AG2-107 Phase I Study Report

v1.00 released 2025-10-29 19:49

Marysville-Flatlick 765 kV

150.0 MW Capacity / 0.0 MW Energy

Introduction

This Phase I System Impact Study Report (PH1) has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, sections 307 and 308 for New Service Requests (projects) in Transition Cycle 2. The Project Developer/Eligible Customer (developer) is Oak Run Solar Project, LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is American Electric Power.

Preface

The Phase I System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle executive summary format and (ii) an individual project-level basis. The Phase I System Impact Study Results (for both the executive summary and individual reports) will be publicly available on PJM’s website. Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.3, PJM takes the following actions during the Phase I System Impact Study:
  1. PJM studies each New Service Request on a summer peak, winter peak and light load RTEP base case study. The case year is dependent on the new services cycle under study. PJM will identify the base case year to be used in the study of a specific cycle on its website.
  2. PJM will only perform load flow analysis during the Phase I System Impact Study.
  3. In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with Affected System impacts and provides each Affected System Operator with a list of New Service Request in the Cycle with potential impacts to their respective system.
  4. PJM will create both the short circuit and stability base cases to be used in the Phase II System Impact Study.
  5. The Phase I System Impact Study results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.
The Transmission Owner takes the following actions during the Phase I System Impact Study:
  1. Identify required Interconnection Facilities to accommodate the New Service Request.
  2. Identify required Network Upgrades to mitigate system violations from the Phase I System Impact Study.
  3. Provide planning-level preliminary estimates of Interconnection Facilities and Network Upgrades including scope, cost and elapsed time to complete the work.

Decision Point I Requirements

At the close of Phase I System Impact Study, PJM will initiate Decision Point I (DP1). During DP1, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.A.1. Additional information on these elements is available in PJM Manual 14H sections 4.4, 6, and 7.

Allowable project modifications at Decision Point I are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

General

The Project Developer has proposed an uprate to a planned/existing Solar facility located in the American Electric Power zone — Madison County, Ohio. This project is an increase to the developer’s AG1-126 project(s), which will share the same Point of Interconnection. The AG2-107 project is a 150.0 MW Capacity only uprate to the previous project(s). The total installed facilities will have a capability of 400.0 MW with 384.9 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AG2-107
Project Name:
Marysville-Flatlick 765 kV
Project Developer Name:
Oak Run Solar Project, LLC
State:
Ohio
County:
Madison
Transmission Owner:
American Electric Power
MFO:
400.0
MWE:
0.0
MWC:
150.0
Battery Storage Specification:
600.0 MWh, 4.0-hr class
Grid Charging:
Yes
Fuel Type:
Storage
Basecase Study Year:
2028

Physical Interconnection Facility Study

Physical Interconnection Facilities Study is not performed as part of the Phase I System Impact Study. Physical Interconnection Facilities Study will commence in the Phase II System Impact Study.

Point of Interconnection

AG2-107 will interconnect on the American Electric Power  transmission system by tapping the Marysville-Flatlick 765 kV Line.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In the Phase I SIS, the costs shown are subject to change as a result of a facility study performed by the TO during the Phase II or Phase III System Impact Study.

Based on the Phase I SIS results, the AG2-107 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit are also shown below.

Cost Summary
DescriptionCost Allocated to AG2-107Cost Subject to Readiness*
Transmission Owner Interconnection Facilities (TOIF)$0$0
Other Scope$1,280,000$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0
Network Upgrades$0$0
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$25,668,070$25,668,070
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$0$0
Total$26,948,070$25,668,070

* Contributes to calculation for Readiness Deposit #2 (RD2). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 309 (Decision Point I) A.1.a.i and PJM Manual 14H, section 6.2, Readiness Deposit #2 (RD2) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point I (DP1), the Project Developer or Eligible Customer is required to submit Readiness Deposit #2, which is calculated as 10% of cost allocation for required Phase I Network Upgrades minus Readiness Deposit #1.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Readiness Deposit #2 Due for Project AG2-107

Readiness Deposit #2 has been calculated for the project based on the Phase I System Impact Study results and is shown in the table below. This Readiness Deposit #2 must be provided at Decision Point I through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit
Project ID10% of cost allocation for Phase I Network UpgradesReadiness Deposit #1 Received (RD1)Readiness Deposit #2 (RD2) for AG2-107 Project due at DP1
ABA - B
AG2-107$2,566,807$600,000$1,966,807

Note: Failure to provide an acceptable form of Readiness Deposit #2 by the end of Decision Point I will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Physical Interconnection
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)AEP will install standard metering on the generation lead circuit$1,280,000 $1,280,000

Based on the scope of work for the Interconnection Facilities, it is expected to take 6 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

The schedule for any required Network Impact Reinforcements will be more clearly identified in the Phase II and Phase III System Impact Studies.

Transmission Owner Analysis

No Transmission Owner impacts identified.

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. AEP interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AG2-107 was evaluated as a 0.0 MW (150.0 MW Capacity) injection in the AEP area.

AG2-107 was evaluated as part of a plant. The plant consists of AG2-107. The total Energy output of the plant was evaluated at its maximum seasonal capability of 400.0 MW (121.46 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT10A_SRT-SL
BreakerAC121.47 %3792.0B4606.2615.82
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AEP_P4_#8975_05KAMMER 765_MM2_SRT-A
BreakerAC121.45 %3792.0B4605.3815.77
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT7A_SRT-SL
BreakerAC121.43 %3792.0B4604.6815.77
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AP_P1-2_MP-500-028_SRT-A
SingleAC120.65 %3792.0B4574.9619.47
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-502T_SRT-A
SingleAC120.64 %3792.0B4574.6319.47
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AEP_P4_#8975_05KAMMER 765_MM2_SRT-A
BreakerAC139.97 %3792.0B5307.7915.25
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT7A_SRT-SL
BreakerAC139.96 %3792.0B5307.115.25
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT10A_SRT-SL
BreakerAC139.86 %3792.0B5303.4315.37
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-502T_SRT-A
SingleAC139.36 %3792.0B5284.6118.83
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P1-2_MP-500-028_SRT-A
SingleAC139.32 %3792.0B5282.9118.83
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-024_SRT-A
BreakerAC132.75 %3729.0B4950.2717.95
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-025_SRT-A
BreakerAC131.94 %3729.0B4919.9317.88
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-015_SRT-A
BreakerAC131.63 %3729.0B4908.4717.87
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-014_SRT-A
BreakerAC131.63 %3729.0B4908.4717.87
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P1-2_MP-500-007A_SRT-A
SingleAC130.62 %3729.0B4870.9822.05
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-012_SRT-A
BreakerAC130.23 %3729.0B4856.2617.86
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P1-2_MP-500-008A_SRT-SL
SingleAC124.1 %3729.0B4627.621.25
GD2AEP
05FLTLCK-05GAVIN_RF 765.0 kV Ckt 1 line
AEP_P4_#8075_05MARYSV 765_A2_SRT-A
BreakerAC103.34 %4349.0B4494.0875.97
GD2AEP
05GAVIN-05MOUNTN 765.0 kV Ckt 1 line
AEP_P4_#8075_05MARYSV 765_A2_SRT-A
BreakerAC123.29 %4571.0B5635.5451.36
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P4_#9728_05MALIS 138_L1_SRT-A
BreakerAC124.65 %1409.0B1756.359.12
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P4_#9730_05MALIS 138_P1_SRT-A
BreakerAC124.16 %1409.0B1749.369.1
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P4_#9729_05MALIS 138_M1_SRT-A
BreakerAC124.05 %1409.0B1747.919.1
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
BusAC112.44 %1409.0B1584.279.06
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P4_#7222_05MALIS 765_D_SRT-A
BreakerAC112.42 %1409.0B1584.059.06
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P4_#7216_05VASSEL 765_B1_SRT-A
BreakerAC102.74 %1409.0B1447.548.78
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-024_SRT-A
BreakerAC134.01 %3792.0B5081.5217.95
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-025_SRT-A
BreakerAC133.21 %3792.0B5051.217.88
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-015_SRT-A
BreakerAC132.9 %3792.0B5039.6917.87
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-014_SRT-A
BreakerAC132.9 %3792.0B5039.6917.87
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P1-2_MP-500-007A_SRT-A
SingleAC131.92 %3792.0B5002.2822.05
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-012_SRT-A
BreakerAC131.49 %3792.0B4985.9817.86
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P1-2_MP-500-008A_SRT-SL
SingleAC125.38 %3792.0B4754.3321.25
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
BreakerAC124.95 %4142.0B5175.3925.99
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
AP_P2-3_MP-500-020_SRT-SL
BreakerAC120.6 %4142.0B4995.0926.24
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
AP_P2-3_MP-500-021_SRT-SL
BreakerAC120.39 %4142.0B4986.3726.18
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
BreakerAC120.3 %4142.0B4982.8226.16
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC118.76 %4142.0B4919.1832.3
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
BreakerAC135.19 %4142.0B5599.5638.38
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
AP_P2-3_MP-500-020_SRT-SL
BreakerAC132.22 %4142.0B5476.6538.51
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
AP_P2-3_MP-500-021_SRT-SL
BreakerAC132.17 %4142.0B5474.4938.49
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
BreakerAC132.15 %4142.0B5473.5538.48
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC130.8 %4142.0B5417.8647.53
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
AEP_P4_#706_05GAVIN 765_C1_SRT-A
BreakerAC116.53 %4142.0B4826.4856.64
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
AEP_P2-2_#8072_05MARYSV 765_2_SRT-A
BusAC114.32 %4142.0B4735.2543.7
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
AEP_P1-2_#706_SRT-A
SingleAC114.0 %4142.0B4722.0669.95
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
AEP_P7-1_#10944___SRT-A
TowerAC108.04 %4142.0B4474.9135.36
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
ATSI_P7-1_TE-345-027A_SRT-A
TowerAC107.84 %4142.0B4466.8935.62
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
AP_P2-2_WP-500-DRT14_SRT-SL
BusAC104.56 %4142.0B4331.0835.24
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Base Case
SingleAC100.2 %4142.0A4150.4443.57
GD2AEP
05MALISX-05MALIS 138.0 kV Ckt ZB line
AEP_P4_#7216_05VASSEL 765_B1_SRT-A
BreakerAC100.12 %1054.0B1055.310.83
GD2AEP
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
AEP_P4_#711_05MARYSV 765_A1_SRT-A
BreakerAC109.69 %3097.0B3397.134.1
GD2AEP
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
BusAC109.6 %3097.0B3394.3633.98
GD2AEP
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
AEP_P4_#7222_05MALIS 765_D_SRT-A
BreakerAC109.59 %3097.0B3394.133.98
GD2AEP
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
AEP_P4_#9729_05MALIS 138_M1_SRT-A
BreakerAC109.53 %3097.0B3392.2533.97
GD2AEP
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
AEP_P4_#9730_05MALIS 138_P1_SRT-A
BreakerAC109.53 %3097.0B3392.0633.97
GD2AEP
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
AEP_P4_#9728_05MALIS 138_L1_SRT-A
BreakerAC109.5 %3097.0B3391.1333.97
GD2AEP
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
AEP_P1-2_#711_6224_SRT-A
SingleAC105.12 %3097.0B3255.6142.12
GD2AEP
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
AEP_P1-3_#7222_05MALIS 765_1_SRT-A
SingleAC104.65 %3097.0B3241.0641.97
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
BreakerAC134.69 %4571.0B6156.8741.67
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AP_P2-3_MP-500-020_SRT-SL
BreakerAC132.13 %4571.0B6039.5641.78
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AP_P2-3_MP-500-021_SRT-SL
BreakerAC132.1 %4571.0B6038.2941.77
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
BreakerAC132.09 %4571.0B6037.7341.77
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC130.64 %4571.0B5971.4351.58
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AEP_P4_#8085_05MARYSV 345_H_SRT-A
BreakerAC120.72 %4571.0B5518.1448.72
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AEP_P2-2_#8072_05MARYSV 765_2_SRT-A
BusAC119.53 %4571.0B5463.9348.95
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AEP_P1-2_#706_SRT-A
SingleAC116.18 %4571.0B5310.7776.66
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Base Case
SingleAC114.73 %4047.0A4643.0247.64
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AEP_P7-1_#10944___SRT-A
TowerAC111.6 %4571.0B5101.338.67
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
ATSI_P7-1_TE-345-027A_SRT-A
TowerAC109.99 %4571.0B5027.5138.89
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AP_P2-2_WP-500-DRT14_SRT-SL
BusAC107.3 %4571.0B4904.4738.54
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
BreakerAC134.71 %4571.0B6157.3841.67
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AP_P2-3_MP-500-020_SRT-SL
BreakerAC132.15 %4571.0B6040.6741.78
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AP_P2-3_MP-500-021_SRT-SL
BreakerAC132.12 %4571.0B6039.441.77
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
BreakerAC132.11 %4571.0B6038.8541.77
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC130.66 %4571.0B5972.5451.58
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AEP_P4_#8085_05MARYSV 345_H_SRT-A
BreakerAC120.94 %4571.0B5528.2448.72
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AEP_P2-2_#8072_05MARYSV 765_2_SRT-A
BusAC119.76 %4571.0B5474.1748.95
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AEP_P1-2_#706_SRT-A
SingleAC116.43 %4571.0B5322.0176.66
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Base Case
SingleAC114.86 %4047.0A4648.2547.64
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AEP_P7-1_#10944___SRT-A
TowerAC111.67 %4571.0B5104.5238.67
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
ATSI_P7-1_TE-345-027A_SRT-A
TowerAC110.09 %4571.0B5032.3238.89
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AP_P2-2_WP-500-DRT14_SRT-SL
BusAC107.38 %4571.0B4908.3338.54
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#8075_05MARYSV 765_A2_SRT-A
BreakerAC118.92 %5523.0B6567.8229.42
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#8980_05KAMMER 765_QQ2_SRT-A
BreakerAC116.66 %5523.0B6443.1123.89
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P1-2_#17217_SRT-A
SingleAC115.67 %5523.0B6388.3229.5
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#7445_05MARYSV 765_B_SRT-A
BreakerAC113.05 %5523.0B6243.5340.07
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#17219_05GUERNSEY 765_A_SRT-A
BreakerAC112.12 %5523.0B6192.1724.08
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Base Case
SingleAC108.86 %4558.0A4961.8517.54
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
BreakerAC108.47 %5523.0B5991.0216.66
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
BusAC107.09 %5523.0B5914.3222.36
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC106.56 %5523.0B5885.3420.57

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT10A_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT10A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.47 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4606.26
MW Contribution:15.82
Bus #Bus NameTypeMW Contribution
23559101PLEAS2
50/50
11.904
23684101S70BUS1
50/50
0.301
23562301OGROV1
50/50
2.301
24721705FLATG2
Adder
24.275
962761AG1-125 GEN
Solar/Wind Harmer
36.289
970149AG2-104 GEN
Solar/Wind Harmer
44.817
970155AG2-107 GEN
Solar/Wind Harmer
15.824
270510AE1-227 GEN1
Solar/Wind Harmer
2.641
960001AF2-291 GEN
Solar/Wind Harmer
3.22
970947AG2-589 GEN
Solar/Wind Harmer
2.097
270331AC1-082 GEN3
Solar/Wind Harmer
0.474
270349AD2-093_GEN
Solar/Wind Harmer
3.8
927014AC1-188 GEN
Solar/Wind Harmer
1.647
270263AC1-001 GEN
Solar/Wind Harmer
1.075
270159DARBY CT4
Adder
8.977
24686105CER G3
Adder
8.446
24686505CER G6
Adder
8.435
253343AC1-166 GEN
Solar/Wind Harmer
1.099
253325AC1-069 GEN
Solar/Wind Harmer
1.06
24723205RIVRG3
Adder
18.943
970593AG2-378 GEN
Solar/Wind Harmer
2.015
253432AC1-085 GEN2
Solar/Wind Harmer
0.263
946171AF1-282 GEN
Solar/Wind Harmer
9.835
253370AE2-315 SEC1
Adder
1.967
253371AE2-315 SEC2
Adder
1.861
270223U2-072_GEN1
Solar/Wind Harmer
1.941
270578AF1-285 GEN2
Solar/Wind Harmer
1.187
270391AF1-285 GEN3
Solar/Wind Harmer
1.187
25326309TAIT D
Adder
1.075
960071AF2-298 GEN
Solar/Wind Harmer
4.886
252507AC2-088 GEN
Solar/Wind Harmer
1.752
25194608D.CRK4
Adder
1.598
270462AD2-086
Solar/Wind Harmer
6.754
25196808ZIMRHP
Adder
73.524
25196008MFTGT1
Adder
1.336
970333AG2-219 GEN
Solar/Wind Harmer
30.143
945681AF1-233 GEN
Solar/Wind Harmer
17.979
971995AH1-542 GEN
Solar/Wind Harmer
10.473
247536S-71 GEN
Solar/Wind Harmer
3.848
942081AE2-220 GEN
Solar/Wind Harmer
6.077
270239V3-007_GEN1
Solar/Wind Harmer
1.636
965651AG1-433 GEN
Solar/Wind Harmer
5.19
958861AF2-177 GEN
Solar/Wind Harmer
10.377
945371AF1-202 GEN
Solar/Wind Harmer
6.621
270005AE1-210 C O1
Solar/Wind Harmer
5.18
965031AG1-367 GEN
Solar/Wind Harmer
9.478
970825AG2-519 GEN
Solar/Wind Harmer
2.23
970091AG2-072 GEN
Adder
72.371
24728605AND G2
Adder
3.578
24639705ELKHART HY
Adder
0.142
274773LINCOLN ;4U
Adder
7.771
274774LINCOLN ;5U
Adder
7.771
274751CRETE EC ;1U
Adder
7.583
274754CRETE EC ;4U
Adder
7.583
274723RIVER EC ;12
Adder
16.483
274812UNIV PK N;8U
Adder
4.602
274801UNIV PARK;4U
Adder
5.348
274732ELWOOD EC;7P
Adder
8.785
23751101LEADS_P59
Solar/Wind Helper
1.563
23583801GRNGAP
Solar/Wind Helper
4.994
316095T157 G97
Solar/Wind Helper
1.335
23751201ROTHROCK
Solar/Wind Helper
0.822
238185AF2-356 C
Solar/Wind Helper
2.423
23562501BACKB
Solar/Wind Helper
1.01
235054AD2-180 GEN
Solar/Wind Helper
1.889
238108AE1-109 GEN1
Solar/Wind Helper
0.101
235531U2-073 GEN
Solar/Wind Helper
2.957
238117U2-030
Solar/Wind Helper
0.309
238147AE2-230_GEN1
Solar/Wind Helper
0.431
238149AF1-291A_GEN
Solar/Wind Helper
0.123
237061AD1-155 GEN
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.237
235067AD1-061 GEN
Solar/Wind Helper
0.429
237030AB1-096 C
Solar/Wind Helper
0.061
962771AG1-126 GEN
Solar/Wind Harmer
36.289
270330AC1-082 GEN2
Solar/Wind Harmer
0.803
270329AC1-082 GEN1
Solar/Wind Harmer
0.473
270054AF2-122 C O1
Solar/Wind Harmer
3.4
270520AE2-214 GEN
Solar/Wind Harmer
6.265
270459AD2-067 GEN
Solar/Wind Harmer
8.652
961821AG1-024 GEN
Solar/Wind Harmer
8.784
970879AG2-548 GEN
Solar/Wind Harmer
4.434
970689AG2-444 GEN
Solar/Wind Harmer
16.764
270432AC2-029 GEN
Solar/Wind Harmer
7.199
270269AC2-059
Solar/Wind Harmer
9.583
972203AH1-686 GEN
Adder
2.36
940611AE2-048 GEN
Solar/Wind Harmer
22.51
941391AE2-136 GEN
Solar/Wind Harmer
11.664
270284AF1-227 GEN1
Solar/Wind Harmer
5.777
270286AF1-227 GEN2
Solar/Wind Harmer
2.137
270287AF1-227 GEN3
Solar/Wind Harmer
2.137
270156DARBY CT1
Adder
9.122
270157DARBY CT2
Adder
9.1
270158DARBY CT3
Adder
8.955
945631AF1-228 GEN
Solar/Wind Harmer
4.774
253383AE2-342_GEN
Solar/Wind Harmer
0.9
241973AD2-163_GEN1
Solar/Wind Harmer
2.012
943861AF1-054 GEN
Solar/Wind Harmer
3.894
943851AF1-053 GEN
Solar/Wind Harmer
1.882
971985AH1-537 GEN
Solar/Wind Harmer
18.016
270340AC2-060 GEN
Solar/Wind Harmer
3.05
241972AD1-140 GEN
Solar/Wind Harmer
4.451
270367AC2-061_GEN
Solar/Wind Harmer
3.138
253372AE2-315 SEC3
Adder
1.861
253372AE2-315 SEC3
Adder
1.861
270578AF1-285 GEN2
Solar/Wind Harmer
0.457
25306009OHH W.
Adder
2.823
253349AC2-067 GEN
Solar/Wind Harmer
4.865
253400AC2-068 GEN
Solar/Wind Harmer
1.956
252524AE2-267 GEN
Solar/Wind Harmer
1.533
25196408WSDLE3
Adder
8.578
25196308WSDLE2
Adder
8.503
25196208WSDLE1
Adder
8.482
25196708WSDLE6
Adder
8.461
25196508WSDLE4
Adder
8.248
270302AB2-170 GEN
Solar/Wind Harmer
8.119
270317AD1-130_GEN
Solar/Wind Harmer
3.113
944031AF1-071 GEN
Solar/Wind Harmer
0.966
25196108MFTGT2
Adder
1.473
25196108MFTGT2
Adder
1.368
971673AH1-337 GEN
Solar/Wind Harmer
4.391
971029AG2-637 GEN
Solar/Wind Harmer
14.309
972163AH1-664 GEN
Solar/Wind Harmer
9.523
972165AH1-665 GEN
Solar/Wind Harmer
7.618
270543AE2-219 C
Solar/Wind Harmer
4.876
24729505KEY G4
Adder
6.165
270240V3-007_GEN2
Solar/Wind Harmer
5.881
958711AF2-162 GEN
Solar/Wind Harmer
0.961
965101AG1-375 GEN
Solar/Wind Harmer
9.494
945581AF1-223 GEN
Solar/Wind Harmer
4.304
961761AG1-017 GEN
Solar/Wind Harmer
0.406
970115AG2-085 GEN
Solar/Wind Harmer
3.786
24477305BRIDGE
Adder
0.323
274775LINCOLN ;6U
Adder
7.771
274776LINCOLN ;7U
Adder
7.771
274777LINCOLN ;8U
Adder
7.771
274814UNIV PK N;0U
Adder
4.642
274807UNIV PK N;3U
Adder
4.632
274805UNIV PK N;1U
Adder
4.612
274811UNIV PK N;7U
Adder
4.602
972037AH1-567 GEN1
Adder
0.168
972227AH1-698 GEN1
Adder
2.393
274827FISK ;RP
Adder
7.117
274687WILL CNTY;4U
Adder
25.585
274687WILL CNTY;4U
Adder
25.585
274731ELWOOD EC;2P
Adder
15.046
274733ELWOOD EC;3P
Adder
15.046
274735ELWOOD EC;4P
Adder
15.046
274728ELWOOD EC;5P
Adder
15.046
238109AE1-109 GEN2
Solar/Wind Helper
0.101
238110AE1-109 GEN3
Solar/Wind Helper
0.101
238126S14_GEN_1
Solar/Wind Helper
0.75
238152AF2-075_GEN
Solar/Wind Helper
0.615
23546401DTGZ2-030
Solar/Wind Helper
0.077
238208AF1-136 C
Solar/Wind Helper
0.191
23750501ELLIOTTS
Solar/Wind Helper
0.607
237085AD2-009_GEN
Solar/Wind Helper
1.43
3138216PACIFIC
Solar/Wind Helper
0.038
316411AF1-147_GEN1
Solar/Wind Helper
0.761
316415AF1-147_GEN2
Solar/Wind Helper
0.761
270024AE2-089 GEN
Solar/Wind Harmer
0.702
24318905MLG2
50/50
4.888
270471AD2-092_GEN
Solar/Wind Harmer
3.8
946101AF1-275 GEN
Solar/Wind Harmer
1.564
970879AG2-548 GEN
Solar/Wind Harmer
6.355
971073AG2-665 GEN
Solar/Wind Harmer
6.355
971073AG2-665 GEN
Solar/Wind Harmer
4.434
24685805CER G1
Adder
8.39
24685905CER G2
Adder
8.39
942861AE2-305 GEN
Solar/Wind Harmer
7.89
270518AE2-148 GEN
Solar/Wind Harmer
12.226
24723005RIVRG1
Adder
18.943
24723105RIVRG2
Adder
18.943
970077AG2-063 GEN
Solar/Wind Harmer
5.44
972269AH1-719 GEN
Adder
2.314
962581AG1-107 GEN
Solar/Wind Harmer
4.971
961491AF2-440 GEN
Solar/Wind Harmer
2.066
253394AE2-221_GEN
Solar/Wind Harmer
4.473
253398AE2-221_GEN2
Solar/Wind Harmer
4.473
253317AC1-085 GEN4
Solar/Wind Harmer
8.238
25326109MON D
Adder
1.293
964601AG1-323 GEN
Solar/Wind Harmer
3.12
964601AG1-323 GEN
Solar/Wind Harmer
1.451
23559001PLEAS1
50/50
11.904
23684201S70BUS2
50/50
0.306
23562401OGROV2
50/50
2.286
24318805MLG1
50/50
6.661
24721905FLATG4
Adder
24.275
970153AG2-106 GEN
Solar/Wind Harmer
15.824
270512AE1-227 GEN2
Solar/Wind Harmer
2.242
971191AH1-055 GEN
Solar/Wind Harmer
22.996
957541AF2-048 GEN
Solar/Wind Harmer
1.643
961921AG1-034 GEN
Solar/Wind Harmer
13.176
270291AC1-194 GEN
Solar/Wind Harmer
10.919
960801AF2-371 GEN
Solar/Wind Harmer
2.612
964871AG1-351 GEN
Solar/Wind Harmer
1.804
270273AD2-016 GEN
Solar/Wind Harmer
2.741
972173AH1-669 GEN
Solar/Wind Harmer
5.136
241955AC1-078 GEN
Solar/Wind Harmer
7.631
942051AE2-217 GEN
Solar/Wind Harmer
18.255
24686205CER G4
Adder
8.402
24686405CER G5
Adder
8.368
241974AD2-163_GEN2
Solar/Wind Harmer
2.012
253338AC1-165 GEN
Solar/Wind Harmer
1.099
253333AC1-068 GEN
Solar/Wind Harmer
1.06
970605AG2-385 GEN
Solar/Wind Harmer
5.44
253415AE1-040 GEN
Solar/Wind Harmer
1.134
253406AD2-031_GEN
Solar/Wind Harmer
1.265
253316AC1-085 GEN3
Solar/Wind Harmer
8.238
253433AC1-085 GEN1
Solar/Wind Harmer
5.23
946181AF1-283 GEN
Solar/Wind Harmer
12.786
253303V4-073 C
Solar/Wind Harmer
0.114
253370AE2-315 SEC1
Adder
1.967
253371AE2-315 SEC2
Adder
1.861
942871AE2-306 GEN
Solar/Wind Harmer
0.89
270391AF1-285 GEN3
Solar/Wind Harmer
0.457
252510AF1-249 C
Solar/Wind Harmer
0.407
25196608WSDLE5
Adder
8.333
25194608D.CRK4
Adder
1.598
270485AE1-090_GEN
Solar/Wind Harmer
0.587
270222AC2-111 GEN
Solar/Wind Harmer
7.836
25196008MFTGT1
Adder
1.294
970243AG2-164 GEN
Solar/Wind Harmer
24.663
970519AG2-331 GEN
Solar/Wind Harmer
16.569
970699AG2-449 GEN
Solar/Wind Harmer
10.961
972167AH1-666 GEN
Solar/Wind Harmer
7.633
958171AF2-111 GEN
Solar/Wind Harmer
23.849
944531AF1-118 GEN
Solar/Wind Harmer
33.274
270437AC2-090 C
Solar/Wind Harmer
5.307
962031AG1-047 GEN
Solar/Wind Harmer
2.867
957741AF2-068 GEN
Solar/Wind Harmer
14.228
946031AF1-268 GEN
Solar/Wind Harmer
7.867
958821AF2-173 GEN
Solar/Wind Harmer
13.269
270004AE1-209 GEN
Solar/Wind Harmer
5.18
270356AE2-297 GEN
Solar/Wind Harmer
4.32
24728705AND G3
Adder
7.484
24728505AND G1
Adder
3.578
24642205MAYFLWER
Adder
0.588
274772LINCOLN ;3U
Adder
7.771
274752CRETE EC ;2U
Adder
7.583
274753CRETE EC ;3U
Adder
7.583
274724RIVER EC ;11
Adder
16.291
274802UNIV PARK;5U
Adder
5.35
972228AH1-698 GEN2
Adder
3.398
274826FISK ;BP
Adder
10.043
274800UNIV PARK;3U
Adder
5.348
972038AH1-567 GEN2
Adder
0.335
274729ELWOOD EC;1P
Adder
15.046
274730ELWOOD EC;6P
Adder
15.046
316097T157 G90
Solar/Wind Helper
1.335
964991AG1-363 GEN
Solar/Wind Helper
4.295
23750701CROSSCHOOL
Solar/Wind Helper
1.345
238127S14_GEN_2
Solar/Wind Helper
0.75
238118U2-030_1
Solar/Wind Helper
0.309
238148AE2-230_GEN2
Solar/Wind Helper
0.432
237080AD1-060 GEN
Solar/Wind Helper
0.295
237038AE2-054 C
Solar/Wind Helper
0.236
235062AE1-101 C1
Solar/Wind Helper
1.439
23779801AA1-109
Solar/Wind Helper
0.167
971617AH1-308 GEN
Solar/Wind Harmer
0.869
253370AE2-315 SEC1
Adder
1.967
270224U2-072_GEN2
Solar/Wind Harmer
1.941
270227U2-072_GEN3
Solar/Wind Harmer
1.941
270228U2-072_GEN4
Solar/Wind Harmer
1.941
270231U2-072_GEN5
Solar/Wind Harmer
1.941
25322209TAIT E
Adder
9.568
25322209TAIT E
Adder
9.353
270186AC1-089 GEN
Solar/Wind Harmer
5.991
972159AH1-661 GEN
Adder
0.977
938701AE1-092 GEN
Solar/Wind Harmer
20.234
25183208HLCRTG
Solar/Wind Harmer
5.927
252509AD1-136 GEN
Solar/Wind Harmer
0.25
252519AF1-045_GEN
Solar/Wind Harmer
5.924
252516AE2-318_GEN
Solar/Wind Harmer
4.519
253378AE2-206_GEN
Solar/Wind Harmer
3.5
276820AF1-078_GEN
Solar/Wind Harmer
1.555
25194408D.CRK1
Adder
7.352
25194508D.CRK3
Adder
1.375
25326509SID D
Adder
1.274
970239AG2-162 GEN
Solar/Wind Harmer
10.505
24728805RICHG1
Adder
3.601
24728905RICHG2
Adder
3.601
970883AG2-550 GEN
Solar/Wind Harmer
9.522
970885AG2-551 GEN
Solar/Wind Harmer
2.214
270383AD1-128 GEN
Solar/Wind Harmer
5.808
24379505HDWTR1G C
Solar/Wind Harmer
7.516
270209AC1-174_GEN
Solar/Wind Harmer
5.304
926881AC1-175 GEN
Solar/Wind Harmer
5.304
944541AF1-119 GEN
Solar/Wind Harmer
3.977
960971AF2-388 GEN
Solar/Wind Harmer
10.38
247621Y3-024
Adder
0.229
270201AC2-176 GEN
Solar/Wind Harmer
4.876
964611AG1-324 GEN
Solar/Wind Harmer
1.118
964611AG1-324 GEN
Solar/Wind Harmer
0.496
970825AG2-519 GEN
Solar/Wind Harmer
9.992
960441AF2-335 GEN
Solar/Wind Harmer
9.465
247620Y3-023
Adder
0.427
274770LINCOLN ;1U
Adder
7.771
274771LINCOLN ;2U
Adder
7.771
274808UNIV PK N;4U
Adder
4.582
274803UNIV PARK;6U
Adder
5.35
972259AH1-714 GEN
Adder
17.495
23585401KL_K28_T16
Solar/Wind Helper
1.401
238120AE2-309 GEN
Solar/Wind Helper
0.474
238175AF1-290_GEN
Solar/Wind Helper
0.131
238169AE2-226 GEN1
Solar/Wind Helper
0.604
238170AE2-226 GEN2
Solar/Wind Helper
0.604
235020AA1-095 C
Solar/Wind Helper
0.045
23777901MDS_W4-102
Solar/Wind Helper
0.152
235063AE1-101 C2
Solar/Wind Helper
1.439
237002AB1-128_GEN
Solar/Wind Helper
0.384
237001AB1-127_GEN
Solar/Wind Helper
0.383
237034AC2-136 C
Solar/Wind Helper
0.196
23777801MSM_W1-116
Solar/Wind Helper
0.099
237025AB1-124 C
Solar/Wind Helper
0.143
237006AB1-125 GEN
Solar/Wind Helper
0.107
944201AF1-088_MTX
Adder
106.917
957141AF2-008_MTX
Adder
53.458
NYPJM->LTFIMP_NY
CLTF
4.499
LGEELTFEXP_LGEE->PJM
CLTF
6.294
WECLTFEXP_WEC->PJM
CLTF
3.447
AG2-052LTFEXP_AG2-052->PJM
LTF
0.215
AH1-155LTFEXP_AH1-155->PJM
LTF
0.322
CPLELTFEXP_CPLE->PJM
CLTF
1.268
CBM West 2LTFEXP_CBM-W2->PJM
CBM
105.814
LAGNLTFEXP_LAGN->PJM
CLTF
14.208
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.03
TVALTFEXP_TVA->PJM
CLTF
7.054
CBM West 1LTFEXP_CBM-W1->PJM
CBM
126.934
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.919
MECLTFEXP_MEC->PJM
CLTF
14.518
SIGELTFEXP_SIGE->PJM
CLTF
0.468

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AEP_P4_#8975_05KAMMER 765_MM2_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8975_05KAMMER 765_MM2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.45 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4605.38
MW Contribution:15.77
Bus #Bus NameTypeMW Contribution
23559101PLEAS2
50/50
11.891
23684101S70BUS1
50/50
0.299
23562301OGROV1
50/50
2.291
24721705FLATG2
Adder
24.202
962761AG1-125 GEN
Solar/Wind Harmer
36.157
970149AG2-104 GEN
Solar/Wind Harmer
44.654
970155AG2-107 GEN
Solar/Wind Harmer
15.766
960001AF2-291 GEN
Solar/Wind Harmer
3.209
270510AE1-227 GEN1
Solar/Wind Harmer
2.625
970947AG2-589 GEN
Solar/Wind Harmer
2.09
270331AC1-082 GEN3
Solar/Wind Harmer
0.472
270349AD2-093_GEN
Solar/Wind Harmer
3.785
927014AC1-188 GEN
Solar/Wind Harmer
1.641
270263AC1-001 GEN
Solar/Wind Harmer
1.071
270159DARBY CT4
Adder
8.94
24686105CER G3
Adder
8.419
24686505CER G6
Adder
8.408
253343AC1-166 GEN
Solar/Wind Harmer
1.094
253325AC1-069 GEN
Solar/Wind Harmer
1.056
962771AG1-126 GEN
Solar/Wind Harmer
36.157
270330AC1-082 GEN2
Solar/Wind Harmer
0.8
270329AC1-082 GEN1
Solar/Wind Harmer
0.471
270054AF2-122 C O1
Solar/Wind Harmer
3.386
270520AE2-214 GEN
Solar/Wind Harmer
6.239
270459AD2-067 GEN
Solar/Wind Harmer
8.614
961821AG1-024 GEN
Solar/Wind Harmer
8.746
970879AG2-548 GEN
Solar/Wind Harmer
4.417
970689AG2-444 GEN
Solar/Wind Harmer
16.696
270432AC2-029 GEN
Solar/Wind Harmer
7.17
270269AC2-059
Solar/Wind Harmer
9.545
972203AH1-686 GEN
Adder
2.352
940611AE2-048 GEN
Solar/Wind Harmer
22.396
941391AE2-136 GEN
Solar/Wind Harmer
11.605
270284AF1-227 GEN1
Solar/Wind Harmer
5.752
270286AF1-227 GEN2
Solar/Wind Harmer
2.128
270287AF1-227 GEN3
Solar/Wind Harmer
2.128
270156DARBY CT1
Adder
9.085
270157DARBY CT2
Adder
9.063
270158DARBY CT3
Adder
8.918
945631AF1-228 GEN
Solar/Wind Harmer
4.754
253383AE2-342_GEN
Solar/Wind Harmer
0.896
241973AD2-163_GEN1
Solar/Wind Harmer
2.003
943861AF1-054 GEN
Solar/Wind Harmer
3.878
943851AF1-053 GEN
Solar/Wind Harmer
1.874
971985AH1-537 GEN
Solar/Wind Harmer
17.95
270340AC2-060 GEN
Solar/Wind Harmer
3.039
241972AD1-140 GEN
Solar/Wind Harmer
4.433
270367AC2-061_GEN
Solar/Wind Harmer
3.127
253372AE2-315 SEC3
Adder
1.853
253372AE2-315 SEC3
Adder
1.853
270578AF1-285 GEN2
Solar/Wind Harmer
0.455
25306009OHH W.
Adder
2.812
253349AC2-067 GEN
Solar/Wind Harmer
4.845
253400AC2-068 GEN
Solar/Wind Harmer
1.948
252524AE2-267 GEN
Solar/Wind Harmer
1.528
25196408WSDLE3
Adder
8.545
25196308WSDLE2
Adder
8.471
25196208WSDLE1
Adder
8.45
25196708WSDLE6
Adder
8.428
25196508WSDLE4
Adder
8.216
270302AB2-170 GEN
Solar/Wind Harmer
8.082
270317AD1-130_GEN
Solar/Wind Harmer
3.098
944031AF1-071 GEN
Solar/Wind Harmer
0.962
25196108MFTGT2
Adder
1.467
25196108MFTGT2
Adder
1.362
971673AH1-337 GEN
Solar/Wind Harmer
4.374
971029AG2-637 GEN
Solar/Wind Harmer
14.252
972163AH1-664 GEN
Solar/Wind Harmer
9.488
972165AH1-665 GEN
Solar/Wind Harmer
7.591
270543AE2-219 C
Solar/Wind Harmer
4.856
270240V3-007_GEN2
Solar/Wind Harmer
5.858
24729505KEY G4
Adder
6.141
958711AF2-162 GEN
Solar/Wind Harmer
0.957
965101AG1-375 GEN
Solar/Wind Harmer
9.456
945581AF1-223 GEN
Solar/Wind Harmer
4.286
961761AG1-017 GEN
Solar/Wind Harmer
0.404
970115AG2-085 GEN
Solar/Wind Harmer
3.771
24477305BRIDGE
Adder
0.321
274775LINCOLN ;6U
Adder
7.74
274776LINCOLN ;7U
Adder
7.74
274777LINCOLN ;8U
Adder
7.74
274814UNIV PK N;0U
Adder
4.624
274807UNIV PK N;3U
Adder
4.614
274805UNIV PK N;1U
Adder
4.594
274811UNIV PK N;7U
Adder
4.584
972037AH1-567 GEN1
Adder
0.167
972227AH1-698 GEN1
Adder
2.383
274827FISK ;RP
Adder
7.089
274687WILL CNTY;4U
Adder
25.484
274687WILL CNTY;4U
Adder
25.484
274731ELWOOD EC;2P
Adder
14.987
274733ELWOOD EC;3P
Adder
14.987
274735ELWOOD EC;4P
Adder
14.987
274728ELWOOD EC;5P
Adder
14.987
238109AE1-109 GEN2
Solar/Wind Helper
0.102
238110AE1-109 GEN3
Solar/Wind Helper
0.102
238126S14_GEN_1
Solar/Wind Helper
0.764
23750501ELLIOTTS
Solar/Wind Helper
0.636
238152AF2-075_GEN
Solar/Wind Helper
0.611
238208AF1-136 C
Solar/Wind Helper
0.19
23546401DTGZ2-030
Solar/Wind Helper
0.077
237085AD2-009_GEN
Solar/Wind Helper
1.425
3138216PACIFIC
Solar/Wind Helper
0.038
316411AF1-147_GEN1
Solar/Wind Helper
0.754
316415AF1-147_GEN2
Solar/Wind Helper
0.754
270024AE2-089 GEN
Solar/Wind Harmer
0.699
23559001PLEAS1
50/50
11.891
23684201S70BUS2
50/50
0.305
23562401OGROV2
50/50
2.277
24318805MLG1
50/50
6.637
24721905FLATG4
Adder
24.202
970153AG2-106 GEN
Solar/Wind Harmer
15.766
270512AE1-227 GEN2
Solar/Wind Harmer
2.228
971191AH1-055 GEN
Solar/Wind Harmer
22.913
957541AF2-048 GEN
Solar/Wind Harmer
1.637
961921AG1-034 GEN
Solar/Wind Harmer
13.119
270291AC1-194 GEN
Solar/Wind Harmer
10.875
960801AF2-371 GEN
Solar/Wind Harmer
2.601
964871AG1-351 GEN
Solar/Wind Harmer
1.796
270273AD2-016 GEN
Solar/Wind Harmer
2.73
972173AH1-669 GEN
Solar/Wind Harmer
5.115
241955AC1-078 GEN
Solar/Wind Harmer
7.599
942051AE2-217 GEN
Solar/Wind Harmer
18.179
24686205CER G4
Adder
8.375
24686405CER G5
Adder
8.342
241974AD2-163_GEN2
Solar/Wind Harmer
2.003
253338AC1-165 GEN
Solar/Wind Harmer
1.094
253333AC1-068 GEN
Solar/Wind Harmer
1.056
970605AG2-385 GEN
Solar/Wind Harmer
5.418
253415AE1-040 GEN
Solar/Wind Harmer
1.129
253406AD2-031_GEN
Solar/Wind Harmer
1.261
253316AC1-085 GEN3
Solar/Wind Harmer
8.207
253433AC1-085 GEN1
Solar/Wind Harmer
5.21
946181AF1-283 GEN
Solar/Wind Harmer
12.737
253303V4-073 C
Solar/Wind Harmer
0.113
253370AE2-315 SEC1
Adder
1.959
253371AE2-315 SEC2
Adder
1.853
942871AE2-306 GEN
Solar/Wind Harmer
0.886
270391AF1-285 GEN3
Solar/Wind Harmer
0.455
252510AF1-249 C
Solar/Wind Harmer
0.405
25196608WSDLE5
Adder
8.301
25194608D.CRK4
Adder
1.592
270485AE1-090_GEN
Solar/Wind Harmer
0.584
270222AC2-111 GEN
Solar/Wind Harmer
7.805
25196008MFTGT1
Adder
1.289
970243AG2-164 GEN
Solar/Wind Harmer
24.571
970519AG2-331 GEN
Solar/Wind Harmer
16.508
970699AG2-449 GEN
Solar/Wind Harmer
10.921
972167AH1-666 GEN
Solar/Wind Harmer
7.605
958171AF2-111 GEN
Solar/Wind Harmer
23.761
944531AF1-118 GEN
Solar/Wind Harmer
33.14
270437AC2-090 C
Solar/Wind Harmer
5.286
962031AG1-047 GEN
Solar/Wind Harmer
2.855
957741AF2-068 GEN
Solar/Wind Harmer
14.171
958821AF2-173 GEN
Solar/Wind Harmer
13.216
270004AE1-209 GEN
Solar/Wind Harmer
5.159
946031AF1-268 GEN
Solar/Wind Harmer
7.836
270356AE2-297 GEN
Solar/Wind Harmer
4.303
24728705AND G3
Adder
7.455
24728505AND G1
Adder
3.565
24642205MAYFLWER
Adder
0.585
274772LINCOLN ;3U
Adder
7.74
274752CRETE EC ;2U
Adder
7.553
274753CRETE EC ;3U
Adder
7.553
274724RIVER EC ;11
Adder
16.226
274802UNIV PARK;5U
Adder
5.329
972228AH1-698 GEN2
Adder
3.385
274826FISK ;BP
Adder
10.003
274800UNIV PARK;3U
Adder
5.327
972038AH1-567 GEN2
Adder
0.333
274729ELWOOD EC;1P
Adder
14.987
274730ELWOOD EC;6P
Adder
14.987
964991AG1-363 GEN
Solar/Wind Helper
4.266
316097T157 G90
Solar/Wind Helper
1.323
23750701CROSSCHOOL
Solar/Wind Helper
1.364
238118U2-030_1
Solar/Wind Helper
0.318
238127S14_GEN_2
Solar/Wind Helper
0.764
238148AE2-230_GEN2
Solar/Wind Helper
0.429
237048AF1-022 C
Solar/Wind Helper
0.17
237080AD1-060 GEN
Solar/Wind Helper
0.294
237038AE2-054 C
Solar/Wind Helper
0.235
235062AE1-101 C1
Solar/Wind Helper
1.433
23779801AA1-109
Solar/Wind Helper
0.166
971617AH1-308 GEN
Solar/Wind Harmer
0.866
24318905MLG2
50/50
4.855
270471AD2-092_GEN
Solar/Wind Harmer
3.785
946101AF1-275 GEN
Solar/Wind Harmer
1.557
970879AG2-548 GEN
Solar/Wind Harmer
6.331
971073AG2-665 GEN
Solar/Wind Harmer
6.331
971073AG2-665 GEN
Solar/Wind Harmer
4.417
24685805CER G1
Adder
8.364
24685905CER G2
Adder
8.364
942861AE2-305 GEN
Solar/Wind Harmer
7.857
270518AE2-148 GEN
Solar/Wind Harmer
12.175
24723005RIVRG1
Adder
18.885
24723105RIVRG2
Adder
18.885
970077AG2-063 GEN
Solar/Wind Harmer
5.418
972269AH1-719 GEN
Adder
2.302
962581AG1-107 GEN
Solar/Wind Harmer
4.952
961491AF2-440 GEN
Solar/Wind Harmer
2.058
253394AE2-221_GEN
Solar/Wind Harmer
4.456
253398AE2-221_GEN2
Solar/Wind Harmer
4.456
253317AC1-085 GEN4
Solar/Wind Harmer
8.207
25326109MON D
Adder
1.288
964601AG1-323 GEN
Solar/Wind Harmer
3.106
964601AG1-323 GEN
Solar/Wind Harmer
1.445
253370AE2-315 SEC1
Adder
1.959
270224U2-072_GEN2
Solar/Wind Harmer
1.932
270227U2-072_GEN3
Solar/Wind Harmer
1.932
270228U2-072_GEN4
Solar/Wind Harmer
1.932
270231U2-072_GEN5
Solar/Wind Harmer
1.932
25322209TAIT E
Adder
9.53
25322209TAIT E
Adder
9.316
270186AC1-089 GEN
Solar/Wind Harmer
5.968
938701AE1-092 GEN
Solar/Wind Harmer
20.142
25183208HLCRTG
Solar/Wind Harmer
5.905
972159AH1-661 GEN
Adder
0.972
252509AD1-136 GEN
Solar/Wind Harmer
0.249
252519AF1-045_GEN
Solar/Wind Harmer
5.902
252516AE2-318_GEN
Solar/Wind Harmer
4.502
253378AE2-206_GEN
Solar/Wind Harmer
3.485
276820AF1-078_GEN
Solar/Wind Harmer
1.548
25194408D.CRK1
Adder
7.324
25194508D.CRK3
Adder
1.369
25326509SID D
Adder
1.268
970239AG2-162 GEN
Solar/Wind Harmer
10.466
24728805RICHG1
Adder
3.587
24728905RICHG2
Adder
3.587
970883AG2-550 GEN
Solar/Wind Harmer
9.484
970885AG2-551 GEN
Solar/Wind Harmer
2.206
270383AD1-128 GEN
Solar/Wind Harmer
5.785
24379505HDWTR1G C
Solar/Wind Harmer
7.487
270209AC1-174_GEN
Solar/Wind Harmer
5.284
926881AC1-175 GEN
Solar/Wind Harmer
5.284
944541AF1-119 GEN
Solar/Wind Harmer
3.962
24723205RIVRG3
Adder
18.885
970593AG2-378 GEN
Solar/Wind Harmer
2.007
253432AC1-085 GEN2
Solar/Wind Harmer
0.262
946171AF1-282 GEN
Solar/Wind Harmer
9.798
253370AE2-315 SEC1
Adder
1.959
253371AE2-315 SEC2
Adder
1.853
270223U2-072_GEN1
Solar/Wind Harmer
1.932
270578AF1-285 GEN2
Solar/Wind Harmer
1.182
270391AF1-285 GEN3
Solar/Wind Harmer
1.182
25326309TAIT D
Adder
1.071
960071AF2-298 GEN
Solar/Wind Harmer
4.866
252507AC2-088 GEN
Solar/Wind Harmer
1.745
25194608D.CRK4
Adder
1.592
25196808ZIMRHP
Adder
73.247
270462AD2-086
Solar/Wind Harmer
6.724
25196008MFTGT1
Adder
1.331
970333AG2-219 GEN
Solar/Wind Harmer
30.032
945681AF1-233 GEN
Solar/Wind Harmer
17.913
971995AH1-542 GEN
Solar/Wind Harmer
10.422
247536S-71 GEN
Solar/Wind Harmer
3.833
942081AE2-220 GEN
Solar/Wind Harmer
6.053
270239V3-007_GEN1
Solar/Wind Harmer
1.629
965651AG1-433 GEN
Solar/Wind Harmer
5.169
958861AF2-177 GEN
Solar/Wind Harmer
10.335
945371AF1-202 GEN
Solar/Wind Harmer
6.594
270005AE1-210 C O1
Solar/Wind Harmer
5.159
965031AG1-367 GEN
Solar/Wind Harmer
9.44
970825AG2-519 GEN
Solar/Wind Harmer
2.221
970091AG2-072 GEN
Adder
72.107
24728605AND G2
Adder
3.565
24639705ELKHART HY
Adder
0.142
274773LINCOLN ;4U
Adder
7.74
274774LINCOLN ;5U
Adder
7.74
274751CRETE EC ;1U
Adder
7.553
274754CRETE EC ;4U
Adder
7.553
274723RIVER EC ;12
Adder
16.418
274812UNIV PK N;8U
Adder
4.584
274801UNIV PARK;4U
Adder
5.327
274732ELWOOD EC;7P
Adder
8.75
23751101LEADS_P59
Solar/Wind Helper
1.597
23751201ROTHROCK
Solar/Wind Helper
0.849
23562501BACKB
Solar/Wind Helper
1.042
23583801GRNGAP
Solar/Wind Helper
4.948
316095T157 G97
Solar/Wind Helper
1.323
238185AF2-356 C
Solar/Wind Helper
2.474
235054AD2-180 GEN
Solar/Wind Helper
1.935
238117U2-030
Solar/Wind Helper
0.318
238108AE1-109 GEN1
Solar/Wind Helper
0.102
235531U2-073 GEN
Solar/Wind Helper
3.033
238147AE2-230_GEN1
Solar/Wind Helper
0.427
238149AF1-291A_GEN
Solar/Wind Helper
0.122
237061AD1-155 GEN
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.235
235067AD1-061 GEN
Solar/Wind Helper
0.427
237030AB1-096 C
Solar/Wind Helper
0.061
960971AF2-388 GEN
Solar/Wind Harmer
10.338
247621Y3-024
Adder
0.228
270201AC2-176 GEN
Solar/Wind Harmer
4.857
964611AG1-324 GEN
Solar/Wind Harmer
1.114
964611AG1-324 GEN
Solar/Wind Harmer
0.494
970825AG2-519 GEN
Solar/Wind Harmer
9.953
960441AF2-335 GEN
Solar/Wind Harmer
9.427
247620Y3-023
Adder
0.425
274770LINCOLN ;1U
Adder
7.74
274771LINCOLN ;2U
Adder
7.74
274808UNIV PK N;4U
Adder
4.563
274803UNIV PARK;6U
Adder
5.329
972259AH1-714 GEN
Adder
17.426
23585401KL_K28_T16
Solar/Wind Helper
1.442
238120AE2-309 GEN
Solar/Wind Helper
0.483
238175AF1-290_GEN
Solar/Wind Helper
0.13
238169AE2-226 GEN1
Solar/Wind Helper
0.6
238170AE2-226 GEN2
Solar/Wind Helper
0.6
235020AA1-095 C
Solar/Wind Helper
0.045
23777901MDS_W4-102
Solar/Wind Helper
0.151
235063AE1-101 C2
Solar/Wind Helper
1.433
237002AB1-128_GEN
Solar/Wind Helper
0.382
237001AB1-127_GEN
Solar/Wind Helper
0.381
237034AC2-136 C
Solar/Wind Helper
0.194
23777801MSM_W1-116
Solar/Wind Helper
0.098
237025AB1-124 C
Solar/Wind Helper
0.142
237006AB1-125 GEN
Solar/Wind Helper
0.106
944201AF1-088_MTX
Adder
106.522
957141AF2-008_MTX
Adder
53.261
NYPJM->LTFIMP_NY
CLTF
4.491
LGEELTFEXP_LGEE->PJM
CLTF
6.272
WECLTFEXP_WEC->PJM
CLTF
3.434
AG2-052LTFEXP_AG2-052->PJM
LTF
0.214
AH1-155LTFEXP_AH1-155->PJM
LTF
0.321
CPLELTFEXP_CPLE->PJM
CLTF
1.288
CBM West 2LTFEXP_CBM-W2->PJM
CBM
105.476
LAGNLTFEXP_LAGN->PJM
CLTF
14.169
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.052
TVALTFEXP_TVA->PJM
CLTF
7.036
CBM West 1LTFEXP_CBM-W1->PJM
CBM
126.393
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.84
MECLTFEXP_MEC->PJM
CLTF
14.465
SIGELTFEXP_SIGE->PJM
CLTF
0.467

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT7A_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT7A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.43 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4604.68
MW Contribution:15.77
Bus #Bus NameTypeMW Contribution
962771AG1-126 GEN
Solar/Wind Harmer
36.157
270330AC1-082 GEN2
Solar/Wind Harmer
0.8
270329AC1-082 GEN1
Solar/Wind Harmer
0.471
270054AF2-122 C O1
Solar/Wind Harmer
3.386
270520AE2-214 GEN
Solar/Wind Harmer
6.239
270459AD2-067 GEN
Solar/Wind Harmer
8.614
961821AG1-024 GEN
Solar/Wind Harmer
8.746
970879AG2-548 GEN
Solar/Wind Harmer
4.417
970689AG2-444 GEN
Solar/Wind Harmer
16.696
270432AC2-029 GEN
Solar/Wind Harmer
7.17
270269AC2-059
Solar/Wind Harmer
9.545
972203AH1-686 GEN
Adder
2.352
940611AE2-048 GEN
Solar/Wind Harmer
22.396
941391AE2-136 GEN
Solar/Wind Harmer
11.605
270284AF1-227 GEN1
Solar/Wind Harmer
5.752
270286AF1-227 GEN2
Solar/Wind Harmer
2.128
270287AF1-227 GEN3
Solar/Wind Harmer
2.128
270156DARBY CT1
Adder
9.085
270157DARBY CT2
Adder
9.063
270158DARBY CT3
Adder
8.918
945631AF1-228 GEN
Solar/Wind Harmer
4.754
253383AE2-342_GEN
Solar/Wind Harmer
0.896
241973AD2-163_GEN1
Solar/Wind Harmer
2.003
943861AF1-054 GEN
Solar/Wind Harmer
3.878
943851AF1-053 GEN
Solar/Wind Harmer
1.874
971985AH1-537 GEN
Solar/Wind Harmer
17.95
270340AC2-060 GEN
Solar/Wind Harmer
3.039
241972AD1-140 GEN
Solar/Wind Harmer
4.433
270367AC2-061_GEN
Solar/Wind Harmer
3.127
253372AE2-315 SEC3
Adder
1.853
253372AE2-315 SEC3
Adder
1.853
270578AF1-285 GEN2
Solar/Wind Harmer
0.455
25306009OHH W.
Adder
2.812
253349AC2-067 GEN
Solar/Wind Harmer
4.845
253400AC2-068 GEN
Solar/Wind Harmer
1.948
252524AE2-267 GEN
Solar/Wind Harmer
1.528
25196408WSDLE3
Adder
8.545
25196308WSDLE2
Adder
8.471
25196208WSDLE1
Adder
8.45
25196708WSDLE6
Adder
8.428
25196508WSDLE4
Adder
8.216
270302AB2-170 GEN
Solar/Wind Harmer
8.082
270317AD1-130_GEN
Solar/Wind Harmer
3.098
944031AF1-071 GEN
Solar/Wind Harmer
0.962
25196108MFTGT2
Adder
1.467
25196108MFTGT2
Adder
1.362
971673AH1-337 GEN
Solar/Wind Harmer
4.374
971029AG2-637 GEN
Solar/Wind Harmer
14.252
972163AH1-664 GEN
Solar/Wind Harmer
9.488
972165AH1-665 GEN
Solar/Wind Harmer
7.591
270543AE2-219 C
Solar/Wind Harmer
4.856
270240V3-007_GEN2
Solar/Wind Harmer
5.858
24729505KEY G4
Adder
6.141
958711AF2-162 GEN
Solar/Wind Harmer
0.957
965101AG1-375 GEN
Solar/Wind Harmer
9.456
945581AF1-223 GEN
Solar/Wind Harmer
4.286
961761AG1-017 GEN
Solar/Wind Harmer
0.404
970115AG2-085 GEN
Solar/Wind Harmer
3.771
24477305BRIDGE
Adder
0.321
274775LINCOLN ;6U
Adder
7.74
274776LINCOLN ;7U
Adder
7.74
274777LINCOLN ;8U
Adder
7.74
274814UNIV PK N;0U
Adder
4.624
274807UNIV PK N;3U
Adder
4.614
274805UNIV PK N;1U
Adder
4.594
274811UNIV PK N;7U
Adder
4.584
972037AH1-567 GEN1
Adder
0.167
972227AH1-698 GEN1
Adder
2.383
274827FISK ;RP
Adder
7.089
274687WILL CNTY;4U
Adder
25.484
274687WILL CNTY;4U
Adder
25.484
274731ELWOOD EC;2P
Adder
14.987
274733ELWOOD EC;3P
Adder
14.987
274735ELWOOD EC;4P
Adder
14.987
274728ELWOOD EC;5P
Adder
14.987
238109AE1-109 GEN2
Solar/Wind Helper
0.102
238110AE1-109 GEN3
Solar/Wind Helper
0.102
238126S14_GEN_1
Solar/Wind Helper
0.764
23750501ELLIOTTS
Solar/Wind Helper
0.636
238152AF2-075_GEN
Solar/Wind Helper
0.611
238208AF1-136 C
Solar/Wind Helper
0.19
23546401DTGZ2-030
Solar/Wind Helper
0.077
237085AD2-009_GEN
Solar/Wind Helper
1.425
3138216PACIFIC
Solar/Wind Helper
0.038
316411AF1-147_GEN1
Solar/Wind Helper
0.754
316415AF1-147_GEN2
Solar/Wind Helper
0.754
23559001PLEAS1
50/50
11.891
23684201S70BUS2
50/50
0.305
23562401OGROV2
50/50
2.277
24318805MLG1
50/50
6.637
24721905FLATG4
Adder
24.202
970153AG2-106 GEN
Solar/Wind Harmer
15.766
270512AE1-227 GEN2
Solar/Wind Harmer
2.228
971191AH1-055 GEN
Solar/Wind Harmer
22.913
957541AF2-048 GEN
Solar/Wind Harmer
1.637
961921AG1-034 GEN
Solar/Wind Harmer
13.119
270291AC1-194 GEN
Solar/Wind Harmer
10.875
960801AF2-371 GEN
Solar/Wind Harmer
2.601
964871AG1-351 GEN
Solar/Wind Harmer
1.796
270273AD2-016 GEN
Solar/Wind Harmer
2.73
972173AH1-669 GEN
Solar/Wind Harmer
5.115
241955AC1-078 GEN
Solar/Wind Harmer
7.599
942051AE2-217 GEN
Solar/Wind Harmer
18.179
24686205CER G4
Adder
8.375
24686405CER G5
Adder
8.342
241974AD2-163_GEN2
Solar/Wind Harmer
2.003
253338AC1-165 GEN
Solar/Wind Harmer
1.094
253333AC1-068 GEN
Solar/Wind Harmer
1.056
970605AG2-385 GEN
Solar/Wind Harmer
5.418
253415AE1-040 GEN
Solar/Wind Harmer
1.129
253406AD2-031_GEN
Solar/Wind Harmer
1.261
253316AC1-085 GEN3
Solar/Wind Harmer
8.207
253433AC1-085 GEN1
Solar/Wind Harmer
5.21
946181AF1-283 GEN
Solar/Wind Harmer
12.737
253303V4-073 C
Solar/Wind Harmer
0.113
253370AE2-315 SEC1
Adder
1.959
253371AE2-315 SEC2
Adder
1.853
942871AE2-306 GEN
Solar/Wind Harmer
0.886
270391AF1-285 GEN3
Solar/Wind Harmer
0.455
252510AF1-249 C
Solar/Wind Harmer
0.405
25196608WSDLE5
Adder
8.301
25194608D.CRK4
Adder
1.592
270485AE1-090_GEN
Solar/Wind Harmer
0.584
270222AC2-111 GEN
Solar/Wind Harmer
7.805
25196008MFTGT1
Adder
1.289
970243AG2-164 GEN
Solar/Wind Harmer
24.571
970519AG2-331 GEN
Solar/Wind Harmer
16.508
970699AG2-449 GEN
Solar/Wind Harmer
10.921
972167AH1-666 GEN
Solar/Wind Harmer
7.605
958171AF2-111 GEN
Solar/Wind Harmer
23.761
944531AF1-118 GEN
Solar/Wind Harmer
33.14
270437AC2-090 C
Solar/Wind Harmer
5.286
962031AG1-047 GEN
Solar/Wind Harmer
2.855
957741AF2-068 GEN
Solar/Wind Harmer
14.171
958821AF2-173 GEN
Solar/Wind Harmer
13.216
270004AE1-209 GEN
Solar/Wind Harmer
5.159
946031AF1-268 GEN
Solar/Wind Harmer
7.836
270356AE2-297 GEN
Solar/Wind Harmer
4.303
24728705AND G3
Adder
7.455
24728505AND G1
Adder
3.565
24642205MAYFLWER
Adder
0.585
274772LINCOLN ;3U
Adder
7.74
274752CRETE EC ;2U
Adder
7.553
274753CRETE EC ;3U
Adder
7.553
274724RIVER EC ;11
Adder
16.226
274802UNIV PARK;5U
Adder
5.329
972228AH1-698 GEN2
Adder
3.385
274826FISK ;BP
Adder
10.003
274800UNIV PARK;3U
Adder
5.327
972038AH1-567 GEN2
Adder
0.333
274729ELWOOD EC;1P
Adder
14.987
274730ELWOOD EC;6P
Adder
14.987
964991AG1-363 GEN
Solar/Wind Helper
4.266
316097T157 G90
Solar/Wind Helper
1.323
23750701CROSSCHOOL
Solar/Wind Helper
1.364
238118U2-030_1
Solar/Wind Helper
0.318
238127S14_GEN_2
Solar/Wind Helper
0.764
238148AE2-230_GEN2
Solar/Wind Helper
0.429
237048AF1-022 C
Solar/Wind Helper
0.17
237080AD1-060 GEN
Solar/Wind Helper
0.294
237038AE2-054 C
Solar/Wind Helper
0.235
235062AE1-101 C1
Solar/Wind Helper
1.433
23779801AA1-109
Solar/Wind Helper
0.166
971617AH1-308 GEN
Solar/Wind Harmer
0.866
23559101PLEAS2
50/50
11.891
23684101S70BUS1
50/50
0.299
23562301OGROV1
50/50
2.291
24721705FLATG2
Adder
24.202
962761AG1-125 GEN
Solar/Wind Harmer
36.157
970149AG2-104 GEN
Solar/Wind Harmer
44.654
970155AG2-107 GEN
Solar/Wind Harmer
15.766
960001AF2-291 GEN
Solar/Wind Harmer
3.209
270510AE1-227 GEN1
Solar/Wind Harmer
2.625
970947AG2-589 GEN
Solar/Wind Harmer
2.09
270331AC1-082 GEN3
Solar/Wind Harmer
0.472
270349AD2-093_GEN
Solar/Wind Harmer
3.785
927014AC1-188 GEN
Solar/Wind Harmer
1.641
270263AC1-001 GEN
Solar/Wind Harmer
1.071
270159DARBY CT4
Adder
8.94
24686105CER G3
Adder
8.419
24686505CER G6
Adder
8.408
253343AC1-166 GEN
Solar/Wind Harmer
1.094
253325AC1-069 GEN
Solar/Wind Harmer
1.056
24723205RIVRG3
Adder
18.885
970593AG2-378 GEN
Solar/Wind Harmer
2.007
253432AC1-085 GEN2
Solar/Wind Harmer
0.262
946171AF1-282 GEN
Solar/Wind Harmer
9.798
253370AE2-315 SEC1
Adder
1.959
253371AE2-315 SEC2
Adder
1.853
270223U2-072_GEN1
Solar/Wind Harmer
1.932
270578AF1-285 GEN2
Solar/Wind Harmer
1.182
270391AF1-285 GEN3
Solar/Wind Harmer
1.182
25326309TAIT D
Adder
1.071
960071AF2-298 GEN
Solar/Wind Harmer
4.866
252507AC2-088 GEN
Solar/Wind Harmer
1.745
25194608D.CRK4
Adder
1.592
25196808ZIMRHP
Adder
73.247
270462AD2-086
Solar/Wind Harmer
6.724
25196008MFTGT1
Adder
1.331
970333AG2-219 GEN
Solar/Wind Harmer
30.032
945681AF1-233 GEN
Solar/Wind Harmer
17.913
971995AH1-542 GEN
Solar/Wind Harmer
10.422
247536S-71 GEN
Solar/Wind Harmer
3.833
942081AE2-220 GEN
Solar/Wind Harmer
6.053
270239V3-007_GEN1
Solar/Wind Harmer
1.629
965651AG1-433 GEN
Solar/Wind Harmer
5.169
958861AF2-177 GEN
Solar/Wind Harmer
10.335
945371AF1-202 GEN
Solar/Wind Harmer
6.594
270005AE1-210 C O1
Solar/Wind Harmer
5.159
965031AG1-367 GEN
Solar/Wind Harmer
9.44
970825AG2-519 GEN
Solar/Wind Harmer
2.221
970091AG2-072 GEN
Adder
72.107
24728605AND G2
Adder
3.565
24639705ELKHART HY
Adder
0.142
274773LINCOLN ;4U
Adder
7.74
274774LINCOLN ;5U
Adder
7.74
274751CRETE EC ;1U
Adder
7.553
274754CRETE EC ;4U
Adder
7.553
274723RIVER EC ;12
Adder
16.418
274812UNIV PK N;8U
Adder
4.584
274801UNIV PARK;4U
Adder
5.327
274732ELWOOD EC;7P
Adder
8.75
23751101LEADS_P59
Solar/Wind Helper
1.597
23751201ROTHROCK
Solar/Wind Helper
0.849
23562501BACKB
Solar/Wind Helper
1.042
23583801GRNGAP
Solar/Wind Helper
4.948
316095T157 G97
Solar/Wind Helper
1.323
238185AF2-356 C
Solar/Wind Helper
2.474
235054AD2-180 GEN
Solar/Wind Helper
1.935
238117U2-030
Solar/Wind Helper
0.318
238108AE1-109 GEN1
Solar/Wind Helper
0.102
235531U2-073 GEN
Solar/Wind Helper
3.033
238147AE2-230_GEN1
Solar/Wind Helper
0.427
238149AF1-291A_GEN
Solar/Wind Helper
0.122
237061AD1-155 GEN
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.235
235067AD1-061 GEN
Solar/Wind Helper
0.427
237030AB1-096 C
Solar/Wind Helper
0.061
270024AE2-089 GEN
Solar/Wind Harmer
0.699
24318905MLG2
50/50
4.855
270471AD2-092_GEN
Solar/Wind Harmer
3.785
946101AF1-275 GEN
Solar/Wind Harmer
1.557
970879AG2-548 GEN
Solar/Wind Harmer
6.331
971073AG2-665 GEN
Solar/Wind Harmer
6.331
971073AG2-665 GEN
Solar/Wind Harmer
4.417
24685805CER G1
Adder
8.364
24685905CER G2
Adder
8.364
942861AE2-305 GEN
Solar/Wind Harmer
7.857
270518AE2-148 GEN
Solar/Wind Harmer
12.175
24723005RIVRG1
Adder
18.885
24723105RIVRG2
Adder
18.885
970077AG2-063 GEN
Solar/Wind Harmer
5.418
972269AH1-719 GEN
Adder
2.302
962581AG1-107 GEN
Solar/Wind Harmer
4.952
961491AF2-440 GEN
Solar/Wind Harmer
2.058
253394AE2-221_GEN
Solar/Wind Harmer
4.456
253398AE2-221_GEN2
Solar/Wind Harmer
4.456
253317AC1-085 GEN4
Solar/Wind Harmer
8.207
25326109MON D
Adder
1.288
964601AG1-323 GEN
Solar/Wind Harmer
3.106
964601AG1-323 GEN
Solar/Wind Harmer
1.445
253370AE2-315 SEC1
Adder
1.959
270224U2-072_GEN2
Solar/Wind Harmer
1.932
270227U2-072_GEN3
Solar/Wind Harmer
1.932
270228U2-072_GEN4
Solar/Wind Harmer
1.932
270231U2-072_GEN5
Solar/Wind Harmer
1.932
25322209TAIT E
Adder
9.53
25322209TAIT E
Adder
9.316
270186AC1-089 GEN
Solar/Wind Harmer
5.968
938701AE1-092 GEN
Solar/Wind Harmer
20.142
25183208HLCRTG
Solar/Wind Harmer
5.905
972159AH1-661 GEN
Adder
0.972
252509AD1-136 GEN
Solar/Wind Harmer
0.249
252519AF1-045_GEN
Solar/Wind Harmer
5.902
252516AE2-318_GEN
Solar/Wind Harmer
4.502
253378AE2-206_GEN
Solar/Wind Harmer
3.485
276820AF1-078_GEN
Solar/Wind Harmer
1.548
25194408D.CRK1
Adder
7.324
25194508D.CRK3
Adder
1.369
25326509SID D
Adder
1.268
970239AG2-162 GEN
Solar/Wind Harmer
10.466
24728805RICHG1
Adder
3.587
24728905RICHG2
Adder
3.587
970883AG2-550 GEN
Solar/Wind Harmer
9.484
970885AG2-551 GEN
Solar/Wind Harmer
2.206
270383AD1-128 GEN
Solar/Wind Harmer
5.785
24379505HDWTR1G C
Solar/Wind Harmer
7.487
270209AC1-174_GEN
Solar/Wind Harmer
5.284
926881AC1-175 GEN
Solar/Wind Harmer
5.284
944541AF1-119 GEN
Solar/Wind Harmer
3.962
960971AF2-388 GEN
Solar/Wind Harmer
10.338
247621Y3-024
Adder
0.228
270201AC2-176 GEN
Solar/Wind Harmer
4.857
964611AG1-324 GEN
Solar/Wind Harmer
1.114
964611AG1-324 GEN
Solar/Wind Harmer
0.494
970825AG2-519 GEN
Solar/Wind Harmer
9.953
960441AF2-335 GEN
Solar/Wind Harmer
9.427
247620Y3-023
Adder
0.425
274770LINCOLN ;1U
Adder
7.74
274771LINCOLN ;2U
Adder
7.74
274808UNIV PK N;4U
Adder
4.563
274803UNIV PARK;6U
Adder
5.329
972259AH1-714 GEN
Adder
17.426
23585401KL_K28_T16
Solar/Wind Helper
1.442
238120AE2-309 GEN
Solar/Wind Helper
0.483
238175AF1-290_GEN
Solar/Wind Helper
0.13
238169AE2-226 GEN1
Solar/Wind Helper
0.6
238170AE2-226 GEN2
Solar/Wind Helper
0.6
235020AA1-095 C
Solar/Wind Helper
0.045
23777901MDS_W4-102
Solar/Wind Helper
0.151
235063AE1-101 C2
Solar/Wind Helper
1.433
237002AB1-128_GEN
Solar/Wind Helper
0.382
237001AB1-127_GEN
Solar/Wind Helper
0.381
237034AC2-136 C
Solar/Wind Helper
0.194
23777801MSM_W1-116
Solar/Wind Helper
0.098
237025AB1-124 C
Solar/Wind Helper
0.142
237006AB1-125 GEN
Solar/Wind Helper
0.106
944201AF1-088_MTX
Adder
106.522
957141AF2-008_MTX
Adder
53.261
NYPJM->LTFIMP_NY
CLTF
4.491
LGEELTFEXP_LGEE->PJM
CLTF
6.272
WECLTFEXP_WEC->PJM
CLTF
3.434
AG2-052LTFEXP_AG2-052->PJM
LTF
0.214
AH1-155LTFEXP_AH1-155->PJM
LTF
0.321
CPLELTFEXP_CPLE->PJM
CLTF
1.288
CBM West 2LTFEXP_CBM-W2->PJM
CBM
105.476
LAGNLTFEXP_LAGN->PJM
CLTF
14.169
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.052
TVALTFEXP_TVA->PJM
CLTF
7.036
CBM West 1LTFEXP_CBM-W1->PJM
CBM
126.393
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.84
MECLTFEXP_MEC->PJM
CLTF
14.465
SIGELTFEXP_SIGE->PJM
CLTF
0.467

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-028_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.65 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4574.96
MW Contribution:19.47
Bus #Bus NameTypeMW Contribution
962771AG1-126 GEN
Solar/Wind Harmer
30.492
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0.006
270520AE2-214 GEN
Solar/Wind Harmer
0.011
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.271
970879AG2-548 GEN
Solar/Wind Harmer
6.448
970689AG2-444 GEN
Solar/Wind Harmer
14.59
270432AC2-029 GEN
Solar/Wind Harmer
3.168
270269AC2-059
Solar/Wind Harmer
0.004
972203AH1-686 GEN
Adder
2.352
940611AE2-048 GEN
Solar/Wind Harmer
17.483
941391AE2-136 GEN
Solar/Wind Harmer
9.848
270284AF1-227 GEN1
Solar/Wind Harmer
0.009
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
270156DARBY CT1
Adder
9.085
270157DARBY CT2
Adder
9.063
270158DARBY CT3
Adder
8.918
945631AF1-228 GEN
Solar/Wind Harmer
0
253383AE2-342_GEN
Solar/Wind Harmer
0.002
241973AD2-163_GEN1
Solar/Wind Harmer
0.005
943861AF1-054 GEN
Solar/Wind Harmer
2.706
943851AF1-053 GEN
Solar/Wind Harmer
1.874
971985AH1-537 GEN
Solar/Wind Harmer
2.087
270340AC2-060 GEN
Solar/Wind Harmer
0.008
241972AD1-140 GEN
Solar/Wind Harmer
0.755
270367AC2-061_GEN
Solar/Wind Harmer
0.005
253372AE2-315 SEC3
Adder
1.853
253372AE2-315 SEC3
Adder
1.853
270578AF1-285 GEN2
Solar/Wind Harmer
0.455
25306009OHH W.
Adder
2.812
253349AC2-067 GEN
Solar/Wind Harmer
2.136
253400AC2-068 GEN
Solar/Wind Harmer
0.859
252524AE2-267 GEN
Solar/Wind Harmer
0.002
25196408WSDLE3
Adder
8.545
25196308WSDLE2
Adder
8.471
25196208WSDLE1
Adder
8.45
25196708WSDLE6
Adder
8.428
25196508WSDLE4
Adder
8.216
270302AB2-170 GEN
Solar/Wind Harmer
0.004
270317AD1-130_GEN
Solar/Wind Harmer
0.01
971653AH1-327 GEN
Solar/Wind Harmer
0.947
25196108MFTGT2
Adder
1.467
25196108MFTGT2
Adder
1.362
971673AH1-337 GEN
Solar/Wind Harmer
4.312
971029AG2-637 GEN
Solar/Wind Harmer
9.944
972163AH1-664 GEN
Solar/Wind Harmer
7.37
972165AH1-665 GEN
Solar/Wind Harmer
5.903
270543AE2-219 C
Solar/Wind Harmer
0.004
270240V3-007_GEN2
Solar/Wind Harmer
0.002
24729505KEY G4
Adder
6.141
965101AG1-375 GEN
Solar/Wind Harmer
6.597
945581AF1-223 GEN
Solar/Wind Harmer
0
970115AG2-085 GEN
Solar/Wind Harmer
2.631
270024AE2-089 GEN
Solar/Wind Harmer
0.007
971609AH1-304 GEN
Solar/Wind Harmer
1.074
270071AF1-092 GEN
Solar/Wind Harmer
12.598
270594AE1-207 GEN
Solar/Wind Harmer
7.357
970289AG2-191 GEN
Solar/Wind Harmer
1.247
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
8.837
965051AG1-369 GEN
Solar/Wind Harmer
3.247
971347AH1-153 GEN
Solar/Wind Harmer
9.745
965041AG1-368 GEN
Solar/Wind Harmer
6.496
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.821
971611AH1-305 GEN
Solar/Wind Harmer
3.852
958391AF2-133 GEN
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0.008
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
247607V1-011 GEN
Solar/Wind Harmer
0.001
971771AH1-392 GEN
Solar/Wind Harmer
6.442
971769AH1-391 GEN
Solar/Wind Harmer
7.189
963841AG1-237 GEN
Solar/Wind Harmer
2.789
24477305BRIDGE
Adder
0.321
971619AH1-309 GEN
Solar/Wind Harmer
2.888
274775LINCOLN ;6U
Adder
7.74
274776LINCOLN ;7U
Adder
7.74
274777LINCOLN ;8U
Adder
7.74
274814UNIV PK N;0U
Adder
4.624
274807UNIV PK N;3U
Adder
4.614
274805UNIV PK N;1U
Adder
4.594
274811UNIV PK N;7U
Adder
4.584
972037AH1-567 GEN1
Adder
0.167
960591AF2-350 GEN
Solar/Wind Harmer
6.377
972227AH1-698 GEN1
Adder
2.383
274827FISK ;RP
Adder
7.089
970179AG2-119 GEN
Solar/Wind Harmer
5.69
274687WILL CNTY;4U
Adder
25.484
274687WILL CNTY;4U
Adder
25.484
274731ELWOOD EC;2P
Adder
14.987
274733ELWOOD EC;3P
Adder
14.987
274735ELWOOD EC;4P
Adder
14.987
274728ELWOOD EC;5P
Adder
14.987
970833AG2-524 GEN
Solar/Wind Harmer
6.995
970833AG2-524 GEN
Solar/Wind Harmer
4.664
23559101PLEAS2
50/50
11.891
23684101S70BUS1
50/50
0.299
23562301OGROV1
50/50
2.291
24721705FLATG2
Adder
24.202
962761AG1-125 GEN
Solar/Wind Harmer
30.492
970149AG2-104 GEN
Solar/Wind Harmer
32.932
970155AG2-107 GEN
Solar/Wind Harmer
19.471
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
270510AE1-227 GEN1
Solar/Wind Harmer
1.892
970947AG2-589 GEN
Solar/Wind Harmer
0.243
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
270349AD2-093_GEN
Solar/Wind Harmer
0.005
927014AC1-188 GEN
Solar/Wind Harmer
0.004
270263AC1-001 GEN
Solar/Wind Harmer
0.716
270159DARBY CT4
Adder
8.94
24686105CER G3
Adder
8.419
24686505CER G6
Adder
8.408
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.011
24723205RIVRG3
Adder
18.885
970593AG2-378 GEN
Solar/Wind Harmer
1.575
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.836
253370AE2-315 SEC1
Adder
1.959
253371AE2-315 SEC2
Adder
1.853
270223U2-072_GEN1
Solar/Wind Harmer
0.001
25326309TAIT D
Adder
1.071
960071AF2-298 GEN
Solar/Wind Harmer
3.39
252507AC2-088 GEN
Solar/Wind Harmer
0.308
25194608D.CRK4
Adder
1.592
25196808ZIMRHP
Adder
73.247
270462AD2-086
Solar/Wind Harmer
0.014
25196008MFTGT1
Adder
1.331
970333AG2-219 GEN
Solar/Wind Harmer
4.752
945681AF1-233 GEN
Solar/Wind Harmer
12.498
971995AH1-542 GEN
Solar/Wind Harmer
2.424
247536S-71 GEN
Solar/Wind Harmer
0.266
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.843
965651AG1-433 GEN
Solar/Wind Harmer
1.936
958861AF2-177 GEN
Solar/Wind Harmer
2.859
945371AF1-202 GEN
Solar/Wind Harmer
0.001
270005AE1-210 C O1
Solar/Wind Harmer
1.427
965031AG1-367 GEN
Solar/Wind Harmer
6.586
970773AG2-487 GEN
Solar/Wind Harmer
1.163
970825AG2-519 GEN
Solar/Wind Harmer
2.336
270032AE2-172
Solar/Wind Harmer
4.379
970245AG2-165 GEN
Solar/Wind Harmer
2.844
970291AG2-192 GEN
Solar/Wind Harmer
0.853
970091AG2-072 GEN
Adder
72.107
276903AD2-071 C
Solar/Wind Harmer
7.32
965011AG1-365 GEN
Solar/Wind Harmer
6.533
247521TR3_G114
Solar/Wind Harmer
0.237
270246TR4_N_V150
Solar/Wind Harmer
0.042
965421AG1-410 GEN
Solar/Wind Harmer
19.465
24728605AND G2
Adder
3.565
246936BC-WTG1
Solar/Wind Harmer
0.263
270489AE1-102 GEN1
Solar/Wind Harmer
0.843
24695305TIMB G C
Solar/Wind Harmer
0.002
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.087
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
24791305MDL-5G
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.406
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270063AE2-323 C
Solar/Wind Harmer
0.005
270055AF2-134 C O1
Solar/Wind Harmer
0.005
970373AG2-245 GEN
Solar/Wind Harmer
13.568
339216AC1-074 GEN
Solar/Wind Harmer
0.177
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.002
24639705ELKHART HY
Adder
0.142
963741AG1-226 GEN
Solar/Wind Harmer
15.2
945111AF1-176 GEN
Solar/Wind Harmer
11.453
270505AE1-170 C O1
Solar/Wind Harmer
6.739
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.342
274773LINCOLN ;4U
Adder
7.74
274774LINCOLN ;5U
Adder
7.74
274751CRETE EC ;1U
Adder
7.553
274754CRETE EC ;4U
Adder
7.553
274723RIVER EC ;12
Adder
16.418
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.584
276776AD2-060 GEN
Solar/Wind Harmer
0.666
941551AE2-152 GEN
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
5.327
274732ELWOOD EC;7P
Adder
8.75
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
4.75
276691AA1-018 GEN1
Solar/Wind Harmer
0.768
944231AF1-091 GEN
Solar/Wind Harmer
1.688
276901AD2-066 C O1
Solar/Wind Harmer
0.006
24318905MLG2
50/50
4.855
270471AD2-092_GEN
Solar/Wind Harmer
0.005
971073AG2-665 GEN
Solar/Wind Harmer
6.448
24685805CER G1
Adder
8.364
24685905CER G2
Adder
8.364
942861AE2-305 GEN
Solar/Wind Harmer
5.482
270518AE2-148 GEN
Solar/Wind Harmer
0.606
24723005RIVRG1
Adder
18.885
24723105RIVRG2
Adder
18.885
970077AG2-063 GEN
Solar/Wind Harmer
4.025
972269AH1-719 GEN
Adder
2.302
962581AG1-107 GEN
Solar/Wind Harmer
0.001
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
25326109MON D
Adder
1.288
964601AG1-323 GEN
Solar/Wind Harmer
2.731
964601AG1-323 GEN
Solar/Wind Harmer
1.82
253370AE2-315 SEC1
Adder
1.959
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
25322209TAIT E
Adder
9.53
25322209TAIT E
Adder
9.316
270186AC1-089 GEN
Solar/Wind Harmer
0.004
938701AE1-092 GEN
Solar/Wind Harmer
10.928
971655AH1-328 GEN
Solar/Wind Harmer
2.415
25183208HLCRTG
Solar/Wind Harmer
0.011
972159AH1-661 GEN
Adder
0.972
252509AD1-136 GEN
Solar/Wind Harmer
0.034
252519AF1-045_GEN
Solar/Wind Harmer
5.902
252516AE2-318_GEN
Solar/Wind Harmer
5.235
253378AE2-206_GEN
Solar/Wind Harmer
0.004
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
2.92
25194408D.CRK1
Adder
7.324
25194508D.CRK3
Adder
1.369
25326509SID D
Adder
1.268
970239AG2-162 GEN
Solar/Wind Harmer
1.662
24728805RICHG1
Adder
3.587
24728905RICHG2
Adder
3.587
970883AG2-550 GEN
Solar/Wind Harmer
6.617
970885AG2-551 GEN
Solar/Wind Harmer
2.206
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
944541AF1-119 GEN
Solar/Wind Harmer
0.442
960971AF2-388 GEN
Solar/Wind Harmer
3.871
247621Y3-024
Adder
0.228
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.494
970825AG2-519 GEN
Solar/Wind Harmer
7.293
960441AF2-335 GEN
Solar/Wind Harmer
6.577
270599AE1-208 GEN
Solar/Wind Harmer
6.026
270031AE2-169
Solar/Wind Harmer
3.616
942221AE2-234 GEN
Solar/Wind Harmer
0.033
971613AH1-306 GEN
Solar/Wind Harmer
3.153
970321AG2-212 GEN
Solar/Wind Harmer
2.844
970611AG2-400 GEN
Solar/Wind Harmer
6.533
970627AG2-408 GEN
Solar/Wind Harmer
1.96
246938BC-WTG3
Solar/Wind Harmer
0.235
246937BC-WTG2
Solar/Wind Harmer
0.263
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
970235AG2-159 GEN
Solar/Wind Harmer
3.948
970235AG2-159 GEN
Solar/Wind Harmer
2.265
971199AH1-059 GEN
Solar/Wind Harmer
2.587
339221AD2-048_GEN
Solar/Wind Harmer
0.004
966841AG1-555 GEN
Solar/Wind Harmer
0.73
965681AG1-436 GEN
Solar/Wind Harmer
8.059
965791AG1-447 GEN
Solar/Wind Harmer
5.91
270007AE1-245 C
Solar/Wind Harmer
0.002
270216AD2-079_GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.425
270526AF1-158 GEN
Solar/Wind Harmer
0.008
972043AH1-570 GEN
Solar/Wind Harmer
1.674
972045AH1-571 GEN
Solar/Wind Harmer
1.341
24441505OLIV SLR
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
3.747
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
12.817
961051AF2-396 GEN
Solar/Wind Harmer
8.545
274770LINCOLN ;1U
Adder
7.74
274771LINCOLN ;2U
Adder
7.74
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
4.687
970623AG2-406 GEN
Solar/Wind Harmer
1.169
274808UNIV PK N;4U
Adder
4.563
274803UNIV PARK;6U
Adder
5.329
274888KELLY CRK;1U
Solar/Wind Harmer
0.375
274887GEN-1.85
Solar/Wind Harmer
0.168
276843GEN-1.7
Solar/Wind Harmer
0.206
945391AF1-204 GEN
Solar/Wind Harmer
6.775
958011AF2-095 GEN
Solar/Wind Harmer
9.182
972259AH1-714 GEN
Adder
17.426
241960AC2-195 GEN
Solar/Wind Harmer
0.005
971125AH1-004 GEN
Solar/Wind Harmer
2.546
970107AG2-081 GEN
Solar/Wind Harmer
1.909
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
960161AF2-307 GEN
Solar/Wind Harmer
4.195
944971AF1-162 GEN
Solar/Wind Harmer
6.345
958481AF2-142 GEN
Solar/Wind Harmer
9.506
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.857
971573AH1-285 GEN
Solar/Wind Harmer
1.18
958491AF2-143 GEN
Solar/Wind Harmer
9.485
274879MINONK ;1U
Solar/Wind Harmer
0.267
23585401KL_K28_T16
Solar/Wind Helper
1.442
238120AE2-309 GEN
Solar/Wind Helper
0.483
238175AF1-290_GEN
Solar/Wind Helper
0.13
238169AE2-226 GEN1
Solar/Wind Helper
0.6
238170AE2-226 GEN2
Solar/Wind Helper
0.6
235020AA1-095 C
Solar/Wind Helper
0.045
23777901MDS_W4-102
Solar/Wind Helper
0.151
235063AE1-101 C2
Solar/Wind Helper
1.433
237002AB1-128_GEN
Solar/Wind Helper
0.382
237001AB1-127_GEN
Solar/Wind Helper
0.381
237034AC2-136 C
Solar/Wind Helper
0.194
23777801MSM_W1-116
Solar/Wind Helper
0.098
237025AB1-124 C
Solar/Wind Helper
0.142
237006AB1-125 GEN
Solar/Wind Helper
0.106
962691AG1-118 GEN
Solar/Wind Harmer
7.548
23559001PLEAS1
50/50
11.891
23684201S70BUS2
50/50
0.305
23562401OGROV2
50/50
2.277
24318805MLG1
50/50
6.637
24721905FLATG4
Adder
24.202
970153AG2-106 GEN
Solar/Wind Harmer
19.471
270512AE1-227 GEN2
Solar/Wind Harmer
1.892
971191AH1-055 GEN
Solar/Wind Harmer
18.65
961921AG1-034 GEN
Solar/Wind Harmer
6.407
270291AC1-194 GEN
Solar/Wind Harmer
5.661
270273AD2-016 GEN
Solar/Wind Harmer
0.74
972173AH1-669 GEN
Solar/Wind Harmer
3.569
241955AC1-078 GEN
Solar/Wind Harmer
0.006
942051AE2-217 GEN
Solar/Wind Harmer
12.683
24686205CER G4
Adder
8.375
24686405CER G5
Adder
8.342
241974AD2-163_GEN2
Solar/Wind Harmer
0.005
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.011
970605AG2-385 GEN
Solar/Wind Harmer
4.258
253415AE1-040 GEN
Solar/Wind Harmer
0.003
253406AD2-031_GEN
Solar/Wind Harmer
0.512
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
8.886
253370AE2-315 SEC1
Adder
1.959
253371AE2-315 SEC2
Adder
1.853
270391AF1-285 GEN3
Solar/Wind Harmer
0.455
970191AG2-125 GEN
Solar/Wind Harmer
1.745
252510AF1-249 C
Solar/Wind Harmer
0.052
25196608WSDLE5
Adder
8.301
25194608D.CRK4
Adder
1.592
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270222AC2-111 GEN
Solar/Wind Harmer
3.385
25196008MFTGT1
Adder
1.289
970243AG2-164 GEN
Solar/Wind Harmer
3.888
970519AG2-331 GEN
Solar/Wind Harmer
17.281
970699AG2-449 GEN
Solar/Wind Harmer
1.662
972167AH1-666 GEN
Solar/Wind Harmer
5.306
958171AF2-111 GEN
Solar/Wind Harmer
16.577
944531AF1-118 GEN
Solar/Wind Harmer
29.606
270437AC2-090 C
Solar/Wind Harmer
0.003
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
9.887
958821AF2-173 GEN
Solar/Wind Harmer
9.221
270004AE1-209 GEN
Solar/Wind Harmer
1.427
946031AF1-268 GEN
Solar/Wind Harmer
6.268
270356AE2-297 GEN
Solar/Wind Harmer
0.009
971617AH1-308 GEN
Solar/Wind Harmer
5.478
970513AG2-328 GEN
Solar/Wind Harmer
2.844
970517AG2-330 GEN
Solar/Wind Harmer
17.067
970289AG2-191 GEN
Solar/Wind Harmer
0.722
970291AG2-192 GEN
Solar/Wind Harmer
0.656
247642Z2-115 C
Solar/Wind Harmer
0.003
270043AE2-236 GEN
Solar/Wind Harmer
4.199
959331AF2-224 GEN
Solar/Wind Harmer
4.573
965021AG1-366 GEN
Solar/Wind Harmer
2.178
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.042
970349AG2-230 GEN
Solar/Wind Harmer
9.745
24728705AND G3
Adder
7.455
24728505AND G1
Adder
3.565
270491AE1-102 GEN2
Solar/Wind Harmer
0.843
970031AG2-029 GEN
Solar/Wind Harmer
4.207
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.466
964401AG1-302 GEN
Solar/Wind Harmer
0.001
270535AF1-215 GEN1
Solar/Wind Harmer
0.008
247643Z2-116 C
Solar/Wind Harmer
0
24642205MAYFLWER
Adder
0.585
945111AF1-176 GEN
Solar/Wind Harmer
5.203
274772LINCOLN ;3U
Adder
7.74
274752CRETE EC ;2U
Adder
7.553
274753CRETE EC ;3U
Adder
7.553
274724RIVER EC ;11
Adder
16.226
270258AD1-119 GEN
Solar/Wind Harmer
0.002
274802UNIV PARK;5U
Adder
5.329
276806AD2-047 C O1
Solar/Wind Harmer
3.613
970193AG2-126 GEN
Solar/Wind Harmer
9.564
970941AG2-585 GEN
Solar/Wind Harmer
7.971
972228AH1-698 GEN2
Adder
3.385
274826FISK ;BP
Adder
10.003
276897AD1-100 C
Solar/Wind Harmer
0.008
939351AE1-166 GEN
Solar/Wind Harmer
0
274800UNIV PARK;3U
Adder
5.327
972038AH1-567 GEN2
Adder
0.333
970707AG2-453 GEN
Solar/Wind Harmer
20.817
24441205WTRV SLR C
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.252
274729ELWOOD EC;1P
Adder
14.987
274730ELWOOD EC;6P
Adder
14.987
270404AC1-167 GEN
Solar/Wind Harmer
0.003
270053AF1-130 C
Solar/Wind Harmer
1.432
943121AE2-341 GEN
Solar/Wind Harmer
10.635
943591AF1-030 GEN
Solar/Wind Harmer
7.072
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
276805AD2-038 GEN
Solar/Wind Harmer
0.002
964991AG1-363 GEN
Solar/Wind Helper
4.266
316097T157 G90
Solar/Wind Helper
1.323
23750701CROSSCHOOL
Solar/Wind Helper
1.364
238118U2-030_1
Solar/Wind Helper
0.318
238127S14_GEN_2
Solar/Wind Helper
0.764
238148AE2-230_GEN2
Solar/Wind Helper
0.429
237048AF1-022 C
Solar/Wind Helper
0.17
237080AD1-060 GEN
Solar/Wind Helper
0.294
237038AE2-054 C
Solar/Wind Helper
0.235
235062AE1-101 C1
Solar/Wind Helper
1.433
23779801AA1-109
Solar/Wind Helper
0.166
971997AH1-543 GEN
Solar/Wind Harmer
3.315
23751101LEADS_P59
Solar/Wind Helper
1.597
23751201ROTHROCK
Solar/Wind Helper
0.849
23562501BACKB
Solar/Wind Helper
1.042
23583801GRNGAP
Solar/Wind Helper
4.948
316095T157 G97
Solar/Wind Helper
1.323
238185AF2-356 C
Solar/Wind Helper
2.474
235054AD2-180 GEN
Solar/Wind Helper
1.935
238117U2-030
Solar/Wind Helper
0.318
238108AE1-109 GEN1
Solar/Wind Helper
0.102
235531U2-073 GEN
Solar/Wind Helper
3.033
238147AE2-230_GEN1
Solar/Wind Helper
0.427
238149AF1-291A_GEN
Solar/Wind Helper
0.122
237061AD1-155 GEN
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.235
235067AD1-061 GEN
Solar/Wind Helper
0.427
237030AB1-096 C
Solar/Wind Helper
0.061
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
970169AG2-114 GEN
Solar/Wind Harmer
6.327
276868AE1-113 GEN
Solar/Wind Harmer
1.267
276882AE2-255 GEN
Solar/Wind Harmer
0.739
238109AE1-109 GEN2
Solar/Wind Helper
0.102
238110AE1-109 GEN3
Solar/Wind Helper
0.102
238126S14_GEN_1
Solar/Wind Helper
0.764
23750501ELLIOTTS
Solar/Wind Helper
0.636
238152AF2-075_GEN
Solar/Wind Helper
0.611
238208AF1-136 C
Solar/Wind Helper
0.19
23546401DTGZ2-030
Solar/Wind Helper
0.077
237085AD2-009_GEN
Solar/Wind Helper
1.425
3138216PACIFIC
Solar/Wind Helper
0.038
316411AF1-147_GEN1
Solar/Wind Helper
0.754
316415AF1-147_GEN2
Solar/Wind Helper
0.754
944201AF1-088_MTX
Adder
106.522
957141AF2-008_MTX
Adder
53.261
NYPJM->LTFIMP_NY
CLTF
4.491
LGEELTFEXP_LGEE->PJM
CLTF
6.272
WECLTFEXP_WEC->PJM
CLTF
3.434
AG2-052LTFEXP_AG2-052->PJM
LTF
0.214
AH1-155LTFEXP_AH1-155->PJM
LTF
0.321
CPLELTFEXP_CPLE->PJM
CLTF
1.288
CBM West 2LTFEXP_CBM-W2->PJM
CBM
105.476
LAGNLTFEXP_LAGN->PJM
CLTF
14.169
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.052
TVALTFEXP_TVA->PJM
CLTF
7.036
CBM West 1LTFEXP_CBM-W1->PJM
CBM
126.393
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.84
MECLTFEXP_MEC->PJM
CLTF
14.465
SIGELTFEXP_SIGE->PJM
CLTF
0.467

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-502T_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-502T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.64 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4574.63
MW Contribution:19.47
Bus #Bus NameTypeMW Contribution
24318905MLG2
50/50
4.855
270471AD2-092_GEN
Solar/Wind Harmer
0.005
971073AG2-665 GEN
Solar/Wind Harmer
6.448
24685805CER G1
Adder
8.364
24685905CER G2
Adder
8.364
942861AE2-305 GEN
Solar/Wind Harmer
5.482
270518AE2-148 GEN
Solar/Wind Harmer
0.606
24723005RIVRG1
Adder
18.885
24723105RIVRG2
Adder
18.885
970077AG2-063 GEN
Solar/Wind Harmer
4.025
972269AH1-719 GEN
Adder
2.302
962581AG1-107 GEN
Solar/Wind Harmer
0.001
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
25326109MON D
Adder
1.288
964601AG1-323 GEN
Solar/Wind Harmer
2.731
964601AG1-323 GEN
Solar/Wind Harmer
1.82
253370AE2-315 SEC1
Adder
1.959
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
25322209TAIT E
Adder
9.53
25322209TAIT E
Adder
9.316
270186AC1-089 GEN
Solar/Wind Harmer
0.004
938701AE1-092 GEN
Solar/Wind Harmer
10.928
971655AH1-328 GEN
Solar/Wind Harmer
2.415
25183208HLCRTG
Solar/Wind Harmer
0.011
972159AH1-661 GEN
Adder
0.972
252509AD1-136 GEN
Solar/Wind Harmer
0.034
252519AF1-045_GEN
Solar/Wind Harmer
5.902
252516AE2-318_GEN
Solar/Wind Harmer
5.235
253378AE2-206_GEN
Solar/Wind Harmer
0.004
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
2.92
25194408D.CRK1
Adder
7.324
25194508D.CRK3
Adder
1.369
25326509SID D
Adder
1.268
970239AG2-162 GEN
Solar/Wind Harmer
1.662
24728805RICHG1
Adder
3.587
24728905RICHG2
Adder
3.587
970883AG2-550 GEN
Solar/Wind Harmer
6.617
970885AG2-551 GEN
Solar/Wind Harmer
2.206
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
944541AF1-119 GEN
Solar/Wind Harmer
0.442
960971AF2-388 GEN
Solar/Wind Harmer
3.871
23559001PLEAS1
50/50
11.891
23684201S70BUS2
50/50
0.305
23562401OGROV2
50/50
2.277
24318805MLG1
50/50
6.637
24721905FLATG4
Adder
24.202
970153AG2-106 GEN
Solar/Wind Harmer
19.471
270512AE1-227 GEN2
Solar/Wind Harmer
1.892
971191AH1-055 GEN
Solar/Wind Harmer
18.65
961921AG1-034 GEN
Solar/Wind Harmer
6.407
270291AC1-194 GEN
Solar/Wind Harmer
5.661
270273AD2-016 GEN
Solar/Wind Harmer
0.74
972173AH1-669 GEN
Solar/Wind Harmer
3.569
241955AC1-078 GEN
Solar/Wind Harmer
0.006
942051AE2-217 GEN
Solar/Wind Harmer
12.683
24686205CER G4
Adder
8.375
24686405CER G5
Adder
8.342
241974AD2-163_GEN2
Solar/Wind Harmer
0.005
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.011
970605AG2-385 GEN
Solar/Wind Harmer
4.258
253415AE1-040 GEN
Solar/Wind Harmer
0.003
253406AD2-031_GEN
Solar/Wind Harmer
0.512
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
8.886
253370AE2-315 SEC1
Adder
1.959
253371AE2-315 SEC2
Adder
1.853
270391AF1-285 GEN3
Solar/Wind Harmer
0.455
970191AG2-125 GEN
Solar/Wind Harmer
1.745
252510AF1-249 C
Solar/Wind Harmer
0.052
25196608WSDLE5
Adder
8.301
25194608D.CRK4
Adder
1.592
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270222AC2-111 GEN
Solar/Wind Harmer
3.385
25196008MFTGT1
Adder
1.289
970243AG2-164 GEN
Solar/Wind Harmer
3.888
970519AG2-331 GEN
Solar/Wind Harmer
17.281
970699AG2-449 GEN
Solar/Wind Harmer
1.662
972167AH1-666 GEN
Solar/Wind Harmer
5.306
958171AF2-111 GEN
Solar/Wind Harmer
16.577
944531AF1-118 GEN
Solar/Wind Harmer
29.606
270437AC2-090 C
Solar/Wind Harmer
0.003
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
9.887
958821AF2-173 GEN
Solar/Wind Harmer
9.221
270004AE1-209 GEN
Solar/Wind Harmer
1.427
946031AF1-268 GEN
Solar/Wind Harmer
6.268
270356AE2-297 GEN
Solar/Wind Harmer
0.009
971617AH1-308 GEN
Solar/Wind Harmer
5.478
970513AG2-328 GEN
Solar/Wind Harmer
2.844
970517AG2-330 GEN
Solar/Wind Harmer
17.067
970289AG2-191 GEN
Solar/Wind Harmer
0.722
970291AG2-192 GEN
Solar/Wind Harmer
0.656
247642Z2-115 C
Solar/Wind Harmer
0.003
270043AE2-236 GEN
Solar/Wind Harmer
4.199
959331AF2-224 GEN
Solar/Wind Harmer
4.573
965021AG1-366 GEN
Solar/Wind Harmer
2.178
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.042
970349AG2-230 GEN
Solar/Wind Harmer
9.745
24728705AND G3
Adder
7.455
24728505AND G1
Adder
3.565
270491AE1-102 GEN2
Solar/Wind Harmer
0.843
970031AG2-029 GEN
Solar/Wind Harmer
4.207
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.466
964401AG1-302 GEN
Solar/Wind Harmer
0.001
270535AF1-215 GEN1
Solar/Wind Harmer
0.008
247643Z2-116 C
Solar/Wind Harmer
0
24642205MAYFLWER
Adder
0.585
945111AF1-176 GEN
Solar/Wind Harmer
5.203
274772LINCOLN ;3U
Adder
7.74
274752CRETE EC ;2U
Adder
7.553
274753CRETE EC ;3U
Adder
7.553
274724RIVER EC ;11
Adder
16.226
270258AD1-119 GEN
Solar/Wind Harmer
0.002
274802UNIV PARK;5U
Adder
5.329
276806AD2-047 C O1
Solar/Wind Harmer
3.613
970193AG2-126 GEN
Solar/Wind Harmer
9.564
970941AG2-585 GEN
Solar/Wind Harmer
7.971
972228AH1-698 GEN2
Adder
3.385
274826FISK ;BP
Adder
10.003
276897AD1-100 C
Solar/Wind Harmer
0.008
23559101PLEAS2
50/50
11.891
23684101S70BUS1
50/50
0.299
23562301OGROV1
50/50
2.291
24721705FLATG2
Adder
24.202
962761AG1-125 GEN
Solar/Wind Harmer
30.492
970149AG2-104 GEN
Solar/Wind Harmer
32.932
970155AG2-107 GEN
Solar/Wind Harmer
19.471
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
270510AE1-227 GEN1
Solar/Wind Harmer
1.892
970947AG2-589 GEN
Solar/Wind Harmer
0.243
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
270349AD2-093_GEN
Solar/Wind Harmer
0.005
927014AC1-188 GEN
Solar/Wind Harmer
0.004
270263AC1-001 GEN
Solar/Wind Harmer
0.716
270159DARBY CT4
Adder
8.94
24686105CER G3
Adder
8.419
24686505CER G6
Adder
8.408
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.011
24723205RIVRG3
Adder
18.885
970593AG2-378 GEN
Solar/Wind Harmer
1.575
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.836
253370AE2-315 SEC1
Adder
1.959
253371AE2-315 SEC2
Adder
1.853
270223U2-072_GEN1
Solar/Wind Harmer
0.001
25326309TAIT D
Adder
1.071
960071AF2-298 GEN
Solar/Wind Harmer
3.39
252507AC2-088 GEN
Solar/Wind Harmer
0.308
25194608D.CRK4
Adder
1.592
25196808ZIMRHP
Adder
73.247
270462AD2-086
Solar/Wind Harmer
0.014
25196008MFTGT1
Adder
1.331
970333AG2-219 GEN
Solar/Wind Harmer
4.752
945681AF1-233 GEN
Solar/Wind Harmer
12.498
971995AH1-542 GEN
Solar/Wind Harmer
2.424
247536S-71 GEN
Solar/Wind Harmer
0.266
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.843
965651AG1-433 GEN
Solar/Wind Harmer
1.936
958861AF2-177 GEN
Solar/Wind Harmer
2.859
945371AF1-202 GEN
Solar/Wind Harmer
0.001
270005AE1-210 C O1
Solar/Wind Harmer
1.427
965031AG1-367 GEN
Solar/Wind Harmer
6.586
970773AG2-487 GEN
Solar/Wind Harmer
1.163
970825AG2-519 GEN
Solar/Wind Harmer
2.336
270032AE2-172
Solar/Wind Harmer
4.379
970245AG2-165 GEN
Solar/Wind Harmer
2.844
970291AG2-192 GEN
Solar/Wind Harmer
0.853
970091AG2-072 GEN
Adder
72.107
276903AD2-071 C
Solar/Wind Harmer
7.32
965011AG1-365 GEN
Solar/Wind Harmer
6.533
247521TR3_G114
Solar/Wind Harmer
0.237
270246TR4_N_V150
Solar/Wind Harmer
0.042
965421AG1-410 GEN
Solar/Wind Harmer
19.465
24728605AND G2
Adder
3.565
246936BC-WTG1
Solar/Wind Harmer
0.263
270489AE1-102 GEN1
Solar/Wind Harmer
0.843
24695305TIMB G C
Solar/Wind Harmer
0.002
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.087
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
24791305MDL-5G
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.406
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270063AE2-323 C
Solar/Wind Harmer
0.005
270055AF2-134 C O1
Solar/Wind Harmer
0.005
970373AG2-245 GEN
Solar/Wind Harmer
13.568
339216AC1-074 GEN
Solar/Wind Harmer
0.177
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.002
24639705ELKHART HY
Adder
0.142
963741AG1-226 GEN
Solar/Wind Harmer
15.2
945111AF1-176 GEN
Solar/Wind Harmer
11.453
270505AE1-170 C O1
Solar/Wind Harmer
6.739
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.342
274773LINCOLN ;4U
Adder
7.74
274774LINCOLN ;5U
Adder
7.74
274751CRETE EC ;1U
Adder
7.553
274754CRETE EC ;4U
Adder
7.553
274723RIVER EC ;12
Adder
16.418
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.584
276776AD2-060 GEN
Solar/Wind Harmer
0.666
941551AE2-152 GEN
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
5.327
274732ELWOOD EC;7P
Adder
8.75
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
4.75
276691AA1-018 GEN1
Solar/Wind Harmer
0.768
944231AF1-091 GEN
Solar/Wind Harmer
1.688
276901AD2-066 C O1
Solar/Wind Harmer
0.006
971997AH1-543 GEN
Solar/Wind Harmer
3.315
23751101LEADS_P59
Solar/Wind Helper
1.597
23751201ROTHROCK
Solar/Wind Helper
0.849
23562501BACKB
Solar/Wind Helper
1.042
23583801GRNGAP
Solar/Wind Helper
4.948
316095T157 G97
Solar/Wind Helper
1.323
238185AF2-356 C
Solar/Wind Helper
2.474
235054AD2-180 GEN
Solar/Wind Helper
1.935
238117U2-030
Solar/Wind Helper
0.318
238108AE1-109 GEN1
Solar/Wind Helper
0.102
235531U2-073 GEN
Solar/Wind Helper
3.033
238147AE2-230_GEN1
Solar/Wind Helper
0.427
238149AF1-291A_GEN
Solar/Wind Helper
0.122
237061AD1-155 GEN
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.235
235067AD1-061 GEN
Solar/Wind Helper
0.427
237030AB1-096 C
Solar/Wind Helper
0.061
247621Y3-024
Adder
0.228
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.494
970825AG2-519 GEN
Solar/Wind Harmer
7.293
960441AF2-335 GEN
Solar/Wind Harmer
6.577
270599AE1-208 GEN
Solar/Wind Harmer
6.026
270031AE2-169
Solar/Wind Harmer
3.616
942221AE2-234 GEN
Solar/Wind Harmer
0.033
971613AH1-306 GEN
Solar/Wind Harmer
3.153
970321AG2-212 GEN
Solar/Wind Harmer
2.844
970611AG2-400 GEN
Solar/Wind Harmer
6.533
970627AG2-408 GEN
Solar/Wind Harmer
1.96
246938BC-WTG3
Solar/Wind Harmer
0.235
246937BC-WTG2
Solar/Wind Harmer
0.263
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
970235AG2-159 GEN
Solar/Wind Harmer
3.948
970235AG2-159 GEN
Solar/Wind Harmer
2.265
971199AH1-059 GEN
Solar/Wind Harmer
2.587
339221AD2-048_GEN
Solar/Wind Harmer
0.004
966841AG1-555 GEN
Solar/Wind Harmer
0.73
965681AG1-436 GEN
Solar/Wind Harmer
8.059
965791AG1-447 GEN
Solar/Wind Harmer
5.91
270007AE1-245 C
Solar/Wind Harmer
0.002
270216AD2-079_GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.425
270526AF1-158 GEN
Solar/Wind Harmer
0.008
972043AH1-570 GEN
Solar/Wind Harmer
1.674
972045AH1-571 GEN
Solar/Wind Harmer
1.341
24441505OLIV SLR
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
3.747
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
12.817
961051AF2-396 GEN
Solar/Wind Harmer
8.545
274770LINCOLN ;1U
Adder
7.74
274771LINCOLN ;2U
Adder
7.74
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
4.687
970623AG2-406 GEN
Solar/Wind Harmer
1.169
274808UNIV PK N;4U
Adder
4.563
274803UNIV PARK;6U
Adder
5.329
274888KELLY CRK;1U
Solar/Wind Harmer
0.375
274887GEN-1.85
Solar/Wind Harmer
0.168
276843GEN-1.7
Solar/Wind Harmer
0.206
945391AF1-204 GEN
Solar/Wind Harmer
6.775
958011AF2-095 GEN
Solar/Wind Harmer
9.182
972259AH1-714 GEN
Adder
17.426
241960AC2-195 GEN
Solar/Wind Harmer
0.005
971125AH1-004 GEN
Solar/Wind Harmer
2.546
970107AG2-081 GEN
Solar/Wind Harmer
1.909
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
960161AF2-307 GEN
Solar/Wind Harmer
4.195
944971AF1-162 GEN
Solar/Wind Harmer
6.345
958481AF2-142 GEN
Solar/Wind Harmer
9.506
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.857
971573AH1-285 GEN
Solar/Wind Harmer
1.18
958491AF2-143 GEN
Solar/Wind Harmer
9.485
274879MINONK ;1U
Solar/Wind Harmer
0.267
23585401KL_K28_T16
Solar/Wind Helper
1.442
238120AE2-309 GEN
Solar/Wind Helper
0.483
238175AF1-290_GEN
Solar/Wind Helper
0.13
238169AE2-226 GEN1
Solar/Wind Helper
0.6
238170AE2-226 GEN2
Solar/Wind Helper
0.6
235020AA1-095 C
Solar/Wind Helper
0.045
23777901MDS_W4-102
Solar/Wind Helper
0.151
235063AE1-101 C2
Solar/Wind Helper
1.433
237002AB1-128_GEN
Solar/Wind Helper
0.382
237001AB1-127_GEN
Solar/Wind Helper
0.381
237034AC2-136 C
Solar/Wind Helper
0.194
23777801MSM_W1-116
Solar/Wind Helper
0.098
237025AB1-124 C
Solar/Wind Helper
0.142
237006AB1-125 GEN
Solar/Wind Helper
0.106
962691AG1-118 GEN
Solar/Wind Harmer
7.548
962771AG1-126 GEN
Solar/Wind Harmer
30.492
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0.006
270520AE2-214 GEN
Solar/Wind Harmer
0.011
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.271
970879AG2-548 GEN
Solar/Wind Harmer
6.448
970689AG2-444 GEN
Solar/Wind Harmer
14.59
270432AC2-029 GEN
Solar/Wind Harmer
3.168
270269AC2-059
Solar/Wind Harmer
0.004
972203AH1-686 GEN
Adder
2.352
940611AE2-048 GEN
Solar/Wind Harmer
17.483
941391AE2-136 GEN
Solar/Wind Harmer
9.848
270284AF1-227 GEN1
Solar/Wind Harmer
0.009
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
270156DARBY CT1
Adder
9.085
270157DARBY CT2
Adder
9.063
270158DARBY CT3
Adder
8.918
945631AF1-228 GEN
Solar/Wind Harmer
0
253383AE2-342_GEN
Solar/Wind Harmer
0.002
241973AD2-163_GEN1
Solar/Wind Harmer
0.005
943861AF1-054 GEN
Solar/Wind Harmer
2.706
943851AF1-053 GEN
Solar/Wind Harmer
1.874
971985AH1-537 GEN
Solar/Wind Harmer
2.087
270340AC2-060 GEN
Solar/Wind Harmer
0.008
241972AD1-140 GEN
Solar/Wind Harmer
0.755
270367AC2-061_GEN
Solar/Wind Harmer
0.005
253372AE2-315 SEC3
Adder
1.853
253372AE2-315 SEC3
Adder
1.853
270578AF1-285 GEN2
Solar/Wind Harmer
0.455
25306009OHH W.
Adder
2.812
253349AC2-067 GEN
Solar/Wind Harmer
2.136
253400AC2-068 GEN
Solar/Wind Harmer
0.859
252524AE2-267 GEN
Solar/Wind Harmer
0.002
25196408WSDLE3
Adder
8.545
25196308WSDLE2
Adder
8.471
25196208WSDLE1
Adder
8.45
25196708WSDLE6
Adder
8.428
25196508WSDLE4
Adder
8.216
270302AB2-170 GEN
Solar/Wind Harmer
0.004
270317AD1-130_GEN
Solar/Wind Harmer
0.01
971653AH1-327 GEN
Solar/Wind Harmer
0.947
25196108MFTGT2
Adder
1.467
25196108MFTGT2
Adder
1.362
971673AH1-337 GEN
Solar/Wind Harmer
4.312
971029AG2-637 GEN
Solar/Wind Harmer
9.944
972163AH1-664 GEN
Solar/Wind Harmer
7.37
972165AH1-665 GEN
Solar/Wind Harmer
5.903
270543AE2-219 C
Solar/Wind Harmer
0.004
270240V3-007_GEN2
Solar/Wind Harmer
0.002
24729505KEY G4
Adder
6.141
965101AG1-375 GEN
Solar/Wind Harmer
6.597
945581AF1-223 GEN
Solar/Wind Harmer
0
970115AG2-085 GEN
Solar/Wind Harmer
2.631
270024AE2-089 GEN
Solar/Wind Harmer
0.007
971609AH1-304 GEN
Solar/Wind Harmer
1.074
270071AF1-092 GEN
Solar/Wind Harmer
12.598
270594AE1-207 GEN
Solar/Wind Harmer
7.357
970289AG2-191 GEN
Solar/Wind Harmer
1.247
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
8.837
965051AG1-369 GEN
Solar/Wind Harmer
3.247
971347AH1-153 GEN
Solar/Wind Harmer
9.745
965041AG1-368 GEN
Solar/Wind Harmer
6.496
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.821
971611AH1-305 GEN
Solar/Wind Harmer
3.852
958391AF2-133 GEN
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0.008
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
247607V1-011 GEN
Solar/Wind Harmer
0.001
971771AH1-392 GEN
Solar/Wind Harmer
6.442
971769AH1-391 GEN
Solar/Wind Harmer
7.189
963841AG1-237 GEN
Solar/Wind Harmer
2.789
24477305BRIDGE
Adder
0.321
971619AH1-309 GEN
Solar/Wind Harmer
2.888
274775LINCOLN ;6U
Adder
7.74
274776LINCOLN ;7U
Adder
7.74
274777LINCOLN ;8U
Adder
7.74
274814UNIV PK N;0U
Adder
4.624
274807UNIV PK N;3U
Adder
4.614
274805UNIV PK N;1U
Adder
4.594
274811UNIV PK N;7U
Adder
4.584
972037AH1-567 GEN1
Adder
0.167
960591AF2-350 GEN
Solar/Wind Harmer
6.377
972227AH1-698 GEN1
Adder
2.383
274827FISK ;RP
Adder
7.089
970179AG2-119 GEN
Solar/Wind Harmer
5.69
274687WILL CNTY;4U
Adder
25.484
274687WILL CNTY;4U
Adder
25.484
274731ELWOOD EC;2P
Adder
14.987
274733ELWOOD EC;3P
Adder
14.987
274735ELWOOD EC;4P
Adder
14.987
274728ELWOOD EC;5P
Adder
14.987
970833AG2-524 GEN
Solar/Wind Harmer
6.995
970833AG2-524 GEN
Solar/Wind Harmer
4.664
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
970169AG2-114 GEN
Solar/Wind Harmer
6.327
276868AE1-113 GEN
Solar/Wind Harmer
1.267
276882AE2-255 GEN
Solar/Wind Harmer
0.739
238109AE1-109 GEN2
Solar/Wind Helper
0.102
238110AE1-109 GEN3
Solar/Wind Helper
0.102
238126S14_GEN_1
Solar/Wind Helper
0.764
23750501ELLIOTTS
Solar/Wind Helper
0.636
238152AF2-075_GEN
Solar/Wind Helper
0.611
238208AF1-136 C
Solar/Wind Helper
0.19
23546401DTGZ2-030
Solar/Wind Helper
0.077
237085AD2-009_GEN
Solar/Wind Helper
1.425
3138216PACIFIC
Solar/Wind Helper
0.038
316411AF1-147_GEN1
Solar/Wind Helper
0.754
316415AF1-147_GEN2
Solar/Wind Helper
0.754
939351AE1-166 GEN
Solar/Wind Harmer
0
274800UNIV PARK;3U
Adder
5.327
972038AH1-567 GEN2
Adder
0.333
970707AG2-453 GEN
Solar/Wind Harmer
20.817
24441205WTRV SLR C
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.252
274729ELWOOD EC;1P
Adder
14.987
274730ELWOOD EC;6P
Adder
14.987
270404AC1-167 GEN
Solar/Wind Harmer
0.003
270053AF1-130 C
Solar/Wind Harmer
1.432
943121AE2-341 GEN
Solar/Wind Harmer
10.635
943591AF1-030 GEN
Solar/Wind Harmer
7.072
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
276805AD2-038 GEN
Solar/Wind Harmer
0.002
964991AG1-363 GEN
Solar/Wind Helper
4.266
316097T157 G90
Solar/Wind Helper
1.323
23750701CROSSCHOOL
Solar/Wind Helper
1.364
238118U2-030_1
Solar/Wind Helper
0.318
238127S14_GEN_2
Solar/Wind Helper
0.764
238148AE2-230_GEN2
Solar/Wind Helper
0.429
237048AF1-022 C
Solar/Wind Helper
0.17
237080AD1-060 GEN
Solar/Wind Helper
0.294
237038AE2-054 C
Solar/Wind Helper
0.235
235062AE1-101 C1
Solar/Wind Helper
1.433
23779801AA1-109
Solar/Wind Helper
0.166
944201AF1-088_MTX
Adder
106.522
957141AF2-008_MTX
Adder
53.261
NYPJM->LTFIMP_NY
CLTF
4.491
LGEELTFEXP_LGEE->PJM
CLTF
6.272
WECLTFEXP_WEC->PJM
CLTF
3.434
AG2-052LTFEXP_AG2-052->PJM
LTF
0.214
AH1-155LTFEXP_AH1-155->PJM
LTF
0.321
CPLELTFEXP_CPLE->PJM
CLTF
1.288
CBM West 2LTFEXP_CBM-W2->PJM
CBM
105.476
LAGNLTFEXP_LAGN->PJM
CLTF
14.169
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.052
TVALTFEXP_TVA->PJM
CLTF
7.036
CBM West 1LTFEXP_CBM-W1->PJM
CBM
126.393
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.84
MECLTFEXP_MEC->PJM
CLTF
14.465
SIGELTFEXP_SIGE->PJM
CLTF
0.467

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AEP_P4_#8975_05KAMMER 765_MM2_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8975_05KAMMER 765_MM2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:139.97 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5307.79
MW Contribution:15.25
Bus #Bus NameTypeMW Contribution
962771AG1-126 GEN
Solar/Wind Harmer
34.974
270330AC1-082 GEN2
Solar/Wind Harmer
0.789
270329AC1-082 GEN1
Solar/Wind Harmer
0.465
270054AF2-122 C O1
Solar/Wind Harmer
3.29
970879AG2-548 GEN
Solar/Wind Harmer
4.317
940611AE2-048 GEN
Solar/Wind Harmer
22.053
941391AE2-136 GEN
Solar/Wind Harmer
11.427
270520AE2-214 GEN
Solar/Wind Harmer
6.059
270459AD2-067 GEN
Solar/Wind Harmer
8.36
961821AG1-024 GEN
Solar/Wind Harmer
8.487
972203AH1-686 GEN
Adder
2.298
270432AC2-029 GEN
Solar/Wind Harmer
6.982
970689AG2-444 GEN
Solar/Wind Harmer
16.256
270269AC2-059
Solar/Wind Harmer
9.3
270156DARBY CT1
Adder
8.832
270157DARBY CT2
Adder
8.81
270158DARBY CT3
Adder
8.67
945631AF1-228 GEN
Solar/Wind Harmer
4.621
270284AF1-227 GEN1
Solar/Wind Harmer
5.57
270286AF1-227 GEN2
Solar/Wind Harmer
2.061
270287AF1-227 GEN3
Solar/Wind Harmer
2.061
971985AH1-537 GEN
Solar/Wind Harmer
17.522
253383AE2-342_GEN
Solar/Wind Harmer
0.869
241973AD2-163_GEN1
Solar/Wind Harmer
1.944
943861AF1-054 GEN
Solar/Wind Harmer
3.765
943851AF1-053 GEN
Solar/Wind Harmer
1.82
270340AC2-060 GEN
Solar/Wind Harmer
2.96
24477305BRIDGE
Adder
0.338
241972AD1-140 GEN
Solar/Wind Harmer
4.309
270367AC2-061_GEN
Solar/Wind Harmer
3.048
253372AE2-315 SEC3
Adder
1.803
253372AE2-315 SEC3
Adder
1.803
25306009OHH W.
Adder
2.735
270578AF1-285 GEN2
Solar/Wind Harmer
0.44
253349AC2-067 GEN
Solar/Wind Harmer
4.712
253400AC2-068 GEN
Solar/Wind Harmer
1.895
252524AE2-267 GEN
Solar/Wind Harmer
1.487
25196408WSDLE3
Adder
8.32
25196308WSDLE2
Adder
8.248
25196208WSDLE1
Adder
8.227
25196708WSDLE6
Adder
8.207
25196508WSDLE4
Adder
8
270302AB2-170 GEN
Solar/Wind Harmer
7.824
270317AD1-130_GEN
Solar/Wind Harmer
3
944031AF1-071 GEN
Solar/Wind Harmer
0.936
25196108MFTGT2
Adder
1.429
25196108MFTGT2
Adder
1.327
972163AH1-664 GEN
Solar/Wind Harmer
9.252
972165AH1-665 GEN
Solar/Wind Harmer
7.402
971673AH1-337 GEN
Solar/Wind Harmer
4.251
971029AG2-637 GEN
Solar/Wind Harmer
13.852
270543AE2-219 C
Solar/Wind Harmer
4.719
270240V3-007_GEN2
Solar/Wind Harmer
5.693
24729505KEY G4
Adder
5.961
958711AF2-162 GEN
Solar/Wind Harmer
0.929
965101AG1-375 GEN
Solar/Wind Harmer
9.182
945581AF1-223 GEN
Solar/Wind Harmer
4.163
961761AG1-017 GEN
Solar/Wind Harmer
0.393
970115AG2-085 GEN
Solar/Wind Harmer
3.664
274775LINCOLN ;6U
Adder
7.514
274776LINCOLN ;7U
Adder
7.514
274777LINCOLN ;8U
Adder
7.514
274814UNIV PK N;0U
Adder
4.489
274807UNIV PK N;3U
Adder
4.479
274805UNIV PK N;1U
Adder
4.459
274811UNIV PK N;7U
Adder
0.697
238152AF2-075_GEN
Solar/Wind Helper
0.593
23546401DTGZ2-030
Solar/Wind Helper
0.075
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
238208AF1-136 C
Solar/Wind Helper
0.18
237085AD2-009_GEN
Solar/Wind Helper
1.367
238126S14_GEN_1
Solar/Wind Helper
0.641
23559001PLEAS1
50/50
11.213
23684201S70BUS2
50/50
0.319
23562401OGROV2
50/50
2.411
24318805MLG1
50/50
6.319
24721905FLATG4
Adder
23.442
970153AG2-106 GEN
Solar/Wind Harmer
15.25
270512AE1-227 GEN2
Solar/Wind Harmer
2.245
971191AH1-055 GEN
Solar/Wind Harmer
22.406
957541AF2-048 GEN
Solar/Wind Harmer
1.601
270291AC1-194 GEN
Solar/Wind Harmer
10.629
961921AG1-034 GEN
Solar/Wind Harmer
12.731
960801AF2-371 GEN
Solar/Wind Harmer
2.533
964871AG1-351 GEN
Solar/Wind Harmer
1.749
270273AD2-016 GEN
Solar/Wind Harmer
2.659
972173AH1-669 GEN
Solar/Wind Harmer
4.984
241955AC1-078 GEN
Solar/Wind Harmer
7.382
24686205CER G4
Adder
8.21
24686405CER G5
Adder
8.177
942051AE2-217 GEN
Solar/Wind Harmer
17.654
253338AC1-165 GEN
Solar/Wind Harmer
1.064
253333AC1-068 GEN
Solar/Wind Harmer
1.027
241974AD2-163_GEN2
Solar/Wind Harmer
1.944
253415AE1-040 GEN
Solar/Wind Harmer
1.1
970605AG2-385 GEN
Solar/Wind Harmer
5.262
253406AD2-031_GEN
Solar/Wind Harmer
1.228
253316AC1-085 GEN3
Solar/Wind Harmer
7.992
253433AC1-085 GEN1
Solar/Wind Harmer
5.073
946181AF1-283 GEN
Solar/Wind Harmer
12.404
253303V4-073 C
Solar/Wind Harmer
0.11
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
942871AE2-306 GEN
Solar/Wind Harmer
0.858
270391AF1-285 GEN3
Solar/Wind Harmer
0.44
252510AF1-249 C
Solar/Wind Harmer
0.395
25196608WSDLE5
Adder
8.083
25194608D.CRK4
Adder
1.55
270485AE1-090_GEN
Solar/Wind Harmer
0.566
270222AC2-111 GEN
Solar/Wind Harmer
7.593
25196008MFTGT1
Adder
1.255
970243AG2-164 GEN
Solar/Wind Harmer
23.909
970519AG2-331 GEN
Solar/Wind Harmer
16.063
970699AG2-449 GEN
Solar/Wind Harmer
10.626
972167AH1-666 GEN
Solar/Wind Harmer
7.416
958171AF2-111 GEN
Solar/Wind Harmer
23.159
270437AC2-090 C
Solar/Wind Harmer
5.138
944531AF1-118 GEN
Solar/Wind Harmer
32.165
962031AG1-047 GEN
Solar/Wind Harmer
2.774
957741AF2-068 GEN
Solar/Wind Harmer
13.765
270356AE2-297 GEN
Solar/Wind Harmer
4.184
946031AF1-268 GEN
Solar/Wind Harmer
7.613
958821AF2-173 GEN
Solar/Wind Harmer
12.842
270004AE1-209 GEN
Solar/Wind Harmer
5.013
24728705AND G3
Adder
7.25
24728505AND G1
Adder
3.466
24642205MAYFLWER
Adder
0.568
274772LINCOLN ;3U
Adder
7.514
274752CRETE EC ;2U
Adder
7.332
274753CRETE EC ;3U
Adder
7.332
274724RIVER EC ;11
Adder
15.751
316097T157 G90
Solar/Wind Helper
1.299
964991AG1-363 GEN
Solar/Wind Helper
4.135
238148AE2-230_GEN2
Solar/Wind Helper
0.417
23750701CROSSCHOOL
Solar/Wind Helper
1.155
237080AD1-060 GEN
Solar/Wind Helper
0.284
237038AE2-054 C
Solar/Wind Helper
0.226
235062AE1-101 C1
Solar/Wind Helper
1.38
238127S14_GEN_2
Solar/Wind Helper
0.641
23779801AA1-109
Solar/Wind Helper
0.162
238118U2-030_1
Solar/Wind Helper
0.26
970935AG2-582 GEN
50/50
1217.062
24318905MLG2
50/50
4.656
270471AD2-092_GEN
Solar/Wind Harmer
3.665
970879AG2-548 GEN
Solar/Wind Harmer
6.188
971073AG2-665 GEN
Solar/Wind Harmer
6.188
971073AG2-665 GEN
Solar/Wind Harmer
4.317
946101AF1-275 GEN
Solar/Wind Harmer
1.512
24685805CER G1
Adder
8.199
24685905CER G2
Adder
8.199
972269AH1-719 GEN
Adder
2.268
24723005RIVRG1
Adder
18.473
24723105RIVRG2
Adder
18.473
942861AE2-305 GEN
Solar/Wind Harmer
7.629
270518AE2-148 GEN
Solar/Wind Harmer
11.837
970077AG2-063 GEN
Solar/Wind Harmer
5.262
962581AG1-107 GEN
Solar/Wind Harmer
4.827
961491AF2-440 GEN
Solar/Wind Harmer
2.006
972159AH1-661 GEN
Adder
0.952
253394AE2-221_GEN
Solar/Wind Harmer
4.338
253398AE2-221_GEN2
Solar/Wind Harmer
4.338
253317AC1-085 GEN4
Solar/Wind Harmer
7.992
270186AC1-089 GEN
Solar/Wind Harmer
5.819
25326109MON D
Adder
1.252
253370AE2-315 SEC1
Adder
1.906
25322209TAIT E
Adder
9.269
25322209TAIT E
Adder
9.061
25183208HLCRTG
Solar/Wind Harmer
5.751
964601AG1-323 GEN
Solar/Wind Harmer
3.011
964601AG1-323 GEN
Solar/Wind Harmer
1.401
252509AD1-136 GEN
Solar/Wind Harmer
0.243
252519AF1-045_GEN
Solar/Wind Harmer
5.748
252516AE2-318_GEN
Solar/Wind Harmer
4.385
270224U2-072_GEN2
Solar/Wind Harmer
1.871
270227U2-072_GEN3
Solar/Wind Harmer
1.871
270228U2-072_GEN4
Solar/Wind Harmer
1.871
270231U2-072_GEN5
Solar/Wind Harmer
1.871
938701AE1-092 GEN
Solar/Wind Harmer
19.52
25194408D.CRK1
Adder
7.132
25194508D.CRK3
Adder
1.333
253378AE2-206_GEN
Solar/Wind Harmer
3.382
276820AF1-078_GEN
Solar/Wind Harmer
1.502
25326509SID D
Adder
1.231
970239AG2-162 GEN
Solar/Wind Harmer
10.183
24728805RICHG1
Adder
3.489
24728905RICHG2
Adder
3.489
970883AG2-550 GEN
Solar/Wind Harmer
9.215
970885AG2-551 GEN
Solar/Wind Harmer
2.143
270383AD1-128 GEN
Solar/Wind Harmer
5.623
24379505HDWTR1G C
Solar/Wind Harmer
7.277
270209AC1-174_GEN
Solar/Wind Harmer
5.136
926881AC1-175 GEN
Solar/Wind Harmer
5.136
247621Y3-024
Adder
0.222
944541AF1-119 GEN
Solar/Wind Harmer
3.847
960971AF2-388 GEN
Solar/Wind Harmer
10.038
270201AC2-176 GEN
Solar/Wind Harmer
4.717
964611AG1-324 GEN
Solar/Wind Harmer
1.082
964611AG1-324 GEN
Solar/Wind Harmer
0.48
970825AG2-519 GEN
Solar/Wind Harmer
9.671
960441AF2-335 GEN
Solar/Wind Harmer
9.16
247620Y3-023
Adder
0.412
274770LINCOLN ;1U
Adder
7.514
274771LINCOLN ;2U
Adder
7.514
238175AF1-290_GEN
Solar/Wind Helper
0.126
238169AE2-226 GEN1
Solar/Wind Helper
0.582
238170AE2-226 GEN2
Solar/Wind Helper
0.582
235020AA1-095 C
Solar/Wind Helper
0.044
23777901MDS_W4-102
Solar/Wind Helper
0.146
238120AE2-309 GEN
Solar/Wind Helper
0.406
237034AC2-136 C
Solar/Wind Helper
0.189
237002AB1-128_GEN
Solar/Wind Helper
0.369
235063AE1-101 C2
Solar/Wind Helper
1.38
237001AB1-127_GEN
Solar/Wind Helper
0.368
23777801MSM_W1-116
Solar/Wind Helper
0.096
270599AE1-208 GEN
Solar/Wind Harmer
0.76
270031AE2-169
Solar/Wind Harmer
0.76
23559101PLEAS2
50/50
11.213
23684101S70BUS1
50/50
0.313
23562301OGROV1
50/50
2.427
24721705FLATG2
Adder
23.442
962761AG1-125 GEN
Solar/Wind Harmer
34.974
970149AG2-104 GEN
Solar/Wind Harmer
43.193
970155AG2-107 GEN
Solar/Wind Harmer
15.25
270510AE1-227 GEN1
Solar/Wind Harmer
2.645
960001AF2-291 GEN
Solar/Wind Harmer
3.152
970947AG2-589 GEN
Solar/Wind Harmer
2.059
270331AC1-082 GEN3
Solar/Wind Harmer
0.466
927014AC1-188 GEN
Solar/Wind Harmer
1.606
270349AD2-093_GEN
Solar/Wind Harmer
3.665
270263AC1-001 GEN
Solar/Wind Harmer
1.044
24686105CER G3
Adder
8.253
24686505CER G6
Adder
8.242
270159DARBY CT4
Adder
8.691
24723205RIVRG3
Adder
18.473
253343AC1-166 GEN
Solar/Wind Harmer
1.064
253325AC1-069 GEN
Solar/Wind Harmer
1.027
970593AG2-378 GEN
Solar/Wind Harmer
1.949
253432AC1-085 GEN2
Solar/Wind Harmer
0.255
946171AF1-282 GEN
Solar/Wind Harmer
9.541
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
25326309TAIT D
Adder
1.041
960071AF2-298 GEN
Solar/Wind Harmer
4.732
252507AC2-088 GEN
Solar/Wind Harmer
1.7
270223U2-072_GEN1
Solar/Wind Harmer
1.871
270578AF1-285 GEN2
Solar/Wind Harmer
1.144
270391AF1-285 GEN3
Solar/Wind Harmer
1.144
25194608D.CRK4
Adder
1.55
25196808ZIMRHP
Adder
71.347
270462AD2-086
Solar/Wind Harmer
6.509
25196008MFTGT1
Adder
1.296
970333AG2-219 GEN
Solar/Wind Harmer
29.222
945681AF1-233 GEN
Solar/Wind Harmer
17.467
942081AE2-220 GEN
Solar/Wind Harmer
5.883
270239V3-007_GEN1
Solar/Wind Harmer
1.584
247536S-71 GEN
Solar/Wind Harmer
3.724
965651AG1-433 GEN
Solar/Wind Harmer
5.019
958861AF2-177 GEN
Solar/Wind Harmer
10.036
945371AF1-202 GEN
Solar/Wind Harmer
6.405
971995AH1-542 GEN
Solar/Wind Harmer
10.093
270005AE1-210 C O1
Solar/Wind Harmer
5.013
965031AG1-367 GEN
Solar/Wind Harmer
9.173
970825AG2-519 GEN
Solar/Wind Harmer
2.158
970091AG2-072 GEN
Adder
70.193
24728605AND G2
Adder
3.466
24639705ELKHART HY
Adder
0.137
274773LINCOLN ;4U
Adder
7.514
274774LINCOLN ;5U
Adder
7.514
274751CRETE EC ;1U
Adder
7.332
274754CRETE EC ;4U
Adder
7.332
274723RIVER EC ;12
Adder
15.938
274812UNIV PK N;8U
Adder
4.45
23583801GRNGAP
Solar/Wind Helper
4.858
316095T157 G97
Solar/Wind Helper
1.299
238147AE2-230_GEN1
Solar/Wind Helper
0.415
238149AF1-291A_GEN
Solar/Wind Helper
0.119
238108AE1-109 GEN1
Solar/Wind Helper
0.088
237061AD1-155 GEN
Solar/Wind Helper
0.045
238185AF2-356 C
Solar/Wind Helper
1.996
238221AF1-254 C O1
Solar/Wind Helper
0.228
235067AD1-061 GEN
Solar/Wind Helper
0.412
235531U2-073 GEN
Solar/Wind Helper
2.523
238117U2-030
Solar/Wind Helper
0.26
944201AF1-088_MTX
Adder
103.64
957141AF2-008_MTX
Adder
51.82
NYPJM->LTFIMP_NY
CLTF
4.417
LGEELTFEXP_LGEE->PJM
CLTF
6.111
WECLTFEXP_WEC->PJM
CLTF
3.336
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312
CPLELTFEXP_CPLE->PJM
CLTF
1.286
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.798
LAGNLTFEXP_LAGN->PJM
CLTF
13.832
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.925
TVALTFEXP_TVA->PJM
CLTF
6.876
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.614
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.188
MECLTFEXP_MEC->PJM
CLTF
14.066
SIGELTFEXP_SIGE->PJM
CLTF
0.455

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT7A_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT7A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:139.96 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5307.1
MW Contribution:15.25
Bus #Bus NameTypeMW Contribution
962771AG1-126 GEN
Solar/Wind Harmer
34.974
270330AC1-082 GEN2
Solar/Wind Harmer
0.789
270329AC1-082 GEN1
Solar/Wind Harmer
0.465
270054AF2-122 C O1
Solar/Wind Harmer
3.29
970879AG2-548 GEN
Solar/Wind Harmer
4.317
940611AE2-048 GEN
Solar/Wind Harmer
22.053
941391AE2-136 GEN
Solar/Wind Harmer
11.427
270520AE2-214 GEN
Solar/Wind Harmer
6.059
270459AD2-067 GEN
Solar/Wind Harmer
8.36
961821AG1-024 GEN
Solar/Wind Harmer
8.487
972203AH1-686 GEN
Adder
2.298
270432AC2-029 GEN
Solar/Wind Harmer
6.982
970689AG2-444 GEN
Solar/Wind Harmer
16.256
270269AC2-059
Solar/Wind Harmer
9.3
270156DARBY CT1
Adder
8.832
270157DARBY CT2
Adder
8.81
270158DARBY CT3
Adder
8.67
945631AF1-228 GEN
Solar/Wind Harmer
4.621
270284AF1-227 GEN1
Solar/Wind Harmer
5.57
270286AF1-227 GEN2
Solar/Wind Harmer
2.061
270287AF1-227 GEN3
Solar/Wind Harmer
2.061
971985AH1-537 GEN
Solar/Wind Harmer
17.522
253383AE2-342_GEN
Solar/Wind Harmer
0.869
241973AD2-163_GEN1
Solar/Wind Harmer
1.944
943861AF1-054 GEN
Solar/Wind Harmer
3.765
943851AF1-053 GEN
Solar/Wind Harmer
1.82
270340AC2-060 GEN
Solar/Wind Harmer
2.96
24477305BRIDGE
Adder
0.338
241972AD1-140 GEN
Solar/Wind Harmer
4.309
270367AC2-061_GEN
Solar/Wind Harmer
3.048
253372AE2-315 SEC3
Adder
1.803
253372AE2-315 SEC3
Adder
1.803
25306009OHH W.
Adder
2.735
270578AF1-285 GEN2
Solar/Wind Harmer
0.44
253349AC2-067 GEN
Solar/Wind Harmer
4.712
253400AC2-068 GEN
Solar/Wind Harmer
1.895
252524AE2-267 GEN
Solar/Wind Harmer
1.487
25196408WSDLE3
Adder
8.32
25196308WSDLE2
Adder
8.248
25196208WSDLE1
Adder
8.227
25196708WSDLE6
Adder
8.207
25196508WSDLE4
Adder
8
270302AB2-170 GEN
Solar/Wind Harmer
7.824
270317AD1-130_GEN
Solar/Wind Harmer
3
944031AF1-071 GEN
Solar/Wind Harmer
0.936
25196108MFTGT2
Adder
1.429
25196108MFTGT2
Adder
1.327
972163AH1-664 GEN
Solar/Wind Harmer
9.252
972165AH1-665 GEN
Solar/Wind Harmer
7.402
971673AH1-337 GEN
Solar/Wind Harmer
4.251
971029AG2-637 GEN
Solar/Wind Harmer
13.852
270543AE2-219 C
Solar/Wind Harmer
4.719
270240V3-007_GEN2
Solar/Wind Harmer
5.693
24729505KEY G4
Adder
5.961
958711AF2-162 GEN
Solar/Wind Harmer
0.929
965101AG1-375 GEN
Solar/Wind Harmer
9.182
945581AF1-223 GEN
Solar/Wind Harmer
4.163
961761AG1-017 GEN
Solar/Wind Harmer
0.393
970115AG2-085 GEN
Solar/Wind Harmer
3.664
274775LINCOLN ;6U
Adder
7.514
274776LINCOLN ;7U
Adder
7.514
274777LINCOLN ;8U
Adder
7.514
274814UNIV PK N;0U
Adder
4.489
274807UNIV PK N;3U
Adder
4.479
274805UNIV PK N;1U
Adder
4.459
274811UNIV PK N;7U
Adder
0.697
238152AF2-075_GEN
Solar/Wind Helper
0.593
23546401DTGZ2-030
Solar/Wind Helper
0.075
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
238208AF1-136 C
Solar/Wind Helper
0.18
237085AD2-009_GEN
Solar/Wind Helper
1.367
238126S14_GEN_1
Solar/Wind Helper
0.641
23559001PLEAS1
50/50
11.213
23684201S70BUS2
50/50
0.319
23562401OGROV2
50/50
2.411
24318805MLG1
50/50
6.319
24721905FLATG4
Adder
23.442
970153AG2-106 GEN
Solar/Wind Harmer
15.25
270512AE1-227 GEN2
Solar/Wind Harmer
2.245
971191AH1-055 GEN
Solar/Wind Harmer
22.406
957541AF2-048 GEN
Solar/Wind Harmer
1.601
270291AC1-194 GEN
Solar/Wind Harmer
10.629
961921AG1-034 GEN
Solar/Wind Harmer
12.731
960801AF2-371 GEN
Solar/Wind Harmer
2.533
964871AG1-351 GEN
Solar/Wind Harmer
1.749
270273AD2-016 GEN
Solar/Wind Harmer
2.659
972173AH1-669 GEN
Solar/Wind Harmer
4.984
241955AC1-078 GEN
Solar/Wind Harmer
7.382
24686205CER G4
Adder
8.21
24686405CER G5
Adder
8.177
942051AE2-217 GEN
Solar/Wind Harmer
17.654
253338AC1-165 GEN
Solar/Wind Harmer
1.064
253333AC1-068 GEN
Solar/Wind Harmer
1.027
241974AD2-163_GEN2
Solar/Wind Harmer
1.944
253415AE1-040 GEN
Solar/Wind Harmer
1.1
970605AG2-385 GEN
Solar/Wind Harmer
5.262
253406AD2-031_GEN
Solar/Wind Harmer
1.228
253316AC1-085 GEN3
Solar/Wind Harmer
7.992
253433AC1-085 GEN1
Solar/Wind Harmer
5.073
946181AF1-283 GEN
Solar/Wind Harmer
12.404
253303V4-073 C
Solar/Wind Harmer
0.11
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
942871AE2-306 GEN
Solar/Wind Harmer
0.858
270391AF1-285 GEN3
Solar/Wind Harmer
0.44
252510AF1-249 C
Solar/Wind Harmer
0.395
25196608WSDLE5
Adder
8.083
25194608D.CRK4
Adder
1.55
270485AE1-090_GEN
Solar/Wind Harmer
0.566
270222AC2-111 GEN
Solar/Wind Harmer
7.593
25196008MFTGT1
Adder
1.255
970243AG2-164 GEN
Solar/Wind Harmer
23.909
970519AG2-331 GEN
Solar/Wind Harmer
16.063
970699AG2-449 GEN
Solar/Wind Harmer
10.626
972167AH1-666 GEN
Solar/Wind Harmer
7.416
958171AF2-111 GEN
Solar/Wind Harmer
23.159
270437AC2-090 C
Solar/Wind Harmer
5.138
944531AF1-118 GEN
Solar/Wind Harmer
32.165
962031AG1-047 GEN
Solar/Wind Harmer
2.774
957741AF2-068 GEN
Solar/Wind Harmer
13.765
270356AE2-297 GEN
Solar/Wind Harmer
4.184
946031AF1-268 GEN
Solar/Wind Harmer
7.613
958821AF2-173 GEN
Solar/Wind Harmer
12.842
270004AE1-209 GEN
Solar/Wind Harmer
5.013
24728705AND G3
Adder
7.25
24728505AND G1
Adder
3.466
24642205MAYFLWER
Adder
0.568
274772LINCOLN ;3U
Adder
7.514
274752CRETE EC ;2U
Adder
7.332
274753CRETE EC ;3U
Adder
7.332
274724RIVER EC ;11
Adder
15.751
316097T157 G90
Solar/Wind Helper
1.299
964991AG1-363 GEN
Solar/Wind Helper
4.135
238148AE2-230_GEN2
Solar/Wind Helper
0.417
23750701CROSSCHOOL
Solar/Wind Helper
1.155
237080AD1-060 GEN
Solar/Wind Helper
0.284
237038AE2-054 C
Solar/Wind Helper
0.226
235062AE1-101 C1
Solar/Wind Helper
1.38
238127S14_GEN_2
Solar/Wind Helper
0.641
23779801AA1-109
Solar/Wind Helper
0.162
238118U2-030_1
Solar/Wind Helper
0.26
970935AG2-582 GEN
50/50
1217.062
24318905MLG2
50/50
4.656
270471AD2-092_GEN
Solar/Wind Harmer
3.665
970879AG2-548 GEN
Solar/Wind Harmer
6.188
971073AG2-665 GEN
Solar/Wind Harmer
6.188
971073AG2-665 GEN
Solar/Wind Harmer
4.317
946101AF1-275 GEN
Solar/Wind Harmer
1.512
24685805CER G1
Adder
8.199
24685905CER G2
Adder
8.199
972269AH1-719 GEN
Adder
2.268
24723005RIVRG1
Adder
18.473
24723105RIVRG2
Adder
18.473
942861AE2-305 GEN
Solar/Wind Harmer
7.629
270518AE2-148 GEN
Solar/Wind Harmer
11.837
970077AG2-063 GEN
Solar/Wind Harmer
5.262
962581AG1-107 GEN
Solar/Wind Harmer
4.827
961491AF2-440 GEN
Solar/Wind Harmer
2.006
972159AH1-661 GEN
Adder
0.952
253394AE2-221_GEN
Solar/Wind Harmer
4.338
253398AE2-221_GEN2
Solar/Wind Harmer
4.338
253317AC1-085 GEN4
Solar/Wind Harmer
7.992
270186AC1-089 GEN
Solar/Wind Harmer
5.819
25326109MON D
Adder
1.252
253370AE2-315 SEC1
Adder
1.906
25322209TAIT E
Adder
9.269
23559101PLEAS2
50/50
11.213
23684101S70BUS1
50/50
0.313
23562301OGROV1
50/50
2.427
24721705FLATG2
Adder
23.442
962761AG1-125 GEN
Solar/Wind Harmer
34.974
970149AG2-104 GEN
Solar/Wind Harmer
43.193
970155AG2-107 GEN
Solar/Wind Harmer
15.25
270510AE1-227 GEN1
Solar/Wind Harmer
2.645
960001AF2-291 GEN
Solar/Wind Harmer
3.152
970947AG2-589 GEN
Solar/Wind Harmer
2.059
270331AC1-082 GEN3
Solar/Wind Harmer
0.466
927014AC1-188 GEN
Solar/Wind Harmer
1.606
270349AD2-093_GEN
Solar/Wind Harmer
3.665
270263AC1-001 GEN
Solar/Wind Harmer
1.044
24686105CER G3
Adder
8.253
24686505CER G6
Adder
8.242
270159DARBY CT4
Adder
8.691
24723205RIVRG3
Adder
18.473
253343AC1-166 GEN
Solar/Wind Harmer
1.064
253325AC1-069 GEN
Solar/Wind Harmer
1.027
970593AG2-378 GEN
Solar/Wind Harmer
1.949
253432AC1-085 GEN2
Solar/Wind Harmer
0.255
946171AF1-282 GEN
Solar/Wind Harmer
9.541
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
25326309TAIT D
Adder
1.041
960071AF2-298 GEN
Solar/Wind Harmer
4.732
252507AC2-088 GEN
Solar/Wind Harmer
1.7
270223U2-072_GEN1
Solar/Wind Harmer
1.871
270578AF1-285 GEN2
Solar/Wind Harmer
1.144
270391AF1-285 GEN3
Solar/Wind Harmer
1.144
25194608D.CRK4
Adder
1.55
25196808ZIMRHP
Adder
71.347
270462AD2-086
Solar/Wind Harmer
6.509
25196008MFTGT1
Adder
1.296
970333AG2-219 GEN
Solar/Wind Harmer
29.222
945681AF1-233 GEN
Solar/Wind Harmer
17.467
942081AE2-220 GEN
Solar/Wind Harmer
5.883
270239V3-007_GEN1
Solar/Wind Harmer
1.584
247536S-71 GEN
Solar/Wind Harmer
3.724
965651AG1-433 GEN
Solar/Wind Harmer
5.019
958861AF2-177 GEN
Solar/Wind Harmer
10.036
945371AF1-202 GEN
Solar/Wind Harmer
6.405
971995AH1-542 GEN
Solar/Wind Harmer
10.093
270005AE1-210 C O1
Solar/Wind Harmer
5.013
965031AG1-367 GEN
Solar/Wind Harmer
9.173
970825AG2-519 GEN
Solar/Wind Harmer
2.158
970091AG2-072 GEN
Adder
70.193
24728605AND G2
Adder
3.466
24639705ELKHART HY
Adder
0.137
274773LINCOLN ;4U
Adder
7.514
274774LINCOLN ;5U
Adder
7.514
274751CRETE EC ;1U
Adder
7.332
274754CRETE EC ;4U
Adder
7.332
274723RIVER EC ;12
Adder
15.938
274812UNIV PK N;8U
Adder
4.45
23583801GRNGAP
Solar/Wind Helper
4.858
316095T157 G97
Solar/Wind Helper
1.299
238147AE2-230_GEN1
Solar/Wind Helper
0.415
238149AF1-291A_GEN
Solar/Wind Helper
0.119
238108AE1-109 GEN1
Solar/Wind Helper
0.088
237061AD1-155 GEN
Solar/Wind Helper
0.045
238185AF2-356 C
Solar/Wind Helper
1.996
238221AF1-254 C O1
Solar/Wind Helper
0.228
235067AD1-061 GEN
Solar/Wind Helper
0.412
235531U2-073 GEN
Solar/Wind Helper
2.523
238117U2-030
Solar/Wind Helper
0.26
25322209TAIT E
Adder
9.061
25183208HLCRTG
Solar/Wind Harmer
5.751
964601AG1-323 GEN
Solar/Wind Harmer
3.011
964601AG1-323 GEN
Solar/Wind Harmer
1.401
252509AD1-136 GEN
Solar/Wind Harmer
0.243
252519AF1-045_GEN
Solar/Wind Harmer
5.748
252516AE2-318_GEN
Solar/Wind Harmer
4.385
270224U2-072_GEN2
Solar/Wind Harmer
1.871
270227U2-072_GEN3
Solar/Wind Harmer
1.871
270228U2-072_GEN4
Solar/Wind Harmer
1.871
270231U2-072_GEN5
Solar/Wind Harmer
1.871
938701AE1-092 GEN
Solar/Wind Harmer
19.52
25194408D.CRK1
Adder
7.132
25194508D.CRK3
Adder
1.333
253378AE2-206_GEN
Solar/Wind Harmer
3.382
276820AF1-078_GEN
Solar/Wind Harmer
1.502
25326509SID D
Adder
1.231
970239AG2-162 GEN
Solar/Wind Harmer
10.183
24728805RICHG1
Adder
3.489
24728905RICHG2
Adder
3.489
970883AG2-550 GEN
Solar/Wind Harmer
9.215
970885AG2-551 GEN
Solar/Wind Harmer
2.143
270383AD1-128 GEN
Solar/Wind Harmer
5.623
24379505HDWTR1G C
Solar/Wind Harmer
7.277
270209AC1-174_GEN
Solar/Wind Harmer
5.136
926881AC1-175 GEN
Solar/Wind Harmer
5.136
247621Y3-024
Adder
0.222
944541AF1-119 GEN
Solar/Wind Harmer
3.847
960971AF2-388 GEN
Solar/Wind Harmer
10.038
270201AC2-176 GEN
Solar/Wind Harmer
4.717
964611AG1-324 GEN
Solar/Wind Harmer
1.082
964611AG1-324 GEN
Solar/Wind Harmer
0.48
970825AG2-519 GEN
Solar/Wind Harmer
9.671
960441AF2-335 GEN
Solar/Wind Harmer
9.16
247620Y3-023
Adder
0.412
274770LINCOLN ;1U
Adder
7.514
274771LINCOLN ;2U
Adder
7.514
238175AF1-290_GEN
Solar/Wind Helper
0.126
238169AE2-226 GEN1
Solar/Wind Helper
0.582
238170AE2-226 GEN2
Solar/Wind Helper
0.582
235020AA1-095 C
Solar/Wind Helper
0.044
23777901MDS_W4-102
Solar/Wind Helper
0.146
238120AE2-309 GEN
Solar/Wind Helper
0.406
237034AC2-136 C
Solar/Wind Helper
0.189
237002AB1-128_GEN
Solar/Wind Helper
0.369
235063AE1-101 C2
Solar/Wind Helper
1.38
237001AB1-127_GEN
Solar/Wind Helper
0.368
23777801MSM_W1-116
Solar/Wind Helper
0.096
270599AE1-208 GEN
Solar/Wind Harmer
0.76
270031AE2-169
Solar/Wind Harmer
0.76
944201AF1-088_MTX
Adder
103.64
957141AF2-008_MTX
Adder
51.82
NYPJM->LTFIMP_NY
CLTF
4.417
LGEELTFEXP_LGEE->PJM
CLTF
6.111
WECLTFEXP_WEC->PJM
CLTF
3.336
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312
CPLELTFEXP_CPLE->PJM
CLTF
1.286
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.798
LAGNLTFEXP_LAGN->PJM
CLTF
13.832
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.925
TVALTFEXP_TVA->PJM
CLTF
6.876
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.614
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.188
MECLTFEXP_MEC->PJM
CLTF
14.066
SIGELTFEXP_SIGE->PJM
CLTF
0.455

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT10A_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT10A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:139.86 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5303.43
MW Contribution:15.37
Bus #Bus NameTypeMW Contribution
962771AG1-126 GEN
Solar/Wind Harmer
35.245
270330AC1-082 GEN2
Solar/Wind Harmer
0.795
270329AC1-082 GEN1
Solar/Wind Harmer
0.468
270054AF2-122 C O1
Solar/Wind Harmer
3.32
940611AE2-048 GEN
Solar/Wind Harmer
22.287
941391AE2-136 GEN
Solar/Wind Harmer
11.549
970879AG2-548 GEN
Solar/Wind Harmer
4.353
270520AE2-214 GEN
Solar/Wind Harmer
6.113
270459AD2-067 GEN
Solar/Wind Harmer
8.438
961821AG1-024 GEN
Solar/Wind Harmer
8.566
270432AC2-029 GEN
Solar/Wind Harmer
7.042
970689AG2-444 GEN
Solar/Wind Harmer
16.397
270269AC2-059
Solar/Wind Harmer
9.378
972203AH1-686 GEN
Adder
2.313
270156DARBY CT1
Adder
8.909
270157DARBY CT2
Adder
8.887
270158DARBY CT3
Adder
8.745
945631AF1-228 GEN
Solar/Wind Harmer
4.662
270284AF1-227 GEN1
Solar/Wind Harmer
5.621
270286AF1-227 GEN2
Solar/Wind Harmer
2.079
270287AF1-227 GEN3
Solar/Wind Harmer
2.079
253383AE2-342_GEN
Solar/Wind Harmer
0.877
971985AH1-537 GEN
Solar/Wind Harmer
17.658
241973AD2-163_GEN1
Solar/Wind Harmer
1.962
943861AF1-054 GEN
Solar/Wind Harmer
3.799
943851AF1-053 GEN
Solar/Wind Harmer
1.836
270340AC2-060 GEN
Solar/Wind Harmer
2.985
24477305BRIDGE
Adder
0.341
241972AD1-140 GEN
Solar/Wind Harmer
4.346
270367AC2-061_GEN
Solar/Wind Harmer
3.072
253372AE2-315 SEC3
Adder
1.818
253372AE2-315 SEC3
Adder
1.818
25306009OHH W.
Adder
2.758
270578AF1-285 GEN2
Solar/Wind Harmer
0.444
253349AC2-067 GEN
Solar/Wind Harmer
4.752
253400AC2-068 GEN
Solar/Wind Harmer
1.911
252524AE2-267 GEN
Solar/Wind Harmer
1.499
25196408WSDLE3
Adder
8.387
25196308WSDLE2
Adder
8.314
25196208WSDLE1
Adder
8.294
25196708WSDLE6
Adder
8.273
25196508WSDLE4
Adder
8.064
270302AB2-170 GEN
Solar/Wind Harmer
7.9
270317AD1-130_GEN
Solar/Wind Harmer
3.028
944031AF1-071 GEN
Solar/Wind Harmer
0.944
25196108MFTGT2
Adder
1.44
25196108MFTGT2
Adder
1.337
972163AH1-664 GEN
Solar/Wind Harmer
9.324
972165AH1-665 GEN
Solar/Wind Harmer
7.459
971673AH1-337 GEN
Solar/Wind Harmer
4.287
971029AG2-637 GEN
Solar/Wind Harmer
13.968
270543AE2-219 C
Solar/Wind Harmer
4.759
270240V3-007_GEN2
Solar/Wind Harmer
5.741
24729505KEY G4
Adder
6.012
958711AF2-162 GEN
Solar/Wind Harmer
0.937
965101AG1-375 GEN
Solar/Wind Harmer
9.26
945581AF1-223 GEN
Solar/Wind Harmer
4.198
961761AG1-017 GEN
Solar/Wind Harmer
0.396
970115AG2-085 GEN
Solar/Wind Harmer
3.695
274775LINCOLN ;6U
Adder
7.577
274776LINCOLN ;7U
Adder
7.577
274777LINCOLN ;8U
Adder
7.577
274814UNIV PK N;0U
Adder
4.526
274807UNIV PK N;3U
Adder
4.517
274805UNIV PK N;1U
Adder
4.497
274811UNIV PK N;7U
Adder
0.593
238152AF2-075_GEN
Solar/Wind Helper
0.602
23546401DTGZ2-030
Solar/Wind Helper
0.076
238208AF1-136 C
Solar/Wind Helper
0.181
238109AE1-109 GEN2
Solar/Wind Helper
0.087
238110AE1-109 GEN3
Solar/Wind Helper
0.087
237085AD2-009_GEN
Solar/Wind Helper
1.378
3138216PACIFIC
Solar/Wind Helper
0.038
316411AF1-147_GEN1
Solar/Wind Helper
0.751
316415AF1-147_GEN2
Solar/Wind Helper
0.751
23559001PLEAS1
50/50
11.24
23684201S70BUS2
50/50
0.322
23562401OGROV2
50/50
2.431
24318805MLG1
50/50
6.369
23534401HANNIB
50/50
0.15
24721905FLATG4
Adder
23.592
970153AG2-106 GEN
Solar/Wind Harmer
15.368
270512AE1-227 GEN2
Solar/Wind Harmer
2.273
971191AH1-055 GEN
Solar/Wind Harmer
22.576
957541AF2-048 GEN
Solar/Wind Harmer
1.614
270291AC1-194 GEN
Solar/Wind Harmer
10.719
961921AG1-034 GEN
Solar/Wind Harmer
12.85
960801AF2-371 GEN
Solar/Wind Harmer
2.556
964871AG1-351 GEN
Solar/Wind Harmer
1.765
270273AD2-016 GEN
Solar/Wind Harmer
2.682
972173AH1-669 GEN
Solar/Wind Harmer
5.026
241955AC1-078 GEN
Solar/Wind Harmer
7.448
24686205CER G4
Adder
8.265
24686405CER G5
Adder
8.232
942051AE2-217 GEN
Solar/Wind Harmer
17.81
253338AC1-165 GEN
Solar/Wind Harmer
1.074
253333AC1-068 GEN
Solar/Wind Harmer
1.035
241974AD2-163_GEN2
Solar/Wind Harmer
1.962
253415AE1-040 GEN
Solar/Wind Harmer
1.109
970605AG2-385 GEN
Solar/Wind Harmer
5.308
253406AD2-031_GEN
Solar/Wind Harmer
1.238
253316AC1-085 GEN3
Solar/Wind Harmer
8.057
253433AC1-085 GEN1
Solar/Wind Harmer
5.115
946181AF1-283 GEN
Solar/Wind Harmer
12.504
253303V4-073 C
Solar/Wind Harmer
0.111
253370AE2-315 SEC1
Adder
1.922
253371AE2-315 SEC2
Adder
1.818
942871AE2-306 GEN
Solar/Wind Harmer
0.866
270391AF1-285 GEN3
Solar/Wind Harmer
0.444
252510AF1-249 C
Solar/Wind Harmer
0.398
25194608D.CRK4
Adder
1.563
25196608WSDLE5
Adder
8.148
270485AE1-090_GEN
Solar/Wind Harmer
0.571
270222AC2-111 GEN
Solar/Wind Harmer
7.655
25196008MFTGT1
Adder
1.265
970243AG2-164 GEN
Solar/Wind Harmer
24.096
970519AG2-331 GEN
Solar/Wind Harmer
16.189
970699AG2-449 GEN
Solar/Wind Harmer
10.709
972167AH1-666 GEN
Solar/Wind Harmer
7.473
958171AF2-111 GEN
Solar/Wind Harmer
23.339
270437AC2-090 C
Solar/Wind Harmer
5.18
944531AF1-118 GEN
Solar/Wind Harmer
32.44
962031AG1-047 GEN
Solar/Wind Harmer
2.797
957741AF2-068 GEN
Solar/Wind Harmer
13.882
946031AF1-268 GEN
Solar/Wind Harmer
7.677
958821AF2-173 GEN
Solar/Wind Harmer
12.949
270004AE1-209 GEN
Solar/Wind Harmer
5.055
270356AE2-297 GEN
Solar/Wind Harmer
4.219
24728705AND G3
Adder
7.308
24728505AND G1
Adder
3.494
24642205MAYFLWER
Adder
0.573
274772LINCOLN ;3U
Adder
7.577
274752CRETE EC ;2U
Adder
7.394
274753CRETE EC ;3U
Adder
7.394
274724RIVER EC ;11
Adder
15.884
316097T157 G90
Solar/Wind Helper
1.324
964991AG1-363 GEN
Solar/Wind Helper
4.195
238148AE2-230_GEN2
Solar/Wind Helper
0.423
237080AD1-060 GEN
Solar/Wind Helper
0.287
23750701CROSSCHOOL
Solar/Wind Helper
1.116
237038AE2-054 C
Solar/Wind Helper
0.228
235062AE1-101 C1
Solar/Wind Helper
1.393
23779801AA1-109
Solar/Wind Helper
0.164
23559101PLEAS2
50/50
11.24
23684101S70BUS1
50/50
0.316
23562301OGROV1
50/50
2.447
24721705FLATG2
Adder
23.592
962761AG1-125 GEN
Solar/Wind Harmer
35.245
970149AG2-104 GEN
Solar/Wind Harmer
43.528
970155AG2-107 GEN
Solar/Wind Harmer
15.368
270510AE1-227 GEN1
Solar/Wind Harmer
2.678
960001AF2-291 GEN
Solar/Wind Harmer
3.176
970947AG2-589 GEN
Solar/Wind Harmer
2.074
270331AC1-082 GEN3
Solar/Wind Harmer
0.469
927014AC1-188 GEN
Solar/Wind Harmer
1.618
270349AD2-093_GEN
Solar/Wind Harmer
3.698
270263AC1-001 GEN
Solar/Wind Harmer
1.052
270159DARBY CT4
Adder
8.767
24686105CER G3
Adder
8.308
24686505CER G6
Adder
8.298
24723205RIVRG3
Adder
18.592
253343AC1-166 GEN
Solar/Wind Harmer
1.074
253325AC1-069 GEN
Solar/Wind Harmer
1.035
970593AG2-378 GEN
Solar/Wind Harmer
1.966
253432AC1-085 GEN2
Solar/Wind Harmer
0.257
946171AF1-282 GEN
Solar/Wind Harmer
9.619
253370AE2-315 SEC1
Adder
1.922
253371AE2-315 SEC2
Adder
1.818
25326309TAIT D
Adder
1.05
960071AF2-298 GEN
Solar/Wind Harmer
4.772
270223U2-072_GEN1
Solar/Wind Harmer
1.889
252507AC2-088 GEN
Solar/Wind Harmer
1.713
270578AF1-285 GEN2
Solar/Wind Harmer
1.155
270391AF1-285 GEN3
Solar/Wind Harmer
1.155
25194608D.CRK4
Adder
1.563
25196808ZIMRHP
Adder
71.915
270462AD2-086
Solar/Wind Harmer
6.572
25196008MFTGT1
Adder
1.306
970333AG2-219 GEN
Solar/Wind Harmer
29.451
945681AF1-233 GEN
Solar/Wind Harmer
17.602
247536S-71 GEN
Solar/Wind Harmer
3.755
942081AE2-220 GEN
Solar/Wind Harmer
5.932
270239V3-007_GEN1
Solar/Wind Harmer
1.597
971995AH1-542 GEN
Solar/Wind Harmer
10.198
965651AG1-433 GEN
Solar/Wind Harmer
5.062
958861AF2-177 GEN
Solar/Wind Harmer
10.121
945371AF1-202 GEN
Solar/Wind Harmer
6.459
270005AE1-210 C O1
Solar/Wind Harmer
5.055
965031AG1-367 GEN
Solar/Wind Harmer
9.249
970825AG2-519 GEN
Solar/Wind Harmer
2.176
970091AG2-072 GEN
Adder
70.733
24728605AND G2
Adder
3.494
24639705ELKHART HY
Adder
0.139
274773LINCOLN ;4U
Adder
7.577
274774LINCOLN ;5U
Adder
7.577
274751CRETE EC ;1U
Adder
7.394
274754CRETE EC ;4U
Adder
7.394
274723RIVER EC ;12
Adder
16.072
274812UNIV PK N;8U
Adder
4.487
23583801GRNGAP
Solar/Wind Helper
4.952
316095T157 G97
Solar/Wind Helper
1.324
238147AE2-230_GEN1
Solar/Wind Helper
0.422
238149AF1-291A_GEN
Solar/Wind Helper
0.12
237061AD1-155 GEN
Solar/Wind Helper
0.045
238221AF1-254 C O1
Solar/Wind Helper
0.23
238108AE1-109 GEN1
Solar/Wind Helper
0.087
235067AD1-061 GEN
Solar/Wind Helper
0.416
237030AB1-096 C
Solar/Wind Helper
0.06
970935AG2-582 GEN
50/50
1215.723
24318905MLG2
50/50
4.724
270471AD2-092_GEN
Solar/Wind Harmer
3.698
970879AG2-548 GEN
Solar/Wind Harmer
6.239
971073AG2-665 GEN
Solar/Wind Harmer
6.239
971073AG2-665 GEN
Solar/Wind Harmer
4.353
946101AF1-275 GEN
Solar/Wind Harmer
1.525
972269AH1-719 GEN
Adder
2.293
24685805CER G1
Adder
8.254
24685905CER G2
Adder
8.254
24723005RIVRG1
Adder
18.592
24723105RIVRG2
Adder
18.592
942861AE2-305 GEN
Solar/Wind Harmer
7.696
270518AE2-148 GEN
Solar/Wind Harmer
11.94
970077AG2-063 GEN
Solar/Wind Harmer
5.308
962581AG1-107 GEN
Solar/Wind Harmer
4.865
961491AF2-440 GEN
Solar/Wind Harmer
2.022
972159AH1-661 GEN
Adder
0.962
253394AE2-221_GEN
Solar/Wind Harmer
4.373
253398AE2-221_GEN2
Solar/Wind Harmer
4.373
253317AC1-085 GEN4
Solar/Wind Harmer
8.057
25326109MON D
Adder
1.263
270186AC1-089 GEN
Solar/Wind Harmer
5.865
253370AE2-315 SEC1
Adder
1.922
25322209TAIT E
Adder
9.347
25322209TAIT E
Adder
9.137
964601AG1-323 GEN
Solar/Wind Harmer
3.04
964601AG1-323 GEN
Solar/Wind Harmer
1.414
25183208HLCRTG
Solar/Wind Harmer
5.797
270224U2-072_GEN2
Solar/Wind Harmer
1.889
270227U2-072_GEN3
Solar/Wind Harmer
1.889
270228U2-072_GEN4
Solar/Wind Harmer
1.889
270231U2-072_GEN5
Solar/Wind Harmer
1.889
252509AD1-136 GEN
Solar/Wind Harmer
0.245
252519AF1-045_GEN
Solar/Wind Harmer
5.794
252516AE2-318_GEN
Solar/Wind Harmer
4.42
938701AE1-092 GEN
Solar/Wind Harmer
19.71
25194408D.CRK1
Adder
7.189
25194508D.CRK3
Adder
1.344
253378AE2-206_GEN
Solar/Wind Harmer
3.413
276820AF1-078_GEN
Solar/Wind Harmer
1.516
25326509SID D
Adder
1.242
970239AG2-162 GEN
Solar/Wind Harmer
10.263
24728805RICHG1
Adder
3.517
24728905RICHG2
Adder
3.517
970883AG2-550 GEN
Solar/Wind Harmer
9.293
970885AG2-551 GEN
Solar/Wind Harmer
2.161
270383AD1-128 GEN
Solar/Wind Harmer
5.669
24379505HDWTR1G C
Solar/Wind Harmer
7.337
270209AC1-174_GEN
Solar/Wind Harmer
5.178
926881AC1-175 GEN
Solar/Wind Harmer
5.178
247621Y3-024
Adder
0.223
944541AF1-119 GEN
Solar/Wind Harmer
3.879
960971AF2-388 GEN
Solar/Wind Harmer
10.123
270201AC2-176 GEN
Solar/Wind Harmer
4.758
964611AG1-324 GEN
Solar/Wind Harmer
1.091
964611AG1-324 GEN
Solar/Wind Harmer
0.484
970825AG2-519 GEN
Solar/Wind Harmer
9.752
960441AF2-335 GEN
Solar/Wind Harmer
9.237
247620Y3-023
Adder
0.416
274770LINCOLN ;1U
Adder
7.577
274771LINCOLN ;2U
Adder
7.577
238175AF1-290_GEN
Solar/Wind Helper
0.128
238169AE2-226 GEN1
Solar/Wind Helper
0.591
238170AE2-226 GEN2
Solar/Wind Helper
0.591
235020AA1-095 C
Solar/Wind Helper
0.044
23777901MDS_W4-102
Solar/Wind Helper
0.148
237034AC2-136 C
Solar/Wind Helper
0.192
237002AB1-128_GEN
Solar/Wind Helper
0.372
237001AB1-127_GEN
Solar/Wind Helper
0.372
235063AE1-101 C2
Solar/Wind Helper
1.393
23777801MSM_W1-116
Solar/Wind Helper
0.097
237025AB1-124 C
Solar/Wind Helper
0.14
237006AB1-125 GEN
Solar/Wind Helper
0.105
270599AE1-208 GEN
Solar/Wind Harmer
0.766
270031AE2-169
Solar/Wind Harmer
0.766
944201AF1-088_MTX
Adder
104.45
957141AF2-008_MTX
Adder
52.225
NYPJM->LTFIMP_NY
CLTF
4.434
LGEELTFEXP_LGEE->PJM
CLTF
6.157
WECLTFEXP_WEC->PJM
CLTF
3.363
AG2-052LTFEXP_AG2-052->PJM
LTF
0.21
AH1-155LTFEXP_AH1-155->PJM
LTF
0.314
CPLELTFEXP_CPLE->PJM
CLTF
1.246
CBM West 2LTFEXP_CBM-W2->PJM
CBM
103.491
LAGNLTFEXP_LAGN->PJM
CLTF
13.912
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.88
TVALTFEXP_TVA->PJM
CLTF
6.914
CBM West 1LTFEXP_CBM-W1->PJM
CBM
123.724
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.351
MECLTFEXP_MEC->PJM
CLTF
14.175
SIGELTFEXP_SIGE->PJM
CLTF
0.458

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-502T_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-502T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:139.36 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5284.61
MW Contribution:18.83
Bus #Bus NameTypeMW Contribution
962771AG1-126 GEN
Solar/Wind Harmer
29.494
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0.006
970879AG2-548 GEN
Solar/Wind Harmer
6.304
940611AE2-048 GEN
Solar/Wind Harmer
17.215
941391AE2-136 GEN
Solar/Wind Harmer
9.698
270520AE2-214 GEN
Solar/Wind Harmer
0.011
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.145
972203AH1-686 GEN
Adder
2.298
270432AC2-029 GEN
Solar/Wind Harmer
3.085
970689AG2-444 GEN
Solar/Wind Harmer
14.206
270269AC2-059
Solar/Wind Harmer
0.004
270156DARBY CT1
Adder
8.832
270157DARBY CT2
Adder
8.81
270158DARBY CT3
Adder
8.67
945631AF1-228 GEN
Solar/Wind Harmer
0
270284AF1-227 GEN1
Solar/Wind Harmer
0.009
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
971985AH1-537 GEN
Solar/Wind Harmer
2.037
253383AE2-342_GEN
Solar/Wind Harmer
0.002
241973AD2-163_GEN1
Solar/Wind Harmer
0.005
943861AF1-054 GEN
Solar/Wind Harmer
2.627
943851AF1-053 GEN
Solar/Wind Harmer
1.82
270340AC2-060 GEN
Solar/Wind Harmer
0.008
24477305BRIDGE
Adder
0.338
241972AD1-140 GEN
Solar/Wind Harmer
0.734
270367AC2-061_GEN
Solar/Wind Harmer
0.005
253372AE2-315 SEC3
Adder
1.803
253372AE2-315 SEC3
Adder
1.803
25306009OHH W.
Adder
2.735
270578AF1-285 GEN2
Solar/Wind Harmer
0.44
253349AC2-067 GEN
Solar/Wind Harmer
2.077
253400AC2-068 GEN
Solar/Wind Harmer
0.835
252524AE2-267 GEN
Solar/Wind Harmer
0.002
25196408WSDLE3
Adder
8.32
25196308WSDLE2
Adder
8.248
25196208WSDLE1
Adder
8.227
25196708WSDLE6
Adder
8.207
25196508WSDLE4
Adder
8
270302AB2-170 GEN
Solar/Wind Harmer
0.004
270317AD1-130_GEN
Solar/Wind Harmer
0.009
971653AH1-327 GEN
Solar/Wind Harmer
0.917
25196108MFTGT2
Adder
1.429
25196108MFTGT2
Adder
1.327
972163AH1-664 GEN
Solar/Wind Harmer
7.187
972165AH1-665 GEN
Solar/Wind Harmer
5.756
971673AH1-337 GEN
Solar/Wind Harmer
4.191
971029AG2-637 GEN
Solar/Wind Harmer
9.664
270543AE2-219 C
Solar/Wind Harmer
0.004
270240V3-007_GEN2
Solar/Wind Harmer
0.002
24729505KEY G4
Adder
5.961
965101AG1-375 GEN
Solar/Wind Harmer
6.406
945581AF1-223 GEN
Solar/Wind Harmer
0
970115AG2-085 GEN
Solar/Wind Harmer
2.556
971609AH1-304 GEN
Solar/Wind Harmer
1.043
270024AE2-089 GEN
Solar/Wind Harmer
0.007
270594AE1-207 GEN
Solar/Wind Harmer
7.147
270071AF1-092 GEN
Solar/Wind Harmer
12.224
970289AG2-191 GEN
Solar/Wind Harmer
1.211
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
8.573
965051AG1-369 GEN
Solar/Wind Harmer
3.147
971347AH1-153 GEN
Solar/Wind Harmer
9.454
965041AG1-368 GEN
Solar/Wind Harmer
6.297
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
3.74
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.796
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.008
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
963841AG1-237 GEN
Solar/Wind Harmer
2.71
971771AH1-392 GEN
Solar/Wind Harmer
6.248
971769AH1-391 GEN
Solar/Wind Harmer
6.974
247607V1-011 GEN
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
2.801
274775LINCOLN ;6U
Adder
7.514
274776LINCOLN ;7U
Adder
7.514
274777LINCOLN ;8U
Adder
7.514
274814UNIV PK N;0U
Adder
4.489
274807UNIV PK N;3U
Adder
4.479
274805UNIV PK N;1U
Adder
4.459
274811UNIV PK N;7U
Adder
0.697
960591AF2-350 GEN
Solar/Wind Harmer
6.191
270399AC1-101 GEN
Solar/Wind Harmer
1.957
270400AC1-102 GEN
Solar/Wind Harmer
1.957
970833AG2-524 GEN
Solar/Wind Harmer
6.792
970833AG2-524 GEN
Solar/Wind Harmer
4.528
970179AG2-119 GEN
Solar/Wind Harmer
5.506
274863CRW1-WTG
Solar/Wind Harmer
0.002
23559101PLEAS2
50/50
11.213
23684101S70BUS1
50/50
0.313
23562301OGROV1
50/50
2.427
24721705FLATG2
Adder
23.442
962761AG1-125 GEN
Solar/Wind Harmer
29.494
970149AG2-104 GEN
Solar/Wind Harmer
31.855
970155AG2-107 GEN
Solar/Wind Harmer
18.834
270510AE1-227 GEN1
Solar/Wind Harmer
1.907
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
970947AG2-589 GEN
Solar/Wind Harmer
0.239
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
927014AC1-188 GEN
Solar/Wind Harmer
0.004
270349AD2-093_GEN
Solar/Wind Harmer
0.005
270263AC1-001 GEN
Solar/Wind Harmer
0.698
24686105CER G3
Adder
8.253
24686505CER G6
Adder
8.242
270159DARBY CT4
Adder
8.691
24723205RIVRG3
Adder
18.473
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.011
970593AG2-378 GEN
Solar/Wind Harmer
1.53
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.657
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
25326309TAIT D
Adder
1.041
960071AF2-298 GEN
Solar/Wind Harmer
3.297
252507AC2-088 GEN
Solar/Wind Harmer
0.3
270223U2-072_GEN1
Solar/Wind Harmer
0.001
25194608D.CRK4
Adder
1.55
25196808ZIMRHP
Adder
71.347
270462AD2-086
Solar/Wind Harmer
0.014
25196008MFTGT1
Adder
1.296
970333AG2-219 GEN
Solar/Wind Harmer
4.624
945681AF1-233 GEN
Solar/Wind Harmer
12.186
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.707
247536S-71 GEN
Solar/Wind Harmer
0.258
965651AG1-433 GEN
Solar/Wind Harmer
1.879
958861AF2-177 GEN
Solar/Wind Harmer
2.776
945371AF1-202 GEN
Solar/Wind Harmer
0.001
971995AH1-542 GEN
Solar/Wind Harmer
2.347
970773AG2-487 GEN
Solar/Wind Harmer
1.131
270005AE1-210 C O1
Solar/Wind Harmer
1.387
965031AG1-367 GEN
Solar/Wind Harmer
6.4
970825AG2-519 GEN
Solar/Wind Harmer
2.27
970091AG2-072 GEN
Adder
70.193
270032AE2-172
Solar/Wind Harmer
4.254
970291AG2-192 GEN
Solar/Wind Harmer
0.829
970245AG2-165 GEN
Solar/Wind Harmer
2.761
276903AD2-071 C
Solar/Wind Harmer
7.113
965011AG1-365 GEN
Solar/Wind Harmer
6.333
247521TR3_G114
Solar/Wind Harmer
0.23
270246TR4_N_V150
Solar/Wind Harmer
0.041
24728605AND G2
Adder
3.466
339216AC1-074 GEN
Solar/Wind Harmer
0.172
965421AG1-410 GEN
Solar/Wind Harmer
18.858
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
7.853
246936BC-WTG1
Solar/Wind Harmer
0.255
24791305MDL-5G
Solar/Wind Harmer
0.001
270489AE1-102 GEN1
Solar/Wind Harmer
0.817
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.162
24695305TIMB G C
Solar/Wind Harmer
0.002
270055AF2-134 C O1
Solar/Wind Harmer
0.005
970373AG2-245 GEN
Solar/Wind Harmer
13.169
270063AE2-323 C
Solar/Wind Harmer
0.005
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.002
24639705ELKHART HY
Adder
0.137
963741AG1-226 GEN
Solar/Wind Harmer
14.772
945111AF1-176 GEN
Solar/Wind Harmer
11.105
270505AE1-170 C O1
Solar/Wind Harmer
6.535
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
274773LINCOLN ;4U
Adder
7.514
274774LINCOLN ;5U
Adder
7.514
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.241
274751CRETE EC ;1U
Adder
7.332
274754CRETE EC ;4U
Adder
7.332
274723RIVER EC ;12
Adder
15.938
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.45
276776AD2-060 GEN
Solar/Wind Harmer
0.646
941551AE2-152 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
4.613
276691AA1-018 GEN1
Solar/Wind Harmer
0.745
276901AD2-066 C O1
Solar/Wind Harmer
0.006
944231AF1-091 GEN
Solar/Wind Harmer
1.635
971997AH1-543 GEN
Solar/Wind Harmer
3.22
23583801GRNGAP
Solar/Wind Helper
4.858
316095T157 G97
Solar/Wind Helper
1.299
238147AE2-230_GEN1
Solar/Wind Helper
0.415
238149AF1-291A_GEN
Solar/Wind Helper
0.119
238108AE1-109 GEN1
Solar/Wind Helper
0.088
237061AD1-155 GEN
Solar/Wind Helper
0.045
238185AF2-356 C
Solar/Wind Helper
1.996
238221AF1-254 C O1
Solar/Wind Helper
0.228
235067AD1-061 GEN
Solar/Wind Helper
0.412
235531U2-073 GEN
Solar/Wind Helper
2.523
238117U2-030
Solar/Wind Helper
0.26
23559001PLEAS1
50/50
11.213
23684201S70BUS2
50/50
0.319
23562401OGROV2
50/50
2.411
24318805MLG1
50/50
6.319
24721905FLATG4
Adder
23.442
970153AG2-106 GEN
Solar/Wind Harmer
18.834
270512AE1-227 GEN2
Solar/Wind Harmer
1.907
971191AH1-055 GEN
Solar/Wind Harmer
18.237
270291AC1-194 GEN
Solar/Wind Harmer
5.533
961921AG1-034 GEN
Solar/Wind Harmer
6.218
270273AD2-016 GEN
Solar/Wind Harmer
0.721
972173AH1-669 GEN
Solar/Wind Harmer
3.478
241955AC1-078 GEN
Solar/Wind Harmer
0.006
24686205CER G4
Adder
8.21
24686405CER G5
Adder
8.177
942051AE2-217 GEN
Solar/Wind Harmer
12.316
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.011
241974AD2-163_GEN2
Solar/Wind Harmer
0.005
253415AE1-040 GEN
Solar/Wind Harmer
0.003
970605AG2-385 GEN
Solar/Wind Harmer
4.136
253406AD2-031_GEN
Solar/Wind Harmer
0.499
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
8.654
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
270391AF1-285 GEN3
Solar/Wind Harmer
0.44
970191AG2-125 GEN
Solar/Wind Harmer
1.697
252510AF1-249 C
Solar/Wind Harmer
0.051
25196608WSDLE5
Adder
8.083
25194608D.CRK4
Adder
1.55
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270222AC2-111 GEN
Solar/Wind Harmer
3.293
25196008MFTGT1
Adder
1.255
970243AG2-164 GEN
Solar/Wind Harmer
3.783
970519AG2-331 GEN
Solar/Wind Harmer
16.815
970699AG2-449 GEN
Solar/Wind Harmer
1.617
972167AH1-666 GEN
Solar/Wind Harmer
5.174
958171AF2-111 GEN
Solar/Wind Harmer
16.157
270437AC2-090 C
Solar/Wind Harmer
0.003
944531AF1-118 GEN
Solar/Wind Harmer
28.735
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
9.603
270356AE2-297 GEN
Solar/Wind Harmer
0.009
946031AF1-268 GEN
Solar/Wind Harmer
6.09
958821AF2-173 GEN
Solar/Wind Harmer
8.959
270004AE1-209 GEN
Solar/Wind Harmer
1.387
971617AH1-308 GEN
Solar/Wind Harmer
5.319
970289AG2-191 GEN
Solar/Wind Harmer
0.701
970291AG2-192 GEN
Solar/Wind Harmer
0.638
970513AG2-328 GEN
Solar/Wind Harmer
2.761
970517AG2-330 GEN
Solar/Wind Harmer
16.566
247642Z2-115 C
Solar/Wind Harmer
0.003
270043AE2-236 GEN
Solar/Wind Harmer
4.072
959331AF2-224 GEN
Solar/Wind Harmer
4.433
965021AG1-366 GEN
Solar/Wind Harmer
2.111
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.041
24728705AND G3
Adder
7.25
24728505AND G1
Adder
3.466
970349AG2-230 GEN
Solar/Wind Harmer
9.454
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.281
270491AE1-102 GEN2
Solar/Wind Harmer
0.817
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970031AG2-029 GEN
Solar/Wind Harmer
4.079
270535AF1-215 GEN1
Solar/Wind Harmer
0.008
270053AF1-130 C
Solar/Wind Harmer
1.414
247643Z2-116 C
Solar/Wind Harmer
0
24642205MAYFLWER
Adder
0.568
945111AF1-176 GEN
Solar/Wind Harmer
5.045
274772LINCOLN ;3U
Adder
7.514
274752CRETE EC ;2U
Adder
7.332
274753CRETE EC ;3U
Adder
7.332
274724RIVER EC ;11
Adder
15.751
970193AG2-126 GEN
Solar/Wind Harmer
9.3
276806AD2-047 C O1
Solar/Wind Harmer
3.508
970941AG2-585 GEN
Solar/Wind Harmer
7.739
276897AD1-100 C
Solar/Wind Harmer
0.008
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
20.212
270258AD1-119 GEN
Solar/Wind Harmer
0.002
276893AG1-478 C
Solar/Wind Harmer
0.245
24441205WTRV SLR C
Solar/Wind Harmer
0
943121AE2-341 GEN
Solar/Wind Harmer
10.327
943591AF1-030 GEN
Solar/Wind Harmer
6.867
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
270404AC1-167 GEN
Solar/Wind Harmer
0.003
276805AD2-038 GEN
Solar/Wind Harmer
0.002
316097T157 G90
Solar/Wind Helper
1.299
964991AG1-363 GEN
Solar/Wind Helper
4.135
238148AE2-230_GEN2
Solar/Wind Helper
0.417
23750701CROSSCHOOL
Solar/Wind Helper
1.155
237080AD1-060 GEN
Solar/Wind Helper
0.284
237038AE2-054 C
Solar/Wind Helper
0.226
235062AE1-101 C1
Solar/Wind Helper
1.38
238127S14_GEN_2
Solar/Wind Helper
0.641
23779801AA1-109
Solar/Wind Helper
0.162
238118U2-030_1
Solar/Wind Helper
0.26
274864CRW2-WTG
Solar/Wind Harmer
0.002
970169AG2-114 GEN
Solar/Wind Harmer
6.145
276868AE1-113 GEN
Solar/Wind Harmer
1.231
276882AE2-255 GEN
Solar/Wind Harmer
0.717
238152AF2-075_GEN
Solar/Wind Helper
0.593
23546401DTGZ2-030
Solar/Wind Helper
0.075
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
238208AF1-136 C
Solar/Wind Helper
0.18
237085AD2-009_GEN
Solar/Wind Helper
1.367
238126S14_GEN_1
Solar/Wind Helper
0.641
970935AG2-582 GEN
50/50
1217.062
24318905MLG2
50/50
4.656
270471AD2-092_GEN
Solar/Wind Harmer
0.005
971073AG2-665 GEN
Solar/Wind Harmer
6.304
24685805CER G1
Adder
8.199
24685905CER G2
Adder
8.199
972269AH1-719 GEN
Adder
2.268
24723005RIVRG1
Adder
18.473
24723105RIVRG2
Adder
18.473
942861AE2-305 GEN
Solar/Wind Harmer
5.322
270518AE2-148 GEN
Solar/Wind Harmer
0.589
970077AG2-063 GEN
Solar/Wind Harmer
3.909
962581AG1-107 GEN
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
0.952
253394AE2-221_GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0.008
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
270186AC1-089 GEN
Solar/Wind Harmer
0.004
25326109MON D
Adder
1.252
253370AE2-315 SEC1
Adder
1.906
25322209TAIT E
Adder
9.269
25322209TAIT E
Adder
9.061
25183208HLCRTG
Solar/Wind Harmer
0.01
964601AG1-323 GEN
Solar/Wind Harmer
2.647
964601AG1-323 GEN
Solar/Wind Harmer
1.765
252509AD1-136 GEN
Solar/Wind Harmer
0.033
252519AF1-045_GEN
Solar/Wind Harmer
5.748
252516AE2-318_GEN
Solar/Wind Harmer
5.098
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
10.591
971655AH1-328 GEN
Solar/Wind Harmer
2.34
25194408D.CRK1
Adder
7.132
25194508D.CRK3
Adder
1.333
253378AE2-206_GEN
Solar/Wind Harmer
0.003
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
2.833
25326509SID D
Adder
1.231
970239AG2-162 GEN
Solar/Wind Harmer
1.617
24728805RICHG1
Adder
3.489
24728905RICHG2
Adder
3.489
970883AG2-550 GEN
Solar/Wind Harmer
6.429
970885AG2-551 GEN
Solar/Wind Harmer
2.143
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
247621Y3-024
Adder
0.222
944541AF1-119 GEN
Solar/Wind Harmer
0.429
960971AF2-388 GEN
Solar/Wind Harmer
3.759
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.48
970825AG2-519 GEN
Solar/Wind Harmer
7.086
960441AF2-335 GEN
Solar/Wind Harmer
6.391
270599AE1-208 GEN
Solar/Wind Harmer
5.854
270031AE2-169
Solar/Wind Harmer
3.512
971613AH1-306 GEN
Solar/Wind Harmer
3.063
942221AE2-234 GEN
Solar/Wind Harmer
0.032
970321AG2-212 GEN
Solar/Wind Harmer
2.761
970611AG2-400 GEN
Solar/Wind Harmer
6.333
970627AG2-408 GEN
Solar/Wind Harmer
1.9
970235AG2-159 GEN
Solar/Wind Harmer
3.847
970235AG2-159 GEN
Solar/Wind Harmer
2.207
339221AD2-048_GEN
Solar/Wind Harmer
0.004
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
971199AH1-059 GEN
Solar/Wind Harmer
2.513
246938BC-WTG3
Solar/Wind Harmer
0.228
246937BC-WTG2
Solar/Wind Harmer
0.255
972043AH1-570 GEN
Solar/Wind Harmer
1.633
972045AH1-571 GEN
Solar/Wind Harmer
1.308
966841AG1-555 GEN
Solar/Wind Harmer
0.709
944971AF1-162 GEN
Solar/Wind Harmer
6.265
965681AG1-436 GEN
Solar/Wind Harmer
7.82
965791AG1-447 GEN
Solar/Wind Harmer
5.734
270216AD2-079_GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.412
270526AF1-158 GEN
Solar/Wind Harmer
0.008
24441505OLIV SLR
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
3.641
957891AF2-083 GEN
Solar/Wind Harmer
0.001
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
4.56
961051AF2-396 GEN
Solar/Wind Harmer
12.428
961051AF2-396 GEN
Solar/Wind Harmer
8.285
274770LINCOLN ;1U
Adder
7.514
274771LINCOLN ;2U
Adder
7.514
971125AH1-004 GEN
Solar/Wind Harmer
2.483
970107AG2-081 GEN
Solar/Wind Harmer
1.862
960161AF2-307 GEN
Solar/Wind Harmer
4.096
945391AF1-204 GEN
Solar/Wind Harmer
6.587
274888KELLY CRK;1U
Solar/Wind Harmer
0.364
274887GEN-1.85
Solar/Wind Harmer
0.163
276843GEN-1.7
Solar/Wind Harmer
0.2
958011AF2-095 GEN
Solar/Wind Harmer
8.915
970623AG2-406 GEN
Solar/Wind Harmer
1.132
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
241960AC2-195 GEN
Solar/Wind Harmer
0.005
958481AF2-142 GEN
Solar/Wind Harmer
9.231
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.833
971573AH1-285 GEN
Solar/Wind Harmer
1.146
958491AF2-143 GEN
Solar/Wind Harmer
9.212
274879MINONK ;1U
Solar/Wind Harmer
0.259
238175AF1-290_GEN
Solar/Wind Helper
0.126
238169AE2-226 GEN1
Solar/Wind Helper
0.582
238170AE2-226 GEN2
Solar/Wind Helper
0.582
235020AA1-095 C
Solar/Wind Helper
0.044
23777901MDS_W4-102
Solar/Wind Helper
0.146
238120AE2-309 GEN
Solar/Wind Helper
0.406
237034AC2-136 C
Solar/Wind Helper
0.189
237002AB1-128_GEN
Solar/Wind Helper
0.369
235063AE1-101 C2
Solar/Wind Helper
1.38
237001AB1-127_GEN
Solar/Wind Helper
0.368
23777801MSM_W1-116
Solar/Wind Helper
0.096
962691AG1-118 GEN
Solar/Wind Harmer
3.447
944201AF1-088_MTX
Adder
103.64
957141AF2-008_MTX
Adder
51.82
NYPJM->LTFIMP_NY
CLTF
4.417
LGEELTFEXP_LGEE->PJM
CLTF
6.111
WECLTFEXP_WEC->PJM
CLTF
3.336
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312
CPLELTFEXP_CPLE->PJM
CLTF
1.286
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.798
LAGNLTFEXP_LAGN->PJM
CLTF
13.832
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.925
TVALTFEXP_TVA->PJM
CLTF
6.876
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.614
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.188
MECLTFEXP_MEC->PJM
CLTF
14.066
SIGELTFEXP_SIGE->PJM
CLTF
0.455

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-028_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:139.32 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5282.91
MW Contribution:18.83
Bus #Bus NameTypeMW Contribution
23559101PLEAS2
50/50
11.213
23684101S70BUS1
50/50
0.313
23562301OGROV1
50/50
2.427
24721705FLATG2
Adder
23.442
962761AG1-125 GEN
Solar/Wind Harmer
29.494
970149AG2-104 GEN
Solar/Wind Harmer
31.855
970155AG2-107 GEN
Solar/Wind Harmer
18.834
270510AE1-227 GEN1
Solar/Wind Harmer
1.907
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
970947AG2-589 GEN
Solar/Wind Harmer
0.239
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
927014AC1-188 GEN
Solar/Wind Harmer
0.004
270349AD2-093_GEN
Solar/Wind Harmer
0.005
270263AC1-001 GEN
Solar/Wind Harmer
0.698
24686105CER G3
Adder
8.253
24686505CER G6
Adder
8.242
270159DARBY CT4
Adder
8.691
24723205RIVRG3
Adder
18.473
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.011
970593AG2-378 GEN
Solar/Wind Harmer
1.53
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.657
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
25326309TAIT D
Adder
1.041
960071AF2-298 GEN
Solar/Wind Harmer
3.297
252507AC2-088 GEN
Solar/Wind Harmer
0.3
270223U2-072_GEN1
Solar/Wind Harmer
0.001
25194608D.CRK4
Adder
1.55
25196808ZIMRHP
Adder
71.347
270462AD2-086
Solar/Wind Harmer
0.014
25196008MFTGT1
Adder
1.296
970333AG2-219 GEN
Solar/Wind Harmer
4.624
945681AF1-233 GEN
Solar/Wind Harmer
12.186
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.707
247536S-71 GEN
Solar/Wind Harmer
0.258
965651AG1-433 GEN
Solar/Wind Harmer
1.879
958861AF2-177 GEN
Solar/Wind Harmer
2.776
945371AF1-202 GEN
Solar/Wind Harmer
0.001
971995AH1-542 GEN
Solar/Wind Harmer
2.347
970773AG2-487 GEN
Solar/Wind Harmer
1.131
270005AE1-210 C O1
Solar/Wind Harmer
1.387
965031AG1-367 GEN
Solar/Wind Harmer
6.4
970825AG2-519 GEN
Solar/Wind Harmer
2.27
970091AG2-072 GEN
Adder
70.193
270032AE2-172
Solar/Wind Harmer
4.254
970291AG2-192 GEN
Solar/Wind Harmer
0.829
970245AG2-165 GEN
Solar/Wind Harmer
2.761
276903AD2-071 C
Solar/Wind Harmer
7.113
965011AG1-365 GEN
Solar/Wind Harmer
6.333
247521TR3_G114
Solar/Wind Harmer
0.23
270246TR4_N_V150
Solar/Wind Harmer
0.041
24728605AND G2
Adder
3.466
339216AC1-074 GEN
Solar/Wind Harmer
0.172
965421AG1-410 GEN
Solar/Wind Harmer
18.858
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
7.853
246936BC-WTG1
Solar/Wind Harmer
0.255
24791305MDL-5G
Solar/Wind Harmer
0.001
270489AE1-102 GEN1
Solar/Wind Harmer
0.817
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.162
24695305TIMB G C
Solar/Wind Harmer
0.002
270055AF2-134 C O1
Solar/Wind Harmer
0.005
970373AG2-245 GEN
Solar/Wind Harmer
13.169
270063AE2-323 C
Solar/Wind Harmer
0.005
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.002
24639705ELKHART HY
Adder
0.137
963741AG1-226 GEN
Solar/Wind Harmer
14.772
945111AF1-176 GEN
Solar/Wind Harmer
11.105
270505AE1-170 C O1
Solar/Wind Harmer
6.535
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
274773LINCOLN ;4U
Adder
7.514
274774LINCOLN ;5U
Adder
7.514
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.241
274751CRETE EC ;1U
Adder
7.332
274754CRETE EC ;4U
Adder
7.332
274723RIVER EC ;12
Adder
15.938
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.45
276776AD2-060 GEN
Solar/Wind Harmer
0.646
941551AE2-152 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
4.613
276691AA1-018 GEN1
Solar/Wind Harmer
0.745
276901AD2-066 C O1
Solar/Wind Harmer
0.006
944231AF1-091 GEN
Solar/Wind Harmer
1.635
971997AH1-543 GEN
Solar/Wind Harmer
3.22
23583801GRNGAP
Solar/Wind Helper
4.858
316095T157 G97
Solar/Wind Helper
1.299
238147AE2-230_GEN1
Solar/Wind Helper
0.415
238149AF1-291A_GEN
Solar/Wind Helper
0.119
238108AE1-109 GEN1
Solar/Wind Helper
0.088
237061AD1-155 GEN
Solar/Wind Helper
0.045
238185AF2-356 C
Solar/Wind Helper
1.996
238221AF1-254 C O1
Solar/Wind Helper
0.228
235067AD1-061 GEN
Solar/Wind Helper
0.412
235531U2-073 GEN
Solar/Wind Helper
2.523
238117U2-030
Solar/Wind Helper
0.26
23559001PLEAS1
50/50
11.213
23684201S70BUS2
50/50
0.319
23562401OGROV2
50/50
2.411
24318805MLG1
50/50
6.319
24721905FLATG4
Adder
23.442
970153AG2-106 GEN
Solar/Wind Harmer
18.834
270512AE1-227 GEN2
Solar/Wind Harmer
1.907
971191AH1-055 GEN
Solar/Wind Harmer
18.237
270291AC1-194 GEN
Solar/Wind Harmer
5.533
961921AG1-034 GEN
Solar/Wind Harmer
6.218
270273AD2-016 GEN
Solar/Wind Harmer
0.721
972173AH1-669 GEN
Solar/Wind Harmer
3.478
241955AC1-078 GEN
Solar/Wind Harmer
0.006
24686205CER G4
Adder
8.21
24686405CER G5
Adder
8.177
942051AE2-217 GEN
Solar/Wind Harmer
12.316
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.011
241974AD2-163_GEN2
Solar/Wind Harmer
0.005
253415AE1-040 GEN
Solar/Wind Harmer
0.003
970605AG2-385 GEN
Solar/Wind Harmer
4.136
253406AD2-031_GEN
Solar/Wind Harmer
0.499
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
8.654
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
270391AF1-285 GEN3
Solar/Wind Harmer
0.44
970191AG2-125 GEN
Solar/Wind Harmer
1.697
252510AF1-249 C
Solar/Wind Harmer
0.051
25196608WSDLE5
Adder
8.083
25194608D.CRK4
Adder
1.55
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270222AC2-111 GEN
Solar/Wind Harmer
3.293
25196008MFTGT1
Adder
1.255
970243AG2-164 GEN
Solar/Wind Harmer
3.783
970519AG2-331 GEN
Solar/Wind Harmer
16.815
970699AG2-449 GEN
Solar/Wind Harmer
1.617
972167AH1-666 GEN
Solar/Wind Harmer
5.174
958171AF2-111 GEN
Solar/Wind Harmer
16.157
270437AC2-090 C
Solar/Wind Harmer
0.003
944531AF1-118 GEN
Solar/Wind Harmer
28.735
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
9.603
270356AE2-297 GEN
Solar/Wind Harmer
0.009
946031AF1-268 GEN
Solar/Wind Harmer
6.09
958821AF2-173 GEN
Solar/Wind Harmer
8.959
270004AE1-209 GEN
Solar/Wind Harmer
1.387
971617AH1-308 GEN
Solar/Wind Harmer
5.319
970289AG2-191 GEN
Solar/Wind Harmer
0.701
970291AG2-192 GEN
Solar/Wind Harmer
0.638
970513AG2-328 GEN
Solar/Wind Harmer
2.761
970517AG2-330 GEN
Solar/Wind Harmer
16.566
247642Z2-115 C
Solar/Wind Harmer
0.003
270043AE2-236 GEN
Solar/Wind Harmer
4.072
959331AF2-224 GEN
Solar/Wind Harmer
4.433
965021AG1-366 GEN
Solar/Wind Harmer
2.111
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.041
24728705AND G3
Adder
7.25
24728505AND G1
Adder
3.466
970349AG2-230 GEN
Solar/Wind Harmer
9.454
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.281
270491AE1-102 GEN2
Solar/Wind Harmer
0.817
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970031AG2-029 GEN
Solar/Wind Harmer
4.079
270535AF1-215 GEN1
Solar/Wind Harmer
0.008
270053AF1-130 C
Solar/Wind Harmer
1.414
247643Z2-116 C
Solar/Wind Harmer
0
24642205MAYFLWER
Adder
0.568
945111AF1-176 GEN
Solar/Wind Harmer
5.045
274772LINCOLN ;3U
Adder
7.514
274752CRETE EC ;2U
Adder
7.332
274753CRETE EC ;3U
Adder
7.332
274724RIVER EC ;11
Adder
15.751
970193AG2-126 GEN
Solar/Wind Harmer
9.3
276806AD2-047 C O1
Solar/Wind Harmer
3.508
970941AG2-585 GEN
Solar/Wind Harmer
7.739
276897AD1-100 C
Solar/Wind Harmer
0.008
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
20.212
270258AD1-119 GEN
Solar/Wind Harmer
0.002
276893AG1-478 C
Solar/Wind Harmer
0.245
24441205WTRV SLR C
Solar/Wind Harmer
0
943121AE2-341 GEN
Solar/Wind Harmer
10.327
943591AF1-030 GEN
Solar/Wind Harmer
6.867
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
270404AC1-167 GEN
Solar/Wind Harmer
0.003
276805AD2-038 GEN
Solar/Wind Harmer
0.002
316097T157 G90
Solar/Wind Helper
1.299
964991AG1-363 GEN
Solar/Wind Helper
4.135
238148AE2-230_GEN2
Solar/Wind Helper
0.417
23750701CROSSCHOOL
Solar/Wind Helper
1.155
237080AD1-060 GEN
Solar/Wind Helper
0.284
237038AE2-054 C
Solar/Wind Helper
0.226
235062AE1-101 C1
Solar/Wind Helper
1.38
238127S14_GEN_2
Solar/Wind Helper
0.641
23779801AA1-109
Solar/Wind Helper
0.162
238118U2-030_1
Solar/Wind Helper
0.26
962771AG1-126 GEN
Solar/Wind Harmer
29.494
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0.006
970879AG2-548 GEN
Solar/Wind Harmer
6.304
940611AE2-048 GEN
Solar/Wind Harmer
17.215
941391AE2-136 GEN
Solar/Wind Harmer
9.698
270520AE2-214 GEN
Solar/Wind Harmer
0.011
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.145
972203AH1-686 GEN
Adder
2.298
270432AC2-029 GEN
Solar/Wind Harmer
3.085
970689AG2-444 GEN
Solar/Wind Harmer
14.206
270269AC2-059
Solar/Wind Harmer
0.004
270156DARBY CT1
Adder
8.832
270157DARBY CT2
Adder
8.81
270158DARBY CT3
Adder
8.67
945631AF1-228 GEN
Solar/Wind Harmer
0
270284AF1-227 GEN1
Solar/Wind Harmer
0.009
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
971985AH1-537 GEN
Solar/Wind Harmer
2.037
253383AE2-342_GEN
Solar/Wind Harmer
0.002
241973AD2-163_GEN1
Solar/Wind Harmer
0.005
943861AF1-054 GEN
Solar/Wind Harmer
2.627
943851AF1-053 GEN
Solar/Wind Harmer
1.82
270340AC2-060 GEN
Solar/Wind Harmer
0.008
24477305BRIDGE
Adder
0.338
241972AD1-140 GEN
Solar/Wind Harmer
0.734
270367AC2-061_GEN
Solar/Wind Harmer
0.005
253372AE2-315 SEC3
Adder
1.803
253372AE2-315 SEC3
Adder
1.803
25306009OHH W.
Adder
2.735
270578AF1-285 GEN2
Solar/Wind Harmer
0.44
253349AC2-067 GEN
Solar/Wind Harmer
2.077
253400AC2-068 GEN
Solar/Wind Harmer
0.835
252524AE2-267 GEN
Solar/Wind Harmer
0.002
25196408WSDLE3
Adder
8.32
25196308WSDLE2
Adder
8.248
25196208WSDLE1
Adder
8.227
25196708WSDLE6
Adder
8.207
25196508WSDLE4
Adder
8
270302AB2-170 GEN
Solar/Wind Harmer
0.004
270317AD1-130_GEN
Solar/Wind Harmer
0.009
971653AH1-327 GEN
Solar/Wind Harmer
0.917
25196108MFTGT2
Adder
1.429
25196108MFTGT2
Adder
1.327
972163AH1-664 GEN
Solar/Wind Harmer
7.187
972165AH1-665 GEN
Solar/Wind Harmer
5.756
971673AH1-337 GEN
Solar/Wind Harmer
4.191
971029AG2-637 GEN
Solar/Wind Harmer
9.664
270543AE2-219 C
Solar/Wind Harmer
0.004
270240V3-007_GEN2
Solar/Wind Harmer
0.002
24729505KEY G4
Adder
5.961
965101AG1-375 GEN
Solar/Wind Harmer
6.406
945581AF1-223 GEN
Solar/Wind Harmer
0
970115AG2-085 GEN
Solar/Wind Harmer
2.556
971609AH1-304 GEN
Solar/Wind Harmer
1.043
270024AE2-089 GEN
Solar/Wind Harmer
0.007
270594AE1-207 GEN
Solar/Wind Harmer
7.147
270071AF1-092 GEN
Solar/Wind Harmer
12.224
970289AG2-191 GEN
Solar/Wind Harmer
1.211
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
8.573
965051AG1-369 GEN
Solar/Wind Harmer
3.147
971347AH1-153 GEN
Solar/Wind Harmer
9.454
965041AG1-368 GEN
Solar/Wind Harmer
6.297
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
3.74
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.796
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.008
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
963841AG1-237 GEN
Solar/Wind Harmer
2.71
971771AH1-392 GEN
Solar/Wind Harmer
6.248
971769AH1-391 GEN
Solar/Wind Harmer
6.974
247607V1-011 GEN
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
2.801
274775LINCOLN ;6U
Adder
7.514
274776LINCOLN ;7U
Adder
7.514
274777LINCOLN ;8U
Adder
7.514
274814UNIV PK N;0U
Adder
4.489
274807UNIV PK N;3U
Adder
4.479
274805UNIV PK N;1U
Adder
4.459
274811UNIV PK N;7U
Adder
0.697
960591AF2-350 GEN
Solar/Wind Harmer
6.191
270399AC1-101 GEN
Solar/Wind Harmer
1.957
270400AC1-102 GEN
Solar/Wind Harmer
1.957
970833AG2-524 GEN
Solar/Wind Harmer
6.792
970833AG2-524 GEN
Solar/Wind Harmer
4.528
970179AG2-119 GEN
Solar/Wind Harmer
5.506
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
970169AG2-114 GEN
Solar/Wind Harmer
6.145
276868AE1-113 GEN
Solar/Wind Harmer
1.231
276882AE2-255 GEN
Solar/Wind Harmer
0.717
238152AF2-075_GEN
Solar/Wind Helper
0.593
23546401DTGZ2-030
Solar/Wind Helper
0.075
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
238208AF1-136 C
Solar/Wind Helper
0.18
237085AD2-009_GEN
Solar/Wind Helper
1.367
238126S14_GEN_1
Solar/Wind Helper
0.641
970935AG2-582 GEN
50/50
1217.062
24318905MLG2
50/50
4.656
270471AD2-092_GEN
Solar/Wind Harmer
0.005
971073AG2-665 GEN
Solar/Wind Harmer
6.304
24685805CER G1
Adder
8.199
24685905CER G2
Adder
8.199
972269AH1-719 GEN
Adder
2.268
24723005RIVRG1
Adder
18.473
24723105RIVRG2
Adder
18.473
942861AE2-305 GEN
Solar/Wind Harmer
5.322
270518AE2-148 GEN
Solar/Wind Harmer
0.589
970077AG2-063 GEN
Solar/Wind Harmer
3.909
962581AG1-107 GEN
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
0.952
253394AE2-221_GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0.008
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
270186AC1-089 GEN
Solar/Wind Harmer
0.004
25326109MON D
Adder
1.252
253370AE2-315 SEC1
Adder
1.906
25322209TAIT E
Adder
9.269
25322209TAIT E
Adder
9.061
25183208HLCRTG
Solar/Wind Harmer
0.01
964601AG1-323 GEN
Solar/Wind Harmer
2.647
964601AG1-323 GEN
Solar/Wind Harmer
1.765
252509AD1-136 GEN
Solar/Wind Harmer
0.033
252519AF1-045_GEN
Solar/Wind Harmer
5.748
252516AE2-318_GEN
Solar/Wind Harmer
5.098
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
10.591
971655AH1-328 GEN
Solar/Wind Harmer
2.34
25194408D.CRK1
Adder
7.132
25194508D.CRK3
Adder
1.333
253378AE2-206_GEN
Solar/Wind Harmer
0.003
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
2.833
25326509SID D
Adder
1.231
970239AG2-162 GEN
Solar/Wind Harmer
1.617
24728805RICHG1
Adder
3.489
24728905RICHG2
Adder
3.489
970883AG2-550 GEN
Solar/Wind Harmer
6.429
970885AG2-551 GEN
Solar/Wind Harmer
2.143
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
247621Y3-024
Adder
0.222
944541AF1-119 GEN
Solar/Wind Harmer
0.429
960971AF2-388 GEN
Solar/Wind Harmer
3.759
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.48
970825AG2-519 GEN
Solar/Wind Harmer
7.086
960441AF2-335 GEN
Solar/Wind Harmer
6.391
270599AE1-208 GEN
Solar/Wind Harmer
5.854
270031AE2-169
Solar/Wind Harmer
3.512
971613AH1-306 GEN
Solar/Wind Harmer
3.063
942221AE2-234 GEN
Solar/Wind Harmer
0.032
970321AG2-212 GEN
Solar/Wind Harmer
2.761
970611AG2-400 GEN
Solar/Wind Harmer
6.333
970627AG2-408 GEN
Solar/Wind Harmer
1.9
970235AG2-159 GEN
Solar/Wind Harmer
3.847
970235AG2-159 GEN
Solar/Wind Harmer
2.207
339221AD2-048_GEN
Solar/Wind Harmer
0.004
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
971199AH1-059 GEN
Solar/Wind Harmer
2.513
246938BC-WTG3
Solar/Wind Harmer
0.228
246937BC-WTG2
Solar/Wind Harmer
0.255
972043AH1-570 GEN
Solar/Wind Harmer
1.633
972045AH1-571 GEN
Solar/Wind Harmer
1.308
966841AG1-555 GEN
Solar/Wind Harmer
0.709
944971AF1-162 GEN
Solar/Wind Harmer
6.265
965681AG1-436 GEN
Solar/Wind Harmer
7.82
965791AG1-447 GEN
Solar/Wind Harmer
5.734
270216AD2-079_GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.412
270526AF1-158 GEN
Solar/Wind Harmer
0.008
24441505OLIV SLR
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
3.641
957891AF2-083 GEN
Solar/Wind Harmer
0.001
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
4.56
961051AF2-396 GEN
Solar/Wind Harmer
12.428
961051AF2-396 GEN
Solar/Wind Harmer
8.285
274770LINCOLN ;1U
Adder
7.514
274771LINCOLN ;2U
Adder
7.514
971125AH1-004 GEN
Solar/Wind Harmer
2.483
970107AG2-081 GEN
Solar/Wind Harmer
1.862
960161AF2-307 GEN
Solar/Wind Harmer
4.096
945391AF1-204 GEN
Solar/Wind Harmer
6.587
274888KELLY CRK;1U
Solar/Wind Harmer
0.364
274887GEN-1.85
Solar/Wind Harmer
0.163
276843GEN-1.7
Solar/Wind Harmer
0.2
958011AF2-095 GEN
Solar/Wind Harmer
8.915
970623AG2-406 GEN
Solar/Wind Harmer
1.132
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
241960AC2-195 GEN
Solar/Wind Harmer
0.005
958481AF2-142 GEN
Solar/Wind Harmer
9.231
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.833
971573AH1-285 GEN
Solar/Wind Harmer
1.146
958491AF2-143 GEN
Solar/Wind Harmer
9.212
274879MINONK ;1U
Solar/Wind Harmer
0.259
238175AF1-290_GEN
Solar/Wind Helper
0.126
238169AE2-226 GEN1
Solar/Wind Helper
0.582
238170AE2-226 GEN2
Solar/Wind Helper
0.582
235020AA1-095 C
Solar/Wind Helper
0.044
23777901MDS_W4-102
Solar/Wind Helper
0.146
238120AE2-309 GEN
Solar/Wind Helper
0.406
237034AC2-136 C
Solar/Wind Helper
0.189
237002AB1-128_GEN
Solar/Wind Helper
0.369
235063AE1-101 C2
Solar/Wind Helper
1.38
237001AB1-127_GEN
Solar/Wind Helper
0.368
23777801MSM_W1-116
Solar/Wind Helper
0.096
962691AG1-118 GEN
Solar/Wind Harmer
3.447
944201AF1-088_MTX
Adder
103.64
957141AF2-008_MTX
Adder
51.82
NYPJM->LTFIMP_NY
CLTF
4.417
LGEELTFEXP_LGEE->PJM
CLTF
6.111
WECLTFEXP_WEC->PJM
CLTF
3.336
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312
CPLELTFEXP_CPLE->PJM
CLTF
1.286
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.798
LAGNLTFEXP_LAGN->PJM
CLTF
13.832
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.925
TVALTFEXP_TVA->PJM
CLTF
6.876
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.614
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.188
MECLTFEXP_MEC->PJM
CLTF
14.066
SIGELTFEXP_SIGE->PJM
CLTF
0.455

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-024_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.75 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4950.27
MW Contribution:17.95
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
7.1
23559101PLEAS2
50/50
6.365
962761AG1-125 GEN
Solar/Wind Harmer
41.173
970149AG2-104 GEN
Solar/Wind Harmer
50.849
970155AG2-107 GEN
Solar/Wind Harmer
17.953
270349AD2-093_GEN
Solar/Wind Harmer
4.477
24721705FLATG2
Adder
24.144
270159DARBY CT4
Adder
10.266
970593AG2-378 GEN
Solar/Wind Harmer
2.315
270223U2-072_GEN1
Solar/Wind Harmer
2.287
270578AF1-285 GEN2
Solar/Wind Harmer
1.399
270391AF1-285 GEN3
Solar/Wind Harmer
1.399
253343AC1-166 GEN
Solar/Wind Harmer
1.243
253325AC1-069 GEN
Solar/Wind Harmer
1.199
270462AD2-086
Solar/Wind Harmer
7.958
971995AH1-542 GEN
Solar/Wind Harmer
12.515
270263AC1-001 GEN
Solar/Wind Harmer
1.179
25326309TAIT D
Adder
1.2
960071AF2-298 GEN
Solar/Wind Harmer
5.454
253370AE2-315 SEC1
Adder
2.189
253371AE2-315 SEC2
Adder
2.071
927014AC1-188 GEN
Solar/Wind Harmer
1.729
241813AF1-122_GEN
Solar/Wind Harmer
6.978
246936BC-WTG1
Solar/Wind Harmer
4.237
270489AE1-102 GEN1
Solar/Wind Harmer
1.407
965421AG1-410 GEN
Solar/Wind Harmer
32.464
960001AF2-291 GEN
Solar/Wind Harmer
3.264
253432AC1-085 GEN2
Solar/Wind Harmer
0.289
946171AF1-282 GEN
Solar/Wind Harmer
10.789
247521TR3_G114
Solar/Wind Harmer
3.623
270246TR4_N_V150
Solar/Wind Harmer
0.916
965011AG1-365 GEN
Solar/Wind Harmer
10.775
24695305TIMB G C
Solar/Wind Harmer
5.916
965651AG1-433 GEN
Solar/Wind Harmer
5.83
958861AF2-177 GEN
Solar/Wind Harmer
11.644
247536S-71 GEN
Solar/Wind Harmer
4.305
25194608D.CRK4
Adder
1.747
945371AF1-202 GEN
Solar/Wind Harmer
7.414
252507AC2-088 GEN
Solar/Wind Harmer
1.904
270063AE2-323 C
Solar/Wind Harmer
2.336
25196808ZIMRHP
Adder
80.055
24639705ELKHART HY
Adder
0.162
25196008MFTGT1
Adder
1.456
274751CRETE EC ;1U
Adder
8.515
274754CRETE EC ;4U
Adder
8.515
274773LINCOLN ;4U
Adder
8.715
274774LINCOLN ;5U
Adder
8.715
274723RIVER EC ;12
Adder
18.501
274812UNIV PK N;8U
Adder
5.162
24728605AND G2
Adder
3.945
274801UNIV PARK;4U
Adder
5.993
274676JOLIET 29;8U
Adder
31.445
274732ELWOOD EC;7P
Adder
16.844
274674JOLIET 9 ;6U
Adder
15.776
274745AC1-111 GEN9
Adder
5.705
970091AG2-072 GEN
Adder
78.03
316095T157 G97
Solar/Wind Helper
1.508
23583801GRNGAP
Solar/Wind Helper
5.618
238185AF2-356 C
Solar/Wind Helper
2.662
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.043
235531U2-073 GEN
Solar/Wind Helper
3.301
238117U2-030
Solar/Wind Helper
0.344
238147AE2-230_GEN1
Solar/Wind Helper
0.496
238149AF1-291A_GEN
Solar/Wind Helper
0.142
23751201ROTHROCK
Solar/Wind Helper
0.832
23562501BACKB
Solar/Wind Helper
1.017
237061AD1-155 GEN
Solar/Wind Helper
0.053
238221AF1-254 C O1
Solar/Wind Helper
0.275
235067AD1-061 GEN
Solar/Wind Helper
0.498
23751101LEADS_P59
Solar/Wind Helper
1.424
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.034
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.347
223402AF1-300 C
Solar/Wind Helper
0.369
205917AD1-020 ES
Solar/Wind Helper
0.37
233918AB1-142 GEN
Solar/Wind Helper
0.504
233982AB2-133 GEN
Solar/Wind Helper
0.359
233994AC2-023 GEN
Solar/Wind Helper
0.965
233996TM1833_GEN
Solar/Wind Helper
0.262
233997TMININ_4.2
Solar/Wind Helper
0.262
232406W1-004 FULL
Solar/Wind Helper
0.509
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.233
233971AC1-093 C
Solar/Wind Helper
0.359
230430AE1-229_GEN
Solar/Wind Helper
3.385
316044AC1-158 PL1
Solar/Wind Helper
1.296
316450AC1-158 RIC
Solar/Wind Helper
0.346
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.111
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.354
219276PARKLANDSO C
Solar/Wind Helper
0.09
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
963161AG1-165 GEN
Solar/Wind Helper
0.441
970245AG2-165 GEN
Solar/Wind Harmer
4.981
962771AG1-126 GEN
Solar/Wind Harmer
41.173
270459AD2-067 GEN
Solar/Wind Harmer
10.252
961821AG1-024 GEN
Solar/Wind Harmer
10.408
270054AF2-122 C O1
Solar/Wind Harmer
3.995
972239AH1-704 GEN
Adder
2.671
270284AF1-227 GEN1
Solar/Wind Harmer
6.806
270286AF1-227 GEN2
Solar/Wind Harmer
2.518
270287AF1-227 GEN3
Solar/Wind Harmer
2.518
270520AE2-214 GEN
Solar/Wind Harmer
7.284
253383AE2-342_GEN
Solar/Wind Harmer
1.047
241973AD2-163_GEN1
Solar/Wind Harmer
2.334
943861AF1-054 GEN
Solar/Wind Harmer
4.494
943851AF1-053 GEN
Solar/Wind Harmer
2.172
945631AF1-228 GEN
Solar/Wind Harmer
5.47
270156DARBY CT1
Adder
10.432
270157DARBY CT2
Adder
10.407
270158DARBY CT3
Adder
10.24
270578AF1-285 GEN2
Solar/Wind Harmer
0.538
970689AG2-444 GEN
Solar/Wind Harmer
18.845
270432AC2-029 GEN
Solar/Wind Harmer
8.059
270302AB2-170 GEN
Solar/Wind Harmer
9.566
270317AD1-130_GEN
Solar/Wind Harmer
3.667
270269AC2-059
Solar/Wind Harmer
10.62
940611AE2-048 GEN
Solar/Wind Harmer
24.866
941391AE2-136 GEN
Solar/Wind Harmer
12.885
241972AD1-140 GEN
Solar/Wind Harmer
5.031
270340AC2-060 GEN
Solar/Wind Harmer
3.353
958581AF2-149 GEN
Solar/Wind Harmer
4.732
970179AG2-119 GEN
Solar/Wind Harmer
8.844
970879AG2-548 GEN
Solar/Wind Harmer
4.736
253372AE2-315 SEC3
Adder
2.071
253372AE2-315 SEC3
Adder
2.071
25306009OHH W.
Adder
3.141
253349AC2-067 GEN
Solar/Wind Harmer
5.421
253400AC2-068 GEN
Solar/Wind Harmer
2.18
957201AF2-014 GEN
Solar/Wind Harmer
4.91
270435AC2-044 GEN
Solar/Wind Harmer
2.165
965051AG1-369 GEN
Solar/Wind Harmer
5.38
965041AG1-368 GEN
Solar/Wind Harmer
10.749
247607V1-011 GEN
Solar/Wind Harmer
4.249
24729505KEY G4
Adder
6.948
963791AG1-232 GEN
Solar/Wind Harmer
14.455
971567AH1-282 GEN
Solar/Wind Harmer
16.053
966831AG1-554 GEN
Solar/Wind Harmer
1.28
971989AH1-539 GEN
Solar/Wind Harmer
13.846
270071AF1-092 GEN
Solar/Wind Harmer
16.048
971985AH1-537 GEN
Solar/Wind Harmer
19.051
958711AF2-162 GEN
Solar/Wind Harmer
1.079
270024AE2-089 GEN
Solar/Wind Harmer
5.004
965101AG1-375 GEN
Solar/Wind Harmer
10.653
270367AC2-061_GEN
Solar/Wind Harmer
3.388
971673AH1-337 GEN
Solar/Wind Harmer
4.893
971029AG2-637 GEN
Solar/Wind Harmer
15.954
252524AE2-267 GEN
Solar/Wind Harmer
1.677
25196408WSDLE3
Adder
9.382
25196308WSDLE2
Adder
9.3
25196208WSDLE1
Adder
9.277
25196708WSDLE6
Adder
9.254
25196508WSDLE4
Adder
9.021
270543AE2-219 C
Solar/Wind Harmer
5.445
961761AG1-017 GEN
Solar/Wind Harmer
0.455
945581AF1-223 GEN
Solar/Wind Harmer
4.819
944031AF1-071 GEN
Solar/Wind Harmer
1.067
270297AD1-101 GEN
Solar/Wind Harmer
2.953
25196108MFTGT2
Adder
1.605
25196108MFTGT2
Adder
1.491
274775LINCOLN ;6U
Adder
8.715
274776LINCOLN ;7U
Adder
8.715
274777LINCOLN ;8U
Adder
8.715
274814UNIV PK N;0U
Adder
5.208
274807UNIV PK N;3U
Adder
5.196
274805UNIV PK N;1U
Adder
5.174
274811UNIV PK N;7U
Adder
5.162
972037AH1-567 GEN1
Adder
0.188
274827FISK ;RP
Adder
7.977
972227AH1-698 GEN1
Adder
2.681
274687WILL CNTY;4U
Adder
28.653
274687WILL CNTY;4U
Adder
28.653
274675JOLIET 29;7U
Adder
31.445
274675JOLIET 29;7U
Adder
30.322
274731ELWOOD EC;2P
Adder
16.844
274733ELWOOD EC;3P
Adder
16.844
274735ELWOOD EC;4P
Adder
16.844
274728ELWOOD EC;5P
Adder
16.844
972203AH1-686 GEN
Adder
2.356
274746AC1-111 G10
Adder
5.705
274744AC1-111 GEN8
Adder
5.705
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.832
238152AF2-075_GEN
Solar/Wind Helper
0.709
238208AF1-136 C
Solar/Wind Helper
0.221
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.655
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.891
316415AF1-147_GEN2
Solar/Wind Helper
0.891
23750501ELLIOTTS
Solar/Wind Helper
0.644
959381AF2-229 GEN
Solar/Wind Helper
0.359
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.182
205943AE1-185 GEN
Solar/Wind Helper
0.511
205932AD2-116_GEN
Solar/Wind Helper
0.511
205956AE1-196_GEN
Solar/Wind Helper
0.511
233935AB2-179 C
Solar/Wind Helper
1.273
232436AB1-176 C
Solar/Wind Helper
0.045
233923SMA
Solar/Wind Helper
0.962
233990AG1-397 GEN
Solar/Wind Helper
0.031
232432Z2-076 GEN
Solar/Wind Helper
0.067
234033AF1-007_GEN
Solar/Wind Helper
7.046
964001AG1-254 GEN
Solar/Wind Helper
0.959
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.508
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.291
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.099
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.082
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
20675128HRM_W1-127
Solar/Wind Helper
0.03
209116AE2-175 GEN
Solar/Wind Helper
1.786
24318805MLG1
50/50
10.158
23559001PLEAS1
50/50
6.365
270051AF1-062 GEN
50/50
11.843
270475AD2-096_GEN
50/50
7.165
970153AG2-106 GEN
Solar/Wind Harmer
17.953
961921AG1-034 GEN
Solar/Wind Harmer
15.612
24721905FLATG4
Adder
24.144
241955AC1-078 GEN
Solar/Wind Harmer
8.824
241974AD2-163_GEN2
Solar/Wind Harmer
2.334
942051AE2-217 GEN
Solar/Wind Harmer
21.08
960801AF2-371 GEN
Solar/Wind Harmer
2.95
964871AG1-351 GEN
Solar/Wind Harmer
2.037
970605AG2-385 GEN
Solar/Wind Harmer
6.25
942871AE2-306 GEN
Solar/Wind Harmer
1.049
270391AF1-285 GEN3
Solar/Wind Harmer
0.538
253338AC1-165 GEN
Solar/Wind Harmer
1.243
253333AC1-068 GEN
Solar/Wind Harmer
1.199
270485AE1-090_GEN
Solar/Wind Harmer
0.692
270273AD2-016 GEN
Solar/Wind Harmer
3.037
972173AH1-669 GEN
Solar/Wind Harmer
5.679
253415AE1-040 GEN
Solar/Wind Harmer
1.251
270291AC1-194 GEN
Solar/Wind Harmer
11.751
253303V4-073 C
Solar/Wind Harmer
0.127
253370AE2-315 SEC1
Adder
2.189
253371AE2-315 SEC2
Adder
2.071
957541AF2-048 GEN
Solar/Wind Harmer
1.724
970065AG2-057 GEN
Solar/Wind Harmer
1.09
253406AD2-031_GEN
Solar/Wind Harmer
1.391
270491AE1-102 GEN2
Solar/Wind Harmer
1.407
971191AH1-055 GEN
Solar/Wind Harmer
23.759
253316AC1-085 GEN3
Solar/Wind Harmer
9.037
253433AC1-085 GEN1
Solar/Wind Harmer
5.737
946181AF1-283 GEN
Solar/Wind Harmer
14.025
270191TR4_S_V150
Solar/Wind Harmer
3.232
270247TR4_N_V136
Solar/Wind Harmer
0.916
959331AF2-224 GEN
Solar/Wind Harmer
10.775
965021AG1-366 GEN
Solar/Wind Harmer
2.506
270377AD1-106 GEN
Solar/Wind Harmer
6.65
958091AF2-103 GEN
Solar/Wind Harmer
0.174
270588AE1-091_GEN
Solar/Wind Harmer
11.804
944531AF1-118 GEN
Solar/Wind Harmer
37.541
270043AE2-236 GEN
Solar/Wind Harmer
5.893
971617AH1-308 GEN
Solar/Wind Harmer
6.198
270258AD1-119 GEN
Solar/Wind Harmer
2.97
25196608WSDLE5
Adder
9.114
962031AG1-047 GEN
Solar/Wind Harmer
3.214
957741AF2-068 GEN
Solar/Wind Harmer
15.949
252510AF1-249 C
Solar/Wind Harmer
0.444
25194608D.CRK4
Adder
1.747
270222AC2-111 GEN
Solar/Wind Harmer
8.657
970031AG2-029 GEN
Solar/Wind Harmer
31.849
270044AE2-322 C
Solar/Wind Harmer
1.394
270404AC1-167 GEN
Solar/Wind Harmer
1.161
24642205MAYFLWER
Adder
0.667
25196008MFTGT1
Adder
1.411
247604X1-042
Adder
0.435
274752CRETE EC ;2U
Adder
8.515
274753CRETE EC ;3U
Adder
8.515
274772LINCOLN ;3U
Adder
8.715
274724RIVER EC ;11
Adder
18.285
274802UNIV PARK;5U
Adder
5.997
24728705AND G3
Adder
8.251
24728505AND G1
Adder
3.945
274826FISK ;BP
Adder
11.256
274800UNIV PARK;3U
Adder
5.993
972038AH1-567 GEN2
Adder
0.375
972228AH1-698 GEN2
Adder
3.807
274676JOLIET 29;8U
Adder
30.322
274729ELWOOD EC;1P
Adder
16.844
274730ELWOOD EC;6P
Adder
16.844
274734ELWOOD EC;8P
Adder
16.844
274736ELWOOD EC;9P
Adder
16.844
274682WAUKEGAN ;7U
Adder
9.773
964991AG1-363 GEN
Solar/Wind Helper
5.152
316097T157 G90
Solar/Wind Helper
1.508
23750701CROSSCHOOL
Solar/Wind Helper
1.51
238118U2-030_1
Solar/Wind Helper
0.344
238127S14_GEN_2
Solar/Wind Helper
0.832
238148AE2-230_GEN2
Solar/Wind Helper
0.498
237080AD1-060 GEN
Solar/Wind Helper
0.343
237038AE2-054 C
Solar/Wind Helper
0.273
235062AE1-101 C1
Solar/Wind Helper
1.665
23779801AA1-109
Solar/Wind Helper
0.194
237048AF1-022 C
Solar/Wind Helper
0.179
223401AF1-299 GEN
Solar/Wind Helper
0.369
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.078
233930AB2-032 GEN
Solar/Wind Helper
0.382
233915AB1-141 GEN
Solar/Wind Helper
0.504
232422X3-066 FULL
Solar/Wind Helper
0.115
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.262
232404W1-003 C
Solar/Wind Helper
0.509
232428Y3-058 C
Solar/Wind Helper
0.339
232434Z2-077 GEN
Solar/Wind Helper
0.127
233954AC2-188 GEN
Solar/Wind Helper
0.233
233950AC2-186 GEN
Solar/Wind Helper
0.117
233972AC1-094 C
Solar/Wind Helper
0.303
230511AF1-262
Solar/Wind Helper
0.015
316045AC1-158 PL2
Solar/Wind Helper
4.149
230434AG1-499 GEN
Solar/Wind Helper
0.231
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.061
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.132
20720728JCB_W1-129
Solar/Wind Helper
0.057
207445AB1-138_GEN
Solar/Wind Helper
0.105
316254AC1-120 GEN1
Solar/Wind Helper
1.062
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.311
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.497
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.023
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.577
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.03
202652Y1-033 WT C
Solar/Wind Helper
0.5
961301AF2-421 GEN
Solar/Wind Helper
0.441
963151AG1-164 GEN
Solar/Wind Helper
0.441
970513AG2-328 GEN
Solar/Wind Harmer
4.981
970517AG2-330 GEN
Solar/Wind Harmer
4.518
270119AB2-067 GEN1
50/50
7.1
270120AB2-067 GEN2
50/50
7.1
24318905MLG2
50/50
7.059
270471AD2-092_GEN
Solar/Wind Harmer
4.477
946101AF1-275 GEN
Solar/Wind Harmer
1.818
942861AE2-305 GEN
Solar/Wind Harmer
9.105
970077AG2-063 GEN
Solar/Wind Harmer
6.25
270224U2-072_GEN2
Solar/Wind Harmer
2.287
270227U2-072_GEN3
Solar/Wind Harmer
2.287
270228U2-072_GEN4
Solar/Wind Harmer
2.287
270231U2-072_GEN5
Solar/Wind Harmer
2.287
938701AE1-092 GEN
Solar/Wind Harmer
23.86
964601AG1-323 GEN
Solar/Wind Harmer
3.665
964601AG1-323 GEN
Solar/Wind Harmer
1.705
270518AE2-148 GEN
Solar/Wind Harmer
13.911
253378AE2-206_GEN
Solar/Wind Harmer
4.016
276820AF1-078_GEN
Solar/Wind Harmer
1.784
972159AH1-661 GEN
Adder
1.111
972269AH1-719 GEN
Adder
2.557
25326509SID D
Adder
1.455
971199AH1-059 GEN
Solar/Wind Harmer
4.424
241960AC2-195 GEN
Solar/Wind Harmer
3.074
970879AG2-548 GEN
Solar/Wind Harmer
6.788
971073AG2-665 GEN
Solar/Wind Harmer
6.788
971073AG2-665 GEN
Solar/Wind Harmer
4.736
25326109MON D
Adder
1.447
25322209TAIT E
Adder
10.679
25322209TAIT E
Adder
10.439
253370AE2-315 SEC1
Adder
2.189
971201AH1-060 GEN
Solar/Wind Harmer
2.181
253394AE2-221_GEN
Solar/Wind Harmer
4.93
253398AE2-221_GEN2
Solar/Wind Harmer
4.93
246938BC-WTG3
Solar/Wind Harmer
4.31
246937BC-WTG2
Solar/Wind Harmer
4.237
253317AC1-085 GEN4
Solar/Wind Harmer
9.037
970611AG2-400 GEN
Solar/Wind Harmer
10.775
971231AH1-075 GEN
Solar/Wind Harmer
0.862
270007AE1-245 C
Solar/Wind Harmer
6.374
942801AE2-298 GEN
Solar/Wind Harmer
1.626
962581AG1-107 GEN
Solar/Wind Harmer
5.38
961491AF2-440 GEN
Solar/Wind Harmer
2.236
25183208HLCRTG
Solar/Wind Harmer
6.467
944541AF1-119 GEN
Solar/Wind Harmer
4.468
960971AF2-388 GEN
Solar/Wind Harmer
11.659
942221AE2-234 GEN
Solar/Wind Harmer
0.781
252519AF1-045_GEN
Solar/Wind Harmer
6.466
252516AE2-318_GEN
Solar/Wind Harmer
4.932
247621Y3-024
Adder
0.256
970883AG2-550 GEN
Solar/Wind Harmer
10.634
970885AG2-551 GEN
Solar/Wind Harmer
2.473
270201AC2-176 GEN
Solar/Wind Harmer
5.466
25194408D.CRK1
Adder
8.037
25194508D.CRK3
Adder
1.502
964611AG1-324 GEN
Solar/Wind Harmer
1.252
964611AG1-324 GEN
Solar/Wind Harmer
0.556
252509AD1-136 GEN
Solar/Wind Harmer
0.272
247620Y3-023
Adder
0.486
24728805RICHG1
Adder
3.981
24728905RICHG2
Adder
3.981
274770LINCOLN ;1U
Adder
8.715
274771LINCOLN ;2U
Adder
8.715
274808UNIV PK N;4U
Adder
5.14
274803UNIV PARK;6U
Adder
5.997
972259AH1-714 GEN
Adder
19.596
274674JOLIET 9 ;6U
Adder
15.776
274696ROCKY RD ;4P
Adder
11.59
274695ROCKY RD ;2P
Adder
11.323
274693ROCKY RD ;1P
Adder
11.211
274697ROCKY RD ;3P
Adder
3.076
23585401KL_K28_T16
Solar/Wind Helper
1.493
238120AE2-309 GEN
Solar/Wind Helper
0.528
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.703
238170AE2-226 GEN2
Solar/Wind Helper
0.703
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237002AB1-128_GEN
Solar/Wind Helper
0.445
237034AC2-136 C
Solar/Wind Helper
0.228
235063AE1-101 C2
Solar/Wind Helper
1.665
237001AB1-127_GEN
Solar/Wind Helper
0.443
23777801MSM_W1-116
Solar/Wind Helper
0.115
237025AB1-124 C
Solar/Wind Helper
0.165
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.72
20390526W1-045 C
Solar/Wind Helper
0.351
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.35
233933AB2-153 GEN
Solar/Wind Helper
0.233
232424Y1-079 C
Solar/Wind Helper
0.117
233944AB2-135 GEN
Solar/Wind Helper
0.591
233946AB2-136 GEN
Solar/Wind Helper
0.57
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.233
232408W1-005 C
Solar/Wind Helper
0.509
232410W1-006 C
Solar/Wind Helper
0.509
233939AC1-091 C
Solar/Wind Helper
0.351
233970AC1-092 C
Solar/Wind Helper
0.351
315651AD1-115 GEN
Solar/Wind Helper
0.787
316447AC1-158 HLD
Solar/Wind Helper
2.853
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.083
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.327
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.169
20674928WA_W3-044
Solar/Wind Helper
0.099
964851AG1-348 GEN
Solar/Wind Helper
0.081
20676228FRD_X1-012
Solar/Wind Helper
0.092
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.045
211065PSPA IPP
Solar/Wind Helper
0.152
211065PSPA IPP
Solar/Wind Helper
0.152
203955AF1-039 C O1
Solar/Wind Helper
0.33
970321AG2-212 GEN
Solar/Wind Harmer
4.981
NYPJM->LTFIMP_NY
CLTF
4.819
LGEELTFEXP_LGEE->PJM
CLTF
6.781
WECLTFEXP_WEC->PJM
CLTF
3.842
AG2-052LTFEXP_AG2-052->PJM
LTF
0.241
AH1-155LTFEXP_AH1-155->PJM
LTF
0.361
CPLELTFEXP_CPLE->PJM
CLTF
0.647
CBM West 2LTFEXP_CBM-W2->PJM
CBM
113.418
LAGNLTFEXP_LAGN->PJM
CLTF
14.924
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.891
TVALTFEXP_TVA->PJM
CLTF
7.337
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.671
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.268
MECLTFEXP_MEC->PJM
CLTF
15.978
SIGELTFEXP_SIGE->PJM
CLTF
0.507

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-025_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-025_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.94 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4919.93
MW Contribution:17.88
Bus #Bus NameTypeMW Contribution
962771AG1-126 GEN
Solar/Wind Harmer
41.012
972239AH1-704 GEN
Adder
2.683
270459AD2-067 GEN
Solar/Wind Harmer
10.243
961821AG1-024 GEN
Solar/Wind Harmer
10.399
270054AF2-122 C O1
Solar/Wind Harmer
3.993
270520AE2-214 GEN
Solar/Wind Harmer
7.274
270284AF1-227 GEN1
Solar/Wind Harmer
6.791
270286AF1-227 GEN2
Solar/Wind Harmer
2.512
270287AF1-227 GEN3
Solar/Wind Harmer
2.512
253383AE2-342_GEN
Solar/Wind Harmer
1.045
241973AD2-163_GEN1
Solar/Wind Harmer
2.33
945631AF1-228 GEN
Solar/Wind Harmer
5.461
943861AF1-054 GEN
Solar/Wind Harmer
4.486
943851AF1-053 GEN
Solar/Wind Harmer
2.168
270156DARBY CT1
Adder
10.416
270157DARBY CT2
Adder
10.391
270158DARBY CT3
Adder
10.225
970689AG2-444 GEN
Solar/Wind Harmer
18.82
270578AF1-285 GEN2
Solar/Wind Harmer
0.537
270432AC2-029 GEN
Solar/Wind Harmer
8.046
270302AB2-170 GEN
Solar/Wind Harmer
9.546
270317AD1-130_GEN
Solar/Wind Harmer
3.66
940611AE2-048 GEN
Solar/Wind Harmer
25.033
941391AE2-136 GEN
Solar/Wind Harmer
12.972
270269AC2-059
Solar/Wind Harmer
10.602
241972AD1-140 GEN
Solar/Wind Harmer
5.021
958581AF2-149 GEN
Solar/Wind Harmer
4.736
970179AG2-119 GEN
Solar/Wind Harmer
8.837
270340AC2-060 GEN
Solar/Wind Harmer
3.346
970879AG2-548 GEN
Solar/Wind Harmer
4.728
253372AE2-315 SEC3
Adder
2.066
253372AE2-315 SEC3
Adder
2.066
25306009OHH W.
Adder
3.134
253349AC2-067 GEN
Solar/Wind Harmer
5.408
253400AC2-068 GEN
Solar/Wind Harmer
2.175
957201AF2-014 GEN
Solar/Wind Harmer
4.898
270435AC2-044 GEN
Solar/Wind Harmer
2.16
965051AG1-369 GEN
Solar/Wind Harmer
5.366
965041AG1-368 GEN
Solar/Wind Harmer
10.722
247607V1-011 GEN
Solar/Wind Harmer
4.239
971567AH1-282 GEN
Solar/Wind Harmer
16.059
966831AG1-554 GEN
Solar/Wind Harmer
1.279
971989AH1-539 GEN
Solar/Wind Harmer
13.833
24729505KEY G4
Adder
6.928
963791AG1-232 GEN
Solar/Wind Harmer
14.415
270071AF1-092 GEN
Solar/Wind Harmer
16.001
971985AH1-537 GEN
Solar/Wind Harmer
18.998
958711AF2-162 GEN
Solar/Wind Harmer
1.076
270024AE2-089 GEN
Solar/Wind Harmer
4.99
270367AC2-061_GEN
Solar/Wind Harmer
3.379
965101AG1-375 GEN
Solar/Wind Harmer
10.622
971673AH1-337 GEN
Solar/Wind Harmer
4.88
252524AE2-267 GEN
Solar/Wind Harmer
1.673
971029AG2-637 GEN
Solar/Wind Harmer
15.909
25196408WSDLE3
Adder
9.356
25196308WSDLE2
Adder
9.275
25196208WSDLE1
Adder
9.252
25196708WSDLE6
Adder
9.228
25196508WSDLE4
Adder
8.996
270543AE2-219 C
Solar/Wind Harmer
5.43
961761AG1-017 GEN
Solar/Wind Harmer
0.454
945581AF1-223 GEN
Solar/Wind Harmer
4.805
270297AD1-101 GEN
Solar/Wind Harmer
2.947
944031AF1-071 GEN
Solar/Wind Harmer
1.064
25196108MFTGT2
Adder
1.601
25196108MFTGT2
Adder
1.486
274775LINCOLN ;6U
Adder
8.688
274776LINCOLN ;7U
Adder
8.688
274777LINCOLN ;8U
Adder
8.688
274814UNIV PK N;0U
Adder
5.192
274807UNIV PK N;3U
Adder
5.18
274805UNIV PK N;1U
Adder
5.158
274811UNIV PK N;7U
Adder
5.147
972037AH1-567 GEN1
Adder
0.188
274827FISK ;RP
Adder
7.953
972227AH1-698 GEN1
Adder
2.673
274687WILL CNTY;4U
Adder
28.564
274687WILL CNTY;4U
Adder
28.564
274675JOLIET 29;7U
Adder
31.348
274675JOLIET 29;7U
Adder
30.228
274731ELWOOD EC;2P
Adder
16.792
274733ELWOOD EC;3P
Adder
16.792
274735ELWOOD EC;4P
Adder
16.792
274728ELWOOD EC;5P
Adder
16.792
972203AH1-686 GEN
Adder
2.344
274746AC1-111 G10
Adder
5.687
274744AC1-111 GEN8
Adder
5.687
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.829
238152AF2-075_GEN
Solar/Wind Helper
0.708
238208AF1-136 C
Solar/Wind Helper
0.22
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.651
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.889
316415AF1-147_GEN2
Solar/Wind Helper
0.889
23750501ELLIOTTS
Solar/Wind Helper
0.64
959381AF2-229 GEN
Solar/Wind Helper
0.358
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.182
205943AE1-185 GEN
Solar/Wind Helper
0.51
205932AD2-116_GEN
Solar/Wind Helper
0.509
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.27
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.959
233990AG1-397 GEN
Solar/Wind Helper
0.03
234033AF1-007_GEN
Solar/Wind Helper
7.028
232432Z2-076 GEN
Solar/Wind Helper
0.067
964001AG1-254 GEN
Solar/Wind Helper
0.957
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.501
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.097
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
20675128HRM_W1-127
Solar/Wind Helper
0.03
209116AE2-175 GEN
Solar/Wind Helper
1.781
24318805MLG1
50/50
10.115
23559001PLEAS1
50/50
6.183
270051AF1-062 GEN
50/50
11.828
270475AD2-096_GEN
50/50
7.148
970153AG2-106 GEN
Solar/Wind Harmer
17.883
961921AG1-034 GEN
Solar/Wind Harmer
15.599
24721905FLATG4
Adder
23.989
241955AC1-078 GEN
Solar/Wind Harmer
8.811
241974AD2-163_GEN2
Solar/Wind Harmer
2.33
942051AE2-217 GEN
Solar/Wind Harmer
21.044
960801AF2-371 GEN
Solar/Wind Harmer
2.947
964871AG1-351 GEN
Solar/Wind Harmer
2.035
970605AG2-385 GEN
Solar/Wind Harmer
6.239
942871AE2-306 GEN
Solar/Wind Harmer
1.047
270391AF1-285 GEN3
Solar/Wind Harmer
0.537
253338AC1-165 GEN
Solar/Wind Harmer
1.241
253333AC1-068 GEN
Solar/Wind Harmer
1.197
270485AE1-090_GEN
Solar/Wind Harmer
0.69
270273AD2-016 GEN
Solar/Wind Harmer
3.032
972173AH1-669 GEN
Solar/Wind Harmer
5.669
253415AE1-040 GEN
Solar/Wind Harmer
1.248
270291AC1-194 GEN
Solar/Wind Harmer
11.736
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.066
970065AG2-057 GEN
Solar/Wind Harmer
1.09
957541AF2-048 GEN
Solar/Wind Harmer
1.72
270512AE1-227 GEN2
Solar/Wind Harmer
2.283
253406AD2-031_GEN
Solar/Wind Harmer
1.388
270491AE1-102 GEN2
Solar/Wind Harmer
1.404
971191AH1-055 GEN
Solar/Wind Harmer
23.693
270377AD1-106 GEN
Solar/Wind Harmer
6.649
253316AC1-085 GEN3
Solar/Wind Harmer
9.014
253433AC1-085 GEN1
Solar/Wind Harmer
5.722
946181AF1-283 GEN
Solar/Wind Harmer
13.99
270191TR4_S_V150
Solar/Wind Harmer
3.224
270247TR4_N_V136
Solar/Wind Harmer
0.914
959331AF2-224 GEN
Solar/Wind Harmer
10.746
965021AG1-366 GEN
Solar/Wind Harmer
2.499
958091AF2-103 GEN
Solar/Wind Harmer
0.173
270588AE1-091_GEN
Solar/Wind Harmer
11.789
944531AF1-118 GEN
Solar/Wind Harmer
37.432
270043AE2-236 GEN
Solar/Wind Harmer
5.876
270258AD1-119 GEN
Solar/Wind Harmer
2.963
971617AH1-308 GEN
Solar/Wind Harmer
6.181
25196608WSDLE5
Adder
9.089
962031AG1-047 GEN
Solar/Wind Harmer
3.205
252510AF1-249 C
Solar/Wind Harmer
0.443
957741AF2-068 GEN
Solar/Wind Harmer
15.904
25194608D.CRK4
Adder
1.742
270222AC2-111 GEN
Solar/Wind Harmer
8.632
970031AG2-029 GEN
Solar/Wind Harmer
31.759
270044AE2-322 C
Solar/Wind Harmer
1.391
270404AC1-167 GEN
Solar/Wind Harmer
1.158
24642205MAYFLWER
Adder
0.665
25196008MFTGT1
Adder
1.406
247604X1-042
Adder
0.434
274752CRETE EC ;2U
Adder
8.489
274753CRETE EC ;3U
Adder
8.489
274772LINCOLN ;3U
Adder
8.688
274724RIVER EC ;11
Adder
18.229
24728705AND G3
Adder
8.226
274802UNIV PARK;5U
Adder
5.978
24728505AND G1
Adder
3.933
274826FISK ;BP
Adder
11.221
274800UNIV PARK;3U
Adder
5.975
972038AH1-567 GEN2
Adder
0.374
972228AH1-698 GEN2
Adder
3.796
274676JOLIET 29;8U
Adder
30.228
274729ELWOOD EC;1P
Adder
16.792
274730ELWOOD EC;6P
Adder
16.792
274734ELWOOD EC;8P
Adder
16.792
274736ELWOOD EC;9P
Adder
16.792
274682WAUKEGAN ;7U
Adder
9.742
964991AG1-363 GEN
Solar/Wind Helper
5.141
316097T157 G90
Solar/Wind Helper
1.505
23750701CROSSCHOOL
Solar/Wind Helper
1.505
238118U2-030_1
Solar/Wind Helper
0.342
238127S14_GEN_2
Solar/Wind Helper
0.829
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237080AD1-060 GEN
Solar/Wind Helper
0.342
237038AE2-054 C
Solar/Wind Helper
0.272
235062AE1-101 C1
Solar/Wind Helper
1.661
23779801AA1-109
Solar/Wind Helper
0.193
237048AF1-022 C
Solar/Wind Helper
0.178
223401AF1-299 GEN
Solar/Wind Helper
0.368
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.077
233930AB2-032 GEN
Solar/Wind Helper
0.381
233915AB1-141 GEN
Solar/Wind Helper
0.503
232422X3-066 FULL
Solar/Wind Helper
0.114
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.262
232404W1-003 C
Solar/Wind Helper
0.508
232428Y3-058 C
Solar/Wind Helper
0.338
233954AC2-188 GEN
Solar/Wind Helper
0.233
233950AC2-186 GEN
Solar/Wind Helper
0.116
232434Z2-077 GEN
Solar/Wind Helper
0.127
233972AC1-094 C
Solar/Wind Helper
0.303
316045AC1-158 PL2
Solar/Wind Helper
4.142
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.061
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
20720728JCB_W1-129
Solar/Wind Helper
0.057
316254AC1-120 GEN1
Solar/Wind Helper
1.06
207445AB1-138_GEN
Solar/Wind Helper
0.104
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.496
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.573
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.03
970513AG2-328 GEN
Solar/Wind Harmer
3.728
970517AG2-330 GEN
Solar/Wind Harmer
3.381
270119AB2-067 GEN1
50/50
7.072
270120AB2-067 GEN2
50/50
7.072
24318905MLG2
50/50
7.067
270471AD2-092_GEN
Solar/Wind Harmer
4.467
946101AF1-275 GEN
Solar/Wind Harmer
1.815
942861AE2-305 GEN
Solar/Wind Harmer
9.088
970077AG2-063 GEN
Solar/Wind Harmer
6.239
270224U2-072_GEN2
Solar/Wind Harmer
2.282
270227U2-072_GEN3
Solar/Wind Harmer
2.282
270228U2-072_GEN4
Solar/Wind Harmer
2.282
270231U2-072_GEN5
Solar/Wind Harmer
2.282
938701AE1-092 GEN
Solar/Wind Harmer
23.824
964601AG1-323 GEN
Solar/Wind Harmer
3.66
964601AG1-323 GEN
Solar/Wind Harmer
1.702
270518AE2-148 GEN
Solar/Wind Harmer
13.886
972269AH1-719 GEN
Adder
2.575
972159AH1-661 GEN
Adder
1.116
253378AE2-206_GEN
Solar/Wind Harmer
4.007
276820AF1-078_GEN
Solar/Wind Harmer
1.78
971199AH1-059 GEN
Solar/Wind Harmer
4.428
241960AC2-195 GEN
Solar/Wind Harmer
3.072
25326509SID D
Adder
1.452
970879AG2-548 GEN
Solar/Wind Harmer
6.777
971073AG2-665 GEN
Solar/Wind Harmer
6.777
971073AG2-665 GEN
Solar/Wind Harmer
4.728
25326109MON D
Adder
1.444
25322209TAIT E
Adder
10.654
25322209TAIT E
Adder
10.414
253370AE2-315 SEC1
Adder
2.184
971201AH1-060 GEN
Solar/Wind Harmer
2.179
253394AE2-221_GEN
Solar/Wind Harmer
4.918
253398AE2-221_GEN2
Solar/Wind Harmer
4.918
246938BC-WTG3
Solar/Wind Harmer
4.299
246937BC-WTG2
Solar/Wind Harmer
4.226
971231AH1-075 GEN
Solar/Wind Harmer
0.861
253317AC1-085 GEN4
Solar/Wind Harmer
9.014
970611AG2-400 GEN
Solar/Wind Harmer
10.746
270007AE1-245 C
Solar/Wind Harmer
6.359
942801AE2-298 GEN
Solar/Wind Harmer
1.622
962581AG1-107 GEN
Solar/Wind Harmer
5.366
961491AF2-440 GEN
Solar/Wind Harmer
2.23
25183208HLCRTG
Solar/Wind Harmer
6.45
944541AF1-119 GEN
Solar/Wind Harmer
4.455
960971AF2-388 GEN
Solar/Wind Harmer
11.625
942221AE2-234 GEN
Solar/Wind Harmer
0.779
252519AF1-045_GEN
Solar/Wind Harmer
6.448
252516AE2-318_GEN
Solar/Wind Harmer
4.919
247621Y3-024
Adder
0.256
970883AG2-550 GEN
Solar/Wind Harmer
10.605
970885AG2-551 GEN
Solar/Wind Harmer
2.466
270201AC2-176 GEN
Solar/Wind Harmer
5.45
25194408D.CRK1
Adder
8.014
25194508D.CRK3
Adder
1.498
964611AG1-324 GEN
Solar/Wind Harmer
1.249
964611AG1-324 GEN
Solar/Wind Harmer
0.554
252509AD1-136 GEN
Solar/Wind Harmer
0.271
247620Y3-023
Adder
0.484
24728805RICHG1
Adder
3.969
24728905RICHG2
Adder
3.969
274770LINCOLN ;1U
Adder
8.688
274771LINCOLN ;2U
Adder
8.688
274808UNIV PK N;4U
Adder
5.124
274803UNIV PARK;6U
Adder
5.978
972259AH1-714 GEN
Adder
19.535
274674JOLIET 9 ;6U
Adder
15.727
274696ROCKY RD ;4P
Adder
11.554
274695ROCKY RD ;2P
Adder
11.287
274693ROCKY RD ;1P
Adder
11.176
274697ROCKY RD ;3P
Adder
3.066
23585401KL_K28_T16
Solar/Wind Helper
1.485
238120AE2-309 GEN
Solar/Wind Helper
0.526
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.702
238170AE2-226 GEN2
Solar/Wind Helper
0.702
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237002AB1-128_GEN
Solar/Wind Helper
0.444
237034AC2-136 C
Solar/Wind Helper
0.227
235063AE1-101 C2
Solar/Wind Helper
1.661
237001AB1-127_GEN
Solar/Wind Helper
0.442
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.715
20390526W1-045 C
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.344
233933AB2-153 GEN
Solar/Wind Helper
0.233
232424Y1-079 C
Solar/Wind Helper
0.116
233944AB2-135 GEN
Solar/Wind Helper
0.589
233946AB2-136 GEN
Solar/Wind Helper
0.569
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.233
232408W1-005 C
Solar/Wind Helper
0.508
232410W1-006 C
Solar/Wind Helper
0.508
233939AC1-091 C
Solar/Wind Helper
0.35
233970AC1-092 C
Solar/Wind Helper
0.35
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.848
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.169
20674928WA_W3-044
Solar/Wind Helper
0.098
20676228FRD_X1-012
Solar/Wind Helper
0.092
964851AG1-348 GEN
Solar/Wind Helper
0.081
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.045
211065PSPA IPP
Solar/Wind Helper
0.152
211065PSPA IPP
Solar/Wind Helper
0.152
970321AG2-212 GEN
Solar/Wind Harmer
3.728
270166AC1-044 GEN3
50/50
7.072
23559101PLEAS2
50/50
6.183
962761AG1-125 GEN
Solar/Wind Harmer
41.012
970149AG2-104 GEN
Solar/Wind Harmer
50.65
970155AG2-107 GEN
Solar/Wind Harmer
17.883
270349AD2-093_GEN
Solar/Wind Harmer
4.467
24721705FLATG2
Adder
23.989
270159DARBY CT4
Adder
10.25
970593AG2-378 GEN
Solar/Wind Harmer
2.311
270223U2-072_GEN1
Solar/Wind Harmer
2.282
270578AF1-285 GEN2
Solar/Wind Harmer
1.396
270391AF1-285 GEN3
Solar/Wind Harmer
1.396
253343AC1-166 GEN
Solar/Wind Harmer
1.241
253325AC1-069 GEN
Solar/Wind Harmer
1.197
270462AD2-086
Solar/Wind Harmer
7.941
971995AH1-542 GEN
Solar/Wind Harmer
12.502
270263AC1-001 GEN
Solar/Wind Harmer
1.177
25326309TAIT D
Adder
1.197
960071AF2-298 GEN
Solar/Wind Harmer
5.441
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.066
241813AF1-122_GEN
Solar/Wind Harmer
6.974
927014AC1-188 GEN
Solar/Wind Harmer
1.725
270510AE1-227 GEN1
Solar/Wind Harmer
2.689
246936BC-WTG1
Solar/Wind Harmer
4.226
270489AE1-102 GEN1
Solar/Wind Harmer
1.404
965421AG1-410 GEN
Solar/Wind Harmer
32.386
960001AF2-291 GEN
Solar/Wind Harmer
3.255
253432AC1-085 GEN2
Solar/Wind Harmer
0.288
946171AF1-282 GEN
Solar/Wind Harmer
10.761
247521TR3_G114
Solar/Wind Harmer
3.613
270246TR4_N_V150
Solar/Wind Harmer
0.914
965011AG1-365 GEN
Solar/Wind Harmer
10.746
24695305TIMB G C
Solar/Wind Harmer
5.901
965651AG1-433 GEN
Solar/Wind Harmer
5.813
958861AF2-177 GEN
Solar/Wind Harmer
11.61
247536S-71 GEN
Solar/Wind Harmer
4.293
25194608D.CRK4
Adder
1.742
945371AF1-202 GEN
Solar/Wind Harmer
7.392
252507AC2-088 GEN
Solar/Wind Harmer
1.899
270063AE2-323 C
Solar/Wind Harmer
2.33
25196808ZIMRHP
Adder
79.831
24639705ELKHART HY
Adder
0.161
25196008MFTGT1
Adder
1.452
274751CRETE EC ;1U
Adder
8.489
274754CRETE EC ;4U
Adder
8.489
274773LINCOLN ;4U
Adder
8.688
274774LINCOLN ;5U
Adder
8.688
274723RIVER EC ;12
Adder
18.445
274812UNIV PK N;8U
Adder
5.147
24728605AND G2
Adder
3.933
274801UNIV PARK;4U
Adder
5.975
274676JOLIET 29;8U
Adder
31.348
274732ELWOOD EC;7P
Adder
16.792
274674JOLIET 9 ;6U
Adder
15.727
274745AC1-111 GEN9
Adder
5.687
970091AG2-072 GEN
Adder
77.755
316095T157 G97
Solar/Wind Helper
1.505
23583801GRNGAP
Solar/Wind Helper
5.606
238185AF2-356 C
Solar/Wind Helper
2.651
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.034
235531U2-073 GEN
Solar/Wind Helper
3.288
238117U2-030
Solar/Wind Helper
0.342
238147AE2-230_GEN1
Solar/Wind Helper
0.495
238149AF1-291A_GEN
Solar/Wind Helper
0.141
23751201ROTHROCK
Solar/Wind Helper
0.826
23562501BACKB
Solar/Wind Helper
1.01
237061AD1-155 GEN
Solar/Wind Helper
0.053
238221AF1-254 C O1
Solar/Wind Helper
0.275
235067AD1-061 GEN
Solar/Wind Helper
0.496
23751101LEADS_P59
Solar/Wind Helper
1.41
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.032
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.346
223402AF1-300 C
Solar/Wind Helper
0.368
205917AD1-020 ES
Solar/Wind Helper
0.369
233982AB2-133 GEN
Solar/Wind Helper
0.358
233918AB1-142 GEN
Solar/Wind Helper
0.503
233994AC2-023 GEN
Solar/Wind Helper
0.962
233996TM1833_GEN
Solar/Wind Helper
0.262
233997TMININ_4.2
Solar/Wind Helper
0.262
232406W1-004 FULL
Solar/Wind Helper
0.508
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.233
233971AC1-093 C
Solar/Wind Helper
0.358
316044AC1-158 PL1
Solar/Wind Helper
1.294
316450AC1-158 RIC
Solar/Wind Helper
0.345
230430AE1-229_GEN
Solar/Wind Helper
3.376
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.111
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.353
219276PARKLANDSO C
Solar/Wind Helper
0.089
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
970245AG2-165 GEN
Solar/Wind Harmer
3.728
NYPJM->LTFIMP_NY
CLTF
4.803
LGEELTFEXP_LGEE->PJM
CLTF
6.759
WECLTFEXP_WEC->PJM
CLTF
3.83
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
AH1-155LTFEXP_AH1-155->PJM
LTF
0.36
CPLELTFEXP_CPLE->PJM
CLTF
0.632
CBM West 2LTFEXP_CBM-W2->PJM
CBM
113.005
LAGNLTFEXP_LAGN->PJM
CLTF
14.864
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.83
TVALTFEXP_TVA->PJM
CLTF
7.306
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.265
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.153
MECLTFEXP_MEC->PJM
CLTF
15.925
SIGELTFEXP_SIGE->PJM
CLTF
0.506

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-015_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-015_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.63 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4908.47
MW Contribution:17.87
Bus #Bus NameTypeMW Contribution
962771AG1-126 GEN
Solar/Wind Harmer
40.976
972239AH1-704 GEN
Adder
2.69
270054AF2-122 C O1
Solar/Wind Harmer
3.996
270459AD2-067 GEN
Solar/Wind Harmer
10.248
961821AG1-024 GEN
Solar/Wind Harmer
10.404
270520AE2-214 GEN
Solar/Wind Harmer
7.276
270284AF1-227 GEN1
Solar/Wind Harmer
6.79
270286AF1-227 GEN2
Solar/Wind Harmer
2.512
270287AF1-227 GEN3
Solar/Wind Harmer
2.512
253383AE2-342_GEN
Solar/Wind Harmer
1.045
241973AD2-163_GEN1
Solar/Wind Harmer
2.331
945631AF1-228 GEN
Solar/Wind Harmer
5.463
943861AF1-054 GEN
Solar/Wind Harmer
4.486
943851AF1-053 GEN
Solar/Wind Harmer
2.168
270156DARBY CT1
Adder
10.419
270157DARBY CT2
Adder
10.393
270158DARBY CT3
Adder
10.228
970689AG2-444 GEN
Solar/Wind Harmer
18.827
270578AF1-285 GEN2
Solar/Wind Harmer
0.537
270432AC2-029 GEN
Solar/Wind Harmer
8.049
940611AE2-048 GEN
Solar/Wind Harmer
25.14
941391AE2-136 GEN
Solar/Wind Harmer
13.027
270302AB2-170 GEN
Solar/Wind Harmer
9.546
270317AD1-130_GEN
Solar/Wind Harmer
3.659
270269AC2-059
Solar/Wind Harmer
10.605
241972AD1-140 GEN
Solar/Wind Harmer
5.021
958581AF2-149 GEN
Solar/Wind Harmer
4.743
970179AG2-119 GEN
Solar/Wind Harmer
8.842
270340AC2-060 GEN
Solar/Wind Harmer
3.346
970879AG2-548 GEN
Solar/Wind Harmer
4.73
253372AE2-315 SEC3
Adder
2.065
253372AE2-315 SEC3
Adder
2.065
25306009OHH W.
Adder
3.133
253349AC2-067 GEN
Solar/Wind Harmer
5.407
253400AC2-068 GEN
Solar/Wind Harmer
2.174
957201AF2-014 GEN
Solar/Wind Harmer
4.898
270435AC2-044 GEN
Solar/Wind Harmer
2.16
965051AG1-369 GEN
Solar/Wind Harmer
5.365
965041AG1-368 GEN
Solar/Wind Harmer
10.719
247607V1-011 GEN
Solar/Wind Harmer
4.239
971567AH1-282 GEN
Solar/Wind Harmer
16.075
966831AG1-554 GEN
Solar/Wind Harmer
1.28
971989AH1-539 GEN
Solar/Wind Harmer
13.838
24729505KEY G4
Adder
6.925
963791AG1-232 GEN
Solar/Wind Harmer
14.411
270071AF1-092 GEN
Solar/Wind Harmer
15.995
971985AH1-537 GEN
Solar/Wind Harmer
18.996
958711AF2-162 GEN
Solar/Wind Harmer
1.076
270024AE2-089 GEN
Solar/Wind Harmer
4.988
270367AC2-061_GEN
Solar/Wind Harmer
3.378
965101AG1-375 GEN
Solar/Wind Harmer
10.618
971673AH1-337 GEN
Solar/Wind Harmer
4.878
252524AE2-267 GEN
Solar/Wind Harmer
1.672
25196408WSDLE3
Adder
9.354
25196308WSDLE2
Adder
9.273
25196208WSDLE1
Adder
9.25
25196708WSDLE6
Adder
9.227
25196508WSDLE4
Adder
8.994
971029AG2-637 GEN
Solar/Wind Harmer
15.905
270543AE2-219 C
Solar/Wind Harmer
5.429
961761AG1-017 GEN
Solar/Wind Harmer
0.454
945581AF1-223 GEN
Solar/Wind Harmer
4.803
270297AD1-101 GEN
Solar/Wind Harmer
2.947
944031AF1-071 GEN
Solar/Wind Harmer
1.064
25196108MFTGT2
Adder
1.6
25196108MFTGT2
Adder
1.486
274775LINCOLN ;6U
Adder
8.684
274776LINCOLN ;7U
Adder
8.684
274777LINCOLN ;8U
Adder
8.684
274814UNIV PK N;0U
Adder
5.189
274807UNIV PK N;3U
Adder
5.178
274805UNIV PK N;1U
Adder
5.156
274811UNIV PK N;7U
Adder
5.144
972037AH1-567 GEN1
Adder
0.188
274827FISK ;RP
Adder
7.949
972227AH1-698 GEN1
Adder
2.671
274687WILL CNTY;4U
Adder
28.551
274687WILL CNTY;4U
Adder
28.551
274675JOLIET 29;7U
Adder
31.334
274675JOLIET 29;7U
Adder
30.215
274731ELWOOD EC;2P
Adder
16.784
274733ELWOOD EC;3P
Adder
16.784
274735ELWOOD EC;4P
Adder
16.784
274728ELWOOD EC;5P
Adder
16.784
972203AH1-686 GEN
Adder
2.341
274746AC1-111 G10
Adder
5.685
274744AC1-111 GEN8
Adder
5.685
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.826
238152AF2-075_GEN
Solar/Wind Helper
0.708
238208AF1-136 C
Solar/Wind Helper
0.22
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.65
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.889
316415AF1-147_GEN2
Solar/Wind Helper
0.889
23750501ELLIOTTS
Solar/Wind Helper
0.637
959381AF2-229 GEN
Solar/Wind Helper
0.358
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.182
205943AE1-185 GEN
Solar/Wind Helper
0.51
205932AD2-116_GEN
Solar/Wind Helper
0.509
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.27
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.959
234033AF1-007_GEN
Solar/Wind Helper
7.028
233990AG1-397 GEN
Solar/Wind Helper
0.03
232432Z2-076 GEN
Solar/Wind Helper
0.067
964001AG1-254 GEN
Solar/Wind Helper
0.956
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.5
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.097
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
20674828DL_W4-046
Solar/Wind Helper
0.008
207484AF2-139 C O1
Solar/Wind Helper
0.084
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
20675128HRM_W1-127
Solar/Wind Helper
0.03
209116AE2-175 GEN
Solar/Wind Helper
1.781
24318805MLG1
50/50
10.098
23559001PLEAS1
50/50
6.112
270051AF1-062 GEN
50/50
11.831
23684201S70BUS2
50/50
0.171
270475AD2-096_GEN
50/50
7.147
970153AG2-106 GEN
Solar/Wind Harmer
17.867
961921AG1-034 GEN
Solar/Wind Harmer
15.607
241955AC1-078 GEN
Solar/Wind Harmer
8.813
24721905FLATG4
Adder
23.946
241974AD2-163_GEN2
Solar/Wind Harmer
2.331
942051AE2-217 GEN
Solar/Wind Harmer
21.048
960801AF2-371 GEN
Solar/Wind Harmer
2.948
964871AG1-351 GEN
Solar/Wind Harmer
2.036
970605AG2-385 GEN
Solar/Wind Harmer
6.24
942871AE2-306 GEN
Solar/Wind Harmer
1.047
270391AF1-285 GEN3
Solar/Wind Harmer
0.537
253338AC1-165 GEN
Solar/Wind Harmer
1.242
253333AC1-068 GEN
Solar/Wind Harmer
1.197
270485AE1-090_GEN
Solar/Wind Harmer
0.69
270273AD2-016 GEN
Solar/Wind Harmer
3.033
972173AH1-669 GEN
Solar/Wind Harmer
5.671
270291AC1-194 GEN
Solar/Wind Harmer
11.744
253415AE1-040 GEN
Solar/Wind Harmer
1.248
270512AE1-227 GEN2
Solar/Wind Harmer
2.315
970065AG2-057 GEN
Solar/Wind Harmer
1.09
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.065
957541AF2-048 GEN
Solar/Wind Harmer
1.721
253406AD2-031_GEN
Solar/Wind Harmer
1.388
270491AE1-102 GEN2
Solar/Wind Harmer
1.404
270377AD1-106 GEN
Solar/Wind Harmer
6.655
971191AH1-055 GEN
Solar/Wind Harmer
23.692
253316AC1-085 GEN3
Solar/Wind Harmer
9.013
253433AC1-085 GEN1
Solar/Wind Harmer
5.721
946181AF1-283 GEN
Solar/Wind Harmer
13.988
270191TR4_S_V150
Solar/Wind Harmer
3.223
270247TR4_N_V136
Solar/Wind Harmer
0.914
959331AF2-224 GEN
Solar/Wind Harmer
10.743
965021AG1-366 GEN
Solar/Wind Harmer
2.498
270588AE1-091_GEN
Solar/Wind Harmer
11.792
958091AF2-103 GEN
Solar/Wind Harmer
0.173
944531AF1-118 GEN
Solar/Wind Harmer
37.418
270043AE2-236 GEN
Solar/Wind Harmer
5.874
270258AD1-119 GEN
Solar/Wind Harmer
2.962
971617AH1-308 GEN
Solar/Wind Harmer
6.179
25196608WSDLE5
Adder
9.087
252510AF1-249 C
Solar/Wind Harmer
0.443
962031AG1-047 GEN
Solar/Wind Harmer
3.204
957741AF2-068 GEN
Solar/Wind Harmer
15.899
25194608D.CRK4
Adder
1.742
270222AC2-111 GEN
Solar/Wind Harmer
8.63
970031AG2-029 GEN
Solar/Wind Harmer
31.748
270044AE2-322 C
Solar/Wind Harmer
1.39
270404AC1-167 GEN
Solar/Wind Harmer
1.158
24642205MAYFLWER
Adder
0.665
25196008MFTGT1
Adder
1.406
247604X1-042
Adder
0.433
274752CRETE EC ;2U
Adder
8.485
274753CRETE EC ;3U
Adder
8.485
274772LINCOLN ;3U
Adder
8.684
274724RIVER EC ;11
Adder
18.221
24728705AND G3
Adder
8.223
274802UNIV PARK;5U
Adder
5.976
24728505AND G1
Adder
3.932
274826FISK ;BP
Adder
11.216
274800UNIV PARK;3U
Adder
5.972
972038AH1-567 GEN2
Adder
0.374
972228AH1-698 GEN2
Adder
3.794
274676JOLIET 29;8U
Adder
30.215
274729ELWOOD EC;1P
Adder
16.784
274730ELWOOD EC;6P
Adder
16.784
274734ELWOOD EC;8P
Adder
16.784
274736ELWOOD EC;9P
Adder
16.784
274682WAUKEGAN ;7U
Adder
9.459
964991AG1-363 GEN
Solar/Wind Helper
5.14
316097T157 G90
Solar/Wind Helper
1.505
23750701CROSSCHOOL
Solar/Wind Helper
1.501
238118U2-030_1
Solar/Wind Helper
0.341
238127S14_GEN_2
Solar/Wind Helper
0.826
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237080AD1-060 GEN
Solar/Wind Helper
0.342
237038AE2-054 C
Solar/Wind Helper
0.272
235062AE1-101 C1
Solar/Wind Helper
1.661
23779801AA1-109
Solar/Wind Helper
0.193
237048AF1-022 C
Solar/Wind Helper
0.177
223401AF1-299 GEN
Solar/Wind Helper
0.368
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.077
233930AB2-032 GEN
Solar/Wind Helper
0.381
233915AB1-141 GEN
Solar/Wind Helper
0.503
232422X3-066 FULL
Solar/Wind Helper
0.114
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.262
232404W1-003 C
Solar/Wind Helper
0.508
232428Y3-058 C
Solar/Wind Helper
0.338
232434Z2-077 GEN
Solar/Wind Helper
0.127
233954AC2-188 GEN
Solar/Wind Helper
0.233
233950AC2-186 GEN
Solar/Wind Helper
0.116
233972AC1-094 C
Solar/Wind Helper
0.303
316045AC1-158 PL2
Solar/Wind Helper
4.142
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.06
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
20720728JCB_W1-129
Solar/Wind Helper
0.057
316254AC1-120 GEN1
Solar/Wind Helper
1.061
207445AB1-138_GEN
Solar/Wind Helper
0.104
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.496
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.573
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.03
970513AG2-328 GEN
Solar/Wind Harmer
3.726
970517AG2-330 GEN
Solar/Wind Harmer
3.379
270119AB2-067 GEN1
50/50
7.063
270120AB2-067 GEN2
50/50
7.063
24318905MLG2
50/50
7.074
270471AD2-092_GEN
Solar/Wind Harmer
4.466
946101AF1-275 GEN
Solar/Wind Harmer
1.816
942861AE2-305 GEN
Solar/Wind Harmer
9.089
970077AG2-063 GEN
Solar/Wind Harmer
6.24
270224U2-072_GEN2
Solar/Wind Harmer
2.282
270227U2-072_GEN3
Solar/Wind Harmer
2.282
270228U2-072_GEN4
Solar/Wind Harmer
2.282
270231U2-072_GEN5
Solar/Wind Harmer
2.282
938701AE1-092 GEN
Solar/Wind Harmer
23.829
964601AG1-323 GEN
Solar/Wind Harmer
3.66
964601AG1-323 GEN
Solar/Wind Harmer
1.702
270518AE2-148 GEN
Solar/Wind Harmer
13.889
972269AH1-719 GEN
Adder
2.587
972159AH1-661 GEN
Adder
1.119
253378AE2-206_GEN
Solar/Wind Harmer
4.007
276820AF1-078_GEN
Solar/Wind Harmer
1.78
971199AH1-059 GEN
Solar/Wind Harmer
4.433
241960AC2-195 GEN
Solar/Wind Harmer
3.073
25326509SID D
Adder
1.452
970879AG2-548 GEN
Solar/Wind Harmer
6.78
971073AG2-665 GEN
Solar/Wind Harmer
6.78
971073AG2-665 GEN
Solar/Wind Harmer
4.73
25326109MON D
Adder
1.444
25322209TAIT E
Adder
10.653
25322209TAIT E
Adder
10.414
971201AH1-060 GEN
Solar/Wind Harmer
2.181
253370AE2-315 SEC1
Adder
2.184
253394AE2-221_GEN
Solar/Wind Harmer
4.918
253398AE2-221_GEN2
Solar/Wind Harmer
4.918
246938BC-WTG3
Solar/Wind Harmer
4.299
246937BC-WTG2
Solar/Wind Harmer
4.226
971231AH1-075 GEN
Solar/Wind Harmer
0.862
253317AC1-085 GEN4
Solar/Wind Harmer
9.013
970611AG2-400 GEN
Solar/Wind Harmer
10.743
270007AE1-245 C
Solar/Wind Harmer
6.358
942801AE2-298 GEN
Solar/Wind Harmer
1.622
962581AG1-107 GEN
Solar/Wind Harmer
5.365
961491AF2-440 GEN
Solar/Wind Harmer
2.229
25183208HLCRTG
Solar/Wind Harmer
6.449
944541AF1-119 GEN
Solar/Wind Harmer
4.453
960971AF2-388 GEN
Solar/Wind Harmer
11.621
942221AE2-234 GEN
Solar/Wind Harmer
0.778
252519AF1-045_GEN
Solar/Wind Harmer
6.447
252516AE2-318_GEN
Solar/Wind Harmer
4.918
247621Y3-024
Adder
0.256
970883AG2-550 GEN
Solar/Wind Harmer
10.602
970885AG2-551 GEN
Solar/Wind Harmer
2.465
270201AC2-176 GEN
Solar/Wind Harmer
5.449
25194408D.CRK1
Adder
8.013
25194508D.CRK3
Adder
1.498
964611AG1-324 GEN
Solar/Wind Harmer
1.248
964611AG1-324 GEN
Solar/Wind Harmer
0.554
252509AD1-136 GEN
Solar/Wind Harmer
0.271
247620Y3-023
Adder
0.484
24728805RICHG1
Adder
3.968
24728905RICHG2
Adder
3.968
274770LINCOLN ;1U
Adder
8.684
274771LINCOLN ;2U
Adder
8.684
274808UNIV PK N;4U
Adder
5.122
274803UNIV PARK;6U
Adder
5.976
972259AH1-714 GEN
Adder
19.527
274674JOLIET 9 ;6U
Adder
15.72
274696ROCKY RD ;4P
Adder
11.549
274695ROCKY RD ;2P
Adder
11.282
274693ROCKY RD ;1P
Adder
11.171
274697ROCKY RD ;3P
Adder
3.065
23585401KL_K28_T16
Solar/Wind Helper
1.478
238120AE2-309 GEN
Solar/Wind Helper
0.524
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.702
238170AE2-226 GEN2
Solar/Wind Helper
0.702
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237034AC2-136 C
Solar/Wind Helper
0.227
237002AB1-128_GEN
Solar/Wind Helper
0.443
235063AE1-101 C2
Solar/Wind Helper
1.661
237001AB1-127_GEN
Solar/Wind Helper
0.442
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.715
20390526W1-045 C
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.344
233933AB2-153 GEN
Solar/Wind Helper
0.233
232424Y1-079 C
Solar/Wind Helper
0.116
233944AB2-135 GEN
Solar/Wind Helper
0.589
233946AB2-136 GEN
Solar/Wind Helper
0.569
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.233
232408W1-005 C
Solar/Wind Helper
0.508
232410W1-006 C
Solar/Wind Helper
0.508
233939AC1-091 C
Solar/Wind Helper
0.35
233970AC1-092 C
Solar/Wind Helper
0.35
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.848
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.169
20674928WA_W3-044
Solar/Wind Helper
0.098
964851AG1-348 GEN
Solar/Wind Helper
0.081
20676228FRD_X1-012
Solar/Wind Helper
0.092
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.045
211065PSPA IPP
Solar/Wind Helper
0.152
211065PSPA IPP
Solar/Wind Helper
0.152
970321AG2-212 GEN
Solar/Wind Harmer
3.726
270166AC1-044 GEN3
50/50
7.063
23559101PLEAS2
50/50
6.112
23684101S70BUS1
50/50
0.168
962761AG1-125 GEN
Solar/Wind Harmer
40.976
970149AG2-104 GEN
Solar/Wind Harmer
50.605
970155AG2-107 GEN
Solar/Wind Harmer
17.867
270349AD2-093_GEN
Solar/Wind Harmer
4.466
24721705FLATG2
Adder
23.946
270159DARBY CT4
Adder
10.253
970593AG2-378 GEN
Solar/Wind Harmer
2.311
270223U2-072_GEN1
Solar/Wind Harmer
2.282
270578AF1-285 GEN2
Solar/Wind Harmer
1.396
270391AF1-285 GEN3
Solar/Wind Harmer
1.396
253343AC1-166 GEN
Solar/Wind Harmer
1.242
253325AC1-069 GEN
Solar/Wind Harmer
1.197
270462AD2-086
Solar/Wind Harmer
7.941
971995AH1-542 GEN
Solar/Wind Harmer
12.507
270263AC1-001 GEN
Solar/Wind Harmer
1.177
270510AE1-227 GEN1
Solar/Wind Harmer
2.727
25326309TAIT D
Adder
1.197
241813AF1-122_GEN
Solar/Wind Harmer
6.978
960071AF2-298 GEN
Solar/Wind Harmer
5.44
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.065
927014AC1-188 GEN
Solar/Wind Harmer
1.725
246936BC-WTG1
Solar/Wind Harmer
4.226
270489AE1-102 GEN1
Solar/Wind Harmer
1.404
965421AG1-410 GEN
Solar/Wind Harmer
32.379
960001AF2-291 GEN
Solar/Wind Harmer
3.256
253432AC1-085 GEN2
Solar/Wind Harmer
0.288
946171AF1-282 GEN
Solar/Wind Harmer
10.76
247521TR3_G114
Solar/Wind Harmer
3.612
270246TR4_N_V150
Solar/Wind Harmer
0.914
965011AG1-365 GEN
Solar/Wind Harmer
10.743
24695305TIMB G C
Solar/Wind Harmer
5.899
965651AG1-433 GEN
Solar/Wind Harmer
5.811
958861AF2-177 GEN
Solar/Wind Harmer
11.606
247536S-71 GEN
Solar/Wind Harmer
4.292
25194608D.CRK4
Adder
1.742
945371AF1-202 GEN
Solar/Wind Harmer
7.39
252507AC2-088 GEN
Solar/Wind Harmer
1.898
270063AE2-323 C
Solar/Wind Harmer
2.329
25196808ZIMRHP
Adder
79.816
24639705ELKHART HY
Adder
0.161
25196008MFTGT1
Adder
1.452
274751CRETE EC ;1U
Adder
8.485
274754CRETE EC ;4U
Adder
8.485
274773LINCOLN ;4U
Adder
8.684
274774LINCOLN ;5U
Adder
8.684
274723RIVER EC ;12
Adder
18.437
274812UNIV PK N;8U
Adder
5.144
24728605AND G2
Adder
3.932
274801UNIV PARK;4U
Adder
5.972
274676JOLIET 29;8U
Adder
31.334
274732ELWOOD EC;7P
Adder
16.784
274674JOLIET 9 ;6U
Adder
15.72
274745AC1-111 GEN9
Adder
5.685
970091AG2-072 GEN
Adder
77.715
316095T157 G97
Solar/Wind Helper
1.505
23583801GRNGAP
Solar/Wind Helper
5.607
238185AF2-356 C
Solar/Wind Helper
2.642
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.025
235531U2-073 GEN
Solar/Wind Helper
3.278
238117U2-030
Solar/Wind Helper
0.341
238147AE2-230_GEN1
Solar/Wind Helper
0.495
238149AF1-291A_GEN
Solar/Wind Helper
0.141
237061AD1-155 GEN
Solar/Wind Helper
0.053
23751201ROTHROCK
Solar/Wind Helper
0.819
238221AF1-254 C O1
Solar/Wind Helper
0.275
23562501BACKB
Solar/Wind Helper
1.001
235067AD1-061 GEN
Solar/Wind Helper
0.496
23751101LEADS_P59
Solar/Wind Helper
1.388
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.033
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.346
223402AF1-300 C
Solar/Wind Helper
0.368
205917AD1-020 ES
Solar/Wind Helper
0.369
233982AB2-133 GEN
Solar/Wind Helper
0.358
233918AB1-142 GEN
Solar/Wind Helper
0.503
233994AC2-023 GEN
Solar/Wind Helper
0.962
233996TM1833_GEN
Solar/Wind Helper
0.262
233997TMININ_4.2
Solar/Wind Helper
0.262
232406W1-004 FULL
Solar/Wind Helper
0.508
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.233
233971AC1-093 C
Solar/Wind Helper
0.358
316044AC1-158 PL1
Solar/Wind Helper
1.294
316450AC1-158 RIC
Solar/Wind Helper
0.345
230430AE1-229_GEN
Solar/Wind Helper
3.376
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.111
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.354
219276PARKLANDSO C
Solar/Wind Helper
0.089
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
970245AG2-165 GEN
Solar/Wind Harmer
3.726
NYPJM->LTFIMP_NY
CLTF
4.803
LGEELTFEXP_LGEE->PJM
CLTF
6.756
WECLTFEXP_WEC->PJM
CLTF
3.828
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
AH1-155LTFEXP_AH1-155->PJM
LTF
0.36
CPLELTFEXP_CPLE->PJM
CLTF
0.627
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.944
LAGNLTFEXP_LAGN->PJM
CLTF
14.855
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.816
TVALTFEXP_TVA->PJM
CLTF
7.302
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.216
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.135
MECLTFEXP_MEC->PJM
CLTF
15.918
SIGELTFEXP_SIGE->PJM
CLTF
0.506

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-014_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.63 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4908.47
MW Contribution:17.87
Bus #Bus NameTypeMW Contribution
962771AG1-126 GEN
Solar/Wind Harmer
40.976
972239AH1-704 GEN
Adder
2.69
270054AF2-122 C O1
Solar/Wind Harmer
3.996
270459AD2-067 GEN
Solar/Wind Harmer
10.248
961821AG1-024 GEN
Solar/Wind Harmer
10.404
270520AE2-214 GEN
Solar/Wind Harmer
7.276
270284AF1-227 GEN1
Solar/Wind Harmer
6.79
270286AF1-227 GEN2
Solar/Wind Harmer
2.512
270287AF1-227 GEN3
Solar/Wind Harmer
2.512
253383AE2-342_GEN
Solar/Wind Harmer
1.045
241973AD2-163_GEN1
Solar/Wind Harmer
2.331
945631AF1-228 GEN
Solar/Wind Harmer
5.463
943861AF1-054 GEN
Solar/Wind Harmer
4.486
943851AF1-053 GEN
Solar/Wind Harmer
2.168
270156DARBY CT1
Adder
10.419
270157DARBY CT2
Adder
10.393
270158DARBY CT3
Adder
10.228
970689AG2-444 GEN
Solar/Wind Harmer
18.827
270578AF1-285 GEN2
Solar/Wind Harmer
0.537
270432AC2-029 GEN
Solar/Wind Harmer
8.049
940611AE2-048 GEN
Solar/Wind Harmer
25.14
941391AE2-136 GEN
Solar/Wind Harmer
13.027
270302AB2-170 GEN
Solar/Wind Harmer
9.546
270317AD1-130_GEN
Solar/Wind Harmer
3.659
270269AC2-059
Solar/Wind Harmer
10.605
241972AD1-140 GEN
Solar/Wind Harmer
5.021
24318805MLG1
50/50
10.098
23559001PLEAS1
50/50
6.112
270051AF1-062 GEN
50/50
11.831
23684201S70BUS2
50/50
0.171
270475AD2-096_GEN
50/50
7.147
970153AG2-106 GEN
Solar/Wind Harmer
17.867
961921AG1-034 GEN
Solar/Wind Harmer
15.607
241955AC1-078 GEN
Solar/Wind Harmer
8.813
24721905FLATG4
Adder
23.946
241974AD2-163_GEN2
Solar/Wind Harmer
2.331
942051AE2-217 GEN
Solar/Wind Harmer
21.048
960801AF2-371 GEN
Solar/Wind Harmer
2.948
964871AG1-351 GEN
Solar/Wind Harmer
2.036
970605AG2-385 GEN
Solar/Wind Harmer
6.24
942871AE2-306 GEN
Solar/Wind Harmer
1.047
270391AF1-285 GEN3
Solar/Wind Harmer
0.537
253338AC1-165 GEN
Solar/Wind Harmer
1.242
253333AC1-068 GEN
Solar/Wind Harmer
1.197
270485AE1-090_GEN
Solar/Wind Harmer
0.69
270273AD2-016 GEN
Solar/Wind Harmer
3.033
972173AH1-669 GEN
Solar/Wind Harmer
5.671
270291AC1-194 GEN
Solar/Wind Harmer
11.744
253415AE1-040 GEN
Solar/Wind Harmer
1.248
270512AE1-227 GEN2
Solar/Wind Harmer
2.315
970065AG2-057 GEN
Solar/Wind Harmer
1.09
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.065
957541AF2-048 GEN
Solar/Wind Harmer
1.721
253406AD2-031_GEN
Solar/Wind Harmer
1.388
270491AE1-102 GEN2
Solar/Wind Harmer
1.404
270377AD1-106 GEN
Solar/Wind Harmer
6.655
971191AH1-055 GEN
Solar/Wind Harmer
23.692
253316AC1-085 GEN3
Solar/Wind Harmer
9.013
253433AC1-085 GEN1
Solar/Wind Harmer
5.721
946181AF1-283 GEN
Solar/Wind Harmer
13.988
270191TR4_S_V150
Solar/Wind Harmer
3.223
270247TR4_N_V136
Solar/Wind Harmer
0.914
959331AF2-224 GEN
Solar/Wind Harmer
10.743
965021AG1-366 GEN
Solar/Wind Harmer
2.498
270588AE1-091_GEN
Solar/Wind Harmer
11.792
958091AF2-103 GEN
Solar/Wind Harmer
0.173
944531AF1-118 GEN
Solar/Wind Harmer
37.418
270043AE2-236 GEN
Solar/Wind Harmer
5.874
270258AD1-119 GEN
Solar/Wind Harmer
2.962
971617AH1-308 GEN
Solar/Wind Harmer
6.179
25196608WSDLE5
Adder
9.087
252510AF1-249 C
Solar/Wind Harmer
0.443
962031AG1-047 GEN
Solar/Wind Harmer
3.204
957741AF2-068 GEN
Solar/Wind Harmer
15.899
25194608D.CRK4
Adder
1.742
270222AC2-111 GEN
Solar/Wind Harmer
8.63
970031AG2-029 GEN
Solar/Wind Harmer
31.748
270044AE2-322 C
Solar/Wind Harmer
1.39
270404AC1-167 GEN
Solar/Wind Harmer
1.158
24642205MAYFLWER
Adder
0.665
25196008MFTGT1
Adder
1.406
247604X1-042
Adder
0.433
274752CRETE EC ;2U
Adder
8.485
274753CRETE EC ;3U
Adder
8.485
274772LINCOLN ;3U
Adder
8.684
274724RIVER EC ;11
Adder
18.221
24728705AND G3
Adder
8.223
274802UNIV PARK;5U
Adder
5.976
24728505AND G1
Adder
3.932
274826FISK ;BP
Adder
11.216
274800UNIV PARK;3U
Adder
5.972
972038AH1-567 GEN2
Adder
0.374
972228AH1-698 GEN2
Adder
3.794
274676JOLIET 29;8U
Adder
30.215
274729ELWOOD EC;1P
Adder
16.784
274730ELWOOD EC;6P
Adder
16.784
274734ELWOOD EC;8P
Adder
16.784
274736ELWOOD EC;9P
Adder
16.784
274682WAUKEGAN ;7U
Adder
9.459
964991AG1-363 GEN
Solar/Wind Helper
5.14
316097T157 G90
Solar/Wind Helper
1.505
23750701CROSSCHOOL
Solar/Wind Helper
1.501
238118U2-030_1
Solar/Wind Helper
0.341
238127S14_GEN_2
Solar/Wind Helper
0.826
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237080AD1-060 GEN
Solar/Wind Helper
0.342
237038AE2-054 C
Solar/Wind Helper
0.272
235062AE1-101 C1
Solar/Wind Helper
1.661
23779801AA1-109
Solar/Wind Helper
0.193
237048AF1-022 C
Solar/Wind Helper
0.177
223401AF1-299 GEN
Solar/Wind Helper
0.368
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.077
233930AB2-032 GEN
Solar/Wind Helper
0.381
233915AB1-141 GEN
Solar/Wind Helper
0.503
232422X3-066 FULL
Solar/Wind Helper
0.114
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.262
232404W1-003 C
Solar/Wind Helper
0.508
232428Y3-058 C
Solar/Wind Helper
0.338
232434Z2-077 GEN
Solar/Wind Helper
0.127
233954AC2-188 GEN
Solar/Wind Helper
0.233
233950AC2-186 GEN
Solar/Wind Helper
0.116
233972AC1-094 C
Solar/Wind Helper
0.303
316045AC1-158 PL2
Solar/Wind Helper
4.142
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.06
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
20720728JCB_W1-129
Solar/Wind Helper
0.057
316254AC1-120 GEN1
Solar/Wind Helper
1.061
207445AB1-138_GEN
Solar/Wind Helper
0.104
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.496
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
270119AB2-067 GEN1
50/50
7.063
270120AB2-067 GEN2
50/50
7.063
24318905MLG2
50/50
7.074
270471AD2-092_GEN
Solar/Wind Harmer
4.466
946101AF1-275 GEN
Solar/Wind Harmer
1.816
942861AE2-305 GEN
Solar/Wind Harmer
9.089
970077AG2-063 GEN
Solar/Wind Harmer
6.24
270224U2-072_GEN2
Solar/Wind Harmer
2.282
270227U2-072_GEN3
Solar/Wind Harmer
2.282
270228U2-072_GEN4
Solar/Wind Harmer
2.282
270231U2-072_GEN5
Solar/Wind Harmer
2.282
938701AE1-092 GEN
Solar/Wind Harmer
23.829
964601AG1-323 GEN
Solar/Wind Harmer
3.66
964601AG1-323 GEN
Solar/Wind Harmer
1.702
270518AE2-148 GEN
Solar/Wind Harmer
13.889
972269AH1-719 GEN
Adder
2.587
972159AH1-661 GEN
Adder
1.119
253378AE2-206_GEN
Solar/Wind Harmer
4.007
276820AF1-078_GEN
Solar/Wind Harmer
1.78
971199AH1-059 GEN
Solar/Wind Harmer
4.433
241960AC2-195 GEN
Solar/Wind Harmer
3.073
25326509SID D
Adder
1.452
970879AG2-548 GEN
Solar/Wind Harmer
6.78
971073AG2-665 GEN
Solar/Wind Harmer
6.78
971073AG2-665 GEN
Solar/Wind Harmer
4.73
25326109MON D
Adder
1.444
25322209TAIT E
Adder
10.653
25322209TAIT E
Adder
10.414
971201AH1-060 GEN
Solar/Wind Harmer
2.181
253370AE2-315 SEC1
Adder
2.184
253394AE2-221_GEN
Solar/Wind Harmer
4.918
253398AE2-221_GEN2
Solar/Wind Harmer
4.918
246938BC-WTG3
Solar/Wind Harmer
4.299
246937BC-WTG2
Solar/Wind Harmer
4.226
971231AH1-075 GEN
Solar/Wind Harmer
0.862
253317AC1-085 GEN4
Solar/Wind Harmer
9.013
970611AG2-400 GEN
Solar/Wind Harmer
10.743
270007AE1-245 C
Solar/Wind Harmer
6.358
942801AE2-298 GEN
Solar/Wind Harmer
1.622
962581AG1-107 GEN
Solar/Wind Harmer
5.365
961491AF2-440 GEN
Solar/Wind Harmer
2.229
25183208HLCRTG
Solar/Wind Harmer
6.449
944541AF1-119 GEN
Solar/Wind Harmer
4.453
960971AF2-388 GEN
Solar/Wind Harmer
11.621
942221AE2-234 GEN
Solar/Wind Harmer
0.778
252519AF1-045_GEN
Solar/Wind Harmer
6.447
252516AE2-318_GEN
Solar/Wind Harmer
4.918
247621Y3-024
Adder
0.256
970883AG2-550 GEN
Solar/Wind Harmer
10.602
970885AG2-551 GEN
Solar/Wind Harmer
2.465
270201AC2-176 GEN
Solar/Wind Harmer
5.449
25194408D.CRK1
Adder
8.013
25194508D.CRK3
Adder
1.498
964611AG1-324 GEN
Solar/Wind Harmer
1.248
964611AG1-324 GEN
Solar/Wind Harmer
0.554
252509AD1-136 GEN
Solar/Wind Harmer
0.271
247620Y3-023
Adder
0.484
24728805RICHG1
Adder
3.968
24728905RICHG2
Adder
3.968
274770LINCOLN ;1U
Adder
8.684
274771LINCOLN ;2U
Adder
8.684
274808UNIV PK N;4U
Adder
5.122
274803UNIV PARK;6U
Adder
5.976
972259AH1-714 GEN
Adder
19.527
274674JOLIET 9 ;6U
Adder
15.72
274696ROCKY RD ;4P
Adder
11.549
274695ROCKY RD ;2P
Adder
11.282
274693ROCKY RD ;1P
Adder
11.171
274697ROCKY RD ;3P
Adder
3.065
23585401KL_K28_T16
Solar/Wind Helper
1.478
238120AE2-309 GEN
Solar/Wind Helper
0.524
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.702
238170AE2-226 GEN2
Solar/Wind Helper
0.702
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237034AC2-136 C
Solar/Wind Helper
0.227
237002AB1-128_GEN
Solar/Wind Helper
0.443
235063AE1-101 C2
Solar/Wind Helper
1.661
237001AB1-127_GEN
Solar/Wind Helper
0.442
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.715
20390526W1-045 C
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.344
233933AB2-153 GEN
Solar/Wind Helper
0.233
232424Y1-079 C
Solar/Wind Helper
0.116
233944AB2-135 GEN
Solar/Wind Helper
0.589
233946AB2-136 GEN
Solar/Wind Helper
0.569
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.233
232408W1-005 C
Solar/Wind Helper
0.508
232410W1-006 C
Solar/Wind Helper
0.508
233939AC1-091 C
Solar/Wind Helper
0.35
233970AC1-092 C
Solar/Wind Helper
0.35
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.848
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.169
20674928WA_W3-044
Solar/Wind Helper
0.098
964851AG1-348 GEN
Solar/Wind Helper
0.081
20676228FRD_X1-012
Solar/Wind Helper
0.092
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.045
211065PSPA IPP
Solar/Wind Helper
0.152
211065PSPA IPP
Solar/Wind Helper
0.152
970321AG2-212 GEN
Solar/Wind Harmer
3.726
270166AC1-044 GEN3
50/50
7.063
23559101PLEAS2
50/50
6.112
23684101S70BUS1
50/50
0.168
962761AG1-125 GEN
Solar/Wind Harmer
40.976
970149AG2-104 GEN
Solar/Wind Harmer
50.605
970155AG2-107 GEN
Solar/Wind Harmer
17.867
270349AD2-093_GEN
Solar/Wind Harmer
4.466
24721705FLATG2
Adder
23.946
270159DARBY CT4
Adder
10.253
970593AG2-378 GEN
Solar/Wind Harmer
2.311
270223U2-072_GEN1
Solar/Wind Harmer
2.282
270578AF1-285 GEN2
Solar/Wind Harmer
1.396
270391AF1-285 GEN3
Solar/Wind Harmer
1.396
253343AC1-166 GEN
Solar/Wind Harmer
1.242
253325AC1-069 GEN
Solar/Wind Harmer
1.197
270462AD2-086
Solar/Wind Harmer
7.941
971995AH1-542 GEN
Solar/Wind Harmer
12.507
270263AC1-001 GEN
Solar/Wind Harmer
1.177
270510AE1-227 GEN1
Solar/Wind Harmer
2.727
25326309TAIT D
Adder
1.197
241813AF1-122_GEN
Solar/Wind Harmer
6.978
960071AF2-298 GEN
Solar/Wind Harmer
5.44
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.065
927014AC1-188 GEN
Solar/Wind Harmer
1.725
246936BC-WTG1
Solar/Wind Harmer
4.226
270489AE1-102 GEN1
Solar/Wind Harmer
1.404
965421AG1-410 GEN
Solar/Wind Harmer
32.379
960001AF2-291 GEN
Solar/Wind Harmer
3.256
253432AC1-085 GEN2
Solar/Wind Harmer
0.288
946171AF1-282 GEN
Solar/Wind Harmer
10.76
247521TR3_G114
Solar/Wind Harmer
3.612
270246TR4_N_V150
Solar/Wind Harmer
0.914
965011AG1-365 GEN
Solar/Wind Harmer
10.743
24695305TIMB G C
Solar/Wind Harmer
5.899
965651AG1-433 GEN
Solar/Wind Harmer
5.811
958861AF2-177 GEN
Solar/Wind Harmer
11.606
247536S-71 GEN
Solar/Wind Harmer
4.292
25194608D.CRK4
Adder
1.742
945371AF1-202 GEN
Solar/Wind Harmer
7.39
252507AC2-088 GEN
Solar/Wind Harmer
1.898
270063AE2-323 C
Solar/Wind Harmer
2.329
25196808ZIMRHP
Adder
79.816
24639705ELKHART HY
Adder
0.161
25196008MFTGT1
Adder
1.452
274751CRETE EC ;1U
Adder
8.485
274754CRETE EC ;4U
Adder
8.485
274773LINCOLN ;4U
Adder
8.684
274774LINCOLN ;5U
Adder
8.684
274723RIVER EC ;12
Adder
18.437
274812UNIV PK N;8U
Adder
5.144
24728605AND G2
Adder
3.932
274801UNIV PARK;4U
Adder
5.972
274676JOLIET 29;8U
Adder
31.334
274732ELWOOD EC;7P
Adder
16.784
274674JOLIET 9 ;6U
Adder
15.72
274745AC1-111 GEN9
Adder
5.685
970091AG2-072 GEN
Adder
77.715
316095T157 G97
Solar/Wind Helper
1.505
23583801GRNGAP
Solar/Wind Helper
5.607
238185AF2-356 C
Solar/Wind Helper
2.642
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.025
235531U2-073 GEN
Solar/Wind Helper
3.278
238117U2-030
Solar/Wind Helper
0.341
238147AE2-230_GEN1
Solar/Wind Helper
0.495
238149AF1-291A_GEN
Solar/Wind Helper
0.141
237061AD1-155 GEN
Solar/Wind Helper
0.053
23751201ROTHROCK
Solar/Wind Helper
0.819
238221AF1-254 C O1
Solar/Wind Helper
0.275
23562501BACKB
Solar/Wind Helper
1.001
235067AD1-061 GEN
Solar/Wind Helper
0.496
23751101LEADS_P59
Solar/Wind Helper
1.388
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.033
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.346
223402AF1-300 C
Solar/Wind Helper
0.368
205917AD1-020 ES
Solar/Wind Helper
0.369
233982AB2-133 GEN
Solar/Wind Helper
0.358
233918AB1-142 GEN
Solar/Wind Helper
0.503
233994AC2-023 GEN
Solar/Wind Helper
0.962
233996TM1833_GEN
Solar/Wind Helper
0.262
233997TMININ_4.2
Solar/Wind Helper
0.262
232406W1-004 FULL
Solar/Wind Helper
0.508
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.233
233971AC1-093 C
Solar/Wind Helper
0.358
316044AC1-158 PL1
Solar/Wind Helper
1.294
316450AC1-158 RIC
Solar/Wind Helper
0.345
230430AE1-229_GEN
Solar/Wind Helper
3.376
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.111
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.354
219276PARKLANDSO C
Solar/Wind Helper
0.089
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
970245AG2-165 GEN
Solar/Wind Harmer
3.726
958581AF2-149 GEN
Solar/Wind Harmer
4.743
970179AG2-119 GEN
Solar/Wind Harmer
8.842
270340AC2-060 GEN
Solar/Wind Harmer
3.346
970879AG2-548 GEN
Solar/Wind Harmer
4.73
253372AE2-315 SEC3
Adder
2.065
253372AE2-315 SEC3
Adder
2.065
25306009OHH W.
Adder
3.133
253349AC2-067 GEN
Solar/Wind Harmer
5.407
253400AC2-068 GEN
Solar/Wind Harmer
2.174
957201AF2-014 GEN
Solar/Wind Harmer
4.898
270435AC2-044 GEN
Solar/Wind Harmer
2.16
965051AG1-369 GEN
Solar/Wind Harmer
5.365
965041AG1-368 GEN
Solar/Wind Harmer
10.719
247607V1-011 GEN
Solar/Wind Harmer
4.239
971567AH1-282 GEN
Solar/Wind Harmer
16.075
966831AG1-554 GEN
Solar/Wind Harmer
1.28
971989AH1-539 GEN
Solar/Wind Harmer
13.838
24729505KEY G4
Adder
6.925
963791AG1-232 GEN
Solar/Wind Harmer
14.411
270071AF1-092 GEN
Solar/Wind Harmer
15.995
971985AH1-537 GEN
Solar/Wind Harmer
18.996
958711AF2-162 GEN
Solar/Wind Harmer
1.076
270024AE2-089 GEN
Solar/Wind Harmer
4.988
270367AC2-061_GEN
Solar/Wind Harmer
3.378
965101AG1-375 GEN
Solar/Wind Harmer
10.618
971673AH1-337 GEN
Solar/Wind Harmer
4.878
252524AE2-267 GEN
Solar/Wind Harmer
1.672
25196408WSDLE3
Adder
9.354
25196308WSDLE2
Adder
9.273
25196208WSDLE1
Adder
9.25
25196708WSDLE6
Adder
9.227
25196508WSDLE4
Adder
8.994
971029AG2-637 GEN
Solar/Wind Harmer
15.905
270543AE2-219 C
Solar/Wind Harmer
5.429
961761AG1-017 GEN
Solar/Wind Harmer
0.454
945581AF1-223 GEN
Solar/Wind Harmer
4.803
270297AD1-101 GEN
Solar/Wind Harmer
2.947
944031AF1-071 GEN
Solar/Wind Harmer
1.064
25196108MFTGT2
Adder
1.6
25196108MFTGT2
Adder
1.486
274775LINCOLN ;6U
Adder
8.684
274776LINCOLN ;7U
Adder
8.684
274777LINCOLN ;8U
Adder
8.684
274814UNIV PK N;0U
Adder
5.189
274807UNIV PK N;3U
Adder
5.178
274805UNIV PK N;1U
Adder
5.156
274811UNIV PK N;7U
Adder
5.144
972037AH1-567 GEN1
Adder
0.188
274827FISK ;RP
Adder
7.949
972227AH1-698 GEN1
Adder
2.671
274687WILL CNTY;4U
Adder
28.551
274687WILL CNTY;4U
Adder
28.551
274675JOLIET 29;7U
Adder
31.334
274675JOLIET 29;7U
Adder
30.215
274731ELWOOD EC;2P
Adder
16.784
274733ELWOOD EC;3P
Adder
16.784
274735ELWOOD EC;4P
Adder
16.784
274728ELWOOD EC;5P
Adder
16.784
972203AH1-686 GEN
Adder
2.341
274746AC1-111 G10
Adder
5.685
274744AC1-111 GEN8
Adder
5.685
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.826
238152AF2-075_GEN
Solar/Wind Helper
0.708
238208AF1-136 C
Solar/Wind Helper
0.22
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.65
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.889
316415AF1-147_GEN2
Solar/Wind Helper
0.889
23750501ELLIOTTS
Solar/Wind Helper
0.637
959381AF2-229 GEN
Solar/Wind Helper
0.358
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.182
205943AE1-185 GEN
Solar/Wind Helper
0.51
205932AD2-116_GEN
Solar/Wind Helper
0.509
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.27
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.959
234033AF1-007_GEN
Solar/Wind Helper
7.028
233990AG1-397 GEN
Solar/Wind Helper
0.03
232432Z2-076 GEN
Solar/Wind Helper
0.067
964001AG1-254 GEN
Solar/Wind Helper
0.956
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.5
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.097
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
20674828DL_W4-046
Solar/Wind Helper
0.008
207484AF2-139 C O1
Solar/Wind Helper
0.084
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
20675128HRM_W1-127
Solar/Wind Helper
0.03
209116AE2-175 GEN
Solar/Wind Helper
1.781
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.573
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.03
970513AG2-328 GEN
Solar/Wind Harmer
3.726
970517AG2-330 GEN
Solar/Wind Harmer
3.379
NYPJM->LTFIMP_NY
CLTF
4.803
LGEELTFEXP_LGEE->PJM
CLTF
6.756
WECLTFEXP_WEC->PJM
CLTF
3.828
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
AH1-155LTFEXP_AH1-155->PJM
LTF
0.36
CPLELTFEXP_CPLE->PJM
CLTF
0.627
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.944
LAGNLTFEXP_LAGN->PJM
CLTF
14.855
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.816
TVALTFEXP_TVA->PJM
CLTF
7.302
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.216
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.135
MECLTFEXP_MEC->PJM
CLTF
15.918
SIGELTFEXP_SIGE->PJM
CLTF
0.506

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-007A_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-007A_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.62 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4870.98
MW Contribution:22.05
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
7.059
23559101PLEAS2
50/50
6.1
962761AG1-125 GEN
Solar/Wind Harmer
34.524
970149AG2-104 GEN
Solar/Wind Harmer
37.287
970155AG2-107 GEN
Solar/Wind Harmer
22.046
270349AD2-093_GEN
Solar/Wind Harmer
0.006
24721705FLATG2
Adder
23.918
270159DARBY CT4
Adder
10.243
970593AG2-378 GEN
Solar/Wind Harmer
1.812
270223U2-072_GEN1
Solar/Wind Harmer
0.001
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.012
270462AD2-086
Solar/Wind Harmer
0.017
270119AB2-067 GEN1
50/50
7.059
270120AB2-067 GEN2
50/50
7.059
24318905MLG2
50/50
7.071
270471AD2-092_GEN
Solar/Wind Harmer
0.006
942861AE2-305 GEN
Solar/Wind Harmer
6.335
970077AG2-063 GEN
Solar/Wind Harmer
4.631
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
12.917
971655AH1-328 GEN
Solar/Wind Harmer
2.854
964601AG1-323 GEN
Solar/Wind Harmer
3.215
964601AG1-323 GEN
Solar/Wind Harmer
2.143
270518AE2-148 GEN
Solar/Wind Harmer
0.691
972269AH1-719 GEN
Adder
2.584
972159AH1-661 GEN
Adder
1.118
253378AE2-206_GEN
Solar/Wind Harmer
0.004
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
3.354
971199AH1-059 GEN
Solar/Wind Harmer
3.09
241960AC2-195 GEN
Solar/Wind Harmer
0.006
25326509SID D
Adder
1.451
971073AG2-665 GEN
Solar/Wind Harmer
6.898
25326109MON D
Adder
1.443
25322209TAIT E
Adder
10.642
25322209TAIT E
Adder
10.403
971201AH1-060 GEN
Solar/Wind Harmer
1.52
253370AE2-315 SEC1
Adder
2.182
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
246938BC-WTG3
Solar/Wind Harmer
0.273
246937BC-WTG2
Solar/Wind Harmer
0.305
971231AH1-075 GEN
Solar/Wind Harmer
0.861
253317AC1-085 GEN4
Solar/Wind Harmer
0.005
970611AG2-400 GEN
Solar/Wind Harmer
7.488
970627AG2-408 GEN
Solar/Wind Harmer
2.246
270007AE1-245 C
Solar/Wind Harmer
0.002
962581AG1-107 GEN
Solar/Wind Harmer
0.002
25183208HLCRTG
Solar/Wind Harmer
0.012
944541AF1-119 GEN
Solar/Wind Harmer
0.497
960971AF2-388 GEN
Solar/Wind Harmer
4.347
970623AG2-406 GEN
Solar/Wind Harmer
1.356
942221AE2-234 GEN
Solar/Wind Harmer
0.037
252519AF1-045_GEN
Solar/Wind Harmer
6.44
252516AE2-318_GEN
Solar/Wind Harmer
5.712
247621Y3-024
Adder
0.255
970883AG2-550 GEN
Solar/Wind Harmer
7.389
970885AG2-551 GEN
Solar/Wind Harmer
2.463
270201AC2-176 GEN
Solar/Wind Harmer
0.001
25194408D.CRK1
Adder
8.004
25194508D.CRK3
Adder
1.496
970621AG2-405 GEN
Solar/Wind Harmer
1.351
964611AG1-324 GEN
Solar/Wind Harmer
0.553
252509AD1-136 GEN
Solar/Wind Harmer
0.037
970321AG2-212 GEN
Solar/Wind Harmer
3.191
270599AE1-208 GEN
Solar/Wind Harmer
6.737
270031AE2-169
Solar/Wind Harmer
4.042
270186AC1-089 GEN
Solar/Wind Harmer
0.004
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
8.127
247620Y3-023
Adder
0.484
960441AF2-335 GEN
Solar/Wind Harmer
7.33
270216AD2-079_GEN
Solar/Wind Harmer
0.001
971613AH1-306 GEN
Solar/Wind Harmer
3.512
24728805RICHG1
Adder
3.964
24728905RICHG2
Adder
3.964
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
14.589
961051AF2-396 GEN
Solar/Wind Harmer
9.726
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
9.095
965791AG1-447 GEN
Solar/Wind Harmer
6.67
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.797
274770LINCOLN ;1U
Adder
8.676
274771LINCOLN ;2U
Adder
8.676
966841AG1-555 GEN
Solar/Wind Harmer
0.81
274808UNIV PK N;4U
Adder
5.117
274803UNIV PARK;6U
Adder
5.97
274888KELLY CRK;1U
Solar/Wind Harmer
0.419
274887GEN-1.85
Solar/Wind Harmer
0.188
276843GEN-1.7
Solar/Wind Harmer
0.231
958011AF2-095 GEN
Solar/Wind Harmer
10.284
972259AH1-714 GEN
Adder
19.507
274674JOLIET 9 ;6U
Adder
15.704
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
962771AG1-126 GEN
Solar/Wind Harmer
34.524
972239AH1-704 GEN
Adder
2.689
270054AF2-122 C O1
Solar/Wind Harmer
0.007
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
5.077
270520AE2-214 GEN
Solar/Wind Harmer
0.013
270284AF1-227 GEN1
Solar/Wind Harmer
0.011
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
253383AE2-342_GEN
Solar/Wind Harmer
0.003
241973AD2-163_GEN1
Solar/Wind Harmer
0.006
945631AF1-228 GEN
Solar/Wind Harmer
0
943861AF1-054 GEN
Solar/Wind Harmer
3.127
943851AF1-053 GEN
Solar/Wind Harmer
2.166
270156DARBY CT1
Adder
10.409
270157DARBY CT2
Adder
10.383
270158DARBY CT3
Adder
10.218
970689AG2-444 GEN
Solar/Wind Harmer
16.436
270578AF1-285 GEN2
Solar/Wind Harmer
0.536
270432AC2-029 GEN
Solar/Wind Harmer
3.553
940611AE2-048 GEN
Solar/Wind Harmer
19.602
941391AE2-136 GEN
Solar/Wind Harmer
11.042
270302AB2-170 GEN
Solar/Wind Harmer
0.005
270317AD1-130_GEN
Solar/Wind Harmer
0.011
971653AH1-327 GEN
Solar/Wind Harmer
1.117
270269AC2-059
Solar/Wind Harmer
0.005
241972AD1-140 GEN
Solar/Wind Harmer
0.854
970179AG2-119 GEN
Solar/Wind Harmer
6.883
270340AC2-060 GEN
Solar/Wind Harmer
0.009
970879AG2-548 GEN
Solar/Wind Harmer
6.898
253372AE2-315 SEC3
Adder
2.063
253372AE2-315 SEC3
Adder
2.063
25306009OHH W.
Adder
3.13
253349AC2-067 GEN
Solar/Wind Harmer
2.381
253400AC2-068 GEN
Solar/Wind Harmer
0.958
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.953
965051AG1-369 GEN
Solar/Wind Harmer
3.739
965041AG1-368 GEN
Solar/Wind Harmer
7.471
247607V1-011 GEN
Solar/Wind Harmer
0.001
971567AH1-282 GEN
Solar/Wind Harmer
11.206
971989AH1-539 GEN
Solar/Wind Harmer
3.215
963791AG1-232 GEN
Solar/Wind Harmer
10.044
24729505KEY G4
Adder
6.919
270071AF1-092 GEN
Solar/Wind Harmer
14.245
971985AH1-537 GEN
Solar/Wind Harmer
2.206
270024AE2-089 GEN
Solar/Wind Harmer
0.008
270367AC2-061_GEN
Solar/Wind Harmer
0.006
965101AG1-375 GEN
Solar/Wind Harmer
7.401
971673AH1-337 GEN
Solar/Wind Harmer
4.804
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
9.344
25196308WSDLE2
Adder
9.263
25196208WSDLE1
Adder
9.24
25196708WSDLE6
Adder
9.217
25196508WSDLE4
Adder
8.984
971029AG2-637 GEN
Solar/Wind Harmer
11.085
270543AE2-219 C
Solar/Wind Harmer
0.004
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270297AD1-101 GEN
Solar/Wind Harmer
0.002
971347AH1-153 GEN
Solar/Wind Harmer
11.025
971609AH1-304 GEN
Solar/Wind Harmer
1.2
270240V3-007_GEN2
Solar/Wind Harmer
0.002
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
970115AG2-085 GEN
Solar/Wind Harmer
2.932
270594AE1-207 GEN
Solar/Wind Harmer
8.194
970289AG2-191 GEN
Solar/Wind Harmer
1.389
970241AG2-163 GEN
Solar/Wind Harmer
4.144
958481AF2-142 GEN
Solar/Wind Harmer
10.621
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.958
971573AH1-285 GEN
Solar/Wind Harmer
1.319
274696ROCKY RD ;4P
Adder
11.537
274695ROCKY RD ;2P
Adder
11.271
274693ROCKY RD ;1P
Adder
11.16
274697ROCKY RD ;3P
Adder
3.062
958491AF2-143 GEN
Solar/Wind Harmer
10.588
274879MINONK ;1U
Solar/Wind Harmer
0.297
23585401KL_K28_T16
Solar/Wind Helper
1.482
238120AE2-309 GEN
Solar/Wind Helper
0.525
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.701
238170AE2-226 GEN2
Solar/Wind Helper
0.701
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237002AB1-128_GEN
Solar/Wind Helper
0.443
237034AC2-136 C
Solar/Wind Helper
0.227
235063AE1-101 C2
Solar/Wind Helper
1.659
237001AB1-127_GEN
Solar/Wind Helper
0.442
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.713
20390526W1-045 C
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.342
233933AB2-153 GEN
Solar/Wind Helper
0.232
233944AB2-135 GEN
Solar/Wind Helper
0.588
232424Y1-079 C
Solar/Wind Helper
0.116
234036AF2-325 C
Solar/Wind Helper
0.042
233946AB2-136 GEN
Solar/Wind Helper
0.568
233901CHERRYDALE C
Solar/Wind Helper
0.232
232408W1-005 C
Solar/Wind Helper
0.507
232410W1-006 C
Solar/Wind Helper
0.507
233939AC1-091 C
Solar/Wind Helper
0.35
233970AC1-092 C
Solar/Wind Helper
0.35
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.845
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.051
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.09
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.168
20674928WA_W3-044
Solar/Wind Helper
0.098
20676228FRD_X1-012
Solar/Wind Helper
0.092
964851AG1-348 GEN
Solar/Wind Helper
0.081
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.074
211065PSPA IPP
Solar/Wind Helper
0.151
211065PSPA IPP
Solar/Wind Helper
0.151
971771AH1-392 GEN
Solar/Wind Harmer
7.306
971619AH1-309 GEN
Solar/Wind Harmer
3.285
971769AH1-391 GEN
Solar/Wind Harmer
8.134
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
25196108MFTGT2
Adder
1.599
25196108MFTGT2
Adder
1.484
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
4.302
971549AH1-272 GEN
Solar/Wind Harmer
14.865
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.676
274776LINCOLN ;7U
Adder
8.676
274777LINCOLN ;8U
Adder
8.676
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
5.184
274807UNIV PK N;3U
Adder
5.173
274805UNIV PK N;1U
Adder
5.15
274811UNIV PK N;7U
Adder
5.139
972037AH1-567 GEN1
Adder
0.187
960591AF2-350 GEN
Solar/Wind Harmer
7.141
274827FISK ;RP
Adder
7.941
972227AH1-698 GEN1
Adder
2.669
963841AG1-237 GEN
Solar/Wind Harmer
3.09
972163AH1-664 GEN
Solar/Wind Harmer
7.933
972165AH1-665 GEN
Solar/Wind Harmer
6.354
274687WILL CNTY;4U
Adder
28.523
274687WILL CNTY;4U
Adder
28.523
274675JOLIET 29;7U
Adder
31.303
274675JOLIET 29;7U
Adder
30.185
274731ELWOOD EC;2P
Adder
16.768
274733ELWOOD EC;3P
Adder
16.768
274735ELWOOD EC;4P
Adder
16.768
274728ELWOOD EC;5P
Adder
16.768
970833AG2-524 GEN
Solar/Wind Harmer
7.824
970833AG2-524 GEN
Solar/Wind Harmer
5.216
274746AC1-111 G10
Adder
5.679
274744AC1-111 GEN8
Adder
5.679
972203AH1-686 GEN
Adder
2.338
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
276868AE1-113 GEN
Solar/Wind Harmer
1.414
276882AE2-255 GEN
Solar/Wind Harmer
0.824
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.827
238152AF2-075_GEN
Solar/Wind Helper
0.707
238208AF1-136 C
Solar/Wind Helper
0.22
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.649
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.888
316415AF1-147_GEN2
Solar/Wind Helper
0.888
23750501ELLIOTTS
Solar/Wind Helper
0.638
959381AF2-229 GEN
Solar/Wind Helper
0.357
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.364
205943AE1-185 GEN
Solar/Wind Helper
0.509
205932AD2-116_GEN
Solar/Wind Helper
0.509
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.269
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.958
233990AG1-397 GEN
Solar/Wind Helper
0.27
232432Z2-076 GEN
Solar/Wind Helper
0.067
234033AF1-007_GEN
Solar/Wind Helper
7.02
964001AG1-254 GEN
Solar/Wind Helper
0.955
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.498
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.096
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.16
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.136
20675128HRM_W1-127
Solar/Wind Helper
0.029
209116AE2-175 GEN
Solar/Wind Helper
1.778
971995AH1-542 GEN
Solar/Wind Harmer
2.906
270263AC1-001 GEN
Solar/Wind Harmer
0.786
270510AE1-227 GEN1
Solar/Wind Harmer
1.963
25326309TAIT D
Adder
1.196
241813AF1-122_GEN
Solar/Wind Harmer
3.405
960071AF2-298 GEN
Solar/Wind Harmer
3.786
253370AE2-315 SEC1
Adder
2.182
253371AE2-315 SEC2
Adder
2.063
927014AC1-188 GEN
Solar/Wind Harmer
0.005
246936BC-WTG1
Solar/Wind Harmer
0.305
270489AE1-102 GEN1
Solar/Wind Harmer
0.979
965421AG1-410 GEN
Solar/Wind Harmer
22.57
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.499
247521TR3_G114
Solar/Wind Harmer
0.273
270246TR4_N_V150
Solar/Wind Harmer
0.048
965011AG1-365 GEN
Solar/Wind Harmer
7.488
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
2.174
958861AF2-177 GEN
Solar/Wind Harmer
3.207
247536S-71 GEN
Solar/Wind Harmer
0.297
25194608D.CRK4
Adder
1.74
945371AF1-202 GEN
Solar/Wind Harmer
0.001
252507AC2-088 GEN
Solar/Wind Harmer
0.335
270063AE2-323 C
Solar/Wind Harmer
0.006
970245AG2-165 GEN
Solar/Wind Harmer
3.191
970947AG2-589 GEN
Solar/Wind Harmer
0.245
270005AE1-210 C O1
Solar/Wind Harmer
1.59
965031AG1-367 GEN
Solar/Wind Harmer
7.338
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.378
970825AG2-519 GEN
Solar/Wind Harmer
2.603
25196808ZIMRHP
Adder
79.729
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
944231AF1-091 GEN
Solar/Wind Harmer
1.953
24639705ELKHART HY
Adder
0.161
270032AE2-172
Solar/Wind Harmer
4.877
970291AG2-192 GEN
Solar/Wind Harmer
0.95
945111AF1-176 GEN
Solar/Wind Harmer
13.03
270505AE1-170 C O1
Solar/Wind Harmer
7.665
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.805
276903AD2-071 C
Solar/Wind Harmer
8.137
25196008MFTGT1
Adder
1.45
247522W1-056 GEN
Solar/Wind Harmer
0.001
970773AG2-487 GEN
Solar/Wind Harmer
1.284
970373AG2-245 GEN
Solar/Wind Harmer
15.247
270055AF2-134 C O1
Solar/Wind Harmer
0.006
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.41
970515AG2-329 GEN
Solar/Wind Harmer
18.805
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
9.032
24791305MDL-5G
Solar/Wind Harmer
0.001
970333AG2-219 GEN
Solar/Wind Harmer
5.139
274751CRETE EC ;1U
Adder
8.477
274754CRETE EC ;4U
Adder
8.477
274773LINCOLN ;4U
Adder
8.676
274774LINCOLN ;5U
Adder
8.676
274723RIVER EC ;12
Adder
18.418
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
5.139
24728605AND G2
Adder
3.927
276776AD2-060 GEN
Solar/Wind Harmer
0.746
945681AF1-233 GEN
Solar/Wind Harmer
13.461
274801UNIV PARK;4U
Adder
5.966
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
31.303
274732ELWOOD EC;7P
Adder
16.768
274674JOLIET 9 ;6U
Adder
15.704
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
16.815
274745AC1-111 GEN9
Adder
5.679
939401AE1-172 GEN
Solar/Wind Harmer
5.301
276691AA1-018 GEN1
Solar/Wind Harmer
0.858
970091AG2-072 GEN
Adder
77.629
276901AD2-066 C O1
Solar/Wind Harmer
0.007
316095T157 G97
Solar/Wind Helper
1.504
23583801GRNGAP
Solar/Wind Helper
5.601
238185AF2-356 C
Solar/Wind Helper
2.646
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.03
235531U2-073 GEN
Solar/Wind Helper
3.282
238117U2-030
Solar/Wind Helper
0.341
238147AE2-230_GEN1
Solar/Wind Helper
0.495
238149AF1-291A_GEN
Solar/Wind Helper
0.141
23751201ROTHROCK
Solar/Wind Helper
0.824
237061AD1-155 GEN
Solar/Wind Helper
0.053
23562501BACKB
Solar/Wind Helper
1.007
238221AF1-254 C O1
Solar/Wind Helper
0.274
235067AD1-061 GEN
Solar/Wind Helper
0.496
23751101LEADS_P59
Solar/Wind Helper
1.404
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.032
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.346
223402AF1-300 C
Solar/Wind Helper
0.367
205917AD1-020 ES
Solar/Wind Helper
0.368
233918AB1-142 GEN
Solar/Wind Helper
0.502
233982AB2-133 GEN
Solar/Wind Helper
0.358
233994AC2-023 GEN
Solar/Wind Helper
0.961
233996TM1833_GEN
Solar/Wind Helper
0.261
233997TMININ_4.2
Solar/Wind Helper
0.261
232406W1-004 FULL
Solar/Wind Helper
0.507
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.232
233971AC1-093 C
Solar/Wind Helper
0.357
316044AC1-158 PL1
Solar/Wind Helper
1.293
316450AC1-158 RIC
Solar/Wind Helper
0.345
230430AE1-229_GEN
Solar/Wind Helper
3.372
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.11
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.114
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.353
219276PARKLANDSO C
Solar/Wind Helper
0.089
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219908AB1-139 C
Solar/Wind Helper
0.074
219249CENTRALDIV C
Solar/Wind Helper
0.01
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
971997AH1-543 GEN
Solar/Wind Harmer
2.724
24318805MLG1
50/50
10.095
23559001PLEAS1
50/50
6.1
270051AF1-062 GEN
50/50
11.821
270475AD2-096_GEN
50/50
7.141
970153AG2-106 GEN
Solar/Wind Harmer
22.046
961921AG1-034 GEN
Solar/Wind Harmer
7.615
241955AC1-078 GEN
Solar/Wind Harmer
0.007
24721905FLATG4
Adder
23.918
241974AD2-163_GEN2
Solar/Wind Harmer
0.006
942051AE2-217 GEN
Solar/Wind Harmer
14.671
970605AG2-385 GEN
Solar/Wind Harmer
4.899
270391AF1-285 GEN3
Solar/Wind Harmer
0.536
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.012
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270273AD2-016 GEN
Solar/Wind Harmer
0.821
972173AH1-669 GEN
Solar/Wind Harmer
3.952
270291AC1-194 GEN
Solar/Wind Harmer
6.106
253415AE1-040 GEN
Solar/Wind Harmer
0.003
270512AE1-227 GEN2
Solar/Wind Harmer
1.963
970065AG2-057 GEN
Solar/Wind Harmer
0.76
253370AE2-315 SEC1
Adder
2.182
253371AE2-315 SEC2
Adder
2.063
253406AD2-031_GEN
Solar/Wind Harmer
0.563
970191AG2-125 GEN
Solar/Wind Harmer
1.945
270491AE1-102 GEN2
Solar/Wind Harmer
0.979
270377AD1-106 GEN
Solar/Wind Harmer
2.855
971191AH1-055 GEN
Solar/Wind Harmer
19.26
253316AC1-085 GEN3
Solar/Wind Harmer
0.005
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.749
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.048
959331AF2-224 GEN
Solar/Wind Harmer
5.242
965021AG1-366 GEN
Solar/Wind Harmer
2.496
270588AE1-091_GEN
Solar/Wind Harmer
5.845
944531AF1-118 GEN
Solar/Wind Harmer
33.395
270043AE2-236 GEN
Solar/Wind Harmer
4.777
270258AD1-119 GEN
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
6.173
25196608WSDLE5
Adder
9.077
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
252510AF1-249 C
Solar/Wind Harmer
0.057
957741AF2-068 GEN
Solar/Wind Harmer
11.081
25194608D.CRK4
Adder
1.74
270222AC2-111 GEN
Solar/Wind Harmer
3.739
970031AG2-029 GEN
Solar/Wind Harmer
4.795
270404AC1-167 GEN
Solar/Wind Harmer
0.003
970513AG2-328 GEN
Solar/Wind Harmer
3.191
970517AG2-330 GEN
Solar/Wind Harmer
19.146
970349AG2-230 GEN
Solar/Wind Harmer
11.025
946031AF1-268 GEN
Solar/Wind Harmer
6.992
958821AF2-173 GEN
Solar/Wind Harmer
10.273
270004AE1-209 GEN
Solar/Wind Harmer
1.59
270437AC2-090 C
Solar/Wind Harmer
0.003
247643Z2-116 C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.804
970291AG2-192 GEN
Solar/Wind Harmer
0.731
247642Z2-115 C
Solar/Wind Harmer
0.003
945111AF1-176 GEN
Solar/Wind Harmer
5.919
24642205MAYFLWER
Adder
0.665
25196008MFTGT1
Adder
1.405
270356AE2-297 GEN
Solar/Wind Harmer
0.01
24441205WTRV SLR C
Solar/Wind Harmer
0
247604X1-042
Adder
0.433
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970217AG2-149 GEN
Solar/Wind Harmer
6.268
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
7.196
970243AG2-164 GEN
Solar/Wind Harmer
4.205
970519AG2-331 GEN
Solar/Wind Harmer
18.687
970699AG2-449 GEN
Solar/Wind Harmer
1.797
274752CRETE EC ;2U
Adder
8.477
274753CRETE EC ;3U
Adder
8.477
958171AF2-111 GEN
Solar/Wind Harmer
17.94
274772LINCOLN ;3U
Adder
8.676
274724RIVER EC ;11
Adder
18.203
972167AH1-666 GEN
Solar/Wind Harmer
5.717
24728705AND G3
Adder
8.214
274802UNIV PARK;5U
Adder
5.97
24728505AND G1
Adder
3.927
276806AD2-047 C O1
Solar/Wind Harmer
4.047
970941AG2-585 GEN
Solar/Wind Harmer
8.927
274826FISK ;BP
Adder
11.205
274800UNIV PARK;3U
Adder
5.966
972038AH1-567 GEN2
Adder
0.373
972228AH1-698 GEN2
Adder
3.79
276897AD1-100 C
Solar/Wind Harmer
0.009
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
970707AG2-453 GEN
Solar/Wind Harmer
23.303
274676JOLIET 29;8U
Adder
30.185
276893AG1-478 C
Solar/Wind Harmer
0.282
274729ELWOOD EC;1P
Adder
16.768
274730ELWOOD EC;6P
Adder
16.768
274734ELWOOD EC;8P
Adder
16.768
274736ELWOOD EC;9P
Adder
16.768
943121AE2-341 GEN
Solar/Wind Harmer
11.888
943591AF1-030 GEN
Solar/Wind Harmer
7.906
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
270541AE2-072 C
Solar/Wind Harmer
0.009
274682WAUKEGAN ;7U
Adder
9.728
276805AD2-038 GEN
Solar/Wind Harmer
0.002
964991AG1-363 GEN
Solar/Wind Helper
5.136
316097T157 G90
Solar/Wind Helper
1.504
23750701CROSSCHOOL
Solar/Wind Helper
1.502
238118U2-030_1
Solar/Wind Helper
0.341
238127S14_GEN_2
Solar/Wind Helper
0.827
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237080AD1-060 GEN
Solar/Wind Helper
0.342
237038AE2-054 C
Solar/Wind Helper
0.272
235062AE1-101 C1
Solar/Wind Helper
1.659
23779801AA1-109
Solar/Wind Helper
0.193
237048AF1-022 C
Solar/Wind Helper
0.177
223401AF1-299 GEN
Solar/Wind Helper
0.367
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.137
233930AB2-032 GEN
Solar/Wind Helper
0.381
233915AB1-141 GEN
Solar/Wind Helper
0.502
232422X3-066 FULL
Solar/Wind Helper
0.114
232428Y3-058 C
Solar/Wind Helper
0.338
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.261
232404W1-003 C
Solar/Wind Helper
0.507
232434Z2-077 GEN
Solar/Wind Helper
0.127
233954AC2-188 GEN
Solar/Wind Helper
0.232
233950AC2-186 GEN
Solar/Wind Helper
0.116
233972AC1-094 C
Solar/Wind Helper
0.302
316045AC1-158 PL2
Solar/Wind Helper
4.138
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.06
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
20720728JCB_W1-129
Solar/Wind Helper
0.057
316254AC1-120 GEN1
Solar/Wind Helper
1.059
207445AB1-138_GEN
Solar/Wind Helper
0.104
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.13
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.495
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.571
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.029
NYPJM->LTFIMP_NY
CLTF
4.797
LGEELTFEXP_LGEE->PJM
CLTF
6.749
WECLTFEXP_WEC->PJM
CLTF
3.825
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
AH1-155LTFEXP_AH1-155->PJM
LTF
0.359
CPLELTFEXP_CPLE->PJM
CLTF
0.624
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.816
LAGNLTFEXP_LAGN->PJM
CLTF
14.837
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.802
TVALTFEXP_TVA->PJM
CLTF
7.293
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.078
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.1
MECLTFEXP_MEC->PJM
CLTF
15.901
SIGELTFEXP_SIGE->PJM
CLTF
0.505

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-012_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-012_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:130.23 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4856.26
MW Contribution:17.86
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
7.033
23559101PLEAS2
50/50
5.443
270122AB2-093 CT
50/50
4.116
962761AG1-125 GEN
Solar/Wind Harmer
40.965
970149AG2-104 GEN
Solar/Wind Harmer
50.592
970155AG2-107 GEN
Solar/Wind Harmer
17.863
270349AD2-093_GEN
Solar/Wind Harmer
4.529
270223U2-072_GEN1
Solar/Wind Harmer
2.339
270578AF1-285 GEN2
Solar/Wind Harmer
1.43
270391AF1-285 GEN3
Solar/Wind Harmer
1.43
270159DARBY CT4
Adder
10.388
971995AH1-542 GEN
Solar/Wind Harmer
12.974
970593AG2-378 GEN
Solar/Wind Harmer
2.345
270462AD2-086
Solar/Wind Harmer
8.157
270510AE1-227 GEN1
Solar/Wind Harmer
2.893
24721705FLATG2
Adder
23.506
253343AC1-166 GEN
Solar/Wind Harmer
1.256
253325AC1-069 GEN
Solar/Wind Harmer
1.211
241813AF1-122_GEN
Solar/Wind Harmer
7.346
270263AC1-001 GEN
Solar/Wind Harmer
1.187
241847AF2-150_GEN
Solar/Wind Harmer
4.622
246936BC-WTG1
Solar/Wind Harmer
4.343
270489AE1-102 GEN1
Solar/Wind Harmer
1.443
965421AG1-410 GEN
Solar/Wind Harmer
33.256
970515AG2-329 GEN
Solar/Wind Harmer
16.033
25326309TAIT D
Adder
1.21
960071AF2-298 GEN
Solar/Wind Harmer
5.501
253370AE2-315 SEC1
Adder
2.206
253371AE2-315 SEC2
Adder
2.086
247521TR3_G114
Solar/Wind Harmer
3.699
270246TR4_N_V150
Solar/Wind Harmer
0.936
247522W1-056 GEN
Solar/Wind Harmer
2.477
24695305TIMB G C
Solar/Wind Harmer
6.051
965011AG1-365 GEN
Solar/Wind Harmer
10.972
927014AC1-188 GEN
Solar/Wind Harmer
1.729
944231AF1-091 GEN
Solar/Wind Harmer
4.078
253432AC1-085 GEN2
Solar/Wind Harmer
0.29
946171AF1-282 GEN
Solar/Wind Harmer
10.828
270063AE2-323 C
Solar/Wind Harmer
2.376
965651AG1-433 GEN
Solar/Wind Harmer
5.885
958861AF2-177 GEN
Solar/Wind Harmer
11.752
247536S-71 GEN
Solar/Wind Harmer
4.346
960001AF2-291 GEN
Solar/Wind Harmer
3.244
945371AF1-202 GEN
Solar/Wind Harmer
7.479
24639705ELKHART HY
Adder
0.164
25194608D.CRK4
Adder
1.752
25196808ZIMRHP
Adder
80.188
23906502RICHG2&3
Adder
1.272
972301AH1-735 GEN
Adder
6.357
23906402RICHG1
Adder
1.271
25196008MFTGT1
Adder
1.459
274751CRETE EC ;1U
Adder
8.598
274754CRETE EC ;4U
Adder
8.598
274723RIVER EC ;12
Adder
18.677
274773LINCOLN ;4U
Adder
8.792
274774LINCOLN ;5U
Adder
8.792
274812UNIV PK N;8U
Adder
5.21
23920202STRYCT
Adder
1.444
274801UNIV PARK;4U
Adder
6.045
274676JOLIET 29;8U
Adder
31.706
274732ELWOOD EC;7P
Adder
2.004
23583801GRNGAP
Solar/Wind Helper
6.365
316095T157 G97
Solar/Wind Helper
1.705
238108AE1-109 GEN1
Solar/Wind Helper
0.121
238185AF2-356 C
Solar/Wind Helper
2.767
238147AE2-230_GEN1
Solar/Wind Helper
0.552
238149AF1-291A_GEN
Solar/Wind Helper
0.158
237061AD1-155 GEN
Solar/Wind Helper
0.06
235054AD2-180 GEN
Solar/Wind Helper
2.111
235531U2-073 GEN
Solar/Wind Helper
3.439
238117U2-030
Solar/Wind Helper
0.356
238221AF1-254 C O1
Solar/Wind Helper
0.295
235067AD1-061 GEN
Solar/Wind Helper
0.532
3141196NOKESVL
Solar/Wind Helper
1.141
23751201ROTHROCK
Solar/Wind Helper
0.819
237030AB1-096 C
Solar/Wind Helper
0.075
23562501BACKB
Solar/Wind Helper
0.997
226910AB2-157 C
Solar/Wind Helper
0.015
227287AC2-120 GEN
Solar/Wind Helper
0.375
223402AF1-300 C
Solar/Wind Helper
0.387
316044AC1-158 PL1
Solar/Wind Helper
1.443
316450AC1-158 RIC
Solar/Wind Helper
0.385
316170AC1-121 GEN2
Solar/Wind Helper
0.395
23751101LEADS_P59
Solar/Wind Helper
1.316
205917AD1-020 ES
Solar/Wind Helper
0.379
3132273ORANGE
Solar/Wind Helper
0.049
233918AB1-142 GEN
Solar/Wind Helper
0.511
233982AB2-133 GEN
Solar/Wind Helper
0.364
233994AC2-023 GEN
Solar/Wind Helper
0.977
233996TM1833_GEN
Solar/Wind Helper
0.266
233997TMININ_4.2
Solar/Wind Helper
0.266
232406W1-004 FULL
Solar/Wind Helper
0.516
3147666LOUISA
Solar/Wind Helper
0.551
233940AF2-379 C
Solar/Wind Helper
0.063
234015AF2-250 C
Solar/Wind Helper
0.039
233952AC2-187 GEN
Solar/Wind Helper
0.236
233971AC1-093 C
Solar/Wind Helper
0.363
230430AE1-229_GEN
Solar/Wind Helper
3.409
230415AB2-049 C
Solar/Wind Helper
0.031
228729W2-030 C
Solar/Wind Helper
0.112
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.151
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.064
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
219276PARKLANDSO C
Solar/Wind Helper
0.09
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
966881AG1-559 GEN
Solar/Wind Helper
0.312
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
972239AH1-704 GEN
50/50
3.102
962771AG1-126 GEN
Solar/Wind Harmer
40.965
270459AD2-067 GEN
Solar/Wind Harmer
10.453
961821AG1-024 GEN
Solar/Wind Harmer
10.613
270054AF2-122 C O1
Solar/Wind Harmer
4.071
270284AF1-227 GEN1
Solar/Wind Harmer
6.912
270286AF1-227 GEN2
Solar/Wind Harmer
2.557
270287AF1-227 GEN3
Solar/Wind Harmer
2.557
270520AE2-214 GEN
Solar/Wind Harmer
7.382
253383AE2-342_GEN
Solar/Wind Harmer
1.062
241973AD2-163_GEN1
Solar/Wind Harmer
2.37
940611AE2-048 GEN
Solar/Wind Harmer
26.074
941391AE2-136 GEN
Solar/Wind Harmer
13.511
270578AF1-285 GEN2
Solar/Wind Harmer
0.55
943861AF1-054 GEN
Solar/Wind Harmer
4.552
943851AF1-053 GEN
Solar/Wind Harmer
2.2
945631AF1-228 GEN
Solar/Wind Harmer
5.537
270156DARBY CT1
Adder
10.556
270157DARBY CT2
Adder
10.53
270158DARBY CT3
Adder
10.362
270302AB2-170 GEN
Solar/Wind Harmer
9.805
270317AD1-130_GEN
Solar/Wind Harmer
3.759
970689AG2-444 GEN
Solar/Wind Harmer
19.055
270432AC2-029 GEN
Solar/Wind Harmer
8.138
958581AF2-149 GEN
Solar/Wind Harmer
4.968
970179AG2-119 GEN
Solar/Wind Harmer
9.26
270269AC2-059
Solar/Wind Harmer
10.704
241972AD1-140 GEN
Solar/Wind Harmer
5.084
971567AH1-282 GEN
Solar/Wind Harmer
16.984
966831AG1-554 GEN
Solar/Wind Harmer
1.34
971989AH1-539 GEN
Solar/Wind Harmer
14.49
270340AC2-060 GEN
Solar/Wind Harmer
3.371
957201AF2-014 GEN
Solar/Wind Harmer
5.033
270435AC2-044 GEN
Solar/Wind Harmer
2.219
970879AG2-548 GEN
Solar/Wind Harmer
4.763
247607V1-011 GEN
Solar/Wind Harmer
4.359
253372AE2-315 SEC3
Adder
2.086
253372AE2-315 SEC3
Adder
2.086
965051AG1-369 GEN
Solar/Wind Harmer
5.494
25306009OHH W.
Adder
3.166
270297AD1-101 GEN
Solar/Wind Harmer
3.056
965041AG1-368 GEN
Solar/Wind Harmer
10.974
253349AC2-067 GEN
Solar/Wind Harmer
5.466
253400AC2-068 GEN
Solar/Wind Harmer
2.198
963791AG1-232 GEN
Solar/Wind Harmer
14.679
270071AF1-092 GEN
Solar/Wind Harmer
16.242
24729505KEY G4
Adder
7.02
945641AF1-229 GEN
Solar/Wind Harmer
3.923
270024AE2-089 GEN
Solar/Wind Harmer
5.065
958711AF2-162 GEN
Solar/Wind Harmer
1.089
965101AG1-375 GEN
Solar/Wind Harmer
10.752
961761AG1-017 GEN
Solar/Wind Harmer
0.46
270543AE2-219 C
Solar/Wind Harmer
5.494
971029AG2-637 GEN
Solar/Wind Harmer
16.089
971673AH1-337 GEN
Solar/Wind Harmer
4.934
25196408WSDLE3
Adder
9.412
25196308WSDLE2
Adder
9.33
25196208WSDLE1
Adder
9.306
25196708WSDLE6
Adder
9.283
25196508WSDLE4
Adder
9.049
25196108MFTGT2
Adder
1.608
25196108MFTGT2
Adder
1.494
274775LINCOLN ;6U
Adder
8.792
274776LINCOLN ;7U
Adder
8.792
274777LINCOLN ;8U
Adder
8.792
274814UNIV PK N;0U
Adder
5.256
274807UNIV PK N;3U
Adder
5.245
274805UNIV PK N;1U
Adder
5.222
274811UNIV PK N;7U
Adder
5.21
972037AH1-567 GEN1
Adder
0.19
274827FISK ;RP
Adder
8.047
972227AH1-698 GEN1
Adder
2.704
274687WILL CNTY;4U
Adder
28.893
274687WILL CNTY;4U
Adder
28.893
274675JOLIET 29;7U
Adder
31.706
274675JOLIET 29;7U
Adder
30.574
274731ELWOOD EC;2P
Adder
16.983
274733ELWOOD EC;3P
Adder
16.983
274735ELWOOD EC;4P
Adder
16.983
274728ELWOOD EC;5P
Adder
16.983
238109AE1-109 GEN2
Solar/Wind Helper
0.121
238110AE1-109 GEN3
Solar/Wind Helper
0.121
238152AF2-075_GEN
Solar/Wind Helper
0.789
23546401DTGZ2-030
Solar/Wind Helper
0.099
238126S14_GEN_1
Solar/Wind Helper
0.867
238208AF1-136 C
Solar/Wind Helper
0.236
237085AD2-009_GEN
Solar/Wind Helper
1.767
3138216PACIFIC
Solar/Wind Helper
0.049
316411AF1-147_GEN1
Solar/Wind Helper
0.978
316415AF1-147_GEN2
Solar/Wind Helper
0.978
3141426STAFORD
Solar/Wind Helper
0.058
316164AC1-076 GEN
Solar/Wind Helper
1.225
23750501ELLIOTTS
Solar/Wind Helper
0.629
959381AF2-229 GEN
Solar/Wind Helper
0.367
960921AF2-383 GEN
Solar/Wind Helper
0.185
205943AE1-185 GEN
Solar/Wind Helper
0.518
205932AD2-116_GEN
Solar/Wind Helper
0.518
205956AE1-196_GEN
Solar/Wind Helper
0.518
233935AB2-179 C
Solar/Wind Helper
1.29
232436AB1-176 C
Solar/Wind Helper
0.045
233923SMA
Solar/Wind Helper
0.974
233990AG1-397 GEN
Solar/Wind Helper
0.031
232432Z2-076 GEN
Solar/Wind Helper
0.068
234033AF1-007_GEN
Solar/Wind Helper
7.137
964001AG1-254 GEN
Solar/Wind Helper
0.966
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.116
203975AE1-071-GEN
Solar/Wind Helper
2.53
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.081
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.292
219620RIDERU C
Solar/Wind Helper
0.001
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
20674828DL_W4-046
Solar/Wind Helper
0.008
207484AF2-139 C O1
Solar/Wind Helper
0.084
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.136
20675128HRM_W1-127
Solar/Wind Helper
0.029
209116AE2-175 GEN
Solar/Wind Helper
1.768
945581AF1-223 GEN
Solar/Wind Harmer
0.763
24318805MLG1
50/50
10.022
23559001PLEAS1
50/50
5.443
270051AF1-062 GEN
50/50
11.999
970153AG2-106 GEN
Solar/Wind Harmer
17.863
961921AG1-034 GEN
Solar/Wind Harmer
15.919
241955AC1-078 GEN
Solar/Wind Harmer
8.948
241974AD2-163_GEN2
Solar/Wind Harmer
2.37
942051AE2-217 GEN
Solar/Wind Harmer
21.374
942871AE2-306 GEN
Solar/Wind Harmer
1.073
270391AF1-285 GEN3
Solar/Wind Harmer
0.55
960801AF2-371 GEN
Solar/Wind Harmer
2.991
964871AG1-351 GEN
Solar/Wind Harmer
2.065
970605AG2-385 GEN
Solar/Wind Harmer
6.332
270485AE1-090_GEN
Solar/Wind Harmer
0.709
270512AE1-227 GEN2
Solar/Wind Harmer
2.455
24721905FLATG4
Adder
23.506
253338AC1-165 GEN
Solar/Wind Harmer
1.256
253333AC1-068 GEN
Solar/Wind Harmer
1.211
970065AG2-057 GEN
Solar/Wind Harmer
1.148
270273AD2-016 GEN
Solar/Wind Harmer
3.061
972173AH1-669 GEN
Solar/Wind Harmer
5.721
270377AD1-106 GEN
Solar/Wind Harmer
6.988
270588AE1-091_GEN
Solar/Wind Harmer
12.311
270291AC1-194 GEN
Solar/Wind Harmer
11.854
253415AE1-040 GEN
Solar/Wind Harmer
1.258
961961AG1-039 GEN
Solar/Wind Harmer
3.188
270491AE1-102 GEN2
Solar/Wind Harmer
1.443
970217AG2-149 GEN
Solar/Wind Harmer
35.355
958091AF2-103 GEN
Solar/Wind Harmer
0.178
253303V4-073 C
Solar/Wind Harmer
0.128
253370AE2-315 SEC1
Adder
2.206
253371AE2-315 SEC2
Adder
2.086
270191TR4_S_V150
Solar/Wind Harmer
3.3
270247TR4_N_V136
Solar/Wind Harmer
0.936
959331AF2-224 GEN
Solar/Wind Harmer
10.972
965021AG1-366 GEN
Solar/Wind Harmer
2.552
270258AD1-119 GEN
Solar/Wind Harmer
3.051
253406AD2-031_GEN
Solar/Wind Harmer
1.398
270044AE2-322 C
Solar/Wind Harmer
1.435
270404AC1-167 GEN
Solar/Wind Harmer
1.194
957541AF2-048 GEN
Solar/Wind Harmer
1.725
270043AE2-236 GEN
Solar/Wind Harmer
5.98
944531AF1-118 GEN
Solar/Wind Harmer
37.943
253316AC1-085 GEN3
Solar/Wind Harmer
9.07
253433AC1-085 GEN1
Solar/Wind Harmer
5.758
946181AF1-283 GEN
Solar/Wind Harmer
14.077
970031AG2-029 GEN
Solar/Wind Harmer
32.394
971617AH1-308 GEN
Solar/Wind Harmer
6.274
270541AE2-072 C
Solar/Wind Harmer
4.881
971191AH1-055 GEN
Solar/Wind Harmer
23.635
962031AG1-047 GEN
Solar/Wind Harmer
3.246
957741AF2-068 GEN
Solar/Wind Harmer
16.111
25196608WSDLE5
Adder
9.143
24642205MAYFLWER
Adder
0.678
25194608D.CRK4
Adder
1.752
247604X1-042
Adder
0.444
23906502RICHG2&3
Adder
1.272
25196008MFTGT1
Adder
1.413
274752CRETE EC ;2U
Adder
8.598
274753CRETE EC ;3U
Adder
8.598
274724RIVER EC ;11
Adder
18.459
274772LINCOLN ;3U
Adder
8.792
274802UNIV PARK;5U
Adder
6.05
274826FISK ;BP
Adder
11.355
274800UNIV PARK;3U
Adder
6.045
972038AH1-567 GEN2
Adder
0.378
972228AH1-698 GEN2
Adder
3.84
274676JOLIET 29;8U
Adder
30.573
274729ELWOOD EC;1P
Adder
16.983
274730ELWOOD EC;6P
Adder
16.983
964991AG1-363 GEN
Solar/Wind Helper
5.557
316097T157 G90
Solar/Wind Helper
1.705
23750701CROSSCHOOL
Solar/Wind Helper
1.586
238148AE2-230_GEN2
Solar/Wind Helper
0.555
238127S14_GEN_2
Solar/Wind Helper
0.867
238118U2-030_1
Solar/Wind Helper
0.356
237080AD1-060 GEN
Solar/Wind Helper
0.367
237038AE2-054 C
Solar/Wind Helper
0.292
235062AE1-101 C1
Solar/Wind Helper
1.776
23779801AA1-109
Solar/Wind Helper
0.207
316006AB2-029 C
Solar/Wind Helper
0.13
223401AF1-299 GEN
Solar/Wind Helper
0.387
316045AC1-158 PL2
Solar/Wind Helper
4.618
316254AC1-120 GEN1
Solar/Wind Helper
1.184
237048AF1-022 C
Solar/Wind Helper
0.173
966131AG1-482 GEN
Solar/Wind Helper
0.079
233930AB2-032 GEN
Solar/Wind Helper
0.387
233915AB1-141 GEN
Solar/Wind Helper
0.511
232422X3-066 FULL
Solar/Wind Helper
0.116
233964AF2-378 GEN
Solar/Wind Helper
0.042
232426Y1-080 FULL
Solar/Wind Helper
0.039
233998TM1NIN_3.36
Solar/Wind Helper
0.266
232404W1-003 C
Solar/Wind Helper
0.516
232428Y3-058 C
Solar/Wind Helper
0.344
3147666LOUISA
Solar/Wind Helper
0.958
232434Z2-077 GEN
Solar/Wind Helper
0.129
233954AC2-188 GEN
Solar/Wind Helper
0.236
233950AC2-186 GEN
Solar/Wind Helper
0.118
233972AC1-094 C
Solar/Wind Helper
0.307
316192AB2-158 GEN
Solar/Wind Helper
1.608
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.232
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.061
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.132
20720728JCB_W1-129
Solar/Wind Helper
0.057
207445AB1-138_GEN
Solar/Wind Helper
0.105
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.078
207454AA2-184 E
Solar/Wind Helper
0.311
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.497
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.137
207518AF1-320_GEN
Solar/Wind Helper
1.568
20671928W4-073
Solar/Wind Helper
0.089
20675828AU_W4-064
Solar/Wind Helper
0.029
270119AB2-067 GEN1
50/50
7.033
270120AB2-067 GEN2
50/50
7.033
24318905MLG2
50/50
7.475
270471AD2-092_GEN
Solar/Wind Harmer
4.529
946101AF1-275 GEN
Solar/Wind Harmer
1.842
938701AE1-092 GEN
Solar/Wind Harmer
24.483
270224U2-072_GEN2
Solar/Wind Harmer
2.339
270227U2-072_GEN3
Solar/Wind Harmer
2.339
270228U2-072_GEN4
Solar/Wind Harmer
2.339
270231U2-072_GEN5
Solar/Wind Harmer
2.339
942861AE2-305 GEN
Solar/Wind Harmer
9.223
964601AG1-323 GEN
Solar/Wind Harmer
3.753
964601AG1-323 GEN
Solar/Wind Harmer
1.746
972269AH1-719 GEN
Adder
2.7
970077AG2-063 GEN
Solar/Wind Harmer
6.332
972159AH1-661 GEN
Adder
1.166
270518AE2-148 GEN
Solar/Wind Harmer
14.068
971199AH1-059 GEN
Solar/Wind Harmer
4.644
241960AC2-195 GEN
Solar/Wind Harmer
3.219
971201AH1-060 GEN
Solar/Wind Harmer
2.296
253378AE2-206_GEN
Solar/Wind Harmer
4.086
276820AF1-078_GEN
Solar/Wind Harmer
1.815
971231AH1-075 GEN
Solar/Wind Harmer
0.905
25326509SID D
Adder
1.48
25326109MON D
Adder
1.461
246938BC-WTG3
Solar/Wind Harmer
4.418
246937BC-WTG2
Solar/Wind Harmer
4.343
970879AG2-548 GEN
Solar/Wind Harmer
6.827
971073AG2-665 GEN
Solar/Wind Harmer
6.827
971073AG2-665 GEN
Solar/Wind Harmer
4.763
25322209TAIT E
Adder
10.77
25322209TAIT E
Adder
10.528
270007AE1-245 C
Solar/Wind Harmer
6.539
942801AE2-298 GEN
Solar/Wind Harmer
1.667
253370AE2-315 SEC1
Adder
2.206
970611AG2-400 GEN
Solar/Wind Harmer
10.972
253394AE2-221_GEN
Solar/Wind Harmer
4.954
253398AE2-221_GEN2
Solar/Wind Harmer
4.954
253317AC1-085 GEN4
Solar/Wind Harmer
9.07
971677AH1-339 GEN
Solar/Wind Harmer
8.643
942221AE2-234 GEN
Solar/Wind Harmer
0.79
944541AF1-119 GEN
Solar/Wind Harmer
4.511
960971AF2-388 GEN
Solar/Wind Harmer
11.771
247621Y3-024
Adder
0.259
270201AC2-176 GEN
Solar/Wind Harmer
5.522
970883AG2-550 GEN
Solar/Wind Harmer
10.73
970885AG2-551 GEN
Solar/Wind Harmer
2.495
247620Y3-023
Adder
0.494
964611AG1-324 GEN
Solar/Wind Harmer
1.264
964611AG1-324 GEN
Solar/Wind Harmer
0.561
25194408D.CRK1
Adder
8.061
25194508D.CRK3
Adder
1.507
24728805RICHG1
Adder
4.003
24728905RICHG2
Adder
4.003
970935AG2-582 GEN
Adder
239.406
274770LINCOLN ;1U
Adder
8.792
274771LINCOLN ;2U
Adder
8.792
274808UNIV PK N;4U
Adder
5.188
274803UNIV PARK;6U
Adder
6.05
972259AH1-714 GEN
Adder
19.76
238175AF1-290_GEN
Solar/Wind Helper
0.168
238169AE2-226 GEN1
Solar/Wind Helper
0.772
238170AE2-226 GEN2
Solar/Wind Helper
0.772
238120AE2-309 GEN
Solar/Wind Helper
0.552
23585401KL_K28_T16
Solar/Wind Helper
1.529
235020AA1-095 C
Solar/Wind Helper
0.057
23777901MDS_W4-102
Solar/Wind Helper
0.191
237034AC2-136 C
Solar/Wind Helper
0.244
237002AB1-128_GEN
Solar/Wind Helper
0.475
235063AE1-101 C2
Solar/Wind Helper
1.776
237001AB1-127_GEN
Solar/Wind Helper
0.473
23777801MSM_W1-116
Solar/Wind Helper
0.122
237025AB1-124 C
Solar/Wind Helper
0.175
237006AB1-125 GEN
Solar/Wind Helper
0.131
226929AD2-058 GEN
Solar/Wind Helper
0.108
315651AD1-115 GEN
Solar/Wind Helper
0.876
316447AC1-158 HLD
Solar/Wind Helper
3.175
205916AD1-020 GEN
Solar/Wind Helper
1.761
20390526W1-045 C
Solar/Wind Helper
0.36
208835TUHI V3-051
Solar/Wind Helper
0.025
208835TUHI V3-051
Solar/Wind Helper
0.025
3132123MT JACKSON
Solar/Wind Helper
0.764
233987AB2-037 GEN
Solar/Wind Helper
2.381
233933AB2-153 GEN
Solar/Wind Helper
0.236
232424Y1-079 C
Solar/Wind Helper
0.118
233944AB2-135 GEN
Solar/Wind Helper
0.598
233946AB2-136 GEN
Solar/Wind Helper
0.577
234036AF2-325 C
Solar/Wind Helper
0.043
233901CHERRYDALE C
Solar/Wind Helper
0.236
232408W1-005 C
Solar/Wind Helper
0.516
232410W1-006 C
Solar/Wind Helper
0.516
233939AC1-091 C
Solar/Wind Helper
0.356
233970AC1-092 C
Solar/Wind Helper
0.356
966001AG1-469 GEN
Solar/Wind Helper
0.255
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.041
219921AF1-264
Solar/Wind Helper
0.052
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.083
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.168
20674928WA_W3-044
Solar/Wind Helper
0.098
20676228FRD_X1-012
Solar/Wind Helper
0.091
964851AG1-348 GEN
Solar/Wind Helper
0.081
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.044
211065PSPA IPP
Solar/Wind Helper
0.15
211065PSPA IPP
Solar/Wind Helper
0.15
NYPJM->LTFIMP_NY
CLTF
4.554
LGEELTFEXP_LGEE->PJM
CLTF
6.753
WECLTFEXP_WEC->PJM
CLTF
3.866
AG2-052LTFEXP_AG2-052->PJM
LTF
0.243
AH1-155LTFEXP_AH1-155->PJM
LTF
0.364
CBM West 2LTFEXP_CBM-W2->PJM
CBM
111.893
LAGNLTFEXP_LAGN->PJM
CLTF
14.521
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.32
TVALTFEXP_TVA->PJM
CLTF
7.111
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.579
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.544
MECLTFEXP_MEC->PJM
CLTF
15.979
SIGELTFEXP_SIGE->PJM
CLTF
0.506

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-008A_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.1 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4627.6
MW Contribution:21.25
Bus #Bus NameTypeMW Contribution
972239AH1-704 GEN
50/50
2.78
962771AG1-126 GEN
Solar/Wind Harmer
33.269
270459AD2-067 GEN
Solar/Wind Harmer
0
270054AF2-122 C O1
Solar/Wind Harmer
0.007
961821AG1-024 GEN
Solar/Wind Harmer
4.91
270520AE2-214 GEN
Solar/Wind Harmer
0.013
270284AF1-227 GEN1
Solar/Wind Harmer
0.01
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
253383AE2-342_GEN
Solar/Wind Harmer
0.003
241973AD2-163_GEN1
Solar/Wind Harmer
0.006
945631AF1-228 GEN
Solar/Wind Harmer
0
943861AF1-054 GEN
Solar/Wind Harmer
3.02
943851AF1-053 GEN
Solar/Wind Harmer
2.092
270156DARBY CT1
Adder
10.05
270157DARBY CT2
Adder
10.026
270158DARBY CT3
Adder
9.866
270578AF1-285 GEN2
Solar/Wind Harmer
0.518
970689AG2-444 GEN
Solar/Wind Harmer
15.861
270432AC2-029 GEN
Solar/Wind Harmer
3.428
940611AE2-048 GEN
Solar/Wind Harmer
18.967
941391AE2-136 GEN
Solar/Wind Harmer
10.684
270302AB2-170 GEN
Solar/Wind Harmer
0.005
270317AD1-130_GEN
Solar/Wind Harmer
0.011
971653AH1-327 GEN
Solar/Wind Harmer
1.08
270269AC2-059
Solar/Wind Harmer
0.004
241972AD1-140 GEN
Solar/Wind Harmer
0.824
970179AG2-119 GEN
Solar/Wind Harmer
6.658
270340AC2-060 GEN
Solar/Wind Harmer
0.009
970879AG2-548 GEN
Solar/Wind Harmer
6.645
253372AE2-315 SEC3
Adder
1.989
253372AE2-315 SEC3
Adder
1.989
25306009OHH W.
Adder
3.018
253349AC2-067 GEN
Solar/Wind Harmer
2.296
253400AC2-068 GEN
Solar/Wind Harmer
0.923
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.92
965051AG1-369 GEN
Solar/Wind Harmer
3.609
971567AH1-282 GEN
Solar/Wind Harmer
10.843
247607V1-011 GEN
Solar/Wind Harmer
0.001
965041AG1-368 GEN
Solar/Wind Harmer
7.21
971989AH1-539 GEN
Solar/Wind Harmer
3.109
963791AG1-232 GEN
Solar/Wind Harmer
9.689
24729505KEY G4
Adder
6.671
270071AF1-092 GEN
Solar/Wind Harmer
13.737
270024AE2-089 GEN
Solar/Wind Harmer
0.008
971985AH1-537 GEN
Solar/Wind Harmer
2.123
965101AG1-375 GEN
Solar/Wind Harmer
7.135
270297AD1-101 GEN
Solar/Wind Harmer
0.002
270367AC2-061_GEN
Solar/Wind Harmer
0.006
971673AH1-337 GEN
Solar/Wind Harmer
4.631
971029AG2-637 GEN
Solar/Wind Harmer
10.686
270543AE2-219 C
Solar/Wind Harmer
0.004
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
9.002
25196308WSDLE2
Adder
8.924
25196208WSDLE1
Adder
8.902
25196708WSDLE6
Adder
8.879
25196508WSDLE4
Adder
8.656
945581AF1-223 GEN
Solar/Wind Harmer
0.001
971347AH1-153 GEN
Solar/Wind Harmer
10.632
971609AH1-304 GEN
Solar/Wind Harmer
1.157
270240V3-007_GEN2
Solar/Wind Harmer
0.002
970115AG2-085 GEN
Solar/Wind Harmer
2.826
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
7.898
971771AH1-392 GEN
Solar/Wind Harmer
7.046
970289AG2-191 GEN
Solar/Wind Harmer
1.339
971619AH1-309 GEN
Solar/Wind Harmer
3.169
971769AH1-391 GEN
Solar/Wind Harmer
7.844
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
25196108MFTGT2
Adder
1.54
25196108MFTGT2
Adder
1.43
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
4.146
971549AH1-272 GEN
Solar/Wind Harmer
14.344
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.364
274776LINCOLN ;7U
Adder
8.364
274777LINCOLN ;8U
Adder
8.364
274814UNIV PK N;0U
Adder
4.998
274807UNIV PK N;3U
Adder
4.987
274805UNIV PK N;1U
Adder
4.965
274811UNIV PK N;7U
Adder
4.954
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
972037AH1-567 GEN1
Adder
0.181
960591AF2-350 GEN
Solar/Wind Harmer
6.884
274827FISK ;RP
Adder
7.655
972227AH1-698 GEN1
Adder
2.573
963841AG1-237 GEN
Solar/Wind Harmer
2.978
274687WILL CNTY;4U
Adder
27.495
274687WILL CNTY;4U
Adder
27.495
274675JOLIET 29;7U
Adder
30.175
274675JOLIET 29;7U
Adder
29.097
972163AH1-664 GEN
Solar/Wind Harmer
7.639
972165AH1-665 GEN
Solar/Wind Harmer
6.118
274731ELWOOD EC;2P
Adder
16.163
274733ELWOOD EC;3P
Adder
16.163
274735ELWOOD EC;4P
Adder
16.163
274728ELWOOD EC;5P
Adder
16.163
970833AG2-524 GEN
Solar/Wind Harmer
7.542
970833AG2-524 GEN
Solar/Wind Harmer
5.028
945641AF1-229 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
276868AE1-113 GEN
Solar/Wind Harmer
1.363
276882AE2-255 GEN
Solar/Wind Harmer
0.794
238109AE1-109 GEN2
Solar/Wind Helper
0.106
238110AE1-109 GEN3
Solar/Wind Helper
0.106
238152AF2-075_GEN
Solar/Wind Helper
0.683
23546401DTGZ2-030
Solar/Wind Helper
0.086
238208AF1-136 C
Solar/Wind Helper
0.211
238126S14_GEN_1
Solar/Wind Helper
0.766
237085AD2-009_GEN
Solar/Wind Helper
1.588
3138216PACIFIC
Solar/Wind Helper
0.043
316411AF1-147_GEN1
Solar/Wind Helper
0.86
316415AF1-147_GEN2
Solar/Wind Helper
0.86
959381AF2-229 GEN
Solar/Wind Helper
0.345
23750501ELLIOTTS
Solar/Wind Helper
0.571
3141426STAFORD
Solar/Wind Helper
0.051
960921AF2-383 GEN
Solar/Wind Helper
0.352
205943AE1-185 GEN
Solar/Wind Helper
0.492
205956AE1-196_GEN
Solar/Wind Helper
0.492
205932AD2-116_GEN
Solar/Wind Helper
0.492
233935AB2-179 C
Solar/Wind Helper
1.227
232436AB1-176 C
Solar/Wind Helper
0.043
233923SMA
Solar/Wind Helper
0.927
233990AG1-397 GEN
Solar/Wind Helper
0.261
234033AF1-007_GEN
Solar/Wind Helper
6.787
232432Z2-076 GEN
Solar/Wind Helper
0.065
964001AG1-254 GEN
Solar/Wind Helper
0.924
228754AB1-001 C
Solar/Wind Helper
0.025
227927V4-067C
Solar/Wind Helper
0.01
219914AD2-027 C
Solar/Wind Helper
0.111
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.038
219607WPEMNERT C
Solar/Wind Helper
0.077
214067T20SOLAR
Solar/Wind Helper
0.011
203975AE1-071-GEN
Solar/Wind Helper
2.41
20715728PEM_W1-119
Solar/Wind Helper
0.093
20715828PEM_W1-120
Solar/Wind Helper
0.093
207459AE1-142 C O1
Solar/Wind Helper
0.28
316164AC1-076 GEN
Solar/Wind Helper
1.062
219620RIDERU C
Solar/Wind Helper
0.001
270166AC1-044 GEN3
50/50
6.869
23559101PLEAS2
50/50
5.385
270122AB2-093 CT
50/50
3.689
962761AG1-125 GEN
Solar/Wind Harmer
33.269
970149AG2-104 GEN
Solar/Wind Harmer
35.932
970155AG2-107 GEN
Solar/Wind Harmer
21.245
270349AD2-093_GEN
Solar/Wind Harmer
0.006
24721705FLATG2
Adder
22.865
270159DARBY CT4
Adder
9.89
970593AG2-378 GEN
Solar/Wind Harmer
1.75
270223U2-072_GEN1
Solar/Wind Harmer
0.001
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.012
270462AD2-086
Solar/Wind Harmer
0.016
971995AH1-542 GEN
Solar/Wind Harmer
2.81
270263AC1-001 GEN
Solar/Wind Harmer
0.758
270510AE1-227 GEN1
Solar/Wind Harmer
1.904
241813AF1-122_GEN
Solar/Wind Harmer
3.294
25326309TAIT D
Adder
1.153
960071AF2-298 GEN
Solar/Wind Harmer
3.651
253370AE2-315 SEC1
Adder
2.103
253371AE2-315 SEC2
Adder
1.989
927014AC1-188 GEN
Solar/Wind Harmer
0.004
246936BC-WTG1
Solar/Wind Harmer
0.295
270489AE1-102 GEN1
Solar/Wind Harmer
0.945
965421AG1-410 GEN
Solar/Wind Harmer
21.788
247521TR3_G114
Solar/Wind Harmer
0.263
270246TR4_N_V150
Solar/Wind Harmer
0.047
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.226
965011AG1-365 GEN
Solar/Wind Harmer
7.225
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
2.096
958861AF2-177 GEN
Solar/Wind Harmer
3.092
247536S-71 GEN
Solar/Wind Harmer
0.287
945371AF1-202 GEN
Solar/Wind Harmer
0.001
25194608D.CRK4
Adder
1.676
270063AE2-323 C
Solar/Wind Harmer
0.006
252507AC2-088 GEN
Solar/Wind Harmer
0.323
970245AG2-165 GEN
Solar/Wind Harmer
3.076
944231AF1-091 GEN
Solar/Wind Harmer
1.885
270005AE1-210 C O1
Solar/Wind Harmer
1.532
965031AG1-367 GEN
Solar/Wind Harmer
7.073
970947AG2-589 GEN
Solar/Wind Harmer
0.236
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.183
970825AG2-519 GEN
Solar/Wind Harmer
2.509
24639705ELKHART HY
Adder
0.155
25196808ZIMRHP
Adder
76.799
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
270032AE2-172
Solar/Wind Harmer
4.701
970291AG2-192 GEN
Solar/Wind Harmer
0.916
945111AF1-176 GEN
Solar/Wind Harmer
12.568
270505AE1-170 C O1
Solar/Wind Harmer
7.393
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.67
247522W1-056 GEN
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
7.842
25196008MFTGT1
Adder
1.397
970773AG2-487 GEN
Solar/Wind Harmer
1.237
970373AG2-245 GEN
Solar/Wind Harmer
14.699
970515AG2-329 GEN
Solar/Wind Harmer
18.197
270055AF2-134 C O1
Solar/Wind Harmer
0.005
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.071
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.706
24791305MDL-5G
Solar/Wind Harmer
0.001
970333AG2-219 GEN
Solar/Wind Harmer
4.947
274751CRETE EC ;1U
Adder
8.172
274754CRETE EC ;4U
Adder
8.172
274773LINCOLN ;4U
Adder
8.364
274774LINCOLN ;5U
Adder
8.364
274723RIVER EC ;12
Adder
17.756
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.954
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
276776AD2-060 GEN
Solar/Wind Harmer
0.719
24728605AND G2
Adder
3.784
274801UNIV PARK;4U
Adder
5.751
941551AE2-152 GEN
Solar/Wind Harmer
0.001
945681AF1-233 GEN
Solar/Wind Harmer
12.962
274676JOLIET 29;8U
Adder
30.175
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
16.202
939401AE1-172 GEN
Solar/Wind Harmer
5.109
276691AA1-018 GEN1
Solar/Wind Harmer
0.827
276901AD2-066 C O1
Solar/Wind Harmer
0.007
316095T157 G97
Solar/Wind Helper
1.455
23583801GRNGAP
Solar/Wind Helper
5.418
238108AE1-109 GEN1
Solar/Wind Helper
0.106
238185AF2-356 C
Solar/Wind Helper
2.425
238147AE2-230_GEN1
Solar/Wind Helper
0.478
238149AF1-291A_GEN
Solar/Wind Helper
0.137
235531U2-073 GEN
Solar/Wind Helper
3.034
235054AD2-180 GEN
Solar/Wind Helper
1.839
237061AD1-155 GEN
Solar/Wind Helper
0.051
238117U2-030
Solar/Wind Helper
0.314
238221AF1-254 C O1
Solar/Wind Helper
0.265
235067AD1-061 GEN
Solar/Wind Helper
0.478
237030AB1-096 C
Solar/Wind Helper
0.068
3141196NOKESVL
Solar/Wind Helper
0.999
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.335
223402AF1-300 C
Solar/Wind Helper
0.355
23751201ROTHROCK
Solar/Wind Helper
0.694
23562501BACKB
Solar/Wind Helper
0.842
205917AD1-020 ES
Solar/Wind Helper
0.356
233982AB2-133 GEN
Solar/Wind Helper
0.346
233918AB1-142 GEN
Solar/Wind Helper
0.486
233994AC2-023 GEN
Solar/Wind Helper
0.929
233996TM1833_GEN
Solar/Wind Helper
0.253
233997TMININ_4.2
Solar/Wind Helper
0.253
232406W1-004 FULL
Solar/Wind Helper
0.49
233940AF2-379 C
Solar/Wind Helper
0.06
234015AF2-250 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.225
233971AC1-093 C
Solar/Wind Helper
0.346
316044AC1-158 PL1
Solar/Wind Helper
1.252
316450AC1-158 RIC
Solar/Wind Helper
0.334
230430AE1-229_GEN
Solar/Wind Helper
3.26
230415AB2-049 C
Solar/Wind Helper
0.029
228729W2-030 C
Solar/Wind Helper
0.107
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.053
219912AD2-042 GEN
Solar/Wind Helper
0.145
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.111
316170AC1-121 GEN2
Solar/Wind Helper
0.342
959561AF2-247 GEN
Solar/Wind Helper
0.02
20720828JCB_W4-025
Solar/Wind Helper
0.061
20716028EGP_W2-019
Solar/Wind Helper
0.018
20715028HAN_X4-015
Solar/Wind Helper
0.055
219276PARKLANDSO C
Solar/Wind Helper
0.086
20714528FRN_Y2-051
Solar/Wind Helper
0.055
20720528MAN_W1-024
Solar/Wind Helper
0.027
971997AH1-543 GEN
Solar/Wind Harmer
1.86
24318805MLG1
50/50
9.842
23559001PLEAS1
50/50
5.385
270051AF1-062 GEN
50/50
11.434
970153AG2-106 GEN
Solar/Wind Harmer
21.245
961921AG1-034 GEN
Solar/Wind Harmer
7.364
241955AC1-078 GEN
Solar/Wind Harmer
0.007
241974AD2-163_GEN2
Solar/Wind Harmer
0.006
942051AE2-217 GEN
Solar/Wind Harmer
14.169
24721905FLATG4
Adder
22.865
970605AG2-385 GEN
Solar/Wind Harmer
4.731
270391AF1-285 GEN3
Solar/Wind Harmer
0.518
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.012
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270273AD2-016 GEN
Solar/Wind Harmer
0.792
972173AH1-669 GEN
Solar/Wind Harmer
3.811
270512AE1-227 GEN2
Solar/Wind Harmer
1.904
270291AC1-194 GEN
Solar/Wind Harmer
5.884
253415AE1-040 GEN
Solar/Wind Harmer
0.003
270119AB2-067 GEN1
50/50
6.869
270120AB2-067 GEN2
50/50
6.869
24318905MLG2
50/50
6.89
270471AD2-092_GEN
Solar/Wind Harmer
0.006
942861AE2-305 GEN
Solar/Wind Harmer
6.118
970077AG2-063 GEN
Solar/Wind Harmer
4.471
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
12.484
971655AH1-328 GEN
Solar/Wind Harmer
2.758
964601AG1-323 GEN
Solar/Wind Harmer
3.106
964601AG1-323 GEN
Solar/Wind Harmer
2.071
270518AE2-148 GEN
Solar/Wind Harmer
0.667
972269AH1-719 GEN
Adder
2.501
972159AH1-661 GEN
Adder
1.082
253378AE2-206_GEN
Solar/Wind Harmer
0.004
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
3.237
971199AH1-059 GEN
Solar/Wind Harmer
2.99
241960AC2-195 GEN
Solar/Wind Harmer
0.006
970935AG2-582 GEN
Adder
242.403
25326509SID D
Adder
1.4
971073AG2-665 GEN
Solar/Wind Harmer
6.645
25326109MON D
Adder
1.391
971201AH1-060 GEN
Solar/Wind Harmer
1.471
25322209TAIT E
Adder
10.262
25322209TAIT E
Adder
10.031
253370AE2-315 SEC1
Adder
2.103
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
246938BC-WTG3
Solar/Wind Harmer
0.263
246937BC-WTG2
Solar/Wind Harmer
0.295
971231AH1-075 GEN
Solar/Wind Harmer
0.833
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
970611AG2-400 GEN
Solar/Wind Harmer
7.225
970627AG2-408 GEN
Solar/Wind Harmer
2.167
270007AE1-245 C
Solar/Wind Harmer
0.002
970623AG2-406 GEN
Solar/Wind Harmer
1.309
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25183208HLCRTG
Solar/Wind Harmer
0.011
944541AF1-119 GEN
Solar/Wind Harmer
0.479
960971AF2-388 GEN
Solar/Wind Harmer
4.192
942221AE2-234 GEN
Solar/Wind Harmer
0.036
252519AF1-045_GEN
Solar/Wind Harmer
6.204
252516AE2-318_GEN
Solar/Wind Harmer
5.503
970621AG2-405 GEN
Solar/Wind Harmer
1.305
247621Y3-024
Adder
0.246
970883AG2-550 GEN
Solar/Wind Harmer
7.123
970885AG2-551 GEN
Solar/Wind Harmer
2.374
270201AC2-176 GEN
Solar/Wind Harmer
0.001
25194408D.CRK1
Adder
7.711
25194508D.CRK3
Adder
1.442
964611AG1-324 GEN
Solar/Wind Harmer
0.534
252509AD1-136 GEN
Solar/Wind Harmer
0.036
970321AG2-212 GEN
Solar/Wind Harmer
3.076
270599AE1-208 GEN
Solar/Wind Harmer
6.495
270031AE2-169
Solar/Wind Harmer
3.897
270383AD1-128 GEN
Solar/Wind Harmer
0.004
270186AC1-089 GEN
Solar/Wind Harmer
0.004
247620Y3-023
Adder
0.466
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
7.834
960441AF2-335 GEN
Solar/Wind Harmer
7.065
270216AD2-079_GEN
Solar/Wind Harmer
0.001
971613AH1-306 GEN
Solar/Wind Harmer
3.385
24728805RICHG1
Adder
3.82
24728905RICHG2
Adder
3.82
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
14.072
961051AF2-396 GEN
Solar/Wind Harmer
9.381
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
8.77
965791AG1-447 GEN
Solar/Wind Harmer
6.431
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.73
274770LINCOLN ;1U
Adder
8.364
274771LINCOLN ;2U
Adder
8.364
274808UNIV PK N;4U
Adder
4.933
966841AG1-555 GEN
Solar/Wind Harmer
0.781
274803UNIV PARK;6U
Adder
5.755
274888KELLY CRK;1U
Solar/Wind Harmer
0.404
274887GEN-1.85
Solar/Wind Harmer
0.181
276843GEN-1.7
Solar/Wind Harmer
0.223
958011AF2-095 GEN
Solar/Wind Harmer
9.913
972259AH1-714 GEN
Adder
18.805
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
3.993
958481AF2-142 GEN
Solar/Wind Harmer
10.238
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.923
971573AH1-285 GEN
Solar/Wind Harmer
1.271
971677AH1-339 GEN
Solar/Wind Harmer
0.768
958491AF2-143 GEN
Solar/Wind Harmer
10.205
274879MINONK ;1U
Solar/Wind Harmer
0.287
238175AF1-290_GEN
Solar/Wind Helper
0.148
238169AE2-226 GEN1
Solar/Wind Helper
0.677
238170AE2-226 GEN2
Solar/Wind Helper
0.677
970065AG2-057 GEN
Solar/Wind Harmer
0.735
253370AE2-315 SEC1
Adder
2.103
253371AE2-315 SEC2
Adder
1.989
970191AG2-125 GEN
Solar/Wind Harmer
1.876
253406AD2-031_GEN
Solar/Wind Harmer
0.543
270491AE1-102 GEN2
Solar/Wind Harmer
0.945
270377AD1-106 GEN
Solar/Wind Harmer
2.761
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.047
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.394
959331AF2-224 GEN
Solar/Wind Harmer
5.057
965021AG1-366 GEN
Solar/Wind Harmer
2.408
270588AE1-091_GEN
Solar/Wind Harmer
5.649
971191AH1-055 GEN
Solar/Wind Harmer
18.515
944531AF1-118 GEN
Solar/Wind Harmer
32.203
270043AE2-236 GEN
Solar/Wind Harmer
4.607
270258AD1-119 GEN
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
5.953
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
10.684
270404AC1-167 GEN
Solar/Wind Harmer
0.003
25196608WSDLE5
Adder
8.745
252510AF1-249 C
Solar/Wind Harmer
0.055
970031AG2-029 GEN
Solar/Wind Harmer
4.625
25194608D.CRK4
Adder
1.676
270222AC2-111 GEN
Solar/Wind Harmer
3.603
970513AG2-328 GEN
Solar/Wind Harmer
3.076
970517AG2-330 GEN
Solar/Wind Harmer
18.457
970349AG2-230 GEN
Solar/Wind Harmer
10.632
946031AF1-268 GEN
Solar/Wind Harmer
6.74
958821AF2-173 GEN
Solar/Wind Harmer
9.902
270004AE1-209 GEN
Solar/Wind Harmer
1.532
270437AC2-090 C
Solar/Wind Harmer
0.003
247643Z2-116 C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.775
970291AG2-192 GEN
Solar/Wind Harmer
0.705
945111AF1-176 GEN
Solar/Wind Harmer
5.709
247642Z2-115 C
Solar/Wind Harmer
0.003
24642205MAYFLWER
Adder
0.641
24441205WTRV SLR C
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.353
270356AE2-297 GEN
Solar/Wind Harmer
0.009
970217AG2-149 GEN
Solar/Wind Harmer
6.066
247604X1-042
Adder
0.418
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
964401AG1-302 GEN
Solar/Wind Harmer
0.001
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.935
970243AG2-164 GEN
Solar/Wind Harmer
4.047
970519AG2-331 GEN
Solar/Wind Harmer
17.988
970699AG2-449 GEN
Solar/Wind Harmer
1.73
274752CRETE EC ;2U
Adder
8.172
274753CRETE EC ;3U
Adder
8.172
274772LINCOLN ;3U
Adder
8.364
274724RIVER EC ;11
Adder
17.549
958171AF2-111 GEN
Solar/Wind Harmer
17.278
274802UNIV PARK;5U
Adder
5.755
276806AD2-047 C O1
Solar/Wind Harmer
3.901
970941AG2-585 GEN
Solar/Wind Harmer
8.605
274826FISK ;BP
Adder
10.802
24728705AND G3
Adder
7.914
24728505AND G1
Adder
3.784
274800UNIV PARK;3U
Adder
5.751
972038AH1-567 GEN2
Adder
0.36
972228AH1-698 GEN2
Adder
3.654
972167AH1-666 GEN
Solar/Wind Harmer
5.505
276897AD1-100 C
Solar/Wind Harmer
0.009
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
22.464
274676JOLIET 29;8U
Adder
29.097
274729ELWOOD EC;1P
Adder
16.163
274730ELWOOD EC;6P
Adder
13.491
276893AG1-478 C
Solar/Wind Harmer
0.272
270541AE2-072 C
Solar/Wind Harmer
0.009
943121AE2-341 GEN
Solar/Wind Harmer
11.459
943591AF1-030 GEN
Solar/Wind Harmer
7.62
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
276805AD2-038 GEN
Solar/Wind Harmer
0.002
964991AG1-363 GEN
Solar/Wind Helper
4.969
316097T157 G90
Solar/Wind Helper
1.455
23750701CROSSCHOOL
Solar/Wind Helper
1.397
238148AE2-230_GEN2
Solar/Wind Helper
0.48
238127S14_GEN_2
Solar/Wind Helper
0.766
238118U2-030_1
Solar/Wind Helper
0.314
237080AD1-060 GEN
Solar/Wind Helper
0.33
237038AE2-054 C
Solar/Wind Helper
0.262
235062AE1-101 C1
Solar/Wind Helper
1.6
23779801AA1-109
Solar/Wind Helper
0.187
223401AF1-299 GEN
Solar/Wind Helper
0.355
316006AB2-029 C
Solar/Wind Helper
0.113
966131AG1-482 GEN
Solar/Wind Helper
0.132
237048AF1-022 C
Solar/Wind Helper
0.159
233930AB2-032 GEN
Solar/Wind Helper
0.368
233915AB1-141 GEN
Solar/Wind Helper
0.486
232422X3-066 FULL
Solar/Wind Helper
0.11
232426Y1-080 FULL
Solar/Wind Helper
0.038
233964AF2-378 GEN
Solar/Wind Helper
0.04
233998TM1NIN_3.36
Solar/Wind Helper
0.253
232404W1-003 C
Solar/Wind Helper
0.49
232428Y3-058 C
Solar/Wind Helper
0.327
232434Z2-077 GEN
Solar/Wind Helper
0.123
233954AC2-188 GEN
Solar/Wind Helper
0.225
233950AC2-186 GEN
Solar/Wind Helper
0.112
238120AE2-309 GEN
Solar/Wind Helper
0.487
235020AA1-095 C
Solar/Wind Helper
0.051
23777901MDS_W4-102
Solar/Wind Helper
0.171
23585401KL_K28_T16
Solar/Wind Helper
1.328
237034AC2-136 C
Solar/Wind Helper
0.219
237002AB1-128_GEN
Solar/Wind Helper
0.427
235063AE1-101 C2
Solar/Wind Helper
1.6
237001AB1-127_GEN
Solar/Wind Helper
0.426
23777801MSM_W1-116
Solar/Wind Helper
0.11
237025AB1-124 C
Solar/Wind Helper
0.159
237006AB1-125 GEN
Solar/Wind Helper
0.119
226929AD2-058 GEN
Solar/Wind Helper
0.096
205916AD1-020 GEN
Solar/Wind Helper
1.656
20390526W1-045 C
Solar/Wind Helper
0.338
208835TUHI V3-051
Solar/Wind Helper
0.023
208835TUHI V3-051
Solar/Wind Helper
0.023
233987AB2-037 GEN
Solar/Wind Helper
2.264
233933AB2-153 GEN
Solar/Wind Helper
0.225
232424Y1-079 C
Solar/Wind Helper
0.112
233944AB2-135 GEN
Solar/Wind Helper
0.569
233946AB2-136 GEN
Solar/Wind Helper
0.549
234036AF2-325 C
Solar/Wind Helper
0.041
233901CHERRYDALE C
Solar/Wind Helper
0.225
232408W1-005 C
Solar/Wind Helper
0.49
232410W1-006 C
Solar/Wind Helper
0.49
233939AC1-091 C
Solar/Wind Helper
0.338
233970AC1-092 C
Solar/Wind Helper
0.338
315651AD1-115 GEN
Solar/Wind Helper
0.76
316447AC1-158 HLD
Solar/Wind Helper
2.756
230433AD2-135 GEN
Solar/Wind Helper
0.016
230407AD2-065 C
Solar/Wind Helper
0.039
219921AF1-264
Solar/Wind Helper
0.049
219615MILLCREEK C
Solar/Wind Helper
0.026
963401AG1-189 GEN
Solar/Wind Helper
0.054
963391AG1-188 GEN
Solar/Wind Helper
0.079
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.183
233972AC1-094 C
Solar/Wind Helper
0.292
316045AC1-158 PL2
Solar/Wind Helper
4.009
230511AF1-262
Solar/Wind Helper
0.014
230434AG1-499 GEN
Solar/Wind Helper
0.222
228728W1-130C
Solar/Wind Helper
0.052
219258KINSLEYDEP C
Solar/Wind Helper
0.074
219904AC1-010 C
Solar/Wind Helper
0.058
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219907AC1-030 C
Solar/Wind Helper
0.033
219686LUMSOLAR_N C
Solar/Wind Helper
0.038
219304NAMERICA C
Solar/Wind Helper
0.127
316254AC1-120 GEN1
Solar/Wind Helper
1.026
20720728JCB_W1-129
Solar/Wind Helper
0.055
207445AB1-138_GEN
Solar/Wind Helper
0.101
963711AG1-223 GEN
Solar/Wind Helper
0.062
20714828MDF_W3-079
Solar/Wind Helper
0.126
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.299
20715228NPK_W1-113
Solar/Wind Helper
0.075
NYPJM->LTFIMP_NY
CLTF
4.628
LGEELTFEXP_LGEE->PJM
CLTF
6.497
WECLTFEXP_WEC->PJM
CLTF
3.686
AG2-052LTFEXP_AG2-052->PJM
LTF
0.231
AH1-155LTFEXP_AH1-155->PJM
LTF
0.346
CPLELTFEXP_CPLE->PJM
CLTF
0.567
CBM West 2LTFEXP_CBM-W2->PJM
CBM
108.576
LAGNLTFEXP_LAGN->PJM
CLTF
14.268
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.432
TVALTFEXP_TVA->PJM
CLTF
7.011
CBM West 1LTFEXP_CBM-W1->PJM
CBM
137.982
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.984
MECLTFEXP_MEC->PJM
CLTF
15.319
SIGELTFEXP_SIGE->PJM
CLTF
0.486

Details for 05FLTLCK-05GAVIN_RF 765.0 kV Ckt 1 line l/o AEP_P4_#8075_05MARYSV 765_A2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05FLTLCK-05GAVIN_RF 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8075_05MARYSV 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.34 %
Rating:4349.0 MVA
Rating Type:B
MVA to Mitigate:4494.08
MW Contribution:75.97
Bus #Bus NameTypeMW Contribution
24721805FLATG3
50/50
8.432
24721705FLATG2
50/50
154.591
24344105CKG2
50/50
11.53
270143AC1-141 CT2_
50/50
3.334
24639705ELKHART HY
50/50
0.224
970521AG2-332 GEN
50/50
15.95
24307105BERRINSP G
50/50
0.03
962761AG1-125 GEN
Solar/Wind Harmer
174.214
970149AG2-104 GEN
Solar/Wind Harmer
215.155
970155AG2-107 GEN
Solar/Wind Harmer
75.966
970245AG2-165 GEN
Solar/Wind Harmer
25.325
270505AE1-170 C O1
Solar/Wind Harmer
20.687
945111AF1-176 GEN
Solar/Wind Harmer
24.498
270063AE2-323 C
Solar/Wind Harmer
3.019
270449AD2-020 GEN
Solar/Wind Harmer
3.83
943021AE2-325 GEN
Solar/Wind Harmer
4.976
965011AG1-365 GEN
Solar/Wind Harmer
13.218
972207SS24-0001
Solar/Wind Harmer
29.024
274773LINCOLN ;4U
Adder
8.163
274774LINCOLN ;5U
Adder
8.163
274723RIVER EC ;12
Adder
23.321
274751CRETE EC ;1U
Adder
6.353
274754CRETE EC ;4U
Adder
6.353
276164X3-005 C
Solar/Wind Harmer
0.91
970373AG2-245 GEN
Solar/Wind Harmer
27.1
274812UNIV PK N;8U
Adder
6.463
276776AD2-060 GEN
Solar/Wind Harmer
0.541
274801UNIV PARK;4U
Adder
7.462
941551AE2-152 GEN
Solar/Wind Harmer
5.768
274676JOLIET 29;8U
Adder
38.881
274674JOLIET 9 ;6U
Adder
19.473
274732ELWOOD EC;7P
Adder
20.768
274871GR RIDGE ;2U
Solar/Wind Harmer
9.692
270055AF2-134 C O1
Solar/Wind Harmer
3.807
274745AC1-111 GEN9
Adder
6.996
276691AA1-018 GEN1
Solar/Wind Harmer
0.574
274682WAUKEGAN ;7U
Adder
22.136
274828WAUKEGAN ;BP
Adder
13.584
958381AF2-132 GEN
Solar/Wind Harmer
11.14
964861AG1-349 GEN
Solar/Wind Harmer
9.628
971917AH1-482 GEN
Solar/Wind Harmer
11.111
960751AF2-366 GEN
Solar/Wind Harmer
3.499
962781AG1-127 GEN
Solar/Wind Harmer
11.598
939401AE1-172 GEN
Solar/Wind Harmer
16.958
274872LEEDK;1U
Solar/Wind Harmer
9.989
965651AG1-433 GEN
Solar/Wind Harmer
6.647
276901AD2-066 C O1
Solar/Wind Harmer
4.262
971997AH1-543 GEN
Solar/Wind Harmer
18.988
276861AD2-134 GEN
Solar/Wind Harmer
2.146
274822ROCKFORD ;11
Adder
23.305
972235AH1-702 GEN1
Adder
2.984
274761LEE CO EC;2U
Adder
10.813
274766LEE CO EC;7U
Adder
10.686
24721605FLATG1
50/50
8.432
971599AH1-298 GEN
50/50
13.812
270144AC1-141 ST1_
50/50
2.953
24653605MOTTVILLE
50/50
0.005
24643105BUCHANAN
50/50
0.018
962771AG1-126 GEN
Solar/Wind Harmer
174.214
971347AH1-153 GEN
Solar/Wind Harmer
22.036
270071AF1-092 GEN
Solar/Wind Harmer
20.801
971771AH1-392 GEN
Solar/Wind Harmer
12.478
971769AH1-391 GEN
Solar/Wind Harmer
13.692
960681AF2-359 GEN
Solar/Wind Harmer
5.157
944161AF1-084 GEN
Solar/Wind Harmer
3.004
274775LINCOLN ;6U
Adder
8.163
274776LINCOLN ;7U
Adder
8.163
274777LINCOLN ;8U
Adder
8.163
24729505KEY G4
Adder
8.488
274814UNIV PK N;0U
Adder
6.519
274807UNIV PK N;3U
Adder
6.505
274805UNIV PK N;1U
Adder
6.477
274811UNIV PK N;7U
Adder
6.463
972037AH1-567 GEN1
Adder
0.235
274827FISK ;RP
Adder
9.944
960591AF2-350 GEN
Solar/Wind Harmer
12.8
972227AH1-698 GEN1
Adder
3.335
274687WILL CNTY;4U
Adder
35.465
274687WILL CNTY;4U
Adder
35.465
274675JOLIET 29;7U
Adder
38.882
274675JOLIET 29;7U
Adder
37.493
971549AH1-272 GEN
Solar/Wind Harmer
23.441
274731ELWOOD EC;2P
Adder
20.768
274733ELWOOD EC;3P
Adder
20.768
274735ELWOOD EC;4P
Adder
20.768
274728ELWOOD EC;5P
Adder
20.768
970833AG2-524 GEN
Solar/Wind Harmer
11.011
970833AG2-524 GEN
Solar/Wind Harmer
5.121
270536AF1-215 GEN2
Solar/Wind Harmer
5.712
274746AC1-111 G10
Adder
6.996
274744AC1-111 GEN8
Adder
6.996
958711AF2-162 GEN
Solar/Wind Harmer
1.23
958391AF2-133 GEN
Solar/Wind Harmer
11.003
276868AE1-113 GEN
Solar/Wind Harmer
12.231
276882AE2-255 GEN
Solar/Wind Harmer
4.077
971177AH1-047 GEN
Solar/Wind Harmer
7.079
971411AH1-196 GEN
Solar/Wind Harmer
18.031
971675AH1-338 GEN
Solar/Wind Harmer
21.635
274823ROCKFORD ;21
Adder
23.136
24722005FLATG5
50/50
8.432
24721905FLATG4
50/50
154.591
270142AC1-141 CT1_
50/50
3.334
24344005CKG1
50/50
9.104
24641605TWIN BRNCH
50/50
0.024
24642205MAYFLWER
50/50
0.927
944961AF1-161 GEN
50/50
3.972
962601AG1-109 GEN
50/50
3.972
247604X1-042
50/50
0.589
970153AG2-106 GEN
Solar/Wind Harmer
75.966
970349AG2-230 GEN
Solar/Wind Harmer
22.036
270043AE2-236 GEN
Solar/Wind Harmer
7.928
970513AG2-328 GEN
Solar/Wind Harmer
25.325
970517AG2-330 GEN
Solar/Wind Harmer
22.969
247643Z2-116 C
Solar/Wind Harmer
0.097
945111AF1-176 GEN
Solar/Wind Harmer
7.764
970031AG2-029 GEN
Solar/Wind Harmer
40.661
24441205WTRV SLR C
Solar/Wind Harmer
0.181
944531AF1-118 GEN
Solar/Wind Harmer
46.957
959331AF2-224 GEN
Solar/Wind Harmer
13.218
965021AG1-366 GEN
Solar/Wind Harmer
3.074
274772LINCOLN ;3U
Adder
8.163
274724RIVER EC ;11
Adder
23.052
972231SS25-0005
Solar/Wind Harmer
12.334
972181SS23-001
Solar/Wind Harmer
7.709
274752CRETE EC ;2U
Adder
6.353
274753CRETE EC ;3U
Adder
6.353
970707AG2-453 GEN
Solar/Wind Harmer
36.006
274802UNIV PARK;5U
Adder
7.474
274826FISK ;BP
Adder
14.031
276772AC2-154 GEN
Solar/Wind Harmer
3.569
276806AD2-047 C O1
Solar/Wind Harmer
13.693
970941AG2-585 GEN
Solar/Wind Harmer
16
274800UNIV PARK;3U
Adder
7.462
972038AH1-567 GEN2
Adder
0.467
972228AH1-698 GEN2
Adder
4.737
276897AD1-100 C
Solar/Wind Harmer
36.905
939351AE1-166 GEN
Solar/Wind Harmer
7.541
274676JOLIET 29;8U
Adder
37.492
274729ELWOOD EC;1P
Adder
20.768
274730ELWOOD EC;6P
Adder
20.768
274734ELWOOD EC;8P
Adder
20.768
274736ELWOOD EC;9P
Adder
20.768
276893AG1-478 C
Solar/Wind Harmer
0.527
270535AF1-215 GEN1
Solar/Wind Harmer
5.712
943121AE2-341 GEN
Solar/Wind Harmer
18.813
943591AF1-030 GEN
Solar/Wind Harmer
12.542
276694AA1-018 GEN2
Solar/Wind Harmer
7.785
274682WAUKEGAN ;7U
Adder
22.136
964401AG1-302 GEN
Solar/Wind Harmer
11.14
274872LEEDK;1U
Solar/Wind Harmer
0.311
276805AD2-038 GEN
Solar/Wind Harmer
6.236
276799AD1-013 GEN
Solar/Wind Harmer
2.659
946671AF1-331 GEN
Solar/Wind Harmer
0.503
959141AF2-205 GEN
Solar/Wind Harmer
7.265
274855GSG-6 ;RU
Solar/Wind Harmer
4.438
274850MENDOTA H;RU
Solar/Wind Harmer
3.086
276602WESTBROOK C
Solar/Wind Harmer
2.554
276863AD2-134 GEN
Solar/Wind Harmer
2.146
972236AH1-702 GEN2
Adder
2.595
274760LEE CO EC;1U
Adder
10.813
274767LEE CO EC;8U
Adder
10.686
270102X2-052 ST
50/50
2.201
270100X2-052 CT1
50/50
2.028
270101X2-052 CT2
50/50
2.028
247620Y3-023
50/50
0.669
970615AG2-402 GEN
50/50
3.074
970321AG2-212 GEN
Solar/Wind Harmer
25.325
270216AD2-079_GEN
Solar/Wind Harmer
0.841
957891AF2-083 GEN
Solar/Wind Harmer
4.643
960981AF2-389 GEN
Solar/Wind Harmer
2.08
270526AF1-158 GEN
Solar/Wind Harmer
6.237
24441505OLIV SLR
Solar/Wind Harmer
0.183
961051AF2-396 GEN
Solar/Wind Harmer
21.727
961051AF2-396 GEN
Solar/Wind Harmer
10.106
965681AG1-436 GEN
Solar/Wind Harmer
17.064
965791AG1-447 GEN
Solar/Wind Harmer
8.731
970611AG2-400 GEN
Solar/Wind Harmer
13.218
274770LINCOLN ;1U
Adder
8.163
274771LINCOLN ;2U
Adder
8.163
274808UNIV PK N;4U
Adder
6.434
274803UNIV PARK;6U
Adder
7.474
972259AH1-714 GEN
Adder
24.421
274888KELLY CRK;1U
Solar/Wind Harmer
7.557
274887GEN-1.85
Solar/Wind Harmer
6.822
276843GEN-1.7
Solar/Wind Harmer
0.734
958011AF2-095 GEN
Solar/Wind Harmer
18.431
274674JOLIET 9 ;6U
Adder
19.473
274847GR RIDGE ;BU
Solar/Wind Harmer
6.376
971573AH1-285 GEN
Solar/Wind Harmer
10.712
274696ROCKY RD ;4P
Adder
14.064
274695ROCKY RD ;2P
Adder
13.74
274693ROCKY RD ;1P
Adder
13.605
274697ROCKY RD ;3P
Adder
3.732
958481AF2-142 GEN
Solar/Wind Harmer
18.503
274861TOP CROP ;1U
Solar/Wind Harmer
7.47
274862TOP CROP ;2U
Solar/Wind Harmer
6.238
274683WAUKEGAN ;8U
Adder
25.914
274683WAUKEGAN ;8U
Adder
21.844
962691AG1-118 GEN
Solar/Wind Harmer
36.699
970921AG2-575 GEN
Solar/Wind Harmer
12.196
970921AG2-575 GEN
Solar/Wind Harmer
2.836
944541AF1-119 GEN
Solar/Wind Harmer
5.094
960971AF2-388 GEN
Solar/Wind Harmer
13.293
958491AF2-143 GEN
Solar/Wind Harmer
18.234
942991AE2-321 GEN
Solar/Wind Harmer
12.086
274879MINONK ;1U
Solar/Wind Harmer
8.155
274764LEE CO EC;5U
Adder
10.839
274765LEE CO EC;6U
Adder
10.839
274762LEE CO EC;3U
Adder
10.813
274763LEE CO EC;4U
Adder
10.711
972267AH1-718 GEN
Adder
4.78
247621Y3-024
Adder
0.217
971333AH1-146 GEN
Solar/Wind Harmer
8.998
971335AH1-147 GEN
Solar/Wind Harmer
8.998
NYPJM->LTFIMP_NY
CLTF
2.159
LGEELTFEXP_LGEE->PJM
CLTF
2.657
WECLTFEXP_WEC->PJM
CLTF
4.511
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.689
AG2-052LTFEXP_AG2-052->PJM
LTF
0.285
AH1-155LTFEXP_AH1-155->PJM
LTF
0.428
CBM West 2LTFEXP_CBM-W2->PJM
CBM
70.171
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
6.748
TVALTFEXP_TVA->PJM
CLTF
2.171
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.936
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.15
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.3
MECLTFEXP_MEC->PJM
CLTF
15.891
SIGELTFEXP_SIGE->PJM
CLTF
0.293

Details for 05GAVIN-05MOUNTN 765.0 kV Ckt 1 line l/o AEP_P4_#8075_05MARYSV 765_A2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05GAVIN-05MOUNTN 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8075_05MARYSV 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:123.29 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5635.54
MW Contribution:51.36
Bus #Bus NameTypeMW Contribution
243186AF1-051 GEN
50/50
25.26
24318705GVG2
50/50
23.513
24721805FLATG3
50/50
5.618
24721705FLATG2
50/50
102.988
24344105CKG2
50/50
9.075
962761AG1-125 GEN
Solar/Wind Harmer
117.777
970149AG2-104 GEN
Solar/Wind Harmer
145.454
970155AG2-107 GEN
Solar/Wind Harmer
51.356
970245AG2-165 GEN
Solar/Wind Harmer
20.818
972207SS24-0001
Solar/Wind Harmer
24.25
274773LINCOLN ;4U
Adder
6.821
274774LINCOLN ;5U
Adder
6.821
274723RIVER EC ;12
Adder
19.455
276164X3-005 C
Solar/Wind Harmer
0.762
274751CRETE EC ;1U
Adder
5.293
274754CRETE EC ;4U
Adder
5.293
274812UNIV PK N;8U
Adder
5.412
276776AD2-060 GEN
Solar/Wind Harmer
0.456
274801UNIV PARK;4U
Adder
6.287
270505AE1-170 C O1
Solar/Wind Harmer
16.176
941551AE2-152 GEN
Solar/Wind Harmer
4.881
24639705ELKHART HY
Adder
0.165
274676JOLIET 29;8U
Adder
32.95
274674JOLIET 9 ;6U
Adder
16.518
945111AF1-176 GEN
Solar/Wind Harmer
19.135
274732ELWOOD EC;7P
Adder
17.621
274871GR RIDGE ;2U
Solar/Wind Harmer
8.241
970373AG2-245 GEN
Solar/Wind Harmer
22.45
274745AC1-111 GEN9
Adder
5.972
270449AD2-020 GEN
Solar/Wind Harmer
2.988
943021AE2-325 GEN
Solar/Wind Harmer
3.883
274682WAUKEGAN ;7U
Adder
19.034
274828WAUKEGAN ;BP
Adder
11.689
276691AA1-018 GEN1
Solar/Wind Harmer
0.493
270055AF2-134 C O1
Solar/Wind Harmer
3.194
960751AF2-366 GEN
Solar/Wind Harmer
3.025
962781AG1-127 GEN
Solar/Wind Harmer
10.026
270063AE2-323 C
Solar/Wind Harmer
2.322
274872LEEDK;1U
Solar/Wind Harmer
8.646
939401AE1-172 GEN
Solar/Wind Harmer
14.633
276901AD2-066 C O1
Solar/Wind Harmer
3.686
971997AH1-543 GEN
Solar/Wind Harmer
16.471
276861AD2-134 GEN
Solar/Wind Harmer
1.868
958381AF2-132 GEN
Solar/Wind Harmer
9.451
274822ROCKFORD ;11
Adder
20.404
972235AH1-702 GEN1
Adder
2.616
274761LEE CO EC;2U
Adder
9.567
274766LEE CO EC;7U
Adder
9.454
957471AF2-041 GEN
Solar/Wind Harmer
27.965
959081AF2-199 GEN
Solar/Wind Harmer
9.322
971067AG2-660 GEN
Solar/Wind Harmer
2.168
24721605FLATG1
50/50
5.618
971599AH1-298 GEN
50/50
10.439
962771AG1-126 GEN
Solar/Wind Harmer
117.777
971347AH1-153 GEN
Solar/Wind Harmer
17.432
960681AF2-359 GEN
Solar/Wind Harmer
4.165
274775LINCOLN ;6U
Adder
6.821
274776LINCOLN ;7U
Adder
6.821
274777LINCOLN ;8U
Adder
6.821
971771AH1-392 GEN
Solar/Wind Harmer
9.855
971769AH1-391 GEN
Solar/Wind Harmer
10.941
270071AF1-092 GEN
Solar/Wind Harmer
16.349
274814UNIV PK N;0U
Adder
5.46
274807UNIV PK N;3U
Adder
5.448
274805UNIV PK N;1U
Adder
5.424
274811UNIV PK N;7U
Adder
5.412
274827FISK ;RP
Adder
8.372
972227AH1-698 GEN1
Adder
2.814
972037AH1-567 GEN1
Adder
0.197
960591AF2-350 GEN
Solar/Wind Harmer
10.788
274687WILL CNTY;4U
Adder
30.024
274687WILL CNTY;4U
Adder
30.024
274675JOLIET 29;7U
Adder
32.951
274675JOLIET 29;7U
Adder
31.774
274731ELWOOD EC;2P
Adder
17.621
274733ELWOOD EC;3P
Adder
17.621
274735ELWOOD EC;4P
Adder
17.621
274728ELWOOD EC;5P
Adder
17.621
970833AG2-524 GEN
Solar/Wind Harmer
9.359
970833AG2-524 GEN
Solar/Wind Harmer
4.353
274746AC1-111 G10
Adder
5.972
274744AC1-111 GEN8
Adder
5.972
944161AF1-084 GEN
Solar/Wind Harmer
2.341
270536AF1-215 GEN2
Solar/Wind Harmer
4.791
971177AH1-047 GEN
Solar/Wind Harmer
6.146
276868AE1-113 GEN
Solar/Wind Harmer
10.596
276882AE2-255 GEN
Solar/Wind Harmer
3.532
971675AH1-338 GEN
Solar/Wind Harmer
18.832
971411AH1-196 GEN
Solar/Wind Harmer
15.692
274823ROCKFORD ;21
Adder
20.256
24729505KEY G4
Adder
6.702
971171AH1-044 GEN
Solar/Wind Harmer
18.644
24318705GVG2
50/50
23.513
24722005FLATG5
50/50
5.618
243186AF1-051 GEN
50/50
25.26
270102X2-052 ST
50/50
1.77
270100X2-052 CT1
50/50
1.631
270101X2-052 CT2
50/50
1.631
970321AG2-212 GEN
Solar/Wind Harmer
20.818
965681AG1-436 GEN
Solar/Wind Harmer
13.782
965791AG1-447 GEN
Solar/Wind Harmer
7.051
274770LINCOLN ;1U
Adder
6.821
274771LINCOLN ;2U
Adder
6.821
270526AF1-158 GEN
Solar/Wind Harmer
4.972
24441505OLIV SLR
Solar/Wind Harmer
0.147
270216AD2-079_GEN
Solar/Wind Harmer
0.659
972259AH1-714 GEN
Adder
20.623
274808UNIV PK N;4U
Adder
5.389
274803UNIV PARK;6U
Adder
6.289
274888KELLY CRK;1U
Solar/Wind Harmer
6.369
274887GEN-1.85
Solar/Wind Harmer
5.75
276843GEN-1.7
Solar/Wind Harmer
0.619
958011AF2-095 GEN
Solar/Wind Harmer
15.534
957891AF2-083 GEN
Solar/Wind Harmer
3.633
960981AF2-389 GEN
Solar/Wind Harmer
1.628
274674JOLIET 9 ;6U
Adder
16.518
274847GR RIDGE ;BU
Solar/Wind Harmer
5.421
961051AF2-396 GEN
Solar/Wind Harmer
16.96
961051AF2-396 GEN
Solar/Wind Harmer
7.888
971573AH1-285 GEN
Solar/Wind Harmer
9.17
247620Y3-023
Adder
0.49
274696ROCKY RD ;4P
Adder
12.086
274695ROCKY RD ;2P
Adder
11.807
274693ROCKY RD ;1P
Adder
11.691
274697ROCKY RD ;3P
Adder
3.207
274683WAUKEGAN ;8U
Adder
22.3
274683WAUKEGAN ;8U
Adder
18.798
958481AF2-142 GEN
Solar/Wind Harmer
15.868
274861TOP CROP ;1U
Solar/Wind Harmer
6.408
274862TOP CROP ;2U
Solar/Wind Harmer
5.351
962691AG1-118 GEN
Solar/Wind Harmer
31.676
970921AG2-575 GEN
Solar/Wind Harmer
10.542
970921AG2-575 GEN
Solar/Wind Harmer
2.452
958491AF2-143 GEN
Solar/Wind Harmer
15.747
942991AE2-321 GEN
Solar/Wind Harmer
10.491
274879MINONK ;1U
Solar/Wind Harmer
7.065
971333AH1-146 GEN
Solar/Wind Harmer
20.914
971335AH1-147 GEN
Solar/Wind Harmer
20.914
274764LEE CO EC;5U
Adder
9.589
274765LEE CO EC;6U
Adder
9.589
274762LEE CO EC;3U
Adder
9.567
274763LEE CO EC;4U
Adder
9.476
972267AH1-718 GEN
Adder
4.255
971341AH1-150 GEN
Solar/Wind Harmer
18.644
971343AH1-151 GEN
Solar/Wind Harmer
18.644
24721905FLATG4
50/50
102.988
970153AG2-106 GEN
Solar/Wind Harmer
51.356
970513AG2-328 GEN
Solar/Wind Harmer
20.818
970517AG2-330 GEN
Solar/Wind Harmer
18.882
970349AG2-230 GEN
Solar/Wind Harmer
17.432
270043AE2-236 GEN
Solar/Wind Harmer
6.065
274772LINCOLN ;3U
Adder
6.821
247643Z2-116 C
Solar/Wind Harmer
0.076
274724RIVER EC ;11
Adder
19.232
970707AG2-453 GEN
Solar/Wind Harmer
30.387
24642205MAYFLWER
Adder
0.688
972231SS25-0005
Solar/Wind Harmer
10.277
972181SS23-001
Solar/Wind Harmer
6.423
274752CRETE EC ;2U
Adder
5.293
274753CRETE EC ;3U
Adder
5.293
274826FISK ;BP
Adder
11.813
972228AH1-698 GEN2
Adder
3.996
274802UNIV PARK;5U
Adder
6.289
276772AC2-154 GEN
Solar/Wind Harmer
3.008
276806AD2-047 C O1
Solar/Wind Harmer
11.54
970941AG2-585 GEN
Solar/Wind Harmer
13.485
274800UNIV PARK;3U
Adder
6.287
972038AH1-567 GEN2
Adder
0.394
276897AD1-100 C
Solar/Wind Harmer
31.232
939351AE1-166 GEN
Solar/Wind Harmer
6.381
274676JOLIET 29;8U
Adder
31.774
945111AF1-176 GEN
Solar/Wind Harmer
6.065
274729ELWOOD EC;1P
Adder
17.621
274730ELWOOD EC;6P
Adder
17.621
274734ELWOOD EC;8P
Adder
17.621
274736ELWOOD EC;9P
Adder
17.621
276893AG1-478 C
Solar/Wind Harmer
0.448
943121AE2-341 GEN
Solar/Wind Harmer
16.053
943591AF1-030 GEN
Solar/Wind Harmer
10.702
274682WAUKEGAN ;7U
Adder
19.034
276694AA1-018 GEN2
Solar/Wind Harmer
6.676
270535AF1-215 GEN1
Solar/Wind Harmer
4.791
274872LEEDK;1U
Solar/Wind Harmer
0.269
944531AF1-118 GEN
Solar/Wind Harmer
36.841
276805AD2-038 GEN
Solar/Wind Harmer
5.385
276799AD1-013 GEN
Solar/Wind Harmer
2.314
946671AF1-331 GEN
Solar/Wind Harmer
0.438
274855GSG-6 ;RU
Solar/Wind Harmer
3.864
274850MENDOTA H;RU
Solar/Wind Harmer
2.686
276602WESTBROOK C
Solar/Wind Harmer
2.224
276863AD2-134 GEN
Solar/Wind Harmer
1.868
24441205WTRV SLR C
Solar/Wind Harmer
0.141
964401AG1-302 GEN
Solar/Wind Harmer
9.451
972236AH1-702 GEN2
Adder
2.275
247604X1-042
Adder
0.43
274760LEE CO EC;1U
Adder
9.567
274767LEE CO EC;8U
Adder
9.454
959091AF2-200 GEN
Solar/Wind Harmer
18.644
NYPJM->LTFIMP_NY
CLTF
3.425
LGEELTFEXP_LGEE->PJM
CLTF
4.044
WECLTFEXP_WEC->PJM
CLTF
3.963
AG2-052LTFEXP_AG2-052->PJM
LTF
0.242
AH1-155LTFEXP_AH1-155->PJM
LTF
0.363
CPLELTFEXP_CPLE->PJM
CLTF
3.117
CBM West 2LTFEXP_CBM-W2->PJM
CBM
100.483
LAGNLTFEXP_LAGN->PJM
CLTF
13.972
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.347
TVALTFEXP_TVA->PJM
CLTF
6.616
CBM West 1LTFEXP_CBM-W1->PJM
CBM
120.733
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.354
MECLTFEXP_MEC->PJM
CLTF
15.717
SIGELTFEXP_SIGE->PJM
CLTF
0.371

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P4_#9728_05MALIS 138_L1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9728_05MALIS 138_L1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.65 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1756.35
MW Contribution:9.12
Bus #Bus NameTypeMW Contribution
270349AD2-093_GEN
Solar/Wind Harmer
4.882
971995AH1-542 GEN
Solar/Wind Harmer
11.801
270223U2-072_GEN1
Solar/Wind Harmer
1.977
270578AF1-285 GEN2
Solar/Wind Harmer
1.209
270391AF1-285 GEN3
Solar/Wind Harmer
1.209
270462AD2-086
Solar/Wind Harmer
6.507
241813AF1-122_GEN
Solar/Wind Harmer
4.908
970593AG2-378 GEN
Solar/Wind Harmer
1.421
962761AG1-125 GEN
Solar/Wind Harmer
20.924
970149AG2-104 GEN
Solar/Wind Harmer
25.841
970155AG2-107 GEN
Solar/Wind Harmer
9.124
246936BC-WTG1
Solar/Wind Harmer
2.355
270489AE1-102 GEN1
Solar/Wind Harmer
0.782
965421AG1-410 GEN
Solar/Wind Harmer
17.855
247521TR3_G114
Solar/Wind Harmer
1.865
270246TR4_N_V150
Solar/Wind Harmer
0.472
24695305TIMB G C
Solar/Wind Harmer
3.018
965011AG1-365 GEN
Solar/Wind Harmer
5.315
270159DARBY CT4
Adder
4.615
944231AF1-091 GEN
Solar/Wind Harmer
1.845
253343AC1-166 GEN
Solar/Wind Harmer
0.526
253325AC1-069 GEN
Solar/Wind Harmer
0.507
960071AF2-298 GEN
Solar/Wind Harmer
2.404
25326309TAIT D
Adder
0.526
270063AE2-323 C
Solar/Wind Harmer
1.058
965651AG1-433 GEN
Solar/Wind Harmer
2.549
24639705ELKHART HY
Adder
0.071
253370AE2-315 SEC1
Adder
0.929
253371AE2-315 SEC2
Adder
0.879
958861AF2-177 GEN
Solar/Wind Harmer
5.061
247536S-71 GEN
Solar/Wind Harmer
1.868
945111AF1-176 GEN
Solar/Wind Harmer
8.176
270505AE1-170 C O1
Solar/Wind Harmer
6.853
945371AF1-202 GEN
Solar/Wind Harmer
3.186
270449AD2-020 GEN
Solar/Wind Harmer
1.276
943021AE2-325 GEN
Solar/Wind Harmer
1.657
970245AG2-165 GEN
Solar/Wind Harmer
8.061
970825AG2-519 GEN
Solar/Wind Harmer
1.042
270005AE1-210 C O1
Solar/Wind Harmer
2.413
965031AG1-367 GEN
Solar/Wind Harmer
4.414
970373AG2-245 GEN
Solar/Wind Harmer
9.267
274751CRETE EC ;1U
Adder
3.613
274754CRETE EC ;4U
Adder
3.613
274773LINCOLN ;4U
Adder
3.698
274774LINCOLN ;5U
Adder
3.698
274723RIVER EC ;12
Adder
7.85
274812UNIV PK N;8U
Adder
2.185
274801UNIV PARK;4U
Adder
2.53
274676JOLIET 29;8U
Adder
13.243
274674JOLIET 9 ;6U
Adder
6.64
274732ELWOOD EC;7P
Adder
7.088
270036AE2-216 BAT
50/50
5.972
270284AF1-227 GEN1
Solar/Wind Harmer
6.854
270286AF1-227 GEN2
Solar/Wind Harmer
2.536
270287AF1-227 GEN3
Solar/Wind Harmer
2.536
270578AF1-285 GEN2
Solar/Wind Harmer
0.465
241973AD2-163_GEN1
Solar/Wind Harmer
1.957
270302AB2-170 GEN
Solar/Wind Harmer
7.822
270317AD1-130_GEN
Solar/Wind Harmer
2.998
270520AE2-214 GEN
Solar/Wind Harmer
5.402
970179AG2-119 GEN
Solar/Wind Harmer
6.794
962771AG1-126 GEN
Solar/Wind Harmer
20.924
957201AF2-014 GEN
Solar/Wind Harmer
2.73
270435AC2-044 GEN
Solar/Wind Harmer
1.204
241972AD1-140 GEN
Solar/Wind Harmer
2.573
247607V1-011 GEN
Solar/Wind Harmer
2.229
965051AG1-369 GEN
Solar/Wind Harmer
2.769
270297AD1-101 GEN
Solar/Wind Harmer
1.544
965041AG1-368 GEN
Solar/Wind Harmer
5.379
945631AF1-228 GEN
Solar/Wind Harmer
2.515
270156DARBY CT1
Adder
4.69
270157DARBY CT2
Adder
4.678
270158DARBY CT3
Adder
4.603
943861AF1-054 GEN
Solar/Wind Harmer
1.939
943851AF1-053 GEN
Solar/Wind Harmer
0.937
963791AG1-232 GEN
Solar/Wind Harmer
6.797
270071AF1-092 GEN
Solar/Wind Harmer
7.236
270024AE2-089 GEN
Solar/Wind Harmer
2.257
24729505KEY G4
Adder
3.093
253349AC2-067 GEN
Solar/Wind Harmer
2.35
253400AC2-068 GEN
Solar/Wind Harmer
0.945
961761AG1-017 GEN
Solar/Wind Harmer
0.2
958711AF2-162 GEN
Solar/Wind Harmer
0.472
25306009OHH W.
Adder
1.34
253372AE2-315 SEC3
Adder
0.879
253372AE2-315 SEC3
Adder
0.879
965101AG1-375 GEN
Solar/Wind Harmer
4.631
971347AH1-153 GEN
Solar/Wind Harmer
6.938
971771AH1-392 GEN
Solar/Wind Harmer
4.117
270543AE2-219 C
Solar/Wind Harmer
2.339
945581AF1-223 GEN
Solar/Wind Harmer
2.071
944161AF1-084 GEN
Solar/Wind Harmer
1.002
971769AH1-391 GEN
Solar/Wind Harmer
4.525
971029AG2-637 GEN
Solar/Wind Harmer
6.782
971673AH1-337 GEN
Solar/Wind Harmer
2.073
253383AE2-342_GEN
Solar/Wind Harmer
0.399
960681AF2-359 GEN
Solar/Wind Harmer
1.7
970115AG2-085 GEN
Solar/Wind Harmer
1.77
274775LINCOLN ;6U
Adder
3.698
274776LINCOLN ;7U
Adder
3.698
274777LINCOLN ;8U
Adder
3.698
274814UNIV PK N;0U
Adder
2.205
274807UNIV PK N;3U
Adder
2.2
274805UNIV PK N;1U
Adder
2.19
274811UNIV PK N;7U
Adder
2.185
972037AH1-567 GEN1
Adder
0.08
274827FISK ;RP
Adder
3.37
972227AH1-698 GEN1
Adder
1.131
274687WILL CNTY;4U
Adder
12.072
274687WILL CNTY;4U
Adder
12.072
274675JOLIET 29;7U
Adder
13.243
274675JOLIET 29;7U
Adder
12.77
274731ELWOOD EC;2P
Adder
7.088
274733ELWOOD EC;3P
Adder
7.088
274735ELWOOD EC;4P
Adder
7.088
274728ELWOOD EC;5P
Adder
7.088
270054AF2-122 C O1
Solar/Wind Helper
0.823
971549AH1-272 GEN
Solar/Wind Harmer
6.331
270475AD2-096_GEN
50/50
7.813
942871AE2-306 GEN
Solar/Wind Harmer
0.907
270391AF1-285 GEN3
Solar/Wind Harmer
0.465
241974AD2-163_GEN2
Solar/Wind Harmer
1.957
270485AE1-090_GEN
Solar/Wind Harmer
0.566
942051AE2-217 GEN
Solar/Wind Harmer
13.984
970065AG2-057 GEN
Solar/Wind Harmer
0.767
970605AG2-385 GEN
Solar/Wind Harmer
3.836
241955AC1-078 GEN
Solar/Wind Harmer
5.001
970153AG2-106 GEN
Solar/Wind Harmer
9.124
270491AE1-102 GEN2
Solar/Wind Harmer
0.782
958091AF2-103 GEN
Solar/Wind Harmer
0.091
270191TR4_S_V150
Solar/Wind Harmer
1.663
270247TR4_N_V136
Solar/Wind Harmer
0.472
270258AD1-119 GEN
Solar/Wind Harmer
1.498
959331AF2-224 GEN
Solar/Wind Harmer
5.315
965021AG1-366 GEN
Solar/Wind Harmer
1.236
270044AE2-322 C
Solar/Wind Harmer
0.691
270404AC1-167 GEN
Solar/Wind Harmer
0.576
270588AE1-091_GEN
Solar/Wind Harmer
5.503
270043AE2-236 GEN
Solar/Wind Harmer
2.714
253338AC1-165 GEN
Solar/Wind Harmer
0.526
253333AC1-068 GEN
Solar/Wind Harmer
0.507
970031AG2-029 GEN
Solar/Wind Harmer
14.514
971617AH1-308 GEN
Solar/Wind Harmer
2.796
944531AF1-118 GEN
Solar/Wind Harmer
16.819
270541AE2-072 C
Solar/Wind Harmer
2.163
962031AG1-047 GEN
Solar/Wind Harmer
1.413
957741AF2-068 GEN
Solar/Wind Harmer
7.01
253303V4-073 C
Solar/Wind Harmer
0.054
253370AE2-315 SEC1
Adder
0.929
253371AE2-315 SEC2
Adder
0.879
970349AG2-230 GEN
Solar/Wind Harmer
6.938
247643Z2-116 C
Solar/Wind Harmer
0.032
945111AF1-176 GEN
Solar/Wind Harmer
2.591
24642205MAYFLWER
Adder
0.29
970513AG2-328 GEN
Solar/Wind Harmer
8.061
970517AG2-330 GEN
Solar/Wind Harmer
7.311
24441205WTRV SLR C
Solar/Wind Harmer
0.061
247604X1-042
Adder
0.187
946031AF1-268 GEN
Solar/Wind Harmer
3.715
958821AF2-173 GEN
Solar/Wind Harmer
6.18
270004AE1-209 GEN
Solar/Wind Harmer
2.413
274752CRETE EC ;2U
Adder
3.613
274753CRETE EC ;3U
Adder
3.613
274772LINCOLN ;3U
Adder
3.698
274724RIVER EC ;11
Adder
7.758
274802UNIV PARK;5U
Adder
2.533
274826FISK ;BP
Adder
4.755
274800UNIV PARK;3U
Adder
2.53
972038AH1-567 GEN2
Adder
0.158
972228AH1-698 GEN2
Adder
1.606
274676JOLIET 29;8U
Adder
12.77
274729ELWOOD EC;1P
Adder
7.088
274730ELWOOD EC;6P
Adder
7.088
274734ELWOOD EC;8P
Adder
7.088
274736ELWOOD EC;9P
Adder
7.088
270466AD2-091
50/50
5.429
270471AD2-092_GEN
Solar/Wind Harmer
4.882
938701AE1-092 GEN
Solar/Wind Harmer
21.983
964601AG1-323 GEN
Solar/Wind Harmer
3.2
964601AG1-323 GEN
Solar/Wind Harmer
1.488
270224U2-072_GEN2
Solar/Wind Harmer
1.977
270227U2-072_GEN3
Solar/Wind Harmer
1.977
270228U2-072_GEN4
Solar/Wind Harmer
1.977
270231U2-072_GEN5
Solar/Wind Harmer
1.977
946101AF1-275 GEN
Solar/Wind Harmer
1.348
241960AC2-195 GEN
Solar/Wind Harmer
2.362
971201AH1-060 GEN
Solar/Wind Harmer
1.534
970077AG2-063 GEN
Solar/Wind Harmer
3.836
253378AE2-206_GEN
Solar/Wind Harmer
2.399
276820AF1-078_GEN
Solar/Wind Harmer
1.066
25326509SID D
Adder
0.833
246938BC-WTG3
Solar/Wind Harmer
2.396
246937BC-WTG2
Solar/Wind Harmer
2.355
270007AE1-245 C
Solar/Wind Harmer
3.344
942801AE2-298 GEN
Solar/Wind Harmer
0.852
970611AG2-400 GEN
Solar/Wind Harmer
5.315
270518AE2-148 GEN
Solar/Wind Harmer
6.282
942861AE2-305 GEN
Solar/Wind Harmer
3.928
25326109MON D
Adder
0.653
25322209TAIT E
Adder
4.68
25322209TAIT E
Adder
4.575
942221AE2-234 GEN
Solar/Wind Harmer
0.35
247620Y3-023
Adder
0.215
270201AC2-176 GEN
Solar/Wind Harmer
2.402
944541AF1-119 GEN
Solar/Wind Harmer
1.954
960971AF2-388 GEN
Solar/Wind Harmer
5.098
247621Y3-024
Adder
0.112
253370AE2-315 SEC1
Adder
0.929
964611AG1-324 GEN
Solar/Wind Harmer
0.546
964611AG1-324 GEN
Solar/Wind Harmer
0.242
270216AD2-079_GEN
Solar/Wind Harmer
0.28
960981AF2-389 GEN
Solar/Wind Harmer
0.691
957891AF2-083 GEN
Solar/Wind Harmer
1.542
970883AG2-550 GEN
Solar/Wind Harmer
4.568
970885AG2-551 GEN
Solar/Wind Harmer
1.062
961051AF2-396 GEN
Solar/Wind Harmer
7.242
961051AF2-396 GEN
Solar/Wind Harmer
3.368
270526AF1-158 GEN
Solar/Wind Harmer
2.06
24441505OLIV SLR
Solar/Wind Harmer
0.061
970321AG2-212 GEN
Solar/Wind Harmer
8.061
270599AE1-208 GEN
Solar/Wind Harmer
3.679
270031AE2-169
Solar/Wind Harmer
3.679
965681AG1-436 GEN
Solar/Wind Harmer
5.624
965791AG1-447 GEN
Solar/Wind Harmer
2.877
970825AG2-519 GEN
Solar/Wind Harmer
4.672
960441AF2-335 GEN
Solar/Wind Harmer
4.424
274770LINCOLN ;1U
Adder
3.698
274771LINCOLN ;2U
Adder
3.698
274808UNIV PK N;4U
Adder
2.176
274803UNIV PARK;6U
Adder
2.533
972259AH1-714 GEN
Adder
8.267
274674JOLIET 9 ;6U
Adder
6.64
NYPJM->LTFIMP_NY
CLTF
1.307
LGEELTFEXP_LGEE->PJM
CLTF
2.299
WECLTFEXP_WEC->PJM
CLTF
1.593
AG2-052LTFEXP_AG2-052->PJM
LTF
0.101
AH1-155LTFEXP_AH1-155->PJM
LTF
0.151
CPLELTFEXP_CPLE->PJM
CLTF
0.349
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.92
LAGNLTFEXP_LAGN->PJM
CLTF
5.126
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.351
TVALTFEXP_TVA->PJM
CLTF
2.378
CBM West 1LTFEXP_CBM-W1->PJM
CBM
56.507
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.587
MECLTFEXP_MEC->PJM
CLTF
6.34
SIGELTFEXP_SIGE->PJM
CLTF
0.182

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P4_#9730_05MALIS 138_P1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9730_05MALIS 138_P1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.16 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1749.36
MW Contribution:9.1
Bus #Bus NameTypeMW Contribution
270349AD2-093_GEN
Solar/Wind Harmer
4.871
971995AH1-542 GEN
Solar/Wind Harmer
11.773
270223U2-072_GEN1
Solar/Wind Harmer
1.972
270578AF1-285 GEN2
Solar/Wind Harmer
1.206
270391AF1-285 GEN3
Solar/Wind Harmer
1.206
270462AD2-086
Solar/Wind Harmer
6.492
241813AF1-122_GEN
Solar/Wind Harmer
4.897
970593AG2-378 GEN
Solar/Wind Harmer
1.416
962761AG1-125 GEN
Solar/Wind Harmer
20.876
970149AG2-104 GEN
Solar/Wind Harmer
25.782
970155AG2-107 GEN
Solar/Wind Harmer
9.103
246936BC-WTG1
Solar/Wind Harmer
2.35
270489AE1-102 GEN1
Solar/Wind Harmer
0.781
965421AG1-410 GEN
Solar/Wind Harmer
17.815
247521TR3_G114
Solar/Wind Harmer
1.86
270246TR4_N_V150
Solar/Wind Harmer
0.471
24695305TIMB G C
Solar/Wind Harmer
3.012
965011AG1-365 GEN
Solar/Wind Harmer
5.303
270159DARBY CT4
Adder
4.607
944231AF1-091 GEN
Solar/Wind Harmer
1.841
253343AC1-166 GEN
Solar/Wind Harmer
0.525
253325AC1-069 GEN
Solar/Wind Harmer
0.506
960071AF2-298 GEN
Solar/Wind Harmer
2.398
25326309TAIT D
Adder
0.525
270063AE2-323 C
Solar/Wind Harmer
1.055
965651AG1-433 GEN
Solar/Wind Harmer
2.544
24639705ELKHART HY
Adder
0.071
253370AE2-315 SEC1
Adder
0.927
253371AE2-315 SEC2
Adder
0.877
958861AF2-177 GEN
Solar/Wind Harmer
5.05
247536S-71 GEN
Solar/Wind Harmer
1.864
945111AF1-176 GEN
Solar/Wind Harmer
8.158
270505AE1-170 C O1
Solar/Wind Harmer
6.839
945371AF1-202 GEN
Solar/Wind Harmer
3.179
270449AD2-020 GEN
Solar/Wind Harmer
1.273
943021AE2-325 GEN
Solar/Wind Harmer
1.654
970245AG2-165 GEN
Solar/Wind Harmer
8.044
970825AG2-519 GEN
Solar/Wind Harmer
1.04
270005AE1-210 C O1
Solar/Wind Harmer
2.407
965031AG1-367 GEN
Solar/Wind Harmer
4.405
970373AG2-245 GEN
Solar/Wind Harmer
9.248
274751CRETE EC ;1U
Adder
3.605
274754CRETE EC ;4U
Adder
3.605
274773LINCOLN ;4U
Adder
3.69
274774LINCOLN ;5U
Adder
3.69
274723RIVER EC ;12
Adder
7.833
274812UNIV PK N;8U
Adder
2.181
274801UNIV PARK;4U
Adder
2.525
274676JOLIET 29;8U
Adder
13.215
274674JOLIET 9 ;6U
Adder
6.626
274732ELWOOD EC;7P
Adder
7.073
270036AE2-216 BAT
50/50
5.958
270284AF1-227 GEN1
Solar/Wind Harmer
6.838
270286AF1-227 GEN2
Solar/Wind Harmer
2.53
270287AF1-227 GEN3
Solar/Wind Harmer
2.53
270578AF1-285 GEN2
Solar/Wind Harmer
0.464
241973AD2-163_GEN1
Solar/Wind Harmer
1.951
270302AB2-170 GEN
Solar/Wind Harmer
7.804
270317AD1-130_GEN
Solar/Wind Harmer
2.992
270520AE2-214 GEN
Solar/Wind Harmer
5.387
970179AG2-119 GEN
Solar/Wind Harmer
6.779
962771AG1-126 GEN
Solar/Wind Harmer
20.876
957201AF2-014 GEN
Solar/Wind Harmer
2.724
270435AC2-044 GEN
Solar/Wind Harmer
1.201
241972AD1-140 GEN
Solar/Wind Harmer
2.566
247607V1-011 GEN
Solar/Wind Harmer
2.224
965051AG1-369 GEN
Solar/Wind Harmer
2.763
270297AD1-101 GEN
Solar/Wind Harmer
1.54
965041AG1-368 GEN
Solar/Wind Harmer
5.367
945631AF1-228 GEN
Solar/Wind Harmer
2.511
270156DARBY CT1
Adder
4.681
270157DARBY CT2
Adder
4.67
270158DARBY CT3
Adder
4.595
963791AG1-232 GEN
Solar/Wind Harmer
6.783
943861AF1-054 GEN
Solar/Wind Harmer
1.926
943851AF1-053 GEN
Solar/Wind Harmer
0.931
270071AF1-092 GEN
Solar/Wind Harmer
7.22
270024AE2-089 GEN
Solar/Wind Harmer
2.252
24729505KEY G4
Adder
3.086
253349AC2-067 GEN
Solar/Wind Harmer
2.345
253400AC2-068 GEN
Solar/Wind Harmer
0.943
961761AG1-017 GEN
Solar/Wind Harmer
0.2
958711AF2-162 GEN
Solar/Wind Harmer
0.471
25306009OHH W.
Adder
1.337
253372AE2-315 SEC3
Adder
0.877
253372AE2-315 SEC3
Adder
0.877
965101AG1-375 GEN
Solar/Wind Harmer
4.621
971347AH1-153 GEN
Solar/Wind Harmer
6.923
971771AH1-392 GEN
Solar/Wind Harmer
4.108
270543AE2-219 C
Solar/Wind Harmer
2.334
945581AF1-223 GEN
Solar/Wind Harmer
2.066
944161AF1-084 GEN
Solar/Wind Harmer
1
971769AH1-391 GEN
Solar/Wind Harmer
4.515
971029AG2-637 GEN
Solar/Wind Harmer
6.767
971673AH1-337 GEN
Solar/Wind Harmer
2.069
960681AF2-359 GEN
Solar/Wind Harmer
1.696
253383AE2-342_GEN
Solar/Wind Harmer
0.396
970115AG2-085 GEN
Solar/Wind Harmer
1.766
274775LINCOLN ;6U
Adder
3.69
274776LINCOLN ;7U
Adder
3.69
274777LINCOLN ;8U
Adder
3.69
274814UNIV PK N;0U
Adder
2.2
274807UNIV PK N;3U
Adder
2.195
274805UNIV PK N;1U
Adder
2.186
274811UNIV PK N;7U
Adder
2.181
972037AH1-567 GEN1
Adder
0.079
274827FISK ;RP
Adder
3.363
972227AH1-698 GEN1
Adder
1.129
274687WILL CNTY;4U
Adder
12.046
274687WILL CNTY;4U
Adder
12.046
274675JOLIET 29;7U
Adder
13.215
274675JOLIET 29;7U
Adder
12.743
274731ELWOOD EC;2P
Adder
7.072
274733ELWOOD EC;3P
Adder
7.072
274735ELWOOD EC;4P
Adder
7.072
274728ELWOOD EC;5P
Adder
7.073
270054AF2-122 C O1
Solar/Wind Helper
0.817
971549AH1-272 GEN
Solar/Wind Harmer
6.317
270475AD2-096_GEN
50/50
7.794
942871AE2-306 GEN
Solar/Wind Harmer
0.905
270391AF1-285 GEN3
Solar/Wind Harmer
0.464
241974AD2-163_GEN2
Solar/Wind Harmer
1.951
270485AE1-090_GEN
Solar/Wind Harmer
0.564
942051AE2-217 GEN
Solar/Wind Harmer
13.946
970065AG2-057 GEN
Solar/Wind Harmer
0.765
970605AG2-385 GEN
Solar/Wind Harmer
3.824
241955AC1-078 GEN
Solar/Wind Harmer
4.991
970153AG2-106 GEN
Solar/Wind Harmer
9.103
270491AE1-102 GEN2
Solar/Wind Harmer
0.781
958091AF2-103 GEN
Solar/Wind Harmer
0.091
270191TR4_S_V150
Solar/Wind Harmer
1.66
270247TR4_N_V136
Solar/Wind Harmer
0.471
270258AD1-119 GEN
Solar/Wind Harmer
1.494
959331AF2-224 GEN
Solar/Wind Harmer
5.303
965021AG1-366 GEN
Solar/Wind Harmer
1.233
270044AE2-322 C
Solar/Wind Harmer
0.69
270404AC1-167 GEN
Solar/Wind Harmer
0.574
270588AE1-091_GEN
Solar/Wind Harmer
5.492
270043AE2-236 GEN
Solar/Wind Harmer
2.708
253338AC1-165 GEN
Solar/Wind Harmer
0.525
253333AC1-068 GEN
Solar/Wind Harmer
0.506
970031AG2-029 GEN
Solar/Wind Harmer
14.483
971617AH1-308 GEN
Solar/Wind Harmer
2.79
944531AF1-118 GEN
Solar/Wind Harmer
16.782
270541AE2-072 C
Solar/Wind Harmer
2.158
962031AG1-047 GEN
Solar/Wind Harmer
1.409
957741AF2-068 GEN
Solar/Wind Harmer
6.995
253303V4-073 C
Solar/Wind Harmer
0.054
253370AE2-315 SEC1
Adder
0.927
253371AE2-315 SEC2
Adder
0.877
970349AG2-230 GEN
Solar/Wind Harmer
6.923
247643Z2-116 C
Solar/Wind Harmer
0.032
945111AF1-176 GEN
Solar/Wind Harmer
2.586
24642205MAYFLWER
Adder
0.289
970513AG2-328 GEN
Solar/Wind Harmer
8.044
970517AG2-330 GEN
Solar/Wind Harmer
7.296
24441205WTRV SLR C
Solar/Wind Harmer
0.061
247604X1-042
Adder
0.186
946031AF1-268 GEN
Solar/Wind Harmer
3.707
958821AF2-173 GEN
Solar/Wind Harmer
6.167
270004AE1-209 GEN
Solar/Wind Harmer
2.407
274752CRETE EC ;2U
Adder
3.605
274753CRETE EC ;3U
Adder
3.605
274772LINCOLN ;3U
Adder
3.69
274724RIVER EC ;11
Adder
7.742
274802UNIV PARK;5U
Adder
2.528
274826FISK ;BP
Adder
4.745
274800UNIV PARK;3U
Adder
2.525
972038AH1-567 GEN2
Adder
0.158
972228AH1-698 GEN2
Adder
1.603
274676JOLIET 29;8U
Adder
12.743
274729ELWOOD EC;1P
Adder
7.072
274730ELWOOD EC;6P
Adder
7.073
274734ELWOOD EC;8P
Adder
7.073
274736ELWOOD EC;9P
Adder
7.073
270466AD2-091
50/50
5.416
270471AD2-092_GEN
Solar/Wind Harmer
4.871
938701AE1-092 GEN
Solar/Wind Harmer
21.927
964601AG1-323 GEN
Solar/Wind Harmer
3.191
964601AG1-323 GEN
Solar/Wind Harmer
1.484
270224U2-072_GEN2
Solar/Wind Harmer
1.972
270227U2-072_GEN3
Solar/Wind Harmer
1.972
270228U2-072_GEN4
Solar/Wind Harmer
1.972
270231U2-072_GEN5
Solar/Wind Harmer
1.972
946101AF1-275 GEN
Solar/Wind Harmer
1.344
241960AC2-195 GEN
Solar/Wind Harmer
2.356
971201AH1-060 GEN
Solar/Wind Harmer
1.53
970077AG2-063 GEN
Solar/Wind Harmer
3.824
253378AE2-206_GEN
Solar/Wind Harmer
2.393
276820AF1-078_GEN
Solar/Wind Harmer
1.063
25326509SID D
Adder
0.831
246938BC-WTG3
Solar/Wind Harmer
2.391
246937BC-WTG2
Solar/Wind Harmer
2.35
270007AE1-245 C
Solar/Wind Harmer
3.337
942801AE2-298 GEN
Solar/Wind Harmer
0.85
970611AG2-400 GEN
Solar/Wind Harmer
5.303
270518AE2-148 GEN
Solar/Wind Harmer
6.27
942861AE2-305 GEN
Solar/Wind Harmer
3.903
25326109MON D
Adder
0.652
25322209TAIT E
Adder
4.67
25322209TAIT E
Adder
4.565
942221AE2-234 GEN
Solar/Wind Harmer
0.35
247620Y3-023
Adder
0.215
270201AC2-176 GEN
Solar/Wind Harmer
2.397
944541AF1-119 GEN
Solar/Wind Harmer
1.949
960971AF2-388 GEN
Solar/Wind Harmer
5.087
247621Y3-024
Adder
0.112
253370AE2-315 SEC1
Adder
0.927
964611AG1-324 GEN
Solar/Wind Harmer
0.545
964611AG1-324 GEN
Solar/Wind Harmer
0.242
270216AD2-079_GEN
Solar/Wind Harmer
0.279
960981AF2-389 GEN
Solar/Wind Harmer
0.69
957891AF2-083 GEN
Solar/Wind Harmer
1.539
970883AG2-550 GEN
Solar/Wind Harmer
4.558
970885AG2-551 GEN
Solar/Wind Harmer
1.06
961051AF2-396 GEN
Solar/Wind Harmer
7.227
961051AF2-396 GEN
Solar/Wind Harmer
3.361
270526AF1-158 GEN
Solar/Wind Harmer
2.056
24441505OLIV SLR
Solar/Wind Harmer
0.06
970321AG2-212 GEN
Solar/Wind Harmer
8.044
270599AE1-208 GEN
Solar/Wind Harmer
3.671
270031AE2-169
Solar/Wind Harmer
3.671
965681AG1-436 GEN
Solar/Wind Harmer
5.612
965791AG1-447 GEN
Solar/Wind Harmer
2.871
970825AG2-519 GEN
Solar/Wind Harmer
4.662
960441AF2-335 GEN
Solar/Wind Harmer
4.415
274770LINCOLN ;1U
Adder
3.69
274771LINCOLN ;2U
Adder
3.69
274808UNIV PK N;4U
Adder
2.171
274803UNIV PARK;6U
Adder
2.528
972259AH1-714 GEN
Adder
8.249
274674JOLIET 9 ;6U
Adder
6.626
NYPJM->LTFIMP_NY
CLTF
1.305
LGEELTFEXP_LGEE->PJM
CLTF
2.295
WECLTFEXP_WEC->PJM
CLTF
1.59
AG2-052LTFEXP_AG2-052->PJM
LTF
0.1
AH1-155LTFEXP_AH1-155->PJM
LTF
0.151
CPLELTFEXP_CPLE->PJM
CLTF
0.349
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.837
LAGNLTFEXP_LAGN->PJM
CLTF
5.116
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.348
TVALTFEXP_TVA->PJM
CLTF
2.374
CBM West 1LTFEXP_CBM-W1->PJM
CBM
56.388
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.568
MECLTFEXP_MEC->PJM
CLTF
6.327
SIGELTFEXP_SIGE->PJM
CLTF
0.182

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P4_#9729_05MALIS 138_M1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9729_05MALIS 138_M1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.05 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1747.91
MW Contribution:9.1
Bus #Bus NameTypeMW Contribution
270349AD2-093_GEN
Solar/Wind Harmer
4.868
971995AH1-542 GEN
Solar/Wind Harmer
11.766
270223U2-072_GEN1
Solar/Wind Harmer
1.971
270578AF1-285 GEN2
Solar/Wind Harmer
1.206
270391AF1-285 GEN3
Solar/Wind Harmer
1.206
270462AD2-086
Solar/Wind Harmer
6.488
241813AF1-122_GEN
Solar/Wind Harmer
4.895
970593AG2-378 GEN
Solar/Wind Harmer
1.415
962761AG1-125 GEN
Solar/Wind Harmer
20.865
970149AG2-104 GEN
Solar/Wind Harmer
25.768
970155AG2-107 GEN
Solar/Wind Harmer
9.098
246936BC-WTG1
Solar/Wind Harmer
2.349
270489AE1-102 GEN1
Solar/Wind Harmer
0.78
965421AG1-410 GEN
Solar/Wind Harmer
17.806
247521TR3_G114
Solar/Wind Harmer
1.86
270246TR4_N_V150
Solar/Wind Harmer
0.47
24695305TIMB G C
Solar/Wind Harmer
3.01
965011AG1-365 GEN
Solar/Wind Harmer
5.301
270159DARBY CT4
Adder
4.605
944231AF1-091 GEN
Solar/Wind Harmer
1.84
253343AC1-166 GEN
Solar/Wind Harmer
0.525
253325AC1-069 GEN
Solar/Wind Harmer
0.506
960071AF2-298 GEN
Solar/Wind Harmer
2.397
25326309TAIT D
Adder
0.525
270063AE2-323 C
Solar/Wind Harmer
1.055
965651AG1-433 GEN
Solar/Wind Harmer
2.542
24639705ELKHART HY
Adder
0.071
253370AE2-315 SEC1
Adder
0.926
253371AE2-315 SEC2
Adder
0.876
958861AF2-177 GEN
Solar/Wind Harmer
5.048
247536S-71 GEN
Solar/Wind Harmer
1.863
945111AF1-176 GEN
Solar/Wind Harmer
8.154
270505AE1-170 C O1
Solar/Wind Harmer
6.835
945371AF1-202 GEN
Solar/Wind Harmer
3.177
270449AD2-020 GEN
Solar/Wind Harmer
1.272
943021AE2-325 GEN
Solar/Wind Harmer
1.653
970245AG2-165 GEN
Solar/Wind Harmer
8.04
970825AG2-519 GEN
Solar/Wind Harmer
1.04
270005AE1-210 C O1
Solar/Wind Harmer
2.406
965031AG1-367 GEN
Solar/Wind Harmer
4.403
970373AG2-245 GEN
Solar/Wind Harmer
9.243
274751CRETE EC ;1U
Adder
3.603
274754CRETE EC ;4U
Adder
3.603
274773LINCOLN ;4U
Adder
3.688
274774LINCOLN ;5U
Adder
3.688
274723RIVER EC ;12
Adder
7.829
274812UNIV PK N;8U
Adder
2.18
274801UNIV PARK;4U
Adder
2.524
274676JOLIET 29;8U
Adder
13.208
274674JOLIET 9 ;6U
Adder
6.622
274732ELWOOD EC;7P
Adder
7.069
270036AE2-216 BAT
50/50
5.955
270284AF1-227 GEN1
Solar/Wind Harmer
6.834
270286AF1-227 GEN2
Solar/Wind Harmer
2.528
270287AF1-227 GEN3
Solar/Wind Harmer
2.528
270578AF1-285 GEN2
Solar/Wind Harmer
0.464
241973AD2-163_GEN1
Solar/Wind Harmer
1.95
270302AB2-170 GEN
Solar/Wind Harmer
7.799
270317AD1-130_GEN
Solar/Wind Harmer
2.99
270520AE2-214 GEN
Solar/Wind Harmer
5.383
970179AG2-119 GEN
Solar/Wind Harmer
6.775
962771AG1-126 GEN
Solar/Wind Harmer
20.865
957201AF2-014 GEN
Solar/Wind Harmer
2.722
270435AC2-044 GEN
Solar/Wind Harmer
1.201
241972AD1-140 GEN
Solar/Wind Harmer
2.565
247607V1-011 GEN
Solar/Wind Harmer
2.223
965051AG1-369 GEN
Solar/Wind Harmer
2.761
270297AD1-101 GEN
Solar/Wind Harmer
1.539
965041AG1-368 GEN
Solar/Wind Harmer
5.365
945631AF1-228 GEN
Solar/Wind Harmer
2.51
270156DARBY CT1
Adder
4.68
270157DARBY CT2
Adder
4.668
270158DARBY CT3
Adder
4.594
963791AG1-232 GEN
Solar/Wind Harmer
6.779
943861AF1-054 GEN
Solar/Wind Harmer
1.923
943851AF1-053 GEN
Solar/Wind Harmer
0.929
270071AF1-092 GEN
Solar/Wind Harmer
7.217
270024AE2-089 GEN
Solar/Wind Harmer
2.251
24729505KEY G4
Adder
3.085
253349AC2-067 GEN
Solar/Wind Harmer
2.344
253400AC2-068 GEN
Solar/Wind Harmer
0.943
961761AG1-017 GEN
Solar/Wind Harmer
0.199
958711AF2-162 GEN
Solar/Wind Harmer
0.471
25306009OHH W.
Adder
1.337
253372AE2-315 SEC3
Adder
0.876
253372AE2-315 SEC3
Adder
0.876
965101AG1-375 GEN
Solar/Wind Harmer
4.618
971347AH1-153 GEN
Solar/Wind Harmer
6.92
971771AH1-392 GEN
Solar/Wind Harmer
4.106
270543AE2-219 C
Solar/Wind Harmer
2.333
945581AF1-223 GEN
Solar/Wind Harmer
2.065
944161AF1-084 GEN
Solar/Wind Harmer
1
971769AH1-391 GEN
Solar/Wind Harmer
4.513
971029AG2-637 GEN
Solar/Wind Harmer
6.764
971673AH1-337 GEN
Solar/Wind Harmer
2.068
960681AF2-359 GEN
Solar/Wind Harmer
1.695
253383AE2-342_GEN
Solar/Wind Harmer
0.395
970115AG2-085 GEN
Solar/Wind Harmer
1.765
274775LINCOLN ;6U
Adder
3.688
274776LINCOLN ;7U
Adder
3.688
274777LINCOLN ;8U
Adder
3.688
274814UNIV PK N;0U
Adder
2.199
274807UNIV PK N;3U
Adder
2.194
274805UNIV PK N;1U
Adder
2.185
274811UNIV PK N;7U
Adder
2.18
972037AH1-567 GEN1
Adder
0.079
274827FISK ;RP
Adder
3.361
972227AH1-698 GEN1
Adder
1.128
274687WILL CNTY;4U
Adder
12.041
274687WILL CNTY;4U
Adder
12.041
274675JOLIET 29;7U
Adder
13.208
274675JOLIET 29;7U
Adder
12.736
274731ELWOOD EC;2P
Adder
7.069
274733ELWOOD EC;3P
Adder
7.069
274735ELWOOD EC;4P
Adder
7.069
274728ELWOOD EC;5P
Adder
7.069
270054AF2-122 C O1
Solar/Wind Helper
0.816
971549AH1-272 GEN
Solar/Wind Harmer
6.314
270475AD2-096_GEN
50/50
7.79
942871AE2-306 GEN
Solar/Wind Harmer
0.904
270391AF1-285 GEN3
Solar/Wind Harmer
0.464
241974AD2-163_GEN2
Solar/Wind Harmer
1.95
270485AE1-090_GEN
Solar/Wind Harmer
0.564
942051AE2-217 GEN
Solar/Wind Harmer
13.937
970065AG2-057 GEN
Solar/Wind Harmer
0.765
970605AG2-385 GEN
Solar/Wind Harmer
3.821
241955AC1-078 GEN
Solar/Wind Harmer
4.989
970153AG2-106 GEN
Solar/Wind Harmer
9.098
270491AE1-102 GEN2
Solar/Wind Harmer
0.78
958091AF2-103 GEN
Solar/Wind Harmer
0.091
270191TR4_S_V150
Solar/Wind Harmer
1.659
270247TR4_N_V136
Solar/Wind Harmer
0.47
270258AD1-119 GEN
Solar/Wind Harmer
1.494
959331AF2-224 GEN
Solar/Wind Harmer
5.301
965021AG1-366 GEN
Solar/Wind Harmer
1.233
270044AE2-322 C
Solar/Wind Harmer
0.689
270404AC1-167 GEN
Solar/Wind Harmer
0.574
270588AE1-091_GEN
Solar/Wind Harmer
5.49
270043AE2-236 GEN
Solar/Wind Harmer
2.707
253338AC1-165 GEN
Solar/Wind Harmer
0.525
253333AC1-068 GEN
Solar/Wind Harmer
0.506
970031AG2-029 GEN
Solar/Wind Harmer
14.476
971617AH1-308 GEN
Solar/Wind Harmer
2.788
944531AF1-118 GEN
Solar/Wind Harmer
16.774
270541AE2-072 C
Solar/Wind Harmer
2.157
962031AG1-047 GEN
Solar/Wind Harmer
1.409
957741AF2-068 GEN
Solar/Wind Harmer
6.991
253303V4-073 C
Solar/Wind Harmer
0.054
253370AE2-315 SEC1
Adder
0.926
253371AE2-315 SEC2
Adder
0.876
970349AG2-230 GEN
Solar/Wind Harmer
6.92
247643Z2-116 C
Solar/Wind Harmer
0.032
945111AF1-176 GEN
Solar/Wind Harmer
2.584
24642205MAYFLWER
Adder
0.289
970513AG2-328 GEN
Solar/Wind Harmer
8.04
970517AG2-330 GEN
Solar/Wind Harmer
7.292
24441205WTRV SLR C
Solar/Wind Harmer
0.061
247604X1-042
Adder
0.186
946031AF1-268 GEN
Solar/Wind Harmer
3.705
958821AF2-173 GEN
Solar/Wind Harmer
6.164
270004AE1-209 GEN
Solar/Wind Harmer
2.406
274752CRETE EC ;2U
Adder
3.603
274753CRETE EC ;3U
Adder
3.603
274772LINCOLN ;3U
Adder
3.688
274724RIVER EC ;11
Adder
7.738
274802UNIV PARK;5U
Adder
2.527
274826FISK ;BP
Adder
4.742
274800UNIV PARK;3U
Adder
2.524
972038AH1-567 GEN2
Adder
0.158
972228AH1-698 GEN2
Adder
1.602
274676JOLIET 29;8U
Adder
12.736
274729ELWOOD EC;1P
Adder
7.069
274730ELWOOD EC;6P
Adder
7.069
274734ELWOOD EC;8P
Adder
7.069
274736ELWOOD EC;9P
Adder
7.069
270466AD2-091
50/50
5.413
270471AD2-092_GEN
Solar/Wind Harmer
4.868
938701AE1-092 GEN
Solar/Wind Harmer
21.914
964601AG1-323 GEN
Solar/Wind Harmer
3.189
964601AG1-323 GEN
Solar/Wind Harmer
1.483
270224U2-072_GEN2
Solar/Wind Harmer
1.971
270227U2-072_GEN3
Solar/Wind Harmer
1.971
270228U2-072_GEN4
Solar/Wind Harmer
1.971
270231U2-072_GEN5
Solar/Wind Harmer
1.971
946101AF1-275 GEN
Solar/Wind Harmer
1.343
241960AC2-195 GEN
Solar/Wind Harmer
2.355
971201AH1-060 GEN
Solar/Wind Harmer
1.53
970077AG2-063 GEN
Solar/Wind Harmer
3.821
253378AE2-206_GEN
Solar/Wind Harmer
2.391
276820AF1-078_GEN
Solar/Wind Harmer
1.062
25326509SID D
Adder
0.831
246938BC-WTG3
Solar/Wind Harmer
2.389
246937BC-WTG2
Solar/Wind Harmer
2.349
270007AE1-245 C
Solar/Wind Harmer
3.335
942801AE2-298 GEN
Solar/Wind Harmer
0.849
970611AG2-400 GEN
Solar/Wind Harmer
5.301
270518AE2-148 GEN
Solar/Wind Harmer
6.267
942861AE2-305 GEN
Solar/Wind Harmer
3.897
25326109MON D
Adder
0.651
25322209TAIT E
Adder
4.667
25322209TAIT E
Adder
4.562
942221AE2-234 GEN
Solar/Wind Harmer
0.349
247620Y3-023
Adder
0.215
270201AC2-176 GEN
Solar/Wind Harmer
2.396
944541AF1-119 GEN
Solar/Wind Harmer
1.948
960971AF2-388 GEN
Solar/Wind Harmer
5.085
247621Y3-024
Adder
0.112
253370AE2-315 SEC1
Adder
0.926
964611AG1-324 GEN
Solar/Wind Harmer
0.545
964611AG1-324 GEN
Solar/Wind Harmer
0.242
270216AD2-079_GEN
Solar/Wind Harmer
0.279
957891AF2-083 GEN
Solar/Wind Harmer
1.538
960981AF2-389 GEN
Solar/Wind Harmer
0.689
970883AG2-550 GEN
Solar/Wind Harmer
4.556
970885AG2-551 GEN
Solar/Wind Harmer
1.06
961051AF2-396 GEN
Solar/Wind Harmer
7.223
961051AF2-396 GEN
Solar/Wind Harmer
3.36
270526AF1-158 GEN
Solar/Wind Harmer
2.055
24441505OLIV SLR
Solar/Wind Harmer
0.06
970321AG2-212 GEN
Solar/Wind Harmer
8.04
270599AE1-208 GEN
Solar/Wind Harmer
3.669
270031AE2-169
Solar/Wind Harmer
3.669
965681AG1-436 GEN
Solar/Wind Harmer
5.609
965791AG1-447 GEN
Solar/Wind Harmer
2.87
970825AG2-519 GEN
Solar/Wind Harmer
4.659
960441AF2-335 GEN
Solar/Wind Harmer
4.412
274770LINCOLN ;1U
Adder
3.688
274771LINCOLN ;2U
Adder
3.688
274808UNIV PK N;4U
Adder
2.17
274803UNIV PARK;6U
Adder
2.527
972259AH1-714 GEN
Adder
8.245
274674JOLIET 9 ;6U
Adder
6.622
NYPJM->LTFIMP_NY
CLTF
1.304
LGEELTFEXP_LGEE->PJM
CLTF
2.294
WECLTFEXP_WEC->PJM
CLTF
1.589
AG2-052LTFEXP_AG2-052->PJM
LTF
0.1
AH1-155LTFEXP_AH1-155->PJM
LTF
0.15
CPLELTFEXP_CPLE->PJM
CLTF
0.349
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.818
LAGNLTFEXP_LAGN->PJM
CLTF
5.114
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.347
TVALTFEXP_TVA->PJM
CLTF
2.373
CBM West 1LTFEXP_CBM-W1->PJM
CBM
56.361
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.564
MECLTFEXP_MEC->PJM
CLTF
6.323
SIGELTFEXP_SIGE->PJM
CLTF
0.181

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P2-2_#7222_05MALIS 765_1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:112.44 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1584.27
MW Contribution:9.06
Bus #Bus NameTypeMW Contribution
270036AE2-216 BAT
50/50
5.929
270284AF1-227 GEN1
Solar/Wind Harmer
6.804
270286AF1-227 GEN2
Solar/Wind Harmer
2.517
270287AF1-227 GEN3
Solar/Wind Harmer
2.517
270578AF1-285 GEN2
Solar/Wind Harmer
0.462
241973AD2-163_GEN1
Solar/Wind Harmer
1.939
270302AB2-170 GEN
Solar/Wind Harmer
7.765
270317AD1-130_GEN
Solar/Wind Harmer
2.977
270520AE2-214 GEN
Solar/Wind Harmer
5.355
970179AG2-119 GEN
Solar/Wind Harmer
6.746
962771AG1-126 GEN
Solar/Wind Harmer
20.775
957201AF2-014 GEN
Solar/Wind Harmer
2.711
270435AC2-044 GEN
Solar/Wind Harmer
1.195
241972AD1-140 GEN
Solar/Wind Harmer
2.551
247607V1-011 GEN
Solar/Wind Harmer
2.214
965051AG1-369 GEN
Solar/Wind Harmer
2.75
270297AD1-101 GEN
Solar/Wind Harmer
1.533
965041AG1-368 GEN
Solar/Wind Harmer
5.342
945631AF1-228 GEN
Solar/Wind Harmer
2.501
270156DARBY CT1
Adder
4.664
270157DARBY CT2
Adder
4.653
270158DARBY CT3
Adder
4.578
963791AG1-232 GEN
Solar/Wind Harmer
6.751
943861AF1-054 GEN
Solar/Wind Harmer
1.9
943851AF1-053 GEN
Solar/Wind Harmer
0.918
270071AF1-092 GEN
Solar/Wind Harmer
7.187
270024AE2-089 GEN
Solar/Wind Harmer
2.242
24729505KEY G4
Adder
3.072
253349AC2-067 GEN
Solar/Wind Harmer
2.334
253400AC2-068 GEN
Solar/Wind Harmer
0.939
961761AG1-017 GEN
Solar/Wind Harmer
0.199
958711AF2-162 GEN
Solar/Wind Harmer
0.469
25306009OHH W.
Adder
1.331
253372AE2-315 SEC3
Adder
0.873
253372AE2-315 SEC3
Adder
0.873
965101AG1-375 GEN
Solar/Wind Harmer
4.6
971347AH1-153 GEN
Solar/Wind Harmer
6.892
971771AH1-392 GEN
Solar/Wind Harmer
4.09
270543AE2-219 C
Solar/Wind Harmer
2.323
945581AF1-223 GEN
Solar/Wind Harmer
2.057
944161AF1-084 GEN
Solar/Wind Harmer
0.996
971769AH1-391 GEN
Solar/Wind Harmer
4.495
971029AG2-637 GEN
Solar/Wind Harmer
6.737
971673AH1-337 GEN
Solar/Wind Harmer
2.06
960681AF2-359 GEN
Solar/Wind Harmer
1.688
970115AG2-085 GEN
Solar/Wind Harmer
1.758
253383AE2-342_GEN
Solar/Wind Harmer
0.388
274775LINCOLN ;6U
Adder
3.673
274776LINCOLN ;7U
Adder
3.673
274777LINCOLN ;8U
Adder
3.673
274814UNIV PK N;0U
Adder
2.19
274807UNIV PK N;3U
Adder
2.185
274805UNIV PK N;1U
Adder
2.176
274811UNIV PK N;7U
Adder
2.171
972037AH1-567 GEN1
Adder
0.079
274827FISK ;RP
Adder
3.347
972227AH1-698 GEN1
Adder
1.124
270054AF2-122 C O1
Solar/Wind Helper
0.806
971549AH1-272 GEN
Solar/Wind Harmer
6.289
270475AD2-096_GEN
50/50
7.755
942871AE2-306 GEN
Solar/Wind Harmer
0.9
270391AF1-285 GEN3
Solar/Wind Harmer
0.462
241974AD2-163_GEN2
Solar/Wind Harmer
1.939
270485AE1-090_GEN
Solar/Wind Harmer
0.562
942051AE2-217 GEN
Solar/Wind Harmer
13.864
970065AG2-057 GEN
Solar/Wind Harmer
0.762
970605AG2-385 GEN
Solar/Wind Harmer
3.797
241955AC1-078 GEN
Solar/Wind Harmer
4.97
970153AG2-106 GEN
Solar/Wind Harmer
9.059
270491AE1-102 GEN2
Solar/Wind Harmer
0.777
958091AF2-103 GEN
Solar/Wind Harmer
0.09
270191TR4_S_V150
Solar/Wind Harmer
1.652
270247TR4_N_V136
Solar/Wind Harmer
0.468
270258AD1-119 GEN
Solar/Wind Harmer
1.487
959331AF2-224 GEN
Solar/Wind Harmer
5.279
965021AG1-366 GEN
Solar/Wind Harmer
1.228
270044AE2-322 C
Solar/Wind Harmer
0.687
270404AC1-167 GEN
Solar/Wind Harmer
0.572
270588AE1-091_GEN
Solar/Wind Harmer
5.47
270043AE2-236 GEN
Solar/Wind Harmer
2.696
253338AC1-165 GEN
Solar/Wind Harmer
0.523
253333AC1-068 GEN
Solar/Wind Harmer
0.505
970031AG2-029 GEN
Solar/Wind Harmer
14.416
971617AH1-308 GEN
Solar/Wind Harmer
2.777
944531AF1-118 GEN
Solar/Wind Harmer
16.706
270541AE2-072 C
Solar/Wind Harmer
2.148
962031AG1-047 GEN
Solar/Wind Harmer
1.403
957741AF2-068 GEN
Solar/Wind Harmer
6.963
253303V4-073 C
Solar/Wind Harmer
0.053
253370AE2-315 SEC1
Adder
0.923
253371AE2-315 SEC2
Adder
0.873
970349AG2-230 GEN
Solar/Wind Harmer
6.892
247643Z2-116 C
Solar/Wind Harmer
0.032
945111AF1-176 GEN
Solar/Wind Harmer
2.574
24642205MAYFLWER
Adder
0.288
970513AG2-328 GEN
Solar/Wind Harmer
8.007
970517AG2-330 GEN
Solar/Wind Harmer
7.263
24441205WTRV SLR C
Solar/Wind Harmer
0.06
247604X1-042
Adder
0.185
946031AF1-268 GEN
Solar/Wind Harmer
3.69
958821AF2-173 GEN
Solar/Wind Harmer
6.139
270004AE1-209 GEN
Solar/Wind Harmer
2.397
274752CRETE EC ;2U
Adder
3.589
274753CRETE EC ;3U
Adder
3.589
274772LINCOLN ;3U
Adder
3.673
274724RIVER EC ;11
Adder
7.706
274802UNIV PARK;5U
Adder
2.517
274826FISK ;BP
Adder
4.723
274800UNIV PARK;3U
Adder
2.514
972038AH1-567 GEN2
Adder
0.157
972228AH1-698 GEN2
Adder
1.596
270349AD2-093_GEN
Solar/Wind Harmer
4.846
971995AH1-542 GEN
Solar/Wind Harmer
11.714
270223U2-072_GEN1
Solar/Wind Harmer
1.963
270578AF1-285 GEN2
Solar/Wind Harmer
1.2
270391AF1-285 GEN3
Solar/Wind Harmer
1.2
270462AD2-086
Solar/Wind Harmer
6.46
241813AF1-122_GEN
Solar/Wind Harmer
4.874
970593AG2-378 GEN
Solar/Wind Harmer
1.406
962761AG1-125 GEN
Solar/Wind Harmer
20.775
970149AG2-104 GEN
Solar/Wind Harmer
25.657
970155AG2-107 GEN
Solar/Wind Harmer
9.059
246936BC-WTG1
Solar/Wind Harmer
2.339
270489AE1-102 GEN1
Solar/Wind Harmer
0.777
965421AG1-410 GEN
Solar/Wind Harmer
17.731
247521TR3_G114
Solar/Wind Harmer
1.852
270246TR4_N_V150
Solar/Wind Harmer
0.468
24695305TIMB G C
Solar/Wind Harmer
2.998
965011AG1-365 GEN
Solar/Wind Harmer
5.279
270159DARBY CT4
Adder
4.59
944231AF1-091 GEN
Solar/Wind Harmer
1.832
253343AC1-166 GEN
Solar/Wind Harmer
0.523
253325AC1-069 GEN
Solar/Wind Harmer
0.505
960071AF2-298 GEN
Solar/Wind Harmer
2.387
25326309TAIT D
Adder
0.523
270063AE2-323 C
Solar/Wind Harmer
1.051
965651AG1-433 GEN
Solar/Wind Harmer
2.532
24639705ELKHART HY
Adder
0.071
253370AE2-315 SEC1
Adder
0.923
253371AE2-315 SEC2
Adder
0.873
958861AF2-177 GEN
Solar/Wind Harmer
5.028
247536S-71 GEN
Solar/Wind Harmer
1.856
945111AF1-176 GEN
Solar/Wind Harmer
8.121
270505AE1-170 C O1
Solar/Wind Harmer
6.807
945371AF1-202 GEN
Solar/Wind Harmer
3.165
270449AD2-020 GEN
Solar/Wind Harmer
1.267
943021AE2-325 GEN
Solar/Wind Harmer
1.646
970245AG2-165 GEN
Solar/Wind Harmer
8.007
970825AG2-519 GEN
Solar/Wind Harmer
1.035
270005AE1-210 C O1
Solar/Wind Harmer
2.397
965031AG1-367 GEN
Solar/Wind Harmer
4.385
970373AG2-245 GEN
Solar/Wind Harmer
9.206
274751CRETE EC ;1U
Adder
3.589
274754CRETE EC ;4U
Adder
3.589
274773LINCOLN ;4U
Adder
3.673
274774LINCOLN ;5U
Adder
3.673
274723RIVER EC ;12
Adder
7.798
274812UNIV PK N;8U
Adder
2.171
274801UNIV PARK;4U
Adder
2.514
270466AD2-091
50/50
5.39
270471AD2-092_GEN
Solar/Wind Harmer
4.846
938701AE1-092 GEN
Solar/Wind Harmer
21.808
964601AG1-323 GEN
Solar/Wind Harmer
3.173
964601AG1-323 GEN
Solar/Wind Harmer
1.476
270224U2-072_GEN2
Solar/Wind Harmer
1.963
270227U2-072_GEN3
Solar/Wind Harmer
1.963
270228U2-072_GEN4
Solar/Wind Harmer
1.963
270231U2-072_GEN5
Solar/Wind Harmer
1.963
946101AF1-275 GEN
Solar/Wind Harmer
1.336
241960AC2-195 GEN
Solar/Wind Harmer
2.345
971201AH1-060 GEN
Solar/Wind Harmer
1.523
970077AG2-063 GEN
Solar/Wind Harmer
3.797
253378AE2-206_GEN
Solar/Wind Harmer
2.379
276820AF1-078_GEN
Solar/Wind Harmer
1.057
25326509SID D
Adder
0.827
246938BC-WTG3
Solar/Wind Harmer
2.379
246937BC-WTG2
Solar/Wind Harmer
2.339
270007AE1-245 C
Solar/Wind Harmer
3.321
942801AE2-298 GEN
Solar/Wind Harmer
0.846
970611AG2-400 GEN
Solar/Wind Harmer
5.279
270518AE2-148 GEN
Solar/Wind Harmer
6.245
942861AE2-305 GEN
Solar/Wind Harmer
3.849
25326109MON D
Adder
0.648
25322209TAIT E
Adder
4.647
25322209TAIT E
Adder
4.543
942221AE2-234 GEN
Solar/Wind Harmer
0.348
247620Y3-023
Adder
0.214
270201AC2-176 GEN
Solar/Wind Harmer
2.386
944541AF1-119 GEN
Solar/Wind Harmer
1.941
960971AF2-388 GEN
Solar/Wind Harmer
5.064
247621Y3-024
Adder
0.111
253370AE2-315 SEC1
Adder
0.923
964611AG1-324 GEN
Solar/Wind Harmer
0.542
964611AG1-324 GEN
Solar/Wind Harmer
0.241
270216AD2-079_GEN
Solar/Wind Harmer
0.278
960981AF2-389 GEN
Solar/Wind Harmer
0.686
957891AF2-083 GEN
Solar/Wind Harmer
1.532
970883AG2-550 GEN
Solar/Wind Harmer
4.537
970885AG2-551 GEN
Solar/Wind Harmer
1.055
961051AF2-396 GEN
Solar/Wind Harmer
7.194
961051AF2-396 GEN
Solar/Wind Harmer
3.346
270526AF1-158 GEN
Solar/Wind Harmer
2.047
24441505OLIV SLR
Solar/Wind Harmer
0.06
970321AG2-212 GEN
Solar/Wind Harmer
8.007
270599AE1-208 GEN
Solar/Wind Harmer
3.654
270031AE2-169
Solar/Wind Harmer
3.654
965681AG1-436 GEN
Solar/Wind Harmer
5.586
965791AG1-447 GEN
Solar/Wind Harmer
2.858
970825AG2-519 GEN
Solar/Wind Harmer
4.641
960441AF2-335 GEN
Solar/Wind Harmer
4.395
274770LINCOLN ;1U
Adder
3.673
274771LINCOLN ;2U
Adder
3.673
274808UNIV PK N;4U
Adder
2.161
274803UNIV PARK;6U
Adder
2.517
972259AH1-714 GEN
Adder
8.212
NYPJM->LTFIMP_NY
CLTF
1.299
LGEELTFEXP_LGEE->PJM
CLTF
2.285
WECLTFEXP_WEC->PJM
CLTF
1.583
AG2-052LTFEXP_AG2-052->PJM
LTF
0.1
AH1-155LTFEXP_AH1-155->PJM
LTF
0.15
CPLELTFEXP_CPLE->PJM
CLTF
0.348
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.662
LAGNLTFEXP_LAGN->PJM
CLTF
5.094
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.339
TVALTFEXP_TVA->PJM
CLTF
2.364
CBM West 1LTFEXP_CBM-W1->PJM
CBM
56.137
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.529
MECLTFEXP_MEC->PJM
CLTF
6.298
SIGELTFEXP_SIGE->PJM
CLTF
0.181

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P4_#7222_05MALIS 765_D_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7222_05MALIS 765_D_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.42 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1584.05
MW Contribution:9.06
Bus #Bus NameTypeMW Contribution
270475AD2-096_GEN
50/50
7.755
942871AE2-306 GEN
Solar/Wind Harmer
0.9
270391AF1-285 GEN3
Solar/Wind Harmer
0.462
241974AD2-163_GEN2
Solar/Wind Harmer
1.939
270485AE1-090_GEN
Solar/Wind Harmer
0.562
942051AE2-217 GEN
Solar/Wind Harmer
13.864
970065AG2-057 GEN
Solar/Wind Harmer
0.762
970605AG2-385 GEN
Solar/Wind Harmer
3.797
241955AC1-078 GEN
Solar/Wind Harmer
4.97
970153AG2-106 GEN
Solar/Wind Harmer
9.059
270491AE1-102 GEN2
Solar/Wind Harmer
0.777
958091AF2-103 GEN
Solar/Wind Harmer
0.09
270191TR4_S_V150
Solar/Wind Harmer
1.652
270247TR4_N_V136
Solar/Wind Harmer
0.468
270258AD1-119 GEN
Solar/Wind Harmer
1.487
959331AF2-224 GEN
Solar/Wind Harmer
5.279
965021AG1-366 GEN
Solar/Wind Harmer
1.228
270044AE2-322 C
Solar/Wind Harmer
0.687
270404AC1-167 GEN
Solar/Wind Harmer
0.572
270588AE1-091_GEN
Solar/Wind Harmer
5.47
270043AE2-236 GEN
Solar/Wind Harmer
2.696
253338AC1-165 GEN
Solar/Wind Harmer
0.523
253333AC1-068 GEN
Solar/Wind Harmer
0.505
970031AG2-029 GEN
Solar/Wind Harmer
14.416
971617AH1-308 GEN
Solar/Wind Harmer
2.777
944531AF1-118 GEN
Solar/Wind Harmer
16.706
270541AE2-072 C
Solar/Wind Harmer
2.148
962031AG1-047 GEN
Solar/Wind Harmer
1.403
957741AF2-068 GEN
Solar/Wind Harmer
6.963
253303V4-073 C
Solar/Wind Harmer
0.053
253370AE2-315 SEC1
Adder
0.923
253371AE2-315 SEC2
Adder
0.873
970349AG2-230 GEN
Solar/Wind Harmer
6.892
247643Z2-116 C
Solar/Wind Harmer
0.032
945111AF1-176 GEN
Solar/Wind Harmer
2.574
24642205MAYFLWER
Adder
0.288
970513AG2-328 GEN
Solar/Wind Harmer
8.007
970517AG2-330 GEN
Solar/Wind Harmer
7.263
24441205WTRV SLR C
Solar/Wind Harmer
0.06
247604X1-042
Adder
0.185
946031AF1-268 GEN
Solar/Wind Harmer
3.69
958821AF2-173 GEN
Solar/Wind Harmer
6.139
270004AE1-209 GEN
Solar/Wind Harmer
2.397
274752CRETE EC ;2U
Adder
3.589
274753CRETE EC ;3U
Adder
3.589
274772LINCOLN ;3U
Adder
3.673
274724RIVER EC ;11
Adder
7.706
274802UNIV PARK;5U
Adder
2.517
274826FISK ;BP
Adder
4.723
274800UNIV PARK;3U
Adder
2.514
972038AH1-567 GEN2
Adder
0.157
972228AH1-698 GEN2
Adder
1.596
270466AD2-091
50/50
5.39
270471AD2-092_GEN
Solar/Wind Harmer
4.846
938701AE1-092 GEN
Solar/Wind Harmer
21.808
964601AG1-323 GEN
Solar/Wind Harmer
3.173
964601AG1-323 GEN
Solar/Wind Harmer
1.476
270224U2-072_GEN2
Solar/Wind Harmer
1.963
270227U2-072_GEN3
Solar/Wind Harmer
1.963
270228U2-072_GEN4
Solar/Wind Harmer
1.963
270231U2-072_GEN5
Solar/Wind Harmer
1.963
946101AF1-275 GEN
Solar/Wind Harmer
1.336
241960AC2-195 GEN
Solar/Wind Harmer
2.345
971201AH1-060 GEN
Solar/Wind Harmer
1.523
970077AG2-063 GEN
Solar/Wind Harmer
3.797
253378AE2-206_GEN
Solar/Wind Harmer
2.379
276820AF1-078_GEN
Solar/Wind Harmer
1.057
25326509SID D
Adder
0.827
246938BC-WTG3
Solar/Wind Harmer
2.379
246937BC-WTG2
Solar/Wind Harmer
2.339
270007AE1-245 C
Solar/Wind Harmer
3.321
942801AE2-298 GEN
Solar/Wind Harmer
0.846
970611AG2-400 GEN
Solar/Wind Harmer
5.279
270518AE2-148 GEN
Solar/Wind Harmer
6.245
942861AE2-305 GEN
Solar/Wind Harmer
3.849
25326109MON D
Adder
0.648
25322209TAIT E
Adder
4.647
25322209TAIT E
Adder
4.543
942221AE2-234 GEN
Solar/Wind Harmer
0.348
247620Y3-023
Adder
0.214
270201AC2-176 GEN
Solar/Wind Harmer
2.386
944541AF1-119 GEN
Solar/Wind Harmer
1.941
960971AF2-388 GEN
Solar/Wind Harmer
5.064
247621Y3-024
Adder
0.111
253370AE2-315 SEC1
Adder
0.923
964611AG1-324 GEN
Solar/Wind Harmer
0.542
964611AG1-324 GEN
Solar/Wind Harmer
0.241
270216AD2-079_GEN
Solar/Wind Harmer
0.278
960981AF2-389 GEN
Solar/Wind Harmer
0.686
957891AF2-083 GEN
Solar/Wind Harmer
1.532
970883AG2-550 GEN
Solar/Wind Harmer
4.537
970885AG2-551 GEN
Solar/Wind Harmer
1.055
961051AF2-396 GEN
Solar/Wind Harmer
7.194
961051AF2-396 GEN
Solar/Wind Harmer
3.346
270526AF1-158 GEN
Solar/Wind Harmer
2.047
24441505OLIV SLR
Solar/Wind Harmer
0.06
970321AG2-212 GEN
Solar/Wind Harmer
8.007
270599AE1-208 GEN
Solar/Wind Harmer
3.654
270031AE2-169
Solar/Wind Harmer
3.654
965681AG1-436 GEN
Solar/Wind Harmer
5.586
965791AG1-447 GEN
Solar/Wind Harmer
2.858
970825AG2-519 GEN
Solar/Wind Harmer
4.641
960441AF2-335 GEN
Solar/Wind Harmer
4.395
274770LINCOLN ;1U
Adder
3.673
274771LINCOLN ;2U
Adder
3.673
274808UNIV PK N;4U
Adder
2.161
274803UNIV PARK;6U
Adder
2.517
972259AH1-714 GEN
Adder
8.212
270349AD2-093_GEN
Solar/Wind Harmer
4.846
971995AH1-542 GEN
Solar/Wind Harmer
11.714
270223U2-072_GEN1
Solar/Wind Harmer
1.963
270578AF1-285 GEN2
Solar/Wind Harmer
1.2
270391AF1-285 GEN3
Solar/Wind Harmer
1.2
270462AD2-086
Solar/Wind Harmer
6.46
241813AF1-122_GEN
Solar/Wind Harmer
4.874
970593AG2-378 GEN
Solar/Wind Harmer
1.406
962761AG1-125 GEN
Solar/Wind Harmer
20.775
970149AG2-104 GEN
Solar/Wind Harmer
25.657
970155AG2-107 GEN
Solar/Wind Harmer
9.059
246936BC-WTG1
Solar/Wind Harmer
2.339
270489AE1-102 GEN1
Solar/Wind Harmer
0.777
965421AG1-410 GEN
Solar/Wind Harmer
17.731
247521TR3_G114
Solar/Wind Harmer
1.852
270246TR4_N_V150
Solar/Wind Harmer
0.468
24695305TIMB G C
Solar/Wind Harmer
2.998
965011AG1-365 GEN
Solar/Wind Harmer
5.279
270159DARBY CT4
Adder
4.59
944231AF1-091 GEN
Solar/Wind Harmer
1.832
253343AC1-166 GEN
Solar/Wind Harmer
0.523
253325AC1-069 GEN
Solar/Wind Harmer
0.505
960071AF2-298 GEN
Solar/Wind Harmer
2.387
25326309TAIT D
Adder
0.523
270063AE2-323 C
Solar/Wind Harmer
1.051
965651AG1-433 GEN
Solar/Wind Harmer
2.532
24639705ELKHART HY
Adder
0.071
253370AE2-315 SEC1
Adder
0.923
253371AE2-315 SEC2
Adder
0.873
958861AF2-177 GEN
Solar/Wind Harmer
5.028
247536S-71 GEN
Solar/Wind Harmer
1.856
945111AF1-176 GEN
Solar/Wind Harmer
8.121
270505AE1-170 C O1
Solar/Wind Harmer
6.807
945371AF1-202 GEN
Solar/Wind Harmer
3.165
270449AD2-020 GEN
Solar/Wind Harmer
1.267
943021AE2-325 GEN
Solar/Wind Harmer
1.646
970245AG2-165 GEN
Solar/Wind Harmer
8.007
970825AG2-519 GEN
Solar/Wind Harmer
1.035
270005AE1-210 C O1
Solar/Wind Harmer
2.397
965031AG1-367 GEN
Solar/Wind Harmer
4.385
970373AG2-245 GEN
Solar/Wind Harmer
9.206
274751CRETE EC ;1U
Adder
3.589
274754CRETE EC ;4U
Adder
3.589
274773LINCOLN ;4U
Adder
3.673
274774LINCOLN ;5U
Adder
3.673
274723RIVER EC ;12
Adder
7.798
274812UNIV PK N;8U
Adder
2.171
274801UNIV PARK;4U
Adder
2.514
270036AE2-216 BAT
50/50
5.929
270284AF1-227 GEN1
Solar/Wind Harmer
6.804
270286AF1-227 GEN2
Solar/Wind Harmer
2.517
270287AF1-227 GEN3
Solar/Wind Harmer
2.517
270578AF1-285 GEN2
Solar/Wind Harmer
0.462
241973AD2-163_GEN1
Solar/Wind Harmer
1.939
270302AB2-170 GEN
Solar/Wind Harmer
7.765
270317AD1-130_GEN
Solar/Wind Harmer
2.977
270520AE2-214 GEN
Solar/Wind Harmer
5.355
970179AG2-119 GEN
Solar/Wind Harmer
6.746
962771AG1-126 GEN
Solar/Wind Harmer
20.775
957201AF2-014 GEN
Solar/Wind Harmer
2.711
270435AC2-044 GEN
Solar/Wind Harmer
1.195
241972AD1-140 GEN
Solar/Wind Harmer
2.551
247607V1-011 GEN
Solar/Wind Harmer
2.214
965051AG1-369 GEN
Solar/Wind Harmer
2.75
270297AD1-101 GEN
Solar/Wind Harmer
1.533
965041AG1-368 GEN
Solar/Wind Harmer
5.342
945631AF1-228 GEN
Solar/Wind Harmer
2.501
270156DARBY CT1
Adder
4.664
270157DARBY CT2
Adder
4.653
270158DARBY CT3
Adder
4.578
963791AG1-232 GEN
Solar/Wind Harmer
6.751
943861AF1-054 GEN
Solar/Wind Harmer
1.9
943851AF1-053 GEN
Solar/Wind Harmer
0.918
270071AF1-092 GEN
Solar/Wind Harmer
7.187
270024AE2-089 GEN
Solar/Wind Harmer
2.242
24729505KEY G4
Adder
3.072
253349AC2-067 GEN
Solar/Wind Harmer
2.334
253400AC2-068 GEN
Solar/Wind Harmer
0.939
961761AG1-017 GEN
Solar/Wind Harmer
0.199
958711AF2-162 GEN
Solar/Wind Harmer
0.469
25306009OHH W.
Adder
1.331
253372AE2-315 SEC3
Adder
0.873
253372AE2-315 SEC3
Adder
0.873
965101AG1-375 GEN
Solar/Wind Harmer
4.6
971347AH1-153 GEN
Solar/Wind Harmer
6.892
971771AH1-392 GEN
Solar/Wind Harmer
4.09
270543AE2-219 C
Solar/Wind Harmer
2.323
945581AF1-223 GEN
Solar/Wind Harmer
2.057
944161AF1-084 GEN
Solar/Wind Harmer
0.996
971769AH1-391 GEN
Solar/Wind Harmer
4.495
971029AG2-637 GEN
Solar/Wind Harmer
6.737
971673AH1-337 GEN
Solar/Wind Harmer
2.06
960681AF2-359 GEN
Solar/Wind Harmer
1.688
970115AG2-085 GEN
Solar/Wind Harmer
1.758
253383AE2-342_GEN
Solar/Wind Harmer
0.388
274775LINCOLN ;6U
Adder
3.673
274776LINCOLN ;7U
Adder
3.673
274777LINCOLN ;8U
Adder
3.673
274814UNIV PK N;0U
Adder
2.19
274807UNIV PK N;3U
Adder
2.185
274805UNIV PK N;1U
Adder
2.176
274811UNIV PK N;7U
Adder
2.171
972037AH1-567 GEN1
Adder
0.079
274827FISK ;RP
Adder
3.347
972227AH1-698 GEN1
Adder
1.124
270054AF2-122 C O1
Solar/Wind Helper
0.806
971549AH1-272 GEN
Solar/Wind Harmer
6.289
NYPJM->LTFIMP_NY
CLTF
1.299
LGEELTFEXP_LGEE->PJM
CLTF
2.285
WECLTFEXP_WEC->PJM
CLTF
1.583
AG2-052LTFEXP_AG2-052->PJM
LTF
0.1
AH1-155LTFEXP_AH1-155->PJM
LTF
0.15
CPLELTFEXP_CPLE->PJM
CLTF
0.348
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.662
LAGNLTFEXP_LAGN->PJM
CLTF
5.094
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.339
TVALTFEXP_TVA->PJM
CLTF
2.364
CBM West 1LTFEXP_CBM-W1->PJM
CBM
56.137
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.529
MECLTFEXP_MEC->PJM
CLTF
6.298
SIGELTFEXP_SIGE->PJM
CLTF
0.181

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P4_#7216_05VASSEL 765_B1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7216_05VASSEL 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.74 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1447.54
MW Contribution:8.78
Bus #Bus NameTypeMW Contribution
270349AD2-093_GEN
Solar/Wind Harmer
4.839
971995AH1-542 GEN
Solar/Wind Harmer
11.797
270223U2-072_GEN1
Solar/Wind Harmer
1.959
270578AF1-285 GEN2
Solar/Wind Harmer
1.198
270391AF1-285 GEN3
Solar/Wind Harmer
1.198
270462AD2-086
Solar/Wind Harmer
6.448
241813AF1-122_GEN
Solar/Wind Harmer
4.917
970593AG2-378 GEN
Solar/Wind Harmer
1.423
962761AG1-125 GEN
Solar/Wind Harmer
20.13
970149AG2-104 GEN
Solar/Wind Harmer
24.861
970155AG2-107 GEN
Solar/Wind Harmer
8.778
246936BC-WTG1
Solar/Wind Harmer
2.324
270489AE1-102 GEN1
Solar/Wind Harmer
0.772
965421AG1-410 GEN
Solar/Wind Harmer
17.611
247521TR3_G114
Solar/Wind Harmer
1.837
270246TR4_N_V150
Solar/Wind Harmer
0.465
24695305TIMB G C
Solar/Wind Harmer
2.974
270159DARBY CT4
Adder
4.69
965011AG1-365 GEN
Solar/Wind Harmer
5.222
253343AC1-166 GEN
Solar/Wind Harmer
0.533
253325AC1-069 GEN
Solar/Wind Harmer
0.514
944231AF1-091 GEN
Solar/Wind Harmer
1.814
960071AF2-298 GEN
Solar/Wind Harmer
2.399
25326309TAIT D
Adder
0.526
270063AE2-323 C
Solar/Wind Harmer
1.037
253370AE2-315 SEC1
Adder
0.928
253371AE2-315 SEC2
Adder
0.878
965651AG1-433 GEN
Solar/Wind Harmer
2.504
247536S-71 GEN
Solar/Wind Harmer
1.844
958861AF2-177 GEN
Solar/Wind Harmer
4.973
24639705ELKHART HY
Adder
0.07
945111AF1-176 GEN
Solar/Wind Harmer
8.011
945371AF1-202 GEN
Solar/Wind Harmer
3.132
270505AE1-170 C O1
Solar/Wind Harmer
6.714
270449AD2-020 GEN
Solar/Wind Harmer
1.25
943021AE2-325 GEN
Solar/Wind Harmer
1.624
970245AG2-165 GEN
Solar/Wind Harmer
7.888
970825AG2-519 GEN
Solar/Wind Harmer
1.026
270005AE1-210 C O1
Solar/Wind Harmer
2.375
965031AG1-367 GEN
Solar/Wind Harmer
4.346
970373AG2-245 GEN
Solar/Wind Harmer
9.08
270032AE2-172
Solar/Wind Harmer
0.861
270036AE2-216 BAT
50/50
5.918
270284AF1-227 GEN1
Solar/Wind Harmer
6.793
270286AF1-227 GEN2
Solar/Wind Harmer
2.513
270287AF1-227 GEN3
Solar/Wind Harmer
2.513
270578AF1-285 GEN2
Solar/Wind Harmer
0.461
241973AD2-163_GEN1
Solar/Wind Harmer
1.957
270302AB2-170 GEN
Solar/Wind Harmer
7.752
270317AD1-130_GEN
Solar/Wind Harmer
2.972
270520AE2-214 GEN
Solar/Wind Harmer
5.445
970179AG2-119 GEN
Solar/Wind Harmer
6.8
962771AG1-126 GEN
Solar/Wind Harmer
20.13
957201AF2-014 GEN
Solar/Wind Harmer
2.694
270435AC2-044 GEN
Solar/Wind Harmer
1.188
241972AD1-140 GEN
Solar/Wind Harmer
2.576
247607V1-011 GEN
Solar/Wind Harmer
2.2
270297AD1-101 GEN
Solar/Wind Harmer
1.527
965051AG1-369 GEN
Solar/Wind Harmer
2.727
945631AF1-228 GEN
Solar/Wind Harmer
2.554
270156DARBY CT1
Adder
4.766
270157DARBY CT2
Adder
4.755
270158DARBY CT3
Adder
4.679
965041AG1-368 GEN
Solar/Wind Harmer
5.294
943861AF1-054 GEN
Solar/Wind Harmer
1.935
943851AF1-053 GEN
Solar/Wind Harmer
0.935
963791AG1-232 GEN
Solar/Wind Harmer
6.686
270024AE2-089 GEN
Solar/Wind Harmer
2.223
270071AF1-092 GEN
Solar/Wind Harmer
7.094
253349AC2-067 GEN
Solar/Wind Harmer
2.343
253400AC2-068 GEN
Solar/Wind Harmer
0.942
24729505KEY G4
Adder
3.036
25306009OHH W.
Adder
1.338
253372AE2-315 SEC3
Adder
0.878
253372AE2-315 SEC3
Adder
0.878
961761AG1-017 GEN
Solar/Wind Harmer
0.197
958711AF2-162 GEN
Solar/Wind Harmer
0.464
965101AG1-375 GEN
Solar/Wind Harmer
4.55
971347AH1-153 GEN
Solar/Wind Harmer
6.79
270543AE2-219 C
Solar/Wind Harmer
2.31
945581AF1-223 GEN
Solar/Wind Harmer
2.036
971771AH1-392 GEN
Solar/Wind Harmer
4.033
253383AE2-342_GEN
Solar/Wind Harmer
0.396
971029AG2-637 GEN
Solar/Wind Harmer
6.703
971673AH1-337 GEN
Solar/Wind Harmer
2.05
944161AF1-084 GEN
Solar/Wind Harmer
0.982
971769AH1-391 GEN
Solar/Wind Harmer
4.432
960681AF2-359 GEN
Solar/Wind Harmer
1.665
970115AG2-085 GEN
Solar/Wind Harmer
1.742
270054AF2-122 C O1
Solar/Wind Helper
0.786
270594AE1-207 GEN
Solar/Wind Harmer
2.721
270475AD2-096_GEN
50/50
7.743
942871AE2-306 GEN
Solar/Wind Harmer
0.899
270391AF1-285 GEN3
Solar/Wind Harmer
0.461
241974AD2-163_GEN2
Solar/Wind Harmer
1.957
270485AE1-090_GEN
Solar/Wind Harmer
0.561
942051AE2-217 GEN
Solar/Wind Harmer
14.042
970065AG2-057 GEN
Solar/Wind Harmer
0.768
970605AG2-385 GEN
Solar/Wind Harmer
3.843
241955AC1-078 GEN
Solar/Wind Harmer
5.062
970153AG2-106 GEN
Solar/Wind Harmer
8.778
270491AE1-102 GEN2
Solar/Wind Harmer
0.772
958091AF2-103 GEN
Solar/Wind Harmer
0.09
270191TR4_S_V150
Solar/Wind Harmer
1.639
270247TR4_N_V136
Solar/Wind Harmer
0.465
270258AD1-119 GEN
Solar/Wind Harmer
1.477
959331AF2-224 GEN
Solar/Wind Harmer
5.222
965021AG1-366 GEN
Solar/Wind Harmer
1.214
270044AE2-322 C
Solar/Wind Harmer
0.682
270404AC1-167 GEN
Solar/Wind Harmer
0.568
270588AE1-091_GEN
Solar/Wind Harmer
5.477
253338AC1-165 GEN
Solar/Wind Harmer
0.533
253333AC1-068 GEN
Solar/Wind Harmer
0.514
270043AE2-236 GEN
Solar/Wind Harmer
2.66
970031AG2-029 GEN
Solar/Wind Harmer
14.237
971617AH1-308 GEN
Solar/Wind Harmer
2.754
270541AE2-072 C
Solar/Wind Harmer
2.143
944531AF1-118 GEN
Solar/Wind Harmer
16.503
253303V4-073 C
Solar/Wind Harmer
0.054
253370AE2-315 SEC1
Adder
0.928
253371AE2-315 SEC2
Adder
0.878
962031AG1-047 GEN
Solar/Wind Harmer
1.393
957741AF2-068 GEN
Solar/Wind Harmer
6.912
970349AG2-230 GEN
Solar/Wind Harmer
6.79
247643Z2-116 C
Solar/Wind Harmer
0.032
945111AF1-176 GEN
Solar/Wind Harmer
2.539
24642205MAYFLWER
Adder
0.284
970513AG2-328 GEN
Solar/Wind Harmer
7.888
970517AG2-330 GEN
Solar/Wind Harmer
7.154
24441205WTRV SLR C
Solar/Wind Harmer
0.06
946031AF1-268 GEN
Solar/Wind Harmer
3.659
247604X1-042
Adder
0.183
958821AF2-173 GEN
Solar/Wind Harmer
6.084
270004AE1-209 GEN
Solar/Wind Harmer
2.375
270466AD2-091
50/50
5.38
270471AD2-092_GEN
Solar/Wind Harmer
4.839
938701AE1-092 GEN
Solar/Wind Harmer
21.937
964601AG1-323 GEN
Solar/Wind Harmer
3.19
964601AG1-323 GEN
Solar/Wind Harmer
1.484
270224U2-072_GEN2
Solar/Wind Harmer
1.959
270227U2-072_GEN3
Solar/Wind Harmer
1.959
270228U2-072_GEN4
Solar/Wind Harmer
1.959
270231U2-072_GEN5
Solar/Wind Harmer
1.959
946101AF1-275 GEN
Solar/Wind Harmer
1.359
241960AC2-195 GEN
Solar/Wind Harmer
2.364
971201AH1-060 GEN
Solar/Wind Harmer
1.536
970077AG2-063 GEN
Solar/Wind Harmer
3.843
253378AE2-206_GEN
Solar/Wind Harmer
2.386
276820AF1-078_GEN
Solar/Wind Harmer
1.06
25326509SID D
Adder
0.829
246938BC-WTG3
Solar/Wind Harmer
2.364
246937BC-WTG2
Solar/Wind Harmer
2.324
270007AE1-245 C
Solar/Wind Harmer
3.3
942801AE2-298 GEN
Solar/Wind Harmer
0.841
270518AE2-148 GEN
Solar/Wind Harmer
6.356
970611AG2-400 GEN
Solar/Wind Harmer
5.222
942861AE2-305 GEN
Solar/Wind Harmer
3.921
25326109MON D
Adder
0.653
25322209TAIT E
Adder
4.675
25322209TAIT E
Adder
4.57
942221AE2-234 GEN
Solar/Wind Harmer
0.344
253370AE2-315 SEC1
Adder
0.928
270201AC2-176 GEN
Solar/Wind Harmer
2.369
944541AF1-119 GEN
Solar/Wind Harmer
1.919
960971AF2-388 GEN
Solar/Wind Harmer
5.008
247620Y3-023
Adder
0.211
247621Y3-024
Adder
0.11
964611AG1-324 GEN
Solar/Wind Harmer
0.538
964611AG1-324 GEN
Solar/Wind Harmer
0.239
270216AD2-079_GEN
Solar/Wind Harmer
0.274
970883AG2-550 GEN
Solar/Wind Harmer
4.511
970885AG2-551 GEN
Solar/Wind Harmer
1.049
960981AF2-389 GEN
Solar/Wind Harmer
0.677
957891AF2-083 GEN
Solar/Wind Harmer
1.511
961051AF2-396 GEN
Solar/Wind Harmer
7.096
961051AF2-396 GEN
Solar/Wind Harmer
3.301
270526AF1-158 GEN
Solar/Wind Harmer
2.018
270599AE1-208 GEN
Solar/Wind Harmer
3.619
270031AE2-169
Solar/Wind Harmer
3.619
24441505OLIV SLR
Solar/Wind Harmer
0.059
970321AG2-212 GEN
Solar/Wind Harmer
7.888
965681AG1-436 GEN
Solar/Wind Harmer
5.508
965791AG1-447 GEN
Solar/Wind Harmer
2.818
970825AG2-519 GEN
Solar/Wind Harmer
4.6
960441AF2-335 GEN
Solar/Wind Harmer
4.356
270383AD1-128 GEN
Solar/Wind Harmer
2.637
NYPJM->LTFIMP_NY
CLTF
1.287
LGEELTFEXP_LGEE->PJM
CLTF
2.274
WECLTFEXP_WEC->PJM
CLTF
1.561
AG2-052LTFEXP_AG2-052->PJM
LTF
0.099
AH1-155LTFEXP_AH1-155->PJM
LTF
0.148
CPLELTFEXP_CPLE->PJM
CLTF
0.34
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.234
LAGNLTFEXP_LAGN->PJM
CLTF
5.039
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.304
TVALTFEXP_TVA->PJM
CLTF
2.34
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.504
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.444
MECLTFEXP_MEC->PJM
CLTF
6.218
SIGELTFEXP_SIGE->PJM
CLTF
0.179

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-024_SRT-A


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.01 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5081.52
MW Contribution:17.95
Bus #Bus NameTypeMW Contribution
962771AG1-126 GEN
Solar/Wind Harmer
41.173
270459AD2-067 GEN
Solar/Wind Harmer
10.252
961821AG1-024 GEN
Solar/Wind Harmer
10.408
270054AF2-122 C O1
Solar/Wind Harmer
3.995
972239AH1-704 GEN
Adder
2.671
270284AF1-227 GEN1
Solar/Wind Harmer
6.806
270286AF1-227 GEN2
Solar/Wind Harmer
2.518
270287AF1-227 GEN3
Solar/Wind Harmer
2.518
270520AE2-214 GEN
Solar/Wind Harmer
7.284
253383AE2-342_GEN
Solar/Wind Harmer
1.047
241973AD2-163_GEN1
Solar/Wind Harmer
2.334
943861AF1-054 GEN
Solar/Wind Harmer
4.494
943851AF1-053 GEN
Solar/Wind Harmer
2.172
945631AF1-228 GEN
Solar/Wind Harmer
5.47
270156DARBY CT1
Adder
10.432
270157DARBY CT2
Adder
10.407
270158DARBY CT3
Adder
10.24
270578AF1-285 GEN2
Solar/Wind Harmer
0.538
970689AG2-444 GEN
Solar/Wind Harmer
18.845
270432AC2-029 GEN
Solar/Wind Harmer
8.059
270302AB2-170 GEN
Solar/Wind Harmer
9.566
270317AD1-130_GEN
Solar/Wind Harmer
3.667
270269AC2-059
Solar/Wind Harmer
10.62
940611AE2-048 GEN
Solar/Wind Harmer
24.866
941391AE2-136 GEN
Solar/Wind Harmer
12.885
241972AD1-140 GEN
Solar/Wind Harmer
5.031
270340AC2-060 GEN
Solar/Wind Harmer
3.353
958581AF2-149 GEN
Solar/Wind Harmer
4.732
970179AG2-119 GEN
Solar/Wind Harmer
8.844
970879AG2-548 GEN
Solar/Wind Harmer
4.736
253372AE2-315 SEC3
Adder
2.071
253372AE2-315 SEC3
Adder
2.071
25306009OHH W.
Adder
3.141
253349AC2-067 GEN
Solar/Wind Harmer
5.421
253400AC2-068 GEN
Solar/Wind Harmer
2.18
957201AF2-014 GEN
Solar/Wind Harmer
4.91
270435AC2-044 GEN
Solar/Wind Harmer
2.165
965051AG1-369 GEN
Solar/Wind Harmer
5.38
965041AG1-368 GEN
Solar/Wind Harmer
10.749
247607V1-011 GEN
Solar/Wind Harmer
4.249
24729505KEY G4
Adder
6.948
963791AG1-232 GEN
Solar/Wind Harmer
14.455
971567AH1-282 GEN
Solar/Wind Harmer
16.053
966831AG1-554 GEN
Solar/Wind Harmer
1.28
971989AH1-539 GEN
Solar/Wind Harmer
13.846
270071AF1-092 GEN
Solar/Wind Harmer
16.048
971985AH1-537 GEN
Solar/Wind Harmer
19.051
958711AF2-162 GEN
Solar/Wind Harmer
1.079
270024AE2-089 GEN
Solar/Wind Harmer
5.004
965101AG1-375 GEN
Solar/Wind Harmer
10.653
270367AC2-061_GEN
Solar/Wind Harmer
3.388
971673AH1-337 GEN
Solar/Wind Harmer
4.893
971029AG2-637 GEN
Solar/Wind Harmer
15.954
252524AE2-267 GEN
Solar/Wind Harmer
1.677
25196408WSDLE3
Adder
9.382
25196308WSDLE2
Adder
9.3
25196208WSDLE1
Adder
9.277
25196708WSDLE6
Adder
9.254
25196508WSDLE4
Adder
9.021
270543AE2-219 C
Solar/Wind Harmer
5.445
961761AG1-017 GEN
Solar/Wind Harmer
0.455
945581AF1-223 GEN
Solar/Wind Harmer
4.819
944031AF1-071 GEN
Solar/Wind Harmer
1.067
270297AD1-101 GEN
Solar/Wind Harmer
2.953
25196108MFTGT2
Adder
1.605
25196108MFTGT2
Adder
1.491
274775LINCOLN ;6U
Adder
8.715
274776LINCOLN ;7U
Adder
8.715
274777LINCOLN ;8U
Adder
8.715
274814UNIV PK N;0U
Adder
5.208
274807UNIV PK N;3U
Adder
5.196
274805UNIV PK N;1U
Adder
5.174
274811UNIV PK N;7U
Adder
5.162
972037AH1-567 GEN1
Adder
0.188
274827FISK ;RP
Adder
7.977
972227AH1-698 GEN1
Adder
2.681
274687WILL CNTY;4U
Adder
28.653
274687WILL CNTY;4U
Adder
28.653
274675JOLIET 29;7U
Adder
31.445
274675JOLIET 29;7U
Adder
30.322
274731ELWOOD EC;2P
Adder
16.844
274733ELWOOD EC;3P
Adder
16.844
274735ELWOOD EC;4P
Adder
16.844
274728ELWOOD EC;5P
Adder
16.844
972203AH1-686 GEN
Adder
2.356
274746AC1-111 G10
Adder
5.705
274744AC1-111 GEN8
Adder
5.705
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.832
238152AF2-075_GEN
Solar/Wind Helper
0.709
238208AF1-136 C
Solar/Wind Helper
0.221
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.655
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.891
316415AF1-147_GEN2
Solar/Wind Helper
0.891
23750501ELLIOTTS
Solar/Wind Helper
0.644
959381AF2-229 GEN
Solar/Wind Helper
0.359
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.182
205943AE1-185 GEN
Solar/Wind Helper
0.511
205932AD2-116_GEN
Solar/Wind Helper
0.511
205956AE1-196_GEN
Solar/Wind Helper
0.511
233935AB2-179 C
Solar/Wind Helper
1.273
232436AB1-176 C
Solar/Wind Helper
0.045
233923SMA
Solar/Wind Helper
0.962
233990AG1-397 GEN
Solar/Wind Helper
0.031
232432Z2-076 GEN
Solar/Wind Helper
0.067
234033AF1-007_GEN
Solar/Wind Helper
7.046
964001AG1-254 GEN
Solar/Wind Helper
0.959
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.508
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.291
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.099
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.082
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
20675128HRM_W1-127
Solar/Wind Helper
0.03
209116AE2-175 GEN
Solar/Wind Helper
1.786
270166AC1-044 GEN3
50/50
7.1
23559101PLEAS2
50/50
6.365
962761AG1-125 GEN
Solar/Wind Harmer
41.173
970149AG2-104 GEN
Solar/Wind Harmer
50.849
970155AG2-107 GEN
Solar/Wind Harmer
17.953
270349AD2-093_GEN
Solar/Wind Harmer
4.477
24721705FLATG2
Adder
24.144
270159DARBY CT4
Adder
10.266
970593AG2-378 GEN
Solar/Wind Harmer
2.315
270223U2-072_GEN1
Solar/Wind Harmer
2.287
270578AF1-285 GEN2
Solar/Wind Harmer
1.399
270391AF1-285 GEN3
Solar/Wind Harmer
1.399
253343AC1-166 GEN
Solar/Wind Harmer
1.243
253325AC1-069 GEN
Solar/Wind Harmer
1.199
270462AD2-086
Solar/Wind Harmer
7.958
971995AH1-542 GEN
Solar/Wind Harmer
12.515
270263AC1-001 GEN
Solar/Wind Harmer
1.179
25326309TAIT D
Adder
1.2
960071AF2-298 GEN
Solar/Wind Harmer
5.454
253370AE2-315 SEC1
Adder
2.189
253371AE2-315 SEC2
Adder
2.071
927014AC1-188 GEN
Solar/Wind Harmer
1.729
241813AF1-122_GEN
Solar/Wind Harmer
6.978
246936BC-WTG1
Solar/Wind Harmer
4.237
270489AE1-102 GEN1
Solar/Wind Harmer
1.407
965421AG1-410 GEN
Solar/Wind Harmer
32.464
960001AF2-291 GEN
Solar/Wind Harmer
3.264
253432AC1-085 GEN2
Solar/Wind Harmer
0.289
946171AF1-282 GEN
Solar/Wind Harmer
10.789
247521TR3_G114
Solar/Wind Harmer
3.623
270246TR4_N_V150
Solar/Wind Harmer
0.916
965011AG1-365 GEN
Solar/Wind Harmer
10.775
24695305TIMB G C
Solar/Wind Harmer
5.916
965651AG1-433 GEN
Solar/Wind Harmer
5.83
958861AF2-177 GEN
Solar/Wind Harmer
11.644
247536S-71 GEN
Solar/Wind Harmer
4.305
25194608D.CRK4
Adder
1.747
945371AF1-202 GEN
Solar/Wind Harmer
7.414
252507AC2-088 GEN
Solar/Wind Harmer
1.904
270063AE2-323 C
Solar/Wind Harmer
2.336
25196808ZIMRHP
Adder
80.055
24639705ELKHART HY
Adder
0.162
25196008MFTGT1
Adder
1.456
274751CRETE EC ;1U
Adder
8.515
274754CRETE EC ;4U
Adder
8.515
274773LINCOLN ;4U
Adder
8.715
274774LINCOLN ;5U
Adder
8.715
274723RIVER EC ;12
Adder
18.501
274812UNIV PK N;8U
Adder
5.162
24728605AND G2
Adder
3.945
274801UNIV PARK;4U
Adder
5.993
274676JOLIET 29;8U
Adder
31.445
274732ELWOOD EC;7P
Adder
16.844
274674JOLIET 9 ;6U
Adder
15.776
274745AC1-111 GEN9
Adder
5.705
970091AG2-072 GEN
Adder
78.03
316095T157 G97
Solar/Wind Helper
1.508
23583801GRNGAP
Solar/Wind Helper
5.618
238185AF2-356 C
Solar/Wind Helper
2.662
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.043
235531U2-073 GEN
Solar/Wind Helper
3.301
238117U2-030
Solar/Wind Helper
0.344
238147AE2-230_GEN1
Solar/Wind Helper
0.496
238149AF1-291A_GEN
Solar/Wind Helper
0.142
23751201ROTHROCK
Solar/Wind Helper
0.832
23562501BACKB
Solar/Wind Helper
1.017
237061AD1-155 GEN
Solar/Wind Helper
0.053
238221AF1-254 C O1
Solar/Wind Helper
0.275
235067AD1-061 GEN
Solar/Wind Helper
0.498
23751101LEADS_P59
Solar/Wind Helper
1.424
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.034
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.347
223402AF1-300 C
Solar/Wind Helper
0.369
205917AD1-020 ES
Solar/Wind Helper
0.37
233918AB1-142 GEN
Solar/Wind Helper
0.504
233982AB2-133 GEN
Solar/Wind Helper
0.359
233994AC2-023 GEN
Solar/Wind Helper
0.965
233996TM1833_GEN
Solar/Wind Helper
0.262
233997TMININ_4.2
Solar/Wind Helper
0.262
232406W1-004 FULL
Solar/Wind Helper
0.509
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.233
233971AC1-093 C
Solar/Wind Helper
0.359
230430AE1-229_GEN
Solar/Wind Helper
3.385
316044AC1-158 PL1
Solar/Wind Helper
1.296
316450AC1-158 RIC
Solar/Wind Helper
0.346
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.111
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.354
219276PARKLANDSO C
Solar/Wind Helper
0.09
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
963161AG1-165 GEN
Solar/Wind Helper
0.441
970245AG2-165 GEN
Solar/Wind Harmer
4.981
24318805MLG1
50/50
10.158
23559001PLEAS1
50/50
6.365
270051AF1-062 GEN
50/50
11.843
270475AD2-096_GEN
50/50
7.165
970153AG2-106 GEN
Solar/Wind Harmer
17.953
961921AG1-034 GEN
Solar/Wind Harmer
15.612
24721905FLATG4
Adder
24.144
241955AC1-078 GEN
Solar/Wind Harmer
8.824
241974AD2-163_GEN2
Solar/Wind Harmer
2.334
942051AE2-217 GEN
Solar/Wind Harmer
21.08
960801AF2-371 GEN
Solar/Wind Harmer
2.95
964871AG1-351 GEN
Solar/Wind Harmer
2.037
970605AG2-385 GEN
Solar/Wind Harmer
6.25
942871AE2-306 GEN
Solar/Wind Harmer
1.049
270391AF1-285 GEN3
Solar/Wind Harmer
0.538
253338AC1-165 GEN
Solar/Wind Harmer
1.243
253333AC1-068 GEN
Solar/Wind Harmer
1.199
270485AE1-090_GEN
Solar/Wind Harmer
0.692
270273AD2-016 GEN
Solar/Wind Harmer
3.037
972173AH1-669 GEN
Solar/Wind Harmer
5.679
253415AE1-040 GEN
Solar/Wind Harmer
1.251
270291AC1-194 GEN
Solar/Wind Harmer
11.751
253303V4-073 C
Solar/Wind Harmer
0.127
253370AE2-315 SEC1
Adder
2.189
253371AE2-315 SEC2
Adder
2.071
957541AF2-048 GEN
Solar/Wind Harmer
1.724
970065AG2-057 GEN
Solar/Wind Harmer
1.09
253406AD2-031_GEN
Solar/Wind Harmer
1.391
270491AE1-102 GEN2
Solar/Wind Harmer
1.407
971191AH1-055 GEN
Solar/Wind Harmer
23.759
253316AC1-085 GEN3
Solar/Wind Harmer
9.037
253433AC1-085 GEN1
Solar/Wind Harmer
5.737
946181AF1-283 GEN
Solar/Wind Harmer
14.025
270191TR4_S_V150
Solar/Wind Harmer
3.232
270247TR4_N_V136
Solar/Wind Harmer
0.916
959331AF2-224 GEN
Solar/Wind Harmer
10.775
965021AG1-366 GEN
Solar/Wind Harmer
2.506
270377AD1-106 GEN
Solar/Wind Harmer
6.65
958091AF2-103 GEN
Solar/Wind Harmer
0.174
270588AE1-091_GEN
Solar/Wind Harmer
11.804
944531AF1-118 GEN
Solar/Wind Harmer
37.541
270043AE2-236 GEN
Solar/Wind Harmer
5.893
971617AH1-308 GEN
Solar/Wind Harmer
6.198
270258AD1-119 GEN
Solar/Wind Harmer
2.97
25196608WSDLE5
Adder
9.114
962031AG1-047 GEN
Solar/Wind Harmer
3.214
957741AF2-068 GEN
Solar/Wind Harmer
15.949
252510AF1-249 C
Solar/Wind Harmer
0.444
25194608D.CRK4
Adder
1.747
270222AC2-111 GEN
Solar/Wind Harmer
8.657
970031AG2-029 GEN
Solar/Wind Harmer
31.849
270044AE2-322 C
Solar/Wind Harmer
1.394
270404AC1-167 GEN
Solar/Wind Harmer
1.161
24642205MAYFLWER
Adder
0.667
25196008MFTGT1
Adder
1.411
247604X1-042
Adder
0.435
274752CRETE EC ;2U
Adder
8.515
274753CRETE EC ;3U
Adder
8.515
274772LINCOLN ;3U
Adder
8.715
274724RIVER EC ;11
Adder
18.285
274802UNIV PARK;5U
Adder
5.997
24728705AND G3
Adder
8.251
24728505AND G1
Adder
3.945
274826FISK ;BP
Adder
11.256
274800UNIV PARK;3U
Adder
5.993
972038AH1-567 GEN2
Adder
0.375
972228AH1-698 GEN2
Adder
3.807
274676JOLIET 29;8U
Adder
30.322
274729ELWOOD EC;1P
Adder
16.844
274730ELWOOD EC;6P
Adder
16.844
274734ELWOOD EC;8P
Adder
16.844
274736ELWOOD EC;9P
Adder
16.844
274682WAUKEGAN ;7U
Adder
9.773
964991AG1-363 GEN
Solar/Wind Helper
5.152
316097T157 G90
Solar/Wind Helper
1.508
23750701CROSSCHOOL
Solar/Wind Helper
1.51
238118U2-030_1
Solar/Wind Helper
0.344
238127S14_GEN_2
Solar/Wind Helper
0.832
238148AE2-230_GEN2
Solar/Wind Helper
0.498
237080AD1-060 GEN
Solar/Wind Helper
0.343
237038AE2-054 C
Solar/Wind Helper
0.273
235062AE1-101 C1
Solar/Wind Helper
1.665
23779801AA1-109
Solar/Wind Helper
0.194
237048AF1-022 C
Solar/Wind Helper
0.179
223401AF1-299 GEN
Solar/Wind Helper
0.369
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.078
233930AB2-032 GEN
Solar/Wind Helper
0.382
233915AB1-141 GEN
Solar/Wind Helper
0.504
232422X3-066 FULL
Solar/Wind Helper
0.115
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.262
232404W1-003 C
Solar/Wind Helper
0.509
232428Y3-058 C
Solar/Wind Helper
0.339
232434Z2-077 GEN
Solar/Wind Helper
0.127
233954AC2-188 GEN
Solar/Wind Helper
0.233
233950AC2-186 GEN
Solar/Wind Helper
0.117
233972AC1-094 C
Solar/Wind Helper
0.303
230511AF1-262
Solar/Wind Helper
0.015
316045AC1-158 PL2
Solar/Wind Helper
4.149
230434AG1-499 GEN
Solar/Wind Helper
0.231
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.061
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.132
20720728JCB_W1-129
Solar/Wind Helper
0.057
207445AB1-138_GEN
Solar/Wind Helper
0.105
316254AC1-120 GEN1
Solar/Wind Helper
1.062
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
270119AB2-067 GEN1
50/50
7.1
270120AB2-067 GEN2
50/50
7.1
24318905MLG2
50/50
7.059
270471AD2-092_GEN
Solar/Wind Harmer
4.477
946101AF1-275 GEN
Solar/Wind Harmer
1.818
942861AE2-305 GEN
Solar/Wind Harmer
9.105
970077AG2-063 GEN
Solar/Wind Harmer
6.25
270224U2-072_GEN2
Solar/Wind Harmer
2.287
270227U2-072_GEN3
Solar/Wind Harmer
2.287
270228U2-072_GEN4
Solar/Wind Harmer
2.287
270231U2-072_GEN5
Solar/Wind Harmer
2.287
938701AE1-092 GEN
Solar/Wind Harmer
23.86
964601AG1-323 GEN
Solar/Wind Harmer
3.665
964601AG1-323 GEN
Solar/Wind Harmer
1.705
270518AE2-148 GEN
Solar/Wind Harmer
13.911
253378AE2-206_GEN
Solar/Wind Harmer
4.016
276820AF1-078_GEN
Solar/Wind Harmer
1.784
972159AH1-661 GEN
Adder
1.111
972269AH1-719 GEN
Adder
2.557
25326509SID D
Adder
1.455
971199AH1-059 GEN
Solar/Wind Harmer
4.424
241960AC2-195 GEN
Solar/Wind Harmer
3.074
970879AG2-548 GEN
Solar/Wind Harmer
6.788
971073AG2-665 GEN
Solar/Wind Harmer
6.788
971073AG2-665 GEN
Solar/Wind Harmer
4.736
25326109MON D
Adder
1.447
25322209TAIT E
Adder
10.679
25322209TAIT E
Adder
10.439
253370AE2-315 SEC1
Adder
2.189
971201AH1-060 GEN
Solar/Wind Harmer
2.181
253394AE2-221_GEN
Solar/Wind Harmer
4.93
253398AE2-221_GEN2
Solar/Wind Harmer
4.93
246938BC-WTG3
Solar/Wind Harmer
4.31
246937BC-WTG2
Solar/Wind Harmer
4.237
253317AC1-085 GEN4
Solar/Wind Harmer
9.037
970611AG2-400 GEN
Solar/Wind Harmer
10.775
971231AH1-075 GEN
Solar/Wind Harmer
0.862
270007AE1-245 C
Solar/Wind Harmer
6.374
942801AE2-298 GEN
Solar/Wind Harmer
1.626
962581AG1-107 GEN
Solar/Wind Harmer
5.38
961491AF2-440 GEN
Solar/Wind Harmer
2.236
25183208HLCRTG
Solar/Wind Harmer
6.467
944541AF1-119 GEN
Solar/Wind Harmer
4.468
960971AF2-388 GEN
Solar/Wind Harmer
11.659
207454AA2-184 E
Solar/Wind Helper
0.311
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.497
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.023
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.577
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.03
202652Y1-033 WT C
Solar/Wind Helper
0.5
961301AF2-421 GEN
Solar/Wind Helper
0.441
963151AG1-164 GEN
Solar/Wind Helper
0.441
970513AG2-328 GEN
Solar/Wind Harmer
4.981
970517AG2-330 GEN
Solar/Wind Harmer
4.518
942221AE2-234 GEN
Solar/Wind Harmer
0.781
252519AF1-045_GEN
Solar/Wind Harmer
6.466
252516AE2-318_GEN
Solar/Wind Harmer
4.932
247621Y3-024
Adder
0.256
970883AG2-550 GEN
Solar/Wind Harmer
10.634
970885AG2-551 GEN
Solar/Wind Harmer
2.473
270201AC2-176 GEN
Solar/Wind Harmer
5.466
25194408D.CRK1
Adder
8.037
25194508D.CRK3
Adder
1.502
964611AG1-324 GEN
Solar/Wind Harmer
1.252
964611AG1-324 GEN
Solar/Wind Harmer
0.556
252509AD1-136 GEN
Solar/Wind Harmer
0.272
247620Y3-023
Adder
0.486
24728805RICHG1
Adder
3.981
24728905RICHG2
Adder
3.981
274770LINCOLN ;1U
Adder
8.715
274771LINCOLN ;2U
Adder
8.715
274808UNIV PK N;4U
Adder
5.14
274803UNIV PARK;6U
Adder
5.997
972259AH1-714 GEN
Adder
19.596
274674JOLIET 9 ;6U
Adder
15.776
274696ROCKY RD ;4P
Adder
11.59
274695ROCKY RD ;2P
Adder
11.323
274693ROCKY RD ;1P
Adder
11.211
274697ROCKY RD ;3P
Adder
3.076
23585401KL_K28_T16
Solar/Wind Helper
1.493
238120AE2-309 GEN
Solar/Wind Helper
0.528
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.703
238170AE2-226 GEN2
Solar/Wind Helper
0.703
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237002AB1-128_GEN
Solar/Wind Helper
0.445
237034AC2-136 C
Solar/Wind Helper
0.228
235063AE1-101 C2
Solar/Wind Helper
1.665
237001AB1-127_GEN
Solar/Wind Helper
0.443
23777801MSM_W1-116
Solar/Wind Helper
0.115
237025AB1-124 C
Solar/Wind Helper
0.165
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.72
20390526W1-045 C
Solar/Wind Helper
0.351
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.35
233933AB2-153 GEN
Solar/Wind Helper
0.233
232424Y1-079 C
Solar/Wind Helper
0.117
233944AB2-135 GEN
Solar/Wind Helper
0.591
233946AB2-136 GEN
Solar/Wind Helper
0.57
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.233
232408W1-005 C
Solar/Wind Helper
0.509
232410W1-006 C
Solar/Wind Helper
0.509
233939AC1-091 C
Solar/Wind Helper
0.351
233970AC1-092 C
Solar/Wind Helper
0.351
315651AD1-115 GEN
Solar/Wind Helper
0.787
316447AC1-158 HLD
Solar/Wind Helper
2.853
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.083
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.327
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.169
20674928WA_W3-044
Solar/Wind Helper
0.099
964851AG1-348 GEN
Solar/Wind Helper
0.081
20676228FRD_X1-012
Solar/Wind Helper
0.092
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.045
211065PSPA IPP
Solar/Wind Helper
0.152
211065PSPA IPP
Solar/Wind Helper
0.152
203955AF1-039 C O1
Solar/Wind Helper
0.33
970321AG2-212 GEN
Solar/Wind Harmer
4.981
NYPJM->LTFIMP_NY
CLTF
4.819
LGEELTFEXP_LGEE->PJM
CLTF
6.781
WECLTFEXP_WEC->PJM
CLTF
3.842
AG2-052LTFEXP_AG2-052->PJM
LTF
0.241
AH1-155LTFEXP_AH1-155->PJM
LTF
0.361
CPLELTFEXP_CPLE->PJM
CLTF
0.647
CBM West 2LTFEXP_CBM-W2->PJM
CBM
113.418
LAGNLTFEXP_LAGN->PJM
CLTF
14.924
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.891
TVALTFEXP_TVA->PJM
CLTF
7.337
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.671
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.268
MECLTFEXP_MEC->PJM
CLTF
15.978
SIGELTFEXP_SIGE->PJM
CLTF
0.507

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-025_SRT-A


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-025_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.21 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5051.2
MW Contribution:17.88
Bus #Bus NameTypeMW Contribution
962771AG1-126 GEN
Solar/Wind Harmer
41.012
972239AH1-704 GEN
Adder
2.683
270459AD2-067 GEN
Solar/Wind Harmer
10.243
961821AG1-024 GEN
Solar/Wind Harmer
10.399
270054AF2-122 C O1
Solar/Wind Harmer
3.993
270520AE2-214 GEN
Solar/Wind Harmer
7.274
270284AF1-227 GEN1
Solar/Wind Harmer
6.791
270286AF1-227 GEN2
Solar/Wind Harmer
2.512
270287AF1-227 GEN3
Solar/Wind Harmer
2.512
253383AE2-342_GEN
Solar/Wind Harmer
1.045
241973AD2-163_GEN1
Solar/Wind Harmer
2.33
945631AF1-228 GEN
Solar/Wind Harmer
5.461
943861AF1-054 GEN
Solar/Wind Harmer
4.486
943851AF1-053 GEN
Solar/Wind Harmer
2.168
270156DARBY CT1
Adder
10.416
270157DARBY CT2
Adder
10.391
270158DARBY CT3
Adder
10.225
970689AG2-444 GEN
Solar/Wind Harmer
18.82
270578AF1-285 GEN2
Solar/Wind Harmer
0.537
270432AC2-029 GEN
Solar/Wind Harmer
8.046
270302AB2-170 GEN
Solar/Wind Harmer
9.546
270317AD1-130_GEN
Solar/Wind Harmer
3.66
940611AE2-048 GEN
Solar/Wind Harmer
25.033
941391AE2-136 GEN
Solar/Wind Harmer
12.972
270269AC2-059
Solar/Wind Harmer
10.602
241972AD1-140 GEN
Solar/Wind Harmer
5.021
958581AF2-149 GEN
Solar/Wind Harmer
4.736
970179AG2-119 GEN
Solar/Wind Harmer
8.837
270340AC2-060 GEN
Solar/Wind Harmer
3.346
970879AG2-548 GEN
Solar/Wind Harmer
4.728
253372AE2-315 SEC3
Adder
2.066
253372AE2-315 SEC3
Adder
2.066
25306009OHH W.
Adder
3.134
253349AC2-067 GEN
Solar/Wind Harmer
5.408
253400AC2-068 GEN
Solar/Wind Harmer
2.175
957201AF2-014 GEN
Solar/Wind Harmer
4.898
270435AC2-044 GEN
Solar/Wind Harmer
2.16
965051AG1-369 GEN
Solar/Wind Harmer
5.366
965041AG1-368 GEN
Solar/Wind Harmer
10.722
247607V1-011 GEN
Solar/Wind Harmer
4.239
971567AH1-282 GEN
Solar/Wind Harmer
16.059
966831AG1-554 GEN
Solar/Wind Harmer
1.279
971989AH1-539 GEN
Solar/Wind Harmer
13.833
24729505KEY G4
Adder
6.928
963791AG1-232 GEN
Solar/Wind Harmer
14.415
270071AF1-092 GEN
Solar/Wind Harmer
16.001
971985AH1-537 GEN
Solar/Wind Harmer
18.998
958711AF2-162 GEN
Solar/Wind Harmer
1.076
270024AE2-089 GEN
Solar/Wind Harmer
4.99
270367AC2-061_GEN
Solar/Wind Harmer
3.379
965101AG1-375 GEN
Solar/Wind Harmer
10.622
971673AH1-337 GEN
Solar/Wind Harmer
4.88
252524AE2-267 GEN
Solar/Wind Harmer
1.673
971029AG2-637 GEN
Solar/Wind Harmer
15.909
25196408WSDLE3
Adder
9.356
25196308WSDLE2
Adder
9.275
25196208WSDLE1
Adder
9.252
25196708WSDLE6
Adder
9.228
25196508WSDLE4
Adder
8.996
270543AE2-219 C
Solar/Wind Harmer
5.43
961761AG1-017 GEN
Solar/Wind Harmer
0.454
945581AF1-223 GEN
Solar/Wind Harmer
4.805
270297AD1-101 GEN
Solar/Wind Harmer
2.947
944031AF1-071 GEN
Solar/Wind Harmer
1.064
270166AC1-044 GEN3
50/50
7.072
23559101PLEAS2
50/50
6.183
962761AG1-125 GEN
Solar/Wind Harmer
41.012
970149AG2-104 GEN
Solar/Wind Harmer
50.65
970155AG2-107 GEN
Solar/Wind Harmer
17.883
270349AD2-093_GEN
Solar/Wind Harmer
4.467
24721705FLATG2
Adder
23.989
270159DARBY CT4
Adder
10.25
970593AG2-378 GEN
Solar/Wind Harmer
2.311
270223U2-072_GEN1
Solar/Wind Harmer
2.282
270578AF1-285 GEN2
Solar/Wind Harmer
1.396
270391AF1-285 GEN3
Solar/Wind Harmer
1.396
253343AC1-166 GEN
Solar/Wind Harmer
1.241
253325AC1-069 GEN
Solar/Wind Harmer
1.197
270462AD2-086
Solar/Wind Harmer
7.941
971995AH1-542 GEN
Solar/Wind Harmer
12.502
270263AC1-001 GEN
Solar/Wind Harmer
1.177
24318805MLG1
50/50
10.115
23559001PLEAS1
50/50
6.183
270051AF1-062 GEN
50/50
11.828
270475AD2-096_GEN
50/50
7.148
970153AG2-106 GEN
Solar/Wind Harmer
17.883
961921AG1-034 GEN
Solar/Wind Harmer
15.599
24721905FLATG4
Adder
23.989
241955AC1-078 GEN
Solar/Wind Harmer
8.811
241974AD2-163_GEN2
Solar/Wind Harmer
2.33
942051AE2-217 GEN
Solar/Wind Harmer
21.044
960801AF2-371 GEN
Solar/Wind Harmer
2.947
964871AG1-351 GEN
Solar/Wind Harmer
2.035
970605AG2-385 GEN
Solar/Wind Harmer
6.239
942871AE2-306 GEN
Solar/Wind Harmer
1.047
270391AF1-285 GEN3
Solar/Wind Harmer
0.537
253338AC1-165 GEN
Solar/Wind Harmer
1.241
253333AC1-068 GEN
Solar/Wind Harmer
1.197
270485AE1-090_GEN
Solar/Wind Harmer
0.69
270273AD2-016 GEN
Solar/Wind Harmer
3.032
972173AH1-669 GEN
Solar/Wind Harmer
5.669
253415AE1-040 GEN
Solar/Wind Harmer
1.248
270291AC1-194 GEN
Solar/Wind Harmer
11.736
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.066
970065AG2-057 GEN
Solar/Wind Harmer
1.09
957541AF2-048 GEN
Solar/Wind Harmer
1.72
270512AE1-227 GEN2
Solar/Wind Harmer
2.283
253406AD2-031_GEN
Solar/Wind Harmer
1.388
270491AE1-102 GEN2
Solar/Wind Harmer
1.404
971191AH1-055 GEN
Solar/Wind Harmer
23.693
270377AD1-106 GEN
Solar/Wind Harmer
6.649
253316AC1-085 GEN3
Solar/Wind Harmer
9.014
253433AC1-085 GEN1
Solar/Wind Harmer
5.722
946181AF1-283 GEN
Solar/Wind Harmer
13.99
270191TR4_S_V150
Solar/Wind Harmer
3.224
270247TR4_N_V136
Solar/Wind Harmer
0.914
959331AF2-224 GEN
Solar/Wind Harmer
10.746
965021AG1-366 GEN
Solar/Wind Harmer
2.499
958091AF2-103 GEN
Solar/Wind Harmer
0.173
270588AE1-091_GEN
Solar/Wind Harmer
11.789
944531AF1-118 GEN
Solar/Wind Harmer
37.432
270043AE2-236 GEN
Solar/Wind Harmer
5.876
270258AD1-119 GEN
Solar/Wind Harmer
2.963
971617AH1-308 GEN
Solar/Wind Harmer
6.181
25196608WSDLE5
Adder
9.089
962031AG1-047 GEN
Solar/Wind Harmer
3.205
252510AF1-249 C
Solar/Wind Harmer
0.443
957741AF2-068 GEN
Solar/Wind Harmer
15.904
25194608D.CRK4
Adder
1.742
270222AC2-111 GEN
Solar/Wind Harmer
8.632
970031AG2-029 GEN
Solar/Wind Harmer
31.759
270044AE2-322 C
Solar/Wind Harmer
1.391
270404AC1-167 GEN
Solar/Wind Harmer
1.158
24642205MAYFLWER
Adder
0.665
25196008MFTGT1
Adder
1.406
247604X1-042
Adder
0.434
274752CRETE EC ;2U
Adder
8.489
274753CRETE EC ;3U
Adder
8.489
274772LINCOLN ;3U
Adder
8.688
274724RIVER EC ;11
Adder
18.229
24728705AND G3
Adder
8.226
274802UNIV PARK;5U
Adder
5.978
24728505AND G1
Adder
3.933
274826FISK ;BP
Adder
11.221
274800UNIV PARK;3U
Adder
5.975
972038AH1-567 GEN2
Adder
0.374
972228AH1-698 GEN2
Adder
3.796
274676JOLIET 29;8U
Adder
30.228
274729ELWOOD EC;1P
Adder
16.792
274730ELWOOD EC;6P
Adder
16.792
274734ELWOOD EC;8P
Adder
16.792
274736ELWOOD EC;9P
Adder
16.792
274682WAUKEGAN ;7U
Adder
9.742
964991AG1-363 GEN
Solar/Wind Helper
5.141
316097T157 G90
Solar/Wind Helper
1.505
23750701CROSSCHOOL
Solar/Wind Helper
1.505
238118U2-030_1
Solar/Wind Helper
0.342
238127S14_GEN_2
Solar/Wind Helper
0.829
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237080AD1-060 GEN
Solar/Wind Helper
0.342
237038AE2-054 C
Solar/Wind Helper
0.272
235062AE1-101 C1
Solar/Wind Helper
1.661
23779801AA1-109
Solar/Wind Helper
0.193
270119AB2-067 GEN1
50/50
7.072
270120AB2-067 GEN2
50/50
7.072
24318905MLG2
50/50
7.067
270471AD2-092_GEN
Solar/Wind Harmer
4.467
946101AF1-275 GEN
Solar/Wind Harmer
1.815
942861AE2-305 GEN
Solar/Wind Harmer
9.088
970077AG2-063 GEN
Solar/Wind Harmer
6.239
270224U2-072_GEN2
Solar/Wind Harmer
2.282
270227U2-072_GEN3
Solar/Wind Harmer
2.282
270228U2-072_GEN4
Solar/Wind Harmer
2.282
270231U2-072_GEN5
Solar/Wind Harmer
2.282
938701AE1-092 GEN
Solar/Wind Harmer
23.824
964601AG1-323 GEN
Solar/Wind Harmer
3.66
964601AG1-323 GEN
Solar/Wind Harmer
1.702
270518AE2-148 GEN
Solar/Wind Harmer
13.886
972269AH1-719 GEN
Adder
2.575
972159AH1-661 GEN
Adder
1.116
253378AE2-206_GEN
Solar/Wind Harmer
4.007
276820AF1-078_GEN
Solar/Wind Harmer
1.78
237048AF1-022 C
Solar/Wind Helper
0.178
223401AF1-299 GEN
Solar/Wind Helper
0.368
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.077
233930AB2-032 GEN
Solar/Wind Helper
0.381
233915AB1-141 GEN
Solar/Wind Helper
0.503
232422X3-066 FULL
Solar/Wind Helper
0.114
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.262
232404W1-003 C
Solar/Wind Helper
0.508
232428Y3-058 C
Solar/Wind Helper
0.338
233954AC2-188 GEN
Solar/Wind Helper
0.233
233950AC2-186 GEN
Solar/Wind Helper
0.116
232434Z2-077 GEN
Solar/Wind Helper
0.127
233972AC1-094 C
Solar/Wind Helper
0.303
316045AC1-158 PL2
Solar/Wind Helper
4.142
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.061
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
20720728JCB_W1-129
Solar/Wind Helper
0.057
316254AC1-120 GEN1
Solar/Wind Helper
1.06
207445AB1-138_GEN
Solar/Wind Helper
0.104
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.496
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.573
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.03
970513AG2-328 GEN
Solar/Wind Harmer
3.728
970517AG2-330 GEN
Solar/Wind Harmer
3.381
971199AH1-059 GEN
Solar/Wind Harmer
4.428
241960AC2-195 GEN
Solar/Wind Harmer
3.072
25326509SID D
Adder
1.452
970879AG2-548 GEN
Solar/Wind Harmer
6.777
971073AG2-665 GEN
Solar/Wind Harmer
6.777
971073AG2-665 GEN
Solar/Wind Harmer
4.728
25326109MON D
Adder
1.444
25322209TAIT E
Adder
10.654
25322209TAIT E
Adder
10.414
253370AE2-315 SEC1
Adder
2.184
971201AH1-060 GEN
Solar/Wind Harmer
2.179
253394AE2-221_GEN
Solar/Wind Harmer
4.918
253398AE2-221_GEN2
Solar/Wind Harmer
4.918
246938BC-WTG3
Solar/Wind Harmer
4.299
246937BC-WTG2
Solar/Wind Harmer
4.226
971231AH1-075 GEN
Solar/Wind Harmer
0.861
253317AC1-085 GEN4
Solar/Wind Harmer
9.014
970611AG2-400 GEN
Solar/Wind Harmer
10.746
270007AE1-245 C
Solar/Wind Harmer
6.359
942801AE2-298 GEN
Solar/Wind Harmer
1.622
962581AG1-107 GEN
Solar/Wind Harmer
5.366
961491AF2-440 GEN
Solar/Wind Harmer
2.23
25183208HLCRTG
Solar/Wind Harmer
6.45
944541AF1-119 GEN
Solar/Wind Harmer
4.455
960971AF2-388 GEN
Solar/Wind Harmer
11.625
942221AE2-234 GEN
Solar/Wind Harmer
0.779
252519AF1-045_GEN
Solar/Wind Harmer
6.448
252516AE2-318_GEN
Solar/Wind Harmer
4.919
247621Y3-024
Adder
0.256
970883AG2-550 GEN
Solar/Wind Harmer
10.605
970885AG2-551 GEN
Solar/Wind Harmer
2.466
270201AC2-176 GEN
Solar/Wind Harmer
5.45
25194408D.CRK1
Adder
8.014
25194508D.CRK3
Adder
1.498
964611AG1-324 GEN
Solar/Wind Harmer
1.249
964611AG1-324 GEN
Solar/Wind Harmer
0.554
252509AD1-136 GEN
Solar/Wind Harmer
0.271
247620Y3-023
Adder
0.484
24728805RICHG1
Adder
3.969
24728905RICHG2
Adder
3.969
274770LINCOLN ;1U
Adder
8.688
274771LINCOLN ;2U
Adder
8.688
274808UNIV PK N;4U
Adder
5.124
274803UNIV PARK;6U
Adder
5.978
972259AH1-714 GEN
Adder
19.535
274674JOLIET 9 ;6U
Adder
15.727
274696ROCKY RD ;4P
Adder
11.554
274695ROCKY RD ;2P
Adder
11.287
274693ROCKY RD ;1P
Adder
11.176
274697ROCKY RD ;3P
Adder
3.066
23585401KL_K28_T16
Solar/Wind Helper
1.485
238120AE2-309 GEN
Solar/Wind Helper
0.526
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.702
238170AE2-226 GEN2
Solar/Wind Helper
0.702
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237002AB1-128_GEN
Solar/Wind Helper
0.444
237034AC2-136 C
Solar/Wind Helper
0.227
235063AE1-101 C2
Solar/Wind Helper
1.661
237001AB1-127_GEN
Solar/Wind Helper
0.442
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.715
20390526W1-045 C
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.344
233933AB2-153 GEN
Solar/Wind Helper
0.233
232424Y1-079 C
Solar/Wind Helper
0.116
233944AB2-135 GEN
Solar/Wind Helper
0.589
233946AB2-136 GEN
Solar/Wind Helper
0.569
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.233
232408W1-005 C
Solar/Wind Helper
0.508
232410W1-006 C
Solar/Wind Helper
0.508
233939AC1-091 C
Solar/Wind Helper
0.35
233970AC1-092 C
Solar/Wind Helper
0.35
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.848
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.169
20674928WA_W3-044
Solar/Wind Helper
0.098
20676228FRD_X1-012
Solar/Wind Helper
0.092
964851AG1-348 GEN
Solar/Wind Helper
0.081
20674128FR_U2-059
Solar/Wind Helper
0.004
25326309TAIT D
Adder
1.197
960071AF2-298 GEN
Solar/Wind Harmer
5.441
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.066
241813AF1-122_GEN
Solar/Wind Harmer
6.974
927014AC1-188 GEN
Solar/Wind Harmer
1.725
270510AE1-227 GEN1
Solar/Wind Harmer
2.689
246936BC-WTG1
Solar/Wind Harmer
4.226
270489AE1-102 GEN1
Solar/Wind Harmer
1.404
965421AG1-410 GEN
Solar/Wind Harmer
32.386
960001AF2-291 GEN
Solar/Wind Harmer
3.255
253432AC1-085 GEN2
Solar/Wind Harmer
0.288
946171AF1-282 GEN
Solar/Wind Harmer
10.761
247521TR3_G114
Solar/Wind Harmer
3.613
270246TR4_N_V150
Solar/Wind Harmer
0.914
965011AG1-365 GEN
Solar/Wind Harmer
10.746
24695305TIMB G C
Solar/Wind Harmer
5.901
965651AG1-433 GEN
Solar/Wind Harmer
5.813
958861AF2-177 GEN
Solar/Wind Harmer
11.61
247536S-71 GEN
Solar/Wind Harmer
4.293
25194608D.CRK4
Adder
1.742
945371AF1-202 GEN
Solar/Wind Harmer
7.392
252507AC2-088 GEN
Solar/Wind Harmer
1.899
270063AE2-323 C
Solar/Wind Harmer
2.33
25196808ZIMRHP
Adder
79.831
24639705ELKHART HY
Adder
0.161
25196008MFTGT1
Adder
1.452
274751CRETE EC ;1U
Adder
8.489
274754CRETE EC ;4U
Adder
8.489
274773LINCOLN ;4U
Adder
8.688
274774LINCOLN ;5U
Adder
8.688
274723RIVER EC ;12
Adder
18.445
274812UNIV PK N;8U
Adder
5.147
24728605AND G2
Adder
3.933
274801UNIV PARK;4U
Adder
5.975
274676JOLIET 29;8U
Adder
31.348
274732ELWOOD EC;7P
Adder
16.792
274674JOLIET 9 ;6U
Adder
15.727
274745AC1-111 GEN9
Adder
5.687
970091AG2-072 GEN
Adder
77.755
316095T157 G97
Solar/Wind Helper
1.505
23583801GRNGAP
Solar/Wind Helper
5.606
238185AF2-356 C
Solar/Wind Helper
2.651
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.034
235531U2-073 GEN
Solar/Wind Helper
3.288
238117U2-030
Solar/Wind Helper
0.342
238147AE2-230_GEN1
Solar/Wind Helper
0.495
238149AF1-291A_GEN
Solar/Wind Helper
0.141
23751201ROTHROCK
Solar/Wind Helper
0.826
23562501BACKB
Solar/Wind Helper
1.01
237061AD1-155 GEN
Solar/Wind Helper
0.053
238221AF1-254 C O1
Solar/Wind Helper
0.275
235067AD1-061 GEN
Solar/Wind Helper
0.496
23751101LEADS_P59
Solar/Wind Helper
1.41
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.032
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.346
223402AF1-300 C
Solar/Wind Helper
0.368
205917AD1-020 ES
Solar/Wind Helper
0.369
233982AB2-133 GEN
Solar/Wind Helper
0.358
233918AB1-142 GEN
Solar/Wind Helper
0.503
233994AC2-023 GEN
Solar/Wind Helper
0.962
233996TM1833_GEN
Solar/Wind Helper
0.262
233997TMININ_4.2
Solar/Wind Helper
0.262
232406W1-004 FULL
Solar/Wind Helper
0.508
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.233
233971AC1-093 C
Solar/Wind Helper
0.358
316044AC1-158 PL1
Solar/Wind Helper
1.294
316450AC1-158 RIC
Solar/Wind Helper
0.345
230430AE1-229_GEN
Solar/Wind Helper
3.376
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.111
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.353
219276PARKLANDSO C
Solar/Wind Helper
0.089
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
970245AG2-165 GEN
Solar/Wind Harmer
3.728
25196108MFTGT2
Adder
1.601
25196108MFTGT2
Adder
1.486
274775LINCOLN ;6U
Adder
8.688
274776LINCOLN ;7U
Adder
8.688
274777LINCOLN ;8U
Adder
8.688
274814UNIV PK N;0U
Adder
5.192
274807UNIV PK N;3U
Adder
5.18
274805UNIV PK N;1U
Adder
5.158
274811UNIV PK N;7U
Adder
5.147
972037AH1-567 GEN1
Adder
0.188
274827FISK ;RP
Adder
7.953
972227AH1-698 GEN1
Adder
2.673
274687WILL CNTY;4U
Adder
28.564
274687WILL CNTY;4U
Adder
28.564
274675JOLIET 29;7U
Adder
31.348
274675JOLIET 29;7U
Adder
30.228
274731ELWOOD EC;2P
Adder
16.792
274733ELWOOD EC;3P
Adder
16.792
274735ELWOOD EC;4P
Adder
16.792
274728ELWOOD EC;5P
Adder
16.792
972203AH1-686 GEN
Adder
2.344
274746AC1-111 G10
Adder
5.687
274744AC1-111 GEN8
Adder
5.687
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.829
238152AF2-075_GEN
Solar/Wind Helper
0.708
238208AF1-136 C
Solar/Wind Helper
0.22
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.651
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.889
316415AF1-147_GEN2
Solar/Wind Helper
0.889
23750501ELLIOTTS
Solar/Wind Helper
0.64
959381AF2-229 GEN
Solar/Wind Helper
0.358
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.182
205943AE1-185 GEN
Solar/Wind Helper
0.51
205932AD2-116_GEN
Solar/Wind Helper
0.509
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.27
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.959
233990AG1-397 GEN
Solar/Wind Helper
0.03
234033AF1-007_GEN
Solar/Wind Helper
7.028
232432Z2-076 GEN
Solar/Wind Helper
0.067
964001AG1-254 GEN
Solar/Wind Helper
0.957
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.501
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.097
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
20675128HRM_W1-127
Solar/Wind Helper
0.03
209116AE2-175 GEN
Solar/Wind Helper
1.781
966111AG1-480 GEN
Solar/Wind Helper
0.045
211065PSPA IPP
Solar/Wind Helper
0.152
211065PSPA IPP
Solar/Wind Helper
0.152
970321AG2-212 GEN
Solar/Wind Harmer
3.728
NYPJM->LTFIMP_NY
CLTF
4.803
LGEELTFEXP_LGEE->PJM
CLTF
6.759
WECLTFEXP_WEC->PJM
CLTF
3.83
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
AH1-155LTFEXP_AH1-155->PJM
LTF
0.36
CPLELTFEXP_CPLE->PJM
CLTF
0.632
CBM West 2LTFEXP_CBM-W2->PJM
CBM
113.005
LAGNLTFEXP_LAGN->PJM
CLTF
14.864
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.83
TVALTFEXP_TVA->PJM
CLTF
7.306
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.265
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.153
MECLTFEXP_MEC->PJM
CLTF
15.925
SIGELTFEXP_SIGE->PJM
CLTF
0.506

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-015_SRT-A


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-015_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.9 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5039.69
MW Contribution:17.87
Bus #Bus NameTypeMW Contribution
24318805MLG1
50/50
10.098
23559001PLEAS1
50/50
6.112
270051AF1-062 GEN
50/50
11.831
23684201S70BUS2
50/50
0.171
270475AD2-096_GEN
50/50
7.147
970153AG2-106 GEN
Solar/Wind Harmer
17.867
961921AG1-034 GEN
Solar/Wind Harmer
15.607
241955AC1-078 GEN
Solar/Wind Harmer
8.813
24721905FLATG4
Adder
23.946
241974AD2-163_GEN2
Solar/Wind Harmer
2.331
942051AE2-217 GEN
Solar/Wind Harmer
21.048
960801AF2-371 GEN
Solar/Wind Harmer
2.948
964871AG1-351 GEN
Solar/Wind Harmer
2.036
970605AG2-385 GEN
Solar/Wind Harmer
6.24
942871AE2-306 GEN
Solar/Wind Harmer
1.047
270391AF1-285 GEN3
Solar/Wind Harmer
0.537
253338AC1-165 GEN
Solar/Wind Harmer
1.242
253333AC1-068 GEN
Solar/Wind Harmer
1.197
270485AE1-090_GEN
Solar/Wind Harmer
0.69
270273AD2-016 GEN
Solar/Wind Harmer
3.033
972173AH1-669 GEN
Solar/Wind Harmer
5.671
270291AC1-194 GEN
Solar/Wind Harmer
11.744
253415AE1-040 GEN
Solar/Wind Harmer
1.248
270512AE1-227 GEN2
Solar/Wind Harmer
2.315
970065AG2-057 GEN
Solar/Wind Harmer
1.09
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.065
957541AF2-048 GEN
Solar/Wind Harmer
1.721
253406AD2-031_GEN
Solar/Wind Harmer
1.388
270491AE1-102 GEN2
Solar/Wind Harmer
1.404
270377AD1-106 GEN
Solar/Wind Harmer
6.655
971191AH1-055 GEN
Solar/Wind Harmer
23.692
253316AC1-085 GEN3
Solar/Wind Harmer
9.013
253433AC1-085 GEN1
Solar/Wind Harmer
5.721
946181AF1-283 GEN
Solar/Wind Harmer
13.988
270191TR4_S_V150
Solar/Wind Harmer
3.223
270247TR4_N_V136
Solar/Wind Harmer
0.914
959331AF2-224 GEN
Solar/Wind Harmer
10.743
965021AG1-366 GEN
Solar/Wind Harmer
2.498
270588AE1-091_GEN
Solar/Wind Harmer
11.792
958091AF2-103 GEN
Solar/Wind Harmer
0.173
944531AF1-118 GEN
Solar/Wind Harmer
37.418
270043AE2-236 GEN
Solar/Wind Harmer
5.874
270258AD1-119 GEN
Solar/Wind Harmer
2.962
971617AH1-308 GEN
Solar/Wind Harmer
6.179
25196608WSDLE5
Adder
9.087
252510AF1-249 C
Solar/Wind Harmer
0.443
962031AG1-047 GEN
Solar/Wind Harmer
3.204
957741AF2-068 GEN
Solar/Wind Harmer
15.899
25194608D.CRK4
Adder
1.742
270222AC2-111 GEN
Solar/Wind Harmer
8.63
270166AC1-044 GEN3
50/50
7.063
23559101PLEAS2
50/50
6.112
23684101S70BUS1
50/50
0.168
962761AG1-125 GEN
Solar/Wind Harmer
40.976
970149AG2-104 GEN
Solar/Wind Harmer
50.605
970155AG2-107 GEN
Solar/Wind Harmer
17.867
270349AD2-093_GEN
Solar/Wind Harmer
4.466
24721705FLATG2
Adder
23.946
270159DARBY CT4
Adder
10.253
970593AG2-378 GEN
Solar/Wind Harmer
2.311
270223U2-072_GEN1
Solar/Wind Harmer
2.282
270578AF1-285 GEN2
Solar/Wind Harmer
1.396
270391AF1-285 GEN3
Solar/Wind Harmer
1.396
253343AC1-166 GEN
Solar/Wind Harmer
1.242
253325AC1-069 GEN
Solar/Wind Harmer
1.197
270462AD2-086
Solar/Wind Harmer
7.941
971995AH1-542 GEN
Solar/Wind Harmer
12.507
270263AC1-001 GEN
Solar/Wind Harmer
1.177
270510AE1-227 GEN1
Solar/Wind Harmer
2.727
25326309TAIT D
Adder
1.197
241813AF1-122_GEN
Solar/Wind Harmer
6.978
960071AF2-298 GEN
Solar/Wind Harmer
5.44
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.065
927014AC1-188 GEN
Solar/Wind Harmer
1.725
246936BC-WTG1
Solar/Wind Harmer
4.226
270489AE1-102 GEN1
Solar/Wind Harmer
1.404
965421AG1-410 GEN
Solar/Wind Harmer
32.379
960001AF2-291 GEN
Solar/Wind Harmer
3.256
253432AC1-085 GEN2
Solar/Wind Harmer
0.288
946171AF1-282 GEN
Solar/Wind Harmer
10.76
247521TR3_G114
Solar/Wind Harmer
3.612
270246TR4_N_V150
Solar/Wind Harmer
0.914
965011AG1-365 GEN
Solar/Wind Harmer
10.743
24695305TIMB G C
Solar/Wind Harmer
5.899
965651AG1-433 GEN
Solar/Wind Harmer
5.811
958861AF2-177 GEN
Solar/Wind Harmer
11.606
247536S-71 GEN
Solar/Wind Harmer
4.292
25194608D.CRK4
Adder
1.742
945371AF1-202 GEN
Solar/Wind Harmer
7.39
252507AC2-088 GEN
Solar/Wind Harmer
1.898
270063AE2-323 C
Solar/Wind Harmer
2.329
25196808ZIMRHP
Adder
79.816
24639705ELKHART HY
Adder
0.161
25196008MFTGT1
Adder
1.452
274751CRETE EC ;1U
Adder
8.485
274754CRETE EC ;4U
Adder
8.485
274773LINCOLN ;4U
Adder
8.684
274774LINCOLN ;5U
Adder
8.684
274723RIVER EC ;12
Adder
18.437
274812UNIV PK N;8U
Adder
5.144
24728605AND G2
Adder
3.932
274801UNIV PARK;4U
Adder
5.972
274676JOLIET 29;8U
Adder
31.334
274732ELWOOD EC;7P
Adder
16.784
274674JOLIET 9 ;6U
Adder
15.72
274745AC1-111 GEN9
Adder
5.685
970091AG2-072 GEN
Adder
77.715
316095T157 G97
Solar/Wind Helper
1.505
23583801GRNGAP
Solar/Wind Helper
5.607
238185AF2-356 C
Solar/Wind Helper
2.642
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.025
235531U2-073 GEN
Solar/Wind Helper
3.278
238117U2-030
Solar/Wind Helper
0.341
238147AE2-230_GEN1
Solar/Wind Helper
0.495
238149AF1-291A_GEN
Solar/Wind Helper
0.141
237061AD1-155 GEN
Solar/Wind Helper
0.053
23751201ROTHROCK
Solar/Wind Helper
0.819
238221AF1-254 C O1
Solar/Wind Helper
0.275
23562501BACKB
Solar/Wind Helper
1.001
235067AD1-061 GEN
Solar/Wind Helper
0.496
23751101LEADS_P59
Solar/Wind Helper
1.388
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.033
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.346
223402AF1-300 C
Solar/Wind Helper
0.368
205917AD1-020 ES
Solar/Wind Helper
0.369
233982AB2-133 GEN
Solar/Wind Helper
0.358
233918AB1-142 GEN
Solar/Wind Helper
0.503
233994AC2-023 GEN
Solar/Wind Helper
0.962
233996TM1833_GEN
Solar/Wind Helper
0.262
233997TMININ_4.2
Solar/Wind Helper
0.262
232406W1-004 FULL
Solar/Wind Helper
0.508
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.233
233971AC1-093 C
Solar/Wind Helper
0.358
316044AC1-158 PL1
Solar/Wind Helper
1.294
316450AC1-158 RIC
Solar/Wind Helper
0.345
230430AE1-229_GEN
Solar/Wind Helper
3.376
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.111
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.354
219276PARKLANDSO C
Solar/Wind Helper
0.089
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
970245AG2-165 GEN
Solar/Wind Harmer
3.726
962771AG1-126 GEN
Solar/Wind Harmer
40.976
972239AH1-704 GEN
Adder
2.69
270054AF2-122 C O1
Solar/Wind Harmer
3.996
270459AD2-067 GEN
Solar/Wind Harmer
10.248
961821AG1-024 GEN
Solar/Wind Harmer
10.404
270520AE2-214 GEN
Solar/Wind Harmer
7.276
270284AF1-227 GEN1
Solar/Wind Harmer
6.79
270286AF1-227 GEN2
Solar/Wind Harmer
2.512
270287AF1-227 GEN3
Solar/Wind Harmer
2.512
253383AE2-342_GEN
Solar/Wind Harmer
1.045
241973AD2-163_GEN1
Solar/Wind Harmer
2.331
945631AF1-228 GEN
Solar/Wind Harmer
5.463
943861AF1-054 GEN
Solar/Wind Harmer
4.486
943851AF1-053 GEN
Solar/Wind Harmer
2.168
270156DARBY CT1
Adder
10.419
270157DARBY CT2
Adder
10.393
270158DARBY CT3
Adder
10.228
970689AG2-444 GEN
Solar/Wind Harmer
18.827
270578AF1-285 GEN2
Solar/Wind Harmer
0.537
270432AC2-029 GEN
Solar/Wind Harmer
8.049
940611AE2-048 GEN
Solar/Wind Harmer
25.14
941391AE2-136 GEN
Solar/Wind Harmer
13.027
270302AB2-170 GEN
Solar/Wind Harmer
9.546
270317AD1-130_GEN
Solar/Wind Harmer
3.659
270269AC2-059
Solar/Wind Harmer
10.605
241972AD1-140 GEN
Solar/Wind Harmer
5.021
958581AF2-149 GEN
Solar/Wind Harmer
4.743
970179AG2-119 GEN
Solar/Wind Harmer
8.842
270340AC2-060 GEN
Solar/Wind Harmer
3.346
970879AG2-548 GEN
Solar/Wind Harmer
4.73
253372AE2-315 SEC3
Adder
2.065
253372AE2-315 SEC3
Adder
2.065
25306009OHH W.
Adder
3.133
253349AC2-067 GEN
Solar/Wind Harmer
5.407
253400AC2-068 GEN
Solar/Wind Harmer
2.174
957201AF2-014 GEN
Solar/Wind Harmer
4.898
270435AC2-044 GEN
Solar/Wind Harmer
2.16
965051AG1-369 GEN
Solar/Wind Harmer
5.365
965041AG1-368 GEN
Solar/Wind Harmer
10.719
247607V1-011 GEN
Solar/Wind Harmer
4.239
971567AH1-282 GEN
Solar/Wind Harmer
16.075
966831AG1-554 GEN
Solar/Wind Harmer
1.28
971989AH1-539 GEN
Solar/Wind Harmer
13.838
24729505KEY G4
Adder
6.925
963791AG1-232 GEN
Solar/Wind Harmer
14.411
270071AF1-092 GEN
Solar/Wind Harmer
15.995
971985AH1-537 GEN
Solar/Wind Harmer
18.996
958711AF2-162 GEN
Solar/Wind Harmer
1.076
270024AE2-089 GEN
Solar/Wind Harmer
4.988
270367AC2-061_GEN
Solar/Wind Harmer
3.378
965101AG1-375 GEN
Solar/Wind Harmer
10.618
971673AH1-337 GEN
Solar/Wind Harmer
4.878
252524AE2-267 GEN
Solar/Wind Harmer
1.672
25196408WSDLE3
Adder
9.354
25196308WSDLE2
Adder
9.273
25196208WSDLE1
Adder
9.25
25196708WSDLE6
Adder
9.227
25196508WSDLE4
Adder
8.994
971029AG2-637 GEN
Solar/Wind Harmer
15.905
270543AE2-219 C
Solar/Wind Harmer
5.429
961761AG1-017 GEN
Solar/Wind Harmer
0.454
945581AF1-223 GEN
Solar/Wind Harmer
4.803
270297AD1-101 GEN
Solar/Wind Harmer
2.947
944031AF1-071 GEN
Solar/Wind Harmer
1.064
25196108MFTGT2
Adder
1.6
25196108MFTGT2
Adder
1.486
274775LINCOLN ;6U
Adder
8.684
274776LINCOLN ;7U
Adder
8.684
274777LINCOLN ;8U
Adder
8.684
274814UNIV PK N;0U
Adder
5.189
274807UNIV PK N;3U
Adder
5.178
274805UNIV PK N;1U
Adder
5.156
274811UNIV PK N;7U
Adder
5.144
972037AH1-567 GEN1
Adder
0.188
274827FISK ;RP
Adder
7.949
972227AH1-698 GEN1
Adder
2.671
274687WILL CNTY;4U
Adder
28.551
274687WILL CNTY;4U
Adder
28.551
274675JOLIET 29;7U
Adder
31.334
274675JOLIET 29;7U
Adder
30.215
274731ELWOOD EC;2P
Adder
16.784
274733ELWOOD EC;3P
Adder
16.784
274735ELWOOD EC;4P
Adder
16.784
274728ELWOOD EC;5P
Adder
16.784
972203AH1-686 GEN
Adder
2.341
274746AC1-111 G10
Adder
5.685
274744AC1-111 GEN8
Adder
5.685
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.826
238152AF2-075_GEN
Solar/Wind Helper
0.708
238208AF1-136 C
Solar/Wind Helper
0.22
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.65
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.889
316415AF1-147_GEN2
Solar/Wind Helper
0.889
23750501ELLIOTTS
Solar/Wind Helper
0.637
959381AF2-229 GEN
Solar/Wind Helper
0.358
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.182
205943AE1-185 GEN
Solar/Wind Helper
0.51
205932AD2-116_GEN
Solar/Wind Helper
0.509
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.27
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.959
234033AF1-007_GEN
Solar/Wind Helper
7.028
233990AG1-397 GEN
Solar/Wind Helper
0.03
232432Z2-076 GEN
Solar/Wind Helper
0.067
964001AG1-254 GEN
Solar/Wind Helper
0.956
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.5
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.097
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
20674828DL_W4-046
Solar/Wind Helper
0.008
207484AF2-139 C O1
Solar/Wind Helper
0.084
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
20675128HRM_W1-127
Solar/Wind Helper
0.03
209116AE2-175 GEN
Solar/Wind Helper
1.781
970031AG2-029 GEN
Solar/Wind Harmer
31.748
270044AE2-322 C
Solar/Wind Harmer
1.39
270404AC1-167 GEN
Solar/Wind Harmer
1.158
24642205MAYFLWER
Adder
0.665
25196008MFTGT1
Adder
1.406
247604X1-042
Adder
0.433
274752CRETE EC ;2U
Adder
8.485
274753CRETE EC ;3U
Adder
8.485
274772LINCOLN ;3U
Adder
8.684
274724RIVER EC ;11
Adder
18.221
24728705AND G3
Adder
8.223
274802UNIV PARK;5U
Adder
5.976
24728505AND G1
Adder
3.932
274826FISK ;BP
Adder
11.216
274800UNIV PARK;3U
Adder
5.972
972038AH1-567 GEN2
Adder
0.374
972228AH1-698 GEN2
Adder
3.794
274676JOLIET 29;8U
Adder
30.215
274729ELWOOD EC;1P
Adder
16.784
274730ELWOOD EC;6P
Adder
16.784
274734ELWOOD EC;8P
Adder
16.784
274736ELWOOD EC;9P
Adder
16.784
274682WAUKEGAN ;7U
Adder
9.459
964991AG1-363 GEN
Solar/Wind Helper
5.14
316097T157 G90
Solar/Wind Helper
1.505
23750701CROSSCHOOL
Solar/Wind Helper
1.501
238118U2-030_1
Solar/Wind Helper
0.341
238127S14_GEN_2
Solar/Wind Helper
0.826
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237080AD1-060 GEN
Solar/Wind Helper
0.342
237038AE2-054 C
Solar/Wind Helper
0.272
235062AE1-101 C1
Solar/Wind Helper
1.661
23779801AA1-109
Solar/Wind Helper
0.193
237048AF1-022 C
Solar/Wind Helper
0.177
223401AF1-299 GEN
Solar/Wind Helper
0.368
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.077
233930AB2-032 GEN
Solar/Wind Helper
0.381
233915AB1-141 GEN
Solar/Wind Helper
0.503
232422X3-066 FULL
Solar/Wind Helper
0.114
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.262
232404W1-003 C
Solar/Wind Helper
0.508
232428Y3-058 C
Solar/Wind Helper
0.338
232434Z2-077 GEN
Solar/Wind Helper
0.127
233954AC2-188 GEN
Solar/Wind Helper
0.233
233950AC2-186 GEN
Solar/Wind Helper
0.116
233972AC1-094 C
Solar/Wind Helper
0.303
316045AC1-158 PL2
Solar/Wind Helper
4.142
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.06
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
20720728JCB_W1-129
Solar/Wind Helper
0.057
316254AC1-120 GEN1
Solar/Wind Helper
1.061
207445AB1-138_GEN
Solar/Wind Helper
0.104
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.496
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.573
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.03
970513AG2-328 GEN
Solar/Wind Harmer
3.726
970517AG2-330 GEN
Solar/Wind Harmer
3.379
270119AB2-067 GEN1
50/50
7.063
270120AB2-067 GEN2
50/50
7.063
24318905MLG2
50/50
7.074
270471AD2-092_GEN
Solar/Wind Harmer
4.466
946101AF1-275 GEN
Solar/Wind Harmer
1.816
942861AE2-305 GEN
Solar/Wind Harmer
9.089
970077AG2-063 GEN
Solar/Wind Harmer
6.24
270224U2-072_GEN2
Solar/Wind Harmer
2.282
270227U2-072_GEN3
Solar/Wind Harmer
2.282
270228U2-072_GEN4
Solar/Wind Harmer
2.282
270231U2-072_GEN5
Solar/Wind Harmer
2.282
938701AE1-092 GEN
Solar/Wind Harmer
23.829
964601AG1-323 GEN
Solar/Wind Harmer
3.66
964601AG1-323 GEN
Solar/Wind Harmer
1.702
270518AE2-148 GEN
Solar/Wind Harmer
13.889
972269AH1-719 GEN
Adder
2.587
972159AH1-661 GEN
Adder
1.119
253378AE2-206_GEN
Solar/Wind Harmer
4.007
276820AF1-078_GEN
Solar/Wind Harmer
1.78
971199AH1-059 GEN
Solar/Wind Harmer
4.433
241960AC2-195 GEN
Solar/Wind Harmer
3.073
25326509SID D
Adder
1.452
970879AG2-548 GEN
Solar/Wind Harmer
6.78
971073AG2-665 GEN
Solar/Wind Harmer
6.78
971073AG2-665 GEN
Solar/Wind Harmer
4.73
25326109MON D
Adder
1.444
25322209TAIT E
Adder
10.653
25322209TAIT E
Adder
10.414
971201AH1-060 GEN
Solar/Wind Harmer
2.181
253370AE2-315 SEC1
Adder
2.184
253394AE2-221_GEN
Solar/Wind Harmer
4.918
253398AE2-221_GEN2
Solar/Wind Harmer
4.918
246938BC-WTG3
Solar/Wind Harmer
4.299
246937BC-WTG2
Solar/Wind Harmer
4.226
971231AH1-075 GEN
Solar/Wind Harmer
0.862
253317AC1-085 GEN4
Solar/Wind Harmer
9.013
970611AG2-400 GEN
Solar/Wind Harmer
10.743
270007AE1-245 C
Solar/Wind Harmer
6.358
942801AE2-298 GEN
Solar/Wind Harmer
1.622
962581AG1-107 GEN
Solar/Wind Harmer
5.365
961491AF2-440 GEN
Solar/Wind Harmer
2.229
25183208HLCRTG
Solar/Wind Harmer
6.449
944541AF1-119 GEN
Solar/Wind Harmer
4.453
960971AF2-388 GEN
Solar/Wind Harmer
11.621
942221AE2-234 GEN
Solar/Wind Harmer
0.778
252519AF1-045_GEN
Solar/Wind Harmer
6.447
252516AE2-318_GEN
Solar/Wind Harmer
4.918
247621Y3-024
Adder
0.256
970883AG2-550 GEN
Solar/Wind Harmer
10.602
970885AG2-551 GEN
Solar/Wind Harmer
2.465
270201AC2-176 GEN
Solar/Wind Harmer
5.449
25194408D.CRK1
Adder
8.013
25194508D.CRK3
Adder
1.498
964611AG1-324 GEN
Solar/Wind Harmer
1.248
964611AG1-324 GEN
Solar/Wind Harmer
0.554
252509AD1-136 GEN
Solar/Wind Harmer
0.271
247620Y3-023
Adder
0.484
24728805RICHG1
Adder
3.968
24728905RICHG2
Adder
3.968
274770LINCOLN ;1U
Adder
8.684
274771LINCOLN ;2U
Adder
8.684
274808UNIV PK N;4U
Adder
5.122
274803UNIV PARK;6U
Adder
5.976
972259AH1-714 GEN
Adder
19.527
274674JOLIET 9 ;6U
Adder
15.72
274696ROCKY RD ;4P
Adder
11.549
274695ROCKY RD ;2P
Adder
11.282
274693ROCKY RD ;1P
Adder
11.171
274697ROCKY RD ;3P
Adder
3.065
23585401KL_K28_T16
Solar/Wind Helper
1.478
238120AE2-309 GEN
Solar/Wind Helper
0.524
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.702
238170AE2-226 GEN2
Solar/Wind Helper
0.702
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237034AC2-136 C
Solar/Wind Helper
0.227
237002AB1-128_GEN
Solar/Wind Helper
0.443
235063AE1-101 C2
Solar/Wind Helper
1.661
237001AB1-127_GEN
Solar/Wind Helper
0.442
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.715
20390526W1-045 C
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.344
233933AB2-153 GEN
Solar/Wind Helper
0.233
232424Y1-079 C
Solar/Wind Helper
0.116
233944AB2-135 GEN
Solar/Wind Helper
0.589
233946AB2-136 GEN
Solar/Wind Helper
0.569
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.233
232408W1-005 C
Solar/Wind Helper
0.508
232410W1-006 C
Solar/Wind Helper
0.508
233939AC1-091 C
Solar/Wind Helper
0.35
233970AC1-092 C
Solar/Wind Helper
0.35
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.848
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.169
20674928WA_W3-044
Solar/Wind Helper
0.098
964851AG1-348 GEN
Solar/Wind Helper
0.081
20676228FRD_X1-012
Solar/Wind Helper
0.092
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.045
211065PSPA IPP
Solar/Wind Helper
0.152
211065PSPA IPP
Solar/Wind Helper
0.152
970321AG2-212 GEN
Solar/Wind Harmer
3.726
NYPJM->LTFIMP_NY
CLTF
4.803
LGEELTFEXP_LGEE->PJM
CLTF
6.756
WECLTFEXP_WEC->PJM
CLTF
3.828
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
AH1-155LTFEXP_AH1-155->PJM
LTF
0.36
CPLELTFEXP_CPLE->PJM
CLTF
0.627
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.944
LAGNLTFEXP_LAGN->PJM
CLTF
14.855
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.816
TVALTFEXP_TVA->PJM
CLTF
7.302
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.216
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.135
MECLTFEXP_MEC->PJM
CLTF
15.918
SIGELTFEXP_SIGE->PJM
CLTF
0.506

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-014_SRT-A


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.9 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5039.69
MW Contribution:17.87
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
7.063
23559101PLEAS2
50/50
6.112
23684101S70BUS1
50/50
0.168
962761AG1-125 GEN
Solar/Wind Harmer
40.976
970149AG2-104 GEN
Solar/Wind Harmer
50.605
970155AG2-107 GEN
Solar/Wind Harmer
17.867
270349AD2-093_GEN
Solar/Wind Harmer
4.466
24721705FLATG2
Adder
23.946
270159DARBY CT4
Adder
10.253
970593AG2-378 GEN
Solar/Wind Harmer
2.311
270223U2-072_GEN1
Solar/Wind Harmer
2.282
270578AF1-285 GEN2
Solar/Wind Harmer
1.396
270391AF1-285 GEN3
Solar/Wind Harmer
1.396
253343AC1-166 GEN
Solar/Wind Harmer
1.242
253325AC1-069 GEN
Solar/Wind Harmer
1.197
270462AD2-086
Solar/Wind Harmer
7.941
971995AH1-542 GEN
Solar/Wind Harmer
12.507
270263AC1-001 GEN
Solar/Wind Harmer
1.177
270510AE1-227 GEN1
Solar/Wind Harmer
2.727
25326309TAIT D
Adder
1.197
241813AF1-122_GEN
Solar/Wind Harmer
6.978
960071AF2-298 GEN
Solar/Wind Harmer
5.44
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.065
927014AC1-188 GEN
Solar/Wind Harmer
1.725
246936BC-WTG1
Solar/Wind Harmer
4.226
270489AE1-102 GEN1
Solar/Wind Harmer
1.404
965421AG1-410 GEN
Solar/Wind Harmer
32.379
960001AF2-291 GEN
Solar/Wind Harmer
3.256
253432AC1-085 GEN2
Solar/Wind Harmer
0.288
946171AF1-282 GEN
Solar/Wind Harmer
10.76
247521TR3_G114
Solar/Wind Harmer
3.612
270246TR4_N_V150
Solar/Wind Harmer
0.914
965011AG1-365 GEN
Solar/Wind Harmer
10.743
24695305TIMB G C
Solar/Wind Harmer
5.899
965651AG1-433 GEN
Solar/Wind Harmer
5.811
958861AF2-177 GEN
Solar/Wind Harmer
11.606
247536S-71 GEN
Solar/Wind Harmer
4.292
25194608D.CRK4
Adder
1.742
945371AF1-202 GEN
Solar/Wind Harmer
7.39
252507AC2-088 GEN
Solar/Wind Harmer
1.898
270063AE2-323 C
Solar/Wind Harmer
2.329
25196808ZIMRHP
Adder
79.816
24639705ELKHART HY
Adder
0.161
25196008MFTGT1
Adder
1.452
274751CRETE EC ;1U
Adder
8.485
274754CRETE EC ;4U
Adder
8.485
274773LINCOLN ;4U
Adder
8.684
274774LINCOLN ;5U
Adder
8.684
274723RIVER EC ;12
Adder
18.437
274812UNIV PK N;8U
Adder
5.144
24728605AND G2
Adder
3.932
274801UNIV PARK;4U
Adder
5.972
274676JOLIET 29;8U
Adder
31.334
274732ELWOOD EC;7P
Adder
16.784
274674JOLIET 9 ;6U
Adder
15.72
274745AC1-111 GEN9
Adder
5.685
970091AG2-072 GEN
Adder
77.715
316095T157 G97
Solar/Wind Helper
1.505
23583801GRNGAP
Solar/Wind Helper
5.607
238185AF2-356 C
Solar/Wind Helper
2.642
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.025
235531U2-073 GEN
Solar/Wind Helper
3.278
238117U2-030
Solar/Wind Helper
0.341
238147AE2-230_GEN1
Solar/Wind Helper
0.495
238149AF1-291A_GEN
Solar/Wind Helper
0.141
237061AD1-155 GEN
Solar/Wind Helper
0.053
23751201ROTHROCK
Solar/Wind Helper
0.819
238221AF1-254 C O1
Solar/Wind Helper
0.275
23562501BACKB
Solar/Wind Helper
1.001
235067AD1-061 GEN
Solar/Wind Helper
0.496
23751101LEADS_P59
Solar/Wind Helper
1.388
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.033
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.346
223402AF1-300 C
Solar/Wind Helper
0.368
205917AD1-020 ES
Solar/Wind Helper
0.369
233982AB2-133 GEN
Solar/Wind Helper
0.358
233918AB1-142 GEN
Solar/Wind Helper
0.503
233994AC2-023 GEN
Solar/Wind Helper
0.962
233996TM1833_GEN
Solar/Wind Helper
0.262
233997TMININ_4.2
Solar/Wind Helper
0.262
232406W1-004 FULL
Solar/Wind Helper
0.508
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.233
233971AC1-093 C
Solar/Wind Helper
0.358
316044AC1-158 PL1
Solar/Wind Helper
1.294
316450AC1-158 RIC
Solar/Wind Helper
0.345
230430AE1-229_GEN
Solar/Wind Helper
3.376
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.111
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.354
219276PARKLANDSO C
Solar/Wind Helper
0.089
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
970245AG2-165 GEN
Solar/Wind Harmer
3.726
962771AG1-126 GEN
Solar/Wind Harmer
40.976
972239AH1-704 GEN
Adder
2.69
270054AF2-122 C O1
Solar/Wind Harmer
3.996
270459AD2-067 GEN
Solar/Wind Harmer
10.248
961821AG1-024 GEN
Solar/Wind Harmer
10.404
270520AE2-214 GEN
Solar/Wind Harmer
7.276
270284AF1-227 GEN1
Solar/Wind Harmer
6.79
270286AF1-227 GEN2
Solar/Wind Harmer
2.512
270287AF1-227 GEN3
Solar/Wind Harmer
2.512
253383AE2-342_GEN
Solar/Wind Harmer
1.045
241973AD2-163_GEN1
Solar/Wind Harmer
2.331
945631AF1-228 GEN
Solar/Wind Harmer
5.463
943861AF1-054 GEN
Solar/Wind Harmer
4.486
943851AF1-053 GEN
Solar/Wind Harmer
2.168
270156DARBY CT1
Adder
10.419
270157DARBY CT2
Adder
10.393
270158DARBY CT3
Adder
10.228
970689AG2-444 GEN
Solar/Wind Harmer
18.827
270578AF1-285 GEN2
Solar/Wind Harmer
0.537
270432AC2-029 GEN
Solar/Wind Harmer
8.049
940611AE2-048 GEN
Solar/Wind Harmer
25.14
941391AE2-136 GEN
Solar/Wind Harmer
13.027
270302AB2-170 GEN
Solar/Wind Harmer
9.546
270317AD1-130_GEN
Solar/Wind Harmer
3.659
270269AC2-059
Solar/Wind Harmer
10.605
241972AD1-140 GEN
Solar/Wind Harmer
5.021
958581AF2-149 GEN
Solar/Wind Harmer
4.743
970179AG2-119 GEN
Solar/Wind Harmer
8.842
270340AC2-060 GEN
Solar/Wind Harmer
3.346
970879AG2-548 GEN
Solar/Wind Harmer
4.73
253372AE2-315 SEC3
Adder
2.065
253372AE2-315 SEC3
Adder
2.065
25306009OHH W.
Adder
3.133
253349AC2-067 GEN
Solar/Wind Harmer
5.407
253400AC2-068 GEN
Solar/Wind Harmer
2.174
957201AF2-014 GEN
Solar/Wind Harmer
4.898
270435AC2-044 GEN
Solar/Wind Harmer
2.16
965051AG1-369 GEN
Solar/Wind Harmer
5.365
965041AG1-368 GEN
Solar/Wind Harmer
10.719
247607V1-011 GEN
Solar/Wind Harmer
4.239
971567AH1-282 GEN
Solar/Wind Harmer
16.075
966831AG1-554 GEN
Solar/Wind Harmer
1.28
971989AH1-539 GEN
Solar/Wind Harmer
13.838
24729505KEY G4
Adder
6.925
963791AG1-232 GEN
Solar/Wind Harmer
14.411
270071AF1-092 GEN
Solar/Wind Harmer
15.995
971985AH1-537 GEN
Solar/Wind Harmer
18.996
958711AF2-162 GEN
Solar/Wind Harmer
1.076
270024AE2-089 GEN
Solar/Wind Harmer
4.988
270367AC2-061_GEN
Solar/Wind Harmer
3.378
965101AG1-375 GEN
Solar/Wind Harmer
10.618
971673AH1-337 GEN
Solar/Wind Harmer
4.878
252524AE2-267 GEN
Solar/Wind Harmer
1.672
25196408WSDLE3
Adder
9.354
25196308WSDLE2
Adder
9.273
25196208WSDLE1
Adder
9.25
25196708WSDLE6
Adder
9.227
25196508WSDLE4
Adder
8.994
971029AG2-637 GEN
Solar/Wind Harmer
15.905
270543AE2-219 C
Solar/Wind Harmer
5.429
961761AG1-017 GEN
Solar/Wind Harmer
0.454
945581AF1-223 GEN
Solar/Wind Harmer
4.803
270297AD1-101 GEN
Solar/Wind Harmer
2.947
944031AF1-071 GEN
Solar/Wind Harmer
1.064
25196108MFTGT2
Adder
1.6
25196108MFTGT2
Adder
1.486
274775LINCOLN ;6U
Adder
8.684
274776LINCOLN ;7U
Adder
8.684
274777LINCOLN ;8U
Adder
8.684
274814UNIV PK N;0U
Adder
5.189
274807UNIV PK N;3U
Adder
5.178
274805UNIV PK N;1U
Adder
5.156
274811UNIV PK N;7U
Adder
5.144
972037AH1-567 GEN1
Adder
0.188
274827FISK ;RP
Adder
7.949
972227AH1-698 GEN1
Adder
2.671
274687WILL CNTY;4U
Adder
28.551
274687WILL CNTY;4U
Adder
28.551
274675JOLIET 29;7U
Adder
31.334
274675JOLIET 29;7U
Adder
30.215
274731ELWOOD EC;2P
Adder
16.784
274733ELWOOD EC;3P
Adder
16.784
274735ELWOOD EC;4P
Adder
16.784
274728ELWOOD EC;5P
Adder
16.784
972203AH1-686 GEN
Adder
2.341
274746AC1-111 G10
Adder
5.685
274744AC1-111 GEN8
Adder
5.685
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.826
238152AF2-075_GEN
Solar/Wind Helper
0.708
238208AF1-136 C
Solar/Wind Helper
0.22
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.65
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.889
316415AF1-147_GEN2
Solar/Wind Helper
0.889
23750501ELLIOTTS
Solar/Wind Helper
0.637
959381AF2-229 GEN
Solar/Wind Helper
0.358
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.182
205943AE1-185 GEN
Solar/Wind Helper
0.51
205932AD2-116_GEN
Solar/Wind Helper
0.509
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.27
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.959
234033AF1-007_GEN
Solar/Wind Helper
7.028
233990AG1-397 GEN
Solar/Wind Helper
0.03
232432Z2-076 GEN
Solar/Wind Helper
0.067
964001AG1-254 GEN
Solar/Wind Helper
0.956
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.5
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.097
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
20674828DL_W4-046
Solar/Wind Helper
0.008
207484AF2-139 C O1
Solar/Wind Helper
0.084
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
20675128HRM_W1-127
Solar/Wind Helper
0.03
209116AE2-175 GEN
Solar/Wind Helper
1.781
24318805MLG1
50/50
10.098
23559001PLEAS1
50/50
6.112
270051AF1-062 GEN
50/50
11.831
23684201S70BUS2
50/50
0.171
270475AD2-096_GEN
50/50
7.147
970153AG2-106 GEN
Solar/Wind Harmer
17.867
961921AG1-034 GEN
Solar/Wind Harmer
15.607
241955AC1-078 GEN
Solar/Wind Harmer
8.813
24721905FLATG4
Adder
23.946
241974AD2-163_GEN2
Solar/Wind Harmer
2.331
942051AE2-217 GEN
Solar/Wind Harmer
21.048
960801AF2-371 GEN
Solar/Wind Harmer
2.948
964871AG1-351 GEN
Solar/Wind Harmer
2.036
970605AG2-385 GEN
Solar/Wind Harmer
6.24
942871AE2-306 GEN
Solar/Wind Harmer
1.047
270391AF1-285 GEN3
Solar/Wind Harmer
0.537
253338AC1-165 GEN
Solar/Wind Harmer
1.242
253333AC1-068 GEN
Solar/Wind Harmer
1.197
270485AE1-090_GEN
Solar/Wind Harmer
0.69
270273AD2-016 GEN
Solar/Wind Harmer
3.033
972173AH1-669 GEN
Solar/Wind Harmer
5.671
270291AC1-194 GEN
Solar/Wind Harmer
11.744
253415AE1-040 GEN
Solar/Wind Harmer
1.248
270512AE1-227 GEN2
Solar/Wind Harmer
2.315
970065AG2-057 GEN
Solar/Wind Harmer
1.09
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.065
957541AF2-048 GEN
Solar/Wind Harmer
1.721
253406AD2-031_GEN
Solar/Wind Harmer
1.388
270491AE1-102 GEN2
Solar/Wind Harmer
1.404
270377AD1-106 GEN
Solar/Wind Harmer
6.655
971191AH1-055 GEN
Solar/Wind Harmer
23.692
253316AC1-085 GEN3
Solar/Wind Harmer
9.013
253433AC1-085 GEN1
Solar/Wind Harmer
5.721
946181AF1-283 GEN
Solar/Wind Harmer
13.988
270191TR4_S_V150
Solar/Wind Harmer
3.223
270247TR4_N_V136
Solar/Wind Harmer
0.914
959331AF2-224 GEN
Solar/Wind Harmer
10.743
965021AG1-366 GEN
Solar/Wind Harmer
2.498
270588AE1-091_GEN
Solar/Wind Harmer
11.792
958091AF2-103 GEN
Solar/Wind Harmer
0.173
944531AF1-118 GEN
Solar/Wind Harmer
37.418
270043AE2-236 GEN
Solar/Wind Harmer
5.874
270258AD1-119 GEN
Solar/Wind Harmer
2.962
971617AH1-308 GEN
Solar/Wind Harmer
6.179
25196608WSDLE5
Adder
9.087
252510AF1-249 C
Solar/Wind Harmer
0.443
962031AG1-047 GEN
Solar/Wind Harmer
3.204
957741AF2-068 GEN
Solar/Wind Harmer
15.899
25194608D.CRK4
Adder
1.742
270222AC2-111 GEN
Solar/Wind Harmer
8.63
970031AG2-029 GEN
Solar/Wind Harmer
31.748
270044AE2-322 C
Solar/Wind Harmer
1.39
270404AC1-167 GEN
Solar/Wind Harmer
1.158
24642205MAYFLWER
Adder
0.665
25196008MFTGT1
Adder
1.406
247604X1-042
Adder
0.433
274752CRETE EC ;2U
Adder
8.485
274753CRETE EC ;3U
Adder
8.485
274772LINCOLN ;3U
Adder
8.684
274724RIVER EC ;11
Adder
18.221
24728705AND G3
Adder
8.223
274802UNIV PARK;5U
Adder
5.976
24728505AND G1
Adder
3.932
274826FISK ;BP
Adder
11.216
274800UNIV PARK;3U
Adder
5.972
972038AH1-567 GEN2
Adder
0.374
972228AH1-698 GEN2
Adder
3.794
274676JOLIET 29;8U
Adder
30.215
274729ELWOOD EC;1P
Adder
16.784
274730ELWOOD EC;6P
Adder
16.784
274734ELWOOD EC;8P
Adder
16.784
274736ELWOOD EC;9P
Adder
16.784
274682WAUKEGAN ;7U
Adder
9.459
964991AG1-363 GEN
Solar/Wind Helper
5.14
316097T157 G90
Solar/Wind Helper
1.505
23750701CROSSCHOOL
Solar/Wind Helper
1.501
238118U2-030_1
Solar/Wind Helper
0.341
238127S14_GEN_2
Solar/Wind Helper
0.826
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237080AD1-060 GEN
Solar/Wind Helper
0.342
237038AE2-054 C
Solar/Wind Helper
0.272
235062AE1-101 C1
Solar/Wind Helper
1.661
23779801AA1-109
Solar/Wind Helper
0.193
237048AF1-022 C
Solar/Wind Helper
0.177
223401AF1-299 GEN
Solar/Wind Helper
0.368
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.077
233930AB2-032 GEN
Solar/Wind Helper
0.381
233915AB1-141 GEN
Solar/Wind Helper
0.503
232422X3-066 FULL
Solar/Wind Helper
0.114
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.262
232404W1-003 C
Solar/Wind Helper
0.508
232428Y3-058 C
Solar/Wind Helper
0.338
232434Z2-077 GEN
Solar/Wind Helper
0.127
233954AC2-188 GEN
Solar/Wind Helper
0.233
233950AC2-186 GEN
Solar/Wind Helper
0.116
233972AC1-094 C
Solar/Wind Helper
0.303
316045AC1-158 PL2
Solar/Wind Helper
4.142
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.06
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
20720728JCB_W1-129
Solar/Wind Helper
0.057
316254AC1-120 GEN1
Solar/Wind Helper
1.061
207445AB1-138_GEN
Solar/Wind Helper
0.104
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.496
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.573
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.03
970513AG2-328 GEN
Solar/Wind Harmer
3.726
970517AG2-330 GEN
Solar/Wind Harmer
3.379
270119AB2-067 GEN1
50/50
7.063
270120AB2-067 GEN2
50/50
7.063
24318905MLG2
50/50
7.074
270471AD2-092_GEN
Solar/Wind Harmer
4.466
946101AF1-275 GEN
Solar/Wind Harmer
1.816
942861AE2-305 GEN
Solar/Wind Harmer
9.089
970077AG2-063 GEN
Solar/Wind Harmer
6.24
270224U2-072_GEN2
Solar/Wind Harmer
2.282
270227U2-072_GEN3
Solar/Wind Harmer
2.282
270228U2-072_GEN4
Solar/Wind Harmer
2.282
270231U2-072_GEN5
Solar/Wind Harmer
2.282
938701AE1-092 GEN
Solar/Wind Harmer
23.829
964601AG1-323 GEN
Solar/Wind Harmer
3.66
964601AG1-323 GEN
Solar/Wind Harmer
1.702
270518AE2-148 GEN
Solar/Wind Harmer
13.889
972269AH1-719 GEN
Adder
2.587
972159AH1-661 GEN
Adder
1.119
253378AE2-206_GEN
Solar/Wind Harmer
4.007
276820AF1-078_GEN
Solar/Wind Harmer
1.78
971199AH1-059 GEN
Solar/Wind Harmer
4.433
241960AC2-195 GEN
Solar/Wind Harmer
3.073
25326509SID D
Adder
1.452
970879AG2-548 GEN
Solar/Wind Harmer
6.78
971073AG2-665 GEN
Solar/Wind Harmer
6.78
971073AG2-665 GEN
Solar/Wind Harmer
4.73
25326109MON D
Adder
1.444
25322209TAIT E
Adder
10.653
25322209TAIT E
Adder
10.414
971201AH1-060 GEN
Solar/Wind Harmer
2.181
253370AE2-315 SEC1
Adder
2.184
253394AE2-221_GEN
Solar/Wind Harmer
4.918
253398AE2-221_GEN2
Solar/Wind Harmer
4.918
246938BC-WTG3
Solar/Wind Harmer
4.299
246937BC-WTG2
Solar/Wind Harmer
4.226
971231AH1-075 GEN
Solar/Wind Harmer
0.862
253317AC1-085 GEN4
Solar/Wind Harmer
9.013
970611AG2-400 GEN
Solar/Wind Harmer
10.743
270007AE1-245 C
Solar/Wind Harmer
6.358
942801AE2-298 GEN
Solar/Wind Harmer
1.622
962581AG1-107 GEN
Solar/Wind Harmer
5.365
961491AF2-440 GEN
Solar/Wind Harmer
2.229
25183208HLCRTG
Solar/Wind Harmer
6.449
944541AF1-119 GEN
Solar/Wind Harmer
4.453
960971AF2-388 GEN
Solar/Wind Harmer
11.621
942221AE2-234 GEN
Solar/Wind Harmer
0.778
252519AF1-045_GEN
Solar/Wind Harmer
6.447
252516AE2-318_GEN
Solar/Wind Harmer
4.918
247621Y3-024
Adder
0.256
970883AG2-550 GEN
Solar/Wind Harmer
10.602
970885AG2-551 GEN
Solar/Wind Harmer
2.465
270201AC2-176 GEN
Solar/Wind Harmer
5.449
25194408D.CRK1
Adder
8.013
25194508D.CRK3
Adder
1.498
964611AG1-324 GEN
Solar/Wind Harmer
1.248
964611AG1-324 GEN
Solar/Wind Harmer
0.554
252509AD1-136 GEN
Solar/Wind Harmer
0.271
247620Y3-023
Adder
0.484
24728805RICHG1
Adder
3.968
24728905RICHG2
Adder
3.968
274770LINCOLN ;1U
Adder
8.684
274771LINCOLN ;2U
Adder
8.684
274808UNIV PK N;4U
Adder
5.122
274803UNIV PARK;6U
Adder
5.976
972259AH1-714 GEN
Adder
19.527
274674JOLIET 9 ;6U
Adder
15.72
274696ROCKY RD ;4P
Adder
11.549
274695ROCKY RD ;2P
Adder
11.282
274693ROCKY RD ;1P
Adder
11.171
274697ROCKY RD ;3P
Adder
3.065
23585401KL_K28_T16
Solar/Wind Helper
1.478
238120AE2-309 GEN
Solar/Wind Helper
0.524
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.702
238170AE2-226 GEN2
Solar/Wind Helper
0.702
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237034AC2-136 C
Solar/Wind Helper
0.227
237002AB1-128_GEN
Solar/Wind Helper
0.443
235063AE1-101 C2
Solar/Wind Helper
1.661
237001AB1-127_GEN
Solar/Wind Helper
0.442
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.715
20390526W1-045 C
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.344
233933AB2-153 GEN
Solar/Wind Helper
0.233
232424Y1-079 C
Solar/Wind Helper
0.116
233944AB2-135 GEN
Solar/Wind Helper
0.589
233946AB2-136 GEN
Solar/Wind Helper
0.569
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.233
232408W1-005 C
Solar/Wind Helper
0.508
232410W1-006 C
Solar/Wind Helper
0.508
233939AC1-091 C
Solar/Wind Helper
0.35
233970AC1-092 C
Solar/Wind Helper
0.35
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.848
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.169
20674928WA_W3-044
Solar/Wind Helper
0.098
964851AG1-348 GEN
Solar/Wind Helper
0.081
20676228FRD_X1-012
Solar/Wind Helper
0.092
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.045
211065PSPA IPP
Solar/Wind Helper
0.152
211065PSPA IPP
Solar/Wind Helper
0.152
970321AG2-212 GEN
Solar/Wind Harmer
3.726
NYPJM->LTFIMP_NY
CLTF
4.803
LGEELTFEXP_LGEE->PJM
CLTF
6.756
WECLTFEXP_WEC->PJM
CLTF
3.828
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
AH1-155LTFEXP_AH1-155->PJM
LTF
0.36
CPLELTFEXP_CPLE->PJM
CLTF
0.627
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.944
LAGNLTFEXP_LAGN->PJM
CLTF
14.855
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.816
TVALTFEXP_TVA->PJM
CLTF
7.302
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.216
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.135
MECLTFEXP_MEC->PJM
CLTF
15.918
SIGELTFEXP_SIGE->PJM
CLTF
0.506

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P1-2_MP-500-007A_SRT-A


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P1-2_MP-500-007A_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:131.92 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5002.28
MW Contribution:22.05
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
7.059
23559101PLEAS2
50/50
6.1
962761AG1-125 GEN
Solar/Wind Harmer
34.524
970149AG2-104 GEN
Solar/Wind Harmer
37.287
970155AG2-107 GEN
Solar/Wind Harmer
22.046
270349AD2-093_GEN
Solar/Wind Harmer
0.006
24721705FLATG2
Adder
23.918
270159DARBY CT4
Adder
10.243
970593AG2-378 GEN
Solar/Wind Harmer
1.812
270223U2-072_GEN1
Solar/Wind Harmer
0.001
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.012
270462AD2-086
Solar/Wind Harmer
0.017
971995AH1-542 GEN
Solar/Wind Harmer
2.906
270263AC1-001 GEN
Solar/Wind Harmer
0.786
270510AE1-227 GEN1
Solar/Wind Harmer
1.963
25326309TAIT D
Adder
1.196
241813AF1-122_GEN
Solar/Wind Harmer
3.405
960071AF2-298 GEN
Solar/Wind Harmer
3.786
253370AE2-315 SEC1
Adder
2.182
253371AE2-315 SEC2
Adder
2.063
927014AC1-188 GEN
Solar/Wind Harmer
0.005
246936BC-WTG1
Solar/Wind Harmer
0.305
270489AE1-102 GEN1
Solar/Wind Harmer
0.979
965421AG1-410 GEN
Solar/Wind Harmer
22.57
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.499
247521TR3_G114
Solar/Wind Harmer
0.273
270246TR4_N_V150
Solar/Wind Harmer
0.048
965011AG1-365 GEN
Solar/Wind Harmer
7.488
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
2.174
958861AF2-177 GEN
Solar/Wind Harmer
3.207
247536S-71 GEN
Solar/Wind Harmer
0.297
25194608D.CRK4
Adder
1.74
945371AF1-202 GEN
Solar/Wind Harmer
0.001
252507AC2-088 GEN
Solar/Wind Harmer
0.335
270063AE2-323 C
Solar/Wind Harmer
0.006
970245AG2-165 GEN
Solar/Wind Harmer
3.191
970947AG2-589 GEN
Solar/Wind Harmer
0.245
270005AE1-210 C O1
Solar/Wind Harmer
1.59
965031AG1-367 GEN
Solar/Wind Harmer
7.338
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.378
970825AG2-519 GEN
Solar/Wind Harmer
2.603
25196808ZIMRHP
Adder
79.729
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
944231AF1-091 GEN
Solar/Wind Harmer
1.953
24639705ELKHART HY
Adder
0.161
270032AE2-172
Solar/Wind Harmer
4.877
970291AG2-192 GEN
Solar/Wind Harmer
0.95
945111AF1-176 GEN
Solar/Wind Harmer
13.03
270505AE1-170 C O1
Solar/Wind Harmer
7.665
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.805
276903AD2-071 C
Solar/Wind Harmer
8.137
25196008MFTGT1
Adder
1.45
247522W1-056 GEN
Solar/Wind Harmer
0.001
970773AG2-487 GEN
Solar/Wind Harmer
1.284
970373AG2-245 GEN
Solar/Wind Harmer
15.247
270055AF2-134 C O1
Solar/Wind Harmer
0.006
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.41
970515AG2-329 GEN
Solar/Wind Harmer
18.805
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
9.032
24791305MDL-5G
Solar/Wind Harmer
0.001
970333AG2-219 GEN
Solar/Wind Harmer
5.139
274751CRETE EC ;1U
Adder
8.477
274754CRETE EC ;4U
Adder
8.477
274773LINCOLN ;4U
Adder
8.676
274774LINCOLN ;5U
Adder
8.676
274723RIVER EC ;12
Adder
18.418
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
5.139
24728605AND G2
Adder
3.927
276776AD2-060 GEN
Solar/Wind Harmer
0.746
945681AF1-233 GEN
Solar/Wind Harmer
13.461
274801UNIV PARK;4U
Adder
5.966
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
31.303
274732ELWOOD EC;7P
Adder
16.768
274674JOLIET 9 ;6U
Adder
15.704
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
16.815
274745AC1-111 GEN9
Adder
5.679
939401AE1-172 GEN
Solar/Wind Harmer
5.301
276691AA1-018 GEN1
Solar/Wind Harmer
0.858
970091AG2-072 GEN
Adder
77.629
276901AD2-066 C O1
Solar/Wind Harmer
0.007
316095T157 G97
Solar/Wind Helper
1.504
23583801GRNGAP
Solar/Wind Helper
5.601
238185AF2-356 C
Solar/Wind Helper
2.646
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.03
235531U2-073 GEN
Solar/Wind Helper
3.282
238117U2-030
Solar/Wind Helper
0.341
238147AE2-230_GEN1
Solar/Wind Helper
0.495
238149AF1-291A_GEN
Solar/Wind Helper
0.141
23751201ROTHROCK
Solar/Wind Helper
0.824
237061AD1-155 GEN
Solar/Wind Helper
0.053
23562501BACKB
Solar/Wind Helper
1.007
238221AF1-254 C O1
Solar/Wind Helper
0.274
235067AD1-061 GEN
Solar/Wind Helper
0.496
23751101LEADS_P59
Solar/Wind Helper
1.404
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.032
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.346
223402AF1-300 C
Solar/Wind Helper
0.367
205917AD1-020 ES
Solar/Wind Helper
0.368
233918AB1-142 GEN
Solar/Wind Helper
0.502
233982AB2-133 GEN
Solar/Wind Helper
0.358
233994AC2-023 GEN
Solar/Wind Helper
0.961
233996TM1833_GEN
Solar/Wind Helper
0.261
233997TMININ_4.2
Solar/Wind Helper
0.261
232406W1-004 FULL
Solar/Wind Helper
0.507
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.232
233971AC1-093 C
Solar/Wind Helper
0.357
316044AC1-158 PL1
Solar/Wind Helper
1.293
316450AC1-158 RIC
Solar/Wind Helper
0.345
230430AE1-229_GEN
Solar/Wind Helper
3.372
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.11
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.114
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.353
219276PARKLANDSO C
Solar/Wind Helper
0.089
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219908AB1-139 C
Solar/Wind Helper
0.074
219249CENTRALDIV C
Solar/Wind Helper
0.01
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
971997AH1-543 GEN
Solar/Wind Harmer
2.724
24318805MLG1
50/50
10.095
23559001PLEAS1
50/50
6.1
270051AF1-062 GEN
50/50
11.821
270475AD2-096_GEN
50/50
7.141
970153AG2-106 GEN
Solar/Wind Harmer
22.046
961921AG1-034 GEN
Solar/Wind Harmer
7.615
241955AC1-078 GEN
Solar/Wind Harmer
0.007
24721905FLATG4
Adder
23.918
241974AD2-163_GEN2
Solar/Wind Harmer
0.006
942051AE2-217 GEN
Solar/Wind Harmer
14.671
970605AG2-385 GEN
Solar/Wind Harmer
4.899
270391AF1-285 GEN3
Solar/Wind Harmer
0.536
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.012
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270273AD2-016 GEN
Solar/Wind Harmer
0.821
972173AH1-669 GEN
Solar/Wind Harmer
3.952
270291AC1-194 GEN
Solar/Wind Harmer
6.106
253415AE1-040 GEN
Solar/Wind Harmer
0.003
270512AE1-227 GEN2
Solar/Wind Harmer
1.963
970065AG2-057 GEN
Solar/Wind Harmer
0.76
253370AE2-315 SEC1
Adder
2.182
253371AE2-315 SEC2
Adder
2.063
253406AD2-031_GEN
Solar/Wind Harmer
0.563
970191AG2-125 GEN
Solar/Wind Harmer
1.945
270491AE1-102 GEN2
Solar/Wind Harmer
0.979
270377AD1-106 GEN
Solar/Wind Harmer
2.855
971191AH1-055 GEN
Solar/Wind Harmer
19.26
253316AC1-085 GEN3
Solar/Wind Harmer
0.005
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.749
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.048
959331AF2-224 GEN
Solar/Wind Harmer
5.242
965021AG1-366 GEN
Solar/Wind Harmer
2.496
270588AE1-091_GEN
Solar/Wind Harmer
5.845
944531AF1-118 GEN
Solar/Wind Harmer
33.395
270043AE2-236 GEN
Solar/Wind Harmer
4.777
270258AD1-119 GEN
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
6.173
25196608WSDLE5
Adder
9.077
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
252510AF1-249 C
Solar/Wind Harmer
0.057
957741AF2-068 GEN
Solar/Wind Harmer
11.081
25194608D.CRK4
Adder
1.74
270222AC2-111 GEN
Solar/Wind Harmer
3.739
970031AG2-029 GEN
Solar/Wind Harmer
4.795
270404AC1-167 GEN
Solar/Wind Harmer
0.003
970513AG2-328 GEN
Solar/Wind Harmer
3.191
970517AG2-330 GEN
Solar/Wind Harmer
19.146
970349AG2-230 GEN
Solar/Wind Harmer
11.025
946031AF1-268 GEN
Solar/Wind Harmer
6.992
958821AF2-173 GEN
Solar/Wind Harmer
10.273
270004AE1-209 GEN
Solar/Wind Harmer
1.59
270437AC2-090 C
Solar/Wind Harmer
0.003
247643Z2-116 C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.804
970291AG2-192 GEN
Solar/Wind Harmer
0.731
247642Z2-115 C
Solar/Wind Harmer
0.003
945111AF1-176 GEN
Solar/Wind Harmer
5.919
24642205MAYFLWER
Adder
0.665
25196008MFTGT1
Adder
1.405
270356AE2-297 GEN
Solar/Wind Harmer
0.01
24441205WTRV SLR C
Solar/Wind Harmer
0
247604X1-042
Adder
0.433
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970217AG2-149 GEN
Solar/Wind Harmer
6.268
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
7.196
970243AG2-164 GEN
Solar/Wind Harmer
4.205
970519AG2-331 GEN
Solar/Wind Harmer
18.687
970699AG2-449 GEN
Solar/Wind Harmer
1.797
274752CRETE EC ;2U
Adder
8.477
274753CRETE EC ;3U
Adder
8.477
958171AF2-111 GEN
Solar/Wind Harmer
17.94
274772LINCOLN ;3U
Adder
8.676
274724RIVER EC ;11
Adder
18.203
972167AH1-666 GEN
Solar/Wind Harmer
5.717
24728705AND G3
Adder
8.214
274802UNIV PARK;5U
Adder
5.97
24728505AND G1
Adder
3.927
276806AD2-047 C O1
Solar/Wind Harmer
4.047
970941AG2-585 GEN
Solar/Wind Harmer
8.927
274826FISK ;BP
Adder
11.205
274800UNIV PARK;3U
Adder
5.966
972038AH1-567 GEN2
Adder
0.373
972228AH1-698 GEN2
Adder
3.79
276897AD1-100 C
Solar/Wind Harmer
0.009
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
970707AG2-453 GEN
Solar/Wind Harmer
23.303
274676JOLIET 29;8U
Adder
30.185
276893AG1-478 C
Solar/Wind Harmer
0.282
274729ELWOOD EC;1P
Adder
16.768
274730ELWOOD EC;6P
Adder
16.768
274734ELWOOD EC;8P
Adder
16.768
274736ELWOOD EC;9P
Adder
16.768
943121AE2-341 GEN
Solar/Wind Harmer
11.888
943591AF1-030 GEN
Solar/Wind Harmer
7.906
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
270541AE2-072 C
Solar/Wind Harmer
0.009
274682WAUKEGAN ;7U
Adder
9.728
276805AD2-038 GEN
Solar/Wind Harmer
0.002
964991AG1-363 GEN
Solar/Wind Helper
5.136
316097T157 G90
Solar/Wind Helper
1.504
23750701CROSSCHOOL
Solar/Wind Helper
1.502
238118U2-030_1
Solar/Wind Helper
0.341
238127S14_GEN_2
Solar/Wind Helper
0.827
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237080AD1-060 GEN
Solar/Wind Helper
0.342
237038AE2-054 C
Solar/Wind Helper
0.272
235062AE1-101 C1
Solar/Wind Helper
1.659
23779801AA1-109
Solar/Wind Helper
0.193
237048AF1-022 C
Solar/Wind Helper
0.177
223401AF1-299 GEN
Solar/Wind Helper
0.367
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.137
233930AB2-032 GEN
Solar/Wind Helper
0.381
233915AB1-141 GEN
Solar/Wind Helper
0.502
232422X3-066 FULL
Solar/Wind Helper
0.114
232428Y3-058 C
Solar/Wind Helper
0.338
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.261
232404W1-003 C
Solar/Wind Helper
0.507
232434Z2-077 GEN
Solar/Wind Helper
0.127
233954AC2-188 GEN
Solar/Wind Helper
0.232
233950AC2-186 GEN
Solar/Wind Helper
0.116
233972AC1-094 C
Solar/Wind Helper
0.302
316045AC1-158 PL2
Solar/Wind Helper
4.138
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.06
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
20720728JCB_W1-129
Solar/Wind Helper
0.057
316254AC1-120 GEN1
Solar/Wind Helper
1.059
207445AB1-138_GEN
Solar/Wind Helper
0.104
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.13
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.495
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.571
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.029
962771AG1-126 GEN
Solar/Wind Harmer
34.524
972239AH1-704 GEN
Adder
2.689
270054AF2-122 C O1
Solar/Wind Harmer
0.007
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
5.077
270520AE2-214 GEN
Solar/Wind Harmer
0.013
270284AF1-227 GEN1
Solar/Wind Harmer
0.011
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
253383AE2-342_GEN
Solar/Wind Harmer
0.003
241973AD2-163_GEN1
Solar/Wind Harmer
0.006
945631AF1-228 GEN
Solar/Wind Harmer
0
943861AF1-054 GEN
Solar/Wind Harmer
3.127
943851AF1-053 GEN
Solar/Wind Harmer
2.166
270156DARBY CT1
Adder
10.409
270157DARBY CT2
Adder
10.383
270158DARBY CT3
Adder
10.218
970689AG2-444 GEN
Solar/Wind Harmer
16.436
270578AF1-285 GEN2
Solar/Wind Harmer
0.536
270432AC2-029 GEN
Solar/Wind Harmer
3.553
940611AE2-048 GEN
Solar/Wind Harmer
19.602
941391AE2-136 GEN
Solar/Wind Harmer
11.042
270302AB2-170 GEN
Solar/Wind Harmer
0.005
270317AD1-130_GEN
Solar/Wind Harmer
0.011
971653AH1-327 GEN
Solar/Wind Harmer
1.117
270269AC2-059
Solar/Wind Harmer
0.005
241972AD1-140 GEN
Solar/Wind Harmer
0.854
970179AG2-119 GEN
Solar/Wind Harmer
6.883
270340AC2-060 GEN
Solar/Wind Harmer
0.009
970879AG2-548 GEN
Solar/Wind Harmer
6.898
253372AE2-315 SEC3
Adder
2.063
253372AE2-315 SEC3
Adder
2.063
25306009OHH W.
Adder
3.13
253349AC2-067 GEN
Solar/Wind Harmer
2.381
253400AC2-068 GEN
Solar/Wind Harmer
0.958
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.953
965051AG1-369 GEN
Solar/Wind Harmer
3.739
965041AG1-368 GEN
Solar/Wind Harmer
7.471
247607V1-011 GEN
Solar/Wind Harmer
0.001
971567AH1-282 GEN
Solar/Wind Harmer
11.206
971989AH1-539 GEN
Solar/Wind Harmer
3.215
963791AG1-232 GEN
Solar/Wind Harmer
10.044
24729505KEY G4
Adder
6.919
270071AF1-092 GEN
Solar/Wind Harmer
14.245
971985AH1-537 GEN
Solar/Wind Harmer
2.206
270024AE2-089 GEN
Solar/Wind Harmer
0.008
270367AC2-061_GEN
Solar/Wind Harmer
0.006
965101AG1-375 GEN
Solar/Wind Harmer
7.401
971673AH1-337 GEN
Solar/Wind Harmer
4.804
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
9.344
25196308WSDLE2
Adder
9.263
25196208WSDLE1
Adder
9.24
25196708WSDLE6
Adder
9.217
25196508WSDLE4
Adder
8.984
971029AG2-637 GEN
Solar/Wind Harmer
11.085
270543AE2-219 C
Solar/Wind Harmer
0.004
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270297AD1-101 GEN
Solar/Wind Harmer
0.002
971347AH1-153 GEN
Solar/Wind Harmer
11.025
971609AH1-304 GEN
Solar/Wind Harmer
1.2
270240V3-007_GEN2
Solar/Wind Harmer
0.002
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
970115AG2-085 GEN
Solar/Wind Harmer
2.932
270594AE1-207 GEN
Solar/Wind Harmer
8.194
970289AG2-191 GEN
Solar/Wind Harmer
1.389
971771AH1-392 GEN
Solar/Wind Harmer
7.306
971619AH1-309 GEN
Solar/Wind Harmer
3.285
971769AH1-391 GEN
Solar/Wind Harmer
8.134
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
25196108MFTGT2
Adder
1.599
25196108MFTGT2
Adder
1.484
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
4.302
971549AH1-272 GEN
Solar/Wind Harmer
14.865
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.676
274776LINCOLN ;7U
Adder
8.676
274777LINCOLN ;8U
Adder
8.676
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
5.184
274807UNIV PK N;3U
Adder
5.173
274805UNIV PK N;1U
Adder
5.15
274811UNIV PK N;7U
Adder
5.139
972037AH1-567 GEN1
Adder
0.187
960591AF2-350 GEN
Solar/Wind Harmer
7.141
274827FISK ;RP
Adder
7.941
972227AH1-698 GEN1
Adder
2.669
963841AG1-237 GEN
Solar/Wind Harmer
3.09
972163AH1-664 GEN
Solar/Wind Harmer
7.933
972165AH1-665 GEN
Solar/Wind Harmer
6.354
274687WILL CNTY;4U
Adder
28.523
274687WILL CNTY;4U
Adder
28.523
274675JOLIET 29;7U
Adder
31.303
274675JOLIET 29;7U
Adder
30.185
274731ELWOOD EC;2P
Adder
16.768
274733ELWOOD EC;3P
Adder
16.768
274735ELWOOD EC;4P
Adder
16.768
274728ELWOOD EC;5P
Adder
16.768
970833AG2-524 GEN
Solar/Wind Harmer
7.824
970833AG2-524 GEN
Solar/Wind Harmer
5.216
274746AC1-111 G10
Adder
5.679
274744AC1-111 GEN8
Adder
5.679
972203AH1-686 GEN
Adder
2.338
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
276868AE1-113 GEN
Solar/Wind Harmer
1.414
276882AE2-255 GEN
Solar/Wind Harmer
0.824
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.827
238152AF2-075_GEN
Solar/Wind Helper
0.707
238208AF1-136 C
Solar/Wind Helper
0.22
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.649
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.888
316415AF1-147_GEN2
Solar/Wind Helper
0.888
23750501ELLIOTTS
Solar/Wind Helper
0.638
959381AF2-229 GEN
Solar/Wind Helper
0.357
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.364
205943AE1-185 GEN
Solar/Wind Helper
0.509
205932AD2-116_GEN
Solar/Wind Helper
0.509
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.269
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.958
233990AG1-397 GEN
Solar/Wind Helper
0.27
232432Z2-076 GEN
Solar/Wind Helper
0.067
234033AF1-007_GEN
Solar/Wind Helper
7.02
964001AG1-254 GEN
Solar/Wind Helper
0.955
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.498
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.096
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.16
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.136
20675128HRM_W1-127
Solar/Wind Helper
0.029
209116AE2-175 GEN
Solar/Wind Helper
1.778
270119AB2-067 GEN1
50/50
7.059
270120AB2-067 GEN2
50/50
7.059
24318905MLG2
50/50
7.071
270471AD2-092_GEN
Solar/Wind Harmer
0.006
942861AE2-305 GEN
Solar/Wind Harmer
6.335
970077AG2-063 GEN
Solar/Wind Harmer
4.631
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
12.917
971655AH1-328 GEN
Solar/Wind Harmer
2.854
964601AG1-323 GEN
Solar/Wind Harmer
3.215
964601AG1-323 GEN
Solar/Wind Harmer
2.143
270518AE2-148 GEN
Solar/Wind Harmer
0.691
972269AH1-719 GEN
Adder
2.584
972159AH1-661 GEN
Adder
1.118
253378AE2-206_GEN
Solar/Wind Harmer
0.004
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
3.354
971199AH1-059 GEN
Solar/Wind Harmer
3.09
241960AC2-195 GEN
Solar/Wind Harmer
0.006
25326509SID D
Adder
1.451
971073AG2-665 GEN
Solar/Wind Harmer
6.898
25326109MON D
Adder
1.443
25322209TAIT E
Adder
10.642
25322209TAIT E
Adder
10.403
971201AH1-060 GEN
Solar/Wind Harmer
1.52
253370AE2-315 SEC1
Adder
2.182
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
246938BC-WTG3
Solar/Wind Harmer
0.273
246937BC-WTG2
Solar/Wind Harmer
0.305
971231AH1-075 GEN
Solar/Wind Harmer
0.861
253317AC1-085 GEN4
Solar/Wind Harmer
0.005
970611AG2-400 GEN
Solar/Wind Harmer
7.488
970627AG2-408 GEN
Solar/Wind Harmer
2.246
270007AE1-245 C
Solar/Wind Harmer
0.002
962581AG1-107 GEN
Solar/Wind Harmer
0.002
25183208HLCRTG
Solar/Wind Harmer
0.012
944541AF1-119 GEN
Solar/Wind Harmer
0.497
960971AF2-388 GEN
Solar/Wind Harmer
4.347
970623AG2-406 GEN
Solar/Wind Harmer
1.356
942221AE2-234 GEN
Solar/Wind Harmer
0.037
252519AF1-045_GEN
Solar/Wind Harmer
6.44
252516AE2-318_GEN
Solar/Wind Harmer
5.712
247621Y3-024
Adder
0.255
970883AG2-550 GEN
Solar/Wind Harmer
7.389
970885AG2-551 GEN
Solar/Wind Harmer
2.463
270201AC2-176 GEN
Solar/Wind Harmer
0.001
25194408D.CRK1
Adder
8.004
25194508D.CRK3
Adder
1.496
970621AG2-405 GEN
Solar/Wind Harmer
1.351
964611AG1-324 GEN
Solar/Wind Harmer
0.553
252509AD1-136 GEN
Solar/Wind Harmer
0.037
970321AG2-212 GEN
Solar/Wind Harmer
3.191
270599AE1-208 GEN
Solar/Wind Harmer
6.737
270031AE2-169
Solar/Wind Harmer
4.042
270186AC1-089 GEN
Solar/Wind Harmer
0.004
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
8.127
247620Y3-023
Adder
0.484
960441AF2-335 GEN
Solar/Wind Harmer
7.33
270216AD2-079_GEN
Solar/Wind Harmer
0.001
971613AH1-306 GEN
Solar/Wind Harmer
3.512
24728805RICHG1
Adder
3.964
24728905RICHG2
Adder
3.964
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
14.589
961051AF2-396 GEN
Solar/Wind Harmer
9.726
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
9.095
965791AG1-447 GEN
Solar/Wind Harmer
6.67
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.797
274770LINCOLN ;1U
Adder
8.676
274771LINCOLN ;2U
Adder
8.676
966841AG1-555 GEN
Solar/Wind Harmer
0.81
274808UNIV PK N;4U
Adder
5.117
274803UNIV PARK;6U
Adder
5.97
274888KELLY CRK;1U
Solar/Wind Harmer
0.419
274887GEN-1.85
Solar/Wind Harmer
0.188
276843GEN-1.7
Solar/Wind Harmer
0.231
958011AF2-095 GEN
Solar/Wind Harmer
10.284
972259AH1-714 GEN
Adder
19.507
274674JOLIET 9 ;6U
Adder
15.704
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
970241AG2-163 GEN
Solar/Wind Harmer
4.144
958481AF2-142 GEN
Solar/Wind Harmer
10.621
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.958
971573AH1-285 GEN
Solar/Wind Harmer
1.319
274696ROCKY RD ;4P
Adder
11.537
274695ROCKY RD ;2P
Adder
11.271
274693ROCKY RD ;1P
Adder
11.16
274697ROCKY RD ;3P
Adder
3.062
958491AF2-143 GEN
Solar/Wind Harmer
10.588
274879MINONK ;1U
Solar/Wind Harmer
0.297
23585401KL_K28_T16
Solar/Wind Helper
1.482
238120AE2-309 GEN
Solar/Wind Helper
0.525
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.701
238170AE2-226 GEN2
Solar/Wind Helper
0.701
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237002AB1-128_GEN
Solar/Wind Helper
0.443
237034AC2-136 C
Solar/Wind Helper
0.227
235063AE1-101 C2
Solar/Wind Helper
1.659
237001AB1-127_GEN
Solar/Wind Helper
0.442
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.713
20390526W1-045 C
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.342
233933AB2-153 GEN
Solar/Wind Helper
0.232
233944AB2-135 GEN
Solar/Wind Helper
0.588
232424Y1-079 C
Solar/Wind Helper
0.116
234036AF2-325 C
Solar/Wind Helper
0.042
233946AB2-136 GEN
Solar/Wind Helper
0.568
233901CHERRYDALE C
Solar/Wind Helper
0.232
232408W1-005 C
Solar/Wind Helper
0.507
232410W1-006 C
Solar/Wind Helper
0.507
233939AC1-091 C
Solar/Wind Helper
0.35
233970AC1-092 C
Solar/Wind Helper
0.35
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.845
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.051
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.09
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.168
20674928WA_W3-044
Solar/Wind Helper
0.098
20676228FRD_X1-012
Solar/Wind Helper
0.092
964851AG1-348 GEN
Solar/Wind Helper
0.081
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.074
211065PSPA IPP
Solar/Wind Helper
0.151
211065PSPA IPP
Solar/Wind Helper
0.151
NYPJM->LTFIMP_NY
CLTF
4.797
LGEELTFEXP_LGEE->PJM
CLTF
6.749
WECLTFEXP_WEC->PJM
CLTF
3.825
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
AH1-155LTFEXP_AH1-155->PJM
LTF
0.359
CPLELTFEXP_CPLE->PJM
CLTF
0.624
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.816
LAGNLTFEXP_LAGN->PJM
CLTF
14.837
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.802
TVALTFEXP_TVA->PJM
CLTF
7.293
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.078
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.1
MECLTFEXP_MEC->PJM
CLTF
15.901
SIGELTFEXP_SIGE->PJM
CLTF
0.505

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-012_SRT-A


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-012_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.49 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4985.98
MW Contribution:17.86
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
7.033
270120AB2-067 GEN2
50/50
7.033
24318905MLG2
50/50
7.475
270471AD2-092_GEN
Solar/Wind Harmer
4.529
946101AF1-275 GEN
Solar/Wind Harmer
1.842
938701AE1-092 GEN
Solar/Wind Harmer
24.483
270224U2-072_GEN2
Solar/Wind Harmer
2.339
270227U2-072_GEN3
Solar/Wind Harmer
2.339
270228U2-072_GEN4
Solar/Wind Harmer
2.339
270231U2-072_GEN5
Solar/Wind Harmer
2.339
942861AE2-305 GEN
Solar/Wind Harmer
9.223
964601AG1-323 GEN
Solar/Wind Harmer
3.753
964601AG1-323 GEN
Solar/Wind Harmer
1.746
972269AH1-719 GEN
Adder
2.7
970077AG2-063 GEN
Solar/Wind Harmer
6.332
972159AH1-661 GEN
Adder
1.166
270518AE2-148 GEN
Solar/Wind Harmer
14.068
971199AH1-059 GEN
Solar/Wind Harmer
4.644
241960AC2-195 GEN
Solar/Wind Harmer
3.219
971201AH1-060 GEN
Solar/Wind Harmer
2.296
253378AE2-206_GEN
Solar/Wind Harmer
4.086
276820AF1-078_GEN
Solar/Wind Harmer
1.815
971231AH1-075 GEN
Solar/Wind Harmer
0.905
25326509SID D
Adder
1.48
25326109MON D
Adder
1.461
246938BC-WTG3
Solar/Wind Harmer
4.418
246937BC-WTG2
Solar/Wind Harmer
4.343
970879AG2-548 GEN
Solar/Wind Harmer
6.827
971073AG2-665 GEN
Solar/Wind Harmer
6.827
971073AG2-665 GEN
Solar/Wind Harmer
4.763
25322209TAIT E
Adder
10.77
25322209TAIT E
Adder
10.528
270007AE1-245 C
Solar/Wind Harmer
6.539
942801AE2-298 GEN
Solar/Wind Harmer
1.667
253370AE2-315 SEC1
Adder
2.206
970611AG2-400 GEN
Solar/Wind Harmer
10.972
253394AE2-221_GEN
Solar/Wind Harmer
4.954
253398AE2-221_GEN2
Solar/Wind Harmer
4.954
253317AC1-085 GEN4
Solar/Wind Harmer
9.07
971677AH1-339 GEN
Solar/Wind Harmer
8.643
942221AE2-234 GEN
Solar/Wind Harmer
0.79
944541AF1-119 GEN
Solar/Wind Harmer
4.511
960971AF2-388 GEN
Solar/Wind Harmer
11.771
247621Y3-024
Adder
0.259
270166AC1-044 GEN3
50/50
7.033
23559101PLEAS2
50/50
5.443
270122AB2-093 CT
50/50
4.116
962761AG1-125 GEN
Solar/Wind Harmer
40.965
970149AG2-104 GEN
Solar/Wind Harmer
50.592
970155AG2-107 GEN
Solar/Wind Harmer
17.863
270349AD2-093_GEN
Solar/Wind Harmer
4.529
270223U2-072_GEN1
Solar/Wind Harmer
2.339
270578AF1-285 GEN2
Solar/Wind Harmer
1.43
270391AF1-285 GEN3
Solar/Wind Harmer
1.43
270159DARBY CT4
Adder
10.388
971995AH1-542 GEN
Solar/Wind Harmer
12.974
970593AG2-378 GEN
Solar/Wind Harmer
2.345
270462AD2-086
Solar/Wind Harmer
8.157
270510AE1-227 GEN1
Solar/Wind Harmer
2.893
24721705FLATG2
Adder
23.506
253343AC1-166 GEN
Solar/Wind Harmer
1.256
253325AC1-069 GEN
Solar/Wind Harmer
1.211
241813AF1-122_GEN
Solar/Wind Harmer
7.346
270263AC1-001 GEN
Solar/Wind Harmer
1.187
241847AF2-150_GEN
Solar/Wind Harmer
4.622
246936BC-WTG1
Solar/Wind Harmer
4.343
270489AE1-102 GEN1
Solar/Wind Harmer
1.443
965421AG1-410 GEN
Solar/Wind Harmer
33.256
970515AG2-329 GEN
Solar/Wind Harmer
16.033
25326309TAIT D
Adder
1.21
960071AF2-298 GEN
Solar/Wind Harmer
5.501
253370AE2-315 SEC1
Adder
2.206
253371AE2-315 SEC2
Adder
2.086
247521TR3_G114
Solar/Wind Harmer
3.699
270246TR4_N_V150
Solar/Wind Harmer
0.936
247522W1-056 GEN
Solar/Wind Harmer
2.477
24695305TIMB G C
Solar/Wind Harmer
6.051
965011AG1-365 GEN
Solar/Wind Harmer
10.972
927014AC1-188 GEN
Solar/Wind Harmer
1.729
944231AF1-091 GEN
Solar/Wind Harmer
4.078
253432AC1-085 GEN2
Solar/Wind Harmer
0.29
946171AF1-282 GEN
Solar/Wind Harmer
10.828
270063AE2-323 C
Solar/Wind Harmer
2.376
965651AG1-433 GEN
Solar/Wind Harmer
5.885
958861AF2-177 GEN
Solar/Wind Harmer
11.752
247536S-71 GEN
Solar/Wind Harmer
4.346
960001AF2-291 GEN
Solar/Wind Harmer
3.244
945371AF1-202 GEN
Solar/Wind Harmer
7.479
24639705ELKHART HY
Adder
0.164
25194608D.CRK4
Adder
1.752
25196808ZIMRHP
Adder
80.188
23906502RICHG2&3
Adder
1.272
972301AH1-735 GEN
Adder
6.357
23906402RICHG1
Adder
1.271
25196008MFTGT1
Adder
1.459
274751CRETE EC ;1U
Adder
8.598
274754CRETE EC ;4U
Adder
8.598
274723RIVER EC ;12
Adder
18.677
274773LINCOLN ;4U
Adder
8.792
274774LINCOLN ;5U
Adder
8.792
274812UNIV PK N;8U
Adder
5.21
23920202STRYCT
Adder
1.444
274801UNIV PARK;4U
Adder
6.045
274676JOLIET 29;8U
Adder
31.706
274732ELWOOD EC;7P
Adder
2.004
23583801GRNGAP
Solar/Wind Helper
6.365
316095T157 G97
Solar/Wind Helper
1.705
238108AE1-109 GEN1
Solar/Wind Helper
0.121
238185AF2-356 C
Solar/Wind Helper
2.767
238147AE2-230_GEN1
Solar/Wind Helper
0.552
238149AF1-291A_GEN
Solar/Wind Helper
0.158
237061AD1-155 GEN
Solar/Wind Helper
0.06
235054AD2-180 GEN
Solar/Wind Helper
2.111
235531U2-073 GEN
Solar/Wind Helper
3.439
238117U2-030
Solar/Wind Helper
0.356
238221AF1-254 C O1
Solar/Wind Helper
0.295
235067AD1-061 GEN
Solar/Wind Helper
0.532
3141196NOKESVL
Solar/Wind Helper
1.141
23751201ROTHROCK
Solar/Wind Helper
0.819
237030AB1-096 C
Solar/Wind Helper
0.075
23562501BACKB
Solar/Wind Helper
0.997
226910AB2-157 C
Solar/Wind Helper
0.015
227287AC2-120 GEN
Solar/Wind Helper
0.375
223402AF1-300 C
Solar/Wind Helper
0.387
316044AC1-158 PL1
Solar/Wind Helper
1.443
316450AC1-158 RIC
Solar/Wind Helper
0.385
316170AC1-121 GEN2
Solar/Wind Helper
0.395
23751101LEADS_P59
Solar/Wind Helper
1.316
205917AD1-020 ES
Solar/Wind Helper
0.379
3132273ORANGE
Solar/Wind Helper
0.049
233918AB1-142 GEN
Solar/Wind Helper
0.511
233982AB2-133 GEN
Solar/Wind Helper
0.364
233994AC2-023 GEN
Solar/Wind Helper
0.977
233996TM1833_GEN
Solar/Wind Helper
0.266
233997TMININ_4.2
Solar/Wind Helper
0.266
232406W1-004 FULL
Solar/Wind Helper
0.516
3147666LOUISA
Solar/Wind Helper
0.551
233940AF2-379 C
Solar/Wind Helper
0.063
234015AF2-250 C
Solar/Wind Helper
0.039
233952AC2-187 GEN
Solar/Wind Helper
0.236
233971AC1-093 C
Solar/Wind Helper
0.363
230430AE1-229_GEN
Solar/Wind Helper
3.409
230415AB2-049 C
Solar/Wind Helper
0.031
228729W2-030 C
Solar/Wind Helper
0.112
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.151
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.064
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
219276PARKLANDSO C
Solar/Wind Helper
0.09
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
966881AG1-559 GEN
Solar/Wind Helper
0.312
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
972239AH1-704 GEN
50/50
3.102
962771AG1-126 GEN
Solar/Wind Harmer
40.965
270459AD2-067 GEN
Solar/Wind Harmer
10.453
961821AG1-024 GEN
Solar/Wind Harmer
10.613
270054AF2-122 C O1
Solar/Wind Harmer
4.071
270284AF1-227 GEN1
Solar/Wind Harmer
6.912
270286AF1-227 GEN2
Solar/Wind Harmer
2.557
270287AF1-227 GEN3
Solar/Wind Harmer
2.557
270520AE2-214 GEN
Solar/Wind Harmer
7.382
253383AE2-342_GEN
Solar/Wind Harmer
1.062
241973AD2-163_GEN1
Solar/Wind Harmer
2.37
940611AE2-048 GEN
Solar/Wind Harmer
26.074
941391AE2-136 GEN
Solar/Wind Harmer
13.511
270578AF1-285 GEN2
Solar/Wind Harmer
0.55
943861AF1-054 GEN
Solar/Wind Harmer
4.552
943851AF1-053 GEN
Solar/Wind Harmer
2.2
945631AF1-228 GEN
Solar/Wind Harmer
5.537
270156DARBY CT1
Adder
10.556
270157DARBY CT2
Adder
10.53
270158DARBY CT3
Adder
10.362
270302AB2-170 GEN
Solar/Wind Harmer
9.805
270317AD1-130_GEN
Solar/Wind Harmer
3.759
970689AG2-444 GEN
Solar/Wind Harmer
19.055
270432AC2-029 GEN
Solar/Wind Harmer
8.138
958581AF2-149 GEN
Solar/Wind Harmer
4.968
970179AG2-119 GEN
Solar/Wind Harmer
9.26
270269AC2-059
Solar/Wind Harmer
10.704
241972AD1-140 GEN
Solar/Wind Harmer
5.084
971567AH1-282 GEN
Solar/Wind Harmer
16.984
966831AG1-554 GEN
Solar/Wind Harmer
1.34
971989AH1-539 GEN
Solar/Wind Harmer
14.49
270340AC2-060 GEN
Solar/Wind Harmer
3.371
957201AF2-014 GEN
Solar/Wind Harmer
5.033
270435AC2-044 GEN
Solar/Wind Harmer
2.219
970879AG2-548 GEN
Solar/Wind Harmer
4.763
247607V1-011 GEN
Solar/Wind Harmer
4.359
253372AE2-315 SEC3
Adder
2.086
253372AE2-315 SEC3
Adder
2.086
965051AG1-369 GEN
Solar/Wind Harmer
5.494
25306009OHH W.
Adder
3.166
270297AD1-101 GEN
Solar/Wind Harmer
3.056
965041AG1-368 GEN
Solar/Wind Harmer
10.974
253349AC2-067 GEN
Solar/Wind Harmer
5.466
253400AC2-068 GEN
Solar/Wind Harmer
2.198
963791AG1-232 GEN
Solar/Wind Harmer
14.679
270071AF1-092 GEN
Solar/Wind Harmer
16.242
24729505KEY G4
Adder
7.02
945641AF1-229 GEN
Solar/Wind Harmer
3.923
270024AE2-089 GEN
Solar/Wind Harmer
5.065
958711AF2-162 GEN
Solar/Wind Harmer
1.089
965101AG1-375 GEN
Solar/Wind Harmer
10.752
961761AG1-017 GEN
Solar/Wind Harmer
0.46
270543AE2-219 C
Solar/Wind Harmer
5.494
971029AG2-637 GEN
Solar/Wind Harmer
16.089
971673AH1-337 GEN
Solar/Wind Harmer
4.934
25196408WSDLE3
Adder
9.412
25196308WSDLE2
Adder
9.33
25196208WSDLE1
Adder
9.306
25196708WSDLE6
Adder
9.283
25196508WSDLE4
Adder
9.049
25196108MFTGT2
Adder
1.608
25196108MFTGT2
Adder
1.494
274775LINCOLN ;6U
Adder
8.792
274776LINCOLN ;7U
Adder
8.792
274777LINCOLN ;8U
Adder
8.792
274814UNIV PK N;0U
Adder
5.256
274807UNIV PK N;3U
Adder
5.245
274805UNIV PK N;1U
Adder
5.222
274811UNIV PK N;7U
Adder
5.21
972037AH1-567 GEN1
Adder
0.19
274827FISK ;RP
Adder
8.047
972227AH1-698 GEN1
Adder
2.704
274687WILL CNTY;4U
Adder
28.893
274687WILL CNTY;4U
Adder
28.893
274675JOLIET 29;7U
Adder
31.706
274675JOLIET 29;7U
Adder
30.574
274731ELWOOD EC;2P
Adder
16.983
274733ELWOOD EC;3P
Adder
16.983
274735ELWOOD EC;4P
Adder
16.983
274728ELWOOD EC;5P
Adder
16.983
238109AE1-109 GEN2
Solar/Wind Helper
0.121
238110AE1-109 GEN3
Solar/Wind Helper
0.121
238152AF2-075_GEN
Solar/Wind Helper
0.789
23546401DTGZ2-030
Solar/Wind Helper
0.099
238126S14_GEN_1
Solar/Wind Helper
0.867
238208AF1-136 C
Solar/Wind Helper
0.236
237085AD2-009_GEN
Solar/Wind Helper
1.767
3138216PACIFIC
Solar/Wind Helper
0.049
316411AF1-147_GEN1
Solar/Wind Helper
0.978
316415AF1-147_GEN2
Solar/Wind Helper
0.978
3141426STAFORD
Solar/Wind Helper
0.058
316164AC1-076 GEN
Solar/Wind Helper
1.225
23750501ELLIOTTS
Solar/Wind Helper
0.629
959381AF2-229 GEN
Solar/Wind Helper
0.367
960921AF2-383 GEN
Solar/Wind Helper
0.185
205943AE1-185 GEN
Solar/Wind Helper
0.518
205932AD2-116_GEN
Solar/Wind Helper
0.518
205956AE1-196_GEN
Solar/Wind Helper
0.518
233935AB2-179 C
Solar/Wind Helper
1.29
232436AB1-176 C
Solar/Wind Helper
0.045
233923SMA
Solar/Wind Helper
0.974
233990AG1-397 GEN
Solar/Wind Helper
0.031
232432Z2-076 GEN
Solar/Wind Helper
0.068
234033AF1-007_GEN
Solar/Wind Helper
7.137
964001AG1-254 GEN
Solar/Wind Helper
0.966
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.116
203975AE1-071-GEN
Solar/Wind Helper
2.53
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.081
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.292
219620RIDERU C
Solar/Wind Helper
0.001
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
20674828DL_W4-046
Solar/Wind Helper
0.008
207484AF2-139 C O1
Solar/Wind Helper
0.084
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.136
20675128HRM_W1-127
Solar/Wind Helper
0.029
209116AE2-175 GEN
Solar/Wind Helper
1.768
945581AF1-223 GEN
Solar/Wind Harmer
0.763
24318805MLG1
50/50
10.022
23559001PLEAS1
50/50
5.443
270051AF1-062 GEN
50/50
11.999
970153AG2-106 GEN
Solar/Wind Harmer
17.863
961921AG1-034 GEN
Solar/Wind Harmer
15.919
241955AC1-078 GEN
Solar/Wind Harmer
8.948
241974AD2-163_GEN2
Solar/Wind Harmer
2.37
942051AE2-217 GEN
Solar/Wind Harmer
21.374
942871AE2-306 GEN
Solar/Wind Harmer
1.073
270391AF1-285 GEN3
Solar/Wind Harmer
0.55
960801AF2-371 GEN
Solar/Wind Harmer
2.991
964871AG1-351 GEN
Solar/Wind Harmer
2.065
970605AG2-385 GEN
Solar/Wind Harmer
6.332
270485AE1-090_GEN
Solar/Wind Harmer
0.709
270512AE1-227 GEN2
Solar/Wind Harmer
2.455
24721905FLATG4
Adder
23.506
253338AC1-165 GEN
Solar/Wind Harmer
1.256
253333AC1-068 GEN
Solar/Wind Harmer
1.211
970065AG2-057 GEN
Solar/Wind Harmer
1.148
270273AD2-016 GEN
Solar/Wind Harmer
3.061
972173AH1-669 GEN
Solar/Wind Harmer
5.721
270377AD1-106 GEN
Solar/Wind Harmer
6.988
270588AE1-091_GEN
Solar/Wind Harmer
12.311
270291AC1-194 GEN
Solar/Wind Harmer
11.854
253415AE1-040 GEN
Solar/Wind Harmer
1.258
961961AG1-039 GEN
Solar/Wind Harmer
3.188
270491AE1-102 GEN2
Solar/Wind Harmer
1.443
970217AG2-149 GEN
Solar/Wind Harmer
35.355
958091AF2-103 GEN
Solar/Wind Harmer
0.178
253303V4-073 C
Solar/Wind Harmer
0.128
253370AE2-315 SEC1
Adder
2.206
253371AE2-315 SEC2
Adder
2.086
270191TR4_S_V150
Solar/Wind Harmer
3.3
270247TR4_N_V136
Solar/Wind Harmer
0.936
959331AF2-224 GEN
Solar/Wind Harmer
10.972
965021AG1-366 GEN
Solar/Wind Harmer
2.552
270258AD1-119 GEN
Solar/Wind Harmer
3.051
253406AD2-031_GEN
Solar/Wind Harmer
1.398
270044AE2-322 C
Solar/Wind Harmer
1.435
270404AC1-167 GEN
Solar/Wind Harmer
1.194
957541AF2-048 GEN
Solar/Wind Harmer
1.725
270043AE2-236 GEN
Solar/Wind Harmer
5.98
944531AF1-118 GEN
Solar/Wind Harmer
37.943
253316AC1-085 GEN3
Solar/Wind Harmer
9.07
253433AC1-085 GEN1
Solar/Wind Harmer
5.758
946181AF1-283 GEN
Solar/Wind Harmer
14.077
970031AG2-029 GEN
Solar/Wind Harmer
32.394
971617AH1-308 GEN
Solar/Wind Harmer
6.274
270541AE2-072 C
Solar/Wind Harmer
4.881
971191AH1-055 GEN
Solar/Wind Harmer
23.635
962031AG1-047 GEN
Solar/Wind Harmer
3.246
957741AF2-068 GEN
Solar/Wind Harmer
16.111
25196608WSDLE5
Adder
9.143
24642205MAYFLWER
Adder
0.678
25194608D.CRK4
Adder
1.752
247604X1-042
Adder
0.444
23906502RICHG2&3
Adder
1.272
25196008MFTGT1
Adder
1.413
274752CRETE EC ;2U
Adder
8.598
274753CRETE EC ;3U
Adder
8.598
274724RIVER EC ;11
Adder
18.459
274772LINCOLN ;3U
Adder
8.792
274802UNIV PARK;5U
Adder
6.05
274826FISK ;BP
Adder
11.355
274800UNIV PARK;3U
Adder
6.045
972038AH1-567 GEN2
Adder
0.378
972228AH1-698 GEN2
Adder
3.84
274676JOLIET 29;8U
Adder
30.573
274729ELWOOD EC;1P
Adder
16.983
274730ELWOOD EC;6P
Adder
16.983
964991AG1-363 GEN
Solar/Wind Helper
5.557
316097T157 G90
Solar/Wind Helper
1.705
23750701CROSSCHOOL
Solar/Wind Helper
1.586
238148AE2-230_GEN2
Solar/Wind Helper
0.555
238127S14_GEN_2
Solar/Wind Helper
0.867
238118U2-030_1
Solar/Wind Helper
0.356
237080AD1-060 GEN
Solar/Wind Helper
0.367
237038AE2-054 C
Solar/Wind Helper
0.292
235062AE1-101 C1
Solar/Wind Helper
1.776
23779801AA1-109
Solar/Wind Helper
0.207
316006AB2-029 C
Solar/Wind Helper
0.13
223401AF1-299 GEN
Solar/Wind Helper
0.387
316045AC1-158 PL2
Solar/Wind Helper
4.618
316254AC1-120 GEN1
Solar/Wind Helper
1.184
237048AF1-022 C
Solar/Wind Helper
0.173
966131AG1-482 GEN
Solar/Wind Helper
0.079
233930AB2-032 GEN
Solar/Wind Helper
0.387
233915AB1-141 GEN
Solar/Wind Helper
0.511
232422X3-066 FULL
Solar/Wind Helper
0.116
233964AF2-378 GEN
Solar/Wind Helper
0.042
232426Y1-080 FULL
Solar/Wind Helper
0.039
233998TM1NIN_3.36
Solar/Wind Helper
0.266
232404W1-003 C
Solar/Wind Helper
0.516
232428Y3-058 C
Solar/Wind Helper
0.344
3147666LOUISA
Solar/Wind Helper
0.958
232434Z2-077 GEN
Solar/Wind Helper
0.129
233954AC2-188 GEN
Solar/Wind Helper
0.236
233950AC2-186 GEN
Solar/Wind Helper
0.118
233972AC1-094 C
Solar/Wind Helper
0.307
316192AB2-158 GEN
Solar/Wind Helper
1.608
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.232
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.061
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.132
20720728JCB_W1-129
Solar/Wind Helper
0.057
207445AB1-138_GEN
Solar/Wind Helper
0.105
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.078
207454AA2-184 E
Solar/Wind Helper
0.311
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.497
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.137
207518AF1-320_GEN
Solar/Wind Helper
1.568
20671928W4-073
Solar/Wind Helper
0.089
20675828AU_W4-064
Solar/Wind Helper
0.029
270201AC2-176 GEN
Solar/Wind Harmer
5.522
970883AG2-550 GEN
Solar/Wind Harmer
10.73
970885AG2-551 GEN
Solar/Wind Harmer
2.495
247620Y3-023
Adder
0.494
964611AG1-324 GEN
Solar/Wind Harmer
1.264
964611AG1-324 GEN
Solar/Wind Harmer
0.561
25194408D.CRK1
Adder
8.061
25194508D.CRK3
Adder
1.507
24728805RICHG1
Adder
4.003
24728905RICHG2
Adder
4.003
970935AG2-582 GEN
Adder
239.406
274770LINCOLN ;1U
Adder
8.792
274771LINCOLN ;2U
Adder
8.792
274808UNIV PK N;4U
Adder
5.188
274803UNIV PARK;6U
Adder
6.05
972259AH1-714 GEN
Adder
19.76
238175AF1-290_GEN
Solar/Wind Helper
0.168
238169AE2-226 GEN1
Solar/Wind Helper
0.772
238170AE2-226 GEN2
Solar/Wind Helper
0.772
238120AE2-309 GEN
Solar/Wind Helper
0.552
23585401KL_K28_T16
Solar/Wind Helper
1.529
235020AA1-095 C
Solar/Wind Helper
0.057
23777901MDS_W4-102
Solar/Wind Helper
0.191
237034AC2-136 C
Solar/Wind Helper
0.244
237002AB1-128_GEN
Solar/Wind Helper
0.475
235063AE1-101 C2
Solar/Wind Helper
1.776
237001AB1-127_GEN
Solar/Wind Helper
0.473
23777801MSM_W1-116
Solar/Wind Helper
0.122
237025AB1-124 C
Solar/Wind Helper
0.175
237006AB1-125 GEN
Solar/Wind Helper
0.131
226929AD2-058 GEN
Solar/Wind Helper
0.108
315651AD1-115 GEN
Solar/Wind Helper
0.876
316447AC1-158 HLD
Solar/Wind Helper
3.175
205916AD1-020 GEN
Solar/Wind Helper
1.761
20390526W1-045 C
Solar/Wind Helper
0.36
208835TUHI V3-051
Solar/Wind Helper
0.025
208835TUHI V3-051
Solar/Wind Helper
0.025
3132123MT JACKSON
Solar/Wind Helper
0.764
233987AB2-037 GEN
Solar/Wind Helper
2.381
233933AB2-153 GEN
Solar/Wind Helper
0.236
232424Y1-079 C
Solar/Wind Helper
0.118
233944AB2-135 GEN
Solar/Wind Helper
0.598
233946AB2-136 GEN
Solar/Wind Helper
0.577
234036AF2-325 C
Solar/Wind Helper
0.043
233901CHERRYDALE C
Solar/Wind Helper
0.236
232408W1-005 C
Solar/Wind Helper
0.516
232410W1-006 C
Solar/Wind Helper
0.516
233939AC1-091 C
Solar/Wind Helper
0.356
233970AC1-092 C
Solar/Wind Helper
0.356
966001AG1-469 GEN
Solar/Wind Helper
0.255
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.041
219921AF1-264
Solar/Wind Helper
0.052
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.083
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.168
20674928WA_W3-044
Solar/Wind Helper
0.098
20676228FRD_X1-012
Solar/Wind Helper
0.091
964851AG1-348 GEN
Solar/Wind Helper
0.081
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.044
211065PSPA IPP
Solar/Wind Helper
0.15
211065PSPA IPP
Solar/Wind Helper
0.15
NYPJM->LTFIMP_NY
CLTF
4.554
LGEELTFEXP_LGEE->PJM
CLTF
6.753
WECLTFEXP_WEC->PJM
CLTF
3.866
AG2-052LTFEXP_AG2-052->PJM
LTF
0.243
AH1-155LTFEXP_AH1-155->PJM
LTF
0.364
CBM West 2LTFEXP_CBM-W2->PJM
CBM
111.893
LAGNLTFEXP_LAGN->PJM
CLTF
14.521
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.32
TVALTFEXP_TVA->PJM
CLTF
7.111
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.579
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.544
MECLTFEXP_MEC->PJM
CLTF
15.979
SIGELTFEXP_SIGE->PJM
CLTF
0.506

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P1-2_MP-500-008A_SRT-SL


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:125.38 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4754.33
MW Contribution:21.25
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
6.869
270120AB2-067 GEN2
50/50
6.869
24318905MLG2
50/50
6.89
270471AD2-092_GEN
Solar/Wind Harmer
0.006
942861AE2-305 GEN
Solar/Wind Harmer
6.118
970077AG2-063 GEN
Solar/Wind Harmer
4.471
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
12.484
971655AH1-328 GEN
Solar/Wind Harmer
2.758
964601AG1-323 GEN
Solar/Wind Harmer
3.106
964601AG1-323 GEN
Solar/Wind Harmer
2.071
270518AE2-148 GEN
Solar/Wind Harmer
0.667
972269AH1-719 GEN
Adder
2.501
972159AH1-661 GEN
Adder
1.082
253378AE2-206_GEN
Solar/Wind Harmer
0.004
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
3.237
971199AH1-059 GEN
Solar/Wind Harmer
2.99
241960AC2-195 GEN
Solar/Wind Harmer
0.006
970935AG2-582 GEN
Adder
242.403
25326509SID D
Adder
1.4
971073AG2-665 GEN
Solar/Wind Harmer
6.645
25326109MON D
Adder
1.391
971201AH1-060 GEN
Solar/Wind Harmer
1.471
25322209TAIT E
Adder
10.262
25322209TAIT E
Adder
10.031
253370AE2-315 SEC1
Adder
2.103
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
246938BC-WTG3
Solar/Wind Harmer
0.263
246937BC-WTG2
Solar/Wind Harmer
0.295
972239AH1-704 GEN
50/50
2.78
962771AG1-126 GEN
Solar/Wind Harmer
33.269
270459AD2-067 GEN
Solar/Wind Harmer
0
270054AF2-122 C O1
Solar/Wind Harmer
0.007
961821AG1-024 GEN
Solar/Wind Harmer
4.91
270520AE2-214 GEN
Solar/Wind Harmer
0.013
270284AF1-227 GEN1
Solar/Wind Harmer
0.01
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
253383AE2-342_GEN
Solar/Wind Harmer
0.003
241973AD2-163_GEN1
Solar/Wind Harmer
0.006
945631AF1-228 GEN
Solar/Wind Harmer
0
943861AF1-054 GEN
Solar/Wind Harmer
3.02
943851AF1-053 GEN
Solar/Wind Harmer
2.092
270156DARBY CT1
Adder
10.05
270157DARBY CT2
Adder
10.026
270158DARBY CT3
Adder
9.866
270578AF1-285 GEN2
Solar/Wind Harmer
0.518
970689AG2-444 GEN
Solar/Wind Harmer
15.861
270432AC2-029 GEN
Solar/Wind Harmer
3.428
940611AE2-048 GEN
Solar/Wind Harmer
18.967
941391AE2-136 GEN
Solar/Wind Harmer
10.684
270302AB2-170 GEN
Solar/Wind Harmer
0.005
270317AD1-130_GEN
Solar/Wind Harmer
0.011
971653AH1-327 GEN
Solar/Wind Harmer
1.08
270269AC2-059
Solar/Wind Harmer
0.004
241972AD1-140 GEN
Solar/Wind Harmer
0.824
970179AG2-119 GEN
Solar/Wind Harmer
6.658
270340AC2-060 GEN
Solar/Wind Harmer
0.009
970879AG2-548 GEN
Solar/Wind Harmer
6.645
253372AE2-315 SEC3
Adder
1.989
253372AE2-315 SEC3
Adder
1.989
25306009OHH W.
Adder
3.018
253349AC2-067 GEN
Solar/Wind Harmer
2.296
253400AC2-068 GEN
Solar/Wind Harmer
0.923
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.92
965051AG1-369 GEN
Solar/Wind Harmer
3.609
971567AH1-282 GEN
Solar/Wind Harmer
10.843
247607V1-011 GEN
Solar/Wind Harmer
0.001
965041AG1-368 GEN
Solar/Wind Harmer
7.21
971989AH1-539 GEN
Solar/Wind Harmer
3.109
963791AG1-232 GEN
Solar/Wind Harmer
9.689
24729505KEY G4
Adder
6.671
270071AF1-092 GEN
Solar/Wind Harmer
13.737
270024AE2-089 GEN
Solar/Wind Harmer
0.008
971985AH1-537 GEN
Solar/Wind Harmer
2.123
965101AG1-375 GEN
Solar/Wind Harmer
7.135
270297AD1-101 GEN
Solar/Wind Harmer
0.002
270367AC2-061_GEN
Solar/Wind Harmer
0.006
971673AH1-337 GEN
Solar/Wind Harmer
4.631
971029AG2-637 GEN
Solar/Wind Harmer
10.686
270543AE2-219 C
Solar/Wind Harmer
0.004
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
9.002
25196308WSDLE2
Adder
8.924
25196208WSDLE1
Adder
8.902
25196708WSDLE6
Adder
8.879
25196508WSDLE4
Adder
8.656
945581AF1-223 GEN
Solar/Wind Harmer
0.001
971347AH1-153 GEN
Solar/Wind Harmer
10.632
971609AH1-304 GEN
Solar/Wind Harmer
1.157
270240V3-007_GEN2
Solar/Wind Harmer
0.002
970115AG2-085 GEN
Solar/Wind Harmer
2.826
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
7.898
971771AH1-392 GEN
Solar/Wind Harmer
7.046
970289AG2-191 GEN
Solar/Wind Harmer
1.339
971619AH1-309 GEN
Solar/Wind Harmer
3.169
971769AH1-391 GEN
Solar/Wind Harmer
7.844
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
25196108MFTGT2
Adder
1.54
25196108MFTGT2
Adder
1.43
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
4.146
971549AH1-272 GEN
Solar/Wind Harmer
14.344
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.364
274776LINCOLN ;7U
Adder
8.364
274777LINCOLN ;8U
Adder
8.364
274814UNIV PK N;0U
Adder
4.998
274807UNIV PK N;3U
Adder
4.987
274805UNIV PK N;1U
Adder
4.965
274811UNIV PK N;7U
Adder
4.954
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
972037AH1-567 GEN1
Adder
0.181
960591AF2-350 GEN
Solar/Wind Harmer
6.884
274827FISK ;RP
Adder
7.655
972227AH1-698 GEN1
Adder
2.573
963841AG1-237 GEN
Solar/Wind Harmer
2.978
274687WILL CNTY;4U
Adder
27.495
274687WILL CNTY;4U
Adder
27.495
274675JOLIET 29;7U
Adder
30.175
274675JOLIET 29;7U
Adder
29.097
972163AH1-664 GEN
Solar/Wind Harmer
7.639
972165AH1-665 GEN
Solar/Wind Harmer
6.118
274731ELWOOD EC;2P
Adder
16.163
274733ELWOOD EC;3P
Adder
16.163
274735ELWOOD EC;4P
Adder
16.163
274728ELWOOD EC;5P
Adder
16.163
970833AG2-524 GEN
Solar/Wind Harmer
7.542
970833AG2-524 GEN
Solar/Wind Harmer
5.028
945641AF1-229 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
276868AE1-113 GEN
Solar/Wind Harmer
1.363
276882AE2-255 GEN
Solar/Wind Harmer
0.794
238109AE1-109 GEN2
Solar/Wind Helper
0.106
238110AE1-109 GEN3
Solar/Wind Helper
0.106
238152AF2-075_GEN
Solar/Wind Helper
0.683
23546401DTGZ2-030
Solar/Wind Helper
0.086
238208AF1-136 C
Solar/Wind Helper
0.211
238126S14_GEN_1
Solar/Wind Helper
0.766
237085AD2-009_GEN
Solar/Wind Helper
1.588
3138216PACIFIC
Solar/Wind Helper
0.043
316411AF1-147_GEN1
Solar/Wind Helper
0.86
316415AF1-147_GEN2
Solar/Wind Helper
0.86
959381AF2-229 GEN
Solar/Wind Helper
0.345
23750501ELLIOTTS
Solar/Wind Helper
0.571
3141426STAFORD
Solar/Wind Helper
0.051
960921AF2-383 GEN
Solar/Wind Helper
0.352
205943AE1-185 GEN
Solar/Wind Helper
0.492
205956AE1-196_GEN
Solar/Wind Helper
0.492
205932AD2-116_GEN
Solar/Wind Helper
0.492
233935AB2-179 C
Solar/Wind Helper
1.227
232436AB1-176 C
Solar/Wind Helper
0.043
233923SMA
Solar/Wind Helper
0.927
233990AG1-397 GEN
Solar/Wind Helper
0.261
234033AF1-007_GEN
Solar/Wind Helper
6.787
232432Z2-076 GEN
Solar/Wind Helper
0.065
964001AG1-254 GEN
Solar/Wind Helper
0.924
228754AB1-001 C
Solar/Wind Helper
0.025
227927V4-067C
Solar/Wind Helper
0.01
219914AD2-027 C
Solar/Wind Helper
0.111
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.038
219607WPEMNERT C
Solar/Wind Helper
0.077
214067T20SOLAR
Solar/Wind Helper
0.011
203975AE1-071-GEN
Solar/Wind Helper
2.41
20715728PEM_W1-119
Solar/Wind Helper
0.093
20715828PEM_W1-120
Solar/Wind Helper
0.093
207459AE1-142 C O1
Solar/Wind Helper
0.28
316164AC1-076 GEN
Solar/Wind Helper
1.062
219620RIDERU C
Solar/Wind Helper
0.001
270166AC1-044 GEN3
50/50
6.869
23559101PLEAS2
50/50
5.385
270122AB2-093 CT
50/50
3.689
962761AG1-125 GEN
Solar/Wind Harmer
33.269
970149AG2-104 GEN
Solar/Wind Harmer
35.932
970155AG2-107 GEN
Solar/Wind Harmer
21.245
270349AD2-093_GEN
Solar/Wind Harmer
0.006
24721705FLATG2
Adder
22.865
270159DARBY CT4
Adder
9.89
970593AG2-378 GEN
Solar/Wind Harmer
1.75
270223U2-072_GEN1
Solar/Wind Harmer
0.001
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.012
270462AD2-086
Solar/Wind Harmer
0.016
971995AH1-542 GEN
Solar/Wind Harmer
2.81
270263AC1-001 GEN
Solar/Wind Harmer
0.758
270510AE1-227 GEN1
Solar/Wind Harmer
1.904
241813AF1-122_GEN
Solar/Wind Harmer
3.294
25326309TAIT D
Adder
1.153
960071AF2-298 GEN
Solar/Wind Harmer
3.651
253370AE2-315 SEC1
Adder
2.103
253371AE2-315 SEC2
Adder
1.989
927014AC1-188 GEN
Solar/Wind Harmer
0.004
246936BC-WTG1
Solar/Wind Harmer
0.295
270489AE1-102 GEN1
Solar/Wind Harmer
0.945
965421AG1-410 GEN
Solar/Wind Harmer
21.788
247521TR3_G114
Solar/Wind Harmer
0.263
270246TR4_N_V150
Solar/Wind Harmer
0.047
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.226
965011AG1-365 GEN
Solar/Wind Harmer
7.225
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
2.096
958861AF2-177 GEN
Solar/Wind Harmer
3.092
247536S-71 GEN
Solar/Wind Harmer
0.287
945371AF1-202 GEN
Solar/Wind Harmer
0.001
25194608D.CRK4
Adder
1.676
270063AE2-323 C
Solar/Wind Harmer
0.006
252507AC2-088 GEN
Solar/Wind Harmer
0.323
970245AG2-165 GEN
Solar/Wind Harmer
3.076
944231AF1-091 GEN
Solar/Wind Harmer
1.885
270005AE1-210 C O1
Solar/Wind Harmer
1.532
965031AG1-367 GEN
Solar/Wind Harmer
7.073
970947AG2-589 GEN
Solar/Wind Harmer
0.236
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.183
970825AG2-519 GEN
Solar/Wind Harmer
2.509
24639705ELKHART HY
Adder
0.155
25196808ZIMRHP
Adder
76.799
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
270032AE2-172
Solar/Wind Harmer
4.701
970291AG2-192 GEN
Solar/Wind Harmer
0.916
945111AF1-176 GEN
Solar/Wind Harmer
12.568
270505AE1-170 C O1
Solar/Wind Harmer
7.393
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.67
247522W1-056 GEN
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
7.842
25196008MFTGT1
Adder
1.397
970773AG2-487 GEN
Solar/Wind Harmer
1.237
970373AG2-245 GEN
Solar/Wind Harmer
14.699
970515AG2-329 GEN
Solar/Wind Harmer
18.197
270055AF2-134 C O1
Solar/Wind Harmer
0.005
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.071
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.706
24791305MDL-5G
Solar/Wind Harmer
0.001
970333AG2-219 GEN
Solar/Wind Harmer
4.947
274751CRETE EC ;1U
Adder
8.172
274754CRETE EC ;4U
Adder
8.172
274773LINCOLN ;4U
Adder
8.364
274774LINCOLN ;5U
Adder
8.364
274723RIVER EC ;12
Adder
17.756
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.954
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
276776AD2-060 GEN
Solar/Wind Harmer
0.719
24728605AND G2
Adder
3.784
274801UNIV PARK;4U
Adder
5.751
941551AE2-152 GEN
Solar/Wind Harmer
0.001
945681AF1-233 GEN
Solar/Wind Harmer
12.962
274676JOLIET 29;8U
Adder
30.175
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
16.202
939401AE1-172 GEN
Solar/Wind Harmer
5.109
276691AA1-018 GEN1
Solar/Wind Harmer
0.827
276901AD2-066 C O1
Solar/Wind Harmer
0.007
316095T157 G97
Solar/Wind Helper
1.455
23583801GRNGAP
Solar/Wind Helper
5.418
238108AE1-109 GEN1
Solar/Wind Helper
0.106
238185AF2-356 C
Solar/Wind Helper
2.425
238147AE2-230_GEN1
Solar/Wind Helper
0.478
238149AF1-291A_GEN
Solar/Wind Helper
0.137
235531U2-073 GEN
Solar/Wind Helper
3.034
235054AD2-180 GEN
Solar/Wind Helper
1.839
237061AD1-155 GEN
Solar/Wind Helper
0.051
238117U2-030
Solar/Wind Helper
0.314
238221AF1-254 C O1
Solar/Wind Helper
0.265
235067AD1-061 GEN
Solar/Wind Helper
0.478
237030AB1-096 C
Solar/Wind Helper
0.068
3141196NOKESVL
Solar/Wind Helper
0.999
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.335
223402AF1-300 C
Solar/Wind Helper
0.355
23751201ROTHROCK
Solar/Wind Helper
0.694
23562501BACKB
Solar/Wind Helper
0.842
205917AD1-020 ES
Solar/Wind Helper
0.356
233982AB2-133 GEN
Solar/Wind Helper
0.346
233918AB1-142 GEN
Solar/Wind Helper
0.486
233994AC2-023 GEN
Solar/Wind Helper
0.929
233996TM1833_GEN
Solar/Wind Helper
0.253
233997TMININ_4.2
Solar/Wind Helper
0.253
232406W1-004 FULL
Solar/Wind Helper
0.49
233940AF2-379 C
Solar/Wind Helper
0.06
234015AF2-250 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.225
233971AC1-093 C
Solar/Wind Helper
0.346
316044AC1-158 PL1
Solar/Wind Helper
1.252
316450AC1-158 RIC
Solar/Wind Helper
0.334
230430AE1-229_GEN
Solar/Wind Helper
3.26
230415AB2-049 C
Solar/Wind Helper
0.029
228729W2-030 C
Solar/Wind Helper
0.107
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.053
219912AD2-042 GEN
Solar/Wind Helper
0.145
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.111
316170AC1-121 GEN2
Solar/Wind Helper
0.342
959561AF2-247 GEN
Solar/Wind Helper
0.02
20720828JCB_W4-025
Solar/Wind Helper
0.061
20716028EGP_W2-019
Solar/Wind Helper
0.018
20715028HAN_X4-015
Solar/Wind Helper
0.055
219276PARKLANDSO C
Solar/Wind Helper
0.086
20714528FRN_Y2-051
Solar/Wind Helper
0.055
20720528MAN_W1-024
Solar/Wind Helper
0.027
971997AH1-543 GEN
Solar/Wind Harmer
1.86
24318805MLG1
50/50
9.842
23559001PLEAS1
50/50
5.385
270051AF1-062 GEN
50/50
11.434
970153AG2-106 GEN
Solar/Wind Harmer
21.245
961921AG1-034 GEN
Solar/Wind Harmer
7.364
241955AC1-078 GEN
Solar/Wind Harmer
0.007
241974AD2-163_GEN2
Solar/Wind Harmer
0.006
942051AE2-217 GEN
Solar/Wind Harmer
14.169
24721905FLATG4
Adder
22.865
970605AG2-385 GEN
Solar/Wind Harmer
4.731
270391AF1-285 GEN3
Solar/Wind Harmer
0.518
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.012
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270273AD2-016 GEN
Solar/Wind Harmer
0.792
972173AH1-669 GEN
Solar/Wind Harmer
3.811
270512AE1-227 GEN2
Solar/Wind Harmer
1.904
270291AC1-194 GEN
Solar/Wind Harmer
5.884
253415AE1-040 GEN
Solar/Wind Harmer
0.003
970065AG2-057 GEN
Solar/Wind Harmer
0.735
253370AE2-315 SEC1
Adder
2.103
253371AE2-315 SEC2
Adder
1.989
970191AG2-125 GEN
Solar/Wind Harmer
1.876
253406AD2-031_GEN
Solar/Wind Harmer
0.543
270491AE1-102 GEN2
Solar/Wind Harmer
0.945
270377AD1-106 GEN
Solar/Wind Harmer
2.761
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.047
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.394
959331AF2-224 GEN
Solar/Wind Harmer
5.057
965021AG1-366 GEN
Solar/Wind Harmer
2.408
270588AE1-091_GEN
Solar/Wind Harmer
5.649
971191AH1-055 GEN
Solar/Wind Harmer
18.515
944531AF1-118 GEN
Solar/Wind Harmer
32.203
270043AE2-236 GEN
Solar/Wind Harmer
4.607
270258AD1-119 GEN
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
5.953
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
10.684
270404AC1-167 GEN
Solar/Wind Harmer
0.003
25196608WSDLE5
Adder
8.745
252510AF1-249 C
Solar/Wind Harmer
0.055
970031AG2-029 GEN
Solar/Wind Harmer
4.625
25194608D.CRK4
Adder
1.676
270222AC2-111 GEN
Solar/Wind Harmer
3.603
970513AG2-328 GEN
Solar/Wind Harmer
3.076
970517AG2-330 GEN
Solar/Wind Harmer
18.457
970349AG2-230 GEN
Solar/Wind Harmer
10.632
946031AF1-268 GEN
Solar/Wind Harmer
6.74
958821AF2-173 GEN
Solar/Wind Harmer
9.902
270004AE1-209 GEN
Solar/Wind Harmer
1.532
270437AC2-090 C
Solar/Wind Harmer
0.003
247643Z2-116 C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.775
970291AG2-192 GEN
Solar/Wind Harmer
0.705
971231AH1-075 GEN
Solar/Wind Harmer
0.833
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
970611AG2-400 GEN
Solar/Wind Harmer
7.225
970627AG2-408 GEN
Solar/Wind Harmer
2.167
270007AE1-245 C
Solar/Wind Harmer
0.002
970623AG2-406 GEN
Solar/Wind Harmer
1.309
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25183208HLCRTG
Solar/Wind Harmer
0.011
944541AF1-119 GEN
Solar/Wind Harmer
0.479
960971AF2-388 GEN
Solar/Wind Harmer
4.192
942221AE2-234 GEN
Solar/Wind Harmer
0.036
252519AF1-045_GEN
Solar/Wind Harmer
6.204
252516AE2-318_GEN
Solar/Wind Harmer
5.503
970621AG2-405 GEN
Solar/Wind Harmer
1.305
247621Y3-024
Adder
0.246
970883AG2-550 GEN
Solar/Wind Harmer
7.123
970885AG2-551 GEN
Solar/Wind Harmer
2.374
270201AC2-176 GEN
Solar/Wind Harmer
0.001
25194408D.CRK1
Adder
7.711
25194508D.CRK3
Adder
1.442
964611AG1-324 GEN
Solar/Wind Harmer
0.534
252509AD1-136 GEN
Solar/Wind Harmer
0.036
970321AG2-212 GEN
Solar/Wind Harmer
3.076
270599AE1-208 GEN
Solar/Wind Harmer
6.495
270031AE2-169
Solar/Wind Harmer
3.897
270383AD1-128 GEN
Solar/Wind Harmer
0.004
270186AC1-089 GEN
Solar/Wind Harmer
0.004
247620Y3-023
Adder
0.466
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
7.834
960441AF2-335 GEN
Solar/Wind Harmer
7.065
270216AD2-079_GEN
Solar/Wind Harmer
0.001
971613AH1-306 GEN
Solar/Wind Harmer
3.385
24728805RICHG1
Adder
3.82
24728905RICHG2
Adder
3.82
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
14.072
961051AF2-396 GEN
Solar/Wind Harmer
9.381
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
8.77
965791AG1-447 GEN
Solar/Wind Harmer
6.431
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.73
274770LINCOLN ;1U
Adder
8.364
274771LINCOLN ;2U
Adder
8.364
274808UNIV PK N;4U
Adder
4.933
966841AG1-555 GEN
Solar/Wind Harmer
0.781
274803UNIV PARK;6U
Adder
5.755
274888KELLY CRK;1U
Solar/Wind Harmer
0.404
274887GEN-1.85
Solar/Wind Harmer
0.181
276843GEN-1.7
Solar/Wind Harmer
0.223
958011AF2-095 GEN
Solar/Wind Harmer
9.913
972259AH1-714 GEN
Adder
18.805
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
3.993
958481AF2-142 GEN
Solar/Wind Harmer
10.238
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.923
971573AH1-285 GEN
Solar/Wind Harmer
1.271
971677AH1-339 GEN
Solar/Wind Harmer
0.768
958491AF2-143 GEN
Solar/Wind Harmer
10.205
274879MINONK ;1U
Solar/Wind Harmer
0.287
238175AF1-290_GEN
Solar/Wind Helper
0.148
238169AE2-226 GEN1
Solar/Wind Helper
0.677
238170AE2-226 GEN2
Solar/Wind Helper
0.677
238120AE2-309 GEN
Solar/Wind Helper
0.487
235020AA1-095 C
Solar/Wind Helper
0.051
23777901MDS_W4-102
Solar/Wind Helper
0.171
23585401KL_K28_T16
Solar/Wind Helper
1.328
237034AC2-136 C
Solar/Wind Helper
0.219
237002AB1-128_GEN
Solar/Wind Helper
0.427
235063AE1-101 C2
Solar/Wind Helper
1.6
237001AB1-127_GEN
Solar/Wind Helper
0.426
23777801MSM_W1-116
Solar/Wind Helper
0.11
237025AB1-124 C
Solar/Wind Helper
0.159
237006AB1-125 GEN
Solar/Wind Helper
0.119
226929AD2-058 GEN
Solar/Wind Helper
0.096
205916AD1-020 GEN
Solar/Wind Helper
1.656
20390526W1-045 C
Solar/Wind Helper
0.338
208835TUHI V3-051
Solar/Wind Helper
0.023
208835TUHI V3-051
Solar/Wind Helper
0.023
233987AB2-037 GEN
Solar/Wind Helper
2.264
233933AB2-153 GEN
Solar/Wind Helper
0.225
232424Y1-079 C
Solar/Wind Helper
0.112
233944AB2-135 GEN
Solar/Wind Helper
0.569
233946AB2-136 GEN
Solar/Wind Helper
0.549
234036AF2-325 C
Solar/Wind Helper
0.041
233901CHERRYDALE C
Solar/Wind Helper
0.225
232408W1-005 C
Solar/Wind Helper
0.49
232410W1-006 C
Solar/Wind Helper
0.49
233939AC1-091 C
Solar/Wind Helper
0.338
233970AC1-092 C
Solar/Wind Helper
0.338
315651AD1-115 GEN
Solar/Wind Helper
0.76
316447AC1-158 HLD
Solar/Wind Helper
2.756
230433AD2-135 GEN
Solar/Wind Helper
0.016
230407AD2-065 C
Solar/Wind Helper
0.039
219921AF1-264
Solar/Wind Helper
0.049
219615MILLCREEK C
Solar/Wind Helper
0.026
963401AG1-189 GEN
Solar/Wind Helper
0.054
963391AG1-188 GEN
Solar/Wind Helper
0.079
945111AF1-176 GEN
Solar/Wind Harmer
5.709
247642Z2-115 C
Solar/Wind Harmer
0.003
24642205MAYFLWER
Adder
0.641
24441205WTRV SLR C
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.353
270356AE2-297 GEN
Solar/Wind Harmer
0.009
970217AG2-149 GEN
Solar/Wind Harmer
6.066
247604X1-042
Adder
0.418
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
964401AG1-302 GEN
Solar/Wind Harmer
0.001
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.935
970243AG2-164 GEN
Solar/Wind Harmer
4.047
970519AG2-331 GEN
Solar/Wind Harmer
17.988
970699AG2-449 GEN
Solar/Wind Harmer
1.73
274752CRETE EC ;2U
Adder
8.172
274753CRETE EC ;3U
Adder
8.172
274772LINCOLN ;3U
Adder
8.364
274724RIVER EC ;11
Adder
17.549
958171AF2-111 GEN
Solar/Wind Harmer
17.278
274802UNIV PARK;5U
Adder
5.755
276806AD2-047 C O1
Solar/Wind Harmer
3.901
970941AG2-585 GEN
Solar/Wind Harmer
8.605
274826FISK ;BP
Adder
10.802
24728705AND G3
Adder
7.914
24728505AND G1
Adder
3.784
274800UNIV PARK;3U
Adder
5.751
972038AH1-567 GEN2
Adder
0.36
972228AH1-698 GEN2
Adder
3.654
972167AH1-666 GEN
Solar/Wind Harmer
5.505
276897AD1-100 C
Solar/Wind Harmer
0.009
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
22.464
274676JOLIET 29;8U
Adder
29.097
274729ELWOOD EC;1P
Adder
16.163
274730ELWOOD EC;6P
Adder
13.491
276893AG1-478 C
Solar/Wind Harmer
0.272
270541AE2-072 C
Solar/Wind Harmer
0.009
943121AE2-341 GEN
Solar/Wind Harmer
11.459
943591AF1-030 GEN
Solar/Wind Harmer
7.62
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
276805AD2-038 GEN
Solar/Wind Harmer
0.002
964991AG1-363 GEN
Solar/Wind Helper
4.969
316097T157 G90
Solar/Wind Helper
1.455
23750701CROSSCHOOL
Solar/Wind Helper
1.397
238148AE2-230_GEN2
Solar/Wind Helper
0.48
238127S14_GEN_2
Solar/Wind Helper
0.766
238118U2-030_1
Solar/Wind Helper
0.314
237080AD1-060 GEN
Solar/Wind Helper
0.33
237038AE2-054 C
Solar/Wind Helper
0.262
235062AE1-101 C1
Solar/Wind Helper
1.6
23779801AA1-109
Solar/Wind Helper
0.187
223401AF1-299 GEN
Solar/Wind Helper
0.355
316006AB2-029 C
Solar/Wind Helper
0.113
966131AG1-482 GEN
Solar/Wind Helper
0.132
237048AF1-022 C
Solar/Wind Helper
0.159
233930AB2-032 GEN
Solar/Wind Helper
0.368
233915AB1-141 GEN
Solar/Wind Helper
0.486
232422X3-066 FULL
Solar/Wind Helper
0.11
232426Y1-080 FULL
Solar/Wind Helper
0.038
233964AF2-378 GEN
Solar/Wind Helper
0.04
233998TM1NIN_3.36
Solar/Wind Helper
0.253
232404W1-003 C
Solar/Wind Helper
0.49
232428Y3-058 C
Solar/Wind Helper
0.327
232434Z2-077 GEN
Solar/Wind Helper
0.123
233954AC2-188 GEN
Solar/Wind Helper
0.225
233950AC2-186 GEN
Solar/Wind Helper
0.112
233972AC1-094 C
Solar/Wind Helper
0.292
316045AC1-158 PL2
Solar/Wind Helper
4.009
230511AF1-262
Solar/Wind Helper
0.014
230434AG1-499 GEN
Solar/Wind Helper
0.222
228728W1-130C
Solar/Wind Helper
0.052
219258KINSLEYDEP C
Solar/Wind Helper
0.074
219904AC1-010 C
Solar/Wind Helper
0.058
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219907AC1-030 C
Solar/Wind Helper
0.033
219686LUMSOLAR_N C
Solar/Wind Helper
0.038
219304NAMERICA C
Solar/Wind Helper
0.127
316254AC1-120 GEN1
Solar/Wind Helper
1.026
20720728JCB_W1-129
Solar/Wind Helper
0.055
207445AB1-138_GEN
Solar/Wind Helper
0.101
963711AG1-223 GEN
Solar/Wind Helper
0.062
20714828MDF_W3-079
Solar/Wind Helper
0.126
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.299
20715228NPK_W1-113
Solar/Wind Helper
0.075
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.183
NYPJM->LTFIMP_NY
CLTF
4.628
LGEELTFEXP_LGEE->PJM
CLTF
6.497
WECLTFEXP_WEC->PJM
CLTF
3.686
AG2-052LTFEXP_AG2-052->PJM
LTF
0.231
AH1-155LTFEXP_AH1-155->PJM
LTF
0.346
CPLELTFEXP_CPLE->PJM
CLTF
0.567
CBM West 2LTFEXP_CBM-W2->PJM
CBM
108.576
LAGNLTFEXP_LAGN->PJM
CLTF
14.268
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.432
TVALTFEXP_TVA->PJM
CLTF
7.011
CBM West 1LTFEXP_CBM-W1->PJM
CBM
137.982
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.984
MECLTFEXP_MEC->PJM
CLTF
15.319
SIGELTFEXP_SIGE->PJM
CLTF
0.486

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o AEP_P4_#2942_05KAMMER 765_PP_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.95 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5175.39
MW Contribution:25.99
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
18.357
270159DARBY CT4
50/50
13.387
962761AG1-125 GEN
Solar/Wind Harmer
59.614
970149AG2-104 GEN
Solar/Wind Harmer
73.623
970155AG2-107 GEN
Solar/Wind Harmer
25.994
270349AD2-093_GEN
Solar/Wind Harmer
6.249
270223U2-072_GEN1
Solar/Wind Harmer
2.862
270578AF1-285 GEN2
Solar/Wind Harmer
1.75
270391AF1-285 GEN3
Solar/Wind Harmer
1.75
970593AG2-378 GEN
Solar/Wind Harmer
2.869
270462AD2-086
Solar/Wind Harmer
9.72
253343AC1-166 GEN
Solar/Wind Harmer
1.495
253325AC1-069 GEN
Solar/Wind Harmer
1.442
25326309TAIT D
Adder
1.387
960071AF2-298 GEN
Solar/Wind Harmer
6.296
965011AG1-365 GEN
Solar/Wind Harmer
12.615
253370AE2-315 SEC1
Adder
2.522
253371AE2-315 SEC2
Adder
2.385
965651AG1-433 GEN
Solar/Wind Harmer
6.877
970245AG2-165 GEN
Solar/Wind Harmer
22.419
958861AF2-177 GEN
Solar/Wind Harmer
13.71
971995AH1-542 GEN
Solar/Wind Harmer
13.79
945371AF1-202 GEN
Solar/Wind Harmer
8.699
247521TR3_G114
Solar/Wind Harmer
4.176
270246TR4_N_V150
Solar/Wind Harmer
1.057
24721705FLATG2
Adder
25.137
965421AG1-410 GEN
Solar/Wind Harmer
37.184
246936BC-WTG1
Solar/Wind Harmer
4.841
270489AE1-102 GEN1
Solar/Wind Harmer
1.608
247536S-71 GEN
Solar/Wind Harmer
4.98
270005AE1-210 C O1
Solar/Wind Harmer
6.717
965031AG1-367 GEN
Solar/Wind Harmer
12.29
270063AE2-323 C
Solar/Wind Harmer
2.705
24695305TIMB G C
Solar/Wind Harmer
6.75
970825AG2-519 GEN
Solar/Wind Harmer
2.886
270263AC1-001 GEN
Solar/Wind Harmer
1.282
270032AE2-172
Solar/Wind Harmer
5.689
970291AG2-192 GEN
Solar/Wind Harmer
1.589
942081AE2-220 GEN
Solar/Wind Harmer
7.808
270239V3-007_GEN1
Solar/Wind Harmer
2.102
24639705ELKHART HY
Adder
0.187
274773LINCOLN ;4U
Adder
10.257
274774LINCOLN ;5U
Adder
10.257
274723RIVER EC ;12
Adder
21.689
274751CRETE EC ;1U
Adder
9.969
274754CRETE EC ;4U
Adder
9.969
274812UNIV PK N;8U
Adder
6.05
274801UNIV PARK;4U
Adder
7.031
274676JOLIET 29;8U
Adder
36.901
274674JOLIET 9 ;6U
Adder
18.512
274732ELWOOD EC;7P
Adder
19.763
274745AC1-111 GEN9
Adder
6.698
274682WAUKEGAN ;7U
Adder
21.437
274828WAUKEGAN ;BP
Adder
13.169
25194608D.CRK4
Adder
1.955
24728605AND G2
Adder
4.529
274822ROCKFORD ;11
Adder
23.174
972235AH1-702 GEN1
Adder
2.974
25196808ZIMRHP
Adder
57.753
254303AC2-168 GEN
Solar/Wind Helper
0.156
237046AF1-021 C
Solar/Wind Helper
0.468
241966AE1-183 GEN
Solar/Wind Helper
0.251
238185AF2-356 C
Solar/Wind Helper
2.051
20089226LOOKOUT
Solar/Wind Helper
0.549
20088826HIGHLAND
Solar/Wind Helper
0.858
20094526CT_V3-030
Solar/Wind Helper
0.452
235054AD2-180 GEN
Solar/Wind Helper
1.586
964201AG1-281 GEN
Solar/Wind Helper
0.463
238117U2-030
Solar/Wind Helper
0.272
235531U2-073 GEN
Solar/Wind Helper
2.578
964391AG1-301 GEN
Solar/Wind Helper
0.452
203954AE2-126 C
Solar/Wind Helper
0.449
23751201ROTHROCK
Solar/Wind Helper
0.661
238206AE2-263_GEN
Solar/Wind Helper
0.87
959471AF2-238 GEN
Solar/Wind Helper
0.445
203860AG1-193 C
Solar/Wind Helper
0.222
23562501BACKB
Solar/Wind Helper
0.804
253432AC1-085 GEN2
Solar/Wind Harmer
0.293
270156DARBY CT1
50/50
13.604
270157DARBY CT2
50/50
13.571
270158DARBY CT3
50/50
13.354
270036AE2-216 BAT
50/50
8.921
962771AG1-126 GEN
Solar/Wind Harmer
59.614
270284AF1-227 GEN1
Solar/Wind Harmer
9.137
270286AF1-227 GEN2
Solar/Wind Harmer
3.38
270287AF1-227 GEN3
Solar/Wind Harmer
3.38
270459AD2-067 GEN
Solar/Wind Harmer
13.262
961821AG1-024 GEN
Solar/Wind Harmer
13.464
270520AE2-214 GEN
Solar/Wind Harmer
9.4
270054AF2-122 C O1
Solar/Wind Harmer
5.025
253383AE2-342_GEN
Solar/Wind Harmer
1.352
241973AD2-163_GEN1
Solar/Wind Harmer
2.945
943861AF1-054 GEN
Solar/Wind Harmer
5.682
943851AF1-053 GEN
Solar/Wind Harmer
2.746
270578AF1-285 GEN2
Solar/Wind Harmer
0.673
945631AF1-228 GEN
Solar/Wind Harmer
6.732
270302AB2-170 GEN
Solar/Wind Harmer
11.684
270317AD1-130_GEN
Solar/Wind Harmer
4.479
241972AD1-140 GEN
Solar/Wind Harmer
6.007
970689AG2-444 GEN
Solar/Wind Harmer
21.667
270432AC2-029 GEN
Solar/Wind Harmer
9.275
270269AC2-059
Solar/Wind Harmer
11.946
24729505KEY G4
Adder
8.242
270071AF1-092 GEN
Solar/Wind Harmer
18.992
253372AE2-315 SEC3
Adder
2.385
253372AE2-315 SEC3
Adder
2.385
958711AF2-162 GEN
Solar/Wind Harmer
1.273
965101AG1-375 GEN
Solar/Wind Harmer
12.544
25306009OHH W.
Adder
3.614
253349AC2-067 GEN
Solar/Wind Harmer
6.244
253400AC2-068 GEN
Solar/Wind Harmer
2.511
945581AF1-223 GEN
Solar/Wind Harmer
5.655
963791AG1-232 GEN
Solar/Wind Harmer
16.817
971347AH1-153 GEN
Solar/Wind Harmer
18.681
965051AG1-369 GEN
Solar/Wind Harmer
6.202
965041AG1-368 GEN
Solar/Wind Harmer
12.384
270024AE2-089 GEN
Solar/Wind Harmer
5.81
957201AF2-014 GEN
Solar/Wind Harmer
5.611
270435AC2-044 GEN
Solar/Wind Harmer
2.474
270340AC2-060 GEN
Solar/Wind Harmer
3.749
961761AG1-017 GEN
Solar/Wind Harmer
0.528
270543AE2-219 C
Solar/Wind Harmer
6.289
971029AG2-637 GEN
Solar/Wind Harmer
18.391
971673AH1-337 GEN
Solar/Wind Harmer
5.637
970115AG2-085 GEN
Solar/Wind Harmer
4.901
270594AE1-207 GEN
Solar/Wind Harmer
17.978
965461AG1-414 GEN
Solar/Wind Harmer
2.772
970289AG2-191 GEN
Solar/Wind Harmer
2.322
270240V3-007_GEN2
Solar/Wind Harmer
7.556
960681AF2-359 GEN
Solar/Wind Harmer
4.61
971771AH1-392 GEN
Solar/Wind Harmer
10.956
274775LINCOLN ;6U
Adder
10.257
274776LINCOLN ;7U
Adder
10.257
274777LINCOLN ;8U
Adder
10.257
274814UNIV PK N;0U
Adder
6.103
274807UNIV PK N;3U
Adder
6.089
274805UNIV PK N;1U
Adder
6.063
274811UNIV PK N;7U
Adder
6.05
972227AH1-698 GEN1
Adder
3.146
972037AH1-567 GEN1
Adder
0.221
274827FISK ;RP
Adder
9.358
274687WILL CNTY;4U
Adder
33.62
274687WILL CNTY;4U
Adder
33.62
274675JOLIET 29;7U
Adder
36.901
274675JOLIET 29;7U
Adder
35.583
274731ELWOOD EC;2P
Adder
19.763
274733ELWOOD EC;3P
Adder
19.763
274735ELWOOD EC;4P
Adder
19.763
274728ELWOOD EC;5P
Adder
19.763
274746AC1-111 G10
Adder
6.698
274744AC1-111 GEN8
Adder
6.698
25196408WSDLE3
Adder
10.507
25196308WSDLE2
Adder
10.416
25196208WSDLE1
Adder
10.39
25196708WSDLE6
Adder
10.364
25196508WSDLE4
Adder
10.103
274823ROCKFORD ;21
Adder
23.006
254304AE2-114 C
Solar/Wind Helper
0.216
241982AE2-343 S C
Solar/Wind Helper
0.22
241997AF1-093 GEN
Solar/Wind Helper
0.251
23750501ELLIOTTS
Solar/Wind Helper
0.617
20092526R32
Solar/Wind Helper
1.112
203961AE2-224 GEN
Solar/Wind Helper
2.307
20091526CHSTN_FL
Solar/Wind Helper
0.557
20090526Q36
Solar/Wind Helper
0.998
203993AD2-133_GEN1
Solar/Wind Helper
0.998
203846AF2-130 C
Solar/Wind Helper
0.431
238126S14_GEN_1
Solar/Wind Helper
0.648
941231AE2-117 GEN
Solar/Wind Helper
0.453
203855AF2-088 C
Solar/Wind Helper
0.146
203804AE2-113_GEN
Solar/Wind Helper
1.661
270051AF1-062 GEN
50/50
16.969
270475AD2-096_GEN
50/50
10
970153AG2-106 GEN
Solar/Wind Harmer
25.994
961921AG1-034 GEN
Solar/Wind Harmer
20.196
241955AC1-078 GEN
Solar/Wind Harmer
11.082
241974AD2-163_GEN2
Solar/Wind Harmer
2.945
942051AE2-217 GEN
Solar/Wind Harmer
26.379
942871AE2-306 GEN
Solar/Wind Harmer
1.313
270391AF1-285 GEN3
Solar/Wind Harmer
0.673
970605AG2-385 GEN
Solar/Wind Harmer
7.746
270485AE1-090_GEN
Solar/Wind Harmer
0.845
253338AC1-165 GEN
Solar/Wind Harmer
1.495
253333AC1-068 GEN
Solar/Wind Harmer
1.442
960801AF2-371 GEN
Solar/Wind Harmer
3.362
964871AG1-351 GEN
Solar/Wind Harmer
2.322
270273AD2-016 GEN
Solar/Wind Harmer
3.416
944531AF1-118 GEN
Solar/Wind Harmer
44.619
972173AH1-669 GEN
Solar/Wind Harmer
6.355
270043AE2-236 GEN
Solar/Wind Harmer
6.955
959331AF2-224 GEN
Solar/Wind Harmer
12.615
965021AG1-366 GEN
Solar/Wind Harmer
2.934
253303V4-073 C
Solar/Wind Harmer
0.146
253370AE2-315 SEC1
Adder
2.522
253371AE2-315 SEC2
Adder
2.385
970513AG2-328 GEN
Solar/Wind Harmer
22.419
970517AG2-330 GEN
Solar/Wind Harmer
20.333
253415AE1-040 GEN
Solar/Wind Harmer
1.412
970349AG2-230 GEN
Solar/Wind Harmer
18.681
270191TR4_S_V150
Solar/Wind Harmer
3.726
270247TR4_N_V136
Solar/Wind Harmer
1.057
24721905FLATG4
Adder
25.137
971617AH1-308 GEN
Solar/Wind Harmer
7.196
270491AE1-102 GEN2
Solar/Wind Harmer
1.608
962031AG1-047 GEN
Solar/Wind Harmer
3.725
957741AF2-068 GEN
Solar/Wind Harmer
18.489
970031AG2-029 GEN
Solar/Wind Harmer
36.885
958821AF2-173 GEN
Solar/Wind Harmer
17.206
270004AE1-209 GEN
Solar/Wind Harmer
6.717
946031AF1-268 GEN
Solar/Wind Harmer
10.188
253406AD2-031_GEN
Solar/Wind Harmer
1.568
970289AG2-191 GEN
Solar/Wind Harmer
0.938
970291AG2-192 GEN
Solar/Wind Harmer
0.853
247642Z2-115 C
Solar/Wind Harmer
0.078
270437AC2-090 C
Solar/Wind Harmer
6.819
247643Z2-116 C
Solar/Wind Harmer
0.085
274772LINCOLN ;3U
Adder
10.257
274724RIVER EC ;11
Adder
21.436
274752CRETE EC ;2U
Adder
9.969
274753CRETE EC ;3U
Adder
9.969
24642205MAYFLWER
Adder
0.769
274802UNIV PARK;5U
Adder
7.033
972228AH1-698 GEN2
Adder
4.468
274826FISK ;BP
Adder
13.204
274800UNIV PARK;3U
Adder
7.031
972038AH1-567 GEN2
Adder
0.44
274676JOLIET 29;8U
Adder
35.583
274729ELWOOD EC;1P
Adder
19.763
274730ELWOOD EC;6P
Adder
19.763
274734ELWOOD EC;8P
Adder
19.763
274736ELWOOD EC;9P
Adder
19.763
274682WAUKEGAN ;7U
Adder
21.437
25196608WSDLE5
Adder
10.207
25194608D.CRK4
Adder
1.955
24728705AND G3
Adder
9.473
24728505AND G1
Adder
4.529
972236AH1-702 GEN2
Adder
2.586
235058AG1-386 C
Solar/Wind Helper
0.458
237048AF1-022 C
Solar/Wind Helper
0.178
254305AE2-115 C
Solar/Wind Helper
0.216
237043AE2-125 C
Solar/Wind Helper
0.174
964991AG1-363 GEN
Solar/Wind Helper
3.62
202652Y1-033 WT C
Solar/Wind Helper
0.532
20089126CSLMN_L13
Solar/Wind Helper
0.564
20089026BF_G21_K23
Solar/Wind Helper
0.447
23750701CROSSCHOOL
Solar/Wind Helper
1.136
203818AF1-086 GEN
Solar/Wind Helper
1.615
238118U2-030_1
Solar/Wind Helper
0.272
238127S14_GEN_2
Solar/Wind Helper
0.648
203854AF2-039 C
Solar/Wind Helper
0.304
20334926Z1-069 C
Solar/Wind Helper
1.285
238202AE2-262_GEN
Solar/Wind Helper
0.914
959441AF2-235 GEN
Solar/Wind Helper
0.223
941421AE2-139 GEN
Solar/Wind Helper
2.214
253316AC1-085 GEN3
Solar/Wind Harmer
9.161
253433AC1-085 GEN1
Solar/Wind Harmer
5.815
270119AB2-067 GEN1
50/50
18.357
270120AB2-067 GEN2
50/50
18.357
270160DARBY CT5
50/50
0.729
270161DARBY CT6
50/50
0.719
270466AD2-091
50/50
8.11
270471AD2-092_GEN
Solar/Wind Harmer
6.249
946101AF1-275 GEN
Solar/Wind Harmer
2.346
942861AE2-305 GEN
Solar/Wind Harmer
11.513
270224U2-072_GEN2
Solar/Wind Harmer
2.862
270227U2-072_GEN3
Solar/Wind Harmer
2.862
270228U2-072_GEN4
Solar/Wind Harmer
2.862
270231U2-072_GEN5
Solar/Wind Harmer
2.862
970077AG2-063 GEN
Solar/Wind Harmer
7.746
270518AE2-148 GEN
Solar/Wind Harmer
16.865
964601AG1-323 GEN
Solar/Wind Harmer
4.402
964601AG1-323 GEN
Solar/Wind Harmer
2.047
938701AE1-092 GEN
Solar/Wind Harmer
28.355
253378AE2-206_GEN
Solar/Wind Harmer
4.74
276820AF1-078_GEN
Solar/Wind Harmer
2.106
25326509SID D
Adder
1.698
25326109MON D
Adder
1.683
25322209TAIT E
Adder
12.344
25322209TAIT E
Adder
12.066
970611AG2-400 GEN
Solar/Wind Harmer
12.615
253370AE2-315 SEC1
Adder
2.522
944541AF1-119 GEN
Solar/Wind Harmer
5.27
960971AF2-388 GEN
Solar/Wind Harmer
13.754
970321AG2-212 GEN
Solar/Wind Harmer
22.419
942221AE2-234 GEN
Solar/Wind Harmer
0.913
246938BC-WTG3
Solar/Wind Harmer
4.925
246937BC-WTG2
Solar/Wind Harmer
4.841
270599AE1-208 GEN
Solar/Wind Harmer
10.052
270031AE2-169
Solar/Wind Harmer
10.052
253394AE2-221_GEN
Solar/Wind Harmer
5.603
253398AE2-221_GEN2
Solar/Wind Harmer
5.603
270201AC2-176 GEN
Solar/Wind Harmer
6.336
964611AG1-324 GEN
Solar/Wind Harmer
1.452
964611AG1-324 GEN
Solar/Wind Harmer
0.644
247621Y3-024
Adder
0.297
970883AG2-550 GEN
Solar/Wind Harmer
12.281
970885AG2-551 GEN
Solar/Wind Harmer
2.856
970825AG2-519 GEN
Solar/Wind Harmer
12.934
960441AF2-335 GEN
Solar/Wind Harmer
12.253
270383AD1-128 GEN
Solar/Wind Harmer
7.465
24379505HDWTR1G C
Solar/Wind Harmer
9.658
270209AC1-174_GEN
Solar/Wind Harmer
6.816
926881AC1-175 GEN
Solar/Wind Harmer
6.816
965681AG1-436 GEN
Solar/Wind Harmer
15.255
965791AG1-447 GEN
Solar/Wind Harmer
7.805
270216AD2-079_GEN
Solar/Wind Harmer
0.738
247620Y3-023
Adder
0.56
274770LINCOLN ;1U
Adder
10.257
274771LINCOLN ;2U
Adder
10.257
274808UNIV PK N;4U
Adder
6.023
972259AH1-714 GEN
Adder
23.016
274803UNIV PARK;6U
Adder
7.033
24728805RICHG1
Adder
4.555
24728905RICHG2
Adder
4.555
274674JOLIET 9 ;6U
Adder
18.512
274696ROCKY RD ;4P
Adder
13.603
274695ROCKY RD ;2P
Adder
13.289
274693ROCKY RD ;1P
Adder
13.158
274697ROCKY RD ;3P
Adder
3.61
274683WAUKEGAN ;8U
Adder
25.124
274683WAUKEGAN ;8U
Adder
21.178
25194408D.CRK1
Adder
8.991
25194508D.CRK3
Adder
1.681
23652301WDPWR_K20
Solar/Wind Helper
0.139
241967AE2-285_GEN
Solar/Wind Helper
0.629
241801AE1-079 GEN
Solar/Wind Helper
0.245
241985AE1-237 GEN
Solar/Wind Helper
0.245
962101AG1-054 GEN
Solar/Wind Helper
0.639
946071AF1-272 GEN
Solar/Wind Helper
2.599
23585401KL_K28_T16
Solar/Wind Helper
1.182
203955AF1-039 C O1
Solar/Wind Helper
0.351
944781AF1-143 GEN
Solar/Wind Helper
2.342
20083426SW_E13_K22
Solar/Wind Helper
0.053
20084626FORWARD
Solar/Wind Helper
0.34
20088926STNY CRK
Solar/Wind Helper
0.78
203940AF1-140 C
Solar/Wind Helper
0.378
20088626ARWF_N39
Solar/Wind Helper
1.161
20303426NA_O38_P22
Solar/Wind Helper
0.952
946381AF1-302 GEN
Solar/Wind Helper
0.212
203853AF1-134 C O1
Solar/Wind Helper
0.457
203952AE2-129 C
Solar/Wind Helper
0.453
203946AE2-131 C
Solar/Wind Helper
0.454
238120AE2-309 GEN
Solar/Wind Helper
0.406
238217AF1-153 C O1
Solar/Wind Helper
0.226
20398826ARMNA MT
Solar/Wind Helper
1.425
253317AC1-085 GEN4
Solar/Wind Harmer
9.161
NYPJM->LTFIMP_NY
CLTF
5.405
LGEELTFEXP_LGEE->PJM
CLTF
7.595
WECLTFEXP_WEC->PJM
CLTF
4.506
AG2-052LTFEXP_AG2-052->PJM
LTF
0.28
AH1-155LTFEXP_AH1-155->PJM
LTF
0.42
CPLELTFEXP_CPLE->PJM
CLTF
2.579
CBM West 2LTFEXP_CBM-W2->PJM
CBM
132.191
LAGNLTFEXP_LAGN->PJM
CLTF
17.654
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.421
TVALTFEXP_TVA->PJM
CLTF
8.605
CBM West 1LTFEXP_CBM-W1->PJM
CBM
154.079
CBM South 1LTFEXP_CBM-S1->PJM
CBM
33.973
MECLTFEXP_MEC->PJM
CLTF
18.683
SIGELTFEXP_SIGE->PJM
CLTF
0.577

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o AP_P2-3_MP-500-020_SRT-SL


Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-3_MP-500-020_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.6 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4995.09
MW Contribution:26.24
Bus #Bus NameTypeMW Contribution
270051AF1-062 GEN
50/50
17.137
270475AD2-096_GEN
50/50
10.101
970153AG2-106 GEN
Solar/Wind Harmer
26.237
961921AG1-034 GEN
Solar/Wind Harmer
20.428
241955AC1-078 GEN
Solar/Wind Harmer
11.216
241974AD2-163_GEN2
Solar/Wind Harmer
2.98
942051AE2-217 GEN
Solar/Wind Harmer
26.699
942871AE2-306 GEN
Solar/Wind Harmer
1.328
270391AF1-285 GEN3
Solar/Wind Harmer
0.681
970605AG2-385 GEN
Solar/Wind Harmer
7.841
270485AE1-090_GEN
Solar/Wind Harmer
0.855
253338AC1-165 GEN
Solar/Wind Harmer
1.515
253333AC1-068 GEN
Solar/Wind Harmer
1.461
960801AF2-371 GEN
Solar/Wind Harmer
3.409
964871AG1-351 GEN
Solar/Wind Harmer
2.354
270273AD2-016 GEN
Solar/Wind Harmer
3.465
944531AF1-118 GEN
Solar/Wind Harmer
45.213
972173AH1-669 GEN
Solar/Wind Harmer
6.446
270043AE2-236 GEN
Solar/Wind Harmer
7.048
959331AF2-224 GEN
Solar/Wind Harmer
12.784
965021AG1-366 GEN
Solar/Wind Harmer
2.973
253303V4-073 C
Solar/Wind Harmer
0.148
253370AE2-315 SEC1
Adder
2.557
253371AE2-315 SEC2
Adder
2.418
970513AG2-328 GEN
Solar/Wind Harmer
22.72
970517AG2-330 GEN
Solar/Wind Harmer
20.606
253415AE1-040 GEN
Solar/Wind Harmer
1.432
970349AG2-230 GEN
Solar/Wind Harmer
18.933
270191TR4_S_V150
Solar/Wind Harmer
3.777
270166AC1-044 GEN3
50/50
18.415
270159DARBY CT4
50/50
13.555
962761AG1-125 GEN
Solar/Wind Harmer
60.17
970149AG2-104 GEN
Solar/Wind Harmer
74.31
970155AG2-107 GEN
Solar/Wind Harmer
26.237
270349AD2-093_GEN
Solar/Wind Harmer
6.312
270223U2-072_GEN1
Solar/Wind Harmer
2.896
270578AF1-285 GEN2
Solar/Wind Harmer
1.771
270391AF1-285 GEN3
Solar/Wind Harmer
1.771
970593AG2-378 GEN
Solar/Wind Harmer
2.904
270462AD2-086
Solar/Wind Harmer
9.839
253343AC1-166 GEN
Solar/Wind Harmer
1.515
253325AC1-069 GEN
Solar/Wind Harmer
1.461
25326309TAIT D
Adder
1.406
960071AF2-298 GEN
Solar/Wind Harmer
6.383
965011AG1-365 GEN
Solar/Wind Harmer
12.784
253370AE2-315 SEC1
Adder
2.557
253371AE2-315 SEC2
Adder
2.418
965651AG1-433 GEN
Solar/Wind Harmer
6.97
970245AG2-165 GEN
Solar/Wind Harmer
22.72
958861AF2-177 GEN
Solar/Wind Harmer
13.896
971995AH1-542 GEN
Solar/Wind Harmer
13.983
945371AF1-202 GEN
Solar/Wind Harmer
8.818
247521TR3_G114
Solar/Wind Harmer
4.233
270246TR4_N_V150
Solar/Wind Harmer
1.071
24721705FLATG2
Adder
25.49
965421AG1-410 GEN
Solar/Wind Harmer
37.691
246936BC-WTG1
Solar/Wind Harmer
4.907
270489AE1-102 GEN1
Solar/Wind Harmer
1.63
247536S-71 GEN
Solar/Wind Harmer
5.049
270005AE1-210 C O1
Solar/Wind Harmer
6.81
965031AG1-367 GEN
Solar/Wind Harmer
12.46
270063AE2-323 C
Solar/Wind Harmer
2.742
24695305TIMB G C
Solar/Wind Harmer
6.843
970825AG2-519 GEN
Solar/Wind Harmer
2.926
270263AC1-001 GEN
Solar/Wind Harmer
1.301
270032AE2-172
Solar/Wind Harmer
5.768
970291AG2-192 GEN
Solar/Wind Harmer
1.611
942081AE2-220 GEN
Solar/Wind Harmer
7.917
270239V3-007_GEN1
Solar/Wind Harmer
2.131
253432AC1-085 GEN2
Solar/Wind Harmer
0.33
24639705ELKHART HY
Adder
0.189
274773LINCOLN ;4U
Adder
10.399
274774LINCOLN ;5U
Adder
10.399
274723RIVER EC ;12
Adder
21.989
274751CRETE EC ;1U
Adder
10.107
274754CRETE EC ;4U
Adder
10.107
274812UNIV PK N;8U
Adder
6.133
274801UNIV PARK;4U
Adder
7.128
274676JOLIET 29;8U
Adder
37.414
274674JOLIET 9 ;6U
Adder
18.77
274732ELWOOD EC;7P
Adder
20.037
274745AC1-111 GEN9
Adder
6.792
274682WAUKEGAN ;7U
Adder
21.737
274828WAUKEGAN ;BP
Adder
13.354
25194608D.CRK4
Adder
1.983
24728605AND G2
Adder
4.594
274822ROCKFORD ;11
Adder
23.501
972235AH1-702 GEN1
Adder
3.016
25196808ZIMRHP
Adder
58.606
254303AC2-168 GEN
Solar/Wind Helper
0.155
237046AF1-021 C
Solar/Wind Helper
0.465
241966AE1-183 GEN
Solar/Wind Helper
0.248
238185AF2-356 C
Solar/Wind Helper
2.036
20089226LOOKOUT
Solar/Wind Helper
0.545
20088826HIGHLAND
Solar/Wind Helper
0.85
20094526CT_V3-030
Solar/Wind Helper
0.448
235054AD2-180 GEN
Solar/Wind Helper
1.575
964201AG1-281 GEN
Solar/Wind Helper
0.458
238117U2-030
Solar/Wind Helper
0.27
235531U2-073 GEN
Solar/Wind Helper
2.559
964391AG1-301 GEN
Solar/Wind Helper
0.448
203954AE2-126 C
Solar/Wind Helper
0.445
23751201ROTHROCK
Solar/Wind Helper
0.656
238206AE2-263_GEN
Solar/Wind Helper
0.861
959471AF2-238 GEN
Solar/Wind Helper
0.441
270156DARBY CT1
50/50
13.775
270157DARBY CT2
50/50
13.741
270158DARBY CT3
50/50
13.521
270036AE2-216 BAT
50/50
9.031
962771AG1-126 GEN
Solar/Wind Harmer
60.17
270284AF1-227 GEN1
Solar/Wind Harmer
9.235
270286AF1-227 GEN2
Solar/Wind Harmer
3.417
270287AF1-227 GEN3
Solar/Wind Harmer
3.417
270459AD2-067 GEN
Solar/Wind Harmer
13.414
961821AG1-024 GEN
Solar/Wind Harmer
13.619
270247TR4_N_V136
Solar/Wind Harmer
1.071
24721905FLATG4
Adder
25.49
971617AH1-308 GEN
Solar/Wind Harmer
7.295
270491AE1-102 GEN2
Solar/Wind Harmer
1.63
962031AG1-047 GEN
Solar/Wind Harmer
3.777
957741AF2-068 GEN
Solar/Wind Harmer
18.744
970031AG2-029 GEN
Solar/Wind Harmer
37.389
958821AF2-173 GEN
Solar/Wind Harmer
17.445
270004AE1-209 GEN
Solar/Wind Harmer
6.81
946031AF1-268 GEN
Solar/Wind Harmer
10.33
253406AD2-031_GEN
Solar/Wind Harmer
1.591
970289AG2-191 GEN
Solar/Wind Harmer
0.951
970291AG2-192 GEN
Solar/Wind Harmer
0.865
247642Z2-115 C
Solar/Wind Harmer
0.079
270437AC2-090 C
Solar/Wind Harmer
6.914
247643Z2-116 C
Solar/Wind Harmer
0.086
253316AC1-085 GEN3
Solar/Wind Harmer
10.337
253433AC1-085 GEN1
Solar/Wind Harmer
6.562
274772LINCOLN ;3U
Adder
10.399
274724RIVER EC ;11
Adder
21.733
274752CRETE EC ;2U
Adder
10.107
274753CRETE EC ;3U
Adder
10.107
24642205MAYFLWER
Adder
0.779
274802UNIV PARK;5U
Adder
7.13
972228AH1-698 GEN2
Adder
4.53
274826FISK ;BP
Adder
13.387
274800UNIV PARK;3U
Adder
7.128
972038AH1-567 GEN2
Adder
0.446
274676JOLIET 29;8U
Adder
36.078
274729ELWOOD EC;1P
Adder
20.037
274730ELWOOD EC;6P
Adder
20.037
274734ELWOOD EC;8P
Adder
20.037
274736ELWOOD EC;9P
Adder
20.037
274682WAUKEGAN ;7U
Adder
21.737
25196608WSDLE5
Adder
10.356
25194608D.CRK4
Adder
1.983
24728705AND G3
Adder
9.609
24728505AND G1
Adder
4.594
972236AH1-702 GEN2
Adder
2.622
235058AG1-386 C
Solar/Wind Helper
0.453
237048AF1-022 C
Solar/Wind Helper
0.177
254305AE2-115 C
Solar/Wind Helper
0.213
237043AE2-125 C
Solar/Wind Helper
0.172
964991AG1-363 GEN
Solar/Wind Helper
3.598
202652Y1-033 WT C
Solar/Wind Helper
0.528
23750701CROSSCHOOL
Solar/Wind Helper
1.128
20089126CSLMN_L13
Solar/Wind Helper
0.559
20089026BF_G21_K23
Solar/Wind Helper
0.443
203818AF1-086 GEN
Solar/Wind Helper
1.599
238118U2-030_1
Solar/Wind Helper
0.27
238127S14_GEN_2
Solar/Wind Helper
0.644
203854AF2-039 C
Solar/Wind Helper
0.301
20334926Z1-069 C
Solar/Wind Helper
1.271
238202AE2-262_GEN
Solar/Wind Helper
0.905
959441AF2-235 GEN
Solar/Wind Helper
0.22
946181AF1-283 GEN
Solar/Wind Harmer
8.323
270520AE2-214 GEN
Solar/Wind Harmer
9.509
270054AF2-122 C O1
Solar/Wind Harmer
5.085
253383AE2-342_GEN
Solar/Wind Harmer
1.367
241973AD2-163_GEN1
Solar/Wind Harmer
2.98
943861AF1-054 GEN
Solar/Wind Harmer
5.751
943851AF1-053 GEN
Solar/Wind Harmer
2.779
270578AF1-285 GEN2
Solar/Wind Harmer
0.681
945631AF1-228 GEN
Solar/Wind Harmer
6.816
270302AB2-170 GEN
Solar/Wind Harmer
11.828
270317AD1-130_GEN
Solar/Wind Harmer
4.534
241972AD1-140 GEN
Solar/Wind Harmer
6.086
970689AG2-444 GEN
Solar/Wind Harmer
21.964
270432AC2-029 GEN
Solar/Wind Harmer
9.402
270269AC2-059
Solar/Wind Harmer
12.116
24729505KEY G4
Adder
8.352
270071AF1-092 GEN
Solar/Wind Harmer
19.246
253372AE2-315 SEC3
Adder
2.418
253372AE2-315 SEC3
Adder
2.418
958711AF2-162 GEN
Solar/Wind Harmer
1.29
25306009OHH W.
Adder
3.664
965101AG1-375 GEN
Solar/Wind Harmer
12.713
253349AC2-067 GEN
Solar/Wind Harmer
6.33
253400AC2-068 GEN
Solar/Wind Harmer
2.546
945581AF1-223 GEN
Solar/Wind Harmer
5.732
963791AG1-232 GEN
Solar/Wind Harmer
17.046
971347AH1-153 GEN
Solar/Wind Harmer
18.933
965051AG1-369 GEN
Solar/Wind Harmer
6.287
965041AG1-368 GEN
Solar/Wind Harmer
12.553
270024AE2-089 GEN
Solar/Wind Harmer
5.889
270340AC2-060 GEN
Solar/Wind Harmer
3.803
957201AF2-014 GEN
Solar/Wind Harmer
5.688
270435AC2-044 GEN
Solar/Wind Harmer
2.508
961761AG1-017 GEN
Solar/Wind Harmer
0.535
270543AE2-219 C
Solar/Wind Harmer
6.376
971029AG2-637 GEN
Solar/Wind Harmer
18.648
971673AH1-337 GEN
Solar/Wind Harmer
5.716
970115AG2-085 GEN
Solar/Wind Harmer
4.969
270594AE1-207 GEN
Solar/Wind Harmer
18.228
965461AG1-414 GEN
Solar/Wind Harmer
2.81
970289AG2-191 GEN
Solar/Wind Harmer
2.355
270240V3-007_GEN2
Solar/Wind Harmer
7.662
960681AF2-359 GEN
Solar/Wind Harmer
4.674
274775LINCOLN ;6U
Adder
10.399
274776LINCOLN ;7U
Adder
10.399
274777LINCOLN ;8U
Adder
10.399
274814UNIV PK N;0U
Adder
6.187
274807UNIV PK N;3U
Adder
6.174
274805UNIV PK N;1U
Adder
6.147
274811UNIV PK N;7U
Adder
6.133
972037AH1-567 GEN1
Adder
0.224
972227AH1-698 GEN1
Adder
3.19
274827FISK ;RP
Adder
9.488
274687WILL CNTY;4U
Adder
34.087
274687WILL CNTY;4U
Adder
34.087
274675JOLIET 29;7U
Adder
37.414
274675JOLIET 29;7U
Adder
36.078
274731ELWOOD EC;2P
Adder
20.037
274733ELWOOD EC;3P
Adder
20.037
274735ELWOOD EC;4P
Adder
20.037
274728ELWOOD EC;5P
Adder
20.037
274746AC1-111 G10
Adder
6.792
274744AC1-111 GEN8
Adder
6.792
25196408WSDLE3
Adder
10.661
25196308WSDLE2
Adder
10.568
25196208WSDLE1
Adder
10.541
25196708WSDLE6
Adder
10.515
25196508WSDLE4
Adder
10.25
274823ROCKFORD ;21
Adder
23.331
254304AE2-114 C
Solar/Wind Helper
0.213
241982AE2-343 S C
Solar/Wind Helper
0.217
241997AF1-093 GEN
Solar/Wind Helper
0.248
23750501ELLIOTTS
Solar/Wind Helper
0.613
20092526R32
Solar/Wind Helper
1.102
203961AE2-224 GEN
Solar/Wind Helper
2.286
20091526CHSTN_FL
Solar/Wind Helper
0.552
20090526Q36
Solar/Wind Helper
0.989
203993AD2-133_GEN1
Solar/Wind Helper
0.989
203846AF2-130 C
Solar/Wind Helper
0.426
238126S14_GEN_1
Solar/Wind Helper
0.644
941231AE2-117 GEN
Solar/Wind Helper
0.449
203855AF2-088 C
Solar/Wind Helper
0.145
203804AE2-113_GEN
Solar/Wind Helper
1.643
270119AB2-067 GEN1
50/50
18.415
270120AB2-067 GEN2
50/50
18.415
270160DARBY CT5
50/50
0.738
270161DARBY CT6
50/50
0.728
270466AD2-091
50/50
8.21
270471AD2-092_GEN
Solar/Wind Harmer
6.312
946101AF1-275 GEN
Solar/Wind Harmer
2.373
942861AE2-305 GEN
Solar/Wind Harmer
11.65
270224U2-072_GEN2
Solar/Wind Harmer
2.896
270227U2-072_GEN3
Solar/Wind Harmer
2.896
270228U2-072_GEN4
Solar/Wind Harmer
2.896
270231U2-072_GEN5
Solar/Wind Harmer
2.896
970077AG2-063 GEN
Solar/Wind Harmer
7.841
270518AE2-148 GEN
Solar/Wind Harmer
17.081
964601AG1-323 GEN
Solar/Wind Harmer
4.458
964601AG1-323 GEN
Solar/Wind Harmer
2.073
938701AE1-092 GEN
Solar/Wind Harmer
28.718
253378AE2-206_GEN
Solar/Wind Harmer
4.802
276820AF1-078_GEN
Solar/Wind Harmer
2.133
25326509SID D
Adder
1.721
25326109MON D
Adder
1.706
25322209TAIT E
Adder
12.514
25322209TAIT E
Adder
12.233
970611AG2-400 GEN
Solar/Wind Harmer
12.784
253370AE2-315 SEC1
Adder
2.557
944541AF1-119 GEN
Solar/Wind Harmer
5.341
960971AF2-388 GEN
Solar/Wind Harmer
13.939
970321AG2-212 GEN
Solar/Wind Harmer
22.72
942221AE2-234 GEN
Solar/Wind Harmer
0.925
246938BC-WTG3
Solar/Wind Harmer
4.992
246937BC-WTG2
Solar/Wind Harmer
4.907
253394AE2-221_GEN
Solar/Wind Harmer
5.683
253398AE2-221_GEN2
Solar/Wind Harmer
5.683
270599AE1-208 GEN
Solar/Wind Harmer
10.191
270031AE2-169
Solar/Wind Harmer
10.191
270201AC2-176 GEN
Solar/Wind Harmer
6.424
964611AG1-324 GEN
Solar/Wind Harmer
1.472
964611AG1-324 GEN
Solar/Wind Harmer
0.653
247621Y3-024
Adder
0.301
970883AG2-550 GEN
Solar/Wind Harmer
12.452
970885AG2-551 GEN
Solar/Wind Harmer
2.896
970825AG2-519 GEN
Solar/Wind Harmer
13.114
960441AF2-335 GEN
Solar/Wind Harmer
12.423
270383AD1-128 GEN
Solar/Wind Harmer
7.569
24379505HDWTR1G C
Solar/Wind Harmer
9.793
270209AC1-174_GEN
Solar/Wind Harmer
6.911
926881AC1-175 GEN
Solar/Wind Harmer
6.911
965681AG1-436 GEN
Solar/Wind Harmer
15.464
965791AG1-447 GEN
Solar/Wind Harmer
7.912
270216AD2-079_GEN
Solar/Wind Harmer
0.748
253317AC1-085 GEN4
Solar/Wind Harmer
10.337
247620Y3-023
Adder
0.568
274770LINCOLN ;1U
Adder
10.399
274771LINCOLN ;2U
Adder
10.399
274808UNIV PK N;4U
Adder
6.107
972259AH1-714 GEN
Adder
23.335
274803UNIV PARK;6U
Adder
7.13
24728805RICHG1
Adder
4.62
24728905RICHG2
Adder
4.62
274674JOLIET 9 ;6U
Adder
18.77
274696ROCKY RD ;4P
Adder
13.793
274695ROCKY RD ;2P
Adder
13.475
274693ROCKY RD ;1P
Adder
13.342
274697ROCKY RD ;3P
Adder
3.661
274683WAUKEGAN ;8U
Adder
25.476
274683WAUKEGAN ;8U
Adder
21.475
25194408D.CRK1
Adder
9.122
25194508D.CRK3
Adder
1.705
23652301WDPWR_K20
Solar/Wind Helper
0.137
241967AE2-285_GEN
Solar/Wind Helper
0.621
241801AE1-079 GEN
Solar/Wind Helper
0.242
241985AE1-237 GEN
Solar/Wind Helper
0.242
962101AG1-054 GEN
Solar/Wind Helper
0.632
946071AF1-272 GEN
Solar/Wind Helper
2.575
23585401KL_K28_T16
Solar/Wind Helper
1.173
203955AF1-039 C O1
Solar/Wind Helper
0.348
944781AF1-143 GEN
Solar/Wind Helper
2.322
20083426SW_E13_K22
Solar/Wind Helper
0.053
20084626FORWARD
Solar/Wind Helper
0.337
20088926STNY CRK
Solar/Wind Helper
0.773
203940AF1-140 C
Solar/Wind Helper
0.375
20088626ARWF_N39
Solar/Wind Helper
1.151
20303426NA_O38_P22
Solar/Wind Helper
0.944
946381AF1-302 GEN
Solar/Wind Helper
0.21
203853AF1-134 C O1
Solar/Wind Helper
0.453
238120AE2-309 GEN
Solar/Wind Helper
0.403
203952AE2-129 C
Solar/Wind Helper
0.449
203946AE2-131 C
Solar/Wind Helper
0.45
238217AF1-153 C O1
Solar/Wind Helper
0.224
20398826ARMNA MT
Solar/Wind Helper
1.411
NYPJM->LTFIMP_NY
CLTF
5.354
LGEELTFEXP_LGEE->PJM
CLTF
7.711
WECLTFEXP_WEC->PJM
CLTF
4.569
AG2-052LTFEXP_AG2-052->PJM
LTF
0.284
AH1-155LTFEXP_AH1-155->PJM
LTF
0.426
CPLELTFEXP_CPLE->PJM
CLTF
2.716
CBM West 2LTFEXP_CBM-W2->PJM
CBM
134.362
LAGNLTFEXP_LAGN->PJM
CLTF
17.971
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.828
TVALTFEXP_TVA->PJM
CLTF
8.763
CBM West 1LTFEXP_CBM-W1->PJM
CBM
156.498
CBM South 1LTFEXP_CBM-S1->PJM
CBM
34.576
MECLTFEXP_MEC->PJM
CLTF
18.96
SIGELTFEXP_SIGE->PJM
CLTF
0.586

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o AP_P2-3_MP-500-021_SRT-SL


Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-3_MP-500-021_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.39 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4986.37
MW Contribution:26.18
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
18.405
270159DARBY CT4
50/50
13.513
962761AG1-125 GEN
Solar/Wind Harmer
60.041
970149AG2-104 GEN
Solar/Wind Harmer
74.151
970155AG2-107 GEN
Solar/Wind Harmer
26.181
270349AD2-093_GEN
Solar/Wind Harmer
6.297
270223U2-072_GEN1
Solar/Wind Harmer
2.888
270578AF1-285 GEN2
Solar/Wind Harmer
1.766
270391AF1-285 GEN3
Solar/Wind Harmer
1.766
970593AG2-378 GEN
Solar/Wind Harmer
2.895
270462AD2-086
Solar/Wind Harmer
9.812
253343AC1-166 GEN
Solar/Wind Harmer
1.51
253325AC1-069 GEN
Solar/Wind Harmer
1.456
25326309TAIT D
Adder
1.402
960071AF2-298 GEN
Solar/Wind Harmer
6.362
965011AG1-365 GEN
Solar/Wind Harmer
12.746
253370AE2-315 SEC1
Adder
2.549
253371AE2-315 SEC2
Adder
2.411
965651AG1-433 GEN
Solar/Wind Harmer
6.949
970245AG2-165 GEN
Solar/Wind Harmer
22.653
958861AF2-177 GEN
Solar/Wind Harmer
13.854
971995AH1-542 GEN
Solar/Wind Harmer
13.936
945371AF1-202 GEN
Solar/Wind Harmer
8.791
247521TR3_G114
Solar/Wind Harmer
4.221
270246TR4_N_V150
Solar/Wind Harmer
1.068
24721705FLATG2
Adder
25.406
965421AG1-410 GEN
Solar/Wind Harmer
37.577
246936BC-WTG1
Solar/Wind Harmer
4.892
270489AE1-102 GEN1
Solar/Wind Harmer
1.625
247536S-71 GEN
Solar/Wind Harmer
5.033
270005AE1-210 C O1
Solar/Wind Harmer
6.789
965031AG1-367 GEN
Solar/Wind Harmer
12.422
270063AE2-323 C
Solar/Wind Harmer
2.733
24695305TIMB G C
Solar/Wind Harmer
6.822
970825AG2-519 GEN
Solar/Wind Harmer
2.917
270263AC1-001 GEN
Solar/Wind Harmer
1.296
270032AE2-172
Solar/Wind Harmer
5.75
970291AG2-192 GEN
Solar/Wind Harmer
1.606
942081AE2-220 GEN
Solar/Wind Harmer
7.893
270239V3-007_GEN1
Solar/Wind Harmer
2.124
24639705ELKHART HY
Adder
0.189
274773LINCOLN ;4U
Adder
10.368
274774LINCOLN ;5U
Adder
10.368
274723RIVER EC ;12
Adder
21.923
274751CRETE EC ;1U
Adder
10.077
274754CRETE EC ;4U
Adder
10.077
274812UNIV PK N;8U
Adder
6.115
274801UNIV PARK;4U
Adder
7.107
274676JOLIET 29;8U
Adder
37.301
274674JOLIET 9 ;6U
Adder
18.713
274732ELWOOD EC;7P
Adder
19.977
274745AC1-111 GEN9
Adder
6.771
274682WAUKEGAN ;7U
Adder
21.671
274828WAUKEGAN ;BP
Adder
13.314
25194608D.CRK4
Adder
1.976
24728605AND G2
Adder
4.58
274822ROCKFORD ;11
Adder
23.43
972235AH1-702 GEN1
Adder
3.007
25196808ZIMRHP
Adder
58.404
254303AC2-168 GEN
Solar/Wind Helper
0.155
237046AF1-021 C
Solar/Wind Helper
0.464
241966AE1-183 GEN
Solar/Wind Helper
0.248
238185AF2-356 C
Solar/Wind Helper
2.029
20089226LOOKOUT
Solar/Wind Helper
0.543
20088826HIGHLAND
Solar/Wind Helper
0.848
20094526CT_V3-030
Solar/Wind Helper
0.447
235054AD2-180 GEN
Solar/Wind Helper
1.569
964201AG1-281 GEN
Solar/Wind Helper
0.457
238117U2-030
Solar/Wind Helper
0.269
235531U2-073 GEN
Solar/Wind Helper
2.549
964391AG1-301 GEN
Solar/Wind Helper
0.447
203954AE2-126 C
Solar/Wind Helper
0.444
23751201ROTHROCK
Solar/Wind Helper
0.653
238206AE2-263_GEN
Solar/Wind Helper
0.859
253432AC1-085 GEN2
Solar/Wind Harmer
0.296
270051AF1-062 GEN
50/50
17.095
270475AD2-096_GEN
50/50
10.077
970153AG2-106 GEN
Solar/Wind Harmer
26.181
961921AG1-034 GEN
Solar/Wind Harmer
20.368
241955AC1-078 GEN
Solar/Wind Harmer
11.182
241974AD2-163_GEN2
Solar/Wind Harmer
2.972
942051AE2-217 GEN
Solar/Wind Harmer
26.62
942871AE2-306 GEN
Solar/Wind Harmer
1.325
270391AF1-285 GEN3
Solar/Wind Harmer
0.679
970605AG2-385 GEN
Solar/Wind Harmer
7.818
270485AE1-090_GEN
Solar/Wind Harmer
0.853
253338AC1-165 GEN
Solar/Wind Harmer
1.51
253333AC1-068 GEN
Solar/Wind Harmer
1.456
960801AF2-371 GEN
Solar/Wind Harmer
3.397
964871AG1-351 GEN
Solar/Wind Harmer
2.345
270273AD2-016 GEN
Solar/Wind Harmer
3.452
944531AF1-118 GEN
Solar/Wind Harmer
45.079
972173AH1-669 GEN
Solar/Wind Harmer
6.423
270043AE2-236 GEN
Solar/Wind Harmer
7.027
959331AF2-224 GEN
Solar/Wind Harmer
12.746
965021AG1-366 GEN
Solar/Wind Harmer
2.964
253303V4-073 C
Solar/Wind Harmer
0.147
253370AE2-315 SEC1
Adder
2.549
253371AE2-315 SEC2
Adder
2.411
970513AG2-328 GEN
Solar/Wind Harmer
22.653
970517AG2-330 GEN
Solar/Wind Harmer
20.546
253415AE1-040 GEN
Solar/Wind Harmer
1.427
970349AG2-230 GEN
Solar/Wind Harmer
18.878
270191TR4_S_V150
Solar/Wind Harmer
3.765
270247TR4_N_V136
Solar/Wind Harmer
1.068
24721905FLATG4
Adder
25.406
971617AH1-308 GEN
Solar/Wind Harmer
7.273
270491AE1-102 GEN2
Solar/Wind Harmer
1.625
962031AG1-047 GEN
Solar/Wind Harmer
3.765
957741AF2-068 GEN
Solar/Wind Harmer
18.686
970031AG2-029 GEN
Solar/Wind Harmer
37.277
958821AF2-173 GEN
Solar/Wind Harmer
17.391
270004AE1-209 GEN
Solar/Wind Harmer
6.789
946031AF1-268 GEN
Solar/Wind Harmer
10.298
253406AD2-031_GEN
Solar/Wind Harmer
1.585
970289AG2-191 GEN
Solar/Wind Harmer
0.948
970291AG2-192 GEN
Solar/Wind Harmer
0.862
247642Z2-115 C
Solar/Wind Harmer
0.079
270437AC2-090 C
Solar/Wind Harmer
6.893
247643Z2-116 C
Solar/Wind Harmer
0.086
274772LINCOLN ;3U
Adder
10.368
274724RIVER EC ;11
Adder
21.668
274752CRETE EC ;2U
Adder
10.077
274753CRETE EC ;3U
Adder
10.077
24642205MAYFLWER
Adder
0.777
274802UNIV PARK;5U
Adder
7.109
270156DARBY CT1
50/50
13.732
270157DARBY CT2
50/50
13.698
270158DARBY CT3
50/50
13.479
270036AE2-216 BAT
50/50
9.005
962771AG1-126 GEN
Solar/Wind Harmer
60.041
270284AF1-227 GEN1
Solar/Wind Harmer
9.212
270286AF1-227 GEN2
Solar/Wind Harmer
3.408
270287AF1-227 GEN3
Solar/Wind Harmer
3.408
270459AD2-067 GEN
Solar/Wind Harmer
13.375
961821AG1-024 GEN
Solar/Wind Harmer
13.579
270520AE2-214 GEN
Solar/Wind Harmer
9.481
270054AF2-122 C O1
Solar/Wind Harmer
5.069
253383AE2-342_GEN
Solar/Wind Harmer
1.364
241973AD2-163_GEN1
Solar/Wind Harmer
2.972
943861AF1-054 GEN
Solar/Wind Harmer
5.734
943851AF1-053 GEN
Solar/Wind Harmer
2.771
270578AF1-285 GEN2
Solar/Wind Harmer
0.679
945631AF1-228 GEN
Solar/Wind Harmer
6.795
270302AB2-170 GEN
Solar/Wind Harmer
11.795
270317AD1-130_GEN
Solar/Wind Harmer
4.522
241972AD1-140 GEN
Solar/Wind Harmer
6.067
970689AG2-444 GEN
Solar/Wind Harmer
21.887
270432AC2-029 GEN
Solar/Wind Harmer
9.37
270269AC2-059
Solar/Wind Harmer
12.072
24729505KEY G4
Adder
8.327
270071AF1-092 GEN
Solar/Wind Harmer
19.189
253372AE2-315 SEC3
Adder
2.411
253372AE2-315 SEC3
Adder
2.411
958711AF2-162 GEN
Solar/Wind Harmer
1.286
965101AG1-375 GEN
Solar/Wind Harmer
12.675
25306009OHH W.
Adder
3.652
253349AC2-067 GEN
Solar/Wind Harmer
6.31
253400AC2-068 GEN
Solar/Wind Harmer
2.537
945581AF1-223 GEN
Solar/Wind Harmer
5.714
963791AG1-232 GEN
Solar/Wind Harmer
16.994
971347AH1-153 GEN
Solar/Wind Harmer
18.878
965051AG1-369 GEN
Solar/Wind Harmer
6.268
965041AG1-368 GEN
Solar/Wind Harmer
12.515
270024AE2-089 GEN
Solar/Wind Harmer
5.871
957201AF2-014 GEN
Solar/Wind Harmer
5.67
270435AC2-044 GEN
Solar/Wind Harmer
2.5
270340AC2-060 GEN
Solar/Wind Harmer
3.789
961761AG1-017 GEN
Solar/Wind Harmer
0.533
270543AE2-219 C
Solar/Wind Harmer
6.356
971029AG2-637 GEN
Solar/Wind Harmer
18.589
971673AH1-337 GEN
Solar/Wind Harmer
5.698
970115AG2-085 GEN
Solar/Wind Harmer
4.954
270594AE1-207 GEN
Solar/Wind Harmer
18.171
965461AG1-414 GEN
Solar/Wind Harmer
2.801
970289AG2-191 GEN
Solar/Wind Harmer
2.347
270240V3-007_GEN2
Solar/Wind Harmer
7.638
960681AF2-359 GEN
Solar/Wind Harmer
4.66
971771AH1-392 GEN
Solar/Wind Harmer
11.073
274775LINCOLN ;6U
Adder
10.368
274776LINCOLN ;7U
Adder
10.368
274777LINCOLN ;8U
Adder
10.368
274814UNIV PK N;0U
Adder
6.169
274807UNIV PK N;3U
Adder
6.155
274805UNIV PK N;1U
Adder
6.128
274811UNIV PK N;7U
Adder
6.115
972227AH1-698 GEN1
Adder
3.18
972037AH1-567 GEN1
Adder
0.223
274827FISK ;RP
Adder
9.459
274687WILL CNTY;4U
Adder
33.985
274687WILL CNTY;4U
Adder
33.985
274675JOLIET 29;7U
Adder
37.302
274675JOLIET 29;7U
Adder
35.969
274731ELWOOD EC;2P
Adder
19.977
274733ELWOOD EC;3P
Adder
19.977
274735ELWOOD EC;4P
Adder
19.977
274728ELWOOD EC;5P
Adder
19.977
274746AC1-111 G10
Adder
6.771
274744AC1-111 GEN8
Adder
6.771
25196408WSDLE3
Adder
10.624
25196308WSDLE2
Adder
10.532
25196208WSDLE1
Adder
10.505
25196708WSDLE6
Adder
10.479
25196508WSDLE4
Adder
10.215
274823ROCKFORD ;21
Adder
23.26
254304AE2-114 C
Solar/Wind Helper
0.213
241982AE2-343 S C
Solar/Wind Helper
0.217
241997AF1-093 GEN
Solar/Wind Helper
0.248
23750501ELLIOTTS
Solar/Wind Helper
0.611
20092526R32
Solar/Wind Helper
1.1
203961AE2-224 GEN
Solar/Wind Helper
2.28
20091526CHSTN_FL
Solar/Wind Helper
0.551
20090526Q36
Solar/Wind Helper
0.986
203993AD2-133_GEN1
Solar/Wind Helper
0.986
203846AF2-130 C
Solar/Wind Helper
0.426
238126S14_GEN_1
Solar/Wind Helper
0.641
941231AE2-117 GEN
Solar/Wind Helper
0.447
203855AF2-088 C
Solar/Wind Helper
0.145
203804AE2-113_GEN
Solar/Wind Helper
1.64
972228AH1-698 GEN2
Adder
4.517
274826FISK ;BP
Adder
13.347
274800UNIV PARK;3U
Adder
7.107
972038AH1-567 GEN2
Adder
0.445
274676JOLIET 29;8U
Adder
35.969
274729ELWOOD EC;1P
Adder
19.977
274730ELWOOD EC;6P
Adder
19.977
274734ELWOOD EC;8P
Adder
19.977
274736ELWOOD EC;9P
Adder
19.977
274682WAUKEGAN ;7U
Adder
21.671
25196608WSDLE5
Adder
10.321
25194608D.CRK4
Adder
1.976
24728705AND G3
Adder
9.578
24728505AND G1
Adder
4.58
972236AH1-702 GEN2
Adder
2.615
235058AG1-386 C
Solar/Wind Helper
0.453
237048AF1-022 C
Solar/Wind Helper
0.176
254305AE2-115 C
Solar/Wind Helper
0.213
237043AE2-125 C
Solar/Wind Helper
0.172
964991AG1-363 GEN
Solar/Wind Helper
3.583
202652Y1-033 WT C
Solar/Wind Helper
0.526
20089126CSLMN_L13
Solar/Wind Helper
0.558
20089026BF_G21_K23
Solar/Wind Helper
0.442
23750701CROSSCHOOL
Solar/Wind Helper
1.124
203818AF1-086 GEN
Solar/Wind Helper
1.596
238118U2-030_1
Solar/Wind Helper
0.269
238127S14_GEN_2
Solar/Wind Helper
0.641
203854AF2-039 C
Solar/Wind Helper
0.3
20334926Z1-069 C
Solar/Wind Helper
1.269
238202AE2-262_GEN
Solar/Wind Helper
0.903
253316AC1-085 GEN3
Solar/Wind Harmer
9.261
253433AC1-085 GEN1
Solar/Wind Harmer
5.879
270119AB2-067 GEN1
50/50
18.405
270120AB2-067 GEN2
50/50
18.405
270160DARBY CT5
50/50
0.736
270161DARBY CT6
50/50
0.726
270466AD2-091
50/50
8.187
270471AD2-092_GEN
Solar/Wind Harmer
6.297
946101AF1-275 GEN
Solar/Wind Harmer
2.366
942861AE2-305 GEN
Solar/Wind Harmer
11.617
270224U2-072_GEN2
Solar/Wind Harmer
2.888
270227U2-072_GEN3
Solar/Wind Harmer
2.888
270228U2-072_GEN4
Solar/Wind Harmer
2.888
270231U2-072_GEN5
Solar/Wind Harmer
2.888
970077AG2-063 GEN
Solar/Wind Harmer
7.818
270518AE2-148 GEN
Solar/Wind Harmer
17.027
964601AG1-323 GEN
Solar/Wind Harmer
4.444
964601AG1-323 GEN
Solar/Wind Harmer
2.067
938701AE1-092 GEN
Solar/Wind Harmer
28.63
253378AE2-206_GEN
Solar/Wind Harmer
4.787
276820AF1-078_GEN
Solar/Wind Harmer
2.127
25326509SID D
Adder
1.715
25326109MON D
Adder
1.7
25322209TAIT E
Adder
12.473
25322209TAIT E
Adder
12.193
970611AG2-400 GEN
Solar/Wind Harmer
12.746
253370AE2-315 SEC1
Adder
2.549
944541AF1-119 GEN
Solar/Wind Harmer
5.325
960971AF2-388 GEN
Solar/Wind Harmer
13.897
970321AG2-212 GEN
Solar/Wind Harmer
22.653
942221AE2-234 GEN
Solar/Wind Harmer
0.922
246938BC-WTG3
Solar/Wind Harmer
4.977
246937BC-WTG2
Solar/Wind Harmer
4.892
253394AE2-221_GEN
Solar/Wind Harmer
5.664
253398AE2-221_GEN2
Solar/Wind Harmer
5.664
270599AE1-208 GEN
Solar/Wind Harmer
10.159
270031AE2-169
Solar/Wind Harmer
10.159
270201AC2-176 GEN
Solar/Wind Harmer
6.404
964611AG1-324 GEN
Solar/Wind Harmer
1.468
964611AG1-324 GEN
Solar/Wind Harmer
0.651
247621Y3-024
Adder
0.3
970883AG2-550 GEN
Solar/Wind Harmer
12.413
970885AG2-551 GEN
Solar/Wind Harmer
2.887
970825AG2-519 GEN
Solar/Wind Harmer
13.073
960441AF2-335 GEN
Solar/Wind Harmer
12.384
270383AD1-128 GEN
Solar/Wind Harmer
7.545
24379505HDWTR1G C
Solar/Wind Harmer
9.762
270209AC1-174_GEN
Solar/Wind Harmer
6.889
926881AC1-175 GEN
Solar/Wind Harmer
6.889
965681AG1-436 GEN
Solar/Wind Harmer
15.418
965791AG1-447 GEN
Solar/Wind Harmer
7.888
270216AD2-079_GEN
Solar/Wind Harmer
0.746
247620Y3-023
Adder
0.566
274770LINCOLN ;1U
Adder
10.368
274771LINCOLN ;2U
Adder
10.368
274808UNIV PK N;4U
Adder
6.088
972259AH1-714 GEN
Adder
23.265
274803UNIV PARK;6U
Adder
7.109
24728805RICHG1
Adder
4.605
24728905RICHG2
Adder
4.605
274674JOLIET 9 ;6U
Adder
18.713
274696ROCKY RD ;4P
Adder
13.751
274695ROCKY RD ;2P
Adder
13.434
274693ROCKY RD ;1P
Adder
13.302
274697ROCKY RD ;3P
Adder
3.649
274683WAUKEGAN ;8U
Adder
25.399
274683WAUKEGAN ;8U
Adder
21.41
25194408D.CRK1
Adder
9.091
25194508D.CRK3
Adder
1.7
23652301WDPWR_K20
Solar/Wind Helper
0.137
241967AE2-285_GEN
Solar/Wind Helper
0.621
241801AE1-079 GEN
Solar/Wind Helper
0.242
241985AE1-237 GEN
Solar/Wind Helper
0.242
962101AG1-054 GEN
Solar/Wind Helper
0.632
946071AF1-272 GEN
Solar/Wind Helper
2.569
23585401KL_K28_T16
Solar/Wind Helper
1.169
203955AF1-039 C O1
Solar/Wind Helper
0.347
944781AF1-143 GEN
Solar/Wind Helper
2.315
20083426SW_E13_K22
Solar/Wind Helper
0.053
20084626FORWARD
Solar/Wind Helper
0.336
20088926STNY CRK
Solar/Wind Helper
0.771
203940AF1-140 C
Solar/Wind Helper
0.374
20088626ARWF_N39
Solar/Wind Helper
1.148
20303426NA_O38_P22
Solar/Wind Helper
0.941
946381AF1-302 GEN
Solar/Wind Helper
0.21
203853AF1-134 C O1
Solar/Wind Helper
0.452
203952AE2-129 C
Solar/Wind Helper
0.448
203946AE2-131 C
Solar/Wind Helper
0.449
238120AE2-309 GEN
Solar/Wind Helper
0.401
238217AF1-153 C O1
Solar/Wind Helper
0.223
20398826ARMNA MT
Solar/Wind Helper
1.408
253317AC1-085 GEN4
Solar/Wind Harmer
9.261
NYPJM->LTFIMP_NY
CLTF
5.339
LGEELTFEXP_LGEE->PJM
CLTF
7.685
WECLTFEXP_WEC->PJM
CLTF
4.556
AG2-052LTFEXP_AG2-052->PJM
LTF
0.283
AH1-155LTFEXP_AH1-155->PJM
LTF
0.425
CPLELTFEXP_CPLE->PJM
CLTF
2.708
CBM West 2LTFEXP_CBM-W2->PJM
CBM
133.928
LAGNLTFEXP_LAGN->PJM
CLTF
17.912
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.787
TVALTFEXP_TVA->PJM
CLTF
8.734
CBM West 1LTFEXP_CBM-W1->PJM
CBM
155.982
CBM South 1LTFEXP_CBM-S1->PJM
CBM
34.46
MECLTFEXP_MEC->PJM
CLTF
18.901
SIGELTFEXP_SIGE->PJM
CLTF
0.584

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o AEP_P4_#37_05MOUNTN 765_B1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.3 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4982.82
MW Contribution:26.16
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
18.401
270159DARBY CT4
50/50
13.494
962761AG1-125 GEN
Solar/Wind Harmer
59.984
970149AG2-104 GEN
Solar/Wind Harmer
74.081
970155AG2-107 GEN
Solar/Wind Harmer
26.156
270349AD2-093_GEN
Solar/Wind Harmer
6.29
270223U2-072_GEN1
Solar/Wind Harmer
2.884
270578AF1-285 GEN2
Solar/Wind Harmer
1.764
270391AF1-285 GEN3
Solar/Wind Harmer
1.764
970593AG2-378 GEN
Solar/Wind Harmer
2.892
270462AD2-086
Solar/Wind Harmer
9.8
253343AC1-166 GEN
Solar/Wind Harmer
1.508
253325AC1-069 GEN
Solar/Wind Harmer
1.454
25326309TAIT D
Adder
1.4
960071AF2-298 GEN
Solar/Wind Harmer
6.353
965011AG1-365 GEN
Solar/Wind Harmer
12.73
253370AE2-315 SEC1
Adder
2.545
253371AE2-315 SEC2
Adder
2.407
965651AG1-433 GEN
Solar/Wind Harmer
6.939
970245AG2-165 GEN
Solar/Wind Harmer
22.623
958861AF2-177 GEN
Solar/Wind Harmer
13.835
971995AH1-542 GEN
Solar/Wind Harmer
13.916
945371AF1-202 GEN
Solar/Wind Harmer
8.779
247521TR3_G114
Solar/Wind Harmer
4.215
270246TR4_N_V150
Solar/Wind Harmer
1.066
24721705FLATG2
Adder
25.369
965421AG1-410 GEN
Solar/Wind Harmer
37.527
246936BC-WTG1
Solar/Wind Harmer
4.886
270489AE1-102 GEN1
Solar/Wind Harmer
1.623
247536S-71 GEN
Solar/Wind Harmer
5.026
270005AE1-210 C O1
Solar/Wind Harmer
6.779
965031AG1-367 GEN
Solar/Wind Harmer
12.405
270063AE2-323 C
Solar/Wind Harmer
2.73
24695305TIMB G C
Solar/Wind Harmer
6.813
970825AG2-519 GEN
Solar/Wind Harmer
2.913
270263AC1-001 GEN
Solar/Wind Harmer
1.294
270032AE2-172
Solar/Wind Harmer
5.743
970291AG2-192 GEN
Solar/Wind Harmer
1.604
942081AE2-220 GEN
Solar/Wind Harmer
7.882
270239V3-007_GEN1
Solar/Wind Harmer
2.121
24639705ELKHART HY
Adder
0.188
274773LINCOLN ;4U
Adder
10.354
274774LINCOLN ;5U
Adder
10.354
274723RIVER EC ;12
Adder
21.894
274751CRETE EC ;1U
Adder
10.063
274754CRETE EC ;4U
Adder
10.063
274812UNIV PK N;8U
Adder
6.107
274801UNIV PARK;4U
Adder
7.097
274676JOLIET 29;8U
Adder
37.252
274674JOLIET 9 ;6U
Adder
18.689
274732ELWOOD EC;7P
Adder
19.951
274745AC1-111 GEN9
Adder
6.762
274682WAUKEGAN ;7U
Adder
21.642
274828WAUKEGAN ;BP
Adder
13.296
25194608D.CRK4
Adder
1.973
24728605AND G2
Adder
4.573
274822ROCKFORD ;11
Adder
23.399
972235AH1-702 GEN1
Adder
3.003
25196808ZIMRHP
Adder
58.315
254303AC2-168 GEN
Solar/Wind Helper
0.155
237046AF1-021 C
Solar/Wind Helper
0.463
241966AE1-183 GEN
Solar/Wind Helper
0.248
238185AF2-356 C
Solar/Wind Helper
2.025
20089226LOOKOUT
Solar/Wind Helper
0.542
20088826HIGHLAND
Solar/Wind Helper
0.847
20094526CT_V3-030
Solar/Wind Helper
0.446
235054AD2-180 GEN
Solar/Wind Helper
1.566
964201AG1-281 GEN
Solar/Wind Helper
0.457
238117U2-030
Solar/Wind Helper
0.269
235531U2-073 GEN
Solar/Wind Helper
2.545
964391AG1-301 GEN
Solar/Wind Helper
0.446
203954AE2-126 C
Solar/Wind Helper
0.443
23751201ROTHROCK
Solar/Wind Helper
0.652
238206AE2-263_GEN
Solar/Wind Helper
0.858
253432AC1-085 GEN2
Solar/Wind Harmer
0.296
270156DARBY CT1
50/50
13.713
270157DARBY CT2
50/50
13.679
270158DARBY CT3
50/50
13.461
270036AE2-216 BAT
50/50
8.994
962771AG1-126 GEN
Solar/Wind Harmer
59.984
270284AF1-227 GEN1
Solar/Wind Harmer
9.201
270286AF1-227 GEN2
Solar/Wind Harmer
3.404
270287AF1-227 GEN3
Solar/Wind Harmer
3.404
270459AD2-067 GEN
Solar/Wind Harmer
13.358
961821AG1-024 GEN
Solar/Wind Harmer
13.561
270520AE2-214 GEN
Solar/Wind Harmer
9.469
270054AF2-122 C O1
Solar/Wind Harmer
5.062
253383AE2-342_GEN
Solar/Wind Harmer
1.362
241973AD2-163_GEN1
Solar/Wind Harmer
2.968
943861AF1-054 GEN
Solar/Wind Harmer
5.727
943851AF1-053 GEN
Solar/Wind Harmer
2.767
270578AF1-285 GEN2
Solar/Wind Harmer
0.678
945631AF1-228 GEN
Solar/Wind Harmer
6.786
270302AB2-170 GEN
Solar/Wind Harmer
11.78
270317AD1-130_GEN
Solar/Wind Harmer
4.516
241972AD1-140 GEN
Solar/Wind Harmer
6.058
970689AG2-444 GEN
Solar/Wind Harmer
21.853
270432AC2-029 GEN
Solar/Wind Harmer
9.355
270269AC2-059
Solar/Wind Harmer
12.053
24729505KEY G4
Adder
8.316
270071AF1-092 GEN
Solar/Wind Harmer
19.164
253372AE2-315 SEC3
Adder
2.407
253372AE2-315 SEC3
Adder
2.407
958711AF2-162 GEN
Solar/Wind Harmer
1.285
965101AG1-375 GEN
Solar/Wind Harmer
12.658
25306009OHH W.
Adder
3.647
253349AC2-067 GEN
Solar/Wind Harmer
6.301
253400AC2-068 GEN
Solar/Wind Harmer
2.534
945581AF1-223 GEN
Solar/Wind Harmer
5.707
963791AG1-232 GEN
Solar/Wind Harmer
16.971
971347AH1-153 GEN
Solar/Wind Harmer
18.853
965051AG1-369 GEN
Solar/Wind Harmer
6.259
965041AG1-368 GEN
Solar/Wind Harmer
12.498
270024AE2-089 GEN
Solar/Wind Harmer
5.863
957201AF2-014 GEN
Solar/Wind Harmer
5.663
270435AC2-044 GEN
Solar/Wind Harmer
2.497
270340AC2-060 GEN
Solar/Wind Harmer
3.783
961761AG1-017 GEN
Solar/Wind Harmer
0.532
270543AE2-219 C
Solar/Wind Harmer
6.347
971029AG2-637 GEN
Solar/Wind Harmer
18.562
971673AH1-337 GEN
Solar/Wind Harmer
5.69
970115AG2-085 GEN
Solar/Wind Harmer
4.947
270594AE1-207 GEN
Solar/Wind Harmer
18.147
965461AG1-414 GEN
Solar/Wind Harmer
2.797
970289AG2-191 GEN
Solar/Wind Harmer
2.344
270240V3-007_GEN2
Solar/Wind Harmer
7.627
960681AF2-359 GEN
Solar/Wind Harmer
4.654
971771AH1-392 GEN
Solar/Wind Harmer
11.059
274775LINCOLN ;6U
Adder
10.354
274776LINCOLN ;7U
Adder
10.354
274777LINCOLN ;8U
Adder
10.354
274814UNIV PK N;0U
Adder
6.16
274807UNIV PK N;3U
Adder
6.147
274805UNIV PK N;1U
Adder
6.12
274811UNIV PK N;7U
Adder
6.107
972227AH1-698 GEN1
Adder
3.176
972037AH1-567 GEN1
Adder
0.223
274827FISK ;RP
Adder
9.447
274687WILL CNTY;4U
Adder
33.939
274687WILL CNTY;4U
Adder
33.939
274675JOLIET 29;7U
Adder
37.252
274675JOLIET 29;7U
Adder
35.922
274731ELWOOD EC;2P
Adder
19.951
274733ELWOOD EC;3P
Adder
19.951
274735ELWOOD EC;4P
Adder
19.951
274728ELWOOD EC;5P
Adder
19.951
274746AC1-111 G10
Adder
6.762
274744AC1-111 GEN8
Adder
6.762
25196408WSDLE3
Adder
10.608
25196308WSDLE2
Adder
10.516
25196208WSDLE1
Adder
10.49
25196708WSDLE6
Adder
10.463
25196508WSDLE4
Adder
10.2
274823ROCKFORD ;21
Adder
23.229
254304AE2-114 C
Solar/Wind Helper
0.214
241982AE2-343 S C
Solar/Wind Helper
0.217
241997AF1-093 GEN
Solar/Wind Helper
0.248
23750501ELLIOTTS
Solar/Wind Helper
0.61
20092526R32
Solar/Wind Helper
1.098
203961AE2-224 GEN
Solar/Wind Helper
2.278
20091526CHSTN_FL
Solar/Wind Helper
0.55
20090526Q36
Solar/Wind Helper
0.985
203993AD2-133_GEN1
Solar/Wind Helper
0.985
203846AF2-130 C
Solar/Wind Helper
0.425
238126S14_GEN_1
Solar/Wind Helper
0.64
941231AE2-117 GEN
Solar/Wind Helper
0.447
203855AF2-088 C
Solar/Wind Helper
0.144
203804AE2-113_GEN
Solar/Wind Helper
1.639
270051AF1-062 GEN
50/50
17.076
270475AD2-096_GEN
50/50
10.066
970153AG2-106 GEN
Solar/Wind Harmer
26.156
961921AG1-034 GEN
Solar/Wind Harmer
20.342
241955AC1-078 GEN
Solar/Wind Harmer
11.167
241974AD2-163_GEN2
Solar/Wind Harmer
2.968
942051AE2-217 GEN
Solar/Wind Harmer
26.585
942871AE2-306 GEN
Solar/Wind Harmer
1.323
270391AF1-285 GEN3
Solar/Wind Harmer
0.678
970605AG2-385 GEN
Solar/Wind Harmer
7.807
270485AE1-090_GEN
Solar/Wind Harmer
0.852
253338AC1-165 GEN
Solar/Wind Harmer
1.508
253333AC1-068 GEN
Solar/Wind Harmer
1.454
960801AF2-371 GEN
Solar/Wind Harmer
3.391
964871AG1-351 GEN
Solar/Wind Harmer
2.342
270273AD2-016 GEN
Solar/Wind Harmer
3.447
944531AF1-118 GEN
Solar/Wind Harmer
45.02
972173AH1-669 GEN
Solar/Wind Harmer
6.413
270043AE2-236 GEN
Solar/Wind Harmer
7.018
959331AF2-224 GEN
Solar/Wind Harmer
12.73
965021AG1-366 GEN
Solar/Wind Harmer
2.96
253303V4-073 C
Solar/Wind Harmer
0.147
253370AE2-315 SEC1
Adder
2.545
253371AE2-315 SEC2
Adder
2.407
970513AG2-328 GEN
Solar/Wind Harmer
22.623
970517AG2-330 GEN
Solar/Wind Harmer
20.519
253415AE1-040 GEN
Solar/Wind Harmer
1.424
970349AG2-230 GEN
Solar/Wind Harmer
18.853
270191TR4_S_V150
Solar/Wind Harmer
3.76
270247TR4_N_V136
Solar/Wind Harmer
1.066
24721905FLATG4
Adder
25.369
971617AH1-308 GEN
Solar/Wind Harmer
7.263
270491AE1-102 GEN2
Solar/Wind Harmer
1.623
962031AG1-047 GEN
Solar/Wind Harmer
3.76
957741AF2-068 GEN
Solar/Wind Harmer
18.66
970031AG2-029 GEN
Solar/Wind Harmer
37.228
958821AF2-173 GEN
Solar/Wind Harmer
17.367
270004AE1-209 GEN
Solar/Wind Harmer
6.779
946031AF1-268 GEN
Solar/Wind Harmer
10.283
253406AD2-031_GEN
Solar/Wind Harmer
1.583
970289AG2-191 GEN
Solar/Wind Harmer
0.947
970291AG2-192 GEN
Solar/Wind Harmer
0.861
247642Z2-115 C
Solar/Wind Harmer
0.079
270437AC2-090 C
Solar/Wind Harmer
6.883
247643Z2-116 C
Solar/Wind Harmer
0.086
274772LINCOLN ;3U
Adder
10.354
274724RIVER EC ;11
Adder
21.639
274752CRETE EC ;2U
Adder
10.063
274753CRETE EC ;3U
Adder
10.063
24642205MAYFLWER
Adder
0.776
274802UNIV PARK;5U
Adder
7.1
972228AH1-698 GEN2
Adder
4.511
274826FISK ;BP
Adder
13.329
274800UNIV PARK;3U
Adder
7.097
972038AH1-567 GEN2
Adder
0.444
274676JOLIET 29;8U
Adder
35.922
274729ELWOOD EC;1P
Adder
19.951
274730ELWOOD EC;6P
Adder
19.951
274734ELWOOD EC;8P
Adder
19.951
274736ELWOOD EC;9P
Adder
19.951
274682WAUKEGAN ;7U
Adder
21.642
25196608WSDLE5
Adder
10.305
25194608D.CRK4
Adder
1.973
24728705AND G3
Adder
9.564
24728505AND G1
Adder
4.573
972236AH1-702 GEN2
Adder
2.611
235058AG1-386 C
Solar/Wind Helper
0.453
237048AF1-022 C
Solar/Wind Helper
0.176
254305AE2-115 C
Solar/Wind Helper
0.214
237043AE2-125 C
Solar/Wind Helper
0.172
964991AG1-363 GEN
Solar/Wind Helper
3.577
202652Y1-033 WT C
Solar/Wind Helper
0.525
20089126CSLMN_L13
Solar/Wind Helper
0.557
20089026BF_G21_K23
Solar/Wind Helper
0.441
23750701CROSSCHOOL
Solar/Wind Helper
1.122
203818AF1-086 GEN
Solar/Wind Helper
1.594
238118U2-030_1
Solar/Wind Helper
0.269
238127S14_GEN_2
Solar/Wind Helper
0.64
203854AF2-039 C
Solar/Wind Helper
0.3
20334926Z1-069 C
Solar/Wind Helper
1.268
238202AE2-262_GEN
Solar/Wind Helper
0.902
253316AC1-085 GEN3
Solar/Wind Harmer
9.247
253433AC1-085 GEN1
Solar/Wind Harmer
5.87
270119AB2-067 GEN1
50/50
18.401
270120AB2-067 GEN2
50/50
18.401
270160DARBY CT5
50/50
0.735
270161DARBY CT6
50/50
0.725
270466AD2-091
50/50
8.176
270471AD2-092_GEN
Solar/Wind Harmer
6.29
946101AF1-275 GEN
Solar/Wind Harmer
2.363
942861AE2-305 GEN
Solar/Wind Harmer
11.602
270224U2-072_GEN2
Solar/Wind Harmer
2.884
270227U2-072_GEN3
Solar/Wind Harmer
2.884
270228U2-072_GEN4
Solar/Wind Harmer
2.884
270231U2-072_GEN5
Solar/Wind Harmer
2.884
970077AG2-063 GEN
Solar/Wind Harmer
7.807
270518AE2-148 GEN
Solar/Wind Harmer
17.003
964601AG1-323 GEN
Solar/Wind Harmer
4.438
964601AG1-323 GEN
Solar/Wind Harmer
2.064
938701AE1-092 GEN
Solar/Wind Harmer
28.592
253378AE2-206_GEN
Solar/Wind Harmer
4.781
276820AF1-078_GEN
Solar/Wind Harmer
2.124
25326509SID D
Adder
1.713
25326109MON D
Adder
1.698
25322209TAIT E
Adder
12.455
25322209TAIT E
Adder
12.175
970611AG2-400 GEN
Solar/Wind Harmer
12.73
253370AE2-315 SEC1
Adder
2.545
944541AF1-119 GEN
Solar/Wind Harmer
5.318
960971AF2-388 GEN
Solar/Wind Harmer
13.879
970321AG2-212 GEN
Solar/Wind Harmer
22.623
942221AE2-234 GEN
Solar/Wind Harmer
0.921
246938BC-WTG3
Solar/Wind Harmer
4.97
246937BC-WTG2
Solar/Wind Harmer
4.886
270599AE1-208 GEN
Solar/Wind Harmer
10.145
270031AE2-169
Solar/Wind Harmer
10.145
253394AE2-221_GEN
Solar/Wind Harmer
5.655
253398AE2-221_GEN2
Solar/Wind Harmer
5.655
270201AC2-176 GEN
Solar/Wind Harmer
6.395
964611AG1-324 GEN
Solar/Wind Harmer
1.466
964611AG1-324 GEN
Solar/Wind Harmer
0.65
247621Y3-024
Adder
0.3
970883AG2-550 GEN
Solar/Wind Harmer
12.396
970885AG2-551 GEN
Solar/Wind Harmer
2.883
970825AG2-519 GEN
Solar/Wind Harmer
13.055
960441AF2-335 GEN
Solar/Wind Harmer
12.367
270383AD1-128 GEN
Solar/Wind Harmer
7.535
24379505HDWTR1G C
Solar/Wind Harmer
9.748
270209AC1-174_GEN
Solar/Wind Harmer
6.88
926881AC1-175 GEN
Solar/Wind Harmer
6.88
965681AG1-436 GEN
Solar/Wind Harmer
15.398
965791AG1-447 GEN
Solar/Wind Harmer
7.878
270216AD2-079_GEN
Solar/Wind Harmer
0.745
247620Y3-023
Adder
0.565
274770LINCOLN ;1U
Adder
10.354
274771LINCOLN ;2U
Adder
10.354
274808UNIV PK N;4U
Adder
6.08
972259AH1-714 GEN
Adder
23.234
274803UNIV PARK;6U
Adder
7.1
24728805RICHG1
Adder
4.598
24728905RICHG2
Adder
4.598
274674JOLIET 9 ;6U
Adder
18.689
274696ROCKY RD ;4P
Adder
13.733
274695ROCKY RD ;2P
Adder
13.416
274693ROCKY RD ;1P
Adder
13.284
274697ROCKY RD ;3P
Adder
3.645
274683WAUKEGAN ;8U
Adder
25.365
274683WAUKEGAN ;8U
Adder
21.381
25194408D.CRK1
Adder
9.077
25194508D.CRK3
Adder
1.697
23652301WDPWR_K20
Solar/Wind Helper
0.137
241967AE2-285_GEN
Solar/Wind Helper
0.621
241801AE1-079 GEN
Solar/Wind Helper
0.242
241985AE1-237 GEN
Solar/Wind Helper
0.242
962101AG1-054 GEN
Solar/Wind Helper
0.632
946071AF1-272 GEN
Solar/Wind Helper
2.567
23585401KL_K28_T16
Solar/Wind Helper
1.167
203955AF1-039 C O1
Solar/Wind Helper
0.346
944781AF1-143 GEN
Solar/Wind Helper
2.312
20083426SW_E13_K22
Solar/Wind Helper
0.053
20084626FORWARD
Solar/Wind Helper
0.336
20088926STNY CRK
Solar/Wind Helper
0.77
203940AF1-140 C
Solar/Wind Helper
0.374
20088626ARWF_N39
Solar/Wind Helper
1.147
20303426NA_O38_P22
Solar/Wind Helper
0.94
946381AF1-302 GEN
Solar/Wind Helper
0.21
203853AF1-134 C O1
Solar/Wind Helper
0.452
203952AE2-129 C
Solar/Wind Helper
0.447
203946AE2-131 C
Solar/Wind Helper
0.448
238120AE2-309 GEN
Solar/Wind Helper
0.401
238217AF1-153 C O1
Solar/Wind Helper
0.223
20398826ARMNA MT
Solar/Wind Helper
1.407
253317AC1-085 GEN4
Solar/Wind Harmer
9.247
NYPJM->LTFIMP_NY
CLTF
5.332
LGEELTFEXP_LGEE->PJM
CLTF
7.674
WECLTFEXP_WEC->PJM
CLTF
4.549
AG2-052LTFEXP_AG2-052->PJM
LTF
0.283
AH1-155LTFEXP_AH1-155->PJM
LTF
0.424
CPLELTFEXP_CPLE->PJM
CLTF
2.705
CBM West 2LTFEXP_CBM-W2->PJM
CBM
133.737
LAGNLTFEXP_LAGN->PJM
CLTF
17.886
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.768
TVALTFEXP_TVA->PJM
CLTF
8.721
CBM West 1LTFEXP_CBM-W1->PJM
CBM
155.754
CBM South 1LTFEXP_CBM-S1->PJM
CBM
34.409
MECLTFEXP_MEC->PJM
CLTF
18.875
SIGELTFEXP_SIGE->PJM
CLTF
0.583

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o AP_P1-3_MP-765-501T_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.76 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4919.18
MW Contribution:32.3
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
18.401
270159DARBY CT4
50/50
13.494
962761AG1-125 GEN
Solar/Wind Harmer
50.586
970149AG2-104 GEN
Solar/Wind Harmer
54.635
970155AG2-107 GEN
Solar/Wind Harmer
32.303
270349AD2-093_GEN
Solar/Wind Harmer
0.009
270223U2-072_GEN1
Solar/Wind Harmer
0.001
970593AG2-378 GEN
Solar/Wind Harmer
2.27
270462AD2-086
Solar/Wind Harmer
0.021
253343AC1-166 GEN
Solar/Wind Harmer
0.004
253325AC1-069 GEN
Solar/Wind Harmer
0.015
25326309TAIT D
Adder
1.4
960071AF2-298 GEN
Solar/Wind Harmer
4.426
965011AG1-365 GEN
Solar/Wind Harmer
8.881
253370AE2-315 SEC1
Adder
2.545
253371AE2-315 SEC2
Adder
2.407
965651AG1-433 GEN
Solar/Wind Harmer
2.599
970245AG2-165 GEN
Solar/Wind Harmer
3.83
958861AF2-177 GEN
Solar/Wind Harmer
3.827
971995AH1-542 GEN
Solar/Wind Harmer
3.236
945371AF1-202 GEN
Solar/Wind Harmer
0.001
247521TR3_G114
Solar/Wind Harmer
0.319
270246TR4_N_V150
Solar/Wind Harmer
0.056
24721705FLATG2
Adder
25.369
965421AG1-410 GEN
Solar/Wind Harmer
26.181
246936BC-WTG1
Solar/Wind Harmer
0.353
270489AE1-102 GEN1
Solar/Wind Harmer
1.132
247536S-71 GEN
Solar/Wind Harmer
0.349
270005AE1-210 C O1
Solar/Wind Harmer
1.875
965031AG1-367 GEN
Solar/Wind Harmer
8.654
270063AE2-323 C
Solar/Wind Harmer
0.007
24695305TIMB G C
Solar/Wind Harmer
0.002
970825AG2-519 GEN
Solar/Wind Harmer
3.064
270263AC1-001 GEN
Solar/Wind Harmer
0.865
270032AE2-172
Solar/Wind Harmer
5.743
970291AG2-192 GEN
Solar/Wind Harmer
1.119
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
6.306
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
8.568
24639705ELKHART HY
Adder
0.188
276903AD2-071 C
Solar/Wind Harmer
9.56
274773LINCOLN ;4U
Adder
10.354
274774LINCOLN ;5U
Adder
10.354
970373AG2-245 GEN
Solar/Wind Harmer
17.958
270055AF2-134 C O1
Solar/Wind Harmer
0.007
274723RIVER EC ;12
Adder
21.894
274751CRETE EC ;1U
Adder
10.063
274754CRETE EC ;4U
Adder
10.063
276164X3-005 C
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.064
274812UNIV PK N;8U
Adder
6.107
276776AD2-060 GEN
Solar/Wind Harmer
0.887
274801UNIV PARK;4U
Adder
7.097
941551AE2-152 GEN
Solar/Wind Harmer
0.001
945111AF1-176 GEN
Solar/Wind Harmer
15.149
270505AE1-170 C O1
Solar/Wind Harmer
8.915
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
10.609
274676JOLIET 29;8U
Adder
37.252
274674JOLIET 9 ;6U
Adder
18.689
274732ELWOOD EC;7P
Adder
19.951
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
970773AG2-487 GEN
Solar/Wind Harmer
1.492
274745AC1-111 GEN9
Adder
6.762
24791305MDL-5G
Solar/Wind Harmer
0.001
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
4.404
939401AE1-172 GEN
Solar/Wind Harmer
6.298
276691AA1-018 GEN1
Solar/Wind Harmer
1.02
274682WAUKEGAN ;7U
Adder
21.642
274828WAUKEGAN ;BP
Adder
13.296
276901AD2-066 C O1
Solar/Wind Harmer
0.008
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
962781AG1-127 GEN
Solar/Wind Harmer
7.975
971997AH1-543 GEN
Solar/Wind Harmer
4.396
25194608D.CRK4
Adder
1.973
274872LEEDK;1U
Solar/Wind Harmer
0.005
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
276861AD2-134 GEN
Solar/Wind Harmer
0.15
957471AF2-041 GEN
Solar/Wind Harmer
24.989
959081AF2-199 GEN
Solar/Wind Harmer
8.33
971067AG2-660 GEN
Solar/Wind Harmer
2.777
970569AG2-363 GEN
Solar/Wind Harmer
24.96
24728605AND G2
Adder
4.573
274822ROCKFORD ;11
Adder
23.399
972235AH1-702 GEN1
Adder
3.003
963741AG1-226 GEN
Solar/Wind Harmer
19.652
25196808ZIMRHP
Adder
58.315
254303AC2-168 GEN
Solar/Wind Helper
0.155
237046AF1-021 C
Solar/Wind Helper
0.463
241966AE1-183 GEN
Solar/Wind Helper
0.248
238185AF2-356 C
Solar/Wind Helper
2.025
20089226LOOKOUT
Solar/Wind Helper
0.542
20088826HIGHLAND
Solar/Wind Helper
0.847
20094526CT_V3-030
Solar/Wind Helper
0.446
235054AD2-180 GEN
Solar/Wind Helper
1.566
964201AG1-281 GEN
Solar/Wind Helper
0.457
238117U2-030
Solar/Wind Helper
0.269
235531U2-073 GEN
Solar/Wind Helper
2.545
964391AG1-301 GEN
Solar/Wind Helper
0.446
203954AE2-126 C
Solar/Wind Helper
0.443
23751201ROTHROCK
Solar/Wind Helper
0.652
238206AE2-263_GEN
Solar/Wind Helper
0.858
970819AG2-516 GEN
Solar/Wind Harmer
7.858
270119AB2-067 GEN1
50/50
18.401
270120AB2-067 GEN2
50/50
18.401
270160DARBY CT5
50/50
0.735
270161DARBY CT6
50/50
0.725
270466AD2-091
50/50
8.176
270471AD2-092_GEN
Solar/Wind Harmer
0.009
942861AE2-305 GEN
Solar/Wind Harmer
8.094
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
970077AG2-063 GEN
Solar/Wind Harmer
5.8
270518AE2-148 GEN
Solar/Wind Harmer
0.847
964601AG1-323 GEN
Solar/Wind Harmer
3.902
964601AG1-323 GEN
Solar/Wind Harmer
2.601
938701AE1-092 GEN
Solar/Wind Harmer
15.513
971655AH1-328 GEN
Solar/Wind Harmer
3.428
253378AE2-206_GEN
Solar/Wind Harmer
0.005
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
4.005
25326509SID D
Adder
1.713
25326109MON D
Adder
1.698
25322209TAIT E
Adder
12.455
25322209TAIT E
Adder
12.175
970611AG2-400 GEN
Solar/Wind Harmer
8.881
970627AG2-408 GEN
Solar/Wind Harmer
2.664
253370AE2-315 SEC1
Adder
2.545
944541AF1-119 GEN
Solar/Wind Harmer
0.594
960971AF2-388 GEN
Solar/Wind Harmer
5.197
970321AG2-212 GEN
Solar/Wind Harmer
3.83
942221AE2-234 GEN
Solar/Wind Harmer
0.044
270156DARBY CT1
50/50
13.713
270157DARBY CT2
50/50
13.679
270158DARBY CT3
50/50
13.461
270036AE2-216 BAT
50/50
8.994
962771AG1-126 GEN
Solar/Wind Harmer
50.586
270284AF1-227 GEN1
Solar/Wind Harmer
0.014
270286AF1-227 GEN2
Solar/Wind Harmer
0.006
270287AF1-227 GEN3
Solar/Wind Harmer
0.006
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
6.623
270520AE2-214 GEN
Solar/Wind Harmer
0.017
270054AF2-122 C O1
Solar/Wind Harmer
0.009
253383AE2-342_GEN
Solar/Wind Harmer
0.004
241973AD2-163_GEN1
Solar/Wind Harmer
0.008
943861AF1-054 GEN
Solar/Wind Harmer
3.995
943851AF1-053 GEN
Solar/Wind Harmer
2.767
270578AF1-285 GEN2
Solar/Wind Harmer
0.678
945631AF1-228 GEN
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Harmer
0.006
270317AD1-130_GEN
Solar/Wind Harmer
0.014
971653AH1-327 GEN
Solar/Wind Harmer
1.38
241972AD1-140 GEN
Solar/Wind Harmer
1.032
970689AG2-444 GEN
Solar/Wind Harmer
19.097
270432AC2-029 GEN
Solar/Wind Harmer
4.134
270269AC2-059
Solar/Wind Harmer
0.005
24729505KEY G4
Adder
8.316
270071AF1-092 GEN
Solar/Wind Harmer
17.084
253372AE2-315 SEC3
Adder
2.407
253372AE2-315 SEC3
Adder
2.407
965101AG1-375 GEN
Solar/Wind Harmer
8.831
25306009OHH W.
Adder
3.647
253349AC2-067 GEN
Solar/Wind Harmer
2.778
253400AC2-068 GEN
Solar/Wind Harmer
1.117
945581AF1-223 GEN
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
11.841
971347AH1-153 GEN
Solar/Wind Harmer
13.153
965051AG1-369 GEN
Solar/Wind Harmer
4.367
965041AG1-368 GEN
Solar/Wind Harmer
8.719
270024AE2-089 GEN
Solar/Wind Harmer
0.009
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.103
270340AC2-060 GEN
Solar/Wind Harmer
0.01
971609AH1-304 GEN
Solar/Wind Harmer
1.419
270543AE2-219 C
Solar/Wind Harmer
0.005
971029AG2-637 GEN
Solar/Wind Harmer
12.951
971673AH1-337 GEN
Solar/Wind Harmer
5.609
970115AG2-085 GEN
Solar/Wind Harmer
3.451
270594AE1-207 GEN
Solar/Wind Harmer
9.648
970289AG2-191 GEN
Solar/Wind Harmer
1.635
270240V3-007_GEN2
Solar/Wind Harmer
0.003
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971771AH1-392 GEN
Solar/Wind Harmer
8.573
971769AH1-391 GEN
Solar/Wind Harmer
9.561
274775LINCOLN ;6U
Adder
10.354
274776LINCOLN ;7U
Adder
10.354
274777LINCOLN ;8U
Adder
10.354
24725505WLD G2 C
Solar/Wind Harmer
0.002
24699105WLD G1 C
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.011
247607V1-011 GEN
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
6.16
274807UNIV PK N;3U
Adder
6.147
274805UNIV PK N;1U
Adder
6.12
274811UNIV PK N;7U
Adder
6.107
958391AF2-133 GEN
Solar/Wind Harmer
0.001
960591AF2-350 GEN
Solar/Wind Harmer
8.497
972227AH1-698 GEN1
Adder
3.176
972037AH1-567 GEN1
Adder
0.223
274827FISK ;RP
Adder
9.447
971619AH1-309 GEN
Solar/Wind Harmer
3.821
971611AH1-305 GEN
Solar/Wind Harmer
5.053
274687WILL CNTY;4U
Adder
33.939
274687WILL CNTY;4U
Adder
33.939
274675JOLIET 29;7U
Adder
37.252
274675JOLIET 29;7U
Adder
35.922
274731ELWOOD EC;2P
Adder
19.951
274733ELWOOD EC;3P
Adder
19.951
274735ELWOOD EC;4P
Adder
19.951
274728ELWOOD EC;5P
Adder
19.951
970833AG2-524 GEN
Solar/Wind Harmer
9.313
970833AG2-524 GEN
Solar/Wind Harmer
6.209
274746AC1-111 G10
Adder
6.762
274744AC1-111 GEN8
Adder
6.762
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
10.608
25196308WSDLE2
Adder
10.516
25196208WSDLE1
Adder
10.49
25196708WSDLE6
Adder
10.463
25196508WSDLE4
Adder
10.2
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.681
276882AE2-255 GEN
Solar/Wind Harmer
0.979
970169AG2-114 GEN
Solar/Wind Harmer
8.358
971177AH1-047 GEN
Solar/Wind Harmer
5.154
971675AH1-338 GEN
Solar/Wind Harmer
3.256
971411AH1-196 GEN
Solar/Wind Harmer
12.519
963841AG1-237 GEN
Solar/Wind Harmer
3.615
971171AH1-044 GEN
Solar/Wind Harmer
16.66
926823AC1-168 GEN
Solar/Wind Harmer
1.415
274823ROCKFORD ;21
Adder
23.229
254304AE2-114 C
Solar/Wind Helper
0.214
241982AE2-343 S C
Solar/Wind Helper
0.217
241997AF1-093 GEN
Solar/Wind Helper
0.248
23750501ELLIOTTS
Solar/Wind Helper
0.61
20092526R32
Solar/Wind Helper
1.098
203961AE2-224 GEN
Solar/Wind Helper
2.278
20091526CHSTN_FL
Solar/Wind Helper
0.55
20090526Q36
Solar/Wind Helper
0.985
203993AD2-133_GEN1
Solar/Wind Helper
0.985
203846AF2-130 C
Solar/Wind Helper
0.425
238126S14_GEN_1
Solar/Wind Helper
0.64
941231AE2-117 GEN
Solar/Wind Helper
0.447
203855AF2-088 C
Solar/Wind Helper
0.144
203804AE2-113_GEN
Solar/Wind Helper
1.639
270051AF1-062 GEN
50/50
17.076
270475AD2-096_GEN
50/50
10.066
970153AG2-106 GEN
Solar/Wind Harmer
32.303
961921AG1-034 GEN
Solar/Wind Harmer
9.935
241955AC1-078 GEN
Solar/Wind Harmer
0.009
241974AD2-163_GEN2
Solar/Wind Harmer
0.008
942051AE2-217 GEN
Solar/Wind Harmer
18.548
270391AF1-285 GEN3
Solar/Wind Harmer
0.678
970605AG2-385 GEN
Solar/Wind Harmer
6.136
270485AE1-090_GEN
Solar/Wind Harmer
0.001
253338AC1-165 GEN
Solar/Wind Harmer
0.004
253333AC1-068 GEN
Solar/Wind Harmer
0.015
270273AD2-016 GEN
Solar/Wind Harmer
0.935
944531AF1-118 GEN
Solar/Wind Harmer
40.219
972173AH1-669 GEN
Solar/Wind Harmer
4.474
270043AE2-236 GEN
Solar/Wind Harmer
5.712
959331AF2-224 GEN
Solar/Wind Harmer
6.217
965021AG1-366 GEN
Solar/Wind Harmer
2.96
253370AE2-315 SEC1
Adder
2.545
253371AE2-315 SEC2
Adder
2.407
970513AG2-328 GEN
Solar/Wind Harmer
3.83
970517AG2-330 GEN
Solar/Wind Harmer
22.981
970191AG2-125 GEN
Solar/Wind Harmer
2.269
253415AE1-040 GEN
Solar/Wind Harmer
0.004
970349AG2-230 GEN
Solar/Wind Harmer
13.153
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.056
24721905FLATG4
Adder
25.369
971617AH1-308 GEN
Solar/Wind Harmer
7.263
270491AE1-102 GEN2
Solar/Wind Harmer
1.132
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
13.019
970031AG2-029 GEN
Solar/Wind Harmer
5.627
958821AF2-173 GEN
Solar/Wind Harmer
12.116
270004AE1-209 GEN
Solar/Wind Harmer
1.875
946031AF1-268 GEN
Solar/Wind Harmer
8.226
253406AD2-031_GEN
Solar/Wind Harmer
0.643
970289AG2-191 GEN
Solar/Wind Harmer
0.947
970291AG2-192 GEN
Solar/Wind Harmer
0.861
247642Z2-115 C
Solar/Wind Harmer
0.004
270437AC2-090 C
Solar/Wind Harmer
0.004
247643Z2-116 C
Solar/Wind Harmer
0
253316AC1-085 GEN3
Solar/Wind Harmer
0.005
253433AC1-085 GEN1
Solar/Wind Harmer
0.004
946181AF1-283 GEN
Solar/Wind Harmer
11.138
274772LINCOLN ;3U
Adder
10.354
270535AF1-215 GEN1
Solar/Wind Harmer
0.011
270222AC2-111 GEN
Solar/Wind Harmer
4.32
274724RIVER EC ;11
Adder
21.639
274752CRETE EC ;2U
Adder
10.063
274753CRETE EC ;3U
Adder
10.063
24642205MAYFLWER
Adder
0.776
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970707AG2-453 GEN
Solar/Wind Harmer
27.781
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
276806AD2-047 C O1
Solar/Wind Harmer
4.815
970941AG2-585 GEN
Solar/Wind Harmer
10.621
274802UNIV PARK;5U
Adder
7.1
972228AH1-698 GEN2
Adder
4.511
274826FISK ;BP
Adder
13.329
274800UNIV PARK;3U
Adder
7.097
972038AH1-567 GEN2
Adder
0.444
276897AD1-100 C
Solar/Wind Harmer
0.011
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
945111AF1-176 GEN
Solar/Wind Harmer
6.882
274676JOLIET 29;8U
Adder
35.922
274729ELWOOD EC;1P
Adder
19.951
274730ELWOOD EC;6P
Adder
19.951
274734ELWOOD EC;8P
Adder
19.951
274736ELWOOD EC;9P
Adder
19.951
276893AG1-478 C
Solar/Wind Harmer
0.336
943121AE2-341 GEN
Solar/Wind Harmer
14.16
943591AF1-030 GEN
Solar/Wind Harmer
9.416
270356AE2-297 GEN
Solar/Wind Harmer
0.011
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
8.438
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
21.642
25196608WSDLE5
Adder
10.305
276805AD2-038 GEN
Solar/Wind Harmer
0.002
25194608D.CRK4
Adder
1.973
274872LEEDK;1U
Solar/Wind Harmer
0.307
252510AF1-249 C
Solar/Wind Harmer
0.065
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.891
276889AE2-281 GEN
Solar/Wind Harmer
0.001
274855GSG-6 ;RU
Solar/Wind Harmer
0.306
274850MENDOTA H;RU
Solar/Wind Harmer
0.098
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.15
959091AF2-200 GEN
Solar/Wind Harmer
16.66
24441205WTRV SLR C
Solar/Wind Harmer
0
970571AG2-364 GEN
Solar/Wind Harmer
16.64
24728705AND G3
Adder
9.564
24728505AND G1
Adder
4.573
270258AD1-119 GEN
Solar/Wind Harmer
0.002
972236AH1-702 GEN2
Adder
2.611
235058AG1-386 C
Solar/Wind Helper
0.453
237048AF1-022 C
Solar/Wind Helper
0.176
254305AE2-115 C
Solar/Wind Helper
0.214
237043AE2-125 C
Solar/Wind Helper
0.172
964991AG1-363 GEN
Solar/Wind Helper
3.577
202652Y1-033 WT C
Solar/Wind Helper
0.525
20089126CSLMN_L13
Solar/Wind Helper
0.557
20089026BF_G21_K23
Solar/Wind Helper
0.441
23750701CROSSCHOOL
Solar/Wind Helper
1.122
203818AF1-086 GEN
Solar/Wind Helper
1.594
238118U2-030_1
Solar/Wind Helper
0.269
238127S14_GEN_2
Solar/Wind Helper
0.64
203854AF2-039 C
Solar/Wind Helper
0.3
20334926Z1-069 C
Solar/Wind Helper
1.268
238202AE2-262_GEN
Solar/Wind Helper
0.902
246938BC-WTG3
Solar/Wind Harmer
0.316
246937BC-WTG2
Solar/Wind Harmer
0.353
270599AE1-208 GEN
Solar/Wind Harmer
7.961
270031AE2-169
Solar/Wind Harmer
4.777
253394AE2-221_GEN
Solar/Wind Harmer
0.011
253398AE2-221_GEN2
Solar/Wind Harmer
0.011
270201AC2-176 GEN
Solar/Wind Harmer
0.002
964611AG1-324 GEN
Solar/Wind Harmer
0.65
247621Y3-024
Adder
0.3
970883AG2-550 GEN
Solar/Wind Harmer
8.648
970885AG2-551 GEN
Solar/Wind Harmer
2.883
970825AG2-519 GEN
Solar/Wind Harmer
9.566
960441AF2-335 GEN
Solar/Wind Harmer
8.628
971613AH1-306 GEN
Solar/Wind Harmer
4.135
270383AD1-128 GEN
Solar/Wind Harmer
0.005
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
965681AG1-436 GEN
Solar/Wind Harmer
10.743
965791AG1-447 GEN
Solar/Wind Harmer
7.878
270216AD2-079_GEN
Solar/Wind Harmer
0.001
253317AC1-085 GEN4
Solar/Wind Harmer
0.005
247620Y3-023
Adder
0.565
270526AF1-158 GEN
Solar/Wind Harmer
0.011
24441505OLIV SLR
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
10.354
274771LINCOLN ;2U
Adder
10.354
270007AE1-245 C
Solar/Wind Harmer
0.002
274808UNIV PK N;4U
Adder
6.08
274888KELLY CRK;1U
Solar/Wind Harmer
0.499
274887GEN-1.85
Solar/Wind Harmer
0.224
276843GEN-1.7
Solar/Wind Harmer
0.275
972259AH1-714 GEN
Adder
23.234
958011AF2-095 GEN
Solar/Wind Harmer
12.235
274803UNIV PARK;6U
Adder
7.1
957891AF2-083 GEN
Solar/Wind Harmer
0.001
24728805RICHG1
Adder
4.598
24728905RICHG2
Adder
4.598
274674JOLIET 9 ;6U
Adder
18.689
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
961051AF2-396 GEN
Solar/Wind Harmer
16.913
961051AF2-396 GEN
Solar/Wind Harmer
11.276
971573AH1-285 GEN
Solar/Wind Harmer
1.571
958481AF2-142 GEN
Solar/Wind Harmer
12.626
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
1.139
274696ROCKY RD ;4P
Adder
13.733
274695ROCKY RD ;2P
Adder
13.416
274693ROCKY RD ;1P
Adder
13.284
274697ROCKY RD ;3P
Adder
3.645
274683WAUKEGAN ;8U
Adder
25.365
274683WAUKEGAN ;8U
Adder
21.381
25183208HLCRTG
Solar/Wind Harmer
0.013
958491AF2-143 GEN
Solar/Wind Harmer
12.583
962691AG1-118 GEN
Solar/Wind Harmer
25.162
966841AG1-555 GEN
Solar/Wind Harmer
0.948
970921AG2-575 GEN
Solar/Wind Harmer
8.38
970921AG2-575 GEN
Solar/Wind Harmer
2.793
274879MINONK ;1U
Solar/Wind Harmer
0.353
25194408D.CRK1
Adder
9.077
25194508D.CRK3
Adder
1.697
252519AF1-045_GEN
Solar/Wind Harmer
7.283
252516AE2-318_GEN
Solar/Wind Harmer
6.46
942991AE2-321 GEN
Solar/Wind Harmer
9.334
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
971333AH1-146 GEN
Solar/Wind Harmer
16.689
971335AH1-147 GEN
Solar/Wind Harmer
16.689
971341AH1-150 GEN
Solar/Wind Harmer
16.66
971343AH1-151 GEN
Solar/Wind Harmer
16.66
970623AG2-406 GEN
Solar/Wind Harmer
1.522
970241AG2-163 GEN
Solar/Wind Harmer
4.844
23652301WDPWR_K20
Solar/Wind Helper
0.137
241967AE2-285_GEN
Solar/Wind Helper
0.621
241801AE1-079 GEN
Solar/Wind Helper
0.242
241985AE1-237 GEN
Solar/Wind Helper
0.242
962101AG1-054 GEN
Solar/Wind Helper
0.632
946071AF1-272 GEN
Solar/Wind Helper
2.567
23585401KL_K28_T16
Solar/Wind Helper
1.167
203955AF1-039 C O1
Solar/Wind Helper
0.346
944781AF1-143 GEN
Solar/Wind Helper
2.312
20083426SW_E13_K22
Solar/Wind Helper
0.053
20084626FORWARD
Solar/Wind Helper
0.336
20088926STNY CRK
Solar/Wind Helper
0.77
203940AF1-140 C
Solar/Wind Helper
0.374
20088626ARWF_N39
Solar/Wind Helper
1.147
20303426NA_O38_P22
Solar/Wind Helper
0.94
946381AF1-302 GEN
Solar/Wind Helper
0.21
203853AF1-134 C O1
Solar/Wind Helper
0.452
203952AE2-129 C
Solar/Wind Helper
0.447
203946AE2-131 C
Solar/Wind Helper
0.448
238120AE2-309 GEN
Solar/Wind Helper
0.401
238217AF1-153 C O1
Solar/Wind Helper
0.223
20398826ARMNA MT
Solar/Wind Helper
1.407
NYPJM->LTFIMP_NY
CLTF
5.332
LGEELTFEXP_LGEE->PJM
CLTF
7.674
WECLTFEXP_WEC->PJM
CLTF
4.549
AG2-052LTFEXP_AG2-052->PJM
LTF
0.283
AH1-155LTFEXP_AH1-155->PJM
LTF
0.424
CPLELTFEXP_CPLE->PJM
CLTF
2.705
CBM West 2LTFEXP_CBM-W2->PJM
CBM
133.737
LAGNLTFEXP_LAGN->PJM
CLTF
17.886
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.768
TVALTFEXP_TVA->PJM
CLTF
8.721
CBM West 1LTFEXP_CBM-W1->PJM
CBM
155.754
CBM South 1LTFEXP_CBM-S1->PJM
CBM
34.409
MECLTFEXP_MEC->PJM
CLTF
18.875
SIGELTFEXP_SIGE->PJM
CLTF
0.583

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o AEP_P4_#2942_05KAMMER 765_PP_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:135.19 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5599.56
MW Contribution:38.38
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
1.712
971599AH1-298 GEN
50/50
11.939
962771AG1-126 GEN
Solar/Wind Harmer
88.009
971347AH1-153 GEN
Solar/Wind Harmer
19.74
270071AF1-092 GEN
Solar/Wind Harmer
19.263
960681AF2-359 GEN
Solar/Wind Harmer
4.78
274775LINCOLN ;6U
Adder
7.811
274776LINCOLN ;7U
Adder
7.811
274777LINCOLN ;8U
Adder
7.811
971771AH1-392 GEN
Solar/Wind Harmer
11.34
971769AH1-391 GEN
Solar/Wind Harmer
12.581
24729505KEY G4
Adder
8.072
274814UNIV PK N;0U
Adder
6.285
274807UNIV PK N;3U
Adder
6.271
274805UNIV PK N;1U
Adder
6.244
274811UNIV PK N;7U
Adder
6.23
274827FISK ;RP
Adder
9.635
972037AH1-567 GEN1
Adder
0.227
960591AF2-350 GEN
Solar/Wind Harmer
12.418
972227AH1-698 GEN1
Adder
3.239
274687WILL CNTY;4U
Adder
34.573
274687WILL CNTY;4U
Adder
34.573
274675JOLIET 29;7U
Adder
37.943
274675JOLIET 29;7U
Adder
36.588
274731ELWOOD EC;2P
Adder
20.304
274733ELWOOD EC;3P
Adder
20.304
274735ELWOOD EC;4P
Adder
20.304
274728ELWOOD EC;5P
Adder
20.304
970833AG2-524 GEN
Solar/Wind Harmer
10.782
970833AG2-524 GEN
Solar/Wind Harmer
5.015
274746AC1-111 G10
Adder
6.879
274744AC1-111 GEN8
Adder
6.879
270536AF1-215 GEN2
Solar/Wind Harmer
5.59
944161AF1-084 GEN
Solar/Wind Harmer
2.707
958391AF2-133 GEN
Solar/Wind Harmer
11.03
276868AE1-113 GEN
Solar/Wind Harmer
12.269
276882AE2-255 GEN
Solar/Wind Harmer
4.09
971177AH1-047 GEN
Solar/Wind Harmer
7.102
971675AH1-338 GEN
Solar/Wind Harmer
21.77
971411AH1-196 GEN
Solar/Wind Harmer
18.14
274863CRW1-WTG
Solar/Wind Harmer
6.746
274864CRW2-WTG
Solar/Wind Harmer
6.746
274823ROCKFORD ;21
Adder
23.439
24722005FLATG5
50/50
1.712
24721905FLATG4
50/50
31.388
970153AG2-106 GEN
Solar/Wind Harmer
38.376
970513AG2-328 GEN
Solar/Wind Harmer
23.63
970517AG2-330 GEN
Solar/Wind Harmer
21.432
970349AG2-230 GEN
Solar/Wind Harmer
19.74
270043AE2-236 GEN
Solar/Wind Harmer
7.114
274772LINCOLN ;3U
Adder
7.811
944531AF1-118 GEN
Solar/Wind Harmer
44.088
247643Z2-116 C
Solar/Wind Harmer
0.088
274724RIVER EC ;11
Adder
22.115
24642205MAYFLWER
Adder
0.793
972231SS25-0005
Solar/Wind Harmer
11.831
972181SS23-001
Solar/Wind Harmer
7.394
274752CRETE EC ;2U
Adder
6.093
274753CRETE EC ;3U
Adder
6.093
970707AG2-453 GEN
Solar/Wind Harmer
34.896
274826FISK ;BP
Adder
13.595
274802UNIV PARK;5U
Adder
7.24
276772AC2-154 GEN
Solar/Wind Harmer
3.463
276806AD2-047 C O1
Solar/Wind Harmer
13.284
970941AG2-585 GEN
Solar/Wind Harmer
15.522
972228AH1-698 GEN2
Adder
4.599
274800UNIV PARK;3U
Adder
7.237
972038AH1-567 GEN2
Adder
0.453
945111AF1-176 GEN
Solar/Wind Harmer
7.013
276897AD1-100 C
Solar/Wind Harmer
35.973
939351AE1-166 GEN
Solar/Wind Harmer
7.35
970031AG2-029 GEN
Solar/Wind Harmer
37.15
274676JOLIET 29;8U
Adder
36.588
274729ELWOOD EC;1P
Adder
20.304
274730ELWOOD EC;6P
Adder
20.304
274734ELWOOD EC;8P
Adder
20.304
274736ELWOOD EC;9P
Adder
20.304
276893AG1-478 C
Solar/Wind Harmer
0.516
943121AE2-341 GEN
Solar/Wind Harmer
18.483
943591AF1-030 GEN
Solar/Wind Harmer
12.322
270535AF1-215 GEN1
Solar/Wind Harmer
5.59
959331AF2-224 GEN
Solar/Wind Harmer
12.268
965021AG1-366 GEN
Solar/Wind Harmer
2.853
276694AA1-018 GEN2
Solar/Wind Harmer
7.714
274682WAUKEGAN ;7U
Adder
21.959
964401AG1-302 GEN
Solar/Wind Harmer
11.074
274872LEEDK;1U
Solar/Wind Harmer
0.311
276805AD2-038 GEN
Solar/Wind Harmer
6.233
959141AF2-205 GEN
Solar/Wind Harmer
7.329
24441205WTRV SLR C
Solar/Wind Harmer
0.163
276799AD1-013 GEN
Solar/Wind Harmer
2.674
946671AF1-331 GEN
Solar/Wind Harmer
0.506
274855GSG-6 ;RU
Solar/Wind Harmer
4.467
274850MENDOTA H;RU
Solar/Wind Harmer
3.106
276602WESTBROOK C
Solar/Wind Harmer
2.571
276863AD2-134 GEN
Solar/Wind Harmer
2.16
972236AH1-702 GEN2
Adder
2.633
247604X1-042
Adder
0.499
274760LEE CO EC;1U
Adder
11.092
274767LEE CO EC;8U
Adder
10.962
24728705AND G3
Adder
5.203
24721805FLATG3
50/50
1.712
24721705FLATG2
50/50
31.388
24344105CKG2
50/50
10.173
962761AG1-125 GEN
Solar/Wind Harmer
88.009
970149AG2-104 GEN
Solar/Wind Harmer
108.691
970155AG2-107 GEN
Solar/Wind Harmer
38.376
970245AG2-165 GEN
Solar/Wind Harmer
23.63
972207SS24-0001
Solar/Wind Harmer
27.773
274773LINCOLN ;4U
Adder
7.811
274774LINCOLN ;5U
Adder
7.811
274723RIVER EC ;12
Adder
22.373
24639705ELKHART HY
Adder
0.192
276164X3-005 C
Solar/Wind Harmer
0.876
274751CRETE EC ;1U
Adder
6.093
274754CRETE EC ;4U
Adder
6.093
274812UNIV PK N;8U
Adder
6.23
270063AE2-323 C
Solar/Wind Harmer
2.741
270505AE1-170 C O1
Solar/Wind Harmer
18.655
276776AD2-060 GEN
Solar/Wind Harmer
0.525
274801UNIV PARK;4U
Adder
7.237
970373AG2-245 GEN
Solar/Wind Harmer
26.061
945111AF1-176 GEN
Solar/Wind Harmer
22.129
941551AE2-152 GEN
Solar/Wind Harmer
5.622
274676JOLIET 29;8U
Adder
37.943
274674JOLIET 9 ;6U
Adder
19.027
274732ELWOOD EC;7P
Adder
20.304
274871GR RIDGE ;2U
Solar/Wind Harmer
9.495
270449AD2-020 GEN
Solar/Wind Harmer
3.453
943021AE2-325 GEN
Solar/Wind Harmer
4.486
274745AC1-111 GEN9
Adder
6.879
270055AF2-134 C O1
Solar/Wind Harmer
3.726
965011AG1-365 GEN
Solar/Wind Harmer
12.268
276691AA1-018 GEN1
Solar/Wind Harmer
0.569
274682WAUKEGAN ;7U
Adder
21.959
274828WAUKEGAN ;BP
Adder
13.487
958381AF2-132 GEN
Solar/Wind Harmer
11.074
964861AG1-349 GEN
Solar/Wind Harmer
9.588
971917AH1-482 GEN
Solar/Wind Harmer
11.064
939401AE1-172 GEN
Solar/Wind Harmer
16.965
960751AF2-366 GEN
Solar/Wind Harmer
3.492
962781AG1-127 GEN
Solar/Wind Harmer
11.574
274872LEEDK;1U
Solar/Wind Harmer
9.985
276901AD2-066 C O1
Solar/Wind Harmer
4.267
971997AH1-543 GEN
Solar/Wind Harmer
19.076
276861AD2-134 GEN
Solar/Wind Harmer
2.16
274822ROCKFORD ;11
Adder
23.61
972235AH1-702 GEN1
Adder
3.028
274761LEE CO EC;2U
Adder
11.092
274766LEE CO EC;7U
Adder
10.962
940581AE2-045 GEN
Solar/Wind Harmer
2.548
971605AH1-302 GEN
Solar/Wind Harmer
2.178
270102X2-052 ST
50/50
2.03
270100X2-052 CT1
50/50
1.87
270101X2-052 CT2
50/50
1.87
970321AG2-212 GEN
Solar/Wind Harmer
23.63
965681AG1-436 GEN
Solar/Wind Harmer
15.817
965791AG1-447 GEN
Solar/Wind Harmer
8.092
274770LINCOLN ;1U
Adder
7.811
274771LINCOLN ;2U
Adder
7.811
270526AF1-158 GEN
Solar/Wind Harmer
5.718
24441505OLIV SLR
Solar/Wind Harmer
0.169
270216AD2-079_GEN
Solar/Wind Harmer
0.761
274808UNIV PK N;4U
Adder
6.203
957891AF2-083 GEN
Solar/Wind Harmer
4.193
972259AH1-714 GEN
Adder
23.715
960981AF2-389 GEN
Solar/Wind Harmer
1.879
247620Y3-023
Adder
0.572
274803UNIV PARK;6U
Adder
7.24
274888KELLY CRK;1U
Solar/Wind Harmer
7.331
274887GEN-1.85
Solar/Wind Harmer
6.619
276843GEN-1.7
Solar/Wind Harmer
0.712
958011AF2-095 GEN
Solar/Wind Harmer
17.882
274674JOLIET 9 ;6U
Adder
19.027
961051AF2-396 GEN
Solar/Wind Harmer
19.603
961051AF2-396 GEN
Solar/Wind Harmer
9.118
274847GR RIDGE ;BU
Solar/Wind Harmer
6.245
971573AH1-285 GEN
Solar/Wind Harmer
10.565
970611AG2-400 GEN
Solar/Wind Harmer
12.268
274696ROCKY RD ;4P
Adder
13.939
274695ROCKY RD ;2P
Adder
13.618
274693ROCKY RD ;1P
Adder
13.484
274697ROCKY RD ;3P
Adder
3.699
958481AF2-142 GEN
Solar/Wind Harmer
18.335
274861TOP CROP ;1U
Solar/Wind Harmer
7.405
274862TOP CROP ;2U
Solar/Wind Harmer
6.183
274683WAUKEGAN ;8U
Adder
25.73
274683WAUKEGAN ;8U
Adder
21.689
962691AG1-118 GEN
Solar/Wind Harmer
36.56
970921AG2-575 GEN
Solar/Wind Harmer
12.17
970921AG2-575 GEN
Solar/Wind Harmer
2.83
958491AF2-143 GEN
Solar/Wind Harmer
18.224
274879MINONK ;1U
Solar/Wind Harmer
8.18
942991AE2-321 GEN
Solar/Wind Harmer
12.121
971333AH1-146 GEN
Solar/Wind Harmer
24.178
971335AH1-147 GEN
Solar/Wind Harmer
24.178
274764LEE CO EC;5U
Adder
11.118
274765LEE CO EC;6U
Adder
11.118
274762LEE CO EC;3U
Adder
11.092
274763LEE CO EC;4U
Adder
10.988
972267AH1-718 GEN
Adder
4.939
247621Y3-024
Adder
0.249
944201AF1-088_MTX
Adder
120.897
957141AF2-008_MTX
Adder
60.448
NYPJM->LTFIMP_NY
CLTF
3.943
LGEELTFEXP_LGEE->PJM
CLTF
5.944
WECLTFEXP_WEC->PJM
CLTF
4.587
AG2-052LTFEXP_AG2-052->PJM
LTF
0.283
AH1-155LTFEXP_AH1-155->PJM
LTF
0.425
CPLELTFEXP_CPLE->PJM
CLTF
3.179
CBM West 2LTFEXP_CBM-W2->PJM
CBM
122.482
LAGNLTFEXP_LAGN->PJM
CLTF
16.558
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.028
TVALTFEXP_TVA->PJM
CLTF
7.884
CBM West 1LTFEXP_CBM-W1->PJM
CBM
147.549
CBM South 1LTFEXP_CBM-S1->PJM
CBM
30.127
MECLTFEXP_MEC->PJM
CLTF
18.475
SIGELTFEXP_SIGE->PJM
CLTF
0.494

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o AP_P2-3_MP-500-020_SRT-SL


Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-020_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.22 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5476.65
MW Contribution:38.51
Bus #Bus NameTypeMW Contribution
24721805FLATG3
50/50
1.723
24721705FLATG2
50/50
31.59
24344105CKG2
50/50
10.242
962761AG1-125 GEN
Solar/Wind Harmer
88.31
970149AG2-104 GEN
Solar/Wind Harmer
109.063
970155AG2-107 GEN
Solar/Wind Harmer
38.507
970245AG2-165 GEN
Solar/Wind Harmer
23.794
972207SS24-0001
Solar/Wind Harmer
27.975
274773LINCOLN ;4U
Adder
7.868
274774LINCOLN ;5U
Adder
7.868
274723RIVER EC ;12
Adder
22.538
24639705ELKHART HY
Adder
0.193
276164X3-005 C
Solar/Wind Harmer
0.882
274751CRETE EC ;1U
Adder
6.138
274754CRETE EC ;4U
Adder
6.138
274812UNIV PK N;8U
Adder
6.276
270063AE2-323 C
Solar/Wind Harmer
2.761
270505AE1-170 C O1
Solar/Wind Harmer
18.792
276776AD2-060 GEN
Solar/Wind Harmer
0.529
274801UNIV PARK;4U
Adder
7.291
970373AG2-245 GEN
Solar/Wind Harmer
26.254
945111AF1-176 GEN
Solar/Wind Harmer
22.293
941551AE2-152 GEN
Solar/Wind Harmer
5.664
274676JOLIET 29;8U
Adder
38.224
274674JOLIET 9 ;6U
Adder
19.168
274732ELWOOD EC;7P
Adder
20.454
274871GR RIDGE ;2U
Solar/Wind Harmer
9.565
270449AD2-020 GEN
Solar/Wind Harmer
3.478
943021AE2-325 GEN
Solar/Wind Harmer
4.52
274745AC1-111 GEN9
Adder
6.931
270055AF2-134 C O1
Solar/Wind Harmer
3.754
965011AG1-365 GEN
Solar/Wind Harmer
12.36
276691AA1-018 GEN1
Solar/Wind Harmer
0.573
274682WAUKEGAN ;7U
Adder
22.124
274828WAUKEGAN ;BP
Adder
13.588
958381AF2-132 GEN
Solar/Wind Harmer
11.158
964861AG1-349 GEN
Solar/Wind Harmer
9.66
971917AH1-482 GEN
Solar/Wind Harmer
11.148
939401AE1-172 GEN
Solar/Wind Harmer
17.093
960751AF2-366 GEN
Solar/Wind Harmer
3.518
962781AG1-127 GEN
Solar/Wind Harmer
11.661
274872LEEDK;1U
Solar/Wind Harmer
10.06
276901AD2-066 C O1
Solar/Wind Harmer
4.299
971997AH1-543 GEN
Solar/Wind Harmer
19.22
276861AD2-134 GEN
Solar/Wind Harmer
2.176
274822ROCKFORD ;11
Adder
23.79
972235AH1-702 GEN1
Adder
3.052
274761LEE CO EC;2U
Adder
11.177
274766LEE CO EC;7U
Adder
11.046
940581AE2-045 GEN
Solar/Wind Harmer
2.567
971605AH1-302 GEN
Solar/Wind Harmer
2.195
24721605FLATG1
50/50
1.723
971599AH1-298 GEN
50/50
12.019
962771AG1-126 GEN
Solar/Wind Harmer
88.31
971347AH1-153 GEN
Solar/Wind Harmer
19.878
270071AF1-092 GEN
Solar/Wind Harmer
19.402
960681AF2-359 GEN
Solar/Wind Harmer
4.815
274775LINCOLN ;6U
Adder
7.868
274776LINCOLN ;7U
Adder
7.868
274777LINCOLN ;8U
Adder
7.868
971771AH1-392 GEN
Solar/Wind Harmer
11.423
971769AH1-391 GEN
Solar/Wind Harmer
12.673
24729505KEY G4
Adder
8.132
274814UNIV PK N;0U
Adder
6.331
274807UNIV PK N;3U
Adder
6.318
274805UNIV PK N;1U
Adder
6.29
274811UNIV PK N;7U
Adder
6.276
274827FISK ;RP
Adder
9.706
972037AH1-567 GEN1
Adder
0.229
960591AF2-350 GEN
Solar/Wind Harmer
12.509
972227AH1-698 GEN1
Adder
3.263
274687WILL CNTY;4U
Adder
34.83
274687WILL CNTY;4U
Adder
34.83
274675JOLIET 29;7U
Adder
38.225
274675JOLIET 29;7U
Adder
36.86
274731ELWOOD EC;2P
Adder
20.454
274733ELWOOD EC;3P
Adder
20.454
274735ELWOOD EC;4P
Adder
20.454
274728ELWOOD EC;5P
Adder
20.454
970833AG2-524 GEN
Solar/Wind Harmer
10.862
970833AG2-524 GEN
Solar/Wind Harmer
5.052
274746AC1-111 G10
Adder
6.931
274744AC1-111 GEN8
Adder
6.931
270536AF1-215 GEN2
Solar/Wind Harmer
5.632
944161AF1-084 GEN
Solar/Wind Harmer
2.727
958391AF2-133 GEN
Solar/Wind Harmer
11.114
276868AE1-113 GEN
Solar/Wind Harmer
12.361
276882AE2-255 GEN
Solar/Wind Harmer
4.121
971177AH1-047 GEN
Solar/Wind Harmer
7.155
971675AH1-338 GEN
Solar/Wind Harmer
21.935
971411AH1-196 GEN
Solar/Wind Harmer
18.277
274863CRW1-WTG
Solar/Wind Harmer
6.797
274864CRW2-WTG
Solar/Wind Harmer
6.797
274823ROCKFORD ;21
Adder
23.617
24722005FLATG5
50/50
1.723
24721905FLATG4
50/50
31.59
970153AG2-106 GEN
Solar/Wind Harmer
38.507
970513AG2-328 GEN
Solar/Wind Harmer
23.794
970517AG2-330 GEN
Solar/Wind Harmer
21.581
970349AG2-230 GEN
Solar/Wind Harmer
19.878
270043AE2-236 GEN
Solar/Wind Harmer
7.165
274772LINCOLN ;3U
Adder
7.868
944531AF1-118 GEN
Solar/Wind Harmer
44.412
247643Z2-116 C
Solar/Wind Harmer
0.088
274724RIVER EC ;11
Adder
22.277
24642205MAYFLWER
Adder
0.799
972231SS25-0005
Solar/Wind Harmer
11.918
972181SS23-001
Solar/Wind Harmer
7.449
274752CRETE EC ;2U
Adder
6.138
274753CRETE EC ;3U
Adder
6.138
970707AG2-453 GEN
Solar/Wind Harmer
35.152
274826FISK ;BP
Adder
13.696
274802UNIV PARK;5U
Adder
7.293
972228AH1-698 GEN2
Adder
4.633
276772AC2-154 GEN
Solar/Wind Harmer
3.489
276806AD2-047 C O1
Solar/Wind Harmer
13.382
970941AG2-585 GEN
Solar/Wind Harmer
15.637
274800UNIV PARK;3U
Adder
7.291
972038AH1-567 GEN2
Adder
0.456
945111AF1-176 GEN
Solar/Wind Harmer
7.065
276897AD1-100 C
Solar/Wind Harmer
36.239
939351AE1-166 GEN
Solar/Wind Harmer
7.405
970031AG2-029 GEN
Solar/Wind Harmer
37.426
274676JOLIET 29;8U
Adder
36.859
274729ELWOOD EC;1P
Adder
20.454
274730ELWOOD EC;6P
Adder
20.454
274734ELWOOD EC;8P
Adder
20.454
274736ELWOOD EC;9P
Adder
20.454
276893AG1-478 C
Solar/Wind Harmer
0.52
943121AE2-341 GEN
Solar/Wind Harmer
18.62
943591AF1-030 GEN
Solar/Wind Harmer
12.414
270535AF1-215 GEN1
Solar/Wind Harmer
5.632
959331AF2-224 GEN
Solar/Wind Harmer
12.36
965021AG1-366 GEN
Solar/Wind Harmer
2.874
276694AA1-018 GEN2
Solar/Wind Harmer
7.772
274682WAUKEGAN ;7U
Adder
22.124
964401AG1-302 GEN
Solar/Wind Harmer
11.158
274872LEEDK;1U
Solar/Wind Harmer
0.313
276805AD2-038 GEN
Solar/Wind Harmer
6.28
959141AF2-205 GEN
Solar/Wind Harmer
7.384
24441205WTRV SLR C
Solar/Wind Harmer
0.164
276799AD1-013 GEN
Solar/Wind Harmer
2.695
946671AF1-331 GEN
Solar/Wind Harmer
0.51
274855GSG-6 ;RU
Solar/Wind Harmer
4.5
274850MENDOTA H;RU
Solar/Wind Harmer
3.129
276602WESTBROOK C
Solar/Wind Harmer
2.591
276863AD2-134 GEN
Solar/Wind Harmer
2.176
972236AH1-702 GEN2
Adder
2.653
247604X1-042
Adder
0.503
274760LEE CO EC;1U
Adder
11.177
274767LEE CO EC;8U
Adder
11.046
24728705AND G3
Adder
5.25
270102X2-052 ST
50/50
2.044
270100X2-052 CT1
50/50
1.884
270101X2-052 CT2
50/50
1.884
970321AG2-212 GEN
Solar/Wind Harmer
23.794
965681AG1-436 GEN
Solar/Wind Harmer
15.932
965791AG1-447 GEN
Solar/Wind Harmer
8.151
274770LINCOLN ;1U
Adder
7.868
274771LINCOLN ;2U
Adder
7.868
270526AF1-158 GEN
Solar/Wind Harmer
5.76
24441505OLIV SLR
Solar/Wind Harmer
0.17
270216AD2-079_GEN
Solar/Wind Harmer
0.767
274808UNIV PK N;4U
Adder
6.249
957891AF2-083 GEN
Solar/Wind Harmer
4.224
972259AH1-714 GEN
Adder
23.89
960981AF2-389 GEN
Solar/Wind Harmer
1.893
247620Y3-023
Adder
0.576
274803UNIV PARK;6U
Adder
7.293
274888KELLY CRK;1U
Solar/Wind Harmer
7.386
274887GEN-1.85
Solar/Wind Harmer
6.668
276843GEN-1.7
Solar/Wind Harmer
0.717
958011AF2-095 GEN
Solar/Wind Harmer
18.014
274674JOLIET 9 ;6U
Adder
19.168
961051AF2-396 GEN
Solar/Wind Harmer
19.749
961051AF2-396 GEN
Solar/Wind Harmer
9.185
274847GR RIDGE ;BU
Solar/Wind Harmer
6.292
971573AH1-285 GEN
Solar/Wind Harmer
10.643
970611AG2-400 GEN
Solar/Wind Harmer
12.36
274695ROCKY RD ;2P
Adder
13.72
274693ROCKY RD ;1P
Adder
13.585
274697ROCKY RD ;3P
Adder
3.727
274696ROCKY RD ;4P
Adder
14.044
958481AF2-142 GEN
Solar/Wind Harmer
18.473
274861TOP CROP ;1U
Solar/Wind Harmer
7.461
274862TOP CROP ;2U
Solar/Wind Harmer
6.23
274683WAUKEGAN ;8U
Adder
25.923
274683WAUKEGAN ;8U
Adder
21.852
962691AG1-118 GEN
Solar/Wind Harmer
36.835
970921AG2-575 GEN
Solar/Wind Harmer
12.262
970921AG2-575 GEN
Solar/Wind Harmer
2.852
958491AF2-143 GEN
Solar/Wind Harmer
18.361
274879MINONK ;1U
Solar/Wind Harmer
8.242
942991AE2-321 GEN
Solar/Wind Harmer
12.213
971333AH1-146 GEN
Solar/Wind Harmer
24.361
971335AH1-147 GEN
Solar/Wind Harmer
24.361
274764LEE CO EC;5U
Adder
11.204
274765LEE CO EC;6U
Adder
11.204
274762LEE CO EC;3U
Adder
11.177
274763LEE CO EC;4U
Adder
11.072
972267AH1-718 GEN
Adder
4.977
247621Y3-024
Adder
0.251
944201AF1-088_MTX
Adder
121.966
957141AF2-008_MTX
Adder
60.983
NYPJM->LTFIMP_NY
CLTF
3.9
LGEELTFEXP_LGEE->PJM
CLTF
6.008
WECLTFEXP_WEC->PJM
CLTF
4.622
AG2-052LTFEXP_AG2-052->PJM
LTF
0.285
AH1-155LTFEXP_AH1-155->PJM
LTF
0.428
CPLELTFEXP_CPLE->PJM
CLTF
3.266
CBM West 2LTFEXP_CBM-W2->PJM
CBM
123.696
LAGNLTFEXP_LAGN->PJM
CLTF
16.738
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.278
TVALTFEXP_TVA->PJM
CLTF
7.974
CBM West 1LTFEXP_CBM-W1->PJM
CBM
148.884
CBM South 1LTFEXP_CBM-S1->PJM
CBM
30.467
MECLTFEXP_MEC->PJM
CLTF
18.629
SIGELTFEXP_SIGE->PJM
CLTF
0.499

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o AP_P2-3_MP-500-021_SRT-SL


Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-021_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.17 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5474.49
MW Contribution:38.49
Bus #Bus NameTypeMW Contribution
24721805FLATG3
50/50
1.722
24721705FLATG2
50/50
31.565
24344105CKG2
50/50
10.234
962761AG1-125 GEN
Solar/Wind Harmer
88.274
970149AG2-104 GEN
Solar/Wind Harmer
109.018
970155AG2-107 GEN
Solar/Wind Harmer
38.491
970245AG2-165 GEN
Solar/Wind Harmer
23.775
972207SS24-0001
Solar/Wind Harmer
27.952
274773LINCOLN ;4U
Adder
7.862
274774LINCOLN ;5U
Adder
7.862
274723RIVER EC ;12
Adder
22.519
24639705ELKHART HY
Adder
0.193
276164X3-005 C
Solar/Wind Harmer
0.882
274751CRETE EC ;1U
Adder
6.133
274754CRETE EC ;4U
Adder
6.133
274812UNIV PK N;8U
Adder
6.271
270063AE2-323 C
Solar/Wind Harmer
2.759
270505AE1-170 C O1
Solar/Wind Harmer
18.777
276776AD2-060 GEN
Solar/Wind Harmer
0.528
274801UNIV PARK;4U
Adder
7.284
970373AG2-245 GEN
Solar/Wind Harmer
26.232
945111AF1-176 GEN
Solar/Wind Harmer
22.274
941551AE2-152 GEN
Solar/Wind Harmer
5.659
274676JOLIET 29;8U
Adder
38.193
274674JOLIET 9 ;6U
Adder
19.152
274732ELWOOD EC;7P
Adder
20.437
274871GR RIDGE ;2U
Solar/Wind Harmer
9.557
270449AD2-020 GEN
Solar/Wind Harmer
3.475
943021AE2-325 GEN
Solar/Wind Harmer
4.516
274745AC1-111 GEN9
Adder
6.925
270055AF2-134 C O1
Solar/Wind Harmer
3.751
965011AG1-365 GEN
Solar/Wind Harmer
12.349
276691AA1-018 GEN1
Solar/Wind Harmer
0.573
274682WAUKEGAN ;7U
Adder
22.105
274828WAUKEGAN ;BP
Adder
13.577
958381AF2-132 GEN
Solar/Wind Harmer
11.148
964861AG1-349 GEN
Solar/Wind Harmer
9.652
971917AH1-482 GEN
Solar/Wind Harmer
11.138
939401AE1-172 GEN
Solar/Wind Harmer
17.078
960751AF2-366 GEN
Solar/Wind Harmer
3.515
962781AG1-127 GEN
Solar/Wind Harmer
11.651
274872LEEDK;1U
Solar/Wind Harmer
10.051
276901AD2-066 C O1
Solar/Wind Harmer
4.296
971997AH1-543 GEN
Solar/Wind Harmer
19.204
276861AD2-134 GEN
Solar/Wind Harmer
2.175
274822ROCKFORD ;11
Adder
23.77
972235AH1-702 GEN1
Adder
3.049
274761LEE CO EC;2U
Adder
11.168
274766LEE CO EC;7U
Adder
11.036
940581AE2-045 GEN
Solar/Wind Harmer
2.565
971605AH1-302 GEN
Solar/Wind Harmer
2.193
24721605FLATG1
50/50
1.722
971599AH1-298 GEN
50/50
12.01
962771AG1-126 GEN
Solar/Wind Harmer
88.274
971347AH1-153 GEN
Solar/Wind Harmer
19.862
270071AF1-092 GEN
Solar/Wind Harmer
19.385
960681AF2-359 GEN
Solar/Wind Harmer
4.811
274775LINCOLN ;6U
Adder
7.862
274776LINCOLN ;7U
Adder
7.862
274777LINCOLN ;8U
Adder
7.862
971771AH1-392 GEN
Solar/Wind Harmer
11.413
971769AH1-391 GEN
Solar/Wind Harmer
12.662
24729505KEY G4
Adder
8.125
274814UNIV PK N;0U
Adder
6.326
274807UNIV PK N;3U
Adder
6.312
274805UNIV PK N;1U
Adder
6.285
274811UNIV PK N;7U
Adder
6.271
274827FISK ;RP
Adder
9.698
972037AH1-567 GEN1
Adder
0.229
960591AF2-350 GEN
Solar/Wind Harmer
12.499
972227AH1-698 GEN1
Adder
3.26
274687WILL CNTY;4U
Adder
34.801
274687WILL CNTY;4U
Adder
34.801
274675JOLIET 29;7U
Adder
38.193
274675JOLIET 29;7U
Adder
36.829
274731ELWOOD EC;2P
Adder
20.437
274733ELWOOD EC;3P
Adder
20.437
274735ELWOOD EC;4P
Adder
20.437
274728ELWOOD EC;5P
Adder
20.437
970833AG2-524 GEN
Solar/Wind Harmer
10.853
970833AG2-524 GEN
Solar/Wind Harmer
5.048
274746AC1-111 G10
Adder
6.925
274744AC1-111 GEN8
Adder
6.925
270536AF1-215 GEN2
Solar/Wind Harmer
5.627
944161AF1-084 GEN
Solar/Wind Harmer
2.725
958391AF2-133 GEN
Solar/Wind Harmer
11.104
276868AE1-113 GEN
Solar/Wind Harmer
12.351
276882AE2-255 GEN
Solar/Wind Harmer
4.117
971177AH1-047 GEN
Solar/Wind Harmer
7.149
971675AH1-338 GEN
Solar/Wind Harmer
21.917
971411AH1-196 GEN
Solar/Wind Harmer
18.262
274863CRW1-WTG
Solar/Wind Harmer
6.791
274864CRW2-WTG
Solar/Wind Harmer
6.791
274823ROCKFORD ;21
Adder
23.597
24722005FLATG5
50/50
1.722
24721905FLATG4
50/50
31.565
970153AG2-106 GEN
Solar/Wind Harmer
38.491
970513AG2-328 GEN
Solar/Wind Harmer
23.775
970517AG2-330 GEN
Solar/Wind Harmer
21.564
970349AG2-230 GEN
Solar/Wind Harmer
19.862
270043AE2-236 GEN
Solar/Wind Harmer
7.159
274772LINCOLN ;3U
Adder
7.862
944531AF1-118 GEN
Solar/Wind Harmer
44.374
247643Z2-116 C
Solar/Wind Harmer
0.088
274724RIVER EC ;11
Adder
22.259
24642205MAYFLWER
Adder
0.798
972231SS25-0005
Solar/Wind Harmer
11.908
972181SS23-001
Solar/Wind Harmer
7.442
274752CRETE EC ;2U
Adder
6.133
274753CRETE EC ;3U
Adder
6.133
970707AG2-453 GEN
Solar/Wind Harmer
35.123
274826FISK ;BP
Adder
13.684
274802UNIV PARK;5U
Adder
7.287
972228AH1-698 GEN2
Adder
4.63
276772AC2-154 GEN
Solar/Wind Harmer
3.486
276806AD2-047 C O1
Solar/Wind Harmer
13.371
970941AG2-585 GEN
Solar/Wind Harmer
15.624
274800UNIV PARK;3U
Adder
7.284
972038AH1-567 GEN2
Adder
0.456
945111AF1-176 GEN
Solar/Wind Harmer
7.059
276897AD1-100 C
Solar/Wind Harmer
36.209
939351AE1-166 GEN
Solar/Wind Harmer
7.399
970031AG2-029 GEN
Solar/Wind Harmer
37.394
274676JOLIET 29;8U
Adder
36.829
274729ELWOOD EC;1P
Adder
20.437
274730ELWOOD EC;6P
Adder
20.437
274734ELWOOD EC;8P
Adder
20.437
274736ELWOOD EC;9P
Adder
20.437
276893AG1-478 C
Solar/Wind Harmer
0.519
943121AE2-341 GEN
Solar/Wind Harmer
18.605
943591AF1-030 GEN
Solar/Wind Harmer
12.403
270535AF1-215 GEN1
Solar/Wind Harmer
5.627
959331AF2-224 GEN
Solar/Wind Harmer
12.349
965021AG1-366 GEN
Solar/Wind Harmer
2.872
276694AA1-018 GEN2
Solar/Wind Harmer
7.765
274682WAUKEGAN ;7U
Adder
22.105
964401AG1-302 GEN
Solar/Wind Harmer
11.148
274872LEEDK;1U
Solar/Wind Harmer
0.313
276805AD2-038 GEN
Solar/Wind Harmer
6.274
959141AF2-205 GEN
Solar/Wind Harmer
7.378
24441205WTRV SLR C
Solar/Wind Harmer
0.164
276799AD1-013 GEN
Solar/Wind Harmer
2.692
946671AF1-331 GEN
Solar/Wind Harmer
0.51
274855GSG-6 ;RU
Solar/Wind Harmer
4.497
274850MENDOTA H;RU
Solar/Wind Harmer
3.127
276602WESTBROOK C
Solar/Wind Harmer
2.588
276863AD2-134 GEN
Solar/Wind Harmer
2.175
972236AH1-702 GEN2
Adder
2.651
247604X1-042
Adder
0.502
274760LEE CO EC;1U
Adder
11.168
274767LEE CO EC;8U
Adder
11.036
24728705AND G3
Adder
5.245
270102X2-052 ST
50/50
2.043
270100X2-052 CT1
50/50
1.882
270101X2-052 CT2
50/50
1.882
970321AG2-212 GEN
Solar/Wind Harmer
23.775
965681AG1-436 GEN
Solar/Wind Harmer
15.919
965791AG1-447 GEN
Solar/Wind Harmer
8.144
274770LINCOLN ;1U
Adder
7.862
274771LINCOLN ;2U
Adder
7.862
270526AF1-158 GEN
Solar/Wind Harmer
5.755
24441505OLIV SLR
Solar/Wind Harmer
0.17
270216AD2-079_GEN
Solar/Wind Harmer
0.766
274808UNIV PK N;4U
Adder
6.244
957891AF2-083 GEN
Solar/Wind Harmer
4.22
972259AH1-714 GEN
Adder
23.87
960981AF2-389 GEN
Solar/Wind Harmer
1.891
247620Y3-023
Adder
0.576
274803UNIV PARK;6U
Adder
7.287
274888KELLY CRK;1U
Solar/Wind Harmer
7.379
274887GEN-1.85
Solar/Wind Harmer
6.662
276843GEN-1.7
Solar/Wind Harmer
0.717
958011AF2-095 GEN
Solar/Wind Harmer
17.999
274674JOLIET 9 ;6U
Adder
19.152
961051AF2-396 GEN
Solar/Wind Harmer
19.732
961051AF2-396 GEN
Solar/Wind Harmer
9.178
274847GR RIDGE ;BU
Solar/Wind Harmer
6.287
971573AH1-285 GEN
Solar/Wind Harmer
10.635
970611AG2-400 GEN
Solar/Wind Harmer
12.349
274695ROCKY RD ;2P
Adder
13.709
274693ROCKY RD ;1P
Adder
13.574
274697ROCKY RD ;3P
Adder
3.724
274696ROCKY RD ;4P
Adder
14.032
958481AF2-142 GEN
Solar/Wind Harmer
18.457
274861TOP CROP ;1U
Solar/Wind Harmer
7.454
274862TOP CROP ;2U
Solar/Wind Harmer
6.225
274683WAUKEGAN ;8U
Adder
25.901
274683WAUKEGAN ;8U
Adder
21.834
962691AG1-118 GEN
Solar/Wind Harmer
36.804
970921AG2-575 GEN
Solar/Wind Harmer
12.252
970921AG2-575 GEN
Solar/Wind Harmer
2.849
958491AF2-143 GEN
Solar/Wind Harmer
18.346
274879MINONK ;1U
Solar/Wind Harmer
8.235
942991AE2-321 GEN
Solar/Wind Harmer
12.203
971333AH1-146 GEN
Solar/Wind Harmer
24.34
971335AH1-147 GEN
Solar/Wind Harmer
24.34
274764LEE CO EC;5U
Adder
11.194
274765LEE CO EC;6U
Adder
11.194
274762LEE CO EC;3U
Adder
11.168
274763LEE CO EC;4U
Adder
11.063
972267AH1-718 GEN
Adder
4.973
247621Y3-024
Adder
0.251
944201AF1-088_MTX
Adder
121.843
957141AF2-008_MTX
Adder
60.922
NYPJM->LTFIMP_NY
CLTF
3.896
LGEELTFEXP_LGEE->PJM
CLTF
6
WECLTFEXP_WEC->PJM
CLTF
4.618
AG2-052LTFEXP_AG2-052->PJM
LTF
0.285
AH1-155LTFEXP_AH1-155->PJM
LTF
0.428
CPLELTFEXP_CPLE->PJM
CLTF
3.264
CBM West 2LTFEXP_CBM-W2->PJM
CBM
123.573
LAGNLTFEXP_LAGN->PJM
CLTF
16.721
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.266
TVALTFEXP_TVA->PJM
CLTF
7.965
CBM West 1LTFEXP_CBM-W1->PJM
CBM
148.738
CBM South 1LTFEXP_CBM-S1->PJM
CBM
30.434
MECLTFEXP_MEC->PJM
CLTF
18.612
SIGELTFEXP_SIGE->PJM
CLTF
0.498

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o AEP_P4_#37_05MOUNTN 765_B1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.15 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5473.55
MW Contribution:38.48
Bus #Bus NameTypeMW Contribution
24721805FLATG3
50/50
1.721
24721705FLATG2
50/50
31.554
24344105CKG2
50/50
10.231
962761AG1-125 GEN
Solar/Wind Harmer
88.258
970149AG2-104 GEN
Solar/Wind Harmer
108.998
970155AG2-107 GEN
Solar/Wind Harmer
38.484
970245AG2-165 GEN
Solar/Wind Harmer
23.767
972207SS24-0001
Solar/Wind Harmer
27.942
274773LINCOLN ;4U
Adder
7.859
274774LINCOLN ;5U
Adder
7.859
274723RIVER EC ;12
Adder
22.511
24639705ELKHART HY
Adder
0.193
276164X3-005 C
Solar/Wind Harmer
0.881
274751CRETE EC ;1U
Adder
6.131
274754CRETE EC ;4U
Adder
6.131
274812UNIV PK N;8U
Adder
6.269
270063AE2-323 C
Solar/Wind Harmer
2.758
270505AE1-170 C O1
Solar/Wind Harmer
18.77
276776AD2-060 GEN
Solar/Wind Harmer
0.528
274801UNIV PARK;4U
Adder
7.282
970373AG2-245 GEN
Solar/Wind Harmer
26.222
945111AF1-176 GEN
Solar/Wind Harmer
22.266
941551AE2-152 GEN
Solar/Wind Harmer
5.657
274676JOLIET 29;8U
Adder
38.179
274674JOLIET 9 ;6U
Adder
19.145
274732ELWOOD EC;7P
Adder
20.43
274871GR RIDGE ;2U
Solar/Wind Harmer
9.554
270449AD2-020 GEN
Solar/Wind Harmer
3.474
943021AE2-325 GEN
Solar/Wind Harmer
4.514
274745AC1-111 GEN9
Adder
6.922
270055AF2-134 C O1
Solar/Wind Harmer
3.749
965011AG1-365 GEN
Solar/Wind Harmer
12.344
276691AA1-018 GEN1
Solar/Wind Harmer
0.573
274682WAUKEGAN ;7U
Adder
22.097
274828WAUKEGAN ;BP
Adder
13.572
958381AF2-132 GEN
Solar/Wind Harmer
11.144
964861AG1-349 GEN
Solar/Wind Harmer
9.648
971917AH1-482 GEN
Solar/Wind Harmer
11.134
939401AE1-172 GEN
Solar/Wind Harmer
17.072
960751AF2-366 GEN
Solar/Wind Harmer
3.514
962781AG1-127 GEN
Solar/Wind Harmer
11.647
274872LEEDK;1U
Solar/Wind Harmer
10.048
276901AD2-066 C O1
Solar/Wind Harmer
4.294
971997AH1-543 GEN
Solar/Wind Harmer
19.196
276861AD2-134 GEN
Solar/Wind Harmer
2.174
274822ROCKFORD ;11
Adder
23.761
972235AH1-702 GEN1
Adder
3.048
274761LEE CO EC;2U
Adder
11.164
274766LEE CO EC;7U
Adder
11.032
940581AE2-045 GEN
Solar/Wind Harmer
2.564
971605AH1-302 GEN
Solar/Wind Harmer
2.192
24721605FLATG1
50/50
1.721
971599AH1-298 GEN
50/50
12.006
962771AG1-126 GEN
Solar/Wind Harmer
88.258
971347AH1-153 GEN
Solar/Wind Harmer
19.855
270071AF1-092 GEN
Solar/Wind Harmer
19.378
960681AF2-359 GEN
Solar/Wind Harmer
4.809
274775LINCOLN ;6U
Adder
7.859
274776LINCOLN ;7U
Adder
7.859
274777LINCOLN ;8U
Adder
7.859
971771AH1-392 GEN
Solar/Wind Harmer
11.409
971769AH1-391 GEN
Solar/Wind Harmer
12.658
24729505KEY G4
Adder
8.122
274814UNIV PK N;0U
Adder
6.324
274807UNIV PK N;3U
Adder
6.31
274805UNIV PK N;1U
Adder
6.283
274811UNIV PK N;7U
Adder
6.269
274827FISK ;RP
Adder
9.695
972037AH1-567 GEN1
Adder
0.229
960591AF2-350 GEN
Solar/Wind Harmer
12.495
972227AH1-698 GEN1
Adder
3.259
274687WILL CNTY;4U
Adder
34.788
274687WILL CNTY;4U
Adder
34.788
274675JOLIET 29;7U
Adder
38.179
274675JOLIET 29;7U
Adder
36.815
274731ELWOOD EC;2P
Adder
20.43
274733ELWOOD EC;3P
Adder
20.43
274735ELWOOD EC;4P
Adder
20.43
274728ELWOOD EC;5P
Adder
20.43
970833AG2-524 GEN
Solar/Wind Harmer
10.849
970833AG2-524 GEN
Solar/Wind Harmer
5.046
24722005FLATG5
50/50
1.721
24721905FLATG4
50/50
31.554
970153AG2-106 GEN
Solar/Wind Harmer
38.484
970513AG2-328 GEN
Solar/Wind Harmer
23.767
970517AG2-330 GEN
Solar/Wind Harmer
21.556
970349AG2-230 GEN
Solar/Wind Harmer
19.855
270043AE2-236 GEN
Solar/Wind Harmer
7.157
274772LINCOLN ;3U
Adder
7.859
944531AF1-118 GEN
Solar/Wind Harmer
44.357
247643Z2-116 C
Solar/Wind Harmer
0.088
274724RIVER EC ;11
Adder
22.251
24642205MAYFLWER
Adder
0.798
972231SS25-0005
Solar/Wind Harmer
11.904
972181SS23-001
Solar/Wind Harmer
7.44
274752CRETE EC ;2U
Adder
6.131
274753CRETE EC ;3U
Adder
6.131
970707AG2-453 GEN
Solar/Wind Harmer
35.11
274826FISK ;BP
Adder
13.679
274802UNIV PARK;5U
Adder
7.284
276772AC2-154 GEN
Solar/Wind Harmer
3.484
276806AD2-047 C O1
Solar/Wind Harmer
13.366
970941AG2-585 GEN
Solar/Wind Harmer
15.618
972228AH1-698 GEN2
Adder
4.628
274800UNIV PARK;3U
Adder
7.282
972038AH1-567 GEN2
Adder
0.456
945111AF1-176 GEN
Solar/Wind Harmer
7.057
276897AD1-100 C
Solar/Wind Harmer
36.196
939351AE1-166 GEN
Solar/Wind Harmer
7.396
970031AG2-029 GEN
Solar/Wind Harmer
37.38
274676JOLIET 29;8U
Adder
36.815
274729ELWOOD EC;1P
Adder
20.43
274730ELWOOD EC;6P
Adder
20.43
274734ELWOOD EC;8P
Adder
20.43
274736ELWOOD EC;9P
Adder
20.43
276893AG1-478 C
Solar/Wind Harmer
0.519
943121AE2-341 GEN
Solar/Wind Harmer
18.598
943591AF1-030 GEN
Solar/Wind Harmer
12.399
270535AF1-215 GEN1
Solar/Wind Harmer
5.625
959331AF2-224 GEN
Solar/Wind Harmer
12.344
965021AG1-366 GEN
Solar/Wind Harmer
2.871
276694AA1-018 GEN2
Solar/Wind Harmer
7.762
274682WAUKEGAN ;7U
Adder
22.097
964401AG1-302 GEN
Solar/Wind Harmer
11.144
274872LEEDK;1U
Solar/Wind Harmer
0.313
276805AD2-038 GEN
Solar/Wind Harmer
6.272
959141AF2-205 GEN
Solar/Wind Harmer
7.375
24441205WTRV SLR C
Solar/Wind Harmer
0.164
276799AD1-013 GEN
Solar/Wind Harmer
2.691
946671AF1-331 GEN
Solar/Wind Harmer
0.51
274855GSG-6 ;RU
Solar/Wind Harmer
4.495
274850MENDOTA H;RU
Solar/Wind Harmer
3.126
276602WESTBROOK C
Solar/Wind Harmer
2.587
276863AD2-134 GEN
Solar/Wind Harmer
2.174
972236AH1-702 GEN2
Adder
2.65
247604X1-042
Adder
0.502
274760LEE CO EC;1U
Adder
11.164
274767LEE CO EC;8U
Adder
11.032
24728705AND G3
Adder
5.242
274746AC1-111 G10
Adder
6.922
274744AC1-111 GEN8
Adder
6.922
270536AF1-215 GEN2
Solar/Wind Harmer
5.625
944161AF1-084 GEN
Solar/Wind Harmer
2.724
958391AF2-133 GEN
Solar/Wind Harmer
11.1
276868AE1-113 GEN
Solar/Wind Harmer
12.346
276882AE2-255 GEN
Solar/Wind Harmer
4.116
971177AH1-047 GEN
Solar/Wind Harmer
7.147
971675AH1-338 GEN
Solar/Wind Harmer
21.909
971411AH1-196 GEN
Solar/Wind Harmer
18.255
274863CRW1-WTG
Solar/Wind Harmer
6.789
274864CRW2-WTG
Solar/Wind Harmer
6.789
274823ROCKFORD ;21
Adder
23.589
270102X2-052 ST
50/50
2.042
270100X2-052 CT1
50/50
1.881
270101X2-052 CT2
50/50
1.881
970321AG2-212 GEN
Solar/Wind Harmer
23.767
965681AG1-436 GEN
Solar/Wind Harmer
15.913
965791AG1-447 GEN
Solar/Wind Harmer
8.141
274770LINCOLN ;1U
Adder
7.859
274771LINCOLN ;2U
Adder
7.859
270526AF1-158 GEN
Solar/Wind Harmer
5.753
24441505OLIV SLR
Solar/Wind Harmer
0.17
270216AD2-079_GEN
Solar/Wind Harmer
0.766
274808UNIV PK N;4U
Adder
6.241
957891AF2-083 GEN
Solar/Wind Harmer
4.219
972259AH1-714 GEN
Adder
23.861
960981AF2-389 GEN
Solar/Wind Harmer
1.89
247620Y3-023
Adder
0.576
274803UNIV PARK;6U
Adder
7.284
274888KELLY CRK;1U
Solar/Wind Harmer
7.377
274887GEN-1.85
Solar/Wind Harmer
6.66
276843GEN-1.7
Solar/Wind Harmer
0.717
958011AF2-095 GEN
Solar/Wind Harmer
17.992
274674JOLIET 9 ;6U
Adder
19.145
961051AF2-396 GEN
Solar/Wind Harmer
19.725
961051AF2-396 GEN
Solar/Wind Harmer
9.174
274847GR RIDGE ;BU
Solar/Wind Harmer
6.284
971573AH1-285 GEN
Solar/Wind Harmer
10.631
970611AG2-400 GEN
Solar/Wind Harmer
12.344
274695ROCKY RD ;2P
Adder
13.703
274693ROCKY RD ;1P
Adder
13.569
274697ROCKY RD ;3P
Adder
3.723
274696ROCKY RD ;4P
Adder
14.027
958481AF2-142 GEN
Solar/Wind Harmer
18.451
274861TOP CROP ;1U
Solar/Wind Harmer
7.451
274862TOP CROP ;2U
Solar/Wind Harmer
6.222
274683WAUKEGAN ;8U
Adder
25.892
274683WAUKEGAN ;8U
Adder
21.826
962691AG1-118 GEN
Solar/Wind Harmer
36.79
970921AG2-575 GEN
Solar/Wind Harmer
12.247
970921AG2-575 GEN
Solar/Wind Harmer
2.848
958491AF2-143 GEN
Solar/Wind Harmer
18.339
274879MINONK ;1U
Solar/Wind Harmer
8.232
942991AE2-321 GEN
Solar/Wind Harmer
12.198
971333AH1-146 GEN
Solar/Wind Harmer
24.331
971335AH1-147 GEN
Solar/Wind Harmer
24.331
274764LEE CO EC;5U
Adder
11.19
274765LEE CO EC;6U
Adder
11.19
274762LEE CO EC;3U
Adder
11.164
274763LEE CO EC;4U
Adder
11.058
972267AH1-718 GEN
Adder
4.971
247621Y3-024
Adder
0.251
944201AF1-088_MTX
Adder
121.789
957141AF2-008_MTX
Adder
60.895
NYPJM->LTFIMP_NY
CLTF
3.894
LGEELTFEXP_LGEE->PJM
CLTF
5.997
WECLTFEXP_WEC->PJM
CLTF
4.617
AG2-052LTFEXP_AG2-052->PJM
LTF
0.285
AH1-155LTFEXP_AH1-155->PJM
LTF
0.427
CPLELTFEXP_CPLE->PJM
CLTF
3.263
CBM West 2LTFEXP_CBM-W2->PJM
CBM
123.519
LAGNLTFEXP_LAGN->PJM
CLTF
16.714
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.261
TVALTFEXP_TVA->PJM
CLTF
7.962
CBM West 1LTFEXP_CBM-W1->PJM
CBM
148.673
CBM South 1LTFEXP_CBM-S1->PJM
CBM
30.42
MECLTFEXP_MEC->PJM
CLTF
18.605
SIGELTFEXP_SIGE->PJM
CLTF
0.498

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o AP_P1-3_MP-765-501T_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.8 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5417.86
MW Contribution:47.53
Bus #Bus NameTypeMW Contribution
24721805FLATG3
50/50
1.721
24721705FLATG2
50/50
31.554
24344105CKG2
50/50
10.231
962761AG1-125 GEN
Solar/Wind Harmer
74.429
970149AG2-104 GEN
Solar/Wind Harmer
80.386
970155AG2-107 GEN
Solar/Wind Harmer
47.528
970245AG2-165 GEN
Solar/Wind Harmer
4.024
274773LINCOLN ;4U
Adder
10.698
274774LINCOLN ;5U
Adder
10.698
274723RIVER EC ;12
Adder
22.511
24639705ELKHART HY
Adder
0.193
276164X3-005 C
Solar/Wind Harmer
0
274751CRETE EC ;1U
Adder
10.335
274754CRETE EC ;4U
Adder
10.335
274812UNIV PK N;8U
Adder
6.269
270063AE2-323 C
Solar/Wind Harmer
0.007
270505AE1-170 C O1
Solar/Wind Harmer
9.167
276776AD2-060 GEN
Solar/Wind Harmer
0.91
274801UNIV PARK;4U
Adder
7.282
970373AG2-245 GEN
Solar/Wind Harmer
18.295
945111AF1-176 GEN
Solar/Wind Harmer
15.535
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
38.179
274674JOLIET 9 ;6U
Adder
19.145
274732ELWOOD EC;7P
Adder
20.43
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
4.514
274745AC1-111 GEN9
Adder
6.922
270055AF2-134 C O1
Solar/Wind Harmer
0.007
965011AG1-365 GEN
Solar/Wind Harmer
8.612
276691AA1-018 GEN1
Solar/Wind Harmer
1.04
274682WAUKEGAN ;7U
Adder
22.097
274828WAUKEGAN ;BP
Adder
13.572
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.134
939401AE1-172 GEN
Solar/Wind Harmer
6.393
962781AG1-127 GEN
Solar/Wind Harmer
8.132
274872LEEDK;1U
Solar/Wind Harmer
0.005
276901AD2-066 C O1
Solar/Wind Harmer
0.008
971997AH1-543 GEN
Solar/Wind Harmer
4.464
276861AD2-134 GEN
Solar/Wind Harmer
0.152
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
10.6
957471AF2-041 GEN
Solar/Wind Harmer
25.388
959081AF2-199 GEN
Solar/Wind Harmer
8.463
971067AG2-660 GEN
Solar/Wind Harmer
2.821
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
274822ROCKFORD ;11
Adder
23.761
965651AG1-433 GEN
Solar/Wind Harmer
2.475
972235AH1-702 GEN1
Adder
3.048
970819AG2-516 GEN
Solar/Wind Harmer
10.106
970569AG2-363 GEN
Solar/Wind Harmer
25.226
971475AH1-234 GEN
Solar/Wind Harmer
4.081
24722005FLATG5
50/50
1.721
24721905FLATG4
50/50
31.554
970153AG2-106 GEN
Solar/Wind Harmer
47.528
970513AG2-328 GEN
Solar/Wind Harmer
4.024
970517AG2-330 GEN
Solar/Wind Harmer
24.143
970349AG2-230 GEN
Solar/Wind Harmer
13.852
270043AE2-236 GEN
Solar/Wind Harmer
5.825
274772LINCOLN ;3U
Adder
10.698
944531AF1-118 GEN
Solar/Wind Harmer
39.627
247643Z2-116 C
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
22.251
24642205MAYFLWER
Adder
0.798
274752CRETE EC ;2U
Adder
10.335
274753CRETE EC ;3U
Adder
10.335
970707AG2-453 GEN
Solar/Wind Harmer
28.578
274826FISK ;BP
Adder
13.679
274802UNIV PARK;5U
Adder
7.284
276806AD2-047 C O1
Solar/Wind Harmer
4.94
970941AG2-585 GEN
Solar/Wind Harmer
10.896
972228AH1-698 GEN2
Adder
4.628
274800UNIV PARK;3U
Adder
7.282
972038AH1-567 GEN2
Adder
0.456
945111AF1-176 GEN
Solar/Wind Harmer
7.057
276897AD1-100 C
Solar/Wind Harmer
0.012
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
970031AG2-029 GEN
Solar/Wind Harmer
5.65
274676JOLIET 29;8U
Adder
36.815
274729ELWOOD EC;1P
Adder
20.43
274730ELWOOD EC;6P
Adder
20.43
274734ELWOOD EC;8P
Adder
20.43
274736ELWOOD EC;9P
Adder
20.43
276893AG1-478 C
Solar/Wind Harmer
0.344
943121AE2-341 GEN
Solar/Wind Harmer
14.504
943591AF1-030 GEN
Solar/Wind Harmer
9.645
270535AF1-215 GEN1
Solar/Wind Harmer
0.011
959331AF2-224 GEN
Solar/Wind Harmer
6.029
965021AG1-366 GEN
Solar/Wind Harmer
2.871
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
22.097
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.313
276805AD2-038 GEN
Solar/Wind Harmer
0.002
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
24441205WTRV SLR C
Solar/Wind Harmer
0
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.906
274855GSG-6 ;RU
Solar/Wind Harmer
0.311
274850MENDOTA H;RU
Solar/Wind Harmer
0.1
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.152
959091AF2-200 GEN
Solar/Wind Harmer
16.925
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
2.65
247604X1-042
Adder
0.502
970571AG2-364 GEN
Solar/Wind Harmer
16.817
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
11.164
274767LEE CO EC;8U
Adder
11.032
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
8.324
276157O29GEN1
Solar/Wind Harmer
1.345
274878BISHOP HL;2U
Solar/Wind Harmer
0.279
942111AE2-223 GEN
Solar/Wind Harmer
2.687
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
24.591
959611AF2-252 GEN
Solar/Wind Harmer
2.732
965931AG1-462 GEN
Solar/Wind Harmer
20.863
247642Z2-115 C
Solar/Wind Harmer
0.003
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
3.685
276668AB2-070 GEN1
Solar/Wind Harmer
0.291
970289AG2-191 GEN
Solar/Wind Harmer
0.875
970291AG2-192 GEN
Solar/Wind Harmer
0.796
276621W2-048 GEN
Solar/Wind Harmer
0.399
276838X2-022 GEN2
Solar/Wind Harmer
0.445
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.051
942481AE2-261 GEN
Solar/Wind Harmer
23.26
958821AF2-173 GEN
Solar/Wind Harmer
10.805
270004AE1-209 GEN
Solar/Wind Harmer
1.672
971617AH1-308 GEN
Solar/Wind Harmer
6.396
970193AG2-126 GEN
Solar/Wind Harmer
11.433
946031AF1-268 GEN
Solar/Wind Harmer
7.175
970243AG2-164 GEN
Solar/Wind Harmer
1.523
970519AG2-331 GEN
Solar/Wind Harmer
6.77
970699AG2-449 GEN
Solar/Wind Harmer
0.651
24721605FLATG1
50/50
1.721
971599AH1-298 GEN
50/50
12.006
962771AG1-126 GEN
Solar/Wind Harmer
74.429
971347AH1-153 GEN
Solar/Wind Harmer
13.852
270071AF1-092 GEN
Solar/Wind Harmer
17.275
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
274775LINCOLN ;6U
Adder
10.698
274776LINCOLN ;7U
Adder
10.698
274777LINCOLN ;8U
Adder
10.698
971771AH1-392 GEN
Solar/Wind Harmer
8.844
971769AH1-391 GEN
Solar/Wind Harmer
9.861
24729505KEY G4
Adder
8.122
274814UNIV PK N;0U
Adder
6.324
274807UNIV PK N;3U
Adder
6.31
274805UNIV PK N;1U
Adder
6.283
274811UNIV PK N;7U
Adder
6.269
971619AH1-309 GEN
Solar/Wind Harmer
3.929
274827FISK ;RP
Adder
9.695
972037AH1-567 GEN1
Adder
0.229
960591AF2-350 GEN
Solar/Wind Harmer
8.717
972227AH1-698 GEN1
Adder
3.259
274687WILL CNTY;4U
Adder
34.788
274687WILL CNTY;4U
Adder
34.788
274675JOLIET 29;7U
Adder
38.179
274675JOLIET 29;7U
Adder
36.815
274731ELWOOD EC;2P
Adder
20.43
274733ELWOOD EC;3P
Adder
20.43
274735ELWOOD EC;4P
Adder
20.43
274728ELWOOD EC;5P
Adder
20.43
970833AG2-524 GEN
Solar/Wind Harmer
9.537
970833AG2-524 GEN
Solar/Wind Harmer
6.358
274746AC1-111 G10
Adder
6.922
274744AC1-111 GEN8
Adder
6.922
270536AF1-215 GEN2
Solar/Wind Harmer
0.011
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.708
276882AE2-255 GEN
Solar/Wind Harmer
0.995
971177AH1-047 GEN
Solar/Wind Harmer
5.247
971675AH1-338 GEN
Solar/Wind Harmer
3.312
971411AH1-196 GEN
Solar/Wind Harmer
12.736
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
971611AH1-305 GEN
Solar/Wind Harmer
5.049
971171AH1-044 GEN
Solar/Wind Harmer
16.925
274823ROCKFORD ;21
Adder
23.589
970169AG2-114 GEN
Solar/Wind Harmer
8.416
276612AE2-035 GEN
Solar/Wind Harmer
0.002
926823AC1-168 GEN
Solar/Wind Harmer
1.43
971681AH1-341 GEN
Solar/Wind Harmer
13.508
961011AF2-392 GEN
Solar/Wind Harmer
4.894
965101AG1-375 GEN
Solar/Wind Harmer
8.339
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
957751AF2-069 GEN
Solar/Wind Harmer
0.274
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
8.681
941731AE2-173 GEN
Solar/Wind Harmer
6.89
946321AF1-296 GEN
Solar/Wind Harmer
4.595
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
945581AF1-223 GEN
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
10.958
963841AG1-237 GEN
Solar/Wind Harmer
3.497
965041AG1-368 GEN
Solar/Wind Harmer
8.037
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.291
276848AB2-070 GEN3
Solar/Wind Harmer
0.289
970289AG2-191 GEN
Solar/Wind Harmer
1.512
971549AH1-272 GEN
Solar/Wind Harmer
16.344
971609AH1-304 GEN
Solar/Wind Harmer
1.291
270594AE1-207 GEN
Solar/Wind Harmer
8.813
965051AG1-369 GEN
Solar/Wind Harmer
3.913
270284AF1-227 GEN1
Solar/Wind Harmer
0.01
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
270024AE2-089 GEN
Solar/Wind Harmer
0.008
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
944221AF1-090 GEN
Solar/Wind Harmer
4.485
970115AG2-085 GEN
Solar/Wind Harmer
3.056
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
11.164
274766LEE CO EC;7U
Adder
11.032
958861AF2-177 GEN
Solar/Wind Harmer
3.614
24791305MDL-5G
Solar/Wind Harmer
0.001
276158O29GEN2
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.279
270349AD2-093_GEN
Solar/Wind Harmer
0.006
276726Z2-087_GEN
Solar/Wind Harmer
0.003
939741AE1-205 GEN
Solar/Wind Harmer
11.575
274854TWINGROVE;U2
Solar/Wind Harmer
0.004
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
945371AF1-202 GEN
Solar/Wind Harmer
0.001
972175AH1-670 GEN
Solar/Wind Harmer
6.679
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
18.86
970291AG2-192 GEN
Solar/Wind Harmer
1.034
963831AG1-236 GEN
Solar/Wind Harmer
3.102
276615X2-022 GEN
Solar/Wind Harmer
0.083
270032AE2-172
Solar/Wind Harmer
5.246
247521TR3_G114
Solar/Wind Harmer
0.286
270246TR4_N_V150
Solar/Wind Harmer
0.051
965911AG1-460 GEN
Solar/Wind Harmer
1.556
276903AD2-071 C
Solar/Wind Harmer
8.661
270005AE1-210 C O1
Solar/Wind Harmer
1.672
965031AG1-367 GEN
Solar/Wind Harmer
7.718
944231AF1-091 GEN
Solar/Wind Harmer
2.052
24695305TIMB G C
Solar/Wind Harmer
0.002
970825AG2-519 GEN
Solar/Wind Harmer
2.704
970333AG2-219 GEN
Solar/Wind Harmer
1.862
270102X2-052 ST
50/50
2.042
270100X2-052 CT1
50/50
1.881
270101X2-052 CT2
50/50
1.881
970321AG2-212 GEN
Solar/Wind Harmer
4.024
965681AG1-436 GEN
Solar/Wind Harmer
11.102
965791AG1-447 GEN
Solar/Wind Harmer
8.141
274770LINCOLN ;1U
Adder
10.698
274771LINCOLN ;2U
Adder
10.698
270526AF1-158 GEN
Solar/Wind Harmer
0.011
24441505OLIV SLR
Solar/Wind Harmer
0
270216AD2-079_GEN
Solar/Wind Harmer
0.001
274808UNIV PK N;4U
Adder
6.241
957891AF2-083 GEN
Solar/Wind Harmer
0.001
972259AH1-714 GEN
Adder
23.861
247620Y3-023
Adder
0.576
274803UNIV PARK;6U
Adder
7.284
274888KELLY CRK;1U
Solar/Wind Harmer
0.512
274887GEN-1.85
Solar/Wind Harmer
0.23
276843GEN-1.7
Solar/Wind Harmer
0.282
958011AF2-095 GEN
Solar/Wind Harmer
12.553
274674JOLIET 9 ;6U
Adder
19.145
961051AF2-396 GEN
Solar/Wind Harmer
17.339
961051AF2-396 GEN
Solar/Wind Harmer
11.56
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
971573AH1-285 GEN
Solar/Wind Harmer
1.607
970611AG2-400 GEN
Solar/Wind Harmer
8.612
970627AG2-408 GEN
Solar/Wind Harmer
2.584
274695ROCKY RD ;2P
Adder
13.703
274693ROCKY RD ;1P
Adder
13.569
274697ROCKY RD ;3P
Adder
3.723
274696ROCKY RD ;4P
Adder
14.027
958481AF2-142 GEN
Solar/Wind Harmer
12.872
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
1.161
274683WAUKEGAN ;8U
Adder
25.892
274683WAUKEGAN ;8U
Adder
21.826
962691AG1-118 GEN
Solar/Wind Harmer
25.667
970921AG2-575 GEN
Solar/Wind Harmer
8.545
970921AG2-575 GEN
Solar/Wind Harmer
2.848
958491AF2-143 GEN
Solar/Wind Harmer
12.795
274879MINONK ;1U
Solar/Wind Harmer
0.359
942991AE2-321 GEN
Solar/Wind Harmer
9.503
971333AH1-146 GEN
Solar/Wind Harmer
16.975
971335AH1-147 GEN
Solar/Wind Harmer
16.975
971341AH1-150 GEN
Solar/Wind Harmer
16.925
971343AH1-151 GEN
Solar/Wind Harmer
16.925
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
944541AF1-119 GEN
Solar/Wind Harmer
0.565
960971AF2-388 GEN
Solar/Wind Harmer
4.95
274856ECOGROVE ;U1
Solar/Wind Harmer
0.198
276611AD2-172 GEN
Solar/Wind Harmer
0.002
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
938861AE1-114 GEN
Solar/Wind Harmer
4.753
274764LEE CO EC;5U
Adder
11.19
274765LEE CO EC;6U
Adder
11.19
274762LEE CO EC;3U
Adder
11.164
274763LEE CO EC;4U
Adder
11.058
276603SUBLETTE C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
4.971
276741O09 GEN1
Solar/Wind Harmer
0.296
276708O09 GEN2
Solar/Wind Harmer
0.296
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.327
276646AC1-214 GEN2
Solar/Wind Harmer
0.327
276782AC1-033 GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.006
960611AF2-352 GEN
Solar/Wind Harmer
2.732
966841AG1-555 GEN
Solar/Wind Harmer
0.926
942221AE2-234 GEN
Solar/Wind Harmer
0.041
970241AG2-163 GEN
Solar/Wind Harmer
4.649
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
270599AE1-208 GEN
Solar/Wind Harmer
7.244
270031AE2-169
Solar/Wind Harmer
4.346
971613AH1-306 GEN
Solar/Wind Harmer
3.777
276916AD2-100_GEN
Solar/Wind Harmer
16.273
276911AD2-131_GEN
Solar/Wind Harmer
1.072
960441AF2-335 GEN
Solar/Wind Harmer
7.639
945391AF1-204 GEN
Solar/Wind Harmer
8.098
970825AG2-519 GEN
Solar/Wind Harmer
8.443
970239AG2-162 GEN
Solar/Wind Harmer
0.651
944201AF1-088_MTX
Adder
121.789
957141AF2-008_MTX
Adder
33.652
NYPJM->LTFIMP_NY
CLTF
3.894
LGEELTFEXP_LGEE->PJM
CLTF
5.997
WECLTFEXP_WEC->PJM
CLTF
4.617
AG2-052LTFEXP_AG2-052->PJM
LTF
0.285
AH1-155LTFEXP_AH1-155->PJM
LTF
0.427
CPLELTFEXP_CPLE->PJM
CLTF
3.263
CBM West 2LTFEXP_CBM-W2->PJM
CBM
123.519
LAGNLTFEXP_LAGN->PJM
CLTF
16.714
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.261
TVALTFEXP_TVA->PJM
CLTF
7.962
CBM West 1LTFEXP_CBM-W1->PJM
CBM
148.673
CBM South 1LTFEXP_CBM-S1->PJM
CBM
30.42
MECLTFEXP_MEC->PJM
CLTF
18.605
SIGELTFEXP_SIGE->PJM
CLTF
0.498

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o AEP_P4_#706_05GAVIN 765_C1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#706_05GAVIN 765_C1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.53 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4826.48
MW Contribution:56.64
Bus #Bus NameTypeMW Contribution
24722005FLATG5
50/50
4.694
24721905FLATG4
50/50
86.059
270475AD2-096_GEN
50/50
10.488
270142AC1-141 CT1_
50/50
3.444
24641605TWIN BRNCH
50/50
0.025
24344005CKG1
50/50
9.376
24642205MAYFLWER
50/50
0.961
944961AF1-161 GEN
50/50
4.122
24721605FLATG1
50/50
4.694
971599AH1-298 GEN
50/50
14.063
270144AC1-141 ST1_
50/50
3.051
24653605MOTTVILLE
50/50
0.005
24643105BUCHANAN
50/50
0.018
270036AE2-216 BAT
50/50
8.975
962771AG1-126 GEN
Solar/Wind Harmer
129.902
270284AF1-227 GEN1
Solar/Wind Harmer
9.474
270286AF1-227 GEN2
Solar/Wind Harmer
3.505
270287AF1-227 GEN3
Solar/Wind Harmer
3.505
971347AH1-153 GEN
Solar/Wind Harmer
22.443
270578AF1-285 GEN2
Solar/Wind Harmer
0.683
270071AF1-092 GEN
Solar/Wind Harmer
21.965
971771AH1-392 GEN
Solar/Wind Harmer
12.923
971769AH1-391 GEN
Solar/Wind Harmer
14.204
960681AF2-359 GEN
Solar/Wind Harmer
5.35
944161AF1-084 GEN
Solar/Wind Harmer
3.119
270302AB2-170 GEN
Solar/Wind Harmer
11.755
270317AD1-130_GEN
Solar/Wind Harmer
4.507
24729505KEY G4
Adder
9.092
965041AG1-368 GEN
Solar/Wind Harmer
13.959
274775LINCOLN ;6U
Adder
8.527
274776LINCOLN ;7U
Adder
8.527
274777LINCOLN ;8U
Adder
8.527
965051AG1-369 GEN
Solar/Wind Harmer
6.856
274814UNIV PK N;0U
Adder
6.852
274807UNIV PK N;3U
Adder
6.837
274805UNIV PK N;1U
Adder
6.807
274811UNIV PK N;7U
Adder
6.792
972037AH1-567 GEN1
Adder
0.247
274827FISK ;RP
Adder
10.465
960591AF2-350 GEN
Solar/Wind Harmer
13.475
972227AH1-698 GEN1
Adder
3.512
957201AF2-014 GEN
Solar/Wind Harmer
6.1
270435AC2-044 GEN
Solar/Wind Harmer
2.69
963791AG1-232 GEN
Solar/Wind Harmer
18.134
274687WILL CNTY;4U
Adder
37.406
274687WILL CNTY;4U
Adder
37.406
274675JOLIET 29;7U
Adder
41.022
274675JOLIET 29;7U
Adder
39.557
270536AF1-215 GEN2
Solar/Wind Harmer
6.069
274731ELWOOD EC;2P
Adder
21.93
274733ELWOOD EC;3P
Adder
21.93
274735ELWOOD EC;4P
Adder
21.93
274728ELWOOD EC;5P
Adder
21.93
970833AG2-524 GEN
Solar/Wind Harmer
11.63
970833AG2-524 GEN
Solar/Wind Harmer
5.409
971549AH1-272 GEN
Solar/Wind Harmer
24.604
958711AF2-162 GEN
Solar/Wind Harmer
1.345
274746AC1-111 G10
Adder
7.401
274744AC1-111 GEN8
Adder
7.401
965101AG1-375 GEN
Solar/Wind Harmer
13.06
958391AF2-133 GEN
Solar/Wind Harmer
11.816
274823ROCKFORD ;21
Adder
24.797
962601AG1-109 GEN
50/50
4.122
970153AG2-106 GEN
Solar/Wind Harmer
56.644
270043AE2-236 GEN
Solar/Wind Harmer
8.306
970349AG2-230 GEN
Solar/Wind Harmer
22.443
959331AF2-224 GEN
Solar/Wind Harmer
14.786
965021AG1-366 GEN
Solar/Wind Harmer
3.439
942871AE2-306 GEN
Solar/Wind Harmer
1.331
270391AF1-285 GEN3
Solar/Wind Harmer
0.683
970513AG2-328 GEN
Solar/Wind Harmer
26.004
970517AG2-330 GEN
Solar/Wind Harmer
23.585
970031AG2-029 GEN
Solar/Wind Harmer
43.335
247643Z2-116 C
Solar/Wind Harmer
0.101
944531AF1-118 GEN
Solar/Wind Harmer
49.96
945111AF1-176 GEN
Solar/Wind Harmer
8.066
270485AE1-090_GEN
Solar/Wind Harmer
0.85
24441205WTRV SLR C
Solar/Wind Harmer
0.189
247604X1-042
Adder
0.578
274772LINCOLN ;3U
Adder
8.527
270191TR4_S_V150
Solar/Wind Harmer
4.119
270247TR4_N_V136
Solar/Wind Harmer
1.168
274724RIVER EC ;11
Adder
24.177
972231SS25-0005
Solar/Wind Harmer
12.946
972181SS23-001
Solar/Wind Harmer
8.091
274752CRETE EC ;2U
Adder
6.668
274753CRETE EC ;3U
Adder
6.668
970707AG2-453 GEN
Solar/Wind Harmer
37.832
274802UNIV PARK;5U
Adder
7.866
274826FISK ;BP
Adder
14.766
276772AC2-154 GEN
Solar/Wind Harmer
3.758
276806AD2-047 C O1
Solar/Wind Harmer
14.415
970941AG2-585 GEN
Solar/Wind Harmer
16.843
274800UNIV PARK;3U
Adder
7.856
972038AH1-567 GEN2
Adder
0.492
972228AH1-698 GEN2
Adder
4.987
270491AE1-102 GEN2
Solar/Wind Harmer
1.748
276897AD1-100 C
Solar/Wind Harmer
38.911
939351AE1-166 GEN
Solar/Wind Harmer
7.95
274676JOLIET 29;8U
Adder
39.557
270535AF1-215 GEN1
Solar/Wind Harmer
6.069
274729ELWOOD EC;1P
Adder
21.93
274730ELWOOD EC;6P
Adder
21.93
274734ELWOOD EC;8P
Adder
21.93
274736ELWOOD EC;9P
Adder
21.93
276893AG1-478 C
Solar/Wind Harmer
0.557
943121AE2-341 GEN
Solar/Wind Harmer
19.89
943591AF1-030 GEN
Solar/Wind Harmer
13.26
964401AG1-302 GEN
Solar/Wind Harmer
11.919
276694AA1-018 GEN2
Solar/Wind Harmer
8.271
274682WAUKEGAN ;7U
Adder
23.511
972236AH1-702 GEN2
Adder
2.783
274760LEE CO EC;1U
Adder
11.654
274767LEE CO EC;8U
Adder
11.517
24728705AND G3
Adder
7.997
24728505AND G1
Adder
3.824
970615AG2-402 GEN
50/50
3.439
247620Y3-023
50/50
0.701
270102X2-052 ST
50/50
2.279
270100X2-052 CT1
50/50
2.1
270101X2-052 CT2
50/50
2.1
270471AD2-092_GEN
Solar/Wind Harmer
6.554
970611AG2-400 GEN
Solar/Wind Harmer
14.786
270224U2-072_GEN2
Solar/Wind Harmer
2.903
270227U2-072_GEN3
Solar/Wind Harmer
2.903
270228U2-072_GEN4
Solar/Wind Harmer
2.903
270231U2-072_GEN5
Solar/Wind Harmer
2.903
970321AG2-212 GEN
Solar/Wind Harmer
26.004
270216AD2-079_GEN
Solar/Wind Harmer
0.873
957891AF2-083 GEN
Solar/Wind Harmer
4.815
960981AF2-389 GEN
Solar/Wind Harmer
2.158
270526AF1-158 GEN
Solar/Wind Harmer
6.468
961051AF2-396 GEN
Solar/Wind Harmer
22.558
961051AF2-396 GEN
Solar/Wind Harmer
10.492
24441505OLIV SLR
Solar/Wind Harmer
0.19
965681AG1-436 GEN
Solar/Wind Harmer
17.703
965791AG1-447 GEN
Solar/Wind Harmer
9.057
274770LINCOLN ;1U
Adder
8.527
274771LINCOLN ;2U
Adder
8.527
274808UNIV PK N;4U
Adder
6.763
274803UNIV PARK;6U
Adder
7.866
274888KELLY CRK;1U
Solar/Wind Harmer
7.955
274887GEN-1.85
Solar/Wind Harmer
7.182
276843GEN-1.7
Solar/Wind Harmer
0.773
958011AF2-095 GEN
Solar/Wind Harmer
19.404
972259AH1-714 GEN
Adder
25.697
246938BC-WTG3
Solar/Wind Harmer
5.354
246937BC-WTG2
Solar/Wind Harmer
5.263
274674JOLIET 9 ;6U
Adder
20.555
274847GR RIDGE ;BU
Solar/Wind Harmer
6.735
944541AF1-119 GEN
Solar/Wind Harmer
5.569
960971AF2-388 GEN
Solar/Wind Harmer
14.532
971573AH1-285 GEN
Solar/Wind Harmer
11.345
958481AF2-142 GEN
Solar/Wind Harmer
19.659
274696ROCKY RD ;4P
Adder
14.93
274695ROCKY RD ;2P
Adder
14.586
274693ROCKY RD ;1P
Adder
14.442
274697ROCKY RD ;3P
Adder
3.962
274861TOP CROP ;1U
Solar/Wind Harmer
7.938
274862TOP CROP ;2U
Solar/Wind Harmer
6.628
274683WAUKEGAN ;8U
Adder
27.535
274683WAUKEGAN ;8U
Adder
23.211
962691AG1-118 GEN
Solar/Wind Harmer
39.042
942221AE2-234 GEN
Solar/Wind Harmer
0.953
274764LEE CO EC;5U
Adder
11.682
274765LEE CO EC;6U
Adder
11.682
274762LEE CO EC;3U
Adder
11.654
274763LEE CO EC;4U
Adder
11.544
972267AH1-718 GEN
Adder
5.169
247621Y3-024
Adder
0.268
970921AG2-575 GEN
Solar/Wind Harmer
11.763
970921AG2-575 GEN
Solar/Wind Harmer
2.735
24721805FLATG3
50/50
4.694
24721705FLATG2
50/50
86.059
24344105CKG2
50/50
11.607
270143AC1-141 CT2_
50/50
3.444
24639705ELKHART HY
50/50
0.234
970521AG2-332 GEN
50/50
16.668
24307105BERRINSP G
50/50
0.031
962761AG1-125 GEN
Solar/Wind Harmer
129.902
970149AG2-104 GEN
Solar/Wind Harmer
160.43
970155AG2-107 GEN
Solar/Wind Harmer
56.644
270349AD2-093_GEN
Solar/Wind Harmer
6.554
965011AG1-365 GEN
Solar/Wind Harmer
14.786
270223U2-072_GEN1
Solar/Wind Harmer
2.903
270578AF1-285 GEN2
Solar/Wind Harmer
1.775
270391AF1-285 GEN3
Solar/Wind Harmer
1.775
970245AG2-165 GEN
Solar/Wind Harmer
26.004
270063AE2-323 C
Solar/Wind Harmer
3.194
270505AE1-170 C O1
Solar/Wind Harmer
21.434
945111AF1-176 GEN
Solar/Wind Harmer
25.451
270449AD2-020 GEN
Solar/Wind Harmer
3.975
943021AE2-325 GEN
Solar/Wind Harmer
5.164
270462AD2-086
Solar/Wind Harmer
9.779
972207SS24-0001
Solar/Wind Harmer
30.317
274773LINCOLN ;4U
Adder
8.527
274774LINCOLN ;5U
Adder
8.527
247521TR3_G114
Solar/Wind Harmer
4.617
270246TR4_N_V150
Solar/Wind Harmer
1.168
274723RIVER EC ;12
Adder
24.46
274751CRETE EC ;1U
Adder
6.668
274754CRETE EC ;4U
Adder
6.668
970373AG2-245 GEN
Solar/Wind Harmer
28.573
276164X3-005 C
Solar/Wind Harmer
0.955
965421AG1-410 GEN
Solar/Wind Harmer
40.731
274812UNIV PK N;8U
Adder
6.792
24695305TIMB G C
Solar/Wind Harmer
7.439
276776AD2-060 GEN
Solar/Wind Harmer
0.57
274801UNIV PARK;4U
Adder
7.856
246936BC-WTG1
Solar/Wind Harmer
5.263
270489AE1-102 GEN1
Solar/Wind Harmer
1.748
941551AE2-152 GEN
Solar/Wind Harmer
6.081
944231AF1-091 GEN
Solar/Wind Harmer
5.048
274676JOLIET 29;8U
Adder
41.022
270055AF2-134 C O1
Solar/Wind Harmer
4.045
274674JOLIET 9 ;6U
Adder
20.555
274732ELWOOD EC;7P
Adder
21.93
274871GR RIDGE ;2U
Solar/Wind Harmer
10.239
965651AG1-433 GEN
Solar/Wind Harmer
7.266
274745AC1-111 GEN9
Adder
7.401
958381AF2-132 GEN
Solar/Wind Harmer
11.919
964861AG1-349 GEN
Solar/Wind Harmer
10.309
971917AH1-482 GEN
Solar/Wind Harmer
11.896
276691AA1-018 GEN1
Solar/Wind Harmer
0.61
274682WAUKEGAN ;7U
Adder
23.511
274828WAUKEGAN ;BP
Adder
14.433
958861AF2-177 GEN
Solar/Wind Harmer
14.275
274822ROCKFORD ;11
Adder
24.978
972235AH1-702 GEN1
Adder
3.201
274761LEE CO EC;2U
Adder
11.654
274766LEE CO EC;7U
Adder
11.517
24728605AND G2
Adder
3.824
960751AF2-366 GEN
Solar/Wind Harmer
3.375
962781AG1-127 GEN
Solar/Wind Harmer
11.186
944201AF1-088_MTX
Adder
108.034
957141AF2-008_MTX
Adder
1.852
NYPJM->LTFIMP_NY
CLTF
3.072
LGEELTFEXP_LGEE->PJM
CLTF
4.553
WECLTFEXP_WEC->PJM
CLTF
4.843
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.157
AG2-052LTFEXP_AG2-052->PJM
LTF
0.305
AH1-155LTFEXP_AH1-155->PJM
LTF
0.457
CBM West 2LTFEXP_CBM-W2->PJM
CBM
98.823
LAGNLTFEXP_LAGN->PJM
CLTF
11.481
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.982
TVALTFEXP_TVA->PJM
CLTF
4.813
CBM West 1LTFEXP_CBM-W1->PJM
CBM
159.327
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.302
MECLTFEXP_MEC->PJM
CLTF
18.121
SIGELTFEXP_SIGE->PJM
CLTF
0.416

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o AEP_P2-2_#8072_05MARYSV 765_2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#8072_05MARYSV 765_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:114.32 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4735.25
MW Contribution:43.7
Bus #Bus NameTypeMW Contribution
971599AH1-298 GEN
50/50
10.477
24721605FLATG1
50/50
1.323
962771AG1-126 GEN
Solar/Wind Harmer
100.225
971347AH1-153 GEN
Solar/Wind Harmer
17.482
960681AF2-359 GEN
Solar/Wind Harmer
4.148
274775LINCOLN ;6U
Adder
6.778
274776LINCOLN ;7U
Adder
6.778
274777LINCOLN ;8U
Adder
6.778
971771AH1-392 GEN
Solar/Wind Harmer
9.803
971769AH1-391 GEN
Solar/Wind Harmer
10.885
270071AF1-092 GEN
Solar/Wind Harmer
16.225
274814UNIV PK N;0U
Adder
5.412
274807UNIV PK N;3U
Adder
5.4
274805UNIV PK N;1U
Adder
5.376
274811UNIV PK N;7U
Adder
5.365
274827FISK ;RP
Adder
8.294
972227AH1-698 GEN1
Adder
2.788
960591AF2-350 GEN
Solar/Wind Harmer
10.687
972037AH1-567 GEN1
Adder
0.196
274687WILL CNTY;4U
Adder
29.717
274687WILL CNTY;4U
Adder
29.717
274675JOLIET 29;7U
Adder
32.609
274675JOLIET 29;7U
Adder
31.444
274728ELWOOD EC;5P
Adder
17.435
274731ELWOOD EC;2P
Adder
17.435
274733ELWOOD EC;3P
Adder
17.435
274735ELWOOD EC;4P
Adder
17.435
970833AG2-524 GEN
Solar/Wind Harmer
9.26
970833AG2-524 GEN
Solar/Wind Harmer
4.307
274746AC1-111 G10
Adder
5.903
274744AC1-111 GEN8
Adder
5.903
944161AF1-084 GEN
Solar/Wind Harmer
2.321
270536AF1-215 GEN2
Solar/Wind Harmer
4.747
971177AH1-047 GEN
Solar/Wind Harmer
6.051
276868AE1-113 GEN
Solar/Wind Harmer
10.439
276882AE2-255 GEN
Solar/Wind Harmer
3.48
971675AH1-338 GEN
Solar/Wind Harmer
18.533
971411AH1-196 GEN
Solar/Wind Harmer
15.443
24729505KEY G4
Adder
6.664
274823ROCKFORD ;21
Adder
19.907
270054AF2-122 C O1
Solar/Wind Helper
1.49
971171AH1-044 GEN
Solar/Wind Harmer
15.497
24722005FLATG5
50/50
1.323
24721905FLATG4
50/50
24.262
970153AG2-106 GEN
Solar/Wind Harmer
43.703
970513AG2-328 GEN
Solar/Wind Harmer
20.906
970517AG2-330 GEN
Solar/Wind Harmer
18.961
970349AG2-230 GEN
Solar/Wind Harmer
17.482
274772LINCOLN ;3U
Adder
6.778
270043AE2-236 GEN
Solar/Wind Harmer
6.013
247643Z2-116 C
Solar/Wind Harmer
0.075
274724RIVER EC ;11
Adder
19.077
24642205MAYFLWER
Adder
0.684
970707AG2-453 GEN
Solar/Wind Harmer
30.121
972231SS25-0005
Solar/Wind Harmer
10.191
972181SS23-001
Solar/Wind Harmer
6.369
274752CRETE EC ;2U
Adder
5.249
274753CRETE EC ;3U
Adder
5.249
274826FISK ;BP
Adder
11.703
972228AH1-698 GEN2
Adder
3.959
276772AC2-154 GEN
Solar/Wind Harmer
2.98
276806AD2-047 C O1
Solar/Wind Harmer
11.433
970941AG2-585 GEN
Solar/Wind Harmer
13.359
274802UNIV PARK;5U
Adder
6.231
274800UNIV PARK;3U
Adder
6.228
972038AH1-567 GEN2
Adder
0.39
276897AD1-100 C
Solar/Wind Harmer
30.932
939351AE1-166 GEN
Solar/Wind Harmer
6.32
945111AF1-176 GEN
Solar/Wind Harmer
6.017
274676JOLIET 29;8U
Adder
31.444
274730ELWOOD EC;6P
Adder
17.435
274734ELWOOD EC;8P
Adder
17.435
274736ELWOOD EC;9P
Adder
17.435
274729ELWOOD EC;1P
Adder
17.435
276893AG1-478 C
Solar/Wind Harmer
0.443
943121AE2-341 GEN
Solar/Wind Harmer
15.87
943591AF1-030 GEN
Solar/Wind Harmer
10.58
944531AF1-118 GEN
Solar/Wind Harmer
36.684
274682WAUKEGAN ;7U
Adder
18.78
270535AF1-215 GEN1
Solar/Wind Harmer
4.747
276694AA1-018 GEN2
Solar/Wind Harmer
6.59
274872LEEDK;1U
Solar/Wind Harmer
0.265
276805AD2-038 GEN
Solar/Wind Harmer
5.308
24441205WTRV SLR C
Solar/Wind Harmer
0.14
964401AG1-302 GEN
Solar/Wind Harmer
9.349
276799AD1-013 GEN
Solar/Wind Harmer
2.277
946671AF1-331 GEN
Solar/Wind Harmer
0.431
274855GSG-6 ;RU
Solar/Wind Harmer
3.802
274850MENDOTA H;RU
Solar/Wind Harmer
2.644
276602WESTBROOK C
Solar/Wind Harmer
2.189
276863AD2-134 GEN
Solar/Wind Harmer
1.839
247604X1-042
Adder
0.426
972236AH1-702 GEN2
Adder
2.235
274760LEE CO EC;1U
Adder
9.381
274767LEE CO EC;8U
Adder
9.27
959091AF2-200 GEN
Solar/Wind Harmer
15.497
24344105CKG2
50/50
9.143
24721805FLATG3
50/50
1.323
24721705FLATG2
50/50
24.262
962761AG1-125 GEN
Solar/Wind Harmer
100.225
970149AG2-104 GEN
Solar/Wind Harmer
123.777
970155AG2-107 GEN
Solar/Wind Harmer
43.703
970245AG2-165 GEN
Solar/Wind Harmer
20.906
972207SS24-0001
Solar/Wind Harmer
24.098
274773LINCOLN ;4U
Adder
6.778
274774LINCOLN ;5U
Adder
6.778
274723RIVER EC ;12
Adder
19.298
276164X3-005 C
Solar/Wind Harmer
0.755
274751CRETE EC ;1U
Adder
5.249
274754CRETE EC ;4U
Adder
5.249
274812UNIV PK N;8U
Adder
5.365
270505AE1-170 C O1
Solar/Wind Harmer
16.067
276776AD2-060 GEN
Solar/Wind Harmer
0.452
274801UNIV PARK;4U
Adder
6.228
941551AE2-152 GEN
Solar/Wind Harmer
4.834
24639705ELKHART HY
Adder
0.163
945111AF1-176 GEN
Solar/Wind Harmer
18.984
274676JOLIET 29;8U
Adder
32.608
274674JOLIET 9 ;6U
Adder
16.345
970373AG2-245 GEN
Solar/Wind Harmer
22.281
274732ELWOOD EC;7P
Adder
17.435
274871GR RIDGE ;2U
Solar/Wind Harmer
8.153
270449AD2-020 GEN
Solar/Wind Harmer
2.964
943021AE2-325 GEN
Solar/Wind Harmer
3.851
274745AC1-111 GEN9
Adder
5.903
274682WAUKEGAN ;7U
Adder
18.78
270055AF2-134 C O1
Solar/Wind Harmer
3.164
276691AA1-018 GEN1
Solar/Wind Harmer
0.486
274828WAUKEGAN ;BP
Adder
11.531
960751AF2-366 GEN
Solar/Wind Harmer
2.981
962781AG1-127 GEN
Solar/Wind Harmer
9.882
270063AE2-323 C
Solar/Wind Harmer
2.286
274872LEEDK;1U
Solar/Wind Harmer
8.52
939401AE1-172 GEN
Solar/Wind Harmer
14.44
276901AD2-066 C O1
Solar/Wind Harmer
3.633
971997AH1-543 GEN
Solar/Wind Harmer
16.227
958381AF2-132 GEN
Solar/Wind Harmer
9.349
276861AD2-134 GEN
Solar/Wind Harmer
1.839
964861AG1-349 GEN
Solar/Wind Harmer
8.089
971917AH1-482 GEN
Solar/Wind Harmer
9.335
274822ROCKFORD ;11
Adder
20.053
972235AH1-702 GEN1
Adder
2.571
274761LEE CO EC;2U
Adder
9.381
274766LEE CO EC;7U
Adder
9.27
957471AF2-041 GEN
Solar/Wind Harmer
23.245
959081AF2-199 GEN
Solar/Wind Harmer
7.748
971067AG2-660 GEN
Solar/Wind Harmer
1.802
270102X2-052 ST
50/50
1.764
270100X2-052 CT1
50/50
1.626
270101X2-052 CT2
50/50
1.626
970321AG2-212 GEN
Solar/Wind Harmer
20.906
965681AG1-436 GEN
Solar/Wind Harmer
13.726
965791AG1-447 GEN
Solar/Wind Harmer
7.022
274770LINCOLN ;1U
Adder
6.778
274771LINCOLN ;2U
Adder
6.778
270526AF1-158 GEN
Solar/Wind Harmer
4.946
24441505OLIV SLR
Solar/Wind Harmer
0.146
270216AD2-079_GEN
Solar/Wind Harmer
0.655
274808UNIV PK N;4U
Adder
5.341
972259AH1-714 GEN
Adder
20.433
957891AF2-083 GEN
Solar/Wind Harmer
3.607
960981AF2-389 GEN
Solar/Wind Harmer
1.616
274888KELLY CRK;1U
Solar/Wind Harmer
6.31
274887GEN-1.85
Solar/Wind Harmer
5.697
276843GEN-1.7
Solar/Wind Harmer
0.613
958011AF2-095 GEN
Solar/Wind Harmer
15.39
274803UNIV PARK;6U
Adder
6.231
274674JOLIET 9 ;6U
Adder
16.345
274847GR RIDGE ;BU
Solar/Wind Harmer
5.363
961051AF2-396 GEN
Solar/Wind Harmer
16.824
961051AF2-396 GEN
Solar/Wind Harmer
7.825
971573AH1-285 GEN
Solar/Wind Harmer
9.059
247620Y3-023
Adder
0.485
274696ROCKY RD ;4P
Adder
11.927
274695ROCKY RD ;2P
Adder
11.652
274693ROCKY RD ;1P
Adder
11.538
274697ROCKY RD ;3P
Adder
3.165
958481AF2-142 GEN
Solar/Wind Harmer
15.663
274683WAUKEGAN ;8U
Adder
21.998
274683WAUKEGAN ;8U
Adder
18.543
274861TOP CROP ;1U
Solar/Wind Harmer
6.325
274862TOP CROP ;2U
Solar/Wind Harmer
5.281
962691AG1-118 GEN
Solar/Wind Harmer
31.232
970921AG2-575 GEN
Solar/Wind Harmer
10.391
970921AG2-575 GEN
Solar/Wind Harmer
2.417
958491AF2-143 GEN
Solar/Wind Harmer
15.522
942991AE2-321 GEN
Solar/Wind Harmer
10.33
274879MINONK ;1U
Solar/Wind Harmer
6.96
971333AH1-146 GEN
Solar/Wind Harmer
20.58
971335AH1-147 GEN
Solar/Wind Harmer
20.58
274764LEE CO EC;5U
Adder
9.403
274765LEE CO EC;6U
Adder
9.403
274762LEE CO EC;3U
Adder
9.381
274763LEE CO EC;4U
Adder
9.292
972267AH1-718 GEN
Adder
4.167
971341AH1-150 GEN
Solar/Wind Harmer
15.497
971343AH1-151 GEN
Solar/Wind Harmer
15.497
NYPJM->LTFIMP_NY
CLTF
2.604
LGEELTFEXP_LGEE->PJM
CLTF
3.723
WECLTFEXP_WEC->PJM
CLTF
3.891
AG2-052LTFEXP_AG2-052->PJM
LTF
0.239
AH1-155LTFEXP_AH1-155->PJM
LTF
0.359
CPLELTFEXP_CPLE->PJM
CLTF
1.845
CBM West 2LTFEXP_CBM-W2->PJM
CBM
89.975
LAGNLTFEXP_LAGN->PJM
CLTF
11.821
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.882
TVALTFEXP_TVA->PJM
CLTF
5.371
CBM West 1LTFEXP_CBM-W1->PJM
CBM
116.664
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.203
MECLTFEXP_MEC->PJM
CLTF
15.045
SIGELTFEXP_SIGE->PJM
CLTF
0.344

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o AEP_P1-2_#706_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#706_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.0 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4722.06
MW Contribution:69.95
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
4.694
971599AH1-298 GEN
50/50
14.063
270144AC1-141 ST1_
50/50
3.051
24653605MOTTVILLE
50/50
0.005
24643105BUCHANAN
50/50
0.018
270036AE2-216 BAT
50/50
8.975
962771AG1-126 GEN
Solar/Wind Harmer
109.549
270284AF1-227 GEN1
Solar/Wind Harmer
0.015
270286AF1-227 GEN2
Solar/Wind Harmer
0.006
270287AF1-227 GEN3
Solar/Wind Harmer
0.006
971347AH1-153 GEN
Solar/Wind Harmer
15.658
270578AF1-285 GEN2
Solar/Wind Harmer
0.683
270071AF1-092 GEN
Solar/Wind Harmer
19.582
971771AH1-392 GEN
Solar/Wind Harmer
10.018
971619AH1-309 GEN
Solar/Wind Harmer
4.486
971769AH1-391 GEN
Solar/Wind Harmer
11.066
960681AF2-359 GEN
Solar/Wind Harmer
-0.002
270302AB2-170 GEN
Solar/Wind Harmer
0.006
270317AD1-130_GEN
Solar/Wind Harmer
0.014
971653AH1-327 GEN
Solar/Wind Harmer
1.377
24729505KEY G4
Adder
9.092
965041AG1-368 GEN
Solar/Wind Harmer
9.739
274775LINCOLN ;6U
Adder
11.607
274776LINCOLN ;7U
Adder
11.607
274777LINCOLN ;8U
Adder
11.607
965051AG1-369 GEN
Solar/Wind Harmer
4.783
274814UNIV PK N;0U
Adder
6.852
274807UNIV PK N;3U
Adder
6.837
274805UNIV PK N;1U
Adder
6.807
274811UNIV PK N;7U
Adder
6.792
972037AH1-567 GEN1
Adder
0.247
274827FISK ;RP
Adder
10.465
960591AF2-350 GEN
Solar/Wind Harmer
9.401
972227AH1-698 GEN1
Adder
3.512
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.189
963791AG1-232 GEN
Solar/Wind Harmer
12.652
274687WILL CNTY;4U
Adder
37.406
274687WILL CNTY;4U
Adder
37.406
274675JOLIET 29;7U
Adder
41.022
274675JOLIET 29;7U
Adder
39.557
270536AF1-215 GEN2
Solar/Wind Harmer
0.012
274731ELWOOD EC;2P
Adder
21.93
274733ELWOOD EC;3P
Adder
21.93
274735ELWOOD EC;4P
Adder
21.93
274728ELWOOD EC;5P
Adder
21.93
970833AG2-524 GEN
Solar/Wind Harmer
10.224
970833AG2-524 GEN
Solar/Wind Harmer
6.816
971549AH1-272 GEN
Solar/Wind Harmer
19.16
274746AC1-111 G10
Adder
7.401
274744AC1-111 GEN8
Adder
7.401
965101AG1-375 GEN
Solar/Wind Harmer
9.112
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.807
276882AE2-255 GEN
Solar/Wind Harmer
1.053
971177AH1-047 GEN
Solar/Wind Harmer
5.547
247607V1-011 GEN
Solar/Wind Harmer
0.001
971411AH1-196 GEN
Solar/Wind Harmer
13.442
971675AH1-338 GEN
Solar/Wind Harmer
3.495
971611AH1-305 GEN
Solar/Wind Harmer
5.332
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
971171AH1-044 GEN
Solar/Wind Harmer
17.815
274823ROCKFORD ;21
Adder
24.797
276612AE2-035 GEN
Solar/Wind Harmer
0.002
926823AC1-168 GEN
Solar/Wind Harmer
1.498
970169AG2-114 GEN
Solar/Wind Harmer
8.81
945581AF1-223 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
14.125
961011AF2-392 GEN
Solar/Wind Harmer
5.094
957751AF2-069 GEN
Solar/Wind Harmer
0.285
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
8.957
941731AE2-173 GEN
Solar/Wind Harmer
7.108
270024AE2-089 GEN
Solar/Wind Harmer
0.009
946321AF1-296 GEN
Solar/Wind Harmer
4.721
971609AH1-304 GEN
Solar/Wind Harmer
1.376
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
970289AG2-191 GEN
Solar/Wind Harmer
1.575
270594AE1-207 GEN
Solar/Wind Harmer
9.184
963841AG1-237 GEN
Solar/Wind Harmer
3.53
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
970115AG2-085 GEN
Solar/Wind Harmer
3.191
276849AB2-070 GEN2
Solar/Wind Harmer
0.291
276848AB2-070 GEN3
Solar/Wind Harmer
0.29
270297AD1-101 GEN
Solar/Wind Harmer
0.002
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
24721805FLATG3
50/50
4.694
24721705FLATG2
50/50
86.059
24344105CKG2
50/50
11.607
270143AC1-141 CT2_
50/50
3.444
24639705ELKHART HY
50/50
0.234
970521AG2-332 GEN
50/50
16.668
24307105BERRINSP G
50/50
0.031
962761AG1-125 GEN
Solar/Wind Harmer
109.549
970149AG2-104 GEN
Solar/Wind Harmer
118.317
970155AG2-107 GEN
Solar/Wind Harmer
69.955
270349AD2-093_GEN
Solar/Wind Harmer
0.009
965011AG1-365 GEN
Solar/Wind Harmer
10.316
270223U2-072_GEN1
Solar/Wind Harmer
0.001
970245AG2-165 GEN
Solar/Wind Harmer
4.403
270063AE2-323 C
Solar/Wind Harmer
0.008
270505AE1-170 C O1
Solar/Wind Harmer
10.468
945111AF1-176 GEN
Solar/Wind Harmer
17.757
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
5.164
270462AD2-086
Solar/Wind Harmer
0.02
274773LINCOLN ;4U
Adder
11.607
274774LINCOLN ;5U
Adder
11.607
247521TR3_G114
Solar/Wind Harmer
0.349
270246TR4_N_V150
Solar/Wind Harmer
0.062
274723RIVER EC ;12
Adder
24.46
274751CRETE EC ;1U
Adder
11.24
274754CRETE EC ;4U
Adder
11.24
970373AG2-245 GEN
Solar/Wind Harmer
19.935
276164X3-005 C
Solar/Wind Harmer
0
965421AG1-410 GEN
Solar/Wind Harmer
28.417
274812UNIV PK N;8U
Adder
6.792
24695305TIMB G C
Solar/Wind Harmer
0.002
276776AD2-060 GEN
Solar/Wind Harmer
0.981
274801UNIV PARK;4U
Adder
7.856
246936BC-WTG1
Solar/Wind Harmer
0.381
270489AE1-102 GEN1
Solar/Wind Harmer
1.22
941551AE2-152 GEN
Solar/Wind Harmer
0.001
944231AF1-091 GEN
Solar/Wind Harmer
2.492
274676JOLIET 29;8U
Adder
41.022
270055AF2-134 C O1
Solar/Wind Harmer
0.007
274674JOLIET 9 ;6U
Adder
20.555
274732ELWOOD EC;7P
Adder
21.93
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
2.721
274745AC1-111 GEN9
Adder
7.401
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.896
276691AA1-018 GEN1
Solar/Wind Harmer
1.108
274682WAUKEGAN ;7U
Adder
23.511
274828WAUKEGAN ;BP
Adder
14.433
958861AF2-177 GEN
Solar/Wind Harmer
3.948
962781AG1-127 GEN
Solar/Wind Harmer
8.621
939401AE1-172 GEN
Solar/Wind Harmer
6.775
274872LEEDK;1U
Solar/Wind Harmer
0.006
276901AD2-066 C O1
Solar/Wind Harmer
0.009
971997AH1-543 GEN
Solar/Wind Harmer
4.718
276861AD2-134 GEN
Solar/Wind Harmer
0.161
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
11.195
957471AF2-041 GEN
Solar/Wind Harmer
26.723
959081AF2-199 GEN
Solar/Wind Harmer
8.908
971067AG2-660 GEN
Solar/Wind Harmer
2.969
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
274822ROCKFORD ;11
Adder
24.978
972235AH1-702 GEN1
Adder
3.201
970819AG2-516 GEN
Solar/Wind Harmer
10.6
970569AG2-363 GEN
Solar/Wind Harmer
26.435
971475AH1-234 GEN
Solar/Wind Harmer
4.275
945371AF1-202 GEN
Solar/Wind Harmer
0.001
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
11.654
274766LEE CO EC;7U
Adder
11.517
276158O29GEN2
Solar/Wind Harmer
0.001
24791305MDL-5G
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.289
276726Z2-087_GEN
Solar/Wind Harmer
0.003
939741AE1-205 GEN
Solar/Wind Harmer
11.942
24722005FLATG5
50/50
4.694
24721905FLATG4
50/50
86.059
270475AD2-096_GEN
50/50
10.488
270142AC1-141 CT1_
50/50
3.444
24641605TWIN BRNCH
50/50
0.025
24344005CKG1
50/50
9.376
24642205MAYFLWER
50/50
0.961
944961AF1-161 GEN
50/50
4.122
962601AG1-109 GEN
50/50
4.122
970153AG2-106 GEN
Solar/Wind Harmer
69.955
270043AE2-236 GEN
Solar/Wind Harmer
6.761
970349AG2-230 GEN
Solar/Wind Harmer
15.658
959331AF2-224 GEN
Solar/Wind Harmer
7.221
965021AG1-366 GEN
Solar/Wind Harmer
3.439
270391AF1-285 GEN3
Solar/Wind Harmer
0.683
970513AG2-328 GEN
Solar/Wind Harmer
4.403
970517AG2-330 GEN
Solar/Wind Harmer
26.415
970031AG2-029 GEN
Solar/Wind Harmer
6.551
247643Z2-116 C
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
44.632
945111AF1-176 GEN
Solar/Wind Harmer
8.066
270485AE1-090_GEN
Solar/Wind Harmer
0.001
24441205WTRV SLR C
Solar/Wind Harmer
0
247604X1-042
Adder
0.578
274772LINCOLN ;3U
Adder
11.607
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.062
274724RIVER EC ;11
Adder
24.177
274752CRETE EC ;2U
Adder
11.24
274753CRETE EC ;3U
Adder
11.24
970707AG2-453 GEN
Solar/Wind Harmer
30.794
274802UNIV PARK;5U
Adder
7.866
274826FISK ;BP
Adder
14.766
276806AD2-047 C O1
Solar/Wind Harmer
5.327
970941AG2-585 GEN
Solar/Wind Harmer
11.751
274800UNIV PARK;3U
Adder
7.856
972038AH1-567 GEN2
Adder
0.492
972228AH1-698 GEN2
Adder
4.987
270491AE1-102 GEN2
Solar/Wind Harmer
1.22
276897AD1-100 C
Solar/Wind Harmer
0.012
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
39.557
270535AF1-215 GEN1
Solar/Wind Harmer
0.012
274729ELWOOD EC;1P
Adder
21.93
274730ELWOOD EC;6P
Adder
21.93
274734ELWOOD EC;8P
Adder
21.93
274736ELWOOD EC;9P
Adder
21.93
276893AG1-478 C
Solar/Wind Harmer
0.369
943121AE2-341 GEN
Solar/Wind Harmer
15.511
943591AF1-030 GEN
Solar/Wind Harmer
10.315
964401AG1-302 GEN
Solar/Wind Harmer
0.001
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
23.511
276805AD2-038 GEN
Solar/Wind Harmer
0.003
274872LEEDK;1U
Solar/Wind Harmer
0.331
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.956
274855GSG-6 ;RU
Solar/Wind Harmer
0.329
274850MENDOTA H;RU
Solar/Wind Harmer
0.106
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.161
959091AF2-200 GEN
Solar/Wind Harmer
17.815
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
2.783
270258AD1-119 GEN
Solar/Wind Harmer
0.002
970571AG2-364 GEN
Solar/Wind Harmer
17.623
270404AC1-167 GEN
Solar/Wind Harmer
0.004
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
11.654
274767LEE CO EC;8U
Adder
11.517
276157O29GEN1
Solar/Wind Harmer
1.397
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
8.621
274878BISHOP HL;2U
Solar/Wind Harmer
0.289
942111AE2-223 GEN
Solar/Wind Harmer
2.772
971617AH1-308 GEN
Solar/Wind Harmer
7.081
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
25.189
959611AF2-252 GEN
Solar/Wind Harmer
2.799
965931AG1-462 GEN
Solar/Wind Harmer
21.385
247642Z2-115 C
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
0.912
970291AG2-192 GEN
Solar/Wind Harmer
0.829
958821AF2-173 GEN
Solar/Wind Harmer
11.29
270004AE1-209 GEN
Solar/Wind Harmer
1.747
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
3.686
276668AB2-070 GEN1
Solar/Wind Harmer
0.291
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
11.901
946031AF1-268 GEN
Solar/Wind Harmer
7.527
276621W2-048 GEN
Solar/Wind Harmer
0.396
276838X2-022 GEN2
Solar/Wind Harmer
0.442
942481AE2-261 GEN
Solar/Wind Harmer
22.745
24728705AND G3
Adder
7.997
24728505AND G1
Adder
3.824
970615AG2-402 GEN
50/50
3.439
247620Y3-023
50/50
0.701
270102X2-052 ST
50/50
2.279
270100X2-052 CT1
50/50
2.1
270101X2-052 CT2
50/50
2.1
270471AD2-092_GEN
Solar/Wind Harmer
0.009
970611AG2-400 GEN
Solar/Wind Harmer
10.316
970627AG2-408 GEN
Solar/Wind Harmer
3.095
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
970321AG2-212 GEN
Solar/Wind Harmer
4.403
270216AD2-079_GEN
Solar/Wind Harmer
0.002
957891AF2-083 GEN
Solar/Wind Harmer
0.001
270526AF1-158 GEN
Solar/Wind Harmer
0.012
961051AF2-396 GEN
Solar/Wind Harmer
19.83
961051AF2-396 GEN
Solar/Wind Harmer
13.22
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
12.351
965791AG1-447 GEN
Solar/Wind Harmer
9.057
274770LINCOLN ;1U
Adder
11.607
274771LINCOLN ;2U
Adder
11.607
274808UNIV PK N;4U
Adder
6.763
274803UNIV PARK;6U
Adder
7.866
274888KELLY CRK;1U
Solar/Wind Harmer
0.552
274887GEN-1.85
Solar/Wind Harmer
0.248
276843GEN-1.7
Solar/Wind Harmer
0.304
958011AF2-095 GEN
Solar/Wind Harmer
13.537
972259AH1-714 GEN
Adder
25.697
246938BC-WTG3
Solar/Wind Harmer
0.34
246937BC-WTG2
Solar/Wind Harmer
0.381
274674JOLIET 9 ;6U
Adder
20.555
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
944541AF1-119 GEN
Solar/Wind Harmer
0.622
960971AF2-388 GEN
Solar/Wind Harmer
5.442
971573AH1-285 GEN
Solar/Wind Harmer
1.715
958481AF2-142 GEN
Solar/Wind Harmer
13.715
274696ROCKY RD ;4P
Adder
14.93
274695ROCKY RD ;2P
Adder
14.586
274693ROCKY RD ;1P
Adder
14.442
274697ROCKY RD ;3P
Adder
3.962
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
1.237
274683WAUKEGAN ;8U
Adder
27.535
274683WAUKEGAN ;8U
Adder
23.211
962691AG1-118 GEN
Solar/Wind Harmer
27.238
942221AE2-234 GEN
Solar/Wind Harmer
0.045
970921AG2-575 GEN
Solar/Wind Harmer
9.059
970921AG2-575 GEN
Solar/Wind Harmer
3.02
958491AF2-143 GEN
Solar/Wind Harmer
13.566
274879MINONK ;1U
Solar/Wind Harmer
0.38
942991AE2-321 GEN
Solar/Wind Harmer
10.048
270007AE1-245 C
Solar/Wind Harmer
0.002
971333AH1-146 GEN
Solar/Wind Harmer
17.91
971335AH1-147 GEN
Solar/Wind Harmer
17.91
971341AH1-150 GEN
Solar/Wind Harmer
17.815
971343AH1-151 GEN
Solar/Wind Harmer
17.815
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
970623AG2-406 GEN
Solar/Wind Harmer
1.621
274856ECOGROVE ;U1
Solar/Wind Harmer
0.208
276611AD2-172 GEN
Solar/Wind Harmer
0.002
938861AE1-114 GEN
Solar/Wind Harmer
4.97
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
274764LEE CO EC;5U
Adder
11.682
274765LEE CO EC;6U
Adder
11.682
274762LEE CO EC;3U
Adder
11.654
274763LEE CO EC;4U
Adder
11.544
276603SUBLETTE C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
5.169
276741O09 GEN1
Solar/Wind Harmer
0.308
276708O09 GEN2
Solar/Wind Harmer
0.308
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.339
276646AC1-214 GEN2
Solar/Wind Harmer
0.339
276782AC1-033 GEN
Solar/Wind Harmer
0.001
270599AE1-208 GEN
Solar/Wind Harmer
7.723
270031AE2-169
Solar/Wind Harmer
4.634
960611AF2-352 GEN
Solar/Wind Harmer
2.799
966841AG1-555 GEN
Solar/Wind Harmer
0.944
971613AH1-306 GEN
Solar/Wind Harmer
3.936
960441AF2-335 GEN
Solar/Wind Harmer
7.977
970241AG2-163 GEN
Solar/Wind Harmer
4.643
970825AG2-519 GEN
Solar/Wind Harmer
8.815
970621AG2-405 GEN
Solar/Wind Harmer
1.453
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.595
247621Y3-024
Adder
0.268
276916AD2-100_GEN
Solar/Wind Harmer
12.804
276911AD2-131_GEN
Solar/Wind Harmer
0.843
274854TWINGROVE;U2
Solar/Wind Harmer
0.004
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
970291AG2-192 GEN
Solar/Wind Harmer
1.078
270032AE2-172
Solar/Wind Harmer
5.467
972175AH1-670 GEN
Solar/Wind Harmer
6.757
270005AE1-210 C O1
Solar/Wind Harmer
1.747
965031AG1-367 GEN
Solar/Wind Harmer
8.064
276903AD2-071 C
Solar/Wind Harmer
8.911
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
18.836
970825AG2-519 GEN
Solar/Wind Harmer
2.823
963831AG1-236 GEN
Solar/Wind Harmer
3.095
276615X2-022 GEN
Solar/Wind Harmer
0.082
965911AG1-460 GEN
Solar/Wind Harmer
1.521
247536S-71 GEN
Solar/Wind Harmer
0.305
24728605AND G2
Adder
3.824
944201AF1-088_MTX
Adder
80.786
NYPJM->LTFIMP_NY
CLTF
3.072
LGEELTFEXP_LGEE->PJM
CLTF
4.553
WECLTFEXP_WEC->PJM
CLTF
4.843
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.157
AG2-052LTFEXP_AG2-052->PJM
LTF
0.305
AH1-155LTFEXP_AH1-155->PJM
LTF
0.457
CBM West 2LTFEXP_CBM-W2->PJM
CBM
98.823
LAGNLTFEXP_LAGN->PJM
CLTF
11.481
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.982
TVALTFEXP_TVA->PJM
CLTF
4.813
CBM West 1LTFEXP_CBM-W1->PJM
CBM
159.327
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.302
MECLTFEXP_MEC->PJM
CLTF
18.121
SIGELTFEXP_SIGE->PJM
CLTF
0.416

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o AEP_P7-1_#10944___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10944___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:108.04 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4474.91
MW Contribution:35.36
Bus #Bus NameTypeMW Contribution
270102X2-052 ST
50/50
1.753
270100X2-052 CT1
50/50
1.615
270101X2-052 CT2
50/50
1.615
274770LINCOLN ;1U
50/50
7.103
274771LINCOLN ;2U
50/50
7.103
247620Y3-023
50/50
0.527
970321AG2-212 GEN
Solar/Wind Harmer
20.356
965681AG1-436 GEN
Solar/Wind Harmer
13.644
965791AG1-447 GEN
Solar/Wind Harmer
6.981
270216AD2-079_GEN
Solar/Wind Harmer
0.661
270526AF1-158 GEN
Solar/Wind Harmer
4.945
24441505OLIV SLR
Solar/Wind Harmer
0.146
957891AF2-083 GEN
Solar/Wind Harmer
3.638
960981AF2-389 GEN
Solar/Wind Harmer
1.63
961051AF2-396 GEN
Solar/Wind Harmer
17.007
961051AF2-396 GEN
Solar/Wind Harmer
7.91
970611AG2-400 GEN
Solar/Wind Harmer
10.695
274808UNIV PK N;4U
Adder
5.307
972259AH1-714 GEN
Adder
20.26
274803UNIV PARK;6U
Adder
6.188
274888KELLY CRK;1U
Solar/Wind Harmer
6.264
274887GEN-1.85
Solar/Wind Harmer
5.656
276843GEN-1.7
Solar/Wind Harmer
0.609
958011AF2-095 GEN
Solar/Wind Harmer
15.279
274674JOLIET 9 ;6U
Adder
16.234
274847GR RIDGE ;BU
Solar/Wind Harmer
5.326
971573AH1-285 GEN
Solar/Wind Harmer
8.997
270471AD2-092_GEN
Solar/Wind Harmer
3.79
274696ROCKY RD ;4P
Adder
11.859
274695ROCKY RD ;2P
Adder
11.585
274693ROCKY RD ;1P
Adder
11.471
274697ROCKY RD ;3P
Adder
3.147
958481AF2-142 GEN
Solar/Wind Harmer
15.598
274861TOP CROP ;1U
Solar/Wind Harmer
6.299
274862TOP CROP ;2U
Solar/Wind Harmer
5.26
274683WAUKEGAN ;8U
Adder
21.882
274683WAUKEGAN ;8U
Adder
18.445
962691AG1-118 GEN
Solar/Wind Harmer
31.071
970921AG2-575 GEN
Solar/Wind Harmer
10.34
970921AG2-575 GEN
Solar/Wind Harmer
2.405
958491AF2-143 GEN
Solar/Wind Harmer
15.476
942991AE2-321 GEN
Solar/Wind Harmer
10.288
274879MINONK ;1U
Solar/Wind Harmer
6.941
971333AH1-146 GEN
Solar/Wind Harmer
20.505
971335AH1-147 GEN
Solar/Wind Harmer
20.505
274764LEE CO EC;5U
Adder
9.394
274765LEE CO EC;6U
Adder
9.394
274762LEE CO EC;3U
Adder
9.372
274763LEE CO EC;4U
Adder
9.283
971599AH1-298 GEN
50/50
10.493
270144AC1-141 ST1_
50/50
2.307
274775LINCOLN ;6U
50/50
7.103
274776LINCOLN ;7U
50/50
7.103
274777LINCOLN ;8U
50/50
7.103
24643105BUCHANAN
50/50
0.014
24653605MOTTVILLE
50/50
0.004
962771AG1-126 GEN
Solar/Wind Harmer
81.099
971347AH1-153 GEN
Solar/Wind Harmer
17.162
24344105CKG2
50/50
8.873
270143AC1-141 CT2_
50/50
2.604
24639705ELKHART HY
50/50
0.176
970521AG2-332 GEN
50/50
12.559
274773LINCOLN ;4U
50/50
7.103
274774LINCOLN ;5U
50/50
7.103
962761AG1-125 GEN
Solar/Wind Harmer
81.099
970149AG2-104 GEN
Solar/Wind Harmer
100.157
970155AG2-107 GEN
Solar/Wind Harmer
35.363
970245AG2-165 GEN
Solar/Wind Harmer
20.356
270063AE2-323 C
Solar/Wind Harmer
2.382
972207SS24-0001
Solar/Wind Harmer
23.8
270505AE1-170 C O1
Solar/Wind Harmer
16.187
945111AF1-176 GEN
Solar/Wind Harmer
19.199
274723RIVER EC ;12
Adder
19.163
965011AG1-365 GEN
Solar/Wind Harmer
10.695
270449AD2-020 GEN
Solar/Wind Harmer
2.996
943021AE2-325 GEN
Solar/Wind Harmer
3.892
270142AC1-141 CT1_
50/50
2.604
24641605TWIN BRNCH
50/50
0.019
24344005CKG1
50/50
7.093
24642205MAYFLWER
50/50
0.729
274772LINCOLN ;3U
50/50
7.103
970153AG2-106 GEN
Solar/Wind Harmer
35.363
970349AG2-230 GEN
Solar/Wind Harmer
17.162
970513AG2-328 GEN
Solar/Wind Harmer
20.356
970517AG2-330 GEN
Solar/Wind Harmer
18.462
270043AE2-236 GEN
Solar/Wind Harmer
6.202
247643Z2-116 C
Solar/Wind Harmer
0.076
944531AF1-118 GEN
Solar/Wind Harmer
37.964
945111AF1-176 GEN
Solar/Wind Harmer
6.085
970031AG2-029 GEN
Solar/Wind Harmer
32.264
274724RIVER EC ;11
Adder
18.942
959331AF2-224 GEN
Solar/Wind Harmer
10.695
965021AG1-366 GEN
Solar/Wind Harmer
2.487
972231SS25-0005
Solar/Wind Harmer
10.133
972181SS23-001
Solar/Wind Harmer
6.333
274752CRETE EC ;2U
Adder
5.219
274753CRETE EC ;3U
Adder
5.219
970707AG2-453 GEN
Solar/Wind Harmer
29.824
274826FISK ;BP
Adder
11.62
274802UNIV PARK;5U
Adder
6.188
276772AC2-154 GEN
Solar/Wind Harmer
2.959
276806AD2-047 C O1
Solar/Wind Harmer
11.351
970941AG2-585 GEN
Solar/Wind Harmer
13.263
274800UNIV PARK;3U
Adder
6.184
972228AH1-698 GEN2
Adder
3.929
972038AH1-567 GEN2
Adder
0.387
276897AD1-100 C
Solar/Wind Harmer
30.707
939351AE1-166 GEN
Solar/Wind Harmer
6.274
274676JOLIET 29;8U
Adder
31.226
274729ELWOOD EC;1P
Adder
17.321
274730ELWOOD EC;6P
Adder
17.321
274734ELWOOD EC;8P
Adder
17.321
274736ELWOOD EC;9P
Adder
17.321
276893AG1-478 C
Solar/Wind Harmer
0.44
943121AE2-341 GEN
Solar/Wind Harmer
15.753
943591AF1-030 GEN
Solar/Wind Harmer
10.502
24441205WTRV SLR C
Solar/Wind Harmer
0.142
270535AF1-215 GEN1
Solar/Wind Harmer
4.766
276694AA1-018 GEN2
Solar/Wind Harmer
6.562
274682WAUKEGAN ;7U
Adder
18.678
247604X1-042
Adder
0.433
964401AG1-302 GEN
Solar/Wind Harmer
9.41
274872LEEDK;1U
Solar/Wind Harmer
0.264
276805AD2-038 GEN
Solar/Wind Harmer
5.293
959141AF2-205 GEN
Solar/Wind Harmer
6.209
276799AD1-013 GEN
Solar/Wind Harmer
2.268
946671AF1-331 GEN
Solar/Wind Harmer
0.43
274855GSG-6 ;RU
Solar/Wind Harmer
3.788
274850MENDOTA H;RU
Solar/Wind Harmer
2.634
276602WESTBROOK C
Solar/Wind Harmer
2.18
276863AD2-134 GEN
Solar/Wind Harmer
1.832
972236AH1-702 GEN2
Adder
2.23
274760LEE CO EC;1U
Adder
9.372
274767LEE CO EC;8U
Adder
9.261
24721905FLATG4
Adder
19.591
972267AH1-718 GEN
Adder
4.167
270071AF1-092 GEN
Solar/Wind Harmer
16.665
971771AH1-392 GEN
Solar/Wind Harmer
9.826
960681AF2-359 GEN
Solar/Wind Harmer
4.124
971769AH1-391 GEN
Solar/Wind Harmer
10.874
24729505KEY G4
Adder
6.929
274814UNIV PK N;0U
Adder
5.377
274807UNIV PK N;3U
Adder
5.366
274805UNIV PK N;1U
Adder
5.342
274811UNIV PK N;7U
Adder
5.331
944161AF1-084 GEN
Solar/Wind Harmer
2.348
274827FISK ;RP
Adder
8.235
972037AH1-567 GEN1
Adder
0.194
960591AF2-350 GEN
Solar/Wind Harmer
10.611
972227AH1-698 GEN1
Adder
2.767
274687WILL CNTY;4U
Adder
29.513
274687WILL CNTY;4U
Adder
29.513
274675JOLIET 29;7U
Adder
32.383
274675JOLIET 29;7U
Adder
31.226
274731ELWOOD EC;2P
Adder
17.321
274733ELWOOD EC;3P
Adder
17.321
274735ELWOOD EC;4P
Adder
17.321
274728ELWOOD EC;5P
Adder
17.321
970833AG2-524 GEN
Solar/Wind Harmer
9.195
970833AG2-524 GEN
Solar/Wind Harmer
4.277
274746AC1-111 G10
Adder
5.862
274744AC1-111 GEN8
Adder
5.862
270536AF1-215 GEN2
Solar/Wind Harmer
4.766
958391AF2-133 GEN
Solar/Wind Harmer
9.357
276868AE1-113 GEN
Solar/Wind Harmer
10.411
276882AE2-255 GEN
Solar/Wind Harmer
3.471
971177AH1-047 GEN
Solar/Wind Harmer
6.027
971675AH1-338 GEN
Solar/Wind Harmer
18.464
971411AH1-196 GEN
Solar/Wind Harmer
15.386
274823ROCKFORD ;21
Adder
19.853
270054AF2-122 C O1
Solar/Wind Helper
1.254
274863CRW1-WTG
Solar/Wind Harmer
3.998
274864CRW2-WTG
Solar/Wind Harmer
3.998
274751CRETE EC ;1U
Adder
5.219
274754CRETE EC ;4U
Adder
5.219
276164X3-005 C
Solar/Wind Harmer
0.75
274812UNIV PK N;8U
Adder
5.331
970373AG2-245 GEN
Solar/Wind Harmer
22.301
276776AD2-060 GEN
Solar/Wind Harmer
0.449
274801UNIV PARK;4U
Adder
6.184
941551AE2-152 GEN
Solar/Wind Harmer
4.799
274676JOLIET 29;8U
Adder
32.382
274674JOLIET 9 ;6U
Adder
16.234
274732ELWOOD EC;7P
Adder
17.321
274871GR RIDGE ;2U
Solar/Wind Harmer
8.096
274745AC1-111 GEN9
Adder
5.862
270055AF2-134 C O1
Solar/Wind Harmer
3.177
270349AD2-093_GEN
Solar/Wind Harmer
3.79
276691AA1-018 GEN1
Solar/Wind Harmer
0.484
274682WAUKEGAN ;7U
Adder
18.678
274828WAUKEGAN ;BP
Adder
11.47
958381AF2-132 GEN
Solar/Wind Harmer
9.41
964861AG1-349 GEN
Solar/Wind Harmer
8.144
971917AH1-482 GEN
Solar/Wind Harmer
9.398
960751AF2-366 GEN
Solar/Wind Harmer
2.967
962781AG1-127 GEN
Solar/Wind Harmer
9.833
939401AE1-172 GEN
Solar/Wind Harmer
14.402
274872LEEDK;1U
Solar/Wind Harmer
8.48
276901AD2-066 C O1
Solar/Wind Harmer
3.622
971997AH1-543 GEN
Solar/Wind Harmer
16.182
276861AD2-134 GEN
Solar/Wind Harmer
1.832
274822ROCKFORD ;11
Adder
19.998
972235AH1-702 GEN1
Adder
2.564
274761LEE CO EC;2U
Adder
9.372
274766LEE CO EC;7U
Adder
9.261
24721705FLATG2
Adder
19.591
NYPJM->LTFIMP_NY
CLTF
2.909
LGEELTFEXP_LGEE->PJM
CLTF
4.431
WECLTFEXP_WEC->PJM
CLTF
3.883
AG2-052LTFEXP_AG2-052->PJM
LTF
0.241
AH1-155LTFEXP_AH1-155->PJM
LTF
0.361
CPLELTFEXP_CPLE->PJM
CLTF
1.819
CBM West 2LTFEXP_CBM-W2->PJM
CBM
95.132
LAGNLTFEXP_LAGN->PJM
CLTF
12.443
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.1
TVALTFEXP_TVA->PJM
CLTF
5.746
CBM West 1LTFEXP_CBM-W1->PJM
CBM
124.006
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.057
MECLTFEXP_MEC->PJM
CLTF
15.25
SIGELTFEXP_SIGE->PJM
CLTF
0.383

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-027A_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-027A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:107.84 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4466.89
MW Contribution:35.62
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
2.745
24641605TWIN BRNCH
50/50
0.02
24344005CKG1
50/50
7.486
24642205MAYFLWER
50/50
0.768
944961AF1-161 GEN
50/50
3.289
962601AG1-109 GEN
50/50
3.289
970153AG2-106 GEN
Solar/Wind Harmer
35.618
970349AG2-230 GEN
Solar/Wind Harmer
17.891
270043AE2-236 GEN
Solar/Wind Harmer
6.493
970513AG2-328 GEN
Solar/Wind Harmer
21.006
970517AG2-330 GEN
Solar/Wind Harmer
19.052
247643Z2-116 C
Solar/Wind Harmer
0.08
945111AF1-176 GEN
Solar/Wind Harmer
6.428
970031AG2-029 GEN
Solar/Wind Harmer
34.05
959331AF2-224 GEN
Solar/Wind Harmer
11.324
965021AG1-366 GEN
Solar/Wind Harmer
2.634
944531AF1-118 GEN
Solar/Wind Harmer
39.305
274772LINCOLN ;3U
Adder
6.925
24441205WTRV SLR C
Solar/Wind Harmer
0.151
247604X1-042
Adder
0.462
274724RIVER EC ;11
Adder
19.633
972231SS25-0005
Solar/Wind Harmer
10.51
972181SS23-001
Solar/Wind Harmer
6.569
274752CRETE EC ;2U
Adder
5.413
274753CRETE EC ;3U
Adder
5.413
970707AG2-453 GEN
Solar/Wind Harmer
30.834
274802UNIV PARK;5U
Adder
6.406
274826FISK ;BP
Adder
12.027
276772AC2-154 GEN
Solar/Wind Harmer
3.062
276806AD2-047 C O1
Solar/Wind Harmer
11.745
970941AG2-585 GEN
Solar/Wind Harmer
13.724
274800UNIV PARK;3U
Adder
6.4
972038AH1-567 GEN2
Adder
0.401
972228AH1-698 GEN2
Adder
4.065
276897AD1-100 C
Solar/Wind Harmer
31.748
939351AE1-166 GEN
Solar/Wind Harmer
6.487
274676JOLIET 29;8U
Adder
32.29
274729ELWOOD EC;1P
Adder
17.909
274730ELWOOD EC;6P
Adder
17.909
274734ELWOOD EC;8P
Adder
17.909
274736ELWOOD EC;9P
Adder
17.909
276893AG1-478 C
Solar/Wind Harmer
0.455
270535AF1-215 GEN1
Solar/Wind Harmer
4.946
943121AE2-341 GEN
Solar/Wind Harmer
16.272
943591AF1-030 GEN
Solar/Wind Harmer
10.848
964401AG1-302 GEN
Solar/Wind Harmer
9.751
276694AA1-018 GEN2
Solar/Wind Harmer
6.779
274682WAUKEGAN ;7U
Adder
19.286
274872LEEDK;1U
Solar/Wind Harmer
0.273
276805AD2-038 GEN
Solar/Wind Harmer
5.464
959141AF2-205 GEN
Solar/Wind Harmer
6.424
276799AD1-013 GEN
Solar/Wind Harmer
2.339
946671AF1-331 GEN
Solar/Wind Harmer
0.443
274855GSG-6 ;RU
Solar/Wind Harmer
3.907
274850MENDOTA H;RU
Solar/Wind Harmer
2.716
276602WESTBROOK C
Solar/Wind Harmer
2.249
276863AD2-134 GEN
Solar/Wind Harmer
1.889
972236AH1-702 GEN2
Adder
2.298
274760LEE CO EC;1U
Adder
9.652
274767LEE CO EC;8U
Adder
9.538
24721905FLATG4
Adder
18.408
270102X2-052 ST
50/50
1.83
270100X2-052 CT1
50/50
1.686
270101X2-052 CT2
50/50
1.686
247620Y3-023
50/50
0.556
970615AG2-402 GEN
50/50
2.634
970321AG2-212 GEN
Solar/Wind Harmer
21.006
270216AD2-079_GEN
Solar/Wind Harmer
0.695
270526AF1-158 GEN
Solar/Wind Harmer
5.182
965681AG1-436 GEN
Solar/Wind Harmer
14.237
965791AG1-447 GEN
Solar/Wind Harmer
7.284
24441505OLIV SLR
Solar/Wind Harmer
0.153
957891AF2-083 GEN
Solar/Wind Harmer
3.84
960981AF2-389 GEN
Solar/Wind Harmer
1.721
961051AF2-396 GEN
Solar/Wind Harmer
17.989
961051AF2-396 GEN
Solar/Wind Harmer
8.367
970611AG2-400 GEN
Solar/Wind Harmer
11.324
274770LINCOLN ;1U
Adder
6.925
274771LINCOLN ;2U
Adder
6.925
270471AD2-092_GEN
Solar/Wind Harmer
4.046
274808UNIV PK N;4U
Adder
5.499
274803UNIV PARK;6U
Adder
6.406
972259AH1-714 GEN
Adder
20.95
274888KELLY CRK;1U
Solar/Wind Harmer
6.482
274887GEN-1.85
Solar/Wind Harmer
5.852
276843GEN-1.7
Solar/Wind Harmer
0.63
958011AF2-095 GEN
Solar/Wind Harmer
15.81
274674JOLIET 9 ;6U
Adder
16.785
274847GR RIDGE ;BU
Solar/Wind Harmer
5.504
971573AH1-285 GEN
Solar/Wind Harmer
9.291
274695ROCKY RD ;2P
Adder
11.962
274693ROCKY RD ;1P
Adder
11.844
274697ROCKY RD ;3P
Adder
3.25
274696ROCKY RD ;4P
Adder
12.244
958481AF2-142 GEN
Solar/Wind Harmer
16.113
274861TOP CROP ;1U
Solar/Wind Harmer
6.507
274862TOP CROP ;2U
Solar/Wind Harmer
5.433
274683WAUKEGAN ;8U
Adder
22.593
274683WAUKEGAN ;8U
Adder
19.044
962691AG1-118 GEN
Solar/Wind Harmer
32.066
970921AG2-575 GEN
Solar/Wind Harmer
10.67
970921AG2-575 GEN
Solar/Wind Harmer
2.481
958491AF2-143 GEN
Solar/Wind Harmer
15.976
274879MINONK ;1U
Solar/Wind Harmer
7.163
942991AE2-321 GEN
Solar/Wind Harmer
10.613
274764LEE CO EC;5U
Adder
9.675
274765LEE CO EC;6U
Adder
9.675
274762LEE CO EC;3U
Adder
9.652
274763LEE CO EC;4U
Adder
9.561
972267AH1-718 GEN
Adder
4.289
247621Y3-024
Adder
0.213
971333AH1-146 GEN
Solar/Wind Harmer
10.211
971335AH1-147 GEN
Solar/Wind Harmer
10.211
971599AH1-298 GEN
50/50
10.933
270144AC1-141 ST1_
50/50
2.431
24653605MOTTVILLE
50/50
0.004
24643105BUCHANAN
50/50
0.015
962771AG1-126 GEN
Solar/Wind Harmer
81.683
971347AH1-153 GEN
Solar/Wind Harmer
17.891
270071AF1-092 GEN
Solar/Wind Harmer
17.328
971771AH1-392 GEN
Solar/Wind Harmer
10.32
960681AF2-359 GEN
Solar/Wind Harmer
4.303
971769AH1-391 GEN
Solar/Wind Harmer
11.39
944161AF1-084 GEN
Solar/Wind Harmer
2.49
274775LINCOLN ;6U
Adder
6.925
274776LINCOLN ;7U
Adder
6.925
274777LINCOLN ;8U
Adder
6.925
24729505KEY G4
Adder
7.169
274814UNIV PK N;0U
Adder
5.572
274807UNIV PK N;3U
Adder
5.56
274805UNIV PK N;1U
Adder
5.536
274811UNIV PK N;7U
Adder
5.523
972037AH1-567 GEN1
Adder
0.201
274827FISK ;RP
Adder
8.524
960591AF2-350 GEN
Solar/Wind Harmer
10.979
972227AH1-698 GEN1
Adder
2.862
274687WILL CNTY;4U
Adder
30.524
274687WILL CNTY;4U
Adder
30.524
274675JOLIET 29;7U
Adder
33.487
274675JOLIET 29;7U
Adder
32.291
274731ELWOOD EC;2P
Adder
17.909
274733ELWOOD EC;3P
Adder
17.909
274735ELWOOD EC;4P
Adder
17.909
274728ELWOOD EC;5P
Adder
17.909
270536AF1-215 GEN2
Solar/Wind Harmer
4.946
970833AG2-524 GEN
Solar/Wind Harmer
9.503
970833AG2-524 GEN
Solar/Wind Harmer
4.42
274746AC1-111 G10
Adder
6.056
274744AC1-111 GEN8
Adder
6.056
958391AF2-133 GEN
Solar/Wind Harmer
9.687
971549AH1-272 GEN
Solar/Wind Harmer
19.683
276868AE1-113 GEN
Solar/Wind Harmer
10.743
276882AE2-255 GEN
Solar/Wind Harmer
3.581
971177AH1-047 GEN
Solar/Wind Harmer
6.217
965041AG1-368 GEN
Solar/Wind Harmer
10.597
971675AH1-338 GEN
Solar/Wind Harmer
19.042
971411AH1-196 GEN
Solar/Wind Harmer
15.869
274823ROCKFORD ;21
Adder
20.465
24344105CKG2
50/50
9.236
270143AC1-141 CT2_
50/50
2.745
24639705ELKHART HY
50/50
0.186
970521AG2-332 GEN
50/50
13.241
24307105BERRINSP G
50/50
0.025
962761AG1-125 GEN
Solar/Wind Harmer
81.683
970149AG2-104 GEN
Solar/Wind Harmer
100.878
970155AG2-107 GEN
Solar/Wind Harmer
35.618
970245AG2-165 GEN
Solar/Wind Harmer
21.006
270063AE2-323 C
Solar/Wind Harmer
2.513
270505AE1-170 C O1
Solar/Wind Harmer
17.093
945111AF1-176 GEN
Solar/Wind Harmer
20.281
965011AG1-365 GEN
Solar/Wind Harmer
11.324
270449AD2-020 GEN
Solar/Wind Harmer
3.171
943021AE2-325 GEN
Solar/Wind Harmer
4.12
972207SS24-0001
Solar/Wind Harmer
24.622
274773LINCOLN ;4U
Adder
6.925
274774LINCOLN ;5U
Adder
6.925
270349AD2-093_GEN
Solar/Wind Harmer
4.046
274723RIVER EC ;12
Adder
19.863
274751CRETE EC ;1U
Adder
5.413
274754CRETE EC ;4U
Adder
5.413
276164X3-005 C
Solar/Wind Harmer
0.776
970373AG2-245 GEN
Solar/Wind Harmer
23.188
274812UNIV PK N;8U
Adder
5.523
276776AD2-060 GEN
Solar/Wind Harmer
0.464
274801UNIV PARK;4U
Adder
6.4
941551AE2-152 GEN
Solar/Wind Harmer
4.962
274676JOLIET 29;8U
Adder
33.486
274674JOLIET 9 ;6U
Adder
16.785
274732ELWOOD EC;7P
Adder
17.909
270055AF2-134 C O1
Solar/Wind Harmer
3.297
274871GR RIDGE ;2U
Solar/Wind Harmer
8.367
274745AC1-111 GEN9
Adder
6.056
958381AF2-132 GEN
Solar/Wind Harmer
9.751
276691AA1-018 GEN1
Solar/Wind Harmer
0.5
964861AG1-349 GEN
Solar/Wind Harmer
8.438
971917AH1-482 GEN
Solar/Wind Harmer
9.737
274682WAUKEGAN ;7U
Adder
19.286
274828WAUKEGAN ;BP
Adder
11.843
960751AF2-366 GEN
Solar/Wind Harmer
3.061
962781AG1-127 GEN
Solar/Wind Harmer
10.147
939401AE1-172 GEN
Solar/Wind Harmer
14.86
274872LEEDK;1U
Solar/Wind Harmer
8.749
276901AD2-066 C O1
Solar/Wind Harmer
3.738
971997AH1-543 GEN
Solar/Wind Harmer
16.692
276861AD2-134 GEN
Solar/Wind Harmer
1.889
274822ROCKFORD ;11
Adder
20.615
972235AH1-702 GEN1
Adder
2.643
274761LEE CO EC;2U
Adder
9.652
274766LEE CO EC;7U
Adder
9.538
24721705FLATG2
Adder
18.408
NYPJM->LTFIMP_NY
CLTF
2.961
LGEELTFEXP_LGEE->PJM
CLTF
4.354
WECLTFEXP_WEC->PJM
CLTF
4.001
AG2-052LTFEXP_AG2-052->PJM
LTF
0.249
AH1-155LTFEXP_AH1-155->PJM
LTF
0.374
CPLELTFEXP_CPLE->PJM
CLTF
1.446
CBM West 2LTFEXP_CBM-W2->PJM
CBM
94.727
LAGNLTFEXP_LAGN->PJM
CLTF
12.189
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.026
TVALTFEXP_TVA->PJM
CLTF
5.551
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.664
CBM South 1LTFEXP_CBM-S1->PJM
CBM
21.379
MECLTFEXP_MEC->PJM
CLTF
15.566
SIGELTFEXP_SIGE->PJM
CLTF
0.382

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o AP_P2-2_WP-500-DRT14_SRT-SL


Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-500-DRT14_SRT-SL
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:104.56 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4331.08
MW Contribution:35.24
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
2.57
24641605TWIN BRNCH
50/50
0.019
270475AD2-096_GEN
50/50
6.25
24344005CKG1
50/50
6.999
24642205MAYFLWER
50/50
0.719
970153AG2-106 GEN
Solar/Wind Harmer
35.24
970349AG2-230 GEN
Solar/Wind Harmer
16.9
970513AG2-328 GEN
Solar/Wind Harmer
19.945
970517AG2-330 GEN
Solar/Wind Harmer
18.09
270043AE2-236 GEN
Solar/Wind Harmer
6.129
247643Z2-116 C
Solar/Wind Harmer
0.075
944531AF1-118 GEN
Solar/Wind Harmer
37.271
970031AG2-029 GEN
Solar/Wind Harmer
31.903
959331AF2-224 GEN
Solar/Wind Harmer
10.627
965021AG1-366 GEN
Solar/Wind Harmer
2.471
945111AF1-176 GEN
Solar/Wind Harmer
6.006
274772LINCOLN ;3U
Adder
6.552
274724RIVER EC ;11
Adder
18.546
972231SS25-0005
Solar/Wind Harmer
9.923
972181SS23-001
Solar/Wind Harmer
6.202
274752CRETE EC ;2U
Adder
5.111
274753CRETE EC ;3U
Adder
5.111
970707AG2-453 GEN
Solar/Wind Harmer
29.165
274802UNIV PARK;5U
Adder
6.053
274826FISK ;BP
Adder
11.367
276772AC2-154 GEN
Solar/Wind Harmer
2.894
276806AD2-047 C O1
Solar/Wind Harmer
11.101
970941AG2-585 GEN
Solar/Wind Harmer
12.972
274800UNIV PARK;3U
Adder
6.049
972038AH1-567 GEN2
Adder
0.379
972228AH1-698 GEN2
Adder
3.843
24441205WTRV SLR C
Solar/Wind Harmer
0.14
276897AD1-100 C
Solar/Wind Harmer
30.017
939351AE1-166 GEN
Solar/Wind Harmer
6.133
274676JOLIET 29;8U
Adder
30.524
274729ELWOOD EC;1P
Adder
16.929
274730ELWOOD EC;6P
Adder
16.929
274734ELWOOD EC;8P
Adder
16.929
274736ELWOOD EC;9P
Adder
16.929
276893AG1-478 C
Solar/Wind Harmer
0.43
247604X1-042
Adder
0.428
943121AE2-341 GEN
Solar/Wind Harmer
15.389
943591AF1-030 GEN
Solar/Wind Harmer
10.259
270535AF1-215 GEN1
Solar/Wind Harmer
4.661
276694AA1-018 GEN2
Solar/Wind Harmer
6.407
274682WAUKEGAN ;7U
Adder
18.234
964401AG1-302 GEN
Solar/Wind Harmer
9.192
274872LEEDK;1U
Solar/Wind Harmer
0.258
276805AD2-038 GEN
Solar/Wind Harmer
5.164
959141AF2-205 GEN
Solar/Wind Harmer
6.057
276799AD1-013 GEN
Solar/Wind Harmer
2.212
946671AF1-331 GEN
Solar/Wind Harmer
0.419
274855GSG-6 ;RU
Solar/Wind Harmer
3.694
274850MENDOTA H;RU
Solar/Wind Harmer
2.568
276602WESTBROOK C
Solar/Wind Harmer
2.126
276863AD2-134 GEN
Solar/Wind Harmer
1.786
972236AH1-702 GEN2
Adder
2.173
274760LEE CO EC;1U
Adder
9.125
274767LEE CO EC;8U
Adder
9.017
24721905FLATG4
Adder
18.071
270102X2-052 ST
50/50
1.723
270100X2-052 CT1
50/50
1.588
270101X2-052 CT2
50/50
1.588
247620Y3-023
50/50
0.52
970615AG2-402 GEN
50/50
2.471
970321AG2-212 GEN
Solar/Wind Harmer
19.945
270216AD2-079_GEN
Solar/Wind Harmer
0.652
270471AD2-092_GEN
Solar/Wind Harmer
3.906
965681AG1-436 GEN
Solar/Wind Harmer
13.408
965791AG1-447 GEN
Solar/Wind Harmer
6.86
270526AF1-158 GEN
Solar/Wind Harmer
4.867
24441505OLIV SLR
Solar/Wind Harmer
0.143
957891AF2-083 GEN
Solar/Wind Harmer
3.59
960981AF2-389 GEN
Solar/Wind Harmer
1.609
970611AG2-400 GEN
Solar/Wind Harmer
10.627
961051AF2-396 GEN
Solar/Wind Harmer
16.791
961051AF2-396 GEN
Solar/Wind Harmer
7.81
274770LINCOLN ;1U
Adder
6.552
274771LINCOLN ;2U
Adder
6.552
274808UNIV PK N;4U
Adder
5.195
972259AH1-714 GEN
Adder
19.81
274803UNIV PARK;6U
Adder
6.053
274888KELLY CRK;1U
Solar/Wind Harmer
6.127
274887GEN-1.85
Solar/Wind Harmer
5.531
276843GEN-1.7
Solar/Wind Harmer
0.595
958011AF2-095 GEN
Solar/Wind Harmer
14.944
274674JOLIET 9 ;6U
Adder
15.867
274847GR RIDGE ;BU
Solar/Wind Harmer
5.204
971573AH1-285 GEN
Solar/Wind Harmer
8.786
274696ROCKY RD ;4P
Adder
11.577
274695ROCKY RD ;2P
Adder
11.31
274693ROCKY RD ;1P
Adder
11.199
274697ROCKY RD ;3P
Adder
3.072
958481AF2-142 GEN
Solar/Wind Harmer
15.23
274861TOP CROP ;1U
Solar/Wind Harmer
6.15
274862TOP CROP ;2U
Solar/Wind Harmer
5.135
274683WAUKEGAN ;8U
Adder
21.36
274683WAUKEGAN ;8U
Adder
18.005
962691AG1-118 GEN
Solar/Wind Harmer
30.32
970921AG2-575 GEN
Solar/Wind Harmer
10.088
970921AG2-575 GEN
Solar/Wind Harmer
2.346
958491AF2-143 GEN
Solar/Wind Harmer
15.1
942991AE2-321 GEN
Solar/Wind Harmer
10.034
274879MINONK ;1U
Solar/Wind Harmer
6.77
274764LEE CO EC;5U
Adder
9.146
274765LEE CO EC;6U
Adder
9.146
274762LEE CO EC;3U
Adder
9.125
274763LEE CO EC;4U
Adder
9.039
972267AH1-718 GEN
Adder
4.055
971333AH1-146 GEN
Solar/Wind Harmer
18.98
971335AH1-147 GEN
Solar/Wind Harmer
18.98
971599AH1-298 GEN
50/50
10.378
270144AC1-141 ST1_
50/50
2.276
24653605MOTTVILLE
50/50
0.004
24643105BUCHANAN
50/50
0.014
962771AG1-126 GEN
Solar/Wind Harmer
80.816
971347AH1-153 GEN
Solar/Wind Harmer
16.9
270071AF1-092 GEN
Solar/Wind Harmer
16.402
971771AH1-392 GEN
Solar/Wind Harmer
9.684
960681AF2-359 GEN
Solar/Wind Harmer
4.052
971769AH1-391 GEN
Solar/Wind Harmer
10.7
274775LINCOLN ;6U
Adder
6.552
274776LINCOLN ;7U
Adder
6.552
274777LINCOLN ;8U
Adder
6.552
944161AF1-084 GEN
Solar/Wind Harmer
2.319
24729505KEY G4
Adder
6.795
274814UNIV PK N;0U
Adder
5.263
274807UNIV PK N;3U
Adder
5.252
274805UNIV PK N;1U
Adder
5.229
274811UNIV PK N;7U
Adder
5.217
972037AH1-567 GEN1
Adder
0.19
274827FISK ;RP
Adder
8.056
960591AF2-350 GEN
Solar/Wind Harmer
10.377
972227AH1-698 GEN1
Adder
2.706
274687WILL CNTY;4U
Adder
28.853
274687WILL CNTY;4U
Adder
28.853
274675JOLIET 29;7U
Adder
31.655
274675JOLIET 29;7U
Adder
30.525
274731ELWOOD EC;2P
Adder
16.929
274733ELWOOD EC;3P
Adder
16.929
274735ELWOOD EC;4P
Adder
16.929
274728ELWOOD EC;5P
Adder
16.929
970833AG2-524 GEN
Solar/Wind Harmer
8.985
970833AG2-524 GEN
Solar/Wind Harmer
4.179
270536AF1-215 GEN2
Solar/Wind Harmer
4.661
274746AC1-111 G10
Adder
5.726
274744AC1-111 GEN8
Adder
5.726
958391AF2-133 GEN
Solar/Wind Harmer
9.133
276868AE1-113 GEN
Solar/Wind Harmer
10.155
276882AE2-255 GEN
Solar/Wind Harmer
3.385
971177AH1-047 GEN
Solar/Wind Harmer
5.878
270284AF1-227 GEN1
Solar/Wind Harmer
5.666
270286AF1-227 GEN2
Solar/Wind Harmer
2.096
270287AF1-227 GEN3
Solar/Wind Harmer
2.096
971675AH1-338 GEN
Solar/Wind Harmer
18.004
971411AH1-196 GEN
Solar/Wind Harmer
15.003
274823ROCKFORD ;21
Adder
19.348
24344105CKG2
50/50
8.741
270143AC1-141 CT2_
50/50
2.57
24639705ELKHART HY
50/50
0.174
970521AG2-332 GEN
50/50
12.397
962761AG1-125 GEN
Solar/Wind Harmer
80.816
970149AG2-104 GEN
Solar/Wind Harmer
99.808
970155AG2-107 GEN
Solar/Wind Harmer
35.24
970245AG2-165 GEN
Solar/Wind Harmer
19.945
270349AD2-093_GEN
Solar/Wind Harmer
3.906
270063AE2-323 C
Solar/Wind Harmer
2.355
270505AE1-170 C O1
Solar/Wind Harmer
15.976
965011AG1-365 GEN
Solar/Wind Harmer
10.627
945111AF1-176 GEN
Solar/Wind Harmer
18.951
972207SS24-0001
Solar/Wind Harmer
23.296
274773LINCOLN ;4U
Adder
6.552
274774LINCOLN ;5U
Adder
6.552
270449AD2-020 GEN
Solar/Wind Harmer
2.958
943021AE2-325 GEN
Solar/Wind Harmer
3.843
274723RIVER EC ;12
Adder
18.763
274751CRETE EC ;1U
Adder
5.111
274754CRETE EC ;4U
Adder
5.111
276164X3-005 C
Solar/Wind Harmer
0.734
274812UNIV PK N;8U
Adder
5.217
970373AG2-245 GEN
Solar/Wind Harmer
21.845
276776AD2-060 GEN
Solar/Wind Harmer
0.439
274801UNIV PARK;4U
Adder
6.049
941551AE2-152 GEN
Solar/Wind Harmer
4.691
274676JOLIET 29;8U
Adder
31.655
274674JOLIET 9 ;6U
Adder
15.867
274732ELWOOD EC;7P
Adder
16.929
274871GR RIDGE ;2U
Solar/Wind Harmer
7.911
270055AF2-134 C O1
Solar/Wind Harmer
3.107
274745AC1-111 GEN9
Adder
5.726
276691AA1-018 GEN1
Solar/Wind Harmer
0.473
274682WAUKEGAN ;7U
Adder
18.234
274828WAUKEGAN ;BP
Adder
11.196
958381AF2-132 GEN
Solar/Wind Harmer
9.192
964861AG1-349 GEN
Solar/Wind Harmer
7.954
971917AH1-482 GEN
Solar/Wind Harmer
9.179
960751AF2-366 GEN
Solar/Wind Harmer
2.894
962781AG1-127 GEN
Solar/Wind Harmer
9.594
939401AE1-172 GEN
Solar/Wind Harmer
14.049
274872LEEDK;1U
Solar/Wind Harmer
8.273
276901AD2-066 C O1
Solar/Wind Harmer
3.534
971997AH1-543 GEN
Solar/Wind Harmer
15.781
276861AD2-134 GEN
Solar/Wind Harmer
1.786
274822ROCKFORD ;11
Adder
19.489
972235AH1-702 GEN1
Adder
2.499
274761LEE CO EC;2U
Adder
9.125
274766LEE CO EC;7U
Adder
9.017
24721705FLATG2
Adder
18.071
NYPJM->LTFIMP_NY
CLTF
2.724
LGEELTFEXP_LGEE->PJM
CLTF
4.084
WECLTFEXP_WEC->PJM
CLTF
3.783
AG2-052LTFEXP_AG2-052->PJM
LTF
0.235
AH1-155LTFEXP_AH1-155->PJM
LTF
0.353
CPLELTFEXP_CPLE->PJM
CLTF
1.375
CBM West 2LTFEXP_CBM-W2->PJM
CBM
89.414
LAGNLTFEXP_LAGN->PJM
CLTF
11.516
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.671
TVALTFEXP_TVA->PJM
CLTF
5.244
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.32
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.167
MECLTFEXP_MEC->PJM
CLTF
14.71
SIGELTFEXP_SIGE->PJM
CLTF
0.36

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.2 %
Rating:4142.0 MVA
Rating Type:A
MVA to Mitigate:4150.44
MW Contribution:43.57
Bus #Bus NameTypeMW Contribution
971599AH1-298 GEN
50/50
10.4
270144AC1-141 ST1_
50/50
2.281
24653605MOTTVILLE
50/50
0.004
24643105BUCHANAN
50/50
0.014
962771AG1-126 GEN
Solar/Wind Harmer
68.224
971347AH1-153 GEN
Solar/Wind Harmer
11.817
270071AF1-092 GEN
Solar/Wind Harmer
14.657
971771AH1-392 GEN
Solar/Wind Harmer
7.525
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971769AH1-391 GEN
Solar/Wind Harmer
8.356
971619AH1-309 GEN
Solar/Wind Harmer
3.352
274775LINCOLN ;6U
Adder
8.941
274776LINCOLN ;7U
Adder
8.941
274777LINCOLN ;8U
Adder
8.941
24729505KEY G4
Adder
6.812
274814UNIV PK N;0U
Adder
5.276
274807UNIV PK N;3U
Adder
5.265
274805UNIV PK N;1U
Adder
5.242
274811UNIV PK N;7U
Adder
5.23
274827FISK ;RP
Adder
8.075
972037AH1-567 GEN1
Adder
0.19
960591AF2-350 GEN
Solar/Wind Harmer
7.258
972227AH1-698 GEN1
Adder
2.712
274687WILL CNTY;4U
Adder
28.924
274687WILL CNTY;4U
Adder
28.924
274675JOLIET 29;7U
Adder
31.734
274675JOLIET 29;7U
Adder
30.6
274731ELWOOD EC;2P
Adder
16.971
274733ELWOOD EC;3P
Adder
16.971
274735ELWOOD EC;4P
Adder
16.971
274728ELWOOD EC;5P
Adder
16.972
970833AG2-524 GEN
Solar/Wind Harmer
7.918
970833AG2-524 GEN
Solar/Wind Harmer
5.279
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
274746AC1-111 G10
Adder
5.741
274744AC1-111 GEN8
Adder
5.741
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.408
276882AE2-255 GEN
Solar/Wind Harmer
0.821
971177AH1-047 GEN
Solar/Wind Harmer
4.327
270284AF1-227 GEN1
Solar/Wind Harmer
0.009
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
971675AH1-338 GEN
Solar/Wind Harmer
2.729
971411AH1-196 GEN
Solar/Wind Harmer
10.494
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
971611AH1-305 GEN
Solar/Wind Harmer
4.147
971171AH1-044 GEN
Solar/Wind Harmer
13.927
274823ROCKFORD ;21
Adder
19.398
276612AE2-035 GEN
Solar/Wind Harmer
0.002
965041AG1-368 GEN
Solar/Wind Harmer
6.907
926823AC1-168 GEN
Solar/Wind Harmer
1.173
970169AG2-114 GEN
Solar/Wind Harmer
6.898
971681AH1-341 GEN
Solar/Wind Harmer
11.079
965101AG1-375 GEN
Solar/Wind Harmer
6.878
963791AG1-232 GEN
Solar/Wind Harmer
9.223
961011AF2-392 GEN
Solar/Wind Harmer
4.004
957751AF2-069 GEN
Solar/Wind Harmer
0.224
971549AH1-272 GEN
Solar/Wind Harmer
14.025
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
965051AG1-369 GEN
Solar/Wind Harmer
3.359
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.06
941731AE2-173 GEN
Solar/Wind Harmer
5.603
946321AF1-296 GEN
Solar/Wind Harmer
3.736
945581AF1-223 GEN
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
963841AG1-237 GEN
Solar/Wind Harmer
2.803
970289AG2-191 GEN
Solar/Wind Harmer
1.217
971609AH1-304 GEN
Solar/Wind Harmer
1.046
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.808
276849AB2-070 GEN2
Solar/Wind Harmer
0.233
276848AB2-070 GEN3
Solar/Wind Harmer
0.232
270594AE1-207 GEN
Solar/Wind Harmer
7.078
270024AE2-089 GEN
Solar/Wind Harmer
0.007
270578AF1-285 GEN2
Solar/Wind Harmer
0.412
247607V1-011 GEN
Solar/Wind Harmer
0.001
970115AG2-085 GEN
Solar/Wind Harmer
2.44
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
270142AC1-141 CT1_
50/50
2.576
24641605TWIN BRNCH
50/50
0.019
270475AD2-096_GEN
50/50
6.265
24344005CKG1
50/50
7.016
24642205MAYFLWER
50/50
0.721
970153AG2-106 GEN
Solar/Wind Harmer
43.566
970349AG2-230 GEN
Solar/Wind Harmer
11.817
970513AG2-328 GEN
Solar/Wind Harmer
3.385
970517AG2-330 GEN
Solar/Wind Harmer
20.307
270043AE2-236 GEN
Solar/Wind Harmer
5
247643Z2-116 C
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
33.376
970031AG2-029 GEN
Solar/Wind Harmer
4.834
959331AF2-224 GEN
Solar/Wind Harmer
5.202
965021AG1-366 GEN
Solar/Wind Harmer
2.477
945111AF1-176 GEN
Solar/Wind Harmer
6.021
274772LINCOLN ;3U
Adder
8.941
274724RIVER EC ;11
Adder
18.592
274752CRETE EC ;2U
Adder
8.637
274753CRETE EC ;3U
Adder
8.637
970707AG2-453 GEN
Solar/Wind Harmer
23.798
274826FISK ;BP
Adder
11.395
274802UNIV PARK;5U
Adder
6.068
276806AD2-047 C O1
Solar/Wind Harmer
4.113
970941AG2-585 GEN
Solar/Wind Harmer
9.072
274800UNIV PARK;3U
Adder
6.064
972038AH1-567 GEN2
Adder
0.38
972228AH1-698 GEN2
Adder
3.852
24441205WTRV SLR C
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
0.01
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
30.6
274729ELWOOD EC;1P
Adder
16.971
274730ELWOOD EC;6P
Adder
16.972
274734ELWOOD EC;8P
Adder
16.972
274736ELWOOD EC;9P
Adder
16.972
276893AG1-478 C
Solar/Wind Harmer
0.285
247604X1-042
Adder
0.429
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
943121AE2-341 GEN
Solar/Wind Harmer
12.031
943591AF1-030 GEN
Solar/Wind Harmer
8
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
18.28
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.258
276805AD2-038 GEN
Solar/Wind Harmer
0.002
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.747
270102X2-052 ST
50/50
1.727
270100X2-052 CT1
50/50
1.592
270101X2-052 CT2
50/50
1.592
247620Y3-023
50/50
0.521
970615AG2-402 GEN
50/50
2.477
970321AG2-212 GEN
Solar/Wind Harmer
3.385
270216AD2-079_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.006
965681AG1-436 GEN
Solar/Wind Harmer
9.376
965791AG1-447 GEN
Solar/Wind Harmer
6.876
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
7.432
970627AG2-408 GEN
Solar/Wind Harmer
2.23
961051AF2-396 GEN
Solar/Wind Harmer
14.796
961051AF2-396 GEN
Solar/Wind Harmer
9.864
274770LINCOLN ;1U
Adder
8.941
274771LINCOLN ;2U
Adder
8.941
274808UNIV PK N;4U
Adder
5.207
972259AH1-714 GEN
Adder
19.859
274803UNIV PARK;6U
Adder
6.068
274888KELLY CRK;1U
Solar/Wind Harmer
0.426
274887GEN-1.85
Solar/Wind Harmer
0.191
276843GEN-1.7
Solar/Wind Harmer
0.235
958011AF2-095 GEN
Solar/Wind Harmer
10.451
274674JOLIET 9 ;6U
Adder
15.907
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
971573AH1-285 GEN
Solar/Wind Harmer
1.332
274695ROCKY RD ;2P
Adder
11.339
274693ROCKY RD ;1P
Adder
11.227
274697ROCKY RD ;3P
Adder
3.08
274696ROCKY RD ;4P
Adder
11.606
958481AF2-142 GEN
Solar/Wind Harmer
10.652
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.96
274683WAUKEGAN ;8U
Adder
21.414
274683WAUKEGAN ;8U
Adder
18.051
962691AG1-118 GEN
Solar/Wind Harmer
21.207
970921AG2-575 GEN
Solar/Wind Harmer
7.056
970921AG2-575 GEN
Solar/Wind Harmer
2.352
958491AF2-143 GEN
Solar/Wind Harmer
10.561
942991AE2-321 GEN
Solar/Wind Harmer
7.837
274879MINONK ;1U
Solar/Wind Harmer
0.296
971333AH1-146 GEN
Solar/Wind Harmer
13.985
971335AH1-147 GEN
Solar/Wind Harmer
13.985
944541AF1-119 GEN
Solar/Wind Harmer
0.468
960971AF2-388 GEN
Solar/Wind Harmer
4.1
971341AH1-150 GEN
Solar/Wind Harmer
13.927
971343AH1-151 GEN
Solar/Wind Harmer
13.927
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
274856ECOGROVE ;U1
Solar/Wind Harmer
0.163
276611AD2-172 GEN
Solar/Wind Harmer
0.002
938861AE1-114 GEN
Solar/Wind Harmer
3.898
274764LEE CO EC;5U
Adder
9.17
274765LEE CO EC;6U
Adder
9.17
274762LEE CO EC;3U
Adder
9.148
274763LEE CO EC;4U
Adder
9.062
276603SUBLETTE C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
972267AH1-718 GEN
Adder
4.066
276741O09 GEN1
Solar/Wind Harmer
0.242
276708O09 GEN2
Solar/Wind Harmer
0.242
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.267
276646AC1-214 GEN2
Solar/Wind Harmer
0.267
276782AC1-033 GEN
Solar/Wind Harmer
0.001
942221AE2-234 GEN
Solar/Wind Harmer
0.034
960611AF2-352 GEN
Solar/Wind Harmer
2.214
966841AG1-555 GEN
Solar/Wind Harmer
0.746
270599AE1-208 GEN
Solar/Wind Harmer
5.869
270031AE2-169
Solar/Wind Harmer
3.522
246938BC-WTG3
Solar/Wind Harmer
0.231
246937BC-WTG2
Solar/Wind Harmer
0.259
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
970241AG2-163 GEN
Solar/Wind Harmer
3.704
971613AH1-306 GEN
Solar/Wind Harmer
3.033
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
274855GSG-6 ;RU
Solar/Wind Harmer
0.257
274850MENDOTA H;RU
Solar/Wind Harmer
0.082
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.125
959091AF2-200 GEN
Solar/Wind Harmer
13.927
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
2.178
970571AG2-364 GEN
Solar/Wind Harmer
13.8
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
9.148
274767LEE CO EC;8U
Adder
9.041
276157O29GEN1
Solar/Wind Harmer
1.1
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.767
274878BISHOP HL;2U
Solar/Wind Harmer
0.227
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.043
942111AE2-223 GEN
Solar/Wind Harmer
2.185
965931AG1-462 GEN
Solar/Wind Harmer
16.944
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
19.925
959611AF2-252 GEN
Solar/Wind Harmer
2.214
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.704
970291AG2-192 GEN
Solar/Wind Harmer
0.64
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
2.949
270491AE1-102 GEN2
Solar/Wind Harmer
0.83
276668AB2-070 GEN1
Solar/Wind Harmer
0.233
276621W2-048 GEN
Solar/Wind Harmer
0.318
276838X2-022 GEN2
Solar/Wind Harmer
0.355
971617AH1-308 GEN
Solar/Wind Harmer
5.233
24721905FLATG4
Adder
18.123
270391AF1-285 GEN3
Solar/Wind Harmer
0.412
958821AF2-173 GEN
Solar/Wind Harmer
8.644
270004AE1-209 GEN
Solar/Wind Harmer
1.338
942481AE2-261 GEN
Solar/Wind Harmer
18.406
270258AD1-119 GEN
Solar/Wind Harmer
0.002
270404AC1-167 GEN
Solar/Wind Harmer
0.003
946031AF1-268 GEN
Solar/Wind Harmer
5.724
270231U2-072_GEN5
Solar/Wind Harmer
0.001
270007AE1-245 C
Solar/Wind Harmer
0.002
276916AD2-100_GEN
Solar/Wind Harmer
12.852
276911AD2-131_GEN
Solar/Wind Harmer
0.847
960441AF2-335 GEN
Solar/Wind Harmer
6.101
970623AG2-406 GEN
Solar/Wind Harmer
1.115
970825AG2-519 GEN
Solar/Wind Harmer
6.738
24344105CKG2
50/50
8.761
270143AC1-141 CT2_
50/50
2.576
24639705ELKHART HY
50/50
0.174
970521AG2-332 GEN
50/50
12.426
962761AG1-125 GEN
Solar/Wind Harmer
68.224
970149AG2-104 GEN
Solar/Wind Harmer
73.684
970155AG2-107 GEN
Solar/Wind Harmer
43.566
970245AG2-165 GEN
Solar/Wind Harmer
3.385
270349AD2-093_GEN
Solar/Wind Harmer
0.006
270063AE2-323 C
Solar/Wind Harmer
0.006
270505AE1-170 C O1
Solar/Wind Harmer
7.821
965011AG1-365 GEN
Solar/Wind Harmer
7.432
945111AF1-176 GEN
Solar/Wind Harmer
13.254
274773LINCOLN ;4U
Adder
8.941
274774LINCOLN ;5U
Adder
8.941
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
3.852
274723RIVER EC ;12
Adder
18.809
274751CRETE EC ;1U
Adder
8.637
274754CRETE EC ;4U
Adder
8.637
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
5.23
970373AG2-245 GEN
Solar/Wind Harmer
15.278
276776AD2-060 GEN
Solar/Wind Harmer
0.758
274801UNIV PARK;4U
Adder
6.064
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
31.733
274674JOLIET 9 ;6U
Adder
15.907
274732ELWOOD EC;7P
Adder
16.972
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0.006
274745AC1-111 GEN9
Adder
5.741
276691AA1-018 GEN1
Solar/Wind Harmer
0.86
274682WAUKEGAN ;7U
Adder
18.28
274828WAUKEGAN ;BP
Adder
11.225
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.202
962781AG1-127 GEN
Solar/Wind Harmer
6.715
939401AE1-172 GEN
Solar/Wind Harmer
5.274
274872LEEDK;1U
Solar/Wind Harmer
0.004
276901AD2-066 C O1
Solar/Wind Harmer
0.007
971997AH1-543 GEN
Solar/Wind Harmer
3.679
276861AD2-134 GEN
Solar/Wind Harmer
0.125
965651AG1-433 GEN
Solar/Wind Harmer
2.05
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.708
957471AF2-041 GEN
Solar/Wind Harmer
20.89
959081AF2-199 GEN
Solar/Wind Harmer
6.963
971067AG2-660 GEN
Solar/Wind Harmer
2.321
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
274822ROCKFORD ;11
Adder
19.54
972235AH1-702 GEN1
Adder
2.505
970819AG2-516 GEN
Solar/Wind Harmer
8.301
971475AH1-234 GEN
Solar/Wind Harmer
3.35
970569AG2-363 GEN
Solar/Wind Harmer
20.699
958861AF2-177 GEN
Solar/Wind Harmer
2.981
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
9.148
274766LEE CO EC;7U
Adder
9.041
276158O29GEN2
Solar/Wind Harmer
0.001
24791305MDL-5G
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.227
247521TR3_G114
Solar/Wind Harmer
0.245
270246TR4_N_V150
Solar/Wind Harmer
0.043
276726Z2-087_GEN
Solar/Wind Harmer
0.002
939741AE1-205 GEN
Solar/Wind Harmer
9.414
945371AF1-202 GEN
Solar/Wind Harmer
0.001
944231AF1-091 GEN
Solar/Wind Harmer
1.771
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.002
24695305TIMB G C
Solar/Wind Harmer
0.002
972175AH1-670 GEN
Solar/Wind Harmer
5.377
965421AG1-410 GEN
Solar/Wind Harmer
19.447
970291AG2-192 GEN
Solar/Wind Harmer
0.832
274880W4-005 GEN4
Solar/Wind Harmer
0.001
246936BC-WTG1
Solar/Wind Harmer
0.259
270489AE1-102 GEN1
Solar/Wind Harmer
0.83
963831AG1-236 GEN
Solar/Wind Harmer
2.479
963741AG1-226 GEN
Solar/Wind Harmer
15.028
270032AE2-172
Solar/Wind Harmer
4.213
276615X2-022 GEN
Solar/Wind Harmer
0.066
24721705FLATG2
Adder
18.123
270223U2-072_GEN1
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
6.907
270005AE1-210 C O1
Solar/Wind Harmer
1.338
965031AG1-367 GEN
Solar/Wind Harmer
6.174
965911AG1-460 GEN
Solar/Wind Harmer
1.231
970825AG2-519 GEN
Solar/Wind Harmer
2.158
NYPJM->LTFIMP_NY
CLTF
2.707
LGEELTFEXP_LGEE->PJM
CLTF
4.102
WECLTFEXP_WEC->PJM
CLTF
3.793
AG2-052LTFEXP_AG2-052->PJM
LTF
0.236
AH1-155LTFEXP_AH1-155->PJM
LTF
0.353
CPLELTFEXP_CPLE->PJM
CLTF
1.403
CBM West 2LTFEXP_CBM-W2->PJM
CBM
89.76
LAGNLTFEXP_LAGN->PJM
CLTF
11.568
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.749
TVALTFEXP_TVA->PJM
CLTF
5.27
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.695
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.264
MECLTFEXP_MEC->PJM
CLTF
14.753
SIGELTFEXP_SIGE->PJM
CLTF
0.361

Details for 05MALISX-05MALIS 138.0 kV Ckt ZB line l/o AEP_P4_#7216_05VASSEL 765_B1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MALISX-05MALIS 138.0 kV Ckt ZB line
Contingency Name:
AEP_P4_#7216_05VASSEL 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.12 %
Rating:1054.0 MVA
Rating Type:B
MVA to Mitigate:1055.3
MW Contribution:10.83
Bus #Bus NameTypeMW Contribution
962761AG1-125 GEN
Solar/Wind Harmer
24.827
970149AG2-104 GEN
Solar/Wind Harmer
30.661
970155AG2-107 GEN
Solar/Wind Harmer
10.826
962771AG1-126 GEN
Solar/Wind Harmer
24.827
270520AE2-214 GEN
Solar/Wind Helper
2.927
270054AF2-122 C O1
Solar/Wind Helper
0.755
970153AG2-106 GEN
Solar/Wind Harmer
10.826
241955AC1-078 GEN
Solar/Wind Helper
0.999
946101AF1-275 GEN
Solar/Wind Helper
0.367
NYPJM->LTFIMP_NY
CLTF
0.461
LGEELTFEXP_LGEE->PJM
CLTF
0.437
WECLTFEXP_WEC->PJM
CLTF
0.832
CPLELTFEXP_CPLE->PJM
CLTF
0.326
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.471
LAGNLTFEXP_LAGN->PJM
CLTF
2.146
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.364
TVALTFEXP_TVA->PJM
CLTF
0.92
CBM West 1LTFEXP_CBM-W1->PJM
CBM
24.357
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.264
MECLTFEXP_MEC->PJM
CLTF
3.093
SIGELTFEXP_SIGE->PJM
CLTF
0.055

Details for 05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#711_05MARYSV 765_A1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
Contingency Name:
AEP_P4_#711_05MARYSV 765_A1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.69 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3397.1
MW Contribution:34.1
Bus #Bus NameTypeMW Contribution
970321AG2-212 GEN
Solar/Wind Harmer
10.845
274770LINCOLN ;1U
Adder
3.364
274771LINCOLN ;2U
Adder
3.364
965681AG1-436 GEN
Solar/Wind Harmer
6.595
965791AG1-447 GEN
Solar/Wind Harmer
3.374
972259AH1-714 GEN
Adder
10.035
274888KELLY CRK;1U
Solar/Wind Harmer
3.083
274887GEN-1.85
Solar/Wind Harmer
2.783
276843GEN-1.7
Solar/Wind Harmer
0.299
958011AF2-095 GEN
Solar/Wind Harmer
7.52
274803UNIV PARK;6U
Adder
3.039
274808UNIV PK N;4U
Adder
2.597
274847GR RIDGE ;BU
Solar/Wind Harmer
2.625
274674JOLIET 9 ;6U
Adder
7.988
971573AH1-285 GEN
Solar/Wind Harmer
4.438
24441505OLIV SLR
Solar/Wind Harmer
0.069
274696ROCKY RD ;4P
Adder
5.826
274695ROCKY RD ;2P
Adder
5.692
274693ROCKY RD ;1P
Adder
5.636
274697ROCKY RD ;3P
Adder
1.546
270526AF1-158 GEN
Solar/Wind Harmer
2.32
274683WAUKEGAN ;8U
Adder
10.733
274683WAUKEGAN ;8U
Adder
9.047
962691AG1-118 GEN
Solar/Wind Harmer
15.245
958481AF2-142 GEN
Solar/Wind Harmer
7.607
970921AG2-575 GEN
Solar/Wind Harmer
5.069
970921AG2-575 GEN
Solar/Wind Harmer
1.179
274861TOP CROP ;1U
Solar/Wind Harmer
3.071
274862TOP CROP ;2U
Solar/Wind Harmer
2.564
942991AE2-321 GEN
Solar/Wind Harmer
5.03
958491AF2-143 GEN
Solar/Wind Harmer
7.519
971333AH1-146 GEN
Solar/Wind Harmer
10.012
971335AH1-147 GEN
Solar/Wind Harmer
10.012
274879MINONK ;1U
Solar/Wind Harmer
3.372
971341AH1-150 GEN
Solar/Wind Harmer
9.956
971343AH1-151 GEN
Solar/Wind Harmer
9.956
276872AE1-163_GEN1
Solar/Wind Harmer
3.313
274856ECOGROVE ;U1
Solar/Wind Harmer
1.662
276611AD2-172 GEN
Solar/Wind Harmer
1.261
938861AE1-114 GEN
Solar/Wind Harmer
4.014
274764LEE CO EC;5U
Adder
4.55
274765LEE CO EC;6U
Adder
4.55
274762LEE CO EC;3U
Adder
4.539
274763LEE CO EC;4U
Adder
4.497
972267AH1-718 GEN
Adder
2.012
247620Y3-023
Adder
0.206
270471AD2-092_GEN
Solar/Wind Helper
4.665
270224U2-072_GEN2
Solar/Wind Helper
1.522
270227U2-072_GEN3
Solar/Wind Helper
1.522
270228U2-072_GEN4
Solar/Wind Helper
1.522
270231U2-072_GEN5
Solar/Wind Helper
1.522
946101AF1-275 GEN
Solar/Wind Helper
0.783
241960AC2-195 GEN
Solar/Wind Helper
1.825
253378AE2-206_GEN
Solar/Wind Helper
1.285
276820AF1-078_GEN
Solar/Wind Helper
0.6
270518AE2-148 GEN
Solar/Wind Helper
10.557
24721805FLATG3
50/50
1.058
24721705FLATG2
50/50
19.393
962761AG1-125 GEN
Solar/Wind Harmer
78.213
970149AG2-104 GEN
Solar/Wind Harmer
96.593
970155AG2-107 GEN
Solar/Wind Harmer
34.105
970245AG2-165 GEN
Solar/Wind Harmer
10.845
972207SS24-0001
Solar/Wind Harmer
11.962
274773LINCOLN ;4U
Adder
3.364
274774LINCOLN ;5U
Adder
3.364
276164X3-005 C
Solar/Wind Harmer
0.369
274723RIVER EC ;12
Adder
9.397
276776AD2-060 GEN
Solar/Wind Harmer
0.221
941551AE2-152 GEN
Solar/Wind Harmer
2.366
274801UNIV PARK;4U
Adder
3.041
274812UNIV PK N;8U
Adder
2.608
274751CRETE EC ;1U
Adder
2.543
274754CRETE EC ;4U
Adder
2.543
274676JOLIET 29;8U
Adder
15.941
274871GR RIDGE ;2U
Solar/Wind Harmer
3.99
274674JOLIET 9 ;6U
Adder
7.988
274732ELWOOD EC;7P
Adder
8.515
274745AC1-111 GEN9
Adder
2.891
274682WAUKEGAN ;7U
Adder
9.164
274828WAUKEGAN ;BP
Adder
5.626
276691AA1-018 GEN1
Solar/Wind Harmer
0.236
960751AF2-366 GEN
Solar/Wind Harmer
1.454
962781AG1-127 GEN
Solar/Wind Harmer
4.821
274872LEEDK;1U
Solar/Wind Harmer
4.155
970373AG2-245 GEN
Solar/Wind Harmer
10.535
939401AE1-172 GEN
Solar/Wind Harmer
6.99
276901AD2-066 C O1
Solar/Wind Harmer
1.76
276861AD2-134 GEN
Solar/Wind Harmer
0.895
971997AH1-543 GEN
Solar/Wind Harmer
7.867
957471AF2-041 GEN
Solar/Wind Harmer
14.934
959081AF2-199 GEN
Solar/Wind Harmer
4.978
971067AG2-660 GEN
Solar/Wind Harmer
1.158
274822ROCKFORD ;11
Adder
9.739
972235AH1-702 GEN1
Adder
1.248
970819AG2-516 GEN
Solar/Wind Harmer
5.922
276876AE1-163_GEN2
Solar/Wind Harmer
3.313
971475AH1-234 GEN
Solar/Wind Harmer
11.028
270055AF2-134 C O1
Solar/Wind Harmer
1.486
274857EASY ROAD;U1
Solar/Wind Harmer
2.338
274761LEE CO EC;2U
Adder
4.539
274766LEE CO EC;7U
Adder
4.486
24639705ELKHART HY
Adder
0.072
270349AD2-093_GEN
Solar/Wind Helper
4.665
270223U2-072_GEN1
Solar/Wind Helper
1.522
270578AF1-285 GEN2
Solar/Wind Helper
1.031
270391AF1-285 GEN3
Solar/Wind Helper
1.031
270462AD2-086
Solar/Wind Helper
5.319
247522W1-056 GEN
Solar/Wind Helper
1.149
253343AC1-166 GEN
Solar/Wind Helper
0.826
253325AC1-069 GEN
Solar/Wind Helper
0.856
960841AF2-375 GEN
Solar/Wind Helper
1.143
958961AF2-187 GEN
Solar/Wind Helper
1.121
270263AC1-001 GEN
Solar/Wind Helper
0.539
241840AF1-064_GEN
Solar/Wind Helper
0.473
241807AE2-176_GEN
Solar/Wind Helper
0.695
970569AG2-363 GEN
Solar/Wind Harmer
9.509
24722005FLATG5
50/50
1.058
24721905FLATG4
50/50
19.393
970153AG2-106 GEN
Solar/Wind Harmer
34.105
970513AG2-328 GEN
Solar/Wind Harmer
10.845
970517AG2-330 GEN
Solar/Wind Harmer
9.837
970349AG2-230 GEN
Solar/Wind Harmer
8.723
274772LINCOLN ;3U
Adder
3.364
970707AG2-453 GEN
Solar/Wind Harmer
14.859
274724RIVER EC ;11
Adder
9.292
972228AH1-698 GEN2
Adder
1.937
276772AC2-154 GEN
Solar/Wind Harmer
1.456
276806AD2-047 C O1
Solar/Wind Harmer
5.586
970941AG2-585 GEN
Solar/Wind Harmer
6.528
274826FISK ;BP
Adder
5.714
276897AD1-100 C
Solar/Wind Harmer
15.138
939351AE1-166 GEN
Solar/Wind Harmer
3.093
274800UNIV PARK;3U
Adder
3.041
972038AH1-567 GEN2
Adder
0.19
274802UNIV PARK;5U
Adder
3.039
972231SS25-0005
Solar/Wind Harmer
4.937
972181SS23-001
Solar/Wind Harmer
3.086
274752CRETE EC ;2U
Adder
2.543
274753CRETE EC ;3U
Adder
2.543
274676JOLIET 29;8U
Adder
15.371
943121AE2-341 GEN
Solar/Wind Harmer
7.785
943591AF1-030 GEN
Solar/Wind Harmer
5.19
274729ELWOOD EC;1P
Adder
8.515
274730ELWOOD EC;6P
Adder
8.515
274734ELWOOD EC;8P
Adder
8.515
274736ELWOOD EC;9P
Adder
8.515
276893AG1-478 C
Solar/Wind Harmer
0.216
274682WAUKEGAN ;7U
Adder
9.164
276694AA1-018 GEN2
Solar/Wind Harmer
3.2
274872LEEDK;1U
Solar/Wind Harmer
0.129
276805AD2-038 GEN
Solar/Wind Harmer
2.572
276799AD1-013 GEN
Solar/Wind Harmer
1.108
946671AF1-331 GEN
Solar/Wind Harmer
0.21
274855GSG-6 ;RU
Solar/Wind Harmer
1.85
274850MENDOTA H;RU
Solar/Wind Harmer
1.286
276602WESTBROOK C
Solar/Wind Harmer
1.065
276863AD2-134 GEN
Solar/Wind Harmer
0.895
959091AF2-200 GEN
Solar/Wind Harmer
9.956
972236AH1-702 GEN2
Adder
1.085
276889AE2-281 GEN
Solar/Wind Harmer
0.947
24642205MAYFLWER
Adder
0.313
270535AF1-215 GEN1
Solar/Wind Harmer
2.23
247643Z2-116 C
Solar/Wind Harmer
0.034
274858EASY ROAD;U2
Solar/Wind Harmer
2.338
274760LEE CO EC;1U
Adder
4.539
274767LEE CO EC;8U
Adder
4.486
247604X1-042
Adder
0.185
942871AE2-306 GEN
Solar/Wind Helper
0.773
270485AE1-090_GEN
Solar/Wind Helper
0.463
241974AD2-163_GEN2
Solar/Wind Helper
2.393
241955AC1-078 GEN
Solar/Wind Helper
2.378
960801AF2-371 GEN
Solar/Wind Helper
0.85
964871AG1-351 GEN
Solar/Wind Helper
0.587
253338AC1-165 GEN
Solar/Wind Helper
0.826
253333AC1-068 GEN
Solar/Wind Helper
0.856
270273AD2-016 GEN
Solar/Wind Helper
1.657
270541AE2-072 C
Solar/Wind Helper
1.102
253415AE1-040 GEN
Solar/Wind Helper
0.453
970571AG2-364 GEN
Solar/Wind Harmer
6.339
24721605FLATG1
50/50
1.058
962771AG1-126 GEN
Solar/Wind Harmer
78.213
971347AH1-153 GEN
Solar/Wind Harmer
8.723
274775LINCOLN ;6U
Adder
3.364
274776LINCOLN ;7U
Adder
3.364
274777LINCOLN ;8U
Adder
3.364
960681AF2-359 GEN
Solar/Wind Harmer
1.993
972227AH1-698 GEN1
Adder
1.364
960591AF2-350 GEN
Solar/Wind Harmer
5.222
274827FISK ;RP
Adder
4.049
972037AH1-567 GEN1
Adder
0.095
274814UNIV PK N;0U
Adder
2.631
274807UNIV PK N;3U
Adder
2.626
274805UNIV PK N;1U
Adder
2.614
274811UNIV PK N;7U
Adder
2.608
274687WILL CNTY;4U
Adder
14.52
274687WILL CNTY;4U
Adder
14.52
274675JOLIET 29;7U
Adder
15.941
274675JOLIET 29;7U
Adder
15.372
970833AG2-524 GEN
Solar/Wind Harmer
4.531
970833AG2-524 GEN
Solar/Wind Harmer
2.108
274731ELWOOD EC;2P
Adder
8.515
274733ELWOOD EC;3P
Adder
8.515
274735ELWOOD EC;4P
Adder
8.515
274728ELWOOD EC;5P
Adder
8.515
274746AC1-111 G10
Adder
2.891
274744AC1-111 GEN8
Adder
2.891
971769AH1-391 GEN
Solar/Wind Harmer
5.121
971771AH1-392 GEN
Solar/Wind Harmer
4.539
971177AH1-047 GEN
Solar/Wind Harmer
2.946
971675AH1-338 GEN
Solar/Wind Harmer
9.019
971411AH1-196 GEN
Solar/Wind Harmer
7.513
276868AE1-113 GEN
Solar/Wind Harmer
5.057
276882AE2-255 GEN
Solar/Wind Harmer
1.686
971171AH1-044 GEN
Solar/Wind Harmer
9.956
274823ROCKFORD ;21
Adder
9.668
274863CRW1-WTG
Solar/Wind Harmer
2.753
274864CRW2-WTG
Solar/Wind Harmer
2.753
276612AE2-035 GEN
Solar/Wind Harmer
1.261
270536AF1-215 GEN2
Solar/Wind Harmer
2.23
971681AH1-341 GEN
Solar/Wind Harmer
7.347
926823AC1-168 GEN
Solar/Wind Harmer
2.1
270284AF1-227 GEN1
Solar/Wind Helper
6.336
270286AF1-227 GEN2
Solar/Wind Helper
2.323
270287AF1-227 GEN3
Solar/Wind Helper
2.323
270317AD1-130_GEN
Solar/Wind Helper
5.891
253383AE2-342_GEN
Solar/Wind Helper
1.103
241973AD2-163_GEN1
Solar/Wind Helper
2.393
270520AE2-214 GEN
Solar/Wind Helper
6.251
270054AF2-122 C O1
Solar/Wind Helper
1.45
945631AF1-228 GEN
Solar/Wind Helper
1.86
966831AG1-554 GEN
Solar/Wind Helper
0.856
241972AD1-140 GEN
Solar/Wind Helper
3.072
945641AF1-229 GEN
Solar/Wind Helper
1.093
270499AE1-146 GEN
Solar/Wind Helper
1.872
270340AC2-060 GEN
Solar/Wind Helper
0.963
NYPJM->LTFIMP_NY
CLTF
0.939
LGEELTFEXP_LGEE->PJM
CLTF
0.854
WECLTFEXP_WEC->PJM
CLTF
1.888
AG2-052LTFEXP_AG2-052->PJM
LTF
0.112
AH1-155LTFEXP_AH1-155->PJM
LTF
0.168
CPLELTFEXP_CPLE->PJM
CLTF
1.524
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.966
LAGNLTFEXP_LAGN->PJM
CLTF
5.489
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.243
TVALTFEXP_TVA->PJM
CLTF
2.447
CBM West 1LTFEXP_CBM-W1->PJM
CBM
42.979
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.373
MECLTFEXP_MEC->PJM
CLTF
7.095
SIGELTFEXP_SIGE->PJM
CLTF
0.116

Details for 05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer l/o AEP_P2-2_#7222_05MALIS 765_1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
Contingency Name:
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:109.6 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3394.36
MW Contribution:33.98
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
1.054
962771AG1-126 GEN
Solar/Wind Harmer
77.929
971347AH1-153 GEN
Solar/Wind Harmer
8.598
274775LINCOLN ;6U
Adder
3.314
274776LINCOLN ;7U
Adder
3.314
274777LINCOLN ;8U
Adder
3.314
960681AF2-359 GEN
Solar/Wind Harmer
1.962
972227AH1-698 GEN1
Adder
1.343
960591AF2-350 GEN
Solar/Wind Harmer
5.142
274827FISK ;RP
Adder
3.987
972037AH1-567 GEN1
Adder
0.094
274814UNIV PK N;0U
Adder
2.591
274807UNIV PK N;3U
Adder
2.585
274805UNIV PK N;1U
Adder
2.574
274811UNIV PK N;7U
Adder
2.568
274675JOLIET 29;7U
Adder
15.696
274675JOLIET 29;7U
Adder
15.135
274687WILL CNTY;4U
Adder
14.296
274687WILL CNTY;4U
Adder
14.296
970833AG2-524 GEN
Solar/Wind Harmer
4.461
24722005FLATG5
50/50
1.054
24721905FLATG4
50/50
19.316
970153AG2-106 GEN
Solar/Wind Harmer
33.981
970513AG2-328 GEN
Solar/Wind Harmer
10.698
970517AG2-330 GEN
Solar/Wind Harmer
9.703
970349AG2-230 GEN
Solar/Wind Harmer
8.598
274772LINCOLN ;3U
Adder
3.314
970707AG2-453 GEN
Solar/Wind Harmer
14.634
274724RIVER EC ;11
Adder
9.15
972228AH1-698 GEN2
Adder
1.907
276772AC2-154 GEN
Solar/Wind Harmer
1.434
276806AD2-047 C O1
Solar/Wind Harmer
5.5
970941AG2-585 GEN
Solar/Wind Harmer
6.427
274826FISK ;BP
Adder
5.626
276897AD1-100 C
Solar/Wind Harmer
14.905
939351AE1-166 GEN
Solar/Wind Harmer
3.046
274800UNIV PARK;3U
Adder
2.994
972038AH1-567 GEN2
Adder
0.187
274802UNIV PARK;5U
Adder
2.992
972231SS25-0005
Solar/Wind Harmer
4.861
972181SS23-001
Solar/Wind Harmer
3.038
274752CRETE EC ;2U
Adder
2.503
274753CRETE EC ;3U
Adder
2.503
274676JOLIET 29;8U
Adder
15.135
943121AE2-341 GEN
Solar/Wind Harmer
7.665
943591AF1-030 GEN
Solar/Wind Harmer
5.11
274729ELWOOD EC;1P
Adder
8.383
274730ELWOOD EC;6P
Adder
8.383
274734ELWOOD EC;8P
Adder
8.383
274736ELWOOD EC;9P
Adder
8.383
276893AG1-478 C
Solar/Wind Harmer
0.213
274682WAUKEGAN ;7U
Adder
9.022
276694AA1-018 GEN2
Solar/Wind Harmer
3.15
274872LEEDK;1U
Solar/Wind Harmer
0.127
276799AD1-013 GEN
Solar/Wind Harmer
1.091
946671AF1-331 GEN
Solar/Wind Harmer
0.207
276805AD2-038 GEN
Solar/Wind Harmer
2.531
274855GSG-6 ;RU
Solar/Wind Harmer
1.821
274850MENDOTA H;RU
Solar/Wind Harmer
1.266
276602WESTBROOK C
Solar/Wind Harmer
1.048
276863AD2-134 GEN
Solar/Wind Harmer
0.881
959091AF2-200 GEN
Solar/Wind Harmer
9.799
972236AH1-702 GEN2
Adder
1.068
276889AE2-281 GEN
Solar/Wind Harmer
0.931
24642205MAYFLWER
Adder
0.308
270535AF1-215 GEN1
Solar/Wind Harmer
2.193
247643Z2-116 C
Solar/Wind Harmer
0.033
274858EASY ROAD;U2
Solar/Wind Harmer
2.301
274760LEE CO EC;1U
Adder
4.467
274767LEE CO EC;8U
Adder
4.414
247604X1-042
Adder
0.181
942871AE2-306 GEN
Solar/Wind Helper
0.779
270485AE1-090_GEN
Solar/Wind Helper
0.466
241974AD2-163_GEN2
Solar/Wind Helper
2.428
241955AC1-078 GEN
Solar/Wind Helper
2.425
960801AF2-371 GEN
Solar/Wind Helper
0.869
964871AG1-351 GEN
Solar/Wind Helper
0.6
253338AC1-165 GEN
Solar/Wind Helper
0.845
253333AC1-068 GEN
Solar/Wind Helper
0.876
270273AD2-016 GEN
Solar/Wind Helper
1.698
270541AE2-072 C
Solar/Wind Helper
1.118
253415AE1-040 GEN
Solar/Wind Helper
0.466
970571AG2-364 GEN
Solar/Wind Harmer
6.237
24721805FLATG3
50/50
1.054
24721705FLATG2
50/50
19.316
962761AG1-125 GEN
Solar/Wind Harmer
77.929
970149AG2-104 GEN
Solar/Wind Harmer
96.242
970155AG2-107 GEN
Solar/Wind Harmer
33.981
970245AG2-165 GEN
Solar/Wind Harmer
10.698
972207SS24-0001
Solar/Wind Harmer
11.784
274773LINCOLN ;4U
Adder
3.314
274774LINCOLN ;5U
Adder
3.314
276164X3-005 C
Solar/Wind Harmer
0.363
274723RIVER EC ;12
Adder
9.252
276776AD2-060 GEN
Solar/Wind Harmer
0.217
941551AE2-152 GEN
Solar/Wind Harmer
2.329
274801UNIV PARK;4U
Adder
2.994
274812UNIV PK N;8U
Adder
2.568
274751CRETE EC ;1U
Adder
2.503
274754CRETE EC ;4U
Adder
2.503
274676JOLIET 29;8U
Adder
15.695
274871GR RIDGE ;2U
Solar/Wind Harmer
3.929
274674JOLIET 9 ;6U
Adder
7.865
274732ELWOOD EC;7P
Adder
8.383
274745AC1-111 GEN9
Adder
2.846
274682WAUKEGAN ;7U
Adder
9.022
274828WAUKEGAN ;BP
Adder
5.538
276691AA1-018 GEN1
Solar/Wind Harmer
0.232
960751AF2-366 GEN
Solar/Wind Harmer
1.432
962781AG1-127 GEN
Solar/Wind Harmer
4.746
274872LEEDK;1U
Solar/Wind Harmer
4.09
939401AE1-172 GEN
Solar/Wind Harmer
6.878
970373AG2-245 GEN
Solar/Wind Harmer
10.364
276901AD2-066 C O1
Solar/Wind Harmer
1.733
276861AD2-134 GEN
Solar/Wind Harmer
0.881
971997AH1-543 GEN
Solar/Wind Harmer
7.742
957471AF2-041 GEN
Solar/Wind Harmer
14.698
959081AF2-199 GEN
Solar/Wind Harmer
4.899
971067AG2-660 GEN
Solar/Wind Harmer
1.139
274822ROCKFORD ;11
Adder
9.585
972235AH1-702 GEN1
Adder
1.228
970819AG2-516 GEN
Solar/Wind Harmer
5.828
276876AE1-163_GEN2
Solar/Wind Harmer
3.26
971475AH1-234 GEN
Solar/Wind Harmer
10.852
270055AF2-134 C O1
Solar/Wind Harmer
1.462
274857EASY ROAD;U1
Solar/Wind Harmer
2.301
274761LEE CO EC;2U
Adder
4.467
274766LEE CO EC;7U
Adder
4.414
24639705ELKHART HY
Adder
0.07
270349AD2-093_GEN
Solar/Wind Helper
4.69
270223U2-072_GEN1
Solar/Wind Helper
1.532
270578AF1-285 GEN2
Solar/Wind Helper
1.038
270391AF1-285 GEN3
Solar/Wind Helper
1.038
270462AD2-086
Solar/Wind Helper
5.357
247522W1-056 GEN
Solar/Wind Helper
1.161
253343AC1-166 GEN
Solar/Wind Helper
0.845
253325AC1-069 GEN
Solar/Wind Helper
0.876
960841AF2-375 GEN
Solar/Wind Helper
1.156
270263AC1-001 GEN
Solar/Wind Helper
0.553
958961AF2-187 GEN
Solar/Wind Helper
1.122
241840AF1-064_GEN
Solar/Wind Helper
0.48
241807AE2-176_GEN
Solar/Wind Helper
0.7
970569AG2-363 GEN
Solar/Wind Harmer
9.355
970833AG2-524 GEN
Solar/Wind Harmer
2.075
274731ELWOOD EC;2P
Adder
8.383
274733ELWOOD EC;3P
Adder
8.383
274735ELWOOD EC;4P
Adder
8.383
274728ELWOOD EC;5P
Adder
8.383
274746AC1-111 G10
Adder
2.846
274744AC1-111 GEN8
Adder
2.846
971769AH1-391 GEN
Solar/Wind Harmer
5.039
971771AH1-392 GEN
Solar/Wind Harmer
4.464
971177AH1-047 GEN
Solar/Wind Harmer
2.9
971675AH1-338 GEN
Solar/Wind Harmer
8.877
971411AH1-196 GEN
Solar/Wind Harmer
7.395
276868AE1-113 GEN
Solar/Wind Harmer
4.977
276882AE2-255 GEN
Solar/Wind Harmer
1.659
971171AH1-044 GEN
Solar/Wind Harmer
9.799
274823ROCKFORD ;21
Adder
9.515
274863CRW1-WTG
Solar/Wind Harmer
2.709
274864CRW2-WTG
Solar/Wind Harmer
2.709
276612AE2-035 GEN
Solar/Wind Harmer
1.241
270536AF1-215 GEN2
Solar/Wind Harmer
2.193
971681AH1-341 GEN
Solar/Wind Harmer
7.23
926823AC1-168 GEN
Solar/Wind Harmer
2.067
270284AF1-227 GEN1
Solar/Wind Helper
6.373
270286AF1-227 GEN2
Solar/Wind Helper
2.337
270287AF1-227 GEN3
Solar/Wind Helper
2.337
270317AD1-130_GEN
Solar/Wind Helper
5.933
253383AE2-342_GEN
Solar/Wind Helper
1.119
241973AD2-163_GEN1
Solar/Wind Helper
2.428
270520AE2-214 GEN
Solar/Wind Helper
6.383
270054AF2-122 C O1
Solar/Wind Helper
1.467
945631AF1-228 GEN
Solar/Wind Helper
1.9
966831AG1-554 GEN
Solar/Wind Helper
0.865
241972AD1-140 GEN
Solar/Wind Helper
3.134
945641AF1-229 GEN
Solar/Wind Helper
1.104
270499AE1-146 GEN
Solar/Wind Helper
1.892
270340AC2-060 GEN
Solar/Wind Helper
0.99
970321AG2-212 GEN
Solar/Wind Harmer
10.698
274770LINCOLN ;1U
Adder
3.314
274771LINCOLN ;2U
Adder
3.314
965681AG1-436 GEN
Solar/Wind Harmer
6.493
965791AG1-447 GEN
Solar/Wind Harmer
3.322
972259AH1-714 GEN
Adder
9.882
274888KELLY CRK;1U
Solar/Wind Harmer
3.036
274887GEN-1.85
Solar/Wind Harmer
2.741
276843GEN-1.7
Solar/Wind Harmer
0.295
958011AF2-095 GEN
Solar/Wind Harmer
7.404
274803UNIV PARK;6U
Adder
2.992
274808UNIV PK N;4U
Adder
2.557
274847GR RIDGE ;BU
Solar/Wind Harmer
2.584
274674JOLIET 9 ;6U
Adder
7.865
971573AH1-285 GEN
Solar/Wind Harmer
4.369
24441505OLIV SLR
Solar/Wind Harmer
0.068
274696ROCKY RD ;4P
Adder
5.736
274695ROCKY RD ;2P
Adder
5.604
274693ROCKY RD ;1P
Adder
5.549
274697ROCKY RD ;3P
Adder
1.522
270526AF1-158 GEN
Solar/Wind Harmer
2.283
274683WAUKEGAN ;8U
Adder
10.566
274683WAUKEGAN ;8U
Adder
8.906
962691AG1-118 GEN
Solar/Wind Harmer
15.007
958481AF2-142 GEN
Solar/Wind Harmer
7.488
970921AG2-575 GEN
Solar/Wind Harmer
4.99
970921AG2-575 GEN
Solar/Wind Harmer
1.161
274861TOP CROP ;1U
Solar/Wind Harmer
3.023
274862TOP CROP ;2U
Solar/Wind Harmer
2.524
942991AE2-321 GEN
Solar/Wind Harmer
4.951
958491AF2-143 GEN
Solar/Wind Harmer
7.4
971333AH1-146 GEN
Solar/Wind Harmer
9.855
971335AH1-147 GEN
Solar/Wind Harmer
9.855
274879MINONK ;1U
Solar/Wind Harmer
3.318
971341AH1-150 GEN
Solar/Wind Harmer
9.799
971343AH1-151 GEN
Solar/Wind Harmer
9.799
276872AE1-163_GEN1
Solar/Wind Harmer
3.26
274856ECOGROVE ;U1
Solar/Wind Harmer
1.636
276611AD2-172 GEN
Solar/Wind Harmer
1.241
938861AE1-114 GEN
Solar/Wind Harmer
3.95
274764LEE CO EC;5U
Adder
4.477
274765LEE CO EC;6U
Adder
4.477
274762LEE CO EC;3U
Adder
4.467
274763LEE CO EC;4U
Adder
4.425
972267AH1-718 GEN
Adder
1.98
247620Y3-023
Adder
0.202
270471AD2-092_GEN
Solar/Wind Helper
4.69
270224U2-072_GEN2
Solar/Wind Helper
1.532
270227U2-072_GEN3
Solar/Wind Helper
1.532
270228U2-072_GEN4
Solar/Wind Helper
1.532
270231U2-072_GEN5
Solar/Wind Helper
1.532
946101AF1-275 GEN
Solar/Wind Helper
0.8
241960AC2-195 GEN
Solar/Wind Helper
1.845
253378AE2-206_GEN
Solar/Wind Helper
1.302
276820AF1-078_GEN
Solar/Wind Helper
0.608
270518AE2-148 GEN
Solar/Wind Helper
10.792
NYPJM->LTFIMP_NY
CLTF
0.911
LGEELTFEXP_LGEE->PJM
CLTF
0.799
WECLTFEXP_WEC->PJM
CLTF
1.858
AG2-052LTFEXP_AG2-052->PJM
LTF
0.11
AH1-155LTFEXP_AH1-155->PJM
LTF
0.166
CPLELTFEXP_CPLE->PJM
CLTF
1.514
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.096
LAGNLTFEXP_LAGN->PJM
CLTF
5.378
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.184
TVALTFEXP_TVA->PJM
CLTF
2.393
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.902
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.154
MECLTFEXP_MEC->PJM
CLTF
6.971
SIGELTFEXP_SIGE->PJM
CLTF
0.112

Details for 05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#7222_05MALIS 765_D_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
Contingency Name:
AEP_P4_#7222_05MALIS 765_D_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.59 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3394.1
MW Contribution:33.98
Bus #Bus NameTypeMW Contribution
970321AG2-212 GEN
Solar/Wind Harmer
10.698
274770LINCOLN ;1U
Adder
3.314
274771LINCOLN ;2U
Adder
3.314
965681AG1-436 GEN
Solar/Wind Harmer
6.493
965791AG1-447 GEN
Solar/Wind Harmer
3.322
972259AH1-714 GEN
Adder
9.882
274888KELLY CRK;1U
Solar/Wind Harmer
3.036
274887GEN-1.85
Solar/Wind Harmer
2.741
276843GEN-1.7
Solar/Wind Harmer
0.295
958011AF2-095 GEN
Solar/Wind Harmer
7.404
274803UNIV PARK;6U
Adder
2.992
274808UNIV PK N;4U
Adder
2.557
274847GR RIDGE ;BU
Solar/Wind Harmer
2.584
274674JOLIET 9 ;6U
Adder
7.865
971573AH1-285 GEN
Solar/Wind Harmer
4.369
24441505OLIV SLR
Solar/Wind Harmer
0.068
274696ROCKY RD ;4P
Adder
5.736
274695ROCKY RD ;2P
Adder
5.604
274693ROCKY RD ;1P
Adder
5.549
274697ROCKY RD ;3P
Adder
1.522
270526AF1-158 GEN
Solar/Wind Harmer
2.283
274683WAUKEGAN ;8U
Adder
10.566
274683WAUKEGAN ;8U
Adder
8.906
962691AG1-118 GEN
Solar/Wind Harmer
15.007
958481AF2-142 GEN
Solar/Wind Harmer
7.488
970921AG2-575 GEN
Solar/Wind Harmer
4.99
970921AG2-575 GEN
Solar/Wind Harmer
1.161
274861TOP CROP ;1U
Solar/Wind Harmer
3.023
274862TOP CROP ;2U
Solar/Wind Harmer
2.524
942991AE2-321 GEN
Solar/Wind Harmer
4.951
958491AF2-143 GEN
Solar/Wind Harmer
7.4
971333AH1-146 GEN
Solar/Wind Harmer
9.855
971335AH1-147 GEN
Solar/Wind Harmer
9.855
274879MINONK ;1U
Solar/Wind Harmer
3.318
971341AH1-150 GEN
Solar/Wind Harmer
9.799
971343AH1-151 GEN
Solar/Wind Harmer
9.799
276872AE1-163_GEN1
Solar/Wind Harmer
3.26
274856ECOGROVE ;U1
Solar/Wind Harmer
1.636
276611AD2-172 GEN
Solar/Wind Harmer
1.241
938861AE1-114 GEN
Solar/Wind Harmer
3.95
274764LEE CO EC;5U
Adder
4.477
274765LEE CO EC;6U
Adder
4.477
274762LEE CO EC;3U
Adder
4.467
274763LEE CO EC;4U
Adder
4.425
972267AH1-718 GEN
Adder
1.98
247620Y3-023
Adder
0.202
270471AD2-092_GEN
Solar/Wind Helper
4.69
270224U2-072_GEN2
Solar/Wind Helper
1.532
270227U2-072_GEN3
Solar/Wind Helper
1.532
270228U2-072_GEN4
Solar/Wind Helper
1.532
270231U2-072_GEN5
Solar/Wind Helper
1.532
946101AF1-275 GEN
Solar/Wind Helper
0.8
241960AC2-195 GEN
Solar/Wind Helper
1.845
253378AE2-206_GEN
Solar/Wind Helper
1.302
276820AF1-078_GEN
Solar/Wind Helper
0.608
270518AE2-148 GEN
Solar/Wind Helper
10.792
24721805FLATG3
50/50
1.054
24721705FLATG2
50/50
19.316
962761AG1-125 GEN
Solar/Wind Harmer
77.929
970149AG2-104 GEN
Solar/Wind Harmer
96.242
970155AG2-107 GEN
Solar/Wind Harmer
33.981
970245AG2-165 GEN
Solar/Wind Harmer
10.698
972207SS24-0001
Solar/Wind Harmer
11.784
274773LINCOLN ;4U
Adder
3.314
274774LINCOLN ;5U
Adder
3.314
276164X3-005 C
Solar/Wind Harmer
0.363
274723RIVER EC ;12
Adder
9.252
276776AD2-060 GEN
Solar/Wind Harmer
0.217
941551AE2-152 GEN
Solar/Wind Harmer
2.329
274801UNIV PARK;4U
Adder
2.994
274812UNIV PK N;8U
Adder
2.568
274751CRETE EC ;1U
Adder
2.503
274754CRETE EC ;4U
Adder
2.503
274676JOLIET 29;8U
Adder
15.695
274871GR RIDGE ;2U
Solar/Wind Harmer
3.929
274674JOLIET 9 ;6U
Adder
7.865
274732ELWOOD EC;7P
Adder
8.383
274745AC1-111 GEN9
Adder
2.846
274682WAUKEGAN ;7U
Adder
9.022
274828WAUKEGAN ;BP
Adder
5.538
276691AA1-018 GEN1
Solar/Wind Harmer
0.232
960751AF2-366 GEN
Solar/Wind Harmer
1.432
962781AG1-127 GEN
Solar/Wind Harmer
4.746
274872LEEDK;1U
Solar/Wind Harmer
4.09
939401AE1-172 GEN
Solar/Wind Harmer
6.878
970373AG2-245 GEN
Solar/Wind Harmer
10.364
276901AD2-066 C O1
Solar/Wind Harmer
1.733
276861AD2-134 GEN
Solar/Wind Harmer
0.881
971997AH1-543 GEN
Solar/Wind Harmer
7.742
957471AF2-041 GEN
Solar/Wind Harmer
14.698
959081AF2-199 GEN
Solar/Wind Harmer
4.899
971067AG2-660 GEN
Solar/Wind Harmer
1.139
274822ROCKFORD ;11
Adder
9.585
972235AH1-702 GEN1
Adder
1.228
970819AG2-516 GEN
Solar/Wind Harmer
5.828
276876AE1-163_GEN2
Solar/Wind Harmer
3.26
971475AH1-234 GEN
Solar/Wind Harmer
10.852
270055AF2-134 C O1
Solar/Wind Harmer
1.462
274857EASY ROAD;U1
Solar/Wind Harmer
2.301
274761LEE CO EC;2U
Adder
4.467
274766LEE CO EC;7U
Adder
4.414
24639705ELKHART HY
Adder
0.07
270349AD2-093_GEN
Solar/Wind Helper
4.69
270223U2-072_GEN1
Solar/Wind Helper
1.532
270578AF1-285 GEN2
Solar/Wind Helper
1.038
270391AF1-285 GEN3
Solar/Wind Helper
1.038
270462AD2-086
Solar/Wind Helper
5.357
247522W1-056 GEN
Solar/Wind Helper
1.161
253343AC1-166 GEN
Solar/Wind Helper
0.845
253325AC1-069 GEN
Solar/Wind Helper
0.876
960841AF2-375 GEN
Solar/Wind Helper
1.156
270263AC1-001 GEN
Solar/Wind Helper
0.553
958961AF2-187 GEN
Solar/Wind Helper
1.122
241840AF1-064_GEN
Solar/Wind Helper
0.48
241807AE2-176_GEN
Solar/Wind Helper
0.7
970569AG2-363 GEN
Solar/Wind Harmer
9.355
24722005FLATG5
50/50
1.054
24721905FLATG4
50/50
19.316
970153AG2-106 GEN
Solar/Wind Harmer
33.981
970513AG2-328 GEN
Solar/Wind Harmer
10.698
970517AG2-330 GEN
Solar/Wind Harmer
9.703
970349AG2-230 GEN
Solar/Wind Harmer
8.598
274772LINCOLN ;3U
Adder
3.314
970707AG2-453 GEN
Solar/Wind Harmer
14.634
274724RIVER EC ;11
Adder
9.15
972228AH1-698 GEN2
Adder
1.907
276772AC2-154 GEN
Solar/Wind Harmer
1.434
276806AD2-047 C O1
Solar/Wind Harmer
5.5
970941AG2-585 GEN
Solar/Wind Harmer
6.427
274826FISK ;BP
Adder
5.626
276897AD1-100 C
Solar/Wind Harmer
14.905
939351AE1-166 GEN
Solar/Wind Harmer
3.046
274800UNIV PARK;3U
Adder
2.994
972038AH1-567 GEN2
Adder
0.187
274802UNIV PARK;5U
Adder
2.992
972231SS25-0005
Solar/Wind Harmer
4.861
972181SS23-001
Solar/Wind Harmer
3.038
274752CRETE EC ;2U
Adder
2.503
274753CRETE EC ;3U
Adder
2.503
274676JOLIET 29;8U
Adder
15.135
943121AE2-341 GEN
Solar/Wind Harmer
7.665
943591AF1-030 GEN
Solar/Wind Harmer
5.11
274729ELWOOD EC;1P
Adder
8.383
274730ELWOOD EC;6P
Adder
8.383
274734ELWOOD EC;8P
Adder
8.383
274736ELWOOD EC;9P
Adder
8.383
276893AG1-478 C
Solar/Wind Harmer
0.213
274682WAUKEGAN ;7U
Adder
9.022
276694AA1-018 GEN2
Solar/Wind Harmer
3.15
274872LEEDK;1U
Solar/Wind Harmer
0.127
276799AD1-013 GEN
Solar/Wind Harmer
1.091
946671AF1-331 GEN
Solar/Wind Harmer
0.207
276805AD2-038 GEN
Solar/Wind Harmer
2.531
274855GSG-6 ;RU
Solar/Wind Harmer
1.821
274850MENDOTA H;RU
Solar/Wind Harmer
1.266
276602WESTBROOK C
Solar/Wind Harmer
1.048
276863AD2-134 GEN
Solar/Wind Harmer
0.881
959091AF2-200 GEN
Solar/Wind Harmer
9.799
972236AH1-702 GEN2
Adder
1.068
276889AE2-281 GEN
Solar/Wind Harmer
0.931
24642205MAYFLWER
Adder
0.308
270535AF1-215 GEN1
Solar/Wind Harmer
2.193
247643Z2-116 C
Solar/Wind Harmer
0.033
274858EASY ROAD;U2
Solar/Wind Harmer
2.301
274760LEE CO EC;1U
Adder
4.467
274767LEE CO EC;8U
Adder
4.414
247604X1-042
Adder
0.181
942871AE2-306 GEN
Solar/Wind Helper
0.779
270485AE1-090_GEN
Solar/Wind Helper
0.466
241974AD2-163_GEN2
Solar/Wind Helper
2.428
241955AC1-078 GEN
Solar/Wind Helper
2.425
960801AF2-371 GEN
Solar/Wind Helper
0.869
964871AG1-351 GEN
Solar/Wind Helper
0.6
253338AC1-165 GEN
Solar/Wind Helper
0.845
253333AC1-068 GEN
Solar/Wind Helper
0.876
270273AD2-016 GEN
Solar/Wind Helper
1.698
270541AE2-072 C
Solar/Wind Helper
1.118
253415AE1-040 GEN
Solar/Wind Helper
0.466
970571AG2-364 GEN
Solar/Wind Harmer
6.237
24721605FLATG1
50/50
1.054
962771AG1-126 GEN
Solar/Wind Harmer
77.929
971347AH1-153 GEN
Solar/Wind Harmer
8.598
274775LINCOLN ;6U
Adder
3.314
274776LINCOLN ;7U
Adder
3.314
274777LINCOLN ;8U
Adder
3.314
960681AF2-359 GEN
Solar/Wind Harmer
1.962
972227AH1-698 GEN1
Adder
1.343
960591AF2-350 GEN
Solar/Wind Harmer
5.142
274827FISK ;RP
Adder
3.987
972037AH1-567 GEN1
Adder
0.094
274814UNIV PK N;0U
Adder
2.591
274807UNIV PK N;3U
Adder
2.585
274805UNIV PK N;1U
Adder
2.574
274811UNIV PK N;7U
Adder
2.568
274675JOLIET 29;7U
Adder
15.696
274675JOLIET 29;7U
Adder
15.135
274687WILL CNTY;4U
Adder
14.296
274687WILL CNTY;4U
Adder
14.296
970833AG2-524 GEN
Solar/Wind Harmer
4.461
970833AG2-524 GEN
Solar/Wind Harmer
2.075
274731ELWOOD EC;2P
Adder
8.383
274733ELWOOD EC;3P
Adder
8.383
274735ELWOOD EC;4P
Adder
8.383
274728ELWOOD EC;5P
Adder
8.383
274746AC1-111 G10
Adder
2.846
274744AC1-111 GEN8
Adder
2.846
971769AH1-391 GEN
Solar/Wind Harmer
5.039
971771AH1-392 GEN
Solar/Wind Harmer
4.464
971177AH1-047 GEN
Solar/Wind Harmer
2.9
971675AH1-338 GEN
Solar/Wind Harmer
8.877
971411AH1-196 GEN
Solar/Wind Harmer
7.395
276868AE1-113 GEN
Solar/Wind Harmer
4.977
276882AE2-255 GEN
Solar/Wind Harmer
1.659
971171AH1-044 GEN
Solar/Wind Harmer
9.799
274823ROCKFORD ;21
Adder
9.515
274863CRW1-WTG
Solar/Wind Harmer
2.709
274864CRW2-WTG
Solar/Wind Harmer
2.709
276612AE2-035 GEN
Solar/Wind Harmer
1.241
270536AF1-215 GEN2
Solar/Wind Harmer
2.193
971681AH1-341 GEN
Solar/Wind Harmer
7.23
926823AC1-168 GEN
Solar/Wind Harmer
2.067
270284AF1-227 GEN1
Solar/Wind Helper
6.373
270286AF1-227 GEN2
Solar/Wind Helper
2.337
270287AF1-227 GEN3
Solar/Wind Helper
2.337
270317AD1-130_GEN
Solar/Wind Helper
5.933
253383AE2-342_GEN
Solar/Wind Helper
1.119
241973AD2-163_GEN1
Solar/Wind Helper
2.428
270520AE2-214 GEN
Solar/Wind Helper
6.383
270054AF2-122 C O1
Solar/Wind Helper
1.467
945631AF1-228 GEN
Solar/Wind Helper
1.9
966831AG1-554 GEN
Solar/Wind Helper
0.865
241972AD1-140 GEN
Solar/Wind Helper
3.134
945641AF1-229 GEN
Solar/Wind Helper
1.104
270499AE1-146 GEN
Solar/Wind Helper
1.892
270340AC2-060 GEN
Solar/Wind Helper
0.99
NYPJM->LTFIMP_NY
CLTF
0.911
LGEELTFEXP_LGEE->PJM
CLTF
0.799
WECLTFEXP_WEC->PJM
CLTF
1.858
AG2-052LTFEXP_AG2-052->PJM
LTF
0.11
AH1-155LTFEXP_AH1-155->PJM
LTF
0.166
CPLELTFEXP_CPLE->PJM
CLTF
1.514
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.096
LAGNLTFEXP_LAGN->PJM
CLTF
5.378
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.184
TVALTFEXP_TVA->PJM
CLTF
2.393
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.902
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.154
MECLTFEXP_MEC->PJM
CLTF
6.971
SIGELTFEXP_SIGE->PJM
CLTF
0.112

Details for 05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#9729_05MALIS 138_M1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
Contingency Name:
AEP_P4_#9729_05MALIS 138_M1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.53 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3392.25
MW Contribution:33.97
Bus #Bus NameTypeMW Contribution
970321AG2-212 GEN
Solar/Wind Harmer
10.693
274770LINCOLN ;1U
Adder
3.312
274771LINCOLN ;2U
Adder
3.312
965681AG1-436 GEN
Solar/Wind Harmer
6.489
965791AG1-447 GEN
Solar/Wind Harmer
3.32
972259AH1-714 GEN
Adder
9.876
274888KELLY CRK;1U
Solar/Wind Harmer
3.034
274887GEN-1.85
Solar/Wind Harmer
2.739
276843GEN-1.7
Solar/Wind Harmer
0.295
958011AF2-095 GEN
Solar/Wind Harmer
7.4
274803UNIV PARK;6U
Adder
2.99
274808UNIV PK N;4U
Adder
2.555
274847GR RIDGE ;BU
Solar/Wind Harmer
2.583
274674JOLIET 9 ;6U
Adder
7.861
971573AH1-285 GEN
Solar/Wind Harmer
4.367
24441505OLIV SLR
Solar/Wind Harmer
0.067
274696ROCKY RD ;4P
Adder
5.733
274695ROCKY RD ;2P
Adder
5.601
274693ROCKY RD ;1P
Adder
5.545
274697ROCKY RD ;3P
Adder
1.521
270526AF1-158 GEN
Solar/Wind Harmer
2.281
274683WAUKEGAN ;8U
Adder
10.559
274683WAUKEGAN ;8U
Adder
8.901
962691AG1-118 GEN
Solar/Wind Harmer
14.999
958481AF2-142 GEN
Solar/Wind Harmer
7.483
970921AG2-575 GEN
Solar/Wind Harmer
4.988
970921AG2-575 GEN
Solar/Wind Harmer
1.16
274861TOP CROP ;1U
Solar/Wind Harmer
3.021
274862TOP CROP ;2U
Solar/Wind Harmer
2.523
942991AE2-321 GEN
Solar/Wind Harmer
4.948
958491AF2-143 GEN
Solar/Wind Harmer
7.396
971333AH1-146 GEN
Solar/Wind Harmer
9.849
971335AH1-147 GEN
Solar/Wind Harmer
9.849
274879MINONK ;1U
Solar/Wind Harmer
3.316
971341AH1-150 GEN
Solar/Wind Harmer
9.793
971343AH1-151 GEN
Solar/Wind Harmer
9.793
276872AE1-163_GEN1
Solar/Wind Harmer
3.258
274856ECOGROVE ;U1
Solar/Wind Harmer
1.635
276611AD2-172 GEN
Solar/Wind Harmer
1.241
938861AE1-114 GEN
Solar/Wind Harmer
3.948
274764LEE CO EC;5U
Adder
4.475
274765LEE CO EC;6U
Adder
4.475
274762LEE CO EC;3U
Adder
4.464
274763LEE CO EC;4U
Adder
4.422
972267AH1-718 GEN
Adder
1.979
247620Y3-023
Adder
0.202
270471AD2-092_GEN
Solar/Wind Helper
4.692
270224U2-072_GEN2
Solar/Wind Helper
1.533
270227U2-072_GEN3
Solar/Wind Helper
1.533
270228U2-072_GEN4
Solar/Wind Helper
1.533
270231U2-072_GEN5
Solar/Wind Helper
1.533
946101AF1-275 GEN
Solar/Wind Helper
0.8
241960AC2-195 GEN
Solar/Wind Helper
1.846
253378AE2-206_GEN
Solar/Wind Helper
1.303
276820AF1-078_GEN
Solar/Wind Helper
0.609
270518AE2-148 GEN
Solar/Wind Helper
10.796
24721805FLATG3
50/50
1.053
24721705FLATG2
50/50
19.313
962761AG1-125 GEN
Solar/Wind Harmer
77.914
970149AG2-104 GEN
Solar/Wind Harmer
96.223
970155AG2-107 GEN
Solar/Wind Harmer
33.974
970245AG2-165 GEN
Solar/Wind Harmer
10.693
972207SS24-0001
Solar/Wind Harmer
11.777
274773LINCOLN ;4U
Adder
3.312
274774LINCOLN ;5U
Adder
3.312
276164X3-005 C
Solar/Wind Harmer
0.363
274723RIVER EC ;12
Adder
9.247
276776AD2-060 GEN
Solar/Wind Harmer
0.217
941551AE2-152 GEN
Solar/Wind Harmer
2.328
274801UNIV PARK;4U
Adder
2.992
274812UNIV PK N;8U
Adder
2.567
274751CRETE EC ;1U
Adder
2.502
274754CRETE EC ;4U
Adder
2.502
274676JOLIET 29;8U
Adder
15.686
274871GR RIDGE ;2U
Solar/Wind Harmer
3.926
274674JOLIET 9 ;6U
Adder
7.861
274732ELWOOD EC;7P
Adder
8.378
274745AC1-111 GEN9
Adder
2.845
274682WAUKEGAN ;7U
Adder
9.017
274828WAUKEGAN ;BP
Adder
5.535
276691AA1-018 GEN1
Solar/Wind Harmer
0.232
960751AF2-366 GEN
Solar/Wind Harmer
1.431
962781AG1-127 GEN
Solar/Wind Harmer
4.743
274872LEEDK;1U
Solar/Wind Harmer
4.087
939401AE1-172 GEN
Solar/Wind Harmer
6.874
970373AG2-245 GEN
Solar/Wind Harmer
10.358
276901AD2-066 C O1
Solar/Wind Harmer
1.732
276861AD2-134 GEN
Solar/Wind Harmer
0.88
971997AH1-543 GEN
Solar/Wind Harmer
7.738
957471AF2-041 GEN
Solar/Wind Harmer
14.689
959081AF2-199 GEN
Solar/Wind Harmer
4.896
971067AG2-660 GEN
Solar/Wind Harmer
1.139
274822ROCKFORD ;11
Adder
9.579
972235AH1-702 GEN1
Adder
1.227
970819AG2-516 GEN
Solar/Wind Harmer
5.825
276876AE1-163_GEN2
Solar/Wind Harmer
3.258
971475AH1-234 GEN
Solar/Wind Harmer
10.846
270055AF2-134 C O1
Solar/Wind Harmer
1.461
274857EASY ROAD;U1
Solar/Wind Harmer
2.299
274761LEE CO EC;2U
Adder
4.464
274766LEE CO EC;7U
Adder
4.412
24639705ELKHART HY
Adder
0.07
270349AD2-093_GEN
Solar/Wind Helper
4.692
270223U2-072_GEN1
Solar/Wind Helper
1.533
270578AF1-285 GEN2
Solar/Wind Helper
1.038
270391AF1-285 GEN3
Solar/Wind Helper
1.038
270462AD2-086
Solar/Wind Helper
5.359
247522W1-056 GEN
Solar/Wind Helper
1.162
253343AC1-166 GEN
Solar/Wind Helper
0.845
253325AC1-069 GEN
Solar/Wind Helper
0.876
960841AF2-375 GEN
Solar/Wind Helper
1.157
270263AC1-001 GEN
Solar/Wind Helper
0.553
958961AF2-187 GEN
Solar/Wind Helper
1.122
241840AF1-064_GEN
Solar/Wind Helper
0.48
241807AE2-176_GEN
Solar/Wind Helper
0.7
970569AG2-363 GEN
Solar/Wind Harmer
9.35
24722005FLATG5
50/50
1.053
24721905FLATG4
50/50
19.313
970153AG2-106 GEN
Solar/Wind Harmer
33.974
970513AG2-328 GEN
Solar/Wind Harmer
10.693
970517AG2-330 GEN
Solar/Wind Harmer
9.698
970349AG2-230 GEN
Solar/Wind Harmer
8.593
274772LINCOLN ;3U
Adder
3.312
970707AG2-453 GEN
Solar/Wind Harmer
14.626
274724RIVER EC ;11
Adder
9.144
972228AH1-698 GEN2
Adder
1.906
276772AC2-154 GEN
Solar/Wind Harmer
1.433
276806AD2-047 C O1
Solar/Wind Harmer
5.497
970941AG2-585 GEN
Solar/Wind Harmer
6.423
274826FISK ;BP
Adder
5.622
276897AD1-100 C
Solar/Wind Harmer
14.897
939351AE1-166 GEN
Solar/Wind Harmer
3.044
274800UNIV PARK;3U
Adder
2.992
972038AH1-567 GEN2
Adder
0.187
274802UNIV PARK;5U
Adder
2.99
972231SS25-0005
Solar/Wind Harmer
4.858
972181SS23-001
Solar/Wind Harmer
3.036
274752CRETE EC ;2U
Adder
2.502
274753CRETE EC ;3U
Adder
2.502
274676JOLIET 29;8U
Adder
15.126
943121AE2-341 GEN
Solar/Wind Harmer
7.661
943591AF1-030 GEN
Solar/Wind Harmer
5.107
274729ELWOOD EC;1P
Adder
8.379
274730ELWOOD EC;6P
Adder
8.378
274734ELWOOD EC;8P
Adder
8.378
274736ELWOOD EC;9P
Adder
8.378
276893AG1-478 C
Solar/Wind Harmer
0.213
274682WAUKEGAN ;7U
Adder
9.017
276694AA1-018 GEN2
Solar/Wind Harmer
3.148
274872LEEDK;1U
Solar/Wind Harmer
0.127
276799AD1-013 GEN
Solar/Wind Harmer
1.09
946671AF1-331 GEN
Solar/Wind Harmer
0.206
276805AD2-038 GEN
Solar/Wind Harmer
2.529
274855GSG-6 ;RU
Solar/Wind Harmer
1.82
274850MENDOTA H;RU
Solar/Wind Harmer
1.266
276602WESTBROOK C
Solar/Wind Harmer
1.048
276863AD2-134 GEN
Solar/Wind Harmer
0.88
959091AF2-200 GEN
Solar/Wind Harmer
9.793
972236AH1-702 GEN2
Adder
1.067
276889AE2-281 GEN
Solar/Wind Harmer
0.931
24642205MAYFLWER
Adder
0.307
270535AF1-215 GEN1
Solar/Wind Harmer
2.192
247643Z2-116 C
Solar/Wind Harmer
0.033
274858EASY ROAD;U2
Solar/Wind Harmer
2.299
274760LEE CO EC;1U
Adder
4.464
274767LEE CO EC;8U
Adder
4.412
247604X1-042
Adder
0.181
942871AE2-306 GEN
Solar/Wind Helper
0.779
270485AE1-090_GEN
Solar/Wind Helper
0.466
241974AD2-163_GEN2
Solar/Wind Helper
2.43
241955AC1-078 GEN
Solar/Wind Helper
2.426
960801AF2-371 GEN
Solar/Wind Helper
0.868
964871AG1-351 GEN
Solar/Wind Helper
0.6
253338AC1-165 GEN
Solar/Wind Helper
0.845
253333AC1-068 GEN
Solar/Wind Helper
0.876
270273AD2-016 GEN
Solar/Wind Helper
1.697
270541AE2-072 C
Solar/Wind Helper
1.118
253415AE1-040 GEN
Solar/Wind Helper
0.466
970571AG2-364 GEN
Solar/Wind Harmer
6.233
24721605FLATG1
50/50
1.053
962771AG1-126 GEN
Solar/Wind Harmer
77.914
971347AH1-153 GEN
Solar/Wind Harmer
8.593
274775LINCOLN ;6U
Adder
3.312
274776LINCOLN ;7U
Adder
3.312
274777LINCOLN ;8U
Adder
3.312
960681AF2-359 GEN
Solar/Wind Harmer
1.961
972227AH1-698 GEN1
Adder
1.342
960591AF2-350 GEN
Solar/Wind Harmer
5.139
274827FISK ;RP
Adder
3.985
972037AH1-567 GEN1
Adder
0.094
274814UNIV PK N;0U
Adder
2.589
274807UNIV PK N;3U
Adder
2.583
274805UNIV PK N;1U
Adder
2.572
274811UNIV PK N;7U
Adder
2.567
274687WILL CNTY;4U
Adder
14.288
274687WILL CNTY;4U
Adder
14.288
274675JOLIET 29;7U
Adder
15.686
274675JOLIET 29;7U
Adder
15.126
970833AG2-524 GEN
Solar/Wind Harmer
4.459
970833AG2-524 GEN
Solar/Wind Harmer
2.074
274731ELWOOD EC;2P
Adder
8.379
274733ELWOOD EC;3P
Adder
8.379
274735ELWOOD EC;4P
Adder
8.379
274728ELWOOD EC;5P
Adder
8.378
274746AC1-111 G10
Adder
2.845
274744AC1-111 GEN8
Adder
2.845
971769AH1-391 GEN
Solar/Wind Harmer
5.036
971771AH1-392 GEN
Solar/Wind Harmer
4.462
971177AH1-047 GEN
Solar/Wind Harmer
2.899
971675AH1-338 GEN
Solar/Wind Harmer
8.872
971411AH1-196 GEN
Solar/Wind Harmer
7.391
276868AE1-113 GEN
Solar/Wind Harmer
4.974
276882AE2-255 GEN
Solar/Wind Harmer
1.658
971171AH1-044 GEN
Solar/Wind Harmer
9.793
274823ROCKFORD ;21
Adder
9.51
274863CRW1-WTG
Solar/Wind Harmer
2.707
274864CRW2-WTG
Solar/Wind Harmer
2.707
276612AE2-035 GEN
Solar/Wind Harmer
1.241
270536AF1-215 GEN2
Solar/Wind Harmer
2.192
971681AH1-341 GEN
Solar/Wind Harmer
7.225
926823AC1-168 GEN
Solar/Wind Harmer
2.065
270284AF1-227 GEN1
Solar/Wind Helper
6.375
270286AF1-227 GEN2
Solar/Wind Helper
2.338
270287AF1-227 GEN3
Solar/Wind Helper
2.338
270317AD1-130_GEN
Solar/Wind Helper
5.935
253383AE2-342_GEN
Solar/Wind Helper
1.12
241973AD2-163_GEN1
Solar/Wind Helper
2.43
270520AE2-214 GEN
Solar/Wind Helper
6.387
270054AF2-122 C O1
Solar/Wind Helper
1.465
945631AF1-228 GEN
Solar/Wind Helper
1.901
966831AG1-554 GEN
Solar/Wind Helper
0.865
241972AD1-140 GEN
Solar/Wind Helper
3.137
945641AF1-229 GEN
Solar/Wind Helper
1.105
270499AE1-146 GEN
Solar/Wind Helper
1.893
270340AC2-060 GEN
Solar/Wind Helper
0.99
NYPJM->LTFIMP_NY
CLTF
0.91
LGEELTFEXP_LGEE->PJM
CLTF
0.797
WECLTFEXP_WEC->PJM
CLTF
1.857
AG2-052LTFEXP_AG2-052->PJM
LTF
0.11
AH1-155LTFEXP_AH1-155->PJM
LTF
0.165
CPLELTFEXP_CPLE->PJM
CLTF
1.514
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.07
LAGNLTFEXP_LAGN->PJM
CLTF
5.375
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.182
TVALTFEXP_TVA->PJM
CLTF
2.392
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.864
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.148
MECLTFEXP_MEC->PJM
CLTF
6.967
SIGELTFEXP_SIGE->PJM
CLTF
0.112

Details for 05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#9730_05MALIS 138_P1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
Contingency Name:
AEP_P4_#9730_05MALIS 138_P1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.53 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3392.06
MW Contribution:33.97
Bus #Bus NameTypeMW Contribution
970321AG2-212 GEN
Solar/Wind Harmer
10.692
274770LINCOLN ;1U
Adder
3.312
274771LINCOLN ;2U
Adder
3.312
965681AG1-436 GEN
Solar/Wind Harmer
6.489
965791AG1-447 GEN
Solar/Wind Harmer
3.32
972259AH1-714 GEN
Adder
9.875
274888KELLY CRK;1U
Solar/Wind Harmer
3.034
274887GEN-1.85
Solar/Wind Harmer
2.739
276843GEN-1.7
Solar/Wind Harmer
0.295
958011AF2-095 GEN
Solar/Wind Harmer
7.399
274803UNIV PARK;6U
Adder
2.99
274808UNIV PK N;4U
Adder
2.555
274847GR RIDGE ;BU
Solar/Wind Harmer
2.583
274674JOLIET 9 ;6U
Adder
7.86
971573AH1-285 GEN
Solar/Wind Harmer
4.366
24441505OLIV SLR
Solar/Wind Harmer
0.067
274696ROCKY RD ;4P
Adder
5.732
274695ROCKY RD ;2P
Adder
5.6
274693ROCKY RD ;1P
Adder
5.545
274697ROCKY RD ;3P
Adder
1.521
270526AF1-158 GEN
Solar/Wind Harmer
2.281
274683WAUKEGAN ;8U
Adder
10.559
274683WAUKEGAN ;8U
Adder
8.9
962691AG1-118 GEN
Solar/Wind Harmer
14.997
958481AF2-142 GEN
Solar/Wind Harmer
7.483
970921AG2-575 GEN
Solar/Wind Harmer
4.987
970921AG2-575 GEN
Solar/Wind Harmer
1.16
274861TOP CROP ;1U
Solar/Wind Harmer
3.021
274862TOP CROP ;2U
Solar/Wind Harmer
2.522
942991AE2-321 GEN
Solar/Wind Harmer
4.948
958491AF2-143 GEN
Solar/Wind Harmer
7.395
971333AH1-146 GEN
Solar/Wind Harmer
9.848
971335AH1-147 GEN
Solar/Wind Harmer
9.848
274879MINONK ;1U
Solar/Wind Harmer
3.316
971341AH1-150 GEN
Solar/Wind Harmer
9.792
971343AH1-151 GEN
Solar/Wind Harmer
9.792
276872AE1-163_GEN1
Solar/Wind Harmer
3.257
274856ECOGROVE ;U1
Solar/Wind Harmer
1.635
276611AD2-172 GEN
Solar/Wind Harmer
1.24
938861AE1-114 GEN
Solar/Wind Harmer
3.947
274764LEE CO EC;5U
Adder
4.474
274765LEE CO EC;6U
Adder
4.474
274762LEE CO EC;3U
Adder
4.464
274763LEE CO EC;4U
Adder
4.422
972267AH1-718 GEN
Adder
1.978
247620Y3-023
Adder
0.202
270471AD2-092_GEN
Solar/Wind Helper
4.692
270224U2-072_GEN2
Solar/Wind Helper
1.533
270227U2-072_GEN3
Solar/Wind Helper
1.533
270228U2-072_GEN4
Solar/Wind Helper
1.533
270231U2-072_GEN5
Solar/Wind Helper
1.533
946101AF1-275 GEN
Solar/Wind Helper
0.8
241960AC2-195 GEN
Solar/Wind Helper
1.846
253378AE2-206_GEN
Solar/Wind Helper
1.303
276820AF1-078_GEN
Solar/Wind Helper
0.609
270518AE2-148 GEN
Solar/Wind Helper
10.796
24721805FLATG3
50/50
1.053
24721705FLATG2
50/50
19.313
962761AG1-125 GEN
Solar/Wind Harmer
77.912
970149AG2-104 GEN
Solar/Wind Harmer
96.221
970155AG2-107 GEN
Solar/Wind Harmer
33.973
970245AG2-165 GEN
Solar/Wind Harmer
10.692
972207SS24-0001
Solar/Wind Harmer
11.776
274773LINCOLN ;4U
Adder
3.312
274774LINCOLN ;5U
Adder
3.312
276164X3-005 C
Solar/Wind Harmer
0.363
274723RIVER EC ;12
Adder
9.246
276776AD2-060 GEN
Solar/Wind Harmer
0.217
941551AE2-152 GEN
Solar/Wind Harmer
2.328
274801UNIV PARK;4U
Adder
2.992
274812UNIV PK N;8U
Adder
2.566
274751CRETE EC ;1U
Adder
2.502
274754CRETE EC ;4U
Adder
2.502
274676JOLIET 29;8U
Adder
15.685
274871GR RIDGE ;2U
Solar/Wind Harmer
3.926
274674JOLIET 9 ;6U
Adder
7.86
274732ELWOOD EC;7P
Adder
8.378
274745AC1-111 GEN9
Adder
2.845
274682WAUKEGAN ;7U
Adder
9.016
274828WAUKEGAN ;BP
Adder
5.535
276691AA1-018 GEN1
Solar/Wind Harmer
0.232
960751AF2-366 GEN
Solar/Wind Harmer
1.431
962781AG1-127 GEN
Solar/Wind Harmer
4.743
274872LEEDK;1U
Solar/Wind Harmer
4.087
939401AE1-172 GEN
Solar/Wind Harmer
6.874
970373AG2-245 GEN
Solar/Wind Harmer
10.357
276901AD2-066 C O1
Solar/Wind Harmer
1.731
276861AD2-134 GEN
Solar/Wind Harmer
0.88
971997AH1-543 GEN
Solar/Wind Harmer
7.737
957471AF2-041 GEN
Solar/Wind Harmer
14.688
959081AF2-199 GEN
Solar/Wind Harmer
4.896
971067AG2-660 GEN
Solar/Wind Harmer
1.139
274822ROCKFORD ;11
Adder
9.578
972235AH1-702 GEN1
Adder
1.227
970819AG2-516 GEN
Solar/Wind Harmer
5.825
276876AE1-163_GEN2
Solar/Wind Harmer
3.257
971475AH1-234 GEN
Solar/Wind Harmer
10.845
270055AF2-134 C O1
Solar/Wind Harmer
1.461
274857EASY ROAD;U1
Solar/Wind Harmer
2.299
274761LEE CO EC;2U
Adder
4.464
274766LEE CO EC;7U
Adder
4.411
24639705ELKHART HY
Adder
0.07
270349AD2-093_GEN
Solar/Wind Helper
4.692
270223U2-072_GEN1
Solar/Wind Helper
1.533
270578AF1-285 GEN2
Solar/Wind Helper
1.039
270391AF1-285 GEN3
Solar/Wind Helper
1.039
270462AD2-086
Solar/Wind Helper
5.359
247522W1-056 GEN
Solar/Wind Helper
1.162
253343AC1-166 GEN
Solar/Wind Helper
0.845
253325AC1-069 GEN
Solar/Wind Helper
0.876
960841AF2-375 GEN
Solar/Wind Helper
1.157
270263AC1-001 GEN
Solar/Wind Helper
0.553
958961AF2-187 GEN
Solar/Wind Helper
1.122
241840AF1-064_GEN
Solar/Wind Helper
0.48
241807AE2-176_GEN
Solar/Wind Helper
0.7
970569AG2-363 GEN
Solar/Wind Harmer
9.349
24722005FLATG5
50/50
1.053
24721905FLATG4
50/50
19.313
970153AG2-106 GEN
Solar/Wind Harmer
33.973
970513AG2-328 GEN
Solar/Wind Harmer
10.692
970517AG2-330 GEN
Solar/Wind Harmer
9.698
970349AG2-230 GEN
Solar/Wind Harmer
8.593
274772LINCOLN ;3U
Adder
3.312
970707AG2-453 GEN
Solar/Wind Harmer
14.625
274724RIVER EC ;11
Adder
9.144
972228AH1-698 GEN2
Adder
1.906
276772AC2-154 GEN
Solar/Wind Harmer
1.433
276806AD2-047 C O1
Solar/Wind Harmer
5.497
970941AG2-585 GEN
Solar/Wind Harmer
6.423
274826FISK ;BP
Adder
5.622
276897AD1-100 C
Solar/Wind Harmer
14.896
939351AE1-166 GEN
Solar/Wind Harmer
3.044
274800UNIV PARK;3U
Adder
2.992
972038AH1-567 GEN2
Adder
0.187
274802UNIV PARK;5U
Adder
2.99
972231SS25-0005
Solar/Wind Harmer
4.857
972181SS23-001
Solar/Wind Harmer
3.036
274752CRETE EC ;2U
Adder
2.502
274753CRETE EC ;3U
Adder
2.502
274676JOLIET 29;8U
Adder
15.125
943121AE2-341 GEN
Solar/Wind Harmer
7.66
943591AF1-030 GEN
Solar/Wind Harmer
5.107
274729ELWOOD EC;1P
Adder
8.378
274730ELWOOD EC;6P
Adder
8.378
274734ELWOOD EC;8P
Adder
8.378
274736ELWOOD EC;9P
Adder
8.378
276893AG1-478 C
Solar/Wind Harmer
0.213
274682WAUKEGAN ;7U
Adder
9.016
276694AA1-018 GEN2
Solar/Wind Harmer
3.148
274872LEEDK;1U
Solar/Wind Harmer
0.127
276799AD1-013 GEN
Solar/Wind Harmer
1.09
946671AF1-331 GEN
Solar/Wind Harmer
0.206
276805AD2-038 GEN
Solar/Wind Harmer
2.529
274855GSG-6 ;RU
Solar/Wind Harmer
1.82
274850MENDOTA H;RU
Solar/Wind Harmer
1.265
276602WESTBROOK C
Solar/Wind Harmer
1.048
276863AD2-134 GEN
Solar/Wind Harmer
0.88
959091AF2-200 GEN
Solar/Wind Harmer
9.792
972236AH1-702 GEN2
Adder
1.067
276889AE2-281 GEN
Solar/Wind Harmer
0.931
24642205MAYFLWER
Adder
0.307
270535AF1-215 GEN1
Solar/Wind Harmer
2.191
247643Z2-116 C
Solar/Wind Harmer
0.033
274858EASY ROAD;U2
Solar/Wind Harmer
2.299
274760LEE CO EC;1U
Adder
4.464
274767LEE CO EC;8U
Adder
4.411
247604X1-042
Adder
0.181
942871AE2-306 GEN
Solar/Wind Helper
0.779
270485AE1-090_GEN
Solar/Wind Helper
0.466
241974AD2-163_GEN2
Solar/Wind Helper
2.43
241955AC1-078 GEN
Solar/Wind Helper
2.426
960801AF2-371 GEN
Solar/Wind Helper
0.868
964871AG1-351 GEN
Solar/Wind Helper
0.6
253338AC1-165 GEN
Solar/Wind Helper
0.845
253333AC1-068 GEN
Solar/Wind Helper
0.876
270273AD2-016 GEN
Solar/Wind Helper
1.697
270541AE2-072 C
Solar/Wind Helper
1.118
253415AE1-040 GEN
Solar/Wind Helper
0.466
970571AG2-364 GEN
Solar/Wind Harmer
6.233
24721605FLATG1
50/50
1.053
962771AG1-126 GEN
Solar/Wind Harmer
77.912
971347AH1-153 GEN
Solar/Wind Harmer
8.593
274775LINCOLN ;6U
Adder
3.312
274776LINCOLN ;7U
Adder
3.312
274777LINCOLN ;8U
Adder
3.312
960681AF2-359 GEN
Solar/Wind Harmer
1.961
972227AH1-698 GEN1
Adder
1.342
960591AF2-350 GEN
Solar/Wind Harmer
5.138
274827FISK ;RP
Adder
3.984
972037AH1-567 GEN1
Adder
0.094
274814UNIV PK N;0U
Adder
2.589
274807UNIV PK N;3U
Adder
2.583
274805UNIV PK N;1U
Adder
2.572
274811UNIV PK N;7U
Adder
2.566
274687WILL CNTY;4U
Adder
14.287
274687WILL CNTY;4U
Adder
14.287
274675JOLIET 29;7U
Adder
15.685
274675JOLIET 29;7U
Adder
15.125
970833AG2-524 GEN
Solar/Wind Harmer
4.458
970833AG2-524 GEN
Solar/Wind Harmer
2.074
274731ELWOOD EC;2P
Adder
8.378
274733ELWOOD EC;3P
Adder
8.378
274735ELWOOD EC;4P
Adder
8.378
274728ELWOOD EC;5P
Adder
8.378
274746AC1-111 G10
Adder
2.845
274744AC1-111 GEN8
Adder
2.845
971769AH1-391 GEN
Solar/Wind Harmer
5.036
971771AH1-392 GEN
Solar/Wind Harmer
4.461
971177AH1-047 GEN
Solar/Wind Harmer
2.898
971675AH1-338 GEN
Solar/Wind Harmer
8.872
971411AH1-196 GEN
Solar/Wind Harmer
7.39
276868AE1-113 GEN
Solar/Wind Harmer
4.974
276882AE2-255 GEN
Solar/Wind Harmer
1.658
971171AH1-044 GEN
Solar/Wind Harmer
9.792
274823ROCKFORD ;21
Adder
9.509
274863CRW1-WTG
Solar/Wind Harmer
2.707
274864CRW2-WTG
Solar/Wind Harmer
2.707
276612AE2-035 GEN
Solar/Wind Harmer
1.24
270536AF1-215 GEN2
Solar/Wind Harmer
2.191
971681AH1-341 GEN
Solar/Wind Harmer
7.225
926823AC1-168 GEN
Solar/Wind Harmer
2.065
270284AF1-227 GEN1
Solar/Wind Helper
6.375
270286AF1-227 GEN2
Solar/Wind Helper
2.338
270287AF1-227 GEN3
Solar/Wind Helper
2.338
270317AD1-130_GEN
Solar/Wind Helper
5.936
253383AE2-342_GEN
Solar/Wind Helper
1.121
241973AD2-163_GEN1
Solar/Wind Helper
2.43
270520AE2-214 GEN
Solar/Wind Helper
6.387
270054AF2-122 C O1
Solar/Wind Helper
1.465
945631AF1-228 GEN
Solar/Wind Helper
1.901
966831AG1-554 GEN
Solar/Wind Helper
0.865
241972AD1-140 GEN
Solar/Wind Helper
3.137
945641AF1-229 GEN
Solar/Wind Helper
1.105
270499AE1-146 GEN
Solar/Wind Helper
1.893
270340AC2-060 GEN
Solar/Wind Helper
0.99
NYPJM->LTFIMP_NY
CLTF
0.91
LGEELTFEXP_LGEE->PJM
CLTF
0.797
WECLTFEXP_WEC->PJM
CLTF
1.857
AG2-052LTFEXP_AG2-052->PJM
LTF
0.11
AH1-155LTFEXP_AH1-155->PJM
LTF
0.165
CPLELTFEXP_CPLE->PJM
CLTF
1.514
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.066
LAGNLTFEXP_LAGN->PJM
CLTF
5.374
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.182
TVALTFEXP_TVA->PJM
CLTF
2.391
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.859
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.148
MECLTFEXP_MEC->PJM
CLTF
6.966
SIGELTFEXP_SIGE->PJM
CLTF
0.112

Details for 05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#9728_05MALIS 138_L1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
Contingency Name:
AEP_P4_#9728_05MALIS 138_L1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.5 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3391.13
MW Contribution:33.97
Bus #Bus NameTypeMW Contribution
970321AG2-212 GEN
Solar/Wind Harmer
10.689
274770LINCOLN ;1U
Adder
3.311
274771LINCOLN ;2U
Adder
3.311
965681AG1-436 GEN
Solar/Wind Harmer
6.486
965791AG1-447 GEN
Solar/Wind Harmer
3.319
972259AH1-714 GEN
Adder
9.872
274888KELLY CRK;1U
Solar/Wind Harmer
3.033
274887GEN-1.85
Solar/Wind Harmer
2.738
276843GEN-1.7
Solar/Wind Harmer
0.295
958011AF2-095 GEN
Solar/Wind Harmer
7.397
274803UNIV PARK;6U
Adder
2.989
274808UNIV PK N;4U
Adder
2.554
274847GR RIDGE ;BU
Solar/Wind Harmer
2.582
274674JOLIET 9 ;6U
Adder
7.858
971573AH1-285 GEN
Solar/Wind Harmer
4.365
24441505OLIV SLR
Solar/Wind Harmer
0.067
274695ROCKY RD ;2P
Adder
5.598
274693ROCKY RD ;1P
Adder
5.543
274697ROCKY RD ;3P
Adder
1.521
274696ROCKY RD ;4P
Adder
5.73
270526AF1-158 GEN
Solar/Wind Harmer
2.28
274683WAUKEGAN ;8U
Adder
10.555
274683WAUKEGAN ;8U
Adder
8.898
962691AG1-118 GEN
Solar/Wind Harmer
14.993
958481AF2-142 GEN
Solar/Wind Harmer
7.48
24721805FLATG3
50/50
1.053
24721705FLATG2
50/50
19.311
962761AG1-125 GEN
Solar/Wind Harmer
77.904
970149AG2-104 GEN
Solar/Wind Harmer
96.211
970155AG2-107 GEN
Solar/Wind Harmer
33.97
970245AG2-165 GEN
Solar/Wind Harmer
10.689
972207SS24-0001
Solar/Wind Harmer
11.773
274773LINCOLN ;4U
Adder
3.311
274774LINCOLN ;5U
Adder
3.311
276164X3-005 C
Solar/Wind Harmer
0.363
274723RIVER EC ;12
Adder
9.243
276776AD2-060 GEN
Solar/Wind Harmer
0.217
941551AE2-152 GEN
Solar/Wind Harmer
2.327
274801UNIV PARK;4U
Adder
2.991
274812UNIV PK N;8U
Adder
2.566
274751CRETE EC ;1U
Adder
2.501
274754CRETE EC ;4U
Adder
2.501
274676JOLIET 29;8U
Adder
15.68
274871GR RIDGE ;2U
Solar/Wind Harmer
3.925
274674JOLIET 9 ;6U
Adder
7.858
274732ELWOOD EC;7P
Adder
8.375
274745AC1-111 GEN9
Adder
2.844
274682WAUKEGAN ;7U
Adder
9.013
274828WAUKEGAN ;BP
Adder
5.533
276691AA1-018 GEN1
Solar/Wind Harmer
0.232
960751AF2-366 GEN
Solar/Wind Harmer
1.43
962781AG1-127 GEN
Solar/Wind Harmer
4.741
274872LEEDK;1U
Solar/Wind Harmer
4.086
939401AE1-172 GEN
Solar/Wind Harmer
6.872
970373AG2-245 GEN
Solar/Wind Harmer
10.354
276901AD2-066 C O1
Solar/Wind Harmer
1.731
276861AD2-134 GEN
Solar/Wind Harmer
0.88
971997AH1-543 GEN
Solar/Wind Harmer
7.735
957471AF2-041 GEN
Solar/Wind Harmer
14.684
959081AF2-199 GEN
Solar/Wind Harmer
4.895
971067AG2-660 GEN
Solar/Wind Harmer
1.138
274822ROCKFORD ;11
Adder
9.575
972235AH1-702 GEN1
Adder
1.227
970819AG2-516 GEN
Solar/Wind Harmer
5.823
276876AE1-163_GEN2
Solar/Wind Harmer
3.256
971475AH1-234 GEN
Solar/Wind Harmer
10.842
270055AF2-134 C O1
Solar/Wind Harmer
1.46
274857EASY ROAD;U1
Solar/Wind Harmer
2.299
274761LEE CO EC;2U
Adder
4.462
274766LEE CO EC;7U
Adder
4.41
24639705ELKHART HY
Adder
0.07
270349AD2-093_GEN
Solar/Wind Helper
4.693
270223U2-072_GEN1
Solar/Wind Helper
1.533
270578AF1-285 GEN2
Solar/Wind Helper
1.039
270391AF1-285 GEN3
Solar/Wind Helper
1.039
270462AD2-086
Solar/Wind Helper
5.36
247522W1-056 GEN
Solar/Wind Helper
1.162
253343AC1-166 GEN
Solar/Wind Helper
0.845
253325AC1-069 GEN
Solar/Wind Helper
0.876
960841AF2-375 GEN
Solar/Wind Helper
1.157
270263AC1-001 GEN
Solar/Wind Helper
0.553
958961AF2-187 GEN
Solar/Wind Helper
1.122
241840AF1-064_GEN
Solar/Wind Helper
0.48
241807AE2-176_GEN
Solar/Wind Helper
0.701
970569AG2-363 GEN
Solar/Wind Harmer
9.346
24722005FLATG5
50/50
1.053
24721905FLATG4
50/50
19.311
970153AG2-106 GEN
Solar/Wind Harmer
33.97
970513AG2-328 GEN
Solar/Wind Harmer
10.689
970517AG2-330 GEN
Solar/Wind Harmer
9.695
970349AG2-230 GEN
Solar/Wind Harmer
8.59
274772LINCOLN ;3U
Adder
3.311
970707AG2-453 GEN
Solar/Wind Harmer
14.62
274724RIVER EC ;11
Adder
9.141
972228AH1-698 GEN2
Adder
1.905
276772AC2-154 GEN
Solar/Wind Harmer
1.432
276806AD2-047 C O1
Solar/Wind Harmer
5.495
970941AG2-585 GEN
Solar/Wind Harmer
6.421
274826FISK ;BP
Adder
5.62
276897AD1-100 C
Solar/Wind Harmer
14.891
939351AE1-166 GEN
Solar/Wind Harmer
3.043
274800UNIV PARK;3U
Adder
2.991
972038AH1-567 GEN2
Adder
0.187
274802UNIV PARK;5U
Adder
2.989
972231SS25-0005
Solar/Wind Harmer
4.856
972181SS23-001
Solar/Wind Harmer
3.035
274752CRETE EC ;2U
Adder
2.501
274753CRETE EC ;3U
Adder
2.501
274676JOLIET 29;8U
Adder
15.12
943121AE2-341 GEN
Solar/Wind Harmer
7.658
943591AF1-030 GEN
Solar/Wind Harmer
5.105
274729ELWOOD EC;1P
Adder
8.375
274730ELWOOD EC;6P
Adder
8.375
274734ELWOOD EC;8P
Adder
8.375
274736ELWOOD EC;9P
Adder
8.375
276893AG1-478 C
Solar/Wind Harmer
0.213
274682WAUKEGAN ;7U
Adder
9.013
276694AA1-018 GEN2
Solar/Wind Harmer
3.147
274872LEEDK;1U
Solar/Wind Harmer
0.127
276805AD2-038 GEN
Solar/Wind Harmer
2.528
276799AD1-013 GEN
Solar/Wind Harmer
1.09
946671AF1-331 GEN
Solar/Wind Harmer
0.206
274855GSG-6 ;RU
Solar/Wind Harmer
1.819
274850MENDOTA H;RU
Solar/Wind Harmer
1.265
276602WESTBROOK C
Solar/Wind Harmer
1.047
276863AD2-134 GEN
Solar/Wind Harmer
0.88
959091AF2-200 GEN
Solar/Wind Harmer
9.789
972236AH1-702 GEN2
Adder
1.067
276889AE2-281 GEN
Solar/Wind Harmer
0.93
24642205MAYFLWER
Adder
0.307
270535AF1-215 GEN1
Solar/Wind Harmer
2.191
247643Z2-116 C
Solar/Wind Harmer
0.033
274858EASY ROAD;U2
Solar/Wind Harmer
2.299
274760LEE CO EC;1U
Adder
4.462
274767LEE CO EC;8U
Adder
4.41
247604X1-042
Adder
0.181
942871AE2-306 GEN
Solar/Wind Helper
0.779
270485AE1-090_GEN
Solar/Wind Helper
0.466
241974AD2-163_GEN2
Solar/Wind Helper
2.431
241955AC1-078 GEN
Solar/Wind Helper
2.426
960801AF2-371 GEN
Solar/Wind Helper
0.868
964871AG1-351 GEN
Solar/Wind Helper
0.6
253338AC1-165 GEN
Solar/Wind Helper
0.845
253333AC1-068 GEN
Solar/Wind Helper
0.876
270273AD2-016 GEN
Solar/Wind Helper
1.697
270541AE2-072 C
Solar/Wind Helper
1.119
253415AE1-040 GEN
Solar/Wind Helper
0.466
970571AG2-364 GEN
Solar/Wind Harmer
6.231
970921AG2-575 GEN
Solar/Wind Harmer
4.986
970921AG2-575 GEN
Solar/Wind Harmer
1.159
274861TOP CROP ;1U
Solar/Wind Harmer
3.02
274862TOP CROP ;2U
Solar/Wind Harmer
2.522
942991AE2-321 GEN
Solar/Wind Harmer
4.946
958491AF2-143 GEN
Solar/Wind Harmer
7.393
971333AH1-146 GEN
Solar/Wind Harmer
9.845
971335AH1-147 GEN
Solar/Wind Harmer
9.845
274879MINONK ;1U
Solar/Wind Harmer
3.315
971341AH1-150 GEN
Solar/Wind Harmer
9.789
971343AH1-151 GEN
Solar/Wind Harmer
9.789
276872AE1-163_GEN1
Solar/Wind Harmer
3.256
274856ECOGROVE ;U1
Solar/Wind Harmer
1.634
276611AD2-172 GEN
Solar/Wind Harmer
1.24
938861AE1-114 GEN
Solar/Wind Harmer
3.946
274764LEE CO EC;5U
Adder
4.473
274765LEE CO EC;6U
Adder
4.473
274762LEE CO EC;3U
Adder
4.462
274763LEE CO EC;4U
Adder
4.42
972267AH1-718 GEN
Adder
1.978
247620Y3-023
Adder
0.201
270471AD2-092_GEN
Solar/Wind Helper
4.693
270224U2-072_GEN2
Solar/Wind Helper
1.533
270227U2-072_GEN3
Solar/Wind Helper
1.533
270228U2-072_GEN4
Solar/Wind Helper
1.533
270231U2-072_GEN5
Solar/Wind Helper
1.533
946101AF1-275 GEN
Solar/Wind Helper
0.8
241960AC2-195 GEN
Solar/Wind Helper
1.847
253378AE2-206_GEN
Solar/Wind Helper
1.303
276820AF1-078_GEN
Solar/Wind Helper
0.609
270518AE2-148 GEN
Solar/Wind Helper
10.798
24721605FLATG1
50/50
1.053
962771AG1-126 GEN
Solar/Wind Harmer
77.904
971347AH1-153 GEN
Solar/Wind Harmer
8.59
274775LINCOLN ;6U
Adder
3.311
274776LINCOLN ;7U
Adder
3.311
274777LINCOLN ;8U
Adder
3.311
960681AF2-359 GEN
Solar/Wind Harmer
1.96
972227AH1-698 GEN1
Adder
1.342
960591AF2-350 GEN
Solar/Wind Harmer
5.137
274827FISK ;RP
Adder
3.983
972037AH1-567 GEN1
Adder
0.094
274814UNIV PK N;0U
Adder
2.588
274807UNIV PK N;3U
Adder
2.582
274805UNIV PK N;1U
Adder
2.571
274811UNIV PK N;7U
Adder
2.566
274687WILL CNTY;4U
Adder
14.282
274687WILL CNTY;4U
Adder
14.282
274675JOLIET 29;7U
Adder
15.681
274675JOLIET 29;7U
Adder
15.121
970833AG2-524 GEN
Solar/Wind Harmer
4.457
970833AG2-524 GEN
Solar/Wind Harmer
2.073
274731ELWOOD EC;2P
Adder
8.375
274733ELWOOD EC;3P
Adder
8.375
274735ELWOOD EC;4P
Adder
8.375
274728ELWOOD EC;5P
Adder
8.375
274746AC1-111 G10
Adder
2.844
274744AC1-111 GEN8
Adder
2.844
971769AH1-391 GEN
Solar/Wind Harmer
5.034
971771AH1-392 GEN
Solar/Wind Harmer
4.46
971177AH1-047 GEN
Solar/Wind Harmer
2.897
971675AH1-338 GEN
Solar/Wind Harmer
8.869
971411AH1-196 GEN
Solar/Wind Harmer
7.388
276868AE1-113 GEN
Solar/Wind Harmer
4.972
276882AE2-255 GEN
Solar/Wind Harmer
1.658
971171AH1-044 GEN
Solar/Wind Harmer
9.789
274823ROCKFORD ;21
Adder
9.506
274863CRW1-WTG
Solar/Wind Harmer
2.706
274864CRW2-WTG
Solar/Wind Harmer
2.706
276612AE2-035 GEN
Solar/Wind Harmer
1.24
270536AF1-215 GEN2
Solar/Wind Harmer
2.191
971681AH1-341 GEN
Solar/Wind Harmer
7.223
926823AC1-168 GEN
Solar/Wind Harmer
2.065
270284AF1-227 GEN1
Solar/Wind Helper
6.376
270286AF1-227 GEN2
Solar/Wind Helper
2.338
270287AF1-227 GEN3
Solar/Wind Helper
2.338
270317AD1-130_GEN
Solar/Wind Helper
5.937
253383AE2-342_GEN
Solar/Wind Helper
1.121
241973AD2-163_GEN1
Solar/Wind Helper
2.431
270520AE2-214 GEN
Solar/Wind Helper
6.39
270054AF2-122 C O1
Solar/Wind Helper
1.464
945631AF1-228 GEN
Solar/Wind Helper
1.901
966831AG1-554 GEN
Solar/Wind Helper
0.865
241972AD1-140 GEN
Solar/Wind Helper
3.138
945641AF1-229 GEN
Solar/Wind Helper
1.105
270499AE1-146 GEN
Solar/Wind Helper
1.894
270340AC2-060 GEN
Solar/Wind Helper
0.99
NYPJM->LTFIMP_NY
CLTF
0.909
LGEELTFEXP_LGEE->PJM
CLTF
0.796
WECLTFEXP_WEC->PJM
CLTF
1.857
AG2-052LTFEXP_AG2-052->PJM
LTF
0.11
AH1-155LTFEXP_AH1-155->PJM
LTF
0.165
CPLELTFEXP_CPLE->PJM
CLTF
1.514
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.052
LAGNLTFEXP_LAGN->PJM
CLTF
5.373
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.182
TVALTFEXP_TVA->PJM
CLTF
2.391
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.839
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.144
MECLTFEXP_MEC->PJM
CLTF
6.964
SIGELTFEXP_SIGE->PJM
CLTF
0.112

Details for 05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer l/o AEP_P1-2_#711_6224_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
Contingency Name:
AEP_P1-2_#711_6224_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.12 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3255.61
MW Contribution:42.12
Bus #Bus NameTypeMW Contribution
24722005FLATG5
50/50
1.058
24721905FLATG4
50/50
19.393
24318705GVG2
50/50
2.909
970153AG2-106 GEN
Solar/Wind Harmer
42.119
970513AG2-328 GEN
Solar/Wind Harmer
1.836
970517AG2-330 GEN
Solar/Wind Harmer
11.017
970349AG2-230 GEN
Solar/Wind Harmer
6.085
274772LINCOLN ;3U
Adder
4.58
970707AG2-453 GEN
Solar/Wind Harmer
12.094
274724RIVER EC ;11
Adder
9.292
972228AH1-698 GEN2
Adder
1.937
276806AD2-047 C O1
Solar/Wind Harmer
2.065
970941AG2-585 GEN
Solar/Wind Harmer
4.554
274826FISK ;BP
Adder
5.714
276897AD1-100 C
Solar/Wind Harmer
0.005
939351AE1-166 GEN
Solar/Wind Harmer
0
274800UNIV PARK;3U
Adder
3.041
972038AH1-567 GEN2
Adder
0.19
274802UNIV PARK;5U
Adder
3.039
274752CRETE EC ;2U
Adder
4.287
274753CRETE EC ;3U
Adder
4.287
274676JOLIET 29;8U
Adder
15.371
943121AE2-341 GEN
Solar/Wind Harmer
6.071
943591AF1-030 GEN
Solar/Wind Harmer
4.037
274729ELWOOD EC;1P
Adder
8.515
274730ELWOOD EC;6P
Adder
8.515
274734ELWOOD EC;8P
Adder
8.515
274736ELWOOD EC;9P
Adder
8.515
276893AG1-478 C
Solar/Wind Harmer
0.143
274682WAUKEGAN ;7U
Adder
9.164
276694AA1-018 GEN2
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0.129
276805AD2-038 GEN
Solar/Wind Harmer
0.001
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.373
274855GSG-6 ;RU
Solar/Wind Harmer
0.128
274850MENDOTA H;RU
Solar/Wind Harmer
0.041
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.063
959091AF2-200 GEN
Solar/Wind Harmer
6.946
972236AH1-702 GEN2
Adder
1.085
276889AE2-281 GEN
Solar/Wind Harmer
0
24642205MAYFLWER
Adder
0.313
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
247643Z2-116 C
Solar/Wind Harmer
0
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
4.539
274767LEE CO EC;8U
Adder
4.486
970571AG2-364 GEN
Solar/Wind Harmer
6.804
964401AG1-302 GEN
Solar/Wind Harmer
0.001
276157O29GEN1
Solar/Wind Harmer
0.543
274878BISHOP HL;2U
Solar/Wind Harmer
0.111
945111AF1-176 GEN
Solar/Wind Harmer
2.681
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
965931AG1-462 GEN
Solar/Wind Harmer
8.314
942111AE2-223 GEN
Solar/Wind Harmer
1.053
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
9.533
959611AF2-252 GEN
Solar/Wind Harmer
1.059
24441205WTRV SLR C
Solar/Wind Harmer
0
270043AE2-236 GEN
Solar/Wind Harmer
2.016
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.112
247604X1-042
Adder
0.185
944531AF1-118 GEN
Solar/Wind Harmer
13.488
942871AE2-306 GEN
Solar/Wind Helper
0.773
270485AE1-090_GEN
Solar/Wind Helper
0.463
241974AD2-163_GEN2
Solar/Wind Helper
2.393
241955AC1-078 GEN
Solar/Wind Helper
2.378
960801AF2-371 GEN
Solar/Wind Helper
0.85
964871AG1-351 GEN
Solar/Wind Helper
0.587
253338AC1-165 GEN
Solar/Wind Helper
0.826
253333AC1-068 GEN
Solar/Wind Helper
0.856
270273AD2-016 GEN
Solar/Wind Helper
1.657
270541AE2-072 C
Solar/Wind Helper
1.102
253415AE1-040 GEN
Solar/Wind Helper
0.453
243186AF1-051 GEN
50/50
3.125
970321AG2-212 GEN
Solar/Wind Harmer
1.836
274770LINCOLN ;1U
Adder
4.58
274771LINCOLN ;2U
Adder
4.58
965681AG1-436 GEN
Solar/Wind Harmer
4.601
965791AG1-447 GEN
Solar/Wind Harmer
3.374
972259AH1-714 GEN
Adder
10.035
274888KELLY CRK;1U
Solar/Wind Harmer
0.214
274887GEN-1.85
Solar/Wind Harmer
0.096
276843GEN-1.7
Solar/Wind Harmer
0.118
958011AF2-095 GEN
Solar/Wind Harmer
5.246
274803UNIV PARK;6U
Adder
3.039
274808UNIV PK N;4U
Adder
2.597
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
274674JOLIET 9 ;6U
Adder
7.988
971573AH1-285 GEN
Solar/Wind Harmer
0.671
24441505OLIV SLR
Solar/Wind Harmer
0
274696ROCKY RD ;4P
Adder
5.826
274695ROCKY RD ;2P
Adder
5.692
274693ROCKY RD ;1P
Adder
5.636
274697ROCKY RD ;3P
Adder
1.546
270526AF1-158 GEN
Solar/Wind Harmer
0.004
274683WAUKEGAN ;8U
Adder
10.733
274683WAUKEGAN ;8U
Adder
9.047
962691AG1-118 GEN
Solar/Wind Harmer
10.636
958481AF2-142 GEN
Solar/Wind Harmer
5.307
970921AG2-575 GEN
Solar/Wind Harmer
3.537
970921AG2-575 GEN
Solar/Wind Harmer
1.179
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.478
942991AE2-321 GEN
Solar/Wind Harmer
3.919
958491AF2-143 GEN
Solar/Wind Harmer
5.246
971333AH1-146 GEN
Solar/Wind Harmer
6.985
971335AH1-147 GEN
Solar/Wind Harmer
6.985
274879MINONK ;1U
Solar/Wind Harmer
0.147
971341AH1-150 GEN
Solar/Wind Harmer
6.946
971343AH1-151 GEN
Solar/Wind Harmer
6.946
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
274856ECOGROVE ;U1
Solar/Wind Harmer
0.081
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
1.936
274764LEE CO EC;5U
Adder
4.55
274765LEE CO EC;6U
Adder
4.55
274762LEE CO EC;3U
Adder
4.539
274763LEE CO EC;4U
Adder
4.497
276603SUBLETTE C
Solar/Wind Harmer
0
270216AD2-079_GEN
Solar/Wind Harmer
0.001
972267AH1-718 GEN
Adder
2.012
957891AF2-083 GEN
Solar/Wind Harmer
0
276741O09 GEN1
Solar/Wind Harmer
0.12
276708O09 GEN2
Solar/Wind Harmer
0.12
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.131
276646AC1-214 GEN2
Solar/Wind Harmer
0.131
276782AC1-033 GEN
Solar/Wind Harmer
0
961051AF2-396 GEN
Solar/Wind Harmer
6.595
961051AF2-396 GEN
Solar/Wind Harmer
4.397
960611AF2-352 GEN
Solar/Wind Harmer
1.059
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
247620Y3-023
Adder
0.206
270471AD2-092_GEN
Solar/Wind Helper
4.665
270224U2-072_GEN2
Solar/Wind Helper
1.522
270227U2-072_GEN3
Solar/Wind Helper
1.522
270228U2-072_GEN4
Solar/Wind Helper
1.522
270231U2-072_GEN5
Solar/Wind Helper
1.522
946101AF1-275 GEN
Solar/Wind Helper
0.783
241960AC2-195 GEN
Solar/Wind Helper
1.825
253378AE2-206_GEN
Solar/Wind Helper
1.285
276820AF1-078_GEN
Solar/Wind Helper
0.6
270518AE2-148 GEN
Solar/Wind Helper
10.557
24721605FLATG1
50/50
1.058
971599AH1-298 GEN
50/50
4.831
962771AG1-126 GEN
Solar/Wind Harmer
65.959
971347AH1-153 GEN
Solar/Wind Harmer
6.085
274775LINCOLN ;6U
Adder
4.58
274776LINCOLN ;7U
Adder
4.58
274777LINCOLN ;8U
Adder
4.58
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
972227AH1-698 GEN1
Adder
1.364
960591AF2-350 GEN
Solar/Wind Harmer
3.643
274827FISK ;RP
Adder
4.049
972037AH1-567 GEN1
Adder
0.095
274814UNIV PK N;0U
Adder
2.631
274807UNIV PK N;3U
Adder
2.626
274805UNIV PK N;1U
Adder
2.614
274811UNIV PK N;7U
Adder
2.608
274687WILL CNTY;4U
Adder
14.52
274687WILL CNTY;4U
Adder
14.52
274675JOLIET 29;7U
Adder
15.941
274675JOLIET 29;7U
Adder
15.372
970833AG2-524 GEN
Solar/Wind Harmer
3.983
970833AG2-524 GEN
Solar/Wind Harmer
2.655
274731ELWOOD EC;2P
Adder
8.515
274733ELWOOD EC;3P
Adder
8.515
274735ELWOOD EC;4P
Adder
8.515
274728ELWOOD EC;5P
Adder
8.515
274746AC1-111 G10
Adder
2.891
274744AC1-111 GEN8
Adder
2.891
971769AH1-391 GEN
Solar/Wind Harmer
3.99
971771AH1-392 GEN
Solar/Wind Harmer
3.518
971177AH1-047 GEN
Solar/Wind Harmer
2.163
971675AH1-338 GEN
Solar/Wind Harmer
1.363
971411AH1-196 GEN
Solar/Wind Harmer
5.242
276868AE1-113 GEN
Solar/Wind Harmer
0.7
276882AE2-255 GEN
Solar/Wind Harmer
0.408
971171AH1-044 GEN
Solar/Wind Harmer
6.946
274823ROCKFORD ;21
Adder
9.668
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
276612AE2-035 GEN
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
971681AH1-341 GEN
Solar/Wind Harmer
5.502
926823AC1-168 GEN
Solar/Wind Harmer
0.579
970169AG2-114 GEN
Solar/Wind Harmer
3.38
961011AF2-392 GEN
Solar/Wind Harmer
1.983
971619AH1-309 GEN
Solar/Wind Harmer
1.52
957751AF2-069 GEN
Solar/Wind Harmer
0.11
958391AF2-133 GEN
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
946321AF1-296 GEN
Solar/Wind Harmer
1.836
971611AH1-305 GEN
Solar/Wind Harmer
1.944
276655WTG1_EQ
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.401
941731AE2-173 GEN
Solar/Wind Harmer
2.699
24721805FLATG3
50/50
1.058
24721705FLATG2
50/50
19.393
24344105CKG2
50/50
4.731
243186AF1-051 GEN
50/50
3.125
24318705GVG2
50/50
2.909
962761AG1-125 GEN
Solar/Wind Harmer
65.959
970149AG2-104 GEN
Solar/Wind Harmer
71.237
970155AG2-107 GEN
Solar/Wind Harmer
42.119
970245AG2-165 GEN
Solar/Wind Harmer
1.836
274773LINCOLN ;4U
Adder
4.58
274774LINCOLN ;5U
Adder
4.58
276164X3-005 C
Solar/Wind Harmer
0
274723RIVER EC ;12
Adder
9.397
276776AD2-060 GEN
Solar/Wind Harmer
0.38
941551AE2-152 GEN
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
3.041
274812UNIV PK N;8U
Adder
2.608
274751CRETE EC ;1U
Adder
4.287
274754CRETE EC ;4U
Adder
4.287
274676JOLIET 29;8U
Adder
15.941
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
7.988
274732ELWOOD EC;7P
Adder
8.515
274745AC1-111 GEN9
Adder
2.891
274682WAUKEGAN ;7U
Adder
9.164
274828WAUKEGAN ;BP
Adder
5.626
276691AA1-018 GEN1
Solar/Wind Harmer
0.429
962781AG1-127 GEN
Solar/Wind Harmer
3.366
274872LEEDK;1U
Solar/Wind Harmer
0.002
970373AG2-245 GEN
Solar/Wind Harmer
7.35
939401AE1-172 GEN
Solar/Wind Harmer
2.617
276901AD2-066 C O1
Solar/Wind Harmer
0.003
276861AD2-134 GEN
Solar/Wind Harmer
0.063
971997AH1-543 GEN
Solar/Wind Harmer
1.83
957471AF2-041 GEN
Solar/Wind Harmer
10.419
959081AF2-199 GEN
Solar/Wind Harmer
3.473
971067AG2-660 GEN
Solar/Wind Harmer
1.158
274822ROCKFORD ;11
Adder
9.739
972235AH1-702 GEN1
Adder
1.248
970819AG2-516 GEN
Solar/Wind Harmer
4.132
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
971475AH1-234 GEN
Solar/Wind Harmer
1.667
270055AF2-134 C O1
Solar/Wind Harmer
0.003
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
4.539
274766LEE CO EC;7U
Adder
4.486
970569AG2-363 GEN
Solar/Wind Harmer
10.206
270505AE1-170 C O1
Solar/Wind Harmer
3.548
958381AF2-132 GEN
Solar/Wind Harmer
0.001
276158O29GEN2
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.356
274877BISHOP HL;1U
Solar/Wind Harmer
0.111
945111AF1-176 GEN
Solar/Wind Harmer
5.901
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
1.718
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.081
24639705ELKHART HY
Adder
0.072
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
4.535
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
24791305MDL-5G
Solar/Wind Harmer
0
972175AH1-670 GEN
Solar/Wind Harmer
2.538
270349AD2-093_GEN
Solar/Wind Helper
4.665
270223U2-072_GEN1
Solar/Wind Helper
1.522
270578AF1-285 GEN2
Solar/Wind Helper
1.031
270391AF1-285 GEN3
Solar/Wind Helper
1.031
270462AD2-086
Solar/Wind Helper
5.319
247522W1-056 GEN
Solar/Wind Helper
1.149
253343AC1-166 GEN
Solar/Wind Helper
0.826
253325AC1-069 GEN
Solar/Wind Helper
0.856
960841AF2-375 GEN
Solar/Wind Helper
1.143
958961AF2-187 GEN
Solar/Wind Helper
1.121
270263AC1-001 GEN
Solar/Wind Helper
0.539
241840AF1-064_GEN
Solar/Wind Helper
0.473
241807AE2-176_GEN
Solar/Wind Helper
0.695
270071AF1-092 GEN
Solar/Wind Harmer
6.128
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0
270181AB1-006 GEN2
Solar/Wind Harmer
0
270284AF1-227 GEN1
Solar/Wind Helper
6.336
270286AF1-227 GEN2
Solar/Wind Helper
2.323
270287AF1-227 GEN3
Solar/Wind Helper
2.323
270317AD1-130_GEN
Solar/Wind Helper
5.891
253383AE2-342_GEN
Solar/Wind Helper
1.103
241973AD2-163_GEN1
Solar/Wind Helper
2.393
270520AE2-214 GEN
Solar/Wind Helper
6.251
270054AF2-122 C O1
Solar/Wind Helper
1.45
945631AF1-228 GEN
Solar/Wind Helper
1.86
966831AG1-554 GEN
Solar/Wind Helper
0.856
241972AD1-140 GEN
Solar/Wind Helper
3.072
945641AF1-229 GEN
Solar/Wind Helper
1.093
270499AE1-146 GEN
Solar/Wind Helper
1.872
270340AC2-060 GEN
Solar/Wind Helper
0.963
NYPJM->LTFIMP_NY
CLTF
0.939
LGEELTFEXP_LGEE->PJM
CLTF
0.854
WECLTFEXP_WEC->PJM
CLTF
1.888
AG2-052LTFEXP_AG2-052->PJM
LTF
0.112
AH1-155LTFEXP_AH1-155->PJM
LTF
0.168
CPLELTFEXP_CPLE->PJM
CLTF
1.524
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.966
LAGNLTFEXP_LAGN->PJM
CLTF
5.489
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.243
TVALTFEXP_TVA->PJM
CLTF
2.447
CBM West 1LTFEXP_CBM-W1->PJM
CBM
42.979
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.373
MECLTFEXP_MEC->PJM
CLTF
7.095
SIGELTFEXP_SIGE->PJM
CLTF
0.116

Details for 05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer l/o AEP_P1-3_#7222_05MALIS 765_1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
Contingency Name:
AEP_P1-3_#7222_05MALIS 765_1_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.65 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3241.06
MW Contribution:41.97
Bus #Bus NameTypeMW Contribution
24722005FLATG5
50/50
1.054
24721905FLATG4
50/50
19.316
24318705GVG2
50/50
2.897
970153AG2-106 GEN
Solar/Wind Harmer
41.966
970513AG2-328 GEN
Solar/Wind Harmer
1.811
970517AG2-330 GEN
Solar/Wind Harmer
10.868
970349AG2-230 GEN
Solar/Wind Harmer
5.999
274772LINCOLN ;3U
Adder
4.511
970707AG2-453 GEN
Solar/Wind Harmer
11.912
274724RIVER EC ;11
Adder
9.15
972228AH1-698 GEN2
Adder
1.907
276806AD2-047 C O1
Solar/Wind Harmer
2.033
970941AG2-585 GEN
Solar/Wind Harmer
4.484
274826FISK ;BP
Adder
5.626
276897AD1-100 C
Solar/Wind Harmer
0.005
939351AE1-166 GEN
Solar/Wind Harmer
0
274800UNIV PARK;3U
Adder
2.994
243186AF1-051 GEN
50/50
3.112
970321AG2-212 GEN
Solar/Wind Harmer
1.811
274770LINCOLN ;1U
Adder
4.511
274771LINCOLN ;2U
Adder
4.511
965681AG1-436 GEN
Solar/Wind Harmer
4.53
965791AG1-447 GEN
Solar/Wind Harmer
3.322
972259AH1-714 GEN
Adder
9.882
274888KELLY CRK;1U
Solar/Wind Harmer
0.211
274887GEN-1.85
Solar/Wind Harmer
0.094
276843GEN-1.7
Solar/Wind Harmer
0.116
958011AF2-095 GEN
Solar/Wind Harmer
5.166
274803UNIV PARK;6U
Adder
2.992
274808UNIV PK N;4U
Adder
2.557
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
274674JOLIET 9 ;6U
Adder
7.865
971573AH1-285 GEN
Solar/Wind Harmer
0.66
24441505OLIV SLR
Solar/Wind Harmer
0
274696ROCKY RD ;4P
Adder
5.736
274695ROCKY RD ;2P
Adder
5.604
274693ROCKY RD ;1P
Adder
5.549
274697ROCKY RD ;3P
Adder
1.522
270526AF1-158 GEN
Solar/Wind Harmer
0.004
274683WAUKEGAN ;8U
Adder
10.566
274683WAUKEGAN ;8U
Adder
8.906
962691AG1-118 GEN
Solar/Wind Harmer
10.47
958481AF2-142 GEN
Solar/Wind Harmer
5.224
970921AG2-575 GEN
Solar/Wind Harmer
3.482
970921AG2-575 GEN
Solar/Wind Harmer
1.161
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.471
942991AE2-321 GEN
Solar/Wind Harmer
3.857
958491AF2-143 GEN
Solar/Wind Harmer
5.163
971333AH1-146 GEN
Solar/Wind Harmer
6.875
971335AH1-147 GEN
Solar/Wind Harmer
6.875
274879MINONK ;1U
Solar/Wind Harmer
0.145
971341AH1-150 GEN
Solar/Wind Harmer
6.836
971343AH1-151 GEN
Solar/Wind Harmer
6.836
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
274856ECOGROVE ;U1
Solar/Wind Harmer
0.08
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
1.905
274764LEE CO EC;5U
Adder
4.477
274765LEE CO EC;6U
Adder
4.477
274762LEE CO EC;3U
Adder
4.467
274763LEE CO EC;4U
Adder
4.425
276603SUBLETTE C
Solar/Wind Harmer
0
270216AD2-079_GEN
Solar/Wind Harmer
0.001
972267AH1-718 GEN
Adder
1.98
957891AF2-083 GEN
Solar/Wind Harmer
0
276741O09 GEN1
Solar/Wind Harmer
0.118
24721805FLATG3
50/50
1.054
24721705FLATG2
50/50
19.316
24344105CKG2
50/50
4.668
243186AF1-051 GEN
50/50
3.112
24318705GVG2
50/50
2.897
962761AG1-125 GEN
Solar/Wind Harmer
65.719
970149AG2-104 GEN
Solar/Wind Harmer
70.979
970155AG2-107 GEN
Solar/Wind Harmer
41.966
970245AG2-165 GEN
Solar/Wind Harmer
1.811
274773LINCOLN ;4U
Adder
4.511
274774LINCOLN ;5U
Adder
4.511
276164X3-005 C
Solar/Wind Harmer
0
274723RIVER EC ;12
Adder
9.252
276776AD2-060 GEN
Solar/Wind Harmer
0.375
941551AE2-152 GEN
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
2.994
274812UNIV PK N;8U
Adder
2.568
24721605FLATG1
50/50
1.054
971599AH1-298 GEN
50/50
4.754
962771AG1-126 GEN
Solar/Wind Harmer
65.719
971347AH1-153 GEN
Solar/Wind Harmer
5.999
274775LINCOLN ;6U
Adder
4.511
274776LINCOLN ;7U
Adder
4.511
274777LINCOLN ;8U
Adder
4.511
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
972227AH1-698 GEN1
Adder
1.343
960591AF2-350 GEN
Solar/Wind Harmer
3.587
274827FISK ;RP
Adder
3.987
972037AH1-567 GEN1
Adder
0.094
274814UNIV PK N;0U
Adder
2.591
274807UNIV PK N;3U
Adder
2.585
274805UNIV PK N;1U
Adder
2.574
274811UNIV PK N;7U
Adder
2.568
274675JOLIET 29;7U
Adder
15.696
274675JOLIET 29;7U
Adder
15.135
274687WILL CNTY;4U
Adder
14.296
274687WILL CNTY;4U
Adder
14.296
970833AG2-524 GEN
Solar/Wind Harmer
3.922
970833AG2-524 GEN
Solar/Wind Harmer
2.615
274731ELWOOD EC;2P
Adder
8.383
274733ELWOOD EC;3P
Adder
8.383
274735ELWOOD EC;4P
Adder
8.383
274728ELWOOD EC;5P
Adder
8.383
274746AC1-111 G10
Adder
2.846
274744AC1-111 GEN8
Adder
2.846
971769AH1-391 GEN
Solar/Wind Harmer
3.926
971771AH1-392 GEN
Solar/Wind Harmer
3.461
971177AH1-047 GEN
Solar/Wind Harmer
2.129
971675AH1-338 GEN
Solar/Wind Harmer
1.342
971411AH1-196 GEN
Solar/Wind Harmer
5.159
276868AE1-113 GEN
Solar/Wind Harmer
0.688
276882AE2-255 GEN
Solar/Wind Harmer
0.401
971171AH1-044 GEN
Solar/Wind Harmer
6.836
274823ROCKFORD ;21
Adder
9.515
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
276612AE2-035 GEN
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
971681AH1-341 GEN
Solar/Wind Harmer
5.414
926823AC1-168 GEN
Solar/Wind Harmer
0.57
970169AG2-114 GEN
Solar/Wind Harmer
3.325
961011AF2-392 GEN
Solar/Wind Harmer
1.951
971619AH1-309 GEN
Solar/Wind Harmer
1.495
957751AF2-069 GEN
Solar/Wind Harmer
0.108
958391AF2-133 GEN
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
946321AF1-296 GEN
Solar/Wind Harmer
1.806
971611AH1-305 GEN
Solar/Wind Harmer
1.91
276655WTG1_EQ
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.343
941731AE2-173 GEN
Solar/Wind Harmer
2.653
270071AF1-092 GEN
Solar/Wind Harmer
6.011
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0
270181AB1-006 GEN2
Solar/Wind Harmer
0
270284AF1-227 GEN1
Solar/Wind Helper
6.373
270286AF1-227 GEN2
Solar/Wind Helper
2.337
270287AF1-227 GEN3
Solar/Wind Helper
2.337
270317AD1-130_GEN
Solar/Wind Helper
5.933
253383AE2-342_GEN
Solar/Wind Helper
1.119
241973AD2-163_GEN1
Solar/Wind Helper
2.428
270520AE2-214 GEN
Solar/Wind Helper
6.383
270054AF2-122 C O1
Solar/Wind Helper
1.467
945631AF1-228 GEN
Solar/Wind Helper
1.9
966831AG1-554 GEN
Solar/Wind Helper
0.865
241972AD1-140 GEN
Solar/Wind Helper
3.134
945641AF1-229 GEN
Solar/Wind Helper
1.104
270499AE1-146 GEN
Solar/Wind Helper
1.892
270340AC2-060 GEN
Solar/Wind Helper
0.99
972038AH1-567 GEN2
Adder
0.187
274802UNIV PARK;5U
Adder
2.992
274752CRETE EC ;2U
Adder
4.22
274753CRETE EC ;3U
Adder
4.22
274676JOLIET 29;8U
Adder
15.135
943121AE2-341 GEN
Solar/Wind Harmer
5.978
943591AF1-030 GEN
Solar/Wind Harmer
3.975
274729ELWOOD EC;1P
Adder
8.383
274730ELWOOD EC;6P
Adder
8.383
274734ELWOOD EC;8P
Adder
8.383
274736ELWOOD EC;9P
Adder
8.383
276893AG1-478 C
Solar/Wind Harmer
0.141
274682WAUKEGAN ;7U
Adder
9.022
276694AA1-018 GEN2
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0.127
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.367
276805AD2-038 GEN
Solar/Wind Harmer
0.001
274855GSG-6 ;RU
Solar/Wind Harmer
0.126
274850MENDOTA H;RU
Solar/Wind Harmer
0.041
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.062
959091AF2-200 GEN
Solar/Wind Harmer
6.836
972236AH1-702 GEN2
Adder
1.068
276889AE2-281 GEN
Solar/Wind Harmer
0
24642205MAYFLWER
Adder
0.308
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
247643Z2-116 C
Solar/Wind Harmer
0
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
4.467
274767LEE CO EC;8U
Adder
4.414
970571AG2-364 GEN
Solar/Wind Harmer
6.694
276157O29GEN1
Solar/Wind Harmer
0.534
964401AG1-302 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.11
945111AF1-176 GEN
Solar/Wind Harmer
2.634
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
965931AG1-462 GEN
Solar/Wind Harmer
8.178
942111AE2-223 GEN
Solar/Wind Harmer
1.035
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
9.369
959611AF2-252 GEN
Solar/Wind Harmer
1.041
24441205WTRV SLR C
Solar/Wind Harmer
0
270043AE2-236 GEN
Solar/Wind Harmer
1.976
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.055
247604X1-042
Adder
0.181
942871AE2-306 GEN
Solar/Wind Helper
0.779
270485AE1-090_GEN
Solar/Wind Helper
0.466
241974AD2-163_GEN2
Solar/Wind Helper
2.428
241955AC1-078 GEN
Solar/Wind Helper
2.425
960801AF2-371 GEN
Solar/Wind Helper
0.869
964871AG1-351 GEN
Solar/Wind Helper
0.6
253338AC1-165 GEN
Solar/Wind Helper
0.845
253333AC1-068 GEN
Solar/Wind Helper
0.876
270273AD2-016 GEN
Solar/Wind Helper
1.698
270541AE2-072 C
Solar/Wind Helper
1.118
253415AE1-040 GEN
Solar/Wind Helper
0.466
276708O09 GEN2
Solar/Wind Harmer
0.118
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.129
276646AC1-214 GEN2
Solar/Wind Harmer
0.129
276782AC1-033 GEN
Solar/Wind Harmer
0
961051AF2-396 GEN
Solar/Wind Harmer
6.481
961051AF2-396 GEN
Solar/Wind Harmer
4.32
960611AF2-352 GEN
Solar/Wind Harmer
1.041
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
247620Y3-023
Adder
0.202
270471AD2-092_GEN
Solar/Wind Helper
4.69
270224U2-072_GEN2
Solar/Wind Helper
1.532
270227U2-072_GEN3
Solar/Wind Helper
1.532
270228U2-072_GEN4
Solar/Wind Helper
1.532
270231U2-072_GEN5
Solar/Wind Helper
1.532
946101AF1-275 GEN
Solar/Wind Helper
0.8
241960AC2-195 GEN
Solar/Wind Helper
1.845
253378AE2-206_GEN
Solar/Wind Helper
1.302
276820AF1-078_GEN
Solar/Wind Helper
0.608
270518AE2-148 GEN
Solar/Wind Helper
10.792
274751CRETE EC ;1U
Adder
4.22
274754CRETE EC ;4U
Adder
4.22
274676JOLIET 29;8U
Adder
15.695
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
7.865
274732ELWOOD EC;7P
Adder
8.383
274745AC1-111 GEN9
Adder
2.846
274682WAUKEGAN ;7U
Adder
9.022
274828WAUKEGAN ;BP
Adder
5.538
276691AA1-018 GEN1
Solar/Wind Harmer
0.422
962781AG1-127 GEN
Solar/Wind Harmer
3.313
274872LEEDK;1U
Solar/Wind Harmer
0.002
939401AE1-172 GEN
Solar/Wind Harmer
2.576
970373AG2-245 GEN
Solar/Wind Harmer
7.231
276901AD2-066 C O1
Solar/Wind Harmer
0.003
276861AD2-134 GEN
Solar/Wind Harmer
0.062
971997AH1-543 GEN
Solar/Wind Harmer
1.801
957471AF2-041 GEN
Solar/Wind Harmer
10.254
959081AF2-199 GEN
Solar/Wind Harmer
3.418
971067AG2-660 GEN
Solar/Wind Harmer
1.139
274822ROCKFORD ;11
Adder
9.585
972235AH1-702 GEN1
Adder
1.228
970819AG2-516 GEN
Solar/Wind Harmer
4.066
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
971475AH1-234 GEN
Solar/Wind Harmer
1.64
270055AF2-134 C O1
Solar/Wind Harmer
0.003
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
4.467
274766LEE CO EC;7U
Adder
4.414
970569AG2-363 GEN
Solar/Wind Harmer
10.041
270505AE1-170 C O1
Solar/Wind Harmer
3.488
276158O29GEN2
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.282
274877BISHOP HL;1U
Solar/Wind Harmer
0.11
945111AF1-176 GEN
Solar/Wind Harmer
5.799
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
1.689
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.011
24639705ELKHART HY
Adder
0.07
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
4.458
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
24791305MDL-5G
Solar/Wind Harmer
0
972175AH1-670 GEN
Solar/Wind Harmer
2.493
270349AD2-093_GEN
Solar/Wind Helper
4.69
270223U2-072_GEN1
Solar/Wind Helper
1.532
270578AF1-285 GEN2
Solar/Wind Helper
1.038
270391AF1-285 GEN3
Solar/Wind Helper
1.038
270462AD2-086
Solar/Wind Helper
5.357
247522W1-056 GEN
Solar/Wind Helper
1.161
253343AC1-166 GEN
Solar/Wind Helper
0.845
253325AC1-069 GEN
Solar/Wind Helper
0.876
960841AF2-375 GEN
Solar/Wind Helper
1.156
270263AC1-001 GEN
Solar/Wind Helper
0.553
958961AF2-187 GEN
Solar/Wind Helper
1.122
241840AF1-064_GEN
Solar/Wind Helper
0.48
241807AE2-176_GEN
Solar/Wind Helper
0.7
NYPJM->LTFIMP_NY
CLTF
0.911
LGEELTFEXP_LGEE->PJM
CLTF
0.799
WECLTFEXP_WEC->PJM
CLTF
1.858
AG2-052LTFEXP_AG2-052->PJM
LTF
0.11
AH1-155LTFEXP_AH1-155->PJM
LTF
0.166
CPLELTFEXP_CPLE->PJM
CLTF
1.514
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.096
LAGNLTFEXP_LAGN->PJM
CLTF
5.378
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.184
TVALTFEXP_TVA->PJM
CLTF
2.393
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.902
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.154
MECLTFEXP_MEC->PJM
CLTF
6.971
SIGELTFEXP_SIGE->PJM
CLTF
0.112

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AEP_P4_#2942_05KAMMER 765_PP_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.69 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:6156.87
MW Contribution:41.67
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
1.786
971599AH1-298 GEN
50/50
12.095
962771AG1-126 GEN
Solar/Wind Harmer
95.557
971347AH1-153 GEN
Solar/Wind Harmer
20.011
270071AF1-092 GEN
Solar/Wind Harmer
19.32
960681AF2-359 GEN
Solar/Wind Harmer
4.823
971771AH1-392 GEN
Solar/Wind Harmer
11.437
274775LINCOLN ;6U
Adder
7.877
274776LINCOLN ;7U
Adder
7.877
274777LINCOLN ;8U
Adder
7.877
971769AH1-391 GEN
Solar/Wind Harmer
12.687
274814UNIV PK N;0U
Adder
6.327
274807UNIV PK N;3U
Adder
6.313
274805UNIV PK N;1U
Adder
6.286
274811UNIV PK N;7U
Adder
6.272
274827FISK ;RP
Adder
9.699
972037AH1-567 GEN1
Adder
0.229
960591AF2-350 GEN
Solar/Wind Harmer
12.498
972227AH1-698 GEN1
Adder
3.26
274687WILL CNTY;4U
Adder
34.788
274687WILL CNTY;4U
Adder
34.788
274675JOLIET 29;7U
Adder
38.178
274675JOLIET 29;7U
Adder
36.814
274731ELWOOD EC;2P
Adder
20.424
274733ELWOOD EC;3P
Adder
20.424
274735ELWOOD EC;4P
Adder
20.424
274728ELWOOD EC;5P
Adder
20.425
970833AG2-524 GEN
Solar/Wind Harmer
10.846
970833AG2-524 GEN
Solar/Wind Harmer
5.045
274746AC1-111 G10
Adder
6.919
274744AC1-111 GEN8
Adder
6.919
24729505KEY G4
Adder
8.014
270536AF1-215 GEN2
Solar/Wind Harmer
5.608
944161AF1-084 GEN
Solar/Wind Harmer
2.725
958391AF2-133 GEN
Solar/Wind Harmer
11.042
971177AH1-047 GEN
Solar/Wind Harmer
7.132
276868AE1-113 GEN
Solar/Wind Harmer
12.314
276882AE2-255 GEN
Solar/Wind Harmer
4.105
971675AH1-338 GEN
Solar/Wind Harmer
21.857
971411AH1-196 GEN
Solar/Wind Harmer
18.212
274863CRW1-WTG
Solar/Wind Harmer
6.762
274864CRW2-WTG
Solar/Wind Harmer
6.762
274823ROCKFORD ;21
Adder
23.521
270054AF2-122 C O1
Solar/Wind Helper
1.549
971171AH1-044 GEN
Solar/Wind Harmer
0.774
24721805FLATG3
50/50
1.786
24721705FLATG2
50/50
32.751
24344105CKG2
50/50
10.346
962761AG1-125 GEN
Solar/Wind Harmer
95.557
970149AG2-104 GEN
Solar/Wind Harmer
118.013
970155AG2-107 GEN
Solar/Wind Harmer
41.667
970245AG2-165 GEN
Solar/Wind Harmer
23.936
972207SS24-0001
Solar/Wind Harmer
28.005
274773LINCOLN ;4U
Adder
7.877
274774LINCOLN ;5U
Adder
7.877
274723RIVER EC ;12
Adder
22.533
24639705ELKHART HY
Adder
0.193
276164X3-005 C
Solar/Wind Harmer
0.882
274751CRETE EC ;1U
Adder
6.135
274754CRETE EC ;4U
Adder
6.135
270505AE1-170 C O1
Solar/Wind Harmer
18.802
274812UNIV PK N;8U
Adder
6.272
276776AD2-060 GEN
Solar/Wind Harmer
0.528
274801UNIV PARK;4U
Adder
7.284
945111AF1-176 GEN
Solar/Wind Harmer
22.288
270063AE2-323 C
Solar/Wind Harmer
2.75
941551AE2-152 GEN
Solar/Wind Harmer
5.657
970373AG2-245 GEN
Solar/Wind Harmer
26.192
274676JOLIET 29;8U
Adder
38.177
274674JOLIET 9 ;6U
Adder
19.142
274732ELWOOD EC;7P
Adder
20.425
274871GR RIDGE ;2U
Solar/Wind Harmer
9.551
270449AD2-020 GEN
Solar/Wind Harmer
3.477
943021AE2-325 GEN
Solar/Wind Harmer
4.518
274745AC1-111 GEN9
Adder
6.919
270055AF2-134 C O1
Solar/Wind Harmer
3.738
276691AA1-018 GEN1
Solar/Wind Harmer
0.572
274682WAUKEGAN ;7U
Adder
22.07
274828WAUKEGAN ;BP
Adder
13.555
958381AF2-132 GEN
Solar/Wind Harmer
11.095
960751AF2-366 GEN
Solar/Wind Harmer
3.508
962781AG1-127 GEN
Solar/Wind Harmer
11.628
964861AG1-349 GEN
Solar/Wind Harmer
9.604
971917AH1-482 GEN
Solar/Wind Harmer
11.083
939401AE1-172 GEN
Solar/Wind Harmer
17.025
274872LEEDK;1U
Solar/Wind Harmer
10.03
276901AD2-066 C O1
Solar/Wind Harmer
4.283
965011AG1-365 GEN
Solar/Wind Harmer
12.175
971997AH1-543 GEN
Solar/Wind Harmer
19.145
276861AD2-134 GEN
Solar/Wind Harmer
2.169
274822ROCKFORD ;11
Adder
23.693
972235AH1-702 GEN1
Adder
3.039
274761LEE CO EC;2U
Adder
11.12
274766LEE CO EC;7U
Adder
10.989
970091AG2-072 GEN
Adder
5.216
957471AF2-041 GEN
Solar/Wind Harmer
1.161
959081AF2-199 GEN
Solar/Wind Harmer
0.387
971067AG2-660 GEN
Solar/Wind Harmer
0.09
24722005FLATG5
50/50
1.786
24721905FLATG4
50/50
32.751
970153AG2-106 GEN
Solar/Wind Harmer
41.667
970513AG2-328 GEN
Solar/Wind Harmer
23.936
970517AG2-330 GEN
Solar/Wind Harmer
21.709
970349AG2-230 GEN
Solar/Wind Harmer
20.011
270043AE2-236 GEN
Solar/Wind Harmer
7.153
274772LINCOLN ;3U
Adder
7.877
247643Z2-116 C
Solar/Wind Harmer
0.088
24642205MAYFLWER
Adder
0.8
274724RIVER EC ;11
Adder
22.273
970707AG2-453 GEN
Solar/Wind Harmer
35.145
972231SS25-0005
Solar/Wind Harmer
11.912
972181SS23-001
Solar/Wind Harmer
7.445
274752CRETE EC ;2U
Adder
6.135
274753CRETE EC ;3U
Adder
6.135
944531AF1-118 GEN
Solar/Wind Harmer
43.883
274826FISK ;BP
Adder
13.685
274802UNIV PARK;5U
Adder
7.287
276772AC2-154 GEN
Solar/Wind Harmer
3.485
276806AD2-047 C O1
Solar/Wind Harmer
13.37
970941AG2-585 GEN
Solar/Wind Harmer
15.623
972228AH1-698 GEN2
Adder
4.629
274800UNIV PARK;3U
Adder
7.284
972038AH1-567 GEN2
Adder
0.456
945111AF1-176 GEN
Solar/Wind Harmer
7.064
276897AD1-100 C
Solar/Wind Harmer
36.195
939351AE1-166 GEN
Solar/Wind Harmer
7.396
274676JOLIET 29;8U
Adder
36.814
274729ELWOOD EC;1P
Adder
20.424
274730ELWOOD EC;6P
Adder
20.425
274734ELWOOD EC;8P
Adder
20.425
274736ELWOOD EC;9P
Adder
20.425
276893AG1-478 C
Solar/Wind Harmer
0.519
970031AG2-029 GEN
Solar/Wind Harmer
37.211
943121AE2-341 GEN
Solar/Wind Harmer
18.593
943591AF1-030 GEN
Solar/Wind Harmer
12.395
270535AF1-215 GEN1
Solar/Wind Harmer
5.608
276694AA1-018 GEN2
Solar/Wind Harmer
7.75
274682WAUKEGAN ;7U
Adder
22.07
964401AG1-302 GEN
Solar/Wind Harmer
11.095
274872LEEDK;1U
Solar/Wind Harmer
0.312
276805AD2-038 GEN
Solar/Wind Harmer
6.257
959331AF2-224 GEN
Solar/Wind Harmer
12.175
965021AG1-366 GEN
Solar/Wind Harmer
2.831
24441205WTRV SLR C
Solar/Wind Harmer
0.164
276799AD1-013 GEN
Solar/Wind Harmer
2.685
946671AF1-331 GEN
Solar/Wind Harmer
0.508
274855GSG-6 ;RU
Solar/Wind Harmer
4.484
274850MENDOTA H;RU
Solar/Wind Harmer
3.118
276602WESTBROOK C
Solar/Wind Harmer
2.581
276863AD2-134 GEN
Solar/Wind Harmer
2.169
959141AF2-205 GEN
Solar/Wind Harmer
7.332
972236AH1-702 GEN2
Adder
2.642
247604X1-042
Adder
0.502
274760LEE CO EC;1U
Adder
11.12
274767LEE CO EC;8U
Adder
10.989
959091AF2-200 GEN
Solar/Wind Harmer
0.774
270102X2-052 ST
50/50
2.048
270100X2-052 CT1
50/50
1.887
270101X2-052 CT2
50/50
1.887
970321AG2-212 GEN
Solar/Wind Harmer
23.936
965681AG1-436 GEN
Solar/Wind Harmer
15.956
965791AG1-447 GEN
Solar/Wind Harmer
8.164
274770LINCOLN ;1U
Adder
7.877
274771LINCOLN ;2U
Adder
7.877
270526AF1-158 GEN
Solar/Wind Harmer
5.766
24441505OLIV SLR
Solar/Wind Harmer
0.17
270216AD2-079_GEN
Solar/Wind Harmer
0.767
957891AF2-083 GEN
Solar/Wind Harmer
4.225
960981AF2-389 GEN
Solar/Wind Harmer
1.893
274808UNIV PK N;4U
Adder
6.245
972259AH1-714 GEN
Adder
23.874
274803UNIV PARK;6U
Adder
7.287
274888KELLY CRK;1U
Solar/Wind Harmer
7.379
274887GEN-1.85
Solar/Wind Harmer
6.662
276843GEN-1.7
Solar/Wind Harmer
0.717
958011AF2-095 GEN
Solar/Wind Harmer
17.998
247620Y3-023
Adder
0.575
961051AF2-396 GEN
Solar/Wind Harmer
19.743
961051AF2-396 GEN
Solar/Wind Harmer
9.183
274674JOLIET 9 ;6U
Adder
19.142
274847GR RIDGE ;BU
Solar/Wind Harmer
6.282
971573AH1-285 GEN
Solar/Wind Harmer
10.624
274695ROCKY RD ;2P
Adder
13.688
274693ROCKY RD ;1P
Adder
13.554
274697ROCKY RD ;3P
Adder
3.718
274696ROCKY RD ;4P
Adder
14.011
958481AF2-142 GEN
Solar/Wind Harmer
18.422
274861TOP CROP ;1U
Solar/Wind Harmer
7.44
274862TOP CROP ;2U
Solar/Wind Harmer
6.212
274683WAUKEGAN ;8U
Adder
25.859
274683WAUKEGAN ;8U
Adder
21.798
962691AG1-118 GEN
Solar/Wind Harmer
36.735
970921AG2-575 GEN
Solar/Wind Harmer
12.227
970921AG2-575 GEN
Solar/Wind Harmer
2.844
958491AF2-143 GEN
Solar/Wind Harmer
18.296
970611AG2-400 GEN
Solar/Wind Harmer
12.175
942991AE2-321 GEN
Solar/Wind Harmer
12.173
274879MINONK ;1U
Solar/Wind Harmer
8.21
971333AH1-146 GEN
Solar/Wind Harmer
24.274
971335AH1-147 GEN
Solar/Wind Harmer
24.274
274764LEE CO EC;5U
Adder
11.146
274765LEE CO EC;6U
Adder
11.146
274762LEE CO EC;3U
Adder
11.12
274763LEE CO EC;4U
Adder
11.015
972267AH1-718 GEN
Adder
4.949
971341AH1-150 GEN
Solar/Wind Harmer
0.774
971343AH1-151 GEN
Solar/Wind Harmer
0.774
944201AF1-088_MTX
Adder
117.628
957141AF2-008_MTX
Adder
58.814
NYPJM->LTFIMP_NY
CLTF
3.802
LGEELTFEXP_LGEE->PJM
CLTF
5.477
WECLTFEXP_WEC->PJM
CLTF
4.602
AG2-052LTFEXP_AG2-052->PJM
LTF
0.284
AH1-155LTFEXP_AH1-155->PJM
LTF
0.425
CPLELTFEXP_CPLE->PJM
CLTF
3.161
CBM West 2LTFEXP_CBM-W2->PJM
CBM
119.296
LAGNLTFEXP_LAGN->PJM
CLTF
16.151
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.809
TVALTFEXP_TVA->PJM
CLTF
7.633
CBM West 1LTFEXP_CBM-W1->PJM
CBM
145.765
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.894
MECLTFEXP_MEC->PJM
CLTF
18.376
SIGELTFEXP_SIGE->PJM
CLTF
0.47

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AP_P2-3_MP-500-020_SRT-SL


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-3_MP-500-020_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.13 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:6039.56
MW Contribution:41.78
Bus #Bus NameTypeMW Contribution
24721805FLATG3
50/50
1.796
24721705FLATG2
50/50
32.926
24344105CKG2
50/50
10.407
962761AG1-125 GEN
Solar/Wind Harmer
95.82
970149AG2-104 GEN
Solar/Wind Harmer
118.338
970155AG2-107 GEN
Solar/Wind Harmer
41.782
970245AG2-165 GEN
Solar/Wind Harmer
24.08
972207SS24-0001
Solar/Wind Harmer
28.182
274773LINCOLN ;4U
Adder
7.927
274774LINCOLN ;5U
Adder
7.927
274723RIVER EC ;12
Adder
22.677
24639705ELKHART HY
Adder
0.194
276164X3-005 C
Solar/Wind Harmer
0.888
274751CRETE EC ;1U
Adder
6.174
274754CRETE EC ;4U
Adder
6.174
270505AE1-170 C O1
Solar/Wind Harmer
18.922
274812UNIV PK N;8U
Adder
6.313
276776AD2-060 GEN
Solar/Wind Harmer
0.532
274801UNIV PARK;4U
Adder
7.331
945111AF1-176 GEN
Solar/Wind Harmer
22.432
270063AE2-323 C
Solar/Wind Harmer
2.768
941551AE2-152 GEN
Solar/Wind Harmer
5.693
970373AG2-245 GEN
Solar/Wind Harmer
26.361
274676JOLIET 29;8U
Adder
38.424
274674JOLIET 9 ;6U
Adder
19.265
274732ELWOOD EC;7P
Adder
20.557
274871GR RIDGE ;2U
Solar/Wind Harmer
9.612
270449AD2-020 GEN
Solar/Wind Harmer
3.5
943021AE2-325 GEN
Solar/Wind Harmer
4.548
274745AC1-111 GEN9
Adder
6.964
270055AF2-134 C O1
Solar/Wind Harmer
3.763
276691AA1-018 GEN1
Solar/Wind Harmer
0.576
274682WAUKEGAN ;7U
Adder
22.214
274828WAUKEGAN ;BP
Adder
13.643
958381AF2-132 GEN
Solar/Wind Harmer
11.168
960751AF2-366 GEN
Solar/Wind Harmer
3.531
962781AG1-127 GEN
Solar/Wind Harmer
11.704
964861AG1-349 GEN
Solar/Wind Harmer
9.667
971917AH1-482 GEN
Solar/Wind Harmer
11.156
939401AE1-172 GEN
Solar/Wind Harmer
17.137
274872LEEDK;1U
Solar/Wind Harmer
10.096
276901AD2-066 C O1
Solar/Wind Harmer
4.312
965011AG1-365 GEN
Solar/Wind Harmer
12.256
971997AH1-543 GEN
Solar/Wind Harmer
19.271
276861AD2-134 GEN
Solar/Wind Harmer
2.183
274822ROCKFORD ;11
Adder
23.85
972235AH1-702 GEN1
Adder
3.059
274761LEE CO EC;2U
Adder
11.195
274766LEE CO EC;7U
Adder
11.063
970091AG2-072 GEN
Adder
5.259
957471AF2-041 GEN
Solar/Wind Harmer
1.169
959081AF2-199 GEN
Solar/Wind Harmer
0.39
971067AG2-660 GEN
Solar/Wind Harmer
0.091
24722005FLATG5
50/50
1.796
24721905FLATG4
50/50
32.926
970153AG2-106 GEN
Solar/Wind Harmer
41.782
970513AG2-328 GEN
Solar/Wind Harmer
24.08
970517AG2-330 GEN
Solar/Wind Harmer
21.84
970349AG2-230 GEN
Solar/Wind Harmer
20.131
270043AE2-236 GEN
Solar/Wind Harmer
7.197
274772LINCOLN ;3U
Adder
7.927
247643Z2-116 C
Solar/Wind Harmer
0.089
24642205MAYFLWER
Adder
0.805
274724RIVER EC ;11
Adder
22.416
970707AG2-453 GEN
Solar/Wind Harmer
35.371
972231SS25-0005
Solar/Wind Harmer
11.989
972181SS23-001
Solar/Wind Harmer
7.493
274752CRETE EC ;2U
Adder
6.174
274753CRETE EC ;3U
Adder
6.174
944531AF1-118 GEN
Solar/Wind Harmer
44.166
274826FISK ;BP
Adder
13.773
274802UNIV PARK;5U
Adder
7.334
276772AC2-154 GEN
Solar/Wind Harmer
3.508
276806AD2-047 C O1
Solar/Wind Harmer
13.456
970941AG2-585 GEN
Solar/Wind Harmer
15.724
972228AH1-698 GEN2
Adder
4.659
274800UNIV PARK;3U
Adder
7.331
972038AH1-567 GEN2
Adder
0.459
945111AF1-176 GEN
Solar/Wind Harmer
7.109
276897AD1-100 C
Solar/Wind Harmer
36.429
939351AE1-166 GEN
Solar/Wind Harmer
7.443
274676JOLIET 29;8U
Adder
37.052
274729ELWOOD EC;1P
Adder
20.557
274730ELWOOD EC;6P
Adder
20.557
274734ELWOOD EC;8P
Adder
20.557
274736ELWOOD EC;9P
Adder
20.557
276893AG1-478 C
Solar/Wind Harmer
0.522
970031AG2-029 GEN
Solar/Wind Harmer
37.453
943121AE2-341 GEN
Solar/Wind Harmer
18.714
943591AF1-030 GEN
Solar/Wind Harmer
12.476
270535AF1-215 GEN1
Solar/Wind Harmer
5.645
276694AA1-018 GEN2
Solar/Wind Harmer
7.801
274682WAUKEGAN ;7U
Adder
22.214
964401AG1-302 GEN
Solar/Wind Harmer
11.168
274872LEEDK;1U
Solar/Wind Harmer
0.314
276805AD2-038 GEN
Solar/Wind Harmer
6.299
959331AF2-224 GEN
Solar/Wind Harmer
12.256
965021AG1-366 GEN
Solar/Wind Harmer
2.85
24441205WTRV SLR C
Solar/Wind Harmer
0.165
276799AD1-013 GEN
Solar/Wind Harmer
2.703
946671AF1-331 GEN
Solar/Wind Harmer
0.512
274855GSG-6 ;RU
Solar/Wind Harmer
4.514
274850MENDOTA H;RU
Solar/Wind Harmer
3.139
276602WESTBROOK C
Solar/Wind Harmer
2.598
276863AD2-134 GEN
Solar/Wind Harmer
2.183
959141AF2-205 GEN
Solar/Wind Harmer
7.381
972236AH1-702 GEN2
Adder
2.66
247604X1-042
Adder
0.505
274760LEE CO EC;1U
Adder
11.195
274767LEE CO EC;8U
Adder
11.063
959091AF2-200 GEN
Solar/Wind Harmer
0.779
24721605FLATG1
50/50
1.796
971599AH1-298 GEN
50/50
12.165
962771AG1-126 GEN
Solar/Wind Harmer
95.82
971347AH1-153 GEN
Solar/Wind Harmer
20.131
270071AF1-092 GEN
Solar/Wind Harmer
19.441
960681AF2-359 GEN
Solar/Wind Harmer
4.853
971771AH1-392 GEN
Solar/Wind Harmer
11.51
274775LINCOLN ;6U
Adder
7.927
274776LINCOLN ;7U
Adder
7.927
274777LINCOLN ;8U
Adder
7.927
971769AH1-391 GEN
Solar/Wind Harmer
12.768
274814UNIV PK N;0U
Adder
6.368
274807UNIV PK N;3U
Adder
6.354
274805UNIV PK N;1U
Adder
6.326
274811UNIV PK N;7U
Adder
6.313
274827FISK ;RP
Adder
9.761
972037AH1-567 GEN1
Adder
0.23
960591AF2-350 GEN
Solar/Wind Harmer
12.579
972227AH1-698 GEN1
Adder
3.281
274687WILL CNTY;4U
Adder
35.013
274687WILL CNTY;4U
Adder
35.013
274675JOLIET 29;7U
Adder
38.424
274675JOLIET 29;7U
Adder
37.052
274731ELWOOD EC;2P
Adder
20.557
274733ELWOOD EC;3P
Adder
20.557
274735ELWOOD EC;4P
Adder
20.557
274728ELWOOD EC;5P
Adder
20.557
970833AG2-524 GEN
Solar/Wind Harmer
10.916
970833AG2-524 GEN
Solar/Wind Harmer
5.077
274746AC1-111 G10
Adder
6.964
274744AC1-111 GEN8
Adder
6.964
24729505KEY G4
Adder
8.066
270536AF1-215 GEN2
Solar/Wind Harmer
5.645
944161AF1-084 GEN
Solar/Wind Harmer
2.743
958391AF2-133 GEN
Solar/Wind Harmer
11.115
971177AH1-047 GEN
Solar/Wind Harmer
7.179
276868AE1-113 GEN
Solar/Wind Harmer
12.396
276882AE2-255 GEN
Solar/Wind Harmer
4.132
971675AH1-338 GEN
Solar/Wind Harmer
22.002
971411AH1-196 GEN
Solar/Wind Harmer
18.333
274863CRW1-WTG
Solar/Wind Harmer
6.807
274864CRW2-WTG
Solar/Wind Harmer
6.807
274823ROCKFORD ;21
Adder
23.677
270054AF2-122 C O1
Solar/Wind Helper
1.538
971171AH1-044 GEN
Solar/Wind Harmer
0.779
270102X2-052 ST
50/50
2.061
270100X2-052 CT1
50/50
1.899
270101X2-052 CT2
50/50
1.899
970321AG2-212 GEN
Solar/Wind Harmer
24.08
965681AG1-436 GEN
Solar/Wind Harmer
16.057
965791AG1-447 GEN
Solar/Wind Harmer
8.215
274770LINCOLN ;1U
Adder
7.927
274771LINCOLN ;2U
Adder
7.927
270526AF1-158 GEN
Solar/Wind Harmer
5.803
24441505OLIV SLR
Solar/Wind Harmer
0.171
270216AD2-079_GEN
Solar/Wind Harmer
0.772
957891AF2-083 GEN
Solar/Wind Harmer
4.252
274808UNIV PK N;4U
Adder
6.285
960981AF2-389 GEN
Solar/Wind Harmer
1.905
972259AH1-714 GEN
Adder
24.028
274803UNIV PARK;6U
Adder
7.334
274888KELLY CRK;1U
Solar/Wind Harmer
7.426
274887GEN-1.85
Solar/Wind Harmer
6.705
276843GEN-1.7
Solar/Wind Harmer
0.721
958011AF2-095 GEN
Solar/Wind Harmer
18.114
247620Y3-023
Adder
0.579
961051AF2-396 GEN
Solar/Wind Harmer
19.871
961051AF2-396 GEN
Solar/Wind Harmer
9.242
274674JOLIET 9 ;6U
Adder
19.265
274847GR RIDGE ;BU
Solar/Wind Harmer
6.323
971573AH1-285 GEN
Solar/Wind Harmer
10.693
274696ROCKY RD ;4P
Adder
14.103
274695ROCKY RD ;2P
Adder
13.778
274693ROCKY RD ;1P
Adder
13.642
274697ROCKY RD ;3P
Adder
3.743
958481AF2-142 GEN
Solar/Wind Harmer
18.542
274861TOP CROP ;1U
Solar/Wind Harmer
7.488
274862TOP CROP ;2U
Solar/Wind Harmer
6.253
274683WAUKEGAN ;8U
Adder
26.028
274683WAUKEGAN ;8U
Adder
21.94
962691AG1-118 GEN
Solar/Wind Harmer
36.976
970921AG2-575 GEN
Solar/Wind Harmer
12.308
970921AG2-575 GEN
Solar/Wind Harmer
2.862
958491AF2-143 GEN
Solar/Wind Harmer
18.417
970611AG2-400 GEN
Solar/Wind Harmer
12.256
942991AE2-321 GEN
Solar/Wind Harmer
12.253
274879MINONK ;1U
Solar/Wind Harmer
8.265
971333AH1-146 GEN
Solar/Wind Harmer
24.435
971335AH1-147 GEN
Solar/Wind Harmer
24.435
274764LEE CO EC;5U
Adder
11.221
274765LEE CO EC;6U
Adder
11.221
274762LEE CO EC;3U
Adder
11.195
274763LEE CO EC;4U
Adder
11.089
972267AH1-718 GEN
Adder
4.982
971341AH1-150 GEN
Solar/Wind Harmer
0.779
971343AH1-151 GEN
Solar/Wind Harmer
0.779
944201AF1-088_MTX
Adder
118.565
957141AF2-008_MTX
Adder
59.283
NYPJM->LTFIMP_NY
CLTF
3.759
LGEELTFEXP_LGEE->PJM
CLTF
5.533
WECLTFEXP_WEC->PJM
CLTF
4.633
AG2-052LTFEXP_AG2-052->PJM
LTF
0.285
AH1-155LTFEXP_AH1-155->PJM
LTF
0.428
CPLELTFEXP_CPLE->PJM
CLTF
3.242
CBM West 2LTFEXP_CBM-W2->PJM
CBM
120.367
LAGNLTFEXP_LAGN->PJM
CLTF
16.31
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.037
TVALTFEXP_TVA->PJM
CLTF
7.713
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.937
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.195
MECLTFEXP_MEC->PJM
CLTF
18.51
SIGELTFEXP_SIGE->PJM
CLTF
0.474

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AP_P2-3_MP-500-021_SRT-SL


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-3_MP-500-021_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.1 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:6038.29
MW Contribution:41.77
Bus #Bus NameTypeMW Contribution
24721805FLATG3
50/50
1.795
24721705FLATG2
50/50
32.911
24344105CKG2
50/50
10.402
962761AG1-125 GEN
Solar/Wind Harmer
95.798
970149AG2-104 GEN
Solar/Wind Harmer
118.311
970155AG2-107 GEN
Solar/Wind Harmer
41.773
970245AG2-165 GEN
Solar/Wind Harmer
24.069
972207SS24-0001
Solar/Wind Harmer
28.169
274773LINCOLN ;4U
Adder
7.923
274774LINCOLN ;5U
Adder
7.923
274723RIVER EC ;12
Adder
22.666
24639705ELKHART HY
Adder
0.194
276164X3-005 C
Solar/Wind Harmer
0.887
274751CRETE EC ;1U
Adder
6.171
274754CRETE EC ;4U
Adder
6.171
270505AE1-170 C O1
Solar/Wind Harmer
18.913
274812UNIV PK N;8U
Adder
6.309
276776AD2-060 GEN
Solar/Wind Harmer
0.532
274801UNIV PARK;4U
Adder
7.327
945111AF1-176 GEN
Solar/Wind Harmer
22.421
270063AE2-323 C
Solar/Wind Harmer
2.766
941551AE2-152 GEN
Solar/Wind Harmer
5.69
970373AG2-245 GEN
Solar/Wind Harmer
26.348
274676JOLIET 29;8U
Adder
38.405
274674JOLIET 9 ;6U
Adder
19.256
274732ELWOOD EC;7P
Adder
20.547
274871GR RIDGE ;2U
Solar/Wind Harmer
9.608
270102X2-052 ST
50/50
2.06
270100X2-052 CT1
50/50
1.898
270101X2-052 CT2
50/50
1.898
24721605FLATG1
50/50
1.795
971599AH1-298 GEN
50/50
12.16
962771AG1-126 GEN
Solar/Wind Harmer
95.798
971347AH1-153 GEN
Solar/Wind Harmer
20.122
270071AF1-092 GEN
Solar/Wind Harmer
19.432
960681AF2-359 GEN
Solar/Wind Harmer
4.851
971771AH1-392 GEN
Solar/Wind Harmer
11.504
274775LINCOLN ;6U
Adder
7.923
274776LINCOLN ;7U
Adder
7.923
274777LINCOLN ;8U
Adder
7.923
971769AH1-391 GEN
Solar/Wind Harmer
12.761
274814UNIV PK N;0U
Adder
6.365
274807UNIV PK N;3U
Adder
6.351
274805UNIV PK N;1U
Adder
6.323
274811UNIV PK N;7U
Adder
6.309
274827FISK ;RP
Adder
9.756
972037AH1-567 GEN1
Adder
0.23
960591AF2-350 GEN
Solar/Wind Harmer
12.573
972227AH1-698 GEN1
Adder
3.279
274687WILL CNTY;4U
Adder
34.996
274687WILL CNTY;4U
Adder
34.996
274675JOLIET 29;7U
Adder
38.406
274675JOLIET 29;7U
Adder
37.034
274731ELWOOD EC;2P
Adder
20.547
274733ELWOOD EC;3P
Adder
20.547
274735ELWOOD EC;4P
Adder
20.547
274728ELWOOD EC;5P
Adder
20.547
970833AG2-524 GEN
Solar/Wind Harmer
10.911
970833AG2-524 GEN
Solar/Wind Harmer
5.075
274746AC1-111 G10
Adder
6.961
274744AC1-111 GEN8
Adder
6.961
24729505KEY G4
Adder
8.062
270536AF1-215 GEN2
Solar/Wind Harmer
5.642
944161AF1-084 GEN
Solar/Wind Harmer
2.742
958391AF2-133 GEN
Solar/Wind Harmer
11.109
971177AH1-047 GEN
Solar/Wind Harmer
7.175
276868AE1-113 GEN
Solar/Wind Harmer
12.39
276882AE2-255 GEN
Solar/Wind Harmer
4.13
971675AH1-338 GEN
Solar/Wind Harmer
21.991
971411AH1-196 GEN
Solar/Wind Harmer
18.324
274863CRW1-WTG
Solar/Wind Harmer
6.804
274864CRW2-WTG
Solar/Wind Harmer
6.804
274823ROCKFORD ;21
Adder
23.666
270054AF2-122 C O1
Solar/Wind Helper
1.539
971171AH1-044 GEN
Solar/Wind Harmer
0.779
24722005FLATG5
50/50
1.795
24721905FLATG4
50/50
32.911
970153AG2-106 GEN
Solar/Wind Harmer
41.773
970513AG2-328 GEN
Solar/Wind Harmer
24.069
970517AG2-330 GEN
Solar/Wind Harmer
21.83
970349AG2-230 GEN
Solar/Wind Harmer
20.122
270043AE2-236 GEN
Solar/Wind Harmer
7.194
274772LINCOLN ;3U
Adder
7.923
247643Z2-116 C
Solar/Wind Harmer
0.089
24642205MAYFLWER
Adder
0.804
274724RIVER EC ;11
Adder
22.405
970707AG2-453 GEN
Solar/Wind Harmer
35.353
972231SS25-0005
Solar/Wind Harmer
11.983
972181SS23-001
Solar/Wind Harmer
7.489
274752CRETE EC ;2U
Adder
6.171
274753CRETE EC ;3U
Adder
6.171
944531AF1-118 GEN
Solar/Wind Harmer
44.143
274826FISK ;BP
Adder
13.766
274802UNIV PARK;5U
Adder
7.33
276772AC2-154 GEN
Solar/Wind Harmer
3.506
276806AD2-047 C O1
Solar/Wind Harmer
13.45
970941AG2-585 GEN
Solar/Wind Harmer
15.716
972228AH1-698 GEN2
Adder
4.657
274800UNIV PARK;3U
Adder
7.327
972038AH1-567 GEN2
Adder
0.459
945111AF1-176 GEN
Solar/Wind Harmer
7.106
276897AD1-100 C
Solar/Wind Harmer
36.411
939351AE1-166 GEN
Solar/Wind Harmer
7.44
274676JOLIET 29;8U
Adder
37.034
274729ELWOOD EC;1P
Adder
20.547
274730ELWOOD EC;6P
Adder
20.547
274734ELWOOD EC;8P
Adder
20.547
274736ELWOOD EC;9P
Adder
20.547
276893AG1-478 C
Solar/Wind Harmer
0.522
970031AG2-029 GEN
Solar/Wind Harmer
37.434
943121AE2-341 GEN
Solar/Wind Harmer
18.704
943591AF1-030 GEN
Solar/Wind Harmer
12.47
270535AF1-215 GEN1
Solar/Wind Harmer
5.642
276694AA1-018 GEN2
Solar/Wind Harmer
7.797
274682WAUKEGAN ;7U
Adder
22.204
964401AG1-302 GEN
Solar/Wind Harmer
11.162
274872LEEDK;1U
Solar/Wind Harmer
0.314
276805AD2-038 GEN
Solar/Wind Harmer
6.295
959331AF2-224 GEN
Solar/Wind Harmer
12.25
965021AG1-366 GEN
Solar/Wind Harmer
2.849
24441205WTRV SLR C
Solar/Wind Harmer
0.165
276799AD1-013 GEN
Solar/Wind Harmer
2.702
946671AF1-331 GEN
Solar/Wind Harmer
0.512
274855GSG-6 ;RU
Solar/Wind Harmer
4.512
274850MENDOTA H;RU
Solar/Wind Harmer
3.137
276602WESTBROOK C
Solar/Wind Harmer
2.597
276863AD2-134 GEN
Solar/Wind Harmer
2.182
959141AF2-205 GEN
Solar/Wind Harmer
7.377
972236AH1-702 GEN2
Adder
2.659
247604X1-042
Adder
0.505
274760LEE CO EC;1U
Adder
11.189
274767LEE CO EC;8U
Adder
11.057
959091AF2-200 GEN
Solar/Wind Harmer
0.779
970321AG2-212 GEN
Solar/Wind Harmer
24.069
965681AG1-436 GEN
Solar/Wind Harmer
16.049
965791AG1-447 GEN
Solar/Wind Harmer
8.211
274770LINCOLN ;1U
Adder
7.923
274771LINCOLN ;2U
Adder
7.923
270526AF1-158 GEN
Solar/Wind Harmer
5.8
24441505OLIV SLR
Solar/Wind Harmer
0.171
270216AD2-079_GEN
Solar/Wind Harmer
0.772
957891AF2-083 GEN
Solar/Wind Harmer
4.25
274808UNIV PK N;4U
Adder
6.282
960981AF2-389 GEN
Solar/Wind Harmer
1.904
972259AH1-714 GEN
Adder
24.016
274803UNIV PARK;6U
Adder
7.33
274888KELLY CRK;1U
Solar/Wind Harmer
7.423
274887GEN-1.85
Solar/Wind Harmer
6.702
276843GEN-1.7
Solar/Wind Harmer
0.721
958011AF2-095 GEN
Solar/Wind Harmer
18.105
247620Y3-023
Adder
0.579
961051AF2-396 GEN
Solar/Wind Harmer
19.861
961051AF2-396 GEN
Solar/Wind Harmer
9.238
274674JOLIET 9 ;6U
Adder
19.256
274847GR RIDGE ;BU
Solar/Wind Harmer
6.32
971573AH1-285 GEN
Solar/Wind Harmer
10.688
274696ROCKY RD ;4P
Adder
14.096
274695ROCKY RD ;2P
Adder
13.771
274693ROCKY RD ;1P
Adder
13.635
274697ROCKY RD ;3P
Adder
3.741
958481AF2-142 GEN
Solar/Wind Harmer
18.533
274861TOP CROP ;1U
Solar/Wind Harmer
7.485
274862TOP CROP ;2U
Solar/Wind Harmer
6.25
274683WAUKEGAN ;8U
Adder
26.015
274683WAUKEGAN ;8U
Adder
21.929
962691AG1-118 GEN
Solar/Wind Harmer
36.958
970921AG2-575 GEN
Solar/Wind Harmer
12.301
970921AG2-575 GEN
Solar/Wind Harmer
2.861
958491AF2-143 GEN
Solar/Wind Harmer
18.408
970611AG2-400 GEN
Solar/Wind Harmer
12.25
942991AE2-321 GEN
Solar/Wind Harmer
12.247
274879MINONK ;1U
Solar/Wind Harmer
8.261
971333AH1-146 GEN
Solar/Wind Harmer
24.423
971335AH1-147 GEN
Solar/Wind Harmer
24.423
274764LEE CO EC;5U
Adder
11.215
274765LEE CO EC;6U
Adder
11.215
274762LEE CO EC;3U
Adder
11.189
274763LEE CO EC;4U
Adder
11.084
972267AH1-718 GEN
Adder
4.98
971341AH1-150 GEN
Solar/Wind Harmer
0.779
971343AH1-151 GEN
Solar/Wind Harmer
0.779
270449AD2-020 GEN
Solar/Wind Harmer
3.498
943021AE2-325 GEN
Solar/Wind Harmer
4.545
274745AC1-111 GEN9
Adder
6.961
270055AF2-134 C O1
Solar/Wind Harmer
3.761
276691AA1-018 GEN1
Solar/Wind Harmer
0.575
274682WAUKEGAN ;7U
Adder
22.204
274828WAUKEGAN ;BP
Adder
13.637
958381AF2-132 GEN
Solar/Wind Harmer
11.162
960751AF2-366 GEN
Solar/Wind Harmer
3.529
962781AG1-127 GEN
Solar/Wind Harmer
11.699
964861AG1-349 GEN
Solar/Wind Harmer
9.662
971917AH1-482 GEN
Solar/Wind Harmer
11.15
939401AE1-172 GEN
Solar/Wind Harmer
17.129
274872LEEDK;1U
Solar/Wind Harmer
10.091
276901AD2-066 C O1
Solar/Wind Harmer
4.309
965011AG1-365 GEN
Solar/Wind Harmer
12.25
971997AH1-543 GEN
Solar/Wind Harmer
19.262
276861AD2-134 GEN
Solar/Wind Harmer
2.182
274822ROCKFORD ;11
Adder
23.838
972235AH1-702 GEN1
Adder
3.057
274761LEE CO EC;2U
Adder
11.189
274766LEE CO EC;7U
Adder
11.057
970091AG2-072 GEN
Adder
5.255
957471AF2-041 GEN
Solar/Wind Harmer
1.168
959081AF2-199 GEN
Solar/Wind Harmer
0.389
971067AG2-660 GEN
Solar/Wind Harmer
0.091
944201AF1-088_MTX
Adder
118.492
957141AF2-008_MTX
Adder
59.246
NYPJM->LTFIMP_NY
CLTF
3.757
LGEELTFEXP_LGEE->PJM
CLTF
5.528
WECLTFEXP_WEC->PJM
CLTF
4.631
AG2-052LTFEXP_AG2-052->PJM
LTF
0.285
AH1-155LTFEXP_AH1-155->PJM
LTF
0.428
CPLELTFEXP_CPLE->PJM
CLTF
3.241
CBM West 2LTFEXP_CBM-W2->PJM
CBM
120.295
LAGNLTFEXP_LAGN->PJM
CLTF
16.301
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.03
TVALTFEXP_TVA->PJM
CLTF
7.708
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.85
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.176
MECLTFEXP_MEC->PJM
CLTF
18.5
SIGELTFEXP_SIGE->PJM
CLTF
0.474

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AEP_P4_#37_05MOUNTN 765_B1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.09 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:6037.73
MW Contribution:41.77
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
1.795
971599AH1-298 GEN
50/50
12.157
962771AG1-126 GEN
Solar/Wind Harmer
95.789
971347AH1-153 GEN
Solar/Wind Harmer
20.118
270071AF1-092 GEN
Solar/Wind Harmer
19.428
960681AF2-359 GEN
Solar/Wind Harmer
4.85
971771AH1-392 GEN
Solar/Wind Harmer
11.502
274775LINCOLN ;6U
Adder
7.921
274776LINCOLN ;7U
Adder
7.921
274777LINCOLN ;8U
Adder
7.921
971769AH1-391 GEN
Solar/Wind Harmer
12.759
274814UNIV PK N;0U
Adder
6.363
274807UNIV PK N;3U
Adder
6.35
274805UNIV PK N;1U
Adder
6.322
274811UNIV PK N;7U
Adder
6.308
274827FISK ;RP
Adder
9.754
972037AH1-567 GEN1
Adder
0.23
960591AF2-350 GEN
Solar/Wind Harmer
12.57
972227AH1-698 GEN1
Adder
3.278
274687WILL CNTY;4U
Adder
34.988
274687WILL CNTY;4U
Adder
34.988
274675JOLIET 29;7U
Adder
38.397
274675JOLIET 29;7U
Adder
37.026
274731ELWOOD EC;2P
Adder
20.542
274733ELWOOD EC;3P
Adder
20.542
274735ELWOOD EC;4P
Adder
20.542
274728ELWOOD EC;5P
Adder
20.542
970833AG2-524 GEN
Solar/Wind Harmer
10.908
970833AG2-524 GEN
Solar/Wind Harmer
5.074
274746AC1-111 G10
Adder
6.959
274744AC1-111 GEN8
Adder
6.959
24729505KEY G4
Adder
8.06
270536AF1-215 GEN2
Solar/Wind Harmer
5.641
944161AF1-084 GEN
Solar/Wind Harmer
2.741
958391AF2-133 GEN
Solar/Wind Harmer
11.107
971177AH1-047 GEN
Solar/Wind Harmer
7.174
276868AE1-113 GEN
Solar/Wind Harmer
12.387
276882AE2-255 GEN
Solar/Wind Harmer
4.129
971675AH1-338 GEN
Solar/Wind Harmer
21.986
971411AH1-196 GEN
Solar/Wind Harmer
18.32
274863CRW1-WTG
Solar/Wind Harmer
6.802
274864CRW2-WTG
Solar/Wind Harmer
6.802
274823ROCKFORD ;21
Adder
23.66
270054AF2-122 C O1
Solar/Wind Helper
1.539
971171AH1-044 GEN
Solar/Wind Harmer
0.778
24722005FLATG5
50/50
1.795
24721905FLATG4
50/50
32.905
970153AG2-106 GEN
Solar/Wind Harmer
41.768
970513AG2-328 GEN
Solar/Wind Harmer
24.064
970517AG2-330 GEN
Solar/Wind Harmer
21.825
970349AG2-230 GEN
Solar/Wind Harmer
20.118
270043AE2-236 GEN
Solar/Wind Harmer
7.192
274772LINCOLN ;3U
Adder
7.921
247643Z2-116 C
Solar/Wind Harmer
0.089
24642205MAYFLWER
Adder
0.804
274724RIVER EC ;11
Adder
22.4
970707AG2-453 GEN
Solar/Wind Harmer
35.346
972231SS25-0005
Solar/Wind Harmer
11.98
972181SS23-001
Solar/Wind Harmer
7.488
274752CRETE EC ;2U
Adder
6.17
274753CRETE EC ;3U
Adder
6.17
944531AF1-118 GEN
Solar/Wind Harmer
44.133
274826FISK ;BP
Adder
13.763
274802UNIV PARK;5U
Adder
7.329
276772AC2-154 GEN
Solar/Wind Harmer
3.505
276806AD2-047 C O1
Solar/Wind Harmer
13.447
970941AG2-585 GEN
Solar/Wind Harmer
15.712
972228AH1-698 GEN2
Adder
4.656
274800UNIV PARK;3U
Adder
7.326
972038AH1-567 GEN2
Adder
0.459
945111AF1-176 GEN
Solar/Wind Harmer
7.104
276897AD1-100 C
Solar/Wind Harmer
36.403
939351AE1-166 GEN
Solar/Wind Harmer
7.438
274676JOLIET 29;8U
Adder
37.026
274729ELWOOD EC;1P
Adder
20.542
274730ELWOOD EC;6P
Adder
20.542
274734ELWOOD EC;8P
Adder
20.542
274736ELWOOD EC;9P
Adder
20.542
276893AG1-478 C
Solar/Wind Harmer
0.522
970031AG2-029 GEN
Solar/Wind Harmer
37.426
943121AE2-341 GEN
Solar/Wind Harmer
18.7
943591AF1-030 GEN
Solar/Wind Harmer
12.467
270535AF1-215 GEN1
Solar/Wind Harmer
5.641
276694AA1-018 GEN2
Solar/Wind Harmer
7.795
274682WAUKEGAN ;7U
Adder
22.199
964401AG1-302 GEN
Solar/Wind Harmer
11.16
274872LEEDK;1U
Solar/Wind Harmer
0.314
276805AD2-038 GEN
Solar/Wind Harmer
6.294
959331AF2-224 GEN
Solar/Wind Harmer
12.247
965021AG1-366 GEN
Solar/Wind Harmer
2.848
24441205WTRV SLR C
Solar/Wind Harmer
0.165
276799AD1-013 GEN
Solar/Wind Harmer
2.701
946671AF1-331 GEN
Solar/Wind Harmer
0.511
274855GSG-6 ;RU
Solar/Wind Harmer
4.511
274850MENDOTA H;RU
Solar/Wind Harmer
3.137
276602WESTBROOK C
Solar/Wind Harmer
2.596
276863AD2-134 GEN
Solar/Wind Harmer
2.181
959141AF2-205 GEN
Solar/Wind Harmer
7.375
972236AH1-702 GEN2
Adder
2.658
247604X1-042
Adder
0.505
274760LEE CO EC;1U
Adder
11.187
274767LEE CO EC;8U
Adder
11.055
959091AF2-200 GEN
Solar/Wind Harmer
0.778
270102X2-052 ST
50/50
2.06
270100X2-052 CT1
50/50
1.898
270101X2-052 CT2
50/50
1.898
970321AG2-212 GEN
Solar/Wind Harmer
24.064
965681AG1-436 GEN
Solar/Wind Harmer
16.046
965791AG1-447 GEN
Solar/Wind Harmer
8.21
274770LINCOLN ;1U
Adder
7.921
274771LINCOLN ;2U
Adder
7.921
270526AF1-158 GEN
Solar/Wind Harmer
5.799
24441505OLIV SLR
Solar/Wind Harmer
0.171
270216AD2-079_GEN
Solar/Wind Harmer
0.772
957891AF2-083 GEN
Solar/Wind Harmer
4.249
960981AF2-389 GEN
Solar/Wind Harmer
1.904
274808UNIV PK N;4U
Adder
6.281
972259AH1-714 GEN
Adder
24.011
274803UNIV PARK;6U
Adder
7.329
274888KELLY CRK;1U
Solar/Wind Harmer
7.421
274887GEN-1.85
Solar/Wind Harmer
6.7
276843GEN-1.7
Solar/Wind Harmer
0.721
958011AF2-095 GEN
Solar/Wind Harmer
18.101
247620Y3-023
Adder
0.578
961051AF2-396 GEN
Solar/Wind Harmer
19.857
961051AF2-396 GEN
Solar/Wind Harmer
9.236
274674JOLIET 9 ;6U
Adder
19.252
274847GR RIDGE ;BU
Solar/Wind Harmer
6.319
971573AH1-285 GEN
Solar/Wind Harmer
10.686
274696ROCKY RD ;4P
Adder
14.093
274695ROCKY RD ;2P
Adder
13.768
274693ROCKY RD ;1P
Adder
13.632
274697ROCKY RD ;3P
Adder
3.74
958481AF2-142 GEN
Solar/Wind Harmer
18.529
274861TOP CROP ;1U
Solar/Wind Harmer
7.483
274862TOP CROP ;2U
Solar/Wind Harmer
6.248
274683WAUKEGAN ;8U
Adder
26.009
274683WAUKEGAN ;8U
Adder
21.925
962691AG1-118 GEN
Solar/Wind Harmer
36.95
970921AG2-575 GEN
Solar/Wind Harmer
12.299
970921AG2-575 GEN
Solar/Wind Harmer
2.86
958491AF2-143 GEN
Solar/Wind Harmer
18.404
970611AG2-400 GEN
Solar/Wind Harmer
12.247
942991AE2-321 GEN
Solar/Wind Harmer
12.245
274879MINONK ;1U
Solar/Wind Harmer
8.259
971333AH1-146 GEN
Solar/Wind Harmer
24.417
971335AH1-147 GEN
Solar/Wind Harmer
24.417
274764LEE CO EC;5U
Adder
11.213
274765LEE CO EC;6U
Adder
11.213
274762LEE CO EC;3U
Adder
11.187
274763LEE CO EC;4U
Adder
11.081
972267AH1-718 GEN
Adder
4.979
971341AH1-150 GEN
Solar/Wind Harmer
0.778
971343AH1-151 GEN
Solar/Wind Harmer
0.778
24721805FLATG3
50/50
1.795
24721705FLATG2
50/50
32.905
24344105CKG2
50/50
10.4
962761AG1-125 GEN
Solar/Wind Harmer
95.789
970149AG2-104 GEN
Solar/Wind Harmer
118.299
970155AG2-107 GEN
Solar/Wind Harmer
41.768
970245AG2-165 GEN
Solar/Wind Harmer
24.064
972207SS24-0001
Solar/Wind Harmer
28.163
274773LINCOLN ;4U
Adder
7.921
274774LINCOLN ;5U
Adder
7.921
274723RIVER EC ;12
Adder
22.661
24639705ELKHART HY
Adder
0.194
276164X3-005 C
Solar/Wind Harmer
0.887
274751CRETE EC ;1U
Adder
6.17
274754CRETE EC ;4U
Adder
6.17
270505AE1-170 C O1
Solar/Wind Harmer
18.909
274812UNIV PK N;8U
Adder
6.308
276776AD2-060 GEN
Solar/Wind Harmer
0.531
274801UNIV PARK;4U
Adder
7.326
945111AF1-176 GEN
Solar/Wind Harmer
22.416
270063AE2-323 C
Solar/Wind Harmer
2.766
941551AE2-152 GEN
Solar/Wind Harmer
5.689
970373AG2-245 GEN
Solar/Wind Harmer
26.342
274676JOLIET 29;8U
Adder
38.397
274674JOLIET 9 ;6U
Adder
19.252
274732ELWOOD EC;7P
Adder
20.542
274871GR RIDGE ;2U
Solar/Wind Harmer
9.606
270449AD2-020 GEN
Solar/Wind Harmer
3.497
943021AE2-325 GEN
Solar/Wind Harmer
4.544
274745AC1-111 GEN9
Adder
6.959
270055AF2-134 C O1
Solar/Wind Harmer
3.76
276691AA1-018 GEN1
Solar/Wind Harmer
0.575
274682WAUKEGAN ;7U
Adder
22.199
274828WAUKEGAN ;BP
Adder
13.634
958381AF2-132 GEN
Solar/Wind Harmer
11.16
960751AF2-366 GEN
Solar/Wind Harmer
3.529
962781AG1-127 GEN
Solar/Wind Harmer
11.696
964861AG1-349 GEN
Solar/Wind Harmer
9.66
971917AH1-482 GEN
Solar/Wind Harmer
11.147
939401AE1-172 GEN
Solar/Wind Harmer
17.125
274872LEEDK;1U
Solar/Wind Harmer
10.089
276901AD2-066 C O1
Solar/Wind Harmer
4.308
965011AG1-365 GEN
Solar/Wind Harmer
12.247
971997AH1-543 GEN
Solar/Wind Harmer
19.257
276861AD2-134 GEN
Solar/Wind Harmer
2.181
274822ROCKFORD ;11
Adder
23.833
972235AH1-702 GEN1
Adder
3.057
274761LEE CO EC;2U
Adder
11.187
274766LEE CO EC;7U
Adder
11.055
970091AG2-072 GEN
Adder
5.254
957471AF2-041 GEN
Solar/Wind Harmer
1.168
959081AF2-199 GEN
Solar/Wind Harmer
0.389
971067AG2-660 GEN
Solar/Wind Harmer
0.091
944201AF1-088_MTX
Adder
118.46
957141AF2-008_MTX
Adder
59.23
NYPJM->LTFIMP_NY
CLTF
3.756
LGEELTFEXP_LGEE->PJM
CLTF
5.526
WECLTFEXP_WEC->PJM
CLTF
4.63
AG2-052LTFEXP_AG2-052->PJM
LTF
0.285
AH1-155LTFEXP_AH1-155->PJM
LTF
0.428
CPLELTFEXP_CPLE->PJM
CLTF
3.24
CBM West 2LTFEXP_CBM-W2->PJM
CBM
120.262
LAGNLTFEXP_LAGN->PJM
CLTF
16.296
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.027
TVALTFEXP_TVA->PJM
CLTF
7.706
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.812
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.167
MECLTFEXP_MEC->PJM
CLTF
18.496
SIGELTFEXP_SIGE->PJM
CLTF
0.474

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AP_P1-3_MP-765-501T_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.64 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5971.43
MW Contribution:51.58
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
1.795
971599AH1-298 GEN
50/50
12.157
962771AG1-126 GEN
Solar/Wind Harmer
80.781
971347AH1-153 GEN
Solar/Wind Harmer
14.036
270071AF1-092 GEN
Solar/Wind Harmer
17.319
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971771AH1-392 GEN
Solar/Wind Harmer
8.916
274775LINCOLN ;6U
Adder
10.782
274776LINCOLN ;7U
Adder
10.782
274777LINCOLN ;8U
Adder
10.782
971769AH1-391 GEN
Solar/Wind Harmer
9.94
971619AH1-309 GEN
Solar/Wind Harmer
3.958
274814UNIV PK N;0U
Adder
6.363
274807UNIV PK N;3U
Adder
6.35
274805UNIV PK N;1U
Adder
6.322
274811UNIV PK N;7U
Adder
6.308
274827FISK ;RP
Adder
9.754
972037AH1-567 GEN1
Adder
0.23
960591AF2-350 GEN
Solar/Wind Harmer
8.77
972227AH1-698 GEN1
Adder
3.278
274687WILL CNTY;4U
Adder
34.988
274687WILL CNTY;4U
Adder
34.988
274675JOLIET 29;7U
Adder
38.397
274675JOLIET 29;7U
Adder
37.026
274731ELWOOD EC;2P
Adder
20.542
274733ELWOOD EC;3P
Adder
20.542
274735ELWOOD EC;4P
Adder
20.542
274728ELWOOD EC;5P
Adder
20.542
970833AG2-524 GEN
Solar/Wind Harmer
9.589
970833AG2-524 GEN
Solar/Wind Harmer
6.393
274746AC1-111 G10
Adder
6.959
274744AC1-111 GEN8
Adder
6.959
24729505KEY G4
Adder
8.06
270536AF1-215 GEN2
Solar/Wind Harmer
0.011
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971177AH1-047 GEN
Solar/Wind Harmer
5.267
276868AE1-113 GEN
Solar/Wind Harmer
1.713
276882AE2-255 GEN
Solar/Wind Harmer
0.998
971675AH1-338 GEN
Solar/Wind Harmer
3.323
971411AH1-196 GEN
Solar/Wind Harmer
12.781
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
971171AH1-044 GEN
Solar/Wind Harmer
16.979
971611AH1-305 GEN
Solar/Wind Harmer
5.045
274823ROCKFORD ;21
Adder
23.66
276612AE2-035 GEN
Solar/Wind Harmer
0.002
926823AC1-168 GEN
Solar/Wind Harmer
1.432
970169AG2-114 GEN
Solar/Wind Harmer
8.423
971681AH1-341 GEN
Solar/Wind Harmer
13.539
961011AF2-392 GEN
Solar/Wind Harmer
4.902
957751AF2-069 GEN
Solar/Wind Harmer
0.275
24690905MDL-1G C
Solar/Wind Harmer
0.003
24721805FLATG3
50/50
1.795
24721705FLATG2
50/50
32.905
24344105CKG2
50/50
10.4
962761AG1-125 GEN
Solar/Wind Harmer
80.781
970149AG2-104 GEN
Solar/Wind Harmer
87.246
970155AG2-107 GEN
Solar/Wind Harmer
51.584
970245AG2-165 GEN
Solar/Wind Harmer
4.074
274773LINCOLN ;4U
Adder
10.782
274774LINCOLN ;5U
Adder
10.782
274723RIVER EC ;12
Adder
22.661
24639705ELKHART HY
Adder
0.194
276164X3-005 C
Solar/Wind Harmer
0
274751CRETE EC ;1U
Adder
10.401
274754CRETE EC ;4U
Adder
10.401
270505AE1-170 C O1
Solar/Wind Harmer
9.235
274812UNIV PK N;8U
Adder
6.308
276776AD2-060 GEN
Solar/Wind Harmer
0.916
274801UNIV PARK;4U
Adder
7.326
945111AF1-176 GEN
Solar/Wind Harmer
15.639
270063AE2-323 C
Solar/Wind Harmer
0.007
941551AE2-152 GEN
Solar/Wind Harmer
0.001
970373AG2-245 GEN
Solar/Wind Harmer
18.378
274676JOLIET 29;8U
Adder
38.397
274674JOLIET 9 ;6U
Adder
19.252
274732ELWOOD EC;7P
Adder
20.542
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
4.544
274745AC1-111 GEN9
Adder
6.959
270055AF2-134 C O1
Solar/Wind Harmer
0.007
276691AA1-018 GEN1
Solar/Wind Harmer
1.044
274682WAUKEGAN ;7U
Adder
22.199
274828WAUKEGAN ;BP
Adder
13.634
958381AF2-132 GEN
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
8.166
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.147
939401AE1-172 GEN
Solar/Wind Harmer
6.413
274872LEEDK;1U
Solar/Wind Harmer
0.005
276901AD2-066 C O1
Solar/Wind Harmer
0.008
965011AG1-365 GEN
Solar/Wind Harmer
8.544
971997AH1-543 GEN
Solar/Wind Harmer
4.478
276861AD2-134 GEN
Solar/Wind Harmer
0.153
957471AF2-041 GEN
Solar/Wind Harmer
25.469
959081AF2-199 GEN
Solar/Wind Harmer
8.49
971067AG2-660 GEN
Solar/Wind Harmer
2.83
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
10.593
274822ROCKFORD ;11
Adder
23.833
972235AH1-702 GEN1
Adder
3.057
970819AG2-516 GEN
Solar/Wind Harmer
10.134
971475AH1-234 GEN
Solar/Wind Harmer
4.092
970569AG2-363 GEN
Solar/Wind Harmer
25.271
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
11.187
274766LEE CO EC;7U
Adder
11.055
276158O29GEN2
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
2.438
274877BISHOP HL;1U
Solar/Wind Harmer
0.279
24791305MDL-5G
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0.003
939741AE1-205 GEN
Solar/Wind Harmer
11.552
958861AF2-177 GEN
Solar/Wind Harmer
3.551
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
972175AH1-670 GEN
Solar/Wind Harmer
6.643
945371AF1-202 GEN
Solar/Wind Harmer
0.001
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
3.078
963741AG1-226 GEN
Solar/Wind Harmer
18.629
276615X2-022 GEN
Solar/Wind Harmer
0.082
970291AG2-192 GEN
Solar/Wind Harmer
1.01
965911AG1-460 GEN
Solar/Wind Harmer
1.539
270032AE2-172
Solar/Wind Harmer
5.104
247521TR3_G114
Solar/Wind Harmer
0.277
270246TR4_N_V150
Solar/Wind Harmer
0.049
944231AF1-091 GEN
Solar/Wind Harmer
2.021
276903AD2-071 C
Solar/Wind Harmer
8.405
270005AE1-210 C O1
Solar/Wind Harmer
1.614
965031AG1-367 GEN
Solar/Wind Harmer
7.45
24695305TIMB G C
Solar/Wind Harmer
0.002
970333AG2-219 GEN
Solar/Wind Harmer
4.707
270102X2-052 ST
50/50
2.06
270100X2-052 CT1
50/50
1.898
270101X2-052 CT2
50/50
1.898
970321AG2-212 GEN
Solar/Wind Harmer
4.074
965681AG1-436 GEN
Solar/Wind Harmer
11.195
965791AG1-447 GEN
Solar/Wind Harmer
8.21
274770LINCOLN ;1U
Adder
10.782
274771LINCOLN ;2U
Adder
10.782
270526AF1-158 GEN
Solar/Wind Harmer
0.011
24441505OLIV SLR
Solar/Wind Harmer
0
270216AD2-079_GEN
Solar/Wind Harmer
0.001
957891AF2-083 GEN
Solar/Wind Harmer
0.001
274808UNIV PK N;4U
Adder
6.281
972259AH1-714 GEN
Adder
24.011
274803UNIV PARK;6U
Adder
7.329
274888KELLY CRK;1U
Solar/Wind Harmer
0.515
274887GEN-1.85
Solar/Wind Harmer
0.231
276843GEN-1.7
Solar/Wind Harmer
0.284
958011AF2-095 GEN
Solar/Wind Harmer
12.628
247620Y3-023
Adder
0.578
961051AF2-396 GEN
Solar/Wind Harmer
17.455
961051AF2-396 GEN
Solar/Wind Harmer
11.637
274674JOLIET 9 ;6U
Adder
19.252
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
971573AH1-285 GEN
Solar/Wind Harmer
1.615
274696ROCKY RD ;4P
Adder
14.093
274695ROCKY RD ;2P
Adder
13.768
274693ROCKY RD ;1P
Adder
13.632
274697ROCKY RD ;3P
Adder
3.74
958481AF2-142 GEN
Solar/Wind Harmer
12.927
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
1.166
274683WAUKEGAN ;8U
Adder
26.009
274683WAUKEGAN ;8U
Adder
21.925
962691AG1-118 GEN
Solar/Wind Harmer
25.779
970921AG2-575 GEN
Solar/Wind Harmer
8.581
970921AG2-575 GEN
Solar/Wind Harmer
2.86
958491AF2-143 GEN
Solar/Wind Harmer
12.84
970611AG2-400 GEN
Solar/Wind Harmer
8.544
970627AG2-408 GEN
Solar/Wind Harmer
2.563
942991AE2-321 GEN
Solar/Wind Harmer
9.539
274879MINONK ;1U
Solar/Wind Harmer
0.36
971333AH1-146 GEN
Solar/Wind Harmer
17.035
971335AH1-147 GEN
Solar/Wind Harmer
17.035
971341AH1-150 GEN
Solar/Wind Harmer
16.979
971343AH1-151 GEN
Solar/Wind Harmer
16.979
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
274856ECOGROVE ;U1
Solar/Wind Harmer
0.199
276611AD2-172 GEN
Solar/Wind Harmer
0.002
938861AE1-114 GEN
Solar/Wind Harmer
4.764
274764LEE CO EC;5U
Adder
11.213
274765LEE CO EC;6U
Adder
11.213
274762LEE CO EC;3U
Adder
11.187
274763LEE CO EC;4U
Adder
11.081
276603SUBLETTE C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
972267AH1-718 GEN
Adder
4.979
276741O09 GEN1
Solar/Wind Harmer
0.297
276708O09 GEN2
Solar/Wind Harmer
0.297
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.327
276646AC1-214 GEN2
Solar/Wind Harmer
0.327
944541AF1-119 GEN
Solar/Wind Harmer
0.557
960971AF2-388 GEN
Solar/Wind Harmer
4.876
276782AC1-033 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
2.724
966841AG1-555 GEN
Solar/Wind Harmer
0.919
942221AE2-234 GEN
Solar/Wind Harmer
0.04
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
970241AG2-163 GEN
Solar/Wind Harmer
4.592
270599AE1-208 GEN
Solar/Wind Harmer
7.039
270031AE2-169
Solar/Wind Harmer
4.223
276916AD2-100_GEN
Solar/Wind Harmer
16.09
276911AD2-131_GEN
Solar/Wind Harmer
1.06
971613AH1-306 GEN
Solar/Wind Harmer
3.675
945391AF1-204 GEN
Solar/Wind Harmer
7.93
960441AF2-335 GEN
Solar/Wind Harmer
7.358
970239AG2-162 GEN
Solar/Wind Harmer
1.646
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
8.664
941731AE2-173 GEN
Solar/Wind Harmer
6.876
946321AF1-296 GEN
Solar/Wind Harmer
4.594
965101AG1-375 GEN
Solar/Wind Harmer
8.195
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
963841AG1-237 GEN
Solar/Wind Harmer
3.463
945581AF1-223 GEN
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
10.716
971549AH1-272 GEN
Solar/Wind Harmer
16.349
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.289
276848AB2-070 GEN3
Solar/Wind Harmer
0.287
965041AG1-368 GEN
Solar/Wind Harmer
7.862
970289AG2-191 GEN
Solar/Wind Harmer
1.476
971609AH1-304 GEN
Solar/Wind Harmer
1.254
270594AE1-207 GEN
Solar/Wind Harmer
8.574
965051AG1-369 GEN
Solar/Wind Harmer
3.795
944221AF1-090 GEN
Solar/Wind Harmer
4.425
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
270024AE2-089 GEN
Solar/Wind Harmer
0.008
970115AG2-085 GEN
Solar/Wind Harmer
2.943
270054AF2-122 C O1
Solar/Wind Helper
1.539
24722005FLATG5
50/50
1.795
24721905FLATG4
50/50
32.905
970153AG2-106 GEN
Solar/Wind Harmer
51.584
970513AG2-328 GEN
Solar/Wind Harmer
4.074
970517AG2-330 GEN
Solar/Wind Harmer
24.444
970349AG2-230 GEN
Solar/Wind Harmer
14.036
270043AE2-236 GEN
Solar/Wind Harmer
5.854
274772LINCOLN ;3U
Adder
10.782
247643Z2-116 C
Solar/Wind Harmer
0
24642205MAYFLWER
Adder
0.804
274724RIVER EC ;11
Adder
22.4
970707AG2-453 GEN
Solar/Wind Harmer
28.77
274752CRETE EC ;2U
Adder
10.401
274753CRETE EC ;3U
Adder
10.401
944531AF1-118 GEN
Solar/Wind Harmer
39.427
274826FISK ;BP
Adder
13.763
274802UNIV PARK;5U
Adder
7.329
276806AD2-047 C O1
Solar/Wind Harmer
4.97
970941AG2-585 GEN
Solar/Wind Harmer
10.962
972228AH1-698 GEN2
Adder
4.656
274800UNIV PARK;3U
Adder
7.326
972038AH1-567 GEN2
Adder
0.459
945111AF1-176 GEN
Solar/Wind Harmer
7.104
276897AD1-100 C
Solar/Wind Harmer
0.012
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
37.026
274729ELWOOD EC;1P
Adder
20.542
274730ELWOOD EC;6P
Adder
20.542
274734ELWOOD EC;8P
Adder
20.542
274736ELWOOD EC;9P
Adder
20.542
276893AG1-478 C
Solar/Wind Harmer
0.345
970031AG2-029 GEN
Solar/Wind Harmer
5.657
943121AE2-341 GEN
Solar/Wind Harmer
14.583
943591AF1-030 GEN
Solar/Wind Harmer
9.698
270535AF1-215 GEN1
Solar/Wind Harmer
0.011
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
22.199
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.314
276805AD2-038 GEN
Solar/Wind Harmer
0.003
959331AF2-224 GEN
Solar/Wind Harmer
5.981
965021AG1-366 GEN
Solar/Wind Harmer
2.848
24441205WTRV SLR C
Solar/Wind Harmer
0
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.909
274855GSG-6 ;RU
Solar/Wind Harmer
0.313
274850MENDOTA H;RU
Solar/Wind Harmer
0.1
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.153
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
959091AF2-200 GEN
Solar/Wind Harmer
16.979
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
2.658
247604X1-042
Adder
0.505
970571AG2-364 GEN
Solar/Wind Harmer
16.847
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
11.187
274767LEE CO EC;8U
Adder
11.055
276157O29GEN1
Solar/Wind Harmer
1.347
274878BISHOP HL;2U
Solar/Wind Harmer
0.279
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
8.289
942111AE2-223 GEN
Solar/Wind Harmer
2.682
965931AG1-462 GEN
Solar/Wind Harmer
20.855
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
24.514
959611AF2-252 GEN
Solar/Wind Harmer
2.724
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
3.657
276668AB2-070 GEN1
Solar/Wind Harmer
0.289
247642Z2-115 C
Solar/Wind Harmer
0.003
276621W2-048 GEN
Solar/Wind Harmer
0.395
276838X2-022 GEN2
Solar/Wind Harmer
0.442
970289AG2-191 GEN
Solar/Wind Harmer
0.855
970291AG2-192 GEN
Solar/Wind Harmer
0.777
942481AE2-261 GEN
Solar/Wind Harmer
23.013
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.049
970193AG2-126 GEN
Solar/Wind Harmer
11.195
958821AF2-173 GEN
Solar/Wind Harmer
10.43
270004AE1-209 GEN
Solar/Wind Harmer
1.614
971617AH1-308 GEN
Solar/Wind Harmer
6.153
970243AG2-164 GEN
Solar/Wind Harmer
3.851
970519AG2-331 GEN
Solar/Wind Harmer
17.115
970699AG2-449 GEN
Solar/Wind Harmer
1.646
944201AF1-088_MTX
Adder
118.46
957141AF2-008_MTX
Adder
32.732
NYPJM->LTFIMP_NY
CLTF
3.756
LGEELTFEXP_LGEE->PJM
CLTF
5.526
WECLTFEXP_WEC->PJM
CLTF
4.63
AG2-052LTFEXP_AG2-052->PJM
LTF
0.285
AH1-155LTFEXP_AH1-155->PJM
LTF
0.428
CPLELTFEXP_CPLE->PJM
CLTF
3.24
CBM West 2LTFEXP_CBM-W2->PJM
CBM
120.262
LAGNLTFEXP_LAGN->PJM
CLTF
16.296
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.027
TVALTFEXP_TVA->PJM
CLTF
7.706
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.812
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.167
MECLTFEXP_MEC->PJM
CLTF
18.496
SIGELTFEXP_SIGE->PJM
CLTF
0.474

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AEP_P4_#8085_05MARYSV 345_H_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#8085_05MARYSV 345_H_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.72 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5518.14
MW Contribution:48.72
Bus #Bus NameTypeMW Contribution
24722005FLATG5
50/50
1.463
24721905FLATG4
50/50
26.818
970153AG2-106 GEN
Solar/Wind Harmer
48.717
970513AG2-328 GEN
Solar/Wind Harmer
21.746
970517AG2-330 GEN
Solar/Wind Harmer
19.723
970349AG2-230 GEN
Solar/Wind Harmer
18.177
274772LINCOLN ;3U
Adder
7.008
270043AE2-236 GEN
Solar/Wind Harmer
6.178
247643Z2-116 C
Solar/Wind Harmer
0.078
274724RIVER EC ;11
Adder
19.691
970707AG2-453 GEN
Solar/Wind Harmer
31.101
24642205MAYFLWER
Adder
0.705
972231SS25-0005
Solar/Wind Harmer
10.514
972181SS23-001
Solar/Wind Harmer
6.571
274752CRETE EC ;2U
Adder
5.415
274753CRETE EC ;3U
Adder
5.415
274826FISK ;BP
Adder
12.072
972228AH1-698 GEN2
Adder
4.084
274802UNIV PARK;5U
Adder
6.427
276772AC2-154 GEN
Solar/Wind Harmer
3.074
276806AD2-047 C O1
Solar/Wind Harmer
11.793
970941AG2-585 GEN
Solar/Wind Harmer
13.78
274800UNIV PARK;3U
Adder
6.424
972038AH1-567 GEN2
Adder
0.402
276897AD1-100 C
Solar/Wind Harmer
31.897
939351AE1-166 GEN
Solar/Wind Harmer
6.517
274676JOLIET 29;8U
Adder
32.424
945111AF1-176 GEN
Solar/Wind Harmer
6.195
274729ELWOOD EC;1P
Adder
17.974
274730ELWOOD EC;6P
Adder
17.974
274734ELWOOD EC;8P
Adder
17.974
274736ELWOOD EC;9P
Adder
17.974
276893AG1-478 C
Solar/Wind Harmer
0.456
943121AE2-341 GEN
Solar/Wind Harmer
16.363
943591AF1-030 GEN
Solar/Wind Harmer
10.909
274682WAUKEGAN ;7U
Adder
19.342
276694AA1-018 GEN2
Solar/Wind Harmer
6.783
270535AF1-215 GEN1
Solar/Wind Harmer
4.874
274872LEEDK;1U
Solar/Wind Harmer
0.273
276805AD2-038 GEN
Solar/Wind Harmer
5.46
944531AF1-118 GEN
Solar/Wind Harmer
37.24
24441205WTRV SLR C
Solar/Wind Harmer
0.143
276799AD1-013 GEN
Solar/Wind Harmer
2.342
946671AF1-331 GEN
Solar/Wind Harmer
0.444
274855GSG-6 ;RU
Solar/Wind Harmer
3.911
274850MENDOTA H;RU
Solar/Wind Harmer
2.719
276602WESTBROOK C
Solar/Wind Harmer
2.251
276863AD2-134 GEN
Solar/Wind Harmer
1.891
964401AG1-302 GEN
Solar/Wind Harmer
9.583
247604X1-042
Adder
0.437
972236AH1-702 GEN2
Adder
2.298
274760LEE CO EC;1U
Adder
9.633
274767LEE CO EC;8U
Adder
9.519
241955AC1-078 GEN
Solar/Wind Helper
2.355
241974AD2-163_GEN2
Solar/Wind Helper
1.908
960801AF2-371 GEN
Solar/Wind Helper
0.993
964871AG1-351 GEN
Solar/Wind Helper
0.686
959091AF2-200 GEN
Solar/Wind Harmer
15.934
24344105CKG2
50/50
9.547
24721805FLATG3
50/50
1.463
24721705FLATG2
50/50
26.818
962761AG1-125 GEN
Solar/Wind Harmer
111.725
970149AG2-104 GEN
Solar/Wind Harmer
137.98
970155AG2-107 GEN
Solar/Wind Harmer
48.717
970245AG2-165 GEN
Solar/Wind Harmer
21.746
972207SS24-0001
Solar/Wind Harmer
24.918
274773LINCOLN ;4U
Adder
7.008
274774LINCOLN ;5U
Adder
7.008
274723RIVER EC ;12
Adder
19.918
276164X3-005 C
Solar/Wind Harmer
0.779
274751CRETE EC ;1U
Adder
5.415
274754CRETE EC ;4U
Adder
5.415
274812UNIV PK N;8U
Adder
5.534
270505AE1-170 C O1
Solar/Wind Harmer
16.56
276776AD2-060 GEN
Solar/Wind Harmer
0.466
274801UNIV PARK;4U
Adder
6.424
941551AE2-152 GEN
Solar/Wind Harmer
4.985
24639705ELKHART HY
Adder
0.168
274676JOLIET 29;8U
Adder
33.625
945111AF1-176 GEN
Solar/Wind Harmer
19.547
274674JOLIET 9 ;6U
Adder
16.852
274732ELWOOD EC;7P
Adder
17.974
274871GR RIDGE ;2U
Solar/Wind Harmer
8.405
970373AG2-245 GEN
Solar/Wind Harmer
22.924
274745AC1-111 GEN9
Adder
6.085
270449AD2-020 GEN
Solar/Wind Harmer
3.051
943021AE2-325 GEN
Solar/Wind Harmer
3.965
274682WAUKEGAN ;7U
Adder
19.342
274828WAUKEGAN ;BP
Adder
11.875
276691AA1-018 GEN1
Solar/Wind Harmer
0.5
270055AF2-134 C O1
Solar/Wind Harmer
3.249
960751AF2-366 GEN
Solar/Wind Harmer
3.069
962781AG1-127 GEN
Solar/Wind Harmer
10.173
274872LEEDK;1U
Solar/Wind Harmer
8.77
939401AE1-172 GEN
Solar/Wind Harmer
14.843
276901AD2-066 C O1
Solar/Wind Harmer
3.736
270063AE2-323 C
Solar/Wind Harmer
2.34
971997AH1-543 GEN
Solar/Wind Harmer
16.683
276861AD2-134 GEN
Solar/Wind Harmer
1.891
958381AF2-132 GEN
Solar/Wind Harmer
9.583
964861AG1-349 GEN
Solar/Wind Harmer
8.289
971917AH1-482 GEN
Solar/Wind Harmer
9.566
274822ROCKFORD ;11
Adder
20.615
972235AH1-702 GEN1
Adder
2.642
274761LEE CO EC;2U
Adder
9.633
274766LEE CO EC;7U
Adder
9.519
270349AD2-093_GEN
Solar/Wind Helper
2.063
957471AF2-041 GEN
Solar/Wind Harmer
23.901
959081AF2-199 GEN
Solar/Wind Harmer
7.967
971067AG2-660 GEN
Solar/Wind Harmer
1.853
971599AH1-298 GEN
50/50
10.874
24721605FLATG1
50/50
1.463
962771AG1-126 GEN
Solar/Wind Harmer
111.725
971347AH1-153 GEN
Solar/Wind Harmer
18.177
960681AF2-359 GEN
Solar/Wind Harmer
4.287
274775LINCOLN ;6U
Adder
7.008
274776LINCOLN ;7U
Adder
7.008
274777LINCOLN ;8U
Adder
7.008
971771AH1-392 GEN
Solar/Wind Harmer
10.12
971769AH1-391 GEN
Solar/Wind Harmer
11.239
270071AF1-092 GEN
Solar/Wind Harmer
16.631
274814UNIV PK N;0U
Adder
5.583
274807UNIV PK N;3U
Adder
5.57
274805UNIV PK N;1U
Adder
5.546
274811UNIV PK N;7U
Adder
5.534
274827FISK ;RP
Adder
8.556
972227AH1-698 GEN1
Adder
2.876
972037AH1-567 GEN1
Adder
0.202
960591AF2-350 GEN
Solar/Wind Harmer
11.024
274687WILL CNTY;4U
Adder
30.645
274687WILL CNTY;4U
Adder
30.645
274675JOLIET 29;7U
Adder
33.626
274675JOLIET 29;7U
Adder
32.425
274731ELWOOD EC;2P
Adder
17.974
274733ELWOOD EC;3P
Adder
17.974
274735ELWOOD EC;4P
Adder
17.974
274728ELWOOD EC;5P
Adder
17.974
970833AG2-524 GEN
Solar/Wind Harmer
9.546
970833AG2-524 GEN
Solar/Wind Harmer
4.44
274746AC1-111 G10
Adder
6.085
274744AC1-111 GEN8
Adder
6.085
944161AF1-084 GEN
Solar/Wind Harmer
2.388
270536AF1-215 GEN2
Solar/Wind Harmer
4.874
971177AH1-047 GEN
Solar/Wind Harmer
6.227
276868AE1-113 GEN
Solar/Wind Harmer
10.734
276882AE2-255 GEN
Solar/Wind Harmer
3.578
971675AH1-338 GEN
Solar/Wind Harmer
19.065
971411AH1-196 GEN
Solar/Wind Harmer
15.886
274823ROCKFORD ;21
Adder
20.466
24729505KEY G4
Adder
6.743
270054AF2-122 C O1
Solar/Wind Helper
2.141
270520AE2-214 GEN
Solar/Wind Helper
6.625
270284AF1-227 GEN1
Solar/Wind Helper
2.625
270286AF1-227 GEN2
Solar/Wind Helper
0.963
270287AF1-227 GEN3
Solar/Wind Helper
0.963
253383AE2-342_GEN
Solar/Wind Helper
0.859
241973AD2-163_GEN1
Solar/Wind Helper
1.908
945631AF1-228 GEN
Solar/Wind Helper
1.875
971171AH1-044 GEN
Solar/Wind Harmer
15.934
270102X2-052 ST
50/50
1.824
270100X2-052 CT1
50/50
1.681
270101X2-052 CT2
50/50
1.681
970321AG2-212 GEN
Solar/Wind Harmer
21.746
965681AG1-436 GEN
Solar/Wind Harmer
14.185
965791AG1-447 GEN
Solar/Wind Harmer
7.258
274770LINCOLN ;1U
Adder
7.008
274771LINCOLN ;2U
Adder
7.008
270526AF1-158 GEN
Solar/Wind Harmer
5.107
24441505OLIV SLR
Solar/Wind Harmer
0.151
270216AD2-079_GEN
Solar/Wind Harmer
0.675
972259AH1-714 GEN
Adder
21.085
274808UNIV PK N;4U
Adder
5.51
274803UNIV PARK;6U
Adder
6.427
274888KELLY CRK;1U
Solar/Wind Harmer
6.509
274887GEN-1.85
Solar/Wind Harmer
5.876
276843GEN-1.7
Solar/Wind Harmer
0.632
958011AF2-095 GEN
Solar/Wind Harmer
15.875
957891AF2-083 GEN
Solar/Wind Harmer
3.717
960981AF2-389 GEN
Solar/Wind Harmer
1.665
274674JOLIET 9 ;6U
Adder
16.852
274847GR RIDGE ;BU
Solar/Wind Harmer
5.529
961051AF2-396 GEN
Solar/Wind Harmer
17.321
961051AF2-396 GEN
Solar/Wind Harmer
8.056
971573AH1-285 GEN
Solar/Wind Harmer
9.336
247620Y3-023
Adder
0.498
274696ROCKY RD ;4P
Adder
12.286
274695ROCKY RD ;2P
Adder
12.003
274693ROCKY RD ;1P
Adder
11.884
274697ROCKY RD ;3P
Adder
3.261
274683WAUKEGAN ;8U
Adder
22.655
274683WAUKEGAN ;8U
Adder
19.097
958481AF2-142 GEN
Solar/Wind Harmer
16.124
274861TOP CROP ;1U
Solar/Wind Harmer
6.51
274862TOP CROP ;2U
Solar/Wind Harmer
5.436
962691AG1-118 GEN
Solar/Wind Harmer
32.158
970921AG2-575 GEN
Solar/Wind Harmer
10.697
970921AG2-575 GEN
Solar/Wind Harmer
2.488
958491AF2-143 GEN
Solar/Wind Harmer
15.964
942991AE2-321 GEN
Solar/Wind Harmer
10.629
274879MINONK ;1U
Solar/Wind Harmer
7.157
971333AH1-146 GEN
Solar/Wind Harmer
21.169
971335AH1-147 GEN
Solar/Wind Harmer
21.169
274764LEE CO EC;5U
Adder
9.655
274765LEE CO EC;6U
Adder
9.655
274762LEE CO EC;3U
Adder
9.633
274763LEE CO EC;4U
Adder
9.542
972267AH1-718 GEN
Adder
4.276
270471AD2-092_GEN
Solar/Wind Helper
2.063
946101AF1-275 GEN
Solar/Wind Helper
0.83
241960AC2-195 GEN
Solar/Wind Helper
1.452
971341AH1-150 GEN
Solar/Wind Harmer
15.934
971343AH1-151 GEN
Solar/Wind Harmer
15.934
NYPJM->LTFIMP_NY
CLTF
2.504
LGEELTFEXP_LGEE->PJM
CLTF
3.288
WECLTFEXP_WEC->PJM
CLTF
4
AG2-052LTFEXP_AG2-052->PJM
LTF
0.245
AH1-155LTFEXP_AH1-155->PJM
LTF
0.368
CPLELTFEXP_CPLE->PJM
CLTF
1.947
CBM West 2LTFEXP_CBM-W2->PJM
CBM
88.828
LAGNLTFEXP_LAGN->PJM
CLTF
11.716
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.038
TVALTFEXP_TVA->PJM
CLTF
5.258
CBM West 1LTFEXP_CBM-W1->PJM
CBM
116.721
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.427
MECLTFEXP_MEC->PJM
CLTF
15.3
SIGELTFEXP_SIGE->PJM
CLTF
0.326

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AEP_P2-2_#8072_05MARYSV 765_2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P2-2_#8072_05MARYSV 765_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:119.53 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5463.93
MW Contribution:48.95
Bus #Bus NameTypeMW Contribution
24721805FLATG3
50/50
1.475
24721705FLATG2
50/50
27.034
24344105CKG2
50/50
9.41
962761AG1-125 GEN
Solar/Wind Harmer
112.25
970149AG2-104 GEN
Solar/Wind Harmer
138.629
970155AG2-107 GEN
Solar/Wind Harmer
48.946
970245AG2-165 GEN
Solar/Wind Harmer
21.445
972207SS24-0001
Solar/Wind Harmer
24.53
274773LINCOLN ;4U
Adder
6.899
274774LINCOLN ;5U
Adder
6.899
274723RIVER EC ;12
Adder
19.592
24722005FLATG5
50/50
1.475
24721905FLATG4
50/50
27.034
970153AG2-106 GEN
Solar/Wind Harmer
48.946
24721605FLATG1
50/50
1.475
971599AH1-298 GEN
50/50
10.653
962771AG1-126 GEN
Solar/Wind Harmer
112.25
971347AH1-153 GEN
Solar/Wind Harmer
17.888
960681AF2-359 GEN
Solar/Wind Harmer
4.214
274775LINCOLN ;6U
Adder
6.899
274776LINCOLN ;7U
Adder
6.899
274777LINCOLN ;8U
Adder
6.899
971769AH1-391 GEN
Solar/Wind Harmer
11.035
971771AH1-392 GEN
Solar/Wind Harmer
9.928
274814UNIV PK N;0U
Adder
5.491
274807UNIV PK N;3U
Adder
5.479
274805UNIV PK N;1U
Adder
5.455
274811UNIV PK N;7U
Adder
5.443
274827FISK ;RP
Adder
8.417
972227AH1-698 GEN1
Adder
2.829
960591AF2-350 GEN
Solar/Wind Harmer
10.846
972037AH1-567 GEN1
Adder
0.198
270071AF1-092 GEN
Solar/Wind Harmer
16.243
274687WILL CNTY;4U
Adder
30.151
274687WILL CNTY;4U
Adder
30.151
274675JOLIET 29;7U
Adder
33.085
274675JOLIET 29;7U
Adder
31.904
970833AG2-524 GEN
Solar/Wind Harmer
9.393
970833AG2-524 GEN
Solar/Wind Harmer
4.369
274731ELWOOD EC;2P
Adder
17.685
274733ELWOOD EC;3P
Adder
17.685
274735ELWOOD EC;4P
Adder
17.685
274728ELWOOD EC;5P
Adder
17.685
274746AC1-111 G10
Adder
5.988
274744AC1-111 GEN8
Adder
5.988
944161AF1-084 GEN
Solar/Wind Harmer
2.339
270536AF1-215 GEN2
Solar/Wind Harmer
4.788
971177AH1-047 GEN
Solar/Wind Harmer
6.127
276868AE1-113 GEN
Solar/Wind Harmer
10.56
276882AE2-255 GEN
Solar/Wind Harmer
3.52
971675AH1-338 GEN
Solar/Wind Harmer
18.759
971411AH1-196 GEN
Solar/Wind Harmer
15.631
274823ROCKFORD ;21
Adder
20.137
24729505KEY G4
Adder
6.578
270054AF2-122 C O1
Solar/Wind Helper
2.088
270520AE2-214 GEN
Solar/Wind Helper
6.396
253383AE2-342_GEN
Solar/Wind Helper
0.847
270284AF1-227 GEN1
Solar/Wind Helper
2.356
270286AF1-227 GEN2
Solar/Wind Helper
0.864
270287AF1-227 GEN3
Solar/Wind Helper
0.864
241973AD2-163_GEN1
Solar/Wind Helper
1.851
945631AF1-228 GEN
Solar/Wind Helper
1.836
971171AH1-044 GEN
Solar/Wind Harmer
18.92
970513AG2-328 GEN
Solar/Wind Harmer
21.445
970517AG2-330 GEN
Solar/Wind Harmer
19.45
970349AG2-230 GEN
Solar/Wind Harmer
17.888
274772LINCOLN ;3U
Adder
6.899
270043AE2-236 GEN
Solar/Wind Harmer
6.024
247643Z2-116 C
Solar/Wind Harmer
0.076
274724RIVER EC ;11
Adder
19.369
970707AG2-453 GEN
Solar/Wind Harmer
30.611
972231SS25-0005
Solar/Wind Harmer
10.34
972181SS23-001
Solar/Wind Harmer
6.462
274752CRETE EC ;2U
Adder
5.325
274753CRETE EC ;3U
Adder
5.325
24642205MAYFLWER
Adder
0.691
274826FISK ;BP
Adder
11.877
972228AH1-698 GEN2
Adder
4.018
276772AC2-154 GEN
Solar/Wind Harmer
3.025
276806AD2-047 C O1
Solar/Wind Harmer
11.603
970941AG2-585 GEN
Solar/Wind Harmer
13.558
274802UNIV PARK;5U
Adder
6.323
274800UNIV PARK;3U
Adder
6.32
972038AH1-567 GEN2
Adder
0.396
276897AD1-100 C
Solar/Wind Harmer
31.386
939351AE1-166 GEN
Solar/Wind Harmer
6.413
274676JOLIET 29;8U
Adder
31.903
274729ELWOOD EC;1P
Adder
17.685
274730ELWOOD EC;6P
Adder
17.685
274734ELWOOD EC;8P
Adder
17.685
274736ELWOOD EC;9P
Adder
17.685
276893AG1-478 C
Solar/Wind Harmer
0.449
943121AE2-341 GEN
Solar/Wind Harmer
16.103
943591AF1-030 GEN
Solar/Wind Harmer
10.736
945111AF1-176 GEN
Solar/Wind Harmer
6.068
274682WAUKEGAN ;7U
Adder
19.032
276694AA1-018 GEN2
Solar/Wind Harmer
6.673
270535AF1-215 GEN1
Solar/Wind Harmer
4.788
274872LEEDK;1U
Solar/Wind Harmer
0.269
276805AD2-038 GEN
Solar/Wind Harmer
5.371
276799AD1-013 GEN
Solar/Wind Harmer
2.305
946671AF1-331 GEN
Solar/Wind Harmer
0.436
274855GSG-6 ;RU
Solar/Wind Harmer
3.848
274850MENDOTA H;RU
Solar/Wind Harmer
2.676
276602WESTBROOK C
Solar/Wind Harmer
2.215
276863AD2-134 GEN
Solar/Wind Harmer
1.861
24441205WTRV SLR C
Solar/Wind Harmer
0.14
944531AF1-118 GEN
Solar/Wind Harmer
36.351
964401AG1-302 GEN
Solar/Wind Harmer
9.412
972236AH1-702 GEN2
Adder
2.261
247604X1-042
Adder
0.428
274760LEE CO EC;1U
Adder
9.477
274767LEE CO EC;8U
Adder
9.366
241955AC1-078 GEN
Solar/Wind Helper
2.287
241974AD2-163_GEN2
Solar/Wind Helper
1.851
960801AF2-371 GEN
Solar/Wind Helper
0.963
964871AG1-351 GEN
Solar/Wind Helper
0.665
959091AF2-200 GEN
Solar/Wind Harmer
18.92
276164X3-005 C
Solar/Wind Harmer
0.767
274751CRETE EC ;1U
Adder
5.325
274754CRETE EC ;4U
Adder
5.325
274812UNIV PK N;8U
Adder
5.443
276776AD2-060 GEN
Solar/Wind Harmer
0.459
274801UNIV PARK;4U
Adder
6.32
270505AE1-170 C O1
Solar/Wind Harmer
16.232
941551AE2-152 GEN
Solar/Wind Harmer
4.905
274676JOLIET 29;8U
Adder
33.085
274674JOLIET 9 ;6U
Adder
16.581
274732ELWOOD EC;7P
Adder
17.685
274871GR RIDGE ;2U
Solar/Wind Harmer
8.271
945111AF1-176 GEN
Solar/Wind Harmer
19.147
24639705ELKHART HY
Adder
0.165
970373AG2-245 GEN
Solar/Wind Harmer
22.522
274745AC1-111 GEN9
Adder
5.988
270449AD2-020 GEN
Solar/Wind Harmer
2.989
943021AE2-325 GEN
Solar/Wind Harmer
3.884
274682WAUKEGAN ;7U
Adder
19.032
274828WAUKEGAN ;BP
Adder
11.685
276691AA1-018 GEN1
Solar/Wind Harmer
0.492
270055AF2-134 C O1
Solar/Wind Harmer
3.192
960751AF2-366 GEN
Solar/Wind Harmer
3.02
962781AG1-127 GEN
Solar/Wind Harmer
10.01
274872LEEDK;1U
Solar/Wind Harmer
8.629
939401AE1-172 GEN
Solar/Wind Harmer
14.602
276901AD2-066 C O1
Solar/Wind Harmer
3.675
971997AH1-543 GEN
Solar/Wind Harmer
16.413
276861AD2-134 GEN
Solar/Wind Harmer
1.861
958381AF2-132 GEN
Solar/Wind Harmer
9.412
274822ROCKFORD ;11
Adder
20.284
972235AH1-702 GEN1
Adder
2.6
274761LEE CO EC;2U
Adder
9.477
274766LEE CO EC;7U
Adder
9.366
270349AD2-093_GEN
Solar/Wind Helper
1.808
957471AF2-041 GEN
Solar/Wind Harmer
28.38
959081AF2-199 GEN
Solar/Wind Harmer
9.46
971067AG2-660 GEN
Solar/Wind Harmer
2.2
270102X2-052 ST
50/50
1.793
270100X2-052 CT1
50/50
1.652
270101X2-052 CT2
50/50
1.652
970321AG2-212 GEN
Solar/Wind Harmer
21.445
965681AG1-436 GEN
Solar/Wind Harmer
13.942
965791AG1-447 GEN
Solar/Wind Harmer
7.133
274770LINCOLN ;1U
Adder
6.899
274771LINCOLN ;2U
Adder
6.899
24441505OLIV SLR
Solar/Wind Harmer
0.148
270526AF1-158 GEN
Solar/Wind Harmer
5.013
270216AD2-079_GEN
Solar/Wind Harmer
0.661
972259AH1-714 GEN
Adder
20.75
274808UNIV PK N;4U
Adder
5.42
274888KELLY CRK;1U
Solar/Wind Harmer
6.404
274887GEN-1.85
Solar/Wind Harmer
5.781
276843GEN-1.7
Solar/Wind Harmer
0.622
958011AF2-095 GEN
Solar/Wind Harmer
15.619
274803UNIV PARK;6U
Adder
6.323
957891AF2-083 GEN
Solar/Wind Harmer
3.643
960981AF2-389 GEN
Solar/Wind Harmer
1.632
274674JOLIET 9 ;6U
Adder
16.581
274847GR RIDGE ;BU
Solar/Wind Harmer
5.441
961051AF2-396 GEN
Solar/Wind Harmer
16.968
961051AF2-396 GEN
Solar/Wind Harmer
7.892
971573AH1-285 GEN
Solar/Wind Harmer
9.188
274695ROCKY RD ;2P
Adder
11.811
274693ROCKY RD ;1P
Adder
11.694
274697ROCKY RD ;3P
Adder
3.208
274696ROCKY RD ;4P
Adder
12.089
274683WAUKEGAN ;8U
Adder
22.291
274683WAUKEGAN ;8U
Adder
18.791
958481AF2-142 GEN
Solar/Wind Harmer
15.862
274861TOP CROP ;1U
Solar/Wind Harmer
6.405
274862TOP CROP ;2U
Solar/Wind Harmer
5.348
247620Y3-023
Adder
0.486
962691AG1-118 GEN
Solar/Wind Harmer
31.644
970921AG2-575 GEN
Solar/Wind Harmer
10.526
970921AG2-575 GEN
Solar/Wind Harmer
2.448
958491AF2-143 GEN
Solar/Wind Harmer
15.704
942991AE2-321 GEN
Solar/Wind Harmer
10.459
274879MINONK ;1U
Solar/Wind Harmer
7.04
971333AH1-146 GEN
Solar/Wind Harmer
20.829
971335AH1-147 GEN
Solar/Wind Harmer
20.829
274764LEE CO EC;5U
Adder
9.5
274765LEE CO EC;6U
Adder
9.5
274762LEE CO EC;3U
Adder
9.477
274763LEE CO EC;4U
Adder
9.388
972267AH1-718 GEN
Adder
4.207
946101AF1-275 GEN
Solar/Wind Helper
0.801
270471AD2-092_GEN
Solar/Wind Helper
1.808
241960AC2-195 GEN
Solar/Wind Helper
1.411
971341AH1-150 GEN
Solar/Wind Harmer
18.92
971343AH1-151 GEN
Solar/Wind Harmer
18.92
NYPJM->LTFIMP_NY
CLTF
2.462
LGEELTFEXP_LGEE->PJM
CLTF
3.192
WECLTFEXP_WEC->PJM
CLTF
3.935
AG2-052LTFEXP_AG2-052->PJM
LTF
0.241
AH1-155LTFEXP_AH1-155->PJM
LTF
0.362
CPLELTFEXP_CPLE->PJM
CLTF
1.972
CBM West 2LTFEXP_CBM-W2->PJM
CBM
87.287
LAGNLTFEXP_LAGN->PJM
CLTF
11.551
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.064
TVALTFEXP_TVA->PJM
CLTF
5.187
CBM West 1LTFEXP_CBM-W1->PJM
CBM
113.826
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.114
MECLTFEXP_MEC->PJM
CLTF
15.05
SIGELTFEXP_SIGE->PJM
CLTF
0.318

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AEP_P1-2_#706_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#706_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.18 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5310.77
MW Contribution:76.66
Bus #Bus NameTypeMW Contribution
24721805FLATG3
50/50
5.145
24721705FLATG2
50/50
94.33
24344105CKG2
50/50
12.069
270143AC1-141 CT2_
50/50
3.558
24639705ELKHART HY
50/50
0.241
970521AG2-332 GEN
50/50
17.184
24307105BERRINSP G
50/50
0.032
962761AG1-125 GEN
Solar/Wind Harmer
120.047
970149AG2-104 GEN
Solar/Wind Harmer
129.655
970155AG2-107 GEN
Solar/Wind Harmer
76.659
270349AD2-093_GEN
Solar/Wind Harmer
0.009
965011AG1-365 GEN
Solar/Wind Harmer
10.537
970245AG2-165 GEN
Solar/Wind Harmer
4.559
270063AE2-323 C
Solar/Wind Harmer
0.008
270505AE1-170 C O1
Solar/Wind Harmer
10.806
945111AF1-176 GEN
Solar/Wind Harmer
18.321
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
5.329
274773LINCOLN ;4U
Adder
11.972
274774LINCOLN ;5U
Adder
11.972
274723RIVER EC ;12
Adder
25.205
274751CRETE EC ;1U
Adder
11.58
274754CRETE EC ;4U
Adder
11.58
270223U2-072_GEN1
Solar/Wind Harmer
0.001
276164X3-005 C
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
20.506
274812UNIV PK N;8U
Adder
6.996
274801UNIV PARK;4U
Adder
8.089
276776AD2-060 GEN
Solar/Wind Harmer
1.011
247521TR3_G114
Solar/Wind Harmer
0.351
270246TR4_N_V150
Solar/Wind Harmer
0.062
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
42.222
274674JOLIET 9 ;6U
Adder
21.154
274732ELWOOD EC;7P
Adder
22.567
270055AF2-134 C O1
Solar/Wind Harmer
0.007
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
7.614
944231AF1-091 GEN
Solar/Wind Harmer
2.532
24695305TIMB G C
Solar/Wind Harmer
0.002
965421AG1-410 GEN
Solar/Wind Harmer
28.36
958381AF2-132 GEN
Solar/Wind Harmer
0.001
276691AA1-018 GEN1
Solar/Wind Harmer
1.138
965651AG1-433 GEN
Solar/Wind Harmer
2.755
274682WAUKEGAN ;7U
Adder
24.169
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
12.195
274828WAUKEGAN ;BP
Adder
14.836
246936BC-WTG1
Solar/Wind Harmer
0.379
270489AE1-102 GEN1
Solar/Wind Harmer
1.214
270462AD2-086
Solar/Wind Harmer
0.02
962781AG1-127 GEN
Solar/Wind Harmer
8.858
939401AE1-172 GEN
Solar/Wind Harmer
6.954
274872LEEDK;1U
Solar/Wind Harmer
0.006
276901AD2-066 C O1
Solar/Wind Harmer
0.009
971997AH1-543 GEN
Solar/Wind Harmer
4.843
958861AF2-177 GEN
Solar/Wind Harmer
3.987
276861AD2-134 GEN
Solar/Wind Harmer
0.165
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
11.452
957471AF2-041 GEN
Solar/Wind Harmer
27.428
959081AF2-199 GEN
Solar/Wind Harmer
9.143
971067AG2-660 GEN
Solar/Wind Harmer
3.048
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
274822ROCKFORD ;11
Adder
25.633
972235AH1-702 GEN1
Adder
3.284
970819AG2-516 GEN
Solar/Wind Harmer
10.874
971475AH1-234 GEN
Solar/Wind Harmer
4.385
970569AG2-363 GEN
Solar/Wind Harmer
27.095
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
11.947
274766LEE CO EC;7U
Adder
11.806
276158O29GEN2
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.295
24791305MDL-5G
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0.003
939741AE1-205 GEN
Solar/Wind Harmer
12.194
274854TWINGROVE;U2
Solar/Wind Harmer
0.004
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
972175AH1-670 GEN
Solar/Wind Harmer
6.873
970291AG2-192 GEN
Solar/Wind Harmer
1.08
270032AE2-172
Solar/Wind Harmer
5.46
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
3.14
963741AG1-226 GEN
Solar/Wind Harmer
19.026
270005AE1-210 C O1
Solar/Wind Harmer
1.733
965031AG1-367 GEN
Solar/Wind Harmer
8
276615X2-022 GEN
Solar/Wind Harmer
0.084
276903AD2-071 C
Solar/Wind Harmer
8.872
970825AG2-519 GEN
Solar/Wind Harmer
2.793
965911AG1-460 GEN
Solar/Wind Harmer
1.538
24728605AND G2
Adder
3.739
24721605FLATG1
50/50
5.145
971599AH1-298 GEN
50/50
14.587
270144AC1-141 ST1_
50/50
3.152
24653605MOTTVILLE
50/50
0.006
24643105BUCHANAN
50/50
0.019
962771AG1-126 GEN
Solar/Wind Harmer
120.047
270284AF1-227 GEN1
Solar/Wind Harmer
0.014
270286AF1-227 GEN2
Solar/Wind Harmer
0.006
270287AF1-227 GEN3
Solar/Wind Harmer
0.006
971347AH1-153 GEN
Solar/Wind Harmer
16.236
270071AF1-092 GEN
Solar/Wind Harmer
20.132
971771AH1-392 GEN
Solar/Wind Harmer
10.346
971619AH1-309 GEN
Solar/Wind Harmer
4.631
971769AH1-391 GEN
Solar/Wind Harmer
11.424
960681AF2-359 GEN
Solar/Wind Harmer
-0.002
24729505KEY G4
Adder
9.267
274775LINCOLN ;6U
Adder
11.972
274776LINCOLN ;7U
Adder
11.972
274777LINCOLN ;8U
Adder
11.972
965041AG1-368 GEN
Solar/Wind Harmer
9.847
270578AF1-285 GEN2
Solar/Wind Harmer
0.651
274814UNIV PK N;0U
Adder
7.057
274807UNIV PK N;3U
Adder
7.042
274805UNIV PK N;1U
Adder
7.011
274811UNIV PK N;7U
Adder
6.996
972037AH1-567 GEN1
Adder
0.254
274827FISK ;RP
Adder
10.776
960591AF2-350 GEN
Solar/Wind Harmer
9.68
972227AH1-698 GEN1
Adder
3.616
965051AG1-369 GEN
Solar/Wind Harmer
4.807
274687WILL CNTY;4U
Adder
38.503
274687WILL CNTY;4U
Adder
38.503
274675JOLIET 29;7U
Adder
42.223
274675JOLIET 29;7U
Adder
40.715
274728ELWOOD EC;5P
Adder
22.567
274731ELWOOD EC;2P
Adder
22.566
274733ELWOOD EC;3P
Adder
22.566
274735ELWOOD EC;4P
Adder
22.566
270536AF1-215 GEN2
Solar/Wind Harmer
0.012
970833AG2-524 GEN
Solar/Wind Harmer
10.52
970833AG2-524 GEN
Solar/Wind Harmer
7.013
971549AH1-272 GEN
Solar/Wind Harmer
19.681
274746AC1-111 G10
Adder
7.614
274744AC1-111 GEN8
Adder
7.614
963791AG1-232 GEN
Solar/Wind Harmer
12.76
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.183
270302AB2-170 GEN
Solar/Wind Harmer
0.006
270317AD1-130_GEN
Solar/Wind Harmer
0.013
971653AH1-327 GEN
Solar/Wind Harmer
1.314
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.855
276882AE2-255 GEN
Solar/Wind Harmer
1.081
971177AH1-047 GEN
Solar/Wind Harmer
5.697
965101AG1-375 GEN
Solar/Wind Harmer
9.202
971411AH1-196 GEN
Solar/Wind Harmer
13.802
971675AH1-338 GEN
Solar/Wind Harmer
3.588
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
971611AH1-305 GEN
Solar/Wind Harmer
5.454
971171AH1-044 GEN
Solar/Wind Harmer
18.285
274823ROCKFORD ;21
Adder
25.447
276612AE2-035 GEN
Solar/Wind Harmer
0.002
926823AC1-168 GEN
Solar/Wind Harmer
1.535
970169AG2-114 GEN
Solar/Wind Harmer
9.023
971681AH1-341 GEN
Solar/Wind Harmer
14.483
247607V1-011 GEN
Solar/Wind Harmer
0.001
961011AF2-392 GEN
Solar/Wind Harmer
5.219
945581AF1-223 GEN
Solar/Wind Harmer
0.001
957751AF2-069 GEN
Solar/Wind Harmer
0.292
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
9.145
941731AE2-173 GEN
Solar/Wind Harmer
7.258
946321AF1-296 GEN
Solar/Wind Harmer
4.827
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
270024AE2-089 GEN
Solar/Wind Harmer
0.009
971609AH1-304 GEN
Solar/Wind Harmer
1.375
970289AG2-191 GEN
Solar/Wind Harmer
1.578
963841AG1-237 GEN
Solar/Wind Harmer
3.575
270594AE1-207 GEN
Solar/Wind Harmer
9.172
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.295
276848AB2-070 GEN3
Solar/Wind Harmer
0.294
970115AG2-085 GEN
Solar/Wind Harmer
3.159
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
270297AD1-101 GEN
Solar/Wind Harmer
0.002
24722005FLATG5
50/50
5.145
24721905FLATG4
50/50
94.33
270475AD2-096_GEN
50/50
10.026
270142AC1-141 CT1_
50/50
3.558
24641605TWIN BRNCH
50/50
0.026
24344005CKG1
50/50
9.691
24642205MAYFLWER
50/50
0.992
944961AF1-161 GEN
50/50
4.253
962601AG1-109 GEN
50/50
4.253
247604X1-042
50/50
0.632
970153AG2-106 GEN
Solar/Wind Harmer
76.659
270043AE2-236 GEN
Solar/Wind Harmer
6.969
970349AG2-230 GEN
Solar/Wind Harmer
16.236
959331AF2-224 GEN
Solar/Wind Harmer
7.376
965021AG1-366 GEN
Solar/Wind Harmer
3.512
970513AG2-328 GEN
Solar/Wind Harmer
4.559
970517AG2-330 GEN
Solar/Wind Harmer
27.357
247643Z2-116 C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
6.732
945111AF1-176 GEN
Solar/Wind Harmer
8.323
944531AF1-118 GEN
Solar/Wind Harmer
45.595
24441205WTRV SLR C
Solar/Wind Harmer
0
274772LINCOLN ;3U
Adder
11.972
274724RIVER EC ;11
Adder
24.913
274752CRETE EC ;2U
Adder
11.58
274753CRETE EC ;3U
Adder
11.58
270391AF1-285 GEN3
Solar/Wind Harmer
0.651
970707AG2-453 GEN
Solar/Wind Harmer
31.724
274802UNIV PARK;5U
Adder
8.1
274826FISK ;BP
Adder
15.205
274800UNIV PARK;3U
Adder
8.089
972038AH1-567 GEN2
Adder
0.506
276806AD2-047 C O1
Solar/Wind Harmer
5.485
970941AG2-585 GEN
Solar/Wind Harmer
12.1
972228AH1-698 GEN2
Adder
5.135
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.062
276897AD1-100 C
Solar/Wind Harmer
0.013
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
40.714
274730ELWOOD EC;6P
Adder
22.567
274734ELWOOD EC;8P
Adder
22.567
274736ELWOOD EC;9P
Adder
22.567
274729ELWOOD EC;1P
Adder
22.566
276893AG1-478 C
Solar/Wind Harmer
0.379
270535AF1-215 GEN1
Solar/Wind Harmer
0.012
943121AE2-341 GEN
Solar/Wind Harmer
15.96
943591AF1-030 GEN
Solar/Wind Harmer
10.614
964401AG1-302 GEN
Solar/Wind Harmer
0.001
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
24.169
270491AE1-102 GEN2
Solar/Wind Harmer
1.214
270485AE1-090_GEN
Solar/Wind Harmer
0.001
276805AD2-038 GEN
Solar/Wind Harmer
0.003
274872LEEDK;1U
Solar/Wind Harmer
0.341
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.982
274855GSG-6 ;RU
Solar/Wind Harmer
0.337
274850MENDOTA H;RU
Solar/Wind Harmer
0.108
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.165
959091AF2-200 GEN
Solar/Wind Harmer
18.285
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
2.856
970571AG2-364 GEN
Solar/Wind Harmer
18.064
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
11.947
274767LEE CO EC;8U
Adder
11.806
276157O29GEN1
Solar/Wind Harmer
1.431
270258AD1-119 GEN
Solar/Wind Harmer
0.002
274878BISHOP HL;2U
Solar/Wind Harmer
0.295
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
8.785
270404AC1-167 GEN
Solar/Wind Harmer
0.004
942111AE2-223 GEN
Solar/Wind Harmer
2.831
965931AG1-462 GEN
Solar/Wind Harmer
21.861
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
25.685
959611AF2-252 GEN
Solar/Wind Harmer
2.854
971617AH1-308 GEN
Solar/Wind Harmer
7.03
247642Z2-115 C
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
0.914
970291AG2-192 GEN
Solar/Wind Harmer
0.831
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
3.74
276668AB2-070 GEN1
Solar/Wind Harmer
0.295
958821AF2-173 GEN
Solar/Wind Harmer
11.2
270004AE1-209 GEN
Solar/Wind Harmer
1.733
276621W2-048 GEN
Solar/Wind Harmer
0.401
276838X2-022 GEN2
Solar/Wind Harmer
0.448
946031AF1-268 GEN
Solar/Wind Harmer
7.422
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
11.672
942481AE2-261 GEN
Solar/Wind Harmer
22.986
24728705AND G3
Adder
7.82
24728505AND G1
Adder
3.739
970615AG2-402 GEN
50/50
3.512
247620Y3-023
50/50
0.722
270102X2-052 ST
50/50
2.354
270100X2-052 CT1
50/50
2.169
270101X2-052 CT2
50/50
2.169
270471AD2-092_GEN
Solar/Wind Harmer
0.009
970611AG2-400 GEN
Solar/Wind Harmer
10.537
970627AG2-408 GEN
Solar/Wind Harmer
3.161
970321AG2-212 GEN
Solar/Wind Harmer
4.559
270216AD2-079_GEN
Solar/Wind Harmer
0.002
957891AF2-083 GEN
Solar/Wind Harmer
0.001
270526AF1-158 GEN
Solar/Wind Harmer
0.013
24441505OLIV SLR
Solar/Wind Harmer
0
961051AF2-396 GEN
Solar/Wind Harmer
20.46
961051AF2-396 GEN
Solar/Wind Harmer
13.64
965681AG1-436 GEN
Solar/Wind Harmer
12.752
965791AG1-447 GEN
Solar/Wind Harmer
9.351
274770LINCOLN ;1U
Adder
11.972
274771LINCOLN ;2U
Adder
11.972
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
274808UNIV PK N;4U
Adder
6.965
274803UNIV PARK;6U
Adder
8.1
274888KELLY CRK;1U
Solar/Wind Harmer
0.568
274887GEN-1.85
Solar/Wind Harmer
0.255
276843GEN-1.7
Solar/Wind Harmer
0.313
958011AF2-095 GEN
Solar/Wind Harmer
13.939
972259AH1-714 GEN
Adder
26.463
274674JOLIET 9 ;6U
Adder
21.154
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
971573AH1-285 GEN
Solar/Wind Harmer
1.764
958481AF2-142 GEN
Solar/Wind Harmer
14.096
274695ROCKY RD ;2P
Adder
14.996
274693ROCKY RD ;1P
Adder
14.848
274697ROCKY RD ;3P
Adder
4.074
274696ROCKY RD ;4P
Adder
15.349
274861TOP CROP ;1U
Solar/Wind Harmer
0.003
274862TOP CROP ;2U
Solar/Wind Harmer
1.271
944541AF1-119 GEN
Solar/Wind Harmer
0.629
960971AF2-388 GEN
Solar/Wind Harmer
5.509
274683WAUKEGAN ;8U
Adder
28.303
274683WAUKEGAN ;8U
Adder
23.858
246938BC-WTG3
Solar/Wind Harmer
0.338
246937BC-WTG2
Solar/Wind Harmer
0.379
962691AG1-118 GEN
Solar/Wind Harmer
27.992
970921AG2-575 GEN
Solar/Wind Harmer
9.308
970921AG2-575 GEN
Solar/Wind Harmer
3.103
958491AF2-143 GEN
Solar/Wind Harmer
13.931
274879MINONK ;1U
Solar/Wind Harmer
0.39
942991AE2-321 GEN
Solar/Wind Harmer
10.32
971333AH1-146 GEN
Solar/Wind Harmer
18.389
971335AH1-147 GEN
Solar/Wind Harmer
18.389
971341AH1-150 GEN
Solar/Wind Harmer
18.285
971343AH1-151 GEN
Solar/Wind Harmer
18.285
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
942221AE2-234 GEN
Solar/Wind Harmer
0.046
274856ECOGROVE ;U1
Solar/Wind Harmer
0.213
276611AD2-172 GEN
Solar/Wind Harmer
0.002
938861AE1-114 GEN
Solar/Wind Harmer
5.096
274764LEE CO EC;5U
Adder
11.975
274765LEE CO EC;6U
Adder
11.975
274762LEE CO EC;3U
Adder
11.947
274763LEE CO EC;4U
Adder
11.834
276603SUBLETTE C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
270007AE1-245 C
Solar/Wind Harmer
0.002
972267AH1-718 GEN
Adder
5.295
276741O09 GEN1
Solar/Wind Harmer
0.315
276708O09 GEN2
Solar/Wind Harmer
0.315
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.347
276646AC1-214 GEN2
Solar/Wind Harmer
0.347
970623AG2-406 GEN
Solar/Wind Harmer
1.614
276782AC1-033 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
2.854
966841AG1-555 GEN
Solar/Wind Harmer
0.959
270599AE1-208 GEN
Solar/Wind Harmer
7.715
270031AE2-169
Solar/Wind Harmer
4.629
971613AH1-306 GEN
Solar/Wind Harmer
3.931
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
970241AG2-163 GEN
Solar/Wind Harmer
4.69
960441AF2-335 GEN
Solar/Wind Harmer
7.897
970825AG2-519 GEN
Solar/Wind Harmer
8.719
964611AG1-324 GEN
Solar/Wind Harmer
0.584
270201AC2-176 GEN
Solar/Wind Harmer
0.001
970621AG2-405 GEN
Solar/Wind Harmer
1.413
247621Y3-024
Adder
0.262
276916AD2-100_GEN
Solar/Wind Harmer
13.41
276911AD2-131_GEN
Solar/Wind Harmer
0.883
944201AF1-088_MTX
Adder
85.667
NYPJM->LTFIMP_NY
CLTF
2.99
LGEELTFEXP_LGEE->PJM
CLTF
4.155
WECLTFEXP_WEC->PJM
CLTF
4.968
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.286
AG2-052LTFEXP_AG2-052->PJM
LTF
0.312
AH1-155LTFEXP_AH1-155->PJM
LTF
0.469
CBM West 2LTFEXP_CBM-W2->PJM
CBM
96.989
LAGNLTFEXP_LAGN->PJM
CLTF
11.144
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.328
TVALTFEXP_TVA->PJM
CLTF
4.56
CBM West 1LTFEXP_CBM-W1->PJM
CBM
161.402
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.132
MECLTFEXP_MEC->PJM
CLTF
18.394
SIGELTFEXP_SIGE->PJM
CLTF
0.399

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o Base Case


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.73 %
Rating:4047.0 MVA
Rating Type:A
MVA to Mitigate:4643.02
MW Contribution:47.64
Bus #Bus NameTypeMW Contribution
971599AH1-298 GEN
50/50
10.558
270144AC1-141 ST1_
50/50
2.306
24643105BUCHANAN
50/50
0.014
24653605MOTTVILLE
50/50
0.004
274775LINCOLN ;6U
50/50
9.593
274776LINCOLN ;7U
50/50
9.593
274777LINCOLN ;8U
50/50
9.593
962771AG1-126 GEN
Solar/Wind Harmer
74.603
971347AH1-153 GEN
Solar/Wind Harmer
12.013
270071AF1-092 GEN
Solar/Wind Harmer
14.717
971771AH1-392 GEN
Solar/Wind Harmer
7.604
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971769AH1-391 GEN
Solar/Wind Harmer
8.444
971619AH1-309 GEN
Solar/Wind Harmer
3.384
274814UNIV PK N;0U
Adder
5.324
274807UNIV PK N;3U
Adder
5.313
274805UNIV PK N;1U
Adder
5.29
274811UNIV PK N;7U
Adder
5.278
274827FISK ;RP
Adder
8.149
972037AH1-567 GEN1
Adder
0.192
960591AF2-350 GEN
Solar/Wind Harmer
7.323
972227AH1-698 GEN1
Adder
2.737
274687WILL CNTY;4U
Adder
29.176
274687WILL CNTY;4U
Adder
29.176
274675JOLIET 29;7U
Adder
32.008
274675JOLIET 29;7U
Adder
30.865
24729505KEY G4
Adder
6.759
274731ELWOOD EC;2P
Adder
17.114
274733ELWOOD EC;3P
Adder
17.114
274735ELWOOD EC;4P
Adder
17.114
274728ELWOOD EC;5P
Adder
17.114
970833AG2-524 GEN
Solar/Wind Harmer
7.985
970833AG2-524 GEN
Solar/Wind Harmer
5.323
274746AC1-111 G10
Adder
5.788
274744AC1-111 GEN8
Adder
5.788
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
971177AH1-047 GEN
Solar/Wind Harmer
4.355
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.417
276882AE2-255 GEN
Solar/Wind Harmer
0.825
971675AH1-338 GEN
Solar/Wind Harmer
2.746
971411AH1-196 GEN
Solar/Wind Harmer
10.56
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
971171AH1-044 GEN
Solar/Wind Harmer
14.009
274823ROCKFORD ;21
Adder
19.51
971611AH1-305 GEN
Solar/Wind Harmer
4.152
276612AE2-035 GEN
Solar/Wind Harmer
0.002
926823AC1-168 GEN
Solar/Wind Harmer
1.178
970169AG2-114 GEN
Solar/Wind Harmer
6.92
971681AH1-341 GEN
Solar/Wind Harmer
11.133
961011AF2-392 GEN
Solar/Wind Harmer
4.021
957751AF2-069 GEN
Solar/Wind Harmer
0.225
971549AH1-272 GEN
Solar/Wind Harmer
14.034
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
965101AG1-375 GEN
Solar/Wind Harmer
6.746
965041AG1-368 GEN
Solar/Wind Harmer
6.733
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.06
941731AE2-173 GEN
Solar/Wind Harmer
5.603
946321AF1-296 GEN
Solar/Wind Harmer
3.744
963791AG1-232 GEN
Solar/Wind Harmer
8.989
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
945581AF1-223 GEN
Solar/Wind Harmer
0
965051AG1-369 GEN
Solar/Wind Harmer
3.241
963841AG1-237 GEN
Solar/Wind Harmer
2.776
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.231
276848AB2-070 GEN3
Solar/Wind Harmer
0.23
970289AG2-191 GEN
Solar/Wind Harmer
1.184
971609AH1-304 GEN
Solar/Wind Harmer
1.011
270594AE1-207 GEN
Solar/Wind Harmer
6.856
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.765
270284AF1-227 GEN1
Solar/Wind Harmer
0.008
270286AF1-227 GEN2
Solar/Wind Harmer
0.003
270287AF1-227 GEN3
Solar/Wind Harmer
0.003
270054AF2-122 C O1
Solar/Wind Helper
1.65
270142AC1-141 CT1_
50/50
2.603
24641605TWIN BRNCH
50/50
0.019
24344005CKG1
50/50
7.096
24642205MAYFLWER
50/50
0.728
274772LINCOLN ;3U
50/50
9.593
970153AG2-106 GEN
Solar/Wind Harmer
47.639
970349AG2-230 GEN
Solar/Wind Harmer
12.013
970513AG2-328 GEN
Solar/Wind Harmer
3.44
970517AG2-330 GEN
Solar/Wind Harmer
20.64
270043AE2-236 GEN
Solar/Wind Harmer
5.033
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
6.073
970031AG2-029 GEN
Solar/Wind Harmer
4.844
944531AF1-118 GEN
Solar/Wind Harmer
33.218
274724RIVER EC ;11
Adder
18.771
274752CRETE EC ;2U
Adder
8.717
274753CRETE EC ;3U
Adder
8.717
959331AF2-224 GEN
Solar/Wind Harmer
5.157
965021AG1-366 GEN
Solar/Wind Harmer
2.455
970707AG2-453 GEN
Solar/Wind Harmer
24.03
274826FISK ;BP
Adder
11.498
274802UNIV PARK;5U
Adder
6.123
276806AD2-047 C O1
Solar/Wind Harmer
4.15
970941AG2-585 GEN
Solar/Wind Harmer
9.154
274800UNIV PARK;3U
Adder
6.118
972038AH1-567 GEN2
Adder
0.383
972228AH1-698 GEN2
Adder
3.887
24441205WTRV SLR C
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
0.01
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
30.865
274729ELWOOD EC;1P
Adder
17.114
274730ELWOOD EC;6P
Adder
17.114
274734ELWOOD EC;8P
Adder
17.114
274736ELWOOD EC;9P
Adder
17.114
276893AG1-478 C
Solar/Wind Harmer
0.288
943121AE2-341 GEN
Solar/Wind Harmer
12.132
943591AF1-030 GEN
Solar/Wind Harmer
8.068
247604X1-042
Adder
0.432
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
18.416
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.26
276805AD2-038 GEN
Solar/Wind Harmer
0.002
24344105CKG2
50/50
8.939
270143AC1-141 CT2_
50/50
2.603
24639705ELKHART HY
50/50
0.176
970521AG2-332 GEN
50/50
12.519
274773LINCOLN ;4U
50/50
9.593
274774LINCOLN ;5U
50/50
9.593
962761AG1-125 GEN
Solar/Wind Harmer
74.603
970149AG2-104 GEN
Solar/Wind Harmer
80.573
970155AG2-107 GEN
Solar/Wind Harmer
47.639
970245AG2-165 GEN
Solar/Wind Harmer
3.44
270505AE1-170 C O1
Solar/Wind Harmer
7.896
270063AE2-323 C
Solar/Wind Harmer
0.006
945111AF1-176 GEN
Solar/Wind Harmer
13.37
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
3.886
274723RIVER EC ;12
Adder
18.99
274751CRETE EC ;1U
Adder
8.717
274754CRETE EC ;4U
Adder
8.717
276164X3-005 C
Solar/Wind Harmer
0
965011AG1-365 GEN
Solar/Wind Harmer
7.366
274812UNIV PK N;8U
Adder
5.278
970373AG2-245 GEN
Solar/Wind Harmer
15.386
276776AD2-060 GEN
Solar/Wind Harmer
0.765
274801UNIV PARK;4U
Adder
6.118
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
32.008
274674JOLIET 9 ;6U
Adder
16.042
274732ELWOOD EC;7P
Adder
17.114
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
5.788
270055AF2-134 C O1
Solar/Wind Harmer
0.006
276691AA1-018 GEN1
Solar/Wind Harmer
0.866
274682WAUKEGAN ;7U
Adder
18.416
274828WAUKEGAN ;BP
Adder
11.308
958381AF2-132 GEN
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
6.763
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.233
274872LEEDK;1U
Solar/Wind Harmer
0.004
939401AE1-172 GEN
Solar/Wind Harmer
5.304
276901AD2-066 C O1
Solar/Wind Harmer
0.007
971997AH1-543 GEN
Solar/Wind Harmer
3.701
276861AD2-134 GEN
Solar/Wind Harmer
0.126
957471AF2-041 GEN
Solar/Wind Harmer
21.014
959081AF2-199 GEN
Solar/Wind Harmer
7.005
971067AG2-660 GEN
Solar/Wind Harmer
2.335
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
274822ROCKFORD ;11
Adder
19.652
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.717
972235AH1-702 GEN1
Adder
2.519
970819AG2-516 GEN
Solar/Wind Harmer
8.346
971475AH1-234 GEN
Solar/Wind Harmer
3.368
970569AG2-363 GEN
Solar/Wind Harmer
20.788
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
9.191
274766LEE CO EC;7U
Adder
9.083
965651AG1-433 GEN
Solar/Wind Harmer
2.017
276158O29GEN2
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.228
24721705FLATG2
Adder
19.64
24791305MDL-5G
Solar/Wind Harmer
0.001
958861AF2-177 GEN
Solar/Wind Harmer
2.923
276726Z2-087_GEN
Solar/Wind Harmer
0.002
939741AE1-205 GEN
Solar/Wind Harmer
9.413
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.002
944231AF1-091 GEN
Solar/Wind Harmer
1.739
945371AF1-202 GEN
Solar/Wind Harmer
0.001
247521TR3_G114
Solar/Wind Harmer
0.237
270246TR4_N_V150
Solar/Wind Harmer
0.042
972175AH1-670 GEN
Solar/Wind Harmer
5.355
270349AD2-093_GEN
Solar/Wind Harmer
0.005
24695305TIMB G C
Solar/Wind Harmer
0.002
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
2.462
963741AG1-226 GEN
Solar/Wind Harmer
14.839
276615X2-022 GEN
Solar/Wind Harmer
0.066
970291AG2-192 GEN
Solar/Wind Harmer
0.81
965421AG1-410 GEN
Solar/Wind Harmer
18.496
270032AE2-172
Solar/Wind Harmer
4.081
965911AG1-460 GEN
Solar/Wind Harmer
1.218
246936BC-WTG1
Solar/Wind Harmer
0.245
270489AE1-102 GEN1
Solar/Wind Harmer
0.785
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.751
274855GSG-6 ;RU
Solar/Wind Harmer
0.258
274850MENDOTA H;RU
Solar/Wind Harmer
0.083
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.126
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
959091AF2-200 GEN
Solar/Wind Harmer
14.009
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
2.191
970571AG2-364 GEN
Solar/Wind Harmer
13.859
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
9.191
274767LEE CO EC;8U
Adder
9.083
276157O29GEN1
Solar/Wind Harmer
1.104
274878BISHOP HL;2U
Solar/Wind Harmer
0.228
24721905FLATG4
Adder
19.64
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.747
942111AE2-223 GEN
Solar/Wind Harmer
2.185
965931AG1-462 GEN
Solar/Wind Harmer
16.976
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
19.897
959611AF2-252 GEN
Solar/Wind Harmer
2.211
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.042
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
2.93
276668AB2-070 GEN1
Solar/Wind Harmer
0.231
247642Z2-115 C
Solar/Wind Harmer
0.003
276621W2-048 GEN
Solar/Wind Harmer
0.316
276838X2-022 GEN2
Solar/Wind Harmer
0.352
970289AG2-191 GEN
Solar/Wind Harmer
0.686
970291AG2-192 GEN
Solar/Wind Harmer
0.623
942481AE2-261 GEN
Solar/Wind Harmer
18.215
270491AE1-102 GEN2
Solar/Wind Harmer
0.785
270102X2-052 ST
50/50
1.747
270100X2-052 CT1
50/50
1.61
270101X2-052 CT2
50/50
1.61
247620Y3-023
50/50
0.525
274770LINCOLN ;1U
50/50
9.593
274771LINCOLN ;2U
50/50
9.593
970321AG2-212 GEN
Solar/Wind Harmer
3.44
270216AD2-079_GEN
Solar/Wind Harmer
0.001
965681AG1-436 GEN
Solar/Wind Harmer
9.481
965791AG1-447 GEN
Solar/Wind Harmer
6.953
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
14.924
961051AF2-396 GEN
Solar/Wind Harmer
9.95
970611AG2-400 GEN
Solar/Wind Harmer
7.366
970627AG2-408 GEN
Solar/Wind Harmer
2.21
274808UNIV PK N;4U
Adder
5.255
972259AH1-714 GEN
Adder
20.044
274803UNIV PARK;6U
Adder
6.123
274888KELLY CRK;1U
Solar/Wind Harmer
0.43
274887GEN-1.85
Solar/Wind Harmer
0.193
276843GEN-1.7
Solar/Wind Harmer
0.237
958011AF2-095 GEN
Solar/Wind Harmer
10.545
274674JOLIET 9 ;6U
Adder
16.042
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
971573AH1-285 GEN
Solar/Wind Harmer
1.342
274695ROCKY RD ;2P
Adder
11.425
274693ROCKY RD ;1P
Adder
11.312
274697ROCKY RD ;3P
Adder
3.104
274696ROCKY RD ;4P
Adder
11.694
958481AF2-142 GEN
Solar/Wind Harmer
10.727
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.967
274683WAUKEGAN ;8U
Adder
21.572
274683WAUKEGAN ;8U
Adder
18.184
962691AG1-118 GEN
Solar/Wind Harmer
21.36
970921AG2-575 GEN
Solar/Wind Harmer
7.106
970921AG2-575 GEN
Solar/Wind Harmer
2.369
958491AF2-143 GEN
Solar/Wind Harmer
10.627
942991AE2-321 GEN
Solar/Wind Harmer
7.889
274879MINONK ;1U
Solar/Wind Harmer
0.298
971333AH1-146 GEN
Solar/Wind Harmer
14.073
971335AH1-147 GEN
Solar/Wind Harmer
14.073
971341AH1-150 GEN
Solar/Wind Harmer
14.009
971343AH1-151 GEN
Solar/Wind Harmer
14.009
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
274856ECOGROVE ;U1
Solar/Wind Harmer
0.164
276611AD2-172 GEN
Solar/Wind Harmer
0.002
938861AE1-114 GEN
Solar/Wind Harmer
3.917
274764LEE CO EC;5U
Adder
9.213
274765LEE CO EC;6U
Adder
9.213
274762LEE CO EC;3U
Adder
9.191
274763LEE CO EC;4U
Adder
9.105
276603SUBLETTE C
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.461
960971AF2-388 GEN
Solar/Wind Harmer
4.033
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
972267AH1-718 GEN
Adder
4.082
276741O09 GEN1
Solar/Wind Harmer
0.243
276708O09 GEN2
Solar/Wind Harmer
0.243
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.268
276646AC1-214 GEN2
Solar/Wind Harmer
0.268
276782AC1-033 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
2.211
942221AE2-234 GEN
Solar/Wind Harmer
0.033
966841AG1-555 GEN
Solar/Wind Harmer
0.741
270471AD2-092_GEN
Solar/Wind Harmer
0.005
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
970241AG2-163 GEN
Solar/Wind Harmer
3.657
270599AE1-208 GEN
Solar/Wind Harmer
5.676
270031AE2-169
Solar/Wind Harmer
3.406
971613AH1-306 GEN
Solar/Wind Harmer
2.938
276916AD2-100_GEN
Solar/Wind Harmer
12.71
276911AD2-131_GEN
Solar/Wind Harmer
0.837
246938BC-WTG3
Solar/Wind Harmer
0.219
246937BC-WTG2
Solar/Wind Harmer
0.245
NYPJM->LTFIMP_NY
CLTF
2.589
LGEELTFEXP_LGEE->PJM
CLTF
3.659
WECLTFEXP_WEC->PJM
CLTF
3.814
AG2-052LTFEXP_AG2-052->PJM
LTF
0.236
AH1-155LTFEXP_AH1-155->PJM
LTF
0.355
CPLELTFEXP_CPLE->PJM
CLTF
1.429
CBM West 2LTFEXP_CBM-W2->PJM
CBM
87.023
LAGNLTFEXP_LAGN->PJM
CLTF
11.239
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.669
TVALTFEXP_TVA->PJM
CLTF
5.062
CBM West 1LTFEXP_CBM-W1->PJM
CBM
120.019
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.189
MECLTFEXP_MEC->PJM
CLTF
14.69
SIGELTFEXP_SIGE->PJM
CLTF
0.339

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AEP_P7-1_#10944___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P7-1_#10944___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:111.6 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5101.3
MW Contribution:38.67
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
2.636
24641605TWIN BRNCH
50/50
0.019
24344005CKG1
50/50
7.184
274772LINCOLN ;3U
50/50
7.2
24642205MAYFLWER
50/50
0.738
970153AG2-106 GEN
Solar/Wind Harmer
38.674
970349AG2-230 GEN
Solar/Wind Harmer
17.476
970513AG2-328 GEN
Solar/Wind Harmer
20.738
970517AG2-330 GEN
Solar/Wind Harmer
18.809
270043AE2-236 GEN
Solar/Wind Harmer
6.251
247643Z2-116 C
Solar/Wind Harmer
0.077
945111AF1-176 GEN
Solar/Wind Harmer
6.147
274724RIVER EC ;11
Adder
19.173
944531AF1-118 GEN
Solar/Wind Harmer
37.878
972231SS25-0005
Solar/Wind Harmer
10.253
972181SS23-001
Solar/Wind Harmer
6.408
274752CRETE EC ;2U
Adder
5.281
274753CRETE EC ;3U
Adder
5.281
970031AG2-029 GEN
Solar/Wind Harmer
32.374
970707AG2-453 GEN
Solar/Wind Harmer
30.198
274826FISK ;BP
Adder
11.757
274802UNIV PARK;5U
Adder
6.261
276772AC2-154 GEN
Solar/Wind Harmer
2.994
276806AD2-047 C O1
Solar/Wind Harmer
11.484
970941AG2-585 GEN
Solar/Wind Harmer
13.419
972228AH1-698 GEN2
Adder
3.976
274800UNIV PARK;3U
Adder
6.257
972038AH1-567 GEN2
Adder
0.392
276897AD1-100 C
Solar/Wind Harmer
31.058
939351AE1-166 GEN
Solar/Wind Harmer
6.346
274676JOLIET 29;8U
Adder
31.584
274729ELWOOD EC;1P
Adder
17.516
274730ELWOOD EC;6P
Adder
17.516
274734ELWOOD EC;8P
Adder
17.516
274736ELWOOD EC;9P
Adder
17.516
276893AG1-478 C
Solar/Wind Harmer
0.445
943121AE2-341 GEN
Solar/Wind Harmer
15.932
943591AF1-030 GEN
Solar/Wind Harmer
10.621
959331AF2-224 GEN
Solar/Wind Harmer
10.607
965021AG1-366 GEN
Solar/Wind Harmer
2.467
24441205WTRV SLR C
Solar/Wind Harmer
0.143
270535AF1-215 GEN1
Solar/Wind Harmer
4.803
24721905FLATG4
Adder
21.327
276694AA1-018 GEN2
Solar/Wind Harmer
6.628
274682WAUKEGAN ;7U
Adder
18.874
247604X1-042
Adder
0.436
964401AG1-302 GEN
Solar/Wind Harmer
9.472
274872LEEDK;1U
Solar/Wind Harmer
0.267
276805AD2-038 GEN
Solar/Wind Harmer
5.342
276799AD1-013 GEN
Solar/Wind Harmer
2.29
946671AF1-331 GEN
Solar/Wind Harmer
0.434
274855GSG-6 ;RU
Solar/Wind Harmer
3.824
274850MENDOTA H;RU
Solar/Wind Harmer
2.659
276602WESTBROOK C
Solar/Wind Harmer
2.201
276863AD2-134 GEN
Solar/Wind Harmer
1.849
959141AF2-205 GEN
Solar/Wind Harmer
6.241
972236AH1-702 GEN2
Adder
2.25
274760LEE CO EC;1U
Adder
9.448
274767LEE CO EC;8U
Adder
9.337
959091AF2-200 GEN
Solar/Wind Harmer
0.659
270102X2-052 ST
50/50
1.777
270100X2-052 CT1
50/50
1.637
270101X2-052 CT2
50/50
1.637
274770LINCOLN ;1U
50/50
7.2
274771LINCOLN ;2U
50/50
7.2
247620Y3-023
50/50
0.531
970321AG2-212 GEN
Solar/Wind Harmer
20.738
965681AG1-436 GEN
Solar/Wind Harmer
13.825
965791AG1-447 GEN
Solar/Wind Harmer
7.073
270216AD2-079_GEN
Solar/Wind Harmer
0.668
270526AF1-158 GEN
Solar/Wind Harmer
5.006
24441505OLIV SLR
Solar/Wind Harmer
0.147
957891AF2-083 GEN
Solar/Wind Harmer
3.677
960981AF2-389 GEN
Solar/Wind Harmer
1.648
961051AF2-396 GEN
Solar/Wind Harmer
17.18
961051AF2-396 GEN
Solar/Wind Harmer
7.99
274808UNIV PK N;4U
Adder
5.37
972259AH1-714 GEN
Adder
20.504
274803UNIV PARK;6U
Adder
6.261
274888KELLY CRK;1U
Solar/Wind Harmer
6.338
274887GEN-1.85
Solar/Wind Harmer
5.722
276843GEN-1.7
Solar/Wind Harmer
0.616
958011AF2-095 GEN
Solar/Wind Harmer
15.458
274674JOLIET 9 ;6U
Adder
16.418
274847GR RIDGE ;BU
Solar/Wind Harmer
5.386
970611AG2-400 GEN
Solar/Wind Harmer
10.607
971573AH1-285 GEN
Solar/Wind Harmer
9.097
274695ROCKY RD ;2P
Adder
11.708
274693ROCKY RD ;1P
Adder
11.593
274697ROCKY RD ;3P
Adder
3.181
274696ROCKY RD ;4P
Adder
11.984
958481AF2-142 GEN
Solar/Wind Harmer
15.755
274861TOP CROP ;1U
Solar/Wind Harmer
6.362
274862TOP CROP ;2U
Solar/Wind Harmer
5.313
274683WAUKEGAN ;8U
Adder
22.11
274683WAUKEGAN ;8U
Adder
18.638
962691AG1-118 GEN
Solar/Wind Harmer
31.39
970921AG2-575 GEN
Solar/Wind Harmer
10.445
970921AG2-575 GEN
Solar/Wind Harmer
2.429
958491AF2-143 GEN
Solar/Wind Harmer
15.621
942991AE2-321 GEN
Solar/Wind Harmer
10.388
274879MINONK ;1U
Solar/Wind Harmer
7.005
971333AH1-146 GEN
Solar/Wind Harmer
20.7
971335AH1-147 GEN
Solar/Wind Harmer
20.7
274764LEE CO EC;5U
Adder
9.47
274765LEE CO EC;6U
Adder
9.47
274762LEE CO EC;3U
Adder
9.448
274763LEE CO EC;4U
Adder
9.359
972267AH1-718 GEN
Adder
4.199
971341AH1-150 GEN
Solar/Wind Harmer
0.659
971343AH1-151 GEN
Solar/Wind Harmer
0.659
971599AH1-298 GEN
50/50
10.665
270144AC1-141 ST1_
50/50
2.335
274775LINCOLN ;6U
50/50
7.2
274776LINCOLN ;7U
50/50
7.2
274777LINCOLN ;8U
50/50
7.2
24643105BUCHANAN
50/50
0.014
24653605MOTTVILLE
50/50
0.004
962771AG1-126 GEN
Solar/Wind Harmer
88.693
971347AH1-153 GEN
Solar/Wind Harmer
17.476
270071AF1-092 GEN
Solar/Wind Harmer
16.765
960681AF2-359 GEN
Solar/Wind Harmer
4.178
971771AH1-392 GEN
Solar/Wind Harmer
9.947
971769AH1-391 GEN
Solar/Wind Harmer
11.009
274814UNIV PK N;0U
Adder
5.441
274807UNIV PK N;3U
Adder
5.429
274805UNIV PK N;1U
Adder
5.405
274811UNIV PK N;7U
Adder
5.394
274827FISK ;RP
Adder
8.332
972037AH1-567 GEN1
Adder
0.197
960591AF2-350 GEN
Solar/Wind Harmer
10.735
972227AH1-698 GEN1
Adder
2.799
944161AF1-084 GEN
Solar/Wind Harmer
2.371
274687WILL CNTY;4U
Adder
29.852
274687WILL CNTY;4U
Adder
29.852
274675JOLIET 29;7U
Adder
32.754
274675JOLIET 29;7U
Adder
31.584
274731ELWOOD EC;2P
Adder
17.516
274733ELWOOD EC;3P
Adder
17.516
274735ELWOOD EC;4P
Adder
17.516
274728ELWOOD EC;5P
Adder
17.516
970833AG2-524 GEN
Solar/Wind Harmer
9.299
970833AG2-524 GEN
Solar/Wind Harmer
4.325
24729505KEY G4
Adder
6.895
274746AC1-111 G10
Adder
5.928
274744AC1-111 GEN8
Adder
5.928
270536AF1-215 GEN2
Solar/Wind Harmer
4.803
971177AH1-047 GEN
Solar/Wind Harmer
6.086
276868AE1-113 GEN
Solar/Wind Harmer
10.506
276882AE2-255 GEN
Solar/Wind Harmer
3.502
958391AF2-133 GEN
Solar/Wind Harmer
9.41
971675AH1-338 GEN
Solar/Wind Harmer
18.64
971411AH1-196 GEN
Solar/Wind Harmer
15.533
274863CRW1-WTG
Solar/Wind Harmer
5.758
274864CRW2-WTG
Solar/Wind Harmer
5.758
274823ROCKFORD ;21
Adder
20.032
270054AF2-122 C O1
Solar/Wind Helper
1.787
971171AH1-044 GEN
Solar/Wind Harmer
0.659
24344105CKG2
50/50
9.068
270143AC1-141 CT2_
50/50
2.636
274773LINCOLN ;4U
50/50
7.2
274774LINCOLN ;5U
50/50
7.2
24639705ELKHART HY
50/50
0.178
970521AG2-332 GEN
50/50
12.672
962761AG1-125 GEN
Solar/Wind Harmer
88.693
970149AG2-104 GEN
Solar/Wind Harmer
109.536
970155AG2-107 GEN
Solar/Wind Harmer
38.674
970245AG2-165 GEN
Solar/Wind Harmer
20.738
972207SS24-0001
Solar/Wind Harmer
24.126
270505AE1-170 C O1
Solar/Wind Harmer
16.366
945111AF1-176 GEN
Solar/Wind Harmer
19.395
270063AE2-323 C
Solar/Wind Harmer
2.395
274723RIVER EC ;12
Adder
19.397
274751CRETE EC ;1U
Adder
5.281
274754CRETE EC ;4U
Adder
5.281
276164X3-005 C
Solar/Wind Harmer
0.759
270449AD2-020 GEN
Solar/Wind Harmer
3.026
943021AE2-325 GEN
Solar/Wind Harmer
3.932
274812UNIV PK N;8U
Adder
5.394
276776AD2-060 GEN
Solar/Wind Harmer
0.454
274801UNIV PARK;4U
Adder
6.257
970373AG2-245 GEN
Solar/Wind Harmer
22.515
941551AE2-152 GEN
Solar/Wind Harmer
4.854
274676JOLIET 29;8U
Adder
32.754
274674JOLIET 9 ;6U
Adder
16.418
274732ELWOOD EC;7P
Adder
17.516
274871GR RIDGE ;2U
Solar/Wind Harmer
8.188
965011AG1-365 GEN
Solar/Wind Harmer
10.607
274745AC1-111 GEN9
Adder
5.928
270055AF2-134 C O1
Solar/Wind Harmer
3.202
24721705FLATG2
Adder
21.327
276691AA1-018 GEN1
Solar/Wind Harmer
0.489
274682WAUKEGAN ;7U
Adder
18.874
274828WAUKEGAN ;BP
Adder
11.59
960751AF2-366 GEN
Solar/Wind Harmer
2.997
962781AG1-127 GEN
Solar/Wind Harmer
9.933
958381AF2-132 GEN
Solar/Wind Harmer
9.472
274872LEEDK;1U
Solar/Wind Harmer
8.565
964861AG1-349 GEN
Solar/Wind Harmer
8.196
971917AH1-482 GEN
Solar/Wind Harmer
9.458
939401AE1-172 GEN
Solar/Wind Harmer
14.53
276901AD2-066 C O1
Solar/Wind Harmer
3.656
971997AH1-543 GEN
Solar/Wind Harmer
16.328
276861AD2-134 GEN
Solar/Wind Harmer
1.849
274822ROCKFORD ;11
Adder
20.179
972235AH1-702 GEN1
Adder
2.587
274761LEE CO EC;2U
Adder
9.448
274766LEE CO EC;7U
Adder
9.337
957471AF2-041 GEN
Solar/Wind Harmer
0.989
959081AF2-199 GEN
Solar/Wind Harmer
0.33
971067AG2-660 GEN
Solar/Wind Harmer
0.077
NYPJM->LTFIMP_NY
CLTF
2.821
LGEELTFEXP_LGEE->PJM
CLTF
4.037
WECLTFEXP_WEC->PJM
CLTF
3.917
AG2-052LTFEXP_AG2-052->PJM
LTF
0.242
AH1-155LTFEXP_AH1-155->PJM
LTF
0.363
CPLELTFEXP_CPLE->PJM
CLTF
1.907
CBM West 2LTFEXP_CBM-W2->PJM
CBM
93.196
LAGNLTFEXP_LAGN->PJM
CLTF
12.245
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.222
TVALTFEXP_TVA->PJM
CLTF
5.61
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.675
CBM South 1LTFEXP_CBM-S1->PJM
CBM
21.249
MECLTFEXP_MEC->PJM
CLTF
15.261
SIGELTFEXP_SIGE->PJM
CLTF
0.364

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o ATSI_P7-1_TE-345-027A_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
ATSI_P7-1_TE-345-027A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:109.99 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5027.51
MW Contribution:38.89
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
2.761
24344005CKG1
50/50
7.535
24641605TWIN BRNCH
50/50
0.02
24642205MAYFLWER
50/50
0.772
944961AF1-161 GEN
50/50
3.302
270102X2-052 ST
50/50
1.844
270100X2-052 CT1
50/50
1.699
270101X2-052 CT2
50/50
1.699
247620Y3-023
50/50
0.557
970321AG2-212 GEN
Solar/Wind Harmer
21.268
270216AD2-079_GEN
Solar/Wind Harmer
0.699
270526AF1-158 GEN
Solar/Wind Harmer
5.214
965681AG1-436 GEN
Solar/Wind Harmer
14.336
965791AG1-447 GEN
Solar/Wind Harmer
7.335
24441505OLIV SLR
Solar/Wind Harmer
0.154
957891AF2-083 GEN
Solar/Wind Harmer
3.858
960981AF2-389 GEN
Solar/Wind Harmer
1.729
961051AF2-396 GEN
Solar/Wind Harmer
18.061
961051AF2-396 GEN
Solar/Wind Harmer
8.401
274770LINCOLN ;1U
Adder
6.975
274771LINCOLN ;2U
Adder
6.975
970611AG2-400 GEN
Solar/Wind Harmer
11.187
274808UNIV PK N;4U
Adder
5.528
274803UNIV PARK;6U
Adder
6.439
972259AH1-714 GEN
Adder
21.064
274888KELLY CRK;1U
Solar/Wind Harmer
6.515
274887GEN-1.85
Solar/Wind Harmer
5.882
276843GEN-1.7
Solar/Wind Harmer
0.633
958011AF2-095 GEN
Solar/Wind Harmer
15.891
274674JOLIET 9 ;6U
Adder
16.864
274847GR RIDGE ;BU
Solar/Wind Harmer
5.529
971573AH1-285 GEN
Solar/Wind Harmer
9.332
274695ROCKY RD ;2P
Adder
12.008
274693ROCKY RD ;1P
Adder
11.89
274697ROCKY RD ;3P
Adder
3.262
274696ROCKY RD ;4P
Adder
12.291
958481AF2-142 GEN
Solar/Wind Harmer
16.166
274861TOP CROP ;1U
Solar/Wind Harmer
6.528
274862TOP CROP ;2U
Solar/Wind Harmer
5.451
274683WAUKEGAN ;8U
Adder
22.675
274683WAUKEGAN ;8U
Adder
19.114
962691AG1-118 GEN
Solar/Wind Harmer
32.178
970921AG2-575 GEN
Solar/Wind Harmer
10.705
970921AG2-575 GEN
Solar/Wind Harmer
2.49
958491AF2-143 GEN
Solar/Wind Harmer
16.016
942991AE2-321 GEN
Solar/Wind Harmer
10.644
274879MINONK ;1U
Solar/Wind Harmer
7.179
971333AH1-146 GEN
Solar/Wind Harmer
21.203
971335AH1-147 GEN
Solar/Wind Harmer
21.203
274764LEE CO EC;5U
Adder
9.685
274765LEE CO EC;6U
Adder
9.685
274762LEE CO EC;3U
Adder
9.662
274763LEE CO EC;4U
Adder
9.571
972267AH1-718 GEN
Adder
4.292
971599AH1-298 GEN
50/50
11.057
270144AC1-141 ST1_
50/50
2.446
24643105BUCHANAN
50/50
0.015
24653605MOTTVILLE
50/50
0.004
962771AG1-126 GEN
Solar/Wind Harmer
89.197
971347AH1-153 GEN
Solar/Wind Harmer
18.111
270071AF1-092 GEN
Solar/Wind Harmer
17.338
971771AH1-392 GEN
Solar/Wind Harmer
10.383
960681AF2-359 GEN
Solar/Wind Harmer
4.333
971769AH1-391 GEN
Solar/Wind Harmer
11.46
944161AF1-084 GEN
Solar/Wind Harmer
2.498
274775LINCOLN ;6U
Adder
6.975
274776LINCOLN ;7U
Adder
6.975
274777LINCOLN ;8U
Adder
6.975
274814UNIV PK N;0U
Adder
5.601
274807UNIV PK N;3U
Adder
5.589
274805UNIV PK N;1U
Adder
5.565
274811UNIV PK N;7U
Adder
5.552
972037AH1-567 GEN1
Adder
0.202
274827FISK ;RP
Adder
8.568
960591AF2-350 GEN
Solar/Wind Harmer
11.036
972227AH1-698 GEN1
Adder
2.877
274687WILL CNTY;4U
Adder
30.673
274687WILL CNTY;4U
Adder
30.673
274675JOLIET 29;7U
Adder
33.649
274675JOLIET 29;7U
Adder
32.447
274731ELWOOD EC;2P
Adder
17.991
274733ELWOOD EC;3P
Adder
17.991
274735ELWOOD EC;4P
Adder
17.991
274728ELWOOD EC;5P
Adder
17.991
970833AG2-524 GEN
Solar/Wind Harmer
9.547
970833AG2-524 GEN
Solar/Wind Harmer
4.44
24729505KEY G4
Adder
7.093
270536AF1-215 GEN2
Solar/Wind Harmer
4.953
274746AC1-111 G10
Adder
6.083
274744AC1-111 GEN8
Adder
6.083
958391AF2-133 GEN
Solar/Wind Harmer
9.677
971177AH1-047 GEN
Solar/Wind Harmer
6.235
276868AE1-113 GEN
Solar/Wind Harmer
10.768
276882AE2-255 GEN
Solar/Wind Harmer
3.589
971411AH1-196 GEN
Solar/Wind Harmer
15.911
971675AH1-338 GEN
Solar/Wind Harmer
19.093
274823ROCKFORD ;21
Adder
20.508
270054AF2-122 C O1
Solar/Wind Helper
1.62
971549AH1-272 GEN
Solar/Wind Harmer
15.966
24344105CKG2
50/50
9.384
270143AC1-141 CT2_
50/50
2.761
24639705ELKHART HY
50/50
0.186
970521AG2-332 GEN
50/50
13.281
24307105BERRINSP G
50/50
0.025
962761AG1-125 GEN
Solar/Wind Harmer
89.197
970149AG2-104 GEN
Solar/Wind Harmer
110.158
970155AG2-107 GEN
Solar/Wind Harmer
38.894
970245AG2-165 GEN
Solar/Wind Harmer
21.268
270505AE1-170 C O1
Solar/Wind Harmer
17.176
945111AF1-176 GEN
Solar/Wind Harmer
20.364
270063AE2-323 C
Solar/Wind Harmer
2.513
270449AD2-020 GEN
Solar/Wind Harmer
3.183
943021AE2-325 GEN
Solar/Wind Harmer
4.136
972207SS24-0001
Solar/Wind Harmer
24.8
274773LINCOLN ;4U
Adder
6.975
274774LINCOLN ;5U
Adder
6.975
965011AG1-365 GEN
Solar/Wind Harmer
11.187
274723RIVER EC ;12
Adder
19.976
274751CRETE EC ;1U
Adder
5.442
274754CRETE EC ;4U
Adder
5.442
276164X3-005 C
Solar/Wind Harmer
0.781
274812UNIV PK N;8U
Adder
5.552
970373AG2-245 GEN
Solar/Wind Harmer
23.259
276776AD2-060 GEN
Solar/Wind Harmer
0.467
274801UNIV PARK;4U
Adder
6.433
941551AE2-152 GEN
Solar/Wind Harmer
4.986
274676JOLIET 29;8U
Adder
33.648
274674JOLIET 9 ;6U
Adder
16.864
274732ELWOOD EC;7P
Adder
17.991
274871GR RIDGE ;2U
Solar/Wind Harmer
8.406
270055AF2-134 C O1
Solar/Wind Harmer
3.301
274745AC1-111 GEN9
Adder
6.083
276691AA1-018 GEN1
Solar/Wind Harmer
0.502
274682WAUKEGAN ;7U
Adder
19.358
274828WAUKEGAN ;BP
Adder
11.886
958381AF2-132 GEN
Solar/Wind Harmer
9.749
964861AG1-349 GEN
Solar/Wind Harmer
8.434
971917AH1-482 GEN
Solar/Wind Harmer
9.733
960751AF2-366 GEN
Solar/Wind Harmer
3.071
962781AG1-127 GEN
Solar/Wind Harmer
10.181
274872LEEDK;1U
Solar/Wind Harmer
8.777
939401AE1-172 GEN
Solar/Wind Harmer
14.891
276901AD2-066 C O1
Solar/Wind Harmer
3.747
971997AH1-543 GEN
Solar/Wind Harmer
16.729
276861AD2-134 GEN
Solar/Wind Harmer
1.894
274822ROCKFORD ;11
Adder
20.658
972235AH1-702 GEN1
Adder
2.648
274761LEE CO EC;2U
Adder
9.662
274766LEE CO EC;7U
Adder
9.549
24721705FLATG2
Adder
19.907
962601AG1-109 GEN
50/50
3.302
970153AG2-106 GEN
Solar/Wind Harmer
38.894
970349AG2-230 GEN
Solar/Wind Harmer
18.111
970513AG2-328 GEN
Solar/Wind Harmer
21.268
970517AG2-330 GEN
Solar/Wind Harmer
19.29
270043AE2-236 GEN
Solar/Wind Harmer
6.511
247643Z2-116 C
Solar/Wind Harmer
0.08
945111AF1-176 GEN
Solar/Wind Harmer
6.454
970031AG2-029 GEN
Solar/Wind Harmer
33.986
274772LINCOLN ;3U
Adder
6.975
24441205WTRV SLR C
Solar/Wind Harmer
0.151
959331AF2-224 GEN
Solar/Wind Harmer
11.187
965021AG1-366 GEN
Solar/Wind Harmer
2.602
274724RIVER EC ;11
Adder
19.746
944531AF1-118 GEN
Solar/Wind Harmer
39.003
972231SS25-0005
Solar/Wind Harmer
10.567
972181SS23-001
Solar/Wind Harmer
6.604
274752CRETE EC ;2U
Adder
5.442
274753CRETE EC ;3U
Adder
5.442
247604X1-042
Adder
0.463
970707AG2-453 GEN
Solar/Wind Harmer
31.017
274802UNIV PARK;5U
Adder
6.439
274826FISK ;BP
Adder
12.09
276772AC2-154 GEN
Solar/Wind Harmer
3.077
276806AD2-047 C O1
Solar/Wind Harmer
11.806
970941AG2-585 GEN
Solar/Wind Harmer
13.795
274800UNIV PARK;3U
Adder
6.433
972038AH1-567 GEN2
Adder
0.403
972228AH1-698 GEN2
Adder
4.086
276897AD1-100 C
Solar/Wind Harmer
31.901
939351AE1-166 GEN
Solar/Wind Harmer
6.518
274676JOLIET 29;8U
Adder
32.446
274729ELWOOD EC;1P
Adder
17.991
274730ELWOOD EC;6P
Adder
17.991
274734ELWOOD EC;8P
Adder
17.991
274736ELWOOD EC;9P
Adder
17.991
276893AG1-478 C
Solar/Wind Harmer
0.457
270535AF1-215 GEN1
Solar/Wind Harmer
4.953
943121AE2-341 GEN
Solar/Wind Harmer
16.349
943591AF1-030 GEN
Solar/Wind Harmer
10.899
276694AA1-018 GEN2
Solar/Wind Harmer
6.801
274682WAUKEGAN ;7U
Adder
19.358
964401AG1-302 GEN
Solar/Wind Harmer
9.749
274872LEEDK;1U
Solar/Wind Harmer
0.273
276805AD2-038 GEN
Solar/Wind Harmer
5.478
276799AD1-013 GEN
Solar/Wind Harmer
2.346
946671AF1-331 GEN
Solar/Wind Harmer
0.444
959141AF2-205 GEN
Solar/Wind Harmer
6.413
274855GSG-6 ;RU
Solar/Wind Harmer
3.917
274850MENDOTA H;RU
Solar/Wind Harmer
2.724
276602WESTBROOK C
Solar/Wind Harmer
2.255
276863AD2-134 GEN
Solar/Wind Harmer
1.894
972236AH1-702 GEN2
Adder
2.303
274760LEE CO EC;1U
Adder
9.662
274767LEE CO EC;8U
Adder
9.549
24721905FLATG4
Adder
19.907
NYPJM->LTFIMP_NY
CLTF
2.826
LGEELTFEXP_LGEE->PJM
CLTF
3.895
WECLTFEXP_WEC->PJM
CLTF
4.009
AG2-052LTFEXP_AG2-052->PJM
LTF
0.249
AH1-155LTFEXP_AH1-155->PJM
LTF
0.373
CPLELTFEXP_CPLE->PJM
CLTF
1.469
CBM West 2LTFEXP_CBM-W2->PJM
CBM
91.671
LAGNLTFEXP_LAGN->PJM
CLTF
11.82
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.928
TVALTFEXP_TVA->PJM
CLTF
5.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
131.22
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.233
MECLTFEXP_MEC->PJM
CLTF
15.452
SIGELTFEXP_SIGE->PJM
CLTF
0.358

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AP_P2-2_WP-500-DRT14_SRT-SL


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-2_WP-500-DRT14_SRT-SL
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:107.3 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:4904.47
MW Contribution:38.54
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
2.597
24641605TWIN BRNCH
50/50
0.019
24344005CKG1
50/50
7.08
24642205MAYFLWER
50/50
0.726
274772LINCOLN ;3U
50/50
7.031
970153AG2-106 GEN
Solar/Wind Harmer
38.539
970349AG2-230 GEN
Solar/Wind Harmer
17.182
970513AG2-328 GEN
Solar/Wind Harmer
20.275
970517AG2-330 GEN
Solar/Wind Harmer
18.389
270043AE2-236 GEN
Solar/Wind Harmer
6.17
247643Z2-116 C
Solar/Wind Harmer
0.076
945111AF1-176 GEN
Solar/Wind Harmer
6.059
970031AG2-029 GEN
Solar/Wind Harmer
31.974
944531AF1-118 GEN
Solar/Wind Harmer
37.097
274724RIVER EC ;11
Adder
18.728
972231SS25-0005
Solar/Wind Harmer
10.017
972181SS23-001
Solar/Wind Harmer
6.261
274752CRETE EC ;2U
Adder
5.159
274753CRETE EC ;3U
Adder
5.159
959331AF2-224 GEN
Solar/Wind Harmer
10.534
965021AG1-366 GEN
Solar/Wind Harmer
2.45
970707AG2-453 GEN
Solar/Wind Harmer
29.454
274826FISK ;BP
Adder
11.471
274802UNIV PARK;5U
Adder
6.109
276772AC2-154 GEN
Solar/Wind Harmer
2.92
276806AD2-047 C O1
Solar/Wind Harmer
11.203
970941AG2-585 GEN
Solar/Wind Harmer
13.09
274800UNIV PARK;3U
Adder
6.104
972038AH1-567 GEN2
Adder
0.382
972228AH1-698 GEN2
Adder
3.878
24441205WTRV SLR C
Solar/Wind Harmer
0.141
276897AD1-100 C
Solar/Wind Harmer
30.28
939351AE1-166 GEN
Solar/Wind Harmer
6.187
274676JOLIET 29;8U
Adder
30.792
274729ELWOOD EC;1P
Adder
17.074
274730ELWOOD EC;6P
Adder
17.074
274734ELWOOD EC;8P
Adder
17.074
274736ELWOOD EC;9P
Adder
17.074
276893AG1-478 C
Solar/Wind Harmer
0.434
24344105CKG2
50/50
8.921
270143AC1-141 CT2_
50/50
2.597
24639705ELKHART HY
50/50
0.175
970521AG2-332 GEN
50/50
12.491
274773LINCOLN ;4U
50/50
7.031
274774LINCOLN ;5U
50/50
7.031
962761AG1-125 GEN
Solar/Wind Harmer
88.384
970149AG2-104 GEN
Solar/Wind Harmer
109.154
970155AG2-107 GEN
Solar/Wind Harmer
38.539
970245AG2-165 GEN
Solar/Wind Harmer
20.275
270505AE1-170 C O1
Solar/Wind Harmer
16.131
270063AE2-323 C
Solar/Wind Harmer
2.365
945111AF1-176 GEN
Solar/Wind Harmer
19.119
972207SS24-0001
Solar/Wind Harmer
23.558
270449AD2-020 GEN
Solar/Wind Harmer
2.984
943021AE2-325 GEN
Solar/Wind Harmer
3.877
274723RIVER EC ;12
Adder
18.946
274751CRETE EC ;1U
Adder
5.159
274754CRETE EC ;4U
Adder
5.159
276164X3-005 C
Solar/Wind Harmer
0.741
965011AG1-365 GEN
Solar/Wind Harmer
10.534
274812UNIV PK N;8U
Adder
5.266
970373AG2-245 GEN
Solar/Wind Harmer
22.001
276776AD2-060 GEN
Solar/Wind Harmer
0.443
274801UNIV PARK;4U
Adder
6.104
941551AE2-152 GEN
Solar/Wind Harmer
4.732
274676JOLIET 29;8U
Adder
31.933
274674JOLIET 9 ;6U
Adder
16.004
274732ELWOOD EC;7P
Adder
17.074
274871GR RIDGE ;2U
Solar/Wind Harmer
7.979
274745AC1-111 GEN9
Adder
5.774
270055AF2-134 C O1
Solar/Wind Harmer
3.123
276691AA1-018 GEN1
Solar/Wind Harmer
0.476
274682WAUKEGAN ;7U
Adder
18.372
274828WAUKEGAN ;BP
Adder
11.281
958381AF2-132 GEN
Solar/Wind Harmer
9.225
960751AF2-366 GEN
Solar/Wind Harmer
2.915
962781AG1-127 GEN
Solar/Wind Harmer
9.663
964861AG1-349 GEN
Solar/Wind Harmer
7.981
971917AH1-482 GEN
Solar/Wind Harmer
9.21
274872LEEDK;1U
Solar/Wind Harmer
8.331
939401AE1-172 GEN
Solar/Wind Harmer
14.131
276901AD2-066 C O1
Solar/Wind Harmer
3.555
971997AH1-543 GEN
Solar/Wind Harmer
15.875
276861AD2-134 GEN
Solar/Wind Harmer
1.798
274822ROCKFORD ;11
Adder
19.604
972235AH1-702 GEN1
Adder
2.513
274761LEE CO EC;2U
Adder
9.168
274766LEE CO EC;7U
Adder
9.06
24721705FLATG2
Adder
19.59
957471AF2-041 GEN
Solar/Wind Harmer
0.961
959081AF2-199 GEN
Solar/Wind Harmer
0.32
971067AG2-660 GEN
Solar/Wind Harmer
0.075
971599AH1-298 GEN
50/50
10.537
270144AC1-141 ST1_
50/50
2.301
24643105BUCHANAN
50/50
0.014
24653605MOTTVILLE
50/50
0.004
274775LINCOLN ;6U
50/50
7.031
274776LINCOLN ;7U
50/50
7.031
274777LINCOLN ;8U
50/50
7.031
962771AG1-126 GEN
Solar/Wind Harmer
88.384
971347AH1-153 GEN
Solar/Wind Harmer
17.182
270071AF1-092 GEN
Solar/Wind Harmer
16.471
971771AH1-392 GEN
Solar/Wind Harmer
9.787
960681AF2-359 GEN
Solar/Wind Harmer
4.098
971769AH1-391 GEN
Solar/Wind Harmer
10.814
944161AF1-084 GEN
Solar/Wind Harmer
2.339
274814UNIV PK N;0U
Adder
5.312
274807UNIV PK N;3U
Adder
5.3
274805UNIV PK N;1U
Adder
5.277
274811UNIV PK N;7U
Adder
5.266
274827FISK ;RP
Adder
8.13
972037AH1-567 GEN1
Adder
0.192
960591AF2-350 GEN
Solar/Wind Harmer
10.472
972227AH1-698 GEN1
Adder
2.73
274687WILL CNTY;4U
Adder
29.107
274687WILL CNTY;4U
Adder
29.107
274675JOLIET 29;7U
Adder
31.933
274675JOLIET 29;7U
Adder
30.793
943121AE2-341 GEN
Solar/Wind Harmer
15.521
943591AF1-030 GEN
Solar/Wind Harmer
10.347
247604X1-042
Adder
0.431
270535AF1-215 GEN1
Solar/Wind Harmer
4.686
276694AA1-018 GEN2
Solar/Wind Harmer
6.453
274682WAUKEGAN ;7U
Adder
18.372
964401AG1-302 GEN
Solar/Wind Harmer
9.225
274872LEEDK;1U
Solar/Wind Harmer
0.259
276805AD2-038 GEN
Solar/Wind Harmer
5.197
276799AD1-013 GEN
Solar/Wind Harmer
2.226
946671AF1-331 GEN
Solar/Wind Harmer
0.422
274855GSG-6 ;RU
Solar/Wind Harmer
3.717
274850MENDOTA H;RU
Solar/Wind Harmer
2.585
276602WESTBROOK C
Solar/Wind Harmer
2.14
276863AD2-134 GEN
Solar/Wind Harmer
1.798
959141AF2-205 GEN
Solar/Wind Harmer
6.07
972236AH1-702 GEN2
Adder
2.185
274760LEE CO EC;1U
Adder
9.168
274767LEE CO EC;8U
Adder
9.06
24721905FLATG4
Adder
19.59
959091AF2-200 GEN
Solar/Wind Harmer
0.641
270102X2-052 ST
50/50
1.744
270100X2-052 CT1
50/50
1.606
270101X2-052 CT2
50/50
1.606
247620Y3-023
50/50
0.524
274770LINCOLN ;1U
50/50
7.031
274771LINCOLN ;2U
50/50
7.031
970321AG2-212 GEN
Solar/Wind Harmer
20.275
270216AD2-079_GEN
Solar/Wind Harmer
0.658
965681AG1-436 GEN
Solar/Wind Harmer
13.559
965791AG1-447 GEN
Solar/Wind Harmer
6.937
270526AF1-158 GEN
Solar/Wind Harmer
4.919
24441505OLIV SLR
Solar/Wind Harmer
0.145
957891AF2-083 GEN
Solar/Wind Harmer
3.624
960981AF2-389 GEN
Solar/Wind Harmer
1.624
961051AF2-396 GEN
Solar/Wind Harmer
16.938
961051AF2-396 GEN
Solar/Wind Harmer
7.878
970611AG2-400 GEN
Solar/Wind Harmer
10.534
274808UNIV PK N;4U
Adder
5.243
972259AH1-714 GEN
Adder
19.997
274803UNIV PARK;6U
Adder
6.109
274888KELLY CRK;1U
Solar/Wind Harmer
6.183
274887GEN-1.85
Solar/Wind Harmer
5.582
276843GEN-1.7
Solar/Wind Harmer
0.601
958011AF2-095 GEN
Solar/Wind Harmer
15.08
274674JOLIET 9 ;6U
Adder
16.004
274847GR RIDGE ;BU
Solar/Wind Harmer
5.248
971573AH1-285 GEN
Solar/Wind Harmer
8.859
274696ROCKY RD ;4P
Adder
11.666
274695ROCKY RD ;2P
Adder
11.398
274693ROCKY RD ;1P
Adder
11.285
274697ROCKY RD ;3P
Adder
3.096
958481AF2-142 GEN
Solar/Wind Harmer
15.339
274861TOP CROP ;1U
Solar/Wind Harmer
6.194
274862TOP CROP ;2U
Solar/Wind Harmer
5.172
274683WAUKEGAN ;8U
Adder
21.521
274683WAUKEGAN ;8U
Adder
18.141
962691AG1-118 GEN
Solar/Wind Harmer
30.542
970921AG2-575 GEN
Solar/Wind Harmer
10.161
970921AG2-575 GEN
Solar/Wind Harmer
2.363
958491AF2-143 GEN
Solar/Wind Harmer
15.196
942991AE2-321 GEN
Solar/Wind Harmer
10.102
274879MINONK ;1U
Solar/Wind Harmer
6.812
971333AH1-146 GEN
Solar/Wind Harmer
20.122
971335AH1-147 GEN
Solar/Wind Harmer
20.122
274764LEE CO EC;5U
Adder
9.19
274765LEE CO EC;6U
Adder
9.19
274762LEE CO EC;3U
Adder
9.168
274763LEE CO EC;4U
Adder
9.082
972267AH1-718 GEN
Adder
4.072
971341AH1-150 GEN
Solar/Wind Harmer
0.641
971343AH1-151 GEN
Solar/Wind Harmer
0.641
24729505KEY G4
Adder
6.744
274731ELWOOD EC;2P
Adder
17.074
274733ELWOOD EC;3P
Adder
17.074
274735ELWOOD EC;4P
Adder
17.074
274728ELWOOD EC;5P
Adder
17.074
970833AG2-524 GEN
Solar/Wind Harmer
9.062
970833AG2-524 GEN
Solar/Wind Harmer
4.215
274746AC1-111 G10
Adder
5.774
274744AC1-111 GEN8
Adder
5.774
270536AF1-215 GEN2
Solar/Wind Harmer
4.686
971177AH1-047 GEN
Solar/Wind Harmer
5.918
958391AF2-133 GEN
Solar/Wind Harmer
9.158
276868AE1-113 GEN
Solar/Wind Harmer
10.216
276882AE2-255 GEN
Solar/Wind Harmer
3.406
971675AH1-338 GEN
Solar/Wind Harmer
18.12
971411AH1-196 GEN
Solar/Wind Harmer
15.1
274863CRW1-WTG
Solar/Wind Harmer
5.594
274864CRW2-WTG
Solar/Wind Harmer
5.594
274823ROCKFORD ;21
Adder
19.462
270054AF2-122 C O1
Solar/Wind Helper
1.653
971171AH1-044 GEN
Solar/Wind Harmer
0.641
NYPJM->LTFIMP_NY
CLTF
2.605
LGEELTFEXP_LGEE->PJM
CLTF
3.642
WECLTFEXP_WEC->PJM
CLTF
3.804
AG2-052LTFEXP_AG2-052->PJM
LTF
0.236
AH1-155LTFEXP_AH1-155->PJM
LTF
0.354
CPLELTFEXP_CPLE->PJM
CLTF
1.403
CBM West 2LTFEXP_CBM-W2->PJM
CBM
86.692
LAGNLTFEXP_LAGN->PJM
CLTF
11.189
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.594
TVALTFEXP_TVA->PJM
CLTF
5.037
CBM West 1LTFEXP_CBM-W1->PJM
CBM
119.66
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.096
MECLTFEXP_MEC->PJM
CLTF
14.649
SIGELTFEXP_SIGE->PJM
CLTF
0.337

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AEP_P4_#2942_05KAMMER 765_PP_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.71 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:6157.38
MW Contribution:41.67
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
1.786
971599AH1-298 GEN
50/50
12.095
962771AG1-126 GEN
Solar/Wind Harmer
95.557
971347AH1-153 GEN
Solar/Wind Harmer
20.011
270071AF1-092 GEN
Solar/Wind Harmer
19.32
960681AF2-359 GEN
Solar/Wind Harmer
4.823
971771AH1-392 GEN
Solar/Wind Harmer
11.437
274775LINCOLN ;6U
Adder
7.877
274776LINCOLN ;7U
Adder
7.877
274777LINCOLN ;8U
Adder
7.877
971769AH1-391 GEN
Solar/Wind Harmer
12.687
274814UNIV PK N;0U
Adder
6.327
274807UNIV PK N;3U
Adder
6.313
274805UNIV PK N;1U
Adder
6.286
274811UNIV PK N;7U
Adder
6.272
274827FISK ;RP
Adder
9.699
972037AH1-567 GEN1
Adder
0.229
960591AF2-350 GEN
Solar/Wind Harmer
12.498
972227AH1-698 GEN1
Adder
3.26
274687WILL CNTY;4U
Adder
34.788
274687WILL CNTY;4U
Adder
34.788
274675JOLIET 29;7U
Adder
38.178
274675JOLIET 29;7U
Adder
36.814
274731ELWOOD EC;2P
Adder
20.424
274733ELWOOD EC;3P
Adder
20.424
274735ELWOOD EC;4P
Adder
20.424
274728ELWOOD EC;5P
Adder
20.425
970833AG2-524 GEN
Solar/Wind Harmer
10.846
970833AG2-524 GEN
Solar/Wind Harmer
5.045
274746AC1-111 G10
Adder
6.919
274744AC1-111 GEN8
Adder
6.919
24729505KEY G4
Adder
8.014
270536AF1-215 GEN2
Solar/Wind Harmer
5.608
944161AF1-084 GEN
Solar/Wind Harmer
2.725
958391AF2-133 GEN
Solar/Wind Harmer
11.042
971177AH1-047 GEN
Solar/Wind Harmer
7.132
276868AE1-113 GEN
Solar/Wind Harmer
12.314
276882AE2-255 GEN
Solar/Wind Harmer
4.105
971675AH1-338 GEN
Solar/Wind Harmer
21.857
971411AH1-196 GEN
Solar/Wind Harmer
18.212
274863CRW1-WTG
Solar/Wind Harmer
6.762
274864CRW2-WTG
Solar/Wind Harmer
6.762
274823ROCKFORD ;21
Adder
23.521
270054AF2-122 C O1
Solar/Wind Helper
1.549
971171AH1-044 GEN
Solar/Wind Harmer
0.774
24722005FLATG5
50/50
1.786
24721905FLATG4
50/50
32.751
970153AG2-106 GEN
Solar/Wind Harmer
41.667
970513AG2-328 GEN
Solar/Wind Harmer
23.936
970517AG2-330 GEN
Solar/Wind Harmer
21.709
970349AG2-230 GEN
Solar/Wind Harmer
20.011
270043AE2-236 GEN
Solar/Wind Harmer
7.153
274772LINCOLN ;3U
Adder
7.877
247643Z2-116 C
Solar/Wind Harmer
0.088
24642205MAYFLWER
Adder
0.8
274724RIVER EC ;11
Adder
22.273
970707AG2-453 GEN
Solar/Wind Harmer
35.145
972231SS25-0005
Solar/Wind Harmer
11.912
972181SS23-001
Solar/Wind Harmer
7.445
274752CRETE EC ;2U
Adder
6.135
274753CRETE EC ;3U
Adder
6.135
944531AF1-118 GEN
Solar/Wind Harmer
43.883
24721805FLATG3
50/50
1.786
24721705FLATG2
50/50
32.751
24344105CKG2
50/50
10.346
962761AG1-125 GEN
Solar/Wind Harmer
95.557
970149AG2-104 GEN
Solar/Wind Harmer
118.013
970155AG2-107 GEN
Solar/Wind Harmer
41.667
970245AG2-165 GEN
Solar/Wind Harmer
23.936
972207SS24-0001
Solar/Wind Harmer
28.005
274773LINCOLN ;4U
Adder
7.877
274774LINCOLN ;5U
Adder
7.877
274723RIVER EC ;12
Adder
22.533
24639705ELKHART HY
Adder
0.193
276164X3-005 C
Solar/Wind Harmer
0.882
274751CRETE EC ;1U
Adder
6.135
274754CRETE EC ;4U
Adder
6.135
270505AE1-170 C O1
Solar/Wind Harmer
18.802
274812UNIV PK N;8U
Adder
6.272
276776AD2-060 GEN
Solar/Wind Harmer
0.528
274801UNIV PARK;4U
Adder
7.284
945111AF1-176 GEN
Solar/Wind Harmer
22.288
270063AE2-323 C
Solar/Wind Harmer
2.75
941551AE2-152 GEN
Solar/Wind Harmer
5.657
970373AG2-245 GEN
Solar/Wind Harmer
26.192
274676JOLIET 29;8U
Adder
38.177
274674JOLIET 9 ;6U
Adder
19.142
274732ELWOOD EC;7P
Adder
20.425
274871GR RIDGE ;2U
Solar/Wind Harmer
9.551
270449AD2-020 GEN
Solar/Wind Harmer
3.477
943021AE2-325 GEN
Solar/Wind Harmer
4.518
274745AC1-111 GEN9
Adder
6.919
270055AF2-134 C O1
Solar/Wind Harmer
3.738
276691AA1-018 GEN1
Solar/Wind Harmer
0.572
274682WAUKEGAN ;7U
Adder
22.07
274828WAUKEGAN ;BP
Adder
13.555
958381AF2-132 GEN
Solar/Wind Harmer
11.095
960751AF2-366 GEN
Solar/Wind Harmer
3.508
962781AG1-127 GEN
Solar/Wind Harmer
11.628
964861AG1-349 GEN
Solar/Wind Harmer
9.604
971917AH1-482 GEN
Solar/Wind Harmer
11.083
939401AE1-172 GEN
Solar/Wind Harmer
17.025
274872LEEDK;1U
Solar/Wind Harmer
10.03
276901AD2-066 C O1
Solar/Wind Harmer
4.283
965011AG1-365 GEN
Solar/Wind Harmer
12.175
971997AH1-543 GEN
Solar/Wind Harmer
19.145
276861AD2-134 GEN
Solar/Wind Harmer
2.169
274822ROCKFORD ;11
Adder
23.693
972235AH1-702 GEN1
Adder
3.039
274761LEE CO EC;2U
Adder
11.12
274766LEE CO EC;7U
Adder
10.989
970091AG2-072 GEN
Adder
5.216
957471AF2-041 GEN
Solar/Wind Harmer
1.161
959081AF2-199 GEN
Solar/Wind Harmer
0.387
971067AG2-660 GEN
Solar/Wind Harmer
0.09
274826FISK ;BP
Adder
13.685
274802UNIV PARK;5U
Adder
7.287
276772AC2-154 GEN
Solar/Wind Harmer
3.485
276806AD2-047 C O1
Solar/Wind Harmer
13.37
970941AG2-585 GEN
Solar/Wind Harmer
15.623
972228AH1-698 GEN2
Adder
4.629
274800UNIV PARK;3U
Adder
7.284
972038AH1-567 GEN2
Adder
0.456
945111AF1-176 GEN
Solar/Wind Harmer
7.064
276897AD1-100 C
Solar/Wind Harmer
36.195
939351AE1-166 GEN
Solar/Wind Harmer
7.396
274676JOLIET 29;8U
Adder
36.814
274729ELWOOD EC;1P
Adder
20.424
274730ELWOOD EC;6P
Adder
20.425
274734ELWOOD EC;8P
Adder
20.425
274736ELWOOD EC;9P
Adder
20.425
276893AG1-478 C
Solar/Wind Harmer
0.519
970031AG2-029 GEN
Solar/Wind Harmer
37.211
943121AE2-341 GEN
Solar/Wind Harmer
18.593
943591AF1-030 GEN
Solar/Wind Harmer
12.395
270535AF1-215 GEN1
Solar/Wind Harmer
5.608
276694AA1-018 GEN2
Solar/Wind Harmer
7.75
274682WAUKEGAN ;7U
Adder
22.07
964401AG1-302 GEN
Solar/Wind Harmer
11.095
274872LEEDK;1U
Solar/Wind Harmer
0.312
276805AD2-038 GEN
Solar/Wind Harmer
6.257
959331AF2-224 GEN
Solar/Wind Harmer
12.175
965021AG1-366 GEN
Solar/Wind Harmer
2.831
24441205WTRV SLR C
Solar/Wind Harmer
0.164
276799AD1-013 GEN
Solar/Wind Harmer
2.685
946671AF1-331 GEN
Solar/Wind Harmer
0.508
274855GSG-6 ;RU
Solar/Wind Harmer
4.484
274850MENDOTA H;RU
Solar/Wind Harmer
3.118
276602WESTBROOK C
Solar/Wind Harmer
2.581
276863AD2-134 GEN
Solar/Wind Harmer
2.169
959141AF2-205 GEN
Solar/Wind Harmer
7.332
972236AH1-702 GEN2
Adder
2.642
247604X1-042
Adder
0.502
274760LEE CO EC;1U
Adder
11.12
274767LEE CO EC;8U
Adder
10.989
959091AF2-200 GEN
Solar/Wind Harmer
0.774
270102X2-052 ST
50/50
2.048
270100X2-052 CT1
50/50
1.887
270101X2-052 CT2
50/50
1.887
970321AG2-212 GEN
Solar/Wind Harmer
23.936
965681AG1-436 GEN
Solar/Wind Harmer
15.956
965791AG1-447 GEN
Solar/Wind Harmer
8.164
274770LINCOLN ;1U
Adder
7.877
274771LINCOLN ;2U
Adder
7.877
270526AF1-158 GEN
Solar/Wind Harmer
5.766
24441505OLIV SLR
Solar/Wind Harmer
0.17
270216AD2-079_GEN
Solar/Wind Harmer
0.767
957891AF2-083 GEN
Solar/Wind Harmer
4.225
960981AF2-389 GEN
Solar/Wind Harmer
1.893
274808UNIV PK N;4U
Adder
6.245
972259AH1-714 GEN
Adder
23.874
274803UNIV PARK;6U
Adder
7.287
274888KELLY CRK;1U
Solar/Wind Harmer
7.379
274887GEN-1.85
Solar/Wind Harmer
6.662
276843GEN-1.7
Solar/Wind Harmer
0.717
958011AF2-095 GEN
Solar/Wind Harmer
17.998
247620Y3-023
Adder
0.575
961051AF2-396 GEN
Solar/Wind Harmer
19.743
961051AF2-396 GEN
Solar/Wind Harmer
9.183
274674JOLIET 9 ;6U
Adder
19.142
274847GR RIDGE ;BU
Solar/Wind Harmer
6.282
971573AH1-285 GEN
Solar/Wind Harmer
10.624
274695ROCKY RD ;2P
Adder
13.688
274693ROCKY RD ;1P
Adder
13.554
274697ROCKY RD ;3P
Adder
3.718
274696ROCKY RD ;4P
Adder
14.011
958481AF2-142 GEN
Solar/Wind Harmer
18.422
274861TOP CROP ;1U
Solar/Wind Harmer
7.44
274862TOP CROP ;2U
Solar/Wind Harmer
6.212
274683WAUKEGAN ;8U
Adder
25.859
274683WAUKEGAN ;8U
Adder
21.798
962691AG1-118 GEN
Solar/Wind Harmer
36.735
970921AG2-575 GEN
Solar/Wind Harmer
12.227
970921AG2-575 GEN
Solar/Wind Harmer
2.844
958491AF2-143 GEN
Solar/Wind Harmer
18.296
970611AG2-400 GEN
Solar/Wind Harmer
12.175
942991AE2-321 GEN
Solar/Wind Harmer
12.173
274879MINONK ;1U
Solar/Wind Harmer
8.21
971333AH1-146 GEN
Solar/Wind Harmer
24.274
971335AH1-147 GEN
Solar/Wind Harmer
24.274
274764LEE CO EC;5U
Adder
11.146
274765LEE CO EC;6U
Adder
11.146
274762LEE CO EC;3U
Adder
11.12
274763LEE CO EC;4U
Adder
11.015
972267AH1-718 GEN
Adder
4.949
971341AH1-150 GEN
Solar/Wind Harmer
0.774
971343AH1-151 GEN
Solar/Wind Harmer
0.774
944201AF1-088_MTX
Adder
117.628
957141AF2-008_MTX
Adder
58.814
NYPJM->LTFIMP_NY
CLTF
3.802
LGEELTFEXP_LGEE->PJM
CLTF
5.477
WECLTFEXP_WEC->PJM
CLTF
4.602
AG2-052LTFEXP_AG2-052->PJM
LTF
0.284
AH1-155LTFEXP_AH1-155->PJM
LTF
0.425
CPLELTFEXP_CPLE->PJM
CLTF
3.161
CBM West 2LTFEXP_CBM-W2->PJM
CBM
119.296
LAGNLTFEXP_LAGN->PJM
CLTF
16.151
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.809
TVALTFEXP_TVA->PJM
CLTF
7.633
CBM West 1LTFEXP_CBM-W1->PJM
CBM
145.765
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.894
MECLTFEXP_MEC->PJM
CLTF
18.376
SIGELTFEXP_SIGE->PJM
CLTF
0.47

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AP_P2-3_MP-500-020_SRT-SL


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-020_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.15 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:6040.67
MW Contribution:41.78
Bus #Bus NameTypeMW Contribution
24721805FLATG3
50/50
1.796
24721705FLATG2
50/50
32.926
24344105CKG2
50/50
10.407
962761AG1-125 GEN
Solar/Wind Harmer
95.82
970149AG2-104 GEN
Solar/Wind Harmer
118.338
970155AG2-107 GEN
Solar/Wind Harmer
41.782
970245AG2-165 GEN
Solar/Wind Harmer
24.08
972207SS24-0001
Solar/Wind Harmer
28.182
274773LINCOLN ;4U
Adder
7.927
274774LINCOLN ;5U
Adder
7.927
274723RIVER EC ;12
Adder
22.677
24639705ELKHART HY
Adder
0.194
276164X3-005 C
Solar/Wind Harmer
0.888
274751CRETE EC ;1U
Adder
6.174
274754CRETE EC ;4U
Adder
6.174
270505AE1-170 C O1
Solar/Wind Harmer
18.922
274812UNIV PK N;8U
Adder
6.313
276776AD2-060 GEN
Solar/Wind Harmer
0.532
274801UNIV PARK;4U
Adder
7.331
945111AF1-176 GEN
Solar/Wind Harmer
22.432
270063AE2-323 C
Solar/Wind Harmer
2.768
941551AE2-152 GEN
Solar/Wind Harmer
5.693
970373AG2-245 GEN
Solar/Wind Harmer
26.361
274676JOLIET 29;8U
Adder
38.424
274674JOLIET 9 ;6U
Adder
19.265
274732ELWOOD EC;7P
Adder
20.557
274871GR RIDGE ;2U
Solar/Wind Harmer
9.612
270449AD2-020 GEN
Solar/Wind Harmer
3.5
943021AE2-325 GEN
Solar/Wind Harmer
4.548
274745AC1-111 GEN9
Adder
6.964
270055AF2-134 C O1
Solar/Wind Harmer
3.763
276691AA1-018 GEN1
Solar/Wind Harmer
0.576
274682WAUKEGAN ;7U
Adder
22.214
274828WAUKEGAN ;BP
Adder
13.643
958381AF2-132 GEN
Solar/Wind Harmer
11.168
960751AF2-366 GEN
Solar/Wind Harmer
3.531
962781AG1-127 GEN
Solar/Wind Harmer
11.704
964861AG1-349 GEN
Solar/Wind Harmer
9.667
971917AH1-482 GEN
Solar/Wind Harmer
11.156
939401AE1-172 GEN
Solar/Wind Harmer
17.137
274872LEEDK;1U
Solar/Wind Harmer
10.096
276901AD2-066 C O1
Solar/Wind Harmer
4.312
965011AG1-365 GEN
Solar/Wind Harmer
12.256
971997AH1-543 GEN
Solar/Wind Harmer
19.271
276861AD2-134 GEN
Solar/Wind Harmer
2.183
274822ROCKFORD ;11
Adder
23.85
972235AH1-702 GEN1
Adder
3.059
274761LEE CO EC;2U
Adder
11.195
274766LEE CO EC;7U
Adder
11.063
970091AG2-072 GEN
Adder
5.259
957471AF2-041 GEN
Solar/Wind Harmer
1.169
959081AF2-199 GEN
Solar/Wind Harmer
0.39
971067AG2-660 GEN
Solar/Wind Harmer
0.091
24721605FLATG1
50/50
1.796
971599AH1-298 GEN
50/50
12.165
962771AG1-126 GEN
Solar/Wind Harmer
95.82
971347AH1-153 GEN
Solar/Wind Harmer
20.131
270071AF1-092 GEN
Solar/Wind Harmer
19.441
960681AF2-359 GEN
Solar/Wind Harmer
4.853
971771AH1-392 GEN
Solar/Wind Harmer
11.51
274775LINCOLN ;6U
Adder
7.927
274776LINCOLN ;7U
Adder
7.927
274777LINCOLN ;8U
Adder
7.927
971769AH1-391 GEN
Solar/Wind Harmer
12.768
274814UNIV PK N;0U
Adder
6.368
274807UNIV PK N;3U
Adder
6.354
274805UNIV PK N;1U
Adder
6.326
274811UNIV PK N;7U
Adder
6.313
274827FISK ;RP
Adder
9.761
972037AH1-567 GEN1
Adder
0.23
960591AF2-350 GEN
Solar/Wind Harmer
12.579
972227AH1-698 GEN1
Adder
3.281
274687WILL CNTY;4U
Adder
35.013
274687WILL CNTY;4U
Adder
35.013
274675JOLIET 29;7U
Adder
38.424
274675JOLIET 29;7U
Adder
37.052
274731ELWOOD EC;2P
Adder
20.557
274733ELWOOD EC;3P
Adder
20.557
274735ELWOOD EC;4P
Adder
20.557
274728ELWOOD EC;5P
Adder
20.557
970833AG2-524 GEN
Solar/Wind Harmer
10.916
970833AG2-524 GEN
Solar/Wind Harmer
5.077
274746AC1-111 G10
Adder
6.964
274744AC1-111 GEN8
Adder
6.964
24729505KEY G4
Adder
8.066
270536AF1-215 GEN2
Solar/Wind Harmer
5.645
944161AF1-084 GEN
Solar/Wind Harmer
2.743
958391AF2-133 GEN
Solar/Wind Harmer
11.115
971177AH1-047 GEN
Solar/Wind Harmer
7.179
276868AE1-113 GEN
Solar/Wind Harmer
12.396
276882AE2-255 GEN
Solar/Wind Harmer
4.132
971675AH1-338 GEN
Solar/Wind Harmer
22.002
971411AH1-196 GEN
Solar/Wind Harmer
18.333
274863CRW1-WTG
Solar/Wind Harmer
6.807
274864CRW2-WTG
Solar/Wind Harmer
6.807
274823ROCKFORD ;21
Adder
23.677
270054AF2-122 C O1
Solar/Wind Helper
1.538
971171AH1-044 GEN
Solar/Wind Harmer
0.779
24722005FLATG5
50/50
1.796
24721905FLATG4
50/50
32.926
970153AG2-106 GEN
Solar/Wind Harmer
41.782
970513AG2-328 GEN
Solar/Wind Harmer
24.08
970517AG2-330 GEN
Solar/Wind Harmer
21.84
970349AG2-230 GEN
Solar/Wind Harmer
20.131
270043AE2-236 GEN
Solar/Wind Harmer
7.197
274772LINCOLN ;3U
Adder
7.927
247643Z2-116 C
Solar/Wind Harmer
0.089
24642205MAYFLWER
Adder
0.805
274724RIVER EC ;11
Adder
22.416
970707AG2-453 GEN
Solar/Wind Harmer
35.371
972231SS25-0005
Solar/Wind Harmer
11.989
972181SS23-001
Solar/Wind Harmer
7.493
274752CRETE EC ;2U
Adder
6.174
274753CRETE EC ;3U
Adder
6.174
944531AF1-118 GEN
Solar/Wind Harmer
44.166
274826FISK ;BP
Adder
13.773
274802UNIV PARK;5U
Adder
7.334
276772AC2-154 GEN
Solar/Wind Harmer
3.508
276806AD2-047 C O1
Solar/Wind Harmer
13.456
970941AG2-585 GEN
Solar/Wind Harmer
15.724
972228AH1-698 GEN2
Adder
4.659
274800UNIV PARK;3U
Adder
7.331
972038AH1-567 GEN2
Adder
0.459
945111AF1-176 GEN
Solar/Wind Harmer
7.109
276897AD1-100 C
Solar/Wind Harmer
36.429
939351AE1-166 GEN
Solar/Wind Harmer
7.443
274676JOLIET 29;8U
Adder
37.052
274729ELWOOD EC;1P
Adder
20.557
274730ELWOOD EC;6P
Adder
20.557
274734ELWOOD EC;8P
Adder
20.557
274736ELWOOD EC;9P
Adder
20.557
276893AG1-478 C
Solar/Wind Harmer
0.522
970031AG2-029 GEN
Solar/Wind Harmer
37.453
943121AE2-341 GEN
Solar/Wind Harmer
18.714
943591AF1-030 GEN
Solar/Wind Harmer
12.476
270535AF1-215 GEN1
Solar/Wind Harmer
5.645
276694AA1-018 GEN2
Solar/Wind Harmer
7.801
274682WAUKEGAN ;7U
Adder
22.214
964401AG1-302 GEN
Solar/Wind Harmer
11.168
274872LEEDK;1U
Solar/Wind Harmer
0.314
276805AD2-038 GEN
Solar/Wind Harmer
6.299
959331AF2-224 GEN
Solar/Wind Harmer
12.256
965021AG1-366 GEN
Solar/Wind Harmer
2.85
24441205WTRV SLR C
Solar/Wind Harmer
0.165
276799AD1-013 GEN
Solar/Wind Harmer
2.703
946671AF1-331 GEN
Solar/Wind Harmer
0.512
274855GSG-6 ;RU
Solar/Wind Harmer
4.514
274850MENDOTA H;RU
Solar/Wind Harmer
3.139
276602WESTBROOK C
Solar/Wind Harmer
2.598
276863AD2-134 GEN
Solar/Wind Harmer
2.183
959141AF2-205 GEN
Solar/Wind Harmer
7.381
972236AH1-702 GEN2
Adder
2.66
247604X1-042
Adder
0.505
274760LEE CO EC;1U
Adder
11.195
274767LEE CO EC;8U
Adder
11.063
959091AF2-200 GEN
Solar/Wind Harmer
0.779
270102X2-052 ST
50/50
2.061
270100X2-052 CT1
50/50
1.899
270101X2-052 CT2
50/50
1.899
970321AG2-212 GEN
Solar/Wind Harmer
24.08
965681AG1-436 GEN
Solar/Wind Harmer
16.057
965791AG1-447 GEN
Solar/Wind Harmer
8.215
274770LINCOLN ;1U
Adder
7.927
274771LINCOLN ;2U
Adder
7.927
270526AF1-158 GEN
Solar/Wind Harmer
5.803
24441505OLIV SLR
Solar/Wind Harmer
0.171
270216AD2-079_GEN
Solar/Wind Harmer
0.772
957891AF2-083 GEN
Solar/Wind Harmer
4.252
274808UNIV PK N;4U
Adder
6.285
960981AF2-389 GEN
Solar/Wind Harmer
1.905
972259AH1-714 GEN
Adder
24.028
274803UNIV PARK;6U
Adder
7.334
274888KELLY CRK;1U
Solar/Wind Harmer
7.426
274887GEN-1.85
Solar/Wind Harmer
6.705
276843GEN-1.7
Solar/Wind Harmer
0.721
958011AF2-095 GEN
Solar/Wind Harmer
18.114
247620Y3-023
Adder
0.579
961051AF2-396 GEN
Solar/Wind Harmer
19.871
961051AF2-396 GEN
Solar/Wind Harmer
9.242
274674JOLIET 9 ;6U
Adder
19.265
274847GR RIDGE ;BU
Solar/Wind Harmer
6.323
971573AH1-285 GEN
Solar/Wind Harmer
10.693
274696ROCKY RD ;4P
Adder
14.103
274695ROCKY RD ;2P
Adder
13.778
274693ROCKY RD ;1P
Adder
13.642
274697ROCKY RD ;3P
Adder
3.743
958481AF2-142 GEN
Solar/Wind Harmer
18.542
274861TOP CROP ;1U
Solar/Wind Harmer
7.488
274862TOP CROP ;2U
Solar/Wind Harmer
6.253
274683WAUKEGAN ;8U
Adder
26.028
274683WAUKEGAN ;8U
Adder
21.94
962691AG1-118 GEN
Solar/Wind Harmer
36.976
970921AG2-575 GEN
Solar/Wind Harmer
12.308
970921AG2-575 GEN
Solar/Wind Harmer
2.862
958491AF2-143 GEN
Solar/Wind Harmer
18.417
970611AG2-400 GEN
Solar/Wind Harmer
12.256
942991AE2-321 GEN
Solar/Wind Harmer
12.253
274879MINONK ;1U
Solar/Wind Harmer
8.265
971333AH1-146 GEN
Solar/Wind Harmer
24.435
971335AH1-147 GEN
Solar/Wind Harmer
24.435
274764LEE CO EC;5U
Adder
11.221
274765LEE CO EC;6U
Adder
11.221
274762LEE CO EC;3U
Adder
11.195
274763LEE CO EC;4U
Adder
11.089
972267AH1-718 GEN
Adder
4.982
971341AH1-150 GEN
Solar/Wind Harmer
0.779
971343AH1-151 GEN
Solar/Wind Harmer
0.779
944201AF1-088_MTX
Adder
118.565
957141AF2-008_MTX
Adder
59.283
NYPJM->LTFIMP_NY
CLTF
3.759
LGEELTFEXP_LGEE->PJM
CLTF
5.533
WECLTFEXP_WEC->PJM
CLTF
4.633
AG2-052LTFEXP_AG2-052->PJM
LTF
0.285
AH1-155LTFEXP_AH1-155->PJM
LTF
0.428
CPLELTFEXP_CPLE->PJM
CLTF
3.242
CBM West 2LTFEXP_CBM-W2->PJM
CBM
120.367
LAGNLTFEXP_LAGN->PJM
CLTF
16.31
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.037
TVALTFEXP_TVA->PJM
CLTF
7.713
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.937
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.195
MECLTFEXP_MEC->PJM
CLTF
18.51
SIGELTFEXP_SIGE->PJM
CLTF
0.474

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AP_P2-3_MP-500-021_SRT-SL


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-021_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.12 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:6039.4
MW Contribution:41.77
Bus #Bus NameTypeMW Contribution
24721805FLATG3
50/50
1.795
24721705FLATG2
50/50
32.911
24344105CKG2
50/50
10.402
962761AG1-125 GEN
Solar/Wind Harmer
95.798
970149AG2-104 GEN
Solar/Wind Harmer
118.311
970155AG2-107 GEN
Solar/Wind Harmer
41.773
970245AG2-165 GEN
Solar/Wind Harmer
24.069
972207SS24-0001
Solar/Wind Harmer
28.169
274773LINCOLN ;4U
Adder
7.923
274774LINCOLN ;5U
Adder
7.923
274723RIVER EC ;12
Adder
22.666
24639705ELKHART HY
Adder
0.194
276164X3-005 C
Solar/Wind Harmer
0.887
274751CRETE EC ;1U
Adder
6.171
274754CRETE EC ;4U
Adder
6.171
270505AE1-170 C O1
Solar/Wind Harmer
18.913
274812UNIV PK N;8U
Adder
6.309
276776AD2-060 GEN
Solar/Wind Harmer
0.532
274801UNIV PARK;4U
Adder
7.327
945111AF1-176 GEN
Solar/Wind Harmer
22.421
270063AE2-323 C
Solar/Wind Harmer
2.766
941551AE2-152 GEN
Solar/Wind Harmer
5.69
970373AG2-245 GEN
Solar/Wind Harmer
26.348
274676JOLIET 29;8U
Adder
38.405
24722005FLATG5
50/50
1.795
24721905FLATG4
50/50
32.911
970153AG2-106 GEN
Solar/Wind Harmer
41.773
970513AG2-328 GEN
Solar/Wind Harmer
24.069
970517AG2-330 GEN
Solar/Wind Harmer
21.83
970349AG2-230 GEN
Solar/Wind Harmer
20.122
270043AE2-236 GEN
Solar/Wind Harmer
7.194
274772LINCOLN ;3U
Adder
7.923
247643Z2-116 C
Solar/Wind Harmer
0.089
24642205MAYFLWER
Adder
0.804
274724RIVER EC ;11
Adder
22.405
970707AG2-453 GEN
Solar/Wind Harmer
35.353
972231SS25-0005
Solar/Wind Harmer
11.983
972181SS23-001
Solar/Wind Harmer
7.489
274752CRETE EC ;2U
Adder
6.171
274753CRETE EC ;3U
Adder
6.171
944531AF1-118 GEN
Solar/Wind Harmer
44.143
274826FISK ;BP
Adder
13.766
274802UNIV PARK;5U
Adder
7.33
276772AC2-154 GEN
Solar/Wind Harmer
3.506
276806AD2-047 C O1
Solar/Wind Harmer
13.45
970941AG2-585 GEN
Solar/Wind Harmer
15.716
972228AH1-698 GEN2
Adder
4.657
274800UNIV PARK;3U
Adder
7.327
972038AH1-567 GEN2
Adder
0.459
945111AF1-176 GEN
Solar/Wind Harmer
7.106
276897AD1-100 C
Solar/Wind Harmer
36.411
939351AE1-166 GEN
Solar/Wind Harmer
7.44
274676JOLIET 29;8U
Adder
37.034
274729ELWOOD EC;1P
Adder
20.547
274730ELWOOD EC;6P
Adder
20.547
274734ELWOOD EC;8P
Adder
20.547
274736ELWOOD EC;9P
Adder
20.547
276893AG1-478 C
Solar/Wind Harmer
0.522
970031AG2-029 GEN
Solar/Wind Harmer
37.434
943121AE2-341 GEN
Solar/Wind Harmer
18.704
943591AF1-030 GEN
Solar/Wind Harmer
12.47
270535AF1-215 GEN1
Solar/Wind Harmer
5.642
276694AA1-018 GEN2
Solar/Wind Harmer
7.797
274682WAUKEGAN ;7U
Adder
22.204
964401AG1-302 GEN
Solar/Wind Harmer
11.162
274872LEEDK;1U
Solar/Wind Harmer
0.314
276805AD2-038 GEN
Solar/Wind Harmer
6.295
959331AF2-224 GEN
Solar/Wind Harmer
12.25
965021AG1-366 GEN
Solar/Wind Harmer
2.849
24441205WTRV SLR C
Solar/Wind Harmer
0.165
276799AD1-013 GEN
Solar/Wind Harmer
2.702
946671AF1-331 GEN
Solar/Wind Harmer
0.512
274855GSG-6 ;RU
Solar/Wind Harmer
4.512
274850MENDOTA H;RU
Solar/Wind Harmer
3.137
276602WESTBROOK C
Solar/Wind Harmer
2.597
276863AD2-134 GEN
Solar/Wind Harmer
2.182
959141AF2-205 GEN
Solar/Wind Harmer
7.377
972236AH1-702 GEN2
Adder
2.659
247604X1-042
Adder
0.505
274760LEE CO EC;1U
Adder
11.189
274767LEE CO EC;8U
Adder
11.057
959091AF2-200 GEN
Solar/Wind Harmer
0.779
274674JOLIET 9 ;6U
Adder
19.256
274732ELWOOD EC;7P
Adder
20.547
274871GR RIDGE ;2U
Solar/Wind Harmer
9.608
270449AD2-020 GEN
Solar/Wind Harmer
3.498
943021AE2-325 GEN
Solar/Wind Harmer
4.545
274745AC1-111 GEN9
Adder
6.961
270055AF2-134 C O1
Solar/Wind Harmer
3.761
276691AA1-018 GEN1
Solar/Wind Harmer
0.575
274682WAUKEGAN ;7U
Adder
22.204
274828WAUKEGAN ;BP
Adder
13.637
958381AF2-132 GEN
Solar/Wind Harmer
11.162
960751AF2-366 GEN
Solar/Wind Harmer
3.529
962781AG1-127 GEN
Solar/Wind Harmer
11.699
964861AG1-349 GEN
Solar/Wind Harmer
9.662
971917AH1-482 GEN
Solar/Wind Harmer
11.15
939401AE1-172 GEN
Solar/Wind Harmer
17.129
274872LEEDK;1U
Solar/Wind Harmer
10.091
276901AD2-066 C O1
Solar/Wind Harmer
4.309
965011AG1-365 GEN
Solar/Wind Harmer
12.25
971997AH1-543 GEN
Solar/Wind Harmer
19.262
276861AD2-134 GEN
Solar/Wind Harmer
2.182
274822ROCKFORD ;11
Adder
23.838
972235AH1-702 GEN1
Adder
3.057
274761LEE CO EC;2U
Adder
11.189
274766LEE CO EC;7U
Adder
11.057
970091AG2-072 GEN
Adder
5.255
957471AF2-041 GEN
Solar/Wind Harmer
1.168
959081AF2-199 GEN
Solar/Wind Harmer
0.389
971067AG2-660 GEN
Solar/Wind Harmer
0.091
24721605FLATG1
50/50
1.795
971599AH1-298 GEN
50/50
12.16
962771AG1-126 GEN
Solar/Wind Harmer
95.798
971347AH1-153 GEN
Solar/Wind Harmer
20.122
270071AF1-092 GEN
Solar/Wind Harmer
19.432
960681AF2-359 GEN
Solar/Wind Harmer
4.851
971771AH1-392 GEN
Solar/Wind Harmer
11.504
274775LINCOLN ;6U
Adder
7.923
274776LINCOLN ;7U
Adder
7.923
274777LINCOLN ;8U
Adder
7.923
971769AH1-391 GEN
Solar/Wind Harmer
12.761
274814UNIV PK N;0U
Adder
6.365
274807UNIV PK N;3U
Adder
6.351
274805UNIV PK N;1U
Adder
6.323
274811UNIV PK N;7U
Adder
6.309
274827FISK ;RP
Adder
9.756
972037AH1-567 GEN1
Adder
0.23
960591AF2-350 GEN
Solar/Wind Harmer
12.573
972227AH1-698 GEN1
Adder
3.279
274687WILL CNTY;4U
Adder
34.996
274687WILL CNTY;4U
Adder
34.996
274675JOLIET 29;7U
Adder
38.406
274675JOLIET 29;7U
Adder
37.034
274731ELWOOD EC;2P
Adder
20.547
274733ELWOOD EC;3P
Adder
20.547
274735ELWOOD EC;4P
Adder
20.547
274728ELWOOD EC;5P
Adder
20.547
970833AG2-524 GEN
Solar/Wind Harmer
10.911
970833AG2-524 GEN
Solar/Wind Harmer
5.075
274746AC1-111 G10
Adder
6.961
274744AC1-111 GEN8
Adder
6.961
24729505KEY G4
Adder
8.062
270536AF1-215 GEN2
Solar/Wind Harmer
5.642
944161AF1-084 GEN
Solar/Wind Harmer
2.742
958391AF2-133 GEN
Solar/Wind Harmer
11.109
971177AH1-047 GEN
Solar/Wind Harmer
7.175
276868AE1-113 GEN
Solar/Wind Harmer
12.39
276882AE2-255 GEN
Solar/Wind Harmer
4.13
971675AH1-338 GEN
Solar/Wind Harmer
21.991
971411AH1-196 GEN
Solar/Wind Harmer
18.324
274863CRW1-WTG
Solar/Wind Harmer
6.804
274864CRW2-WTG
Solar/Wind Harmer
6.804
274823ROCKFORD ;21
Adder
23.666
270054AF2-122 C O1
Solar/Wind Helper
1.539
971171AH1-044 GEN
Solar/Wind Harmer
0.779
270102X2-052 ST
50/50
2.06
270100X2-052 CT1
50/50
1.898
270101X2-052 CT2
50/50
1.898
970321AG2-212 GEN
Solar/Wind Harmer
24.069
965681AG1-436 GEN
Solar/Wind Harmer
16.049
965791AG1-447 GEN
Solar/Wind Harmer
8.211
274770LINCOLN ;1U
Adder
7.923
274771LINCOLN ;2U
Adder
7.923
270526AF1-158 GEN
Solar/Wind Harmer
5.8
24441505OLIV SLR
Solar/Wind Harmer
0.171
270216AD2-079_GEN
Solar/Wind Harmer
0.772
957891AF2-083 GEN
Solar/Wind Harmer
4.25
274808UNIV PK N;4U
Adder
6.282
960981AF2-389 GEN
Solar/Wind Harmer
1.904
972259AH1-714 GEN
Adder
24.016
274803UNIV PARK;6U
Adder
7.33
274888KELLY CRK;1U
Solar/Wind Harmer
7.423
274887GEN-1.85
Solar/Wind Harmer
6.702
276843GEN-1.7
Solar/Wind Harmer
0.721
958011AF2-095 GEN
Solar/Wind Harmer
18.105
247620Y3-023
Adder
0.579
961051AF2-396 GEN
Solar/Wind Harmer
19.861
961051AF2-396 GEN
Solar/Wind Harmer
9.238
274674JOLIET 9 ;6U
Adder
19.256
274847GR RIDGE ;BU
Solar/Wind Harmer
6.32
971573AH1-285 GEN
Solar/Wind Harmer
10.688
274696ROCKY RD ;4P
Adder
14.096
274695ROCKY RD ;2P
Adder
13.771
274693ROCKY RD ;1P
Adder
13.635
274697ROCKY RD ;3P
Adder
3.741
958481AF2-142 GEN
Solar/Wind Harmer
18.533
274861TOP CROP ;1U
Solar/Wind Harmer
7.485
274862TOP CROP ;2U
Solar/Wind Harmer
6.25
274683WAUKEGAN ;8U
Adder
26.015
274683WAUKEGAN ;8U
Adder
21.929
962691AG1-118 GEN
Solar/Wind Harmer
36.958
970921AG2-575 GEN
Solar/Wind Harmer
12.301
970921AG2-575 GEN
Solar/Wind Harmer
2.861
958491AF2-143 GEN
Solar/Wind Harmer
18.408
970611AG2-400 GEN
Solar/Wind Harmer
12.25
942991AE2-321 GEN
Solar/Wind Harmer
12.247
274879MINONK ;1U
Solar/Wind Harmer
8.261
971333AH1-146 GEN
Solar/Wind Harmer
24.423
971335AH1-147 GEN
Solar/Wind Harmer
24.423
274764LEE CO EC;5U
Adder
11.215
274765LEE CO EC;6U
Adder
11.215
274762LEE CO EC;3U
Adder
11.189
274763LEE CO EC;4U
Adder
11.084
972267AH1-718 GEN
Adder
4.98
971341AH1-150 GEN
Solar/Wind Harmer
0.779
971343AH1-151 GEN
Solar/Wind Harmer
0.779
944201AF1-088_MTX
Adder
118.492
957141AF2-008_MTX
Adder
59.246
NYPJM->LTFIMP_NY
CLTF
3.757
LGEELTFEXP_LGEE->PJM
CLTF
5.528
WECLTFEXP_WEC->PJM
CLTF
4.631
AG2-052LTFEXP_AG2-052->PJM
LTF
0.285
AH1-155LTFEXP_AH1-155->PJM
LTF
0.428
CPLELTFEXP_CPLE->PJM
CLTF
3.241
CBM West 2LTFEXP_CBM-W2->PJM
CBM
120.295
LAGNLTFEXP_LAGN->PJM
CLTF
16.301
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.03
TVALTFEXP_TVA->PJM
CLTF
7.708
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.85
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.176
MECLTFEXP_MEC->PJM
CLTF
18.5
SIGELTFEXP_SIGE->PJM
CLTF
0.474

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AEP_P4_#37_05MOUNTN 765_B1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.11 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:6038.85
MW Contribution:41.77
Bus #Bus NameTypeMW Contribution
24722005FLATG5
50/50
1.795
24721905FLATG4
50/50
32.905
970153AG2-106 GEN
Solar/Wind Harmer
41.768
970513AG2-328 GEN
Solar/Wind Harmer
24.064
970517AG2-330 GEN
Solar/Wind Harmer
21.825
970349AG2-230 GEN
Solar/Wind Harmer
20.118
270043AE2-236 GEN
Solar/Wind Harmer
7.192
274772LINCOLN ;3U
Adder
7.921
247643Z2-116 C
Solar/Wind Harmer
0.089
24642205MAYFLWER
Adder
0.804
274724RIVER EC ;11
Adder
22.4
970707AG2-453 GEN
Solar/Wind Harmer
35.346
972231SS25-0005
Solar/Wind Harmer
11.98
972181SS23-001
Solar/Wind Harmer
7.488
274752CRETE EC ;2U
Adder
6.17
274753CRETE EC ;3U
Adder
6.17
944531AF1-118 GEN
Solar/Wind Harmer
44.133
274826FISK ;BP
Adder
13.763
274802UNIV PARK;5U
Adder
7.329
276772AC2-154 GEN
Solar/Wind Harmer
3.505
276806AD2-047 C O1
Solar/Wind Harmer
13.447
970941AG2-585 GEN
Solar/Wind Harmer
15.712
972228AH1-698 GEN2
Adder
4.656
274800UNIV PARK;3U
Adder
7.326
972038AH1-567 GEN2
Adder
0.459
945111AF1-176 GEN
Solar/Wind Harmer
7.104
276897AD1-100 C
Solar/Wind Harmer
36.403
939351AE1-166 GEN
Solar/Wind Harmer
7.438
274676JOLIET 29;8U
Adder
37.026
274729ELWOOD EC;1P
Adder
20.542
274730ELWOOD EC;6P
Adder
20.542
274734ELWOOD EC;8P
Adder
20.542
274736ELWOOD EC;9P
Adder
20.542
276893AG1-478 C
Solar/Wind Harmer
0.522
970031AG2-029 GEN
Solar/Wind Harmer
37.426
943121AE2-341 GEN
Solar/Wind Harmer
18.7
943591AF1-030 GEN
Solar/Wind Harmer
12.467
270535AF1-215 GEN1
Solar/Wind Harmer
5.641
276694AA1-018 GEN2
Solar/Wind Harmer
7.795
274682WAUKEGAN ;7U
Adder
22.199
964401AG1-302 GEN
Solar/Wind Harmer
11.16
274872LEEDK;1U
Solar/Wind Harmer
0.314
276805AD2-038 GEN
Solar/Wind Harmer
6.294
24721805FLATG3
50/50
1.795
24721705FLATG2
50/50
32.905
24344105CKG2
50/50
10.4
962761AG1-125 GEN
Solar/Wind Harmer
95.789
970149AG2-104 GEN
Solar/Wind Harmer
118.299
970155AG2-107 GEN
Solar/Wind Harmer
41.768
970245AG2-165 GEN
Solar/Wind Harmer
24.064
972207SS24-0001
Solar/Wind Harmer
28.163
274773LINCOLN ;4U
Adder
7.921
274774LINCOLN ;5U
Adder
7.921
274723RIVER EC ;12
Adder
22.661
24639705ELKHART HY
Adder
0.194
276164X3-005 C
Solar/Wind Harmer
0.887
274751CRETE EC ;1U
Adder
6.17
274754CRETE EC ;4U
Adder
6.17
270505AE1-170 C O1
Solar/Wind Harmer
18.909
274812UNIV PK N;8U
Adder
6.308
276776AD2-060 GEN
Solar/Wind Harmer
0.531
274801UNIV PARK;4U
Adder
7.326
945111AF1-176 GEN
Solar/Wind Harmer
22.416
270063AE2-323 C
Solar/Wind Harmer
2.766
941551AE2-152 GEN
Solar/Wind Harmer
5.689
970373AG2-245 GEN
Solar/Wind Harmer
26.342
274676JOLIET 29;8U
Adder
38.397
274674JOLIET 9 ;6U
Adder
19.252
274732ELWOOD EC;7P
Adder
20.542
274871GR RIDGE ;2U
Solar/Wind Harmer
9.606
270449AD2-020 GEN
Solar/Wind Harmer
3.497
943021AE2-325 GEN
Solar/Wind Harmer
4.544
274745AC1-111 GEN9
Adder
6.959
270055AF2-134 C O1
Solar/Wind Harmer
3.76
276691AA1-018 GEN1
Solar/Wind Harmer
0.575
274682WAUKEGAN ;7U
Adder
22.199
274828WAUKEGAN ;BP
Adder
13.634
958381AF2-132 GEN
Solar/Wind Harmer
11.16
960751AF2-366 GEN
Solar/Wind Harmer
3.529
962781AG1-127 GEN
Solar/Wind Harmer
11.696
964861AG1-349 GEN
Solar/Wind Harmer
9.66
971917AH1-482 GEN
Solar/Wind Harmer
11.147
939401AE1-172 GEN
Solar/Wind Harmer
17.125
274872LEEDK;1U
Solar/Wind Harmer
10.089
276901AD2-066 C O1
Solar/Wind Harmer
4.308
965011AG1-365 GEN
Solar/Wind Harmer
12.247
971997AH1-543 GEN
Solar/Wind Harmer
19.257
276861AD2-134 GEN
Solar/Wind Harmer
2.181
274822ROCKFORD ;11
Adder
23.833
972235AH1-702 GEN1
Adder
3.057
274761LEE CO EC;2U
Adder
11.187
274766LEE CO EC;7U
Adder
11.055
970091AG2-072 GEN
Adder
5.254
957471AF2-041 GEN
Solar/Wind Harmer
1.168
959081AF2-199 GEN
Solar/Wind Harmer
0.389
971067AG2-660 GEN
Solar/Wind Harmer
0.091
24721605FLATG1
50/50
1.795
971599AH1-298 GEN
50/50
12.157
962771AG1-126 GEN
Solar/Wind Harmer
95.789
971347AH1-153 GEN
Solar/Wind Harmer
20.118
270071AF1-092 GEN
Solar/Wind Harmer
19.428
960681AF2-359 GEN
Solar/Wind Harmer
4.85
270102X2-052 ST
50/50
2.06
270100X2-052 CT1
50/50
1.898
270101X2-052 CT2
50/50
1.898
970321AG2-212 GEN
Solar/Wind Harmer
24.064
965681AG1-436 GEN
Solar/Wind Harmer
16.046
965791AG1-447 GEN
Solar/Wind Harmer
8.21
274770LINCOLN ;1U
Adder
7.921
274771LINCOLN ;2U
Adder
7.921
270526AF1-158 GEN
Solar/Wind Harmer
5.799
24441505OLIV SLR
Solar/Wind Harmer
0.171
270216AD2-079_GEN
Solar/Wind Harmer
0.772
957891AF2-083 GEN
Solar/Wind Harmer
4.249
960981AF2-389 GEN
Solar/Wind Harmer
1.904
274808UNIV PK N;4U
Adder
6.281
972259AH1-714 GEN
Adder
24.011
274803UNIV PARK;6U
Adder
7.329
274888KELLY CRK;1U
Solar/Wind Harmer
7.421
274887GEN-1.85
Solar/Wind Harmer
6.7
276843GEN-1.7
Solar/Wind Harmer
0.721
958011AF2-095 GEN
Solar/Wind Harmer
18.101
247620Y3-023
Adder
0.578
961051AF2-396 GEN
Solar/Wind Harmer
19.857
961051AF2-396 GEN
Solar/Wind Harmer
9.236
274674JOLIET 9 ;6U
Adder
19.252
274847GR RIDGE ;BU
Solar/Wind Harmer
6.319
971573AH1-285 GEN
Solar/Wind Harmer
10.686
274696ROCKY RD ;4P
Adder
14.093
274695ROCKY RD ;2P
Adder
13.768
274693ROCKY RD ;1P
Adder
13.632
274697ROCKY RD ;3P
Adder
3.74
958481AF2-142 GEN
Solar/Wind Harmer
18.529
274861TOP CROP ;1U
Solar/Wind Harmer
7.483
274862TOP CROP ;2U
Solar/Wind Harmer
6.248
274683WAUKEGAN ;8U
Adder
26.009
274683WAUKEGAN ;8U
Adder
21.925
962691AG1-118 GEN
Solar/Wind Harmer
36.95
970921AG2-575 GEN
Solar/Wind Harmer
12.299
970921AG2-575 GEN
Solar/Wind Harmer
2.86
958491AF2-143 GEN
Solar/Wind Harmer
18.404
970611AG2-400 GEN
Solar/Wind Harmer
12.247
942991AE2-321 GEN
Solar/Wind Harmer
12.245
274879MINONK ;1U
Solar/Wind Harmer
8.259
971333AH1-146 GEN
Solar/Wind Harmer
24.417
971335AH1-147 GEN
Solar/Wind Harmer
24.417
274764LEE CO EC;5U
Adder
11.213
274765LEE CO EC;6U
Adder
11.213
274762LEE CO EC;3U
Adder
11.187
274763LEE CO EC;4U
Adder
11.081
972267AH1-718 GEN
Adder
4.979
971341AH1-150 GEN
Solar/Wind Harmer
0.778
971343AH1-151 GEN
Solar/Wind Harmer
0.778
971771AH1-392 GEN
Solar/Wind Harmer
11.502
274775LINCOLN ;6U
Adder
7.921
274776LINCOLN ;7U
Adder
7.921
274777LINCOLN ;8U
Adder
7.921
971769AH1-391 GEN
Solar/Wind Harmer
12.759
274814UNIV PK N;0U
Adder
6.363
274807UNIV PK N;3U
Adder
6.35
274805UNIV PK N;1U
Adder
6.322
274811UNIV PK N;7U
Adder
6.308
274827FISK ;RP
Adder
9.754
972037AH1-567 GEN1
Adder
0.23
960591AF2-350 GEN
Solar/Wind Harmer
12.57
972227AH1-698 GEN1
Adder
3.278
274687WILL CNTY;4U
Adder
34.988
274687WILL CNTY;4U
Adder
34.988
274675JOLIET 29;7U
Adder
38.397
274675JOLIET 29;7U
Adder
37.026
274731ELWOOD EC;2P
Adder
20.542
274733ELWOOD EC;3P
Adder
20.542
274735ELWOOD EC;4P
Adder
20.542
274728ELWOOD EC;5P
Adder
20.542
970833AG2-524 GEN
Solar/Wind Harmer
10.908
970833AG2-524 GEN
Solar/Wind Harmer
5.074
274746AC1-111 G10
Adder
6.959
274744AC1-111 GEN8
Adder
6.959
24729505KEY G4
Adder
8.06
270536AF1-215 GEN2
Solar/Wind Harmer
5.641
944161AF1-084 GEN
Solar/Wind Harmer
2.741
958391AF2-133 GEN
Solar/Wind Harmer
11.107
971177AH1-047 GEN
Solar/Wind Harmer
7.174
276868AE1-113 GEN
Solar/Wind Harmer
12.387
276882AE2-255 GEN
Solar/Wind Harmer
4.129
971675AH1-338 GEN
Solar/Wind Harmer
21.986
971411AH1-196 GEN
Solar/Wind Harmer
18.32
274863CRW1-WTG
Solar/Wind Harmer
6.802
274864CRW2-WTG
Solar/Wind Harmer
6.802
274823ROCKFORD ;21
Adder
23.66
270054AF2-122 C O1
Solar/Wind Helper
1.539
971171AH1-044 GEN
Solar/Wind Harmer
0.778
959331AF2-224 GEN
Solar/Wind Harmer
12.247
965021AG1-366 GEN
Solar/Wind Harmer
2.848
24441205WTRV SLR C
Solar/Wind Harmer
0.165
276799AD1-013 GEN
Solar/Wind Harmer
2.701
946671AF1-331 GEN
Solar/Wind Harmer
0.511
274855GSG-6 ;RU
Solar/Wind Harmer
4.511
274850MENDOTA H;RU
Solar/Wind Harmer
3.137
276602WESTBROOK C
Solar/Wind Harmer
2.596
276863AD2-134 GEN
Solar/Wind Harmer
2.181
959141AF2-205 GEN
Solar/Wind Harmer
7.375
972236AH1-702 GEN2
Adder
2.658
247604X1-042
Adder
0.505
274760LEE CO EC;1U
Adder
11.187
274767LEE CO EC;8U
Adder
11.055
959091AF2-200 GEN
Solar/Wind Harmer
0.778
944201AF1-088_MTX
Adder
118.46
957141AF2-008_MTX
Adder
59.23
NYPJM->LTFIMP_NY
CLTF
3.756
LGEELTFEXP_LGEE->PJM
CLTF
5.526
WECLTFEXP_WEC->PJM
CLTF
4.63
AG2-052LTFEXP_AG2-052->PJM
LTF
0.285
AH1-155LTFEXP_AH1-155->PJM
LTF
0.428
CPLELTFEXP_CPLE->PJM
CLTF
3.24
CBM West 2LTFEXP_CBM-W2->PJM
CBM
120.262
LAGNLTFEXP_LAGN->PJM
CLTF
16.296
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.027
TVALTFEXP_TVA->PJM
CLTF
7.706
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.812
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.167
MECLTFEXP_MEC->PJM
CLTF
18.496
SIGELTFEXP_SIGE->PJM
CLTF
0.474

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AP_P1-3_MP-765-501T_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.66 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5972.54
MW Contribution:51.58
Bus #Bus NameTypeMW Contribution
24722005FLATG5
50/50
1.795
24721905FLATG4
50/50
32.905
970153AG2-106 GEN
Solar/Wind Harmer
51.584
970513AG2-328 GEN
Solar/Wind Harmer
4.074
970517AG2-330 GEN
Solar/Wind Harmer
24.444
970349AG2-230 GEN
Solar/Wind Harmer
14.036
270043AE2-236 GEN
Solar/Wind Harmer
5.854
274772LINCOLN ;3U
Adder
10.782
247643Z2-116 C
Solar/Wind Harmer
0
24642205MAYFLWER
Adder
0.804
274724RIVER EC ;11
Adder
22.4
970707AG2-453 GEN
Solar/Wind Harmer
28.77
274752CRETE EC ;2U
Adder
10.401
274753CRETE EC ;3U
Adder
10.401
944531AF1-118 GEN
Solar/Wind Harmer
39.427
274826FISK ;BP
Adder
13.763
274802UNIV PARK;5U
Adder
7.329
276806AD2-047 C O1
Solar/Wind Harmer
4.97
970941AG2-585 GEN
Solar/Wind Harmer
10.962
972228AH1-698 GEN2
Adder
4.656
274800UNIV PARK;3U
Adder
7.326
972038AH1-567 GEN2
Adder
0.459
945111AF1-176 GEN
Solar/Wind Harmer
7.104
276897AD1-100 C
Solar/Wind Harmer
0.012
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
37.026
274729ELWOOD EC;1P
Adder
20.542
274730ELWOOD EC;6P
Adder
20.542
274734ELWOOD EC;8P
Adder
20.542
274736ELWOOD EC;9P
Adder
20.542
276893AG1-478 C
Solar/Wind Harmer
0.345
970031AG2-029 GEN
Solar/Wind Harmer
5.657
943121AE2-341 GEN
Solar/Wind Harmer
14.583
943591AF1-030 GEN
Solar/Wind Harmer
9.698
270535AF1-215 GEN1
Solar/Wind Harmer
0.011
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
22.199
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.314
276805AD2-038 GEN
Solar/Wind Harmer
0.003
959331AF2-224 GEN
Solar/Wind Harmer
5.981
965021AG1-366 GEN
Solar/Wind Harmer
2.848
24441205WTRV SLR C
Solar/Wind Harmer
0
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.909
274855GSG-6 ;RU
Solar/Wind Harmer
0.313
274850MENDOTA H;RU
Solar/Wind Harmer
0.1
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.153
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
959091AF2-200 GEN
Solar/Wind Harmer
16.979
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
2.658
247604X1-042
Adder
0.505
970571AG2-364 GEN
Solar/Wind Harmer
16.847
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
11.187
274767LEE CO EC;8U
Adder
11.055
276157O29GEN1
Solar/Wind Harmer
1.347
274878BISHOP HL;2U
Solar/Wind Harmer
0.279
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
8.289
942111AE2-223 GEN
Solar/Wind Harmer
2.682
965931AG1-462 GEN
Solar/Wind Harmer
20.855
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
24.514
959611AF2-252 GEN
Solar/Wind Harmer
2.724
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
3.657
276668AB2-070 GEN1
Solar/Wind Harmer
0.289
247642Z2-115 C
Solar/Wind Harmer
0.003
276621W2-048 GEN
Solar/Wind Harmer
0.395
276838X2-022 GEN2
Solar/Wind Harmer
0.442
970289AG2-191 GEN
Solar/Wind Harmer
0.855
970291AG2-192 GEN
Solar/Wind Harmer
0.777
942481AE2-261 GEN
Solar/Wind Harmer
23.013
24721605FLATG1
50/50
1.795
971599AH1-298 GEN
50/50
12.157
962771AG1-126 GEN
Solar/Wind Harmer
80.781
971347AH1-153 GEN
Solar/Wind Harmer
14.036
270071AF1-092 GEN
Solar/Wind Harmer
17.319
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971771AH1-392 GEN
Solar/Wind Harmer
8.916
274775LINCOLN ;6U
Adder
10.782
274776LINCOLN ;7U
Adder
10.782
274777LINCOLN ;8U
Adder
10.782
971769AH1-391 GEN
Solar/Wind Harmer
9.94
971619AH1-309 GEN
Solar/Wind Harmer
3.958
274814UNIV PK N;0U
Adder
6.363
274807UNIV PK N;3U
Adder
6.35
274805UNIV PK N;1U
Adder
6.322
274811UNIV PK N;7U
Adder
6.308
274827FISK ;RP
Adder
9.754
972037AH1-567 GEN1
Adder
0.23
960591AF2-350 GEN
Solar/Wind Harmer
8.77
972227AH1-698 GEN1
Adder
3.278
274687WILL CNTY;4U
Adder
34.988
274687WILL CNTY;4U
Adder
34.988
274675JOLIET 29;7U
Adder
38.397
274675JOLIET 29;7U
Adder
37.026
274731ELWOOD EC;2P
Adder
20.542
274733ELWOOD EC;3P
Adder
20.542
274735ELWOOD EC;4P
Adder
20.542
274728ELWOOD EC;5P
Adder
20.542
970833AG2-524 GEN
Solar/Wind Harmer
9.589
970833AG2-524 GEN
Solar/Wind Harmer
6.393
274746AC1-111 G10
Adder
6.959
274744AC1-111 GEN8
Adder
6.959
24729505KEY G4
Adder
8.06
270536AF1-215 GEN2
Solar/Wind Harmer
0.011
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971177AH1-047 GEN
Solar/Wind Harmer
5.267
276868AE1-113 GEN
Solar/Wind Harmer
1.713
276882AE2-255 GEN
Solar/Wind Harmer
0.998
971675AH1-338 GEN
Solar/Wind Harmer
3.323
971411AH1-196 GEN
Solar/Wind Harmer
12.781
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
971171AH1-044 GEN
Solar/Wind Harmer
16.979
971611AH1-305 GEN
Solar/Wind Harmer
5.045
274823ROCKFORD ;21
Adder
23.66
276612AE2-035 GEN
Solar/Wind Harmer
0.002
926823AC1-168 GEN
Solar/Wind Harmer
1.432
970169AG2-114 GEN
Solar/Wind Harmer
8.423
971681AH1-341 GEN
Solar/Wind Harmer
13.539
961011AF2-392 GEN
Solar/Wind Harmer
4.902
957751AF2-069 GEN
Solar/Wind Harmer
0.275
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
8.664
941731AE2-173 GEN
Solar/Wind Harmer
6.876
946321AF1-296 GEN
Solar/Wind Harmer
4.594
965101AG1-375 GEN
Solar/Wind Harmer
8.195
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
963841AG1-237 GEN
Solar/Wind Harmer
3.463
945581AF1-223 GEN
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
10.716
971549AH1-272 GEN
Solar/Wind Harmer
16.349
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.289
276848AB2-070 GEN3
Solar/Wind Harmer
0.287
965041AG1-368 GEN
Solar/Wind Harmer
7.862
970289AG2-191 GEN
Solar/Wind Harmer
1.476
971609AH1-304 GEN
Solar/Wind Harmer
1.254
270594AE1-207 GEN
Solar/Wind Harmer
8.574
965051AG1-369 GEN
Solar/Wind Harmer
3.795
944221AF1-090 GEN
Solar/Wind Harmer
4.425
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
270024AE2-089 GEN
Solar/Wind Harmer
0.008
970115AG2-085 GEN
Solar/Wind Harmer
2.943
270054AF2-122 C O1
Solar/Wind Helper
1.539
24721805FLATG3
50/50
1.795
24721705FLATG2
50/50
32.905
24344105CKG2
50/50
10.4
962761AG1-125 GEN
Solar/Wind Harmer
80.781
970149AG2-104 GEN
Solar/Wind Harmer
87.246
970155AG2-107 GEN
Solar/Wind Harmer
51.584
970245AG2-165 GEN
Solar/Wind Harmer
4.074
274773LINCOLN ;4U
Adder
10.782
274774LINCOLN ;5U
Adder
10.782
274723RIVER EC ;12
Adder
22.661
24639705ELKHART HY
Adder
0.194
276164X3-005 C
Solar/Wind Harmer
0
274751CRETE EC ;1U
Adder
10.401
274754CRETE EC ;4U
Adder
10.401
270505AE1-170 C O1
Solar/Wind Harmer
9.235
274812UNIV PK N;8U
Adder
6.308
276776AD2-060 GEN
Solar/Wind Harmer
0.916
274801UNIV PARK;4U
Adder
7.326
945111AF1-176 GEN
Solar/Wind Harmer
15.639
270063AE2-323 C
Solar/Wind Harmer
0.007
941551AE2-152 GEN
Solar/Wind Harmer
0.001
970373AG2-245 GEN
Solar/Wind Harmer
18.378
274676JOLIET 29;8U
Adder
38.397
274674JOLIET 9 ;6U
Adder
19.252
274732ELWOOD EC;7P
Adder
20.542
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
4.544
274745AC1-111 GEN9
Adder
6.959
270055AF2-134 C O1
Solar/Wind Harmer
0.007
276691AA1-018 GEN1
Solar/Wind Harmer
1.044
274682WAUKEGAN ;7U
Adder
22.199
274828WAUKEGAN ;BP
Adder
13.634
958381AF2-132 GEN
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
8.166
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.147
939401AE1-172 GEN
Solar/Wind Harmer
6.413
274872LEEDK;1U
Solar/Wind Harmer
0.005
276901AD2-066 C O1
Solar/Wind Harmer
0.008
965011AG1-365 GEN
Solar/Wind Harmer
8.544
971997AH1-543 GEN
Solar/Wind Harmer
4.478
276861AD2-134 GEN
Solar/Wind Harmer
0.153
957471AF2-041 GEN
Solar/Wind Harmer
25.469
959081AF2-199 GEN
Solar/Wind Harmer
8.49
971067AG2-660 GEN
Solar/Wind Harmer
2.83
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
10.593
274822ROCKFORD ;11
Adder
23.833
972235AH1-702 GEN1
Adder
3.057
970819AG2-516 GEN
Solar/Wind Harmer
10.134
971475AH1-234 GEN
Solar/Wind Harmer
4.092
970569AG2-363 GEN
Solar/Wind Harmer
25.271
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
11.187
274766LEE CO EC;7U
Adder
11.055
276158O29GEN2
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
2.438
274877BISHOP HL;1U
Solar/Wind Harmer
0.279
24791305MDL-5G
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0.003
939741AE1-205 GEN
Solar/Wind Harmer
11.552
958861AF2-177 GEN
Solar/Wind Harmer
3.551
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
972175AH1-670 GEN
Solar/Wind Harmer
6.643
945371AF1-202 GEN
Solar/Wind Harmer
0.001
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
3.078
963741AG1-226 GEN
Solar/Wind Harmer
18.629
276615X2-022 GEN
Solar/Wind Harmer
0.082
970291AG2-192 GEN
Solar/Wind Harmer
1.01
965911AG1-460 GEN
Solar/Wind Harmer
1.539
270032AE2-172
Solar/Wind Harmer
5.104
247521TR3_G114
Solar/Wind Harmer
0.277
270246TR4_N_V150
Solar/Wind Harmer
0.049
944231AF1-091 GEN
Solar/Wind Harmer
2.021
276903AD2-071 C
Solar/Wind Harmer
8.405
270005AE1-210 C O1
Solar/Wind Harmer
1.614
965031AG1-367 GEN
Solar/Wind Harmer
7.45
24695305TIMB G C
Solar/Wind Harmer
0.002
970333AG2-219 GEN
Solar/Wind Harmer
4.707
270102X2-052 ST
50/50
2.06
270100X2-052 CT1
50/50
1.898
270101X2-052 CT2
50/50
1.898
970321AG2-212 GEN
Solar/Wind Harmer
4.074
965681AG1-436 GEN
Solar/Wind Harmer
11.195
965791AG1-447 GEN
Solar/Wind Harmer
8.21
274770LINCOLN ;1U
Adder
10.782
274771LINCOLN ;2U
Adder
10.782
270526AF1-158 GEN
Solar/Wind Harmer
0.011
24441505OLIV SLR
Solar/Wind Harmer
0
270216AD2-079_GEN
Solar/Wind Harmer
0.001
957891AF2-083 GEN
Solar/Wind Harmer
0.001
274808UNIV PK N;4U
Adder
6.281
972259AH1-714 GEN
Adder
24.011
274803UNIV PARK;6U
Adder
7.329
274888KELLY CRK;1U
Solar/Wind Harmer
0.515
274887GEN-1.85
Solar/Wind Harmer
0.231
276843GEN-1.7
Solar/Wind Harmer
0.284
958011AF2-095 GEN
Solar/Wind Harmer
12.628
247620Y3-023
Adder
0.578
961051AF2-396 GEN
Solar/Wind Harmer
17.455
961051AF2-396 GEN
Solar/Wind Harmer
11.637
274674JOLIET 9 ;6U
Adder
19.252
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
971573AH1-285 GEN
Solar/Wind Harmer
1.615
274696ROCKY RD ;4P
Adder
14.093
274695ROCKY RD ;2P
Adder
13.768
274693ROCKY RD ;1P
Adder
13.632
274697ROCKY RD ;3P
Adder
3.74
958481AF2-142 GEN
Solar/Wind Harmer
12.927
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
1.166
274683WAUKEGAN ;8U
Adder
26.009
274683WAUKEGAN ;8U
Adder
21.925
962691AG1-118 GEN
Solar/Wind Harmer
25.779
970921AG2-575 GEN
Solar/Wind Harmer
8.581
970921AG2-575 GEN
Solar/Wind Harmer
2.86
958491AF2-143 GEN
Solar/Wind Harmer
12.84
970611AG2-400 GEN
Solar/Wind Harmer
8.544
970627AG2-408 GEN
Solar/Wind Harmer
2.563
942991AE2-321 GEN
Solar/Wind Harmer
9.539
274879MINONK ;1U
Solar/Wind Harmer
0.36
971333AH1-146 GEN
Solar/Wind Harmer
17.035
971335AH1-147 GEN
Solar/Wind Harmer
17.035
971341AH1-150 GEN
Solar/Wind Harmer
16.979
971343AH1-151 GEN
Solar/Wind Harmer
16.979
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
274856ECOGROVE ;U1
Solar/Wind Harmer
0.199
276611AD2-172 GEN
Solar/Wind Harmer
0.002
938861AE1-114 GEN
Solar/Wind Harmer
4.764
274764LEE CO EC;5U
Adder
11.213
274765LEE CO EC;6U
Adder
11.213
274762LEE CO EC;3U
Adder
11.187
274763LEE CO EC;4U
Adder
11.081
276603SUBLETTE C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
972267AH1-718 GEN
Adder
4.979
276741O09 GEN1
Solar/Wind Harmer
0.297
276708O09 GEN2
Solar/Wind Harmer
0.297
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.327
276646AC1-214 GEN2
Solar/Wind Harmer
0.327
944541AF1-119 GEN
Solar/Wind Harmer
0.557
960971AF2-388 GEN
Solar/Wind Harmer
4.876
276782AC1-033 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
2.724
966841AG1-555 GEN
Solar/Wind Harmer
0.919
942221AE2-234 GEN
Solar/Wind Harmer
0.04
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
970241AG2-163 GEN
Solar/Wind Harmer
4.592
270599AE1-208 GEN
Solar/Wind Harmer
7.039
270031AE2-169
Solar/Wind Harmer
4.223
276916AD2-100_GEN
Solar/Wind Harmer
16.09
276911AD2-131_GEN
Solar/Wind Harmer
1.06
971613AH1-306 GEN
Solar/Wind Harmer
3.675
945391AF1-204 GEN
Solar/Wind Harmer
7.93
960441AF2-335 GEN
Solar/Wind Harmer
7.358
970239AG2-162 GEN
Solar/Wind Harmer
1.646
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.049
970193AG2-126 GEN
Solar/Wind Harmer
11.195
958821AF2-173 GEN
Solar/Wind Harmer
10.43
270004AE1-209 GEN
Solar/Wind Harmer
1.614
971617AH1-308 GEN
Solar/Wind Harmer
6.153
970243AG2-164 GEN
Solar/Wind Harmer
3.851
970519AG2-331 GEN
Solar/Wind Harmer
17.115
970699AG2-449 GEN
Solar/Wind Harmer
1.646
944201AF1-088_MTX
Adder
118.46
957141AF2-008_MTX
Adder
32.732
NYPJM->LTFIMP_NY
CLTF
3.756
LGEELTFEXP_LGEE->PJM
CLTF
5.526
WECLTFEXP_WEC->PJM
CLTF
4.63
AG2-052LTFEXP_AG2-052->PJM
LTF
0.285
AH1-155LTFEXP_AH1-155->PJM
LTF
0.428
CPLELTFEXP_CPLE->PJM
CLTF
3.24
CBM West 2LTFEXP_CBM-W2->PJM
CBM
120.262
LAGNLTFEXP_LAGN->PJM
CLTF
16.296
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.027
TVALTFEXP_TVA->PJM
CLTF
7.706
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.812
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.167
MECLTFEXP_MEC->PJM
CLTF
18.496
SIGELTFEXP_SIGE->PJM
CLTF
0.474

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AEP_P4_#8085_05MARYSV 345_H_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8085_05MARYSV 345_H_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.94 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5528.24
MW Contribution:48.72
Bus #Bus NameTypeMW Contribution
24722005FLATG5
50/50
1.463
24721905FLATG4
50/50
26.818
970153AG2-106 GEN
Solar/Wind Harmer
48.717
970513AG2-328 GEN
Solar/Wind Harmer
21.746
970517AG2-330 GEN
Solar/Wind Harmer
19.723
970349AG2-230 GEN
Solar/Wind Harmer
18.177
274772LINCOLN ;3U
Adder
7.008
270043AE2-236 GEN
Solar/Wind Harmer
6.178
247643Z2-116 C
Solar/Wind Harmer
0.078
274724RIVER EC ;11
Adder
19.691
970707AG2-453 GEN
Solar/Wind Harmer
31.101
24642205MAYFLWER
Adder
0.705
972231SS25-0005
Solar/Wind Harmer
10.514
972181SS23-001
Solar/Wind Harmer
6.571
274752CRETE EC ;2U
Adder
5.415
274753CRETE EC ;3U
Adder
5.415
274826FISK ;BP
Adder
12.072
972228AH1-698 GEN2
Adder
4.084
274802UNIV PARK;5U
Adder
6.427
276772AC2-154 GEN
Solar/Wind Harmer
3.074
276806AD2-047 C O1
Solar/Wind Harmer
11.793
970941AG2-585 GEN
Solar/Wind Harmer
13.78
274800UNIV PARK;3U
Adder
6.424
972038AH1-567 GEN2
Adder
0.402
276897AD1-100 C
Solar/Wind Harmer
31.897
939351AE1-166 GEN
Solar/Wind Harmer
6.517
274676JOLIET 29;8U
Adder
32.424
945111AF1-176 GEN
Solar/Wind Harmer
6.195
274729ELWOOD EC;1P
Adder
17.974
274730ELWOOD EC;6P
Adder
17.974
274734ELWOOD EC;8P
Adder
17.974
274736ELWOOD EC;9P
Adder
17.974
276893AG1-478 C
Solar/Wind Harmer
0.456
943121AE2-341 GEN
Solar/Wind Harmer
16.363
943591AF1-030 GEN
Solar/Wind Harmer
10.909
274682WAUKEGAN ;7U
Adder
19.342
276694AA1-018 GEN2
Solar/Wind Harmer
6.783
270535AF1-215 GEN1
Solar/Wind Harmer
4.874
274872LEEDK;1U
Solar/Wind Harmer
0.273
276805AD2-038 GEN
Solar/Wind Harmer
5.46
944531AF1-118 GEN
Solar/Wind Harmer
37.24
24441205WTRV SLR C
Solar/Wind Harmer
0.143
276799AD1-013 GEN
Solar/Wind Harmer
2.342
946671AF1-331 GEN
Solar/Wind Harmer
0.444
274855GSG-6 ;RU
Solar/Wind Harmer
3.911
274850MENDOTA H;RU
Solar/Wind Harmer
2.719
276602WESTBROOK C
Solar/Wind Harmer
2.251
276863AD2-134 GEN
Solar/Wind Harmer
1.891
964401AG1-302 GEN
Solar/Wind Harmer
9.583
247604X1-042
Adder
0.437
972236AH1-702 GEN2
Adder
2.298
274760LEE CO EC;1U
Adder
9.633
274767LEE CO EC;8U
Adder
9.519
241955AC1-078 GEN
Solar/Wind Helper
2.355
241974AD2-163_GEN2
Solar/Wind Helper
1.908
960801AF2-371 GEN
Solar/Wind Helper
0.993
964871AG1-351 GEN
Solar/Wind Helper
0.686
959091AF2-200 GEN
Solar/Wind Harmer
15.934
24344105CKG2
50/50
9.547
24721805FLATG3
50/50
1.463
24721705FLATG2
50/50
26.818
962761AG1-125 GEN
Solar/Wind Harmer
111.725
970149AG2-104 GEN
Solar/Wind Harmer
137.98
970155AG2-107 GEN
Solar/Wind Harmer
48.717
970245AG2-165 GEN
Solar/Wind Harmer
21.746
972207SS24-0001
Solar/Wind Harmer
24.918
274773LINCOLN ;4U
Adder
7.008
274774LINCOLN ;5U
Adder
7.008
274723RIVER EC ;12
Adder
19.918
276164X3-005 C
Solar/Wind Harmer
0.779
274751CRETE EC ;1U
Adder
5.415
274754CRETE EC ;4U
Adder
5.415
274812UNIV PK N;8U
Adder
5.534
270505AE1-170 C O1
Solar/Wind Harmer
16.56
276776AD2-060 GEN
Solar/Wind Harmer
0.466
274801UNIV PARK;4U
Adder
6.424
941551AE2-152 GEN
Solar/Wind Harmer
4.985
24639705ELKHART HY
Adder
0.168
274676JOLIET 29;8U
Adder
33.625
945111AF1-176 GEN
Solar/Wind Harmer
19.547
274674JOLIET 9 ;6U
Adder
16.852
274732ELWOOD EC;7P
Adder
17.974
274871GR RIDGE ;2U
Solar/Wind Harmer
8.405
970373AG2-245 GEN
Solar/Wind Harmer
22.924
274745AC1-111 GEN9
Adder
6.085
270449AD2-020 GEN
Solar/Wind Harmer
3.051
943021AE2-325 GEN
Solar/Wind Harmer
3.965
274682WAUKEGAN ;7U
Adder
19.342
274828WAUKEGAN ;BP
Adder
11.875
276691AA1-018 GEN1
Solar/Wind Harmer
0.5
270055AF2-134 C O1
Solar/Wind Harmer
3.249
960751AF2-366 GEN
Solar/Wind Harmer
3.069
962781AG1-127 GEN
Solar/Wind Harmer
10.173
274872LEEDK;1U
Solar/Wind Harmer
8.77
939401AE1-172 GEN
Solar/Wind Harmer
14.843
276901AD2-066 C O1
Solar/Wind Harmer
3.736
270063AE2-323 C
Solar/Wind Harmer
2.34
971997AH1-543 GEN
Solar/Wind Harmer
16.683
276861AD2-134 GEN
Solar/Wind Harmer
1.891
958381AF2-132 GEN
Solar/Wind Harmer
9.583
964861AG1-349 GEN
Solar/Wind Harmer
8.289
971917AH1-482 GEN
Solar/Wind Harmer
9.566
274822ROCKFORD ;11
Adder
20.615
972235AH1-702 GEN1
Adder
2.642
274761LEE CO EC;2U
Adder
9.633
274766LEE CO EC;7U
Adder
9.519
270349AD2-093_GEN
Solar/Wind Helper
2.063
957471AF2-041 GEN
Solar/Wind Harmer
23.901
959081AF2-199 GEN
Solar/Wind Harmer
7.967
971067AG2-660 GEN
Solar/Wind Harmer
1.853
971599AH1-298 GEN
50/50
10.874
24721605FLATG1
50/50
1.463
962771AG1-126 GEN
Solar/Wind Harmer
111.725
971347AH1-153 GEN
Solar/Wind Harmer
18.177
960681AF2-359 GEN
Solar/Wind Harmer
4.287
274775LINCOLN ;6U
Adder
7.008
274776LINCOLN ;7U
Adder
7.008
274777LINCOLN ;8U
Adder
7.008
971771AH1-392 GEN
Solar/Wind Harmer
10.12
971769AH1-391 GEN
Solar/Wind Harmer
11.239
270071AF1-092 GEN
Solar/Wind Harmer
16.631
274814UNIV PK N;0U
Adder
5.583
274807UNIV PK N;3U
Adder
5.57
274805UNIV PK N;1U
Adder
5.546
274811UNIV PK N;7U
Adder
5.534
274827FISK ;RP
Adder
8.556
972227AH1-698 GEN1
Adder
2.876
972037AH1-567 GEN1
Adder
0.202
960591AF2-350 GEN
Solar/Wind Harmer
11.024
274687WILL CNTY;4U
Adder
30.645
274687WILL CNTY;4U
Adder
30.645
274675JOLIET 29;7U
Adder
33.626
274675JOLIET 29;7U
Adder
32.425
274731ELWOOD EC;2P
Adder
17.974
274733ELWOOD EC;3P
Adder
17.974
274735ELWOOD EC;4P
Adder
17.974
274728ELWOOD EC;5P
Adder
17.974
970833AG2-524 GEN
Solar/Wind Harmer
9.546
970833AG2-524 GEN
Solar/Wind Harmer
4.44
274746AC1-111 G10
Adder
6.085
274744AC1-111 GEN8
Adder
6.085
944161AF1-084 GEN
Solar/Wind Harmer
2.388
270536AF1-215 GEN2
Solar/Wind Harmer
4.874
971177AH1-047 GEN
Solar/Wind Harmer
6.227
276868AE1-113 GEN
Solar/Wind Harmer
10.734
276882AE2-255 GEN
Solar/Wind Harmer
3.578
971675AH1-338 GEN
Solar/Wind Harmer
19.065
971411AH1-196 GEN
Solar/Wind Harmer
15.886
274823ROCKFORD ;21
Adder
20.466
24729505KEY G4
Adder
6.743
270054AF2-122 C O1
Solar/Wind Helper
2.141
270520AE2-214 GEN
Solar/Wind Helper
6.625
270284AF1-227 GEN1
Solar/Wind Helper
2.625
270286AF1-227 GEN2
Solar/Wind Helper
0.963
270287AF1-227 GEN3
Solar/Wind Helper
0.963
253383AE2-342_GEN
Solar/Wind Helper
0.859
241973AD2-163_GEN1
Solar/Wind Helper
1.908
945631AF1-228 GEN
Solar/Wind Helper
1.875
971171AH1-044 GEN
Solar/Wind Harmer
15.934
270102X2-052 ST
50/50
1.824
270100X2-052 CT1
50/50
1.681
270101X2-052 CT2
50/50
1.681
970321AG2-212 GEN
Solar/Wind Harmer
21.746
965681AG1-436 GEN
Solar/Wind Harmer
14.185
965791AG1-447 GEN
Solar/Wind Harmer
7.258
274770LINCOLN ;1U
Adder
7.008
274771LINCOLN ;2U
Adder
7.008
270526AF1-158 GEN
Solar/Wind Harmer
5.107
24441505OLIV SLR
Solar/Wind Harmer
0.151
270216AD2-079_GEN
Solar/Wind Harmer
0.675
972259AH1-714 GEN
Adder
21.085
274808UNIV PK N;4U
Adder
5.51
274803UNIV PARK;6U
Adder
6.427
274888KELLY CRK;1U
Solar/Wind Harmer
6.509
274887GEN-1.85
Solar/Wind Harmer
5.876
276843GEN-1.7
Solar/Wind Harmer
0.632
958011AF2-095 GEN
Solar/Wind Harmer
15.875
957891AF2-083 GEN
Solar/Wind Harmer
3.717
960981AF2-389 GEN
Solar/Wind Harmer
1.665
274674JOLIET 9 ;6U
Adder
16.852
274847GR RIDGE ;BU
Solar/Wind Harmer
5.529
961051AF2-396 GEN
Solar/Wind Harmer
17.321
961051AF2-396 GEN
Solar/Wind Harmer
8.056
971573AH1-285 GEN
Solar/Wind Harmer
9.336
247620Y3-023
Adder
0.498
274696ROCKY RD ;4P
Adder
12.286
274695ROCKY RD ;2P
Adder
12.003
274693ROCKY RD ;1P
Adder
11.884
274697ROCKY RD ;3P
Adder
3.261
274683WAUKEGAN ;8U
Adder
22.655
274683WAUKEGAN ;8U
Adder
19.097
958481AF2-142 GEN
Solar/Wind Harmer
16.124
274861TOP CROP ;1U
Solar/Wind Harmer
6.51
274862TOP CROP ;2U
Solar/Wind Harmer
5.436
962691AG1-118 GEN
Solar/Wind Harmer
32.158
970921AG2-575 GEN
Solar/Wind Harmer
10.697
970921AG2-575 GEN
Solar/Wind Harmer
2.488
958491AF2-143 GEN
Solar/Wind Harmer
15.964
942991AE2-321 GEN
Solar/Wind Harmer
10.629
274879MINONK ;1U
Solar/Wind Harmer
7.157
971333AH1-146 GEN
Solar/Wind Harmer
21.169
971335AH1-147 GEN
Solar/Wind Harmer
21.169
274764LEE CO EC;5U
Adder
9.655
274765LEE CO EC;6U
Adder
9.655
274762LEE CO EC;3U
Adder
9.633
274763LEE CO EC;4U
Adder
9.542
972267AH1-718 GEN
Adder
4.276
270471AD2-092_GEN
Solar/Wind Helper
2.063
946101AF1-275 GEN
Solar/Wind Helper
0.83
241960AC2-195 GEN
Solar/Wind Helper
1.452
971341AH1-150 GEN
Solar/Wind Harmer
15.934
971343AH1-151 GEN
Solar/Wind Harmer
15.934
NYPJM->LTFIMP_NY
CLTF
2.504
LGEELTFEXP_LGEE->PJM
CLTF
3.288
WECLTFEXP_WEC->PJM
CLTF
4
AG2-052LTFEXP_AG2-052->PJM
LTF
0.245
AH1-155LTFEXP_AH1-155->PJM
LTF
0.368
CPLELTFEXP_CPLE->PJM
CLTF
1.947
CBM West 2LTFEXP_CBM-W2->PJM
CBM
88.828
LAGNLTFEXP_LAGN->PJM
CLTF
11.716
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.038
TVALTFEXP_TVA->PJM
CLTF
5.258
CBM West 1LTFEXP_CBM-W1->PJM
CBM
116.721
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.427
MECLTFEXP_MEC->PJM
CLTF
15.3
SIGELTFEXP_SIGE->PJM
CLTF
0.326

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AEP_P2-2_#8072_05MARYSV 765_2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#8072_05MARYSV 765_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:119.76 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5474.17
MW Contribution:48.95
Bus #Bus NameTypeMW Contribution
24721805FLATG3
50/50
1.475
24721705FLATG2
50/50
27.034
24344105CKG2
50/50
9.41
962761AG1-125 GEN
Solar/Wind Harmer
112.25
970149AG2-104 GEN
Solar/Wind Harmer
138.629
970155AG2-107 GEN
Solar/Wind Harmer
48.946
970245AG2-165 GEN
Solar/Wind Harmer
21.445
972207SS24-0001
Solar/Wind Harmer
24.53
274773LINCOLN ;4U
Adder
6.899
274774LINCOLN ;5U
Adder
6.899
274723RIVER EC ;12
Adder
19.592
276164X3-005 C
Solar/Wind Harmer
0.767
274751CRETE EC ;1U
Adder
5.325
274754CRETE EC ;4U
Adder
5.325
274812UNIV PK N;8U
Adder
5.443
276776AD2-060 GEN
Solar/Wind Harmer
0.459
274801UNIV PARK;4U
Adder
6.32
270505AE1-170 C O1
Solar/Wind Harmer
16.232
941551AE2-152 GEN
Solar/Wind Harmer
4.905
274676JOLIET 29;8U
Adder
33.085
274674JOLIET 9 ;6U
Adder
16.581
274732ELWOOD EC;7P
Adder
17.685
274871GR RIDGE ;2U
Solar/Wind Harmer
8.271
945111AF1-176 GEN
Solar/Wind Harmer
19.147
24639705ELKHART HY
Adder
0.165
970373AG2-245 GEN
Solar/Wind Harmer
22.522
274745AC1-111 GEN9
Adder
5.988
270449AD2-020 GEN
Solar/Wind Harmer
2.989
943021AE2-325 GEN
Solar/Wind Harmer
3.884
274682WAUKEGAN ;7U
Adder
19.032
274828WAUKEGAN ;BP
Adder
11.685
276691AA1-018 GEN1
Solar/Wind Harmer
0.492
270055AF2-134 C O1
Solar/Wind Harmer
3.192
960751AF2-366 GEN
Solar/Wind Harmer
3.02
962781AG1-127 GEN
Solar/Wind Harmer
10.01
274872LEEDK;1U
Solar/Wind Harmer
8.629
939401AE1-172 GEN
Solar/Wind Harmer
14.602
276901AD2-066 C O1
Solar/Wind Harmer
3.675
971997AH1-543 GEN
Solar/Wind Harmer
16.413
276861AD2-134 GEN
Solar/Wind Harmer
1.861
958381AF2-132 GEN
Solar/Wind Harmer
9.412
274822ROCKFORD ;11
Adder
20.284
972235AH1-702 GEN1
Adder
2.6
274761LEE CO EC;2U
Adder
9.477
274766LEE CO EC;7U
Adder
9.366
270349AD2-093_GEN
Solar/Wind Helper
1.808
957471AF2-041 GEN
Solar/Wind Harmer
28.38
959081AF2-199 GEN
Solar/Wind Harmer
9.46
971067AG2-660 GEN
Solar/Wind Harmer
2.2
24721605FLATG1
50/50
1.475
24722005FLATG5
50/50
1.475
24721905FLATG4
50/50
27.034
970153AG2-106 GEN
Solar/Wind Harmer
48.946
970513AG2-328 GEN
Solar/Wind Harmer
21.445
970517AG2-330 GEN
Solar/Wind Harmer
19.45
970349AG2-230 GEN
Solar/Wind Harmer
17.888
274772LINCOLN ;3U
Adder
6.899
270043AE2-236 GEN
Solar/Wind Harmer
6.024
247643Z2-116 C
Solar/Wind Harmer
0.076
274724RIVER EC ;11
Adder
19.369
970707AG2-453 GEN
Solar/Wind Harmer
30.611
972231SS25-0005
Solar/Wind Harmer
10.34
972181SS23-001
Solar/Wind Harmer
6.462
274752CRETE EC ;2U
Adder
5.325
274753CRETE EC ;3U
Adder
5.325
24642205MAYFLWER
Adder
0.691
274826FISK ;BP
Adder
11.877
972228AH1-698 GEN2
Adder
4.018
276772AC2-154 GEN
Solar/Wind Harmer
3.025
276806AD2-047 C O1
Solar/Wind Harmer
11.603
970941AG2-585 GEN
Solar/Wind Harmer
13.558
274802UNIV PARK;5U
Adder
6.323
274800UNIV PARK;3U
Adder
6.32
972038AH1-567 GEN2
Adder
0.396
276897AD1-100 C
Solar/Wind Harmer
31.386
939351AE1-166 GEN
Solar/Wind Harmer
6.413
274676JOLIET 29;8U
Adder
31.903
274729ELWOOD EC;1P
Adder
17.685
274730ELWOOD EC;6P
Adder
17.685
274734ELWOOD EC;8P
Adder
17.685
274736ELWOOD EC;9P
Adder
17.685
276893AG1-478 C
Solar/Wind Harmer
0.449
943121AE2-341 GEN
Solar/Wind Harmer
16.103
943591AF1-030 GEN
Solar/Wind Harmer
10.736
945111AF1-176 GEN
Solar/Wind Harmer
6.068
274682WAUKEGAN ;7U
Adder
19.032
276694AA1-018 GEN2
Solar/Wind Harmer
6.673
270535AF1-215 GEN1
Solar/Wind Harmer
4.788
274872LEEDK;1U
Solar/Wind Harmer
0.269
276805AD2-038 GEN
Solar/Wind Harmer
5.371
276799AD1-013 GEN
Solar/Wind Harmer
2.305
946671AF1-331 GEN
Solar/Wind Harmer
0.436
274855GSG-6 ;RU
Solar/Wind Harmer
3.848
274850MENDOTA H;RU
Solar/Wind Harmer
2.676
276602WESTBROOK C
Solar/Wind Harmer
2.215
276863AD2-134 GEN
Solar/Wind Harmer
1.861
24441205WTRV SLR C
Solar/Wind Harmer
0.14
944531AF1-118 GEN
Solar/Wind Harmer
36.351
964401AG1-302 GEN
Solar/Wind Harmer
9.412
972236AH1-702 GEN2
Adder
2.261
247604X1-042
Adder
0.428
274760LEE CO EC;1U
Adder
9.477
274767LEE CO EC;8U
Adder
9.366
241955AC1-078 GEN
Solar/Wind Helper
2.287
241974AD2-163_GEN2
Solar/Wind Helper
1.851
960801AF2-371 GEN
Solar/Wind Helper
0.963
964871AG1-351 GEN
Solar/Wind Helper
0.665
959091AF2-200 GEN
Solar/Wind Harmer
18.92
971599AH1-298 GEN
50/50
10.653
962771AG1-126 GEN
Solar/Wind Harmer
112.25
971347AH1-153 GEN
Solar/Wind Harmer
17.888
960681AF2-359 GEN
Solar/Wind Harmer
4.214
274775LINCOLN ;6U
Adder
6.899
274776LINCOLN ;7U
Adder
6.899
274777LINCOLN ;8U
Adder
6.899
971769AH1-391 GEN
Solar/Wind Harmer
11.035
971771AH1-392 GEN
Solar/Wind Harmer
9.928
274814UNIV PK N;0U
Adder
5.491
274807UNIV PK N;3U
Adder
5.479
274805UNIV PK N;1U
Adder
5.455
274811UNIV PK N;7U
Adder
5.443
274827FISK ;RP
Adder
8.417
972227AH1-698 GEN1
Adder
2.829
960591AF2-350 GEN
Solar/Wind Harmer
10.846
972037AH1-567 GEN1
Adder
0.198
270071AF1-092 GEN
Solar/Wind Harmer
16.243
274687WILL CNTY;4U
Adder
30.151
274687WILL CNTY;4U
Adder
30.151
274675JOLIET 29;7U
Adder
33.085
274675JOLIET 29;7U
Adder
31.904
970833AG2-524 GEN
Solar/Wind Harmer
9.393
970833AG2-524 GEN
Solar/Wind Harmer
4.369
274731ELWOOD EC;2P
Adder
17.685
274733ELWOOD EC;3P
Adder
17.685
274735ELWOOD EC;4P
Adder
17.685
274728ELWOOD EC;5P
Adder
17.685
274746AC1-111 G10
Adder
5.988
274744AC1-111 GEN8
Adder
5.988
944161AF1-084 GEN
Solar/Wind Harmer
2.339
270536AF1-215 GEN2
Solar/Wind Harmer
4.788
971177AH1-047 GEN
Solar/Wind Harmer
6.127
276868AE1-113 GEN
Solar/Wind Harmer
10.56
276882AE2-255 GEN
Solar/Wind Harmer
3.52
971675AH1-338 GEN
Solar/Wind Harmer
18.759
971411AH1-196 GEN
Solar/Wind Harmer
15.631
274823ROCKFORD ;21
Adder
20.137
24729505KEY G4
Adder
6.578
270054AF2-122 C O1
Solar/Wind Helper
2.088
270520AE2-214 GEN
Solar/Wind Helper
6.396
253383AE2-342_GEN
Solar/Wind Helper
0.847
270284AF1-227 GEN1
Solar/Wind Helper
2.356
270286AF1-227 GEN2
Solar/Wind Helper
0.864
270287AF1-227 GEN3
Solar/Wind Helper
0.864
241973AD2-163_GEN1
Solar/Wind Helper
1.851
945631AF1-228 GEN
Solar/Wind Helper
1.836
971171AH1-044 GEN
Solar/Wind Harmer
18.92
270102X2-052 ST
50/50
1.793
270100X2-052 CT1
50/50
1.652
270101X2-052 CT2
50/50
1.652
970321AG2-212 GEN
Solar/Wind Harmer
21.445
965681AG1-436 GEN
Solar/Wind Harmer
13.942
965791AG1-447 GEN
Solar/Wind Harmer
7.133
274770LINCOLN ;1U
Adder
6.899
274771LINCOLN ;2U
Adder
6.899
24441505OLIV SLR
Solar/Wind Harmer
0.148
270526AF1-158 GEN
Solar/Wind Harmer
5.013
270216AD2-079_GEN
Solar/Wind Harmer
0.661
972259AH1-714 GEN
Adder
20.75
274808UNIV PK N;4U
Adder
5.42
274888KELLY CRK;1U
Solar/Wind Harmer
6.404
274887GEN-1.85
Solar/Wind Harmer
5.781
276843GEN-1.7
Solar/Wind Harmer
0.622
958011AF2-095 GEN
Solar/Wind Harmer
15.619
274803UNIV PARK;6U
Adder
6.323
957891AF2-083 GEN
Solar/Wind Harmer
3.643
960981AF2-389 GEN
Solar/Wind Harmer
1.632
274674JOLIET 9 ;6U
Adder
16.581
274847GR RIDGE ;BU
Solar/Wind Harmer
5.441
961051AF2-396 GEN
Solar/Wind Harmer
16.968
961051AF2-396 GEN
Solar/Wind Harmer
7.892
971573AH1-285 GEN
Solar/Wind Harmer
9.188
274695ROCKY RD ;2P
Adder
11.811
274693ROCKY RD ;1P
Adder
11.694
274697ROCKY RD ;3P
Adder
3.208
274696ROCKY RD ;4P
Adder
12.089
274683WAUKEGAN ;8U
Adder
22.291
274683WAUKEGAN ;8U
Adder
18.791
958481AF2-142 GEN
Solar/Wind Harmer
15.862
274861TOP CROP ;1U
Solar/Wind Harmer
6.405
274862TOP CROP ;2U
Solar/Wind Harmer
5.348
247620Y3-023
Adder
0.486
962691AG1-118 GEN
Solar/Wind Harmer
31.644
970921AG2-575 GEN
Solar/Wind Harmer
10.526
970921AG2-575 GEN
Solar/Wind Harmer
2.448
958491AF2-143 GEN
Solar/Wind Harmer
15.704
942991AE2-321 GEN
Solar/Wind Harmer
10.459
274879MINONK ;1U
Solar/Wind Harmer
7.04
971333AH1-146 GEN
Solar/Wind Harmer
20.829
971335AH1-147 GEN
Solar/Wind Harmer
20.829
274764LEE CO EC;5U
Adder
9.5
274765LEE CO EC;6U
Adder
9.5
274762LEE CO EC;3U
Adder
9.477
274763LEE CO EC;4U
Adder
9.388
972267AH1-718 GEN
Adder
4.207
946101AF1-275 GEN
Solar/Wind Helper
0.801
270471AD2-092_GEN
Solar/Wind Helper
1.808
241960AC2-195 GEN
Solar/Wind Helper
1.411
971341AH1-150 GEN
Solar/Wind Harmer
18.92
971343AH1-151 GEN
Solar/Wind Harmer
18.92
NYPJM->LTFIMP_NY
CLTF
2.462
LGEELTFEXP_LGEE->PJM
CLTF
3.192
WECLTFEXP_WEC->PJM
CLTF
3.935
AG2-052LTFEXP_AG2-052->PJM
LTF
0.241
AH1-155LTFEXP_AH1-155->PJM
LTF
0.362
CPLELTFEXP_CPLE->PJM
CLTF
1.972
CBM West 2LTFEXP_CBM-W2->PJM
CBM
87.287
LAGNLTFEXP_LAGN->PJM
CLTF
11.551
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.064
TVALTFEXP_TVA->PJM
CLTF
5.187
CBM West 1LTFEXP_CBM-W1->PJM
CBM
113.826
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.114
MECLTFEXP_MEC->PJM
CLTF
15.05
SIGELTFEXP_SIGE->PJM
CLTF
0.318

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AEP_P1-2_#706_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#706_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.43 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5322.01
MW Contribution:76.66
Bus #Bus NameTypeMW Contribution
24721805FLATG3
50/50
5.145
24721705FLATG2
50/50
94.33
24344105CKG2
50/50
12.069
270143AC1-141 CT2_
50/50
3.558
24639705ELKHART HY
50/50
0.241
970521AG2-332 GEN
50/50
17.184
24307105BERRINSP G
50/50
0.032
962761AG1-125 GEN
Solar/Wind Harmer
120.047
970149AG2-104 GEN
Solar/Wind Harmer
129.655
970155AG2-107 GEN
Solar/Wind Harmer
76.659
270349AD2-093_GEN
Solar/Wind Harmer
0.009
965011AG1-365 GEN
Solar/Wind Harmer
10.537
970245AG2-165 GEN
Solar/Wind Harmer
4.559
270063AE2-323 C
Solar/Wind Harmer
0.008
270505AE1-170 C O1
Solar/Wind Harmer
10.806
945111AF1-176 GEN
Solar/Wind Harmer
18.321
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
5.329
274773LINCOLN ;4U
Adder
11.972
274774LINCOLN ;5U
Adder
11.972
274723RIVER EC ;12
Adder
25.205
274751CRETE EC ;1U
Adder
11.58
274754CRETE EC ;4U
Adder
11.58
270223U2-072_GEN1
Solar/Wind Harmer
0.001
276164X3-005 C
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
20.506
274812UNIV PK N;8U
Adder
6.996
274801UNIV PARK;4U
Adder
8.089
276776AD2-060 GEN
Solar/Wind Harmer
1.011
247521TR3_G114
Solar/Wind Harmer
0.351
270246TR4_N_V150
Solar/Wind Harmer
0.062
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
42.222
274674JOLIET 9 ;6U
Adder
21.154
274732ELWOOD EC;7P
Adder
22.567
270055AF2-134 C O1
Solar/Wind Harmer
0.007
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
7.614
944231AF1-091 GEN
Solar/Wind Harmer
2.532
24695305TIMB G C
Solar/Wind Harmer
0.002
965421AG1-410 GEN
Solar/Wind Harmer
28.36
958381AF2-132 GEN
Solar/Wind Harmer
0.001
276691AA1-018 GEN1
Solar/Wind Harmer
1.138
965651AG1-433 GEN
Solar/Wind Harmer
2.755
274682WAUKEGAN ;7U
Adder
24.169
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
12.195
274828WAUKEGAN ;BP
Adder
14.836
246936BC-WTG1
Solar/Wind Harmer
0.379
270489AE1-102 GEN1
Solar/Wind Harmer
1.214
270462AD2-086
Solar/Wind Harmer
0.02
962781AG1-127 GEN
Solar/Wind Harmer
8.858
939401AE1-172 GEN
Solar/Wind Harmer
6.954
274872LEEDK;1U
Solar/Wind Harmer
0.006
276901AD2-066 C O1
Solar/Wind Harmer
0.009
971997AH1-543 GEN
Solar/Wind Harmer
4.843
958861AF2-177 GEN
Solar/Wind Harmer
3.987
276861AD2-134 GEN
Solar/Wind Harmer
0.165
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
11.452
957471AF2-041 GEN
Solar/Wind Harmer
27.428
959081AF2-199 GEN
Solar/Wind Harmer
9.143
971067AG2-660 GEN
Solar/Wind Harmer
3.048
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
274822ROCKFORD ;11
Adder
25.633
972235AH1-702 GEN1
Adder
3.284
970819AG2-516 GEN
Solar/Wind Harmer
10.874
971475AH1-234 GEN
Solar/Wind Harmer
4.385
970569AG2-363 GEN
Solar/Wind Harmer
27.095
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
11.947
274766LEE CO EC;7U
Adder
11.806
276158O29GEN2
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.295
24791305MDL-5G
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0.003
939741AE1-205 GEN
Solar/Wind Harmer
12.194
274854TWINGROVE;U2
Solar/Wind Harmer
0.004
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
972175AH1-670 GEN
Solar/Wind Harmer
6.873
970291AG2-192 GEN
Solar/Wind Harmer
1.08
270032AE2-172
Solar/Wind Harmer
5.46
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
3.14
963741AG1-226 GEN
Solar/Wind Harmer
19.026
270005AE1-210 C O1
Solar/Wind Harmer
1.733
965031AG1-367 GEN
Solar/Wind Harmer
8
276615X2-022 GEN
Solar/Wind Harmer
0.084
276903AD2-071 C
Solar/Wind Harmer
8.872
970825AG2-519 GEN
Solar/Wind Harmer
2.793
965911AG1-460 GEN
Solar/Wind Harmer
1.538
24728605AND G2
Adder
3.739
24721605FLATG1
50/50
5.145
971599AH1-298 GEN
50/50
14.587
270144AC1-141 ST1_
50/50
3.152
24653605MOTTVILLE
50/50
0.006
24643105BUCHANAN
50/50
0.019
962771AG1-126 GEN
Solar/Wind Harmer
120.047
270284AF1-227 GEN1
Solar/Wind Harmer
0.014
270286AF1-227 GEN2
Solar/Wind Harmer
0.006
270287AF1-227 GEN3
Solar/Wind Harmer
0.006
971347AH1-153 GEN
Solar/Wind Harmer
16.236
270071AF1-092 GEN
Solar/Wind Harmer
20.132
971771AH1-392 GEN
Solar/Wind Harmer
10.346
971619AH1-309 GEN
Solar/Wind Harmer
4.631
971769AH1-391 GEN
Solar/Wind Harmer
11.424
960681AF2-359 GEN
Solar/Wind Harmer
-0.002
24729505KEY G4
Adder
9.267
274775LINCOLN ;6U
Adder
11.972
274776LINCOLN ;7U
Adder
11.972
274777LINCOLN ;8U
Adder
11.972
965041AG1-368 GEN
Solar/Wind Harmer
9.847
270578AF1-285 GEN2
Solar/Wind Harmer
0.651
274814UNIV PK N;0U
Adder
7.057
274807UNIV PK N;3U
Adder
7.042
274805UNIV PK N;1U
Adder
7.011
274811UNIV PK N;7U
Adder
6.996
972037AH1-567 GEN1
Adder
0.254
274827FISK ;RP
Adder
10.776
960591AF2-350 GEN
Solar/Wind Harmer
9.68
972227AH1-698 GEN1
Adder
3.616
965051AG1-369 GEN
Solar/Wind Harmer
4.807
274687WILL CNTY;4U
Adder
38.503
274687WILL CNTY;4U
Adder
38.503
274675JOLIET 29;7U
Adder
42.223
274675JOLIET 29;7U
Adder
40.715
274728ELWOOD EC;5P
Adder
22.567
274731ELWOOD EC;2P
Adder
22.566
274733ELWOOD EC;3P
Adder
22.566
274735ELWOOD EC;4P
Adder
22.566
270536AF1-215 GEN2
Solar/Wind Harmer
0.012
970833AG2-524 GEN
Solar/Wind Harmer
10.52
970833AG2-524 GEN
Solar/Wind Harmer
7.013
971549AH1-272 GEN
Solar/Wind Harmer
19.681
274746AC1-111 G10
Adder
7.614
274744AC1-111 GEN8
Adder
7.614
963791AG1-232 GEN
Solar/Wind Harmer
12.76
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.183
270302AB2-170 GEN
Solar/Wind Harmer
0.006
270317AD1-130_GEN
Solar/Wind Harmer
0.013
971653AH1-327 GEN
Solar/Wind Harmer
1.314
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.855
276882AE2-255 GEN
Solar/Wind Harmer
1.081
971177AH1-047 GEN
Solar/Wind Harmer
5.697
965101AG1-375 GEN
Solar/Wind Harmer
9.202
971411AH1-196 GEN
Solar/Wind Harmer
13.802
971675AH1-338 GEN
Solar/Wind Harmer
3.588
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
971611AH1-305 GEN
Solar/Wind Harmer
5.454
971171AH1-044 GEN
Solar/Wind Harmer
18.285
274823ROCKFORD ;21
Adder
25.447
276612AE2-035 GEN
Solar/Wind Harmer
0.002
926823AC1-168 GEN
Solar/Wind Harmer
1.535
970169AG2-114 GEN
Solar/Wind Harmer
9.023
971681AH1-341 GEN
Solar/Wind Harmer
14.483
247607V1-011 GEN
Solar/Wind Harmer
0.001
961011AF2-392 GEN
Solar/Wind Harmer
5.219
945581AF1-223 GEN
Solar/Wind Harmer
0.001
957751AF2-069 GEN
Solar/Wind Harmer
0.292
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
9.145
941731AE2-173 GEN
Solar/Wind Harmer
7.258
946321AF1-296 GEN
Solar/Wind Harmer
4.827
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
270024AE2-089 GEN
Solar/Wind Harmer
0.009
971609AH1-304 GEN
Solar/Wind Harmer
1.375
970289AG2-191 GEN
Solar/Wind Harmer
1.578
963841AG1-237 GEN
Solar/Wind Harmer
3.575
270594AE1-207 GEN
Solar/Wind Harmer
9.172
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.295
276848AB2-070 GEN3
Solar/Wind Harmer
0.294
970115AG2-085 GEN
Solar/Wind Harmer
3.159
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
270297AD1-101 GEN
Solar/Wind Harmer
0.002
24722005FLATG5
50/50
5.145
24721905FLATG4
50/50
94.33
270475AD2-096_GEN
50/50
10.026
270142AC1-141 CT1_
50/50
3.558
24641605TWIN BRNCH
50/50
0.026
24344005CKG1
50/50
9.691
24642205MAYFLWER
50/50
0.992
944961AF1-161 GEN
50/50
4.253
962601AG1-109 GEN
50/50
4.253
247604X1-042
50/50
0.632
970153AG2-106 GEN
Solar/Wind Harmer
76.659
270043AE2-236 GEN
Solar/Wind Harmer
6.969
970349AG2-230 GEN
Solar/Wind Harmer
16.236
959331AF2-224 GEN
Solar/Wind Harmer
7.376
965021AG1-366 GEN
Solar/Wind Harmer
3.512
970513AG2-328 GEN
Solar/Wind Harmer
4.559
970517AG2-330 GEN
Solar/Wind Harmer
27.357
247643Z2-116 C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
6.732
945111AF1-176 GEN
Solar/Wind Harmer
8.323
944531AF1-118 GEN
Solar/Wind Harmer
45.595
24441205WTRV SLR C
Solar/Wind Harmer
0
274772LINCOLN ;3U
Adder
11.972
274724RIVER EC ;11
Adder
24.913
274752CRETE EC ;2U
Adder
11.58
274753CRETE EC ;3U
Adder
11.58
270391AF1-285 GEN3
Solar/Wind Harmer
0.651
970707AG2-453 GEN
Solar/Wind Harmer
31.724
274802UNIV PARK;5U
Adder
8.1
274826FISK ;BP
Adder
15.205
274800UNIV PARK;3U
Adder
8.089
972038AH1-567 GEN2
Adder
0.506
276806AD2-047 C O1
Solar/Wind Harmer
5.485
970941AG2-585 GEN
Solar/Wind Harmer
12.1
972228AH1-698 GEN2
Adder
5.135
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.062
276897AD1-100 C
Solar/Wind Harmer
0.013
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
40.714
274730ELWOOD EC;6P
Adder
22.567
274734ELWOOD EC;8P
Adder
22.567
274736ELWOOD EC;9P
Adder
22.567
274729ELWOOD EC;1P
Adder
22.566
276893AG1-478 C
Solar/Wind Harmer
0.379
270535AF1-215 GEN1
Solar/Wind Harmer
0.012
943121AE2-341 GEN
Solar/Wind Harmer
15.96
943591AF1-030 GEN
Solar/Wind Harmer
10.614
964401AG1-302 GEN
Solar/Wind Harmer
0.001
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
24.169
270491AE1-102 GEN2
Solar/Wind Harmer
1.214
270485AE1-090_GEN
Solar/Wind Harmer
0.001
276805AD2-038 GEN
Solar/Wind Harmer
0.003
274872LEEDK;1U
Solar/Wind Harmer
0.341
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.982
274855GSG-6 ;RU
Solar/Wind Harmer
0.337
274850MENDOTA H;RU
Solar/Wind Harmer
0.108
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.165
959091AF2-200 GEN
Solar/Wind Harmer
18.285
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
2.856
970571AG2-364 GEN
Solar/Wind Harmer
18.064
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
11.947
274767LEE CO EC;8U
Adder
11.806
276157O29GEN1
Solar/Wind Harmer
1.431
270258AD1-119 GEN
Solar/Wind Harmer
0.002
274878BISHOP HL;2U
Solar/Wind Harmer
0.295
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
8.785
270404AC1-167 GEN
Solar/Wind Harmer
0.004
942111AE2-223 GEN
Solar/Wind Harmer
2.831
965931AG1-462 GEN
Solar/Wind Harmer
21.861
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
25.685
959611AF2-252 GEN
Solar/Wind Harmer
2.854
971617AH1-308 GEN
Solar/Wind Harmer
7.03
247642Z2-115 C
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
0.914
970291AG2-192 GEN
Solar/Wind Harmer
0.831
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
3.74
276668AB2-070 GEN1
Solar/Wind Harmer
0.295
958821AF2-173 GEN
Solar/Wind Harmer
11.2
270004AE1-209 GEN
Solar/Wind Harmer
1.733
276621W2-048 GEN
Solar/Wind Harmer
0.401
276838X2-022 GEN2
Solar/Wind Harmer
0.448
946031AF1-268 GEN
Solar/Wind Harmer
7.422
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
11.672
942481AE2-261 GEN
Solar/Wind Harmer
22.986
24728705AND G3
Adder
7.82
24728505AND G1
Adder
3.739
970615AG2-402 GEN
50/50
3.512
247620Y3-023
50/50
0.722
270102X2-052 ST
50/50
2.354
270100X2-052 CT1
50/50
2.169
270101X2-052 CT2
50/50
2.169
270471AD2-092_GEN
Solar/Wind Harmer
0.009
970611AG2-400 GEN
Solar/Wind Harmer
10.537
970627AG2-408 GEN
Solar/Wind Harmer
3.161
970321AG2-212 GEN
Solar/Wind Harmer
4.559
270216AD2-079_GEN
Solar/Wind Harmer
0.002
957891AF2-083 GEN
Solar/Wind Harmer
0.001
270526AF1-158 GEN
Solar/Wind Harmer
0.013
24441505OLIV SLR
Solar/Wind Harmer
0
961051AF2-396 GEN
Solar/Wind Harmer
20.46
961051AF2-396 GEN
Solar/Wind Harmer
13.64
965681AG1-436 GEN
Solar/Wind Harmer
12.752
965791AG1-447 GEN
Solar/Wind Harmer
9.351
274770LINCOLN ;1U
Adder
11.972
274771LINCOLN ;2U
Adder
11.972
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
274808UNIV PK N;4U
Adder
6.965
274803UNIV PARK;6U
Adder
8.1
274888KELLY CRK;1U
Solar/Wind Harmer
0.568
274887GEN-1.85
Solar/Wind Harmer
0.255
276843GEN-1.7
Solar/Wind Harmer
0.313
958011AF2-095 GEN
Solar/Wind Harmer
13.939
972259AH1-714 GEN
Adder
26.463
274674JOLIET 9 ;6U
Adder
21.154
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
971573AH1-285 GEN
Solar/Wind Harmer
1.764
958481AF2-142 GEN
Solar/Wind Harmer
14.096
274695ROCKY RD ;2P
Adder
14.996
274693ROCKY RD ;1P
Adder
14.848
274697ROCKY RD ;3P
Adder
4.074
274696ROCKY RD ;4P
Adder
15.349
274861TOP CROP ;1U
Solar/Wind Harmer
0.003
274862TOP CROP ;2U
Solar/Wind Harmer
1.271
944541AF1-119 GEN
Solar/Wind Harmer
0.629
960971AF2-388 GEN
Solar/Wind Harmer
5.509
274683WAUKEGAN ;8U
Adder
28.303
274683WAUKEGAN ;8U
Adder
23.858
246938BC-WTG3
Solar/Wind Harmer
0.338
246937BC-WTG2
Solar/Wind Harmer
0.379
962691AG1-118 GEN
Solar/Wind Harmer
27.992
970921AG2-575 GEN
Solar/Wind Harmer
9.308
970921AG2-575 GEN
Solar/Wind Harmer
3.103
958491AF2-143 GEN
Solar/Wind Harmer
13.931
274879MINONK ;1U
Solar/Wind Harmer
0.39
942991AE2-321 GEN
Solar/Wind Harmer
10.32
971333AH1-146 GEN
Solar/Wind Harmer
18.389
971335AH1-147 GEN
Solar/Wind Harmer
18.389
971341AH1-150 GEN
Solar/Wind Harmer
18.285
971343AH1-151 GEN
Solar/Wind Harmer
18.285
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
942221AE2-234 GEN
Solar/Wind Harmer
0.046
274856ECOGROVE ;U1
Solar/Wind Harmer
0.213
276611AD2-172 GEN
Solar/Wind Harmer
0.002
938861AE1-114 GEN
Solar/Wind Harmer
5.096
274764LEE CO EC;5U
Adder
11.975
274765LEE CO EC;6U
Adder
11.975
274762LEE CO EC;3U
Adder
11.947
274763LEE CO EC;4U
Adder
11.834
276603SUBLETTE C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
270007AE1-245 C
Solar/Wind Harmer
0.002
972267AH1-718 GEN
Adder
5.295
276741O09 GEN1
Solar/Wind Harmer
0.315
276708O09 GEN2
Solar/Wind Harmer
0.315
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.347
276646AC1-214 GEN2
Solar/Wind Harmer
0.347
970623AG2-406 GEN
Solar/Wind Harmer
1.614
276782AC1-033 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
2.854
966841AG1-555 GEN
Solar/Wind Harmer
0.959
270599AE1-208 GEN
Solar/Wind Harmer
7.715
270031AE2-169
Solar/Wind Harmer
4.629
971613AH1-306 GEN
Solar/Wind Harmer
3.931
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
970241AG2-163 GEN
Solar/Wind Harmer
4.69
960441AF2-335 GEN
Solar/Wind Harmer
7.897
970825AG2-519 GEN
Solar/Wind Harmer
8.719
964611AG1-324 GEN
Solar/Wind Harmer
0.584
270201AC2-176 GEN
Solar/Wind Harmer
0.001
970621AG2-405 GEN
Solar/Wind Harmer
1.413
247621Y3-024
Adder
0.262
276916AD2-100_GEN
Solar/Wind Harmer
13.41
276911AD2-131_GEN
Solar/Wind Harmer
0.883
944201AF1-088_MTX
Adder
85.667
NYPJM->LTFIMP_NY
CLTF
2.99
LGEELTFEXP_LGEE->PJM
CLTF
4.155
WECLTFEXP_WEC->PJM
CLTF
4.968
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.286
AG2-052LTFEXP_AG2-052->PJM
LTF
0.312
AH1-155LTFEXP_AH1-155->PJM
LTF
0.469
CBM West 2LTFEXP_CBM-W2->PJM
CBM
96.989
LAGNLTFEXP_LAGN->PJM
CLTF
11.144
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.328
TVALTFEXP_TVA->PJM
CLTF
4.56
CBM West 1LTFEXP_CBM-W1->PJM
CBM
161.402
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.132
MECLTFEXP_MEC->PJM
CLTF
18.394
SIGELTFEXP_SIGE->PJM
CLTF
0.399

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.86 %
Rating:4047.0 MVA
Rating Type:A
MVA to Mitigate:4648.25
MW Contribution:47.64
Bus #Bus NameTypeMW Contribution
24344105CKG2
50/50
8.939
270143AC1-141 CT2_
50/50
2.603
24639705ELKHART HY
50/50
0.176
970521AG2-332 GEN
50/50
12.519
274773LINCOLN ;4U
50/50
9.593
274774LINCOLN ;5U
50/50
9.593
962761AG1-125 GEN
Solar/Wind Harmer
74.603
970149AG2-104 GEN
Solar/Wind Harmer
80.573
970155AG2-107 GEN
Solar/Wind Harmer
47.639
970245AG2-165 GEN
Solar/Wind Harmer
3.44
270505AE1-170 C O1
Solar/Wind Harmer
7.896
270063AE2-323 C
Solar/Wind Harmer
0.006
945111AF1-176 GEN
Solar/Wind Harmer
13.37
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
3.886
274723RIVER EC ;12
Adder
18.99
274751CRETE EC ;1U
Adder
8.717
274754CRETE EC ;4U
Adder
8.717
276164X3-005 C
Solar/Wind Harmer
0
965011AG1-365 GEN
Solar/Wind Harmer
7.366
274812UNIV PK N;8U
Adder
5.278
970373AG2-245 GEN
Solar/Wind Harmer
15.386
276776AD2-060 GEN
Solar/Wind Harmer
0.765
274801UNIV PARK;4U
Adder
6.118
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
32.008
274674JOLIET 9 ;6U
Adder
16.042
274732ELWOOD EC;7P
Adder
17.114
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
5.788
270055AF2-134 C O1
Solar/Wind Harmer
0.006
276691AA1-018 GEN1
Solar/Wind Harmer
0.866
274682WAUKEGAN ;7U
Adder
18.416
274828WAUKEGAN ;BP
Adder
11.308
958381AF2-132 GEN
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
6.763
971599AH1-298 GEN
50/50
10.558
270144AC1-141 ST1_
50/50
2.306
24643105BUCHANAN
50/50
0.014
24653605MOTTVILLE
50/50
0.004
274775LINCOLN ;6U
50/50
9.593
274776LINCOLN ;7U
50/50
9.593
274777LINCOLN ;8U
50/50
9.593
962771AG1-126 GEN
Solar/Wind Harmer
74.603
971347AH1-153 GEN
Solar/Wind Harmer
12.013
270071AF1-092 GEN
Solar/Wind Harmer
14.717
971771AH1-392 GEN
Solar/Wind Harmer
7.604
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971769AH1-391 GEN
Solar/Wind Harmer
8.444
971619AH1-309 GEN
Solar/Wind Harmer
3.384
274814UNIV PK N;0U
Adder
5.324
274807UNIV PK N;3U
Adder
5.313
274805UNIV PK N;1U
Adder
5.29
274811UNIV PK N;7U
Adder
5.278
274827FISK ;RP
Adder
8.149
972037AH1-567 GEN1
Adder
0.192
960591AF2-350 GEN
Solar/Wind Harmer
7.323
972227AH1-698 GEN1
Adder
2.737
274687WILL CNTY;4U
Adder
29.176
274687WILL CNTY;4U
Adder
29.176
274675JOLIET 29;7U
Adder
32.008
274675JOLIET 29;7U
Adder
30.865
24729505KEY G4
Adder
6.759
274731ELWOOD EC;2P
Adder
17.114
274733ELWOOD EC;3P
Adder
17.114
274735ELWOOD EC;4P
Adder
17.114
274728ELWOOD EC;5P
Adder
17.114
970833AG2-524 GEN
Solar/Wind Harmer
7.985
970833AG2-524 GEN
Solar/Wind Harmer
5.323
274746AC1-111 G10
Adder
5.788
274744AC1-111 GEN8
Adder
5.788
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
971177AH1-047 GEN
Solar/Wind Harmer
4.355
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.417
276882AE2-255 GEN
Solar/Wind Harmer
0.825
971675AH1-338 GEN
Solar/Wind Harmer
2.746
971411AH1-196 GEN
Solar/Wind Harmer
10.56
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
971171AH1-044 GEN
Solar/Wind Harmer
14.009
274823ROCKFORD ;21
Adder
19.51
971611AH1-305 GEN
Solar/Wind Harmer
4.152
276612AE2-035 GEN
Solar/Wind Harmer
0.002
926823AC1-168 GEN
Solar/Wind Harmer
1.178
970169AG2-114 GEN
Solar/Wind Harmer
6.92
971681AH1-341 GEN
Solar/Wind Harmer
11.133
961011AF2-392 GEN
Solar/Wind Harmer
4.021
957751AF2-069 GEN
Solar/Wind Harmer
0.225
971549AH1-272 GEN
Solar/Wind Harmer
14.034
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
965101AG1-375 GEN
Solar/Wind Harmer
6.746
965041AG1-368 GEN
Solar/Wind Harmer
6.733
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.06
941731AE2-173 GEN
Solar/Wind Harmer
5.603
946321AF1-296 GEN
Solar/Wind Harmer
3.744
963791AG1-232 GEN
Solar/Wind Harmer
8.989
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
945581AF1-223 GEN
Solar/Wind Harmer
0
965051AG1-369 GEN
Solar/Wind Harmer
3.241
963841AG1-237 GEN
Solar/Wind Harmer
2.776
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.231
276848AB2-070 GEN3
Solar/Wind Harmer
0.23
970289AG2-191 GEN
Solar/Wind Harmer
1.184
971609AH1-304 GEN
Solar/Wind Harmer
1.011
270594AE1-207 GEN
Solar/Wind Harmer
6.856
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.765
270284AF1-227 GEN1
Solar/Wind Harmer
0.008
270286AF1-227 GEN2
Solar/Wind Harmer
0.003
270287AF1-227 GEN3
Solar/Wind Harmer
0.003
270054AF2-122 C O1
Solar/Wind Helper
1.65
270142AC1-141 CT1_
50/50
2.603
24641605TWIN BRNCH
50/50
0.019
24344005CKG1
50/50
7.096
24642205MAYFLWER
50/50
0.728
274772LINCOLN ;3U
50/50
9.593
970153AG2-106 GEN
Solar/Wind Harmer
47.639
970349AG2-230 GEN
Solar/Wind Harmer
12.013
970513AG2-328 GEN
Solar/Wind Harmer
3.44
970517AG2-330 GEN
Solar/Wind Harmer
20.64
270043AE2-236 GEN
Solar/Wind Harmer
5.033
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
6.073
970031AG2-029 GEN
Solar/Wind Harmer
4.844
944531AF1-118 GEN
Solar/Wind Harmer
33.218
274724RIVER EC ;11
Adder
18.771
274752CRETE EC ;2U
Adder
8.717
274753CRETE EC ;3U
Adder
8.717
959331AF2-224 GEN
Solar/Wind Harmer
5.157
965021AG1-366 GEN
Solar/Wind Harmer
2.455
970707AG2-453 GEN
Solar/Wind Harmer
24.03
274826FISK ;BP
Adder
11.498
274802UNIV PARK;5U
Adder
6.123
276806AD2-047 C O1
Solar/Wind Harmer
4.15
970941AG2-585 GEN
Solar/Wind Harmer
9.154
274800UNIV PARK;3U
Adder
6.118
972038AH1-567 GEN2
Adder
0.383
972228AH1-698 GEN2
Adder
3.887
24441205WTRV SLR C
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
0.01
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
30.865
274729ELWOOD EC;1P
Adder
17.114
274730ELWOOD EC;6P
Adder
17.114
274734ELWOOD EC;8P
Adder
17.114
274736ELWOOD EC;9P
Adder
17.114
276893AG1-478 C
Solar/Wind Harmer
0.288
943121AE2-341 GEN
Solar/Wind Harmer
12.132
943591AF1-030 GEN
Solar/Wind Harmer
8.068
247604X1-042
Adder
0.432
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
18.416
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.26
276805AD2-038 GEN
Solar/Wind Harmer
0.002
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.751
274855GSG-6 ;RU
Solar/Wind Harmer
0.258
274850MENDOTA H;RU
Solar/Wind Harmer
0.083
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.126
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
959091AF2-200 GEN
Solar/Wind Harmer
14.009
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
2.191
970571AG2-364 GEN
Solar/Wind Harmer
13.859
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
9.191
274767LEE CO EC;8U
Adder
9.083
276157O29GEN1
Solar/Wind Harmer
1.104
274878BISHOP HL;2U
Solar/Wind Harmer
0.228
24721905FLATG4
Adder
19.64
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.747
942111AE2-223 GEN
Solar/Wind Harmer
2.185
965931AG1-462 GEN
Solar/Wind Harmer
16.976
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
19.897
959611AF2-252 GEN
Solar/Wind Harmer
2.211
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.042
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
2.93
276668AB2-070 GEN1
Solar/Wind Harmer
0.231
247642Z2-115 C
Solar/Wind Harmer
0.003
276621W2-048 GEN
Solar/Wind Harmer
0.316
276838X2-022 GEN2
Solar/Wind Harmer
0.352
970289AG2-191 GEN
Solar/Wind Harmer
0.686
970291AG2-192 GEN
Solar/Wind Harmer
0.623
942481AE2-261 GEN
Solar/Wind Harmer
18.215
270491AE1-102 GEN2
Solar/Wind Harmer
0.785
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.233
274872LEEDK;1U
Solar/Wind Harmer
0.004
939401AE1-172 GEN
Solar/Wind Harmer
5.304
276901AD2-066 C O1
Solar/Wind Harmer
0.007
971997AH1-543 GEN
Solar/Wind Harmer
3.701
276861AD2-134 GEN
Solar/Wind Harmer
0.126
957471AF2-041 GEN
Solar/Wind Harmer
21.014
959081AF2-199 GEN
Solar/Wind Harmer
7.005
971067AG2-660 GEN
Solar/Wind Harmer
2.335
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
274822ROCKFORD ;11
Adder
19.652
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.717
972235AH1-702 GEN1
Adder
2.519
970819AG2-516 GEN
Solar/Wind Harmer
8.346
971475AH1-234 GEN
Solar/Wind Harmer
3.368
970569AG2-363 GEN
Solar/Wind Harmer
20.788
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
9.191
274766LEE CO EC;7U
Adder
9.083
965651AG1-433 GEN
Solar/Wind Harmer
2.017
276158O29GEN2
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.228
24721705FLATG2
Adder
19.64
24791305MDL-5G
Solar/Wind Harmer
0.001
958861AF2-177 GEN
Solar/Wind Harmer
2.923
276726Z2-087_GEN
Solar/Wind Harmer
0.002
939741AE1-205 GEN
Solar/Wind Harmer
9.413
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.002
944231AF1-091 GEN
Solar/Wind Harmer
1.739
945371AF1-202 GEN
Solar/Wind Harmer
0.001
247521TR3_G114
Solar/Wind Harmer
0.237
270246TR4_N_V150
Solar/Wind Harmer
0.042
972175AH1-670 GEN
Solar/Wind Harmer
5.355
270349AD2-093_GEN
Solar/Wind Harmer
0.005
24695305TIMB G C
Solar/Wind Harmer
0.002
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
2.462
963741AG1-226 GEN
Solar/Wind Harmer
14.839
276615X2-022 GEN
Solar/Wind Harmer
0.066
970291AG2-192 GEN
Solar/Wind Harmer
0.81
965421AG1-410 GEN
Solar/Wind Harmer
18.496
270032AE2-172
Solar/Wind Harmer
4.081
965911AG1-460 GEN
Solar/Wind Harmer
1.218
246936BC-WTG1
Solar/Wind Harmer
0.245
270489AE1-102 GEN1
Solar/Wind Harmer
0.785
270102X2-052 ST
50/50
1.747
270100X2-052 CT1
50/50
1.61
270101X2-052 CT2
50/50
1.61
247620Y3-023
50/50
0.525
274770LINCOLN ;1U
50/50
9.593
274771LINCOLN ;2U
50/50
9.593
970321AG2-212 GEN
Solar/Wind Harmer
3.44
270216AD2-079_GEN
Solar/Wind Harmer
0.001
965681AG1-436 GEN
Solar/Wind Harmer
9.481
965791AG1-447 GEN
Solar/Wind Harmer
6.953
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
14.924
961051AF2-396 GEN
Solar/Wind Harmer
9.95
970611AG2-400 GEN
Solar/Wind Harmer
7.366
970627AG2-408 GEN
Solar/Wind Harmer
2.21
274808UNIV PK N;4U
Adder
5.255
972259AH1-714 GEN
Adder
20.044
274803UNIV PARK;6U
Adder
6.123
274888KELLY CRK;1U
Solar/Wind Harmer
0.43
274887GEN-1.85
Solar/Wind Harmer
0.193
276843GEN-1.7
Solar/Wind Harmer
0.237
958011AF2-095 GEN
Solar/Wind Harmer
10.545
274674JOLIET 9 ;6U
Adder
16.042
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
971573AH1-285 GEN
Solar/Wind Harmer
1.342
274695ROCKY RD ;2P
Adder
11.425
274693ROCKY RD ;1P
Adder
11.312
274697ROCKY RD ;3P
Adder
3.104
274696ROCKY RD ;4P
Adder
11.694
958481AF2-142 GEN
Solar/Wind Harmer
10.727
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.967
274683WAUKEGAN ;8U
Adder
21.572
274683WAUKEGAN ;8U
Adder
18.184
962691AG1-118 GEN
Solar/Wind Harmer
21.36
970921AG2-575 GEN
Solar/Wind Harmer
7.106
970921AG2-575 GEN
Solar/Wind Harmer
2.369
958491AF2-143 GEN
Solar/Wind Harmer
10.627
942991AE2-321 GEN
Solar/Wind Harmer
7.889
274879MINONK ;1U
Solar/Wind Harmer
0.298
971333AH1-146 GEN
Solar/Wind Harmer
14.073
971335AH1-147 GEN
Solar/Wind Harmer
14.073
971341AH1-150 GEN
Solar/Wind Harmer
14.009
971343AH1-151 GEN
Solar/Wind Harmer
14.009
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
274856ECOGROVE ;U1
Solar/Wind Harmer
0.164
276611AD2-172 GEN
Solar/Wind Harmer
0.002
938861AE1-114 GEN
Solar/Wind Harmer
3.917
274764LEE CO EC;5U
Adder
9.213
274765LEE CO EC;6U
Adder
9.213
274762LEE CO EC;3U
Adder
9.191
274763LEE CO EC;4U
Adder
9.105
276603SUBLETTE C
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.461
960971AF2-388 GEN
Solar/Wind Harmer
4.033
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
972267AH1-718 GEN
Adder
4.082
276741O09 GEN1
Solar/Wind Harmer
0.243
276708O09 GEN2
Solar/Wind Harmer
0.243
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.268
276646AC1-214 GEN2
Solar/Wind Harmer
0.268
276782AC1-033 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
2.211
942221AE2-234 GEN
Solar/Wind Harmer
0.033
966841AG1-555 GEN
Solar/Wind Harmer
0.741
270471AD2-092_GEN
Solar/Wind Harmer
0.005
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
970241AG2-163 GEN
Solar/Wind Harmer
3.657
270599AE1-208 GEN
Solar/Wind Harmer
5.676
270031AE2-169
Solar/Wind Harmer
3.406
971613AH1-306 GEN
Solar/Wind Harmer
2.938
276916AD2-100_GEN
Solar/Wind Harmer
12.71
276911AD2-131_GEN
Solar/Wind Harmer
0.837
246938BC-WTG3
Solar/Wind Harmer
0.219
246937BC-WTG2
Solar/Wind Harmer
0.245
NYPJM->LTFIMP_NY
CLTF
2.589
LGEELTFEXP_LGEE->PJM
CLTF
3.659
WECLTFEXP_WEC->PJM
CLTF
3.814
AG2-052LTFEXP_AG2-052->PJM
LTF
0.236
AH1-155LTFEXP_AH1-155->PJM
LTF
0.355
CPLELTFEXP_CPLE->PJM
CLTF
1.429
CBM West 2LTFEXP_CBM-W2->PJM
CBM
87.023
LAGNLTFEXP_LAGN->PJM
CLTF
11.239
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.669
TVALTFEXP_TVA->PJM
CLTF
5.062
CBM West 1LTFEXP_CBM-W1->PJM
CBM
120.019
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.189
MECLTFEXP_MEC->PJM
CLTF
14.69
SIGELTFEXP_SIGE->PJM
CLTF
0.339

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AEP_P7-1_#10944___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10944___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:111.67 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5104.52
MW Contribution:38.67
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
2.636
24641605TWIN BRNCH
50/50
0.019
24344005CKG1
50/50
7.184
274772LINCOLN ;3U
50/50
7.2
24642205MAYFLWER
50/50
0.738
970153AG2-106 GEN
Solar/Wind Harmer
38.674
970349AG2-230 GEN
Solar/Wind Harmer
17.476
970513AG2-328 GEN
Solar/Wind Harmer
20.738
970517AG2-330 GEN
Solar/Wind Harmer
18.809
270043AE2-236 GEN
Solar/Wind Harmer
6.251
247643Z2-116 C
Solar/Wind Harmer
0.077
945111AF1-176 GEN
Solar/Wind Harmer
6.147
274724RIVER EC ;11
Adder
19.173
944531AF1-118 GEN
Solar/Wind Harmer
37.878
972231SS25-0005
Solar/Wind Harmer
10.253
972181SS23-001
Solar/Wind Harmer
6.408
274752CRETE EC ;2U
Adder
5.281
274753CRETE EC ;3U
Adder
5.281
970031AG2-029 GEN
Solar/Wind Harmer
32.374
970707AG2-453 GEN
Solar/Wind Harmer
30.198
274826FISK ;BP
Adder
11.757
274802UNIV PARK;5U
Adder
6.261
276772AC2-154 GEN
Solar/Wind Harmer
2.994
276806AD2-047 C O1
Solar/Wind Harmer
11.484
970941AG2-585 GEN
Solar/Wind Harmer
13.419
972228AH1-698 GEN2
Adder
3.976
274800UNIV PARK;3U
Adder
6.257
972038AH1-567 GEN2
Adder
0.392
276897AD1-100 C
Solar/Wind Harmer
31.058
939351AE1-166 GEN
Solar/Wind Harmer
6.346
274676JOLIET 29;8U
Adder
31.584
274729ELWOOD EC;1P
Adder
17.516
274730ELWOOD EC;6P
Adder
17.516
274734ELWOOD EC;8P
Adder
17.516
274736ELWOOD EC;9P
Adder
17.516
276893AG1-478 C
Solar/Wind Harmer
0.445
943121AE2-341 GEN
Solar/Wind Harmer
15.932
943591AF1-030 GEN
Solar/Wind Harmer
10.621
959331AF2-224 GEN
Solar/Wind Harmer
10.607
965021AG1-366 GEN
Solar/Wind Harmer
2.467
24441205WTRV SLR C
Solar/Wind Harmer
0.143
270535AF1-215 GEN1
Solar/Wind Harmer
4.803
24721905FLATG4
Adder
21.327
276694AA1-018 GEN2
Solar/Wind Harmer
6.628
274682WAUKEGAN ;7U
Adder
18.874
247604X1-042
Adder
0.436
964401AG1-302 GEN
Solar/Wind Harmer
9.472
274872LEEDK;1U
Solar/Wind Harmer
0.267
276805AD2-038 GEN
Solar/Wind Harmer
5.342
276799AD1-013 GEN
Solar/Wind Harmer
2.29
946671AF1-331 GEN
Solar/Wind Harmer
0.434
274855GSG-6 ;RU
Solar/Wind Harmer
3.824
274850MENDOTA H;RU
Solar/Wind Harmer
2.659
276602WESTBROOK C
Solar/Wind Harmer
2.201
276863AD2-134 GEN
Solar/Wind Harmer
1.849
959141AF2-205 GEN
Solar/Wind Harmer
6.241
972236AH1-702 GEN2
Adder
2.25
274760LEE CO EC;1U
Adder
9.448
274767LEE CO EC;8U
Adder
9.337
959091AF2-200 GEN
Solar/Wind Harmer
0.659
270102X2-052 ST
50/50
1.777
270100X2-052 CT1
50/50
1.637
270101X2-052 CT2
50/50
1.637
274770LINCOLN ;1U
50/50
7.2
274771LINCOLN ;2U
50/50
7.2
247620Y3-023
50/50
0.531
970321AG2-212 GEN
Solar/Wind Harmer
20.738
965681AG1-436 GEN
Solar/Wind Harmer
13.825
965791AG1-447 GEN
Solar/Wind Harmer
7.073
270216AD2-079_GEN
Solar/Wind Harmer
0.668
270526AF1-158 GEN
Solar/Wind Harmer
5.006
24441505OLIV SLR
Solar/Wind Harmer
0.147
957891AF2-083 GEN
Solar/Wind Harmer
3.677
960981AF2-389 GEN
Solar/Wind Harmer
1.648
961051AF2-396 GEN
Solar/Wind Harmer
17.18
961051AF2-396 GEN
Solar/Wind Harmer
7.99
274808UNIV PK N;4U
Adder
5.37
972259AH1-714 GEN
Adder
20.504
274803UNIV PARK;6U
Adder
6.261
274888KELLY CRK;1U
Solar/Wind Harmer
6.338
274887GEN-1.85
Solar/Wind Harmer
5.722
276843GEN-1.7
Solar/Wind Harmer
0.616
958011AF2-095 GEN
Solar/Wind Harmer
15.458
274674JOLIET 9 ;6U
Adder
16.418
274847GR RIDGE ;BU
Solar/Wind Harmer
5.386
970611AG2-400 GEN
Solar/Wind Harmer
10.607
971573AH1-285 GEN
Solar/Wind Harmer
9.097
274695ROCKY RD ;2P
Adder
11.708
274693ROCKY RD ;1P
Adder
11.593
274697ROCKY RD ;3P
Adder
3.181
274696ROCKY RD ;4P
Adder
11.984
958481AF2-142 GEN
Solar/Wind Harmer
15.755
274861TOP CROP ;1U
Solar/Wind Harmer
6.362
274862TOP CROP ;2U
Solar/Wind Harmer
5.313
274683WAUKEGAN ;8U
Adder
22.11
274683WAUKEGAN ;8U
Adder
18.638
962691AG1-118 GEN
Solar/Wind Harmer
31.39
970921AG2-575 GEN
Solar/Wind Harmer
10.445
970921AG2-575 GEN
Solar/Wind Harmer
2.429
958491AF2-143 GEN
Solar/Wind Harmer
15.621
942991AE2-321 GEN
Solar/Wind Harmer
10.388
274879MINONK ;1U
Solar/Wind Harmer
7.005
971333AH1-146 GEN
Solar/Wind Harmer
20.7
971335AH1-147 GEN
Solar/Wind Harmer
20.7
274764LEE CO EC;5U
Adder
9.47
274765LEE CO EC;6U
Adder
9.47
274762LEE CO EC;3U
Adder
9.448
274763LEE CO EC;4U
Adder
9.359
972267AH1-718 GEN
Adder
4.199
971341AH1-150 GEN
Solar/Wind Harmer
0.659
971343AH1-151 GEN
Solar/Wind Harmer
0.659
971599AH1-298 GEN
50/50
10.665
270144AC1-141 ST1_
50/50
2.335
274775LINCOLN ;6U
50/50
7.2
274776LINCOLN ;7U
50/50
7.2
274777LINCOLN ;8U
50/50
7.2
24643105BUCHANAN
50/50
0.014
24653605MOTTVILLE
50/50
0.004
962771AG1-126 GEN
Solar/Wind Harmer
88.693
971347AH1-153 GEN
Solar/Wind Harmer
17.476
270071AF1-092 GEN
Solar/Wind Harmer
16.765
960681AF2-359 GEN
Solar/Wind Harmer
4.178
971771AH1-392 GEN
Solar/Wind Harmer
9.947
971769AH1-391 GEN
Solar/Wind Harmer
11.009
274814UNIV PK N;0U
Adder
5.441
274807UNIV PK N;3U
Adder
5.429
274805UNIV PK N;1U
Adder
5.405
274811UNIV PK N;7U
Adder
5.394
274827FISK ;RP
Adder
8.332
972037AH1-567 GEN1
Adder
0.197
960591AF2-350 GEN
Solar/Wind Harmer
10.735
972227AH1-698 GEN1
Adder
2.799
944161AF1-084 GEN
Solar/Wind Harmer
2.371
274687WILL CNTY;4U
Adder
29.852
274687WILL CNTY;4U
Adder
29.852
274675JOLIET 29;7U
Adder
32.754
274675JOLIET 29;7U
Adder
31.584
274731ELWOOD EC;2P
Adder
17.516
274733ELWOOD EC;3P
Adder
17.516
274735ELWOOD EC;4P
Adder
17.516
274728ELWOOD EC;5P
Adder
17.516
970833AG2-524 GEN
Solar/Wind Harmer
9.299
970833AG2-524 GEN
Solar/Wind Harmer
4.325
24729505KEY G4
Adder
6.895
274746AC1-111 G10
Adder
5.928
274744AC1-111 GEN8
Adder
5.928
270536AF1-215 GEN2
Solar/Wind Harmer
4.803
971177AH1-047 GEN
Solar/Wind Harmer
6.086
276868AE1-113 GEN
Solar/Wind Harmer
10.506
276882AE2-255 GEN
Solar/Wind Harmer
3.502
958391AF2-133 GEN
Solar/Wind Harmer
9.41
971675AH1-338 GEN
Solar/Wind Harmer
18.64
971411AH1-196 GEN
Solar/Wind Harmer
15.533
274863CRW1-WTG
Solar/Wind Harmer
5.758
274864CRW2-WTG
Solar/Wind Harmer
5.758
274823ROCKFORD ;21
Adder
20.032
270054AF2-122 C O1
Solar/Wind Helper
1.787
971171AH1-044 GEN
Solar/Wind Harmer
0.659
24344105CKG2
50/50
9.068
270143AC1-141 CT2_
50/50
2.636
274773LINCOLN ;4U
50/50
7.2
274774LINCOLN ;5U
50/50
7.2
24639705ELKHART HY
50/50
0.178
970521AG2-332 GEN
50/50
12.672
962761AG1-125 GEN
Solar/Wind Harmer
88.693
970149AG2-104 GEN
Solar/Wind Harmer
109.536
970155AG2-107 GEN
Solar/Wind Harmer
38.674
970245AG2-165 GEN
Solar/Wind Harmer
20.738
972207SS24-0001
Solar/Wind Harmer
24.126
270505AE1-170 C O1
Solar/Wind Harmer
16.366
945111AF1-176 GEN
Solar/Wind Harmer
19.395
270063AE2-323 C
Solar/Wind Harmer
2.395
274723RIVER EC ;12
Adder
19.397
274751CRETE EC ;1U
Adder
5.281
274754CRETE EC ;4U
Adder
5.281
276164X3-005 C
Solar/Wind Harmer
0.759
270449AD2-020 GEN
Solar/Wind Harmer
3.026
943021AE2-325 GEN
Solar/Wind Harmer
3.932
274812UNIV PK N;8U
Adder
5.394
276776AD2-060 GEN
Solar/Wind Harmer
0.454
274801UNIV PARK;4U
Adder
6.257
970373AG2-245 GEN
Solar/Wind Harmer
22.515
941551AE2-152 GEN
Solar/Wind Harmer
4.854
274676JOLIET 29;8U
Adder
32.754
274674JOLIET 9 ;6U
Adder
16.418
274732ELWOOD EC;7P
Adder
17.516
274871GR RIDGE ;2U
Solar/Wind Harmer
8.188
965011AG1-365 GEN
Solar/Wind Harmer
10.607
274745AC1-111 GEN9
Adder
5.928
270055AF2-134 C O1
Solar/Wind Harmer
3.202
24721705FLATG2
Adder
21.327
276691AA1-018 GEN1
Solar/Wind Harmer
0.489
274682WAUKEGAN ;7U
Adder
18.874
274828WAUKEGAN ;BP
Adder
11.59
960751AF2-366 GEN
Solar/Wind Harmer
2.997
962781AG1-127 GEN
Solar/Wind Harmer
9.933
958381AF2-132 GEN
Solar/Wind Harmer
9.472
274872LEEDK;1U
Solar/Wind Harmer
8.565
964861AG1-349 GEN
Solar/Wind Harmer
8.196
971917AH1-482 GEN
Solar/Wind Harmer
9.458
939401AE1-172 GEN
Solar/Wind Harmer
14.53
276901AD2-066 C O1
Solar/Wind Harmer
3.656
971997AH1-543 GEN
Solar/Wind Harmer
16.328
276861AD2-134 GEN
Solar/Wind Harmer
1.849
274822ROCKFORD ;11
Adder
20.179
972235AH1-702 GEN1
Adder
2.587
274761LEE CO EC;2U
Adder
9.448
274766LEE CO EC;7U
Adder
9.337
957471AF2-041 GEN
Solar/Wind Harmer
0.989
959081AF2-199 GEN
Solar/Wind Harmer
0.33
971067AG2-660 GEN
Solar/Wind Harmer
0.077
NYPJM->LTFIMP_NY
CLTF
2.821
LGEELTFEXP_LGEE->PJM
CLTF
4.037
WECLTFEXP_WEC->PJM
CLTF
3.917
AG2-052LTFEXP_AG2-052->PJM
LTF
0.242
AH1-155LTFEXP_AH1-155->PJM
LTF
0.363
CPLELTFEXP_CPLE->PJM
CLTF
1.907
CBM West 2LTFEXP_CBM-W2->PJM
CBM
93.196
LAGNLTFEXP_LAGN->PJM
CLTF
12.245
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.222
TVALTFEXP_TVA->PJM
CLTF
5.61
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.675
CBM South 1LTFEXP_CBM-S1->PJM
CBM
21.249
MECLTFEXP_MEC->PJM
CLTF
15.261
SIGELTFEXP_SIGE->PJM
CLTF
0.364

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-027A_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-027A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:110.09 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5032.32
MW Contribution:38.89
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
2.761
24344005CKG1
50/50
7.535
24641605TWIN BRNCH
50/50
0.02
24642205MAYFLWER
50/50
0.772
944961AF1-161 GEN
50/50
3.302
962601AG1-109 GEN
50/50
3.302
970153AG2-106 GEN
Solar/Wind Harmer
38.894
970349AG2-230 GEN
Solar/Wind Harmer
18.111
970513AG2-328 GEN
Solar/Wind Harmer
21.268
970517AG2-330 GEN
Solar/Wind Harmer
19.29
270043AE2-236 GEN
Solar/Wind Harmer
6.511
247643Z2-116 C
Solar/Wind Harmer
0.08
945111AF1-176 GEN
Solar/Wind Harmer
6.454
970031AG2-029 GEN
Solar/Wind Harmer
33.986
274772LINCOLN ;3U
Adder
6.975
24441205WTRV SLR C
Solar/Wind Harmer
0.151
959331AF2-224 GEN
Solar/Wind Harmer
11.187
965021AG1-366 GEN
Solar/Wind Harmer
2.602
274724RIVER EC ;11
Adder
19.746
944531AF1-118 GEN
Solar/Wind Harmer
39.003
972231SS25-0005
Solar/Wind Harmer
10.567
972181SS23-001
Solar/Wind Harmer
6.604
274752CRETE EC ;2U
Adder
5.442
274753CRETE EC ;3U
Adder
5.442
247604X1-042
Adder
0.463
970707AG2-453 GEN
Solar/Wind Harmer
31.017
274802UNIV PARK;5U
Adder
6.439
274826FISK ;BP
Adder
12.09
276772AC2-154 GEN
Solar/Wind Harmer
3.077
276806AD2-047 C O1
Solar/Wind Harmer
11.806
970941AG2-585 GEN
Solar/Wind Harmer
13.795
274800UNIV PARK;3U
Adder
6.433
972038AH1-567 GEN2
Adder
0.403
972228AH1-698 GEN2
Adder
4.086
276897AD1-100 C
Solar/Wind Harmer
31.901
939351AE1-166 GEN
Solar/Wind Harmer
6.518
274676JOLIET 29;8U
Adder
32.446
274729ELWOOD EC;1P
Adder
17.991
274730ELWOOD EC;6P
Adder
17.991
274734ELWOOD EC;8P
Adder
17.991
274736ELWOOD EC;9P
Adder
17.991
276893AG1-478 C
Solar/Wind Harmer
0.457
270535AF1-215 GEN1
Solar/Wind Harmer
4.953
943121AE2-341 GEN
Solar/Wind Harmer
16.349
943591AF1-030 GEN
Solar/Wind Harmer
10.899
276694AA1-018 GEN2
Solar/Wind Harmer
6.801
274682WAUKEGAN ;7U
Adder
19.358
964401AG1-302 GEN
Solar/Wind Harmer
9.749
274872LEEDK;1U
Solar/Wind Harmer
0.273
276805AD2-038 GEN
Solar/Wind Harmer
5.478
276799AD1-013 GEN
Solar/Wind Harmer
2.346
946671AF1-331 GEN
Solar/Wind Harmer
0.444
959141AF2-205 GEN
Solar/Wind Harmer
6.413
274855GSG-6 ;RU
Solar/Wind Harmer
3.917
274850MENDOTA H;RU
Solar/Wind Harmer
2.724
276602WESTBROOK C
Solar/Wind Harmer
2.255
276863AD2-134 GEN
Solar/Wind Harmer
1.894
972236AH1-702 GEN2
Adder
2.303
274760LEE CO EC;1U
Adder
9.662
274767LEE CO EC;8U
Adder
9.549
24721905FLATG4
Adder
19.907
270102X2-052 ST
50/50
1.844
270100X2-052 CT1
50/50
1.699
270101X2-052 CT2
50/50
1.699
247620Y3-023
50/50
0.557
970321AG2-212 GEN
Solar/Wind Harmer
21.268
270216AD2-079_GEN
Solar/Wind Harmer
0.699
270526AF1-158 GEN
Solar/Wind Harmer
5.214
965681AG1-436 GEN
Solar/Wind Harmer
14.336
965791AG1-447 GEN
Solar/Wind Harmer
7.335
24441505OLIV SLR
Solar/Wind Harmer
0.154
957891AF2-083 GEN
Solar/Wind Harmer
3.858
960981AF2-389 GEN
Solar/Wind Harmer
1.729
961051AF2-396 GEN
Solar/Wind Harmer
18.061
961051AF2-396 GEN
Solar/Wind Harmer
8.401
274770LINCOLN ;1U
Adder
6.975
274771LINCOLN ;2U
Adder
6.975
970611AG2-400 GEN
Solar/Wind Harmer
11.187
274808UNIV PK N;4U
Adder
5.528
274803UNIV PARK;6U
Adder
6.439
972259AH1-714 GEN
Adder
21.064
274888KELLY CRK;1U
Solar/Wind Harmer
6.515
274887GEN-1.85
Solar/Wind Harmer
5.882
276843GEN-1.7
Solar/Wind Harmer
0.633
958011AF2-095 GEN
Solar/Wind Harmer
15.891
274674JOLIET 9 ;6U
Adder
16.864
274847GR RIDGE ;BU
Solar/Wind Harmer
5.529
971573AH1-285 GEN
Solar/Wind Harmer
9.332
274695ROCKY RD ;2P
Adder
12.008
274693ROCKY RD ;1P
Adder
11.89
274697ROCKY RD ;3P
Adder
3.262
274696ROCKY RD ;4P
Adder
12.291
958481AF2-142 GEN
Solar/Wind Harmer
16.166
274861TOP CROP ;1U
Solar/Wind Harmer
6.528
274862TOP CROP ;2U
Solar/Wind Harmer
5.451
274683WAUKEGAN ;8U
Adder
22.675
274683WAUKEGAN ;8U
Adder
19.114
962691AG1-118 GEN
Solar/Wind Harmer
32.178
970921AG2-575 GEN
Solar/Wind Harmer
10.705
970921AG2-575 GEN
Solar/Wind Harmer
2.49
958491AF2-143 GEN
Solar/Wind Harmer
16.016
942991AE2-321 GEN
Solar/Wind Harmer
10.644
274879MINONK ;1U
Solar/Wind Harmer
7.179
971333AH1-146 GEN
Solar/Wind Harmer
21.203
971335AH1-147 GEN
Solar/Wind Harmer
21.203
274764LEE CO EC;5U
Adder
9.685
274765LEE CO EC;6U
Adder
9.685
274762LEE CO EC;3U
Adder
9.662
274763LEE CO EC;4U
Adder
9.571
972267AH1-718 GEN
Adder
4.292
971599AH1-298 GEN
50/50
11.057
270144AC1-141 ST1_
50/50
2.446
24643105BUCHANAN
50/50
0.015
24653605MOTTVILLE
50/50
0.004
962771AG1-126 GEN
Solar/Wind Harmer
89.197
971347AH1-153 GEN
Solar/Wind Harmer
18.111
270071AF1-092 GEN
Solar/Wind Harmer
17.338
971771AH1-392 GEN
Solar/Wind Harmer
10.383
960681AF2-359 GEN
Solar/Wind Harmer
4.333
971769AH1-391 GEN
Solar/Wind Harmer
11.46
944161AF1-084 GEN
Solar/Wind Harmer
2.498
274775LINCOLN ;6U
Adder
6.975
274776LINCOLN ;7U
Adder
6.975
274777LINCOLN ;8U
Adder
6.975
274814UNIV PK N;0U
Adder
5.601
274807UNIV PK N;3U
Adder
5.589
274805UNIV PK N;1U
Adder
5.565
274811UNIV PK N;7U
Adder
5.552
972037AH1-567 GEN1
Adder
0.202
274827FISK ;RP
Adder
8.568
960591AF2-350 GEN
Solar/Wind Harmer
11.036
972227AH1-698 GEN1
Adder
2.877
274687WILL CNTY;4U
Adder
30.673
274687WILL CNTY;4U
Adder
30.673
274675JOLIET 29;7U
Adder
33.649
274675JOLIET 29;7U
Adder
32.447
274731ELWOOD EC;2P
Adder
17.991
274733ELWOOD EC;3P
Adder
17.991
274735ELWOOD EC;4P
Adder
17.991
274728ELWOOD EC;5P
Adder
17.991
970833AG2-524 GEN
Solar/Wind Harmer
9.547
970833AG2-524 GEN
Solar/Wind Harmer
4.44
24729505KEY G4
Adder
7.093
270536AF1-215 GEN2
Solar/Wind Harmer
4.953
274746AC1-111 G10
Adder
6.083
274744AC1-111 GEN8
Adder
6.083
958391AF2-133 GEN
Solar/Wind Harmer
9.677
971177AH1-047 GEN
Solar/Wind Harmer
6.235
276868AE1-113 GEN
Solar/Wind Harmer
10.768
276882AE2-255 GEN
Solar/Wind Harmer
3.589
971411AH1-196 GEN
Solar/Wind Harmer
15.911
971675AH1-338 GEN
Solar/Wind Harmer
19.093
274823ROCKFORD ;21
Adder
20.508
270054AF2-122 C O1
Solar/Wind Helper
1.62
971549AH1-272 GEN
Solar/Wind Harmer
15.966
24344105CKG2
50/50
9.384
270143AC1-141 CT2_
50/50
2.761
24639705ELKHART HY
50/50
0.186
970521AG2-332 GEN
50/50
13.281
24307105BERRINSP G
50/50
0.025
962761AG1-125 GEN
Solar/Wind Harmer
89.197
970149AG2-104 GEN
Solar/Wind Harmer
110.158
970155AG2-107 GEN
Solar/Wind Harmer
38.894
970245AG2-165 GEN
Solar/Wind Harmer
21.268
270505AE1-170 C O1
Solar/Wind Harmer
17.176
945111AF1-176 GEN
Solar/Wind Harmer
20.364
270063AE2-323 C
Solar/Wind Harmer
2.513
270449AD2-020 GEN
Solar/Wind Harmer
3.183
943021AE2-325 GEN
Solar/Wind Harmer
4.136
972207SS24-0001
Solar/Wind Harmer
24.8
274773LINCOLN ;4U
Adder
6.975
274774LINCOLN ;5U
Adder
6.975
965011AG1-365 GEN
Solar/Wind Harmer
11.187
274723RIVER EC ;12
Adder
19.976
274751CRETE EC ;1U
Adder
5.442
274754CRETE EC ;4U
Adder
5.442
276164X3-005 C
Solar/Wind Harmer
0.781
274812UNIV PK N;8U
Adder
5.552
970373AG2-245 GEN
Solar/Wind Harmer
23.259
276776AD2-060 GEN
Solar/Wind Harmer
0.467
274801UNIV PARK;4U
Adder
6.433
941551AE2-152 GEN
Solar/Wind Harmer
4.986
274676JOLIET 29;8U
Adder
33.648
274674JOLIET 9 ;6U
Adder
16.864
274732ELWOOD EC;7P
Adder
17.991
274871GR RIDGE ;2U
Solar/Wind Harmer
8.406
270055AF2-134 C O1
Solar/Wind Harmer
3.301
274745AC1-111 GEN9
Adder
6.083
276691AA1-018 GEN1
Solar/Wind Harmer
0.502
274682WAUKEGAN ;7U
Adder
19.358
274828WAUKEGAN ;BP
Adder
11.886
958381AF2-132 GEN
Solar/Wind Harmer
9.749
964861AG1-349 GEN
Solar/Wind Harmer
8.434
971917AH1-482 GEN
Solar/Wind Harmer
9.733
960751AF2-366 GEN
Solar/Wind Harmer
3.071
962781AG1-127 GEN
Solar/Wind Harmer
10.181
274872LEEDK;1U
Solar/Wind Harmer
8.777
939401AE1-172 GEN
Solar/Wind Harmer
14.891
276901AD2-066 C O1
Solar/Wind Harmer
3.747
971997AH1-543 GEN
Solar/Wind Harmer
16.729
276861AD2-134 GEN
Solar/Wind Harmer
1.894
274822ROCKFORD ;11
Adder
20.658
972235AH1-702 GEN1
Adder
2.648
274761LEE CO EC;2U
Adder
9.662
274766LEE CO EC;7U
Adder
9.549
24721705FLATG2
Adder
19.907
NYPJM->LTFIMP_NY
CLTF
2.826
LGEELTFEXP_LGEE->PJM
CLTF
3.895
WECLTFEXP_WEC->PJM
CLTF
4.009
AG2-052LTFEXP_AG2-052->PJM
LTF
0.249
AH1-155LTFEXP_AH1-155->PJM
LTF
0.373
CPLELTFEXP_CPLE->PJM
CLTF
1.469
CBM West 2LTFEXP_CBM-W2->PJM
CBM
91.671
LAGNLTFEXP_LAGN->PJM
CLTF
11.82
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.928
TVALTFEXP_TVA->PJM
CLTF
5.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
131.22
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.233
MECLTFEXP_MEC->PJM
CLTF
15.452
SIGELTFEXP_SIGE->PJM
CLTF
0.358

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AP_P2-2_WP-500-DRT14_SRT-SL


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-500-DRT14_SRT-SL
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:107.38 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:4908.33
MW Contribution:38.54
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
2.597
24641605TWIN BRNCH
50/50
0.019
24344005CKG1
50/50
7.08
24642205MAYFLWER
50/50
0.726
274772LINCOLN ;3U
50/50
7.031
970153AG2-106 GEN
Solar/Wind Harmer
38.539
970349AG2-230 GEN
Solar/Wind Harmer
17.182
970513AG2-328 GEN
Solar/Wind Harmer
20.275
970517AG2-330 GEN
Solar/Wind Harmer
18.389
270043AE2-236 GEN
Solar/Wind Harmer
6.17
247643Z2-116 C
Solar/Wind Harmer
0.076
945111AF1-176 GEN
Solar/Wind Harmer
6.059
970031AG2-029 GEN
Solar/Wind Harmer
31.974
944531AF1-118 GEN
Solar/Wind Harmer
37.097
274724RIVER EC ;11
Adder
18.728
972231SS25-0005
Solar/Wind Harmer
10.017
972181SS23-001
Solar/Wind Harmer
6.261
274752CRETE EC ;2U
Adder
5.159
274753CRETE EC ;3U
Adder
5.159
959331AF2-224 GEN
Solar/Wind Harmer
10.534
965021AG1-366 GEN
Solar/Wind Harmer
2.45
970707AG2-453 GEN
Solar/Wind Harmer
29.454
274826FISK ;BP
Adder
11.471
274802UNIV PARK;5U
Adder
6.109
276772AC2-154 GEN
Solar/Wind Harmer
2.92
276806AD2-047 C O1
Solar/Wind Harmer
11.203
970941AG2-585 GEN
Solar/Wind Harmer
13.09
274800UNIV PARK;3U
Adder
6.104
972038AH1-567 GEN2
Adder
0.382
972228AH1-698 GEN2
Adder
3.878
24441205WTRV SLR C
Solar/Wind Harmer
0.141
276897AD1-100 C
Solar/Wind Harmer
30.28
939351AE1-166 GEN
Solar/Wind Harmer
6.187
274676JOLIET 29;8U
Adder
30.792
274729ELWOOD EC;1P
Adder
17.074
274730ELWOOD EC;6P
Adder
17.074
274734ELWOOD EC;8P
Adder
17.074
274736ELWOOD EC;9P
Adder
17.074
276893AG1-478 C
Solar/Wind Harmer
0.434
943121AE2-341 GEN
Solar/Wind Harmer
15.521
943591AF1-030 GEN
Solar/Wind Harmer
10.347
247604X1-042
Adder
0.431
270535AF1-215 GEN1
Solar/Wind Harmer
4.686
276694AA1-018 GEN2
Solar/Wind Harmer
6.453
274682WAUKEGAN ;7U
Adder
18.372
964401AG1-302 GEN
Solar/Wind Harmer
9.225
274872LEEDK;1U
Solar/Wind Harmer
0.259
276805AD2-038 GEN
Solar/Wind Harmer
5.197
276799AD1-013 GEN
Solar/Wind Harmer
2.226
946671AF1-331 GEN
Solar/Wind Harmer
0.422
274855GSG-6 ;RU
Solar/Wind Harmer
3.717
274850MENDOTA H;RU
Solar/Wind Harmer
2.585
276602WESTBROOK C
Solar/Wind Harmer
2.14
276863AD2-134 GEN
Solar/Wind Harmer
1.798
959141AF2-205 GEN
Solar/Wind Harmer
6.07
972236AH1-702 GEN2
Adder
2.185
274760LEE CO EC;1U
Adder
9.168
274767LEE CO EC;8U
Adder
9.06
24721905FLATG4
Adder
19.59
959091AF2-200 GEN
Solar/Wind Harmer
0.641
24344105CKG2
50/50
8.921
270143AC1-141 CT2_
50/50
2.597
24639705ELKHART HY
50/50
0.175
970521AG2-332 GEN
50/50
12.491
274773LINCOLN ;4U
50/50
7.031
274774LINCOLN ;5U
50/50
7.031
962761AG1-125 GEN
Solar/Wind Harmer
88.384
970149AG2-104 GEN
Solar/Wind Harmer
109.154
970155AG2-107 GEN
Solar/Wind Harmer
38.539
970245AG2-165 GEN
Solar/Wind Harmer
20.275
270505AE1-170 C O1
Solar/Wind Harmer
16.131
270063AE2-323 C
Solar/Wind Harmer
2.365
945111AF1-176 GEN
Solar/Wind Harmer
19.119
972207SS24-0001
Solar/Wind Harmer
23.558
270449AD2-020 GEN
Solar/Wind Harmer
2.984
943021AE2-325 GEN
Solar/Wind Harmer
3.877
274723RIVER EC ;12
Adder
18.946
274751CRETE EC ;1U
Adder
5.159
274754CRETE EC ;4U
Adder
5.159
276164X3-005 C
Solar/Wind Harmer
0.741
965011AG1-365 GEN
Solar/Wind Harmer
10.534
274812UNIV PK N;8U
Adder
5.266
970373AG2-245 GEN
Solar/Wind Harmer
22.001
276776AD2-060 GEN
Solar/Wind Harmer
0.443
274801UNIV PARK;4U
Adder
6.104
941551AE2-152 GEN
Solar/Wind Harmer
4.732
274676JOLIET 29;8U
Adder
31.933
274674JOLIET 9 ;6U
Adder
16.004
274732ELWOOD EC;7P
Adder
17.074
274871GR RIDGE ;2U
Solar/Wind Harmer
7.979
274745AC1-111 GEN9
Adder
5.774
270055AF2-134 C O1
Solar/Wind Harmer
3.123
276691AA1-018 GEN1
Solar/Wind Harmer
0.476
274682WAUKEGAN ;7U
Adder
18.372
274828WAUKEGAN ;BP
Adder
11.281
958381AF2-132 GEN
Solar/Wind Harmer
9.225
960751AF2-366 GEN
Solar/Wind Harmer
2.915
962781AG1-127 GEN
Solar/Wind Harmer
9.663
964861AG1-349 GEN
Solar/Wind Harmer
7.981
971917AH1-482 GEN
Solar/Wind Harmer
9.21
274872LEEDK;1U
Solar/Wind Harmer
8.331
939401AE1-172 GEN
Solar/Wind Harmer
14.131
276901AD2-066 C O1
Solar/Wind Harmer
3.555
971997AH1-543 GEN
Solar/Wind Harmer
15.875
276861AD2-134 GEN
Solar/Wind Harmer
1.798
274822ROCKFORD ;11
Adder
19.604
972235AH1-702 GEN1
Adder
2.513
274761LEE CO EC;2U
Adder
9.168
274766LEE CO EC;7U
Adder
9.06
24721705FLATG2
Adder
19.59
957471AF2-041 GEN
Solar/Wind Harmer
0.961
959081AF2-199 GEN
Solar/Wind Harmer
0.32
971067AG2-660 GEN
Solar/Wind Harmer
0.075
971599AH1-298 GEN
50/50
10.537
270144AC1-141 ST1_
50/50
2.301
24643105BUCHANAN
50/50
0.014
24653605MOTTVILLE
50/50
0.004
274775LINCOLN ;6U
50/50
7.031
274776LINCOLN ;7U
50/50
7.031
274777LINCOLN ;8U
50/50
7.031
962771AG1-126 GEN
Solar/Wind Harmer
88.384
971347AH1-153 GEN
Solar/Wind Harmer
17.182
270071AF1-092 GEN
Solar/Wind Harmer
16.471
971771AH1-392 GEN
Solar/Wind Harmer
9.787
960681AF2-359 GEN
Solar/Wind Harmer
4.098
971769AH1-391 GEN
Solar/Wind Harmer
10.814
944161AF1-084 GEN
Solar/Wind Harmer
2.339
274814UNIV PK N;0U
Adder
5.312
274807UNIV PK N;3U
Adder
5.3
274805UNIV PK N;1U
Adder
5.277
274811UNIV PK N;7U
Adder
5.266
274827FISK ;RP
Adder
8.13
972037AH1-567 GEN1
Adder
0.192
960591AF2-350 GEN
Solar/Wind Harmer
10.472
972227AH1-698 GEN1
Adder
2.73
274687WILL CNTY;4U
Adder
29.107
274687WILL CNTY;4U
Adder
29.107
274675JOLIET 29;7U
Adder
31.933
274675JOLIET 29;7U
Adder
30.793
24729505KEY G4
Adder
6.744
274731ELWOOD EC;2P
Adder
17.074
274733ELWOOD EC;3P
Adder
17.074
274735ELWOOD EC;4P
Adder
17.074
274728ELWOOD EC;5P
Adder
17.074
970833AG2-524 GEN
Solar/Wind Harmer
9.062
970833AG2-524 GEN
Solar/Wind Harmer
4.215
274746AC1-111 G10
Adder
5.774
274744AC1-111 GEN8
Adder
5.774
270536AF1-215 GEN2
Solar/Wind Harmer
4.686
971177AH1-047 GEN
Solar/Wind Harmer
5.918
958391AF2-133 GEN
Solar/Wind Harmer
9.158
276868AE1-113 GEN
Solar/Wind Harmer
10.216
276882AE2-255 GEN
Solar/Wind Harmer
3.406
971675AH1-338 GEN
Solar/Wind Harmer
18.12
971411AH1-196 GEN
Solar/Wind Harmer
15.1
274863CRW1-WTG
Solar/Wind Harmer
5.594
274864CRW2-WTG
Solar/Wind Harmer
5.594
274823ROCKFORD ;21
Adder
19.462
270054AF2-122 C O1
Solar/Wind Helper
1.653
971171AH1-044 GEN
Solar/Wind Harmer
0.641
270102X2-052 ST
50/50
1.744
270100X2-052 CT1
50/50
1.606
270101X2-052 CT2
50/50
1.606
247620Y3-023
50/50
0.524
274770LINCOLN ;1U
50/50
7.031
274771LINCOLN ;2U
50/50
7.031
970321AG2-212 GEN
Solar/Wind Harmer
20.275
270216AD2-079_GEN
Solar/Wind Harmer
0.658
965681AG1-436 GEN
Solar/Wind Harmer
13.559
965791AG1-447 GEN
Solar/Wind Harmer
6.937
270526AF1-158 GEN
Solar/Wind Harmer
4.919
24441505OLIV SLR
Solar/Wind Harmer
0.145
957891AF2-083 GEN
Solar/Wind Harmer
3.624
960981AF2-389 GEN
Solar/Wind Harmer
1.624
961051AF2-396 GEN
Solar/Wind Harmer
16.938
961051AF2-396 GEN
Solar/Wind Harmer
7.878
970611AG2-400 GEN
Solar/Wind Harmer
10.534
274808UNIV PK N;4U
Adder
5.243
972259AH1-714 GEN
Adder
19.997
274803UNIV PARK;6U
Adder
6.109
274888KELLY CRK;1U
Solar/Wind Harmer
6.183
274887GEN-1.85
Solar/Wind Harmer
5.582
276843GEN-1.7
Solar/Wind Harmer
0.601
958011AF2-095 GEN
Solar/Wind Harmer
15.08
274674JOLIET 9 ;6U
Adder
16.004
274847GR RIDGE ;BU
Solar/Wind Harmer
5.248
971573AH1-285 GEN
Solar/Wind Harmer
8.859
274696ROCKY RD ;4P
Adder
11.666
274695ROCKY RD ;2P
Adder
11.398
274693ROCKY RD ;1P
Adder
11.285
274697ROCKY RD ;3P
Adder
3.096
958481AF2-142 GEN
Solar/Wind Harmer
15.339
274861TOP CROP ;1U
Solar/Wind Harmer
6.194
274862TOP CROP ;2U
Solar/Wind Harmer
5.172
274683WAUKEGAN ;8U
Adder
21.521
274683WAUKEGAN ;8U
Adder
18.141
962691AG1-118 GEN
Solar/Wind Harmer
30.542
970921AG2-575 GEN
Solar/Wind Harmer
10.161
970921AG2-575 GEN
Solar/Wind Harmer
2.363
958491AF2-143 GEN
Solar/Wind Harmer
15.196
942991AE2-321 GEN
Solar/Wind Harmer
10.102
274879MINONK ;1U
Solar/Wind Harmer
6.812
971333AH1-146 GEN
Solar/Wind Harmer
20.122
971335AH1-147 GEN
Solar/Wind Harmer
20.122
274764LEE CO EC;5U
Adder
9.19
274765LEE CO EC;6U
Adder
9.19
274762LEE CO EC;3U
Adder
9.168
274763LEE CO EC;4U
Adder
9.082
972267AH1-718 GEN
Adder
4.072
971341AH1-150 GEN
Solar/Wind Harmer
0.641
971343AH1-151 GEN
Solar/Wind Harmer
0.641
NYPJM->LTFIMP_NY
CLTF
2.605
LGEELTFEXP_LGEE->PJM
CLTF
3.642
WECLTFEXP_WEC->PJM
CLTF
3.804
AG2-052LTFEXP_AG2-052->PJM
LTF
0.236
AH1-155LTFEXP_AH1-155->PJM
LTF
0.354
CPLELTFEXP_CPLE->PJM
CLTF
1.403
CBM West 2LTFEXP_CBM-W2->PJM
CBM
86.692
LAGNLTFEXP_LAGN->PJM
CLTF
11.189
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.594
TVALTFEXP_TVA->PJM
CLTF
5.037
CBM West 1LTFEXP_CBM-W1->PJM
CBM
119.66
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.096
MECLTFEXP_MEC->PJM
CLTF
14.649
SIGELTFEXP_SIGE->PJM
CLTF
0.337

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#8075_05MARYSV 765_A2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8075_05MARYSV 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.92 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6567.82
MW Contribution:29.42
Bus #Bus NameTypeMW Contribution
24289405MTG1
50/50
11.755
243186AF1-051 GEN
50/50
13.011
24318705GVG2
50/50
12.111
24721805FLATG3
50/50
2.932
24721705FLATG2
50/50
53.759
962761AG1-125 GEN
Solar/Wind Harmer
67.471
970149AG2-104 GEN
Solar/Wind Harmer
83.326
970155AG2-107 GEN
Solar/Wind Harmer
29.42
24723205RIVRG3
Adder
35.494
24686105CER G3
Adder
15.183
24686505CER G6
Adder
15.163
971403AH1-188 GEN
Solar/Wind Harmer
23.764
270331AC1-082 GEN3
Solar/Wind Harmer
0.753
970947AG2-589 GEN
Solar/Wind Harmer
3.299
960001AF2-291 GEN
Solar/Wind Harmer
4.831
24728305BUCHG2
Adder
6.779
971315AH1-136 GEN
Solar/Wind Harmer
2.975
971687AH1-348 GEN
Solar/Wind Harmer
1.478
24735205WLF2G2
Adder
7.873
970333AG2-219 GEN
Solar/Wind Harmer
42.852
970091AG2-072 GEN
Adder
103.022
971329AH1-144 GEN
Solar/Wind Harmer
15.308
270445AC2-157 GEN2
Solar/Wind Harmer
7.082
927014AC1-188 GEN
Solar/Wind Harmer
2.008
970245AG2-165 GEN
Solar/Wind Harmer
22.591
24385905FR-11G C
Solar/Wind Harmer
10.226
24387305FR-4G C
Solar/Wind Harmer
6.252
963741AG1-226 GEN
Solar/Wind Harmer
55.333
24791305MDL-5G
Solar/Wind Harmer
2.962
972207SS24-0001
Solar/Wind Harmer
26.925
274773LINCOLN ;4U
Adder
7.573
274774LINCOLN ;5U
Adder
7.573
274880W4-005 GEN4
Solar/Wind Harmer
3.693
963831AG1-236 GEN
Solar/Wind Harmer
12.008
276615X2-022 GEN
Solar/Wind Harmer
2.392
972175AH1-670 GEN
Solar/Wind Harmer
16.675
965911AG1-460 GEN
Solar/Wind Harmer
1.703
940581AE2-045 GEN
Solar/Wind Harmer
12.446
971605AH1-302 GEN
Solar/Wind Harmer
10.643
274854TWINGROVE;U2
Solar/Wind Harmer
8.609
276726Z2-087_GEN
Solar/Wind Harmer
9.649
274745AC1-111 GEN9
Adder
6.801
274674JOLIET 9 ;6U
Adder
18.717
274732ELWOOD EC;7P
Adder
19.981
274682WAUKEGAN ;7U
Adder
21.842
274676JOLIET 29;8U
Adder
37.288
274828WAUKEGAN ;BP
Adder
13.424
237046AF1-021 C
Solar/Wind Helper
0.497
238185AF2-356 C
Solar/Wind Helper
2.208
254303AC2-168 GEN
Solar/Wind Helper
0.155
23751201ROTHROCK
Solar/Wind Helper
0.744
241966AE1-183 GEN
Solar/Wind Helper
0.251
235054AD2-180 GEN
Solar/Wind Helper
1.717
23562501BACKB
Solar/Wind Helper
0.906
238117U2-030
Solar/Wind Helper
0.289
20089226LOOKOUT
Solar/Wind Helper
0.572
235531U2-073 GEN
Solar/Wind Helper
2.719
20088826HIGHLAND
Solar/Wind Helper
0.874
20094526CT_V3-030
Solar/Wind Helper
0.459
964201AG1-281 GEN
Solar/Wind Helper
0.47
23751101LEADS_P59
Solar/Wind Helper
1.247
203860AG1-193 C
Solar/Wind Helper
0.227
203954AE2-126 C
Solar/Wind Helper
0.454
964391AG1-301 GEN
Solar/Wind Helper
0.454
238108AE1-109 GEN1
Solar/Wind Helper
0.085
238206AE2-263_GEN
Solar/Wind Helper
0.874
959471AF2-238 GEN
Solar/Wind Helper
0.447
961971AG1-040 GEN
Solar/Wind Helper
0.444
203835AF1-098 GEN
Solar/Wind Helper
1.765
939741AE1-205 GEN
Solar/Wind Harmer
20.221
24721605FLATG1
50/50
2.932
962771AG1-126 GEN
Solar/Wind Harmer
67.471
972203AH1-686 GEN
Adder
4.314
957241AF2-018 GEN
Solar/Wind Harmer
7.577
270399AC1-101 GEN
Solar/Wind Harmer
7.162
270400AC1-102 GEN
Solar/Wind Harmer
7.162
24477305BRIDGE
Adder
0.586
270330AC1-082 GEN2
Solar/Wind Harmer
1.275
270329AC1-082 GEN1
Solar/Wind Harmer
0.751
941621AE2-160 GEN
Adder
5.032
970281AG2-184 GEN
Solar/Wind Harmer
31.364
972143AH1-644 GEN
Solar/Wind Harmer
14.935
971313AH1-133 GEN
Solar/Wind Harmer
14.825
270132AB1-180 C
Adder
0.172
962211AG1-066 GEN
Solar/Wind Harmer
3.426
24734705WLF1G3
Adder
8.014
24734805WLF1G4
Adder
8.014
24734905WLF1G5
Adder
8.014
971061AG2-657 GEN
Solar/Wind Harmer
12.379
24735105WLF2G1
Adder
7.873
966391AG1-508 GEN
Solar/Wind Harmer
4.623
971985AH1-537 GEN
Solar/Wind Harmer
23.443
971981AH1-535 GEN
Solar/Wind Harmer
12.541
24386205FR-12G C
Solar/Wind Harmer
5.273
24386405FR-21G C
Solar/Wind Harmer
5.292
24386605FR-22G C
Solar/Wind Harmer
5.292
24387005FR-3G C
Solar/Wind Harmer
4.867
963841AG1-237 GEN
Solar/Wind Harmer
13.441
24690905MDL-1G C
Solar/Wind Harmer
9.861
270180AB1-006 GEN1
Solar/Wind Harmer
8.834
946581AF1-322 GEN
Solar/Wind Harmer
12.566
24691005MDL-2G C
Solar/Wind Harmer
4.542
24697605MDL-3G C
Solar/Wind Harmer
4.528
24697905MDL-4G C
Solar/Wind Harmer
2.819
270181AB1-006 GEN2
Solar/Wind Harmer
0.878
274775LINCOLN ;6U
Adder
7.573
274776LINCOLN ;7U
Adder
7.573
274777LINCOLN ;8U
Adder
7.573
944221AF1-090 GEN
Solar/Wind Harmer
13.349
276785W4-005 GEN1
Solar/Wind Harmer
3.693
276174W4-005 GEN2
Solar/Wind Harmer
3.693
276849AB2-070 GEN2
Solar/Wind Harmer
2.746
276848AB2-070 GEN3
Solar/Wind Harmer
2.746
276655WTG1_EQ
Solar/Wind Harmer
10.651
276656WTG2_EQ
Solar/Wind Harmer
1.41
959341AF2-225 GEN
Solar/Wind Harmer
18.299
274746AC1-111 G10
Adder
6.801
274744AC1-111 GEN8
Adder
6.801
972227AH1-698 GEN1
Adder
3.171
274731ELWOOD EC;2P
Adder
19.981
274733ELWOOD EC;3P
Adder
19.981
274735ELWOOD EC;4P
Adder
19.981
274728ELWOOD EC;5P
Adder
19.981
274675JOLIET 29;7U
Adder
37.288
274675JOLIET 29;7U
Adder
35.957
274687WILL CNTY;4U
Adder
2.145
23750501ELLIOTTS
Solar/Wind Helper
0.675
254304AE2-114 C
Solar/Wind Helper
0.214
241997AF1-093 GEN
Solar/Wind Helper
0.251
241982AE2-343 S C
Solar/Wind Helper
0.219
238126S14_GEN_1
Solar/Wind Helper
0.681
20092526R32
Solar/Wind Helper
1.133
203961AE2-224 GEN
Solar/Wind Helper
2.335
20091526CHSTN_FL
Solar/Wind Helper
0.565
203846AF2-130 C
Solar/Wind Helper
0.44
20090526Q36
Solar/Wind Helper
1.009
203993AD2-133_GEN1
Solar/Wind Helper
1.009
203804AE2-113_GEN
Solar/Wind Helper
1.683
941231AE2-117 GEN
Solar/Wind Helper
0.455
203855AF2-088 C
Solar/Wind Helper
0.148
238109AE1-109 GEN2
Solar/Wind Helper
0.085
238110AE1-109 GEN3
Solar/Wind Helper
0.085
941731AE2-173 GEN
Solar/Wind Harmer
5.878
24289405MTG1
50/50
11.755
24318705GVG2
50/50
12.111
24722005FLATG5
50/50
2.932
24721905FLATG4
50/50
53.759
970153AG2-106 GEN
Solar/Wind Harmer
29.42
24686205CER G4
Adder
15.103
24686405CER G5
Adder
15.043
270053AF1-130 C
Solar/Wind Harmer
6.338
970913AG2-568 GEN
Solar/Wind Harmer
12.572
960911AF2-382 GEN
Solar/Wind Harmer
11.374
972103AH1-617 GEN
Solar/Wind Harmer
29.871
971461AH1-227 GEN
Solar/Wind Harmer
7.579
971191AH1-055 GEN
Solar/Wind Harmer
32.25
270346AE1-212 GEN
Solar/Wind Harmer
12.382
970243AG2-164 GEN
Solar/Wind Harmer
35.061
970519AG2-331 GEN
Solar/Wind Harmer
23.555
970699AG2-449 GEN
Solar/Wind Harmer
15.583
943031AE2-326 GEN
Solar/Wind Harmer
4.895
971331AH1-145 GEN
Solar/Wind Harmer
11.867
957541AF2-048 GEN
Solar/Wind Harmer
2.003
970513AG2-328 GEN
Solar/Wind Harmer
22.591
970517AG2-330 GEN
Solar/Wind Harmer
20.49
247619Y1-049
Adder
0.54
970193AG2-126 GEN
Solar/Wind Harmer
18.442
24755605MDL-5G
Solar/Wind Harmer
2.962
970781AG2-491 GEN
Solar/Wind Harmer
12.28
958121AF2-106 GEN
Solar/Wind Harmer
5.567
274772LINCOLN ;3U
Adder
7.573
276686W4-005 GEN3
Solar/Wind Harmer
3.693
971993AH1-541 GEN
Solar/Wind Harmer
11.28
276668AB2-070 GEN1
Solar/Wind Harmer
2.746
276621W2-048 GEN
Solar/Wind Harmer
7.618
276838X2-022 GEN2
Solar/Wind Harmer
0.284
942481AE2-261 GEN
Solar/Wind Harmer
36.492
274853TWINGROVE;U1
Solar/Wind Harmer
8.794
965091AG1-374 GEN
Solar/Wind Harmer
36.602
959611AF2-252 GEN
Solar/Wind Harmer
2.837
942111AE2-223 GEN
Solar/Wind Harmer
10.001
972273AH1-721 GEN
Adder
101.345
972228AH1-698 GEN2
Adder
4.504
274729ELWOOD EC;1P
Adder
19.981
274730ELWOOD EC;6P
Adder
19.981
274734ELWOOD EC;8P
Adder
19.981
274736ELWOOD EC;9P
Adder
19.981
274682WAUKEGAN ;7U
Adder
21.842
274676JOLIET 29;8U
Adder
35.957
237048AF1-022 C
Solar/Wind Helper
0.196
235058AG1-386 C
Solar/Wind Helper
0.457
237043AE2-125 C
Solar/Wind Helper
0.18
254305AE2-115 C
Solar/Wind Helper
0.214
23750701CROSSCHOOL
Solar/Wind Helper
1.202
202652Y1-033 WT C
Solar/Wind Helper
0.561
964991AG1-363 GEN
Solar/Wind Helper
3.697
238118U2-030_1
Solar/Wind Helper
0.289
20089126CSLMN_L13
Solar/Wind Helper
0.588
20089026BF_G21_K23
Solar/Wind Helper
0.465
238127S14_GEN_2
Solar/Wind Helper
0.681
203818AF1-086 GEN
Solar/Wind Helper
1.639
959441AF2-235 GEN
Solar/Wind Helper
0.228
203854AF2-039 C
Solar/Wind Helper
0.307
20334926Z1-069 C
Solar/Wind Helper
1.299
238202AE2-262_GEN
Solar/Wind Helper
0.919
203830AF1-094 GEN
Solar/Wind Helper
0.445
962511AG1-100 GEN
Solar/Wind Helper
0.442
243186AF1-051 GEN
50/50
13.011
24723005RIVRG1
Adder
35.494
24723105RIVRG2
Adder
35.494
24685805CER G1
Adder
15.083
24685905CER G2
Adder
15.083
944971AF1-162 GEN
Solar/Wind Harmer
11.935
24728205BUCHG1
Adder
6.779
971225AH1-072 GEN
Solar/Wind Harmer
2.955
971227AH1-073 GEN
Solar/Wind Harmer
2.955
970239AG2-162 GEN
Solar/Wind Harmer
14.933
270214AC2-123 GEN
Solar/Wind Harmer
3.11
971277AH1-098 GEN
Solar/Wind Harmer
5.306
270444AC2-157 GEN1
Solar/Wind Harmer
7.082
970321AG2-212 GEN
Solar/Wind Harmer
22.591
966841AG1-555 GEN
Solar/Wind Harmer
3.087
970241AG2-163 GEN
Solar/Wind Harmer
30.74
945391AF1-204 GEN
Solar/Wind Harmer
17.134
270583AD2-179 GEN
Solar/Wind Harmer
12.284
945421AF1-207 GEN
Solar/Wind Harmer
17.235
957841AF2-078 GEN
Solar/Wind Harmer
7.417
960161AF2-307 GEN
Solar/Wind Harmer
7.874
274770LINCOLN ;1U
Adder
7.573
274771LINCOLN ;2U
Adder
7.573
276763AC1-053 GEN1
Solar/Wind Harmer
4.827
276764AC1-053 GEN2
Solar/Wind Harmer
4.827
276916AD2-100_GEN
Solar/Wind Harmer
25.634
276911AD2-131_GEN
Solar/Wind Harmer
5.181
957381AF2-032 GEN
Solar/Wind Harmer
0.511
960611AF2-352 GEN
Solar/Wind Harmer
2.837
972259AH1-714 GEN
Adder
23.231
274696ROCKY RD ;4P
Adder
13.859
274695ROCKY RD ;2P
Adder
13.539
274693ROCKY RD ;1P
Adder
13.406
274697ROCKY RD ;3P
Adder
3.678
274674JOLIET 9 ;6U
Adder
18.717
274683WAUKEGAN ;8U
Adder
25.61
274683WAUKEGAN ;8U
Adder
21.588
23652301WDPWR_K20
Solar/Wind Helper
0.145
23585401KL_K28_T16
Solar/Wind Helper
1.297
962101AG1-054 GEN
Solar/Wind Helper
0.64
241985AE1-237 GEN
Solar/Wind Helper
0.244
241967AE2-285_GEN
Solar/Wind Helper
0.626
241801AE1-079 GEN
Solar/Wind Helper
0.243
203955AF1-039 C O1
Solar/Wind Helper
0.37
944781AF1-143 GEN
Solar/Wind Helper
2.439
20083426SW_E13_K22
Solar/Wind Helper
0.055
946071AF1-272 GEN
Solar/Wind Helper
2.647
20088926STNY CRK
Solar/Wind Helper
0.8
20084626FORWARD
Solar/Wind Helper
0.347
238120AE2-309 GEN
Solar/Wind Helper
0.426
203940AF1-140 C
Solar/Wind Helper
0.385
20088626ARWF_N39
Solar/Wind Helper
1.174
20303426NA_O38_P22
Solar/Wind Helper
0.963
946381AF1-302 GEN
Solar/Wind Helper
0.215
203853AF1-134 C O1
Solar/Wind Helper
0.463
203952AE2-129 C
Solar/Wind Helper
0.458
203946AE2-131 C
Solar/Wind Helper
0.459
238217AF1-153 C O1
Solar/Wind Helper
0.229
20398826ARMNA MT
Solar/Wind Helper
1.433
203979AG1-198 GEN
Solar/Wind Helper
0.267
203980AG1-197 GEN
Solar/Wind Helper
0.333
944201AF1-088_MTX
Adder
147.459
957141AF2-008_MTX
Adder
73.729
NYPJM->LTFIMP_NY
CLTF
5.324
LGEELTFEXP_LGEE->PJM
CLTF
8.439
WECLTFEXP_WEC->PJM
CLTF
4.643
AG2-052LTFEXP_AG2-052->PJM
LTF
0.281
AH1-155LTFEXP_AH1-155->PJM
LTF
0.422
CPLELTFEXP_CPLE->PJM
CLTF
6.999
CBM West 2LTFEXP_CBM-W2->PJM
CBM
159.017
LAGNLTFEXP_LAGN->PJM
CLTF
23.289
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.656
TVALTFEXP_TVA->PJM
CLTF
11.825
CBM West 1LTFEXP_CBM-W1->PJM
CBM
150.395
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.72
MECLTFEXP_MEC->PJM
CLTF
20.29
SIGELTFEXP_SIGE->PJM
CLTF
0.642

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#8980_05KAMMER 765_QQ2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8980_05KAMMER 765_QQ2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.66 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6443.11
MW Contribution:23.89
Bus #Bus NameTypeMW Contribution
24289405MTG1
50/50
11.351
243186AF1-051 GEN
50/50
12.478
24318705GVG2
50/50
11.615
24721805FLATG3
50/50
2.756
24721705FLATG2
50/50
50.519
24723205RIVRG3
Adder
36.021
24686105CER G3
Adder
15.629
24686505CER G6
Adder
15.608
270331AC1-082 GEN3
Solar/Wind Harmer
0.804
970947AG2-589 GEN
Solar/Wind Harmer
3.539
960001AF2-291 GEN
Solar/Wind Harmer
5.242
971403AH1-188 GEN
Solar/Wind Harmer
24.059
962761AG1-125 GEN
Solar/Wind Harmer
54.777
970149AG2-104 GEN
Solar/Wind Harmer
67.649
970155AG2-107 GEN
Solar/Wind Harmer
23.885
971315AH1-136 GEN
Solar/Wind Harmer
3.199
927014AC1-188 GEN
Solar/Wind Harmer
2.494
971687AH1-348 GEN
Solar/Wind Harmer
1.529
24728305BUCHG2
Adder
6.831
970333AG2-219 GEN
Solar/Wind Harmer
46.803
970091AG2-072 GEN
Adder
113.581
945681AF1-233 GEN
Solar/Wind Harmer
27.516
252507AC2-088 GEN
Solar/Wind Harmer
2.603
25196808ZIMRHP
Adder
109.116
339216AC1-074 GEN
Solar/Wind Harmer
2.413
25196008MFTGT1
Adder
1.989
943111AE2-339 GEN
Solar/Wind Harmer
1.263
25194608D.CRK4
Adder
2.348
3429241JKCT 3G
Adder
16.894
3429421JKCT 10G
Adder
11.865
253432AC1-085 GEN2
Solar/Wind Harmer
0.38
946171AF1-282 GEN
Solar/Wind Harmer
14.195
270263AC1-001 GEN
Solar/Wind Harmer
1.475
270445AC2-157 GEN2
Solar/Wind Harmer
7.855
971565AH1-281 GEN
Solar/Wind Harmer
2.807
971821AH1-427 GEN
Solar/Wind Harmer
14.027
24735205WLF2G2
Adder
8.08
24728605AND G2
Adder
5.27
339241AF1-083 GEN
Solar/Wind Harmer
2.279
942081AE2-220 GEN
Solar/Wind Harmer
8.729
270239V3-007_GEN1
Solar/Wind Harmer
2.35
253370AE2-315 SEC1
Adder
2.733
253371AE2-315 SEC2
Adder
2.585
970273AG2-179 GEN
Solar/Wind Harmer
3.322
276903AD2-071 C
Solar/Wind Harmer
13.573
963741AG1-226 GEN
Solar/Wind Harmer
61.007
970291AG2-192 GEN
Solar/Wind Harmer
1.76
270005AE1-210 C O1
Solar/Wind Harmer
7.396
965031AG1-367 GEN
Solar/Wind Harmer
13.534
270032AE2-172
Solar/Wind Harmer
6.293
25326309TAIT D
Adder
1.481
964901AG1-354 GEN
Solar/Wind Harmer
20.265
960071AF2-298 GEN
Solar/Wind Harmer
6.737
274773LINCOLN ;4U
Adder
11.055
274774LINCOLN ;5U
Adder
11.055
274745AC1-111 GEN9
Adder
7.316
274761LEE CO EC;2U
Adder
12.175
274766LEE CO EC;7U
Adder
12.032
237046AF1-021 C
Solar/Wind Helper
0.577
238185AF2-356 C
Solar/Wind Helper
2.612
23751201ROTHROCK
Solar/Wind Helper
0.878
235054AD2-180 GEN
Solar/Wind Helper
2.032
23562501BACKB
Solar/Wind Helper
1.07
238117U2-030
Solar/Wind Helper
0.343
235531U2-073 GEN
Solar/Wind Helper
3.23
20089226LOOKOUT
Solar/Wind Helper
0.665
254303AC2-168 GEN
Solar/Wind Helper
0.173
241966AE1-183 GEN
Solar/Wind Helper
0.28
23751101LEADS_P59
Solar/Wind Helper
1.483
20088826HIGHLAND
Solar/Wind Helper
1.011
20094526CT_V3-030
Solar/Wind Helper
0.53
964201AG1-281 GEN
Solar/Wind Helper
0.544
238108AE1-109 GEN1
Solar/Wind Helper
0.102
964391AG1-301 GEN
Solar/Wind Helper
0.529
203954AE2-126 C
Solar/Wind Helper
0.522
238206AE2-263_GEN
Solar/Wind Helper
1.011
959471AF2-238 GEN
Solar/Wind Helper
0.517
203860AG1-193 C
Solar/Wind Helper
0.254
209067AE2-060 GEN
Solar/Wind Helper
0.091
946691AF1-333 GEN
Solar/Wind Helper
0.5
946741AF1-338 GEN
Solar/Wind Helper
0.5
961421AF2-433 GEN
Solar/Wind Helper
0.499
957921AF2-086 GEN
Solar/Wind Helper
0.493
961331AF2-424 GEN
Solar/Wind Helper
0.499
209027LOR2_Q27
Solar/Wind Helper
1.165
963071AG1-156 GEN
Solar/Wind Helper
1.625
963161AG1-165 GEN
Solar/Wind Helper
0.496
316095T157 G97
Solar/Wind Helper
1.154
23583801GRNGAP
Solar/Wind Helper
4.282
961971AG1-040 GEN
Solar/Wind Helper
0.492
203835AF1-098 GEN
Solar/Wind Helper
1.958
20674628WNG_W3-110
Solar/Wind Helper
0.097
207510AF2-138 C
Solar/Wind Helper
0.088
20676728BRNX1-095
Solar/Wind Helper
0.032
217169METRODIV C
Solar/Wind Helper
0.004
217211CAMDEN ST C
Solar/Wind Helper
0.005
20673728F2S_V4-070
Solar/Wind Helper
0.032
219249CENTRALDIV C
Solar/Wind Helper
0.011
219908AB1-139 C
Solar/Wind Helper
0.079
219919AE1-041 FULL
Solar/Wind Helper
0.004
218438BLK ROCK C
Solar/Wind Helper
0.029
219612MATRIX C
Solar/Wind Helper
0.025
20720528MAN_W1-024
Solar/Wind Helper
0.03
20714528FRN_Y2-051
Solar/Wind Helper
0.061
219276PARKLANDSO C
Solar/Wind Helper
0.095
20720828JCB_W4-025
Solar/Wind Helper
0.067
20715028HAN_X4-015
Solar/Wind Helper
0.061
20716028EGP_W2-019
Solar/Wind Helper
0.02
959561AF2-247 GEN
Solar/Wind Helper
0.022
219348LDSOLAR C
Solar/Wind Helper
0.121
219906AC1-017 C
Solar/Wind Helper
0.044
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219291REEVESSOUT C
Solar/Wind Helper
0.012
219912AD2-042 GEN
Solar/Wind Helper
0.158
219766PARADISE C
Solar/Wind Helper
0.057
219623KINSLEYBEA C
Solar/Wind Helper
0.002
228729W2-030 C
Solar/Wind Helper
0.116
24721605FLATG1
50/50
2.756
972203AH1-686 GEN
Adder
4.425
270330AC1-082 GEN2
Solar/Wind Harmer
1.362
270329AC1-082 GEN1
Solar/Wind Harmer
0.802
957241AF2-018 GEN
Solar/Wind Harmer
7.728
270399AC1-101 GEN
Solar/Wind Harmer
7.31
270400AC1-102 GEN
Solar/Wind Harmer
7.31
962771AG1-126 GEN
Solar/Wind Harmer
54.777
24477305BRIDGE
Adder
0.588
970281AG2-184 GEN
Solar/Wind Harmer
32.861
972143AH1-644 GEN
Solar/Wind Harmer
15.648
971985AH1-537 GEN
Solar/Wind Harmer
27.909
941621AE2-160 GEN
Adder
5.057
962211AG1-066 GEN
Solar/Wind Harmer
3.665
971313AH1-133 GEN
Solar/Wind Harmer
14.875
270367AC2-061_GEN
Solar/Wind Harmer
4.719
970879AG2-548 GEN
Solar/Wind Harmer
6.295
972163AH1-664 GEN
Solar/Wind Harmer
14.604
972165AH1-665 GEN
Solar/Wind Harmer
11.684
339243AC2-075 GEN1
Solar/Wind Harmer
0.653
25196108MFTGT2
Adder
2.193
25196108MFTGT2
Adder
2.036
3429211JKCT 2G
Adder
16.676
252524AE2-267 GEN
Solar/Wind Harmer
2.249
25196408WSDLE3
Adder
12.579
25196308WSDLE2
Adder
12.47
25196208WSDLE1
Adder
12.439
25196708WSDLE6
Adder
12.407
25196508WSDLE4
Adder
12.095
24734705WLF1G3
Adder
8.198
24734805WLF1G4
Adder
8.198
24734905WLF1G5
Adder
8.198
270340AC2-060 GEN
Solar/Wind Harmer
4.288
270132AB1-180 C
Adder
0.17
339211AE2-254 GEN
Solar/Wind Harmer
2.129
24735105WLF2G1
Adder
8.08
970455AG2-298 GEN
Solar/Wind Harmer
8.379
965401AG1-405 GEN
Solar/Wind Harmer
7.914
965411AG1-406 GEN
Solar/Wind Harmer
3.552
944031AF1-071 GEN
Solar/Wind Harmer
1.391
270269AC2-059
Solar/Wind Harmer
12.868
971061AG2-657 GEN
Solar/Wind Harmer
12.35
270240V3-007_GEN2
Solar/Wind Harmer
8.448
253372AE2-315 SEC3
Adder
2.585
253372AE2-315 SEC3
Adder
2.585
25306009OHH W.
Adder
3.927
24725505WLD G2 C
Solar/Wind Harmer
5.403
24699105WLD G1 C
Solar/Wind Harmer
5.339
253349AC2-067 GEN
Solar/Wind Harmer
6.756
253400AC2-068 GEN
Solar/Wind Harmer
2.717
965461AG1-414 GEN
Solar/Wind Harmer
3.069
970289AG2-191 GEN
Solar/Wind Harmer
2.572
270594AE1-207 GEN
Solar/Wind Harmer
19.886
963841AG1-237 GEN
Solar/Wind Harmer
14.783
24729505KEY G4
Adder
8.586
274775LINCOLN ;6U
Adder
11.055
274776LINCOLN ;7U
Adder
11.055
274777LINCOLN ;8U
Adder
11.055
274746AC1-111 G10
Adder
7.316
274744AC1-111 GEN8
Adder
7.316
274731ELWOOD EC;2P
Adder
21.509
274733ELWOOD EC;3P
Adder
13.442
23750501ELLIOTTS
Solar/Wind Helper
0.788
238126S14_GEN_1
Solar/Wind Helper
0.81
254304AE2-114 C
Solar/Wind Helper
0.239
241997AF1-093 GEN
Solar/Wind Helper
0.28
241982AE2-343 S C
Solar/Wind Helper
0.243
20092526R32
Solar/Wind Helper
1.311
203961AE2-224 GEN
Solar/Wind Helper
2.707
20091526CHSTN_FL
Solar/Wind Helper
0.654
238109AE1-109 GEN2
Solar/Wind Helper
0.102
238110AE1-109 GEN3
Solar/Wind Helper
0.102
20090526Q36
Solar/Wind Helper
1.167
203993AD2-133_GEN1
Solar/Wind Helper
1.167
941231AE2-117 GEN
Solar/Wind Helper
0.53
203846AF2-130 C
Solar/Wind Helper
0.497
203855AF2-088 C
Solar/Wind Helper
0.17
203804AE2-113_GEN
Solar/Wind Helper
1.924
959431AF2-234 GEN
Solar/Wind Helper
1
964051AG1-259 GEN
Solar/Wind Helper
0.075
964061AG1-260 GEN
Solar/Wind Helper
0.075
959421AF2-233 GEN
Solar/Wind Helper
0.5
961261AF2-417 GEN
Solar/Wind Helper
0.495
209116AE2-175 GEN
Solar/Wind Helper
1.966
20675128HRM_W1-127
Solar/Wind Helper
0.032
207408W3-077 C
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.149
207484AF2-139 C O1
Solar/Wind Helper
0.092
203975AE1-071-GEN
Solar/Wind Helper
2.674
20674828DL_W4-046
Solar/Wind Helper
0.008
20675928HOL_W4-097
Solar/Wind Helper
0.055
24289405MTG1
50/50
11.351
24318705GVG2
50/50
11.615
24722005FLATG5
50/50
2.756
24721905FLATG4
50/50
50.519
24686205CER G4
Adder
15.547
24686405CER G5
Adder
15.485
270053AF1-130 C
Solar/Wind Harmer
6.465
970153AG2-106 GEN
Solar/Wind Harmer
23.885
971191AH1-055 GEN
Solar/Wind Harmer
36.863
957541AF2-048 GEN
Solar/Wind Harmer
2.488
970913AG2-568 GEN
Solar/Wind Harmer
12.569
972103AH1-617 GEN
Solar/Wind Harmer
31.296
960911AF2-382 GEN
Solar/Wind Harmer
11.517
971461AH1-227 GEN
Solar/Wind Harmer
7.832
970243AG2-164 GEN
Solar/Wind Harmer
38.293
970519AG2-331 GEN
Solar/Wind Harmer
25.727
970699AG2-449 GEN
Solar/Wind Harmer
17.019
972167AH1-666 GEN
Solar/Wind Harmer
11.674
958171AF2-111 GEN
Solar/Wind Harmer
36.017
252510AF1-249 C
Solar/Wind Harmer
0.598
25196008MFTGT1
Adder
1.926
25194608D.CRK4
Adder
2.348
25196608WSDLE5
Adder
12.22
3429391JKCT 9G
Adder
11.865
970093AG2-073 GEN
Solar/Wind Harmer
14.232
253316AC1-085 GEN3
Solar/Wind Harmer
11.89
253433AC1-085 GEN1
Solar/Wind Harmer
7.548
946181AF1-283 GEN
Solar/Wind Harmer
18.454
253406AD2-031_GEN
Solar/Wind Harmer
1.808
966571AG1-526 GEN
Solar/Wind Harmer
31.338
270291AC1-194 GEN
Solar/Wind Harmer
14.929
253415AE1-040 GEN
Solar/Wind Harmer
1.582
972173AH1-669 GEN
Solar/Wind Harmer
6.941
270222AC2-111 GEN
Solar/Wind Harmer
11.283
972273AH1-721 GEN
Adder
114.731
270273AD2-016 GEN
Solar/Wind Harmer
3.68
270356AE2-297 GEN
Solar/Wind Harmer
6.29
24728705AND G3
Adder
11.022
24728505AND G1
Adder
5.27
970193AG2-126 GEN
Solar/Wind Harmer
20.501
270437AC2-090 C
Solar/Wind Harmer
7.623
253303V4-073 C
Solar/Wind Harmer
0.158
253370AE2-315 SEC1
Adder
2.733
253371AE2-315 SEC2
Adder
2.585
270346AE1-212 GEN
Solar/Wind Harmer
12.267
970273AG2-179 GEN
Solar/Wind Harmer
5.305
960741AF2-365 GEN
Solar/Wind Harmer
6.78
247642Z2-115 C
Solar/Wind Harmer
0.087
970289AG2-191 GEN
Solar/Wind Harmer
1.039
970291AG2-192 GEN
Solar/Wind Harmer
0.944
958821AF2-173 GEN
Solar/Wind Harmer
18.947
270004AE1-209 GEN
Solar/Wind Harmer
7.396
274772LINCOLN ;3U
Adder
11.055
274760LEE CO EC;1U
Adder
12.175
274767LEE CO EC;8U
Adder
12.032
274729ELWOOD EC;1P
Adder
21.509
237048AF1-022 C
Solar/Wind Helper
0.228
237043AE2-125 C
Solar/Wind Helper
0.207
235058AG1-386 C
Solar/Wind Helper
0.514
964991AG1-363 GEN
Solar/Wind Helper
4.415
23750701CROSSCHOOL
Solar/Wind Helper
1.427
238118U2-030_1
Solar/Wind Helper
0.343
202652Y1-033 WT C
Solar/Wind Helper
0.655
20089126CSLMN_L13
Solar/Wind Helper
0.683
20089026BF_G21_K23
Solar/Wind Helper
0.541
238127S14_GEN_2
Solar/Wind Helper
0.81
254305AE2-115 C
Solar/Wind Helper
0.239
203818AF1-086 GEN
Solar/Wind Helper
1.887
203854AF2-039 C
Solar/Wind Helper
0.354
20334926Z1-069 C
Solar/Wind Helper
1.49
238202AE2-262_GEN
Solar/Wind Helper
1.063
941421AE2-139 GEN
Solar/Wind Helper
2.573
959441AF2-235 GEN
Solar/Wind Helper
0.255
200917MEHOOPANY_G
Solar/Wind Helper
2.428
209071AE2-133 GEN
Solar/Wind Helper
0.09
946731AF1-337 GEN
Solar/Wind Helper
0.5
212507AE2-042_GEN
Solar/Wind Helper
1.772
961341AF2-425 GEN
Solar/Wind Helper
0.499
212266LOR1
Solar/Wind Helper
0.054
961301AF2-421 GEN
Solar/Wind Helper
0.496
963151AG1-164 GEN
Solar/Wind Helper
0.496
316097T157 G90
Solar/Wind Helper
1.154
203830AF1-094 GEN
Solar/Wind Helper
0.495
20671928W4-073
Solar/Wind Helper
0.098
207518AF1-320_GEN
Solar/Wind Helper
1.718
207437AD2-070 GEN
Solar/Wind Helper
0.15
20675828AU_W4-064
Solar/Wind Helper
0.032
207439AE1-081 C O1
Solar/Wind Helper
0.02
20674328GAR_V4-001
Solar/Wind Helper
0.024
217208PARK ELE C
Solar/Wind Helper
0.005
217209CENTRL HS C
Solar/Wind Helper
0.009
20676428JCR_X2-075
Solar/Wind Helper
0.073
207528AF2-192 GEN
Solar/Wind Helper
0.082
20673628F1S_V4-069
Solar/Wind Helper
0.032
20675428EAM_W2-061
Solar/Wind Helper
0.017
962511AG1-100 GEN
Solar/Wind Helper
0.488
217213AMBOY SO C
Solar/Wind Helper
0.031
218428ETC SOLAR C
Solar/Wind Helper
0.005
205941AD2-115 GEN
Solar/Wind Helper
0.531
20742028HF_AC1-207
Solar/Wind Helper
0.15
20715228NPK_W1-113
Solar/Wind Helper
0.083
207454AA2-184 E
Solar/Wind Helper
0.331
219680HOPEWELLV C1
Solar/Wind Helper
0.003
963711AG1-223 GEN
Solar/Wind Helper
0.068
20714828MDF_W3-079
Solar/Wind Helper
0.139
207445AB1-138_GEN
Solar/Wind Helper
0.111
20720728JCB_W1-129
Solar/Wind Helper
0.061
219304NAMERICA C
Solar/Wind Helper
0.139
219686LUMSOLAR_N C
Solar/Wind Helper
0.042
219907AC1-030 C
Solar/Wind Helper
0.036
218660EHAMPSOLAR C
Solar/Wind Helper
0.035
219904AC1-010 C
Solar/Wind Helper
0.064
219258KINSLEYDEP C
Solar/Wind Helper
0.081
228728W1-130C
Solar/Wind Helper
0.057
230434AG1-499 GEN
Solar/Wind Helper
0.241
230511AF1-262
Solar/Wind Helper
0.015
233972AC1-094 C
Solar/Wind Helper
0.312
233998TM1NIN_3.36
Solar/Wind Helper
0.27
233954AC2-188 GEN
Solar/Wind Helper
0.24
232404W1-003 C
Solar/Wind Helper
0.523
233950AC2-186 GEN
Solar/Wind Helper
0.12
232428Y3-058 C
Solar/Wind Helper
0.349
232434Z2-077 GEN
Solar/Wind Helper
0.131
232426Y1-080 FULL
Solar/Wind Helper
0.04
233964AF2-378 GEN
Solar/Wind Helper
0.043
232422X3-066 FULL
Solar/Wind Helper
0.118
233930AB2-032 GEN
Solar/Wind Helper
0.392
233915AB1-141 GEN
Solar/Wind Helper
0.518
966131AG1-482 GEN
Solar/Wind Helper
0.078
235062AE1-101 C1
Solar/Wind Helper
1.463
237038AE2-054 C
Solar/Wind Helper
0.238
237080AD1-060 GEN
Solar/Wind Helper
0.296
23779801AA1-109
Solar/Wind Helper
0.168
223401AF1-299 GEN
Solar/Wind Helper
0.338
243186AF1-051 GEN
50/50
12.478
24723005RIVRG1
Adder
36.021
24723105RIVRG2
Adder
36.021
24685805CER G1
Adder
15.526
24685905CER G2
Adder
15.526
944971AF1-162 GEN
Solar/Wind Harmer
12.174
971225AH1-072 GEN
Solar/Wind Harmer
3.053
971227AH1-073 GEN
Solar/Wind Harmer
3.053
24728205BUCHG1
Adder
6.831
970239AG2-162 GEN
Solar/Wind Harmer
16.31
270186AC1-089 GEN
Solar/Wind Harmer
9.06
962581AG1-107 GEN
Solar/Wind Harmer
7.424
961491AF2-440 GEN
Solar/Wind Harmer
3.085
960161AF2-307 GEN
Solar/Wind Harmer
9.441
970879AG2-548 GEN
Solar/Wind Harmer
9.023
971073AG2-665 GEN
Solar/Wind Harmer
9.023
971073AG2-665 GEN
Solar/Wind Harmer
6.295
252509AD1-136 GEN
Solar/Wind Harmer
0.372
339221AD2-048_GEN
Solar/Wind Harmer
2.218
972043AH1-570 GEN
Solar/Wind Harmer
3.602
972045AH1-571 GEN
Solar/Wind Harmer
2.882
25183208HLCRTG
Solar/Wind Harmer
8.709
252519AF1-045_GEN
Solar/Wind Harmer
8.714
252516AE2-318_GEN
Solar/Wind Harmer
6.647
970235AG2-159 GEN
Solar/Wind Harmer
5.741
970235AG2-159 GEN
Solar/Wind Harmer
3.504
971125AH1-004 GEN
Solar/Wind Harmer
5.722
970107AG2-081 GEN
Solar/Wind Harmer
4.291
25194408D.CRK1
Adder
10.799
25194508D.CRK3
Adder
2.019
942891AE2-308 GEN
Solar/Wind Harmer
14.268
253317AC1-085 GEN4
Solar/Wind Harmer
11.89
270444AC2-157 GEN1
Solar/Wind Harmer
7.855
253394AE2-221_GEN
Solar/Wind Harmer
6.369
253398AE2-221_GEN2
Solar/Wind Harmer
6.369
964571AG1-320 GEN
Solar/Wind Harmer
11.394
970653AG2-424 GEN
Solar/Wind Harmer
6.671
970653AG2-424 GEN
Solar/Wind Harmer
2.412
24728805RICHG1
Adder
5.204
24728905RICHG2
Adder
5.204
971081AG2-670 GEN
Solar/Wind Harmer
10.253
945391AF1-204 GEN
Solar/Wind Harmer
19.047
24379505HDWTR1G C
Solar/Wind Harmer
10.797
270209AC1-174_GEN
Solar/Wind Harmer
7.62
926881AC1-175 GEN
Solar/Wind Harmer
7.62
253370AE2-315 SEC1
Adder
2.733
339231AF1-038_GEN
Solar/Wind Harmer
2.469
270383AD1-128 GEN
Solar/Wind Harmer
8.302
339236AF1-050_GEN
Solar/Wind Harmer
2.463
970241AG2-163 GEN
Solar/Wind Harmer
33.893
25322209TAIT E
Adder
13.187
25322209TAIT E
Adder
12.891
25326109MON D
Adder
1.763
247621Y3-024
Adder
0.32
274770LINCOLN ;1U
Adder
11.055
274771LINCOLN ;2U
Adder
11.055
972259AH1-714 GEN
Adder
24.976
972267AH1-718 GEN
Adder
5.45
274696ROCKY RD ;4P
Adder
14.914
274695ROCKY RD ;2P
Adder
14.57
274693ROCKY RD ;1P
Adder
14.427
274764LEE CO EC;5U
Adder
12.204
274765LEE CO EC;6U
Adder
12.204
274762LEE CO EC;3U
Adder
12.175
274763LEE CO EC;4U
Adder
12.06
274697ROCKY RD ;3P
Adder
3.958
23652301WDPWR_K20
Solar/Wind Helper
0.168
23585401KL_K28_T16
Solar/Wind Helper
1.53
203955AF1-039 C O1
Solar/Wind Helper
0.432
944781AF1-143 GEN
Solar/Wind Helper
2.836
238120AE2-309 GEN
Solar/Wind Helper
0.507
962101AG1-054 GEN
Solar/Wind Helper
0.715
20083426SW_E13_K22
Solar/Wind Helper
0.064
241985AE1-237 GEN
Solar/Wind Helper
0.271
241967AE2-285_GEN
Solar/Wind Helper
0.696
241801AE1-079 GEN
Solar/Wind Helper
0.271
20088926STNY CRK
Solar/Wind Helper
0.928
946071AF1-272 GEN
Solar/Wind Helper
3.051
20084626FORWARD
Solar/Wind Helper
0.402
203940AF1-140 C
Solar/Wind Helper
0.446
20088626ARWF_N39
Solar/Wind Helper
1.362
20303426NA_O38_P22
Solar/Wind Helper
1.117
203853AF1-134 C O1
Solar/Wind Helper
0.534
946381AF1-302 GEN
Solar/Wind Helper
0.246
203952AE2-129 C
Solar/Wind Helper
0.529
203946AE2-131 C
Solar/Wind Helper
0.53
238217AF1-153 C O1
Solar/Wind Helper
0.262
20398826ARMNA MT
Solar/Wind Helper
1.656
209137AF2-361 C
Solar/Wind Helper
1.531
946751AF1-339 GEN
Solar/Wind Helper
0.5
209054AE2-059 GEN
Solar/Wind Helper
0.09
961431AF2-434 GEN
Solar/Wind Helper
0.499
208972BECR K09
Solar/Wind Helper
0.372
209029WAYMART-WD
Solar/Wind Helper
0.937
203979AG1-198 GEN
Solar/Wind Helper
0.297
211065PSPA IPP
Solar/Wind Helper
0.168
211065PSPA IPP
Solar/Wind Helper
0.168
203980AG1-197 GEN
Solar/Wind Helper
0.369
966111AG1-480 GEN
Solar/Wind Helper
0.049
20674128FR_U2-059
Solar/Wind Helper
0.004
964851AG1-348 GEN
Solar/Wind Helper
0.088
20676328BVR_Y1-020
Solar/Wind Helper
0.029
238208AF1-136 C
Solar/Wind Helper
0.192
207530AG1-191 GEN
Solar/Wind Helper
0.072
966261AG1-495 GEN
Solar/Wind Helper
0.088
218524CNTRALGAS1 C
Solar/Wind Helper
0.173
20675528CPH_W2-050
Solar/Wind Helper
0.093
218526CNTRALGAS2 C
Solar/Wind Helper
0.173
219620RIDERU C
Solar/Wind Helper
0.001
207459AE1-142 C O1
Solar/Wind Helper
0.309
20715728PEM_W1-119
Solar/Wind Helper
0.102
20715828PEM_W1-120
Solar/Wind Helper
0.102
214067T20SOLAR
Solar/Wind Helper
0.012
959381AF2-229 GEN
Solar/Wind Helper
0.364
219607WPEMNERT C
Solar/Wind Helper
0.085
219688LUMSOLAR_S C
Solar/Wind Helper
0.042
219272CLEANLIGHT C
Solar/Wind Helper
0.027
219914AD2-027 C
Solar/Wind Helper
0.121
227927V4-067C
Solar/Wind Helper
0.011
228754AB1-001 C
Solar/Wind Helper
0.027
964001AG1-254 GEN
Solar/Wind Helper
1.003
234033AF1-007_GEN
Solar/Wind Helper
7.245
233923SMA
Solar/Wind Helper
0.989
233990AG1-397 GEN
Solar/Wind Helper
0.031
232432Z2-076 GEN
Solar/Wind Helper
0.069
237085AD2-009_GEN
Solar/Wind Helper
1.449
205932AD2-116_GEN
Solar/Wind Helper
0.523
205956AE1-196_GEN
Solar/Wind Helper
0.523
205943AE1-185 GEN
Solar/Wind Helper
0.523
232436AB1-176 C
Solar/Wind Helper
0.046
233935AB2-179 C
Solar/Wind Helper
1.307
960921AF2-383 GEN
Solar/Wind Helper
0.186
207471AF2-354 C
Solar/Wind Helper
0.184
20674928WA_W3-044
Solar/Wind Helper
0.107
20676228FRD_X1-012
Solar/Wind Helper
0.1
217204WCALDSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217081WEATEXAS C
Solar/Wind Helper
0.014
20671828STAW2-080
Solar/Wind Helper
0.029
207442AE1-156 GEN
Solar/Wind Helper
0.351
20676128MHD_W3-029
Solar/Wind Helper
0.103
20673828FLE_V3-070
Solar/Wind Helper
0.097
218440SUMMTASSOC C
Solar/Wind Helper
0.018
20716928W4-060COL
Solar/Wind Helper
0.055
20720628TIN_W1-124
Solar/Wind Helper
0.203
963391AG1-188 GEN
Solar/Wind Helper
0.088
20714928UPF_X1-085
Solar/Wind Helper
0.005
963401AG1-189 GEN
Solar/Wind Helper
0.06
20390526W1-045 C
Solar/Wind Helper
0.357
219615MILLCREEK C
Solar/Wind Helper
0.028
219921AF1-264
Solar/Wind Helper
0.054
203947AF1-006 C
Solar/Wind Helper
0.527
230407AD2-065 C
Solar/Wind Helper
0.042
230433AD2-135 GEN
Solar/Wind Helper
0.018
233939AC1-091 C
Solar/Wind Helper
0.361
233970AC1-092 C
Solar/Wind Helper
0.361
233901CHERRYDALE C
Solar/Wind Helper
0.24
232408W1-005 C
Solar/Wind Helper
0.523
232410W1-006 C
Solar/Wind Helper
0.523
233946AB2-136 GEN
Solar/Wind Helper
0.586
234036AF2-325 C
Solar/Wind Helper
0.043
233987AB2-037 GEN
Solar/Wind Helper
2.415
233944AB2-135 GEN
Solar/Wind Helper
0.607
232424Y1-079 C
Solar/Wind Helper
0.12
233933AB2-153 GEN
Solar/Wind Helper
0.24
235063AE1-101 C2
Solar/Wind Helper
1.463
205916AD1-020 GEN
Solar/Wind Helper
1.711
237002AB1-128_GEN
Solar/Wind Helper
0.388
237001AB1-127_GEN
Solar/Wind Helper
0.388
235020AA1-095 C
Solar/Wind Helper
0.045
23777901MDS_W4-102
Solar/Wind Helper
0.15
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
237034AC2-136 C
Solar/Wind Helper
0.194
238175AF1-290_GEN
Solar/Wind Helper
0.123
237025AB1-124 C
Solar/Wind Helper
0.145
237006AB1-125 GEN
Solar/Wind Helper
0.109
23777801MSM_W1-116
Solar/Wind Helper
0.1
238169AE2-226 GEN1
Solar/Wind Helper
0.555
238170AE2-226 GEN2
Solar/Wind Helper
0.555
970825AG2-519 GEN
Solar/Wind Harmer
8.467
230415AB2-049 C
Solar/Wind Helper
0.032
230430AE1-229_GEN
Solar/Wind Helper
3.539
233971AC1-093 C
Solar/Wind Helper
0.369
233996TM1833_GEN
Solar/Wind Helper
0.27
233997TMININ_4.2
Solar/Wind Helper
0.27
233952AC2-187 GEN
Solar/Wind Helper
0.24
232406W1-004 FULL
Solar/Wind Helper
0.523
233940AF2-379 C
Solar/Wind Helper
0.064
234015AF2-250 C
Solar/Wind Helper
0.039
233994AC2-023 GEN
Solar/Wind Helper
0.992
233982AB2-133 GEN
Solar/Wind Helper
0.369
233918AB1-142 GEN
Solar/Wind Helper
0.518
235067AD1-061 GEN
Solar/Wind Helper
0.433
205917AD1-020 ES
Solar/Wind Helper
0.368
238221AF1-254 C O1
Solar/Wind Helper
0.236
237030AB1-096 C
Solar/Wind Helper
0.063
223402AF1-300 C
Solar/Wind Helper
0.338
970825AG2-519 GEN
Solar/Wind Harmer
1.889
944201AF1-088_MTX
Adder
163.563
957141AF2-008_MTX
Adder
81.782
NYPJM->LTFIMP_NY
CLTF
6.276
LGEELTFEXP_LGEE->PJM
CLTF
9.844
WECLTFEXP_WEC->PJM
CLTF
5.002
AG2-052LTFEXP_AG2-052->PJM
LTF
0.306
AH1-155LTFEXP_AH1-155->PJM
LTF
0.459
CPLELTFEXP_CPLE->PJM
CLTF
6.557
CBM West 2LTFEXP_CBM-W2->PJM
CBM
173.156
LAGNLTFEXP_LAGN->PJM
CLTF
24.864
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.24
TVALTFEXP_TVA->PJM
CLTF
12.63
CBM West 1LTFEXP_CBM-W1->PJM
CBM
170.264
CBM South 1LTFEXP_CBM-S1->PJM
CBM
48.581
MECLTFEXP_MEC->PJM
CLTF
21.939
SIGELTFEXP_SIGE->PJM
CLTF
0.729

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P1-2_#17217_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#17217_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.67 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6388.32
MW Contribution:29.5
Bus #Bus NameTypeMW Contribution
24289405MTG1
50/50
11.351
243186AF1-051 GEN
50/50
12.478
24318705GVG2
50/50
11.615
24721805FLATG3
50/50
2.756
24721705FLATG2
50/50
50.519
24723205RIVRG3
Adder
36.021
24686105CER G3
Adder
15.629
24686505CER G6
Adder
15.608
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
970947AG2-589 GEN
Solar/Wind Harmer
0.412
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
971403AH1-188 GEN
Solar/Wind Harmer
16.785
962761AG1-125 GEN
Solar/Wind Harmer
46.194
970149AG2-104 GEN
Solar/Wind Harmer
49.891
970155AG2-107 GEN
Solar/Wind Harmer
29.498
971315AH1-136 GEN
Solar/Wind Harmer
2.232
927014AC1-188 GEN
Solar/Wind Harmer
0.007
971687AH1-348 GEN
Solar/Wind Harmer
1.067
24728305BUCHG2
Adder
6.831
970333AG2-219 GEN
Solar/Wind Harmer
7.406
970091AG2-072 GEN
Adder
113.581
945681AF1-233 GEN
Solar/Wind Harmer
19.197
252507AC2-088 GEN
Solar/Wind Harmer
0.46
25196808ZIMRHP
Adder
109.116
339216AC1-074 GEN
Solar/Wind Harmer
0.274
25196008MFTGT1
Adder
1.989
25194608D.CRK4
Adder
2.348
3429241JKCT 3G
Adder
16.894
3429421JKCT 10G
Adder
11.865
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
9.904
270263AC1-001 GEN
Solar/Wind Harmer
0.987
270445AC2-157 GEN2
Solar/Wind Harmer
0.004
971565AH1-281 GEN
Solar/Wind Harmer
1.958
971821AH1-427 GEN
Solar/Wind Harmer
9.786
24735205WLF2G2
Adder
8.08
970773AG2-487 GEN
Solar/Wind Harmer
1.7
24728605AND G2
Adder
5.27
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
6.984
253370AE2-315 SEC1
Adder
2.733
253371AE2-315 SEC2
Adder
2.585
970273AG2-179 GEN
Solar/Wind Harmer
3.322
276903AD2-071 C
Solar/Wind Harmer
10.574
963741AG1-226 GEN
Solar/Wind Harmer
22.385
970291AG2-192 GEN
Solar/Wind Harmer
1.228
270005AE1-210 C O1
Solar/Wind Harmer
2.046
965031AG1-367 GEN
Solar/Wind Harmer
9.442
270032AE2-172
Solar/Wind Harmer
6.293
25326309TAIT D
Adder
1.481
964901AG1-354 GEN
Solar/Wind Harmer
14.138
960071AF2-298 GEN
Solar/Wind Harmer
4.694
970825AG2-519 GEN
Solar/Wind Harmer
3.343
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.004
24791305MDL-5G
Solar/Wind Harmer
0.001
970245AG2-165 GEN
Solar/Wind Harmer
4.056
962241AG1-070 GEN
Solar/Wind Harmer
5.098
945371AF1-202 GEN
Solar/Wind Harmer
0.001
958861AF2-177 GEN
Solar/Wind Harmer
4.037
965911AG1-460 GEN
Solar/Wind Harmer
1.861
247536S-71 GEN
Solar/Wind Harmer
0.374
965651AG1-433 GEN
Solar/Wind Harmer
2.727
276615X2-022 GEN
Solar/Wind Harmer
0.098
963831AG1-236 GEN
Solar/Wind Harmer
3.623
274880W4-005 GEN4
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
11.601
972175AH1-670 GEN
Solar/Wind Harmer
7.662
274854TWINGROVE;U2
Solar/Wind Harmer
0.004
276726Z2-087_GEN
Solar/Wind Harmer
0.003
939741AE1-205 GEN
Solar/Wind Harmer
12.928
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.983
958381AF2-132 GEN
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
6.864
270055AF2-134 C O1
Solar/Wind Harmer
0.007
274877BISHOP HL;1U
Solar/Wind Harmer
0.308
253343AC1-166 GEN
Solar/Wind Harmer
0.004
253325AC1-069 GEN
Solar/Wind Harmer
0.014
970569AG2-363 GEN
Solar/Wind Harmer
27.46
971997AH1-543 GEN
Solar/Wind Harmer
4.802
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
276901AD2-066 C O1
Solar/Wind Harmer
0.009
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274773LINCOLN ;4U
Adder
11.055
274774LINCOLN ;5U
Adder
11.055
276158O29GEN2
Solar/Wind Harmer
0.001
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
276691AA1-018 GEN1
Solar/Wind Harmer
1.106
274745AC1-111 GEN9
Adder
7.316
276861AD2-134 GEN
Solar/Wind Harmer
0.164
274872LEEDK;1U
Solar/Wind Harmer
0.006
274761LEE CO EC;2U
Adder
12.175
274766LEE CO EC;7U
Adder
12.032
237046AF1-021 C
Solar/Wind Helper
0.577
238185AF2-356 C
Solar/Wind Helper
2.612
23751201ROTHROCK
Solar/Wind Helper
0.878
235054AD2-180 GEN
Solar/Wind Helper
2.032
23562501BACKB
Solar/Wind Helper
1.07
238117U2-030
Solar/Wind Helper
0.343
235531U2-073 GEN
Solar/Wind Helper
3.23
20089226LOOKOUT
Solar/Wind Helper
0.665
254303AC2-168 GEN
Solar/Wind Helper
0.173
241966AE1-183 GEN
Solar/Wind Helper
0.28
23751101LEADS_P59
Solar/Wind Helper
1.483
20088826HIGHLAND
Solar/Wind Helper
1.011
20094526CT_V3-030
Solar/Wind Helper
0.53
964201AG1-281 GEN
Solar/Wind Helper
0.544
238108AE1-109 GEN1
Solar/Wind Helper
0.102
964391AG1-301 GEN
Solar/Wind Helper
0.529
203954AE2-126 C
Solar/Wind Helper
0.522
238206AE2-263_GEN
Solar/Wind Helper
1.011
959471AF2-238 GEN
Solar/Wind Helper
0.517
203860AG1-193 C
Solar/Wind Helper
0.254
209067AE2-060 GEN
Solar/Wind Helper
0.091
946691AF1-333 GEN
Solar/Wind Helper
0.5
946741AF1-338 GEN
Solar/Wind Helper
0.5
961421AF2-433 GEN
Solar/Wind Helper
0.499
957921AF2-086 GEN
Solar/Wind Helper
0.493
961331AF2-424 GEN
Solar/Wind Helper
0.499
209027LOR2_Q27
Solar/Wind Helper
1.165
963071AG1-156 GEN
Solar/Wind Helper
1.625
963161AG1-165 GEN
Solar/Wind Helper
0.496
316095T157 G97
Solar/Wind Helper
1.154
23583801GRNGAP
Solar/Wind Helper
4.282
961971AG1-040 GEN
Solar/Wind Helper
0.492
203835AF1-098 GEN
Solar/Wind Helper
1.958
20674628WNG_W3-110
Solar/Wind Helper
0.097
207510AF2-138 C
Solar/Wind Helper
0.088
20676728BRNX1-095
Solar/Wind Helper
0.032
217169METRODIV C
Solar/Wind Helper
0.004
217211CAMDEN ST C
Solar/Wind Helper
0.005
20673728F2S_V4-070
Solar/Wind Helper
0.032
219249CENTRALDIV C
Solar/Wind Helper
0.011
219908AB1-139 C
Solar/Wind Helper
0.079
219919AE1-041 FULL
Solar/Wind Helper
0.004
218438BLK ROCK C
Solar/Wind Helper
0.029
219612MATRIX C
Solar/Wind Helper
0.025
20720528MAN_W1-024
Solar/Wind Helper
0.03
20714528FRN_Y2-051
Solar/Wind Helper
0.061
219276PARKLANDSO C
Solar/Wind Helper
0.095
20720828JCB_W4-025
Solar/Wind Helper
0.067
20715028HAN_X4-015
Solar/Wind Helper
0.061
20716028EGP_W2-019
Solar/Wind Helper
0.02
959561AF2-247 GEN
Solar/Wind Helper
0.022
219348LDSOLAR C
Solar/Wind Helper
0.121
219906AC1-017 C
Solar/Wind Helper
0.044
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219291REEVESSOUT C
Solar/Wind Helper
0.012
219912AD2-042 GEN
Solar/Wind Helper
0.158
219766PARADISE C
Solar/Wind Helper
0.057
219623KINSLEYBEA C
Solar/Wind Helper
0.002
228729W2-030 C
Solar/Wind Helper
0.116
230415AB2-049 C
Solar/Wind Helper
0.032
230430AE1-229_GEN
Solar/Wind Helper
3.539
233971AC1-093 C
Solar/Wind Helper
0.369
233996TM1833_GEN
Solar/Wind Helper
0.27
233997TMININ_4.2
Solar/Wind Helper
0.27
233952AC2-187 GEN
Solar/Wind Helper
0.24
232406W1-004 FULL
Solar/Wind Helper
0.523
233940AF2-379 C
Solar/Wind Helper
0.064
234015AF2-250 C
Solar/Wind Helper
0.039
233994AC2-023 GEN
Solar/Wind Helper
0.992
233982AB2-133 GEN
Solar/Wind Helper
0.369
233918AB1-142 GEN
Solar/Wind Helper
0.518
235067AD1-061 GEN
Solar/Wind Helper
0.433
205917AD1-020 ES
Solar/Wind Helper
0.368
238221AF1-254 C O1
Solar/Wind Helper
0.236
237030AB1-096 C
Solar/Wind Helper
0.063
223402AF1-300 C
Solar/Wind Helper
0.338
957471AF2-041 GEN
Solar/Wind Harmer
5.997
959081AF2-199 GEN
Solar/Wind Harmer
1.999
971067AG2-660 GEN
Solar/Wind Harmer
0.666
24721605FLATG1
50/50
2.756
972203AH1-686 GEN
Adder
4.425
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
957241AF2-018 GEN
Solar/Wind Harmer
-0.002
270399AC1-101 GEN
Solar/Wind Harmer
3.805
270400AC1-102 GEN
Solar/Wind Harmer
3.805
962771AG1-126 GEN
Solar/Wind Harmer
46.194
24477305BRIDGE
Adder
0.588
970281AG2-184 GEN
Solar/Wind Harmer
22.926
972143AH1-644 GEN
Solar/Wind Harmer
11.827
971985AH1-537 GEN
Solar/Wind Harmer
3.245
941621AE2-160 GEN
Adder
5.057
971313AH1-133 GEN
Solar/Wind Harmer
10.378
270367AC2-061_GEN
Solar/Wind Harmer
0.008
970879AG2-548 GEN
Solar/Wind Harmer
9.191
972163AH1-664 GEN
Solar/Wind Harmer
11.344
972165AH1-665 GEN
Solar/Wind Harmer
9.085
339243AC2-075 GEN1
Solar/Wind Harmer
0.002
25196108MFTGT2
Adder
2.193
25196108MFTGT2
Adder
2.036
3429211JKCT 2G
Adder
16.676
252524AE2-267 GEN
Solar/Wind Harmer
0.004
25196408WSDLE3
Adder
12.579
25196308WSDLE2
Adder
12.47
25196208WSDLE1
Adder
12.439
25196708WSDLE6
Adder
12.407
25196508WSDLE4
Adder
12.095
24734705WLF1G3
Adder
8.198
24734805WLF1G4
Adder
8.198
24734905WLF1G5
Adder
8.198
270340AC2-060 GEN
Solar/Wind Harmer
0.011
270132AB1-180 C
Adder
0.17
339211AE2-254 GEN
Solar/Wind Harmer
0.004
24735105WLF2G1
Adder
8.08
970455AG2-298 GEN
Solar/Wind Harmer
6.495
965401AG1-405 GEN
Solar/Wind Harmer
5.522
965411AG1-406 GEN
Solar/Wind Harmer
3.552
270269AC2-059
Solar/Wind Harmer
0.006
971061AG2-657 GEN
Solar/Wind Harmer
6.031
270240V3-007_GEN2
Solar/Wind Harmer
0.003
253372AE2-315 SEC3
Adder
2.585
253372AE2-315 SEC3
Adder
2.585
25306009OHH W.
Adder
3.927
24725505WLD G2 C
Solar/Wind Harmer
0.002
24699105WLD G1 C
Solar/Wind Harmer
0.001
253349AC2-067 GEN
Solar/Wind Harmer
2.978
253400AC2-068 GEN
Solar/Wind Harmer
1.198
970289AG2-191 GEN
Solar/Wind Harmer
1.794
270594AE1-207 GEN
Solar/Wind Harmer
10.572
963841AG1-237 GEN
Solar/Wind Harmer
4.089
970115AG2-085 GEN
Solar/Wind Harmer
3.766
971673AH1-337 GEN
Solar/Wind Harmer
6.118
24386205FR-12G C
Solar/Wind Harmer
0.002
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.002
971029AG2-637 GEN
Solar/Wind Harmer
14.095
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270543AE2-219 C
Solar/Wind Harmer
0.006
971609AH1-304 GEN
Solar/Wind Harmer
1.526
270432AC2-029 GEN
Solar/Wind Harmer
4.141
944221AF1-090 GEN
Solar/Wind Harmer
5.475
965101AG1-375 GEN
Solar/Wind Harmer
9.315
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.339
276848AB2-070 GEN3
Solar/Wind Harmer
0.337
971611AH1-305 GEN
Solar/Wind Harmer
5.525
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.004
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
9.696
24729505KEY G4
Adder
8.586
941731AE2-173 GEN
Solar/Wind Harmer
7.695
966391AG1-508 GEN
Solar/Wind Harmer
1.427
970169AG2-114 GEN
Solar/Wind Harmer
9.2
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
241972AD1-140 GEN
Solar/Wind Harmer
1.003
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
957751AF2-069 GEN
Solar/Wind Harmer
0.302
270536AF1-215 GEN2
Solar/Wind Harmer
0.011
926823AC1-168 GEN
Solar/Wind Harmer
1.557
276868AE1-113 GEN
Solar/Wind Harmer
1.835
276882AE2-255 GEN
Solar/Wind Harmer
1.069
274775LINCOLN ;6U
Adder
11.055
274776LINCOLN ;7U
Adder
11.055
274777LINCOLN ;8U
Adder
11.055
970833AG2-524 GEN
Solar/Wind Harmer
10.052
970833AG2-524 GEN
Solar/Wind Harmer
6.701
274746AC1-111 G10
Adder
7.316
274744AC1-111 GEN8
Adder
7.316
961011AF2-392 GEN
Solar/Wind Harmer
5.358
971675AH1-338 GEN
Solar/Wind Harmer
3.562
274731ELWOOD EC;2P
Adder
21.509
274733ELWOOD EC;3P
Adder
13.442
23750501ELLIOTTS
Solar/Wind Helper
0.788
238126S14_GEN_1
Solar/Wind Helper
0.81
254304AE2-114 C
Solar/Wind Helper
0.239
241997AF1-093 GEN
Solar/Wind Helper
0.28
241982AE2-343 S C
Solar/Wind Helper
0.243
20092526R32
Solar/Wind Helper
1.311
203961AE2-224 GEN
Solar/Wind Helper
2.707
20091526CHSTN_FL
Solar/Wind Helper
0.654
238109AE1-109 GEN2
Solar/Wind Helper
0.102
238110AE1-109 GEN3
Solar/Wind Helper
0.102
20090526Q36
Solar/Wind Helper
1.167
203993AD2-133_GEN1
Solar/Wind Helper
1.167
941231AE2-117 GEN
Solar/Wind Helper
0.53
203846AF2-130 C
Solar/Wind Helper
0.497
203855AF2-088 C
Solar/Wind Helper
0.17
203804AE2-113_GEN
Solar/Wind Helper
1.924
959431AF2-234 GEN
Solar/Wind Helper
1
964051AG1-259 GEN
Solar/Wind Helper
0.075
964061AG1-260 GEN
Solar/Wind Helper
0.075
959421AF2-233 GEN
Solar/Wind Helper
0.5
961261AF2-417 GEN
Solar/Wind Helper
0.495
209116AE2-175 GEN
Solar/Wind Helper
1.966
20675128HRM_W1-127
Solar/Wind Helper
0.032
207408W3-077 C
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.149
207484AF2-139 C O1
Solar/Wind Helper
0.092
203975AE1-071-GEN
Solar/Wind Helper
2.674
20674828DL_W4-046
Solar/Wind Helper
0.008
20675928HOL_W4-097
Solar/Wind Helper
0.055
20676328BVR_Y1-020
Solar/Wind Helper
0.029
238208AF1-136 C
Solar/Wind Helper
0.192
207530AG1-191 GEN
Solar/Wind Helper
0.072
966261AG1-495 GEN
Solar/Wind Helper
0.088
218524CNTRALGAS1 C
Solar/Wind Helper
0.173
20675528CPH_W2-050
Solar/Wind Helper
0.093
218526CNTRALGAS2 C
Solar/Wind Helper
0.173
219620RIDERU C
Solar/Wind Helper
0.001
207459AE1-142 C O1
Solar/Wind Helper
0.309
20715728PEM_W1-119
Solar/Wind Helper
0.102
20715828PEM_W1-120
Solar/Wind Helper
0.102
214067T20SOLAR
Solar/Wind Helper
0.012
959381AF2-229 GEN
Solar/Wind Helper
0.364
219607WPEMNERT C
Solar/Wind Helper
0.085
219688LUMSOLAR_S C
Solar/Wind Helper
0.042
219272CLEANLIGHT C
Solar/Wind Helper
0.027
219914AD2-027 C
Solar/Wind Helper
0.121
227927V4-067C
Solar/Wind Helper
0.011
228754AB1-001 C
Solar/Wind Helper
0.027
964001AG1-254 GEN
Solar/Wind Helper
1.003
234033AF1-007_GEN
Solar/Wind Helper
7.245
233923SMA
Solar/Wind Helper
0.989
233990AG1-397 GEN
Solar/Wind Helper
0.279
232432Z2-076 GEN
Solar/Wind Helper
0.069
237085AD2-009_GEN
Solar/Wind Helper
1.449
205932AD2-116_GEN
Solar/Wind Helper
0.523
205956AE1-196_GEN
Solar/Wind Helper
0.523
205943AE1-185 GEN
Solar/Wind Helper
0.523
232436AB1-176 C
Solar/Wind Helper
0.046
233935AB2-179 C
Solar/Wind Helper
1.307
960921AF2-383 GEN
Solar/Wind Helper
0.373
971171AH1-044 GEN
Solar/Wind Harmer
3.998
24289405MTG1
50/50
11.351
24318705GVG2
50/50
11.615
24722005FLATG5
50/50
2.756
24721905FLATG4
50/50
50.519
24686205CER G4
Adder
15.547
24686405CER G5
Adder
15.485
270053AF1-130 C
Solar/Wind Harmer
2.748
970153AG2-106 GEN
Solar/Wind Harmer
29.498
971191AH1-055 GEN
Solar/Wind Harmer
30.005
970913AG2-568 GEN
Solar/Wind Harmer
8.769
972103AH1-617 GEN
Solar/Wind Harmer
21.835
960911AF2-382 GEN
Solar/Wind Harmer
8.035
971461AH1-227 GEN
Solar/Wind Harmer
5.464
970243AG2-164 GEN
Solar/Wind Harmer
6.06
970519AG2-331 GEN
Solar/Wind Harmer
26.931
970699AG2-449 GEN
Solar/Wind Harmer
2.59
972167AH1-666 GEN
Solar/Wind Harmer
8.145
958171AF2-111 GEN
Solar/Wind Harmer
25.128
252510AF1-249 C
Solar/Wind Harmer
0.077
25196008MFTGT1
Adder
1.926
25194608D.CRK4
Adder
2.348
25196608WSDLE5
Adder
12.22
3429391JKCT 9G
Adder
11.865
970093AG2-073 GEN
Solar/Wind Harmer
9.929
253316AC1-085 GEN3
Solar/Wind Harmer
0.006
253433AC1-085 GEN1
Solar/Wind Harmer
0.005
946181AF1-283 GEN
Solar/Wind Harmer
12.875
253406AD2-031_GEN
Solar/Wind Harmer
0.735
966571AG1-526 GEN
Solar/Wind Harmer
21.864
270291AC1-194 GEN
Solar/Wind Harmer
7.771
253415AE1-040 GEN
Solar/Wind Harmer
0.004
972173AH1-669 GEN
Solar/Wind Harmer
4.843
270222AC2-111 GEN
Solar/Wind Harmer
4.893
972273AH1-721 GEN
Adder
114.731
270273AD2-016 GEN
Solar/Wind Harmer
0.998
270356AE2-297 GEN
Solar/Wind Harmer
0.013
24728705AND G3
Adder
11.022
24728505AND G1
Adder
5.27
970193AG2-126 GEN
Solar/Wind Harmer
14.303
270437AC2-090 C
Solar/Wind Harmer
0.004
253370AE2-315 SEC1
Adder
2.733
253371AE2-315 SEC2
Adder
2.585
270346AE1-212 GEN
Solar/Wind Harmer
8.4
970273AG2-179 GEN
Solar/Wind Harmer
5.694
960741AF2-365 GEN
Solar/Wind Harmer
4.731
970191AG2-125 GEN
Solar/Wind Harmer
2.433
247642Z2-115 C
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
1.039
970291AG2-192 GEN
Solar/Wind Harmer
0.944
958821AF2-173 GEN
Solar/Wind Harmer
13.219
270004AE1-209 GEN
Solar/Wind Harmer
2.046
946031AF1-268 GEN
Solar/Wind Harmer
8.936
339250AF1-203 GEN
Solar/Wind Harmer
0.001
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
9.369
971155AH1-034 GEN
Solar/Wind Harmer
10.922
970513AG2-328 GEN
Solar/Wind Harmer
4.056
970517AG2-330 GEN
Solar/Wind Harmer
24.338
962251AG1-071 GEN
Solar/Wind Harmer
5.847
942481AE2-261 GEN
Solar/Wind Harmer
27.825
276621W2-048 GEN
Solar/Wind Harmer
0.469
276838X2-022 GEN2
Solar/Wind Harmer
0.523
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
4.291
276668AB2-070 GEN1
Solar/Wind Harmer
0.339
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
943031AE2-326 GEN
Solar/Wind Harmer
4.828
274853TWINGROVE;U1
Solar/Wind Harmer
0.004
965091AG1-374 GEN
Solar/Wind Harmer
27.736
959611AF2-252 GEN
Solar/Wind Harmer
3.082
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
13.864
942111AE2-223 GEN
Solar/Wind Harmer
3.001
964401AG1-302 GEN
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
41.286
270535AF1-215 GEN1
Solar/Wind Harmer
0.011
274878BISHOP HL;2U
Solar/Wind Harmer
0.308
253338AC1-165 GEN
Solar/Wind Harmer
0.004
253333AC1-068 GEN
Solar/Wind Harmer
0.014
970571AG2-364 GEN
Solar/Wind Harmer
18.307
276889AE2-281 GEN
Solar/Wind Harmer
0.001
276897AD1-100 C
Solar/Wind Harmer
0.012
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274772LINCOLN ;3U
Adder
11.055
276805AD2-038 GEN
Solar/Wind Harmer
0.003
276157O29GEN1
Solar/Wind Harmer
1.478
970707AG2-453 GEN
Solar/Wind Harmer
29.848
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
943121AE2-341 GEN
Solar/Wind Harmer
15.314
943591AF1-030 GEN
Solar/Wind Harmer
10.184
274855GSG-6 ;RU
Solar/Wind Harmer
0.335
274850MENDOTA H;RU
Solar/Wind Harmer
0.108
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.164
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.974
274760LEE CO EC;1U
Adder
12.175
274767LEE CO EC;8U
Adder
12.032
274729ELWOOD EC;1P
Adder
21.509
237048AF1-022 C
Solar/Wind Helper
0.228
237043AE2-125 C
Solar/Wind Helper
0.207
235058AG1-386 C
Solar/Wind Helper
0.514
964991AG1-363 GEN
Solar/Wind Helper
4.415
23750701CROSSCHOOL
Solar/Wind Helper
1.427
238118U2-030_1
Solar/Wind Helper
0.343
202652Y1-033 WT C
Solar/Wind Helper
0.655
20089126CSLMN_L13
Solar/Wind Helper
0.683
20089026BF_G21_K23
Solar/Wind Helper
0.541
238127S14_GEN_2
Solar/Wind Helper
0.81
254305AE2-115 C
Solar/Wind Helper
0.239
203818AF1-086 GEN
Solar/Wind Helper
1.887
203854AF2-039 C
Solar/Wind Helper
0.354
20334926Z1-069 C
Solar/Wind Helper
1.49
238202AE2-262_GEN
Solar/Wind Helper
1.063
941421AE2-139 GEN
Solar/Wind Helper
2.573
959441AF2-235 GEN
Solar/Wind Helper
0.255
200917MEHOOPANY_G
Solar/Wind Helper
2.428
209071AE2-133 GEN
Solar/Wind Helper
0.09
946731AF1-337 GEN
Solar/Wind Helper
0.5
212507AE2-042_GEN
Solar/Wind Helper
1.772
961341AF2-425 GEN
Solar/Wind Helper
0.499
212266LOR1
Solar/Wind Helper
0.054
961301AF2-421 GEN
Solar/Wind Helper
0.496
963151AG1-164 GEN
Solar/Wind Helper
0.496
316097T157 G90
Solar/Wind Helper
1.154
203830AF1-094 GEN
Solar/Wind Helper
0.495
20671928W4-073
Solar/Wind Helper
0.098
207518AF1-320_GEN
Solar/Wind Helper
1.718
207437AD2-070 GEN
Solar/Wind Helper
0.15
20675828AU_W4-064
Solar/Wind Helper
0.032
207439AE1-081 C O1
Solar/Wind Helper
0.02
20674328GAR_V4-001
Solar/Wind Helper
0.024
217208PARK ELE C
Solar/Wind Helper
0.005
217209CENTRL HS C
Solar/Wind Helper
0.009
20676428JCR_X2-075
Solar/Wind Helper
0.073
207528AF2-192 GEN
Solar/Wind Helper
0.082
20673628F1S_V4-069
Solar/Wind Helper
0.032
20675428EAM_W2-061
Solar/Wind Helper
0.017
962511AG1-100 GEN
Solar/Wind Helper
0.488
217213AMBOY SO C
Solar/Wind Helper
0.031
218428ETC SOLAR C
Solar/Wind Helper
0.005
205941AD2-115 GEN
Solar/Wind Helper
0.531
20742028HF_AC1-207
Solar/Wind Helper
0.15
20715228NPK_W1-113
Solar/Wind Helper
0.083
207454AA2-184 E
Solar/Wind Helper
0.331
219680HOPEWELLV C1
Solar/Wind Helper
0.003
963711AG1-223 GEN
Solar/Wind Helper
0.068
20714828MDF_W3-079
Solar/Wind Helper
0.139
207445AB1-138_GEN
Solar/Wind Helper
0.111
20720728JCB_W1-129
Solar/Wind Helper
0.061
219304NAMERICA C
Solar/Wind Helper
0.139
219686LUMSOLAR_N C
Solar/Wind Helper
0.042
219907AC1-030 C
Solar/Wind Helper
0.036
218660EHAMPSOLAR C
Solar/Wind Helper
0.035
219904AC1-010 C
Solar/Wind Helper
0.064
219258KINSLEYDEP C
Solar/Wind Helper
0.081
228728W1-130C
Solar/Wind Helper
0.057
230434AG1-499 GEN
Solar/Wind Helper
0.241
230511AF1-262
Solar/Wind Helper
0.015
233972AC1-094 C
Solar/Wind Helper
0.312
233998TM1NIN_3.36
Solar/Wind Helper
0.27
233954AC2-188 GEN
Solar/Wind Helper
0.24
232404W1-003 C
Solar/Wind Helper
0.523
233950AC2-186 GEN
Solar/Wind Helper
0.12
232428Y3-058 C
Solar/Wind Helper
0.349
232434Z2-077 GEN
Solar/Wind Helper
0.131
232426Y1-080 FULL
Solar/Wind Helper
0.04
233964AF2-378 GEN
Solar/Wind Helper
0.043
232422X3-066 FULL
Solar/Wind Helper
0.118
233930AB2-032 GEN
Solar/Wind Helper
0.392
233915AB1-141 GEN
Solar/Wind Helper
0.518
966131AG1-482 GEN
Solar/Wind Helper
0.139
235062AE1-101 C1
Solar/Wind Helper
1.463
237038AE2-054 C
Solar/Wind Helper
0.238
237080AD1-060 GEN
Solar/Wind Helper
0.296
23779801AA1-109
Solar/Wind Helper
0.168
223401AF1-299 GEN
Solar/Wind Helper
0.338
959091AF2-200 GEN
Solar/Wind Harmer
3.998
243186AF1-051 GEN
50/50
12.478
24723005RIVRG1
Adder
36.021
24723105RIVRG2
Adder
36.021
24685805CER G1
Adder
15.526
24685905CER G2
Adder
15.526
944971AF1-162 GEN
Solar/Wind Harmer
12.174
971225AH1-072 GEN
Solar/Wind Harmer
2.13
971227AH1-073 GEN
Solar/Wind Harmer
2.13
24728205BUCHG1
Adder
6.831
970239AG2-162 GEN
Solar/Wind Harmer
2.59
270186AC1-089 GEN
Solar/Wind Harmer
0.006
962581AG1-107 GEN
Solar/Wind Harmer
0.002
960161AF2-307 GEN
Solar/Wind Harmer
6.771
971073AG2-665 GEN
Solar/Wind Harmer
9.191
252509AD1-136 GEN
Solar/Wind Harmer
0.051
339221AD2-048_GEN
Solar/Wind Harmer
0.006
972043AH1-570 GEN
Solar/Wind Harmer
2.614
972045AH1-571 GEN
Solar/Wind Harmer
2.094
25183208HLCRTG
Solar/Wind Harmer
0.016
252519AF1-045_GEN
Solar/Wind Harmer
8.714
252516AE2-318_GEN
Solar/Wind Harmer
7.729
970235AG2-159 GEN
Solar/Wind Harmer
6.108
970235AG2-159 GEN
Solar/Wind Harmer
3.504
971125AH1-004 GEN
Solar/Wind Harmer
3.992
970107AG2-081 GEN
Solar/Wind Harmer
2.994
25194408D.CRK1
Adder
10.799
25194508D.CRK3
Adder
2.019
942891AE2-308 GEN
Solar/Wind Harmer
9.954
253317AC1-085 GEN4
Solar/Wind Harmer
0.006
270444AC2-157 GEN1
Solar/Wind Harmer
0.004
971587AH1-292 GEN
Solar/Wind Harmer
7.197
253394AE2-221_GEN
Solar/Wind Harmer
0.012
253398AE2-221_GEN2
Solar/Wind Harmer
0.012
964571AG1-320 GEN
Solar/Wind Harmer
8.854
970653AG2-424 GEN
Solar/Wind Harmer
4.654
970653AG2-424 GEN
Solar/Wind Harmer
2.412
24728805RICHG1
Adder
5.204
24728905RICHG2
Adder
5.204
971081AG2-670 GEN
Solar/Wind Harmer
7.154
945391AF1-204 GEN
Solar/Wind Harmer
10.131
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
253370AE2-315 SEC1
Adder
2.733
270383AD1-128 GEN
Solar/Wind Harmer
0.006
970241AG2-163 GEN
Solar/Wind Harmer
5.517
971613AH1-306 GEN
Solar/Wind Harmer
4.531
25322209TAIT E
Adder
13.187
25322209TAIT E
Adder
12.891
970825AG2-519 GEN
Solar/Wind Harmer
10.439
960441AF2-335 GEN
Solar/Wind Harmer
9.416
966841AG1-555 GEN
Solar/Wind Harmer
1.065
339255AE2-071 GEN
Solar/Wind Harmer
-0.154
970321AG2-212 GEN
Solar/Wind Harmer
4.056
971485AH1-239 GEN
Solar/Wind Harmer
7.489
964781AG1-341 GEN
Solar/Wind Harmer
9.922
966021AG1-471 GEN
Solar/Wind Harmer
5.054
25326109MON D
Adder
1.763
970883AG2-550 GEN
Solar/Wind Harmer
9.347
970885AG2-551 GEN
Solar/Wind Harmer
3.116
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
270599AE1-208 GEN
Solar/Wind Harmer
8.564
270031AE2-169
Solar/Wind Harmer
5.138
276916AD2-100_GEN
Solar/Wind Harmer
19.555
276911AD2-131_GEN
Solar/Wind Harmer
1.288
944541AF1-119 GEN
Solar/Wind Harmer
0.623
960971AF2-388 GEN
Solar/Wind Harmer
5.453
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.696
247621Y3-024
Adder
0.32
960611AF2-352 GEN
Solar/Wind Harmer
3.082
270201AC2-176 GEN
Solar/Wind Harmer
0.002
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.36
276646AC1-214 GEN2
Solar/Wind Harmer
0.36
276782AC1-033 GEN
Solar/Wind Harmer
0.001
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
274879MINONK ;1U
Solar/Wind Harmer
0.386
274770LINCOLN ;1U
Adder
11.055
274771LINCOLN ;2U
Adder
11.055
276741O09 GEN1
Solar/Wind Harmer
0.325
276708O09 GEN2
Solar/Wind Harmer
0.325
958491AF2-143 GEN
Solar/Wind Harmer
13.709
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
1.236
972259AH1-714 GEN
Adder
24.976
958481AF2-142 GEN
Solar/Wind Harmer
13.701
971573AH1-285 GEN
Solar/Wind Harmer
1.702
276603SUBLETTE C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
5.45
274696ROCKY RD ;4P
Adder
14.914
274695ROCKY RD ;2P
Adder
14.57
274693ROCKY RD ;1P
Adder
14.427
274764LEE CO EC;5U
Adder
12.204
274765LEE CO EC;6U
Adder
12.204
274762LEE CO EC;3U
Adder
12.175
274763LEE CO EC;4U
Adder
12.06
274697ROCKY RD ;3P
Adder
3.958
23652301WDPWR_K20
Solar/Wind Helper
0.168
23585401KL_K28_T16
Solar/Wind Helper
1.53
203955AF1-039 C O1
Solar/Wind Helper
0.432
944781AF1-143 GEN
Solar/Wind Helper
2.836
238120AE2-309 GEN
Solar/Wind Helper
0.507
962101AG1-054 GEN
Solar/Wind Helper
0.715
20083426SW_E13_K22
Solar/Wind Helper
0.064
241985AE1-237 GEN
Solar/Wind Helper
0.271
241967AE2-285_GEN
Solar/Wind Helper
0.696
241801AE1-079 GEN
Solar/Wind Helper
0.271
20088926STNY CRK
Solar/Wind Helper
0.928
946071AF1-272 GEN
Solar/Wind Helper
3.051
20084626FORWARD
Solar/Wind Helper
0.402
203940AF1-140 C
Solar/Wind Helper
0.446
20088626ARWF_N39
Solar/Wind Helper
1.362
20303426NA_O38_P22
Solar/Wind Helper
1.117
203853AF1-134 C O1
Solar/Wind Helper
0.534
946381AF1-302 GEN
Solar/Wind Helper
0.246
203952AE2-129 C
Solar/Wind Helper
0.529
203946AE2-131 C
Solar/Wind Helper
0.53
238217AF1-153 C O1
Solar/Wind Helper
0.262
20398826ARMNA MT
Solar/Wind Helper
1.656
209137AF2-361 C
Solar/Wind Helper
1.531
946751AF1-339 GEN
Solar/Wind Helper
0.5
209054AE2-059 GEN
Solar/Wind Helper
0.09
961431AF2-434 GEN
Solar/Wind Helper
0.499
208972BECR K09
Solar/Wind Helper
0.372
209029WAYMART-WD
Solar/Wind Helper
0.937
203979AG1-198 GEN
Solar/Wind Helper
0.297
211065PSPA IPP
Solar/Wind Helper
0.168
211065PSPA IPP
Solar/Wind Helper
0.168
203980AG1-197 GEN
Solar/Wind Helper
0.369
966111AG1-480 GEN
Solar/Wind Helper
0.082
20674128FR_U2-059
Solar/Wind Helper
0.004
964851AG1-348 GEN
Solar/Wind Helper
0.088
207471AF2-354 C
Solar/Wind Helper
0.184
20674928WA_W3-044
Solar/Wind Helper
0.107
20676228FRD_X1-012
Solar/Wind Helper
0.1
217204WCALDSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217081WEATEXAS C
Solar/Wind Helper
0.014
20671828STAW2-080
Solar/Wind Helper
0.029
207442AE1-156 GEN
Solar/Wind Helper
0.351
20676128MHD_W3-029
Solar/Wind Helper
0.103
20673828FLE_V3-070
Solar/Wind Helper
0.097
218440SUMMTASSOC C
Solar/Wind Helper
0.018
20716928W4-060COL
Solar/Wind Helper
0.055
20720628TIN_W1-124
Solar/Wind Helper
0.203
963391AG1-188 GEN
Solar/Wind Helper
0.088
20714928UPF_X1-085
Solar/Wind Helper
0.005
963401AG1-189 GEN
Solar/Wind Helper
0.06
20390526W1-045 C
Solar/Wind Helper
0.357
219615MILLCREEK C
Solar/Wind Helper
0.028
219921AF1-264
Solar/Wind Helper
0.054
203947AF1-006 C
Solar/Wind Helper
0.527
230407AD2-065 C
Solar/Wind Helper
0.042
230433AD2-135 GEN
Solar/Wind Helper
0.018
233939AC1-091 C
Solar/Wind Helper
0.361
233970AC1-092 C
Solar/Wind Helper
0.361
233901CHERRYDALE C
Solar/Wind Helper
0.24
232408W1-005 C
Solar/Wind Helper
0.523
232410W1-006 C
Solar/Wind Helper
0.523
233946AB2-136 GEN
Solar/Wind Helper
0.586
234036AF2-325 C
Solar/Wind Helper
0.043
233987AB2-037 GEN
Solar/Wind Helper
2.415
233944AB2-135 GEN
Solar/Wind Helper
0.607
232424Y1-079 C
Solar/Wind Helper
0.12
233933AB2-153 GEN
Solar/Wind Helper
0.24
235063AE1-101 C2
Solar/Wind Helper
1.463
205916AD1-020 GEN
Solar/Wind Helper
1.711
237002AB1-128_GEN
Solar/Wind Helper
0.388
237001AB1-127_GEN
Solar/Wind Helper
0.388
235020AA1-095 C
Solar/Wind Helper
0.045
23777901MDS_W4-102
Solar/Wind Helper
0.15
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
237034AC2-136 C
Solar/Wind Helper
0.194
238175AF1-290_GEN
Solar/Wind Helper
0.123
237025AB1-124 C
Solar/Wind Helper
0.145
237006AB1-125 GEN
Solar/Wind Helper
0.109
23777801MSM_W1-116
Solar/Wind Helper
0.1
238169AE2-226 GEN1
Solar/Wind Helper
0.555
238170AE2-226 GEN2
Solar/Wind Helper
0.555
971341AH1-150 GEN
Solar/Wind Harmer
3.998
971343AH1-151 GEN
Solar/Wind Harmer
3.998
944201AF1-088_MTX
Adder
163.563
957141AF2-008_MTX
Adder
81.782
NYPJM->LTFIMP_NY
CLTF
6.276
LGEELTFEXP_LGEE->PJM
CLTF
9.844
WECLTFEXP_WEC->PJM
CLTF
5.002
AG2-052LTFEXP_AG2-052->PJM
LTF
0.306
AH1-155LTFEXP_AH1-155->PJM
LTF
0.459
CPLELTFEXP_CPLE->PJM
CLTF
6.557
CBM West 2LTFEXP_CBM-W2->PJM
CBM
173.156
LAGNLTFEXP_LAGN->PJM
CLTF
24.864
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.24
TVALTFEXP_TVA->PJM
CLTF
12.63
CBM West 1LTFEXP_CBM-W1->PJM
CBM
170.264
CBM South 1LTFEXP_CBM-S1->PJM
CBM
48.581
MECLTFEXP_MEC->PJM
CLTF
21.939
SIGELTFEXP_SIGE->PJM
CLTF
0.729

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7445_05MARYSV 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.05 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6243.53
MW Contribution:40.07
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
3.32
962771AG1-126 GEN
Solar/Wind Harmer
91.898
972203AH1-686 GEN
Adder
4.552
24477305BRIDGE
Adder
0.636
957241AF2-018 GEN
Solar/Wind Harmer
8.055
270399AC1-101 GEN
Solar/Wind Harmer
7.605
270400AC1-102 GEN
Solar/Wind Harmer
7.605
270330AC1-082 GEN2
Solar/Wind Harmer
1.366
270329AC1-082 GEN1
Solar/Wind Harmer
0.805
941621AE2-160 GEN
Adder
5.471
971313AH1-133 GEN
Solar/Wind Harmer
15.802
970281AG2-184 GEN
Solar/Wind Harmer
32.56
972143AH1-644 GEN
Solar/Wind Harmer
15.505
270132AB1-180 C
Adder
0.187
971061AG2-657 GEN
Solar/Wind Harmer
13.568
24734705WLF1G3
Adder
8.349
24734805WLF1G4
Adder
8.349
24734905WLF1G5
Adder
8.349
962211AG1-066 GEN
Solar/Wind Harmer
3.499
966391AG1-508 GEN
Solar/Wind Harmer
4.988
24735105WLF2G1
Adder
8.16
971985AH1-537 GEN
Solar/Wind Harmer
23.222
971981AH1-535 GEN
Solar/Wind Harmer
12.796
24289405MTG1
50/50
12.693
24722005FLATG5
50/50
3.32
24721905FLATG4
50/50
60.871
24318705GVG2
50/50
13.293
970153AG2-106 GEN
Solar/Wind Harmer
40.072
24686205CER G4
Adder
16.091
24686405CER G5
Adder
16.028
270053AF1-130 C
Solar/Wind Harmer
6.738
970913AG2-568 GEN
Solar/Wind Harmer
13.608
960911AF2-382 GEN
Solar/Wind Harmer
12.052
972103AH1-617 GEN
Solar/Wind Harmer
31.009
971461AH1-227 GEN
Solar/Wind Harmer
7.917
971191AH1-055 GEN
Solar/Wind Harmer
33.8
270346AE1-212 GEN
Solar/Wind Harmer
13.484
943031AE2-326 GEN
Solar/Wind Harmer
5.284
971331AH1-145 GEN
Solar/Wind Harmer
12.895
247619Y1-049
Adder
0.586
958121AF2-106 GEN
Solar/Wind Harmer
6.061
957541AF2-048 GEN
Solar/Wind Harmer
2.113
970243AG2-164 GEN
Solar/Wind Harmer
30.166
970519AG2-331 GEN
Solar/Wind Harmer
20.267
970699AG2-449 GEN
Solar/Wind Harmer
13.407
972273AH1-721 GEN
Adder
96.475
270030AE2-140 GEN
Solar/Wind Harmer
23.108
970273AG2-179 GEN
Solar/Wind Harmer
4.447
970093AG2-073 GEN
Solar/Wind Harmer
11.307
966571AG1-526 GEN
Solar/Wind Harmer
25.008
339250AF1-203 GEN
Solar/Wind Harmer
0.677
971155AH1-034 GEN
Solar/Wind Harmer
11.167
962251AG1-071 GEN
Solar/Wind Harmer
6.119
960741AF2-365 GEN
Solar/Wind Harmer
5.543
3429391JKCT 9G
Adder
9.194
972167AH1-666 GEN
Solar/Wind Harmer
8.642
958171AF2-111 GEN
Solar/Wind Harmer
25.894
270291AC1-194 GEN
Solar/Wind Harmer
10.843
25196008MFTGT1
Adder
1.363
970193AG2-126 GEN
Solar/Wind Harmer
14.82
252510AF1-249 C
Solar/Wind Harmer
0.411
270173AC1-122 GEN
Solar/Wind Harmer
1.562
25194608D.CRK4
Adder
1.604
25196608WSDLE5
Adder
8.312
942481AE2-261 GEN
Solar/Wind Harmer
28.829
24728705AND G3
Adder
7.718
24728505AND G1
Adder
3.69
962751AG1-124 GEN
Solar/Wind Harmer
8.642
276621W2-048 GEN
Solar/Wind Harmer
5.949
276838X2-022 GEN2
Solar/Wind Harmer
0.222
274760LEE CO EC;1U
Adder
8.426
274767LEE CO EC;8U
Adder
8.327
972236AH1-702 GEN2
Adder
1.974
274682WAUKEGAN ;7U
Adder
15.992
274729ELWOOD EC;1P
Adder
14.499
237048AF1-022 C
Solar/Wind Helper
0.178
235058AG1-386 C
Solar/Wind Helper
0.421
237043AE2-125 C
Solar/Wind Helper
0.164
254305AE2-115 C
Solar/Wind Helper
0.199
202652Y1-033 WT C
Solar/Wind Helper
0.509
23750701CROSSCHOOL
Solar/Wind Helper
1.078
20089126CSLMN_L13
Solar/Wind Helper
0.533
20089026BF_G21_K23
Solar/Wind Helper
0.422
964991AG1-363 GEN
Solar/Wind Helper
3.317
243186AF1-051 GEN
50/50
14.281
24723005RIVRG1
Adder
37.861
24723105RIVRG2
Adder
37.861
24685805CER G1
Adder
16.07
24685905CER G2
Adder
16.07
944971AF1-162 GEN
Solar/Wind Harmer
12.689
24728205BUCHG1
Adder
7.204
971225AH1-072 GEN
Solar/Wind Harmer
3.087
971227AH1-073 GEN
Solar/Wind Harmer
3.087
270214AC2-123 GEN
Solar/Wind Harmer
3.357
971277AH1-098 GEN
Solar/Wind Harmer
5.729
270583AD2-179 GEN
Solar/Wind Harmer
13.373
960161AF2-307 GEN
Solar/Wind Harmer
7.621
970239AG2-162 GEN
Solar/Wind Harmer
12.849
966021AG1-471 GEN
Solar/Wind Harmer
6.166
339231AF1-038_GEN
Solar/Wind Harmer
2.069
971485AH1-239 GEN
Solar/Wind Harmer
9.113
970879AG2-548 GEN
Solar/Wind Harmer
6.915
971073AG2-665 GEN
Solar/Wind Harmer
6.915
971073AG2-665 GEN
Solar/Wind Harmer
4.825
942891AE2-308 GEN
Solar/Wind Harmer
11.21
971081AG2-670 GEN
Solar/Wind Harmer
8.401
339236AF1-050_GEN
Solar/Wind Harmer
2.029
339255AE2-071 GEN
Solar/Wind Harmer
1.185
964781AG1-341 GEN
Solar/Wind Harmer
11.836
970653AG2-424 GEN
Solar/Wind Harmer
5.35
970653AG2-424 GEN
Solar/Wind Harmer
1.934
964571AG1-320 GEN
Solar/Wind Harmer
9.018
972043AH1-570 GEN
Solar/Wind Harmer
2.743
972045AH1-571 GEN
Solar/Wind Harmer
2.195
971125AH1-004 GEN
Solar/Wind Harmer
4.377
970107AG2-081 GEN
Solar/Wind Harmer
3.283
270186AC1-089 GEN
Solar/Wind Harmer
6.681
339221AD2-048_GEN
Solar/Wind Harmer
1.68
970235AG2-159 GEN
Solar/Wind Harmer
4.336
970235AG2-159 GEN
Solar/Wind Harmer
2.647
270444AC2-157 GEN1
Solar/Wind Harmer
5.954
962581AG1-107 GEN
Solar/Wind Harmer
5.324
961491AF2-440 GEN
Solar/Wind Harmer
2.213
252509AD1-136 GEN
Solar/Wind Harmer
0.262
945391AF1-204 GEN
Solar/Wind Harmer
13.769
252519AF1-045_GEN
Solar/Wind Harmer
5.968
252516AE2-318_GEN
Solar/Wind Harmer
4.552
25183208HLCRTG
Solar/Wind Harmer
5.931
25194408D.CRK1
Adder
7.379
25194508D.CRK3
Adder
1.38
276916AD2-100_GEN
Solar/Wind Harmer
20.308
276911AD2-131_GEN
Solar/Wind Harmer
4.104
957381AF2-032 GEN
Solar/Wind Harmer
0.403
970241AG2-163 GEN
Solar/Wind Harmer
23.985
276763AC1-053 GEN1
Solar/Wind Harmer
3.755
276764AC1-053 GEN2
Solar/Wind Harmer
3.755
24728805RICHG1
Adder
3.448
24728905RICHG2
Adder
3.448
972267AH1-718 GEN
Adder
3.785
274764LEE CO EC;5U
Adder
8.446
274765LEE CO EC;6U
Adder
8.446
274762LEE CO EC;3U
Adder
8.426
274763LEE CO EC;4U
Adder
8.346
274683WAUKEGAN ;8U
Adder
18.761
274683WAUKEGAN ;8U
Adder
15.814
274696ROCKY RD ;4P
Adder
10.143
274695ROCKY RD ;2P
Adder
9.908
274693ROCKY RD ;1P
Adder
9.811
274697ROCKY RD ;3P
Adder
2.692
23652301WDPWR_K20
Solar/Wind Helper
0.133
962101AG1-054 GEN
Solar/Wind Helper
0.594
241967AE2-285_GEN
Solar/Wind Helper
0.583
241801AE1-079 GEN
Solar/Wind Helper
0.227
241985AE1-237 GEN
Solar/Wind Helper
0.227
23585401KL_K28_T16
Solar/Wind Helper
1.167
203955AF1-039 C O1
Solar/Wind Helper
0.335
944781AF1-143 GEN
Solar/Wind Helper
2.213
24289405MTG1
50/50
12.693
24721805FLATG3
50/50
3.32
24721705FLATG2
50/50
60.871
243186AF1-051 GEN
50/50
14.281
24318705GVG2
50/50
13.293
962761AG1-125 GEN
Solar/Wind Harmer
91.898
970149AG2-104 GEN
Solar/Wind Harmer
113.494
970155AG2-107 GEN
Solar/Wind Harmer
40.072
24723205RIVRG3
Adder
37.861
24686105CER G3
Adder
16.176
24686505CER G6
Adder
16.155
971403AH1-188 GEN
Solar/Wind Harmer
25.361
270331AC1-082 GEN3
Solar/Wind Harmer
0.807
970947AG2-589 GEN
Solar/Wind Harmer
3.533
960001AF2-291 GEN
Solar/Wind Harmer
5.186
24728305BUCHG2
Adder
7.204
971687AH1-348 GEN
Solar/Wind Harmer
1.543
971315AH1-136 GEN
Solar/Wind Harmer
3.067
24735205WLF2G2
Adder
8.16
971329AH1-144 GEN
Solar/Wind Harmer
16.634
927014AC1-188 GEN
Solar/Wind Harmer
2.118
270336AE1-100 GEN
Solar/Wind Harmer
2.043
970091AG2-072 GEN
Adder
90.557
970333AG2-219 GEN
Solar/Wind Harmer
36.87
971367AH1-164 GEN
Solar/Wind Harmer
3.994
970273AG2-179 GEN
Solar/Wind Harmer
2.784
971821AH1-427 GEN
Solar/Wind Harmer
11.315
943811AF1-049 GEN
Solar/Wind Harmer
4.273
339241AF1-083 GEN
Solar/Wind Harmer
1.864
964901AG1-354 GEN
Solar/Wind Harmer
16.766
3429241JKCT 3G
Adder
13.209
962241AG1-070 GEN
Solar/Wind Harmer
5.006
971565AH1-281 GEN
Solar/Wind Harmer
2.213
3429421JKCT 10G
Adder
9.194
943111AE2-339 GEN
Solar/Wind Harmer
0.969
339216AC1-074 GEN
Solar/Wind Harmer
1.819
945681AF1-233 GEN
Solar/Wind Harmer
20.401
270445AC2-157 GEN2
Solar/Wind Harmer
5.954
270018AE2-047 C O1
Solar/Wind Harmer
1.277
252507AC2-088 GEN
Solar/Wind Harmer
1.836
25196008MFTGT1
Adder
1.408
25196808ZIMRHP
Adder
76.262
25194608D.CRK4
Adder
1.604
965911AG1-460 GEN
Solar/Wind Harmer
1.345
24728605AND G2
Adder
3.69
963741AG1-226 GEN
Solar/Wind Harmer
43.173
276615X2-022 GEN
Solar/Wind Harmer
1.868
274761LEE CO EC;2U
Adder
8.426
274766LEE CO EC;7U
Adder
8.327
972235AH1-702 GEN1
Adder
2.27
274822ROCKFORD ;11
Adder
17.664
274828WAUKEGAN ;BP
Adder
9.834
274682WAUKEGAN ;7U
Adder
15.992
274745AC1-111 GEN9
Adder
4.954
237046AF1-021 C
Solar/Wind Helper
0.454
254303AC2-168 GEN
Solar/Wind Helper
0.144
241966AE1-183 GEN
Solar/Wind Helper
0.233
238185AF2-356 C
Solar/Wind Helper
1.986
23751201ROTHROCK
Solar/Wind Helper
0.666
235054AD2-180 GEN
Solar/Wind Helper
1.542
23562501BACKB
Solar/Wind Helper
0.81
20089226LOOKOUT
Solar/Wind Helper
0.519
963831AG1-236 GEN
Solar/Wind Harmer
2.691
270069AE2-166 C O1
Solar/Wind Harmer
3.217
965401AG1-405 GEN
Solar/Wind Harmer
6.573
965411AG1-406 GEN
Solar/Wind Harmer
2.95
339211AE2-254 GEN
Solar/Wind Harmer
1.711
970879AG2-548 GEN
Solar/Wind Harmer
4.825
3429211JKCT 2G
Adder
13.038
970455AG2-298 GEN
Solar/Wind Harmer
6.646
972163AH1-664 GEN
Solar/Wind Harmer
10.872
972165AH1-665 GEN
Solar/Wind Harmer
8.697
270367AC2-061_GEN
Solar/Wind Harmer
3.448
339243AC2-075 GEN1
Solar/Wind Harmer
0.493
25196108MFTGT2
Adder
1.552
25196108MFTGT2
Adder
1.441
944221AF1-090 GEN
Solar/Wind Harmer
10.676
252524AE2-267 GEN
Solar/Wind Harmer
1.53
25196408WSDLE3
Adder
8.556
25196308WSDLE2
Adder
8.482
25196208WSDLE1
Adder
8.46
25196708WSDLE6
Adder
8.439
25196508WSDLE4
Adder
8.227
963841AG1-237 GEN
Solar/Wind Harmer
10.394
274823ROCKFORD ;21
Adder
17.536
274746AC1-111 G10
Adder
4.954
274744AC1-111 GEN8
Adder
4.954
274731ELWOOD EC;2P
Adder
14.499
274733ELWOOD EC;3P
Adder
10.298
23750501ELLIOTTS
Solar/Wind Helper
0.613
254304AE2-114 C
Solar/Wind Helper
0.199
241997AF1-093 GEN
Solar/Wind Helper
0.233
241982AE2-343 S C
Solar/Wind Helper
0.203
944201AF1-088_MTX
Adder
123.966
957141AF2-008_MTX
Adder
61.983
NYPJM->LTFIMP_NY
CLTF
4.768
LGEELTFEXP_LGEE->PJM
CLTF
7.621
WECLTFEXP_WEC->PJM
CLTF
3.448
AG2-052LTFEXP_AG2-052->PJM
LTF
0.206
AH1-155LTFEXP_AH1-155->PJM
LTF
0.308
CPLELTFEXP_CPLE->PJM
CLTF
7.658
CBM West 2LTFEXP_CBM-W2->PJM
CBM
139.058
LAGNLTFEXP_LAGN->PJM
CLTF
21.271
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.975
TVALTFEXP_TVA->PJM
CLTF
11.116
CBM West 1LTFEXP_CBM-W1->PJM
CBM
111.704
CBM South 1LTFEXP_CBM-S1->PJM
CBM
41.73
MECLTFEXP_MEC->PJM
CLTF
16.018
SIGELTFEXP_SIGE->PJM
CLTF
0.557

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#17219_05GUERNSEY 765_A_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#17219_05GUERNSEY 765_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.12 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6192.17
MW Contribution:24.08
Bus #Bus NameTypeMW Contribution
24289405MTG1
50/50
11.412
24318705GVG2
50/50
11.681
24722005FLATG5
50/50
2.772
24721905FLATG4
50/50
50.82
24686205CER G4
Adder
15.663
24686405CER G5
Adder
15.601
270053AF1-130 C
Solar/Wind Harmer
6.517
970153AG2-106 GEN
Solar/Wind Harmer
24.083
971191AH1-055 GEN
Solar/Wind Harmer
37.171
957541AF2-048 GEN
Solar/Wind Harmer
2.51
970913AG2-568 GEN
Solar/Wind Harmer
12.681
972103AH1-617 GEN
Solar/Wind Harmer
31.576
960911AF2-382 GEN
Solar/Wind Harmer
11.622
971461AH1-227 GEN
Solar/Wind Harmer
7.904
970243AG2-164 GEN
Solar/Wind Harmer
38.654
970519AG2-331 GEN
Solar/Wind Harmer
25.969
970699AG2-449 GEN
Solar/Wind Harmer
17.18
972167AH1-666 GEN
Solar/Wind Harmer
11.786
958171AF2-111 GEN
Solar/Wind Harmer
36.367
252510AF1-249 C
Solar/Wind Harmer
0.604
25196008MFTGT1
Adder
1.945
25194608D.CRK4
Adder
2.371
25196608WSDLE5
Adder
12.34
3429391JKCT 9G
Adder
11.981
970093AG2-073 GEN
Solar/Wind Harmer
14.372
253316AC1-085 GEN3
Solar/Wind Harmer
12.008
253433AC1-085 GEN1
Solar/Wind Harmer
7.622
946181AF1-283 GEN
Solar/Wind Harmer
18.636
253406AD2-031_GEN
Solar/Wind Harmer
1.826
966571AG1-526 GEN
Solar/Wind Harmer
31.649
270291AC1-194 GEN
Solar/Wind Harmer
15.077
253415AE1-040 GEN
Solar/Wind Harmer
1.598
972173AH1-669 GEN
Solar/Wind Harmer
7.011
270222AC2-111 GEN
Solar/Wind Harmer
11.397
270273AD2-016 GEN
Solar/Wind Harmer
3.717
972273AH1-721 GEN
Adder
115.895
270356AE2-297 GEN
Solar/Wind Harmer
6.354
24728705AND G3
Adder
11.134
24728505AND G1
Adder
5.324
970193AG2-126 GEN
Solar/Wind Harmer
20.711
270437AC2-090 C
Solar/Wind Harmer
7.702
253303V4-073 C
Solar/Wind Harmer
0.16
253370AE2-315 SEC1
Adder
2.761
253371AE2-315 SEC2
Adder
2.611
270346AE1-212 GEN
Solar/Wind Harmer
12.393
970273AG2-179 GEN
Solar/Wind Harmer
5.36
960741AF2-365 GEN
Solar/Wind Harmer
6.85
247642Z2-115 C
Solar/Wind Harmer
0.088
970289AG2-191 GEN
Solar/Wind Harmer
1.05
243186AF1-051 GEN
50/50
12.549
24723005RIVRG1
Adder
36.284
24723105RIVRG2
Adder
36.284
24685805CER G1
Adder
15.642
24685905CER G2
Adder
15.642
944971AF1-162 GEN
Solar/Wind Harmer
12.272
971225AH1-072 GEN
Solar/Wind Harmer
3.081
971227AH1-073 GEN
Solar/Wind Harmer
3.081
24728205BUCHG1
Adder
6.894
970239AG2-162 GEN
Solar/Wind Harmer
16.464
270186AC1-089 GEN
Solar/Wind Harmer
9.145
962581AG1-107 GEN
Solar/Wind Harmer
7.495
961491AF2-440 GEN
Solar/Wind Harmer
3.115
960161AF2-307 GEN
Solar/Wind Harmer
9.531
970879AG2-548 GEN
Solar/Wind Harmer
9.109
971073AG2-665 GEN
Solar/Wind Harmer
9.109
971073AG2-665 GEN
Solar/Wind Harmer
6.355
252509AD1-136 GEN
Solar/Wind Harmer
0.375
339221AD2-048_GEN
Solar/Wind Harmer
2.24
972043AH1-570 GEN
Solar/Wind Harmer
3.637
972045AH1-571 GEN
Solar/Wind Harmer
2.91
25183208HLCRTG
Solar/Wind Harmer
8.794
252519AF1-045_GEN
Solar/Wind Harmer
8.799
252516AE2-318_GEN
Solar/Wind Harmer
6.712
970235AG2-159 GEN
Solar/Wind Harmer
5.797
970235AG2-159 GEN
Solar/Wind Harmer
3.539
971125AH1-004 GEN
Solar/Wind Harmer
5.778
970107AG2-081 GEN
Solar/Wind Harmer
4.333
25194408D.CRK1
Adder
10.905
25194508D.CRK3
Adder
2.039
942891AE2-308 GEN
Solar/Wind Harmer
14.408
253317AC1-085 GEN4
Solar/Wind Harmer
12.008
270444AC2-157 GEN1
Solar/Wind Harmer
7.934
253394AE2-221_GEN
Solar/Wind Harmer
6.433
253398AE2-221_GEN2
Solar/Wind Harmer
6.433
964571AG1-320 GEN
Solar/Wind Harmer
11.509
970653AG2-424 GEN
Solar/Wind Harmer
6.739
970653AG2-424 GEN
Solar/Wind Harmer
2.436
24728805RICHG1
Adder
5.257
24728905RICHG2
Adder
5.257
971081AG2-670 GEN
Solar/Wind Harmer
10.358
945391AF1-204 GEN
Solar/Wind Harmer
19.242
24379505HDWTR1G C
Solar/Wind Harmer
10.908
270209AC1-174_GEN
Solar/Wind Harmer
7.698
926881AC1-175 GEN
Solar/Wind Harmer
7.698
253370AE2-315 SEC1
Adder
2.761
339231AF1-038_GEN
Solar/Wind Harmer
2.495
270383AD1-128 GEN
Solar/Wind Harmer
8.387
339236AF1-050_GEN
Solar/Wind Harmer
2.488
970241AG2-163 GEN
Solar/Wind Harmer
34.243
25322209TAIT E
Adder
13.324
25322209TAIT E
Adder
13.025
25326109MON D
Adder
1.782
247621Y3-024
Adder
0.324
274770LINCOLN ;1U
Adder
11.173
274771LINCOLN ;2U
Adder
11.173
972259AH1-714 GEN
Adder
25.243
972267AH1-718 GEN
Adder
5.508
274696ROCKY RD ;4P
Adder
15.074
274695ROCKY RD ;2P
Adder
14.726
274693ROCKY RD ;1P
Adder
14.581
274697ROCKY RD ;3P
Adder
4
274764LEE CO EC;5U
Adder
12.334
274765LEE CO EC;6U
Adder
12.334
274762LEE CO EC;3U
Adder
12.305
274763LEE CO EC;4U
Adder
12.189
23652301WDPWR_K20
Solar/Wind Helper
0.166
23585401KL_K28_T16
Solar/Wind Helper
1.512
203955AF1-039 C O1
Solar/Wind Helper
0.427
944781AF1-143 GEN
Solar/Wind Helper
2.801
238120AE2-309 GEN
Solar/Wind Helper
0.501
962101AG1-054 GEN
Solar/Wind Helper
0.706
20083426SW_E13_K22
Solar/Wind Helper
0.063
241985AE1-237 GEN
Solar/Wind Helper
0.267
241967AE2-285_GEN
Solar/Wind Helper
0.687
241801AE1-079 GEN
Solar/Wind Helper
0.267
20088926STNY CRK
Solar/Wind Helper
0.916
946071AF1-272 GEN
Solar/Wind Helper
3.012
20084626FORWARD
Solar/Wind Helper
0.397
203940AF1-140 C
Solar/Wind Helper
0.44
20088626ARWF_N39
Solar/Wind Helper
1.344
20303426NA_O38_P22
Solar/Wind Helper
1.102
203853AF1-134 C O1
Solar/Wind Helper
0.526
946381AF1-302 GEN
Solar/Wind Helper
0.243
203952AE2-129 C
Solar/Wind Helper
0.521
203946AE2-131 C
Solar/Wind Helper
0.522
238217AF1-153 C O1
Solar/Wind Helper
0.259
20398826ARMNA MT
Solar/Wind Helper
1.633
209137AF2-361 C
Solar/Wind Helper
1.509
946751AF1-339 GEN
Solar/Wind Helper
0.493
209054AE2-059 GEN
Solar/Wind Helper
0.089
961431AF2-434 GEN
Solar/Wind Helper
0.491
208972BECR K09
Solar/Wind Helper
0.367
209029WAYMART-WD
Solar/Wind Helper
0.923
203979AG1-198 GEN
Solar/Wind Helper
0.292
211065PSPA IPP
Solar/Wind Helper
0.165
211065PSPA IPP
Solar/Wind Helper
0.165
203980AG1-197 GEN
Solar/Wind Helper
0.363
966111AG1-480 GEN
Solar/Wind Helper
0.048
20674128FR_U2-059
Solar/Wind Helper
0.004
964851AG1-348 GEN
Solar/Wind Helper
0.087
20676228FRD_X1-012
Solar/Wind Helper
0.099
207471AF2-354 C
Solar/Wind Helper
0.181
20674928WA_W3-044
Solar/Wind Helper
0.106
217204WCALDSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217081WEATEXAS C
Solar/Wind Helper
0.013
20671828STAW2-080
Solar/Wind Helper
0.028
207442AE1-156 GEN
Solar/Wind Helper
0.346
20676128MHD_W3-029
Solar/Wind Helper
0.102
20673828FLE_V3-070
Solar/Wind Helper
0.096
218440SUMMTASSOC C
Solar/Wind Helper
0.017
20716928W4-060COL
Solar/Wind Helper
0.054
20720628TIN_W1-124
Solar/Wind Helper
0.2
20714928UPF_X1-085
Solar/Wind Helper
0.005
963391AG1-188 GEN
Solar/Wind Helper
0.086
963401AG1-189 GEN
Solar/Wind Helper
0.059
20390526W1-045 C
Solar/Wind Helper
0.351
219615MILLCREEK C
Solar/Wind Helper
0.028
219921AF1-264
Solar/Wind Helper
0.053
203947AF1-006 C
Solar/Wind Helper
0.519
230407AD2-065 C
Solar/Wind Helper
0.042
230433AD2-135 GEN
Solar/Wind Helper
0.018
233939AC1-091 C
Solar/Wind Helper
0.356
233970AC1-092 C
Solar/Wind Helper
0.356
233901CHERRYDALE C
Solar/Wind Helper
0.236
232408W1-005 C
Solar/Wind Helper
0.516
232410W1-006 C
Solar/Wind Helper
0.516
233946AB2-136 GEN
Solar/Wind Helper
0.577
234036AF2-325 C
Solar/Wind Helper
0.043
233987AB2-037 GEN
Solar/Wind Helper
2.379
232424Y1-079 C
Solar/Wind Helper
0.118
233944AB2-135 GEN
Solar/Wind Helper
0.598
233933AB2-153 GEN
Solar/Wind Helper
0.236
235063AE1-101 C2
Solar/Wind Helper
1.441
205916AD1-020 GEN
Solar/Wind Helper
1.685
237002AB1-128_GEN
Solar/Wind Helper
0.382
237001AB1-127_GEN
Solar/Wind Helper
0.382
235020AA1-095 C
Solar/Wind Helper
0.044
23777901MDS_W4-102
Solar/Wind Helper
0.148
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
237034AC2-136 C
Solar/Wind Helper
0.191
238175AF1-290_GEN
Solar/Wind Helper
0.121
237025AB1-124 C
Solar/Wind Helper
0.143
237006AB1-125 GEN
Solar/Wind Helper
0.107
23777801MSM_W1-116
Solar/Wind Helper
0.098
238169AE2-226 GEN1
Solar/Wind Helper
0.546
238170AE2-226 GEN2
Solar/Wind Helper
0.546
970825AG2-519 GEN
Solar/Wind Harmer
8.555
24289405MTG1
50/50
11.412
243186AF1-051 GEN
50/50
12.549
24318705GVG2
50/50
11.681
24721805FLATG3
50/50
2.772
24721705FLATG2
50/50
50.82
24723205RIVRG3
Adder
36.284
24686105CER G3
Adder
15.746
24686505CER G6
Adder
15.725
270331AC1-082 GEN3
Solar/Wind Harmer
0.811
970947AG2-589 GEN
Solar/Wind Harmer
3.567
960001AF2-291 GEN
Solar/Wind Harmer
5.284
971403AH1-188 GEN
Solar/Wind Harmer
24.255
962761AG1-125 GEN
Solar/Wind Harmer
55.23
970149AG2-104 GEN
Solar/Wind Harmer
68.21
970155AG2-107 GEN
Solar/Wind Harmer
24.083
971315AH1-136 GEN
Solar/Wind Harmer
3.227
927014AC1-188 GEN
Solar/Wind Harmer
2.517
971687AH1-348 GEN
Solar/Wind Harmer
1.543
24728305BUCHG2
Adder
6.894
970333AG2-219 GEN
Solar/Wind Harmer
47.244
970091AG2-072 GEN
Adder
114.655
945681AF1-233 GEN
Solar/Wind Harmer
27.78
252507AC2-088 GEN
Solar/Wind Harmer
2.628
25196808ZIMRHP
Adder
110.178
339216AC1-074 GEN
Solar/Wind Harmer
2.436
25196008MFTGT1
Adder
2.009
943111AE2-339 GEN
Solar/Wind Harmer
1.275
25194608D.CRK4
Adder
2.371
3429241JKCT 3G
Adder
17.06
3429421JKCT 10G
Adder
11.981
253432AC1-085 GEN2
Solar/Wind Harmer
0.384
946171AF1-282 GEN
Solar/Wind Harmer
14.335
270263AC1-001 GEN
Solar/Wind Harmer
1.49
270445AC2-157 GEN2
Solar/Wind Harmer
7.934
971565AH1-281 GEN
Solar/Wind Harmer
2.835
971821AH1-427 GEN
Solar/Wind Harmer
14.167
24735205WLF2G2
Adder
8.161
24728605AND G2
Adder
5.324
339241AF1-083 GEN
Solar/Wind Harmer
2.303
942081AE2-220 GEN
Solar/Wind Harmer
8.819
270239V3-007_GEN1
Solar/Wind Harmer
2.374
253370AE2-315 SEC1
Adder
2.761
253371AE2-315 SEC2
Adder
2.611
970273AG2-179 GEN
Solar/Wind Harmer
3.356
276903AD2-071 C
Solar/Wind Harmer
13.713
963741AG1-226 GEN
Solar/Wind Harmer
61.637
970291AG2-192 GEN
Solar/Wind Harmer
1.778
270005AE1-210 C O1
Solar/Wind Harmer
7.473
965031AG1-367 GEN
Solar/Wind Harmer
13.674
270032AE2-172
Solar/Wind Harmer
6.358
25326309TAIT D
Adder
1.497
964901AG1-354 GEN
Solar/Wind Harmer
20.475
960071AF2-298 GEN
Solar/Wind Harmer
6.807
274773LINCOLN ;4U
Adder
11.173
274774LINCOLN ;5U
Adder
11.173
274745AC1-111 GEN9
Adder
7.394
274761LEE CO EC;2U
Adder
12.305
274766LEE CO EC;7U
Adder
12.16
237046AF1-021 C
Solar/Wind Helper
0.57
238185AF2-356 C
Solar/Wind Helper
2.581
23751201ROTHROCK
Solar/Wind Helper
0.868
235054AD2-180 GEN
Solar/Wind Helper
2.007
23562501BACKB
Solar/Wind Helper
1.057
238117U2-030
Solar/Wind Helper
0.339
235531U2-073 GEN
Solar/Wind Helper
3.19
20089226LOOKOUT
Solar/Wind Helper
0.657
254303AC2-168 GEN
Solar/Wind Helper
0.171
241966AE1-183 GEN
Solar/Wind Helper
0.277
23751101LEADS_P59
Solar/Wind Helper
1.464
20088826HIGHLAND
Solar/Wind Helper
0.998
20094526CT_V3-030
Solar/Wind Helper
0.523
964201AG1-281 GEN
Solar/Wind Helper
0.537
238108AE1-109 GEN1
Solar/Wind Helper
0.101
964391AG1-301 GEN
Solar/Wind Helper
0.522
203954AE2-126 C
Solar/Wind Helper
0.514
238206AE2-263_GEN
Solar/Wind Helper
0.997
959471AF2-238 GEN
Solar/Wind Helper
0.51
203860AG1-193 C
Solar/Wind Helper
0.25
209067AE2-060 GEN
Solar/Wind Helper
0.09
946691AF1-333 GEN
Solar/Wind Helper
0.493
946741AF1-338 GEN
Solar/Wind Helper
0.493
961421AF2-433 GEN
Solar/Wind Helper
0.491
957921AF2-086 GEN
Solar/Wind Helper
0.486
961331AF2-424 GEN
Solar/Wind Helper
0.491
209027LOR2_Q27
Solar/Wind Helper
1.148
963071AG1-156 GEN
Solar/Wind Helper
1.601
963161AG1-165 GEN
Solar/Wind Helper
0.489
316095T157 G97
Solar/Wind Helper
1.137
23583801GRNGAP
Solar/Wind Helper
4.22
961971AG1-040 GEN
Solar/Wind Helper
0.485
203835AF1-098 GEN
Solar/Wind Helper
1.929
20674628WNG_W3-110
Solar/Wind Helper
0.096
207510AF2-138 C
Solar/Wind Helper
0.087
20676728BRNX1-095
Solar/Wind Helper
0.032
217169METRODIV C
Solar/Wind Helper
0.004
217211CAMDEN ST C
Solar/Wind Helper
0.005
20673728F2S_V4-070
Solar/Wind Helper
0.032
219249CENTRALDIV C
Solar/Wind Helper
0.011
219908AB1-139 C
Solar/Wind Helper
0.078
219919AE1-041 FULL
Solar/Wind Helper
0.004
219612MATRIX C
Solar/Wind Helper
0.025
218438BLK ROCK C
Solar/Wind Helper
0.029
20720528MAN_W1-024
Solar/Wind Helper
0.03
20714528FRN_Y2-051
Solar/Wind Helper
0.06
219276PARKLANDSO C
Solar/Wind Helper
0.094
20720828JCB_W4-025
Solar/Wind Helper
0.066
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.06
959561AF2-247 GEN
Solar/Wind Helper
0.022
219348LDSOLAR C
Solar/Wind Helper
0.119
219906AC1-017 C
Solar/Wind Helper
0.043
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219291REEVESSOUT C
Solar/Wind Helper
0.012
219912AD2-042 GEN
Solar/Wind Helper
0.155
219766PARADISE C
Solar/Wind Helper
0.057
219623KINSLEYBEA C
Solar/Wind Helper
0.002
228729W2-030 C
Solar/Wind Helper
0.114
230415AB2-049 C
Solar/Wind Helper
0.031
230430AE1-229_GEN
Solar/Wind Helper
3.487
233971AC1-093 C
Solar/Wind Helper
0.364
233952AC2-187 GEN
Solar/Wind Helper
0.236
233994AC2-023 GEN
Solar/Wind Helper
0.977
233996TM1833_GEN
Solar/Wind Helper
0.266
233997TMININ_4.2
Solar/Wind Helper
0.266
232406W1-004 FULL
Solar/Wind Helper
0.516
233940AF2-379 C
Solar/Wind Helper
0.063
234015AF2-250 C
Solar/Wind Helper
0.039
233982AB2-133 GEN
Solar/Wind Helper
0.363
233918AB1-142 GEN
Solar/Wind Helper
0.51
235067AD1-061 GEN
Solar/Wind Helper
0.427
205917AD1-020 ES
Solar/Wind Helper
0.362
238221AF1-254 C O1
Solar/Wind Helper
0.232
237030AB1-096 C
Solar/Wind Helper
0.062
223402AF1-300 C
Solar/Wind Helper
0.332
970825AG2-519 GEN
Solar/Wind Harmer
1.909
24721605FLATG1
50/50
2.772
972203AH1-686 GEN
Adder
4.457
270330AC1-082 GEN2
Solar/Wind Harmer
1.373
270329AC1-082 GEN1
Solar/Wind Harmer
0.808
957241AF2-018 GEN
Solar/Wind Harmer
7.79
270399AC1-101 GEN
Solar/Wind Harmer
7.37
270400AC1-102 GEN
Solar/Wind Harmer
7.37
962771AG1-126 GEN
Solar/Wind Harmer
55.23
24477305BRIDGE
Adder
0.593
970281AG2-184 GEN
Solar/Wind Harmer
33.155
972143AH1-644 GEN
Solar/Wind Harmer
15.788
971985AH1-537 GEN
Solar/Wind Harmer
28.159
941621AE2-160 GEN
Adder
5.103
962211AG1-066 GEN
Solar/Wind Harmer
3.699
971313AH1-133 GEN
Solar/Wind Harmer
15.015
270367AC2-061_GEN
Solar/Wind Harmer
4.764
970879AG2-548 GEN
Solar/Wind Harmer
6.355
972163AH1-664 GEN
Solar/Wind Harmer
14.744
970291AG2-192 GEN
Solar/Wind Harmer
0.954
958821AF2-173 GEN
Solar/Wind Harmer
19.143
270004AE1-209 GEN
Solar/Wind Harmer
7.473
274772LINCOLN ;3U
Adder
11.173
274760LEE CO EC;1U
Adder
12.305
274767LEE CO EC;8U
Adder
12.16
274729ELWOOD EC;1P
Adder
21.74
237048AF1-022 C
Solar/Wind Helper
0.225
237043AE2-125 C
Solar/Wind Helper
0.205
235058AG1-386 C
Solar/Wind Helper
0.508
964991AG1-363 GEN
Solar/Wind Helper
4.361
23750701CROSSCHOOL
Solar/Wind Helper
1.41
238118U2-030_1
Solar/Wind Helper
0.339
202652Y1-033 WT C
Solar/Wind Helper
0.647
20089126CSLMN_L13
Solar/Wind Helper
0.675
20089026BF_G21_K23
Solar/Wind Helper
0.534
238127S14_GEN_2
Solar/Wind Helper
0.8
254305AE2-115 C
Solar/Wind Helper
0.235
203818AF1-086 GEN
Solar/Wind Helper
1.862
203854AF2-039 C
Solar/Wind Helper
0.349
20334926Z1-069 C
Solar/Wind Helper
1.47
238202AE2-262_GEN
Solar/Wind Helper
1.048
941421AE2-139 GEN
Solar/Wind Helper
2.537
959441AF2-235 GEN
Solar/Wind Helper
0.252
200917MEHOOPANY_G
Solar/Wind Helper
2.394
209071AE2-133 GEN
Solar/Wind Helper
0.089
946731AF1-337 GEN
Solar/Wind Helper
0.493
212507AE2-042_GEN
Solar/Wind Helper
1.746
961341AF2-425 GEN
Solar/Wind Helper
0.491
212266LOR1
Solar/Wind Helper
0.053
961301AF2-421 GEN
Solar/Wind Helper
0.489
963151AG1-164 GEN
Solar/Wind Helper
0.489
316097T157 G90
Solar/Wind Helper
1.137
203830AF1-094 GEN
Solar/Wind Helper
0.488
20671928W4-073
Solar/Wind Helper
0.097
207518AF1-320_GEN
Solar/Wind Helper
1.692
207437AD2-070 GEN
Solar/Wind Helper
0.148
20675828AU_W4-064
Solar/Wind Helper
0.032
207439AE1-081 C O1
Solar/Wind Helper
0.02
20674328GAR_V4-001
Solar/Wind Helper
0.024
217208PARK ELE C
Solar/Wind Helper
0.005
217209CENTRL HS C
Solar/Wind Helper
0.009
20676428JCR_X2-075
Solar/Wind Helper
0.072
207528AF2-192 GEN
Solar/Wind Helper
0.081
20673628F1S_V4-069
Solar/Wind Helper
0.032
20675428EAM_W2-061
Solar/Wind Helper
0.017
962511AG1-100 GEN
Solar/Wind Helper
0.481
217213AMBOY SO C
Solar/Wind Helper
0.03
218428ETC SOLAR C
Solar/Wind Helper
0.005
205941AD2-115 GEN
Solar/Wind Helper
0.524
20742028HF_AC1-207
Solar/Wind Helper
0.148
20715228NPK_W1-113
Solar/Wind Helper
0.082
207454AA2-184 E
Solar/Wind Helper
0.327
219680HOPEWELLV C1
Solar/Wind Helper
0.003
963711AG1-223 GEN
Solar/Wind Helper
0.067
20714828MDF_W3-079
Solar/Wind Helper
0.137
207445AB1-138_GEN
Solar/Wind Helper
0.109
20720728JCB_W1-129
Solar/Wind Helper
0.06
219304NAMERICA C
Solar/Wind Helper
0.137
219686LUMSOLAR_N C
Solar/Wind Helper
0.041
219907AC1-030 C
Solar/Wind Helper
0.035
218660EHAMPSOLAR C
Solar/Wind Helper
0.034
219904AC1-010 C
Solar/Wind Helper
0.063
219258KINSLEYDEP C
Solar/Wind Helper
0.079
228728W1-130C
Solar/Wind Helper
0.056
230434AG1-499 GEN
Solar/Wind Helper
0.238
230511AF1-262
Solar/Wind Helper
0.015
233972AC1-094 C
Solar/Wind Helper
0.308
233954AC2-188 GEN
Solar/Wind Helper
0.236
233950AC2-186 GEN
Solar/Wind Helper
0.118
233998TM1NIN_3.36
Solar/Wind Helper
0.266
232404W1-003 C
Solar/Wind Helper
0.516
232428Y3-058 C
Solar/Wind Helper
0.344
232434Z2-077 GEN
Solar/Wind Helper
0.129
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
232422X3-066 FULL
Solar/Wind Helper
0.116
233930AB2-032 GEN
Solar/Wind Helper
0.387
233915AB1-141 GEN
Solar/Wind Helper
0.51
966131AG1-482 GEN
Solar/Wind Helper
0.077
235062AE1-101 C1
Solar/Wind Helper
1.441
237038AE2-054 C
Solar/Wind Helper
0.234
237080AD1-060 GEN
Solar/Wind Helper
0.292
23779801AA1-109
Solar/Wind Helper
0.165
223401AF1-299 GEN
Solar/Wind Helper
0.332
972165AH1-665 GEN
Solar/Wind Harmer
11.796
339243AC2-075 GEN1
Solar/Wind Harmer
0.66
25196108MFTGT2
Adder
2.214
25196108MFTGT2
Adder
2.056
3429211JKCT 2G
Adder
16.839
252524AE2-267 GEN
Solar/Wind Harmer
2.271
25196408WSDLE3
Adder
12.703
25196308WSDLE2
Adder
12.592
25196208WSDLE1
Adder
12.561
25196708WSDLE6
Adder
12.529
25196508WSDLE4
Adder
12.214
24734705WLF1G3
Adder
8.278
24734805WLF1G4
Adder
8.278
24734905WLF1G5
Adder
8.278
270340AC2-060 GEN
Solar/Wind Harmer
4.33
270132AB1-180 C
Adder
0.172
339211AE2-254 GEN
Solar/Wind Harmer
2.15
24735105WLF2G1
Adder
8.161
970455AG2-298 GEN
Solar/Wind Harmer
8.463
965401AG1-405 GEN
Solar/Wind Harmer
7.994
965411AG1-406 GEN
Solar/Wind Harmer
3.588
944031AF1-071 GEN
Solar/Wind Harmer
1.405
270269AC2-059
Solar/Wind Harmer
12.998
971061AG2-657 GEN
Solar/Wind Harmer
12.476
270240V3-007_GEN2
Solar/Wind Harmer
8.534
253372AE2-315 SEC3
Adder
2.611
253372AE2-315 SEC3
Adder
2.611
25306009OHH W.
Adder
3.967
24725505WLD G2 C
Solar/Wind Harmer
5.459
24699105WLD G1 C
Solar/Wind Harmer
5.394
253349AC2-067 GEN
Solar/Wind Harmer
6.826
253400AC2-068 GEN
Solar/Wind Harmer
2.745
965461AG1-414 GEN
Solar/Wind Harmer
3.101
970289AG2-191 GEN
Solar/Wind Harmer
2.598
270594AE1-207 GEN
Solar/Wind Harmer
20.092
963841AG1-237 GEN
Solar/Wind Harmer
14.936
24729505KEY G4
Adder
8.677
274775LINCOLN ;6U
Adder
11.173
274776LINCOLN ;7U
Adder
11.173
274777LINCOLN ;8U
Adder
11.173
274746AC1-111 G10
Adder
7.394
274744AC1-111 GEN8
Adder
7.394
274731ELWOOD EC;2P
Adder
21.74
274733ELWOOD EC;3P
Adder
13.586
23750501ELLIOTTS
Solar/Wind Helper
0.779
238126S14_GEN_1
Solar/Wind Helper
0.8
254304AE2-114 C
Solar/Wind Helper
0.235
241997AF1-093 GEN
Solar/Wind Helper
0.277
241982AE2-343 S C
Solar/Wind Helper
0.24
20092526R32
Solar/Wind Helper
1.294
203961AE2-224 GEN
Solar/Wind Helper
2.672
20091526CHSTN_FL
Solar/Wind Helper
0.646
238109AE1-109 GEN2
Solar/Wind Helper
0.101
238110AE1-109 GEN3
Solar/Wind Helper
0.101
20090526Q36
Solar/Wind Helper
1.152
203993AD2-133_GEN1
Solar/Wind Helper
1.152
941231AE2-117 GEN
Solar/Wind Helper
0.523
203846AF2-130 C
Solar/Wind Helper
0.491
203855AF2-088 C
Solar/Wind Helper
0.168
203804AE2-113_GEN
Solar/Wind Helper
1.898
959431AF2-234 GEN
Solar/Wind Helper
0.986
964051AG1-259 GEN
Solar/Wind Helper
0.074
964061AG1-260 GEN
Solar/Wind Helper
0.074
959421AF2-233 GEN
Solar/Wind Helper
0.493
961261AF2-417 GEN
Solar/Wind Helper
0.488
209116AE2-175 GEN
Solar/Wind Helper
1.938
20675128HRM_W1-127
Solar/Wind Helper
0.032
207408W3-077 C
Solar/Wind Helper
0.09
20675728RH_W2-091
Solar/Wind Helper
0.147
207484AF2-139 C O1
Solar/Wind Helper
0.09
203975AE1-071-GEN
Solar/Wind Helper
2.635
20674828DL_W4-046
Solar/Wind Helper
0.008
20675928HOL_W4-097
Solar/Wind Helper
0.054
238208AF1-136 C
Solar/Wind Helper
0.189
20676328BVR_Y1-020
Solar/Wind Helper
0.029
207530AG1-191 GEN
Solar/Wind Helper
0.071
966261AG1-495 GEN
Solar/Wind Helper
0.087
218524CNTRALGAS1 C
Solar/Wind Helper
0.17
218526CNTRALGAS2 C
Solar/Wind Helper
0.17
20675528CPH_W2-050
Solar/Wind Helper
0.092
219620RIDERU C
Solar/Wind Helper
0.001
207459AE1-142 C O1
Solar/Wind Helper
0.304
20715728PEM_W1-119
Solar/Wind Helper
0.1
20715828PEM_W1-120
Solar/Wind Helper
0.1
214067T20SOLAR
Solar/Wind Helper
0.012
959381AF2-229 GEN
Solar/Wind Helper
0.359
219607WPEMNERT C
Solar/Wind Helper
0.083
219688LUMSOLAR_S C
Solar/Wind Helper
0.041
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.119
227927V4-067C
Solar/Wind Helper
0.011
228754AB1-001 C
Solar/Wind Helper
0.027
964001AG1-254 GEN
Solar/Wind Helper
0.988
234033AF1-007_GEN
Solar/Wind Helper
7.137
233923SMA
Solar/Wind Helper
0.974
233990AG1-397 GEN
Solar/Wind Helper
0.031
232432Z2-076 GEN
Solar/Wind Helper
0.068
237085AD2-009_GEN
Solar/Wind Helper
1.427
205932AD2-116_GEN
Solar/Wind Helper
0.516
205956AE1-196_GEN
Solar/Wind Helper
0.516
205943AE1-185 GEN
Solar/Wind Helper
0.515
232436AB1-176 C
Solar/Wind Helper
0.045
233935AB2-179 C
Solar/Wind Helper
1.288
960921AF2-383 GEN
Solar/Wind Helper
0.183
944201AF1-088_MTX
Adder
165.192
957141AF2-008_MTX
Adder
82.596
NYPJM->LTFIMP_NY
CLTF
6.186
LGEELTFEXP_LGEE->PJM
CLTF
9.94
WECLTFEXP_WEC->PJM
CLTF
5.055
AG2-052LTFEXP_AG2-052->PJM
LTF
0.309
AH1-155LTFEXP_AH1-155->PJM
LTF
0.464
CPLELTFEXP_CPLE->PJM
CLTF
6.71
CBM West 2LTFEXP_CBM-W2->PJM
CBM
175.047
LAGNLTFEXP_LAGN->PJM
CLTF
25.149
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.665
TVALTFEXP_TVA->PJM
CLTF
12.772
CBM West 1LTFEXP_CBM-W1->PJM
CBM
172.314
CBM South 1LTFEXP_CBM-S1->PJM
CBM
49.115
MECLTFEXP_MEC->PJM
CLTF
22.175
SIGELTFEXP_SIGE->PJM
CLTF
0.736

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.86 %
Rating:4558.0 MVA
Rating Type:A
MVA to Mitigate:4961.85
MW Contribution:17.54
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
2.473
972203AH1-686 GEN
Adder
3.978
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
957241AF2-018 GEN
Solar/Wind Harmer
-0.002
24477305BRIDGE
Adder
0.546
270399AC1-101 GEN
Solar/Wind Harmer
3.444
270400AC1-102 GEN
Solar/Wind Harmer
3.444
941621AE2-160 GEN
Adder
4.703
970281AG2-184 GEN
Solar/Wind Harmer
20.149
972143AH1-644 GEN
Solar/Wind Harmer
10.394
971313AH1-133 GEN
Solar/Wind Harmer
9.492
270132AB1-180 C
Adder
0.159
971061AG2-657 GEN
Solar/Wind Harmer
5.654
24734705WLF1G3
Adder
7.306
24734805WLF1G4
Adder
7.306
24734905WLF1G5
Adder
7.306
971985AH1-537 GEN
Solar/Wind Harmer
2.617
24735105WLF2G1
Adder
7.162
966391AG1-508 GEN
Solar/Wind Harmer
1.328
970879AG2-548 GEN
Solar/Wind Harmer
7.21
971981AH1-535 GEN
Solar/Wind Harmer
5.272
270367AC2-061_GEN
Solar/Wind Harmer
0.006
972163AH1-664 GEN
Solar/Wind Harmer
8.62
972165AH1-665 GEN
Solar/Wind Harmer
6.904
3429211JKCT 2G
Adder
12.898
965401AG1-405 GEN
Solar/Wind Harmer
4.386
965411AG1-406 GEN
Solar/Wind Harmer
2.821
339211AE2-254 GEN
Solar/Wind Harmer
0.003
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
970455AG2-298 GEN
Solar/Wind Harmer
5.018
25196108MFTGT2
Adder
1.614
25196108MFTGT2
Adder
1.499
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
9.147
25196308WSDLE2
Adder
9.067
25196208WSDLE1
Adder
9.045
25196708WSDLE6
Adder
9.022
25196508WSDLE4
Adder
8.795
962771AG1-126 GEN
Solar/Wind Harmer
27.465
270340AC2-060 GEN
Solar/Wind Harmer
0.008
24289405MTG1
50/50
10.907
24318705GVG2
50/50
10.872
24722005FLATG5
50/50
2.473
24721905FLATG4
50/50
45.331
24686205CER G4
Adder
14.065
24686405CER G5
Adder
14.009
270053AF1-130 C
Solar/Wind Harmer
2.49
970913AG2-568 GEN
Solar/Wind Harmer
8.136
971191AH1-055 GEN
Solar/Wind Harmer
25.624
960911AF2-382 GEN
Solar/Wind Harmer
7.284
972103AH1-617 GEN
Solar/Wind Harmer
19.189
971461AH1-227 GEN
Solar/Wind Harmer
4.855
270346AE1-212 GEN
Solar/Wind Harmer
7.86
943031AE2-326 GEN
Solar/Wind Harmer
4.498
971331AH1-145 GEN
Solar/Wind Harmer
10.953
247619Y1-049
Adder
0.497
958121AF2-106 GEN
Solar/Wind Harmer
0.001
970243AG2-164 GEN
Solar/Wind Harmer
4.588
970519AG2-331 GEN
Solar/Wind Harmer
20.392
970699AG2-449 GEN
Solar/Wind Harmer
1.961
970093AG2-073 GEN
Solar/Wind Harmer
7.734
972167AH1-666 GEN
Solar/Wind Harmer
6.174
972273AH1-721 GEN
Adder
91.659
966571AG1-526 GEN
Solar/Wind Harmer
17.032
3429391JKCT 9G
Adder
9.139
970273AG2-179 GEN
Solar/Wind Harmer
4.533
270291AC1-194 GEN
Solar/Wind Harmer
5.957
958171AF2-111 GEN
Solar/Wind Harmer
18.792
339250AF1-203 GEN
Solar/Wind Harmer
0.001
960741AF2-365 GEN
Solar/Wind Harmer
3.705
971155AH1-034 GEN
Solar/Wind Harmer
8.639
962251AG1-071 GEN
Solar/Wind Harmer
4.615
25196008MFTGT1
Adder
1.418
252510AF1-249 C
Solar/Wind Harmer
0.056
25194608D.CRK4
Adder
1.71
25196608WSDLE5
Adder
8.886
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.211
970153AG2-106 GEN
Solar/Wind Harmer
17.538
253406AD2-031_GEN
Solar/Wind Harmer
0.522
970193AG2-126 GEN
Solar/Wind Harmer
10.289
24728705AND G3
Adder
7.865
24728505AND G1
Adder
3.761
270356AE2-297 GEN
Solar/Wind Harmer
0.009
270222AC2-111 GEN
Solar/Wind Harmer
3.451
253415AE1-040 GEN
Solar/Wind Harmer
0.003
270030AE2-140 GEN
Solar/Wind Harmer
13.595
942481AE2-261 GEN
Solar/Wind Harmer
19.91
972173AH1-669 GEN
Solar/Wind Harmer
3.31
270437AC2-090 C
Solar/Wind Harmer
0.003
276621W2-048 GEN
Solar/Wind Harmer
0.333
276838X2-022 GEN2
Solar/Wind Harmer
0.372
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
3.038
276668AB2-070 GEN1
Solar/Wind Harmer
0.24
247642Z2-115 C
Solar/Wind Harmer
0.003
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.514
270273AD2-016 GEN
Solar/Wind Harmer
0.675
970289AG2-191 GEN
Solar/Wind Harmer
0.716
970291AG2-192 GEN
Solar/Wind Harmer
0.651
958821AF2-173 GEN
Solar/Wind Harmer
9.079
270004AE1-209 GEN
Solar/Wind Harmer
1.405
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
19.404
959611AF2-252 GEN
Solar/Wind Harmer
2.156
253370AE2-315 SEC1
Adder
1.856
253371AE2-315 SEC2
Adder
1.755
942111AE2-223 GEN
Solar/Wind Harmer
2.091
946031AF1-268 GEN
Solar/Wind Harmer
6.117
970191AG2-125 GEN
Solar/Wind Harmer
1.65
965931AG1-462 GEN
Solar/Wind Harmer
16.291
274878BISHOP HL;2U
Solar/Wind Harmer
0.214
276157O29GEN1
Solar/Wind Harmer
1.026
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
970571AG2-364 GEN
Solar/Wind Harmer
12.648
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
8.432
243186AF1-051 GEN
50/50
11.679
24723005RIVRG1
Adder
32.794
24723105RIVRG2
Adder
32.794
24685805CER G1
Adder
14.046
24685905CER G2
Adder
14.046
944971AF1-162 GEN
Solar/Wind Harmer
11.031
24728205BUCHG1
Adder
6.221
971225AH1-072 GEN
Solar/Wind Harmer
1.893
971227AH1-073 GEN
Solar/Wind Harmer
1.893
971277AH1-098 GEN
Solar/Wind Harmer
3.403
960161AF2-307 GEN
Solar/Wind Harmer
5.337
971073AG2-665 GEN
Solar/Wind Harmer
7.21
270583AD2-179 GEN
Solar/Wind Harmer
7.911
270186AC1-089 GEN
Solar/Wind Harmer
0.005
970239AG2-162 GEN
Solar/Wind Harmer
1.961
962581AG1-107 GEN
Solar/Wind Harmer
0.002
942891AE2-308 GEN
Solar/Wind Harmer
7.714
972043AH1-570 GEN
Solar/Wind Harmer
1.999
972045AH1-571 GEN
Solar/Wind Harmer
1.602
339221AD2-048_GEN
Solar/Wind Harmer
0.005
971125AH1-004 GEN
Solar/Wind Harmer
3.056
970107AG2-081 GEN
Solar/Wind Harmer
2.292
970235AG2-159 GEN
Solar/Wind Harmer
4.628
970235AG2-159 GEN
Solar/Wind Harmer
2.656
966021AG1-471 GEN
Solar/Wind Harmer
4.054
252509AD1-136 GEN
Solar/Wind Harmer
0.038
971485AH1-239 GEN
Solar/Wind Harmer
5.998
971081AG2-670 GEN
Solar/Wind Harmer
5.621
970653AG2-424 GEN
Solar/Wind Harmer
3.613
970653AG2-424 GEN
Solar/Wind Harmer
1.872
964571AG1-320 GEN
Solar/Wind Harmer
6.819
339255AE2-071 GEN
Solar/Wind Harmer
-0.122
964781AG1-341 GEN
Solar/Wind Harmer
7.848
25183208HLCRTG
Solar/Wind Harmer
0.011
252519AF1-045_GEN
Solar/Wind Harmer
6.373
252516AE2-318_GEN
Solar/Wind Harmer
5.653
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
5.336
25194408D.CRK1
Adder
7.868
25194508D.CRK3
Adder
1.471
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
945391AF1-204 GEN
Solar/Wind Harmer
7.288
24728805RICHG1
Adder
3.669
24728905RICHG2
Adder
3.669
970241AG2-163 GEN
Solar/Wind Harmer
3.905
276916AD2-100_GEN
Solar/Wind Harmer
14.016
276911AD2-131_GEN
Solar/Wind Harmer
0.923
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
966841AG1-555 GEN
Solar/Wind Harmer
0.746
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
270383AD1-128 GEN
Solar/Wind Harmer
0.004
971613AH1-306 GEN
Solar/Wind Harmer
3.122
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
970825AG2-519 GEN
Solar/Wind Harmer
7.169
960441AF2-335 GEN
Solar/Wind Harmer
6.468
960611AF2-352 GEN
Solar/Wind Harmer
2.156
253370AE2-315 SEC1
Adder
1.856
970883AG2-550 GEN
Solar/Wind Harmer
6.374
970885AG2-551 GEN
Solar/Wind Harmer
2.125
276782AC1-033 GEN
Solar/Wind Harmer
0.001
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.25
276646AC1-214 GEN2
Solar/Wind Harmer
0.25
270599AE1-208 GEN
Solar/Wind Harmer
5.819
270031AE2-169
Solar/Wind Harmer
3.492
276741O09 GEN1
Solar/Wind Harmer
0.226
276708O09 GEN2
Solar/Wind Harmer
0.226
972267AH1-718 GEN
Adder
3.783
25322209TAIT E
Adder
8.86
25322209TAIT E
Adder
8.661
276603SUBLETTE C
Solar/Wind Harmer
0
274764LEE CO EC;5U
Adder
8.452
274765LEE CO EC;6U
Adder
8.452
274762LEE CO EC;3U
Adder
8.432
274763LEE CO EC;4U
Adder
8.352
938861AE1-114 GEN
Solar/Wind Harmer
3.58
274856ECOGROVE ;U1
Solar/Wind Harmer
0.149
276611AD2-172 GEN
Solar/Wind Harmer
0.002
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
971341AH1-150 GEN
Solar/Wind Harmer
12.585
971343AH1-151 GEN
Solar/Wind Harmer
12.585
247621Y3-024
Adder
0.216
274683WAUKEGAN ;8U
Adder
18.876
274683WAUKEGAN ;8U
Adder
15.912
274696ROCKY RD ;4P
Adder
10.207
274695ROCKY RD ;2P
Adder
9.971
274693ROCKY RD ;1P
Adder
9.873
274697ROCKY RD ;3P
Adder
2.709
23652301WDPWR_K20
Solar/Wind Helper
0.126
23585401KL_K28_T16
Solar/Wind Helper
1.149
970321AG2-212 GEN
Solar/Wind Harmer
1.358
274767LEE CO EC;8U
Adder
8.332
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
1.979
959091AF2-200 GEN
Solar/Wind Harmer
12.585
274682WAUKEGAN ;7U
Adder
16.093
274729ELWOOD EC;1P
Adder
6.64
237048AF1-022 C
Solar/Wind Helper
0.172
237043AE2-125 C
Solar/Wind Helper
0.155
235058AG1-386 C
Solar/Wind Helper
0.383
970513AG2-328 GEN
Solar/Wind Harmer
1.358
970517AG2-330 GEN
Solar/Wind Harmer
8.151
270069AE2-166 C O1
Solar/Wind Harmer
0.005
944221AF1-090 GEN
Solar/Wind Harmer
3.946
963841AG1-237 GEN
Solar/Wind Harmer
2.88
270240V3-007_GEN2
Solar/Wind Harmer
0.002
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.24
276848AB2-070 GEN3
Solar/Wind Harmer
0.239
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
270269AC2-059
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
1.237
270594AE1-207 GEN
Solar/Wind Harmer
7.284
25306009OHH W.
Adder
2.673
970115AG2-085 GEN
Solar/Wind Harmer
2.587
253372AE2-315 SEC3
Adder
1.755
253372AE2-315 SEC3
Adder
1.755
971673AH1-337 GEN
Solar/Wind Harmer
4.2
971029AG2-637 GEN
Solar/Wind Harmer
9.661
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.757
941731AE2-173 GEN
Solar/Wind Harmer
5.363
253349AC2-067 GEN
Solar/Wind Harmer
2.02
253400AC2-068 GEN
Solar/Wind Harmer
0.812
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
946321AF1-296 GEN
Solar/Wind Harmer
3.573
971611AH1-305 GEN
Solar/Wind Harmer
3.799
270543AE2-219 C
Solar/Wind Harmer
0.004
957751AF2-069 GEN
Solar/Wind Harmer
0.21
970169AG2-114 GEN
Solar/Wind Harmer
6.359
971609AH1-304 GEN
Solar/Wind Harmer
1.037
961011AF2-392 GEN
Solar/Wind Harmer
3.717
926823AC1-168 GEN
Solar/Wind Harmer
1.076
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
10.171
945581AF1-223 GEN
Solar/Wind Harmer
0
276612AE2-035 GEN
Solar/Wind Harmer
0.002
274823ROCKFORD ;21
Adder
17.581
971171AH1-044 GEN
Solar/Wind Harmer
12.585
274746AC1-111 G10
Adder
4.992
274744AC1-111 GEN8
Adder
4.992
23750501ELLIOTTS
Solar/Wind Helper
0.594
24289405MTG1
50/50
10.907
243186AF1-051 GEN
50/50
11.679
24318705GVG2
50/50
10.872
24721805FLATG3
50/50
2.473
24721705FLATG2
50/50
45.331
24723205RIVRG3
Adder
32.794
24686105CER G3
Adder
14.139
24686505CER G6
Adder
14.12
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
970947AG2-589 GEN
Solar/Wind Harmer
0.368
971403AH1-188 GEN
Solar/Wind Harmer
15.305
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
24728305BUCHG2
Adder
6.221
971315AH1-136 GEN
Solar/Wind Harmer
1.928
971687AH1-348 GEN
Solar/Wind Harmer
0.947
927014AC1-188 GEN
Solar/Wind Harmer
0.005
24735205WLF2G2
Adder
7.162
971329AH1-144 GEN
Solar/Wind Harmer
6.901
970091AG2-072 GEN
Adder
86.947
970333AG2-219 GEN
Solar/Wind Harmer
5.608
945681AF1-233 GEN
Solar/Wind Harmer
14.563
3429241JKCT 3G
Adder
13.068
971821AH1-427 GEN
Solar/Wind Harmer
7.658
3429421JKCT 10G
Adder
9.139
339216AC1-074 GEN
Solar/Wind Harmer
0.209
970273AG2-179 GEN
Solar/Wind Harmer
2.644
971565AH1-281 GEN
Solar/Wind Harmer
1.508
252507AC2-088 GEN
Solar/Wind Harmer
0.341
964901AG1-354 GEN
Solar/Wind Harmer
11.154
25196808ZIMRHP
Adder
80.408
962241AG1-070 GEN
Solar/Wind Harmer
4.025
25196008MFTGT1
Adder
1.465
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
25194608D.CRK4
Adder
1.71
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.086
962761AG1-125 GEN
Solar/Wind Harmer
27.465
970149AG2-104 GEN
Solar/Wind Harmer
29.663
970155AG2-107 GEN
Solar/Wind Harmer
17.538
270336AE1-100 GEN
Solar/Wind Harmer
0.004
270263AC1-001 GEN
Solar/Wind Harmer
0.699
24728605AND G2
Adder
3.761
970773AG2-487 GEN
Solar/Wind Harmer
1.204
971367AH1-164 GEN
Solar/Wind Harmer
2.344
963741AG1-226 GEN
Solar/Wind Harmer
15.844
965911AG1-460 GEN
Solar/Wind Harmer
1.332
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.849
276615X2-022 GEN
Solar/Wind Harmer
0.069
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.002
963831AG1-236 GEN
Solar/Wind Harmer
2.568
274880W4-005 GEN4
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
7.334
972175AH1-670 GEN
Solar/Wind Harmer
5.394
24791305MDL-5G
Solar/Wind Harmer
0.001
970291AG2-192 GEN
Solar/Wind Harmer
0.846
270032AE2-172
Solar/Wind Harmer
4.336
270005AE1-210 C O1
Solar/Wind Harmer
1.405
965031AG1-367 GEN
Solar/Wind Harmer
6.485
970825AG2-519 GEN
Solar/Wind Harmer
2.296
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
253370AE2-315 SEC1
Adder
1.856
253371AE2-315 SEC2
Adder
1.755
276726Z2-087_GEN
Solar/Wind Harmer
0.002
939741AE1-205 GEN
Solar/Wind Harmer
9.009
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
7.976
274877BISHOP HL;1U
Solar/Wind Harmer
0.214
276158O29GEN2
Solar/Wind Harmer
0.001
960071AF2-298 GEN
Solar/Wind Harmer
3.157
25326309TAIT D
Adder
0.995
970569AG2-363 GEN
Solar/Wind Harmer
18.972
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
8.432
274766LEE CO EC;7U
Adder
8.332
945371AF1-202 GEN
Solar/Wind Harmer
0.001
247536S-71 GEN
Solar/Wind Harmer
0.254
971475AH1-234 GEN
Solar/Wind Harmer
3.061
970819AG2-516 GEN
Solar/Wind Harmer
7.565
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
972235AH1-702 GEN1
Adder
2.276
939401AE1-172 GEN
Solar/Wind Harmer
4.71
274822ROCKFORD ;11
Adder
17.71
957471AF2-041 GEN
Solar/Wind Harmer
18.878
959081AF2-199 GEN
Solar/Wind Harmer
6.293
971067AG2-660 GEN
Solar/Wind Harmer
2.098
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.18
971997AH1-543 GEN
Solar/Wind Harmer
3.301
274828WAUKEGAN ;BP
Adder
9.895
274682WAUKEGAN ;7U
Adder
16.093
274745AC1-111 GEN9
Adder
4.992
237046AF1-021 C
Solar/Wind Helper
0.433
238185AF2-356 C
Solar/Wind Helper
1.954
23751201ROTHROCK
Solar/Wind Helper
0.662
235054AD2-180 GEN
Solar/Wind Helper
1.52
23562501BACKB
Solar/Wind Helper
0.806
970245AG2-165 GEN
Solar/Wind Harmer
1.358
944201AF1-088_MTX
Adder
121.273
957141AF2-008_MTX
Adder
60.637
NYPJM->LTFIMP_NY
CLTF
4.59
LGEELTFEXP_LGEE->PJM
CLTF
7.503
WECLTFEXP_WEC->PJM
CLTF
3.454
AG2-052LTFEXP_AG2-052->PJM
LTF
0.209
AH1-155LTFEXP_AH1-155->PJM
LTF
0.313
CPLELTFEXP_CPLE->PJM
CLTF
6.38
CBM West 2LTFEXP_CBM-W2->PJM
CBM
132.776
LAGNLTFEXP_LAGN->PJM
CLTF
19.803
CBM South 2LTFEXP_CBM-S2->PJM
CBM
23.164
TVALTFEXP_TVA->PJM
CLTF
10.26
CBM West 1LTFEXP_CBM-W1->PJM
CBM
116.498
CBM South 1LTFEXP_CBM-S1->PJM
CBM
38.98
MECLTFEXP_MEC->PJM
CLTF
15.75
SIGELTFEXP_SIGE->PJM
CLTF
0.547

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.47 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5991.02
MW Contribution:16.66
Bus #Bus NameTypeMW Contribution
24289405MTG1
50/50
11.79
243186AF1-051 GEN
50/50
12.748
24318705GVG2
50/50
11.866
24721805FLATG3
50/50
2.714
24721705FLATG2
50/50
49.755
24723205RIVRG3
Adder
37.637
24686105CER G3
Adder
16.224
24686505CER G6
Adder
16.203
971403AH1-188 GEN
Solar/Wind Harmer
26.09
270331AC1-082 GEN3
Solar/Wind Harmer
0.823
970947AG2-589 GEN
Solar/Wind Harmer
3.612
960001AF2-291 GEN
Solar/Wind Harmer
5.329
24728305BUCHG2
Adder
7.763
971687AH1-348 GEN
Solar/Wind Harmer
1.664
971329AH1-144 GEN
Solar/Wind Harmer
19.813
971315AH1-136 GEN
Solar/Wind Harmer
3.299
24289405MTG1
50/50
11.79
24318705GVG2
50/50
11.866
24722005FLATG5
50/50
2.714
24721905FLATG4
50/50
49.755
24686205CER G4
Adder
16.139
24686405CER G5
Adder
16.075
270053AF1-130 C
Solar/Wind Harmer
6.909
970913AG2-568 GEN
Solar/Wind Harmer
14.13
960911AF2-382 GEN
Solar/Wind Harmer
12.931
943031AE2-326 GEN
Solar/Wind Harmer
6.109
971461AH1-227 GEN
Solar/Wind Harmer
8.54
972103AH1-617 GEN
Solar/Wind Harmer
33.271
971331AH1-145 GEN
Solar/Wind Harmer
15.359
247619Y1-049
Adder
0.704
971191AH1-055 GEN
Solar/Wind Harmer
36.143
270346AE1-212 GEN
Solar/Wind Harmer
14.72
958121AF2-106 GEN
Solar/Wind Harmer
7.412
957541AF2-048 GEN
Solar/Wind Harmer
2.373
972273AH1-721 GEN
Adder
111.61
270030AE2-140 GEN
Solar/Wind Harmer
26.875
970093AG2-073 GEN
Solar/Wind Harmer
13.356
970243AG2-164 GEN
Solar/Wind Harmer
34.33
970519AG2-331 GEN
Solar/Wind Harmer
23.064
970699AG2-449 GEN
Solar/Wind Harmer
15.258
966571AG1-526 GEN
Solar/Wind Harmer
29.484
270173AC1-122 GEN
Solar/Wind Harmer
2.108
243186AF1-051 GEN
50/50
12.748
24723005RIVRG1
Adder
37.637
24723105RIVRG2
Adder
37.637
24685805CER G1
Adder
16.117
24685905CER G2
Adder
16.117
944971AF1-162 GEN
Solar/Wind Harmer
13.01
24728205BUCHG1
Adder
7.763
270214AC2-123 GEN
Solar/Wind Harmer
3.882
971225AH1-072 GEN
Solar/Wind Harmer
3.33
971227AH1-073 GEN
Solar/Wind Harmer
3.33
971277AH1-098 GEN
Solar/Wind Harmer
6.642
270583AD2-179 GEN
Solar/Wind Harmer
16.345
960161AF2-307 GEN
Solar/Wind Harmer
8.906
970879AG2-548 GEN
Solar/Wind Harmer
8.293
971073AG2-665 GEN
Solar/Wind Harmer
8.293
971073AG2-665 GEN
Solar/Wind Harmer
5.786
270186AC1-089 GEN
Solar/Wind Harmer
8.143
970239AG2-162 GEN
Solar/Wind Harmer
14.622
942891AE2-308 GEN
Solar/Wind Harmer
13.304
339231AF1-038_GEN
Solar/Wind Harmer
2.394
972043AH1-570 GEN
Solar/Wind Harmer
3.299
972045AH1-571 GEN
Solar/Wind Harmer
2.639
339221AD2-048_GEN
Solar/Wind Harmer
2.024
966021AG1-471 GEN
Solar/Wind Harmer
7.099
971125AH1-004 GEN
Solar/Wind Harmer
5.257
970107AG2-081 GEN
Solar/Wind Harmer
3.942
971485AH1-239 GEN
Solar/Wind Harmer
10.499
962581AG1-107 GEN
Solar/Wind Harmer
6.599
961491AF2-440 GEN
Solar/Wind Harmer
2.742
971081AG2-670 GEN
Solar/Wind Harmer
9.778
970235AG2-159 GEN
Solar/Wind Harmer
5.2
970235AG2-159 GEN
Solar/Wind Harmer
3.174
339236AF1-050_GEN
Solar/Wind Harmer
2.357
970653AG2-424 GEN
Solar/Wind Harmer
6.261
970653AG2-424 GEN
Solar/Wind Harmer
2.263
339255AE2-071 GEN
Solar/Wind Harmer
1.372
964781AG1-341 GEN
Solar/Wind Harmer
13.698
964571AG1-320 GEN
Solar/Wind Harmer
10.586
252509AD1-136 GEN
Solar/Wind Harmer
0.327
25183208HLCRTG
Solar/Wind Harmer
7.582
252519AF1-045_GEN
Solar/Wind Harmer
7.591
252516AE2-318_GEN
Solar/Wind Harmer
5.79
270444AC2-157 GEN1
Solar/Wind Harmer
6.973
25194408D.CRK1
Adder
9.381
25194508D.CRK3
Adder
1.754
253317AC1-085 GEN4
Solar/Wind Harmer
10.168
945391AF1-204 GEN
Solar/Wind Harmer
16.499
253394AE2-221_GEN
Solar/Wind Harmer
5.367
253398AE2-221_GEN2
Solar/Wind Harmer
5.367
316217AC1-145 GEN
Solar/Wind Harmer
2.806
316197AC1-042 GEN
Solar/Wind Harmer
2.127
942671AE2-283 GEN
Solar/Wind Harmer
5.728
24728805RICHG1
Adder
4.412
24728905RICHG2
Adder
4.412
276916AD2-100_GEN
Solar/Wind Harmer
24.323
276911AD2-131_GEN
Solar/Wind Harmer
4.916
253370AE2-315 SEC1
Adder
2.238
972267AH1-718 GEN
Adder
4.6
274764LEE CO EC;5U
Adder
10.276
274765LEE CO EC;6U
Adder
10.276
274762LEE CO EC;3U
Adder
10.252
274763LEE CO EC;4U
Adder
10.155
25322209TAIT E
Adder
10.707
25322209TAIT E
Adder
10.466
274683WAUKEGAN ;8U
Adder
22.951
274683WAUKEGAN ;8U
Adder
19.347
274696ROCKY RD ;4P
Adder
12.409
274695ROCKY RD ;2P
Adder
12.123
274693ROCKY RD ;1P
Adder
12.003
274697ROCKY RD ;3P
Adder
3.293
247621Y3-024
Adder
0.262
23585401KL_K28_T16
Solar/Wind Helper
1.267
23652301WDPWR_K20
Solar/Wind Helper
0.133
238120AE2-309 GEN
Solar/Wind Helper
0.43
203955AF1-039 C O1
Solar/Wind Helper
0.352
24721605FLATG1
50/50
2.714
972203AH1-686 GEN
Adder
4.544
957241AF2-018 GEN
Solar/Wind Harmer
8.259
270399AC1-101 GEN
Solar/Wind Harmer
7.833
270400AC1-102 GEN
Solar/Wind Harmer
7.833
24477305BRIDGE
Adder
0.637
270330AC1-082 GEN2
Solar/Wind Harmer
1.393
270329AC1-082 GEN1
Solar/Wind Harmer
0.821
971313AH1-133 GEN
Solar/Wind Harmer
17.224
941621AE2-160 GEN
Adder
5.66
966391AG1-508 GEN
Solar/Wind Harmer
5.763
970281AG2-184 GEN
Solar/Wind Harmer
34.934
972143AH1-644 GEN
Solar/Wind Harmer
16.635
270132AB1-180 C
Adder
0.198
24734705WLF1G3
Adder
9.185
24734805WLF1G4
Adder
9.185
24734905WLF1G5
Adder
9.185
962211AG1-066 GEN
Solar/Wind Harmer
3.823
24735105WLF2G1
Adder
9.002
971061AG2-657 GEN
Solar/Wind Harmer
14.056
971985AH1-537 GEN
Solar/Wind Harmer
26.201
971981AH1-535 GEN
Solar/Wind Harmer
14.209
270069AE2-166 C O1
Solar/Wind Harmer
3.796
970879AG2-548 GEN
Solar/Wind Harmer
5.786
965401AG1-405 GEN
Solar/Wind Harmer
7.637
965411AG1-406 GEN
Solar/Wind Harmer
3.428
270367AC2-061_GEN
Solar/Wind Harmer
4.222
3429211JKCT 2G
Adder
15.52
339211AE2-254 GEN
Solar/Wind Harmer
2.01
972163AH1-664 GEN
Solar/Wind Harmer
13.228
972165AH1-665 GEN
Solar/Wind Harmer
10.582
339243AC2-075 GEN1
Solar/Wind Harmer
0.595
970455AG2-298 GEN
Solar/Wind Harmer
7.809
25196108MFTGT2
Adder
1.926
25196108MFTGT2
Adder
1.788
252524AE2-267 GEN
Solar/Wind Harmer
1.95
25196408WSDLE3
Adder
10.91
25196308WSDLE2
Adder
10.815
25196208WSDLE1
Adder
10.788
25196708WSDLE6
Adder
10.761
25196508WSDLE4
Adder
10.49
270340AC2-060 GEN
Solar/Wind Harmer
3.615
962771AG1-126 GEN
Solar/Wind Harmer
38.198
944031AF1-071 GEN
Solar/Wind Harmer
1.178
944221AF1-090 GEN
Solar/Wind Harmer
12.754
25306009OHH W.
Adder
3.223
253372AE2-315 SEC3
Adder
2.117
24735205WLF2G2
Adder
9.002
927014AC1-188 GEN
Solar/Wind Harmer
2.379
971367AH1-164 GEN
Solar/Wind Harmer
5.069
270336AE1-100 GEN
Solar/Wind Harmer
2.384
970091AG2-072 GEN
Adder
103.033
970333AG2-219 GEN
Solar/Wind Harmer
41.959
3429241JKCT 3G
Adder
15.723
971821AH1-427 GEN
Solar/Wind Harmer
13.272
3429421JKCT 10G
Adder
10.993
945681AF1-233 GEN
Solar/Wind Harmer
24.878
970273AG2-179 GEN
Solar/Wind Harmer
3.221
943111AE2-339 GEN
Solar/Wind Harmer
1.163
943811AF1-049 GEN
Solar/Wind Harmer
4.961
339216AC1-074 GEN
Solar/Wind Harmer
2.198
339241AF1-083 GEN
Solar/Wind Harmer
2.171
971565AH1-281 GEN
Solar/Wind Harmer
2.604
964901AG1-354 GEN
Solar/Wind Harmer
19.445
962241AG1-070 GEN
Solar/Wind Harmer
5.799
252507AC2-088 GEN
Solar/Wind Harmer
2.292
25196808ZIMRHP
Adder
95.812
25196008MFTGT1
Adder
1.747
270445AC2-157 GEN2
Solar/Wind Harmer
6.973
25194608D.CRK4
Adder
2.039
270018AE2-047 C O1
Solar/Wind Harmer
1.511
253432AC1-085 GEN2
Solar/Wind Harmer
0.325
946171AF1-282 GEN
Solar/Wind Harmer
12.138
270263AC1-001 GEN
Solar/Wind Harmer
1.245
24728605AND G2
Adder
4.525
962761AG1-125 GEN
Solar/Wind Harmer
38.198
970149AG2-104 GEN
Solar/Wind Harmer
47.174
970155AG2-107 GEN
Solar/Wind Harmer
16.656
270197AD1-017 GEN1
Solar/Wind Harmer
1.81
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
6.484
253370AE2-315 SEC1
Adder
2.238
253371AE2-315 SEC2
Adder
2.117
274761LEE CO EC;2U
Adder
10.252
274766LEE CO EC;7U
Adder
10.131
972235AH1-702 GEN1
Adder
2.767
25326309TAIT D
Adder
1.202
274822ROCKFORD ;11
Adder
21.533
274828WAUKEGAN ;BP
Adder
12.03
274682WAUKEGAN ;7U
Adder
19.567
274745AC1-111 GEN9
Adder
6.069
238185AF2-356 C
Solar/Wind Helper
2.176
237046AF1-021 C
Solar/Wind Helper
0.457
235054AD2-180 GEN
Solar/Wind Helper
1.695
238117U2-030
Solar/Wind Helper
0.288
235531U2-073 GEN
Solar/Wind Helper
2.733
23751201ROTHROCK
Solar/Wind Helper
0.71
23562501BACKB
Solar/Wind Helper
0.864
23583801GRNGAP
Solar/Wind Helper
4.088
316095T157 G97
Solar/Wind Helper
1.094
238108AE1-109 GEN1
Solar/Wind Helper
0.088
20089226LOOKOUT
Solar/Wind Helper
0.539
20088826HIGHLAND
Solar/Wind Helper
0.812
963741AG1-226 GEN
Solar/Wind Harmer
22.669
253372AE2-315 SEC3
Adder
2.117
274823ROCKFORD ;21
Adder
21.377
274746AC1-111 G10
Adder
6.069
274744AC1-111 GEN8
Adder
6.069
23750501ELLIOTTS
Solar/Wind Helper
0.635
238126S14_GEN_1
Solar/Wind Helper
0.687
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
20092526R32
Solar/Wind Helper
1.053
3429391JKCT 9G
Adder
10.993
970273AG2-179 GEN
Solar/Wind Harmer
5.144
972167AH1-666 GEN
Solar/Wind Harmer
10.547
962751AG1-124 GEN
Solar/Wind Harmer
11.816
339250AF1-203 GEN
Solar/Wind Harmer
0.784
971155AH1-034 GEN
Solar/Wind Harmer
12.926
960741AF2-365 GEN
Solar/Wind Harmer
6.448
962251AG1-071 GEN
Solar/Wind Harmer
7.087
958171AF2-111 GEN
Solar/Wind Harmer
32.167
270291AC1-194 GEN
Solar/Wind Harmer
13.485
25196008MFTGT1
Adder
1.692
252510AF1-249 C
Solar/Wind Harmer
0.521
25194608D.CRK4
Adder
2.039
25196608WSDLE5
Adder
10.598
253316AC1-085 GEN3
Solar/Wind Harmer
10.168
253433AC1-085 GEN1
Solar/Wind Harmer
6.454
946181AF1-283 GEN
Solar/Wind Harmer
15.78
253406AD2-031_GEN
Solar/Wind Harmer
1.534
970193AG2-126 GEN
Solar/Wind Harmer
17.759
24728705AND G3
Adder
9.464
24728505AND G1
Adder
4.525
970153AG2-106 GEN
Solar/Wind Harmer
16.656
270574AD1-017 GEN2
Solar/Wind Harmer
6.023
3147312GRETNA
Solar/Wind Harmer
-0.014
3146802CHATHAM
Solar/Wind Harmer
-0.013
941801AE2-185 GEN
Solar/Wind Harmer
6.484
270356AE2-297 GEN
Solar/Wind Harmer
5.354
270222AC2-111 GEN
Solar/Wind Harmer
9.554
253415AE1-040 GEN
Solar/Wind Harmer
1.318
253370AE2-315 SEC1
Adder
2.238
253371AE2-315 SEC2
Adder
2.117
274760LEE CO EC;1U
Adder
10.252
274767LEE CO EC;8U
Adder
10.131
972236AH1-702 GEN2
Adder
2.406
274682WAUKEGAN ;7U
Adder
19.567
274729ELWOOD EC;1P
Adder
8.072
237048AF1-022 C
Solar/Wind Helper
0.182
964991AG1-363 GEN
Solar/Wind Helper
3.709
23750701CROSSCHOOL
Solar/Wind Helper
1.197
238118U2-030_1
Solar/Wind Helper
0.288
238127S14_GEN_2
Solar/Wind Helper
0.687
237043AE2-125 C
Solar/Wind Helper
0.163
202652Y1-033 WT C
Solar/Wind Helper
0.534
316097T157 G90
Solar/Wind Helper
1.094
20089126CSLMN_L13
Solar/Wind Helper
0.554
20089026BF_G21_K23
Solar/Wind Helper
0.438
944781AF1-143 GEN
Solar/Wind Helper
2.298
20083426SW_E13_K22
Solar/Wind Helper
0.051
20088926STNY CRK
Solar/Wind Helper
0.747
20084626FORWARD
Solar/Wind Helper
0.323
946071AF1-272 GEN
Solar/Wind Helper
2.428
203940AF1-140 C
Solar/Wind Helper
0.359
970241AG2-163 GEN
Solar/Wind Harmer
12.594
944201AF1-088_MTX
Adder
145.184
957141AF2-008_MTX
Adder
72.592
NYPJM->LTFIMP_NY
CLTF
5.271
LGEELTFEXP_LGEE->PJM
CLTF
8.989
WECLTFEXP_WEC->PJM
CLTF
4.2
AG2-052LTFEXP_AG2-052->PJM
LTF
0.253
AH1-155LTFEXP_AH1-155->PJM
LTF
0.38
CPLELTFEXP_CPLE->PJM
CLTF
7.791
CBM West 2LTFEXP_CBM-W2->PJM
CBM
162.06
LAGNLTFEXP_LAGN->PJM
CLTF
24.37
CBM South 2LTFEXP_CBM-S2->PJM
CBM
29.03
TVALTFEXP_TVA->PJM
CLTF
12.655
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.592
CBM South 1LTFEXP_CBM-S1->PJM
CBM
47.815
MECLTFEXP_MEC->PJM
CLTF
19.173
SIGELTFEXP_SIGE->PJM
CLTF
0.659

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P2-2_#7222_05MALIS 765_1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:107.09 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5914.32
MW Contribution:22.36
Bus #Bus NameTypeMW Contribution
24289405MTG1
50/50
11.329
243186AF1-051 GEN
50/50
12.367
24318705GVG2
50/50
11.512
24721805FLATG3
50/50
2.714
24721705FLATG2
50/50
49.756
24723205RIVRG3
Adder
34.405
24686105CER G3
Adder
14.787
24686505CER G6
Adder
14.768
971403AH1-188 GEN
Solar/Wind Harmer
23.029
270331AC1-082 GEN3
Solar/Wind Harmer
0.743
970947AG2-589 GEN
Solar/Wind Harmer
3.261
960001AF2-291 GEN
Solar/Wind Harmer
4.797
962761AG1-125 GEN
Solar/Wind Harmer
51.279
970149AG2-104 GEN
Solar/Wind Harmer
63.33
970155AG2-107 GEN
Solar/Wind Harmer
22.36
971315AH1-136 GEN
Solar/Wind Harmer
2.924
24728305BUCHG2
Adder
6.555
971687AH1-348 GEN
Solar/Wind Harmer
1.437
24735205WLF2G2
Adder
7.624
927014AC1-188 GEN
Solar/Wind Harmer
2.074
970333AG2-219 GEN
Solar/Wind Harmer
40.872
24289405MTG1
50/50
11.329
24318705GVG2
50/50
11.512
24722005FLATG5
50/50
2.714
24721905FLATG4
50/50
49.756
24686205CER G4
Adder
14.71
24686405CER G5
Adder
14.651
270053AF1-130 C
Solar/Wind Harmer
6.152
970153AG2-106 GEN
Solar/Wind Harmer
22.36
970913AG2-568 GEN
Solar/Wind Harmer
12.168
971191AH1-055 GEN
Solar/Wind Harmer
32.44
960911AF2-382 GEN
Solar/Wind Harmer
11.01
972103AH1-617 GEN
Solar/Wind Harmer
29.136
971461AH1-227 GEN
Solar/Wind Harmer
7.367
270346AE1-212 GEN
Solar/Wind Harmer
11.966
957541AF2-048 GEN
Solar/Wind Harmer
2.069
970243AG2-164 GEN
Solar/Wind Harmer
33.441
970519AG2-331 GEN
Solar/Wind Harmer
22.466
970699AG2-449 GEN
Solar/Wind Harmer
14.862
943031AE2-326 GEN
Solar/Wind Harmer
4.718
971331AH1-145 GEN
Solar/Wind Harmer
11.446
247619Y1-049
Adder
0.52
972273AH1-721 GEN
Adder
100.06
970093AG2-073 GEN
Solar/Wind Harmer
12.017
966571AG1-526 GEN
Solar/Wind Harmer
26.615
970273AG2-179 GEN
Solar/Wind Harmer
4.636
3429391JKCT 9G
Adder
9.882
958121AF2-106 GEN
Solar/Wind Harmer
5.368
960741AF2-365 GEN
Solar/Wind Harmer
5.892
972167AH1-666 GEN
Solar/Wind Harmer
9.416
339250AF1-203 GEN
Solar/Wind Harmer
0.712
971155AH1-034 GEN
Solar/Wind Harmer
11.743
962251AG1-071 GEN
Solar/Wind Harmer
6.45
970193AG2-126 GEN
Solar/Wind Harmer
17.522
25196008MFTGT1
Adder
1.556
24728705AND G3
Adder
9.226
24728505AND G1
Adder
4.411
970513AG2-328 GEN
Solar/Wind Harmer
20.527
970517AG2-330 GEN
Solar/Wind Harmer
18.618
942481AE2-261 GEN
Solar/Wind Harmer
34.305
25194608D.CRK4
Adder
1.851
274760LEE CO EC;1U
Adder
10.448
274767LEE CO EC;8U
Adder
10.325
25196608WSDLE5
Adder
9.621
972236AH1-702 GEN2
Adder
2.459
274682WAUKEGAN ;7U
Adder
20.129
274772LINCOLN ;3U
Adder
9.447
237048AF1-022 C
Solar/Wind Helper
0.191
237043AE2-125 C
Solar/Wind Helper
0.174
235058AG1-386 C
Solar/Wind Helper
0.436
23750701CROSSCHOOL
Solar/Wind Helper
1.181
964991AG1-363 GEN
Solar/Wind Helper
3.632
202652Y1-033 WT C
Solar/Wind Helper
0.547
238118U2-030_1
Solar/Wind Helper
0.284
254305AE2-115 C
Solar/Wind Helper
0.203
20089126CSLMN_L13
Solar/Wind Helper
0.571
20089026BF_G21_K23
Solar/Wind Helper
0.452
238127S14_GEN_2
Solar/Wind Helper
0.669
203818AF1-086 GEN
Solar/Wind Helper
1.58
24755605MDL-5G
Solar/Wind Harmer
1.072
243186AF1-051 GEN
50/50
12.367
24723005RIVRG1
Adder
34.405
24723105RIVRG2
Adder
34.405
24685805CER G1
Adder
14.69
24685905CER G2
Adder
14.69
944971AF1-162 GEN
Solar/Wind Harmer
11.585
24728205BUCHG1
Adder
6.555
971225AH1-072 GEN
Solar/Wind Harmer
2.872
971227AH1-073 GEN
Solar/Wind Harmer
2.872
970239AG2-162 GEN
Solar/Wind Harmer
14.243
270214AC2-123 GEN
Solar/Wind Harmer
2.998
971277AH1-098 GEN
Solar/Wind Harmer
5.115
960161AF2-307 GEN
Solar/Wind Harmer
7.971
270444AC2-157 GEN1
Solar/Wind Harmer
6.775
942891AE2-308 GEN
Solar/Wind Harmer
11.976
970235AG2-159 GEN
Solar/Wind Harmer
4.77
970235AG2-159 GEN
Solar/Wind Harmer
2.912
964571AG1-320 GEN
Solar/Wind Harmer
9.767
970653AG2-424 GEN
Solar/Wind Harmer
5.74
970653AG2-424 GEN
Solar/Wind Harmer
2.075
339231AF1-038_GEN
Solar/Wind Harmer
2.157
270186AC1-089 GEN
Solar/Wind Harmer
7.264
972043AH1-570 GEN
Solar/Wind Harmer
2.97
972045AH1-571 GEN
Solar/Wind Harmer
2.376
339221AD2-048_GEN
Solar/Wind Harmer
1.825
971081AG2-670 GEN
Solar/Wind Harmer
8.888
270583AD2-179 GEN
Solar/Wind Harmer
11.844
971125AH1-004 GEN
Solar/Wind Harmer
4.737
970107AG2-081 GEN
Solar/Wind Harmer
3.553
966021AG1-471 GEN
Solar/Wind Harmer
6.38
339236AF1-050_GEN
Solar/Wind Harmer
2.142
971485AH1-239 GEN
Solar/Wind Harmer
9.446
339255AE2-071 GEN
Solar/Wind Harmer
1.246
964781AG1-341 GEN
Solar/Wind Harmer
12.447
945391AF1-204 GEN
Solar/Wind Harmer
16.279
962581AG1-107 GEN
Solar/Wind Harmer
5.875
961491AF2-440 GEN
Solar/Wind Harmer
2.442
970241AG2-163 GEN
Solar/Wind Harmer
28.958
966841AG1-555 GEN
Solar/Wind Harmer
2.893
252509AD1-136 GEN
Solar/Wind Harmer
0.295
970321AG2-212 GEN
Solar/Wind Harmer
20.527
276916AD2-100_GEN
Solar/Wind Harmer
24.115
276911AD2-131_GEN
Solar/Wind Harmer
4.874
957381AF2-032 GEN
Solar/Wind Harmer
0.48
25194408D.CRK1
Adder
8.517
25194508D.CRK3
Adder
1.592
972267AH1-718 GEN
Adder
4.679
274764LEE CO EC;5U
Adder
10.473
274765LEE CO EC;6U
Adder
10.473
274762LEE CO EC;3U
Adder
10.448
274763LEE CO EC;4U
Adder
10.35
274696ROCKY RD ;4P
Adder
12.769
274695ROCKY RD ;2P
Adder
12.475
274693ROCKY RD ;1P
Adder
12.352
274697ROCKY RD ;3P
Adder
3.389
274683WAUKEGAN ;8U
Adder
23.604
274683WAUKEGAN ;8U
Adder
19.897
274770LINCOLN ;1U
Adder
9.447
274771LINCOLN ;2U
Adder
9.447
23652301WDPWR_K20
Solar/Wind Helper
0.141
23585401KL_K28_T16
Solar/Wind Helper
1.274
203955AF1-039 C O1
Solar/Wind Helper
0.36
962101AG1-054 GEN
Solar/Wind Helper
0.609
241985AE1-237 GEN
Solar/Wind Helper
0.231
241967AE2-285_GEN
Solar/Wind Helper
0.593
241801AE1-079 GEN
Solar/Wind Helper
0.231
944781AF1-143 GEN
Solar/Wind Helper
2.369
238120AE2-309 GEN
Solar/Wind Helper
0.419
20083426SW_E13_K22
Solar/Wind Helper
0.053
946071AF1-272 GEN
Solar/Wind Helper
2.555
20088926STNY CRK
Solar/Wind Helper
0.775
20084626FORWARD
Solar/Wind Helper
0.336
203940AF1-140 C
Solar/Wind Helper
0.373
20088626ARWF_N39
Solar/Wind Helper
1.136
20303426NA_O38_P22
Solar/Wind Helper
0.931
203853AF1-134 C O1
Solar/Wind Helper
0.446
946381AF1-302 GEN
Solar/Wind Helper
0.207
203952AE2-129 C
Solar/Wind Helper
0.442
203946AE2-131 C
Solar/Wind Helper
0.442
24721605FLATG1
50/50
2.714
972203AH1-686 GEN
Adder
4.188
957241AF2-018 GEN
Solar/Wind Harmer
7.355
270330AC1-082 GEN2
Solar/Wind Harmer
1.259
270329AC1-082 GEN1
Solar/Wind Harmer
0.741
270399AC1-101 GEN
Solar/Wind Harmer
6.952
270400AC1-102 GEN
Solar/Wind Harmer
6.952
24477305BRIDGE
Adder
0.568
962771AG1-126 GEN
Solar/Wind Harmer
51.279
941621AE2-160 GEN
Adder
4.884
970281AG2-184 GEN
Solar/Wind Harmer
30.593
972143AH1-644 GEN
Solar/Wind Harmer
14.568
971313AH1-133 GEN
Solar/Wind Harmer
14.325
962211AG1-066 GEN
Solar/Wind Harmer
3.356
270132AB1-180 C
Adder
0.166
24734705WLF1G3
Adder
7.759
24734805WLF1G4
Adder
7.759
24734905WLF1G5
Adder
7.759
971061AG2-657 GEN
Solar/Wind Harmer
12.002
971985AH1-537 GEN
Solar/Wind Harmer
23.775
24735105WLF2G1
Adder
7.624
966391AG1-508 GEN
Solar/Wind Harmer
4.457
971981AH1-535 GEN
Solar/Wind Harmer
12.146
965401AG1-405 GEN
Solar/Wind Harmer
6.855
965411AG1-406 GEN
Solar/Wind Harmer
3.076
339211AE2-254 GEN
Solar/Wind Harmer
1.816
970455AG2-298 GEN
Solar/Wind Harmer
7.163
3429211JKCT 2G
Adder
13.952
270367AC2-061_GEN
Solar/Wind Harmer
3.766
972163AH1-664 GEN
Solar/Wind Harmer
11.816
972165AH1-665 GEN
Solar/Wind Harmer
9.453
339243AC2-075 GEN1
Solar/Wind Harmer
0.537
963841AG1-237 GEN
Solar/Wind Harmer
12.629
25196108MFTGT2
Adder
1.772
25196108MFTGT2
Adder
1.645
24386205FR-12G C
Solar/Wind Harmer
4.941
24386405FR-21G C
Solar/Wind Harmer
4.958
24386605FR-22G C
Solar/Wind Harmer
4.958
24387005FR-3G C
Solar/Wind Harmer
4.561
944221AF1-090 GEN
Solar/Wind Harmer
12.589
24690905MDL-1G C
Solar/Wind Harmer
9.207
270180AB1-006 GEN1
Solar/Wind Harmer
8.248
946581AF1-322 GEN
Solar/Wind Harmer
11.733
24691005MDL-2G C
Solar/Wind Harmer
4.241
24697605MDL-3G C
Solar/Wind Harmer
4.228
25196408WSDLE3
Adder
9.904
25196308WSDLE2
Adder
9.818
25196208WSDLE1
Adder
9.794
25196708WSDLE6
Adder
9.769
25196508WSDLE4
Adder
9.523
274823ROCKFORD ;21
Adder
21.86
274746AC1-111 G10
Adder
6.26
274744AC1-111 GEN8
Adder
6.26
274775LINCOLN ;6U
Adder
9.447
274776LINCOLN ;7U
Adder
1.661
23750501ELLIOTTS
Solar/Wind Helper
0.66
254304AE2-114 C
Solar/Wind Helper
0.203
241997AF1-093 GEN
Solar/Wind Helper
0.238
241982AE2-343 S C
Solar/Wind Helper
0.207
238126S14_GEN_1
Solar/Wind Helper
0.669
20092526R32
Solar/Wind Helper
1.095
203961AE2-224 GEN
Solar/Wind Helper
2.258
20091526CHSTN_FL
Solar/Wind Helper
0.546
20090526Q36
Solar/Wind Helper
0.975
203993AD2-133_GEN1
Solar/Wind Helper
0.975
203846AF2-130 C
Solar/Wind Helper
0.42
238109AE1-109 GEN2
Solar/Wind Helper
0.084
238110AE1-109 GEN3
Solar/Wind Helper
0.084
941231AE2-117 GEN
Solar/Wind Helper
0.441
24697905MDL-4G C
Solar/Wind Harmer
1.02
970091AG2-072 GEN
Adder
99.087
971329AH1-144 GEN
Solar/Wind Harmer
14.766
270445AC2-157 GEN2
Solar/Wind Harmer
6.775
971821AH1-427 GEN
Solar/Wind Harmer
11.992
971565AH1-281 GEN
Solar/Wind Harmer
2.394
3429241JKCT 3G
Adder
14.135
970273AG2-179 GEN
Solar/Wind Harmer
2.902
339241AF1-083 GEN
Solar/Wind Harmer
1.973
3429421JKCT 10G
Adder
9.882
943111AE2-339 GEN
Solar/Wind Harmer
1.047
339216AC1-074 GEN
Solar/Wind Harmer
1.982
945681AF1-233 GEN
Solar/Wind Harmer
22.212
964901AG1-354 GEN
Solar/Wind Harmer
17.673
962241AG1-070 GEN
Solar/Wind Harmer
5.277
963741AG1-226 GEN
Solar/Wind Harmer
52.124
25196008MFTGT1
Adder
1.607
24385905FR-11G C
Solar/Wind Harmer
9.582
24387305FR-4G C
Solar/Wind Harmer
5.858
252507AC2-088 GEN
Solar/Wind Harmer
2.064
24728605AND G2
Adder
4.411
970245AG2-165 GEN
Solar/Wind Harmer
20.527
965911AG1-460 GEN
Solar/Wind Harmer
1.601
25196808ZIMRHP
Adder
86.412
25194608D.CRK4
Adder
1.851
274761LEE CO EC;2U
Adder
10.448
274766LEE CO EC;7U
Adder
10.325
972235AH1-702 GEN1
Adder
2.828
274822ROCKFORD ;11
Adder
22.02
274745AC1-111 GEN9
Adder
6.26
274682WAUKEGAN ;7U
Adder
20.129
274828WAUKEGAN ;BP
Adder
12.373
274773LINCOLN ;4U
Adder
9.447
274774LINCOLN ;5U
Adder
9.447
237046AF1-021 C
Solar/Wind Helper
0.484
238185AF2-356 C
Solar/Wind Helper
2.169
23751201ROTHROCK
Solar/Wind Helper
0.732
235054AD2-180 GEN
Solar/Wind Helper
1.687
23562501BACKB
Solar/Wind Helper
0.892
254303AC2-168 GEN
Solar/Wind Helper
0.147
238117U2-030
Solar/Wind Helper
0.284
241966AE1-183 GEN
Solar/Wind Helper
0.238
20089226LOOKOUT
Solar/Wind Helper
0.556
235531U2-073 GEN
Solar/Wind Helper
2.67
23751101LEADS_P59
Solar/Wind Helper
1.234
20088826HIGHLAND
Solar/Wind Helper
0.845
20094526CT_V3-030
Solar/Wind Helper
0.443
964201AG1-281 GEN
Solar/Wind Helper
0.454
238108AE1-109 GEN1
Solar/Wind Helper
0.084
24791305MDL-5G
Solar/Wind Harmer
1.072
944201AF1-088_MTX
Adder
141.066
957141AF2-008_MTX
Adder
70.533
NYPJM->LTFIMP_NY
CLTF
5.171
LGEELTFEXP_LGEE->PJM
CLTF
8.351
WECLTFEXP_WEC->PJM
CLTF
4.291
AG2-052LTFEXP_AG2-052->PJM
LTF
0.261
AH1-155LTFEXP_AH1-155->PJM
LTF
0.391
CPLELTFEXP_CPLE->PJM
CLTF
6.692
CBM West 2LTFEXP_CBM-W2->PJM
CBM
152.177
LAGNLTFEXP_LAGN->PJM
CLTF
22.306
CBM South 2LTFEXP_CBM-S2->PJM
CBM
24.638
TVALTFEXP_TVA->PJM
CLTF
11.394
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.051
CBM South 1LTFEXP_CBM-S1->PJM
CBM
43.304
MECLTFEXP_MEC->PJM
CLTF
18.986
SIGELTFEXP_SIGE->PJM
CLTF
0.624

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.56 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5885.34
MW Contribution:20.57
Bus #Bus NameTypeMW Contribution
243186AF1-051 GEN
50/50
12.748
24723005RIVRG1
Adder
37.637
24723105RIVRG2
Adder
37.637
24685805CER G1
Adder
16.117
24685905CER G2
Adder
16.117
944971AF1-162 GEN
Solar/Wind Harmer
13.01
24728205BUCHG1
Adder
7.763
971225AH1-072 GEN
Solar/Wind Harmer
2.323
971227AH1-073 GEN
Solar/Wind Harmer
2.323
971277AH1-098 GEN
Solar/Wind Harmer
4.634
270583AD2-179 GEN
Solar/Wind Harmer
11.403
960161AF2-307 GEN
Solar/Wind Harmer
6.387
971073AG2-665 GEN
Solar/Wind Harmer
8.448
270186AC1-089 GEN
Solar/Wind Harmer
0.006
970239AG2-162 GEN
Solar/Wind Harmer
2.322
942891AE2-308 GEN
Solar/Wind Harmer
9.282
972043AH1-570 GEN
Solar/Wind Harmer
2.394
972045AH1-571 GEN
Solar/Wind Harmer
1.918
339221AD2-048_GEN
Solar/Wind Harmer
0.006
24289405MTG1
50/50
11.79
24318705GVG2
50/50
11.866
24722005FLATG5
50/50
2.714
24721905FLATG4
50/50
49.755
24686205CER G4
Adder
16.139
24686405CER G5
Adder
16.075
270053AF1-130 C
Solar/Wind Harmer
2.937
970913AG2-568 GEN
Solar/Wind Harmer
9.858
960911AF2-382 GEN
Solar/Wind Harmer
9.021
943031AE2-326 GEN
Solar/Wind Harmer
6.109
971461AH1-227 GEN
Solar/Wind Harmer
5.958
972103AH1-617 GEN
Solar/Wind Harmer
23.212
971331AH1-145 GEN
Solar/Wind Harmer
15.359
247619Y1-049
Adder
0.704
971191AH1-055 GEN
Solar/Wind Harmer
29.418
270346AE1-212 GEN
Solar/Wind Harmer
10.08
958121AF2-106 GEN
Solar/Wind Harmer
0.001
972273AH1-721 GEN
Adder
111.61
270030AE2-140 GEN
Solar/Wind Harmer
18.75
970093AG2-073 GEN
Solar/Wind Harmer
9.318
970243AG2-164 GEN
Solar/Wind Harmer
5.432
970519AG2-331 GEN
Solar/Wind Harmer
24.144
970699AG2-449 GEN
Solar/Wind Harmer
2.322
966571AG1-526 GEN
Solar/Wind Harmer
20.57
270173AC1-122 GEN
Solar/Wind Harmer
0.435
3429391JKCT 9G
Adder
10.993
970273AG2-179 GEN
Solar/Wind Harmer
5.522
972167AH1-666 GEN
Solar/Wind Harmer
7.359
962751AG1-124 GEN
Solar/Wind Harmer
8.092
339250AF1-203 GEN
Solar/Wind Harmer
0.001
971155AH1-034 GEN
Solar/Wind Harmer
10.521
960741AF2-365 GEN
Solar/Wind Harmer
4.499
962251AG1-071 GEN
Solar/Wind Harmer
5.619
958171AF2-111 GEN
Solar/Wind Harmer
22.442
270291AC1-194 GEN
Solar/Wind Harmer
7.02
25196008MFTGT1
Adder
1.692
252510AF1-249 C
Solar/Wind Harmer
0.067
25194608D.CRK4
Adder
2.039
25196608WSDLE5
Adder
10.598
253316AC1-085 GEN3
Solar/Wind Harmer
0.005
253433AC1-085 GEN1
Solar/Wind Harmer
0.004
946181AF1-283 GEN
Solar/Wind Harmer
11.009
253406AD2-031_GEN
Solar/Wind Harmer
0.624
970193AG2-126 GEN
Solar/Wind Harmer
12.39
24728705AND G3
Adder
9.464
24728505AND G1
Adder
4.525
970153AG2-106 GEN
Solar/Wind Harmer
20.57
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
3147312GRETNA
Solar/Wind Harmer
0.123
3146802CHATHAM
Solar/Wind Harmer
0.115
941801AE2-185 GEN
Solar/Wind Harmer
4.925
270356AE2-297 GEN
Solar/Wind Harmer
0.011
270222AC2-111 GEN
Solar/Wind Harmer
4.144
253415AE1-040 GEN
Solar/Wind Harmer
0.003
942481AE2-261 GEN
Solar/Wind Harmer
24.109
276621W2-048 GEN
Solar/Wind Harmer
0.403
276838X2-022 GEN2
Solar/Wind Harmer
0.45
270437AC2-090 C
Solar/Wind Harmer
0.004
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
3.68
276668AB2-070 GEN1
Solar/Wind Harmer
0.29
972173AH1-669 GEN
Solar/Wind Harmer
3.965
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
7.866
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.864
970291AG2-192 GEN
Solar/Wind Harmer
0.786
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
23.525
959611AF2-252 GEN
Solar/Wind Harmer
2.614
958821AF2-173 GEN
Solar/Wind Harmer
10.961
270004AE1-209 GEN
Solar/Wind Harmer
1.696
270273AD2-016 GEN
Solar/Wind Harmer
0.81
942111AE2-223 GEN
Solar/Wind Harmer
2.536
253370AE2-315 SEC1
Adder
2.238
253371AE2-315 SEC2
Adder
2.117
965931AG1-462 GEN
Solar/Wind Harmer
19.808
946031AF1-268 GEN
Solar/Wind Harmer
7.391
3147123OTTER R
Solar/Wind Harmer
0.087
274878BISHOP HL;2U
Solar/Wind Harmer
0.26
970191AG2-125 GEN
Solar/Wind Harmer
1.992
276157O29GEN1
Solar/Wind Harmer
1.248
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
10.252
274767LEE CO EC;8U
Adder
10.131
970571AG2-364 GEN
Solar/Wind Harmer
15.368
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
972236AH1-702 GEN2
Adder
2.406
276889AE2-281 GEN
Solar/Wind Harmer
0.001
270016AE1-250 BESS
Solar/Wind Harmer
0.004
959091AF2-200 GEN
Solar/Wind Harmer
15.301
274855GSG-6 ;RU
Solar/Wind Harmer
0.28
274850MENDOTA H;RU
Solar/Wind Harmer
0.09
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.137
274682WAUKEGAN ;7U
Adder
19.567
274729ELWOOD EC;1P
Adder
8.072
237048AF1-022 C
Solar/Wind Helper
0.182
964991AG1-363 GEN
Solar/Wind Helper
3.709
23750701CROSSCHOOL
Solar/Wind Helper
1.197
238118U2-030_1
Solar/Wind Helper
0.288
238127S14_GEN_2
Solar/Wind Helper
0.687
237043AE2-125 C
Solar/Wind Helper
0.163
202652Y1-033 WT C
Solar/Wind Helper
0.534
316097T157 G90
Solar/Wind Helper
1.094
20089126CSLMN_L13
Solar/Wind Helper
0.554
20089026BF_G21_K23
Solar/Wind Helper
0.438
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.329
966021AG1-471 GEN
Solar/Wind Harmer
4.953
971125AH1-004 GEN
Solar/Wind Harmer
3.667
970107AG2-081 GEN
Solar/Wind Harmer
2.751
971485AH1-239 GEN
Solar/Wind Harmer
7.325
962581AG1-107 GEN
Solar/Wind Harmer
0.002
971081AG2-670 GEN
Solar/Wind Harmer
6.822
970235AG2-159 GEN
Solar/Wind Harmer
5.533
970235AG2-159 GEN
Solar/Wind Harmer
3.174
970653AG2-424 GEN
Solar/Wind Harmer
4.368
970653AG2-424 GEN
Solar/Wind Harmer
2.263
339255AE2-071 GEN
Solar/Wind Harmer
-0.148
964781AG1-341 GEN
Solar/Wind Harmer
9.557
964571AG1-320 GEN
Solar/Wind Harmer
8.226
252509AD1-136 GEN
Solar/Wind Harmer
0.045
25183208HLCRTG
Solar/Wind Harmer
0.014
252519AF1-045_GEN
Solar/Wind Harmer
7.591
252516AE2-318_GEN
Solar/Wind Harmer
6.733
270444AC2-157 GEN1
Solar/Wind Harmer
0.004
971587AH1-292 GEN
Solar/Wind Harmer
6.388
25194408D.CRK1
Adder
9.381
25194508D.CRK3
Adder
1.754
253317AC1-085 GEN4
Solar/Wind Harmer
0.005
945391AF1-204 GEN
Solar/Wind Harmer
8.776
253394AE2-221_GEN
Solar/Wind Harmer
0.01
253398AE2-221_GEN2
Solar/Wind Harmer
0.01
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.002
942671AE2-283 GEN
Solar/Wind Harmer
3.83
24728805RICHG1
Adder
4.412
24728905RICHG2
Adder
4.412
276916AD2-100_GEN
Solar/Wind Harmer
16.969
276911AD2-131_GEN
Solar/Wind Harmer
1.118
970241AG2-163 GEN
Solar/Wind Harmer
4.709
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
966841AG1-555 GEN
Solar/Wind Harmer
0.9
270383AD1-128 GEN
Solar/Wind Harmer
0.005
971613AH1-306 GEN
Solar/Wind Harmer
3.767
960611AF2-352 GEN
Solar/Wind Harmer
2.614
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970825AG2-519 GEN
Solar/Wind Harmer
8.658
960441AF2-335 GEN
Solar/Wind Harmer
7.811
253370AE2-315 SEC1
Adder
2.238
276782AC1-033 GEN
Solar/Wind Harmer
0.001
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.304
276646AC1-214 GEN2
Solar/Wind Harmer
0.304
276741O09 GEN1
Solar/Wind Harmer
0.275
276708O09 GEN2
Solar/Wind Harmer
0.275
972267AH1-718 GEN
Adder
4.6
970883AG2-550 GEN
Solar/Wind Harmer
7.705
970885AG2-551 GEN
Solar/Wind Harmer
2.568
276603SUBLETTE C
Solar/Wind Harmer
0
274764LEE CO EC;5U
Adder
10.276
274765LEE CO EC;6U
Adder
10.276
274762LEE CO EC;3U
Adder
10.252
274763LEE CO EC;4U
Adder
10.155
938861AE1-114 GEN
Solar/Wind Harmer
4.353
270599AE1-208 GEN
Solar/Wind Harmer
7.04
270031AE2-169
Solar/Wind Harmer
4.224
274856ECOGROVE ;U1
Solar/Wind Harmer
0.181
276611AD2-172 GEN
Solar/Wind Harmer
0.002
25322209TAIT E
Adder
10.707
25322209TAIT E
Adder
10.466
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
270013AE1-250 PV
Solar/Wind Harmer
0.004
971341AH1-150 GEN
Solar/Wind Harmer
15.301
971343AH1-151 GEN
Solar/Wind Harmer
15.301
274683WAUKEGAN ;8U
Adder
22.951
274683WAUKEGAN ;8U
Adder
19.347
274696ROCKY RD ;4P
Adder
12.409
274695ROCKY RD ;2P
Adder
12.123
274693ROCKY RD ;1P
Adder
12.003
274697ROCKY RD ;3P
Adder
3.293
247621Y3-024
Adder
0.262
23585401KL_K28_T16
Solar/Wind Helper
1.267
23652301WDPWR_K20
Solar/Wind Helper
0.133
238120AE2-309 GEN
Solar/Wind Helper
0.43
203955AF1-039 C O1
Solar/Wind Helper
0.352
944781AF1-143 GEN
Solar/Wind Helper
2.298
20083426SW_E13_K22
Solar/Wind Helper
0.051
20088926STNY CRK
Solar/Wind Helper
0.747
20084626FORWARD
Solar/Wind Helper
0.323
946071AF1-272 GEN
Solar/Wind Helper
2.428
203940AF1-140 C
Solar/Wind Helper
0.359
24721605FLATG1
50/50
2.714
972203AH1-686 GEN
Adder
4.544
957241AF2-018 GEN
Solar/Wind Harmer
-0.002
270399AC1-101 GEN
Solar/Wind Harmer
4.077
270400AC1-102 GEN
Solar/Wind Harmer
4.077
24477305BRIDGE
Adder
0.637
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
971313AH1-133 GEN
Solar/Wind Harmer
12.016
941621AE2-160 GEN
Adder
5.66
966391AG1-508 GEN
Solar/Wind Harmer
1.802
970281AG2-184 GEN
Solar/Wind Harmer
24.373
972143AH1-644 GEN
Solar/Wind Harmer
12.573
270132AB1-180 C
Adder
0.198
24734705WLF1G3
Adder
9.185
24734805WLF1G4
Adder
9.185
24734905WLF1G5
Adder
9.185
24735105WLF2G1
Adder
9.002
971061AG2-657 GEN
Solar/Wind Harmer
6.864
971985AH1-537 GEN
Solar/Wind Harmer
3.047
971981AH1-535 GEN
Solar/Wind Harmer
6.609
270069AE2-166 C O1
Solar/Wind Harmer
0.007
970879AG2-548 GEN
Solar/Wind Harmer
8.448
965401AG1-405 GEN
Solar/Wind Harmer
5.328
965411AG1-406 GEN
Solar/Wind Harmer
3.428
270367AC2-061_GEN
Solar/Wind Harmer
0.007
3429211JKCT 2G
Adder
15.52
339211AE2-254 GEN
Solar/Wind Harmer
0.004
972163AH1-664 GEN
Solar/Wind Harmer
10.275
972165AH1-665 GEN
Solar/Wind Harmer
8.229
339243AC2-075 GEN1
Solar/Wind Harmer
0.002
970455AG2-298 GEN
Solar/Wind Harmer
6.053
25196108MFTGT2
Adder
1.926
25196108MFTGT2
Adder
1.788
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
10.91
25196308WSDLE2
Adder
10.815
25196208WSDLE1
Adder
10.788
25196708WSDLE6
Adder
10.761
25196508WSDLE4
Adder
10.49
270340AC2-060 GEN
Solar/Wind Harmer
0.01
962771AG1-126 GEN
Solar/Wind Harmer
32.213
944221AF1-090 GEN
Solar/Wind Harmer
4.776
963841AG1-237 GEN
Solar/Wind Harmer
3.474
270240V3-007_GEN2
Solar/Wind Harmer
0.002
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.29
276848AB2-070 GEN3
Solar/Wind Harmer
0.289
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
1.493
270594AE1-207 GEN
Solar/Wind Harmer
8.791
270269AC2-059
Solar/Wind Harmer
0.004
970115AG2-085 GEN
Solar/Wind Harmer
3.124
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
8.194
941731AE2-173 GEN
Solar/Wind Harmer
6.503
25306009OHH W.
Adder
3.223
971673AH1-337 GEN
Solar/Wind Harmer
5.07
253372AE2-315 SEC3
Adder
2.117
253372AE2-315 SEC3
Adder
2.117
971029AG2-637 GEN
Solar/Wind Harmer
11.666
946321AF1-296 GEN
Solar/Wind Harmer
4.345
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
253349AC2-067 GEN
Solar/Wind Harmer
2.438
253400AC2-068 GEN
Solar/Wind Harmer
0.981
957751AF2-069 GEN
Solar/Wind Harmer
0.255
971611AH1-305 GEN
Solar/Wind Harmer
4.596
970169AG2-114 GEN
Solar/Wind Harmer
7.718
270543AE2-219 C
Solar/Wind Harmer
0.005
961011AF2-392 GEN
Solar/Wind Harmer
4.519
926823AC1-168 GEN
Solar/Wind Harmer
1.307
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
971681AH1-341 GEN
Solar/Wind Harmer
12.366
971609AH1-304 GEN
Solar/Wind Harmer
1.254
276612AE2-035 GEN
Solar/Wind Harmer
0.002
274823ROCKFORD ;21
Adder
21.377
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971171AH1-044 GEN
Solar/Wind Harmer
15.301
971675AH1-338 GEN
Solar/Wind Harmer
2.979
945581AF1-223 GEN
Solar/Wind Harmer
0.001
274746AC1-111 G10
Adder
6.069
274744AC1-111 GEN8
Adder
6.069
23750501ELLIOTTS
Solar/Wind Helper
0.635
238126S14_GEN_1
Solar/Wind Helper
0.687
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
20092526R32
Solar/Wind Helper
1.053
24289405MTG1
50/50
11.79
243186AF1-051 GEN
50/50
12.748
24318705GVG2
50/50
11.866
24721805FLATG3
50/50
2.714
24721705FLATG2
50/50
49.755
24723205RIVRG3
Adder
37.637
24686105CER G3
Adder
16.224
24686505CER G6
Adder
16.203
971403AH1-188 GEN
Solar/Wind Harmer
18.202
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
970947AG2-589 GEN
Solar/Wind Harmer
0.42
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
24728305BUCHG2
Adder
7.763
971687AH1-348 GEN
Solar/Wind Harmer
1.161
971329AH1-144 GEN
Solar/Wind Harmer
9.676
971315AH1-136 GEN
Solar/Wind Harmer
2.301
24735205WLF2G2
Adder
9.002
927014AC1-188 GEN
Solar/Wind Harmer
0.006
971367AH1-164 GEN
Solar/Wind Harmer
3.536
270336AE1-100 GEN
Solar/Wind Harmer
0.005
970091AG2-072 GEN
Adder
103.033
970333AG2-219 GEN
Solar/Wind Harmer
6.64
3429241JKCT 3G
Adder
15.723
971821AH1-427 GEN
Solar/Wind Harmer
9.259
3429421JKCT 10G
Adder
10.993
945681AF1-233 GEN
Solar/Wind Harmer
17.357
970273AG2-179 GEN
Solar/Wind Harmer
3.221
943811AF1-049 GEN
Solar/Wind Harmer
-0.002
339216AC1-074 GEN
Solar/Wind Harmer
0.25
971565AH1-281 GEN
Solar/Wind Harmer
1.817
964901AG1-354 GEN
Solar/Wind Harmer
13.566
962241AG1-070 GEN
Solar/Wind Harmer
4.9
252507AC2-088 GEN
Solar/Wind Harmer
0.405
25196808ZIMRHP
Adder
95.812
25196008MFTGT1
Adder
1.747
270445AC2-157 GEN2
Solar/Wind Harmer
0.004
25194608D.CRK4
Adder
2.039
270018AE2-047 C O1
Solar/Wind Harmer
0.004
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
8.469
270263AC1-001 GEN
Solar/Wind Harmer
0.833
24728605AND G2
Adder
4.525
962761AG1-125 GEN
Solar/Wind Harmer
32.213
970149AG2-104 GEN
Solar/Wind Harmer
34.791
970155AG2-107 GEN
Solar/Wind Harmer
20.57
270197AD1-017 GEN1
Solar/Wind Harmer
1.016
3147312GRETNA
Solar/Wind Harmer
0.031
941821AE2-187 GEN
Solar/Wind Harmer
4.925
970773AG2-487 GEN
Solar/Wind Harmer
1.447
963741AG1-226 GEN
Solar/Wind Harmer
19.103
965911AG1-460 GEN
Solar/Wind Harmer
1.613
276615X2-022 GEN
Solar/Wind Harmer
0.084
963831AG1-236 GEN
Solar/Wind Harmer
3.11
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
5.842
274880W4-005 GEN4
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
276903AD2-071 C
Solar/Wind Harmer
8.845
972175AH1-670 GEN
Solar/Wind Harmer
6.537
24791305MDL-5G
Solar/Wind Harmer
0.001
970291AG2-192 GEN
Solar/Wind Harmer
1.021
270032AE2-172
Solar/Wind Harmer
5.233
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
270005AE1-210 C O1
Solar/Wind Harmer
1.696
965031AG1-367 GEN
Solar/Wind Harmer
7.829
970825AG2-519 GEN
Solar/Wind Harmer
2.773
276726Z2-087_GEN
Solar/Wind Harmer
0.003
939741AE1-205 GEN
Solar/Wind Harmer
10.926
253370AE2-315 SEC1
Adder
2.238
253371AE2-315 SEC2
Adder
2.117
274877BISHOP HL;1U
Solar/Wind Harmer
0.26
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
9.649
276158O29GEN2
Solar/Wind Harmer
0.001
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
10.252
274766LEE CO EC;7U
Adder
10.131
970569AG2-363 GEN
Solar/Wind Harmer
23.052
971475AH1-234 GEN
Solar/Wind Harmer
3.722
970819AG2-516 GEN
Solar/Wind Harmer
9.198
972235AH1-702 GEN1
Adder
2.767
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
960071AF2-298 GEN
Solar/Wind Harmer
3.815
25326309TAIT D
Adder
1.202
274822ROCKFORD ;11
Adder
21.533
957471AF2-041 GEN
Solar/Wind Harmer
22.952
959081AF2-199 GEN
Solar/Wind Harmer
7.651
971067AG2-660 GEN
Solar/Wind Harmer
2.55
939401AE1-172 GEN
Solar/Wind Harmer
5.72
971997AH1-543 GEN
Solar/Wind Harmer
4.011
276861AD2-134 GEN
Solar/Wind Harmer
0.137
945371AF1-202 GEN
Solar/Wind Harmer
0.001
274828WAUKEGAN ;BP
Adder
12.03
274682WAUKEGAN ;7U
Adder
19.567
274745AC1-111 GEN9
Adder
6.069
238185AF2-356 C
Solar/Wind Helper
2.176
237046AF1-021 C
Solar/Wind Helper
0.457
235054AD2-180 GEN
Solar/Wind Helper
1.695
238117U2-030
Solar/Wind Helper
0.288
235531U2-073 GEN
Solar/Wind Helper
2.733
23751201ROTHROCK
Solar/Wind Helper
0.71
23562501BACKB
Solar/Wind Helper
0.864
23583801GRNGAP
Solar/Wind Helper
4.088
316095T157 G97
Solar/Wind Helper
1.094
238108AE1-109 GEN1
Solar/Wind Helper
0.088
20089226LOOKOUT
Solar/Wind Helper
0.539
20088826HIGHLAND
Solar/Wind Helper
0.812
944201AF1-088_MTX
Adder
145.184
957141AF2-008_MTX
Adder
72.592
NYPJM->LTFIMP_NY
CLTF
5.271
LGEELTFEXP_LGEE->PJM
CLTF
8.989
WECLTFEXP_WEC->PJM
CLTF
4.2
AG2-052LTFEXP_AG2-052->PJM
LTF
0.253
AH1-155LTFEXP_AH1-155->PJM
LTF
0.38
CPLELTFEXP_CPLE->PJM
CLTF
7.791
CBM West 2LTFEXP_CBM-W2->PJM
CBM
162.06
LAGNLTFEXP_LAGN->PJM
CLTF
24.37
CBM South 2LTFEXP_CBM-S2->PJM
CBM
29.03
TVALTFEXP_TVA->PJM
CLTF
12.655
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.592
CBM South 1LTFEXP_CBM-S1->PJM
CBM
47.815
MECLTFEXP_MEC->PJM
CLTF
19.173
SIGELTFEXP_SIGE->PJM
CLTF
0.659
CONTINGENCY 'AP_P2-3_WP-500-DRT10A_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235111 TO BUS 235117 CKT 1          /*01 502 J     500.0 - 01KAMMER     500.0
 OPEN BRANCH FROM BUS 235111 TO BUS 235113 CKT 2                /*01 502 J     500.0 - 01 502JCT    138.0
 SET POSTCONTRATING 4289 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3546 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3753 BRANCH FROM BUS 235111 TO BUS 235098 CKT 1 /*01 502 J     500.0 - WOODSIDE     500.0
END
CONTINGENCY 'AEP_P4_#8975_05KAMMER 765_MM2_SRT-A'
 OPEN BRANCH FROM BUS 235111 TO BUS 235117 CKT 1   /*01 502 J     500.0 - 01KAMMER     500.0
 OPEN BRANCH FROM BUS 235117 TO BUS 242925 CKT 1   /*01KAMMER     500.0 - 05KAMMER     765.0
END
CONTINGENCY 'AP_P2-3_WP-500-DRT7A_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235111 TO BUS 235117 CKT 1          /*01 502 J     500.0 - 01KAMMER     500.0
 SET POSTCONTRATING 4289 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3546 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3753 BRANCH FROM BUS 235111 TO BUS 235098 CKT 1 /*01 502 J     500.0 - WOODSIDE     500.0
END
CONTINGENCY 'AP_P1-2_MP-500-028_SRT-A'
 DISCONNECT BRANCH FROM BUS 235111 TO BUS 235117 CKT 1   /*01 502 J     500.0 - 01KAMMER     500.0
 DISCONNECT BRANCH FROM BUS 235117 TO BUS 242925 CKT 1   /*01KAMMER     500.0 - 05KAMMER     765.0
END
CONTINGENCY 'AP_P1-3_MP-765-502T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235117 TO BUS 242925 CKT 1   /*01KAMMER     500.0 - 05KAMMER     765.0
END
CONTINGENCY 'AP_P2-3_MP-500-024_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 1   /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 2   /*01BELMNT     500.0 - 01BELMNT     138.0
END
CONTINGENCY 'AP_P2-3_MP-500-025_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 3   /*01BELMNT     500.0 - 01BELMNT     138.0
END
CONTINGENCY 'AP_P2-3_MP-500-015_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235100 CKT 2   /*01FLINTRUN   500.0 - 01FLINTRN    138.0
END
CONTINGENCY 'AP_P2-3_MP-500-014_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235100 CKT 1   /*01FLINTRUN   500.0 - 01FLINTRN    138.0
END
CONTINGENCY 'AP_P1-2_MP-500-007A_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AP_P2-3_MP-500-012_SRT-A'
 DISCONNECT BRANCH FROM BUS 235107 TO BUS 235235 CKT 1   /*01HARRSN     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235107 TO BUS 235703 CKT 1   /*01HARRSN     500.0 - 01WYLIE R    500.0
END
CONTINGENCY 'AP_P1-2_MP-500-008A_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235107 CKT 1          /*01FLINTRUN   500.0 - 01HARRSN     500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235107 TO BUS 235703 CKT 1 /*01HARRSN     500.0 - 01WYLIE R    500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235107 TO BUS 235703 CKT 1 /*01HARRSN     500.0 - 01WYLIE R    500.0
END
CONTINGENCY 'AEP_P4_#8075_05MARYSV 765_A2_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 242939 CKT 2    /*05MARYSV     765.0 - 05MARYSV     345.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
END
CONTINGENCY 'AEP_P4_#9728_05MALIS 138_L1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243526 TO BUS 243537 CKT 2    /*05HYATT      138.0 - 05MALIS      138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P4_#9730_05MALIS 138_P1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243553 CKT 1    /*05MALIS      138.0 - 05POLARS     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P4_#9729_05MALIS 138_M1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243526 TO BUS 243537 CKT 1    /*05HYATT      138.0 - 05MALIS      138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P2-2_#7222_05MALIS 765_1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P4_#7222_05MALIS 765_D_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P4_#7216_05VASSEL 765_B1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1   /*05MALIS      765.0 - 05VASSEL     765.0
END
CONTINGENCY 'AEP_P4_#2942_05KAMMER 765_PP_SRT-A'
 OPEN BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242516 TO BUS 242920 CKT 1   /*05MOUNTN     765.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 OPEN BRANCH FROM BUS 242925 TO BUS 243188 CKT 1   /*05KAMMER     765.0 - 05MLG1        26.0
 REMOVE UNIT 1 FROM BUS 243188                     /*05MLG1        26.0
END
CONTINGENCY 'AP_P2-3_MP-500-020_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 1          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 2          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5          /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1          /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1          /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                          /*05BELMON     765.0
 SET POSTCONTRATING 2492 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
 SET PRECONTRATING 1986 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AP_P2-3_MP-500-021_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 3          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5          /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1          /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1          /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                          /*05BELMON     765.0
 SET POSTCONTRATING 2492 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
 SET PRECONTRATING 1986 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AEP_P4_#37_05MOUNTN 765_B1_SRT-A'
 OPEN BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242516 TO BUS 242920 CKT 1   /*05MOUNTN     765.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
END
CONTINGENCY 'AP_P1-3_MP-765-501T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1   /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                   /*05BELMON     765.0
END
CONTINGENCY 'AEP_P4_#706_05GAVIN 765_C1_SRT-A'
 OPEN BRANCH FROM BUS 242922 TO BUS 290622 CKT 1    /*05FLTLCK     765.0 - 05GAVIN_RF   765.0
 OPEN BRANCH FROM BUS 242923 TO BUS 290622 CKT Z1   /*05GAVIN      765.0 - 05GAVIN_RF   765.0
END
CONTINGENCY 'AEP_P2-2_#8072_05MARYSV 765_2_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 242939 CKT 2   /*05MARYSV     765.0 - 05MARYSV     345.0
END
CONTINGENCY 'AEP_P1-2_#706_SRT-A'
 OPEN BRANCH FROM BUS 242922 TO BUS 290622 CKT 1    /*05FLTLCK     765.0 - 05GAVIN_RF   765.0
 OPEN BRANCH FROM BUS 242923 TO BUS 290622 CKT Z1   /*05GAVIN      765.0 - 05GAVIN_RF   765.0
END
CONTINGENCY 'AEP_P7-1_#10944___SRT-A'
 OPEN BRANCH FROM BUS 242528 TO BUS 242940 CKT 1   /*05SPORN      345.0 - 05MUSKNG     345.0
 OPEN BRANCH FROM BUS 242940 TO BUS 242947 CKT 1   /*05MUSKNG     345.0 - 05WATERFORD  345.0
END
CONTINGENCY 'ATSI_P7-1_TE-345-027A_SRT-A'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 239289 CKT 1   /*02DAV-BE     345.0 - 02HAYES      345.0
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 241877 CKT 1   /*02DAV-BE     345.0 - AC2-103 TAP  345.0
END
CONTINGENCY 'AP_P2-2_WP-500-DRT14_SRT-SL'
 OPEN BRANCH FROM BUS 235109 TO BUS 235081 CKT 1                /*AB1-106 POI  500.0 - T-174  1     500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235108 TO BUS 235109 CKT 1 /*01HATFLD     500.0 - AB1-106 POI  500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235116 TO BUS 235109 CKT 1 /*01YUKON      500.0 - AB1-106 POI  500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235108 TO BUS 235109 CKT 1 /*01HATFLD     500.0 - AB1-106 POI  500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235116 TO BUS 235109 CKT 1 /*01YUKON      500.0 - AB1-106 POI  500.0
END
CONTINGENCY 'AEP_P4_#711_05MARYSV 765_A1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
END
CONTINGENCY 'AEP_P1-2_#711_6224_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
END
CONTINGENCY 'AEP_P1-3_#7222_05MALIS 765_1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P4_#8085_05MARYSV 345_H_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 242939 CKT 2   /*05MARYSV     765.0 - 05MARYSV     345.0
 OPEN BRANCH FROM BUS 242939 TO BUS 242945 CKT 1   /*05MARYSV     345.0 - 05SW LIM     345.0
END
CONTINGENCY 'AEP_P4_#8980_05KAMMER 765_QQ2_SRT-A'
 OPEN BRANCH FROM BUS 242925 TO BUS 290623 CKT Z1   /*05KAMMER     765.0 - 05KAMMER_RG  765.0
 OPEN BRANCH FROM BUS 246526 TO BUS 290623 CKT 1    /*05GUERNSEY   765.0 - 05KAMMER_RG  765.0
END
CONTINGENCY 'AEP_P1-2_#17217_SRT-A'
 OPEN BRANCH FROM BUS 242925 TO BUS 290623 CKT Z1   /*05KAMMER     765.0 - 05KAMMER_RG  765.0
 OPEN BRANCH FROM BUS 246526 TO BUS 290623 CKT 1    /*05GUERNSEY   765.0 - 05KAMMER_RG  765.0
END
CONTINGENCY 'AEP_P4_#7445_05MARYSV 765_B_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290621 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RF 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 962760 TO BUS 290621 CKT 1    /*AG1-125 TP   765.0 - 05MARYSVL_RF 765.0
END
CONTINGENCY 'AEP_P4_#17219_05GUERNSEY 765_A_SRT-A'
 OPEN BRANCH FROM BUS 242925 TO BUS 290623 CKT Z1   /*05KAMMER     765.0 - 05KAMMER_RG  765.0
 OPEN BRANCH FROM BUS 246526 TO BUS 246751 CKT 1    /*05GUERNSEY   765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 246526 TO BUS 290623 CKT 1    /*05GUERNSEY   765.0 - 05KAMMER_RG  765.0
END
CONTINGENCY 'AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'AEP_P1-2_#7422_16_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
235102 to 235235 ckt 1
235235 to 235107 ckt 1
235117 to 235111 ckt 1
242922 to 290622 ckt 1
242923 to 242516 ckt 1
243458 to 246752 ckt 1
242925 to 235117 ckt 1
290623 to 242925 ckt Z1
242926 to 246751 ckt 1
243538 to 243537 ckt ZB
242928 to 242939 ckt 2
242928 to 290620 ckt Z1
290620 to 242926 ckt 1
242516 to 242920 ckt 1

Winter Peak Analysis

The New Service Request AG2-107 was evaluated as a 0.0 MW (150.0 MW Capacity) injection in the AEP area.

AG2-107 was evaluated as part of a plant. The plant consists of AG2-107. The total Energy output of the plant was evaluated at its maximum seasonal capability of 400.0 MW (150.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

(No impacts were found for this analysis)

Light Load Analysis

The New Service Request AG2-107 was evaluated as a 0.0 MW injection and 150.0 MW withdrawal in the AEP area.

AG2-107 was evaluated as part of a plant. The plant consists of AG2-107. The total Energy output of the plant was evaluated at its maximum seasonal capability of 400.0 MW (150.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05BOKESCRK-05MARYSV 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC111.91 %1301.0B1455.999.79

Details for 05BOKESCRK-05MARYSV 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05BOKESCRK-05MARYSV 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.91 %
Rating:1301.0 MVA
Rating Type:B
MVA to Mitigate:1455.99
MW Contribution:9.79
Bus #Bus NameTypeMW Contribution
24695305TIMB G C
Solar/Wind Harmer
5.688
247607V1-011 GEN
Solar/Wind Harmer
4.215
247521TR3_G114
Solar/Wind Harmer
3.536
270191TR4_S_V150
Solar/Wind Harmer
2.695
270302AB2-170 GEN
Solar/Wind Harmer
0.002
270317AD1-130_GEN
Solar/Wind Harmer
0.002
270435AC2-044 GEN
Solar/Wind Harmer
1.441
270489AE1-102 GEN1
Solar/Wind Harmer
0.937
246936BC-WTG1
Solar/Wind Harmer
6.536
246937BC-WTG2
Solar/Wind Harmer
6.536
246938BC-WTG3
Solar/Wind Harmer
6.648
270297AD1-101 GEN
Solar/Wind Harmer
0.149
270258AD1-119 GEN
Solar/Wind Harmer
0.128
270471AD2-092_GEN
Solar/Wind Helper
4.05
270349AD2-093_GEN
Solar/Wind Helper
4.05
270588AE1-091_GEN
Solar/Wind Harmer
7.154
270499AE1-146 GEN
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
6.326
270541AE2-072 C
Solar/Wind Harmer
0
270520AE2-214 GEN
Solar/Wind Helper
3.26
270284AF1-227 GEN1
Solar/Wind Harmer
0.002
270054AF2-122 C O1
Solar/Wind Helper
1.466
270466AD2-091
50/50
22.432
270036AE2-216 BAT
50/50
24.675
270475AD2-096_GEN
50/50
Charging
6.251
270459AD2-067 GEN
Solar/Wind Helper
2.087
270578AF1-285 GEN2
Solar/Wind Harmer
5.173
270391AF1-285 GEN3
Solar/Wind Harmer
5.173
270361_3
Solar/Wind Harmer
4.666
270575GUS2 35KV
Solar/Wind Harmer
4.935
270462AD2-086
Solar/Wind Harmer
-0.002
972211AH1-690 GEN
50/50
53.824
247522W1-056 GEN
Solar/Wind Harmer
2.788
270491AE1-102 GEN2
Solar/Wind Harmer
0.937
946101AF1-275 GEN
Solar/Wind Helper
0.71
959331AF2-224 GEN
Solar/Wind Harmer
4.13
960851AF2-376 GEN
50/50
4.427
960861AF2-377 GEN
50/50
4.128
966831AG1-554 GEN
Solar/Wind Harmer
0
970153AG2-106 GEN
50/50
Charging
9.794
970155AG2-107 GEN
50/50
Charging
9.794
970583AG2-370 GEN
50/50
4.103
970615AG2-402 GEN
50/50
3.938
971989AH1-539 GEN
Solar/Wind Harmer
7.065
971989AH1-539 GEN
Solar/Wind Harmer
3.465
972253AH1-711 GEN
50/50
19.684
270223U2-072_GEN1
Solar/Wind Harmer
11.122
270224U2-072_GEN2
Solar/Wind Harmer
11.122
270227U2-072_GEN3
Solar/Wind Harmer
11.122
270228U2-072_GEN4
Solar/Wind Harmer
11.122
270231U2-072_GEN5
Solar/Wind Harmer
11.122
270246TR4_N_V150
Solar/Wind Harmer
0.895
270247TR4_N_V136
Solar/Wind Harmer
0.895
957201AF2-014 GEN
Solar/Wind Harmer
0.001
958091AF2-103 GEN
Solar/Wind Harmer
0
958091AF2-103 GEN
Solar/Wind Harmer
0.309
965041AG1-368 GEN
Solar/Wind Harmer
4.513
965051AG1-369 GEN
Solar/Wind Harmer
2.266
965421AG1-410 GEN
Solar/Wind Harmer
20.793
965431AG1-411 GEN
50/50
12.602
CBM West 1LTFEXP_CBM-W1->PJM
CBM
47.657
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.572
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.781
NYPJM->LTFIMP_NY
CLTF
1.051
LGEELTFEXP_LGEE->PJM
CLTF
0.48
WECLTFEXP_WEC->PJM
CLTF
1.078
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.836
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.469
TVALTFEXP_TVA->PJM
CLTF
0.104
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MECLTFEXP_MEC->PJM
CLTF
3.645
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.968
SIGELTFEXP_SIGE->PJM
CLTF
0.062
AG2-052LTFEXP_AG2-052->PJM
LTF
0.067
AH1-155LTFEXP_AH1-155->PJM
LTF
0.101
CONTINGENCY 'AEP_P1-2_#7441_100545_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
290984 to 242939 ckt 1

Short Circuit Analysis

Short Circuit analysis is not performed as part of the Phase I System Impact Study. Short Circuit analysis will commence in the Phase II System Impact Study.

Stability Analysis

Stability analysis is not performed as part of the Phase I System Impact Study. Stability analysis will commence in the Phase II System Impact Study.

Reactive Power Analysis

Reactive Power Analysis was not performed. This project is responsible for meeting all applicable power factor requirements.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-018Powerton-Goodings GroveIn Service
AA1-095Halfway-Marlowe 34.5kVIn Service
AA2-184Atlantic-Red Bank 34kVIn Service
AB1-001Absecon 12 kVIn Service
AB1-006Meadow Lake 345kVIn Service
AB1-096Carroll-Mt. Airy 34.5kVIn Service
AB1-124Carroll-Monocacy 34.5kVPartially in Service - Under Construction
AB1-125Carroll-Monocacy 34.5kVIn Service
AB1-127St. Thomas-Guilford 34.5kVIn Service
AB1-128St. Thomas-Mercersburg 34.5kVIn Service
AB1-138Navy 34.5kVIn Service
AB1-139Metuchen 26kVIn Service
AB1-141Church-Wye Mills 138 kV IIn Service
AB1-142Church-Wye Mills 138 kV IIIn Service
AB1-176Price 25kV IIEngineering & Procurement
AB1-180Pine View 12kVIn Service
AB2-029Remington 34.5kVIn Service
AB2-032Church-Wye Mills 138 kVIn Service
AB2-037Keeney-Steele 230kVUnder Construction
AB2-049Gloucester Township 12kVIn Service
AB2-067Kammer-Vassell 765kVIn Service
AB2-070Mt. Pulaski-BrokawIn Service
AB2-093Ormet 138kVIn Service
AB2-133Chestertown 69kVUnder Construction
AB2-135Church-Kent 69kVIn Service
AB2-136Cambridge-West Cambridge 69kVUnder Construction
AB2-153Church-Wye Mills 138 kVIn Service
AB2-157Prince George's County 12kVIn Service
AB2-158Louisa-South Anna 230kVIn Service
AB2-170East Lima-Marysville 345kVIn Service
AB2-179Townsend 138kVIn Service
AC1-001Delano 138kVIn Service
AC1-010Gloucester 26kVUnder Construction
AC1-017Levittown 13 kVIn Service
AC1-030Cinnaminson 13kVIn Service
AC1-033Kewanee 138 kVIn Service
AC1-042Altavista-Mt. Airy 69kVIn Service
AC1-044Kammer-Vassell 765kVIn Service
AC1-053Lanesville-BrokawPartially in Service - Under Construction
AC1-068Atlanta 69kV IIn Service
AC1-069Atlanta 69kV IIIn Service
AC1-074Jacksonville-Renaker 138kV IIn Service
AC1-076Locust Grove-Paytes 115kVIn Service
AC1-078Beatty-London 138kVIn Service
AC1-082Ravenswood-Hemlock 69kVUnder Construction
AC1-085Stuart-Clinton 345kVIn Service
AC1-089Hillsboro-Wildcat 138kVIn Service
AC1-091Cedar Creek 138kV IEngineering & Procurement
AC1-092Cedar Creek 138kV IIEngineering & Procurement
AC1-093Cedar Creek 138kV IIIEngineering & Procurement
AC1-094Cedar Creek 138kV IVEngineering & Procurement
AC1-101Johns Creek-Excel 138kV ISuspended
AC1-102Johns Creek-Excel 138kV IISuspended
AC1-111Aurora 138kVIn Service
AC1-120Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-121Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-122Smith Mountain-Candler's Mountain 138kVIn Service
AC1-141Cook-East Elkhart 345kVIn Service
AC1-145Gretna DP 69 kVIn Service
AC1-158Spotsylvania 500kVIn Service
AC1-165Atlanta 69kV IIIIn Service
AC1-166Atlanta 69kV IVIn Service
AC1-167Mark Center 69kVUnder Construction
AC1-168Kewanee-StreatorSuspended
AC1-174Losantville 345kVIn Service
AC1-175Losantville 345kVIn Service
AC1-188Rio-Lick 138kVEngineering & Procurement
AC1-194Elk 138kVActive
AC1-214Crescent RidgeIn Service
AC2-023Hebron 69kVEngineering & Procurement
AC2-029Circleville 138kVSuspended
AC2-044Maddox Creek 345kVSuspended
AC2-059Biers Run-Circleville 138kVIn Service
AC2-060Buckskin 69kVIn Service
AC2-061Hillsboro-Clinton 138kVIn Service
AC2-067Camden-Crystal I 69kVEngineering & Procurement
AC2-068Camden-Crystal II 69kVEngineering & Procurement
AC2-075Jacksonville-Renaker 138 kVIn Service
AC2-088S. Bethel-Brown 69kVIn Service
AC2-090Losantville 345kVIn Service
AC2-111College Corner 138kVEngineering & Procurement
AC2-120Ripley 69kVIn Service
AC2-123Jacksons Ferry 138kVIn Service
AC2-136East Hagerstown 12kVUnder Construction
AC2-154Davis Creek 138kVEngineering & Procurement
AC2-157Sullivan 345 kVUnder Construction
AC2-168Clinton 23kVIn Service
AC2-176Jay 138 kVIn Service
AC2-186Harrington 25kVUnder Construction
AC2-187Harrington 69kVUnder Construction
AC2-188Harrington 69 kVUnder Construction
AC2-195Galion-Roberts South 138 kVUnder Construction
AD1-013Twombly Road 138kVEngineering & Procurement
AD1-017Smith Mountain-Bearskin 138 kVIn Service
AD1-020Hunterstown-Lincoln 115 kVIn Service
AD1-060Mercersburg-Milnor 34.5 kVIn Service
AD1-061McConnelsburg-Mercersburg 34 kVIn Service
AD1-100Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVUnder Construction
AD1-101Continental 69 kVIn Service
AD1-106North Waldo-Wild Creek 138 kVSuspended
AD1-115Mountain Run-Mitchell 115 kVEngineering & Procurement
AD1-119Payne 69 kVIn Service
AD1-128Modoc-Delaware 138 kVPartially in Service - Under Construction
AD1-130Hardin Switch 345 kVIn Service
AD1-136South Bethel-Brown 69 kVIn Service
AD1-140Greene-Clark 138 kVEngineering & Procurement
AD1-155Meadow Brook-Strasburg 138 kVIn Service
AD2-009McConnellsburg 138 kVIn Service
AD2-016Biers Run-Circleville 138 kVIn Service
AD2-020Valley 138 kVEngineering & Procurement
AD2-027Camden Switch 26 kVIn Service
AD2-031Martinsville-Wilmington 69 kVIn Service
AD2-038Powerton-Nevada 345 kVUnder Construction
AD2-042Camden Switch 26 kV IIIn Service
AD2-047Davis Creek 138 kVSuspended
AD2-048Cynthia-Headquarters 69 kVUnder Construction
AD2-058St. Barnabas 13 kVIn Service
AD2-060Davis Creek 138kVEngineering & Procurement
AD2-065Atco 12 kVIn Service
AD2-066Mazon-Crescent Ridge 138 kVEngineering & Procurement
AD2-067Centerburg 138kVEngineering & Procurement
AD2-070Gilbert-Morris Park 34.5kVIn Service
AD2-071Strawton-Deer Creek 138 kVSuspended
AD2-079Capitol Ave 34.5kVIn Service
AD2-086Hardin Switch 345 kVIn Service
AD2-091Hardin Tap 345kVSuspended
AD2-092Marysville 345kVUnder Construction
AD2-093Marysville 345kVUnder Construction
AD2-096Marysville 345kVSuspended
AD2-100Kincaid-Pana 345 kVSuspended
AD2-115Lyons-Moselem 69kVIn Service
AD2-116Hokes-Grantley 69 kVIn Service
AD2-131Kincaid-Pana 345kVSuspended
AD2-133Eagle Valley 115kVIn Service
AD2-134Shady OaksPartially in Service - Under Construction
AD2-135Williamstown 12kVPartially in Service - Under Construction
AD2-163Broadview-Tangy 138 kVIn Service
AD2-172Lena 138kVIn Service
AD2-179Morgans Cut-Glen Lyn 138kVSuspended
AD2-180Elk Garden-Parr Run 138kVIn Service
AE1-040Greenfield 69 kVIn Service
AE1-041Edison 4kVIn Service
AE1-071Shade Gap-Roxbury 115 kVIn Service
AE1-079Maysville-Sharon 69 kVUnder Construction
AE1-081Landing 12.47 kVIn Service
AE1-090Hardin Switch 345 kVIn Service
AE1-091West Newton-Lynn 138 kVSuspended
AE1-092Blue Jacket-Kirby 138 kVActive
AE1-100Axton 138 kVIn Service
AE1-101McConnellsburg-Texas Eastern 138 kVIn Service
AE1-102Maddox Creek 345 kVSuspended
AE1-109Frenchs Mill 34 kVIn Service
AE1-113Mole Creek 345 kVEngineering & Procurement
AE1-114Maryland-Lancaster 138 kVActive
AE1-142Manitou-Pleasant Plains 34.5 kVIn Service
AE1-146Ebersole #2-Fostoria Central 138 kVUnder Construction
AE1-156Quakertown Solar II 34.5 kVPartially in Service - Under Construction
AE1-163Powerton-Nevada 345 kVEngineering & Procurement
AE1-166Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE1-170Kenzie Creek-Colby 138 kVSuspended
AE1-172Loretto-Wilton CenterActive
AE1-183Maysville-McDowell 69 kVEngineering & Procurement
AE1-185Hokes-Jackson 69 kVIn Service
AE1-196Hokes-Jackson 69 kV IIIn Service
AE1-205McLean 345 kVEngineering & Procurement
AE1-207Mississinewa-Gaston 138 kVSuspended
AE1-208Delaware-Van Buren 138 kVSuspended
AE1-209Desoto 345 kVSuspended
AE1-210Desoto 345 kVSuspended
AE1-212Grandview-Clifftop 138 kVSuspended
AE1-227South Cumberland 69 kVSuspended
AE1-229Deepwater-Upper Pittsgrove 138 kVSuspended
AE1-237Andover (Maysville) 69kV IUnder Construction
AE1-245Haviland 138 kVUnder Construction
AE1-250Smith Mountain-E. Danville 138 kVEngineering & Procurement
AE2-035Lena 138 kVIn Service
AE2-042Milton 69 kVIn Service
AE2-045Olive-Reynolds 345 kVEngineering & Procurement
AE2-047Ridgeway-Solite 69 kVEngineering & Procurement
AE2-048Muskingum-W. Millersport 345 kVEngineering & Procurement
AE2-054Warfordsburg 34 kVIn Service
AE2-059Derry Tap-Derry Bus 69 kVIn Service
AE2-060Mifflintown Bus-Mifflintown Tap 69 kVIn Service
AE2-071Patton Rd-Summer Shade 69 kVIn Service
AE2-072East Leipsic-Richland 138 kVIn Service
AE2-089Pennville-Adams 138 kVEngineering & Procurement
AE2-113Farmers Valley-Ridgeway 115 kVUnder Construction
AE2-114Midland 23 kV IIn Service
AE2-115Midland 23 kV IIIn Service
AE2-117ABW Tap-Alexandria 46 kVSuspended
AE2-125Stahlstown-Ligonier 25 kVIn Service
AE2-126Dubois-Curwensville 34.5 kVIn Service
AE2-129Philipsburg-Clarence 34.5 kVIn Service
AE2-131Philipsburg-Karthaus 34.5Under Construction
AE2-133Penns Tap-Richfield Tie 69 kVIn Service
AE2-136Muskingum River-W. Millersport 345 kVEngineering & Procurement
AE2-139East Towanda-Grover 230 kVEngineering & Procurement
AE2-140Axton-Danville 138 kVSuspended
AE2-148Beatty-Greene 345 kVIn Service
AE2-152Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE2-160Kanawha River 138 kVEngineering & Procurement
AE2-166Stockton 138 kVSuspended
AE2-169Delaware-Van Buren 138 kVSuspended
AE2-172Mississinewa-Gaston 138 kVSuspended
AE2-173McLean 345 kVActive
AE2-175Jackson-Long Pond 69 kVPartially in Service - Under Construction
AE2-176Groton 138 kV SolarIn Service
AE2-185Gladys DP-Stonemill Switching Station 69 kVActive
AE2-187Shockoe DP-Chatham 69 kVActive
AE2-206East Sidney-Quincy 138 kVIn Service
AE2-214Cole 345 kVEngineering & Procurement
AE2-216Hardin Switch 345 kVEngineering & Procurement
AE2-217East Springfield-London 138 kVEngineering & Procurement
AE2-219Bluff Point-Randolph 138 kVSuspended
AE2-220Losantville 345 kVEngineering & Procurement
AE2-221Clinton-Stuart 345 kVUnder Construction
AE2-223McLean 345 kVActive
AE2-224Bear Rock-Johnstown 230 kVIn Service
AE2-226Millville-Old Chapel 138 kVEngineering & Procurement
AE2-230Bartonsville-Meadow Brook 138 kVIn Service
AE2-234Liberty Center-Buckeye Tap 69 kVEngineering & Procurement
AE2-236Columbia-Northeast 138 kVSuspended
AE2-254Garrard County-Tommy-Gooch 69 kVIn Service
AE2-255Molecreek 345 kVEngineering & Procurement
AE2-261Kincaid-Pana 345 kVActive
AE2-262Moshannon-Milesburg 230 kVEngineering & Procurement
AE2-263Moshannon-Milesburg 230 kV IIEngineering & Procurement
AE2-267Woodsdale 345 kVEngineering & Procurement
AE2-281Powerton-Nevada 345 kVEngineering & Procurement
AE2-283Gladys-Stone Mill 69 kVActive
AE2-285Maysville 69 kVEngineering & Procurement
AE2-297Madison-Tanners Creek 138 kVIn Service
AE2-298Cavett Switch - West Van Wert 69 kVEngineering & Procurement
AE2-305Givens-Mechanicsburg 138 kVEngineering & Procurement
AE2-306Gunn Road 345 kVUnder Construction
AE2-308Three Forks-Dale 138 kVActive
AE2-309Carlos Junction-Lonaconing 34.5 kVIn Service
AE2-315Yankee Tap 69 kVIn Service
AE2-318Ford-Cedarville 138 kVSuspended
AE2-321Belvidere-Marengo 138 kVActive
AE2-322Mark Center 69 kVUnder Construction
AE2-323Twin Branch-Guardian 138 kVUnder Construction
AE2-325Valley 138 kVActive
AE2-326Jacksons Ferry 138 kVEngineering & Procurement
AE2-339Avon 138 kVEngineering & Procurement
AE2-341Sandwich-Plano 138 kVActive
AE2-342Woodstock 69 kVEngineering & Procurement
AE2-343Andover (Maysville) 69 kV IIUnder Construction
AF1-006Fairview East 34.5 kVIn Service
AF1-007Indian River 230 kV ISuspended
AF1-021Bethelboro-Connellsville #1 25 kVIn Service
AF1-022Lake Lynn-Uniontown 25 kVIn Service
AF1-030Sandwich-Plano 138 kVActive
AF1-038Sewellton Jct-Webbs Crossroads 69 kVEngineering & Procurement
AF1-039Listonburg-Highpoint 24.9 kVIn Service
AF1-045Cedarville-Ford 138 kVSuspended
AF1-049Berry Hill 138 kVUnder Construction
AF1-050Summer Shade - Green County 161 kVEngineering & Procurement
AF1-051Gavin 765 kVIn Service
AF1-053Givens-Mechanicsburg 138 kVEngineering & Procurement
AF1-054Givens-Mechanicsburg 138 kVEngineering & Procurement
AF1-062Jug Street 138 kVEngineering & Procurement
AF1-064Weston 69 kVUnder Construction
AF1-071College Corner 138 kVEngineering & Procurement
AF1-078East Sidney-Quincy 138 kVIn Service
AF1-083Green County-Saloma 161 kVEngineering & Procurement
AF1-084Hartford-Almena 69 kVEngineering & Procurement
AF1-086Madera-Westover South 115 kVUnder Construction
AF1-088Sullivan 345 kVActive
AF1-090Kincaid-PanaEngineering & Procurement
AF1-091Varner - Sowers 138 kVEngineering & Procurement
AF1-092Huntington Jct. 138 kVSuspended
AF1-093Henderson-Stoneboro 69 kVEngineering & Procurement
AF1-094Union City-Cambridge Springs 34.5 kVEngineering & Procurement
AF1-098Four Mile Jct-Corry East 115 kVEngineering & Procurement
AF1-118Sorenson-Desoto 345 kVEngineering & Procurement
AF1-119Keystone-Desoto 345 kVEngineering & Procurement
AF1-122Cardington-Liberty 69 kVSuspended
AF1-130Inez 138 kVSuspended
AF1-134Philipsburg-Madera 34.5 kVEngineering & Procurement
AF1-136Warfordsburg-Purcell Junction 34.5 kVEngineering & Procurement
AF1-140Claysburg 23 kVEngineering & Procurement
AF1-143Lick Run 115 kVEngineering & Procurement
AF1-147Poland Rd-Runway DP 230kVUnder Construction
AF1-153Motion-Ridgeway 46 kVSuspended
AF1-158Edison-Gravel Pit 138 kVIn Service
AF1-161Valley 138 kVActive
AF1-162Inez 138 kVEngineering & Procurement
AF1-176Corey 138 kVActive
AF1-202Keystone-Desoto 345 kVUnder Construction
AF1-203Patton Rd-Summer Shade 69 kVIn Service
AF1-204Eugene 345 kVActive
AF1-207Reynolds-Olive #1 345 kVEngineering & Procurement
AF1-215Olive-Reynolds 345 kVIn Service
AF1-223Keystone-Desoto 345 kVUnder Construction
AF1-227Marysville – Gunn Road 345 kVIn Service
AF1-228Beatty-Greene 345 kVEngineering & Procurement
AF1-229Galion-South Berwick 345 kVEngineering & Procurement
AF1-233Flemingsburg – Spurlock 138kVActive
AF1-249Nickel 12.47 kVIn Service
AF1-254Milnor-Huyetts 34.5 kVUnder Construction
AF1-262Upper Pittsgrove 12 kVIn Service
AF1-264Runnemede 13 kVIn Service
AF1-268Desoto-Jay 138 kVEngineering & Procurement
AF1-272Lucerne 115 kVEngineering & Procurement
AF1-275Cole 345 kVEngineering & Procurement
AF1-282Stuart-Clinton 345 kVEngineering & Procurement
AF1-283Stuart-Clinton 345 kVEngineering & Procurement
AF1-285Gunn Road 345 kVUnder Construction
AF1-290Feagans Mill-Millville 138 kVIn Service
AF1-291ABartonsville-Meadow Brook 138 kVIn Service
AF1-296Garden Plain 138 kVActive
AF1-299Otter Point 34.5 kV IIn Service
AF1-300Otter Point 34.5 kV IIIn Service
AF1-302Brookville-Squab Hollow 138 kVEngineering & Procurement
AF1-320Merrill Creek 115 kVEngineering & Procurement
AF1-322Meadow Lake 345 kVEngineering & Procurement
AF1-331Twombley RoadEngineering & Procurement
AF1-333Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-337Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-338Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-339Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF2-008Sullivan 345 kVActive
AF2-014Maddox Creek 345 kVEngineering & Procurement
AF2-018Inez 138 kVEngineering & Procurement
AF2-032Kincaid 345 kVEngineering & Procurement
AF2-039Shawville-Clearfield 34.5 kVEngineering & Procurement
AF2-041Nelson-Electric Junction 345 kVActive
AF2-048Rio-Lick 138 kVEngineering & Procurement
AF2-068Jay 138 kVActive
AF2-069Crescent Ridge 138 kVActive
AF2-075Bartonsville-Meadow Brook 138 kV IIIIn Service
AF2-078Reynolds-Olive #1 345 kVEngineering & Procurement
AF2-083Kenzie Creek-Stone Lake 69 kVUnder Construction
AF2-086Scott Tap-Bowmans Mill Tap 69 kVEngineering & Procurement
AF2-088Shawville-Clearfield 34.5 kV IIEngineering & Procurement
AF2-095Davis Creek 138 kVActive
AF2-103Haviland 138 kVIn Service
AF2-106Hazel Hollow-Glen Lyn #1 138 kVEngineering & Procurement
AF2-111North Clark-Spurlock 345 kVActive
AF2-122Kirk 138 kVUnder Construction
AF2-130Cobalt Corners 34.5 kVIn Service
AF2-132Reynolds-Olive #1 345 kVUnder Construction
AF2-133Reynolds-Olive #2 345 kVUnder Construction
AF2-134Olive-Reynolds #2 345 kVIn Service
AF2-138Flanders-West Wharton 34.5 kVIn Service
AF2-139Gilbert-Warren Glen 34.5 kVIn Service
AF2-142Nevada 345 kVActive
AF2-143Powerton-Nevada 345 kVActive
AF2-149Sharp Road 69 kVEngineering & Procurement
AF2-150Galion 138 kVUnder Construction
AF2-162Keystone-Desoto 345 kVEngineering & Procurement
AF2-173Desoto 345 kVActive
AF2-177Sorenson-DeSoto #2 345 kVActive
AF2-187Brookside-Cloverdale 138 kVEngineering & Procurement
AF2-192Frenchtown Solar-West Flemington 34.5 kVSuspended
AF2-199Nelson-Electric Junction 345 kVActive
AF2-200Nelson-Electric Junction 345 kVActive
AF2-205Olive-Reynolds #2 345 kVEngineering & Procurement
AF2-224Allen 345 kVEngineering & Procurement
AF2-225McLean 345 kVActive
AF2-229Roxbury 23 kVEngineering & Procurement
AF2-233Penns-Richfield Tie #1 69 kVEngineering & Procurement
AF2-234Sunbury Yard #1-Richfield Tie #2 69 kVEngineering & Procurement
AF2-235Titusville-Oil Creek 34.5 kVWithdrawn
AF2-238Mansfield-South Troy 34.5 kVEngineering & Procurement
AF2-247Bustleton 13.2 kVIn Service
AF2-250Edgewood 12 kV IIIIn Service
AF2-252Blue Mound 345 kVEngineering & Procurement
AF2-291Sporn South-Leon 138 kVEngineering & Procurement
AF2-298Crown-New Lebanon 69 kVEngineering & Procurement
AF2-307Hope-Belvins Valley Tap 69 kVActive
AF2-325Jacktown 12 kVEngineering & Procurement
AF2-335Delaware-Royerton 138 kVActive
AF2-350Kensington 138 kVActive
AF2-352Blue Mound 345 kVEngineering & Procurement
AF2-354Washington 34.5 kV IIEngineering & Procurement
AF2-356Albright-Mt. Zion 138 kVUnder Construction
AF2-359Olive-University Park 345 kVEngineering & Procurement
AF2-361Mifflintown Tap 69 kVEngineering & Procurement
AF2-365Munfordville KU Tap-Horse Cave Jct. 69 kVActive
AF2-366Crego Rd 138 kVEngineering & Procurement
AF2-371Harrison-Good Hope 138 kVEngineering & Procurement
AF2-375Ebersole-Fostoria 138 kVEngineering & Procurement
AF2-376Timber Switch 138 kVActive
AF2-377Logtown 138 kVEngineering & Procurement
AF2-378Cambridge 12 kVEngineering & Procurement
AF2-379Princess Anne 25 kVUnder Construction
AF2-382Hurley 69 kVEngineering & Procurement
AF2-383Tolna 115 kVWithdrawn
AF2-388Keystone-Desoto 345 kVActive
AF2-389Kenzie Creek-Stone Lake 69 kVWithdrawn
AF2-392Nelson-Dixon 138 kVActive
AF2-396Stinger 138 kVActive
AF2-417West Damascus Tap-West Damascus 69 kVEngineering & Procurement
AF2-421East Hazelton-Weatherly Tap 69Engineering & Procurement
AF2-424Reed-Reed Tap #1 69 kVEngineering & Procurement
AF2-425Reed-Reed Tap#1 69 kVEngineering & Procurement
AF2-433Columbia-Geisinger Tap #1 69 kVEngineering & Procurement
AF2-434Columbia-Geisinger Tap #1 69 kVEngineering & Procurement
AF2-440Hillsboro-Middleboro 138 kVEngineering & Procurement
AG1-017Jay 138 kVUnder Construction
AG1-024Centerburg 138 kVEngineering & Procurement
AG1-034Centerburg 138 kVEngineering & Procurement
AG1-039Galion 138 kV IIUnder Construction
AG1-040Morgan Street-Mount Hope 34.5 kVEngineering & Procurement
AG1-047Jay 138 kVEngineering & Procurement
AG1-054Potter-Harlan 69 kVEngineering & Procurement
AG1-066Bonnyman 69 kVEngineering & Procurement
AG1-070Bon Ayr 69 kVActive
AG1-071Bon Ayr 69 kVActive
AG1-100Venango-Saegertown 34.5 kVEngineering & Procurement
AG1-107Hillsboro-Middleboro 138 kVEngineering & Procurement
AG1-109Valley 138 kVActive
AG1-118Sugar Grove-Waterman 138kVActive
AG1-124Gladstone 138 kVActive
AG1-125Marysville-Flatlick 765 kVEngineering & Procurement
AG1-126Marysville-Flatlick 765 kVEngineering & Procurement
AG1-127Crego Rd 138 kVActive
AG1-156Jack Frost-Lake Harmony 69 kVEngineering & Procurement
AG1-164East Hazelton-Weatherly Tap 69 kVEngineering & Procurement
AG1-165East Hazelton-Weatherly Tap 69 kVEngineering & Procurement
AG1-188Manitou-Oyster Creek 34.5 kVEngineering & Procurement
AG1-189Oyster Creek-Bamber Lake 34.5Engineering & Procurement
AG1-191Chester-Pohatcong Mountain 34.5 kVPartially in Service - Under Construction
AG1-193Utica Junction 34.5 kVSuspended
AG1-197Morgan Street-Cochranton 34.5 kVSuspended
AG1-198Union City 34.5 kVUnder Construction
AG1-223Larrabee-Allaire 34.5 kVUnder Construction
AG1-226Dequine-Eugene 345 kVActive
AG1-232Magley 138 kVEngineering & Procurement
AG1-236Lanesville-Brokaw 345 kVActive
AG1-237Dequine-Eugene 345 kVEngineering & Procurement
AG1-254Salem-Woodstown 69 kVEngineering & Procurement
AG1-259Sunbury-Dalmatia 69 kVEngineering & Procurement
AG1-260Sunbury-Dalmatia 69 kVEngineering & Procurement
AG1-281Claysburg-HCR Tap 46 kVEngineering & Procurement
AG1-301Miller REC-Warrior Ridge 46 kVEngineering & Procurement
AG1-302Olive-Reynolds #1 345 kVUnder Construction
AG1-320Glendale-Stephensburg 69 kVActive
AG1-323Blue Jacket 138 kVActive
AG1-324Jay-Desoto 138 kVEngineering & Procurement
AG1-341Summer Shade 161 kVActive
AG1-348Pequest River-Washington 34.5 kVIn Service
AG1-349Olive-Reynolds #2 345 kVEngineering & Procurement
AG1-351Harrison-Good Hope 138 kVEngineering & Procurement
AG1-354Summershade-Green County 161 kVActive
AG1-363Black Oak-Hatfield 500 kVEngineering & Procurement
AG1-365Allen 345 kVEngineering & Procurement
AG1-366Allen 345 kVEngineering & Procurement
AG1-367DeSoto 345 kVActive
AG1-368Tillman 138 kVEngineering & Procurement
AG1-369Logtown 138 kVEngineering & Procurement
AG1-374Blue Mound 345 kVActive
AG1-375Sorenson-Desoto 345 kVActive
AG1-386Smith-Francis Junction 25 kVIn Service
AG1-397Walston 12 kVWithdrawn
AG1-405Walnut Grove-Asahi 69 kVActive
AG1-406Walnut Grove-Asahi 69 kVActive
AG1-410Maddox Creek-RP Mone 345 kVActive
AG1-411Maddox Creek-RP Mone 345 kVActive
AG1-414Mississinewa 138 kVEngineering & Procurement
AG1-433Keystone-DeSoto 345 kVActive
AG1-436Olive-University Park 345 kVActive
AG1-447Olive-University Park 345 kVActive
AG1-460Kincaid-Pana 345 kVActive
AG1-462Cordova 345 kVActive
AG1-469Gordonsville 34.5 kVEngineering & Procurement
AG1-471Up Church-Wayne County 69 kVActive
AG1-478Wilmington 34.5 kVEngineering & Procurement
AG1-480Shawnee 34.5 kVEngineering & Procurement
AG1-482Hamilton 115 kVWithdrawn
AG1-495Gilbert-Rocktown 34.5 kVEngineering & Procurement
AG1-499Lambs 12.47 kVUnder Construction
AG1-508Point Lookout 69 kVEngineering & Procurement
AG1-526West Garrard 345 kVActive
AG1-554South Kenton 138 kVEngineering & Procurement
AG1-555Dequine 345 kVEngineering & Procurement
AG1-559Caroline Pines 22 kVEngineering & Procurement
AG2-029Forest G. Hipple-Collingwood 345 kVActive
AG2-057Cardington-Liberty 69 kV IIActive
AG2-063North Hampton 69 kVActive
AG2-072Rockport 765 kVActive
AG2-073Crooksville 69 kVActive
AG2-081Mt. Sterling-Fogg Pike 69 kVActive
AG2-085Delaware-Royerton 138 kVActive
AG2-104Marysville-Flatlick 765 kVActive
AG2-106Marysville-Flatlick 765 kVActive
AG2-114Dresden-Pontiac Midpoint 345 kVActive
AG2-119Galion-Roberts South 138 kV IIActive
AG2-125Camden-Crystal 69 kVActive
AG2-126Eugene 345 kVActive
AG2-149Galion-South Berwick 345 kVActive
AG2-159Williamstown 69 kVActive
AG2-162Jefferson-Greentown 765 kVActive
AG2-163Dequine-Eugene 345 kVActive
AG2-164Jefferson-Greentown 765 kVActive
AG2-165Dumont-Greentown 765 kVActive
AG2-179Sewellton Junction 69 kVActive
AG2-184Harbert Metering 138 kVActive
AG2-191Mississinewa 138 kVActive
AG2-192Mississinewa 138 kVActive
AG2-212Dumont-Greentown 765 kVActive
AG2-216East Sidney-Quincy 138 kVActive
AG2-219Jefferson-Greentown 765 kVActive
AG2-230Dumont 345 kVActive
AG2-245Olive - Reynolds #1 345 kVActive
AG2-298Sulphur Creek-Loretto 69 kVActive
AG2-328Dumont - Greentown 765 kVActive
AG2-329S Berwick - Galion 345 kVActive
AG2-330Dumont - Greentown 765 kVActive
AG2-331Jefferson-Greentown 765 kVActive
AG2-332East Elkhart – Elcona Tap 138 kVActive
AG2-363Powerton 345 kVActive
AG2-364Powerton 345 kVActive
AG2-370Tillman 138 kVActive
AG2-378North Hampton – Medway 69 kVActive
AG2-385North Hampton 69 kVActive
AG2-400Allen 345 kVActive
AG2-401Losantville 345 kVActive
AG2-402Allen 345 kVActive
AG2-405Continental 69 kVActive
AG2-406Payne 69 kVActive
AG2-408Allen 345 kVActive
AG2-424Magnolia - Summersville 69 kVActive
AG2-444Bixby - Biers Run 345 kVActive
AG2-449Jefferson-Greentown 765 kVActive
AG2-453Lasalle - Plano 345 kVActive
AG2-487Madison - Tanners Creek 138 kVActive
AG2-491Meadow Lake 345 kVActive
AG2-516Pecatonica 138kVActive
AG2-519Royerton - Desoto 138 kVActive
AG2-524LaSalle Station - Mazon 138 kVActive
AG2-548Corwin - Elk 138 kVActive
AG2-550Bluff Point - Randolph 138 kVActive
AG2-551Bluff Point - Randolph 138 kVActive
AG2-568Stink Run – Sundial 138 kVActive
AG2-575Crego Rd. 138 kVActive
AG2-582Flint Run 500 kVActive
AG2-585Kensington 138kVActive
AG2-589Ravenswood - Hemlock 69 kVActive
AG2-637Randolph - Hodgin 138 kVActive
AG2-657Kanawha River - Carbondale 138 kVActive
AG2-660Nelson-Electric Junction 345 kVActive
AG2-665Corwin - Elk 138 kVActive
AG2-670Green County -Taylor County Junction 161 kVActive
AH1-004Avon - Renaker 138 kVActive
AH1-034Patton Road Junction - Summer Shade 69 kVActive
AH1-044Nelson - Electric Junction 345 kVActive
AH1-047Marengo - Belvidere 138 kVActive
AH1-055Kyger Creek - Don Marquis 345 kVActive
AH1-059Sharp Road 69 kVActive
AH1-060Cardington-Liberty 69 kV IIIActive
AH1-072Red Onion - VC5 69 kVActive
AH1-073Red Onion - VC5 69 kVActive
AH1-075North Waldo - Wild Creek 138 kVActive
AH1-098Wolf Glade-West Carroll 138 kVActive
AH1-133Saltville - Tazewell 138 kVActive
AH1-136Falcon - Middle Creek 46 kVActive
AH1-144Peter's Mountain 138 kVActive
AH1-145Peter's Mountain 138 kVActive
AH1-146White Rock - Wayne 345 kVActive
AH1-147White Rock - Wayne 345 kVActive
AH1-150Nelson-Electric Junction 345 kVActive
AH1-151Nelson-Electric Junction 345 kVActive
AH1-153Dumont 345 kVActive
AH1-164Oak Level - Tank Hill 138 kVActive
AH1-188Pigeon Creek 138 kVActive
AH1-196Prairie 345 kVActive
AH1-227Flemming - Fremont 69 kVActive
AH1-234Wempletown - Paddock 345 kVActive
AH1-239Upchurch - Zula 69 kVActive
AH1-272Argenta - Twin Branch 345 kVActive
AH1-281Bluegrass Parkway Tap - Woodlawn 69 kVActive
AH1-282Galion - Ohio Central 345 kVActive
AH1-285Sandwich 138 kVActive
AH1-292Sullivan 345 kVActive
AH1-298Meridian 345 kVActive
AH1-302Olive - Reynolds 345 kVActive
AH1-304Delaware-Van Buren 138 kVActive
AH1-305Olive - Reynolds 345 kVActive
AH1-306Mississinewa-Gaston 138 kVActive
AH1-308Pennville - Adams 138 kVActive
AH1-309Kenzie Creek-Colby 138 kVActive
AH1-327Hardin Switch 345 kVActive
AH1-328Blue Jacket - Kirby 138 kVActive
AH1-337Randolph - Hodgin 138 kVActive
AH1-338McGirr Rd - Ritchie Road 138kVActive
AH1-339West Crawford 69 kVActive
AH1-341Stillman - Dixon 138KVActive
AH1-348Pound 34.5 kVActive
AH1-391Olive 138 kVActive
AH1-392Gravel Pit-Kankakee 138 kVActive
AH1-427Tommy Gooch - Garrard County 69 kVActive
AH1-482Olive - Reynolds #2 345 kVActive
AH1-535Nagel - Cane River 230 kVActive
AH1-537Pierce - Kyger Creek 345 kVActive
AH1-539South Kenton 138 kVActive
AH1-541Chestnut 345 kVActive
AH1-542Crissinger-Kirby 138kVActive
AH1-543Mulberry – Tazewell 345 kVActive
AH1-567University Park 138 kVActive
AH1-570Headquarters - Millersburg Junction 69 kVActive
AH1-571Headquarters - Millersburg Junction 69 kVActive
AH1-617Harbert Metering 138 kVActive
AH1-644Spicewood Metering 138 kVActive
AH1-661Cannelville 12.47 kVActive
AH1-664Goddard-Plumville 138 kVActive
AH1-665Goddard-Plumsville 138 kV IIActive
AH1-666Flemingsburg - Spurlock 138 kVActive
AH1-669Circleville-Biers Run 138 kVActive
AH1-670Blue Mound-Chestnut 345 kVActive
AH1-686Hanging Rock 765 kVActive
AH1-690Bay Shore - Lallendorf 345 kVActive
AH1-698Braidwood 345 kVActive
AH1-702Byron 345 kVActive
AH1-704Hannibal 138 kVActive
AH1-711Lemoyne 345 kVActive
AH1-714Lasalle 345 kVActive
AH1-718Nelson 345 kVActive
AH1-719Beverly 345 kVActive
AH1-721Laurel-Cooper 161 kVActive
AH1-735Richland 138 kVActive
U2-030Four Mile Ridge Wind 138kVIn Service
U2-072East Lima-Marysville 345kVIn Service
U2-073Frostburg 138kV IIIn Service
V1-011Haviland 138kVIn Service
V3-007Desoto-Tanners Creek #1 345kVIn Service
V4-067Cates Road Egg Harbor Township 12kVDeactivated
V4-073Yankee 12.5kVIn Service
W1-003Oak HallIn Service
W1-004Oak HallIn Service
W1-005Oak HallIn Service
W1-006Oak HallIn Service
W1-056Ada-Dunkirk 69kVIn Service
W1-130Vine Road 12kVIn Service
W2-030Egg Harbor TownshipIn Service
W2-048Brokaw-LanesvilleIn Service
W3-077Broadway-Stewartsville 34.5kVIn Service
W4-005Blue Mound-LathamIn Service
X1-042WatervlietIn Service
X2-022Brokaw-LanesvilleIn Service
X2-052Dumont-Olive 345kVIn Service
X3-005Wildwood 12kVIn Service
X3-066Church Hill 69kVIn Service
Y1-033Penn Mar-Rock Wood 115kVIn Service
Y1-049Wurno 34.5kVIn Service
Y1-079Wye Mills 69kVIn Service
Y1-080Dorchester 12kVIn Service
Y3-023Country Side 12kVIn Service
Y3-024Bluff Point 12kVIn Service
Y3-058Rockawalkin 69kVIn Service
Z2-076Worcester South 25kVIn Service
Z2-077Worcester North 25kVIn Service
Z2-087Pontiac MidPoint-Brokaw 345kVIn Service
Z2-115Deer Creek 12.47kVIn Service
Z2-116Twin Branch 12.47kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with potential Affected System impacts. PJM initiates coordination with each Affected System Operator by providing a list of New Service Requests in the Cycle with potential impacts to their respective system. If the Affected System Operator indicates an Affected System Study is required, PJM will notify the Project Developer or Eligible Customer of the need for an Affected System Study. See below if any Affected System Operator requires a study for this project:

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Phase I analysis results, this project may have a cost responsibility for the following System Reinforcements:

AG2-107 System Reinforcements:
TORTEP IDTitleAllocated Cost ($USD)
AEP(Pending) / AEP-TC2-1865305MALIS 765.0 kV to 05VASSEL 765.0 kV ckt 1 - Replace Equipment$15,751,205
AEP(Pending) / AEP-TC2-1863405MARYSV 765.0 kV to 05MARYSV 345.0 kV ckt 2 - Add second XFMR$3,482,723
AEP(Pending) / AEP-TC2-1863505MARYSVL_RM 765.0 kV to 05MALIS 765.0 kV ckt 1 - Replace Equipment$3,157,906
AEP(Pending) / AEP-TC2-1867905GAVIN 765.0 kV to 05MOUNTN 765.0 kV ckt 1 - Replace Equipement$1,977,802
AEP(Pending) / AEP-TC2-1868205MALISX 138.0 kV to 05MALIS 138.0 kV ckt ZB - Replace equipment$668,438
AEP(Pending) / AEP-TC2-1862605FLTLCK 765.0 kV to 05GAVIN_RF 765.0 kV ckt 1 - Replace Equipment$342,914
AEP(Pending) / AEP-TC2-1868005MARYSV 765.0 kV to 05MARYSVL_RM 765.0 kV ckt Z1 - Replace Equipment$287,082
Grand Total:$25,668,070

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18653
Title
05MALIS 765.0 kV to 05VASSEL 765.0 kV ckt 1 - Replace Equipment
Description
Replace circuit breaker B, Disconnects, and reconductor between structures 432-453 to bring rating up to the sub conductor.
Total Cost ($USD)
$153,100,000
Allocated Cost ($USD)
$15,751,205
Time Estimate
36 to 48 Months

Contributor

FacilityContingency
05MALIS-05VASSEL 765.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-029
43.3 MW9.4%$14,361,607
AG2-104
108.7 MW23.5%$36,021,171
AG2-106
47.5 MW10.3%$15,751,205
AG2-107
47.5 MW10.3%$15,751,205
AG2-165
23.6 MW5.1%$7,831,194
AG2-212
23.6 MW5.1%$7,831,194
AG2-328
23.6 MW5.1%$7,831,194
AG2-363
25.2 MW5.5%$8,360,122
AG2-364
16.8 MW3.6%$5,573,304
AG2-660
2.8 MW0.6%$934,905
AH1-044
16.9 MW3.7%$5,609,097
AH1-146
24.2 MW5.2%$8,012,806
AH1-147
24.2 MW5.2%$8,012,806
AH1-150
16.9 MW3.7%$5,609,097
AH1-151
16.9 MW3.7%$5,609,097

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18634
Title
05MARYSV 765.0 kV to 05MARYSV 345.0 kV ckt 2 - Add second XFMR
Description
Add secondary 765/345 kV Transformer to Marysville. Add additional breakers to accommodate new transformer.
Total Cost ($USD)
$23,320,000
Allocated Cost ($USD)
$3,482,723
Time Estimate
36 to 48 Months

Contributor

FacilityContingency
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-104
96.6 MW42.3%$9,863,852
AG2-106
34.1 MW14.9%$3,482,723
AG2-107
34.1 MW14.9%$3,482,723
AG2-165
10.8 MW4.7%$1,107,466
AG2-212
10.8 MW4.7%$1,107,466
AG2-328
10.8 MW4.7%$1,107,466
AG2-660
1.2 MW0.5%$118,252
AH1-044
10.0 MW4.4%$1,016,684
AH1-150
10.0 MW4.4%$1,016,684
AH1-151
10.0 MW4.4%$1,016,684

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18635
Title
05MARYSVL_RM 765.0 kV to 05MALIS 765.0 kV ckt 1 - Replace Equipment
Description
Replace wave tap at Maliszewski towards Marysville along with circuit breakers, disconnects, and Sub Conductor.
Total Cost ($USD)
$24,200,000
Allocated Cost ($USD)
$3,157,906
Time Estimate
24 to 36 Months

Contributor

FacilityContingency
05MALIS-05MARYSVL_RM 765.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-104
118.0 MW29.9%$7,224,603
AG2-106
51.6 MW13.0%$3,157,906
AG2-107
51.6 MW13.0%$3,157,906
AG2-165
23.9 MW6.1%$1,465,331
AG2-212
23.9 MW6.1%$1,465,331
AG2-328
23.9 MW6.1%$1,465,331
AG2-660
2.8 MW0.7%$173,249
AH1-044
17.0 MW4.3%$1,039,432
AH1-146
24.3 MW6.1%$1,486,023
AH1-147
24.3 MW6.1%$1,486,023
AH1-150
17.0 MW4.3%$1,039,432
AH1-151
17.0 MW4.3%$1,039,432

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18679
Title
05GAVIN 765.0 kV to 05MOUNTN 765.0 kV ckt 1 - Replace Equipement
Description
At Mountaineer Station replace the following equipment: Gavin D1, Gavin D2, Gavin PH A Trap, Gavin PH C Trap. At Gavin Station Replace the following equipment: Mountaineer CB-B1, Trap - Phase 1, Trap - Phase 2, Trap - Phase 3, Unit 1 Mountaineer B
Total Cost ($USD)
$14,200,000
Allocated Cost ($USD)
$1,977,802
Time Estimate
48 to 72 Months

Contributor

FacilityContingency
05MOUNTN-05GAVIN 765.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-104
145.5 MW39.4%$5,601,667
AG2-106
51.4 MW13.9%$1,977,802
AG2-107
51.4 MW13.9%$1,977,802
AG2-165
20.8 MW5.6%$801,735
AG2-212
20.8 MW5.6%$801,735
AG2-328
20.8 MW5.6%$801,735
AG2-660
2.2 MW0.6%$83,493
AH1-044
18.6 MW5.1%$718,010
AH1-150
18.6 MW5.1%$718,010
AH1-151
18.6 MW5.1%$718,010

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18682
Title
05MALISX 138.0 kV to 05MALIS 138.0 kV ckt ZB - Replace equipment
Description
Replace air-core reactor and 2-2156 KCM at Maliszewski 138 kV
Total Cost ($USD)
$3,230,000
Allocated Cost ($USD)
$668,438
Time Estimate
24 to 36 Months

Contributor

FacilityContingency
05MALIS-05MALISX 138.0 kV Ckt ZB line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-104
30.7 MW58.6%$1,893,125
AG2-106
10.8 MW20.7%$668,438
AG2-107
10.8 MW20.7%$668,438

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18626
Title
05FLTLCK 765.0 kV to 05GAVIN_RF 765.0 kV ckt 1 - Replace Equipment
Description
At Flatlick Station replace the following equipment: CB-A, CB-B, GCB A PH. A, GCB A PH. B, GCB A PH. C, GCB B PH. A, GCB B PH. B, GCB B PH. C, Traps, CTTL 3000 Amps
Total Cost ($USD)
$2,000,000
Allocated Cost ($USD)
$342,914
Time Estimate
30 to 36 Months

Contributor

FacilityContingency
05FLTLCK-05GAVIN_RF 765.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-104
215.2 MW48.6%$971,218
AG2-106
76.0 MW17.1%$342,914
AG2-107
76.0 MW17.1%$342,914
AG2-165
25.3 MW5.7%$114,318
AG2-212
25.3 MW5.7%$114,318
AG2-328
25.3 MW5.7%$114,318

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18680
Title
05MARYSV 765.0 kV to 05MARYSVL_RM 765.0 kV ckt Z1 - Replace Equipment
Description
Replace wave trap and associated equipment on Marysville Reactor towards Maliszewski.
Total Cost ($USD)
$2,200,000
Allocated Cost ($USD)
$287,082
Time Estimate
24 to 36 Months

Contributor

FacilityContingency
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-104
118.0 MW29.9%$656,782
AG2-106
51.6 MW13.0%$287,082
AG2-107
51.6 MW13.0%$287,082
AG2-165
23.9 MW6.1%$133,212
AG2-212
23.9 MW6.1%$133,212
AG2-328
23.9 MW6.1%$133,212
AG2-660
2.8 MW0.7%$15,750
AH1-044
17.0 MW4.3%$94,494
AH1-146
24.3 MW6.1%$135,093
AH1-147
24.3 MW6.1%$135,093
AH1-150
17.0 MW4.3%$94,494
AH1-151
17.0 MW4.3%$94,494

System Reinforcement: b4000.11
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.11
Title
Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)
Description
Expand Black Oak Substation to accommodate the connection of the 502 Jct-Woodside 500 kV line and loop the 502 Jct-Woodside 500 kV line into the Black Oak substation by constructing ~0.85 miles of new 500 kV line into and out of Black Oak 500 kV substation
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-107 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-107 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)

System Reinforcement: b4000.4
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.4
Title
Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-107 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-107 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)

System Reinforcement: b4000.8
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.8
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-107 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-107 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)

System Reinforcement: b4000.7
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.7
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-107 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-107 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)

System Reinforcement: b4000.10
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.10
Title
Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yard
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-107 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-107 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)

System Reinforcement: b4000.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.1
Title
Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-107 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-107 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)

System Reinforcement: b4000.2
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.2
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-107 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-107 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)

System Reinforcement: b4000.5
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.5
Title
Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substation
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-107 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-107 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)

System Reinforcement: b4000.9
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.9
Title
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)
Description
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard. Loop in the Doubs-Goose Creek 500 kV line, the Doubs-Aspen 500 kV line, and the Woodside-Goose Creek 500 kV line. Install two 765/500 kV transformer at Rocky Point substation. 765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-107 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-107 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)

System Reinforcement: b4000.6
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.6
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-107 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-107 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)

System Reinforcement: b4000.3
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.3
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-107 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-107 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18733
Title
05BOKESCRK 345kV to 05MARYSV 345kV ckt 1 - Reconductor
Description
Reconductor line between Marysville - Boke Creek 345 kV due to paper expanded line. New line will be 2-954 ACSR RAIL
Total Cost ($USD)
$6,810,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 52 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-107 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-107 could receive cost allocation. Although AG2-107 may not presently have cost responsibility for this upgrade, AG2-107 is a potential Aggregate Pool Contributor.

FacilityContingency
05MARYSV-05BOKESCRK 345.0 kV Ckt 1 line(Any)
          New AG2-165 765kV swyd - AEP: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-165, AG2-212, AG2-328
        
          Powerton ;B 345 kV  (ComEd): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-363, AG2-364
        
          Nelson-Electric Junction 345kV - ComEd: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-660, AH1-044, AH1-150, AH1-151
        
          Byron - Wayne 345 kV - ComEd: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AH1-146, AH1-147
        

Attachments

AG2-107 One Line Diagram

AG2-107 One Line Diagram.jpg
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.