AG2-582 Phase I Study Report

v1.00 released 2025-10-29 22:16

Flint Run 500 kV

2075.0 MW Capacity / 2100.0 MW Energy

Introduction

This Phase I System Impact Study Report (PH1) has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, sections 307 and 308 for New Service Requests (projects) in Transition Cycle 2. The Project Developer/Eligible Customer (developer) is CPV Shay, LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Monongahela Power Company.

Preface

The Phase I System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle executive summary format and (ii) an individual project-level basis. The Phase I System Impact Study Results (for both the executive summary and individual reports) will be publicly available on PJM’s website. Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.3, PJM takes the following actions during the Phase I System Impact Study:
  1. PJM studies each New Service Request on a summer peak, winter peak and light load RTEP base case study. The case year is dependent on the new services cycle under study. PJM will identify the base case year to be used in the study of a specific cycle on its website.
  2. PJM will only perform load flow analysis during the Phase I System Impact Study.
  3. In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with Affected System impacts and provides each Affected System Operator with a list of New Service Request in the Cycle with potential impacts to their respective system.
  4. PJM will create both the short circuit and stability base cases to be used in the Phase II System Impact Study.
  5. The Phase I System Impact Study results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.
The Transmission Owner takes the following actions during the Phase I System Impact Study:
  1. Identify required Interconnection Facilities to accommodate the New Service Request.
  2. Identify required Network Upgrades to mitigate system violations from the Phase I System Impact Study.
  3. Provide planning-level preliminary estimates of Interconnection Facilities and Network Upgrades including scope, cost and elapsed time to complete the work.

Decision Point I Requirements

At the close of Phase I System Impact Study, PJM will initiate Decision Point I (DP1). During DP1, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.A.1. Additional information on these elements is available in PJM Manual 14H sections 4.4, 6, and 7.

Allowable project modifications at Decision Point I are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

General

The Project Developer has proposed a Natural Gas generating facility located in the Monongahela Power Company zone — Doddridge County, West Virginia. The installed facilities will have a total capability of 2100.0 MW with 2075.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AG2-582
Project Name:
Flint Run 500 kV
Project Developer Name:
CPV Shay, LLC
State:
West Virginia
County:
Doddridge
Transmission Owner:
Monongahela Power Company
MFO:
2100.0
MWE:
2100.0
MWC:
2075.0
Fuel Type:
Natural Gas
Basecase Study Year:
2028

Physical Interconnection Facility Study

Physical Interconnection Facilities Study is not performed as part of the Phase I System Impact Study. Physical Interconnection Facilities Study will commence in the Phase II System Impact Study.

Point of Interconnection

AG2-582 will interconnect on the Monongahela Power Company transmission system as a direct connect at the Flint Run 500 kV substation.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In the Phase I SIS, the costs shown are subject to change as a result of a facility study performed by the TO during the Phase II or Phase III System Impact Study.

Based on the Phase I SIS results, the AG2-582 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit are also shown below.

Cost Summary
DescriptionCost Allocated to AG2-582Cost Subject to Readiness*
Transmission Owner Interconnection Facilities (TOIF)$7,130,657$0
Other Scope$60,800$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0
Network Upgrades$0$0
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$174,887,472$174,887,472
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$0$0
Total$182,078,929$174,887,472

* Contributes to calculation for Readiness Deposit #2 (RD2). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 309 (Decision Point I) A.1.a.i and PJM Manual 14H, section 6.2, Readiness Deposit #2 (RD2) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point I (DP1), the Project Developer or Eligible Customer is required to submit Readiness Deposit #2, which is calculated as 10% of cost allocation for required Phase I Network Upgrades minus Readiness Deposit #1.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Readiness Deposit #2 Due for Project AG2-582

Readiness Deposit #2 has been calculated for the project based on the Phase I System Impact Study results and is shown in the table below. This Readiness Deposit #2 must be provided at Decision Point I through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit
Project ID10% of cost allocation for Phase I Network UpgradesReadiness Deposit #1 Received (RD1)Readiness Deposit #2 (RD2) for AG2-582 Project due at DP1
ABA - B
AG2-582$17,488,747$8,400,000$9,088,747

Note: Failure to provide an acceptable form of Readiness Deposit #2 by the end of Decision Point I will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Interconnection Facilities
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)Integrate Interconnection Facilities protection and controls to the transmission system.$63,840 $63,840
(Pending)Expand the existing Flint Run substation, add one (1) new circuit breaker with SCADA controls.$6,245,891 $6,245,891
(Pending)Construct one span of 500kV circuit from Flint Run substation to the Point of Change in Ownership outside the substation.$820,926 $820,926
Physical Interconnection
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)Install revenue metering on AG2-582 terminal at the existing Flint Run substation.$60,800 $60,800

Based on the scope of work for the Interconnection Facilities, it is expected to take 56 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

The schedule for any required Network Impact Reinforcements will be more clearly identified in the Phase II and Phase III System Impact Studies.

Transmission Owner Analysis

FE performed an analysis of its underlying transmission system <100 kV system. New Service Request Project AG2-582 did not contribute to any overloads on the FE transmission <100 kV system.

 

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. FirstEnergy interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AG2-582 was evaluated as a 2100.0 MW (2075.0 MW Capacity) injection in the APS area.

AG2-582 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 2100.0 MW (2100.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AP
01BARNET-01SHINNS 138.0 kV Ckt 1 line
AP_P2-3_MP-500-012_SRT-A
BreakerAC111.91 %268.0B299.9382.7
GD2AP
01BARNET-01SHINNS 138.0 kV Ckt 1 line
AP_P1-2_MP-500-008A_SRT-SL
SingleAC110.42 %268.0B295.9382.91
GD2AP
01BARNET-01SHINNS 138.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT4_SRT-SL
BreakerAC110.42 %268.0B295.9182.91
GD2AP
01BARNET-01SHINNS 138.0 kV Ckt 1 line
AP_P2-3_MP-500-018_SRT-SL
BreakerAC110.42 %268.0B295.9182.91
GD2AP
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
AP_P2-3_PE-500-014_SRT-SL
BreakerAC166.47 %206.0B342.9211.5
GD2AP
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT19_SRT-SL
BreakerAC162.98 %206.0B335.7311.62
GD2AP
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
AP_P1-2_PE-500-004_SRT-SL-2
SingleAC149.36 %206.0B307.6711.5
GD2AP
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
AP_P1-2_PE-500-004_SRT-SL-1
SingleAC145.88 %206.0B300.5111.62
GD2AP
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
AP_P2-2_WP-500-DRT9_SRT-SL
BusAC121.63 %206.0B250.5611.79
GD2AP
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT22_SRT-SL
BreakerAC121.62 %206.0B250.5411.79
GD2AP
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
AP_P2-3_MP-138-206_SRT-A
BreakerAC120.19 %206.0B247.5811.83
GD2AP
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
AP_P2-2_WP-500-DRT11_SRT-SL
BusAC116.27 %206.0B239.5211.94
GD2AP
01BRIDGP-01BARNET 138.0 kV Ckt 1 line
AP_P2-3_MP-500-012_SRT-A
BreakerAC113.93 %268.0B305.3282.7
GD2AP
01BRIDGP-01BARNET 138.0 kV Ckt 1 line
AP_P1-2_MP-500-008A_SRT-SL
SingleAC112.43 %268.0B301.3182.91
GD2AP
01BRIDGP-01BARNET 138.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT4_SRT-SL
BreakerAC112.42 %268.0B301.2982.91
GD2AP
01BRIDGP-01BARNET 138.0 kV Ckt 1 line
AP_P2-3_MP-500-018_SRT-SL
BreakerAC112.42 %268.0B301.2982.91
GD2AP
01BRIDGP-01BARNET 138.0 kV Ckt 1 line
AP_P2-3_MP-500-016_SRT-A
BreakerAC101.26 %268.0B271.3871.47
GD2AP
01BRIDGP-01BARNET 138.0 kV Ckt 1 line
AP_P2-3_MP-500-017_SRT-A
BreakerAC101.26 %268.0B271.3871.47
GD2AP
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer
AP_P2-3_MP-500-017_SRT-A
BreakerAC163.89 %527.0B863.7339.54
IPDAP
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer
AP_P2-3_MP-500-017_SRT-A
BreakerAC149.65 %527.0B788.65339.54
GD2AP
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer
AP_P2-3_MP-500-016_SRT-A
BreakerAC163.89 %527.0B863.7339.54
IPDAP
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer
AP_P2-3_MP-500-016_SRT-A
BreakerAC149.65 %527.0B788.65339.54
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AEP_P4_#8975_05KAMMER 765_MM2_SRT-A
BreakerAC139.97 %3792.0B5307.791217.06
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT7A_SRT-SL
BreakerAC139.96 %3792.0B5307.11217.06
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT10A_SRT-SL
BreakerAC139.86 %3792.0B5303.431215.72
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-502T_SRT-A
SingleAC139.36 %3792.0B5284.611217.06
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P1-2_MP-500-028_SRT-A
SingleAC139.32 %3792.0B5282.911217.06
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P2-2_MP-500-007_SRT-SL
BusAC105.4 %2811.0B2962.751251.46
GD2AP
01GLENFL-01BRIDGP 138.0 kV Ckt 1 line
AP_P2-3_MP-500-012_SRT-A
BreakerAC119.05 %268.0B319.0682.7
GD2AP
01GLENFL-01BRIDGP 138.0 kV Ckt 1 line
AP_P1-2_MP-500-008A_SRT-SL
SingleAC117.56 %268.0B315.0582.91
GD2AP
01GLENFL-01BRIDGP 138.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT4_SRT-SL
BreakerAC117.55 %268.0B315.0382.91
GD2AP
01GLENFL-01BRIDGP 138.0 kV Ckt 1 line
AP_P2-3_MP-500-018_SRT-SL
BreakerAC117.55 %268.0B315.0382.91
GD2AP
01GLENFL-01BRIDGP 138.0 kV Ckt 1 line
AP_P2-3_MP-500-017_SRT-A
BreakerAC106.37 %268.0B285.0871.47
GD2AP
01GLENFL-01BRIDGP 138.0 kV Ckt 1 line
AP_P2-3_MP-500-016_SRT-A
BreakerAC106.37 %268.0B285.0871.47
GD2AP
01GLENFL-01BRIDGP 138.0 kV Ckt 1 line
AP_P2-2_MP-138-013_SRT-A
BusAC102.26 %268.0B274.0527.69
GD2AP
01GLENFL-01MCALPN 138.0 kV Ckt 1 line
AP_P2-3_MP-500-012_SRT-A
BreakerAC114.99 %268.0B308.1876.6
GD2AP
01GLENFL-01MCALPN 138.0 kV Ckt 1 line
AP_P1-2_MP-500-008A_SRT-SL
SingleAC113.89 %268.0B305.2276.75
GD2AP
01GLENFL-01MCALPN 138.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT4_SRT-SL
BreakerAC113.88 %268.0B305.276.75
GD2AP
01GLENFL-01MCALPN 138.0 kV Ckt 1 line
AP_P2-3_MP-500-018_SRT-SL
BreakerAC113.88 %268.0B305.276.75
GD2AP
01GLENFL-01MCALPN 138.0 kV Ckt 1 line
AP_P2-3_MP-500-017_SRT-A
BreakerAC103.22 %268.0B276.6365.82
GD2AP
01GLENFL-01MCALPN 138.0 kV Ckt 1 line
AP_P2-3_MP-500-016_SRT-A
BreakerAC103.22 %268.0B276.6365.82
GD2AP
01HARRSN-01PRNTY 500.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT6_SRT-SL
BreakerAC104.19 %3792.0B3950.77814.67
GD2AP
01HARRSN-01PRNTY 500.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT9_SRT-SL
BreakerAC104.01 %3792.0B3943.9815.91
GD2AP
01HARRSN-01PRNTY 500.0 kV Ckt 1 line
AP_P1-2_MP-500-022_SRT-A
SingleAC103.61 %3792.0B3929.01814.67
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-012_SRT-A
BreakerAC130.23 %3729.0B4856.26239.41
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P1-2_MP-500-008A_SRT-SL
SingleAC124.1 %3729.0B4627.6242.4
GD2AP
01MTZION-AG2-505 TP 138.0 kV Ckt 1 line
AP_P2-3_PE-500-014_SRT-SL
BreakerAC148.09 %206.0B305.0611.5
GD2AP
01MTZION-AG2-505 TP 138.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT19_SRT-SL
BreakerAC144.6 %206.0B297.8711.62
GD2AP
01MTZION-AG2-505 TP 138.0 kV Ckt 1 line
AP_P1-2_PE-500-004_SRT-SL-2
SingleAC135.36 %206.0B278.8311.5
GD2AP
01MTZION-AG2-505 TP 138.0 kV Ckt 1 line
AP_P1-2_PE-500-004_SRT-SL-1
SingleAC131.89 %206.0B271.6911.62
GD2AP
01MTZION-AG2-505 TP 138.0 kV Ckt 1 line
AP_P2-2_WP-500-DRT9_SRT-SL
BusAC102.74 %206.0B211.6511.79
GD2AP
01MTZION-AG2-505 TP 138.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT22_SRT-SL
BreakerAC102.73 %206.0B211.6311.79
GD2AP
01MTZION-AG2-505 TP 138.0 kV Ckt 1 line
AP_P2-3_MP-138-206_SRT-A
BreakerAC101.3 %206.0B208.6911.83
GD2AP
01SHINNS-01PRNTY 138.0 kV Ckt 1 line
AP_P2-3_MP-500-012_SRT-A
BreakerAC110.45 %268.0B296.082.7
GD2AP
01SHINNS-01PRNTY 138.0 kV Ckt 1 line
AP_P1-2_MP-500-008A_SRT-SL
SingleAC108.96 %268.0B292.0182.91
GD2AP
01SHINNS-01PRNTY 138.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT4_SRT-SL
BreakerAC108.95 %268.0B291.9982.91
GD2AP
01SHINNS-01PRNTY 138.0 kV Ckt 1 line
AP_P2-3_MP-500-018_SRT-SL
BreakerAC108.95 %268.0B291.9982.91
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-012_SRT-A
BreakerAC131.49 %3792.0B4985.98239.41
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P1-2_MP-500-008A_SRT-SL
SingleAC125.38 %3792.0B4754.33242.4
GD2AP
AG2-505 TP-01BERYL 138.0 kV Ckt 1 line
AP_P2-3_PE-500-014_SRT-SL
BreakerAC152.24 %206.0B313.6211.5
GD2AP
AG2-505 TP-01BERYL 138.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT19_SRT-SL
BreakerAC148.75 %206.0B306.4211.62
GD2AP
AG2-505 TP-01BERYL 138.0 kV Ckt 1 line
AP_P1-2_PE-500-004_SRT-SL-2
SingleAC139.52 %206.0B287.4211.5
GD2AP
AG2-505 TP-01BERYL 138.0 kV Ckt 1 line
AP_P1-2_PE-500-004_SRT-SL-1
SingleAC136.04 %206.0B280.2511.62
GD2AP
AG2-505 TP-01BERYL 138.0 kV Ckt 1 line
AP_P2-2_WP-500-DRT9_SRT-SL
BusAC107.16 %206.0B220.7511.79
GD2AP
AG2-505 TP-01BERYL 138.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT22_SRT-SL
BreakerAC107.15 %206.0B220.7311.79
GD2AP
AG2-505 TP-01BERYL 138.0 kV Ckt 1 line
AP_P2-3_MP-138-206_SRT-A
BreakerAC105.72 %206.0B217.7811.83
GD2AP
AG2-505 TP-01BERYL 138.0 kV Ckt 1 line
AP_P2-2_WP-500-DRT11_SRT-SL
BusAC101.8 %206.0B209.7111.94
GD2NYISO/PENELEC
N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line
PN_P1-1_PN-230-018_SRT-A
SingleAC139.93 %128.0B179.126.78
GD2NYISO/PENELEC
N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line
PN_P1-1_PN-230-017_SRT-A
SingleAC139.93 %128.0B179.126.78
GD2NYISO/PENELEC
N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line
PN_P2-2_PN-345-1154-W_SRT-A
BusAC124.81 %128.0B159.767.7
GD2NYISO/PENELEC
N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line
Base Case
SingleAC116.38 %114.0A132.686.78
GD2NYISO/PENELEC
N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line
AP_P2-2_WP-230-001T_SRT-A
BusAC113.06 %128.0B144.717.18

Details for 01BARNET-01SHINNS 138.0 kV Ckt 1 line l/o AP_P2-3_MP-500-012_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01BARNET-01SHINNS 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-012_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.91 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:299.93
MW Contribution:82.7
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
Adder
82.703
237068AA2-119 GEN
50/50
18.76
LAGNLTFEXP_LAGN->PJM
CLTF
0.877
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.419
TVALTFEXP_TVA->PJM
CLTF
0.437
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.635
NYPJM->LTFIMP_NY
CLTF
0.335
LGEELTFEXP_LGEE->PJM
CLTF
0.404
WECLTFEXP_WEC->PJM
CLTF
0.218
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.11
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.744
MECLTFEXP_MEC->PJM
CLTF
0.917
SIGELTFEXP_SIGE->PJM
CLTF
0.03

Details for 01BARNET-01SHINNS 138.0 kV Ckt 1 line l/o AP_P1-2_MP-500-008A_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01BARNET-01SHINNS 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.42 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:295.93
MW Contribution:82.91
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
Adder
82.907
237068AA2-119 GEN
50/50
18.89
LAGNLTFEXP_LAGN->PJM
CLTF
0.86
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.494
TVALTFEXP_TVA->PJM
CLTF
0.43
CPLELTFEXP_CPLE->PJM
CLTF
0.04
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.409
NYPJM->LTFIMP_NY
CLTF
0.34
LGEELTFEXP_LGEE->PJM
CLTF
0.387
WECLTFEXP_WEC->PJM
CLTF
0.206
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.523
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.706
MECLTFEXP_MEC->PJM
CLTF
0.872
SIGELTFEXP_SIGE->PJM
CLTF
0.029

Details for 01BARNET-01SHINNS 138.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT4_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01BARNET-01SHINNS 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT4_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.42 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:295.91
MW Contribution:82.91
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
Adder
82.907
237068AA2-119 GEN
50/50
18.89
LAGNLTFEXP_LAGN->PJM
CLTF
0.86
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.494
TVALTFEXP_TVA->PJM
CLTF
0.43
CPLELTFEXP_CPLE->PJM
CLTF
0.04
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.409
NYPJM->LTFIMP_NY
CLTF
0.34
LGEELTFEXP_LGEE->PJM
CLTF
0.387
WECLTFEXP_WEC->PJM
CLTF
0.206
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.523
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.706
MECLTFEXP_MEC->PJM
CLTF
0.872
SIGELTFEXP_SIGE->PJM
CLTF
0.029

Details for 01BARNET-01SHINNS 138.0 kV Ckt 1 line l/o AP_P2-3_MP-500-018_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01BARNET-01SHINNS 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-018_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.42 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:295.91
MW Contribution:82.91
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
Adder
82.907
237068AA2-119 GEN
50/50
18.89
LAGNLTFEXP_LAGN->PJM
CLTF
0.86
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.494
TVALTFEXP_TVA->PJM
CLTF
0.43
CPLELTFEXP_CPLE->PJM
CLTF
0.04
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.409
NYPJM->LTFIMP_NY
CLTF
0.34
LGEELTFEXP_LGEE->PJM
CLTF
0.387
WECLTFEXP_WEC->PJM
CLTF
0.206
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.523
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.706
MECLTFEXP_MEC->PJM
CLTF
0.872
SIGELTFEXP_SIGE->PJM
CLTF
0.029

Details for 01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line l/o AP_P2-3_PE-500-014_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-014_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:166.47 %
Rating:206.0 MVA
Rating Type:B
MVA to Mitigate:342.92
MW Contribution:11.5
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
Adder
11.497
971679AH1-340 GEN
Solar/Wind Harmer
3.052
23750501ELLIOTTS
Solar/Wind Harmer
0.971
970801AG2-505 GEN
50/50
8.712
23750701CROSSCHOOL
Solar/Wind Helper
3.115
970697AG2-448 GEN
Solar/Wind Harmer
29.897
238185AF2-356 C
Solar/Wind Harmer
24.354
LAGNLTFEXP_LAGN->PJM
CLTF
0.311
TVALTFEXP_TVA->PJM
CLTF
0.151
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.61
NYPJM->LTFIMP_NY
CLTF
0.151
LGEELTFEXP_LGEE->PJM
CLTF
0.17
WECLTFEXP_WEC->PJM
CLTF
0.098
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.055
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.007
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.91
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.634
MECLTFEXP_MEC->PJM
CLTF
0.397
SIGELTFEXP_SIGE->PJM
CLTF
0.013

Details for 01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT19_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT19_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:162.98 %
Rating:206.0 MVA
Rating Type:B
MVA to Mitigate:335.73
MW Contribution:11.62
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
Adder
11.619
971679AH1-340 GEN
Solar/Wind Harmer
3.055
23750501ELLIOTTS
Solar/Wind Harmer
0.972
970801AG2-505 GEN
50/50
8.713
23750701CROSSCHOOL
Solar/Wind Helper
3.114
964991AG1-363 GEN
Solar/Wind Helper
1.776
970697AG2-448 GEN
Solar/Wind Harmer
29.899
238185AF2-356 C
Solar/Wind Harmer
24.357
LAGNLTFEXP_LAGN->PJM
CLTF
0.322
TVALTFEXP_TVA->PJM
CLTF
0.157
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.683
NYPJM->LTFIMP_NY
CLTF
0.148
LGEELTFEXP_LGEE->PJM
CLTF
0.174
WECLTFEXP_WEC->PJM
CLTF
0.1
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.051
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.005
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.989
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.654
MECLTFEXP_MEC->PJM
CLTF
0.406
SIGELTFEXP_SIGE->PJM
CLTF
0.013

Details for 01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line l/o AP_P1-2_PE-500-004_SRT-SL-2


Base Case Flowgate

Area:AP
Facility Description:
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-500-004_SRT-SL-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:149.36 %
Rating:206.0 MVA
Rating Type:B
MVA to Mitigate:307.67
MW Contribution:11.5
Bus #Bus NameTypeMW Contribution
970801AG2-505 GEN
50/50
8.712
23750701CROSSCHOOL
Solar/Wind Helper
3.115
970935AG2-582 GEN
Adder
11.497
971679AH1-340 GEN
Solar/Wind Harmer
2.129
23750501ELLIOTTS
Solar/Wind Harmer
0
970697AG2-448 GEN
Solar/Wind Harmer
20.858
238185AF2-356 C
Solar/Wind Harmer
0.048
LAGNLTFEXP_LAGN->PJM
CLTF
0.311
TVALTFEXP_TVA->PJM
CLTF
0.151
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.61
NYPJM->LTFIMP_NY
CLTF
0.151
LGEELTFEXP_LGEE->PJM
CLTF
0.17
WECLTFEXP_WEC->PJM
CLTF
0.098
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.055
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.007
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.91
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.634
MECLTFEXP_MEC->PJM
CLTF
0.397
SIGELTFEXP_SIGE->PJM
CLTF
0.013

Details for 01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line l/o AP_P1-2_PE-500-004_SRT-SL-1


Base Case Flowgate

Area:AP
Facility Description:
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-500-004_SRT-SL-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:145.88 %
Rating:206.0 MVA
Rating Type:B
MVA to Mitigate:300.51
MW Contribution:11.62
Bus #Bus NameTypeMW Contribution
970801AG2-505 GEN
50/50
8.713
23750701CROSSCHOOL
Solar/Wind Helper
3.114
964991AG1-363 GEN
Solar/Wind Helper
1.776
970935AG2-582 GEN
Adder
11.619
971679AH1-340 GEN
Solar/Wind Harmer
2.131
23750501ELLIOTTS
Solar/Wind Harmer
0
970697AG2-448 GEN
Solar/Wind Harmer
20.86
238185AF2-356 C
Solar/Wind Harmer
0.048
LAGNLTFEXP_LAGN->PJM
CLTF
0.322
TVALTFEXP_TVA->PJM
CLTF
0.157
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.683
NYPJM->LTFIMP_NY
CLTF
0.148
LGEELTFEXP_LGEE->PJM
CLTF
0.174
WECLTFEXP_WEC->PJM
CLTF
0.1
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.051
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.005
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.989
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.654
MECLTFEXP_MEC->PJM
CLTF
0.406
SIGELTFEXP_SIGE->PJM
CLTF
0.013

Details for 01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line l/o AP_P2-2_WP-500-DRT9_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-500-DRT9_SRT-SL
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:121.63 %
Rating:206.0 MVA
Rating Type:B
MVA to Mitigate:250.56
MW Contribution:11.79
Bus #Bus NameTypeMW Contribution
971679AH1-340 GEN
Solar/Wind Harmer
3.12
23750501ELLIOTTS
Solar/Wind Harmer
0.95
970801AG2-505 GEN
50/50
8.854
23750701CROSSCHOOL
Solar/Wind Helper
2.993
970935AG2-582 GEN
Adder
11.79
970697AG2-448 GEN
Solar/Wind Harmer
30.376
238185AF2-356 C
Solar/Wind Harmer
24.755
23751201ROTHROCK
Solar/Wind Harmer
0.889
LAGNLTFEXP_LAGN->PJM
CLTF
0.368
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.186
TVALTFEXP_TVA->PJM
CLTF
0.183
CPLELTFEXP_CPLE->PJM
CLTF
0.005
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.779
NYPJM->LTFIMP_NY
CLTF
0.191
LGEELTFEXP_LGEE->PJM
CLTF
0.166
WECLTFEXP_WEC->PJM
CLTF
0.093
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.55
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.726
MECLTFEXP_MEC->PJM
CLTF
0.388
SIGELTFEXP_SIGE->PJM
CLTF
0.012

Details for 01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT22_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT22_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.62 %
Rating:206.0 MVA
Rating Type:B
MVA to Mitigate:250.54
MW Contribution:11.79
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
Adder
11.79
970801AG2-505 GEN
50/50
8.854
23750701CROSSCHOOL
Solar/Wind Helper
2.993
971679AH1-340 GEN
Solar/Wind Harmer
3.12
23750501ELLIOTTS
Solar/Wind Harmer
0.95
970697AG2-448 GEN
Solar/Wind Harmer
30.376
238185AF2-356 C
Solar/Wind Harmer
24.755
23751201ROTHROCK
Solar/Wind Harmer
0.889
LAGNLTFEXP_LAGN->PJM
CLTF
0.368
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.186
TVALTFEXP_TVA->PJM
CLTF
0.183
CPLELTFEXP_CPLE->PJM
CLTF
0.005
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.779
NYPJM->LTFIMP_NY
CLTF
0.191
LGEELTFEXP_LGEE->PJM
CLTF
0.166
WECLTFEXP_WEC->PJM
CLTF
0.093
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.55
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.726
MECLTFEXP_MEC->PJM
CLTF
0.388
SIGELTFEXP_SIGE->PJM
CLTF
0.012

Details for 01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line l/o AP_P2-3_MP-138-206_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-138-206_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.19 %
Rating:206.0 MVA
Rating Type:B
MVA to Mitigate:247.58
MW Contribution:11.83
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
Adder
11.829
970801AG2-505 GEN
50/50
8.854
23750701CROSSCHOOL
Solar/Wind Helper
2.993
971679AH1-340 GEN
Solar/Wind Harmer
3.121
23750501ELLIOTTS
Solar/Wind Harmer
0.95
970697AG2-448 GEN
Solar/Wind Harmer
30.376
238185AF2-356 C
Solar/Wind Harmer
24.756
23751201ROTHROCK
Solar/Wind Harmer
0.889
LAGNLTFEXP_LAGN->PJM
CLTF
0.372
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.192
TVALTFEXP_TVA->PJM
CLTF
0.184
CPLELTFEXP_CPLE->PJM
CLTF
0.006
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.802
NYPJM->LTFIMP_NY
CLTF
0.19
LGEELTFEXP_LGEE->PJM
CLTF
0.167
WECLTFEXP_WEC->PJM
CLTF
0.093
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.575
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.733
MECLTFEXP_MEC->PJM
CLTF
0.39
SIGELTFEXP_SIGE->PJM
CLTF
0.012

Details for 01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line l/o AP_P2-2_WP-500-DRT11_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-500-DRT11_SRT-SL
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:116.27 %
Rating:206.0 MVA
Rating Type:B
MVA to Mitigate:239.52
MW Contribution:11.94
Bus #Bus NameTypeMW Contribution
971679AH1-340 GEN
Solar/Wind Harmer
3.123
23750501ELLIOTTS
Solar/Wind Harmer
0.951
970801AG2-505 GEN
50/50
8.855
23750701CROSSCHOOL
Solar/Wind Helper
2.993
970935AG2-582 GEN
Adder
11.939
970697AG2-448 GEN
Solar/Wind Harmer
30.379
238185AF2-356 C
Solar/Wind Harmer
24.758
23751201ROTHROCK
Solar/Wind Harmer
0.89
LAGNLTFEXP_LAGN->PJM
CLTF
0.382
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.206
TVALTFEXP_TVA->PJM
CLTF
0.189
CPLELTFEXP_CPLE->PJM
CLTF
0.012
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.867
NYPJM->LTFIMP_NY
CLTF
0.187
LGEELTFEXP_LGEE->PJM
CLTF
0.171
WECLTFEXP_WEC->PJM
CLTF
0.095
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.646
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.751
MECLTFEXP_MEC->PJM
CLTF
0.399
SIGELTFEXP_SIGE->PJM
CLTF
0.013

Details for 01BRIDGP-01BARNET 138.0 kV Ckt 1 line l/o AP_P2-3_MP-500-012_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01BRIDGP-01BARNET 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-012_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.93 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:305.32
MW Contribution:82.7
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
Adder
82.703
237068AA2-119 GEN
50/50
18.76
LAGNLTFEXP_LAGN->PJM
CLTF
0.877
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.419
TVALTFEXP_TVA->PJM
CLTF
0.437
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.635
NYPJM->LTFIMP_NY
CLTF
0.335
LGEELTFEXP_LGEE->PJM
CLTF
0.404
WECLTFEXP_WEC->PJM
CLTF
0.218
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.11
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.744
MECLTFEXP_MEC->PJM
CLTF
0.917
SIGELTFEXP_SIGE->PJM
CLTF
0.03

Details for 01BRIDGP-01BARNET 138.0 kV Ckt 1 line l/o AP_P1-2_MP-500-008A_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01BRIDGP-01BARNET 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.43 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:301.31
MW Contribution:82.91
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
Adder
82.907
237068AA2-119 GEN
50/50
18.89
LAGNLTFEXP_LAGN->PJM
CLTF
0.86
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.494
TVALTFEXP_TVA->PJM
CLTF
0.43
CPLELTFEXP_CPLE->PJM
CLTF
0.04
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.409
NYPJM->LTFIMP_NY
CLTF
0.34
LGEELTFEXP_LGEE->PJM
CLTF
0.387
WECLTFEXP_WEC->PJM
CLTF
0.206
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.523
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.706
MECLTFEXP_MEC->PJM
CLTF
0.872
SIGELTFEXP_SIGE->PJM
CLTF
0.029

Details for 01BRIDGP-01BARNET 138.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT4_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01BRIDGP-01BARNET 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT4_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.42 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:301.29
MW Contribution:82.91
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
Adder
82.907
237068AA2-119 GEN
50/50
18.89
LAGNLTFEXP_LAGN->PJM
CLTF
0.86
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.494
TVALTFEXP_TVA->PJM
CLTF
0.43
CPLELTFEXP_CPLE->PJM
CLTF
0.04
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.409
NYPJM->LTFIMP_NY
CLTF
0.34
LGEELTFEXP_LGEE->PJM
CLTF
0.387
WECLTFEXP_WEC->PJM
CLTF
0.206
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.523
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.706
MECLTFEXP_MEC->PJM
CLTF
0.872
SIGELTFEXP_SIGE->PJM
CLTF
0.029

Details for 01BRIDGP-01BARNET 138.0 kV Ckt 1 line l/o AP_P2-3_MP-500-018_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01BRIDGP-01BARNET 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-018_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.42 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:301.29
MW Contribution:82.91
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
Adder
82.907
237068AA2-119 GEN
50/50
18.89
LAGNLTFEXP_LAGN->PJM
CLTF
0.86
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.494
TVALTFEXP_TVA->PJM
CLTF
0.43
CPLELTFEXP_CPLE->PJM
CLTF
0.04
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.409
NYPJM->LTFIMP_NY
CLTF
0.34
LGEELTFEXP_LGEE->PJM
CLTF
0.387
WECLTFEXP_WEC->PJM
CLTF
0.206
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.523
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.706
MECLTFEXP_MEC->PJM
CLTF
0.872
SIGELTFEXP_SIGE->PJM
CLTF
0.029

Details for 01BRIDGP-01BARNET 138.0 kV Ckt 1 line l/o AP_P2-3_MP-500-016_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01BRIDGP-01BARNET 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-016_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.26 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:271.38
MW Contribution:71.47
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
Adder
71.472
237068AA2-119 GEN
50/50
19.547
LAGNLTFEXP_LAGN->PJM
CLTF
0.783
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.443
TVALTFEXP_TVA->PJM
CLTF
0.392
CPLELTFEXP_CPLE->PJM
CLTF
0.032
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.84
NYPJM->LTFIMP_NY
CLTF
0.317
LGEELTFEXP_LGEE->PJM
CLTF
0.353
WECLTFEXP_WEC->PJM
CLTF
0.188
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.85
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.555
MECLTFEXP_MEC->PJM
CLTF
0.794
SIGELTFEXP_SIGE->PJM
CLTF
0.026

Details for 01BRIDGP-01BARNET 138.0 kV Ckt 1 line l/o AP_P2-3_MP-500-017_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01BRIDGP-01BARNET 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-017_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.26 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:271.38
MW Contribution:71.47
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
Adder
71.472
237068AA2-119 GEN
50/50
19.547
LAGNLTFEXP_LAGN->PJM
CLTF
0.783
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.443
TVALTFEXP_TVA->PJM
CLTF
0.392
CPLELTFEXP_CPLE->PJM
CLTF
0.032
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.84
NYPJM->LTFIMP_NY
CLTF
0.317
LGEELTFEXP_LGEE->PJM
CLTF
0.353
WECLTFEXP_WEC->PJM
CLTF
0.188
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.85
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.555
MECLTFEXP_MEC->PJM
CLTF
0.794
SIGELTFEXP_SIGE->PJM
CLTF
0.026

Details for 01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-017_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-017_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:163.89 %
Rating:527.0 MVA
Rating Type:B
MVA to Mitigate:863.7
MW Contribution:339.54
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
50/50
339.542
23751101LEADS_P59
Solar/Wind Helper
0.916
23562501BACKB
Solar/Wind Helper
0.431
23751201ROTHROCK
Solar/Wind Helper
0.341
LAGNLTFEXP_LAGN->PJM
CLTF
2.146
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.437
TVALTFEXP_TVA->PJM
CLTF
1.067
CPLELTFEXP_CPLE->PJM
CLTF
0.229
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.908
NYPJM->LTFIMP_NY
CLTF
0.652
LGEELTFEXP_LGEE->PJM
CLTF
0.944
WECLTFEXP_WEC->PJM
CLTF
0.514
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.85
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.213
MECLTFEXP_MEC->PJM
CLTF
2.171
SIGELTFEXP_SIGE->PJM
CLTF
0.07

Details for [AG2-582] 01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-017_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-017_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:149.65 %
Rating:527.0 MVA
Rating Type:B
MVA to Mitigate:788.65
MW Contribution:339.54
IPD Plant:AG2-582
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
PJM_IPD
339.542

Details for 01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer l/o AP_P2-3_MP-500-016_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer
Contingency Name:
AP_P2-3_MP-500-016_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:163.89 %
Rating:527.0 MVA
Rating Type:B
MVA to Mitigate:863.7
MW Contribution:339.54
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
50/50
339.542
23751101LEADS_P59
Solar/Wind Helper
0.916
23562501BACKB
Solar/Wind Helper
0.431
23751201ROTHROCK
Solar/Wind Helper
0.341
LAGNLTFEXP_LAGN->PJM
CLTF
2.146
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.437
TVALTFEXP_TVA->PJM
CLTF
1.067
CPLELTFEXP_CPLE->PJM
CLTF
0.229
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.908
NYPJM->LTFIMP_NY
CLTF
0.652
LGEELTFEXP_LGEE->PJM
CLTF
0.944
WECLTFEXP_WEC->PJM
CLTF
0.514
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.85
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.213
MECLTFEXP_MEC->PJM
CLTF
2.171
SIGELTFEXP_SIGE->PJM
CLTF
0.07

Details for [AG2-582] 01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer l/o AP_P2-3_MP-500-016_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer
Contingency Name:
AP_P2-3_MP-500-016_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:149.65 %
Rating:527.0 MVA
Rating Type:B
MVA to Mitigate:788.65
MW Contribution:339.54
IPD Plant:AG2-582
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
PJM_IPD
339.542

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AEP_P4_#8975_05KAMMER 765_MM2_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8975_05KAMMER 765_MM2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:139.97 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5307.79
MW Contribution:1217.06
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
50/50
1217.062
24318905MLG2
50/50
4.656
270471AD2-092_GEN
Solar/Wind Harmer
3.665
970879AG2-548 GEN
Solar/Wind Harmer
6.188
971073AG2-665 GEN
Solar/Wind Harmer
6.188
971073AG2-665 GEN
Solar/Wind Harmer
4.317
946101AF1-275 GEN
Solar/Wind Harmer
1.512
24685805CER G1
Adder
8.199
24685905CER G2
Adder
8.199
972269AH1-719 GEN
Adder
2.268
24723005RIVRG1
Adder
18.473
24723105RIVRG2
Adder
18.473
942861AE2-305 GEN
Solar/Wind Harmer
7.629
270518AE2-148 GEN
Solar/Wind Harmer
11.837
970077AG2-063 GEN
Solar/Wind Harmer
5.262
962581AG1-107 GEN
Solar/Wind Harmer
4.827
961491AF2-440 GEN
Solar/Wind Harmer
2.006
972159AH1-661 GEN
Adder
0.952
253394AE2-221_GEN
Solar/Wind Harmer
4.338
253398AE2-221_GEN2
Solar/Wind Harmer
4.338
253317AC1-085 GEN4
Solar/Wind Harmer
7.992
270186AC1-089 GEN
Solar/Wind Harmer
5.819
25326109MON D
Adder
1.252
253370AE2-315 SEC1
Adder
1.906
25322209TAIT E
Adder
9.269
25322209TAIT E
Adder
9.061
25183208HLCRTG
Solar/Wind Harmer
5.751
964601AG1-323 GEN
Solar/Wind Harmer
3.011
964601AG1-323 GEN
Solar/Wind Harmer
1.401
252509AD1-136 GEN
Solar/Wind Harmer
0.243
252519AF1-045_GEN
Solar/Wind Harmer
5.748
252516AE2-318_GEN
Solar/Wind Harmer
4.385
270224U2-072_GEN2
Solar/Wind Harmer
1.871
270227U2-072_GEN3
Solar/Wind Harmer
1.871
270228U2-072_GEN4
Solar/Wind Harmer
1.871
270231U2-072_GEN5
Solar/Wind Harmer
1.871
938701AE1-092 GEN
Solar/Wind Harmer
19.52
25194408D.CRK1
Adder
7.132
25194508D.CRK3
Adder
1.333
253378AE2-206_GEN
Solar/Wind Harmer
3.382
276820AF1-078_GEN
Solar/Wind Harmer
1.502
25326509SID D
Adder
1.231
970239AG2-162 GEN
Solar/Wind Harmer
10.183
24728805RICHG1
Adder
3.489
24728905RICHG2
Adder
3.489
970883AG2-550 GEN
Solar/Wind Harmer
9.215
970885AG2-551 GEN
Solar/Wind Harmer
2.143
270383AD1-128 GEN
Solar/Wind Harmer
5.623
24379505HDWTR1G C
Solar/Wind Harmer
7.277
270209AC1-174_GEN
Solar/Wind Harmer
5.136
926881AC1-175 GEN
Solar/Wind Harmer
5.136
247621Y3-024
Adder
0.222
944541AF1-119 GEN
Solar/Wind Harmer
3.847
960971AF2-388 GEN
Solar/Wind Harmer
10.038
270201AC2-176 GEN
Solar/Wind Harmer
4.717
964611AG1-324 GEN
Solar/Wind Harmer
1.082
964611AG1-324 GEN
Solar/Wind Harmer
0.48
970825AG2-519 GEN
Solar/Wind Harmer
9.671
960441AF2-335 GEN
Solar/Wind Harmer
9.16
247620Y3-023
Adder
0.412
274770LINCOLN ;1U
Adder
7.514
274771LINCOLN ;2U
Adder
7.514
238175AF1-290_GEN
Solar/Wind Helper
0.126
238169AE2-226 GEN1
Solar/Wind Helper
0.582
238170AE2-226 GEN2
Solar/Wind Helper
0.582
235020AA1-095 C
Solar/Wind Helper
0.044
23777901MDS_W4-102
Solar/Wind Helper
0.146
238120AE2-309 GEN
Solar/Wind Helper
0.406
237034AC2-136 C
Solar/Wind Helper
0.189
237002AB1-128_GEN
Solar/Wind Helper
0.369
235063AE1-101 C2
Solar/Wind Helper
1.38
237001AB1-127_GEN
Solar/Wind Helper
0.368
23777801MSM_W1-116
Solar/Wind Helper
0.096
270599AE1-208 GEN
Solar/Wind Harmer
0.76
270031AE2-169
Solar/Wind Harmer
0.76
962771AG1-126 GEN
Solar/Wind Harmer
34.974
270330AC1-082 GEN2
Solar/Wind Harmer
0.789
270329AC1-082 GEN1
Solar/Wind Harmer
0.465
270054AF2-122 C O1
Solar/Wind Harmer
3.29
970879AG2-548 GEN
Solar/Wind Harmer
4.317
940611AE2-048 GEN
Solar/Wind Harmer
22.053
941391AE2-136 GEN
Solar/Wind Harmer
11.427
270520AE2-214 GEN
Solar/Wind Harmer
6.059
270459AD2-067 GEN
Solar/Wind Harmer
8.36
961821AG1-024 GEN
Solar/Wind Harmer
8.487
972203AH1-686 GEN
Adder
2.298
270432AC2-029 GEN
Solar/Wind Harmer
6.982
970689AG2-444 GEN
Solar/Wind Harmer
16.256
270269AC2-059
Solar/Wind Harmer
9.3
270156DARBY CT1
Adder
8.832
270157DARBY CT2
Adder
8.81
270158DARBY CT3
Adder
8.67
945631AF1-228 GEN
Solar/Wind Harmer
4.621
270284AF1-227 GEN1
Solar/Wind Harmer
5.57
270286AF1-227 GEN2
Solar/Wind Harmer
2.061
270287AF1-227 GEN3
Solar/Wind Harmer
2.061
971985AH1-537 GEN
Solar/Wind Harmer
17.522
253383AE2-342_GEN
Solar/Wind Harmer
0.869
241973AD2-163_GEN1
Solar/Wind Harmer
1.944
943861AF1-054 GEN
Solar/Wind Harmer
3.765
943851AF1-053 GEN
Solar/Wind Harmer
1.82
270340AC2-060 GEN
Solar/Wind Harmer
2.96
24477305BRIDGE
Adder
0.338
241972AD1-140 GEN
Solar/Wind Harmer
4.309
270367AC2-061_GEN
Solar/Wind Harmer
3.048
253372AE2-315 SEC3
Adder
1.803
253372AE2-315 SEC3
Adder
1.803
25306009OHH W.
Adder
2.735
270578AF1-285 GEN2
Solar/Wind Harmer
0.44
253349AC2-067 GEN
Solar/Wind Harmer
4.712
253400AC2-068 GEN
Solar/Wind Harmer
1.895
252524AE2-267 GEN
Solar/Wind Harmer
1.487
25196408WSDLE3
Adder
8.32
25196308WSDLE2
Adder
8.248
25196208WSDLE1
Adder
8.227
25196708WSDLE6
Adder
8.207
25196508WSDLE4
Adder
8
270302AB2-170 GEN
Solar/Wind Harmer
7.824
270317AD1-130_GEN
Solar/Wind Harmer
3
944031AF1-071 GEN
Solar/Wind Harmer
0.936
25196108MFTGT2
Adder
1.429
25196108MFTGT2
Adder
1.327
972163AH1-664 GEN
Solar/Wind Harmer
9.252
972165AH1-665 GEN
Solar/Wind Harmer
7.402
971673AH1-337 GEN
Solar/Wind Harmer
4.251
971029AG2-637 GEN
Solar/Wind Harmer
13.852
270543AE2-219 C
Solar/Wind Harmer
4.719
270240V3-007_GEN2
Solar/Wind Harmer
5.693
24729505KEY G4
Adder
5.961
958711AF2-162 GEN
Solar/Wind Harmer
0.929
965101AG1-375 GEN
Solar/Wind Harmer
9.182
945581AF1-223 GEN
Solar/Wind Harmer
4.163
961761AG1-017 GEN
Solar/Wind Harmer
0.393
970115AG2-085 GEN
Solar/Wind Harmer
3.664
274775LINCOLN ;6U
Adder
7.514
274776LINCOLN ;7U
Adder
7.514
274777LINCOLN ;8U
Adder
7.514
274814UNIV PK N;0U
Adder
4.489
274807UNIV PK N;3U
Adder
4.479
274805UNIV PK N;1U
Adder
4.459
274811UNIV PK N;7U
Adder
0.697
238152AF2-075_GEN
Solar/Wind Helper
0.593
23546401DTGZ2-030
Solar/Wind Helper
0.075
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
238208AF1-136 C
Solar/Wind Helper
0.18
237085AD2-009_GEN
Solar/Wind Helper
1.367
238126S14_GEN_1
Solar/Wind Helper
0.641
23559001PLEAS1
50/50
11.213
23684201S70BUS2
50/50
0.319
23562401OGROV2
50/50
2.411
24318805MLG1
50/50
6.319
24721905FLATG4
Adder
23.442
970153AG2-106 GEN
Solar/Wind Harmer
15.25
270512AE1-227 GEN2
Solar/Wind Harmer
2.245
971191AH1-055 GEN
Solar/Wind Harmer
22.406
957541AF2-048 GEN
Solar/Wind Harmer
1.601
270291AC1-194 GEN
Solar/Wind Harmer
10.629
961921AG1-034 GEN
Solar/Wind Harmer
12.731
960801AF2-371 GEN
Solar/Wind Harmer
2.533
964871AG1-351 GEN
Solar/Wind Harmer
1.749
270273AD2-016 GEN
Solar/Wind Harmer
2.659
972173AH1-669 GEN
Solar/Wind Harmer
4.984
241955AC1-078 GEN
Solar/Wind Harmer
7.382
24686205CER G4
Adder
8.21
24686405CER G5
Adder
8.177
942051AE2-217 GEN
Solar/Wind Harmer
17.654
253338AC1-165 GEN
Solar/Wind Harmer
1.064
253333AC1-068 GEN
Solar/Wind Harmer
1.027
241974AD2-163_GEN2
Solar/Wind Harmer
1.944
253415AE1-040 GEN
Solar/Wind Harmer
1.1
970605AG2-385 GEN
Solar/Wind Harmer
5.262
253406AD2-031_GEN
Solar/Wind Harmer
1.228
253316AC1-085 GEN3
Solar/Wind Harmer
7.992
253433AC1-085 GEN1
Solar/Wind Harmer
5.073
946181AF1-283 GEN
Solar/Wind Harmer
12.404
253303V4-073 C
Solar/Wind Harmer
0.11
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
942871AE2-306 GEN
Solar/Wind Harmer
0.858
270391AF1-285 GEN3
Solar/Wind Harmer
0.44
252510AF1-249 C
Solar/Wind Harmer
0.395
25196608WSDLE5
Adder
8.083
25194608D.CRK4
Adder
1.55
270485AE1-090_GEN
Solar/Wind Harmer
0.566
270222AC2-111 GEN
Solar/Wind Harmer
7.593
25196008MFTGT1
Adder
1.255
970243AG2-164 GEN
Solar/Wind Harmer
23.909
970519AG2-331 GEN
Solar/Wind Harmer
16.063
970699AG2-449 GEN
Solar/Wind Harmer
10.626
972167AH1-666 GEN
Solar/Wind Harmer
7.416
958171AF2-111 GEN
Solar/Wind Harmer
23.159
270437AC2-090 C
Solar/Wind Harmer
5.138
944531AF1-118 GEN
Solar/Wind Harmer
32.165
962031AG1-047 GEN
Solar/Wind Harmer
2.774
957741AF2-068 GEN
Solar/Wind Harmer
13.765
270356AE2-297 GEN
Solar/Wind Harmer
4.184
946031AF1-268 GEN
Solar/Wind Harmer
7.613
958821AF2-173 GEN
Solar/Wind Harmer
12.842
270004AE1-209 GEN
Solar/Wind Harmer
5.013
24728705AND G3
Adder
7.25
24728505AND G1
Adder
3.466
24642205MAYFLWER
Adder
0.568
274772LINCOLN ;3U
Adder
7.514
274752CRETE EC ;2U
Adder
7.332
274753CRETE EC ;3U
Adder
7.332
274724RIVER EC ;11
Adder
15.751
316097T157 G90
Solar/Wind Helper
1.299
964991AG1-363 GEN
Solar/Wind Helper
4.135
238148AE2-230_GEN2
Solar/Wind Helper
0.417
23750701CROSSCHOOL
Solar/Wind Helper
1.155
237080AD1-060 GEN
Solar/Wind Helper
0.284
237038AE2-054 C
Solar/Wind Helper
0.226
235062AE1-101 C1
Solar/Wind Helper
1.38
238127S14_GEN_2
Solar/Wind Helper
0.641
23779801AA1-109
Solar/Wind Helper
0.162
238118U2-030_1
Solar/Wind Helper
0.26
23559101PLEAS2
50/50
11.213
23684101S70BUS1
50/50
0.313
23562301OGROV1
50/50
2.427
24721705FLATG2
Adder
23.442
962761AG1-125 GEN
Solar/Wind Harmer
34.974
970149AG2-104 GEN
Solar/Wind Harmer
43.193
970155AG2-107 GEN
Solar/Wind Harmer
15.25
270510AE1-227 GEN1
Solar/Wind Harmer
2.645
960001AF2-291 GEN
Solar/Wind Harmer
3.152
970947AG2-589 GEN
Solar/Wind Harmer
2.059
270331AC1-082 GEN3
Solar/Wind Harmer
0.466
927014AC1-188 GEN
Solar/Wind Harmer
1.606
270349AD2-093_GEN
Solar/Wind Harmer
3.665
270263AC1-001 GEN
Solar/Wind Harmer
1.044
24686105CER G3
Adder
8.253
24686505CER G6
Adder
8.242
270159DARBY CT4
Adder
8.691
24723205RIVRG3
Adder
18.473
253343AC1-166 GEN
Solar/Wind Harmer
1.064
253325AC1-069 GEN
Solar/Wind Harmer
1.027
970593AG2-378 GEN
Solar/Wind Harmer
1.949
253432AC1-085 GEN2
Solar/Wind Harmer
0.255
946171AF1-282 GEN
Solar/Wind Harmer
9.541
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
25326309TAIT D
Adder
1.041
960071AF2-298 GEN
Solar/Wind Harmer
4.732
252507AC2-088 GEN
Solar/Wind Harmer
1.7
270223U2-072_GEN1
Solar/Wind Harmer
1.871
270578AF1-285 GEN2
Solar/Wind Harmer
1.144
270391AF1-285 GEN3
Solar/Wind Harmer
1.144
25194608D.CRK4
Adder
1.55
25196808ZIMRHP
Adder
71.347
270462AD2-086
Solar/Wind Harmer
6.509
25196008MFTGT1
Adder
1.296
970333AG2-219 GEN
Solar/Wind Harmer
29.222
945681AF1-233 GEN
Solar/Wind Harmer
17.467
942081AE2-220 GEN
Solar/Wind Harmer
5.883
270239V3-007_GEN1
Solar/Wind Harmer
1.584
247536S-71 GEN
Solar/Wind Harmer
3.724
965651AG1-433 GEN
Solar/Wind Harmer
5.019
958861AF2-177 GEN
Solar/Wind Harmer
10.036
945371AF1-202 GEN
Solar/Wind Harmer
6.405
971995AH1-542 GEN
Solar/Wind Harmer
10.093
270005AE1-210 C O1
Solar/Wind Harmer
5.013
965031AG1-367 GEN
Solar/Wind Harmer
9.173
970825AG2-519 GEN
Solar/Wind Harmer
2.158
970091AG2-072 GEN
Adder
70.193
24728605AND G2
Adder
3.466
24639705ELKHART HY
Adder
0.137
274773LINCOLN ;4U
Adder
7.514
274774LINCOLN ;5U
Adder
7.514
274751CRETE EC ;1U
Adder
7.332
274754CRETE EC ;4U
Adder
7.332
274723RIVER EC ;12
Adder
15.938
274812UNIV PK N;8U
Adder
4.45
23583801GRNGAP
Solar/Wind Helper
4.858
316095T157 G97
Solar/Wind Helper
1.299
238147AE2-230_GEN1
Solar/Wind Helper
0.415
238149AF1-291A_GEN
Solar/Wind Helper
0.119
238108AE1-109 GEN1
Solar/Wind Helper
0.088
237061AD1-155 GEN
Solar/Wind Helper
0.045
238185AF2-356 C
Solar/Wind Helper
1.996
238221AF1-254 C O1
Solar/Wind Helper
0.228
235067AD1-061 GEN
Solar/Wind Helper
0.412
235531U2-073 GEN
Solar/Wind Helper
2.523
238117U2-030
Solar/Wind Helper
0.26
944201AF1-088_MTX
Adder
103.64
957141AF2-008_MTX
Adder
51.82
LAGNLTFEXP_LAGN->PJM
CLTF
13.832
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.925
TVALTFEXP_TVA->PJM
CLTF
6.876
CPLELTFEXP_CPLE->PJM
CLTF
1.286
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.798
NYPJM->LTFIMP_NY
CLTF
4.417
LGEELTFEXP_LGEE->PJM
CLTF
6.111
WECLTFEXP_WEC->PJM
CLTF
3.336
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.614
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.188
MECLTFEXP_MEC->PJM
CLTF
14.066
SIGELTFEXP_SIGE->PJM
CLTF
0.455

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT7A_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT7A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:139.96 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5307.1
MW Contribution:1217.06
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
50/50
1217.062
24318905MLG2
50/50
4.656
270471AD2-092_GEN
Solar/Wind Harmer
3.665
970879AG2-548 GEN
Solar/Wind Harmer
6.188
971073AG2-665 GEN
Solar/Wind Harmer
6.188
971073AG2-665 GEN
Solar/Wind Harmer
4.317
946101AF1-275 GEN
Solar/Wind Harmer
1.512
24685805CER G1
Adder
8.199
24685905CER G2
Adder
8.199
972269AH1-719 GEN
Adder
2.268
24723005RIVRG1
Adder
18.473
24723105RIVRG2
Adder
18.473
942861AE2-305 GEN
Solar/Wind Harmer
7.629
270518AE2-148 GEN
Solar/Wind Harmer
11.837
970077AG2-063 GEN
Solar/Wind Harmer
5.262
962581AG1-107 GEN
Solar/Wind Harmer
4.827
961491AF2-440 GEN
Solar/Wind Harmer
2.006
972159AH1-661 GEN
Adder
0.952
253394AE2-221_GEN
Solar/Wind Harmer
4.338
253398AE2-221_GEN2
Solar/Wind Harmer
4.338
253317AC1-085 GEN4
Solar/Wind Harmer
7.992
270186AC1-089 GEN
Solar/Wind Harmer
5.819
25326109MON D
Adder
1.252
253370AE2-315 SEC1
Adder
1.906
25322209TAIT E
Adder
9.269
25322209TAIT E
Adder
9.061
25183208HLCRTG
Solar/Wind Harmer
5.751
964601AG1-323 GEN
Solar/Wind Harmer
3.011
964601AG1-323 GEN
Solar/Wind Harmer
1.401
252509AD1-136 GEN
Solar/Wind Harmer
0.243
252519AF1-045_GEN
Solar/Wind Harmer
5.748
252516AE2-318_GEN
Solar/Wind Harmer
4.385
270224U2-072_GEN2
Solar/Wind Harmer
1.871
270227U2-072_GEN3
Solar/Wind Harmer
1.871
270228U2-072_GEN4
Solar/Wind Harmer
1.871
270231U2-072_GEN5
Solar/Wind Harmer
1.871
938701AE1-092 GEN
Solar/Wind Harmer
19.52
25194408D.CRK1
Adder
7.132
25194508D.CRK3
Adder
1.333
253378AE2-206_GEN
Solar/Wind Harmer
3.382
276820AF1-078_GEN
Solar/Wind Harmer
1.502
25326509SID D
Adder
1.231
970239AG2-162 GEN
Solar/Wind Harmer
10.183
24728805RICHG1
Adder
3.489
24728905RICHG2
Adder
3.489
970883AG2-550 GEN
Solar/Wind Harmer
9.215
970885AG2-551 GEN
Solar/Wind Harmer
2.143
270383AD1-128 GEN
Solar/Wind Harmer
5.623
24379505HDWTR1G C
Solar/Wind Harmer
7.277
270209AC1-174_GEN
Solar/Wind Harmer
5.136
926881AC1-175 GEN
Solar/Wind Harmer
5.136
247621Y3-024
Adder
0.222
944541AF1-119 GEN
Solar/Wind Harmer
3.847
960971AF2-388 GEN
Solar/Wind Harmer
10.038
270201AC2-176 GEN
Solar/Wind Harmer
4.717
964611AG1-324 GEN
Solar/Wind Harmer
1.082
964611AG1-324 GEN
Solar/Wind Harmer
0.48
970825AG2-519 GEN
Solar/Wind Harmer
9.671
960441AF2-335 GEN
Solar/Wind Harmer
9.16
247620Y3-023
Adder
0.412
274770LINCOLN ;1U
Adder
7.514
274771LINCOLN ;2U
Adder
7.514
238175AF1-290_GEN
Solar/Wind Helper
0.126
238169AE2-226 GEN1
Solar/Wind Helper
0.582
238170AE2-226 GEN2
Solar/Wind Helper
0.582
235020AA1-095 C
Solar/Wind Helper
0.044
23777901MDS_W4-102
Solar/Wind Helper
0.146
238120AE2-309 GEN
Solar/Wind Helper
0.406
237034AC2-136 C
Solar/Wind Helper
0.189
237002AB1-128_GEN
Solar/Wind Helper
0.369
235063AE1-101 C2
Solar/Wind Helper
1.38
237001AB1-127_GEN
Solar/Wind Helper
0.368
23777801MSM_W1-116
Solar/Wind Helper
0.096
270599AE1-208 GEN
Solar/Wind Harmer
0.76
270031AE2-169
Solar/Wind Harmer
0.76
962771AG1-126 GEN
Solar/Wind Harmer
34.974
270330AC1-082 GEN2
Solar/Wind Harmer
0.789
270329AC1-082 GEN1
Solar/Wind Harmer
0.465
270054AF2-122 C O1
Solar/Wind Harmer
3.29
970879AG2-548 GEN
Solar/Wind Harmer
4.317
940611AE2-048 GEN
Solar/Wind Harmer
22.053
941391AE2-136 GEN
Solar/Wind Harmer
11.427
270520AE2-214 GEN
Solar/Wind Harmer
6.059
270459AD2-067 GEN
Solar/Wind Harmer
8.36
961821AG1-024 GEN
Solar/Wind Harmer
8.487
972203AH1-686 GEN
Adder
2.298
270432AC2-029 GEN
Solar/Wind Harmer
6.982
970689AG2-444 GEN
Solar/Wind Harmer
16.256
270269AC2-059
Solar/Wind Harmer
9.3
270156DARBY CT1
Adder
8.832
270157DARBY CT2
Adder
8.81
270158DARBY CT3
Adder
8.67
945631AF1-228 GEN
Solar/Wind Harmer
4.621
270284AF1-227 GEN1
Solar/Wind Harmer
5.57
270286AF1-227 GEN2
Solar/Wind Harmer
2.061
270287AF1-227 GEN3
Solar/Wind Harmer
2.061
971985AH1-537 GEN
Solar/Wind Harmer
17.522
253383AE2-342_GEN
Solar/Wind Harmer
0.869
241973AD2-163_GEN1
Solar/Wind Harmer
1.944
943861AF1-054 GEN
Solar/Wind Harmer
3.765
943851AF1-053 GEN
Solar/Wind Harmer
1.82
270340AC2-060 GEN
Solar/Wind Harmer
2.96
24477305BRIDGE
Adder
0.338
241972AD1-140 GEN
Solar/Wind Harmer
4.309
270367AC2-061_GEN
Solar/Wind Harmer
3.048
253372AE2-315 SEC3
Adder
1.803
253372AE2-315 SEC3
Adder
1.803
25306009OHH W.
Adder
2.735
270578AF1-285 GEN2
Solar/Wind Harmer
0.44
253349AC2-067 GEN
Solar/Wind Harmer
4.712
253400AC2-068 GEN
Solar/Wind Harmer
1.895
252524AE2-267 GEN
Solar/Wind Harmer
1.487
25196408WSDLE3
Adder
8.32
25196308WSDLE2
Adder
8.248
25196208WSDLE1
Adder
8.227
25196708WSDLE6
Adder
8.207
25196508WSDLE4
Adder
8
270302AB2-170 GEN
Solar/Wind Harmer
7.824
270317AD1-130_GEN
Solar/Wind Harmer
3
944031AF1-071 GEN
Solar/Wind Harmer
0.936
25196108MFTGT2
Adder
1.429
25196108MFTGT2
Adder
1.327
972163AH1-664 GEN
Solar/Wind Harmer
9.252
972165AH1-665 GEN
Solar/Wind Harmer
7.402
971673AH1-337 GEN
Solar/Wind Harmer
4.251
971029AG2-637 GEN
Solar/Wind Harmer
13.852
270543AE2-219 C
Solar/Wind Harmer
4.719
270240V3-007_GEN2
Solar/Wind Harmer
5.693
24729505KEY G4
Adder
5.961
958711AF2-162 GEN
Solar/Wind Harmer
0.929
965101AG1-375 GEN
Solar/Wind Harmer
9.182
945581AF1-223 GEN
Solar/Wind Harmer
4.163
961761AG1-017 GEN
Solar/Wind Harmer
0.393
970115AG2-085 GEN
Solar/Wind Harmer
3.664
274775LINCOLN ;6U
Adder
7.514
274776LINCOLN ;7U
Adder
7.514
274777LINCOLN ;8U
Adder
7.514
274814UNIV PK N;0U
Adder
4.489
274807UNIV PK N;3U
Adder
4.479
274805UNIV PK N;1U
Adder
4.459
274811UNIV PK N;7U
Adder
0.697
238152AF2-075_GEN
Solar/Wind Helper
0.593
23546401DTGZ2-030
Solar/Wind Helper
0.075
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
238208AF1-136 C
Solar/Wind Helper
0.18
237085AD2-009_GEN
Solar/Wind Helper
1.367
238126S14_GEN_1
Solar/Wind Helper
0.641
23559001PLEAS1
50/50
11.213
23684201S70BUS2
50/50
0.319
23562401OGROV2
50/50
2.411
24318805MLG1
50/50
6.319
24721905FLATG4
Adder
23.442
970153AG2-106 GEN
Solar/Wind Harmer
15.25
270512AE1-227 GEN2
Solar/Wind Harmer
2.245
971191AH1-055 GEN
Solar/Wind Harmer
22.406
957541AF2-048 GEN
Solar/Wind Harmer
1.601
270291AC1-194 GEN
Solar/Wind Harmer
10.629
961921AG1-034 GEN
Solar/Wind Harmer
12.731
960801AF2-371 GEN
Solar/Wind Harmer
2.533
964871AG1-351 GEN
Solar/Wind Harmer
1.749
270273AD2-016 GEN
Solar/Wind Harmer
2.659
972173AH1-669 GEN
Solar/Wind Harmer
4.984
241955AC1-078 GEN
Solar/Wind Harmer
7.382
24686205CER G4
Adder
8.21
24686405CER G5
Adder
8.177
942051AE2-217 GEN
Solar/Wind Harmer
17.654
253338AC1-165 GEN
Solar/Wind Harmer
1.064
253333AC1-068 GEN
Solar/Wind Harmer
1.027
241974AD2-163_GEN2
Solar/Wind Harmer
1.944
253415AE1-040 GEN
Solar/Wind Harmer
1.1
970605AG2-385 GEN
Solar/Wind Harmer
5.262
253406AD2-031_GEN
Solar/Wind Harmer
1.228
253316AC1-085 GEN3
Solar/Wind Harmer
7.992
253433AC1-085 GEN1
Solar/Wind Harmer
5.073
946181AF1-283 GEN
Solar/Wind Harmer
12.404
253303V4-073 C
Solar/Wind Harmer
0.11
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
942871AE2-306 GEN
Solar/Wind Harmer
0.858
270391AF1-285 GEN3
Solar/Wind Harmer
0.44
252510AF1-249 C
Solar/Wind Harmer
0.395
25196608WSDLE5
Adder
8.083
25194608D.CRK4
Adder
1.55
270485AE1-090_GEN
Solar/Wind Harmer
0.566
270222AC2-111 GEN
Solar/Wind Harmer
7.593
25196008MFTGT1
Adder
1.255
970243AG2-164 GEN
Solar/Wind Harmer
23.909
970519AG2-331 GEN
Solar/Wind Harmer
16.063
970699AG2-449 GEN
Solar/Wind Harmer
10.626
972167AH1-666 GEN
Solar/Wind Harmer
7.416
958171AF2-111 GEN
Solar/Wind Harmer
23.159
270437AC2-090 C
Solar/Wind Harmer
5.138
944531AF1-118 GEN
Solar/Wind Harmer
32.165
962031AG1-047 GEN
Solar/Wind Harmer
2.774
957741AF2-068 GEN
Solar/Wind Harmer
13.765
270356AE2-297 GEN
Solar/Wind Harmer
4.184
946031AF1-268 GEN
Solar/Wind Harmer
7.613
958821AF2-173 GEN
Solar/Wind Harmer
12.842
270004AE1-209 GEN
Solar/Wind Harmer
5.013
24728705AND G3
Adder
7.25
24728505AND G1
Adder
3.466
24642205MAYFLWER
Adder
0.568
274772LINCOLN ;3U
Adder
7.514
274752CRETE EC ;2U
Adder
7.332
274753CRETE EC ;3U
Adder
7.332
274724RIVER EC ;11
Adder
15.751
316097T157 G90
Solar/Wind Helper
1.299
964991AG1-363 GEN
Solar/Wind Helper
4.135
238148AE2-230_GEN2
Solar/Wind Helper
0.417
23750701CROSSCHOOL
Solar/Wind Helper
1.155
237080AD1-060 GEN
Solar/Wind Helper
0.284
237038AE2-054 C
Solar/Wind Helper
0.226
235062AE1-101 C1
Solar/Wind Helper
1.38
238127S14_GEN_2
Solar/Wind Helper
0.641
23779801AA1-109
Solar/Wind Helper
0.162
238118U2-030_1
Solar/Wind Helper
0.26
23559101PLEAS2
50/50
11.213
23684101S70BUS1
50/50
0.313
23562301OGROV1
50/50
2.427
24721705FLATG2
Adder
23.442
962761AG1-125 GEN
Solar/Wind Harmer
34.974
970149AG2-104 GEN
Solar/Wind Harmer
43.193
970155AG2-107 GEN
Solar/Wind Harmer
15.25
270510AE1-227 GEN1
Solar/Wind Harmer
2.645
960001AF2-291 GEN
Solar/Wind Harmer
3.152
970947AG2-589 GEN
Solar/Wind Harmer
2.059
270331AC1-082 GEN3
Solar/Wind Harmer
0.466
927014AC1-188 GEN
Solar/Wind Harmer
1.606
270349AD2-093_GEN
Solar/Wind Harmer
3.665
270263AC1-001 GEN
Solar/Wind Harmer
1.044
24686105CER G3
Adder
8.253
24686505CER G6
Adder
8.242
270159DARBY CT4
Adder
8.691
24723205RIVRG3
Adder
18.473
253343AC1-166 GEN
Solar/Wind Harmer
1.064
253325AC1-069 GEN
Solar/Wind Harmer
1.027
970593AG2-378 GEN
Solar/Wind Harmer
1.949
253432AC1-085 GEN2
Solar/Wind Harmer
0.255
946171AF1-282 GEN
Solar/Wind Harmer
9.541
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
25326309TAIT D
Adder
1.041
960071AF2-298 GEN
Solar/Wind Harmer
4.732
252507AC2-088 GEN
Solar/Wind Harmer
1.7
270223U2-072_GEN1
Solar/Wind Harmer
1.871
270578AF1-285 GEN2
Solar/Wind Harmer
1.144
270391AF1-285 GEN3
Solar/Wind Harmer
1.144
25194608D.CRK4
Adder
1.55
25196808ZIMRHP
Adder
71.347
270462AD2-086
Solar/Wind Harmer
6.509
25196008MFTGT1
Adder
1.296
970333AG2-219 GEN
Solar/Wind Harmer
29.222
945681AF1-233 GEN
Solar/Wind Harmer
17.467
942081AE2-220 GEN
Solar/Wind Harmer
5.883
270239V3-007_GEN1
Solar/Wind Harmer
1.584
247536S-71 GEN
Solar/Wind Harmer
3.724
965651AG1-433 GEN
Solar/Wind Harmer
5.019
958861AF2-177 GEN
Solar/Wind Harmer
10.036
945371AF1-202 GEN
Solar/Wind Harmer
6.405
971995AH1-542 GEN
Solar/Wind Harmer
10.093
270005AE1-210 C O1
Solar/Wind Harmer
5.013
965031AG1-367 GEN
Solar/Wind Harmer
9.173
970825AG2-519 GEN
Solar/Wind Harmer
2.158
970091AG2-072 GEN
Adder
70.193
24728605AND G2
Adder
3.466
24639705ELKHART HY
Adder
0.137
274773LINCOLN ;4U
Adder
7.514
274774LINCOLN ;5U
Adder
7.514
274751CRETE EC ;1U
Adder
7.332
274754CRETE EC ;4U
Adder
7.332
274723RIVER EC ;12
Adder
15.938
274812UNIV PK N;8U
Adder
4.45
23583801GRNGAP
Solar/Wind Helper
4.858
316095T157 G97
Solar/Wind Helper
1.299
238147AE2-230_GEN1
Solar/Wind Helper
0.415
238149AF1-291A_GEN
Solar/Wind Helper
0.119
238108AE1-109 GEN1
Solar/Wind Helper
0.088
237061AD1-155 GEN
Solar/Wind Helper
0.045
238185AF2-356 C
Solar/Wind Helper
1.996
238221AF1-254 C O1
Solar/Wind Helper
0.228
235067AD1-061 GEN
Solar/Wind Helper
0.412
235531U2-073 GEN
Solar/Wind Helper
2.523
238117U2-030
Solar/Wind Helper
0.26
944201AF1-088_MTX
Adder
103.64
957141AF2-008_MTX
Adder
51.82
LAGNLTFEXP_LAGN->PJM
CLTF
13.832
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.925
TVALTFEXP_TVA->PJM
CLTF
6.876
CPLELTFEXP_CPLE->PJM
CLTF
1.286
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.798
NYPJM->LTFIMP_NY
CLTF
4.417
LGEELTFEXP_LGEE->PJM
CLTF
6.111
WECLTFEXP_WEC->PJM
CLTF
3.336
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.614
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.188
MECLTFEXP_MEC->PJM
CLTF
14.066
SIGELTFEXP_SIGE->PJM
CLTF
0.455

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT10A_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT10A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:139.86 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5303.43
MW Contribution:1215.72
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
50/50
1215.723
24318905MLG2
50/50
4.724
270471AD2-092_GEN
Solar/Wind Harmer
3.698
970879AG2-548 GEN
Solar/Wind Harmer
6.239
971073AG2-665 GEN
Solar/Wind Harmer
6.239
971073AG2-665 GEN
Solar/Wind Harmer
4.353
946101AF1-275 GEN
Solar/Wind Harmer
1.525
972269AH1-719 GEN
Adder
2.293
24685805CER G1
Adder
8.254
24685905CER G2
Adder
8.254
24723005RIVRG1
Adder
18.592
24723105RIVRG2
Adder
18.592
942861AE2-305 GEN
Solar/Wind Harmer
7.696
270518AE2-148 GEN
Solar/Wind Harmer
11.94
970077AG2-063 GEN
Solar/Wind Harmer
5.308
962581AG1-107 GEN
Solar/Wind Harmer
4.865
961491AF2-440 GEN
Solar/Wind Harmer
2.022
972159AH1-661 GEN
Adder
0.962
962771AG1-126 GEN
Solar/Wind Harmer
35.245
270330AC1-082 GEN2
Solar/Wind Harmer
0.795
270329AC1-082 GEN1
Solar/Wind Harmer
0.468
270054AF2-122 C O1
Solar/Wind Harmer
3.32
940611AE2-048 GEN
Solar/Wind Harmer
22.287
941391AE2-136 GEN
Solar/Wind Harmer
11.549
970879AG2-548 GEN
Solar/Wind Harmer
4.353
270520AE2-214 GEN
Solar/Wind Harmer
6.113
270459AD2-067 GEN
Solar/Wind Harmer
8.438
961821AG1-024 GEN
Solar/Wind Harmer
8.566
270432AC2-029 GEN
Solar/Wind Harmer
7.042
970689AG2-444 GEN
Solar/Wind Harmer
16.397
270269AC2-059
Solar/Wind Harmer
9.378
972203AH1-686 GEN
Adder
2.313
270156DARBY CT1
Adder
8.909
270157DARBY CT2
Adder
8.887
270158DARBY CT3
Adder
8.745
945631AF1-228 GEN
Solar/Wind Harmer
4.662
270284AF1-227 GEN1
Solar/Wind Harmer
5.621
270286AF1-227 GEN2
Solar/Wind Harmer
2.079
270287AF1-227 GEN3
Solar/Wind Harmer
2.079
253383AE2-342_GEN
Solar/Wind Harmer
0.877
971985AH1-537 GEN
Solar/Wind Harmer
17.658
241973AD2-163_GEN1
Solar/Wind Harmer
1.962
943861AF1-054 GEN
Solar/Wind Harmer
3.799
943851AF1-053 GEN
Solar/Wind Harmer
1.836
270340AC2-060 GEN
Solar/Wind Harmer
2.985
24477305BRIDGE
Adder
0.341
241972AD1-140 GEN
Solar/Wind Harmer
4.346
270367AC2-061_GEN
Solar/Wind Harmer
3.072
253372AE2-315 SEC3
Adder
1.818
253372AE2-315 SEC3
Adder
1.818
25306009OHH W.
Adder
2.758
270578AF1-285 GEN2
Solar/Wind Harmer
0.444
253349AC2-067 GEN
Solar/Wind Harmer
4.752
253400AC2-068 GEN
Solar/Wind Harmer
1.911
252524AE2-267 GEN
Solar/Wind Harmer
1.499
25196408WSDLE3
Adder
8.387
25196308WSDLE2
Adder
8.314
25196208WSDLE1
Adder
8.294
25196708WSDLE6
Adder
8.273
25196508WSDLE4
Adder
8.064
270302AB2-170 GEN
Solar/Wind Harmer
7.9
270317AD1-130_GEN
Solar/Wind Harmer
3.028
944031AF1-071 GEN
Solar/Wind Harmer
0.944
25196108MFTGT2
Adder
1.44
25196108MFTGT2
Adder
1.337
972163AH1-664 GEN
Solar/Wind Harmer
9.324
972165AH1-665 GEN
Solar/Wind Harmer
7.459
971673AH1-337 GEN
Solar/Wind Harmer
4.287
971029AG2-637 GEN
Solar/Wind Harmer
13.968
270543AE2-219 C
Solar/Wind Harmer
4.759
270240V3-007_GEN2
Solar/Wind Harmer
5.741
24729505KEY G4
Adder
6.012
958711AF2-162 GEN
Solar/Wind Harmer
0.937
965101AG1-375 GEN
Solar/Wind Harmer
9.26
945581AF1-223 GEN
Solar/Wind Harmer
4.198
961761AG1-017 GEN
Solar/Wind Harmer
0.396
970115AG2-085 GEN
Solar/Wind Harmer
3.695
274775LINCOLN ;6U
Adder
7.577
274776LINCOLN ;7U
Adder
7.577
274777LINCOLN ;8U
Adder
7.577
274814UNIV PK N;0U
Adder
4.526
274807UNIV PK N;3U
Adder
4.517
274805UNIV PK N;1U
Adder
4.497
274811UNIV PK N;7U
Adder
0.593
238152AF2-075_GEN
Solar/Wind Helper
0.602
23546401DTGZ2-030
Solar/Wind Helper
0.076
238208AF1-136 C
Solar/Wind Helper
0.181
238109AE1-109 GEN2
Solar/Wind Helper
0.087
238110AE1-109 GEN3
Solar/Wind Helper
0.087
237085AD2-009_GEN
Solar/Wind Helper
1.378
3138216PACIFIC
Solar/Wind Helper
0.038
316411AF1-147_GEN1
Solar/Wind Helper
0.751
316415AF1-147_GEN2
Solar/Wind Helper
0.751
253394AE2-221_GEN
Solar/Wind Harmer
4.373
253398AE2-221_GEN2
Solar/Wind Harmer
4.373
253317AC1-085 GEN4
Solar/Wind Harmer
8.057
25326109MON D
Adder
1.263
270186AC1-089 GEN
Solar/Wind Harmer
5.865
253370AE2-315 SEC1
Adder
1.922
25322209TAIT E
Adder
9.347
25322209TAIT E
Adder
9.137
964601AG1-323 GEN
Solar/Wind Harmer
3.04
964601AG1-323 GEN
Solar/Wind Harmer
1.414
25183208HLCRTG
Solar/Wind Harmer
5.797
270224U2-072_GEN2
Solar/Wind Harmer
1.889
270227U2-072_GEN3
Solar/Wind Harmer
1.889
270228U2-072_GEN4
Solar/Wind Harmer
1.889
270231U2-072_GEN5
Solar/Wind Harmer
1.889
252509AD1-136 GEN
Solar/Wind Harmer
0.245
252519AF1-045_GEN
Solar/Wind Harmer
5.794
252516AE2-318_GEN
Solar/Wind Harmer
4.42
938701AE1-092 GEN
Solar/Wind Harmer
19.71
25194408D.CRK1
Adder
7.189
25194508D.CRK3
Adder
1.344
253378AE2-206_GEN
Solar/Wind Harmer
3.413
276820AF1-078_GEN
Solar/Wind Harmer
1.516
25326509SID D
Adder
1.242
970239AG2-162 GEN
Solar/Wind Harmer
10.263
24728805RICHG1
Adder
3.517
24728905RICHG2
Adder
3.517
970883AG2-550 GEN
Solar/Wind Harmer
9.293
970885AG2-551 GEN
Solar/Wind Harmer
2.161
270383AD1-128 GEN
Solar/Wind Harmer
5.669
24379505HDWTR1G C
Solar/Wind Harmer
7.337
270209AC1-174_GEN
Solar/Wind Harmer
5.178
926881AC1-175 GEN
Solar/Wind Harmer
5.178
247621Y3-024
Adder
0.223
944541AF1-119 GEN
Solar/Wind Harmer
3.879
960971AF2-388 GEN
Solar/Wind Harmer
10.123
270201AC2-176 GEN
Solar/Wind Harmer
4.758
964611AG1-324 GEN
Solar/Wind Harmer
1.091
964611AG1-324 GEN
Solar/Wind Harmer
0.484
970825AG2-519 GEN
Solar/Wind Harmer
9.752
960441AF2-335 GEN
Solar/Wind Harmer
9.237
247620Y3-023
Adder
0.416
274770LINCOLN ;1U
Adder
7.577
274771LINCOLN ;2U
Adder
7.577
238175AF1-290_GEN
Solar/Wind Helper
0.128
238169AE2-226 GEN1
Solar/Wind Helper
0.591
238170AE2-226 GEN2
Solar/Wind Helper
0.591
235020AA1-095 C
Solar/Wind Helper
0.044
23777901MDS_W4-102
Solar/Wind Helper
0.148
237034AC2-136 C
Solar/Wind Helper
0.192
237002AB1-128_GEN
Solar/Wind Helper
0.372
237001AB1-127_GEN
Solar/Wind Helper
0.372
235063AE1-101 C2
Solar/Wind Helper
1.393
23777801MSM_W1-116
Solar/Wind Helper
0.097
237025AB1-124 C
Solar/Wind Helper
0.14
237006AB1-125 GEN
Solar/Wind Helper
0.105
270599AE1-208 GEN
Solar/Wind Harmer
0.766
270031AE2-169
Solar/Wind Harmer
0.766
23559001PLEAS1
50/50
11.24
23684201S70BUS2
50/50
0.322
23562401OGROV2
50/50
2.431
24318805MLG1
50/50
6.369
23534401HANNIB
50/50
0.15
24721905FLATG4
Adder
23.592
970153AG2-106 GEN
Solar/Wind Harmer
15.368
270512AE1-227 GEN2
Solar/Wind Harmer
2.273
971191AH1-055 GEN
Solar/Wind Harmer
22.576
957541AF2-048 GEN
Solar/Wind Harmer
1.614
270291AC1-194 GEN
Solar/Wind Harmer
10.719
961921AG1-034 GEN
Solar/Wind Harmer
12.85
960801AF2-371 GEN
Solar/Wind Harmer
2.556
964871AG1-351 GEN
Solar/Wind Harmer
1.765
270273AD2-016 GEN
Solar/Wind Harmer
2.682
972173AH1-669 GEN
Solar/Wind Harmer
5.026
241955AC1-078 GEN
Solar/Wind Harmer
7.448
24686205CER G4
Adder
8.265
24686405CER G5
Adder
8.232
942051AE2-217 GEN
Solar/Wind Harmer
17.81
253338AC1-165 GEN
Solar/Wind Harmer
1.074
253333AC1-068 GEN
Solar/Wind Harmer
1.035
241974AD2-163_GEN2
Solar/Wind Harmer
1.962
253415AE1-040 GEN
Solar/Wind Harmer
1.109
970605AG2-385 GEN
Solar/Wind Harmer
5.308
253406AD2-031_GEN
Solar/Wind Harmer
1.238
253316AC1-085 GEN3
Solar/Wind Harmer
8.057
253433AC1-085 GEN1
Solar/Wind Harmer
5.115
946181AF1-283 GEN
Solar/Wind Harmer
12.504
253303V4-073 C
Solar/Wind Harmer
0.111
253370AE2-315 SEC1
Adder
1.922
253371AE2-315 SEC2
Adder
1.818
942871AE2-306 GEN
Solar/Wind Harmer
0.866
270391AF1-285 GEN3
Solar/Wind Harmer
0.444
252510AF1-249 C
Solar/Wind Harmer
0.398
25194608D.CRK4
Adder
1.563
25196608WSDLE5
Adder
8.148
270485AE1-090_GEN
Solar/Wind Harmer
0.571
270222AC2-111 GEN
Solar/Wind Harmer
7.655
25196008MFTGT1
Adder
1.265
970243AG2-164 GEN
Solar/Wind Harmer
24.096
970519AG2-331 GEN
Solar/Wind Harmer
16.189
970699AG2-449 GEN
Solar/Wind Harmer
10.709
972167AH1-666 GEN
Solar/Wind Harmer
7.473
958171AF2-111 GEN
Solar/Wind Harmer
23.339
270437AC2-090 C
Solar/Wind Harmer
5.18
944531AF1-118 GEN
Solar/Wind Harmer
32.44
962031AG1-047 GEN
Solar/Wind Harmer
2.797
957741AF2-068 GEN
Solar/Wind Harmer
13.882
946031AF1-268 GEN
Solar/Wind Harmer
7.677
958821AF2-173 GEN
Solar/Wind Harmer
12.949
270004AE1-209 GEN
Solar/Wind Harmer
5.055
270356AE2-297 GEN
Solar/Wind Harmer
4.219
24728705AND G3
Adder
7.308
24728505AND G1
Adder
3.494
24642205MAYFLWER
Adder
0.573
274772LINCOLN ;3U
Adder
7.577
274752CRETE EC ;2U
Adder
7.394
274753CRETE EC ;3U
Adder
7.394
274724RIVER EC ;11
Adder
15.884
316097T157 G90
Solar/Wind Helper
1.324
964991AG1-363 GEN
Solar/Wind Helper
4.195
238148AE2-230_GEN2
Solar/Wind Helper
0.423
237080AD1-060 GEN
Solar/Wind Helper
0.287
23750701CROSSCHOOL
Solar/Wind Helper
1.116
237038AE2-054 C
Solar/Wind Helper
0.228
235062AE1-101 C1
Solar/Wind Helper
1.393
23779801AA1-109
Solar/Wind Helper
0.164
23559101PLEAS2
50/50
11.24
23684101S70BUS1
50/50
0.316
23562301OGROV1
50/50
2.447
24721705FLATG2
Adder
23.592
962761AG1-125 GEN
Solar/Wind Harmer
35.245
970149AG2-104 GEN
Solar/Wind Harmer
43.528
970155AG2-107 GEN
Solar/Wind Harmer
15.368
270510AE1-227 GEN1
Solar/Wind Harmer
2.678
960001AF2-291 GEN
Solar/Wind Harmer
3.176
970947AG2-589 GEN
Solar/Wind Harmer
2.074
270331AC1-082 GEN3
Solar/Wind Harmer
0.469
927014AC1-188 GEN
Solar/Wind Harmer
1.618
270349AD2-093_GEN
Solar/Wind Harmer
3.698
270263AC1-001 GEN
Solar/Wind Harmer
1.052
270159DARBY CT4
Adder
8.767
24686105CER G3
Adder
8.308
24686505CER G6
Adder
8.298
24723205RIVRG3
Adder
18.592
253343AC1-166 GEN
Solar/Wind Harmer
1.074
253325AC1-069 GEN
Solar/Wind Harmer
1.035
970593AG2-378 GEN
Solar/Wind Harmer
1.966
253432AC1-085 GEN2
Solar/Wind Harmer
0.257
946171AF1-282 GEN
Solar/Wind Harmer
9.619
253370AE2-315 SEC1
Adder
1.922
253371AE2-315 SEC2
Adder
1.818
25326309TAIT D
Adder
1.05
960071AF2-298 GEN
Solar/Wind Harmer
4.772
270223U2-072_GEN1
Solar/Wind Harmer
1.889
252507AC2-088 GEN
Solar/Wind Harmer
1.713
270578AF1-285 GEN2
Solar/Wind Harmer
1.155
270391AF1-285 GEN3
Solar/Wind Harmer
1.155
25194608D.CRK4
Adder
1.563
25196808ZIMRHP
Adder
71.915
270462AD2-086
Solar/Wind Harmer
6.572
25196008MFTGT1
Adder
1.306
970333AG2-219 GEN
Solar/Wind Harmer
29.451
945681AF1-233 GEN
Solar/Wind Harmer
17.602
247536S-71 GEN
Solar/Wind Harmer
3.755
942081AE2-220 GEN
Solar/Wind Harmer
5.932
270239V3-007_GEN1
Solar/Wind Harmer
1.597
971995AH1-542 GEN
Solar/Wind Harmer
10.198
965651AG1-433 GEN
Solar/Wind Harmer
5.062
958861AF2-177 GEN
Solar/Wind Harmer
10.121
945371AF1-202 GEN
Solar/Wind Harmer
6.459
270005AE1-210 C O1
Solar/Wind Harmer
5.055
965031AG1-367 GEN
Solar/Wind Harmer
9.249
970825AG2-519 GEN
Solar/Wind Harmer
2.176
970091AG2-072 GEN
Adder
70.733
24728605AND G2
Adder
3.494
24639705ELKHART HY
Adder
0.139
274773LINCOLN ;4U
Adder
7.577
274774LINCOLN ;5U
Adder
7.577
274751CRETE EC ;1U
Adder
7.394
274754CRETE EC ;4U
Adder
7.394
274723RIVER EC ;12
Adder
16.072
274812UNIV PK N;8U
Adder
4.487
23583801GRNGAP
Solar/Wind Helper
4.952
316095T157 G97
Solar/Wind Helper
1.324
238147AE2-230_GEN1
Solar/Wind Helper
0.422
238149AF1-291A_GEN
Solar/Wind Helper
0.12
237061AD1-155 GEN
Solar/Wind Helper
0.045
238221AF1-254 C O1
Solar/Wind Helper
0.23
238108AE1-109 GEN1
Solar/Wind Helper
0.087
235067AD1-061 GEN
Solar/Wind Helper
0.416
237030AB1-096 C
Solar/Wind Helper
0.06
944201AF1-088_MTX
Adder
104.45
957141AF2-008_MTX
Adder
52.225
LAGNLTFEXP_LAGN->PJM
CLTF
13.912
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.88
TVALTFEXP_TVA->PJM
CLTF
6.914
CPLELTFEXP_CPLE->PJM
CLTF
1.246
CBM West 2LTFEXP_CBM-W2->PJM
CBM
103.491
NYPJM->LTFIMP_NY
CLTF
4.434
LGEELTFEXP_LGEE->PJM
CLTF
6.157
WECLTFEXP_WEC->PJM
CLTF
3.363
AG2-052LTFEXP_AG2-052->PJM
LTF
0.21
AH1-155LTFEXP_AH1-155->PJM
LTF
0.314
CBM West 1LTFEXP_CBM-W1->PJM
CBM
123.724
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.351
MECLTFEXP_MEC->PJM
CLTF
14.175
SIGELTFEXP_SIGE->PJM
CLTF
0.458

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-502T_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-502T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:139.36 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5284.61
MW Contribution:1217.06
Bus #Bus NameTypeMW Contribution
23559001PLEAS1
50/50
11.213
23684201S70BUS2
50/50
0.319
23562401OGROV2
50/50
2.411
24318805MLG1
50/50
6.319
24721905FLATG4
Adder
23.442
970153AG2-106 GEN
Solar/Wind Harmer
18.834
270512AE1-227 GEN2
Solar/Wind Harmer
1.907
971191AH1-055 GEN
Solar/Wind Harmer
18.237
270291AC1-194 GEN
Solar/Wind Harmer
5.533
961921AG1-034 GEN
Solar/Wind Harmer
6.218
270273AD2-016 GEN
Solar/Wind Harmer
0.721
972173AH1-669 GEN
Solar/Wind Harmer
3.478
241955AC1-078 GEN
Solar/Wind Harmer
0.006
24686205CER G4
Adder
8.21
24686405CER G5
Adder
8.177
942051AE2-217 GEN
Solar/Wind Harmer
12.316
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.011
241974AD2-163_GEN2
Solar/Wind Harmer
0.005
253415AE1-040 GEN
Solar/Wind Harmer
0.003
970605AG2-385 GEN
Solar/Wind Harmer
4.136
253406AD2-031_GEN
Solar/Wind Harmer
0.499
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
8.654
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
270391AF1-285 GEN3
Solar/Wind Harmer
0.44
970191AG2-125 GEN
Solar/Wind Harmer
1.697
252510AF1-249 C
Solar/Wind Harmer
0.051
25196608WSDLE5
Adder
8.083
25194608D.CRK4
Adder
1.55
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270222AC2-111 GEN
Solar/Wind Harmer
3.293
25196008MFTGT1
Adder
1.255
970243AG2-164 GEN
Solar/Wind Harmer
3.783
970519AG2-331 GEN
Solar/Wind Harmer
16.815
970699AG2-449 GEN
Solar/Wind Harmer
1.617
972167AH1-666 GEN
Solar/Wind Harmer
5.174
958171AF2-111 GEN
Solar/Wind Harmer
16.157
270437AC2-090 C
Solar/Wind Harmer
0.003
944531AF1-118 GEN
Solar/Wind Harmer
28.735
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
9.603
270356AE2-297 GEN
Solar/Wind Harmer
0.009
946031AF1-268 GEN
Solar/Wind Harmer
6.09
958821AF2-173 GEN
Solar/Wind Harmer
8.959
270004AE1-209 GEN
Solar/Wind Harmer
1.387
971617AH1-308 GEN
Solar/Wind Harmer
5.319
970289AG2-191 GEN
Solar/Wind Harmer
0.701
970291AG2-192 GEN
Solar/Wind Harmer
0.638
970513AG2-328 GEN
Solar/Wind Harmer
2.761
970517AG2-330 GEN
Solar/Wind Harmer
16.566
247642Z2-115 C
Solar/Wind Harmer
0.003
270043AE2-236 GEN
Solar/Wind Harmer
4.072
959331AF2-224 GEN
Solar/Wind Harmer
4.433
965021AG1-366 GEN
Solar/Wind Harmer
2.111
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.041
24728705AND G3
Adder
7.25
24728505AND G1
Adder
3.466
970349AG2-230 GEN
Solar/Wind Harmer
9.454
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.281
270491AE1-102 GEN2
Solar/Wind Harmer
0.817
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970031AG2-029 GEN
Solar/Wind Harmer
4.079
270535AF1-215 GEN1
Solar/Wind Harmer
0.008
270053AF1-130 C
Solar/Wind Harmer
1.414
247643Z2-116 C
Solar/Wind Harmer
0
24642205MAYFLWER
Adder
0.568
945111AF1-176 GEN
Solar/Wind Harmer
5.045
274772LINCOLN ;3U
Adder
7.514
274752CRETE EC ;2U
Adder
7.332
274753CRETE EC ;3U
Adder
7.332
274724RIVER EC ;11
Adder
15.751
970193AG2-126 GEN
Solar/Wind Harmer
9.3
276806AD2-047 C O1
Solar/Wind Harmer
3.508
970941AG2-585 GEN
Solar/Wind Harmer
7.739
276897AD1-100 C
Solar/Wind Harmer
0.008
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
20.212
270258AD1-119 GEN
Solar/Wind Harmer
0.002
276893AG1-478 C
Solar/Wind Harmer
0.245
24441205WTRV SLR C
Solar/Wind Harmer
0
943121AE2-341 GEN
Solar/Wind Harmer
10.327
943591AF1-030 GEN
Solar/Wind Harmer
6.867
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
270404AC1-167 GEN
Solar/Wind Harmer
0.003
276805AD2-038 GEN
Solar/Wind Harmer
0.002
316097T157 G90
Solar/Wind Helper
1.299
964991AG1-363 GEN
Solar/Wind Helper
4.135
238148AE2-230_GEN2
Solar/Wind Helper
0.417
23750701CROSSCHOOL
Solar/Wind Helper
1.155
237080AD1-060 GEN
Solar/Wind Helper
0.284
237038AE2-054 C
Solar/Wind Helper
0.226
235062AE1-101 C1
Solar/Wind Helper
1.38
238127S14_GEN_2
Solar/Wind Helper
0.641
23779801AA1-109
Solar/Wind Helper
0.162
238118U2-030_1
Solar/Wind Helper
0.26
970935AG2-582 GEN
50/50
1217.062
24318905MLG2
50/50
4.656
270471AD2-092_GEN
Solar/Wind Harmer
0.005
971073AG2-665 GEN
Solar/Wind Harmer
6.304
24685805CER G1
Adder
8.199
24685905CER G2
Adder
8.199
972269AH1-719 GEN
Adder
2.268
24723005RIVRG1
Adder
18.473
24723105RIVRG2
Adder
18.473
942861AE2-305 GEN
Solar/Wind Harmer
5.322
270518AE2-148 GEN
Solar/Wind Harmer
0.589
970077AG2-063 GEN
Solar/Wind Harmer
3.909
962581AG1-107 GEN
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
0.952
253394AE2-221_GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0.008
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
270186AC1-089 GEN
Solar/Wind Harmer
0.004
25326109MON D
Adder
1.252
253370AE2-315 SEC1
Adder
1.906
25322209TAIT E
Adder
9.269
25322209TAIT E
Adder
9.061
25183208HLCRTG
Solar/Wind Harmer
0.01
964601AG1-323 GEN
Solar/Wind Harmer
2.647
964601AG1-323 GEN
Solar/Wind Harmer
1.765
252509AD1-136 GEN
Solar/Wind Harmer
0.033
252519AF1-045_GEN
Solar/Wind Harmer
5.748
252516AE2-318_GEN
Solar/Wind Harmer
5.098
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
10.591
971655AH1-328 GEN
Solar/Wind Harmer
2.34
25194408D.CRK1
Adder
7.132
25194508D.CRK3
Adder
1.333
253378AE2-206_GEN
Solar/Wind Harmer
0.003
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
2.833
25326509SID D
Adder
1.231
970239AG2-162 GEN
Solar/Wind Harmer
1.617
24728805RICHG1
Adder
3.489
24728905RICHG2
Adder
3.489
970883AG2-550 GEN
Solar/Wind Harmer
6.429
970885AG2-551 GEN
Solar/Wind Harmer
2.143
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
247621Y3-024
Adder
0.222
944541AF1-119 GEN
Solar/Wind Harmer
0.429
960971AF2-388 GEN
Solar/Wind Harmer
3.759
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.48
970825AG2-519 GEN
Solar/Wind Harmer
7.086
960441AF2-335 GEN
Solar/Wind Harmer
6.391
270599AE1-208 GEN
Solar/Wind Harmer
5.854
270031AE2-169
Solar/Wind Harmer
3.512
971613AH1-306 GEN
Solar/Wind Harmer
3.063
942221AE2-234 GEN
Solar/Wind Harmer
0.032
970321AG2-212 GEN
Solar/Wind Harmer
2.761
970611AG2-400 GEN
Solar/Wind Harmer
6.333
970627AG2-408 GEN
Solar/Wind Harmer
1.9
970235AG2-159 GEN
Solar/Wind Harmer
3.847
970235AG2-159 GEN
Solar/Wind Harmer
2.207
339221AD2-048_GEN
Solar/Wind Harmer
0.004
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
971199AH1-059 GEN
Solar/Wind Harmer
2.513
246938BC-WTG3
Solar/Wind Harmer
0.228
246937BC-WTG2
Solar/Wind Harmer
0.255
972043AH1-570 GEN
Solar/Wind Harmer
1.633
972045AH1-571 GEN
Solar/Wind Harmer
1.308
966841AG1-555 GEN
Solar/Wind Harmer
0.709
944971AF1-162 GEN
Solar/Wind Harmer
6.265
965681AG1-436 GEN
Solar/Wind Harmer
7.82
965791AG1-447 GEN
Solar/Wind Harmer
5.734
270216AD2-079_GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.412
270526AF1-158 GEN
Solar/Wind Harmer
0.008
24441505OLIV SLR
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
3.641
957891AF2-083 GEN
Solar/Wind Harmer
0.001
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
4.56
961051AF2-396 GEN
Solar/Wind Harmer
12.428
961051AF2-396 GEN
Solar/Wind Harmer
8.285
274770LINCOLN ;1U
Adder
7.514
274771LINCOLN ;2U
Adder
7.514
971125AH1-004 GEN
Solar/Wind Harmer
2.483
970107AG2-081 GEN
Solar/Wind Harmer
1.862
960161AF2-307 GEN
Solar/Wind Harmer
4.096
945391AF1-204 GEN
Solar/Wind Harmer
6.587
274888KELLY CRK;1U
Solar/Wind Harmer
0.364
274887GEN-1.85
Solar/Wind Harmer
0.163
276843GEN-1.7
Solar/Wind Harmer
0.2
958011AF2-095 GEN
Solar/Wind Harmer
8.915
970623AG2-406 GEN
Solar/Wind Harmer
1.132
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
241960AC2-195 GEN
Solar/Wind Harmer
0.005
958481AF2-142 GEN
Solar/Wind Harmer
9.231
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.833
971573AH1-285 GEN
Solar/Wind Harmer
1.146
958491AF2-143 GEN
Solar/Wind Harmer
9.212
274879MINONK ;1U
Solar/Wind Harmer
0.259
238175AF1-290_GEN
Solar/Wind Helper
0.126
238169AE2-226 GEN1
Solar/Wind Helper
0.582
238170AE2-226 GEN2
Solar/Wind Helper
0.582
235020AA1-095 C
Solar/Wind Helper
0.044
23777901MDS_W4-102
Solar/Wind Helper
0.146
238120AE2-309 GEN
Solar/Wind Helper
0.406
237034AC2-136 C
Solar/Wind Helper
0.189
237002AB1-128_GEN
Solar/Wind Helper
0.369
235063AE1-101 C2
Solar/Wind Helper
1.38
237001AB1-127_GEN
Solar/Wind Helper
0.368
23777801MSM_W1-116
Solar/Wind Helper
0.096
962691AG1-118 GEN
Solar/Wind Harmer
3.447
962771AG1-126 GEN
Solar/Wind Harmer
29.494
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0.006
970879AG2-548 GEN
Solar/Wind Harmer
6.304
940611AE2-048 GEN
Solar/Wind Harmer
17.215
941391AE2-136 GEN
Solar/Wind Harmer
9.698
270520AE2-214 GEN
Solar/Wind Harmer
0.011
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.145
972203AH1-686 GEN
Adder
2.298
270432AC2-029 GEN
Solar/Wind Harmer
3.085
970689AG2-444 GEN
Solar/Wind Harmer
14.206
270269AC2-059
Solar/Wind Harmer
0.004
270156DARBY CT1
Adder
8.832
270157DARBY CT2
Adder
8.81
270158DARBY CT3
Adder
8.67
945631AF1-228 GEN
Solar/Wind Harmer
0
270284AF1-227 GEN1
Solar/Wind Harmer
0.009
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
971985AH1-537 GEN
Solar/Wind Harmer
2.037
253383AE2-342_GEN
Solar/Wind Harmer
0.002
241973AD2-163_GEN1
Solar/Wind Harmer
0.005
943861AF1-054 GEN
Solar/Wind Harmer
2.627
943851AF1-053 GEN
Solar/Wind Harmer
1.82
270340AC2-060 GEN
Solar/Wind Harmer
0.008
24477305BRIDGE
Adder
0.338
241972AD1-140 GEN
Solar/Wind Harmer
0.734
270367AC2-061_GEN
Solar/Wind Harmer
0.005
253372AE2-315 SEC3
Adder
1.803
253372AE2-315 SEC3
Adder
1.803
25306009OHH W.
Adder
2.735
270578AF1-285 GEN2
Solar/Wind Harmer
0.44
253349AC2-067 GEN
Solar/Wind Harmer
2.077
253400AC2-068 GEN
Solar/Wind Harmer
0.835
252524AE2-267 GEN
Solar/Wind Harmer
0.002
25196408WSDLE3
Adder
8.32
25196308WSDLE2
Adder
8.248
25196208WSDLE1
Adder
8.227
25196708WSDLE6
Adder
8.207
25196508WSDLE4
Adder
8
270302AB2-170 GEN
Solar/Wind Harmer
0.004
270317AD1-130_GEN
Solar/Wind Harmer
0.009
971653AH1-327 GEN
Solar/Wind Harmer
0.917
25196108MFTGT2
Adder
1.429
25196108MFTGT2
Adder
1.327
972163AH1-664 GEN
Solar/Wind Harmer
7.187
972165AH1-665 GEN
Solar/Wind Harmer
5.756
971673AH1-337 GEN
Solar/Wind Harmer
4.191
971029AG2-637 GEN
Solar/Wind Harmer
9.664
270543AE2-219 C
Solar/Wind Harmer
0.004
270240V3-007_GEN2
Solar/Wind Harmer
0.002
24729505KEY G4
Adder
5.961
965101AG1-375 GEN
Solar/Wind Harmer
6.406
945581AF1-223 GEN
Solar/Wind Harmer
0
970115AG2-085 GEN
Solar/Wind Harmer
2.556
971609AH1-304 GEN
Solar/Wind Harmer
1.043
270024AE2-089 GEN
Solar/Wind Harmer
0.007
270594AE1-207 GEN
Solar/Wind Harmer
7.147
270071AF1-092 GEN
Solar/Wind Harmer
12.224
970289AG2-191 GEN
Solar/Wind Harmer
1.211
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
8.573
965051AG1-369 GEN
Solar/Wind Harmer
3.147
971347AH1-153 GEN
Solar/Wind Harmer
9.454
965041AG1-368 GEN
Solar/Wind Harmer
6.297
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
3.74
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.796
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.008
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
963841AG1-237 GEN
Solar/Wind Harmer
2.71
971771AH1-392 GEN
Solar/Wind Harmer
6.248
971769AH1-391 GEN
Solar/Wind Harmer
6.974
247607V1-011 GEN
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
2.801
23559101PLEAS2
50/50
11.213
23684101S70BUS1
50/50
0.313
23562301OGROV1
50/50
2.427
24721705FLATG2
Adder
23.442
962761AG1-125 GEN
Solar/Wind Harmer
29.494
970149AG2-104 GEN
Solar/Wind Harmer
31.855
970155AG2-107 GEN
Solar/Wind Harmer
18.834
270510AE1-227 GEN1
Solar/Wind Harmer
1.907
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
970947AG2-589 GEN
Solar/Wind Harmer
0.239
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
927014AC1-188 GEN
Solar/Wind Harmer
0.004
270349AD2-093_GEN
Solar/Wind Harmer
0.005
270263AC1-001 GEN
Solar/Wind Harmer
0.698
24686105CER G3
Adder
8.253
24686505CER G6
Adder
8.242
270159DARBY CT4
Adder
8.691
24723205RIVRG3
Adder
18.473
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.011
970593AG2-378 GEN
Solar/Wind Harmer
1.53
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.657
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
25326309TAIT D
Adder
1.041
960071AF2-298 GEN
Solar/Wind Harmer
3.297
252507AC2-088 GEN
Solar/Wind Harmer
0.3
270223U2-072_GEN1
Solar/Wind Harmer
0.001
25194608D.CRK4
Adder
1.55
25196808ZIMRHP
Adder
71.347
270462AD2-086
Solar/Wind Harmer
0.014
25196008MFTGT1
Adder
1.296
970333AG2-219 GEN
Solar/Wind Harmer
4.624
945681AF1-233 GEN
Solar/Wind Harmer
12.186
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.707
247536S-71 GEN
Solar/Wind Harmer
0.258
965651AG1-433 GEN
Solar/Wind Harmer
1.879
958861AF2-177 GEN
Solar/Wind Harmer
2.776
945371AF1-202 GEN
Solar/Wind Harmer
0.001
971995AH1-542 GEN
Solar/Wind Harmer
2.347
970773AG2-487 GEN
Solar/Wind Harmer
1.131
270005AE1-210 C O1
Solar/Wind Harmer
1.387
965031AG1-367 GEN
Solar/Wind Harmer
6.4
970825AG2-519 GEN
Solar/Wind Harmer
2.27
970091AG2-072 GEN
Adder
70.193
270032AE2-172
Solar/Wind Harmer
4.254
970291AG2-192 GEN
Solar/Wind Harmer
0.829
970245AG2-165 GEN
Solar/Wind Harmer
2.761
276903AD2-071 C
Solar/Wind Harmer
7.113
965011AG1-365 GEN
Solar/Wind Harmer
6.333
247521TR3_G114
Solar/Wind Harmer
0.23
270246TR4_N_V150
Solar/Wind Harmer
0.041
24728605AND G2
Adder
3.466
339216AC1-074 GEN
Solar/Wind Harmer
0.172
965421AG1-410 GEN
Solar/Wind Harmer
18.858
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
7.853
246936BC-WTG1
Solar/Wind Harmer
0.255
24791305MDL-5G
Solar/Wind Harmer
0.001
270489AE1-102 GEN1
Solar/Wind Harmer
0.817
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.162
24695305TIMB G C
Solar/Wind Harmer
0.002
270055AF2-134 C O1
Solar/Wind Harmer
0.005
970373AG2-245 GEN
Solar/Wind Harmer
13.169
270063AE2-323 C
Solar/Wind Harmer
0.005
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.002
24639705ELKHART HY
Adder
0.137
963741AG1-226 GEN
Solar/Wind Harmer
14.772
945111AF1-176 GEN
Solar/Wind Harmer
11.105
270505AE1-170 C O1
Solar/Wind Harmer
6.535
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
274773LINCOLN ;4U
Adder
7.514
274774LINCOLN ;5U
Adder
7.514
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.241
274751CRETE EC ;1U
Adder
7.332
274754CRETE EC ;4U
Adder
7.332
274723RIVER EC ;12
Adder
15.938
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.45
276776AD2-060 GEN
Solar/Wind Harmer
0.646
941551AE2-152 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
4.613
276691AA1-018 GEN1
Solar/Wind Harmer
0.745
276901AD2-066 C O1
Solar/Wind Harmer
0.006
944231AF1-091 GEN
Solar/Wind Harmer
1.635
971997AH1-543 GEN
Solar/Wind Harmer
3.22
23583801GRNGAP
Solar/Wind Helper
4.858
316095T157 G97
Solar/Wind Helper
1.299
238147AE2-230_GEN1
Solar/Wind Helper
0.415
238149AF1-291A_GEN
Solar/Wind Helper
0.119
238108AE1-109 GEN1
Solar/Wind Helper
0.088
237061AD1-155 GEN
Solar/Wind Helper
0.045
238185AF2-356 C
Solar/Wind Helper
1.996
238221AF1-254 C O1
Solar/Wind Helper
0.228
235067AD1-061 GEN
Solar/Wind Helper
0.412
235531U2-073 GEN
Solar/Wind Helper
2.523
238117U2-030
Solar/Wind Helper
0.26
274775LINCOLN ;6U
Adder
7.514
274776LINCOLN ;7U
Adder
7.514
274777LINCOLN ;8U
Adder
7.514
274814UNIV PK N;0U
Adder
4.489
274807UNIV PK N;3U
Adder
4.479
274805UNIV PK N;1U
Adder
4.459
274811UNIV PK N;7U
Adder
0.697
960591AF2-350 GEN
Solar/Wind Harmer
6.191
270399AC1-101 GEN
Solar/Wind Harmer
1.957
270400AC1-102 GEN
Solar/Wind Harmer
1.957
970833AG2-524 GEN
Solar/Wind Harmer
6.792
970833AG2-524 GEN
Solar/Wind Harmer
4.528
970179AG2-119 GEN
Solar/Wind Harmer
5.506
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
970169AG2-114 GEN
Solar/Wind Harmer
6.145
276868AE1-113 GEN
Solar/Wind Harmer
1.231
276882AE2-255 GEN
Solar/Wind Harmer
0.717
238152AF2-075_GEN
Solar/Wind Helper
0.593
23546401DTGZ2-030
Solar/Wind Helper
0.075
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
238208AF1-136 C
Solar/Wind Helper
0.18
237085AD2-009_GEN
Solar/Wind Helper
1.367
238126S14_GEN_1
Solar/Wind Helper
0.641
944201AF1-088_MTX
Adder
103.64
957141AF2-008_MTX
Adder
51.82
LAGNLTFEXP_LAGN->PJM
CLTF
13.832
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.925
TVALTFEXP_TVA->PJM
CLTF
6.876
CPLELTFEXP_CPLE->PJM
CLTF
1.286
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.798
NYPJM->LTFIMP_NY
CLTF
4.417
LGEELTFEXP_LGEE->PJM
CLTF
6.111
WECLTFEXP_WEC->PJM
CLTF
3.336
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.614
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.188
MECLTFEXP_MEC->PJM
CLTF
14.066
SIGELTFEXP_SIGE->PJM
CLTF
0.455

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-028_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:139.32 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5282.91
MW Contribution:1217.06
Bus #Bus NameTypeMW Contribution
23559001PLEAS1
50/50
11.213
23684201S70BUS2
50/50
0.319
23562401OGROV2
50/50
2.411
24318805MLG1
50/50
6.319
24721905FLATG4
Adder
23.442
970153AG2-106 GEN
Solar/Wind Harmer
18.834
270512AE1-227 GEN2
Solar/Wind Harmer
1.907
971191AH1-055 GEN
Solar/Wind Harmer
18.237
270291AC1-194 GEN
Solar/Wind Harmer
5.533
961921AG1-034 GEN
Solar/Wind Harmer
6.218
270273AD2-016 GEN
Solar/Wind Harmer
0.721
972173AH1-669 GEN
Solar/Wind Harmer
3.478
241955AC1-078 GEN
Solar/Wind Harmer
0.006
24686205CER G4
Adder
8.21
24686405CER G5
Adder
8.177
942051AE2-217 GEN
Solar/Wind Harmer
12.316
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.011
241974AD2-163_GEN2
Solar/Wind Harmer
0.005
253415AE1-040 GEN
Solar/Wind Harmer
0.003
970605AG2-385 GEN
Solar/Wind Harmer
4.136
253406AD2-031_GEN
Solar/Wind Harmer
0.499
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
8.654
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
270391AF1-285 GEN3
Solar/Wind Harmer
0.44
970191AG2-125 GEN
Solar/Wind Harmer
1.697
252510AF1-249 C
Solar/Wind Harmer
0.051
25196608WSDLE5
Adder
8.083
25194608D.CRK4
Adder
1.55
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270222AC2-111 GEN
Solar/Wind Harmer
3.293
25196008MFTGT1
Adder
1.255
970243AG2-164 GEN
Solar/Wind Harmer
3.783
970519AG2-331 GEN
Solar/Wind Harmer
16.815
970699AG2-449 GEN
Solar/Wind Harmer
1.617
972167AH1-666 GEN
Solar/Wind Harmer
5.174
958171AF2-111 GEN
Solar/Wind Harmer
16.157
270437AC2-090 C
Solar/Wind Harmer
0.003
944531AF1-118 GEN
Solar/Wind Harmer
28.735
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
9.603
270356AE2-297 GEN
Solar/Wind Harmer
0.009
946031AF1-268 GEN
Solar/Wind Harmer
6.09
958821AF2-173 GEN
Solar/Wind Harmer
8.959
270004AE1-209 GEN
Solar/Wind Harmer
1.387
971617AH1-308 GEN
Solar/Wind Harmer
5.319
970289AG2-191 GEN
Solar/Wind Harmer
0.701
970291AG2-192 GEN
Solar/Wind Harmer
0.638
970513AG2-328 GEN
Solar/Wind Harmer
2.761
970517AG2-330 GEN
Solar/Wind Harmer
16.566
247642Z2-115 C
Solar/Wind Harmer
0.003
270043AE2-236 GEN
Solar/Wind Harmer
4.072
959331AF2-224 GEN
Solar/Wind Harmer
4.433
965021AG1-366 GEN
Solar/Wind Harmer
2.111
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.041
24728705AND G3
Adder
7.25
24728505AND G1
Adder
3.466
970349AG2-230 GEN
Solar/Wind Harmer
9.454
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.281
270491AE1-102 GEN2
Solar/Wind Harmer
0.817
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970031AG2-029 GEN
Solar/Wind Harmer
4.079
270535AF1-215 GEN1
Solar/Wind Harmer
0.008
270053AF1-130 C
Solar/Wind Harmer
1.414
247643Z2-116 C
Solar/Wind Harmer
0
24642205MAYFLWER
Adder
0.568
945111AF1-176 GEN
Solar/Wind Harmer
5.045
274772LINCOLN ;3U
Adder
7.514
274752CRETE EC ;2U
Adder
7.332
274753CRETE EC ;3U
Adder
7.332
274724RIVER EC ;11
Adder
15.751
970193AG2-126 GEN
Solar/Wind Harmer
9.3
276806AD2-047 C O1
Solar/Wind Harmer
3.508
970941AG2-585 GEN
Solar/Wind Harmer
7.739
276897AD1-100 C
Solar/Wind Harmer
0.008
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
20.212
270258AD1-119 GEN
Solar/Wind Harmer
0.002
276893AG1-478 C
Solar/Wind Harmer
0.245
24441205WTRV SLR C
Solar/Wind Harmer
0
943121AE2-341 GEN
Solar/Wind Harmer
10.327
943591AF1-030 GEN
Solar/Wind Harmer
6.867
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
270404AC1-167 GEN
Solar/Wind Harmer
0.003
276805AD2-038 GEN
Solar/Wind Harmer
0.002
316097T157 G90
Solar/Wind Helper
1.299
964991AG1-363 GEN
Solar/Wind Helper
4.135
238148AE2-230_GEN2
Solar/Wind Helper
0.417
23750701CROSSCHOOL
Solar/Wind Helper
1.155
237080AD1-060 GEN
Solar/Wind Helper
0.284
237038AE2-054 C
Solar/Wind Helper
0.226
235062AE1-101 C1
Solar/Wind Helper
1.38
238127S14_GEN_2
Solar/Wind Helper
0.641
23779801AA1-109
Solar/Wind Helper
0.162
238118U2-030_1
Solar/Wind Helper
0.26
970935AG2-582 GEN
50/50
1217.062
24318905MLG2
50/50
4.656
270471AD2-092_GEN
Solar/Wind Harmer
0.005
971073AG2-665 GEN
Solar/Wind Harmer
6.304
24685805CER G1
Adder
8.199
24685905CER G2
Adder
8.199
972269AH1-719 GEN
Adder
2.268
24723005RIVRG1
Adder
18.473
24723105RIVRG2
Adder
18.473
942861AE2-305 GEN
Solar/Wind Harmer
5.322
270518AE2-148 GEN
Solar/Wind Harmer
0.589
970077AG2-063 GEN
Solar/Wind Harmer
3.909
962581AG1-107 GEN
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
0.952
253394AE2-221_GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0.008
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
270186AC1-089 GEN
Solar/Wind Harmer
0.004
25326109MON D
Adder
1.252
253370AE2-315 SEC1
Adder
1.906
25322209TAIT E
Adder
9.269
25322209TAIT E
Adder
9.061
25183208HLCRTG
Solar/Wind Harmer
0.01
964601AG1-323 GEN
Solar/Wind Harmer
2.647
964601AG1-323 GEN
Solar/Wind Harmer
1.765
252509AD1-136 GEN
Solar/Wind Harmer
0.033
252519AF1-045_GEN
Solar/Wind Harmer
5.748
252516AE2-318_GEN
Solar/Wind Harmer
5.098
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
10.591
971655AH1-328 GEN
Solar/Wind Harmer
2.34
25194408D.CRK1
Adder
7.132
25194508D.CRK3
Adder
1.333
253378AE2-206_GEN
Solar/Wind Harmer
0.003
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
2.833
25326509SID D
Adder
1.231
970239AG2-162 GEN
Solar/Wind Harmer
1.617
24728805RICHG1
Adder
3.489
24728905RICHG2
Adder
3.489
970883AG2-550 GEN
Solar/Wind Harmer
6.429
970885AG2-551 GEN
Solar/Wind Harmer
2.143
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
247621Y3-024
Adder
0.222
944541AF1-119 GEN
Solar/Wind Harmer
0.429
960971AF2-388 GEN
Solar/Wind Harmer
3.759
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.48
970825AG2-519 GEN
Solar/Wind Harmer
7.086
960441AF2-335 GEN
Solar/Wind Harmer
6.391
270599AE1-208 GEN
Solar/Wind Harmer
5.854
270031AE2-169
Solar/Wind Harmer
3.512
971613AH1-306 GEN
Solar/Wind Harmer
3.063
942221AE2-234 GEN
Solar/Wind Harmer
0.032
970321AG2-212 GEN
Solar/Wind Harmer
2.761
970611AG2-400 GEN
Solar/Wind Harmer
6.333
970627AG2-408 GEN
Solar/Wind Harmer
1.9
970235AG2-159 GEN
Solar/Wind Harmer
3.847
970235AG2-159 GEN
Solar/Wind Harmer
2.207
339221AD2-048_GEN
Solar/Wind Harmer
0.004
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
971199AH1-059 GEN
Solar/Wind Harmer
2.513
246938BC-WTG3
Solar/Wind Harmer
0.228
246937BC-WTG2
Solar/Wind Harmer
0.255
972043AH1-570 GEN
Solar/Wind Harmer
1.633
972045AH1-571 GEN
Solar/Wind Harmer
1.308
966841AG1-555 GEN
Solar/Wind Harmer
0.709
944971AF1-162 GEN
Solar/Wind Harmer
6.265
965681AG1-436 GEN
Solar/Wind Harmer
7.82
965791AG1-447 GEN
Solar/Wind Harmer
5.734
270216AD2-079_GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.412
270526AF1-158 GEN
Solar/Wind Harmer
0.008
24441505OLIV SLR
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
3.641
957891AF2-083 GEN
Solar/Wind Harmer
0.001
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
4.56
961051AF2-396 GEN
Solar/Wind Harmer
12.428
961051AF2-396 GEN
Solar/Wind Harmer
8.285
274770LINCOLN ;1U
Adder
7.514
274771LINCOLN ;2U
Adder
7.514
971125AH1-004 GEN
Solar/Wind Harmer
2.483
970107AG2-081 GEN
Solar/Wind Harmer
1.862
960161AF2-307 GEN
Solar/Wind Harmer
4.096
945391AF1-204 GEN
Solar/Wind Harmer
6.587
274888KELLY CRK;1U
Solar/Wind Harmer
0.364
274887GEN-1.85
Solar/Wind Harmer
0.163
276843GEN-1.7
Solar/Wind Harmer
0.2
958011AF2-095 GEN
Solar/Wind Harmer
8.915
970623AG2-406 GEN
Solar/Wind Harmer
1.132
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
241960AC2-195 GEN
Solar/Wind Harmer
0.005
958481AF2-142 GEN
Solar/Wind Harmer
9.231
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.833
971573AH1-285 GEN
Solar/Wind Harmer
1.146
958491AF2-143 GEN
Solar/Wind Harmer
9.212
274879MINONK ;1U
Solar/Wind Harmer
0.259
238175AF1-290_GEN
Solar/Wind Helper
0.126
238169AE2-226 GEN1
Solar/Wind Helper
0.582
238170AE2-226 GEN2
Solar/Wind Helper
0.582
235020AA1-095 C
Solar/Wind Helper
0.044
23777901MDS_W4-102
Solar/Wind Helper
0.146
238120AE2-309 GEN
Solar/Wind Helper
0.406
237034AC2-136 C
Solar/Wind Helper
0.189
237002AB1-128_GEN
Solar/Wind Helper
0.369
235063AE1-101 C2
Solar/Wind Helper
1.38
237001AB1-127_GEN
Solar/Wind Helper
0.368
23777801MSM_W1-116
Solar/Wind Helper
0.096
962691AG1-118 GEN
Solar/Wind Harmer
3.447
23559101PLEAS2
50/50
11.213
23684101S70BUS1
50/50
0.313
23562301OGROV1
50/50
2.427
24721705FLATG2
Adder
23.442
962761AG1-125 GEN
Solar/Wind Harmer
29.494
970149AG2-104 GEN
Solar/Wind Harmer
31.855
970155AG2-107 GEN
Solar/Wind Harmer
18.834
270510AE1-227 GEN1
Solar/Wind Harmer
1.907
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
970947AG2-589 GEN
Solar/Wind Harmer
0.239
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
927014AC1-188 GEN
Solar/Wind Harmer
0.004
270349AD2-093_GEN
Solar/Wind Harmer
0.005
270263AC1-001 GEN
Solar/Wind Harmer
0.698
24686105CER G3
Adder
8.253
24686505CER G6
Adder
8.242
270159DARBY CT4
Adder
8.691
24723205RIVRG3
Adder
18.473
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.011
970593AG2-378 GEN
Solar/Wind Harmer
1.53
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.657
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
25326309TAIT D
Adder
1.041
960071AF2-298 GEN
Solar/Wind Harmer
3.297
252507AC2-088 GEN
Solar/Wind Harmer
0.3
270223U2-072_GEN1
Solar/Wind Harmer
0.001
25194608D.CRK4
Adder
1.55
25196808ZIMRHP
Adder
71.347
270462AD2-086
Solar/Wind Harmer
0.014
25196008MFTGT1
Adder
1.296
970333AG2-219 GEN
Solar/Wind Harmer
4.624
945681AF1-233 GEN
Solar/Wind Harmer
12.186
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.707
247536S-71 GEN
Solar/Wind Harmer
0.258
965651AG1-433 GEN
Solar/Wind Harmer
1.879
958861AF2-177 GEN
Solar/Wind Harmer
2.776
945371AF1-202 GEN
Solar/Wind Harmer
0.001
971995AH1-542 GEN
Solar/Wind Harmer
2.347
970773AG2-487 GEN
Solar/Wind Harmer
1.131
270005AE1-210 C O1
Solar/Wind Harmer
1.387
965031AG1-367 GEN
Solar/Wind Harmer
6.4
970825AG2-519 GEN
Solar/Wind Harmer
2.27
970091AG2-072 GEN
Adder
70.193
270032AE2-172
Solar/Wind Harmer
4.254
970291AG2-192 GEN
Solar/Wind Harmer
0.829
970245AG2-165 GEN
Solar/Wind Harmer
2.761
276903AD2-071 C
Solar/Wind Harmer
7.113
965011AG1-365 GEN
Solar/Wind Harmer
6.333
247521TR3_G114
Solar/Wind Harmer
0.23
270246TR4_N_V150
Solar/Wind Harmer
0.041
24728605AND G2
Adder
3.466
339216AC1-074 GEN
Solar/Wind Harmer
0.172
965421AG1-410 GEN
Solar/Wind Harmer
18.858
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
7.853
246936BC-WTG1
Solar/Wind Harmer
0.255
24791305MDL-5G
Solar/Wind Harmer
0.001
270489AE1-102 GEN1
Solar/Wind Harmer
0.817
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.162
24695305TIMB G C
Solar/Wind Harmer
0.002
270055AF2-134 C O1
Solar/Wind Harmer
0.005
970373AG2-245 GEN
Solar/Wind Harmer
13.169
270063AE2-323 C
Solar/Wind Harmer
0.005
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.002
24639705ELKHART HY
Adder
0.137
963741AG1-226 GEN
Solar/Wind Harmer
14.772
945111AF1-176 GEN
Solar/Wind Harmer
11.105
270505AE1-170 C O1
Solar/Wind Harmer
6.535
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
274773LINCOLN ;4U
Adder
7.514
274774LINCOLN ;5U
Adder
7.514
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.241
274751CRETE EC ;1U
Adder
7.332
274754CRETE EC ;4U
Adder
7.332
274723RIVER EC ;12
Adder
15.938
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.45
276776AD2-060 GEN
Solar/Wind Harmer
0.646
941551AE2-152 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
4.613
276691AA1-018 GEN1
Solar/Wind Harmer
0.745
276901AD2-066 C O1
Solar/Wind Harmer
0.006
944231AF1-091 GEN
Solar/Wind Harmer
1.635
971997AH1-543 GEN
Solar/Wind Harmer
3.22
23583801GRNGAP
Solar/Wind Helper
4.858
316095T157 G97
Solar/Wind Helper
1.299
238147AE2-230_GEN1
Solar/Wind Helper
0.415
238149AF1-291A_GEN
Solar/Wind Helper
0.119
238108AE1-109 GEN1
Solar/Wind Helper
0.088
237061AD1-155 GEN
Solar/Wind Helper
0.045
238185AF2-356 C
Solar/Wind Helper
1.996
238221AF1-254 C O1
Solar/Wind Helper
0.228
235067AD1-061 GEN
Solar/Wind Helper
0.412
235531U2-073 GEN
Solar/Wind Helper
2.523
238117U2-030
Solar/Wind Helper
0.26
962771AG1-126 GEN
Solar/Wind Harmer
29.494
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0.006
970879AG2-548 GEN
Solar/Wind Harmer
6.304
940611AE2-048 GEN
Solar/Wind Harmer
17.215
941391AE2-136 GEN
Solar/Wind Harmer
9.698
270520AE2-214 GEN
Solar/Wind Harmer
0.011
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.145
972203AH1-686 GEN
Adder
2.298
270432AC2-029 GEN
Solar/Wind Harmer
3.085
970689AG2-444 GEN
Solar/Wind Harmer
14.206
270269AC2-059
Solar/Wind Harmer
0.004
270156DARBY CT1
Adder
8.832
270157DARBY CT2
Adder
8.81
270158DARBY CT3
Adder
8.67
945631AF1-228 GEN
Solar/Wind Harmer
0
270284AF1-227 GEN1
Solar/Wind Harmer
0.009
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
971985AH1-537 GEN
Solar/Wind Harmer
2.037
253383AE2-342_GEN
Solar/Wind Harmer
0.002
241973AD2-163_GEN1
Solar/Wind Harmer
0.005
943861AF1-054 GEN
Solar/Wind Harmer
2.627
943851AF1-053 GEN
Solar/Wind Harmer
1.82
270340AC2-060 GEN
Solar/Wind Harmer
0.008
24477305BRIDGE
Adder
0.338
241972AD1-140 GEN
Solar/Wind Harmer
0.734
270367AC2-061_GEN
Solar/Wind Harmer
0.005
253372AE2-315 SEC3
Adder
1.803
253372AE2-315 SEC3
Adder
1.803
25306009OHH W.
Adder
2.735
270578AF1-285 GEN2
Solar/Wind Harmer
0.44
253349AC2-067 GEN
Solar/Wind Harmer
2.077
253400AC2-068 GEN
Solar/Wind Harmer
0.835
252524AE2-267 GEN
Solar/Wind Harmer
0.002
25196408WSDLE3
Adder
8.32
25196308WSDLE2
Adder
8.248
25196208WSDLE1
Adder
8.227
25196708WSDLE6
Adder
8.207
25196508WSDLE4
Adder
8
270302AB2-170 GEN
Solar/Wind Harmer
0.004
270317AD1-130_GEN
Solar/Wind Harmer
0.009
971653AH1-327 GEN
Solar/Wind Harmer
0.917
25196108MFTGT2
Adder
1.429
25196108MFTGT2
Adder
1.327
972163AH1-664 GEN
Solar/Wind Harmer
7.187
972165AH1-665 GEN
Solar/Wind Harmer
5.756
971673AH1-337 GEN
Solar/Wind Harmer
4.191
971029AG2-637 GEN
Solar/Wind Harmer
9.664
270543AE2-219 C
Solar/Wind Harmer
0.004
270240V3-007_GEN2
Solar/Wind Harmer
0.002
24729505KEY G4
Adder
5.961
965101AG1-375 GEN
Solar/Wind Harmer
6.406
945581AF1-223 GEN
Solar/Wind Harmer
0
970115AG2-085 GEN
Solar/Wind Harmer
2.556
971609AH1-304 GEN
Solar/Wind Harmer
1.043
270024AE2-089 GEN
Solar/Wind Harmer
0.007
270594AE1-207 GEN
Solar/Wind Harmer
7.147
270071AF1-092 GEN
Solar/Wind Harmer
12.224
970289AG2-191 GEN
Solar/Wind Harmer
1.211
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
8.573
965051AG1-369 GEN
Solar/Wind Harmer
3.147
971347AH1-153 GEN
Solar/Wind Harmer
9.454
965041AG1-368 GEN
Solar/Wind Harmer
6.297
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
3.74
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.796
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.008
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
963841AG1-237 GEN
Solar/Wind Harmer
2.71
971771AH1-392 GEN
Solar/Wind Harmer
6.248
971769AH1-391 GEN
Solar/Wind Harmer
6.974
247607V1-011 GEN
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
2.801
274775LINCOLN ;6U
Adder
7.514
274776LINCOLN ;7U
Adder
7.514
274777LINCOLN ;8U
Adder
7.514
274814UNIV PK N;0U
Adder
4.489
274807UNIV PK N;3U
Adder
4.479
274805UNIV PK N;1U
Adder
4.459
274811UNIV PK N;7U
Adder
0.697
960591AF2-350 GEN
Solar/Wind Harmer
6.191
270399AC1-101 GEN
Solar/Wind Harmer
1.957
270400AC1-102 GEN
Solar/Wind Harmer
1.957
970833AG2-524 GEN
Solar/Wind Harmer
6.792
970833AG2-524 GEN
Solar/Wind Harmer
4.528
970179AG2-119 GEN
Solar/Wind Harmer
5.506
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
970169AG2-114 GEN
Solar/Wind Harmer
6.145
276868AE1-113 GEN
Solar/Wind Harmer
1.231
276882AE2-255 GEN
Solar/Wind Harmer
0.717
238152AF2-075_GEN
Solar/Wind Helper
0.593
23546401DTGZ2-030
Solar/Wind Helper
0.075
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
238208AF1-136 C
Solar/Wind Helper
0.18
237085AD2-009_GEN
Solar/Wind Helper
1.367
238126S14_GEN_1
Solar/Wind Helper
0.641
944201AF1-088_MTX
Adder
103.64
957141AF2-008_MTX
Adder
51.82
LAGNLTFEXP_LAGN->PJM
CLTF
13.832
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.925
TVALTFEXP_TVA->PJM
CLTF
6.876
CPLELTFEXP_CPLE->PJM
CLTF
1.286
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.798
NYPJM->LTFIMP_NY
CLTF
4.417
LGEELTFEXP_LGEE->PJM
CLTF
6.111
WECLTFEXP_WEC->PJM
CLTF
3.336
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.614
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.188
MECLTFEXP_MEC->PJM
CLTF
14.066
SIGELTFEXP_SIGE->PJM
CLTF
0.455

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P2-2_MP-500-007_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_MP-500-007_SRT-SL
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:105.4 %
Rating:2811.0 MVA
Rating Type:B
MVA to Mitigate:2962.75
MW Contribution:1251.46
Bus #Bus NameTypeMW Contribution
23559001PLEAS1
50/50
10.469
23684201S70BUS2
50/50
0.295
23562401OGROV2
50/50
2.224
24289405MTG1
50/50
4.043
23534401HANNIB
50/50
0.115
24721905FLATG4
Adder
17.806
970935AG2-582 GEN
50/50
1251.459
243186AF1-051 GEN
50/50
4.545
23559101PLEAS2
50/50
10.469
23684101S70BUS1
50/50
0.29
23562301OGROV1
50/50
2.238
237068AA2-119 GEN
50/50
10.106
24289405MTG1
50/50
4.043
243186AF1-051 GEN
50/50
4.545
24721705FLATG2
Adder
17.806
LAGNLTFEXP_LAGN->PJM
CLTF
10.234
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.227
TVALTFEXP_TVA->PJM
CLTF
5.116
CPLELTFEXP_CPLE->PJM
CLTF
1.219
CBM West 2LTFEXP_CBM-W2->PJM
CBM
75.163
NYPJM->LTFIMP_NY
CLTF
3.243
LGEELTFEXP_LGEE->PJM
CLTF
4.454
WECLTFEXP_WEC->PJM
CLTF
2.382
AG2-052LTFEXP_AG2-052->PJM
LTF
0.148
AH1-155LTFEXP_AH1-155->PJM
LTF
0.222
CBM West 1LTFEXP_CBM-W1->PJM
CBM
86.671
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.137
MECLTFEXP_MEC->PJM
CLTF
10.123
SIGELTFEXP_SIGE->PJM
CLTF
0.33

Details for 01GLENFL-01BRIDGP 138.0 kV Ckt 1 line l/o AP_P2-3_MP-500-012_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01GLENFL-01BRIDGP 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-012_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.05 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:319.06
MW Contribution:82.7
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
Adder
82.703
237068AA2-119 GEN
50/50
18.76
LAGNLTFEXP_LAGN->PJM
CLTF
0.877
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.419
TVALTFEXP_TVA->PJM
CLTF
0.437
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.635
NYPJM->LTFIMP_NY
CLTF
0.335
LGEELTFEXP_LGEE->PJM
CLTF
0.404
WECLTFEXP_WEC->PJM
CLTF
0.218
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.11
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.744
MECLTFEXP_MEC->PJM
CLTF
0.917
SIGELTFEXP_SIGE->PJM
CLTF
0.03

Details for 01GLENFL-01BRIDGP 138.0 kV Ckt 1 line l/o AP_P1-2_MP-500-008A_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01GLENFL-01BRIDGP 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:117.56 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:315.05
MW Contribution:82.91
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
Adder
82.907
237068AA2-119 GEN
50/50
18.89
LAGNLTFEXP_LAGN->PJM
CLTF
0.86
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.494
TVALTFEXP_TVA->PJM
CLTF
0.43
CPLELTFEXP_CPLE->PJM
CLTF
0.04
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.409
NYPJM->LTFIMP_NY
CLTF
0.34
LGEELTFEXP_LGEE->PJM
CLTF
0.387
WECLTFEXP_WEC->PJM
CLTF
0.206
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.523
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.706
MECLTFEXP_MEC->PJM
CLTF
0.872
SIGELTFEXP_SIGE->PJM
CLTF
0.029

Details for 01GLENFL-01BRIDGP 138.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT4_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01GLENFL-01BRIDGP 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT4_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.55 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:315.03
MW Contribution:82.91
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
Adder
82.907
237068AA2-119 GEN
50/50
18.89
LAGNLTFEXP_LAGN->PJM
CLTF
0.86
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.494
TVALTFEXP_TVA->PJM
CLTF
0.43
CPLELTFEXP_CPLE->PJM
CLTF
0.04
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.409
NYPJM->LTFIMP_NY
CLTF
0.34
LGEELTFEXP_LGEE->PJM
CLTF
0.387
WECLTFEXP_WEC->PJM
CLTF
0.206
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.523
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.706
MECLTFEXP_MEC->PJM
CLTF
0.872
SIGELTFEXP_SIGE->PJM
CLTF
0.029

Details for 01GLENFL-01BRIDGP 138.0 kV Ckt 1 line l/o AP_P2-3_MP-500-018_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01GLENFL-01BRIDGP 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-018_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.55 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:315.03
MW Contribution:82.91
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
Adder
82.907
237068AA2-119 GEN
50/50
18.89
LAGNLTFEXP_LAGN->PJM
CLTF
0.86
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.494
TVALTFEXP_TVA->PJM
CLTF
0.43
CPLELTFEXP_CPLE->PJM
CLTF
0.04
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.409
NYPJM->LTFIMP_NY
CLTF
0.34
LGEELTFEXP_LGEE->PJM
CLTF
0.387
WECLTFEXP_WEC->PJM
CLTF
0.206
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.523
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.706
MECLTFEXP_MEC->PJM
CLTF
0.872
SIGELTFEXP_SIGE->PJM
CLTF
0.029

Details for 01GLENFL-01BRIDGP 138.0 kV Ckt 1 line l/o AP_P2-3_MP-500-017_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01GLENFL-01BRIDGP 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-017_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.37 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:285.08
MW Contribution:71.47
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
Adder
71.472
237068AA2-119 GEN
50/50
19.547
LAGNLTFEXP_LAGN->PJM
CLTF
0.783
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.443
TVALTFEXP_TVA->PJM
CLTF
0.392
CPLELTFEXP_CPLE->PJM
CLTF
0.032
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.84
NYPJM->LTFIMP_NY
CLTF
0.317
LGEELTFEXP_LGEE->PJM
CLTF
0.353
WECLTFEXP_WEC->PJM
CLTF
0.188
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.85
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.555
MECLTFEXP_MEC->PJM
CLTF
0.794
SIGELTFEXP_SIGE->PJM
CLTF
0.026

Details for 01GLENFL-01BRIDGP 138.0 kV Ckt 1 line l/o AP_P2-3_MP-500-016_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01GLENFL-01BRIDGP 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-016_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.37 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:285.08
MW Contribution:71.47
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
Adder
71.472
237068AA2-119 GEN
50/50
19.547
LAGNLTFEXP_LAGN->PJM
CLTF
0.783
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.443
TVALTFEXP_TVA->PJM
CLTF
0.392
CPLELTFEXP_CPLE->PJM
CLTF
0.032
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.84
NYPJM->LTFIMP_NY
CLTF
0.317
LGEELTFEXP_LGEE->PJM
CLTF
0.353
WECLTFEXP_WEC->PJM
CLTF
0.188
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.85
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.555
MECLTFEXP_MEC->PJM
CLTF
0.794
SIGELTFEXP_SIGE->PJM
CLTF
0.026

Details for 01GLENFL-01BRIDGP 138.0 kV Ckt 1 line l/o AP_P2-2_MP-138-013_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01GLENFL-01BRIDGP 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_MP-138-013_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:102.26 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:274.05
MW Contribution:27.69
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
Adder
27.692
237068AA2-119 GEN
50/50
29.766
LAGNLTFEXP_LAGN->PJM
CLTF
0.332
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.092
TVALTFEXP_TVA->PJM
CLTF
0.167
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.554
NYPJM->LTFIMP_NY
CLTF
0.219
LGEELTFEXP_LGEE->PJM
CLTF
0.161
WECLTFEXP_WEC->PJM
CLTF
0.084
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.003
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.064
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.672
MECLTFEXP_MEC->PJM
CLTF
0.354
SIGELTFEXP_SIGE->PJM
CLTF
0.012

Details for 01GLENFL-01MCALPN 138.0 kV Ckt 1 line l/o AP_P2-3_MP-500-012_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01GLENFL-01MCALPN 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-012_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.99 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:308.18
MW Contribution:76.6
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
Adder
76.601
237068AA2-119 GEN
50/50
17.689
LAGNLTFEXP_LAGN->PJM
CLTF
0.794
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.436
TVALTFEXP_TVA->PJM
CLTF
0.397
CPLELTFEXP_CPLE->PJM
CLTF
0.028
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.939
NYPJM->LTFIMP_NY
CLTF
0.309
LGEELTFEXP_LGEE->PJM
CLTF
0.359
WECLTFEXP_WEC->PJM
CLTF
0.192
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.096
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.574
MECLTFEXP_MEC->PJM
CLTF
0.812
SIGELTFEXP_SIGE->PJM
CLTF
0.027

Details for 01GLENFL-01MCALPN 138.0 kV Ckt 1 line l/o AP_P1-2_MP-500-008A_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01GLENFL-01MCALPN 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.89 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:305.22
MW Contribution:76.75
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
Adder
76.753
237068AA2-119 GEN
50/50
17.786
LAGNLTFEXP_LAGN->PJM
CLTF
0.781
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.493
TVALTFEXP_TVA->PJM
CLTF
0.391
CPLELTFEXP_CPLE->PJM
CLTF
0.058
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.771
NYPJM->LTFIMP_NY
CLTF
0.312
LGEELTFEXP_LGEE->PJM
CLTF
0.346
WECLTFEXP_WEC->PJM
CLTF
0.183
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.66
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.546
MECLTFEXP_MEC->PJM
CLTF
0.779
SIGELTFEXP_SIGE->PJM
CLTF
0.026

Details for 01GLENFL-01MCALPN 138.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT4_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01GLENFL-01MCALPN 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT4_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.88 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:305.2
MW Contribution:76.75
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
Adder
76.753
237068AA2-119 GEN
50/50
17.786
LAGNLTFEXP_LAGN->PJM
CLTF
0.781
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.493
TVALTFEXP_TVA->PJM
CLTF
0.391
CPLELTFEXP_CPLE->PJM
CLTF
0.058
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.771
NYPJM->LTFIMP_NY
CLTF
0.312
LGEELTFEXP_LGEE->PJM
CLTF
0.346
WECLTFEXP_WEC->PJM
CLTF
0.183
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.66
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.546
MECLTFEXP_MEC->PJM
CLTF
0.779
SIGELTFEXP_SIGE->PJM
CLTF
0.026

Details for 01GLENFL-01MCALPN 138.0 kV Ckt 1 line l/o AP_P2-3_MP-500-018_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01GLENFL-01MCALPN 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-018_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.88 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:305.2
MW Contribution:76.75
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
Adder
76.753
237068AA2-119 GEN
50/50
17.786
LAGNLTFEXP_LAGN->PJM
CLTF
0.781
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.493
TVALTFEXP_TVA->PJM
CLTF
0.391
CPLELTFEXP_CPLE->PJM
CLTF
0.058
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.771
NYPJM->LTFIMP_NY
CLTF
0.312
LGEELTFEXP_LGEE->PJM
CLTF
0.346
WECLTFEXP_WEC->PJM
CLTF
0.183
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.66
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.546
MECLTFEXP_MEC->PJM
CLTF
0.779
SIGELTFEXP_SIGE->PJM
CLTF
0.026

Details for 01GLENFL-01MCALPN 138.0 kV Ckt 1 line l/o AP_P2-3_MP-500-017_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01GLENFL-01MCALPN 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-017_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.22 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:276.63
MW Contribution:65.82
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
Adder
65.819
237068AA2-119 GEN
50/50
18.414
LAGNLTFEXP_LAGN->PJM
CLTF
0.707
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.443
TVALTFEXP_TVA->PJM
CLTF
0.355
CPLELTFEXP_CPLE->PJM
CLTF
0.05
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.227
NYPJM->LTFIMP_NY
CLTF
0.29
LGEELTFEXP_LGEE->PJM
CLTF
0.314
WECLTFEXP_WEC->PJM
CLTF
0.166
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.016
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.402
MECLTFEXP_MEC->PJM
CLTF
0.705
SIGELTFEXP_SIGE->PJM
CLTF
0.023

Details for 01GLENFL-01MCALPN 138.0 kV Ckt 1 line l/o AP_P2-3_MP-500-016_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01GLENFL-01MCALPN 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-016_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.22 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:276.63
MW Contribution:65.82
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
Adder
65.819
237068AA2-119 GEN
50/50
18.414
LAGNLTFEXP_LAGN->PJM
CLTF
0.707
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.443
TVALTFEXP_TVA->PJM
CLTF
0.355
CPLELTFEXP_CPLE->PJM
CLTF
0.05
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.227
NYPJM->LTFIMP_NY
CLTF
0.29
LGEELTFEXP_LGEE->PJM
CLTF
0.314
WECLTFEXP_WEC->PJM
CLTF
0.166
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.016
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.402
MECLTFEXP_MEC->PJM
CLTF
0.705
SIGELTFEXP_SIGE->PJM
CLTF
0.023

Details for 01HARRSN-01PRNTY 500.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT6_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01HARRSN-01PRNTY 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT6_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.19 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:3950.77
MW Contribution:814.67
Bus #Bus NameTypeMW Contribution
23558501HARRN1
50/50
18.438
23559001PLEAS1
50/50
7.018
23684201S70BUS2
50/50
0.198
316097T157 G90
Solar/Wind Helper
1.645
238148AE2-230_GEN2
Solar/Wind Helper
0.498
23750701CROSSCHOOL
Solar/Wind Helper
1.319
964991AG1-363 GEN
Solar/Wind Helper
3.934
238118U2-030_1
Solar/Wind Helper
0.306
238127S14_GEN_2
Solar/Wind Helper
0.739
316006AB2-029 C
Solar/Wind Helper
0.113
237080AD1-060 GEN
Solar/Wind Helper
0.284
316045AC1-158 PL2
Solar/Wind Helper
4.07
316254AC1-120 GEN1
Solar/Wind Helper
1.051
237038AE2-054 C
Solar/Wind Helper
0.225
235062AE1-101 C1
Solar/Wind Helper
1.363
972001AH1-545 GEN
Solar/Wind Harmer
19.946
972229AH1-699 GEN
Adder
6.976
238152AF2-075_GEN
Solar/Wind Helper
0.709
23546401DTGZ2-030
Solar/Wind Helper
0.09
238109AE1-109 GEN2
Solar/Wind Helper
0.102
238110AE1-109 GEN3
Solar/Wind Helper
0.102
238126S14_GEN_1
Solar/Wind Helper
0.739
316411AF1-147_GEN1
Solar/Wind Helper
0.814
316415AF1-147_GEN2
Solar/Wind Helper
0.814
3138216PACIFIC
Solar/Wind Helper
0.04
238208AF1-136 C
Solar/Wind Helper
0.185
237085AD2-009_GEN
Solar/Wind Helper
1.363
316164AC1-076 GEN
Solar/Wind Helper
1.086
3141426STAFORD
Solar/Wind Helper
0.05
23558601HARRN2
50/50
18.438
23558701HARRN3
50/50
18.438
970935AG2-582 GEN
50/50
814.67
23909002SAMMG6
Adder
26.274
23908902SAMMG5
Adder
21.019
23585401KL_K28_T16
Solar/Wind Helper
1.427
238169AE2-226 GEN1
Solar/Wind Helper
0.648
238170AE2-226 GEN2
Solar/Wind Helper
0.648
238120AE2-309 GEN
Solar/Wind Helper
0.47
238175AF1-290_GEN
Solar/Wind Helper
0.137
3132123MT JACKSON
Solar/Wind Helper
0.749
235020AA1-095 C
Solar/Wind Helper
0.044
23777901MDS_W4-102
Solar/Wind Helper
0.149
315651AD1-115 GEN
Solar/Wind Helper
0.774
316447AC1-158 HLD
Solar/Wind Helper
2.799
237034AC2-136 C
Solar/Wind Helper
0.189
237002AB1-128_GEN
Solar/Wind Helper
0.365
235063AE1-101 C2
Solar/Wind Helper
1.363
237001AB1-127_GEN
Solar/Wind Helper
0.363
226929AD2-058 GEN
Solar/Wind Helper
0.087
23559101PLEAS2
50/50
7.018
23684101S70BUS1
50/50
0.194
23909102SAMMG7
Adder
26.274
241859AE2-194_GEN
Solar/Wind Harmer
13.418
23583801GRNGAP
Solar/Wind Helper
6.238
316095T157 G97
Solar/Wind Helper
1.645
23751101LEADS_P59
Solar/Wind Helper
1.587
238147AE2-230_GEN1
Solar/Wind Helper
0.496
238149AF1-291A_GEN
Solar/Wind Helper
0.142
237061AD1-155 GEN
Solar/Wind Helper
0.054
23751201ROTHROCK
Solar/Wind Helper
0.825
235054AD2-180 GEN
Solar/Wind Helper
1.912
23562501BACKB
Solar/Wind Helper
1.009
238185AF2-356 C
Solar/Wind Helper
2.412
238108AE1-109 GEN1
Solar/Wind Helper
0.102
235531U2-073 GEN
Solar/Wind Helper
2.932
238117U2-030
Solar/Wind Helper
0.306
3141196NOKESVL
Solar/Wind Helper
0.971
238221AF1-254 C O1
Solar/Wind Helper
0.228
316044AC1-158 PL1
Solar/Wind Helper
1.272
316450AC1-158 RIC
Solar/Wind Helper
0.339
316170AC1-121 GEN2
Solar/Wind Helper
0.35
235067AD1-061 GEN
Solar/Wind Helper
0.41
LAGNLTFEXP_LAGN->PJM
CLTF
6.222
TVALTFEXP_TVA->PJM
CLTF
3.017
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.962
NYPJM->LTFIMP_NY
CLTF
2.516
LGEELTFEXP_LGEE->PJM
CLTF
3.38
WECLTFEXP_WEC->PJM
CLTF
1.942
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.848
AG2-052LTFEXP_AG2-052->PJM
LTF
0.124
AH1-155LTFEXP_AH1-155->PJM
LTF
0.185
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.069
CBM West 1LTFEXP_CBM-W1->PJM
CBM
76.715
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.619
MECLTFEXP_MEC->PJM
CLTF
7.849
SIGELTFEXP_SIGE->PJM
CLTF
0.25

Details for 01HARRSN-01PRNTY 500.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT9_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01HARRSN-01PRNTY 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT9_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.01 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:3943.9
MW Contribution:815.91
Bus #Bus NameTypeMW Contribution
23558501HARRN1
50/50
18.452
23559001PLEAS1
50/50
7.034
23684201S70BUS2
50/50
0.199
316097T157 G90
Solar/Wind Helper
1.653
238148AE2-230_GEN2
Solar/Wind Helper
0.5
23750701CROSSCHOOL
Solar/Wind Helper
1.298
964991AG1-363 GEN
Solar/Wind Helper
3.954
238127S14_GEN_2
Solar/Wind Helper
0.724
238118U2-030_1
Solar/Wind Helper
0.296
316006AB2-029 C
Solar/Wind Helper
0.114
237080AD1-060 GEN
Solar/Wind Helper
0.284
316045AC1-158 PL2
Solar/Wind Helper
4.092
316254AC1-120 GEN1
Solar/Wind Helper
1.056
237038AE2-054 C
Solar/Wind Helper
0.226
235062AE1-101 C1
Solar/Wind Helper
1.366
3147983MERCK5
Solar/Wind Helper
0.089
972001AH1-545 GEN
Solar/Wind Harmer
20.073
972229AH1-699 GEN
Adder
7.026
238152AF2-075_GEN
Solar/Wind Helper
0.712
23546401DTGZ2-030
Solar/Wind Helper
0.09
238109AE1-109 GEN2
Solar/Wind Helper
0.101
238110AE1-109 GEN3
Solar/Wind Helper
0.101
238126S14_GEN_1
Solar/Wind Helper
0.724
316411AF1-147_GEN1
Solar/Wind Helper
0.819
316415AF1-147_GEN2
Solar/Wind Helper
0.819
3138216PACIFIC
Solar/Wind Helper
0.041
238208AF1-136 C
Solar/Wind Helper
0.185
316164AC1-076 GEN
Solar/Wind Helper
1.092
237085AD2-009_GEN
Solar/Wind Helper
1.365
3141426STAFORD
Solar/Wind Helper
0.05
23558601HARRN2
50/50
18.452
23558701HARRN3
50/50
18.452
970935AG2-582 GEN
50/50
815.909
23909002SAMMG6
Adder
26.452
23908902SAMMG5
Adder
21.162
23585401KL_K28_T16
Solar/Wind Helper
1.384
238169AE2-226 GEN1
Solar/Wind Helper
0.651
238170AE2-226 GEN2
Solar/Wind Helper
0.651
238175AF1-290_GEN
Solar/Wind Helper
0.138
238120AE2-309 GEN
Solar/Wind Helper
0.461
3132123MT JACKSON
Solar/Wind Helper
0.753
235020AA1-095 C
Solar/Wind Helper
0.045
23777901MDS_W4-102
Solar/Wind Helper
0.149
315651AD1-115 GEN
Solar/Wind Helper
0.779
316447AC1-158 HLD
Solar/Wind Helper
2.814
237034AC2-136 C
Solar/Wind Helper
0.19
237002AB1-128_GEN
Solar/Wind Helper
0.366
235063AE1-101 C2
Solar/Wind Helper
1.366
237001AB1-127_GEN
Solar/Wind Helper
0.364
226929AD2-058 GEN
Solar/Wind Helper
0.087
23559101PLEAS2
50/50
7.034
23684101S70BUS1
50/50
0.195
23909102SAMMG7
Adder
26.452
241859AE2-194_GEN
Solar/Wind Harmer
13.505
23583801GRNGAP
Solar/Wind Helper
6.269
316095T157 G97
Solar/Wind Helper
1.653
23751101LEADS_P59
Solar/Wind Helper
1.548
238147AE2-230_GEN1
Solar/Wind Helper
0.498
238149AF1-291A_GEN
Solar/Wind Helper
0.142
237061AD1-155 GEN
Solar/Wind Helper
0.055
235054AD2-180 GEN
Solar/Wind Helper
1.864
238185AF2-356 C
Solar/Wind Helper
2.359
23751201ROTHROCK
Solar/Wind Helper
0.798
23562501BACKB
Solar/Wind Helper
0.976
238108AE1-109 GEN1
Solar/Wind Helper
0.101
235531U2-073 GEN
Solar/Wind Helper
2.855
238117U2-030
Solar/Wind Helper
0.296
3141196NOKESVL
Solar/Wind Helper
0.976
238221AF1-254 C O1
Solar/Wind Helper
0.229
316044AC1-158 PL1
Solar/Wind Helper
1.278
316450AC1-158 RIC
Solar/Wind Helper
0.341
316170AC1-121 GEN2
Solar/Wind Helper
0.352
235067AD1-061 GEN
Solar/Wind Helper
0.411
3132273ORANGE
Solar/Wind Helper
0.045
227287AC2-120 GEN
Solar/Wind Helper
0.302
LAGNLTFEXP_LAGN->PJM
CLTF
6.227
TVALTFEXP_TVA->PJM
CLTF
3.019
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.04
NYPJM->LTFIMP_NY
CLTF
2.514
LGEELTFEXP_LGEE->PJM
CLTF
3.387
WECLTFEXP_WEC->PJM
CLTF
1.946
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.858
AG2-052LTFEXP_AG2-052->PJM
LTF
0.124
AH1-155LTFEXP_AH1-155->PJM
LTF
0.186
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.073
CBM West 1LTFEXP_CBM-W1->PJM
CBM
76.913
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.633
MECLTFEXP_MEC->PJM
CLTF
7.864
SIGELTFEXP_SIGE->PJM
CLTF
0.251

Details for 01HARRSN-01PRNTY 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-022_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01HARRSN-01PRNTY 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-022_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.61 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:3929.01
MW Contribution:814.67
Bus #Bus NameTypeMW Contribution
23558501HARRN1
50/50
18.438
23559001PLEAS1
50/50
7.018
23684201S70BUS2
50/50
0.198
316097T157 G90
Solar/Wind Helper
1.645
238148AE2-230_GEN2
Solar/Wind Helper
0.498
23750701CROSSCHOOL
Solar/Wind Helper
1.319
964991AG1-363 GEN
Solar/Wind Helper
3.934
238118U2-030_1
Solar/Wind Helper
0.306
238127S14_GEN_2
Solar/Wind Helper
0.739
23558601HARRN2
50/50
18.438
23558701HARRN3
50/50
18.438
970935AG2-582 GEN
50/50
814.67
23909002SAMMG6
Adder
26.274
23908902SAMMG5
Adder
21.019
23585401KL_K28_T16
Solar/Wind Helper
1.427
238169AE2-226 GEN1
Solar/Wind Helper
0.648
238170AE2-226 GEN2
Solar/Wind Helper
0.648
238120AE2-309 GEN
Solar/Wind Helper
0.47
238175AF1-290_GEN
Solar/Wind Helper
0.137
3132123MT JACKSON
Solar/Wind Helper
0.749
235020AA1-095 C
Solar/Wind Helper
0.044
23777901MDS_W4-102
Solar/Wind Helper
0.149
315651AD1-115 GEN
Solar/Wind Helper
0.774
316447AC1-158 HLD
Solar/Wind Helper
2.799
237034AC2-136 C
Solar/Wind Helper
0.189
237002AB1-128_GEN
Solar/Wind Helper
0.365
235063AE1-101 C2
Solar/Wind Helper
1.363
237001AB1-127_GEN
Solar/Wind Helper
0.363
226929AD2-058 GEN
Solar/Wind Helper
0.087
972001AH1-545 GEN
Solar/Wind Harmer
2.319
972229AH1-699 GEN
Adder
6.976
238152AF2-075_GEN
Solar/Wind Helper
0.709
23546401DTGZ2-030
Solar/Wind Helper
0.09
238109AE1-109 GEN2
Solar/Wind Helper
0.102
238110AE1-109 GEN3
Solar/Wind Helper
0.102
238126S14_GEN_1
Solar/Wind Helper
0.739
316411AF1-147_GEN1
Solar/Wind Helper
0.814
316415AF1-147_GEN2
Solar/Wind Helper
0.814
3138216PACIFIC
Solar/Wind Helper
0.04
238208AF1-136 C
Solar/Wind Helper
0.185
237085AD2-009_GEN
Solar/Wind Helper
1.363
316164AC1-076 GEN
Solar/Wind Helper
1.086
3141426STAFORD
Solar/Wind Helper
0.05
23559101PLEAS2
50/50
7.018
23684101S70BUS1
50/50
0.194
23909102SAMMG7
Adder
26.274
241859AE2-194_GEN
Solar/Wind Harmer
9.039
23583801GRNGAP
Solar/Wind Helper
6.238
316095T157 G97
Solar/Wind Helper
1.645
23751101LEADS_P59
Solar/Wind Helper
1.587
316006AB2-029 C
Solar/Wind Helper
0.113
237080AD1-060 GEN
Solar/Wind Helper
0.284
316045AC1-158 PL2
Solar/Wind Helper
4.07
316254AC1-120 GEN1
Solar/Wind Helper
1.051
237038AE2-054 C
Solar/Wind Helper
0.225
235062AE1-101 C1
Solar/Wind Helper
1.363
238147AE2-230_GEN1
Solar/Wind Helper
0.496
238149AF1-291A_GEN
Solar/Wind Helper
0.142
237061AD1-155 GEN
Solar/Wind Helper
0.054
23751201ROTHROCK
Solar/Wind Helper
0.825
235054AD2-180 GEN
Solar/Wind Helper
1.912
23562501BACKB
Solar/Wind Helper
1.009
238185AF2-356 C
Solar/Wind Helper
2.412
238108AE1-109 GEN1
Solar/Wind Helper
0.102
235531U2-073 GEN
Solar/Wind Helper
2.932
238117U2-030
Solar/Wind Helper
0.306
3141196NOKESVL
Solar/Wind Helper
0.971
238221AF1-254 C O1
Solar/Wind Helper
0.228
316044AC1-158 PL1
Solar/Wind Helper
1.272
316450AC1-158 RIC
Solar/Wind Helper
0.339
316170AC1-121 GEN2
Solar/Wind Helper
0.35
235067AD1-061 GEN
Solar/Wind Helper
0.41
LAGNLTFEXP_LAGN->PJM
CLTF
6.222
TVALTFEXP_TVA->PJM
CLTF
3.017
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.962
NYPJM->LTFIMP_NY
CLTF
2.516
LGEELTFEXP_LGEE->PJM
CLTF
3.38
WECLTFEXP_WEC->PJM
CLTF
1.942
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.848
AG2-052LTFEXP_AG2-052->PJM
LTF
0.124
AH1-155LTFEXP_AH1-155->PJM
LTF
0.185
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.069
CBM West 1LTFEXP_CBM-W1->PJM
CBM
76.715
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.619
MECLTFEXP_MEC->PJM
CLTF
7.849
SIGELTFEXP_SIGE->PJM
CLTF
0.25

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-012_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-012_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:130.23 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4856.26
MW Contribution:239.41
Bus #Bus NameTypeMW Contribution
972239AH1-704 GEN
50/50
3.102
962771AG1-126 GEN
Solar/Wind Harmer
40.965
270459AD2-067 GEN
Solar/Wind Harmer
10.453
961821AG1-024 GEN
Solar/Wind Harmer
10.613
270054AF2-122 C O1
Solar/Wind Harmer
4.071
270284AF1-227 GEN1
Solar/Wind Harmer
6.912
270286AF1-227 GEN2
Solar/Wind Harmer
2.557
270287AF1-227 GEN3
Solar/Wind Harmer
2.557
270520AE2-214 GEN
Solar/Wind Harmer
7.382
253383AE2-342_GEN
Solar/Wind Harmer
1.062
241973AD2-163_GEN1
Solar/Wind Harmer
2.37
940611AE2-048 GEN
Solar/Wind Harmer
26.074
941391AE2-136 GEN
Solar/Wind Harmer
13.511
270578AF1-285 GEN2
Solar/Wind Harmer
0.55
943861AF1-054 GEN
Solar/Wind Harmer
4.552
943851AF1-053 GEN
Solar/Wind Harmer
2.2
945631AF1-228 GEN
Solar/Wind Harmer
5.537
270156DARBY CT1
Adder
10.556
270157DARBY CT2
Adder
10.53
270158DARBY CT3
Adder
10.362
270302AB2-170 GEN
Solar/Wind Harmer
9.805
270317AD1-130_GEN
Solar/Wind Harmer
3.759
970689AG2-444 GEN
Solar/Wind Harmer
19.055
270432AC2-029 GEN
Solar/Wind Harmer
8.138
958581AF2-149 GEN
Solar/Wind Harmer
4.968
970179AG2-119 GEN
Solar/Wind Harmer
9.26
270269AC2-059
Solar/Wind Harmer
10.704
241972AD1-140 GEN
Solar/Wind Harmer
5.084
971567AH1-282 GEN
Solar/Wind Harmer
16.984
966831AG1-554 GEN
Solar/Wind Harmer
1.34
971989AH1-539 GEN
Solar/Wind Harmer
14.49
270340AC2-060 GEN
Solar/Wind Harmer
3.371
957201AF2-014 GEN
Solar/Wind Harmer
5.033
270435AC2-044 GEN
Solar/Wind Harmer
2.219
970879AG2-548 GEN
Solar/Wind Harmer
4.763
247607V1-011 GEN
Solar/Wind Harmer
4.359
253372AE2-315 SEC3
Adder
2.086
253372AE2-315 SEC3
Adder
2.086
965051AG1-369 GEN
Solar/Wind Harmer
5.494
25306009OHH W.
Adder
3.166
270297AD1-101 GEN
Solar/Wind Harmer
3.056
965041AG1-368 GEN
Solar/Wind Harmer
10.974
253349AC2-067 GEN
Solar/Wind Harmer
5.466
253400AC2-068 GEN
Solar/Wind Harmer
2.198
963791AG1-232 GEN
Solar/Wind Harmer
14.679
270071AF1-092 GEN
Solar/Wind Harmer
16.242
24729505KEY G4
Adder
7.02
945641AF1-229 GEN
Solar/Wind Harmer
3.923
270024AE2-089 GEN
Solar/Wind Harmer
5.065
958711AF2-162 GEN
Solar/Wind Harmer
1.089
965101AG1-375 GEN
Solar/Wind Harmer
10.752
961761AG1-017 GEN
Solar/Wind Harmer
0.46
270543AE2-219 C
Solar/Wind Harmer
5.494
971029AG2-637 GEN
Solar/Wind Harmer
16.089
971673AH1-337 GEN
Solar/Wind Harmer
4.934
25196408WSDLE3
Adder
9.412
25196308WSDLE2
Adder
9.33
25196208WSDLE1
Adder
9.306
25196708WSDLE6
Adder
9.283
25196508WSDLE4
Adder
9.049
25196108MFTGT2
Adder
1.608
25196108MFTGT2
Adder
1.494
274775LINCOLN ;6U
Adder
8.792
274776LINCOLN ;7U
Adder
8.792
274777LINCOLN ;8U
Adder
8.792
274814UNIV PK N;0U
Adder
5.256
274807UNIV PK N;3U
Adder
5.245
274805UNIV PK N;1U
Adder
5.222
274811UNIV PK N;7U
Adder
5.21
972037AH1-567 GEN1
Adder
0.19
274827FISK ;RP
Adder
8.047
972227AH1-698 GEN1
Adder
2.704
274687WILL CNTY;4U
Adder
28.893
274687WILL CNTY;4U
Adder
28.893
274675JOLIET 29;7U
Adder
31.706
274675JOLIET 29;7U
Adder
30.574
274731ELWOOD EC;2P
Adder
16.983
274733ELWOOD EC;3P
Adder
16.983
274735ELWOOD EC;4P
Adder
16.983
274728ELWOOD EC;5P
Adder
16.983
238109AE1-109 GEN2
Solar/Wind Helper
0.121
238110AE1-109 GEN3
Solar/Wind Helper
0.121
238152AF2-075_GEN
Solar/Wind Helper
0.789
23546401DTGZ2-030
Solar/Wind Helper
0.099
238126S14_GEN_1
Solar/Wind Helper
0.867
238208AF1-136 C
Solar/Wind Helper
0.236
237085AD2-009_GEN
Solar/Wind Helper
1.767
3138216PACIFIC
Solar/Wind Helper
0.049
316411AF1-147_GEN1
Solar/Wind Helper
0.978
316415AF1-147_GEN2
Solar/Wind Helper
0.978
3141426STAFORD
Solar/Wind Helper
0.058
316164AC1-076 GEN
Solar/Wind Helper
1.225
23750501ELLIOTTS
Solar/Wind Helper
0.629
959381AF2-229 GEN
Solar/Wind Helper
0.367
960921AF2-383 GEN
Solar/Wind Helper
0.185
205943AE1-185 GEN
Solar/Wind Helper
0.518
205932AD2-116_GEN
Solar/Wind Helper
0.518
205956AE1-196_GEN
Solar/Wind Helper
0.518
233935AB2-179 C
Solar/Wind Helper
1.29
232436AB1-176 C
Solar/Wind Helper
0.045
233923SMA
Solar/Wind Helper
0.974
233990AG1-397 GEN
Solar/Wind Helper
0.031
232432Z2-076 GEN
Solar/Wind Helper
0.068
234033AF1-007_GEN
Solar/Wind Helper
7.137
964001AG1-254 GEN
Solar/Wind Helper
0.966
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.116
203975AE1-071-GEN
Solar/Wind Helper
2.53
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.081
214067T20SOLAR
Solar/Wind Helper
0.011
24318805MLG1
50/50
10.022
23559001PLEAS1
50/50
5.443
270051AF1-062 GEN
50/50
11.999
970153AG2-106 GEN
Solar/Wind Harmer
17.863
961921AG1-034 GEN
Solar/Wind Harmer
15.919
241955AC1-078 GEN
Solar/Wind Harmer
8.948
241974AD2-163_GEN2
Solar/Wind Harmer
2.37
942051AE2-217 GEN
Solar/Wind Harmer
21.374
942871AE2-306 GEN
Solar/Wind Harmer
1.073
270391AF1-285 GEN3
Solar/Wind Harmer
0.55
960801AF2-371 GEN
Solar/Wind Harmer
2.991
964871AG1-351 GEN
Solar/Wind Harmer
2.065
970605AG2-385 GEN
Solar/Wind Harmer
6.332
270485AE1-090_GEN
Solar/Wind Harmer
0.709
270512AE1-227 GEN2
Solar/Wind Harmer
2.455
24721905FLATG4
Adder
23.506
253338AC1-165 GEN
Solar/Wind Harmer
1.256
253333AC1-068 GEN
Solar/Wind Harmer
1.211
970065AG2-057 GEN
Solar/Wind Harmer
1.148
270273AD2-016 GEN
Solar/Wind Harmer
3.061
972173AH1-669 GEN
Solar/Wind Harmer
5.721
270377AD1-106 GEN
Solar/Wind Harmer
6.988
270588AE1-091_GEN
Solar/Wind Harmer
12.311
270291AC1-194 GEN
Solar/Wind Harmer
11.854
253415AE1-040 GEN
Solar/Wind Harmer
1.258
961961AG1-039 GEN
Solar/Wind Harmer
3.188
270491AE1-102 GEN2
Solar/Wind Harmer
1.443
970217AG2-149 GEN
Solar/Wind Harmer
35.355
958091AF2-103 GEN
Solar/Wind Harmer
0.178
253303V4-073 C
Solar/Wind Harmer
0.128
253370AE2-315 SEC1
Adder
2.206
253371AE2-315 SEC2
Adder
2.086
270191TR4_S_V150
Solar/Wind Harmer
3.3
270247TR4_N_V136
Solar/Wind Harmer
0.936
959331AF2-224 GEN
Solar/Wind Harmer
10.972
965021AG1-366 GEN
Solar/Wind Harmer
2.552
270258AD1-119 GEN
Solar/Wind Harmer
3.051
253406AD2-031_GEN
Solar/Wind Harmer
1.398
270044AE2-322 C
Solar/Wind Harmer
1.435
270404AC1-167 GEN
Solar/Wind Harmer
1.194
957541AF2-048 GEN
Solar/Wind Harmer
1.725
270043AE2-236 GEN
Solar/Wind Harmer
5.98
944531AF1-118 GEN
Solar/Wind Harmer
37.943
253316AC1-085 GEN3
Solar/Wind Harmer
9.07
253433AC1-085 GEN1
Solar/Wind Harmer
5.758
946181AF1-283 GEN
Solar/Wind Harmer
14.077
970031AG2-029 GEN
Solar/Wind Harmer
32.394
971617AH1-308 GEN
Solar/Wind Harmer
6.274
270541AE2-072 C
Solar/Wind Harmer
4.881
971191AH1-055 GEN
Solar/Wind Harmer
23.635
962031AG1-047 GEN
Solar/Wind Harmer
3.246
957741AF2-068 GEN
Solar/Wind Harmer
16.111
25196608WSDLE5
Adder
9.143
24642205MAYFLWER
Adder
0.678
25194608D.CRK4
Adder
1.752
247604X1-042
Adder
0.444
23906502RICHG2&3
Adder
1.272
25196008MFTGT1
Adder
1.413
274752CRETE EC ;2U
Adder
8.598
274753CRETE EC ;3U
Adder
8.598
274724RIVER EC ;11
Adder
18.459
274772LINCOLN ;3U
Adder
8.792
274802UNIV PARK;5U
Adder
6.05
274826FISK ;BP
Adder
11.355
274800UNIV PARK;3U
Adder
6.045
972038AH1-567 GEN2
Adder
0.378
972228AH1-698 GEN2
Adder
3.84
274676JOLIET 29;8U
Adder
30.573
274729ELWOOD EC;1P
Adder
16.983
274730ELWOOD EC;6P
Adder
16.983
270119AB2-067 GEN1
50/50
7.033
270120AB2-067 GEN2
50/50
7.033
24318905MLG2
50/50
7.475
270471AD2-092_GEN
Solar/Wind Harmer
4.529
946101AF1-275 GEN
Solar/Wind Harmer
1.842
938701AE1-092 GEN
Solar/Wind Harmer
24.483
270224U2-072_GEN2
Solar/Wind Harmer
2.339
270227U2-072_GEN3
Solar/Wind Harmer
2.339
270228U2-072_GEN4
Solar/Wind Harmer
2.339
270231U2-072_GEN5
Solar/Wind Harmer
2.339
942861AE2-305 GEN
Solar/Wind Harmer
9.223
964601AG1-323 GEN
Solar/Wind Harmer
3.753
964601AG1-323 GEN
Solar/Wind Harmer
1.746
972269AH1-719 GEN
Adder
2.7
970077AG2-063 GEN
Solar/Wind Harmer
6.332
972159AH1-661 GEN
Adder
1.166
270518AE2-148 GEN
Solar/Wind Harmer
14.068
971199AH1-059 GEN
Solar/Wind Harmer
4.644
241960AC2-195 GEN
Solar/Wind Harmer
3.219
971201AH1-060 GEN
Solar/Wind Harmer
2.296
253378AE2-206_GEN
Solar/Wind Harmer
4.086
276820AF1-078_GEN
Solar/Wind Harmer
1.815
971231AH1-075 GEN
Solar/Wind Harmer
0.905
25326509SID D
Adder
1.48
25326109MON D
Adder
1.461
246938BC-WTG3
Solar/Wind Harmer
4.418
246937BC-WTG2
Solar/Wind Harmer
4.343
970879AG2-548 GEN
Solar/Wind Harmer
6.827
971073AG2-665 GEN
Solar/Wind Harmer
6.827
971073AG2-665 GEN
Solar/Wind Harmer
4.763
25322209TAIT E
Adder
10.77
25322209TAIT E
Adder
10.528
270007AE1-245 C
Solar/Wind Harmer
6.539
942801AE2-298 GEN
Solar/Wind Harmer
1.667
253370AE2-315 SEC1
Adder
2.206
970611AG2-400 GEN
Solar/Wind Harmer
10.972
253394AE2-221_GEN
Solar/Wind Harmer
4.954
253398AE2-221_GEN2
Solar/Wind Harmer
4.954
253317AC1-085 GEN4
Solar/Wind Harmer
9.07
971677AH1-339 GEN
Solar/Wind Harmer
8.643
942221AE2-234 GEN
Solar/Wind Harmer
0.79
944541AF1-119 GEN
Solar/Wind Harmer
4.511
960971AF2-388 GEN
Solar/Wind Harmer
11.771
247621Y3-024
Adder
0.259
270201AC2-176 GEN
Solar/Wind Harmer
5.522
970883AG2-550 GEN
Solar/Wind Harmer
10.73
970885AG2-551 GEN
Solar/Wind Harmer
2.495
247620Y3-023
Adder
0.494
964611AG1-324 GEN
Solar/Wind Harmer
1.264
964611AG1-324 GEN
Solar/Wind Harmer
0.561
25194408D.CRK1
Adder
8.061
25194508D.CRK3
Adder
1.507
24728805RICHG1
Adder
4.003
24728905RICHG2
Adder
4.003
970935AG2-582 GEN
Adder
239.406
274770LINCOLN ;1U
Adder
8.792
274771LINCOLN ;2U
Adder
8.792
274808UNIV PK N;4U
Adder
5.188
274803UNIV PARK;6U
Adder
6.05
972259AH1-714 GEN
Adder
19.76
238175AF1-290_GEN
Solar/Wind Helper
0.168
238169AE2-226 GEN1
Solar/Wind Helper
0.772
238170AE2-226 GEN2
Solar/Wind Helper
0.772
238120AE2-309 GEN
Solar/Wind Helper
0.552
23585401KL_K28_T16
Solar/Wind Helper
1.529
235020AA1-095 C
Solar/Wind Helper
0.057
23777901MDS_W4-102
Solar/Wind Helper
0.191
237034AC2-136 C
Solar/Wind Helper
0.244
237002AB1-128_GEN
Solar/Wind Helper
0.475
235063AE1-101 C2
Solar/Wind Helper
1.776
237001AB1-127_GEN
Solar/Wind Helper
0.473
23777801MSM_W1-116
Solar/Wind Helper
0.122
237025AB1-124 C
Solar/Wind Helper
0.175
237006AB1-125 GEN
Solar/Wind Helper
0.131
226929AD2-058 GEN
Solar/Wind Helper
0.108
315651AD1-115 GEN
Solar/Wind Helper
0.876
316447AC1-158 HLD
Solar/Wind Helper
3.175
205916AD1-020 GEN
Solar/Wind Helper
1.761
20390526W1-045 C
Solar/Wind Helper
0.36
208835TUHI V3-051
Solar/Wind Helper
0.025
208835TUHI V3-051
Solar/Wind Helper
0.025
3132123MT JACKSON
Solar/Wind Helper
0.764
233987AB2-037 GEN
Solar/Wind Helper
2.381
233933AB2-153 GEN
Solar/Wind Helper
0.236
232424Y1-079 C
Solar/Wind Helper
0.118
233944AB2-135 GEN
Solar/Wind Helper
0.598
233946AB2-136 GEN
Solar/Wind Helper
0.577
234036AF2-325 C
Solar/Wind Helper
0.043
233901CHERRYDALE C
Solar/Wind Helper
0.236
232408W1-005 C
Solar/Wind Helper
0.516
232410W1-006 C
Solar/Wind Helper
0.516
233939AC1-091 C
Solar/Wind Helper
0.356
233970AC1-092 C
Solar/Wind Helper
0.356
966001AG1-469 GEN
Solar/Wind Helper
0.255
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.041
219921AF1-264
Solar/Wind Helper
0.052
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.083
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.168
20674928WA_W3-044
Solar/Wind Helper
0.098
20676228FRD_X1-012
Solar/Wind Helper
0.091
964851AG1-348 GEN
Solar/Wind Helper
0.081
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.044
211065PSPA IPP
Solar/Wind Helper
0.15
211065PSPA IPP
Solar/Wind Helper
0.15
270166AC1-044 GEN3
50/50
7.033
23559101PLEAS2
50/50
5.443
270122AB2-093 CT
50/50
4.116
962761AG1-125 GEN
Solar/Wind Harmer
40.965
970149AG2-104 GEN
Solar/Wind Harmer
50.592
970155AG2-107 GEN
Solar/Wind Harmer
17.863
270349AD2-093_GEN
Solar/Wind Harmer
4.529
270223U2-072_GEN1
Solar/Wind Harmer
2.339
270578AF1-285 GEN2
Solar/Wind Harmer
1.43
270391AF1-285 GEN3
Solar/Wind Harmer
1.43
270159DARBY CT4
Adder
10.388
971995AH1-542 GEN
Solar/Wind Harmer
12.974
970593AG2-378 GEN
Solar/Wind Harmer
2.345
270462AD2-086
Solar/Wind Harmer
8.157
270510AE1-227 GEN1
Solar/Wind Harmer
2.893
24721705FLATG2
Adder
23.506
253343AC1-166 GEN
Solar/Wind Harmer
1.256
253325AC1-069 GEN
Solar/Wind Harmer
1.211
241813AF1-122_GEN
Solar/Wind Harmer
7.346
270263AC1-001 GEN
Solar/Wind Harmer
1.187
241847AF2-150_GEN
Solar/Wind Harmer
4.622
246936BC-WTG1
Solar/Wind Harmer
4.343
270489AE1-102 GEN1
Solar/Wind Harmer
1.443
965421AG1-410 GEN
Solar/Wind Harmer
33.256
970515AG2-329 GEN
Solar/Wind Harmer
16.033
25326309TAIT D
Adder
1.21
960071AF2-298 GEN
Solar/Wind Harmer
5.501
253370AE2-315 SEC1
Adder
2.206
253371AE2-315 SEC2
Adder
2.086
247521TR3_G114
Solar/Wind Harmer
3.699
270246TR4_N_V150
Solar/Wind Harmer
0.936
247522W1-056 GEN
Solar/Wind Harmer
2.477
24695305TIMB G C
Solar/Wind Harmer
6.051
965011AG1-365 GEN
Solar/Wind Harmer
10.972
927014AC1-188 GEN
Solar/Wind Harmer
1.729
944231AF1-091 GEN
Solar/Wind Harmer
4.078
253432AC1-085 GEN2
Solar/Wind Harmer
0.29
946171AF1-282 GEN
Solar/Wind Harmer
10.828
270063AE2-323 C
Solar/Wind Harmer
2.376
965651AG1-433 GEN
Solar/Wind Harmer
5.885
958861AF2-177 GEN
Solar/Wind Harmer
11.752
247536S-71 GEN
Solar/Wind Harmer
4.346
960001AF2-291 GEN
Solar/Wind Harmer
3.244
945371AF1-202 GEN
Solar/Wind Harmer
7.479
24639705ELKHART HY
Adder
0.164
25194608D.CRK4
Adder
1.752
25196808ZIMRHP
Adder
80.188
23906502RICHG2&3
Adder
1.272
972301AH1-735 GEN
Adder
6.357
23906402RICHG1
Adder
1.271
25196008MFTGT1
Adder
1.459
274751CRETE EC ;1U
Adder
8.598
274754CRETE EC ;4U
Adder
8.598
274723RIVER EC ;12
Adder
18.677
274773LINCOLN ;4U
Adder
8.792
274774LINCOLN ;5U
Adder
8.792
274812UNIV PK N;8U
Adder
5.21
23920202STRYCT
Adder
1.444
274801UNIV PARK;4U
Adder
6.045
274676JOLIET 29;8U
Adder
31.706
274732ELWOOD EC;7P
Adder
2.004
23583801GRNGAP
Solar/Wind Helper
6.365
316095T157 G97
Solar/Wind Helper
1.705
238108AE1-109 GEN1
Solar/Wind Helper
0.121
238185AF2-356 C
Solar/Wind Helper
2.767
238147AE2-230_GEN1
Solar/Wind Helper
0.552
238149AF1-291A_GEN
Solar/Wind Helper
0.158
237061AD1-155 GEN
Solar/Wind Helper
0.06
235054AD2-180 GEN
Solar/Wind Helper
2.111
235531U2-073 GEN
Solar/Wind Helper
3.439
238117U2-030
Solar/Wind Helper
0.356
238221AF1-254 C O1
Solar/Wind Helper
0.295
235067AD1-061 GEN
Solar/Wind Helper
0.532
3141196NOKESVL
Solar/Wind Helper
1.141
964991AG1-363 GEN
Solar/Wind Helper
5.557
316097T157 G90
Solar/Wind Helper
1.705
23750701CROSSCHOOL
Solar/Wind Helper
1.586
238148AE2-230_GEN2
Solar/Wind Helper
0.555
238127S14_GEN_2
Solar/Wind Helper
0.867
238118U2-030_1
Solar/Wind Helper
0.356
237080AD1-060 GEN
Solar/Wind Helper
0.367
237038AE2-054 C
Solar/Wind Helper
0.292
235062AE1-101 C1
Solar/Wind Helper
1.776
23779801AA1-109
Solar/Wind Helper
0.207
316006AB2-029 C
Solar/Wind Helper
0.13
223401AF1-299 GEN
Solar/Wind Helper
0.387
316045AC1-158 PL2
Solar/Wind Helper
4.618
316254AC1-120 GEN1
Solar/Wind Helper
1.184
237048AF1-022 C
Solar/Wind Helper
0.173
966131AG1-482 GEN
Solar/Wind Helper
0.079
233930AB2-032 GEN
Solar/Wind Helper
0.387
233915AB1-141 GEN
Solar/Wind Helper
0.511
232422X3-066 FULL
Solar/Wind Helper
0.116
233964AF2-378 GEN
Solar/Wind Helper
0.042
232426Y1-080 FULL
Solar/Wind Helper
0.039
233998TM1NIN_3.36
Solar/Wind Helper
0.266
232404W1-003 C
Solar/Wind Helper
0.516
232428Y3-058 C
Solar/Wind Helper
0.344
3147666LOUISA
Solar/Wind Helper
0.958
232434Z2-077 GEN
Solar/Wind Helper
0.129
233954AC2-188 GEN
Solar/Wind Helper
0.236
233950AC2-186 GEN
Solar/Wind Helper
0.118
233972AC1-094 C
Solar/Wind Helper
0.307
316192AB2-158 GEN
Solar/Wind Helper
1.608
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.232
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.061
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.132
20720728JCB_W1-129
Solar/Wind Helper
0.057
207445AB1-138_GEN
Solar/Wind Helper
0.105
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.078
207454AA2-184 E
Solar/Wind Helper
0.311
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.497
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.137
207518AF1-320_GEN
Solar/Wind Helper
1.568
20671928W4-073
Solar/Wind Helper
0.089
20675828AU_W4-064
Solar/Wind Helper
0.029
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.292
219620RIDERU C
Solar/Wind Helper
0.001
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
20674828DL_W4-046
Solar/Wind Helper
0.008
207484AF2-139 C O1
Solar/Wind Helper
0.084
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.136
20675128HRM_W1-127
Solar/Wind Helper
0.029
209116AE2-175 GEN
Solar/Wind Helper
1.768
945581AF1-223 GEN
Solar/Wind Harmer
0.763
23751201ROTHROCK
Solar/Wind Helper
0.819
237030AB1-096 C
Solar/Wind Helper
0.075
23562501BACKB
Solar/Wind Helper
0.997
226910AB2-157 C
Solar/Wind Helper
0.015
227287AC2-120 GEN
Solar/Wind Helper
0.375
223402AF1-300 C
Solar/Wind Helper
0.387
316044AC1-158 PL1
Solar/Wind Helper
1.443
316450AC1-158 RIC
Solar/Wind Helper
0.385
316170AC1-121 GEN2
Solar/Wind Helper
0.395
23751101LEADS_P59
Solar/Wind Helper
1.316
205917AD1-020 ES
Solar/Wind Helper
0.379
3132273ORANGE
Solar/Wind Helper
0.049
233918AB1-142 GEN
Solar/Wind Helper
0.511
233982AB2-133 GEN
Solar/Wind Helper
0.364
233994AC2-023 GEN
Solar/Wind Helper
0.977
233996TM1833_GEN
Solar/Wind Helper
0.266
233997TMININ_4.2
Solar/Wind Helper
0.266
232406W1-004 FULL
Solar/Wind Helper
0.516
3147666LOUISA
Solar/Wind Helper
0.551
233940AF2-379 C
Solar/Wind Helper
0.063
234015AF2-250 C
Solar/Wind Helper
0.039
233952AC2-187 GEN
Solar/Wind Helper
0.236
233971AC1-093 C
Solar/Wind Helper
0.363
230430AE1-229_GEN
Solar/Wind Helper
3.409
230415AB2-049 C
Solar/Wind Helper
0.031
228729W2-030 C
Solar/Wind Helper
0.112
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.151
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.064
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
219276PARKLANDSO C
Solar/Wind Helper
0.09
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
966881AG1-559 GEN
Solar/Wind Helper
0.312
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
LAGNLTFEXP_LAGN->PJM
CLTF
14.521
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.32
TVALTFEXP_TVA->PJM
CLTF
7.111
CBM West 2LTFEXP_CBM-W2->PJM
CBM
111.893
NYPJM->LTFIMP_NY
CLTF
4.554
LGEELTFEXP_LGEE->PJM
CLTF
6.753
WECLTFEXP_WEC->PJM
CLTF
3.866
AG2-052LTFEXP_AG2-052->PJM
LTF
0.243
AH1-155LTFEXP_AH1-155->PJM
LTF
0.364
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.579
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.544
MECLTFEXP_MEC->PJM
CLTF
15.979
SIGELTFEXP_SIGE->PJM
CLTF
0.506

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-008A_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.1 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4627.6
MW Contribution:242.4
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
6.869
270120AB2-067 GEN2
50/50
6.869
24318905MLG2
50/50
6.89
270471AD2-092_GEN
Solar/Wind Harmer
0.006
942861AE2-305 GEN
Solar/Wind Harmer
6.118
970077AG2-063 GEN
Solar/Wind Harmer
4.471
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
12.484
971655AH1-328 GEN
Solar/Wind Harmer
2.758
964601AG1-323 GEN
Solar/Wind Harmer
3.106
964601AG1-323 GEN
Solar/Wind Harmer
2.071
270518AE2-148 GEN
Solar/Wind Harmer
0.667
972269AH1-719 GEN
Adder
2.501
972159AH1-661 GEN
Adder
1.082
253378AE2-206_GEN
Solar/Wind Harmer
0.004
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
3.237
971199AH1-059 GEN
Solar/Wind Harmer
2.99
241960AC2-195 GEN
Solar/Wind Harmer
0.006
970935AG2-582 GEN
Adder
242.403
25326509SID D
Adder
1.4
971073AG2-665 GEN
Solar/Wind Harmer
6.645
25326109MON D
Adder
1.391
971201AH1-060 GEN
Solar/Wind Harmer
1.471
25322209TAIT E
Adder
10.262
25322209TAIT E
Adder
10.031
253370AE2-315 SEC1
Adder
2.103
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
246938BC-WTG3
Solar/Wind Harmer
0.263
246937BC-WTG2
Solar/Wind Harmer
0.295
971231AH1-075 GEN
Solar/Wind Harmer
0.833
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
970611AG2-400 GEN
Solar/Wind Harmer
7.225
970627AG2-408 GEN
Solar/Wind Harmer
2.167
270007AE1-245 C
Solar/Wind Harmer
0.002
970623AG2-406 GEN
Solar/Wind Harmer
1.309
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25183208HLCRTG
Solar/Wind Harmer
0.011
944541AF1-119 GEN
Solar/Wind Harmer
0.479
960971AF2-388 GEN
Solar/Wind Harmer
4.192
942221AE2-234 GEN
Solar/Wind Harmer
0.036
252519AF1-045_GEN
Solar/Wind Harmer
6.204
252516AE2-318_GEN
Solar/Wind Harmer
5.503
970621AG2-405 GEN
Solar/Wind Harmer
1.305
247621Y3-024
Adder
0.246
970883AG2-550 GEN
Solar/Wind Harmer
7.123
970885AG2-551 GEN
Solar/Wind Harmer
2.374
270201AC2-176 GEN
Solar/Wind Harmer
0.001
25194408D.CRK1
Adder
7.711
25194508D.CRK3
Adder
1.442
964611AG1-324 GEN
Solar/Wind Harmer
0.534
252509AD1-136 GEN
Solar/Wind Harmer
0.036
970321AG2-212 GEN
Solar/Wind Harmer
3.076
270599AE1-208 GEN
Solar/Wind Harmer
6.495
270031AE2-169
Solar/Wind Harmer
3.897
270383AD1-128 GEN
Solar/Wind Harmer
0.004
270186AC1-089 GEN
Solar/Wind Harmer
0.004
247620Y3-023
Adder
0.466
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
7.834
960441AF2-335 GEN
Solar/Wind Harmer
7.065
270216AD2-079_GEN
Solar/Wind Harmer
0.001
971613AH1-306 GEN
Solar/Wind Harmer
3.385
24728805RICHG1
Adder
3.82
24728905RICHG2
Adder
3.82
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
14.072
961051AF2-396 GEN
Solar/Wind Harmer
9.381
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
8.77
965791AG1-447 GEN
Solar/Wind Harmer
6.431
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.73
274770LINCOLN ;1U
Adder
8.364
274771LINCOLN ;2U
Adder
8.364
274808UNIV PK N;4U
Adder
4.933
966841AG1-555 GEN
Solar/Wind Harmer
0.781
274803UNIV PARK;6U
Adder
5.755
274888KELLY CRK;1U
Solar/Wind Harmer
0.404
274887GEN-1.85
Solar/Wind Harmer
0.181
276843GEN-1.7
Solar/Wind Harmer
0.223
958011AF2-095 GEN
Solar/Wind Harmer
9.913
972259AH1-714 GEN
Adder
18.805
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
3.993
958481AF2-142 GEN
Solar/Wind Harmer
10.238
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.923
971573AH1-285 GEN
Solar/Wind Harmer
1.271
971677AH1-339 GEN
Solar/Wind Harmer
0.768
958491AF2-143 GEN
Solar/Wind Harmer
10.205
274879MINONK ;1U
Solar/Wind Harmer
0.287
238175AF1-290_GEN
Solar/Wind Helper
0.148
238169AE2-226 GEN1
Solar/Wind Helper
0.677
238170AE2-226 GEN2
Solar/Wind Helper
0.677
238120AE2-309 GEN
Solar/Wind Helper
0.487
235020AA1-095 C
Solar/Wind Helper
0.051
23777901MDS_W4-102
Solar/Wind Helper
0.171
23585401KL_K28_T16
Solar/Wind Helper
1.328
237034AC2-136 C
Solar/Wind Helper
0.219
237002AB1-128_GEN
Solar/Wind Helper
0.427
235063AE1-101 C2
Solar/Wind Helper
1.6
237001AB1-127_GEN
Solar/Wind Helper
0.426
23777801MSM_W1-116
Solar/Wind Helper
0.11
237025AB1-124 C
Solar/Wind Helper
0.159
237006AB1-125 GEN
Solar/Wind Helper
0.119
226929AD2-058 GEN
Solar/Wind Helper
0.096
205916AD1-020 GEN
Solar/Wind Helper
1.656
20390526W1-045 C
Solar/Wind Helper
0.338
208835TUHI V3-051
Solar/Wind Helper
0.023
208835TUHI V3-051
Solar/Wind Helper
0.023
233987AB2-037 GEN
Solar/Wind Helper
2.264
233933AB2-153 GEN
Solar/Wind Helper
0.225
232424Y1-079 C
Solar/Wind Helper
0.112
233944AB2-135 GEN
Solar/Wind Helper
0.569
233946AB2-136 GEN
Solar/Wind Helper
0.549
234036AF2-325 C
Solar/Wind Helper
0.041
233901CHERRYDALE C
Solar/Wind Helper
0.225
232408W1-005 C
Solar/Wind Helper
0.49
232410W1-006 C
Solar/Wind Helper
0.49
233939AC1-091 C
Solar/Wind Helper
0.338
233970AC1-092 C
Solar/Wind Helper
0.338
315651AD1-115 GEN
Solar/Wind Helper
0.76
972239AH1-704 GEN
50/50
2.78
962771AG1-126 GEN
Solar/Wind Harmer
33.269
270459AD2-067 GEN
Solar/Wind Harmer
0
270054AF2-122 C O1
Solar/Wind Harmer
0.007
961821AG1-024 GEN
Solar/Wind Harmer
4.91
270520AE2-214 GEN
Solar/Wind Harmer
0.013
270284AF1-227 GEN1
Solar/Wind Harmer
0.01
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
253383AE2-342_GEN
Solar/Wind Harmer
0.003
241973AD2-163_GEN1
Solar/Wind Harmer
0.006
945631AF1-228 GEN
Solar/Wind Harmer
0
943861AF1-054 GEN
Solar/Wind Harmer
3.02
943851AF1-053 GEN
Solar/Wind Harmer
2.092
270156DARBY CT1
Adder
10.05
270157DARBY CT2
Adder
10.026
270158DARBY CT3
Adder
9.866
270578AF1-285 GEN2
Solar/Wind Harmer
0.518
970689AG2-444 GEN
Solar/Wind Harmer
15.861
270432AC2-029 GEN
Solar/Wind Harmer
3.428
940611AE2-048 GEN
Solar/Wind Harmer
18.967
941391AE2-136 GEN
Solar/Wind Harmer
10.684
270302AB2-170 GEN
Solar/Wind Harmer
0.005
270317AD1-130_GEN
Solar/Wind Harmer
0.011
971653AH1-327 GEN
Solar/Wind Harmer
1.08
270269AC2-059
Solar/Wind Harmer
0.004
241972AD1-140 GEN
Solar/Wind Harmer
0.824
970179AG2-119 GEN
Solar/Wind Harmer
6.658
270340AC2-060 GEN
Solar/Wind Harmer
0.009
970879AG2-548 GEN
Solar/Wind Harmer
6.645
253372AE2-315 SEC3
Adder
1.989
253372AE2-315 SEC3
Adder
1.989
25306009OHH W.
Adder
3.018
253349AC2-067 GEN
Solar/Wind Harmer
2.296
253400AC2-068 GEN
Solar/Wind Harmer
0.923
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.92
965051AG1-369 GEN
Solar/Wind Harmer
3.609
971567AH1-282 GEN
Solar/Wind Harmer
10.843
247607V1-011 GEN
Solar/Wind Harmer
0.001
965041AG1-368 GEN
Solar/Wind Harmer
7.21
971989AH1-539 GEN
Solar/Wind Harmer
3.109
963791AG1-232 GEN
Solar/Wind Harmer
9.689
24729505KEY G4
Adder
6.671
270071AF1-092 GEN
Solar/Wind Harmer
13.737
270024AE2-089 GEN
Solar/Wind Harmer
0.008
971985AH1-537 GEN
Solar/Wind Harmer
2.123
965101AG1-375 GEN
Solar/Wind Harmer
7.135
270297AD1-101 GEN
Solar/Wind Harmer
0.002
270367AC2-061_GEN
Solar/Wind Harmer
0.006
971673AH1-337 GEN
Solar/Wind Harmer
4.631
971029AG2-637 GEN
Solar/Wind Harmer
10.686
270543AE2-219 C
Solar/Wind Harmer
0.004
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
9.002
25196308WSDLE2
Adder
8.924
25196208WSDLE1
Adder
8.902
25196708WSDLE6
Adder
8.879
25196508WSDLE4
Adder
8.656
945581AF1-223 GEN
Solar/Wind Harmer
0.001
971347AH1-153 GEN
Solar/Wind Harmer
10.632
971609AH1-304 GEN
Solar/Wind Harmer
1.157
270240V3-007_GEN2
Solar/Wind Harmer
0.002
970115AG2-085 GEN
Solar/Wind Harmer
2.826
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
7.898
971771AH1-392 GEN
Solar/Wind Harmer
7.046
970289AG2-191 GEN
Solar/Wind Harmer
1.339
971619AH1-309 GEN
Solar/Wind Harmer
3.169
971769AH1-391 GEN
Solar/Wind Harmer
7.844
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
25196108MFTGT2
Adder
1.54
25196108MFTGT2
Adder
1.43
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
4.146
971549AH1-272 GEN
Solar/Wind Harmer
14.344
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.364
274776LINCOLN ;7U
Adder
8.364
274777LINCOLN ;8U
Adder
8.364
274814UNIV PK N;0U
Adder
4.998
274807UNIV PK N;3U
Adder
4.987
274805UNIV PK N;1U
Adder
4.965
274811UNIV PK N;7U
Adder
4.954
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
972037AH1-567 GEN1
Adder
0.181
960591AF2-350 GEN
Solar/Wind Harmer
6.884
274827FISK ;RP
Adder
7.655
972227AH1-698 GEN1
Adder
2.573
963841AG1-237 GEN
Solar/Wind Harmer
2.978
274687WILL CNTY;4U
Adder
27.495
274687WILL CNTY;4U
Adder
27.495
274675JOLIET 29;7U
Adder
30.175
274675JOLIET 29;7U
Adder
29.097
972163AH1-664 GEN
Solar/Wind Harmer
7.639
972165AH1-665 GEN
Solar/Wind Harmer
6.118
274731ELWOOD EC;2P
Adder
16.163
274733ELWOOD EC;3P
Adder
16.163
274735ELWOOD EC;4P
Adder
16.163
274728ELWOOD EC;5P
Adder
16.163
970833AG2-524 GEN
Solar/Wind Harmer
7.542
970833AG2-524 GEN
Solar/Wind Harmer
5.028
945641AF1-229 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
276868AE1-113 GEN
Solar/Wind Harmer
1.363
24318805MLG1
50/50
9.842
23559001PLEAS1
50/50
5.385
270051AF1-062 GEN
50/50
11.434
970153AG2-106 GEN
Solar/Wind Harmer
21.245
961921AG1-034 GEN
Solar/Wind Harmer
7.364
241955AC1-078 GEN
Solar/Wind Harmer
0.007
241974AD2-163_GEN2
Solar/Wind Harmer
0.006
942051AE2-217 GEN
Solar/Wind Harmer
14.169
24721905FLATG4
Adder
22.865
970605AG2-385 GEN
Solar/Wind Harmer
4.731
270391AF1-285 GEN3
Solar/Wind Harmer
0.518
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.012
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270273AD2-016 GEN
Solar/Wind Harmer
0.792
972173AH1-669 GEN
Solar/Wind Harmer
3.811
270512AE1-227 GEN2
Solar/Wind Harmer
1.904
270291AC1-194 GEN
Solar/Wind Harmer
5.884
253415AE1-040 GEN
Solar/Wind Harmer
0.003
970065AG2-057 GEN
Solar/Wind Harmer
0.735
253370AE2-315 SEC1
Adder
2.103
253371AE2-315 SEC2
Adder
1.989
970191AG2-125 GEN
Solar/Wind Harmer
1.876
253406AD2-031_GEN
Solar/Wind Harmer
0.543
270491AE1-102 GEN2
Solar/Wind Harmer
0.945
270377AD1-106 GEN
Solar/Wind Harmer
2.761
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.047
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.394
959331AF2-224 GEN
Solar/Wind Harmer
5.057
965021AG1-366 GEN
Solar/Wind Harmer
2.408
270588AE1-091_GEN
Solar/Wind Harmer
5.649
971191AH1-055 GEN
Solar/Wind Harmer
18.515
944531AF1-118 GEN
Solar/Wind Harmer
32.203
270043AE2-236 GEN
Solar/Wind Harmer
4.607
270258AD1-119 GEN
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
5.953
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
10.684
270404AC1-167 GEN
Solar/Wind Harmer
0.003
25196608WSDLE5
Adder
8.745
252510AF1-249 C
Solar/Wind Harmer
0.055
970031AG2-029 GEN
Solar/Wind Harmer
4.625
25194608D.CRK4
Adder
1.676
270222AC2-111 GEN
Solar/Wind Harmer
3.603
970513AG2-328 GEN
Solar/Wind Harmer
3.076
970517AG2-330 GEN
Solar/Wind Harmer
18.457
970349AG2-230 GEN
Solar/Wind Harmer
10.632
946031AF1-268 GEN
Solar/Wind Harmer
6.74
958821AF2-173 GEN
Solar/Wind Harmer
9.902
270004AE1-209 GEN
Solar/Wind Harmer
1.532
270437AC2-090 C
Solar/Wind Harmer
0.003
247643Z2-116 C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.775
970291AG2-192 GEN
Solar/Wind Harmer
0.705
945111AF1-176 GEN
Solar/Wind Harmer
5.709
247642Z2-115 C
Solar/Wind Harmer
0.003
24642205MAYFLWER
Adder
0.641
24441205WTRV SLR C
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.353
270356AE2-297 GEN
Solar/Wind Harmer
0.009
970217AG2-149 GEN
Solar/Wind Harmer
6.066
247604X1-042
Adder
0.418
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
964401AG1-302 GEN
Solar/Wind Harmer
0.001
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.935
970243AG2-164 GEN
Solar/Wind Harmer
4.047
970519AG2-331 GEN
Solar/Wind Harmer
17.988
970699AG2-449 GEN
Solar/Wind Harmer
1.73
274752CRETE EC ;2U
Adder
8.172
274753CRETE EC ;3U
Adder
8.172
274772LINCOLN ;3U
Adder
8.364
274724RIVER EC ;11
Adder
17.549
958171AF2-111 GEN
Solar/Wind Harmer
17.278
274802UNIV PARK;5U
Adder
5.755
276806AD2-047 C O1
Solar/Wind Harmer
3.901
970941AG2-585 GEN
Solar/Wind Harmer
8.605
274826FISK ;BP
Adder
10.802
24728705AND G3
Adder
7.914
24728505AND G1
Adder
3.784
274800UNIV PARK;3U
Adder
5.751
972038AH1-567 GEN2
Adder
0.36
972228AH1-698 GEN2
Adder
3.654
972167AH1-666 GEN
Solar/Wind Harmer
5.505
276897AD1-100 C
Solar/Wind Harmer
0.009
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
22.464
274676JOLIET 29;8U
Adder
29.097
274729ELWOOD EC;1P
Adder
16.163
274730ELWOOD EC;6P
Adder
13.491
276893AG1-478 C
Solar/Wind Harmer
0.272
270541AE2-072 C
Solar/Wind Harmer
0.009
943121AE2-341 GEN
Solar/Wind Harmer
11.459
943591AF1-030 GEN
Solar/Wind Harmer
7.62
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
276805AD2-038 GEN
Solar/Wind Harmer
0.002
964991AG1-363 GEN
Solar/Wind Helper
4.969
316097T157 G90
Solar/Wind Helper
1.455
23750701CROSSCHOOL
Solar/Wind Helper
1.397
238148AE2-230_GEN2
Solar/Wind Helper
0.48
238127S14_GEN_2
Solar/Wind Helper
0.766
238118U2-030_1
Solar/Wind Helper
0.314
237080AD1-060 GEN
Solar/Wind Helper
0.33
237038AE2-054 C
Solar/Wind Helper
0.262
235062AE1-101 C1
Solar/Wind Helper
1.6
23779801AA1-109
Solar/Wind Helper
0.187
223401AF1-299 GEN
Solar/Wind Helper
0.355
316006AB2-029 C
Solar/Wind Helper
0.113
966131AG1-482 GEN
Solar/Wind Helper
0.132
237048AF1-022 C
Solar/Wind Helper
0.159
233930AB2-032 GEN
Solar/Wind Helper
0.368
233915AB1-141 GEN
Solar/Wind Helper
0.486
232422X3-066 FULL
Solar/Wind Helper
0.11
232426Y1-080 FULL
Solar/Wind Helper
0.038
233964AF2-378 GEN
Solar/Wind Helper
0.04
233998TM1NIN_3.36
Solar/Wind Helper
0.253
232404W1-003 C
Solar/Wind Helper
0.49
232428Y3-058 C
Solar/Wind Helper
0.327
232434Z2-077 GEN
Solar/Wind Helper
0.123
233954AC2-188 GEN
Solar/Wind Helper
0.225
233950AC2-186 GEN
Solar/Wind Helper
0.112
233972AC1-094 C
Solar/Wind Helper
0.292
316045AC1-158 PL2
Solar/Wind Helper
4.009
230511AF1-262
Solar/Wind Helper
0.014
230434AG1-499 GEN
Solar/Wind Helper
0.222
228728W1-130C
Solar/Wind Helper
0.052
219258KINSLEYDEP C
Solar/Wind Helper
0.074
219904AC1-010 C
Solar/Wind Helper
0.058
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219907AC1-030 C
Solar/Wind Helper
0.033
219686LUMSOLAR_N C
Solar/Wind Helper
0.038
219304NAMERICA C
Solar/Wind Helper
0.127
316254AC1-120 GEN1
Solar/Wind Helper
1.026
20720728JCB_W1-129
Solar/Wind Helper
0.055
207445AB1-138_GEN
Solar/Wind Helper
0.101
963711AG1-223 GEN
Solar/Wind Helper
0.062
20714828MDF_W3-079
Solar/Wind Helper
0.126
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.299
20715228NPK_W1-113
Solar/Wind Helper
0.075
270166AC1-044 GEN3
50/50
6.869
23559101PLEAS2
50/50
5.385
270122AB2-093 CT
50/50
3.689
962761AG1-125 GEN
Solar/Wind Harmer
33.269
970149AG2-104 GEN
Solar/Wind Harmer
35.932
970155AG2-107 GEN
Solar/Wind Harmer
21.245
270349AD2-093_GEN
Solar/Wind Harmer
0.006
24721705FLATG2
Adder
22.865
270159DARBY CT4
Adder
9.89
970593AG2-378 GEN
Solar/Wind Harmer
1.75
270223U2-072_GEN1
Solar/Wind Harmer
0.001
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.012
270462AD2-086
Solar/Wind Harmer
0.016
971995AH1-542 GEN
Solar/Wind Harmer
2.81
270263AC1-001 GEN
Solar/Wind Harmer
0.758
270510AE1-227 GEN1
Solar/Wind Harmer
1.904
241813AF1-122_GEN
Solar/Wind Harmer
3.294
25326309TAIT D
Adder
1.153
960071AF2-298 GEN
Solar/Wind Harmer
3.651
253370AE2-315 SEC1
Adder
2.103
253371AE2-315 SEC2
Adder
1.989
927014AC1-188 GEN
Solar/Wind Harmer
0.004
246936BC-WTG1
Solar/Wind Harmer
0.295
270489AE1-102 GEN1
Solar/Wind Harmer
0.945
965421AG1-410 GEN
Solar/Wind Harmer
21.788
247521TR3_G114
Solar/Wind Harmer
0.263
270246TR4_N_V150
Solar/Wind Harmer
0.047
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.226
965011AG1-365 GEN
Solar/Wind Harmer
7.225
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
2.096
958861AF2-177 GEN
Solar/Wind Harmer
3.092
247536S-71 GEN
Solar/Wind Harmer
0.287
945371AF1-202 GEN
Solar/Wind Harmer
0.001
25194608D.CRK4
Adder
1.676
270063AE2-323 C
Solar/Wind Harmer
0.006
252507AC2-088 GEN
Solar/Wind Harmer
0.323
970245AG2-165 GEN
Solar/Wind Harmer
3.076
944231AF1-091 GEN
Solar/Wind Harmer
1.885
270005AE1-210 C O1
Solar/Wind Harmer
1.532
965031AG1-367 GEN
Solar/Wind Harmer
7.073
970947AG2-589 GEN
Solar/Wind Harmer
0.236
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.183
970825AG2-519 GEN
Solar/Wind Harmer
2.509
24639705ELKHART HY
Adder
0.155
25196808ZIMRHP
Adder
76.799
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
270032AE2-172
Solar/Wind Harmer
4.701
970291AG2-192 GEN
Solar/Wind Harmer
0.916
316447AC1-158 HLD
Solar/Wind Helper
2.756
230433AD2-135 GEN
Solar/Wind Helper
0.016
230407AD2-065 C
Solar/Wind Helper
0.039
219921AF1-264
Solar/Wind Helper
0.049
219615MILLCREEK C
Solar/Wind Helper
0.026
963401AG1-189 GEN
Solar/Wind Helper
0.054
963391AG1-188 GEN
Solar/Wind Helper
0.079
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.183
276882AE2-255 GEN
Solar/Wind Harmer
0.794
238109AE1-109 GEN2
Solar/Wind Helper
0.106
238110AE1-109 GEN3
Solar/Wind Helper
0.106
238152AF2-075_GEN
Solar/Wind Helper
0.683
23546401DTGZ2-030
Solar/Wind Helper
0.086
238208AF1-136 C
Solar/Wind Helper
0.211
238126S14_GEN_1
Solar/Wind Helper
0.766
237085AD2-009_GEN
Solar/Wind Helper
1.588
3138216PACIFIC
Solar/Wind Helper
0.043
316411AF1-147_GEN1
Solar/Wind Helper
0.86
316415AF1-147_GEN2
Solar/Wind Helper
0.86
959381AF2-229 GEN
Solar/Wind Helper
0.345
23750501ELLIOTTS
Solar/Wind Helper
0.571
3141426STAFORD
Solar/Wind Helper
0.051
960921AF2-383 GEN
Solar/Wind Helper
0.352
205943AE1-185 GEN
Solar/Wind Helper
0.492
205956AE1-196_GEN
Solar/Wind Helper
0.492
205932AD2-116_GEN
Solar/Wind Helper
0.492
233935AB2-179 C
Solar/Wind Helper
1.227
232436AB1-176 C
Solar/Wind Helper
0.043
233923SMA
Solar/Wind Helper
0.927
233990AG1-397 GEN
Solar/Wind Helper
0.261
234033AF1-007_GEN
Solar/Wind Helper
6.787
232432Z2-076 GEN
Solar/Wind Helper
0.065
964001AG1-254 GEN
Solar/Wind Helper
0.924
228754AB1-001 C
Solar/Wind Helper
0.025
227927V4-067C
Solar/Wind Helper
0.01
219914AD2-027 C
Solar/Wind Helper
0.111
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.038
219607WPEMNERT C
Solar/Wind Helper
0.077
214067T20SOLAR
Solar/Wind Helper
0.011
203975AE1-071-GEN
Solar/Wind Helper
2.41
20715728PEM_W1-119
Solar/Wind Helper
0.093
20715828PEM_W1-120
Solar/Wind Helper
0.093
207459AE1-142 C O1
Solar/Wind Helper
0.28
316164AC1-076 GEN
Solar/Wind Helper
1.062
219620RIDERU C
Solar/Wind Helper
0.001
945111AF1-176 GEN
Solar/Wind Harmer
12.568
270505AE1-170 C O1
Solar/Wind Harmer
7.393
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.67
247522W1-056 GEN
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
7.842
25196008MFTGT1
Adder
1.397
970773AG2-487 GEN
Solar/Wind Harmer
1.237
970373AG2-245 GEN
Solar/Wind Harmer
14.699
970515AG2-329 GEN
Solar/Wind Harmer
18.197
270055AF2-134 C O1
Solar/Wind Harmer
0.005
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.071
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.706
24791305MDL-5G
Solar/Wind Harmer
0.001
970333AG2-219 GEN
Solar/Wind Harmer
4.947
274751CRETE EC ;1U
Adder
8.172
274754CRETE EC ;4U
Adder
8.172
274773LINCOLN ;4U
Adder
8.364
274774LINCOLN ;5U
Adder
8.364
274723RIVER EC ;12
Adder
17.756
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.954
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
276776AD2-060 GEN
Solar/Wind Harmer
0.719
24728605AND G2
Adder
3.784
274801UNIV PARK;4U
Adder
5.751
941551AE2-152 GEN
Solar/Wind Harmer
0.001
945681AF1-233 GEN
Solar/Wind Harmer
12.962
274676JOLIET 29;8U
Adder
30.175
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
16.202
939401AE1-172 GEN
Solar/Wind Harmer
5.109
276691AA1-018 GEN1
Solar/Wind Harmer
0.827
276901AD2-066 C O1
Solar/Wind Harmer
0.007
316095T157 G97
Solar/Wind Helper
1.455
23583801GRNGAP
Solar/Wind Helper
5.418
238108AE1-109 GEN1
Solar/Wind Helper
0.106
238185AF2-356 C
Solar/Wind Helper
2.425
238147AE2-230_GEN1
Solar/Wind Helper
0.478
238149AF1-291A_GEN
Solar/Wind Helper
0.137
235531U2-073 GEN
Solar/Wind Helper
3.034
235054AD2-180 GEN
Solar/Wind Helper
1.839
237061AD1-155 GEN
Solar/Wind Helper
0.051
238117U2-030
Solar/Wind Helper
0.314
238221AF1-254 C O1
Solar/Wind Helper
0.265
235067AD1-061 GEN
Solar/Wind Helper
0.478
237030AB1-096 C
Solar/Wind Helper
0.068
3141196NOKESVL
Solar/Wind Helper
0.999
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.335
223402AF1-300 C
Solar/Wind Helper
0.355
23751201ROTHROCK
Solar/Wind Helper
0.694
23562501BACKB
Solar/Wind Helper
0.842
205917AD1-020 ES
Solar/Wind Helper
0.356
233982AB2-133 GEN
Solar/Wind Helper
0.346
233918AB1-142 GEN
Solar/Wind Helper
0.486
233994AC2-023 GEN
Solar/Wind Helper
0.929
233996TM1833_GEN
Solar/Wind Helper
0.253
233997TMININ_4.2
Solar/Wind Helper
0.253
232406W1-004 FULL
Solar/Wind Helper
0.49
233940AF2-379 C
Solar/Wind Helper
0.06
234015AF2-250 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.225
233971AC1-093 C
Solar/Wind Helper
0.346
316044AC1-158 PL1
Solar/Wind Helper
1.252
316450AC1-158 RIC
Solar/Wind Helper
0.334
230430AE1-229_GEN
Solar/Wind Helper
3.26
230415AB2-049 C
Solar/Wind Helper
0.029
228729W2-030 C
Solar/Wind Helper
0.107
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.053
219912AD2-042 GEN
Solar/Wind Helper
0.145
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.111
316170AC1-121 GEN2
Solar/Wind Helper
0.342
959561AF2-247 GEN
Solar/Wind Helper
0.02
20720828JCB_W4-025
Solar/Wind Helper
0.061
20716028EGP_W2-019
Solar/Wind Helper
0.018
20715028HAN_X4-015
Solar/Wind Helper
0.055
219276PARKLANDSO C
Solar/Wind Helper
0.086
20714528FRN_Y2-051
Solar/Wind Helper
0.055
20720528MAN_W1-024
Solar/Wind Helper
0.027
971997AH1-543 GEN
Solar/Wind Harmer
1.86
LAGNLTFEXP_LAGN->PJM
CLTF
14.268
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.432
TVALTFEXP_TVA->PJM
CLTF
7.011
CPLELTFEXP_CPLE->PJM
CLTF
0.567
CBM West 2LTFEXP_CBM-W2->PJM
CBM
108.576
NYPJM->LTFIMP_NY
CLTF
4.628
LGEELTFEXP_LGEE->PJM
CLTF
6.497
WECLTFEXP_WEC->PJM
CLTF
3.686
AG2-052LTFEXP_AG2-052->PJM
LTF
0.231
AH1-155LTFEXP_AH1-155->PJM
LTF
0.346
CBM West 1LTFEXP_CBM-W1->PJM
CBM
137.982
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.984
MECLTFEXP_MEC->PJM
CLTF
15.319
SIGELTFEXP_SIGE->PJM
CLTF
0.486

Details for 01MTZION-AG2-505 TP 138.0 kV Ckt 1 line l/o AP_P2-3_PE-500-014_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01MTZION-AG2-505 TP 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-014_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:148.09 %
Rating:206.0 MVA
Rating Type:B
MVA to Mitigate:305.06
MW Contribution:11.5
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
Adder
11.497
971679AH1-340 GEN
Solar/Wind Harmer
3.052
23750501ELLIOTTS
Solar/Wind Harmer
0.971
23750701CROSSCHOOL
Solar/Wind Helper
3.115
238185AF2-356 C
Solar/Wind Harmer
24.354
LAGNLTFEXP_LAGN->PJM
CLTF
0.311
TVALTFEXP_TVA->PJM
CLTF
0.151
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.61
NYPJM->LTFIMP_NY
CLTF
0.151
LGEELTFEXP_LGEE->PJM
CLTF
0.17
WECLTFEXP_WEC->PJM
CLTF
0.098
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.055
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.007
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.91
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.634
MECLTFEXP_MEC->PJM
CLTF
0.397
SIGELTFEXP_SIGE->PJM
CLTF
0.013

Details for 01MTZION-AG2-505 TP 138.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT19_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01MTZION-AG2-505 TP 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT19_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:144.6 %
Rating:206.0 MVA
Rating Type:B
MVA to Mitigate:297.87
MW Contribution:11.62
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
Adder
11.619
971679AH1-340 GEN
Solar/Wind Harmer
3.055
23750501ELLIOTTS
Solar/Wind Harmer
0.972
23750701CROSSCHOOL
Solar/Wind Helper
3.114
964991AG1-363 GEN
Solar/Wind Helper
1.776
238185AF2-356 C
Solar/Wind Harmer
24.357
LAGNLTFEXP_LAGN->PJM
CLTF
0.322
TVALTFEXP_TVA->PJM
CLTF
0.157
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.683
NYPJM->LTFIMP_NY
CLTF
0.148
LGEELTFEXP_LGEE->PJM
CLTF
0.174
WECLTFEXP_WEC->PJM
CLTF
0.1
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.051
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.005
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.989
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.654
MECLTFEXP_MEC->PJM
CLTF
0.406
SIGELTFEXP_SIGE->PJM
CLTF
0.013

Details for 01MTZION-AG2-505 TP 138.0 kV Ckt 1 line l/o AP_P1-2_PE-500-004_SRT-SL-2


Base Case Flowgate

Area:AP
Facility Description:
01MTZION-AG2-505 TP 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-500-004_SRT-SL-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:135.36 %
Rating:206.0 MVA
Rating Type:B
MVA to Mitigate:278.83
MW Contribution:11.5
Bus #Bus NameTypeMW Contribution
23750701CROSSCHOOL
Solar/Wind Helper
3.115
970935AG2-582 GEN
Adder
11.497
238185AF2-356 C
Solar/Wind Harmer
0.048
971679AH1-340 GEN
Solar/Wind Harmer
2.129
23750501ELLIOTTS
Solar/Wind Harmer
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.311
TVALTFEXP_TVA->PJM
CLTF
0.151
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.61
NYPJM->LTFIMP_NY
CLTF
0.151
LGEELTFEXP_LGEE->PJM
CLTF
0.17
WECLTFEXP_WEC->PJM
CLTF
0.098
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.055
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.007
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.91
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.634
MECLTFEXP_MEC->PJM
CLTF
0.397
SIGELTFEXP_SIGE->PJM
CLTF
0.013

Details for 01MTZION-AG2-505 TP 138.0 kV Ckt 1 line l/o AP_P1-2_PE-500-004_SRT-SL-1


Base Case Flowgate

Area:AP
Facility Description:
01MTZION-AG2-505 TP 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-500-004_SRT-SL-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:131.89 %
Rating:206.0 MVA
Rating Type:B
MVA to Mitigate:271.69
MW Contribution:11.62
Bus #Bus NameTypeMW Contribution
23750701CROSSCHOOL
Solar/Wind Helper
3.114
964991AG1-363 GEN
Solar/Wind Helper
1.776
970935AG2-582 GEN
Adder
11.619
238185AF2-356 C
Solar/Wind Harmer
0.048
971679AH1-340 GEN
Solar/Wind Harmer
2.131
23750501ELLIOTTS
Solar/Wind Harmer
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.322
TVALTFEXP_TVA->PJM
CLTF
0.157
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.683
NYPJM->LTFIMP_NY
CLTF
0.148
LGEELTFEXP_LGEE->PJM
CLTF
0.174
WECLTFEXP_WEC->PJM
CLTF
0.1
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.051
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.005
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.989
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.654
MECLTFEXP_MEC->PJM
CLTF
0.406
SIGELTFEXP_SIGE->PJM
CLTF
0.013

Details for 01MTZION-AG2-505 TP 138.0 kV Ckt 1 line l/o AP_P2-2_WP-500-DRT9_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01MTZION-AG2-505 TP 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-500-DRT9_SRT-SL
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:102.74 %
Rating:206.0 MVA
Rating Type:B
MVA to Mitigate:211.65
MW Contribution:11.79
Bus #Bus NameTypeMW Contribution
971679AH1-340 GEN
Solar/Wind Harmer
3.12
23750501ELLIOTTS
Solar/Wind Harmer
0.95
23750701CROSSCHOOL
Solar/Wind Helper
2.993
970935AG2-582 GEN
Adder
11.79
238185AF2-356 C
Solar/Wind Harmer
24.755
23751201ROTHROCK
Solar/Wind Harmer
0.889
LAGNLTFEXP_LAGN->PJM
CLTF
0.368
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.186
TVALTFEXP_TVA->PJM
CLTF
0.183
CPLELTFEXP_CPLE->PJM
CLTF
0.005
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.779
NYPJM->LTFIMP_NY
CLTF
0.191
LGEELTFEXP_LGEE->PJM
CLTF
0.166
WECLTFEXP_WEC->PJM
CLTF
0.093
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.55
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.726
MECLTFEXP_MEC->PJM
CLTF
0.388
SIGELTFEXP_SIGE->PJM
CLTF
0.012

Details for 01MTZION-AG2-505 TP 138.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT22_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01MTZION-AG2-505 TP 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT22_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.73 %
Rating:206.0 MVA
Rating Type:B
MVA to Mitigate:211.63
MW Contribution:11.79
Bus #Bus NameTypeMW Contribution
23750701CROSSCHOOL
Solar/Wind Helper
2.993
971679AH1-340 GEN
Solar/Wind Harmer
3.12
23750501ELLIOTTS
Solar/Wind Harmer
0.95
970935AG2-582 GEN
Adder
11.79
238185AF2-356 C
Solar/Wind Harmer
24.755
23751201ROTHROCK
Solar/Wind Harmer
0.889
LAGNLTFEXP_LAGN->PJM
CLTF
0.368
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.186
TVALTFEXP_TVA->PJM
CLTF
0.183
CPLELTFEXP_CPLE->PJM
CLTF
0.005
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.779
NYPJM->LTFIMP_NY
CLTF
0.191
LGEELTFEXP_LGEE->PJM
CLTF
0.166
WECLTFEXP_WEC->PJM
CLTF
0.093
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.55
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.726
MECLTFEXP_MEC->PJM
CLTF
0.388
SIGELTFEXP_SIGE->PJM
CLTF
0.012

Details for 01MTZION-AG2-505 TP 138.0 kV Ckt 1 line l/o AP_P2-3_MP-138-206_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01MTZION-AG2-505 TP 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-138-206_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.3 %
Rating:206.0 MVA
Rating Type:B
MVA to Mitigate:208.69
MW Contribution:11.83
Bus #Bus NameTypeMW Contribution
23750701CROSSCHOOL
Solar/Wind Helper
2.993
971679AH1-340 GEN
Solar/Wind Harmer
3.121
23750501ELLIOTTS
Solar/Wind Harmer
0.95
970935AG2-582 GEN
Adder
11.829
238185AF2-356 C
Solar/Wind Harmer
24.756
23751201ROTHROCK
Solar/Wind Harmer
0.889
LAGNLTFEXP_LAGN->PJM
CLTF
0.372
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.192
TVALTFEXP_TVA->PJM
CLTF
0.184
CPLELTFEXP_CPLE->PJM
CLTF
0.006
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.802
NYPJM->LTFIMP_NY
CLTF
0.19
LGEELTFEXP_LGEE->PJM
CLTF
0.167
WECLTFEXP_WEC->PJM
CLTF
0.093
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.575
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.733
MECLTFEXP_MEC->PJM
CLTF
0.39
SIGELTFEXP_SIGE->PJM
CLTF
0.012

Details for 01SHINNS-01PRNTY 138.0 kV Ckt 1 line l/o AP_P2-3_MP-500-012_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01SHINNS-01PRNTY 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-012_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.45 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:296.0
MW Contribution:82.7
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
Adder
82.703
237068AA2-119 GEN
50/50
18.76
LAGNLTFEXP_LAGN->PJM
CLTF
0.877
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.419
TVALTFEXP_TVA->PJM
CLTF
0.437
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.635
NYPJM->LTFIMP_NY
CLTF
0.335
LGEELTFEXP_LGEE->PJM
CLTF
0.404
WECLTFEXP_WEC->PJM
CLTF
0.218
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.11
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.744
MECLTFEXP_MEC->PJM
CLTF
0.917
SIGELTFEXP_SIGE->PJM
CLTF
0.03

Details for 01SHINNS-01PRNTY 138.0 kV Ckt 1 line l/o AP_P1-2_MP-500-008A_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01SHINNS-01PRNTY 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.96 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:292.01
MW Contribution:82.91
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
Adder
82.907
237068AA2-119 GEN
50/50
18.89
LAGNLTFEXP_LAGN->PJM
CLTF
0.86
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.494
TVALTFEXP_TVA->PJM
CLTF
0.43
CPLELTFEXP_CPLE->PJM
CLTF
0.04
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.409
NYPJM->LTFIMP_NY
CLTF
0.34
LGEELTFEXP_LGEE->PJM
CLTF
0.387
WECLTFEXP_WEC->PJM
CLTF
0.206
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.523
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.706
MECLTFEXP_MEC->PJM
CLTF
0.872
SIGELTFEXP_SIGE->PJM
CLTF
0.029

Details for 01SHINNS-01PRNTY 138.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT4_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01SHINNS-01PRNTY 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT4_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.95 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:291.99
MW Contribution:82.91
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
Adder
82.907
237068AA2-119 GEN
50/50
18.89
LAGNLTFEXP_LAGN->PJM
CLTF
0.86
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.494
TVALTFEXP_TVA->PJM
CLTF
0.43
CPLELTFEXP_CPLE->PJM
CLTF
0.04
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.409
NYPJM->LTFIMP_NY
CLTF
0.34
LGEELTFEXP_LGEE->PJM
CLTF
0.387
WECLTFEXP_WEC->PJM
CLTF
0.206
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.523
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.706
MECLTFEXP_MEC->PJM
CLTF
0.872
SIGELTFEXP_SIGE->PJM
CLTF
0.029

Details for 01SHINNS-01PRNTY 138.0 kV Ckt 1 line l/o AP_P2-3_MP-500-018_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01SHINNS-01PRNTY 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-018_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.95 %
Rating:268.0 MVA
Rating Type:B
MVA to Mitigate:291.99
MW Contribution:82.91
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
Adder
82.907
237068AA2-119 GEN
50/50
18.89
LAGNLTFEXP_LAGN->PJM
CLTF
0.86
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.494
TVALTFEXP_TVA->PJM
CLTF
0.43
CPLELTFEXP_CPLE->PJM
CLTF
0.04
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.409
NYPJM->LTFIMP_NY
CLTF
0.34
LGEELTFEXP_LGEE->PJM
CLTF
0.387
WECLTFEXP_WEC->PJM
CLTF
0.206
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.523
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.706
MECLTFEXP_MEC->PJM
CLTF
0.872
SIGELTFEXP_SIGE->PJM
CLTF
0.029

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-012_SRT-A


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-012_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.49 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4985.98
MW Contribution:239.41
Bus #Bus NameTypeMW Contribution
972239AH1-704 GEN
50/50
3.102
962771AG1-126 GEN
Solar/Wind Harmer
40.965
270459AD2-067 GEN
Solar/Wind Harmer
10.453
961821AG1-024 GEN
Solar/Wind Harmer
10.613
270054AF2-122 C O1
Solar/Wind Harmer
4.071
270284AF1-227 GEN1
Solar/Wind Harmer
6.912
270286AF1-227 GEN2
Solar/Wind Harmer
2.557
270287AF1-227 GEN3
Solar/Wind Harmer
2.557
270520AE2-214 GEN
Solar/Wind Harmer
7.382
253383AE2-342_GEN
Solar/Wind Harmer
1.062
241973AD2-163_GEN1
Solar/Wind Harmer
2.37
940611AE2-048 GEN
Solar/Wind Harmer
26.074
941391AE2-136 GEN
Solar/Wind Harmer
13.511
270578AF1-285 GEN2
Solar/Wind Harmer
0.55
943861AF1-054 GEN
Solar/Wind Harmer
4.552
943851AF1-053 GEN
Solar/Wind Harmer
2.2
945631AF1-228 GEN
Solar/Wind Harmer
5.537
270156DARBY CT1
Adder
10.556
270157DARBY CT2
Adder
10.53
270158DARBY CT3
Adder
10.362
270302AB2-170 GEN
Solar/Wind Harmer
9.805
270317AD1-130_GEN
Solar/Wind Harmer
3.759
970689AG2-444 GEN
Solar/Wind Harmer
19.055
270432AC2-029 GEN
Solar/Wind Harmer
8.138
958581AF2-149 GEN
Solar/Wind Harmer
4.968
970179AG2-119 GEN
Solar/Wind Harmer
9.26
270269AC2-059
Solar/Wind Harmer
10.704
241972AD1-140 GEN
Solar/Wind Harmer
5.084
971567AH1-282 GEN
Solar/Wind Harmer
16.984
966831AG1-554 GEN
Solar/Wind Harmer
1.34
971989AH1-539 GEN
Solar/Wind Harmer
14.49
270340AC2-060 GEN
Solar/Wind Harmer
3.371
957201AF2-014 GEN
Solar/Wind Harmer
5.033
270435AC2-044 GEN
Solar/Wind Harmer
2.219
970879AG2-548 GEN
Solar/Wind Harmer
4.763
247607V1-011 GEN
Solar/Wind Harmer
4.359
253372AE2-315 SEC3
Adder
2.086
253372AE2-315 SEC3
Adder
2.086
965051AG1-369 GEN
Solar/Wind Harmer
5.494
25306009OHH W.
Adder
3.166
270297AD1-101 GEN
Solar/Wind Harmer
3.056
965041AG1-368 GEN
Solar/Wind Harmer
10.974
253349AC2-067 GEN
Solar/Wind Harmer
5.466
253400AC2-068 GEN
Solar/Wind Harmer
2.198
963791AG1-232 GEN
Solar/Wind Harmer
14.679
270071AF1-092 GEN
Solar/Wind Harmer
16.242
24729505KEY G4
Adder
7.02
945641AF1-229 GEN
Solar/Wind Harmer
3.923
270024AE2-089 GEN
Solar/Wind Harmer
5.065
958711AF2-162 GEN
Solar/Wind Harmer
1.089
965101AG1-375 GEN
Solar/Wind Harmer
10.752
961761AG1-017 GEN
Solar/Wind Harmer
0.46
270543AE2-219 C
Solar/Wind Harmer
5.494
971029AG2-637 GEN
Solar/Wind Harmer
16.089
971673AH1-337 GEN
Solar/Wind Harmer
4.934
25196408WSDLE3
Adder
9.412
25196308WSDLE2
Adder
9.33
25196208WSDLE1
Adder
9.306
25196708WSDLE6
Adder
9.283
25196508WSDLE4
Adder
9.049
25196108MFTGT2
Adder
1.608
25196108MFTGT2
Adder
1.494
274775LINCOLN ;6U
Adder
8.792
274776LINCOLN ;7U
Adder
8.792
274777LINCOLN ;8U
Adder
8.792
274814UNIV PK N;0U
Adder
5.256
274807UNIV PK N;3U
Adder
5.245
274805UNIV PK N;1U
Adder
5.222
274811UNIV PK N;7U
Adder
5.21
972037AH1-567 GEN1
Adder
0.19
274827FISK ;RP
Adder
8.047
972227AH1-698 GEN1
Adder
2.704
274687WILL CNTY;4U
Adder
28.893
274687WILL CNTY;4U
Adder
28.893
274675JOLIET 29;7U
Adder
31.706
274675JOLIET 29;7U
Adder
30.574
274731ELWOOD EC;2P
Adder
16.983
274733ELWOOD EC;3P
Adder
16.983
274735ELWOOD EC;4P
Adder
16.983
274728ELWOOD EC;5P
Adder
16.983
238109AE1-109 GEN2
Solar/Wind Helper
0.121
238110AE1-109 GEN3
Solar/Wind Helper
0.121
238152AF2-075_GEN
Solar/Wind Helper
0.789
23546401DTGZ2-030
Solar/Wind Helper
0.099
238126S14_GEN_1
Solar/Wind Helper
0.867
238208AF1-136 C
Solar/Wind Helper
0.236
237085AD2-009_GEN
Solar/Wind Helper
1.767
3138216PACIFIC
Solar/Wind Helper
0.049
316411AF1-147_GEN1
Solar/Wind Helper
0.978
316415AF1-147_GEN2
Solar/Wind Helper
0.978
3141426STAFORD
Solar/Wind Helper
0.058
316164AC1-076 GEN
Solar/Wind Helper
1.225
23750501ELLIOTTS
Solar/Wind Helper
0.629
959381AF2-229 GEN
Solar/Wind Helper
0.367
960921AF2-383 GEN
Solar/Wind Helper
0.185
205943AE1-185 GEN
Solar/Wind Helper
0.518
205932AD2-116_GEN
Solar/Wind Helper
0.518
205956AE1-196_GEN
Solar/Wind Helper
0.518
233935AB2-179 C
Solar/Wind Helper
1.29
232436AB1-176 C
Solar/Wind Helper
0.045
233923SMA
Solar/Wind Helper
0.974
233990AG1-397 GEN
Solar/Wind Helper
0.031
232432Z2-076 GEN
Solar/Wind Helper
0.068
234033AF1-007_GEN
Solar/Wind Helper
7.137
964001AG1-254 GEN
Solar/Wind Helper
0.966
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.116
203975AE1-071-GEN
Solar/Wind Helper
2.53
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.081
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.292
219620RIDERU C
Solar/Wind Helper
0.001
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
20674828DL_W4-046
Solar/Wind Helper
0.008
207484AF2-139 C O1
Solar/Wind Helper
0.084
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.136
20675128HRM_W1-127
Solar/Wind Helper
0.029
209116AE2-175 GEN
Solar/Wind Helper
1.768
945581AF1-223 GEN
Solar/Wind Harmer
0.763
270119AB2-067 GEN1
50/50
7.033
270120AB2-067 GEN2
50/50
7.033
24318905MLG2
50/50
7.475
270471AD2-092_GEN
Solar/Wind Harmer
4.529
946101AF1-275 GEN
Solar/Wind Harmer
1.842
938701AE1-092 GEN
Solar/Wind Harmer
24.483
270224U2-072_GEN2
Solar/Wind Harmer
2.339
270227U2-072_GEN3
Solar/Wind Harmer
2.339
270228U2-072_GEN4
Solar/Wind Harmer
2.339
270231U2-072_GEN5
Solar/Wind Harmer
2.339
942861AE2-305 GEN
Solar/Wind Harmer
9.223
964601AG1-323 GEN
Solar/Wind Harmer
3.753
964601AG1-323 GEN
Solar/Wind Harmer
1.746
972269AH1-719 GEN
Adder
2.7
970077AG2-063 GEN
Solar/Wind Harmer
6.332
972159AH1-661 GEN
Adder
1.166
270518AE2-148 GEN
Solar/Wind Harmer
14.068
971199AH1-059 GEN
Solar/Wind Harmer
4.644
241960AC2-195 GEN
Solar/Wind Harmer
3.219
971201AH1-060 GEN
Solar/Wind Harmer
2.296
253378AE2-206_GEN
Solar/Wind Harmer
4.086
276820AF1-078_GEN
Solar/Wind Harmer
1.815
971231AH1-075 GEN
Solar/Wind Harmer
0.905
25326509SID D
Adder
1.48
25326109MON D
Adder
1.461
246938BC-WTG3
Solar/Wind Harmer
4.418
246937BC-WTG2
Solar/Wind Harmer
4.343
970879AG2-548 GEN
Solar/Wind Harmer
6.827
971073AG2-665 GEN
Solar/Wind Harmer
6.827
971073AG2-665 GEN
Solar/Wind Harmer
4.763
25322209TAIT E
Adder
10.77
25322209TAIT E
Adder
10.528
270007AE1-245 C
Solar/Wind Harmer
6.539
942801AE2-298 GEN
Solar/Wind Harmer
1.667
253370AE2-315 SEC1
Adder
2.206
970611AG2-400 GEN
Solar/Wind Harmer
10.972
253394AE2-221_GEN
Solar/Wind Harmer
4.954
253398AE2-221_GEN2
Solar/Wind Harmer
4.954
253317AC1-085 GEN4
Solar/Wind Harmer
9.07
971677AH1-339 GEN
Solar/Wind Harmer
8.643
942221AE2-234 GEN
Solar/Wind Harmer
0.79
944541AF1-119 GEN
Solar/Wind Harmer
4.511
960971AF2-388 GEN
Solar/Wind Harmer
11.771
247621Y3-024
Adder
0.259
270201AC2-176 GEN
Solar/Wind Harmer
5.522
970883AG2-550 GEN
Solar/Wind Harmer
10.73
970885AG2-551 GEN
Solar/Wind Harmer
2.495
247620Y3-023
Adder
0.494
24318805MLG1
50/50
10.022
23559001PLEAS1
50/50
5.443
270051AF1-062 GEN
50/50
11.999
970153AG2-106 GEN
Solar/Wind Harmer
17.863
961921AG1-034 GEN
Solar/Wind Harmer
15.919
241955AC1-078 GEN
Solar/Wind Harmer
8.948
241974AD2-163_GEN2
Solar/Wind Harmer
2.37
942051AE2-217 GEN
Solar/Wind Harmer
21.374
942871AE2-306 GEN
Solar/Wind Harmer
1.073
270391AF1-285 GEN3
Solar/Wind Harmer
0.55
960801AF2-371 GEN
Solar/Wind Harmer
2.991
964871AG1-351 GEN
Solar/Wind Harmer
2.065
970605AG2-385 GEN
Solar/Wind Harmer
6.332
270485AE1-090_GEN
Solar/Wind Harmer
0.709
270512AE1-227 GEN2
Solar/Wind Harmer
2.455
24721905FLATG4
Adder
23.506
253338AC1-165 GEN
Solar/Wind Harmer
1.256
253333AC1-068 GEN
Solar/Wind Harmer
1.211
970065AG2-057 GEN
Solar/Wind Harmer
1.148
270273AD2-016 GEN
Solar/Wind Harmer
3.061
972173AH1-669 GEN
Solar/Wind Harmer
5.721
270377AD1-106 GEN
Solar/Wind Harmer
6.988
270588AE1-091_GEN
Solar/Wind Harmer
12.311
270291AC1-194 GEN
Solar/Wind Harmer
11.854
253415AE1-040 GEN
Solar/Wind Harmer
1.258
961961AG1-039 GEN
Solar/Wind Harmer
3.188
270491AE1-102 GEN2
Solar/Wind Harmer
1.443
970217AG2-149 GEN
Solar/Wind Harmer
35.355
958091AF2-103 GEN
Solar/Wind Harmer
0.178
253303V4-073 C
Solar/Wind Harmer
0.128
253370AE2-315 SEC1
Adder
2.206
253371AE2-315 SEC2
Adder
2.086
270191TR4_S_V150
Solar/Wind Harmer
3.3
270247TR4_N_V136
Solar/Wind Harmer
0.936
959331AF2-224 GEN
Solar/Wind Harmer
10.972
965021AG1-366 GEN
Solar/Wind Harmer
2.552
270258AD1-119 GEN
Solar/Wind Harmer
3.051
253406AD2-031_GEN
Solar/Wind Harmer
1.398
270044AE2-322 C
Solar/Wind Harmer
1.435
270404AC1-167 GEN
Solar/Wind Harmer
1.194
957541AF2-048 GEN
Solar/Wind Harmer
1.725
270043AE2-236 GEN
Solar/Wind Harmer
5.98
944531AF1-118 GEN
Solar/Wind Harmer
37.943
253316AC1-085 GEN3
Solar/Wind Harmer
9.07
253433AC1-085 GEN1
Solar/Wind Harmer
5.758
946181AF1-283 GEN
Solar/Wind Harmer
14.077
970031AG2-029 GEN
Solar/Wind Harmer
32.394
971617AH1-308 GEN
Solar/Wind Harmer
6.274
270541AE2-072 C
Solar/Wind Harmer
4.881
971191AH1-055 GEN
Solar/Wind Harmer
23.635
962031AG1-047 GEN
Solar/Wind Harmer
3.246
957741AF2-068 GEN
Solar/Wind Harmer
16.111
25196608WSDLE5
Adder
9.143
24642205MAYFLWER
Adder
0.678
25194608D.CRK4
Adder
1.752
247604X1-042
Adder
0.444
23906502RICHG2&3
Adder
1.272
25196008MFTGT1
Adder
1.413
274752CRETE EC ;2U
Adder
8.598
274753CRETE EC ;3U
Adder
8.598
274724RIVER EC ;11
Adder
18.459
274772LINCOLN ;3U
Adder
8.792
274802UNIV PARK;5U
Adder
6.05
274826FISK ;BP
Adder
11.355
274800UNIV PARK;3U
Adder
6.045
972038AH1-567 GEN2
Adder
0.378
972228AH1-698 GEN2
Adder
3.84
274676JOLIET 29;8U
Adder
30.573
274729ELWOOD EC;1P
Adder
16.983
274730ELWOOD EC;6P
Adder
16.983
964991AG1-363 GEN
Solar/Wind Helper
5.557
316097T157 G90
Solar/Wind Helper
1.705
23750701CROSSCHOOL
Solar/Wind Helper
1.586
238148AE2-230_GEN2
Solar/Wind Helper
0.555
238127S14_GEN_2
Solar/Wind Helper
0.867
238118U2-030_1
Solar/Wind Helper
0.356
237080AD1-060 GEN
Solar/Wind Helper
0.367
237038AE2-054 C
Solar/Wind Helper
0.292
235062AE1-101 C1
Solar/Wind Helper
1.776
23779801AA1-109
Solar/Wind Helper
0.207
316006AB2-029 C
Solar/Wind Helper
0.13
223401AF1-299 GEN
Solar/Wind Helper
0.387
316045AC1-158 PL2
Solar/Wind Helper
4.618
316254AC1-120 GEN1
Solar/Wind Helper
1.184
237048AF1-022 C
Solar/Wind Helper
0.173
966131AG1-482 GEN
Solar/Wind Helper
0.079
233930AB2-032 GEN
Solar/Wind Helper
0.387
233915AB1-141 GEN
Solar/Wind Helper
0.511
232422X3-066 FULL
Solar/Wind Helper
0.116
233964AF2-378 GEN
Solar/Wind Helper
0.042
232426Y1-080 FULL
Solar/Wind Helper
0.039
233998TM1NIN_3.36
Solar/Wind Helper
0.266
232404W1-003 C
Solar/Wind Helper
0.516
232428Y3-058 C
Solar/Wind Helper
0.344
3147666LOUISA
Solar/Wind Helper
0.958
232434Z2-077 GEN
Solar/Wind Helper
0.129
270166AC1-044 GEN3
50/50
7.033
23559101PLEAS2
50/50
5.443
270122AB2-093 CT
50/50
4.116
962761AG1-125 GEN
Solar/Wind Harmer
40.965
970149AG2-104 GEN
Solar/Wind Harmer
50.592
970155AG2-107 GEN
Solar/Wind Harmer
17.863
270349AD2-093_GEN
Solar/Wind Harmer
4.529
270223U2-072_GEN1
Solar/Wind Harmer
2.339
270578AF1-285 GEN2
Solar/Wind Harmer
1.43
270391AF1-285 GEN3
Solar/Wind Harmer
1.43
270159DARBY CT4
Adder
10.388
971995AH1-542 GEN
Solar/Wind Harmer
12.974
970593AG2-378 GEN
Solar/Wind Harmer
2.345
270462AD2-086
Solar/Wind Harmer
8.157
270510AE1-227 GEN1
Solar/Wind Harmer
2.893
24721705FLATG2
Adder
23.506
253343AC1-166 GEN
Solar/Wind Harmer
1.256
253325AC1-069 GEN
Solar/Wind Harmer
1.211
241813AF1-122_GEN
Solar/Wind Harmer
7.346
270263AC1-001 GEN
Solar/Wind Harmer
1.187
241847AF2-150_GEN
Solar/Wind Harmer
4.622
246936BC-WTG1
Solar/Wind Harmer
4.343
270489AE1-102 GEN1
Solar/Wind Harmer
1.443
965421AG1-410 GEN
Solar/Wind Harmer
33.256
970515AG2-329 GEN
Solar/Wind Harmer
16.033
25326309TAIT D
Adder
1.21
960071AF2-298 GEN
Solar/Wind Harmer
5.501
253370AE2-315 SEC1
Adder
2.206
253371AE2-315 SEC2
Adder
2.086
247521TR3_G114
Solar/Wind Harmer
3.699
270246TR4_N_V150
Solar/Wind Harmer
0.936
247522W1-056 GEN
Solar/Wind Harmer
2.477
24695305TIMB G C
Solar/Wind Harmer
6.051
965011AG1-365 GEN
Solar/Wind Harmer
10.972
927014AC1-188 GEN
Solar/Wind Harmer
1.729
944231AF1-091 GEN
Solar/Wind Harmer
4.078
253432AC1-085 GEN2
Solar/Wind Harmer
0.29
946171AF1-282 GEN
Solar/Wind Harmer
10.828
270063AE2-323 C
Solar/Wind Harmer
2.376
965651AG1-433 GEN
Solar/Wind Harmer
5.885
958861AF2-177 GEN
Solar/Wind Harmer
11.752
247536S-71 GEN
Solar/Wind Harmer
4.346
960001AF2-291 GEN
Solar/Wind Harmer
3.244
945371AF1-202 GEN
Solar/Wind Harmer
7.479
24639705ELKHART HY
Adder
0.164
25194608D.CRK4
Adder
1.752
25196808ZIMRHP
Adder
80.188
23906502RICHG2&3
Adder
1.272
972301AH1-735 GEN
Adder
6.357
23906402RICHG1
Adder
1.271
25196008MFTGT1
Adder
1.459
274751CRETE EC ;1U
Adder
8.598
274754CRETE EC ;4U
Adder
8.598
274723RIVER EC ;12
Adder
18.677
274773LINCOLN ;4U
Adder
8.792
274774LINCOLN ;5U
Adder
8.792
274812UNIV PK N;8U
Adder
5.21
23920202STRYCT
Adder
1.444
274801UNIV PARK;4U
Adder
6.045
274676JOLIET 29;8U
Adder
31.706
274732ELWOOD EC;7P
Adder
2.004
23583801GRNGAP
Solar/Wind Helper
6.365
316095T157 G97
Solar/Wind Helper
1.705
238108AE1-109 GEN1
Solar/Wind Helper
0.121
238185AF2-356 C
Solar/Wind Helper
2.767
238147AE2-230_GEN1
Solar/Wind Helper
0.552
238149AF1-291A_GEN
Solar/Wind Helper
0.158
237061AD1-155 GEN
Solar/Wind Helper
0.06
235054AD2-180 GEN
Solar/Wind Helper
2.111
235531U2-073 GEN
Solar/Wind Helper
3.439
238117U2-030
Solar/Wind Helper
0.356
238221AF1-254 C O1
Solar/Wind Helper
0.295
235067AD1-061 GEN
Solar/Wind Helper
0.532
3141196NOKESVL
Solar/Wind Helper
1.141
23751201ROTHROCK
Solar/Wind Helper
0.819
237030AB1-096 C
Solar/Wind Helper
0.075
23562501BACKB
Solar/Wind Helper
0.997
226910AB2-157 C
Solar/Wind Helper
0.015
227287AC2-120 GEN
Solar/Wind Helper
0.375
223402AF1-300 C
Solar/Wind Helper
0.387
316044AC1-158 PL1
Solar/Wind Helper
1.443
316450AC1-158 RIC
Solar/Wind Helper
0.385
316170AC1-121 GEN2
Solar/Wind Helper
0.395
23751101LEADS_P59
Solar/Wind Helper
1.316
205917AD1-020 ES
Solar/Wind Helper
0.379
3132273ORANGE
Solar/Wind Helper
0.049
233918AB1-142 GEN
Solar/Wind Helper
0.511
233982AB2-133 GEN
Solar/Wind Helper
0.364
233994AC2-023 GEN
Solar/Wind Helper
0.977
233996TM1833_GEN
Solar/Wind Helper
0.266
233997TMININ_4.2
Solar/Wind Helper
0.266
232406W1-004 FULL
Solar/Wind Helper
0.516
3147666LOUISA
Solar/Wind Helper
0.551
233954AC2-188 GEN
Solar/Wind Helper
0.236
233950AC2-186 GEN
Solar/Wind Helper
0.118
233972AC1-094 C
Solar/Wind Helper
0.307
316192AB2-158 GEN
Solar/Wind Helper
1.608
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.232
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.061
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.132
20720728JCB_W1-129
Solar/Wind Helper
0.057
207445AB1-138_GEN
Solar/Wind Helper
0.105
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.078
207454AA2-184 E
Solar/Wind Helper
0.311
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.497
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.137
207518AF1-320_GEN
Solar/Wind Helper
1.568
20671928W4-073
Solar/Wind Helper
0.089
20675828AU_W4-064
Solar/Wind Helper
0.029
964611AG1-324 GEN
Solar/Wind Harmer
1.264
964611AG1-324 GEN
Solar/Wind Harmer
0.561
25194408D.CRK1
Adder
8.061
25194508D.CRK3
Adder
1.507
24728805RICHG1
Adder
4.003
24728905RICHG2
Adder
4.003
970935AG2-582 GEN
Adder
239.406
274770LINCOLN ;1U
Adder
8.792
274771LINCOLN ;2U
Adder
8.792
274808UNIV PK N;4U
Adder
5.188
274803UNIV PARK;6U
Adder
6.05
972259AH1-714 GEN
Adder
19.76
238175AF1-290_GEN
Solar/Wind Helper
0.168
238169AE2-226 GEN1
Solar/Wind Helper
0.772
238170AE2-226 GEN2
Solar/Wind Helper
0.772
238120AE2-309 GEN
Solar/Wind Helper
0.552
23585401KL_K28_T16
Solar/Wind Helper
1.529
235020AA1-095 C
Solar/Wind Helper
0.057
23777901MDS_W4-102
Solar/Wind Helper
0.191
237034AC2-136 C
Solar/Wind Helper
0.244
237002AB1-128_GEN
Solar/Wind Helper
0.475
235063AE1-101 C2
Solar/Wind Helper
1.776
237001AB1-127_GEN
Solar/Wind Helper
0.473
23777801MSM_W1-116
Solar/Wind Helper
0.122
237025AB1-124 C
Solar/Wind Helper
0.175
237006AB1-125 GEN
Solar/Wind Helper
0.131
226929AD2-058 GEN
Solar/Wind Helper
0.108
315651AD1-115 GEN
Solar/Wind Helper
0.876
316447AC1-158 HLD
Solar/Wind Helper
3.175
205916AD1-020 GEN
Solar/Wind Helper
1.761
20390526W1-045 C
Solar/Wind Helper
0.36
208835TUHI V3-051
Solar/Wind Helper
0.025
208835TUHI V3-051
Solar/Wind Helper
0.025
3132123MT JACKSON
Solar/Wind Helper
0.764
233987AB2-037 GEN
Solar/Wind Helper
2.381
233933AB2-153 GEN
Solar/Wind Helper
0.236
232424Y1-079 C
Solar/Wind Helper
0.118
233944AB2-135 GEN
Solar/Wind Helper
0.598
233946AB2-136 GEN
Solar/Wind Helper
0.577
234036AF2-325 C
Solar/Wind Helper
0.043
233901CHERRYDALE C
Solar/Wind Helper
0.236
232408W1-005 C
Solar/Wind Helper
0.516
232410W1-006 C
Solar/Wind Helper
0.516
233939AC1-091 C
Solar/Wind Helper
0.356
233970AC1-092 C
Solar/Wind Helper
0.356
966001AG1-469 GEN
Solar/Wind Helper
0.255
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.041
219921AF1-264
Solar/Wind Helper
0.052
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.083
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.168
20674928WA_W3-044
Solar/Wind Helper
0.098
20676228FRD_X1-012
Solar/Wind Helper
0.091
964851AG1-348 GEN
Solar/Wind Helper
0.081
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.044
211065PSPA IPP
Solar/Wind Helper
0.15
211065PSPA IPP
Solar/Wind Helper
0.15
233940AF2-379 C
Solar/Wind Helper
0.063
234015AF2-250 C
Solar/Wind Helper
0.039
233952AC2-187 GEN
Solar/Wind Helper
0.236
233971AC1-093 C
Solar/Wind Helper
0.363
230430AE1-229_GEN
Solar/Wind Helper
3.409
230415AB2-049 C
Solar/Wind Helper
0.031
228729W2-030 C
Solar/Wind Helper
0.112
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.151
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.064
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
219276PARKLANDSO C
Solar/Wind Helper
0.09
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
966881AG1-559 GEN
Solar/Wind Helper
0.312
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
LAGNLTFEXP_LAGN->PJM
CLTF
14.521
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.32
TVALTFEXP_TVA->PJM
CLTF
7.111
CBM West 2LTFEXP_CBM-W2->PJM
CBM
111.893
NYPJM->LTFIMP_NY
CLTF
4.554
LGEELTFEXP_LGEE->PJM
CLTF
6.753
WECLTFEXP_WEC->PJM
CLTF
3.866
AG2-052LTFEXP_AG2-052->PJM
LTF
0.243
AH1-155LTFEXP_AH1-155->PJM
LTF
0.364
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.579
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.544
MECLTFEXP_MEC->PJM
CLTF
15.979
SIGELTFEXP_SIGE->PJM
CLTF
0.506

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P1-2_MP-500-008A_SRT-SL


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:125.38 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4754.33
MW Contribution:242.4
Bus #Bus NameTypeMW Contribution
24318805MLG1
50/50
9.842
23559001PLEAS1
50/50
5.385
270051AF1-062 GEN
50/50
11.434
970153AG2-106 GEN
Solar/Wind Harmer
21.245
961921AG1-034 GEN
Solar/Wind Harmer
7.364
241955AC1-078 GEN
Solar/Wind Harmer
0.007
241974AD2-163_GEN2
Solar/Wind Harmer
0.006
942051AE2-217 GEN
Solar/Wind Harmer
14.169
24721905FLATG4
Adder
22.865
970605AG2-385 GEN
Solar/Wind Harmer
4.731
270391AF1-285 GEN3
Solar/Wind Harmer
0.518
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.012
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270273AD2-016 GEN
Solar/Wind Harmer
0.792
972173AH1-669 GEN
Solar/Wind Harmer
3.811
270512AE1-227 GEN2
Solar/Wind Harmer
1.904
270291AC1-194 GEN
Solar/Wind Harmer
5.884
253415AE1-040 GEN
Solar/Wind Harmer
0.003
970065AG2-057 GEN
Solar/Wind Harmer
0.735
253370AE2-315 SEC1
Adder
2.103
253371AE2-315 SEC2
Adder
1.989
970191AG2-125 GEN
Solar/Wind Harmer
1.876
253406AD2-031_GEN
Solar/Wind Harmer
0.543
270491AE1-102 GEN2
Solar/Wind Harmer
0.945
270377AD1-106 GEN
Solar/Wind Harmer
2.761
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.047
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.394
959331AF2-224 GEN
Solar/Wind Harmer
5.057
965021AG1-366 GEN
Solar/Wind Harmer
2.408
270588AE1-091_GEN
Solar/Wind Harmer
5.649
971191AH1-055 GEN
Solar/Wind Harmer
18.515
944531AF1-118 GEN
Solar/Wind Harmer
32.203
270043AE2-236 GEN
Solar/Wind Harmer
4.607
270258AD1-119 GEN
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
5.953
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
10.684
270404AC1-167 GEN
Solar/Wind Harmer
0.003
25196608WSDLE5
Adder
8.745
252510AF1-249 C
Solar/Wind Harmer
0.055
970031AG2-029 GEN
Solar/Wind Harmer
4.625
25194608D.CRK4
Adder
1.676
270222AC2-111 GEN
Solar/Wind Harmer
3.603
970513AG2-328 GEN
Solar/Wind Harmer
3.076
970517AG2-330 GEN
Solar/Wind Harmer
18.457
970349AG2-230 GEN
Solar/Wind Harmer
10.632
946031AF1-268 GEN
Solar/Wind Harmer
6.74
958821AF2-173 GEN
Solar/Wind Harmer
9.902
270004AE1-209 GEN
Solar/Wind Harmer
1.532
270437AC2-090 C
Solar/Wind Harmer
0.003
247643Z2-116 C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.775
970291AG2-192 GEN
Solar/Wind Harmer
0.705
945111AF1-176 GEN
Solar/Wind Harmer
5.709
247642Z2-115 C
Solar/Wind Harmer
0.003
24642205MAYFLWER
Adder
0.641
24441205WTRV SLR C
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.353
270356AE2-297 GEN
Solar/Wind Harmer
0.009
970217AG2-149 GEN
Solar/Wind Harmer
6.066
247604X1-042
Adder
0.418
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
964401AG1-302 GEN
Solar/Wind Harmer
0.001
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.935
970243AG2-164 GEN
Solar/Wind Harmer
4.047
970519AG2-331 GEN
Solar/Wind Harmer
17.988
970699AG2-449 GEN
Solar/Wind Harmer
1.73
274752CRETE EC ;2U
Adder
8.172
274753CRETE EC ;3U
Adder
8.172
274772LINCOLN ;3U
Adder
8.364
274724RIVER EC ;11
Adder
17.549
958171AF2-111 GEN
Solar/Wind Harmer
17.278
274802UNIV PARK;5U
Adder
5.755
276806AD2-047 C O1
Solar/Wind Harmer
3.901
970941AG2-585 GEN
Solar/Wind Harmer
8.605
274826FISK ;BP
Adder
10.802
24728705AND G3
Adder
7.914
24728505AND G1
Adder
3.784
274800UNIV PARK;3U
Adder
5.751
972038AH1-567 GEN2
Adder
0.36
972228AH1-698 GEN2
Adder
3.654
972167AH1-666 GEN
Solar/Wind Harmer
5.505
276897AD1-100 C
Solar/Wind Harmer
0.009
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
22.464
274676JOLIET 29;8U
Adder
29.097
270119AB2-067 GEN1
50/50
6.869
270120AB2-067 GEN2
50/50
6.869
24318905MLG2
50/50
6.89
270471AD2-092_GEN
Solar/Wind Harmer
0.006
942861AE2-305 GEN
Solar/Wind Harmer
6.118
970077AG2-063 GEN
Solar/Wind Harmer
4.471
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
12.484
971655AH1-328 GEN
Solar/Wind Harmer
2.758
964601AG1-323 GEN
Solar/Wind Harmer
3.106
964601AG1-323 GEN
Solar/Wind Harmer
2.071
270518AE2-148 GEN
Solar/Wind Harmer
0.667
972269AH1-719 GEN
Adder
2.501
972159AH1-661 GEN
Adder
1.082
253378AE2-206_GEN
Solar/Wind Harmer
0.004
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
3.237
971199AH1-059 GEN
Solar/Wind Harmer
2.99
241960AC2-195 GEN
Solar/Wind Harmer
0.006
970935AG2-582 GEN
Adder
242.403
25326509SID D
Adder
1.4
971073AG2-665 GEN
Solar/Wind Harmer
6.645
25326109MON D
Adder
1.391
971201AH1-060 GEN
Solar/Wind Harmer
1.471
25322209TAIT E
Adder
10.262
25322209TAIT E
Adder
10.031
253370AE2-315 SEC1
Adder
2.103
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
246938BC-WTG3
Solar/Wind Harmer
0.263
246937BC-WTG2
Solar/Wind Harmer
0.295
971231AH1-075 GEN
Solar/Wind Harmer
0.833
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
970611AG2-400 GEN
Solar/Wind Harmer
7.225
970627AG2-408 GEN
Solar/Wind Harmer
2.167
270007AE1-245 C
Solar/Wind Harmer
0.002
970623AG2-406 GEN
Solar/Wind Harmer
1.309
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25183208HLCRTG
Solar/Wind Harmer
0.011
944541AF1-119 GEN
Solar/Wind Harmer
0.479
960971AF2-388 GEN
Solar/Wind Harmer
4.192
942221AE2-234 GEN
Solar/Wind Harmer
0.036
252519AF1-045_GEN
Solar/Wind Harmer
6.204
252516AE2-318_GEN
Solar/Wind Harmer
5.503
970621AG2-405 GEN
Solar/Wind Harmer
1.305
247621Y3-024
Adder
0.246
970883AG2-550 GEN
Solar/Wind Harmer
7.123
970885AG2-551 GEN
Solar/Wind Harmer
2.374
270201AC2-176 GEN
Solar/Wind Harmer
0.001
25194408D.CRK1
Adder
7.711
25194508D.CRK3
Adder
1.442
964611AG1-324 GEN
Solar/Wind Harmer
0.534
252509AD1-136 GEN
Solar/Wind Harmer
0.036
970321AG2-212 GEN
Solar/Wind Harmer
3.076
270599AE1-208 GEN
Solar/Wind Harmer
6.495
270031AE2-169
Solar/Wind Harmer
3.897
270383AD1-128 GEN
Solar/Wind Harmer
0.004
270186AC1-089 GEN
Solar/Wind Harmer
0.004
247620Y3-023
Adder
0.466
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
7.834
960441AF2-335 GEN
Solar/Wind Harmer
7.065
270216AD2-079_GEN
Solar/Wind Harmer
0.001
971613AH1-306 GEN
Solar/Wind Harmer
3.385
24728805RICHG1
Adder
3.82
24728905RICHG2
Adder
3.82
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
14.072
961051AF2-396 GEN
Solar/Wind Harmer
9.381
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
8.77
965791AG1-447 GEN
Solar/Wind Harmer
6.431
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.73
274770LINCOLN ;1U
Adder
8.364
274771LINCOLN ;2U
Adder
8.364
274808UNIV PK N;4U
Adder
4.933
966841AG1-555 GEN
Solar/Wind Harmer
0.781
274803UNIV PARK;6U
Adder
5.755
274888KELLY CRK;1U
Solar/Wind Harmer
0.404
274887GEN-1.85
Solar/Wind Harmer
0.181
276843GEN-1.7
Solar/Wind Harmer
0.223
958011AF2-095 GEN
Solar/Wind Harmer
9.913
972259AH1-714 GEN
Adder
18.805
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
3.993
958481AF2-142 GEN
Solar/Wind Harmer
10.238
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.923
971573AH1-285 GEN
Solar/Wind Harmer
1.271
971677AH1-339 GEN
Solar/Wind Harmer
0.768
958491AF2-143 GEN
Solar/Wind Harmer
10.205
274879MINONK ;1U
Solar/Wind Harmer
0.287
238175AF1-290_GEN
Solar/Wind Helper
0.148
238169AE2-226 GEN1
Solar/Wind Helper
0.677
238170AE2-226 GEN2
Solar/Wind Helper
0.677
238120AE2-309 GEN
Solar/Wind Helper
0.487
235020AA1-095 C
Solar/Wind Helper
0.051
23777901MDS_W4-102
Solar/Wind Helper
0.171
23585401KL_K28_T16
Solar/Wind Helper
1.328
237034AC2-136 C
Solar/Wind Helper
0.219
237002AB1-128_GEN
Solar/Wind Helper
0.427
235063AE1-101 C2
Solar/Wind Helper
1.6
237001AB1-127_GEN
Solar/Wind Helper
0.426
23777801MSM_W1-116
Solar/Wind Helper
0.11
237025AB1-124 C
Solar/Wind Helper
0.159
237006AB1-125 GEN
Solar/Wind Helper
0.119
226929AD2-058 GEN
Solar/Wind Helper
0.096
205916AD1-020 GEN
Solar/Wind Helper
1.656
20390526W1-045 C
Solar/Wind Helper
0.338
208835TUHI V3-051
Solar/Wind Helper
0.023
208835TUHI V3-051
Solar/Wind Helper
0.023
233987AB2-037 GEN
Solar/Wind Helper
2.264
233933AB2-153 GEN
Solar/Wind Helper
0.225
232424Y1-079 C
Solar/Wind Helper
0.112
233944AB2-135 GEN
Solar/Wind Helper
0.569
233946AB2-136 GEN
Solar/Wind Helper
0.549
234036AF2-325 C
Solar/Wind Helper
0.041
233901CHERRYDALE C
Solar/Wind Helper
0.225
232408W1-005 C
Solar/Wind Helper
0.49
232410W1-006 C
Solar/Wind Helper
0.49
233939AC1-091 C
Solar/Wind Helper
0.338
233970AC1-092 C
Solar/Wind Helper
0.338
315651AD1-115 GEN
Solar/Wind Helper
0.76
316447AC1-158 HLD
Solar/Wind Helper
2.756
230433AD2-135 GEN
Solar/Wind Helper
0.016
230407AD2-065 C
Solar/Wind Helper
0.039
219921AF1-264
Solar/Wind Helper
0.049
219615MILLCREEK C
Solar/Wind Helper
0.026
963401AG1-189 GEN
Solar/Wind Helper
0.054
963391AG1-188 GEN
Solar/Wind Helper
0.079
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.183
270166AC1-044 GEN3
50/50
6.869
23559101PLEAS2
50/50
5.385
270122AB2-093 CT
50/50
3.689
962761AG1-125 GEN
Solar/Wind Harmer
33.269
970149AG2-104 GEN
Solar/Wind Harmer
35.932
970155AG2-107 GEN
Solar/Wind Harmer
21.245
270349AD2-093_GEN
Solar/Wind Harmer
0.006
24721705FLATG2
Adder
22.865
270159DARBY CT4
Adder
9.89
970593AG2-378 GEN
Solar/Wind Harmer
1.75
270223U2-072_GEN1
Solar/Wind Harmer
0.001
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.012
270462AD2-086
Solar/Wind Harmer
0.016
971995AH1-542 GEN
Solar/Wind Harmer
2.81
270263AC1-001 GEN
Solar/Wind Harmer
0.758
270510AE1-227 GEN1
Solar/Wind Harmer
1.904
241813AF1-122_GEN
Solar/Wind Harmer
3.294
25326309TAIT D
Adder
1.153
960071AF2-298 GEN
Solar/Wind Harmer
3.651
253370AE2-315 SEC1
Adder
2.103
253371AE2-315 SEC2
Adder
1.989
927014AC1-188 GEN
Solar/Wind Harmer
0.004
246936BC-WTG1
Solar/Wind Harmer
0.295
270489AE1-102 GEN1
Solar/Wind Harmer
0.945
965421AG1-410 GEN
Solar/Wind Harmer
21.788
247521TR3_G114
Solar/Wind Harmer
0.263
270246TR4_N_V150
Solar/Wind Harmer
0.047
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.226
965011AG1-365 GEN
Solar/Wind Harmer
7.225
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
2.096
958861AF2-177 GEN
Solar/Wind Harmer
3.092
247536S-71 GEN
Solar/Wind Harmer
0.287
945371AF1-202 GEN
Solar/Wind Harmer
0.001
25194608D.CRK4
Adder
1.676
270063AE2-323 C
Solar/Wind Harmer
0.006
252507AC2-088 GEN
Solar/Wind Harmer
0.323
970245AG2-165 GEN
Solar/Wind Harmer
3.076
944231AF1-091 GEN
Solar/Wind Harmer
1.885
270005AE1-210 C O1
Solar/Wind Harmer
1.532
965031AG1-367 GEN
Solar/Wind Harmer
7.073
970947AG2-589 GEN
Solar/Wind Harmer
0.236
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.183
970825AG2-519 GEN
Solar/Wind Harmer
2.509
24639705ELKHART HY
Adder
0.155
25196808ZIMRHP
Adder
76.799
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
270032AE2-172
Solar/Wind Harmer
4.701
970291AG2-192 GEN
Solar/Wind Harmer
0.916
945111AF1-176 GEN
Solar/Wind Harmer
12.568
270505AE1-170 C O1
Solar/Wind Harmer
7.393
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.67
247522W1-056 GEN
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
7.842
25196008MFTGT1
Adder
1.397
970773AG2-487 GEN
Solar/Wind Harmer
1.237
970373AG2-245 GEN
Solar/Wind Harmer
14.699
970515AG2-329 GEN
Solar/Wind Harmer
18.197
270055AF2-134 C O1
Solar/Wind Harmer
0.005
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.071
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.706
24791305MDL-5G
Solar/Wind Harmer
0.001
970333AG2-219 GEN
Solar/Wind Harmer
4.947
274751CRETE EC ;1U
Adder
8.172
274754CRETE EC ;4U
Adder
8.172
274773LINCOLN ;4U
Adder
8.364
274774LINCOLN ;5U
Adder
8.364
274723RIVER EC ;12
Adder
17.756
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.954
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
276776AD2-060 GEN
Solar/Wind Harmer
0.719
24728605AND G2
Adder
3.784
274801UNIV PARK;4U
Adder
5.751
941551AE2-152 GEN
Solar/Wind Harmer
0.001
945681AF1-233 GEN
Solar/Wind Harmer
12.962
274676JOLIET 29;8U
Adder
30.175
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
16.202
939401AE1-172 GEN
Solar/Wind Harmer
5.109
276691AA1-018 GEN1
Solar/Wind Harmer
0.827
276901AD2-066 C O1
Solar/Wind Harmer
0.007
972239AH1-704 GEN
50/50
2.78
962771AG1-126 GEN
Solar/Wind Harmer
33.269
270459AD2-067 GEN
Solar/Wind Harmer
0
270054AF2-122 C O1
Solar/Wind Harmer
0.007
961821AG1-024 GEN
Solar/Wind Harmer
4.91
270520AE2-214 GEN
Solar/Wind Harmer
0.013
270284AF1-227 GEN1
Solar/Wind Harmer
0.01
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
253383AE2-342_GEN
Solar/Wind Harmer
0.003
241973AD2-163_GEN1
Solar/Wind Harmer
0.006
945631AF1-228 GEN
Solar/Wind Harmer
0
943861AF1-054 GEN
Solar/Wind Harmer
3.02
943851AF1-053 GEN
Solar/Wind Harmer
2.092
270156DARBY CT1
Adder
10.05
270157DARBY CT2
Adder
10.026
270158DARBY CT3
Adder
9.866
270578AF1-285 GEN2
Solar/Wind Harmer
0.518
970689AG2-444 GEN
Solar/Wind Harmer
15.861
270432AC2-029 GEN
Solar/Wind Harmer
3.428
940611AE2-048 GEN
Solar/Wind Harmer
18.967
941391AE2-136 GEN
Solar/Wind Harmer
10.684
270302AB2-170 GEN
Solar/Wind Harmer
0.005
270317AD1-130_GEN
Solar/Wind Harmer
0.011
971653AH1-327 GEN
Solar/Wind Harmer
1.08
270269AC2-059
Solar/Wind Harmer
0.004
241972AD1-140 GEN
Solar/Wind Harmer
0.824
970179AG2-119 GEN
Solar/Wind Harmer
6.658
270340AC2-060 GEN
Solar/Wind Harmer
0.009
970879AG2-548 GEN
Solar/Wind Harmer
6.645
253372AE2-315 SEC3
Adder
1.989
253372AE2-315 SEC3
Adder
1.989
25306009OHH W.
Adder
3.018
253349AC2-067 GEN
Solar/Wind Harmer
2.296
253400AC2-068 GEN
Solar/Wind Harmer
0.923
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.92
965051AG1-369 GEN
Solar/Wind Harmer
3.609
971567AH1-282 GEN
Solar/Wind Harmer
10.843
247607V1-011 GEN
Solar/Wind Harmer
0.001
965041AG1-368 GEN
Solar/Wind Harmer
7.21
971989AH1-539 GEN
Solar/Wind Harmer
3.109
963791AG1-232 GEN
Solar/Wind Harmer
9.689
24729505KEY G4
Adder
6.671
270071AF1-092 GEN
Solar/Wind Harmer
13.737
270024AE2-089 GEN
Solar/Wind Harmer
0.008
971985AH1-537 GEN
Solar/Wind Harmer
2.123
965101AG1-375 GEN
Solar/Wind Harmer
7.135
270297AD1-101 GEN
Solar/Wind Harmer
0.002
270367AC2-061_GEN
Solar/Wind Harmer
0.006
971673AH1-337 GEN
Solar/Wind Harmer
4.631
971029AG2-637 GEN
Solar/Wind Harmer
10.686
270543AE2-219 C
Solar/Wind Harmer
0.004
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
9.002
25196308WSDLE2
Adder
8.924
25196208WSDLE1
Adder
8.902
25196708WSDLE6
Adder
8.879
25196508WSDLE4
Adder
8.656
945581AF1-223 GEN
Solar/Wind Harmer
0.001
971347AH1-153 GEN
Solar/Wind Harmer
10.632
971609AH1-304 GEN
Solar/Wind Harmer
1.157
270240V3-007_GEN2
Solar/Wind Harmer
0.002
970115AG2-085 GEN
Solar/Wind Harmer
2.826
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
7.898
971771AH1-392 GEN
Solar/Wind Harmer
7.046
970289AG2-191 GEN
Solar/Wind Harmer
1.339
971619AH1-309 GEN
Solar/Wind Harmer
3.169
971769AH1-391 GEN
Solar/Wind Harmer
7.844
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
25196108MFTGT2
Adder
1.54
25196108MFTGT2
Adder
1.43
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
4.146
971549AH1-272 GEN
Solar/Wind Harmer
14.344
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.364
274776LINCOLN ;7U
Adder
8.364
274777LINCOLN ;8U
Adder
8.364
274814UNIV PK N;0U
Adder
4.998
274807UNIV PK N;3U
Adder
4.987
274805UNIV PK N;1U
Adder
4.965
274811UNIV PK N;7U
Adder
4.954
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
972037AH1-567 GEN1
Adder
0.181
960591AF2-350 GEN
Solar/Wind Harmer
6.884
274827FISK ;RP
Adder
7.655
972227AH1-698 GEN1
Adder
2.573
963841AG1-237 GEN
Solar/Wind Harmer
2.978
274687WILL CNTY;4U
Adder
27.495
274687WILL CNTY;4U
Adder
27.495
274675JOLIET 29;7U
Adder
30.175
274675JOLIET 29;7U
Adder
29.097
972163AH1-664 GEN
Solar/Wind Harmer
7.639
972165AH1-665 GEN
Solar/Wind Harmer
6.118
274731ELWOOD EC;2P
Adder
16.163
274733ELWOOD EC;3P
Adder
16.163
274735ELWOOD EC;4P
Adder
16.163
274728ELWOOD EC;5P
Adder
16.163
970833AG2-524 GEN
Solar/Wind Harmer
7.542
970833AG2-524 GEN
Solar/Wind Harmer
5.028
945641AF1-229 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
276868AE1-113 GEN
Solar/Wind Harmer
1.363
276882AE2-255 GEN
Solar/Wind Harmer
0.794
238109AE1-109 GEN2
Solar/Wind Helper
0.106
238110AE1-109 GEN3
Solar/Wind Helper
0.106
238152AF2-075_GEN
Solar/Wind Helper
0.683
23546401DTGZ2-030
Solar/Wind Helper
0.086
238208AF1-136 C
Solar/Wind Helper
0.211
238126S14_GEN_1
Solar/Wind Helper
0.766
237085AD2-009_GEN
Solar/Wind Helper
1.588
3138216PACIFIC
Solar/Wind Helper
0.043
316411AF1-147_GEN1
Solar/Wind Helper
0.86
316415AF1-147_GEN2
Solar/Wind Helper
0.86
959381AF2-229 GEN
Solar/Wind Helper
0.345
23750501ELLIOTTS
Solar/Wind Helper
0.571
3141426STAFORD
Solar/Wind Helper
0.051
960921AF2-383 GEN
Solar/Wind Helper
0.352
205943AE1-185 GEN
Solar/Wind Helper
0.492
205956AE1-196_GEN
Solar/Wind Helper
0.492
205932AD2-116_GEN
Solar/Wind Helper
0.492
233935AB2-179 C
Solar/Wind Helper
1.227
232436AB1-176 C
Solar/Wind Helper
0.043
233923SMA
Solar/Wind Helper
0.927
233990AG1-397 GEN
Solar/Wind Helper
0.261
234033AF1-007_GEN
Solar/Wind Helper
6.787
232432Z2-076 GEN
Solar/Wind Helper
0.065
964001AG1-254 GEN
Solar/Wind Helper
0.924
228754AB1-001 C
Solar/Wind Helper
0.025
227927V4-067C
Solar/Wind Helper
0.01
219914AD2-027 C
Solar/Wind Helper
0.111
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.038
219607WPEMNERT C
Solar/Wind Helper
0.077
214067T20SOLAR
Solar/Wind Helper
0.011
203975AE1-071-GEN
Solar/Wind Helper
2.41
20715728PEM_W1-119
Solar/Wind Helper
0.093
20715828PEM_W1-120
Solar/Wind Helper
0.093
207459AE1-142 C O1
Solar/Wind Helper
0.28
316164AC1-076 GEN
Solar/Wind Helper
1.062
219620RIDERU C
Solar/Wind Helper
0.001
274729ELWOOD EC;1P
Adder
16.163
274730ELWOOD EC;6P
Adder
13.491
276893AG1-478 C
Solar/Wind Harmer
0.272
270541AE2-072 C
Solar/Wind Harmer
0.009
943121AE2-341 GEN
Solar/Wind Harmer
11.459
943591AF1-030 GEN
Solar/Wind Harmer
7.62
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
276805AD2-038 GEN
Solar/Wind Harmer
0.002
964991AG1-363 GEN
Solar/Wind Helper
4.969
316097T157 G90
Solar/Wind Helper
1.455
23750701CROSSCHOOL
Solar/Wind Helper
1.397
238148AE2-230_GEN2
Solar/Wind Helper
0.48
238127S14_GEN_2
Solar/Wind Helper
0.766
238118U2-030_1
Solar/Wind Helper
0.314
237080AD1-060 GEN
Solar/Wind Helper
0.33
237038AE2-054 C
Solar/Wind Helper
0.262
235062AE1-101 C1
Solar/Wind Helper
1.6
23779801AA1-109
Solar/Wind Helper
0.187
223401AF1-299 GEN
Solar/Wind Helper
0.355
316006AB2-029 C
Solar/Wind Helper
0.113
966131AG1-482 GEN
Solar/Wind Helper
0.132
237048AF1-022 C
Solar/Wind Helper
0.159
233930AB2-032 GEN
Solar/Wind Helper
0.368
233915AB1-141 GEN
Solar/Wind Helper
0.486
232422X3-066 FULL
Solar/Wind Helper
0.11
232426Y1-080 FULL
Solar/Wind Helper
0.038
233964AF2-378 GEN
Solar/Wind Helper
0.04
233998TM1NIN_3.36
Solar/Wind Helper
0.253
232404W1-003 C
Solar/Wind Helper
0.49
232428Y3-058 C
Solar/Wind Helper
0.327
232434Z2-077 GEN
Solar/Wind Helper
0.123
233954AC2-188 GEN
Solar/Wind Helper
0.225
233950AC2-186 GEN
Solar/Wind Helper
0.112
233972AC1-094 C
Solar/Wind Helper
0.292
316045AC1-158 PL2
Solar/Wind Helper
4.009
230511AF1-262
Solar/Wind Helper
0.014
230434AG1-499 GEN
Solar/Wind Helper
0.222
228728W1-130C
Solar/Wind Helper
0.052
219258KINSLEYDEP C
Solar/Wind Helper
0.074
219904AC1-010 C
Solar/Wind Helper
0.058
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219907AC1-030 C
Solar/Wind Helper
0.033
219686LUMSOLAR_N C
Solar/Wind Helper
0.038
219304NAMERICA C
Solar/Wind Helper
0.127
316254AC1-120 GEN1
Solar/Wind Helper
1.026
20720728JCB_W1-129
Solar/Wind Helper
0.055
207445AB1-138_GEN
Solar/Wind Helper
0.101
963711AG1-223 GEN
Solar/Wind Helper
0.062
20714828MDF_W3-079
Solar/Wind Helper
0.126
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.299
20715228NPK_W1-113
Solar/Wind Helper
0.075
316095T157 G97
Solar/Wind Helper
1.455
23583801GRNGAP
Solar/Wind Helper
5.418
238108AE1-109 GEN1
Solar/Wind Helper
0.106
238185AF2-356 C
Solar/Wind Helper
2.425
238147AE2-230_GEN1
Solar/Wind Helper
0.478
238149AF1-291A_GEN
Solar/Wind Helper
0.137
235531U2-073 GEN
Solar/Wind Helper
3.034
235054AD2-180 GEN
Solar/Wind Helper
1.839
237061AD1-155 GEN
Solar/Wind Helper
0.051
238117U2-030
Solar/Wind Helper
0.314
238221AF1-254 C O1
Solar/Wind Helper
0.265
235067AD1-061 GEN
Solar/Wind Helper
0.478
237030AB1-096 C
Solar/Wind Helper
0.068
3141196NOKESVL
Solar/Wind Helper
0.999
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.335
223402AF1-300 C
Solar/Wind Helper
0.355
23751201ROTHROCK
Solar/Wind Helper
0.694
23562501BACKB
Solar/Wind Helper
0.842
205917AD1-020 ES
Solar/Wind Helper
0.356
233982AB2-133 GEN
Solar/Wind Helper
0.346
233918AB1-142 GEN
Solar/Wind Helper
0.486
233994AC2-023 GEN
Solar/Wind Helper
0.929
233996TM1833_GEN
Solar/Wind Helper
0.253
233997TMININ_4.2
Solar/Wind Helper
0.253
232406W1-004 FULL
Solar/Wind Helper
0.49
233940AF2-379 C
Solar/Wind Helper
0.06
234015AF2-250 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.225
233971AC1-093 C
Solar/Wind Helper
0.346
316044AC1-158 PL1
Solar/Wind Helper
1.252
316450AC1-158 RIC
Solar/Wind Helper
0.334
230430AE1-229_GEN
Solar/Wind Helper
3.26
230415AB2-049 C
Solar/Wind Helper
0.029
228729W2-030 C
Solar/Wind Helper
0.107
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.053
219912AD2-042 GEN
Solar/Wind Helper
0.145
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.111
316170AC1-121 GEN2
Solar/Wind Helper
0.342
959561AF2-247 GEN
Solar/Wind Helper
0.02
20720828JCB_W4-025
Solar/Wind Helper
0.061
20716028EGP_W2-019
Solar/Wind Helper
0.018
20715028HAN_X4-015
Solar/Wind Helper
0.055
219276PARKLANDSO C
Solar/Wind Helper
0.086
20714528FRN_Y2-051
Solar/Wind Helper
0.055
20720528MAN_W1-024
Solar/Wind Helper
0.027
971997AH1-543 GEN
Solar/Wind Harmer
1.86
LAGNLTFEXP_LAGN->PJM
CLTF
14.268
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.432
TVALTFEXP_TVA->PJM
CLTF
7.011
CPLELTFEXP_CPLE->PJM
CLTF
0.567
CBM West 2LTFEXP_CBM-W2->PJM
CBM
108.576
NYPJM->LTFIMP_NY
CLTF
4.628
LGEELTFEXP_LGEE->PJM
CLTF
6.497
WECLTFEXP_WEC->PJM
CLTF
3.686
AG2-052LTFEXP_AG2-052->PJM
LTF
0.231
AH1-155LTFEXP_AH1-155->PJM
LTF
0.346
CBM West 1LTFEXP_CBM-W1->PJM
CBM
137.982
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.984
MECLTFEXP_MEC->PJM
CLTF
15.319
SIGELTFEXP_SIGE->PJM
CLTF
0.486

Details for AG2-505 TP-01BERYL 138.0 kV Ckt 1 line l/o AP_P2-3_PE-500-014_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
AG2-505 TP-01BERYL 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-014_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:152.24 %
Rating:206.0 MVA
Rating Type:B
MVA to Mitigate:313.62
MW Contribution:11.5
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
Adder
11.497
971679AH1-340 GEN
Solar/Wind Harmer
3.052
23750501ELLIOTTS
Solar/Wind Harmer
0.971
970801AG2-505 GEN
50/50
8.712
23750701CROSSCHOOL
Solar/Wind Helper
3.115
238185AF2-356 C
Solar/Wind Harmer
24.354
LAGNLTFEXP_LAGN->PJM
CLTF
0.311
TVALTFEXP_TVA->PJM
CLTF
0.151
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.61
NYPJM->LTFIMP_NY
CLTF
0.151
LGEELTFEXP_LGEE->PJM
CLTF
0.17
WECLTFEXP_WEC->PJM
CLTF
0.098
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.055
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.007
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.91
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.634
MECLTFEXP_MEC->PJM
CLTF
0.397
SIGELTFEXP_SIGE->PJM
CLTF
0.013

Details for AG2-505 TP-01BERYL 138.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT19_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
AG2-505 TP-01BERYL 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT19_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:148.75 %
Rating:206.0 MVA
Rating Type:B
MVA to Mitigate:306.42
MW Contribution:11.62
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
Adder
11.619
971679AH1-340 GEN
Solar/Wind Harmer
3.055
23750501ELLIOTTS
Solar/Wind Harmer
0.972
970801AG2-505 GEN
50/50
8.713
23750701CROSSCHOOL
Solar/Wind Helper
3.114
964991AG1-363 GEN
Solar/Wind Helper
1.776
238185AF2-356 C
Solar/Wind Harmer
24.357
LAGNLTFEXP_LAGN->PJM
CLTF
0.322
TVALTFEXP_TVA->PJM
CLTF
0.157
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.683
NYPJM->LTFIMP_NY
CLTF
0.148
LGEELTFEXP_LGEE->PJM
CLTF
0.174
WECLTFEXP_WEC->PJM
CLTF
0.1
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.051
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.005
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.989
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.654
MECLTFEXP_MEC->PJM
CLTF
0.406
SIGELTFEXP_SIGE->PJM
CLTF
0.013

Details for AG2-505 TP-01BERYL 138.0 kV Ckt 1 line l/o AP_P1-2_PE-500-004_SRT-SL-2


Base Case Flowgate

Area:AP
Facility Description:
AG2-505 TP-01BERYL 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-500-004_SRT-SL-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:139.52 %
Rating:206.0 MVA
Rating Type:B
MVA to Mitigate:287.42
MW Contribution:11.5
Bus #Bus NameTypeMW Contribution
970801AG2-505 GEN
50/50
8.712
23750701CROSSCHOOL
Solar/Wind Helper
3.115
970935AG2-582 GEN
Adder
11.497
971679AH1-340 GEN
Solar/Wind Harmer
2.129
23750501ELLIOTTS
Solar/Wind Harmer
0
238185AF2-356 C
Solar/Wind Harmer
0.048
LAGNLTFEXP_LAGN->PJM
CLTF
0.311
TVALTFEXP_TVA->PJM
CLTF
0.151
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.61
NYPJM->LTFIMP_NY
CLTF
0.151
LGEELTFEXP_LGEE->PJM
CLTF
0.17
WECLTFEXP_WEC->PJM
CLTF
0.098
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.055
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.007
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.91
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.634
MECLTFEXP_MEC->PJM
CLTF
0.397
SIGELTFEXP_SIGE->PJM
CLTF
0.013

Details for AG2-505 TP-01BERYL 138.0 kV Ckt 1 line l/o AP_P1-2_PE-500-004_SRT-SL-1


Base Case Flowgate

Area:AP
Facility Description:
AG2-505 TP-01BERYL 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-500-004_SRT-SL-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:136.04 %
Rating:206.0 MVA
Rating Type:B
MVA to Mitigate:280.25
MW Contribution:11.62
Bus #Bus NameTypeMW Contribution
970801AG2-505 GEN
50/50
8.713
23750701CROSSCHOOL
Solar/Wind Helper
3.114
964991AG1-363 GEN
Solar/Wind Helper
1.776
970935AG2-582 GEN
Adder
11.619
238185AF2-356 C
Solar/Wind Harmer
0.048
971679AH1-340 GEN
Solar/Wind Harmer
2.131
23750501ELLIOTTS
Solar/Wind Harmer
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.322
TVALTFEXP_TVA->PJM
CLTF
0.157
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.683
NYPJM->LTFIMP_NY
CLTF
0.148
LGEELTFEXP_LGEE->PJM
CLTF
0.174
WECLTFEXP_WEC->PJM
CLTF
0.1
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.051
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.005
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.989
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.654
MECLTFEXP_MEC->PJM
CLTF
0.406
SIGELTFEXP_SIGE->PJM
CLTF
0.013

Details for AG2-505 TP-01BERYL 138.0 kV Ckt 1 line l/o AP_P2-2_WP-500-DRT9_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
AG2-505 TP-01BERYL 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-500-DRT9_SRT-SL
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:107.16 %
Rating:206.0 MVA
Rating Type:B
MVA to Mitigate:220.75
MW Contribution:11.79
Bus #Bus NameTypeMW Contribution
971679AH1-340 GEN
Solar/Wind Harmer
3.12
23750501ELLIOTTS
Solar/Wind Harmer
0.95
970801AG2-505 GEN
50/50
8.854
23750701CROSSCHOOL
Solar/Wind Helper
2.993
970935AG2-582 GEN
Adder
11.79
238185AF2-356 C
Solar/Wind Harmer
24.755
23751201ROTHROCK
Solar/Wind Harmer
0.889
LAGNLTFEXP_LAGN->PJM
CLTF
0.368
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.186
TVALTFEXP_TVA->PJM
CLTF
0.183
CPLELTFEXP_CPLE->PJM
CLTF
0.005
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.779
NYPJM->LTFIMP_NY
CLTF
0.191
LGEELTFEXP_LGEE->PJM
CLTF
0.166
WECLTFEXP_WEC->PJM
CLTF
0.093
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.55
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.726
MECLTFEXP_MEC->PJM
CLTF
0.388
SIGELTFEXP_SIGE->PJM
CLTF
0.012

Details for AG2-505 TP-01BERYL 138.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT22_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
AG2-505 TP-01BERYL 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT22_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.15 %
Rating:206.0 MVA
Rating Type:B
MVA to Mitigate:220.73
MW Contribution:11.79
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
Adder
11.79
970801AG2-505 GEN
50/50
8.854
23750701CROSSCHOOL
Solar/Wind Helper
2.993
971679AH1-340 GEN
Solar/Wind Harmer
3.12
23750501ELLIOTTS
Solar/Wind Harmer
0.95
238185AF2-356 C
Solar/Wind Harmer
24.755
23751201ROTHROCK
Solar/Wind Harmer
0.889
LAGNLTFEXP_LAGN->PJM
CLTF
0.368
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.186
TVALTFEXP_TVA->PJM
CLTF
0.183
CPLELTFEXP_CPLE->PJM
CLTF
0.005
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.779
NYPJM->LTFIMP_NY
CLTF
0.191
LGEELTFEXP_LGEE->PJM
CLTF
0.166
WECLTFEXP_WEC->PJM
CLTF
0.093
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.55
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.726
MECLTFEXP_MEC->PJM
CLTF
0.388
SIGELTFEXP_SIGE->PJM
CLTF
0.012

Details for AG2-505 TP-01BERYL 138.0 kV Ckt 1 line l/o AP_P2-3_MP-138-206_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
AG2-505 TP-01BERYL 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-138-206_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.72 %
Rating:206.0 MVA
Rating Type:B
MVA to Mitigate:217.78
MW Contribution:11.83
Bus #Bus NameTypeMW Contribution
970801AG2-505 GEN
50/50
8.854
23750701CROSSCHOOL
Solar/Wind Helper
2.993
971679AH1-340 GEN
Solar/Wind Harmer
3.121
23750501ELLIOTTS
Solar/Wind Harmer
0.95
970935AG2-582 GEN
Adder
11.829
238185AF2-356 C
Solar/Wind Harmer
24.756
23751201ROTHROCK
Solar/Wind Harmer
0.889
LAGNLTFEXP_LAGN->PJM
CLTF
0.372
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.192
TVALTFEXP_TVA->PJM
CLTF
0.184
CPLELTFEXP_CPLE->PJM
CLTF
0.006
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.802
NYPJM->LTFIMP_NY
CLTF
0.19
LGEELTFEXP_LGEE->PJM
CLTF
0.167
WECLTFEXP_WEC->PJM
CLTF
0.093
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.575
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.733
MECLTFEXP_MEC->PJM
CLTF
0.39
SIGELTFEXP_SIGE->PJM
CLTF
0.012

Details for AG2-505 TP-01BERYL 138.0 kV Ckt 1 line l/o AP_P2-2_WP-500-DRT11_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
AG2-505 TP-01BERYL 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-500-DRT11_SRT-SL
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:101.8 %
Rating:206.0 MVA
Rating Type:B
MVA to Mitigate:209.71
MW Contribution:11.94
Bus #Bus NameTypeMW Contribution
971679AH1-340 GEN
Solar/Wind Harmer
3.123
23750501ELLIOTTS
Solar/Wind Harmer
0.951
970801AG2-505 GEN
50/50
8.855
23750701CROSSCHOOL
Solar/Wind Helper
2.993
970935AG2-582 GEN
Adder
11.939
238185AF2-356 C
Solar/Wind Harmer
24.758
23751201ROTHROCK
Solar/Wind Harmer
0.89
LAGNLTFEXP_LAGN->PJM
CLTF
0.382
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.206
TVALTFEXP_TVA->PJM
CLTF
0.189
CPLELTFEXP_CPLE->PJM
CLTF
0.012
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.867
NYPJM->LTFIMP_NY
CLTF
0.187
LGEELTFEXP_LGEE->PJM
CLTF
0.171
WECLTFEXP_WEC->PJM
CLTF
0.095
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.646
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.751
MECLTFEXP_MEC->PJM
CLTF
0.399
SIGELTFEXP_SIGE->PJM
CLTF
0.013

Details for N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line l/o PN_P1-1_PN-230-018_SRT-A


Base Case Flowgate

Area:NYISO/PENELEC
Facility Description:
N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line
Contingency Name:
PN_P1-1_PN-230-018_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:139.93 %
Rating:128.0 MVA
Rating Type:B
MVA to Mitigate:179.12
MW Contribution:6.78
Bus #Bus NameTypeMW Contribution
971703AH1-357 GEN
Solar/Wind Harmer
0.451
971707AH1-359 GEN
Solar/Wind Harmer
0.451
972191AH1-680 GEN
Adder
6.653
941421AE2-139 GEN
Solar/Wind Helper
2.971
200917MEHOOPANY_G
Solar/Wind Helper
1.989
203859AF2-294 C
Solar/Wind Harmer
0.513
972077AH1-588 GEN
Solar/Wind Harmer
5.415
972079AH1-589 GEN
Solar/Wind Harmer
6.393
970715AG2-457 GEN
Solar/Wind Harmer
2.098
970935AG2-582 GEN
Adder
6.78
20083926HOMER C3
Adder
15.347
20083826HOMER C2
Adder
14.497
20083726HOMER C1
Adder
9.085
972211AH1-690 GEN
Adder
7.013
970713AG2-456 GEN
Solar/Wind Harmer
2.098
971705AH1-358 GEN
Solar/Wind Harmer
0.752
971709AH1-360 GEN
Solar/Wind Harmer
0.752
959471AF2-238 GEN
Solar/Wind Helper
0.26
LAGNLTFEXP_LAGN->PJM
CLTF
0.624
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.726
TVALTFEXP_TVA->PJM
CLTF
0.309
CPLELTFEXP_CPLE->PJM
CLTF
0.233
CBM NorthLTFEXP_CBM-N->PJM
CBM
17.815
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.353
LGEELTFEXP_LGEE->PJM
CLTF
0.234
WECLTFEXP_WEC->PJM
CLTF
0.134
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.354
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.181
MECLTFEXP_MEC->PJM
CLTF
0.575
SIGELTFEXP_SIGE->PJM
CLTF
0.018

Details for N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line l/o PN_P1-1_PN-230-017_SRT-A


Base Case Flowgate

Area:NYISO/PENELEC
Facility Description:
N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line
Contingency Name:
PN_P1-1_PN-230-017_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:139.93 %
Rating:128.0 MVA
Rating Type:B
MVA to Mitigate:179.12
MW Contribution:6.78
Bus #Bus NameTypeMW Contribution
971703AH1-357 GEN
Solar/Wind Harmer
0.451
971707AH1-359 GEN
Solar/Wind Harmer
0.451
972191AH1-680 GEN
Adder
6.653
941421AE2-139 GEN
Solar/Wind Helper
2.971
200917MEHOOPANY_G
Solar/Wind Helper
1.989
203859AF2-294 C
Solar/Wind Harmer
0.513
972077AH1-588 GEN
Solar/Wind Harmer
5.415
972079AH1-589 GEN
Solar/Wind Harmer
6.393
970715AG2-457 GEN
Solar/Wind Harmer
2.098
970935AG2-582 GEN
Adder
6.78
20083926HOMER C3
Adder
15.347
20083826HOMER C2
Adder
14.497
20083726HOMER C1
Adder
9.085
972211AH1-690 GEN
Adder
7.013
970713AG2-456 GEN
Solar/Wind Harmer
2.098
971705AH1-358 GEN
Solar/Wind Harmer
0.752
971709AH1-360 GEN
Solar/Wind Harmer
0.752
959471AF2-238 GEN
Solar/Wind Helper
0.26
LAGNLTFEXP_LAGN->PJM
CLTF
0.624
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.726
TVALTFEXP_TVA->PJM
CLTF
0.309
CPLELTFEXP_CPLE->PJM
CLTF
0.233
CBM NorthLTFEXP_CBM-N->PJM
CBM
17.815
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.353
LGEELTFEXP_LGEE->PJM
CLTF
0.234
WECLTFEXP_WEC->PJM
CLTF
0.134
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.354
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.181
MECLTFEXP_MEC->PJM
CLTF
0.575
SIGELTFEXP_SIGE->PJM
CLTF
0.018

Details for N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line l/o PN_P2-2_PN-345-1154-W_SRT-A


Base Case Flowgate

Area:NYISO/PENELEC
Facility Description:
N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line
Contingency Name:
PN_P2-2_PN-345-1154-W_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:124.81 %
Rating:128.0 MVA
Rating Type:B
MVA to Mitigate:159.76
MW Contribution:7.7
Bus #Bus NameTypeMW Contribution
971703AH1-357 GEN
Solar/Wind Harmer
0.619
971707AH1-359 GEN
Solar/Wind Harmer
0.619
20083926HOMER C3
Adder
18.011
20083826HOMER C2
Adder
17.014
20083726HOMER C1
Adder
10.622
972211AH1-690 GEN
Adder
7.849
972191AH1-680 GEN
Adder
7.47
941421AE2-139 GEN
Solar/Wind Helper
3.345
200917MEHOOPANY_G
Solar/Wind Helper
2.227
203859AF2-294 C
Solar/Wind Harmer
0.816
972077AH1-588 GEN
Solar/Wind Harmer
7.43
972079AH1-589 GEN
Solar/Wind Harmer
6.12
970715AG2-457 GEN
Solar/Wind Harmer
2.477
970935AG2-582 GEN
Adder
7.698
20398826ARMNA MT
Solar/Wind Helper
1.623
970713AG2-456 GEN
Solar/Wind Harmer
2.477
971705AH1-358 GEN
Solar/Wind Harmer
0.72
971709AH1-360 GEN
Solar/Wind Harmer
0.72
959471AF2-238 GEN
Solar/Wind Helper
0.551
LAGNLTFEXP_LAGN->PJM
CLTF
0.704
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.823
TVALTFEXP_TVA->PJM
CLTF
0.349
CPLELTFEXP_CPLE->PJM
CLTF
0.265
CBM NorthLTFEXP_CBM-N->PJM
CBM
19.942
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.909
LGEELTFEXP_LGEE->PJM
CLTF
0.264
WECLTFEXP_WEC->PJM
CLTF
0.151
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.021
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.333
MECLTFEXP_MEC->PJM
CLTF
0.647
SIGELTFEXP_SIGE->PJM
CLTF
0.02

Details for N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:NYISO/PENELEC
Facility Description:
N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.38 %
Rating:114.0 MVA
Rating Type:A
MVA to Mitigate:132.68
MW Contribution:6.78
Bus #Bus NameTypeMW Contribution
971703AH1-357 GEN
Solar/Wind Harmer
0.451
971707AH1-359 GEN
Solar/Wind Harmer
0.451
972191AH1-680 GEN
Adder
6.653
941421AE2-139 GEN
Solar/Wind Helper
2.971
200917MEHOOPANY_G
Solar/Wind Helper
1.989
203859AF2-294 C
Solar/Wind Harmer
0.513
972077AH1-588 GEN
Solar/Wind Harmer
5.415
972079AH1-589 GEN
Solar/Wind Harmer
6.393
970715AG2-457 GEN
Solar/Wind Harmer
2.098
970935AG2-582 GEN
Adder
6.78
20083926HOMER C3
Adder
15.347
20083826HOMER C2
Adder
14.497
20083726HOMER C1
Adder
9.085
972211AH1-690 GEN
Adder
7.013
970713AG2-456 GEN
Solar/Wind Harmer
2.098
971705AH1-358 GEN
Solar/Wind Harmer
0.752
971709AH1-360 GEN
Solar/Wind Harmer
0.752
959471AF2-238 GEN
Solar/Wind Helper
0.26
LAGNLTFEXP_LAGN->PJM
CLTF
0.624
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.726
TVALTFEXP_TVA->PJM
CLTF
0.309
CPLELTFEXP_CPLE->PJM
CLTF
0.233
CBM NorthLTFEXP_CBM-N->PJM
CBM
17.815
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.353
LGEELTFEXP_LGEE->PJM
CLTF
0.234
WECLTFEXP_WEC->PJM
CLTF
0.134
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.354
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.181
MECLTFEXP_MEC->PJM
CLTF
0.575
SIGELTFEXP_SIGE->PJM
CLTF
0.018

Details for N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line l/o AP_P2-2_WP-230-001T_SRT-A


Base Case Flowgate

Area:NYISO/PENELEC
Facility Description:
N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-230-001T_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:113.06 %
Rating:128.0 MVA
Rating Type:B
MVA to Mitigate:144.71
MW Contribution:7.18
Bus #Bus NameTypeMW Contribution
20083926HOMER C3
Adder
16.064
20083826HOMER C2
Adder
15.174
20083726HOMER C1
Adder
9.328
972211AH1-690 GEN
Adder
7.602
971703AH1-357 GEN
Solar/Wind Harmer
0.725
971707AH1-359 GEN
Solar/Wind Harmer
0.725
972191AH1-680 GEN
Adder
7.211
941421AE2-139 GEN
Solar/Wind Helper
3.037
200917MEHOOPANY_G
Solar/Wind Helper
2.024
203859AF2-294 C
Solar/Wind Harmer
0.732
972077AH1-588 GEN
Solar/Wind Harmer
8.696
972079AH1-589 GEN
Solar/Wind Harmer
7.162
970715AG2-457 GEN
Solar/Wind Harmer
2.899
970935AG2-582 GEN
Adder
7.181
970713AG2-456 GEN
Solar/Wind Harmer
2.899
971705AH1-358 GEN
Solar/Wind Harmer
0.843
971709AH1-360 GEN
Solar/Wind Harmer
0.843
959471AF2-238 GEN
Solar/Wind Helper
0.265
LAGNLTFEXP_LAGN->PJM
CLTF
0.665
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.766
TVALTFEXP_TVA->PJM
CLTF
0.329
CPLELTFEXP_CPLE->PJM
CLTF
0.244
CBM NorthLTFEXP_CBM-N->PJM
CBM
17.786
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.655
LGEELTFEXP_LGEE->PJM
CLTF
0.251
WECLTFEXP_WEC->PJM
CLTF
0.144
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.756
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.261
MECLTFEXP_MEC->PJM
CLTF
0.616
SIGELTFEXP_SIGE->PJM
CLTF
0.019
CONTINGENCY 'AP_P2-3_MP-500-012_SRT-A'
 DISCONNECT BRANCH FROM BUS 235107 TO BUS 235235 CKT 1   /*01HARRSN     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235107 TO BUS 235703 CKT 1   /*01HARRSN     500.0 - 01WYLIE R    500.0
END
CONTINGENCY 'AP_P1-2_MP-500-008A_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235107 CKT 1          /*01FLINTRUN   500.0 - 01HARRSN     500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235107 TO BUS 235703 CKT 1 /*01HARRSN     500.0 - 01WYLIE R    500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235107 TO BUS 235703 CKT 1 /*01HARRSN     500.0 - 01WYLIE R    500.0
END
CONTINGENCY 'AP_P2-3_WP-500-DRT4_SRT-SL'
 OPEN BRANCH FROM BUS 235107 TO BUS 235235 CKT 1                /*01HARRSN     500.0 - 01FLINTRUN   500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235107 TO BUS 235111 CKT 1 /*01HARRSN     500.0 - 01 502 J     500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235107 TO BUS 235111 CKT 1 /*01HARRSN     500.0 - 01 502 J     500.0
END
CONTINGENCY 'AP_P2-3_MP-500-018_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235107 TO BUS 235235 CKT 1          /*01HARRSN     500.0 - 01FLINTRUN   500.0
 SET POSTCONTRATING 2492 BRANCH FROM BUS 235107 TO BUS 235703 CKT 1 /*01HARRSN     500.0 - 01WYLIE R    500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235107 TO BUS 235111 CKT 1 /*01HARRSN     500.0 - 01 502 J     500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235107 TO BUS 235112 CKT 1 /*01HARRSN     500.0 - 01PRNTY      500.0
 SET PRECONTRATING 1986 BRANCH FROM BUS 235107 TO BUS 235703 CKT 1 /*01HARRSN     500.0 - 01WYLIE R    500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235107 TO BUS 235111 CKT 1 /*01HARRSN     500.0 - 01 502 J     500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235107 TO BUS 235112 CKT 1 /*01HARRSN     500.0 - 01PRNTY      500.0
END
CONTINGENCY 'AP_P2-3_PE-500-014_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235103 TO BUS 964990 CKT 1          /*01BLACKO     500.0 - AG1-363 TP   500.0
 REDUCE BUS 235103 SHUNT BY 50 PERCENT                          /*01BLACKO     500.0
 SET POSTCONTRATING 2771 BRANCH FROM BUS 235101 TO BUS 235103 CKT 1 /*01BEDNGT     500.0 - 01BLACKO     500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235101 TO BUS 235103 CKT 1 /*01BEDNGT     500.0 - 01BLACKO     500.0
END
CONTINGENCY 'AP_P2-3_WP-500-DRT19_SRT-SL'
 OPEN BRANCH FROM BUS 235108 TO BUS 964990 CKT 1                /*01HATFLD     500.0 - AG1-363 TP   500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235108 TO BUS 235109 CKT 1 /*01HATFLD     500.0 - AB1-106 POI  500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235108 TO BUS 235774 CKT 1 /*01HATFLD     500.0 - 01RONCO      500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235108 TO BUS 235109 CKT 1 /*01HATFLD     500.0 - AB1-106 POI  500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235108 TO BUS 235774 CKT 1 /*01HATFLD     500.0 - 01RONCO      500.0
END
CONTINGENCY 'AP_P1-2_PE-500-004_SRT-SL-2'
 DISCONNECT BRANCH FROM BUS 964990 TO BUS 235103 CKT 1   /*AG1-363 TP   500.0 - 01BLACKO     500.0
END
CONTINGENCY 'AP_P1-2_PE-500-004_SRT-SL-1'
 DISCONNECT BRANCH FROM BUS 235108 TO BUS 964990 CKT 1   /*01HATFLD     500.0 - AG1-363 TP   500.0
END
CONTINGENCY 'AP_P2-2_WP-500-DRT9_SRT-SL'
 OPEN BRANCH FROM BUS 235774 TO BUS 235108 CKT 1                /*01RONCO      500.0 - 01HATFLD     500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235106 TO BUS 235774 CKT 1 /*01FMARTN     500.0 - 01RONCO      500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235106 TO BUS 235774 CKT 1 /*01FMARTN     500.0 - 01RONCO      500.0
END
CONTINGENCY 'AP_P2-3_WP-500-DRT22_SRT-SL'
 OPEN BRANCH FROM BUS 235108 TO BUS 235774 CKT 1                /*01HATFLD     500.0 - 01RONCO      500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235108 TO BUS 235109 CKT 1 /*01HATFLD     500.0 - AB1-106 POI  500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235108 TO BUS 964990 CKT 1 /*01HATFLD     500.0 - AG1-363 TP   500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235108 TO BUS 235109 CKT 1 /*01HATFLD     500.0 - AB1-106 POI  500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235108 TO BUS 964990 CKT 1 /*01HATFLD     500.0 - AG1-363 TP   500.0
END
CONTINGENCY 'AP_P2-3_MP-138-206_SRT-A'
 DISCONNECT BRANCH FROM BUS 235106 TO BUS 235774 CKT 1   /*01FMARTN     500.0 - 01RONCO      500.0
 DISCONNECT BRANCH FROM BUS 235108 TO BUS 235774 CKT 1   /*01HATFLD     500.0 - 01RONCO      500.0
 DISCONNECT BRANCH FROM BUS 235755 TO BUS 235774 CKT 1   /*01RONCO1      18.0 - 01RONCO      500.0
 DISCONNECT BRANCH FROM BUS 235756 TO BUS 235774 CKT 1   /*01RONCO2      18.0 - 01RONCO      500.0
 DISCONNECT BRANCH FROM BUS 235757 TO BUS 235774 CKT 1   /*01RONCO3      18.0 - 01RONCO      500.0
END
CONTINGENCY 'AP_P2-2_WP-500-DRT11_SRT-SL'
 OPEN BRANCH FROM BUS 235774 TO BUS 235106 CKT 1                /*01RONCO      500.0 - 01FMARTN     500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235774 TO BUS 235108 CKT 1 /*01RONCO      500.0 - 01HATFLD     500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235774 TO BUS 235108 CKT 1 /*01RONCO      500.0 - 01HATFLD     500.0
END
CONTINGENCY 'AP_P2-3_MP-500-016_SRT-A'
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235100 CKT 1   /*01FLINTRUN   500.0 - 01FLINTRN    138.0
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235107 CKT 1   /*01FLINTRUN   500.0 - 01HARRSN     500.0
END
CONTINGENCY 'AP_P2-3_MP-500-017_SRT-A'
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235100 CKT 2   /*01FLINTRUN   500.0 - 01FLINTRN    138.0
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235107 CKT 1   /*01FLINTRUN   500.0 - 01HARRSN     500.0
END
CONTINGENCY 'AEP_P4_#8975_05KAMMER 765_MM2_SRT-A'
 OPEN BRANCH FROM BUS 235111 TO BUS 235117 CKT 1   /*01 502 J     500.0 - 01KAMMER     500.0
 OPEN BRANCH FROM BUS 235117 TO BUS 242925 CKT 1   /*01KAMMER     500.0 - 05KAMMER     765.0
END
CONTINGENCY 'AP_P2-3_WP-500-DRT7A_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235111 TO BUS 235117 CKT 1          /*01 502 J     500.0 - 01KAMMER     500.0
 SET POSTCONTRATING 4289 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3546 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3753 BRANCH FROM BUS 235111 TO BUS 235098 CKT 1 /*01 502 J     500.0 - WOODSIDE     500.0
END
CONTINGENCY 'AP_P2-3_WP-500-DRT10A_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235111 TO BUS 235117 CKT 1          /*01 502 J     500.0 - 01KAMMER     500.0
 OPEN BRANCH FROM BUS 235111 TO BUS 235113 CKT 2                /*01 502 J     500.0 - 01 502JCT    138.0
 SET POSTCONTRATING 4289 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3546 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3753 BRANCH FROM BUS 235111 TO BUS 235098 CKT 1 /*01 502 J     500.0 - WOODSIDE     500.0
END
CONTINGENCY 'AP_P1-3_MP-765-502T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235117 TO BUS 242925 CKT 1   /*01KAMMER     500.0 - 05KAMMER     765.0
END
CONTINGENCY 'AP_P1-2_MP-500-028_SRT-A'
 DISCONNECT BRANCH FROM BUS 235111 TO BUS 235117 CKT 1   /*01 502 J     500.0 - 01KAMMER     500.0
 DISCONNECT BRANCH FROM BUS 235117 TO BUS 242925 CKT 1   /*01KAMMER     500.0 - 05KAMMER     765.0
END
CONTINGENCY 'AP_P2-2_MP-500-007_SRT-SL'
 SET POSTCONTRATING 2811 BRANCH FROM BUS 235235 TO BUS 235107 CKT 1 /*01FLINTRUN   500.0 - 01HARRSN     500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235107 TO BUS 235111 CKT 1 /*01HARRSN     500.0 - 01 502 J     500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235107 TO BUS 235112 CKT 1 /*01HARRSN     500.0 - 01PRNTY      500.0
 SET PRECONTRATING 2179 BRANCH FROM BUS 235235 TO BUS 235107 CKT 1 /*01FLINTRUN   500.0 - 01HARRSN     500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235107 TO BUS 235111 CKT 1 /*01HARRSN     500.0 - 01 502 J     500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235107 TO BUS 235112 CKT 1 /*01HARRSN     500.0 - 01PRNTY      500.0
END
CONTINGENCY 'AP_P2-2_MP-138-013_SRT-A'
 DISCONNECT BRANCH FROM BUS 235334 TO BUS 235349 CKT 1   /*01GLENFL     138.0 - 01HARR T     138.0
 DISCONNECT BRANCH FROM BUS 235334 TO BUS 235375 CKT 1   /*01GLENFL     138.0 - 01NATLCN     138.0
 DISCONNECT BRANCH FROM BUS 235334 TO BUS 235442 CKT 1   /*01GLENFL     138.0 - 01MCALPN     138.0
END
CONTINGENCY 'AP_P2-3_WP-500-DRT6_SRT-SL'
 OPEN BRANCH FROM BUS 235111 TO BUS 235107 CKT 1                /*01 502 J     500.0 - 01HARRSN     500.0
 SET POSTCONTRATING 4289 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3546 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3753 BRANCH FROM BUS 235111 TO BUS 235098 CKT 1 /*01 502 J     500.0 - WOODSIDE     500.0
END
CONTINGENCY 'AP_P2-3_WP-500-DRT9_SRT-SL'
 OPEN BRANCH FROM BUS 235111 TO BUS 235107 CKT 1                /*01 502 J     500.0 - 01HARRSN     500.0
 OPEN BRANCH FROM BUS 235111 TO BUS 235113 CKT 2                /*01 502 J     500.0 - 01 502JCT    138.0
 SET POSTCONTRATING 4289 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3546 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3753 BRANCH FROM BUS 235111 TO BUS 235098 CKT 1 /*01 502 J     500.0 - WOODSIDE     500.0
END
CONTINGENCY 'AP_P1-2_MP-500-022_SRT-A'
 DISCONNECT BRANCH FROM BUS 235107 TO BUS 235111 CKT 1   /*01HARRSN     500.0 - 01 502 J     500.0
END
CONTINGENCY 'PN_P1-1_PN-230-018_SRT-A'
 REMOVE MACHINE 1 FROM BUS 203923   /*AA1-082 G2    23.0
END
CONTINGENCY 'PN_P1-1_PN-230-017_SRT-A'
 REMOVE MACHINE 1 FROM BUS 203922   /*AA1-082 G1    23.0
END
CONTINGENCY 'PN_P2-2_PN-345-1154-W_SRT-A'
 DISCONNECT BRANCH FROM BUS 200930 TO BUS 200929 CKT 1   /*26MAINESBURG 345.0 - 26MAINESBURG 115.0
 REMOVE SWSHUNT FROM BUS 200930 BLOCK 1 STEP 1           /*26MAINESBURG 345.0
 REMOVE SWSHUNT FROM BUS 200930 BLOCK 2 STEP 1           /*26MAINESBURG 345.0
END
CONTINGENCY 'AP_P2-2_WP-230-001T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235175 TO BUS 200726 CKT 1   /*01ELKO       230.0 - 26SHAWVL 2   230.0
 DISCONNECT BRANCH FROM BUS 235175 TO BUS 235158 CKT 1   /*01ELKO       230.0 - 01CARB       230.0
 DISCONNECT BRANCH FROM BUS 235175 TO BUS 235236 CKT 1   /*01ELKO       230.0 - 01QUEHAN     230.0
END
235473 to 235527 ckt 1
235550 to 237506 ckt 1
235306 to 235473 ckt 1
235235 to 235100 ckt 1
235235 to 235100 ckt 2
235235 to 235107 ckt 1
235334 to 235306 ckt 1
235334 to 235442 ckt 1
235107 to 235112 ckt 1
235117 to 235111 ckt 1
235492 to 970800 ckt 1
235527 to 235391 ckt 1
242925 to 235117 ckt 1
970800 to 235550 ckt 1
130836 to 200676 ckt 1

Winter Peak Analysis

The New Service Request AG2-582 was evaluated as a 2100.0 MW (2075.0 MW Capacity) injection in the APS area.

AG2-582 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 2100.0 MW (2100.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AP
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer
AP_P2-3_MP-500-017_SRT-A
BreakerAC144.97 %578.0B837.9343.99
IPDAP
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer
AP_P2-3_MP-500-017_SRT-A
BreakerAC132.79 %578.0B767.55343.99
GD2AP
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer
AP_P2-3_MP-500-016_SRT-A
BreakerAC144.97 %578.0B837.9343.99
IPDAP
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer
AP_P2-3_MP-500-016_SRT-A
BreakerAC132.79 %578.0B767.55343.99

Details for 01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-017_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-017_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:144.97 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:837.9
MW Contribution:343.99
Bus #Bus NameTypeMW Contribution
23751201ROTHROCK
Solar/Wind Helper
0.052
23562501BACKB
Solar/Wind Helper
0.04
23751101LEADS_P59
Solar/Wind Helper
0.075
970935AG2-582 GEN
50/50
343.992
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.154
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.112
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.264
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.457
NYPJM->LTFIMP_NY
CLTF
0.643
LGEELTFEXP_LGEE->PJM
CLTF
0.958
WECLTFEXP_WEC->PJM
CLTF
0.52
CPLELTFEXP_CPLE->PJM
CLTF
0.248
TVALTFEXP_TVA->PJM
CLTF
1.079
MECLTFEXP_MEC->PJM
CLTF
2.193
LAGNLTFEXP_LAGN->PJM
CLTF
2.167
SIGELTFEXP_SIGE->PJM
CLTF
0.071

Details for [AG2-582] 01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-017_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-017_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.79 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:767.55
MW Contribution:343.99
IPD Plant:AG2-582
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
PJM_IPD
343.992

Details for 01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer l/o AP_P2-3_MP-500-016_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer
Contingency Name:
AP_P2-3_MP-500-016_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:144.97 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:837.9
MW Contribution:343.99
Bus #Bus NameTypeMW Contribution
23751201ROTHROCK
Solar/Wind Helper
0.052
23562501BACKB
Solar/Wind Helper
0.04
23751101LEADS_P59
Solar/Wind Helper
0.075
970935AG2-582 GEN
50/50
343.992
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.154
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.112
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.264
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.457
NYPJM->LTFIMP_NY
CLTF
0.643
LGEELTFEXP_LGEE->PJM
CLTF
0.958
WECLTFEXP_WEC->PJM
CLTF
0.52
CPLELTFEXP_CPLE->PJM
CLTF
0.248
TVALTFEXP_TVA->PJM
CLTF
1.079
MECLTFEXP_MEC->PJM
CLTF
2.193
LAGNLTFEXP_LAGN->PJM
CLTF
2.167
SIGELTFEXP_SIGE->PJM
CLTF
0.071

Details for [AG2-582] 01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer l/o AP_P2-3_MP-500-016_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer
Contingency Name:
AP_P2-3_MP-500-016_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.79 %
Rating:578.0 MVA
Rating Type:B
MVA to Mitigate:767.55
MW Contribution:343.99
IPD Plant:AG2-582
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
PJM_IPD
343.992
CONTINGENCY 'AP_P2-3_MP-500-017_SRT-A'
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235100 CKT 2   /*01FLINTRUN   500.0 - 01FLINTRN    138.0
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235107 CKT 1   /*01FLINTRUN   500.0 - 01HARRSN     500.0
END
CONTINGENCY 'AP_P2-3_MP-500-016_SRT-A'
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235100 CKT 1   /*01FLINTRUN   500.0 - 01FLINTRN    138.0
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235107 CKT 1   /*01FLINTRUN   500.0 - 01HARRSN     500.0
END
235235 to 235100 ckt 1
235235 to 235100 ckt 2

Light Load Analysis

The New Service Request AG2-582 was evaluated as a 2100.0 MW injection

AG2-582 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 2100.0 MW (2100.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AP
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer
AP_P2-3_MP-500-017_SRT-A
BreakerAC124.11 %527.0B654.05194.57
IPDAP
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer
AP_P2-3_MP-500-017_SRT-A
BreakerAC109.23 %527.0B575.67341.17
GD2AP
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer
AP_P2-3_MP-500-016_SRT-A
BreakerAC124.11 %527.0B654.05194.57
IPDAP
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer
AP_P2-3_MP-500-016_SRT-A
BreakerAC109.23 %527.0B575.67341.17

Details for 01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-017_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-017_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.11 %
Rating:527.0 MVA
Rating Type:B
MVA to Mitigate:654.05
MW Contribution:194.57
Bus #Bus NameTypeMW Contribution
23751201ROTHROCK
Solar/Wind Helper
0.699
23562501BACKB
Solar/Wind Helper
0.948
23751101LEADS_P59
Solar/Wind Helper
2.043
970935AG2-582 GEN
50/50
194.575
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.695
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.792
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.423
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.785
NYPJM->LTFIMP_NY
CLTF
0.609
LGEELTFEXP_LGEE->PJM
CLTF
0.996
WECLTFEXP_WEC->PJM
CLTF
0.539
CPLELTFEXP_CPLE->PJM
CLTF
0.357
TVALTFEXP_TVA->PJM
CLTF
1.12
MECLTFEXP_MEC->PJM
CLTF
2.28
LAGNLTFEXP_LAGN->PJM
CLTF
2.283
SIGELTFEXP_SIGE->PJM
CLTF
0.074
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.994

Details for [AG2-582] 01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-017_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-017_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.23 %
Rating:527.0 MVA
Rating Type:B
MVA to Mitigate:575.67
MW Contribution:341.17
IPD Plant:AG2-582
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
PJM_IPD
341.169

Details for 01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer l/o AP_P2-3_MP-500-016_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer
Contingency Name:
AP_P2-3_MP-500-016_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.11 %
Rating:527.0 MVA
Rating Type:B
MVA to Mitigate:654.05
MW Contribution:194.57
Bus #Bus NameTypeMW Contribution
23751201ROTHROCK
Solar/Wind Helper
0.699
23562501BACKB
Solar/Wind Helper
0.948
23751101LEADS_P59
Solar/Wind Helper
2.043
970935AG2-582 GEN
50/50
194.575
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.695
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.792
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.423
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.785
NYPJM->LTFIMP_NY
CLTF
0.609
LGEELTFEXP_LGEE->PJM
CLTF
0.996
WECLTFEXP_WEC->PJM
CLTF
0.539
CPLELTFEXP_CPLE->PJM
CLTF
0.357
TVALTFEXP_TVA->PJM
CLTF
1.12
MECLTFEXP_MEC->PJM
CLTF
2.28
LAGNLTFEXP_LAGN->PJM
CLTF
2.283
SIGELTFEXP_SIGE->PJM
CLTF
0.074
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.994

Details for [AG2-582] 01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer l/o AP_P2-3_MP-500-016_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01FLINTRN 500.0/138.0 kV Ckt 2 transformer
Contingency Name:
AP_P2-3_MP-500-016_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.23 %
Rating:527.0 MVA
Rating Type:B
MVA to Mitigate:575.67
MW Contribution:341.17
IPD Plant:AG2-582
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
PJM_IPD
341.169
CONTINGENCY 'AP_P2-3_MP-500-017_SRT-A'
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235100 CKT 2   /*01FLINTRUN   500.0 - 01FLINTRN    138.0
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235107 CKT 1   /*01FLINTRUN   500.0 - 01HARRSN     500.0
END
CONTINGENCY 'AP_P2-3_MP-500-016_SRT-A'
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235100 CKT 1   /*01FLINTRUN   500.0 - 01FLINTRN    138.0
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235107 CKT 1   /*01FLINTRUN   500.0 - 01HARRSN     500.0
END
235235 to 235100 ckt 1
235235 to 235100 ckt 2

Short Circuit Analysis

Short Circuit analysis is not performed as part of the Phase I System Impact Study. Short Circuit analysis will commence in the Phase II System Impact Study.

Stability Analysis

Stability analysis is not performed as part of the Phase I System Impact Study. Stability analysis will commence in the Phase II System Impact Study.

Reactive Power Analysis

Reactive Power analysis is not performed as part of the Phase I System Impact Study. Reactive Power analysis will commence in the Phase II System Impact Study.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-018Powerton-Goodings GroveIn Service
AA1-095Halfway-Marlowe 34.5kVIn Service
AA2-119Glen Falls 138kVEngineering & Procurement
AA2-184Atlantic-Red Bank 34kVIn Service
AB1-001Absecon 12 kVIn Service
AB1-006Meadow Lake 345kVIn Service
AB1-096Carroll-Mt. Airy 34.5kVIn Service
AB1-124Carroll-Monocacy 34.5kVPartially in Service - Under Construction
AB1-125Carroll-Monocacy 34.5kVIn Service
AB1-127St. Thomas-Guilford 34.5kVIn Service
AB1-128St. Thomas-Mercersburg 34.5kVIn Service
AB1-138Navy 34.5kVIn Service
AB1-139Metuchen 26kVIn Service
AB1-141Church-Wye Mills 138 kV IIn Service
AB1-142Church-Wye Mills 138 kV IIIn Service
AB1-176Price 25kV IIEngineering & Procurement
AB2-029Remington 34.5kVIn Service
AB2-032Church-Wye Mills 138 kVIn Service
AB2-037Keeney-Steele 230kVUnder Construction
AB2-049Gloucester Township 12kVIn Service
AB2-067Kammer-Vassell 765kVIn Service
AB2-093Ormet 138kVIn Service
AB2-133Chestertown 69kVUnder Construction
AB2-135Church-Kent 69kVIn Service
AB2-136Cambridge-West Cambridge 69kVUnder Construction
AB2-153Church-Wye Mills 138 kVIn Service
AB2-157Prince George's County 12kVIn Service
AB2-158Louisa-South Anna 230kVIn Service
AB2-170East Lima-Marysville 345kVIn Service
AB2-179Townsend 138kVIn Service
AC1-001Delano 138kVIn Service
AC1-010Gloucester 26kVUnder Construction
AC1-017Levittown 13 kVIn Service
AC1-030Cinnaminson 13kVIn Service
AC1-044Kammer-Vassell 765kVIn Service
AC1-068Atlanta 69kV IIn Service
AC1-069Atlanta 69kV IIIn Service
AC1-074Jacksonville-Renaker 138kV IIn Service
AC1-076Locust Grove-Paytes 115kVIn Service
AC1-078Beatty-London 138kVIn Service
AC1-082Ravenswood-Hemlock 69kVUnder Construction
AC1-085Stuart-Clinton 345kVIn Service
AC1-089Hillsboro-Wildcat 138kVIn Service
AC1-091Cedar Creek 138kV IEngineering & Procurement
AC1-092Cedar Creek 138kV IIEngineering & Procurement
AC1-093Cedar Creek 138kV IIIEngineering & Procurement
AC1-094Cedar Creek 138kV IVEngineering & Procurement
AC1-101Johns Creek-Excel 138kV ISuspended
AC1-102Johns Creek-Excel 138kV IISuspended
AC1-120Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-121Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-158Spotsylvania 500kVIn Service
AC1-165Atlanta 69kV IIIIn Service
AC1-166Atlanta 69kV IVIn Service
AC1-167Mark Center 69kVUnder Construction
AC1-174Losantville 345kVIn Service
AC1-175Losantville 345kVIn Service
AC1-188Rio-Lick 138kVEngineering & Procurement
AC1-194Elk 138kVActive
AC2-023Hebron 69kVEngineering & Procurement
AC2-029Circleville 138kVSuspended
AC2-044Maddox Creek 345kVSuspended
AC2-059Biers Run-Circleville 138kVIn Service
AC2-060Buckskin 69kVIn Service
AC2-061Hillsboro-Clinton 138kVIn Service
AC2-067Camden-Crystal I 69kVEngineering & Procurement
AC2-068Camden-Crystal II 69kVEngineering & Procurement
AC2-075Jacksonville-Renaker 138 kVIn Service
AC2-088S. Bethel-Brown 69kVIn Service
AC2-090Losantville 345kVIn Service
AC2-111College Corner 138kVEngineering & Procurement
AC2-120Ripley 69kVIn Service
AC2-136East Hagerstown 12kVUnder Construction
AC2-157Sullivan 345 kVUnder Construction
AC2-176Jay 138 kVIn Service
AC2-186Harrington 25kVUnder Construction
AC2-187Harrington 69kVUnder Construction
AC2-188Harrington 69 kVUnder Construction
AC2-195Galion-Roberts South 138 kVUnder Construction
AD1-020Hunterstown-Lincoln 115 kVIn Service
AD1-060Mercersburg-Milnor 34.5 kVIn Service
AD1-061McConnelsburg-Mercersburg 34 kVIn Service
AD1-100Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVUnder Construction
AD1-101Continental 69 kVIn Service
AD1-106North Waldo-Wild Creek 138 kVSuspended
AD1-115Mountain Run-Mitchell 115 kVEngineering & Procurement
AD1-119Payne 69 kVIn Service
AD1-128Modoc-Delaware 138 kVPartially in Service - Under Construction
AD1-130Hardin Switch 345 kVIn Service
AD1-136South Bethel-Brown 69 kVIn Service
AD1-140Greene-Clark 138 kVEngineering & Procurement
AD1-155Meadow Brook-Strasburg 138 kVIn Service
AD2-009McConnellsburg 138 kVIn Service
AD2-016Biers Run-Circleville 138 kVIn Service
AD2-020Valley 138 kVEngineering & Procurement
AD2-027Camden Switch 26 kVIn Service
AD2-031Martinsville-Wilmington 69 kVIn Service
AD2-038Powerton-Nevada 345 kVUnder Construction
AD2-042Camden Switch 26 kV IIIn Service
AD2-047Davis Creek 138 kVSuspended
AD2-048Cynthia-Headquarters 69 kVUnder Construction
AD2-058St. Barnabas 13 kVIn Service
AD2-060Davis Creek 138kVEngineering & Procurement
AD2-065Atco 12 kVIn Service
AD2-066Mazon-Crescent Ridge 138 kVEngineering & Procurement
AD2-067Centerburg 138kVEngineering & Procurement
AD2-070Gilbert-Morris Park 34.5kVIn Service
AD2-071Strawton-Deer Creek 138 kVSuspended
AD2-079Capitol Ave 34.5kVIn Service
AD2-086Hardin Switch 345 kVIn Service
AD2-092Marysville 345kVUnder Construction
AD2-093Marysville 345kVUnder Construction
AD2-115Lyons-Moselem 69kVIn Service
AD2-116Hokes-Grantley 69 kVIn Service
AD2-135Williamstown 12kVPartially in Service - Under Construction
AD2-163Broadview-Tangy 138 kVIn Service
AD2-180Elk Garden-Parr Run 138kVIn Service
AE1-040Greenfield 69 kVIn Service
AE1-041Edison 4kVIn Service
AE1-071Shade Gap-Roxbury 115 kVIn Service
AE1-081Landing 12.47 kVIn Service
AE1-090Hardin Switch 345 kVIn Service
AE1-091West Newton-Lynn 138 kVSuspended
AE1-092Blue Jacket-Kirby 138 kVActive
AE1-101McConnellsburg-Texas Eastern 138 kVIn Service
AE1-102Maddox Creek 345 kVSuspended
AE1-109Frenchs Mill 34 kVIn Service
AE1-113Mole Creek 345 kVEngineering & Procurement
AE1-142Manitou-Pleasant Plains 34.5 kVIn Service
AE1-156Quakertown Solar II 34.5 kVPartially in Service - Under Construction
AE1-166Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE1-170Kenzie Creek-Colby 138 kVSuspended
AE1-172Loretto-Wilton CenterActive
AE1-185Hokes-Jackson 69 kVIn Service
AE1-196Hokes-Jackson 69 kV IIIn Service
AE1-207Mississinewa-Gaston 138 kVSuspended
AE1-208Delaware-Van Buren 138 kVSuspended
AE1-209Desoto 345 kVSuspended
AE1-210Desoto 345 kVSuspended
AE1-227South Cumberland 69 kVSuspended
AE1-229Deepwater-Upper Pittsgrove 138 kVSuspended
AE1-245Haviland 138 kVUnder Construction
AE2-045Olive-Reynolds 345 kVEngineering & Procurement
AE2-048Muskingum-W. Millersport 345 kVEngineering & Procurement
AE2-054Warfordsburg 34 kVIn Service
AE2-072East Leipsic-Richland 138 kVIn Service
AE2-089Pennville-Adams 138 kVEngineering & Procurement
AE2-136Muskingum River-W. Millersport 345 kVEngineering & Procurement
AE2-139East Towanda-Grover 230 kVEngineering & Procurement
AE2-148Beatty-Greene 345 kVIn Service
AE2-152Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE2-169Delaware-Van Buren 138 kVSuspended
AE2-172Mississinewa-Gaston 138 kVSuspended
AE2-175Jackson-Long Pond 69 kVPartially in Service - Under Construction
AE2-194Congress-Toronto 138 kVSuspended
AE2-206East Sidney-Quincy 138 kVIn Service
AE2-214Cole 345 kVEngineering & Procurement
AE2-217East Springfield-London 138 kVEngineering & Procurement
AE2-219Bluff Point-Randolph 138 kVSuspended
AE2-220Losantville 345 kVEngineering & Procurement
AE2-221Clinton-Stuart 345 kVUnder Construction
AE2-226Millville-Old Chapel 138 kVEngineering & Procurement
AE2-230Bartonsville-Meadow Brook 138 kVIn Service
AE2-234Liberty Center-Buckeye Tap 69 kVEngineering & Procurement
AE2-236Columbia-Northeast 138 kVSuspended
AE2-255Molecreek 345 kVEngineering & Procurement
AE2-267Woodsdale 345 kVEngineering & Procurement
AE2-297Madison-Tanners Creek 138 kVIn Service
AE2-298Cavett Switch - West Van Wert 69 kVEngineering & Procurement
AE2-305Givens-Mechanicsburg 138 kVEngineering & Procurement
AE2-306Gunn Road 345 kVUnder Construction
AE2-309Carlos Junction-Lonaconing 34.5 kVIn Service
AE2-315Yankee Tap 69 kVIn Service
AE2-318Ford-Cedarville 138 kVSuspended
AE2-322Mark Center 69 kVUnder Construction
AE2-323Twin Branch-Guardian 138 kVUnder Construction
AE2-325Valley 138 kVActive
AE2-341Sandwich-Plano 138 kVActive
AE2-342Woodstock 69 kVEngineering & Procurement
AF1-007Indian River 230 kV ISuspended
AF1-022Lake Lynn-Uniontown 25 kVIn Service
AF1-030Sandwich-Plano 138 kVActive
AF1-045Cedarville-Ford 138 kVSuspended
AF1-051Gavin 765 kVIn Service
AF1-053Givens-Mechanicsburg 138 kVEngineering & Procurement
AF1-054Givens-Mechanicsburg 138 kVEngineering & Procurement
AF1-062Jug Street 138 kVEngineering & Procurement
AF1-071College Corner 138 kVEngineering & Procurement
AF1-078East Sidney-Quincy 138 kVIn Service
AF1-088Sullivan 345 kVActive
AF1-091Varner - Sowers 138 kVEngineering & Procurement
AF1-092Huntington Jct. 138 kVSuspended
AF1-118Sorenson-Desoto 345 kVEngineering & Procurement
AF1-119Keystone-Desoto 345 kVEngineering & Procurement
AF1-122Cardington-Liberty 69 kVSuspended
AF1-130Inez 138 kVSuspended
AF1-136Warfordsburg-Purcell Junction 34.5 kVEngineering & Procurement
AF1-147Poland Rd-Runway DP 230kVUnder Construction
AF1-158Edison-Gravel Pit 138 kVIn Service
AF1-162Inez 138 kVEngineering & Procurement
AF1-176Corey 138 kVActive
AF1-202Keystone-Desoto 345 kVUnder Construction
AF1-204Eugene 345 kVActive
AF1-207Reynolds-Olive #1 345 kVEngineering & Procurement
AF1-215Olive-Reynolds 345 kVIn Service
AF1-223Keystone-Desoto 345 kVUnder Construction
AF1-227Marysville – Gunn Road 345 kVIn Service
AF1-228Beatty-Greene 345 kVEngineering & Procurement
AF1-229Galion-South Berwick 345 kVEngineering & Procurement
AF1-233Flemingsburg – Spurlock 138kVActive
AF1-249Nickel 12.47 kVIn Service
AF1-254Milnor-Huyetts 34.5 kVUnder Construction
AF1-262Upper Pittsgrove 12 kVIn Service
AF1-264Runnemede 13 kVIn Service
AF1-268Desoto-Jay 138 kVEngineering & Procurement
AF1-275Cole 345 kVEngineering & Procurement
AF1-282Stuart-Clinton 345 kVEngineering & Procurement
AF1-283Stuart-Clinton 345 kVEngineering & Procurement
AF1-285Gunn Road 345 kVUnder Construction
AF1-290Feagans Mill-Millville 138 kVIn Service
AF1-291ABartonsville-Meadow Brook 138 kVIn Service
AF1-299Otter Point 34.5 kV IIn Service
AF1-300Otter Point 34.5 kV IIIn Service
AF1-320Merrill Creek 115 kVEngineering & Procurement
AF1-322Meadow Lake 345 kVEngineering & Procurement
AF2-008Sullivan 345 kVActive
AF2-014Maddox Creek 345 kVEngineering & Procurement
AF2-018Inez 138 kVEngineering & Procurement
AF2-048Rio-Lick 138 kVEngineering & Procurement
AF2-068Jay 138 kVActive
AF2-075Bartonsville-Meadow Brook 138 kV IIIIn Service
AF2-078Reynolds-Olive #1 345 kVEngineering & Procurement
AF2-083Kenzie Creek-Stone Lake 69 kVUnder Construction
AF2-095Davis Creek 138 kVActive
AF2-103Haviland 138 kVIn Service
AF2-111North Clark-Spurlock 345 kVActive
AF2-122Kirk 138 kVUnder Construction
AF2-132Reynolds-Olive #1 345 kVUnder Construction
AF2-133Reynolds-Olive #2 345 kVUnder Construction
AF2-134Olive-Reynolds #2 345 kVIn Service
AF2-138Flanders-West Wharton 34.5 kVIn Service
AF2-139Gilbert-Warren Glen 34.5 kVIn Service
AF2-142Nevada 345 kVActive
AF2-143Powerton-Nevada 345 kVActive
AF2-149Sharp Road 69 kVEngineering & Procurement
AF2-150Galion 138 kVUnder Construction
AF2-162Keystone-Desoto 345 kVEngineering & Procurement
AF2-173Desoto 345 kVActive
AF2-177Sorenson-DeSoto #2 345 kVActive
AF2-192Frenchtown Solar-West Flemington 34.5 kVSuspended
AF2-205Olive-Reynolds #2 345 kVEngineering & Procurement
AF2-224Allen 345 kVEngineering & Procurement
AF2-229Roxbury 23 kVEngineering & Procurement
AF2-238Mansfield-South Troy 34.5 kVEngineering & Procurement
AF2-247Bustleton 13.2 kVIn Service
AF2-250Edgewood 12 kV IIIIn Service
AF2-291Sporn South-Leon 138 kVEngineering & Procurement
AF2-294Thompson 34.5 kVSuspended
AF2-298Crown-New Lebanon 69 kVEngineering & Procurement
AF2-307Hope-Belvins Valley Tap 69 kVActive
AF2-325Jacktown 12 kVEngineering & Procurement
AF2-335Delaware-Royerton 138 kVActive
AF2-350Kensington 138 kVActive
AF2-354Washington 34.5 kV IIEngineering & Procurement
AF2-356Albright-Mt. Zion 138 kVUnder Construction
AF2-359Olive-University Park 345 kVEngineering & Procurement
AF2-371Harrison-Good Hope 138 kVEngineering & Procurement
AF2-378Cambridge 12 kVEngineering & Procurement
AF2-379Princess Anne 25 kVUnder Construction
AF2-383Tolna 115 kVWithdrawn
AF2-388Keystone-Desoto 345 kVActive
AF2-396Stinger 138 kVActive
AF2-440Hillsboro-Middleboro 138 kVEngineering & Procurement
AG1-017Jay 138 kVUnder Construction
AG1-024Centerburg 138 kVEngineering & Procurement
AG1-034Centerburg 138 kVEngineering & Procurement
AG1-039Galion 138 kV IIUnder Construction
AG1-047Jay 138 kVEngineering & Procurement
AG1-107Hillsboro-Middleboro 138 kVEngineering & Procurement
AG1-118Sugar Grove-Waterman 138kVActive
AG1-125Marysville-Flatlick 765 kVEngineering & Procurement
AG1-126Marysville-Flatlick 765 kVEngineering & Procurement
AG1-188Manitou-Oyster Creek 34.5 kVEngineering & Procurement
AG1-189Oyster Creek-Bamber Lake 34.5Engineering & Procurement
AG1-191Chester-Pohatcong Mountain 34.5 kVPartially in Service - Under Construction
AG1-223Larrabee-Allaire 34.5 kVUnder Construction
AG1-226Dequine-Eugene 345 kVActive
AG1-232Magley 138 kVEngineering & Procurement
AG1-237Dequine-Eugene 345 kVEngineering & Procurement
AG1-254Salem-Woodstown 69 kVEngineering & Procurement
AG1-302Olive-Reynolds #1 345 kVUnder Construction
AG1-323Blue Jacket 138 kVActive
AG1-324Jay-Desoto 138 kVEngineering & Procurement
AG1-348Pequest River-Washington 34.5 kVIn Service
AG1-349Olive-Reynolds #2 345 kVEngineering & Procurement
AG1-351Harrison-Good Hope 138 kVEngineering & Procurement
AG1-363Black Oak-Hatfield 500 kVEngineering & Procurement
AG1-365Allen 345 kVEngineering & Procurement
AG1-366Allen 345 kVEngineering & Procurement
AG1-367DeSoto 345 kVActive
AG1-368Tillman 138 kVEngineering & Procurement
AG1-369Logtown 138 kVEngineering & Procurement
AG1-375Sorenson-Desoto 345 kVActive
AG1-397Walston 12 kVWithdrawn
AG1-410Maddox Creek-RP Mone 345 kVActive
AG1-433Keystone-DeSoto 345 kVActive
AG1-436Olive-University Park 345 kVActive
AG1-447Olive-University Park 345 kVActive
AG1-469Gordonsville 34.5 kVEngineering & Procurement
AG1-478Wilmington 34.5 kVEngineering & Procurement
AG1-480Shawnee 34.5 kVEngineering & Procurement
AG1-482Hamilton 115 kVWithdrawn
AG1-495Gilbert-Rocktown 34.5 kVEngineering & Procurement
AG1-499Lambs 12.47 kVUnder Construction
AG1-554South Kenton 138 kVEngineering & Procurement
AG1-555Dequine 345 kVEngineering & Procurement
AG1-559Caroline Pines 22 kVEngineering & Procurement
AG2-029Forest G. Hipple-Collingwood 345 kVActive
AG2-057Cardington-Liberty 69 kV IIActive
AG2-063North Hampton 69 kVActive
AG2-072Rockport 765 kVActive
AG2-081Mt. Sterling-Fogg Pike 69 kVActive
AG2-085Delaware-Royerton 138 kVActive
AG2-104Marysville-Flatlick 765 kVActive
AG2-106Marysville-Flatlick 765 kVActive
AG2-107Marysville-Flatlick 765 kVActive
AG2-114Dresden-Pontiac Midpoint 345 kVActive
AG2-119Galion-Roberts South 138 kV IIActive
AG2-125Camden-Crystal 69 kVActive
AG2-126Eugene 345 kVActive
AG2-149Galion-South Berwick 345 kVActive
AG2-159Williamstown 69 kVActive
AG2-162Jefferson-Greentown 765 kVActive
AG2-163Dequine-Eugene 345 kVActive
AG2-164Jefferson-Greentown 765 kVActive
AG2-165Dumont-Greentown 765 kVActive
AG2-191Mississinewa 138 kVActive
AG2-192Mississinewa 138 kVActive
AG2-212Dumont-Greentown 765 kVActive
AG2-216East Sidney-Quincy 138 kVActive
AG2-219Jefferson-Greentown 765 kVActive
AG2-230Dumont 345 kVActive
AG2-245Olive - Reynolds #1 345 kVActive
AG2-328Dumont - Greentown 765 kVActive
AG2-329S Berwick - Galion 345 kVActive
AG2-330Dumont - Greentown 765 kVActive
AG2-331Jefferson-Greentown 765 kVActive
AG2-378North Hampton – Medway 69 kVActive
AG2-385North Hampton 69 kVActive
AG2-400Allen 345 kVActive
AG2-401Losantville 345 kVActive
AG2-405Continental 69 kVActive
AG2-406Payne 69 kVActive
AG2-408Allen 345 kVActive
AG2-444Bixby - Biers Run 345 kVActive
AG2-448Cross School - Westvaco 138 kVActive
AG2-449Jefferson-Greentown 765 kVActive
AG2-453Lasalle - Plano 345 kVActive
AG2-456Pierce Brook-Lewis Run 230 kVActive
AG2-457Pierce Brook - Lewis Run 230 kVActive
AG2-487Madison - Tanners Creek 138 kVActive
AG2-491Meadow Lake 345 kVActive
AG2-505Westvaco - Mt Zion 138 kVActive
AG2-519Royerton - Desoto 138 kVActive
AG2-524LaSalle Station - Mazon 138 kVActive
AG2-548Corwin - Elk 138 kVActive
AG2-550Bluff Point - Randolph 138 kVActive
AG2-551Bluff Point - Randolph 138 kVActive
AG2-585Kensington 138kVActive
AG2-589Ravenswood - Hemlock 69 kVActive
AG2-637Randolph - Hodgin 138 kVActive
AG2-665Corwin - Elk 138 kVActive
AH1-004Avon - Renaker 138 kVActive
AH1-055Kyger Creek - Don Marquis 345 kVActive
AH1-059Sharp Road 69 kVActive
AH1-060Cardington-Liberty 69 kV IIIActive
AH1-075North Waldo - Wild Creek 138 kVActive
AH1-153Dumont 345 kVActive
AH1-272Argenta - Twin Branch 345 kVActive
AH1-282Galion - Ohio Central 345 kVActive
AH1-285Sandwich 138 kVActive
AH1-292Sullivan 345 kVActive
AH1-302Olive - Reynolds 345 kVActive
AH1-304Delaware-Van Buren 138 kVActive
AH1-305Olive - Reynolds 345 kVActive
AH1-306Mississinewa-Gaston 138 kVActive
AH1-308Pennville - Adams 138 kVActive
AH1-309Kenzie Creek-Colby 138 kVActive
AH1-327Hardin Switch 345 kVActive
AH1-328Blue Jacket - Kirby 138 kVActive
AH1-337Randolph - Hodgin 138 kVActive
AH1-339West Crawford 69 kVActive
AH1-340Cheat Lake-Ruthbelle 138 kVActive
AH1-357Pierce Brook-Lewis Run 230kVActive
AH1-358Pierce Brook-Lewis Run 230kVActive
AH1-359Pierce Brook - Lewis Run 230 kVActive
AH1-360Pierce Brook - Lewis Run 230 kVActive
AH1-391Olive 138 kVActive
AH1-392Gravel Pit-Kankakee 138 kVActive
AH1-482Olive - Reynolds #2 345 kVActive
AH1-537Pierce - Kyger Creek 345 kVActive
AH1-539South Kenton 138 kVActive
AH1-542Crissinger-Kirby 138kVActive
AH1-543Mulberry – Tazewell 345 kVActive
AH1-545Wylie Ridge-Tidd 345kVActive
AH1-567University Park 138 kVActive
AH1-570Headquarters - Millersburg Junction 69 kVActive
AH1-571Headquarters - Millersburg Junction 69 kVActive
AH1-588Lewis Run - Pierce Brook 230 kVActive
AH1-589Lewis Run - Pierce Brook 230 kVActive
AH1-661Cannelville 12.47 kVActive
AH1-664Goddard-Plumville 138 kVActive
AH1-665Goddard-Plumsville 138 kV IIActive
AH1-666Flemingsburg - Spurlock 138 kVActive
AH1-669Circleville-Biers Run 138 kVActive
AH1-680Sammis - South Canton 345 kVActive
AH1-686Hanging Rock 765 kVActive
AH1-690Bay Shore - Lallendorf 345 kVActive
AH1-698Braidwood 345 kVActive
AH1-699Wellsville 345 kVActive
AH1-704Hannibal 138 kVActive
AH1-714Lasalle 345 kVActive
AH1-719Beverly 345 kVActive
AH1-735Richland 138 kVActive
U2-030Four Mile Ridge Wind 138kVIn Service
U2-072East Lima-Marysville 345kVIn Service
U2-073Frostburg 138kV IIIn Service
V1-011Haviland 138kVIn Service
V3-007Desoto-Tanners Creek #1 345kVIn Service
V4-067Cates Road Egg Harbor Township 12kVDeactivated
V4-073Yankee 12.5kVIn Service
W1-003Oak HallIn Service
W1-004Oak HallIn Service
W1-005Oak HallIn Service
W1-006Oak HallIn Service
W1-056Ada-Dunkirk 69kVIn Service
W1-130Vine Road 12kVIn Service
W2-030Egg Harbor TownshipIn Service
W3-077Broadway-Stewartsville 34.5kVIn Service
X1-042WatervlietIn Service
X3-005Wildwood 12kVIn Service
X3-066Church Hill 69kVIn Service
Y1-079Wye Mills 69kVIn Service
Y1-080Dorchester 12kVIn Service
Y3-023Country Side 12kVIn Service
Y3-024Bluff Point 12kVIn Service
Y3-058Rockawalkin 69kVIn Service
Z2-076Worcester South 25kVIn Service
Z2-077Worcester North 25kVIn Service
Z2-115Deer Creek 12.47kVIn Service
Z2-116Twin Branch 12.47kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)Identified Impacts

No cost allocated AFS Tie Line reinforcements were identified for this project in the Phase I System Impact Study load flow analysis.


System Reinforcement
Type
Load Flow
TO
NYISO
RTEP ID / TO ID
(Pending) / NYISO_CY17_13387
Title
East Sayre-North Waverly 115kV line upgrade - NYSEG (NYISO CY17 driven upgrade)
Description
North Waverly terminal equipment upgrades and a line reconductor of the NYSEG portion of the East Sayre – North Waverly 115kV line. (Install approximately twenty-six (26) new steel pole structures, one (1) 795 kcmil (26/7) ACSR conductor, and 36 Fiber OPGW). Final expected SUM ratings with both NYSEG & Penelec work complete = 218/251 MVA SN/SE. NYSEG uses LTE for Rate B, not STE like FirstEnergy. The earliest projected in-service date for this project is in 2026, but that timeframe may shift to complete the terminal equipment work at North Waverly. The final trip setting for the line will be updated during engineering and construction, but it must meet at least 176 MVA. Note: NYISO customers Q387, Q421, Q505 require an upgrade on the East Sayre-North Waverly 115 kV line as part of the CY17 study. NYSEG will complete work at North Waverly substation and the line reconductor/rebuild. FirstEnergy will complete work at East Sayre substation. Per NYISO, the rating that must be achieved for CY17 is 176/176/176 MVA Summer Normal/LTE/STE. NYSEG confirmed the new line ratings for the NYISO side (218/251/282 MVA Summer Normal/LTE/STE; 265/291/318 MVA Winter Normal/LTE/STE), but the East Sayre terminal needs to be upgraded since it is limiting. NYSEG uses LTE for Rate B, not STE like FirstEnergy.
Total Cost ($USD)
$10,525,000
Allocated Cost ($USD)
$0
Time Estimate
32 Months

Info

Note: AG2-582 contributes to the loading of an overloaded tie line facility between PJM and an affected system entity, which was identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line and will be confirmed in subsequent study phases, along with cost allocation of such upgrade if applicable, in coordination with the affected system.

FacilityContingency
N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line(Any)
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with potential Affected System impacts. PJM initiates coordination with each Affected System Operator by providing a list of New Service Requests in the Cycle with potential impacts to their respective system. If the Affected System Operator indicates an Affected System Study is required, PJM will notify the Project Developer or Eligible Customer of the need for an Affected System Study. See below if any Affected System Operator requires a study for this project:

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Phase I analysis results, this project may have a cost responsibility for the following System Reinforcements:

AG2-582 System Reinforcements:
TORTEP IDTitleAllocated Cost ($USD)
APS(Pending) / TC2-APS-009.aReconductor Pruntytown - Shinns Run 138kV line including line drops at Shinns Run$36,786,038
APS(Pending) / TC2-APS-016.aReplace 500/138 kV TR1 at Flint Run$28,558,871
APS(Pending) / TC2-APS-015.aReplace 500/138 kV TR2 at Flint Run$28,558,871
APS(Pending) / TC2-APS-011.aReconductor Glen Falls - Mcalpin transmission line.$16,988,135
APS(Pending) / TC2-APS-012.bReconductor Bridgeport Hill - Glen Falls transmission line$16,031,404
APS(Pending) / TC2-APS-029Reconductor (Possible Rebuild) ~3.4 mile of Barnetts Run - Bridgeport Hill 138 kV transmission line. Including Wave trap drop and transmission line drop at Barnetts Run$13,223,334
APS(Pending) / TC2-APS-002.bReconductor (Possible Rebuild) ~3.8 miles of AG2-505 - Beryl 138kV transmission line$9,561,669
APS(Pending) / TC2-PH1-025Reconductor (Possible Rebuild) ~2 miles of Barnetts Run-Shinns Run 138kV line including T-line drops at Barnetts Run & Shinns Run$8,443,469
APS(Pending) / TC2-APS-028Reconductor Mt Zion - AG2-505 138kV transmission line$8,051,517
APS(Pending) / TC2-APS-016.bReplace 6 138 kV Disc Switches and 5 Breaker Leads at Flint Run$1,826,164
APS(Pending) / TC2-APS-015.bReplace 6 138 kV Disc Switches and 5 Breaker Leads at Flint Run$1,826,164
APS(Pending) / TC2-APS-009.bUpgrade Meters at Pruntytown$1,098,322
APS(Pending) / TC2-APS-023.bReconductor (Possible Rebuild) ~1 mile of Beryl - Cross School 138 kV transmission line.$1,016,011
APS(Pending) / TC2-APS-012.aReconductor 556.5 ACSR 26/7-line exit at Bridgeport Hill$977,534
APS(Pending) / TC2-APS-016.cReplace SCCIR 3" Pipe A-frame closest to Disc SW A-39$597,737
APS(Pending) / TC2-APS-011.bReplace Breaker Failure Relaying at Mcalpin$509,895
APS(Pending) / TC2-APS-012.dReplace SEL-321 impedance relay and 1200 CT at Glen Falls$396,495
APS(Pending) / TC2-APS-002.aUpgrade Disc Switch at Beryl$189,395
APS(Pending) / TC2-APS-012.cUpgrade/Replace (3) 10 Amp Bitronics Meters at Glen Falls$157,861
APS(Pending) / TC2-PH1-023.aUpgrade 138 kV Disc Sw 1306_Q at Beryl$88,586
Grand Total:$174,887,472

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC2-APS-009.a
Title
Reconductor Pruntytown - Shinns Run 138kV line including line drops at Shinns Run
Description
Reconductor (Possible Rebuild) ~8.48 miles of Pruntytown - Shinns Run 138kV line including (2) line drops at Shinns Run
Total Cost ($USD)
$36,786,038
Allocated Cost ($USD)
$36,786,038
Time Estimate
26 Months

Contributor

FacilityContingency
01PRNTY-01SHINNS 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-582
82.7 MW100.0%$36,786,038

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC2-APS-016.a
Title
Replace 500/138 kV TR1 at Flint Run
Description
Replace 500/138 kV TR1 at Flint Run. An assessment was made on reconfiguration/expansion options at Flint Run substation to accomodate the AG2-582 interconnection and any changes to address stuck breaker contingencies. Due to the substation location/space constraints, the Flint Run 500/138kV transformer replacements are the only option while still being able to accomodate the AG2-582 interconnection into the 500kV yard.
Total Cost ($USD)
$28,558,871
Allocated Cost ($USD)
$28,558,871
Time Estimate
66 Months

Contributor

FacilityContingency
01FLINTRN-01FLINTRUN 138.0/500.0 kV Ckt 1 transformer(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-582
344.0 MW100.0%$28,558,871

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC2-APS-015.a
Title
Replace 500/138 kV TR2 at Flint Run
Description
Replace 500/138 kV TR2 at Flint Run. An assessment was made on reconfiguration/expansion options at Flint Run substation to accomodate the AG2-582 interconnection and any changes to address stuck breaker contingencies. Due to the substation location/space constraints, the Flint Run 500/138kV transformer replacements are the only option while still being able to accomodate the AG2-582 interconnection into the 500kV yard.
Total Cost ($USD)
$28,558,871
Allocated Cost ($USD)
$28,558,871
Time Estimate
66 Months

Contributor

FacilityContingency
01FLINTRN-01FLINTRUN 138.0/500.0 kV Ckt 2 transformer(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-582
344.0 MW100.0%$28,558,871

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC2-APS-011.a
Title
Reconductor Glen Falls - Mcalpin transmission line.
Description
Reconductor (Possible Rebuild) 4.6 miles of Glen Falls - Mcalpin transmission line.
Total Cost ($USD)
$16,988,135
Allocated Cost ($USD)
$16,988,135
Time Estimate
19 Months

Contributor

FacilityContingency
01GLENFL-01MCALPN 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-582
76.6 MW100.0%$16,988,135

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC2-APS-012.b
Title
Reconductor Bridgeport Hill - Glen Falls transmission line
Description
Reconductor (Possible Rebuild) 4.3 miles of Bridgeport Hill - Glen Falls transmission line
Total Cost ($USD)
$16,031,404
Allocated Cost ($USD)
$16,031,404
Time Estimate
19 Months

Contributor

FacilityContingency
01BRIDGP-01GLENFL 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-582
82.7 MW100.0%$16,031,404

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC2-APS-029
Title
Reconductor (Possible Rebuild) ~3.4 mile of Barnetts Run - Bridgeport Hill 138 kV transmission line. Including Wave trap drop and transmission line drop at Barnetts Run
Description
Reconductor (Possible Rebuild) ~3.4 mile of Barnetts Run - Bridgeport Hill 138 kV transmission line. Including Wave trap drop and transmission line drop at Barnetts Run
Total Cost ($USD)
$13,223,334
Allocated Cost ($USD)
$13,223,334
Time Estimate
20 Months

Contributor

FacilityContingency
01BRIDGP-01BARNET 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-582
82.7 MW100.0%$13,223,334

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC2-APS-002.b
Title
Reconductor (Possible Rebuild) ~3.8 miles of AG2-505 - Beryl 138kV transmission line
Description
Reconductor (Possible Rebuild) ~3.8 miles of AG2-505 - Beryl 138kV transmission line.
Total Cost ($USD)
$16,807,147
Allocated Cost ($USD)
$9,561,669
Time Estimate
19 Months

Contributor

FacilityContingency
01BERYL-AG2-505 TP 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-505
8.7 MW43.1%$7,245,478
AG2-582
11.5 MW56.9%$9,561,669

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC2-PH1-025
Title
Reconductor (Possible Rebuild) ~2 miles of Barnetts Run-Shinns Run 138kV line including T-line drops at Barnetts Run & Shinns Run
Description
Reconductor (Possible Rebuild) ~2 miles of Barnetts Run - Shinns Run 138 kV line including (2) T-line drops at Barnetts Run and (2) T-line drops at Shinns Run
Total Cost ($USD)
$8,443,469
Allocated Cost ($USD)
$8,443,469
Time Estimate
18 Months

Contributor

FacilityContingency
01BARNET-01SHINNS 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-582
82.7 MW100.0%$8,443,469

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC2-APS-028
Title
Reconductor Mt Zion - AG2-505 138kV transmission line
Description
Reconductor (Possible Rebuild) ~2.8 miles of Mt Zion - AG2-505 138kV transmission line
Total Cost ($USD)
$12,297,524
Allocated Cost ($USD)
$8,051,517
Time Estimate
18 Months

Contributor

FacilityContingency
01MTZION-AG2-505 TP 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-582
11.5 MW65.5%$8,051,517
AG2-615
6.1 MW34.5%$4,246,007

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC2-APS-016.b
Title
Replace 6 138 kV Disc Switches and 5 Breaker Leads at Flint Run
Description
Replace 6 138 kV Disc Switches and 5 Breaker Leads at Flint Run
Total Cost ($USD)
$1,826,164
Allocated Cost ($USD)
$1,826,164
Time Estimate
24 Months

Contributor

FacilityContingency
01FLINTRN-01FLINTRUN 138.0/500.0 kV Ckt 1 transformer(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-582
344.0 MW100.0%$1,826,164

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC2-APS-015.b
Title
Replace 6 138 kV Disc Switches and 5 Breaker Leads at Flint Run
Description
Replace 6 138 kV Disc Switches and 5 Breaker Leads at Flint Run
Total Cost ($USD)
$1,826,164
Allocated Cost ($USD)
$1,826,164
Time Estimate
24 Months

Contributor

FacilityContingency
01FLINTRN-01FLINTRUN 138.0/500.0 kV Ckt 2 transformer(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-582
344.0 MW100.0%$1,826,164

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC2-APS-009.b
Title
Upgrade Meters at Pruntytown
Description
Upgrade (5) Meters at Pruntytown
Total Cost ($USD)
$1,098,322
Allocated Cost ($USD)
$1,098,322
Time Estimate
13 Months

Contributor

FacilityContingency
01PRNTY-01SHINNS 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-582
82.7 MW100.0%$1,098,322

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC2-APS-023.b
Title
Reconductor (Possible Rebuild) ~1 mile of Beryl - Cross School 138 kV transmission line.
Description
Reconductor (Possible Rebuild) ~1 mile of Beryl - Cross School 138 kV transmission line.
Total Cost ($USD)
$4,427,958
Allocated Cost ($USD)
$1,016,011
Time Estimate
18 Months

Contributor

FacilityContingency
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-448
29.9 MW59.7%$2,642,052
AG2-505
8.7 MW17.4%$769,895
AG2-582
11.5 MW22.9%$1,016,011

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC2-APS-012.a
Title
Reconductor 556.5 ACSR 26/7-line exit at Bridgeport Hill
Description
Reconductor 556.5 ACSR 26/7-line exit at Bridgeport Hill
Total Cost ($USD)
$977,534
Allocated Cost ($USD)
$977,534
Time Estimate
14 Months

Contributor

FacilityContingency
01BRIDGP-01GLENFL 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-582
82.7 MW100.0%$977,534

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC2-APS-016.c
Title
Replace SCCIR 3" Pipe A-frame closest to Disc SW A-39
Description
Replace SCCIR 3" Pipe A-frame closest to Disc SW A-39
Total Cost ($USD)
$597,737
Allocated Cost ($USD)
$597,737
Time Estimate
18 Months

Contributor

FacilityContingency
01FLINTRN-01FLINTRUN 138.0/500.0 kV Ckt 1 transformer(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-582
344.0 MW100.0%$597,737

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC2-APS-011.b
Title
Replace Breaker Failure Relaying at Mcalpin
Description
Replace Breaker Failure Relaying at Mcalpin
Total Cost ($USD)
$509,895
Allocated Cost ($USD)
$509,895
Time Estimate
18 Months

Contributor

FacilityContingency
01GLENFL-01MCALPN 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-582
76.6 MW100.0%$509,895

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC2-APS-012.d
Title
Replace SEL-321 impedance relay and 1200 CT at Glen Falls
Description
Replace SEL-321 impedance relay and 1200 CT at Glen Falls
Total Cost ($USD)
$396,495
Allocated Cost ($USD)
$396,495
Time Estimate
17 Months

Contributor

FacilityContingency
01BRIDGP-01GLENFL 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-582
82.7 MW100.0%$396,495

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC2-APS-002.a
Title
Upgrade Disc Switch at Beryl
Description
Upgrade (1) 138 kV Disc Switch at Beryl
Total Cost ($USD)
$432,791
Allocated Cost ($USD)
$189,395
Time Estimate
21 Months

Contributor

FacilityContingency
01BERYL-AG2-505 TP 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-505
8.7 MW33.2%$143,517
AG2-582
11.5 MW43.8%$189,395
AG2-615
6.1 MW23.1%$99,879

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC2-APS-012.c
Title
Upgrade/Replace (3) 10 Amp Bitronics Meters at Glen Falls
Description
Upgrade/Replace (3) 10 Amp Bitronics Meters at Glen Falls
Total Cost ($USD)
$157,861
Allocated Cost ($USD)
$157,861
Time Estimate
12 Months

Contributor

FacilityContingency
01BRIDGP-01GLENFL 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-582
82.7 MW100.0%$157,861

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC2-PH1-023.a
Title
Upgrade 138 kV Disc Sw 1306_Q at Beryl
Description
Upgrade 138 kV Disc Sw 1306_Q at Beryl
Total Cost ($USD)
$432,790
Allocated Cost ($USD)
$88,586
Time Estimate
19 Months

Contributor

FacilityContingency
01BERYL-01CROSSCHOOL 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-448
29.9 MW53.2%$230,361
AG2-505
8.7 MW15.5%$67,127
AG2-582
11.5 MW20.5%$88,586
AG2-615
6.1 MW10.8%$46,716

System Reinforcement: b4000.11
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.11
Title
Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)
Description
Expand Black Oak Substation to accommodate the connection of the 502 Jct-Woodside 500 kV line and loop the 502 Jct-Woodside 500 kV line into the Black Oak substation by constructing ~0.85 miles of new 500 kV line into and out of Black Oak 500 kV substation
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-582 may not presently have cost responsibility for this upgrade, AG2-582 may need this upgrade in-service to be deliverable to the PJM system. If AG2-582 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)

System Reinforcement: s3191.1
Type
Load Flow
TO
APS
RTEP ID / TO ID
s3191.1 / APS-2023-056
Title
Harrison – Pruntytown 500 kV Misoperation Relays (Projected ISD by end of 2025)
Description
- Replace wave trap, line metering and relaying at Harrison Substation- - Replace wave trap, line metering and relaying at Pruntytown Substation
Cost Information
Time Estimate
Dec 31 2024

Not Contingent

Note: AG2-582 contributes to the loading of an overloaded facility that is being mitigated by a planned supplemental project. AG2-582 is not contingent on this supplemental project as it is already in-service.

FacilityContingency
01HARRSN-01PRNTY 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.3
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.3
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-582 may not presently have cost responsibility for this upgrade, AG2-582 may need this upgrade in-service to be deliverable to the PJM system. If AG2-582 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.9
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.9
Title
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)
Description
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard. Loop in the Doubs-Goose Creek 500 kV line, the Doubs-Aspen 500 kV line, and the Woodside-Goose Creek 500 kV line. Install two 765/500 kV transformer at Rocky Point substation. 765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-582 may not presently have cost responsibility for this upgrade, AG2-582 may need this upgrade in-service to be deliverable to the PJM system. If AG2-582 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.5
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.5
Title
Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substation
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-582 may not presently have cost responsibility for this upgrade, AG2-582 may need this upgrade in-service to be deliverable to the PJM system. If AG2-582 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.2
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.2
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-582 may not presently have cost responsibility for this upgrade, AG2-582 may need this upgrade in-service to be deliverable to the PJM system. If AG2-582 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.6
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.6
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-582 may not presently have cost responsibility for this upgrade, AG2-582 may need this upgrade in-service to be deliverable to the PJM system. If AG2-582 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.10
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.10
Title
Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yard
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-582 may not presently have cost responsibility for this upgrade, AG2-582 may need this upgrade in-service to be deliverable to the PJM system. If AG2-582 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.7
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.7
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-582 may not presently have cost responsibility for this upgrade, AG2-582 may need this upgrade in-service to be deliverable to the PJM system. If AG2-582 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.4
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.4
Title
Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-582 may not presently have cost responsibility for this upgrade, AG2-582 may need this upgrade in-service to be deliverable to the PJM system. If AG2-582 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.8
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.8
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-582 may not presently have cost responsibility for this upgrade, AG2-582 may need this upgrade in-service to be deliverable to the PJM system. If AG2-582 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.1
Title
Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-582 may not presently have cost responsibility for this upgrade, AG2-582 may need this upgrade in-service to be deliverable to the PJM system. If AG2-582 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)

System Reinforcement: n8471
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
n8471
Title
East Sayre-North Waverly 115kV line upgrade - FirstEnergy (NYISO CY17 driven upgrade)
Description
East Sayre Substation: Replace one (1) 115 kV circuit breaker on North Waverly (NYSEG) terminal at East Sayre. Revise wiring for the North Waverly 115kV PR and BU line protection relays to utilize the redundant CT’s and trip coils on the new breaker. East Sayre – North Waverly 115kV line: Replace 3 pole wood Structure 141 due to NYSEG reconductor of East Sayre-North Waverly 115kV line. Enable load encroachment such that all protection elements will achieve the required loadability of 221/263/263/301 MVA (SN/SE/WN/WE) Note: NYISO customers Q387, Q421, Q505 require an upgrade on the East Sayre-North Waverly 115 kV line as part of the CY17 study. NYSEG will complete work at North Waverly substation and the line reconductor/rebuild. FirstEnergy will complete work at East Sayre substation. Per NYISO, the rating that must be achieved for CY17 is 176/176/176 MVA Summer Normal/LTE/STE. NYSEG confirmed the new line ratings for the NYISO side (218/251/282 MVA Summer Normal/LTE/STE; 265/291/318 MVA Winter Normal/LTE/STE), but the East Sayre terminal is still limiting. Once the scope of work and ratings at East Sayre are finalized, the expected line ratings will be updated. NYSEG uses LTE for Rate B, not STE like FirstEnergy.
Total Cost ($USD)
$1,417,388
Allocated Cost ($USD)
$0
Time Estimate
Nov 01 2027

Contingent

Note: Based on PJM cost allocation criteria, AG2-582 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-582 could receive cost allocation. Although AG2-582 may not presently have cost responsibility for this upgrade, AG2-582 may need this upgrade in-service to be deliverable to the PJM system. If AG2-582 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
N.WAV115-26E.SAYRE 115.0 kV Ckt 1 line(Any)

Attachments

AG2-582 One Line Diagram

AG2-582 One Line Diagram.pdf
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.