 0.05 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 5.59 MW | 5.59 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.46 MW | 1.46 MW |
| Details for 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 961941 | AG1-037 C | Adder | 0.18 MW | 0.15 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 961942 | AG1-037 E | Adder | 0.12 MW | 0.1 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962331 | AG1-082 C | Adder | 0.71 MW | 0.61 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962332 | AG1-082 E | Adder | 0.48 MW | 0.4 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962341 | AG1-083 C | Adder | 0.71 MW | 0.61 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962342 | AG1-083 E | Adder | 0.48 MW | 0.4 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 964801 | AG1-343 C | Adder | 2.16 MW | 1.84 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 964802 | AG1-343 E | Adder | 1.7 MW | 1.45 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 966811 | AG1-552 C | Adder | 0.74 MW | 0.63 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 966812 | AG1-552 E | Adder | 0.35 MW | 0.3 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965291 | AG1-394 C | Adder | 0.74 MW | 0.63 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965292 | AG1-394 E | Adder | 0.5 MW | 0.42 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 966621 | AG1-532 C | Adder | 0.56 MW | 0.47 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 966622 | AG1-532 E | Adder | 0.37 MW | 0.32 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314541 | 3WATKINS | Adder | 0.25 MW | 0.22 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314572 | 3EMPORIA | Adder | 0.17 MW | 0.14 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 918492 | AA1-063AE OP | Adder | 1.47 MW | 1.25 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 919692 | AA2-053 E OP | Adder | 1.51 MW | 1.29 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 920042 | AA2-088 E OP | Adder | 3.86 MW | 3.28 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 943172 | AE2-346 E | Adder | 0.21 MW | 0.18 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 960081 | AF2-299 C | Adder | 1.03 MW | 0.87 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 960082 | AF2-299 E | Adder | 0.69 MW | 0.58 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316141 | AB2-099 E | Adder | 0.09 MW | 0.08 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 900672 | V4-068 E | Adder | 0.13 MW | 0.11 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 923263 | AB1-132 E OP | Adder | 2.37 MW | 2.02 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 923573 | AB1-173 E OP | Adder | 1.24 MW | 1.06 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 946281 | AF1-292 C | Adder | 0.61 MW | 0.52 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 946282 | AF1-292 E | Adder | 0.41 MW | 0.35 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957521 | AF2-046 C | Adder | 6.06 MW | 5.15 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957522 | AF2-046 E | Adder | 3.05 MW | 2.59 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957531 | AF2-047 C | Adder | 5.86 MW | 4.99 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957532 | AF2-047 E | Adder | 0.28 MW | 0.24 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314539 | 3UNCAMP | Adder | 2.24 MW | 1.91 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 916042 | Z1-036 E | Adder | 9.81 MW | 8.34 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 938771 | AE1-103 C | Adder | 1.08 MW | 0.92 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 938772 | AE1-103 E | Adder | 1.5 MW | 1.27 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314314 | 3LOCKS | Adder | 1.04 MW | 0.88 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314331 | 6POE | 50/50 | 1.04 MW | 1.04 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314507 | 3THOMPSN | Adder | 0.7 MW | 0.59 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314525 | 6KINGFORK | Adder | 0.36 MW | 0.31 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314550 | 6HICKORY | Adder | 0.73 MW | 0.62 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315065 | 1CHESTF6 | 50/50 | 22.86 MW | 22.86 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315073 | 1STONECA | 50/50 | 4.57 MW | 4.57 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315076 | 1HOPPOLC | 50/50 | 0.86 MW | 0.86 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315077 | 1HOPHCF1 | 50/50 | 1.36 MW | 1.36 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315078 | 1HOPHCF2 | 50/50 | 1.36 MW | 1.36 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315079 | 1HOPHCF3 | 50/50 | 1.36 MW | 1.36 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315080 | 1HOPHCF4 | 50/50 | 2.07 MW | 2.07 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 926662 | AC1-147 E | Adder | 0.46 MW | 0.39 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 927226 | AC1-216 E | Adder | 4.2 MW | 3.57 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 935112 | AD1-144 E | Adder | 0.34 MW | 0.28 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 942162 | AE2-228 E | 50/50 | 1.58 MW | 1.58 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 942341 | AE2-247 C | Adder | 0.67 MW | 0.57 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 942342 | AE2-247 E | Adder | 0.93 MW | 0.79 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 943461 | AF1-017 C | Adder | 0.61 MW | 0.52 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 943462 | AF1-017 E | Adder | 0.99 MW | 0.84 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 943612 | AF1-032 E | Adder | 0.32 MW | 0.27 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944871 | AF1-152 C | Adder | 1.8 MW | 1.53 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944872 | AF1-152 E | Adder | 1.2 MW | 1.02 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315260 | 1GOSPORTA | Adder | 0.73 MW | 0.62 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315261 | 1GOSPORTB | Adder | 0.94 MW | 0.8 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315262 | 1GOSPORTC | Adder | 0.8 MW | 0.68 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315611 | 6Z1-036WIND | Adder | 2.32 MW | 1.98 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316108 | AB2-160 C | 50/50 | 3.15 MW | 3.15 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316109 | AB2-160 E | 50/50 | 5.13 MW | 5.13 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316132 | AB2-190 C | 50/50 | 2.33 MW | 2.33 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 913392 | Y1-086 E | Adder | 0.74 MW | 0.63 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 916192 | Z1-068 E | Adder | 0.64 MW | 0.54 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 923832 | AB2-022 E | Adder | 0.42 MW | 0.36 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 923852 | AB2-025 E | Adder | 0.58 MW | 0.49 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 939312 | AE1-162 E | Adder | 0.58 MW | 0.49 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 946262 | AF1-291 E | 50/50 | 1.61 MW | 1.61 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957492 | AF2-043 E | Adder | 0.49 MW | 0.42 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 901082 | W1-029 E | Adder | 10.89 MW | 9.26 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 917122 | Z2-027 E | Adder | 0.46 MW | 0.39 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 925332 | AB2-190 E | 50/50 | 4.77 MW | 4.77 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 925522 | AC1-027 E | Adder | 0.41 MW | 0.35 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941501 | AE2-147 C | Adder | 5.42 MW | 4.6 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941502 | AE2-147 E | Adder | 3.61 MW | 3.07 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 942001 | AE2-212 C | 50/50 | 2.07 MW | 2.07 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 942002 | AE2-212 E | 50/50 | 1.38 MW | 1.38 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957871 | AF2-081 C | Adder | 3.36 MW | 2.86 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957872 | AF2-081 E | Adder | 1.44 MW | 1.23 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 958161 | AF2-110 C | Adder | 0.51 MW | 0.43 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 958162 | AF2-110 E | Adder | 0.81 MW | 0.69 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 926071 | AC1-086 C | Adder | 8.15 MW | 6.93 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 926072 | AC1-086 E | Adder | 3.71 MW | 3.15 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 934011 | AD1-025 C | Adder | 9.17 MW | 7.8 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 934012 | AD1-025 E | Adder | 5.43 MW | 4.62 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962572 | AG1-106 E | Adder | 1.03 MW | 0.87 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 961681 | AG1-008 C | Adder | 6.07 MW | 5.16 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 961682 | AG1-008 E | Adder | 3.04 MW | 2.58 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962571 | AG1-106 C | Adder | 2.27 MW | 1.93 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314632 | 6AYDLETT TAP | Adder | 0.46 MW | 0.39 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316240 | AF1-291 C | 50/50 | 2.42 MW | 2.42 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316301 | AE2-228 C | 50/50 | 2.37 MW | 2.37 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 924516 | AB2-100 E1 | Adder | 1.25 MW | 1.07 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 924517 | AB2-100 E2 | Adder | 1.25 MW | 1.07 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 934065 | AD1-033 E | Adder | 1.68 MW | 1.43 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 937226 | AE2-253 E | Adder | 1.96 MW | 1.67 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963221 | AG1-171 C | Adder | 1.17 MW | 0.99 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963222 | AG1-171 E | Adder | 0.78 MW | 0.66 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963231 | AG1-172 C | Adder | 1.17 MW | 0.99 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963232 | AG1-172 E | Adder | 0.78 MW | 0.66 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963241 | AG1-173 C | Adder | 1.17 MW | 0.99 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963242 | AG1-173 E | Adder | 0.78 MW | 0.66 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963251 | AG1-174 C | Adder | 1.17 MW | 0.99 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963252 | AG1-174 E | Adder | 0.78 MW | 0.66 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 918512 | AA1-065 E OP | Adder | 1.93 MW | 1.64 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 919153 | AA1-139 E2 | Adder | 1.38 MW | 1.17 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 919152 | AA1-139 E1 | Adder | 1.38 MW | 1.17 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316181 | AB2-040 GEN | Adder | 2.85 MW | 2.42 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 923994 | AB2-040_E | Adder | 2.33 MW | 1.98 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 924814 | AB2-134 E | Adder | 6.87 MW | 5.84 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316084 | AB2-161 E | Adder | 3.14 MW | 2.67 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316088 | AB2-174 E | Adder | 2.51 MW | 2.13 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 932046 | AC2-012 E | Adder | 4.51 MW | 3.83 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316311 | AC2-079 C | Adder | 2.53 MW | 2.15 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 932596 | AC2-079 E | Adder | 4.13 MW | 3.51 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 934576 | AD1-082 E | Adder | 2.5 MW | 2.13 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316349 | AD2-085 C | Adder | 1.55 MW | 1.32 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 936666 | AD2-085 E | Adder | 2.53 MW | 2.15 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 961611 | AG1-000B C | Adder | 7.5 MW | 6.38 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941291 | AE2-123 C | Adder | 9.92 MW | 8.43 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941292 | AE2-123 E | Adder | 38.69 MW | 32.89 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941301 | AE2-124 C | Adder | 9.01 MW | 7.66 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941302 | AE2-124 E | Adder | 39.53 MW | 33.6 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941591 | AE2-156 C | Adder | 6.15 MW | 5.23 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 942371 | AE2-250 C | 50/50 | 5.59 MW | 5.59 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 942372 | AE2-250 E | 50/50 | 2.95 MW | 2.95 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 942551 | AE2-270 C | Adder | 14.59 MW | 12.4 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944581 | AF1-123 C | Adder | 15.73 MW | 13.37 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944582 | AF1-123 E | Adder | 36.02 MW | 30.61 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944591 | AF1-124 C | Adder | 15.73 MW | 13.37 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944592 | AF1-124 E | Adder | 36.02 MW | 30.61 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944601 | AF1-125 C | Adder | 15.73 MW | 13.37 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944602 | AF1-125 E | Adder | 36.02 MW | 30.61 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 946011 | AF1-266 C | Adder | 6.65 MW | 5.65 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957711 | AF2-065 C | Adder | 7.44 MW | 6.33 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957712 | AF2-065 E | Adder | 7.15 MW | 6.08 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 961711 | AG1-011 C | Adder | 15.58 MW | 13.24 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962271 | AG1-075 C | 50/50 | 9.65 MW | 9.65 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962272 | AG1-075 E | 50/50 | 5.88 MW | 5.88 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 964951 | AG1-359 C | Adder | 7.66 MW | 6.51 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965001 | AG1-364 C | Adder | 2.46 MW | 2.09 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965002 | AG1-364 E | Adder | 3.69 MW | 3.14 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965281 | AG1-393 C | 50/50 | 1.24 MW | 1.24 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965282 | AG1-393 E | 50/50 | 0.83 MW | 0.83 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 966611 | AG1-531 C | Adder | 2.16 MW | 1.84 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 966612 | AG1-531 E | Adder | 1.44 MW | 1.23 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 313764 | 3SOCKMAN | Adder | 0.26 MW | 0.22 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 935161 | AD1-151 C | Adder | 9.17 MW | 7.8 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 935162 | AD1-151 E | Adder | 6.12 MW | 5.2 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 938531 | AE1-072 C | Adder | 5.92 MW | 5.03 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 938532 | AE1-072 E | Adder | 3.09 MW | 2.62 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 939191 | AE1-149 C | 50/50 | 6.96 MW | 6.96 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 939192 | AE1-149 E | 50/50 | 4.64 MW | 4.64 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 940431 | AE2-027 C | Adder | 6.92 MW | 5.89 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 940432 | AE2-027 E | Adder | 4.62 MW | 3.92 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 940481 | AE2-033 C | Adder | 7.94 MW | 6.75 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 940482 | AE2-033 E | Adder | 5.36 MW | 4.55 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 940541 | AE2-040 C | Adder | 1.43 MW | 1.22 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 940651 | AE2-052 C | 50/50 | 2.32 MW | 2.32 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941101 | AE2-104 C | Adder | 1.25 MW | 1.07 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941102 | AE2-104 E | Adder | 2.0 MW | 1.7 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941281 | AE2-122 C | Adder | 9.65 MW | 8.21 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941282 | AE2-122 E | Adder | 38.96 MW | 33.11 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944641 | AF1-129 C | 50/50 | 119.22 MW | 119.22 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 6.63 MW | 6.63 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 5.23 MW | 5.23 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 24.7 MW | 24.7 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 0.88 MW | 0.88 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | NY | PJM->LTFIMP_NY | CLTF | 0.41 MW | 0.41 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.27 MW | 0.27 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | WEC | LTFEXP_WEC->PJM | CLTF | 0.14 MW | 0.14 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CPLE | LTFEXP_CPLE->PJM | CLTF | 3.07 MW | 3.07 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | TVA | LTFEXP_TVA->PJM | CLTF | 1.45 MW | 1.45 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | MEC | LTFEXP_MEC->PJM | CLTF | 0.88 MW | 0.88 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | LAGN | LTFEXP_LAGN->PJM | CLTF | 1.85 MW | 1.85 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.05 MW | 0.05 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 5.59 MW | 5.59 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.46 MW | 1.46 MW |
| Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 963041 | AG1-153 C | 50/50 | 7.24 MW | 7.24 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 963042 | AG1-153 E | 50/50 | 10.86 MW | 10.86 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 963111 | AG1-160 C | 50/50 | 7.34 MW | 7.34 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 963112 | AG1-160 E | 50/50 | 11.0 MW | 11.0 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 966361 | AG1-505 C | 50/50 | 21.49 MW | 21.49 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 966362 | AG1-505 E | 50/50 | 14.32 MW | 14.32 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 966371 | AG1-506 C | 50/50 | 21.49 MW | 21.49 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 966372 | AG1-506 E | 50/50 | 14.32 MW | 14.32 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 966621 | AG1-532 C | 50/50 | 1.58 MW | 1.58 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 966622 | AG1-532 E | 50/50 | 1.05 MW | 1.05 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 315153 | 1CLOVER1 | 50/50 | 12.85 MW | 12.85 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 315154 | 1CLOVER2 | 50/50 | 12.73 MW | 12.73 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 942931 | AE2-313 C | 50/50 | 46.98 MW | 46.98 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 942932 | AE2-313 E | 50/50 | 31.32 MW | 31.32 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 944011 | AF1-069 C | 50/50 | 17.06 MW | 17.06 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 944012 | AF1-069 E | 50/50 | 6.63 MW | 6.63 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 960081 | AF2-299 C | 50/50 | 2.93 MW | 2.93 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 960082 | AF2-299 E | 50/50 | 1.95 MW | 1.95 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 941031 | AE2-094 C | 50/50 | 52.22 MW | 52.22 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 941032 | AE2-094 E | 50/50 | 23.39 MW | 23.39 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 946281 | AF1-292 C | 50/50 | 1.75 MW | 1.75 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 946282 | AF1-292 E | 50/50 | 1.16 MW | 1.16 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 957481 | AF2-042 C | 50/50 | 65.78 MW | 65.78 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 957482 | AF2-042 E | 50/50 | 43.86 MW | 43.86 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 314295 | 6BIRDNECK | 50/50 | 0.04 MW | 0.04 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 314331 | 6POE | 50/50 | 1.51 MW | 1.51 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 314550 | 6HICKORY | 50/50 | 2.38 MW | 2.38 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 926755 | AC1-161 E | 50/50 | 14.11 MW | 14.11 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 958502 | AF2-144 E | 50/50 | 1.42 MW | 1.42 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 315102 | 1BRUNSWICKG1 | 50/50 | 9.02 MW | 9.02 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 315103 | 1BRUNSWICKG2 | 50/50 | 9.02 MW | 9.02 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 315104 | 1BRUNSWICKG3 | 50/50 | 9.02 MW | 9.02 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 315105 | 1BRUNSWICKS1 | 50/50 | 18.73 MW | 18.73 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 315241 | 1Z1-086 GT1 | 50/50 | 11.56 MW | 11.56 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 315242 | 1Z1-086 GT2 | 50/50 | 11.56 MW | 11.56 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 315243 | 1Z1-086 GT3 | 50/50 | 11.56 MW | 11.56 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 315244 | 1Z1-086 ST | 50/50 | 20.12 MW | 20.12 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 916192 | Z1-068 E | 50/50 | 2.05 MW | 2.05 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 923852 | AB2-025 E | 50/50 | 1.36 MW | 1.36 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 923862 | AB2-026 E | 50/50 | 1.45 MW | 1.45 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 938552 | AE1-074 E | 50/50 | 1.52 MW | 1.52 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 938562 | AE1-075 E | 50/50 | 1.24 MW | 1.24 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 925522 | AC1-027 E | 50/50 | 1.32 MW | 1.32 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 957871 | AF2-081 C | 50/50 | 10.9 MW | 10.9 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 957872 | AF2-081 E | 50/50 | 4.67 MW | 4.67 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 933291 | AC2-141 C | 50/50 | 33.06 MW | 33.06 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 933292 | AC2-141 E | 50/50 | 14.11 MW | 14.11 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 939411 | AE1-173 C | 50/50 | 113.44 MW | 113.44 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 939412 | AE1-173 E | 50/50 | 75.63 MW | 75.63 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 316023 | AB2-100 C2 | 50/50 | 0.93 MW | 0.93 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 316185 | AD1-033 C | 50/50 | 1.13 MW | 1.13 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 316233 | AE1-074 C | 50/50 | 3.01 MW | 3.01 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 316258 | AE1-075 C | 50/50 | 0.35 MW | 0.35 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 316294 | AC1-161 C | 50/50 | 4.56 MW | 4.56 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 316313 | AB2-026 C | 50/50 | 0.38 MW | 0.38 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 316315 | AB2-025 C | 50/50 | 0.4 MW | 0.4 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 316316 | AC1-027 C | 50/50 | 0.29 MW | 0.29 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 316365 | AB2-100 C1 | 50/50 | 0.93 MW | 0.93 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 316405 | AF2-144 C | 50/50 | 0.29 MW | 0.29 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 924516 | AB2-100 E1 | 50/50 | 3.31 MW | 3.31 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 924517 | AB2-100 E2 | 50/50 | 3.31 MW | 3.31 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 934065 | AD1-033 E | 50/50 | 5.47 MW | 5.47 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 937226 | AE2-253 E | 50/50 | 6.37 MW | 6.37 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 316017 | AA1-139 ULT1 | 50/50 | 1.0 MW | 1.0 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 316018 | AA1-139 ULT2 | 50/50 | 1.0 MW | 1.0 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 919153 | AA1-139 E2 | 50/50 | 4.46 MW | 4.46 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 919152 | AA1-139 E1 | 50/50 | 4.46 MW | 4.46 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 316388 | AE2-253 GEN | 50/50 | 1.81 MW | 1.81 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 941291 | AE2-123 C | 50/50 | 31.83 MW | 31.83 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 941292 | AE2-123 E | 50/50 | 124.11 MW | 124.11 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 941301 | AE2-124 C | 50/50 | 28.95 MW | 28.95 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 941302 | AE2-124 E | 50/50 | 127.03 MW | 127.03 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 944581 | AF1-123 C | 50/50 | 52.7 MW | 52.7 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 944582 | AF1-123 E | 50/50 | 120.68 MW | 120.68 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 944591 | AF1-124 C | 50/50 | 52.7 MW | 52.7 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 944592 | AF1-124 E | 50/50 | 120.68 MW | 120.68 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 944601 | AF1-125 C | 50/50 | 52.7 MW | 52.7 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 944602 | AF1-125 E | 50/50 | 120.68 MW | 120.68 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 946011 | AF1-266 C | 50/50 | 15.85 MW | 15.85 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 963291 | AG1-178 C | 50/50 | 81.95 MW | 81.95 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 963351 | AG1-184 C | 50/50 | 44.15 MW | 44.15 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 964951 | AG1-359 C | 50/50 | 24.92 MW | 24.92 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 965811 | AG1-449 C | 50/50 | 30.42 MW | 30.42 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 934611 | AD1-087 C | 50/50 | 1.26 MW | 1.26 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 934612 | AD1-087 E | 50/50 | 4.32 MW | 4.32 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 935171 | AD1-152 C | 50/50 | 1.3 MW | 1.3 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 935172 | AD1-152 E | 50/50 | 6.36 MW | 6.36 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 937481 | AD2-202 C | 50/50 | 0.37 MW | 0.37 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 937482 | AD2-202 E | 50/50 | 1.26 MW | 1.26 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 940481 | AE2-033 C | 50/50 | 18.94 MW | 18.94 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 940482 | AE2-033 E | 50/50 | 12.77 MW | 12.77 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 940541 | AE2-040 C | 50/50 | 3.37 MW | 3.37 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 940641 | AE2-051 C | 50/50 | 22.49 MW | 22.49 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 940642 | AE2-051 E | 50/50 | 14.99 MW | 14.99 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 941281 | AE2-122 C | 50/50 | 30.97 MW | 30.97 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 941282 | AE2-122 E | 50/50 | 124.96 MW | 124.96 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 945811 | AF1-246 C | 50/50 | 9.21 MW | 9.21 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 945812 | AF1-246 E | 50/50 | 12.72 MW | 12.72 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | 316303 | AF2-085 | 50/50 | 5.35 MW | 5.35 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 43.37 MW | 43.37 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 28.28 MW | 28.28 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 109.7 MW | 109.7 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 4.56 MW | 4.56 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | NY | PJM->LTFIMP_NY | CLTF | 2.09 MW | 2.09 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | LGEE | LTFEXP_LGEE->PJM | CLTF | 1.72 MW | 1.72 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | WEC | LTFEXP_WEC->PJM | CLTF | 0.89 MW | 0.89 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | CPLE | LTFEXP_CPLE->PJM | CLTF | 12.92 MW | 12.92 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | TVA | LTFEXP_TVA->PJM | CLTF | 7.47 MW | 7.47 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | MEC | LTFEXP_MEC->PJM | CLTF | 5.21 MW | 5.21 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | LAGN | LTFEXP_LAGN->PJM | CLTF | 9.43 MW | 9.43 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.33 MW | 0.33 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 29.02 MW | 29.02 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 6.16 MW | 6.16 MW |
| Details for AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 314507 | 3THOMPSN | Adder | 0.76 MW | 0.65 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 314525 | 6KINGFORK | Adder | 0.42 MW | 0.35 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 314550 | 6HICKORY | Adder | 0.68 MW | 0.58 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 926662 | AC1-147 E | Adder | 0.5 MW | 0.42 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 927226 | AC1-216 E | Adder | 2.2 MW | 1.87 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 935112 | AD1-144 E | Adder | 0.39 MW | 0.33 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 943612 | AF1-032 E | Adder | 0.28 MW | 0.24 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 944871 | AF1-152 C | Adder | 1.51 MW | 1.28 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 944872 | AF1-152 E | Adder | 1.0 MW | 0.85 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 315116 | 1SURRY 1 | 50/50 | 21.75 MW | 21.75 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 315117 | 1GRAVELC | 50/50 | 0.76 MW | 0.76 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 315119 | 1GRAVEL3 | 50/50 | 2.21 MW | 2.21 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 315120 | 1GRAVEL4 | 50/50 | 2.24 MW | 2.24 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 315121 | 1GRAVEL5 | 50/50 | 2.21 MW | 2.21 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 315122 | 1GRAVEL6 | 50/50 | 2.23 MW | 2.23 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 315260 | 1GOSPORTA | Adder | 0.8 MW | 0.68 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 315261 | 1GOSPORTB | Adder | 1.03 MW | 0.87 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 315262 | 1GOSPORTC | Adder | 0.87 MW | 0.74 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 316132 | AB2-190 C | 50/50 | 14.35 MW | 14.35 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 913392 | Y1-086 E | Adder | 0.65 MW | 0.55 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 916192 | Z1-068 E | Adder | 0.65 MW | 0.55 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 923832 | AB2-022 E | Adder | 0.37 MW | 0.31 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 939312 | AE1-162 E | 50/50 | 1.13 MW | 1.13 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 957492 | AF2-043 E | Adder | 0.43 MW | 0.36 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 901082 | W1-029 E | Adder | 9.08 MW | 7.72 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 917122 | Z2-027 E | Adder | 0.39 MW | 0.33 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 925332 | AB2-190 E | 50/50 | 29.32 MW | 29.32 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 925522 | AC1-027 E | Adder | 0.42 MW | 0.36 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 941501 | AE2-147 C | Adder | 4.52 MW | 3.84 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 941502 | AE2-147 E | Adder | 3.01 MW | 2.56 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 957871 | AF2-081 C | Adder | 3.07 MW | 2.61 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 957872 | AF2-081 E | Adder | 1.32 MW | 1.12 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 934011 | AD1-025 C | Adder | 4.82 MW | 4.09 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 934012 | AD1-025 E | Adder | 2.85 MW | 2.42 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 314632 | 6AYDLETT TAP | Adder | 0.41 MW | 0.35 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 316236 | AE1-162 C | 50/50 | 0.23 MW | 0.23 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 316240 | AF1-291 C | Adder | -0.61 MW | -0.52 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 934065 | AD1-033 E | Adder | 1.6 MW | 1.36 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 937226 | AE2-253 E | Adder | 1.81 MW | 1.54 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 963221 | AG1-171 C | Adder | 0.61 MW | 0.52 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 963222 | AG1-171 E | Adder | 0.41 MW | 0.35 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 963231 | AG1-172 C | Adder | 0.61 MW | 0.52 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 963232 | AG1-172 E | Adder | 0.41 MW | 0.35 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 963241 | AG1-173 C | Adder | 0.61 MW | 0.52 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 963242 | AG1-173 E | Adder | 0.41 MW | 0.35 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 963251 | AG1-174 C | Adder | 0.61 MW | 0.52 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 963252 | AG1-174 E | Adder | 0.41 MW | 0.35 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 919153 | AA1-139 E2 | Adder | 1.26 MW | 1.07 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 919152 | AA1-139 E1 | Adder | 1.26 MW | 1.07 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 924814 | AB2-134 E | Adder | 3.61 MW | 3.07 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 932046 | AC2-012 E | Adder | 4.95 MW | 4.21 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 961611 | AG1-000B C | 50/50 | 23.93 MW | 23.93 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 941291 | AE2-123 C | Adder | 9.97 MW | 8.47 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 941292 | AE2-123 E | Adder | 38.88 MW | 33.05 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 941301 | AE2-124 C | Adder | 8.97 MW | 7.62 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 941302 | AE2-124 E | Adder | 39.35 MW | 33.45 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 941591 | AE2-156 C | Adder | 6.69 MW | 5.69 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 942551 | AE2-270 C | 50/50 | 74.82 MW | 74.82 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 944581 | AF1-123 C | Adder | 13.42 MW | 11.41 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 944582 | AF1-123 E | Adder | 30.73 MW | 26.12 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 944591 | AF1-124 C | Adder | 13.42 MW | 11.41 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 944592 | AF1-124 E | Adder | 30.73 MW | 26.12 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 944601 | AF1-125 C | Adder | 13.42 MW | 11.41 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 944602 | AF1-125 E | Adder | 30.73 MW | 26.12 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 957711 | AF2-065 C | 50/50 | 38.16 MW | 38.16 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 957712 | AF2-065 E | 50/50 | 36.66 MW | 36.66 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 961711 | AG1-011 C | Adder | 8.18 MW | 6.95 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 964951 | AG1-359 C | Adder | 7.2 MW | 6.12 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 965001 | AG1-364 C | Adder | 2.68 MW | 2.28 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 965002 | AG1-364 E | Adder | 4.02 MW | 3.42 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 966611 | AG1-531 C | 50/50 | 3.99 MW | 3.99 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 966612 | AG1-531 E | 50/50 | 2.66 MW | 2.66 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 938531 | AE1-072 C | Adder | 5.37 MW | 4.56 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 938532 | AE1-072 E | Adder | 2.8 MW | 2.38 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 941281 | AE2-122 C | Adder | 9.7 MW | 8.25 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | 941282 | AE2-122 E | Adder | 39.15 MW | 33.28 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 0.63 MW | 0.63 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 5.37 MW | 5.37 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 0.34 MW | 0.34 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | NY | PJM->LTFIMP_NY | CLTF | 0.17 MW | 0.17 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.0 MW | 0.0 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | CPLE | LTFEXP_CPLE->PJM | CLTF | 0.73 MW | 0.73 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | TVA | LTFEXP_TVA->PJM | CLTF | 0.22 MW | 0.22 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | TRIMBLE | PJM->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | MEC | LTFEXP_MEC->PJM | CLTF | 0.05 MW | 0.05 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | LAGN | LTFEXP_LAGN->PJM | CLTF | 0.28 MW | 0.28 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.0 MW | 0.0 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 2.19 MW | 2.19 MW |
| AB2-190 TAP-6GARYSVILLE 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.34 MW | 0.34 MW |
| Details for 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 314507 | 3THOMPSN | Adder | 0.76 MW | 0.65 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 314525 | 6KINGFORK | Adder | 0.42 MW | 0.35 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 314550 | 6HICKORY | Adder | 0.68 MW | 0.58 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 926662 | AC1-147 E | Adder | 0.5 MW | 0.42 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 927226 | AC1-216 E | Adder | 2.2 MW | 1.87 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 935112 | AD1-144 E | Adder | 0.39 MW | 0.33 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 943612 | AF1-032 E | Adder | 0.28 MW | 0.24 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 944871 | AF1-152 C | Adder | 1.51 MW | 1.28 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 944872 | AF1-152 E | Adder | 1.0 MW | 0.85 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 315116 | 1SURRY 1 | 50/50 | 21.75 MW | 21.75 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 315117 | 1GRAVELC | 50/50 | 0.76 MW | 0.76 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 315119 | 1GRAVEL3 | 50/50 | 2.21 MW | 2.21 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 315120 | 1GRAVEL4 | 50/50 | 2.24 MW | 2.24 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 315121 | 1GRAVEL5 | 50/50 | 2.21 MW | 2.21 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 315122 | 1GRAVEL6 | 50/50 | 2.23 MW | 2.23 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 315260 | 1GOSPORTA | Adder | 0.8 MW | 0.68 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 315261 | 1GOSPORTB | Adder | 1.03 MW | 0.87 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 315262 | 1GOSPORTC | Adder | 0.87 MW | 0.74 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 316132 | AB2-190 C | 50/50 | 14.35 MW | 14.35 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 913392 | Y1-086 E | Adder | 0.65 MW | 0.55 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 916192 | Z1-068 E | Adder | 0.65 MW | 0.55 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 923832 | AB2-022 E | Adder | 0.37 MW | 0.31 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 939312 | AE1-162 E | 50/50 | 1.13 MW | 1.13 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 957492 | AF2-043 E | Adder | 0.43 MW | 0.36 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 901082 | W1-029 E | Adder | 9.08 MW | 7.72 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 917122 | Z2-027 E | Adder | 0.39 MW | 0.33 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 925332 | AB2-190 E | 50/50 | 29.32 MW | 29.32 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 925522 | AC1-027 E | Adder | 0.42 MW | 0.36 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 941501 | AE2-147 C | Adder | 4.52 MW | 3.84 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 941502 | AE2-147 E | Adder | 3.01 MW | 2.56 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 957871 | AF2-081 C | Adder | 3.07 MW | 2.61 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 957872 | AF2-081 E | Adder | 1.32 MW | 1.12 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 934011 | AD1-025 C | Adder | 4.82 MW | 4.09 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 934012 | AD1-025 E | Adder | 2.85 MW | 2.42 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 314632 | 6AYDLETT TAP | Adder | 0.41 MW | 0.35 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 316236 | AE1-162 C | 50/50 | 0.23 MW | 0.23 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 316240 | AF1-291 C | Adder | -0.61 MW | -0.52 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 934065 | AD1-033 E | Adder | 1.6 MW | 1.36 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 937226 | AE2-253 E | Adder | 1.81 MW | 1.54 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 963221 | AG1-171 C | Adder | 0.61 MW | 0.52 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 963222 | AG1-171 E | Adder | 0.41 MW | 0.35 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 963231 | AG1-172 C | Adder | 0.61 MW | 0.52 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 963232 | AG1-172 E | Adder | 0.41 MW | 0.35 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 963241 | AG1-173 C | Adder | 0.61 MW | 0.52 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 963242 | AG1-173 E | Adder | 0.41 MW | 0.35 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 963251 | AG1-174 C | Adder | 0.61 MW | 0.52 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 963252 | AG1-174 E | Adder | 0.41 MW | 0.35 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 919153 | AA1-139 E2 | Adder | 1.26 MW | 1.07 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 919152 | AA1-139 E1 | Adder | 1.26 MW | 1.07 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 924814 | AB2-134 E | Adder | 3.61 MW | 3.07 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 932046 | AC2-012 E | Adder | 4.95 MW | 4.21 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 961611 | AG1-000B C | 50/50 | 23.93 MW | 23.93 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 941291 | AE2-123 C | Adder | 9.97 MW | 8.47 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 941292 | AE2-123 E | Adder | 38.88 MW | 33.05 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 941301 | AE2-124 C | Adder | 8.97 MW | 7.62 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 941302 | AE2-124 E | Adder | 39.35 MW | 33.45 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 941591 | AE2-156 C | Adder | 6.69 MW | 5.69 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 942551 | AE2-270 C | 50/50 | 74.82 MW | 74.82 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 944581 | AF1-123 C | Adder | 13.42 MW | 11.41 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 944582 | AF1-123 E | Adder | 30.73 MW | 26.12 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 944591 | AF1-124 C | Adder | 13.42 MW | 11.41 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 944592 | AF1-124 E | Adder | 30.73 MW | 26.12 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 944601 | AF1-125 C | Adder | 13.42 MW | 11.41 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 944602 | AF1-125 E | Adder | 30.73 MW | 26.12 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 957711 | AF2-065 C | 50/50 | 38.16 MW | 38.16 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 957712 | AF2-065 E | 50/50 | 36.66 MW | 36.66 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 961711 | AG1-011 C | Adder | 8.18 MW | 6.95 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 964951 | AG1-359 C | Adder | 7.2 MW | 6.12 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 965001 | AG1-364 C | Adder | 2.68 MW | 2.28 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 965002 | AG1-364 E | Adder | 4.02 MW | 3.42 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 966611 | AG1-531 C | 50/50 | 3.99 MW | 3.99 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 966612 | AG1-531 E | 50/50 | 2.66 MW | 2.66 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 938531 | AE1-072 C | Adder | 5.37 MW | 4.56 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 938532 | AE1-072 E | Adder | 2.8 MW | 2.38 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 941281 | AE2-122 C | Adder | 9.7 MW | 8.25 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | 941282 | AE2-122 E | Adder | 39.15 MW | 33.28 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 0.63 MW | 0.63 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 5.37 MW | 5.37 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 0.34 MW | 0.34 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | NY | PJM->LTFIMP_NY | CLTF | 0.17 MW | 0.17 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.0 MW | 0.0 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | CPLE | LTFEXP_CPLE->PJM | CLTF | 0.73 MW | 0.73 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | TVA | LTFEXP_TVA->PJM | CLTF | 0.22 MW | 0.22 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | TRIMBLE | PJM->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | MEC | LTFEXP_MEC->PJM | CLTF | 0.05 MW | 0.05 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | LAGN | LTFEXP_LAGN->PJM | CLTF | 0.28 MW | 0.28 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.0 MW | 0.0 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 2.19 MW | 2.19 MW |
| 6GARYSVILLE-6HOPEWLL 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.34 MW | 0.34 MW |
| Details for 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 314229 | 6MT RD221 | 50/50 | 0.12 MW | 0.12 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 314250 | 6ROCKVILLE | Adder | 2.27 MW | 1.93 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 314314 | 3LOCKS | Adder | 1.98 MW | 1.68 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 314331 | 6POE | Adder | 1.47 MW | 1.25 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 314507 | 3THOMPSN | Adder | 2.18 MW | 1.86 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315039 | 1LDYSMT3 | 50/50 | 4.57 MW | 4.57 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315040 | 1LDYSMT4 | 50/50 | 4.58 MW | 4.58 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315041 | 1LDYSMT5 | 50/50 | 4.59 MW | 4.59 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315060 | 1CHESTF5 | Adder | 70.7 MW | 60.09 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315065 | 1CHESTF6 | Adder | 21.77 MW | 18.5 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315073 | 1STONECA | Adder | 7.66 MW | 6.51 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315083 | 1SPRUNCA | Adder | 10.13 MW | 8.61 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315084 | 1SPRUNCB | Adder | 10.13 MW | 8.61 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315092 | 1YORKTN3 | Adder | 154.89 MW | 131.65 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 925865 | AC1-065 E | Adder | 18.03 MW | 15.32 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 926412 | AC1-112 E | Adder | 1.26 MW | 1.07 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 926662 | AC1-147 E | Adder | 1.43 MW | 1.22 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 926755 | AC1-161 E | Adder | 14.06 MW | 11.95 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 927226 | AC1-216 E | Adder | 8.51 MW | 7.24 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 934392 | AD1-063 E | Adder | 1.16 MW | 0.99 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 942152 | AE2-227 E | Adder | 1.63 MW | 1.38 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 942162 | AE2-228 E | Adder | 1.59 MW | 1.35 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 960091 | AF2-300 C | 50/50 | 2.5 MW | 2.5 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 960092 | AF2-300 E | 50/50 | 1.67 MW | 1.67 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 966871 | AG1-558 C | Adder | 2.67 MW | 2.27 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 966872 | AG1-558 E | Adder | 1.34 MW | 1.14 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 966881 | AG1-559 C | 50/50 | 2.77 MW | 2.77 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 966882 | AG1-559 E | 50/50 | 1.39 MW | 1.39 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315225 | 1N ANNA1 | 50/50 | 34.08 MW | 34.08 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315226 | 1N ANNA2 | 50/50 | 34.09 MW | 34.09 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315260 | 1GOSPORTA | Adder | 2.3 MW | 1.96 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315261 | 1GOSPORTB | Adder | 2.94 MW | 2.5 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315262 | 1GOSPORTC | Adder | 2.5 MW | 2.12 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 316076 | AC2-137 E | Adder | 1.49 MW | 1.26 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 316108 | AB2-160 C | Adder | 6.01 MW | 5.11 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 316109 | AB2-160 E | Adder | 9.81 MW | 8.34 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 916192 | Z1-068 E | Adder | 2.03 MW | 1.72 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 923842 | AB2-024 E | Adder | 1.95 MW | 1.66 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 930122 | AB1-027 E | Adder | 1.55 MW | 1.32 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 938552 | AE1-074 E | Adder | 1.36 MW | 1.16 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 939312 | AE1-162 E | Adder | 1.56 MW | 1.33 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 946262 | AF1-291 E | Adder | 1.59 MW | 1.35 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 957411 | AF2-035 C | 50/50 | 9.99 MW | 9.99 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 957412 | AF2-035 E | 50/50 | 4.99 MW | 4.99 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 962531 | AG1-102 C | Adder | 1.2 MW | 1.02 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 962532 | AG1-102 E | Adder | 2.5 MW | 2.12 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 962962 | AG1-145 E | Adder | 1.59 MW | 1.35 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 963051 | AG1-154 C | Adder | 4.14 MW | 3.52 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 963052 | AG1-154 E | Adder | 6.22 MW | 5.28 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 964271 | AG1-288 C | 50/50 | 25.01 MW | 25.01 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 925332 | AB2-190 E | Adder | 8.92 MW | 7.58 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 925522 | AC1-027 E | Adder | 1.31 MW | 1.12 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 942001 | AE2-212 C | Adder | 2.37 MW | 2.01 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 942002 | AE2-212 E | Adder | 1.58 MW | 1.34 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 957831 | AF2-077 C | Adder | 2.33 MW | 1.98 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 957832 | AF2-077 E | Adder | 1.56 MW | 1.32 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 313811 | 6ELKO L286 | Adder | 1.55 MW | 1.32 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 933291 | AC2-141 C | Adder | 32.94 MW | 28.0 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 933292 | AC2-141 E | Adder | 14.06 MW | 11.95 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 934011 | AD1-025 C | Adder | 18.6 MW | 15.81 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 934012 | AD1-025 E | Adder | 11.02 MW | 9.37 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 927041 | AC1-191 C | Adder | 10.71 MW | 9.1 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 927042 | AC1-191 E | Adder | 5.33 MW | 4.53 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 313053 | 6PAPERMILL | Adder | 7.2 MW | 6.12 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 316160 | AE1-175 E | Adder | 1.32 MW | 1.12 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 316233 | AE1-074 C | Adder | 2.7 MW | 2.29 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 316240 | AF1-291 C | Adder | 2.39 MW | 2.03 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 316301 | AE2-228 C | Adder | 2.39 MW | 2.03 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 316304 | AE2-227 C | Adder | 2.44 MW | 2.07 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 926785 | AC1-164_E | Adder | 20.17 MW | 17.14 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 963221 | AG1-171 C | Adder | 2.37 MW | 2.01 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 963222 | AG1-171 E | Adder | 1.58 MW | 1.34 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 963231 | AG1-172 C | Adder | 2.37 MW | 2.01 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 963232 | AG1-172 E | Adder | 1.58 MW | 1.34 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 963241 | AG1-173 C | Adder | 2.37 MW | 2.01 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 963242 | AG1-173 E | Adder | 1.58 MW | 1.34 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 963251 | AG1-174 C | Adder | 2.37 MW | 2.01 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 963252 | AG1-174 E | Adder | 1.58 MW | 1.34 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315037 | 1LDYSMT1 | 50/50 | 4.39 MW | 4.39 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315038 | 1LDYSMT2 | 50/50 | 4.45 MW | 4.45 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315051 | AA1-145 CT1 | 50/50 | 4.77 MW | 4.77 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315052 | AA1-145 CT2 | 50/50 | 4.76 MW | 4.76 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 316201 | AC1-065 C | Adder | 10.94 MW | 9.3 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 316427 | AG1-213 C | 50/50 | 0.83 MW | 0.83 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315043 | 1FOUR RIVERA | 50/50 | 2.99 MW | 2.99 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315044 | 1FOUR RIVERB | 50/50 | 2.99 MW | 2.99 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315045 | 1FOUR RIVERC | 50/50 | 3.66 MW | 3.66 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315046 | 1FOUR RIVERD | 50/50 | 2.95 MW | 2.95 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315047 | 1FOUR RIVERE | 50/50 | 2.95 MW | 2.95 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 315048 | 1FOUR RIVERF | 50/50 | 3.6 MW | 3.6 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 924814 | AB2-134 E | Adder | 13.94 MW | 11.85 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 316084 | AB2-161 E | Adder | 6.0 MW | 5.1 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 316044 | AC1-158 C1 | 50/50 | 6.28 MW | 6.28 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 316045 | AC1-158 C2 | 50/50 | 6.28 MW | 6.28 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 926739 | AC1-158 E1 | 50/50 | 19.27 MW | 19.27 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 926740 | AC1-158 E2 | 50/50 | 19.27 MW | 19.27 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 932046 | AC2-012 E | Adder | 14.17 MW | 12.05 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 934576 | AD1-082 E | Adder | 4.78 MW | 4.06 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 961611 | AG1-000B C | Adder | 17.47 MW | 14.85 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 941291 | AE2-123 C | Adder | 8.72 MW | 7.41 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 941292 | AE2-123 E | Adder | 123.01 MW | 104.56 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 941591 | AE2-156 C | Adder | 19.37 MW | 16.46 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 942371 | AE2-250 C | Adder | 10.68 MW | 9.08 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 942372 | AE2-250 E | Adder | 5.64 MW | 4.79 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 942551 | AE2-270 C | Adder | 29.62 MW | 25.18 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 944581 | AF1-123 C | Adder | 51.8 MW | 44.03 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 944582 | AF1-123 E | Adder | 118.61 MW | 100.82 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 944591 | AF1-124 C | Adder | 51.8 MW | 44.03 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 944592 | AF1-124 E | Adder | 118.61 MW | 100.82 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 944601 | AF1-125 C | Adder | 51.8 MW | 44.03 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 944602 | AF1-125 E | Adder | 118.61 MW | 100.82 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 944631 | AF1-128 C | Adder | 44.24 MW | 37.6 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 945361 | AF1-201 C | Adder | 17.56 MW | 14.93 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 945362 | AF1-201 E | Adder | 11.71 MW | 9.95 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 957711 | AF2-065 C | Adder | 15.11 MW | 12.84 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 957712 | AF2-065 E | Adder | 14.51 MW | 12.34 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 961711 | AG1-011 C | Adder | 31.6 MW | 26.86 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 962271 | AG1-075 C | Adder | 18.44 MW | 15.67 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 962272 | AG1-075 E | Adder | 11.24 MW | 9.55 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 962841 | AG1-133 C | 50/50 | 20.87 MW | 20.87 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 962842 | AG1-133 E | 50/50 | 13.91 MW | 13.91 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 964281 | AG1-289 C | 50/50 | 13.83 MW | 13.83 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 965001 | AG1-364 C | Adder | 7.75 MW | 6.58 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 965002 | AG1-364 E | Adder | 11.62 MW | 9.88 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 965281 | AG1-393 C | Adder | 2.37 MW | 2.02 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 965282 | AG1-393 E | Adder | 1.58 MW | 1.34 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 966611 | AG1-531 C | Adder | 6.36 MW | 5.41 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 966612 | AG1-531 E | Adder | 4.24 MW | 3.6 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 935161 | AD1-151 C | Adder | 17.81 MW | 15.14 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 935162 | AD1-151 E | Adder | 11.87 MW | 10.09 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 939191 | AE1-149 C | Adder | 11.7 MW | 9.94 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 939192 | AE1-149 E | Adder | 7.8 MW | 6.63 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 939261 | AE1-157 C | 50/50 | 16.16 MW | 16.16 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 939262 | AE1-157 E | 50/50 | 8.77 MW | 8.77 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 940431 | AE2-027 C | Adder | 14.27 MW | 12.13 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 940432 | AE2-027 E | Adder | 9.52 MW | 8.09 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 940551 | AE2-041 C | Adder | 7.74 MW | 6.58 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 940651 | AE2-052 C | Adder | 3.9 MW | 3.31 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 941282 | AE2-122 E | Adder | 123.86 MW | 105.28 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 942191 | AE2-231 C | 50/50 | 5.49 MW | 5.49 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 942192 | AE2-231 E | 50/50 | 3.66 MW | 3.66 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 943471 | AF1-018 C | Adder | 7.74 MW | 6.58 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 944641 | AF1-129 C | Adder | 113.52 MW | 96.49 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | 963622 | AG1-213 E | 50/50 | 0.83 MW | 0.83 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 29.77 MW | 29.77 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 22.29 MW | 22.29 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 90.58 MW | 90.58 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 5.77 MW | 5.77 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | NY | PJM->LTFIMP_NY | CLTF | 2.73 MW | 2.73 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | LGEE | LTFEXP_LGEE->PJM | CLTF | 1.29 MW | 1.29 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | WEC | LTFEXP_WEC->PJM | CLTF | 0.63 MW | 0.63 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | CPLE | LTFEXP_CPLE->PJM | CLTF | 10.58 MW | 10.58 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | TVA | LTFEXP_TVA->PJM | CLTF | 6.11 MW | 6.11 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | MEC | LTFEXP_MEC->PJM | CLTF | 3.89 MW | 3.89 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | LAGN | LTFEXP_LAGN->PJM | CLTF | 7.63 MW | 7.63 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.25 MW | 0.25 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 36.79 MW | 36.79 MW |
| 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 5.04 MW | 5.04 MW |
| Details for 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 916042 | Z1-036 E | Adder | 11.53 MW | 9.8 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314184 | 3SHACKLE | 50/50 | 0.33 MW | 0.33 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314507 | 3THOMPSN | Adder | 0.88 MW | 0.75 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314525 | 6KINGFORK | Adder | 0.45 MW | 0.38 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314550 | 6HICKORY | Adder | 0.95 MW | 0.8 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315034 | 1NORNECKC1 | 50/50 | 0.41 MW | 0.41 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315060 | 1CHESTF5 | Adder | 32.41 MW | 27.55 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315092 | 1YORKTN3 | Adder | 84.81 MW | 72.09 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 925865 | AC1-065 E | 50/50 | 12.12 MW | 12.12 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 926412 | AC1-112 E | 50/50 | 3.33 MW | 3.33 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 926472 | AC1-118 E | Adder | 0.67 MW | 0.57 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 926662 | AC1-147 E | Adder | 0.58 MW | 0.49 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 926755 | AC1-161 E | Adder | 6.0 MW | 5.1 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 927226 | AC1-216 E | Adder | 3.12 MW | 2.65 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 934392 | AD1-063 E | 50/50 | 0.83 MW | 0.83 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 935112 | AD1-144 E | Adder | 0.42 MW | 0.36 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 936582 | AD2-073 E | Adder | 0.72 MW | 0.61 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 936591 | AD2-074 C | 50/50 | 4.03 MW | 4.03 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 936592 | AD2-074 E | 50/50 | 6.58 MW | 6.58 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 943612 | AF1-032 E | Adder | 0.4 MW | 0.34 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 943741 | AF1-042 C | 50/50 | 2.11 MW | 2.11 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 943742 | AF1-042 E | 50/50 | 3.44 MW | 3.44 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944491 | AF1-114 C | Adder | 2.99 MW | 2.54 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944492 | AF1-114 E | Adder | 4.12 MW | 3.51 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944871 | AF1-152 C | Adder | 2.19 MW | 1.86 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944872 | AF1-152 E | Adder | 1.46 MW | 1.24 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 961951 | AG1-038 C | 50/50 | 2.33 MW | 2.33 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 961952 | AG1-038 E | 50/50 | 3.22 MW | 3.22 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 966661 | AG1-536 C | 50/50 | 3.89 MW | 3.89 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 966662 | AG1-536 E | 50/50 | 5.23 MW | 5.23 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315260 | 1GOSPORTA | Adder | 0.93 MW | 0.79 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315261 | 1GOSPORTB | Adder | 1.19 MW | 1.01 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315262 | 1GOSPORTC | Adder | 1.01 MW | 0.86 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315611 | 6Z1-036WIND | Adder | 2.73 MW | 2.32 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316075 | AC2-137 C | 50/50 | 0.21 MW | 0.21 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316076 | AC2-137 E | 50/50 | 0.89 MW | 0.89 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316078 | AC2-138 E | Adder | 0.66 MW | 0.56 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316156 | AD2-030 C | 50/50 | 0.23 MW | 0.23 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316157 | AD2-030 E | 50/50 | 0.87 MW | 0.87 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 913392 | Y1-086 E | Adder | 0.93 MW | 0.79 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 916192 | Z1-068 E | Adder | 0.82 MW | 0.7 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 923832 | AB2-022 E | Adder | 0.52 MW | 0.45 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 923842 | AB2-024 E | 50/50 | 1.45 MW | 1.45 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 930122 | AB1-027 E | 50/50 | 4.1 MW | 4.1 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 939312 | AE1-162 E | Adder | 0.63 MW | 0.54 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957492 | AF2-043 E | Adder | 0.61 MW | 0.52 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957601 | AF2-054 C | 50/50 | 1.55 MW | 1.55 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957602 | AF2-054 E | 50/50 | 1.03 MW | 1.03 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962531 | AG1-102 C | Adder | 0.73 MW | 0.62 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962532 | AG1-102 E | Adder | 1.52 MW | 1.29 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962861 | AG1-135 C | 50/50 | 4.39 MW | 4.39 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962862 | AG1-135 E | 50/50 | 2.93 MW | 2.93 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962962 | AG1-145 E | 50/50 | 1.05 MW | 1.05 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962971 | AG1-146 C | 50/50 | 2.24 MW | 2.24 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962972 | AG1-146 E | 50/50 | 1.49 MW | 1.49 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962981 | AG1-147 C | 50/50 | 5.23 MW | 5.23 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962982 | AG1-147 E | 50/50 | 3.49 MW | 3.49 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963611 | AG1-210 C | Adder | 0.47 MW | 0.4 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963612 | AG1-210 E | Adder | 0.71 MW | 0.6 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 964211 | AG1-282 C | 50/50 | 1.48 MW | 1.48 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 964212 | AG1-282 E | 50/50 | 0.99 MW | 0.99 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 901082 | W1-029 E | Adder | 13.21 MW | 11.23 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 917122 | Z2-027 E | Adder | 0.56 MW | 0.48 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 925332 | AB2-190 E | Adder | 3.12 MW | 2.65 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 925522 | AC1-027 E | Adder | 0.53 MW | 0.45 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941501 | AE2-147 C | Adder | 6.57 MW | 5.58 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941502 | AE2-147 E | Adder | 4.38 MW | 3.72 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957831 | AF2-077 C | Adder | 1.42 MW | 1.21 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957832 | AF2-077 E | Adder | 0.94 MW | 0.8 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957871 | AF2-081 C | Adder | 4.3 MW | 3.65 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957872 | AF2-081 E | Adder | 1.84 MW | 1.56 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957971 | AF2-091 C | Adder | 1.02 MW | 0.86 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957972 | AF2-091 E | Adder | 1.4 MW | 1.19 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 958161 | AF2-110 C | Adder | 0.56 MW | 0.48 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 958162 | AF2-110 E | Adder | 0.89 MW | 0.76 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 313811 | 6ELKO L286 | 50/50 | 0.93 MW | 0.93 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314181 | 3NORNECK | Adder | 0.63 MW | 0.54 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 933291 | AC2-141 C | Adder | 14.06 MW | 11.95 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 933292 | AC2-141 E | Adder | 6.0 MW | 5.1 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 934011 | AD1-025 C | Adder | 6.82 MW | 5.8 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 934012 | AD1-025 E | Adder | 4.04 MW | 3.44 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 313053 | 6PAPERMILL | 50/50 | 5.31 MW | 5.31 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314632 | 6AYDLETT TAP | Adder | 0.58 MW | 0.49 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316004 | AC1-112 C | 50/50 | 0.82 MW | 0.82 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316059 | AD1-063 C | 50/50 | 0.17 MW | 0.17 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316159 | AE1-175 C | 50/50 | 0.24 MW | 0.24 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316160 | AE1-175 E | 50/50 | 0.87 MW | 0.87 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316169 | AC1-164 GEN | 50/50 | 5.32 MW | 5.32 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316312 | AB1-027 C | 50/50 | 1.32 MW | 1.32 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316314 | AB2-024 C | 50/50 | 0.2 MW | 0.2 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316382 | AG1-145 C | 50/50 | 0.22 MW | 0.22 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 926785 | AC1-164_E | 50/50 | 17.33 MW | 17.33 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 934065 | AD1-033 E | Adder | 2.18 MW | 1.86 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 937226 | AE2-253 E | Adder | 2.52 MW | 2.14 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 939611 | AE1-191 C | 50/50 | 0.84 MW | 0.84 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 939612 | AE1-191 E | 50/50 | 4.15 MW | 4.15 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963221 | AG1-171 C | Adder | 0.87 MW | 0.74 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963222 | AG1-171 E | Adder | 0.58 MW | 0.49 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963231 | AG1-172 C | Adder | 0.87 MW | 0.74 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963232 | AG1-172 E | Adder | 0.58 MW | 0.49 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963241 | AG1-173 C | Adder | 0.87 MW | 0.74 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963242 | AG1-173 E | Adder | 0.58 MW | 0.49 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963251 | AG1-174 C | Adder | 0.87 MW | 0.74 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963252 | AG1-174 E | Adder | 0.58 MW | 0.49 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316201 | AC1-065 C | 50/50 | 7.35 MW | 7.35 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316404 | AE1-155 C | 50/50 | 1.3 MW | 1.3 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 939246 | AE1-155 E | 50/50 | 6.3 MW | 6.3 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 919153 | AA1-139 E2 | Adder | 1.76 MW | 1.49 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 919152 | AA1-139 E1 | Adder | 1.76 MW | 1.49 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 924814 | AB2-134 E | Adder | 5.12 MW | 4.35 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 932046 | AC2-012 E | Adder | 5.74 MW | 4.88 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316311 | AC2-079 C | Adder | 1.64 MW | 1.4 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 932596 | AC2-079 E | Adder | 3.57 MW | 3.03 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316280 | AD1-041 C | 50/50 | 0.53 MW | 0.53 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 934146 | AD1-041 E | 50/50 | 2.59 MW | 2.59 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 961611 | AG1-000B C | Adder | 6.88 MW | 5.84 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941291 | AE2-123 C | Adder | 12.76 MW | 10.85 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941292 | AE2-123 E | Adder | 49.76 MW | 42.29 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941301 | AE2-124 C | Adder | 11.6 MW | 9.86 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941302 | AE2-124 E | Adder | 50.89 MW | 43.26 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941591 | AE2-156 C | Adder | 7.85 MW | 6.67 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 942551 | AE2-270 C | Adder | 10.87 MW | 9.24 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944581 | AF1-123 C | Adder | 21.06 MW | 17.9 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944582 | AF1-123 E | Adder | 48.22 MW | 40.99 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944591 | AF1-124 C | Adder | 21.06 MW | 17.9 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944592 | AF1-124 E | Adder | 48.22 MW | 40.99 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944601 | AF1-125 C | Adder | 21.06 MW | 17.9 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944602 | AF1-125 E | Adder | 48.22 MW | 40.99 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944631 | AF1-128 C | Adder | 20.28 MW | 17.24 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 945361 | AF1-201 C | Adder | 10.31 MW | 8.77 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 945362 | AF1-201 E | Adder | 6.88 MW | 5.84 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957711 | AF2-065 C | Adder | 5.54 MW | 4.71 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957712 | AF2-065 E | Adder | 5.33 MW | 4.53 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 958261 | AF2-120 C | 50/50 | 4.52 MW | 4.52 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 958262 | AF2-120 E | 50/50 | 3.02 MW | 3.02 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 961711 | AG1-011 C | Adder | 11.59 MW | 9.85 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 964951 | AG1-359 C | Adder | 9.94 MW | 8.45 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965001 | AG1-364 C | Adder | 3.14 MW | 2.67 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965002 | AG1-364 E | Adder | 4.71 MW | 4.0 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 966611 | AG1-531 C | Adder | 2.99 MW | 2.54 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 966612 | AG1-531 E | Adder | 1.99 MW | 1.69 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 935161 | AD1-151 C | Adder | 6.37 MW | 5.41 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 935162 | AD1-151 E | Adder | 4.25 MW | 3.61 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 938531 | AE1-072 C | Adder | 7.53 MW | 6.4 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 938532 | AE1-072 E | Adder | 3.92 MW | 3.33 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 939601 | AE1-190 C | 50/50 | 1.56 MW | 1.56 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 939602 | AE1-190 E | 50/50 | 1.04 MW | 1.04 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 940551 | AE2-041 C | 50/50 | 5.56 MW | 5.56 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941101 | AE2-104 C | Adder | 1.37 MW | 1.17 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941102 | AE2-104 E | Adder | 2.18 MW | 1.85 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941281 | AE2-122 C | Adder | 12.42 MW | 10.55 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941282 | AE2-122 E | Adder | 50.1 MW | 42.58 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 943471 | AF1-018 C | 50/50 | 5.56 MW | 5.56 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 3.88 MW | 3.88 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 3.82 MW | 3.82 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 20.48 MW | 20.48 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 0.82 MW | 0.82 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | NY | PJM->LTFIMP_NY | CLTF | 0.39 MW | 0.39 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.16 MW | 0.16 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | WEC | LTFEXP_WEC->PJM | CLTF | 0.08 MW | 0.08 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CPLE | LTFEXP_CPLE->PJM | CLTF | 2.59 MW | 2.59 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | TVA | LTFEXP_TVA->PJM | CLTF | 1.1 MW | 1.1 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | MEC | LTFEXP_MEC->PJM | CLTF | 0.59 MW | 0.59 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | LAGN | LTFEXP_LAGN->PJM | CLTF | 1.41 MW | 1.41 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.04 MW | 0.04 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 5.22 MW | 5.22 MW |
| 6OLDCHRC-6PEARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.23 MW | 1.23 MW |
| Details for 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 314229 | 6MT RD221 | 50/50 | 0.12 MW | 0.12 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 314250 | 6ROCKVILLE | Adder | 2.31 MW | 1.97 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 314314 | 3LOCKS | Adder | 2.02 MW | 1.72 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 314331 | 6POE | Adder | 1.5 MW | 1.27 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 314507 | 3THOMPSN | Adder | 2.23 MW | 1.89 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315039 | 1LDYSMT3 | 50/50 | 4.7 MW | 4.7 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315040 | 1LDYSMT4 | 50/50 | 4.71 MW | 4.71 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315041 | 1LDYSMT5 | 50/50 | 4.72 MW | 4.72 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315060 | 1CHESTF5 | Adder | 72.17 MW | 61.34 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315065 | 1CHESTF6 | Adder | 22.2 MW | 18.87 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315073 | 1STONECA | Adder | 7.81 MW | 6.64 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315083 | 1SPRUNCA | Adder | 10.33 MW | 8.78 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315084 | 1SPRUNCB | Adder | 10.33 MW | 8.78 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315092 | 1YORKTN3 | Adder | 158.08 MW | 134.37 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 925865 | AC1-065 E | Adder | 18.42 MW | 15.66 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 926412 | AC1-112 E | 50/50 | 1.29 MW | 1.29 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 926662 | AC1-147 E | Adder | 1.46 MW | 1.24 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 926755 | AC1-161 E | Adder | 14.34 MW | 12.19 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 927226 | AC1-216 E | Adder | 8.68 MW | 7.38 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 934392 | AD1-063 E | Adder | 1.19 MW | 1.01 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 942152 | AE2-227 E | Adder | 1.66 MW | 1.41 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 942162 | AE2-228 E | Adder | 1.62 MW | 1.38 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 960091 | AF2-300 C | 50/50 | 2.56 MW | 2.56 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 960092 | AF2-300 E | 50/50 | 1.71 MW | 1.71 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 966871 | AG1-558 C | Adder | 2.73 MW | 2.32 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 966872 | AG1-558 E | Adder | 1.37 MW | 1.17 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 966881 | AG1-559 C | 50/50 | 2.84 MW | 2.84 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 966882 | AG1-559 E | 50/50 | 1.43 MW | 1.43 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315225 | 1N ANNA1 | 50/50 | 34.62 MW | 34.62 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315226 | 1N ANNA2 | 50/50 | 34.63 MW | 34.63 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315260 | 1GOSPORTA | Adder | 2.35 MW | 2.0 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315261 | 1GOSPORTB | Adder | 3.0 MW | 2.55 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315262 | 1GOSPORTC | Adder | 2.55 MW | 2.17 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316076 | AC2-137 E | Adder | 1.52 MW | 1.29 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316108 | AB2-160 C | Adder | 6.13 MW | 5.21 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316109 | AB2-160 E | Adder | 10.01 MW | 8.51 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 916192 | Z1-068 E | Adder | 2.07 MW | 1.76 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 923842 | AB2-024 E | Adder | 1.99 MW | 1.69 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 930122 | AB1-027 E | 50/50 | 1.58 MW | 1.58 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 938552 | AE1-074 E | Adder | 1.38 MW | 1.18 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 939312 | AE1-162 E | Adder | 1.59 MW | 1.35 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 946262 | AF1-291 E | Adder | 1.62 MW | 1.38 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 957411 | AF2-035 C | 50/50 | 10.25 MW | 10.25 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 957412 | AF2-035 E | 50/50 | 5.13 MW | 5.13 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 962531 | AG1-102 C | Adder | 1.22 MW | 1.04 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 962532 | AG1-102 E | Adder | 2.55 MW | 2.17 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 962962 | AG1-145 E | Adder | 1.63 MW | 1.38 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 963051 | AG1-154 C | 50/50 | 4.26 MW | 4.26 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 963052 | AG1-154 E | 50/50 | 6.39 MW | 6.39 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 925332 | AB2-190 E | Adder | 9.1 MW | 7.74 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 925522 | AC1-027 E | Adder | 1.34 MW | 1.14 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 942001 | AE2-212 C | Adder | 2.42 MW | 2.05 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 942002 | AE2-212 E | Adder | 1.61 MW | 1.37 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 957831 | AF2-077 C | Adder | 2.38 MW | 2.02 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 957832 | AF2-077 E | Adder | 1.59 MW | 1.35 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 313811 | 6ELKO L286 | Adder | 1.58 MW | 1.35 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 933291 | AC2-141 C | Adder | 33.59 MW | 28.55 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 933292 | AC2-141 E | Adder | 14.34 MW | 12.19 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 934011 | AD1-025 C | Adder | 18.98 MW | 16.13 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 934012 | AD1-025 E | Adder | 11.24 MW | 9.56 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 927041 | AC1-191 C | Adder | 10.95 MW | 9.3 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 927042 | AC1-191 E | Adder | 5.45 MW | 4.63 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 313053 | 6PAPERMILL | Adder | 7.35 MW | 6.25 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316004 | AC1-112 C | 50/50 | 0.32 MW | 0.32 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316160 | AE1-175 E | Adder | 1.34 MW | 1.14 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316233 | AE1-074 C | Adder | 2.75 MW | 2.33 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316240 | AF1-291 C | Adder | 2.44 MW | 2.07 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316301 | AE2-228 C | Adder | 2.43 MW | 2.07 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316304 | AE2-227 C | Adder | 2.49 MW | 2.12 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316312 | AB1-027 C | 50/50 | 0.51 MW | 0.51 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 926785 | AC1-164_E | Adder | 20.6 MW | 17.51 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 963221 | AG1-171 C | Adder | 2.42 MW | 2.06 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 963222 | AG1-171 E | Adder | 1.61 MW | 1.37 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 963231 | AG1-172 C | Adder | 2.42 MW | 2.06 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 963232 | AG1-172 E | Adder | 1.61 MW | 1.37 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 963241 | AG1-173 C | Adder | 2.42 MW | 2.06 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 963242 | AG1-173 E | Adder | 1.61 MW | 1.37 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 963251 | AG1-174 C | Adder | 2.42 MW | 2.06 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 963252 | AG1-174 E | Adder | 1.61 MW | 1.37 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315037 | 1LDYSMT1 | 50/50 | 4.52 MW | 4.52 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315038 | 1LDYSMT2 | 50/50 | 4.58 MW | 4.58 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315051 | AA1-145 CT1 | 50/50 | 4.88 MW | 4.88 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315052 | AA1-145 CT2 | 50/50 | 4.88 MW | 4.88 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316201 | AC1-065 C | Adder | 11.18 MW | 9.5 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316427 | AG1-213 C | 50/50 | 0.85 MW | 0.85 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315043 | 1FOUR RIVERA | 50/50 | 3.06 MW | 3.06 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315044 | 1FOUR RIVERB | 50/50 | 3.06 MW | 3.06 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315045 | 1FOUR RIVERC | 50/50 | 3.74 MW | 3.74 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315046 | 1FOUR RIVERD | 50/50 | 3.02 MW | 3.02 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315047 | 1FOUR RIVERE | 50/50 | 3.02 MW | 3.02 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 315048 | 1FOUR RIVERF | 50/50 | 3.69 MW | 3.69 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 924814 | AB2-134 E | Adder | 14.22 MW | 12.09 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 316084 | AB2-161 E | Adder | 6.12 MW | 5.2 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 932046 | AC2-012 E | Adder | 14.45 MW | 12.29 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 934576 | AD1-082 E | Adder | 4.87 MW | 4.14 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 961611 | AG1-000B C | Adder | 17.82 MW | 15.15 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 941291 | AE2-123 C | Adder | 32.17 MW | 27.34 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 941292 | AE2-123 E | Adder | 125.44 MW | 106.62 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 941302 | AE2-124 E | Adder | 26.24 MW | 22.3 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 941591 | AE2-156 C | Adder | 19.75 MW | 16.79 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 942371 | AE2-250 C | Adder | 10.9 MW | 9.26 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 942372 | AE2-250 E | Adder | 5.75 MW | 4.89 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 942551 | AE2-270 C | Adder | 30.22 MW | 25.69 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 944581 | AF1-123 C | Adder | 52.82 MW | 44.9 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 944582 | AF1-123 E | Adder | 120.95 MW | 102.81 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 944591 | AF1-124 C | Adder | 52.82 MW | 44.9 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 944592 | AF1-124 E | Adder | 120.95 MW | 102.81 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 944601 | AF1-125 C | Adder | 52.82 MW | 44.9 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 944602 | AF1-125 E | Adder | 120.95 MW | 102.81 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 944631 | AF1-128 C | Adder | 45.16 MW | 38.38 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 945361 | AF1-201 C | Adder | 17.94 MW | 15.24 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 945362 | AF1-201 E | Adder | 11.96 MW | 10.16 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 957711 | AF2-065 C | Adder | 15.41 MW | 13.1 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 957712 | AF2-065 E | Adder | 14.81 MW | 12.59 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 961711 | AG1-011 C | Adder | 32.24 MW | 27.4 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 962271 | AG1-075 C | Adder | 18.81 MW | 15.99 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 962272 | AG1-075 E | Adder | 11.46 MW | 9.74 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 962841 | AG1-133 C | 50/50 | 21.28 MW | 21.28 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 962842 | AG1-133 E | 50/50 | 14.19 MW | 14.19 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 965001 | AG1-364 C | Adder | 7.9 MW | 6.71 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 965002 | AG1-364 E | Adder | 11.85 MW | 10.07 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 965281 | AG1-393 C | Adder | 2.42 MW | 2.06 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 965282 | AG1-393 E | Adder | 1.61 MW | 1.37 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 966611 | AG1-531 C | Adder | 6.49 MW | 5.52 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 966612 | AG1-531 E | Adder | 4.33 MW | 3.68 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 935161 | AD1-151 C | Adder | 18.17 MW | 15.45 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 935162 | AD1-151 E | Adder | 12.11 MW | 10.3 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 939191 | AE1-149 C | Adder | 11.93 MW | 10.14 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 939192 | AE1-149 E | Adder | 7.95 MW | 6.76 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 939261 | AE1-157 C | 50/50 | 16.6 MW | 16.6 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 939262 | AE1-157 E | 50/50 | 9.01 MW | 9.01 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 940431 | AE2-027 C | Adder | 14.56 MW | 12.38 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 940432 | AE2-027 E | Adder | 9.71 MW | 8.25 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 940551 | AE2-041 C | Adder | 7.91 MW | 6.72 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 940651 | AE2-052 C | Adder | 3.98 MW | 3.38 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 941281 | AE2-122 C | Adder | 31.3 MW | 26.61 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 941282 | AE2-122 E | Adder | 126.3 MW | 107.36 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 942191 | AE2-231 C | 50/50 | 5.64 MW | 5.64 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 942192 | AE2-231 E | 50/50 | 3.76 MW | 3.76 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 943471 | AF1-018 C | Adder | 7.91 MW | 6.72 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 944641 | AF1-129 C | Adder | 115.8 MW | 98.43 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | 963622 | AG1-213 E | 50/50 | 0.85 MW | 0.85 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 31.31 MW | 31.31 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 22.98 MW | 22.98 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 92.33 MW | 92.33 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 5.67 MW | 5.67 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | NY | PJM->LTFIMP_NY | CLTF | 2.68 MW | 2.68 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | LGEE | LTFEXP_LGEE->PJM | CLTF | 1.34 MW | 1.34 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | WEC | LTFEXP_WEC->PJM | CLTF | 0.66 MW | 0.66 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | CPLE | LTFEXP_CPLE->PJM | CLTF | 10.77 MW | 10.77 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | TVA | LTFEXP_TVA->PJM | CLTF | 6.27 MW | 6.27 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | MEC | LTFEXP_MEC->PJM | CLTF | 4.04 MW | 4.04 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | LAGN | LTFEXP_LAGN->PJM | CLTF | 7.83 MW | 7.83 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.26 MW | 0.26 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 36.11 MW | 36.11 MW |
| 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 5.14 MW | 5.14 MW |
| Details for 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 964801 | AG1-343 C | Adder | 2.24 MW | 1.9 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 964802 | AG1-343 E | Adder | 1.76 MW | 1.49 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965291 | AG1-394 C | Adder | 0.77 MW | 0.65 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965292 | AG1-394 E | Adder | 0.51 MW | 0.43 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314541 | 3WATKINS | Adder | 0.28 MW | 0.24 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 920042 | AA2-088 E OP | Adder | 4.02 MW | 3.42 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934521 | AD1-076 C | Adder | 5.16 MW | 4.38 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934522 | AD1-076 E | Adder | 2.63 MW | 2.23 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 900672 | V4-068 E | Adder | 0.13 MW | 0.11 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 940492 | AE2-034 E | Adder | 1.36 MW | 1.16 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957521 | AF2-046 C | Adder | 6.32 MW | 5.37 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957522 | AF2-046 E | Adder | 3.18 MW | 2.7 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957531 | AF2-047 C | Adder | 7.54 MW | 6.41 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957532 | AF2-047 E | Adder | 3.79 MW | 3.22 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314539 | 3UNCAMP | Adder | 2.57 MW | 2.18 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 916042 | Z1-036 E | Adder | 13.59 MW | 11.55 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 938771 | AE1-103 C | Adder | 1.26 MW | 1.07 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 938772 | AE1-103 E | Adder | 1.74 MW | 1.48 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314421 | 6WINCHST | 50/50 | 0.1 MW | 0.1 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314507 | 3THOMPSN | Adder | 1.04 MW | 0.88 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314525 | 6KINGFORK | Adder | 0.55 MW | 0.47 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314550 | 6HICKORY | Adder | 1.12 MW | 0.95 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315092 | 1YORKTN3 | 50/50 | 139.18 MW | 139.18 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 926662 | AC1-147 E | Adder | 0.68 MW | 0.58 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 926755 | AC1-161 E | 50/50 | 7.36 MW | 7.36 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 935112 | AD1-144 E | Adder | 0.51 MW | 0.43 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 936591 | AD2-074 C | Adder | -4.75 MW | -4.04 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 942341 | AE2-247 C | Adder | 0.58 MW | 0.5 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 942342 | AE2-247 E | Adder | 0.81 MW | 0.69 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 943461 | AF1-017 C | Adder | 0.53 MW | 0.45 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 943462 | AF1-017 E | Adder | 0.86 MW | 0.73 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 943612 | AF1-032 E | Adder | 0.47 MW | 0.4 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 943741 | AF1-042 C | Adder | -2.49 MW | -2.12 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944871 | AF1-152 C | Adder | 2.6 MW | 2.21 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944872 | AF1-152 E | Adder | 1.73 MW | 1.47 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315233 | 1SURRY 2 | 50/50 | 13.85 MW | 13.85 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315260 | 1GOSPORTA | Adder | 1.09 MW | 0.93 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315261 | 1GOSPORTB | Adder | 1.4 MW | 1.19 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315262 | 1GOSPORTC | Adder | 1.18 MW | 1.01 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315611 | 6Z1-036WIND | Adder | 3.22 MW | 2.74 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 913392 | Y1-086 E | Adder | 1.1 MW | 0.93 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 916192 | Z1-068 E | Adder | 0.97 MW | 0.82 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 923832 | AB2-022 E | Adder | 0.62 MW | 0.53 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 939312 | AE1-162 E | Adder | 0.68 MW | 0.58 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957492 | AF2-043 E | Adder | 0.73 MW | 0.62 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 962962 | AG1-145 E | 50/50 | 0.91 MW | 0.91 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 901082 | W1-029 E | Adder | 15.66 MW | 13.31 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 917122 | Z2-027 E | Adder | 0.67 MW | 0.57 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 925522 | AC1-027 E | Adder | 0.63 MW | 0.53 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941501 | AE2-147 C | Adder | 7.78 MW | 6.62 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941502 | AE2-147 E | Adder | 5.19 MW | 4.41 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957871 | AF2-081 C | Adder | 5.09 MW | 4.32 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957872 | AF2-081 E | Adder | 2.18 MW | 1.85 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 958161 | AF2-110 C | Adder | 0.65 MW | 0.55 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 958162 | AF2-110 E | Adder | 1.03 MW | 0.87 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 933291 | AC2-141 C | 50/50 | 17.24 MW | 17.24 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 933292 | AC2-141 E | 50/50 | 7.36 MW | 7.36 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 939411 | AE1-173 C | Adder | 34.53 MW | 29.35 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 939412 | AE1-173 E | Adder | 23.02 MW | 19.57 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 933981 | AD1-022 C | Adder | 3.61 MW | 3.07 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 933982 | AD1-022 E | Adder | 1.97 MW | 1.67 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 961681 | AG1-008 C | Adder | 6.33 MW | 5.38 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 961682 | AG1-008 E | Adder | 2.99 MW | 2.54 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314594 | 6PLYMOUTH TP | Adder | 0.14 MW | 0.12 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314632 | 6AYDLETT TAP | Adder | 0.69 MW | 0.58 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 316159 | AE1-175 C | 50/50 | 0.21 MW | 0.21 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 316160 | AE1-175 E | 50/50 | 0.75 MW | 0.75 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 316294 | AC1-161 C | 50/50 | 2.38 MW | 2.38 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 316382 | AG1-145 C | 50/50 | 0.19 MW | 0.19 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934065 | AD1-033 E | Adder | 2.58 MW | 2.2 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 937226 | AE2-253 E | Adder | 2.98 MW | 2.54 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 918512 | AA1-065 E OP | Adder | 2.14 MW | 1.82 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 919153 | AA1-139 E2 | Adder | 2.08 MW | 1.77 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 919152 | AA1-139 E1 | Adder | 2.08 MW | 1.77 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 920692 | AA2-178 E | Adder | 1.81 MW | 1.54 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 932046 | AC2-012 E | Adder | 6.72 MW | 5.71 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 316311 | AC2-079 C | Adder | 2.3 MW | 1.96 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 932596 | AC2-079 E | Adder | 3.76 MW | 3.19 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 316349 | AD2-085 C | Adder | 1.35 MW | 1.15 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 936666 | AD2-085 E | Adder | 2.2 MW | 1.87 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 961611 | AG1-000B C | Adder | 6.39 MW | 5.43 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941291 | AE2-123 C | Adder | 15.04 MW | 12.79 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941292 | AE2-123 E | Adder | 58.66 MW | 49.86 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941301 | AE2-124 C | Adder | 13.68 MW | 11.63 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941302 | AE2-124 E | Adder | 60.04 MW | 51.04 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941591 | AE2-156 C | Adder | 9.2 MW | 7.82 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944581 | AF1-123 C | Adder | 25.12 MW | 21.36 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944582 | AF1-123 E | Adder | 57.53 MW | 48.9 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944591 | AF1-124 C | Adder | 25.12 MW | 21.36 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944592 | AF1-124 E | Adder | 57.53 MW | 48.9 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944601 | AF1-125 C | Adder | 25.12 MW | 21.36 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944602 | AF1-125 E | Adder | 57.53 MW | 48.9 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 945361 | AF1-201 C | Adder | 7.52 MW | 6.39 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 945362 | AF1-201 E | Adder | 5.02 MW | 4.26 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 964951 | AG1-359 C | Adder | 11.77 MW | 10.01 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965001 | AG1-364 C | Adder | 3.68 MW | 3.13 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965002 | AG1-364 E | Adder | 5.52 MW | 4.69 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965691 | AG1-437 C | Adder | 4.11 MW | 3.49 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965692 | AG1-437 E | Adder | 2.74 MW | 2.33 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965701 | AG1-438 C | Adder | 4.11 MW | 3.49 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965702 | AG1-438 E | Adder | 2.74 MW | 2.33 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965741 | AG1-442 C | Adder | 2.4 MW | 2.04 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965751 | AG1-443 C | Adder | 2.4 MW | 2.04 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 966611 | AG1-531 C | 50/50 | 4.09 MW | 4.09 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 966612 | AG1-531 E | 50/50 | 2.73 MW | 2.73 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934501 | AD1-074 C | Adder | 14.2 MW | 12.07 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934502 | AD1-074 E | Adder | 7.23 MW | 6.14 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934511 | AD1-075 C | Adder | 3.55 MW | 3.02 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 934512 | AD1-075 E | Adder | 1.81 MW | 1.54 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 938531 | AE1-072 C | Adder | 8.91 MW | 7.58 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 938532 | AE1-072 E | Adder | 4.65 MW | 3.95 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 939601 | AE1-190 C | Adder | -1.6 MW | -1.36 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 940641 | AE2-051 C | Adder | 5.83 MW | 4.96 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 940642 | AE2-051 E | Adder | 3.89 MW | 3.3 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941101 | AE2-104 C | Adder | 1.58 MW | 1.34 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941102 | AE2-104 E | Adder | 2.52 MW | 2.14 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941281 | AE2-122 C | Adder | 14.64 MW | 12.44 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941282 | AE2-122 E | Adder | 59.07 MW | 50.21 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 7.31 MW | 7.31 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 5.39 MW | 5.39 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 24.17 MW | 24.17 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 0.85 MW | 0.85 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | NY | PJM->LTFIMP_NY | CLTF | 0.4 MW | 0.4 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.29 MW | 0.29 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | WEC | LTFEXP_WEC->PJM | CLTF | 0.15 MW | 0.15 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | CPLE | LTFEXP_CPLE->PJM | CLTF | 2.98 MW | 2.98 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | TVA | LTFEXP_TVA->PJM | CLTF | 1.47 MW | 1.47 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | MEC | LTFEXP_MEC->PJM | CLTF | 0.93 MW | 0.93 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | LAGN | LTFEXP_LAGN->PJM | CLTF | 1.87 MW | 1.87 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.06 MW | 0.06 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 5.41 MW | 5.41 MW |
| 6WALR209-6LIGH209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.42 MW | 1.42 MW |
| Details for 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 961941 | AG1-037 C | Adder | 0.18 MW | 0.15 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 961942 | AG1-037 E | Adder | 0.12 MW | 0.1 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962331 | AG1-082 C | Adder | 0.71 MW | 0.61 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962332 | AG1-082 E | Adder | 0.48 MW | 0.4 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962341 | AG1-083 C | Adder | 0.71 MW | 0.61 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962342 | AG1-083 E | Adder | 0.48 MW | 0.4 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 964801 | AG1-343 C | Adder | 2.16 MW | 1.84 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 964802 | AG1-343 E | Adder | 1.7 MW | 1.45 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 966811 | AG1-552 C | Adder | 0.74 MW | 0.63 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 966812 | AG1-552 E | Adder | 0.35 MW | 0.3 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965291 | AG1-394 C | Adder | 0.74 MW | 0.63 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965292 | AG1-394 E | Adder | 0.5 MW | 0.42 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 966621 | AG1-532 C | Adder | 0.56 MW | 0.47 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 966622 | AG1-532 E | Adder | 0.37 MW | 0.32 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314541 | 3WATKINS | Adder | 0.25 MW | 0.22 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314572 | 3EMPORIA | Adder | 0.17 MW | 0.14 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 918492 | AA1-063AE OP | Adder | 1.47 MW | 1.25 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 919692 | AA2-053 E OP | Adder | 1.51 MW | 1.29 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 920042 | AA2-088 E OP | Adder | 3.86 MW | 3.28 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 943172 | AE2-346 E | Adder | 0.21 MW | 0.18 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 960081 | AF2-299 C | Adder | 1.03 MW | 0.87 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 960082 | AF2-299 E | Adder | 0.69 MW | 0.58 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316141 | AB2-099 E | Adder | 0.09 MW | 0.08 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 900672 | V4-068 E | Adder | 0.13 MW | 0.11 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 923263 | AB1-132 E OP | Adder | 2.37 MW | 2.02 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 923573 | AB1-173 E OP | Adder | 1.24 MW | 1.06 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 946281 | AF1-292 C | Adder | 0.61 MW | 0.52 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 946282 | AF1-292 E | Adder | 0.41 MW | 0.35 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957521 | AF2-046 C | Adder | 6.06 MW | 5.15 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957522 | AF2-046 E | Adder | 3.05 MW | 2.59 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957531 | AF2-047 C | Adder | 5.86 MW | 4.99 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957532 | AF2-047 E | Adder | 0.28 MW | 0.24 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314539 | 3UNCAMP | Adder | 2.24 MW | 1.91 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 916042 | Z1-036 E | Adder | 9.81 MW | 8.34 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 938771 | AE1-103 C | Adder | 1.08 MW | 0.92 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 938772 | AE1-103 E | Adder | 1.5 MW | 1.27 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314314 | 3LOCKS | Adder | 1.04 MW | 0.88 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314331 | 6POE | 50/50 | 1.04 MW | 1.04 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314507 | 3THOMPSN | Adder | 0.7 MW | 0.59 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314525 | 6KINGFORK | Adder | 0.36 MW | 0.31 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314550 | 6HICKORY | Adder | 0.73 MW | 0.62 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315065 | 1CHESTF6 | 50/50 | 22.86 MW | 22.86 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315073 | 1STONECA | 50/50 | 4.57 MW | 4.57 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315076 | 1HOPPOLC | 50/50 | 0.86 MW | 0.86 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315077 | 1HOPHCF1 | 50/50 | 1.36 MW | 1.36 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315078 | 1HOPHCF2 | 50/50 | 1.36 MW | 1.36 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315079 | 1HOPHCF3 | 50/50 | 1.36 MW | 1.36 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315080 | 1HOPHCF4 | 50/50 | 2.07 MW | 2.07 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 926662 | AC1-147 E | Adder | 0.46 MW | 0.39 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 927226 | AC1-216 E | Adder | 4.2 MW | 3.57 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 935112 | AD1-144 E | Adder | 0.34 MW | 0.28 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 942162 | AE2-228 E | 50/50 | 1.58 MW | 1.58 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 942341 | AE2-247 C | Adder | 0.67 MW | 0.57 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 942342 | AE2-247 E | Adder | 0.93 MW | 0.79 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 943461 | AF1-017 C | Adder | 0.61 MW | 0.52 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 943462 | AF1-017 E | Adder | 0.99 MW | 0.84 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 943612 | AF1-032 E | Adder | 0.32 MW | 0.27 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944871 | AF1-152 C | Adder | 1.8 MW | 1.53 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944872 | AF1-152 E | Adder | 1.2 MW | 1.02 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315260 | 1GOSPORTA | Adder | 0.73 MW | 0.62 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315261 | 1GOSPORTB | Adder | 0.94 MW | 0.8 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315262 | 1GOSPORTC | Adder | 0.8 MW | 0.68 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 315611 | 6Z1-036WIND | Adder | 2.32 MW | 1.98 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316108 | AB2-160 C | 50/50 | 3.15 MW | 3.15 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316109 | AB2-160 E | 50/50 | 5.13 MW | 5.13 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316132 | AB2-190 C | 50/50 | 2.33 MW | 2.33 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 913392 | Y1-086 E | Adder | 0.74 MW | 0.63 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 916192 | Z1-068 E | Adder | 0.64 MW | 0.54 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 923832 | AB2-022 E | Adder | 0.42 MW | 0.36 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 923852 | AB2-025 E | Adder | 0.58 MW | 0.49 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 939312 | AE1-162 E | Adder | 0.58 MW | 0.49 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 946262 | AF1-291 E | 50/50 | 1.61 MW | 1.61 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957492 | AF2-043 E | Adder | 0.49 MW | 0.42 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 901082 | W1-029 E | Adder | 10.89 MW | 9.26 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 917122 | Z2-027 E | Adder | 0.46 MW | 0.39 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 925332 | AB2-190 E | 50/50 | 4.77 MW | 4.77 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 925522 | AC1-027 E | Adder | 0.41 MW | 0.35 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941501 | AE2-147 C | Adder | 5.42 MW | 4.6 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941502 | AE2-147 E | Adder | 3.61 MW | 3.07 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 942001 | AE2-212 C | 50/50 | 2.07 MW | 2.07 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 942002 | AE2-212 E | 50/50 | 1.38 MW | 1.38 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957871 | AF2-081 C | Adder | 3.36 MW | 2.86 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957872 | AF2-081 E | Adder | 1.44 MW | 1.23 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 958161 | AF2-110 C | Adder | 0.51 MW | 0.43 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 958162 | AF2-110 E | Adder | 0.81 MW | 0.69 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 926071 | AC1-086 C | Adder | 8.15 MW | 6.93 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 926072 | AC1-086 E | Adder | 3.71 MW | 3.15 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 934011 | AD1-025 C | Adder | 9.17 MW | 7.8 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 934012 | AD1-025 E | Adder | 5.43 MW | 4.62 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962572 | AG1-106 E | Adder | 1.03 MW | 0.87 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 961681 | AG1-008 C | Adder | 6.07 MW | 5.16 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 961682 | AG1-008 E | Adder | 3.04 MW | 2.58 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962571 | AG1-106 C | Adder | 2.27 MW | 1.93 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 314632 | 6AYDLETT TAP | Adder | 0.46 MW | 0.39 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316240 | AF1-291 C | 50/50 | 2.42 MW | 2.42 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316301 | AE2-228 C | 50/50 | 2.37 MW | 2.37 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 924516 | AB2-100 E1 | Adder | 1.25 MW | 1.07 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 924517 | AB2-100 E2 | Adder | 1.25 MW | 1.07 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 934065 | AD1-033 E | Adder | 1.68 MW | 1.43 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 937226 | AE2-253 E | Adder | 1.96 MW | 1.67 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963221 | AG1-171 C | Adder | 1.17 MW | 0.99 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963222 | AG1-171 E | Adder | 0.78 MW | 0.66 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963231 | AG1-172 C | Adder | 1.17 MW | 0.99 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963232 | AG1-172 E | Adder | 0.78 MW | 0.66 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963241 | AG1-173 C | Adder | 1.17 MW | 0.99 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963242 | AG1-173 E | Adder | 0.78 MW | 0.66 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963251 | AG1-174 C | Adder | 1.17 MW | 0.99 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 963252 | AG1-174 E | Adder | 0.78 MW | 0.66 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 918512 | AA1-065 E OP | Adder | 1.93 MW | 1.64 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 919153 | AA1-139 E2 | Adder | 1.38 MW | 1.17 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 919152 | AA1-139 E1 | Adder | 1.38 MW | 1.17 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316181 | AB2-040 GEN | Adder | 2.85 MW | 2.42 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 923994 | AB2-040_E | Adder | 2.33 MW | 1.98 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 924814 | AB2-134 E | Adder | 6.87 MW | 5.84 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316084 | AB2-161 E | Adder | 3.14 MW | 2.67 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316088 | AB2-174 E | Adder | 2.51 MW | 2.13 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 932046 | AC2-012 E | Adder | 4.51 MW | 3.83 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316311 | AC2-079 C | Adder | 2.53 MW | 2.15 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 932596 | AC2-079 E | Adder | 4.13 MW | 3.51 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 934576 | AD1-082 E | Adder | 2.5 MW | 2.13 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 316349 | AD2-085 C | Adder | 1.55 MW | 1.32 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 936666 | AD2-085 E | Adder | 2.53 MW | 2.15 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 961611 | AG1-000B C | Adder | 7.5 MW | 6.38 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941291 | AE2-123 C | Adder | 9.92 MW | 8.43 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941292 | AE2-123 E | Adder | 38.69 MW | 32.89 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941301 | AE2-124 C | Adder | 9.01 MW | 7.66 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941302 | AE2-124 E | Adder | 39.53 MW | 33.6 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941591 | AE2-156 C | Adder | 6.15 MW | 5.23 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 942371 | AE2-250 C | 50/50 | 5.59 MW | 5.59 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 942372 | AE2-250 E | 50/50 | 2.95 MW | 2.95 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 942551 | AE2-270 C | Adder | 14.59 MW | 12.4 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944581 | AF1-123 C | Adder | 15.73 MW | 13.37 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944582 | AF1-123 E | Adder | 36.02 MW | 30.61 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944591 | AF1-124 C | Adder | 15.73 MW | 13.37 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944592 | AF1-124 E | Adder | 36.02 MW | 30.61 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944601 | AF1-125 C | Adder | 15.73 MW | 13.37 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944602 | AF1-125 E | Adder | 36.02 MW | 30.61 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 946011 | AF1-266 C | Adder | 6.65 MW | 5.65 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957711 | AF2-065 C | Adder | 7.44 MW | 6.33 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 957712 | AF2-065 E | Adder | 7.15 MW | 6.08 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 961711 | AG1-011 C | Adder | 15.58 MW | 13.24 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962271 | AG1-075 C | 50/50 | 9.65 MW | 9.65 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 962272 | AG1-075 E | 50/50 | 5.88 MW | 5.88 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 964951 | AG1-359 C | Adder | 7.66 MW | 6.51 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965001 | AG1-364 C | Adder | 2.46 MW | 2.09 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965002 | AG1-364 E | Adder | 3.69 MW | 3.14 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965281 | AG1-393 C | 50/50 | 1.24 MW | 1.24 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 965282 | AG1-393 E | 50/50 | 0.83 MW | 0.83 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 966611 | AG1-531 C | Adder | 2.16 MW | 1.84 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 966612 | AG1-531 E | Adder | 1.44 MW | 1.23 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 313764 | 3SOCKMAN | Adder | 0.26 MW | 0.22 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 935161 | AD1-151 C | Adder | 9.17 MW | 7.8 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 935162 | AD1-151 E | Adder | 6.12 MW | 5.2 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 938531 | AE1-072 C | Adder | 5.92 MW | 5.03 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 938532 | AE1-072 E | Adder | 3.09 MW | 2.62 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 939191 | AE1-149 C | 50/50 | 6.96 MW | 6.96 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 939192 | AE1-149 E | 50/50 | 4.64 MW | 4.64 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 940431 | AE2-027 C | Adder | 6.92 MW | 5.89 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 940432 | AE2-027 E | Adder | 4.62 MW | 3.92 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 940481 | AE2-033 C | Adder | 7.94 MW | 6.75 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 940482 | AE2-033 E | Adder | 5.36 MW | 4.55 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 940541 | AE2-040 C | Adder | 1.43 MW | 1.22 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 940651 | AE2-052 C | 50/50 | 2.32 MW | 2.32 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941101 | AE2-104 C | Adder | 1.25 MW | 1.07 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941102 | AE2-104 E | Adder | 2.0 MW | 1.7 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941281 | AE2-122 C | Adder | 9.65 MW | 8.21 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 941282 | AE2-122 E | Adder | 38.96 MW | 33.11 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | 944641 | AF1-129 C | 50/50 | 119.22 MW | 119.22 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CBM West 1 | LTFEXP_CBM-W1->PJM | CBM | 6.63 MW | 6.63 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CBM West 2 | LTFEXP_CBM-W2->PJM | CBM | 5.23 MW | 5.23 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CBM South 1 | LTFEXP_CBM-S1->PJM | CBM | 0.0 MW | 0.0 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CBM South 2 | LTFEXP_CBM-S2->PJM | CBM | 24.7 MW | 24.7 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | G-007 | PJM->LTFIMP_G-007 | CMTX_NF | 0.88 MW | 0.88 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | NY | PJM->LTFIMP_NY | CLTF | 0.41 MW | 0.41 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | LGEE | LTFEXP_LGEE->PJM | CLTF | 0.27 MW | 0.27 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | WEC | LTFEXP_WEC->PJM | CLTF | 0.14 MW | 0.14 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | CPLE | LTFEXP_CPLE->PJM | CLTF | 3.07 MW | 3.07 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | TVA | LTFEXP_TVA->PJM | CLTF | 1.45 MW | 1.45 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | MEC | LTFEXP_MEC->PJM | CLTF | 0.88 MW | 0.88 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | LAGN | LTFEXP_LAGN->PJM | CLTF | 1.85 MW | 1.85 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | SIGE | LTFEXP_SIGE->PJM | CLTF | 0.05 MW | 0.05 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | O66 | PJM->LTFIMP_O-066 | CMTX_NF | 5.59 MW | 5.59 MW |
| 6CHARCTY-6LAKESIDE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.46 MW | 1.46 MW |
Winter Peak Analysis
PJM will start performing Winter Peak analysis in Transition Cycle #2.
Winter Potential Congestion due to Local Energy Deliverability
PJM will start performing Winter Peak analysis in Transition Cycle #2.
Light Load Analysis
The Queue Project was evaluated as a 880.0 MW (Capacity 267.5 MW) injection in the Dominion area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential light load period network impacts were as follows:
| Light Load Analysis | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Final Cycle Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | ||
| DVP |
6FENTRES-6THRASHER 230.0 kV Ckt 1 line
314466 to 314508 ckt 1 |
DVP_P1-2: LN 588_SRT-A
CONTINGENCY 'DVP_P1-2: LN 588_SRT-A' OPEN BRANCH FROM BUS 314909 TO BUS 314927 CKT 1 /*8FENTRES 500.0 - 8YADKIN 500.0 END |
Single | AC | 217.92 % | 678.68 | B | 1478.96 | 400.32 | ||
| DVP |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
314747 to 313867 ckt 1 |
DVP_P1-2: LN 534_SRT-L
CONTINGENCY 'DVP_P1-2: LN 534_SRT-L' OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1 /*8DOOMS 500.0 - 8CUNINGHAM 500.0 SET POSTCONTRATING 1663 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM 500.0 - 8FLUVANNAEAS 500.0 SET POSTCONTRATING 1663 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM 500.0 - 8FLUVANNAWES 500.0 SET POSTCONTRATING 4399 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 SET PRECONTRATING 1481 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM 500.0 - 8FLUVANNAEAS 500.0 SET PRECONTRATING 1481 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM 500.0 - 8FLUVANNAWES 500.0 SET PRECONTRATING 4157 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 END |
Single | AC | 157.6 % | 678.68 | B | 1069.57 | 40.16 | ||
| DVP |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
314747 to 313867 ckt 1 |
DVP_P1-2: LN 576_SRT-A
CONTINGENCY 'DVP_P1-2: LN 576_SRT-A' OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN 500.0 - 8NO ANNA 500.0 END |
Single | AC | 155.57 % | 678.68 | B | 1055.81 | 41.3 | ||
| DVP |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
313867 to 313707 ckt 1 |
DVP_P1-2: LN 534_SRT-L
CONTINGENCY 'DVP_P1-2: LN 534_SRT-L' OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1 /*8DOOMS 500.0 - 8CUNINGHAM 500.0 SET POSTCONTRATING 1663 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM 500.0 - 8FLUVANNAEAS 500.0 SET POSTCONTRATING 1663 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM 500.0 - 8FLUVANNAWES 500.0 SET POSTCONTRATING 4399 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 SET PRECONTRATING 1481 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM 500.0 - 8FLUVANNAEAS 500.0 SET PRECONTRATING 1481 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM 500.0 - 8FLUVANNAWES 500.0 SET PRECONTRATING 4157 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 END |
Single | AC | 157.11 % | 678.68 | B | 1066.3 | 40.16 | ||
| DVP |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
313867 to 313707 ckt 1 |
DVP_P1-2: LN 576_SRT-A
CONTINGENCY 'DVP_P1-2: LN 576_SRT-A' OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN 500.0 - 8NO ANNA 500.0 END |
Single | AC | 155.07 % | 678.68 | B | 1052.42 | 41.3 | ||
| DVP |
6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer
314747 to 314744 ckt 1 |
DVP_P1-2: LN 2193_SRT-A
CONTINGENCY 'DVP_P1-2: LN 2193_SRT-A' OPEN BRANCH FROM BUS 313707 TO BUS 313867 CKT 1 /*6FORK UNION 230.0 - 6BREMODIST 230.0 OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1 /*6BREMODIST 230.0 - 6BREMO 230.0 OPEN BUS 313867 /*6BREMODIST 230.0 END |
Single | AC | 156.67 % | 307.38 | B | 481.57 | 18.39 | ||
| DVP |
6THRASHER-6YADKIN 230.0 kV Ckt 1 line
314508 to 314514 ckt 1 |
DVP_P1-2: LN 588_SRT-A
CONTINGENCY 'DVP_P1-2: LN 588_SRT-A' OPEN BRANCH FROM BUS 314909 TO BUS 314927 CKT 1 /*8FENTRES 500.0 - 8YADKIN 500.0 END |
Single | AC | 143.44 % | 818.74 | B | 1174.38 | 250.6 | ||
| DVP |
6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line
313707 to 961060 ckt 1 |
DVP_P1-2: LN 576_SRT-A
CONTINGENCY 'DVP_P1-2: LN 576_SRT-A' OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN 500.0 - 8NO ANNA 500.0 END |
Single | AC | 136.2 % | 661.76 | B | 901.33 | 36.41 | ||
| DVP |
6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line
313707 to 961060 ckt 1 |
DVP_P1-2: LN 534_SRT-L
CONTINGENCY 'DVP_P1-2: LN 534_SRT-L' OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1 /*8DOOMS 500.0 - 8CUNINGHAM 500.0 SET POSTCONTRATING 1663 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM 500.0 - 8FLUVANNAEAS 500.0 SET POSTCONTRATING 1663 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM 500.0 - 8FLUVANNAWES 500.0 SET POSTCONTRATING 4399 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 SET PRECONTRATING 1481 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM 500.0 - 8FLUVANNAEAS 500.0 SET PRECONTRATING 1481 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM 500.0 - 8FLUVANNAWES 500.0 SET PRECONTRATING 4157 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 END |
Single | AC | 128.01 % | 661.76 | B | 847.12 | 35.09 | ||
| DVP |
AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line
961060 to 313373 ckt 1 |
DVP_P1-2: LN 576_SRT-A
CONTINGENCY 'DVP_P1-2: LN 576_SRT-A' OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN 500.0 - 8NO ANNA 500.0 END |
Single | AC | 135.61 % | 661.76 | B | 897.38 | 36.41 | ||
| DVP |
AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line
961060 to 313373 ckt 1 |
DVP_P1-2: LN 534_SRT-L
CONTINGENCY 'DVP_P1-2: LN 534_SRT-L' OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1 /*8DOOMS 500.0 - 8CUNINGHAM 500.0 SET POSTCONTRATING 1663 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM 500.0 - 8FLUVANNAEAS 500.0 SET POSTCONTRATING 1663 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM 500.0 - 8FLUVANNAWES 500.0 SET POSTCONTRATING 4399 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 SET PRECONTRATING 1481 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM 500.0 - 8FLUVANNAEAS 500.0 SET PRECONTRATING 1481 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM 500.0 - 8FLUVANNAWES 500.0 SET PRECONTRATING 4157 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 END |
Single | AC | 127.82 % | 661.76 | B | 845.89 | 35.09 | ||
| DVP |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
314287 to 314276 ckt 1 |
DVP_P1-2: LN 563_SRT-L-1
CONTINGENCY 'DVP_P1-2: LN 563_SRT-L-1' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 SET POSTCONTRATING 3559 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TP 500.0 SET POSTCONTRATING 3559 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA 500.0 - AE2-051 TP 500.0 SET PRECONTRATING 3377 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TP 500.0 SET PRECONTRATING 3377 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA 500.0 - AE2-051 TP 500.0 END |
Single | AC | 135.59 % | 663.64 | B | 899.86 | 41.13 | ||
| DVP |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
314287 to 314276 ckt 1 |
DVP_P1-2: LN 217_SRT-A
CONTINGENCY 'DVP_P1-2: LN 217_SRT-A' OPEN BRANCH FROM BUS 314225 TO BUS 314227 CKT 1 /*6CHARCTY 230.0 - 6LAKESIDE 230.0 OPEN BRANCH FROM BUS 314225 TO BUS 314260 CKT 1 /*6CHARCTY 230.0 - 6VARINA 230.0 OPEN BRANCH FROM BUS 314260 TO BUS 314287 CKT 1 /*6VARINA 230.0 - 6CHESTF B 230.0 OPEN BUS 314225 /*6CHARCTY 230.0 OPEN BUS 314260 /*6VARINA 230.0 END |
Single | AC | 106.06 % | 663.64 | B | 703.86 | 33.4 | ||
| DVP |
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line
313373 to 314765 ckt 1 |
DVP_P1-2: LN 576_SRT-A
CONTINGENCY 'DVP_P1-2: LN 576_SRT-A' OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN 500.0 - 8NO ANNA 500.0 END |
Single | AC | 134.38 % | 661.76 | B | 889.25 | 36.41 | ||
| DVP |
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line
313373 to 314765 ckt 1 |
DVP_P1-2: LN 534_SRT-L
CONTINGENCY 'DVP_P1-2: LN 534_SRT-L' OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1 /*8DOOMS 500.0 - 8CUNINGHAM 500.0 SET POSTCONTRATING 1663 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM 500.0 - 8FLUVANNAEAS 500.0 SET POSTCONTRATING 1663 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM 500.0 - 8FLUVANNAWES 500.0 SET POSTCONTRATING 4399 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 SET PRECONTRATING 1481 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM 500.0 - 8FLUVANNAEAS 500.0 SET PRECONTRATING 1481 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM 500.0 - 8FLUVANNAWES 500.0 SET PRECONTRATING 4157 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 END |
Single | AC | 126.59 % | 661.76 | B | 837.72 | 35.09 | ||
| DVP |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
314765 to 314749 ckt 1 |
DVP_P1-2: LN 576_SRT-A
CONTINGENCY 'DVP_P1-2: LN 576_SRT-A' OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN 500.0 - 8NO ANNA 500.0 END |
Single | AC | 132.71 % | 661.76 | B | 878.23 | 36.41 | ||
| DVP |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
314765 to 314749 ckt 1 |
DVP_P1-2: LN 534_SRT-L
CONTINGENCY 'DVP_P1-2: LN 534_SRT-L' OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1 /*8DOOMS 500.0 - 8CUNINGHAM 500.0 SET POSTCONTRATING 1663 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM 500.0 - 8FLUVANNAEAS 500.0 SET POSTCONTRATING 1663 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM 500.0 - 8FLUVANNAWES 500.0 SET POSTCONTRATING 4399 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 SET PRECONTRATING 1481 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM 500.0 - 8FLUVANNAEAS 500.0 SET PRECONTRATING 1481 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM 500.0 - 8FLUVANNAWES 500.0 SET PRECONTRATING 4157 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 END |
Single | AC | 124.92 % | 661.76 | B | 826.65 | 35.09 | ||
| DVP |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer
314218 to 314908 ckt 2 |
DVP_P1-2: LN 557_SRT-L
CONTINGENCY 'DVP_P1-2: LN 557_SRT-L' OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1 /*8CHCKAHM 500.0 - 8ELMONT 500.0 SET POSTCONTRATING 3300 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 SET PRECONTRATING 3118 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 END |
Single | AC | 113.45 % | 879.84 | B | 998.17 | 76.12 | ||
| DVP |
3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 2 transformer
314666 to 314667 ckt 2 |
DVP_P1-3: 4ALTVSTA-TX#3_SRT-A
CONTINGENCY 'DVP_P1-3: 4ALTVSTA-TX#3_SRT-A' OPEN BRANCH FROM BUS 314666 TO BUS 314667 CKT 1 /*3ALTVSTA 115.0 - 4ALTVSTA 138.0 END |
Single | AC | 112.91 % | 130.47 | B | 147.31 | 8.84 | ||
| DVP |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer
314218 to 314908 ckt 1 |
DVP_P1-2: LN 557_SRT-L
CONTINGENCY 'DVP_P1-2: LN 557_SRT-L' OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1 /*8CHCKAHM 500.0 - 8ELMONT 500.0 SET POSTCONTRATING 3300 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 SET PRECONTRATING 3118 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 END |
Single | AC | 112.65 % | 888.3 | B | 1000.66 | 76.31 | ||
| DVP |
3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 1 transformer
314666 to 314667 ckt 1 |
DVP_P1-3: 4ALTVSTA-TX#4_SRT-A
CONTINGENCY 'DVP_P1-3: 4ALTVSTA-TX#4_SRT-A' OPEN BRANCH FROM BUS 314666 TO BUS 314667 CKT 2 /*3ALTVSTA 115.0 - 4ALTVSTA 138.0 END |
Single | AC | 109.59 % | 126.52 | B | 138.66 | 8.32 | ||
| DVP |
6FENTRES-6POCATY 230.0 kV Ckt 1 line
314466 to 316171 ckt 1 |
DVP_P1-2: LN 588_SRT-A
CONTINGENCY 'DVP_P1-2: LN 588_SRT-A' OPEN BRANCH FROM BUS 314909 TO BUS 314927 CKT 1 /*8FENTRES 500.0 - 8YADKIN 500.0 END |
Single | AC | 106.77 % | 678.68 | B | 724.62 | 203.06 | ||
| DVP |
6POCATY-6LANDSTN 230.0 kV Ckt 1 line
316171 to 314481 ckt 1 |
DVP_P1-2: LN 588_SRT-A
CONTINGENCY 'DVP_P1-2: LN 588_SRT-A' OPEN BRANCH FROM BUS 314909 TO BUS 314927 CKT 1 /*8FENTRES 500.0 - 8YADKIN 500.0 END |
Single | AC | 106.75 % | 678.68 | B | 724.51 | 203.06 | ||
| DVP |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
314924 to 314903 ckt 1 |
DVP_P1-2: LN 563_SRT-L-1
CONTINGENCY 'DVP_P1-2: LN 563_SRT-L-1' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 SET POSTCONTRATING 3559 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TP 500.0 SET POSTCONTRATING 3559 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA 500.0 - AE2-051 TP 500.0 SET PRECONTRATING 3377 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TP 500.0 SET PRECONTRATING 3377 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA 500.0 - AE2-051 TP 500.0 END |
Single | AC | 104.41 % | 2442.12 | B | 2549.9 | 205.74 | ||
| DVP |
6LIGH209-6LANEXA 230.0 kV Ckt 1 line
314391 to 314388 ckt 1 |
DVP_P1-2: LN 567_SRT-A
CONTINGENCY 'DVP_P1-2: LN 567_SRT-A' OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1 /*8CHCKAHM 500.0 - 8SURRY 500.0 END |
Single | AC | 104.08 % | 663.64 | B | 690.74 | 65.13 | ||
| DVP |
6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer
314269 to 314291 ckt 1 |
DVP_P7-1: LN 211-228_SRT-L
CONTINGENCY 'DVP_P7-1: LN 211-228_SRT-L' OPEN BRANCH FROM BUS 314286 TO BUS 314303 CKT 1 /*6CHESTF A 230.0 - 6HOPEWLL 230.0 OPEN BRANCH FROM BUS 314287 TO BUS 314303 CKT 1 /*6CHESTF B 230.0 - 6HOPEWLL 230.0 SET POSTCONTRATING 1012 BRANCH FROM BUS 314269 TO BUS 314303 CKT 1 /*6PRGEORG 230.0 - 6HOPEWLL 230.0 SET PRECONTRATING 908 BRANCH FROM BUS 314269 TO BUS 314303 CKT 1 /*6PRGEORG 230.0 - 6HOPEWLL 230.0 END |
Tower | AC | 119.92 % | 287.5 | C | 344.78 | 20.56 | ||
| DVP |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer
314218 to 314908 ckt 1 |
DVP_P4-2: H2T557_SRT-L
CONTINGENCY 'DVP_P4-2: H2T557_SRT-L' OPEN BRANCH FROM BUS 314218 TO BUS 314908 CKT 2 /*6ELMONT 230.0 - 8ELMONT 500.0 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1 /*8CHCKAHM 500.0 - 8ELMONT 500.0 SET POSTCONTRATING 3300 BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT 500.0 - 8CUNINGHAM 500.0 SET POSTCONTRATING 3300 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 SET PRECONTRATING 3118 BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT 500.0 - 8CUNINGHAM 500.0 SET PRECONTRATING 3118 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 END |
Breaker | AC | 132.17 % | 1065.0 | C | 1407.61 | 116.16 | ||
| DVP |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
314747 to 313867 ckt 1 |
DVP_P4-2: 534T549_SRT-L
CONTINGENCY 'DVP_P4-2: 534T549_SRT-L' OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1 /*8DOOMS 500.0 - 8CUNINGHAM 500.0 OPEN BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 SET POSTCONTRATING 1663 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM 500.0 - 8FLUVANNAEAS 500.0 SET POSTCONTRATING 1663 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM 500.0 - 8FLUVANNAWES 500.0 SET PRECONTRATING 1481 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM 500.0 - 8FLUVANNAEAS 500.0 SET PRECONTRATING 1481 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM 500.0 - 8FLUVANNAWES 500.0 END |
Breaker | AC | 120.25 % | 830.0 | C | 998.05 | 39.49 | ||
| DVP |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
313867 to 313707 ckt 1 |
DVP_P4-2: 534T549_SRT-L
CONTINGENCY 'DVP_P4-2: 534T549_SRT-L' OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1 /*8DOOMS 500.0 - 8CUNINGHAM 500.0 OPEN BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 SET POSTCONTRATING 1663 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM 500.0 - 8FLUVANNAEAS 500.0 SET POSTCONTRATING 1663 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM 500.0 - 8FLUVANNAWES 500.0 SET PRECONTRATING 1481 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM 500.0 - 8FLUVANNAEAS 500.0 SET PRECONTRATING 1481 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM 500.0 - 8FLUVANNAWES 500.0 END |
Breaker | AC | 119.87 % | 830.0 | C | 994.9 | 39.49 | ||
| DVP |
6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line
313707 to 961060 ckt 1 |
DVP_P4-2: 534T564_SRT-L
CONTINGENCY 'DVP_P4-2: 534T564_SRT-L' OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1 /*8DOOMS 500.0 - 8CUNINGHAM 500.0 OPEN BUS 315216 /*1CUNINGA 18.0 OPEN BUS 315219 /*1CUNINGD 22.0 SET POSTCONTRATING 1663 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM 500.0 - 8FLUVANNAEAS 500.0 SET POSTCONTRATING 1663 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM 500.0 - 8FLUVANNAWES 500.0 SET POSTCONTRATING 4399 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 SET PRECONTRATING 1481 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM 500.0 - 8FLUVANNAEAS 500.0 SET PRECONTRATING 1481 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM 500.0 - 8FLUVANNAWES 500.0 SET PRECONTRATING 4157 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 END |
Breaker | AC | 104.65 % | 809.0 | C | 846.63 | 35.24 | ||
| DVP |
6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line
313707 to 961060 ckt 1 |
DVP_P4-2: 57602_SRT-L
CONTINGENCY 'DVP_P4-2: 57602_SRT-L' OPEN BRANCH FROM BUS 314232 TO BUS 314918 CKT 1 /*6NO ANNA 230.0 - 8NO ANNA 500.0 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN 500.0 - 8NO ANNA 500.0 SET POSTCONTRATING 3300 BRANCH FROM BUS 962840 TO BUS 314918 CKT 1 /*AG1-133 TP 500.0 - 8NO ANNA 500.0 SET POSTCONTRATING 3559 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA 500.0 - 8SPOTSYL 500.0 SET PRECONTRATING 3118 BRANCH FROM BUS 962840 TO BUS 314918 CKT 1 /*AG1-133 TP 500.0 - 8NO ANNA 500.0 SET PRECONTRATING 3377 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA 500.0 - 8SPOTSYL 500.0 END |
Breaker | AC | 103.87 % | 809.0 | C | 840.34 | 36.45 | ||
| DVP |
AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line
961060 to 313373 ckt 1 |
DVP_P4-2: 534T564_SRT-L
CONTINGENCY 'DVP_P4-2: 534T564_SRT-L' OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1 /*8DOOMS 500.0 - 8CUNINGHAM 500.0 OPEN BUS 315216 /*1CUNINGA 18.0 OPEN BUS 315219 /*1CUNINGD 22.0 SET POSTCONTRATING 1663 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM 500.0 - 8FLUVANNAEAS 500.0 SET POSTCONTRATING 1663 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM 500.0 - 8FLUVANNAWES 500.0 SET POSTCONTRATING 4399 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 SET PRECONTRATING 1481 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM 500.0 - 8FLUVANNAEAS 500.0 SET PRECONTRATING 1481 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM 500.0 - 8FLUVANNAWES 500.0 SET PRECONTRATING 4157 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 END |
Breaker | AC | 104.0 % | 809.0 | C | 841.37 | 35.24 | ||
| DVP |
AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line
961060 to 313373 ckt 1 |
DVP_P4-2: 57602_SRT-L
CONTINGENCY 'DVP_P4-2: 57602_SRT-L' OPEN BRANCH FROM BUS 314232 TO BUS 314918 CKT 1 /*6NO ANNA 230.0 - 8NO ANNA 500.0 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN 500.0 - 8NO ANNA 500.0 SET POSTCONTRATING 3300 BRANCH FROM BUS 962840 TO BUS 314918 CKT 1 /*AG1-133 TP 500.0 - 8NO ANNA 500.0 SET POSTCONTRATING 3559 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA 500.0 - 8SPOTSYL 500.0 SET PRECONTRATING 3118 BRANCH FROM BUS 962840 TO BUS 314918 CKT 1 /*AG1-133 TP 500.0 - 8NO ANNA 500.0 SET PRECONTRATING 3377 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA 500.0 - 8SPOTSYL 500.0 END |
Breaker | AC | 103.41 % | 809.0 | C | 836.56 | 36.45 | ||
| DVP |
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line
313373 to 314765 ckt 1 |
DVP_P4-2: 534T564_SRT-L
CONTINGENCY 'DVP_P4-2: 534T564_SRT-L' OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1 /*8DOOMS 500.0 - 8CUNINGHAM 500.0 OPEN BUS 315216 /*1CUNINGA 18.0 OPEN BUS 315219 /*1CUNINGD 22.0 SET POSTCONTRATING 1663 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM 500.0 - 8FLUVANNAEAS 500.0 SET POSTCONTRATING 1663 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM 500.0 - 8FLUVANNAWES 500.0 SET POSTCONTRATING 4399 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 SET PRECONTRATING 1481 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM 500.0 - 8FLUVANNAEAS 500.0 SET PRECONTRATING 1481 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM 500.0 - 8FLUVANNAWES 500.0 SET PRECONTRATING 4157 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 END |
Breaker | AC | 103.0 % | 809.0 | C | 833.26 | 35.24 | ||
| DVP |
6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line
313373 to 314765 ckt 1 |
DVP_P4-2: 57602_SRT-L
CONTINGENCY 'DVP_P4-2: 57602_SRT-L' OPEN BRANCH FROM BUS 314232 TO BUS 314918 CKT 1 /*6NO ANNA 230.0 - 8NO ANNA 500.0 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN 500.0 - 8NO ANNA 500.0 SET POSTCONTRATING 3300 BRANCH FROM BUS 962840 TO BUS 314918 CKT 1 /*AG1-133 TP 500.0 - 8NO ANNA 500.0 SET POSTCONTRATING 3559 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA 500.0 - 8SPOTSYL 500.0 SET PRECONTRATING 3118 BRANCH FROM BUS 962840 TO BUS 314918 CKT 1 /*AG1-133 TP 500.0 - 8NO ANNA 500.0 SET PRECONTRATING 3377 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA 500.0 - 8SPOTSYL 500.0 END |
Breaker | AC | 102.4 % | 809.0 | C | 828.45 | 36.45 | ||
| DVP |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
314765 to 314749 ckt 1 |
DVP_P4-2: 534T564_SRT-L
CONTINGENCY 'DVP_P4-2: 534T564_SRT-L' OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1 /*8DOOMS 500.0 - 8CUNINGHAM 500.0 OPEN BUS 315216 /*1CUNINGA 18.0 OPEN BUS 315219 /*1CUNINGD 22.0 SET POSTCONTRATING 1663 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM 500.0 - 8FLUVANNAEAS 500.0 SET POSTCONTRATING 1663 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM 500.0 - 8FLUVANNAWES 500.0 SET POSTCONTRATING 4399 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 SET PRECONTRATING 1481 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM 500.0 - 8FLUVANNAEAS 500.0 SET PRECONTRATING 1481 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM 500.0 - 8FLUVANNAWES 500.0 SET PRECONTRATING 4157 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 END |
Breaker | AC | 101.65 % | 809.0 | C | 822.31 | 35.24 | ||
| DVP |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
314765 to 314749 ckt 1 |
DVP_P4-2: 57602_SRT-L
CONTINGENCY 'DVP_P4-2: 57602_SRT-L' OPEN BRANCH FROM BUS 314232 TO BUS 314918 CKT 1 /*6NO ANNA 230.0 - 8NO ANNA 500.0 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN 500.0 - 8NO ANNA 500.0 SET POSTCONTRATING 3300 BRANCH FROM BUS 962840 TO BUS 314918 CKT 1 /*AG1-133 TP 500.0 - 8NO ANNA 500.0 SET POSTCONTRATING 3559 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA 500.0 - 8SPOTSYL 500.0 SET PRECONTRATING 3118 BRANCH FROM BUS 962840 TO BUS 314918 CKT 1 /*AG1-133 TP 500.0 - 8NO ANNA 500.0 SET PRECONTRATING 3377 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA 500.0 - 8SPOTSYL 500.0 END |
Breaker | AC | 101.05 % | 809.0 | C | 817.49 | 36.45 | ||
| DVP |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
314287 to 314276 ckt 1 |
DVP_P4-2: 562T563_SRT-L
CONTINGENCY 'DVP_P4-2: 562T563_SRT-L' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 OPEN BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TP 500.0 SET POSTCONTRATING 3300 BRANCH FROM BUS 314923 TO BUS 314927 CKT 1 /*8SEPTA 500.0 - 8YADKIN 500.0 SET PRECONTRATING 3118 BRANCH FROM BUS 314923 TO BUS 314927 CKT 1 /*8SEPTA 500.0 - 8YADKIN 500.0 END |
Breaker | AC | 101.49 % | 812.0 | C | 824.11 | 36.17 | ||
| DVP |
8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer
314902 to 314282 ckt 2 |
DVP_P4-2: 56372_SRT-L
CONTINGENCY 'DVP_P4-2: 56372_SRT-L' OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1 /*6CARSON 230.0 - 8CARSON 500.0 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 SET POSTCONTRATING 3559 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TP 500.0 SET PRECONTRATING 3377 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TP 500.0 END |
Breaker | AC | 101.48 % | 1056.8 | C | 1072.48 | 47.01 | ||
| Details for 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 314295 | 6BIRDNECK | 80/20 | 0.07 MW | 0.07 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 315605 | 6W1-029WIND | 80/20 | 2.17 MW | 2.17 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 315611 | 6Z1-036WIND | 80/20 | 6.32 MW | 6.32 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 901082 | W1-029 E | 80/20 | 14.58 MW | 14.58 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 916042 | Z1-036 E | 80/20 | 26.67 MW | 26.67 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 916192 | Z1-068 E | 80/20 | 0.48 MW | 0.48 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 941281 | AE2-122 C | 80/20 | 16.32 MW | 16.32 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 941282 | AE2-122 E | 80/20 | 65.86 MW | 65.86 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 941291 | AE2-123 C | 80/20 | 16.77 MW | 16.77 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 941292 | AE2-123 E | 80/20 | 65.41 MW | 65.41 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 941301 | AE2-124 C | 80/20 | 18.05 MW | 18.05 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 941302 | AE2-124 E | 80/20 | 79.22 MW | 79.22 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944581 | AF1-123 C | 80/20 | 121.69 MW | 121.69 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944582 | AF1-123 E | 80/20 | 278.63 MW | 278.63 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944591 | AF1-124 C | 80/20 | 121.69 MW | 121.69 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944592 | AF1-124 E | 80/20 | 278.63 MW | 278.63 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944601 | AF1-125 C | 80/20 | 121.69 MW | 121.69 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944602 | AF1-125 E | 80/20 | 278.63 MW | 278.63 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 964951 | AG1-359 C | 80/20 | 72.5 MW | 72.5 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 965741 | AG1-442 C | 80/20 | 2.86 MW | 2.86 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 965751 | AG1-443 C | 80/20 | 2.86 MW | 2.86 MW |
| Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 315083 | 1SPRUNCA | 80/20 | 1.66 MW | 1.66 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 315084 | 1SPRUNCB | 80/20 | 1.66 MW | 1.66 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 315611 | 6Z1-036WIND | Adder | 1.76 MW | 1.5 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 916042 | Z1-036 E | Adder | 7.42 MW | 6.3 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 941032 | AE2-094 E | 80/20 | 12.57 MW | 12.57 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 944012 | AF1-069 E | 80/20 | 4.11 MW | 4.11 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 961942 | AG1-037 E | 80/20 | 0.1 MW | 0.1 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 962332 | AG1-082 E | 80/20 | 0.4 MW | 0.4 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 962342 | AG1-083 E | 80/20 | 0.4 MW | 0.4 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 962531 | AG1-102 C | Adder | 0.33 MW | 0.28 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 962532 | AG1-102 E | Adder | 0.69 MW | 0.59 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963041 | AG1-153 C | 80/20 | 1.83 MW | 1.83 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963042 | AG1-153 E | 80/20 | 2.74 MW | 2.74 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963102 | AG1-159 E | 80/20 | 1.17 MW | 1.17 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963111 | AG1-160 C | 80/20 | 1.82 MW | 1.82 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963112 | AG1-160 E | 80/20 | 2.74 MW | 2.74 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964111 | AG1-272 C | 80/20 | 0.6 MW | 0.6 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964112 | AG1-272 E | 80/20 | 0.9 MW | 0.9 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964121 | AG1-273 C | 80/20 | 0.6 MW | 0.6 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964122 | AG1-273 E | 80/20 | 0.9 MW | 0.9 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964131 | AG1-274 C | 80/20 | 0.6 MW | 0.6 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964132 | AG1-274 E | 80/20 | 0.9 MW | 0.9 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964791 | AG1-342 C | 80/20 | 0.34 MW | 0.34 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964792 | AG1-342 E | 80/20 | 0.52 MW | 0.52 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964801 | AG1-343 C | 80/20 | 0.31 MW | 0.31 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964802 | AG1-343 E | 80/20 | 0.47 MW | 0.47 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 965191 | AG1-384 C | 80/20 | 0.6 MW | 0.6 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 965192 | AG1-384 E | 80/20 | 0.9 MW | 0.9 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 966872 | AG1-558 E | Adder | 0.65 MW | 0.55 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963311 | AG1-180 C | 80/20 | 1.53 MW | 1.53 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963312 | AG1-180 E | 80/20 | 1.28 MW | 1.28 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963351 | AG1-184 C | 80/20 | 10.48 MW | 10.48 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963352 | AG1-184 E | 80/20 | 7.48 MW | 7.48 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963361 | AG1-185 C | 80/20 | 8.24 MW | 8.24 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963362 | AG1-185 E | 80/20 | 6.93 MW | 6.93 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 961611 | AG1-000B C | 80/20 | 1.74 MW | 1.74 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 940541 | AE2-040 C | 80/20 | 0.97 MW | 0.97 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 940551 | AE2-041 C | Adder | 2.1 MW | 1.79 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 940651 | AE2-052 C | 80/20 | 1.21 MW | 1.21 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 940661 | AE2-053 C | 80/20 | 2.13 MW | 2.13 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 941281 | AE2-122 C | Adder | 7.26 MW | 6.17 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 941282 | AE2-122 E | Adder | 29.29 MW | 24.9 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 941291 | AE2-123 C | Adder | 7.46 MW | 6.34 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 941292 | AE2-123 E | Adder | 29.09 MW | 24.73 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 941301 | AE2-124 C | Adder | 6.78 MW | 5.77 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 941302 | AE2-124 E | Adder | 29.76 MW | 25.3 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 941591 | AE2-156 C | Adder | 5.72 MW | 4.86 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 942551 | AE2-270 C | 80/20 | 3.53 MW | 3.53 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 942552 | AE2-270 E | 80/20 | 5.29 MW | 5.29 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 943471 | AF1-018 C | Adder | 2.1 MW | 1.79 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 943571 | AF1-028 C | Adder | -15.96 MW | -13.56 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 944581 | AF1-123 C | Adder | 12.21 MW | 10.38 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 944582 | AF1-123 E | Adder | 27.95 MW | 23.76 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 944591 | AF1-124 C | Adder | 12.21 MW | 10.38 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 944592 | AF1-124 E | Adder | 27.95 MW | 23.76 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 944601 | AF1-125 C | Adder | 12.21 MW | 10.38 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 944602 | AF1-125 E | Adder | 27.95 MW | 23.76 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 944631 | AF1-128 C | 80/20 | 13.02 MW | 13.02 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 944641 | AF1-129 C | 80/20 | 35.18 MW | 35.18 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 945362 | AF1-201 E | Adder | 1.09 MW | 0.93 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 946011 | AF1-266 C | 80/20 | 4.61 MW | 4.61 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 961612 | AG1-000B E | 80/20 | 2.61 MW | 2.61 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 961711 | AG1-011 C | 80/20 | 9.41 MW | 9.41 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964951 | AG1-359 C | Adder | 7.28 MW | 6.18 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 965001 | AG1-364 C | Adder | 2.29 MW | 1.94 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 965002 | AG1-364 E | Adder | 3.43 MW | 2.92 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 965741 | AG1-442 C | Adder | 1.95 MW | 1.66 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 965751 | AG1-443 C | Adder | 1.95 MW | 1.66 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 965771 | AG1-445 C | 80/20 | 2.49 MW | 2.49 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 965781 | AG1-446 C | 80/20 | 2.49 MW | 2.49 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 965811 | AG1-449 C | 80/20 | 7.7 MW | 7.7 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 965831 | AG1-451 C | 80/20 | 5.36 MW | 5.36 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 966871 | AG1-558 C | Adder | 0.07 MW | 0.06 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 316303 | AF2-085 | 80/20 | 2.08 MW | 2.08 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 943573 | AF1-028 BT | 80/20 | 15.96 MW | 15.96 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 946293 | AF1-293 BT | 80/20 | 5.64 MW | 5.64 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 958502 | AF2-144 E | Adder | 3.12 MW | 2.65 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 961063 | AF2-397 BT | 80/20 | 23.92 MW | 23.92 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963023 | AG1-151 BT | 80/20 | 7.98 MW | 7.98 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963463 | AG1-195 BT | 80/20 | 13.55 MW | 13.55 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963473 | AG1-196 BT | 80/20 | 15.31 MW | 15.31 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 965543 | AG1-422 BT | 80/20 | 4.99 MW | 4.99 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 966673 | AG1-537 BT | 80/20 | 8.96 MW | 8.96 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 966853 | AG1-556 BT | 80/20 | 8.72 MW | 8.72 MW |
| Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 314295 | 6BIRDNECK | 80/20 | 0.04 MW | 0.04 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315083 | 1SPRUNCA | 80/20 | 1.64 MW | 1.64 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315084 | 1SPRUNCB | 80/20 | 1.64 MW | 1.64 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315131 | 1EDGECMA | Adder | 1.69 MW | 1.44 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315605 | 6W1-029WIND | 80/20 | 0.64 MW | 0.64 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315611 | 6Z1-036WIND | 80/20 | 1.85 MW | 1.85 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 901082 | W1-029 E | 80/20 | 4.27 MW | 4.27 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 916042 | Z1-036 E | 80/20 | 7.79 MW | 7.79 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 916192 | Z1-068 E | 80/20 | 0.25 MW | 0.25 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941032 | AE2-094 E | 80/20 | 14.67 MW | 14.67 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944012 | AF1-069 E | 80/20 | 4.79 MW | 4.79 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 961942 | AG1-037 E | 80/20 | 0.1 MW | 0.1 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 962332 | AG1-082 E | 80/20 | 0.43 MW | 0.43 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 962342 | AG1-083 E | 80/20 | 0.43 MW | 0.43 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963041 | AG1-153 C | 80/20 | 2.13 MW | 2.13 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963042 | AG1-153 E | 80/20 | 3.2 MW | 3.2 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963102 | AG1-159 E | 80/20 | 1.31 MW | 1.31 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963111 | AG1-160 C | 80/20 | 2.13 MW | 2.13 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963112 | AG1-160 E | 80/20 | 3.19 MW | 3.19 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964111 | AG1-272 C | 80/20 | 0.64 MW | 0.64 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964112 | AG1-272 E | 80/20 | 0.96 MW | 0.96 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964121 | AG1-273 C | 80/20 | 0.64 MW | 0.64 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964122 | AG1-273 E | 80/20 | 0.96 MW | 0.96 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964131 | AG1-274 C | 80/20 | 0.64 MW | 0.64 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964132 | AG1-274 E | 80/20 | 0.96 MW | 0.96 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964791 | AG1-342 C | 80/20 | 0.38 MW | 0.38 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964792 | AG1-342 E | 80/20 | 0.57 MW | 0.57 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964801 | AG1-343 C | 80/20 | 0.34 MW | 0.34 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964802 | AG1-343 E | 80/20 | 0.5 MW | 0.5 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965191 | AG1-384 C | 80/20 | 0.64 MW | 0.64 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965192 | AG1-384 E | 80/20 | 0.96 MW | 0.96 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963311 | AG1-180 C | 80/20 | 1.67 MW | 1.67 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963312 | AG1-180 E | 80/20 | 1.4 MW | 1.4 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963351 | AG1-184 C | 80/20 | 12.03 MW | 12.03 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963352 | AG1-184 E | 80/20 | 8.58 MW | 8.58 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963361 | AG1-185 C | 80/20 | 8.8 MW | 8.8 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963362 | AG1-185 E | 80/20 | 7.4 MW | 7.4 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 940541 | AE2-040 C | 80/20 | 1.06 MW | 1.06 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 940651 | AE2-052 C | 80/20 | 1.22 MW | 1.22 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 940661 | AE2-053 C | 80/20 | 2.33 MW | 2.33 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941281 | AE2-122 C | 80/20 | 7.44 MW | 7.44 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941282 | AE2-122 E | 80/20 | 30.03 MW | 30.03 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941291 | AE2-123 C | 80/20 | 7.65 MW | 7.65 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941292 | AE2-123 E | 80/20 | 29.83 MW | 29.83 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941301 | AE2-124 C | 80/20 | 6.96 MW | 6.96 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941302 | AE2-124 E | 80/20 | 30.53 MW | 30.53 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941591 | AE2-156 C | 80/20 | 5.84 MW | 5.84 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 943571 | AF1-028 C | Adder | -11.86 MW | -10.08 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944141 | AF1-082 C | Adder | 1.03 MW | 0.88 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944581 | AF1-123 C | 80/20 | 12.55 MW | 12.55 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944582 | AF1-123 E | 80/20 | 28.74 MW | 28.74 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944591 | AF1-124 C | 80/20 | 12.55 MW | 12.55 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944592 | AF1-124 E | 80/20 | 28.74 MW | 28.74 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944601 | AF1-125 C | 80/20 | 12.55 MW | 12.55 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944602 | AF1-125 E | 80/20 | 28.74 MW | 28.74 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944641 | AF1-129 C | 80/20 | 33.9 MW | 33.9 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 946011 | AF1-266 C | 80/20 | 5.05 MW | 5.05 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 961602 | AG1-000A E | Adder | 1.99 MW | 1.69 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964951 | AG1-359 C | 80/20 | 7.47 MW | 7.47 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965001 | AG1-364 C | 80/20 | 2.34 MW | 2.34 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965002 | AG1-364 E | 80/20 | 3.51 MW | 3.51 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965741 | AG1-442 C | 80/20 | 2.11 MW | 2.11 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965751 | AG1-443 C | 80/20 | 2.11 MW | 2.11 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965761 | AG1-444 C | Adder | 4.55 MW | 3.87 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965771 | AG1-445 C | 80/20 | 2.73 MW | 2.73 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965781 | AG1-446 C | 80/20 | 2.73 MW | 2.73 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965811 | AG1-449 C | 80/20 | 8.95 MW | 8.95 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965831 | AG1-451 C | 80/20 | 5.63 MW | 5.63 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 316303 | AF2-085 | 80/20 | 2.28 MW | 2.28 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 943573 | AF1-028 BT | 80/20 | 11.86 MW | 11.86 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 958502 | AF2-144 E | Adder | 3.28 MW | 2.79 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 961063 | AF2-397 BT | 80/20 | 23.01 MW | 23.01 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963023 | AG1-151 BT | 80/20 | 5.93 MW | 5.93 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963463 | AG1-195 BT | 80/20 | 9.46 MW | 9.46 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963473 | AG1-196 BT | 80/20 | 11.55 MW | 11.55 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965543 | AG1-422 BT | 80/20 | 3.57 MW | 3.57 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 966673 | AG1-537 BT | 80/20 | 6.88 MW | 6.88 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 966853 | AG1-556 BT | 80/20 | 5.89 MW | 5.89 MW |
| Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 315083 | 1SPRUNCA | 80/20 | 1.66 MW | 1.66 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 315084 | 1SPRUNCB | 80/20 | 1.66 MW | 1.66 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 315611 | 6Z1-036WIND | Adder | 1.76 MW | 1.5 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 916042 | Z1-036 E | Adder | 7.42 MW | 6.3 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 941032 | AE2-094 E | 80/20 | 12.57 MW | 12.57 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 944012 | AF1-069 E | 80/20 | 4.11 MW | 4.11 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 961942 | AG1-037 E | 80/20 | 0.1 MW | 0.1 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 962332 | AG1-082 E | 80/20 | 0.4 MW | 0.4 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 962342 | AG1-083 E | 80/20 | 0.4 MW | 0.4 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 962531 | AG1-102 C | Adder | 0.33 MW | 0.28 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 962532 | AG1-102 E | Adder | 0.69 MW | 0.59 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963041 | AG1-153 C | 80/20 | 1.83 MW | 1.83 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963042 | AG1-153 E | 80/20 | 2.74 MW | 2.74 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963102 | AG1-159 E | 80/20 | 1.17 MW | 1.17 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963111 | AG1-160 C | 80/20 | 1.82 MW | 1.82 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963112 | AG1-160 E | 80/20 | 2.74 MW | 2.74 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964111 | AG1-272 C | 80/20 | 0.6 MW | 0.6 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964112 | AG1-272 E | 80/20 | 0.9 MW | 0.9 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964121 | AG1-273 C | 80/20 | 0.6 MW | 0.6 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964122 | AG1-273 E | 80/20 | 0.9 MW | 0.9 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964131 | AG1-274 C | 80/20 | 0.6 MW | 0.6 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964132 | AG1-274 E | 80/20 | 0.9 MW | 0.9 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964791 | AG1-342 C | 80/20 | 0.34 MW | 0.34 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964792 | AG1-342 E | 80/20 | 0.52 MW | 0.52 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964801 | AG1-343 C | 80/20 | 0.31 MW | 0.31 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964802 | AG1-343 E | 80/20 | 0.47 MW | 0.47 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 965191 | AG1-384 C | 80/20 | 0.6 MW | 0.6 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 965192 | AG1-384 E | 80/20 | 0.9 MW | 0.9 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 966872 | AG1-558 E | Adder | 0.65 MW | 0.55 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963311 | AG1-180 C | 80/20 | 1.53 MW | 1.53 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963312 | AG1-180 E | 80/20 | 1.28 MW | 1.28 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963351 | AG1-184 C | 80/20 | 10.48 MW | 10.48 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963352 | AG1-184 E | 80/20 | 7.48 MW | 7.48 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963361 | AG1-185 C | 80/20 | 8.24 MW | 8.24 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963362 | AG1-185 E | 80/20 | 6.93 MW | 6.93 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 961611 | AG1-000B C | 80/20 | 1.74 MW | 1.74 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 940541 | AE2-040 C | 80/20 | 0.97 MW | 0.97 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 940551 | AE2-041 C | Adder | 2.1 MW | 1.79 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 940651 | AE2-052 C | 80/20 | 1.21 MW | 1.21 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 940661 | AE2-053 C | 80/20 | 2.13 MW | 2.13 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 941281 | AE2-122 C | Adder | 7.26 MW | 6.17 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 941282 | AE2-122 E | Adder | 29.29 MW | 24.9 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 941291 | AE2-123 C | Adder | 7.46 MW | 6.34 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 941292 | AE2-123 E | Adder | 29.09 MW | 24.73 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 941301 | AE2-124 C | Adder | 6.78 MW | 5.77 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 941302 | AE2-124 E | Adder | 29.76 MW | 25.3 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 941591 | AE2-156 C | Adder | 5.72 MW | 4.86 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 942551 | AE2-270 C | 80/20 | 3.53 MW | 3.53 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 942552 | AE2-270 E | 80/20 | 5.29 MW | 5.29 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 943471 | AF1-018 C | Adder | 2.1 MW | 1.79 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 943571 | AF1-028 C | Adder | -15.96 MW | -13.56 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 944581 | AF1-123 C | Adder | 12.21 MW | 10.38 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 944582 | AF1-123 E | Adder | 27.95 MW | 23.76 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 944591 | AF1-124 C | Adder | 12.21 MW | 10.38 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 944592 | AF1-124 E | Adder | 27.95 MW | 23.76 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 944601 | AF1-125 C | Adder | 12.21 MW | 10.38 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 944602 | AF1-125 E | Adder | 27.95 MW | 23.76 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 944631 | AF1-128 C | 80/20 | 13.02 MW | 13.02 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 944641 | AF1-129 C | 80/20 | 35.18 MW | 35.18 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 945362 | AF1-201 E | Adder | 1.09 MW | 0.93 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 946011 | AF1-266 C | 80/20 | 4.61 MW | 4.61 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 961612 | AG1-000B E | 80/20 | 2.61 MW | 2.61 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 961711 | AG1-011 C | 80/20 | 9.41 MW | 9.41 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964951 | AG1-359 C | Adder | 7.28 MW | 6.18 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 965001 | AG1-364 C | Adder | 2.29 MW | 1.94 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 965002 | AG1-364 E | Adder | 3.43 MW | 2.92 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 965741 | AG1-442 C | Adder | 1.95 MW | 1.66 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 965751 | AG1-443 C | Adder | 1.95 MW | 1.66 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 965771 | AG1-445 C | 80/20 | 2.49 MW | 2.49 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 965781 | AG1-446 C | 80/20 | 2.49 MW | 2.49 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 965811 | AG1-449 C | 80/20 | 7.7 MW | 7.7 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 965831 | AG1-451 C | 80/20 | 5.36 MW | 5.36 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 966871 | AG1-558 C | Adder | 0.07 MW | 0.06 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 316303 | AF2-085 | 80/20 | 2.08 MW | 2.08 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 943573 | AF1-028 BT | 80/20 | 15.96 MW | 15.96 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 946293 | AF1-293 BT | 80/20 | 5.64 MW | 5.64 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 958502 | AF2-144 E | Adder | 3.12 MW | 2.65 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 961063 | AF2-397 BT | 80/20 | 23.92 MW | 23.92 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963023 | AG1-151 BT | 80/20 | 7.98 MW | 7.98 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963463 | AG1-195 BT | 80/20 | 13.55 MW | 13.55 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963473 | AG1-196 BT | 80/20 | 15.31 MW | 15.31 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 965543 | AG1-422 BT | 80/20 | 4.99 MW | 4.99 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 966673 | AG1-537 BT | 80/20 | 8.96 MW | 8.96 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 966853 | AG1-556 BT | 80/20 | 8.72 MW | 8.72 MW |
| Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 314295 | 6BIRDNECK | 80/20 | 0.04 MW | 0.04 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315083 | 1SPRUNCA | 80/20 | 1.64 MW | 1.64 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315084 | 1SPRUNCB | 80/20 | 1.64 MW | 1.64 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315131 | 1EDGECMA | Adder | 1.69 MW | 1.44 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315605 | 6W1-029WIND | 80/20 | 0.64 MW | 0.64 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315611 | 6Z1-036WIND | 80/20 | 1.85 MW | 1.85 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 901082 | W1-029 E | 80/20 | 4.27 MW | 4.27 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 916042 | Z1-036 E | 80/20 | 7.79 MW | 7.79 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 916192 | Z1-068 E | 80/20 | 0.25 MW | 0.25 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941032 | AE2-094 E | 80/20 | 14.67 MW | 14.67 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944012 | AF1-069 E | 80/20 | 4.79 MW | 4.79 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 961942 | AG1-037 E | 80/20 | 0.1 MW | 0.1 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 962332 | AG1-082 E | 80/20 | 0.43 MW | 0.43 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 962342 | AG1-083 E | 80/20 | 0.43 MW | 0.43 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963041 | AG1-153 C | 80/20 | 2.13 MW | 2.13 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963042 | AG1-153 E | 80/20 | 3.2 MW | 3.2 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963102 | AG1-159 E | 80/20 | 1.31 MW | 1.31 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963111 | AG1-160 C | 80/20 | 2.13 MW | 2.13 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963112 | AG1-160 E | 80/20 | 3.19 MW | 3.19 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964111 | AG1-272 C | 80/20 | 0.64 MW | 0.64 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964112 | AG1-272 E | 80/20 | 0.96 MW | 0.96 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964121 | AG1-273 C | 80/20 | 0.64 MW | 0.64 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964122 | AG1-273 E | 80/20 | 0.96 MW | 0.96 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964131 | AG1-274 C | 80/20 | 0.64 MW | 0.64 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964132 | AG1-274 E | 80/20 | 0.96 MW | 0.96 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964791 | AG1-342 C | 80/20 | 0.38 MW | 0.38 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964792 | AG1-342 E | 80/20 | 0.57 MW | 0.57 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964801 | AG1-343 C | 80/20 | 0.34 MW | 0.34 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964802 | AG1-343 E | 80/20 | 0.5 MW | 0.5 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965191 | AG1-384 C | 80/20 | 0.64 MW | 0.64 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965192 | AG1-384 E | 80/20 | 0.96 MW | 0.96 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963311 | AG1-180 C | 80/20 | 1.67 MW | 1.67 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963312 | AG1-180 E | 80/20 | 1.4 MW | 1.4 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963351 | AG1-184 C | 80/20 | 12.03 MW | 12.03 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963352 | AG1-184 E | 80/20 | 8.58 MW | 8.58 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963361 | AG1-185 C | 80/20 | 8.8 MW | 8.8 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963362 | AG1-185 E | 80/20 | 7.4 MW | 7.4 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 940541 | AE2-040 C | 80/20 | 1.06 MW | 1.06 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 940651 | AE2-052 C | 80/20 | 1.22 MW | 1.22 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 940661 | AE2-053 C | 80/20 | 2.33 MW | 2.33 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941281 | AE2-122 C | 80/20 | 7.44 MW | 7.44 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941282 | AE2-122 E | 80/20 | 30.03 MW | 30.03 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941291 | AE2-123 C | 80/20 | 7.65 MW | 7.65 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941292 | AE2-123 E | 80/20 | 29.83 MW | 29.83 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941301 | AE2-124 C | 80/20 | 6.96 MW | 6.96 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941302 | AE2-124 E | 80/20 | 30.53 MW | 30.53 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941591 | AE2-156 C | 80/20 | 5.84 MW | 5.84 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 943571 | AF1-028 C | Adder | -11.86 MW | -10.08 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944141 | AF1-082 C | Adder | 1.03 MW | 0.88 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944581 | AF1-123 C | 80/20 | 12.55 MW | 12.55 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944582 | AF1-123 E | 80/20 | 28.74 MW | 28.74 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944591 | AF1-124 C | 80/20 | 12.55 MW | 12.55 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944592 | AF1-124 E | 80/20 | 28.74 MW | 28.74 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944601 | AF1-125 C | 80/20 | 12.55 MW | 12.55 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944602 | AF1-125 E | 80/20 | 28.74 MW | 28.74 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944641 | AF1-129 C | 80/20 | 33.9 MW | 33.9 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 946011 | AF1-266 C | 80/20 | 5.05 MW | 5.05 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 961602 | AG1-000A E | Adder | 1.99 MW | 1.69 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964951 | AG1-359 C | 80/20 | 7.47 MW | 7.47 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965001 | AG1-364 C | 80/20 | 2.34 MW | 2.34 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965002 | AG1-364 E | 80/20 | 3.51 MW | 3.51 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965741 | AG1-442 C | 80/20 | 2.11 MW | 2.11 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965751 | AG1-443 C | 80/20 | 2.11 MW | 2.11 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965761 | AG1-444 C | Adder | 4.55 MW | 3.87 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965771 | AG1-445 C | 80/20 | 2.73 MW | 2.73 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965781 | AG1-446 C | 80/20 | 2.73 MW | 2.73 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965811 | AG1-449 C | 80/20 | 8.95 MW | 8.95 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965831 | AG1-451 C | 80/20 | 5.63 MW | 5.63 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 316303 | AF2-085 | 80/20 | 2.28 MW | 2.28 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 943573 | AF1-028 BT | 80/20 | 11.86 MW | 11.86 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 958502 | AF2-144 E | Adder | 3.28 MW | 2.79 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 961063 | AF2-397 BT | 80/20 | 23.01 MW | 23.01 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963023 | AG1-151 BT | 80/20 | 5.93 MW | 5.93 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963463 | AG1-195 BT | 80/20 | 9.46 MW | 9.46 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963473 | AG1-196 BT | 80/20 | 11.55 MW | 11.55 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965543 | AG1-422 BT | 80/20 | 3.57 MW | 3.57 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 966673 | AG1-537 BT | 80/20 | 6.88 MW | 6.88 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 966853 | AG1-556 BT | 80/20 | 5.89 MW | 5.89 MW |
| Details for 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 964111 | AG1-272 C | 80/20 | 0.35 MW | 0.35 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 964112 | AG1-272 E | 80/20 | 0.53 MW | 0.53 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 964121 | AG1-273 C | 80/20 | 0.35 MW | 0.35 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 964122 | AG1-273 E | 80/20 | 0.53 MW | 0.53 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 964131 | AG1-274 C | 80/20 | 0.35 MW | 0.35 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 964132 | AG1-274 E | 80/20 | 0.53 MW | 0.53 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 964791 | AG1-342 C | 80/20 | 0.19 MW | 0.19 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 964792 | AG1-342 E | 80/20 | 0.28 MW | 0.28 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 965191 | AG1-384 C | 80/20 | 0.35 MW | 0.35 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 965192 | AG1-384 E | 80/20 | 0.53 MW | 0.53 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 963311 | AG1-180 C | 80/20 | 0.83 MW | 0.83 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 963312 | AG1-180 E | 80/20 | 0.7 MW | 0.7 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 963361 | AG1-185 C | 80/20 | 4.83 MW | 4.83 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 963362 | AG1-185 E | 80/20 | 4.05 MW | 4.05 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 940661 | AE2-053 C | 80/20 | 1.19 MW | 1.19 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 941281 | AE2-122 C | Adder | 3.33 MW | 2.83 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 941282 | AE2-122 E | Adder | 13.42 MW | 11.41 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 941291 | AE2-123 C | Adder | 3.42 MW | 2.9 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 941292 | AE2-123 E | Adder | 13.33 MW | 11.33 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 941301 | AE2-124 C | Adder | 3.11 MW | 2.64 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 941302 | AE2-124 E | Adder | 13.64 MW | 11.59 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 944581 | AF1-123 C | Adder | 5.59 MW | 4.75 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 944582 | AF1-123 E | Adder | 12.8 MW | 10.88 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 944591 | AF1-124 C | Adder | 5.59 MW | 4.75 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 944592 | AF1-124 E | Adder | 12.8 MW | 10.88 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 944601 | AF1-125 C | Adder | 5.59 MW | 4.75 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 944602 | AF1-125 E | Adder | 12.8 MW | 10.88 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 944641 | AF1-129 C | Adder | 16.22 MW | 13.79 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 965771 | AG1-445 C | 80/20 | 1.37 MW | 1.37 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 965781 | AG1-446 C | 80/20 | 1.37 MW | 1.37 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 965831 | AG1-451 C | 80/20 | 3.23 MW | 3.23 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 316303 | AF2-085 | 80/20 | 1.12 MW | 1.12 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 946293 | AF1-293 BT | 80/20 | 26.71 MW | 26.71 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 958502 | AF2-144 E | Adder | 1.86 MW | 1.58 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 961063 | AF2-397 BT | 80/20 | 8.81 MW | 8.81 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 965583 | AG1-426 BT | 80/20 | 13.34 MW | 13.34 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 966253 | AG1-494 BT | 80/20 | 3.82 MW | 3.82 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 966673 | AG1-537 BT | 80/20 | 5.33 MW | 5.33 MW |
| Details for 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 314295 | 6BIRDNECK | 80/20 | 0.15 MW | 0.15 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 315605 | 6W1-029WIND | 80/20 | 1.9 MW | 1.9 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 315611 | 6Z1-036WIND | 80/20 | 5.33 MW | 5.33 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 901082 | W1-029 E | 80/20 | 12.77 MW | 12.77 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 916042 | Z1-036 E | 80/20 | 22.5 MW | 22.5 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 916192 | Z1-068 E | 80/20 | 1.08 MW | 1.08 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 961942 | AG1-037 E | 80/20 | 0.1 MW | 0.1 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 962332 | AG1-082 E | 80/20 | 0.42 MW | 0.42 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 962342 | AG1-083 E | 80/20 | 0.42 MW | 0.42 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 964801 | AG1-343 C | 80/20 | 0.29 MW | 0.29 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 964802 | AG1-343 E | 80/20 | 0.43 MW | 0.43 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 941281 | AE2-122 C | 80/20 | 35.05 MW | 35.05 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 941282 | AE2-122 E | 80/20 | 141.44 MW | 141.44 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 941291 | AE2-123 C | 80/20 | 36.02 MW | 36.02 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 941292 | AE2-123 E | 80/20 | 140.47 MW | 140.47 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 941301 | AE2-124 C | 80/20 | 36.1 MW | 36.1 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 941302 | AE2-124 E | 80/20 | 158.39 MW | 158.39 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944581 | AF1-123 C | 80/20 | 76.18 MW | 76.18 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944582 | AF1-123 E | 80/20 | 174.43 MW | 174.43 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944591 | AF1-124 C | 80/20 | 76.18 MW | 76.18 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944592 | AF1-124 E | 80/20 | 174.43 MW | 174.43 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944601 | AF1-125 C | 80/20 | 76.18 MW | 76.18 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944602 | AF1-125 E | 80/20 | 174.43 MW | 174.43 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 964951 | AG1-359 C | 80/20 | 45.39 MW | 45.39 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 965741 | AG1-442 C | 80/20 | 3.25 MW | 3.25 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 965751 | AG1-443 C | 80/20 | 3.25 MW | 3.25 MW |
| Details for 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315083 | 1SPRUNCA | 80/20 | 1.43 MW | 1.43 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315084 | 1SPRUNCB | 80/20 | 1.43 MW | 1.43 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315131 | 1EDGECMA | Adder | 2.35 MW | 2.0 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315605 | 6W1-029WIND | 80/20 | 0.56 MW | 0.56 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315611 | 6Z1-036WIND | 80/20 | 1.64 MW | 1.64 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 901082 | W1-029 E | 80/20 | 3.79 MW | 3.79 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 916042 | Z1-036 E | 80/20 | 6.92 MW | 6.92 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941032 | AE2-094 E | 80/20 | 13.11 MW | 13.11 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944012 | AF1-069 E | 80/20 | 4.28 MW | 4.28 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 961942 | AG1-037 E | 80/20 | 0.1 MW | 0.1 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 962332 | AG1-082 E | 80/20 | 0.39 MW | 0.39 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 962342 | AG1-083 E | 80/20 | 0.39 MW | 0.39 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963041 | AG1-153 C | 80/20 | 1.91 MW | 1.91 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963042 | AG1-153 E | 80/20 | 2.87 MW | 2.87 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963102 | AG1-159 E | 80/20 | 1.19 MW | 1.19 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963111 | AG1-160 C | 80/20 | 1.91 MW | 1.91 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963112 | AG1-160 E | 80/20 | 2.86 MW | 2.86 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964111 | AG1-272 C | 80/20 | 0.58 MW | 0.58 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964112 | AG1-272 E | 80/20 | 0.87 MW | 0.87 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964121 | AG1-273 C | 80/20 | 0.58 MW | 0.58 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964122 | AG1-273 E | 80/20 | 0.87 MW | 0.87 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964131 | AG1-274 C | 80/20 | 0.58 MW | 0.58 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964132 | AG1-274 E | 80/20 | 0.87 MW | 0.87 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964791 | AG1-342 C | 80/20 | 0.35 MW | 0.35 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964792 | AG1-342 E | 80/20 | 0.53 MW | 0.53 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964801 | AG1-343 C | 80/20 | 0.3 MW | 0.3 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964802 | AG1-343 E | 80/20 | 0.45 MW | 0.45 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965191 | AG1-384 C | 80/20 | 0.58 MW | 0.58 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965192 | AG1-384 E | 80/20 | 0.87 MW | 0.87 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 966251 | AG1-494 C | 80/20 | 1.21 MW | 1.21 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 966252 | AG1-494 E | 80/20 | 1.82 MW | 1.82 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 966691 | AG1-539 C | 80/20 | 1.69 MW | 1.69 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 966692 | AG1-539 E | 80/20 | 2.27 MW | 2.27 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963311 | AG1-180 C | 80/20 | 1.51 MW | 1.51 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963312 | AG1-180 E | 80/20 | 1.26 MW | 1.26 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963351 | AG1-184 C | 80/20 | 10.7 MW | 10.7 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963352 | AG1-184 E | 80/20 | 7.63 MW | 7.63 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963361 | AG1-185 C | 80/20 | 7.95 MW | 7.95 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963362 | AG1-185 E | 80/20 | 6.67 MW | 6.67 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965581 | AG1-426 C | 80/20 | 4.61 MW | 4.61 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 940541 | AE2-040 C | 80/20 | 0.95 MW | 0.95 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 940651 | AE2-052 C | 80/20 | 1.07 MW | 1.07 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 940661 | AE2-053 C | 80/20 | 2.12 MW | 2.12 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941281 | AE2-122 C | Adder | 6.56 MW | 5.58 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941282 | AE2-122 E | Adder | 26.48 MW | 22.51 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941291 | AE2-123 C | Adder | 6.74 MW | 5.73 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941292 | AE2-123 E | Adder | 26.3 MW | 22.36 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941301 | AE2-124 C | Adder | 6.14 MW | 5.22 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941302 | AE2-124 E | Adder | 26.92 MW | 22.89 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941591 | AE2-156 C | Adder | 5.15 MW | 4.38 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 943571 | AF1-028 C | Adder | -11.38 MW | -9.67 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944141 | AF1-082 C | 80/20 | 0.95 MW | 0.95 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944581 | AF1-123 C | Adder | 11.07 MW | 9.41 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944582 | AF1-123 E | Adder | 25.34 MW | 21.54 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944591 | AF1-124 C | Adder | 11.07 MW | 9.41 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944592 | AF1-124 E | Adder | 25.34 MW | 21.54 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944601 | AF1-125 C | Adder | 11.07 MW | 9.41 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944602 | AF1-125 E | Adder | 25.34 MW | 21.54 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944641 | AF1-129 C | Adder | 29.63 MW | 25.19 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 946011 | AF1-266 C | 80/20 | 4.5 MW | 4.5 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 946291 | AF1-293 C | 80/20 | 9.21 MW | 9.21 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 946292 | AF1-293 E | 80/20 | 13.82 MW | 13.82 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 961602 | AG1-000A E | Adder | 1.83 MW | 1.55 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964951 | AG1-359 C | Adder | 6.59 MW | 5.61 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965001 | AG1-364 C | Adder | 2.06 MW | 1.75 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965002 | AG1-364 E | Adder | 3.09 MW | 2.63 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965741 | AG1-442 C | 80/20 | 1.9 MW | 1.9 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965751 | AG1-443 C | 80/20 | 1.9 MW | 1.9 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965761 | AG1-444 C | Adder | 4.16 MW | 3.54 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965771 | AG1-445 C | 80/20 | 2.48 MW | 2.48 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965781 | AG1-446 C | 80/20 | 2.48 MW | 2.48 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965811 | AG1-449 C | 80/20 | 8.01 MW | 8.01 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965831 | AG1-451 C | 80/20 | 5.05 MW | 5.05 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 316303 | AF2-085 | 80/20 | 2.02 MW | 2.02 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 943573 | AF1-028 BT | 80/20 | 11.38 MW | 11.38 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 958502 | AF2-144 E | Adder | 2.92 MW | 2.48 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 961063 | AF2-397 BT | 80/20 | 26.02 MW | 26.02 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963023 | AG1-151 BT | 80/20 | 5.69 MW | 5.69 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963463 | AG1-195 BT | 80/20 | 9.01 MW | 9.01 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963473 | AG1-196 BT | 80/20 | 11.14 MW | 11.14 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965543 | AG1-422 BT | 80/20 | 3.41 MW | 3.41 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 966673 | AG1-537 BT | 80/20 | 4.79 MW | 4.79 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 966853 | AG1-556 BT | 80/20 | 5.56 MW | 5.56 MW |
| Details for 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 315083 | 1SPRUNCA | 80/20 | 1.45 MW | 1.45 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 315084 | 1SPRUNCB | 80/20 | 1.45 MW | 1.45 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 941032 | AE2-094 E | 80/20 | 11.09 MW | 11.09 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 944012 | AF1-069 E | 80/20 | 3.62 MW | 3.62 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 961942 | AG1-037 E | 80/20 | 0.09 MW | 0.09 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 962332 | AG1-082 E | 80/20 | 0.35 MW | 0.35 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 962342 | AG1-083 E | 80/20 | 0.35 MW | 0.35 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963041 | AG1-153 C | 80/20 | 1.62 MW | 1.62 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963042 | AG1-153 E | 80/20 | 2.43 MW | 2.43 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963102 | AG1-159 E | 80/20 | 1.05 MW | 1.05 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963111 | AG1-160 C | 80/20 | 1.62 MW | 1.62 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963112 | AG1-160 E | 80/20 | 2.42 MW | 2.42 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964111 | AG1-272 C | 80/20 | 0.54 MW | 0.54 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964112 | AG1-272 E | 80/20 | 0.81 MW | 0.81 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964121 | AG1-273 C | 80/20 | 0.54 MW | 0.54 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964122 | AG1-273 E | 80/20 | 0.81 MW | 0.81 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964131 | AG1-274 C | 80/20 | 0.54 MW | 0.54 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964132 | AG1-274 E | 80/20 | 0.81 MW | 0.81 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964791 | AG1-342 C | 80/20 | 0.32 MW | 0.32 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964792 | AG1-342 E | 80/20 | 0.47 MW | 0.47 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964801 | AG1-343 C | 80/20 | 0.28 MW | 0.28 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964802 | AG1-343 E | 80/20 | 0.41 MW | 0.41 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 965191 | AG1-384 C | 80/20 | 0.54 MW | 0.54 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 965192 | AG1-384 E | 80/20 | 0.81 MW | 0.81 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963311 | AG1-180 C | 80/20 | 1.38 MW | 1.38 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963312 | AG1-180 E | 80/20 | 1.15 MW | 1.15 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963351 | AG1-184 C | 80/20 | 9.2 MW | 9.2 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963352 | AG1-184 E | 80/20 | 6.57 MW | 6.57 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963361 | AG1-185 C | 80/20 | 7.42 MW | 7.42 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963362 | AG1-185 E | 80/20 | 6.23 MW | 6.23 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 965581 | AG1-426 C | 80/20 | 4.34 MW | 4.34 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 961611 | AG1-000B C | Adder | 1.52 MW | 1.29 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 940541 | AE2-040 C | 80/20 | 0.86 MW | 0.86 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 940651 | AE2-052 C | 80/20 | 1.05 MW | 1.05 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 940661 | AE2-053 C | 80/20 | 1.93 MW | 1.93 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 942551 | AE2-270 C | Adder | 3.07 MW | 2.61 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 942552 | AE2-270 E | 80/20 | 4.6 MW | 4.6 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 943571 | AF1-028 C | Adder | -15.09 MW | -12.83 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 944581 | AF1-123 C | Adder | 10.67 MW | 9.07 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 944582 | AF1-123 E | Adder | 24.43 MW | 20.76 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 944591 | AF1-124 C | Adder | 10.67 MW | 9.07 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 944592 | AF1-124 E | Adder | 24.43 MW | 20.76 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 944601 | AF1-125 C | Adder | 10.67 MW | 9.07 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 944602 | AF1-125 E | Adder | 24.43 MW | 20.76 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 944631 | AF1-128 C | 80/20 | 11.27 MW | 11.27 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 944641 | AF1-129 C | 80/20 | 30.59 MW | 30.59 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 946011 | AF1-266 C | 80/20 | 4.07 MW | 4.07 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 946291 | AF1-293 C | 80/20 | 8.65 MW | 8.65 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 946292 | AF1-293 E | 80/20 | 12.97 MW | 12.97 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 961612 | AG1-000B E | Adder | 2.28 MW | 1.93 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 961711 | AG1-011 C | 80/20 | 8.19 MW | 8.19 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 965771 | AG1-445 C | 80/20 | 2.25 MW | 2.25 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 965781 | AG1-446 C | 80/20 | 2.25 MW | 2.25 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 965811 | AG1-449 C | 80/20 | 6.82 MW | 6.82 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 965831 | AG1-451 C | 80/20 | 4.8 MW | 4.8 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 316303 | AF2-085 | 80/20 | 1.82 MW | 1.82 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 943573 | AF1-028 BT | 80/20 | 15.09 MW | 15.09 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 958502 | AF2-144 E | Adder | 2.77 MW | 2.36 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 961063 | AF2-397 BT | 80/20 | 26.85 MW | 26.85 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963023 | AG1-151 BT | 80/20 | 7.55 MW | 7.55 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963463 | AG1-195 BT | 80/20 | 12.72 MW | 12.72 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963473 | AG1-196 BT | 80/20 | 14.56 MW | 14.56 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 965543 | AG1-422 BT | 80/20 | 4.71 MW | 4.71 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 966673 | AG1-537 BT | 80/20 | 6.68 MW | 6.68 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 966853 | AG1-556 BT | 80/20 | 8.13 MW | 8.13 MW |
| Details for AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315083 | 1SPRUNCA | 80/20 | 1.43 MW | 1.43 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315084 | 1SPRUNCB | 80/20 | 1.43 MW | 1.43 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315131 | 1EDGECMA | Adder | 2.35 MW | 2.0 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315611 | 6Z1-036WIND | Adder | 1.64 MW | 1.4 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 916042 | Z1-036 E | Adder | 6.92 MW | 5.89 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941032 | AE2-094 E | 80/20 | 13.11 MW | 13.11 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944012 | AF1-069 E | 80/20 | 4.28 MW | 4.28 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 961062 | AF2-397 E | 80/20 | 26.63 MW | 26.63 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 961942 | AG1-037 E | 80/20 | 0.1 MW | 0.1 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 962332 | AG1-082 E | 80/20 | 0.39 MW | 0.39 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 962342 | AG1-083 E | 80/20 | 0.39 MW | 0.39 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963041 | AG1-153 C | 80/20 | 1.91 MW | 1.91 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963042 | AG1-153 E | 80/20 | 2.87 MW | 2.87 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963102 | AG1-159 E | 80/20 | 1.19 MW | 1.19 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963111 | AG1-160 C | 80/20 | 1.91 MW | 1.91 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963112 | AG1-160 E | 80/20 | 2.86 MW | 2.86 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964111 | AG1-272 C | 80/20 | 0.58 MW | 0.58 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964112 | AG1-272 E | 80/20 | 0.87 MW | 0.87 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964121 | AG1-273 C | 80/20 | 0.58 MW | 0.58 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964122 | AG1-273 E | 80/20 | 0.87 MW | 0.87 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964131 | AG1-274 C | 80/20 | 0.58 MW | 0.58 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964132 | AG1-274 E | 80/20 | 0.87 MW | 0.87 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964791 | AG1-342 C | 80/20 | 0.35 MW | 0.35 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964792 | AG1-342 E | 80/20 | 0.53 MW | 0.53 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964801 | AG1-343 C | 80/20 | 0.3 MW | 0.3 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964802 | AG1-343 E | 80/20 | 0.45 MW | 0.45 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965191 | AG1-384 C | 80/20 | 0.58 MW | 0.58 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965192 | AG1-384 E | 80/20 | 0.87 MW | 0.87 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 966251 | AG1-494 C | 80/20 | 1.21 MW | 1.21 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 966252 | AG1-494 E | 80/20 | 1.82 MW | 1.82 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 966691 | AG1-539 C | 80/20 | 1.69 MW | 1.69 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 966692 | AG1-539 E | 80/20 | 2.27 MW | 2.27 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963311 | AG1-180 C | 80/20 | 1.51 MW | 1.51 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963312 | AG1-180 E | 80/20 | 1.26 MW | 1.26 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963351 | AG1-184 C | 80/20 | 10.7 MW | 10.7 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963352 | AG1-184 E | 80/20 | 7.63 MW | 7.63 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963361 | AG1-185 C | 80/20 | 7.95 MW | 7.95 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963362 | AG1-185 E | 80/20 | 6.67 MW | 6.67 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965581 | AG1-426 C | 80/20 | 4.61 MW | 4.61 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 940541 | AE2-040 C | 80/20 | 0.95 MW | 0.95 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 940651 | AE2-052 C | 80/20 | 1.07 MW | 1.07 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 940661 | AE2-053 C | 80/20 | 2.12 MW | 2.12 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941281 | AE2-122 C | Adder | 6.56 MW | 5.58 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941282 | AE2-122 E | Adder | 26.48 MW | 22.51 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941291 | AE2-123 C | Adder | 6.74 MW | 5.73 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941292 | AE2-123 E | Adder | 26.3 MW | 22.36 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941301 | AE2-124 C | Adder | 6.14 MW | 5.22 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941302 | AE2-124 E | Adder | 26.92 MW | 22.89 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941591 | AE2-156 C | Adder | 5.15 MW | 4.38 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 943571 | AF1-028 C | Adder | -11.38 MW | -9.67 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944141 | AF1-082 C | Adder | 0.95 MW | 0.81 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944581 | AF1-123 C | Adder | 11.07 MW | 9.41 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944582 | AF1-123 E | Adder | 25.34 MW | 21.54 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944591 | AF1-124 C | Adder | 11.07 MW | 9.41 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944592 | AF1-124 E | Adder | 25.34 MW | 21.54 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944601 | AF1-125 C | Adder | 11.07 MW | 9.41 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944602 | AF1-125 E | Adder | 25.34 MW | 21.54 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944641 | AF1-129 C | Adder | 29.63 MW | 25.19 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 946011 | AF1-266 C | 80/20 | 4.5 MW | 4.5 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 946291 | AF1-293 C | 80/20 | 9.21 MW | 9.21 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 946292 | AF1-293 E | 80/20 | 13.82 MW | 13.82 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 961602 | AG1-000A E | Adder | 1.83 MW | 1.55 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964951 | AG1-359 C | Adder | 6.59 MW | 5.61 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965001 | AG1-364 C | Adder | 2.06 MW | 1.75 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965002 | AG1-364 E | Adder | 3.09 MW | 2.63 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965741 | AG1-442 C | 80/20 | 1.9 MW | 1.9 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965751 | AG1-443 C | 80/20 | 1.9 MW | 1.9 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965761 | AG1-444 C | Adder | 4.16 MW | 3.54 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965771 | AG1-445 C | 80/20 | 2.48 MW | 2.48 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965781 | AG1-446 C | 80/20 | 2.48 MW | 2.48 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965811 | AG1-449 C | 80/20 | 8.01 MW | 8.01 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965831 | AG1-451 C | 80/20 | 5.05 MW | 5.05 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 316303 | AF2-085 | 80/20 | 2.02 MW | 2.02 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 943573 | AF1-028 BT | 80/20 | 11.38 MW | 11.38 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 958502 | AF2-144 E | Adder | 2.92 MW | 2.48 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963023 | AG1-151 BT | 80/20 | 5.69 MW | 5.69 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963463 | AG1-195 BT | 80/20 | 9.01 MW | 9.01 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963473 | AG1-196 BT | 80/20 | 11.14 MW | 11.14 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965543 | AG1-422 BT | 80/20 | 3.41 MW | 3.41 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 966673 | AG1-537 BT | 80/20 | 4.79 MW | 4.79 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 966853 | AG1-556 BT | 80/20 | 5.56 MW | 5.56 MW |
| Details for AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 315083 | 1SPRUNCA | 80/20 | 1.45 MW | 1.45 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 315084 | 1SPRUNCB | 80/20 | 1.45 MW | 1.45 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 941032 | AE2-094 E | 80/20 | 11.09 MW | 11.09 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 944012 | AF1-069 E | 80/20 | 3.62 MW | 3.62 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 961062 | AF2-397 E | 80/20 | 25.8 MW | 25.8 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 961942 | AG1-037 E | 80/20 | 0.09 MW | 0.09 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 962332 | AG1-082 E | 80/20 | 0.35 MW | 0.35 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 962342 | AG1-083 E | 80/20 | 0.35 MW | 0.35 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963041 | AG1-153 C | 80/20 | 1.62 MW | 1.62 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963042 | AG1-153 E | 80/20 | 2.43 MW | 2.43 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963102 | AG1-159 E | 80/20 | 1.05 MW | 1.05 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963111 | AG1-160 C | 80/20 | 1.62 MW | 1.62 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963112 | AG1-160 E | 80/20 | 2.42 MW | 2.42 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964111 | AG1-272 C | 80/20 | 0.54 MW | 0.54 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964112 | AG1-272 E | 80/20 | 0.81 MW | 0.81 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964121 | AG1-273 C | 80/20 | 0.54 MW | 0.54 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964122 | AG1-273 E | 80/20 | 0.81 MW | 0.81 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964131 | AG1-274 C | 80/20 | 0.54 MW | 0.54 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964132 | AG1-274 E | 80/20 | 0.81 MW | 0.81 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964791 | AG1-342 C | 80/20 | 0.32 MW | 0.32 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964792 | AG1-342 E | 80/20 | 0.47 MW | 0.47 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964801 | AG1-343 C | 80/20 | 0.28 MW | 0.28 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964802 | AG1-343 E | 80/20 | 0.41 MW | 0.41 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 965191 | AG1-384 C | 80/20 | 0.54 MW | 0.54 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 965192 | AG1-384 E | 80/20 | 0.81 MW | 0.81 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963311 | AG1-180 C | 80/20 | 1.38 MW | 1.38 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963312 | AG1-180 E | 80/20 | 1.15 MW | 1.15 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963351 | AG1-184 C | 80/20 | 9.2 MW | 9.2 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963352 | AG1-184 E | 80/20 | 6.57 MW | 6.57 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963361 | AG1-185 C | 80/20 | 7.42 MW | 7.42 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963362 | AG1-185 E | 80/20 | 6.23 MW | 6.23 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 965581 | AG1-426 C | 80/20 | 4.34 MW | 4.34 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 961611 | AG1-000B C | Adder | 1.52 MW | 1.29 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 940541 | AE2-040 C | 80/20 | 0.86 MW | 0.86 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 940651 | AE2-052 C | 80/20 | 1.05 MW | 1.05 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 940661 | AE2-053 C | 80/20 | 1.93 MW | 1.93 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 942551 | AE2-270 C | Adder | 3.07 MW | 2.61 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 942552 | AE2-270 E | Adder | 4.6 MW | 3.91 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 943571 | AF1-028 C | Adder | -15.09 MW | -12.83 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 944581 | AF1-123 C | Adder | 10.67 MW | 9.07 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 944582 | AF1-123 E | Adder | 24.43 MW | 20.76 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 944591 | AF1-124 C | Adder | 10.67 MW | 9.07 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 944592 | AF1-124 E | Adder | 24.43 MW | 20.76 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 944601 | AF1-125 C | Adder | 10.67 MW | 9.07 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 944602 | AF1-125 E | Adder | 24.43 MW | 20.76 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 944631 | AF1-128 C | 80/20 | 11.27 MW | 11.27 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 944641 | AF1-129 C | 80/20 | 30.59 MW | 30.59 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 946011 | AF1-266 C | 80/20 | 4.07 MW | 4.07 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 946291 | AF1-293 C | 80/20 | 8.65 MW | 8.65 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 946292 | AF1-293 E | 80/20 | 12.97 MW | 12.97 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 961612 | AG1-000B E | Adder | 2.28 MW | 1.93 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 961711 | AG1-011 C | Adder | 8.19 MW | 6.96 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 965771 | AG1-445 C | 80/20 | 2.25 MW | 2.25 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 965781 | AG1-446 C | 80/20 | 2.25 MW | 2.25 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 965811 | AG1-449 C | 80/20 | 6.82 MW | 6.82 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 965831 | AG1-451 C | 80/20 | 4.8 MW | 4.8 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 316303 | AF2-085 | 80/20 | 1.82 MW | 1.82 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 943573 | AF1-028 BT | 80/20 | 15.09 MW | 15.09 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 958502 | AF2-144 E | Adder | 2.77 MW | 2.36 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963023 | AG1-151 BT | 80/20 | 7.55 MW | 7.55 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963463 | AG1-195 BT | 80/20 | 12.72 MW | 12.72 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963473 | AG1-196 BT | 80/20 | 14.56 MW | 14.56 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 965543 | AG1-422 BT | 80/20 | 4.71 MW | 4.71 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 966673 | AG1-537 BT | 80/20 | 6.68 MW | 6.68 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 966853 | AG1-556 BT | 80/20 | 8.13 MW | 8.13 MW |
| Details for 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 314295 | 6BIRDNECK | 80/20 | 0.04 MW | 0.04 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 315131 | 1EDGECMA | 80/20 | 2.56 MW | 2.56 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 315605 | 6W1-029WIND | 80/20 | 0.66 MW | 0.66 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 315611 | 6Z1-036WIND | 80/20 | 1.91 MW | 1.91 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 901082 | W1-029 E | 80/20 | 4.42 MW | 4.42 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 916042 | Z1-036 E | 80/20 | 8.04 MW | 8.04 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 916192 | Z1-068 E | 80/20 | 0.25 MW | 0.25 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 941032 | AE2-094 E | 80/20 | 14.54 MW | 14.54 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 944012 | AF1-069 E | 80/20 | 4.75 MW | 4.75 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 961942 | AG1-037 E | 80/20 | 0.11 MW | 0.11 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 962332 | AG1-082 E | 80/20 | 0.43 MW | 0.43 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 962342 | AG1-083 E | 80/20 | 0.43 MW | 0.43 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 963041 | AG1-153 C | 80/20 | 2.01 MW | 2.01 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 963042 | AG1-153 E | 80/20 | 3.01 MW | 3.01 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 963102 | AG1-159 E | 80/20 | 1.24 MW | 1.24 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 963111 | AG1-160 C | 80/20 | 2.04 MW | 2.04 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 963112 | AG1-160 E | 80/20 | 3.06 MW | 3.06 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 964801 | AG1-343 C | 80/20 | 0.33 MW | 0.33 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 964802 | AG1-343 E | 80/20 | 0.5 MW | 0.5 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 963311 | AG1-180 C | 80/20 | 1.05 MW | 1.05 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 963312 | AG1-180 E | 80/20 | 0.87 MW | 0.87 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 963351 | AG1-184 C | 80/20 | 12.39 MW | 12.39 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 963352 | AG1-184 E | 80/20 | 8.85 MW | 8.85 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 961611 | AG1-000B C | 80/20 | 2.51 MW | 2.51 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 940541 | AE2-040 C | 80/20 | 1.65 MW | 1.65 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 940651 | AE2-052 C | 80/20 | 2.49 MW | 2.49 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 941281 | AE2-122 C | 80/20 | 7.68 MW | 7.68 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 941282 | AE2-122 E | 80/20 | 31.01 MW | 31.01 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 941291 | AE2-123 C | 80/20 | 7.9 MW | 7.9 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 941292 | AE2-123 E | 80/20 | 30.8 MW | 30.8 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 941301 | AE2-124 C | 80/20 | 7.17 MW | 7.17 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 941302 | AE2-124 E | 80/20 | 31.47 MW | 31.47 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 941591 | AE2-156 C | 80/20 | 6.11 MW | 6.11 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 942551 | AE2-270 C | 80/20 | 5.9 MW | 5.9 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 942552 | AE2-270 E | 80/20 | 8.85 MW | 8.85 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 944141 | AF1-082 C | 80/20 | 1.02 MW | 1.02 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 944581 | AF1-123 C | 80/20 | 12.5 MW | 12.5 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 944582 | AF1-123 E | 80/20 | 28.63 MW | 28.63 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 944591 | AF1-124 C | 80/20 | 12.5 MW | 12.5 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 944592 | AF1-124 E | 80/20 | 28.63 MW | 28.63 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 944601 | AF1-125 C | 80/20 | 12.5 MW | 12.5 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 944602 | AF1-125 E | 80/20 | 28.63 MW | 28.63 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 944641 | AF1-129 C | 80/20 | 136.08 MW | 136.08 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 946011 | AF1-266 C | 80/20 | 7.63 MW | 7.63 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 961602 | AG1-000A E | 80/20 | 1.99 MW | 1.99 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 961612 | AG1-000B E | 80/20 | 3.77 MW | 3.77 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 961711 | AG1-011 C | 80/20 | 15.75 MW | 15.75 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 964951 | AG1-359 C | 80/20 | 7.63 MW | 7.63 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 965001 | AG1-364 C | 80/20 | 2.44 MW | 2.44 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 965002 | AG1-364 E | 80/20 | 3.67 MW | 3.67 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 965741 | AG1-442 C | 80/20 | 2.19 MW | 2.19 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 965751 | AG1-443 C | 80/20 | 2.19 MW | 2.19 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 965761 | AG1-444 C | 80/20 | 4.57 MW | 4.57 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 965771 | AG1-445 C | 80/20 | 1.33 MW | 1.33 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 965781 | AG1-446 C | 80/20 | 1.33 MW | 1.33 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 965811 | AG1-449 C | 80/20 | 8.42 MW | 8.42 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 974591 | AF2-085 BE | 80/20 | 1.82 MW | 1.82 MW |
| Details for 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217_SRT-A | 314295 | 6BIRDNECK | 80/20 | 0.03 MW | 0.03 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217_SRT-A | 315605 | 6W1-029WIND | 80/20 | 0.56 MW | 0.56 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217_SRT-A | 315611 | 6Z1-036WIND | 80/20 | 1.63 MW | 1.63 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217_SRT-A | 901082 | W1-029 E | 80/20 | 3.76 MW | 3.76 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217_SRT-A | 916042 | Z1-036 E | 80/20 | 6.87 MW | 6.87 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217_SRT-A | 916192 | Z1-068 E | 80/20 | 0.21 MW | 0.21 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217_SRT-A | 961942 | AG1-037 E | 80/20 | 0.09 MW | 0.09 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217_SRT-A | 962332 | AG1-082 E | 80/20 | 0.39 MW | 0.39 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217_SRT-A | 962342 | AG1-083 E | 80/20 | 0.39 MW | 0.39 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217_SRT-A | 963102 | AG1-159 E | 80/20 | 1.1 MW | 1.1 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217_SRT-A | 964801 | AG1-343 C | 80/20 | 0.3 MW | 0.3 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217_SRT-A | 964802 | AG1-343 E | 80/20 | 0.45 MW | 0.45 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217_SRT-A | 963311 | AG1-180 C | 80/20 | 0.95 MW | 0.95 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217_SRT-A | 963312 | AG1-180 E | 80/20 | 0.8 MW | 0.8 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217_SRT-A | 961611 | AG1-000B C | 80/20 | 2.68 MW | 2.68 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217_SRT-A | 940541 | AE2-040 C | 80/20 | 1.67 MW | 1.67 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217_SRT-A | 940651 | AE2-052 C | 80/20 | 2.83 MW | 2.83 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217_SRT-A | 941281 | AE2-122 C | 80/20 | 6.47 MW | 6.47 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217_SRT-A | 941282 | AE2-122 E | 80/20 | 26.09 MW | 26.09 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217_SRT-A | 941291 | AE2-123 C | 80/20 | 6.65 MW | 6.65 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217_SRT-A | 941292 | AE2-123 E | 80/20 | 25.91 MW | 25.91 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217_SRT-A | 941301 | AE2-124 C | 80/20 | 6.03 MW | 6.03 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217_SRT-A | 941302 | AE2-124 E | 80/20 | 26.45 MW | 26.45 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217_SRT-A | 941591 | AE2-156 C | 80/20 | 5.2 MW | 5.2 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217_SRT-A | 942551 | AE2-270 C | 80/20 | 6.67 MW | 6.67 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217_SRT-A | 942552 | AE2-270 E | 80/20 | 10.0 MW | 10.0 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217_SRT-A | 944581 | AF1-123 C | Adder | 10.15 MW | 8.63 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217_SRT-A | 944582 | AF1-123 E | Adder | 23.25 MW | 19.76 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217_SRT-A | 944591 | AF1-124 C | Adder | 10.15 MW | 8.63 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217_SRT-A | 944592 | AF1-124 E | Adder | 23.25 MW | 19.76 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217_SRT-A | 944601 | AF1-125 C | Adder | 10.15 MW | 8.63 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217_SRT-A | 944602 | AF1-125 E | Adder | 23.25 MW | 19.76 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217_SRT-A | 944641 | AF1-129 C | 80/20 | 169.16 MW | 169.16 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217_SRT-A | 946011 | AF1-266 C | 80/20 | 7.68 MW | 7.68 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217_SRT-A | 961612 | AG1-000B E | 80/20 | 4.02 MW | 4.02 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217_SRT-A | 961711 | AG1-011 C | 80/20 | 17.8 MW | 17.8 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217_SRT-A | 965001 | AG1-364 C | 80/20 | 2.08 MW | 2.08 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217_SRT-A | 965002 | AG1-364 E | 80/20 | 3.12 MW | 3.12 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217_SRT-A | 965741 | AG1-442 C | 80/20 | 1.91 MW | 1.91 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217_SRT-A | 965751 | AG1-443 C | 80/20 | 1.91 MW | 1.91 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217_SRT-A | 974591 | AF2-085 BE | 80/20 | 1.45 MW | 1.45 MW |
| Details for 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315083 | 1SPRUNCA | 80/20 | 1.43 MW | 1.43 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315084 | 1SPRUNCB | 80/20 | 1.43 MW | 1.43 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315131 | 1EDGECMA | Adder | 2.35 MW | 2.0 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315611 | 6Z1-036WIND | Adder | 1.64 MW | 1.4 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 916042 | Z1-036 E | Adder | 6.92 MW | 5.89 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941032 | AE2-094 E | 80/20 | 13.11 MW | 13.11 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944012 | AF1-069 E | 80/20 | 4.28 MW | 4.28 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 961062 | AF2-397 E | 80/20 | 26.63 MW | 26.63 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 961942 | AG1-037 E | 80/20 | 0.1 MW | 0.1 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 962332 | AG1-082 E | 80/20 | 0.39 MW | 0.39 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 962342 | AG1-083 E | 80/20 | 0.39 MW | 0.39 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963041 | AG1-153 C | 80/20 | 1.91 MW | 1.91 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963042 | AG1-153 E | 80/20 | 2.87 MW | 2.87 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963102 | AG1-159 E | 80/20 | 1.19 MW | 1.19 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963111 | AG1-160 C | 80/20 | 1.91 MW | 1.91 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963112 | AG1-160 E | 80/20 | 2.86 MW | 2.86 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964111 | AG1-272 C | 80/20 | 0.58 MW | 0.58 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964112 | AG1-272 E | 80/20 | 0.87 MW | 0.87 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964121 | AG1-273 C | 80/20 | 0.58 MW | 0.58 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964122 | AG1-273 E | 80/20 | 0.87 MW | 0.87 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964131 | AG1-274 C | 80/20 | 0.58 MW | 0.58 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964132 | AG1-274 E | 80/20 | 0.87 MW | 0.87 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964791 | AG1-342 C | 80/20 | 0.35 MW | 0.35 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964792 | AG1-342 E | 80/20 | 0.53 MW | 0.53 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964801 | AG1-343 C | 80/20 | 0.3 MW | 0.3 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964802 | AG1-343 E | 80/20 | 0.45 MW | 0.45 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965191 | AG1-384 C | 80/20 | 0.58 MW | 0.58 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965192 | AG1-384 E | 80/20 | 0.87 MW | 0.87 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 966251 | AG1-494 C | 80/20 | 1.21 MW | 1.21 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 966252 | AG1-494 E | 80/20 | 1.82 MW | 1.82 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 966691 | AG1-539 C | 80/20 | 1.69 MW | 1.69 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 966692 | AG1-539 E | 80/20 | 2.27 MW | 2.27 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963311 | AG1-180 C | 80/20 | 1.51 MW | 1.51 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963312 | AG1-180 E | 80/20 | 1.26 MW | 1.26 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963351 | AG1-184 C | 80/20 | 10.7 MW | 10.7 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963352 | AG1-184 E | 80/20 | 7.63 MW | 7.63 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963361 | AG1-185 C | 80/20 | 7.95 MW | 7.95 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963362 | AG1-185 E | 80/20 | 6.67 MW | 6.67 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965581 | AG1-426 C | 80/20 | 4.61 MW | 4.61 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 940541 | AE2-040 C | 80/20 | 0.95 MW | 0.95 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 940651 | AE2-052 C | 80/20 | 1.07 MW | 1.07 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 940661 | AE2-053 C | 80/20 | 2.12 MW | 2.12 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941281 | AE2-122 C | Adder | 6.56 MW | 5.58 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941282 | AE2-122 E | Adder | 26.48 MW | 22.51 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941291 | AE2-123 C | Adder | 6.74 MW | 5.73 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941292 | AE2-123 E | Adder | 26.3 MW | 22.36 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941301 | AE2-124 C | Adder | 6.14 MW | 5.22 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941302 | AE2-124 E | Adder | 26.92 MW | 22.89 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941591 | AE2-156 C | Adder | 5.15 MW | 4.38 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 943571 | AF1-028 C | Adder | -11.38 MW | -9.67 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944141 | AF1-082 C | Adder | 0.95 MW | 0.81 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944581 | AF1-123 C | Adder | 11.07 MW | 9.41 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944582 | AF1-123 E | Adder | 25.34 MW | 21.54 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944591 | AF1-124 C | Adder | 11.07 MW | 9.41 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944592 | AF1-124 E | Adder | 25.34 MW | 21.54 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944601 | AF1-125 C | Adder | 11.07 MW | 9.41 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944602 | AF1-125 E | Adder | 25.34 MW | 21.54 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944641 | AF1-129 C | Adder | 29.63 MW | 25.19 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 946011 | AF1-266 C | 80/20 | 4.5 MW | 4.5 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 946291 | AF1-293 C | 80/20 | 9.21 MW | 9.21 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 946292 | AF1-293 E | 80/20 | 13.82 MW | 13.82 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 961602 | AG1-000A E | Adder | 1.83 MW | 1.55 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964951 | AG1-359 C | Adder | 6.59 MW | 5.61 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965001 | AG1-364 C | Adder | 2.06 MW | 1.75 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965002 | AG1-364 E | Adder | 3.09 MW | 2.63 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965741 | AG1-442 C | 80/20 | 1.9 MW | 1.9 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965751 | AG1-443 C | 80/20 | 1.9 MW | 1.9 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965761 | AG1-444 C | Adder | 4.16 MW | 3.54 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965771 | AG1-445 C | 80/20 | 2.48 MW | 2.48 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965781 | AG1-446 C | 80/20 | 2.48 MW | 2.48 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965811 | AG1-449 C | 80/20 | 8.01 MW | 8.01 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965831 | AG1-451 C | 80/20 | 5.05 MW | 5.05 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 316303 | AF2-085 | 80/20 | 2.02 MW | 2.02 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 943573 | AF1-028 BT | 80/20 | 11.38 MW | 11.38 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 958502 | AF2-144 E | Adder | 2.92 MW | 2.48 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963023 | AG1-151 BT | 80/20 | 5.69 MW | 5.69 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963463 | AG1-195 BT | 80/20 | 9.01 MW | 9.01 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963473 | AG1-196 BT | 80/20 | 11.14 MW | 11.14 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965543 | AG1-422 BT | 80/20 | 3.41 MW | 3.41 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 966673 | AG1-537 BT | 80/20 | 4.79 MW | 4.79 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 966853 | AG1-556 BT | 80/20 | 5.56 MW | 5.56 MW |
| Details for 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 315083 | 1SPRUNCA | 80/20 | 1.45 MW | 1.45 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 315084 | 1SPRUNCB | 80/20 | 1.45 MW | 1.45 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 941032 | AE2-094 E | 80/20 | 11.09 MW | 11.09 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 944012 | AF1-069 E | 80/20 | 3.62 MW | 3.62 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 961062 | AF2-397 E | 80/20 | 25.8 MW | 25.8 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 961942 | AG1-037 E | 80/20 | 0.09 MW | 0.09 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 962332 | AG1-082 E | 80/20 | 0.35 MW | 0.35 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 962342 | AG1-083 E | 80/20 | 0.35 MW | 0.35 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963041 | AG1-153 C | 80/20 | 1.62 MW | 1.62 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963042 | AG1-153 E | 80/20 | 2.43 MW | 2.43 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963102 | AG1-159 E | 80/20 | 1.05 MW | 1.05 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963111 | AG1-160 C | 80/20 | 1.62 MW | 1.62 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963112 | AG1-160 E | 80/20 | 2.42 MW | 2.42 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964111 | AG1-272 C | 80/20 | 0.54 MW | 0.54 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964112 | AG1-272 E | 80/20 | 0.81 MW | 0.81 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964121 | AG1-273 C | 80/20 | 0.54 MW | 0.54 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964122 | AG1-273 E | 80/20 | 0.81 MW | 0.81 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964131 | AG1-274 C | 80/20 | 0.54 MW | 0.54 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964132 | AG1-274 E | 80/20 | 0.81 MW | 0.81 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964791 | AG1-342 C | 80/20 | 0.32 MW | 0.32 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964792 | AG1-342 E | 80/20 | 0.47 MW | 0.47 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964801 | AG1-343 C | 80/20 | 0.28 MW | 0.28 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964802 | AG1-343 E | 80/20 | 0.41 MW | 0.41 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 965191 | AG1-384 C | 80/20 | 0.54 MW | 0.54 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 965192 | AG1-384 E | 80/20 | 0.81 MW | 0.81 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963311 | AG1-180 C | 80/20 | 1.38 MW | 1.38 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963312 | AG1-180 E | 80/20 | 1.15 MW | 1.15 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963351 | AG1-184 C | 80/20 | 9.2 MW | 9.2 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963352 | AG1-184 E | 80/20 | 6.57 MW | 6.57 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963361 | AG1-185 C | 80/20 | 7.42 MW | 7.42 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963362 | AG1-185 E | 80/20 | 6.23 MW | 6.23 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 965581 | AG1-426 C | 80/20 | 4.34 MW | 4.34 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 961611 | AG1-000B C | Adder | 1.52 MW | 1.29 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 940541 | AE2-040 C | 80/20 | 0.86 MW | 0.86 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 940651 | AE2-052 C | 80/20 | 1.05 MW | 1.05 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 940661 | AE2-053 C | 80/20 | 1.93 MW | 1.93 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 942551 | AE2-270 C | Adder | 3.07 MW | 2.61 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 942552 | AE2-270 E | Adder | 4.6 MW | 3.91 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 943571 | AF1-028 C | Adder | -15.09 MW | -12.83 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 944581 | AF1-123 C | Adder | 10.67 MW | 9.07 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 944582 | AF1-123 E | Adder | 24.43 MW | 20.76 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 944591 | AF1-124 C | Adder | 10.67 MW | 9.07 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 944592 | AF1-124 E | Adder | 24.43 MW | 20.76 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 944601 | AF1-125 C | Adder | 10.67 MW | 9.07 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 944602 | AF1-125 E | Adder | 24.43 MW | 20.76 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 944631 | AF1-128 C | 80/20 | 11.27 MW | 11.27 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 944641 | AF1-129 C | 80/20 | 30.59 MW | 30.59 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 946011 | AF1-266 C | 80/20 | 4.07 MW | 4.07 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 946291 | AF1-293 C | 80/20 | 8.65 MW | 8.65 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 946292 | AF1-293 E | 80/20 | 12.97 MW | 12.97 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 961612 | AG1-000B E | Adder | 2.28 MW | 1.93 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 961711 | AG1-011 C | Adder | 8.19 MW | 6.96 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 965771 | AG1-445 C | 80/20 | 2.25 MW | 2.25 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 965781 | AG1-446 C | 80/20 | 2.25 MW | 2.25 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 965811 | AG1-449 C | 80/20 | 6.82 MW | 6.82 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 965831 | AG1-451 C | 80/20 | 4.8 MW | 4.8 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 316303 | AF2-085 | 80/20 | 1.82 MW | 1.82 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 943573 | AF1-028 BT | 80/20 | 15.09 MW | 15.09 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 958502 | AF2-144 E | Adder | 2.77 MW | 2.36 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963023 | AG1-151 BT | 80/20 | 7.55 MW | 7.55 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963463 | AG1-195 BT | 80/20 | 12.72 MW | 12.72 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963473 | AG1-196 BT | 80/20 | 14.56 MW | 14.56 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 965543 | AG1-422 BT | 80/20 | 4.71 MW | 4.71 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 966673 | AG1-537 BT | 80/20 | 6.68 MW | 6.68 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 966853 | AG1-556 BT | 80/20 | 8.13 MW | 8.13 MW |
| Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315083 | 1SPRUNCA | 80/20 | 1.43 MW | 1.43 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315084 | 1SPRUNCB | 80/20 | 1.43 MW | 1.43 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315131 | 1EDGECMA | Adder | 2.35 MW | 2.0 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 315611 | 6Z1-036WIND | Adder | 1.64 MW | 1.4 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 916042 | Z1-036 E | Adder | 6.92 MW | 5.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941032 | AE2-094 E | 80/20 | 13.11 MW | 13.11 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944012 | AF1-069 E | 80/20 | 4.28 MW | 4.28 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 961062 | AF2-397 E | 80/20 | 26.63 MW | 26.63 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 961942 | AG1-037 E | 80/20 | 0.1 MW | 0.1 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 962332 | AG1-082 E | 80/20 | 0.39 MW | 0.39 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 962342 | AG1-083 E | 80/20 | 0.39 MW | 0.39 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963041 | AG1-153 C | 80/20 | 1.91 MW | 1.91 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963042 | AG1-153 E | 80/20 | 2.87 MW | 2.87 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963102 | AG1-159 E | 80/20 | 1.19 MW | 1.19 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963111 | AG1-160 C | 80/20 | 1.91 MW | 1.91 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963112 | AG1-160 E | 80/20 | 2.86 MW | 2.86 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964111 | AG1-272 C | 80/20 | 0.58 MW | 0.58 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964112 | AG1-272 E | 80/20 | 0.87 MW | 0.87 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964121 | AG1-273 C | 80/20 | 0.58 MW | 0.58 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964122 | AG1-273 E | 80/20 | 0.87 MW | 0.87 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964131 | AG1-274 C | 80/20 | 0.58 MW | 0.58 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964132 | AG1-274 E | 80/20 | 0.87 MW | 0.87 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964791 | AG1-342 C | 80/20 | 0.35 MW | 0.35 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964792 | AG1-342 E | 80/20 | 0.53 MW | 0.53 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964801 | AG1-343 C | 80/20 | 0.3 MW | 0.3 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964802 | AG1-343 E | 80/20 | 0.45 MW | 0.45 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965191 | AG1-384 C | 80/20 | 0.58 MW | 0.58 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965192 | AG1-384 E | 80/20 | 0.87 MW | 0.87 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 966251 | AG1-494 C | 80/20 | 1.21 MW | 1.21 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 966252 | AG1-494 E | 80/20 | 1.82 MW | 1.82 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 966691 | AG1-539 C | 80/20 | 1.69 MW | 1.69 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 966692 | AG1-539 E | 80/20 | 2.27 MW | 2.27 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963311 | AG1-180 C | 80/20 | 1.51 MW | 1.51 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963312 | AG1-180 E | 80/20 | 1.26 MW | 1.26 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963351 | AG1-184 C | 80/20 | 10.7 MW | 10.7 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963352 | AG1-184 E | 80/20 | 7.63 MW | 7.63 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963361 | AG1-185 C | 80/20 | 7.95 MW | 7.95 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963362 | AG1-185 E | 80/20 | 6.67 MW | 6.67 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965581 | AG1-426 C | 80/20 | 4.61 MW | 4.61 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 940541 | AE2-040 C | 80/20 | 0.95 MW | 0.95 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 940651 | AE2-052 C | 80/20 | 1.07 MW | 1.07 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 940661 | AE2-053 C | 80/20 | 2.12 MW | 2.12 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941281 | AE2-122 C | Adder | 6.56 MW | 5.58 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941282 | AE2-122 E | Adder | 26.48 MW | 22.51 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941291 | AE2-123 C | Adder | 6.74 MW | 5.73 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941292 | AE2-123 E | Adder | 26.3 MW | 22.36 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941301 | AE2-124 C | Adder | 6.14 MW | 5.22 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941302 | AE2-124 E | Adder | 26.92 MW | 22.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 941591 | AE2-156 C | Adder | 5.15 MW | 4.38 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 943571 | AF1-028 C | Adder | -11.38 MW | -9.67 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944141 | AF1-082 C | Adder | 0.95 MW | 0.81 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944581 | AF1-123 C | Adder | 11.07 MW | 9.41 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944582 | AF1-123 E | Adder | 25.34 MW | 21.54 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944591 | AF1-124 C | Adder | 11.07 MW | 9.41 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944592 | AF1-124 E | Adder | 25.34 MW | 21.54 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944601 | AF1-125 C | Adder | 11.07 MW | 9.41 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944602 | AF1-125 E | Adder | 25.34 MW | 21.54 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 944641 | AF1-129 C | Adder | 29.63 MW | 25.19 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 946011 | AF1-266 C | 80/20 | 4.5 MW | 4.5 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 946291 | AF1-293 C | 80/20 | 9.21 MW | 9.21 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 946292 | AF1-293 E | 80/20 | 13.82 MW | 13.82 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 961602 | AG1-000A E | Adder | 1.83 MW | 1.55 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 964951 | AG1-359 C | Adder | 6.59 MW | 5.61 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965001 | AG1-364 C | Adder | 2.06 MW | 1.75 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965002 | AG1-364 E | Adder | 3.09 MW | 2.63 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965741 | AG1-442 C | 80/20 | 1.9 MW | 1.9 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965751 | AG1-443 C | 80/20 | 1.9 MW | 1.9 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965761 | AG1-444 C | Adder | 4.16 MW | 3.54 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965771 | AG1-445 C | 80/20 | 2.48 MW | 2.48 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965781 | AG1-446 C | 80/20 | 2.48 MW | 2.48 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965811 | AG1-449 C | 80/20 | 8.01 MW | 8.01 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965831 | AG1-451 C | 80/20 | 5.05 MW | 5.05 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 316303 | AF2-085 | 80/20 | 2.02 MW | 2.02 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 943573 | AF1-028 BT | 80/20 | 11.38 MW | 11.38 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 958502 | AF2-144 E | Adder | 2.92 MW | 2.48 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963023 | AG1-151 BT | 80/20 | 5.69 MW | 5.69 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963463 | AG1-195 BT | 80/20 | 9.01 MW | 9.01 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 963473 | AG1-196 BT | 80/20 | 11.14 MW | 11.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 965543 | AG1-422 BT | 80/20 | 3.41 MW | 3.41 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 966673 | AG1-537 BT | 80/20 | 4.79 MW | 4.79 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-A | 966853 | AG1-556 BT | 80/20 | 5.56 MW | 5.56 MW |
| Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 315083 | 1SPRUNCA | 80/20 | 1.45 MW | 1.45 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 315084 | 1SPRUNCB | 80/20 | 1.45 MW | 1.45 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 941032 | AE2-094 E | 80/20 | 11.09 MW | 11.09 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 944012 | AF1-069 E | 80/20 | 3.62 MW | 3.62 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 961062 | AF2-397 E | 80/20 | 25.8 MW | 25.8 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 961942 | AG1-037 E | 80/20 | 0.09 MW | 0.09 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 962332 | AG1-082 E | 80/20 | 0.35 MW | 0.35 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 962342 | AG1-083 E | 80/20 | 0.35 MW | 0.35 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963041 | AG1-153 C | 80/20 | 1.62 MW | 1.62 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963042 | AG1-153 E | 80/20 | 2.43 MW | 2.43 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963102 | AG1-159 E | 80/20 | 1.05 MW | 1.05 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963111 | AG1-160 C | 80/20 | 1.62 MW | 1.62 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963112 | AG1-160 E | 80/20 | 2.42 MW | 2.42 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964111 | AG1-272 C | 80/20 | 0.54 MW | 0.54 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964112 | AG1-272 E | 80/20 | 0.81 MW | 0.81 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964121 | AG1-273 C | 80/20 | 0.54 MW | 0.54 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964122 | AG1-273 E | 80/20 | 0.81 MW | 0.81 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964131 | AG1-274 C | 80/20 | 0.54 MW | 0.54 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964132 | AG1-274 E | 80/20 | 0.81 MW | 0.81 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964791 | AG1-342 C | 80/20 | 0.32 MW | 0.32 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964792 | AG1-342 E | 80/20 | 0.47 MW | 0.47 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964801 | AG1-343 C | 80/20 | 0.28 MW | 0.28 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 964802 | AG1-343 E | 80/20 | 0.41 MW | 0.41 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 965191 | AG1-384 C | 80/20 | 0.54 MW | 0.54 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 965192 | AG1-384 E | 80/20 | 0.81 MW | 0.81 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963311 | AG1-180 C | 80/20 | 1.38 MW | 1.38 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963312 | AG1-180 E | 80/20 | 1.15 MW | 1.15 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963351 | AG1-184 C | 80/20 | 9.2 MW | 9.2 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963352 | AG1-184 E | 80/20 | 6.57 MW | 6.57 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963361 | AG1-185 C | 80/20 | 7.42 MW | 7.42 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963362 | AG1-185 E | 80/20 | 6.23 MW | 6.23 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 965581 | AG1-426 C | 80/20 | 4.34 MW | 4.34 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 961611 | AG1-000B C | Adder | 1.52 MW | 1.29 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 940541 | AE2-040 C | 80/20 | 0.86 MW | 0.86 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 940651 | AE2-052 C | 80/20 | 1.05 MW | 1.05 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 940661 | AE2-053 C | 80/20 | 1.93 MW | 1.93 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 942551 | AE2-270 C | Adder | 3.07 MW | 2.61 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 942552 | AE2-270 E | Adder | 4.6 MW | 3.91 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 943571 | AF1-028 C | Adder | -15.09 MW | -12.83 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 944581 | AF1-123 C | Adder | 10.67 MW | 9.07 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 944582 | AF1-123 E | Adder | 24.43 MW | 20.76 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 944591 | AF1-124 C | Adder | 10.67 MW | 9.07 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 944592 | AF1-124 E | Adder | 24.43 MW | 20.76 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 944601 | AF1-125 C | Adder | 10.67 MW | 9.07 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 944602 | AF1-125 E | Adder | 24.43 MW | 20.76 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 944631 | AF1-128 C | 80/20 | 11.27 MW | 11.27 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 944641 | AF1-129 C | 80/20 | 30.59 MW | 30.59 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 946011 | AF1-266 C | 80/20 | 4.07 MW | 4.07 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 946291 | AF1-293 C | 80/20 | 8.65 MW | 8.65 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 946292 | AF1-293 E | 80/20 | 12.97 MW | 12.97 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 961612 | AG1-000B E | Adder | 2.28 MW | 1.93 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 961711 | AG1-011 C | Adder | 8.19 MW | 6.96 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 965771 | AG1-445 C | 80/20 | 2.25 MW | 2.25 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 965781 | AG1-446 C | 80/20 | 2.25 MW | 2.25 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 965811 | AG1-449 C | 80/20 | 6.82 MW | 6.82 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 965831 | AG1-451 C | 80/20 | 4.8 MW | 4.8 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 316303 | AF2-085 | 80/20 | 1.82 MW | 1.82 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 943573 | AF1-028 BT | 80/20 | 15.09 MW | 15.09 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 958502 | AF2-144 E | Adder | 2.77 MW | 2.36 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963023 | AG1-151 BT | 80/20 | 7.55 MW | 7.55 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963463 | AG1-195 BT | 80/20 | 12.72 MW | 12.72 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 963473 | AG1-196 BT | 80/20 | 14.56 MW | 14.56 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 965543 | AG1-422 BT | 80/20 | 4.71 MW | 4.71 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 966673 | AG1-537 BT | 80/20 | 6.68 MW | 6.68 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L | 966853 | AG1-556 BT | 80/20 | 8.13 MW | 8.13 MW |
| Details for 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 314295 | 6BIRDNECK | 80/20 | 0.07 MW | 0.07 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 315083 | 1SPRUNCA | 80/20 | 3.42 MW | 3.42 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 315084 | 1SPRUNCB | 80/20 | 3.42 MW | 3.42 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 315605 | 6W1-029WIND | 80/20 | 1.13 MW | 1.13 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 315611 | 6Z1-036WIND | 80/20 | 3.17 MW | 3.17 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 901082 | W1-029 E | 80/20 | 7.56 MW | 7.56 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 916042 | Z1-036 E | 80/20 | 13.37 MW | 13.37 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 916192 | Z1-068 E | 80/20 | 0.46 MW | 0.46 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 941032 | AE2-094 E | 80/20 | 17.91 MW | 17.91 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 961942 | AG1-037 E | 80/20 | 0.15 MW | 0.15 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 962332 | AG1-082 E | 80/20 | 0.61 MW | 0.61 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 962342 | AG1-083 E | 80/20 | 0.61 MW | 0.61 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 962531 | AG1-102 C | 80/20 | 0.77 MW | 0.77 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 962532 | AG1-102 E | 80/20 | 1.6 MW | 1.6 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 963611 | AG1-210 C | 80/20 | 0.46 MW | 0.46 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 963612 | AG1-210 E | 80/20 | 0.69 MW | 0.69 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 964801 | AG1-343 C | 80/20 | 0.46 MW | 0.46 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 964802 | AG1-343 E | 80/20 | 0.7 MW | 0.7 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 966661 | AG1-536 C | 80/20 | 3.79 MW | 3.79 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 966662 | AG1-536 E | 80/20 | 5.09 MW | 5.09 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 966872 | AG1-558 E | 80/20 | 2.4 MW | 2.4 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 966882 | AG1-559 E | 80/20 | 1.1 MW | 1.1 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 963351 | AG1-184 C | 80/20 | 16.2 MW | 16.2 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 963352 | AG1-184 E | 80/20 | 11.56 MW | 11.56 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 961611 | AG1-000B C | 80/20 | 3.77 MW | 3.77 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 316427 | AG1-213 C | 80/20 | 0.37 MW | 0.37 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 940541 | AE2-040 C | 80/20 | 1.62 MW | 1.62 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 940551 | AE2-041 C | 80/20 | 5.27 MW | 5.27 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 940651 | AE2-052 C | 80/20 | 2.52 MW | 2.52 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 941281 | AE2-122 C | 80/20 | 13.86 MW | 13.86 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 941282 | AE2-122 E | 80/20 | 55.93 MW | 55.93 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 941291 | AE2-123 C | 80/20 | 14.24 MW | 14.24 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 941292 | AE2-123 E | 80/20 | 55.55 MW | 55.55 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 941301 | AE2-124 C | 80/20 | 12.94 MW | 12.94 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 941302 | AE2-124 E | 80/20 | 56.79 MW | 56.79 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 941591 | AE2-156 C | 80/20 | 10.99 MW | 10.99 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 942551 | AE2-270 C | 80/20 | 7.92 MW | 7.92 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 942552 | AE2-270 E | 80/20 | 11.88 MW | 11.88 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 943471 | AF1-018 C | 80/20 | 5.27 MW | 5.27 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 944581 | AF1-123 C | 80/20 | 23.14 MW | 23.14 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 944582 | AF1-123 E | 80/20 | 52.98 MW | 52.98 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 944591 | AF1-124 C | 80/20 | 23.14 MW | 23.14 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 944592 | AF1-124 E | 80/20 | 52.98 MW | 52.98 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 944601 | AF1-125 C | 80/20 | 23.14 MW | 23.14 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 944602 | AF1-125 E | 80/20 | 52.98 MW | 52.98 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 944631 | AF1-128 C | 80/20 | 33.01 MW | 33.01 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 944641 | AF1-129 C | 80/20 | 84.31 MW | 84.31 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 945362 | AF1-201 E | 80/20 | 2.48 MW | 2.48 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 946011 | AF1-266 C | 80/20 | 7.58 MW | 7.58 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 961612 | AG1-000B E | 80/20 | 5.66 MW | 5.66 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 961711 | AG1-011 C | 80/20 | 21.13 MW | 21.13 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 964951 | AG1-359 C | 80/20 | 13.82 MW | 13.82 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 965001 | AG1-364 C | 80/20 | 4.4 MW | 4.4 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 965002 | AG1-364 E | 80/20 | 6.59 MW | 6.59 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 965741 | AG1-442 C | 80/20 | 3.23 MW | 3.23 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 965751 | AG1-443 C | 80/20 | 3.23 MW | 3.23 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 966871 | AG1-558 C | 80/20 | 0.26 MW | 0.26 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 966881 | AG1-559 C | 80/20 | 0.12 MW | 0.12 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 316303 | AF2-085 | 80/20 | 2.34 MW | 2.34 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 963622 | AG1-213 E | 80/20 | 0.37 MW | 0.37 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 963623 | AG1-213 BAT | 80/20 | 0.55 MW | 0.55 MW |
| Details for 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 2 transformer l/o DVP_P1-3: 4ALTVSTA-TX#3_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 2 transformer l/o DVP_P1-3: 4ALTVSTA-TX#3_SRT-A | 964791 | AG1-342 C | 80/20 | 0.31 MW | 0.31 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 2 transformer l/o DVP_P1-3: 4ALTVSTA-TX#3_SRT-A | 964792 | AG1-342 E | 80/20 | 0.47 MW | 0.47 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 2 transformer l/o DVP_P1-3: 4ALTVSTA-TX#3_SRT-A | 966691 | AG1-539 C | 80/20 | 13.26 MW | 13.26 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 2 transformer l/o DVP_P1-3: 4ALTVSTA-TX#3_SRT-A | 966692 | AG1-539 E | 80/20 | 17.82 MW | 17.82 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 2 transformer l/o DVP_P1-3: 4ALTVSTA-TX#3_SRT-A | 941281 | AE2-122 C | Adder | 1.59 MW | 1.35 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 2 transformer l/o DVP_P1-3: 4ALTVSTA-TX#3_SRT-A | 941282 | AE2-122 E | Adder | 6.43 MW | 5.46 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 2 transformer l/o DVP_P1-3: 4ALTVSTA-TX#3_SRT-A | 941291 | AE2-123 C | Adder | 1.64 MW | 1.39 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 2 transformer l/o DVP_P1-3: 4ALTVSTA-TX#3_SRT-A | 941292 | AE2-123 E | Adder | 6.38 MW | 5.43 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 2 transformer l/o DVP_P1-3: 4ALTVSTA-TX#3_SRT-A | 941301 | AE2-124 C | Adder | 1.49 MW | 1.27 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 2 transformer l/o DVP_P1-3: 4ALTVSTA-TX#3_SRT-A | 941302 | AE2-124 E | Adder | 6.54 MW | 5.56 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 2 transformer l/o DVP_P1-3: 4ALTVSTA-TX#3_SRT-A | 944581 | AF1-123 C | Adder | 2.69 MW | 2.29 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 2 transformer l/o DVP_P1-3: 4ALTVSTA-TX#3_SRT-A | 944582 | AF1-123 E | Adder | 6.15 MW | 5.23 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 2 transformer l/o DVP_P1-3: 4ALTVSTA-TX#3_SRT-A | 944591 | AF1-124 C | Adder | 2.69 MW | 2.29 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 2 transformer l/o DVP_P1-3: 4ALTVSTA-TX#3_SRT-A | 944592 | AF1-124 E | Adder | 6.15 MW | 5.23 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 2 transformer l/o DVP_P1-3: 4ALTVSTA-TX#3_SRT-A | 944601 | AF1-125 C | Adder | 2.69 MW | 2.29 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 2 transformer l/o DVP_P1-3: 4ALTVSTA-TX#3_SRT-A | 944602 | AF1-125 E | Adder | 6.15 MW | 5.23 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 2 transformer l/o DVP_P1-3: 4ALTVSTA-TX#3_SRT-A | 961123 | AF2-403 BT | 80/20 | 5.44 MW | 5.44 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 2 transformer l/o DVP_P1-3: 4ALTVSTA-TX#3_SRT-A | 961133 | AF2-404 BT | 80/20 | 5.44 MW | 5.44 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 2 transformer l/o DVP_P1-3: 4ALTVSTA-TX#3_SRT-A | 966763 | AG1-547 BT | 80/20 | 3.42 MW | 3.42 MW |
| Details for 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 314295 | 6BIRDNECK | 80/20 | 0.07 MW | 0.07 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 315083 | 1SPRUNCA | 80/20 | 3.43 MW | 3.43 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 315084 | 1SPRUNCB | 80/20 | 3.43 MW | 3.43 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 315605 | 6W1-029WIND | 80/20 | 1.13 MW | 1.13 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 315611 | 6Z1-036WIND | 80/20 | 3.18 MW | 3.18 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 901082 | W1-029 E | 80/20 | 7.58 MW | 7.58 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 916042 | Z1-036 E | 80/20 | 13.41 MW | 13.41 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 916192 | Z1-068 E | 80/20 | 0.46 MW | 0.46 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 941032 | AE2-094 E | 80/20 | 17.95 MW | 17.95 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 961942 | AG1-037 E | 80/20 | 0.15 MW | 0.15 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 962332 | AG1-082 E | 80/20 | 0.61 MW | 0.61 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 962342 | AG1-083 E | 80/20 | 0.61 MW | 0.61 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 962531 | AG1-102 C | 80/20 | 0.77 MW | 0.77 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 962532 | AG1-102 E | 80/20 | 1.61 MW | 1.61 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 963611 | AG1-210 C | 80/20 | 0.46 MW | 0.46 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 963612 | AG1-210 E | 80/20 | 0.69 MW | 0.69 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 964801 | AG1-343 C | 80/20 | 0.47 MW | 0.47 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 964802 | AG1-343 E | 80/20 | 0.7 MW | 0.7 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 966661 | AG1-536 C | 80/20 | 3.8 MW | 3.8 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 966662 | AG1-536 E | 80/20 | 5.1 MW | 5.1 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 966872 | AG1-558 E | 80/20 | 2.41 MW | 2.41 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 966882 | AG1-559 E | 80/20 | 1.11 MW | 1.11 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 963351 | AG1-184 C | 80/20 | 16.24 MW | 16.24 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 963352 | AG1-184 E | 80/20 | 11.59 MW | 11.59 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 961611 | AG1-000B C | 80/20 | 3.78 MW | 3.78 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 316427 | AG1-213 C | 80/20 | 0.37 MW | 0.37 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 940541 | AE2-040 C | 80/20 | 1.62 MW | 1.62 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 940551 | AE2-041 C | 80/20 | 5.29 MW | 5.29 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 940651 | AE2-052 C | 80/20 | 2.53 MW | 2.53 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 941281 | AE2-122 C | 80/20 | 13.9 MW | 13.9 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 941282 | AE2-122 E | 80/20 | 56.07 MW | 56.07 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 941291 | AE2-123 C | 80/20 | 14.28 MW | 14.28 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 941292 | AE2-123 E | 80/20 | 55.69 MW | 55.69 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 941301 | AE2-124 C | 80/20 | 12.97 MW | 12.97 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 941302 | AE2-124 E | 80/20 | 56.93 MW | 56.93 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 941591 | AE2-156 C | 80/20 | 11.02 MW | 11.02 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 942551 | AE2-270 C | 80/20 | 7.94 MW | 7.94 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 942552 | AE2-270 E | 80/20 | 11.91 MW | 11.91 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 943471 | AF1-018 C | 80/20 | 5.29 MW | 5.29 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 944581 | AF1-123 C | 80/20 | 23.2 MW | 23.2 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 944582 | AF1-123 E | 80/20 | 53.12 MW | 53.12 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 944591 | AF1-124 C | 80/20 | 23.2 MW | 23.2 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 944592 | AF1-124 E | 80/20 | 53.12 MW | 53.12 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 944601 | AF1-125 C | 80/20 | 23.2 MW | 23.2 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 944602 | AF1-125 E | 80/20 | 53.12 MW | 53.12 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 944631 | AF1-128 C | 80/20 | 33.09 MW | 33.09 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 944641 | AF1-129 C | 80/20 | 84.52 MW | 84.52 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 945362 | AF1-201 E | 80/20 | 2.48 MW | 2.48 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 946011 | AF1-266 C | 80/20 | 7.59 MW | 7.59 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 961612 | AG1-000B E | 80/20 | 5.67 MW | 5.67 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 961711 | AG1-011 C | 80/20 | 21.19 MW | 21.19 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 964951 | AG1-359 C | 80/20 | 13.85 MW | 13.85 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 965001 | AG1-364 C | 80/20 | 4.41 MW | 4.41 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 965002 | AG1-364 E | 80/20 | 6.61 MW | 6.61 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 965741 | AG1-442 C | 80/20 | 3.23 MW | 3.23 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 965751 | AG1-443 C | 80/20 | 3.23 MW | 3.23 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 966871 | AG1-558 C | 80/20 | 0.26 MW | 0.26 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 966881 | AG1-559 C | 80/20 | 0.12 MW | 0.12 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 316303 | AF2-085 | 80/20 | 2.34 MW | 2.34 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 963622 | AG1-213 E | 80/20 | 0.37 MW | 0.37 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-L | 963623 | AG1-213 BAT | 80/20 | 0.55 MW | 0.55 MW |
| Details for 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 1 transformer l/o DVP_P1-3: 4ALTVSTA-TX#4_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 1 transformer l/o DVP_P1-3: 4ALTVSTA-TX#4_SRT-A | 964791 | AG1-342 C | 80/20 | 0.29 MW | 0.29 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 1 transformer l/o DVP_P1-3: 4ALTVSTA-TX#4_SRT-A | 964792 | AG1-342 E | 80/20 | 0.44 MW | 0.44 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 1 transformer l/o DVP_P1-3: 4ALTVSTA-TX#4_SRT-A | 966691 | AG1-539 C | 80/20 | 12.48 MW | 12.48 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 1 transformer l/o DVP_P1-3: 4ALTVSTA-TX#4_SRT-A | 966692 | AG1-539 E | 80/20 | 16.77 MW | 16.77 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 1 transformer l/o DVP_P1-3: 4ALTVSTA-TX#4_SRT-A | 941281 | AE2-122 C | Adder | 1.5 MW | 1.27 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 1 transformer l/o DVP_P1-3: 4ALTVSTA-TX#4_SRT-A | 941282 | AE2-122 E | Adder | 6.05 MW | 5.14 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 1 transformer l/o DVP_P1-3: 4ALTVSTA-TX#4_SRT-A | 941291 | AE2-123 C | Adder | 1.54 MW | 1.31 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 1 transformer l/o DVP_P1-3: 4ALTVSTA-TX#4_SRT-A | 941292 | AE2-123 E | Adder | 6.01 MW | 5.11 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 1 transformer l/o DVP_P1-3: 4ALTVSTA-TX#4_SRT-A | 941301 | AE2-124 C | Adder | 1.4 MW | 1.19 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 1 transformer l/o DVP_P1-3: 4ALTVSTA-TX#4_SRT-A | 941302 | AE2-124 E | Adder | 6.15 MW | 5.23 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 1 transformer l/o DVP_P1-3: 4ALTVSTA-TX#4_SRT-A | 944581 | AF1-123 C | Adder | 2.53 MW | 2.15 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 1 transformer l/o DVP_P1-3: 4ALTVSTA-TX#4_SRT-A | 944582 | AF1-123 E | Adder | 5.79 MW | 4.92 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 1 transformer l/o DVP_P1-3: 4ALTVSTA-TX#4_SRT-A | 944591 | AF1-124 C | Adder | 2.53 MW | 2.15 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 1 transformer l/o DVP_P1-3: 4ALTVSTA-TX#4_SRT-A | 944592 | AF1-124 E | Adder | 5.79 MW | 4.92 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 1 transformer l/o DVP_P1-3: 4ALTVSTA-TX#4_SRT-A | 944601 | AF1-125 C | Adder | 2.53 MW | 2.15 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 1 transformer l/o DVP_P1-3: 4ALTVSTA-TX#4_SRT-A | 944602 | AF1-125 E | Adder | 5.79 MW | 4.92 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 1 transformer l/o DVP_P1-3: 4ALTVSTA-TX#4_SRT-A | 961123 | AF2-403 BT | 80/20 | 5.12 MW | 5.12 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 1 transformer l/o DVP_P1-3: 4ALTVSTA-TX#4_SRT-A | 961133 | AF2-404 BT | 80/20 | 5.12 MW | 5.12 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 1 transformer l/o DVP_P1-3: 4ALTVSTA-TX#4_SRT-A | 966763 | AG1-547 BT | 80/20 | 3.22 MW | 3.22 MW |
| Details for 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 315605 | 6W1-029WIND | 80/20 | 1.18 MW | 1.18 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 315611 | 6Z1-036WIND | 80/20 | 3.41 MW | 3.41 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 901082 | W1-029 E | 80/20 | 7.94 MW | 7.94 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 916042 | Z1-036 E | 80/20 | 14.39 MW | 14.39 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944581 | AF1-123 C | 80/20 | 61.73 MW | 61.73 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944582 | AF1-123 E | 80/20 | 141.34 MW | 141.34 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944591 | AF1-124 C | 80/20 | 61.73 MW | 61.73 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944592 | AF1-124 E | 80/20 | 141.34 MW | 141.34 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944601 | AF1-125 C | 80/20 | 61.73 MW | 61.73 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944602 | AF1-125 E | 80/20 | 141.34 MW | 141.34 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 964951 | AG1-359 C | 80/20 | 36.78 MW | 36.78 MW |
| Details for 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 315605 | 6W1-029WIND | 80/20 | 1.18 MW | 1.18 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 315611 | 6Z1-036WIND | 80/20 | 3.41 MW | 3.41 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 901082 | W1-029 E | 80/20 | 7.94 MW | 7.94 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 916042 | Z1-036 E | 80/20 | 14.39 MW | 14.39 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944581 | AF1-123 C | 80/20 | 61.73 MW | 61.73 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944582 | AF1-123 E | 80/20 | 141.34 MW | 141.34 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944591 | AF1-124 C | 80/20 | 61.73 MW | 61.73 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944592 | AF1-124 E | 80/20 | 141.34 MW | 141.34 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944601 | AF1-125 C | 80/20 | 61.73 MW | 61.73 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944602 | AF1-125 E | 80/20 | 141.34 MW | 141.34 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 964951 | AG1-359 C | 80/20 | 36.78 MW | 36.78 MW |
| Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 314295 | 6BIRDNECK | 80/20 | 0.17 MW | 0.17 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 315131 | 1EDGECMA | 80/20 | 7.41 MW | 7.41 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 315605 | 6W1-029WIND | 80/20 | 2.82 MW | 2.82 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 315611 | 6Z1-036WIND | 80/20 | 7.89 MW | 7.89 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 901082 | W1-029 E | 80/20 | 18.93 MW | 18.93 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 916042 | Z1-036 E | 80/20 | 33.27 MW | 33.27 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 916192 | Z1-068 E | 80/20 | 1.18 MW | 1.18 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 941032 | AE2-094 E | 80/20 | 47.06 MW | 47.06 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 944012 | AF1-069 E | 80/20 | 15.38 MW | 15.38 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 961942 | AG1-037 E | 80/20 | 0.34 MW | 0.34 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 962332 | AG1-082 E | 80/20 | 1.39 MW | 1.39 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 962342 | AG1-083 E | 80/20 | 1.39 MW | 1.39 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 962531 | AG1-102 C | 80/20 | 0.9 MW | 0.9 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 962532 | AG1-102 E | 80/20 | 1.86 MW | 1.86 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 963041 | AG1-153 C | 80/20 | 6.49 MW | 6.49 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 963042 | AG1-153 E | 80/20 | 9.73 MW | 9.73 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 963102 | AG1-159 E | 80/20 | 3.57 MW | 3.57 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 963111 | AG1-160 C | 80/20 | 6.59 MW | 6.59 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 963112 | AG1-160 E | 80/20 | 9.88 MW | 9.88 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 964801 | AG1-343 C | 80/20 | 1.05 MW | 1.05 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 964802 | AG1-343 E | 80/20 | 1.57 MW | 1.57 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 963311 | AG1-180 C | 80/20 | 2.63 MW | 2.63 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 963312 | AG1-180 E | 80/20 | 2.2 MW | 2.2 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 963351 | AG1-184 C | 80/20 | 43.17 MW | 43.17 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 963352 | AG1-184 E | 80/20 | 30.81 MW | 30.81 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 961611 | AG1-000B C | 80/20 | 5.41 MW | 5.41 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 940541 | AE2-040 C | 80/20 | 2.76 MW | 2.76 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 940651 | AE2-052 C | 80/20 | 2.81 MW | 2.81 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 940661 | AE2-053 C | 80/20 | 2.99 MW | 2.99 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 941281 | AE2-122 C | 80/20 | 35.62 MW | 35.62 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 941282 | AE2-122 E | 80/20 | 143.76 MW | 143.76 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 941291 | AE2-123 C | 80/20 | 36.61 MW | 36.61 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 941292 | AE2-123 E | 80/20 | 142.77 MW | 142.77 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 941301 | AE2-124 C | 80/20 | 33.33 MW | 33.33 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 941302 | AE2-124 E | 80/20 | 146.23 MW | 146.23 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 941591 | AE2-156 C | 80/20 | 27.84 MW | 27.84 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 942551 | AE2-270 C | 80/20 | 8.44 MW | 8.44 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 942552 | AE2-270 E | 80/20 | 12.66 MW | 12.66 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 944141 | AF1-082 C | 80/20 | 2.96 MW | 2.96 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 944581 | AF1-123 C | 80/20 | 62.54 MW | 62.54 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 944582 | AF1-123 E | 80/20 | 143.2 MW | 143.2 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 944591 | AF1-124 C | 80/20 | 62.54 MW | 62.54 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 944592 | AF1-124 E | 80/20 | 143.2 MW | 143.2 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 944601 | AF1-125 C | 80/20 | 62.54 MW | 62.54 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 944602 | AF1-125 E | 80/20 | 143.2 MW | 143.2 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 945362 | AF1-201 E | 80/20 | 3.43 MW | 3.43 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 946011 | AF1-266 C | 80/20 | 13.13 MW | 13.13 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 961602 | AG1-000A E | 80/20 | 5.76 MW | 5.76 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 961612 | AG1-000B E | 80/20 | 8.12 MW | 8.12 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 964951 | AG1-359 C | 80/20 | 36.07 MW | 36.07 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 965001 | AG1-364 C | 80/20 | 11.13 MW | 11.13 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 965002 | AG1-364 E | 80/20 | 16.69 MW | 16.69 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 965741 | AG1-442 C | 80/20 | 7.65 MW | 7.65 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 965751 | AG1-443 C | 80/20 | 7.65 MW | 7.65 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 965761 | AG1-444 C | 80/20 | 13.98 MW | 13.98 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 965771 | AG1-445 C | 80/20 | 4.08 MW | 4.08 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 965781 | AG1-446 C | 80/20 | 4.08 MW | 4.08 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 965811 | AG1-449 C | 80/20 | 27.29 MW | 27.29 MW |
| Details for 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 314295 | 6BIRDNECK | 80/20 | 0.05 MW | 0.05 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315605 | 6W1-029WIND | 80/20 | 0.92 MW | 0.92 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 315611 | 6Z1-036WIND | 80/20 | 2.53 MW | 2.53 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 901082 | W1-029 E | 80/20 | 6.16 MW | 6.16 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 916042 | Z1-036 E | 80/20 | 10.68 MW | 10.68 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 916192 | Z1-068 E | 80/20 | 0.38 MW | 0.38 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941032 | AE2-094 E | 80/20 | 10.92 MW | 10.92 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944012 | AF1-069 E | 80/20 | 3.57 MW | 3.57 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 961942 | AG1-037 E | 80/20 | 0.1 MW | 0.1 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 962332 | AG1-082 E | 80/20 | 0.41 MW | 0.41 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 962342 | AG1-083 E | 80/20 | 0.41 MW | 0.41 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 963041 | AG1-153 C | 80/20 | 1.51 MW | 1.51 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 963042 | AG1-153 E | 80/20 | 2.27 MW | 2.27 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 963111 | AG1-160 C | 80/20 | 1.53 MW | 1.53 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 963112 | AG1-160 E | 80/20 | 2.3 MW | 2.3 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 964801 | AG1-343 C | 80/20 | 0.31 MW | 0.31 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 964802 | AG1-343 E | 80/20 | 0.47 MW | 0.47 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 963351 | AG1-184 C | 80/20 | 10.64 MW | 10.64 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 963352 | AG1-184 E | 80/20 | 7.59 MW | 7.59 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 961611 | AG1-000B C | 80/20 | 2.11 MW | 2.11 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 940551 | AE2-041 C | Adder | -7.05 MW | -5.99 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941281 | AE2-122 C | 80/20 | 11.53 MW | 11.53 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941282 | AE2-122 E | 80/20 | 46.53 MW | 46.53 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941291 | AE2-123 C | 80/20 | 11.85 MW | 11.85 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941292 | AE2-123 E | 80/20 | 46.21 MW | 46.21 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941301 | AE2-124 C | 80/20 | 10.78 MW | 10.78 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941302 | AE2-124 E | 80/20 | 47.3 MW | 47.3 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 941591 | AE2-156 C | 80/20 | 9.05 MW | 9.05 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 943471 | AF1-018 C | Adder | -7.05 MW | -5.99 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944581 | AF1-123 C | 80/20 | 19.8 MW | 19.8 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944582 | AF1-123 E | 80/20 | 45.33 MW | 45.33 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944591 | AF1-124 C | 80/20 | 19.8 MW | 19.8 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944592 | AF1-124 E | 80/20 | 45.33 MW | 45.33 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944601 | AF1-125 C | 80/20 | 19.8 MW | 19.8 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 944602 | AF1-125 E | 80/20 | 45.33 MW | 45.33 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 945362 | AF1-201 E | 80/20 | 1.65 MW | 1.65 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 961612 | AG1-000B E | 80/20 | 3.17 MW | 3.17 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 964951 | AG1-359 C | 80/20 | 11.59 MW | 11.59 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965001 | AG1-364 C | 80/20 | 3.62 MW | 3.62 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965002 | AG1-364 E | 80/20 | 5.43 MW | 5.43 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965741 | AG1-442 C | 80/20 | 2.34 MW | 2.34 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965751 | AG1-443 C | 80/20 | 2.34 MW | 2.34 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 965811 | AG1-449 C | 80/20 | 6.34 MW | 6.34 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 940553 | AE2-041 BT | 80/20 | 7.05 MW | 7.05 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 943473 | AF1-018 BT | 80/20 | 7.05 MW | 7.05 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 957193 | AF2-013 BT | 80/20 | 9.1 MW | 9.1 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 961783 | AG1-019 BT | 80/20 | 9.1 MW | 9.1 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 963613 | AG1-210 BT | 80/20 | 1.7 MW | 1.7 MW |
| 6LIGH209-6LANEXA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A | 966663 | AG1-536 BT | 80/20 | 11.64 MW | 11.64 MW |
| Details for 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228_SRT-L | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228_SRT-L | 961611 | AG1-000B C | 50/50 | 4.54 MW | 4.54 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228_SRT-L | 941281 | AE2-122 C | Adder | 4.67 MW | 3.97 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228_SRT-L | 941282 | AE2-122 E | Adder | 18.85 MW | 16.02 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228_SRT-L | 941291 | AE2-123 C | Adder | 4.8 MW | 4.08 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228_SRT-L | 941292 | AE2-123 E | Adder | 18.72 MW | 15.91 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228_SRT-L | 941301 | AE2-124 C | Adder | 4.3 MW | 3.66 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228_SRT-L | 941302 | AE2-124 E | Adder | 18.89 MW | 16.06 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228_SRT-L | 942551 | AE2-270 C | 50/50 | 12.53 MW | 12.53 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228_SRT-L | 942552 | AE2-270 E | 50/50 | 18.8 MW | 18.8 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228_SRT-L | 944581 | AF1-123 C | Adder | 6.25 MW | 5.31 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228_SRT-L | 944582 | AF1-123 E | Adder | 14.31 MW | 12.17 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228_SRT-L | 944591 | AF1-124 C | Adder | 6.25 MW | 5.31 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228_SRT-L | 944592 | AF1-124 E | Adder | 14.31 MW | 12.17 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228_SRT-L | 944601 | AF1-125 C | Adder | 6.25 MW | 5.31 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228_SRT-L | 944602 | AF1-125 E | Adder | 14.31 MW | 12.17 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228_SRT-L | 961612 | AG1-000B E | 50/50 | 6.8 MW | 6.8 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228_SRT-L | 961711 | AG1-011 C | 50/50 | 33.48 MW | 33.48 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228_SRT-L | 940653 | AE2-052 BT | 50/50 | 3.26 MW | 3.26 MW |
| Details for 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 315083 | 1SPRUNCA | 50/50 | 5.22 MW | 5.22 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 315084 | 1SPRUNCB | 50/50 | 5.22 MW | 5.22 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 315611 | 6Z1-036WIND | Adder | 4.84 MW | 4.11 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 916042 | Z1-036 E | Adder | 20.41 MW | 17.35 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 941032 | AE2-094 E | Adder | 27.32 MW | 23.23 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 944012 | AF1-069 E | Adder | 8.93 MW | 7.59 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 961942 | AG1-037 E | Adder | 0.23 MW | 0.19 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 962332 | AG1-082 E | Adder | 0.92 MW | 0.79 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 962342 | AG1-083 E | Adder | 0.92 MW | 0.79 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 962531 | AG1-102 C | Adder | 1.18 MW | 1.0 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 962532 | AG1-102 E | Adder | 2.45 MW | 2.08 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 963611 | AG1-210 C | Adder | 0.7 MW | 0.59 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 963612 | AG1-210 E | Adder | 1.05 MW | 0.89 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 964801 | AG1-343 C | Adder | 0.71 MW | 0.6 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 964802 | AG1-343 E | Adder | 1.06 MW | 0.9 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 966661 | AG1-536 C | Adder | 5.78 MW | 4.91 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 966662 | AG1-536 E | Adder | 7.77 MW | 6.6 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 966872 | AG1-558 E | 50/50 | 3.67 MW | 3.67 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 966882 | AG1-559 E | Adder | 1.69 MW | 1.43 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 963351 | AG1-184 C | Adder | 24.72 MW | 21.02 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 963352 | AG1-184 E | Adder | 17.64 MW | 15.0 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 961611 | AG1-000B C | Adder | 5.75 MW | 4.89 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 316427 | AG1-213 C | Adder | 0.56 MW | 0.48 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 940541 | AE2-040 C | Adder | 2.47 MW | 2.1 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 940551 | AE2-041 C | 50/50 | 8.05 MW | 8.05 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 940651 | AE2-052 C | 50/50 | 3.85 MW | 3.85 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 941281 | AE2-122 C | Adder | 21.15 MW | 17.98 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 941282 | AE2-122 E | Adder | 85.35 MW | 72.55 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 941291 | AE2-123 C | Adder | 21.74 MW | 18.48 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 941292 | AE2-123 E | Adder | 84.77 MW | 72.05 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 941301 | AE2-124 C | Adder | 19.75 MW | 16.79 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 941302 | AE2-124 E | Adder | 86.66 MW | 73.66 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 941591 | AE2-156 C | Adder | 16.77 MW | 14.26 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 942551 | AE2-270 C | 50/50 | 12.09 MW | 12.09 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 942552 | AE2-270 E | 50/50 | 18.14 MW | 18.14 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 943471 | AF1-018 C | 50/50 | 8.05 MW | 8.05 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 944581 | AF1-123 C | Adder | 35.31 MW | 30.01 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 944582 | AF1-123 E | Adder | 80.85 MW | 68.72 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 944591 | AF1-124 C | Adder | 35.31 MW | 30.01 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 944592 | AF1-124 E | Adder | 80.85 MW | 68.72 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 944601 | AF1-125 C | Adder | 35.31 MW | 30.01 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 944602 | AF1-125 E | Adder | 80.85 MW | 68.72 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 944631 | AF1-128 C | 50/50 | 50.37 MW | 50.37 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 944641 | AF1-129 C | 50/50 | 128.66 MW | 128.66 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 945362 | AF1-201 E | Adder | 3.78 MW | 3.21 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 946011 | AF1-266 C | Adder | 11.56 MW | 9.83 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 961612 | AG1-000B E | 50/50 | 8.63 MW | 8.63 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 961711 | AG1-011 C | 50/50 | 32.25 MW | 32.25 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 964951 | AG1-359 C | Adder | 21.09 MW | 17.93 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 965001 | AG1-364 C | Adder | 6.71 MW | 5.7 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 965002 | AG1-364 E | Adder | 10.06 MW | 8.55 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 965741 | AG1-442 C | Adder | 4.92 MW | 4.18 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 965751 | AG1-443 C | Adder | 4.92 MW | 4.18 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 965811 | AG1-449 C | Adder | 8.93 MW | 7.59 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 966871 | AG1-558 C | 50/50 | 0.4 MW | 0.4 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 966881 | AG1-559 C | Adder | 0.18 MW | 0.15 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 316303 | AF2-085 | Adder | 4.2 MW | 3.57 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 963622 | AG1-213 E | Adder | 0.66 MW | 0.56 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557_SRT-L | 963623 | AG1-213 BAT | Adder | 0.99 MW | 0.84 MW |
| Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 315083 | 1SPRUNCA | Adder | 1.64 MW | 1.39 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 315084 | 1SPRUNCB | Adder | 1.64 MW | 1.39 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 315611 | 6Z1-036WIND | Adder | 1.73 MW | 1.47 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 916042 | Z1-036 E | Adder | 7.28 MW | 6.19 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 941032 | AE2-094 E | Adder | 12.34 MW | 10.49 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 944012 | AF1-069 E | Adder | 4.03 MW | 3.43 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 961942 | AG1-037 E | Adder | 0.09 MW | 0.08 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 962332 | AG1-082 E | Adder | 0.39 MW | 0.33 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 962342 | AG1-083 E | Adder | 0.39 MW | 0.33 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 962531 | AG1-102 C | Adder | 0.33 MW | 0.28 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 962532 | AG1-102 E | Adder | 0.68 MW | 0.58 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 963041 | AG1-153 C | Adder | 1.79 MW | 1.52 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 963042 | AG1-153 E | Adder | 2.69 MW | 2.29 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 963102 | AG1-159 E | Adder | 1.14 MW | 0.97 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 963111 | AG1-160 C | Adder | 1.79 MW | 1.52 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 963112 | AG1-160 E | Adder | 2.69 MW | 2.28 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 964111 | AG1-272 C | 50/50 | 0.59 MW | 0.59 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 964112 | AG1-272 E | 50/50 | 0.89 MW | 0.89 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 964121 | AG1-273 C | 50/50 | 0.59 MW | 0.59 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 964122 | AG1-273 E | 50/50 | 0.89 MW | 0.89 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 964131 | AG1-274 C | 50/50 | 0.59 MW | 0.59 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 964132 | AG1-274 E | 50/50 | 0.89 MW | 0.89 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 964791 | AG1-342 C | Adder | 0.34 MW | 0.29 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 964792 | AG1-342 E | Adder | 0.5 MW | 0.43 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 964801 | AG1-343 C | Adder | 0.3 MW | 0.26 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 964802 | AG1-343 E | Adder | 0.46 MW | 0.39 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 965191 | AG1-384 C | 50/50 | 0.59 MW | 0.59 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 965192 | AG1-384 E | 50/50 | 0.89 MW | 0.89 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 966872 | AG1-558 E | Adder | 0.64 MW | 0.55 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 963311 | AG1-180 C | Adder | 1.51 MW | 1.28 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 963312 | AG1-180 E | Adder | 1.26 MW | 1.07 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 963351 | AG1-184 C | Adder | 10.3 MW | 8.76 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 963352 | AG1-184 E | Adder | 7.35 MW | 6.25 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 963361 | AG1-185 C | 50/50 | 8.12 MW | 8.12 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 963362 | AG1-185 E | 50/50 | 6.83 MW | 6.83 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 961611 | AG1-000B C | Adder | 1.71 MW | 1.46 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 940541 | AE2-040 C | Adder | 0.95 MW | 0.81 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 940551 | AE2-041 C | Adder | 2.07 MW | 1.76 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 940651 | AE2-052 C | Adder | 1.19 MW | 1.01 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 940661 | AE2-053 C | 50/50 | 2.09 MW | 2.09 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 941281 | AE2-122 C | Adder | 7.14 MW | 6.07 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 941282 | AE2-122 E | Adder | 28.8 MW | 24.48 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 941291 | AE2-123 C | Adder | 7.34 MW | 6.24 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 941292 | AE2-123 E | Adder | 28.6 MW | 24.31 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 941301 | AE2-124 C | Adder | 6.67 MW | 5.67 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 941302 | AE2-124 E | Adder | 29.26 MW | 24.88 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 941591 | AE2-156 C | Adder | 5.62 MW | 4.78 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 942551 | AE2-270 C | Adder | 3.47 MW | 2.95 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 942552 | AE2-270 E | Adder | 5.21 MW | 4.43 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 943471 | AF1-018 C | Adder | 2.07 MW | 1.76 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 943571 | AF1-028 C | Adder | -16.01 MW | -13.61 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 944581 | AF1-123 C | Adder | 12.01 MW | 10.21 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 944582 | AF1-123 E | Adder | 27.49 MW | 23.37 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 944591 | AF1-124 C | Adder | 12.01 MW | 10.21 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 944592 | AF1-124 E | Adder | 27.49 MW | 23.37 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 944601 | AF1-125 C | Adder | 12.01 MW | 10.21 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 944602 | AF1-125 E | Adder | 27.49 MW | 23.37 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 944631 | AF1-128 C | Adder | 12.83 MW | 10.9 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 944641 | AF1-129 C | Adder | 34.65 MW | 29.45 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 945362 | AF1-201 E | Adder | 1.07 MW | 0.91 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 946011 | AF1-266 C | Adder | 4.53 MW | 3.85 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 961612 | AG1-000B E | Adder | 2.57 MW | 2.19 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 961711 | AG1-011 C | Adder | 9.26 MW | 7.87 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 964951 | AG1-359 C | Adder | 7.15 MW | 6.08 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 965001 | AG1-364 C | Adder | 2.25 MW | 1.91 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 965002 | AG1-364 E | Adder | 3.37 MW | 2.87 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 965741 | AG1-442 C | Adder | 1.91 MW | 1.62 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 965751 | AG1-443 C | Adder | 1.91 MW | 1.62 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 965771 | AG1-445 C | Adder | 2.44 MW | 2.08 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 965781 | AG1-446 C | Adder | 2.44 MW | 2.08 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 965811 | AG1-449 C | Adder | 7.57 MW | 6.43 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 965831 | AG1-451 C | 50/50 | 5.29 MW | 5.29 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 966871 | AG1-558 C | Adder | 0.07 MW | 0.06 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 316303 | AF2-085 | 50/50 | 2.05 MW | 2.05 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 958502 | AF2-144 E | Adder | 3.08 MW | 2.62 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 961063 | AF2-397 BT | 50/50 | 24.23 MW | 24.23 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 963473 | AG1-196 BT | 50/50 | 16.01 MW | 16.01 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 965543 | AG1-422 BT | 50/50 | 5.39 MW | 5.39 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 966673 | AG1-537 BT | 50/50 | 9.68 MW | 9.68 MW |
| Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 315083 | 1SPRUNCA | Adder | 1.64 MW | 1.39 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 315084 | 1SPRUNCB | Adder | 1.64 MW | 1.39 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 315611 | 6Z1-036WIND | Adder | 1.73 MW | 1.47 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 916042 | Z1-036 E | Adder | 7.28 MW | 6.19 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 941032 | AE2-094 E | Adder | 12.34 MW | 10.49 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 944012 | AF1-069 E | Adder | 4.03 MW | 3.43 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 961942 | AG1-037 E | Adder | 0.09 MW | 0.08 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 962332 | AG1-082 E | Adder | 0.39 MW | 0.33 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 962342 | AG1-083 E | Adder | 0.39 MW | 0.33 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 962531 | AG1-102 C | Adder | 0.33 MW | 0.28 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 962532 | AG1-102 E | Adder | 0.68 MW | 0.58 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 963041 | AG1-153 C | Adder | 1.79 MW | 1.52 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 963042 | AG1-153 E | Adder | 2.69 MW | 2.29 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 963102 | AG1-159 E | Adder | 1.14 MW | 0.97 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 963111 | AG1-160 C | Adder | 1.79 MW | 1.52 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 963112 | AG1-160 E | Adder | 2.69 MW | 2.28 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 964111 | AG1-272 C | 50/50 | 0.59 MW | 0.59 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 964112 | AG1-272 E | 50/50 | 0.89 MW | 0.89 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 964121 | AG1-273 C | 50/50 | 0.59 MW | 0.59 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 964122 | AG1-273 E | 50/50 | 0.89 MW | 0.89 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 964131 | AG1-274 C | 50/50 | 0.59 MW | 0.59 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 964132 | AG1-274 E | 50/50 | 0.89 MW | 0.89 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 964791 | AG1-342 C | Adder | 0.34 MW | 0.29 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 964792 | AG1-342 E | Adder | 0.5 MW | 0.43 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 964801 | AG1-343 C | Adder | 0.3 MW | 0.26 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 964802 | AG1-343 E | Adder | 0.46 MW | 0.39 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 965191 | AG1-384 C | 50/50 | 0.59 MW | 0.59 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 965192 | AG1-384 E | 50/50 | 0.89 MW | 0.89 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 966872 | AG1-558 E | Adder | 0.64 MW | 0.55 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 963311 | AG1-180 C | Adder | 1.51 MW | 1.28 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 963312 | AG1-180 E | Adder | 1.26 MW | 1.07 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 963351 | AG1-184 C | Adder | 10.3 MW | 8.76 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 963352 | AG1-184 E | Adder | 7.35 MW | 6.25 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 963361 | AG1-185 C | 50/50 | 8.12 MW | 8.12 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 963362 | AG1-185 E | 50/50 | 6.83 MW | 6.83 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 961611 | AG1-000B C | Adder | 1.71 MW | 1.46 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 940541 | AE2-040 C | Adder | 0.95 MW | 0.81 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 940551 | AE2-041 C | Adder | 2.07 MW | 1.76 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 940651 | AE2-052 C | Adder | 1.19 MW | 1.01 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 940661 | AE2-053 C | 50/50 | 2.09 MW | 2.09 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 941281 | AE2-122 C | Adder | 7.14 MW | 6.07 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 941282 | AE2-122 E | Adder | 28.8 MW | 24.48 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 941291 | AE2-123 C | Adder | 7.34 MW | 6.24 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 941292 | AE2-123 E | Adder | 28.6 MW | 24.31 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 941301 | AE2-124 C | Adder | 6.67 MW | 5.67 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 941302 | AE2-124 E | Adder | 29.26 MW | 24.88 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 941591 | AE2-156 C | Adder | 5.62 MW | 4.78 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 942551 | AE2-270 C | Adder | 3.47 MW | 2.95 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 942552 | AE2-270 E | Adder | 5.21 MW | 4.43 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 943471 | AF1-018 C | Adder | 2.07 MW | 1.76 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 943571 | AF1-028 C | Adder | -16.01 MW | -13.61 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 944581 | AF1-123 C | Adder | 12.01 MW | 10.21 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 944582 | AF1-123 E | Adder | 27.49 MW | 23.37 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 944591 | AF1-124 C | Adder | 12.01 MW | 10.21 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 944592 | AF1-124 E | Adder | 27.49 MW | 23.37 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 944601 | AF1-125 C | Adder | 12.01 MW | 10.21 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 944602 | AF1-125 E | Adder | 27.49 MW | 23.37 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 944631 | AF1-128 C | Adder | 12.83 MW | 10.9 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 944641 | AF1-129 C | Adder | 34.65 MW | 29.45 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 945362 | AF1-201 E | Adder | 1.07 MW | 0.91 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 946011 | AF1-266 C | Adder | 4.53 MW | 3.85 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 961612 | AG1-000B E | Adder | 2.57 MW | 2.19 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 961711 | AG1-011 C | Adder | 9.26 MW | 7.87 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 964951 | AG1-359 C | Adder | 7.15 MW | 6.08 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 965001 | AG1-364 C | Adder | 2.25 MW | 1.91 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 965002 | AG1-364 E | Adder | 3.37 MW | 2.87 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 965741 | AG1-442 C | Adder | 1.91 MW | 1.62 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 965751 | AG1-443 C | Adder | 1.91 MW | 1.62 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 965771 | AG1-445 C | Adder | 2.44 MW | 2.08 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 965781 | AG1-446 C | Adder | 2.44 MW | 2.08 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 965811 | AG1-449 C | Adder | 7.57 MW | 6.43 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 965831 | AG1-451 C | 50/50 | 5.29 MW | 5.29 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 966871 | AG1-558 C | Adder | 0.07 MW | 0.06 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 316303 | AF2-085 | 50/50 | 2.05 MW | 2.05 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 958502 | AF2-144 E | Adder | 3.08 MW | 2.62 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 961063 | AF2-397 BT | 50/50 | 24.23 MW | 24.23 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 963473 | AG1-196 BT | 50/50 | 16.01 MW | 16.01 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 965543 | AG1-422 BT | 50/50 | 5.39 MW | 5.39 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T549_SRT-L | 966673 | AG1-537 BT | 50/50 | 9.68 MW | 9.68 MW |
| Details for 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 315083 | 1SPRUNCA | Adder | 1.45 MW | 1.23 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 315084 | 1SPRUNCB | Adder | 1.45 MW | 1.23 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 941032 | AE2-094 E | Adder | 11.14 MW | 9.46 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 944012 | AF1-069 E | Adder | 3.64 MW | 3.09 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 961942 | AG1-037 E | Adder | 0.09 MW | 0.07 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 962332 | AG1-082 E | Adder | 0.35 MW | 0.3 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 962342 | AG1-083 E | Adder | 0.35 MW | 0.3 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 963041 | AG1-153 C | Adder | 1.63 MW | 1.38 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 963042 | AG1-153 E | Adder | 2.44 MW | 2.08 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 963102 | AG1-159 E | Adder | 1.06 MW | 0.9 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 963111 | AG1-160 C | Adder | 1.62 MW | 1.38 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 963112 | AG1-160 E | Adder | 2.43 MW | 2.07 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 964111 | AG1-272 C | 50/50 | 0.54 MW | 0.54 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 964112 | AG1-272 E | 50/50 | 0.81 MW | 0.81 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 964121 | AG1-273 C | 50/50 | 0.54 MW | 0.54 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 964122 | AG1-273 E | 50/50 | 0.81 MW | 0.81 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 964131 | AG1-274 C | 50/50 | 0.54 MW | 0.54 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 964132 | AG1-274 E | 50/50 | 0.81 MW | 0.81 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 964791 | AG1-342 C | Adder | 0.32 MW | 0.27 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 964792 | AG1-342 E | Adder | 0.48 MW | 0.4 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 964801 | AG1-343 C | Adder | 0.28 MW | 0.23 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 964802 | AG1-343 E | Adder | 0.42 MW | 0.35 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 965191 | AG1-384 C | 50/50 | 0.54 MW | 0.54 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 965192 | AG1-384 E | 50/50 | 0.81 MW | 0.81 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 963311 | AG1-180 C | Adder | 1.38 MW | 1.17 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 963312 | AG1-180 E | Adder | 1.15 MW | 0.98 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 963351 | AG1-184 C | Adder | 9.24 MW | 7.85 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 963352 | AG1-184 E | Adder | 6.59 MW | 5.6 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 963361 | AG1-185 C | 50/50 | 7.43 MW | 7.43 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 963362 | AG1-185 E | 50/50 | 6.24 MW | 6.24 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 965581 | AG1-426 C | 50/50 | 4.35 MW | 4.35 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 961611 | AG1-000B C | Adder | 1.52 MW | 1.29 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 940541 | AE2-040 C | Adder | 0.86 MW | 0.73 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 940651 | AE2-052 C | Adder | 1.06 MW | 0.9 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 940661 | AE2-053 C | Adder | 1.93 MW | 1.64 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 941281 | AE2-122 C | Adder | 6.37 MW | 5.42 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 941282 | AE2-122 E | Adder | 25.7 MW | 21.85 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 941291 | AE2-123 C | Adder | 6.55 MW | 5.56 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 941292 | AE2-123 E | Adder | 25.53 MW | 21.7 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 941301 | AE2-124 C | Adder | 5.95 MW | 5.06 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 941302 | AE2-124 E | Adder | 26.12 MW | 22.2 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 941591 | AE2-156 C | Adder | 5.01 MW | 4.26 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 942551 | AE2-270 C | Adder | 3.08 MW | 2.62 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 942552 | AE2-270 E | Adder | 4.62 MW | 3.93 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 943571 | AF1-028 C | Adder | -15.05 MW | -12.79 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 944581 | AF1-123 C | Adder | 9.78 MW | 8.31 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 944582 | AF1-123 E | Adder | 22.4 MW | 19.04 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 944591 | AF1-124 C | Adder | 10.71 MW | 9.11 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 944592 | AF1-124 E | Adder | 24.53 MW | 20.85 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 944601 | AF1-125 C | Adder | 10.71 MW | 9.11 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 944602 | AF1-125 E | Adder | 24.53 MW | 20.85 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 944631 | AF1-128 C | Adder | 11.31 MW | 9.62 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 944641 | AF1-129 C | Adder | 30.71 MW | 26.1 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 946011 | AF1-266 C | Adder | 4.09 MW | 3.48 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 946291 | AF1-293 C | 50/50 | 8.66 MW | 8.66 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 946292 | AF1-293 E | 50/50 | 12.98 MW | 12.98 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 961612 | AG1-000B E | Adder | 2.28 MW | 1.94 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 961711 | AG1-011 C | Adder | 8.22 MW | 6.99 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 964951 | AG1-359 C | Adder | 6.39 MW | 5.43 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 965001 | AG1-364 C | Adder | 2.0 MW | 1.7 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 965002 | AG1-364 E | Adder | 3.01 MW | 2.56 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 965771 | AG1-445 C | Adder | 2.25 MW | 1.91 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 965781 | AG1-446 C | Adder | 2.25 MW | 1.91 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 965811 | AG1-449 C | Adder | 6.84 MW | 5.81 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 965831 | AG1-451 C | 50/50 | 4.81 MW | 4.81 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 316303 | AF2-085 | Adder | 2.15 MW | 1.83 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 958502 | AF2-144 E | Adder | 2.77 MW | 2.36 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 961063 | AF2-397 BT | 50/50 | 26.84 MW | 26.84 MW |
| Details for 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 315083 | 1SPRUNCA | Adder | 1.44 MW | 1.22 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 315084 | 1SPRUNCB | Adder | 1.44 MW | 1.22 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 315131 | 1EDGECMA | Adder | 2.35 MW | 2.0 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 315611 | 6Z1-036WIND | Adder | 1.64 MW | 1.4 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 916042 | Z1-036 E | Adder | 6.93 MW | 5.89 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 941032 | AE2-094 E | Adder | 13.11 MW | 11.15 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 944012 | AF1-069 E | Adder | 4.28 MW | 3.64 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 961942 | AG1-037 E | Adder | 0.1 MW | 0.08 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 962332 | AG1-082 E | Adder | 0.39 MW | 0.33 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 962342 | AG1-083 E | Adder | 0.39 MW | 0.33 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 963041 | AG1-153 C | Adder | 1.92 MW | 1.63 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 963042 | AG1-153 E | Adder | 2.87 MW | 2.44 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 963102 | AG1-159 E | Adder | 1.19 MW | 1.01 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 963111 | AG1-160 C | Adder | 1.91 MW | 1.62 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 963112 | AG1-160 E | Adder | 2.86 MW | 2.44 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 964111 | AG1-272 C | 50/50 | 0.58 MW | 0.58 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 964112 | AG1-272 E | 50/50 | 0.87 MW | 0.87 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 964121 | AG1-273 C | 50/50 | 0.58 MW | 0.58 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 964122 | AG1-273 E | 50/50 | 0.87 MW | 0.87 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 964131 | AG1-274 C | 50/50 | 0.58 MW | 0.58 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 964132 | AG1-274 E | 50/50 | 0.87 MW | 0.87 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 964791 | AG1-342 C | Adder | 0.35 MW | 0.3 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 964792 | AG1-342 E | Adder | 0.53 MW | 0.45 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 964801 | AG1-343 C | Adder | 0.3 MW | 0.26 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 964802 | AG1-343 E | Adder | 0.45 MW | 0.38 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 965191 | AG1-384 C | 50/50 | 0.58 MW | 0.58 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 965192 | AG1-384 E | 50/50 | 0.87 MW | 0.87 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 966251 | AG1-494 C | Adder | 1.21 MW | 1.03 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 966252 | AG1-494 E | Adder | 1.81 MW | 1.54 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 966691 | AG1-539 C | Adder | 1.68 MW | 1.43 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 966692 | AG1-539 E | Adder | 2.26 MW | 1.93 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 963311 | AG1-180 C | Adder | 1.51 MW | 1.28 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 963312 | AG1-180 E | Adder | 1.26 MW | 1.07 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 963351 | AG1-184 C | Adder | 10.7 MW | 9.1 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 963352 | AG1-184 E | Adder | 7.64 MW | 6.49 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 963361 | AG1-185 C | 50/50 | 7.94 MW | 7.94 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 963362 | AG1-185 E | 50/50 | 6.67 MW | 6.67 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 965581 | AG1-426 C | 50/50 | 4.61 MW | 4.61 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 940541 | AE2-040 C | Adder | 0.95 MW | 0.8 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 940651 | AE2-052 C | Adder | 1.08 MW | 0.91 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 940661 | AE2-053 C | 50/50 | 2.12 MW | 2.12 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 941281 | AE2-122 C | Adder | 6.57 MW | 5.58 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 941282 | AE2-122 E | Adder | 26.51 MW | 22.53 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 941291 | AE2-123 C | Adder | 6.75 MW | 5.74 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 941292 | AE2-123 E | Adder | 26.33 MW | 22.38 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 941301 | AE2-124 C | Adder | 6.14 MW | 5.22 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 941302 | AE2-124 E | Adder | 26.94 MW | 22.9 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 941591 | AE2-156 C | Adder | 5.16 MW | 4.38 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 943571 | AF1-028 C | Adder | -11.41 MW | -9.7 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 944141 | AF1-082 C | Adder | 0.95 MW | 0.81 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 944581 | AF1-123 C | Adder | 11.08 MW | 9.42 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 944582 | AF1-123 E | Adder | 25.37 MW | 21.56 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 944591 | AF1-124 C | Adder | 11.08 MW | 9.42 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 944592 | AF1-124 E | Adder | 25.37 MW | 21.56 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 944601 | AF1-125 C | Adder | 11.08 MW | 9.42 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 944602 | AF1-125 E | Adder | 25.37 MW | 21.56 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 944641 | AF1-129 C | Adder | 29.67 MW | 25.22 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 946011 | AF1-266 C | Adder | 4.51 MW | 3.83 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 946291 | AF1-293 C | 50/50 | 9.2 MW | 9.2 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 946292 | AF1-293 E | 50/50 | 13.8 MW | 13.8 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 961602 | AG1-000A E | Adder | 1.83 MW | 1.55 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 964951 | AG1-359 C | Adder | 6.6 MW | 5.61 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 965001 | AG1-364 C | Adder | 2.06 MW | 1.75 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 965002 | AG1-364 E | Adder | 3.09 MW | 2.63 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 965741 | AG1-442 C | Adder | 1.9 MW | 1.61 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 965751 | AG1-443 C | Adder | 1.9 MW | 1.61 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 965761 | AG1-444 C | Adder | 4.16 MW | 3.54 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 965771 | AG1-445 C | Adder | 2.48 MW | 2.11 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 965781 | AG1-446 C | Adder | 2.48 MW | 2.11 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 965811 | AG1-449 C | Adder | 8.01 MW | 6.81 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 965831 | AG1-451 C | 50/50 | 5.04 MW | 5.04 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 316303 | AF2-085 | 50/50 | 2.02 MW | 2.02 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 958502 | AF2-144 E | Adder | 2.92 MW | 2.48 MW |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 961063 | AF2-397 BT | 50/50 | 26.04 MW | 26.04 MW |
| Details for AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 315083 | 1SPRUNCA | Adder | 1.45 MW | 1.23 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 315084 | 1SPRUNCB | Adder | 1.45 MW | 1.23 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 941032 | AE2-094 E | Adder | 11.14 MW | 9.46 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 944012 | AF1-069 E | Adder | 3.64 MW | 3.09 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 961062 | AF2-397 E | 50/50 | 25.81 MW | 25.81 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 961942 | AG1-037 E | Adder | 0.09 MW | 0.07 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 962332 | AG1-082 E | Adder | 0.35 MW | 0.3 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 962342 | AG1-083 E | Adder | 0.35 MW | 0.3 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 963041 | AG1-153 C | Adder | 1.63 MW | 1.38 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 963042 | AG1-153 E | Adder | 2.44 MW | 2.08 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 963102 | AG1-159 E | Adder | 1.06 MW | 0.9 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 963111 | AG1-160 C | Adder | 1.62 MW | 1.38 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 963112 | AG1-160 E | Adder | 2.43 MW | 2.07 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 964111 | AG1-272 C | 50/50 | 0.54 MW | 0.54 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 964112 | AG1-272 E | 50/50 | 0.81 MW | 0.81 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 964121 | AG1-273 C | 50/50 | 0.54 MW | 0.54 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 964122 | AG1-273 E | 50/50 | 0.81 MW | 0.81 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 964131 | AG1-274 C | 50/50 | 0.54 MW | 0.54 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 964132 | AG1-274 E | 50/50 | 0.81 MW | 0.81 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 964791 | AG1-342 C | Adder | 0.32 MW | 0.27 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 964792 | AG1-342 E | Adder | 0.48 MW | 0.4 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 964801 | AG1-343 C | Adder | 0.28 MW | 0.23 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 964802 | AG1-343 E | Adder | 0.42 MW | 0.35 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 965191 | AG1-384 C | 50/50 | 0.54 MW | 0.54 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 965192 | AG1-384 E | 50/50 | 0.81 MW | 0.81 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 963311 | AG1-180 C | Adder | 1.38 MW | 1.17 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 963312 | AG1-180 E | Adder | 1.15 MW | 0.98 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 963351 | AG1-184 C | Adder | 9.24 MW | 7.85 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 963352 | AG1-184 E | Adder | 6.59 MW | 5.6 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 963361 | AG1-185 C | 50/50 | 7.43 MW | 7.43 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 963362 | AG1-185 E | 50/50 | 6.24 MW | 6.24 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 965581 | AG1-426 C | 50/50 | 4.35 MW | 4.35 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 961611 | AG1-000B C | Adder | 1.52 MW | 1.29 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 940541 | AE2-040 C | Adder | 0.86 MW | 0.73 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 940651 | AE2-052 C | Adder | 1.06 MW | 0.9 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 940661 | AE2-053 C | Adder | 1.93 MW | 1.64 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 941281 | AE2-122 C | Adder | 6.37 MW | 5.42 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 941282 | AE2-122 E | Adder | 25.7 MW | 21.85 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 941291 | AE2-123 C | Adder | 6.55 MW | 5.56 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 941292 | AE2-123 E | Adder | 25.53 MW | 21.7 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 941301 | AE2-124 C | Adder | 5.95 MW | 5.06 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 941302 | AE2-124 E | Adder | 26.12 MW | 22.2 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 941591 | AE2-156 C | Adder | 5.01 MW | 4.26 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 942551 | AE2-270 C | Adder | 3.08 MW | 2.62 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 942552 | AE2-270 E | Adder | 4.62 MW | 3.93 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 943571 | AF1-028 C | Adder | -15.05 MW | -12.79 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 944581 | AF1-123 C | Adder | 7.9 MW | 6.71 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 944582 | AF1-123 E | Adder | 18.08 MW | 15.37 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 944591 | AF1-124 C | Adder | 10.71 MW | 9.11 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 944592 | AF1-124 E | Adder | 24.53 MW | 20.85 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 944601 | AF1-125 C | Adder | 10.71 MW | 9.11 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 944602 | AF1-125 E | Adder | 24.53 MW | 20.85 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 944631 | AF1-128 C | Adder | 11.31 MW | 9.62 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 944641 | AF1-129 C | Adder | 30.71 MW | 26.1 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 946011 | AF1-266 C | Adder | 4.09 MW | 3.48 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 946291 | AF1-293 C | 50/50 | 8.66 MW | 8.66 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 946292 | AF1-293 E | 50/50 | 12.98 MW | 12.98 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 961612 | AG1-000B E | Adder | 2.28 MW | 1.94 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 961711 | AG1-011 C | Adder | 8.22 MW | 6.99 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 964951 | AG1-359 C | Adder | 6.39 MW | 5.43 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 965001 | AG1-364 C | Adder | 2.0 MW | 1.7 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 965002 | AG1-364 E | Adder | 3.01 MW | 2.56 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 965771 | AG1-445 C | Adder | 2.25 MW | 1.91 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 965781 | AG1-446 C | Adder | 2.25 MW | 1.91 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 965811 | AG1-449 C | Adder | 6.84 MW | 5.81 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 965831 | AG1-451 C | 50/50 | 4.81 MW | 4.81 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 316303 | AF2-085 | Adder | 2.15 MW | 1.83 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 958502 | AF2-144 E | Adder | 2.77 MW | 2.36 MW |
| Details for AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 315083 | 1SPRUNCA | Adder | 1.44 MW | 1.22 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 315084 | 1SPRUNCB | Adder | 1.44 MW | 1.22 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 315131 | 1EDGECMA | Adder | 2.35 MW | 2.0 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 315611 | 6Z1-036WIND | Adder | 1.64 MW | 1.4 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 916042 | Z1-036 E | Adder | 6.93 MW | 5.89 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 941032 | AE2-094 E | Adder | 13.11 MW | 11.15 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 944012 | AF1-069 E | Adder | 4.28 MW | 3.64 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 961062 | AF2-397 E | 50/50 | 26.61 MW | 26.61 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 961942 | AG1-037 E | Adder | 0.1 MW | 0.08 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 962332 | AG1-082 E | Adder | 0.39 MW | 0.33 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 962342 | AG1-083 E | Adder | 0.39 MW | 0.33 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 963041 | AG1-153 C | Adder | 1.92 MW | 1.63 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 963042 | AG1-153 E | Adder | 2.87 MW | 2.44 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 963102 | AG1-159 E | Adder | 1.19 MW | 1.01 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 963111 | AG1-160 C | Adder | 1.91 MW | 1.62 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 963112 | AG1-160 E | Adder | 2.86 MW | 2.44 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 964111 | AG1-272 C | 50/50 | 0.58 MW | 0.58 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 964112 | AG1-272 E | 50/50 | 0.87 MW | 0.87 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 964121 | AG1-273 C | 50/50 | 0.58 MW | 0.58 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 964122 | AG1-273 E | 50/50 | 0.87 MW | 0.87 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 964131 | AG1-274 C | 50/50 | 0.58 MW | 0.58 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 964132 | AG1-274 E | 50/50 | 0.87 MW | 0.87 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 964791 | AG1-342 C | Adder | 0.35 MW | 0.3 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 964792 | AG1-342 E | Adder | 0.53 MW | 0.45 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 964801 | AG1-343 C | Adder | 0.3 MW | 0.26 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 964802 | AG1-343 E | Adder | 0.45 MW | 0.38 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 965191 | AG1-384 C | 50/50 | 0.58 MW | 0.58 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 965192 | AG1-384 E | 50/50 | 0.87 MW | 0.87 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 966251 | AG1-494 C | Adder | 1.21 MW | 1.03 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 966252 | AG1-494 E | Adder | 1.81 MW | 1.54 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 966691 | AG1-539 C | Adder | 1.68 MW | 1.43 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 966692 | AG1-539 E | Adder | 2.26 MW | 1.93 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 963311 | AG1-180 C | Adder | 1.51 MW | 1.28 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 963312 | AG1-180 E | Adder | 1.26 MW | 1.07 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 963351 | AG1-184 C | Adder | 10.7 MW | 9.1 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 963352 | AG1-184 E | Adder | 7.64 MW | 6.49 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 963361 | AG1-185 C | 50/50 | 7.94 MW | 7.94 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 963362 | AG1-185 E | 50/50 | 6.67 MW | 6.67 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 965581 | AG1-426 C | 50/50 | 4.61 MW | 4.61 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 940541 | AE2-040 C | Adder | 0.95 MW | 0.8 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 940651 | AE2-052 C | Adder | 1.08 MW | 0.91 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 940661 | AE2-053 C | 50/50 | 2.12 MW | 2.12 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 941281 | AE2-122 C | Adder | 6.57 MW | 5.58 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 941282 | AE2-122 E | Adder | 26.51 MW | 22.53 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 941291 | AE2-123 C | Adder | 6.75 MW | 5.74 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 941292 | AE2-123 E | Adder | 26.33 MW | 22.38 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 941301 | AE2-124 C | Adder | 6.14 MW | 5.22 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 941302 | AE2-124 E | Adder | 26.94 MW | 22.9 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 943571 | AF1-028 C | Adder | -11.41 MW | -9.7 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 944141 | AF1-082 C | Adder | 0.95 MW | 0.81 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 944581 | AF1-123 C | Adder | 11.08 MW | 9.42 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 944582 | AF1-123 E | Adder | 25.37 MW | 21.56 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 944591 | AF1-124 C | Adder | 11.08 MW | 9.42 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 944592 | AF1-124 E | Adder | 25.37 MW | 21.56 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 944601 | AF1-125 C | Adder | 11.08 MW | 9.42 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 944602 | AF1-125 E | Adder | 25.37 MW | 21.56 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 944641 | AF1-129 C | Adder | 29.67 MW | 25.22 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 946011 | AF1-266 C | Adder | 4.51 MW | 3.83 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 946291 | AF1-293 C | 50/50 | 9.2 MW | 9.2 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 946292 | AF1-293 E | 50/50 | 13.8 MW | 13.8 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 961602 | AG1-000A E | Adder | 1.83 MW | 1.55 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 964951 | AG1-359 C | Adder | 6.6 MW | 5.61 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 965001 | AG1-364 C | Adder | 1.64 MW | 1.4 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 965002 | AG1-364 E | Adder | 2.46 MW | 2.09 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 965741 | AG1-442 C | Adder | 1.9 MW | 1.61 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 965751 | AG1-443 C | Adder | 1.9 MW | 1.61 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 965761 | AG1-444 C | Adder | 4.16 MW | 3.54 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 965771 | AG1-445 C | Adder | 2.48 MW | 2.11 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 965781 | AG1-446 C | Adder | 2.48 MW | 2.11 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 965811 | AG1-449 C | Adder | 8.01 MW | 6.81 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 965831 | AG1-451 C | 50/50 | 5.04 MW | 5.04 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 316303 | AF2-085 | 50/50 | 2.02 MW | 2.02 MW |
| AF2-397 TP-6CUNNING 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 958502 | AF2-144 E | Adder | 2.92 MW | 2.48 MW |
| Details for 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 315083 | 1SPRUNCA | Adder | 1.45 MW | 1.23 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 315084 | 1SPRUNCB | Adder | 1.45 MW | 1.23 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 941032 | AE2-094 E | Adder | 11.14 MW | 9.46 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 944012 | AF1-069 E | Adder | 3.64 MW | 3.09 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 961062 | AF2-397 E | 50/50 | 25.81 MW | 25.81 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 961942 | AG1-037 E | Adder | 0.09 MW | 0.07 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 962332 | AG1-082 E | Adder | 0.35 MW | 0.3 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 962342 | AG1-083 E | Adder | 0.35 MW | 0.3 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 963041 | AG1-153 C | Adder | 1.63 MW | 1.38 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 963042 | AG1-153 E | Adder | 2.44 MW | 2.08 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 963102 | AG1-159 E | Adder | 1.06 MW | 0.9 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 963111 | AG1-160 C | Adder | 1.62 MW | 1.38 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 963112 | AG1-160 E | Adder | 2.43 MW | 2.07 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 964111 | AG1-272 C | 50/50 | 0.54 MW | 0.54 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 964112 | AG1-272 E | 50/50 | 0.81 MW | 0.81 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 964121 | AG1-273 C | 50/50 | 0.54 MW | 0.54 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 964122 | AG1-273 E | 50/50 | 0.81 MW | 0.81 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 964131 | AG1-274 C | 50/50 | 0.54 MW | 0.54 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 964132 | AG1-274 E | 50/50 | 0.81 MW | 0.81 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 964791 | AG1-342 C | Adder | 0.32 MW | 0.27 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 964792 | AG1-342 E | Adder | 0.48 MW | 0.4 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 964801 | AG1-343 C | Adder | 0.28 MW | 0.23 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 964802 | AG1-343 E | Adder | 0.42 MW | 0.35 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 965191 | AG1-384 C | 50/50 | 0.54 MW | 0.54 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 965192 | AG1-384 E | 50/50 | 0.81 MW | 0.81 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 963311 | AG1-180 C | Adder | 1.38 MW | 1.17 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 963312 | AG1-180 E | Adder | 1.15 MW | 0.98 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 963351 | AG1-184 C | Adder | 9.24 MW | 7.85 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 963352 | AG1-184 E | Adder | 6.59 MW | 5.6 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 963361 | AG1-185 C | 50/50 | 7.43 MW | 7.43 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 963362 | AG1-185 E | 50/50 | 6.24 MW | 6.24 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 965581 | AG1-426 C | 50/50 | 4.35 MW | 4.35 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 961611 | AG1-000B C | Adder | 1.52 MW | 1.29 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 940541 | AE2-040 C | Adder | 0.86 MW | 0.73 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 940651 | AE2-052 C | Adder | 1.06 MW | 0.9 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 940661 | AE2-053 C | Adder | 1.93 MW | 1.64 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 941281 | AE2-122 C | Adder | 6.37 MW | 5.42 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 941282 | AE2-122 E | Adder | 25.7 MW | 21.85 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 941291 | AE2-123 C | Adder | 6.55 MW | 5.56 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 941292 | AE2-123 E | Adder | 25.53 MW | 21.7 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 941301 | AE2-124 C | Adder | 5.95 MW | 5.06 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 941302 | AE2-124 E | Adder | 26.12 MW | 22.2 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 941591 | AE2-156 C | Adder | 5.01 MW | 4.26 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 942551 | AE2-270 C | Adder | 3.08 MW | 2.62 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 942552 | AE2-270 E | Adder | 4.62 MW | 3.93 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 943571 | AF1-028 C | Adder | -15.05 MW | -12.79 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 944581 | AF1-123 C | Adder | 7.9 MW | 6.71 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 944582 | AF1-123 E | Adder | 18.08 MW | 15.37 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 944591 | AF1-124 C | Adder | 10.71 MW | 9.11 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 944592 | AF1-124 E | Adder | 24.53 MW | 20.85 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 944601 | AF1-125 C | Adder | 10.71 MW | 9.11 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 944602 | AF1-125 E | Adder | 24.53 MW | 20.85 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 944631 | AF1-128 C | Adder | 11.31 MW | 9.62 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 944641 | AF1-129 C | Adder | 30.71 MW | 26.1 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 946011 | AF1-266 C | Adder | 4.09 MW | 3.48 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 946291 | AF1-293 C | 50/50 | 8.66 MW | 8.66 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 946292 | AF1-293 E | 50/50 | 12.98 MW | 12.98 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 961612 | AG1-000B E | Adder | 2.28 MW | 1.94 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 961711 | AG1-011 C | Adder | 8.22 MW | 6.99 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 964951 | AG1-359 C | Adder | 6.39 MW | 5.43 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 965001 | AG1-364 C | Adder | 2.0 MW | 1.7 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 965002 | AG1-364 E | Adder | 3.01 MW | 2.56 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 965771 | AG1-445 C | Adder | 2.25 MW | 1.91 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 965781 | AG1-446 C | Adder | 2.25 MW | 1.91 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 965811 | AG1-449 C | Adder | 6.84 MW | 5.81 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 965831 | AG1-451 C | 50/50 | 4.81 MW | 4.81 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 316303 | AF2-085 | Adder | 2.15 MW | 1.83 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 958502 | AF2-144 E | Adder | 2.77 MW | 2.36 MW |
| Details for 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 315083 | 1SPRUNCA | Adder | 1.44 MW | 1.22 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 315084 | 1SPRUNCB | Adder | 1.44 MW | 1.22 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 315131 | 1EDGECMA | Adder | 2.35 MW | 2.0 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 315611 | 6Z1-036WIND | Adder | 1.64 MW | 1.4 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 916042 | Z1-036 E | Adder | 6.93 MW | 5.89 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 941032 | AE2-094 E | Adder | 13.11 MW | 11.15 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 944012 | AF1-069 E | Adder | 4.28 MW | 3.64 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 961062 | AF2-397 E | 50/50 | 26.61 MW | 26.61 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 961942 | AG1-037 E | Adder | 0.1 MW | 0.08 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 962332 | AG1-082 E | Adder | 0.39 MW | 0.33 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 962342 | AG1-083 E | Adder | 0.39 MW | 0.33 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 963041 | AG1-153 C | Adder | 1.92 MW | 1.63 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 963042 | AG1-153 E | Adder | 2.87 MW | 2.44 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 963102 | AG1-159 E | Adder | 1.19 MW | 1.01 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 963111 | AG1-160 C | Adder | 1.91 MW | 1.62 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 963112 | AG1-160 E | Adder | 2.86 MW | 2.44 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 964111 | AG1-272 C | 50/50 | 0.58 MW | 0.58 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 964112 | AG1-272 E | 50/50 | 0.87 MW | 0.87 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 964121 | AG1-273 C | 50/50 | 0.58 MW | 0.58 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 964122 | AG1-273 E | 50/50 | 0.87 MW | 0.87 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 964131 | AG1-274 C | 50/50 | 0.58 MW | 0.58 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 964132 | AG1-274 E | 50/50 | 0.87 MW | 0.87 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 964791 | AG1-342 C | Adder | 0.35 MW | 0.3 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 964792 | AG1-342 E | Adder | 0.53 MW | 0.45 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 964801 | AG1-343 C | Adder | 0.3 MW | 0.26 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 964802 | AG1-343 E | Adder | 0.45 MW | 0.38 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 965191 | AG1-384 C | 50/50 | 0.58 MW | 0.58 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 965192 | AG1-384 E | 50/50 | 0.87 MW | 0.87 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 966251 | AG1-494 C | Adder | 1.21 MW | 1.03 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 966252 | AG1-494 E | Adder | 1.81 MW | 1.54 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 966691 | AG1-539 C | Adder | 1.68 MW | 1.43 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 966692 | AG1-539 E | Adder | 2.26 MW | 1.93 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 963311 | AG1-180 C | Adder | 1.51 MW | 1.28 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 963312 | AG1-180 E | Adder | 1.26 MW | 1.07 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 963351 | AG1-184 C | Adder | 10.7 MW | 9.1 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 963352 | AG1-184 E | Adder | 7.64 MW | 6.49 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 963361 | AG1-185 C | 50/50 | 7.94 MW | 7.94 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 963362 | AG1-185 E | 50/50 | 6.67 MW | 6.67 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 965581 | AG1-426 C | 50/50 | 4.61 MW | 4.61 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 940541 | AE2-040 C | Adder | 0.95 MW | 0.8 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 940651 | AE2-052 C | Adder | 1.08 MW | 0.91 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 940661 | AE2-053 C | 50/50 | 2.12 MW | 2.12 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 941281 | AE2-122 C | Adder | 6.57 MW | 5.58 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 941282 | AE2-122 E | Adder | 26.51 MW | 22.53 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 941291 | AE2-123 C | Adder | 6.75 MW | 5.74 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 941292 | AE2-123 E | Adder | 26.33 MW | 22.38 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 941301 | AE2-124 C | Adder | 6.14 MW | 5.22 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 941302 | AE2-124 E | Adder | 26.94 MW | 22.9 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 943571 | AF1-028 C | Adder | -11.41 MW | -9.7 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 944141 | AF1-082 C | Adder | 0.95 MW | 0.81 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 944581 | AF1-123 C | Adder | 11.08 MW | 9.42 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 944582 | AF1-123 E | Adder | 25.37 MW | 21.56 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 944591 | AF1-124 C | Adder | 11.08 MW | 9.42 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 944592 | AF1-124 E | Adder | 25.37 MW | 21.56 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 944601 | AF1-125 C | Adder | 11.08 MW | 9.42 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 944602 | AF1-125 E | Adder | 25.37 MW | 21.56 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 944641 | AF1-129 C | Adder | 29.67 MW | 25.22 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 946011 | AF1-266 C | Adder | 4.51 MW | 3.83 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 946291 | AF1-293 C | 50/50 | 9.2 MW | 9.2 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 946292 | AF1-293 E | 50/50 | 13.8 MW | 13.8 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 961602 | AG1-000A E | Adder | 1.83 MW | 1.55 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 964951 | AG1-359 C | Adder | 6.6 MW | 5.61 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 965001 | AG1-364 C | Adder | 1.64 MW | 1.4 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 965002 | AG1-364 E | Adder | 2.46 MW | 2.09 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 965741 | AG1-442 C | Adder | 1.9 MW | 1.61 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 965751 | AG1-443 C | Adder | 1.9 MW | 1.61 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 965761 | AG1-444 C | Adder | 4.16 MW | 3.54 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 965771 | AG1-445 C | Adder | 2.48 MW | 2.11 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 965781 | AG1-446 C | Adder | 2.48 MW | 2.11 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 965811 | AG1-449 C | Adder | 8.01 MW | 6.81 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 965831 | AG1-451 C | 50/50 | 5.04 MW | 5.04 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 316303 | AF2-085 | 50/50 | 2.02 MW | 2.02 MW |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 958502 | AF2-144 E | Adder | 2.92 MW | 2.48 MW |
| Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 315083 | 1SPRUNCA | Adder | 1.45 MW | 1.23 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 315084 | 1SPRUNCB | Adder | 1.45 MW | 1.23 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 941032 | AE2-094 E | Adder | 11.14 MW | 9.46 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 944012 | AF1-069 E | Adder | 3.64 MW | 3.09 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 961062 | AF2-397 E | 50/50 | 25.81 MW | 25.81 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 961942 | AG1-037 E | Adder | 0.09 MW | 0.07 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 962332 | AG1-082 E | Adder | 0.35 MW | 0.3 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 962342 | AG1-083 E | Adder | 0.35 MW | 0.3 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 963041 | AG1-153 C | Adder | 1.63 MW | 1.38 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 963042 | AG1-153 E | Adder | 2.44 MW | 2.08 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 963102 | AG1-159 E | Adder | 1.06 MW | 0.9 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 963111 | AG1-160 C | Adder | 1.62 MW | 1.38 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 963112 | AG1-160 E | Adder | 2.43 MW | 2.07 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 964111 | AG1-272 C | 50/50 | 0.54 MW | 0.54 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 964112 | AG1-272 E | 50/50 | 0.81 MW | 0.81 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 964121 | AG1-273 C | 50/50 | 0.54 MW | 0.54 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 964122 | AG1-273 E | 50/50 | 0.81 MW | 0.81 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 964131 | AG1-274 C | 50/50 | 0.54 MW | 0.54 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 964132 | AG1-274 E | 50/50 | 0.81 MW | 0.81 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 964791 | AG1-342 C | Adder | 0.32 MW | 0.27 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 964792 | AG1-342 E | Adder | 0.48 MW | 0.4 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 964801 | AG1-343 C | Adder | 0.28 MW | 0.23 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 964802 | AG1-343 E | Adder | 0.42 MW | 0.35 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 965191 | AG1-384 C | 50/50 | 0.54 MW | 0.54 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 965192 | AG1-384 E | 50/50 | 0.81 MW | 0.81 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 963311 | AG1-180 C | Adder | 1.38 MW | 1.17 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 963312 | AG1-180 E | Adder | 1.15 MW | 0.98 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 963351 | AG1-184 C | Adder | 9.24 MW | 7.85 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 963352 | AG1-184 E | Adder | 6.59 MW | 5.6 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 963361 | AG1-185 C | 50/50 | 7.43 MW | 7.43 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 963362 | AG1-185 E | 50/50 | 6.24 MW | 6.24 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 965581 | AG1-426 C | 50/50 | 4.35 MW | 4.35 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 961611 | AG1-000B C | Adder | 1.52 MW | 1.29 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 940541 | AE2-040 C | Adder | 0.86 MW | 0.73 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 940651 | AE2-052 C | Adder | 1.06 MW | 0.9 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 940661 | AE2-053 C | Adder | 1.93 MW | 1.64 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 941281 | AE2-122 C | Adder | 6.37 MW | 5.42 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 941282 | AE2-122 E | Adder | 25.7 MW | 21.85 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 941291 | AE2-123 C | Adder | 6.55 MW | 5.56 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 941292 | AE2-123 E | Adder | 25.53 MW | 21.7 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 941301 | AE2-124 C | Adder | 5.95 MW | 5.06 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 941302 | AE2-124 E | Adder | 26.12 MW | 22.2 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 941591 | AE2-156 C | Adder | 5.01 MW | 4.26 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 942551 | AE2-270 C | Adder | 3.08 MW | 2.62 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 942552 | AE2-270 E | Adder | 4.62 MW | 3.93 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 943571 | AF1-028 C | Adder | -15.05 MW | -12.79 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 944581 | AF1-123 C | Adder | 7.9 MW | 6.71 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 944582 | AF1-123 E | Adder | 18.08 MW | 15.37 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 944591 | AF1-124 C | Adder | 10.71 MW | 9.11 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 944592 | AF1-124 E | Adder | 24.53 MW | 20.85 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 944601 | AF1-125 C | Adder | 10.71 MW | 9.11 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 944602 | AF1-125 E | Adder | 24.53 MW | 20.85 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 944631 | AF1-128 C | Adder | 11.31 MW | 9.62 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 944641 | AF1-129 C | Adder | 30.71 MW | 26.1 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 946011 | AF1-266 C | Adder | 4.09 MW | 3.48 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 946291 | AF1-293 C | 50/50 | 8.66 MW | 8.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 946292 | AF1-293 E | 50/50 | 12.98 MW | 12.98 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 961612 | AG1-000B E | Adder | 2.28 MW | 1.94 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 961711 | AG1-011 C | Adder | 8.22 MW | 6.99 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 964951 | AG1-359 C | Adder | 6.39 MW | 5.43 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 965001 | AG1-364 C | Adder | 2.0 MW | 1.7 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 965002 | AG1-364 E | Adder | 3.01 MW | 2.56 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 965771 | AG1-445 C | Adder | 2.25 MW | 1.91 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 965781 | AG1-446 C | Adder | 2.25 MW | 1.91 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 965811 | AG1-449 C | Adder | 6.84 MW | 5.81 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 965831 | AG1-451 C | 50/50 | 4.81 MW | 4.81 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 316303 | AF2-085 | Adder | 2.15 MW | 1.83 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 534T564_SRT-L | 958502 | AF2-144 E | Adder | 2.77 MW | 2.36 MW |
| Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 315083 | 1SPRUNCA | Adder | 1.44 MW | 1.22 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 315084 | 1SPRUNCB | Adder | 1.44 MW | 1.22 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 315131 | 1EDGECMA | Adder | 2.35 MW | 2.0 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 315611 | 6Z1-036WIND | Adder | 1.64 MW | 1.4 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 916042 | Z1-036 E | Adder | 6.93 MW | 5.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 941032 | AE2-094 E | Adder | 13.11 MW | 11.15 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 944012 | AF1-069 E | Adder | 4.28 MW | 3.64 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 961062 | AF2-397 E | 50/50 | 26.61 MW | 26.61 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 961942 | AG1-037 E | Adder | 0.1 MW | 0.08 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 962332 | AG1-082 E | Adder | 0.39 MW | 0.33 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 962342 | AG1-083 E | Adder | 0.39 MW | 0.33 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 963041 | AG1-153 C | Adder | 1.92 MW | 1.63 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 963042 | AG1-153 E | Adder | 2.87 MW | 2.44 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 963102 | AG1-159 E | Adder | 1.19 MW | 1.01 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 963111 | AG1-160 C | Adder | 1.91 MW | 1.62 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 963112 | AG1-160 E | Adder | 2.86 MW | 2.44 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 964111 | AG1-272 C | 50/50 | 0.58 MW | 0.58 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 964112 | AG1-272 E | 50/50 | 0.87 MW | 0.87 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 964121 | AG1-273 C | 50/50 | 0.58 MW | 0.58 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 964122 | AG1-273 E | 50/50 | 0.87 MW | 0.87 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 964131 | AG1-274 C | 50/50 | 0.58 MW | 0.58 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 964132 | AG1-274 E | 50/50 | 0.87 MW | 0.87 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 964791 | AG1-342 C | Adder | 0.35 MW | 0.3 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 964792 | AG1-342 E | Adder | 0.53 MW | 0.45 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 964801 | AG1-343 C | Adder | 0.3 MW | 0.26 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 964802 | AG1-343 E | Adder | 0.45 MW | 0.38 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 965191 | AG1-384 C | 50/50 | 0.58 MW | 0.58 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 965192 | AG1-384 E | 50/50 | 0.87 MW | 0.87 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 966251 | AG1-494 C | Adder | 1.21 MW | 1.03 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 966252 | AG1-494 E | Adder | 1.81 MW | 1.54 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 966691 | AG1-539 C | Adder | 1.68 MW | 1.43 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 966692 | AG1-539 E | Adder | 2.26 MW | 1.93 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 963311 | AG1-180 C | Adder | 1.51 MW | 1.28 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 963312 | AG1-180 E | Adder | 1.26 MW | 1.07 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 963351 | AG1-184 C | Adder | 10.7 MW | 9.1 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 963352 | AG1-184 E | Adder | 7.64 MW | 6.49 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 963361 | AG1-185 C | 50/50 | 7.94 MW | 7.94 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 963362 | AG1-185 E | 50/50 | 6.67 MW | 6.67 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 965581 | AG1-426 C | 50/50 | 4.61 MW | 4.61 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 940541 | AE2-040 C | Adder | 0.95 MW | 0.8 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 940651 | AE2-052 C | Adder | 1.08 MW | 0.91 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 940661 | AE2-053 C | 50/50 | 2.12 MW | 2.12 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 941281 | AE2-122 C | Adder | 6.57 MW | 5.58 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 941282 | AE2-122 E | Adder | 26.51 MW | 22.53 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 941291 | AE2-123 C | Adder | 6.75 MW | 5.74 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 941292 | AE2-123 E | Adder | 26.33 MW | 22.38 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 941301 | AE2-124 C | Adder | 6.14 MW | 5.22 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 941302 | AE2-124 E | Adder | 26.94 MW | 22.9 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 943571 | AF1-028 C | Adder | -11.41 MW | -9.7 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 944141 | AF1-082 C | Adder | 0.95 MW | 0.81 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 944581 | AF1-123 C | Adder | 11.08 MW | 9.42 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 944582 | AF1-123 E | Adder | 25.37 MW | 21.56 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 944591 | AF1-124 C | Adder | 11.08 MW | 9.42 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 944592 | AF1-124 E | Adder | 25.37 MW | 21.56 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 944601 | AF1-125 C | Adder | 11.08 MW | 9.42 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 944602 | AF1-125 E | Adder | 25.37 MW | 21.56 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 944641 | AF1-129 C | Adder | 29.67 MW | 25.22 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 946011 | AF1-266 C | Adder | 4.51 MW | 3.83 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 946291 | AF1-293 C | 50/50 | 9.2 MW | 9.2 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 946292 | AF1-293 E | 50/50 | 13.8 MW | 13.8 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 961602 | AG1-000A E | Adder | 1.83 MW | 1.55 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 964951 | AG1-359 C | Adder | 6.6 MW | 5.61 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 965001 | AG1-364 C | Adder | 1.64 MW | 1.4 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 965002 | AG1-364 E | Adder | 2.46 MW | 2.09 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 965741 | AG1-442 C | Adder | 1.9 MW | 1.61 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 965751 | AG1-443 C | Adder | 1.9 MW | 1.61 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 965761 | AG1-444 C | Adder | 4.16 MW | 3.54 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 965771 | AG1-445 C | Adder | 2.48 MW | 2.11 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 965781 | AG1-446 C | Adder | 2.48 MW | 2.11 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 965811 | AG1-449 C | Adder | 8.01 MW | 6.81 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 965831 | AG1-451 C | 50/50 | 5.04 MW | 5.04 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 316303 | AF2-085 | 50/50 | 2.02 MW | 2.02 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-L | 958502 | AF2-144 E | Adder | 2.92 MW | 2.48 MW |
| Details for 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-L | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-L | 315131 | 1EDGECMA | Adder | 2.72 MW | 2.31 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-L | 315611 | 6Z1-036WIND | Adder | 1.79 MW | 1.52 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-L | 916042 | Z1-036 E | Adder | 7.57 MW | 6.43 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-L | 941032 | AE2-094 E | Adder | 16.92 MW | 14.39 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-L | 944012 | AF1-069 E | Adder | 5.53 MW | 4.7 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-L | 961942 | AG1-037 E | Adder | 0.11 MW | 0.09 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-L | 962332 | AG1-082 E | Adder | 0.44 MW | 0.37 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-L | 962342 | AG1-083 E | Adder | 0.44 MW | 0.37 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-L | 963041 | AG1-153 C | Adder | 2.33 MW | 1.98 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-L | 963042 | AG1-153 E | Adder | 3.49 MW | 2.97 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-L | 963102 | AG1-159 E | Adder | 1.3 MW | 1.1 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-L | 963111 | AG1-160 C | Adder | 2.37 MW | 2.01 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-L | 963112 | AG1-160 E | Adder | 3.55 MW | 3.02 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-L | 964801 | AG1-343 C | Adder | 0.33 MW | 0.28 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-L | 964802 | AG1-343 E | Adder | 0.5 MW | 0.42 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-L | 963311 | AG1-180 C | Adder | 1.12 MW | 0.95 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-L | 963312 | AG1-180 E | Adder | 0.94 MW | 0.8 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-L | 963351 | AG1-184 C | Adder | 14.04 MW | 11.93 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-L | 963352 | AG1-184 E | Adder | 10.02 MW | 8.52 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-L | 961611 | AG1-000B C | Adder | 2.38 MW | 2.02 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-L | 940541 | AE2-040 C | 50/50 | 1.75 MW | 1.75 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-L | 940651 | AE2-052 C | 50/50 | 2.52 MW | 2.52 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-L | 940661 | AE2-053 C | Adder | 1.06 MW | 0.9 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-L | 941281 | AE2-122 C | Adder | 6.86 MW | 5.83 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-L | 941282 | AE2-122 E | Adder | 27.7 MW | 23.55 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-L | 941291 | AE2-123 C | Adder | 7.05 MW | 6.0 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-L | 941292 | AE2-123 E | Adder | 27.51 MW | 23.38 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-L | 941301 | AE2-124 C | Adder | 6.41 MW | 5.45 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-L | 941302 | AE2-124 E | Adder | 28.11 MW | 23.9 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-L | 941591 | AE2-156 C | Adder | 5.45 MW | 4.63 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-L | 942551 | AE2-270 C | Adder | 5.7 MW | 4.84 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-L | 942552 | AE2-270 E | Adder | 8.55 MW | 7.26 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-L | 944141 | AF1-082 C | Adder | 1.08 MW | 0.92 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-L | 944581 | AF1-123 C | Adder | 11.0 MW | 9.35 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-L | 944582 | AF1-123 E | Adder | 25.18 MW | 21.4 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-L | 944591 | AF1-124 C | Adder | 11.0 MW | 9.35 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-L | 944592 | AF1-124 E | Adder | 25.18 MW | 21.4 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-L | 944601 | AF1-125 C | Adder | 11.0 MW | 9.35 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-L | 944602 | AF1-125 E | Adder | 25.18 MW | 21.4 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-L | 944641 | AF1-129 C | 50/50 | 136.41 MW | 136.41 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-L | 946011 | AF1-266 C | 50/50 | 8.08 MW | 8.08 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-L | 961602 | AG1-000A E | Adder | 2.11 MW | 1.79 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-L | 961612 | AG1-000B E | Adder | 3.57 MW | 3.03 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-L | 961711 | AG1-011 C | Adder | 15.21 MW | 12.93 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-L | 964951 | AG1-359 C | Adder | 6.8 MW | 5.78 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-L | 965001 | AG1-364 C | Adder | 2.18 MW | 1.85 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-L | 965002 | AG1-364 E | Adder | 3.27 MW | 2.78 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-L | 965741 | AG1-442 C | Adder | 2.17 MW | 1.84 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-L | 965751 | AG1-443 C | Adder | 2.17 MW | 1.84 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-L | 965761 | AG1-444 C | Adder | 4.79 MW | 4.07 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-L | 965771 | AG1-445 C | Adder | 1.47 MW | 1.25 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-L | 965781 | AG1-446 C | Adder | 1.47 MW | 1.25 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-L | 965811 | AG1-449 C | Adder | 9.8 MW | 8.33 MW |
| Details for 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-L | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-L | 941032 | AE2-094 E | 50/50 | 34.95 MW | 34.95 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-L | 944012 | AF1-069 E | 50/50 | 11.42 MW | 11.42 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-L | 963041 | AG1-153 C | 50/50 | 4.67 MW | 4.67 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-L | 963042 | AG1-153 E | 50/50 | 7.01 MW | 7.01 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-L | 963111 | AG1-160 C | 50/50 | 4.79 MW | 4.79 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-L | 963112 | AG1-160 E | 50/50 | 7.18 MW | 7.18 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-L | 963351 | AG1-184 C | 50/50 | 28.72 MW | 28.72 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-L | 963352 | AG1-184 E | 50/50 | 20.5 MW | 20.5 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-L | 941281 | AE2-122 C | Adder | 7.21 MW | 6.13 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-L | 941282 | AE2-122 E | Adder | 29.1 MW | 24.74 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-L | 941291 | AE2-123 C | Adder | 7.41 MW | 6.3 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-L | 941292 | AE2-123 E | Adder | 28.91 MW | 24.57 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-L | 941301 | AE2-124 C | Adder | 6.76 MW | 5.75 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-L | 941302 | AE2-124 E | Adder | 29.67 MW | 25.22 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-L | 941591 | AE2-156 C | Adder | 5.56 MW | 4.72 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-L | 944581 | AF1-123 C | Adder | 14.29 MW | 12.15 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-L | 944582 | AF1-123 E | Adder | 32.72 MW | 27.81 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-L | 944591 | AF1-124 C | Adder | 14.29 MW | 12.15 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-L | 944592 | AF1-124 E | Adder | 32.72 MW | 27.81 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-L | 944601 | AF1-125 C | Adder | 14.29 MW | 12.15 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-L | 944602 | AF1-125 E | Adder | 32.72 MW | 27.81 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-L | 964951 | AG1-359 C | Adder | 7.49 MW | 6.36 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-L | 965001 | AG1-364 C | Adder | 2.22 MW | 1.89 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-L | 965002 | AG1-364 E | Adder | 3.33 MW | 2.83 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-L | 965811 | AG1-449 C | 50/50 | 20.07 MW | 20.07 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-L | 940543 | AE2-040 BT | 50/50 | 5.29 MW | 5.29 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-L | 940653 | AE2-052 BT | 50/50 | 3.84 MW | 3.84 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-L | 946013 | AF1-266 BT | 50/50 | 23.77 MW | 23.77 MW |
Light Load Potential Congestion due to Local Energy Deliverability
| Light Load Potential Congestion due to Local Energy Deliverability | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Final Cycle Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | ||
| DVP |
6FENTRES-6THRASHER 230.0 kV Ckt 1 line
314466 to 314508 ckt 1 |
DVP_P1-2: LN 588_SRT-A
CONTINGENCY 'DVP_P1-2: LN 588_SRT-A' OPEN BRANCH FROM BUS 314909 TO BUS 314927 CKT 1 /*8FENTRES 500.0 - 8YADKIN 500.0 END |
OP | AC | 217.73 % | 678.68 | B | 1477.71 | 400.32 | ||
| DVP |
6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer
314747 to 314744 ckt 1 |
DVP_P1-2: LN 2193_SRT-A
CONTINGENCY 'DVP_P1-2: LN 2193_SRT-A' OPEN BRANCH FROM BUS 313707 TO BUS 313867 CKT 1 /*6FORK UNION 230.0 - 6BREMODIST 230.0 OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1 /*6BREMODIST 230.0 - 6BREMO 230.0 OPEN BUS 313867 /*6BREMODIST 230.0 END |
OP | AC | 153.29 % | 307.38 | B | 471.19 | 18.39 | ||
| DVP |
6THRASHER-6YADKIN 230.0 kV Ckt 1 line
314508 to 314514 ckt 1 |
DVP_P1-2: LN 588_SRT-A
CONTINGENCY 'DVP_P1-2: LN 588_SRT-A' OPEN BRANCH FROM BUS 314909 TO BUS 314927 CKT 1 /*8FENTRES 500.0 - 8YADKIN 500.0 END |
OP | AC | 143.24 % | 818.74 | B | 1172.73 | 250.6 | ||
| DVP |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer
314218 to 314908 ckt 2 |
DVP_P1-2: LN 557_SRT-L
CONTINGENCY 'DVP_P1-2: LN 557_SRT-L' OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1 /*8CHCKAHM 500.0 - 8ELMONT 500.0 SET POSTCONTRATING 3300 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 SET PRECONTRATING 3118 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 END |
OP | AC | 105.0 % | 879.84 | B | 923.79 | 76.12 | ||
| DVP |
3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 2 transformer
314666 to 314667 ckt 2 |
DVP_P1-3: 4ALTVSTA-TX#3_SRT-A
CONTINGENCY 'DVP_P1-3: 4ALTVSTA-TX#3_SRT-A' OPEN BRANCH FROM BUS 314666 TO BUS 314667 CKT 1 /*3ALTVSTA 115.0 - 4ALTVSTA 138.0 END |
OP | AC | 112.86 % | 130.47 | B | 147.25 | 8.84 | ||
| DVP |
3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 1 transformer
314666 to 314667 ckt 1 |
DVP_P1-3: 4ALTVSTA-TX#4_SRT-A
CONTINGENCY 'DVP_P1-3: 4ALTVSTA-TX#4_SRT-A' OPEN BRANCH FROM BUS 314666 TO BUS 314667 CKT 2 /*3ALTVSTA 115.0 - 4ALTVSTA 138.0 END |
OP | AC | 109.55 % | 126.52 | B | 138.61 | 8.32 | ||
| DVP |
6FENTRES-6POCATY 230.0 kV Ckt 1 line
314466 to 316171 ckt 1 |
DVP_P1-2: LN 588_SRT-A
CONTINGENCY 'DVP_P1-2: LN 588_SRT-A' OPEN BRANCH FROM BUS 314909 TO BUS 314927 CKT 1 /*8FENTRES 500.0 - 8YADKIN 500.0 END |
OP | AC | 106.77 % | 678.68 | B | 724.62 | 203.06 | ||
| DVP |
6POCATY-6LANDSTN 230.0 kV Ckt 1 line
316171 to 314481 ckt 1 |
DVP_P1-2: LN 588_SRT-A
CONTINGENCY 'DVP_P1-2: LN 588_SRT-A' OPEN BRANCH FROM BUS 314909 TO BUS 314927 CKT 1 /*8FENTRES 500.0 - 8YADKIN 500.0 END |
OP | AC | 106.75 % | 678.68 | B | 724.51 | 203.06 | ||
| DVP |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
314924 to 314903 ckt 1 |
DVP_P1-2: LN 563_SRT-L-1
CONTINGENCY 'DVP_P1-2: LN 563_SRT-L-1' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 SET POSTCONTRATING 3559 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TP 500.0 SET POSTCONTRATING 3559 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA 500.0 - AE2-051 TP 500.0 SET PRECONTRATING 3377 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TP 500.0 SET PRECONTRATING 3377 BRANCH FROM BUS 314923 TO BUS 940640 CKT 1 /*8SEPTA 500.0 - AE2-051 TP 500.0 END |
OP | AC | 101.94 % | 2442.12 | B | 2489.6 | 205.74 | ||
| Details for 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 314295 | 6BIRDNECK | 50/50 | 0.07 MW | 0.07 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 315605 | 6W1-029WIND | 50/50 | 2.17 MW | 2.17 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 315611 | 6Z1-036WIND | 50/50 | 6.32 MW | 6.32 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 901082 | W1-029 E | 50/50 | 14.58 MW | 14.58 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 916042 | Z1-036 E | 50/50 | 26.67 MW | 26.67 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 916192 | Z1-068 E | 50/50 | 0.48 MW | 0.48 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 941281 | AE2-122 C | 50/50 | 16.32 MW | 16.32 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 941282 | AE2-122 E | 50/50 | 65.86 MW | 65.86 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 941291 | AE2-123 C | 50/50 | 16.77 MW | 16.77 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 941292 | AE2-123 E | 50/50 | 65.41 MW | 65.41 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 941301 | AE2-124 C | 50/50 | 18.05 MW | 18.05 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 941302 | AE2-124 E | 50/50 | 79.22 MW | 79.22 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944581 | AF1-123 C | 50/50 | 121.69 MW | 121.69 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944582 | AF1-123 E | 50/50 | 278.63 MW | 278.63 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944591 | AF1-124 C | 50/50 | 121.69 MW | 121.69 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944592 | AF1-124 E | 50/50 | 278.63 MW | 278.63 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944601 | AF1-125 C | 50/50 | 121.69 MW | 121.69 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944602 | AF1-125 E | 50/50 | 278.63 MW | 278.63 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 964951 | AG1-359 C | 50/50 | 72.5 MW | 72.5 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 965741 | AG1-442 C | Adder | 2.86 MW | 2.43 MW |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 965751 | AG1-443 C | Adder | 2.86 MW | 2.43 MW |
| Details for 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 964111 | AG1-272 C | 50/50 | 0.35 MW | 0.35 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 964112 | AG1-272 E | 50/50 | 0.53 MW | 0.53 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 964121 | AG1-273 C | 50/50 | 0.35 MW | 0.35 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 964122 | AG1-273 E | 50/50 | 0.53 MW | 0.53 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 964131 | AG1-274 C | 50/50 | 0.35 MW | 0.35 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 964132 | AG1-274 E | 50/50 | 0.53 MW | 0.53 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 964791 | AG1-342 C | Adder | 0.19 MW | 0.16 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 964792 | AG1-342 E | Adder | 0.28 MW | 0.24 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 965191 | AG1-384 C | 50/50 | 0.35 MW | 0.35 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 965192 | AG1-384 E | 50/50 | 0.53 MW | 0.53 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 963311 | AG1-180 C | Adder | 0.84 MW | 0.71 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 963312 | AG1-180 E | Adder | 0.7 MW | 0.59 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 963361 | AG1-185 C | Adder | 4.83 MW | 4.1 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 963362 | AG1-185 E | Adder | 4.05 MW | 3.45 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 940661 | AE2-053 C | Adder | 1.19 MW | 1.01 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 941281 | AE2-122 C | Adder | 3.33 MW | 2.83 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 941282 | AE2-122 E | Adder | 13.42 MW | 11.41 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 941291 | AE2-123 C | Adder | 3.42 MW | 2.9 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 941292 | AE2-123 E | Adder | 13.33 MW | 11.33 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 941301 | AE2-124 C | Adder | 3.11 MW | 2.64 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 941302 | AE2-124 E | Adder | 13.64 MW | 11.59 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 944581 | AF1-123 C | Adder | 5.59 MW | 4.75 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 944582 | AF1-123 E | Adder | 12.8 MW | 10.88 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 944591 | AF1-124 C | Adder | 5.59 MW | 4.75 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 944592 | AF1-124 E | Adder | 12.8 MW | 10.88 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 944601 | AF1-125 C | Adder | 5.59 MW | 4.75 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 944602 | AF1-125 E | Adder | 12.8 MW | 10.88 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 944641 | AF1-129 C | Adder | 16.22 MW | 13.79 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 965771 | AG1-445 C | Adder | 1.37 MW | 1.17 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 965781 | AG1-446 C | Adder | 1.37 MW | 1.17 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 965831 | AG1-451 C | 50/50 | 3.23 MW | 3.23 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 316303 | AF2-085 | Adder | 1.32 MW | 1.12 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 946293 | AF1-293 BT | 50/50 | 26.71 MW | 26.71 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 958502 | AF2-144 E | Adder | 1.86 MW | 1.58 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 961063 | AF2-397 BT | 50/50 | 8.81 MW | 8.81 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A | 965583 | AG1-426 BT | 50/50 | 13.34 MW | 13.34 MW |
| Details for 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 314295 | 6BIRDNECK | 50/50 | 0.15 MW | 0.15 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 315605 | 6W1-029WIND | 50/50 | 1.9 MW | 1.9 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 315611 | 6Z1-036WIND | 50/50 | 5.33 MW | 5.33 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 901082 | W1-029 E | 50/50 | 12.77 MW | 12.77 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 916042 | Z1-036 E | 50/50 | 22.5 MW | 22.5 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 916192 | Z1-068 E | 50/50 | 1.08 MW | 1.08 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 961942 | AG1-037 E | Adder | 0.1 MW | 0.09 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 962332 | AG1-082 E | Adder | 0.42 MW | 0.36 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 962342 | AG1-083 E | Adder | 0.42 MW | 0.36 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 964801 | AG1-343 C | Adder | 0.29 MW | 0.25 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 964802 | AG1-343 E | Adder | 0.44 MW | 0.37 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 941281 | AE2-122 C | 50/50 | 35.05 MW | 35.05 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 941282 | AE2-122 E | 50/50 | 141.44 MW | 141.44 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 941291 | AE2-123 C | 50/50 | 36.02 MW | 36.02 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 941292 | AE2-123 E | 50/50 | 140.47 MW | 140.47 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 941301 | AE2-124 C | 50/50 | 36.1 MW | 36.1 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 941302 | AE2-124 E | 50/50 | 158.39 MW | 158.39 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944581 | AF1-123 C | 50/50 | 76.18 MW | 76.18 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944582 | AF1-123 E | 50/50 | 174.43 MW | 174.43 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944591 | AF1-124 C | 50/50 | 76.18 MW | 76.18 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944592 | AF1-124 E | 50/50 | 174.43 MW | 174.43 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944601 | AF1-125 C | 50/50 | 76.18 MW | 76.18 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944602 | AF1-125 E | 50/50 | 174.43 MW | 174.43 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 964951 | AG1-359 C | 50/50 | 45.39 MW | 45.39 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 965741 | AG1-442 C | Adder | 3.25 MW | 2.77 MW |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 965751 | AG1-443 C | Adder | 3.25 MW | 2.77 MW |
| Details for 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 315083 | 1SPRUNCA | 50/50 | 3.42 MW | 3.42 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 315084 | 1SPRUNCB | 50/50 | 3.42 MW | 3.42 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 315611 | 6Z1-036WIND | Adder | 3.17 MW | 2.69 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 916042 | Z1-036 E | Adder | 13.37 MW | 11.37 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 941032 | AE2-094 E | Adder | 17.91 MW | 15.22 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 944012 | AF1-069 E | Adder | 5.85 MW | 4.97 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 961942 | AG1-037 E | Adder | 0.15 MW | 0.13 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 962332 | AG1-082 E | Adder | 0.61 MW | 0.52 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 962342 | AG1-083 E | Adder | 0.61 MW | 0.52 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 962531 | AG1-102 C | Adder | 0.77 MW | 0.65 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 962532 | AG1-102 E | Adder | 1.6 MW | 1.36 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 963611 | AG1-210 C | Adder | 0.46 MW | 0.39 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 963612 | AG1-210 E | Adder | 0.69 MW | 0.58 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 964801 | AG1-343 C | Adder | 0.46 MW | 0.39 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 964802 | AG1-343 E | Adder | 0.7 MW | 0.59 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 966661 | AG1-536 C | Adder | 3.79 MW | 3.22 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 966662 | AG1-536 E | Adder | 5.09 MW | 4.33 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 966872 | AG1-558 E | 50/50 | 2.4 MW | 2.4 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 966882 | AG1-559 E | Adder | 1.11 MW | 0.94 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 963351 | AG1-184 C | Adder | 16.2 MW | 13.77 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 963352 | AG1-184 E | Adder | 11.56 MW | 9.83 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 961611 | AG1-000B C | Adder | 3.77 MW | 3.21 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 316427 | AG1-213 C | Adder | 0.37 MW | 0.31 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 940541 | AE2-040 C | Adder | 1.62 MW | 1.37 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 940551 | AE2-041 C | 50/50 | 5.27 MW | 5.27 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 940651 | AE2-052 C | 50/50 | 2.52 MW | 2.52 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 941281 | AE2-122 C | Adder | 13.86 MW | 11.78 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 941282 | AE2-122 E | Adder | 55.93 MW | 47.54 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 941291 | AE2-123 C | Adder | 14.24 MW | 12.11 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 941292 | AE2-123 E | Adder | 55.55 MW | 47.22 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 941301 | AE2-124 C | Adder | 12.94 MW | 11.0 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 941302 | AE2-124 E | Adder | 56.79 MW | 48.27 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 941591 | AE2-156 C | Adder | 10.99 MW | 9.34 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 942551 | AE2-270 C | 50/50 | 7.92 MW | 7.92 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 942552 | AE2-270 E | 50/50 | 11.88 MW | 11.88 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 943471 | AF1-018 C | 50/50 | 5.27 MW | 5.27 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 944581 | AF1-123 C | Adder | 23.14 MW | 19.67 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 944582 | AF1-123 E | Adder | 52.98 MW | 45.04 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 944591 | AF1-124 C | Adder | 23.14 MW | 19.67 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 944592 | AF1-124 E | Adder | 52.98 MW | 45.04 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 944601 | AF1-125 C | Adder | 23.14 MW | 19.67 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 944602 | AF1-125 E | Adder | 52.98 MW | 45.04 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 944631 | AF1-128 C | 50/50 | 33.01 MW | 33.01 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 944641 | AF1-129 C | 50/50 | 84.31 MW | 84.31 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 945362 | AF1-201 E | Adder | 2.48 MW | 2.11 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 946011 | AF1-266 C | Adder | 7.58 MW | 6.44 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 961612 | AG1-000B E | 50/50 | 5.66 MW | 5.66 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 961711 | AG1-011 C | 50/50 | 21.13 MW | 21.13 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 964951 | AG1-359 C | Adder | 13.82 MW | 11.75 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 965001 | AG1-364 C | Adder | 4.4 MW | 3.74 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 965002 | AG1-364 E | Adder | 6.59 MW | 5.61 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 965741 | AG1-442 C | Adder | 3.22 MW | 2.74 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 965751 | AG1-443 C | Adder | 3.22 MW | 2.74 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 965811 | AG1-449 C | Adder | 5.85 MW | 4.97 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 966871 | AG1-558 C | 50/50 | 0.26 MW | 0.26 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 966881 | AG1-559 C | Adder | 0.12 MW | 0.1 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 316303 | AF2-085 | Adder | 2.75 MW | 2.34 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 963622 | AG1-213 E | Adder | 0.43 MW | 0.37 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-L | 963623 | AG1-213 BAT | Adder | 0.65 MW | 0.55 MW |
| Details for 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 2 transformer l/o DVP_P1-3: 4ALTVSTA-TX#3_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 2 transformer l/o DVP_P1-3: 4ALTVSTA-TX#3_SRT-A | 964791 | AG1-342 C | Adder | 0.31 MW | 0.27 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 2 transformer l/o DVP_P1-3: 4ALTVSTA-TX#3_SRT-A | 964792 | AG1-342 E | Adder | 0.47 MW | 0.4 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 2 transformer l/o DVP_P1-3: 4ALTVSTA-TX#3_SRT-A | 966691 | AG1-539 C | 50/50 | 13.26 MW | 13.26 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 2 transformer l/o DVP_P1-3: 4ALTVSTA-TX#3_SRT-A | 966692 | AG1-539 E | 50/50 | 17.82 MW | 17.82 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 2 transformer l/o DVP_P1-3: 4ALTVSTA-TX#3_SRT-A | 941281 | AE2-122 C | Adder | 1.59 MW | 1.35 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 2 transformer l/o DVP_P1-3: 4ALTVSTA-TX#3_SRT-A | 941282 | AE2-122 E | Adder | 6.43 MW | 5.46 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 2 transformer l/o DVP_P1-3: 4ALTVSTA-TX#3_SRT-A | 941291 | AE2-123 C | Adder | 1.64 MW | 1.39 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 2 transformer l/o DVP_P1-3: 4ALTVSTA-TX#3_SRT-A | 941292 | AE2-123 E | Adder | 6.38 MW | 5.43 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 2 transformer l/o DVP_P1-3: 4ALTVSTA-TX#3_SRT-A | 941301 | AE2-124 C | Adder | 1.49 MW | 1.27 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 2 transformer l/o DVP_P1-3: 4ALTVSTA-TX#3_SRT-A | 941302 | AE2-124 E | Adder | 6.54 MW | 5.56 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 2 transformer l/o DVP_P1-3: 4ALTVSTA-TX#3_SRT-A | 944581 | AF1-123 C | Adder | 2.69 MW | 2.29 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 2 transformer l/o DVP_P1-3: 4ALTVSTA-TX#3_SRT-A | 944582 | AF1-123 E | Adder | 6.15 MW | 5.23 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 2 transformer l/o DVP_P1-3: 4ALTVSTA-TX#3_SRT-A | 944591 | AF1-124 C | Adder | 2.69 MW | 2.29 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 2 transformer l/o DVP_P1-3: 4ALTVSTA-TX#3_SRT-A | 944592 | AF1-124 E | Adder | 6.15 MW | 5.23 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 2 transformer l/o DVP_P1-3: 4ALTVSTA-TX#3_SRT-A | 944601 | AF1-125 C | Adder | 2.69 MW | 2.29 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 2 transformer l/o DVP_P1-3: 4ALTVSTA-TX#3_SRT-A | 944602 | AF1-125 E | Adder | 6.15 MW | 5.23 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 2 transformer l/o DVP_P1-3: 4ALTVSTA-TX#3_SRT-A | 961123 | AF2-403 BT | 50/50 | 5.44 MW | 5.44 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 2 transformer l/o DVP_P1-3: 4ALTVSTA-TX#3_SRT-A | 961133 | AF2-404 BT | 50/50 | 5.44 MW | 5.44 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 2 transformer l/o DVP_P1-3: 4ALTVSTA-TX#3_SRT-A | 966763 | AG1-547 BT | 50/50 | 3.42 MW | 3.42 MW |
| Details for 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 1 transformer l/o DVP_P1-3: 4ALTVSTA-TX#4_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 1 transformer l/o DVP_P1-3: 4ALTVSTA-TX#4_SRT-A | 964791 | AG1-342 C | Adder | 0.29 MW | 0.25 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 1 transformer l/o DVP_P1-3: 4ALTVSTA-TX#4_SRT-A | 964792 | AG1-342 E | Adder | 0.44 MW | 0.37 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 1 transformer l/o DVP_P1-3: 4ALTVSTA-TX#4_SRT-A | 966691 | AG1-539 C | 50/50 | 12.48 MW | 12.48 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 1 transformer l/o DVP_P1-3: 4ALTVSTA-TX#4_SRT-A | 966692 | AG1-539 E | 50/50 | 16.77 MW | 16.77 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 1 transformer l/o DVP_P1-3: 4ALTVSTA-TX#4_SRT-A | 941281 | AE2-122 C | Adder | 1.5 MW | 1.27 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 1 transformer l/o DVP_P1-3: 4ALTVSTA-TX#4_SRT-A | 941282 | AE2-122 E | Adder | 6.05 MW | 5.14 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 1 transformer l/o DVP_P1-3: 4ALTVSTA-TX#4_SRT-A | 941291 | AE2-123 C | Adder | 1.54 MW | 1.31 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 1 transformer l/o DVP_P1-3: 4ALTVSTA-TX#4_SRT-A | 941292 | AE2-123 E | Adder | 6.01 MW | 5.11 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 1 transformer l/o DVP_P1-3: 4ALTVSTA-TX#4_SRT-A | 941301 | AE2-124 C | Adder | 1.4 MW | 1.19 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 1 transformer l/o DVP_P1-3: 4ALTVSTA-TX#4_SRT-A | 941302 | AE2-124 E | Adder | 6.15 MW | 5.23 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 1 transformer l/o DVP_P1-3: 4ALTVSTA-TX#4_SRT-A | 944581 | AF1-123 C | Adder | 2.53 MW | 2.15 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 1 transformer l/o DVP_P1-3: 4ALTVSTA-TX#4_SRT-A | 944582 | AF1-123 E | Adder | 5.79 MW | 4.92 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 1 transformer l/o DVP_P1-3: 4ALTVSTA-TX#4_SRT-A | 944591 | AF1-124 C | Adder | 2.53 MW | 2.15 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 1 transformer l/o DVP_P1-3: 4ALTVSTA-TX#4_SRT-A | 944592 | AF1-124 E | Adder | 5.79 MW | 4.92 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 1 transformer l/o DVP_P1-3: 4ALTVSTA-TX#4_SRT-A | 944601 | AF1-125 C | Adder | 2.53 MW | 2.15 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 1 transformer l/o DVP_P1-3: 4ALTVSTA-TX#4_SRT-A | 944602 | AF1-125 E | Adder | 5.79 MW | 4.92 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 1 transformer l/o DVP_P1-3: 4ALTVSTA-TX#4_SRT-A | 961123 | AF2-403 BT | 50/50 | 5.12 MW | 5.12 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 1 transformer l/o DVP_P1-3: 4ALTVSTA-TX#4_SRT-A | 961133 | AF2-404 BT | 50/50 | 5.12 MW | 5.12 MW |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 1 transformer l/o DVP_P1-3: 4ALTVSTA-TX#4_SRT-A | 966763 | AG1-547 BT | 50/50 | 3.22 MW | 3.22 MW |
| Details for 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 315605 | 6W1-029WIND | 50/50 | 1.18 MW | 1.18 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 315611 | 6Z1-036WIND | 50/50 | 3.41 MW | 3.41 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 901082 | W1-029 E | 50/50 | 7.94 MW | 7.94 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 916042 | Z1-036 E | 50/50 | 14.39 MW | 14.39 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944581 | AF1-123 C | 50/50 | 61.73 MW | 61.73 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944582 | AF1-123 E | 50/50 | 141.34 MW | 141.34 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944591 | AF1-124 C | 50/50 | 61.73 MW | 61.73 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944592 | AF1-124 E | 50/50 | 141.34 MW | 141.34 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944601 | AF1-125 C | 50/50 | 61.73 MW | 61.73 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944602 | AF1-125 E | 50/50 | 141.34 MW | 141.34 MW |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 964951 | AG1-359 C | 50/50 | 36.78 MW | 36.78 MW |
| Details for 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 315605 | 6W1-029WIND | 50/50 | 1.18 MW | 1.18 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 315611 | 6Z1-036WIND | 50/50 | 3.41 MW | 3.41 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 901082 | W1-029 E | 50/50 | 7.94 MW | 7.94 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 916042 | Z1-036 E | 50/50 | 14.39 MW | 14.39 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944581 | AF1-123 C | 50/50 | 61.73 MW | 61.73 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944582 | AF1-123 E | 50/50 | 141.34 MW | 141.34 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944591 | AF1-124 C | 50/50 | 61.73 MW | 61.73 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944592 | AF1-124 E | 50/50 | 141.34 MW | 141.34 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944601 | AF1-125 C | 50/50 | 61.73 MW | 61.73 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 944602 | AF1-125 E | 50/50 | 141.34 MW | 141.34 MW |
| 6POCATY-6LANDSTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 588_SRT-A | 964951 | AG1-359 C | 50/50 | 36.78 MW | 36.78 MW |
| Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 314295 | 6BIRDNECK | 50/50 | 0.17 MW | 0.17 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 315131 | 1EDGECMA | Adder | 7.41 MW | 6.3 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 315605 | 6W1-029WIND | 50/50 | 2.82 MW | 2.82 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 315611 | 6Z1-036WIND | 50/50 | 7.89 MW | 7.89 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 901082 | W1-029 E | 50/50 | 18.93 MW | 18.93 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 916042 | Z1-036 E | 50/50 | 33.27 MW | 33.27 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 916192 | Z1-068 E | 50/50 | 1.18 MW | 1.18 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 941032 | AE2-094 E | 50/50 | 47.06 MW | 47.06 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 944012 | AF1-069 E | 50/50 | 15.38 MW | 15.38 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 961942 | AG1-037 E | Adder | 0.34 MW | 0.29 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 962332 | AG1-082 E | Adder | 1.39 MW | 1.18 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 962342 | AG1-083 E | 50/50 | 1.39 MW | 1.39 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 962531 | AG1-102 C | Adder | 0.89 MW | 0.76 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 962532 | AG1-102 E | Adder | 1.86 MW | 1.58 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 963041 | AG1-153 C | 50/50 | 6.49 MW | 6.49 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 963042 | AG1-153 E | 50/50 | 9.73 MW | 9.73 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 963102 | AG1-159 E | Adder | 3.57 MW | 3.03 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 963111 | AG1-160 C | 50/50 | 6.59 MW | 6.59 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 963112 | AG1-160 E | 50/50 | 9.88 MW | 9.88 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 964801 | AG1-343 C | 50/50 | 1.05 MW | 1.05 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 964802 | AG1-343 E | 50/50 | 1.57 MW | 1.57 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 963311 | AG1-180 C | Adder | 2.63 MW | 2.23 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 963312 | AG1-180 E | Adder | 2.2 MW | 1.87 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 963351 | AG1-184 C | 50/50 | 43.17 MW | 43.17 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 963352 | AG1-184 E | 50/50 | 30.81 MW | 30.81 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 961611 | AG1-000B C | Adder | 5.41 MW | 4.6 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 940541 | AE2-040 C | Adder | 2.76 MW | 2.35 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 940651 | AE2-052 C | Adder | 2.81 MW | 2.39 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 940661 | AE2-053 C | Adder | 2.99 MW | 2.54 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 941281 | AE2-122 C | 50/50 | 35.62 MW | 35.62 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 941282 | AE2-122 E | 50/50 | 143.76 MW | 143.76 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 941291 | AE2-123 C | 50/50 | 36.61 MW | 36.61 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 941292 | AE2-123 E | 50/50 | 142.77 MW | 142.77 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 941301 | AE2-124 C | 50/50 | 33.33 MW | 33.33 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 941302 | AE2-124 E | 50/50 | 146.23 MW | 146.23 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 941591 | AE2-156 C | 50/50 | 27.84 MW | 27.84 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 942551 | AE2-270 C | Adder | 1.11 MW | 0.95 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 942552 | AE2-270 E | Adder | 1.67 MW | 1.42 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 944141 | AF1-082 C | Adder | 2.96 MW | 2.52 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 944581 | AF1-123 C | 50/50 | 62.54 MW | 62.54 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 944582 | AF1-123 E | 50/50 | 143.2 MW | 143.2 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 944591 | AF1-124 C | 50/50 | 62.54 MW | 62.54 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 944592 | AF1-124 E | 50/50 | 143.2 MW | 143.2 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 944601 | AF1-125 C | 50/50 | 62.54 MW | 62.54 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 944602 | AF1-125 E | 50/50 | 143.2 MW | 143.2 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 945362 | AF1-201 E | Adder | 3.43 MW | 2.92 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 946011 | AF1-266 C | Adder | 13.13 MW | 11.16 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 961602 | AG1-000A E | Adder | 5.76 MW | 4.9 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 961612 | AG1-000B E | Adder | 8.12 MW | 6.9 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 964951 | AG1-359 C | 50/50 | 36.07 MW | 36.07 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 965001 | AG1-364 C | 50/50 | 11.13 MW | 11.13 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 965002 | AG1-364 E | 50/50 | 16.69 MW | 16.69 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 965741 | AG1-442 C | 50/50 | 7.65 MW | 7.65 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 965751 | AG1-443 C | 50/50 | 7.65 MW | 7.65 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 965761 | AG1-444 C | Adder | 13.98 MW | 11.88 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 965771 | AG1-445 C | Adder | 4.08 MW | 3.47 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 965781 | AG1-446 C | Adder | 4.08 MW | 3.47 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L-1 | 965811 | AG1-449 C | 50/50 | 27.29 MW | 27.29 MW |
Short Circuit Analysis
Short Circuit analysis is not performed as part of the Phase I System Impact Study. Short Circuit analysis will commence in the Phase II System Impact Study.
Stability Analysis
Stability analysis is not performed as part of the Phase I System Impact Study. Stability analysis will commence in the Phase II System Impact Study.
Reactive Power Analysis
Reactive Power analysis is not performed as part of the Phase I System Impact Study. Reactive Power analysis will commence in the Phase II System Impact Study.
Steady-State Voltage Analysis
Steady State Voltage analysis is not performed as part of the Phase I System Impact Study. Steady State Voltage analysis will commence in the Phase II System Impact Study.
New Service Request Dependencies
The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.
| New Service Requests Dependencies | ||
|---|---|---|
| Project ID | Project Name | Status |
| AA1-063A | Carolina–Seaboard 115kV | In Service |
| AA1-065 | Earleys 230kV | In Service |
| AA1-067 | Everetts 34.5kV | In Service |
| AA1-139 | Hickory-Shawboro 230kV | In Service |
| AA1-145 | Four Rivers 230kV | In Service |
| AA2-053 | Carolina-Jackson 115kV | In Service |
| AA2-057 | Hornertown-Whitakers 115kV | In Service |
| AA2-088 | Boykins-Handsome 115kV | In Service |
| AA2-178 | Mackeys 230kV | In Service |
| AB1-027 | Old Church 34.5 KV | In Service |
| AB1-132 | Thelma 230kV | Partially in Service - Under Construction |
| AB1-173 | Brink-Trego 115kV | In Service |
| AB2-022 | Elizabeth City 34.5kV | In Service |
| AB2-024 | Correctional 34.5kV | In Service |
| AB2-025 | Sapony 34.5kV | In Service |
| AB2-026 | Powhatan 34.5kV | In Service |
| AB2-029 | Remington 34.5kV | In Service |
| AB2-040 | Brink 115kV | Under Construction |
| AB2-043 | Chase City 115kV | In Service |
| AB2-045 | Buckingham 34.5kV | In Service |
| AB2-060 | Chase City-Lunenburg 115kV | In Service |
| AB2-077 | Buggs Island-Chase City 115kV | Partially in Service - Under Construction |
| AB2-078 | Buggs Island-Chase City 115kV | Partially in Service - Under Construction |
| AB2-079 | Buggs Island-Chase City 115kV | Partially in Service - Under Construction |
| AB2-099 | Ahoskie 34.5kV | In Service |
| AB2-100 | Clubhouse-Lakeview 230kV | In Service |
| AB2-134 | Hopewell-Surry 230kV | In Service |
| AB2-158 | Louisa-South Anna 230kV | In Service |
| AB2-160 | Reams 115kV | Engineering & Procurement |
| AB2-161 | Waverly #2 DP 115kV | In Service |
| AB2-169 | Pantago-Five Points 115kV | In Service |
| AB2-174 | Emporia-Trego 115kV | In Service |
| AB2-190 | Hopewell-Surry 230kV | In Service |
| AC1-027 | Pendleton 34.5kV | In Service |
| AC1-034 | Heartsease DP - Mayo Dunbar 115kV | Engineering & Procurement |
| AC1-036 | Twittys Creek 34.5kV | In Service |
| AC1-043 | Mountain Run-Mitchell 115 kV | Engineering & Procurement |
| AC1-054 | Kerr Dam–Eatons Ferry 115 kV | In Service |
| AC1-065 | Harmony Village-Shackleford 115kV | Under Construction |
| AC1-076 | Locust Grove-Paytes 115kV | Under Construction |
| AC1-086 | Thelma 230kV | Engineering & Procurement |
| AC1-098 | Dawson-South Justice 115kV | Engineering & Procurement |
| AC1-099 | Dawson-South Justice 115kV | Engineering & Procurement |
| AC1-105 | Halifax-Mt. Laurel 115kV | In Service |
| AC1-112 | Old Church 34.5kV | In Service |
| AC1-118 | Westmoreland 34.5kV | In Service |
| AC1-120 | Mitchell-Mountain Run 115kV | Suspended |
| AC1-121 | Mitchell-Mountain Run 115kV | Suspended |
| AC1-143 | Brandy-Remington 115kV | Suspended |
| AC1-147 | Grassfield 34.5kV | In Service |
| AC1-158 | Spotsylvania 500kV | In Service |
| AC1-161 | Septa 500kV | Partially in Service - Under Construction |
| AC1-164 | Chickahominy 230kV | Partially in Service - Under Construction |
| AC1-189 | Chinquapin-Everetts 230kV | Suspended |
| AC1-191 | Elmont 115kV | Suspended |
| AC1-208 | Cox-Whitakers 115kV | Suspended |
| AC1-216 | Hopewell-Surry 230kV | In Service |
| AC1-221 | Halifax-Person 230kV | Under Construction |
| AC1-222 | Crystal Hill-Halifax 115kV | In Service |
| AC2-012 | Grassfield-Great Bridge 115kV | In Service |
| AC2-079 | Ivor-Oak Ridge 115kV | Suspended |
| AC2-084 | Dawson-South Justice 115kV | Engineering & Procurement |
| AC2-100 | Halifax-Person 230kV | Partially in Service - Under Construction |
| AC2-137 | Elko 34.5kV | In Service |
| AC2-138 | Northern Neck 34.5kV | In Service |
| AC2-141 | Septa 500kV | Engineering & Procurement |
| AC2-165 | Bremo-Powhatan 230kV | Engineering & Procurement |
| AD1-022 | Cashie-Trowbridge 230 kV | Engineering & Procurement |
| AD1-025 | Hopewell-Surry 230 kV | Engineering & Procurement |
| AD1-033 | Fentress-Landstown 230 kV | In Service |
| AD1-041 | Harmony Village-Shackleford 115 kV | Under Construction |
| AD1-056 | Hornertown-Hathaway 230 kV | Engineering & Procurement |
| AD1-057 | Hornertown-Hathaway 230 kV | Engineering & Procurement |
| AD1-063 | Harmony Village 34.5 kV | In Service |
| AD1-074 | Trowbridge 230 kV | Engineering & Procurement |
| AD1-075 | Trowbridge 230 kV | Engineering & Procurement |
| AD1-076 | Trowbridge 230 kV | Engineering & Procurement |
| AD1-082 | Bakers Pond-Ivor 115kV | In Service |
| AD1-087 | Clover-Sedge Hill 230 kV | In Service |
| AD1-088 | Briery-Clover 230 kV | Engineering & Procurement |
| AD1-105 | Kings Dominion DP 115 kV | Engineering & Procurement |
| AD1-115 | Mountain Run-Mitchell 115 kV | Engineering & Procurement |
| AD1-144 | Kings Fork 34.5 kV | In Service |
| AD1-151 | Hopewell-Surry 230 kV | Suspended |
| AD1-152 | Clover-Sedge Hill 230 kV | In Service |
| AD2-022 | East Danville - Roxborough 230 kV | Engineering & Procurement |
| AD2-023 | East Danville - Roxborough 230 kV | Engineering & Procurement |
| AD2-030 | Wan 34.5 kV | In Service |
| AD2-033 | Chase City-Lunenburg 115 kV | Suspended |
| AD2-073 | Sanders DP 230 kV | In Service |
| AD2-074 | Garner DP-Lancaster 115 kV | Suspended |
| AD2-085 | Myrtle-Windsor DP 115kV | Suspended |
| AD2-202 | Clover-Sedge Hill 230kV | In Service |
| AE1-013 | Suitland Road 13 kV | Withdrawn |
| AE1-044 | Morrisville 230 kV | Suspended |
| AE1-056 | Red House-South Creek 115 kV | Suspended |
| AE1-072 | Shawboro-Sligo 230 kV | Engineering & Procurement |
| AE1-074 | Winterpock 34.5 kV | Suspended |
| AE1-075 | Powhatan 34.5 kV | Under Construction |
| AE1-103 | Holland-Union Camp 115 kV | Suspended |
| AE1-108 | Bremo-Scottsville 138 kV | Engineering & Procurement |
| AE1-148 | Kerr Dam-Ridge Rd 115 kV | Active |
| AE1-149 | Disputanta-Poe 115 kV | Engineering & Procurement |
| AE1-153 | Remington-Gordonsville 230 kV | Suspended |
| AE1-155 | Garner-Northern Neck 115 kV | Partially in Service - Under Construction |
| AE1-157 | Ladysmith CT-St. Johns 230 kV | Suspended |
| AE1-162 | Smithfield 34.5 kV | In Service |
| AE1-173 | Carson-Suffolk 500 kV | Active |
| AE1-175 | Light Foot 34.5 kV | In Service |
| AE1-190 | Harmony Village-Shackleford 115 kV | Engineering & Procurement |
| AE1-191 | Harmony Village-Shackleford 115 kV | Under Construction |
| AE2-027 | Harrowgate-Locks 115kV | Engineering & Procurement |
| AE2-033 | Clubhouse-Sapony 230 kV | Suspended |
| AE2-034 | Mackeys 230 kV | Partially in Service - Under Construction |
| AE2-040 | Sapony 34.5 kV | Suspended |
| AE2-041 | Harmony Village 230 kV | Engineering & Procurement |
| AE2-044 | Anaconda-Dunbar 115 kV | Withdrawn |
| AE2-051 | Carson-Septa 500 kV | Active |
| AE2-052 | Disputanta-Poe 115 kV | Active |
| AE2-053 | Kerr Dam-Ridge Road 115 kV | Active |
| AE2-092 | Kidds Store-Sherwood 115 kV | Engineering & Procurement |
| AE2-094 | Carson-Rogers Road 500 kV | Active |
| AE2-104 | Suffolk 115 kV | Engineering & Procurement |
| AE2-122 | Birdneck-Landstown 230 kV | Active |
| AE2-123 | Birdneck-Landstown 230 kV | Active |
| AE2-124 | Landstown 230 kV | Active |
| AE2-147 | Swamp 230 kV | Active |
| AE2-156 | Yadkin 115 kV | Active |
| AE2-182 | Briery-Clover 230 kV | Engineering & Procurement |
| AE2-212 | Harrowgate 34 kV | Engineering & Procurement |
| AE2-227 | Iron Bridge 34 kV | Engineering & Procurement |
| AE2-228 | Tyler 34 kv | Engineering & Procurement |
| AE2-231 | St. Johns 115 kV | Active |
| AE2-247 | Myrtle-Windsor 115 kV | Suspended |
| AE2-250 | Purdy Sw.-Reams 115 kV | Active |
| AE2-253 | Hickory-Moyock 230 kV | In Service |
| AE2-259 | Curdsville-Willis Mtn 115 kV | Active |
| AE2-270 | Hopewell-Surry 230 kV | Active |
| AE2-313 | Carson-Rawlings 500 kV | Active |
| AE2-346 | Ahoskie 34.5 kV | In Service |
| AF1-017 | Myrtle-Windsor 115 kV | Suspended |
| AF1-018 | Harmony Village 230 kV | Engineering & Procurement |
| AF1-028 | Endless Caverns 115 kV | Engineering & Procurement |
| AF1-032 | Suffolk 34.5 kV | In Service |
| AF1-042 | Garner DP-Lancaster 115 kV | Suspended |
| AF1-058 | Welco 34.5 kV | In Service |
| AF1-069 | Carson-Rogers Rd 500 kV | Active |
| AF1-082 | Heartsease-Mayo Dunbar DP | Withdrawn |
| AF1-114 | Oak Grove-Dahlgren 230 kV | Suspended |
| AF1-124 | Oceana 230 kV | Active |
| AF1-125 | Oceana 230 kV | Active |
| AF1-128 | Chesterfield 230 kV | Active |
| AF1-129 | Chesterfield 230 kV | Active |
| AF1-147 | Poland Rd-Runway DP 230kV | Engineering & Procurement |
| AF1-152 | Swamp 230 kV | Active |
| AF1-201 | Hayes-White Marsh 115 kV | Active |
| AF1-246 | Clover-Rawlings 500 kV | Withdrawn |
| AF1-266 | Clubhouse-Sapony 230 kV | Active |
| AF1-291 | Tyler 34.5 kV | Engineering & Procurement |
| AF1-292 | Fields 34.5kV | Active |
| AF1-293 | Kidds Store-Fort Union 115 kV | Active |
| AF1-294 | Jetersville-Ponton 115 kV | Active |
| AF1-301 | Louisa-South Anna 230 kV | Active |
| AF1-323 | Scottsville-Colleen 138 kV | Active |
| AF2-013 | Arnold's Corner-Dahlgren 230 kV | Active |
| AF2-035 | St. Johns 115 kV | Active |
| AF2-037 | Louisa-North Anna 230 kV | Active |
| AF2-042 | Clover-Rawlings 500 kV | Active |
| AF2-043 | Suffolk 34.5 kV | In Service |
| AF2-046 | Tunis-Mapleton 115 kV | Active |
| AF2-047 | Creswell-Riders Creek 115 kV | Active |
| AF2-054 | Wan 34.5 kV | Active |
| AF2-063 | Louisa-North Anna 230 kV | Active |
| AF2-065 | Surry-Hopewell 230 kV | Active |
| AF2-077 | White Marsh 34.5 kV | Active |
| AF2-080 | Chinquapin-Everetts 230 kV | Active |
| AF2-081 | Moyock 230 kV | Active |
| AF2-085 | Midlothian 34.5 kV | In Service |
| AF2-091 | Oak Grove-Dahlgren 230 kV | Active |
| AF2-110 | Suffolk 115 kV | Engineering & Procurement |
| AF2-115 | Jetersville-Ponton 115 kV | Active |
| AF2-119 | Bristers-Sowego 115 kV | Active |
| AF2-120 | Garner-Northern Neck 115 kV | Active |
| AF2-144 | Powhatan 34.5 kV | In Service |
| AF2-171 | Madisonville 115 kV | Active |
| AF2-222 | Madisonville DP-Twitty's Creek 115 kV | Active |
| AF2-297 | Sedge Hill 115 kV | Active |
| AF2-299 | Fields 34.5 kV | Active |
| AF2-300 | St. Johns 115 kV | Active |
| AF2-302 | Scottsville-Colleen 138 kV | Active |
| AF2-324 | Edgecombe 230 kV | Active |
| AF2-397 | Fork Union-Mt. Eagle 230 kV | Active |
| AF2-403 | Shockoe DP-Chatham 69 kV | Active |
| AF2-404 | Gladys DP-Stonemill 69 kV | Active |
| AG1-007 | Tar River 12.5 kV | Active |
| AG1-008 | Tunis-Mapleton 115 kV | Active |
| AG1-011 | Colonial Trail 230 kV | Active |
| AG1-019 | Arnold's Corner-Dahlgren 230 kV | Active |
| AG1-021 | Jetersville-Ponton 115 kV | Active |
| AG1-022 | Scottsville-Colleen 138 kV | Active |
| AG1-030 | Victoria DP-Martin DP 115 kV | Active |
| AG1-037 | Ahoskie 34.5 kV | Active |
| AG1-038 | Garner DP-Lancaster 115 kV | Active |
| AG1-075 | Purdy-Sapony 115 kV | Active |
| AG1-082 | Ahoskie 34.5 kV | Active |
| AG1-083 | Ahoskie 34.5 kV | Active |
| AG1-098 | Briery-Clover 230 kV | Active |
| AG1-102 | White Marsh 34.5 kV | Active |
| AG1-105 | Mount Laurel-Barnes Junction 115 kV | Active |
| AG1-106 | Thelma 230 kV | Active |
| AG1-133 | North Anna-Ladysmith 500 kV | Active |
| AG1-134 | Kings Dominion DP 115 kV | Active |
| AG1-135 | Garner-Lancaster 115 kV | Active |
| AG1-145 | Lightfoot 34.5 kV | In Service |
| AG1-146 | Garner DP-Lancaster 115 kV | Active |
| AG1-147 | Garner DP-Lancaster 115 kV | Active |
| AG1-151 | Endless Caverns 115 kV | Active |
| AG1-152 | Remington CT 230 kV | Active |
| AG1-153 | Heritage 500 kV | Active |
| AG1-154 | Ladysmith CT 230 kV | Active |
| AG1-159 | Cox-Whitakers 115 kV | Withdrawn |
| AG1-160 | Rogers Road 500 kV | Active |
| AG1-166 | Lone Pine 115 kV | Active |
| AG1-167 | Lone Pine 115 kV | Active |
| AG1-168 | Lone Pine 115 kV | Active |
| AG1-169 | Lone Pine 115 kV | Active |
| AG1-170 | Lone Pine 115 kV | Active |
| AG1-171 | Hopewell-Surry 230kV | Active |
| AG1-172 | Hopewell-Surry 230 kV | Active |
| AG1-173 | Hopewell-Surry 230 kV | Active |
| AG1-174 | Hopewell-Surry 230 kV | Active |
| AG1-178 | Carson-Suffolk 500 kV | Active |
| AG1-179 | Brunswick-Gasburg 69 kV | Active |
| AG1-180 | Brunswick-Gasburg 69 kV | Active |
| AG1-181 | Pamplin-Chase City 115 kV | Active |
| AG1-184 | Carson-Suffolk 500 kV | Active |
| AG1-185 | Pamplin-Chase City 115 kV | Active |
| AG1-195 | Valley 230 kV | Active |
| AG1-196 | Grottoes 115 kV | Active |
| AG1-210 | Northern Neck 34.5 kV | Active |
| AG1-213 | St Johns 13.2 kV | Engineering & Procurement |
| AG1-272 | Twitty's Creek 115 kV | Active |
| AG1-273 | Twitty's Creek 115 kV | Active |
| AG1-274 | Twitty's Creek 115 kV | Active |
| AG1-282 | Dunnsville 34.5 kV | Active |
| AG1-284 | Fork Union 115 kV | Active |
| AG1-285 | Chase City-Central 115 kV | Active |
| AG1-288 | Lake of the Woods DP-Wilderness DP 115 kV | Active |
| AG1-289 | Lake of the Woods DP-Wilderness DP 115 kV | Active |
| AG1-305 | Louisa-North Anna 230 kV | Active |
| AG1-342 | Dryburg 115 kV | Active |
| AG1-343 | Boykins-Murphy 115 kV | Active |
| AG1-359 | Fentress 230 kV | Active |
| AG1-364 | Deep Creek 115 kV | Active |
| AG1-384 | Twitty's Creek 115 kV | Active |
| AG1-393 | Fort Pickett DP 34.5 kV | Active |
| AG1-394 | Boykins 34.5 kV | Active |
| AG1-412 | Ladysmith CT-Mine Road 230 kV | Active |
| AG1-422 | Lexington-Dooms 230 kV | Active |
| AG1-426 | Bremo-Scottsville 138 kV | Active |
| AG1-427 | Chase City-Drakes Branch 115 kV | Active |
| AG1-428 | Danieltown DP–Brunswick 69 kV | Active |
| AG1-432 | Curdsville DP-Willis Mt. 115 kV | Active |
| AG1-437 | Cashie-Earleys 230 kV | Active |
| AG1-438 | Cashie-Earleys 230 kV | Active |
| AG1-439 | Chinquapin 230 kV | Active |
| AG1-440 | Palmer Springs 115 kV | Active |
| AG1-441 | Palmer Springs 115 kV | Active |
| AG1-442 | Cashie-Earleys 230 kV | Active |
| AG1-443 | Cashie-Earleys 230 kV | Active |
| AG1-444 | Chinquapin 230 kV | Active |
| AG1-445 | Palmer Springs 115 kV | Active |
| AG1-446 | Palmer Springs 115 kV | Active |
| AG1-449 | Rawlings-Carson 500 kV | Active |
| AG1-451 | Curdsville DP-Willis Mt. 115 kV | Active |
| AG1-469 | Gordonsville 34.5 kV | Active |
| AG1-494 | Boxwood-Riverville 138 kV | Active |
| AG1-502 | Oak Green 115 kV | Active |
| AG1-503 | Oak Green 115 kV | Active |
| AG1-505 | Rawlings-Clover 500 kV | Active |
| AG1-506 | Rawlings-Clover 500 kV | Active |
| AG1-531 | Poolesville-Winchester 230 kV | Active |
| AG1-532 | Fields 34.5 kV | Active |
| AG1-536 | Garner-Northern Neck 115 kV | Active |
| AG1-537 | Barterbrook-Stuarts Draft 115 kV | Active |
| AG1-538 | Remington-Gordonsville 230 kV | Active |
| AG1-539 | Grit DP-Perth 115 kV | Active |
| AG1-547 | Mount Airy-Chatham 69 kV | Active |
| AG1-551 | Parmele 12.5 kV | Active |
| AG1-552 | Carolina 13.2 kV | Active |
| AG1-556 | Lexington 115 kV | Active |
| AG1-558 | Buckner 34.5 kV | Active |
| AG1-559 | Caroline Pines 22 kV | Active |
| V4-068 | Murphy's 34.5kV | In Service |
| W1-029 | Winfall 230kV | In Service |
| Y1-086 | Morgans Corner | In Service |
| Z1-036 | WinFall-Chowan 230kV | Under Construction |
| Z1-068 | Birdneck 34.5kV | In Service |
| Z2-027 | Pasquotank 34.5kV | In Service |
| Z2-044 | Whitakers 34.5kV | In Service |
| Z2-088 | Tarboro-Everetts 230kV | In Service |
Affected Systems
In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with potential Affected System impacts. PJM initiates coordination with each Affected System Operator by providing a list of New Service Requests in the Cycle with potential impacts to their respective system. If the Affected System Operator indicates an Affected System Study is required, PJM will notify the Project Developer or Eligible Customer of the need for an Affected System Study. See below if any Affected System Operator requires a study for this project:
System Reinforcements
Based on the Phase I analysis results, this project has potential cost responsibility for the following System Reinforcements:
| AF1-123 System Reinforcements Cost Breakdown: | TO | RTEP ID / TO ID | Title | MW Impact | Percent Allocation | Allocated Cost ($USD) | |||
|---|---|---|---|---|---|---|---|---|---|
| Dominion | (Pending) / TC1-PH1-DOM-074 | Wreck and rebuild existing Line 568 Ladysmith - Possum Point for single circuit | 144.4 MW | 20.0% | $54,779,071 | ||||
| Dominion | (Pending) / TC1-PH1-DOM-073 | Wreck and Rebuild the existing 37.41 mile line to monopole from Midlothian to Carson, and build a second line in existing ROW (Line 563) | 319.7 MW | 13.6% | $29,028,291 | ||||
| Dominion | (Pending) / TC1-PH1-DOM-090 | Wreck and Rebuild the existing 41.13 mile line to monopole from North Anna to Midlothian and build a second line in existing ROW (Line 576) | 328.8 MW | 11.2% | $26,351,209 | ||||
| Dominion | (Pending) / TC1-PH1-DOM-089 | Substation Expansion work at Morrisville 500 kV Substation | 127.0 MW | 29.6% | $11,847,578 | ||||
| Dominion | (Pending) / TC1-PH1-DOM-069 | Build a second 18.75 mile Spotsylvania to Morrisville 500 kV (same ROW as Line 594) | 144.8 MW | 11.0% | $11,792,954 | ||||
| Dominion | (Pending) / TC1-PH1-DOM-043 | Wreck and rebuild 5.7 miles of 230 kV line 2128 between Fentress and Thrasher | 400.3 MW | 27.6% | $9,379,034 | ||||
| Dominion | (Pending) / TC1-PH1-DOM-071 | Add a second line between Spotsylvania and North Anna (same ROW as Line 573) | 168.1 MW | 9.2% | $7,330,920 | ||||
| Dominion | (Pending) / dom-022 | Add additional 500/230 kV transformer at Chickahominy substation. | 192.5 MW | 14.7% | $5,867,936 | ||||
| Dominion | (Pending) / TC1-PH1-DOM-051 | Wreck and rebuild 10.7 miles of 230 kV line between Lanex and Lightfoot | 65.1 MW | 17.9% | $5,512,013 | ||||
| Dominion | n7645 / dom-484 | Add additional 500/230 kV transformer Suffolk Substation | 84.4 MW | 11.3% | $4,535,027 | ||||
| Dominion | n8149 / dom-013 | Add Additional 500/230 kV Transformer at Elmont Substation | 176.2 MW | 11.0% | $4,388,599 | ||||
| Dominion | n7611 / dom-413 | Rebuild 9.1 miles of 500 kV Line 575 from Ladysmith to AG1-133 Tap with 3-1351.5 113C ACSR. Replace wave Trap, Line lead at Ladysmith terminal. | 36.0 MW | 7.6% | $3,988,137 | ||||
| Dominion | (Pending) / dom-216 | Rebuild 7.8 miles of 230 kV Line 289 from Kings Fork to Chuckatuck with (2) 768.2 ACSS. | 56.2 MW | 15.0% | $3,370,128 | ||||
| Dominion | (Pending) / TC1-PH1-DOM-055 | Wreck and rebuild 4.82 miles of 230 kV line 2105 between Thrasher and Yadkin / additional station upgrades | 250.6 MW | 21.5% | $3,294,518 | ||||
| Dominion | n8056 | Wreck and rebuild the existing 115 kV Line and Add new 230 kV Circuit | 20.6 MW | 10.0% | $3,261,692 | ||||
| Dominion | (Pending) / TC1-PH1-DOM-087 | Addition of 230/500 kV Transformer at Carson Substation. | 62.3 MW | 7.7% | $3,090,856 | ||||
| Dominion | n6605 / dom-101 | Wreck and rebuild 7.2 miles of line 271 between Pocaty and Landstown | 203.1 MW | 13.6% | $2,823,546 | ||||
| Dominion | n8152 / dom-378 | Add additional 500/230 kV transformer at Midlothian Substation | 20.2 MW | 6.9% | $2,769,209 | ||||
| Dominion | n7634 / dom-379 | Rebuild 500 kV Line #575 from North Anna to AG1-133 Tap. | 36.0 MW | 8.7% | $2,713,343 | ||||
| Dominion | (Pending) / dom-311 | Rebuild 6.8 miles of 230 kV Line 289 from Suffolk to Kings Fork with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 deg C | 56.3 MW | 15.0% | $2,554,968 | ||||
| Dominion | n7569 / dom-490 | Reconductor 6.51 miles of line between Mt. Eagle and Cunningham | 36.4 MW | 6.4% | $2,397,367 | ||||
| Dominion | (Pending) / dom-301 | Rebuild 12.4 miles of 230 kV Line 259 from Chesterfield to Basin with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor at 250 degrees C. And breaker equipment. | 16.0 MW | 5.6% | $2,163,861 | ||||
| Dominion | n6551 / dom-159 | Rebuild 7.32 miles of 230 kV Line 208 from Chesterfield to Iron Bridge with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor at 250 degrees C. | 15.4 MW | 9.9% | $2,089,521 | ||||
| Dominion | (Pending) / dom-164 | Rebuild 7.0 miles of 230 kV Line 208 from Iron Bridge to Southwest with (2) 768.2 ACSS | 15.4 MW | 9.9% | $2,020,026 | ||||
| Dominion | n6607 / dom-116 | Rebuild 5.88 miles of 230 kV Line 2026 from Landstown to Lynnhaven with (2) 768.2 ACSS/TW (20/7) "MAUMEE" | 56.5 MW | 8.4% | $1,426,462 | ||||
| Dominion | n7568 / dom-369 | Rebuild 6.47 miles of 230 kV Line 2028 from Mt Eagle to Charlottesville with 2-768.2 ACSS 250 C. Replace Wave Trap and CB Switch at Charlottesville terminal | 36.4 MW | 6.7% | $1,291,232 | ||||
| Dominion | (Pending) / TC1-PH1-DOM-019 | Wreck and rebuild 5.86 miles of 230 kV line 2028 between AF2-397 Tap to Grape Vine (Cunningham) | 36.4 MW | 6.4% | $1,078,999 | ||||
| Dominion | n6161 / dom-039 | Replace Circuit Breaker at Clifton | 71.7 MW | 34.7% | $866,285 | ||||
| Dominion | n7566 / dom-265 | Rebuild 5 miles of 230 kV Line 2028 from Fork Union to AF2-397 Tap with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor at 250 degrees C. | 36.4 MW | 6.7% | $835,009 | ||||
| Dominion | n8239 / dom-300 | Rebuild 9.46 miles of 230 kV Line 217 from Chesterfield to Varina with 2-768.2 ACSS 250 C | 14.8 MW | 5.2% | $739,375 | ||||
| Dominion | (Pending) / dom-122 | Add additional 138/115 kV transformer at Altavista substation | 17.2 MW | 10.5% | $679,790 | ||||
| Dominion | n6606 / dom-100 | Rebuild 1.76 miles of 230 kV Line 2240 from Pocaty to Fentress | 203.1 MW | 12.6% | $637,608 | ||||
| Dominion | (Pending) / TC1-PH1-DOM-048 | Replace Circuit Breaker at Fentress for increased rating on Line 2128 6FENTRES 230 KV to 6THRASHER 230 KV ckt 1 | 400.3 MW | 27.6% | $413,295 | ||||
| Dominion | (Pending) / TC1-PH1-DOM-081 | Replace Circuit Breaker and Relay at Surry for increased rating on Line 567 8SURRY 500 KV to 8CHCKAHM 500 KV ckt 1 | 265.3 MW | 15.2% | $403,172 | ||||
| Dominion | n7567 / dom-276 | Rebuild 1.63 miles of 230 kV Line 2028 from Fork Union to Bremo Dist with 2-795 ACSR (26/7) 150 C | 40.2 MW | 6.9% | $321,565 | ||||
| Dominion | n8238 / dom-294 | Rebuild 1.38 mi miles of 230 kV Line 217 from Varina to Charles City with 2-768.2 ACSS 250 C | 14.8 MW | 5.2% | $206,728 | ||||
| Dominion | (Pending) / TC1-PH1-DOM-044 | Replace Circuit Breaker Switch at Fentress for increased rating on Line 2128 6FENTRES 230 KV to 6THRASHER 230 KV ckt 1 | 400.3 MW | 27.6% | $151,541 | ||||
| Dominion | (Pending) / TC1-PH1-DOM-082 | Replace Circuit Breaker Switch at Surry for increased rating on 8SURRY 500 KV to 8CHCKAHM 500 KV ckt 1 | 265.3 MW | 15.2% | $136,926 | ||||
| Dominion | n7789 / dom-363 | Rebuild 0.16 miles of Line 2193 from Bremo to Bremo Dist | 40.2 MW | 6.9% | $133,670 | ||||
| Dominion | (Pending) / TC1-PH1-DOM-047 | Replace Wave Trap at Fentress and Thrasher for increased rating on Line 2128 6FENTRES 230 KV to 6THRASHER 230 KV ckt 1 | 400.3 MW | 27.6% | $110,212 | ||||
| Dominion | (Pending) / TC1-PH1-DOM-057 | Replace Wave Trap at Yadkin and Thrasher for increased rating on Line 2015 6THRASHER 230 KV to 6YADKIN 230 KV ckt 1 | 250.6 MW | 21.5% | $85,809 | ||||
| Dominion | (Pending) / TC1-PH1-DOM-049 | Replace Circuit Breaker Switch at Thrasher for increased rating on Line 2128 6FENTRES 230 KV to 6THRASHER 230 KV ckt 1 | 400.3 MW | 27.6% | $75,771 | ||||
| Dominion | n8260 / dom-457 | Replace Wave Traps at Surry and Septa | 50.1 MW | 12.1% | $72,306 | ||||
| Dominion | (Pending) / TC1-PH1-DOM-079 | Replace Wave Trap at Surry for increased rating on Line 567 8SURRY 500 KV to 8CHCKAHM 500 KV ckt 1 | 265.3 MW | 15.2% | $45,642 | ||||
| Dominion | (Pending) / TC1-PH1-DOM-045 | Repalce CT Relay at Fentress for increased rating on Line 2128 6FENTRES 230 KV to 6THRASHER 230 KV ckt 1 | 400.3 MW | 27.6% | $41,329 | ||||
| Dominion | (Pending) / TC1-PH1-DOM-046 | Replace Circuit Breaker Lead at Thrasher for increased rating on Line 2128 6FENTRES 230 KV to 6THRASHER 230 KV ckt 1 | 400.3 MW | 27.6% | $27,553 | ||||
| Dominion | (Pending) / TC1-PH1-DOM-056 | Replace Circuit Breaker Lead at Thrasher for increased rating on Line 2105 6THRASHER 230 KV to 6YADKIN 230 KV ckt 1 | 250.6 MW | 21.5% | $21,452 | ||||
| Dominion | (Pending) / TC1-PH1-DOM-080 | Replace Line Lead at Surry for increased rating on Line 567 8SURRY 500 KV to 8CHCKAHM 500 KV ckt 1 | 265.3 MW | 15.2% | $15,214 | ||||
| Dominion | (Pending) / TC1-PH1-DOM-097 | Substation work for Energizing the bremo Tx#7 | 18.4 MW | 8.1% | $8,120 | ||||
| Grand Total: | $217,174,869 | ||||||||
| System Reinforcement | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| TO | RTEP ID / TO ID | Title | Total Cost ($USD) | Allocated Cost ($USD) | Time Estimate | ||||
| Dominion | (Pending) / TC1-PH1-DOM-074 | Wreck and rebuild existing Line 568 Ladysmith - Possum Point for single circuit | $273,296,000 | $54,779,071 | 48 to 60 Months | ||||
Contributor
Description: Wreck and rebuild existing Line 568 for single circuit with (3) 1351.1 ACSR (45/7) "DIPPER" conductor at 110 degrees C.
| Flowgates Addressed by this Reinforcement | |
|---|---|
| Facility | Contingency |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line | (Any) |
| New Ratings | |||
|---|---|---|---|
| Facility | Rating Set | Rating Type | Rating Value |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line | (All) | A | 4356.0 MVA |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line | (All) | B | 4356.0 MVA |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line | (All) | C | 5009.0 MVA |
| Cost Allocation | |||
|---|---|---|---|
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
| AE2-123 | 131.0 MW | 18.2% | $49,707,700 |
| AE2-124 | 106.7 MW | 14.8% | $40,471,957 |
| AF1-123 | 144.4 MW | 20.0% | $54,779,071 |
| AF1-124 | 144.4 MW | 20.0% | $54,779,071 |
| AF1-125 | 144.4 MW | 20.0% | $54,779,071 |
| AG1-178 | 49.5 MW | 6.9% | $18,779,131 |
| System Reinforcement | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| TO | RTEP ID / TO ID | Title | Total Cost ($USD) | Allocated Cost ($USD) | Time Estimate | ||||
| Dominion | (Pending) / TC1-PH1-DOM-073 | Wreck and Rebuild the existing 37.41 mile line to monopole from Midlothian to Carson, and build a second line in existing ROW (Line 563) | $213,237,000 | $29,028,291 | 48 to 60 Months | ||||
Contributor
Description: Wreck and Rebuild the existing 37.41 mile line to monopole from Midlothian to Carson, and build a second line in existing ROW (Line 563) with (3) 1351.1 ACSR (45/7) "DIPPER" conductor at 110 degrees C.
| Flowgates Addressed by this Reinforcement | |
|---|---|
| Facility | Contingency |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line | (Any) |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line | DVP_P1-2: LN 563_SRT-S-1 |
| New Ratings | |||
|---|---|---|---|
| Facility | Rating Set | Rating Type | Rating Value |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line | (All) | A | 4295.0 MVA |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line | (All) | B | 4357.0 MVA |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line | (All) | C | 4996.0 MVA |
| Cost Allocation | |||
|---|---|---|---|
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
| AE2-123 | 263.9 MW | 11.2% | $23,961,734 |
| AE2-124 | 260.0 MW | 11.1% | $23,603,741 |
| AE2-313 | 152.9 MW | 6.5% | $13,883,822 |
| AF1-123 | 319.7 MW | 13.6% | $29,028,291 |
| AF1-124 | 319.7 MW | 13.6% | $29,028,291 |
| AF1-125 | 319.7 MW | 13.6% | $29,028,291 |
| AF2-042 | 209.8 MW | 8.9% | $19,045,257 |
| AG1-011 | 43.4 MW | 1.8% | $3,941,462 |
| AG1-178 | 189.2 MW | 8.1% | $17,177,030 |
| AG1-184 | 101.9 MW | 4.3% | $9,254,066 |
| AG1-359 | 32.6 MW | 1.4% | $2,961,454 |
| AG1-449 | 39.0 MW | 1.7% | $3,543,975 |
| AG1-505 | 48.4 MW | 2.1% | $4,389,793 |
| AG1-506 | 48.4 MW | 2.1% | $4,389,793 |
| System Reinforcement | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| TO | RTEP ID / TO ID | Title | Total Cost ($USD) | Allocated Cost ($USD) | Time Estimate | ||||
| Dominion | (Pending) / TC1-PH1-DOM-090 | Wreck and Rebuild the existing 41.13 mile line to monopole from North Anna to Midlothian and build a second line in existing ROW (Line 576) | $234,441,000 | $26,351,209 | 48 to 60 Months | ||||
Contributor
Description: Wreck and Rebuild the existing 41.13 mile line to monopole from North Anna to Midlothian and build a second line in existing ROW (Line 576) with (3) 1351.1 ACSR (45/7) "DIPPER" conductor at 110 degrees C.
| Flowgates Addressed by this Reinforcement | |
|---|---|
| Facility | Contingency |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line | DVP_P1-2: LN 576_SRT-A |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line | (Any) |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line | DVP_P4-2: 57602_SRT-S |
| New Ratings | |||
|---|---|---|---|
| Facility | Rating Set | Rating Type | Rating Value |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line | (All) | A | 4295.0 MVA |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line | (All) | B | 4357.0 MVA |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line | (All) | C | 4996.0 MVA |
| Cost Allocation | |||
|---|---|---|---|
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
| AE2-123 | 489.6 MW | 16.7% | $39,232,996 |
| AE2-124 | 489.5 MW | 16.7% | $39,228,910 |
| AE2-270 | 86.9 MW | 3.0% | $6,965,140 |
| AE2-313 | 154.0 MW | 5.3% | $12,344,238 |
| AF1-123 | 328.8 MW | 11.2% | $26,351,209 |
| AF1-124 | 328.8 MW | 11.2% | $26,351,209 |
| AF1-125 | 328.8 MW | 11.2% | $26,351,209 |
| AF2-042 | 160.2 MW | 5.5% | $12,840,117 |
| AG1-011 | 92.7 MW | 3.2% | $7,429,366 |
| AG1-178 | 198.9 MW | 6.8% | $15,940,000 |
| AG1-184 | 107.2 MW | 3.7% | $8,587,565 |
| AG1-359 | 34.7 MW | 1.2% | $2,777,898 |
| AG1-449 | 37.1 MW | 1.3% | $2,970,304 |
| AG1-505 | 44.1 MW | 1.5% | $3,535,420 |
| AG1-506 | 44.1 MW | 1.5% | $3,535,420 |
| System Reinforcement | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| TO | RTEP ID / TO ID | Title | Total Cost ($USD) | Allocated Cost ($USD) | Time Estimate | ||||
| Dominion | (Pending) / TC1-PH1-DOM-089 | Substation Expansion work at Morrisville 500 kV Substation | $40,000,000 | $11,847,578 | 36 to 40 Months | ||||
Contributor
Description: Expand Morrisville substation and relocate line #545 and Line #569.
| Flowgates Addressed by this Reinforcement | |
|---|---|
| Facility | Contingency |
| 8BRISTER-8OX 500.0 kV Ckt 1 line | DVP_P4-2: 541T569_SRT-S |
| Cost Allocation | |||
|---|---|---|---|
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
| AF1-123 | 127.0 MW | 29.6% | $11,847,578 |
| AF1-124 | 127.0 MW | 29.6% | $11,847,578 |
| AF1-125 | 127.0 MW | 29.6% | $11,847,578 |
| AG1-178 | 47.8 MW | 11.1% | $4,457,265 |
| System Reinforcement | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| TO | RTEP ID / TO ID | Title | Total Cost ($USD) | Allocated Cost ($USD) | Time Estimate | ||||
| Dominion | (Pending) / TC1-PH1-DOM-069 | Build a second 18.75 mile Spotsylvania to Morrisville 500 kV (same ROW as Line 594) | $106,875,000 | $11,792,954 | 48 to 60 Months | ||||
Contributor
Description: Build a second 18.75 mile Spotsylvania to Morrisville 500 kV (same ROW as Line 594) with (3) 1351.1 ACSR (45/7) "DIPPER" conductor at 110 degrees C.
| Flowgates Addressed by this Reinforcement | |
|---|---|
| Facility | Contingency |
| 8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line | (Any) |
| 8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line | DVP_P1-2: LN 594_SRT-S |
| 8BRISTER-8CHANCE 500.0 kV Ckt 1 line | DVP_P1-2: LN 594_SRT-S |
| New Ratings | |||
|---|---|---|---|
| Facility | Rating Set | Rating Type | Rating Value |
| 8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line | (All) | A | 4295.0 MVA |
| 8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line | (All) | B | 4357.0 MVA |
| 8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line | (All) | C | 4996.0 MVA |
| Cost Allocation | |||
|---|---|---|---|
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
| AE2-123 | 132.8 MW | 10.1% | $10,814,701 |
| AE2-124 | 132.8 MW | 10.1% | $10,816,818 |
| AE2-313 | 36.0 MW | 2.7% | $2,932,236 |
| AF1-123 | 144.8 MW | 11.0% | $11,792,954 |
| AF1-124 | 144.8 MW | 11.0% | $11,792,954 |
| AF1-125 | 144.8 MW | 11.0% | $11,792,954 |
| AF2-037 | 39.9 MW | 3.0% | $3,253,352 |
| AF2-042 | 150.3 MW | 11.5% | $12,239,895 |
| AF2-063 | 38.0 MW | 2.9% | $3,091,124 |
| AG1-133 | 44.3 MW | 3.4% | $3,604,113 |
| AG1-178 | 186.0 MW | 14.2% | $15,150,712 |
| AG1-184 | 33.9 MW | 2.6% | $2,762,271 |
| AG1-288 | 33.7 MW | 2.6% | $2,746,879 |
| AG1-305 | 50.1 MW | 3.8% | $4,084,037 |
| System Reinforcement | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| TO | RTEP ID / TO ID | Title | Total Cost ($USD) | Allocated Cost ($USD) | Time Estimate | ||||
| Dominion | (Pending) / TC1-PH1-DOM-043 | Wreck and rebuild 5.7 miles of 230 kV line 2128 between Fentress and Thrasher | $34,040,000 | $9,379,034 | 42 to 48 Months | ||||
Contributor
Description: Wreck and rebuild 5.7 miles of 230 kV line 2128 between Fentress and Thrasher with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 degrees C as a double circuit.
| Flowgates Addressed by this Reinforcement | |
|---|---|
| Facility | Contingency |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line | (Any) |
| New Ratings | |||
|---|---|---|---|
| Facility | Rating Set | Rating Type | Rating Value |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line | (All) | A | 877.0 MVA |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line | (All) | B | 957.0 MVA |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line | (All) | C | 1164.0 MVA |
| Cost Allocation | |||
|---|---|---|---|
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
| AE2-123 | 82.2 MW | 5.7% | $1,925,382 |
| AE2-124 | 97.3 MW | 6.7% | $2,278,924 |
| AF1-123 | 400.3 MW | 27.6% | $9,379,034 |
| AF1-124 | 400.3 MW | 27.6% | $9,379,034 |
| AF1-125 | 400.3 MW | 27.6% | $9,379,034 |
| AG1-359 | 72.5 MW | 5.0% | $1,698,591 |
| System Reinforcement | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| TO | RTEP ID / TO ID | Title | Total Cost ($USD) | Allocated Cost ($USD) | Time Estimate | ||||
| Dominion | (Pending) / TC1-PH1-DOM-071 | Add a second line between Spotsylvania and North Anna (same ROW as Line 573) | $79,914,000 | $7,330,920 | 48 to 60 Months | ||||
Contributor
Description: Add a second line between Spotsylvania and North Anna (same ROW as Line 573) with (3) 1351.5 ACSR (45/7) "DIPPER" conductor at 110 degrees C.
| Flowgates Addressed by this Reinforcement | |
|---|---|
| Facility | Contingency |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line | (Any) |
| 8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line | DVP_P1-2: LN 573_SRT-A |
| 8LADYSMITH-AG1-133 TP 500.0 kV Ckt 1 line | DVP_P1-2: LN 573_SRT-A |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line | DVP_P1-2: LN 573_SRT-A |
| New Ratings | |||
|---|---|---|---|
| Facility | Rating Set | Rating Type | Rating Value |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line | (All) | A | 4295.0 MVA |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line | (All) | B | 4357.0 MVA |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line | (All) | C | 4996.0 MVA |
| Cost Allocation | |||
|---|---|---|---|
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
| AE2-123 | 107.4 MW | 5.9% | $4,684,918 |
| AE2-124 | 135.0 MW | 7.4% | $5,887,531 |
| AE2-313 | 107.3 MW | 5.9% | $4,678,942 |
| AF1-123 | 168.1 MW | 9.2% | $7,330,920 |
| AF1-124 | 168.1 MW | 9.2% | $7,330,920 |
| AF1-125 | 168.1 MW | 9.2% | $7,330,920 |
| AF2-037 | 40.2 MW | 2.2% | $1,752,471 |
| AF2-042 | 202.7 MW | 11.1% | $8,842,049 |
| AF2-063 | 128.5 MW | 7.0% | $5,604,664 |
| AG1-011 | 32.3 MW | 1.8% | $1,410,588 |
| AG1-133 | 103.5 MW | 5.7% | $4,515,808 |
| AG1-178 | 249.4 MW | 13.6% | $10,877,127 |
| AG1-184 | 100.2 MW | 5.5% | $4,369,467 |
| AG1-305 | 121.5 MW | 6.6% | $5,297,675 |
| System Reinforcement | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| TO | RTEP ID / TO ID | Title | Total Cost ($USD) | Allocated Cost ($USD) | Time Estimate | ||||
| Dominion | (Pending) / dom-022 | Add additional 500/230 kV transformer at Chickahominy substation. | $40,000,000 | $5,867,936 | 42 to 44 Months | ||||
Contributor
Description: Add additional 500/230 kV transformer at Chickahominy substation.
| Flowgates Addressed by this Reinforcement | |
|---|---|
| Facility | Contingency |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer | (Any) |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer | (Any) |
| New Ratings | |||
|---|---|---|---|
| Facility | Rating Set | Rating Type | Rating Value |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer | (All) | A | 1133.0 MVA |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer | (All) | B | 1203.0 MVA |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer | (All) | C | 1365.0 MVA |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer | (All) | A | 1133.0 MVA |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer | (All) | B | 1203.0 MVA |
| 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 2 transformer | (All) | C | 1365.0 MVA |
| Cost Allocation | |||
|---|---|---|---|
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
| AE2-123 | 177.0 MW | 13.5% | $5,394,675 |
| AE2-124 | 176.8 MW | 13.5% | $5,389,097 |
| AE2-156 | 22.3 MW | 1.7% | $680,537 |
| AE2-270 | 39.7 MW | 3.0% | $1,208,635 |
| AF1-123 | 192.5 MW | 14.7% | $5,867,936 |
| AF1-124 | 192.5 MW | 14.7% | $5,867,936 |
| AF1-125 | 192.5 MW | 14.7% | $5,867,936 |
| AF1-201 | 50.7 MW | 3.9% | $1,544,454 |
| AF2-065 | 39.7 MW | 3.0% | $1,208,635 |
| AF2-120 | 23.6 MW | 1.8% | $719,219 |
| AG1-011 | 42.3 MW | 3.2% | $1,289,382 |
| AG1-075 | 33.8 MW | 2.6% | $1,031,566 |
| AG1-135 | 22.9 MW | 1.7% | $698,064 |
| AG1-147 | 27.2 MW | 2.1% | $827,948 |
| AG1-359 | 28.0 MW | 2.1% | $853,369 |
| AG1-364 | 22.3 MW | 1.7% | $680,598 |
| AG1-536 | 28.5 MW | 2.2% | $870,013 |
| System Reinforcement | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| TO | RTEP ID / TO ID | Title | Total Cost ($USD) | Allocated Cost ($USD) | Time Estimate | ||||
| Dominion | (Pending) / TC1-PH1-DOM-051 | Wreck and rebuild 10.7 miles of 230 kV line between Lanex and Lightfoot | $30,762,500 | $5,512,013 | 42 to 48 Months | ||||
Contributor
Description: Wreck and rebuild 10.7 miles of 230 kV line between Lanex and Lightfoot with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 degrees C. Replace the line lead at Light Foot.
| Flowgates Addressed by this Reinforcement | |
|---|---|
| Facility | Contingency |
| 6LANEXA-6LIGH209 230.0 kV Ckt 1 line | (Any) |
| New Ratings | |||
|---|---|---|---|
| Facility | Rating Set | Rating Type | Rating Value |
| 6LANEXA-6LIGH209 230.0 kV Ckt 1 line | (All) | A | 877.0 MVA |
| 6LANEXA-6LIGH209 230.0 kV Ckt 1 line | (All) | B | 957.0 MVA |
| 6LANEXA-6LIGH209 230.0 kV Ckt 1 line | (All) | C | 1164.0 MVA |
| Cost Allocation | |||
|---|---|---|---|
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
| AE2-123 | 58.1 MW | 16.0% | $4,913,672 |
| AE2-124 | 58.1 MW | 16.0% | $4,914,519 |
| AE2-156 | 9.1 MW | 2.5% | $765,910 |
| AF1-123 | 65.1 MW | 17.9% | $5,512,013 |
| AF1-124 | 65.1 MW | 17.9% | $5,512,013 |
| AF1-125 | 65.1 MW | 17.9% | $5,512,013 |
| AG1-184 | 10.6 MW | 2.9% | $900,473 |
| AG1-359 | 11.6 MW | 3.2% | $980,873 |
| AG1-364 | 9.1 MW | 2.5% | $765,910 |
| AG1-536 | 11.6 MW | 3.2% | $985,104 |
| System Reinforcement | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| TO | RTEP ID / TO ID | Title | Total Cost ($USD) | Allocated Cost ($USD) | Time Estimate | ||||
| Dominion | n7645 / dom-484 | Add additional 500/230 kV transformer Suffolk Substation | $40,000,000 | $4,535,027 | Dec 31 2024 | ||||
Contributor
Description: Add additional 500/230 kV transformer Suffolk Substation
| Flowgates Addressed by this Reinforcement | |
|---|---|
| Facility | Contingency |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer | (Any) |
| New Ratings | |||
|---|---|---|---|
| Facility | Rating Set | Rating Type | Rating Value |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer | (All) | A | 1133.0 MVA |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer | (All) | B | 1203.0 MVA |
| 6SUFFOLK-8SUFFOLK 230.0/500.0 kV Ckt 2 transformer | (All) | C | 1365.0 MVA |
| Cost Allocation | |||
|---|---|---|---|
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
| AE2-123 | 108.2 MW | 14.5% | $5,817,424 |
| AE2-124 | 109.4 MW | 14.7% | $5,880,160 |
| AE2-147 | 38.0 MW | 5.1% | $2,043,557 |
| AE2-156 | 11.7 MW | 1.6% | $630,044 |
| AE2-270 | 11.3 MW | 1.5% | $609,132 |
| AF1-123 | 84.4 MW | 11.3% | $4,535,027 |
| AF1-124 | 84.4 MW | 11.3% | $4,535,027 |
| AF1-125 | 84.4 MW | 11.3% | $4,535,027 |
| AF1-152 | 12.7 MW | 1.7% | $681,168 |
| AF2-046 | 26.7 MW | 3.6% | $1,435,823 |
| AF2-047 | 31.1 MW | 4.2% | $1,669,993 |
| AF2-081 | 12.6 MW | 1.7% | $678,319 |
| AG1-008 | 26.7 MW | 3.6% | $1,435,823 |
| AG1-343 | 11.5 MW | 1.6% | $620,744 |
| AG1-359 | 17.0 MW | 2.3% | $914,962 |
| AG1-364 | 11.8 MW | 1.6% | $632,624 |
| AG1-437 | 18.9 MW | 2.5% | $1,016,564 |
| AG1-438 | 18.9 MW | 2.5% | $1,016,564 |
| AG1-439 | 24.4 MW | 3.3% | $1,312,018 |
| System Reinforcement | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| TO | RTEP ID / TO ID | Title | Total Cost ($USD) | Allocated Cost ($USD) | Time Estimate | ||||
| Dominion | n8149 / dom-013 | Add Additional 500/230 kV Transformer at Elmont Substation | $40,000,000 | $4,388,599 | 42 to 44 Months | ||||
Contributor
| Flowgates Addressed by this Reinforcement | |
|---|---|
| Facility | Contingency |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer | (Any) |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer | (Any) |
| New Ratings | |||
|---|---|---|---|
| Facility | Rating Set | Rating Type | Rating Value |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer | (All) | A | 1133.0 MVA |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer | (All) | B | 1203.0 MVA |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer | (All) | C | 1365.0 MVA |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer | (All) | A | 1133.0 MVA |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer | (All) | B | 1203.0 MVA |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer | (All) | C | 1365.0 MVA |
| Cost Allocation | |||
|---|---|---|---|
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
| AE2-123 | 152.7 MW | 9.5% | $3,803,667 |
| AE2-124 | 150.9 MW | 9.4% | $3,759,777 |
| AE2-147 | 19.0 MW | 1.2% | $474,163 |
| AE2-156 | 28.1 MW | 1.7% | $699,488 |
| AE2-250 | 17.7 MW | 1.1% | $441,981 |
| AE2-270 | 50.5 MW | 3.1% | $1,258,141 |
| AE2-313 | 32.8 MW | 2.0% | $816,086 |
| AF1-123 | 176.2 MW | 11.0% | $4,388,599 |
| AF1-124 | 223.0 MW | 13.9% | $5,555,699 |
| AF1-125 | 223.0 MW | 13.9% | $5,555,699 |
| AF1-201 | 39.9 MW | 2.5% | $994,407 |
| AF1-266 | 11.6 MW | 0.7% | $287,945 |
| AF2-046 | 18.5 MW | 1.2% | $460,588 |
| AF2-047 | 19.5 MW | 1.2% | $486,891 |
| AF2-065 | 40.7 MW | 2.5% | $1,014,110 |
| AF2-120 | 11.3 MW | 0.7% | $281,917 |
| AG1-008 | 18.5 MW | 1.2% | $461,534 |
| AG1-011 | 53.7 MW | 3.3% | $1,337,326 |
| AG1-075 | 45.4 MW | 2.8% | $1,130,808 |
| AG1-134 | 33.9 MW | 2.1% | $843,834 |
| AG1-135 | 11.0 MW | 0.7% | $274,096 |
| AG1-147 | 13.2 MW | 0.8% | $328,248 |
| AG1-178 | 61.1 MW | 3.8% | $1,521,377 |
| AG1-184 | 41.2 MW | 2.6% | $1,025,070 |
| AG1-359 | 35.3 MW | 2.2% | $879,752 |
| AG1-364 | 28.0 MW | 1.7% | $696,374 |
| AG1-449 | 26.5 MW | 1.7% | $660,207 |
| AG1-536 | 22.6 MW | 1.4% | $562,216 |
| System Reinforcement | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| TO | RTEP ID / TO ID | Title | Total Cost ($USD) | Allocated Cost ($USD) | Time Estimate | ||||
| Dominion | n7611 / dom-413 | Rebuild 9.1 miles of 500 kV Line 575 from Ladysmith to AG1-133 Tap with 3-1351.5 113C ACSR. Replace wave Trap, Line lead at Ladysmith terminal. | $52,170,000 | $3,988,137 | Dec 01 2024 | ||||
Contributor
| Flowgates Addressed by this Reinforcement | |
|---|---|
| Facility | Contingency |
| 8LADYSMITH-AG1-133 TAP 500.0 kV Ckt 1 line | (Any) |
| 8LADYSMITH-AG1-133 TP 500.0 kV Ckt 1 line | (Any) |
| New Ratings | |||
|---|---|---|---|
| Facility | Rating Set | Rating Type | Rating Value |
| 8LADYSMITH-AG1-133 TAP 500.0 kV Ckt 1 line | (All) | A | 3897.0 MVA |
| 8LADYSMITH-AG1-133 TAP 500.0 kV Ckt 1 line | (All) | B | 4287.0 MVA |
| 8LADYSMITH-AG1-133 TAP 500.0 kV Ckt 1 line | (All) | C | 5011.0 MVA |
| 8LADYSMITH-AG1-133 TP 500.0 kV Ckt 1 line | (All) | A | 3897.0 MVA |
| 8LADYSMITH-AG1-133 TP 500.0 kV Ckt 1 line | (All) | B | 4287.0 MVA |
| 8LADYSMITH-AG1-133 TP 500.0 kV Ckt 1 line | (All) | C | 5011.0 MVA |
| Cost Allocation | |||
|---|---|---|---|
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
| AE2-313 | 35.1 MW | 7.4% | $3,885,790 |
| AF1-123 | 36.0 MW | 7.6% | $3,988,137 |
| AF1-124 | 36.0 MW | 7.6% | $3,988,137 |
| AF1-125 | 36.0 MW | 7.6% | $3,988,137 |
| AF2-037 | 47.1 MW | 10.0% | $5,221,408 |
| AF2-042 | 49.5 MW | 10.5% | $5,483,924 |
| AF2-063 | 45.1 MW | 9.6% | $4,999,987 |
| AG1-133 | 57.4 MW | 12.2% | $6,362,190 |
| AG1-178 | 60.5 MW | 12.9% | $6,706,119 |
| AG1-184 | 32.6 MW | 6.9% | $3,612,862 |
| AG1-305 | 35.5 MW | 7.5% | $3,933,308 |
| System Reinforcement | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| TO | RTEP ID / TO ID | Title | Total Cost ($USD) | Allocated Cost ($USD) | Time Estimate | ||||
| Dominion | (Pending) / dom-216 | Rebuild 7.8 miles of 230 kV Line 289 from Kings Fork to Chuckatuck with (2) 768.2 ACSS. | $22,425,000 | $3,370,128 | 42 to 48 Months | ||||
Contributor
Description: Rebuild 7.8 miles of 230 kV Line 289 from Kings Fork to Chuckatuck with (2) 768.2 ACSS.
| Flowgates Addressed by this Reinforcement | |
|---|---|
| Facility | Contingency |
| 6CHCKTUK-6KINGFORK 230.0 kV Ckt 1 line | (Any) |
| New Ratings | |||
|---|---|---|---|
| Facility | Rating Set | Rating Type | Rating Value |
| 6CHCKTUK-6KINGFORK 230.0 kV Ckt 1 line | (All) | A | 797.0 MVA |
| 6CHCKTUK-6KINGFORK 230.0 kV Ckt 1 line | (All) | B | 797.0 MVA |
| 6CHCKTUK-6KINGFORK 230.0 kV Ckt 1 line | (All) | C | 1115.0 MVA |
| Cost Allocation | |||
|---|---|---|---|
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
| AE2-123 | 49.2 MW | 13.1% | $2,948,225 |
| AE2-124 | 50.6 MW | 13.5% | $3,032,030 |
| AE2-147 | 18.6 MW | 5.0% | $1,113,325 |
| AF1-123 | 56.2 MW | 15.0% | $3,370,128 |
| AF1-124 | 56.2 MW | 15.0% | $3,370,128 |
| AF1-125 | 56.2 MW | 15.0% | $3,370,128 |
| AF2-046 | 14.0 MW | 3.7% | $838,411 |
| AF2-047 | 15.7 MW | 4.2% | $942,777 |
| AG1-008 | 14.0 MW | 3.7% | $838,411 |
| AG1-359 | 8.7 MW | 2.3% | $522,313 |
| AG1-437 | 9.8 MW | 2.6% | $587,235 |
| AG1-438 | 9.8 MW | 2.6% | $587,235 |
| AG1-439 | 15.1 MW | 4.0% | $904,652 |
| System Reinforcement | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| TO | RTEP ID / TO ID | Title | Total Cost ($USD) | Allocated Cost ($USD) | Time Estimate | ||||
| Dominion | (Pending) / TC1-PH1-DOM-055 | Wreck and rebuild 4.82 miles of 230 kV line 2105 between Thrasher and Yadkin / additional station upgrades | $15,357,500 | $3,294,518 | 36 to 42 Months | ||||
Contributor
Description: Wreck and rebuild 4.82 miles of 230 kV line 2105 between Thrasher and Yadkin with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor at 250 degrees C. Replace Circuit Breaker and Circuit Breaker Lead at Yadkin, and Line Lead at Thrasher.
| Flowgates Addressed by this Reinforcement | |
|---|---|
| Facility | Contingency |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line | (Any) |
| New Ratings | |||
|---|---|---|---|
| Facility | Rating Set | Rating Type | Rating Value |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line | (All) | A | 1051.0 MVA |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line | (All) | B | 1166.0 MVA |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line | (All) | C | 1218.0 MVA |
| Cost Allocation | |||
|---|---|---|---|
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
| AE2-123 | 176.5 MW | 15.1% | $2,320,361 |
| AE2-124 | 194.5 MW | 16.6% | $2,556,866 |
| AF1-123 | 250.6 MW | 21.5% | $3,294,518 |
| AF1-124 | 250.6 MW | 21.5% | $3,294,518 |
| AF1-125 | 250.6 MW | 21.5% | $3,294,518 |
| AG1-359 | 45.4 MW | 3.9% | $596,720 |
| System Reinforcement | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| TO | RTEP ID / TO ID | Title | Total Cost ($USD) | Allocated Cost ($USD) | Time Estimate | ||||
| Dominion | n8056 | Wreck and rebuild the existing 115 kV Line and Add new 230 kV Circuit | $32,493,499 | $3,261,692 | 36 to 42 Months | ||||
Contributor
Description: 1. Wreck and rebuild of an existing 115 kV line as a double circuit line from Prince George-Poe substation. 2. Add one 230 kV Circuit Breaker at Prince George Substation. 3. Add three 230 kV Circuit Breaker at Poe Substation. New Rating: 1047/1047/1204
| Flowgates Addressed by this Reinforcement | |
|---|---|
| Facility | Contingency |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer | (Any) |
| New Ratings | |||
|---|---|---|---|
| Facility | Rating Set | Rating Type | Rating Value |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer | (All) | A | 1047.0 MVA |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer | (All) | B | 1047.0 MVA |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer | (All) | C | 1204.0 MVA |
| Cost Allocation | |||
|---|---|---|---|
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
| AE2-123 | 23.5 MW | 11.5% | $3,731,274 |
| AE2-124 | 23.2 MW | 11.3% | $3,680,509 |
| AE2-270 | 31.4 MW | 15.3% | $4,985,027 |
| AF1-123 | 20.6 MW | 10.0% | $3,261,692 |
| AF1-124 | 20.6 MW | 10.0% | $3,261,692 |
| AF1-125 | 20.6 MW | 10.0% | $3,261,692 |
| AF2-065 | 31.4 MW | 15.3% | $4,985,027 |
| AG1-011 | 33.6 MW | 16.4% | $5,326,585 |
| System Reinforcement | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| TO | RTEP ID / TO ID | Title | Total Cost ($USD) | Allocated Cost ($USD) | Time Estimate | ||||
| Dominion | (Pending) / TC1-PH1-DOM-087 | Addition of 230/500 kV Transformer at Carson Substation. | $40,000,000 | $3,090,856 | 42 to 44 Months | ||||
Contributor
Description: Add an 230/500 kV Transformer at carson Substation. Rating for new transformer is: 1133/1203/1365 MVA
| Flowgates Addressed by this Reinforcement | |
|---|---|
| Facility | Contingency |
| 6CARSON-8CARSON 230.0/500.0 kV Ckt 2 transformer | (Any) |
| 6CARSON-8CARSON 230.0/500.0 kV Ckt 1 transformer | (Any) |
| New Ratings | |||
|---|---|---|---|
| Facility | Rating Set | Rating Type | Rating Value |
| 6CARSON-8CARSON 230.0/500.0 kV Ckt 1 transformer | (All) | A | 1133.0 MVA |
| 6CARSON-8CARSON 230.0/500.0 kV Ckt 1 transformer | (All) | B | 1203.0 MVA |
| 6CARSON-8CARSON 230.0/500.0 kV Ckt 1 transformer | (All) | C | 1365.0 MVA |
| 6CARSON-8CARSON 230.0/500.0 kV Ckt 2 transformer | (All) | A | 1133.0 MVA |
| 6CARSON-8CARSON 230.0/500.0 kV Ckt 2 transformer | (All) | B | 1203.0 MVA |
| 6CARSON-8CARSON 230.0/500.0 kV Ckt 2 transformer | (All) | C | 1365.0 MVA |
| Cost Allocation | |||
|---|---|---|---|
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
| AE2-123 | 48.6 MW | 6.0% | $2,412,540 |
| AE2-124 | 48.8 MW | 6.0% | $2,419,835 |
| AE2-313 | 94.2 MW | 11.7% | $4,676,405 |
| AF1-123 | 62.3 MW | 7.7% | $3,090,856 |
| AF1-124 | 62.3 MW | 7.7% | $3,090,856 |
| AF1-125 | 62.3 MW | 7.7% | $3,090,856 |
| AF1-266 | 23.8 MW | 2.9% | $1,179,572 |
| AF2-042 | 113.4 MW | 14.1% | $5,629,541 |
| AG1-153 | 12.0 MW | 1.5% | $594,153 |
| AG1-160 | 12.3 MW | 1.5% | $608,891 |
| AG1-178 | 95.6 MW | 11.9% | $4,742,257 |
| AG1-184 | 51.5 MW | 6.4% | $2,554,863 |
| AG1-449 | 36.6 MW | 4.5% | $1,816,948 |
| AG1-505 | 41.2 MW | 5.1% | $2,046,213 |
| AG1-506 | 41.2 MW | 5.1% | $2,046,213 |
| System Reinforcement | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| TO | RTEP ID / TO ID | Title | Total Cost ($USD) | Allocated Cost ($USD) | Time Estimate | ||||
| Dominion | n6605 / dom-101 | Wreck and rebuild 7.2 miles of line 271 between Pocaty and Landstown | $20,700,000 | $2,823,546 | Dec 31 2026 | ||||
Contributor
Description: Wreck and rebuild 7.2 miles of line 271 between Pocaty and Landstown with (2)-768 ACSS (20/7) “MAUMEE” conductor @ 250 degrees C. Replace the line lead at Landstown.
| Flowgates Addressed by this Reinforcement | |
|---|---|
| Facility | Contingency |
| 6LANDSTN-6POCATY 230.0 kV Ckt 1 line | (Any) |
| New Ratings | |||
|---|---|---|---|
| Facility | Rating Set | Rating Type | Rating Value |
| 6LANDSTN-6POCATY 230.0 kV Ckt 1 line | (All) | A | 1168.0 MVA |
| 6LANDSTN-6POCATY 230.0 kV Ckt 1 line | (All) | B | 1196.0 MVA |
| 6LANDSTN-6POCATY 230.0 kV Ckt 1 line | (All) | C | 1349.0 MVA |
| Cost Allocation | |||
|---|---|---|---|
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
| AE2-123 | 301.6 MW | 20.3% | $4,193,604 |
| AE2-124 | 543.5 MW | 36.5% | $7,557,984 |
| AE2-156 | 8.7 MW | 0.6% | $120,278 |
| AF1-123 | 203.1 MW | 13.6% | $2,823,546 |
| AF1-124 | 203.1 MW | 13.6% | $2,823,546 |
| AF1-125 | 203.1 MW | 13.6% | $2,823,546 |
| AG1-359 | 16.8 MW | 1.1% | $233,326 |
| AG1-364 | 8.9 MW | 0.6% | $124,171 |
| System Reinforcement | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| TO | RTEP ID / TO ID | Title | Total Cost ($USD) | Allocated Cost ($USD) | Time Estimate | ||||
| Dominion | n8152 / dom-378 | Add additional 500/230 kV transformer at Midlothian Substation | $40,000,000 | $2,769,209 | 42 to 44 Months | ||||
Contributor
| Flowgates Addressed by this Reinforcement | |
|---|---|
| Facility | Contingency |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer | (Any) |
| New Ratings | |||
|---|---|---|---|
| Facility | Rating Set | Rating Type | Rating Value |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer | (All) | A | 1133.0 MVA |
| 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer | (All) | B | 1203.0 MVA |
| Cost Allocation | |||
|---|---|---|---|
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
| AE2-123 | 11.7 MW | 4.0% | $1,608,387 |
| AE2-124 | 10.7 MW | 3.7% | $1,465,681 |
| AE2-270 | 14.2 MW | 4.9% | $1,951,046 |
| AE2-313 | 24.4 MW | 8.3% | $3,337,431 |
| AF1-123 | 20.2 MW | 6.9% | $2,769,209 |
| AF1-124 | 20.2 MW | 6.9% | $2,769,209 |
| AF1-125 | 20.2 MW | 6.9% | $2,769,209 |
| AF1-293 | 10.6 MW | 3.6% | $1,454,314 |
| AF2-042 | 30.0 MW | 10.3% | $4,108,892 |
| AG1-011 | 15.2 MW | 5.2% | $2,081,974 |
| AG1-178 | 42.3 MW | 14.5% | $5,793,562 |
| AG1-184 | 22.8 MW | 7.8% | $3,121,180 |
| AG1-432 | 12.2 MW | 4.2% | $1,664,538 |
| AG1-449 | 15.8 MW | 5.4% | $2,161,133 |
| AG1-505 | 10.7 MW | 3.7% | $1,472,118 |
| AG1-506 | 10.7 MW | 3.7% | $1,472,118 |
| System Reinforcement | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| TO | RTEP ID / TO ID | Title | Total Cost ($USD) | Allocated Cost ($USD) | Time Estimate | ||||
| Dominion | n7634 / dom-379 | Rebuild 500 kV Line #575 from North Anna to AG1-133 Tap. | $31,165,500 | $2,713,343 | 48 to 60 Months | ||||
Contributor
Description: Rebuild 5.415 miles of 500 kV Line 575 from North Anna to AG1-133 Tap with 3-1351.5 113C ACSR. Replace Wave trap, Line Lead at North Anna terminal.
| Flowgates Addressed by this Reinforcement | |
|---|---|
| Facility | Contingency |
| 8NO ANNA-AG1-133 TAP 500.0 kV Ckt 1 line | (Any) |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line | (Any) |
| New Ratings | |||
|---|---|---|---|
| Facility | Rating Set | Rating Type | Rating Value |
| 8NO ANNA-AG1-133 TAP 500.0 kV Ckt 1 line | (All) | A | 3897.0 MVA |
| 8NO ANNA-AG1-133 TAP 500.0 kV Ckt 1 line | (All) | B | 4287.0 MVA |
| 8NO ANNA-AG1-133 TAP 500.0 kV Ckt 1 line | (All) | C | 5011.0 MVA |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line | (All) | A | 3897.0 MVA |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line | (All) | B | 4287.0 MVA |
| 8NO ANNA-AG1-133 TP 500.0 kV Ckt 1 line | (All) | C | 5011.0 MVA |
| Cost Allocation | |||
|---|---|---|---|
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
| AE2-313 | 35.1 MW | 8.5% | $2,643,710 |
| AF1-123 | 36.0 MW | 8.7% | $2,713,343 |
| AF1-124 | 36.0 MW | 8.7% | $2,713,343 |
| AF1-125 | 36.0 MW | 8.7% | $2,713,343 |
| AF2-037 | 47.1 MW | 11.4% | $3,552,403 |
| AF2-042 | 49.5 MW | 12.0% | $3,731,007 |
| AF2-063 | 45.1 MW | 10.9% | $3,401,758 |
| AG1-178 | 60.5 MW | 14.6% | $4,562,531 |
| AG1-184 | 32.6 MW | 7.9% | $2,458,023 |
| AG1-305 | 35.5 MW | 8.6% | $2,676,040 |
| System Reinforcement | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| TO | RTEP ID / TO ID | Title | Total Cost ($USD) | Allocated Cost ($USD) | Time Estimate | ||||
| Dominion | (Pending) / dom-311 | Rebuild 6.8 miles of 230 kV Line 289 from Suffolk to Kings Fork with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 deg C | $17,000,000 | $2,554,968 | 36 to 40 Months | ||||
Contributor
| Flowgates Addressed by this Reinforcement | |
|---|---|
| Facility | Contingency |
| 6KINGFORK-6SUFFOLK 230.0 kV Ckt 1 line | (Any) |
| New Ratings | |||
|---|---|---|---|
| Facility | Rating Set | Rating Type | Rating Value |
| 6KINGFORK-6SUFFOLK 230.0 kV Ckt 1 line | (All) | A | 797.0 MVA |
| 6KINGFORK-6SUFFOLK 230.0 kV Ckt 1 line | (All) | B | 797.0 MVA |
| 6KINGFORK-6SUFFOLK 230.0 kV Ckt 1 line | (All) | C | 956.0 MVA |
| Cost Allocation | |||
|---|---|---|---|
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
| AE2-123 | 49.2 MW | 13.1% | $2,235,234 |
| AE2-124 | 50.6 MW | 13.5% | $2,298,717 |
| AE2-147 | 18.6 MW | 5.0% | $843,679 |
| AF1-123 | 56.3 MW | 15.0% | $2,554,968 |
| AF1-124 | 56.3 MW | 15.0% | $2,554,968 |
| AF1-125 | 56.3 MW | 15.0% | $2,554,968 |
| AF2-046 | 14.0 MW | 3.7% | $635,472 |
| AF2-047 | 15.7 MW | 4.2% | $714,532 |
| AG1-008 | 14.0 MW | 3.7% | $635,472 |
| AG1-359 | 8.7 MW | 2.3% | $395,978 |
| AG1-437 | 9.8 MW | 2.6% | $445,067 |
| AG1-438 | 9.8 MW | 2.6% | $445,067 |
| AG1-439 | 15.1 MW | 4.0% | $685,878 |
| System Reinforcement | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| TO | RTEP ID / TO ID | Title | Total Cost ($USD) | Allocated Cost ($USD) | Time Estimate | ||||
| Dominion | n7569 / dom-490 | Reconductor 6.51 miles of line between Mt. Eagle and Cunningham | $37,432,500 | $2,397,367 | 36 to 40 Months | ||||
Contributor
Description: Reconductor 6.51 miles of line between Mt. Eagle and Cunningham with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @250 degrees C
| Flowgates Addressed by this Reinforcement | |
|---|---|
| Facility | Contingency |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line | (Any) |
| New Ratings | |||
|---|---|---|---|
| Facility | Rating Set | Rating Type | Rating Value |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line | (All) | A | 1315.0 MVA |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line | (All) | B | 1435.0 MVA |
| 6CUNNING-6MTEAGLE 230.0 kV Ckt 1 line | (All) | C | 1745.0 MVA |
| 6CUNNING-AF2-397 TP 230.0 kV Ckt 1 line | (All) | A | 1315.0 MVA |
| 6CUNNING-AF2-397 TP 230.0 kV Ckt 1 line | (All) | B | 1435.0 MVA |
| 6CUNNING-AF2-397 TP 230.0 kV Ckt 1 line | (All) | C | 1745.0 MVA |
| Cost Allocation | |||
|---|---|---|---|
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
| AE2-123 | 33.0 MW | 5.8% | $2,176,132 |
| AE2-124 | 33.1 MW | 5.8% | $2,176,790 |
| AF1-123 | 36.4 MW | 6.4% | $2,397,367 |
| AF1-124 | 36.4 MW | 6.4% | $2,397,367 |
| AF1-125 | 36.4 MW | 6.4% | $2,397,367 |
| AF1-293 | 23.0 MW | 4.1% | $1,516,379 |
| AF1-323 | 11.0 MW | 1.9% | $721,251 |
| AF2-042 | 21.3 MW | 3.7% | $1,403,325 |
| AF2-171 | 23.0 MW | 4.1% | $1,517,169 |
| AF2-222 | 21.2 MW | 3.7% | $1,393,844 |
| AF2-397 | 49.5 MW | 8.7% | $3,257,416 |
| AG1-011 | 8.2 MW | 1.4% | $539,259 |
| AG1-030 | 21.5 MW | 3.8% | $1,413,926 |
| AG1-098 | 13.9 MW | 2.4% | $913,844 |
| AG1-151 | 7.5 MW | 1.3% | $497,119 |
| AG1-181 | 19.7 MW | 3.5% | $1,298,700 |
| AG1-184 | 10.7 MW | 1.9% | $704,527 |
| AG1-185 | 9.5 MW | 1.7% | $628,346 |
| AG1-195 | 9.0 MW | 1.6% | $593,251 |
| AG1-196 | 11.1 MW | 2.0% | $733,498 |
| AG1-284 | 19.9 MW | 3.5% | $1,309,827 |
| AG1-285 | 12.4 MW | 2.2% | $814,222 |
| AG1-427 | 11.4 MW | 2.0% | $750,683 |
| AG1-432 | 39.2 MW | 6.9% | $2,584,231 |
| AG1-449 | 8.0 MW | 1.4% | $527,407 |
| AG1-505 | 13.6 MW | 2.4% | $897,054 |
| AG1-506 | 13.6 MW | 2.4% | $897,054 |
| AG1-537 | 6.7 MW | 1.2% | $439,835 |
| AG1-556 | 8.1 MW | 1.4% | $535,309 |
| System Reinforcement | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| TO | RTEP ID / TO ID | Title | Total Cost ($USD) | Allocated Cost ($USD) | Time Estimate | ||||
| Dominion | (Pending) / dom-301 | Rebuild 12.4 miles of 230 kV Line 259 from Chesterfield to Basin with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor at 250 degrees C. And breaker equipment. | $38,450,000 | $2,163,861 | 36 to 40 Months | ||||
Contributor
Description: Rebuild 12.4 miles of 230 kV Line 259 from Chesterfield to Basin with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor at 250 degrees C. Replace Circuit Breakre and Circuit Breaker Switch at Chesterfield, and Circuit Breaker Switch and Wave Trap at Basin.
| Flowgates Addressed by this Reinforcement | |
|---|---|
| Facility | Contingency |
| 6BASIN-6CHESTF B 230.0 kV Ckt 1 line | (Any) |
| New Ratings | |||
|---|---|---|---|
| Facility | Rating Set | Rating Type | Rating Value |
| 6BASIN-6CHESTF B 230.0 kV Ckt 1 line | (All) | A | 1168.0 MVA |
| 6BASIN-6CHESTF B 230.0 kV Ckt 1 line | (All) | B | 1292.0 MVA |
| 6BASIN-6CHESTF B 230.0 kV Ckt 1 line | (All) | C | 1349.0 MVA |
| Cost Allocation | |||
|---|---|---|---|
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
| AE2-123 | 10.1 MW | 3.6% | $1,365,422 |
| AE2-124 | 9.2 MW | 3.2% | $1,240,073 |
| AE2-147 | 8.7 MW | 3.1% | $1,179,228 |
| AE2-270 | 14.9 MW | 5.3% | $2,024,283 |
| AE2-313 | 25.7 MW | 9.1% | $3,485,919 |
| AF1-123 | 16.0 MW | 5.6% | $2,163,861 |
| AF1-124 | 16.0 MW | 5.6% | $2,163,861 |
| AF1-125 | 16.0 MW | 5.6% | $2,163,861 |
| AF1-266 | 7.7 MW | 2.7% | $1,048,188 |
| AF2-042 | 17.6 MW | 6.2% | $2,388,134 |
| AF2-046 | 10.1 MW | 3.5% | $1,364,338 |
| AF2-047 | 9.1 MW | 3.2% | $1,229,097 |
| AF2-065 | 7.6 MW | 2.7% | $1,032,333 |
| AG1-008 | 6.6 MW | 2.3% | $900,344 |
| AG1-011 | 15.9 MW | 5.6% | $2,161,151 |
| AG1-075 | 8.2 MW | 2.9% | $1,113,098 |
| AG1-178 | 23.4 MW | 8.3% | $3,176,138 |
| AG1-184 | 12.6 MW | 4.5% | $1,711,114 |
| AG1-359 | 7.8 MW | 2.7% | $1,055,099 |
| AG1-439 | 8.7 MW | 3.1% | $1,181,939 |
| AG1-449 | 8.6 MW | 3.0% | $1,164,051 |
| AG1-505 | 11.6 MW | 4.1% | $1,569,233 |
| AG1-506 | 11.6 MW | 4.1% | $1,569,233 |
| System Reinforcement | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| TO | RTEP ID / TO ID | Title | Total Cost ($USD) | Allocated Cost ($USD) | Time Estimate | ||||
| Dominion | n6551 / dom-159 | Rebuild 7.32 miles of 230 kV Line 208 from Chesterfield to Iron Bridge with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor at 250 degrees C. | $21,045,000 | $2,089,521 | 36 to 40 Months | ||||
Contributor
| Flowgates Addressed by this Reinforcement | |
|---|---|
| Facility | Contingency |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line | (Any) |
| New Ratings | |||
|---|---|---|---|
| Facility | Rating Set | Rating Type | Rating Value |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line | (All) | A | 876.0 MVA |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line | (All) | B | 956.0 MVA |
| 6CHESTF A-6IRON208 230.0 kV Ckt 1 line | (All) | C | 1163.0 MVA |
| Cost Allocation | |||
|---|---|---|---|
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
| AE2-123 | 9.7 MW | 6.3% | $1,316,837 |
| AE2-124 | 8.8 MW | 5.7% | $1,194,691 |
| AE2-270 | 14.9 MW | 9.6% | $2,023,353 |
| AF1-123 | 15.4 MW | 9.9% | $2,089,521 |
| AF1-124 | 15.4 MW | 9.9% | $2,089,521 |
| AF1-125 | 15.4 MW | 9.9% | $2,089,521 |
| AF1-128 | 37.7 MW | 24.4% | $5,128,010 |
| AF1-201 | 6.7 MW | 4.3% | $910,047 |
| AF2-065 | 7.6 MW | 4.9% | $1,031,921 |
| AG1-011 | 15.9 MW | 10.3% | $2,159,901 |
| AG1-359 | 7.4 MW | 4.8% | $1,011,677 |
| System Reinforcement | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| TO | RTEP ID / TO ID | Title | Total Cost ($USD) | Allocated Cost ($USD) | Time Estimate | ||||
| Dominion | (Pending) / dom-164 | Rebuild 7.0 miles of 230 kV Line 208 from Iron Bridge to Southwest with (2) 768.2 ACSS | $20,355,000 | $2,020,026 | 42 to 48 Months | ||||
Contributor
Description: Rebuild 7.08 miles of 230 kV Line 208 from Iron Bridge to Southwest with (2) 768.2 ACSS at 250 degrees C.
| Flowgates Addressed by this Reinforcement | |
|---|---|
| Facility | Contingency |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line | (Any) |
| New Ratings | |||
|---|---|---|---|
| Facility | Rating Set | Rating Type | Rating Value |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line | (All) | A | 1046.0 MVA |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line | (All) | B | 1046.0 MVA |
| 6IRON208-6SOUWEST 230.0 kV Ckt 1 line | (All) | C | 1203.0 MVA |
| Cost Allocation | |||
|---|---|---|---|
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
| AE2-123 | 9.7 MW | 6.3% | $1,273,072 |
| AE2-124 | 8.8 MW | 5.7% | $1,154,958 |
| AE2-270 | 14.9 MW | 9.6% | $1,957,155 |
| AF1-123 | 15.4 MW | 9.9% | $2,020,026 |
| AF1-124 | 15.4 MW | 9.9% | $2,020,026 |
| AF1-125 | 15.4 MW | 9.9% | $2,020,026 |
| AF1-128 | 37.7 MW | 24.4% | $4,964,237 |
| AF1-201 | 6.7 MW | 4.3% | $880,062 |
| AF2-065 | 7.6 MW | 4.9% | $998,175 |
| AG1-011 | 15.9 MW | 10.3% | $2,089,210 |
| AG1-359 | 7.4 MW | 4.8% | $978,051 |
| System Reinforcement | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| TO | RTEP ID / TO ID | Title | Total Cost ($USD) | Allocated Cost ($USD) | Time Estimate | ||||
| Dominion | n6607 / dom-116 | Rebuild 5.88 miles of 230 kV Line 2026 from Landstown to Lynnhaven with (2) 768.2 ACSS/TW (20/7) "MAUMEE" | $16,905,000 | $1,426,462 | Dec 31 2026 | ||||
Contributor
Description: Rebuild 5.88 miles of 230 kV Line 2026 from Landstown to Lynnhaven with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor at 250 degrees C and circuit breaker lead.
| Flowgates Addressed by this Reinforcement | |
|---|---|
| Facility | Contingency |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line | (Any) |
| New Ratings | |||
|---|---|---|---|
| Facility | Rating Set | Rating Type | Rating Value |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line | (All) | A | 877.0 MVA |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line | (All) | B | 957.0 MVA |
| 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line | (All) | C | 1164.0 MVA |
| Cost Allocation | |||
|---|---|---|---|
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
| AE2-123 | 227.1 MW | 33.9% | $5,728,728 |
| AE2-124 | 227.1 MW | 33.9% | $5,728,728 |
| AE2-147 | 9.3 MW | 1.4% | $234,666 |
| AF1-123 | 56.5 MW | 8.4% | $1,426,462 |
| AF1-124 | 56.5 MW | 8.4% | $1,426,462 |
| AF1-125 | 56.5 MW | 8.4% | $1,426,462 |
| AF2-081 | 12.9 MW | 1.9% | $326,141 |
| AG1-359 | 24.1 MW | 3.6% | $607,351 |
| System Reinforcement | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| TO | RTEP ID / TO ID | Title | Total Cost ($USD) | Allocated Cost ($USD) | Time Estimate | ||||
| Dominion | n7568 / dom-369 | Rebuild 6.47 miles of 230 kV Line 2028 from Mt Eagle to Charlottesville with 2-768.2 ACSS 250 C. Replace Wave Trap and CB Switch at Charlottesville terminal | $19,351,250 | $1,291,232 | 36 to 40 Months | ||||
Contributor
| Flowgates Addressed by this Reinforcement | |
|---|---|
| Facility | Contingency |
| 6CHARLVL-6MTEAGLE 230.0 kV Ckt 1 line | (Any) |
| New Ratings | |||
|---|---|---|---|
| Facility | Rating Set | Rating Type | Rating Value |
| 6CHARLVL-6MTEAGLE 230.0 kV Ckt 1 line | (All) | A | 1168.0 MVA |
| 6CHARLVL-6MTEAGLE 230.0 kV Ckt 1 line | (All) | B | 1292.0 MVA |
| 6CHARLVL-6MTEAGLE 230.0 kV Ckt 1 line | (All) | C | 1349.0 MVA |
| Cost Allocation | |||
|---|---|---|---|
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
| AE2-123 | 33.0 MW | 6.1% | $1,172,074 |
| AE2-124 | 33.1 MW | 6.1% | $1,172,429 |
| AF1-123 | 36.4 MW | 6.7% | $1,291,232 |
| AF1-124 | 36.4 MW | 6.7% | $1,291,232 |
| AF1-125 | 36.4 MW | 6.7% | $1,291,232 |
| AF1-293 | 23.0 MW | 4.2% | $816,728 |
| AF1-323 | 11.0 MW | 2.0% | $388,469 |
| AF2-042 | 21.3 MW | 3.9% | $755,837 |
| AF2-171 | 23.0 MW | 4.2% | $817,154 |
| AF2-222 | 21.2 MW | 3.9% | $750,731 |
| AF2-397 | 26.6 MW | 4.9% | $944,398 |
| AG1-011 | 8.2 MW | 1.5% | $290,447 |
| AG1-030 | 21.5 MW | 3.9% | $761,547 |
| AG1-098 | 13.9 MW | 2.5% | $492,200 |
| AG1-151 | 7.5 MW | 1.4% | $267,751 |
| AG1-181 | 19.7 MW | 3.6% | $699,485 |
| AG1-184 | 10.7 MW | 2.0% | $379,461 |
| AG1-185 | 9.5 MW | 1.7% | $338,430 |
| AG1-195 | 9.0 MW | 1.7% | $319,528 |
| AG1-196 | 11.1 MW | 2.0% | $395,065 |
| AG1-284 | 19.9 MW | 3.6% | $705,479 |
| AG1-285 | 12.4 MW | 2.3% | $438,544 |
| AG1-427 | 11.4 MW | 2.1% | $404,321 |
| AG1-432 | 39.2 MW | 7.2% | $1,391,878 |
| AG1-449 | 8.0 MW | 1.5% | $284,064 |
| AG1-505 | 13.6 MW | 2.5% | $483,157 |
| AG1-506 | 13.6 MW | 2.5% | $483,157 |
| AG1-537 | 6.7 MW | 1.2% | $236,897 |
| AG1-556 | 8.1 MW | 1.5% | $288,320 |
| System Reinforcement | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| TO | RTEP ID / TO ID | Title | Total Cost ($USD) | Allocated Cost ($USD) | Time Estimate | ||||
| Dominion | (Pending) / TC1-PH1-DOM-019 | Wreck and rebuild 5.86 miles of 230 kV line 2028 between AF2-397 Tap to Grape Vine (Cunningham) | $16,847,500 | $1,078,999 | 42 to 48 Months | ||||
Contributor
Description: Wreck and rebuild 5.86 miles of 230 kV line 2028 between AF2-397 Tap to Grape Vine (Cunningham) with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 degrees C.
| Flowgates Addressed by this Reinforcement | |
|---|---|
| Facility | Contingency |
| 6CUNNING-AF2-397 TP 230.0 kV Ckt 1 line | (Any) |
| New Ratings | |||
|---|---|---|---|
| Facility | Rating Set | Rating Type | Rating Value |
| 6CUNNING-AF2-397 TP 230.0 kV Ckt 1 line | (All) | A | 1175.0 MVA |
| 6CUNNING-AF2-397 TP 230.0 kV Ckt 1 line | (All) | B | 1196.0 MVA |
| 6CUNNING-AF2-397 TP 230.0 kV Ckt 1 line | (All) | C | 1361.0 MVA |
| Cost Allocation | |||
|---|---|---|---|
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
| AE2-123 | 33.0 MW | 5.8% | $979,427 |
| AE2-124 | 33.1 MW | 5.8% | $979,723 |
| AF1-123 | 36.4 MW | 6.4% | $1,078,999 |
| AF1-124 | 36.4 MW | 6.4% | $1,078,999 |
| AF1-125 | 36.4 MW | 6.4% | $1,078,999 |
| AF1-293 | 23.0 MW | 4.1% | $682,487 |
| AF1-323 | 11.0 MW | 1.9% | $324,618 |
| AF2-042 | 21.3 MW | 3.7% | $631,604 |
| AF2-171 | 23.0 MW | 4.1% | $682,843 |
| AF2-222 | 21.2 MW | 3.7% | $627,337 |
| AF2-397 | 49.5 MW | 8.7% | $1,466,087 |
| AG1-011 | 8.2 MW | 1.4% | $242,708 |
| AG1-030 | 21.5 MW | 3.8% | $636,375 |
| AG1-098 | 13.9 MW | 2.4% | $411,300 |
| AG1-151 | 7.5 MW | 1.3% | $223,742 |
| AG1-181 | 19.7 MW | 3.5% | $584,515 |
| AG1-184 | 10.7 MW | 1.9% | $317,091 |
| AG1-185 | 9.5 MW | 1.7% | $282,804 |
| AG1-195 | 9.0 MW | 1.6% | $267,009 |
| AG1-196 | 11.1 MW | 2.0% | $330,130 |
| AG1-284 | 19.9 MW | 3.5% | $589,523 |
| AG1-285 | 12.4 MW | 2.2% | $366,463 |
| AG1-427 | 11.4 MW | 2.0% | $337,865 |
| AG1-432 | 39.2 MW | 6.9% | $1,163,102 |
| AG1-449 | 8.0 MW | 1.4% | $237,374 |
| AG1-505 | 13.6 MW | 2.4% | $403,743 |
| AG1-506 | 13.6 MW | 2.4% | $403,743 |
| AG1-537 | 6.7 MW | 1.2% | $197,960 |
| AG1-556 | 8.1 MW | 1.4% | $240,930 |
| System Reinforcement | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| TO | RTEP ID / TO ID | Title | Total Cost ($USD) | Allocated Cost ($USD) | Time Estimate | ||||
| Dominion | n6161 / dom-039 | Replace Circuit Breaker at Clifton | $2,500,000 | $866,285 | 42 to 48 Months | ||||
Contributor
| Flowgates Addressed by this Reinforcement | |
|---|---|
| Facility | Contingency |
| 8CLIFTON-8OX 500.0 kV Ckt 1 line | (Any) |
| New Ratings | |||
|---|---|---|---|
| Facility | Rating Set | Rating Type | Rating Value |
| 8CLIFTON-8OX 500.0 kV Ckt 1 line | (All) | A | 2858.0 MVA |
| 8CLIFTON-8OX 500.0 kV Ckt 1 line | (All) | B | 3118.0 MVA |
| 8CLIFTON-8OX 500.0 kV Ckt 1 line | (All) | C | 3794.0 MVA |
| Cost Allocation | |||
|---|---|---|---|
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
| AF1-123 | 71.7 MW | 34.7% | $866,285 |
| AF1-124 | 71.7 MW | 34.7% | $866,285 |
| AF1-125 | 29.0 MW | 14.0% | $350,063 |
| AG1-178 | 34.6 MW | 16.7% | $417,367 |
| System Reinforcement | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| TO | RTEP ID / TO ID | Title | Total Cost ($USD) | Allocated Cost ($USD) | Time Estimate | ||||
| Dominion | n7566 / dom-265 | Rebuild 5 miles of 230 kV Line 2028 from Fork Union to AF2-397 Tap with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor at 250 degrees C. | $12,500,000 | $835,009 | 36 to 42 Months | ||||
Contributor
| Flowgates Addressed by this Reinforcement | |
|---|---|
| Facility | Contingency |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line | (Any) |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line | (Any) |
| New Ratings | |||
|---|---|---|---|
| Facility | Rating Set | Rating Type | Rating Value |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line | (All) | A | 1174.0 MVA |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line | (All) | B | 1196.0 MVA |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line | (All) | C | 1360.0 MVA |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line | (All) | A | 1174.0 MVA |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line | (All) | B | 1196.0 MVA |
| 6FORK UNION-AF2-397 TP 230.0 kV Ckt 1 line | (All) | C | 1360.0 MVA |
| Cost Allocation | |||
|---|---|---|---|
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
| AE2-123 | 33.0 MW | 6.1% | $757,952 |
| AE2-124 | 33.1 MW | 6.1% | $758,182 |
| AF1-123 | 36.4 MW | 6.7% | $835,009 |
| AF1-124 | 36.4 MW | 6.7% | $835,009 |
| AF1-125 | 36.4 MW | 6.7% | $835,009 |
| AF1-293 | 23.0 MW | 4.2% | $528,159 |
| AF1-323 | 11.0 MW | 2.0% | $251,214 |
| AF2-042 | 21.3 MW | 3.9% | $488,782 |
| AF2-171 | 23.0 MW | 4.2% | $528,434 |
| AF2-222 | 21.2 MW | 3.9% | $485,479 |
| AF2-397 | 26.0 MW | 4.8% | $596,730 |
| AG1-011 | 8.2 MW | 1.5% | $187,825 |
| AG1-030 | 21.5 MW | 3.9% | $492,474 |
| AG1-098 | 13.9 MW | 2.5% | $318,294 |
| AG1-151 | 7.5 MW | 1.4% | $173,148 |
| AG1-181 | 19.7 MW | 3.6% | $452,341 |
| AG1-184 | 10.7 MW | 2.0% | $245,389 |
| AG1-185 | 9.5 MW | 1.8% | $218,854 |
| AG1-195 | 9.0 MW | 1.7% | $206,631 |
| AG1-196 | 11.1 MW | 2.0% | $255,479 |
| AG1-284 | 19.9 MW | 3.6% | $456,216 |
| AG1-285 | 12.4 MW | 2.3% | $283,596 |
| AG1-427 | 11.4 MW | 2.1% | $261,465 |
| AG1-432 | 39.2 MW | 7.2% | $900,094 |
| AG1-449 | 8.0 MW | 1.5% | $183,697 |
| AG1-505 | 13.6 MW | 2.5% | $312,446 |
| AG1-506 | 13.6 MW | 2.5% | $312,446 |
| AG1-537 | 6.7 MW | 1.2% | $153,196 |
| AG1-556 | 8.1 MW | 1.5% | $186,449 |
| System Reinforcement | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| TO | RTEP ID / TO ID | Title | Total Cost ($USD) | Allocated Cost ($USD) | Time Estimate | ||||
| Dominion | n8239 / dom-300 | Rebuild 9.46 miles of 230 kV Line 217 from Chesterfield to Varina with 2-768.2 ACSS 250 C | $14,190,000 | $739,375 | Dec 01 2024 | ||||
Contributor
| Flowgates Addressed by this Reinforcement | |
|---|---|
| Facility | Contingency |
| 6VARINA-6CHESTF B 230.0 kV Ckt 1 line | (Any) |
| New Ratings | |||
|---|---|---|---|
| Facility | Rating Set | Rating Type | Rating Value |
| 6VARINA-6CHESTF B 230.0 kV Ckt 1 line | (All) | A | 1174.0 MVA |
| 6VARINA-6CHESTF B 230.0 kV Ckt 1 line | (All) | B | 1195.0 MVA |
| 6VARINA-6CHESTF B 230.0 kV Ckt 1 line | (All) | C | 1360.0 MVA |
| Cost Allocation | |||
|---|---|---|---|
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
| AE2-123 | 46.4 MW | 16.3% | $2,316,119 |
| AE2-124 | 46.3 MW | 16.3% | $2,310,583 |
| AE2-270 | 17.7 MW | 6.2% | $884,497 |
| AE2-313 | 12.2 MW | 4.3% | $610,610 |
| AF1-123 | 14.8 MW | 5.2% | $739,375 |
| AF1-124 | 14.8 MW | 5.2% | $739,375 |
| AF1-125 | 14.8 MW | 5.2% | $739,375 |
| AF1-128 | 16.1 MW | 5.6% | $800,565 |
| AF2-042 | 16.8 MW | 5.9% | $837,569 |
| AF2-065 | 17.7 MW | 6.2% | $884,497 |
| AG1-011 | 18.9 MW | 6.7% | $944,540 |
| AG1-075 | 17.9 MW | 6.3% | $890,830 |
| AG1-178 | 18.3 MW | 6.4% | $913,471 |
| AG1-184 | 11.6 MW | 4.1% | $578,593 |
| System Reinforcement | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| TO | RTEP ID / TO ID | Title | Total Cost ($USD) | Allocated Cost ($USD) | Time Estimate | ||||
| Dominion | (Pending) / dom-122 | Add additional 138/115 kV transformer at Altavista substation | $6,500,000 | $679,790 | 42 to 44 Months | ||||
Contributor
Description: Add additional 138/115 kV transformer at Altavista substation
| Flowgates Addressed by this Reinforcement | |
|---|---|
| Facility | Contingency |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 1 transformer | (Any) |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 2 transformer | (Any) |
| New Ratings | |||
|---|---|---|---|
| Facility | Rating Set | Rating Type | Rating Value |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 1 transformer | (All) | A | 135.5 MVA |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 1 transformer | (All) | B | 138.8 MVA |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 1 transformer | (All) | C | 146.6 MVA |
| Cost Allocation | |||
|---|---|---|---|
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
| AE2-123 | 15.6 MW | 9.5% | $616,803 |
| AE2-124 | 15.6 MW | 9.5% | $617,199 |
| AF1-123 | 17.2 MW | 10.5% | $679,790 |
| AF1-124 | 17.2 MW | 10.5% | $679,790 |
| AF1-125 | 17.2 MW | 10.5% | $679,790 |
| AF2-403 | 10.6 MW | 6.4% | $418,333 |
| AF2-404 | 10.6 MW | 6.4% | $418,333 |
| AG1-539 | 60.3 MW | 36.8% | $2,389,962 |
| System Reinforcement | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| TO | RTEP ID / TO ID | Title | Total Cost ($USD) | Allocated Cost ($USD) | Time Estimate | ||||
| Dominion | n6606 / dom-100 | Rebuild 1.76 miles of 230 kV Line 2240 from Pocaty to Fentress | $5,060,000 | $637,608 | Dec 31 2026 | ||||
Contributor
Description: Rebuild 1.76 miles of 230 kV Line 2240 from Pocaty to Fentress with (2) 768 ACSS/TW (20/7) “MAUMEE” conductor at 250 degrees C. Replace the line lead at Fentress.
| Flowgates Addressed by this Reinforcement | |
|---|---|
| Facility | Contingency |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line | (Any) |
| New Ratings | |||
|---|---|---|---|
| Facility | Rating Set | Rating Type | Rating Value |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line | (All) | A | 877.0 MVA |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line | (All) | B | 957.0 MVA |
| 6FENTRES-6POCATY 230.0 kV Ckt 1 line | (All) | C | 1164.0 MVA |
| Cost Allocation | |||
|---|---|---|---|
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
| AE2-123 | 424.6 MW | 26.3% | $1,333,126 |
| AE2-124 | 543.4 MW | 33.7% | $1,706,161 |
| AE2-156 | 8.7 MW | 0.5% | $27,161 |
| AF1-123 | 203.1 MW | 12.6% | $637,608 |
| AF1-124 | 203.1 MW | 12.6% | $637,608 |
| AF1-125 | 203.1 MW | 12.6% | $637,608 |
| AG1-359 | 16.8 MW | 1.0% | $52,689 |
| AG1-364 | 8.9 MW | 0.6% | $28,040 |
| System Reinforcement | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| TO | RTEP ID / TO ID | Title | Total Cost ($USD) | Allocated Cost ($USD) | Time Estimate | ||||
| Dominion | (Pending) / TC1-PH1-DOM-048 | Replace Circuit Breaker at Fentress for increased rating on Line 2128 6FENTRES 230 KV to 6THRASHER 230 KV ckt 1 | $1,500,000 | $413,295 | 42 to 48 Months | ||||
Contributor
Description: Replace Circuit Breaker at Fentress.
| Flowgates Addressed by this Reinforcement | |
|---|---|
| Facility | Contingency |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line | (Any) |
| New Ratings | |||
|---|---|---|---|
| Facility | Rating Set | Rating Type | Rating Value |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line | (All) | A | 1315.0 MVA |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line | (All) | B | 1435.0 MVA |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line | (All) | C | 1745.0 MVA |
| Cost Allocation | |||
|---|---|---|---|
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
| AE2-123 | 82.2 MW | 5.7% | $84,844 |
| AE2-124 | 97.3 MW | 6.7% | $100,423 |
| AF1-123 | 400.3 MW | 27.6% | $413,295 |
| AF1-124 | 400.3 MW | 27.6% | $413,295 |
| AF1-125 | 400.3 MW | 27.6% | $413,295 |
| AG1-359 | 72.5 MW | 5.0% | $74,850 |
| System Reinforcement | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| TO | RTEP ID / TO ID | Title | Total Cost ($USD) | Allocated Cost ($USD) | Time Estimate | ||||
| Dominion | (Pending) / TC1-PH1-DOM-081 | Replace Circuit Breaker and Relay at Surry for increased rating on Line 567 8SURRY 500 KV to 8CHCKAHM 500 KV ckt 1 | $2,650,000 | $403,172 | 42 to 48 Months | ||||
Contributor
Description: Replace Circuit Breaker and Relay at Surry
| Flowgates Addressed by this Reinforcement | |
|---|---|
| Facility | Contingency |
| 8CHCKAHM-8SURRY 500.0 kV Ckt 1 line | (Any) |
| New Ratings | |||
|---|---|---|---|
| Facility | Rating Set | Rating Type | Rating Value |
| 8CHCKAHM-8SURRY 500.0 kV Ckt 1 line | (All) | A | 2858.0 MVA |
| 8CHCKAHM-8SURRY 500.0 kV Ckt 1 line | (All) | B | 3118.0 MVA |
| 8CHCKAHM-8SURRY 500.0 kV Ckt 1 line | (All) | C | 3794.0 MVA |
| Cost Allocation | |||
|---|---|---|---|
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
| AE2-123 | 231.7 MW | 13.3% | $352,040 |
| AE2-124 | 231.9 MW | 13.3% | $352,359 |
| AE2-147 | 40.6 MW | 2.3% | $61,696 |
| AE2-156 | 28.3 MW | 1.6% | $42,938 |
| AE2-313 | 73.2 MW | 4.2% | $111,267 |
| AF1-123 | 265.3 MW | 15.2% | $403,172 |
| AF1-124 | 265.3 MW | 15.2% | $403,172 |
| AF1-125 | 265.3 MW | 15.2% | $403,172 |
| AF2-042 | 58.0 MW | 3.3% | $88,087 |
| AF2-047 | 36.7 MW | 2.1% | $55,815 |
| AG1-178 | 83.2 MW | 4.8% | $126,427 |
| AG1-184 | 44.8 MW | 2.6% | $68,112 |
| AG1-359 | 37.2 MW | 2.1% | $56,604 |
| AG1-364 | 27.8 MW | 1.6% | $42,275 |
| AG1-439 | 26.7 MW | 1.5% | $40,564 |
| AG1-449 | 27.8 MW | 1.6% | $42,300 |
| System Reinforcement | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| TO | RTEP ID / TO ID | Title | Total Cost ($USD) | Allocated Cost ($USD) | Time Estimate | ||||
| Dominion | n7567 / dom-276 | Rebuild 1.63 miles of 230 kV Line 2028 from Fork Union to Bremo Dist with 2-795 ACSR (26/7) 150 C | $4,686,250 | $321,565 | 30 to 36 Months | ||||
Contributor
| Flowgates Addressed by this Reinforcement | |
|---|---|
| Facility | Contingency |
| 6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line | (Any) |
| New Ratings | |||
|---|---|---|---|
| Facility | Rating Set | Rating Type | Rating Value |
| 6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line | (All) | A | 1174.0 MVA |
| 6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line | (All) | B | 1225.0 MVA |
| 6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line | (All) | C | 1360.0 MVA |
| Cost Allocation | |||
|---|---|---|---|
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
| AE2-123 | 36.5 MW | 6.2% | $292,659 |
| AE2-124 | 36.5 MW | 6.2% | $292,659 |
| AF1-123 | 40.2 MW | 6.9% | $321,565 |
| AF1-124 | 40.2 MW | 6.9% | $321,565 |
| AF1-125 | 41.3 MW | 7.1% | $330,693 |
| AF1-293 | 8.4 MW | 1.4% | $66,875 |
| AF1-294 | 7.0 MW | 1.2% | $56,450 |
| AF2-042 | 23.8 MW | 4.1% | $190,537 |
| AF2-171 | 25.7 MW | 4.4% | $205,694 |
| AF2-222 | 23.6 MW | 4.0% | $188,711 |
| AF2-397 | 23.9 MW | 4.1% | $191,530 |
| AG1-011 | 9.4 MW | 1.6% | $75,347 |
| AG1-030 | 23.9 MW | 4.1% | $191,602 |
| AG1-098 | 15.5 MW | 2.6% | $124,062 |
| AG1-151 | 8.0 MW | 1.4% | $63,897 |
| AG1-181 | 21.9 MW | 3.7% | $175,724 |
| AG1-184 | 10.5 MW | 1.8% | $83,914 |
| AG1-185 | 8.2 MW | 1.4% | $66,059 |
| AG1-195 | 13.6 MW | 2.3% | $108,496 |
| AG1-196 | 15.3 MW | 2.6% | $122,589 |
| AG1-285 | 13.7 MW | 2.3% | $110,002 |
| AG1-359 | 7.3 MW | 1.2% | $58,292 |
| AG1-426 | 11.8 MW | 2.0% | $94,163 |
| AG1-427 | 12.7 MW | 2.2% | $101,394 |
| AG1-432 | 43.8 MW | 7.5% | $350,839 |
| AG1-449 | 7.7 MW | 1.3% | $61,655 |
| AG1-451 | 7.3 MW | 1.2% | $58,476 |
| AG1-505 | 14.9 MW | 2.6% | $119,618 |
| AG1-506 | 14.9 MW | 2.6% | $119,618 |
| AG1-537 | 9.0 MW | 1.5% | $71,744 |
| AG1-556 | 8.7 MW | 1.5% | $69,822 |
| System Reinforcement | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| TO | RTEP ID / TO ID | Title | Total Cost ($USD) | Allocated Cost ($USD) | Time Estimate | ||||
| Dominion | n8238 / dom-294 | Rebuild 1.38 mi miles of 230 kV Line 217 from Varina to Charles City with 2-768.2 ACSS 250 C | $3,967,500 | $206,728 | Dec 01 2024 | ||||
Contributor
| Flowgates Addressed by this Reinforcement | |
|---|---|
| Facility | Contingency |
| 6CHARCTY-6VARINA 230.0 kV Ckt 1 line | (Any) |
| New Ratings | |||
|---|---|---|---|
| Facility | Rating Set | Rating Type | Rating Value |
| 6CHARCTY-6VARINA 230.0 kV Ckt 1 line | (All) | A | 1315.0 MVA |
| 6CHARCTY-6VARINA 230.0 kV Ckt 1 line | (All) | B | 1434.0 MVA |
| 6CHARCTY-6VARINA 230.0 kV Ckt 1 line | (All) | C | 1745.0 MVA |
| Cost Allocation | |||
|---|---|---|---|
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
| AE2-123 | 46.4 MW | 16.3% | $647,583 |
| AE2-124 | 46.3 MW | 16.3% | $646,035 |
| AE2-270 | 17.7 MW | 6.2% | $247,304 |
| AE2-313 | 12.2 MW | 4.3% | $170,726 |
| AF1-123 | 14.8 MW | 5.2% | $206,728 |
| AF1-124 | 14.8 MW | 5.2% | $206,728 |
| AF1-125 | 14.8 MW | 5.2% | $206,728 |
| AF1-128 | 16.1 MW | 5.6% | $223,837 |
| AF2-042 | 16.8 MW | 5.9% | $234,183 |
| AF2-065 | 17.7 MW | 6.2% | $247,304 |
| AG1-011 | 18.9 MW | 6.7% | $264,092 |
| AG1-075 | 17.9 MW | 6.3% | $249,075 |
| AG1-178 | 18.3 MW | 6.4% | $255,405 |
| AG1-184 | 11.6 MW | 4.1% | $161,774 |
| System Reinforcement | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| TO | RTEP ID / TO ID | Title | Total Cost ($USD) | Allocated Cost ($USD) | Time Estimate | ||||
| Dominion | (Pending) / TC1-PH1-DOM-044 | Replace Circuit Breaker Switch at Fentress for increased rating on Line 2128 6FENTRES 230 KV to 6THRASHER 230 KV ckt 1 | $550,000 | $151,541 | 12 to 18 Months | ||||
Contributor
Description: Replace Circuit Breaker Switch at Fentress.
| Flowgates Addressed by this Reinforcement | |
|---|---|
| Facility | Contingency |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line | (Any) |
| New Ratings | |||
|---|---|---|---|
| Facility | Rating Set | Rating Type | Rating Value |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line | (All) | A | 957.0 MVA |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line | (All) | B | 1052.0 MVA |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line | (All) | C | 1339.0 MVA |
| Cost Allocation | |||
|---|---|---|---|
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
| AE2-123 | 82.2 MW | 5.7% | $31,109 |
| AE2-124 | 97.3 MW | 6.7% | $36,822 |
| AF1-123 | 400.3 MW | 27.6% | $151,541 |
| AF1-124 | 400.3 MW | 27.6% | $151,541 |
| AF1-125 | 400.3 MW | 27.6% | $151,541 |
| AG1-359 | 72.5 MW | 5.0% | $27,445 |
| System Reinforcement | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| TO | RTEP ID / TO ID | Title | Total Cost ($USD) | Allocated Cost ($USD) | Time Estimate | ||||
| Dominion | (Pending) / TC1-PH1-DOM-082 | Replace Circuit Breaker Switch at Surry for increased rating on 8SURRY 500 KV to 8CHCKAHM 500 KV ckt 1 | $900,000 | $136,926 | 12 to 18 Months | ||||
Contributor
Description: Replace Circuit Breaker Switch at Surry
| Flowgates Addressed by this Reinforcement | |
|---|---|
| Facility | Contingency |
| 8CHCKAHM-8SURRY 500.0 kV Ckt 1 line | (Any) |
| New Ratings | |||
|---|---|---|---|
| Facility | Rating Set | Rating Type | Rating Value |
| 8CHCKAHM-8SURRY 500.0 kV Ckt 1 line | (All) | A | 3426.0 MVA |
| 8CHCKAHM-8SURRY 500.0 kV Ckt 1 line | (All) | B | 3426.0 MVA |
| 8CHCKAHM-8SURRY 500.0 kV Ckt 1 line | (All) | C | 3940.0 MVA |
| Cost Allocation | |||
|---|---|---|---|
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
| AE2-123 | 231.7 MW | 13.3% | $119,561 |
| AE2-124 | 231.9 MW | 13.3% | $119,669 |
| AE2-147 | 40.6 MW | 2.3% | $20,953 |
| AE2-156 | 28.3 MW | 1.6% | $14,583 |
| AE2-313 | 73.2 MW | 4.2% | $37,789 |
| AF1-123 | 265.3 MW | 15.2% | $136,926 |
| AF1-124 | 265.3 MW | 15.2% | $136,926 |
| AF1-125 | 265.3 MW | 15.2% | $136,926 |
| AF2-042 | 58.0 MW | 3.3% | $29,916 |
| AF2-047 | 36.7 MW | 2.1% | $18,956 |
| AG1-178 | 83.2 MW | 4.8% | $42,937 |
| AG1-184 | 44.8 MW | 2.6% | $23,132 |
| AG1-359 | 37.2 MW | 2.1% | $19,224 |
| AG1-364 | 27.8 MW | 1.6% | $14,358 |
| AG1-439 | 26.7 MW | 1.5% | $13,777 |
| AG1-449 | 27.8 MW | 1.6% | $14,366 |
| System Reinforcement | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| TO | RTEP ID / TO ID | Title | Total Cost ($USD) | Allocated Cost ($USD) | Time Estimate | ||||
| Dominion | n7789 / dom-363 | Rebuild 0.16 miles of Line 2193 from Bremo to Bremo Dist | $1,948,000 | $133,670 | 30 to 36 Months | ||||
Contributor
Description: Rebuild 0.16 miles of Line 2193 from Bremo to Bremo Dist with 2-795 ACSR 150 C. Replace Breaker, Breaker Switch, Breaker Lead, Line Lead at Bremo terminal
| Flowgates Addressed by this Reinforcement | |
|---|---|
| Facility | Contingency |
| 6BREMODIST-6BREMO 230.0 kV Ckt 1 line | (Any) |
| New Ratings | |||
|---|---|---|---|
| Facility | Rating Set | Rating Type | Rating Value |
| 6BREMODIST-6BREMO 230.0 kV Ckt 1 line | (All) | A | 1225.0 MVA |
| 6BREMODIST-6BREMO 230.0 kV Ckt 1 line | (All) | B | 1225.0 MVA |
| 6BREMODIST-6BREMO 230.0 kV Ckt 1 line | (All) | C | 1409.0 MVA |
| Cost Allocation | |||
|---|---|---|---|
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
| AE2-123 | 36.5 MW | 6.2% | $121,654 |
| AE2-124 | 36.5 MW | 6.2% | $121,654 |
| AF1-123 | 40.2 MW | 6.9% | $133,670 |
| AF1-124 | 40.2 MW | 6.9% | $133,670 |
| AF1-125 | 41.3 MW | 7.1% | $137,464 |
| AF1-293 | 8.4 MW | 1.4% | $27,799 |
| AF1-294 | 7.0 MW | 1.2% | $23,465 |
| AF2-042 | 23.8 MW | 4.1% | $79,203 |
| AF2-171 | 25.7 MW | 4.4% | $85,504 |
| AF2-222 | 23.6 MW | 4.0% | $78,444 |
| AF2-397 | 23.9 MW | 4.1% | $79,616 |
| AG1-011 | 9.4 MW | 1.6% | $31,320 |
| AG1-030 | 23.9 MW | 4.1% | $79,646 |
| AG1-098 | 15.5 MW | 2.6% | $51,571 |
| AG1-151 | 8.0 MW | 1.4% | $26,561 |
| AG1-181 | 21.9 MW | 3.7% | $73,046 |
| AG1-184 | 10.5 MW | 1.8% | $34,882 |
| AG1-185 | 8.2 MW | 1.4% | $27,459 |
| AG1-195 | 13.6 MW | 2.3% | $45,100 |
| AG1-196 | 15.3 MW | 2.6% | $50,958 |
| AG1-285 | 13.7 MW | 2.3% | $45,726 |
| AG1-359 | 7.3 MW | 1.2% | $24,231 |
| AG1-426 | 11.8 MW | 2.0% | $39,142 |
| AG1-427 | 12.7 MW | 2.2% | $42,148 |
| AG1-432 | 43.8 MW | 7.5% | $145,838 |
| AG1-449 | 7.7 MW | 1.3% | $25,629 |
| AG1-451 | 7.3 MW | 1.2% | $24,307 |
| AG1-505 | 14.9 MW | 2.6% | $49,723 |
| AG1-506 | 14.9 MW | 2.6% | $49,723 |
| AG1-537 | 9.0 MW | 1.5% | $29,823 |
| AG1-556 | 8.7 MW | 1.5% | $29,024 |
| System Reinforcement | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| TO | RTEP ID / TO ID | Title | Total Cost ($USD) | Allocated Cost ($USD) | Time Estimate | ||||
| Dominion | (Pending) / TC1-PH1-DOM-047 | Replace Wave Trap at Fentress and Thrasher for increased rating on Line 2128 6FENTRES 230 KV to 6THRASHER 230 KV ckt 1 | $400,000 | $110,212 | 16 to 18 Months | ||||
Contributor
Description: Replace Wave Trap at Fentress and Thrasher.
| Flowgates Addressed by this Reinforcement | |
|---|---|
| Facility | Contingency |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line | (Any) |
| New Ratings | |||
|---|---|---|---|
| Facility | Rating Set | Rating Type | Rating Value |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line | (All) | A | 1168.0 MVA |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line | (All) | B | 1292.0 MVA |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line | (All) | C | 1349.0 MVA |
| Cost Allocation | |||
|---|---|---|---|
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
| AE2-123 | 82.2 MW | 5.7% | $22,625 |
| AE2-124 | 97.3 MW | 6.7% | $26,779 |
| AF1-123 | 400.3 MW | 27.6% | $110,212 |
| AF1-124 | 400.3 MW | 27.6% | $110,212 |
| AF1-125 | 400.3 MW | 27.6% | $110,212 |
| AG1-359 | 72.5 MW | 5.0% | $19,960 |
| System Reinforcement | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| TO | RTEP ID / TO ID | Title | Total Cost ($USD) | Allocated Cost ($USD) | Time Estimate | ||||
| Dominion | (Pending) / TC1-PH1-DOM-057 | Replace Wave Trap at Yadkin and Thrasher for increased rating on Line 2015 6THRASHER 230 KV to 6YADKIN 230 KV ckt 1 | $400,000 | $85,809 | 16 to 18 Months | ||||
Contributor
Description: Replace Wave Trap at Yadkin and Thrasher.
| Flowgates Addressed by this Reinforcement | |
|---|---|
| Facility | Contingency |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line | (Any) |
| New Ratings | |||
|---|---|---|---|
| Facility | Rating Set | Rating Type | Rating Value |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line | (All) | A | 1220.0 MVA |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line | (All) | B | 1315.0 MVA |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line | (All) | C | 1447.0 MVA |
| Cost Allocation | |||
|---|---|---|---|
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
| AE2-123 | 176.5 MW | 15.1% | $60,436 |
| AE2-124 | 194.5 MW | 16.6% | $66,596 |
| AF1-123 | 250.6 MW | 21.5% | $85,809 |
| AF1-124 | 250.6 MW | 21.5% | $85,809 |
| AF1-125 | 250.6 MW | 21.5% | $85,809 |
| AG1-359 | 45.4 MW | 3.9% | $15,542 |
| System Reinforcement | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| TO | RTEP ID / TO ID | Title | Total Cost ($USD) | Allocated Cost ($USD) | Time Estimate | ||||
| Dominion | (Pending) / TC1-PH1-DOM-049 | Replace Circuit Breaker Switch at Thrasher for increased rating on Line 2128 6FENTRES 230 KV to 6THRASHER 230 KV ckt 1 | $275,000 | $75,771 | 12 to 18 Months | ||||
Contributor
Description: Replace Circuit Breaker Switch at Thrasher.
| Flowgates Addressed by this Reinforcement | |
|---|---|
| Facility | Contingency |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line | (Any) |
| New Ratings | |||
|---|---|---|---|
| Facility | Rating Set | Rating Type | Rating Value |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line | (All) | A | 1594.0 MVA |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line | (All) | B | 1753.0 MVA |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line | (All) | C | 2231.0 MVA |
| Cost Allocation | |||
|---|---|---|---|
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
| AE2-123 | 82.2 MW | 5.7% | $15,555 |
| AE2-124 | 97.3 MW | 6.7% | $18,411 |
| AF1-123 | 400.3 MW | 27.6% | $75,771 |
| AF1-124 | 400.3 MW | 27.6% | $75,771 |
| AF1-125 | 400.3 MW | 27.6% | $75,771 |
| AG1-359 | 72.5 MW | 5.0% | $13,722 |
| System Reinforcement | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| TO | RTEP ID / TO ID | Title | Total Cost ($USD) | Allocated Cost ($USD) | Time Estimate | ||||
| Dominion | n8260 / dom-457 | Replace Wave Traps at Surry and Septa | $600,000 | $72,306 | Dec 01 2024 | ||||
Contributor
Description: Replace Wave Traps at Surry and Septa
| Flowgates Addressed by this Reinforcement | |
|---|---|
| Facility | Contingency |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line | (Any) |
| New Ratings | |||
|---|---|---|---|
| Facility | Rating Set | Rating Type | Rating Value |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line | (All) | A | 2539.0 MVA |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line | (All) | B | 3118.0 MVA |
| 8SEPTA-8SURRY 500.0 kV Ckt 1 line | (All) | C | 3794.0 MVA |
| Cost Allocation | |||
|---|---|---|---|
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
| AE2-123 | 26.5 MW | 6.4% | $38,226 |
| AE2-313 | 43.3 MW | 10.4% | $62,484 |
| AF1-123 | 50.1 MW | 12.1% | $72,306 |
| AF1-124 | 50.1 MW | 12.1% | $72,306 |
| AF1-125 | 50.1 MW | 12.1% | $72,306 |
| AF2-042 | 57.3 MW | 13.8% | $82,625 |
| AG1-178 | 71.8 MW | 17.3% | $103,515 |
| AG1-184 | 38.7 MW | 9.3% | $55,768 |
| AG1-449 | 28.1 MW | 6.7% | $40,463 |
| System Reinforcement | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| TO | RTEP ID / TO ID | Title | Total Cost ($USD) | Allocated Cost ($USD) | Time Estimate | ||||
| Dominion | (Pending) / TC1-PH1-DOM-079 | Replace Wave Trap at Surry for increased rating on Line 567 8SURRY 500 KV to 8CHCKAHM 500 KV ckt 1 | $300,000 | $45,642 | 16 to 18 Months | ||||
Contributor
Description: Replace Wave Trap at Surry
| Flowgates Addressed by this Reinforcement | |
|---|---|
| Facility | Contingency |
| 8CHCKAHM-8SURRY 500.0 kV Ckt 1 line | (Any) |
| New Ratings | |||
|---|---|---|---|
| Facility | Rating Set | Rating Type | Rating Value |
| 8CHCKAHM-8SURRY 500.0 kV Ckt 1 line | (All) | A | 2539.0 MVA |
| 8CHCKAHM-8SURRY 500.0 kV Ckt 1 line | (All) | B | 2809.0 MVA |
| 8CHCKAHM-8SURRY 500.0 kV Ckt 1 line | (All) | C | 2932.0 MVA |
| Cost Allocation | |||
|---|---|---|---|
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
| AE2-123 | 231.7 MW | 13.3% | $39,854 |
| AE2-124 | 231.9 MW | 13.3% | $39,890 |
| AE2-147 | 40.6 MW | 2.3% | $6,984 |
| AE2-156 | 28.3 MW | 1.6% | $4,861 |
| AE2-313 | 73.2 MW | 4.2% | $12,596 |
| AF1-123 | 265.3 MW | 15.2% | $45,642 |
| AF1-124 | 265.3 MW | 15.2% | $45,642 |
| AF1-125 | 265.3 MW | 15.2% | $45,642 |
| AF2-042 | 58.0 MW | 3.3% | $9,972 |
| AF2-047 | 36.7 MW | 2.1% | $6,319 |
| AG1-178 | 83.2 MW | 4.8% | $14,312 |
| AG1-184 | 44.8 MW | 2.6% | $7,711 |
| AG1-359 | 37.2 MW | 2.1% | $6,408 |
| AG1-364 | 27.8 MW | 1.6% | $4,786 |
| AG1-439 | 26.7 MW | 1.5% | $4,592 |
| AG1-449 | 27.8 MW | 1.6% | $4,789 |
| System Reinforcement | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| TO | RTEP ID / TO ID | Title | Total Cost ($USD) | Allocated Cost ($USD) | Time Estimate | ||||
| Dominion | (Pending) / TC1-PH1-DOM-045 | Repalce CT Relay at Fentress for increased rating on Line 2128 6FENTRES 230 KV to 6THRASHER 230 KV ckt 1 | $150,000 | $41,329 | 12 to 18 Months | ||||
Contributor
Description: Repalce CT Relay at Fentress.
| Flowgates Addressed by this Reinforcement | |
|---|---|
| Facility | Contingency |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line | (Any) |
| New Ratings | |||
|---|---|---|---|
| Facility | Rating Set | Rating Type | Rating Value |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line | (All) | A | 1051.0 MVA |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line | (All) | B | 1166.0 MVA |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line | (All) | C | 1218.0 MVA |
| Cost Allocation | |||
|---|---|---|---|
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
| AE2-123 | 82.2 MW | 5.7% | $8,484 |
| AE2-124 | 97.3 MW | 6.7% | $10,042 |
| AF1-123 | 400.3 MW | 27.6% | $41,329 |
| AF1-124 | 400.3 MW | 27.6% | $41,329 |
| AF1-125 | 400.3 MW | 27.6% | $41,329 |
| AG1-359 | 72.5 MW | 5.0% | $7,485 |
| System Reinforcement | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| TO | RTEP ID / TO ID | Title | Total Cost ($USD) | Allocated Cost ($USD) | Time Estimate | ||||
| Dominion | (Pending) / TC1-PH1-DOM-046 | Replace Circuit Breaker Lead at Thrasher for increased rating on Line 2128 6FENTRES 230 KV to 6THRASHER 230 KV ckt 1 | $100,000 | $27,553 | 12 to 18 Months | ||||
Contributor
Description: Replace Circuit Breaker Lead at Thrasher.
| Flowgates Addressed by this Reinforcement | |
|---|---|
| Facility | Contingency |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line | (Any) |
| New Ratings | |||
|---|---|---|---|
| Facility | Rating Set | Rating Type | Rating Value |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line | (All) | A | 1196.0 MVA |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line | (All) | B | 1196.0 MVA |
| 6FENTRES-6THRASHER 230.0 kV Ckt 1 line | (All) | C | 1674.0 MVA |
| Cost Allocation | |||
|---|---|---|---|
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
| AE2-123 | 82.2 MW | 5.7% | $5,656 |
| AE2-124 | 97.3 MW | 6.7% | $6,695 |
| AF1-123 | 400.3 MW | 27.6% | $27,553 |
| AF1-124 | 400.3 MW | 27.6% | $27,553 |
| AF1-125 | 400.3 MW | 27.6% | $27,553 |
| AG1-359 | 72.5 MW | 5.0% | $4,990 |
| System Reinforcement | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| TO | RTEP ID / TO ID | Title | Total Cost ($USD) | Allocated Cost ($USD) | Time Estimate | ||||
| Dominion | (Pending) / TC1-PH1-DOM-056 | Replace Circuit Breaker Lead at Thrasher for increased rating on Line 2105 6THRASHER 230 KV to 6YADKIN 230 KV ckt 1 | $100,000 | $21,452 | 12 to 18 Months | ||||
Contributor
Description: Replace Circuit Breaker Lead at Thrasher
| Flowgates Addressed by this Reinforcement | |
|---|---|
| Facility | Contingency |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line | (Any) |
| New Ratings | |||
|---|---|---|---|
| Facility | Rating Set | Rating Type | Rating Value |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line | (All) | A | 1196.0 MVA |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line | (All) | B | 1196.0 MVA |
| 6THRASHER-6YADKIN 230.0 kV Ckt 1 line | (All) | C | 1674.0 MVA |
| Cost Allocation | |||
|---|---|---|---|
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
| AE2-123 | 176.5 MW | 15.1% | $15,109 |
| AE2-124 | 194.5 MW | 16.6% | $16,649 |
| AF1-123 | 250.6 MW | 21.5% | $21,452 |
| AF1-124 | 250.6 MW | 21.5% | $21,452 |
| AF1-125 | 250.6 MW | 21.5% | $21,452 |
| AG1-359 | 45.4 MW | 3.9% | $3,886 |
| System Reinforcement | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| TO | RTEP ID / TO ID | Title | Total Cost ($USD) | Allocated Cost ($USD) | Time Estimate | ||||
| Dominion | (Pending) / TC1-PH1-DOM-080 | Replace Line Lead at Surry for increased rating on Line 567 8SURRY 500 KV to 8CHCKAHM 500 KV ckt 1 | $100,000 | $15,214 | 12 to 18 Months | ||||
Contributor
Description: Replace Line Lead at Surry
| Flowgates Addressed by this Reinforcement | |
|---|---|
| Facility | Contingency |
| 8CHCKAHM-8SURRY 500.0 kV Ckt 1 line | (Any) |
| New Ratings | |||
|---|---|---|---|
| Facility | Rating Set | Rating Type | Rating Value |
| 8CHCKAHM-8SURRY 500.0 kV Ckt 1 line | (All) | A | 2599.0 MVA |
| 8CHCKAHM-8SURRY 500.0 kV Ckt 1 line | (All) | B | 2858.0 MVA |
| 8CHCKAHM-8SURRY 500.0 kV Ckt 1 line | (All) | C | 3144.0 MVA |
| Cost Allocation | |||
|---|---|---|---|
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
| AE2-123 | 231.7 MW | 13.3% | $13,285 |
| AE2-124 | 231.9 MW | 13.3% | $13,297 |
| AE2-147 | 40.6 MW | 2.3% | $2,328 |
| AE2-156 | 28.3 MW | 1.6% | $1,620 |
| AE2-313 | 73.2 MW | 4.2% | $4,199 |
| AF1-123 | 265.3 MW | 15.2% | $15,214 |
| AF1-124 | 265.3 MW | 15.2% | $15,214 |
| AF1-125 | 265.3 MW | 15.2% | $15,214 |
| AF2-042 | 58.0 MW | 3.3% | $3,324 |
| AF2-047 | 36.7 MW | 2.1% | $2,106 |
| AG1-178 | 83.2 MW | 4.8% | $4,771 |
| AG1-184 | 44.8 MW | 2.6% | $2,570 |
| AG1-359 | 37.2 MW | 2.1% | $2,136 |
| AG1-364 | 27.8 MW | 1.6% | $1,595 |
| AG1-439 | 26.7 MW | 1.5% | $1,531 |
| AG1-449 | 27.8 MW | 1.6% | $1,596 |
| System Reinforcement | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| TO | RTEP ID / TO ID | Title | Total Cost ($USD) | Allocated Cost ($USD) | Time Estimate | ||||
| Dominion | (Pending) / TC1-PH1-DOM-097 | Substation work for Energizing the bremo Tx#7 | $100,000 | $8,120 | 6 to 12 Months | ||||
Contributor
Description: There is a Temporary transformer at Bremo substation which is not in service. the cost is to energizing the temporary transformer #7 Ratings are 290/290/332 MVA.
| Flowgates Addressed by this Reinforcement | |
|---|---|
| Facility | Contingency |
| 3BREMO-6BREMO 115.0/230.0 kV Ckt 1 transformer | (Any) |
| New Ratings | |||
|---|---|---|---|
| Facility | Rating Set | Rating Type | Rating Value |
| 3BREMO-6BREMO 115.0/230.0 kV Ckt 1 transformer | (All) | A | 290.0 MVA |
| 3BREMO-6BREMO 115.0/230.0 kV Ckt 1 transformer | (All) | B | 290.0 MVA |
| 3BREMO-6BREMO 115.0/230.0 kV Ckt 1 transformer | (All) | C | 332.0 MVA |
| Cost Allocation | |||
|---|---|---|---|
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
| AE2-123 | 16.7 MW | 7.4% | $7,392 |
| AE2-124 | 16.7 MW | 7.4% | $7,392 |
| AF1-123 | 18.4 MW | 8.1% | $8,120 |
| AF1-124 | 18.4 MW | 8.1% | $8,120 |
| AF1-125 | 18.4 MW | 8.1% | $8,120 |
| AF1-293 | 26.7 MW | 11.8% | $11,794 |
| AF2-171 | 11.8 MW | 5.2% | $5,192 |
| AF2-222 | 11.0 MW | 4.8% | $4,839 |
| AF2-397 | 8.8 MW | 3.9% | $3,890 |
| AG1-030 | 11.0 MW | 4.9% | $4,863 |
| AG1-098 | 7.3 MW | 3.2% | $3,216 |
| AG1-181 | 10.3 MW | 4.5% | $4,540 |
| AG1-285 | 6.5 MW | 2.9% | $2,892 |
| AG1-426 | 13.3 MW | 5.9% | $5,890 |
| AG1-427 | 6.1 MW | 2.7% | $2,674 |
| AG1-432 | 19.7 MW | 8.7% | $8,712 |
| AG1-537 | 5.3 MW | 2.4% | $2,353 |
| System Reinforcement | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| TO | RTEP ID / TO ID | Title | Total Cost ($USD) | Allocated Cost ($USD) | Time Estimate | ||||
| Dominion | b3211 | Rebuild the 1.3 mile section of 500 kV Line No.569 (Loudoun - Morrisville) | $0 | $0 | Dec 31 2025 | ||||
Contingent Note: Although AF1-123 may not presently have cost responsibility for this upgrade, AF1-123 may need this upgrade in-service to be deliverable to the PJM system. If AF1-123 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.
Description: Rebuild the 1.3 mile section of 500 kV Line No.569 (Loudoun - Morrisville) with single-circuit 500 kV structures at the current 500 kV standard. This will increase the rating of the line to 3424 MVA.
| Flowgates Addressed by this Reinforcement | |
|---|---|
| Facility | Contingency |
| 8LOUDOUN-8MORRSVL 500.0 kV Ckt 1 line | (Any) |
| New Ratings | |||
|---|---|---|---|
| Facility | Rating Set | Rating Type | Rating Value |
| 8LOUDOUN-8MORRSVL 500.0 kV Ckt 1 line | (All) | A | 3426.0 MVA |
| 8LOUDOUN-8MORRSVL 500.0 kV Ckt 1 line | (All) | B | 3426.0 MVA |
| 8LOUDOUN-8MORRSVL 500.0 kV Ckt 1 line | (All) | C | 3940.0 MVA |
Attachments
[1]Winter load flow analysis will be performed starting in Transition Cycle #2.