AG2-562 Phase I Study Report

v1.00 released 2025-10-29 21:14

Elderberry 345 kV

0.0 MW Capacity / 52.0 MW Energy

Introduction

This Phase I System Impact Study Report (PH1) has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, sections 307 and 308 for New Service Requests (projects) in Transition Cycle 2. The Project Developer/Eligible Customer (developer) is St. Joseph Energy Center, LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is American Electric Power.

Preface

The Phase I System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle executive summary format and (ii) an individual project-level basis. The Phase I System Impact Study Results (for both the executive summary and individual reports) will be publicly available on PJM’s website. Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.3, PJM takes the following actions during the Phase I System Impact Study:
  1. PJM studies each New Service Request on a summer peak, winter peak and light load RTEP base case study. The case year is dependent on the new services cycle under study. PJM will identify the base case year to be used in the study of a specific cycle on its website.
  2. PJM will only perform load flow analysis during the Phase I System Impact Study.
  3. In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with Affected System impacts and provides each Affected System Operator with a list of New Service Request in the Cycle with potential impacts to their respective system.
  4. PJM will create both the short circuit and stability base cases to be used in the Phase II System Impact Study.
  5. The Phase I System Impact Study results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.
The Transmission Owner takes the following actions during the Phase I System Impact Study:
  1. Identify required Interconnection Facilities to accommodate the New Service Request.
  2. Identify required Network Upgrades to mitigate system violations from the Phase I System Impact Study.
  3. Provide planning-level preliminary estimates of Interconnection Facilities and Network Upgrades including scope, cost and elapsed time to complete the work.

Decision Point I Requirements

At the close of Phase I System Impact Study, PJM will initiate Decision Point I (DP1). During DP1, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.A.1. Additional information on these elements is available in PJM Manual 14H sections 4.4, 6, and 7.

Allowable project modifications at Decision Point I are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

General

The Project Developer has proposed an uprate to a planned/existing Natural Gas facility located in the American Electric Power zone — St. Joseph County, Indiana. This project is an increase to the developer’s AB1-080 project(s), which will share the same Point of Interconnection. The AG2-562 project is a 52.0 MW uprate (0.0 MW Capacity uprate) to the previous project(s). The total installed facilities will have a capability of 767.0 MW with 40.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AG2-562
Project Name:
Elderberry 345 kV
Project Developer Name:
St. Joseph Energy Center, LLC
State:
Indiana
County:
St. Joseph
Transmission Owner:
American Electric Power
MFO:
767.0
MWE:
52.0
MWC:
0.0
Fuel Type:
Natural Gas
Basecase Study Year:
2028

Physical Interconnection Facility Study

Physical Interconnection Facilities Study is not performed as part of the Phase I System Impact Study. Physical Interconnection Facilities Study will commence in the Phase II System Impact Study.

Point of Interconnection

AG2-562 will interconnect on the American Electric Power transmission system at the Elderberry 345 kV Substation.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In the Phase I SIS, the costs shown are subject to change as a result of a facility study performed by the TO during the Phase II or Phase III System Impact Study.

Based on the Phase I SIS results, the AG2-562 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit are also shown below.

Cost Summary
DescriptionCost Allocated to AG2-562Cost Subject to Readiness*
Transmission Owner Interconnection Facilities (TOIF)$0$0
Other Scope$0$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0
Network Upgrades$111,000$111,000
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$0$0
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$0$0
Total$111,000$111,000

* Contributes to calculation for Readiness Deposit #2 (RD2). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 309 (Decision Point I) A.1.a.i and PJM Manual 14H, section 6.2, Readiness Deposit #2 (RD2) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point I (DP1), the Project Developer or Eligible Customer is required to submit Readiness Deposit #2, which is calculated as 10% of cost allocation for required Phase I Network Upgrades minus Readiness Deposit #1.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Readiness Deposit #2 Due for Project AG2-562

Readiness Deposit #2 has been calculated for the project based on the Phase I System Impact Study results and is shown in the table below. This Readiness Deposit #2 must be provided at Decision Point I through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit
Project ID10% of cost allocation for Phase I Network UpgradesReadiness Deposit #1 Received (RD1)Readiness Deposit #2 (RD2) for AG2-562 Project due at DP1
ABA - B
AG2-562$11,100$208,000$0

Note: Failure to provide an acceptable form of Readiness Deposit #2 by the end of Decision Point I will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Network Upgrades
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)AEP will review and revise the protection and control settings at the ElderBerry Station.$111,000 $111,000

Based on the scope of work for the Interconnection Facilities, it is expected to take 6 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

The schedule for any required Network Impact Reinforcements will be more clearly identified in the Phase II and Phase III System Impact Studies.

Transmission Owner Analysis

No Transmission Owner impacts identified.

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. AEP interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AG2-562 was evaluated as a 52.0 MW (0.0 MW Capacity) injection in the AEP area.

AG2-562 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 767.0 MW (52.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

(No impacts were found for this analysis)

Winter Peak Analysis

The New Service Request AG2-562 was evaluated as a 52.0 MW (0.0 MW Capacity) injection in the AEP area.

AG2-562 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 767.0 MW (52.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC117.93 %1737.0B2048.414.84
GD2AEP
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
AEP_P4_#1760_05JEFRSO 765_A_SRT-A
BreakerAC102.42 %5133.0B5257.2112.45
GD2AEP
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer
AEP_P4_#6189_05HANG R 765_D1_SRT-A
BreakerAC112.15 %3276.0B3674.05.34
GD2AEP
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer
AEP_P1-2_#709_546_SRT-A
SingleAC110.76 %3276.0B3628.465.36
GD2AEP
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer
AEP_P4_#709_05HANG R 765_D2_SRT-A
BreakerAC110.76 %3276.0B3628.465.36
GD2AEP/OVEC
05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line
AEP_P4_#6189_05HANG R 765_D1_SRT-A
BreakerAC121.71 %2991.0B3640.255.34
GD2AEP/OVEC
05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line
AEP_P4_#709_05HANG R 765_D2_SRT-A
BreakerAC120.0 %2991.0B3589.255.36
GD2AEP/OVEC
05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line
AEP_P1-2_#709_546_SRT-A
SingleAC120.0 %2991.0B3589.245.36
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
BreakerAC114.0 %4961.0B5655.6113.76
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P4_#6189_05HANG R 765_D1_SRT-A
BreakerAC104.24 %4961.0B5171.4612.73
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P4_#709_05HANG R 765_D2_SRT-A
BreakerAC102.76 %4961.0B5098.1412.77
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P1-2_#709_546_SRT-A
SingleAC102.76 %4961.0B5098.1112.77
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P4_#1760_05JEFRSO 765_A_SRT-A
BreakerAC100.41 %4961.0B4981.3713.73

Details for 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:117.93 %
Rating:1737.0 MVA
Rating Type:B
MVA to Mitigate:2048.41
MW Contribution:4.84
Bus #Bus NameTypeMW Contribution
24690905MDL-1G C
Solar/Wind Harmer
10.701
24691005MDL-2G C
Solar/Wind Harmer
5.104
24697605MDL-3G C
Solar/Wind Harmer
5.096
24697905MDL-4G C
Solar/Wind Harmer
3.365
24729205KEY G1
50/50
6.754
24729305KEY G2
50/50
6.868
24729405KEY G3
50/50
6.868
24729505KEY G4
50/50
6.754
247620Y3-023
50/50
0.466
247642Z2-115 C
Solar/Wind Harmer
0
24307105BERRINSP G
50/50
0.017
24344005CKG1
50/50
7.905
24344105CKG2
50/50
6.335
274847GR RIDGE ;BU
Solar/Wind Harmer
7.573
274848CAMPGROVE;RU
Solar/Wind Harmer
7.073
274851PROVIDENC;RU
Solar/Wind Harmer
3.718
274853TWINGROVE;U1
Solar/Wind Harmer
9.371
274854TWINGROVE;U2
Solar/Wind Harmer
7.034
274855GSG-6 ;RU
Solar/Wind Harmer
5.182
274856ECOGROVE ;U1
Solar/Wind Harmer
4.705
274861TOP CROP ;1U
Solar/Wind Harmer
8.261
274862TOP CROP ;2U
Solar/Wind Harmer
6.862
274871GR RIDGE ;2U
Solar/Wind Harmer
9.896
274877BISHOP HL;1U
Solar/Wind Harmer
4.523
274878BISHOP HL;2U
Solar/Wind Harmer
4.523
274879MINONK ;1U
Solar/Wind Harmer
9.667
274888KELLY CRK;1U
Solar/Wind Harmer
8.779
24385905FR-11G C
Solar/Wind Harmer
5.987
24386205FR-12G C
Solar/Wind Harmer
3.179
24386405FR-21G C
Solar/Wind Harmer
3.045
24386605FR-22G C
Solar/Wind Harmer
3.045
24387005FR-3G C
Solar/Wind Harmer
3.015
24387305FR-4G C
Solar/Wind Harmer
4.568
24695305TIMB G C
Solar/Wind Harmer
9.919
24699105WLD G1 C
Solar/Wind Harmer
5.025
24725505WLD G2 C
Solar/Wind Harmer
5.056
274849CRESCENT ;1U
Solar/Wind Harmer
2.569
276602WESTBROOK C
Solar/Wind Harmer
2.858
276603SUBLETTE C
Solar/Wind Harmer
1.356
247521TR3_G114
Solar/Wind Harmer
8.771
24755605MDL-5G
Solar/Wind Harmer
3.365
270191TR4_S_V150
Solar/Wind Harmer
6.54
270201AC2-176 GEN
Solar/Wind Harmer
6.697
274850MENDOTA H;RU
Solar/Wind Harmer
3.67
276691AA1-018 GEN1
Solar/Wind Harmer
0.451
276694AA1-018 GEN2
Solar/Wind Harmer
8.088
274872LEEDK;1U
Solar/Wind Harmer
11.948
274872LEEDK;1U
Solar/Wind Harmer
0.181
276646AC1-214 GEN2
Solar/Wind Harmer
1.683
276645AC1-214 GEN1
Solar/Wind Harmer
1.683
276806AD2-047 C O1
Solar/Wind Harmer
13.32
276901AD2-066 C O1
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
43.926
270142AC1-141 CT1_
50/50
2.02
270143AC1-141 CT2_
50/50
2.02
270144AC1-141 ST1_
50/50
1.789
270180AB1-006 GEN1
Solar/Wind Harmer
9.562
270181AB1-006 GEN2
Solar/Wind Harmer
0.634
253378AE2-206_GEN
Solar/Wind Helper
0.312
276889AE2-281 GEN
Solar/Wind Harmer
2.603
276872AE1-163_GEN1
Solar/Wind Harmer
9.109
276876AE1-163_GEN2
Solar/Wind Harmer
9.109
276882AE2-255 GEN
Solar/Wind Harmer
4.361
276868AE1-113 GEN
Solar/Wind Harmer
13.822
276861AD2-134 GEN
Solar/Wind Harmer
2.505
276863AD2-134 GEN
Solar/Wind Harmer
2.505
270302AB2-170 GEN
Solar/Wind Helper
1.101
270317AD1-130_GEN
Solar/Wind Helper
1.101
276655WTG1_EQ
Solar/Wind Harmer
6.657
241847AF2-150_GEN
Solar/Wind Helper
0.239
246936BC-WTG1
Solar/Wind Helper
5.496
246937BC-WTG2
Solar/Wind Helper
5.496
246938BC-WTG3
Solar/Wind Helper
5.433
241960AC2-195 GEN
Solar/Wind Helper
0.26
270449AD2-020 GEN
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
0.395
276805AD2-038 GEN
Solar/Wind Harmer
7.5
270471AD2-092_GEN
Solar/Wind Helper
0.383
270349AD2-093_GEN
Solar/Wind Helper
0.383
270499AE1-146 GEN
Solar/Wind Helper
0.511
270505AE1-170 C O1
Solar/Wind Harmer
0.728
270594AE1-207 GEN
Solar/Wind Harmer
0.66
270032AE2-172
Solar/Wind Harmer
3.298
270599AE1-208 GEN
Solar/Wind Harmer
0.373
270031AE2-169
Solar/Wind Harmer
0.373
270541AE2-072 C
Solar/Wind Helper
0.42
270024AE2-089 GEN
Solar/Wind Harmer
0
270043AE2-236 GEN
Solar/Wind Harmer
0.373
270063AE2-323 C
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
270284AF1-227 GEN1
Solar/Wind Helper
0.847
270286AF1-227 GEN2
Solar/Wind Helper
0.313
270287AF1-227 GEN3
Solar/Wind Helper
0.313
270578AF1-285 GEN2
Solar/Wind Helper
0.267
270391AF1-285 GEN3
Solar/Wind Helper
0.267
276820AF1-078_GEN
Solar/Wind Helper
0.141
270526AF1-158 GEN
Solar/Wind Harmer
0
270462AD2-086
Solar/Wind Helper
1.688
270485AE1-090_GEN
Solar/Wind Helper
0.147
270071AF1-092 GEN
Solar/Wind Harmer
0.944
270004AE1-209 GEN
Solar/Wind Harmer
6.463
270005AE1-210 C O1
Solar/Wind Harmer
6.463
24791305MDL-5G
Solar/Wind Harmer
3.365
274857EASY ROAD;U1
Solar/Wind Harmer
6.231
274858EASY ROAD;U2
Solar/Wind Harmer
6.231
274863CRW1-WTG
Solar/Wind Harmer
7.688
274864CRW2-WTG
Solar/Wind Harmer
7.688
938861AE1-114 GEN
Solar/Wind Harmer
9.335
942111AE2-223 GEN
Solar/Wind Harmer
9.047
942991AE2-321 GEN
Solar/Wind Harmer
0.41
943121AE2-341 GEN
Solar/Wind Harmer
0.633
945421AF1-207 GEN
Solar/Wind Harmer
0
946031AF1-268 GEN
Solar/Wind Harmer
0.329
946321AF1-296 GEN
Solar/Wind Harmer
11.381
946581AF1-322 GEN
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
0.629
958491AF2-143 GEN
Solar/Wind Harmer
0.621
958821AF2-173 GEN
Solar/Wind Harmer
0.58
959081AF2-199 GEN
Solar/Wind Harmer
0.406
959091AF2-200 GEN
Solar/Wind Harmer
0.811
959341AF2-225 GEN
Solar/Wind Harmer
0.58
960441AF2-335 GEN
Solar/Wind Harmer
0.407
960611AF2-352 GEN
Solar/Wind Harmer
1.153
961011AF2-392 GEN
Solar/Wind Harmer
12.249
962691AG1-118 GEN
Solar/Wind Harmer
1.242
962781AG1-127 GEN
Solar/Wind Harmer
0.393
966841AG1-555 GEN
Solar/Wind Harmer
0
970115AG2-085 GEN
Solar/Wind Harmer
0.163
970169AG2-114 GEN
Solar/Wind Harmer
0.401
970289AG2-191 GEN
Solar/Wind Harmer
0.079
970289AG2-191 GEN
Solar/Wind Harmer
0.55
970291AG2-192 GEN
Solar/Wind Harmer
0.054
970291AG2-192 GEN
Solar/Wind Harmer
0.5
970569AG2-363 GEN
Solar/Wind Harmer
1.205
970571AG2-364 GEN
Solar/Wind Harmer
0.803
970781AG2-491 GEN
Solar/Wind Harmer
0.406
970819AG2-516 GEN
Solar/Wind Harmer
0.483
970825AG2-519 GEN
Solar/Wind Harmer
0.448
970825AG2-519 GEN
Solar/Wind Harmer
1.72
970921AG2-575 GEN
Solar/Wind Harmer
0.413
970921AG2-575 GEN
Solar/Wind Harmer
1.652
971067AG2-660 GEN
Solar/Wind Harmer
1.622
971171AH1-044 GEN
Solar/Wind Harmer
0.811
971177AH1-047 GEN
Solar/Wind Harmer
0.24
971333AH1-146 GEN
Solar/Wind Harmer
0.816
971335AH1-147 GEN
Solar/Wind Harmer
0.816
971341AH1-150 GEN
Solar/Wind Harmer
0.811
971343AH1-151 GEN
Solar/Wind Harmer
0.811
971411AH1-196 GEN
Solar/Wind Harmer
0.613
971475AH1-234 GEN
Solar/Wind Harmer
0.898
971573AH1-285 GEN
Solar/Wind Harmer
0.361
971675AH1-338 GEN
Solar/Wind Harmer
0.735
971681AH1-341 GEN
Solar/Wind Harmer
0.599
276157O29GEN1
Solar/Wind Harmer
5.735
276158O29GEN2
Solar/Wind Harmer
5.735
276656WTG2_EQ
Solar/Wind Harmer
0.882
276726Z2-087_GEN
Solar/Wind Harmer
10.052
939401AE1-172 GEN
Solar/Wind Harmer
16.42
939741AE1-205 GEN
Solar/Wind Harmer
0.773
941731AE2-173 GEN
Solar/Wind Harmer
3.866
957471AF2-041 GEN
Solar/Wind Harmer
1.217
957751AF2-069 GEN
Solar/Wind Harmer
0.514
965031AG1-367 GEN
Solar/Wind Harmer
0.414
971997AH1-543 GEN
Solar/Wind Harmer
0.645
24639705ELKHART HY
50/50
0.15
24641605TWIN BRNCH
50/50
0.015
24642205MAYFLWER
50/50
0.618
24643105BUCHANAN
50/50
0.011
24653605MOTTVILLE
50/50
0.003
274887GEN-1.85
Solar/Wind Harmer
8.065
939351AE1-166 GEN
Solar/Wind Harmer
0
942871AE2-306 GEN
Solar/Wind Helper
0.2
943021AE2-325 GEN
Solar/Wind Harmer
2.992
943591AF1-030 GEN
Solar/Wind Harmer
0.422
944231AF1-091 GEN
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
2.062
944541AF1-119 GEN
Solar/Wind Harmer
0
944961AF1-161 GEN
50/50
2.389
945111AF1-176 GEN
Solar/Wind Harmer
0.888
945111AF1-176 GEN
Solar/Wind Harmer
4.84
945371AF1-202 GEN
Solar/Wind Harmer
7.519
945581AF1-223 GEN
Solar/Wind Harmer
0
945641AF1-229 GEN
Solar/Wind Helper
0.422
958861AF2-177 GEN
Solar/Wind Harmer
15.941
959141AF2-205 GEN
Solar/Wind Harmer
0
959331AF2-224 GEN
Solar/Wind Harmer
1.15
960591AF2-350 GEN
Solar/Wind Harmer
0.432
960681AF2-359 GEN
Solar/Wind Harmer
0
960791AF2-370 GEN
Solar/Wind Harmer
1.628
960841AF2-375 GEN
Solar/Wind Helper
0.529
960851AF2-376 GEN
50/50
2.119
960861AF2-377 GEN
50/50
2.413
960971AF2-388 GEN
Solar/Wind Harmer
16.413
961051AF2-396 GEN
Solar/Wind Harmer
0.97
961051AF2-396 GEN
Solar/Wind Harmer
7.761
961761AG1-017 GEN
Solar/Wind Harmer
0.391
961961AG1-039 GEN
Solar/Wind Helper
0.152
962031AG1-047 GEN
Solar/Wind Harmer
0
962601AG1-109 GEN
50/50
2.389
963791AG1-232 GEN
Solar/Wind Harmer
0.972
966831AG1-554 GEN
Solar/Wind Helper
0.265
970031AG2-029 GEN
Solar/Wind Harmer
2.112
970245AG2-165 GEN
Solar/Wind Harmer
0.894
970321AG2-212 GEN
Solar/Wind Harmer
0.894
970349AG2-230 GEN
Solar/Wind Harmer
0.729
970373AG2-245 GEN
Solar/Wind Harmer
0.936
970513AG2-328 GEN
Solar/Wind Harmer
0.894
970517AG2-330 GEN
Solar/Wind Harmer
13.95
970521AG2-332 GEN
50/50
10.877
970583AG2-370 GEN
50/50
2.823
970611AG2-400 GEN
Solar/Wind Harmer
1.15
970615AG2-402 GEN
50/50
4.602
970707AG2-453 GEN
Solar/Wind Harmer
1.203
970833AG2-524 GEN
Solar/Wind Harmer
0.467
970833AG2-524 GEN
Solar/Wind Harmer
3.74
970941AG2-585 GEN
Solar/Wind Harmer
0.541
971347AH1-153 GEN
Solar/Wind Harmer
0.729
971549AH1-272 GEN
Solar/Wind Harmer
0.738
971599AH1-298 GEN
50/50
10.386
971605AH1-302 GEN
Solar/Wind Harmer
6.341
971617AH1-308 GEN
Solar/Wind Harmer
5.201
971769AH1-391 GEN
Solar/Wind Harmer
0.472
971771AH1-392 GEN
Solar/Wind Harmer
0.442
971917AH1-482 GEN
Solar/Wind Harmer
6.726
972181SS23-001
Solar/Wind Harmer
0.444
972207SS24-0001
Solar/Wind Harmer
1.311
972231SS25-0005
Solar/Wind Harmer
0.71
270100X2-052 CT1
50/50
1.18
270101X2-052 CT2
50/50
1.18
270102X2-052 ST
50/50
1.277
270223U2-072_GEN1
Solar/Wind Helper
0.133
270224U2-072_GEN2
Solar/Wind Helper
0.133
270227U2-072_GEN3
Solar/Wind Helper
0.133
270228U2-072_GEN4
Solar/Wind Helper
0.133
270231U2-072_GEN5
Solar/Wind Helper
0.133
270246TR4_N_V150
Solar/Wind Harmer
1.186
270247TR4_N_V136
Solar/Wind Harmer
1.186
276843GEN-1.7
Solar/Wind Harmer
0.714
940581AE2-045 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Helper
3.911
957741AF2-068 GEN
Solar/Wind Harmer
0.594
957841AF2-078 GEN
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
0
958011AF2-095 GEN
Solar/Wind Harmer
0.623
958381AF2-132 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.357
964861AG1-349 GEN
Solar/Wind Harmer
0
965011AG1-365 GEN
Solar/Wind Harmer
1.15
965021AG1-366 GEN
Solar/Wind Harmer
4.602
965041AG1-368 GEN
Solar/Wind Harmer
0.706
965051AG1-369 GEN
Solar/Wind Harmer
0.301
965101AG1-375 GEN
Solar/Wind Harmer
0.511
965651AG1-433 GEN
Solar/Wind Harmer
8.207
965681AG1-436 GEN
Solar/Wind Harmer
0.578
965791AG1-447 GEN
Solar/Wind Harmer
5.09
247522W1-056 GEN
Solar/Wind Helper
1.806
270428AC2-015 C
Solar/Wind Helper
0.344
926823AC1-168 GEN
Solar/Wind Harmer
4.923
970901AG2-562 GEN
50/50
4.84
276708O09 GEN2
Solar/Wind Harmer
4.827
276741O09 GEN1
Solar/Wind Harmer
4.827
276782AC1-033 GEN
Solar/Wind Harmer
5.11
944201AF1-088_MTX
Adder
55.87
957141AF2-008_MTX
Adder
27.935
NYPJM->LTFIMP_NY
CLTF
1.226
LGEELTFEXP_LGEE->PJM
CLTF
1.819
WECLTFEXP_WEC->PJM
CLTF
2.651
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.014
LAGNLTFEXP_LAGN->PJM
CLTF
5.747
CBM West 1LTFEXP_CBM-W1->PJM
CBM
73.505
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.154
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.901
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.599
TVALTFEXP_TVA->PJM
CLTF
2.31
MECLTFEXP_MEC->PJM
CLTF
9.7
SIGELTFEXP_SIGE->PJM
CLTF
0.2
AG2-052LTFEXP_AG2-052->PJM
LTF
0.167
AH1-155LTFEXP_AH1-155->PJM
LTF
0.251
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.037

Details for 05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#1760_05JEFRSO 765_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.42 %
Rating:5133.0 MVA
Rating Type:B
MVA to Mitigate:5257.21
MW Contribution:12.45
Bus #Bus NameTypeMW Contribution
24690905MDL-1G C
Solar/Wind Harmer
26.221
24691005MDL-2G C
Solar/Wind Harmer
12.507
24697605MDL-3G C
Solar/Wind Harmer
12.487
24697905MDL-4G C
Solar/Wind Harmer
8.245
24344105CKG2
50/50
20.836
274660LASCO STA;1U
50/50
15.494
274661LASCO STA;2U
50/50
15.534
274771LINCOLN ;2U
50/50
19.255
274772LINCOLN ;3U
50/50
19.255
274773LINCOLN ;4U
50/50
19.255
274774LINCOLN ;5U
50/50
19.255
274775LINCOLN ;6U
50/50
19.255
274776LINCOLN ;7U
50/50
19.255
274777LINCOLN ;8U
50/50
19.255
274847GR RIDGE ;BU
Solar/Wind Harmer
20.848
274848CAMPGROVE;RU
Solar/Wind Harmer
18.56
274851PROVIDENC;RU
Solar/Wind Harmer
9.799
274853TWINGROVE;U1
Solar/Wind Harmer
23.921
274854TWINGROVE;U2
Solar/Wind Harmer
23.669
274855GSG-6 ;RU
Solar/Wind Harmer
14.096
274856ECOGROVE ;U1
Solar/Wind Harmer
12.687
274861TOP CROP ;1U
Solar/Wind Harmer
22.22
274862TOP CROP ;2U
Solar/Wind Harmer
18.457
274871GR RIDGE ;2U
Solar/Wind Harmer
27.244
274877BISHOP HL;1U
Solar/Wind Harmer
11.908
274878BISHOP HL;2U
Solar/Wind Harmer
11.908
274879MINONK ;1U
Solar/Wind Harmer
25.976
274888KELLY CRK;1U
Solar/Wind Harmer
23.873
24385905FR-11G C
Solar/Wind Harmer
14.202
24386205FR-12G C
Solar/Wind Harmer
7.542
24386405FR-21G C
Solar/Wind Harmer
7.224
24386605FR-22G C
Solar/Wind Harmer
7.224
24387005FR-3G C
Solar/Wind Harmer
7.152
24387305FR-4G C
Solar/Wind Harmer
10.836
274849CRESCENT ;1U
Solar/Wind Harmer
6.772
276602WESTBROOK C
Solar/Wind Harmer
7.773
276603SUBLETTE C
Solar/Wind Harmer
3.635
24755605MDL-5G
Solar/Wind Harmer
8.245
274850MENDOTA H;RU
Solar/Wind Harmer
9.983
276691AA1-018 GEN1
Solar/Wind Harmer
1.215
276694AA1-018 GEN2
Solar/Wind Harmer
21.77
274872LEEDK;1U
Solar/Wind Harmer
32.656
274872LEEDK;1U
Solar/Wind Harmer
0.495
276646AC1-214 GEN2
Solar/Wind Harmer
4.436
276645AC1-214 GEN1
Solar/Wind Harmer
4.436
276806AD2-047 C O1
Solar/Wind Harmer
36.221
276901AD2-066 C O1
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
-0.001
276897AD1-100 C
Solar/Wind Harmer
120.857
270180AB1-006 GEN1
Solar/Wind Harmer
23.431
270181AB1-006 GEN2
Solar/Wind Harmer
1.553
276889AE2-281 GEN
Solar/Wind Harmer
6.938
276872AE1-163_GEN1
Solar/Wind Harmer
24.282
276876AE1-163_GEN2
Solar/Wind Harmer
24.282
276882AE2-255 GEN
Solar/Wind Harmer
11.717
276868AE1-113 GEN
Solar/Wind Harmer
37.14
276621W2-048 GEN
Solar/Wind Harmer
18.423
276861AD2-134 GEN
Solar/Wind Harmer
6.814
276863AD2-134 GEN
Solar/Wind Harmer
6.814
276655WTG1_EQ
Solar/Wind Harmer
17.184
276838X2-022 GEN2
Solar/Wind Harmer
0.693
270449AD2-020 GEN
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
20.107
270505AE1-170 C O1
Solar/Wind Harmer
1.559
270536AF1-215 GEN2
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
5.839
274770LINCOLN ;1U
50/50
19.255
24791305MDL-5G
Solar/Wind Harmer
8.245
274857EASY ROAD;U1
Solar/Wind Harmer
16.727
274858EASY ROAD;U2
Solar/Wind Harmer
16.727
274863CRW1-WTG
Solar/Wind Harmer
20.578
274864CRW2-WTG
Solar/Wind Harmer
20.578
274880W4-005 GEN4
Solar/Wind Harmer
8.725
938861AE1-114 GEN
Solar/Wind Harmer
25.097
942111AE2-223 GEN
Solar/Wind Harmer
23.351
942991AE2-321 GEN
Solar/Wind Harmer
1.116
943121AE2-341 GEN
Solar/Wind Harmer
1.755
945421AF1-207 GEN
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
30.005
946581AF1-322 GEN
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
1.692
958491AF2-143 GEN
Solar/Wind Harmer
1.664
959081AF2-199 GEN
Solar/Wind Harmer
1.099
959091AF2-200 GEN
Solar/Wind Harmer
2.199
959341AF2-225 GEN
Solar/Wind Harmer
1.497
959611AF2-252 GEN
Solar/Wind Harmer
3.879
960611AF2-352 GEN
Solar/Wind Harmer
3.879
961011AF2-392 GEN
Solar/Wind Harmer
32.759
962691AG1-118 GEN
Solar/Wind Harmer
3.401
962781AG1-127 GEN
Solar/Wind Harmer
1.074
966841AG1-555 GEN
Solar/Wind Harmer
0
970169AG2-114 GEN
Solar/Wind Harmer
1.062
970239AG2-162 GEN
Solar/Wind Harmer
1.49
970241AG2-163 GEN
Solar/Wind Harmer
1.384
970243AG2-164 GEN
Solar/Wind Harmer
3.497
970333AG2-219 GEN
Solar/Wind Harmer
4.275
970519AG2-331 GEN
Solar/Wind Harmer
40.415
970569AG2-363 GEN
Solar/Wind Harmer
3.199
970571AG2-364 GEN
Solar/Wind Harmer
2.133
970699AG2-449 GEN
Solar/Wind Harmer
1.554
970781AG2-491 GEN
Solar/Wind Harmer
0.996
970819AG2-516 GEN
Solar/Wind Harmer
1.302
970921AG2-575 GEN
Solar/Wind Harmer
1.13
970921AG2-575 GEN
Solar/Wind Harmer
4.519
971067AG2-660 GEN
Solar/Wind Harmer
4.397
971171AH1-044 GEN
Solar/Wind Harmer
2.199
971177AH1-047 GEN
Solar/Wind Harmer
0.654
971333AH1-146 GEN
Solar/Wind Harmer
2.217
971335AH1-147 GEN
Solar/Wind Harmer
2.217
971341AH1-150 GEN
Solar/Wind Harmer
2.199
971343AH1-151 GEN
Solar/Wind Harmer
2.199
971411AH1-196 GEN
Solar/Wind Harmer
1.664
971475AH1-234 GEN
Solar/Wind Harmer
2.422
971573AH1-285 GEN
Solar/Wind Harmer
0.998
971675AH1-338 GEN
Solar/Wind Harmer
1.999
971681AH1-341 GEN
Solar/Wind Harmer
1.61
276157O29GEN1
Solar/Wind Harmer
15.263
276158O29GEN2
Solar/Wind Harmer
15.263
276174W4-005 GEN2
Solar/Wind Harmer
8.725
276656WTG2_EQ
Solar/Wind Harmer
2.275
276686W4-005 GEN3
Solar/Wind Harmer
8.725
276726Z2-087_GEN
Solar/Wind Harmer
25.946
276785W4-005 GEN1
Solar/Wind Harmer
8.725
939401AE1-172 GEN
Solar/Wind Harmer
44.375
939741AE1-205 GEN
Solar/Wind Harmer
1.996
941731AE2-173 GEN
Solar/Wind Harmer
9.979
957471AF2-041 GEN
Solar/Wind Harmer
3.298
957751AF2-069 GEN
Solar/Wind Harmer
1.354
963741AG1-226 GEN
Solar/Wind Harmer
2.492
963831AG1-236 GEN
Solar/Wind Harmer
24.413
963841AG1-237 GEN
Solar/Wind Harmer
27.26
965091AG1-374 GEN
Solar/Wind Harmer
2.909
965931AG1-462 GEN
Solar/Wind Harmer
2.547
971993AH1-541 GEN
Solar/Wind Harmer
0.811
971997AH1-543 GEN
Solar/Wind Harmer
1.743
972175AH1-670 GEN
Solar/Wind Harmer
35.909
274887GEN-1.85
Solar/Wind Harmer
21.93
939351AE1-166 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
6.426
943591AF1-030 GEN
Solar/Wind Harmer
1.17
945111AF1-176 GEN
Solar/Wind Harmer
1.764
945111AF1-176 GEN
Solar/Wind Harmer
9.614
959141AF2-205 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
1.176
960681AF2-359 GEN
Solar/Wind Harmer
0
961051AF2-396 GEN
Solar/Wind Harmer
2.024
961051AF2-396 GEN
Solar/Wind Harmer
16.191
970245AG2-165 GEN
Solar/Wind Harmer
3.135
970321AG2-212 GEN
Solar/Wind Harmer
3.135
970349AG2-230 GEN
Solar/Wind Harmer
1.965
970373AG2-245 GEN
Solar/Wind Harmer
2.378
970513AG2-328 GEN
Solar/Wind Harmer
3.135
970517AG2-330 GEN
Solar/Wind Harmer
48.901
970707AG2-453 GEN
Solar/Wind Harmer
3.386
970833AG2-524 GEN
Solar/Wind Harmer
1.286
970833AG2-524 GEN
Solar/Wind Harmer
10.292
970941AG2-585 GEN
Solar/Wind Harmer
1.47
971347AH1-153 GEN
Solar/Wind Harmer
1.965
971549AH1-272 GEN
Solar/Wind Harmer
1.657
971605AH1-302 GEN
Solar/Wind Harmer
15.855
971769AH1-391 GEN
Solar/Wind Harmer
1.127
971771AH1-392 GEN
Solar/Wind Harmer
0.959
971917AH1-482 GEN
Solar/Wind Harmer
16.916
972181SS23-001
Solar/Wind Harmer
1.162
972207SS24-0001
Solar/Wind Harmer
3.751
972231SS25-0005
Solar/Wind Harmer
1.859
972259AH1-714 GEN
50/50
40.292
270100X2-052 CT1
50/50
3.036
270101X2-052 CT2
50/50
3.036
270102X2-052 ST
50/50
3.287
276843GEN-1.7
Solar/Wind Harmer
1.943
940581AE2-045 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
0
958011AF2-095 GEN
Solar/Wind Harmer
1.693
958381AF2-132 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
1.485
965791AG1-447 GEN
Solar/Wind Harmer
13.067
926823AC1-168 GEN
Solar/Wind Harmer
13.121
970901AG2-562 GEN
50/50
12.454
276668AB2-070 GEN1
Solar/Wind Harmer
6.635
276708O09 GEN2
Solar/Wind Harmer
12.847
276741O09 GEN1
Solar/Wind Harmer
12.847
276763AC1-053 GEN1
Solar/Wind Harmer
11.302
276764AC1-053 GEN2
Solar/Wind Harmer
11.302
276782AC1-033 GEN
Solar/Wind Harmer
13.453
276848AB2-070 GEN3
Solar/Wind Harmer
6.637
276849AB2-070 GEN2
Solar/Wind Harmer
6.635
944201AF1-088_MTX
Adder
101.469
957141AF2-008_MTX
Adder
50.735
NYPJM->LTFIMP_NY
CLTF
2.839
LGEELTFEXP_LGEE->PJM
CLTF
1.755
WECLTFEXP_WEC->PJM
CLTF
7.148
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.265
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.623
LAGNLTFEXP_LAGN->PJM
CLTF
10.375
CBM West 1LTFEXP_CBM-W1->PJM
CBM
199.823
CBM West 2LTFEXP_CBM-W2->PJM
CBM
96.378
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.128
TVALTFEXP_TVA->PJM
CLTF
3.376
MECLTFEXP_MEC->PJM
CLTF
24.248
SIGELTFEXP_SIGE->PJM
CLTF
0.288
AG2-052LTFEXP_AG2-052->PJM
LTF
0.408
AH1-155LTFEXP_AH1-155->PJM
LTF
0.612
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
82.361

Details for 05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer
Contingency Name:
AEP_P4_#6189_05HANG R 765_D1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.15 %
Rating:3276.0 MVA
Rating Type:B
MVA to Mitigate:3674.0
MW Contribution:5.34
Bus #Bus NameTypeMW Contribution
24690905MDL-1G C
Solar/Wind Harmer
17.566
24691005MDL-2G C
Solar/Wind Harmer
8.379
24697605MDL-3G C
Solar/Wind Harmer
8.366
24697905MDL-4G C
Solar/Wind Harmer
5.524
24344105CKG2
50/50
6.976
24344305RKG2
50/50
11.164
24344305RKG2
50/50
11.059
274847GR RIDGE ;BU
Solar/Wind Harmer
8.595
274848CAMPGROVE;RU
Solar/Wind Harmer
8.2
274851PROVIDENC;RU
Solar/Wind Harmer
4.303
274853TWINGROVE;U1
Solar/Wind Harmer
11.619
274854TWINGROVE;U2
Solar/Wind Harmer
11.497
274855GSG-6 ;RU
Solar/Wind Harmer
5.839
274856ECOGROVE ;U1
Solar/Wind Harmer
5.289
274861TOP CROP ;1U
Solar/Wind Harmer
9.366
274862TOP CROP ;2U
Solar/Wind Harmer
7.78
274871GR RIDGE ;2U
Solar/Wind Harmer
11.232
274877BISHOP HL;1U
Solar/Wind Harmer
5.22
274878BISHOP HL;2U
Solar/Wind Harmer
5.22
274879MINONK ;1U
Solar/Wind Harmer
11.023
274888KELLY CRK;1U
Solar/Wind Harmer
9.889
24344205RKG1
50/50
11.535
24344205RKG1
50/50
11.535
24385905FR-11G C
Solar/Wind Harmer
9.968
24386205FR-12G C
Solar/Wind Harmer
5.294
24386405FR-21G C
Solar/Wind Harmer
5.071
24386605FR-22G C
Solar/Wind Harmer
5.071
24387005FR-3G C
Solar/Wind Harmer
5.02
24387305FR-4G C
Solar/Wind Harmer
7.606
274849CRESCENT ;1U
Solar/Wind Harmer
2.974
276602WESTBROOK C
Solar/Wind Harmer
3.22
276603SUBLETTE C
Solar/Wind Harmer
1.527
24755605MDL-5G
Solar/Wind Harmer
5.524
252510AF1-249 C
Solar/Wind Helper
0.1
253303V4-073 C
Solar/Wind Helper
0.007
339211AE2-254 GEN
Solar/Wind Helper
0.206
25183208HLCRTG
Solar/Wind Helper
0.934
274850MENDOTA H;RU
Solar/Wind Harmer
4.136
276691AA1-018 GEN1
Solar/Wind Harmer
0.512
276694AA1-018 GEN2
Solar/Wind Harmer
9.17
274872LEEDK;1U
Solar/Wind Harmer
13.465
274872LEEDK;1U
Solar/Wind Harmer
0.204
276646AC1-214 GEN2
Solar/Wind Harmer
1.948
276645AC1-214 GEN1
Solar/Wind Harmer
1.948
276806AD2-047 C O1
Solar/Wind Harmer
15.004
276901AD2-066 C O1
Solar/Wind Harmer
0
276916AD2-100_GEN
Solar/Wind Harmer
0.942
276911AD2-131_GEN
Solar/Wind Harmer
0.224
276893AG1-478 C
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
50.03
253415AE1-040 GEN
Solar/Wind Helper
0.146
270180AB1-006 GEN1
Solar/Wind Harmer
15.697
270181AB1-006 GEN2
Solar/Wind Harmer
1.041
253394AE2-221_GEN
Solar/Wind Helper
0.571
253398AE2-221_GEN2
Solar/Wind Helper
0.571
252507AC2-088 GEN
Solar/Wind Helper
0.372
252509AD1-136 GEN
Solar/Wind Helper
0.053
252524AE2-267 GEN
Solar/Wind Helper
0.251
276889AE2-281 GEN
Solar/Wind Harmer
2.978
276872AE1-163_GEN1
Solar/Wind Harmer
10.422
276876AE1-163_GEN2
Solar/Wind Harmer
10.422
276882AE2-255 GEN
Solar/Wind Harmer
4.972
276868AE1-113 GEN
Solar/Wind Harmer
15.761
253432AC1-085 GEN2
Solar/Wind Helper
0.019
253433AC1-085 GEN1
Solar/Wind Helper
0.37
253316AC1-085 GEN3
Solar/Wind Helper
0.584
253317AC1-085 GEN4
Solar/Wind Helper
0.584
339221AD2-048_GEN
Solar/Wind Helper
0.336
339255AE2-071 GEN
Solar/Wind Helper
0.096
276621W2-048 GEN
Solar/Wind Harmer
9.894
276861AD2-134 GEN
Solar/Wind Harmer
2.823
276863AD2-134 GEN
Solar/Wind Harmer
2.823
339231AF1-038_GEN
Solar/Wind Helper
0.182
339236AF1-050_GEN
Solar/Wind Helper
0.187
270393AB1-087 CT1
50/50
2.61
270394AB1-087 ST1
50/50
2.61
270406AB1-088 CT1
50/50
2.61
270407AB1-088 ST1
50/50
2.61
339241AF1-083 GEN
Solar/Wind Helper
0.187
276655WTG1_EQ
Solar/Wind Harmer
8.172
241972AD1-140 GEN
Solar/Wind Helper
0.525
270340AC2-060 GEN
Solar/Wind Helper
0.363
270367AC2-061_GEN
Solar/Wind Helper
0.459
276838X2-022 GEN2
Solar/Wind Harmer
0.372
270449AD2-020 GEN
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
8.535
270505AE1-170 C O1
Solar/Wind Harmer
0.688
270518AE2-148 GEN
Solar/Wind Helper
1.508
270536AF1-215 GEN2
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
339250AF1-203 GEN
Solar/Wind Helper
0.055
253406AD2-031_GEN
Solar/Wind Helper
0.181
276615X2-022 GEN
Solar/Wind Harmer
3.136
24791305MDL-5G
Solar/Wind Harmer
5.524
274857EASY ROAD;U1
Solar/Wind Harmer
7.006
274858EASY ROAD;U2
Solar/Wind Harmer
7.006
274863CRW1-WTG
Solar/Wind Harmer
9.084
274864CRW2-WTG
Solar/Wind Harmer
9.084
274880W4-005 GEN4
Solar/Wind Harmer
4.61
339206AE1-143 GEN
Solar/Wind Helper
0.343
938861AE1-114 GEN
Solar/Wind Harmer
10.503
942111AE2-223 GEN
Solar/Wind Harmer
11.105
942481AE2-261 GEN
Solar/Wind Harmer
1.344
942991AE2-321 GEN
Solar/Wind Harmer
0.462
943111AE2-339 GEN
Solar/Wind Helper
0.18
943121AE2-341 GEN
Solar/Wind Harmer
0.714
944031AF1-071 GEN
Solar/Wind Helper
0.052
944221AF1-090 GEN
Solar/Wind Harmer
13.919
945391AF1-204 GEN
Solar/Wind Harmer
20.182
945421AF1-207 GEN
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
0.713
958491AF2-143 GEN
Solar/Wind Harmer
0.707
959081AF2-199 GEN
Solar/Wind Harmer
0.457
959091AF2-200 GEN
Solar/Wind Harmer
0.913
959341AF2-225 GEN
Solar/Wind Harmer
0.712
959611AF2-252 GEN
Solar/Wind Harmer
1.884
960611AF2-352 GEN
Solar/Wind Harmer
1.884
961491AF2-440 GEN
Solar/Wind Helper
0.188
962211AG1-066 GEN
Solar/Wind Helper
0.203
962581AG1-107 GEN
Solar/Wind Helper
0.564
962691AG1-118 GEN
Solar/Wind Harmer
1.4
962781AG1-127 GEN
Solar/Wind Harmer
0.443
966841AG1-555 GEN
Solar/Wind Harmer
0
970091AG2-072 GEN
50/50
217.845
970169AG2-114 GEN
Solar/Wind Harmer
0.478
970193AG2-126 GEN
Solar/Wind Harmer
0.761
970239AG2-162 GEN
Solar/Wind Harmer
1.98
970241AG2-163 GEN
Solar/Wind Harmer
1.49
970243AG2-164 GEN
Solar/Wind Harmer
4.649
970333AG2-219 GEN
Solar/Wind Harmer
5.682
970519AG2-331 GEN
Solar/Wind Harmer
53.719
970569AG2-363 GEN
Solar/Wind Harmer
1.384
970571AG2-364 GEN
Solar/Wind Harmer
0.923
970699AG2-449 GEN
Solar/Wind Harmer
2.066
970781AG2-491 GEN
Solar/Wind Harmer
0.667
970819AG2-516 GEN
Solar/Wind Harmer
0.542
970921AG2-575 GEN
Solar/Wind Harmer
0.465
970921AG2-575 GEN
Solar/Wind Harmer
1.861
971067AG2-660 GEN
Solar/Wind Harmer
1.827
971171AH1-044 GEN
Solar/Wind Harmer
0.913
971177AH1-047 GEN
Solar/Wind Harmer
0.27
971333AH1-146 GEN
Solar/Wind Harmer
0.918
971335AH1-147 GEN
Solar/Wind Harmer
0.918
971341AH1-150 GEN
Solar/Wind Harmer
0.913
971343AH1-151 GEN
Solar/Wind Harmer
0.913
971411AH1-196 GEN
Solar/Wind Harmer
0.689
971475AH1-234 GEN
Solar/Wind Harmer
1.008
971573AH1-285 GEN
Solar/Wind Harmer
0.407
971675AH1-338 GEN
Solar/Wind Harmer
0.828
971681AH1-341 GEN
Solar/Wind Harmer
0.674
276157O29GEN1
Solar/Wind Harmer
6.495
276158O29GEN2
Solar/Wind Harmer
6.495
276174W4-005 GEN2
Solar/Wind Harmer
4.61
276656WTG2_EQ
Solar/Wind Harmer
1.082
276686W4-005 GEN3
Solar/Wind Harmer
4.61
276726Z2-087_GEN
Solar/Wind Harmer
12.339
276785W4-005 GEN1
Solar/Wind Harmer
4.61
939401AE1-172 GEN
Solar/Wind Harmer
19.205
939741AE1-205 GEN
Solar/Wind Harmer
0.949
941731AE2-173 GEN
Solar/Wind Harmer
4.746
957471AF2-041 GEN
Solar/Wind Harmer
1.37
957751AF2-069 GEN
Solar/Wind Harmer
0.595
963741AG1-226 GEN
Solar/Wind Harmer
2.681
963831AG1-236 GEN
Solar/Wind Harmer
12.96
963841AG1-237 GEN
Solar/Wind Harmer
19.403
965091AG1-374 GEN
Solar/Wind Harmer
1.413
965911AG1-460 GEN
Solar/Wind Harmer
1.079
971993AH1-541 GEN
Solar/Wind Harmer
0.428
971997AH1-543 GEN
Solar/Wind Harmer
0.74
972175AH1-670 GEN
Solar/Wind Harmer
18.216
274887GEN-1.85
Solar/Wind Harmer
9.084
939351AE1-166 GEN
Solar/Wind Harmer
0
942601AE2-276 GEN
50/50
8.301
943021AE2-325 GEN
Solar/Wind Harmer
2.845
943591AF1-030 GEN
Solar/Wind Harmer
0.476
945111AF1-176 GEN
Solar/Wind Harmer
0.807
945111AF1-176 GEN
Solar/Wind Harmer
4.397
959141AF2-205 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
0.487
960681AF2-359 GEN
Solar/Wind Harmer
0
961051AF2-396 GEN
Solar/Wind Harmer
0.907
961051AF2-396 GEN
Solar/Wind Harmer
7.254
970023AG2-014 GEN
50/50
2.668
970245AG2-165 GEN
Solar/Wind Harmer
1.378
970321AG2-212 GEN
Solar/Wind Harmer
1.378
970349AG2-230 GEN
Solar/Wind Harmer
0.752
970373AG2-245 GEN
Solar/Wind Harmer
1.203
970513AG2-328 GEN
Solar/Wind Harmer
1.378
970517AG2-330 GEN
Solar/Wind Harmer
21.5
970539AG2-343 GEN
50/50
9.296
970541AG2-344 GEN
50/50
10.141
970543AG2-345 GEN
50/50
4.648
970707AG2-453 GEN
Solar/Wind Harmer
1.36
970783AG2-492 GEN
50/50
2.668
970833AG2-524 GEN
Solar/Wind Harmer
0.53
970833AG2-524 GEN
Solar/Wind Harmer
4.244
970941AG2-585 GEN
Solar/Wind Harmer
0.609
971347AH1-153 GEN
Solar/Wind Harmer
0.752
971605AH1-302 GEN
Solar/Wind Harmer
9.691
971769AH1-391 GEN
Solar/Wind Harmer
0.492
971771AH1-392 GEN
Solar/Wind Harmer
0.425
971917AH1-482 GEN
Solar/Wind Harmer
9.665
972181SS23-001
Solar/Wind Harmer
0.493
972207SS24-0001
Solar/Wind Harmer
1.483
972231SS25-0005
Solar/Wind Harmer
0.788
270100X2-052 CT1
50/50
1.302
270101X2-052 CT2
50/50
1.302
270102X2-052 ST
50/50
1.41
276843GEN-1.7
Solar/Wind Harmer
0.805
940581AE2-045 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
0
958011AF2-095 GEN
Solar/Wind Harmer
0.701
958381AF2-132 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
0.64
965791AG1-447 GEN
Solar/Wind Harmer
5.629
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
339216AC1-074 GEN
Solar/Wind Helper
0.389
339243AC2-075 GEN1
Solar/Wind Helper
0.097
926823AC1-168 GEN
Solar/Wind Harmer
5.686
970901AG2-562 GEN
50/50
5.341
253325AC1-069 GEN
Solar/Wind Helper
0.13
253333AC1-068 GEN
Solar/Wind Helper
0.13
253338AC1-165 GEN
Solar/Wind Helper
0.13
253343AC1-166 GEN
Solar/Wind Helper
0.13
270186AC1-089 GEN
Solar/Wind Helper
0.595
276668AB2-070 GEN1
Solar/Wind Harmer
3.504
276708O09 GEN2
Solar/Wind Harmer
0.509
276741O09 GEN1
Solar/Wind Harmer
0.509
276763AC1-053 GEN1
Solar/Wind Harmer
6
276764AC1-053 GEN2
Solar/Wind Harmer
6
276782AC1-033 GEN
Solar/Wind Harmer
5.897
276848AB2-070 GEN3
Solar/Wind Harmer
3.504
276849AB2-070 GEN2
Solar/Wind Harmer
3.504
944201AF1-088_MTX
50/50
166.013
957141AF2-008_MTX
50/50
83.006
950031AG9-013
External Queue
6.4584832191467285
990742J1381
External Queue
1.0042113065719604
991082J1475 G
External Queue
0.3522087037563324
991112J1481
External Queue
1.0042113065719604
NYPJM->LTFIMP_NY
CLTF
1.09
WECLTFEXP_WEC->PJM
CLTF
2.966
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.274
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.774
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
10.03
BlueGrassPJM->LTFIMP_BlueG
CLTF
28.766
LAGNLTFEXP_LAGN->PJM
CLTF
1.981
CBM West 1LTFEXP_CBM-W1->PJM
CBM
80.147
CBM West 2LTFEXP_CBM-W2->PJM
CBM
34.191
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MECLTFEXP_MEC->PJM
CLTF
10.384
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.311
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
42.675

Details for 05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P1-2_#709_546_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer
Contingency Name:
AEP_P1-2_#709_546_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.76 %
Rating:3276.0 MVA
Rating Type:B
MVA to Mitigate:3628.46
MW Contribution:5.36
Bus #Bus NameTypeMW Contribution
24690905MDL-1G C
Solar/Wind Harmer
17.617
24691005MDL-2G C
Solar/Wind Harmer
8.403
24697605MDL-3G C
Solar/Wind Harmer
8.389
24697905MDL-4G C
Solar/Wind Harmer
5.539
24344105CKG2
50/50
7.002
24344305RKG2
50/50
11.178
24344305RKG2
50/50
11.072
274847GR RIDGE ;BU
Solar/Wind Harmer
8.629
274848CAMPGROVE;RU
Solar/Wind Harmer
8.235
274851PROVIDENC;RU
Solar/Wind Harmer
4.321
274853TWINGROVE;U1
Solar/Wind Harmer
11.667
274854TWINGROVE;U2
Solar/Wind Harmer
11.544
274855GSG-6 ;RU
Solar/Wind Harmer
5.863
274856ECOGROVE ;U1
Solar/Wind Harmer
5.312
274861TOP CROP ;1U
Solar/Wind Harmer
9.404
274862TOP CROP ;2U
Solar/Wind Harmer
7.811
274871GR RIDGE ;2U
Solar/Wind Harmer
11.277
274877BISHOP HL;1U
Solar/Wind Harmer
5.242
274878BISHOP HL;2U
Solar/Wind Harmer
5.242
274879MINONK ;1U
Solar/Wind Harmer
11.068
274888KELLY CRK;1U
Solar/Wind Harmer
9.928
24344205RKG1
50/50
11.55
24344205RKG1
50/50
11.55
24385905FR-11G C
Solar/Wind Harmer
9.998
24386205FR-12G C
Solar/Wind Harmer
5.309
24386405FR-21G C
Solar/Wind Harmer
5.085
24386605FR-22G C
Solar/Wind Harmer
5.085
24387005FR-3G C
Solar/Wind Harmer
5.035
24387305FR-4G C
Solar/Wind Harmer
7.628
274849CRESCENT ;1U
Solar/Wind Harmer
2.986
276602WESTBROOK C
Solar/Wind Harmer
3.233
276603SUBLETTE C
Solar/Wind Harmer
1.533
24755605MDL-5G
Solar/Wind Harmer
5.539
252510AF1-249 C
Solar/Wind Helper
0.1
253303V4-073 C
Solar/Wind Helper
0.007
339211AE2-254 GEN
Solar/Wind Helper
0.205
25183208HLCRTG
Solar/Wind Helper
0.93
274850MENDOTA H;RU
Solar/Wind Harmer
4.153
276691AA1-018 GEN1
Solar/Wind Harmer
0.514
276694AA1-018 GEN2
Solar/Wind Harmer
9.207
274872LEEDK;1U
Solar/Wind Harmer
13.52
274872LEEDK;1U
Solar/Wind Harmer
0.205
276646AC1-214 GEN2
Solar/Wind Harmer
1.956
276645AC1-214 GEN1
Solar/Wind Harmer
1.956
276806AD2-047 C O1
Solar/Wind Harmer
15.063
276901AD2-066 C O1
Solar/Wind Harmer
0
276916AD2-100_GEN
Solar/Wind Harmer
0.946
276911AD2-131_GEN
Solar/Wind Harmer
0.225
276893AG1-478 C
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
50.226
253415AE1-040 GEN
Solar/Wind Helper
0.145
270180AB1-006 GEN1
Solar/Wind Harmer
15.742
270181AB1-006 GEN2
Solar/Wind Harmer
1.044
253394AE2-221_GEN
Solar/Wind Helper
0.568
253398AE2-221_GEN2
Solar/Wind Helper
0.568
252507AC2-088 GEN
Solar/Wind Helper
0.371
252509AD1-136 GEN
Solar/Wind Helper
0.053
252524AE2-267 GEN
Solar/Wind Helper
0.25
276889AE2-281 GEN
Solar/Wind Harmer
2.99
276872AE1-163_GEN1
Solar/Wind Harmer
10.464
276876AE1-163_GEN2
Solar/Wind Harmer
10.464
276882AE2-255 GEN
Solar/Wind Harmer
4.992
276868AE1-113 GEN
Solar/Wind Harmer
15.825
253432AC1-085 GEN2
Solar/Wind Helper
0.019
253433AC1-085 GEN1
Solar/Wind Helper
0.368
253316AC1-085 GEN3
Solar/Wind Helper
0.581
253317AC1-085 GEN4
Solar/Wind Helper
0.581
339221AD2-048_GEN
Solar/Wind Helper
0.335
339255AE2-071 GEN
Solar/Wind Helper
0.095
276621W2-048 GEN
Solar/Wind Harmer
9.936
276861AD2-134 GEN
Solar/Wind Harmer
2.834
276863AD2-134 GEN
Solar/Wind Harmer
2.834
339231AF1-038_GEN
Solar/Wind Helper
0.181
339236AF1-050_GEN
Solar/Wind Helper
0.186
270393AB1-087 CT1
50/50
2.616
270394AB1-087 ST1
50/50
2.616
270406AB1-088 CT1
50/50
2.616
270407AB1-088 ST1
50/50
2.616
339241AF1-083 GEN
Solar/Wind Helper
0.186
276655WTG1_EQ
Solar/Wind Harmer
8.205
241972AD1-140 GEN
Solar/Wind Helper
0.522
270340AC2-060 GEN
Solar/Wind Helper
0.361
270367AC2-061_GEN
Solar/Wind Helper
0.457
276838X2-022 GEN2
Solar/Wind Harmer
0.374
270449AD2-020 GEN
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
8.569
270505AE1-170 C O1
Solar/Wind Harmer
0.691
270518AE2-148 GEN
Solar/Wind Helper
1.497
270536AF1-215 GEN2
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
339250AF1-203 GEN
Solar/Wind Helper
0.054
253406AD2-031_GEN
Solar/Wind Helper
0.18
276615X2-022 GEN
Solar/Wind Harmer
3.149
24791305MDL-5G
Solar/Wind Harmer
5.539
274857EASY ROAD;U1
Solar/Wind Harmer
7.036
274858EASY ROAD;U2
Solar/Wind Harmer
7.036
274863CRW1-WTG
Solar/Wind Harmer
9.12
274864CRW2-WTG
Solar/Wind Harmer
9.12
274880W4-005 GEN4
Solar/Wind Harmer
4.629
339206AE1-143 GEN
Solar/Wind Helper
0.341
938861AE1-114 GEN
Solar/Wind Harmer
10.548
942111AE2-223 GEN
Solar/Wind Harmer
11.15
942481AE2-261 GEN
Solar/Wind Harmer
1.35
942991AE2-321 GEN
Solar/Wind Harmer
0.464
943111AE2-339 GEN
Solar/Wind Helper
0.179
943121AE2-341 GEN
Solar/Wind Harmer
0.717
944031AF1-071 GEN
Solar/Wind Helper
0.051
944221AF1-090 GEN
Solar/Wind Harmer
13.979
945391AF1-204 GEN
Solar/Wind Harmer
20.258
945421AF1-207 GEN
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
0.716
958491AF2-143 GEN
Solar/Wind Harmer
0.709
959081AF2-199 GEN
Solar/Wind Harmer
0.459
959091AF2-200 GEN
Solar/Wind Harmer
0.917
959341AF2-225 GEN
Solar/Wind Harmer
0.715
959611AF2-252 GEN
Solar/Wind Harmer
1.892
960611AF2-352 GEN
Solar/Wind Harmer
1.892
961491AF2-440 GEN
Solar/Wind Helper
0.187
962211AG1-066 GEN
Solar/Wind Helper
0.201
962581AG1-107 GEN
Solar/Wind Helper
0.562
962691AG1-118 GEN
Solar/Wind Harmer
1.405
962781AG1-127 GEN
Solar/Wind Harmer
0.444
966841AG1-555 GEN
Solar/Wind Harmer
0
970091AG2-072 GEN
50/50
218.112
970169AG2-114 GEN
Solar/Wind Harmer
0.48
970193AG2-126 GEN
Solar/Wind Harmer
0.764
970239AG2-162 GEN
Solar/Wind Harmer
1.982
970241AG2-163 GEN
Solar/Wind Harmer
1.494
970243AG2-164 GEN
Solar/Wind Harmer
4.654
970333AG2-219 GEN
Solar/Wind Harmer
5.688
970519AG2-331 GEN
Solar/Wind Harmer
53.778
970569AG2-363 GEN
Solar/Wind Harmer
1.39
970571AG2-364 GEN
Solar/Wind Harmer
0.926
970699AG2-449 GEN
Solar/Wind Harmer
2.068
970781AG2-491 GEN
Solar/Wind Harmer
0.669
970819AG2-516 GEN
Solar/Wind Harmer
0.544
970921AG2-575 GEN
Solar/Wind Harmer
0.467
970921AG2-575 GEN
Solar/Wind Harmer
1.869
971067AG2-660 GEN
Solar/Wind Harmer
1.835
971171AH1-044 GEN
Solar/Wind Harmer
0.917
971177AH1-047 GEN
Solar/Wind Harmer
0.272
971333AH1-146 GEN
Solar/Wind Harmer
0.922
971335AH1-147 GEN
Solar/Wind Harmer
0.922
971341AH1-150 GEN
Solar/Wind Harmer
0.917
971343AH1-151 GEN
Solar/Wind Harmer
0.917
971411AH1-196 GEN
Solar/Wind Harmer
0.692
971475AH1-234 GEN
Solar/Wind Harmer
1.012
971573AH1-285 GEN
Solar/Wind Harmer
0.409
971675AH1-338 GEN
Solar/Wind Harmer
0.831
971681AH1-341 GEN
Solar/Wind Harmer
0.677
276157O29GEN1
Solar/Wind Harmer
6.523
276158O29GEN2
Solar/Wind Harmer
6.523
276174W4-005 GEN2
Solar/Wind Harmer
4.629
276656WTG2_EQ
Solar/Wind Harmer
1.086
276686W4-005 GEN3
Solar/Wind Harmer
4.629
276726Z2-087_GEN
Solar/Wind Harmer
12.389
276785W4-005 GEN1
Solar/Wind Harmer
4.629
939401AE1-172 GEN
Solar/Wind Harmer
19.281
939741AE1-205 GEN
Solar/Wind Harmer
0.953
941731AE2-173 GEN
Solar/Wind Harmer
4.765
957471AF2-041 GEN
Solar/Wind Harmer
1.376
957751AF2-069 GEN
Solar/Wind Harmer
0.597
963741AG1-226 GEN
Solar/Wind Harmer
2.69
963831AG1-236 GEN
Solar/Wind Harmer
13.013
963841AG1-237 GEN
Solar/Wind Harmer
19.463
965091AG1-374 GEN
Solar/Wind Harmer
1.419
965911AG1-460 GEN
Solar/Wind Harmer
1.083
971993AH1-541 GEN
Solar/Wind Harmer
0.43
971997AH1-543 GEN
Solar/Wind Harmer
0.743
972175AH1-670 GEN
Solar/Wind Harmer
18.29
274887GEN-1.85
Solar/Wind Harmer
9.12
939351AE1-166 GEN
Solar/Wind Harmer
0
942601AE2-276 GEN
50/50
8.32
943021AE2-325 GEN
Solar/Wind Harmer
2.857
943591AF1-030 GEN
Solar/Wind Harmer
0.478
945111AF1-176 GEN
Solar/Wind Harmer
0.81
945111AF1-176 GEN
Solar/Wind Harmer
4.415
959141AF2-205 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
0.489
960681AF2-359 GEN
Solar/Wind Harmer
0
961051AF2-396 GEN
Solar/Wind Harmer
0.911
961051AF2-396 GEN
Solar/Wind Harmer
7.285
970023AG2-014 GEN
50/50
2.676
970245AG2-165 GEN
Solar/Wind Harmer
1.382
970321AG2-212 GEN
Solar/Wind Harmer
1.382
970349AG2-230 GEN
Solar/Wind Harmer
0.755
970373AG2-245 GEN
Solar/Wind Harmer
1.207
970513AG2-328 GEN
Solar/Wind Harmer
1.382
970517AG2-330 GEN
Solar/Wind Harmer
21.56
970539AG2-343 GEN
50/50
9.325
970541AG2-344 GEN
50/50
10.171
970543AG2-345 GEN
50/50
4.663
970707AG2-453 GEN
Solar/Wind Harmer
1.365
970783AG2-492 GEN
50/50
2.676
970833AG2-524 GEN
Solar/Wind Harmer
0.533
970833AG2-524 GEN
Solar/Wind Harmer
4.261
970941AG2-585 GEN
Solar/Wind Harmer
0.611
971347AH1-153 GEN
Solar/Wind Harmer
0.755
971605AH1-302 GEN
Solar/Wind Harmer
9.72
971769AH1-391 GEN
Solar/Wind Harmer
0.494
971771AH1-392 GEN
Solar/Wind Harmer
0.427
971917AH1-482 GEN
Solar/Wind Harmer
9.694
972181SS23-001
Solar/Wind Harmer
0.495
972207SS24-0001
Solar/Wind Harmer
1.489
972231SS25-0005
Solar/Wind Harmer
0.792
270100X2-052 CT1
50/50
1.307
270101X2-052 CT2
50/50
1.307
270102X2-052 ST
50/50
1.415
276843GEN-1.7
Solar/Wind Harmer
0.808
940581AE2-045 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
0
958011AF2-095 GEN
Solar/Wind Harmer
0.704
958381AF2-132 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
0.642
965791AG1-447 GEN
Solar/Wind Harmer
5.65
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
339216AC1-074 GEN
Solar/Wind Helper
0.388
339243AC2-075 GEN1
Solar/Wind Helper
0.097
926823AC1-168 GEN
Solar/Wind Harmer
5.709
970901AG2-562 GEN
50/50
5.361
253325AC1-069 GEN
Solar/Wind Helper
0.129
253333AC1-068 GEN
Solar/Wind Helper
0.129
253338AC1-165 GEN
Solar/Wind Helper
0.129
253343AC1-166 GEN
Solar/Wind Helper
0.129
270186AC1-089 GEN
Solar/Wind Helper
0.592
276668AB2-070 GEN1
Solar/Wind Harmer
3.518
276708O09 GEN2
Solar/Wind Harmer
0.511
276741O09 GEN1
Solar/Wind Harmer
0.511
276763AC1-053 GEN1
Solar/Wind Harmer
6.025
276764AC1-053 GEN2
Solar/Wind Harmer
6.025
276782AC1-033 GEN
Solar/Wind Harmer
5.922
276848AB2-070 GEN3
Solar/Wind Harmer
3.519
276849AB2-070 GEN2
Solar/Wind Harmer
3.518
944201AF1-088_MTX
50/50
166.394
957141AF2-008_MTX
50/50
83.197
950031AG9-013
External Queue
6.4584832191467285
990742J1381
External Queue
1.0042113065719604
991082J1475 G
External Queue
0.3522087037563324
991112J1481
External Queue
1.0042113065719604
NYPJM->LTFIMP_NY
CLTF
1.069
WECLTFEXP_WEC->PJM
CLTF
2.979
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.252
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.761
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
10.008
BlueGrassPJM->LTFIMP_BlueG
CLTF
28.7
LAGNLTFEXP_LAGN->PJM
CLTF
2.048
CBM West 1LTFEXP_CBM-W1->PJM
CBM
80.627
CBM West 2LTFEXP_CBM-W2->PJM
CBM
34.635
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MECLTFEXP_MEC->PJM
CLTF
10.439
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
42.675

Details for 05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#709_05HANG R 765_D2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer
Contingency Name:
AEP_P4_#709_05HANG R 765_D2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.76 %
Rating:3276.0 MVA
Rating Type:B
MVA to Mitigate:3628.46
MW Contribution:5.36
Bus #Bus NameTypeMW Contribution
24690905MDL-1G C
Solar/Wind Harmer
17.617
24691005MDL-2G C
Solar/Wind Harmer
8.403
24697605MDL-3G C
Solar/Wind Harmer
8.389
24697905MDL-4G C
Solar/Wind Harmer
5.539
24344105CKG2
50/50
7.002
24344305RKG2
50/50
11.178
24344305RKG2
50/50
11.072
274847GR RIDGE ;BU
Solar/Wind Harmer
8.629
274848CAMPGROVE;RU
Solar/Wind Harmer
8.235
274851PROVIDENC;RU
Solar/Wind Harmer
4.321
274853TWINGROVE;U1
Solar/Wind Harmer
11.667
274854TWINGROVE;U2
Solar/Wind Harmer
11.544
274855GSG-6 ;RU
Solar/Wind Harmer
5.863
274856ECOGROVE ;U1
Solar/Wind Harmer
5.312
274861TOP CROP ;1U
Solar/Wind Harmer
9.404
274862TOP CROP ;2U
Solar/Wind Harmer
7.811
274871GR RIDGE ;2U
Solar/Wind Harmer
11.277
274877BISHOP HL;1U
Solar/Wind Harmer
5.242
274878BISHOP HL;2U
Solar/Wind Harmer
5.242
274879MINONK ;1U
Solar/Wind Harmer
11.068
274888KELLY CRK;1U
Solar/Wind Harmer
9.928
24344205RKG1
50/50
11.55
24344205RKG1
50/50
11.55
24385905FR-11G C
Solar/Wind Harmer
9.998
24386205FR-12G C
Solar/Wind Harmer
5.309
24386405FR-21G C
Solar/Wind Harmer
5.085
24386605FR-22G C
Solar/Wind Harmer
5.085
24387005FR-3G C
Solar/Wind Harmer
5.035
24387305FR-4G C
Solar/Wind Harmer
7.628
274849CRESCENT ;1U
Solar/Wind Harmer
2.986
276602WESTBROOK C
Solar/Wind Harmer
3.233
276603SUBLETTE C
Solar/Wind Harmer
1.533
24755605MDL-5G
Solar/Wind Harmer
5.539
252510AF1-249 C
Solar/Wind Helper
0.1
253303V4-073 C
Solar/Wind Helper
0.007
339211AE2-254 GEN
Solar/Wind Helper
0.205
25183208HLCRTG
Solar/Wind Helper
0.93
274850MENDOTA H;RU
Solar/Wind Harmer
4.153
276691AA1-018 GEN1
Solar/Wind Harmer
0.514
276694AA1-018 GEN2
Solar/Wind Harmer
9.207
274872LEEDK;1U
Solar/Wind Harmer
13.52
274872LEEDK;1U
Solar/Wind Harmer
0.205
276646AC1-214 GEN2
Solar/Wind Harmer
1.956
276645AC1-214 GEN1
Solar/Wind Harmer
1.956
276806AD2-047 C O1
Solar/Wind Harmer
15.063
276901AD2-066 C O1
Solar/Wind Harmer
0
276916AD2-100_GEN
Solar/Wind Harmer
0.946
276911AD2-131_GEN
Solar/Wind Harmer
0.225
276893AG1-478 C
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
50.226
253415AE1-040 GEN
Solar/Wind Helper
0.145
270180AB1-006 GEN1
Solar/Wind Harmer
15.742
270181AB1-006 GEN2
Solar/Wind Harmer
1.044
253394AE2-221_GEN
Solar/Wind Helper
0.568
253398AE2-221_GEN2
Solar/Wind Helper
0.568
252507AC2-088 GEN
Solar/Wind Helper
0.371
252509AD1-136 GEN
Solar/Wind Helper
0.053
252524AE2-267 GEN
Solar/Wind Helper
0.25
276889AE2-281 GEN
Solar/Wind Harmer
2.99
276872AE1-163_GEN1
Solar/Wind Harmer
10.464
276876AE1-163_GEN2
Solar/Wind Harmer
10.464
276882AE2-255 GEN
Solar/Wind Harmer
4.992
276868AE1-113 GEN
Solar/Wind Harmer
15.825
253432AC1-085 GEN2
Solar/Wind Helper
0.019
253433AC1-085 GEN1
Solar/Wind Helper
0.368
253316AC1-085 GEN3
Solar/Wind Helper
0.581
253317AC1-085 GEN4
Solar/Wind Helper
0.581
339221AD2-048_GEN
Solar/Wind Helper
0.335
339255AE2-071 GEN
Solar/Wind Helper
0.095
276621W2-048 GEN
Solar/Wind Harmer
9.936
276861AD2-134 GEN
Solar/Wind Harmer
2.834
276863AD2-134 GEN
Solar/Wind Harmer
2.834
339231AF1-038_GEN
Solar/Wind Helper
0.181
339236AF1-050_GEN
Solar/Wind Helper
0.186
270393AB1-087 CT1
50/50
2.616
270394AB1-087 ST1
50/50
2.616
270406AB1-088 CT1
50/50
2.616
270407AB1-088 ST1
50/50
2.616
339241AF1-083 GEN
Solar/Wind Helper
0.186
276655WTG1_EQ
Solar/Wind Harmer
8.205
241972AD1-140 GEN
Solar/Wind Helper
0.522
270340AC2-060 GEN
Solar/Wind Helper
0.361
270367AC2-061_GEN
Solar/Wind Helper
0.457
276838X2-022 GEN2
Solar/Wind Harmer
0.374
270449AD2-020 GEN
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
8.569
270505AE1-170 C O1
Solar/Wind Harmer
0.691
270518AE2-148 GEN
Solar/Wind Helper
1.497
270536AF1-215 GEN2
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
339250AF1-203 GEN
Solar/Wind Helper
0.054
253406AD2-031_GEN
Solar/Wind Helper
0.18
276615X2-022 GEN
Solar/Wind Harmer
3.149
24791305MDL-5G
Solar/Wind Harmer
5.539
274857EASY ROAD;U1
Solar/Wind Harmer
7.036
274858EASY ROAD;U2
Solar/Wind Harmer
7.036
274863CRW1-WTG
Solar/Wind Harmer
9.12
274864CRW2-WTG
Solar/Wind Harmer
9.12
274880W4-005 GEN4
Solar/Wind Harmer
4.629
339206AE1-143 GEN
Solar/Wind Helper
0.341
938861AE1-114 GEN
Solar/Wind Harmer
10.548
942111AE2-223 GEN
Solar/Wind Harmer
11.15
942481AE2-261 GEN
Solar/Wind Harmer
1.35
942991AE2-321 GEN
Solar/Wind Harmer
0.464
943111AE2-339 GEN
Solar/Wind Helper
0.179
943121AE2-341 GEN
Solar/Wind Harmer
0.717
944031AF1-071 GEN
Solar/Wind Helper
0.051
944221AF1-090 GEN
Solar/Wind Harmer
13.979
945391AF1-204 GEN
Solar/Wind Harmer
20.258
945421AF1-207 GEN
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
0.716
958491AF2-143 GEN
Solar/Wind Harmer
0.709
959081AF2-199 GEN
Solar/Wind Harmer
0.459
959091AF2-200 GEN
Solar/Wind Harmer
0.917
959341AF2-225 GEN
Solar/Wind Harmer
0.715
959611AF2-252 GEN
Solar/Wind Harmer
1.892
960611AF2-352 GEN
Solar/Wind Harmer
1.892
961491AF2-440 GEN
Solar/Wind Helper
0.187
962211AG1-066 GEN
Solar/Wind Helper
0.201
962581AG1-107 GEN
Solar/Wind Helper
0.562
962691AG1-118 GEN
Solar/Wind Harmer
1.405
962781AG1-127 GEN
Solar/Wind Harmer
0.444
966841AG1-555 GEN
Solar/Wind Harmer
0
970091AG2-072 GEN
50/50
218.112
970169AG2-114 GEN
Solar/Wind Harmer
0.48
970193AG2-126 GEN
Solar/Wind Harmer
0.764
970239AG2-162 GEN
Solar/Wind Harmer
1.982
970241AG2-163 GEN
Solar/Wind Harmer
1.494
970243AG2-164 GEN
Solar/Wind Harmer
4.654
970333AG2-219 GEN
Solar/Wind Harmer
5.688
970519AG2-331 GEN
Solar/Wind Harmer
53.778
970569AG2-363 GEN
Solar/Wind Harmer
1.39
970571AG2-364 GEN
Solar/Wind Harmer
0.926
970699AG2-449 GEN
Solar/Wind Harmer
2.068
970781AG2-491 GEN
Solar/Wind Harmer
0.669
970819AG2-516 GEN
Solar/Wind Harmer
0.544
970921AG2-575 GEN
Solar/Wind Harmer
0.467
970921AG2-575 GEN
Solar/Wind Harmer
1.869
971067AG2-660 GEN
Solar/Wind Harmer
1.835
971171AH1-044 GEN
Solar/Wind Harmer
0.917
971177AH1-047 GEN
Solar/Wind Harmer
0.272
971333AH1-146 GEN
Solar/Wind Harmer
0.922
971335AH1-147 GEN
Solar/Wind Harmer
0.922
971341AH1-150 GEN
Solar/Wind Harmer
0.917
971343AH1-151 GEN
Solar/Wind Harmer
0.917
971411AH1-196 GEN
Solar/Wind Harmer
0.692
971475AH1-234 GEN
Solar/Wind Harmer
1.012
971573AH1-285 GEN
Solar/Wind Harmer
0.409
971675AH1-338 GEN
Solar/Wind Harmer
0.831
971681AH1-341 GEN
Solar/Wind Harmer
0.677
276157O29GEN1
Solar/Wind Harmer
6.523
276158O29GEN2
Solar/Wind Harmer
6.523
276174W4-005 GEN2
Solar/Wind Harmer
4.629
276656WTG2_EQ
Solar/Wind Harmer
1.086
276686W4-005 GEN3
Solar/Wind Harmer
4.629
276726Z2-087_GEN
Solar/Wind Harmer
12.389
276785W4-005 GEN1
Solar/Wind Harmer
4.629
939401AE1-172 GEN
Solar/Wind Harmer
19.281
939741AE1-205 GEN
Solar/Wind Harmer
0.953
941731AE2-173 GEN
Solar/Wind Harmer
4.765
957471AF2-041 GEN
Solar/Wind Harmer
1.376
957751AF2-069 GEN
Solar/Wind Harmer
0.597
963741AG1-226 GEN
Solar/Wind Harmer
2.69
963831AG1-236 GEN
Solar/Wind Harmer
13.013
963841AG1-237 GEN
Solar/Wind Harmer
19.463
965091AG1-374 GEN
Solar/Wind Harmer
1.419
965911AG1-460 GEN
Solar/Wind Harmer
1.083
971993AH1-541 GEN
Solar/Wind Harmer
0.43
971997AH1-543 GEN
Solar/Wind Harmer
0.743
972175AH1-670 GEN
Solar/Wind Harmer
18.29
274887GEN-1.85
Solar/Wind Harmer
9.12
939351AE1-166 GEN
Solar/Wind Harmer
0
942601AE2-276 GEN
50/50
8.32
943021AE2-325 GEN
Solar/Wind Harmer
2.857
943591AF1-030 GEN
Solar/Wind Harmer
0.478
945111AF1-176 GEN
Solar/Wind Harmer
0.81
945111AF1-176 GEN
Solar/Wind Harmer
4.415
959141AF2-205 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
0.489
960681AF2-359 GEN
Solar/Wind Harmer
0
961051AF2-396 GEN
Solar/Wind Harmer
0.911
961051AF2-396 GEN
Solar/Wind Harmer
7.285
970023AG2-014 GEN
50/50
2.676
970245AG2-165 GEN
Solar/Wind Harmer
1.382
970321AG2-212 GEN
Solar/Wind Harmer
1.382
970349AG2-230 GEN
Solar/Wind Harmer
0.755
970373AG2-245 GEN
Solar/Wind Harmer
1.207
970513AG2-328 GEN
Solar/Wind Harmer
1.382
970517AG2-330 GEN
Solar/Wind Harmer
21.56
970539AG2-343 GEN
50/50
9.325
970541AG2-344 GEN
50/50
10.171
970543AG2-345 GEN
50/50
4.663
970707AG2-453 GEN
Solar/Wind Harmer
1.365
970783AG2-492 GEN
50/50
2.676
970833AG2-524 GEN
Solar/Wind Harmer
0.533
970833AG2-524 GEN
Solar/Wind Harmer
4.261
970941AG2-585 GEN
Solar/Wind Harmer
0.611
971347AH1-153 GEN
Solar/Wind Harmer
0.755
971605AH1-302 GEN
Solar/Wind Harmer
9.72
971769AH1-391 GEN
Solar/Wind Harmer
0.494
971771AH1-392 GEN
Solar/Wind Harmer
0.427
971917AH1-482 GEN
Solar/Wind Harmer
9.694
972181SS23-001
Solar/Wind Harmer
0.495
972207SS24-0001
Solar/Wind Harmer
1.489
972231SS25-0005
Solar/Wind Harmer
0.792
270100X2-052 CT1
50/50
1.307
270101X2-052 CT2
50/50
1.307
270102X2-052 ST
50/50
1.415
276843GEN-1.7
Solar/Wind Harmer
0.808
940581AE2-045 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
0
958011AF2-095 GEN
Solar/Wind Harmer
0.704
958381AF2-132 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
0.642
965791AG1-447 GEN
Solar/Wind Harmer
5.65
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
339216AC1-074 GEN
Solar/Wind Helper
0.388
339243AC2-075 GEN1
Solar/Wind Helper
0.097
926823AC1-168 GEN
Solar/Wind Harmer
5.709
970901AG2-562 GEN
50/50
5.361
253325AC1-069 GEN
Solar/Wind Helper
0.129
253333AC1-068 GEN
Solar/Wind Helper
0.129
253338AC1-165 GEN
Solar/Wind Helper
0.129
253343AC1-166 GEN
Solar/Wind Helper
0.129
270186AC1-089 GEN
Solar/Wind Helper
0.592
276668AB2-070 GEN1
Solar/Wind Harmer
3.518
276708O09 GEN2
Solar/Wind Harmer
0.511
276741O09 GEN1
Solar/Wind Harmer
0.511
276763AC1-053 GEN1
Solar/Wind Harmer
6.025
276764AC1-053 GEN2
Solar/Wind Harmer
6.025
276782AC1-033 GEN
Solar/Wind Harmer
5.922
276848AB2-070 GEN3
Solar/Wind Harmer
3.519
276849AB2-070 GEN2
Solar/Wind Harmer
3.518
944201AF1-088_MTX
50/50
166.394
957141AF2-008_MTX
50/50
83.197
950031AG9-013
External Queue
6.4584832191467285
990742J1381
External Queue
1.0042113065719604
991082J1475 G
External Queue
0.3522087037563324
991112J1481
External Queue
1.0042113065719604
NYPJM->LTFIMP_NY
CLTF
1.069
WECLTFEXP_WEC->PJM
CLTF
2.979
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.252
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.761
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
10.008
BlueGrassPJM->LTFIMP_BlueG
CLTF
28.7
LAGNLTFEXP_LAGN->PJM
CLTF
2.048
CBM West 1LTFEXP_CBM-W1->PJM
CBM
80.627
CBM West 2LTFEXP_CBM-W2->PJM
CBM
34.635
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MECLTFEXP_MEC->PJM
CLTF
10.439
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
42.675

Details for 05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1_SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#6189_05HANG R 765_D1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.71 %
Rating:2991.0 MVA
Rating Type:B
MVA to Mitigate:3640.25
MW Contribution:5.34
Bus #Bus NameTypeMW Contribution
24690905MDL-1G C
Solar/Wind Harmer
17.566
24691005MDL-2G C
Solar/Wind Harmer
8.379
24697605MDL-3G C
Solar/Wind Harmer
8.366
24697905MDL-4G C
Solar/Wind Harmer
5.524
24344105CKG2
50/50
6.976
24344305RKG2
50/50
11.164
24344305RKG2
50/50
11.059
274847GR RIDGE ;BU
Solar/Wind Harmer
8.595
274848CAMPGROVE;RU
Solar/Wind Harmer
8.2
274851PROVIDENC;RU
Solar/Wind Harmer
4.303
274853TWINGROVE;U1
Solar/Wind Harmer
11.619
274854TWINGROVE;U2
Solar/Wind Harmer
11.497
274855GSG-6 ;RU
Solar/Wind Harmer
5.839
274856ECOGROVE ;U1
Solar/Wind Harmer
5.289
274861TOP CROP ;1U
Solar/Wind Harmer
9.366
274862TOP CROP ;2U
Solar/Wind Harmer
7.78
274871GR RIDGE ;2U
Solar/Wind Harmer
11.232
274877BISHOP HL;1U
Solar/Wind Harmer
5.22
274878BISHOP HL;2U
Solar/Wind Harmer
5.22
274879MINONK ;1U
Solar/Wind Harmer
11.023
274888KELLY CRK;1U
Solar/Wind Harmer
9.889
24344205RKG1
50/50
11.535
24344205RKG1
50/50
11.535
24385905FR-11G C
Solar/Wind Harmer
9.968
24386205FR-12G C
Solar/Wind Harmer
5.294
24386405FR-21G C
Solar/Wind Harmer
5.071
24386605FR-22G C
Solar/Wind Harmer
5.071
24387005FR-3G C
Solar/Wind Harmer
5.02
24387305FR-4G C
Solar/Wind Harmer
7.606
274849CRESCENT ;1U
Solar/Wind Harmer
2.974
276602WESTBROOK C
Solar/Wind Harmer
3.22
276603SUBLETTE C
Solar/Wind Harmer
1.527
24755605MDL-5G
Solar/Wind Harmer
5.524
252510AF1-249 C
Solar/Wind Helper
0.1
253303V4-073 C
Solar/Wind Helper
0.007
339211AE2-254 GEN
Solar/Wind Helper
0.206
25183208HLCRTG
Solar/Wind Helper
0.934
274850MENDOTA H;RU
Solar/Wind Harmer
4.136
276691AA1-018 GEN1
Solar/Wind Harmer
0.512
276694AA1-018 GEN2
Solar/Wind Harmer
9.17
274872LEEDK;1U
Solar/Wind Harmer
13.465
274872LEEDK;1U
Solar/Wind Harmer
0.204
276646AC1-214 GEN2
Solar/Wind Harmer
1.948
276645AC1-214 GEN1
Solar/Wind Harmer
1.948
276806AD2-047 C O1
Solar/Wind Harmer
15.004
276901AD2-066 C O1
Solar/Wind Harmer
0
276916AD2-100_GEN
Solar/Wind Harmer
0.942
276911AD2-131_GEN
Solar/Wind Harmer
0.224
276893AG1-478 C
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
50.03
253415AE1-040 GEN
Solar/Wind Helper
0.146
270180AB1-006 GEN1
Solar/Wind Harmer
15.697
270181AB1-006 GEN2
Solar/Wind Harmer
1.041
253394AE2-221_GEN
Solar/Wind Helper
0.571
253398AE2-221_GEN2
Solar/Wind Helper
0.571
252507AC2-088 GEN
Solar/Wind Helper
0.372
252509AD1-136 GEN
Solar/Wind Helper
0.053
252524AE2-267 GEN
Solar/Wind Helper
0.251
276889AE2-281 GEN
Solar/Wind Harmer
2.978
276872AE1-163_GEN1
Solar/Wind Harmer
10.422
276876AE1-163_GEN2
Solar/Wind Harmer
10.422
276882AE2-255 GEN
Solar/Wind Harmer
4.972
276868AE1-113 GEN
Solar/Wind Harmer
15.761
253432AC1-085 GEN2
Solar/Wind Helper
0.019
253433AC1-085 GEN1
Solar/Wind Helper
0.37
253316AC1-085 GEN3
Solar/Wind Helper
0.584
253317AC1-085 GEN4
Solar/Wind Helper
0.584
339221AD2-048_GEN
Solar/Wind Helper
0.336
339255AE2-071 GEN
Solar/Wind Helper
0.096
276621W2-048 GEN
Solar/Wind Harmer
9.894
276861AD2-134 GEN
Solar/Wind Harmer
2.823
276863AD2-134 GEN
Solar/Wind Harmer
2.823
339231AF1-038_GEN
Solar/Wind Helper
0.182
339236AF1-050_GEN
Solar/Wind Helper
0.187
270393AB1-087 CT1
50/50
2.61
270394AB1-087 ST1
50/50
2.61
270406AB1-088 CT1
50/50
2.61
270407AB1-088 ST1
50/50
2.61
339241AF1-083 GEN
Solar/Wind Helper
0.187
276655WTG1_EQ
Solar/Wind Harmer
8.172
241972AD1-140 GEN
Solar/Wind Helper
0.525
270340AC2-060 GEN
Solar/Wind Helper
0.363
270367AC2-061_GEN
Solar/Wind Helper
0.459
276838X2-022 GEN2
Solar/Wind Harmer
0.372
270449AD2-020 GEN
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
8.535
270505AE1-170 C O1
Solar/Wind Harmer
0.688
270518AE2-148 GEN
Solar/Wind Helper
1.508
270536AF1-215 GEN2
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
339250AF1-203 GEN
Solar/Wind Helper
0.055
253406AD2-031_GEN
Solar/Wind Helper
0.181
276615X2-022 GEN
Solar/Wind Harmer
3.136
24791305MDL-5G
Solar/Wind Harmer
5.524
274857EASY ROAD;U1
Solar/Wind Harmer
7.006
274858EASY ROAD;U2
Solar/Wind Harmer
7.006
274863CRW1-WTG
Solar/Wind Harmer
9.084
274864CRW2-WTG
Solar/Wind Harmer
9.084
274880W4-005 GEN4
Solar/Wind Harmer
4.61
339206AE1-143 GEN
Solar/Wind Helper
0.343
938861AE1-114 GEN
Solar/Wind Harmer
10.503
942111AE2-223 GEN
Solar/Wind Harmer
11.105
942481AE2-261 GEN
Solar/Wind Harmer
1.344
942991AE2-321 GEN
Solar/Wind Harmer
0.462
943111AE2-339 GEN
Solar/Wind Helper
0.18
943121AE2-341 GEN
Solar/Wind Harmer
0.714
944031AF1-071 GEN
Solar/Wind Helper
0.052
944221AF1-090 GEN
Solar/Wind Harmer
13.919
945391AF1-204 GEN
Solar/Wind Harmer
20.182
945421AF1-207 GEN
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
0.713
958491AF2-143 GEN
Solar/Wind Harmer
0.707
959081AF2-199 GEN
Solar/Wind Harmer
0.457
959091AF2-200 GEN
Solar/Wind Harmer
0.913
959341AF2-225 GEN
Solar/Wind Harmer
0.712
959611AF2-252 GEN
Solar/Wind Harmer
1.884
960611AF2-352 GEN
Solar/Wind Harmer
1.884
961491AF2-440 GEN
Solar/Wind Helper
0.188
962211AG1-066 GEN
Solar/Wind Helper
0.203
962581AG1-107 GEN
Solar/Wind Helper
0.564
962691AG1-118 GEN
Solar/Wind Harmer
1.4
962781AG1-127 GEN
Solar/Wind Harmer
0.443
966841AG1-555 GEN
Solar/Wind Harmer
0
970091AG2-072 GEN
50/50
217.845
970169AG2-114 GEN
Solar/Wind Harmer
0.478
970193AG2-126 GEN
Solar/Wind Harmer
0.761
970239AG2-162 GEN
Solar/Wind Harmer
1.98
970241AG2-163 GEN
Solar/Wind Harmer
1.49
970243AG2-164 GEN
Solar/Wind Harmer
4.649
970333AG2-219 GEN
Solar/Wind Harmer
5.682
970519AG2-331 GEN
Solar/Wind Harmer
53.719
970569AG2-363 GEN
Solar/Wind Harmer
1.384
970571AG2-364 GEN
Solar/Wind Harmer
0.923
970699AG2-449 GEN
Solar/Wind Harmer
2.066
970781AG2-491 GEN
Solar/Wind Harmer
0.667
970819AG2-516 GEN
Solar/Wind Harmer
0.542
970921AG2-575 GEN
Solar/Wind Harmer
0.465
970921AG2-575 GEN
Solar/Wind Harmer
1.861
971067AG2-660 GEN
Solar/Wind Harmer
1.827
971171AH1-044 GEN
Solar/Wind Harmer
0.913
971177AH1-047 GEN
Solar/Wind Harmer
0.27
971333AH1-146 GEN
Solar/Wind Harmer
0.918
971335AH1-147 GEN
Solar/Wind Harmer
0.918
971341AH1-150 GEN
Solar/Wind Harmer
0.913
971343AH1-151 GEN
Solar/Wind Harmer
0.913
971411AH1-196 GEN
Solar/Wind Harmer
0.689
971475AH1-234 GEN
Solar/Wind Harmer
1.008
971573AH1-285 GEN
Solar/Wind Harmer
0.407
971675AH1-338 GEN
Solar/Wind Harmer
0.828
971681AH1-341 GEN
Solar/Wind Harmer
0.674
276157O29GEN1
Solar/Wind Harmer
6.495
276158O29GEN2
Solar/Wind Harmer
6.495
276174W4-005 GEN2
Solar/Wind Harmer
4.61
276656WTG2_EQ
Solar/Wind Harmer
1.082
276686W4-005 GEN3
Solar/Wind Harmer
4.61
276726Z2-087_GEN
Solar/Wind Harmer
12.339
276785W4-005 GEN1
Solar/Wind Harmer
4.61
939401AE1-172 GEN
Solar/Wind Harmer
19.205
939741AE1-205 GEN
Solar/Wind Harmer
0.949
941731AE2-173 GEN
Solar/Wind Harmer
4.746
957471AF2-041 GEN
Solar/Wind Harmer
1.37
957751AF2-069 GEN
Solar/Wind Harmer
0.595
963741AG1-226 GEN
Solar/Wind Harmer
2.681
963831AG1-236 GEN
Solar/Wind Harmer
12.96
963841AG1-237 GEN
Solar/Wind Harmer
19.403
965091AG1-374 GEN
Solar/Wind Harmer
1.413
965911AG1-460 GEN
Solar/Wind Harmer
1.079
971993AH1-541 GEN
Solar/Wind Harmer
0.428
971997AH1-543 GEN
Solar/Wind Harmer
0.74
972175AH1-670 GEN
Solar/Wind Harmer
18.216
274887GEN-1.85
Solar/Wind Harmer
9.084
939351AE1-166 GEN
Solar/Wind Harmer
0
942601AE2-276 GEN
50/50
8.301
943021AE2-325 GEN
Solar/Wind Harmer
2.845
943591AF1-030 GEN
Solar/Wind Harmer
0.476
945111AF1-176 GEN
Solar/Wind Harmer
0.807
945111AF1-176 GEN
Solar/Wind Harmer
4.397
959141AF2-205 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
0.487
960681AF2-359 GEN
Solar/Wind Harmer
0
961051AF2-396 GEN
Solar/Wind Harmer
0.907
961051AF2-396 GEN
Solar/Wind Harmer
7.254
970023AG2-014 GEN
50/50
2.668
970245AG2-165 GEN
Solar/Wind Harmer
1.378
970321AG2-212 GEN
Solar/Wind Harmer
1.378
970349AG2-230 GEN
Solar/Wind Harmer
0.752
970373AG2-245 GEN
Solar/Wind Harmer
1.203
970513AG2-328 GEN
Solar/Wind Harmer
1.378
970517AG2-330 GEN
Solar/Wind Harmer
21.5
970539AG2-343 GEN
50/50
9.296
970541AG2-344 GEN
50/50
10.141
970543AG2-345 GEN
50/50
4.648
970707AG2-453 GEN
Solar/Wind Harmer
1.36
970783AG2-492 GEN
50/50
2.668
970833AG2-524 GEN
Solar/Wind Harmer
0.53
970833AG2-524 GEN
Solar/Wind Harmer
4.244
970941AG2-585 GEN
Solar/Wind Harmer
0.609
971347AH1-153 GEN
Solar/Wind Harmer
0.752
971605AH1-302 GEN
Solar/Wind Harmer
9.691
971769AH1-391 GEN
Solar/Wind Harmer
0.492
971771AH1-392 GEN
Solar/Wind Harmer
0.425
971917AH1-482 GEN
Solar/Wind Harmer
9.665
972181SS23-001
Solar/Wind Harmer
0.493
972207SS24-0001
Solar/Wind Harmer
1.483
972231SS25-0005
Solar/Wind Harmer
0.788
270100X2-052 CT1
50/50
1.302
270101X2-052 CT2
50/50
1.302
270102X2-052 ST
50/50
1.41
276843GEN-1.7
Solar/Wind Harmer
0.805
940581AE2-045 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
0
958011AF2-095 GEN
Solar/Wind Harmer
0.701
958381AF2-132 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
0.64
965791AG1-447 GEN
Solar/Wind Harmer
5.629
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
339216AC1-074 GEN
Solar/Wind Helper
0.389
339243AC2-075 GEN1
Solar/Wind Helper
0.097
926823AC1-168 GEN
Solar/Wind Harmer
5.686
970901AG2-562 GEN
50/50
5.341
253325AC1-069 GEN
Solar/Wind Helper
0.13
253333AC1-068 GEN
Solar/Wind Helper
0.13
253338AC1-165 GEN
Solar/Wind Helper
0.13
253343AC1-166 GEN
Solar/Wind Helper
0.13
270186AC1-089 GEN
Solar/Wind Helper
0.595
276668AB2-070 GEN1
Solar/Wind Harmer
3.504
276708O09 GEN2
Solar/Wind Harmer
0.509
276741O09 GEN1
Solar/Wind Harmer
0.509
276763AC1-053 GEN1
Solar/Wind Harmer
6
276764AC1-053 GEN2
Solar/Wind Harmer
6
276782AC1-033 GEN
Solar/Wind Harmer
5.897
276848AB2-070 GEN3
Solar/Wind Harmer
3.504
276849AB2-070 GEN2
Solar/Wind Harmer
3.504
944201AF1-088_MTX
50/50
166.013
957141AF2-008_MTX
50/50
83.006
950031AG9-013
External Queue
6.4584832191467285
990742J1381
External Queue
1.0042113065719604
991082J1475 G
External Queue
0.3522087037563324
991112J1481
External Queue
1.0042113065719604
NYPJM->LTFIMP_NY
CLTF
1.09
WECLTFEXP_WEC->PJM
CLTF
2.966
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.274
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.774
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
10.03
BlueGrassPJM->LTFIMP_BlueG
CLTF
28.766
LAGNLTFEXP_LAGN->PJM
CLTF
1.981
CBM West 1LTFEXP_CBM-W1->PJM
CBM
80.147
CBM West 2LTFEXP_CBM-W2->PJM
CBM
34.191
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MECLTFEXP_MEC->PJM
CLTF
10.384
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.311
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
42.675

Details for 05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P4_#709_05HANG R 765_D2_SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#709_05HANG R 765_D2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.0 %
Rating:2991.0 MVA
Rating Type:B
MVA to Mitigate:3589.25
MW Contribution:5.36
Bus #Bus NameTypeMW Contribution
24690905MDL-1G C
Solar/Wind Harmer
17.617
24691005MDL-2G C
Solar/Wind Harmer
8.403
24697605MDL-3G C
Solar/Wind Harmer
8.389
24697905MDL-4G C
Solar/Wind Harmer
5.539
24344105CKG2
50/50
7.002
24344305RKG2
50/50
11.178
24344305RKG2
50/50
11.072
274847GR RIDGE ;BU
Solar/Wind Harmer
8.629
274848CAMPGROVE;RU
Solar/Wind Harmer
8.235
274851PROVIDENC;RU
Solar/Wind Harmer
4.321
274853TWINGROVE;U1
Solar/Wind Harmer
11.667
274854TWINGROVE;U2
Solar/Wind Harmer
11.544
274855GSG-6 ;RU
Solar/Wind Harmer
5.863
274856ECOGROVE ;U1
Solar/Wind Harmer
5.312
274861TOP CROP ;1U
Solar/Wind Harmer
9.404
274862TOP CROP ;2U
Solar/Wind Harmer
7.811
274871GR RIDGE ;2U
Solar/Wind Harmer
11.277
274877BISHOP HL;1U
Solar/Wind Harmer
5.242
274878BISHOP HL;2U
Solar/Wind Harmer
5.242
274879MINONK ;1U
Solar/Wind Harmer
11.068
274888KELLY CRK;1U
Solar/Wind Harmer
9.928
24344205RKG1
50/50
11.55
24344205RKG1
50/50
11.55
24385905FR-11G C
Solar/Wind Harmer
9.998
24386205FR-12G C
Solar/Wind Harmer
5.309
24386405FR-21G C
Solar/Wind Harmer
5.085
24386605FR-22G C
Solar/Wind Harmer
5.085
24387005FR-3G C
Solar/Wind Harmer
5.035
24387305FR-4G C
Solar/Wind Harmer
7.628
274849CRESCENT ;1U
Solar/Wind Harmer
2.986
276602WESTBROOK C
Solar/Wind Harmer
3.233
276603SUBLETTE C
Solar/Wind Harmer
1.533
24755605MDL-5G
Solar/Wind Harmer
5.539
252510AF1-249 C
Solar/Wind Helper
0.1
253303V4-073 C
Solar/Wind Helper
0.007
339211AE2-254 GEN
Solar/Wind Helper
0.205
25183208HLCRTG
Solar/Wind Helper
0.93
274850MENDOTA H;RU
Solar/Wind Harmer
4.153
276691AA1-018 GEN1
Solar/Wind Harmer
0.514
276694AA1-018 GEN2
Solar/Wind Harmer
9.207
274872LEEDK;1U
Solar/Wind Harmer
13.52
274872LEEDK;1U
Solar/Wind Harmer
0.205
276646AC1-214 GEN2
Solar/Wind Harmer
1.956
276645AC1-214 GEN1
Solar/Wind Harmer
1.956
276806AD2-047 C O1
Solar/Wind Harmer
15.063
276901AD2-066 C O1
Solar/Wind Harmer
0
276916AD2-100_GEN
Solar/Wind Harmer
0.946
276911AD2-131_GEN
Solar/Wind Harmer
0.225
276893AG1-478 C
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
50.226
253415AE1-040 GEN
Solar/Wind Helper
0.145
270180AB1-006 GEN1
Solar/Wind Harmer
15.742
270181AB1-006 GEN2
Solar/Wind Harmer
1.044
253394AE2-221_GEN
Solar/Wind Helper
0.568
253398AE2-221_GEN2
Solar/Wind Helper
0.568
252507AC2-088 GEN
Solar/Wind Helper
0.371
252509AD1-136 GEN
Solar/Wind Helper
0.053
252524AE2-267 GEN
Solar/Wind Helper
0.25
276889AE2-281 GEN
Solar/Wind Harmer
2.99
276872AE1-163_GEN1
Solar/Wind Harmer
10.464
276876AE1-163_GEN2
Solar/Wind Harmer
10.464
276882AE2-255 GEN
Solar/Wind Harmer
4.992
276868AE1-113 GEN
Solar/Wind Harmer
15.825
253432AC1-085 GEN2
Solar/Wind Helper
0.019
253433AC1-085 GEN1
Solar/Wind Helper
0.368
253316AC1-085 GEN3
Solar/Wind Helper
0.581
253317AC1-085 GEN4
Solar/Wind Helper
0.581
339221AD2-048_GEN
Solar/Wind Helper
0.335
339255AE2-071 GEN
Solar/Wind Helper
0.095
276621W2-048 GEN
Solar/Wind Harmer
9.936
276861AD2-134 GEN
Solar/Wind Harmer
2.834
276863AD2-134 GEN
Solar/Wind Harmer
2.834
339231AF1-038_GEN
Solar/Wind Helper
0.181
339236AF1-050_GEN
Solar/Wind Helper
0.186
270393AB1-087 CT1
50/50
2.616
270394AB1-087 ST1
50/50
2.616
270406AB1-088 CT1
50/50
2.616
270407AB1-088 ST1
50/50
2.616
339241AF1-083 GEN
Solar/Wind Helper
0.186
276655WTG1_EQ
Solar/Wind Harmer
8.205
241972AD1-140 GEN
Solar/Wind Helper
0.522
270340AC2-060 GEN
Solar/Wind Helper
0.361
270367AC2-061_GEN
Solar/Wind Helper
0.457
276838X2-022 GEN2
Solar/Wind Harmer
0.374
270449AD2-020 GEN
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
8.569
270505AE1-170 C O1
Solar/Wind Harmer
0.691
270518AE2-148 GEN
Solar/Wind Helper
1.497
270536AF1-215 GEN2
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
339250AF1-203 GEN
Solar/Wind Helper
0.054
253406AD2-031_GEN
Solar/Wind Helper
0.18
276615X2-022 GEN
Solar/Wind Harmer
3.149
24791305MDL-5G
Solar/Wind Harmer
5.539
274857EASY ROAD;U1
Solar/Wind Harmer
7.036
274858EASY ROAD;U2
Solar/Wind Harmer
7.036
274863CRW1-WTG
Solar/Wind Harmer
9.12
274864CRW2-WTG
Solar/Wind Harmer
9.12
274880W4-005 GEN4
Solar/Wind Harmer
4.629
339206AE1-143 GEN
Solar/Wind Helper
0.341
938861AE1-114 GEN
Solar/Wind Harmer
10.548
942111AE2-223 GEN
Solar/Wind Harmer
11.15
942481AE2-261 GEN
Solar/Wind Harmer
1.35
942991AE2-321 GEN
Solar/Wind Harmer
0.464
943111AE2-339 GEN
Solar/Wind Helper
0.179
943121AE2-341 GEN
Solar/Wind Harmer
0.717
944031AF1-071 GEN
Solar/Wind Helper
0.051
944221AF1-090 GEN
Solar/Wind Harmer
13.979
945391AF1-204 GEN
Solar/Wind Harmer
20.258
945421AF1-207 GEN
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
0.716
958491AF2-143 GEN
Solar/Wind Harmer
0.709
959081AF2-199 GEN
Solar/Wind Harmer
0.459
959091AF2-200 GEN
Solar/Wind Harmer
0.917
959341AF2-225 GEN
Solar/Wind Harmer
0.715
959611AF2-252 GEN
Solar/Wind Harmer
1.892
960611AF2-352 GEN
Solar/Wind Harmer
1.892
961491AF2-440 GEN
Solar/Wind Helper
0.187
962211AG1-066 GEN
Solar/Wind Helper
0.201
962581AG1-107 GEN
Solar/Wind Helper
0.562
962691AG1-118 GEN
Solar/Wind Harmer
1.405
962781AG1-127 GEN
Solar/Wind Harmer
0.444
966841AG1-555 GEN
Solar/Wind Harmer
0
970091AG2-072 GEN
50/50
218.112
970169AG2-114 GEN
Solar/Wind Harmer
0.48
970193AG2-126 GEN
Solar/Wind Harmer
0.764
970239AG2-162 GEN
Solar/Wind Harmer
1.982
970241AG2-163 GEN
Solar/Wind Harmer
1.494
970243AG2-164 GEN
Solar/Wind Harmer
4.654
970333AG2-219 GEN
Solar/Wind Harmer
5.688
970519AG2-331 GEN
Solar/Wind Harmer
53.778
970569AG2-363 GEN
Solar/Wind Harmer
1.39
970571AG2-364 GEN
Solar/Wind Harmer
0.926
970699AG2-449 GEN
Solar/Wind Harmer
2.068
970781AG2-491 GEN
Solar/Wind Harmer
0.669
970819AG2-516 GEN
Solar/Wind Harmer
0.544
970921AG2-575 GEN
Solar/Wind Harmer
0.467
970921AG2-575 GEN
Solar/Wind Harmer
1.869
971067AG2-660 GEN
Solar/Wind Harmer
1.835
971171AH1-044 GEN
Solar/Wind Harmer
0.917
971177AH1-047 GEN
Solar/Wind Harmer
0.272
971333AH1-146 GEN
Solar/Wind Harmer
0.922
971335AH1-147 GEN
Solar/Wind Harmer
0.922
971341AH1-150 GEN
Solar/Wind Harmer
0.917
971343AH1-151 GEN
Solar/Wind Harmer
0.917
971411AH1-196 GEN
Solar/Wind Harmer
0.692
971475AH1-234 GEN
Solar/Wind Harmer
1.012
971573AH1-285 GEN
Solar/Wind Harmer
0.409
971675AH1-338 GEN
Solar/Wind Harmer
0.831
971681AH1-341 GEN
Solar/Wind Harmer
0.677
276157O29GEN1
Solar/Wind Harmer
6.523
276158O29GEN2
Solar/Wind Harmer
6.523
276174W4-005 GEN2
Solar/Wind Harmer
4.629
276656WTG2_EQ
Solar/Wind Harmer
1.086
276686W4-005 GEN3
Solar/Wind Harmer
4.629
276726Z2-087_GEN
Solar/Wind Harmer
12.389
276785W4-005 GEN1
Solar/Wind Harmer
4.629
939401AE1-172 GEN
Solar/Wind Harmer
19.281
939741AE1-205 GEN
Solar/Wind Harmer
0.953
941731AE2-173 GEN
Solar/Wind Harmer
4.765
957471AF2-041 GEN
Solar/Wind Harmer
1.376
957751AF2-069 GEN
Solar/Wind Harmer
0.597
963741AG1-226 GEN
Solar/Wind Harmer
2.69
963831AG1-236 GEN
Solar/Wind Harmer
13.013
963841AG1-237 GEN
Solar/Wind Harmer
19.463
965091AG1-374 GEN
Solar/Wind Harmer
1.419
965911AG1-460 GEN
Solar/Wind Harmer
1.083
971993AH1-541 GEN
Solar/Wind Harmer
0.43
971997AH1-543 GEN
Solar/Wind Harmer
0.743
972175AH1-670 GEN
Solar/Wind Harmer
18.29
274887GEN-1.85
Solar/Wind Harmer
9.12
939351AE1-166 GEN
Solar/Wind Harmer
0
942601AE2-276 GEN
50/50
8.32
943021AE2-325 GEN
Solar/Wind Harmer
2.857
943591AF1-030 GEN
Solar/Wind Harmer
0.478
945111AF1-176 GEN
Solar/Wind Harmer
0.81
945111AF1-176 GEN
Solar/Wind Harmer
4.415
959141AF2-205 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
0.489
960681AF2-359 GEN
Solar/Wind Harmer
0
961051AF2-396 GEN
Solar/Wind Harmer
0.911
961051AF2-396 GEN
Solar/Wind Harmer
7.285
970023AG2-014 GEN
50/50
2.676
970245AG2-165 GEN
Solar/Wind Harmer
1.382
970321AG2-212 GEN
Solar/Wind Harmer
1.382
970349AG2-230 GEN
Solar/Wind Harmer
0.755
970373AG2-245 GEN
Solar/Wind Harmer
1.207
970513AG2-328 GEN
Solar/Wind Harmer
1.382
970517AG2-330 GEN
Solar/Wind Harmer
21.56
970539AG2-343 GEN
50/50
9.325
970541AG2-344 GEN
50/50
10.171
970543AG2-345 GEN
50/50
4.663
970707AG2-453 GEN
Solar/Wind Harmer
1.365
970783AG2-492 GEN
50/50
2.676
970833AG2-524 GEN
Solar/Wind Harmer
0.533
970833AG2-524 GEN
Solar/Wind Harmer
4.261
970941AG2-585 GEN
Solar/Wind Harmer
0.611
971347AH1-153 GEN
Solar/Wind Harmer
0.755
971605AH1-302 GEN
Solar/Wind Harmer
9.72
971769AH1-391 GEN
Solar/Wind Harmer
0.494
971771AH1-392 GEN
Solar/Wind Harmer
0.427
971917AH1-482 GEN
Solar/Wind Harmer
9.694
972181SS23-001
Solar/Wind Harmer
0.495
972207SS24-0001
Solar/Wind Harmer
1.489
972231SS25-0005
Solar/Wind Harmer
0.792
270100X2-052 CT1
50/50
1.307
270101X2-052 CT2
50/50
1.307
270102X2-052 ST
50/50
1.415
276843GEN-1.7
Solar/Wind Harmer
0.808
940581AE2-045 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
0
958011AF2-095 GEN
Solar/Wind Harmer
0.704
958381AF2-132 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
0.642
965791AG1-447 GEN
Solar/Wind Harmer
5.65
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
339216AC1-074 GEN
Solar/Wind Helper
0.388
339243AC2-075 GEN1
Solar/Wind Helper
0.097
926823AC1-168 GEN
Solar/Wind Harmer
5.709
970901AG2-562 GEN
50/50
5.361
253325AC1-069 GEN
Solar/Wind Helper
0.129
253333AC1-068 GEN
Solar/Wind Helper
0.129
253338AC1-165 GEN
Solar/Wind Helper
0.129
253343AC1-166 GEN
Solar/Wind Helper
0.129
270186AC1-089 GEN
Solar/Wind Helper
0.592
276668AB2-070 GEN1
Solar/Wind Harmer
3.518
276708O09 GEN2
Solar/Wind Harmer
0.511
276741O09 GEN1
Solar/Wind Harmer
0.511
276763AC1-053 GEN1
Solar/Wind Harmer
6.025
276764AC1-053 GEN2
Solar/Wind Harmer
6.025
276782AC1-033 GEN
Solar/Wind Harmer
5.922
276848AB2-070 GEN3
Solar/Wind Harmer
3.519
276849AB2-070 GEN2
Solar/Wind Harmer
3.518
944201AF1-088_MTX
50/50
166.394
957141AF2-008_MTX
50/50
83.197
950031AG9-013
External Queue
6.4584832191467285
990742J1381
External Queue
1.0042113065719604
991082J1475 G
External Queue
0.3522087037563324
991112J1481
External Queue
1.0042113065719604
NYPJM->LTFIMP_NY
CLTF
1.069
WECLTFEXP_WEC->PJM
CLTF
2.979
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.252
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.761
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
10.008
BlueGrassPJM->LTFIMP_BlueG
CLTF
28.7
LAGNLTFEXP_LAGN->PJM
CLTF
2.048
CBM West 1LTFEXP_CBM-W1->PJM
CBM
80.627
CBM West 2LTFEXP_CBM-W2->PJM
CBM
34.635
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MECLTFEXP_MEC->PJM
CLTF
10.439
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
42.675

Details for 05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#709_546_SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#709_546_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.0 %
Rating:2991.0 MVA
Rating Type:B
MVA to Mitigate:3589.24
MW Contribution:5.36
Bus #Bus NameTypeMW Contribution
24690905MDL-1G C
Solar/Wind Harmer
17.617
24691005MDL-2G C
Solar/Wind Harmer
8.403
24697605MDL-3G C
Solar/Wind Harmer
8.389
24697905MDL-4G C
Solar/Wind Harmer
5.539
24344105CKG2
50/50
7.002
24344305RKG2
50/50
11.178
24344305RKG2
50/50
11.072
274847GR RIDGE ;BU
Solar/Wind Harmer
8.629
274848CAMPGROVE;RU
Solar/Wind Harmer
8.235
274851PROVIDENC;RU
Solar/Wind Harmer
4.321
274853TWINGROVE;U1
Solar/Wind Harmer
11.667
274854TWINGROVE;U2
Solar/Wind Harmer
11.544
274855GSG-6 ;RU
Solar/Wind Harmer
5.863
274856ECOGROVE ;U1
Solar/Wind Harmer
5.312
274861TOP CROP ;1U
Solar/Wind Harmer
9.404
274862TOP CROP ;2U
Solar/Wind Harmer
7.811
274871GR RIDGE ;2U
Solar/Wind Harmer
11.277
274877BISHOP HL;1U
Solar/Wind Harmer
5.242
274878BISHOP HL;2U
Solar/Wind Harmer
5.242
274879MINONK ;1U
Solar/Wind Harmer
11.068
274888KELLY CRK;1U
Solar/Wind Harmer
9.928
24344205RKG1
50/50
11.55
24344205RKG1
50/50
11.55
24385905FR-11G C
Solar/Wind Harmer
9.998
24386205FR-12G C
Solar/Wind Harmer
5.309
24386405FR-21G C
Solar/Wind Harmer
5.085
24386605FR-22G C
Solar/Wind Harmer
5.085
24387005FR-3G C
Solar/Wind Harmer
5.035
24387305FR-4G C
Solar/Wind Harmer
7.628
274849CRESCENT ;1U
Solar/Wind Harmer
2.986
276602WESTBROOK C
Solar/Wind Harmer
3.233
276603SUBLETTE C
Solar/Wind Harmer
1.533
24755605MDL-5G
Solar/Wind Harmer
5.539
252510AF1-249 C
Solar/Wind Helper
0.1
253303V4-073 C
Solar/Wind Helper
0.007
339211AE2-254 GEN
Solar/Wind Helper
0.205
25183208HLCRTG
Solar/Wind Helper
0.93
274850MENDOTA H;RU
Solar/Wind Harmer
4.153
276691AA1-018 GEN1
Solar/Wind Harmer
0.514
276694AA1-018 GEN2
Solar/Wind Harmer
9.207
274872LEEDK;1U
Solar/Wind Harmer
13.52
274872LEEDK;1U
Solar/Wind Harmer
0.205
276646AC1-214 GEN2
Solar/Wind Harmer
1.956
276645AC1-214 GEN1
Solar/Wind Harmer
1.956
276806AD2-047 C O1
Solar/Wind Harmer
15.063
276901AD2-066 C O1
Solar/Wind Harmer
0
276916AD2-100_GEN
Solar/Wind Harmer
0.946
276911AD2-131_GEN
Solar/Wind Harmer
0.225
276893AG1-478 C
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
50.226
253415AE1-040 GEN
Solar/Wind Helper
0.145
270180AB1-006 GEN1
Solar/Wind Harmer
15.742
270181AB1-006 GEN2
Solar/Wind Harmer
1.044
253394AE2-221_GEN
Solar/Wind Helper
0.568
253398AE2-221_GEN2
Solar/Wind Helper
0.568
252507AC2-088 GEN
Solar/Wind Helper
0.371
252509AD1-136 GEN
Solar/Wind Helper
0.053
252524AE2-267 GEN
Solar/Wind Helper
0.25
276889AE2-281 GEN
Solar/Wind Harmer
2.99
276872AE1-163_GEN1
Solar/Wind Harmer
10.464
276876AE1-163_GEN2
Solar/Wind Harmer
10.464
276882AE2-255 GEN
Solar/Wind Harmer
4.992
276868AE1-113 GEN
Solar/Wind Harmer
15.825
253432AC1-085 GEN2
Solar/Wind Helper
0.019
253433AC1-085 GEN1
Solar/Wind Helper
0.368
253316AC1-085 GEN3
Solar/Wind Helper
0.581
253317AC1-085 GEN4
Solar/Wind Helper
0.581
339221AD2-048_GEN
Solar/Wind Helper
0.335
339255AE2-071 GEN
Solar/Wind Helper
0.095
276621W2-048 GEN
Solar/Wind Harmer
9.936
276861AD2-134 GEN
Solar/Wind Harmer
2.834
276863AD2-134 GEN
Solar/Wind Harmer
2.834
339231AF1-038_GEN
Solar/Wind Helper
0.181
339236AF1-050_GEN
Solar/Wind Helper
0.186
270393AB1-087 CT1
50/50
2.616
270394AB1-087 ST1
50/50
2.616
270406AB1-088 CT1
50/50
2.616
270407AB1-088 ST1
50/50
2.616
339241AF1-083 GEN
Solar/Wind Helper
0.186
276655WTG1_EQ
Solar/Wind Harmer
8.205
241972AD1-140 GEN
Solar/Wind Helper
0.522
270340AC2-060 GEN
Solar/Wind Helper
0.361
270367AC2-061_GEN
Solar/Wind Helper
0.457
276838X2-022 GEN2
Solar/Wind Harmer
0.374
270449AD2-020 GEN
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
8.569
270505AE1-170 C O1
Solar/Wind Harmer
0.691
270518AE2-148 GEN
Solar/Wind Helper
1.497
270536AF1-215 GEN2
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
339250AF1-203 GEN
Solar/Wind Helper
0.054
253406AD2-031_GEN
Solar/Wind Helper
0.18
276615X2-022 GEN
Solar/Wind Harmer
3.149
24791305MDL-5G
Solar/Wind Harmer
5.539
274857EASY ROAD;U1
Solar/Wind Harmer
7.036
274858EASY ROAD;U2
Solar/Wind Harmer
7.036
274863CRW1-WTG
Solar/Wind Harmer
9.12
274864CRW2-WTG
Solar/Wind Harmer
9.12
274880W4-005 GEN4
Solar/Wind Harmer
4.629
339206AE1-143 GEN
Solar/Wind Helper
0.341
938861AE1-114 GEN
Solar/Wind Harmer
10.548
942111AE2-223 GEN
Solar/Wind Harmer
11.15
942481AE2-261 GEN
Solar/Wind Harmer
1.35
942991AE2-321 GEN
Solar/Wind Harmer
0.464
943111AE2-339 GEN
Solar/Wind Helper
0.179
943121AE2-341 GEN
Solar/Wind Harmer
0.717
944031AF1-071 GEN
Solar/Wind Helper
0.051
944221AF1-090 GEN
Solar/Wind Harmer
13.979
945391AF1-204 GEN
Solar/Wind Harmer
20.258
945421AF1-207 GEN
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
0.716
958491AF2-143 GEN
Solar/Wind Harmer
0.709
959081AF2-199 GEN
Solar/Wind Harmer
0.459
959091AF2-200 GEN
Solar/Wind Harmer
0.917
959341AF2-225 GEN
Solar/Wind Harmer
0.715
959611AF2-252 GEN
Solar/Wind Harmer
1.892
960611AF2-352 GEN
Solar/Wind Harmer
1.892
961491AF2-440 GEN
Solar/Wind Helper
0.187
962211AG1-066 GEN
Solar/Wind Helper
0.201
962581AG1-107 GEN
Solar/Wind Helper
0.562
962691AG1-118 GEN
Solar/Wind Harmer
1.405
962781AG1-127 GEN
Solar/Wind Harmer
0.444
966841AG1-555 GEN
Solar/Wind Harmer
0
970091AG2-072 GEN
50/50
218.112
970169AG2-114 GEN
Solar/Wind Harmer
0.48
970193AG2-126 GEN
Solar/Wind Harmer
0.764
970239AG2-162 GEN
Solar/Wind Harmer
1.982
970241AG2-163 GEN
Solar/Wind Harmer
1.494
970243AG2-164 GEN
Solar/Wind Harmer
4.654
970333AG2-219 GEN
Solar/Wind Harmer
5.688
970519AG2-331 GEN
Solar/Wind Harmer
53.778
970569AG2-363 GEN
Solar/Wind Harmer
1.39
970571AG2-364 GEN
Solar/Wind Harmer
0.926
970699AG2-449 GEN
Solar/Wind Harmer
2.068
970781AG2-491 GEN
Solar/Wind Harmer
0.669
970819AG2-516 GEN
Solar/Wind Harmer
0.544
970921AG2-575 GEN
Solar/Wind Harmer
0.467
970921AG2-575 GEN
Solar/Wind Harmer
1.869
971067AG2-660 GEN
Solar/Wind Harmer
1.835
971171AH1-044 GEN
Solar/Wind Harmer
0.917
971177AH1-047 GEN
Solar/Wind Harmer
0.272
971333AH1-146 GEN
Solar/Wind Harmer
0.922
971335AH1-147 GEN
Solar/Wind Harmer
0.922
971341AH1-150 GEN
Solar/Wind Harmer
0.917
971343AH1-151 GEN
Solar/Wind Harmer
0.917
971411AH1-196 GEN
Solar/Wind Harmer
0.692
971475AH1-234 GEN
Solar/Wind Harmer
1.012
971573AH1-285 GEN
Solar/Wind Harmer
0.409
971675AH1-338 GEN
Solar/Wind Harmer
0.831
971681AH1-341 GEN
Solar/Wind Harmer
0.677
276157O29GEN1
Solar/Wind Harmer
6.523
276158O29GEN2
Solar/Wind Harmer
6.523
276174W4-005 GEN2
Solar/Wind Harmer
4.629
276656WTG2_EQ
Solar/Wind Harmer
1.086
276686W4-005 GEN3
Solar/Wind Harmer
4.629
276726Z2-087_GEN
Solar/Wind Harmer
12.389
276785W4-005 GEN1
Solar/Wind Harmer
4.629
939401AE1-172 GEN
Solar/Wind Harmer
19.281
939741AE1-205 GEN
Solar/Wind Harmer
0.953
941731AE2-173 GEN
Solar/Wind Harmer
4.765
957471AF2-041 GEN
Solar/Wind Harmer
1.376
957751AF2-069 GEN
Solar/Wind Harmer
0.597
963741AG1-226 GEN
Solar/Wind Harmer
2.69
963831AG1-236 GEN
Solar/Wind Harmer
13.013
963841AG1-237 GEN
Solar/Wind Harmer
19.463
965091AG1-374 GEN
Solar/Wind Harmer
1.419
965911AG1-460 GEN
Solar/Wind Harmer
1.083
971993AH1-541 GEN
Solar/Wind Harmer
0.43
971997AH1-543 GEN
Solar/Wind Harmer
0.743
972175AH1-670 GEN
Solar/Wind Harmer
18.29
274887GEN-1.85
Solar/Wind Harmer
9.12
939351AE1-166 GEN
Solar/Wind Harmer
0
942601AE2-276 GEN
50/50
8.32
943021AE2-325 GEN
Solar/Wind Harmer
2.857
943591AF1-030 GEN
Solar/Wind Harmer
0.478
945111AF1-176 GEN
Solar/Wind Harmer
0.81
945111AF1-176 GEN
Solar/Wind Harmer
4.415
959141AF2-205 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
0.489
960681AF2-359 GEN
Solar/Wind Harmer
0
961051AF2-396 GEN
Solar/Wind Harmer
0.911
961051AF2-396 GEN
Solar/Wind Harmer
7.285
970023AG2-014 GEN
50/50
2.676
970245AG2-165 GEN
Solar/Wind Harmer
1.382
970321AG2-212 GEN
Solar/Wind Harmer
1.382
970349AG2-230 GEN
Solar/Wind Harmer
0.755
970373AG2-245 GEN
Solar/Wind Harmer
1.207
970513AG2-328 GEN
Solar/Wind Harmer
1.382
970517AG2-330 GEN
Solar/Wind Harmer
21.56
970539AG2-343 GEN
50/50
9.325
970541AG2-344 GEN
50/50
10.171
970543AG2-345 GEN
50/50
4.663
970707AG2-453 GEN
Solar/Wind Harmer
1.365
970783AG2-492 GEN
50/50
2.676
970833AG2-524 GEN
Solar/Wind Harmer
0.533
970833AG2-524 GEN
Solar/Wind Harmer
4.261
970941AG2-585 GEN
Solar/Wind Harmer
0.611
971347AH1-153 GEN
Solar/Wind Harmer
0.755
971605AH1-302 GEN
Solar/Wind Harmer
9.72
971769AH1-391 GEN
Solar/Wind Harmer
0.494
971771AH1-392 GEN
Solar/Wind Harmer
0.427
971917AH1-482 GEN
Solar/Wind Harmer
9.694
972181SS23-001
Solar/Wind Harmer
0.495
972207SS24-0001
Solar/Wind Harmer
1.489
972231SS25-0005
Solar/Wind Harmer
0.792
270100X2-052 CT1
50/50
1.307
270101X2-052 CT2
50/50
1.307
270102X2-052 ST
50/50
1.415
276843GEN-1.7
Solar/Wind Harmer
0.808
940581AE2-045 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
0
958011AF2-095 GEN
Solar/Wind Harmer
0.704
958381AF2-132 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
0.642
965791AG1-447 GEN
Solar/Wind Harmer
5.65
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
339216AC1-074 GEN
Solar/Wind Helper
0.388
339243AC2-075 GEN1
Solar/Wind Helper
0.097
926823AC1-168 GEN
Solar/Wind Harmer
5.709
970901AG2-562 GEN
50/50
5.361
253325AC1-069 GEN
Solar/Wind Helper
0.129
253333AC1-068 GEN
Solar/Wind Helper
0.129
253338AC1-165 GEN
Solar/Wind Helper
0.129
253343AC1-166 GEN
Solar/Wind Helper
0.129
270186AC1-089 GEN
Solar/Wind Helper
0.592
276668AB2-070 GEN1
Solar/Wind Harmer
3.518
276708O09 GEN2
Solar/Wind Harmer
0.511
276741O09 GEN1
Solar/Wind Harmer
0.511
276763AC1-053 GEN1
Solar/Wind Harmer
6.025
276764AC1-053 GEN2
Solar/Wind Harmer
6.025
276782AC1-033 GEN
Solar/Wind Harmer
5.922
276848AB2-070 GEN3
Solar/Wind Harmer
3.519
276849AB2-070 GEN2
Solar/Wind Harmer
3.518
944201AF1-088_MTX
50/50
166.394
957141AF2-008_MTX
50/50
83.197
950031AG9-013
External Queue
6.4584832191467285
990742J1381
External Queue
1.0042113065719604
991082J1475 G
External Queue
0.3522087037563324
991112J1481
External Queue
1.0042113065719604
NYPJM->LTFIMP_NY
CLTF
1.069
WECLTFEXP_WEC->PJM
CLTF
2.979
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.252
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.761
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
10.008
BlueGrassPJM->LTFIMP_BlueG
CLTF
28.7
LAGNLTFEXP_LAGN->PJM
CLTF
2.048
CBM West 1LTFEXP_CBM-W1->PJM
CBM
80.627
CBM West 2LTFEXP_CBM-W2->PJM
CBM
34.635
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MECLTFEXP_MEC->PJM
CLTF
10.439
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
42.675

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P4_#7334_05JEFRSO 765_A2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.0 %
Rating:4961.0 MVA
Rating Type:B
MVA to Mitigate:5655.61
MW Contribution:13.76
Bus #Bus NameTypeMW Contribution
24690905MDL-1G C
Solar/Wind Harmer
31.574
24691005MDL-2G C
Solar/Wind Harmer
15.061
24697605MDL-3G C
Solar/Wind Harmer
15.036
24697905MDL-4G C
Solar/Wind Harmer
9.928
24344005CKG1
50/50
22.413
24344105CKG2
50/50
19.281
274771LINCOLN ;2U
50/50
19.802
274772LINCOLN ;3U
50/50
19.802
274773LINCOLN ;4U
50/50
19.802
274774LINCOLN ;5U
50/50
19.802
274775LINCOLN ;6U
50/50
19.802
274776LINCOLN ;7U
50/50
19.802
274777LINCOLN ;8U
50/50
19.802
274847GR RIDGE ;BU
Solar/Wind Harmer
22.119
274848CAMPGROVE;RU
Solar/Wind Harmer
20.674
274851PROVIDENC;RU
Solar/Wind Harmer
10.865
274853TWINGROVE;U1
Solar/Wind Harmer
27.647
274854TWINGROVE;U2
Solar/Wind Harmer
27.356
274855GSG-6 ;RU
Solar/Wind Harmer
15.127
274856ECOGROVE ;U1
Solar/Wind Harmer
13.719
274861TOP CROP ;1U
Solar/Wind Harmer
24.007
274862TOP CROP ;2U
Solar/Wind Harmer
19.941
274871GR RIDGE ;2U
Solar/Wind Harmer
28.905
274877BISHOP HL;1U
Solar/Wind Harmer
13.215
274878BISHOP HL;2U
Solar/Wind Harmer
13.215
274879MINONK ;1U
Solar/Wind Harmer
28.171
274888KELLY CRK;1U
Solar/Wind Harmer
25.475
24385905FR-11G C
Solar/Wind Harmer
17.778
24386205FR-12G C
Solar/Wind Harmer
9.441
24386405FR-21G C
Solar/Wind Harmer
9.043
24386605FR-22G C
Solar/Wind Harmer
9.043
24387005FR-3G C
Solar/Wind Harmer
8.953
24387305FR-4G C
Solar/Wind Harmer
13.565
274849CRESCENT ;1U
Solar/Wind Harmer
7.509
276602WESTBROOK C
Solar/Wind Harmer
8.341
276603SUBLETTE C
Solar/Wind Harmer
3.953
24755605MDL-5G
Solar/Wind Harmer
9.928
274850MENDOTA H;RU
Solar/Wind Harmer
10.714
276691AA1-018 GEN1
Solar/Wind Harmer
1.312
276694AA1-018 GEN2
Solar/Wind Harmer
23.507
274872LEEDK;1U
Solar/Wind Harmer
34.888
274872LEEDK;1U
Solar/Wind Harmer
0.529
276646AC1-214 GEN2
Solar/Wind Harmer
4.919
276645AC1-214 GEN1
Solar/Wind Harmer
4.919
276806AD2-047 C O1
Solar/Wind Harmer
38.651
276901AD2-066 C O1
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
-0.001
276897AD1-100 C
Solar/Wind Harmer
128.268
270142AC1-141 CT1_
50/50
5.371
270143AC1-141 CT2_
50/50
5.371
270144AC1-141 ST1_
50/50
4.757
270180AB1-006 GEN1
Solar/Wind Harmer
28.214
270181AB1-006 GEN2
Solar/Wind Harmer
1.871
276889AE2-281 GEN
Solar/Wind Harmer
7.582
276872AE1-163_GEN1
Solar/Wind Harmer
26.538
276876AE1-163_GEN2
Solar/Wind Harmer
26.538
276882AE2-255 GEN
Solar/Wind Harmer
12.707
276868AE1-113 GEN
Solar/Wind Harmer
40.278
276861AD2-134 GEN
Solar/Wind Harmer
7.313
276863AD2-134 GEN
Solar/Wind Harmer
7.313
276655WTG1_EQ
Solar/Wind Harmer
19.616
270449AD2-020 GEN
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
21.819
270471AD2-092_GEN
Solar/Wind Helper
0.709
270349AD2-093_GEN
Solar/Wind Helper
0.709
270505AE1-170 C O1
Solar/Wind Harmer
1.935
270043AE2-236 GEN
Solar/Wind Harmer
0.707
270063AE2-323 C
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
270054AF2-122 C O1
Solar/Wind Helper
0.54
270526AF1-158 GEN
Solar/Wind Harmer
0
270071AF1-092 GEN
Solar/Wind Harmer
1.913
274770LINCOLN ;1U
50/50
19.802
24791305MDL-5G
Solar/Wind Harmer
9.928
274857EASY ROAD;U1
Solar/Wind Harmer
18.167
274858EASY ROAD;U2
Solar/Wind Harmer
18.167
274863CRW1-WTG
Solar/Wind Harmer
22.565
274864CRW2-WTG
Solar/Wind Harmer
22.565
274880W4-005 GEN4
Solar/Wind Harmer
10.58
938861AE1-114 GEN
Solar/Wind Harmer
27.221
942111AE2-223 GEN
Solar/Wind Harmer
26.656
942991AE2-321 GEN
Solar/Wind Harmer
1.197
943121AE2-341 GEN
Solar/Wind Harmer
1.851
945421AF1-207 GEN
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
33.152
946581AF1-322 GEN
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
1.827
958491AF2-143 GEN
Solar/Wind Harmer
1.806
959081AF2-199 GEN
Solar/Wind Harmer
1.183
959091AF2-200 GEN
Solar/Wind Harmer
2.367
959341AF2-225 GEN
Solar/Wind Harmer
1.709
959611AF2-252 GEN
Solar/Wind Harmer
4.483
960611AF2-352 GEN
Solar/Wind Harmer
4.483
961011AF2-392 GEN
Solar/Wind Harmer
35.715
962691AG1-118 GEN
Solar/Wind Harmer
3.627
962781AG1-127 GEN
Solar/Wind Harmer
1.147
966841AG1-555 GEN
Solar/Wind Harmer
0
970169AG2-114 GEN
Solar/Wind Harmer
1.177
970239AG2-162 GEN
Solar/Wind Harmer
1.408
970241AG2-163 GEN
Solar/Wind Harmer
2.735
970243AG2-164 GEN
Solar/Wind Harmer
3.306
970333AG2-219 GEN
Solar/Wind Harmer
4.04
970519AG2-331 GEN
Solar/Wind Harmer
38.197
970569AG2-363 GEN
Solar/Wind Harmer
3.514
970571AG2-364 GEN
Solar/Wind Harmer
2.343
970699AG2-449 GEN
Solar/Wind Harmer
1.469
970781AG2-491 GEN
Solar/Wind Harmer
1.199
970819AG2-516 GEN
Solar/Wind Harmer
1.407
970921AG2-575 GEN
Solar/Wind Harmer
1.206
970921AG2-575 GEN
Solar/Wind Harmer
4.823
971067AG2-660 GEN
Solar/Wind Harmer
4.734
971171AH1-044 GEN
Solar/Wind Harmer
2.367
971177AH1-047 GEN
Solar/Wind Harmer
0.701
971333AH1-146 GEN
Solar/Wind Harmer
2.381
971335AH1-147 GEN
Solar/Wind Harmer
2.381
971341AH1-150 GEN
Solar/Wind Harmer
2.367
971343AH1-151 GEN
Solar/Wind Harmer
2.367
971411AH1-196 GEN
Solar/Wind Harmer
1.787
971475AH1-234 GEN
Solar/Wind Harmer
2.618
971573AH1-285 GEN
Solar/Wind Harmer
1.055
971675AH1-338 GEN
Solar/Wind Harmer
2.144
971681AH1-341 GEN
Solar/Wind Harmer
1.746
276157O29GEN1
Solar/Wind Harmer
16.728
276158O29GEN2
Solar/Wind Harmer
16.728
276174W4-005 GEN2
Solar/Wind Harmer
10.58
276656WTG2_EQ
Solar/Wind Harmer
2.597
276686W4-005 GEN3
Solar/Wind Harmer
10.58
276726Z2-087_GEN
Solar/Wind Harmer
29.618
276785W4-005 GEN1
Solar/Wind Harmer
10.58
939401AE1-172 GEN
Solar/Wind Harmer
48.146
939741AE1-205 GEN
Solar/Wind Harmer
2.278
941731AE2-173 GEN
Solar/Wind Harmer
11.391
957471AF2-041 GEN
Solar/Wind Harmer
3.55
957751AF2-069 GEN
Solar/Wind Harmer
1.501
963741AG1-226 GEN
Solar/Wind Harmer
4.923
963841AG1-237 GEN
Solar/Wind Harmer
35.114
965091AG1-374 GEN
Solar/Wind Harmer
3.362
965931AG1-462 GEN
Solar/Wind Harmer
2.821
971993AH1-541 GEN
Solar/Wind Harmer
0.983
971997AH1-543 GEN
Solar/Wind Harmer
1.886
972175AH1-670 GEN
Solar/Wind Harmer
42.535
24639705ELKHART HY
50/50
0.358
24641605TWIN BRNCH
50/50
0.039
24642205MAYFLWER
50/50
1.656
24643105BUCHANAN
50/50
0.028
274887GEN-1.85
Solar/Wind Harmer
23.402
939351AE1-166 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
7.995
943591AF1-030 GEN
Solar/Wind Harmer
1.234
944531AF1-118 GEN
Solar/Wind Harmer
4.133
944541AF1-119 GEN
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
2.286
945111AF1-176 GEN
Solar/Wind Harmer
12.464
959141AF2-205 GEN
Solar/Wind Harmer
0
959331AF2-224 GEN
Solar/Wind Harmer
1.115
960591AF2-350 GEN
Solar/Wind Harmer
1.255
960681AF2-359 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
33.549
961051AF2-396 GEN
Solar/Wind Harmer
2.556
961051AF2-396 GEN
Solar/Wind Harmer
20.451
970031AG2-029 GEN
Solar/Wind Harmer
3.667
970245AG2-165 GEN
Solar/Wind Harmer
2.856
970321AG2-212 GEN
Solar/Wind Harmer
2.856
970349AG2-230 GEN
Solar/Wind Harmer
2.086
970373AG2-245 GEN
Solar/Wind Harmer
2.694
970513AG2-328 GEN
Solar/Wind Harmer
2.856
970517AG2-330 GEN
Solar/Wind Harmer
44.557
970611AG2-400 GEN
Solar/Wind Harmer
1.115
970707AG2-453 GEN
Solar/Wind Harmer
3.529
970833AG2-524 GEN
Solar/Wind Harmer
1.365
970833AG2-524 GEN
Solar/Wind Harmer
10.921
970941AG2-585 GEN
Solar/Wind Harmer
1.569
971347AH1-153 GEN
Solar/Wind Harmer
2.086
971549AH1-272 GEN
Solar/Wind Harmer
2.146
971599AH1-298 GEN
50/50
20.938
971605AH1-302 GEN
Solar/Wind Harmer
18.534
971769AH1-391 GEN
Solar/Wind Harmer
1.305
971771AH1-392 GEN
Solar/Wind Harmer
1.176
971917AH1-482 GEN
Solar/Wind Harmer
19.542
972181SS23-001
Solar/Wind Harmer
1.268
972207SS24-0001
Solar/Wind Harmer
3.857
972231SS25-0005
Solar/Wind Harmer
2.028
270100X2-052 CT1
50/50
3.356
270101X2-052 CT2
50/50
3.356
270102X2-052 ST
50/50
3.632
276843GEN-1.7
Solar/Wind Harmer
2.073
940581AE2-045 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
0
958011AF2-095 GEN
Solar/Wind Harmer
1.807
958381AF2-132 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
965011AG1-365 GEN
Solar/Wind Harmer
1.115
965021AG1-366 GEN
Solar/Wind Harmer
4.46
965651AG1-433 GEN
Solar/Wind Harmer
16.774
965681AG1-436 GEN
Solar/Wind Harmer
1.643
965791AG1-447 GEN
Solar/Wind Harmer
14.461
926823AC1-168 GEN
Solar/Wind Harmer
14.39
970901AG2-562 GEN
50/50
13.762
276668AB2-070 GEN1
Solar/Wind Harmer
8.046
276708O09 GEN2
Solar/Wind Harmer
14.08
276741O09 GEN1
Solar/Wind Harmer
14.08
276763AC1-053 GEN1
Solar/Wind Harmer
9.884
276764AC1-053 GEN2
Solar/Wind Harmer
9.884
276782AC1-033 GEN
Solar/Wind Harmer
14.93
276848AB2-070 GEN3
Solar/Wind Harmer
8.048
276849AB2-070 GEN2
Solar/Wind Harmer
8.046
944201AF1-088_MTX
Adder
195.89
957141AF2-008_MTX
Adder
97.945
NYPJM->LTFIMP_NY
CLTF
3.498
LGEELTFEXP_LGEE->PJM
CLTF
4.156
WECLTFEXP_WEC->PJM
CLTF
7.718
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.329
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.601
LAGNLTFEXP_LAGN->PJM
CLTF
14.593
CBM West 1LTFEXP_CBM-W1->PJM
CBM
237.091
CBM West 2LTFEXP_CBM-W2->PJM
CBM
140.353
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.703
TVALTFEXP_TVA->PJM
CLTF
5.396
MECLTFEXP_MEC->PJM
CLTF
28.039
SIGELTFEXP_SIGE->PJM
CLTF
0.546
AG2-052LTFEXP_AG2-052->PJM
LTF
0.481
AH1-155LTFEXP_AH1-155->PJM
LTF
0.721
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
50.705

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#6189_05HANG R 765_D1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.24 %
Rating:4961.0 MVA
Rating Type:B
MVA to Mitigate:5171.46
MW Contribution:12.73
Bus #Bus NameTypeMW Contribution
24690905MDL-1G C
Solar/Wind Harmer
28.218
24691005MDL-2G C
Solar/Wind Harmer
13.46
24697605MDL-3G C
Solar/Wind Harmer
13.438
24697905MDL-4G C
Solar/Wind Harmer
8.873
247642Z2-115 C
Solar/Wind Harmer
-0.001
24344005CKG1
50/50
20.846
24344105CKG2
50/50
17.939
274771LINCOLN ;2U
50/50
18.334
274772LINCOLN ;3U
50/50
18.334
274773LINCOLN ;4U
50/50
18.334
274774LINCOLN ;5U
50/50
18.334
274775LINCOLN ;6U
50/50
18.334
274776LINCOLN ;7U
50/50
18.334
274777LINCOLN ;8U
50/50
18.334
274847GR RIDGE ;BU
Solar/Wind Harmer
20.461
274848CAMPGROVE;RU
Solar/Wind Harmer
19.088
274851PROVIDENC;RU
Solar/Wind Harmer
10.033
274853TWINGROVE;U1
Solar/Wind Harmer
25.403
274854TWINGROVE;U2
Solar/Wind Harmer
25.135
274855GSG-6 ;RU
Solar/Wind Harmer
13.998
274856ECOGROVE ;U1
Solar/Wind Harmer
12.696
274861TOP CROP ;1U
Solar/Wind Harmer
22.199
274862TOP CROP ;2U
Solar/Wind Harmer
18.439
274871GR RIDGE ;2U
Solar/Wind Harmer
26.738
274877BISHOP HL;1U
Solar/Wind Harmer
12.205
274878BISHOP HL;2U
Solar/Wind Harmer
12.205
274879MINONK ;1U
Solar/Wind Harmer
26.041
274888KELLY CRK;1U
Solar/Wind Harmer
23.567
24385905FR-11G C
Solar/Wind Harmer
15.873
24386205FR-12G C
Solar/Wind Harmer
8.429
24386405FR-21G C
Solar/Wind Harmer
8.074
24386605FR-22G C
Solar/Wind Harmer
8.074
24387005FR-3G C
Solar/Wind Harmer
7.993
24387305FR-4G C
Solar/Wind Harmer
12.111
274849CRESCENT ;1U
Solar/Wind Harmer
6.934
276602WESTBROOK C
Solar/Wind Harmer
7.719
276603SUBLETTE C
Solar/Wind Harmer
3.658
24755605MDL-5G
Solar/Wind Harmer
8.873
274850MENDOTA H;RU
Solar/Wind Harmer
9.914
276691AA1-018 GEN1
Solar/Wind Harmer
1.213
276694AA1-018 GEN2
Solar/Wind Harmer
21.736
274872LEEDK;1U
Solar/Wind Harmer
32.286
274872LEEDK;1U
Solar/Wind Harmer
0.49
276646AC1-214 GEN2
Solar/Wind Harmer
4.542
276645AC1-214 GEN1
Solar/Wind Harmer
4.542
276806AD2-047 C O1
Solar/Wind Harmer
35.756
276901AD2-066 C O1
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
-0.001
276897AD1-100 C
Solar/Wind Harmer
118.617
270142AC1-141 CT1_
50/50
5.003
270143AC1-141 CT2_
50/50
5.003
270144AC1-141 ST1_
50/50
4.431
270180AB1-006 GEN1
Solar/Wind Harmer
25.216
270181AB1-006 GEN2
Solar/Wind Harmer
1.672
276889AE2-281 GEN
Solar/Wind Harmer
7.007
276872AE1-163_GEN1
Solar/Wind Harmer
24.524
276876AE1-163_GEN2
Solar/Wind Harmer
24.524
276882AE2-255 GEN
Solar/Wind Harmer
11.746
276868AE1-113 GEN
Solar/Wind Harmer
37.233
276861AD2-134 GEN
Solar/Wind Harmer
6.767
276863AD2-134 GEN
Solar/Wind Harmer
6.767
276655WTG1_EQ
Solar/Wind Harmer
18.038
270449AD2-020 GEN
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
20.171
270471AD2-092_GEN
Solar/Wind Helper
0.7
270349AD2-093_GEN
Solar/Wind Helper
0.7
270505AE1-170 C O1
Solar/Wind Harmer
1.802
270043AE2-236 GEN
Solar/Wind Harmer
0.672
270063AE2-323 C
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
270071AF1-092 GEN
Solar/Wind Harmer
1.802
274770LINCOLN ;1U
50/50
18.334
24791305MDL-5G
Solar/Wind Harmer
8.873
274857EASY ROAD;U1
Solar/Wind Harmer
16.811
274858EASY ROAD;U2
Solar/Wind Harmer
16.811
274863CRW1-WTG
Solar/Wind Harmer
20.812
274864CRW2-WTG
Solar/Wind Harmer
20.812
274880W4-005 GEN4
Solar/Wind Harmer
9.69
938861AE1-114 GEN
Solar/Wind Harmer
25.188
942111AE2-223 GEN
Solar/Wind Harmer
24.512
942991AE2-321 GEN
Solar/Wind Harmer
1.107
943121AE2-341 GEN
Solar/Wind Harmer
1.714
945421AF1-207 GEN
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
30.676
946581AF1-322 GEN
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
1.69
958491AF2-143 GEN
Solar/Wind Harmer
1.67
959081AF2-199 GEN
Solar/Wind Harmer
1.095
959091AF2-200 GEN
Solar/Wind Harmer
2.19
959341AF2-225 GEN
Solar/Wind Harmer
1.571
959611AF2-252 GEN
Solar/Wind Harmer
4.119
960611AF2-352 GEN
Solar/Wind Harmer
4.119
961011AF2-392 GEN
Solar/Wind Harmer
33.045
962691AG1-118 GEN
Solar/Wind Harmer
3.356
962781AG1-127 GEN
Solar/Wind Harmer
1.061
966841AG1-555 GEN
Solar/Wind Harmer
0
970169AG2-114 GEN
Solar/Wind Harmer
1.084
970241AG2-163 GEN
Solar/Wind Harmer
2.45
970569AG2-363 GEN
Solar/Wind Harmer
3.247
970571AG2-364 GEN
Solar/Wind Harmer
2.164
970781AG2-491 GEN
Solar/Wind Harmer
1.072
970819AG2-516 GEN
Solar/Wind Harmer
1.302
970921AG2-575 GEN
Solar/Wind Harmer
1.116
970921AG2-575 GEN
Solar/Wind Harmer
4.463
971067AG2-660 GEN
Solar/Wind Harmer
4.38
971171AH1-044 GEN
Solar/Wind Harmer
2.19
971177AH1-047 GEN
Solar/Wind Harmer
0.649
971333AH1-146 GEN
Solar/Wind Harmer
2.203
971335AH1-147 GEN
Solar/Wind Harmer
2.203
971341AH1-150 GEN
Solar/Wind Harmer
2.19
971343AH1-151 GEN
Solar/Wind Harmer
2.19
971411AH1-196 GEN
Solar/Wind Harmer
1.654
971475AH1-234 GEN
Solar/Wind Harmer
2.423
971573AH1-285 GEN
Solar/Wind Harmer
0.977
971675AH1-338 GEN
Solar/Wind Harmer
1.984
971681AH1-341 GEN
Solar/Wind Harmer
1.615
276157O29GEN1
Solar/Wind Harmer
15.471
276158O29GEN2
Solar/Wind Harmer
15.471
276174W4-005 GEN2
Solar/Wind Harmer
9.69
276656WTG2_EQ
Solar/Wind Harmer
2.388
276686W4-005 GEN3
Solar/Wind Harmer
9.69
276726Z2-087_GEN
Solar/Wind Harmer
27.235
276785W4-005 GEN1
Solar/Wind Harmer
9.69
939401AE1-172 GEN
Solar/Wind Harmer
44.44
939741AE1-205 GEN
Solar/Wind Harmer
2.095
941731AE2-173 GEN
Solar/Wind Harmer
10.475
957471AF2-041 GEN
Solar/Wind Harmer
3.285
957751AF2-069 GEN
Solar/Wind Harmer
1.386
963741AG1-226 GEN
Solar/Wind Harmer
4.409
963841AG1-237 GEN
Solar/Wind Harmer
31.4
965091AG1-374 GEN
Solar/Wind Harmer
3.089
965931AG1-462 GEN
Solar/Wind Harmer
2.61
971993AH1-541 GEN
Solar/Wind Harmer
0.9
971997AH1-543 GEN
Solar/Wind Harmer
1.743
972175AH1-670 GEN
Solar/Wind Harmer
39.016
24639705ELKHART HY
50/50
0.334
24641605TWIN BRNCH
50/50
0.036
24642205MAYFLWER
50/50
1.54
24643105BUCHANAN
50/50
0.026
24653605MOTTVILLE
50/50
0.007
274887GEN-1.85
Solar/Wind Harmer
21.649
939351AE1-166 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
7.445
943591AF1-030 GEN
Solar/Wind Harmer
1.142
944531AF1-118 GEN
Solar/Wind Harmer
4.019
944541AF1-119 GEN
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
2.13
945111AF1-176 GEN
Solar/Wind Harmer
11.613
945371AF1-202 GEN
Solar/Wind Harmer
15.376
945581AF1-223 GEN
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
32.122
959141AF2-205 GEN
Solar/Wind Harmer
0
959331AF2-224 GEN
Solar/Wind Harmer
1.065
960591AF2-350 GEN
Solar/Wind Harmer
1.161
960681AF2-359 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
32.84
961051AF2-396 GEN
Solar/Wind Harmer
2.381
961051AF2-396 GEN
Solar/Wind Harmer
19.048
970031AG2-029 GEN
Solar/Wind Harmer
3.451
970245AG2-165 GEN
Solar/Wind Harmer
2.593
970321AG2-212 GEN
Solar/Wind Harmer
2.593
970349AG2-230 GEN
Solar/Wind Harmer
1.941
970373AG2-245 GEN
Solar/Wind Harmer
2.463
970513AG2-328 GEN
Solar/Wind Harmer
2.593
970517AG2-330 GEN
Solar/Wind Harmer
40.453
970521AG2-332 GEN
50/50
23.771
970611AG2-400 GEN
Solar/Wind Harmer
1.065
970707AG2-453 GEN
Solar/Wind Harmer
3.267
970833AG2-524 GEN
Solar/Wind Harmer
1.263
970833AG2-524 GEN
Solar/Wind Harmer
10.102
970941AG2-585 GEN
Solar/Wind Harmer
1.451
971347AH1-153 GEN
Solar/Wind Harmer
1.941
971549AH1-272 GEN
Solar/Wind Harmer
2
971599AH1-298 GEN
50/50
20.056
971605AH1-302 GEN
Solar/Wind Harmer
16.681
971769AH1-391 GEN
Solar/Wind Harmer
1.21
971771AH1-392 GEN
Solar/Wind Harmer
1.094
971917AH1-482 GEN
Solar/Wind Harmer
17.692
972181SS23-001
Solar/Wind Harmer
1.173
972207SS24-0001
Solar/Wind Harmer
3.572
972231SS25-0005
Solar/Wind Harmer
1.876
270100X2-052 CT1
50/50
3.105
270101X2-052 CT2
50/50
3.105
270102X2-052 ST
50/50
3.361
276843GEN-1.7
Solar/Wind Harmer
1.918
940581AE2-045 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
0
958011AF2-095 GEN
Solar/Wind Harmer
1.672
958381AF2-132 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
965011AG1-365 GEN
Solar/Wind Harmer
1.065
965021AG1-366 GEN
Solar/Wind Harmer
4.261
965101AG1-375 GEN
Solar/Wind Harmer
1.03
965651AG1-433 GEN
Solar/Wind Harmer
16.42
965681AG1-436 GEN
Solar/Wind Harmer
1.52
965791AG1-447 GEN
Solar/Wind Harmer
13.376
926823AC1-168 GEN
Solar/Wind Harmer
13.291
970901AG2-562 GEN
50/50
12.734
276668AB2-070 GEN1
Solar/Wind Harmer
7.368
276708O09 GEN2
Solar/Wind Harmer
13.022
276741O09 GEN1
Solar/Wind Harmer
13.022
276763AC1-053 GEN1
Solar/Wind Harmer
5.055
276764AC1-053 GEN2
Solar/Wind Harmer
5.055
276782AC1-033 GEN
Solar/Wind Harmer
13.789
276848AB2-070 GEN3
Solar/Wind Harmer
7.37
276849AB2-070 GEN2
Solar/Wind Harmer
7.368
944201AF1-088_MTX
Adder
164.341
957141AF2-008_MTX
Adder
82.17
NYPJM->LTFIMP_NY
CLTF
3.333
LGEELTFEXP_LGEE->PJM
CLTF
5.67
WECLTFEXP_WEC->PJM
CLTF
7.144
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.132
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.48
LAGNLTFEXP_LAGN->PJM
CLTF
14.106
CBM West 1LTFEXP_CBM-W1->PJM
CBM
221.335
CBM West 2LTFEXP_CBM-W2->PJM
CBM
133.208
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.252
TVALTFEXP_TVA->PJM
CLTF
5.42
MECLTFEXP_MEC->PJM
CLTF
26.01
SIGELTFEXP_SIGE->PJM
CLTF
0.556
AG2-052LTFEXP_AG2-052->PJM
LTF
0.441
AH1-155LTFEXP_AH1-155->PJM
LTF
0.661
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
42.769

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P4_#709_05HANG R 765_D2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#709_05HANG R 765_D2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.76 %
Rating:4961.0 MVA
Rating Type:B
MVA to Mitigate:5098.14
MW Contribution:12.77
Bus #Bus NameTypeMW Contribution
24690905MDL-1G C
Solar/Wind Harmer
28.298
24691005MDL-2G C
Solar/Wind Harmer
13.498
24697605MDL-3G C
Solar/Wind Harmer
13.476
24697905MDL-4G C
Solar/Wind Harmer
8.898
247642Z2-115 C
Solar/Wind Harmer
-0.001
24344005CKG1
50/50
20.898
24344105CKG2
50/50
17.979
274771LINCOLN ;2U
50/50
18.381
274772LINCOLN ;3U
50/50
18.381
274773LINCOLN ;4U
50/50
18.381
274774LINCOLN ;5U
50/50
18.381
274775LINCOLN ;6U
50/50
18.381
274776LINCOLN ;7U
50/50
18.381
274777LINCOLN ;8U
50/50
18.381
274847GR RIDGE ;BU
Solar/Wind Harmer
20.515
274848CAMPGROVE;RU
Solar/Wind Harmer
19.143
274851PROVIDENC;RU
Solar/Wind Harmer
10.062
274853TWINGROVE;U1
Solar/Wind Harmer
25.477
274854TWINGROVE;U2
Solar/Wind Harmer
25.209
274855GSG-6 ;RU
Solar/Wind Harmer
14.037
274856ECOGROVE ;U1
Solar/Wind Harmer
12.731
274861TOP CROP ;1U
Solar/Wind Harmer
22.259
274862TOP CROP ;2U
Solar/Wind Harmer
18.489
274871GR RIDGE ;2U
Solar/Wind Harmer
26.808
274877BISHOP HL;1U
Solar/Wind Harmer
12.24
274878BISHOP HL;2U
Solar/Wind Harmer
12.24
274879MINONK ;1U
Solar/Wind Harmer
26.112
274888KELLY CRK;1U
Solar/Wind Harmer
23.628
24385905FR-11G C
Solar/Wind Harmer
15.919
24386205FR-12G C
Solar/Wind Harmer
8.454
24386405FR-21G C
Solar/Wind Harmer
8.098
24386605FR-22G C
Solar/Wind Harmer
8.098
24387005FR-3G C
Solar/Wind Harmer
8.017
24387305FR-4G C
Solar/Wind Harmer
12.146
274849CRESCENT ;1U
Solar/Wind Harmer
6.954
276602WESTBROOK C
Solar/Wind Harmer
7.74
276603SUBLETTE C
Solar/Wind Harmer
3.668
24755605MDL-5G
Solar/Wind Harmer
8.898
274850MENDOTA H;RU
Solar/Wind Harmer
9.942
276691AA1-018 GEN1
Solar/Wind Harmer
1.216
276694AA1-018 GEN2
Solar/Wind Harmer
21.795
274872LEEDK;1U
Solar/Wind Harmer
32.374
274872LEEDK;1U
Solar/Wind Harmer
0.491
276646AC1-214 GEN2
Solar/Wind Harmer
4.555
276645AC1-214 GEN1
Solar/Wind Harmer
4.555
276806AD2-047 C O1
Solar/Wind Harmer
35.85
276901AD2-066 C O1
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
-0.001
276897AD1-100 C
Solar/Wind Harmer
118.927
270142AC1-141 CT1_
50/50
5.015
270143AC1-141 CT2_
50/50
5.015
270144AC1-141 ST1_
50/50
4.442
270180AB1-006 GEN1
Solar/Wind Harmer
25.287
270181AB1-006 GEN2
Solar/Wind Harmer
1.676
276889AE2-281 GEN
Solar/Wind Harmer
7.026
276872AE1-163_GEN1
Solar/Wind Harmer
24.592
276876AE1-163_GEN2
Solar/Wind Harmer
24.592
276882AE2-255 GEN
Solar/Wind Harmer
11.778
276868AE1-113 GEN
Solar/Wind Harmer
37.335
276861AD2-134 GEN
Solar/Wind Harmer
6.785
276863AD2-134 GEN
Solar/Wind Harmer
6.785
276655WTG1_EQ
Solar/Wind Harmer
18.09
270449AD2-020 GEN
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
20.225
270471AD2-092_GEN
Solar/Wind Helper
0.697
270349AD2-093_GEN
Solar/Wind Helper
0.697
270505AE1-170 C O1
Solar/Wind Harmer
1.807
270043AE2-236 GEN
Solar/Wind Harmer
0.674
270063AE2-323 C
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
270071AF1-092 GEN
Solar/Wind Harmer
1.806
274770LINCOLN ;1U
50/50
18.381
24791305MDL-5G
Solar/Wind Harmer
8.898
274857EASY ROAD;U1
Solar/Wind Harmer
16.859
274858EASY ROAD;U2
Solar/Wind Harmer
16.859
274863CRW1-WTG
Solar/Wind Harmer
20.869
274864CRW2-WTG
Solar/Wind Harmer
20.869
274880W4-005 GEN4
Solar/Wind Harmer
9.72
938861AE1-114 GEN
Solar/Wind Harmer
25.259
942111AE2-223 GEN
Solar/Wind Harmer
24.582
942991AE2-321 GEN
Solar/Wind Harmer
1.111
943121AE2-341 GEN
Solar/Wind Harmer
1.718
945421AF1-207 GEN
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
30.766
946581AF1-322 GEN
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
1.694
958491AF2-143 GEN
Solar/Wind Harmer
1.674
959081AF2-199 GEN
Solar/Wind Harmer
1.098
959091AF2-200 GEN
Solar/Wind Harmer
2.196
959341AF2-225 GEN
Solar/Wind Harmer
1.576
959611AF2-252 GEN
Solar/Wind Harmer
4.131
960611AF2-352 GEN
Solar/Wind Harmer
4.131
961011AF2-392 GEN
Solar/Wind Harmer
33.139
962691AG1-118 GEN
Solar/Wind Harmer
3.365
962781AG1-127 GEN
Solar/Wind Harmer
1.064
966841AG1-555 GEN
Solar/Wind Harmer
0
970169AG2-114 GEN
Solar/Wind Harmer
1.087
970241AG2-163 GEN
Solar/Wind Harmer
2.457
970569AG2-363 GEN
Solar/Wind Harmer
3.256
970571AG2-364 GEN
Solar/Wind Harmer
2.17
970781AG2-491 GEN
Solar/Wind Harmer
1.075
970819AG2-516 GEN
Solar/Wind Harmer
1.306
970921AG2-575 GEN
Solar/Wind Harmer
1.119
970921AG2-575 GEN
Solar/Wind Harmer
4.476
971067AG2-660 GEN
Solar/Wind Harmer
4.392
971171AH1-044 GEN
Solar/Wind Harmer
2.196
971177AH1-047 GEN
Solar/Wind Harmer
0.65
971333AH1-146 GEN
Solar/Wind Harmer
2.209
971335AH1-147 GEN
Solar/Wind Harmer
2.209
971341AH1-150 GEN
Solar/Wind Harmer
2.196
971343AH1-151 GEN
Solar/Wind Harmer
2.196
971411AH1-196 GEN
Solar/Wind Harmer
1.658
971475AH1-234 GEN
Solar/Wind Harmer
2.43
971573AH1-285 GEN
Solar/Wind Harmer
0.979
971675AH1-338 GEN
Solar/Wind Harmer
1.99
971681AH1-341 GEN
Solar/Wind Harmer
1.62
276157O29GEN1
Solar/Wind Harmer
15.515
276158O29GEN2
Solar/Wind Harmer
15.515
276174W4-005 GEN2
Solar/Wind Harmer
9.72
276656WTG2_EQ
Solar/Wind Harmer
2.395
276686W4-005 GEN3
Solar/Wind Harmer
9.72
276726Z2-087_GEN
Solar/Wind Harmer
27.314
276785W4-005 GEN1
Solar/Wind Harmer
9.72
939401AE1-172 GEN
Solar/Wind Harmer
44.561
939741AE1-205 GEN
Solar/Wind Harmer
2.101
941731AE2-173 GEN
Solar/Wind Harmer
10.505
957471AF2-041 GEN
Solar/Wind Harmer
3.294
957751AF2-069 GEN
Solar/Wind Harmer
1.39
963741AG1-226 GEN
Solar/Wind Harmer
4.423
963841AG1-237 GEN
Solar/Wind Harmer
31.494
965091AG1-374 GEN
Solar/Wind Harmer
3.098
965931AG1-462 GEN
Solar/Wind Harmer
2.618
971993AH1-541 GEN
Solar/Wind Harmer
0.903
971997AH1-543 GEN
Solar/Wind Harmer
1.748
972175AH1-670 GEN
Solar/Wind Harmer
39.134
24639705ELKHART HY
50/50
0.335
24641605TWIN BRNCH
50/50
0.036
24642205MAYFLWER
50/50
1.544
24643105BUCHANAN
50/50
0.026
24653605MOTTVILLE
50/50
0.007
274887GEN-1.85
Solar/Wind Harmer
21.706
939351AE1-166 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
7.464
943591AF1-030 GEN
Solar/Wind Harmer
1.145
944531AF1-118 GEN
Solar/Wind Harmer
4.029
944541AF1-119 GEN
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
2.136
945111AF1-176 GEN
Solar/Wind Harmer
11.643
945371AF1-202 GEN
Solar/Wind Harmer
15.423
945581AF1-223 GEN
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
32.216
959141AF2-205 GEN
Solar/Wind Harmer
0
959331AF2-224 GEN
Solar/Wind Harmer
1.068
960591AF2-350 GEN
Solar/Wind Harmer
1.164
960681AF2-359 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
32.934
961051AF2-396 GEN
Solar/Wind Harmer
2.387
961051AF2-396 GEN
Solar/Wind Harmer
19.097
970031AG2-029 GEN
Solar/Wind Harmer
3.46
970245AG2-165 GEN
Solar/Wind Harmer
2.599
970321AG2-212 GEN
Solar/Wind Harmer
2.599
970349AG2-230 GEN
Solar/Wind Harmer
1.946
970373AG2-245 GEN
Solar/Wind Harmer
2.469
970513AG2-328 GEN
Solar/Wind Harmer
2.599
970517AG2-330 GEN
Solar/Wind Harmer
40.548
970521AG2-332 GEN
50/50
23.831
970611AG2-400 GEN
Solar/Wind Harmer
1.068
970707AG2-453 GEN
Solar/Wind Harmer
3.275
970833AG2-524 GEN
Solar/Wind Harmer
1.266
970833AG2-524 GEN
Solar/Wind Harmer
10.129
970941AG2-585 GEN
Solar/Wind Harmer
1.455
971347AH1-153 GEN
Solar/Wind Harmer
1.946
971549AH1-272 GEN
Solar/Wind Harmer
2.005
971599AH1-298 GEN
50/50
20.101
971605AH1-302 GEN
Solar/Wind Harmer
16.727
971769AH1-391 GEN
Solar/Wind Harmer
1.213
971771AH1-392 GEN
Solar/Wind Harmer
1.097
971917AH1-482 GEN
Solar/Wind Harmer
17.74
972181SS23-001
Solar/Wind Harmer
1.176
972207SS24-0001
Solar/Wind Harmer
3.581
972231SS25-0005
Solar/Wind Harmer
1.881
270100X2-052 CT1
50/50
3.113
270101X2-052 CT2
50/50
3.113
270102X2-052 ST
50/50
3.369
276843GEN-1.7
Solar/Wind Harmer
1.923
940581AE2-045 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
0
958011AF2-095 GEN
Solar/Wind Harmer
1.676
958381AF2-132 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
965011AG1-365 GEN
Solar/Wind Harmer
1.068
965021AG1-366 GEN
Solar/Wind Harmer
4.273
965101AG1-375 GEN
Solar/Wind Harmer
1.033
965651AG1-433 GEN
Solar/Wind Harmer
16.467
965681AG1-436 GEN
Solar/Wind Harmer
1.524
965791AG1-447 GEN
Solar/Wind Harmer
13.41
926823AC1-168 GEN
Solar/Wind Harmer
13.329
970901AG2-562 GEN
50/50
12.765
276668AB2-070 GEN1
Solar/Wind Harmer
7.391
276708O09 GEN2
Solar/Wind Harmer
13.059
276741O09 GEN1
Solar/Wind Harmer
13.059
276763AC1-053 GEN1
Solar/Wind Harmer
5.071
276764AC1-053 GEN2
Solar/Wind Harmer
5.071
276782AC1-033 GEN
Solar/Wind Harmer
13.828
276848AB2-070 GEN3
Solar/Wind Harmer
7.393
276849AB2-070 GEN2
Solar/Wind Harmer
7.391
944201AF1-088_MTX
Adder
164.946
957141AF2-008_MTX
Adder
82.473
NYPJM->LTFIMP_NY
CLTF
3.299
LGEELTFEXP_LGEE->PJM
CLTF
5.706
WECLTFEXP_WEC->PJM
CLTF
7.164
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.097
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.459
LAGNLTFEXP_LAGN->PJM
CLTF
14.212
CBM West 1LTFEXP_CBM-W1->PJM
CBM
222.098
CBM West 2LTFEXP_CBM-W2->PJM
CBM
133.912
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.451
TVALTFEXP_TVA->PJM
CLTF
5.473
MECLTFEXP_MEC->PJM
CLTF
26.098
SIGELTFEXP_SIGE->PJM
CLTF
0.559
AG2-052LTFEXP_AG2-052->PJM
LTF
0.442
AH1-155LTFEXP_AH1-155->PJM
LTF
0.663
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
42.769

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#709_546_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.76 %
Rating:4961.0 MVA
Rating Type:B
MVA to Mitigate:5098.11
MW Contribution:12.77
Bus #Bus NameTypeMW Contribution
24690905MDL-1G C
Solar/Wind Harmer
28.298
24691005MDL-2G C
Solar/Wind Harmer
13.498
24697605MDL-3G C
Solar/Wind Harmer
13.476
24697905MDL-4G C
Solar/Wind Harmer
8.898
247642Z2-115 C
Solar/Wind Harmer
-0.001
24344005CKG1
50/50
20.898
24344105CKG2
50/50
17.979
274771LINCOLN ;2U
50/50
18.381
274772LINCOLN ;3U
50/50
18.381
274773LINCOLN ;4U
50/50
18.381
274774LINCOLN ;5U
50/50
18.381
274775LINCOLN ;6U
50/50
18.381
274776LINCOLN ;7U
50/50
18.381
274777LINCOLN ;8U
50/50
18.381
274847GR RIDGE ;BU
Solar/Wind Harmer
20.515
274848CAMPGROVE;RU
Solar/Wind Harmer
19.143
274851PROVIDENC;RU
Solar/Wind Harmer
10.062
274853TWINGROVE;U1
Solar/Wind Harmer
25.477
274854TWINGROVE;U2
Solar/Wind Harmer
25.209
274855GSG-6 ;RU
Solar/Wind Harmer
14.037
274856ECOGROVE ;U1
Solar/Wind Harmer
12.731
274861TOP CROP ;1U
Solar/Wind Harmer
22.259
274862TOP CROP ;2U
Solar/Wind Harmer
18.489
274871GR RIDGE ;2U
Solar/Wind Harmer
26.808
274877BISHOP HL;1U
Solar/Wind Harmer
12.24
274878BISHOP HL;2U
Solar/Wind Harmer
12.24
274879MINONK ;1U
Solar/Wind Harmer
26.112
274888KELLY CRK;1U
Solar/Wind Harmer
23.628
24385905FR-11G C
Solar/Wind Harmer
15.919
24386205FR-12G C
Solar/Wind Harmer
8.454
24386405FR-21G C
Solar/Wind Harmer
8.098
24386605FR-22G C
Solar/Wind Harmer
8.098
24387005FR-3G C
Solar/Wind Harmer
8.017
24387305FR-4G C
Solar/Wind Harmer
12.146
274849CRESCENT ;1U
Solar/Wind Harmer
6.954
276602WESTBROOK C
Solar/Wind Harmer
7.74
276603SUBLETTE C
Solar/Wind Harmer
3.668
24755605MDL-5G
Solar/Wind Harmer
8.898
274850MENDOTA H;RU
Solar/Wind Harmer
9.942
276691AA1-018 GEN1
Solar/Wind Harmer
1.216
276694AA1-018 GEN2
Solar/Wind Harmer
21.795
274872LEEDK;1U
Solar/Wind Harmer
32.374
274872LEEDK;1U
Solar/Wind Harmer
0.491
276646AC1-214 GEN2
Solar/Wind Harmer
4.555
276645AC1-214 GEN1
Solar/Wind Harmer
4.555
276806AD2-047 C O1
Solar/Wind Harmer
35.85
276901AD2-066 C O1
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
-0.001
276897AD1-100 C
Solar/Wind Harmer
118.927
270142AC1-141 CT1_
50/50
5.015
270143AC1-141 CT2_
50/50
5.015
270144AC1-141 ST1_
50/50
4.442
270180AB1-006 GEN1
Solar/Wind Harmer
25.287
270181AB1-006 GEN2
Solar/Wind Harmer
1.676
276889AE2-281 GEN
Solar/Wind Harmer
7.026
276872AE1-163_GEN1
Solar/Wind Harmer
24.592
276876AE1-163_GEN2
Solar/Wind Harmer
24.592
276882AE2-255 GEN
Solar/Wind Harmer
11.778
276868AE1-113 GEN
Solar/Wind Harmer
37.335
276861AD2-134 GEN
Solar/Wind Harmer
6.785
276863AD2-134 GEN
Solar/Wind Harmer
6.785
276655WTG1_EQ
Solar/Wind Harmer
18.09
270449AD2-020 GEN
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
20.225
270471AD2-092_GEN
Solar/Wind Helper
0.697
270349AD2-093_GEN
Solar/Wind Helper
0.697
270505AE1-170 C O1
Solar/Wind Harmer
1.807
270043AE2-236 GEN
Solar/Wind Harmer
0.674
270063AE2-323 C
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
270071AF1-092 GEN
Solar/Wind Harmer
1.806
274770LINCOLN ;1U
50/50
18.381
24791305MDL-5G
Solar/Wind Harmer
8.898
274857EASY ROAD;U1
Solar/Wind Harmer
16.859
274858EASY ROAD;U2
Solar/Wind Harmer
16.859
274863CRW1-WTG
Solar/Wind Harmer
20.869
274864CRW2-WTG
Solar/Wind Harmer
20.869
274880W4-005 GEN4
Solar/Wind Harmer
9.72
938861AE1-114 GEN
Solar/Wind Harmer
25.259
942111AE2-223 GEN
Solar/Wind Harmer
24.582
942991AE2-321 GEN
Solar/Wind Harmer
1.111
943121AE2-341 GEN
Solar/Wind Harmer
1.718
945421AF1-207 GEN
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
30.766
946581AF1-322 GEN
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
1.694
958491AF2-143 GEN
Solar/Wind Harmer
1.674
959081AF2-199 GEN
Solar/Wind Harmer
1.098
959091AF2-200 GEN
Solar/Wind Harmer
2.196
959341AF2-225 GEN
Solar/Wind Harmer
1.576
959611AF2-252 GEN
Solar/Wind Harmer
4.131
960611AF2-352 GEN
Solar/Wind Harmer
4.131
961011AF2-392 GEN
Solar/Wind Harmer
33.139
962691AG1-118 GEN
Solar/Wind Harmer
3.365
962781AG1-127 GEN
Solar/Wind Harmer
1.064
966841AG1-555 GEN
Solar/Wind Harmer
0
970169AG2-114 GEN
Solar/Wind Harmer
1.087
970241AG2-163 GEN
Solar/Wind Harmer
2.457
970569AG2-363 GEN
Solar/Wind Harmer
3.256
970571AG2-364 GEN
Solar/Wind Harmer
2.17
970781AG2-491 GEN
Solar/Wind Harmer
1.075
970819AG2-516 GEN
Solar/Wind Harmer
1.306
970921AG2-575 GEN
Solar/Wind Harmer
1.119
970921AG2-575 GEN
Solar/Wind Harmer
4.476
971067AG2-660 GEN
Solar/Wind Harmer
4.392
971171AH1-044 GEN
Solar/Wind Harmer
2.196
971177AH1-047 GEN
Solar/Wind Harmer
0.65
971333AH1-146 GEN
Solar/Wind Harmer
2.209
971335AH1-147 GEN
Solar/Wind Harmer
2.209
971341AH1-150 GEN
Solar/Wind Harmer
2.196
971343AH1-151 GEN
Solar/Wind Harmer
2.196
971411AH1-196 GEN
Solar/Wind Harmer
1.658
971475AH1-234 GEN
Solar/Wind Harmer
2.43
971573AH1-285 GEN
Solar/Wind Harmer
0.979
971675AH1-338 GEN
Solar/Wind Harmer
1.99
971681AH1-341 GEN
Solar/Wind Harmer
1.62
276157O29GEN1
Solar/Wind Harmer
15.515
276158O29GEN2
Solar/Wind Harmer
15.515
276174W4-005 GEN2
Solar/Wind Harmer
9.72
276656WTG2_EQ
Solar/Wind Harmer
2.395
276686W4-005 GEN3
Solar/Wind Harmer
9.72
276726Z2-087_GEN
Solar/Wind Harmer
27.314
276785W4-005 GEN1
Solar/Wind Harmer
9.72
939401AE1-172 GEN
Solar/Wind Harmer
44.561
939741AE1-205 GEN
Solar/Wind Harmer
2.101
941731AE2-173 GEN
Solar/Wind Harmer
10.505
957471AF2-041 GEN
Solar/Wind Harmer
3.294
957751AF2-069 GEN
Solar/Wind Harmer
1.39
963741AG1-226 GEN
Solar/Wind Harmer
4.423
963841AG1-237 GEN
Solar/Wind Harmer
31.494
965091AG1-374 GEN
Solar/Wind Harmer
3.098
965931AG1-462 GEN
Solar/Wind Harmer
2.618
971993AH1-541 GEN
Solar/Wind Harmer
0.903
971997AH1-543 GEN
Solar/Wind Harmer
1.748
972175AH1-670 GEN
Solar/Wind Harmer
39.134
24639705ELKHART HY
50/50
0.335
24641605TWIN BRNCH
50/50
0.036
24642205MAYFLWER
50/50
1.544
24643105BUCHANAN
50/50
0.026
24653605MOTTVILLE
50/50
0.007
274887GEN-1.85
Solar/Wind Harmer
21.706
939351AE1-166 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
7.464
943591AF1-030 GEN
Solar/Wind Harmer
1.145
944531AF1-118 GEN
Solar/Wind Harmer
4.029
944541AF1-119 GEN
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
2.136
945111AF1-176 GEN
Solar/Wind Harmer
11.643
945371AF1-202 GEN
Solar/Wind Harmer
15.423
945581AF1-223 GEN
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
32.216
959141AF2-205 GEN
Solar/Wind Harmer
0
959331AF2-224 GEN
Solar/Wind Harmer
1.068
960591AF2-350 GEN
Solar/Wind Harmer
1.164
960681AF2-359 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
32.934
961051AF2-396 GEN
Solar/Wind Harmer
2.387
961051AF2-396 GEN
Solar/Wind Harmer
19.097
970031AG2-029 GEN
Solar/Wind Harmer
3.46
970245AG2-165 GEN
Solar/Wind Harmer
2.599
970321AG2-212 GEN
Solar/Wind Harmer
2.599
970349AG2-230 GEN
Solar/Wind Harmer
1.946
970373AG2-245 GEN
Solar/Wind Harmer
2.469
970513AG2-328 GEN
Solar/Wind Harmer
2.599
970517AG2-330 GEN
Solar/Wind Harmer
40.548
970521AG2-332 GEN
50/50
23.831
970611AG2-400 GEN
Solar/Wind Harmer
1.068
970707AG2-453 GEN
Solar/Wind Harmer
3.275
970833AG2-524 GEN
Solar/Wind Harmer
1.266
970833AG2-524 GEN
Solar/Wind Harmer
10.129
970941AG2-585 GEN
Solar/Wind Harmer
1.455
971347AH1-153 GEN
Solar/Wind Harmer
1.946
971549AH1-272 GEN
Solar/Wind Harmer
2.005
971599AH1-298 GEN
50/50
20.101
971605AH1-302 GEN
Solar/Wind Harmer
16.727
971769AH1-391 GEN
Solar/Wind Harmer
1.213
971771AH1-392 GEN
Solar/Wind Harmer
1.097
971917AH1-482 GEN
Solar/Wind Harmer
17.74
972181SS23-001
Solar/Wind Harmer
1.176
972207SS24-0001
Solar/Wind Harmer
3.581
972231SS25-0005
Solar/Wind Harmer
1.881
270100X2-052 CT1
50/50
3.113
270101X2-052 CT2
50/50
3.113
270102X2-052 ST
50/50
3.369
276843GEN-1.7
Solar/Wind Harmer
1.923
940581AE2-045 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
0
958011AF2-095 GEN
Solar/Wind Harmer
1.676
958381AF2-132 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
965011AG1-365 GEN
Solar/Wind Harmer
1.068
965021AG1-366 GEN
Solar/Wind Harmer
4.273
965101AG1-375 GEN
Solar/Wind Harmer
1.033
965651AG1-433 GEN
Solar/Wind Harmer
16.467
965681AG1-436 GEN
Solar/Wind Harmer
1.524
965791AG1-447 GEN
Solar/Wind Harmer
13.41
926823AC1-168 GEN
Solar/Wind Harmer
13.329
970901AG2-562 GEN
50/50
12.765
276668AB2-070 GEN1
Solar/Wind Harmer
7.391
276708O09 GEN2
Solar/Wind Harmer
13.059
276741O09 GEN1
Solar/Wind Harmer
13.059
276763AC1-053 GEN1
Solar/Wind Harmer
5.071
276764AC1-053 GEN2
Solar/Wind Harmer
5.071
276782AC1-033 GEN
Solar/Wind Harmer
13.828
276848AB2-070 GEN3
Solar/Wind Harmer
7.393
276849AB2-070 GEN2
Solar/Wind Harmer
7.391
944201AF1-088_MTX
Adder
164.946
957141AF2-008_MTX
Adder
82.473
NYPJM->LTFIMP_NY
CLTF
3.299
LGEELTFEXP_LGEE->PJM
CLTF
5.706
WECLTFEXP_WEC->PJM
CLTF
7.164
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.097
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.459
LAGNLTFEXP_LAGN->PJM
CLTF
14.212
CBM West 1LTFEXP_CBM-W1->PJM
CBM
222.098
CBM West 2LTFEXP_CBM-W2->PJM
CBM
133.912
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.451
TVALTFEXP_TVA->PJM
CLTF
5.473
MECLTFEXP_MEC->PJM
CLTF
26.098
SIGELTFEXP_SIGE->PJM
CLTF
0.559
AG2-052LTFEXP_AG2-052->PJM
LTF
0.442
AH1-155LTFEXP_AH1-155->PJM
LTF
0.663
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
42.769

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#1760_05JEFRSO 765_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.41 %
Rating:4961.0 MVA
Rating Type:B
MVA to Mitigate:4981.37
MW Contribution:13.73
Bus #Bus NameTypeMW Contribution
24690905MDL-1G C
Solar/Wind Harmer
30.87
24691005MDL-2G C
Solar/Wind Harmer
14.724
24697605MDL-3G C
Solar/Wind Harmer
14.701
24697905MDL-4G C
Solar/Wind Harmer
9.707
247642Z2-115 C
Solar/Wind Harmer
-0.001
24307105BERRINSP G
50/50
0.048
24344005CKG1
50/50
22.459
24344105CKG2
50/50
19.362
274847GR RIDGE ;BU
Solar/Wind Harmer
21.75
274848CAMPGROVE;RU
Solar/Wind Harmer
20.056
274851PROVIDENC;RU
Solar/Wind Harmer
10.555
274853TWINGROVE;U1
Solar/Wind Harmer
26.481
274854TWINGROVE;U2
Solar/Wind Harmer
26.202
274855GSG-6 ;RU
Solar/Wind Harmer
14.825
274856ECOGROVE ;U1
Solar/Wind Harmer
13.423
274861TOP CROP ;1U
Solar/Wind Harmer
23.557
274862TOP CROP ;2U
Solar/Wind Harmer
19.567
274871GR RIDGE ;2U
Solar/Wind Harmer
28.423
274877BISHOP HL;1U
Solar/Wind Harmer
12.834
274878BISHOP HL;2U
Solar/Wind Harmer
12.834
274879MINONK ;1U
Solar/Wind Harmer
27.571
274888KELLY CRK;1U
Solar/Wind Harmer
25.103
24385905FR-11G C
Solar/Wind Harmer
17.109
24386205FR-12G C
Solar/Wind Harmer
9.086
24386405FR-21G C
Solar/Wind Harmer
8.703
24386605FR-22G C
Solar/Wind Harmer
8.703
24387005FR-3G C
Solar/Wind Harmer
8.616
24387305FR-4G C
Solar/Wind Harmer
13.054
274849CRESCENT ;1U
Solar/Wind Harmer
7.294
276602WESTBROOK C
Solar/Wind Harmer
8.175
276603SUBLETTE C
Solar/Wind Harmer
3.862
24755605MDL-5G
Solar/Wind Harmer
9.707
274850MENDOTA H;RU
Solar/Wind Harmer
10.5
276691AA1-018 GEN1
Solar/Wind Harmer
1.287
276694AA1-018 GEN2
Solar/Wind Harmer
23.067
274872LEEDK;1U
Solar/Wind Harmer
34.229
274872LEEDK;1U
Solar/Wind Harmer
0.519
276646AC1-214 GEN2
Solar/Wind Harmer
4.778
276645AC1-214 GEN1
Solar/Wind Harmer
4.778
276806AD2-047 C O1
Solar/Wind Harmer
38.087
276901AD2-066 C O1
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
-0.001
276897AD1-100 C
Solar/Wind Harmer
126.162
270142AC1-141 CT1_
50/50
5.381
270143AC1-141 CT2_
50/50
5.381
270144AC1-141 ST1_
50/50
4.766
270180AB1-006 GEN1
Solar/Wind Harmer
27.585
270181AB1-006 GEN2
Solar/Wind Harmer
1.829
276889AE2-281 GEN
Solar/Wind Harmer
7.407
276872AE1-163_GEN1
Solar/Wind Harmer
25.923
276876AE1-163_GEN2
Solar/Wind Harmer
25.923
276882AE2-255 GEN
Solar/Wind Harmer
12.436
276868AE1-113 GEN
Solar/Wind Harmer
39.421
276861AD2-134 GEN
Solar/Wind Harmer
7.166
276863AD2-134 GEN
Solar/Wind Harmer
7.166
276655WTG1_EQ
Solar/Wind Harmer
18.863
270449AD2-020 GEN
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
21.371
270471AD2-092_GEN
Solar/Wind Helper
0.687
270349AD2-093_GEN
Solar/Wind Helper
0.687
270505AE1-170 C O1
Solar/Wind Harmer
1.938
270043AE2-236 GEN
Solar/Wind Harmer
0.71
270063AE2-323 C
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
270071AF1-092 GEN
Solar/Wind Harmer
1.926
24791305MDL-5G
Solar/Wind Harmer
9.707
274857EASY ROAD;U1
Solar/Wind Harmer
17.754
274858EASY ROAD;U2
Solar/Wind Harmer
17.754
274863CRW1-WTG
Solar/Wind Harmer
21.955
274864CRW2-WTG
Solar/Wind Harmer
21.955
274880W4-005 GEN4
Solar/Wind Harmer
7.56
938861AE1-114 GEN
Solar/Wind Harmer
26.61
942111AE2-223 GEN
Solar/Wind Harmer
25.633
942991AE2-321 GEN
Solar/Wind Harmer
1.174
943121AE2-341 GEN
Solar/Wind Harmer
1.821
945421AF1-207 GEN
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
32.251
946581AF1-322 GEN
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
1.793
958491AF2-143 GEN
Solar/Wind Harmer
1.769
959081AF2-199 GEN
Solar/Wind Harmer
1.159
959091AF2-200 GEN
Solar/Wind Harmer
2.318
959341AF2-225 GEN
Solar/Wind Harmer
1.643
959611AF2-252 GEN
Solar/Wind Harmer
4.294
960611AF2-352 GEN
Solar/Wind Harmer
4.294
961011AF2-392 GEN
Solar/Wind Harmer
34.864
962691AG1-118 GEN
Solar/Wind Harmer
3.56
962781AG1-127 GEN
Solar/Wind Harmer
1.125
966841AG1-555 GEN
Solar/Wind Harmer
0
970169AG2-114 GEN
Solar/Wind Harmer
1.141
970239AG2-162 GEN
Solar/Wind Harmer
1.524
970241AG2-163 GEN
Solar/Wind Harmer
2.585
970243AG2-164 GEN
Solar/Wind Harmer
3.577
970289AG2-191 GEN
Solar/Wind Harmer
0.195
970289AG2-191 GEN
Solar/Wind Harmer
1.352
970291AG2-192 GEN
Solar/Wind Harmer
0.133
970291AG2-192 GEN
Solar/Wind Harmer
1.229
970333AG2-219 GEN
Solar/Wind Harmer
4.372
970519AG2-331 GEN
Solar/Wind Harmer
41.339
970569AG2-363 GEN
Solar/Wind Harmer
3.426
970571AG2-364 GEN
Solar/Wind Harmer
2.284
970699AG2-449 GEN
Solar/Wind Harmer
1.59
970781AG2-491 GEN
Solar/Wind Harmer
1.172
970819AG2-516 GEN
Solar/Wind Harmer
1.377
970921AG2-575 GEN
Solar/Wind Harmer
1.183
970921AG2-575 GEN
Solar/Wind Harmer
4.733
971067AG2-660 GEN
Solar/Wind Harmer
4.636
971171AH1-044 GEN
Solar/Wind Harmer
2.318
971177AH1-047 GEN
Solar/Wind Harmer
0.687
971333AH1-146 GEN
Solar/Wind Harmer
2.334
971335AH1-147 GEN
Solar/Wind Harmer
2.334
971341AH1-150 GEN
Solar/Wind Harmer
2.318
971343AH1-151 GEN
Solar/Wind Harmer
2.318
971411AH1-196 GEN
Solar/Wind Harmer
1.752
971475AH1-234 GEN
Solar/Wind Harmer
2.562
971573AH1-285 GEN
Solar/Wind Harmer
1.038
971675AH1-338 GEN
Solar/Wind Harmer
2.102
971681AH1-341 GEN
Solar/Wind Harmer
1.706
276157O29GEN1
Solar/Wind Harmer
16.305
276158O29GEN2
Solar/Wind Harmer
16.305
276174W4-005 GEN2
Solar/Wind Harmer
7.56
276656WTG2_EQ
Solar/Wind Harmer
2.498
276686W4-005 GEN3
Solar/Wind Harmer
7.56
276726Z2-087_GEN
Solar/Wind Harmer
28.481
276785W4-005 GEN1
Solar/Wind Harmer
7.56
939401AE1-172 GEN
Solar/Wind Harmer
46.994
939741AE1-205 GEN
Solar/Wind Harmer
2.191
941731AE2-173 GEN
Solar/Wind Harmer
10.954
957471AF2-041 GEN
Solar/Wind Harmer
3.477
957751AF2-069 GEN
Solar/Wind Harmer
1.458
963741AG1-226 GEN
Solar/Wind Harmer
4.654
963841AG1-237 GEN
Solar/Wind Harmer
33.488
965091AG1-374 GEN
Solar/Wind Harmer
3.22
965931AG1-462 GEN
Solar/Wind Harmer
2.743
971997AH1-543 GEN
Solar/Wind Harmer
1.844
972175AH1-670 GEN
Solar/Wind Harmer
40.448
24639705ELKHART HY
50/50
0.359
24641605TWIN BRNCH
50/50
0.039
24642205MAYFLWER
50/50
1.656
24643105BUCHANAN
50/50
0.028
24653605MOTTVILLE
50/50
0.008
274887GEN-1.85
Solar/Wind Harmer
23.06
939351AE1-166 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
8.008
943591AF1-030 GEN
Solar/Wind Harmer
1.214
944231AF1-091 GEN
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
4.156
944541AF1-119 GEN
Solar/Wind Harmer
0
944961AF1-161 GEN
50/50
6.392
945111AF1-176 GEN
Solar/Wind Harmer
2.29
945111AF1-176 GEN
Solar/Wind Harmer
12.484
945371AF1-202 GEN
Solar/Wind Harmer
15.713
945581AF1-223 GEN
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
32.945
959141AF2-205 GEN
Solar/Wind Harmer
0
959331AF2-224 GEN
Solar/Wind Harmer
1.123
960591AF2-350 GEN
Solar/Wind Harmer
1.237
960681AF2-359 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
33.741
961051AF2-396 GEN
Solar/Wind Harmer
2.561
961051AF2-396 GEN
Solar/Wind Harmer
20.485
962601AG1-109 GEN
50/50
6.392
963791AG1-232 GEN
Solar/Wind Harmer
1.357
970031AG2-029 GEN
Solar/Wind Harmer
3.677
970245AG2-165 GEN
Solar/Wind Harmer
2.888
970321AG2-212 GEN
Solar/Wind Harmer
2.888
970349AG2-230 GEN
Solar/Wind Harmer
2.09
970373AG2-245 GEN
Solar/Wind Harmer
2.675
970513AG2-328 GEN
Solar/Wind Harmer
2.888
970517AG2-330 GEN
Solar/Wind Harmer
45.053
970521AG2-332 GEN
50/50
25.509
970611AG2-400 GEN
Solar/Wind Harmer
1.123
970707AG2-453 GEN
Solar/Wind Harmer
3.479
970833AG2-524 GEN
Solar/Wind Harmer
1.342
970833AG2-524 GEN
Solar/Wind Harmer
10.74
970941AG2-585 GEN
Solar/Wind Harmer
1.546
971347AH1-153 GEN
Solar/Wind Harmer
2.09
971549AH1-272 GEN
Solar/Wind Harmer
2.153
971599AH1-298 GEN
50/50
21.036
971605AH1-302 GEN
Solar/Wind Harmer
18.291
971769AH1-391 GEN
Solar/Wind Harmer
1.303
971771AH1-392 GEN
Solar/Wind Harmer
1.176
971917AH1-482 GEN
Solar/Wind Harmer
19.33
972181SS23-001
Solar/Wind Harmer
1.253
972207SS24-0001
Solar/Wind Harmer
3.811
972231SS25-0005
Solar/Wind Harmer
2.005
270100X2-052 CT1
50/50
3.348
270101X2-052 CT2
50/50
3.348
270102X2-052 ST
50/50
3.624
276843GEN-1.7
Solar/Wind Harmer
2.043
940581AE2-045 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
0
958011AF2-095 GEN
Solar/Wind Harmer
1.781
958381AF2-132 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
965011AG1-365 GEN
Solar/Wind Harmer
1.123
965021AG1-366 GEN
Solar/Wind Harmer
4.491
965101AG1-375 GEN
Solar/Wind Harmer
1.056
965651AG1-433 GEN
Solar/Wind Harmer
16.87
965681AG1-436 GEN
Solar/Wind Harmer
1.638
965791AG1-447 GEN
Solar/Wind Harmer
14.413
926823AC1-168 GEN
Solar/Wind Harmer
14.021
970901AG2-562 GEN
50/50
13.732
276708O09 GEN2
Solar/Wind Harmer
13.724
276741O09 GEN1
Solar/Wind Harmer
13.724
276782AC1-033 GEN
Solar/Wind Harmer
14.5
944201AF1-088_MTX
Adder
148.128
957141AF2-008_MTX
Adder
74.064
NYPJM->LTFIMP_NY
CLTF
3.326
LGEELTFEXP_LGEE->PJM
CLTF
4.567
WECLTFEXP_WEC->PJM
CLTF
7.559
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.261
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.568
LAGNLTFEXP_LAGN->PJM
CLTF
13.768
CBM West 1LTFEXP_CBM-W1->PJM
CBM
232.762
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.171
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.173
TVALTFEXP_TVA->PJM
CLTF
5.095
MECLTFEXP_MEC->PJM
CLTF
26.993
SIGELTFEXP_SIGE->PJM
CLTF
0.513
AG2-052LTFEXP_AG2-052->PJM
LTF
0.47
AH1-155LTFEXP_AH1-155->PJM
LTF
0.706
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
52.01
CONTINGENCY 'AEP_P1-2_#7441_100545_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'AEP_P4_#1760_05JEFRSO 765_A_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290599 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RG 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 970238 TO BUS 290599 CKT 1    /*AG2-162 TP   765.0 - 05JEFFRSN_RG 765.0
END
CONTINGENCY 'AEP_P4_#6189_05HANG R 765_D1_SRT-A'
 OPEN BRANCH FROM BUS 242921 TO BUS 242924 CKT 1    /*05CORNU      765.0 - 05HANG R     765.0
 OPEN BRANCH FROM BUS 242921 TO BUS 242934 CKT 1    /*05CORNU      765.0 - 05CORNU      345.0
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
 REMOVE UNIT 1A FROM BUS 247245                     /*05HRKG1A      18.0
 REMOVE UNIT 1B FROM BUS 247246                     /*05HRKG1B      18.0
 REMOVE UNIT 1S FROM BUS 247247                     /*05HRKG1S      18.0
 REMOVE UNIT 2A FROM BUS 247248                     /*05HRKG2A      18.0
 REMOVE UNIT 2B FROM BUS 247249                     /*05HRKG2B      18.0
 REMOVE UNIT 2S FROM BUS 247250                     /*05HRKG2S      18.0
END
CONTINGENCY 'AEP_P1-2_#709_546_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
CONTINGENCY 'AEP_P4_#709_05HANG R 765_D2_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
CONTINGENCY 'AEP_P4_#7334_05JEFRSO 765_A2_SRT-A'
 OPEN BRANCH FROM BUS 242865 TO BUS 243208 CKT 2    /*05JEFRSO     345.0 - 05JEFRSO     765.0
 OPEN BRANCH FROM BUS 242865 TO BUS 248000 CKT 1    /*05JEFRSO     345.0 - 06CLIFTY     345.0
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
243211 to 242933 ckt 1
243206 to 290606 ckt Z1
243208 to 242865 ckt 2
242865 to 248000 ckt 1
290608 to 242928 ckt Z1

Light Load Analysis

The New Service Request AG2-562 was evaluated as a 52.0 MW injection

AG2-562 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 767.0 MW (52.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

(No impacts were found for this analysis)

Short Circuit Analysis

Short Circuit analysis is not performed as part of the Phase I System Impact Study. Short Circuit analysis will commence in the Phase II System Impact Study.

Stability Analysis

Stability analysis is not performed as part of the Phase I System Impact Study. Stability analysis will commence in the Phase II System Impact Study.

Reactive Power Analysis

Reactive Power analysis is not performed as part of the Phase I System Impact Study. Reactive Power analysis will commence in the Phase II System Impact Study.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-018Powerton-Goodings GroveIn Service
AB1-006Meadow Lake 345kVIn Service
AB1-087Sullivan 345kV #1Under Construction
AB1-088Sullivan 345kV #2Engineering & Procurement
AB2-070Mt. Pulaski-BrokawIn Service
AB2-170East Lima-Marysville 345kVIn Service
AC1-033Kewanee 138 kVIn Service
AC1-053Lanesville-BrokawPartially in Service - Under Construction
AC1-068Atlanta 69kV IIn Service
AC1-069Atlanta 69kV IIIn Service
AC1-074Jacksonville-Renaker 138kV IIn Service
AC1-085Stuart-Clinton 345kVIn Service
AC1-089Hillsboro-Wildcat 138kVIn Service
AC1-141Cook-East Elkhart 345kVIn Service
AC1-165Atlanta 69kV IIIIn Service
AC1-166Atlanta 69kV IVIn Service
AC1-168Kewanee-StreatorSuspended
AC1-214Crescent RidgeIn Service
AC2-015Chatfield-Howard 138kVPartially in Service - Under Construction
AC2-060Buckskin 69kVIn Service
AC2-061Hillsboro-Clinton 138kVIn Service
AC2-075Jacksonville-Renaker 138 kVIn Service
AC2-088S. Bethel-Brown 69kVIn Service
AC2-157Sullivan 345 kVUnder Construction
AC2-176Jay 138 kVIn Service
AC2-195Galion-Roberts South 138 kVUnder Construction
AD1-100Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVUnder Construction
AD1-130Hardin Switch 345 kVIn Service
AD1-136South Bethel-Brown 69 kVIn Service
AD1-140Greene-Clark 138 kVEngineering & Procurement
AD2-020Valley 138 kVEngineering & Procurement
AD2-031Martinsville-Wilmington 69 kVIn Service
AD2-038Powerton-Nevada 345 kVUnder Construction
AD2-047Davis Creek 138 kVSuspended
AD2-048Cynthia-Headquarters 69 kVUnder Construction
AD2-066Mazon-Crescent Ridge 138 kVEngineering & Procurement
AD2-071Strawton-Deer Creek 138 kVSuspended
AD2-086Hardin Switch 345 kVIn Service
AD2-092Marysville 345kVUnder Construction
AD2-093Marysville 345kVUnder Construction
AD2-100Kincaid-Pana 345 kVSuspended
AD2-131Kincaid-Pana 345kVSuspended
AD2-134Shady OaksPartially in Service - Under Construction
AE1-040Greenfield 69 kVIn Service
AE1-090Hardin Switch 345 kVIn Service
AE1-113Mole Creek 345 kVEngineering & Procurement
AE1-114Maryland-Lancaster 138 kVActive
AE1-143Marion County 161 kVEngineering & Procurement
AE1-146Ebersole #2-Fostoria Central 138 kVUnder Construction
AE1-163Powerton-Nevada 345 kVEngineering & Procurement
AE1-166Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE1-170Kenzie Creek-Colby 138 kVSuspended
AE1-172Loretto-Wilton CenterActive
AE1-205McLean 345 kVEngineering & Procurement
AE1-207Mississinewa-Gaston 138 kVSuspended
AE1-208Delaware-Van Buren 138 kVSuspended
AE1-209Desoto 345 kVSuspended
AE1-210Desoto 345 kVSuspended
AE2-045Olive-Reynolds 345 kVEngineering & Procurement
AE2-071Patton Rd-Summer Shade 69 kVIn Service
AE2-072East Leipsic-Richland 138 kVIn Service
AE2-089Pennville-Adams 138 kVEngineering & Procurement
AE2-148Beatty-Greene 345 kVIn Service
AE2-152Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE2-169Delaware-Van Buren 138 kVSuspended
AE2-172Mississinewa-Gaston 138 kVSuspended
AE2-173McLean 345 kVActive
AE2-206East Sidney-Quincy 138 kVIn Service
AE2-221Clinton-Stuart 345 kVUnder Construction
AE2-223McLean 345 kVActive
AE2-236Columbia-Northeast 138 kVSuspended
AE2-254Garrard County-Tommy-Gooch 69 kVIn Service
AE2-255Molecreek 345 kVEngineering & Procurement
AE2-261Kincaid-Pana 345 kVActive
AE2-267Woodsdale 345 kVEngineering & Procurement
AE2-276Sullivan 345kVEngineering & Procurement
AE2-281Powerton-Nevada 345 kVEngineering & Procurement
AE2-306Gunn Road 345 kVUnder Construction
AE2-321Belvidere-Marengo 138 kVActive
AE2-323Twin Branch-Guardian 138 kVUnder Construction
AE2-325Valley 138 kVActive
AE2-339Avon 138 kVEngineering & Procurement
AE2-341Sandwich-Plano 138 kVActive
AF1-030Sandwich-Plano 138 kVActive
AF1-038Sewellton Jct-Webbs Crossroads 69 kVEngineering & Procurement
AF1-050Summer Shade - Green County 161 kVEngineering & Procurement
AF1-071College Corner 138 kVEngineering & Procurement
AF1-078East Sidney-Quincy 138 kVIn Service
AF1-083Green County-Saloma 161 kVEngineering & Procurement
AF1-088Sullivan 345 kVActive
AF1-090Kincaid-PanaEngineering & Procurement
AF1-091Varner - Sowers 138 kVEngineering & Procurement
AF1-092Huntington Jct. 138 kVSuspended
AF1-118Sorenson-Desoto 345 kVEngineering & Procurement
AF1-119Keystone-Desoto 345 kVEngineering & Procurement
AF1-158Edison-Gravel Pit 138 kVIn Service
AF1-161Valley 138 kVActive
AF1-176Corey 138 kVActive
AF1-202Keystone-Desoto 345 kVUnder Construction
AF1-203Patton Rd-Summer Shade 69 kVIn Service
AF1-204Eugene 345 kVActive
AF1-207Reynolds-Olive #1 345 kVEngineering & Procurement
AF1-215Olive-Reynolds 345 kVIn Service
AF1-223Keystone-Desoto 345 kVUnder Construction
AF1-227Marysville – Gunn Road 345 kVIn Service
AF1-229Galion-South Berwick 345 kVEngineering & Procurement
AF1-249Nickel 12.47 kVIn Service
AF1-268Desoto-Jay 138 kVEngineering & Procurement
AF1-285Gunn Road 345 kVUnder Construction
AF1-296Garden Plain 138 kVActive
AF1-322Meadow Lake 345 kVEngineering & Procurement
AF2-008Sullivan 345 kVActive
AF2-014Maddox Creek 345 kVEngineering & Procurement
AF2-041Nelson-Electric Junction 345 kVActive
AF2-068Jay 138 kVActive
AF2-069Crescent Ridge 138 kVActive
AF2-078Reynolds-Olive #1 345 kVEngineering & Procurement
AF2-083Kenzie Creek-Stone Lake 69 kVUnder Construction
AF2-095Davis Creek 138 kVActive
AF2-122Kirk 138 kVUnder Construction
AF2-132Reynolds-Olive #1 345 kVUnder Construction
AF2-133Reynolds-Olive #2 345 kVUnder Construction
AF2-134Olive-Reynolds #2 345 kVIn Service
AF2-142Nevada 345 kVActive
AF2-143Powerton-Nevada 345 kVActive
AF2-150Galion 138 kVUnder Construction
AF2-173Desoto 345 kVActive
AF2-177Sorenson-DeSoto #2 345 kVActive
AF2-199Nelson-Electric Junction 345 kVActive
AF2-200Nelson-Electric Junction 345 kVActive
AF2-205Olive-Reynolds #2 345 kVEngineering & Procurement
AF2-224Allen 345 kVEngineering & Procurement
AF2-225McLean 345 kVActive
AF2-252Blue Mound 345 kVEngineering & Procurement
AF2-335Delaware-Royerton 138 kVActive
AF2-350Kensington 138 kVActive
AF2-352Blue Mound 345 kVEngineering & Procurement
AF2-359Olive-University Park 345 kVEngineering & Procurement
AF2-370Delaware-Royerton 138 kVActive
AF2-375Ebersole-Fostoria 138 kVEngineering & Procurement
AF2-376Timber Switch 138 kVActive
AF2-377Logtown 138 kVEngineering & Procurement
AF2-388Keystone-Desoto 345 kVActive
AF2-392Nelson-Dixon 138 kVActive
AF2-396Stinger 138 kVActive
AF2-440Hillsboro-Middleboro 138 kVEngineering & Procurement
AG1-017Jay 138 kVUnder Construction
AG1-039Galion 138 kV IIUnder Construction
AG1-047Jay 138 kVEngineering & Procurement
AG1-066Bonnyman 69 kVEngineering & Procurement
AG1-107Hillsboro-Middleboro 138 kVEngineering & Procurement
AG1-109Valley 138 kVActive
AG1-118Sugar Grove-Waterman 138kVActive
AG1-127Crego Rd 138 kVActive
AG1-226Dequine-Eugene 345 kVActive
AG1-232Magley 138 kVEngineering & Procurement
AG1-236Lanesville-Brokaw 345 kVActive
AG1-237Dequine-Eugene 345 kVEngineering & Procurement
AG1-302Olive-Reynolds #1 345 kVUnder Construction
AG1-324Jay-Desoto 138 kVEngineering & Procurement
AG1-349Olive-Reynolds #2 345 kVEngineering & Procurement
AG1-365Allen 345 kVEngineering & Procurement
AG1-366Allen 345 kVEngineering & Procurement
AG1-367DeSoto 345 kVActive
AG1-368Tillman 138 kVEngineering & Procurement
AG1-369Logtown 138 kVEngineering & Procurement
AG1-374Blue Mound 345 kVActive
AG1-375Sorenson-Desoto 345 kVActive
AG1-433Keystone-DeSoto 345 kVActive
AG1-436Olive-University Park 345 kVActive
AG1-447Olive-University Park 345 kVActive
AG1-460Kincaid-Pana 345 kVActive
AG1-462Cordova 345 kVActive
AG1-478Wilmington 34.5 kVEngineering & Procurement
AG1-554South Kenton 138 kVEngineering & Procurement
AG1-555Dequine 345 kVEngineering & Procurement
AG2-014Meadow Lake 345 kVActive
AG2-029Forest G. Hipple-Collingwood 345 kVActive
AG2-072Rockport 765 kVActive
AG2-085Delaware-Royerton 138 kVActive
AG2-114Dresden-Pontiac Midpoint 345 kVActive
AG2-126Eugene 345 kVActive
AG2-162Jefferson-Greentown 765 kVActive
AG2-163Dequine-Eugene 345 kVActive
AG2-164Jefferson-Greentown 765 kVActive
AG2-165Dumont-Greentown 765 kVActive
AG2-191Mississinewa 138 kVActive
AG2-192Mississinewa 138 kVActive
AG2-212Dumont-Greentown 765 kVActive
AG2-219Jefferson-Greentown 765 kVActive
AG2-230Dumont 345 kVActive
AG2-245Olive - Reynolds #1 345 kVActive
AG2-328Dumont - Greentown 765 kVActive
AG2-330Dumont - Greentown 765 kVActive
AG2-331Jefferson-Greentown 765 kVActive
AG2-332East Elkhart – Elcona Tap 138 kVActive
AG2-343Eugene - Dequine 345 kVActive
AG2-344Dequine 345 bkVActive
AG2-345Eugene - Dequine 345 kVActive
AG2-363Powerton 345 kVActive
AG2-364Powerton 345 kVActive
AG2-370Tillman 138 kVActive
AG2-400Allen 345 kVActive
AG2-402Allen 345 kVActive
AG2-449Jefferson-Greentown 765 kVActive
AG2-453Lasalle - Plano 345 kVActive
AG2-491Meadow Lake 345 kVActive
AG2-492Meadow Lake 345 kVActive
AG2-516Pecatonica 138kVActive
AG2-519Royerton - Desoto 138 kVActive
AG2-524LaSalle Station - Mazon 138 kVActive
AG2-575Crego Rd. 138 kVActive
AG2-585Kensington 138kVActive
AG2-660Nelson-Electric Junction 345 kVActive
AH1-044Nelson - Electric Junction 345 kVActive
AH1-047Marengo - Belvidere 138 kVActive
AH1-146White Rock - Wayne 345 kVActive
AH1-147White Rock - Wayne 345 kVActive
AH1-150Nelson-Electric Junction 345 kVActive
AH1-151Nelson-Electric Junction 345 kVActive
AH1-153Dumont 345 kVActive
AH1-196Prairie 345 kVActive
AH1-234Wempletown - Paddock 345 kVActive
AH1-272Argenta - Twin Branch 345 kVActive
AH1-285Sandwich 138 kVActive
AH1-298Meridian 345 kVActive
AH1-302Olive - Reynolds 345 kVActive
AH1-308Pennville - Adams 138 kVActive
AH1-338McGirr Rd - Ritchie Road 138kVActive
AH1-341Stillman - Dixon 138KVActive
AH1-391Olive 138 kVActive
AH1-392Gravel Pit-Kankakee 138 kVActive
AH1-482Olive - Reynolds #2 345 kVActive
AH1-541Chestnut 345 kVActive
AH1-543Mulberry – Tazewell 345 kVActive
AH1-670Blue Mound-Chestnut 345 kVActive
AH1-714Lasalle 345 kVActive
U2-072East Lima-Marysville 345kVIn Service
V4-073Yankee 12.5kVIn Service
W1-056Ada-Dunkirk 69kVIn Service
W2-048Brokaw-LanesvilleIn Service
W4-005Blue Mound-LathamIn Service
X2-022Brokaw-LanesvilleIn Service
X2-052Dumont-Olive 345kVIn Service
Y3-023Country Side 12kVIn Service
Z2-087Pontiac MidPoint-Brokaw 345kVIn Service
Z2-115Deer Creek 12.47kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with potential Affected System impacts. PJM initiates coordination with each Affected System Operator by providing a list of New Service Requests in the Cycle with potential impacts to their respective system. If the Affected System Operator indicates an Affected System Study is required, PJM will notify the Project Developer or Eligible Customer of the need for an Affected System Study. See below if any Affected System Operator requires a study for this project:

Midcontinent Independent System Operator, Inc. (MISO)Study Pending
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

No cost allocated system reinforcements were identified for this project in the Phase I System Impact Study load flow analysis.

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18693
Title
Greentown 765 kV to Marysville 765 kV - Greenfield Line
Description
Construct a new greenfield 765kV line from Greentown to Marysville (~160 miles). Install 2 new 765kV breakers at Marysville and 2 new 765kV breakers at Greentown. Install 765kV shunt reactors at both Marysville and Greentown The new 765kV line reduces equipment at Dumont to be replaced to CB A2 and switch A2S2. s3442.26 replaces Dumont 765kV CB A2 and A2S2 "CONTINGENCY 'AEP_P1-2_GREENTOWN TO MARYSVILLE 765_SRT-A' OPEN BRANCH FROM BUS 242928 TO BUS 243207 CKT 1 / 242928 05MARYSV 765 243207 05GRNTWN 765 1 END CONTINGENCY 'AEP_P4_GREENTOWN CB 765_SRT-A' OPEN BRANCH FROM BUS 242928 TO BUS 243207 CKT 1 / 242928 05MARYSV 765 243207 05GRNTWN 765 1 END CONTINGENCY 'AEP_P4_MARYSVILLE CB 765_SRT-A' OPEN BRANCH FROM BUS 242928 TO BUS 243207 CKT 1 / 242928 05MARYSV 765 243207 05GRNTWN 765 1 END"
Total Cost ($USD)
$1,000,000,000
Allocated Cost ($USD)
$0
Time Estimate
72 to 120 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-562 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-562 could receive cost allocation. Although AG2-562 may not presently have cost responsibility for this upgrade, AG2-562 is a potential Aggregate Pool Contributor.

FacilityContingency
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line(Any)

System Reinforcement: n9243.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9243.0 / AEPSERG13
Title
Expand Jefferson 345 kV station. Install a second 765/345 kV 750 MVA transformer. Install a second Jefferson - Clifty Creek 345 kV single circuit ~0.8 miles.
Description
At the Jefferson Station: • Expand the northeast corner of the station • Remove Circuit breaker C1 • Install one (1) new 765/345 kV transformer and associated equipment • Install one (1) new 765 kV circuit breaker with associated control relaying and breaker disconnect switches • Install one (1) new 345 kV circuit breaker with associated control relaying and breaker disconnect switches • Install a new station service center At the Clifty Creek Station: • Extend 345 kV bus 1 and 2 to make room for a new breaker string • Move a section of the 138 kV bus underground to make room for the new breaker string • Relocate circuit breaker S to the new string • Install two (2) new 345 kV circuit breakers on the new string •Remove the existing Jefferson – Clifty Creek 345 kV line •Construct a new Jefferson – Clifty Creek 345 kV double circuit line •Evaluate line settings for all appropriate lines •Install direct fiber relaying between the Jefferson and Clifty Creek station •Associated conductors (buswork, ground grid, jumpers), telecom terminal equipment, insulators, arresters, foundations, and structures
Total Cost ($USD)
$200,238,000
Allocated Cost ($USD)
$0
Time Estimate
55 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-562 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-562 could receive cost allocation. Although AG2-562 may not presently have cost responsibility for this upgrade, AG2-562 is a potential Aggregate Pool Contributor.

FacilityContingency
05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line(Any)
05JEFRSO-05JEFRSO 345.0/765.0 kV Ckt 2 transformer(Any)

System Reinforcement: b3878.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3878.1
Title
Upgrade 765 kV circuit breakers 'B' and 'B2' to 5000A 50kA breakers at Marysville Station
Description
Upgrade 765 kV circuit breakers 'B' and 'B2' to 5000A 50kA breakers at Marysville Station. In addition, the project will upgrade the existing wavetrap towards Sorenson.
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-562 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-562 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MARYSV-05MARYSVL_RS 765.0 kV Ckt Z1 line(Any)

System Reinforcement: b3851.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3851.1 / B3851.1
Title
Rebuild Allen-RP Mone 345kV
Description
Rebuild Allen –R.P. Mone 345kV line (18.6 miles).
Cost Information
Time Estimate
Jun 01 2027

Not Contingent

Note: AG2-562 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-562 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05RPMONE-05ALLEN 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18707
Title
05ALLEN 345.0 kV to 05RPMONE 345.0 kV ckt 1 - Replace Equipment
Description
At RP Mone: Replace CB B and B2 and associated disconnect switches. Replace 2 - 1700 KCM AAC station conductor. At Allen: Replace the disconnect switches for CBs C and C2 at Allen. Replace 2 - 2000 KCM AAC station conductor. B3851.1 to rebuild the Allen - RP Mone line needs to be completed. CB B is also be proposed to be replaced on another flowgate
Total Cost ($USD)
$5,000,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-562 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-562 could receive cost allocation. Although AG2-562 may not presently have cost responsibility for this upgrade, AG2-562 is a potential Aggregate Pool Contributor.

FacilityContingency
05RPMONE-05ALLEN 345.0 kV Ckt 1 line(Any)

Attachments

AG2-562 One Line Diagram

AG2-562 One Line Diagram.jpg
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.