AH1-221 Phase I Study Report

v1.00 released 2025-10-29 21:33

Heritage 500 kV

45.0 MW Capacity / 0.0 MW Energy

Introduction

This Phase I System Impact Study Report (PH1) has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, sections 307 and 308 for New Service Requests (projects) in Transition Cycle 2. The Project Developer/Eligible Customer (developer) is Virginia Electric and Power Company (d/b/a) Dominion Energy Virginia, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Virginia Electric and Power Company (d/b/a Dominion Energy Virginia).

Preface

The Phase I System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle executive summary format and (ii) an individual project-level basis. The Phase I System Impact Study Results (for both the executive summary and individual reports) will be publicly available on PJM’s website. Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.3, PJM takes the following actions during the Phase I System Impact Study:
  1. PJM studies each New Service Request on a summer peak, winter peak and light load RTEP base case study. The case year is dependent on the new services cycle under study. PJM will identify the base case year to be used in the study of a specific cycle on its website.
  2. PJM will only perform load flow analysis during the Phase I System Impact Study.
  3. In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with Affected System impacts and provides each Affected System Operator with a list of New Service Request in the Cycle with potential impacts to their respective system.
  4. PJM will create both the short circuit and stability base cases to be used in the Phase II System Impact Study.
  5. The Phase I System Impact Study results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.
The Transmission Owner takes the following actions during the Phase I System Impact Study:
  1. Identify required Interconnection Facilities to accommodate the New Service Request.
  2. Identify required Network Upgrades to mitigate system violations from the Phase I System Impact Study.
  3. Provide planning-level preliminary estimates of Interconnection Facilities and Network Upgrades including scope, cost and elapsed time to complete the work.

Decision Point I Requirements

At the close of Phase I System Impact Study, PJM will initiate Decision Point I (DP1). During DP1, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.A.1. Additional information on these elements is available in PJM Manual 14H sections 4.4, 6, and 7.

Allowable project modifications at Decision Point I are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

General

The Project Developer has proposed an uprate to a planned/existing Storage facility located in the Virginia Electric and Power Company (d/b/a Dominion Energy Virginia) zone — Brunswick County, Virginia. This project is an increase to the developer’s AG1-153 project(s), which will share the same Point of Interconnection. The AH1-221 project is a 45.0 MW Capacity only uprate to the previous project(s). The total installed facilities will have a capability of 75.0 MW with 75.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AH1-221
Project Name:
Heritage 500 kV
Project Developer Name:
Virginia Electric and Power Company (d/b/a) Dominion Energy Virginia
State:
Virginia
County:
Brunswick
Transmission Owner:
Virginia Electric and Power Company (d/b/a Dominion Energy Virginia)
MFO:
75.0
MWE:
0.0
MWC:
45.0
Battery Storage Specification:
300.0 MWh, 4.0-hr class
Grid Charging:
No
Fuel Type:
Storage
Basecase Study Year:
2028

Capacity Interconnection Rights (CIR) Transfer Details

This project intends to claim and transfer CIRs from the following Deactivation capacity generation resources. PJM performed a reliability analysis of the impacts to the system capability for the proposed transfer of CIRs from the Deactivation generation resources.

Unit NameStatusCIR ClaimedPOI Transfer
Possum Point 5Deactivated Generator45.0Yes

Physical Interconnection Facility Study

Physical Interconnection Facilities Study is not performed as part of the Phase I System Impact Study. Physical Interconnection Facilities Study will commence in the Phase II System Impact Study.

Point of Interconnection

AH1-221 will interconnect on the Virginia Electric and Power Company (d/b/a Dominion Energy Virginia) transmission system as an uprate to AG1-153 at the Heritage 500 kV Substation.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In the Phase I SIS, the costs shown are subject to change as a result of a facility study performed by the TO during the Phase II or Phase III System Impact Study.

Based on the Phase I SIS results, the AH1-221 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit are also shown below.

Cost Summary
DescriptionCost Allocated to AH1-221Cost Subject to Readiness*
Transmission Owner Interconnection Facilities (TOIF)$0$0
Other Scope$0$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0
Network Upgrades$0$0
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$0$0
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$0$0
Total$0$0

* Contributes to calculation for Readiness Deposit #2 (RD2). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 309 (Decision Point I) A.1.a.i and PJM Manual 14H, section 6.2, Readiness Deposit #2 (RD2) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point I (DP1), the Project Developer or Eligible Customer is required to submit Readiness Deposit #2, which is calculated as 10% of cost allocation for required Phase I Network Upgrades minus Readiness Deposit #1.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Readiness Deposit #2 Due for Project AH1-221

Readiness Deposit #2 has been calculated for the project based on the Phase I System Impact Study results and is shown in the table below. This Readiness Deposit #2 must be provided at Decision Point I through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit
Project ID10% of cost allocation for Phase I Network UpgradesReadiness Deposit #1 Received (RD1)Readiness Deposit #2 (RD2) for AH1-221 Project due at DP1
ABA - B
AH1-221$0$180,000$0

Note: Failure to provide an acceptable form of Readiness Deposit #2 by the end of Decision Point I will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Interconnection Facilities
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)AH1-221 is sharing a POI and the TOIF with AG1-153, so there are no associated interconnection costs for this project. Should the previous project(s) AG1-153 withdraw from the Interconnection Queue, AH1-221 will assume responsibility of the TOIF, SANU, and Network Upgrade costs identified in the AG1-153 study report(s) for interconnection to the Dominion System.$0 $0

Based on the scope of work for the Interconnection Facilities, it is expected to take a range of 50 to 54 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

The schedule for any required Network Impact Reinforcements will be more clearly identified in the Phase II and Phase III System Impact Studies.

Transmission Owner Analysis

PJM performed a power flow analysis of the transmission system using a 2028 load flow model and the results were verified by Dominion.

 

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. Dominion interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AH1-221 was evaluated as a 0.0 MW (45.0 MW Capacity) injection in the Dominion area.

AH1-221 was evaluated as part of a plant. The plant consists of AH1-221. The total Energy output of the plant was evaluated at its maximum seasonal capability of 75.0 MW (45.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC203.13 %678.68B1378.63.45
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Base Case
SingleAC113.92 %678.68A773.162.38
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC202.03 %678.68B1371.173.45
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Base Case
SingleAC112.86 %678.68A765.972.38
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S
SingleAC177.07 %571.52B1012.013.36
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Base Case
SingleAC112.79 %571.52A644.612.31
GD2DVP
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
DVP_P4-2: 562T563_SRT-S
BreakerAC154.83 %1204.0C1864.165.99
GD2DVP
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S
SingleAC145.18 %984.18B1428.844.66
GD2DVP
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
DVP_P1-2: LN 2002_SRT-A
SingleAC121.21 %984.18B1192.963.62
GD2DVP
6CARSON-6POE 230.0 kV Ckt 1 line
DVP_P1-2: LN 249_SRT-A
SingleAC124.58 %678.68B845.482.87
GD2DVP
6CARSON-6POE 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S
SingleAC116.29 %678.68B789.263.0
GD2DVP
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
DVP_P4-2: 562T563_SRT-S
BreakerAC152.97 %1204.0C1841.85.99
GD2DVP
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S
SingleAC142.99 %984.18B1407.244.66
GD2DVP
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
DVP_P1-2: LN 2002_SRT-A
SingleAC119.0 %984.18B1171.163.62
GD2DVP
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S
SingleAC167.04 %559.3B934.253.37
GD2DVP
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Base Case
SingleAC101.32 %559.3A566.672.32
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC196.14 %678.68B1331.143.22
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC198.54 %661.76B1313.883.22
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC195.13 %661.76B1291.313.22
GD2DVP
6POE-6TYLER1 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S
SingleAC130.12 %441.8B574.862.4
GD2DVP
6TYLER-6CHESTF B 230.0 kV Ckt 1 line
DVP_P4-2: 562T563_SRT-S
BreakerAC100.46 %1204.0C1209.554.54
GD2DVP
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer
DVP_P4-2: 562T563_SRT-S
BreakerAC105.06 %1039.5C1092.075.39
GD2DVP
8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer
DVP_P4-2: 56372_SRT-S
BreakerAC150.06 %1056.8C1585.796.95
GD2DVP
8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer
DVP_P4-2: 562T563_SRT-S
BreakerAC111.2 %1056.8C1175.185.78
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC139.66 %3220.44B4497.8313.79
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P4-2: 557T574_SRT-S
BreakerAC139.23 %3940.0C5485.7114.78
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P4-2: 56272_SRT-S
BreakerAC131.96 %3118.0C4114.6513.69
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P1-2: LN 567_SRT-A
SingleAC130.02 %3220.44B4187.0814.07
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P4-2: H2T574_SRT-S
BreakerAC128.65 %3940.0C5068.7513.84
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P4-2: H1T574_SRT-S
BreakerAC128.38 %3940.0C5058.2713.77
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P4-2: 56722_SRT-A
BreakerAC126.96 %3940.0C5002.2414.55
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P2-2: BREMO B1_SRT-A
BusAC108.3 %3940.0C4267.1512.85
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P7-1: LN 2003-205_SRT-S
TowerAC107.33 %3940.0C4228.6713.21
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P7-1: LN 208-259_SRT-S
TowerAC106.32 %3940.0C4188.8212.65
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Base Case
SingleAC105.09 %3220.44A3384.2812.31
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
BusAC104.67 %3940.0C4124.0512.79
GD2DVP
8HERITAGE-8RAWLINGS 500.0 kV Ckt 1 line
DVP_P1-2: LN 585_SRT-A-1
SingleAC105.18 %4124.72B4338.4832.62
GD2DVP
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
DVP_P1-2: LN 576_SRT-S
SingleAC127.08 %1057.5B1343.95.44
GD2DVP
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
DVP_P4-2: WT576_SRT-S
BreakerAC122.5 %1265.1C1549.85.44
GD2DVP
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
DVP_P4-2: 57602_SRT-S
BreakerAC122.5 %1265.1C1549.85.44
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC175.45 %3220.44B5650.1413.28
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P4-2: H2T574_SRT-S
BreakerAC154.63 %3940.0C6092.4313.38
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P4-2: 557T574_SRT-S
BreakerAC154.23 %3940.0C6076.813.94
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P4-2: H1T574_SRT-S
BreakerAC152.97 %3940.0C6027.1313.29
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-S
SingleAC136.69 %3220.44B4402.0712.67
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P4-2: 574T575_SRT-S
BreakerAC132.12 %3940.0C5205.612.06
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P4-1: G202_SRT-S
BreakerAC131.07 %3118.0C4086.8810.85
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P2-2: NORTH ANNA B1_SRT-S
BusAC126.92 %3118.0C3957.4410.89
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P2-2: NORTH ANNA B2_SRT-S
BusAC126.92 %3118.0C3957.4410.89
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Base Case
SingleAC113.34 %3193.18A3619.1310.89
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P7-1: LN 2090-256_SRT-S
TowerAC104.73 %3940.0C4126.1811.16
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P7-1: LN 2054-2135_SRT-A
TowerAC104.47 %3940.0C4115.9510.94
GD2DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P4-2: 57302_SRT-S
BreakerAC161.07 %3118.0C5022.168.27
GD2DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 594_SRT-S
SingleAC150.27 %3220.44B4839.457.8
GD2DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 573_SRT-S
SingleAC147.45 %3220.44B4748.68.19
GD2DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P4-2: SPOTS H1T594_SRT-S
BreakerAC134.78 %3940.0C5310.498.15
GD2DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P4-2: H1T594_SRT-S
BreakerAC130.91 %3940.0C5157.737.82
GD2DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P4-2: 515T594_SRT-S
BreakerAC130.47 %3940.0C5140.467.8
GD2DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P4-2: H1T573_SRT-S
BreakerAC128.18 %3940.0C5050.258.21
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P4-2: 574T575_SRT-S
BreakerAC174.96 %3940.0C6893.410.89
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P4-2: 57502_SRT-S
BreakerAC169.18 %3118.0C5274.998.94
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P1-2: LN 575_SRT-S
SingleAC156.39 %3220.44B5036.568.89
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P1-2: LN 550_SRT-A
SingleAC139.38 %3220.44B4488.577.77
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P2-2: NORTH ANNA B2_SRT-S
BusAC128.28 %3118.0C3999.667.19
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P2-2: NORTH ANNA B1_SRT-S
BusAC128.28 %3118.0C3999.667.19
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Base Case
SingleAC118.49 %3193.18A3783.567.19
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P7-1: LN 11-2199_SRT-A-1
TowerAC118.03 %3940.0C4650.587.43
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P7-1: LN 11-2199_SRT-A-2
TowerAC117.81 %3940.0C4641.567.43
GD2DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 585_SRT-A-1
SingleAC139.73 %4070.2B5687.3325.83
GD2DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 585_SRT-A-2
SingleAC133.78 %4070.2B5445.2825.83
GD2DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P4-2: 58572_SRT-A
BreakerAC124.04 %4996.0C6196.9525.83
GD2DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P4-5: W72_SRT-A
BreakerAC123.43 %4996.0C6166.5625.64
GD2DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P4-2: XT585_SRT-S
BreakerAC114.16 %4996.0C5703.6625.83
GD2DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P4-2: 54472_SRT-S
BreakerAC111.74 %2858.0C3193.4912.55
GD2DVP
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
DVP_P1-2: LN 511_SRT-S
SingleAC123.06 %4070.2B5008.6525.61
GD2DVP
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
DVP_P4-2: 51192_SRT-S
BreakerAC109.25 %4996.0C5458.0625.61
GD2DVP
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
DVP_P4-2: 51172_SRT-S
BreakerAC108.79 %4996.0C5435.0725.43
GD2DVP
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
DVP_P4-2: 511T544_SRT-S
BreakerAC107.19 %4996.0C5355.1925.22
GD2DVP
8SEPTA-8SURRY 500.0 kV Ckt 1 line
DVP_P4-2: 56372_SRT-S
BreakerAC103.87 %2931.0C3044.3710.28
GD2DVP
8SEPTA-8SURRY 500.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A
BreakerAC101.05 %2931.0C2961.869.86
GD2DVP
8SEPTA-8SURRY 500.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S
BreakerAC101.05 %2931.0C2961.869.86
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P4-2: 574T575_SRT-S
BreakerAC179.37 %3940.0C7067.1410.54
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P1-2: LN 550_SRT-A
SingleAC146.89 %3220.44B4730.387.64
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P2-2: MORRISVILLE B1_SRT-S
BusAC140.84 %3118.0C4391.47.04
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Base Case
SingleAC129.41 %3220.44A4167.617.04
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
AP_P2-2_WP-500-DRT14_SRT-SL
BusAC113.81 %3940.0C4484.127.03
GD2DVP
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 511_SRT-S
SingleAC136.1 %4070.2B5539.4125.61
GD2DVP
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
DVP_P4-2: 51192_SRT-S
BreakerAC120.36 %4996.0C6013.1125.61
GD2DVP
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
DVP_P4-2: 51172_SRT-S
BreakerAC119.82 %4996.0C5986.2925.43
GD2DVP
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
DVP_P4-2: 511T544_SRT-S
BreakerAC118.15 %4996.0C5902.925.22
GD2DVP
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 591_SRT-S
SingleAC107.48 %4070.2B4374.4531.28
GD2DVP
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S
SingleAC176.17 %559.3B985.353.37
GD2DVP
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Base Case
SingleAC110.37 %559.3A617.322.32
GD2DVP
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
DVP_P1-2: LN 511_SRT-S
SingleAC129.2 %4070.2B5258.7225.61
GD2DVP
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
DVP_P4-2: 51192_SRT-S
BreakerAC114.25 %4996.0C5708.1225.61
GD2DVP
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
DVP_P4-2: 51172_SRT-S
BreakerAC113.76 %4996.0C5683.4425.43
GD2DVP
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
DVP_P4-2: 511T544_SRT-S
BreakerAC112.13 %4996.0C5601.825.22
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S
SingleAC181.65 %559.3B1015.963.37
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Base Case
SingleAC115.81 %559.3A647.72.32
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S
SingleAC183.2 %571.52B1047.03.36
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Base Case
SingleAC118.94 %571.52A679.772.31

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:203.13 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:1378.6
MW Contribution:3.45
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
22.18
316303AF2-085
50/50
2.224
3151541CLOVER2
50/50
2.487
3151611KERR 4
50/50
0.234
3151621KERR 5
50/50
0.234
3151631KERR 6
50/50
0.234
3151641KERR 7
50/50
0.234
963041AG1-153 GEN
50/50
2.299
315244AE2-183_ST
50/50
2.451
3151281ROARAP4
50/50
0.1
3151281ROARAP4
50/50
0.094
971285AH1-108 GEN
50/50
0.651
315779AE2-040
50/50
1.092
971845AH1-439 GEN
Solar/Wind Harmer
17.513
970285AG2-188 GEN
Solar/Wind Harmer
29.552
315657AE1-056 GEN
Solar/Wind Harmer
8.144
946301AF1-294 GEN
Solar/Wind Harmer
4.404
961791AG1-021 GEN
Solar/Wind Harmer
2.143
970683AG2-441 GEN
Solar/Wind Harmer
13.644
970681AG2-440 GEN
Solar/Wind Harmer
10.915
3144303KENBRDG
Solar/Wind Harmer
0.148
971443AH1-215 GEN
Solar/Wind Harmer
3.079
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316233AE1-074 FULL
Solar/Wind Harmer
0.084
971281AH1-106 GEN
Solar/Wind Harmer
1.459
971283AH1-107 GEN
Solar/Wind Harmer
1.459
316118AC1-105 GEN
Solar/Wind Harmer
0.27
270494AE1-108_GEN
Solar/Wind Harmer
1.236
970831AG2-522 GEN
Solar/Wind Harmer
4.291
3147173SINAI
Solar/Wind Harmer
0.095
3147243WELCO
Solar/Wind Harmer
0.059
971967AH1-528 GEN
Solar/Wind Harmer
14.709
316087AB2-174 GEN
Solar/Wind Harmer
0.002
970673AG2-436 GEN
Solar/Wind Harmer
18.242
970673AG2-436 GEN
Solar/Wind Harmer
12.162
941031AE2-094 GEN
Solar/Wind Harmer
15.639
944011AF1-069 GEN
Solar/Wind Harmer
5.11
3137643SOCKMAN
Solar/Wind Harmer
0.336
970085AG2-068 GEN
Solar/Wind Harmer
4.411
970581AG2-369 GEN
Solar/Wind Harmer
3.794
315607AA1-063A GEN
Solar/Wind Harmer
0.164
3146043SEABORD
Solar/Wind Harmer
0.08
315814AE2-033 C
Solar/Wind Harmer
6.192
316315AB2-025 C
Solar/Wind Harmer
0.063
970865AG2-541 GEN
Solar/Wind Harmer
2.68
965291AG1-394 GEN
Solar/Wind Harmer
0.339
315652AC1-086 GEN
Solar/Wind Harmer
8.307
3145893MURPHYS
Solar/Wind Harmer
0.203
3145893MURPHYS
Solar/Wind Harmer
0.075
3145796HORNRTN
Solar/Wind Harmer
0.238
3145796HORNRTN
Solar/Wind Harmer
0.03
3143316POE
Solar/Wind Harmer
0.292
3146033SCOT NK
Solar/Wind Harmer
0.294
3145513AHOSKIE
Solar/Wind Harmer
0.153
3145513AHOSKIE
Solar/Wind Harmer
0.073
3145683EARLEYS
Solar/Wind Harmer
0.146
3145683EARLEYS
Solar/Wind Harmer
0.073
3145683EARLEYS
Solar/Wind Harmer
0.073
3146206CASHIE
Solar/Wind Harmer
0.07
970601AG2-382 GEN
Solar/Wind Harmer
2.62
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.048
316311AC2-079 GEN
Solar/Wind Harmer
2.01
316319Z2-044 C
Solar/Wind Harmer
0
315732AD1-074 GEN1
Solar/Wind Harmer
0.4
315733AD1-074 GEN2
Solar/Wind Harmer
0.4
315735AD1-075 GEN1
Solar/Wind Harmer
0.2
3130546PLYMOUTH
Solar/Wind Harmer
0.07
315835AF2-110_GEN
Solar/Wind Harmer
0.478
315816AE2-034 GEN
Solar/Wind Harmer
0.298
3130156CHOWAN
Solar/Wind Harmer
0.069
3130156CHOWAN
Solar/Wind Harmer
0.069
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3146486SUNBURY
Solar/Wind Harmer
0.069
3146486SUNBURY
Solar/Wind Harmer
0.069
316321Z2-027
Solar/Wind Harmer
0.013
3145176PASQUOTANK
Solar/Wind Harmer
0.043
3146396TANGLEW
Solar/Wind Harmer
0.19
316305AF2-043 C
Solar/Wind Harmer
0.001
313526AB2-022
Solar/Wind Harmer
0.037
3146406KITTY HAWK
Solar/Wind Harmer
0.009
319010AE1-072 C
Solar/Wind Harmer
0.346
957871AF2-081 GEN
Solar/Wind Harmer
3.419
3151081ELIZAR1
Adder
6.268
3151091ELIZAR2
Adder
6.16
3152611GOSPORTB
Adder
0.871
3152621GOSPORTC
Adder
0.739
3152601GOSPORTA
Adder
0.682
3145573BETHELC
Solar/Wind Harmer
0.067
3145573BETHELC
Solar/Wind Harmer
0.067
316420AA1-050 GEN
Solar/Wind Harmer
0.002
957861AF2-080 GEN
Solar/Wind Harmer
2.903
316005AA1-067
Solar/Wind Harmer
0.072
3145746EVERETS
Solar/Wind Harmer
0.267
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
970181AG2-120 GEN
Solar/Wind Harmer
0.836
971445AH1-216 GEN
Solar/Wind Harmer
4.703
972265AH1-717 GEN
Adder
5.124
3151201GRAVEL4
Adder
4.803
3151191GRAVEL3
Adder
4.742
3151211GRAVEL5
Adder
4.742
316369SG1_INVT
Solar/Wind Harmer
0.002
316132AB2-190 GEN1
Solar/Wind Harmer
0.353
316123AC1-075 GEN
Solar/Wind Harmer
0.09
3144293JTRSVLE
50/50
0.754
3144293JTRSVLE
50/50
0.635
970535AG2-341 GEN
50/50
2.24
3152661PLYWOOD A
50/50
0.227
3151041BRUNSWICKG3
50/50
1.135
972187AH1-678 GEN
50/50
2.606
315242AE2-183_GT2
50/50
1.418
315241AE2-183_GT1
50/50
1.409
972185AH1-677 GEN
50/50
5.111
970533AG2-339 GEN
50/50
7.548
970531AG2-338 GEN
50/50
3.019
3146776BUCKING
Solar/Wind Harmer
1.571
3146776BUCKING
Solar/Wind Harmer
0.127
970301AG2-198 GEN
Solar/Wind Harmer
10.262
3147133PAMPLIN
Solar/Wind Harmer
0.236
3147133PAMPLIN
Solar/Wind Harmer
0.189
958211AF2-115 GEN
Solar/Wind Harmer
2.678
963191AG1-168 GEN
Solar/Wind Harmer
0.893
971741AH1-377 GEN
Solar/Wind Harmer
21.598
316034AC1-036 C
Solar/Wind Harmer
0.014
970323AG2-213 GEN
Solar/Wind Harmer
7.892
971775AH1-396 GEN
Solar/Wind Harmer
0.296
313527AB2-043 GEN
Solar/Wind Harmer
0.002
971489AH1-241 GEN
Solar/Wind Harmer
7.009
971223AH1-071 GEN
Solar/Wind Harmer
1.334
962561AG1-105 GEN
Solar/Wind Harmer
5.681
939181AE1-148 GEN
Solar/Wind Harmer
5.661
970099AG2-077 GEN
Solar/Wind Harmer
12.506
964791AG1-342 GEN
Solar/Wind Harmer
2.195
3146843MT LREL
Solar/Wind Harmer
0.114
3146843MT LREL
Solar/Wind Harmer
0.114
3143526WINTERP
Solar/Wind Harmer
0.547
970933AG2-581 GEN
Solar/Wind Harmer
7.995
316181AB2-040 GEN
Solar/Wind Harmer
0.124
3145593CAROLNA
Solar/Wind Harmer
0.083
3145593CAROLNA
Solar/Wind Harmer
0.083
966811AG1-552 GEN
Solar/Wind Harmer
0.899
3145593CAROLNA
Solar/Wind Harmer
0.103
3145783HORNRTN
Solar/Wind Harmer
1.451
3145783HORNRTN
Solar/Wind Harmer
1.161
3145783HORNRTN
Solar/Wind Harmer
0.363
3145783HORNRTN
Solar/Wind Harmer
0.145
316426AA2-053 GEN
Solar/Wind Harmer
0.274
3144356SAPONY
Solar/Wind Harmer
0.654
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
0.503
3145893MURPHYS
Solar/Wind Harmer
0.135
316274AC1-208 GEN
Solar/Wind Harmer
0.39
3145796HORNRTN
Solar/Wind Harmer
0.223
3146173TUNIS
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
315742AE1-103 GEN
Solar/Wind Harmer
0.001
970657AG2-426 GEN
Solar/Wind Harmer
2.47
970657AG2-426 GEN
Solar/Wind Harmer
0.518
316065AD1-022 GEN
Solar/Wind Harmer
3.223
3146376EDENTON
Solar/Wind Harmer
0.308
3146376EDENTON
Solar/Wind Harmer
0.308
3146626S HERTFORD
Solar/Wind Harmer
0.069
3146626S HERTFORD
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3146386ELIZ CT
Solar/Wind Harmer
0.069
316240AF1-291 C
Solar/Wind Harmer
0.001
3130086AYDLETT
Solar/Wind Harmer
0.275
3137176SLIGO L2192
Solar/Wind Harmer
0.273
3146456SLIGO L269
Solar/Wind Harmer
1.215
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.038
316339AD2-160 GEN
Solar/Wind Harmer
0.111
3145506HICKORY
Solar/Wind Harmer
0.274
3145506HICKORY
Solar/Wind Harmer
0.165
3145506HICKORY
Solar/Wind Harmer
0.041
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.066
316036AC1-147 C
Solar/Wind Harmer
0.013
3150991CHESPKB
Adder
0.716
3150991CHESPKB
Adder
0.699
944641AF1-129 GEN
Adder
32.505
316222AC1-221 GEN
Solar/Wind Harmer
0.283
316263AC1-034 GEN
Solar/Wind Harmer
2.586
3145933PARMELE
Solar/Wind Harmer
0.135
3145933PARMELE
Solar/Wind Harmer
0.068
961601AG1-000A GEN
Solar/Wind Harmer
1.202
3145493TOT1
Solar/Wind Harmer
0.156
3145453TOT5
Solar/Wind Harmer
0.094
3145603CNETO
Solar/Wind Harmer
0.063
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316033AB2-134 GEN
Solar/Wind Harmer
0.004
315697AD1-025 GEN
Solar/Wind Harmer
0.074
3142366NRTHEST
Adder
0.195
3142946ENON
Solar/Wind Harmer
0.006
3150691DARBY 3
Adder
4.195
3150701DARBY 4
Adder
4.185
3150681DARBY 2
Adder
4.18
3150671DARBY 1
Adder
4.175
942751AE2-291 GEN
Solar/Wind Harmer
3.155
966001AG1-469 GEN
Solar/Wind Helper
0.19
3151931BEARGRDN S1
50/50
5.869
3151911BEARGRDN G1
50/50
4.548
3144293JTRSVLE
50/50
0.754
970119AG2-088 GEN
50/50
16.679
3151531CLOVER1
50/50
2.499
3151601KERR 3
50/50
0.234
3151581KERR 1
50/50
0.083
3147043LAWRENC
50/50
1
3151051BRUNSWICKS1
50/50
2.357
3151021BRUNSWICKG1
50/50
1.135
971451AH1-221 GEN
50/50
3.449
315243AE2-183_GT3
50/50
1.418
3151261ROARAP2
50/50
0.103
3150851SPRUNCC
50/50
0.398
3151391GASTONA
50/50
0.204
3151411GASTONB
50/50
0.204
972003AH1-546 GEN
Solar/Wind Harmer
20.039
970937AG2-583 GEN
Solar/Wind Harmer
24.928
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.157
3146926FARMVIL
Solar/Wind Harmer
0.188
316336AC2-165 C
Solar/Wind Harmer
0.012
3143336POWHATN
Solar/Wind Harmer
4.81
963171AG1-166 GEN
Solar/Wind Harmer
1.19
971563AH1-280 GEN
Solar/Wind Harmer
2.381
970685AG2-442 GEN
Solar/Wind Harmer
15.281
962491AG1-098 GEN
Solar/Wind Harmer
8.349
315693AD1-088 GEN
Solar/Wind Harmer
6.776
316237AB2-079_GEN
Solar/Wind Harmer
0.001
971377AH1-170 GEN
Solar/Wind Harmer
1.402
3147623JAMES R
Solar/Wind Harmer
0.305
3143226MDLTHAN
Solar/Wind Harmer
0.125
957481AF2-042 GEN
Solar/Wind Harmer
31.266
970401AG2-262 GEN
Solar/Wind Harmer
0.671
315687AD1-152 GEN
Solar/Wind Harmer
0.003
3143526WINTERP
Solar/Wind Harmer
0.547
971065AG2-659 GEN
Solar/Wind Harmer
4.446
316129AC1-054 GEN
Solar/Wind Harmer
0.385
971795AH1-408 GEN
Solar/Wind Harmer
6.611
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.847
970919AG2-571 GEN
Solar/Wind Harmer
2.953
970087AG2-069 GEN
Solar/Wind Harmer
6.617
3145783HORNRTN
Solar/Wind Harmer
0.082
316190AA2-174 GEN
Solar/Wind Harmer
0
940641AE2-051 GEN
Solar/Wind Harmer
6.459
316023GEN1_S
Solar/Wind Harmer
0.176
939411AE1-173 GEN
Solar/Wind Harmer
33.156
3146263WOODLND
Solar/Wind Harmer
0.076
316011AB1-132 GEN
Solar/Wind Harmer
1.373
962571AG1-106 GEN
Solar/Wind Harmer
1.074
3145893MURPHYS
Solar/Wind Harmer
0.301
3145893MURPHYS
Solar/Wind Harmer
0.334
3145796HORNRTN
Solar/Wind Harmer
0.245
3145796HORNRTN
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
316212AC1-099_GEN
Solar/Wind Harmer
0.382
3145823KELFORD
Solar/Wind Harmer
0.073
3145683EARLEYS
Solar/Wind Harmer
0.073
315722AD1-056 GEN
Solar/Wind Harmer
0.447
970659AG2-427 GEN
Solar/Wind Harmer
3.416
316381AD1-082 GEN
Solar/Wind Harmer
0.074
970661AG2-428 GEN
Solar/Wind Harmer
7.004
3146206CASHIE
Solar/Wind Harmer
0.07
971547AH1-271 GEN
Solar/Wind Harmer
1.497
3142543TWELFTH
Solar/Wind Harmer
0.007
3146233WITAKRS
Solar/Wind Harmer
0.278
316093AE2-104_GEN
Solar/Wind Harmer
1.171
3145663CRESWEL
Solar/Wind Harmer
0.194
971163AH1-040 GEN
Solar/Wind Harmer
5.558
3130156CHOWAN
Solar/Wind Harmer
0.069
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.223
3146516WINFALL
Solar/Wind Harmer
0.069
315671AE2-027_GEN
Solar/Wind Harmer
4.41
316246AF1-032 C
Solar/Wind Harmer
0.031
3146456SLIGO L269
Solar/Wind Harmer
0.069
316388AE2-253 GEN
Solar/Wind Harmer
0.215
944591AF1-124 GEN
Solar/Wind Harmer
15.512
3145963POPLR C
Solar/Wind Harmer
0.069
316174AB2-169 GEN
Solar/Wind Harmer
0.002
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
0.853
3145543BTLEBRO
Solar/Wind Harmer
0.068
3145543BTLEBRO
Solar/Wind Harmer
0.054
316359AB2-059 GEN
Solar/Wind Harmer
0.244
316049AB1-081 GEN
Solar/Wind Harmer
0.389
3142053HEARTS
Solar/Wind Harmer
0.12
316072AD1-144
Solar/Wind Harmer
0.025
3146293MARTNCO
Solar/Wind Harmer
0.063
316294AC1-161 GEN
Solar/Wind Harmer
1.171
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.067
3145493TOT1
Solar/Wind Harmer
0.3
316494AC1-189 GEN
Solar/Wind Harmer
0.227
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
3145336SMITFLD
Solar/Wind Harmer
0.267
3143096IRON208
Adder
0.277
3151171GRAVELC
Adder
0.702
961611AG1-000B GEN
Solar/Wind Harmer
3.457
971647AH1-324 GEN
Solar/Wind Harmer
2.81
971069AG2-661 GEN
Solar/Wind Harmer
1.169
316458AB2-190 GEN2
Solar/Wind Harmer
0.353
970129AG2-093 GEN
Solar/Wind Harmer
1.869
944631AF1-128 GEN
Adder
29.45
3138126ROCKLANDING
Solar/Wind Harmer
0.028
3151921BEARGRDN G2
50/50
4.548
3144293JTRSVLE
50/50
0.754
970413AG2-270 GEN
50/50
10.906
3151591KERR 2
50/50
0.234
3151031BRUNSWICKG2
50/50
1.135
3151261ROARAP2
50/50
0.101
3150861SPRUNCD
50/50
0.398
3151391GASTONA
50/50
0.204
3151411GASTONB
50/50
0.204
3146776BUCKING
Solar/Wind Harmer
0.141
3146926FARMVIL
Solar/Wind Harmer
0.188
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
316313AB2-026
Solar/Wind Harmer
0.171
316258AE1-075 C
Solar/Wind Harmer
0.204
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
4.088
970909AG2-566 GEN
Solar/Wind Harmer
2.566
3147133PAMPLIN
Solar/Wind Harmer
0.741
971193AH1-056 GEN
Solar/Wind Harmer
14.378
963181AG1-167 GEN
Solar/Wind Harmer
0.893
959311AF2-222 GEN
Solar/Wind Harmer
16.945
970257AG2-171 GEN
Solar/Wind Harmer
5.919
315785AD2-033 C
Solar/Wind Harmer
1.44
964241AG1-285 GEN
Solar/Wind Harmer
10.432
316131AB2-060 GEN
Solar/Wind Harmer
0.453
970221AG2-151 GEN
Solar/Wind Harmer
7.009
316478AD1-087 GEN
Solar/Wind Harmer
0.407
316486AD2-202 GEN
Solar/Wind Harmer
0.12
3147043LAWRENC
Solar/Wind Harmer
0.063
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
4.061
313506AB2-031 GEN
Solar/Wind Harmer
0.265
971683AH1-343 GEN
Solar/Wind Harmer
3.059
970917AG2-570 GEN
Solar/Wind Harmer
7.384
316365GEN2_N
Solar/Wind Harmer
0.176
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3146263WOODLND
Solar/Wind Harmer
0.076
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3145893MURPHYS
Solar/Wind Harmer
0.126
3145893MURPHYS
Solar/Wind Harmer
0.075
957521AF2-046 GEN
Solar/Wind Harmer
5.572
961681AG1-008 GEN
Solar/Wind Harmer
5.572
3145796HORNRTN
Solar/Wind Harmer
0.297
3145796HORNRTN
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
316210AC1-098 GEN
Solar/Wind Harmer
0.686
316463AE2-346 GEN
Solar/Wind Harmer
0.063
316140AB2-099
Solar/Wind Harmer
0.026
962331AG1-082 GEN
Solar/Wind Harmer
0.783
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.073
316327AA2-057 GEN
Solar/Wind Harmer
0.108
3145273HOLLAND
Solar/Wind Harmer
0.054
315813AE1-149 C
Solar/Wind Harmer
3.784
3156021HOLLOMANSOL
Solar/Wind Harmer
0.322
315839AE2-212 C
Solar/Wind Harmer
0.001
315724AD1-057 GEN
Solar/Wind Harmer
0.265
970659AG2-427 GEN
Solar/Wind Harmer
0.747
316083AB2-161 GEN
Solar/Wind Harmer
0.001
970661AG2-428 GEN
Solar/Wind Harmer
1.49
3146206CASHIE
Solar/Wind Harmer
0.07
3146233WITAKRS
Solar/Wind Harmer
0.351
3146233WITAKRS
Solar/Wind Harmer
0.048
3138543CONSLDL
Solar/Wind Harmer
0.046
315737AD1-076 GEN
Solar/Wind Harmer
0.896
971157AH1-035 GEN
Solar/Wind Harmer
0.836
965281AG1-393 GEN
Solar/Wind Harmer
0.741
315614AA2-178 GEN
Solar/Wind Harmer
0.398
3146376EDENTON
Solar/Wind Harmer
0.069
3146626S HERTFORD
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
316435W1029_GEN3
Solar/Wind Harmer
0
316320Y1-086
Solar/Wind Harmer
0
3146456SLIGO L269
Solar/Wind Harmer
0.069
971153AH1-033 GEN
Solar/Wind Harmer
0.794
944581AF1-123 GEN
Solar/Wind Harmer
15.457
944601AF1-125 GEN
Solar/Wind Harmer
15.219
3145963POPLR C
Solar/Wind Harmer
0.069
3151101ELIZAR3
Adder
6.349
3144873MCLAUGH
Solar/Wind Harmer
0.002
3145543BTLEBRO
Solar/Wind Harmer
0.068
3145543BTLEBRO
Solar/Wind Harmer
0.068
971623AH1-311 GEN
Solar/Wind Harmer
0.136
3144536CHRHLND
Solar/Wind Harmer
0.01
3145933PARMELE
Solar/Wind Harmer
0.068
966801AG1-551 GEN
Solar/Wind Harmer
0.788
961601AG1-000A GEN
Solar/Wind Harmer
4.808
315773AC2-141 GEN
Solar/Wind Harmer
2.468
3146073TAR RVR
Solar/Wind Harmer
0.067
3146083TARBORO
Solar/Wind Harmer
0.067
316283AC2-100 C
Solar/Wind Harmer
0.132
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
3145336SMITFLD
Solar/Wind Harmer
0.027
3143096IRON208
Adder
0.277
3143096IRON208
Adder
0.272
3151221GRAVEL6
Adder
4.798
3151171GRAVELC
Adder
0.923
961611AG1-000B GEN
Solar/Wind Harmer
1.758
315778AD1-151 GEN
Solar/Wind Harmer
5.261
970129AG2-093 GEN
Solar/Wind Harmer
3.971
970133AG2-095 GEN
Solar/Wind Harmer
0.63
3144216WINCHST
Adder
0.231
3150921YORKTN3
Adder
1.525
3142946ENON
Solar/Wind Harmer
0.02
316382AG1-145 C
Solar/Wind Harmer
0
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3148013FISHERV
Solar/Wind Helper
0.175
316499AE2-029_GEN
Solar/Wind Helper
0.514
3132273ORANGE
Solar/Wind Helper
0.027
315616AA1-038_C
Solar/Wind Helper
0.545
3147666LOUISA
Solar/Wind Helper
0.273
970165AG2-112 GEN
Solar/Wind Harmer
0.531
970163AG2-111 GEN
Solar/Wind Harmer
0.506
971447AH1-217 GEN
Solar/Wind Harmer
1.848
971167AH1-042 GEN
Solar/Wind Harmer
5.088
3138283WHITEMARSH
Solar/Wind Harmer
0.013
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.105
3148013FISHERV
Solar/Wind Helper
0.101
3148463FAIRFLD
Solar/Wind Helper
0.12
971317AH1-138 GEN
Solar/Wind Harmer
0.439
316159AE1-175 C
Solar/Wind Harmer
0.05
3142433PROV 92
Solar/Wind Harmer
0.226
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3147983MERCK5
Solar/Wind Helper
0.056
316192AB2-158 GEN
Solar/Wind Helper
0.823
3147666LOUISA
Solar/Wind Helper
0.475
LAGNLTFEXP_LAGN->PJM
CLTF
1.781
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.535
TVALTFEXP_TVA->PJM
CLTF
0.87
CPLELTFEXP_CPLE->PJM
CLTF
4.352
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.276
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.726
MECLTFEXP_MEC->PJM
CLTF
0.354
SIGELTFEXP_SIGE->PJM
CLTF
0.008
NYPJM->LTFIMP_NY
CLTF
0.579
LGEELTFEXP_LGEE->PJM
CLTF
0.048
WECLTFEXP_WEC->PJM
CLTF
0.018

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.92 %
Rating:678.68 MVA
Rating Type:A
MVA to Mitigate:773.16
MW Contribution:2.38
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
21.569
316303AF2-085
50/50
1.694
3151541CLOVER2
50/50
2.007
3151611KERR 4
50/50
0.192
3151621KERR 5
50/50
0.192
3151631KERR 6
50/50
0.192
3151641KERR 7
50/50
0.192
3151281ROARAP4
50/50
0.075
3151281ROARAP4
50/50
0.07
971285AH1-108 GEN
50/50
0.486
963041AG1-153 GEN
50/50
1.59
315244AE2-183_ST
50/50
1.681
971845AH1-439 GEN
Solar/Wind Harmer
16.786
970285AG2-188 GEN
Solar/Wind Harmer
28.258
315657AE1-056 GEN
Solar/Wind Harmer
7.498
946301AF1-294 GEN
Solar/Wind Harmer
4.032
961791AG1-021 GEN
Solar/Wind Harmer
1.962
970683AG2-441 GEN
Solar/Wind Harmer
12.373
970681AG2-440 GEN
Solar/Wind Harmer
9.898
3144303KENBRDG
Solar/Wind Harmer
0.132
971443AH1-215 GEN
Solar/Wind Harmer
2.755
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
270494AE1-108_GEN
Solar/Wind Harmer
1.107
316118AC1-105 GEN
Solar/Wind Harmer
0.222
970831AG2-522 GEN
Solar/Wind Harmer
3.422
316233AE1-074 FULL
Solar/Wind Harmer
0.064
971281AH1-106 GEN
Solar/Wind Harmer
1.107
971283AH1-107 GEN
Solar/Wind Harmer
1.107
3147173SINAI
Solar/Wind Harmer
0.077
3147243WELCO
Solar/Wind Harmer
0.048
316087AB2-174 GEN
Solar/Wind Harmer
0.002
971967AH1-528 GEN
Solar/Wind Harmer
10.427
3137643SOCKMAN
Solar/Wind Harmer
0.253
970865AG2-541 GEN
Solar/Wind Harmer
2.127
315607AA1-063A GEN
Solar/Wind Harmer
0.122
3146043SEABORD
Solar/Wind Harmer
0.059
970673AG2-436 GEN
Solar/Wind Harmer
12.427
970673AG2-436 GEN
Solar/Wind Harmer
8.285
970085AG2-068 GEN
Solar/Wind Harmer
3.058
970581AG2-369 GEN
Solar/Wind Harmer
2.63
941031AE2-094 GEN
Solar/Wind Harmer
10.513
944011AF1-069 GEN
Solar/Wind Harmer
3.435
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.108
3148013FISHERV
Solar/Wind Helper
0.103
3148463FAIRFLD
Solar/Wind Helper
0.124
3144293JTRSVLE
50/50
0.69
3144293JTRSVLE
50/50
0.581
970535AG2-341 GEN
50/50
1.885
3152661PLYWOOD A
50/50
0.185
3151041BRUNSWICKG3
50/50
0.785
972187AH1-678 GEN
50/50
1.802
315242AE2-183_GT2
50/50
0.972
315241AE2-183_GT1
50/50
0.966
972185AH1-677 GEN
50/50
3.505
970533AG2-339 GEN
50/50
5.074
970531AG2-338 GEN
50/50
2.029
3146776BUCKING
Solar/Wind Harmer
1.508
3146776BUCKING
Solar/Wind Harmer
0.122
970301AG2-198 GEN
Solar/Wind Harmer
9.412
3147133PAMPLIN
Solar/Wind Harmer
0.217
3147133PAMPLIN
Solar/Wind Harmer
0.174
958211AF2-115 GEN
Solar/Wind Harmer
2.452
963191AG1-168 GEN
Solar/Wind Harmer
0.817
971741AH1-377 GEN
Solar/Wind Harmer
19.558
316034AC1-036 C
Solar/Wind Harmer
0.012
970323AG2-213 GEN
Solar/Wind Harmer
7.069
971775AH1-396 GEN
Solar/Wind Harmer
0.265
313527AB2-043 GEN
Solar/Wind Harmer
0.002
971489AH1-241 GEN
Solar/Wind Harmer
6.362
962561AG1-105 GEN
Solar/Wind Harmer
4.763
939181AE1-148 GEN
Solar/Wind Harmer
4.697
971223AH1-071 GEN
Solar/Wind Harmer
1.017
964791AG1-342 GEN
Solar/Wind Harmer
1.83
3146843MT LREL
Solar/Wind Harmer
0.095
3146843MT LREL
Solar/Wind Harmer
0.095
970099AG2-077 GEN
Solar/Wind Harmer
9.986
3143526WINTERP
Solar/Wind Harmer
0.415
970933AG2-581 GEN
Solar/Wind Harmer
5.925
316181AB2-040 GEN
Solar/Wind Harmer
0.094
3145593CAROLNA
Solar/Wind Harmer
0.062
3145593CAROLNA
Solar/Wind Harmer
0.062
966811AG1-552 GEN
Solar/Wind Harmer
0.675
3145593CAROLNA
Solar/Wind Harmer
0.077
3145783HORNRTN
Solar/Wind Harmer
1.086
3145783HORNRTN
Solar/Wind Harmer
0.869
3145783HORNRTN
Solar/Wind Harmer
0.271
3145783HORNRTN
Solar/Wind Harmer
0.109
316426AA2-053 GEN
Solar/Wind Harmer
0.204
966001AG1-469 GEN
Solar/Wind Helper
0.174
3151921BEARGRDN G2
50/50
4.422
3144293JTRSVLE
50/50
0.69
970413AG2-270 GEN
50/50
8.802
3151591KERR 2
50/50
0.192
3151261ROARAP2
50/50
0.076
3150861SPRUNCD
50/50
0.297
3151031BRUNSWICKG2
50/50
0.785
3146776BUCKING
Solar/Wind Harmer
0.136
3146926FARMVIL
Solar/Wind Harmer
0.178
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316313AB2-026
Solar/Wind Harmer
0.156
316258AE1-075 C
Solar/Wind Harmer
0.187
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.737
970909AG2-566 GEN
Solar/Wind Harmer
2.353
3147133PAMPLIN
Solar/Wind Harmer
0.682
971193AH1-056 GEN
Solar/Wind Harmer
13.238
963181AG1-167 GEN
Solar/Wind Harmer
0.817
959311AF2-222 GEN
Solar/Wind Harmer
15.236
970257AG2-171 GEN
Solar/Wind Harmer
5.302
315785AD2-033 C
Solar/Wind Harmer
1.283
964241AG1-285 GEN
Solar/Wind Harmer
9.125
316131AB2-060 GEN
Solar/Wind Harmer
0.39
970221AG2-151 GEN
Solar/Wind Harmer
6.362
316478AD1-087 GEN
Solar/Wind Harmer
0.328
316486AD2-202 GEN
Solar/Wind Harmer
0.096
3147043LAWRENC
Solar/Wind Harmer
0.05
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.274
971683AH1-343 GEN
Solar/Wind Harmer
2.442
313506AB2-031 GEN
Solar/Wind Harmer
0.2
970917AG2-570 GEN
Solar/Wind Harmer
5.117
316365GEN2_N
Solar/Wind Harmer
0.127
3148013FISHERV
Solar/Wind Helper
0.18
316499AE2-029_GEN
Solar/Wind Helper
0.518
315616AA1-038_C
Solar/Wind Helper
0.562
3132273ORANGE
Solar/Wind Helper
0.024
3151931BEARGRDN S1
50/50
5.707
3151911BEARGRDN G1
50/50
4.422
3144293JTRSVLE
50/50
0.69
970119AG2-088 GEN
50/50
12.707
3151531CLOVER1
50/50
2.017
3151601KERR 3
50/50
0.192
3151581KERR 1
50/50
0.069
3147043LAWRENC
50/50
0.8
3151261ROARAP2
50/50
0.077
3150851SPRUNCC
50/50
0.297
3151051BRUNSWICKS1
50/50
1.63
3151021BRUNSWICKG1
50/50
0.785
971451AH1-221 GEN
50/50
2.385
315243AE2-183_GT3
50/50
0.972
972003AH1-546 GEN
Solar/Wind Harmer
19.447
970937AG2-583 GEN
Solar/Wind Harmer
23.874
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.151
3146926FARMVIL
Solar/Wind Harmer
0.178
316336AC2-165 C
Solar/Wind Harmer
0.011
3143336POWHATN
Solar/Wind Harmer
4.396
963171AG1-166 GEN
Solar/Wind Harmer
1.09
971563AH1-280 GEN
Solar/Wind Harmer
2.18
970685AG2-442 GEN
Solar/Wind Harmer
13.857
962491AG1-098 GEN
Solar/Wind Harmer
7.06
971377AH1-170 GEN
Solar/Wind Harmer
1.272
3147623JAMES R
Solar/Wind Harmer
0.276
315693AD1-088 GEN
Solar/Wind Harmer
5.685
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3143226MDLTHAN
Solar/Wind Harmer
0.095
970401AG2-262 GEN
Solar/Wind Harmer
0.559
957481AF2-042 GEN
Solar/Wind Harmer
24.966
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
3.579
316129AC1-054 GEN
Solar/Wind Harmer
0.309
3143526WINTERP
Solar/Wind Harmer
0.415
971795AH1-408 GEN
Solar/Wind Harmer
5.206
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.641
3145783HORNRTN
Solar/Wind Harmer
0.061
316190AA2-174 GEN
Solar/Wind Harmer
0
970919AG2-571 GEN
Solar/Wind Harmer
2.047
970087AG2-069 GEN
Solar/Wind Harmer
4.587
316023GEN1_S
Solar/Wind Harmer
0.127
3147983MERCK5
Solar/Wind Helper
0.057
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.118
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.349
LAGNLTFEXP_LAGN->PJM
CLTF
0.897
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.783
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.427
CPLELTFEXP_CPLE->PJM
CLTF
3.08
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.625
MDUPJM->LTFIMP_MDU
CLTF
0
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.208
NYPJM->LTFIMP_NY
CLTF
0.345

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:202.03 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:1371.17
MW Contribution:3.45
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.754
3144293JTRSVLE
50/50
0.635
970535AG2-341 GEN
50/50
2.24
3151921BEARGRDN G2
50/50
4.548
3144293JTRSVLE
50/50
0.754
970413AG2-270 GEN
50/50
10.906
3151591KERR 2
50/50
0.234
3151031BRUNSWICKG2
50/50
1.135
3151261ROARAP2
50/50
0.101
3150861SPRUNCD
50/50
0.398
3151391GASTONA
50/50
0.204
3151411GASTONB
50/50
0.204
3146776BUCKING
Solar/Wind Harmer
0.141
3146926FARMVIL
Solar/Wind Harmer
0.188
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
316313AB2-026
Solar/Wind Harmer
0.171
316258AE1-075 C
Solar/Wind Harmer
0.204
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
4.088
970909AG2-566 GEN
Solar/Wind Harmer
2.566
3147133PAMPLIN
Solar/Wind Harmer
0.741
971193AH1-056 GEN
Solar/Wind Harmer
14.378
972205AH1-687 GEN
50/50
22.18
316303AF2-085
50/50
2.224
3151541CLOVER2
50/50
2.487
3151611KERR 4
50/50
0.234
3151621KERR 5
50/50
0.234
3151631KERR 6
50/50
0.234
3151641KERR 7
50/50
0.234
963041AG1-153 GEN
50/50
2.299
315244AE2-183_ST
50/50
2.451
3151281ROARAP4
50/50
0.1
3151281ROARAP4
50/50
0.094
971285AH1-108 GEN
50/50
0.651
315779AE2-040
50/50
1.092
971845AH1-439 GEN
Solar/Wind Harmer
17.513
970285AG2-188 GEN
Solar/Wind Harmer
29.552
3152661PLYWOOD A
50/50
0.227
3151041BRUNSWICKG3
50/50
1.135
972187AH1-678 GEN
50/50
2.606
315242AE2-183_GT2
50/50
1.418
315241AE2-183_GT1
50/50
1.409
972185AH1-677 GEN
50/50
5.111
970533AG2-339 GEN
50/50
7.548
970531AG2-338 GEN
50/50
3.019
3146776BUCKING
Solar/Wind Harmer
1.571
3146776BUCKING
Solar/Wind Harmer
0.127
970301AG2-198 GEN
Solar/Wind Harmer
10.262
3147133PAMPLIN
Solar/Wind Harmer
0.236
3147133PAMPLIN
Solar/Wind Harmer
0.189
958211AF2-115 GEN
Solar/Wind Harmer
2.678
963191AG1-168 GEN
Solar/Wind Harmer
0.893
971741AH1-377 GEN
Solar/Wind Harmer
21.598
316034AC1-036 C
Solar/Wind Harmer
0.014
970323AG2-213 GEN
Solar/Wind Harmer
7.892
971775AH1-396 GEN
Solar/Wind Harmer
0.296
313527AB2-043 GEN
Solar/Wind Harmer
0.002
971489AH1-241 GEN
Solar/Wind Harmer
7.009
971223AH1-071 GEN
Solar/Wind Harmer
1.334
962561AG1-105 GEN
Solar/Wind Harmer
5.681
939181AE1-148 GEN
Solar/Wind Harmer
5.661
970099AG2-077 GEN
Solar/Wind Harmer
12.506
964791AG1-342 GEN
Solar/Wind Harmer
2.195
315657AE1-056 GEN
Solar/Wind Harmer
8.144
946301AF1-294 GEN
Solar/Wind Harmer
4.404
961791AG1-021 GEN
Solar/Wind Harmer
2.143
970683AG2-441 GEN
Solar/Wind Harmer
13.644
970681AG2-440 GEN
Solar/Wind Harmer
10.915
3144303KENBRDG
Solar/Wind Harmer
0.148
971443AH1-215 GEN
Solar/Wind Harmer
3.079
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316233AE1-074 FULL
Solar/Wind Harmer
0.084
971281AH1-106 GEN
Solar/Wind Harmer
1.459
971283AH1-107 GEN
Solar/Wind Harmer
1.459
316118AC1-105 GEN
Solar/Wind Harmer
0.27
270494AE1-108_GEN
Solar/Wind Harmer
1.236
970831AG2-522 GEN
Solar/Wind Harmer
4.291
3147173SINAI
Solar/Wind Harmer
0.095
3147243WELCO
Solar/Wind Harmer
0.059
971967AH1-528 GEN
Solar/Wind Harmer
14.709
316087AB2-174 GEN
Solar/Wind Harmer
0.002
970673AG2-436 GEN
Solar/Wind Harmer
18.242
970673AG2-436 GEN
Solar/Wind Harmer
12.162
941031AE2-094 GEN
Solar/Wind Harmer
15.639
944011AF1-069 GEN
Solar/Wind Harmer
5.11
3137643SOCKMAN
Solar/Wind Harmer
0.336
970085AG2-068 GEN
Solar/Wind Harmer
4.411
970581AG2-369 GEN
Solar/Wind Harmer
3.794
315607AA1-063A GEN
Solar/Wind Harmer
0.164
3146043SEABORD
Solar/Wind Harmer
0.08
315814AE2-033 C
Solar/Wind Harmer
6.192
316315AB2-025 C
Solar/Wind Harmer
0.063
970865AG2-541 GEN
Solar/Wind Harmer
2.68
3151931BEARGRDN S1
50/50
5.869
3151911BEARGRDN G1
50/50
4.548
3144293JTRSVLE
50/50
0.754
970119AG2-088 GEN
50/50
16.679
3151531CLOVER1
50/50
2.499
3151601KERR 3
50/50
0.234
3151581KERR 1
50/50
0.083
3147043LAWRENC
50/50
1
3151051BRUNSWICKS1
50/50
2.357
3151021BRUNSWICKG1
50/50
1.135
971451AH1-221 GEN
50/50
3.449
315243AE2-183_GT3
50/50
1.418
3151261ROARAP2
50/50
0.103
3150851SPRUNCC
50/50
0.398
3151391GASTONA
50/50
0.204
3151411GASTONB
50/50
0.204
972003AH1-546 GEN
Solar/Wind Harmer
20.039
970937AG2-583 GEN
Solar/Wind Harmer
24.928
316322AB2-045
Solar/Wind Harmer
0.003
3146843MT LREL
Solar/Wind Harmer
0.114
3146843MT LREL
Solar/Wind Harmer
0.114
3143526WINTERP
Solar/Wind Harmer
0.547
970933AG2-581 GEN
Solar/Wind Harmer
7.995
316181AB2-040 GEN
Solar/Wind Harmer
0.124
3145593CAROLNA
Solar/Wind Harmer
0.083
3145593CAROLNA
Solar/Wind Harmer
0.083
966811AG1-552 GEN
Solar/Wind Harmer
0.899
3145593CAROLNA
Solar/Wind Harmer
0.103
3145783HORNRTN
Solar/Wind Harmer
1.451
3145783HORNRTN
Solar/Wind Harmer
1.161
3145783HORNRTN
Solar/Wind Harmer
0.363
3145783HORNRTN
Solar/Wind Harmer
0.145
316426AA2-053 GEN
Solar/Wind Harmer
0.274
3144356SAPONY
Solar/Wind Harmer
0.654
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
0.503
3145893MURPHYS
Solar/Wind Harmer
0.135
316274AC1-208 GEN
Solar/Wind Harmer
0.39
3145796HORNRTN
Solar/Wind Harmer
0.223
3146173TUNIS
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
315742AE1-103 GEN
Solar/Wind Harmer
0.001
970657AG2-426 GEN
Solar/Wind Harmer
2.47
970657AG2-426 GEN
Solar/Wind Harmer
0.518
316065AD1-022 GEN
Solar/Wind Harmer
3.223
3146376EDENTON
Solar/Wind Harmer
0.308
3146376EDENTON
Solar/Wind Harmer
0.308
3146626S HERTFORD
Solar/Wind Harmer
0.069
3146626S HERTFORD
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3146386ELIZ CT
Solar/Wind Harmer
0.069
316240AF1-291 C
Solar/Wind Harmer
0.001
3130086AYDLETT
Solar/Wind Harmer
0.275
3137176SLIGO L2192
Solar/Wind Harmer
0.273
3146456SLIGO L269
Solar/Wind Harmer
1.215
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.038
316339AD2-160 GEN
Solar/Wind Harmer
0.111
3145506HICKORY
Solar/Wind Harmer
0.274
3145506HICKORY
Solar/Wind Harmer
0.165
3145506HICKORY
Solar/Wind Harmer
0.041
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.066
316036AC1-147 C
Solar/Wind Harmer
0.013
3150991CHESPKB
Adder
0.716
3150991CHESPKB
Adder
0.699
944641AF1-129 GEN
Adder
32.505
316222AC1-221 GEN
Solar/Wind Harmer
0.283
316263AC1-034 GEN
Solar/Wind Harmer
2.586
3145933PARMELE
Solar/Wind Harmer
0.135
3145933PARMELE
Solar/Wind Harmer
0.068
961601AG1-000A GEN
Solar/Wind Harmer
1.202
3145493TOT1
Solar/Wind Harmer
0.156
3145453TOT5
Solar/Wind Harmer
0.094
3145603CNETO
Solar/Wind Harmer
0.063
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316033AB2-134 GEN
Solar/Wind Harmer
0.004
315697AD1-025 GEN
Solar/Wind Harmer
0.074
3142366NRTHEST
Adder
0.195
3142946ENON
Solar/Wind Harmer
0.006
3150691DARBY 3
Adder
4.195
3150701DARBY 4
Adder
4.185
3150681DARBY 2
Adder
4.18
3150671DARBY 1
Adder
4.175
942751AE2-291 GEN
Solar/Wind Harmer
3.155
966001AG1-469 GEN
Solar/Wind Helper
0.19
963181AG1-167 GEN
Solar/Wind Harmer
0.893
959311AF2-222 GEN
Solar/Wind Harmer
16.945
970257AG2-171 GEN
Solar/Wind Harmer
5.919
315785AD2-033 C
Solar/Wind Harmer
1.44
964241AG1-285 GEN
Solar/Wind Harmer
10.432
316131AB2-060 GEN
Solar/Wind Harmer
0.453
970221AG2-151 GEN
Solar/Wind Harmer
7.009
316478AD1-087 GEN
Solar/Wind Harmer
0.407
316486AD2-202 GEN
Solar/Wind Harmer
0.12
3147043LAWRENC
Solar/Wind Harmer
0.063
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
4.061
313506AB2-031 GEN
Solar/Wind Harmer
0.265
971683AH1-343 GEN
Solar/Wind Harmer
3.059
970917AG2-570 GEN
Solar/Wind Harmer
7.384
316365GEN2_N
Solar/Wind Harmer
0.176
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3146263WOODLND
Solar/Wind Harmer
0.076
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3145893MURPHYS
Solar/Wind Harmer
0.126
3145893MURPHYS
Solar/Wind Harmer
0.075
957521AF2-046 GEN
Solar/Wind Harmer
5.572
961681AG1-008 GEN
Solar/Wind Harmer
5.572
3145796HORNRTN
Solar/Wind Harmer
0.297
3145796HORNRTN
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
316210AC1-098 GEN
Solar/Wind Harmer
0.686
316463AE2-346 GEN
Solar/Wind Harmer
0.063
316140AB2-099
Solar/Wind Harmer
0.026
962331AG1-082 GEN
Solar/Wind Harmer
0.783
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.073
316327AA2-057 GEN
Solar/Wind Harmer
0.108
3145273HOLLAND
Solar/Wind Harmer
0.054
315813AE1-149 C
Solar/Wind Harmer
3.784
3156021HOLLOMANSOL
Solar/Wind Harmer
0.322
315839AE2-212 C
Solar/Wind Harmer
0.001
315724AD1-057 GEN
Solar/Wind Harmer
0.265
970659AG2-427 GEN
Solar/Wind Harmer
0.747
316083AB2-161 GEN
Solar/Wind Harmer
0.001
970661AG2-428 GEN
Solar/Wind Harmer
1.49
3146206CASHIE
Solar/Wind Harmer
0.07
3146233WITAKRS
Solar/Wind Harmer
0.351
3146233WITAKRS
Solar/Wind Harmer
0.048
3138543CONSLDL
Solar/Wind Harmer
0.046
315737AD1-076 GEN
Solar/Wind Harmer
0.896
971157AH1-035 GEN
Solar/Wind Harmer
0.836
965281AG1-393 GEN
Solar/Wind Harmer
0.741
315614AA2-178 GEN
Solar/Wind Harmer
0.398
3146376EDENTON
Solar/Wind Harmer
0.069
3146626S HERTFORD
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
316435W1029_GEN3
Solar/Wind Harmer
0
316320Y1-086
Solar/Wind Harmer
0
3146456SLIGO L269
Solar/Wind Harmer
0.069
971153AH1-033 GEN
Solar/Wind Harmer
0.794
944581AF1-123 GEN
Solar/Wind Harmer
15.457
944601AF1-125 GEN
Solar/Wind Harmer
15.219
3145963POPLR C
Solar/Wind Harmer
0.069
3151101ELIZAR3
Adder
6.349
3144873MCLAUGH
Solar/Wind Harmer
0.002
3145543BTLEBRO
Solar/Wind Harmer
0.068
3145543BTLEBRO
Solar/Wind Harmer
0.068
971623AH1-311 GEN
Solar/Wind Harmer
0.136
3144536CHRHLND
Solar/Wind Harmer
0.01
3145933PARMELE
Solar/Wind Harmer
0.068
966801AG1-551 GEN
Solar/Wind Harmer
0.788
961601AG1-000A GEN
Solar/Wind Harmer
4.808
315773AC2-141 GEN
Solar/Wind Harmer
2.468
3146073TAR RVR
Solar/Wind Harmer
0.067
3146083TARBORO
Solar/Wind Harmer
0.067
316283AC2-100 C
Solar/Wind Harmer
0.132
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
3145336SMITFLD
Solar/Wind Harmer
0.027
3143096IRON208
Adder
0.277
3143096IRON208
Adder
0.272
3151221GRAVEL6
Adder
4.798
3151171GRAVELC
Adder
0.923
961611AG1-000B GEN
Solar/Wind Harmer
1.758
315778AD1-151 GEN
Solar/Wind Harmer
5.261
970129AG2-093 GEN
Solar/Wind Harmer
3.971
970133AG2-095 GEN
Solar/Wind Harmer
0.63
3144216WINCHST
Adder
0.231
3150921YORKTN3
Adder
1.525
3142946ENON
Solar/Wind Harmer
0.02
316382AG1-145 C
Solar/Wind Harmer
0
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3148013FISHERV
Solar/Wind Helper
0.175
316499AE2-029_GEN
Solar/Wind Helper
0.514
3132273ORANGE
Solar/Wind Helper
0.027
315616AA1-038_C
Solar/Wind Helper
0.545
3147666LOUISA
Solar/Wind Helper
0.273
965291AG1-394 GEN
Solar/Wind Harmer
0.339
315652AC1-086 GEN
Solar/Wind Harmer
8.307
3145893MURPHYS
Solar/Wind Harmer
0.203
3145893MURPHYS
Solar/Wind Harmer
0.075
3145796HORNRTN
Solar/Wind Harmer
0.238
3145796HORNRTN
Solar/Wind Harmer
0.03
3143316POE
Solar/Wind Harmer
0.292
3146033SCOT NK
Solar/Wind Harmer
0.294
3145513AHOSKIE
Solar/Wind Harmer
0.153
3145513AHOSKIE
Solar/Wind Harmer
0.073
3145683EARLEYS
Solar/Wind Harmer
0.146
3145683EARLEYS
Solar/Wind Harmer
0.073
3145683EARLEYS
Solar/Wind Harmer
0.073
3146206CASHIE
Solar/Wind Harmer
0.07
970601AG2-382 GEN
Solar/Wind Harmer
2.62
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.048
316311AC2-079 GEN
Solar/Wind Harmer
2.01
316319Z2-044 C
Solar/Wind Harmer
0
315732AD1-074 GEN1
Solar/Wind Harmer
0.4
315733AD1-074 GEN2
Solar/Wind Harmer
0.4
315735AD1-075 GEN1
Solar/Wind Harmer
0.2
3130546PLYMOUTH
Solar/Wind Harmer
0.07
315835AF2-110_GEN
Solar/Wind Harmer
0.478
315816AE2-034 GEN
Solar/Wind Harmer
0.298
3130156CHOWAN
Solar/Wind Harmer
0.069
3130156CHOWAN
Solar/Wind Harmer
0.069
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3146486SUNBURY
Solar/Wind Harmer
0.069
3146486SUNBURY
Solar/Wind Harmer
0.069
316321Z2-027
Solar/Wind Harmer
0.013
3145176PASQUOTANK
Solar/Wind Harmer
0.043
3146396TANGLEW
Solar/Wind Harmer
0.19
316305AF2-043 C
Solar/Wind Harmer
0.001
313526AB2-022
Solar/Wind Harmer
0.037
3146406KITTY HAWK
Solar/Wind Harmer
0.009
319010AE1-072 C
Solar/Wind Harmer
0.346
957871AF2-081 GEN
Solar/Wind Harmer
3.419
3151081ELIZAR1
Adder
6.268
3151091ELIZAR2
Adder
6.16
3152611GOSPORTB
Adder
0.871
3152621GOSPORTC
Adder
0.739
3152601GOSPORTA
Adder
0.682
3145573BETHELC
Solar/Wind Harmer
0.067
3145573BETHELC
Solar/Wind Harmer
0.067
316420AA1-050 GEN
Solar/Wind Harmer
0.002
957861AF2-080 GEN
Solar/Wind Harmer
2.903
316005AA1-067
Solar/Wind Harmer
0.072
3145746EVERETS
Solar/Wind Harmer
0.267
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
970181AG2-120 GEN
Solar/Wind Harmer
0.836
971445AH1-216 GEN
Solar/Wind Harmer
4.703
972265AH1-717 GEN
Adder
5.124
3151201GRAVEL4
Adder
4.803
3151191GRAVEL3
Adder
4.742
3151211GRAVEL5
Adder
4.742
316369SG1_INVT
Solar/Wind Harmer
0.002
316132AB2-190 GEN1
Solar/Wind Harmer
0.353
316123AC1-075 GEN
Solar/Wind Harmer
0.09
970165AG2-112 GEN
Solar/Wind Harmer
0.531
970163AG2-111 GEN
Solar/Wind Harmer
0.506
971447AH1-217 GEN
Solar/Wind Harmer
1.848
971167AH1-042 GEN
Solar/Wind Harmer
5.088
3138283WHITEMARSH
Solar/Wind Harmer
0.013
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.105
3148013FISHERV
Solar/Wind Helper
0.101
3148463FAIRFLD
Solar/Wind Helper
0.12
3146776BUCKING
Solar/Wind Harmer
0.157
3146926FARMVIL
Solar/Wind Harmer
0.188
316336AC2-165 C
Solar/Wind Harmer
0.012
3143336POWHATN
Solar/Wind Harmer
4.81
963171AG1-166 GEN
Solar/Wind Harmer
1.19
971563AH1-280 GEN
Solar/Wind Harmer
2.381
970685AG2-442 GEN
Solar/Wind Harmer
15.281
962491AG1-098 GEN
Solar/Wind Harmer
8.349
315693AD1-088 GEN
Solar/Wind Harmer
6.776
316237AB2-079_GEN
Solar/Wind Harmer
0.001
971377AH1-170 GEN
Solar/Wind Harmer
1.402
3147623JAMES R
Solar/Wind Harmer
0.305
3143226MDLTHAN
Solar/Wind Harmer
0.125
957481AF2-042 GEN
Solar/Wind Harmer
31.266
970401AG2-262 GEN
Solar/Wind Harmer
0.671
315687AD1-152 GEN
Solar/Wind Harmer
0.003
3143526WINTERP
Solar/Wind Harmer
0.547
971065AG2-659 GEN
Solar/Wind Harmer
4.446
316129AC1-054 GEN
Solar/Wind Harmer
0.385
971795AH1-408 GEN
Solar/Wind Harmer
6.611
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.847
970919AG2-571 GEN
Solar/Wind Harmer
2.953
970087AG2-069 GEN
Solar/Wind Harmer
6.617
3145783HORNRTN
Solar/Wind Harmer
0.082
316190AA2-174 GEN
Solar/Wind Harmer
0
940641AE2-051 GEN
Solar/Wind Harmer
6.459
316023GEN1_S
Solar/Wind Harmer
0.176
939411AE1-173 GEN
Solar/Wind Harmer
33.156
3146263WOODLND
Solar/Wind Harmer
0.076
316011AB1-132 GEN
Solar/Wind Harmer
1.373
962571AG1-106 GEN
Solar/Wind Harmer
1.074
3145893MURPHYS
Solar/Wind Harmer
0.301
3145893MURPHYS
Solar/Wind Harmer
0.334
3145796HORNRTN
Solar/Wind Harmer
0.245
3145796HORNRTN
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
316212AC1-099_GEN
Solar/Wind Harmer
0.382
3145823KELFORD
Solar/Wind Harmer
0.073
3145683EARLEYS
Solar/Wind Harmer
0.073
315722AD1-056 GEN
Solar/Wind Harmer
0.447
970659AG2-427 GEN
Solar/Wind Harmer
3.416
316381AD1-082 GEN
Solar/Wind Harmer
0.074
970661AG2-428 GEN
Solar/Wind Harmer
7.004
3146206CASHIE
Solar/Wind Harmer
0.07
971547AH1-271 GEN
Solar/Wind Harmer
1.497
3142543TWELFTH
Solar/Wind Harmer
0.007
3146233WITAKRS
Solar/Wind Harmer
0.278
316093AE2-104_GEN
Solar/Wind Harmer
1.171
3145663CRESWEL
Solar/Wind Harmer
0.194
971163AH1-040 GEN
Solar/Wind Harmer
5.558
3130156CHOWAN
Solar/Wind Harmer
0.069
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.223
3146516WINFALL
Solar/Wind Harmer
0.069
315671AE2-027_GEN
Solar/Wind Harmer
4.41
316246AF1-032 C
Solar/Wind Harmer
0.031
3146456SLIGO L269
Solar/Wind Harmer
0.069
316388AE2-253 GEN
Solar/Wind Harmer
0.215
944591AF1-124 GEN
Solar/Wind Harmer
15.512
3145963POPLR C
Solar/Wind Harmer
0.069
316174AB2-169 GEN
Solar/Wind Harmer
0.002
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
0.853
3145543BTLEBRO
Solar/Wind Harmer
0.068
3145543BTLEBRO
Solar/Wind Harmer
0.054
316359AB2-059 GEN
Solar/Wind Harmer
0.244
316049AB1-081 GEN
Solar/Wind Harmer
0.389
3142053HEARTS
Solar/Wind Harmer
0.12
316072AD1-144
Solar/Wind Harmer
0.025
3146293MARTNCO
Solar/Wind Harmer
0.063
316294AC1-161 GEN
Solar/Wind Harmer
1.171
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.067
3145493TOT1
Solar/Wind Harmer
0.3
316494AC1-189 GEN
Solar/Wind Harmer
0.227
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
3145336SMITFLD
Solar/Wind Harmer
0.267
3143096IRON208
Adder
0.277
3151171GRAVELC
Adder
0.702
961611AG1-000B GEN
Solar/Wind Harmer
3.457
971647AH1-324 GEN
Solar/Wind Harmer
2.81
971069AG2-661 GEN
Solar/Wind Harmer
1.169
316458AB2-190 GEN2
Solar/Wind Harmer
0.353
970129AG2-093 GEN
Solar/Wind Harmer
1.869
944631AF1-128 GEN
Adder
29.45
3138126ROCKLANDING
Solar/Wind Harmer
0.028
971317AH1-138 GEN
Solar/Wind Harmer
0.439
316159AE1-175 C
Solar/Wind Harmer
0.05
3142433PROV 92
Solar/Wind Harmer
0.226
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3147983MERCK5
Solar/Wind Helper
0.056
316192AB2-158 GEN
Solar/Wind Helper
0.823
3147666LOUISA
Solar/Wind Helper
0.475
LAGNLTFEXP_LAGN->PJM
CLTF
1.781
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.535
TVALTFEXP_TVA->PJM
CLTF
0.87
CPLELTFEXP_CPLE->PJM
CLTF
4.352
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.276
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.726
MECLTFEXP_MEC->PJM
CLTF
0.354
SIGELTFEXP_SIGE->PJM
CLTF
0.008
NYPJM->LTFIMP_NY
CLTF
0.579
LGEELTFEXP_LGEE->PJM
CLTF
0.048
WECLTFEXP_WEC->PJM
CLTF
0.018

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.86 %
Rating:678.68 MVA
Rating Type:A
MVA to Mitigate:765.97
MW Contribution:2.38
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
21.569
316303AF2-085
50/50
1.694
3151541CLOVER2
50/50
2.007
3151611KERR 4
50/50
0.192
3151621KERR 5
50/50
0.192
3151631KERR 6
50/50
0.192
3151641KERR 7
50/50
0.192
3151281ROARAP4
50/50
0.075
3144293JTRSVLE
50/50
0.69
3144293JTRSVLE
50/50
0.581
970535AG2-341 GEN
50/50
1.885
3152661PLYWOOD A
50/50
0.185
3151041BRUNSWICKG3
50/50
0.785
972187AH1-678 GEN
50/50
1.802
315242AE2-183_GT2
50/50
0.972
315241AE2-183_GT1
50/50
0.966
972185AH1-677 GEN
50/50
3.505
970533AG2-339 GEN
50/50
5.074
970531AG2-338 GEN
50/50
2.029
3146776BUCKING
Solar/Wind Harmer
1.508
3146776BUCKING
Solar/Wind Harmer
0.122
970301AG2-198 GEN
Solar/Wind Harmer
9.412
3147133PAMPLIN
Solar/Wind Harmer
0.217
3147133PAMPLIN
Solar/Wind Harmer
0.174
958211AF2-115 GEN
Solar/Wind Harmer
2.452
963191AG1-168 GEN
Solar/Wind Harmer
0.817
971741AH1-377 GEN
Solar/Wind Harmer
19.558
316034AC1-036 C
Solar/Wind Harmer
0.012
970323AG2-213 GEN
Solar/Wind Harmer
7.069
3151281ROARAP4
50/50
0.07
971285AH1-108 GEN
50/50
0.486
963041AG1-153 GEN
50/50
1.59
315244AE2-183_ST
50/50
1.681
971845AH1-439 GEN
Solar/Wind Harmer
16.786
970285AG2-188 GEN
Solar/Wind Harmer
28.258
315657AE1-056 GEN
Solar/Wind Harmer
7.498
946301AF1-294 GEN
Solar/Wind Harmer
4.032
961791AG1-021 GEN
Solar/Wind Harmer
1.962
970683AG2-441 GEN
Solar/Wind Harmer
12.373
970681AG2-440 GEN
Solar/Wind Harmer
9.898
3144303KENBRDG
Solar/Wind Harmer
0.132
971443AH1-215 GEN
Solar/Wind Harmer
2.755
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
270494AE1-108_GEN
Solar/Wind Harmer
1.107
316118AC1-105 GEN
Solar/Wind Harmer
0.222
970831AG2-522 GEN
Solar/Wind Harmer
3.422
316233AE1-074 FULL
Solar/Wind Harmer
0.064
971281AH1-106 GEN
Solar/Wind Harmer
1.107
971283AH1-107 GEN
Solar/Wind Harmer
1.107
3147173SINAI
Solar/Wind Harmer
0.077
3147243WELCO
Solar/Wind Harmer
0.048
316087AB2-174 GEN
Solar/Wind Harmer
0.002
971967AH1-528 GEN
Solar/Wind Harmer
10.427
3137643SOCKMAN
Solar/Wind Harmer
0.253
970865AG2-541 GEN
Solar/Wind Harmer
2.127
315607AA1-063A GEN
Solar/Wind Harmer
0.122
3146043SEABORD
Solar/Wind Harmer
0.059
970673AG2-436 GEN
Solar/Wind Harmer
12.427
970673AG2-436 GEN
Solar/Wind Harmer
8.285
970085AG2-068 GEN
Solar/Wind Harmer
3.058
970581AG2-369 GEN
Solar/Wind Harmer
2.63
941031AE2-094 GEN
Solar/Wind Harmer
10.513
944011AF1-069 GEN
Solar/Wind Harmer
3.435
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.108
3148013FISHERV
Solar/Wind Helper
0.103
3148463FAIRFLD
Solar/Wind Helper
0.124
971775AH1-396 GEN
Solar/Wind Harmer
0.265
313527AB2-043 GEN
Solar/Wind Harmer
0.002
971489AH1-241 GEN
Solar/Wind Harmer
6.362
962561AG1-105 GEN
Solar/Wind Harmer
4.763
939181AE1-148 GEN
Solar/Wind Harmer
4.697
971223AH1-071 GEN
Solar/Wind Harmer
1.017
964791AG1-342 GEN
Solar/Wind Harmer
1.83
3146843MT LREL
Solar/Wind Harmer
0.095
3146843MT LREL
Solar/Wind Harmer
0.095
970099AG2-077 GEN
Solar/Wind Harmer
9.986
3143526WINTERP
Solar/Wind Harmer
0.415
970933AG2-581 GEN
Solar/Wind Harmer
5.925
316181AB2-040 GEN
Solar/Wind Harmer
0.094
3145593CAROLNA
Solar/Wind Harmer
0.062
3145593CAROLNA
Solar/Wind Harmer
0.062
966811AG1-552 GEN
Solar/Wind Harmer
0.675
3145593CAROLNA
Solar/Wind Harmer
0.077
3145783HORNRTN
Solar/Wind Harmer
1.086
3151921BEARGRDN G2
50/50
4.422
3144293JTRSVLE
50/50
0.69
970413AG2-270 GEN
50/50
8.802
3151591KERR 2
50/50
0.192
3151261ROARAP2
50/50
0.076
3150861SPRUNCD
50/50
0.297
3151031BRUNSWICKG2
50/50
0.785
3146776BUCKING
Solar/Wind Harmer
0.136
3146926FARMVIL
Solar/Wind Harmer
0.178
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316313AB2-026
Solar/Wind Harmer
0.156
316258AE1-075 C
Solar/Wind Harmer
0.187
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.737
970909AG2-566 GEN
Solar/Wind Harmer
2.353
3147133PAMPLIN
Solar/Wind Harmer
0.682
971193AH1-056 GEN
Solar/Wind Harmer
13.238
963181AG1-167 GEN
Solar/Wind Harmer
0.817
959311AF2-222 GEN
Solar/Wind Harmer
15.236
970257AG2-171 GEN
Solar/Wind Harmer
5.302
315785AD2-033 C
Solar/Wind Harmer
1.283
964241AG1-285 GEN
Solar/Wind Harmer
9.125
316131AB2-060 GEN
Solar/Wind Harmer
0.39
970221AG2-151 GEN
Solar/Wind Harmer
6.362
316478AD1-087 GEN
Solar/Wind Harmer
0.328
316486AD2-202 GEN
Solar/Wind Harmer
0.096
3147043LAWRENC
Solar/Wind Harmer
0.05
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.274
971683AH1-343 GEN
Solar/Wind Harmer
2.442
313506AB2-031 GEN
Solar/Wind Harmer
0.2
970917AG2-570 GEN
Solar/Wind Harmer
5.117
316365GEN2_N
Solar/Wind Harmer
0.127
3148013FISHERV
Solar/Wind Helper
0.18
316499AE2-029_GEN
Solar/Wind Helper
0.518
315616AA1-038_C
Solar/Wind Helper
0.562
3132273ORANGE
Solar/Wind Helper
0.024
3151931BEARGRDN S1
50/50
5.707
3151911BEARGRDN G1
50/50
4.422
3144293JTRSVLE
50/50
0.69
970119AG2-088 GEN
50/50
12.707
3151531CLOVER1
50/50
2.017
3151601KERR 3
50/50
0.192
3151581KERR 1
50/50
0.069
3147043LAWRENC
50/50
0.8
3151261ROARAP2
50/50
0.077
3150851SPRUNCC
50/50
0.297
3151051BRUNSWICKS1
50/50
1.63
3151021BRUNSWICKG1
50/50
0.785
971451AH1-221 GEN
50/50
2.385
315243AE2-183_GT3
50/50
0.972
972003AH1-546 GEN
Solar/Wind Harmer
19.447
970937AG2-583 GEN
Solar/Wind Harmer
23.874
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.151
3146926FARMVIL
Solar/Wind Harmer
0.178
316336AC2-165 C
Solar/Wind Harmer
0.011
3143336POWHATN
Solar/Wind Harmer
4.396
963171AG1-166 GEN
Solar/Wind Harmer
1.09
971563AH1-280 GEN
Solar/Wind Harmer
2.18
970685AG2-442 GEN
Solar/Wind Harmer
13.857
962491AG1-098 GEN
Solar/Wind Harmer
7.06
971377AH1-170 GEN
Solar/Wind Harmer
1.272
3147623JAMES R
Solar/Wind Harmer
0.276
315693AD1-088 GEN
Solar/Wind Harmer
5.685
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3143226MDLTHAN
Solar/Wind Harmer
0.095
970401AG2-262 GEN
Solar/Wind Harmer
0.559
957481AF2-042 GEN
Solar/Wind Harmer
24.966
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
3.579
316129AC1-054 GEN
Solar/Wind Harmer
0.309
3143526WINTERP
Solar/Wind Harmer
0.415
971795AH1-408 GEN
Solar/Wind Harmer
5.206
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.641
3145783HORNRTN
Solar/Wind Harmer
0.061
316190AA2-174 GEN
Solar/Wind Harmer
0
970919AG2-571 GEN
Solar/Wind Harmer
2.047
970087AG2-069 GEN
Solar/Wind Harmer
4.587
316023GEN1_S
Solar/Wind Harmer
0.127
3147983MERCK5
Solar/Wind Helper
0.057
3145783HORNRTN
Solar/Wind Harmer
0.869
3145783HORNRTN
Solar/Wind Harmer
0.271
3145783HORNRTN
Solar/Wind Harmer
0.109
316426AA2-053 GEN
Solar/Wind Harmer
0.204
966001AG1-469 GEN
Solar/Wind Helper
0.174
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.118
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.349
LAGNLTFEXP_LAGN->PJM
CLTF
0.897
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.783
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.427
CPLELTFEXP_CPLE->PJM
CLTF
3.08
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.625
MDUPJM->LTFIMP_MDU
CLTF
0
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.208
NYPJM->LTFIMP_NY
CLTF
0.345

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:177.07 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:1012.01
MW Contribution:3.36
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.227
3144293JTRSVLE
50/50
1.033
970535AG2-341 GEN
50/50
3.148
3152661PLYWOOD A
50/50
0.306
3151041BRUNSWICKG3
50/50
1.106
972187AH1-678 GEN
50/50
2.539
315242AE2-183_GT2
50/50
1.355
315241AE2-183_GT1
50/50
1.346
972185AH1-677 GEN
50/50
4.884
970533AG2-339 GEN
50/50
6.883
970531AG2-338 GEN
50/50
2.753
3151361ROSEMG1
50/50
0.26
3151371ROSEMS1
50/50
0.161
3151381ROSEMG2
50/50
0.122
3146776BUCKING
Solar/Wind Harmer
2.762
3146776BUCKING
Solar/Wind Harmer
0.224
970301AG2-198 GEN
Solar/Wind Harmer
16.775
3147133PAMPLIN
Solar/Wind Harmer
0.388
3147133PAMPLIN
Solar/Wind Harmer
0.31
958211AF2-115 GEN
Solar/Wind Harmer
4.358
963191AG1-168 GEN
Solar/Wind Harmer
1.453
971741AH1-377 GEN
Solar/Wind Harmer
34.576
316034AC1-036 C
Solar/Wind Harmer
0.021
970323AG2-213 GEN
Solar/Wind Harmer
12.374
971775AH1-396 GEN
Solar/Wind Harmer
0.464
313527AB2-043 GEN
Solar/Wind Harmer
0.003
962561AG1-105 GEN
Solar/Wind Harmer
7.996
939181AE1-148 GEN
Solar/Wind Harmer
7.758
964791AG1-342 GEN
Solar/Wind Harmer
3.064
3146843MT LREL
Solar/Wind Harmer
0.159
3146843MT LREL
Solar/Wind Harmer
0.159
970099AG2-077 GEN
Solar/Wind Harmer
16.138
970933AG2-581 GEN
Solar/Wind Harmer
8.941
316181AB2-040 GEN
Solar/Wind Harmer
0.133
3145593CAROLNA
Solar/Wind Harmer
0.088
3145593CAROLNA
Solar/Wind Harmer
0.088
966811AG1-552 GEN
Solar/Wind Harmer
0.955
3145593CAROLNA
Solar/Wind Harmer
0.11
3145783HORNRTN
Solar/Wind Harmer
1.535
3145783HORNRTN
Solar/Wind Harmer
1.228
3145783HORNRTN
Solar/Wind Harmer
0.384
3145783HORNRTN
Solar/Wind Harmer
0.153
316426AA2-053 GEN
Solar/Wind Harmer
0.285
316222AC1-221 GEN
Solar/Wind Harmer
0.347
316274AC1-208 GEN
Solar/Wind Harmer
0.401
3142666NORTHAMPTON
Solar/Wind Harmer
0.072
3142666NORTHAMPTON
Solar/Wind Harmer
0.072
3142666NORTHAMPTON
Solar/Wind Harmer
0.072
3142666NORTHAMPTON
Solar/Wind Harmer
0.043
942751AE2-291 GEN
Solar/Wind Harmer
3.936
3145796HORNRTN
Solar/Wind Harmer
0.217
3145893MURPHYS
Solar/Wind Harmer
0.472
3145893MURPHYS
Solar/Wind Harmer
0.127
316263AC1-034 GEN
Solar/Wind Harmer
2.649
3146173TUNIS
Solar/Wind Harmer
0.069
3146173TUNIS
Solar/Wind Harmer
0.069
961601AG1-000A GEN
Solar/Wind Harmer
1.224
3145493TOT1
Solar/Wind Harmer
0.156
3145453TOT5
Solar/Wind Harmer
0.094
3145603CNETO
Solar/Wind Harmer
0.062
3145933PARMELE
Solar/Wind Harmer
0.127
3145933PARMELE
Solar/Wind Harmer
0.064
3144356SAPONY
Solar/Wind Harmer
0.516
316065AD1-022 GEN
Solar/Wind Harmer
2.802
315742AE1-103 GEN
Solar/Wind Harmer
0.001
315821AE2-092 GEN
Solar/Wind Helper
2.989
3144293JTRSVLE
50/50
1.227
970413AG2-270 GEN
50/50
14.381
3151591KERR 2
50/50
0.314
3151261ROARAP2
50/50
0.107
3151031BRUNSWICKG2
50/50
1.106
3151391GASTONA
50/50
0.197
3151411GASTONB
50/50
0.197
3146776BUCKING
Solar/Wind Harmer
0.249
3146926FARMVIL
Solar/Wind Harmer
0.322
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
4.194
3147133PAMPLIN
Solar/Wind Harmer
1.217
971193AH1-056 GEN
Solar/Wind Harmer
23.622
963181AG1-167 GEN
Solar/Wind Harmer
1.453
959311AF2-222 GEN
Solar/Wind Harmer
26.742
970257AG2-171 GEN
Solar/Wind Harmer
9.28
315785AD2-033 C
Solar/Wind Harmer
2.237
964241AG1-285 GEN
Solar/Wind Harmer
15.699
316131AB2-060 GEN
Solar/Wind Harmer
0.665
316478AD1-087 GEN
Solar/Wind Harmer
0.537
316486AD2-202 GEN
Solar/Wind Harmer
0.158
3147043LAWRENC
Solar/Wind Harmer
0.077
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
5.394
971683AH1-343 GEN
Solar/Wind Harmer
4.007
313506AB2-031 GEN
Solar/Wind Harmer
0.283
316283AC2-100 C
Solar/Wind Harmer
0.161
970917AG2-570 GEN
Solar/Wind Harmer
7.271
316210AC1-098 GEN
Solar/Wind Harmer
0.691
316327AA2-057 GEN
Solar/Wind Harmer
0.111
3146263WOODLND
Solar/Wind Harmer
0.073
316365GEN2_N
Solar/Wind Harmer
0.163
3142666NORTHAMPTON
Solar/Wind Harmer
0.072
3145796HORNRTN
Solar/Wind Harmer
0.289
3145796HORNRTN
Solar/Wind Harmer
0.072
3146233WITAKRS
Solar/Wind Harmer
0.36
3146233WITAKRS
Solar/Wind Harmer
0.049
3138543CONSLDL
Solar/Wind Harmer
0.047
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3145893MURPHYS
Solar/Wind Harmer
0.118
3145893MURPHYS
Solar/Wind Harmer
0.07
315724AD1-057 GEN
Solar/Wind Harmer
0.264
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.07
957521AF2-046 GEN
Solar/Wind Harmer
5.218
961681AG1-008 GEN
Solar/Wind Harmer
5.218
3145543BTLEBRO
Solar/Wind Harmer
0.07
3145543BTLEBRO
Solar/Wind Harmer
0.07
971623AH1-311 GEN
Solar/Wind Harmer
0.139
3146173TUNIS
Solar/Wind Harmer
0.069
961601AG1-000A GEN
Solar/Wind Harmer
4.894
316463AE2-346 GEN
Solar/Wind Harmer
0.059
316140AB2-099
Solar/Wind Harmer
0.024
962331AG1-082 GEN
Solar/Wind Harmer
0.731
3146073TAR RVR
Solar/Wind Harmer
0.067
3146083TARBORO
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.064
3145746EVERETS
Solar/Wind Harmer
0.064
3156021HOLLOMANSOL
Solar/Wind Harmer
0.29
3145933PARMELE
Solar/Wind Harmer
0.064
966801AG1-551 GEN
Solar/Wind Harmer
0.741
3145963POPLR C
Solar/Wind Harmer
0.062
3146206CASHIE
Solar/Wind Harmer
0.061
315737AD1-076 GEN
Solar/Wind Harmer
0.769
971157AH1-035 GEN
Solar/Wind Harmer
0.714
315614AA2-178 GEN
Solar/Wind Harmer
0.331
3145273HOLLAND
Solar/Wind Harmer
0.043
316313AB2-026
Solar/Wind Helper
0.362
316258AE1-075 C
Solar/Wind Helper
0.326
316405AF2-144 C
Solar/Wind Helper
0.271
3148013FISHERV
Solar/Wind Helper
0.126
3151541CLOVER2
50/50
3.28
3151611KERR 4
50/50
0.314
3151621KERR 5
50/50
0.314
3151631KERR 6
50/50
0.314
3151641KERR 7
50/50
0.314
3151281ROARAP4
50/50
0.107
3151281ROARAP4
50/50
0.1
963041AG1-153 GEN
50/50
2.24
315244AE2-183_ST
50/50
2.342
971845AH1-439 GEN
Solar/Wind Harmer
30.733
970285AG2-188 GEN
Solar/Wind Harmer
51.665
315657AE1-056 GEN
Solar/Wind Harmer
13.38
946301AF1-294 GEN
Solar/Wind Harmer
7.167
961791AG1-021 GEN
Solar/Wind Harmer
3.487
970683AG2-441 GEN
Solar/Wind Harmer
21.847
970681AG2-440 GEN
Solar/Wind Harmer
17.477
3144303KENBRDG
Solar/Wind Harmer
0.232
971443AH1-215 GEN
Solar/Wind Harmer
4.818
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.368
3147173SINAI
Solar/Wind Harmer
0.126
3147243WELCO
Solar/Wind Harmer
0.079
970831AG2-522 GEN
Solar/Wind Harmer
5.363
970865AG2-541 GEN
Solar/Wind Harmer
3.482
971967AH1-528 GEN
Solar/Wind Harmer
15.038
316087AB2-174 GEN
Solar/Wind Harmer
0.003
3137643SOCKMAN
Solar/Wind Harmer
0.358
316123AC1-075 GEN
Solar/Wind Harmer
0.114
970165AG2-112 GEN
Solar/Wind Harmer
0.675
970163AG2-111 GEN
Solar/Wind Harmer
0.644
315607AA1-063A GEN
Solar/Wind Harmer
0.167
970085AG2-068 GEN
Solar/Wind Harmer
4.35
970581AG2-369 GEN
Solar/Wind Harmer
3.741
3146043SEABORD
Solar/Wind Harmer
0.081
970673AG2-436 GEN
Solar/Wind Harmer
17.164
970673AG2-436 GEN
Solar/Wind Harmer
11.442
941031AE2-094 GEN
Solar/Wind Harmer
14.261
944011AF1-069 GEN
Solar/Wind Harmer
4.66
315652AC1-086 GEN
Solar/Wind Harmer
8.006
3146033SCOT NK
Solar/Wind Harmer
0.29
3145796HORNRTN
Solar/Wind Harmer
0.231
3145796HORNRTN
Solar/Wind Harmer
0.029
965291AG1-394 GEN
Solar/Wind Harmer
0.319
316319Z2-044 C
Solar/Wind Harmer
0
3145893MURPHYS
Solar/Wind Harmer
0.19
3145893MURPHYS
Solar/Wind Harmer
0.07
3145513AHOSKIE
Solar/Wind Harmer
0.143
3145513AHOSKIE
Solar/Wind Harmer
0.068
3145683EARLEYS
Solar/Wind Harmer
0.136
3145683EARLEYS
Solar/Wind Harmer
0.068
3145683EARLEYS
Solar/Wind Harmer
0.068
3145573BETHELC
Solar/Wind Harmer
0.067
3145573BETHELC
Solar/Wind Harmer
0.067
316420AA1-050 GEN
Solar/Wind Harmer
0.002
957861AF2-080 GEN
Solar/Wind Harmer
2.845
316005AA1-067
Solar/Wind Harmer
0.069
3145746EVERETS
Solar/Wind Harmer
0.257
3145746EVERETS
Solar/Wind Harmer
0.064
3145746EVERETS
Solar/Wind Harmer
0.064
3145746EVERETS
Solar/Wind Harmer
0.064
970181AG2-120 GEN
Solar/Wind Harmer
0.803
315814AE2-033 C
Solar/Wind Harmer
4.928
316315AB2-025 C
Solar/Wind Harmer
0.05
3146206CASHIE
Solar/Wind Harmer
0.061
970601AG2-382 GEN
Solar/Wind Harmer
2.295
315732AD1-074 GEN1
Solar/Wind Harmer
0.344
315733AD1-074 GEN2
Solar/Wind Harmer
0.344
315735AD1-075 GEN1
Solar/Wind Harmer
0.172
3130546PLYMOUTH
Solar/Wind Harmer
0.059
315816AE2-034 GEN
Solar/Wind Harmer
0.248
270494AE1-108_GEN
Solar/Wind Helper
4.456
3138266HYDRAULIC
Solar/Wind Helper
0.009
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.076
3148013FISHERV
Solar/Wind Helper
0.072
3144293JTRSVLE
50/50
1.227
3151531CLOVER1
50/50
3.295
3151601KERR 3
50/50
0.314
3151581KERR 1
50/50
0.112
3147043LAWRENC
50/50
1.231
3151261ROARAP2
50/50
0.11
3151051BRUNSWICKS1
50/50
2.296
3151021BRUNSWICKG1
50/50
1.106
971451AH1-221 GEN
50/50
3.36
315243AE2-183_GT3
50/50
1.355
3151391GASTONA
50/50
0.197
3151411GASTONB
50/50
0.197
316322AB2-045
Solar/Wind Harmer
0.006
3146776BUCKING
Solar/Wind Harmer
0.276
3146926FARMVIL
Solar/Wind Harmer
0.322
963171AG1-166 GEN
Solar/Wind Harmer
1.937
971563AH1-280 GEN
Solar/Wind Harmer
3.874
970685AG2-442 GEN
Solar/Wind Harmer
24.468
962491AG1-098 GEN
Solar/Wind Harmer
11.913
316237AB2-079_GEN
Solar/Wind Harmer
0.002
315693AD1-088 GEN
Solar/Wind Harmer
9.538
970401AG2-262 GEN
Solar/Wind Harmer
0.936
957481AF2-042 GEN
Solar/Wind Harmer
40.345
315687AD1-152 GEN
Solar/Wind Harmer
0.005
971065AG2-659 GEN
Solar/Wind Harmer
5.693
316129AC1-054 GEN
Solar/Wind Harmer
0.488
971795AH1-408 GEN
Solar/Wind Harmer
7.841
316003AC1-222 GEN
Solar/Wind Harmer
0.003
960081AF2-299 GEN
Solar/Wind Harmer
0.907
3145783HORNRTN
Solar/Wind Harmer
0.086
316190AA2-174 GEN
Solar/Wind Harmer
0
970919AG2-571 GEN
Solar/Wind Harmer
2.909
970087AG2-069 GEN
Solar/Wind Harmer
6.525
316212AC1-099_GEN
Solar/Wind Harmer
0.386
3146263WOODLND
Solar/Wind Harmer
0.073
316011AB1-132 GEN
Solar/Wind Harmer
1.323
316023GEN1_S
Solar/Wind Harmer
0.163
962571AG1-106 GEN
Solar/Wind Harmer
1.036
3145796HORNRTN
Solar/Wind Harmer
0.238
3145796HORNRTN
Solar/Wind Harmer
0.072
3146233WITAKRS
Solar/Wind Harmer
0.285
3145893MURPHYS
Solar/Wind Harmer
0.282
3145893MURPHYS
Solar/Wind Harmer
0.313
315722AD1-056 GEN
Solar/Wind Harmer
0.446
3145823KELFORD
Solar/Wind Harmer
0.07
3145543BTLEBRO
Solar/Wind Harmer
0.07
3145543BTLEBRO
Solar/Wind Harmer
0.056
316359AB2-059 GEN
Solar/Wind Harmer
0.25
316049AB1-081 GEN
Solar/Wind Harmer
0.399
3142053HEARTS
Solar/Wind Harmer
0.123
3146173TUNIS
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.068
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.067
3145493TOT1
Solar/Wind Harmer
0.299
940641AE2-051 GEN
Solar/Wind Harmer
5.379
316494AC1-189 GEN
Solar/Wind Harmer
0.223
3145746EVERETS
Solar/Wind Harmer
0.064
3145746EVERETS
Solar/Wind Harmer
0.064
3146293MARTNCO
Solar/Wind Harmer
0.059
939411AE1-173 GEN
Solar/Wind Harmer
26.834
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3145963POPLR C
Solar/Wind Harmer
0.062
3146206CASHIE
Solar/Wind Harmer
0.061
971547AH1-271 GEN
Solar/Wind Harmer
1.311
3145663CRESWEL
Solar/Wind Harmer
0.162
971163AH1-040 GEN
Solar/Wind Harmer
4.625
316336AC2-165 C
Solar/Wind Helper
1.515
LAGNLTFEXP_LAGN->PJM
CLTF
2.721
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.095
TVALTFEXP_TVA->PJM
CLTF
1.342
CPLELTFEXP_CPLE->PJM
CLTF
4.932
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.368
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.244
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.478
MECLTFEXP_MEC->PJM
CLTF
1.093
SIGELTFEXP_SIGE->PJM
CLTF
0.031
NYPJM->LTFIMP_NY
CLTF
0.491
LGEELTFEXP_LGEE->PJM
CLTF
0.351
WECLTFEXP_WEC->PJM
CLTF
0.183

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.79 %
Rating:571.52 MVA
Rating Type:A
MVA to Mitigate:644.61
MW Contribution:2.31
Bus #Bus NameTypeMW Contribution
3151611KERR 4
50/50
0.278
3151621KERR 5
50/50
0.278
3151631KERR 6
50/50
0.278
3151641KERR 7
50/50
0.278
3151541CLOVER2
50/50
2.843
3151281ROARAP4
50/50
0.085
3151281ROARAP4
50/50
0.079
963041AG1-153 GEN
50/50
1.544
971845AH1-439 GEN
Solar/Wind Harmer
30.475
970285AG2-188 GEN
Solar/Wind Harmer
51.158
315657AE1-056 GEN
Solar/Wind Harmer
12.943
946301AF1-294 GEN
Solar/Wind Harmer
6.907
961791AG1-021 GEN
Solar/Wind Harmer
3.36
970683AG2-441 GEN
Solar/Wind Harmer
20.922
970681AG2-440 GEN
Solar/Wind Harmer
16.737
3144303KENBRDG
Solar/Wind Harmer
0.22
971443AH1-215 GEN
Solar/Wind Harmer
4.571
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.326
3144293JTRSVLE
50/50
1.182
3151591KERR 2
50/50
0.278
970413AG2-270 GEN
50/50
12.466
3151261ROARAP2
50/50
0.085
3151031BRUNSWICKG2
50/50
0.762
3146776BUCKING
Solar/Wind Harmer
0.247
3146926FARMVIL
Solar/Wind Harmer
0.316
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
4.043
3147133PAMPLIN
Solar/Wind Harmer
1.178
971193AH1-056 GEN
Solar/Wind Harmer
22.85
963181AG1-167 GEN
Solar/Wind Harmer
1.4
959311AF2-222 GEN
Solar/Wind Harmer
25.461
970257AG2-171 GEN
Solar/Wind Harmer
8.812
315785AD2-033 C
Solar/Wind Harmer
2.115
964241AG1-285 GEN
Solar/Wind Harmer
14.651
316131AB2-060 GEN
Solar/Wind Harmer
0.614
316478AD1-087 GEN
Solar/Wind Harmer
0.465
316486AD2-202 GEN
Solar/Wind Harmer
0.137
3147043LAWRENC
Solar/Wind Harmer
0.066
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
4.699
971683AH1-343 GEN
Solar/Wind Harmer
3.468
313506AB2-031 GEN
Solar/Wind Harmer
0.226
316283AC2-100 C
Solar/Wind Harmer
0.132
316210AC1-098 GEN
Solar/Wind Harmer
0.53
970917AG2-570 GEN
Solar/Wind Harmer
5.054
316327AA2-057 GEN
Solar/Wind Harmer
0.085
316313AB2-026
Solar/Wind Helper
0.339
316258AE1-075 C
Solar/Wind Helper
0.305
316405AF2-144 C
Solar/Wind Helper
0.254
3148013FISHERV
Solar/Wind Helper
0.124
3144293JTRSVLE
50/50
1.182
3151601KERR 3
50/50
0.278
3151581KERR 1
50/50
0.099
3151531CLOVER1
50/50
2.857
3147043LAWRENC
50/50
1.061
3151261ROARAP2
50/50
0.087
3151051BRUNSWICKS1
50/50
1.582
3151021BRUNSWICKG1
50/50
0.762
971451AH1-221 GEN
50/50
2.315
316322AB2-045
Solar/Wind Harmer
0.005
3146776BUCKING
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Harmer
0.316
963171AG1-166 GEN
Solar/Wind Harmer
1.867
971563AH1-280 GEN
Solar/Wind Harmer
3.734
970685AG2-442 GEN
Solar/Wind Harmer
23.432
962491AG1-098 GEN
Solar/Wind Harmer
10.785
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
8.574
970401AG2-262 GEN
Solar/Wind Harmer
0.841
957481AF2-042 GEN
Solar/Wind Harmer
34.537
315687AD1-152 GEN
Solar/Wind Harmer
0.004
971065AG2-659 GEN
Solar/Wind Harmer
4.943
316129AC1-054 GEN
Solar/Wind Harmer
0.422
316003AC1-222 GEN
Solar/Wind Harmer
0.003
971795AH1-408 GEN
Solar/Wind Harmer
6.643
960081AF2-299 GEN
Solar/Wind Harmer
0.73
3145783HORNRTN
Solar/Wind Harmer
0.068
316190AA2-174 GEN
Solar/Wind Harmer
0
316212AC1-099_GEN
Solar/Wind Harmer
0.295
970919AG2-571 GEN
Solar/Wind Harmer
2.021
970087AG2-069 GEN
Solar/Wind Harmer
4.539
316336AC2-165 C
Solar/Wind Helper
1.447
3144293JTRSVLE
50/50
1.182
3144293JTRSVLE
50/50
0.996
970535AG2-341 GEN
50/50
2.848
3152661PLYWOOD A
50/50
0.269
3151041BRUNSWICKG3
50/50
0.762
972187AH1-678 GEN
50/50
1.749
3146776BUCKING
Solar/Wind Harmer
2.741
3146776BUCKING
Solar/Wind Harmer
0.222
970301AG2-198 GEN
Solar/Wind Harmer
16.173
3147133PAMPLIN
Solar/Wind Harmer
0.375
3147133PAMPLIN
Solar/Wind Harmer
0.3
958211AF2-115 GEN
Solar/Wind Harmer
4.2
963191AG1-168 GEN
Solar/Wind Harmer
1.4
971741AH1-377 GEN
Solar/Wind Harmer
33.04
316034AC1-036 C
Solar/Wind Harmer
0.02
970323AG2-213 GEN
Solar/Wind Harmer
11.75
971775AH1-396 GEN
Solar/Wind Harmer
0.441
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
7.214
939181AE1-148 GEN
Solar/Wind Harmer
6.93
964791AG1-342 GEN
Solar/Wind Harmer
2.751
3146843MT LREL
Solar/Wind Harmer
0.143
3146843MT LREL
Solar/Wind Harmer
0.143
970099AG2-077 GEN
Solar/Wind Harmer
13.815
970933AG2-581 GEN
Solar/Wind Harmer
6.948
316181AB2-040 GEN
Solar/Wind Harmer
0.106
3145593CAROLNA
Solar/Wind Harmer
0.07
3145593CAROLNA
Solar/Wind Harmer
0.07
966811AG1-552 GEN
Solar/Wind Harmer
0.761
3145593CAROLNA
Solar/Wind Harmer
0.087
3145783HORNRTN
Solar/Wind Harmer
1.218
3145783HORNRTN
Solar/Wind Harmer
0.974
3145783HORNRTN
Solar/Wind Harmer
0.304
3145783HORNRTN
Solar/Wind Harmer
0.122
316222AC1-221 GEN
Solar/Wind Harmer
0.283
316426AA2-053 GEN
Solar/Wind Harmer
0.225
942751AE2-291 GEN
Solar/Wind Harmer
3.327
316274AC1-208 GEN
Solar/Wind Harmer
0.31
315821AE2-092 GEN
Solar/Wind Helper
2.982
3147173SINAI
Solar/Wind Harmer
0.11
3147243WELCO
Solar/Wind Harmer
0.069
970831AG2-522 GEN
Solar/Wind Harmer
4.61
970865AG2-541 GEN
Solar/Wind Harmer
3.002
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.286
316123AC1-075 GEN
Solar/Wind Harmer
0.097
970165AG2-112 GEN
Solar/Wind Harmer
0.576
970163AG2-111 GEN
Solar/Wind Harmer
0.549
971967AH1-528 GEN
Solar/Wind Harmer
10.852
315607AA1-063A GEN
Solar/Wind Harmer
0.13
3146043SEABORD
Solar/Wind Harmer
0.063
970085AG2-068 GEN
Solar/Wind Harmer
3.026
970581AG2-369 GEN
Solar/Wind Harmer
2.602
270494AE1-108_GEN
Solar/Wind Helper
4.482
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
LAGNLTFEXP_LAGN->PJM
CLTF
1.944
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.608
TVALTFEXP_TVA->PJM
CLTF
0.955
CPLELTFEXP_CPLE->PJM
CLTF
3.771
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.922
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.157
MECLTFEXP_MEC->PJM
CLTF
0.729
SIGELTFEXP_SIGE->PJM
CLTF
0.02
NYPJM->LTFIMP_NY
CLTF
0.308
LGEELTFEXP_LGEE->PJM
CLTF
0.221
WECLTFEXP_WEC->PJM
CLTF
0.117

Details for 6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:154.83 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1864.16
MW Contribution:5.99
Bus #Bus NameTypeMW Contribution
315779AE2-040
50/50
3.378
315244AE2-183_ST
50/50
4.349
963041AG1-153 GEN
50/50
3.994
3151541CLOVER2
50/50
2.544
3151281ROARAP4
50/50
0.144
3151281ROARAP4
50/50
0.134
316315AB2-025 C
Solar/Wind Harmer
0.734
315814AE2-033 C
Solar/Wind Harmer
24.939
941031AE2-094 GEN
Solar/Wind Harmer
33.281
944011AF1-069 GEN
Solar/Wind Harmer
10.428
970673AG2-436 GEN
Solar/Wind Harmer
36.399
970673AG2-436 GEN
Solar/Wind Harmer
18.43
946281AF1-292 GEN
Solar/Wind Harmer
0.383
971967AH1-528 GEN
Solar/Wind Harmer
31.705
970085AG2-068 GEN
Solar/Wind Harmer
10.008
970581AG2-369 GEN
Solar/Wind Harmer
8.607
316087AB2-174 GEN
Solar/Wind Harmer
2.265
315652AC1-086 GEN
Solar/Wind Harmer
17.05
3145796HORNRTN
Solar/Wind Harmer
-0.047
3145796HORNRTN
Solar/Wind Harmer
-0.006
3137643SOCKMAN
Solar/Wind Harmer
-0.057
970831AG2-522 GEN
Solar/Wind Harmer
6.31
315607AA1-063A GEN
Solar/Wind Harmer
1.207
316319Z2-044 C
Solar/Wind Harmer
0.657
3146043SEABORD
Solar/Wind Harmer
-0.012
316239AB2-077_GEN
Solar/Wind Harmer
0.35
316238AB2-078_GEN
Solar/Wind Harmer
0.35
3146033SCOT NK
Solar/Wind Harmer
-0.045
3145573BETHELC
Solar/Wind Harmer
-0.011
3145573BETHELC
Solar/Wind Harmer
-0.011
316420AA1-050 GEN
Solar/Wind Harmer
1.267
316118AC1-105 GEN
Solar/Wind Harmer
0.759
3147173SINAI
Solar/Wind Harmer
-0.011
3147243WELCO
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
4.731
971443AH1-215 GEN
Solar/Wind Harmer
2.043
3145683EARLEYS
Solar/Wind Harmer
-0.021
3145683EARLEYS
Solar/Wind Harmer
-0.01
3145683EARLEYS
Solar/Wind Harmer
-0.01
3144303KENBRDG
Solar/Wind Harmer
-0.008
3145513AHOSKIE
Solar/Wind Harmer
0.089
961941AG1-037 GEN
Solar/Wind Harmer
0.077
3145513AHOSKIE
Solar/Wind Harmer
-0.01
316005AA1-067
Solar/Wind Harmer
0.207
3145746EVERETS
Solar/Wind Harmer
-0.041
3145746EVERETS
Solar/Wind Harmer
-0.01
3145746EVERETS
Solar/Wind Harmer
-0.01
3145746EVERETS
Solar/Wind Harmer
-0.01
970181AG2-120 GEN
Solar/Wind Harmer
1.344
316318V4-068
Solar/Wind Harmer
0.249
3145893MURPHYS
Solar/Wind Harmer
-0.027
3145893MURPHYS
Solar/Wind Harmer
-0.01
965291AG1-394 GEN
Solar/Wind Harmer
0.871
970683AG2-441 GEN
Solar/Wind Harmer
7.621
970681AG2-440 GEN
Solar/Wind Harmer
6.097
3143316POE
Solar/Wind Harmer
-0.038
970865AG2-541 GEN
Solar/Wind Harmer
3.743
946301AF1-294 GEN
Solar/Wind Harmer
2.361
961791AG1-021 GEN
Solar/Wind Harmer
1.152
315657AE1-056 GEN
Solar/Wind Harmer
3.313
3146206CASHIE
Solar/Wind Harmer
-0.009
970601AG2-382 GEN
Solar/Wind Harmer
3.864
270455AD2-022 GEN
Solar/Wind Harmer
1.529
270457AD2-023 GEN
Solar/Wind Harmer
0.775
315732AD1-074 GEN1
Solar/Wind Harmer
1.65
315733AD1-074 GEN2
Solar/Wind Harmer
1.65
315735AD1-075 GEN1
Solar/Wind Harmer
0.825
316123AC1-075 GEN
Solar/Wind Harmer
0.874
970165AG2-112 GEN
Solar/Wind Harmer
0.77
970163AG2-111 GEN
Solar/Wind Harmer
0.734
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315816AE2-034 GEN
Solar/Wind Harmer
0.593
3130156CHOWAN
Solar/Wind Harmer
-0.006
3130156CHOWAN
Solar/Wind Harmer
-0.006
316132AB2-190 GEN1
Solar/Wind Helper
0.976
316233AE1-074 FULL
Solar/Wind Helper
0.226
316312AB1-027
Solar/Wind Helper
0.27
3143873LANEXA
Solar/Wind Helper
0.076
316369SG1_INVT
Solar/Wind Helper
0.602
3151031BRUNSWICKG2
50/50
1.972
3151391GASTONA
50/50
0.365
3151411GASTONB
50/50
0.365
970413AG2-270 GEN
50/50
11.155
3151261ROARAP2
50/50
0.144
316365GEN2_N
Solar/Wind Harmer
1.302
966621AG1-532 GEN
Solar/Wind Harmer
0.347
970917AG2-570 GEN
Solar/Wind Harmer
40.235
3147043LAWRENC
Solar/Wind Harmer
-0.009
313506AB2-031 GEN
Solar/Wind Harmer
1.233
3145796HORNRTN
Solar/Wind Harmer
-0.058
3145796HORNRTN
Solar/Wind Harmer
-0.015
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
316478AD1-087 GEN
Solar/Wind Harmer
1.161
316486AD2-202 GEN
Solar/Wind Harmer
0.34
315724AD1-057 GEN
Solar/Wind Harmer
0.758
316327AA2-057 GEN
Solar/Wind Harmer
1.21
961601AG1-000A GEN
Solar/Wind Harmer
4.742
3146233WITAKRS
Solar/Wind Harmer
0.249
3146233WITAKRS
Solar/Wind Harmer
-0.008
3138543CONSLDL
Solar/Wind Harmer
-0.008
3145543BTLEBRO
Solar/Wind Harmer
-0.012
3145543BTLEBRO
Solar/Wind Harmer
-0.012
316210AC1-098 GEN
Solar/Wind Harmer
1.85
316131AB2-060 GEN
Solar/Wind Harmer
1.244
3146073TAR RVR
Solar/Wind Harmer
-0.011
3146083TARBORO
Solar/Wind Harmer
-0.011
964241AG1-285 GEN
Solar/Wind Harmer
8.72
3146263WOODLND
Solar/Wind Harmer
-0.011
316248AF1-058 C
Solar/Wind Harmer
0.328
960061AF2-297 GEN
Solar/Wind Harmer
5.444
316317KELFORD C
Solar/Wind Harmer
0.511
3145823KELFORD
Solar/Wind Harmer
-0.011
315785AD2-033 C
Solar/Wind Harmer
2.392
970257AG2-171 GEN
Solar/Wind Harmer
3.873
316463AE2-346 GEN
Solar/Wind Harmer
0.166
316140AB2-099
Solar/Wind Harmer
0.069
962331AG1-082 GEN
Solar/Wind Harmer
1.281
3145746EVERETS
Solar/Wind Harmer
-0.01
3145746EVERETS
Solar/Wind Harmer
-0.01
959311AF2-222 GEN
Solar/Wind Harmer
10.609
3146173TUNIS
Solar/Wind Harmer
-0.01
957521AF2-046 GEN
Solar/Wind Harmer
7.902
961681AG1-008 GEN
Solar/Wind Harmer
7.902
316283AC2-100 C
Solar/Wind Harmer
0.942
3145893MURPHYS
Solar/Wind Harmer
0.07
3145893MURPHYS
Solar/Wind Harmer
-0.01
3145933PARMELE
Solar/Wind Harmer
-0.01
966801AG1-551 GEN
Solar/Wind Harmer
1.233
3156021HOLLOMANSOL
Solar/Wind Harmer
1.319
971683AH1-343 GEN
Solar/Wind Harmer
4.208
3156081AA2-088 GEN
Solar/Wind Harmer
3.105
970909AG2-566 GEN
Solar/Wind Harmer
0.889
963181AG1-167 GEN
Solar/Wind Harmer
0.864
3144293JTRSVLE
Adder
0.261
3145963POPLR C
Solar/Wind Harmer
-0.009
3147133PAMPLIN
Solar/Wind Harmer
-0.028
971193AH1-056 GEN
Solar/Wind Harmer
5.522
3146206CASHIE
Solar/Wind Harmer
-0.009
315737AD1-076 GEN
Solar/Wind Harmer
1.551
971157AH1-035 GEN
Solar/Wind Harmer
1.003
942461AE2-259 GEN
Solar/Wind Harmer
1.167
315614AA2-178 GEN
Solar/Wind Harmer
0.791
3146926FARMVIL
Solar/Wind Harmer
-0.004
3146376EDENTON
Solar/Wind Harmer
-0.006
315839AE2-212 C
Solar/Wind Helper
0.966
3142946ENON
Solar/Wind Helper
0.055
316473AC1-191 GEN
Solar/Wind Helper
1
315243AE2-183_GT3
50/50
2.516
3151051BRUNSWICKS1
50/50
4.094
3151021BRUNSWICKG1
50/50
1.972
971451AH1-221 GEN
50/50
5.991
3147043LAWRENC
50/50
1.32
3151391GASTONA
50/50
0.365
3151411GASTONB
50/50
0.365
3151531CLOVER1
50/50
2.556
3151261ROARAP2
50/50
0.148
316023GEN1_S
Solar/Wind Harmer
1.302
960081AF2-299 GEN
Solar/Wind Harmer
1.926
970919AG2-571 GEN
Solar/Wind Harmer
5.093
970087AG2-069 GEN
Solar/Wind Harmer
15.012
971795AH1-408 GEN
Solar/Wind Harmer
11.982
316011AB1-132 GEN
Solar/Wind Harmer
3.171
962571AG1-106 GEN
Solar/Wind Harmer
2.179
3145796HORNRTN
Solar/Wind Harmer
-0.048
3145796HORNRTN
Solar/Wind Harmer
-0.015
957481AF2-042 GEN
Solar/Wind Harmer
44.356
315722AD1-056 GEN
Solar/Wind Harmer
1.378
3145783HORNRTN
Solar/Wind Harmer
-0.013
315693AD1-088 GEN
Solar/Wind Harmer
6.574
939411AE1-173 GEN
Solar/Wind Harmer
65.115
962491AG1-098 GEN
Solar/Wind Harmer
8.662
316190AA2-174 GEN
Solar/Wind Harmer
0.157
316129AC1-054 GEN
Solar/Wind Harmer
1.1
315687AD1-152 GEN
Solar/Wind Harmer
1.509
971065AG2-659 GEN
Solar/Wind Harmer
6.236
3146233WITAKRS
Solar/Wind Harmer
-0.047
316359AB2-059 GEN
Solar/Wind Harmer
1.597
316049AB1-081 GEN
Solar/Wind Harmer
1.278
3142053HEARTS
Solar/Wind Harmer
0.139
3145543BTLEBRO
Solar/Wind Harmer
-0.012
3145543BTLEBRO
Solar/Wind Harmer
-0.009
316212AC1-099_GEN
Solar/Wind Harmer
1.028
316237AB2-079_GEN
Solar/Wind Harmer
0.35
961671AG1-007 GEN
Solar/Wind Harmer
0.143
3146083TARBORO
Solar/Wind Harmer
-0.011
3145493TOT1
Solar/Wind Harmer
0.335
970401AG2-262 GEN
Solar/Wind Harmer
0.731
3146263WOODLND
Solar/Wind Harmer
-0.011
3145823KELFORD
Solar/Wind Harmer
-0.011
316494AC1-189 GEN
Solar/Wind Harmer
1.164
3145683EARLEYS
Solar/Wind Harmer
-0.01
316003AC1-222 GEN
Solar/Wind Harmer
1.004
3145746EVERETS
Solar/Wind Harmer
-0.01
3145746EVERETS
Solar/Wind Harmer
-0.01
3146173TUNIS
Solar/Wind Harmer
-0.01
3145893MURPHYS
Solar/Wind Harmer
-0.04
3145893MURPHYS
Solar/Wind Harmer
0.296
3146293MARTNCO
Solar/Wind Harmer
0.061
970685AG2-442 GEN
Solar/Wind Harmer
8.535
316174AB2-169 GEN
Solar/Wind Harmer
1.424
963171AG1-166 GEN
Solar/Wind Harmer
1.152
971563AH1-280 GEN
Solar/Wind Harmer
1.152
3144293JTRSVLE
Adder
0.261
3145963POPLR C
Solar/Wind Harmer
-0.009
3146206CASHIE
Solar/Wind Harmer
-0.009
971547AH1-271 GEN
Solar/Wind Harmer
2.208
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.873
3146926FARMVIL
Solar/Wind Harmer
-0.004
3130156CHOWAN
Solar/Wind Harmer
-0.006
3142543TWELFTH
Solar/Wind Helper
0.024
3142433PROV 92
Solar/Wind Helper
0.7
316458AB2-190 GEN2
Solar/Wind Helper
0.976
3143526WINTERP
Solar/Wind Helper
0.769
3142416OLDCHRC
Solar/Wind Helper
0.369
3142416OLDCHRC
Solar/Wind Helper
0.141
3143226MDLTHAN
Solar/Wind Helper
0.133
970533AG2-339 GEN
50/50
14.043
970531AG2-338 GEN
50/50
5.617
315242AE2-183_GT2
50/50
2.516
315241AE2-183_GT1
50/50
2.5
972185AH1-677 GEN
50/50
9.069
3151041BRUNSWICKG3
50/50
1.972
972187AH1-678 GEN
50/50
4.526
3151361ROSEMG1
50/50
0.471
3151371ROSEMS1
50/50
0.292
3151381ROSEMG2
50/50
0.22
3144356SAPONY
Solar/Wind Harmer
0.948
970933AG2-581 GEN
Solar/Wind Harmer
15.092
316181AB2-040 GEN
Solar/Wind Harmer
2.139
3145796HORNRTN
Solar/Wind Harmer
-0.044
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
970099AG2-077 GEN
Solar/Wind Harmer
17.742
3145593CAROLNA
Solar/Wind Harmer
-0.013
3145593CAROLNA
Solar/Wind Harmer
-0.013
966811AG1-552 GEN
Solar/Wind Harmer
1.5
3145593CAROLNA
Solar/Wind Harmer
0.111
3145783HORNRTN
Solar/Wind Harmer
1.561
3145783HORNRTN
Solar/Wind Harmer
1.249
3145783HORNRTN
Solar/Wind Harmer
0.39
3145783HORNRTN
Solar/Wind Harmer
0.156
316426AA2-053 GEN
Solar/Wind Harmer
1.293
316274AC1-208 GEN
Solar/Wind Harmer
1.319
939181AE1-148 GEN
Solar/Wind Harmer
6.767
961601AG1-000A GEN
Solar/Wind Harmer
4.682
316263AC1-034 GEN
Solar/Wind Harmer
5.552
313527AB2-043 GEN
Solar/Wind Harmer
1.888
3145493TOT1
Solar/Wind Harmer
0.175
3145453TOT5
Solar/Wind Harmer
0.105
3145603CNETO
Solar/Wind Harmer
0.07
962561AG1-105 GEN
Solar/Wind Harmer
6.333
964791AG1-342 GEN
Solar/Wind Harmer
2.391
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970323AG2-213 GEN
Solar/Wind Harmer
5.164
971775AH1-396 GEN
Solar/Wind Harmer
0.735
316034AC1-036 C
Solar/Wind Harmer
0.191
971741AH1-377 GEN
Solar/Wind Harmer
11.893
3146173TUNIS
Solar/Wind Harmer
-0.01
3146173TUNIS
Solar/Wind Harmer
-0.01
316222AC1-221 GEN
Solar/Wind Harmer
1.018
3145893MURPHYS
Solar/Wind Harmer
0.278
3145893MURPHYS
Solar/Wind Harmer
-0.018
3145933PARMELE
Solar/Wind Harmer
-0.02
3145933PARMELE
Solar/Wind Harmer
-0.01
970301AG2-198 GEN
Solar/Wind Harmer
4.681
958211AF2-115 GEN
Solar/Wind Harmer
1.439
963191AG1-168 GEN
Solar/Wind Harmer
0.864
3144293JTRSVLE
Adder
0.261
3144293JTRSVLE
Adder
0.22
3147133PAMPLIN
Solar/Wind Harmer
-0.009
3147133PAMPLIN
Solar/Wind Harmer
-0.007
316065AD1-022 GEN
Solar/Wind Harmer
4.293
942751AE2-291 GEN
Solar/Wind Harmer
4.718
315742AE1-103 GEN
Solar/Wind Harmer
0.706
3146376EDENTON
Solar/Wind Harmer
0.191
3146376EDENTON
Solar/Wind Harmer
0.191
316240AF1-291 C
Solar/Wind Helper
0.402
3142946ENON
Solar/Wind Helper
0.017
966871AG1-558 GEN
Solar/Wind Helper
0.221
3143526WINTERP
Solar/Wind Helper
0.769
316468AD1-105 GEN
Solar/Wind Helper
0.714
316075AC2-137 C
Solar/Wind Helper
0.21
316033AB2-134 GEN
Solar/Wind Helper
0.43
315697AD1-025 GEN
Solar/Wind Helper
1.43
LAGNLTFEXP_LAGN->PJM
CLTF
4.648
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.569
TVALTFEXP_TVA->PJM
CLTF
2.315
CPLELTFEXP_CPLE->PJM
CLTF
6.792
CBM West 2LTFEXP_CBM-W2->PJM
CBM
24.55
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.091
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.934
MECLTFEXP_MEC->PJM
CLTF
2.276
SIGELTFEXP_SIGE->PJM
CLTF
0.068
NYPJM->LTFIMP_NY
CLTF
0.817
LGEELTFEXP_LGEE->PJM
CLTF
0.818
WECLTFEXP_WEC->PJM
CLTF
0.427

Details for 6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:145.18 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1428.84
MW Contribution:4.66
Bus #Bus NameTypeMW Contribution
315779AE2-040
50/50
3.099
315244AE2-183_ST
50/50
3.382
963041AG1-153 GEN
50/50
3.109
3151281ROARAP4
50/50
0.132
3151281ROARAP4
50/50
0.123
3151541CLOVER2
50/50
2.008
3151611KERR 4
50/50
0.187
3151621KERR 5
50/50
0.187
3151631KERR 6
50/50
0.187
3151641KERR 7
50/50
0.187
316315AB2-025 C
Solar/Wind Harmer
0.179
315814AE2-033 C
Solar/Wind Harmer
17.298
316087AB2-174 GEN
Solar/Wind Harmer
0.004
315652AC1-086 GEN
Solar/Wind Harmer
13.694
941031AE2-094 GEN
Solar/Wind Harmer
22.572
944011AF1-069 GEN
Solar/Wind Harmer
7.375
3145796HORNRTN
Solar/Wind Harmer
0.385
3145796HORNRTN
Solar/Wind Harmer
0.048
970673AG2-436 GEN
Solar/Wind Harmer
25.561
970673AG2-436 GEN
Solar/Wind Harmer
17.041
971967AH1-528 GEN
Solar/Wind Harmer
18.68
3137643SOCKMAN
Solar/Wind Harmer
0.464
970085AG2-068 GEN
Solar/Wind Harmer
5.942
970581AG2-369 GEN
Solar/Wind Harmer
5.11
315607AA1-063A GEN
Solar/Wind Harmer
0.204
3146043SEABORD
Solar/Wind Harmer
0.098
970831AG2-522 GEN
Solar/Wind Harmer
4.182
316319Z2-044 C
Solar/Wind Harmer
0
3146033SCOT NK
Solar/Wind Harmer
0.379
3145573BETHELC
Solar/Wind Harmer
0.092
3145573BETHELC
Solar/Wind Harmer
0.092
316420AA1-050 GEN
Solar/Wind Harmer
0.003
3151391GASTONA
50/50
0.337
3151411GASTONB
50/50
0.337
3147043LAWRENC
50/50
1.178
315243AE2-183_GT3
50/50
1.956
3151051BRUNSWICKS1
50/50
3.187
3151021BRUNSWICKG1
50/50
1.536
971451AH1-221 GEN
50/50
4.664
3151261ROARAP2
50/50
0.136
3151531CLOVER1
50/50
2.018
3151601KERR 3
50/50
0.187
3151581KERR 1
50/50
0.067
316023GEN1_S
Solar/Wind Harmer
0.354
960081AF2-299 GEN
Solar/Wind Harmer
1.332
971795AH1-408 GEN
Solar/Wind Harmer
8.516
316011AB1-132 GEN
Solar/Wind Harmer
2.263
962571AG1-106 GEN
Solar/Wind Harmer
1.771
3145796HORNRTN
Solar/Wind Harmer
0.397
3145796HORNRTN
Solar/Wind Harmer
0.12
940641AE2-051 GEN
Solar/Wind Harmer
9.263
970919AG2-571 GEN
Solar/Wind Harmer
3.98
970087AG2-069 GEN
Solar/Wind Harmer
8.913
3145783HORNRTN
Solar/Wind Harmer
0.107
315722AD1-056 GEN
Solar/Wind Harmer
0.674
316190AA2-174 GEN
Solar/Wind Harmer
0
939411AE1-173 GEN
Solar/Wind Harmer
42.901
957481AF2-042 GEN
Solar/Wind Harmer
26.456
316212AC1-099_GEN
Solar/Wind Harmer
0.502
316129AC1-054 GEN
Solar/Wind Harmer
0.364
971065AG2-659 GEN
Solar/Wind Harmer
4.087
3146233WITAKRS
Solar/Wind Harmer
0.38
3146263WOODLND
Solar/Wind Harmer
0.095
316359AB2-059 GEN
Solar/Wind Harmer
0.34
316049AB1-081 GEN
Solar/Wind Harmer
0.541
3142053HEARTS
Solar/Wind Harmer
0.166
3145543BTLEBRO
Solar/Wind Harmer
0.094
3145543BTLEBRO
Solar/Wind Harmer
0.075
3145823KELFORD
Solar/Wind Harmer
0.092
315693AD1-088 GEN
Solar/Wind Harmer
4.418
961671AG1-007 GEN
Solar/Wind Harmer
0.014
3146083TARBORO
Solar/Wind Harmer
0.092
3145493TOT1
Solar/Wind Harmer
0.407
962491AG1-098 GEN
Solar/Wind Harmer
5.172
3145683EARLEYS
Solar/Wind Harmer
0.09
316494AC1-189 GEN
Solar/Wind Harmer
0.3
315687AD1-152 GEN
Solar/Wind Harmer
0.003
3146173TUNIS
Solar/Wind Harmer
0.088
3145893MURPHYS
Solar/Wind Harmer
0.348
3145893MURPHYS
Solar/Wind Harmer
0.387
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3145746EVERETS
Solar/Wind Harmer
0.085
3145746EVERETS
Solar/Wind Harmer
0.085
3146293MARTNCO
Solar/Wind Harmer
0.078
970401AG2-262 GEN
Solar/Wind Harmer
0.478
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3146206CASHIE
Solar/Wind Harmer
0.08
971547AH1-271 GEN
Solar/Wind Harmer
1.719
3145963POPLR C
Solar/Wind Harmer
0.08
316003AC1-222 GEN
Solar/Wind Harmer
0.002
3145663CRESWEL
Solar/Wind Harmer
0.201
971163AH1-040 GEN
Solar/Wind Harmer
5.738
970685AG2-442 GEN
Solar/Wind Harmer
5.289
3130156CHOWAN
Solar/Wind Harmer
0.066
963171AG1-166 GEN
Solar/Wind Harmer
0.354
971563AH1-280 GEN
Solar/Wind Harmer
0.708
3144293JTRSVLE
Adder
0.211
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
316294AC1-161 GEN
Solar/Wind Harmer
1.066
3146516WINFALL
Solar/Wind Harmer
0.194
3146516WINFALL
Solar/Wind Harmer
0.06
944591AF1-124 GEN
Solar/Wind Harmer
12.705
3142543TWELFTH
Solar/Wind Helper
0.024
316458AB2-190 GEN2
Solar/Wind Helper
0.895
3142433PROV 92
Solar/Wind Helper
0.616
3143526WINTERP
Solar/Wind Helper
0.72
3143226MDLTHAN
Solar/Wind Helper
0.125
3142416OLDCHRC
Solar/Wind Helper
0.323
3142416OLDCHRC
Solar/Wind Helper
0.124
970533AG2-339 GEN
50/50
10.894
970531AG2-338 GEN
50/50
4.358
3151361ROSEMG1
50/50
0.433
3151371ROSEMS1
50/50
0.268
3151381ROSEMG2
50/50
0.203
315242AE2-183_GT2
50/50
1.956
315241AE2-183_GT1
50/50
1.944
972185AH1-677 GEN
50/50
7.053
3151041BRUNSWICKG3
50/50
1.536
972187AH1-678 GEN
50/50
3.524
970535AG2-341 GEN
50/50
1.57
3152661PLYWOOD A
50/50
0.18
3144356SAPONY
Solar/Wind Harmer
1.857
316181AB2-040 GEN
Solar/Wind Harmer
0.181
3145796HORNRTN
Solar/Wind Harmer
0.361
3142666NORTHAMPTON
Solar/Wind Harmer
0.119
3142666NORTHAMPTON
Solar/Wind Harmer
0.119
3142666NORTHAMPTON
Solar/Wind Harmer
0.119
3142666NORTHAMPTON
Solar/Wind Harmer
0.072
970933AG2-581 GEN
Solar/Wind Harmer
8.936
3145593CAROLNA
Solar/Wind Harmer
0.109
3145593CAROLNA
Solar/Wind Harmer
0.109
966811AG1-552 GEN
Solar/Wind Harmer
1.182
3145593CAROLNA
Solar/Wind Harmer
0.136
3145783HORNRTN
Solar/Wind Harmer
1.911
3145783HORNRTN
Solar/Wind Harmer
1.529
3145783HORNRTN
Solar/Wind Harmer
0.478
3145783HORNRTN
Solar/Wind Harmer
0.191
316426AA2-053 GEN
Solar/Wind Harmer
0.356
316274AC1-208 GEN
Solar/Wind Harmer
0.518
970099AG2-077 GEN
Solar/Wind Harmer
10.582
961601AG1-000A GEN
Solar/Wind Harmer
1.691
316263AC1-034 GEN
Solar/Wind Harmer
3.592
3145493TOT1
Solar/Wind Harmer
0.212
3145453TOT5
Solar/Wind Harmer
0.127
3145603CNETO
Solar/Wind Harmer
0.085
939181AE1-148 GEN
Solar/Wind Harmer
4.3
3146173TUNIS
Solar/Wind Harmer
0.088
3146173TUNIS
Solar/Wind Harmer
0.088
3145893MURPHYS
Solar/Wind Harmer
0.583
3145893MURPHYS
Solar/Wind Harmer
0.157
313527AB2-043 GEN
Solar/Wind Harmer
0.001
3145933PARMELE
Solar/Wind Harmer
0.168
3145933PARMELE
Solar/Wind Harmer
0.084
962561AG1-105 GEN
Solar/Wind Harmer
3.947
964791AG1-342 GEN
Solar/Wind Harmer
1.566
3146843MT LREL
Solar/Wind Harmer
0.081
3146843MT LREL
Solar/Wind Harmer
0.081
316065AD1-022 GEN
Solar/Wind Harmer
3.64
970323AG2-213 GEN
Solar/Wind Harmer
3.221
3151391GASTONA
50/50
0.337
3151411GASTONB
50/50
0.337
3151031BRUNSWICKG2
50/50
1.536
3151261ROARAP2
50/50
0.133
970413AG2-270 GEN
50/50
8.806
3151591KERR 2
50/50
0.187
316365GEN2_N
Solar/Wind Harmer
0.354
313506AB2-031 GEN
Solar/Wind Harmer
0.385
3147043LAWRENC
Solar/Wind Harmer
0.074
3145796HORNRTN
Solar/Wind Harmer
0.481
3145796HORNRTN
Solar/Wind Harmer
0.12
3142666NORTHAMPTON
Solar/Wind Harmer
0.119
970917AG2-570 GEN
Solar/Wind Harmer
9.95
315724AD1-057 GEN
Solar/Wind Harmer
0.4
316210AC1-098 GEN
Solar/Wind Harmer
0.901
316327AA2-057 GEN
Solar/Wind Harmer
0.146
3146233WITAKRS
Solar/Wind Harmer
0.48
3146233WITAKRS
Solar/Wind Harmer
0.065
3138543CONSLDL
Solar/Wind Harmer
0.063
961601AG1-000A GEN
Solar/Wind Harmer
6.766
3146263WOODLND
Solar/Wind Harmer
0.095
971623AH1-311 GEN
Solar/Wind Harmer
0.189
3145543BTLEBRO
Solar/Wind Harmer
0.094
3145543BTLEBRO
Solar/Wind Harmer
0.094
316478AD1-087 GEN
Solar/Wind Harmer
0.329
316486AD2-202 GEN
Solar/Wind Harmer
0.097
316317KELFORD C
Solar/Wind Harmer
0.009
3145823KELFORD
Solar/Wind Harmer
0.092
3146073TAR RVR
Solar/Wind Harmer
0.092
3146083TARBORO
Solar/Wind Harmer
0.092
316463AE2-346 GEN
Solar/Wind Harmer
0.076
316140AB2-099
Solar/Wind Harmer
0.032
962331AG1-082 GEN
Solar/Wind Harmer
0.95
3146173TUNIS
Solar/Wind Harmer
0.088
957521AF2-046 GEN
Solar/Wind Harmer
6.513
961681AG1-008 GEN
Solar/Wind Harmer
6.513
3145893MURPHYS
Solar/Wind Harmer
0.146
3145893MURPHYS
Solar/Wind Harmer
0.087
3156021HOLLOMANSOL
Solar/Wind Harmer
0.393
3145746EVERETS
Solar/Wind Harmer
0.085
3145746EVERETS
Solar/Wind Harmer
0.085
316131AB2-060 GEN
Solar/Wind Harmer
0.268
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3145933PARMELE
Solar/Wind Harmer
0.084
966801AG1-551 GEN
Solar/Wind Harmer
0.976
964241AG1-285 GEN
Solar/Wind Harmer
5.485
3146206CASHIE
Solar/Wind Harmer
0.08
3145963POPLR C
Solar/Wind Harmer
0.08
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.344
315785AD2-033 C
Solar/Wind Harmer
0.629
315737AD1-076 GEN
Solar/Wind Harmer
0.983
971157AH1-035 GEN
Solar/Wind Harmer
0.908
970257AG2-171 GEN
Solar/Wind Harmer
2.416
959311AF2-222 GEN
Solar/Wind Harmer
6.592
316283AC2-100 C
Solar/Wind Harmer
0.142
315614AA2-178 GEN
Solar/Wind Harmer
0.41
971683AH1-343 GEN
Solar/Wind Harmer
2.584
3146376EDENTON
Solar/Wind Harmer
0.067
963181AG1-167 GEN
Solar/Wind Harmer
0.266
3144293JTRSVLE
Adder
0.211
970909AG2-566 GEN
Solar/Wind Harmer
0.692
3147133PAMPLIN
Solar/Wind Harmer
0.199
971193AH1-056 GEN
Solar/Wind Harmer
3.857
315773AC2-141 GEN
Solar/Wind Harmer
2.248
3146626S HERTFORD
Solar/Wind Harmer
0.061
3145273HOLLAND
Solar/Wind Harmer
0.046
3146516WINFALL
Solar/Wind Harmer
0.06
316435W1029_GEN3
Solar/Wind Harmer
0
316320Y1-086
Solar/Wind Harmer
0
944581AF1-123 GEN
Solar/Wind Harmer
12.66
944601AF1-125 GEN
Solar/Wind Harmer
12.465
315839AE2-212 C
Solar/Wind Helper
0.986
316473AC1-191 GEN
Solar/Wind Helper
0.925
3142946ENON
Solar/Wind Helper
0.049
3145683EARLEYS
Solar/Wind Harmer
0.179
3145683EARLEYS
Solar/Wind Harmer
0.09
3145683EARLEYS
Solar/Wind Harmer
0.09
3145513AHOSKIE
Solar/Wind Harmer
0.186
3145513AHOSKIE
Solar/Wind Harmer
0.089
957861AF2-080 GEN
Solar/Wind Harmer
3.828
3145893MURPHYS
Solar/Wind Harmer
0.235
3145893MURPHYS
Solar/Wind Harmer
0.087
965291AG1-394 GEN
Solar/Wind Harmer
0.382
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316005AA1-067
Solar/Wind Harmer
0.092
3145746EVERETS
Solar/Wind Harmer
0.34
3145746EVERETS
Solar/Wind Harmer
0.085
3145746EVERETS
Solar/Wind Harmer
0.085
3145746EVERETS
Solar/Wind Harmer
0.085
970181AG2-120 GEN
Solar/Wind Harmer
1.064
3146206CASHIE
Solar/Wind Harmer
0.08
970601AG2-382 GEN
Solar/Wind Harmer
3.008
316118AC1-105 GEN
Solar/Wind Harmer
0.206
3147173SINAI
Solar/Wind Harmer
0.078
3147243WELCO
Solar/Wind Harmer
0.049
315732AD1-074 GEN1
Solar/Wind Harmer
0.439
315733AD1-074 GEN2
Solar/Wind Harmer
0.439
315735AD1-075 GEN1
Solar/Wind Harmer
0.22
971443AH1-215 GEN
Solar/Wind Harmer
1.275
3130546PLYMOUTH
Solar/Wind Harmer
0.076
3144303KENBRDG
Solar/Wind Harmer
0.06
3143316POE
Solar/Wind Harmer
0.287
315816AE2-034 GEN
Solar/Wind Harmer
0.308
970683AG2-441 GEN
Solar/Wind Harmer
4.722
970681AG2-440 GEN
Solar/Wind Harmer
3.778
3130156CHOWAN
Solar/Wind Harmer
0.066
3130156CHOWAN
Solar/Wind Harmer
0.066
946301AF1-294 GEN
Solar/Wind Harmer
1.311
961791AG1-021 GEN
Solar/Wind Harmer
0.638
970865AG2-541 GEN
Solar/Wind Harmer
2.298
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
315657AE1-056 GEN
Solar/Wind Harmer
2.185
316123AC1-075 GEN
Solar/Wind Harmer
0.08
970165AG2-112 GEN
Solar/Wind Harmer
0.473
970163AG2-111 GEN
Solar/Wind Harmer
0.451
3145176PASQUOTANK
Solar/Wind Harmer
0.036
316321Z2-027
Solar/Wind Harmer
0.011
3146396TANGLEW
Solar/Wind Harmer
0.161
313526AB2-022
Solar/Wind Harmer
0.031
3146486SUNBURY
Solar/Wind Harmer
0.057
3146486SUNBURY
Solar/Wind Harmer
0.057
316132AB2-190 GEN1
Solar/Wind Helper
0.895
316233AE1-074 FULL
Solar/Wind Helper
0.212
316312AB1-027
Solar/Wind Helper
0.237
971775AH1-396 GEN
Solar/Wind Harmer
0.121
316034AC1-036 C
Solar/Wind Harmer
0.005
316222AC1-221 GEN
Solar/Wind Harmer
0.303
971741AH1-377 GEN
Solar/Wind Harmer
7.057
3146376EDENTON
Solar/Wind Harmer
0.296
3146376EDENTON
Solar/Wind Harmer
0.296
958211AF2-115 GEN
Solar/Wind Harmer
0.797
963191AG1-168 GEN
Solar/Wind Harmer
0.266
3144293JTRSVLE
Adder
0.211
3144293JTRSVLE
Adder
0.178
315742AE1-103 GEN
Solar/Wind Harmer
0.001
970301AG2-198 GEN
Solar/Wind Harmer
2.77
3147133PAMPLIN
Solar/Wind Harmer
0.063
3147133PAMPLIN
Solar/Wind Harmer
0.051
3146626S HERTFORD
Solar/Wind Harmer
0.061
3146626S HERTFORD
Solar/Wind Harmer
0.061
3146516WINFALL
Solar/Wind Harmer
0.06
3146516WINFALL
Solar/Wind Harmer
0.06
3146516WINFALL
Solar/Wind Harmer
0.06
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3146386ELIZ CT
Solar/Wind Harmer
0.057
316240AF1-291 C
Solar/Wind Helper
0.411
966871AG1-558 GEN
Solar/Wind Helper
0.204
3142946ENON
Solar/Wind Helper
0.015
3143526WINTERP
Solar/Wind Helper
0.72
316468AD1-105 GEN
Solar/Wind Helper
0.653
316075AC2-137 C
Solar/Wind Helper
0.178
LAGNLTFEXP_LAGN->PJM
CLTF
3.79
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.991
TVALTFEXP_TVA->PJM
CLTF
1.888
CPLELTFEXP_CPLE->PJM
CLTF
5.631
CBM West 2LTFEXP_CBM-W2->PJM
CBM
19.951
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.11
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.461
MECLTFEXP_MEC->PJM
CLTF
1.839
SIGELTFEXP_SIGE->PJM
CLTF
0.055
NYPJM->LTFIMP_NY
CLTF
0.691
LGEELTFEXP_LGEE->PJM
CLTF
0.659
WECLTFEXP_WEC->PJM
CLTF
0.343

Details for 6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2002_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.21 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1192.96
MW Contribution:3.62
Bus #Bus NameTypeMW Contribution
3151391GASTONA
50/50
0.32
3151411GASTONB
50/50
0.32
3151261ROARAP2
50/50
0.119
3151031BRUNSWICKG2
50/50
1.193
3151591KERR 2
50/50
0.157
970413AG2-270 GEN
50/50
6.966
316365GEN2_N
Solar/Wind Harmer
0.362
313506AB2-031 GEN
Solar/Wind Harmer
0.366
3147043LAWRENC
Solar/Wind Harmer
0.071
3145796HORNRTN
Solar/Wind Harmer
0.453
3145796HORNRTN
Solar/Wind Harmer
0.113
3142666NORTHAMPTON
Solar/Wind Harmer
0.111
315724AD1-057 GEN
Solar/Wind Harmer
0.363
970917AG2-570 GEN
Solar/Wind Harmer
7.751
316327AA2-057 GEN
Solar/Wind Harmer
0.127
961601AG1-000A GEN
Solar/Wind Harmer
5.909
316210AC1-098 GEN
Solar/Wind Harmer
0.77
3146233WITAKRS
Solar/Wind Harmer
0.417
3146233WITAKRS
Solar/Wind Harmer
0.056
3138543CONSLDL
Solar/Wind Harmer
0.055
971623AH1-311 GEN
Solar/Wind Harmer
0.164
3145543BTLEBRO
Solar/Wind Harmer
0.082
3145543BTLEBRO
Solar/Wind Harmer
0.082
3146263WOODLND
Solar/Wind Harmer
0.078
3146073TAR RVR
Solar/Wind Harmer
0.078
3146083TARBORO
Solar/Wind Harmer
0.078
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.075
316478AD1-087 GEN
Solar/Wind Harmer
0.26
316486AD2-202 GEN
Solar/Wind Harmer
0.076
316131AB2-060 GEN
Solar/Wind Harmer
0.229
964241AG1-285 GEN
Solar/Wind Harmer
4.665
316463AE2-346 GEN
Solar/Wind Harmer
0.06
316140AB2-099
Solar/Wind Harmer
0.025
962331AG1-082 GEN
Solar/Wind Harmer
0.742
3145746EVERETS
Solar/Wind Harmer
0.069
3145746EVERETS
Solar/Wind Harmer
0.069
3146173TUNIS
Solar/Wind Harmer
0.068
3156021HOLLOMANSOL
Solar/Wind Harmer
0.305
3145933PARMELE
Solar/Wind Harmer
0.066
966801AG1-551 GEN
Solar/Wind Harmer
0.769
957521AF2-046 GEN
Solar/Wind Harmer
4.888
961681AG1-008 GEN
Solar/Wind Harmer
4.888
315785AD2-033 C
Solar/Wind Harmer
0.532
3145893MURPHYS
Solar/Wind Harmer
0.108
3145893MURPHYS
Solar/Wind Harmer
0.065
970257AG2-171 GEN
Solar/Wind Harmer
2.041
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
2.715
959311AF2-222 GEN
Solar/Wind Harmer
5.561
3145963POPLR C
Solar/Wind Harmer
0.06
3156081AA2-088 GEN
Solar/Wind Harmer
0.001
3146206CASHIE
Solar/Wind Harmer
0.059
316283AC2-100 C
Solar/Wind Harmer
0.115
971683AH1-343 GEN
Solar/Wind Harmer
2.095
315839AE2-212 C
Solar/Wind Helper
1.113
3142946ENON
Solar/Wind Helper
0.074
316473AC1-191 GEN
Solar/Wind Helper
1.189
316280AD1-041 GEN
Solar/Wind Helper
0.416
316404AE1-155 C
Solar/Wind Helper
0.956
316484AD2-074 GEN
Solar/Wind Helper
0.219
316156AD2-030 GEN
Solar/Wind Helper
0.171
315779AE2-040
50/50
3.401
3151281ROARAP4
50/50
0.118
3151281ROARAP4
50/50
0.11
315244AE2-183_ST
50/50
2.625
963041AG1-153 GEN
50/50
2.415
3151611KERR 4
50/50
0.157
3151621KERR 5
50/50
0.157
3151631KERR 6
50/50
0.157
3151641KERR 7
50/50
0.157
3151541CLOVER2
50/50
1.589
316315AB2-025 C
Solar/Wind Harmer
0.197
315814AE2-033 C
Solar/Wind Harmer
18.936
316087AB2-174 GEN
Solar/Wind Harmer
0.004
315652AC1-086 GEN
Solar/Wind Harmer
13.019
3145796HORNRTN
Solar/Wind Harmer
0.362
3145796HORNRTN
Solar/Wind Harmer
0.045
3137643SOCKMAN
Solar/Wind Harmer
0.427
941031AE2-094 GEN
Solar/Wind Harmer
17.475
944011AF1-069 GEN
Solar/Wind Harmer
5.71
970673AG2-436 GEN
Solar/Wind Harmer
19.819
970673AG2-436 GEN
Solar/Wind Harmer
13.213
971967AH1-528 GEN
Solar/Wind Harmer
14.51
970085AG2-068 GEN
Solar/Wind Harmer
4.631
970581AG2-369 GEN
Solar/Wind Harmer
3.982
970831AG2-522 GEN
Solar/Wind Harmer
3.621
315607AA1-063A GEN
Solar/Wind Harmer
0.17
316319Z2-044 C
Solar/Wind Harmer
0
3146043SEABORD
Solar/Wind Harmer
0.081
3146033SCOT NK
Solar/Wind Harmer
0.318
3145573BETHELC
Solar/Wind Harmer
0.078
3145573BETHELC
Solar/Wind Harmer
0.078
316420AA1-050 GEN
Solar/Wind Harmer
0.003
957861AF2-080 GEN
Solar/Wind Harmer
3.178
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
3145683EARLEYS
Solar/Wind Harmer
0.142
3145683EARLEYS
Solar/Wind Harmer
0.071
3145683EARLEYS
Solar/Wind Harmer
0.071
3145513AHOSKIE
Solar/Wind Harmer
0.145
3145513AHOSKIE
Solar/Wind Harmer
0.07
316005AA1-067
Solar/Wind Harmer
0.074
3145746EVERETS
Solar/Wind Harmer
0.274
3145746EVERETS
Solar/Wind Harmer
0.069
3145746EVERETS
Solar/Wind Harmer
0.069
3145746EVERETS
Solar/Wind Harmer
0.069
970181AG2-120 GEN
Solar/Wind Harmer
0.856
316118AC1-105 GEN
Solar/Wind Harmer
0.169
3145893MURPHYS
Solar/Wind Harmer
0.175
3145893MURPHYS
Solar/Wind Harmer
0.065
971443AH1-215 GEN
Solar/Wind Harmer
1.078
3144303KENBRDG
Solar/Wind Harmer
0.051
3147173SINAI
Solar/Wind Harmer
0.064
3147243WELCO
Solar/Wind Harmer
0.04
965291AG1-394 GEN
Solar/Wind Harmer
0.275
970683AG2-441 GEN
Solar/Wind Harmer
3.967
970681AG2-440 GEN
Solar/Wind Harmer
3.174
3146206CASHIE
Solar/Wind Harmer
0.059
970601AG2-382 GEN
Solar/Wind Harmer
2.2
3143316POE
Solar/Wind Helper
1.93
316132AB2-190 GEN1
Solar/Wind Helper
1.544
316369SG1_INVT
Solar/Wind Helper
1.002
316312AB1-027
Solar/Wind Helper
0.328
3143873LANEXA
Solar/Wind Helper
0.095
316233AE1-074 FULL
Solar/Wind Helper
0.214
315662AE1-191 GEN
Solar/Wind Helper
0.666
315666AE1-190 GEN
Solar/Wind Helper
0.167
316059AD1-063 C
Solar/Wind Helper
0.122
3141813NORNECK
Solar/Wind Helper
0.113
3141783LANCAST
Solar/Wind Helper
0.068
3141783LANCAST
Solar/Wind Helper
0.045
3141913WHIT STONE
Solar/Wind Helper
0.113
3138133OCRAN
Solar/Wind Helper
0.034
957601AF2-054 GEN
Solar/Wind Helper
0.152
3141873WAN 176
Solar/Wind Helper
0.023
3151391GASTONA
50/50
0.32
3151411GASTONB
50/50
0.32
3147043LAWRENC
50/50
1.13
3151261ROARAP2
50/50
0.121
315243AE2-183_GT3
50/50
1.518
3151051BRUNSWICKS1
50/50
2.476
3151021BRUNSWICKG1
50/50
1.193
971451AH1-221 GEN
50/50
3.623
3151601KERR 3
50/50
0.157
3151581KERR 1
50/50
0.056
3151531CLOVER1
50/50
1.596
316023GEN1_S
Solar/Wind Harmer
0.362
960081AF2-299 GEN
Solar/Wind Harmer
1.316
971795AH1-408 GEN
Solar/Wind Harmer
8.254
316011AB1-132 GEN
Solar/Wind Harmer
2.152
962571AG1-106 GEN
Solar/Wind Harmer
1.684
3145796HORNRTN
Solar/Wind Harmer
0.374
3145796HORNRTN
Solar/Wind Harmer
0.113
315722AD1-056 GEN
Solar/Wind Harmer
0.612
3145783HORNRTN
Solar/Wind Harmer
0.096
316190AA2-174 GEN
Solar/Wind Harmer
0
970919AG2-571 GEN
Solar/Wind Harmer
3.101
970087AG2-069 GEN
Solar/Wind Harmer
6.946
940641AE2-051 GEN
Solar/Wind Harmer
6.931
316129AC1-054 GEN
Solar/Wind Harmer
0.314
316212AC1-099_GEN
Solar/Wind Harmer
0.43
3146233WITAKRS
Solar/Wind Harmer
0.33
971065AG2-659 GEN
Solar/Wind Harmer
3.51
316359AB2-059 GEN
Solar/Wind Harmer
0.295
316049AB1-081 GEN
Solar/Wind Harmer
0.471
3142053HEARTS
Solar/Wind Harmer
0.145
3145543BTLEBRO
Solar/Wind Harmer
0.082
3145543BTLEBRO
Solar/Wind Harmer
0.066
3146263WOODLND
Solar/Wind Harmer
0.078
957481AF2-042 GEN
Solar/Wind Harmer
20.812
961671AG1-007 GEN
Solar/Wind Harmer
0.012
3146083TARBORO
Solar/Wind Harmer
0.078
3145493TOT1
Solar/Wind Harmer
0.346
3145823KELFORD
Solar/Wind Harmer
0.075
316494AC1-189 GEN
Solar/Wind Harmer
0.249
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
3.49
962491AG1-098 GEN
Solar/Wind Harmer
4.086
3145683EARLEYS
Solar/Wind Harmer
0.071
315687AD1-152 GEN
Solar/Wind Harmer
0.002
939411AE1-173 GEN
Solar/Wind Harmer
30.084
3145746EVERETS
Solar/Wind Harmer
0.069
3145746EVERETS
Solar/Wind Harmer
0.069
3146173TUNIS
Solar/Wind Harmer
0.068
970401AG2-262 GEN
Solar/Wind Harmer
0.397
3146293MARTNCO
Solar/Wind Harmer
0.061
3145893MURPHYS
Solar/Wind Harmer
0.259
3145893MURPHYS
Solar/Wind Harmer
0.288
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3145963POPLR C
Solar/Wind Harmer
0.06
316003AC1-222 GEN
Solar/Wind Harmer
0.002
970685AG2-442 GEN
Solar/Wind Harmer
4.444
3146206CASHIE
Solar/Wind Harmer
0.059
971547AH1-271 GEN
Solar/Wind Harmer
1.257
3142543TWELFTH
Solar/Wind Helper
0.031
316458AB2-190 GEN2
Solar/Wind Helper
1.544
316381AD1-082 GEN
Solar/Wind Helper
1.346
3142433PROV 92
Solar/Wind Helper
0.863
3142416OLDCHRC
Solar/Wind Helper
0.448
3142416OLDCHRC
Solar/Wind Helper
0.172
3143526WINTERP
Solar/Wind Helper
0.727
3141766HARMONY
Solar/Wind Helper
0.024
964211AG1-282 GEN
Solar/Wind Helper
0.157
3141726DUNNSVL
Solar/Wind Helper
0.465
3138133OCRAN
Solar/Wind Helper
0.068
3151361ROSEMG1
50/50
0.408
3151371ROSEMS1
50/50
0.253
3151381ROSEMG2
50/50
0.191
970533AG2-339 GEN
50/50
8.434
970531AG2-338 GEN
50/50
3.373
315242AE2-183_GT2
50/50
1.518
315241AE2-183_GT1
50/50
1.509
972185AH1-677 GEN
50/50
5.473
3151041BRUNSWICKG3
50/50
1.193
972187AH1-678 GEN
50/50
2.737
970535AG2-341 GEN
50/50
1.329
3152661PLYWOOD A
50/50
0.148
3144356SAPONY
Solar/Wind Harmer
2.038
316181AB2-040 GEN
Solar/Wind Harmer
0.172
3145796HORNRTN
Solar/Wind Harmer
0.34
3142666NORTHAMPTON
Solar/Wind Harmer
0.111
3142666NORTHAMPTON
Solar/Wind Harmer
0.111
3142666NORTHAMPTON
Solar/Wind Harmer
0.111
3142666NORTHAMPTON
Solar/Wind Harmer
0.067
3145593CAROLNA
Solar/Wind Harmer
0.097
3145593CAROLNA
Solar/Wind Harmer
0.097
966811AG1-552 GEN
Solar/Wind Harmer
1.057
3145593CAROLNA
Solar/Wind Harmer
0.121
3145783HORNRTN
Solar/Wind Harmer
1.703
3145783HORNRTN
Solar/Wind Harmer
1.362
3145783HORNRTN
Solar/Wind Harmer
0.426
3145783HORNRTN
Solar/Wind Harmer
0.17
316426AA2-053 GEN
Solar/Wind Harmer
0.313
970933AG2-581 GEN
Solar/Wind Harmer
6.963
316274AC1-208 GEN
Solar/Wind Harmer
0.45
961601AG1-000A GEN
Solar/Wind Harmer
1.477
316263AC1-034 GEN
Solar/Wind Harmer
3.125
970099AG2-077 GEN
Solar/Wind Harmer
8.325
3145493TOT1
Solar/Wind Harmer
0.181
3145453TOT5
Solar/Wind Harmer
0.108
3145603CNETO
Solar/Wind Harmer
0.072
939181AE1-148 GEN
Solar/Wind Harmer
3.627
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
3.291
3146173TUNIS
Solar/Wind Harmer
0.068
3146173TUNIS
Solar/Wind Harmer
0.068
964791AG1-342 GEN
Solar/Wind Harmer
1.3
3146843MT LREL
Solar/Wind Harmer
0.068
3146843MT LREL
Solar/Wind Harmer
0.068
3145933PARMELE
Solar/Wind Harmer
0.132
3145933PARMELE
Solar/Wind Harmer
0.066
3145893MURPHYS
Solar/Wind Harmer
0.433
3145893MURPHYS
Solar/Wind Harmer
0.116
970323AG2-213 GEN
Solar/Wind Harmer
2.721
971775AH1-396 GEN
Solar/Wind Harmer
0.102
316034AC1-036 C
Solar/Wind Harmer
0.005
316222AC1-221 GEN
Solar/Wind Harmer
0.245
316065AD1-022 GEN
Solar/Wind Harmer
2.617
971741AH1-377 GEN
Solar/Wind Harmer
5.589
316240AF1-291 C
Solar/Wind Helper
0.691
3142946ENON
Solar/Wind Helper
0.022
316033AB2-134 GEN
Solar/Wind Helper
0.717
315697AD1-025 GEN
Solar/Wind Helper
2.382
966871AG1-558 GEN
Solar/Wind Helper
0.262
316075AC2-137 C
Solar/Wind Helper
0.263
316468AD1-105 GEN
Solar/Wind Helper
0.815
3143526WINTERP
Solar/Wind Helper
0.727
316077AC2-138 C
Solar/Wind Helper
0.107
316487AF1-042 GEN
Solar/Wind Helper
0.114
LAGNLTFEXP_LAGN->PJM
CLTF
3.11
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.716
TVALTFEXP_TVA->PJM
CLTF
1.547
CPLELTFEXP_CPLE->PJM
CLTF
4.572
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.518
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.423
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.312
MECLTFEXP_MEC->PJM
CLTF
1.548
SIGELTFEXP_SIGE->PJM
CLTF
0.046
NYPJM->LTFIMP_NY
CLTF
0.457
LGEELTFEXP_LGEE->PJM
CLTF
0.557
WECLTFEXP_WEC->PJM
CLTF
0.293

Details for 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CARSON-6POE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 249_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.58 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:845.48
MW Contribution:2.87
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
50/50
0.889
3151391GASTONA
50/50
0.249
3151411GASTONB
50/50
0.249
3151261ROARAP2
50/50
0.092
315243AE2-183_GT3
50/50
1.203
3151051BRUNSWICKS1
50/50
1.962
3151021BRUNSWICKG1
50/50
0.945
971451AH1-221 GEN
50/50
2.871
3151601KERR 3
50/50
0.122
3151581KERR 1
50/50
0.044
3151531CLOVER1
50/50
1.261
316023GEN1_S
Solar/Wind Harmer
0.287
960081AF2-299 GEN
Solar/Wind Harmer
1.037
971795AH1-408 GEN
Solar/Wind Harmer
6.499
316011AB1-132 GEN
Solar/Wind Harmer
1.672
962571AG1-106 GEN
Solar/Wind Harmer
1.309
3145796HORNRTN
Solar/Wind Harmer
0.29
3145796HORNRTN
Solar/Wind Harmer
0.088
315722AD1-056 GEN
Solar/Wind Harmer
0.473
3145783HORNRTN
Solar/Wind Harmer
0.072
316190AA2-174 GEN
Solar/Wind Harmer
0
970919AG2-571 GEN
Solar/Wind Harmer
2.454
970087AG2-069 GEN
Solar/Wind Harmer
5.498
940641AE2-051 GEN
Solar/Wind Harmer
5.458
316129AC1-054 GEN
Solar/Wind Harmer
0.242
971065AG2-659 GEN
Solar/Wind Harmer
2.706
3146233WITAKRS
Solar/Wind Harmer
0.252
316359AB2-059 GEN
Solar/Wind Harmer
0.227
316049AB1-081 GEN
Solar/Wind Harmer
0.361
3142053HEARTS
Solar/Wind Harmer
0.111
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.05
316212AC1-099_GEN
Solar/Wind Harmer
0.322
957481AF2-042 GEN
Solar/Wind Harmer
16.463
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.059
3145493TOT1
Solar/Wind Harmer
0.263
315693AD1-088 GEN
Solar/Wind Harmer
2.76
316237AB2-079_GEN
Solar/Wind Harmer
0
3146263WOODLND
Solar/Wind Harmer
0.057
962491AG1-098 GEN
Solar/Wind Harmer
3.232
316381AD1-082 GEN
Solar/Wind Helper
2.648
316458AB2-190 GEN2
Solar/Wind Helper
1.354
3142543TWELFTH
Solar/Wind Helper
0.022
3142433PROV 92
Solar/Wind Helper
0.592
315779AE2-040
50/50
2.75
3151281ROARAP4
50/50
0.089
3151281ROARAP4
50/50
0.084
315244AE2-183_ST
50/50
2.08
963041AG1-153 GEN
50/50
1.914
3151611KERR 4
50/50
0.122
3151621KERR 5
50/50
0.122
3151631KERR 6
50/50
0.122
3151641KERR 7
50/50
0.122
3151541CLOVER2
50/50
1.255
316315AB2-025 C
Solar/Wind Harmer
0.159
315814AE2-033 C
Solar/Wind Harmer
15.301
316087AB2-174 GEN
Solar/Wind Harmer
0.003
315652AC1-086 GEN
Solar/Wind Harmer
10.118
3145796HORNRTN
Solar/Wind Harmer
0.281
3145796HORNRTN
Solar/Wind Harmer
0.035
3137643SOCKMAN
Solar/Wind Harmer
0.328
941031AE2-094 GEN
Solar/Wind Harmer
13.859
944011AF1-069 GEN
Solar/Wind Harmer
4.528
970673AG2-436 GEN
Solar/Wind Harmer
15.712
970673AG2-436 GEN
Solar/Wind Harmer
10.474
971967AH1-528 GEN
Solar/Wind Harmer
11.501
3151361ROSEMG1
50/50
0.317
3151371ROSEMS1
50/50
0.196
3151381ROSEMG2
50/50
0.148
970533AG2-339 GEN
50/50
6.689
970531AG2-338 GEN
50/50
2.675
315242AE2-183_GT2
50/50
1.203
315241AE2-183_GT1
50/50
1.196
972185AH1-677 GEN
50/50
4.338
3151041BRUNSWICKG3
50/50
0.945
972187AH1-678 GEN
50/50
2.169
970535AG2-341 GEN
50/50
1.039
3144356SAPONY
Solar/Wind Harmer
1.648
316181AB2-040 GEN
Solar/Wind Harmer
0.133
3145796HORNRTN
Solar/Wind Harmer
0.264
3142666NORTHAMPTON
Solar/Wind Harmer
0.086
3142666NORTHAMPTON
Solar/Wind Harmer
0.086
3142666NORTHAMPTON
Solar/Wind Harmer
0.086
3142666NORTHAMPTON
Solar/Wind Harmer
0.052
3145593CAROLNA
Solar/Wind Harmer
0.074
3145593CAROLNA
Solar/Wind Harmer
0.074
966811AG1-552 GEN
Solar/Wind Harmer
0.8
3145593CAROLNA
Solar/Wind Harmer
0.092
3145783HORNRTN
Solar/Wind Harmer
1.288
3145783HORNRTN
Solar/Wind Harmer
1.031
3145783HORNRTN
Solar/Wind Harmer
0.322
3145783HORNRTN
Solar/Wind Harmer
0.129
316426AA2-053 GEN
Solar/Wind Harmer
0.235
970933AG2-581 GEN
Solar/Wind Harmer
5.516
316274AC1-208 GEN
Solar/Wind Harmer
0.34
961601AG1-000A GEN
Solar/Wind Harmer
1.135
316263AC1-034 GEN
Solar/Wind Harmer
2.397
970099AG2-077 GEN
Solar/Wind Harmer
6.585
3145493TOT1
Solar/Wind Harmer
0.137
3145453TOT5
Solar/Wind Harmer
0.082
3145603CNETO
Solar/Wind Harmer
0.055
939181AE1-148 GEN
Solar/Wind Harmer
2.827
313527AB2-043 GEN
Solar/Wind Harmer
0.001
316240AF1-291 C
Solar/Wind Helper
0.668
316033AB2-134 GEN
Solar/Wind Helper
0.639
315697AD1-025 GEN
Solar/Wind Helper
2.123
3142946ENON
Solar/Wind Helper
0.018
966871AG1-558 GEN
Solar/Wind Helper
0.198
316075AC2-137 C
Solar/Wind Helper
0.206
316468AD1-105 GEN
Solar/Wind Helper
0.615
970085AG2-068 GEN
Solar/Wind Harmer
3.665
970581AG2-369 GEN
Solar/Wind Harmer
3.152
970831AG2-522 GEN
Solar/Wind Harmer
2.782
316319Z2-044 C
Solar/Wind Harmer
0
315607AA1-063A GEN
Solar/Wind Harmer
0.121
3145573BETHELC
Solar/Wind Harmer
0.059
3145573BETHELC
Solar/Wind Harmer
0.059
3151391GASTONA
50/50
0.249
3151411GASTONB
50/50
0.249
3151261ROARAP2
50/50
0.09
3151031BRUNSWICKG2
50/50
0.945
3151591KERR 2
50/50
0.122
970413AG2-270 GEN
50/50
5.504
316365GEN2_N
Solar/Wind Harmer
0.287
3147043LAWRENC
Solar/Wind Harmer
0.056
313506AB2-031 GEN
Solar/Wind Harmer
0.284
3145796HORNRTN
Solar/Wind Harmer
0.352
3145796HORNRTN
Solar/Wind Harmer
0.088
3142666NORTHAMPTON
Solar/Wind Harmer
0.086
315724AD1-057 GEN
Solar/Wind Harmer
0.281
970917AG2-570 GEN
Solar/Wind Harmer
6.136
961601AG1-000A GEN
Solar/Wind Harmer
4.539
316327AA2-057 GEN
Solar/Wind Harmer
0.096
3146233WITAKRS
Solar/Wind Harmer
0.318
3146233WITAKRS
Solar/Wind Harmer
0.043
3138543CONSLDL
Solar/Wind Harmer
0.042
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
316210AC1-098 GEN
Solar/Wind Harmer
0.577
3146073TAR RVR
Solar/Wind Harmer
0.059
3146083TARBORO
Solar/Wind Harmer
0.059
316478AD1-087 GEN
Solar/Wind Harmer
0.206
316486AD2-202 GEN
Solar/Wind Harmer
0.06
316131AB2-060 GEN
Solar/Wind Harmer
0.179
3146263WOODLND
Solar/Wind Harmer
0.057
315839AE2-212 C
Solar/Wind Helper
0.548
3142946ENON
Solar/Wind Helper
0.059
316473AC1-191 GEN
Solar/Wind Helper
0.896
3142416OLDCHRC
Solar/Wind Helper
0.348
3142416OLDCHRC
Solar/Wind Helper
0.133
3146033SCOT NK
Solar/Wind Harmer
0.235
316420AA1-050 GEN
Solar/Wind Harmer
0.002
316239AB2-077_GEN
Solar/Wind Harmer
0
316238AB2-078_GEN
Solar/Wind Harmer
0
3146043SEABORD
Solar/Wind Harmer
0.057
3143316POE
Solar/Wind Helper
4.642
316132AB2-190 GEN1
Solar/Wind Helper
1.354
316349AD2-085 GEN
Solar/Wind Helper
1.038
316369SG1_INVT
Solar/Wind Helper
0.893
316312AB1-027
Solar/Wind Helper
0.255
3143873LANEXA
Solar/Wind Helper
0.07
LAGNLTFEXP_LAGN->PJM
CLTF
2.457
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.602
TVALTFEXP_TVA->PJM
CLTF
1.222
CPLELTFEXP_CPLE->PJM
CLTF
3.563
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.107
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.398
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.204
MECLTFEXP_MEC->PJM
CLTF
1.237
SIGELTFEXP_SIGE->PJM
CLTF
0.037
NYPJM->LTFIMP_NY
CLTF
0.342
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.235

Details for 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CARSON-6POE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.29 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:789.26
MW Contribution:3.0
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
50/50
0.75
3151391GASTONA
50/50
0.21
3151411GASTONB
50/50
0.21
315243AE2-183_GT3
50/50
1.258
3151051BRUNSWICKS1
50/50
2.048
3151021BRUNSWICKG1
50/50
0.987
971451AH1-221 GEN
50/50
2.997
3151261ROARAP2
50/50
0.081
3151531CLOVER1
50/50
1.291
3151601KERR 3
50/50
0.117
3151581KERR 1
50/50
0.042
316023GEN1_S
Solar/Wind Harmer
0.229
960081AF2-299 GEN
Solar/Wind Harmer
0.85
971795AH1-408 GEN
Solar/Wind Harmer
5.427
316011AB1-132 GEN
Solar/Wind Harmer
1.409
962571AG1-106 GEN
Solar/Wind Harmer
1.102
3145796HORNRTN
Solar/Wind Harmer
0.246
3145796HORNRTN
Solar/Wind Harmer
0.075
940641AE2-051 GEN
Solar/Wind Harmer
5.897
970919AG2-571 GEN
Solar/Wind Harmer
2.554
970087AG2-069 GEN
Solar/Wind Harmer
5.718
315722AD1-056 GEN
Solar/Wind Harmer
0.416
3145783HORNRTN
Solar/Wind Harmer
0.064
957481AF2-042 GEN
Solar/Wind Harmer
16.959
316190AA2-174 GEN
Solar/Wind Harmer
0
939411AE1-173 GEN
Solar/Wind Harmer
26.124
316129AC1-054 GEN
Solar/Wind Harmer
0.223
315693AD1-088 GEN
Solar/Wind Harmer
2.832
971065AG2-659 GEN
Solar/Wind Harmer
2.514
962491AG1-098 GEN
Solar/Wind Harmer
3.316
3146233WITAKRS
Solar/Wind Harmer
0.23
316359AB2-059 GEN
Solar/Wind Harmer
0.207
316049AB1-081 GEN
Solar/Wind Harmer
0.33
3142053HEARTS
Solar/Wind Harmer
0.101
3151391GASTONA
50/50
0.21
3151411GASTONB
50/50
0.21
3151031BRUNSWICKG2
50/50
0.987
3151261ROARAP2
50/50
0.079
970413AG2-270 GEN
50/50
5.635
3151591KERR 2
50/50
0.117
316365GEN2_N
Solar/Wind Harmer
0.229
3147043LAWRENC
Solar/Wind Harmer
0.047
313506AB2-031 GEN
Solar/Wind Harmer
0.239
3145796HORNRTN
Solar/Wind Harmer
0.299
3145796HORNRTN
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.073
970917AG2-570 GEN
Solar/Wind Harmer
6.384
315724AD1-057 GEN
Solar/Wind Harmer
0.246
316478AD1-087 GEN
Solar/Wind Harmer
0.21
316486AD2-202 GEN
Solar/Wind Harmer
0.062
961601AG1-000A GEN
Solar/Wind Harmer
4.135
316327AA2-057 GEN
Solar/Wind Harmer
0.088
3146233WITAKRS
Solar/Wind Harmer
0.29
3146233WITAKRS
Solar/Wind Harmer
0.039
3138543CONSLDL
Solar/Wind Harmer
0.038
971623AH1-311 GEN
Solar/Wind Harmer
0.115
3145543BTLEBRO
Solar/Wind Harmer
0.057
3145543BTLEBRO
Solar/Wind Harmer
0.057
316210AC1-098 GEN
Solar/Wind Harmer
0.528
970533AG2-339 GEN
50/50
7.009
970531AG2-338 GEN
50/50
2.804
315242AE2-183_GT2
50/50
1.258
315241AE2-183_GT1
50/50
1.25
972185AH1-677 GEN
50/50
4.534
3151041BRUNSWICKG3
50/50
0.987
972187AH1-678 GEN
50/50
2.264
3151361ROSEMG1
50/50
0.269
3151371ROSEMS1
50/50
0.167
3151381ROSEMG2
50/50
0.126
3144356SAPONY
Solar/Wind Harmer
1.251
316181AB2-040 GEN
Solar/Wind Harmer
0.112
3145796HORNRTN
Solar/Wind Harmer
0.224
3142666NORTHAMPTON
Solar/Wind Harmer
0.073
3142666NORTHAMPTON
Solar/Wind Harmer
0.073
3142666NORTHAMPTON
Solar/Wind Harmer
0.073
3142666NORTHAMPTON
Solar/Wind Harmer
0.044
970933AG2-581 GEN
Solar/Wind Harmer
5.741
3145593CAROLNA
Solar/Wind Harmer
0.065
3145593CAROLNA
Solar/Wind Harmer
0.065
966811AG1-552 GEN
Solar/Wind Harmer
0.703
3145593CAROLNA
Solar/Wind Harmer
0.081
3145783HORNRTN
Solar/Wind Harmer
1.137
3145783HORNRTN
Solar/Wind Harmer
0.909
3145783HORNRTN
Solar/Wind Harmer
0.284
3145783HORNRTN
Solar/Wind Harmer
0.114
970099AG2-077 GEN
Solar/Wind Harmer
6.784
316426AA2-053 GEN
Solar/Wind Harmer
0.209
316274AC1-208 GEN
Solar/Wind Harmer
0.307
961601AG1-000A GEN
Solar/Wind Harmer
1.034
316263AC1-034 GEN
Solar/Wind Harmer
2.189
316240AF1-291 C
Solar/Wind Helper
0.46
315779AE2-040
50/50
2.087
315244AE2-183_ST
50/50
2.174
963041AG1-153 GEN
50/50
1.998
3151281ROARAP4
50/50
0.079
3151281ROARAP4
50/50
0.073
3151541CLOVER2
50/50
1.285
3151611KERR 4
50/50
0.117
3151621KERR 5
50/50
0.117
3151631KERR 6
50/50
0.117
3151641KERR 7
50/50
0.117
316315AB2-025 C
Solar/Wind Harmer
0.121
315814AE2-033 C
Solar/Wind Harmer
11.633
316087AB2-174 GEN
Solar/Wind Harmer
0.002
941031AE2-094 GEN
Solar/Wind Harmer
14.523
944011AF1-069 GEN
Solar/Wind Harmer
4.745
315652AC1-086 GEN
Solar/Wind Harmer
8.522
970673AG2-436 GEN
Solar/Wind Harmer
16.437
970673AG2-436 GEN
Solar/Wind Harmer
10.958
971967AH1-528 GEN
Solar/Wind Harmer
12.009
3145796HORNRTN
Solar/Wind Harmer
0.239
3145796HORNRTN
Solar/Wind Harmer
0.03
970085AG2-068 GEN
Solar/Wind Harmer
3.812
970581AG2-369 GEN
Solar/Wind Harmer
3.278
3137643SOCKMAN
Solar/Wind Harmer
0.282
970831AG2-522 GEN
Solar/Wind Harmer
2.557
316319Z2-044 C
Solar/Wind Harmer
0
3143316POE
Solar/Wind Helper
4.623
316349AD2-085 GEN
Solar/Wind Helper
0.873
316132AB2-190 GEN1
Solar/Wind Helper
0.785
3145543BTLEBRO
Solar/Wind Harmer
0.057
3145543BTLEBRO
Solar/Wind Harmer
0.046
316212AC1-099_GEN
Solar/Wind Harmer
0.294
315687AD1-152 GEN
Solar/Wind Harmer
0.002
316381AD1-082 GEN
Solar/Wind Helper
2.389
316458AB2-190 GEN2
Solar/Wind Helper
0.785
3142543TWELFTH
Solar/Wind Helper
0.012
LAGNLTFEXP_LAGN->PJM
CLTF
2.426
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.56
TVALTFEXP_TVA->PJM
CLTF
1.209
CPLELTFEXP_CPLE->PJM
CLTF
3.53
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.861
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.008
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.148
MECLTFEXP_MEC->PJM
CLTF
1.199
SIGELTFEXP_SIGE->PJM
CLTF
0.036
NYPJM->LTFIMP_NY
CLTF
0.411
LGEELTFEXP_LGEE->PJM
CLTF
0.433
WECLTFEXP_WEC->PJM
CLTF
0.226

Details for 6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:152.97 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1841.8
MW Contribution:5.99
Bus #Bus NameTypeMW Contribution
970533AG2-339 GEN
50/50
14.043
970531AG2-338 GEN
50/50
5.617
315242AE2-183_GT2
50/50
2.516
315241AE2-183_GT1
50/50
2.5
972185AH1-677 GEN
50/50
9.069
3151041BRUNSWICKG3
50/50
1.972
972187AH1-678 GEN
50/50
4.526
3151361ROSEMG1
50/50
0.471
3151371ROSEMS1
50/50
0.292
315779AE2-040
50/50
3.378
315244AE2-183_ST
50/50
4.349
963041AG1-153 GEN
50/50
3.994
3151541CLOVER2
50/50
2.544
3151281ROARAP4
50/50
0.144
3151281ROARAP4
50/50
0.134
316315AB2-025 C
Solar/Wind Harmer
0.734
315814AE2-033 C
Solar/Wind Harmer
24.939
941031AE2-094 GEN
Solar/Wind Harmer
33.281
944011AF1-069 GEN
Solar/Wind Harmer
10.428
970673AG2-436 GEN
Solar/Wind Harmer
36.399
970673AG2-436 GEN
Solar/Wind Harmer
18.43
946281AF1-292 GEN
Solar/Wind Harmer
0.383
971967AH1-528 GEN
Solar/Wind Harmer
31.705
970085AG2-068 GEN
Solar/Wind Harmer
10.008
970581AG2-369 GEN
Solar/Wind Harmer
8.607
316087AB2-174 GEN
Solar/Wind Harmer
2.265
315652AC1-086 GEN
Solar/Wind Harmer
17.05
3145796HORNRTN
Solar/Wind Harmer
-0.047
3145796HORNRTN
Solar/Wind Harmer
-0.006
3137643SOCKMAN
Solar/Wind Harmer
-0.057
970831AG2-522 GEN
Solar/Wind Harmer
6.31
315607AA1-063A GEN
Solar/Wind Harmer
1.207
316319Z2-044 C
Solar/Wind Harmer
0.657
3146043SEABORD
Solar/Wind Harmer
-0.012
316239AB2-077_GEN
Solar/Wind Harmer
0.35
316238AB2-078_GEN
Solar/Wind Harmer
0.35
3146033SCOT NK
Solar/Wind Harmer
-0.045
3145573BETHELC
Solar/Wind Harmer
-0.011
3145573BETHELC
Solar/Wind Harmer
-0.011
316420AA1-050 GEN
Solar/Wind Harmer
1.267
316118AC1-105 GEN
Solar/Wind Harmer
0.759
3147173SINAI
Solar/Wind Harmer
-0.011
3147243WELCO
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
4.731
971443AH1-215 GEN
Solar/Wind Harmer
2.043
3145683EARLEYS
Solar/Wind Harmer
-0.021
3145683EARLEYS
Solar/Wind Harmer
-0.01
3145683EARLEYS
Solar/Wind Harmer
-0.01
3144303KENBRDG
Solar/Wind Harmer
-0.008
3145513AHOSKIE
Solar/Wind Harmer
0.089
961941AG1-037 GEN
Solar/Wind Harmer
0.077
3145513AHOSKIE
Solar/Wind Harmer
-0.01
316005AA1-067
Solar/Wind Harmer
0.207
3145746EVERETS
Solar/Wind Harmer
-0.041
3145746EVERETS
Solar/Wind Harmer
-0.01
3145746EVERETS
Solar/Wind Harmer
-0.01
3145746EVERETS
Solar/Wind Harmer
-0.01
970181AG2-120 GEN
Solar/Wind Harmer
1.344
316318V4-068
Solar/Wind Harmer
0.249
3145893MURPHYS
Solar/Wind Harmer
-0.027
3145893MURPHYS
Solar/Wind Harmer
-0.01
965291AG1-394 GEN
Solar/Wind Harmer
0.871
970683AG2-441 GEN
Solar/Wind Harmer
7.621
970681AG2-440 GEN
Solar/Wind Harmer
6.097
3143316POE
Solar/Wind Harmer
-0.038
970865AG2-541 GEN
Solar/Wind Harmer
3.743
946301AF1-294 GEN
Solar/Wind Harmer
2.361
961791AG1-021 GEN
Solar/Wind Harmer
1.152
315657AE1-056 GEN
Solar/Wind Harmer
3.313
3146206CASHIE
Solar/Wind Harmer
-0.009
970601AG2-382 GEN
Solar/Wind Harmer
3.864
270455AD2-022 GEN
Solar/Wind Harmer
1.529
270457AD2-023 GEN
Solar/Wind Harmer
0.775
315732AD1-074 GEN1
Solar/Wind Harmer
1.65
315733AD1-074 GEN2
Solar/Wind Harmer
1.65
315735AD1-075 GEN1
Solar/Wind Harmer
0.825
316123AC1-075 GEN
Solar/Wind Harmer
0.874
970165AG2-112 GEN
Solar/Wind Harmer
0.77
970163AG2-111 GEN
Solar/Wind Harmer
0.734
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315816AE2-034 GEN
Solar/Wind Harmer
0.593
3130156CHOWAN
Solar/Wind Harmer
-0.006
3130156CHOWAN
Solar/Wind Harmer
-0.006
316132AB2-190 GEN1
Solar/Wind Helper
0.976
316233AE1-074 FULL
Solar/Wind Helper
0.226
316312AB1-027
Solar/Wind Helper
0.27
3143873LANEXA
Solar/Wind Helper
0.076
316369SG1_INVT
Solar/Wind Helper
0.602
3151031BRUNSWICKG2
50/50
1.972
3151391GASTONA
50/50
0.365
3151411GASTONB
50/50
0.365
970413AG2-270 GEN
50/50
11.155
3151261ROARAP2
50/50
0.144
316365GEN2_N
Solar/Wind Harmer
1.302
966621AG1-532 GEN
Solar/Wind Harmer
0.347
970917AG2-570 GEN
Solar/Wind Harmer
40.235
3147043LAWRENC
Solar/Wind Harmer
-0.009
313506AB2-031 GEN
Solar/Wind Harmer
1.233
3145796HORNRTN
Solar/Wind Harmer
-0.058
3145796HORNRTN
Solar/Wind Harmer
-0.015
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
316478AD1-087 GEN
Solar/Wind Harmer
1.161
316486AD2-202 GEN
Solar/Wind Harmer
0.34
315724AD1-057 GEN
Solar/Wind Harmer
0.758
316327AA2-057 GEN
Solar/Wind Harmer
1.21
961601AG1-000A GEN
Solar/Wind Harmer
4.742
3146233WITAKRS
Solar/Wind Harmer
0.249
3146233WITAKRS
Solar/Wind Harmer
-0.008
3138543CONSLDL
Solar/Wind Harmer
-0.008
3145543BTLEBRO
Solar/Wind Harmer
-0.012
3145543BTLEBRO
Solar/Wind Harmer
-0.012
316210AC1-098 GEN
Solar/Wind Harmer
1.85
316131AB2-060 GEN
Solar/Wind Harmer
1.244
3146073TAR RVR
Solar/Wind Harmer
-0.011
3146083TARBORO
Solar/Wind Harmer
-0.011
964241AG1-285 GEN
Solar/Wind Harmer
8.72
3146263WOODLND
Solar/Wind Harmer
-0.011
316248AF1-058 C
Solar/Wind Harmer
0.328
960061AF2-297 GEN
Solar/Wind Harmer
5.444
316317KELFORD C
Solar/Wind Harmer
0.511
3145823KELFORD
Solar/Wind Harmer
-0.011
315785AD2-033 C
Solar/Wind Harmer
2.392
970257AG2-171 GEN
Solar/Wind Harmer
3.873
316463AE2-346 GEN
Solar/Wind Harmer
0.166
316140AB2-099
Solar/Wind Harmer
0.069
962331AG1-082 GEN
Solar/Wind Harmer
1.281
3145746EVERETS
Solar/Wind Harmer
-0.01
3145746EVERETS
Solar/Wind Harmer
-0.01
959311AF2-222 GEN
Solar/Wind Harmer
10.609
3146173TUNIS
Solar/Wind Harmer
-0.01
957521AF2-046 GEN
Solar/Wind Harmer
7.902
961681AG1-008 GEN
Solar/Wind Harmer
7.902
316283AC2-100 C
Solar/Wind Harmer
0.942
3145893MURPHYS
Solar/Wind Harmer
0.07
3145893MURPHYS
Solar/Wind Harmer
-0.01
3145933PARMELE
Solar/Wind Harmer
-0.01
966801AG1-551 GEN
Solar/Wind Harmer
1.233
3156021HOLLOMANSOL
Solar/Wind Harmer
1.319
971683AH1-343 GEN
Solar/Wind Harmer
4.208
3156081AA2-088 GEN
Solar/Wind Harmer
3.105
970909AG2-566 GEN
Solar/Wind Harmer
0.889
963181AG1-167 GEN
Solar/Wind Harmer
0.864
3144293JTRSVLE
Adder
0.261
3145963POPLR C
Solar/Wind Harmer
-0.009
3147133PAMPLIN
Solar/Wind Harmer
-0.028
971193AH1-056 GEN
Solar/Wind Harmer
5.522
3146206CASHIE
Solar/Wind Harmer
-0.009
315737AD1-076 GEN
Solar/Wind Harmer
1.551
971157AH1-035 GEN
Solar/Wind Harmer
1.003
942461AE2-259 GEN
Solar/Wind Harmer
1.167
315614AA2-178 GEN
Solar/Wind Harmer
0.791
3146926FARMVIL
Solar/Wind Harmer
-0.004
3146376EDENTON
Solar/Wind Harmer
-0.006
315839AE2-212 C
Solar/Wind Helper
0.966
3142946ENON
Solar/Wind Helper
0.055
316473AC1-191 GEN
Solar/Wind Helper
1
315243AE2-183_GT3
50/50
2.516
3151051BRUNSWICKS1
50/50
4.094
3151021BRUNSWICKG1
50/50
1.972
971451AH1-221 GEN
50/50
5.991
3147043LAWRENC
50/50
1.32
3151391GASTONA
50/50
0.365
3151411GASTONB
50/50
0.365
3151531CLOVER1
50/50
2.556
3151261ROARAP2
50/50
0.148
316023GEN1_S
Solar/Wind Harmer
1.302
960081AF2-299 GEN
Solar/Wind Harmer
1.926
970919AG2-571 GEN
Solar/Wind Harmer
5.093
970087AG2-069 GEN
Solar/Wind Harmer
15.012
971795AH1-408 GEN
Solar/Wind Harmer
11.982
316011AB1-132 GEN
Solar/Wind Harmer
3.171
962571AG1-106 GEN
Solar/Wind Harmer
2.179
3145796HORNRTN
Solar/Wind Harmer
-0.048
3145796HORNRTN
Solar/Wind Harmer
-0.015
957481AF2-042 GEN
Solar/Wind Harmer
44.356
315722AD1-056 GEN
Solar/Wind Harmer
1.378
3145783HORNRTN
Solar/Wind Harmer
-0.013
315693AD1-088 GEN
Solar/Wind Harmer
6.574
939411AE1-173 GEN
Solar/Wind Harmer
65.115
962491AG1-098 GEN
Solar/Wind Harmer
8.662
316190AA2-174 GEN
Solar/Wind Harmer
0.157
316129AC1-054 GEN
Solar/Wind Harmer
1.1
315687AD1-152 GEN
Solar/Wind Harmer
1.509
971065AG2-659 GEN
Solar/Wind Harmer
6.236
3146233WITAKRS
Solar/Wind Harmer
-0.047
316359AB2-059 GEN
Solar/Wind Harmer
1.597
316049AB1-081 GEN
Solar/Wind Harmer
1.278
3142053HEARTS
Solar/Wind Harmer
0.139
3145543BTLEBRO
Solar/Wind Harmer
-0.012
3145543BTLEBRO
Solar/Wind Harmer
-0.009
316212AC1-099_GEN
Solar/Wind Harmer
1.028
316237AB2-079_GEN
Solar/Wind Harmer
0.35
961671AG1-007 GEN
Solar/Wind Harmer
0.143
3146083TARBORO
Solar/Wind Harmer
-0.011
3145493TOT1
Solar/Wind Harmer
0.335
970401AG2-262 GEN
Solar/Wind Harmer
0.731
3146263WOODLND
Solar/Wind Harmer
-0.011
3145823KELFORD
Solar/Wind Harmer
-0.011
316494AC1-189 GEN
Solar/Wind Harmer
1.164
3145683EARLEYS
Solar/Wind Harmer
-0.01
316003AC1-222 GEN
Solar/Wind Harmer
1.004
3145746EVERETS
Solar/Wind Harmer
-0.01
3145746EVERETS
Solar/Wind Harmer
-0.01
3146173TUNIS
Solar/Wind Harmer
-0.01
3145893MURPHYS
Solar/Wind Harmer
-0.04
3145893MURPHYS
Solar/Wind Harmer
0.296
3146293MARTNCO
Solar/Wind Harmer
0.061
970685AG2-442 GEN
Solar/Wind Harmer
8.535
316174AB2-169 GEN
Solar/Wind Harmer
1.424
963171AG1-166 GEN
Solar/Wind Harmer
1.152
971563AH1-280 GEN
Solar/Wind Harmer
1.152
3144293JTRSVLE
Adder
0.261
3145963POPLR C
Solar/Wind Harmer
-0.009
3146206CASHIE
Solar/Wind Harmer
-0.009
971547AH1-271 GEN
Solar/Wind Harmer
2.208
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.873
3146926FARMVIL
Solar/Wind Harmer
-0.004
3130156CHOWAN
Solar/Wind Harmer
-0.006
3142543TWELFTH
Solar/Wind Helper
0.024
3142433PROV 92
Solar/Wind Helper
0.7
316458AB2-190 GEN2
Solar/Wind Helper
0.976
3143526WINTERP
Solar/Wind Helper
0.769
3142416OLDCHRC
Solar/Wind Helper
0.369
3142416OLDCHRC
Solar/Wind Helper
0.141
3143226MDLTHAN
Solar/Wind Helper
0.133
3151381ROSEMG2
50/50
0.22
3144356SAPONY
Solar/Wind Harmer
0.948
970933AG2-581 GEN
Solar/Wind Harmer
15.092
316181AB2-040 GEN
Solar/Wind Harmer
2.139
3145796HORNRTN
Solar/Wind Harmer
-0.044
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
970099AG2-077 GEN
Solar/Wind Harmer
17.742
3145593CAROLNA
Solar/Wind Harmer
-0.013
3145593CAROLNA
Solar/Wind Harmer
-0.013
966811AG1-552 GEN
Solar/Wind Harmer
1.5
3145593CAROLNA
Solar/Wind Harmer
0.111
3145783HORNRTN
Solar/Wind Harmer
1.561
3145783HORNRTN
Solar/Wind Harmer
1.249
3145783HORNRTN
Solar/Wind Harmer
0.39
3145783HORNRTN
Solar/Wind Harmer
0.156
316426AA2-053 GEN
Solar/Wind Harmer
1.293
316274AC1-208 GEN
Solar/Wind Harmer
1.319
939181AE1-148 GEN
Solar/Wind Harmer
6.767
961601AG1-000A GEN
Solar/Wind Harmer
4.682
316263AC1-034 GEN
Solar/Wind Harmer
5.552
313527AB2-043 GEN
Solar/Wind Harmer
1.888
3145493TOT1
Solar/Wind Harmer
0.175
3145453TOT5
Solar/Wind Harmer
0.105
3145603CNETO
Solar/Wind Harmer
0.07
962561AG1-105 GEN
Solar/Wind Harmer
6.333
964791AG1-342 GEN
Solar/Wind Harmer
2.391
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970323AG2-213 GEN
Solar/Wind Harmer
5.164
971775AH1-396 GEN
Solar/Wind Harmer
0.735
316034AC1-036 C
Solar/Wind Harmer
0.191
971741AH1-377 GEN
Solar/Wind Harmer
11.893
3146173TUNIS
Solar/Wind Harmer
-0.01
3146173TUNIS
Solar/Wind Harmer
-0.01
316222AC1-221 GEN
Solar/Wind Harmer
1.018
3145893MURPHYS
Solar/Wind Harmer
0.278
3145893MURPHYS
Solar/Wind Harmer
-0.018
3145933PARMELE
Solar/Wind Harmer
-0.02
3145933PARMELE
Solar/Wind Harmer
-0.01
970301AG2-198 GEN
Solar/Wind Harmer
4.681
958211AF2-115 GEN
Solar/Wind Harmer
1.439
963191AG1-168 GEN
Solar/Wind Harmer
0.864
3144293JTRSVLE
Adder
0.261
3144293JTRSVLE
Adder
0.22
3147133PAMPLIN
Solar/Wind Harmer
-0.009
3147133PAMPLIN
Solar/Wind Harmer
-0.007
316065AD1-022 GEN
Solar/Wind Harmer
4.293
942751AE2-291 GEN
Solar/Wind Harmer
4.718
315742AE1-103 GEN
Solar/Wind Harmer
0.706
3146376EDENTON
Solar/Wind Harmer
0.191
3146376EDENTON
Solar/Wind Harmer
0.191
316240AF1-291 C
Solar/Wind Helper
0.402
3142946ENON
Solar/Wind Helper
0.017
966871AG1-558 GEN
Solar/Wind Helper
0.221
3143526WINTERP
Solar/Wind Helper
0.769
316468AD1-105 GEN
Solar/Wind Helper
0.714
316075AC2-137 C
Solar/Wind Helper
0.21
316033AB2-134 GEN
Solar/Wind Helper
0.43
315697AD1-025 GEN
Solar/Wind Helper
1.43
LAGNLTFEXP_LAGN->PJM
CLTF
4.648
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.569
TVALTFEXP_TVA->PJM
CLTF
2.315
CPLELTFEXP_CPLE->PJM
CLTF
6.792
CBM West 2LTFEXP_CBM-W2->PJM
CBM
24.55
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.091
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.934
MECLTFEXP_MEC->PJM
CLTF
2.276
SIGELTFEXP_SIGE->PJM
CLTF
0.068
NYPJM->LTFIMP_NY
CLTF
0.817
LGEELTFEXP_LGEE->PJM
CLTF
0.818
WECLTFEXP_WEC->PJM
CLTF
0.427

Details for 6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:142.99 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1407.24
MW Contribution:4.66
Bus #Bus NameTypeMW Contribution
315779AE2-040
50/50
3.099
315244AE2-183_ST
50/50
3.382
963041AG1-153 GEN
50/50
3.109
3151281ROARAP4
50/50
0.132
3151281ROARAP4
50/50
0.123
3151541CLOVER2
50/50
2.008
3151611KERR 4
50/50
0.187
3151621KERR 5
50/50
0.187
3151631KERR 6
50/50
0.187
3151641KERR 7
50/50
0.187
316315AB2-025 C
Solar/Wind Harmer
0.179
315814AE2-033 C
Solar/Wind Harmer
17.298
316087AB2-174 GEN
Solar/Wind Harmer
0.004
315652AC1-086 GEN
Solar/Wind Harmer
13.694
941031AE2-094 GEN
Solar/Wind Harmer
22.572
944011AF1-069 GEN
Solar/Wind Harmer
7.375
3145796HORNRTN
Solar/Wind Harmer
0.385
3145796HORNRTN
Solar/Wind Harmer
0.048
970673AG2-436 GEN
Solar/Wind Harmer
25.561
970673AG2-436 GEN
Solar/Wind Harmer
17.041
971967AH1-528 GEN
Solar/Wind Harmer
18.68
3137643SOCKMAN
Solar/Wind Harmer
0.464
970085AG2-068 GEN
Solar/Wind Harmer
5.942
970581AG2-369 GEN
Solar/Wind Harmer
5.11
315607AA1-063A GEN
Solar/Wind Harmer
0.204
3146043SEABORD
Solar/Wind Harmer
0.098
970831AG2-522 GEN
Solar/Wind Harmer
4.182
316319Z2-044 C
Solar/Wind Harmer
0
3146033SCOT NK
Solar/Wind Harmer
0.379
3145573BETHELC
Solar/Wind Harmer
0.092
3145573BETHELC
Solar/Wind Harmer
0.092
316420AA1-050 GEN
Solar/Wind Harmer
0.003
3145683EARLEYS
Solar/Wind Harmer
0.179
3145683EARLEYS
Solar/Wind Harmer
0.09
3145683EARLEYS
Solar/Wind Harmer
0.09
3145513AHOSKIE
Solar/Wind Harmer
0.186
3145513AHOSKIE
Solar/Wind Harmer
0.089
957861AF2-080 GEN
Solar/Wind Harmer
3.828
3145893MURPHYS
Solar/Wind Harmer
0.235
3145893MURPHYS
Solar/Wind Harmer
0.087
965291AG1-394 GEN
Solar/Wind Harmer
0.382
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316005AA1-067
Solar/Wind Harmer
0.092
3145746EVERETS
Solar/Wind Harmer
0.34
3145746EVERETS
Solar/Wind Harmer
0.085
3145746EVERETS
Solar/Wind Harmer
0.085
3145746EVERETS
Solar/Wind Harmer
0.085
970181AG2-120 GEN
Solar/Wind Harmer
1.064
3146206CASHIE
Solar/Wind Harmer
0.08
970601AG2-382 GEN
Solar/Wind Harmer
3.008
316118AC1-105 GEN
Solar/Wind Harmer
0.206
3147173SINAI
Solar/Wind Harmer
0.078
3147243WELCO
Solar/Wind Harmer
0.049
315732AD1-074 GEN1
Solar/Wind Harmer
0.439
315733AD1-074 GEN2
Solar/Wind Harmer
0.439
315735AD1-075 GEN1
Solar/Wind Harmer
0.22
971443AH1-215 GEN
Solar/Wind Harmer
1.275
3130546PLYMOUTH
Solar/Wind Harmer
0.076
3144303KENBRDG
Solar/Wind Harmer
0.06
3143316POE
Solar/Wind Harmer
0.287
315816AE2-034 GEN
Solar/Wind Harmer
0.308
970683AG2-441 GEN
Solar/Wind Harmer
4.722
970681AG2-440 GEN
Solar/Wind Harmer
3.778
3130156CHOWAN
Solar/Wind Harmer
0.066
3130156CHOWAN
Solar/Wind Harmer
0.066
946301AF1-294 GEN
Solar/Wind Harmer
1.311
961791AG1-021 GEN
Solar/Wind Harmer
0.638
970865AG2-541 GEN
Solar/Wind Harmer
2.298
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
315657AE1-056 GEN
Solar/Wind Harmer
2.185
316123AC1-075 GEN
Solar/Wind Harmer
0.08
970165AG2-112 GEN
Solar/Wind Harmer
0.473
970163AG2-111 GEN
Solar/Wind Harmer
0.451
3145176PASQUOTANK
Solar/Wind Harmer
0.036
316321Z2-027
Solar/Wind Harmer
0.011
3146396TANGLEW
Solar/Wind Harmer
0.161
313526AB2-022
Solar/Wind Harmer
0.031
3146486SUNBURY
Solar/Wind Harmer
0.057
3146486SUNBURY
Solar/Wind Harmer
0.057
316132AB2-190 GEN1
Solar/Wind Helper
0.895
316233AE1-074 FULL
Solar/Wind Helper
0.212
316312AB1-027
Solar/Wind Helper
0.237
3151391GASTONA
50/50
0.337
3151411GASTONB
50/50
0.337
3147043LAWRENC
50/50
1.178
315243AE2-183_GT3
50/50
1.956
3151051BRUNSWICKS1
50/50
3.187
3151021BRUNSWICKG1
50/50
1.536
971451AH1-221 GEN
50/50
4.664
3151261ROARAP2
50/50
0.136
3151531CLOVER1
50/50
2.018
3151601KERR 3
50/50
0.187
3151581KERR 1
50/50
0.067
316023GEN1_S
Solar/Wind Harmer
0.354
960081AF2-299 GEN
Solar/Wind Harmer
1.332
971795AH1-408 GEN
Solar/Wind Harmer
8.516
316011AB1-132 GEN
Solar/Wind Harmer
2.263
962571AG1-106 GEN
Solar/Wind Harmer
1.771
3145796HORNRTN
Solar/Wind Harmer
0.397
3145796HORNRTN
Solar/Wind Harmer
0.12
940641AE2-051 GEN
Solar/Wind Harmer
9.263
970919AG2-571 GEN
Solar/Wind Harmer
3.98
970087AG2-069 GEN
Solar/Wind Harmer
8.913
3145783HORNRTN
Solar/Wind Harmer
0.107
315722AD1-056 GEN
Solar/Wind Harmer
0.674
316190AA2-174 GEN
Solar/Wind Harmer
0
939411AE1-173 GEN
Solar/Wind Harmer
42.901
957481AF2-042 GEN
Solar/Wind Harmer
26.456
316212AC1-099_GEN
Solar/Wind Harmer
0.502
316129AC1-054 GEN
Solar/Wind Harmer
0.364
971065AG2-659 GEN
Solar/Wind Harmer
4.087
3146233WITAKRS
Solar/Wind Harmer
0.38
3146263WOODLND
Solar/Wind Harmer
0.095
316359AB2-059 GEN
Solar/Wind Harmer
0.34
316049AB1-081 GEN
Solar/Wind Harmer
0.541
3142053HEARTS
Solar/Wind Harmer
0.166
3145543BTLEBRO
Solar/Wind Harmer
0.094
3145543BTLEBRO
Solar/Wind Harmer
0.075
3145823KELFORD
Solar/Wind Harmer
0.092
315693AD1-088 GEN
Solar/Wind Harmer
4.418
961671AG1-007 GEN
Solar/Wind Harmer
0.014
3146083TARBORO
Solar/Wind Harmer
0.092
3145493TOT1
Solar/Wind Harmer
0.407
962491AG1-098 GEN
Solar/Wind Harmer
5.172
3145683EARLEYS
Solar/Wind Harmer
0.09
316494AC1-189 GEN
Solar/Wind Harmer
0.3
315687AD1-152 GEN
Solar/Wind Harmer
0.003
3146173TUNIS
Solar/Wind Harmer
0.088
3145893MURPHYS
Solar/Wind Harmer
0.348
3145893MURPHYS
Solar/Wind Harmer
0.387
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3145746EVERETS
Solar/Wind Harmer
0.085
3145746EVERETS
Solar/Wind Harmer
0.085
3146293MARTNCO
Solar/Wind Harmer
0.078
970401AG2-262 GEN
Solar/Wind Harmer
0.478
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3146206CASHIE
Solar/Wind Harmer
0.08
971547AH1-271 GEN
Solar/Wind Harmer
1.719
3145963POPLR C
Solar/Wind Harmer
0.08
316003AC1-222 GEN
Solar/Wind Harmer
0.002
3145663CRESWEL
Solar/Wind Harmer
0.201
971163AH1-040 GEN
Solar/Wind Harmer
5.738
970685AG2-442 GEN
Solar/Wind Harmer
5.289
3130156CHOWAN
Solar/Wind Harmer
0.066
963171AG1-166 GEN
Solar/Wind Harmer
0.354
971563AH1-280 GEN
Solar/Wind Harmer
0.708
3144293JTRSVLE
Adder
0.211
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
316294AC1-161 GEN
Solar/Wind Harmer
1.066
3146516WINFALL
Solar/Wind Harmer
0.194
3146516WINFALL
Solar/Wind Harmer
0.06
944591AF1-124 GEN
Solar/Wind Harmer
12.705
3142543TWELFTH
Solar/Wind Helper
0.024
316458AB2-190 GEN2
Solar/Wind Helper
0.895
3142433PROV 92
Solar/Wind Helper
0.616
3143526WINTERP
Solar/Wind Helper
0.72
3143226MDLTHAN
Solar/Wind Helper
0.125
3142416OLDCHRC
Solar/Wind Helper
0.323
3142416OLDCHRC
Solar/Wind Helper
0.124
3151391GASTONA
50/50
0.337
3151411GASTONB
50/50
0.337
3151031BRUNSWICKG2
50/50
1.536
3151261ROARAP2
50/50
0.133
970413AG2-270 GEN
50/50
8.806
3151591KERR 2
50/50
0.187
316365GEN2_N
Solar/Wind Harmer
0.354
313506AB2-031 GEN
Solar/Wind Harmer
0.385
3147043LAWRENC
Solar/Wind Harmer
0.074
3145796HORNRTN
Solar/Wind Harmer
0.481
3145796HORNRTN
Solar/Wind Harmer
0.12
3142666NORTHAMPTON
Solar/Wind Harmer
0.119
970917AG2-570 GEN
Solar/Wind Harmer
9.95
315724AD1-057 GEN
Solar/Wind Harmer
0.4
316210AC1-098 GEN
Solar/Wind Harmer
0.901
316327AA2-057 GEN
Solar/Wind Harmer
0.146
3146233WITAKRS
Solar/Wind Harmer
0.48
3146233WITAKRS
Solar/Wind Harmer
0.065
3138543CONSLDL
Solar/Wind Harmer
0.063
961601AG1-000A GEN
Solar/Wind Harmer
6.766
3146263WOODLND
Solar/Wind Harmer
0.095
971623AH1-311 GEN
Solar/Wind Harmer
0.189
3145543BTLEBRO
Solar/Wind Harmer
0.094
3145543BTLEBRO
Solar/Wind Harmer
0.094
316478AD1-087 GEN
Solar/Wind Harmer
0.329
316486AD2-202 GEN
Solar/Wind Harmer
0.097
316317KELFORD C
Solar/Wind Harmer
0.009
3145823KELFORD
Solar/Wind Harmer
0.092
3146073TAR RVR
Solar/Wind Harmer
0.092
3146083TARBORO
Solar/Wind Harmer
0.092
316463AE2-346 GEN
Solar/Wind Harmer
0.076
316140AB2-099
Solar/Wind Harmer
0.032
962331AG1-082 GEN
Solar/Wind Harmer
0.95
3146173TUNIS
Solar/Wind Harmer
0.088
957521AF2-046 GEN
Solar/Wind Harmer
6.513
961681AG1-008 GEN
Solar/Wind Harmer
6.513
3145893MURPHYS
Solar/Wind Harmer
0.146
3145893MURPHYS
Solar/Wind Harmer
0.087
3156021HOLLOMANSOL
Solar/Wind Harmer
0.393
3145746EVERETS
Solar/Wind Harmer
0.085
3145746EVERETS
Solar/Wind Harmer
0.085
316131AB2-060 GEN
Solar/Wind Harmer
0.268
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3145933PARMELE
Solar/Wind Harmer
0.084
966801AG1-551 GEN
Solar/Wind Harmer
0.976
964241AG1-285 GEN
Solar/Wind Harmer
5.485
3146206CASHIE
Solar/Wind Harmer
0.08
3145963POPLR C
Solar/Wind Harmer
0.08
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.344
315785AD2-033 C
Solar/Wind Harmer
0.629
315737AD1-076 GEN
Solar/Wind Harmer
0.983
971157AH1-035 GEN
Solar/Wind Harmer
0.908
970257AG2-171 GEN
Solar/Wind Harmer
2.416
959311AF2-222 GEN
Solar/Wind Harmer
6.592
316283AC2-100 C
Solar/Wind Harmer
0.142
315614AA2-178 GEN
Solar/Wind Harmer
0.41
971683AH1-343 GEN
Solar/Wind Harmer
2.584
3146376EDENTON
Solar/Wind Harmer
0.067
963181AG1-167 GEN
Solar/Wind Harmer
0.266
3144293JTRSVLE
Adder
0.211
970909AG2-566 GEN
Solar/Wind Harmer
0.692
3147133PAMPLIN
Solar/Wind Harmer
0.199
971193AH1-056 GEN
Solar/Wind Harmer
3.857
315773AC2-141 GEN
Solar/Wind Harmer
2.248
3146626S HERTFORD
Solar/Wind Harmer
0.061
3145273HOLLAND
Solar/Wind Harmer
0.046
3146516WINFALL
Solar/Wind Harmer
0.06
316435W1029_GEN3
Solar/Wind Harmer
0
316320Y1-086
Solar/Wind Harmer
0
944581AF1-123 GEN
Solar/Wind Harmer
12.66
944601AF1-125 GEN
Solar/Wind Harmer
12.465
315839AE2-212 C
Solar/Wind Helper
0.986
316473AC1-191 GEN
Solar/Wind Helper
0.925
3142946ENON
Solar/Wind Helper
0.049
970533AG2-339 GEN
50/50
10.894
970531AG2-338 GEN
50/50
4.358
3151361ROSEMG1
50/50
0.433
3151371ROSEMS1
50/50
0.268
3151381ROSEMG2
50/50
0.203
315242AE2-183_GT2
50/50
1.956
315241AE2-183_GT1
50/50
1.944
972185AH1-677 GEN
50/50
7.053
3151041BRUNSWICKG3
50/50
1.536
972187AH1-678 GEN
50/50
3.524
970535AG2-341 GEN
50/50
1.57
3152661PLYWOOD A
50/50
0.18
3144356SAPONY
Solar/Wind Harmer
1.857
316181AB2-040 GEN
Solar/Wind Harmer
0.181
3145796HORNRTN
Solar/Wind Harmer
0.361
3142666NORTHAMPTON
Solar/Wind Harmer
0.119
3142666NORTHAMPTON
Solar/Wind Harmer
0.119
3142666NORTHAMPTON
Solar/Wind Harmer
0.119
3142666NORTHAMPTON
Solar/Wind Harmer
0.072
970933AG2-581 GEN
Solar/Wind Harmer
8.936
3145593CAROLNA
Solar/Wind Harmer
0.109
3145593CAROLNA
Solar/Wind Harmer
0.109
966811AG1-552 GEN
Solar/Wind Harmer
1.182
3145593CAROLNA
Solar/Wind Harmer
0.136
3145783HORNRTN
Solar/Wind Harmer
1.911
3145783HORNRTN
Solar/Wind Harmer
1.529
3145783HORNRTN
Solar/Wind Harmer
0.478
3145783HORNRTN
Solar/Wind Harmer
0.191
316426AA2-053 GEN
Solar/Wind Harmer
0.356
316274AC1-208 GEN
Solar/Wind Harmer
0.518
970099AG2-077 GEN
Solar/Wind Harmer
10.582
961601AG1-000A GEN
Solar/Wind Harmer
1.691
316263AC1-034 GEN
Solar/Wind Harmer
3.592
3145493TOT1
Solar/Wind Harmer
0.212
3145453TOT5
Solar/Wind Harmer
0.127
3145603CNETO
Solar/Wind Harmer
0.085
939181AE1-148 GEN
Solar/Wind Harmer
4.3
3146173TUNIS
Solar/Wind Harmer
0.088
3146173TUNIS
Solar/Wind Harmer
0.088
3145893MURPHYS
Solar/Wind Harmer
0.583
3145893MURPHYS
Solar/Wind Harmer
0.157
313527AB2-043 GEN
Solar/Wind Harmer
0.001
3145933PARMELE
Solar/Wind Harmer
0.168
3145933PARMELE
Solar/Wind Harmer
0.084
962561AG1-105 GEN
Solar/Wind Harmer
3.947
964791AG1-342 GEN
Solar/Wind Harmer
1.566
3146843MT LREL
Solar/Wind Harmer
0.081
3146843MT LREL
Solar/Wind Harmer
0.081
316065AD1-022 GEN
Solar/Wind Harmer
3.64
970323AG2-213 GEN
Solar/Wind Harmer
3.221
971775AH1-396 GEN
Solar/Wind Harmer
0.121
316034AC1-036 C
Solar/Wind Harmer
0.005
316222AC1-221 GEN
Solar/Wind Harmer
0.303
971741AH1-377 GEN
Solar/Wind Harmer
7.057
3146376EDENTON
Solar/Wind Harmer
0.296
3146376EDENTON
Solar/Wind Harmer
0.296
958211AF2-115 GEN
Solar/Wind Harmer
0.797
963191AG1-168 GEN
Solar/Wind Harmer
0.266
3144293JTRSVLE
Adder
0.211
3144293JTRSVLE
Adder
0.178
315742AE1-103 GEN
Solar/Wind Harmer
0.001
970301AG2-198 GEN
Solar/Wind Harmer
2.77
3147133PAMPLIN
Solar/Wind Harmer
0.063
3147133PAMPLIN
Solar/Wind Harmer
0.051
3146626S HERTFORD
Solar/Wind Harmer
0.061
3146626S HERTFORD
Solar/Wind Harmer
0.061
3146516WINFALL
Solar/Wind Harmer
0.06
3146516WINFALL
Solar/Wind Harmer
0.06
3146516WINFALL
Solar/Wind Harmer
0.06
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3146386ELIZ CT
Solar/Wind Harmer
0.057
316240AF1-291 C
Solar/Wind Helper
0.411
966871AG1-558 GEN
Solar/Wind Helper
0.204
3142946ENON
Solar/Wind Helper
0.015
3143526WINTERP
Solar/Wind Helper
0.72
316468AD1-105 GEN
Solar/Wind Helper
0.653
316075AC2-137 C
Solar/Wind Helper
0.178
LAGNLTFEXP_LAGN->PJM
CLTF
3.79
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.991
TVALTFEXP_TVA->PJM
CLTF
1.888
CPLELTFEXP_CPLE->PJM
CLTF
5.631
CBM West 2LTFEXP_CBM-W2->PJM
CBM
19.951
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.11
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.461
MECLTFEXP_MEC->PJM
CLTF
1.839
SIGELTFEXP_SIGE->PJM
CLTF
0.055
NYPJM->LTFIMP_NY
CLTF
0.691
LGEELTFEXP_LGEE->PJM
CLTF
0.659
WECLTFEXP_WEC->PJM
CLTF
0.343

Details for 6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2002_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.0 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1171.16
MW Contribution:3.62
Bus #Bus NameTypeMW Contribution
3151391GASTONA
50/50
0.32
3151411GASTONB
50/50
0.32
3151261ROARAP2
50/50
0.119
3151031BRUNSWICKG2
50/50
1.193
3151591KERR 2
50/50
0.157
970413AG2-270 GEN
50/50
6.966
316365GEN2_N
Solar/Wind Harmer
0.362
313506AB2-031 GEN
Solar/Wind Harmer
0.366
3147043LAWRENC
Solar/Wind Harmer
0.071
3145796HORNRTN
Solar/Wind Harmer
0.453
3145796HORNRTN
Solar/Wind Harmer
0.113
3142666NORTHAMPTON
Solar/Wind Harmer
0.111
315724AD1-057 GEN
Solar/Wind Harmer
0.363
970917AG2-570 GEN
Solar/Wind Harmer
7.751
316327AA2-057 GEN
Solar/Wind Harmer
0.127
961601AG1-000A GEN
Solar/Wind Harmer
5.909
316210AC1-098 GEN
Solar/Wind Harmer
0.77
3146233WITAKRS
Solar/Wind Harmer
0.417
3146233WITAKRS
Solar/Wind Harmer
0.056
3138543CONSLDL
Solar/Wind Harmer
0.055
971623AH1-311 GEN
Solar/Wind Harmer
0.164
3145543BTLEBRO
Solar/Wind Harmer
0.082
3145543BTLEBRO
Solar/Wind Harmer
0.082
3146263WOODLND
Solar/Wind Harmer
0.078
3146073TAR RVR
Solar/Wind Harmer
0.078
3146083TARBORO
Solar/Wind Harmer
0.078
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.075
316478AD1-087 GEN
Solar/Wind Harmer
0.26
316486AD2-202 GEN
Solar/Wind Harmer
0.076
316131AB2-060 GEN
Solar/Wind Harmer
0.229
964241AG1-285 GEN
Solar/Wind Harmer
4.665
316463AE2-346 GEN
Solar/Wind Harmer
0.06
316140AB2-099
Solar/Wind Harmer
0.025
962331AG1-082 GEN
Solar/Wind Harmer
0.742
3145746EVERETS
Solar/Wind Harmer
0.069
3145746EVERETS
Solar/Wind Harmer
0.069
3146173TUNIS
Solar/Wind Harmer
0.068
3156021HOLLOMANSOL
Solar/Wind Harmer
0.305
3145933PARMELE
Solar/Wind Harmer
0.066
966801AG1-551 GEN
Solar/Wind Harmer
0.769
957521AF2-046 GEN
Solar/Wind Harmer
4.888
961681AG1-008 GEN
Solar/Wind Harmer
4.888
315785AD2-033 C
Solar/Wind Harmer
0.532
3145893MURPHYS
Solar/Wind Harmer
0.108
3145893MURPHYS
Solar/Wind Harmer
0.065
970257AG2-171 GEN
Solar/Wind Harmer
2.041
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
2.715
959311AF2-222 GEN
Solar/Wind Harmer
5.561
3145963POPLR C
Solar/Wind Harmer
0.06
3156081AA2-088 GEN
Solar/Wind Harmer
0.001
3146206CASHIE
Solar/Wind Harmer
0.059
316283AC2-100 C
Solar/Wind Harmer
0.115
971683AH1-343 GEN
Solar/Wind Harmer
2.095
315839AE2-212 C
Solar/Wind Helper
1.113
3142946ENON
Solar/Wind Helper
0.074
316473AC1-191 GEN
Solar/Wind Helper
1.189
316280AD1-041 GEN
Solar/Wind Helper
0.416
316404AE1-155 C
Solar/Wind Helper
0.956
316484AD2-074 GEN
Solar/Wind Helper
0.219
316156AD2-030 GEN
Solar/Wind Helper
0.171
3151391GASTONA
50/50
0.32
3151411GASTONB
50/50
0.32
3147043LAWRENC
50/50
1.13
3151261ROARAP2
50/50
0.121
315243AE2-183_GT3
50/50
1.518
3151051BRUNSWICKS1
50/50
2.476
3151021BRUNSWICKG1
50/50
1.193
971451AH1-221 GEN
50/50
3.623
3151601KERR 3
50/50
0.157
3151581KERR 1
50/50
0.056
3151531CLOVER1
50/50
1.596
316023GEN1_S
Solar/Wind Harmer
0.362
960081AF2-299 GEN
Solar/Wind Harmer
1.316
971795AH1-408 GEN
Solar/Wind Harmer
8.254
316011AB1-132 GEN
Solar/Wind Harmer
2.152
962571AG1-106 GEN
Solar/Wind Harmer
1.684
3145796HORNRTN
Solar/Wind Harmer
0.374
3145796HORNRTN
Solar/Wind Harmer
0.113
315722AD1-056 GEN
Solar/Wind Harmer
0.612
3145783HORNRTN
Solar/Wind Harmer
0.096
316190AA2-174 GEN
Solar/Wind Harmer
0
970919AG2-571 GEN
Solar/Wind Harmer
3.101
970087AG2-069 GEN
Solar/Wind Harmer
6.946
940641AE2-051 GEN
Solar/Wind Harmer
6.931
316129AC1-054 GEN
Solar/Wind Harmer
0.314
316212AC1-099_GEN
Solar/Wind Harmer
0.43
3146233WITAKRS
Solar/Wind Harmer
0.33
971065AG2-659 GEN
Solar/Wind Harmer
3.51
316359AB2-059 GEN
Solar/Wind Harmer
0.295
316049AB1-081 GEN
Solar/Wind Harmer
0.471
3142053HEARTS
Solar/Wind Harmer
0.145
3145543BTLEBRO
Solar/Wind Harmer
0.082
3145543BTLEBRO
Solar/Wind Harmer
0.066
3146263WOODLND
Solar/Wind Harmer
0.078
957481AF2-042 GEN
Solar/Wind Harmer
20.812
961671AG1-007 GEN
Solar/Wind Harmer
0.012
3146083TARBORO
Solar/Wind Harmer
0.078
3145493TOT1
Solar/Wind Harmer
0.346
3145823KELFORD
Solar/Wind Harmer
0.075
316494AC1-189 GEN
Solar/Wind Harmer
0.249
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
3.49
962491AG1-098 GEN
Solar/Wind Harmer
4.086
3145683EARLEYS
Solar/Wind Harmer
0.071
315687AD1-152 GEN
Solar/Wind Harmer
0.002
939411AE1-173 GEN
Solar/Wind Harmer
30.084
3145746EVERETS
Solar/Wind Harmer
0.069
3145746EVERETS
Solar/Wind Harmer
0.069
3146173TUNIS
Solar/Wind Harmer
0.068
970401AG2-262 GEN
Solar/Wind Harmer
0.397
3146293MARTNCO
Solar/Wind Harmer
0.061
3145893MURPHYS
Solar/Wind Harmer
0.259
3145893MURPHYS
Solar/Wind Harmer
0.288
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3145963POPLR C
Solar/Wind Harmer
0.06
316003AC1-222 GEN
Solar/Wind Harmer
0.002
970685AG2-442 GEN
Solar/Wind Harmer
4.444
3146206CASHIE
Solar/Wind Harmer
0.059
971547AH1-271 GEN
Solar/Wind Harmer
1.257
3142543TWELFTH
Solar/Wind Helper
0.031
316458AB2-190 GEN2
Solar/Wind Helper
1.544
316381AD1-082 GEN
Solar/Wind Helper
1.346
3142433PROV 92
Solar/Wind Helper
0.863
3142416OLDCHRC
Solar/Wind Helper
0.448
3142416OLDCHRC
Solar/Wind Helper
0.172
3143526WINTERP
Solar/Wind Helper
0.727
3141766HARMONY
Solar/Wind Helper
0.024
964211AG1-282 GEN
Solar/Wind Helper
0.157
315779AE2-040
50/50
3.401
3151281ROARAP4
50/50
0.118
3151281ROARAP4
50/50
0.11
315244AE2-183_ST
50/50
2.625
963041AG1-153 GEN
50/50
2.415
3151611KERR 4
50/50
0.157
3151621KERR 5
50/50
0.157
3151631KERR 6
50/50
0.157
3151641KERR 7
50/50
0.157
3151541CLOVER2
50/50
1.589
316315AB2-025 C
Solar/Wind Harmer
0.197
315814AE2-033 C
Solar/Wind Harmer
18.936
316087AB2-174 GEN
Solar/Wind Harmer
0.004
315652AC1-086 GEN
Solar/Wind Harmer
13.019
3145796HORNRTN
Solar/Wind Harmer
0.362
3145796HORNRTN
Solar/Wind Harmer
0.045
3137643SOCKMAN
Solar/Wind Harmer
0.427
941031AE2-094 GEN
Solar/Wind Harmer
17.475
944011AF1-069 GEN
Solar/Wind Harmer
5.71
970673AG2-436 GEN
Solar/Wind Harmer
19.819
970673AG2-436 GEN
Solar/Wind Harmer
13.213
971967AH1-528 GEN
Solar/Wind Harmer
14.51
970085AG2-068 GEN
Solar/Wind Harmer
4.631
970581AG2-369 GEN
Solar/Wind Harmer
3.982
970831AG2-522 GEN
Solar/Wind Harmer
3.621
315607AA1-063A GEN
Solar/Wind Harmer
0.17
316319Z2-044 C
Solar/Wind Harmer
0
3146043SEABORD
Solar/Wind Harmer
0.081
3146033SCOT NK
Solar/Wind Harmer
0.318
3145573BETHELC
Solar/Wind Harmer
0.078
3145573BETHELC
Solar/Wind Harmer
0.078
316420AA1-050 GEN
Solar/Wind Harmer
0.003
957861AF2-080 GEN
Solar/Wind Harmer
3.178
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
3145683EARLEYS
Solar/Wind Harmer
0.142
3145683EARLEYS
Solar/Wind Harmer
0.071
3145683EARLEYS
Solar/Wind Harmer
0.071
3145513AHOSKIE
Solar/Wind Harmer
0.145
3145513AHOSKIE
Solar/Wind Harmer
0.07
316005AA1-067
Solar/Wind Harmer
0.074
3145746EVERETS
Solar/Wind Harmer
0.274
3145746EVERETS
Solar/Wind Harmer
0.069
3145746EVERETS
Solar/Wind Harmer
0.069
3145746EVERETS
Solar/Wind Harmer
0.069
970181AG2-120 GEN
Solar/Wind Harmer
0.856
316118AC1-105 GEN
Solar/Wind Harmer
0.169
3145893MURPHYS
Solar/Wind Harmer
0.175
3145893MURPHYS
Solar/Wind Harmer
0.065
971443AH1-215 GEN
Solar/Wind Harmer
1.078
3144303KENBRDG
Solar/Wind Harmer
0.051
3147173SINAI
Solar/Wind Harmer
0.064
3147243WELCO
Solar/Wind Harmer
0.04
965291AG1-394 GEN
Solar/Wind Harmer
0.275
970683AG2-441 GEN
Solar/Wind Harmer
3.967
970681AG2-440 GEN
Solar/Wind Harmer
3.174
3146206CASHIE
Solar/Wind Harmer
0.059
970601AG2-382 GEN
Solar/Wind Harmer
2.2
3143316POE
Solar/Wind Helper
1.93
316132AB2-190 GEN1
Solar/Wind Helper
1.544
316369SG1_INVT
Solar/Wind Helper
1.002
316312AB1-027
Solar/Wind Helper
0.328
3143873LANEXA
Solar/Wind Helper
0.095
316233AE1-074 FULL
Solar/Wind Helper
0.214
315662AE1-191 GEN
Solar/Wind Helper
0.666
315666AE1-190 GEN
Solar/Wind Helper
0.167
316059AD1-063 C
Solar/Wind Helper
0.122
3141813NORNECK
Solar/Wind Helper
0.113
3141783LANCAST
Solar/Wind Helper
0.068
3141783LANCAST
Solar/Wind Helper
0.045
3141913WHIT STONE
Solar/Wind Helper
0.113
3138133OCRAN
Solar/Wind Helper
0.034
957601AF2-054 GEN
Solar/Wind Helper
0.152
3141873WAN 176
Solar/Wind Helper
0.023
3141726DUNNSVL
Solar/Wind Helper
0.465
3138133OCRAN
Solar/Wind Helper
0.068
3151361ROSEMG1
50/50
0.408
3151371ROSEMS1
50/50
0.253
3151381ROSEMG2
50/50
0.191
970533AG2-339 GEN
50/50
8.434
970531AG2-338 GEN
50/50
3.373
315242AE2-183_GT2
50/50
1.518
315241AE2-183_GT1
50/50
1.509
972185AH1-677 GEN
50/50
5.473
3151041BRUNSWICKG3
50/50
1.193
972187AH1-678 GEN
50/50
2.737
970535AG2-341 GEN
50/50
1.329
3152661PLYWOOD A
50/50
0.148
3144356SAPONY
Solar/Wind Harmer
2.038
316181AB2-040 GEN
Solar/Wind Harmer
0.172
3145796HORNRTN
Solar/Wind Harmer
0.34
3142666NORTHAMPTON
Solar/Wind Harmer
0.111
3142666NORTHAMPTON
Solar/Wind Harmer
0.111
3142666NORTHAMPTON
Solar/Wind Harmer
0.111
3142666NORTHAMPTON
Solar/Wind Harmer
0.067
3145593CAROLNA
Solar/Wind Harmer
0.097
3145593CAROLNA
Solar/Wind Harmer
0.097
966811AG1-552 GEN
Solar/Wind Harmer
1.057
3145593CAROLNA
Solar/Wind Harmer
0.121
3145783HORNRTN
Solar/Wind Harmer
1.703
3145783HORNRTN
Solar/Wind Harmer
1.362
3145783HORNRTN
Solar/Wind Harmer
0.426
3145783HORNRTN
Solar/Wind Harmer
0.17
316426AA2-053 GEN
Solar/Wind Harmer
0.313
970933AG2-581 GEN
Solar/Wind Harmer
6.963
316274AC1-208 GEN
Solar/Wind Harmer
0.45
961601AG1-000A GEN
Solar/Wind Harmer
1.477
316263AC1-034 GEN
Solar/Wind Harmer
3.125
970099AG2-077 GEN
Solar/Wind Harmer
8.325
3145493TOT1
Solar/Wind Harmer
0.181
3145453TOT5
Solar/Wind Harmer
0.108
3145603CNETO
Solar/Wind Harmer
0.072
939181AE1-148 GEN
Solar/Wind Harmer
3.627
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
3.291
3146173TUNIS
Solar/Wind Harmer
0.068
3146173TUNIS
Solar/Wind Harmer
0.068
964791AG1-342 GEN
Solar/Wind Harmer
1.3
3146843MT LREL
Solar/Wind Harmer
0.068
3146843MT LREL
Solar/Wind Harmer
0.068
3145933PARMELE
Solar/Wind Harmer
0.132
3145933PARMELE
Solar/Wind Harmer
0.066
3145893MURPHYS
Solar/Wind Harmer
0.433
3145893MURPHYS
Solar/Wind Harmer
0.116
970323AG2-213 GEN
Solar/Wind Harmer
2.721
971775AH1-396 GEN
Solar/Wind Harmer
0.102
316034AC1-036 C
Solar/Wind Harmer
0.005
316222AC1-221 GEN
Solar/Wind Harmer
0.245
316065AD1-022 GEN
Solar/Wind Harmer
2.617
971741AH1-377 GEN
Solar/Wind Harmer
5.589
316240AF1-291 C
Solar/Wind Helper
0.691
3142946ENON
Solar/Wind Helper
0.022
316033AB2-134 GEN
Solar/Wind Helper
0.717
315697AD1-025 GEN
Solar/Wind Helper
2.382
966871AG1-558 GEN
Solar/Wind Helper
0.262
316075AC2-137 C
Solar/Wind Helper
0.263
316468AD1-105 GEN
Solar/Wind Helper
0.815
3143526WINTERP
Solar/Wind Helper
0.727
316077AC2-138 C
Solar/Wind Helper
0.107
316487AF1-042 GEN
Solar/Wind Helper
0.114
LAGNLTFEXP_LAGN->PJM
CLTF
3.11
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.716
TVALTFEXP_TVA->PJM
CLTF
1.547
CPLELTFEXP_CPLE->PJM
CLTF
4.572
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.518
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.423
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.312
MECLTFEXP_MEC->PJM
CLTF
1.548
SIGELTFEXP_SIGE->PJM
CLTF
0.046
NYPJM->LTFIMP_NY
CLTF
0.457
LGEELTFEXP_LGEE->PJM
CLTF
0.557
WECLTFEXP_WEC->PJM
CLTF
0.293

Details for 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:167.04 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:934.25
MW Contribution:3.37
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.227
970413AG2-270 GEN
50/50
14.4
3151591KERR 2
50/50
0.315
3151261ROARAP2
50/50
0.107
3151031BRUNSWICKG2
50/50
1.109
3151391GASTONA
50/50
0.198
3151411GASTONB
50/50
0.198
3146926FARMVIL
Solar/Wind Harmer
0.322
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
4.196
3147133PAMPLIN
Solar/Wind Harmer
1.218
971193AH1-056 GEN
Solar/Wind Harmer
23.635
963181AG1-167 GEN
Solar/Wind Harmer
1.454
959311AF2-222 GEN
Solar/Wind Harmer
26.76
970257AG2-171 GEN
Solar/Wind Harmer
9.287
315785AD2-033 C
Solar/Wind Harmer
2.238
964241AG1-285 GEN
Solar/Wind Harmer
15.712
316131AB2-060 GEN
Solar/Wind Harmer
0.665
316478AD1-087 GEN
Solar/Wind Harmer
0.537
316486AD2-202 GEN
Solar/Wind Harmer
0.158
3147043LAWRENC
Solar/Wind Harmer
0.077
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
5.403
971683AH1-343 GEN
Solar/Wind Harmer
4.014
313506AB2-031 GEN
Solar/Wind Harmer
0.283
316283AC2-100 C
Solar/Wind Harmer
0.162
970917AG2-570 GEN
Solar/Wind Harmer
7.29
316210AC1-098 GEN
Solar/Wind Harmer
0.693
316327AA2-057 GEN
Solar/Wind Harmer
0.111
3151541CLOVER2
50/50
3.284
3151611KERR 4
50/50
0.315
3151621KERR 5
50/50
0.315
3151631KERR 6
50/50
0.315
3151641KERR 7
50/50
0.315
3151281ROARAP4
50/50
0.107
3151281ROARAP4
50/50
0.1
963041AG1-153 GEN
50/50
2.246
315244AE2-183_ST
50/50
2.348
315657AE1-056 GEN
Solar/Wind Harmer
13.387
946301AF1-294 GEN
Solar/Wind Harmer
7.171
961791AG1-021 GEN
Solar/Wind Harmer
3.489
970683AG2-441 GEN
Solar/Wind Harmer
21.861
970681AG2-440 GEN
Solar/Wind Harmer
17.489
3144303KENBRDG
Solar/Wind Harmer
0.232
971443AH1-215 GEN
Solar/Wind Harmer
4.821
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.369
3147173SINAI
Solar/Wind Harmer
0.127
3147243WELCO
Solar/Wind Harmer
0.079
970831AG2-522 GEN
Solar/Wind Harmer
5.372
970865AG2-541 GEN
Solar/Wind Harmer
3.489
971967AH1-528 GEN
Solar/Wind Harmer
15.071
316087AB2-174 GEN
Solar/Wind Harmer
0.003
3137643SOCKMAN
Solar/Wind Harmer
0.359
316123AC1-075 GEN
Solar/Wind Harmer
0.114
970165AG2-112 GEN
Solar/Wind Harmer
0.676
970163AG2-111 GEN
Solar/Wind Harmer
0.645
315607AA1-063A GEN
Solar/Wind Harmer
0.167
970085AG2-068 GEN
Solar/Wind Harmer
4.361
970581AG2-369 GEN
Solar/Wind Harmer
3.75
3146043SEABORD
Solar/Wind Harmer
0.081
970673AG2-436 GEN
Solar/Wind Harmer
17.208
970673AG2-436 GEN
Solar/Wind Harmer
11.472
941031AE2-094 GEN
Solar/Wind Harmer
14.299
944011AF1-069 GEN
Solar/Wind Harmer
4.672
315652AC1-086 GEN
Solar/Wind Harmer
8.029
3146033SCOT NK
Solar/Wind Harmer
0.291
3145796HORNRTN
Solar/Wind Harmer
0.232
3145796HORNRTN
Solar/Wind Harmer
0.029
965291AG1-394 GEN
Solar/Wind Harmer
0.32
316319Z2-044 C
Solar/Wind Harmer
0
3145893MURPHYS
Solar/Wind Harmer
0.191
3145893MURPHYS
Solar/Wind Harmer
0.071
3145513AHOSKIE
Solar/Wind Harmer
0.144
3145513AHOSKIE
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.136
3145683EARLEYS
Solar/Wind Harmer
0.068
3145683EARLEYS
Solar/Wind Harmer
0.068
3145573BETHELC
Solar/Wind Harmer
0.067
3145573BETHELC
Solar/Wind Harmer
0.067
316420AA1-050 GEN
Solar/Wind Harmer
0.002
957861AF2-080 GEN
Solar/Wind Harmer
2.854
316005AA1-067
Solar/Wind Harmer
0.069
3145746EVERETS
Solar/Wind Harmer
0.257
3145746EVERETS
Solar/Wind Harmer
0.065
3145746EVERETS
Solar/Wind Harmer
0.065
3145746EVERETS
Solar/Wind Harmer
0.065
970181AG2-120 GEN
Solar/Wind Harmer
0.805
315814AE2-033 C
Solar/Wind Harmer
4.945
316315AB2-025 C
Solar/Wind Harmer
0.05
3146206CASHIE
Solar/Wind Harmer
0.062
970601AG2-382 GEN
Solar/Wind Harmer
2.302
315732AD1-074 GEN1
Solar/Wind Harmer
0.345
315733AD1-074 GEN2
Solar/Wind Harmer
0.345
315735AD1-075 GEN1
Solar/Wind Harmer
0.173
3130546PLYMOUTH
Solar/Wind Harmer
0.06
315816AE2-034 GEN
Solar/Wind Harmer
0.249
270494AE1-108_GEN
Solar/Wind Helper
4.45
3138266HYDRAULIC
Solar/Wind Helper
0.009
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3144293JTRSVLE
50/50
1.227
3151531CLOVER1
50/50
3.3
3151601KERR 3
50/50
0.315
3151581KERR 1
50/50
0.112
3147043LAWRENC
50/50
1.233
3151261ROARAP2
50/50
0.11
3151051BRUNSWICKS1
50/50
2.302
3151021BRUNSWICKG1
50/50
1.109
971451AH1-221 GEN
50/50
3.369
315243AE2-183_GT3
50/50
1.358
3151391GASTONA
50/50
0.198
3151411GASTONB
50/50
0.198
3146926FARMVIL
Solar/Wind Harmer
0.322
963171AG1-166 GEN
Solar/Wind Harmer
1.938
971563AH1-280 GEN
Solar/Wind Harmer
3.876
970685AG2-442 GEN
Solar/Wind Harmer
24.484
962491AG1-098 GEN
Solar/Wind Harmer
11.925
316237AB2-079_GEN
Solar/Wind Harmer
0.002
315693AD1-088 GEN
Solar/Wind Harmer
9.548
970401AG2-262 GEN
Solar/Wind Harmer
0.937
957481AF2-042 GEN
Solar/Wind Harmer
40.4
315687AD1-152 GEN
Solar/Wind Harmer
0.005
971065AG2-659 GEN
Solar/Wind Harmer
5.702
316129AC1-054 GEN
Solar/Wind Harmer
0.489
971795AH1-408 GEN
Solar/Wind Harmer
7.855
316003AC1-222 GEN
Solar/Wind Harmer
0.003
960081AF2-299 GEN
Solar/Wind Harmer
0.909
3145783HORNRTN
Solar/Wind Harmer
0.086
316190AA2-174 GEN
Solar/Wind Harmer
0
970919AG2-571 GEN
Solar/Wind Harmer
2.916
970087AG2-069 GEN
Solar/Wind Harmer
6.541
316212AC1-099_GEN
Solar/Wind Harmer
0.387
3146263WOODLND
Solar/Wind Harmer
0.074
316011AB1-132 GEN
Solar/Wind Harmer
1.327
316023GEN1_S
Solar/Wind Harmer
0.164
962571AG1-106 GEN
Solar/Wind Harmer
1.039
3145796HORNRTN
Solar/Wind Harmer
0.239
3145796HORNRTN
Solar/Wind Harmer
0.072
3146233WITAKRS
Solar/Wind Harmer
0.286
3145893MURPHYS
Solar/Wind Harmer
0.283
3145893MURPHYS
Solar/Wind Harmer
0.314
315722AD1-056 GEN
Solar/Wind Harmer
0.447
3145823KELFORD
Solar/Wind Harmer
0.07
3145543BTLEBRO
Solar/Wind Harmer
0.07
3145543BTLEBRO
Solar/Wind Harmer
0.056
316359AB2-059 GEN
Solar/Wind Harmer
0.251
316049AB1-081 GEN
Solar/Wind Harmer
0.4
3142053HEARTS
Solar/Wind Harmer
0.123
3146173TUNIS
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.068
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.067
3145493TOT1
Solar/Wind Harmer
0.3
940641AE2-051 GEN
Solar/Wind Harmer
5.396
316494AC1-189 GEN
Solar/Wind Harmer
0.224
3145746EVERETS
Solar/Wind Harmer
0.065
3145746EVERETS
Solar/Wind Harmer
0.065
3146293MARTNCO
Solar/Wind Harmer
0.059
939411AE1-173 GEN
Solar/Wind Harmer
26.923
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3145963POPLR C
Solar/Wind Harmer
0.062
3146206CASHIE
Solar/Wind Harmer
0.062
971547AH1-271 GEN
Solar/Wind Harmer
1.316
3145663CRESWEL
Solar/Wind Harmer
0.162
971163AH1-040 GEN
Solar/Wind Harmer
4.641
316322AB2-045
Solar/Wind Helper
0.957
3146776BUCKING
Solar/Wind Helper
0.343
316336AC2-165 C
Solar/Wind Helper
1.513
3146263WOODLND
Solar/Wind Harmer
0.074
316365GEN2_N
Solar/Wind Harmer
0.164
3142666NORTHAMPTON
Solar/Wind Harmer
0.072
3145796HORNRTN
Solar/Wind Harmer
0.29
3145796HORNRTN
Solar/Wind Harmer
0.072
3146233WITAKRS
Solar/Wind Harmer
0.361
3146233WITAKRS
Solar/Wind Harmer
0.049
3138543CONSLDL
Solar/Wind Harmer
0.047
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3145893MURPHYS
Solar/Wind Harmer
0.118
3145893MURPHYS
Solar/Wind Harmer
0.071
315724AD1-057 GEN
Solar/Wind Harmer
0.265
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.07
957521AF2-046 GEN
Solar/Wind Harmer
5.233
961681AG1-008 GEN
Solar/Wind Harmer
5.233
3145543BTLEBRO
Solar/Wind Harmer
0.07
3145543BTLEBRO
Solar/Wind Harmer
0.07
971623AH1-311 GEN
Solar/Wind Harmer
0.14
3146173TUNIS
Solar/Wind Harmer
0.069
961601AG1-000A GEN
Solar/Wind Harmer
4.909
316463AE2-346 GEN
Solar/Wind Harmer
0.059
316140AB2-099
Solar/Wind Harmer
0.025
962331AG1-082 GEN
Solar/Wind Harmer
0.733
3146073TAR RVR
Solar/Wind Harmer
0.067
3146083TARBORO
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.065
3145746EVERETS
Solar/Wind Harmer
0.065
3156021HOLLOMANSOL
Solar/Wind Harmer
0.291
3145933PARMELE
Solar/Wind Harmer
0.064
966801AG1-551 GEN
Solar/Wind Harmer
0.744
3145963POPLR C
Solar/Wind Harmer
0.062
3146206CASHIE
Solar/Wind Harmer
0.062
315737AD1-076 GEN
Solar/Wind Harmer
0.772
971157AH1-035 GEN
Solar/Wind Harmer
0.716
315614AA2-178 GEN
Solar/Wind Harmer
0.332
3145273HOLLAND
Solar/Wind Harmer
0.043
3146776BUCKING
Solar/Wind Helper
0.309
316313AB2-026
Solar/Wind Helper
0.361
316258AE1-075 C
Solar/Wind Helper
0.325
316405AF2-144 C
Solar/Wind Helper
0.271
3148013FISHERV
Solar/Wind Helper
0.126
3144293JTRSVLE
50/50
1.227
3144293JTRSVLE
50/50
1.034
970535AG2-341 GEN
50/50
3.152
3152661PLYWOOD A
50/50
0.306
3151041BRUNSWICKG3
50/50
1.109
972187AH1-678 GEN
50/50
2.545
315242AE2-183_GT2
50/50
1.358
315241AE2-183_GT1
50/50
1.35
972185AH1-677 GEN
50/50
4.896
970533AG2-339 GEN
50/50
6.901
970531AG2-338 GEN
50/50
2.76
3151361ROSEMG1
50/50
0.261
3151371ROSEMS1
50/50
0.162
3151381ROSEMG2
50/50
0.122
970301AG2-198 GEN
Solar/Wind Harmer
16.784
3147133PAMPLIN
Solar/Wind Harmer
0.388
3147133PAMPLIN
Solar/Wind Harmer
0.31
958211AF2-115 GEN
Solar/Wind Harmer
4.361
963191AG1-168 GEN
Solar/Wind Harmer
1.454
971741AH1-377 GEN
Solar/Wind Harmer
34.597
316034AC1-036 C
Solar/Wind Harmer
0.021
970323AG2-213 GEN
Solar/Wind Harmer
12.383
971775AH1-396 GEN
Solar/Wind Harmer
0.464
313527AB2-043 GEN
Solar/Wind Harmer
0.003
962561AG1-105 GEN
Solar/Wind Harmer
8.006
939181AE1-148 GEN
Solar/Wind Harmer
7.768
964791AG1-342 GEN
Solar/Wind Harmer
3.068
3146843MT LREL
Solar/Wind Harmer
0.159
3146843MT LREL
Solar/Wind Harmer
0.159
970099AG2-077 GEN
Solar/Wind Harmer
16.16
970933AG2-581 GEN
Solar/Wind Harmer
8.957
316181AB2-040 GEN
Solar/Wind Harmer
0.133
3145593CAROLNA
Solar/Wind Harmer
0.088
3145593CAROLNA
Solar/Wind Harmer
0.088
966811AG1-552 GEN
Solar/Wind Harmer
0.957
3145593CAROLNA
Solar/Wind Harmer
0.11
3145783HORNRTN
Solar/Wind Harmer
1.539
3145783HORNRTN
Solar/Wind Harmer
1.231
3145783HORNRTN
Solar/Wind Harmer
0.385
3145783HORNRTN
Solar/Wind Harmer
0.154
316426AA2-053 GEN
Solar/Wind Harmer
0.286
316222AC1-221 GEN
Solar/Wind Harmer
0.347
316274AC1-208 GEN
Solar/Wind Harmer
0.402
3142666NORTHAMPTON
Solar/Wind Harmer
0.072
3142666NORTHAMPTON
Solar/Wind Harmer
0.072
3142666NORTHAMPTON
Solar/Wind Harmer
0.072
3142666NORTHAMPTON
Solar/Wind Harmer
0.044
942751AE2-291 GEN
Solar/Wind Harmer
3.947
3145796HORNRTN
Solar/Wind Harmer
0.217
3145893MURPHYS
Solar/Wind Harmer
0.473
3145893MURPHYS
Solar/Wind Harmer
0.127
316263AC1-034 GEN
Solar/Wind Harmer
2.657
3146173TUNIS
Solar/Wind Harmer
0.069
3146173TUNIS
Solar/Wind Harmer
0.069
961601AG1-000A GEN
Solar/Wind Harmer
1.227
3145493TOT1
Solar/Wind Harmer
0.156
3145453TOT5
Solar/Wind Harmer
0.094
3145603CNETO
Solar/Wind Harmer
0.063
3145933PARMELE
Solar/Wind Harmer
0.128
3145933PARMELE
Solar/Wind Harmer
0.064
3144356SAPONY
Solar/Wind Harmer
0.517
316065AD1-022 GEN
Solar/Wind Harmer
2.811
315742AE1-103 GEN
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Helper
3.433
3146776BUCKING
Solar/Wind Helper
0.278
315821AE2-092 GEN
Solar/Wind Helper
2.985
LAGNLTFEXP_LAGN->PJM
CLTF
2.753
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.143
TVALTFEXP_TVA->PJM
CLTF
1.358
CPLELTFEXP_CPLE->PJM
CLTF
4.949
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.581
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.475
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.539
MECLTFEXP_MEC->PJM
CLTF
1.12
SIGELTFEXP_SIGE->PJM
CLTF
0.032
NYPJM->LTFIMP_NY
CLTF
0.48
LGEELTFEXP_LGEE->PJM
CLTF
0.362
WECLTFEXP_WEC->PJM
CLTF
0.189

Details for 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.32 %
Rating:559.3 MVA
Rating Type:A
MVA to Mitigate:566.67
MW Contribution:2.32
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.183
3151591KERR 2
50/50
0.279
970413AG2-270 GEN
50/50
12.485
3151261ROARAP2
50/50
0.086
3151031BRUNSWICKG2
50/50
0.765
3146926FARMVIL
Solar/Wind Harmer
0.316
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
4.045
3147133PAMPLIN
Solar/Wind Harmer
1.178
971193AH1-056 GEN
Solar/Wind Harmer
22.863
963181AG1-167 GEN
Solar/Wind Harmer
1.401
959311AF2-222 GEN
Solar/Wind Harmer
25.479
970257AG2-171 GEN
Solar/Wind Harmer
8.819
315785AD2-033 C
Solar/Wind Harmer
2.117
964241AG1-285 GEN
Solar/Wind Harmer
14.665
316131AB2-060 GEN
Solar/Wind Harmer
0.615
316478AD1-087 GEN
Solar/Wind Harmer
0.466
316486AD2-202 GEN
Solar/Wind Harmer
0.137
3147043LAWRENC
Solar/Wind Harmer
0.066
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
4.708
971683AH1-343 GEN
Solar/Wind Harmer
3.476
313506AB2-031 GEN
Solar/Wind Harmer
0.227
316283AC2-100 C
Solar/Wind Harmer
0.132
316210AC1-098 GEN
Solar/Wind Harmer
0.531
970917AG2-570 GEN
Solar/Wind Harmer
5.072
316327AA2-057 GEN
Solar/Wind Harmer
0.085
3146776BUCKING
Solar/Wind Helper
0.313
316313AB2-026
Solar/Wind Helper
0.338
316258AE1-075 C
Solar/Wind Helper
0.304
316405AF2-144 C
Solar/Wind Helper
0.253
3148013FISHERV
Solar/Wind Helper
0.123
3144293JTRSVLE
50/50
1.183
3151601KERR 3
50/50
0.279
3151581KERR 1
50/50
0.1
3151531CLOVER1
50/50
2.861
3147043LAWRENC
50/50
1.063
3151261ROARAP2
50/50
0.088
3151051BRUNSWICKS1
50/50
1.588
3151021BRUNSWICKG1
50/50
0.765
971451AH1-221 GEN
50/50
2.324
3146926FARMVIL
Solar/Wind Harmer
0.316
963171AG1-166 GEN
Solar/Wind Harmer
1.868
971563AH1-280 GEN
Solar/Wind Harmer
3.736
970685AG2-442 GEN
Solar/Wind Harmer
23.448
962491AG1-098 GEN
Solar/Wind Harmer
10.797
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
8.584
970401AG2-262 GEN
Solar/Wind Harmer
0.842
957481AF2-042 GEN
Solar/Wind Harmer
34.592
315687AD1-152 GEN
Solar/Wind Harmer
0.004
971065AG2-659 GEN
Solar/Wind Harmer
4.952
316129AC1-054 GEN
Solar/Wind Harmer
0.422
316003AC1-222 GEN
Solar/Wind Harmer
0.003
971795AH1-408 GEN
Solar/Wind Harmer
6.656
960081AF2-299 GEN
Solar/Wind Harmer
0.732
3145783HORNRTN
Solar/Wind Harmer
0.069
316190AA2-174 GEN
Solar/Wind Harmer
0
316212AC1-099_GEN
Solar/Wind Harmer
0.296
970919AG2-571 GEN
Solar/Wind Harmer
2.029
970087AG2-069 GEN
Solar/Wind Harmer
4.556
316322AB2-045
Solar/Wind Helper
0.968
3146776BUCKING
Solar/Wind Helper
0.347
316336AC2-165 C
Solar/Wind Helper
1.445
3151611KERR 4
50/50
0.279
3151621KERR 5
50/50
0.279
3151631KERR 6
50/50
0.279
3151641KERR 7
50/50
0.279
3151541CLOVER2
50/50
2.847
3151281ROARAP4
50/50
0.085
3151281ROARAP4
50/50
0.08
963041AG1-153 GEN
50/50
1.549
315657AE1-056 GEN
Solar/Wind Harmer
12.95
946301AF1-294 GEN
Solar/Wind Harmer
6.911
961791AG1-021 GEN
Solar/Wind Harmer
3.362
970683AG2-441 GEN
Solar/Wind Harmer
20.935
970681AG2-440 GEN
Solar/Wind Harmer
16.748
3144303KENBRDG
Solar/Wind Harmer
0.22
971443AH1-215 GEN
Solar/Wind Harmer
4.574
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.327
3147173SINAI
Solar/Wind Harmer
0.11
3147243WELCO
Solar/Wind Harmer
0.069
970831AG2-522 GEN
Solar/Wind Harmer
4.619
970865AG2-541 GEN
Solar/Wind Harmer
3.009
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.287
316123AC1-075 GEN
Solar/Wind Harmer
0.097
970165AG2-112 GEN
Solar/Wind Harmer
0.577
970163AG2-111 GEN
Solar/Wind Harmer
0.551
971967AH1-528 GEN
Solar/Wind Harmer
10.885
315607AA1-063A GEN
Solar/Wind Harmer
0.13
3146043SEABORD
Solar/Wind Harmer
0.063
970085AG2-068 GEN
Solar/Wind Harmer
3.037
970581AG2-369 GEN
Solar/Wind Harmer
2.612
270494AE1-108_GEN
Solar/Wind Helper
4.476
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
3144293JTRSVLE
50/50
1.183
3144293JTRSVLE
50/50
0.996
970535AG2-341 GEN
50/50
2.851
3152661PLYWOOD A
50/50
0.269
3151041BRUNSWICKG3
50/50
0.765
972187AH1-678 GEN
50/50
1.756
970301AG2-198 GEN
Solar/Wind Harmer
16.182
3147133PAMPLIN
Solar/Wind Harmer
0.375
3147133PAMPLIN
Solar/Wind Harmer
0.3
958211AF2-115 GEN
Solar/Wind Harmer
4.203
963191AG1-168 GEN
Solar/Wind Harmer
1.401
971741AH1-377 GEN
Solar/Wind Harmer
33.06
316034AC1-036 C
Solar/Wind Harmer
0.02
970323AG2-213 GEN
Solar/Wind Harmer
11.759
971775AH1-396 GEN
Solar/Wind Harmer
0.441
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
7.224
939181AE1-148 GEN
Solar/Wind Harmer
6.94
964791AG1-342 GEN
Solar/Wind Harmer
2.755
3146843MT LREL
Solar/Wind Harmer
0.143
3146843MT LREL
Solar/Wind Harmer
0.143
970099AG2-077 GEN
Solar/Wind Harmer
13.837
970933AG2-581 GEN
Solar/Wind Harmer
6.964
316181AB2-040 GEN
Solar/Wind Harmer
0.107
3145593CAROLNA
Solar/Wind Harmer
0.07
3145593CAROLNA
Solar/Wind Harmer
0.07
966811AG1-552 GEN
Solar/Wind Harmer
0.763
3145593CAROLNA
Solar/Wind Harmer
0.088
3145783HORNRTN
Solar/Wind Harmer
1.221
3145783HORNRTN
Solar/Wind Harmer
0.977
3145783HORNRTN
Solar/Wind Harmer
0.305
3145783HORNRTN
Solar/Wind Harmer
0.122
316222AC1-221 GEN
Solar/Wind Harmer
0.284
316426AA2-053 GEN
Solar/Wind Harmer
0.225
942751AE2-291 GEN
Solar/Wind Harmer
3.338
316274AC1-208 GEN
Solar/Wind Harmer
0.311
3146776BUCKING
Solar/Wind Helper
3.475
3146776BUCKING
Solar/Wind Helper
0.282
315821AE2-092 GEN
Solar/Wind Helper
2.978
LAGNLTFEXP_LAGN->PJM
CLTF
1.976
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.656
TVALTFEXP_TVA->PJM
CLTF
0.971
CPLELTFEXP_CPLE->PJM
CLTF
3.789
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.54
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.153
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.217
MECLTFEXP_MEC->PJM
CLTF
0.756
SIGELTFEXP_SIGE->PJM
CLTF
0.021
NYPJM->LTFIMP_NY
CLTF
0.298
LGEELTFEXP_LGEE->PJM
CLTF
0.232
WECLTFEXP_WEC->PJM
CLTF
0.123

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:196.14 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:1331.14
MW Contribution:3.22
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.706
3144293JTRSVLE
50/50
0.594
970535AG2-341 GEN
50/50
2.11
3152661PLYWOOD A
50/50
0.217
3151041BRUNSWICKG3
50/50
1.059
972187AH1-678 GEN
50/50
2.43
315242AE2-183_GT2
50/50
1.321
315241AE2-183_GT1
50/50
1.313
972185AH1-677 GEN
50/50
4.762
970533AG2-339 GEN
50/50
7.019
970531AG2-338 GEN
50/50
2.808
971489AH1-241 GEN
Solar/Wind Harmer
21.635
3146776BUCKING
Solar/Wind Harmer
1.465
3146776BUCKING
Solar/Wind Harmer
0.119
315821AE2-092 GEN
Solar/Wind Harmer
0.014
970301AG2-198 GEN
Solar/Wind Harmer
9.583
3147133PAMPLIN
Solar/Wind Harmer
0.221
3147133PAMPLIN
Solar/Wind Harmer
0.176
958211AF2-115 GEN
Solar/Wind Harmer
2.506
963191AG1-168 GEN
Solar/Wind Harmer
0.835
971741AH1-377 GEN
Solar/Wind Harmer
20.177
316034AC1-036 C
Solar/Wind Harmer
0.013
970323AG2-213 GEN
Solar/Wind Harmer
7.401
971775AH1-396 GEN
Solar/Wind Harmer
0.278
313527AB2-043 GEN
Solar/Wind Harmer
0.002
971223AH1-071 GEN
Solar/Wind Harmer
1.233
962561AG1-105 GEN
Solar/Wind Harmer
5.397
939181AE1-148 GEN
Solar/Wind Harmer
5.333
970099AG2-077 GEN
Solar/Wind Harmer
11.718
964791AG1-342 GEN
Solar/Wind Harmer
2.089
3146843MT LREL
Solar/Wind Harmer
0.109
3146843MT LREL
Solar/Wind Harmer
0.109
3143526WINTERP
Solar/Wind Harmer
0.504
970933AG2-581 GEN
Solar/Wind Harmer
7.465
316181AB2-040 GEN
Solar/Wind Harmer
0.116
3145593CAROLNA
Solar/Wind Harmer
0.078
3145593CAROLNA
Solar/Wind Harmer
0.078
966811AG1-552 GEN
Solar/Wind Harmer
0.843
3145593CAROLNA
Solar/Wind Harmer
0.097
3145783HORNRTN
Solar/Wind Harmer
1.361
3145783HORNRTN
Solar/Wind Harmer
1.089
3145783HORNRTN
Solar/Wind Harmer
0.34
3145783HORNRTN
Solar/Wind Harmer
0.136
316426AA2-053 GEN
Solar/Wind Harmer
0.256
3144356SAPONY
Solar/Wind Harmer
0.607
316274AC1-208 GEN
Solar/Wind Harmer
0.366
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.042
3145893MURPHYS
Solar/Wind Harmer
0.47
3145893MURPHYS
Solar/Wind Harmer
0.126
3145796HORNRTN
Solar/Wind Harmer
0.209
3146173TUNIS
Solar/Wind Harmer
0.069
3146173TUNIS
Solar/Wind Harmer
0.069
315742AE1-103 GEN
Solar/Wind Harmer
0.001
316222AC1-221 GEN
Solar/Wind Harmer
0.272
316065AD1-022 GEN
Solar/Wind Harmer
3.004
970657AG2-426 GEN
Solar/Wind Harmer
2.275
970657AG2-426 GEN
Solar/Wind Harmer
0.477
316263AC1-034 GEN
Solar/Wind Harmer
2.446
3146376EDENTON
Solar/Wind Harmer
0.286
3146376EDENTON
Solar/Wind Harmer
0.286
961601AG1-000A GEN
Solar/Wind Harmer
1.137
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3145493TOT1
Solar/Wind Harmer
0.148
3145453TOT5
Solar/Wind Harmer
0.089
3145603CNETO
Solar/Wind Harmer
0.059
3146386ELIZ CT
Solar/Wind Harmer
0.064
3145933PARMELE
Solar/Wind Harmer
0.127
3145933PARMELE
Solar/Wind Harmer
0.063
3130086AYDLETT
Solar/Wind Harmer
0.253
3137176SLIGO L2192
Solar/Wind Harmer
0.252
3146456SLIGO L269
Solar/Wind Harmer
1.121
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.035
316339AD2-160 GEN
Solar/Wind Harmer
0.103
3145506HICKORY
Solar/Wind Harmer
0.253
3145506HICKORY
Solar/Wind Harmer
0.152
3145506HICKORY
Solar/Wind Harmer
0.038
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.061
942751AE2-291 GEN
Solar/Wind Harmer
3.43
316240AF1-291 C
Solar/Wind Harmer
0.001
316036AC1-147 C
Solar/Wind Harmer
0.012
3150991CHESPKB
Adder
0.659
3150991CHESPKB
Adder
0.643
944641AF1-129 GEN
Adder
29.755
316236AE1-162_GEN
Solar/Wind Harmer
0
316033AB2-134 GEN
Solar/Wind Harmer
0.004
315697AD1-025 GEN
Solar/Wind Harmer
0.068
966001AG1-469 GEN
Solar/Wind Helper
0.206
3151921BEARGRDN G2
50/50
4.238
3144293JTRSVLE
50/50
0.706
970413AG2-270 GEN
50/50
10.245
3151591KERR 2
50/50
0.22
3151031BRUNSWICKG2
50/50
1.059
3151261ROARAP2
50/50
0.095
3150861SPRUNCD
50/50
0.364
966251AG1-494 GEN
50/50
1.288
970221AG2-151 GEN
Solar/Wind Harmer
21.635
3146776BUCKING
Solar/Wind Harmer
0.132
3146926FARMVIL
Solar/Wind Harmer
0.176
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316313AB2-026
Solar/Wind Harmer
0.159
316258AE1-075 C
Solar/Wind Harmer
0.19
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.801
970909AG2-566 GEN
Solar/Wind Harmer
2.396
3147133PAMPLIN
Solar/Wind Harmer
0.693
971193AH1-056 GEN
Solar/Wind Harmer
13.448
963181AG1-167 GEN
Solar/Wind Harmer
0.835
959311AF2-222 GEN
Solar/Wind Harmer
15.884
970257AG2-171 GEN
Solar/Wind Harmer
5.55
315785AD2-033 C
Solar/Wind Harmer
1.352
964241AG1-285 GEN
Solar/Wind Harmer
9.804
316131AB2-060 GEN
Solar/Wind Harmer
0.426
958131AF2-107 GEN
Solar/Wind Harmer
3.651
316478AD1-087 GEN
Solar/Wind Harmer
0.382
316486AD2-202 GEN
Solar/Wind Harmer
0.112
3147043LAWRENC
Solar/Wind Harmer
0.059
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.912
971683AH1-343 GEN
Solar/Wind Harmer
3.032
313506AB2-031 GEN
Solar/Wind Harmer
0.248
970917AG2-570 GEN
Solar/Wind Harmer
6.901
316365GEN2_N
Solar/Wind Harmer
0.164
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3146263WOODLND
Solar/Wind Harmer
0.071
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3145893MURPHYS
Solar/Wind Harmer
0.117
3145893MURPHYS
Solar/Wind Harmer
0.07
957521AF2-046 GEN
Solar/Wind Harmer
5.202
961681AG1-008 GEN
Solar/Wind Harmer
5.202
3145796HORNRTN
Solar/Wind Harmer
0.279
3145796HORNRTN
Solar/Wind Harmer
0.07
316210AC1-098 GEN
Solar/Wind Harmer
0.644
3146173TUNIS
Solar/Wind Harmer
0.069
316463AE2-346 GEN
Solar/Wind Harmer
0.059
316140AB2-099
Solar/Wind Harmer
0.025
962331AG1-082 GEN
Solar/Wind Harmer
0.732
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.069
316327AA2-057 GEN
Solar/Wind Harmer
0.102
315724AD1-057 GEN
Solar/Wind Harmer
0.25
3145273HOLLAND
Solar/Wind Harmer
0.05
3156021HOLLOMANSOL
Solar/Wind Harmer
0.301
3146233WITAKRS
Solar/Wind Harmer
0.331
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.043
3146206CASHIE
Solar/Wind Harmer
0.065
315813AE1-149 C
Solar/Wind Harmer
3.482
970659AG2-427 GEN
Solar/Wind Harmer
0.688
316083AB2-161 GEN
Solar/Wind Harmer
0.001
316283AC2-100 C
Solar/Wind Harmer
0.127
315839AE2-212 C
Solar/Wind Harmer
0.001
315737AD1-076 GEN
Solar/Wind Harmer
0.835
970661AG2-428 GEN
Solar/Wind Harmer
1.373
971157AH1-035 GEN
Solar/Wind Harmer
0.778
315614AA2-178 GEN
Solar/Wind Harmer
0.37
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.064
971623AH1-311 GEN
Solar/Wind Harmer
0.129
3146376EDENTON
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.064
961601AG1-000A GEN
Solar/Wind Harmer
4.548
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
316435W1029_GEN3
Solar/Wind Harmer
0
965281AG1-393 GEN
Solar/Wind Harmer
0.68
3146073TAR RVR
Solar/Wind Harmer
0.064
3146083TARBORO
Solar/Wind Harmer
0.064
316320Y1-086
Solar/Wind Harmer
0
3145933PARMELE
Solar/Wind Harmer
0.063
966801AG1-551 GEN
Solar/Wind Harmer
0.74
3146456SLIGO L269
Solar/Wind Harmer
0.063
971153AH1-033 GEN
Solar/Wind Harmer
0.732
944581AF1-123 GEN
Solar/Wind Harmer
14.239
944601AF1-125 GEN
Solar/Wind Harmer
14.019
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3151101ELIZAR3
Adder
5.847
3144873MCLAUGH
Solar/Wind Harmer
0.002
3144536CHRHLND
Solar/Wind Harmer
0.009
315773AC2-141 GEN
Solar/Wind Harmer
2.27
3145336SMITFLD
Solar/Wind Harmer
0.025
3151221GRAVEL6
Adder
4.403
3151171GRAVELC
Adder
0.847
961611AG1-000B GEN
Solar/Wind Harmer
1.612
3143096IRON208
Adder
0.252
3143096IRON208
Adder
0.247
315778AD1-151 GEN
Solar/Wind Harmer
4.818
970129AG2-093 GEN
Solar/Wind Harmer
3.634
970133AG2-095 GEN
Solar/Wind Harmer
0.576
316499AE2-029_GEN
Solar/Wind Helper
0.501
3132273ORANGE
Solar/Wind Helper
0.03
3147666LOUISA
Solar/Wind Helper
0.3
3148013FISHERV
Solar/Wind Helper
0.129
315616AA1-038_C
Solar/Wind Helper
0.524
972205AH1-687 GEN
50/50
20.67
316303AF2-085
50/50
2.055
3151541CLOVER2
50/50
2.336
3151611KERR 4
50/50
0.22
3151621KERR 5
50/50
0.22
3151631KERR 6
50/50
0.22
3151641KERR 7
50/50
0.22
963041AG1-153 GEN
50/50
2.144
315244AE2-183_ST
50/50
2.284
3151281ROARAP4
50/50
0.094
3151281ROARAP4
50/50
0.088
971285AH1-108 GEN
50/50
0.596
315779AE2-040
50/50
1.013
971447AH1-217 GEN
Solar/Wind Harmer
11.337
971845AH1-439 GEN
Solar/Wind Harmer
16.33
970285AG2-188 GEN
Solar/Wind Harmer
27.559
270494AE1-108_GEN
Solar/Wind Harmer
3.817
315657AE1-056 GEN
Solar/Wind Harmer
7.617
946301AF1-294 GEN
Solar/Wind Harmer
4.122
961791AG1-021 GEN
Solar/Wind Harmer
2.005
970683AG2-441 GEN
Solar/Wind Harmer
12.78
970681AG2-440 GEN
Solar/Wind Harmer
10.224
3144303KENBRDG
Solar/Wind Harmer
0.139
971443AH1-215 GEN
Solar/Wind Harmer
2.888
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.258
316233AE1-074 FULL
Solar/Wind Harmer
0.078
971281AH1-106 GEN
Solar/Wind Harmer
1.344
971283AH1-107 GEN
Solar/Wind Harmer
1.344
970831AG2-522 GEN
Solar/Wind Harmer
4.036
3147173SINAI
Solar/Wind Harmer
0.092
3147243WELCO
Solar/Wind Harmer
0.057
971967AH1-528 GEN
Solar/Wind Harmer
13.711
316087AB2-174 GEN
Solar/Wind Harmer
0.002
970673AG2-436 GEN
Solar/Wind Harmer
16.986
970673AG2-436 GEN
Solar/Wind Harmer
11.324
941031AE2-094 GEN
Solar/Wind Harmer
14.544
944011AF1-069 GEN
Solar/Wind Harmer
4.752
3137643SOCKMAN
Solar/Wind Harmer
0.315
970865AG2-541 GEN
Solar/Wind Harmer
2.702
970085AG2-068 GEN
Solar/Wind Harmer
4.124
970581AG2-369 GEN
Solar/Wind Harmer
3.547
315607AA1-063A GEN
Solar/Wind Harmer
0.154
3146043SEABORD
Solar/Wind Harmer
0.075
315814AE2-033 C
Solar/Wind Harmer
5.747
316315AB2-025 C
Solar/Wind Harmer
0.059
965291AG1-394 GEN
Solar/Wind Harmer
0.317
315652AC1-086 GEN
Solar/Wind Harmer
7.782
3145893MURPHYS
Solar/Wind Harmer
0.19
3145893MURPHYS
Solar/Wind Harmer
0.07
3145796HORNRTN
Solar/Wind Harmer
0.223
3145796HORNRTN
Solar/Wind Harmer
0.028
3146033SCOT NK
Solar/Wind Harmer
0.276
316123AC1-075 GEN
Solar/Wind Harmer
0.094
970165AG2-112 GEN
Solar/Wind Harmer
0.558
970163AG2-111 GEN
Solar/Wind Harmer
0.532
3145513AHOSKIE
Solar/Wind Harmer
0.143
3145513AHOSKIE
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.136
3145683EARLEYS
Solar/Wind Harmer
0.068
3145683EARLEYS
Solar/Wind Harmer
0.068
3143316POE
Solar/Wind Harmer
0.269
316319Z2-044 C
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
0.065
970601AG2-382 GEN
Solar/Wind Harmer
2.444
315732AD1-074 GEN1
Solar/Wind Harmer
0.373
315733AD1-074 GEN2
Solar/Wind Harmer
0.373
315735AD1-075 GEN1
Solar/Wind Harmer
0.187
3130546PLYMOUTH
Solar/Wind Harmer
0.065
315816AE2-034 GEN
Solar/Wind Harmer
0.277
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.044
316311AC2-079 GEN
Solar/Wind Harmer
1.853
315835AF2-110_GEN
Solar/Wind Harmer
0.441
3130156CHOWAN
Solar/Wind Harmer
0.064
3130156CHOWAN
Solar/Wind Harmer
0.064
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3145573BETHELC
Solar/Wind Harmer
0.064
3145573BETHELC
Solar/Wind Harmer
0.064
3146486SUNBURY
Solar/Wind Harmer
0.064
3146486SUNBURY
Solar/Wind Harmer
0.064
316321Z2-027
Solar/Wind Harmer
0.012
3145176PASQUOTANK
Solar/Wind Harmer
0.039
3146396TANGLEW
Solar/Wind Harmer
0.175
316420AA1-050 GEN
Solar/Wind Harmer
0.002
313526AB2-022
Solar/Wind Harmer
0.034
316305AF2-043 C
Solar/Wind Harmer
0.001
957861AF2-080 GEN
Solar/Wind Harmer
2.737
3146406KITTY HAWK
Solar/Wind Harmer
0.008
319010AE1-072 C
Solar/Wind Harmer
0.319
957871AF2-081 GEN
Solar/Wind Harmer
3.153
316005AA1-067
Solar/Wind Harmer
0.068
3145746EVERETS
Solar/Wind Harmer
0.252
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
970181AG2-120 GEN
Solar/Wind Harmer
0.787
3151081ELIZAR1
Adder
5.773
3151091ELIZAR2
Adder
5.672
3152611GOSPORTB
Adder
0.802
3152621GOSPORTC
Adder
0.68
3152601GOSPORTA
Adder
0.628
971445AH1-216 GEN
Solar/Wind Harmer
4.321
972265AH1-717 GEN
Adder
4.702
3151201GRAVEL4
Adder
4.408
3151191GRAVEL3
Adder
4.352
3151211GRAVEL5
Adder
4.352
316369SG1_INVT
Solar/Wind Harmer
0.002
316132AB2-190 GEN1
Solar/Wind Harmer
0.323
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.077
3148013FISHERV
Solar/Wind Helper
0.074
3148463FAIRFLD
Solar/Wind Helper
0.116
3151931BEARGRDN S1
50/50
5.469
3151911BEARGRDN G1
50/50
4.238
3144293JTRSVLE
50/50
0.706
970119AG2-088 GEN
50/50
15.414
3151531CLOVER1
50/50
2.348
3151601KERR 3
50/50
0.22
3151581KERR 1
50/50
0.079
3147043LAWRENC
50/50
0.939
3151051BRUNSWICKS1
50/50
2.197
3151021BRUNSWICKG1
50/50
1.059
971451AH1-221 GEN
50/50
3.216
315243AE2-183_GT3
50/50
1.321
3151261ROARAP2
50/50
0.097
3150851SPRUNCC
50/50
0.364
972003AH1-546 GEN
Solar/Wind Harmer
18.676
971377AH1-170 GEN
Solar/Wind Harmer
4.327
3147623JAMES R
Solar/Wind Harmer
0.94
970937AG2-583 GEN
Solar/Wind Harmer
23.217
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.147
3146926FARMVIL
Solar/Wind Harmer
0.176
316336AC2-165 C
Solar/Wind Harmer
0.011
3143336POWHATN
Solar/Wind Harmer
4.472
963171AG1-166 GEN
Solar/Wind Harmer
1.114
971563AH1-280 GEN
Solar/Wind Harmer
2.228
970685AG2-442 GEN
Solar/Wind Harmer
14.313
962491AG1-098 GEN
Solar/Wind Harmer
7.815
315693AD1-088 GEN
Solar/Wind Harmer
6.344
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3143226MDLTHAN
Solar/Wind Harmer
0.116
957481AF2-042 GEN
Solar/Wind Harmer
29.295
970401AG2-262 GEN
Solar/Wind Harmer
0.638
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
4.184
3143526WINTERP
Solar/Wind Harmer
0.504
316129AC1-054 GEN
Solar/Wind Harmer
0.363
971795AH1-408 GEN
Solar/Wind Harmer
6.199
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.793
970919AG2-571 GEN
Solar/Wind Harmer
2.76
970087AG2-069 GEN
Solar/Wind Harmer
6.187
3145783HORNRTN
Solar/Wind Harmer
0.076
316190AA2-174 GEN
Solar/Wind Harmer
0
940641AE2-051 GEN
Solar/Wind Harmer
5.984
316023GEN1_S
Solar/Wind Harmer
0.164
939411AE1-173 GEN
Solar/Wind Harmer
30.681
316011AB1-132 GEN
Solar/Wind Harmer
1.286
962571AG1-106 GEN
Solar/Wind Harmer
1.007
3146263WOODLND
Solar/Wind Harmer
0.071
3145893MURPHYS
Solar/Wind Harmer
0.281
3145893MURPHYS
Solar/Wind Harmer
0.312
3145796HORNRTN
Solar/Wind Harmer
0.23
3145796HORNRTN
Solar/Wind Harmer
0.07
316212AC1-099_GEN
Solar/Wind Harmer
0.359
3146173TUNIS
Solar/Wind Harmer
0.069
3145823KELFORD
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.068
315722AD1-056 GEN
Solar/Wind Harmer
0.422
3146233WITAKRS
Solar/Wind Harmer
0.263
3146206CASHIE
Solar/Wind Harmer
0.065
971547AH1-271 GEN
Solar/Wind Harmer
1.396
970659AG2-427 GEN
Solar/Wind Harmer
3.146
316381AD1-082 GEN
Solar/Wind Harmer
0.068
970661AG2-428 GEN
Solar/Wind Harmer
6.453
3145663CRESWEL
Solar/Wind Harmer
0.181
971163AH1-040 GEN
Solar/Wind Harmer
5.167
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.052
316359AB2-059 GEN
Solar/Wind Harmer
0.231
316049AB1-081 GEN
Solar/Wind Harmer
0.368
3142053HEARTS
Solar/Wind Harmer
0.113
316093AE2-104_GEN
Solar/Wind Harmer
1.081
3130156CHOWAN
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.064
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3142543TWELFTH
Solar/Wind Harmer
0.006
3146516WINFALL
Solar/Wind Harmer
0.207
3146516WINFALL
Solar/Wind Harmer
0.064
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.064
3145493TOT1
Solar/Wind Harmer
0.283
316246AF1-032 C
Solar/Wind Harmer
0.029
3146293MARTNCO
Solar/Wind Harmer
0.059
316494AC1-189 GEN
Solar/Wind Harmer
0.214
3146456SLIGO L269
Solar/Wind Harmer
0.063
316388AE2-253 GEN
Solar/Wind Harmer
0.198
944591AF1-124 GEN
Solar/Wind Harmer
14.289
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
315671AE2-027_GEN
Solar/Wind Harmer
4.043
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
0.786
316072AD1-144
Solar/Wind Harmer
0.023
316294AC1-161 GEN
Solar/Wind Harmer
1.077
3145336SMITFLD
Solar/Wind Harmer
0.246
3151171GRAVELC
Adder
0.644
961611AG1-000B GEN
Solar/Wind Harmer
3.17
971647AH1-324 GEN
Solar/Wind Harmer
2.576
3143096IRON208
Adder
0.252
971069AG2-661 GEN
Solar/Wind Harmer
1.071
316458AB2-190 GEN2
Solar/Wind Harmer
0.323
970129AG2-093 GEN
Solar/Wind Harmer
1.71
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.903
3147666LOUISA
Solar/Wind Helper
0.521
LAGNLTFEXP_LAGN->PJM
CLTF
1.972
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.458
TVALTFEXP_TVA->PJM
CLTF
0.973
CPLELTFEXP_CPLE->PJM
CLTF
4.213
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.705
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.642
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.131
MECLTFEXP_MEC->PJM
CLTF
0.546
SIGELTFEXP_SIGE->PJM
CLTF
0.014
NYPJM->LTFIMP_NY
CLTF
0.616
LGEELTFEXP_LGEE->PJM
CLTF
0.137
WECLTFEXP_WEC->PJM
CLTF
0.063

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:198.54 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:1313.88
MW Contribution:3.22
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.238
3144293JTRSVLE
50/50
0.706
970413AG2-270 GEN
50/50
10.245
3151591KERR 2
50/50
0.22
3151031BRUNSWICKG2
50/50
1.059
3151261ROARAP2
50/50
0.095
3150861SPRUNCD
50/50
0.364
966251AG1-494 GEN
50/50
1.288
970221AG2-151 GEN
Solar/Wind Harmer
21.635
3146776BUCKING
Solar/Wind Harmer
0.132
3146926FARMVIL
Solar/Wind Harmer
0.176
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316313AB2-026
Solar/Wind Harmer
0.159
316258AE1-075 C
Solar/Wind Harmer
0.19
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.801
970909AG2-566 GEN
Solar/Wind Harmer
2.396
3147133PAMPLIN
Solar/Wind Harmer
0.693
971193AH1-056 GEN
Solar/Wind Harmer
13.448
963181AG1-167 GEN
Solar/Wind Harmer
0.835
959311AF2-222 GEN
Solar/Wind Harmer
15.884
970257AG2-171 GEN
Solar/Wind Harmer
5.55
315785AD2-033 C
Solar/Wind Harmer
1.352
964241AG1-285 GEN
Solar/Wind Harmer
9.804
316131AB2-060 GEN
Solar/Wind Harmer
0.426
958131AF2-107 GEN
Solar/Wind Harmer
3.651
316478AD1-087 GEN
Solar/Wind Harmer
0.382
316486AD2-202 GEN
Solar/Wind Harmer
0.112
3147043LAWRENC
Solar/Wind Harmer
0.059
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.912
971683AH1-343 GEN
Solar/Wind Harmer
3.032
313506AB2-031 GEN
Solar/Wind Harmer
0.248
970917AG2-570 GEN
Solar/Wind Harmer
6.901
316365GEN2_N
Solar/Wind Harmer
0.164
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3146263WOODLND
Solar/Wind Harmer
0.071
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3145893MURPHYS
Solar/Wind Harmer
0.117
3145893MURPHYS
Solar/Wind Harmer
0.07
957521AF2-046 GEN
Solar/Wind Harmer
5.202
961681AG1-008 GEN
Solar/Wind Harmer
5.202
3145796HORNRTN
Solar/Wind Harmer
0.279
3145796HORNRTN
Solar/Wind Harmer
0.07
316210AC1-098 GEN
Solar/Wind Harmer
0.644
3146173TUNIS
Solar/Wind Harmer
0.069
316463AE2-346 GEN
Solar/Wind Harmer
0.059
316140AB2-099
Solar/Wind Harmer
0.025
962331AG1-082 GEN
Solar/Wind Harmer
0.732
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.069
316327AA2-057 GEN
Solar/Wind Harmer
0.102
315724AD1-057 GEN
Solar/Wind Harmer
0.25
3145273HOLLAND
Solar/Wind Harmer
0.05
3156021HOLLOMANSOL
Solar/Wind Harmer
0.301
3146233WITAKRS
Solar/Wind Harmer
0.331
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.043
3146206CASHIE
Solar/Wind Harmer
0.065
315813AE1-149 C
Solar/Wind Harmer
3.482
970659AG2-427 GEN
Solar/Wind Harmer
0.688
316083AB2-161 GEN
Solar/Wind Harmer
0.001
316283AC2-100 C
Solar/Wind Harmer
0.127
315839AE2-212 C
Solar/Wind Harmer
0.001
315737AD1-076 GEN
Solar/Wind Harmer
0.835
970661AG2-428 GEN
Solar/Wind Harmer
1.373
971157AH1-035 GEN
Solar/Wind Harmer
0.778
315614AA2-178 GEN
Solar/Wind Harmer
0.37
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.064
971623AH1-311 GEN
Solar/Wind Harmer
0.129
3146376EDENTON
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.064
961601AG1-000A GEN
Solar/Wind Harmer
4.548
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
316435W1029_GEN3
Solar/Wind Harmer
0
965281AG1-393 GEN
Solar/Wind Harmer
0.68
3146073TAR RVR
Solar/Wind Harmer
0.064
3146083TARBORO
Solar/Wind Harmer
0.064
316320Y1-086
Solar/Wind Harmer
0
3145933PARMELE
Solar/Wind Harmer
0.063
966801AG1-551 GEN
Solar/Wind Harmer
0.74
3146456SLIGO L269
Solar/Wind Harmer
0.063
971153AH1-033 GEN
Solar/Wind Harmer
0.732
944581AF1-123 GEN
Solar/Wind Harmer
14.239
944601AF1-125 GEN
Solar/Wind Harmer
14.019
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3151101ELIZAR3
Adder
5.847
3144873MCLAUGH
Solar/Wind Harmer
0.002
3144536CHRHLND
Solar/Wind Harmer
0.009
315773AC2-141 GEN
Solar/Wind Harmer
2.27
3145336SMITFLD
Solar/Wind Harmer
0.025
3151221GRAVEL6
Adder
4.403
3151171GRAVELC
Adder
0.847
961611AG1-000B GEN
Solar/Wind Harmer
1.612
3143096IRON208
Adder
0.252
3143096IRON208
Adder
0.247
315778AD1-151 GEN
Solar/Wind Harmer
4.818
970129AG2-093 GEN
Solar/Wind Harmer
3.634
970133AG2-095 GEN
Solar/Wind Harmer
0.576
316499AE2-029_GEN
Solar/Wind Helper
0.501
3132273ORANGE
Solar/Wind Helper
0.03
3147666LOUISA
Solar/Wind Helper
0.3
3148013FISHERV
Solar/Wind Helper
0.129
315616AA1-038_C
Solar/Wind Helper
0.524
972205AH1-687 GEN
50/50
20.67
316303AF2-085
50/50
2.055
3151541CLOVER2
50/50
2.336
3151611KERR 4
50/50
0.22
3151621KERR 5
50/50
0.22
3151631KERR 6
50/50
0.22
3151641KERR 7
50/50
0.22
963041AG1-153 GEN
50/50
2.144
315244AE2-183_ST
50/50
2.284
3151281ROARAP4
50/50
0.094
3151281ROARAP4
50/50
0.088
971285AH1-108 GEN
50/50
0.596
315779AE2-040
50/50
1.013
971447AH1-217 GEN
Solar/Wind Harmer
11.337
971845AH1-439 GEN
Solar/Wind Harmer
16.33
970285AG2-188 GEN
Solar/Wind Harmer
27.559
270494AE1-108_GEN
Solar/Wind Harmer
3.817
315657AE1-056 GEN
Solar/Wind Harmer
7.617
946301AF1-294 GEN
Solar/Wind Harmer
4.122
961791AG1-021 GEN
Solar/Wind Harmer
2.005
970683AG2-441 GEN
Solar/Wind Harmer
12.78
970681AG2-440 GEN
Solar/Wind Harmer
10.224
3144303KENBRDG
Solar/Wind Harmer
0.139
971443AH1-215 GEN
Solar/Wind Harmer
2.888
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.258
316233AE1-074 FULL
Solar/Wind Harmer
0.078
971281AH1-106 GEN
Solar/Wind Harmer
1.344
971283AH1-107 GEN
Solar/Wind Harmer
1.344
970831AG2-522 GEN
Solar/Wind Harmer
4.036
3147173SINAI
Solar/Wind Harmer
0.092
3147243WELCO
Solar/Wind Harmer
0.057
971967AH1-528 GEN
Solar/Wind Harmer
13.711
316087AB2-174 GEN
Solar/Wind Harmer
0.002
970673AG2-436 GEN
Solar/Wind Harmer
16.986
970673AG2-436 GEN
Solar/Wind Harmer
11.324
941031AE2-094 GEN
Solar/Wind Harmer
14.544
944011AF1-069 GEN
Solar/Wind Harmer
4.752
3137643SOCKMAN
Solar/Wind Harmer
0.315
970865AG2-541 GEN
Solar/Wind Harmer
2.702
970085AG2-068 GEN
Solar/Wind Harmer
4.124
970581AG2-369 GEN
Solar/Wind Harmer
3.547
315607AA1-063A GEN
Solar/Wind Harmer
0.154
3146043SEABORD
Solar/Wind Harmer
0.075
315814AE2-033 C
Solar/Wind Harmer
5.747
316315AB2-025 C
Solar/Wind Harmer
0.059
965291AG1-394 GEN
Solar/Wind Harmer
0.317
315652AC1-086 GEN
Solar/Wind Harmer
7.782
3145893MURPHYS
Solar/Wind Harmer
0.19
3145893MURPHYS
Solar/Wind Harmer
0.07
3145796HORNRTN
Solar/Wind Harmer
0.223
3145796HORNRTN
Solar/Wind Harmer
0.028
3146033SCOT NK
Solar/Wind Harmer
0.276
316123AC1-075 GEN
Solar/Wind Harmer
0.094
970165AG2-112 GEN
Solar/Wind Harmer
0.558
970163AG2-111 GEN
Solar/Wind Harmer
0.532
3145513AHOSKIE
Solar/Wind Harmer
0.143
3145513AHOSKIE
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.136
3145683EARLEYS
Solar/Wind Harmer
0.068
3145683EARLEYS
Solar/Wind Harmer
0.068
3143316POE
Solar/Wind Harmer
0.269
316319Z2-044 C
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
0.065
970601AG2-382 GEN
Solar/Wind Harmer
2.444
315732AD1-074 GEN1
Solar/Wind Harmer
0.373
315733AD1-074 GEN2
Solar/Wind Harmer
0.373
315735AD1-075 GEN1
Solar/Wind Harmer
0.187
3130546PLYMOUTH
Solar/Wind Harmer
0.065
315816AE2-034 GEN
Solar/Wind Harmer
0.277
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.044
316311AC2-079 GEN
Solar/Wind Harmer
1.853
315835AF2-110_GEN
Solar/Wind Harmer
0.441
3130156CHOWAN
Solar/Wind Harmer
0.064
3130156CHOWAN
Solar/Wind Harmer
0.064
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3145573BETHELC
Solar/Wind Harmer
0.064
3145573BETHELC
Solar/Wind Harmer
0.064
3146486SUNBURY
Solar/Wind Harmer
0.064
3146486SUNBURY
Solar/Wind Harmer
0.064
316321Z2-027
Solar/Wind Harmer
0.012
3145176PASQUOTANK
Solar/Wind Harmer
0.039
3146396TANGLEW
Solar/Wind Harmer
0.175
316420AA1-050 GEN
Solar/Wind Harmer
0.002
313526AB2-022
Solar/Wind Harmer
0.034
316305AF2-043 C
Solar/Wind Harmer
0.001
957861AF2-080 GEN
Solar/Wind Harmer
2.737
3146406KITTY HAWK
Solar/Wind Harmer
0.008
319010AE1-072 C
Solar/Wind Harmer
0.319
957871AF2-081 GEN
Solar/Wind Harmer
3.153
316005AA1-067
Solar/Wind Harmer
0.068
3145746EVERETS
Solar/Wind Harmer
0.252
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
970181AG2-120 GEN
Solar/Wind Harmer
0.787
3151081ELIZAR1
Adder
5.773
3151091ELIZAR2
Adder
5.672
3152611GOSPORTB
Adder
0.802
3152621GOSPORTC
Adder
0.68
3152601GOSPORTA
Adder
0.628
971445AH1-216 GEN
Solar/Wind Harmer
4.321
972265AH1-717 GEN
Adder
4.702
3151201GRAVEL4
Adder
4.408
3151191GRAVEL3
Adder
4.352
3151211GRAVEL5
Adder
4.352
316369SG1_INVT
Solar/Wind Harmer
0.002
316132AB2-190 GEN1
Solar/Wind Harmer
0.323
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.077
3148013FISHERV
Solar/Wind Helper
0.074
3148463FAIRFLD
Solar/Wind Helper
0.116
3144293JTRSVLE
50/50
0.706
3144293JTRSVLE
50/50
0.594
970535AG2-341 GEN
50/50
2.11
3152661PLYWOOD A
50/50
0.217
3151041BRUNSWICKG3
50/50
1.059
972187AH1-678 GEN
50/50
2.43
315242AE2-183_GT2
50/50
1.321
315241AE2-183_GT1
50/50
1.313
972185AH1-677 GEN
50/50
4.762
970533AG2-339 GEN
50/50
7.019
970531AG2-338 GEN
50/50
2.808
971489AH1-241 GEN
Solar/Wind Harmer
21.635
3146776BUCKING
Solar/Wind Harmer
1.465
3146776BUCKING
Solar/Wind Harmer
0.119
315821AE2-092 GEN
Solar/Wind Harmer
0.014
970301AG2-198 GEN
Solar/Wind Harmer
9.583
3147133PAMPLIN
Solar/Wind Harmer
0.221
3147133PAMPLIN
Solar/Wind Harmer
0.176
958211AF2-115 GEN
Solar/Wind Harmer
2.506
963191AG1-168 GEN
Solar/Wind Harmer
0.835
971741AH1-377 GEN
Solar/Wind Harmer
20.177
316034AC1-036 C
Solar/Wind Harmer
0.013
970323AG2-213 GEN
Solar/Wind Harmer
7.401
971775AH1-396 GEN
Solar/Wind Harmer
0.278
313527AB2-043 GEN
Solar/Wind Harmer
0.002
971223AH1-071 GEN
Solar/Wind Harmer
1.233
962561AG1-105 GEN
Solar/Wind Harmer
5.397
939181AE1-148 GEN
Solar/Wind Harmer
5.333
970099AG2-077 GEN
Solar/Wind Harmer
11.718
964791AG1-342 GEN
Solar/Wind Harmer
2.089
3146843MT LREL
Solar/Wind Harmer
0.109
3146843MT LREL
Solar/Wind Harmer
0.109
3143526WINTERP
Solar/Wind Harmer
0.504
970933AG2-581 GEN
Solar/Wind Harmer
7.465
316181AB2-040 GEN
Solar/Wind Harmer
0.116
3145593CAROLNA
Solar/Wind Harmer
0.078
3145593CAROLNA
Solar/Wind Harmer
0.078
966811AG1-552 GEN
Solar/Wind Harmer
0.843
3145593CAROLNA
Solar/Wind Harmer
0.097
3145783HORNRTN
Solar/Wind Harmer
1.361
3145783HORNRTN
Solar/Wind Harmer
1.089
3145783HORNRTN
Solar/Wind Harmer
0.34
3145783HORNRTN
Solar/Wind Harmer
0.136
316426AA2-053 GEN
Solar/Wind Harmer
0.256
3144356SAPONY
Solar/Wind Harmer
0.607
316274AC1-208 GEN
Solar/Wind Harmer
0.366
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.042
3145893MURPHYS
Solar/Wind Harmer
0.47
3145893MURPHYS
Solar/Wind Harmer
0.126
3145796HORNRTN
Solar/Wind Harmer
0.209
3146173TUNIS
Solar/Wind Harmer
0.069
3146173TUNIS
Solar/Wind Harmer
0.069
315742AE1-103 GEN
Solar/Wind Harmer
0.001
316222AC1-221 GEN
Solar/Wind Harmer
0.272
316065AD1-022 GEN
Solar/Wind Harmer
3.004
970657AG2-426 GEN
Solar/Wind Harmer
2.275
970657AG2-426 GEN
Solar/Wind Harmer
0.477
316263AC1-034 GEN
Solar/Wind Harmer
2.446
3146376EDENTON
Solar/Wind Harmer
0.286
3146376EDENTON
Solar/Wind Harmer
0.286
961601AG1-000A GEN
Solar/Wind Harmer
1.137
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3145493TOT1
Solar/Wind Harmer
0.148
3145453TOT5
Solar/Wind Harmer
0.089
3145603CNETO
Solar/Wind Harmer
0.059
3146386ELIZ CT
Solar/Wind Harmer
0.064
3145933PARMELE
Solar/Wind Harmer
0.127
3145933PARMELE
Solar/Wind Harmer
0.063
3130086AYDLETT
Solar/Wind Harmer
0.253
3137176SLIGO L2192
Solar/Wind Harmer
0.252
3146456SLIGO L269
Solar/Wind Harmer
1.121
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.035
316339AD2-160 GEN
Solar/Wind Harmer
0.103
3145506HICKORY
Solar/Wind Harmer
0.253
3145506HICKORY
Solar/Wind Harmer
0.152
3145506HICKORY
Solar/Wind Harmer
0.038
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.061
942751AE2-291 GEN
Solar/Wind Harmer
3.43
316240AF1-291 C
Solar/Wind Harmer
0.001
316036AC1-147 C
Solar/Wind Harmer
0.012
3150991CHESPKB
Adder
0.659
3150991CHESPKB
Adder
0.643
944641AF1-129 GEN
Adder
29.755
316236AE1-162_GEN
Solar/Wind Harmer
0
316033AB2-134 GEN
Solar/Wind Harmer
0.004
315697AD1-025 GEN
Solar/Wind Harmer
0.068
966001AG1-469 GEN
Solar/Wind Helper
0.206
3151931BEARGRDN S1
50/50
5.469
3151911BEARGRDN G1
50/50
4.238
3144293JTRSVLE
50/50
0.706
970119AG2-088 GEN
50/50
15.414
3151531CLOVER1
50/50
2.348
3151601KERR 3
50/50
0.22
3151581KERR 1
50/50
0.079
3147043LAWRENC
50/50
0.939
3151051BRUNSWICKS1
50/50
2.197
3151021BRUNSWICKG1
50/50
1.059
971451AH1-221 GEN
50/50
3.216
315243AE2-183_GT3
50/50
1.321
3151261ROARAP2
50/50
0.097
3150851SPRUNCC
50/50
0.364
972003AH1-546 GEN
Solar/Wind Harmer
18.676
971377AH1-170 GEN
Solar/Wind Harmer
4.327
3147623JAMES R
Solar/Wind Harmer
0.94
970937AG2-583 GEN
Solar/Wind Harmer
23.217
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.147
3146926FARMVIL
Solar/Wind Harmer
0.176
316336AC2-165 C
Solar/Wind Harmer
0.011
3143336POWHATN
Solar/Wind Harmer
4.472
963171AG1-166 GEN
Solar/Wind Harmer
1.114
971563AH1-280 GEN
Solar/Wind Harmer
2.228
970685AG2-442 GEN
Solar/Wind Harmer
14.313
962491AG1-098 GEN
Solar/Wind Harmer
7.815
315693AD1-088 GEN
Solar/Wind Harmer
6.344
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3143226MDLTHAN
Solar/Wind Harmer
0.116
957481AF2-042 GEN
Solar/Wind Harmer
29.295
970401AG2-262 GEN
Solar/Wind Harmer
0.638
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
4.184
3143526WINTERP
Solar/Wind Harmer
0.504
316129AC1-054 GEN
Solar/Wind Harmer
0.363
971795AH1-408 GEN
Solar/Wind Harmer
6.199
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.793
970919AG2-571 GEN
Solar/Wind Harmer
2.76
970087AG2-069 GEN
Solar/Wind Harmer
6.187
3145783HORNRTN
Solar/Wind Harmer
0.076
316190AA2-174 GEN
Solar/Wind Harmer
0
940641AE2-051 GEN
Solar/Wind Harmer
5.984
316023GEN1_S
Solar/Wind Harmer
0.164
939411AE1-173 GEN
Solar/Wind Harmer
30.681
316011AB1-132 GEN
Solar/Wind Harmer
1.286
962571AG1-106 GEN
Solar/Wind Harmer
1.007
3146263WOODLND
Solar/Wind Harmer
0.071
3145893MURPHYS
Solar/Wind Harmer
0.281
3145893MURPHYS
Solar/Wind Harmer
0.312
3145796HORNRTN
Solar/Wind Harmer
0.23
3145796HORNRTN
Solar/Wind Harmer
0.07
316212AC1-099_GEN
Solar/Wind Harmer
0.359
3146173TUNIS
Solar/Wind Harmer
0.069
3145823KELFORD
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.068
315722AD1-056 GEN
Solar/Wind Harmer
0.422
3146233WITAKRS
Solar/Wind Harmer
0.263
3146206CASHIE
Solar/Wind Harmer
0.065
971547AH1-271 GEN
Solar/Wind Harmer
1.396
970659AG2-427 GEN
Solar/Wind Harmer
3.146
316381AD1-082 GEN
Solar/Wind Harmer
0.068
970661AG2-428 GEN
Solar/Wind Harmer
6.453
3145663CRESWEL
Solar/Wind Harmer
0.181
971163AH1-040 GEN
Solar/Wind Harmer
5.167
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.052
316359AB2-059 GEN
Solar/Wind Harmer
0.231
316049AB1-081 GEN
Solar/Wind Harmer
0.368
3142053HEARTS
Solar/Wind Harmer
0.113
316093AE2-104_GEN
Solar/Wind Harmer
1.081
3130156CHOWAN
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.064
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3142543TWELFTH
Solar/Wind Harmer
0.006
3146516WINFALL
Solar/Wind Harmer
0.207
3146516WINFALL
Solar/Wind Harmer
0.064
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.064
3145493TOT1
Solar/Wind Harmer
0.283
316246AF1-032 C
Solar/Wind Harmer
0.029
3146293MARTNCO
Solar/Wind Harmer
0.059
316494AC1-189 GEN
Solar/Wind Harmer
0.214
3146456SLIGO L269
Solar/Wind Harmer
0.063
316388AE2-253 GEN
Solar/Wind Harmer
0.198
944591AF1-124 GEN
Solar/Wind Harmer
14.289
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
315671AE2-027_GEN
Solar/Wind Harmer
4.043
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
0.786
316072AD1-144
Solar/Wind Harmer
0.023
316294AC1-161 GEN
Solar/Wind Harmer
1.077
3145336SMITFLD
Solar/Wind Harmer
0.246
3151171GRAVELC
Adder
0.644
961611AG1-000B GEN
Solar/Wind Harmer
3.17
971647AH1-324 GEN
Solar/Wind Harmer
2.576
3143096IRON208
Adder
0.252
971069AG2-661 GEN
Solar/Wind Harmer
1.071
316458AB2-190 GEN2
Solar/Wind Harmer
0.323
970129AG2-093 GEN
Solar/Wind Harmer
1.71
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.903
3147666LOUISA
Solar/Wind Helper
0.521
LAGNLTFEXP_LAGN->PJM
CLTF
1.972
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.458
TVALTFEXP_TVA->PJM
CLTF
0.973
CPLELTFEXP_CPLE->PJM
CLTF
4.213
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.705
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.642
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.131
MECLTFEXP_MEC->PJM
CLTF
0.546
SIGELTFEXP_SIGE->PJM
CLTF
0.014
NYPJM->LTFIMP_NY
CLTF
0.616
LGEELTFEXP_LGEE->PJM
CLTF
0.137
WECLTFEXP_WEC->PJM
CLTF
0.063

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:195.13 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:1291.31
MW Contribution:3.22
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.706
3144293JTRSVLE
50/50
0.594
970535AG2-341 GEN
50/50
2.11
3152661PLYWOOD A
50/50
0.217
3151041BRUNSWICKG3
50/50
1.059
972187AH1-678 GEN
50/50
2.43
315242AE2-183_GT2
50/50
1.321
315241AE2-183_GT1
50/50
1.313
972185AH1-677 GEN
50/50
4.762
970533AG2-339 GEN
50/50
7.019
970531AG2-338 GEN
50/50
2.808
971489AH1-241 GEN
Solar/Wind Harmer
21.635
3146776BUCKING
Solar/Wind Harmer
1.465
3146776BUCKING
Solar/Wind Harmer
0.119
315821AE2-092 GEN
Solar/Wind Harmer
0.014
970301AG2-198 GEN
Solar/Wind Harmer
9.583
3147133PAMPLIN
Solar/Wind Harmer
0.221
3147133PAMPLIN
Solar/Wind Harmer
0.176
958211AF2-115 GEN
Solar/Wind Harmer
2.506
963191AG1-168 GEN
Solar/Wind Harmer
0.835
971741AH1-377 GEN
Solar/Wind Harmer
20.177
316034AC1-036 C
Solar/Wind Harmer
0.013
970323AG2-213 GEN
Solar/Wind Harmer
7.401
971775AH1-396 GEN
Solar/Wind Harmer
0.278
313527AB2-043 GEN
Solar/Wind Harmer
0.002
971223AH1-071 GEN
Solar/Wind Harmer
1.233
962561AG1-105 GEN
Solar/Wind Harmer
5.397
939181AE1-148 GEN
Solar/Wind Harmer
5.333
970099AG2-077 GEN
Solar/Wind Harmer
11.718
964791AG1-342 GEN
Solar/Wind Harmer
2.089
3146843MT LREL
Solar/Wind Harmer
0.109
3146843MT LREL
Solar/Wind Harmer
0.109
3143526WINTERP
Solar/Wind Harmer
0.504
970933AG2-581 GEN
Solar/Wind Harmer
7.465
316181AB2-040 GEN
Solar/Wind Harmer
0.116
3145593CAROLNA
Solar/Wind Harmer
0.078
3145593CAROLNA
Solar/Wind Harmer
0.078
966811AG1-552 GEN
Solar/Wind Harmer
0.843
3145593CAROLNA
Solar/Wind Harmer
0.097
3145783HORNRTN
Solar/Wind Harmer
1.361
3145783HORNRTN
Solar/Wind Harmer
1.089
3145783HORNRTN
Solar/Wind Harmer
0.34
3145783HORNRTN
Solar/Wind Harmer
0.136
316426AA2-053 GEN
Solar/Wind Harmer
0.256
3144356SAPONY
Solar/Wind Harmer
0.607
316274AC1-208 GEN
Solar/Wind Harmer
0.366
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.042
3145893MURPHYS
Solar/Wind Harmer
0.47
3145893MURPHYS
Solar/Wind Harmer
0.126
3145796HORNRTN
Solar/Wind Harmer
0.209
3146173TUNIS
Solar/Wind Harmer
0.069
3146173TUNIS
Solar/Wind Harmer
0.069
315742AE1-103 GEN
Solar/Wind Harmer
0.001
316222AC1-221 GEN
Solar/Wind Harmer
0.272
316065AD1-022 GEN
Solar/Wind Harmer
3.004
970657AG2-426 GEN
Solar/Wind Harmer
2.275
970657AG2-426 GEN
Solar/Wind Harmer
0.477
316263AC1-034 GEN
Solar/Wind Harmer
2.446
3146376EDENTON
Solar/Wind Harmer
0.286
3146376EDENTON
Solar/Wind Harmer
0.286
961601AG1-000A GEN
Solar/Wind Harmer
1.137
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3145493TOT1
Solar/Wind Harmer
0.148
3145453TOT5
Solar/Wind Harmer
0.089
3145603CNETO
Solar/Wind Harmer
0.059
3146386ELIZ CT
Solar/Wind Harmer
0.064
3145933PARMELE
Solar/Wind Harmer
0.127
3145933PARMELE
Solar/Wind Harmer
0.063
3130086AYDLETT
Solar/Wind Harmer
0.253
3137176SLIGO L2192
Solar/Wind Harmer
0.252
3146456SLIGO L269
Solar/Wind Harmer
1.121
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.035
316339AD2-160 GEN
Solar/Wind Harmer
0.103
3145506HICKORY
Solar/Wind Harmer
0.253
3145506HICKORY
Solar/Wind Harmer
0.152
3145506HICKORY
Solar/Wind Harmer
0.038
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3151921BEARGRDN G2
50/50
4.238
3144293JTRSVLE
50/50
0.706
970413AG2-270 GEN
50/50
10.245
3151591KERR 2
50/50
0.22
3151031BRUNSWICKG2
50/50
1.059
3151261ROARAP2
50/50
0.095
3150861SPRUNCD
50/50
0.364
966251AG1-494 GEN
50/50
1.288
970221AG2-151 GEN
Solar/Wind Harmer
21.635
3146776BUCKING
Solar/Wind Harmer
0.132
3146926FARMVIL
Solar/Wind Harmer
0.176
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316313AB2-026
Solar/Wind Harmer
0.159
316258AE1-075 C
Solar/Wind Harmer
0.19
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.801
970909AG2-566 GEN
Solar/Wind Harmer
2.396
3147133PAMPLIN
Solar/Wind Harmer
0.693
971193AH1-056 GEN
Solar/Wind Harmer
13.448
963181AG1-167 GEN
Solar/Wind Harmer
0.835
959311AF2-222 GEN
Solar/Wind Harmer
15.884
970257AG2-171 GEN
Solar/Wind Harmer
5.55
315785AD2-033 C
Solar/Wind Harmer
1.352
964241AG1-285 GEN
Solar/Wind Harmer
9.804
316131AB2-060 GEN
Solar/Wind Harmer
0.426
958131AF2-107 GEN
Solar/Wind Harmer
3.651
316478AD1-087 GEN
Solar/Wind Harmer
0.382
316486AD2-202 GEN
Solar/Wind Harmer
0.112
3147043LAWRENC
Solar/Wind Harmer
0.059
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.912
971683AH1-343 GEN
Solar/Wind Harmer
3.032
313506AB2-031 GEN
Solar/Wind Harmer
0.248
970917AG2-570 GEN
Solar/Wind Harmer
6.901
316365GEN2_N
Solar/Wind Harmer
0.164
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3146263WOODLND
Solar/Wind Harmer
0.071
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3145893MURPHYS
Solar/Wind Harmer
0.117
3145893MURPHYS
Solar/Wind Harmer
0.07
957521AF2-046 GEN
Solar/Wind Harmer
5.202
961681AG1-008 GEN
Solar/Wind Harmer
5.202
3145796HORNRTN
Solar/Wind Harmer
0.279
3145796HORNRTN
Solar/Wind Harmer
0.07
316210AC1-098 GEN
Solar/Wind Harmer
0.644
3146173TUNIS
Solar/Wind Harmer
0.069
316463AE2-346 GEN
Solar/Wind Harmer
0.059
316140AB2-099
Solar/Wind Harmer
0.025
962331AG1-082 GEN
Solar/Wind Harmer
0.732
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.069
316327AA2-057 GEN
Solar/Wind Harmer
0.102
315724AD1-057 GEN
Solar/Wind Harmer
0.25
3145273HOLLAND
Solar/Wind Harmer
0.05
3156021HOLLOMANSOL
Solar/Wind Harmer
0.301
3146233WITAKRS
Solar/Wind Harmer
0.331
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.043
3146206CASHIE
Solar/Wind Harmer
0.065
315813AE1-149 C
Solar/Wind Harmer
3.482
970659AG2-427 GEN
Solar/Wind Harmer
0.688
316083AB2-161 GEN
Solar/Wind Harmer
0.001
316283AC2-100 C
Solar/Wind Harmer
0.127
315839AE2-212 C
Solar/Wind Harmer
0.001
315737AD1-076 GEN
Solar/Wind Harmer
0.835
970661AG2-428 GEN
Solar/Wind Harmer
1.373
971157AH1-035 GEN
Solar/Wind Harmer
0.778
315614AA2-178 GEN
Solar/Wind Harmer
0.37
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.064
971623AH1-311 GEN
Solar/Wind Harmer
0.129
3146376EDENTON
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.064
961601AG1-000A GEN
Solar/Wind Harmer
4.548
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
316435W1029_GEN3
Solar/Wind Harmer
0
965281AG1-393 GEN
Solar/Wind Harmer
0.68
3146073TAR RVR
Solar/Wind Harmer
0.064
3146083TARBORO
Solar/Wind Harmer
0.064
316320Y1-086
Solar/Wind Harmer
0
3145933PARMELE
Solar/Wind Harmer
0.063
966801AG1-551 GEN
Solar/Wind Harmer
0.74
3146456SLIGO L269
Solar/Wind Harmer
0.063
971153AH1-033 GEN
Solar/Wind Harmer
0.732
944581AF1-123 GEN
Solar/Wind Harmer
14.239
944601AF1-125 GEN
Solar/Wind Harmer
14.019
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3151101ELIZAR3
Adder
5.847
3144873MCLAUGH
Solar/Wind Harmer
0.002
3144536CHRHLND
Solar/Wind Harmer
0.009
315773AC2-141 GEN
Solar/Wind Harmer
2.27
3145336SMITFLD
Solar/Wind Harmer
0.025
3151221GRAVEL6
Adder
4.403
3151171GRAVELC
Adder
0.847
961611AG1-000B GEN
Solar/Wind Harmer
1.612
3143096IRON208
Adder
0.252
3143096IRON208
Adder
0.247
315778AD1-151 GEN
Solar/Wind Harmer
4.818
970129AG2-093 GEN
Solar/Wind Harmer
3.634
972205AH1-687 GEN
50/50
20.67
316303AF2-085
50/50
2.055
3151541CLOVER2
50/50
2.336
3151611KERR 4
50/50
0.22
3151621KERR 5
50/50
0.22
3151631KERR 6
50/50
0.22
3151641KERR 7
50/50
0.22
963041AG1-153 GEN
50/50
2.144
315244AE2-183_ST
50/50
2.284
3151281ROARAP4
50/50
0.094
3151281ROARAP4
50/50
0.088
971285AH1-108 GEN
50/50
0.596
315779AE2-040
50/50
1.013
971447AH1-217 GEN
Solar/Wind Harmer
11.337
971845AH1-439 GEN
Solar/Wind Harmer
16.33
970285AG2-188 GEN
Solar/Wind Harmer
27.559
270494AE1-108_GEN
Solar/Wind Harmer
3.817
315657AE1-056 GEN
Solar/Wind Harmer
7.617
946301AF1-294 GEN
Solar/Wind Harmer
4.122
961791AG1-021 GEN
Solar/Wind Harmer
2.005
970683AG2-441 GEN
Solar/Wind Harmer
12.78
970681AG2-440 GEN
Solar/Wind Harmer
10.224
3144303KENBRDG
Solar/Wind Harmer
0.139
971443AH1-215 GEN
Solar/Wind Harmer
2.888
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.258
316233AE1-074 FULL
Solar/Wind Harmer
0.078
971281AH1-106 GEN
Solar/Wind Harmer
1.344
971283AH1-107 GEN
Solar/Wind Harmer
1.344
970831AG2-522 GEN
Solar/Wind Harmer
4.036
3147173SINAI
Solar/Wind Harmer
0.092
3147243WELCO
Solar/Wind Harmer
0.057
971967AH1-528 GEN
Solar/Wind Harmer
13.711
316087AB2-174 GEN
Solar/Wind Harmer
0.002
970673AG2-436 GEN
Solar/Wind Harmer
16.986
970673AG2-436 GEN
Solar/Wind Harmer
11.324
941031AE2-094 GEN
Solar/Wind Harmer
14.544
944011AF1-069 GEN
Solar/Wind Harmer
4.752
3137643SOCKMAN
Solar/Wind Harmer
0.315
970865AG2-541 GEN
Solar/Wind Harmer
2.702
970085AG2-068 GEN
Solar/Wind Harmer
4.124
970581AG2-369 GEN
Solar/Wind Harmer
3.547
315607AA1-063A GEN
Solar/Wind Harmer
0.154
3146043SEABORD
Solar/Wind Harmer
0.075
315814AE2-033 C
Solar/Wind Harmer
5.747
316315AB2-025 C
Solar/Wind Harmer
0.059
965291AG1-394 GEN
Solar/Wind Harmer
0.317
315652AC1-086 GEN
Solar/Wind Harmer
7.782
3145893MURPHYS
Solar/Wind Harmer
0.19
3145893MURPHYS
Solar/Wind Harmer
0.07
3145796HORNRTN
Solar/Wind Harmer
0.223
3145796HORNRTN
Solar/Wind Harmer
0.028
3146033SCOT NK
Solar/Wind Harmer
0.276
316123AC1-075 GEN
Solar/Wind Harmer
0.094
970165AG2-112 GEN
Solar/Wind Harmer
0.558
970163AG2-111 GEN
Solar/Wind Harmer
0.532
3145513AHOSKIE
Solar/Wind Harmer
0.143
3145513AHOSKIE
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.136
3145683EARLEYS
Solar/Wind Harmer
0.068
3145683EARLEYS
Solar/Wind Harmer
0.068
3143316POE
Solar/Wind Harmer
0.269
316319Z2-044 C
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
0.065
970601AG2-382 GEN
Solar/Wind Harmer
2.444
315732AD1-074 GEN1
Solar/Wind Harmer
0.373
315733AD1-074 GEN2
Solar/Wind Harmer
0.373
315735AD1-075 GEN1
Solar/Wind Harmer
0.187
3130546PLYMOUTH
Solar/Wind Harmer
0.065
315816AE2-034 GEN
Solar/Wind Harmer
0.277
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.044
316311AC2-079 GEN
Solar/Wind Harmer
1.853
315835AF2-110_GEN
Solar/Wind Harmer
0.441
3130156CHOWAN
Solar/Wind Harmer
0.064
3130156CHOWAN
Solar/Wind Harmer
0.064
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3145573BETHELC
Solar/Wind Harmer
0.064
3145573BETHELC
Solar/Wind Harmer
0.064
3146486SUNBURY
Solar/Wind Harmer
0.064
3146486SUNBURY
Solar/Wind Harmer
0.064
316321Z2-027
Solar/Wind Harmer
0.012
3145176PASQUOTANK
Solar/Wind Harmer
0.039
3146396TANGLEW
Solar/Wind Harmer
0.175
316420AA1-050 GEN
Solar/Wind Harmer
0.002
313526AB2-022
Solar/Wind Harmer
0.034
316305AF2-043 C
Solar/Wind Harmer
0.001
957861AF2-080 GEN
Solar/Wind Harmer
2.737
3146406KITTY HAWK
Solar/Wind Harmer
0.008
319010AE1-072 C
Solar/Wind Harmer
0.319
957871AF2-081 GEN
Solar/Wind Harmer
3.153
316005AA1-067
Solar/Wind Harmer
0.068
3145746EVERETS
Solar/Wind Harmer
0.252
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
970181AG2-120 GEN
Solar/Wind Harmer
0.787
3151081ELIZAR1
Adder
5.773
3151091ELIZAR2
Adder
5.672
3152611GOSPORTB
Adder
0.802
3152621GOSPORTC
Adder
0.68
3152601GOSPORTA
Adder
0.628
971445AH1-216 GEN
Solar/Wind Harmer
4.321
972265AH1-717 GEN
Adder
4.702
3151201GRAVEL4
Adder
4.408
3151191GRAVEL3
Adder
4.352
3151211GRAVEL5
Adder
4.352
316369SG1_INVT
Solar/Wind Harmer
0.002
316132AB2-190 GEN1
Solar/Wind Harmer
0.323
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.077
3148013FISHERV
Solar/Wind Helper
0.074
3148463FAIRFLD
Solar/Wind Helper
0.116
3151931BEARGRDN S1
50/50
5.469
3151911BEARGRDN G1
50/50
4.238
3144293JTRSVLE
50/50
0.706
970119AG2-088 GEN
50/50
15.414
3151531CLOVER1
50/50
2.348
3151601KERR 3
50/50
0.22
3151581KERR 1
50/50
0.079
3147043LAWRENC
50/50
0.939
3151051BRUNSWICKS1
50/50
2.197
3151021BRUNSWICKG1
50/50
1.059
971451AH1-221 GEN
50/50
3.216
315243AE2-183_GT3
50/50
1.321
3151261ROARAP2
50/50
0.097
3150851SPRUNCC
50/50
0.364
972003AH1-546 GEN
Solar/Wind Harmer
18.676
971377AH1-170 GEN
Solar/Wind Harmer
4.327
3147623JAMES R
Solar/Wind Harmer
0.94
970937AG2-583 GEN
Solar/Wind Harmer
23.217
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.147
3146926FARMVIL
Solar/Wind Harmer
0.176
316336AC2-165 C
Solar/Wind Harmer
0.011
3143336POWHATN
Solar/Wind Harmer
4.472
963171AG1-166 GEN
Solar/Wind Harmer
1.114
971563AH1-280 GEN
Solar/Wind Harmer
2.228
970685AG2-442 GEN
Solar/Wind Harmer
14.313
962491AG1-098 GEN
Solar/Wind Harmer
7.815
315693AD1-088 GEN
Solar/Wind Harmer
6.344
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3143226MDLTHAN
Solar/Wind Harmer
0.116
957481AF2-042 GEN
Solar/Wind Harmer
29.295
970401AG2-262 GEN
Solar/Wind Harmer
0.638
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
4.184
3143526WINTERP
Solar/Wind Harmer
0.504
316129AC1-054 GEN
Solar/Wind Harmer
0.363
971795AH1-408 GEN
Solar/Wind Harmer
6.199
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.793
970919AG2-571 GEN
Solar/Wind Harmer
2.76
970087AG2-069 GEN
Solar/Wind Harmer
6.187
3145783HORNRTN
Solar/Wind Harmer
0.076
316190AA2-174 GEN
Solar/Wind Harmer
0
940641AE2-051 GEN
Solar/Wind Harmer
5.984
316023GEN1_S
Solar/Wind Harmer
0.164
939411AE1-173 GEN
Solar/Wind Harmer
30.681
316011AB1-132 GEN
Solar/Wind Harmer
1.286
962571AG1-106 GEN
Solar/Wind Harmer
1.007
3146263WOODLND
Solar/Wind Harmer
0.071
3145893MURPHYS
Solar/Wind Harmer
0.281
3145893MURPHYS
Solar/Wind Harmer
0.312
3145796HORNRTN
Solar/Wind Harmer
0.23
3145796HORNRTN
Solar/Wind Harmer
0.07
316212AC1-099_GEN
Solar/Wind Harmer
0.359
3146173TUNIS
Solar/Wind Harmer
0.069
3145823KELFORD
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.068
315722AD1-056 GEN
Solar/Wind Harmer
0.422
3146233WITAKRS
Solar/Wind Harmer
0.263
3146206CASHIE
Solar/Wind Harmer
0.065
971547AH1-271 GEN
Solar/Wind Harmer
1.396
970659AG2-427 GEN
Solar/Wind Harmer
3.146
316381AD1-082 GEN
Solar/Wind Harmer
0.068
970661AG2-428 GEN
Solar/Wind Harmer
6.453
3145663CRESWEL
Solar/Wind Harmer
0.181
971163AH1-040 GEN
Solar/Wind Harmer
5.167
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.052
316359AB2-059 GEN
Solar/Wind Harmer
0.231
316049AB1-081 GEN
Solar/Wind Harmer
0.368
3142053HEARTS
Solar/Wind Harmer
0.113
316093AE2-104_GEN
Solar/Wind Harmer
1.081
3130156CHOWAN
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.064
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3142543TWELFTH
Solar/Wind Harmer
0.006
3146516WINFALL
Solar/Wind Harmer
0.207
3146516WINFALL
Solar/Wind Harmer
0.064
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.064
3145493TOT1
Solar/Wind Harmer
0.283
316246AF1-032 C
Solar/Wind Harmer
0.029
3146293MARTNCO
Solar/Wind Harmer
0.059
316494AC1-189 GEN
Solar/Wind Harmer
0.214
3146456SLIGO L269
Solar/Wind Harmer
0.063
316388AE2-253 GEN
Solar/Wind Harmer
0.198
944591AF1-124 GEN
Solar/Wind Harmer
14.289
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
315671AE2-027_GEN
Solar/Wind Harmer
4.043
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
0.786
316072AD1-144
Solar/Wind Harmer
0.023
316294AC1-161 GEN
Solar/Wind Harmer
1.077
3145336SMITFLD
Solar/Wind Harmer
0.246
3151171GRAVELC
Adder
0.644
961611AG1-000B GEN
Solar/Wind Harmer
3.17
970133AG2-095 GEN
Solar/Wind Harmer
0.576
316499AE2-029_GEN
Solar/Wind Helper
0.501
3132273ORANGE
Solar/Wind Helper
0.03
3147666LOUISA
Solar/Wind Helper
0.3
3148013FISHERV
Solar/Wind Helper
0.129
315616AA1-038_C
Solar/Wind Helper
0.524
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.061
942751AE2-291 GEN
Solar/Wind Harmer
3.43
316240AF1-291 C
Solar/Wind Harmer
0.001
316036AC1-147 C
Solar/Wind Harmer
0.012
3150991CHESPKB
Adder
0.659
3150991CHESPKB
Adder
0.643
944641AF1-129 GEN
Adder
29.755
316236AE1-162_GEN
Solar/Wind Harmer
0
316033AB2-134 GEN
Solar/Wind Harmer
0.004
315697AD1-025 GEN
Solar/Wind Harmer
0.068
966001AG1-469 GEN
Solar/Wind Helper
0.206
971647AH1-324 GEN
Solar/Wind Harmer
2.576
3143096IRON208
Adder
0.252
971069AG2-661 GEN
Solar/Wind Harmer
1.071
316458AB2-190 GEN2
Solar/Wind Harmer
0.323
970129AG2-093 GEN
Solar/Wind Harmer
1.71
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.903
3147666LOUISA
Solar/Wind Helper
0.521
LAGNLTFEXP_LAGN->PJM
CLTF
1.972
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.458
TVALTFEXP_TVA->PJM
CLTF
0.973
CPLELTFEXP_CPLE->PJM
CLTF
4.213
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.705
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.642
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.131
MECLTFEXP_MEC->PJM
CLTF
0.546
SIGELTFEXP_SIGE->PJM
CLTF
0.014
NYPJM->LTFIMP_NY
CLTF
0.616
LGEELTFEXP_LGEE->PJM
CLTF
0.137
WECLTFEXP_WEC->PJM
CLTF
0.063

Details for 6POE-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6POE-6TYLER1 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.12 %
Rating:441.8 MVA
Rating Type:B
MVA to Mitigate:574.86
MW Contribution:2.4
Bus #Bus NameTypeMW Contribution
3151391GASTONA
50/50
0.178
3151411GASTONB
50/50
0.178
3151031BRUNSWICKG2
50/50
0.791
3151261ROARAP2
50/50
0.072
315813AE1-149 C
Solar/Wind Harmer
10.442
970659AG2-427 GEN
Solar/Wind Harmer
1.715
316083AB2-161 GEN
Solar/Wind Harmer
0.002
970661AG2-428 GEN
Solar/Wind Harmer
2.912
316365GEN2_N
Solar/Wind Harmer
0.181
313506AB2-031 GEN
Solar/Wind Harmer
0.204
3147043LAWRENC
Solar/Wind Harmer
0.038
3142666NORTHAMPTON
Solar/Wind Harmer
0.063
3145796HORNRTN
Solar/Wind Harmer
0.254
3145796HORNRTN
Solar/Wind Harmer
0.063
970917AG2-570 GEN
Solar/Wind Harmer
5.134
315724AD1-057 GEN
Solar/Wind Harmer
0.212
315779AE2-040
50/50
1.535
315244AE2-183_ST
50/50
1.743
963041AG1-153 GEN
50/50
1.603
3151281ROARAP4
50/50
0.072
3151281ROARAP4
50/50
0.067
3143316POE
Solar/Wind Harmer
1.51
316315AB2-025 C
Solar/Wind Harmer
0.089
315814AE2-033 C
Solar/Wind Harmer
8.577
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.064
316311AC2-079 GEN
Solar/Wind Harmer
2.641
316087AB2-174 GEN
Solar/Wind Harmer
0.002
315652AC1-086 GEN
Solar/Wind Harmer
7.218
3145796HORNRTN
Solar/Wind Harmer
0.203
3145796HORNRTN
Solar/Wind Harmer
0.025
941031AE2-094 GEN
Solar/Wind Harmer
11.623
944011AF1-069 GEN
Solar/Wind Harmer
3.798
3137643SOCKMAN
Solar/Wind Harmer
0.249
970673AG2-436 GEN
Solar/Wind Harmer
13.168
970673AG2-436 GEN
Solar/Wind Harmer
8.779
971967AH1-528 GEN
Solar/Wind Harmer
9.624
315607AA1-063A GEN
Solar/Wind Harmer
0.118
3146043SEABORD
Solar/Wind Harmer
0.058
970085AG2-068 GEN
Solar/Wind Harmer
3.066
970581AG2-369 GEN
Solar/Wind Harmer
2.637
3151391GASTONA
50/50
0.178
3151411GASTONB
50/50
0.178
3147043LAWRENC
50/50
0.61
315243AE2-183_GT3
50/50
1.008
3151051BRUNSWICKS1
50/50
1.643
3151021BRUNSWICKG1
50/50
0.791
971451AH1-221 GEN
50/50
2.404
3151261ROARAP2
50/50
0.074
970659AG2-427 GEN
Solar/Wind Harmer
7.841
316381AD1-082 GEN
Solar/Wind Harmer
0.162
970661AG2-428 GEN
Solar/Wind Harmer
13.69
316023GEN1_S
Solar/Wind Harmer
0.181
960081AF2-299 GEN
Solar/Wind Harmer
0.689
971795AH1-408 GEN
Solar/Wind Harmer
4.41
316011AB1-132 GEN
Solar/Wind Harmer
1.193
962571AG1-106 GEN
Solar/Wind Harmer
0.934
3145796HORNRTN
Solar/Wind Harmer
0.209
3145796HORNRTN
Solar/Wind Harmer
0.063
940641AE2-051 GEN
Solar/Wind Harmer
4.814
3145783HORNRTN
Solar/Wind Harmer
0.058
316190AA2-174 GEN
Solar/Wind Harmer
0
970919AG2-571 GEN
Solar/Wind Harmer
2.053
970087AG2-069 GEN
Solar/Wind Harmer
4.599
315722AD1-056 GEN
Solar/Wind Harmer
0.358
939411AE1-173 GEN
Solar/Wind Harmer
23.023
3151361ROSEMG1
50/50
0.229
3151371ROSEMS1
50/50
0.142
3151381ROSEMG2
50/50
0.107
970533AG2-339 GEN
50/50
5.61
970531AG2-338 GEN
50/50
2.244
315242AE2-183_GT2
50/50
1.008
315241AE2-183_GT1
50/50
1.002
972185AH1-677 GEN
50/50
3.634
3151041BRUNSWICKG3
50/50
0.791
972187AH1-678 GEN
50/50
1.816
970657AG2-426 GEN
Solar/Wind Harmer
5.218
970657AG2-426 GEN
Solar/Wind Harmer
1.094
3144356SAPONY
Solar/Wind Harmer
0.92
316181AB2-040 GEN
Solar/Wind Harmer
0.096
3142666NORTHAMPTON
Solar/Wind Harmer
0.063
3142666NORTHAMPTON
Solar/Wind Harmer
0.063
3142666NORTHAMPTON
Solar/Wind Harmer
0.063
3142666NORTHAMPTON
Solar/Wind Harmer
0.038
3145796HORNRTN
Solar/Wind Harmer
0.19
3145593CAROLNA
Solar/Wind Harmer
0.059
3145593CAROLNA
Solar/Wind Harmer
0.059
966811AG1-552 GEN
Solar/Wind Harmer
0.643
3145593CAROLNA
Solar/Wind Harmer
0.074
3145783HORNRTN
Solar/Wind Harmer
1.04
3145783HORNRTN
Solar/Wind Harmer
0.832
3145783HORNRTN
Solar/Wind Harmer
0.26
3145783HORNRTN
Solar/Wind Harmer
0.104
316426AA2-053 GEN
Solar/Wind Harmer
0.195
970933AG2-581 GEN
Solar/Wind Harmer
4.606
316240AF1-291 C
Solar/Wind Helper
0.538
LAGNLTFEXP_LAGN->PJM
CLTF
1.956
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.263
TVALTFEXP_TVA->PJM
CLTF
0.974
CPLELTFEXP_CPLE->PJM
CLTF
2.954
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.24
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.087
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.327
MECLTFEXP_MEC->PJM
CLTF
0.935
SIGELTFEXP_SIGE->PJM
CLTF
0.028
NYPJM->LTFIMP_NY
CLTF
0.376
LGEELTFEXP_LGEE->PJM
CLTF
0.333
WECLTFEXP_WEC->PJM
CLTF
0.173

Details for 6TYLER-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6TYLER-6CHESTF B 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.46 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1209.55
MW Contribution:4.54
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
1.496
315839AE2-212 C
Solar/Wind Harmer
2.248
965281AG1-393 GEN
Solar/Wind Harmer
3.641
316365GEN2_N
Solar/Wind Harmer
0.988
966621AG1-532 GEN
Solar/Wind Harmer
0.264
970917AG2-570 GEN
Solar/Wind Harmer
30.516
3147043LAWRENC
Solar/Wind Harmer
-0.007
313506AB2-031 GEN
Solar/Wind Harmer
0.94
3145796HORNRTN
Solar/Wind Harmer
-0.045
3145796HORNRTN
Solar/Wind Harmer
-0.011
3142666NORTHAMPTON
Solar/Wind Harmer
-0.011
315243AE2-183_GT3
50/50
1.908
3151051BRUNSWICKS1
50/50
3.105
3151021BRUNSWICKG1
50/50
1.496
971451AH1-221 GEN
50/50
4.543
315671AE2-027_GEN
Solar/Wind Harmer
19.499
316023GEN1_S
Solar/Wind Harmer
0.988
960081AF2-299 GEN
Solar/Wind Harmer
1.464
970919AG2-571 GEN
Solar/Wind Harmer
3.863
970087AG2-069 GEN
Solar/Wind Harmer
11.386
971795AH1-408 GEN
Solar/Wind Harmer
9.103
3147043LAWRENC
Adder
0.945
316011AB1-132 GEN
Solar/Wind Harmer
2.416
962571AG1-106 GEN
Solar/Wind Harmer
1.66
3145796HORNRTN
Solar/Wind Harmer
-0.037
3145796HORNRTN
Solar/Wind Harmer
-0.011
957481AF2-042 GEN
Solar/Wind Harmer
33.627
3145783HORNRTN
Solar/Wind Harmer
-0.01
315722AD1-056 GEN
Solar/Wind Harmer
1.05
315693AD1-088 GEN
Solar/Wind Harmer
4.982
939411AE1-173 GEN
Solar/Wind Harmer
49.774
962491AG1-098 GEN
Solar/Wind Harmer
6.564
316190AA2-174 GEN
Solar/Wind Harmer
0.12
316129AC1-054 GEN
Solar/Wind Harmer
0.838
971065AG2-659 GEN
Solar/Wind Harmer
4.751
315687AD1-152 GEN
Solar/Wind Harmer
1.144
3146233WITAKRS
Solar/Wind Harmer
-0.036
316359AB2-059 GEN
Solar/Wind Harmer
1.219
316049AB1-081 GEN
Solar/Wind Harmer
0.975
3142053HEARTS
Solar/Wind Harmer
0.106
316212AC1-099_GEN
Solar/Wind Harmer
0.788
3145543BTLEBRO
Solar/Wind Harmer
-0.009
3145543BTLEBRO
Solar/Wind Harmer
-0.007
316237AB2-079_GEN
Solar/Wind Harmer
0.266
961671AG1-007 GEN
Solar/Wind Harmer
0.109
3146083TARBORO
Solar/Wind Harmer
-0.009
3145493TOT1
Solar/Wind Harmer
0.257
3146263WOODLND
Solar/Wind Harmer
-0.009
970401AG2-262 GEN
Solar/Wind Harmer
0.554
3145823KELFORD
Solar/Wind Harmer
-0.008
316494AC1-189 GEN
Solar/Wind Harmer
0.891
3145683EARLEYS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.232
316003AC1-222 GEN
Solar/Wind Harmer
0.762
3146293MARTNCO
Solar/Wind Harmer
0.047
970685AG2-442 GEN
Solar/Wind Harmer
6.462
316174AB2-169 GEN
Solar/Wind Harmer
1.1
3145963POPLR C
Solar/Wind Harmer
-0.007
963171AG1-166 GEN
Solar/Wind Harmer
0.871
971563AH1-280 GEN
Solar/Wind Harmer
0.871
3144293JTRSVLE
Adder
0.197
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.713
316458AB2-190 GEN2
Solar/Wind Helper
0.849
3142543TWELFTH
Solar/Wind Helper
0.011
970533AG2-339 GEN
50/50
10.649
970531AG2-338 GEN
50/50
4.259
315242AE2-183_GT2
50/50
1.908
315241AE2-183_GT1
50/50
1.896
972185AH1-677 GEN
50/50
6.877
3151041BRUNSWICKG3
50/50
1.496
972187AH1-678 GEN
50/50
3.433
3144356SAPONY
Solar/Wind Harmer
0.717
970933AG2-581 GEN
Solar/Wind Harmer
11.443
316181AB2-040 GEN
Solar/Wind Harmer
1.631
3145796HORNRTN
Solar/Wind Harmer
-0.033
3142666NORTHAMPTON
Solar/Wind Harmer
-0.011
3142666NORTHAMPTON
Solar/Wind Harmer
-0.011
3142666NORTHAMPTON
Solar/Wind Harmer
-0.011
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
970099AG2-077 GEN
Solar/Wind Harmer
13.451
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.148
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.195
3145783HORNRTN
Solar/Wind Harmer
0.956
3145783HORNRTN
Solar/Wind Harmer
0.299
3145783HORNRTN
Solar/Wind Harmer
0.12
316426AA2-053 GEN
Solar/Wind Harmer
0.991
316274AC1-208 GEN
Solar/Wind Harmer
1.01
939181AE1-148 GEN
Solar/Wind Harmer
5.143
961601AG1-000A GEN
Solar/Wind Harmer
3.573
316263AC1-034 GEN
Solar/Wind Harmer
4.237
313527AB2-043 GEN
Solar/Wind Harmer
1.432
3145493TOT1
Solar/Wind Harmer
0.134
3145453TOT5
Solar/Wind Harmer
0.08
3145603CNETO
Solar/Wind Harmer
0.054
962561AG1-105 GEN
Solar/Wind Harmer
4.805
964791AG1-342 GEN
Solar/Wind Harmer
1.814
3146843MT LREL
Solar/Wind Harmer
-0.008
3146843MT LREL
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.218
3145893MURPHYS
Solar/Wind Harmer
-0.014
970323AG2-213 GEN
Solar/Wind Harmer
3.913
971775AH1-396 GEN
Solar/Wind Harmer
0.557
316034AC1-036 C
Solar/Wind Harmer
0.145
971741AH1-377 GEN
Solar/Wind Harmer
8.992
316222AC1-221 GEN
Solar/Wind Harmer
0.773
3145933PARMELE
Solar/Wind Harmer
-0.015
3145933PARMELE
Solar/Wind Harmer
-0.008
970301AG2-198 GEN
Solar/Wind Harmer
3.536
958211AF2-115 GEN
Solar/Wind Harmer
1.089
963191AG1-168 GEN
Solar/Wind Harmer
0.653
3144293JTRSVLE
Adder
0.197
3144293JTRSVLE
Adder
0.166
3147133PAMPLIN
Solar/Wind Harmer
-0.007
3147133PAMPLIN
Solar/Wind Harmer
-0.005
316065AD1-022 GEN
Solar/Wind Harmer
3.333
316240AF1-291 C
Solar/Wind Helper
0.486
966871AG1-558 GEN
Solar/Wind Helper
0.151
316478AD1-087 GEN
Solar/Wind Harmer
0.88
316486AD2-202 GEN
Solar/Wind Harmer
0.258
315724AD1-057 GEN
Solar/Wind Harmer
0.578
316327AA2-057 GEN
Solar/Wind Harmer
0.925
3146233WITAKRS
Solar/Wind Harmer
0.19
3146233WITAKRS
Solar/Wind Harmer
-0.006
961601AG1-000A GEN
Solar/Wind Harmer
3.618
3138543CONSLDL
Solar/Wind Harmer
-0.006
316210AC1-098 GEN
Solar/Wind Harmer
1.418
3145543BTLEBRO
Solar/Wind Harmer
-0.009
3145543BTLEBRO
Solar/Wind Harmer
-0.009
316131AB2-060 GEN
Solar/Wind Harmer
0.944
3146073TAR RVR
Solar/Wind Harmer
-0.009
3146083TARBORO
Solar/Wind Harmer
-0.009
3146263WOODLND
Solar/Wind Harmer
-0.009
964241AG1-285 GEN
Solar/Wind Harmer
6.613
316317KELFORD C
Solar/Wind Harmer
0.394
3145823KELFORD
Solar/Wind Harmer
-0.008
316248AF1-058 C
Solar/Wind Harmer
0.249
960061AF2-297 GEN
Solar/Wind Harmer
4.13
315785AD2-033 C
Solar/Wind Harmer
1.813
316463AE2-346 GEN
Solar/Wind Harmer
0.129
316140AB2-099
Solar/Wind Harmer
0.054
962331AG1-082 GEN
Solar/Wind Harmer
0.994
3146173TUNIS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.185
961681AG1-008 GEN
Solar/Wind Harmer
6.185
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
970257AG2-171 GEN
Solar/Wind Harmer
2.935
959311AF2-222 GEN
Solar/Wind Harmer
8.036
316283AC2-100 C
Solar/Wind Harmer
0.716
3145933PARMELE
Solar/Wind Harmer
-0.008
966801AG1-551 GEN
Solar/Wind Harmer
0.948
3156081AA2-088 GEN
Solar/Wind Harmer
2.463
3156021HOLLOMANSOL
Solar/Wind Harmer
1.02
971683AH1-343 GEN
Solar/Wind Harmer
3.191
970909AG2-566 GEN
Solar/Wind Harmer
0.671
3145963POPLR C
Solar/Wind Harmer
-0.007
963181AG1-167 GEN
Solar/Wind Harmer
0.653
3144293JTRSVLE
Adder
0.197
3146206CASHIE
Solar/Wind Harmer
-0.007
3147133PAMPLIN
Solar/Wind Harmer
-0.021
971193AH1-056 GEN
Solar/Wind Harmer
4.174
315737AD1-076 GEN
Solar/Wind Harmer
1.206
316473AC1-191 GEN
Solar/Wind Helper
0.683
315779AE2-040
50/50
2.552
315244AE2-183_ST
50/50
3.298
963041AG1-153 GEN
50/50
3.029
316315AB2-025 C
Solar/Wind Harmer
0.554
315814AE2-033 C
Solar/Wind Harmer
18.846
941031AE2-094 GEN
Solar/Wind Harmer
25.237
944011AF1-069 GEN
Solar/Wind Harmer
7.908
970673AG2-436 GEN
Solar/Wind Harmer
27.602
970673AG2-436 GEN
Solar/Wind Harmer
13.976
946281AF1-292 GEN
Solar/Wind Harmer
0.291
971967AH1-528 GEN
Solar/Wind Harmer
24.041
970085AG2-068 GEN
Solar/Wind Harmer
7.59
970581AG2-369 GEN
Solar/Wind Harmer
6.528
316087AB2-174 GEN
Solar/Wind Harmer
1.725
315652AC1-086 GEN
Solar/Wind Harmer
12.993
3145796HORNRTN
Solar/Wind Harmer
-0.036
3145796HORNRTN
Solar/Wind Harmer
-0.004
3137643SOCKMAN
Solar/Wind Harmer
-0.043
970831AG2-522 GEN
Solar/Wind Harmer
4.811
315607AA1-063A GEN
Solar/Wind Harmer
0.934
316319Z2-044 C
Solar/Wind Harmer
0.502
3146043SEABORD
Solar/Wind Harmer
-0.009
316239AB2-077_GEN
Solar/Wind Harmer
0.266
316238AB2-078_GEN
Solar/Wind Harmer
0.266
3146033SCOT NK
Solar/Wind Harmer
-0.035
3145573BETHELC
Solar/Wind Harmer
-0.009
3145573BETHELC
Solar/Wind Harmer
-0.009
316420AA1-050 GEN
Solar/Wind Harmer
0.969
316118AC1-105 GEN
Solar/Wind Harmer
0.576
957861AF2-080 GEN
Solar/Wind Harmer
3.624
3147173SINAI
Solar/Wind Harmer
-0.008
3147243WELCO
Solar/Wind Harmer
-0.005
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145513AHOSKIE
Solar/Wind Harmer
0.069
961941AG1-037 GEN
Solar/Wind Harmer
0.06
3145513AHOSKIE
Solar/Wind Harmer
-0.008
971443AH1-215 GEN
Solar/Wind Harmer
1.548
316005AA1-067
Solar/Wind Harmer
0.159
3145746EVERETS
Solar/Wind Harmer
-0.031
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
970181AG2-120 GEN
Solar/Wind Harmer
1.032
316318V4-068
Solar/Wind Harmer
0.195
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3144303KENBRDG
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.689
970683AG2-441 GEN
Solar/Wind Harmer
5.769
970681AG2-440 GEN
Solar/Wind Harmer
4.615
970865AG2-541 GEN
Solar/Wind Harmer
2.838
946301AF1-294 GEN
Solar/Wind Harmer
1.786
961791AG1-021 GEN
Solar/Wind Harmer
0.871
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.997
315657AE1-056 GEN
Solar/Wind Harmer
2.505
270455AD2-022 GEN
Solar/Wind Harmer
1.161
270457AD2-023 GEN
Solar/Wind Harmer
0.589
3143316POE
Solar/Wind Harmer
-0.025
315732AD1-074 GEN1
Solar/Wind Harmer
1.284
315733AD1-074 GEN2
Solar/Wind Harmer
1.284
315735AD1-075 GEN1
Solar/Wind Harmer
0.642
316132AB2-190 GEN1
Solar/Wind Helper
0.849
LAGNLTFEXP_LAGN->PJM
CLTF
3.517
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.061
TVALTFEXP_TVA->PJM
CLTF
1.752
CPLELTFEXP_CPLE->PJM
CLTF
5.162
CBM West 2LTFEXP_CBM-W2->PJM
CBM
18.55
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.341
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.001
MECLTFEXP_MEC->PJM
CLTF
1.715
SIGELTFEXP_SIGE->PJM
CLTF
0.051
NYPJM->LTFIMP_NY
CLTF
0.626
LGEELTFEXP_LGEE->PJM
CLTF
0.616
WECLTFEXP_WEC->PJM
CLTF
0.321

Details for 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.06 %
Rating:1039.5 MVA
Rating Type:C
MVA to Mitigate:1092.07
MW Contribution:5.39
Bus #Bus NameTypeMW Contribution
315244AE2-183_ST
50/50
3.947
963041AG1-153 GEN
50/50
3.597
941031AE2-094 GEN
Solar/Wind Harmer
30.716
944011AF1-069 GEN
Solar/Wind Harmer
9.624
970673AG2-436 GEN
Solar/Wind Harmer
33.229
970673AG2-436 GEN
Solar/Wind Harmer
16.825
971967AH1-528 GEN
Solar/Wind Harmer
28.628
970085AG2-068 GEN
Solar/Wind Harmer
8.78
970581AG2-369 GEN
Solar/Wind Harmer
7.55
3147173SINAI
Solar/Wind Harmer
-0.007
3147243WELCO
Solar/Wind Harmer
-0.004
316118AC1-105 GEN
Solar/Wind Harmer
0.435
316315AB2-025 C
Solar/Wind Helper
0.644
3143316POE
Solar/Wind Helper
1.545
946281AF1-292 GEN
Solar/Wind Helper
0.143
316132AB2-190 GEN1
Solar/Wind Helper
0.692
316087AB2-174 GEN
Solar/Wind Helper
0.788
3151031BRUNSWICKG2
50/50
1.776
970917AG2-570 GEN
Solar/Wind Harmer
35.395
316478AD1-087 GEN
Solar/Wind Harmer
0.919
316486AD2-202 GEN
Solar/Wind Harmer
0.269
970909AG2-566 GEN
Solar/Wind Harmer
0.698
316248AF1-058 C
Solar/Wind Harmer
0.206
960061AF2-297 GEN
Solar/Wind Harmer
3.421
315839AE2-212 C
Solar/Wind Helper
0.418
316365GEN2_N
Solar/Wind Helper
0.815
966621AG1-532 GEN
Solar/Wind Helper
0.13
970533AG2-339 GEN
50/50
12.961
970531AG2-338 GEN
50/50
5.184
315242AE2-183_GT2
50/50
2.283
315241AE2-183_GT1
50/50
2.269
972185AH1-677 GEN
50/50
8.231
3151041BRUNSWICKG3
50/50
1.776
972187AH1-678 GEN
50/50
4.076
970933AG2-581 GEN
Solar/Wind Harmer
13.348
970099AG2-077 GEN
Solar/Wind Harmer
14.675
971741AH1-377 GEN
Solar/Wind Harmer
9.409
970301AG2-198 GEN
Solar/Wind Harmer
3.678
3144356SAPONY
Solar/Wind Helper
0.758
316240AF1-291 C
Solar/Wind Helper
0.337
315243AE2-183_GT3
50/50
2.283
3151051BRUNSWICKS1
50/50
3.687
3151021BRUNSWICKG1
50/50
1.776
971451AH1-221 GEN
50/50
5.395
970919AG2-571 GEN
Solar/Wind Harmer
4.48
970087AG2-069 GEN
Solar/Wind Harmer
13.169
939411AE1-173 GEN
Solar/Wind Harmer
59.872
957481AF2-042 GEN
Solar/Wind Harmer
36.689
315693AD1-088 GEN
Solar/Wind Harmer
5.287
962491AG1-098 GEN
Solar/Wind Harmer
6.96
315687AD1-152 GEN
Solar/Wind Harmer
1.13
316003AC1-222 GEN
Solar/Wind Harmer
0.631
316023GEN1_S
Solar/Wind Helper
0.815
316381AD1-082 GEN
Solar/Wind Helper
0.932
3142543TWELFTH
Solar/Wind Helper
0.014
316458AB2-190 GEN2
Solar/Wind Helper
0.692
LAGNLTFEXP_LAGN->PJM
CLTF
2.783
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.387
TVALTFEXP_TVA->PJM
CLTF
1.388
CPLELTFEXP_CPLE->PJM
CLTF
3.694
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.813
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.35
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.768
MECLTFEXP_MEC->PJM
CLTF
1.39
SIGELTFEXP_SIGE->PJM
CLTF
0.042
NYPJM->LTFIMP_NY
CLTF
0.461
LGEELTFEXP_LGEE->PJM
CLTF
0.504
WECLTFEXP_WEC->PJM
CLTF
0.263

Details for 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P4-2: 56372_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:150.06 %
Rating:1056.8 MVA
Rating Type:C
MVA to Mitigate:1585.79
MW Contribution:6.95
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
2.289
970413AG2-270 GEN
50/50
11.103
970917AG2-570 GEN
Solar/Wind Harmer
45.471
316478AD1-087 GEN
Solar/Wind Harmer
1.154
316486AD2-202 GEN
Solar/Wind Harmer
0.338
315773AC2-141 GEN
Solar/Wind Harmer
4.566
970909AG2-566 GEN
Solar/Wind Harmer
0.861
944581AF1-123 GEN
Solar/Wind Harmer
39.916
944601AF1-125 GEN
Solar/Wind Harmer
39.293
316248AF1-058 C
Solar/Wind Harmer
0.247
960061AF2-297 GEN
Solar/Wind Harmer
4.091
3151101ELIZAR3
Adder
6.215
316283AC2-100 C
Solar/Wind Harmer
0.699
971683AH1-343 GEN
Solar/Wind Harmer
3.159
3144873MCLAUGH
Solar/Wind Harmer
0
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.87
316320Y1-086
Solar/Wind Harmer
0.371
315839AE2-212 C
Solar/Wind Helper
0.734
315244AE2-183_ST
50/50
5.093
963041AG1-153 GEN
50/50
4.635
3151541CLOVER2
50/50
2.532
941031AE2-094 GEN
Solar/Wind Harmer
39.728
944011AF1-069 GEN
Solar/Wind Harmer
12.448
970673AG2-436 GEN
Solar/Wind Harmer
42.909
970673AG2-436 GEN
Solar/Wind Harmer
21.726
971967AH1-528 GEN
Solar/Wind Harmer
36.888
970085AG2-068 GEN
Solar/Wind Harmer
11.275
970581AG2-369 GEN
Solar/Wind Harmer
9.696
3147173SINAI
Solar/Wind Harmer
-0.008
3147243WELCO
Solar/Wind Harmer
-0.005
3151081ELIZAR1
Adder
6.136
3151091ELIZAR2
Adder
6.029
316118AC1-105 GEN
Solar/Wind Harmer
0.506
315243AE2-183_GT3
50/50
2.946
3151051BRUNSWICKS1
50/50
4.751
3151021BRUNSWICKG1
50/50
2.289
971451AH1-221 GEN
50/50
6.952
3151531CLOVER1
50/50
2.544
940641AE2-051 GEN
Solar/Wind Harmer
19.26
970919AG2-571 GEN
Solar/Wind Harmer
5.756
970087AG2-069 GEN
Solar/Wind Harmer
16.912
939411AE1-173 GEN
Solar/Wind Harmer
86.789
957481AF2-042 GEN
Solar/Wind Harmer
46.49
315693AD1-088 GEN
Solar/Wind Harmer
6.649
962491AG1-098 GEN
Solar/Wind Harmer
8.746
315687AD1-152 GEN
Solar/Wind Harmer
1.407
316294AC1-161 GEN
Solar/Wind Harmer
3.53
944591AF1-124 GEN
Solar/Wind Harmer
40.06
316003AC1-222 GEN
Solar/Wind Harmer
0.754
316388AE2-253 GEN
Solar/Wind Harmer
0.496
316375AC2-012 GEN
Solar/Wind Harmer
2.531
3150981CHESPKA
Adder
0.813
3146456SLIGO L269
Solar/Wind Harmer
-0.007
970401AG2-262 GEN
Solar/Wind Harmer
0.425
316023GEN1_S
Solar/Wind Helper
1.533
316381AD1-082 GEN
Solar/Wind Helper
1.562
3142543TWELFTH
Solar/Wind Helper
0.023
316011AB1-132 GEN
Solar/Wind Helper
2.299
3145796HORNRTN
Solar/Wind Helper
0.619
3145796HORNRTN
Solar/Wind Helper
0.187
316458AB2-190 GEN2
Solar/Wind Helper
1.032
3143526WINTERP
Solar/Wind Helper
0.702
3142433PROV 92
Solar/Wind Helper
0.503
3143226MDLTHAN
Solar/Wind Helper
0.121
3142416OLDCHRC
Solar/Wind Helper
0.302
3142416OLDCHRC
Solar/Wind Helper
0.116
3152611GOSPORTB
Adder
0.827
3152621GOSPORTC
Adder
0.702
3152601GOSPORTA
Adder
0.647
957871AF2-081 GEN
Solar/Wind Harmer
3.642
319010AE1-072 C
Solar/Wind Harmer
1.431
3146406KITTY HAWK
Solar/Wind Harmer
0.006
970865AG2-541 GEN
Solar/Wind Harmer
2.808
313526AB2-022
Solar/Wind Harmer
0.171
316315AB2-025 C
Solar/Wind Helper
1.176
3143316POE
Solar/Wind Helper
2.759
946281AF1-292 GEN
Solar/Wind Helper
0.283
316087AB2-174 GEN
Solar/Wind Helper
1.592
3145796HORNRTN
Solar/Wind Helper
0.6
3145796HORNRTN
Solar/Wind Helper
0.075
316132AB2-190 GEN1
Solar/Wind Helper
1.032
3137643SOCKMAN
Solar/Wind Helper
0.624
316233AE1-074 FULL
Solar/Wind Helper
0.206
316369SG1_INVT
Solar/Wind Helper
0.569
316312AB1-027
Solar/Wind Helper
0.221
970533AG2-339 GEN
50/50
16.763
970531AG2-338 GEN
50/50
6.705
315242AE2-183_GT2
50/50
2.946
315241AE2-183_GT1
50/50
2.928
972185AH1-677 GEN
50/50
10.62
3151041BRUNSWICKG3
50/50
2.289
972187AH1-678 GEN
50/50
5.253
970933AG2-581 GEN
Solar/Wind Harmer
17.132
970099AG2-077 GEN
Solar/Wind Harmer
18.596
971741AH1-377 GEN
Solar/Wind Harmer
11.67
970301AG2-198 GEN
Solar/Wind Harmer
4.534
316185AD1-033 GEN
Solar/Wind Harmer
0.819
3145506HICKORY
Solar/Wind Harmer
-0.03
3145506HICKORY
Solar/Wind Harmer
-0.018
3145506HICKORY
Solar/Wind Harmer
-0.005
3142956BIRDNECK
Solar/Wind Harmer
0.405
316316AC1-027 C
Solar/Wind Harmer
0.23
316222AC1-221 GEN
Solar/Wind Harmer
0.758
316339AD2-160 GEN
Solar/Wind Harmer
0.496
316036AC1-147 C
Solar/Wind Harmer
0.197
3150991CHESPKB
Adder
0.682
3150991CHESPKB
Adder
0.665
316018AA1-139 ULT2
Solar/Wind Harmer
0.624
316017AA1-139 ULT1
Solar/Wind Harmer
0.589
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.843
3130086AYDLETT
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.007
3146843MT LREL
Solar/Wind Harmer
-0.007
964791AG1-342 GEN
Solar/Wind Harmer
1.391
3146386ELIZ CT
Solar/Wind Harmer
-0.006
3144356SAPONY
Solar/Wind Helper
1.384
316240AF1-291 C
Solar/Wind Helper
0.58
316181AB2-040 GEN
Solar/Wind Helper
1.463
3142666NORTHAMPTON
Solar/Wind Helper
0.188
3142666NORTHAMPTON
Solar/Wind Helper
0.188
3142666NORTHAMPTON
Solar/Wind Helper
0.188
3142666NORTHAMPTON
Solar/Wind Helper
0.112
3145796HORNRTN
Solar/Wind Helper
0.562
3142946ENON
Solar/Wind Helper
0.015
966871AG1-558 GEN
Solar/Wind Helper
0.195
3143526WINTERP
Solar/Wind Helper
0.702
316468AD1-105 GEN
Solar/Wind Helper
0.616
316033AB2-134 GEN
Solar/Wind Helper
0.407
315697AD1-025 GEN
Solar/Wind Helper
1.353
3145593CAROLNA
Solar/Wind Helper
0.116
3145593CAROLNA
Solar/Wind Helper
0.116
316365GEN2_N
Solar/Wind Helper
1.533
966621AG1-532 GEN
Solar/Wind Helper
0.257
313506AB2-031 GEN
Solar/Wind Helper
0.926
3142666NORTHAMPTON
Solar/Wind Helper
0.188
3145796HORNRTN
Solar/Wind Helper
0.75
3145796HORNRTN
Solar/Wind Helper
0.187
3147043LAWRENC
Solar/Wind Helper
0.104
3142946ENON
Solar/Wind Helper
0.049
316473AC1-191 GEN
Solar/Wind Helper
0.882
LAGNLTFEXP_LAGN->PJM
CLTF
3.312
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.993
TVALTFEXP_TVA->PJM
CLTF
1.652
CPLELTFEXP_CPLE->PJM
CLTF
4.36
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.578
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.972
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.67
MECLTFEXP_MEC->PJM
CLTF
1.642
SIGELTFEXP_SIGE->PJM
CLTF
0.049
NYPJM->LTFIMP_NY
CLTF
0.573
LGEELTFEXP_LGEE->PJM
CLTF
0.594
WECLTFEXP_WEC->PJM
CLTF
0.31

Details for 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 562T563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.2 %
Rating:1056.8 MVA
Rating Type:C
MVA to Mitigate:1175.18
MW Contribution:5.78
Bus #Bus NameTypeMW Contribution
970533AG2-339 GEN
50/50
13.883
970531AG2-338 GEN
50/50
5.553
315242AE2-183_GT2
50/50
2.446
315241AE2-183_GT1
50/50
2.431
972185AH1-677 GEN
50/50
8.817
3151041BRUNSWICKG3
50/50
1.903
972187AH1-678 GEN
50/50
4.366
970933AG2-581 GEN
Solar/Wind Harmer
14.297
970099AG2-077 GEN
Solar/Wind Harmer
15.72
971741AH1-377 GEN
Solar/Wind Harmer
10.078
970301AG2-198 GEN
Solar/Wind Harmer
3.939
315244AE2-183_ST
50/50
4.228
963041AG1-153 GEN
50/50
3.852
941031AE2-094 GEN
Solar/Wind Harmer
32.902
944011AF1-069 GEN
Solar/Wind Harmer
10.309
970673AG2-436 GEN
Solar/Wind Harmer
35.593
970673AG2-436 GEN
Solar/Wind Harmer
18.022
971967AH1-528 GEN
Solar/Wind Harmer
30.665
970085AG2-068 GEN
Solar/Wind Harmer
9.404
970581AG2-369 GEN
Solar/Wind Harmer
8.088
3147173SINAI
Solar/Wind Harmer
-0.007
3147243WELCO
Solar/Wind Harmer
-0.005
316118AC1-105 GEN
Solar/Wind Harmer
0.466
316315AB2-025 C
Solar/Wind Helper
0.69
3143316POE
Solar/Wind Helper
1.655
946281AF1-292 GEN
Solar/Wind Helper
0.154
316132AB2-190 GEN1
Solar/Wind Helper
0.741
316087AB2-174 GEN
Solar/Wind Helper
0.844
3151031BRUNSWICKG2
50/50
1.903
970917AG2-570 GEN
Solar/Wind Harmer
37.913
316478AD1-087 GEN
Solar/Wind Harmer
0.984
316486AD2-202 GEN
Solar/Wind Harmer
0.288
970909AG2-566 GEN
Solar/Wind Harmer
0.748
316248AF1-058 C
Solar/Wind Harmer
0.221
960061AF2-297 GEN
Solar/Wind Harmer
3.664
316283AC2-100 C
Solar/Wind Harmer
0.622
971683AH1-343 GEN
Solar/Wind Harmer
2.83
315839AE2-212 C
Solar/Wind Helper
0.448
316365GEN2_N
Solar/Wind Helper
0.873
966621AG1-532 GEN
Solar/Wind Helper
0.139
316222AC1-221 GEN
Solar/Wind Harmer
0.674
3144356SAPONY
Solar/Wind Helper
0.812
316240AF1-291 C
Solar/Wind Helper
0.361
315243AE2-183_GT3
50/50
2.446
3151051BRUNSWICKS1
50/50
3.949
3151021BRUNSWICKG1
50/50
1.903
971451AH1-221 GEN
50/50
5.779
970919AG2-571 GEN
Solar/Wind Harmer
4.799
970087AG2-069 GEN
Solar/Wind Harmer
14.106
939411AE1-173 GEN
Solar/Wind Harmer
64.131
957481AF2-042 GEN
Solar/Wind Harmer
39.299
315693AD1-088 GEN
Solar/Wind Harmer
5.663
962491AG1-098 GEN
Solar/Wind Harmer
7.455
315687AD1-152 GEN
Solar/Wind Harmer
1.21
316003AC1-222 GEN
Solar/Wind Harmer
0.675
316023GEN1_S
Solar/Wind Helper
0.873
316381AD1-082 GEN
Solar/Wind Helper
0.998
3142543TWELFTH
Solar/Wind Helper
0.015
316458AB2-190 GEN2
Solar/Wind Helper
0.741
316011AB1-132 GEN
Solar/Wind Helper
1.246
LAGNLTFEXP_LAGN->PJM
CLTF
2.98
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.983
TVALTFEXP_TVA->PJM
CLTF
1.486
CPLELTFEXP_CPLE->PJM
CLTF
3.956
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.867
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.015
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.108
MECLTFEXP_MEC->PJM
CLTF
1.489
SIGELTFEXP_SIGE->PJM
CLTF
0.045
NYPJM->LTFIMP_NY
CLTF
0.494
LGEELTFEXP_LGEE->PJM
CLTF
0.54
WECLTFEXP_WEC->PJM
CLTF
0.282

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:139.66 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:4497.83
MW Contribution:13.79
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
5.789
3151051BRUNSWICKS1
50/50
9.423
3151021BRUNSWICKG1
50/50
4.54
971451AH1-221 GEN
50/50
13.79
3151531CLOVER1
50/50
5.905
940641AE2-051 GEN
Solar/Wind Harmer
28.987
939411AE1-173 GEN
Solar/Wind Harmer
145.254
970919AG2-571 GEN
Solar/Wind Harmer
11.736
970087AG2-069 GEN
Solar/Wind Harmer
26.275
957481AF2-042 GEN
Solar/Wind Harmer
77.806
316294AC1-161 GEN
Solar/Wind Harmer
4.901
944591AF1-124 GEN
Solar/Wind Harmer
62.818
316388AE2-253 GEN
Solar/Wind Harmer
0.855
3146456SLIGO L269
Solar/Wind Harmer
0.272
315693AD1-088 GEN
Solar/Wind Harmer
13.02
316375AC2-012 GEN
Solar/Wind Harmer
0.007
3150981CHESPKA
Adder
3.38
316246AF1-032 C
Solar/Wind Harmer
0.122
3146516WINFALL
Solar/Wind Harmer
0.867
3146516WINFALL
Solar/Wind Harmer
0.268
962491AG1-098 GEN
Solar/Wind Harmer
15.268
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
316093AE2-104_GEN
Solar/Wind Harmer
4.461
316023GEN1_S
Solar/Wind Harmer
0.594
3130156CHOWAN
Solar/Wind Harmer
0.263
3145663CRESWEL
Solar/Wind Harmer
0.728
971163AH1-040 GEN
Solar/Wind Harmer
20.811
316072AD1-144
Solar/Wind Harmer
0.094
315687AD1-152 GEN
Solar/Wind Harmer
0.008
960081AF2-299 GEN
Solar/Wind Harmer
2.469
3146206CASHIE
Solar/Wind Harmer
0.256
971547AH1-271 GEN
Solar/Wind Harmer
5.457
3145893MURPHYS
Solar/Wind Harmer
1.02
3145893MURPHYS
Solar/Wind Harmer
1.134
316011AB1-132 GEN
Solar/Wind Harmer
4.622
962571AG1-106 GEN
Solar/Wind Harmer
3.617
3146173TUNIS
Solar/Wind Harmer
0.254
3145683EARLEYS
Solar/Wind Harmer
0.253
3146263WOODLND
Solar/Wind Harmer
0.252
316190AA2-174 GEN
Solar/Wind Harmer
0
3145796HORNRTN
Solar/Wind Harmer
0.829
3145796HORNRTN
Solar/Wind Harmer
0.251
971795AH1-408 GEN
Solar/Wind Harmer
16.715
3145823KELFORD
Solar/Wind Harmer
0.25
3145783HORNRTN
Solar/Wind Harmer
0.25
3145963POPLR C
Solar/Wind Harmer
0.249
316174AB2-169 GEN
Solar/Wind Harmer
0.007
3147043LAWRENC
Adder
2.242
316212AC1-099_GEN
Solar/Wind Harmer
1.268
316129AC1-054 GEN
Solar/Wind Harmer
0.918
970661AG2-428 GEN
Solar/Wind Harmer
24.263
971065AG2-659 GEN
Solar/Wind Harmer
10.39
3145336SMITFLD
Solar/Wind Harmer
0.973
3146293MARTNCO
Solar/Wind Harmer
0.225
315722AD1-056 GEN
Solar/Wind Harmer
1.532
3145746EVERETS
Solar/Wind Harmer
0.24
3145746EVERETS
Solar/Wind Harmer
0.24
316381AD1-082 GEN
Solar/Wind Harmer
0.249
316494AC1-189 GEN
Solar/Wind Harmer
0.804
970659AG2-427 GEN
Solar/Wind Harmer
11.496
3146233WITAKRS
Solar/Wind Harmer
0.942
961671AG1-007 GEN
Solar/Wind Harmer
0.036
3146083TARBORO
Solar/Wind Harmer
0.236
3145493TOT1
Solar/Wind Harmer
1.05
316359AB2-059 GEN
Solar/Wind Harmer
0.841
316049AB1-081 GEN
Solar/Wind Harmer
1.34
3145543BTLEBRO
Solar/Wind Harmer
0.234
3145543BTLEBRO
Solar/Wind Harmer
0.187
3142053HEARTS
Solar/Wind Harmer
0.412
316237AB2-079_GEN
Solar/Wind Harmer
0.002
3151171GRAVELC
Adder
2.407
970401AG2-262 GEN
Solar/Wind Harmer
1.317
3138126ROCKLANDING
Solar/Wind Harmer
0.101
961611AG1-000B GEN
Solar/Wind Harmer
11.332
316003AC1-222 GEN
Solar/Wind Harmer
0.006
971647AH1-324 GEN
Solar/Wind Harmer
8.873
971317AH1-138 GEN
Solar/Wind Harmer
1.539
970685AG2-442 GEN
Solar/Wind Harmer
14.697
971069AG2-661 GEN
Solar/Wind Harmer
3.441
316159AE1-175 C
Solar/Wind Harmer
0.165
963171AG1-166 GEN
Solar/Wind Harmer
1.004
971563AH1-280 GEN
Solar/Wind Harmer
2.008
3144293JTRSVLE
Adder
0.599
316458AB2-190 GEN2
Solar/Wind Harmer
0.989
315671AE2-027_GEN
Solar/Wind Harmer
11.755
970129AG2-093 GEN
Solar/Wind Harmer
5.199
971777AH1-397 GEN
Solar/Wind Harmer
0.395
3141843SHACKLE
Adder
0.764
3141766HARMONY
Solar/Wind Harmer
0.03
3146926FARMVIL
Solar/Wind Harmer
0.088
3138133OCRAN
Solar/Wind Harmer
0.087
3142433PROV 92
Solar/Wind Harmer
0.557
3142433PROV 92
Adder
0.271
3142433PROV 92
Adder
0.271
970223AG2-152 GEN
Solar/Wind Harmer
9.565
944631AF1-128 GEN
Adder
62.411
270016AE1-250 BESS
Solar/Wind Harmer
0.004
962861AG1-135 GEN
Solar/Wind Harmer
4.023
3147123OTTER R
Solar/Wind Harmer
0.07
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
3141726DUNNSVL
Solar/Wind Harmer
0.457
316045AC1-158 PL2
Solar/Wind Helper
5.221
3147666LOUISA
Solar/Wind Helper
1.002
316192AB2-158 GEN
Solar/Wind Helper
1.658
316254AC1-120 GEN1
Solar/Wind Helper
1.035
315244AE2-183_ST
50/50
10.008
963041AG1-153 GEN
50/50
9.194
315779AE2-040
50/50
3.994
3151541CLOVER2
50/50
5.877
3151081ELIZAR1
50/50
26.432
941031AE2-094 GEN
Solar/Wind Harmer
66.901
944011AF1-069 GEN
Solar/Wind Harmer
21.859
970673AG2-436 GEN
Solar/Wind Harmer
75.678
970673AG2-436 GEN
Solar/Wind Harmer
50.452
971967AH1-528 GEN
Solar/Wind Harmer
55.275
970085AG2-068 GEN
Solar/Wind Harmer
17.517
970581AG2-369 GEN
Solar/Wind Harmer
15.064
316315AB2-025 C
Solar/Wind Harmer
0.231
315814AE2-033 C
Solar/Wind Harmer
22.552
957871AF2-081 GEN
Solar/Wind Harmer
13.58
319010AE1-072 C
Solar/Wind Harmer
1.371
3146406KITTY HAWK
Solar/Wind Harmer
0.034
3151091ELIZAR2
Adder
24.477
3152611GOSPORTB
Adder
3.448
3152621GOSPORTC
Adder
2.926
3152601GOSPORTA
Adder
2.699
313526AB2-022
Solar/Wind Harmer
0.146
316305AF2-043 C
Solar/Wind Harmer
0.002
316321Z2-027
Solar/Wind Harmer
0.05
3146396TANGLEW
Solar/Wind Harmer
0.743
3145176PASQUOTANK
Solar/Wind Harmer
0.167
3146486SUNBURY
Solar/Wind Harmer
0.269
3146486SUNBURY
Solar/Wind Harmer
0.269
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
315835AF2-110_GEN
Solar/Wind Harmer
1.82
3130156CHOWAN
Solar/Wind Harmer
0.263
3130156CHOWAN
Solar/Wind Harmer
0.263
315816AE2-034 GEN
Solar/Wind Harmer
1.116
3130546PLYMOUTH
Solar/Wind Harmer
0.257
315732AD1-074 GEN1
Solar/Wind Harmer
1.477
315733AD1-074 GEN2
Solar/Wind Harmer
1.477
315735AD1-075 GEN1
Solar/Wind Harmer
0.74
965291AG1-394 GEN
Solar/Wind Harmer
1.138
3146206CASHIE
Solar/Wind Harmer
0.256
970601AG2-382 GEN
Solar/Wind Harmer
9.549
316311AC2-079 GEN
Solar/Wind Harmer
7.334
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.175
316087AB2-174 GEN
Solar/Wind Harmer
0.007
3145893MURPHYS
Solar/Wind Harmer
0.688
3145893MURPHYS
Solar/Wind Harmer
0.255
315652AC1-086 GEN
Solar/Wind Harmer
27.966
3145513AHOSKIE
Solar/Wind Harmer
0.53
3145513AHOSKIE
Solar/Wind Harmer
0.253
3146043SEABORD
Solar/Wind Harmer
0.253
315607AA1-063A GEN
Solar/Wind Harmer
0.517
3145683EARLEYS
Solar/Wind Harmer
0.506
3145683EARLEYS
Solar/Wind Harmer
0.253
3145683EARLEYS
Solar/Wind Harmer
0.253
3137643SOCKMAN
Solar/Wind Harmer
1.009
3145796HORNRTN
Solar/Wind Harmer
0.804
3145796HORNRTN
Solar/Wind Harmer
0.101
3146033SCOT NK
Solar/Wind Harmer
0.989
970831AG2-522 GEN
Solar/Wind Harmer
10.446
3143316POE
Solar/Wind Harmer
0.965
971445AH1-216 GEN
Solar/Wind Harmer
17.029
316005AA1-067
Solar/Wind Harmer
0.257
3145746EVERETS
Solar/Wind Harmer
0.955
3145746EVERETS
Solar/Wind Harmer
0.24
3145746EVERETS
Solar/Wind Harmer
0.24
3145746EVERETS
Solar/Wind Harmer
0.24
970181AG2-120 GEN
Solar/Wind Harmer
2.987
957861AF2-080 GEN
Solar/Wind Harmer
10.262
316420AA1-050 GEN
Solar/Wind Harmer
0.008
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.236
3145573BETHELC
Solar/Wind Harmer
0.236
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
972265AH1-717 GEN
Adder
17.569
3151201GRAVEL4
Adder
16.47
3151191GRAVEL3
Adder
16.261
3151211GRAVEL5
Adder
16.261
316118AC1-105 GEN
Solar/Wind Harmer
0.578
3147173SINAI
Solar/Wind Harmer
0.223
3147243WELCO
Solar/Wind Harmer
0.14
971443AH1-215 GEN
Solar/Wind Harmer
3.472
3144303KENBRDG
Solar/Wind Harmer
0.165
316369SG1_INVT
Solar/Wind Harmer
0.007
970683AG2-441 GEN
Solar/Wind Harmer
13.122
970681AG2-440 GEN
Solar/Wind Harmer
10.498
970865AG2-541 GEN
Solar/Wind Harmer
6.671
946301AF1-294 GEN
Solar/Wind Harmer
3.715
961791AG1-021 GEN
Solar/Wind Harmer
1.807
3138283WHITEMARSH
Solar/Wind Harmer
0.044
316132AB2-190 GEN1
Solar/Wind Harmer
0.989
315657AE1-056 GEN
Solar/Wind Harmer
6.288
316123AC1-075 GEN
Solar/Wind Harmer
0.235
970165AG2-112 GEN
Solar/Wind Harmer
1.394
970163AG2-111 GEN
Solar/Wind Harmer
1.33
3141873WAN 176
Solar/Wind Harmer
0.031
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.431
316059AD1-063 C
Solar/Wind Harmer
0.001
3141913WHIT STONE
Solar/Wind Harmer
0.147
316314AB2-024 C
Solar/Wind Harmer
0.001
3138133OCRAN
Solar/Wind Harmer
0.044
3143873LANEXA
Solar/Wind Harmer
0.086
3141783LANCAST
Solar/Wind Harmer
0.085
3141783LANCAST
Solar/Wind Harmer
0.057
3142433PROV 92
Adder
0.271
3142433PROV 92
Adder
0.271
971167AH1-042 GEN
Solar/Wind Harmer
12.277
315976AC1-164 GENA
Solar/Wind Harmer
14.222
316169AC1-164_GENC
Solar/Wind Harmer
12.287
315975AC1-164 GENB
Solar/Wind Harmer
0.421
962981AG1-147 GEN
Solar/Wind Harmer
5.038
970327AG2-215 GEN
Solar/Wind Harmer
4.29
316164AC1-076 GEN
Solar/Wind Helper
1.17
3151031BRUNSWICKG2
50/50
4.54
970413AG2-270 GEN
50/50
25.77
3151101ELIZAR3
50/50
26.77
970917AG2-570 GEN
Solar/Wind Harmer
29.34
315773AC2-141 GEN
Solar/Wind Harmer
10.33
944581AF1-123 GEN
Solar/Wind Harmer
62.596
944601AF1-125 GEN
Solar/Wind Harmer
61.631
316478AD1-087 GEN
Solar/Wind Harmer
0.962
316486AD2-202 GEN
Solar/Wind Harmer
0.283
3146456SLIGO L269
Solar/Wind Harmer
0.272
971153AH1-033 GEN
Solar/Wind Harmer
3.148
3144873MCLAUGH
Solar/Wind Harmer
0.007
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.268
3146626S HERTFORD
Solar/Wind Harmer
0.267
316365GEN2_N
Solar/Wind Harmer
0.594
3146376EDENTON
Solar/Wind Harmer
0.263
3144536CHRHLND
Solar/Wind Harmer
0.039
3145273HOLLAND
Solar/Wind Harmer
0.197
315614AA2-178 GEN
Solar/Wind Harmer
1.489
971157AH1-035 GEN
Solar/Wind Harmer
3.091
315737AD1-076 GEN
Solar/Wind Harmer
3.308
3156081AA2-088 GEN
Solar/Wind Harmer
0.006
3146206CASHIE
Solar/Wind Harmer
0.256
3145893MURPHYS
Solar/Wind Harmer
0.427
3145893MURPHYS
Solar/Wind Harmer
0.255
957521AF2-046 GEN
Solar/Wind Harmer
18.955
961681AG1-008 GEN
Solar/Wind Harmer
18.955
313506AB2-031 GEN
Solar/Wind Harmer
0.786
3142666NORTHAMPTON
Solar/Wind Harmer
0.254
3146173TUNIS
Solar/Wind Harmer
0.254
3156021HOLLOMANSOL
Solar/Wind Harmer
1.153
316463AE2-346 GEN
Solar/Wind Harmer
0.218
316140AB2-099
Solar/Wind Harmer
0.091
962331AG1-082 GEN
Solar/Wind Harmer
2.704
3146263WOODLND
Solar/Wind Harmer
0.252
3145796HORNRTN
Solar/Wind Harmer
1.005
3145796HORNRTN
Solar/Wind Harmer
0.251
316317KELFORD C
Solar/Wind Harmer
0.024
3145823KELFORD
Solar/Wind Harmer
0.25
3145963POPLR C
Solar/Wind Harmer
0.249
3147043LAWRENC
Solar/Wind Harmer
0.149
316210AC1-098 GEN
Solar/Wind Harmer
2.273
970661AG2-428 GEN
Solar/Wind Harmer
5.16
3145336SMITFLD
Solar/Wind Harmer
0.097
3145933PARMELE
Solar/Wind Harmer
0.243
966801AG1-551 GEN
Solar/Wind Harmer
2.83
315724AD1-057 GEN
Solar/Wind Harmer
0.908
3145746EVERETS
Solar/Wind Harmer
0.24
3145746EVERETS
Solar/Wind Harmer
0.24
316327AA2-057 GEN
Solar/Wind Harmer
0.362
316083AB2-161 GEN
Solar/Wind Harmer
0.003
970659AG2-427 GEN
Solar/Wind Harmer
2.515
3146233WITAKRS
Solar/Wind Harmer
1.189
3146233WITAKRS
Solar/Wind Harmer
0.161
3138543CONSLDL
Solar/Wind Harmer
0.156
3146073TAR RVR
Solar/Wind Harmer
0.236
3146083TARBORO
Solar/Wind Harmer
0.236
961601AG1-000A GEN
Solar/Wind Harmer
16.657
3145543BTLEBRO
Solar/Wind Harmer
0.234
3145543BTLEBRO
Solar/Wind Harmer
0.234
971623AH1-311 GEN
Solar/Wind Harmer
0.468
315813AE1-149 C
Solar/Wind Harmer
12.227
3151221GRAVEL6
Adder
16.451
3151171GRAVELC
Adder
3.165
316131AB2-060 GEN
Solar/Wind Harmer
0.707
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
9.527
3144216WINCHST
Adder
0.83
964241AG1-285 GEN
Solar/Wind Harmer
14.603
3150921YORKTN3
Adder
5.498
961611AG1-000B GEN
Solar/Wind Harmer
5.762
315785AD2-033 C
Solar/Wind Harmer
1.703
316283AC2-100 C
Solar/Wind Harmer
0.406
970257AG2-171 GEN
Solar/Wind Harmer
6.589
959311AF2-222 GEN
Solar/Wind Harmer
18.071
971683AH1-343 GEN
Solar/Wind Harmer
7.451
315839AE2-212 C
Solar/Wind Harmer
0.002
970909AG2-566 GEN
Solar/Wind Harmer
2.128
315778AD1-151 GEN
Solar/Wind Harmer
15.484
316382AG1-145 C
Solar/Wind Harmer
0.002
965281AG1-393 GEN
Solar/Wind Harmer
2.04
963181AG1-167 GEN
Solar/Wind Harmer
0.753
3144293JTRSVLE
Adder
0.599
970129AG2-093 GEN
Solar/Wind Harmer
11.049
3147133PAMPLIN
Solar/Wind Harmer
0.572
971193AH1-056 GEN
Solar/Wind Harmer
11.101
970133AG2-095 GEN
Solar/Wind Harmer
1.61
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316156AD2-030 GEN
Solar/Wind Harmer
0.114
3141873WAN 176
Solar/Wind Harmer
2.731
316280AD1-041 GEN
Solar/Wind Harmer
0.003
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3141843SHACKLE
Adder
0.764
3141766HARMONY
Solar/Wind Harmer
1.984
3146926FARMVIL
Solar/Wind Harmer
0.088
3142433PROV 92
Adder
0.271
3142433PROV 92
Adder
0.271
962971AG1-146 GEN
Solar/Wind Harmer
2.159
3142946ENON
Solar/Wind Harmer
0.044
970009AG2-005 GEN
Solar/Wind Harmer
0.976
316404AE1-155 C
Solar/Wind Harmer
0.028
270018AE2-047 C O1
Solar/Wind Harmer
0.003
270197AD1-017 GEN1
Solar/Wind Harmer
0.766
316044AC1-158 PL1
Solar/Wind Helper
1.631
316450AC1-158 RIC
Solar/Wind Helper
0.435
3147666LOUISA
Solar/Wind Helper
0.576
316170AC1-121 GEN2
Solar/Wind Helper
0.345
970533AG2-339 GEN
50/50
32.288
970531AG2-338 GEN
50/50
12.915
315242AE2-183_GT2
50/50
5.789
315241AE2-183_GT1
50/50
5.753
972185AH1-677 GEN
50/50
20.868
3151041BRUNSWICKG3
50/50
4.54
972187AH1-678 GEN
50/50
10.419
970933AG2-581 GEN
Solar/Wind Harmer
26.407
970099AG2-077 GEN
Solar/Wind Harmer
31.122
3144356SAPONY
Solar/Wind Harmer
2.393
316185AD1-033 GEN
Solar/Wind Harmer
0.008
3145506HICKORY
Solar/Wind Harmer
1.094
3145506HICKORY
Solar/Wind Harmer
0.657
3145506HICKORY
Solar/Wind Harmer
0.164
316339AD2-160 GEN
Solar/Wind Harmer
0.443
316018AA1-139 ULT2
Solar/Wind Harmer
0.007
316017AA1-139 ULT1
Solar/Wind Harmer
0.152
3142956BIRDNECK
Solar/Wind Harmer
0
3137176SLIGO L2192
Solar/Wind Harmer
1.084
3146456SLIGO L269
Solar/Wind Harmer
4.819
316316AC1-027 C
Solar/Wind Harmer
0.261
3130086AYDLETT
Solar/Wind Harmer
1.088
316036AC1-147 C
Solar/Wind Harmer
0.05
3150991CHESPKB
Adder
2.836
3150991CHESPKB
Adder
2.768
3146386ELIZ CT
Solar/Wind Harmer
0.27
316431W1029_GEN1
Solar/Wind Harmer
0.002
316433W1029_GEN2
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.268
3146516WINFALL
Solar/Wind Harmer
0.268
3146516WINFALL
Solar/Wind Harmer
0.268
3146626S HERTFORD
Solar/Wind Harmer
0.267
3146626S HERTFORD
Solar/Wind Harmer
0.267
3146376EDENTON
Solar/Wind Harmer
1.171
3146376EDENTON
Solar/Wind Harmer
1.171
315742AE1-103 GEN
Solar/Wind Harmer
0.003
316065AD1-022 GEN
Solar/Wind Harmer
11.799
3145893MURPHYS
Solar/Wind Harmer
1.706
3145893MURPHYS
Solar/Wind Harmer
0.459
316181AB2-040 GEN
Solar/Wind Harmer
0.369
3142666NORTHAMPTON
Solar/Wind Harmer
0.254
3142666NORTHAMPTON
Solar/Wind Harmer
0.254
3142666NORTHAMPTON
Solar/Wind Harmer
0.254
3142666NORTHAMPTON
Solar/Wind Harmer
0.153
3146173TUNIS
Solar/Wind Harmer
0.254
3146173TUNIS
Solar/Wind Harmer
0.254
316426AA2-053 GEN
Solar/Wind Harmer
0.849
3145796HORNRTN
Solar/Wind Harmer
0.754
3145593CAROLNA
Solar/Wind Harmer
0.251
3145593CAROLNA
Solar/Wind Harmer
0.251
966811AG1-552 GEN
Solar/Wind Harmer
2.724
3145593CAROLNA
Solar/Wind Harmer
0.313
3145783HORNRTN
Solar/Wind Harmer
4.447
3145783HORNRTN
Solar/Wind Harmer
3.557
3145783HORNRTN
Solar/Wind Harmer
1.112
3145783HORNRTN
Solar/Wind Harmer
0.445
316274AC1-208 GEN
Solar/Wind Harmer
1.268
316236AE1-162_GEN
Solar/Wind Harmer
0.002
3145933PARMELE
Solar/Wind Harmer
0.486
3145933PARMELE
Solar/Wind Harmer
0.243
970657AG2-426 GEN
Solar/Wind Harmer
8.443
970657AG2-426 GEN
Solar/Wind Harmer
1.77
939181AE1-148 GEN
Solar/Wind Harmer
11.415
3145493TOT1
Solar/Wind Harmer
0.548
3145453TOT5
Solar/Wind Harmer
0.329
3145603CNETO
Solar/Wind Harmer
0.219
961601AG1-000A GEN
Solar/Wind Harmer
4.164
316263AC1-034 GEN
Solar/Wind Harmer
8.897
313527AB2-043 GEN
Solar/Wind Harmer
0.003
962561AG1-105 GEN
Solar/Wind Harmer
10.79
964791AG1-342 GEN
Solar/Wind Harmer
4.311
3146843MT LREL
Solar/Wind Harmer
0.224
3146843MT LREL
Solar/Wind Harmer
0.224
971741AH1-377 GEN
Solar/Wind Harmer
21.422
316222AC1-221 GEN
Solar/Wind Harmer
0.867
970323AG2-213 GEN
Solar/Wind Harmer
8.785
971775AH1-396 GEN
Solar/Wind Harmer
0.329
316034AC1-036 C
Solar/Wind Harmer
0.015
316033AB2-134 GEN
Solar/Wind Harmer
0.012
315697AD1-025 GEN
Solar/Wind Harmer
0.225
970301AG2-198 GEN
Solar/Wind Harmer
8.511
958211AF2-115 GEN
Solar/Wind Harmer
2.259
963191AG1-168 GEN
Solar/Wind Harmer
0.753
3144293JTRSVLE
Adder
0.599
3144293JTRSVLE
Adder
0.505
3147133PAMPLIN
Solar/Wind Harmer
0.182
3147133PAMPLIN
Solar/Wind Harmer
0.146
316240AF1-291 C
Solar/Wind Harmer
0.001
944641AF1-129 GEN
Adder
78.098
942751AE2-291 GEN
Solar/Wind Harmer
8.652
3142946ENON
Solar/Wind Harmer
0.013
270013AE1-250 PV
Solar/Wind Harmer
0.004
958261AF2-120 GEN
Solar/Wind Harmer
4.097
316075AC2-137 C
Solar/Wind Harmer
0.033
316447AC1-158 HLD
Solar/Wind Helper
3.59
315651AD1-115 GEN
Solar/Wind Helper
0.751
LAGNLTFEXP_LAGN->PJM
CLTF
11.265
CBM South 2LTFEXP_CBM-S2->PJM
CBM
34.702
TVALTFEXP_TVA->PJM
CLTF
5.645
CPLELTFEXP_CPLE->PJM
CLTF
15.998
CBM West 2LTFEXP_CBM-W2->PJM
CBM
59.498
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.7
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.348
MECLTFEXP_MEC->PJM
CLTF
5.484
SIGELTFEXP_SIGE->PJM
CLTF
0.165
NYPJM->LTFIMP_NY
CLTF
2.873
LGEELTFEXP_LGEE->PJM
CLTF
2
WECLTFEXP_WEC->PJM
CLTF
1.023

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 557T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:139.23 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:5485.71
MW Contribution:14.78
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
4.866
3151101ELIZAR3
50/50
30.758
3151161SURRY 1
50/50
10.034
970917AG2-570 GEN
Solar/Wind Harmer
99.341
315773AC2-141 GEN
Solar/Wind Harmer
15.446
944581AF1-123 GEN
Solar/Wind Harmer
163.249
944601AF1-125 GEN
Solar/Wind Harmer
160.701
3146456SLIGO L269
Solar/Wind Harmer
-0.035
971153AH1-033 GEN
Solar/Wind Harmer
4.273
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316320Y1-086
Solar/Wind Harmer
2.034
316435W1029_GEN3
Solar/Wind Harmer
6.217
3146516WINFALL
Solar/Wind Harmer
-0.034
3146626S HERTFORD
Solar/Wind Harmer
-0.034
3144536CHRHLND
Solar/Wind Harmer
-0.005
3146376EDENTON
Solar/Wind Harmer
-0.033
3145273HOLLAND
Solar/Wind Harmer
-0.025
316478AD1-087 GEN
Solar/Wind Harmer
2.871
316486AD2-202 GEN
Solar/Wind Harmer
0.841
315614AA2-178 GEN
Solar/Wind Harmer
3.553
971157AH1-035 GEN
Solar/Wind Harmer
4.06
315737AD1-076 GEN
Solar/Wind Harmer
6.157
316365GEN2_N
Solar/Wind Harmer
2.184
3146206CASHIE
Solar/Wind Harmer
-0.032
3156081AA2-088 GEN
Solar/Wind Harmer
10.416
3145893MURPHYS
Solar/Wind Harmer
0.222
3145893MURPHYS
Solar/Wind Harmer
-0.032
957521AF2-046 GEN
Solar/Wind Harmer
25.046
961681AG1-008 GEN
Solar/Wind Harmer
25.046
3156021HOLLOMANSOL
Solar/Wind Harmer
4.277
3146173TUNIS
Solar/Wind Harmer
-0.032
316463AE2-346 GEN
Solar/Wind Harmer
0.512
316140AB2-099
Solar/Wind Harmer
0.213
962331AG1-082 GEN
Solar/Wind Harmer
3.951
3145336SMITFLD
Solar/Wind Harmer
-0.012
966621AG1-532 GEN
Solar/Wind Harmer
0.638
3146263WOODLND
Solar/Wind Harmer
-0.031
3142666NORTHAMPTON
Solar/Wind Harmer
-0.031
3145963POPLR C
Solar/Wind Harmer
-0.031
313506AB2-031 GEN
Solar/Wind Harmer
2.505
316317KELFORD C
Solar/Wind Harmer
1.464
3145823KELFORD
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.123
3145796HORNRTN
Solar/Wind Harmer
-0.031
970661AG2-428 GEN
Solar/Wind Harmer
5.777
316210AC1-098 GEN
Solar/Wind Harmer
4.739
3147043LAWRENC
Solar/Wind Harmer
-0.018
3145933PARMELE
Solar/Wind Harmer
-0.03
966801AG1-551 GEN
Solar/Wind Harmer
3.768
316083AB2-161 GEN
Solar/Wind Harmer
4.866
970659AG2-427 GEN
Solar/Wind Harmer
2.8
3145746EVERETS
Solar/Wind Harmer
-0.03
3145746EVERETS
Solar/Wind Harmer
-0.03
315243AE2-183_GT3
50/50
6.204
3151051BRUNSWICKS1
50/50
10.099
3151021BRUNSWICKG1
50/50
4.866
971451AH1-221 GEN
50/50
14.779
3150981CHESPKA
50/50
4.121
3152331SURRY 2
50/50
12.732
940641AE2-051 GEN
Solar/Wind Harmer
41.411
939411AE1-173 GEN
Solar/Wind Harmer
209.945
970919AG2-571 GEN
Solar/Wind Harmer
12.575
970087AG2-069 GEN
Solar/Wind Harmer
37.068
316294AC1-161 GEN
Solar/Wind Harmer
11.942
944591AF1-124 GEN
Solar/Wind Harmer
163.837
316388AE2-253 GEN
Solar/Wind Harmer
2.371
957481AF2-042 GEN
Solar/Wind Harmer
109.7
3146456SLIGO L269
Solar/Wind Harmer
-0.035
316375AC2-012 GEN
Solar/Wind Harmer
12.094
316246AF1-032 C
Solar/Wind Harmer
0.702
3146516WINFALL
Solar/Wind Harmer
-0.11
3146516WINFALL
Solar/Wind Harmer
-0.034
316093AE2-104_GEN
Solar/Wind Harmer
9.863
315800Z1-036_GEN1
Solar/Wind Harmer
8.362
3130156CHOWAN
Solar/Wind Harmer
-0.033
316072AD1-144
Solar/Wind Harmer
0.677
3145663CRESWEL
Solar/Wind Harmer
-0.092
971163AH1-040 GEN
Solar/Wind Harmer
30.87
315693AD1-088 GEN
Solar/Wind Harmer
16.313
316023GEN1_S
Solar/Wind Harmer
2.184
962491AG1-098 GEN
Solar/Wind Harmer
21.518
3146206CASHIE
Solar/Wind Harmer
-0.032
971547AH1-271 GEN
Solar/Wind Harmer
8.032
3145893MURPHYS
Solar/Wind Harmer
-0.127
3145893MURPHYS
Solar/Wind Harmer
0.945
3146173TUNIS
Solar/Wind Harmer
-0.032
3145683EARLEYS
Solar/Wind Harmer
-0.031
3145336SMITFLD
Solar/Wind Harmer
-0.125
960081AF2-299 GEN
Solar/Wind Harmer
3.535
3146263WOODLND
Solar/Wind Harmer
-0.031
316011AB1-132 GEN
Solar/Wind Harmer
6.536
962571AG1-106 GEN
Solar/Wind Harmer
4.491
3145963POPLR C
Solar/Wind Harmer
-0.031
3145823KELFORD
Solar/Wind Harmer
-0.031
316190AA2-174 GEN
Solar/Wind Harmer
0.381
316174AB2-169 GEN
Solar/Wind Harmer
4.777
315687AD1-152 GEN
Solar/Wind Harmer
3.732
3145796HORNRTN
Solar/Wind Harmer
-0.101
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145783HORNRTN
Solar/Wind Harmer
-0.031
970661AG2-428 GEN
Solar/Wind Harmer
32.599
971795AH1-408 GEN
Solar/Wind Harmer
22.92
316212AC1-099_GEN
Solar/Wind Harmer
2.633
3147043LAWRENC
Adder
2.429
3146293MARTNCO
Solar/Wind Harmer
0.187
316381AD1-082 GEN
Solar/Wind Harmer
2.75
970659AG2-427 GEN
Solar/Wind Harmer
15.8
316129AC1-054 GEN
Solar/Wind Harmer
2.604
3145746EVERETS
Solar/Wind Harmer
-0.03
3145746EVERETS
Solar/Wind Harmer
-0.03
315722AD1-056 GEN
Solar/Wind Harmer
3.098
971065AG2-659 GEN
Solar/Wind Harmer
14.797
3138126ROCKLANDING
Solar/Wind Harmer
0.09
3151171GRAVELC
Adder
2.779
316494AC1-189 GEN
Solar/Wind Harmer
3.154
3146233WITAKRS
Solar/Wind Harmer
-0.115
961671AG1-007 GEN
Solar/Wind Harmer
0.367
315244AE2-183_ST
50/50
10.726
963041AG1-153 GEN
50/50
9.853
3151081ELIZAR1
50/50
30.369
3151091ELIZAR2
50/50
29.842
941591AE2-156 GEN
50/50
27.695
3152611GOSPORTB
50/50
4.203
3152621GOSPORTC
50/50
3.567
3152601GOSPORTA
50/50
3.291
315779AE2-040
50/50
4.317
972263AH1-716 GEN
50/50
173.856
941031AE2-094 GEN
Solar/Wind Harmer
82.028
944011AF1-069 GEN
Solar/Wind Harmer
25.702
970673AG2-436 GEN
Solar/Wind Harmer
89.749
970673AG2-436 GEN
Solar/Wind Harmer
45.442
971967AH1-528 GEN
Solar/Wind Harmer
78.206
970085AG2-068 GEN
Solar/Wind Harmer
24.712
970581AG2-369 GEN
Solar/Wind Harmer
21.252
957871AF2-081 GEN
Solar/Wind Harmer
17.564
319010AE1-072 C
Solar/Wind Harmer
7.086
3146406KITTY HAWK
Solar/Wind Harmer
0.029
316315AB2-025 C
Solar/Wind Harmer
0.937
313526AB2-022
Solar/Wind Harmer
0.936
316305AF2-043 C
Solar/Wind Harmer
1.045
315814AE2-033 C
Solar/Wind Harmer
32.246
316321Z2-027
Solar/Wind Harmer
0.932
3146396TANGLEW
Solar/Wind Harmer
0.636
3145176PASQUOTANK
Solar/Wind Harmer
-0.021
3146486SUNBURY
Solar/Wind Harmer
-0.034
3146486SUNBURY
Solar/Wind Harmer
-0.034
315835AF2-110_GEN
Solar/Wind Harmer
4.24
315611Z1-036_GEN2
Solar/Wind Harmer
8.362
3130156CHOWAN
Solar/Wind Harmer
-0.033
3130156CHOWAN
Solar/Wind Harmer
-0.033
315816AE2-034 GEN
Solar/Wind Harmer
2.664
3130546PLYMOUTH
Solar/Wind Harmer
-0.032
316311AC2-079 GEN
Solar/Wind Harmer
16.358
315833AF1-017_GEN
Solar/Wind Harmer
6.154
316349AD2-085 GEN
Solar/Wind Harmer
2.882
315732AD1-074 GEN1
Solar/Wind Harmer
6.552
315733AD1-074 GEN2
Solar/Wind Harmer
6.552
315735AD1-075 GEN1
Solar/Wind Harmer
3.277
3146206CASHIE
Solar/Wind Harmer
-0.032
970601AG2-382 GEN
Solar/Wind Harmer
14.056
965291AG1-394 GEN
Solar/Wind Harmer
2.84
316318V4-068
Solar/Wind Harmer
0.794
3145893MURPHYS
Solar/Wind Harmer
-0.085
3145893MURPHYS
Solar/Wind Harmer
-0.032
3145513AHOSKIE
Solar/Wind Harmer
0.276
961941AG1-037 GEN
Solar/Wind Harmer
0.238
3145513AHOSKIE
Solar/Wind Harmer
-0.032
3145683EARLEYS
Solar/Wind Harmer
-0.063
3145683EARLEYS
Solar/Wind Harmer
-0.031
3145683EARLEYS
Solar/Wind Harmer
-0.031
946281AF1-292 GEN
Solar/Wind Harmer
0.704
3146043SEABORD
Solar/Wind Harmer
-0.031
315607AA1-063A GEN
Solar/Wind Harmer
3.165
971445AH1-216 GEN
Solar/Wind Harmer
19.378
316087AB2-174 GEN
Solar/Wind Harmer
4.457
315652AC1-086 GEN
Solar/Wind Harmer
35.144
3137643SOCKMAN
Solar/Wind Harmer
-0.123
3145796HORNRTN
Solar/Wind Harmer
-0.098
3145796HORNRTN
Solar/Wind Harmer
-0.012
3146033SCOT NK
Solar/Wind Harmer
-0.122
970831AG2-522 GEN
Solar/Wind Harmer
14.908
3143316POE
Solar/Wind Harmer
-0.117
316005AA1-067
Solar/Wind Harmer
0.6
3145746EVERETS
Solar/Wind Harmer
-0.117
3145746EVERETS
Solar/Wind Harmer
-0.03
3145746EVERETS
Solar/Wind Harmer
-0.03
3145746EVERETS
Solar/Wind Harmer
-0.03
970181AG2-120 GEN
Solar/Wind Harmer
3.894
972265AH1-717 GEN
Adder
20.283
3151201GRAVEL4
Adder
19.014
3151191GRAVEL3
Adder
18.773
3151211GRAVEL5
Adder
18.773
957861AF2-080 GEN
Solar/Wind Harmer
12.824
316420AA1-050 GEN
Solar/Wind Harmer
3.328
316319Z2-044 C
Solar/Wind Harmer
1.602
3145573BETHELC
Solar/Wind Harmer
-0.029
3145573BETHELC
Solar/Wind Harmer
-0.029
316239AB2-077_GEN
Solar/Wind Harmer
0.825
316238AB2-078_GEN
Solar/Wind Harmer
0.825
316118AC1-105 GEN
Solar/Wind Harmer
1.849
3147173SINAI
Solar/Wind Harmer
-0.027
3147243WELCO
Solar/Wind Harmer
-0.017
316369SG1_INVT
Solar/Wind Harmer
4.602
957831AF2-077 GEN
Solar/Wind Harmer
0.771
3138283WHITEMARSH
Solar/Wind Harmer
0.04
971443AH1-215 GEN
Solar/Wind Harmer
4.9
3144303KENBRDG
Solar/Wind Harmer
-0.02
3142433PROV 92
Adder
0.328
3142433PROV 92
Adder
0.328
316164AC1-076 GEN
Solar/Wind Helper
1.169
315724AD1-057 GEN
Solar/Wind Harmer
1.704
3144216WINCHST
Adder
0.991
3150921YORKTN3
Adder
6.605
316327AA2-057 GEN
Solar/Wind Harmer
2.969
3151221GRAVEL6
Adder
18.992
3151171GRAVELC
Adder
3.654
3146233WITAKRS
Solar/Wind Harmer
0.607
3146233WITAKRS
Solar/Wind Harmer
-0.02
3146073TAR RVR
Solar/Wind Harmer
-0.029
3146083TARBORO
Solar/Wind Harmer
-0.029
3138543CONSLDL
Solar/Wind Harmer
-0.019
961601AG1-000A GEN
Solar/Wind Harmer
11.396
3145543BTLEBRO
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.029
315813AE1-149 C
Solar/Wind Harmer
17.781
961611AG1-000B GEN
Solar/Wind Harmer
5.887
316131AB2-060 GEN
Solar/Wind Harmer
2.926
316248AF1-058 C
Solar/Wind Harmer
0.807
960061AF2-297 GEN
Solar/Wind Harmer
13.386
316382AG1-145 C
Solar/Wind Harmer
0.796
964241AG1-285 GEN
Solar/Wind Harmer
20.631
315785AD2-033 C
Solar/Wind Harmer
5.719
316283AC2-100 C
Solar/Wind Harmer
2.345
315778AD1-151 GEN
Solar/Wind Harmer
21.559
970257AG2-171 GEN
Solar/Wind Harmer
9.298
959311AF2-222 GEN
Solar/Wind Harmer
25.545
315839AE2-212 C
Solar/Wind Harmer
0.733
971683AH1-343 GEN
Solar/Wind Harmer
10.422
3144293JTRSVLE
Adder
0.641
3141843SHACKLE
Adder
0.947
3142433PROV 92
Adder
0.328
3142433PROV 92
Adder
0.328
3150351NORNECKC2
Adder
1.453
316044AC1-158 PL1
Solar/Wind Helper
1.613
316450AC1-158 RIC
Solar/Wind Helper
0.43
3147666LOUISA
Solar/Wind Helper
0.578
316170AC1-121 GEN2
Solar/Wind Helper
0.347
970909AG2-566 GEN
Solar/Wind Harmer
2.035
3146083TARBORO
Solar/Wind Harmer
-0.029
3145493TOT1
Solar/Wind Harmer
0.861
3145543BTLEBRO
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.023
316359AB2-059 GEN
Solar/Wind Harmer
3.858
316049AB1-081 GEN
Solar/Wind Harmer
3.087
3142053HEARTS
Solar/Wind Harmer
0.336
971317AH1-138 GEN
Solar/Wind Harmer
3.516
961611AG1-000B GEN
Solar/Wind Harmer
13.798
316237AB2-079_GEN
Solar/Wind Harmer
0.825
970401AG2-262 GEN
Solar/Wind Harmer
1.762
971647AH1-324 GEN
Solar/Wind Harmer
13.425
316159AE1-175 C
Solar/Wind Harmer
0.709
316003AC1-222 GEN
Solar/Wind Harmer
2.478
971069AG2-661 GEN
Solar/Wind Harmer
3.938
3144293JTRSVLE
Adder
0.641
3141843SHACKLE
Adder
0.947
3142433PROV 92
Adder
0.328
3142433PROV 92
Adder
0.328
944631AF1-128 GEN
Adder
73.982
3150351NORNECKC2
Adder
1.429
316045AC1-158 PL2
Solar/Wind Helper
5.164
3147666LOUISA
Solar/Wind Helper
1.005
316192AB2-158 GEN
Solar/Wind Helper
1.664
316254AC1-120 GEN1
Solar/Wind Helper
1.04
970533AG2-339 GEN
50/50
34.611
970531AG2-338 GEN
50/50
13.844
315242AE2-183_GT2
50/50
6.204
315241AE2-183_GT1
50/50
6.166
972185AH1-677 GEN
50/50
22.366
3151041BRUNSWICKG3
50/50
4.866
972187AH1-678 GEN
50/50
11.167
3150991CHESPKB
50/50
3.457
3150991CHESPKB
50/50
3.374
970933AG2-581 GEN
Solar/Wind Harmer
37.255
316185AD1-033 GEN
Solar/Wind Harmer
3.726
3145506HICKORY
Solar/Wind Harmer
-0.14
3145506HICKORY
Solar/Wind Harmer
-0.084
3145506HICKORY
Solar/Wind Harmer
-0.021
316339AD2-160 GEN
Solar/Wind Harmer
2.371
3142956BIRDNECK
Solar/Wind Harmer
1.886
316316AC1-027 C
Solar/Wind Harmer
1.078
316018AA1-139 ULT2
Solar/Wind Harmer
3.009
316017AA1-139 ULT1
Solar/Wind Harmer
2.842
970099AG2-077 GEN
Solar/Wind Harmer
43.88
3137176SLIGO L2192
Solar/Wind Harmer
-0.139
3146456SLIGO L269
Solar/Wind Harmer
4.14
3130086AYDLETT
Solar/Wind Harmer
-0.139
316036AC1-147 C
Solar/Wind Harmer
0.943
3144356SAPONY
Solar/Wind Harmer
1.212
3146386ELIZ CT
Solar/Wind Harmer
-0.035
316431W1029_GEN1
Solar/Wind Harmer
6.217
316433W1029_GEN2
Solar/Wind Harmer
6.217
3146516WINFALL
Solar/Wind Harmer
-0.034
3146516WINFALL
Solar/Wind Harmer
-0.034
3146516WINFALL
Solar/Wind Harmer
-0.034
3146626S HERTFORD
Solar/Wind Harmer
-0.034
3146626S HERTFORD
Solar/Wind Harmer
-0.034
3146376EDENTON
Solar/Wind Harmer
0.994
3146376EDENTON
Solar/Wind Harmer
0.994
315742AE1-103 GEN
Solar/Wind Harmer
3.459
316065AD1-022 GEN
Solar/Wind Harmer
16.113
3145893MURPHYS
Solar/Wind Harmer
0.889
3145893MURPHYS
Solar/Wind Harmer
-0.057
3146173TUNIS
Solar/Wind Harmer
-0.032
3146173TUNIS
Solar/Wind Harmer
-0.032
316236AE1-162_GEN
Solar/Wind Harmer
0.95
3142666NORTHAMPTON
Solar/Wind Harmer
-0.031
3142666NORTHAMPTON
Solar/Wind Harmer
-0.031
3142666NORTHAMPTON
Solar/Wind Harmer
-0.031
3142666NORTHAMPTON
Solar/Wind Harmer
-0.019
316181AB2-040 GEN
Solar/Wind Harmer
4.348
316426AA2-053 GEN
Solar/Wind Harmer
3.132
3145593CAROLNA
Solar/Wind Harmer
-0.031
3145593CAROLNA
Solar/Wind Harmer
-0.031
966811AG1-552 GEN
Solar/Wind Harmer
3.475
3145593CAROLNA
Solar/Wind Harmer
0.257
3145796HORNRTN
Solar/Wind Harmer
-0.092
3145783HORNRTN
Solar/Wind Harmer
3.649
3145783HORNRTN
Solar/Wind Harmer
2.919
3145783HORNRTN
Solar/Wind Harmer
0.912
3145783HORNRTN
Solar/Wind Harmer
0.365
970657AG2-426 GEN
Solar/Wind Harmer
9.452
970657AG2-426 GEN
Solar/Wind Harmer
1.977
3145933PARMELE
Solar/Wind Harmer
-0.06
3145933PARMELE
Solar/Wind Harmer
-0.03
316274AC1-208 GEN
Solar/Wind Harmer
3.24
3145493TOT1
Solar/Wind Harmer
0.449
3145453TOT5
Solar/Wind Harmer
0.269
3145603CNETO
Solar/Wind Harmer
0.18
939181AE1-148 GEN
Solar/Wind Harmer
16.17
961601AG1-000A GEN
Solar/Wind Harmer
11.253
316263AC1-034 GEN
Solar/Wind Harmer
13.413
313527AB2-043 GEN
Solar/Wind Harmer
4.434
962561AG1-105 GEN
Solar/Wind Harmer
15.207
964791AG1-342 GEN
Solar/Wind Harmer
5.765
3146843MT LREL
Solar/Wind Harmer
-0.027
3146843MT LREL
Solar/Wind Harmer
-0.027
971741AH1-377 GEN
Solar/Wind Harmer
30.134
316033AB2-134 GEN
Solar/Wind Harmer
8.307
315697AD1-025 GEN
Solar/Wind Harmer
5.21
316222AC1-221 GEN
Solar/Wind Harmer
2.532
970323AG2-213 GEN
Solar/Wind Harmer
12.397
971775AH1-396 GEN
Solar/Wind Harmer
1.765
316034AC1-036 C
Solar/Wind Harmer
0.46
3144293JTRSVLE
Adder
0.641
3144293JTRSVLE
Adder
0.54
944641AF1-129 GEN
Adder
84.798
3150341NORNECKC1
Adder
1.501
3150341NORNECKC1
Adder
1.489
316447AC1-158 HLD
Solar/Wind Helper
3.55
315651AD1-115 GEN
Solar/Wind Helper
0.754
970301AG2-198 GEN
Solar/Wind Harmer
10.716
LAGNLTFEXP_LAGN->PJM
CLTF
11.587
CBM South 2LTFEXP_CBM-S2->PJM
CBM
36.707
TVALTFEXP_TVA->PJM
CLTF
5.796
CPLELTFEXP_CPLE->PJM
CLTF
17.078
CBM West 2LTFEXP_CBM-W2->PJM
CBM
60.508
CBM West 1LTFEXP_CBM-W1->PJM
CBM
34.948
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.784
MECLTFEXP_MEC->PJM
CLTF
5.477
SIGELTFEXP_SIGE->PJM
CLTF
0.164
NYPJM->LTFIMP_NY
CLTF
2.958
LGEELTFEXP_LGEE->PJM
CLTF
1.969
WECLTFEXP_WEC->PJM
CLTF
1.007

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 56272_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56272_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.96 %
Rating:3118.0 MVA
Rating Type:C
MVA to Mitigate:4114.65
MW Contribution:13.69
Bus #Bus NameTypeMW Contribution
315244AE2-183_ST
50/50
9.95
963041AG1-153 GEN
50/50
9.127
3151541CLOVER2
50/50
5.691
315779AE2-040
50/50
3.626
3151611KERR 4
50/50
0.458
3151621KERR 5
50/50
0.458
3151631KERR 6
50/50
0.458
3151641KERR 7
50/50
0.458
3151281ROARAP4
50/50
0.259
3151281ROARAP4
50/50
0.243
941031AE2-094 GEN
Solar/Wind Harmer
76.337
944011AF1-069 GEN
Solar/Wind Harmer
23.919
970673AG2-436 GEN
Solar/Wind Harmer
83.349
970673AG2-436 GEN
Solar/Wind Harmer
42.202
971967AH1-528 GEN
Solar/Wind Harmer
72.452
970085AG2-068 GEN
Solar/Wind Harmer
22.787
970581AG2-369 GEN
Solar/Wind Harmer
19.597
316315AB2-025 C
Solar/Wind Harmer
0.787
315814AE2-033 C
Solar/Wind Harmer
27.034
946281AF1-292 GEN
Solar/Wind Harmer
0.568
316087AB2-174 GEN
Solar/Wind Harmer
3.556
970831AG2-522 GEN
Solar/Wind Harmer
12.26
315652AC1-086 GEN
Solar/Wind Harmer
27.499
3137643SOCKMAN
Solar/Wind Harmer
-0.097
3145796HORNRTN
Solar/Wind Harmer
-0.077
3145796HORNRTN
Solar/Wind Harmer
-0.01
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
316118AC1-105 GEN
Solar/Wind Harmer
1.62
316239AB2-077_GEN
Solar/Wind Harmer
0.708
316238AB2-078_GEN
Solar/Wind Harmer
0.708
315607AA1-063A GEN
Solar/Wind Harmer
2.372
3146043SEABORD
Solar/Wind Harmer
-0.023
316319Z2-044 C
Solar/Wind Harmer
1.269
3146033SCOT NK
Solar/Wind Harmer
-0.091
3143316POE
Solar/Wind Harmer
-0.09
3145573BETHELC
Solar/Wind Harmer
-0.023
3145573BETHELC
Solar/Wind Harmer
-0.023
965291AG1-394 GEN
Solar/Wind Harmer
2.008
316318V4-068
Solar/Wind Harmer
0.563
3145893MURPHYS
Solar/Wind Harmer
-0.061
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145513AHOSKIE
Solar/Wind Harmer
0.197
961941AG1-037 GEN
Solar/Wind Harmer
0.17
3145513AHOSKIE
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.045
3145683EARLEYS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
316420AA1-050 GEN
Solar/Wind Harmer
2.577
957861AF2-080 GEN
Solar/Wind Harmer
9.823
316005AA1-067
Solar/Wind Harmer
0.45
3145746EVERETS
Solar/Wind Harmer
-0.088
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
970181AG2-120 GEN
Solar/Wind Harmer
2.918
3146206CASHIE
Solar/Wind Harmer
-0.022
970601AG2-382 GEN
Solar/Wind Harmer
9.603
315732AD1-074 GEN1
Solar/Wind Harmer
4.385
315733AD1-074 GEN2
Solar/Wind Harmer
4.385
315735AD1-075 GEN1
Solar/Wind Harmer
2.193
3130546PLYMOUTH
Solar/Wind Harmer
-0.022
315816AE2-034 GEN
Solar/Wind Harmer
1.73
971443AH1-215 GEN
Solar/Wind Harmer
4.181
3144303KENBRDG
Solar/Wind Harmer
-0.017
3130156CHOWAN
Solar/Wind Harmer
-0.021
3130156CHOWAN
Solar/Wind Harmer
-0.021
315611Z1-036_GEN2
Solar/Wind Harmer
5.153
315835AF2-110_GEN
Solar/Wind Harmer
2.575
3146486SUNBURY
Solar/Wind Harmer
-0.021
3146486SUNBURY
Solar/Wind Harmer
-0.021
316305AF2-043 C
Solar/Wind Harmer
0.619
3145176PASQUOTANK
Solar/Wind Harmer
-0.013
316321Z2-027
Solar/Wind Harmer
0.551
3146396TANGLEW
Solar/Wind Harmer
0.375
313526AB2-022
Solar/Wind Harmer
0.548
316311AC2-079 GEN
Solar/Wind Harmer
10.237
315833AF1-017_GEN
Solar/Wind Harmer
3.854
316349AD2-085 GEN
Solar/Wind Harmer
1.805
970683AG2-441 GEN
Solar/Wind Harmer
15.731
970681AG2-440 GEN
Solar/Wind Harmer
12.585
3146406KITTY HAWK
Solar/Wind Harmer
0.017
319010AE1-072 C
Solar/Wind Harmer
4.06
970865AG2-541 GEN
Solar/Wind Harmer
8.137
957871AF2-081 GEN
Solar/Wind Harmer
10.005
3151081ELIZAR1
Adder
15.891
3151091ELIZAR2
Adder
15.615
3152611GOSPORTB
Adder
2.203
3152621GOSPORTC
Adder
1.869
3152601GOSPORTA
Adder
1.724
946301AF1-294 GEN
Solar/Wind Harmer
4.916
961791AG1-021 GEN
Solar/Wind Harmer
2.398
270455AD2-022 GEN
Solar/Wind Harmer
3.325
270457AD2-023 GEN
Solar/Wind Harmer
1.686
315657AE1-056 GEN
Solar/Wind Harmer
6.945
316123AC1-075 GEN
Solar/Wind Harmer
1.908
970165AG2-112 GEN
Solar/Wind Harmer
1.68
970163AG2-111 GEN
Solar/Wind Harmer
1.602
972265AH1-717 GEN
Adder
10.663
3151201GRAVEL4
Adder
9.996
3151191GRAVEL3
Adder
9.869
3151211GRAVEL5
Adder
9.869
971445AH1-216 GEN
Solar/Wind Harmer
2.771
3151031BRUNSWICKG2
50/50
4.507
970413AG2-270 GEN
50/50
24.952
3151591KERR 2
50/50
0.458
3151391GASTONA
50/50
0.588
3151411GASTONB
50/50
0.588
3151261ROARAP2
50/50
0.26
970917AG2-570 GEN
Solar/Wind Harmer
91.647
316478AD1-087 GEN
Solar/Wind Harmer
2.597
316486AD2-202 GEN
Solar/Wind Harmer
0.761
316365GEN2_N
Solar/Wind Harmer
1.761
966621AG1-532 GEN
Solar/Wind Harmer
0.515
3147043LAWRENC
Solar/Wind Harmer
-0.015
313506AB2-031 GEN
Solar/Wind Harmer
1.989
3145796HORNRTN
Solar/Wind Harmer
-0.096
3145796HORNRTN
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
316248AF1-058 C
Solar/Wind Harmer
0.711
960061AF2-297 GEN
Solar/Wind Harmer
11.79
315724AD1-057 GEN
Solar/Wind Harmer
1.351
316131AB2-060 GEN
Solar/Wind Harmer
2.509
316210AC1-098 GEN
Solar/Wind Harmer
3.629
316327AA2-057 GEN
Solar/Wind Harmer
2.332
3146263WOODLND
Solar/Wind Harmer
-0.023
3146233WITAKRS
Solar/Wind Harmer
0.481
3146233WITAKRS
Solar/Wind Harmer
-0.015
3138543CONSLDL
Solar/Wind Harmer
-0.015
961601AG1-000A GEN
Solar/Wind Harmer
9.103
3145543BTLEBRO
Solar/Wind Harmer
-0.023
3145543BTLEBRO
Solar/Wind Harmer
-0.023
316317KELFORD C
Solar/Wind Harmer
1.074
3145823KELFORD
Solar/Wind Harmer
-0.023
3146073TAR RVR
Solar/Wind Harmer
-0.023
3146083TARBORO
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
0.158
3145893MURPHYS
Solar/Wind Harmer
-0.023
957521AF2-046 GEN
Solar/Wind Harmer
17.808
961681AG1-008 GEN
Solar/Wind Harmer
17.808
964241AG1-285 GEN
Solar/Wind Harmer
17.664
3146173TUNIS
Solar/Wind Harmer
-0.023
316463AE2-346 GEN
Solar/Wind Harmer
0.366
316140AB2-099
Solar/Wind Harmer
0.152
962331AG1-082 GEN
Solar/Wind Harmer
2.826
3156081AA2-088 GEN
Solar/Wind Harmer
7.311
3156021HOLLOMANSOL
Solar/Wind Harmer
3.009
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
3145933PARMELE
Solar/Wind Harmer
-0.022
966801AG1-551 GEN
Solar/Wind Harmer
2.766
3146206CASHIE
Solar/Wind Harmer
-0.022
3145963POPLR C
Solar/Wind Harmer
-0.022
316283AC2-100 C
Solar/Wind Harmer
2.053
315737AD1-076 GEN
Solar/Wind Harmer
4.121
971157AH1-035 GEN
Solar/Wind Harmer
2.704
315785AD2-033 C
Solar/Wind Harmer
4.883
315614AA2-178 GEN
Solar/Wind Harmer
2.306
3145273HOLLAND
Solar/Wind Harmer
-0.016
971683AH1-343 GEN
Solar/Wind Harmer
9.136
970257AG2-171 GEN
Solar/Wind Harmer
7.93
3146376EDENTON
Solar/Wind Harmer
-0.021
970909AG2-566 GEN
Solar/Wind Harmer
1.981
959311AF2-222 GEN
Solar/Wind Harmer
21.769
3146626S HERTFORD
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.021
316435W1029_GEN3
Solar/Wind Harmer
3.733
316320Y1-086
Solar/Wind Harmer
1.19
3146456SLIGO L269
Solar/Wind Harmer
-0.02
971153AH1-033 GEN
Solar/Wind Harmer
2.444
970661AG2-428 GEN
Solar/Wind Harmer
3.756
944581AF1-123 GEN
Solar/Wind Harmer
90.622
944601AF1-125 GEN
Solar/Wind Harmer
89.208
316083AB2-161 GEN
Solar/Wind Harmer
3.214
970659AG2-427 GEN
Solar/Wind Harmer
1.86
315813AE1-149 C
Solar/Wind Harmer
12.185
3151101ELIZAR3
Adder
16.095
3144873MCLAUGH
Solar/Wind Harmer
0
963181AG1-167 GEN
Solar/Wind Harmer
1.798
3144293JTRSVLE
Adder
0.543
3144536CHRHLND
Solar/Wind Harmer
-0.003
3147133PAMPLIN
Solar/Wind Harmer
-0.058
971193AH1-056 GEN
Solar/Wind Harmer
11.575
3145336SMITFLD
Solar/Wind Harmer
-0.007
315839AE2-212 C
Solar/Wind Harmer
0.509
3151221GRAVEL6
Adder
9.984
3151171GRAVELC
Adder
1.921
3144216WINCHST
Adder
0.443
315243AE2-183_GT3
50/50
5.755
3151051BRUNSWICKS1
50/50
9.355
3151021BRUNSWICKG1
50/50
4.507
971451AH1-221 GEN
50/50
13.69
3151531CLOVER1
50/50
5.718
3151601KERR 3
50/50
0.458
3151581KERR 1
50/50
0.163
3147043LAWRENC
50/50
2.116
3151391GASTONA
50/50
0.588
3151411GASTONB
50/50
0.588
3151261ROARAP2
50/50
0.266
970919AG2-571 GEN
Solar/Wind Harmer
11.601
970087AG2-069 GEN
Solar/Wind Harmer
34.181
939411AE1-173 GEN
Solar/Wind Harmer
170.129
957481AF2-042 GEN
Solar/Wind Harmer
99.882
315693AD1-088 GEN
Solar/Wind Harmer
14.731
962491AG1-098 GEN
Solar/Wind Harmer
19.405
315687AD1-152 GEN
Solar/Wind Harmer
3.35
316023GEN1_S
Solar/Wind Harmer
1.761
960081AF2-299 GEN
Solar/Wind Harmer
2.853
971795AH1-408 GEN
Solar/Wind Harmer
18.718
971065AG2-659 GEN
Solar/Wind Harmer
12.309
316129AC1-054 GEN
Solar/Wind Harmer
2.154
316011AB1-132 GEN
Solar/Wind Harmer
5.114
962571AG1-106 GEN
Solar/Wind Harmer
3.514
3145796HORNRTN
Solar/Wind Harmer
-0.08
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145783HORNRTN
Solar/Wind Harmer
-0.024
316190AA2-174 GEN
Solar/Wind Harmer
0.292
970401AG2-262 GEN
Solar/Wind Harmer
1.534
316237AB2-079_GEN
Solar/Wind Harmer
0.708
315722AD1-056 GEN
Solar/Wind Harmer
2.456
316212AC1-099_GEN
Solar/Wind Harmer
2.016
3146263WOODLND
Solar/Wind Harmer
-0.023
3146233WITAKRS
Solar/Wind Harmer
-0.091
316359AB2-059 GEN
Solar/Wind Harmer
3.083
316049AB1-081 GEN
Solar/Wind Harmer
2.467
3142053HEARTS
Solar/Wind Harmer
0.269
3145543BTLEBRO
Solar/Wind Harmer
-0.023
3145543BTLEBRO
Solar/Wind Harmer
-0.018
3145823KELFORD
Solar/Wind Harmer
-0.023
961671AG1-007 GEN
Solar/Wind Harmer
0.286
3146083TARBORO
Solar/Wind Harmer
-0.023
3145493TOT1
Solar/Wind Harmer
0.672
3145893MURPHYS
Solar/Wind Harmer
-0.09
3145893MURPHYS
Solar/Wind Harmer
0.671
3146173TUNIS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
316494AC1-189 GEN
Solar/Wind Harmer
2.416
316003AC1-222 GEN
Solar/Wind Harmer
2.177
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
3146293MARTNCO
Solar/Wind Harmer
0.137
316174AB2-169 GEN
Solar/Wind Harmer
3.387
3146206CASHIE
Solar/Wind Harmer
-0.022
971547AH1-271 GEN
Solar/Wind Harmer
5.488
3145963POPLR C
Solar/Wind Harmer
-0.022
3145663CRESWEL
Solar/Wind Harmer
-0.06
971163AH1-040 GEN
Solar/Wind Harmer
20.04
3130156CHOWAN
Solar/Wind Harmer
-0.021
315800Z1-036_GEN1
Solar/Wind Harmer
5.153
3146516WINFALL
Solar/Wind Harmer
-0.066
3146516WINFALL
Solar/Wind Harmer
-0.021
316093AE2-104_GEN
Solar/Wind Harmer
5.989
316246AF1-032 C
Solar/Wind Harmer
0.415
970685AG2-442 GEN
Solar/Wind Harmer
17.619
3146456SLIGO L269
Solar/Wind Harmer
-0.02
316388AE2-253 GEN
Solar/Wind Harmer
1.348
970661AG2-428 GEN
Solar/Wind Harmer
21.192
944591AF1-124 GEN
Solar/Wind Harmer
90.948
316381AD1-082 GEN
Solar/Wind Harmer
1.816
970659AG2-427 GEN
Solar/Wind Harmer
10.495
316375AC2-012 GEN
Solar/Wind Harmer
6.72
3150981CHESPKA
Adder
2.158
963171AG1-166 GEN
Solar/Wind Harmer
2.398
971563AH1-280 GEN
Solar/Wind Harmer
2.398
3144293JTRSVLE
Adder
0.543
316072AD1-144
Solar/Wind Harmer
0.387
3145336SMITFLD
Solar/Wind Harmer
-0.067
3151171GRAVELC
Adder
1.461
3143226MDLTHAN
Solar/Wind Helper
0.294
316045AC1-158 PL2
Solar/Wind Helper
4.138
3150921YORKTN3
Adder
2.878
316044AC1-158 PL1
Solar/Wind Helper
1.293
316450AC1-158 RIC
Solar/Wind Helper
0.345
970533AG2-339 GEN
50/50
32.21
970531AG2-338 GEN
50/50
12.884
315242AE2-183_GT2
50/50
5.755
315241AE2-183_GT1
50/50
5.72
972185AH1-677 GEN
50/50
20.748
3151041BRUNSWICKG3
50/50
4.507
972187AH1-678 GEN
50/50
10.344
3151361ROSEMG1
50/50
0.776
3151371ROSEMS1
50/50
0.481
3151381ROSEMG2
50/50
0.363
970535AG2-341 GEN
50/50
3.826
3152661PLYWOOD A
50/50
0.474
970933AG2-581 GEN
Solar/Wind Harmer
34.364
970099AG2-077 GEN
Solar/Wind Harmer
39.953
3144356SAPONY
Solar/Wind Harmer
1.018
316181AB2-040 GEN
Solar/Wind Harmer
3.451
939181AE1-148 GEN
Solar/Wind Harmer
13.835
3145796HORNRTN
Solar/Wind Harmer
-0.072
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3145593CAROLNA
Solar/Wind Harmer
-0.024
3145593CAROLNA
Solar/Wind Harmer
-0.024
966811AG1-552 GEN
Solar/Wind Harmer
2.705
3145593CAROLNA
Solar/Wind Harmer
0.2
3145783HORNRTN
Solar/Wind Harmer
2.839
3145783HORNRTN
Solar/Wind Harmer
2.272
3145783HORNRTN
Solar/Wind Harmer
0.71
3145783HORNRTN
Solar/Wind Harmer
0.284
316426AA2-053 GEN
Solar/Wind Harmer
2.403
3146843MT LREL
Solar/Wind Harmer
-0.023
3146843MT LREL
Solar/Wind Harmer
-0.023
964791AG1-342 GEN
Solar/Wind Harmer
5.022
962561AG1-105 GEN
Solar/Wind Harmer
13.216
313527AB2-043 GEN
Solar/Wind Harmer
3.804
316274AC1-208 GEN
Solar/Wind Harmer
2.516
961601AG1-000A GEN
Solar/Wind Harmer
8.989
316263AC1-034 GEN
Solar/Wind Harmer
10.719
971741AH1-377 GEN
Solar/Wind Harmer
26.554
3145493TOT1
Solar/Wind Harmer
0.35
3145453TOT5
Solar/Wind Harmer
0.21
3145603CNETO
Solar/Wind Harmer
0.14
3145893MURPHYS
Solar/Wind Harmer
0.631
3145893MURPHYS
Solar/Wind Harmer
-0.041
3146173TUNIS
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.023
3145933PARMELE
Solar/Wind Harmer
-0.044
3145933PARMELE
Solar/Wind Harmer
-0.022
316222AC1-221 GEN
Solar/Wind Harmer
2.217
316065AD1-022 GEN
Solar/Wind Harmer
10.926
315742AE1-103 GEN
Solar/Wind Harmer
2.245
970323AG2-213 GEN
Solar/Wind Harmer
10.573
971775AH1-396 GEN
Solar/Wind Harmer
1.506
316034AC1-036 C
Solar/Wind Harmer
0.392
3146376EDENTON
Solar/Wind Harmer
0.624
3146376EDENTON
Solar/Wind Harmer
0.624
970301AG2-198 GEN
Solar/Wind Harmer
10.435
3146626S HERTFORD
Solar/Wind Harmer
-0.021
3146626S HERTFORD
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.021
316431W1029_GEN1
Solar/Wind Harmer
3.733
316433W1029_GEN2
Solar/Wind Harmer
3.733
3146386ELIZ CT
Solar/Wind Harmer
-0.02
3130086AYDLETT
Solar/Wind Harmer
-0.08
3146456SLIGO L269
Solar/Wind Harmer
2.368
3137176SLIGO L2192
Solar/Wind Harmer
-0.079
316018AA1-139 ULT2
Solar/Wind Harmer
1.714
316017AA1-139 ULT1
Solar/Wind Harmer
1.619
316339AD2-160 GEN
Solar/Wind Harmer
1.348
3145506HICKORY
Solar/Wind Harmer
-0.079
3145506HICKORY
Solar/Wind Harmer
-0.048
3145506HICKORY
Solar/Wind Harmer
-0.012
970657AG2-426 GEN
Solar/Wind Harmer
6.206
970657AG2-426 GEN
Solar/Wind Harmer
1.298
316185AD1-033 GEN
Solar/Wind Harmer
2.091
3142956BIRDNECK
Solar/Wind Harmer
1.055
316316AC1-027 C
Solar/Wind Harmer
0.603
316036AC1-147 C
Solar/Wind Harmer
0.524
3150991CHESPKB
Adder
1.81
3150991CHESPKB
Adder
1.767
958211AF2-115 GEN
Solar/Wind Harmer
2.997
963191AG1-168 GEN
Solar/Wind Harmer
1.798
3144293JTRSVLE
Adder
0.543
3144293JTRSVLE
Adder
0.458
3147133PAMPLIN
Solar/Wind Harmer
-0.018
3147133PAMPLIN
Solar/Wind Harmer
-0.015
316236AE1-162_GEN
Solar/Wind Harmer
0.511
316447AC1-158 HLD
Solar/Wind Helper
2.845
LAGNLTFEXP_LAGN->PJM
CLTF
9.968
CBM South 2LTFEXP_CBM-S2->PJM
CBM
31.656
TVALTFEXP_TVA->PJM
CLTF
4.976
CPLELTFEXP_CPLE->PJM
CLTF
14.701
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.1
CBM West 1LTFEXP_CBM-W1->PJM
CBM
30.472
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.988
MECLTFEXP_MEC->PJM
CLTF
4.732
SIGELTFEXP_SIGE->PJM
CLTF
0.141
NYPJM->LTFIMP_NY
CLTF
2.22
LGEELTFEXP_LGEE->PJM
CLTF
1.693
WECLTFEXP_WEC->PJM
CLTF
0.873

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 567_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.02 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:4187.08
MW Contribution:14.07
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
5.909
3151051BRUNSWICKS1
50/50
9.612
3151021BRUNSWICKG1
50/50
4.631
971451AH1-221 GEN
50/50
14.067
3152331SURRY 2
50/50
12.237
3150981CHESPKA
50/50
3.828
940641AE2-051 GEN
Solar/Wind Harmer
30.053
939411AE1-173 GEN
Solar/Wind Harmer
151.675
970919AG2-571 GEN
Solar/Wind Harmer
11.95
970087AG2-069 GEN
Solar/Wind Harmer
26.75
316294AC1-161 GEN
Solar/Wind Harmer
5.441
944591AF1-124 GEN
Solar/Wind Harmer
67.777
957481AF2-042 GEN
Solar/Wind Harmer
78.492
316388AE2-253 GEN
Solar/Wind Harmer
0.915
3146456SLIGO L269
Solar/Wind Harmer
0.291
316375AC2-012 GEN
Solar/Wind Harmer
0.007
316246AF1-032 C
Solar/Wind Harmer
0.129
3146516WINFALL
Solar/Wind Harmer
0.918
3146516WINFALL
Solar/Wind Harmer
0.283
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
316093AE2-104_GEN
Solar/Wind Harmer
4.671
3130156CHOWAN
Solar/Wind Harmer
0.277
315693AD1-088 GEN
Solar/Wind Harmer
13.054
3145663CRESWEL
Solar/Wind Harmer
0.761
971163AH1-040 GEN
Solar/Wind Harmer
21.745
316072AD1-144
Solar/Wind Harmer
0.098
962491AG1-098 GEN
Solar/Wind Harmer
15.287
3146206CASHIE
Solar/Wind Harmer
0.264
971547AH1-271 GEN
Solar/Wind Harmer
5.647
316023GEN1_S
Solar/Wind Harmer
0.591
3145893MURPHYS
Solar/Wind Harmer
1.045
3145893MURPHYS
Solar/Wind Harmer
1.162
3146173TUNIS
Solar/Wind Harmer
0.26
3145683EARLEYS
Solar/Wind Harmer
0.259
315687AD1-152 GEN
Solar/Wind Harmer
0.008
3146263WOODLND
Solar/Wind Harmer
0.257
3145963POPLR C
Solar/Wind Harmer
0.257
960081AF2-299 GEN
Solar/Wind Harmer
2.46
316011AB1-132 GEN
Solar/Wind Harmer
4.645
962571AG1-106 GEN
Solar/Wind Harmer
3.635
316174AB2-169 GEN
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.255
316190AA2-174 GEN
Solar/Wind Harmer
0
3145796HORNRTN
Solar/Wind Harmer
0.833
3145796HORNRTN
Solar/Wind Harmer
0.252
3145783HORNRTN
Solar/Wind Harmer
0.252
971795AH1-408 GEN
Solar/Wind Harmer
16.631
3146293MARTNCO
Solar/Wind Harmer
0.23
3145336SMITFLD
Solar/Wind Harmer
0.992
316212AC1-099_GEN
Solar/Wind Harmer
1.284
3147043LAWRENC
Adder
2.229
316129AC1-054 GEN
Solar/Wind Harmer
0.919
3145746EVERETS
Solar/Wind Harmer
0.244
3145746EVERETS
Solar/Wind Harmer
0.244
971065AG2-659 GEN
Solar/Wind Harmer
10.397
315722AD1-056 GEN
Solar/Wind Harmer
1.539
316494AC1-189 GEN
Solar/Wind Harmer
0.815
961671AG1-007 GEN
Solar/Wind Harmer
0.036
3146083TARBORO
Solar/Wind Harmer
0.239
3145493TOT1
Solar/Wind Harmer
1.061
3146233WITAKRS
Solar/Wind Harmer
0.949
970661AG2-428 GEN
Solar/Wind Harmer
23.724
3145543BTLEBRO
Solar/Wind Harmer
0.235
3145543BTLEBRO
Solar/Wind Harmer
0.188
316359AB2-059 GEN
Solar/Wind Harmer
0.846
316049AB1-081 GEN
Solar/Wind Harmer
1.347
3142053HEARTS
Solar/Wind Harmer
0.415
316381AD1-082 GEN
Solar/Wind Harmer
0.24
970659AG2-427 GEN
Solar/Wind Harmer
10.983
316237AB2-079_GEN
Solar/Wind Harmer
0.002
3151171GRAVELC
Adder
2.368
3138126ROCKLANDING
Solar/Wind Harmer
0.102
970401AG2-262 GEN
Solar/Wind Harmer
1.303
316003AC1-222 GEN
Solar/Wind Harmer
0.006
961611AG1-000B GEN
Solar/Wind Harmer
10.827
971317AH1-138 GEN
Solar/Wind Harmer
1.51
971647AH1-324 GEN
Solar/Wind Harmer
8.259
970685AG2-442 GEN
Solar/Wind Harmer
14.261
963171AG1-166 GEN
Solar/Wind Harmer
0.968
971563AH1-280 GEN
Solar/Wind Harmer
1.936
3144293JTRSVLE
Adder
0.578
316159AE1-175 C
Solar/Wind Harmer
0.148
971069AG2-661 GEN
Solar/Wind Harmer
3.035
316458AB2-190 GEN2
Solar/Wind Harmer
0.837
970129AG2-093 GEN
Solar/Wind Harmer
4.37
315671AE2-027_GEN
Solar/Wind Harmer
9.434
3146926FARMVIL
Solar/Wind Harmer
0.081
970223AG2-152 GEN
Solar/Wind Harmer
8.965
315244AE2-183_ST
50/50
10.216
963041AG1-153 GEN
50/50
9.378
3151081ELIZAR1
50/50
28.253
3151091ELIZAR2
50/50
27.762
941591AE2-156 GEN
50/50
25.74
3152611GOSPORTB
50/50
3.904
3152621GOSPORTC
50/50
3.313
3152601GOSPORTA
50/50
3.057
972263AH1-716 GEN
50/50
164.489
315779AE2-040
50/50
3.913
941031AE2-094 GEN
Solar/Wind Harmer
68.4
944011AF1-069 GEN
Solar/Wind Harmer
22.349
970673AG2-436 GEN
Solar/Wind Harmer
77.293
970673AG2-436 GEN
Solar/Wind Harmer
51.529
971967AH1-528 GEN
Solar/Wind Harmer
56.362
970085AG2-068 GEN
Solar/Wind Harmer
17.833
970581AG2-369 GEN
Solar/Wind Harmer
15.337
957871AF2-081 GEN
Solar/Wind Harmer
14.522
319010AE1-072 C
Solar/Wind Harmer
1.465
3146406KITTY HAWK
Solar/Wind Harmer
0.036
313526AB2-022
Solar/Wind Harmer
0.156
316321Z2-027
Solar/Wind Harmer
0.053
3146396TANGLEW
Solar/Wind Harmer
0.789
3145176PASQUOTANK
Solar/Wind Harmer
0.177
316305AF2-043 C
Solar/Wind Harmer
0.002
3146486SUNBURY
Solar/Wind Harmer
0.285
3146486SUNBURY
Solar/Wind Harmer
0.285
316315AB2-025 C
Solar/Wind Harmer
0.227
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
315814AE2-033 C
Solar/Wind Harmer
22.11
315835AF2-110_GEN
Solar/Wind Harmer
1.906
3130156CHOWAN
Solar/Wind Harmer
0.277
3130156CHOWAN
Solar/Wind Harmer
0.277
315816AE2-034 GEN
Solar/Wind Harmer
1.167
3130546PLYMOUTH
Solar/Wind Harmer
0.268
315732AD1-074 GEN1
Solar/Wind Harmer
1.535
315733AD1-074 GEN2
Solar/Wind Harmer
1.535
315735AD1-075 GEN1
Solar/Wind Harmer
0.768
3146206CASHIE
Solar/Wind Harmer
0.264
970601AG2-382 GEN
Solar/Wind Harmer
9.883
965291AG1-394 GEN
Solar/Wind Harmer
1.166
3145893MURPHYS
Solar/Wind Harmer
0.705
3145893MURPHYS
Solar/Wind Harmer
0.261
3145513AHOSKIE
Solar/Wind Harmer
0.543
3145513AHOSKIE
Solar/Wind Harmer
0.26
316311AC2-079 GEN
Solar/Wind Harmer
7.457
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.178
3145683EARLEYS
Solar/Wind Harmer
0.518
3145683EARLEYS
Solar/Wind Harmer
0.259
3145683EARLEYS
Solar/Wind Harmer
0.259
3146043SEABORD
Solar/Wind Harmer
0.257
315607AA1-063A GEN
Solar/Wind Harmer
0.525
315652AC1-086 GEN
Solar/Wind Harmer
28.1
316087AB2-174 GEN
Solar/Wind Harmer
0.007
3137643SOCKMAN
Solar/Wind Harmer
1.014
3145796HORNRTN
Solar/Wind Harmer
0.808
3145796HORNRTN
Solar/Wind Harmer
0.101
3146033SCOT NK
Solar/Wind Harmer
1.005
971445AH1-216 GEN
Solar/Wind Harmer
17.313
970831AG2-522 GEN
Solar/Wind Harmer
10.467
316005AA1-067
Solar/Wind Harmer
0.262
3145746EVERETS
Solar/Wind Harmer
0.972
3145746EVERETS
Solar/Wind Harmer
0.244
3145746EVERETS
Solar/Wind Harmer
0.244
3145746EVERETS
Solar/Wind Harmer
0.244
970181AG2-120 GEN
Solar/Wind Harmer
3.041
957861AF2-080 GEN
Solar/Wind Harmer
10.405
316420AA1-050 GEN
Solar/Wind Harmer
0.008
3145573BETHELC
Solar/Wind Harmer
0.239
3145573BETHELC
Solar/Wind Harmer
0.239
316319Z2-044 C
Solar/Wind Harmer
0
970533AG2-339 GEN
50/50
33.012
970531AG2-338 GEN
50/50
13.205
315242AE2-183_GT2
50/50
5.909
315241AE2-183_GT1
50/50
5.872
972185AH1-677 GEN
50/50
21.302
3151041BRUNSWICKG3
50/50
4.631
972187AH1-678 GEN
50/50
10.628
3150991CHESPKB
50/50
3.212
3150991CHESPKB
50/50
3.134
970933AG2-581 GEN
Solar/Wind Harmer
26.853
970099AG2-077 GEN
Solar/Wind Harmer
31.397
316185AD1-033 GEN
Solar/Wind Harmer
0.008
3145506HICKORY
Solar/Wind Harmer
1.172
3145506HICKORY
Solar/Wind Harmer
0.703
3145506HICKORY
Solar/Wind Harmer
0.176
316339AD2-160 GEN
Solar/Wind Harmer
0.474
316018AA1-139 ULT2
Solar/Wind Harmer
0.007
316017AA1-139 ULT1
Solar/Wind Harmer
0.163
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.279
3137176SLIGO L2192
Solar/Wind Harmer
1.158
3146456SLIGO L269
Solar/Wind Harmer
5.15
3130086AYDLETT
Solar/Wind Harmer
1.162
316036AC1-147 C
Solar/Wind Harmer
0.054
3146386ELIZ CT
Solar/Wind Harmer
0.287
316431W1029_GEN1
Solar/Wind Harmer
0.002
316433W1029_GEN2
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.283
3146516WINFALL
Solar/Wind Harmer
0.283
3146516WINFALL
Solar/Wind Harmer
0.283
3146626S HERTFORD
Solar/Wind Harmer
0.282
3146626S HERTFORD
Solar/Wind Harmer
0.282
3144356SAPONY
Solar/Wind Harmer
2.345
3146376EDENTON
Solar/Wind Harmer
1.231
3146376EDENTON
Solar/Wind Harmer
1.231
315742AE1-103 GEN
Solar/Wind Harmer
0.003
316065AD1-022 GEN
Solar/Wind Harmer
12.23
3145893MURPHYS
Solar/Wind Harmer
1.749
3145893MURPHYS
Solar/Wind Harmer
0.47
3146173TUNIS
Solar/Wind Harmer
0.26
3146173TUNIS
Solar/Wind Harmer
0.26
3142666NORTHAMPTON
Solar/Wind Harmer
0.256
3142666NORTHAMPTON
Solar/Wind Harmer
0.256
3142666NORTHAMPTON
Solar/Wind Harmer
0.256
3142666NORTHAMPTON
Solar/Wind Harmer
0.154
316181AB2-040 GEN
Solar/Wind Harmer
0.37
316426AA2-053 GEN
Solar/Wind Harmer
0.859
3145593CAROLNA
Solar/Wind Harmer
0.253
3145593CAROLNA
Solar/Wind Harmer
0.253
966811AG1-552 GEN
Solar/Wind Harmer
2.746
3145593CAROLNA
Solar/Wind Harmer
0.315
3145796HORNRTN
Solar/Wind Harmer
0.757
3145783HORNRTN
Solar/Wind Harmer
4.484
3145783HORNRTN
Solar/Wind Harmer
3.587
3145783HORNRTN
Solar/Wind Harmer
1.121
3145783HORNRTN
Solar/Wind Harmer
0.448
3145933PARMELE
Solar/Wind Harmer
0.497
3145933PARMELE
Solar/Wind Harmer
0.248
316236AE1-162_GEN
Solar/Wind Harmer
0.002
316274AC1-208 GEN
Solar/Wind Harmer
1.28
3145493TOT1
Solar/Wind Harmer
0.553
3145453TOT5
Solar/Wind Harmer
0.332
3145603CNETO
Solar/Wind Harmer
0.221
939181AE1-148 GEN
Solar/Wind Harmer
11.37
961601AG1-000A GEN
Solar/Wind Harmer
4.187
316263AC1-034 GEN
Solar/Wind Harmer
8.947
970657AG2-426 GEN
Solar/Wind Harmer
8.169
970657AG2-426 GEN
Solar/Wind Harmer
1.713
313527AB2-043 GEN
Solar/Wind Harmer
0.003
962561AG1-105 GEN
Solar/Wind Harmer
10.674
964791AG1-342 GEN
Solar/Wind Harmer
4.265
3146843MT LREL
Solar/Wind Harmer
0.222
3146843MT LREL
Solar/Wind Harmer
0.222
971741AH1-377 GEN
Solar/Wind Harmer
20.961
316222AC1-221 GEN
Solar/Wind Harmer
0.858
970323AG2-213 GEN
Solar/Wind Harmer
8.579
971775AH1-396 GEN
Solar/Wind Harmer
0.322
316034AC1-036 C
Solar/Wind Harmer
0.015
970301AG2-198 GEN
Solar/Wind Harmer
8.245
958211AF2-115 GEN
Solar/Wind Harmer
2.178
963191AG1-168 GEN
Solar/Wind Harmer
0.726
3144293JTRSVLE
Adder
0.578
3144293JTRSVLE
Adder
0.487
316033AB2-134 GEN
Solar/Wind Harmer
0.011
315697AD1-025 GEN
Solar/Wind Harmer
0.203
3147133PAMPLIN
Solar/Wind Harmer
0.175
3147133PAMPLIN
Solar/Wind Harmer
0.14
942751AE2-291 GEN
Solar/Wind Harmer
8.208
316240AF1-291 C
Solar/Wind Harmer
0.001
270016AE1-250 BESS
Solar/Wind Harmer
0.004
3143226MDLTHAN
Solar/Wind Helper
0.285
316045AC1-158 PL2
Solar/Wind Helper
4.385
3147666LOUISA
Solar/Wind Helper
0.894
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
3143316POE
Solar/Wind Harmer
0.886
972265AH1-717 GEN
Adder
17.287
3151201GRAVEL4
Adder
16.205
3151191GRAVEL3
Adder
16
3151211GRAVEL5
Adder
16
316118AC1-105 GEN
Solar/Wind Harmer
0.572
3147173SINAI
Solar/Wind Harmer
0.221
3147243WELCO
Solar/Wind Harmer
0.138
971443AH1-215 GEN
Solar/Wind Harmer
3.393
3144303KENBRDG
Solar/Wind Harmer
0.161
970683AG2-441 GEN
Solar/Wind Harmer
12.733
970681AG2-440 GEN
Solar/Wind Harmer
10.187
970865AG2-541 GEN
Solar/Wind Harmer
6.495
946301AF1-294 GEN
Solar/Wind Harmer
3.582
961791AG1-021 GEN
Solar/Wind Harmer
1.742
316369SG1_INVT
Solar/Wind Harmer
0.007
315657AE1-056 GEN
Solar/Wind Harmer
6.032
3138283WHITEMARSH
Solar/Wind Harmer
0.04
316123AC1-075 GEN
Solar/Wind Harmer
0.226
970165AG2-112 GEN
Solar/Wind Harmer
1.338
970163AG2-111 GEN
Solar/Wind Harmer
1.276
316132AB2-190 GEN1
Solar/Wind Harmer
0.837
3141873WAN 176
Solar/Wind Harmer
0.024
315662AE1-191 GEN
Solar/Wind Harmer
0.004
315666AE1-190 GEN
Solar/Wind Harmer
0.001
944641AF1-129 GEN
Adder
58.874
270013AE1-250 PV
Solar/Wind Harmer
0.004
316447AC1-158 HLD
Solar/Wind Helper
3.015
3151031BRUNSWICKG2
50/50
4.631
3151101ELIZAR3
50/50
28.615
3151161SURRY 1
50/50
8.552
970917AG2-570 GEN
Solar/Wind Harmer
29.876
315773AC2-141 GEN
Solar/Wind Harmer
11.469
944581AF1-123 GEN
Solar/Wind Harmer
67.537
944601AF1-125 GEN
Solar/Wind Harmer
66.496
3146456SLIGO L269
Solar/Wind Harmer
0.291
971153AH1-033 GEN
Solar/Wind Harmer
3.364
3144873MCLAUGH
Solar/Wind Harmer
0.007
316320Y1-086
Solar/Wind Harmer
0.002
316435W1029_GEN3
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.283
3146626S HERTFORD
Solar/Wind Harmer
0.282
3144536CHRHLND
Solar/Wind Harmer
0.041
316478AD1-087 GEN
Solar/Wind Harmer
0.967
316486AD2-202 GEN
Solar/Wind Harmer
0.284
3146376EDENTON
Solar/Wind Harmer
0.277
3145273HOLLAND
Solar/Wind Harmer
0.205
315614AA2-178 GEN
Solar/Wind Harmer
1.556
971157AH1-035 GEN
Solar/Wind Harmer
3.215
315737AD1-076 GEN
Solar/Wind Harmer
3.437
3146206CASHIE
Solar/Wind Harmer
0.264
316365GEN2_N
Solar/Wind Harmer
0.591
3156081AA2-088 GEN
Solar/Wind Harmer
0.006
3145893MURPHYS
Solar/Wind Harmer
0.437
3145893MURPHYS
Solar/Wind Harmer
0.261
3156021HOLLOMANSOL
Solar/Wind Harmer
1.186
957521AF2-046 GEN
Solar/Wind Harmer
19.425
961681AG1-008 GEN
Solar/Wind Harmer
19.425
3146173TUNIS
Solar/Wind Harmer
0.26
316463AE2-346 GEN
Solar/Wind Harmer
0.223
316140AB2-099
Solar/Wind Harmer
0.093
962331AG1-082 GEN
Solar/Wind Harmer
2.771
3146263WOODLND
Solar/Wind Harmer
0.257
3145963POPLR C
Solar/Wind Harmer
0.257
3142666NORTHAMPTON
Solar/Wind Harmer
0.256
316317KELFORD C
Solar/Wind Harmer
0.025
3145823KELFORD
Solar/Wind Harmer
0.255
313506AB2-031 GEN
Solar/Wind Harmer
0.787
3145796HORNRTN
Solar/Wind Harmer
1.01
3145796HORNRTN
Solar/Wind Harmer
0.252
3145933PARMELE
Solar/Wind Harmer
0.248
966801AG1-551 GEN
Solar/Wind Harmer
2.893
3145336SMITFLD
Solar/Wind Harmer
0.099
316210AC1-098 GEN
Solar/Wind Harmer
2.302
3147043LAWRENC
Solar/Wind Harmer
0.148
3145746EVERETS
Solar/Wind Harmer
0.244
3145746EVERETS
Solar/Wind Harmer
0.244
315724AD1-057 GEN
Solar/Wind Harmer
0.913
316327AA2-057 GEN
Solar/Wind Harmer
0.365
3146073TAR RVR
Solar/Wind Harmer
0.239
3146083TARBORO
Solar/Wind Harmer
0.239
3146233WITAKRS
Solar/Wind Harmer
1.197
3146233WITAKRS
Solar/Wind Harmer
0.162
970661AG2-428 GEN
Solar/Wind Harmer
5.046
3138543CONSLDL
Solar/Wind Harmer
0.157
961601AG1-000A GEN
Solar/Wind Harmer
16.749
3145543BTLEBRO
Solar/Wind Harmer
0.235
3145543BTLEBRO
Solar/Wind Harmer
0.235
971623AH1-311 GEN
Solar/Wind Harmer
0.471
316083AB2-161 GEN
Solar/Wind Harmer
0.003
970659AG2-427 GEN
Solar/Wind Harmer
2.402
3151221GRAVEL6
Adder
16.187
3151171GRAVELC
Adder
3.114
3144216WINCHST
Adder
0.839
316131AB2-060 GEN
Solar/Wind Harmer
0.698
3150921YORKTN3
Adder
5.575
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
9.432
964241AG1-285 GEN
Solar/Wind Harmer
14.377
315813AE1-149 C
Solar/Wind Harmer
11.28
961611AG1-000B GEN
Solar/Wind Harmer
5.505
316283AC2-100 C
Solar/Wind Harmer
0.403
315785AD2-033 C
Solar/Wind Harmer
1.667
970257AG2-171 GEN
Solar/Wind Harmer
6.434
971683AH1-343 GEN
Solar/Wind Harmer
7.298
959311AF2-222 GEN
Solar/Wind Harmer
17.616
970909AG2-566 GEN
Solar/Wind Harmer
2.061
963181AG1-167 GEN
Solar/Wind Harmer
0.726
3144293JTRSVLE
Adder
0.578
3147133PAMPLIN
Solar/Wind Harmer
0.549
971193AH1-056 GEN
Solar/Wind Harmer
10.649
316382AG1-145 C
Solar/Wind Harmer
0.001
315778AD1-151 GEN
Solar/Wind Harmer
13.656
315839AE2-212 C
Solar/Wind Harmer
0.001
965281AG1-393 GEN
Solar/Wind Harmer
1.676
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970129AG2-093 GEN
Solar/Wind Harmer
9.286
3146926FARMVIL
Solar/Wind Harmer
0.081
970133AG2-095 GEN
Solar/Wind Harmer
1.245
316156AD2-030 GEN
Solar/Wind Harmer
0.088
3141873WAN 176
Solar/Wind Harmer
2.112
316280AD1-041 GEN
Solar/Wind Harmer
0.002
316044AC1-158 PL1
Solar/Wind Helper
1.37
316450AC1-158 RIC
Solar/Wind Helper
0.365
3147666LOUISA
Solar/Wind Helper
0.514
LAGNLTFEXP_LAGN->PJM
CLTF
10.343
CBM South 2LTFEXP_CBM-S2->PJM
CBM
33.715
TVALTFEXP_TVA->PJM
CLTF
5.16
CPLELTFEXP_CPLE->PJM
CLTF
15.827
CBM West 2LTFEXP_CBM-W2->PJM
CBM
53.426
CBM West 1LTFEXP_CBM-W1->PJM
CBM
29.836
CBM South 1LTFEXP_CBM-S1->PJM
CBM
17.541
MECLTFEXP_MEC->PJM
CLTF
4.755
SIGELTFEXP_SIGE->PJM
CLTF
0.141
NYPJM->LTFIMP_NY
CLTF
2.482
LGEELTFEXP_LGEE->PJM
CLTF
1.68
WECLTFEXP_WEC->PJM
CLTF
0.862

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:128.65 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:5068.75
MW Contribution:13.84
Bus #Bus NameTypeMW Contribution
315244AE2-183_ST
50/50
10.046
963041AG1-153 GEN
50/50
9.229
315779AE2-040
50/50
4.019
3151541CLOVER2
50/50
5.903
3151081ELIZAR1
50/50
26.625
941031AE2-094 GEN
Solar/Wind Harmer
76.807
315243AE2-183_GT3
50/50
5.81
3151051BRUNSWICKS1
50/50
9.459
3151021BRUNSWICKG1
50/50
4.558
971451AH1-221 GEN
50/50
13.843
3151531CLOVER1
50/50
5.931
940641AE2-051 GEN
Solar/Wind Harmer
38.323
939411AE1-173 GEN
Solar/Wind Harmer
192.154
970919AG2-571 GEN
Solar/Wind Harmer
11.781
970087AG2-069 GEN
Solar/Wind Harmer
34.73
957481AF2-042 GEN
Solar/Wind Harmer
102.878
316294AC1-161 GEN
Solar/Wind Harmer
10.352
944591AF1-124 GEN
Solar/Wind Harmer
143.606
316388AE2-253 GEN
Solar/Wind Harmer
2.083
3146456SLIGO L269
Solar/Wind Harmer
-0.031
316375AC2-012 GEN
Solar/Wind Harmer
10.604
3150981CHESPKA
Adder
3.405
315693AD1-088 GEN
Solar/Wind Harmer
15.307
944011AF1-069 GEN
Solar/Wind Harmer
24.066
970673AG2-436 GEN
Solar/Wind Harmer
84.048
970673AG2-436 GEN
Solar/Wind Harmer
42.556
971967AH1-528 GEN
Solar/Wind Harmer
73.252
970085AG2-068 GEN
Solar/Wind Harmer
23.153
970581AG2-369 GEN
Solar/Wind Harmer
19.912
316315AB2-025 C
Solar/Wind Harmer
0.873
315814AE2-033 C
Solar/Wind Harmer
30.01
957871AF2-081 GEN
Solar/Wind Harmer
15.436
970533AG2-339 GEN
50/50
32.408
970531AG2-338 GEN
50/50
12.963
315242AE2-183_GT2
50/50
5.81
315241AE2-183_GT1
50/50
5.775
972185AH1-677 GEN
50/50
20.947
3151041BRUNSWICKG3
50/50
4.558
972187AH1-678 GEN
50/50
10.459
970933AG2-581 GEN
Solar/Wind Harmer
34.906
970099AG2-077 GEN
Solar/Wind Harmer
41.151
3144356SAPONY
Solar/Wind Harmer
1.128
316185AD1-033 GEN
Solar/Wind Harmer
3.27
3145506HICKORY
Solar/Wind Harmer
-0.123
3145506HICKORY
Solar/Wind Harmer
-0.074
3145506HICKORY
Solar/Wind Harmer
-0.018
316339AD2-160 GEN
Solar/Wind Harmer
2.083
316018AA1-139 ULT2
Solar/Wind Harmer
2.645
316017AA1-139 ULT1
Solar/Wind Harmer
2.498
3142956BIRDNECK
Solar/Wind Harmer
1.655
3137176SLIGO L2192
Solar/Wind Harmer
-0.122
3146456SLIGO L269
Solar/Wind Harmer
3.64
316316AC1-027 C
Solar/Wind Harmer
0.946
3130086AYDLETT
Solar/Wind Harmer
-0.123
316036AC1-147 C
Solar/Wind Harmer
0.827
3150991CHESPKB
Adder
2.857
3150991CHESPKB
Adder
2.788
3146386ELIZ CT
Solar/Wind Harmer
-0.03
316431W1029_GEN1
Solar/Wind Harmer
5.494
316433W1029_GEN2
Solar/Wind Harmer
5.494
3146516WINFALL
Solar/Wind Harmer
-0.03
3146516WINFALL
Solar/Wind Harmer
-0.03
3146516WINFALL
Solar/Wind Harmer
-0.03
3146626S HERTFORD
Solar/Wind Harmer
-0.03
3146626S HERTFORD
Solar/Wind Harmer
-0.03
3146376EDENTON
Solar/Wind Harmer
0.884
3146376EDENTON
Solar/Wind Harmer
0.884
315742AE1-103 GEN
Solar/Wind Harmer
3.09
316065AD1-022 GEN
Solar/Wind Harmer
14.49
3145893MURPHYS
Solar/Wind Harmer
0.805
3145893MURPHYS
Solar/Wind Harmer
-0.052
316181AB2-040 GEN
Solar/Wind Harmer
4.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.029
3142666NORTHAMPTON
Solar/Wind Harmer
-0.029
3142666NORTHAMPTON
Solar/Wind Harmer
-0.029
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.029
3146173TUNIS
Solar/Wind Harmer
-0.029
316426AA2-053 GEN
Solar/Wind Harmer
2.872
3145796HORNRTN
Solar/Wind Harmer
-0.085
3145593CAROLNA
Solar/Wind Harmer
-0.028
3145593CAROLNA
Solar/Wind Harmer
-0.028
966811AG1-552 GEN
Solar/Wind Harmer
3.194
3145593CAROLNA
Solar/Wind Harmer
0.236
3145783HORNRTN
Solar/Wind Harmer
3.355
3145783HORNRTN
Solar/Wind Harmer
2.684
319010AE1-072 C
Solar/Wind Harmer
6.231
3146406KITTY HAWK
Solar/Wind Harmer
0.026
3151091ELIZAR2
Adder
24.656
3152611GOSPORTB
Adder
3.473
3152621GOSPORTC
Adder
2.948
3152601GOSPORTA
Adder
2.719
313526AB2-022
Solar/Wind Harmer
0.825
316305AF2-043 C
Solar/Wind Harmer
0.92
316321Z2-027
Solar/Wind Harmer
0.822
3146396TANGLEW
Solar/Wind Harmer
0.561
3145176PASQUOTANK
Solar/Wind Harmer
-0.019
3146486SUNBURY
Solar/Wind Harmer
-0.03
3146486SUNBURY
Solar/Wind Harmer
-0.03
315611Z1-036_GEN2
Solar/Wind Harmer
7.417
315835AF2-110_GEN
Solar/Wind Harmer
3.752
3130156CHOWAN
Solar/Wind Harmer
-0.03
3130156CHOWAN
Solar/Wind Harmer
-0.03
315816AE2-034 GEN
Solar/Wind Harmer
2.381
3130546PLYMOUTH
Solar/Wind Harmer
-0.029
315732AD1-074 GEN1
Solar/Wind Harmer
5.881
315733AD1-074 GEN2
Solar/Wind Harmer
5.881
315735AD1-075 GEN1
Solar/Wind Harmer
2.941
946281AF1-292 GEN
Solar/Wind Harmer
0.651
965291AG1-394 GEN
Solar/Wind Harmer
2.57
316311AC2-079 GEN
Solar/Wind Harmer
14.59
3146206CASHIE
Solar/Wind Harmer
-0.029
970601AG2-382 GEN
Solar/Wind Harmer
12.655
315833AF1-017_GEN
Solar/Wind Harmer
5.49
316349AD2-085 GEN
Solar/Wind Harmer
2.571
316087AB2-174 GEN
Solar/Wind Harmer
4.115
316318V4-068
Solar/Wind Harmer
0.719
3145893MURPHYS
Solar/Wind Harmer
-0.077
3145893MURPHYS
Solar/Wind Harmer
-0.029
315652AC1-086 GEN
Solar/Wind Harmer
32.341
3145513AHOSKIE
Solar/Wind Harmer
0.25
961941AG1-037 GEN
Solar/Wind Harmer
0.215
3145513AHOSKIE
Solar/Wind Harmer
-0.029
3146043SEABORD
Solar/Wind Harmer
-0.029
315607AA1-063A GEN
Solar/Wind Harmer
2.891
3145683EARLEYS
Solar/Wind Harmer
-0.057
3145683EARLEYS
Solar/Wind Harmer
-0.029
3145683EARLEYS
Solar/Wind Harmer
-0.029
3137643SOCKMAN
Solar/Wind Harmer
-0.114
3145796HORNRTN
Solar/Wind Harmer
-0.09
3145796HORNRTN
Solar/Wind Harmer
-0.011
3146033SCOT NK
Solar/Wind Harmer
-0.111
970831AG2-522 GEN
Solar/Wind Harmer
13.829
3143316POE
Solar/Wind Harmer
-0.109
971445AH1-216 GEN
Solar/Wind Harmer
16.968
316005AA1-067
Solar/Wind Harmer
0.549
3145746EVERETS
Solar/Wind Harmer
-0.107
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
970181AG2-120 GEN
Solar/Wind Harmer
3.56
957861AF2-080 GEN
Solar/Wind Harmer
11.769
316420AA1-050 GEN
Solar/Wind Harmer
3.06
316319Z2-044 C
Solar/Wind Harmer
1.479
3145573BETHELC
Solar/Wind Harmer
-0.027
3145573BETHELC
Solar/Wind Harmer
-0.027
972265AH1-717 GEN
Adder
17.747
3151201GRAVEL4
Adder
16.636
3151191GRAVEL3
Adder
16.426
3151211GRAVEL5
Adder
16.426
316239AB2-077_GEN
Solar/Wind Harmer
0.772
316238AB2-078_GEN
Solar/Wind Harmer
0.772
316118AC1-105 GEN
Solar/Wind Harmer
1.739
3147173SINAI
Solar/Wind Harmer
-0.025
3147243WELCO
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
4.598
3144303KENBRDG
Solar/Wind Harmer
-0.019
316369SG1_INVT
Solar/Wind Harmer
4.063
3142433PROV 92
Adder
0.277
3142433PROV 92
Adder
0.277
316164AC1-076 GEN
Solar/Wind Helper
1.186
970683AG2-441 GEN
Solar/Wind Harmer
2.176
970681AG2-440 GEN
Solar/Wind Harmer
1.741
3145783HORNRTN
Solar/Wind Harmer
0.839
3145783HORNRTN
Solar/Wind Harmer
0.335
316274AC1-208 GEN
Solar/Wind Harmer
2.979
316236AE1-162_GEN
Solar/Wind Harmer
0.832
3145933PARMELE
Solar/Wind Harmer
-0.055
3145933PARMELE
Solar/Wind Harmer
-0.027
970657AG2-426 GEN
Solar/Wind Harmer
8.539
970657AG2-426 GEN
Solar/Wind Harmer
1.786
939181AE1-148 GEN
Solar/Wind Harmer
15.107
3145493TOT1
Solar/Wind Harmer
0.413
3145453TOT5
Solar/Wind Harmer
0.248
3145603CNETO
Solar/Wind Harmer
0.165
961601AG1-000A GEN
Solar/Wind Harmer
10.403
316263AC1-034 GEN
Solar/Wind Harmer
12.4
313527AB2-043 GEN
Solar/Wind Harmer
4.152
962561AG1-105 GEN
Solar/Wind Harmer
14.279
964791AG1-342 GEN
Solar/Wind Harmer
5.416
3146843MT LREL
Solar/Wind Harmer
-0.025
3146843MT LREL
Solar/Wind Harmer
-0.025
971741AH1-377 GEN
Solar/Wind Harmer
28.356
316222AC1-221 GEN
Solar/Wind Harmer
2.385
970323AG2-213 GEN
Solar/Wind Harmer
11.633
971775AH1-396 GEN
Solar/Wind Harmer
1.657
316034AC1-036 C
Solar/Wind Harmer
0.431
316033AB2-134 GEN
Solar/Wind Harmer
7.334
315697AD1-025 GEN
Solar/Wind Harmer
4.6
970301AG2-198 GEN
Solar/Wind Harmer
11.27
3144293JTRSVLE
Adder
0.603
3144293JTRSVLE
Adder
0.508
944641AF1-129 GEN
Adder
79.37
3150341NORNECKC1
Adder
1.21
3150341NORNECKC1
Adder
1.2
316447AC1-158 HLD
Solar/Wind Helper
3.634
315651AD1-115 GEN
Solar/Wind Helper
0.76
316246AF1-032 C
Solar/Wind Harmer
0.618
3146516WINFALL
Solar/Wind Harmer
-0.098
3146516WINFALL
Solar/Wind Harmer
-0.03
962491AG1-098 GEN
Solar/Wind Harmer
20.194
315800Z1-036_GEN1
Solar/Wind Harmer
7.417
316093AE2-104_GEN
Solar/Wind Harmer
8.728
316023GEN1_S
Solar/Wind Harmer
2.02
3130156CHOWAN
Solar/Wind Harmer
-0.03
3145663CRESWEL
Solar/Wind Harmer
-0.082
971163AH1-040 GEN
Solar/Wind Harmer
27.585
316072AD1-144
Solar/Wind Harmer
0.593
315687AD1-152 GEN
Solar/Wind Harmer
3.505
960081AF2-299 GEN
Solar/Wind Harmer
3.27
3146206CASHIE
Solar/Wind Harmer
-0.029
971547AH1-271 GEN
Solar/Wind Harmer
7.231
3145893MURPHYS
Solar/Wind Harmer
-0.115
3145893MURPHYS
Solar/Wind Harmer
0.856
316011AB1-132 GEN
Solar/Wind Harmer
6.015
962571AG1-106 GEN
Solar/Wind Harmer
4.132
3146173TUNIS
Solar/Wind Harmer
-0.029
3145683EARLEYS
Solar/Wind Harmer
-0.029
3146263WOODLND
Solar/Wind Harmer
-0.028
316190AA2-174 GEN
Solar/Wind Harmer
0.349
3145796HORNRTN
Solar/Wind Harmer
-0.093
3145796HORNRTN
Solar/Wind Harmer
-0.028
971795AH1-408 GEN
Solar/Wind Harmer
21.251
3145823KELFORD
Solar/Wind Harmer
-0.028
3145783HORNRTN
Solar/Wind Harmer
-0.028
3145963POPLR C
Solar/Wind Harmer
-0.028
316174AB2-169 GEN
Solar/Wind Harmer
4.328
3147043LAWRENC
Adder
2.254
316212AC1-099_GEN
Solar/Wind Harmer
2.415
970661AG2-428 GEN
Solar/Wind Harmer
29.373
3145336SMITFLD
Solar/Wind Harmer
-0.11
316129AC1-054 GEN
Solar/Wind Harmer
2.418
971065AG2-659 GEN
Solar/Wind Harmer
13.753
3146293MARTNCO
Solar/Wind Harmer
0.17
315722AD1-056 GEN
Solar/Wind Harmer
2.859
316381AD1-082 GEN
Solar/Wind Harmer
2.488
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
970659AG2-427 GEN
Solar/Wind Harmer
14.32
316494AC1-189 GEN
Solar/Wind Harmer
2.894
3146233WITAKRS
Solar/Wind Harmer
-0.106
961671AG1-007 GEN
Solar/Wind Harmer
0.338
3146083TARBORO
Solar/Wind Harmer
-0.027
3145493TOT1
Solar/Wind Harmer
0.792
316359AB2-059 GEN
Solar/Wind Harmer
3.567
316049AB1-081 GEN
Solar/Wind Harmer
2.854
3142053HEARTS
Solar/Wind Harmer
0.311
3145543BTLEBRO
Solar/Wind Harmer
-0.026
3145543BTLEBRO
Solar/Wind Harmer
-0.021
3151171GRAVELC
Adder
2.431
316237AB2-079_GEN
Solar/Wind Harmer
0.772
970401AG2-262 GEN
Solar/Wind Harmer
1.655
3138126ROCKLANDING
Solar/Wind Harmer
0.076
961611AG1-000B GEN
Solar/Wind Harmer
12.112
316003AC1-222 GEN
Solar/Wind Harmer
2.339
971647AH1-324 GEN
Solar/Wind Harmer
11.817
971317AH1-138 GEN
Solar/Wind Harmer
2.931
970685AG2-442 GEN
Solar/Wind Harmer
19.464
3144293JTRSVLE
Adder
0.603
3141843SHACKLE
Adder
0.78
3142433PROV 92
Adder
0.277
3142433PROV 92
Adder
0.277
944631AF1-128 GEN
Adder
63.787
3150351NORNECKC2
Adder
1.152
316045AC1-158 PL2
Solar/Wind Helper
5.286
3147666LOUISA
Solar/Wind Helper
1.014
316192AB2-158 GEN
Solar/Wind Helper
1.677
316254AC1-120 GEN1
Solar/Wind Helper
1.048
3151031BRUNSWICKG2
50/50
4.558
970413AG2-270 GEN
50/50
25.882
3151101ELIZAR3
50/50
26.966
970917AG2-570 GEN
Solar/Wind Harmer
93.072
315773AC2-141 GEN
Solar/Wind Harmer
13.388
944581AF1-123 GEN
Solar/Wind Harmer
143.09
944601AF1-125 GEN
Solar/Wind Harmer
140.857
316478AD1-087 GEN
Solar/Wind Harmer
2.694
316486AD2-202 GEN
Solar/Wind Harmer
0.789
3146456SLIGO L269
Solar/Wind Harmer
-0.031
971153AH1-033 GEN
Solar/Wind Harmer
3.757
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316320Y1-086
Solar/Wind Harmer
1.792
316435W1029_GEN3
Solar/Wind Harmer
5.494
3146516WINFALL
Solar/Wind Harmer
-0.03
3146626S HERTFORD
Solar/Wind Harmer
-0.03
316365GEN2_N
Solar/Wind Harmer
2.02
3146376EDENTON
Solar/Wind Harmer
-0.03
3144536CHRHLND
Solar/Wind Harmer
-0.005
3145273HOLLAND
Solar/Wind Harmer
-0.022
315614AA2-178 GEN
Solar/Wind Harmer
3.175
971157AH1-035 GEN
Solar/Wind Harmer
3.641
315737AD1-076 GEN
Solar/Wind Harmer
5.527
966621AG1-532 GEN
Solar/Wind Harmer
0.59
3156081AA2-088 GEN
Solar/Wind Harmer
9.415
3146206CASHIE
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
0.201
3145893MURPHYS
Solar/Wind Harmer
-0.029
957521AF2-046 GEN
Solar/Wind Harmer
22.687
961681AG1-008 GEN
Solar/Wind Harmer
22.687
313506AB2-031 GEN
Solar/Wind Harmer
2.311
3142666NORTHAMPTON
Solar/Wind Harmer
-0.029
3146173TUNIS
Solar/Wind Harmer
-0.029
3156021HOLLOMANSOL
Solar/Wind Harmer
3.868
316463AE2-346 GEN
Solar/Wind Harmer
0.464
316140AB2-099
Solar/Wind Harmer
0.193
962331AG1-082 GEN
Solar/Wind Harmer
3.582
3146263WOODLND
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.113
3145796HORNRTN
Solar/Wind Harmer
-0.028
316317KELFORD C
Solar/Wind Harmer
1.333
3145823KELFORD
Solar/Wind Harmer
-0.028
3145963POPLR C
Solar/Wind Harmer
-0.028
3147043LAWRENC
Solar/Wind Harmer
-0.017
316210AC1-098 GEN
Solar/Wind Harmer
4.347
970661AG2-428 GEN
Solar/Wind Harmer
5.205
3145336SMITFLD
Solar/Wind Harmer
-0.011
3145933PARMELE
Solar/Wind Harmer
-0.027
966801AG1-551 GEN
Solar/Wind Harmer
3.433
315724AD1-057 GEN
Solar/Wind Harmer
1.573
316083AB2-161 GEN
Solar/Wind Harmer
4.404
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
316327AA2-057 GEN
Solar/Wind Harmer
2.736
970659AG2-427 GEN
Solar/Wind Harmer
2.538
3146233WITAKRS
Solar/Wind Harmer
0.56
3146233WITAKRS
Solar/Wind Harmer
-0.018
3138543CONSLDL
Solar/Wind Harmer
-0.018
3146073TAR RVR
Solar/Wind Harmer
-0.027
3146083TARBORO
Solar/Wind Harmer
-0.027
961601AG1-000A GEN
Solar/Wind Harmer
10.535
3145543BTLEBRO
Solar/Wind Harmer
-0.026
3145543BTLEBRO
Solar/Wind Harmer
-0.026
315813AE1-149 C
Solar/Wind Harmer
16.256
3151221GRAVEL6
Adder
16.617
3151171GRAVELC
Adder
3.197
316131AB2-060 GEN
Solar/Wind Harmer
2.74
316248AF1-058 C
Solar/Wind Harmer
0.76
960061AF2-297 GEN
Solar/Wind Harmer
12.605
3144216WINCHST
Adder
0.839
3150921YORKTN3
Adder
5.559
964241AG1-285 GEN
Solar/Wind Harmer
19.332
961611AG1-000B GEN
Solar/Wind Harmer
5.168
315785AD2-033 C
Solar/Wind Harmer
5.364
316283AC2-100 C
Solar/Wind Harmer
2.209
970257AG2-171 GEN
Solar/Wind Harmer
8.725
959311AF2-222 GEN
Solar/Wind Harmer
23.978
971683AH1-343 GEN
Solar/Wind Harmer
9.859
315839AE2-212 C
Solar/Wind Harmer
0.685
970909AG2-566 GEN
Solar/Wind Harmer
2.14
3144293JTRSVLE
Adder
0.603
3141843SHACKLE
Adder
0.78
3142433PROV 92
Adder
0.277
3142433PROV 92
Adder
0.277
3150351NORNECKC2
Adder
1.171
316044AC1-158 PL1
Solar/Wind Helper
1.651
316450AC1-158 RIC
Solar/Wind Helper
0.44
3147666LOUISA
Solar/Wind Helper
0.583
316170AC1-121 GEN2
Solar/Wind Helper
0.349
LAGNLTFEXP_LAGN->PJM
CLTF
11.324
CBM South 2LTFEXP_CBM-S2->PJM
CBM
34.876
TVALTFEXP_TVA->PJM
CLTF
5.674
CPLELTFEXP_CPLE->PJM
CLTF
16.076
CBM West 2LTFEXP_CBM-W2->PJM
CBM
59.809
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.878
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.45
MECLTFEXP_MEC->PJM
CLTF
5.512
SIGELTFEXP_SIGE->PJM
CLTF
0.166
NYPJM->LTFIMP_NY
CLTF
2.897
LGEELTFEXP_LGEE->PJM
CLTF
2.011
WECLTFEXP_WEC->PJM
CLTF
1.028

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:128.38 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:5058.27
MW Contribution:13.77
Bus #Bus NameTypeMW Contribution
315244AE2-183_ST
50/50
9.99
963041AG1-153 GEN
50/50
9.178
315779AE2-040
50/50
3.975
3151541CLOVER2
50/50
5.868
3151081ELIZAR1
50/50
26.417
941031AE2-094 GEN
Solar/Wind Harmer
76.384
944011AF1-069 GEN
Solar/Wind Harmer
23.934
970673AG2-436 GEN
Solar/Wind Harmer
83.585
970673AG2-436 GEN
Solar/Wind Harmer
42.321
971967AH1-528 GEN
Solar/Wind Harmer
72.843
970085AG2-068 GEN
Solar/Wind Harmer
23.025
970581AG2-369 GEN
Solar/Wind Harmer
19.802
316315AB2-025 C
Solar/Wind Harmer
0.863
315814AE2-033 C
Solar/Wind Harmer
29.689
957871AF2-081 GEN
Solar/Wind Harmer
15.319
319010AE1-072 C
Solar/Wind Harmer
6.184
3146406KITTY HAWK
Solar/Wind Harmer
0.025
3151091ELIZAR2
Adder
24.463
3152611GOSPORTB
Adder
3.446
3152621GOSPORTC
Adder
2.924
3152601GOSPORTA
Adder
2.697
313526AB2-022
Solar/Wind Harmer
0.819
316305AF2-043 C
Solar/Wind Harmer
0.913
316321Z2-027
Solar/Wind Harmer
0.816
3146396TANGLEW
Solar/Wind Harmer
0.557
3145176PASQUOTANK
Solar/Wind Harmer
-0.019
3146486SUNBURY
Solar/Wind Harmer
-0.03
3146486SUNBURY
Solar/Wind Harmer
-0.03
315611Z1-036_GEN2
Solar/Wind Harmer
7.359
315835AF2-110_GEN
Solar/Wind Harmer
3.719
3130156CHOWAN
Solar/Wind Harmer
-0.029
3130156CHOWAN
Solar/Wind Harmer
-0.029
315816AE2-034 GEN
Solar/Wind Harmer
2.363
3130546PLYMOUTH
Solar/Wind Harmer
-0.029
315732AD1-074 GEN1
Solar/Wind Harmer
5.835
315733AD1-074 GEN2
Solar/Wind Harmer
5.835
315735AD1-075 GEN1
Solar/Wind Harmer
2.918
946281AF1-292 GEN
Solar/Wind Harmer
0.645
965291AG1-394 GEN
Solar/Wind Harmer
2.549
3146206CASHIE
Solar/Wind Harmer
-0.029
970601AG2-382 GEN
Solar/Wind Harmer
12.557
316318V4-068
Solar/Wind Harmer
0.713
3145893MURPHYS
Solar/Wind Harmer
-0.077
3145893MURPHYS
Solar/Wind Harmer
-0.029
316311AC2-079 GEN
Solar/Wind Harmer
14.429
316087AB2-174 GEN
Solar/Wind Harmer
4.08
315833AF1-017_GEN
Solar/Wind Harmer
5.429
316349AD2-085 GEN
Solar/Wind Harmer
2.542
315652AC1-086 GEN
Solar/Wind Harmer
32.069
3145513AHOSKIE
Solar/Wind Harmer
0.248
961941AG1-037 GEN
Solar/Wind Harmer
0.214
3145513AHOSKIE
Solar/Wind Harmer
-0.028
3146043SEABORD
Solar/Wind Harmer
-0.028
315607AA1-063A GEN
Solar/Wind Harmer
2.867
3145683EARLEYS
Solar/Wind Harmer
-0.056
3145683EARLEYS
Solar/Wind Harmer
-0.028
3145683EARLEYS
Solar/Wind Harmer
-0.028
3137643SOCKMAN
Solar/Wind Harmer
-0.113
3145796HORNRTN
Solar/Wind Harmer
-0.09
3145796HORNRTN
Solar/Wind Harmer
-0.011
3146033SCOT NK
Solar/Wind Harmer
-0.11
970831AG2-522 GEN
Solar/Wind Harmer
13.728
3143316POE
Solar/Wind Harmer
-0.107
971445AH1-216 GEN
Solar/Wind Harmer
16.766
316005AA1-067
Solar/Wind Harmer
0.545
3145746EVERETS
Solar/Wind Harmer
-0.107
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
970181AG2-120 GEN
Solar/Wind Harmer
3.535
957861AF2-080 GEN
Solar/Wind Harmer
11.684
316420AA1-050 GEN
Solar/Wind Harmer
3.038
316319Z2-044 C
Solar/Wind Harmer
1.468
3145573BETHELC
Solar/Wind Harmer
-0.026
3145573BETHELC
Solar/Wind Harmer
-0.026
316239AB2-077_GEN
Solar/Wind Harmer
0.767
316238AB2-078_GEN
Solar/Wind Harmer
0.767
972265AH1-717 GEN
Adder
17.492
3151201GRAVEL4
Adder
16.397
3151191GRAVEL3
Adder
16.19
3151211GRAVEL5
Adder
16.19
316118AC1-105 GEN
Solar/Wind Harmer
1.728
3147173SINAI
Solar/Wind Harmer
-0.025
3147243WELCO
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
4.563
3144303KENBRDG
Solar/Wind Harmer
-0.018
316369SG1_INVT
Solar/Wind Harmer
3.979
3142433PROV 92
Adder
0.267
3142433PROV 92
Adder
0.267
316164AC1-076 GEN
Solar/Wind Helper
1.177
970683AG2-441 GEN
Solar/Wind Harmer
2.159
970681AG2-440 GEN
Solar/Wind Harmer
1.727
970533AG2-339 GEN
50/50
32.23
970531AG2-338 GEN
50/50
12.892
315242AE2-183_GT2
50/50
5.778
315241AE2-183_GT1
50/50
5.743
972185AH1-677 GEN
50/50
20.831
3151041BRUNSWICKG3
50/50
4.532
972187AH1-678 GEN
50/50
10.401
970933AG2-581 GEN
Solar/Wind Harmer
34.708
970099AG2-077 GEN
Solar/Wind Harmer
40.908
3144356SAPONY
Solar/Wind Harmer
1.116
316185AD1-033 GEN
Solar/Wind Harmer
3.245
3145506HICKORY
Solar/Wind Harmer
-0.122
3145506HICKORY
Solar/Wind Harmer
-0.073
3145506HICKORY
Solar/Wind Harmer
-0.018
316339AD2-160 GEN
Solar/Wind Harmer
2.068
316018AA1-139 ULT2
Solar/Wind Harmer
2.625
316017AA1-139 ULT1
Solar/Wind Harmer
2.479
3142956BIRDNECK
Solar/Wind Harmer
1.642
3137176SLIGO L2192
Solar/Wind Harmer
-0.121
3146456SLIGO L269
Solar/Wind Harmer
3.613
316316AC1-027 C
Solar/Wind Harmer
0.938
3130086AYDLETT
Solar/Wind Harmer
-0.122
316036AC1-147 C
Solar/Wind Harmer
0.82
3150991CHESPKB
Adder
2.834
3150991CHESPKB
Adder
2.766
3146386ELIZ CT
Solar/Wind Harmer
-0.03
316431W1029_GEN1
Solar/Wind Harmer
5.451
316433W1029_GEN2
Solar/Wind Harmer
5.451
3146516WINFALL
Solar/Wind Harmer
-0.03
3146516WINFALL
Solar/Wind Harmer
-0.03
3146516WINFALL
Solar/Wind Harmer
-0.03
3146626S HERTFORD
Solar/Wind Harmer
-0.03
3146626S HERTFORD
Solar/Wind Harmer
-0.03
3146376EDENTON
Solar/Wind Harmer
0.877
3146376EDENTON
Solar/Wind Harmer
0.877
315742AE1-103 GEN
Solar/Wind Harmer
3.064
316065AD1-022 GEN
Solar/Wind Harmer
14.378
3145893MURPHYS
Solar/Wind Harmer
0.798
3145893MURPHYS
Solar/Wind Harmer
-0.051
316181AB2-040 GEN
Solar/Wind Harmer
3.977
3146173TUNIS
Solar/Wind Harmer
-0.028
3146173TUNIS
Solar/Wind Harmer
-0.028
3142666NORTHAMPTON
Solar/Wind Harmer
-0.028
3142666NORTHAMPTON
Solar/Wind Harmer
-0.028
3142666NORTHAMPTON
Solar/Wind Harmer
-0.028
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
316426AA2-053 GEN
Solar/Wind Harmer
2.849
3145796HORNRTN
Solar/Wind Harmer
-0.084
3145593CAROLNA
Solar/Wind Harmer
-0.028
3145593CAROLNA
Solar/Wind Harmer
-0.028
966811AG1-552 GEN
Solar/Wind Harmer
3.169
3145593CAROLNA
Solar/Wind Harmer
0.234
3145783HORNRTN
Solar/Wind Harmer
3.328
3145783HORNRTN
Solar/Wind Harmer
2.662
3145783HORNRTN
Solar/Wind Harmer
0.832
3145783HORNRTN
Solar/Wind Harmer
0.333
316274AC1-208 GEN
Solar/Wind Harmer
2.956
316236AE1-162_GEN
Solar/Wind Harmer
0.822
3145933PARMELE
Solar/Wind Harmer
-0.054
3145933PARMELE
Solar/Wind Harmer
-0.027
970657AG2-426 GEN
Solar/Wind Harmer
8.413
970657AG2-426 GEN
Solar/Wind Harmer
1.759
939181AE1-148 GEN
Solar/Wind Harmer
15.005
3145493TOT1
Solar/Wind Harmer
0.41
3145453TOT5
Solar/Wind Harmer
0.246
3145603CNETO
Solar/Wind Harmer
0.164
961601AG1-000A GEN
Solar/Wind Harmer
10.329
316263AC1-034 GEN
Solar/Wind Harmer
12.313
313527AB2-043 GEN
Solar/Wind Harmer
4.123
962561AG1-105 GEN
Solar/Wind Harmer
14.187
964791AG1-342 GEN
Solar/Wind Harmer
5.382
3146843MT LREL
Solar/Wind Harmer
-0.025
3146843MT LREL
Solar/Wind Harmer
-0.025
971741AH1-377 GEN
Solar/Wind Harmer
28.148
316222AC1-221 GEN
Solar/Wind Harmer
2.372
970323AG2-213 GEN
Solar/Wind Harmer
11.545
971775AH1-396 GEN
Solar/Wind Harmer
1.644
316034AC1-036 C
Solar/Wind Harmer
0.428
970301AG2-198 GEN
Solar/Wind Harmer
11.182
316033AB2-134 GEN
Solar/Wind Harmer
7.183
315697AD1-025 GEN
Solar/Wind Harmer
4.505
3144293JTRSVLE
Adder
0.598
3144293JTRSVLE
Adder
0.504
944641AF1-129 GEN
Adder
76.466
316447AC1-158 HLD
Solar/Wind Helper
3.611
315651AD1-115 GEN
Solar/Wind Helper
0.755
315243AE2-183_GT3
50/50
5.778
3151051BRUNSWICKS1
50/50
9.407
3151021BRUNSWICKG1
50/50
4.532
971451AH1-221 GEN
50/50
13.766
3151531CLOVER1
50/50
5.896
940641AE2-051 GEN
Solar/Wind Harmer
38.111
939411AE1-173 GEN
Solar/Wind Harmer
191.017
970919AG2-571 GEN
Solar/Wind Harmer
11.716
970087AG2-069 GEN
Solar/Wind Harmer
34.538
957481AF2-042 GEN
Solar/Wind Harmer
102.271
316294AC1-161 GEN
Solar/Wind Harmer
10.291
944591AF1-124 GEN
Solar/Wind Harmer
142.584
316388AE2-253 GEN
Solar/Wind Harmer
2.068
3146456SLIGO L269
Solar/Wind Harmer
-0.03
315693AD1-088 GEN
Solar/Wind Harmer
15.212
316375AC2-012 GEN
Solar/Wind Harmer
10.52
3150981CHESPKA
Adder
3.378
316246AF1-032 C
Solar/Wind Harmer
0.613
3146516WINFALL
Solar/Wind Harmer
-0.097
3146516WINFALL
Solar/Wind Harmer
-0.03
962491AG1-098 GEN
Solar/Wind Harmer
20.067
315800Z1-036_GEN1
Solar/Wind Harmer
7.359
316093AE2-104_GEN
Solar/Wind Harmer
8.651
316023GEN1_S
Solar/Wind Harmer
2.001
3130156CHOWAN
Solar/Wind Harmer
-0.029
3145663CRESWEL
Solar/Wind Harmer
-0.081
971163AH1-040 GEN
Solar/Wind Harmer
27.372
316072AD1-144
Solar/Wind Harmer
0.588
315687AD1-152 GEN
Solar/Wind Harmer
3.484
960081AF2-299 GEN
Solar/Wind Harmer
3.241
3146206CASHIE
Solar/Wind Harmer
-0.029
971547AH1-271 GEN
Solar/Wind Harmer
7.175
3145893MURPHYS
Solar/Wind Harmer
-0.114
3145893MURPHYS
Solar/Wind Harmer
0.849
316011AB1-132 GEN
Solar/Wind Harmer
5.964
962571AG1-106 GEN
Solar/Wind Harmer
4.098
3146173TUNIS
Solar/Wind Harmer
-0.028
3145683EARLEYS
Solar/Wind Harmer
-0.028
3146263WOODLND
Solar/Wind Harmer
-0.028
316190AA2-174 GEN
Solar/Wind Harmer
0.346
3145796HORNRTN
Solar/Wind Harmer
-0.093
3145796HORNRTN
Solar/Wind Harmer
-0.028
971795AH1-408 GEN
Solar/Wind Harmer
21.071
3145823KELFORD
Solar/Wind Harmer
-0.028
3145783HORNRTN
Solar/Wind Harmer
-0.028
3145963POPLR C
Solar/Wind Harmer
-0.028
316174AB2-169 GEN
Solar/Wind Harmer
4.295
3147043LAWRENC
Adder
2.236
316212AC1-099_GEN
Solar/Wind Harmer
2.396
316129AC1-054 GEN
Solar/Wind Harmer
2.4
971065AG2-659 GEN
Solar/Wind Harmer
13.655
3145336SMITFLD
Solar/Wind Harmer
-0.109
3146293MARTNCO
Solar/Wind Harmer
0.169
970661AG2-428 GEN
Solar/Wind Harmer
28.962
315722AD1-056 GEN
Solar/Wind Harmer
2.838
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
316381AD1-082 GEN
Solar/Wind Harmer
2.45
316494AC1-189 GEN
Solar/Wind Harmer
2.873
3146233WITAKRS
Solar/Wind Harmer
-0.105
970659AG2-427 GEN
Solar/Wind Harmer
14.096
961671AG1-007 GEN
Solar/Wind Harmer
0.335
3146083TARBORO
Solar/Wind Harmer
-0.026
3145493TOT1
Solar/Wind Harmer
0.787
316359AB2-059 GEN
Solar/Wind Harmer
3.541
316049AB1-081 GEN
Solar/Wind Harmer
2.834
3145543BTLEBRO
Solar/Wind Harmer
-0.026
3145543BTLEBRO
Solar/Wind Harmer
-0.021
3142053HEARTS
Solar/Wind Harmer
0.309
316237AB2-079_GEN
Solar/Wind Harmer
0.767
3151171GRAVELC
Adder
2.396
970401AG2-262 GEN
Solar/Wind Harmer
1.644
3138126ROCKLANDING
Solar/Wind Harmer
0.075
961611AG1-000B GEN
Solar/Wind Harmer
11.911
316003AC1-222 GEN
Solar/Wind Harmer
2.326
971647AH1-324 GEN
Solar/Wind Harmer
11.598
971317AH1-138 GEN
Solar/Wind Harmer
2.891
970685AG2-442 GEN
Solar/Wind Harmer
19.311
3144293JTRSVLE
Adder
0.598
3141843SHACKLE
Adder
0.757
3142433PROV 92
Adder
0.267
3142433PROV 92
Adder
0.267
944631AF1-128 GEN
Adder
61.132
316045AC1-158 PL2
Solar/Wind Helper
5.253
3147666LOUISA
Solar/Wind Helper
1.007
316192AB2-158 GEN
Solar/Wind Helper
1.665
3143226MDLTHAN
Solar/Wind Helper
0.228
316254AC1-120 GEN1
Solar/Wind Helper
1.04
3151031BRUNSWICKG2
50/50
4.532
970413AG2-270 GEN
50/50
25.729
3151101ELIZAR3
50/50
26.755
970917AG2-570 GEN
Solar/Wind Harmer
92.559
315773AC2-141 GEN
Solar/Wind Harmer
13.31
944581AF1-123 GEN
Solar/Wind Harmer
142.072
944601AF1-125 GEN
Solar/Wind Harmer
139.855
316478AD1-087 GEN
Solar/Wind Harmer
2.678
316486AD2-202 GEN
Solar/Wind Harmer
0.784
3146456SLIGO L269
Solar/Wind Harmer
-0.03
971153AH1-033 GEN
Solar/Wind Harmer
3.729
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316320Y1-086
Solar/Wind Harmer
1.779
316435W1029_GEN3
Solar/Wind Harmer
5.451
3146516WINFALL
Solar/Wind Harmer
-0.03
3146626S HERTFORD
Solar/Wind Harmer
-0.03
316365GEN2_N
Solar/Wind Harmer
2.001
3146376EDENTON
Solar/Wind Harmer
-0.029
3144536CHRHLND
Solar/Wind Harmer
-0.005
3145273HOLLAND
Solar/Wind Harmer
-0.022
315614AA2-178 GEN
Solar/Wind Harmer
3.15
971157AH1-035 GEN
Solar/Wind Harmer
3.613
315737AD1-076 GEN
Solar/Wind Harmer
5.484
966621AG1-532 GEN
Solar/Wind Harmer
0.585
3156081AA2-088 GEN
Solar/Wind Harmer
9.337
3146206CASHIE
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
0.2
3145893MURPHYS
Solar/Wind Harmer
-0.029
957521AF2-046 GEN
Solar/Wind Harmer
22.503
961681AG1-008 GEN
Solar/Wind Harmer
22.503
313506AB2-031 GEN
Solar/Wind Harmer
2.291
3146173TUNIS
Solar/Wind Harmer
-0.028
3142666NORTHAMPTON
Solar/Wind Harmer
-0.028
3156021HOLLOMANSOL
Solar/Wind Harmer
3.838
316463AE2-346 GEN
Solar/Wind Harmer
0.46
316140AB2-099
Solar/Wind Harmer
0.192
962331AG1-082 GEN
Solar/Wind Harmer
3.554
3146263WOODLND
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.112
3145796HORNRTN
Solar/Wind Harmer
-0.028
316317KELFORD C
Solar/Wind Harmer
1.323
3145823KELFORD
Solar/Wind Harmer
-0.028
3145963POPLR C
Solar/Wind Harmer
-0.028
3147043LAWRENC
Solar/Wind Harmer
-0.016
316210AC1-098 GEN
Solar/Wind Harmer
4.313
3145336SMITFLD
Solar/Wind Harmer
-0.011
3145933PARMELE
Solar/Wind Harmer
-0.027
966801AG1-551 GEN
Solar/Wind Harmer
3.408
970661AG2-428 GEN
Solar/Wind Harmer
5.132
315724AD1-057 GEN
Solar/Wind Harmer
1.561
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
316327AA2-057 GEN
Solar/Wind Harmer
2.715
316083AB2-161 GEN
Solar/Wind Harmer
4.337
3146233WITAKRS
Solar/Wind Harmer
0.556
3146233WITAKRS
Solar/Wind Harmer
-0.018
3138543CONSLDL
Solar/Wind Harmer
-0.017
970659AG2-427 GEN
Solar/Wind Harmer
2.498
3146073TAR RVR
Solar/Wind Harmer
-0.026
3146083TARBORO
Solar/Wind Harmer
-0.026
961601AG1-000A GEN
Solar/Wind Harmer
10.46
3145543BTLEBRO
Solar/Wind Harmer
-0.026
3145543BTLEBRO
Solar/Wind Harmer
-0.026
315813AE1-149 C
Solar/Wind Harmer
15.961
3151221GRAVEL6
Adder
16.378
3151171GRAVELC
Adder
3.151
316131AB2-060 GEN
Solar/Wind Harmer
2.721
316248AF1-058 C
Solar/Wind Harmer
0.755
960061AF2-297 GEN
Solar/Wind Harmer
12.532
3144216WINCHST
Adder
0.828
964241AG1-285 GEN
Solar/Wind Harmer
19.192
3150921YORKTN3
Adder
5.492
961611AG1-000B GEN
Solar/Wind Harmer
5.082
315785AD2-033 C
Solar/Wind Harmer
5.324
316283AC2-100 C
Solar/Wind Harmer
2.197
970257AG2-171 GEN
Solar/Wind Harmer
8.658
959311AF2-222 GEN
Solar/Wind Harmer
23.794
971683AH1-343 GEN
Solar/Wind Harmer
9.806
970909AG2-566 GEN
Solar/Wind Harmer
2.123
315839AE2-212 C
Solar/Wind Harmer
0.667
3144293JTRSVLE
Adder
0.598
3141843SHACKLE
Adder
0.757
3142433PROV 92
Adder
0.267
3142433PROV 92
Adder
0.267
316044AC1-158 PL1
Solar/Wind Helper
1.641
316450AC1-158 RIC
Solar/Wind Helper
0.438
3147666LOUISA
Solar/Wind Helper
0.579
316170AC1-121 GEN2
Solar/Wind Helper
0.347
LAGNLTFEXP_LAGN->PJM
CLTF
11.311
CBM South 2LTFEXP_CBM-S2->PJM
CBM
34.727
TVALTFEXP_TVA->PJM
CLTF
5.669
CPLELTFEXP_CPLE->PJM
CLTF
15.993
CBM West 2LTFEXP_CBM-W2->PJM
CBM
59.825
CBM West 1LTFEXP_CBM-W1->PJM
CBM
36.059
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.441
MECLTFEXP_MEC->PJM
CLTF
5.526
SIGELTFEXP_SIGE->PJM
CLTF
0.166
NYPJM->LTFIMP_NY
CLTF
2.883
LGEELTFEXP_LGEE->PJM
CLTF
2.019
WECLTFEXP_WEC->PJM
CLTF
1.033

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 56722_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56722_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.96 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:5002.24
MW Contribution:14.55
Bus #Bus NameTypeMW Contribution
315244AE2-183_ST
50/50
10.569
963041AG1-153 GEN
50/50
9.703
3151081ELIZAR1
50/50
30.049
3151091ELIZAR2
50/50
29.527
941591AE2-156 GEN
50/50
27.384
3152611GOSPORTB
50/50
4.154
3152621GOSPORTC
50/50
3.526
3152601GOSPORTA
50/50
3.252
972263AH1-716 GEN
50/50
176.402
315779AE2-040
50/50
4.113
941031AE2-094 GEN
Solar/Wind Harmer
80.926
944011AF1-069 GEN
Solar/Wind Harmer
25.357
970673AG2-436 GEN
Solar/Wind Harmer
88.471
970673AG2-436 GEN
Solar/Wind Harmer
44.796
971967AH1-528 GEN
Solar/Wind Harmer
76.994
970085AG2-068 GEN
Solar/Wind Harmer
24.3
970581AG2-369 GEN
Solar/Wind Harmer
20.898
957871AF2-081 GEN
Solar/Wind Harmer
17.4
319010AE1-072 C
Solar/Wind Harmer
7.017
3146406KITTY HAWK
Solar/Wind Harmer
0.029
313526AB2-022
Solar/Wind Harmer
0.925
316305AF2-043 C
Solar/Wind Harmer
1.03
316321Z2-027
Solar/Wind Harmer
0.921
3146396TANGLEW
Solar/Wind Harmer
0.628
3145176PASQUOTANK
Solar/Wind Harmer
-0.021
3146486SUNBURY
Solar/Wind Harmer
-0.034
3146486SUNBURY
Solar/Wind Harmer
-0.034
315611Z1-036_GEN2
Solar/Wind Harmer
8.233
315835AF2-110_GEN
Solar/Wind Harmer
4.151
316315AB2-025 C
Solar/Wind Harmer
0.893
315814AE2-033 C
Solar/Wind Harmer
30.736
3130156CHOWAN
Solar/Wind Harmer
-0.033
3130156CHOWAN
Solar/Wind Harmer
-0.033
315816AE2-034 GEN
Solar/Wind Harmer
2.614
3130546PLYMOUTH
Solar/Wind Harmer
-0.032
315732AD1-074 GEN1
Solar/Wind Harmer
6.414
315733AD1-074 GEN2
Solar/Wind Harmer
6.414
315735AD1-075 GEN1
Solar/Wind Harmer
3.208
3146206CASHIE
Solar/Wind Harmer
-0.031
970601AG2-382 GEN
Solar/Wind Harmer
13.738
316311AC2-079 GEN
Solar/Wind Harmer
15.73
315833AF1-017_GEN
Solar/Wind Harmer
5.916
315243AE2-183_GT3
50/50
6.113
3151051BRUNSWICKS1
50/50
9.945
3151021BRUNSWICKG1
50/50
4.792
971451AH1-221 GEN
50/50
14.554
3152331SURRY 2
50/50
13.051
3150981CHESPKA
50/50
4.073
940641AE2-051 GEN
Solar/Wind Harmer
41.064
939411AE1-173 GEN
Solar/Wind Harmer
208.234
970919AG2-571 GEN
Solar/Wind Harmer
12.367
970087AG2-069 GEN
Solar/Wind Harmer
36.449
316294AC1-161 GEN
Solar/Wind Harmer
12.074
944591AF1-124 GEN
Solar/Wind Harmer
163.155
316388AE2-253 GEN
Solar/Wind Harmer
2.349
3146456SLIGO L269
Solar/Wind Harmer
-0.035
316375AC2-012 GEN
Solar/Wind Harmer
11.954
957481AF2-042 GEN
Solar/Wind Harmer
107.108
316246AF1-032 C
Solar/Wind Harmer
0.692
3146516WINFALL
Solar/Wind Harmer
-0.109
3146516WINFALL
Solar/Wind Harmer
-0.034
315800Z1-036_GEN1
Solar/Wind Harmer
8.233
316093AE2-104_GEN
Solar/Wind Harmer
9.655
3130156CHOWAN
Solar/Wind Harmer
-0.033
316072AD1-144
Solar/Wind Harmer
0.66
3145663CRESWEL
Solar/Wind Harmer
-0.09
971163AH1-040 GEN
Solar/Wind Harmer
30.289
315693AD1-088 GEN
Solar/Wind Harmer
15.85
3146206CASHIE
Solar/Wind Harmer
-0.031
971547AH1-271 GEN
Solar/Wind Harmer
7.851
962491AG1-098 GEN
Solar/Wind Harmer
20.887
316023GEN1_S
Solar/Wind Harmer
2.098
3145893MURPHYS
Solar/Wind Harmer
-0.123
3145893MURPHYS
Solar/Wind Harmer
0.919
3146173TUNIS
Solar/Wind Harmer
-0.031
3145683EARLEYS
Solar/Wind Harmer
-0.031
3146263WOODLND
Solar/Wind Harmer
-0.03
3145963POPLR C
Solar/Wind Harmer
-0.03
316174AB2-169 GEN
Solar/Wind Harmer
4.66
960081AF2-299 GEN
Solar/Wind Harmer
3.399
3145823KELFORD
Solar/Wind Harmer
-0.03
3145336SMITFLD
Solar/Wind Harmer
-0.12
316011AB1-132 GEN
Solar/Wind Harmer
6.31
962571AG1-106 GEN
Solar/Wind Harmer
4.335
315687AD1-152 GEN
Solar/Wind Harmer
3.624
316190AA2-174 GEN
Solar/Wind Harmer
0.369
3145796HORNRTN
Solar/Wind Harmer
-0.098
3145796HORNRTN
Solar/Wind Harmer
-0.03
3145783HORNRTN
Solar/Wind Harmer
-0.03
971795AH1-408 GEN
Solar/Wind Harmer
22.032
3146293MARTNCO
Solar/Wind Harmer
0.182
316212AC1-099_GEN
Solar/Wind Harmer
2.552
3147043LAWRENC
Adder
2.334
3145746EVERETS
Solar/Wind Harmer
-0.029
3145746EVERETS
Solar/Wind Harmer
-0.029
970661AG2-428 GEN
Solar/Wind Harmer
30.611
316129AC1-054 GEN
Solar/Wind Harmer
2.516
315722AD1-056 GEN
Solar/Wind Harmer
2.994
971065AG2-659 GEN
Solar/Wind Harmer
14.295
316494AC1-189 GEN
Solar/Wind Harmer
3.06
961671AG1-007 GEN
Solar/Wind Harmer
0.355
3146083TARBORO
Solar/Wind Harmer
-0.028
3145493TOT1
Solar/Wind Harmer
0.834
3146233WITAKRS
Solar/Wind Harmer
-0.111
316381AD1-082 GEN
Solar/Wind Harmer
2.555
3138126ROCKLANDING
Solar/Wind Harmer
0.085
3145543BTLEBRO
Solar/Wind Harmer
-0.028
3145543BTLEBRO
Solar/Wind Harmer
-0.022
316359AB2-059 GEN
Solar/Wind Harmer
3.732
316049AB1-081 GEN
Solar/Wind Harmer
2.986
3142053HEARTS
Solar/Wind Harmer
0.325
970659AG2-427 GEN
Solar/Wind Harmer
14.627
3151171GRAVELC
Adder
2.595
316237AB2-079_GEN
Solar/Wind Harmer
0.792
970401AG2-262 GEN
Solar/Wind Harmer
1.694
971317AH1-138 GEN
Solar/Wind Harmer
3.236
961611AG1-000B GEN
Solar/Wind Harmer
12.645
316003AC1-222 GEN
Solar/Wind Harmer
2.377
971647AH1-324 GEN
Solar/Wind Harmer
12.098
316159AE1-175 C
Solar/Wind Harmer
0.615
970685AG2-442 GEN
Solar/Wind Harmer
19.615
3151031BRUNSWICKG2
50/50
4.792
3151101ELIZAR3
50/50
30.433
3151161SURRY 1
50/50
9.371
970917AG2-570 GEN
Solar/Wind Harmer
97.699
315773AC2-141 GEN
Solar/Wind Harmer
15.616
944581AF1-123 GEN
Solar/Wind Harmer
162.57
944601AF1-125 GEN
Solar/Wind Harmer
160.033
3146456SLIGO L269
Solar/Wind Harmer
-0.035
971153AH1-033 GEN
Solar/Wind Harmer
4.232
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316320Y1-086
Solar/Wind Harmer
2.01
316435W1029_GEN3
Solar/Wind Harmer
6.131
3146516WINFALL
Solar/Wind Harmer
-0.034
3146626S HERTFORD
Solar/Wind Harmer
-0.033
3144536CHRHLND
Solar/Wind Harmer
-0.005
3146376EDENTON
Solar/Wind Harmer
-0.033
3145273HOLLAND
Solar/Wind Harmer
-0.024
315614AA2-178 GEN
Solar/Wind Harmer
3.486
316478AD1-087 GEN
Solar/Wind Harmer
2.796
316486AD2-202 GEN
Solar/Wind Harmer
0.819
971157AH1-035 GEN
Solar/Wind Harmer
3.976
315737AD1-076 GEN
Solar/Wind Harmer
6.028
3146206CASHIE
Solar/Wind Harmer
-0.031
3156081AA2-088 GEN
Solar/Wind Harmer
10.133
316365GEN2_N
Solar/Wind Harmer
2.098
3145893MURPHYS
Solar/Wind Harmer
0.216
3145893MURPHYS
Solar/Wind Harmer
-0.031
3156021HOLLOMANSOL
Solar/Wind Harmer
4.17
957521AF2-046 GEN
Solar/Wind Harmer
24.369
961681AG1-008 GEN
Solar/Wind Harmer
24.369
3146173TUNIS
Solar/Wind Harmer
-0.031
316463AE2-346 GEN
Solar/Wind Harmer
0.498
316140AB2-099
Solar/Wind Harmer
0.207
962331AG1-082 GEN
Solar/Wind Harmer
3.846
3146263WOODLND
Solar/Wind Harmer
-0.03
3145963POPLR C
Solar/Wind Harmer
-0.03
3142666NORTHAMPTON
Solar/Wind Harmer
-0.03
966621AG1-532 GEN
Solar/Wind Harmer
0.613
316317KELFORD C
Solar/Wind Harmer
1.423
3145823KELFORD
Solar/Wind Harmer
-0.03
3145336SMITFLD
Solar/Wind Harmer
-0.012
313506AB2-031 GEN
Solar/Wind Harmer
2.416
3145796HORNRTN
Solar/Wind Harmer
-0.119
3145796HORNRTN
Solar/Wind Harmer
-0.03
3145933PARMELE
Solar/Wind Harmer
-0.029
966801AG1-551 GEN
Solar/Wind Harmer
3.667
316210AC1-098 GEN
Solar/Wind Harmer
4.594
3147043LAWRENC
Solar/Wind Harmer
-0.017
3145746EVERETS
Solar/Wind Harmer
-0.029
3145746EVERETS
Solar/Wind Harmer
-0.029
970661AG2-428 GEN
Solar/Wind Harmer
5.425
315724AD1-057 GEN
Solar/Wind Harmer
1.647
316327AA2-057 GEN
Solar/Wind Harmer
2.874
3146073TAR RVR
Solar/Wind Harmer
-0.028
3146083TARBORO
Solar/Wind Harmer
-0.028
3146233WITAKRS
Solar/Wind Harmer
0.587
3146233WITAKRS
Solar/Wind Harmer
-0.019
3138543CONSLDL
Solar/Wind Harmer
-0.018
316083AB2-161 GEN
Solar/Wind Harmer
4.522
3144216WINCHST
Adder
0.934
3150921YORKTN3
Adder
6.222
961601AG1-000A GEN
Solar/Wind Harmer
11.023
3145543BTLEBRO
Solar/Wind Harmer
-0.028
3145543BTLEBRO
Solar/Wind Harmer
-0.028
970659AG2-427 GEN
Solar/Wind Harmer
2.592
3151221GRAVEL6
Adder
17.737
3151171GRAVELC
Adder
3.413
316131AB2-060 GEN
Solar/Wind Harmer
2.806
315813AE1-149 C
Solar/Wind Harmer
16.113
316248AF1-058 C
Solar/Wind Harmer
0.777
960061AF2-297 GEN
Solar/Wind Harmer
12.888
961611AG1-000B GEN
Solar/Wind Harmer
5.395
964241AG1-285 GEN
Solar/Wind Harmer
19.739
315785AD2-033 C
Solar/Wind Harmer
5.448
316283AC2-100 C
Solar/Wind Harmer
2.259
970257AG2-171 GEN
Solar/Wind Harmer
8.842
959311AF2-222 GEN
Solar/Wind Harmer
24.263
971683AH1-343 GEN
Solar/Wind Harmer
9.965
316382AG1-145 C
Solar/Wind Harmer
0.691
970909AG2-566 GEN
Solar/Wind Harmer
2.15
3144293JTRSVLE
Adder
0.604
3141843SHACKLE
Adder
0.734
3142433PROV 92
Adder
0.238
3142433PROV 92
Adder
0.238
316044AC1-158 PL1
Solar/Wind Helper
1.398
316450AC1-158 RIC
Solar/Wind Helper
0.373
3147666LOUISA
Solar/Wind Helper
0.524
316349AD2-085 GEN
Solar/Wind Harmer
2.77
965291AG1-394 GEN
Solar/Wind Harmer
2.762
316318V4-068
Solar/Wind Harmer
0.772
3145893MURPHYS
Solar/Wind Harmer
-0.083
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145513AHOSKIE
Solar/Wind Harmer
0.268
961941AG1-037 GEN
Solar/Wind Harmer
0.231
3145513AHOSKIE
Solar/Wind Harmer
-0.031
3145683EARLEYS
Solar/Wind Harmer
-0.061
3145683EARLEYS
Solar/Wind Harmer
-0.031
3145683EARLEYS
Solar/Wind Harmer
-0.031
3146043SEABORD
Solar/Wind Harmer
-0.03
315607AA1-063A GEN
Solar/Wind Harmer
3.067
946281AF1-292 GEN
Solar/Wind Harmer
0.677
315652AC1-086 GEN
Solar/Wind Harmer
33.928
316087AB2-174 GEN
Solar/Wind Harmer
4.294
3137643SOCKMAN
Solar/Wind Harmer
-0.119
971445AH1-216 GEN
Solar/Wind Harmer
18.512
3145796HORNRTN
Solar/Wind Harmer
-0.095
3145796HORNRTN
Solar/Wind Harmer
-0.012
3146033SCOT NK
Solar/Wind Harmer
-0.118
316005AA1-067
Solar/Wind Harmer
0.583
3145746EVERETS
Solar/Wind Harmer
-0.114
3145746EVERETS
Solar/Wind Harmer
-0.029
3145746EVERETS
Solar/Wind Harmer
-0.029
3145746EVERETS
Solar/Wind Harmer
-0.029
970181AG2-120 GEN
Solar/Wind Harmer
3.785
970831AG2-522 GEN
Solar/Wind Harmer
14.404
957861AF2-080 GEN
Solar/Wind Harmer
12.444
316420AA1-050 GEN
Solar/Wind Harmer
3.227
3145573BETHELC
Solar/Wind Harmer
-0.028
3145573BETHELC
Solar/Wind Harmer
-0.028
316319Z2-044 C
Solar/Wind Harmer
1.551
972265AH1-717 GEN
Adder
18.943
3151201GRAVEL4
Adder
17.758
3151191GRAVEL3
Adder
17.533
3151211GRAVEL5
Adder
17.533
3143316POE
Solar/Wind Harmer
-0.106
316239AB2-077_GEN
Solar/Wind Harmer
0.792
316238AB2-078_GEN
Solar/Wind Harmer
0.792
316118AC1-105 GEN
Solar/Wind Harmer
1.779
3147173SINAI
Solar/Wind Harmer
-0.026
3147243WELCO
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
4.662
3144303KENBRDG
Solar/Wind Harmer
-0.019
316369SG1_INVT
Solar/Wind Harmer
4.072
957831AF2-077 GEN
Solar/Wind Harmer
0.682
3138283WHITEMARSH
Solar/Wind Harmer
0.035
3142433PROV 92
Adder
0.238
3142433PROV 92
Adder
0.238
970683AG2-441 GEN
Solar/Wind Harmer
1.465
970681AG2-440 GEN
Solar/Wind Harmer
1.172
3144293JTRSVLE
Adder
0.604
3141843SHACKLE
Adder
0.734
3142433PROV 92
Adder
0.238
3142433PROV 92
Adder
0.238
3143226MDLTHAN
Solar/Wind Helper
0.265
316045AC1-158 PL2
Solar/Wind Helper
4.474
3147666LOUISA
Solar/Wind Helper
0.911
316192AB2-158 GEN
Solar/Wind Helper
1.512
970533AG2-339 GEN
50/50
34.146
970531AG2-338 GEN
50/50
13.658
315242AE2-183_GT2
50/50
6.113
315241AE2-183_GT1
50/50
6.075
972185AH1-677 GEN
50/50
22.038
3151041BRUNSWICKG3
50/50
4.792
972187AH1-678 GEN
50/50
10.997
3150991CHESPKB
50/50
3.417
3150991CHESPKB
50/50
3.335
970933AG2-581 GEN
Solar/Wind Harmer
36.6
316185AD1-033 GEN
Solar/Wind Harmer
3.695
3145506HICKORY
Solar/Wind Harmer
-0.139
3145506HICKORY
Solar/Wind Harmer
-0.084
3145506HICKORY
Solar/Wind Harmer
-0.021
316339AD2-160 GEN
Solar/Wind Harmer
2.349
3142956BIRDNECK
Solar/Wind Harmer
1.868
316018AA1-139 ULT2
Solar/Wind Harmer
2.981
316017AA1-139 ULT1
Solar/Wind Harmer
2.816
316316AC1-027 C
Solar/Wind Harmer
1.067
3137176SLIGO L2192
Solar/Wind Harmer
-0.137
3146456SLIGO L269
Solar/Wind Harmer
4.1
3130086AYDLETT
Solar/Wind Harmer
-0.138
316036AC1-147 C
Solar/Wind Harmer
0.932
3146386ELIZ CT
Solar/Wind Harmer
-0.034
970099AG2-077 GEN
Solar/Wind Harmer
42.843
316431W1029_GEN1
Solar/Wind Harmer
6.131
316433W1029_GEN2
Solar/Wind Harmer
6.131
3146516WINFALL
Solar/Wind Harmer
-0.034
3146516WINFALL
Solar/Wind Harmer
-0.034
3146516WINFALL
Solar/Wind Harmer
-0.034
3146626S HERTFORD
Solar/Wind Harmer
-0.033
3146626S HERTFORD
Solar/Wind Harmer
-0.033
3144356SAPONY
Solar/Wind Harmer
1.155
3146376EDENTON
Solar/Wind Harmer
0.978
3146376EDENTON
Solar/Wind Harmer
0.978
315742AE1-103 GEN
Solar/Wind Harmer
3.377
316065AD1-022 GEN
Solar/Wind Harmer
15.758
3145893MURPHYS
Solar/Wind Harmer
0.864
3145893MURPHYS
Solar/Wind Harmer
-0.056
3146173TUNIS
Solar/Wind Harmer
-0.031
3146173TUNIS
Solar/Wind Harmer
-0.031
3142666NORTHAMPTON
Solar/Wind Harmer
-0.03
3142666NORTHAMPTON
Solar/Wind Harmer
-0.03
3142666NORTHAMPTON
Solar/Wind Harmer
-0.03
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
316236AE1-162_GEN
Solar/Wind Harmer
0.909
316181AB2-040 GEN
Solar/Wind Harmer
4.192
316426AA2-053 GEN
Solar/Wind Harmer
3.033
3145593CAROLNA
Solar/Wind Harmer
-0.03
3145593CAROLNA
Solar/Wind Harmer
-0.03
966811AG1-552 GEN
Solar/Wind Harmer
3.361
3145593CAROLNA
Solar/Wind Harmer
0.248
3145796HORNRTN
Solar/Wind Harmer
-0.089
3145783HORNRTN
Solar/Wind Harmer
3.53
3145783HORNRTN
Solar/Wind Harmer
2.824
3145783HORNRTN
Solar/Wind Harmer
0.882
3145783HORNRTN
Solar/Wind Harmer
0.353
3145933PARMELE
Solar/Wind Harmer
-0.058
3145933PARMELE
Solar/Wind Harmer
-0.029
316274AC1-208 GEN
Solar/Wind Harmer
3.137
970657AG2-426 GEN
Solar/Wind Harmer
8.819
970657AG2-426 GEN
Solar/Wind Harmer
1.844
3145493TOT1
Solar/Wind Harmer
0.435
3145453TOT5
Solar/Wind Harmer
0.261
3145603CNETO
Solar/Wind Harmer
0.174
939181AE1-148 GEN
Solar/Wind Harmer
15.597
961601AG1-000A GEN
Solar/Wind Harmer
10.885
316263AC1-034 GEN
Solar/Wind Harmer
12.975
313527AB2-043 GEN
Solar/Wind Harmer
4.255
962561AG1-105 GEN
Solar/Wind Harmer
14.617
964791AG1-342 GEN
Solar/Wind Harmer
5.543
3146843MT LREL
Solar/Wind Harmer
-0.026
3146843MT LREL
Solar/Wind Harmer
-0.026
971741AH1-377 GEN
Solar/Wind Harmer
28.741
316222AC1-221 GEN
Solar/Wind Harmer
2.439
970323AG2-213 GEN
Solar/Wind Harmer
11.79
971775AH1-396 GEN
Solar/Wind Harmer
1.679
316034AC1-036 C
Solar/Wind Harmer
0.437
316033AB2-134 GEN
Solar/Wind Harmer
7.35
315697AD1-025 GEN
Solar/Wind Harmer
4.61
970301AG2-198 GEN
Solar/Wind Harmer
11.323
3144293JTRSVLE
Adder
0.604
3144293JTRSVLE
Adder
0.509
944641AF1-129 GEN
Adder
67.1
316447AC1-158 HLD
Solar/Wind Helper
3.076
LAGNLTFEXP_LAGN->PJM
CLTF
10.628
CBM South 2LTFEXP_CBM-S2->PJM
CBM
34.911
TVALTFEXP_TVA->PJM
CLTF
5.301
CPLELTFEXP_CPLE->PJM
CLTF
16.426
CBM West 2LTFEXP_CBM-W2->PJM
CBM
54.71
CBM West 1LTFEXP_CBM-W1->PJM
CBM
30.133
CBM South 1LTFEXP_CBM-S1->PJM
CBM
17.997
MECLTFEXP_MEC->PJM
CLTF
4.839
SIGELTFEXP_SIGE->PJM
CLTF
0.143
NYPJM->LTFIMP_NY
CLTF
2.585
LGEELTFEXP_LGEE->PJM
CLTF
1.702
WECLTFEXP_WEC->PJM
CLTF
0.872

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: BREMO B1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:108.3 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4267.15
MW Contribution:12.85
Bus #Bus NameTypeMW Contribution
970533AG2-339 GEN
50/50
29.851
970531AG2-338 GEN
50/50
11.94
315242AE2-183_GT2
50/50
5.38
315241AE2-183_GT1
50/50
5.347
972185AH1-677 GEN
50/50
19.395
3151041BRUNSWICKG3
50/50
4.23
972187AH1-678 GEN
50/50
9.708
3144293JTRSVLE
50/50
0.895
3144293JTRSVLE
50/50
0.754
970535AG2-341 GEN
50/50
4.4
3152661PLYWOOD A
50/50
0.514
3151361ROSEMG1
50/50
0.809
3151371ROSEMS1
50/50
0.501
3151381ROSEMG2
50/50
0.379
970933AG2-581 GEN
Solar/Wind Harmer
33.334
970099AG2-077 GEN
Solar/Wind Harmer
41.293
971741AH1-377 GEN
Solar/Wind Harmer
37.414
970301AG2-198 GEN
Solar/Wind Harmer
16.032
3146776BUCKING
Solar/Wind Harmer
-0.126
3146776BUCKING
Solar/Wind Harmer
-0.01
3147133PAMPLIN
Solar/Wind Harmer
-0.03
3147133PAMPLIN
Solar/Wind Harmer
-0.024
958211AF2-115 GEN
Solar/Wind Harmer
4.654
963191AG1-168 GEN
Solar/Wind Harmer
2.792
316034AC1-036 C
Solar/Wind Harmer
0.538
970323AG2-213 GEN
Solar/Wind Harmer
14.493
971775AH1-396 GEN
Solar/Wind Harmer
2.064
313527AB2-043 GEN
Solar/Wind Harmer
4.56
3144356SAPONY
Solar/Wind Harmer
0.979
939181AE1-148 GEN
Solar/Wind Harmer
15.561
962561AG1-105 GEN
Solar/Wind Harmer
15.007
964791AG1-342 GEN
Solar/Wind Harmer
5.646
3146843MT LREL
Solar/Wind Harmer
-0.026
3146843MT LREL
Solar/Wind Harmer
-0.026
316181AB2-040 GEN
Solar/Wind Harmer
3.656
3145593CAROLNA
Solar/Wind Harmer
-0.026
3145593CAROLNA
Solar/Wind Harmer
-0.026
966811AG1-552 GEN
Solar/Wind Harmer
2.899
3145593CAROLNA
Solar/Wind Harmer
0.214
316426AA2-053 GEN
Solar/Wind Harmer
2.588
3145783HORNRTN
Solar/Wind Harmer
3.04
3145783HORNRTN
Solar/Wind Harmer
2.432
3145783HORNRTN
Solar/Wind Harmer
0.76
3145783HORNRTN
Solar/Wind Harmer
0.304
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.015
3145506HICKORY
Solar/Wind Harmer
-0.101
3145506HICKORY
Solar/Wind Harmer
-0.061
3145506HICKORY
Solar/Wind Harmer
-0.015
316185AD1-033 GEN
Solar/Wind Harmer
2.674
316339AD2-160 GEN
Solar/Wind Harmer
1.708
315244AE2-183_ST
50/50
9.302
963041AG1-153 GEN
50/50
8.566
3151541CLOVER2
50/50
5.976
315779AE2-040
50/50
3.486
3151611KERR 4
50/50
0.508
3151621KERR 5
50/50
0.508
3151631KERR 6
50/50
0.508
3151641KERR 7
50/50
0.508
3151281ROARAP4
50/50
0.278
3151281ROARAP4
50/50
0.26
941031AE2-094 GEN
Solar/Wind Harmer
70.747
944011AF1-069 GEN
Solar/Wind Harmer
22.167
970673AG2-436 GEN
Solar/Wind Harmer
77.682
970673AG2-436 GEN
Solar/Wind Harmer
39.333
971967AH1-528 GEN
Solar/Wind Harmer
68.625
970085AG2-068 GEN
Solar/Wind Harmer
21.474
970581AG2-369 GEN
Solar/Wind Harmer
18.468
970285AG2-188 GEN
Solar/Wind Harmer
27.712
971845AH1-439 GEN
Solar/Wind Harmer
16.825
315657AE1-056 GEN
Solar/Wind Harmer
11.27
946301AF1-294 GEN
Solar/Wind Harmer
7.632
961791AG1-021 GEN
Solar/Wind Harmer
3.723
970683AG2-441 GEN
Solar/Wind Harmer
22.967
970681AG2-440 GEN
Solar/Wind Harmer
18.373
3144303KENBRDG
Solar/Wind Harmer
-0.023
971443AH1-215 GEN
Solar/Wind Harmer
5.7
316315AB2-025 C
Solar/Wind Harmer
0.757
315814AE2-033 C
Solar/Wind Harmer
26.059
316239AB2-077_GEN
Solar/Wind Harmer
0.842
316238AB2-078_GEN
Solar/Wind Harmer
0.842
970831AG2-522 GEN
Solar/Wind Harmer
13.417
946281AF1-292 GEN
Solar/Wind Harmer
0.596
316087AB2-174 GEN
Solar/Wind Harmer
3.756
3137643SOCKMAN
Solar/Wind Harmer
-0.103
316118AC1-105 GEN
Solar/Wind Harmer
1.777
315607AA1-063A GEN
Solar/Wind Harmer
2.581
3146043SEABORD
Solar/Wind Harmer
-0.025
315652AC1-086 GEN
Solar/Wind Harmer
28.68
957871AF2-081 GEN
Solar/Wind Harmer
12.659
319010AE1-072 C
Solar/Wind Harmer
5.115
3146406KITTY HAWK
Solar/Wind Harmer
0.021
3147173SINAI
Solar/Wind Harmer
-0.025
3147243WELCO
Solar/Wind Harmer
-0.016
3145796HORNRTN
Solar/Wind Harmer
-0.08
3145796HORNRTN
Solar/Wind Harmer
-0.01
965291AG1-394 GEN
Solar/Wind Harmer
2.237
313526AB2-022
Solar/Wind Harmer
0.68
316321Z2-027
Solar/Wind Harmer
0.679
3146396TANGLEW
Solar/Wind Harmer
0.463
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
316318V4-068
Solar/Wind Harmer
0.626
3145893MURPHYS
Solar/Wind Harmer
-0.067
3145893MURPHYS
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
316305AF2-043 C
Solar/Wind Harmer
0.755
3151081ELIZAR1
Adder
20.42
3151091ELIZAR2
Adder
20.065
315611Z1-036_GEN2
Solar/Wind Harmer
6.178
3145513AHOSKIE
Solar/Wind Harmer
0.218
961941AG1-037 GEN
Solar/Wind Harmer
0.188
3145513AHOSKIE
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
3152611GOSPORTB
Adder
2.824
3152621GOSPORTC
Adder
2.396
3152601GOSPORTA
Adder
2.211
3145683EARLEYS
Solar/Wind Harmer
-0.049
3145683EARLEYS
Solar/Wind Harmer
-0.025
3145683EARLEYS
Solar/Wind Harmer
-0.025
315816AE2-034 GEN
Solar/Wind Harmer
2.011
3130546PLYMOUTH
Solar/Wind Harmer
-0.025
3146206CASHIE
Solar/Wind Harmer
-0.025
970601AG2-382 GEN
Solar/Wind Harmer
10.834
3146033SCOT NK
Solar/Wind Harmer
-0.099
315732AD1-074 GEN1
Solar/Wind Harmer
5.007
315733AD1-074 GEN2
Solar/Wind Harmer
5.007
315735AD1-075 GEN1
Solar/Wind Harmer
2.504
315835AF2-110_GEN
Solar/Wind Harmer
3.076
316319Z2-044 C
Solar/Wind Harmer
1.327
316005AA1-067
Solar/Wind Harmer
0.482
3145746EVERETS
Solar/Wind Harmer
-0.094
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
316018AA1-139 ULT2
Solar/Wind Harmer
2.169
316017AA1-139 ULT1
Solar/Wind Harmer
2.049
3137176SLIGO L2192
Solar/Wind Harmer
-0.1
3146456SLIGO L269
Solar/Wind Harmer
2.987
3130086AYDLETT
Solar/Wind Harmer
-0.101
3145796HORNRTN
Solar/Wind Harmer
-0.075
3146386ELIZ CT
Solar/Wind Harmer
-0.025
3142956BIRDNECK
Solar/Wind Harmer
1.35
316316AC1-027 C
Solar/Wind Harmer
0.771
3145893MURPHYS
Solar/Wind Harmer
0.7
3145893MURPHYS
Solar/Wind Harmer
-0.045
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
316431W1029_GEN1
Solar/Wind Harmer
4.542
316433W1029_GEN2
Solar/Wind Harmer
4.542
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.025
3146376EDENTON
Solar/Wind Harmer
0.74
3146376EDENTON
Solar/Wind Harmer
0.74
316036AC1-147 C
Solar/Wind Harmer
0.672
3150991CHESPKB
Adder
2.322
3150991CHESPKB
Adder
2.267
315742AE1-103 GEN
Solar/Wind Harmer
2.599
316274AC1-208 GEN
Solar/Wind Harmer
2.674
316065AD1-022 GEN
Solar/Wind Harmer
12.38
3145933PARMELE
Solar/Wind Harmer
-0.048
3145933PARMELE
Solar/Wind Harmer
-0.024
3145493TOT1
Solar/Wind Harmer
0.368
3145453TOT5
Solar/Wind Harmer
0.221
3145603CNETO
Solar/Wind Harmer
0.147
316263AC1-034 GEN
Solar/Wind Harmer
11.133
961601AG1-000A GEN
Solar/Wind Harmer
9.326
316222AC1-221 GEN
Solar/Wind Harmer
2.263
316447AC1-158 HLD
Solar/Wind Helper
2.916
3143526WINTERP
Solar/Wind Helper
1.191
3151031BRUNSWICKG2
50/50
4.23
970413AG2-270 GEN
50/50
26.203
3144293JTRSVLE
50/50
0.895
3151591KERR 2
50/50
0.508
3151261ROARAP2
50/50
0.279
3151391GASTONA
50/50
0.614
3151411GASTONB
50/50
0.614
970917AG2-570 GEN
Solar/Wind Harmer
86.33
970909AG2-566 GEN
Solar/Wind Harmer
3.044
3146926FARMVIL
Solar/Wind Harmer
-0.019
3146776BUCKING
Solar/Wind Harmer
-0.011
316478AD1-087 GEN
Solar/Wind Harmer
2.727
316486AD2-202 GEN
Solar/Wind Harmer
0.799
942461AE2-259 GEN
Solar/Wind Harmer
4.631
3147133PAMPLIN
Solar/Wind Harmer
-0.094
971193AH1-056 GEN
Solar/Wind Harmer
18.784
963181AG1-167 GEN
Solar/Wind Harmer
2.792
959311AF2-222 GEN
Solar/Wind Harmer
30.378
970257AG2-171 GEN
Solar/Wind Harmer
10.87
315785AD2-033 C
Solar/Wind Harmer
6.532
964241AG1-285 GEN
Solar/Wind Harmer
22.181
316131AB2-060 GEN
Solar/Wind Harmer
3.035
3147043LAWRENC
Solar/Wind Harmer
-0.016
966621AG1-532 GEN
Solar/Wind Harmer
0.54
316365GEN2_N
Solar/Wind Harmer
1.787
313506AB2-031 GEN
Solar/Wind Harmer
2.107
315773AC2-141 GEN
Solar/Wind Harmer
10.925
944581AF1-123 GEN
Solar/Wind Harmer
117.317
944601AF1-125 GEN
Solar/Wind Harmer
115.486
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3146456SLIGO L269
Solar/Wind Harmer
-0.025
971153AH1-033 GEN
Solar/Wind Harmer
3.083
316248AF1-058 C
Solar/Wind Harmer
0.761
960061AF2-297 GEN
Solar/Wind Harmer
12.626
3145796HORNRTN
Solar/Wind Harmer
-0.1
3145796HORNRTN
Solar/Wind Harmer
-0.025
316320Y1-086
Solar/Wind Harmer
1.477
3156081AA2-088 GEN
Solar/Wind Harmer
8.171
3146263WOODLND
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
0.175
3145893MURPHYS
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
957521AF2-046 GEN
Solar/Wind Harmer
19.748
961681AG1-008 GEN
Solar/Wind Harmer
19.748
316435W1029_GEN3
Solar/Wind Harmer
4.542
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3151101ELIZAR3
Adder
20.681
3146173TUNIS
Solar/Wind Harmer
-0.025
316463AE2-346 GEN
Solar/Wind Harmer
0.404
316140AB2-099
Solar/Wind Harmer
0.168
962331AG1-082 GEN
Solar/Wind Harmer
3.119
3146376EDENTON
Solar/Wind Harmer
-0.025
3144873MCLAUGH
Solar/Wind Harmer
-0.001
315614AA2-178 GEN
Solar/Wind Harmer
2.681
316317KELFORD C
Solar/Wind Harmer
1.17
3145823KELFORD
Solar/Wind Harmer
-0.025
3145273HOLLAND
Solar/Wind Harmer
-0.019
3156021HOLLOMANSOL
Solar/Wind Harmer
3.338
971157AH1-035 GEN
Solar/Wind Harmer
3.096
3146206CASHIE
Solar/Wind Harmer
-0.025
315737AD1-076 GEN
Solar/Wind Harmer
4.705
316210AC1-098 GEN
Solar/Wind Harmer
3.877
315724AD1-057 GEN
Solar/Wind Harmer
1.404
3145963POPLR C
Solar/Wind Harmer
-0.024
316327AA2-057 GEN
Solar/Wind Harmer
2.454
3146233WITAKRS
Solar/Wind Harmer
0.503
3146233WITAKRS
Solar/Wind Harmer
-0.016
3145933PARMELE
Solar/Wind Harmer
-0.024
966801AG1-551 GEN
Solar/Wind Harmer
2.999
3138543CONSLDL
Solar/Wind Harmer
-0.016
3144536CHRHLND
Solar/Wind Harmer
-0.004
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
3146073TAR RVR
Solar/Wind Harmer
-0.024
3146083TARBORO
Solar/Wind Harmer
-0.024
3145543BTLEBRO
Solar/Wind Harmer
-0.024
3145543BTLEBRO
Solar/Wind Harmer
-0.024
961601AG1-000A GEN
Solar/Wind Harmer
9.444
971683AH1-343 GEN
Solar/Wind Harmer
9.745
316283AC2-100 C
Solar/Wind Harmer
2.093
3151221GRAVEL6
Adder
12.505
3151171GRAVELC
Adder
2.406
3144216WINCHST
Adder
0.613
3150921YORKTN3
Adder
4.045
316313AB2-026
Solar/Wind Helper
0.532
316258AE1-075 C
Solar/Wind Helper
0.479
316405AF2-144 C
Solar/Wind Helper
0.399
316044AC1-158 PL1
Solar/Wind Helper
1.325
316450AC1-158 RIC
Solar/Wind Helper
0.353
970661AG2-428 GEN
Solar/Wind Harmer
1.85
315243AE2-183_GT3
50/50
5.38
3151051BRUNSWICKS1
50/50
8.78
3151021BRUNSWICKG1
50/50
4.23
971451AH1-221 GEN
50/50
12.849
3151531CLOVER1
50/50
6.004
3144293JTRSVLE
50/50
0.895
3151601KERR 3
50/50
0.508
3151581KERR 1
50/50
0.181
3147043LAWRENC
50/50
2.311
3151261ROARAP2
50/50
0.286
3151391GASTONA
50/50
0.614
3151411GASTONB
50/50
0.614
940641AE2-051 GEN
Solar/Wind Harmer
34.524
970919AG2-571 GEN
Solar/Wind Harmer
10.928
970087AG2-069 GEN
Solar/Wind Harmer
32.211
939411AE1-173 GEN
Solar/Wind Harmer
169.915
957481AF2-042 GEN
Solar/Wind Harmer
103.233
315693AD1-088 GEN
Solar/Wind Harmer
16.294
962491AG1-098 GEN
Solar/Wind Harmer
21.776
3146926FARMVIL
Solar/Wind Harmer
-0.019
316322AB2-045
Solar/Wind Harmer
1.065
3146776BUCKING
Solar/Wind Harmer
-0.013
972003AH1-546 GEN
Solar/Wind Harmer
15.792
963171AG1-166 GEN
Solar/Wind Harmer
3.723
971563AH1-280 GEN
Solar/Wind Harmer
3.723
970685AG2-442 GEN
Solar/Wind Harmer
25.722
315687AD1-152 GEN
Solar/Wind Harmer
3.514
316237AB2-079_GEN
Solar/Wind Harmer
0.842
971065AG2-659 GEN
Solar/Wind Harmer
13.526
316129AC1-054 GEN
Solar/Wind Harmer
2.362
971795AH1-408 GEN
Solar/Wind Harmer
20.182
960081AF2-299 GEN
Solar/Wind Harmer
2.993
316023GEN1_S
Solar/Wind Harmer
1.787
970401AG2-262 GEN
Solar/Wind Harmer
1.725
316294AC1-161 GEN
Solar/Wind Harmer
8.447
944591AF1-124 GEN
Solar/Wind Harmer
117.74
316190AA2-174 GEN
Solar/Wind Harmer
0.315
3145783HORNRTN
Solar/Wind Harmer
-0.026
316011AB1-132 GEN
Solar/Wind Harmer
5.334
962571AG1-106 GEN
Solar/Wind Harmer
3.665
316388AE2-253 GEN
Solar/Wind Harmer
1.708
3146456SLIGO L269
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.083
3145796HORNRTN
Solar/Wind Harmer
-0.025
3146263WOODLND
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
-0.1
3145893MURPHYS
Solar/Wind Harmer
0.745
3146516WINFALL
Solar/Wind Harmer
-0.081
3146516WINFALL
Solar/Wind Harmer
-0.025
316246AF1-032 C
Solar/Wind Harmer
0.507
3146173TUNIS
Solar/Wind Harmer
-0.025
315800Z1-036_GEN1
Solar/Wind Harmer
6.178
3130156CHOWAN
Solar/Wind Harmer
-0.025
316375AC2-012 GEN
Solar/Wind Harmer
8.621
3150981CHESPKA
Adder
2.768
3145683EARLEYS
Solar/Wind Harmer
-0.025
3145663CRESWEL
Solar/Wind Harmer
-0.069
971163AH1-040 GEN
Solar/Wind Harmer
23.294
3145823KELFORD
Solar/Wind Harmer
-0.025
3146206CASHIE
Solar/Wind Harmer
-0.025
971547AH1-271 GEN
Solar/Wind Harmer
6.191
316212AC1-099_GEN
Solar/Wind Harmer
2.154
316093AE2-104_GEN
Solar/Wind Harmer
7.155
315722AD1-056 GEN
Solar/Wind Harmer
2.553
3145963POPLR C
Solar/Wind Harmer
-0.024
316174AB2-169 GEN
Solar/Wind Harmer
3.744
3146233WITAKRS
Solar/Wind Harmer
-0.095
3146293MARTNCO
Solar/Wind Harmer
0.149
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
316003AC1-222 GEN
Solar/Wind Harmer
2.327
316494AC1-189 GEN
Solar/Wind Harmer
2.561
961671AG1-007 GEN
Solar/Wind Harmer
0.3
3146083TARBORO
Solar/Wind Harmer
-0.024
3145493TOT1
Solar/Wind Harmer
0.705
3145543BTLEBRO
Solar/Wind Harmer
-0.024
3145543BTLEBRO
Solar/Wind Harmer
-0.019
316359AB2-059 GEN
Solar/Wind Harmer
3.202
316049AB1-081 GEN
Solar/Wind Harmer
2.562
3142053HEARTS
Solar/Wind Harmer
0.279
316072AD1-144
Solar/Wind Harmer
0.477
3151171GRAVELC
Adder
1.83
3143226MDLTHAN
Solar/Wind Helper
0.35
316336AC2-165 C
Solar/Wind Helper
1.883
316045AC1-158 PL2
Solar/Wind Helper
4.241
3143526WINTERP
Solar/Wind Helper
1.191
970661AG2-428 GEN
Solar/Wind Harmer
10.44
970181AG2-120 GEN
Solar/Wind Harmer
3.13
957861AF2-080 GEN
Solar/Wind Harmer
10.414
316420AA1-050 GEN
Solar/Wind Harmer
2.716
3145573BETHELC
Solar/Wind Harmer
-0.024
3145573BETHELC
Solar/Wind Harmer
-0.024
316311AC2-079 GEN
Solar/Wind Harmer
11.791
315833AF1-017_GEN
Solar/Wind Harmer
4.435
316349AD2-085 GEN
Solar/Wind Harmer
2.077
3143316POE
Solar/Wind Harmer
-0.087
972265AH1-717 GEN
Adder
13.355
3151201GRAVEL4
Adder
12.519
3151191GRAVEL3
Adder
12.361
3151211GRAVEL5
Adder
12.361
316233AE1-074 FULL
Solar/Wind Helper
0.35
LAGNLTFEXP_LAGN->PJM
CLTF
9.794
CBM South 2LTFEXP_CBM-S2->PJM
CBM
31.485
TVALTFEXP_TVA->PJM
CLTF
4.889
CPLELTFEXP_CPLE->PJM
CLTF
14.708
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.937
CBM West 1LTFEXP_CBM-W1->PJM
CBM
29.197
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.662
MECLTFEXP_MEC->PJM
CLTF
4.586
SIGELTFEXP_SIGE->PJM
CLTF
0.137
NYPJM->LTFIMP_NY
CLTF
2.27
LGEELTFEXP_LGEE->PJM
CLTF
1.633
WECLTFEXP_WEC->PJM
CLTF
0.839

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2003-205_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2003-205_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:107.33 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4228.67
MW Contribution:13.21
Bus #Bus NameTypeMW Contribution
970533AG2-339 GEN
50/50
31.019
970531AG2-338 GEN
50/50
12.408
315242AE2-183_GT2
50/50
5.551
315241AE2-183_GT1
50/50
5.517
972185AH1-677 GEN
50/50
20.012
3151041BRUNSWICKG3
50/50
4.351
972187AH1-678 GEN
50/50
9.984
3151361ROSEMG1
50/50
0.866
3151371ROSEMS1
50/50
0.536
3151381ROSEMG2
50/50
0.405
970933AG2-581 GEN
Solar/Wind Harmer
33.195
3144356SAPONY
Solar/Wind Harmer
1.182
970099AG2-077 GEN
Solar/Wind Harmer
38.77
316181AB2-040 GEN
Solar/Wind Harmer
3.83
3142666NORTHAMPTON
Solar/Wind Harmer
-0.027
3142666NORTHAMPTON
Solar/Wind Harmer
-0.027
3142666NORTHAMPTON
Solar/Wind Harmer
-0.027
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3145796HORNRTN
Solar/Wind Harmer
-0.081
3145593CAROLNA
Solar/Wind Harmer
-0.026
3145593CAROLNA
Solar/Wind Harmer
-0.026
966811AG1-552 GEN
Solar/Wind Harmer
2.991
3145593CAROLNA
Solar/Wind Harmer
0.221
316426AA2-053 GEN
Solar/Wind Harmer
2.671
3145783HORNRTN
Solar/Wind Harmer
3.137
3145783HORNRTN
Solar/Wind Harmer
2.509
3145783HORNRTN
Solar/Wind Harmer
0.784
3145783HORNRTN
Solar/Wind Harmer
0.314
3145893MURPHYS
Solar/Wind Harmer
0.723
3145893MURPHYS
Solar/Wind Harmer
-0.047
3146173TUNIS
Solar/Wind Harmer
-0.026
3146173TUNIS
Solar/Wind Harmer
-0.026
3145506HICKORY
Solar/Wind Harmer
-0.102
3145506HICKORY
Solar/Wind Harmer
-0.061
3151031BRUNSWICKG2
50/50
4.351
970413AG2-270 GEN
50/50
24.296
3151391GASTONA
50/50
0.66
3151411GASTONB
50/50
0.66
3151261ROARAP2
50/50
0.288
3151591KERR 2
50/50
0.465
970917AG2-570 GEN
Solar/Wind Harmer
88.674
316365GEN2_N
Solar/Wind Harmer
1.997
316478AD1-087 GEN
Solar/Wind Harmer
2.529
316486AD2-202 GEN
Solar/Wind Harmer
0.741
966621AG1-532 GEN
Solar/Wind Harmer
0.573
313506AB2-031 GEN
Solar/Wind Harmer
2.207
3142666NORTHAMPTON
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.107
3145796HORNRTN
Solar/Wind Harmer
-0.027
3147043LAWRENC
Solar/Wind Harmer
-0.016
315773AC2-141 GEN
Solar/Wind Harmer
11.18
944581AF1-123 GEN
Solar/Wind Harmer
119.255
944601AF1-125 GEN
Solar/Wind Harmer
117.394
3146263WOODLND
Solar/Wind Harmer
-0.026
3156081AA2-088 GEN
Solar/Wind Harmer
8.422
3145893MURPHYS
Solar/Wind Harmer
0.181
3145893MURPHYS
Solar/Wind Harmer
-0.026
957521AF2-046 GEN
Solar/Wind Harmer
20.404
961681AG1-008 GEN
Solar/Wind Harmer
20.404
3146173TUNIS
Solar/Wind Harmer
-0.026
316463AE2-346 GEN
Solar/Wind Harmer
0.418
316140AB2-099
Solar/Wind Harmer
0.174
962331AG1-082 GEN
Solar/Wind Harmer
3.23
316317KELFORD C
Solar/Wind Harmer
1.212
3145823KELFORD
Solar/Wind Harmer
-0.026
3156021HOLLOMANSOL
Solar/Wind Harmer
3.465
315724AD1-057 GEN
Solar/Wind Harmer
1.479
3146456SLIGO L269
Solar/Wind Harmer
-0.026
971153AH1-033 GEN
Solar/Wind Harmer
3.13
316320Y1-086
Solar/Wind Harmer
1.502
3146206CASHIE
Solar/Wind Harmer
-0.026
316210AC1-098 GEN
Solar/Wind Harmer
4.012
3146516WINFALL
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
316435W1029_GEN3
Solar/Wind Harmer
4.628
3146376EDENTON
Solar/Wind Harmer
-0.025
315614AA2-178 GEN
Solar/Wind Harmer
2.753
971157AH1-035 GEN
Solar/Wind Harmer
3.188
315737AD1-076 GEN
Solar/Wind Harmer
4.848
3145273HOLLAND
Solar/Wind Harmer
-0.019
3151101ELIZAR3
Adder
20.863
316327AA2-057 GEN
Solar/Wind Harmer
2.54
3145963POPLR C
Solar/Wind Harmer
-0.025
315243AE2-183_GT3
50/50
5.551
3151051BRUNSWICKS1
50/50
9.029
3151021BRUNSWICKG1
50/50
4.351
971451AH1-221 GEN
50/50
13.214
3151531CLOVER1
50/50
5.567
3151391GASTONA
50/50
0.66
3151411GASTONB
50/50
0.66
3147043LAWRENC
50/50
2.293
3151261ROARAP2
50/50
0.295
3151601KERR 3
50/50
0.465
3151581KERR 1
50/50
0.166
940641AE2-051 GEN
Solar/Wind Harmer
36.076
970919AG2-571 GEN
Solar/Wind Harmer
11.225
939411AE1-173 GEN
Solar/Wind Harmer
176.638
970087AG2-069 GEN
Solar/Wind Harmer
33.081
957481AF2-042 GEN
Solar/Wind Harmer
96.924
316023GEN1_S
Solar/Wind Harmer
1.997
315693AD1-088 GEN
Solar/Wind Harmer
14.305
960081AF2-299 GEN
Solar/Wind Harmer
3.176
962491AG1-098 GEN
Solar/Wind Harmer
18.84
316011AB1-132 GEN
Solar/Wind Harmer
5.734
962571AG1-106 GEN
Solar/Wind Harmer
3.94
971795AH1-408 GEN
Solar/Wind Harmer
20.458
315687AD1-152 GEN
Solar/Wind Harmer
3.278
3145796HORNRTN
Solar/Wind Harmer
-0.089
3145796HORNRTN
Solar/Wind Harmer
-0.027
316294AC1-161 GEN
Solar/Wind Harmer
8.644
316190AA2-174 GEN
Solar/Wind Harmer
0.325
3145783HORNRTN
Solar/Wind Harmer
-0.026
944591AF1-124 GEN
Solar/Wind Harmer
119.684
3146263WOODLND
Solar/Wind Harmer
-0.026
3145893MURPHYS
Solar/Wind Harmer
-0.103
3145893MURPHYS
Solar/Wind Harmer
0.769
3146173TUNIS
Solar/Wind Harmer
-0.026
3145683EARLEYS
Solar/Wind Harmer
-0.026
316129AC1-054 GEN
Solar/Wind Harmer
2.255
3145823KELFORD
Solar/Wind Harmer
-0.026
315722AD1-056 GEN
Solar/Wind Harmer
2.689
316388AE2-253 GEN
Solar/Wind Harmer
1.733
3146456SLIGO L269
Solar/Wind Harmer
-0.026
971065AG2-659 GEN
Solar/Wind Harmer
12.825
3146206CASHIE
Solar/Wind Harmer
-0.026
971547AH1-271 GEN
Solar/Wind Harmer
6.398
316212AC1-099_GEN
Solar/Wind Harmer
2.229
3146516WINFALL
Solar/Wind Harmer
-0.082
3146516WINFALL
Solar/Wind Harmer
-0.025
315800Z1-036_GEN1
Solar/Wind Harmer
6.312
3130156CHOWAN
Solar/Wind Harmer
-0.025
3145663CRESWEL
Solar/Wind Harmer
-0.071
971163AH1-040 GEN
Solar/Wind Harmer
23.925
316246AF1-032 C
Solar/Wind Harmer
0.515
316093AE2-104_GEN
Solar/Wind Harmer
7.34
3145963POPLR C
Solar/Wind Harmer
-0.025
316375AC2-012 GEN
Solar/Wind Harmer
8.687
3150981CHESPKA
Adder
2.789
316174AB2-169 GEN
Solar/Wind Harmer
3.863
3146233WITAKRS
Solar/Wind Harmer
-0.098
3146293MARTNCO
Solar/Wind Harmer
0.153
961671AG1-007 GEN
Solar/Wind Harmer
0.312
3146083TARBORO
Solar/Wind Harmer
-0.025
3145493TOT1
Solar/Wind Harmer
0.731
316494AC1-189 GEN
Solar/Wind Harmer
2.652
3145746EVERETS
Solar/Wind Harmer
-0.025
3145746EVERETS
Solar/Wind Harmer
-0.025
316359AB2-059 GEN
Solar/Wind Harmer
3.32
316049AB1-081 GEN
Solar/Wind Harmer
2.657
3142053HEARTS
Solar/Wind Harmer
0.289
3145543BTLEBRO
Solar/Wind Harmer
-0.025
3145543BTLEBRO
Solar/Wind Harmer
-0.02
970661AG2-428 GEN
Solar/Wind Harmer
25.261
316237AB2-079_GEN
Solar/Wind Harmer
0.715
316072AD1-144
Solar/Wind Harmer
0.478
970401AG2-262 GEN
Solar/Wind Harmer
1.532
316381AD1-082 GEN
Solar/Wind Harmer
2.151
970659AG2-427 GEN
Solar/Wind Harmer
12.403
316003AC1-222 GEN
Solar/Wind Harmer
2.155
3145336SMITFLD
Solar/Wind Harmer
-0.082
970685AG2-442 GEN
Solar/Wind Harmer
17.535
3144293JTRSVLE
Adder
0.538
3151171GRAVELC
Adder
1.692
3143226MDLTHAN
Solar/Wind Helper
0.326
316045AC1-158 PL2
Solar/Wind Helper
4.217
3143526WINTERP
Solar/Wind Helper
1.167
971563AH1-280 GEN
Solar/Wind Harmer
1.538
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146233WITAKRS
Solar/Wind Harmer
0.521
3146233WITAKRS
Solar/Wind Harmer
-0.017
3138543CONSLDL
Solar/Wind Harmer
-0.016
3145933PARMELE
Solar/Wind Harmer
-0.025
966801AG1-551 GEN
Solar/Wind Harmer
3.098
961601AG1-000A GEN
Solar/Wind Harmer
9.813
3146073TAR RVR
Solar/Wind Harmer
-0.025
3146083TARBORO
Solar/Wind Harmer
-0.025
3145746EVERETS
Solar/Wind Harmer
-0.025
3145746EVERETS
Solar/Wind Harmer
-0.025
3145543BTLEBRO
Solar/Wind Harmer
-0.025
3145543BTLEBRO
Solar/Wind Harmer
-0.025
3144536CHRHLND
Solar/Wind Harmer
-0.004
970661AG2-428 GEN
Solar/Wind Harmer
4.477
316131AB2-060 GEN
Solar/Wind Harmer
2.533
316083AB2-161 GEN
Solar/Wind Harmer
3.807
970659AG2-427 GEN
Solar/Wind Harmer
2.198
316248AF1-058 C
Solar/Wind Harmer
0.703
960061AF2-297 GEN
Solar/Wind Harmer
11.67
964241AG1-285 GEN
Solar/Wind Harmer
17.789
315813AE1-149 C
Solar/Wind Harmer
14.226
316283AC2-100 C
Solar/Wind Harmer
2.044
315785AD2-033 C
Solar/Wind Harmer
4.894
970257AG2-171 GEN
Solar/Wind Harmer
7.933
971683AH1-343 GEN
Solar/Wind Harmer
9.043
959311AF2-222 GEN
Solar/Wind Harmer
21.747
3145336SMITFLD
Solar/Wind Harmer
-0.008
970909AG2-566 GEN
Solar/Wind Harmer
1.91
3144293JTRSVLE
Adder
0.538
3151221GRAVEL6
Adder
11.564
3151171GRAVELC
Adder
2.225
3144216WINCHST
Adder
0.593
3150921YORKTN3
Adder
3.941
316044AC1-158 PL1
Solar/Wind Helper
1.317
316450AC1-158 RIC
Solar/Wind Helper
0.351
315244AE2-183_ST
50/50
9.597
963041AG1-153 GEN
50/50
8.809
315779AE2-040
50/50
4.21
3151541CLOVER2
50/50
5.541
3151281ROARAP4
50/50
0.287
3151281ROARAP4
50/50
0.268
3151151S HAMPT1
50/50
0.598
3151611KERR 4
50/50
0.465
3151621KERR 5
50/50
0.465
3151631KERR 6
50/50
0.465
3151641KERR 7
50/50
0.465
941031AE2-094 GEN
Solar/Wind Harmer
73.515
944011AF1-069 GEN
Solar/Wind Harmer
23.035
970673AG2-436 GEN
Solar/Wind Harmer
80.349
970673AG2-436 GEN
Solar/Wind Harmer
40.683
971967AH1-528 GEN
Solar/Wind Harmer
69.889
970085AG2-068 GEN
Solar/Wind Harmer
22.054
970581AG2-369 GEN
Solar/Wind Harmer
18.967
316315AB2-025 C
Solar/Wind Harmer
0.914
315814AE2-033 C
Solar/Wind Harmer
31.355
3143316POE
Solar/Wind Harmer
-0.131
946281AF1-292 GEN
Solar/Wind Harmer
0.632
316087AB2-174 GEN
Solar/Wind Harmer
3.95
315652AC1-086 GEN
Solar/Wind Harmer
30.832
3145796HORNRTN
Solar/Wind Harmer
-0.086
3145796HORNRTN
Solar/Wind Harmer
-0.011
3137643SOCKMAN
Solar/Wind Harmer
-0.107
315607AA1-063A GEN
Solar/Wind Harmer
2.662
3146043SEABORD
Solar/Wind Harmer
-0.026
965291AG1-394 GEN
Solar/Wind Harmer
2.306
316318V4-068
Solar/Wind Harmer
0.646
3145893MURPHYS
Solar/Wind Harmer
-0.07
3145893MURPHYS
Solar/Wind Harmer
-0.026
3145513AHOSKIE
Solar/Wind Harmer
0.225
961941AG1-037 GEN
Solar/Wind Harmer
0.194
3145513AHOSKIE
Solar/Wind Harmer
-0.026
3145683EARLEYS
Solar/Wind Harmer
-0.051
3145683EARLEYS
Solar/Wind Harmer
-0.026
3145683EARLEYS
Solar/Wind Harmer
-0.026
970831AG2-522 GEN
Solar/Wind Harmer
12.905
957871AF2-081 GEN
Solar/Wind Harmer
12.847
319010AE1-072 C
Solar/Wind Harmer
5.194
3146406KITTY HAWK
Solar/Wind Harmer
0.021
3146033SCOT NK
Solar/Wind Harmer
-0.102
313526AB2-022
Solar/Wind Harmer
0.691
316321Z2-027
Solar/Wind Harmer
0.691
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
3146396TANGLEW
Solar/Wind Harmer
0.471
3146206CASHIE
Solar/Wind Harmer
-0.026
970601AG2-382 GEN
Solar/Wind Harmer
11.197
315611Z1-036_GEN2
Solar/Wind Harmer
6.312
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
315816AE2-034 GEN
Solar/Wind Harmer
2.065
3146486SUNBURY
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
3130546PLYMOUTH
Solar/Wind Harmer
-0.025
315732AD1-074 GEN1
Solar/Wind Harmer
5.158
315733AD1-074 GEN2
Solar/Wind Harmer
5.158
315735AD1-075 GEN1
Solar/Wind Harmer
2.58
316305AF2-043 C
Solar/Wind Harmer
0.767
3151081ELIZAR1
Adder
20.599
3151091ELIZAR2
Adder
20.241
315835AF2-110_GEN
Solar/Wind Harmer
3.156
3152611GOSPORTB
Adder
2.846
3152621GOSPORTC
Adder
2.415
3152601GOSPORTA
Adder
2.228
316319Z2-044 C
Solar/Wind Harmer
1.375
3145573BETHELC
Solar/Wind Harmer
-0.025
3145573BETHELC
Solar/Wind Harmer
-0.025
316420AA1-050 GEN
Solar/Wind Harmer
2.815
957861AF2-080 GEN
Solar/Wind Harmer
10.782
316005AA1-067
Solar/Wind Harmer
0.498
3145746EVERETS
Solar/Wind Harmer
-0.097
3145746EVERETS
Solar/Wind Harmer
-0.025
3145746EVERETS
Solar/Wind Harmer
-0.025
3145746EVERETS
Solar/Wind Harmer
-0.025
970181AG2-120 GEN
Solar/Wind Harmer
3.234
316311AC2-079 GEN
Solar/Wind Harmer
12.392
315833AF1-017_GEN
Solar/Wind Harmer
4.664
316349AD2-085 GEN
Solar/Wind Harmer
2.184
316239AB2-077_GEN
Solar/Wind Harmer
0.715
316238AB2-078_GEN
Solar/Wind Harmer
0.715
316118AC1-105 GEN
Solar/Wind Harmer
1.61
3147173SINAI
Solar/Wind Harmer
-0.023
3147243WELCO
Solar/Wind Harmer
-0.014
971443AH1-215 GEN
Solar/Wind Harmer
4.184
3144303KENBRDG
Solar/Wind Harmer
-0.017
971445AH1-216 GEN
Solar/Wind Harmer
12.623
970683AG2-441 GEN
Solar/Wind Harmer
15.657
970681AG2-440 GEN
Solar/Wind Harmer
12.525
970865AG2-541 GEN
Solar/Wind Harmer
8.054
972265AH1-717 GEN
Adder
12.35
3151201GRAVEL4
Adder
11.578
3151191GRAVEL3
Adder
11.431
3151211GRAVEL5
Adder
11.431
316233AE1-074 FULL
Solar/Wind Helper
0.343
946301AF1-294 GEN
Solar/Wind Harmer
3.153
961791AG1-021 GEN
Solar/Wind Harmer
1.538
3145506HICKORY
Solar/Wind Harmer
-0.015
316339AD2-160 GEN
Solar/Wind Harmer
1.733
316018AA1-139 ULT2
Solar/Wind Harmer
2.201
316017AA1-139 ULT1
Solar/Wind Harmer
2.079
316185AD1-033 GEN
Solar/Wind Harmer
2.71
3137176SLIGO L2192
Solar/Wind Harmer
-0.102
3146456SLIGO L269
Solar/Wind Harmer
3.033
3130086AYDLETT
Solar/Wind Harmer
-0.102
316274AC1-208 GEN
Solar/Wind Harmer
2.766
3146386ELIZ CT
Solar/Wind Harmer
-0.026
315742AE1-103 GEN
Solar/Wind Harmer
2.672
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
316065AD1-022 GEN
Solar/Wind Harmer
12.78
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
316431W1029_GEN1
Solar/Wind Harmer
4.628
316433W1029_GEN2
Solar/Wind Harmer
4.628
3146376EDENTON
Solar/Wind Harmer
0.758
3146376EDENTON
Solar/Wind Harmer
0.758
3142956BIRDNECK
Solar/Wind Harmer
1.365
316316AC1-027 C
Solar/Wind Harmer
0.78
316036AC1-147 C
Solar/Wind Harmer
0.677
3150991CHESPKB
Adder
2.34
3150991CHESPKB
Adder
2.284
939181AE1-148 GEN
Solar/Wind Harmer
14.051
3145933PARMELE
Solar/Wind Harmer
-0.049
3145933PARMELE
Solar/Wind Harmer
-0.025
961601AG1-000A GEN
Solar/Wind Harmer
9.691
3145493TOT1
Solar/Wind Harmer
0.381
3145453TOT5
Solar/Wind Harmer
0.229
3145603CNETO
Solar/Wind Harmer
0.153
316263AC1-034 GEN
Solar/Wind Harmer
11.543
313527AB2-043 GEN
Solar/Wind Harmer
3.843
970657AG2-426 GEN
Solar/Wind Harmer
7.368
970657AG2-426 GEN
Solar/Wind Harmer
1.541
962561AG1-105 GEN
Solar/Wind Harmer
13.218
964791AG1-342 GEN
Solar/Wind Harmer
5.014
3146843MT LREL
Solar/Wind Harmer
-0.023
3146843MT LREL
Solar/Wind Harmer
-0.023
971741AH1-377 GEN
Solar/Wind Harmer
25.656
316222AC1-221 GEN
Solar/Wind Harmer
2.208
970323AG2-213 GEN
Solar/Wind Harmer
10.577
971775AH1-396 GEN
Solar/Wind Harmer
1.506
316034AC1-036 C
Solar/Wind Harmer
0.392
316236AE1-162_GEN
Solar/Wind Harmer
0.622
970301AG2-198 GEN
Solar/Wind Harmer
10.061
3144293JTRSVLE
Adder
0.538
3144293JTRSVLE
Adder
0.453
316447AC1-158 HLD
Solar/Wind Helper
2.9
3143526WINTERP
Solar/Wind Helper
1.167
958211AF2-115 GEN
Solar/Wind Harmer
1.923
LAGNLTFEXP_LAGN->PJM
CLTF
9.924
CBM South 2LTFEXP_CBM-S2->PJM
CBM
31.751
TVALTFEXP_TVA->PJM
CLTF
4.954
CPLELTFEXP_CPLE->PJM
CLTF
14.825
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.72
CBM West 1LTFEXP_CBM-W1->PJM
CBM
29.902
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.895
MECLTFEXP_MEC->PJM
CLTF
4.674
SIGELTFEXP_SIGE->PJM
CLTF
0.139
NYPJM->LTFIMP_NY
CLTF
2.268
LGEELTFEXP_LGEE->PJM
CLTF
1.668
WECLTFEXP_WEC->PJM
CLTF
0.858

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 208-259_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 208-259_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:106.32 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4188.82
MW Contribution:12.65
Bus #Bus NameTypeMW Contribution
970533AG2-339 GEN
50/50
29.719
970531AG2-338 GEN
50/50
11.888
315242AE2-183_GT2
50/50
5.316
315241AE2-183_GT1
50/50
5.284
972185AH1-677 GEN
50/50
19.166
3151041BRUNSWICKG3
50/50
4.166
972187AH1-678 GEN
50/50
9.56
970933AG2-581 GEN
Solar/Wind Harmer
31.755
970099AG2-077 GEN
Solar/Wind Harmer
37.003
3144356SAPONY
Solar/Wind Harmer
1.024
316185AD1-033 GEN
Solar/Wind Harmer
2.769
3145506HICKORY
Solar/Wind Harmer
-0.104
3145506HICKORY
Solar/Wind Harmer
-0.063
3145506HICKORY
Solar/Wind Harmer
-0.016
316339AD2-160 GEN
Solar/Wind Harmer
1.767
316018AA1-139 ULT2
Solar/Wind Harmer
2.243
316017AA1-139 ULT1
Solar/Wind Harmer
2.119
3137176SLIGO L2192
Solar/Wind Harmer
-0.103
3146456SLIGO L269
Solar/Wind Harmer
3.088
3130086AYDLETT
Solar/Wind Harmer
-0.104
3142956BIRDNECK
Solar/Wind Harmer
1.401
316316AC1-027 C
Solar/Wind Harmer
0.801
3146386ELIZ CT
Solar/Wind Harmer
-0.026
316036AC1-147 C
Solar/Wind Harmer
0.7
3150991CHESPKB
Adder
2.417
3150991CHESPKB
Adder
2.359
316431W1029_GEN1
Solar/Wind Harmer
4.679
316433W1029_GEN2
Solar/Wind Harmer
4.679
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
315244AE2-183_ST
50/50
9.192
963041AG1-153 GEN
50/50
8.436
315779AE2-040
50/50
3.649
3151541CLOVER2
50/50
5.284
3151081ELIZAR1
50/50
22.53
941031AE2-094 GEN
Solar/Wind Harmer
70.434
944011AF1-069 GEN
Solar/Wind Harmer
22.069
970673AG2-436 GEN
Solar/Wind Harmer
76.963
970673AG2-436 GEN
Solar/Wind Harmer
38.968
971967AH1-528 GEN
Solar/Wind Harmer
66.91
970085AG2-068 GEN
Solar/Wind Harmer
21.111
970581AG2-369 GEN
Solar/Wind Harmer
18.156
316315AB2-025 C
Solar/Wind Harmer
0.792
315814AE2-033 C
Solar/Wind Harmer
27.227
957871AF2-081 GEN
Solar/Wind Harmer
13.091
319010AE1-072 C
Solar/Wind Harmer
5.287
3146406KITTY HAWK
Solar/Wind Harmer
0.022
3151091ELIZAR2
Adder
20.863
313526AB2-022
Solar/Wind Harmer
0.701
316321Z2-027
Solar/Wind Harmer
0.7
3146396TANGLEW
Solar/Wind Harmer
0.477
316305AF2-043 C
Solar/Wind Harmer
0.782
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
3152611GOSPORTB
Adder
2.939
3152621GOSPORTC
Adder
2.494
3152601GOSPORTA
Adder
2.301
3146486SUNBURY
Solar/Wind Harmer
-0.026
3146486SUNBURY
Solar/Wind Harmer
-0.026
946281AF1-292 GEN
Solar/Wind Harmer
0.578
315611Z1-036_GEN2
Solar/Wind Harmer
6.337
315835AF2-110_GEN
Solar/Wind Harmer
3.202
316087AB2-174 GEN
Solar/Wind Harmer
3.644
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
315652AC1-086 GEN
Solar/Wind Harmer
28.603
3143316POE
Solar/Wind Harmer
-0.099
315816AE2-034 GEN
Solar/Wind Harmer
2.046
3137643SOCKMAN
Solar/Wind Harmer
-0.1
965291AG1-394 GEN
Solar/Wind Harmer
2.234
3145796HORNRTN
Solar/Wind Harmer
-0.08
3145796HORNRTN
Solar/Wind Harmer
-0.01
3130546PLYMOUTH
Solar/Wind Harmer
-0.025
315732AD1-074 GEN1
Solar/Wind Harmer
5.073
315733AD1-074 GEN2
Solar/Wind Harmer
5.073
315735AD1-075 GEN1
Solar/Wind Harmer
2.537
316318V4-068
Solar/Wind Harmer
0.625
3145893MURPHYS
Solar/Wind Harmer
-0.067
3145893MURPHYS
Solar/Wind Harmer
-0.025
3146043SEABORD
Solar/Wind Harmer
-0.025
315607AA1-063A GEN
Solar/Wind Harmer
2.532
3146206CASHIE
Solar/Wind Harmer
-0.025
970601AG2-382 GEN
Solar/Wind Harmer
10.946
3145513AHOSKIE
Solar/Wind Harmer
0.217
961941AG1-037 GEN
Solar/Wind Harmer
0.187
3145513AHOSKIE
Solar/Wind Harmer
-0.025
316311AC2-079 GEN
Solar/Wind Harmer
12.569
315833AF1-017_GEN
Solar/Wind Harmer
4.73
316349AD2-085 GEN
Solar/Wind Harmer
2.215
3145683EARLEYS
Solar/Wind Harmer
-0.049
3145683EARLEYS
Solar/Wind Harmer
-0.025
3145683EARLEYS
Solar/Wind Harmer
-0.025
3146033SCOT NK
Solar/Wind Harmer
-0.097
970831AG2-522 GEN
Solar/Wind Harmer
12.178
316005AA1-067
Solar/Wind Harmer
0.479
3145746EVERETS
Solar/Wind Harmer
-0.094
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
970181AG2-120 GEN
Solar/Wind Harmer
3.109
957861AF2-080 GEN
Solar/Wind Harmer
10.308
316319Z2-044 C
Solar/Wind Harmer
1.301
316420AA1-050 GEN
Solar/Wind Harmer
2.684
3145573BETHELC
Solar/Wind Harmer
-0.023
3145573BETHELC
Solar/Wind Harmer
-0.023
971445AH1-216 GEN
Solar/Wind Harmer
14.288
316239AB2-077_GEN
Solar/Wind Harmer
0.674
316238AB2-078_GEN
Solar/Wind Harmer
0.674
316118AC1-105 GEN
Solar/Wind Harmer
1.527
3147173SINAI
Solar/Wind Harmer
-0.022
3147243WELCO
Solar/Wind Harmer
-0.014
972265AH1-717 GEN
Adder
14.899
3146376EDENTON
Solar/Wind Harmer
0.757
3146376EDENTON
Solar/Wind Harmer
0.757
316181AB2-040 GEN
Solar/Wind Harmer
3.547
315742AE1-103 GEN
Solar/Wind Harmer
2.658
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.015
3145796HORNRTN
Solar/Wind Harmer
-0.075
3145893MURPHYS
Solar/Wind Harmer
0.7
3145893MURPHYS
Solar/Wind Harmer
-0.045
316065AD1-022 GEN
Solar/Wind Harmer
12.521
3151201GRAVEL4
Adder
13.967
3151191GRAVEL3
Adder
13.79
3151211GRAVEL5
Adder
13.79
971443AH1-215 GEN
Solar/Wind Harmer
3.932
3144303KENBRDG
Solar/Wind Harmer
-0.016
316369SG1_INVT
Solar/Wind Harmer
3.462
316233AE1-074 FULL
Solar/Wind Helper
0.392
970865AG2-541 GEN
Solar/Wind Harmer
2.854
3145593CAROLNA
Solar/Wind Harmer
-0.025
3145593CAROLNA
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.025
966811AG1-552 GEN
Solar/Wind Harmer
2.811
3145593CAROLNA
Solar/Wind Harmer
0.208
316426AA2-053 GEN
Solar/Wind Harmer
2.523
3145783HORNRTN
Solar/Wind Harmer
2.952
3145783HORNRTN
Solar/Wind Harmer
2.361
3145783HORNRTN
Solar/Wind Harmer
0.738
3145783HORNRTN
Solar/Wind Harmer
0.295
316274AC1-208 GEN
Solar/Wind Harmer
2.617
3145933PARMELE
Solar/Wind Harmer
-0.048
3145933PARMELE
Solar/Wind Harmer
-0.024
970657AG2-426 GEN
Solar/Wind Harmer
7.467
970657AG2-426 GEN
Solar/Wind Harmer
1.562
939181AE1-148 GEN
Solar/Wind Harmer
13.286
3145493TOT1
Solar/Wind Harmer
0.363
3145453TOT5
Solar/Wind Harmer
0.218
3145603CNETO
Solar/Wind Harmer
0.145
961601AG1-000A GEN
Solar/Wind Harmer
9.163
316263AC1-034 GEN
Solar/Wind Harmer
10.92
316236AE1-162_GEN
Solar/Wind Harmer
0.701
313527AB2-043 GEN
Solar/Wind Harmer
3.62
962561AG1-105 GEN
Solar/Wind Harmer
12.505
3146843MT LREL
Solar/Wind Harmer
-0.022
3146843MT LREL
Solar/Wind Harmer
-0.022
964791AG1-342 GEN
Solar/Wind Harmer
4.747
971741AH1-377 GEN
Solar/Wind Harmer
24.269
316222AC1-221 GEN
Solar/Wind Harmer
2.102
970323AG2-213 GEN
Solar/Wind Harmer
9.94
971775AH1-396 GEN
Solar/Wind Harmer
1.416
316034AC1-036 C
Solar/Wind Harmer
0.368
316033AB2-134 GEN
Solar/Wind Harmer
6.249
315697AD1-025 GEN
Solar/Wind Harmer
3.919
970301AG2-198 GEN
Solar/Wind Harmer
9.489
3144293JTRSVLE
Adder
0.504
3144293JTRSVLE
Adder
0.425
944641AF1-129 GEN
Adder
75.287
3143526WINTERP
Solar/Wind Helper
1.336
316447AC1-158 HLD
Solar/Wind Helper
2.874
3151031BRUNSWICKG2
50/50
4.166
970413AG2-270 GEN
50/50
23.168
3151101ELIZAR3
50/50
22.818
970917AG2-570 GEN
Solar/Wind Harmer
84.887
316478AD1-087 GEN
Solar/Wind Harmer
2.411
316486AD2-202 GEN
Solar/Wind Harmer
0.706
315773AC2-141 GEN
Solar/Wind Harmer
11.199
316365GEN2_N
Solar/Wind Harmer
1.804
944581AF1-123 GEN
Solar/Wind Harmer
121.142
944601AF1-125 GEN
Solar/Wind Harmer
119.252
3146456SLIGO L269
Solar/Wind Harmer
-0.026
971153AH1-033 GEN
Solar/Wind Harmer
3.188
316320Y1-086
Solar/Wind Harmer
1.524
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316435W1029_GEN3
Solar/Wind Harmer
4.679
966621AG1-532 GEN
Solar/Wind Harmer
0.524
3146516WINFALL
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3146376EDENTON
Solar/Wind Harmer
-0.025
3145273HOLLAND
Solar/Wind Harmer
-0.019
313506AB2-031 GEN
Solar/Wind Harmer
2.044
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
315614AA2-178 GEN
Solar/Wind Harmer
2.729
3156081AA2-088 GEN
Solar/Wind Harmer
8.176
3144536CHRHLND
Solar/Wind Harmer
-0.004
3145796HORNRTN
Solar/Wind Harmer
-0.1
3145796HORNRTN
Solar/Wind Harmer
-0.025
971157AH1-035 GEN
Solar/Wind Harmer
3.139
315737AD1-076 GEN
Solar/Wind Harmer
4.767
3145893MURPHYS
Solar/Wind Harmer
0.175
3145893MURPHYS
Solar/Wind Harmer
-0.025
957521AF2-046 GEN
Solar/Wind Harmer
19.729
961681AG1-008 GEN
Solar/Wind Harmer
19.729
3146206CASHIE
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.025
316463AE2-346 GEN
Solar/Wind Harmer
0.404
316140AB2-099
Solar/Wind Harmer
0.168
962331AG1-082 GEN
Solar/Wind Harmer
3.117
3156021HOLLOMANSOL
Solar/Wind Harmer
3.359
3146263WOODLND
Solar/Wind Harmer
-0.025
3147043LAWRENC
Solar/Wind Harmer
-0.015
316317KELFORD C
Solar/Wind Harmer
1.163
3145823KELFORD
Solar/Wind Harmer
-0.025
3145963POPLR C
Solar/Wind Harmer
-0.024
316210AC1-098 GEN
Solar/Wind Harmer
3.812
315724AD1-057 GEN
Solar/Wind Harmer
1.388
970661AG2-428 GEN
Solar/Wind Harmer
4.538
3145933PARMELE
Solar/Wind Harmer
-0.024
966801AG1-551 GEN
Solar/Wind Harmer
2.991
316327AA2-057 GEN
Solar/Wind Harmer
2.405
316083AB2-161 GEN
Solar/Wind Harmer
3.858
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
970659AG2-427 GEN
Solar/Wind Harmer
2.227
3146233WITAKRS
Solar/Wind Harmer
0.493
3146233WITAKRS
Solar/Wind Harmer
-0.016
315243AE2-183_GT3
50/50
5.316
3151051BRUNSWICKS1
50/50
8.646
3151021BRUNSWICKG1
50/50
4.166
971451AH1-221 GEN
50/50
12.653
3151531CLOVER1
50/50
5.309
940641AE2-051 GEN
Solar/Wind Harmer
34.779
939411AE1-173 GEN
Solar/Wind Harmer
172.015
970919AG2-571 GEN
Solar/Wind Harmer
10.745
970087AG2-069 GEN
Solar/Wind Harmer
31.667
957481AF2-042 GEN
Solar/Wind Harmer
92.508
315693AD1-088 GEN
Solar/Wind Harmer
13.627
962491AG1-098 GEN
Solar/Wind Harmer
17.939
316294AC1-161 GEN
Solar/Wind Harmer
8.659
316023GEN1_S
Solar/Wind Harmer
1.804
944591AF1-124 GEN
Solar/Wind Harmer
121.578
316388AE2-253 GEN
Solar/Wind Harmer
1.767
3146456SLIGO L269
Solar/Wind Harmer
-0.026
316375AC2-012 GEN
Solar/Wind Harmer
8.973
3150981CHESPKA
Adder
2.881
316246AF1-032 C
Solar/Wind Harmer
0.525
315687AD1-152 GEN
Solar/Wind Harmer
3.124
960081AF2-299 GEN
Solar/Wind Harmer
2.904
3146516WINFALL
Solar/Wind Harmer
-0.083
3146516WINFALL
Solar/Wind Harmer
-0.026
315800Z1-036_GEN1
Solar/Wind Harmer
6.337
316093AE2-104_GEN
Solar/Wind Harmer
7.449
3130156CHOWAN
Solar/Wind Harmer
-0.025
316011AB1-132 GEN
Solar/Wind Harmer
5.319
962571AG1-106 GEN
Solar/Wind Harmer
3.655
3145663CRESWEL
Solar/Wind Harmer
-0.07
971163AH1-040 GEN
Solar/Wind Harmer
23.71
3145796HORNRTN
Solar/Wind Harmer
-0.082
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
-0.1
3145893MURPHYS
Solar/Wind Harmer
0.744
971795AH1-408 GEN
Solar/Wind Harmer
18.809
3146206CASHIE
Solar/Wind Harmer
-0.025
971547AH1-271 GEN
Solar/Wind Harmer
6.255
3146173TUNIS
Solar/Wind Harmer
-0.025
316190AA2-174 GEN
Solar/Wind Harmer
0.307
3146263WOODLND
Solar/Wind Harmer
-0.025
3145683EARLEYS
Solar/Wind Harmer
-0.025
3145783HORNRTN
Solar/Wind Harmer
-0.025
3147043LAWRENC
Adder
1.992
316072AD1-144
Solar/Wind Harmer
0.5
3145823KELFORD
Solar/Wind Harmer
-0.025
3145963POPLR C
Solar/Wind Harmer
-0.024
316174AB2-169 GEN
Solar/Wind Harmer
3.756
316212AC1-099_GEN
Solar/Wind Harmer
2.118
316129AC1-054 GEN
Solar/Wind Harmer
2.129
971065AG2-659 GEN
Solar/Wind Harmer
12.112
315722AD1-056 GEN
Solar/Wind Harmer
2.523
970661AG2-428 GEN
Solar/Wind Harmer
25.606
3146293MARTNCO
Solar/Wind Harmer
0.148
316381AD1-082 GEN
Solar/Wind Harmer
2.18
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
970659AG2-427 GEN
Solar/Wind Harmer
12.568
316494AC1-189 GEN
Solar/Wind Harmer
2.535
3146233WITAKRS
Solar/Wind Harmer
-0.093
961671AG1-007 GEN
Solar/Wind Harmer
0.296
3146083TARBORO
Solar/Wind Harmer
-0.023
3145493TOT1
Solar/Wind Harmer
0.696
316359AB2-059 GEN
Solar/Wind Harmer
3.141
316049AB1-081 GEN
Solar/Wind Harmer
2.514
3142053HEARTS
Solar/Wind Harmer
0.274
3145543BTLEBRO
Solar/Wind Harmer
-0.023
3145543BTLEBRO
Solar/Wind Harmer
-0.019
3145336SMITFLD
Solar/Wind Harmer
-0.093
316237AB2-079_GEN
Solar/Wind Harmer
0.674
970401AG2-262 GEN
Solar/Wind Harmer
1.45
3151171GRAVELC
Adder
2.041
316003AC1-222 GEN
Solar/Wind Harmer
2.048
961611AG1-000B GEN
Solar/Wind Harmer
10.222
971647AH1-324 GEN
Solar/Wind Harmer
10.02
3138126ROCKLANDING
Solar/Wind Harmer
0.06
971069AG2-661 GEN
Solar/Wind Harmer
2.982
3138543CONSLDL
Solar/Wind Harmer
-0.015
3146073TAR RVR
Solar/Wind Harmer
-0.023
3146083TARBORO
Solar/Wind Harmer
-0.023
961601AG1-000A GEN
Solar/Wind Harmer
9.279
3145543BTLEBRO
Solar/Wind Harmer
-0.023
3145543BTLEBRO
Solar/Wind Harmer
-0.023
3145336SMITFLD
Solar/Wind Harmer
-0.009
315813AE1-149 C
Solar/Wind Harmer
14.408
316248AF1-058 C
Solar/Wind Harmer
0.668
960061AF2-297 GEN
Solar/Wind Harmer
11.09
316131AB2-060 GEN
Solar/Wind Harmer
2.386
3151221GRAVEL6
Adder
13.951
3151171GRAVELC
Adder
2.684
964241AG1-285 GEN
Solar/Wind Harmer
16.743
315839AE2-212 C
Solar/Wind Harmer
0.632
961611AG1-000B GEN
Solar/Wind Harmer
4.362
316283AC2-100 C
Solar/Wind Harmer
1.947
315785AD2-033 C
Solar/Wind Harmer
4.601
971683AH1-343 GEN
Solar/Wind Harmer
8.591
970257AG2-171 GEN
Solar/Wind Harmer
7.455
3144216WINCHST
Adder
0.658
959311AF2-222 GEN
Solar/Wind Harmer
20.43
3150921YORKTN3
Adder
4.314
970909AG2-566 GEN
Solar/Wind Harmer
1.802
315778AD1-151 GEN
Solar/Wind Harmer
16.326
3144293JTRSVLE
Adder
0.504
316044AC1-158 PL1
Solar/Wind Helper
1.306
316450AC1-158 RIC
Solar/Wind Helper
0.348
3144293JTRSVLE
Adder
0.504
3143226MDLTHAN
Solar/Wind Helper
0.345
3143526WINTERP
Solar/Wind Helper
1.336
316045AC1-158 PL2
Solar/Wind Helper
4.18
LAGNLTFEXP_LAGN->PJM
CLTF
9.388
CBM South 2LTFEXP_CBM-S2->PJM
CBM
30.224
TVALTFEXP_TVA->PJM
CLTF
4.687
CPLELTFEXP_CPLE->PJM
CLTF
14.126
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.754
CBM West 1LTFEXP_CBM-W1->PJM
CBM
27.772
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.963
MECLTFEXP_MEC->PJM
CLTF
4.378
SIGELTFEXP_SIGE->PJM
CLTF
0.13
NYPJM->LTFIMP_NY
CLTF
2.225
LGEELTFEXP_LGEE->PJM
CLTF
1.558
WECLTFEXP_WEC->PJM
CLTF
0.8

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.09 %
Rating:3220.44 MVA
Rating Type:A
MVA to Mitigate:3384.28
MW Contribution:12.31
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
4.054
970413AG2-270 GEN
50/50
22.561
3151101ELIZAR3
50/50
21.566
970917AG2-570 GEN
Solar/Wind Harmer
26.133
316478AD1-087 GEN
Solar/Wind Harmer
0.842
316486AD2-202 GEN
Solar/Wind Harmer
0.247
315773AC2-141 GEN
Solar/Wind Harmer
8.348
944581AF1-123 GEN
Solar/Wind Harmer
50.754
944601AF1-125 GEN
Solar/Wind Harmer
49.972
316365GEN2_N
Solar/Wind Harmer
0.501
3146456SLIGO L269
Solar/Wind Harmer
0.22
971153AH1-033 GEN
Solar/Wind Harmer
2.55
316320Y1-086
Solar/Wind Harmer
0.001
3144873MCLAUGH
Solar/Wind Harmer
0.005
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.217
3146626S HERTFORD
Solar/Wind Harmer
0.217
3146376EDENTON
Solar/Wind Harmer
0.215
313506AB2-031 GEN
Solar/Wind Harmer
0.662
3145273HOLLAND
Solar/Wind Harmer
0.16
315614AA2-178 GEN
Solar/Wind Harmer
1.222
3142666NORTHAMPTON
Solar/Wind Harmer
0.213
971157AH1-035 GEN
Solar/Wind Harmer
2.545
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
315737AD1-076 GEN
Solar/Wind Harmer
2.725
3145796HORNRTN
Solar/Wind Harmer
0.846
3145796HORNRTN
Solar/Wind Harmer
0.211
3145893MURPHYS
Solar/Wind Harmer
0.354
3145893MURPHYS
Solar/Wind Harmer
0.211
3146206CASHIE
Solar/Wind Harmer
0.211
957521AF2-046 GEN
Solar/Wind Harmer
15.712
961681AG1-008 GEN
Solar/Wind Harmer
15.712
3146173TUNIS
Solar/Wind Harmer
0.211
3156021HOLLOMANSOL
Solar/Wind Harmer
0.955
316463AE2-346 GEN
Solar/Wind Harmer
0.181
316140AB2-099
Solar/Wind Harmer
0.075
3146263WOODLND
Solar/Wind Harmer
0.21
962331AG1-082 GEN
Solar/Wind Harmer
2.245
3144536CHRHLND
Solar/Wind Harmer
0.031
3147043LAWRENC
Solar/Wind Harmer
0.126
316317KELFORD C
Solar/Wind Harmer
0.02
3145823KELFORD
Solar/Wind Harmer
0.208
3145963POPLR C
Solar/Wind Harmer
0.207
316210AC1-098 GEN
Solar/Wind Harmer
1.908
315724AD1-057 GEN
Solar/Wind Harmer
0.766
970533AG2-339 GEN
50/50
28.925
970531AG2-338 GEN
50/50
11.57
315242AE2-183_GT2
50/50
5.174
315241AE2-183_GT1
50/50
5.142
972185AH1-677 GEN
50/50
18.653
3151041BRUNSWICKG3
50/50
4.054
972187AH1-678 GEN
50/50
9.304
970933AG2-581 GEN
Solar/Wind Harmer
23.481
970099AG2-077 GEN
Solar/Wind Harmer
27.375
3144356SAPONY
Solar/Wind Harmer
2.028
316185AD1-033 GEN
Solar/Wind Harmer
0.006
3145506HICKORY
Solar/Wind Harmer
0.885
3145506HICKORY
Solar/Wind Harmer
0.531
3145506HICKORY
Solar/Wind Harmer
0.133
316339AD2-160 GEN
Solar/Wind Harmer
0.358
316018AA1-139 ULT2
Solar/Wind Harmer
0.005
316017AA1-139 ULT1
Solar/Wind Harmer
0.123
3137176SLIGO L2192
Solar/Wind Harmer
0.878
3146456SLIGO L269
Solar/Wind Harmer
3.903
3130086AYDLETT
Solar/Wind Harmer
0.881
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.211
3146386ELIZ CT
Solar/Wind Harmer
0.219
316036AC1-147 C
Solar/Wind Harmer
0.04
3150991CHESPKB
Adder
2.282
3150991CHESPKB
Adder
2.228
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.217
3146516WINFALL
Solar/Wind Harmer
0.217
3146516WINFALL
Solar/Wind Harmer
0.217
3146626S HERTFORD
Solar/Wind Harmer
0.217
3146626S HERTFORD
Solar/Wind Harmer
0.217
3146376EDENTON
Solar/Wind Harmer
0.957
3146376EDENTON
Solar/Wind Harmer
0.957
316181AB2-040 GEN
Solar/Wind Harmer
0.311
3142666NORTHAMPTON
Solar/Wind Harmer
0.213
3142666NORTHAMPTON
Solar/Wind Harmer
0.213
3142666NORTHAMPTON
Solar/Wind Harmer
0.213
3142666NORTHAMPTON
Solar/Wind Harmer
0.128
315742AE1-103 GEN
Solar/Wind Harmer
0.002
3145796HORNRTN
Solar/Wind Harmer
0.634
316065AD1-022 GEN
Solar/Wind Harmer
9.736
3145893MURPHYS
Solar/Wind Harmer
1.414
3145893MURPHYS
Solar/Wind Harmer
0.38
3145593CAROLNA
Solar/Wind Harmer
0.211
3145593CAROLNA
Solar/Wind Harmer
0.211
966811AG1-552 GEN
Solar/Wind Harmer
2.291
3145593CAROLNA
Solar/Wind Harmer
0.263
316426AA2-053 GEN
Solar/Wind Harmer
0.712
3146173TUNIS
Solar/Wind Harmer
0.211
3146173TUNIS
Solar/Wind Harmer
0.211
3145783HORNRTN
Solar/Wind Harmer
3.739
3145783HORNRTN
Solar/Wind Harmer
2.991
3145783HORNRTN
Solar/Wind Harmer
0.935
3145783HORNRTN
Solar/Wind Harmer
0.374
316274AC1-208 GEN
Solar/Wind Harmer
1.066
939181AE1-148 GEN
Solar/Wind Harmer
9.756
3145933PARMELE
Solar/Wind Harmer
0.406
3145933PARMELE
Solar/Wind Harmer
0.203
3145493TOT1
Solar/Wind Harmer
0.462
3145453TOT5
Solar/Wind Harmer
0.277
3145603CNETO
Solar/Wind Harmer
0.185
961601AG1-000A GEN
Solar/Wind Harmer
3.522
316263AC1-034 GEN
Solar/Wind Harmer
7.526
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
9.215
3146843MT LREL
Solar/Wind Harmer
0.192
3146843MT LREL
Solar/Wind Harmer
0.192
964791AG1-342 GEN
Solar/Wind Harmer
3.686
970657AG2-426 GEN
Solar/Wind Harmer
6.636
970657AG2-426 GEN
Solar/Wind Harmer
1.391
316236AE1-162_GEN
Solar/Wind Harmer
0.002
971741AH1-377 GEN
Solar/Wind Harmer
18.103
316222AC1-221 GEN
Solar/Wind Harmer
0.745
970323AG2-213 GEN
Solar/Wind Harmer
7.354
971775AH1-396 GEN
Solar/Wind Harmer
0.276
316034AC1-036 C
Solar/Wind Harmer
0.013
970301AG2-198 GEN
Solar/Wind Harmer
7.099
958211AF2-115 GEN
Solar/Wind Harmer
1.863
963191AG1-168 GEN
Solar/Wind Harmer
0.621
3144293JTRSVLE
Adder
0.494
3144293JTRSVLE
Adder
0.416
3147133PAMPLIN
Solar/Wind Harmer
0.149
3147133PAMPLIN
Solar/Wind Harmer
0.119
316033AB2-134 GEN
Solar/Wind Harmer
0.008
315697AD1-025 GEN
Solar/Wind Harmer
0.161
942751AE2-291 GEN
Solar/Wind Harmer
7.176
316240AF1-291 C
Solar/Wind Harmer
0.001
316447AC1-158 HLD
Solar/Wind Helper
2.812
3145933PARMELE
Solar/Wind Harmer
0.203
966801AG1-551 GEN
Solar/Wind Harmer
2.363
316327AA2-057 GEN
Solar/Wind Harmer
0.305
3145746EVERETS
Solar/Wind Harmer
0.201
3145746EVERETS
Solar/Wind Harmer
0.201
3146233WITAKRS
Solar/Wind Harmer
1.004
3146233WITAKRS
Solar/Wind Harmer
0.136
3138543CONSLDL
Solar/Wind Harmer
0.132
3146073TAR RVR
Solar/Wind Harmer
0.199
3146083TARBORO
Solar/Wind Harmer
0.199
961601AG1-000A GEN
Solar/Wind Harmer
14.088
3145543BTLEBRO
Solar/Wind Harmer
0.198
3145543BTLEBRO
Solar/Wind Harmer
0.198
971623AH1-311 GEN
Solar/Wind Harmer
0.396
970661AG2-428 GEN
Solar/Wind Harmer
4.071
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
8.184
316131AB2-060 GEN
Solar/Wind Harmer
0.6
3145336SMITFLD
Solar/Wind Harmer
0.076
316083AB2-161 GEN
Solar/Wind Harmer
0.003
970659AG2-427 GEN
Solar/Wind Harmer
1.969
964241AG1-285 GEN
Solar/Wind Harmer
12.343
316283AC2-100 C
Solar/Wind Harmer
0.349
315813AE1-149 C
Solar/Wind Harmer
9.464
315785AD2-033 C
Solar/Wind Harmer
1.43
971683AH1-343 GEN
Solar/Wind Harmer
6.344
970257AG2-171 GEN
Solar/Wind Harmer
5.516
3151221GRAVEL6
Adder
12.414
3151171GRAVELC
Adder
2.388
959311AF2-222 GEN
Solar/Wind Harmer
15.096
970909AG2-566 GEN
Solar/Wind Harmer
1.775
3144216WINCHST
Adder
0.609
961611AG1-000B GEN
Solar/Wind Harmer
4.271
3150921YORKTN3
Adder
4.021
963181AG1-167 GEN
Solar/Wind Harmer
0.621
3144293JTRSVLE
Adder
0.494
3147133PAMPLIN
Solar/Wind Harmer
0.469
971193AH1-056 GEN
Solar/Wind Harmer
9.098
315839AE2-212 C
Solar/Wind Harmer
0.001
965281AG1-393 GEN
Solar/Wind Harmer
1.464
315778AD1-151 GEN
Solar/Wind Harmer
10.941
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316382AG1-145 C
Solar/Wind Harmer
0.001
970129AG2-093 GEN
Solar/Wind Harmer
7.591
3146926FARMVIL
Solar/Wind Harmer
0.069
316044AC1-158 PL1
Solar/Wind Helper
1.278
316450AC1-158 RIC
Solar/Wind Helper
0.341
315244AE2-183_ST
50/50
8.945
963041AG1-153 GEN
50/50
8.209
315779AE2-040
50/50
3.384
3151541CLOVER2
50/50
5.145
3151081ELIZAR1
50/50
21.293
941031AE2-094 GEN
Solar/Wind Harmer
59.933
944011AF1-069 GEN
Solar/Wind Harmer
19.582
970673AG2-436 GEN
Solar/Wind Harmer
67.697
970673AG2-436 GEN
Solar/Wind Harmer
45.131
971967AH1-528 GEN
Solar/Wind Harmer
49.335
970085AG2-068 GEN
Solar/Wind Harmer
15.598
970581AG2-369 GEN
Solar/Wind Harmer
13.414
316315AB2-025 C
Solar/Wind Harmer
0.196
315814AE2-033 C
Solar/Wind Harmer
19.104
957871AF2-081 GEN
Solar/Wind Harmer
10.995
319010AE1-072 C
Solar/Wind Harmer
1.11
3146406KITTY HAWK
Solar/Wind Harmer
0.027
313526AB2-022
Solar/Wind Harmer
0.119
3151091ELIZAR2
Adder
19.718
316321Z2-027
Solar/Wind Harmer
0.041
3146396TANGLEW
Solar/Wind Harmer
0.603
3145176PASQUOTANK
Solar/Wind Harmer
0.136
316305AF2-043 C
Solar/Wind Harmer
0.002
3146486SUNBURY
Solar/Wind Harmer
0.218
3146486SUNBURY
Solar/Wind Harmer
0.218
3152611GOSPORTB
Adder
2.775
3152621GOSPORTC
Adder
2.355
3152601GOSPORTA
Adder
2.173
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.215
3130156CHOWAN
Solar/Wind Harmer
0.215
316087AB2-174 GEN
Solar/Wind Harmer
0.006
315835AF2-110_GEN
Solar/Wind Harmer
1.469
315652AC1-086 GEN
Solar/Wind Harmer
23.522
315816AE2-034 GEN
Solar/Wind Harmer
0.916
3137643SOCKMAN
Solar/Wind Harmer
0.849
3130546PLYMOUTH
Solar/Wind Harmer
0.212
965291AG1-394 GEN
Solar/Wind Harmer
0.942
315732AD1-074 GEN1
Solar/Wind Harmer
1.217
315733AD1-074 GEN2
Solar/Wind Harmer
1.217
315735AD1-075 GEN1
Solar/Wind Harmer
0.609
3145796HORNRTN
Solar/Wind Harmer
0.677
3145796HORNRTN
Solar/Wind Harmer
0.085
3146043SEABORD
Solar/Wind Harmer
0.211
315607AA1-063A GEN
Solar/Wind Harmer
0.432
3145893MURPHYS
Solar/Wind Harmer
0.57
3145893MURPHYS
Solar/Wind Harmer
0.211
3146206CASHIE
Solar/Wind Harmer
0.211
970601AG2-382 GEN
Solar/Wind Harmer
7.886
3145513AHOSKIE
Solar/Wind Harmer
0.44
3145513AHOSKIE
Solar/Wind Harmer
0.21
3145683EARLEYS
Solar/Wind Harmer
0.42
3145683EARLEYS
Solar/Wind Harmer
0.21
3145683EARLEYS
Solar/Wind Harmer
0.21
970831AG2-522 GEN
Solar/Wind Harmer
8.873
3146033SCOT NK
Solar/Wind Harmer
0.827
316311AC2-079 GEN
Solar/Wind Harmer
5.862
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.14
316005AA1-067
Solar/Wind Harmer
0.216
3145746EVERETS
Solar/Wind Harmer
0.8
3145746EVERETS
Solar/Wind Harmer
0.201
3145746EVERETS
Solar/Wind Harmer
0.201
3145746EVERETS
Solar/Wind Harmer
0.201
970181AG2-120 GEN
Solar/Wind Harmer
2.501
316319Z2-044 C
Solar/Wind Harmer
0
957861AF2-080 GEN
Solar/Wind Harmer
8.623
316420AA1-050 GEN
Solar/Wind Harmer
0.007
3145573BETHELC
Solar/Wind Harmer
0.199
3145573BETHELC
Solar/Wind Harmer
0.199
3143316POE
Solar/Wind Harmer
0.769
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.495
3147173SINAI
Solar/Wind Harmer
0.192
3147243WELCO
Solar/Wind Harmer
0.12
971445AH1-216 GEN
Solar/Wind Harmer
13.184
971443AH1-215 GEN
Solar/Wind Harmer
2.909
3144303KENBRDG
Solar/Wind Harmer
0.138
972265AH1-717 GEN
Adder
13.258
3151201GRAVEL4
Adder
12.428
3151191GRAVEL3
Adder
12.271
3151211GRAVEL5
Adder
12.271
970683AG2-441 GEN
Solar/Wind Harmer
10.903
970681AG2-440 GEN
Solar/Wind Harmer
8.722
970865AG2-541 GEN
Solar/Wind Harmer
5.652
946301AF1-294 GEN
Solar/Wind Harmer
3.063
961791AG1-021 GEN
Solar/Wind Harmer
1.49
315657AE1-056 GEN
Solar/Wind Harmer
5.154
316123AC1-075 GEN
Solar/Wind Harmer
0.197
970165AG2-112 GEN
Solar/Wind Harmer
1.167
970163AG2-111 GEN
Solar/Wind Harmer
1.113
316369SG1_INVT
Solar/Wind Harmer
0.005
3138283WHITEMARSH
Solar/Wind Harmer
0.03
316132AB2-190 GEN1
Solar/Wind Harmer
0.682
315243AE2-183_GT3
50/50
5.174
3151051BRUNSWICKS1
50/50
8.414
3151021BRUNSWICKG1
50/50
4.054
971451AH1-221 GEN
50/50
12.314
3151531CLOVER1
50/50
5.17
940641AE2-051 GEN
Solar/Wind Harmer
25.663
939411AE1-173 GEN
Solar/Wind Harmer
126.366
970919AG2-571 GEN
Solar/Wind Harmer
10.453
970087AG2-069 GEN
Solar/Wind Harmer
23.397
957481AF2-042 GEN
Solar/Wind Harmer
68.436
315693AD1-088 GEN
Solar/Wind Harmer
11.355
962491AG1-098 GEN
Solar/Wind Harmer
13.293
316294AC1-161 GEN
Solar/Wind Harmer
3.96
944591AF1-124 GEN
Solar/Wind Harmer
50.934
315687AD1-152 GEN
Solar/Wind Harmer
0.007
316023GEN1_S
Solar/Wind Harmer
0.501
316388AE2-253 GEN
Solar/Wind Harmer
0.692
3146456SLIGO L269
Solar/Wind Harmer
0.22
316246AF1-032 C
Solar/Wind Harmer
0.098
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
2.721
3146516WINFALL
Solar/Wind Harmer
0.705
3146516WINFALL
Solar/Wind Harmer
0.217
960081AF2-299 GEN
Solar/Wind Harmer
2.083
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.215
316093AE2-104_GEN
Solar/Wind Harmer
3.601
316011AB1-132 GEN
Solar/Wind Harmer
3.888
962571AG1-106 GEN
Solar/Wind Harmer
3.042
3145663CRESWEL
Solar/Wind Harmer
0.597
971163AH1-040 GEN
Solar/Wind Harmer
17.076
971795AH1-408 GEN
Solar/Wind Harmer
14.122
3145796HORNRTN
Solar/Wind Harmer
0.698
3145796HORNRTN
Solar/Wind Harmer
0.211
3145893MURPHYS
Solar/Wind Harmer
0.845
3145893MURPHYS
Solar/Wind Harmer
0.939
3146206CASHIE
Solar/Wind Harmer
0.211
971547AH1-271 GEN
Solar/Wind Harmer
4.506
316190AA2-174 GEN
Solar/Wind Harmer
0
3146173TUNIS
Solar/Wind Harmer
0.211
3146263WOODLND
Solar/Wind Harmer
0.21
3145783HORNRTN
Solar/Wind Harmer
0.21
3145683EARLEYS
Solar/Wind Harmer
0.21
3147043LAWRENC
Adder
1.895
3145823KELFORD
Solar/Wind Harmer
0.208
316129AC1-054 GEN
Solar/Wind Harmer
0.781
971065AG2-659 GEN
Solar/Wind Harmer
8.844
3145963POPLR C
Solar/Wind Harmer
0.207
316072AD1-144
Solar/Wind Harmer
0.075
316174AB2-169 GEN
Solar/Wind Harmer
0.005
316212AC1-099_GEN
Solar/Wind Harmer
1.064
315722AD1-056 GEN
Solar/Wind Harmer
1.293
3146293MARTNCO
Solar/Wind Harmer
0.188
3145746EVERETS
Solar/Wind Harmer
0.201
3145746EVERETS
Solar/Wind Harmer
0.201
3146233WITAKRS
Solar/Wind Harmer
0.796
316494AC1-189 GEN
Solar/Wind Harmer
0.676
961671AG1-007 GEN
Solar/Wind Harmer
0.03
3146083TARBORO
Solar/Wind Harmer
0.199
3145493TOT1
Solar/Wind Harmer
0.885
316359AB2-059 GEN
Solar/Wind Harmer
0.711
316049AB1-081 GEN
Solar/Wind Harmer
1.133
3145543BTLEBRO
Solar/Wind Harmer
0.198
3145543BTLEBRO
Solar/Wind Harmer
0.158
3142053HEARTS
Solar/Wind Harmer
0.349
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970661AG2-428 GEN
Solar/Wind Harmer
19.138
970401AG2-262 GEN
Solar/Wind Harmer
1.126
3145336SMITFLD
Solar/Wind Harmer
0.755
316381AD1-082 GEN
Solar/Wind Harmer
0.196
970659AG2-427 GEN
Solar/Wind Harmer
8.999
316003AC1-222 GEN
Solar/Wind Harmer
0.005
3151171GRAVELC
Adder
1.816
970685AG2-442 GEN
Solar/Wind Harmer
12.211
3138126ROCKLANDING
Solar/Wind Harmer
0.074
961611AG1-000B GEN
Solar/Wind Harmer
8.399
963171AG1-166 GEN
Solar/Wind Harmer
0.828
971563AH1-280 GEN
Solar/Wind Harmer
1.656
3144293JTRSVLE
Adder
0.494
971647AH1-324 GEN
Solar/Wind Harmer
6.473
971317AH1-138 GEN
Solar/Wind Harmer
1.095
971069AG2-661 GEN
Solar/Wind Harmer
2.431
316159AE1-175 C
Solar/Wind Harmer
0.112
315671AE2-027_GEN
Solar/Wind Harmer
8.259
316458AB2-190 GEN2
Solar/Wind Harmer
0.682
970129AG2-093 GEN
Solar/Wind Harmer
3.572
3146926FARMVIL
Solar/Wind Harmer
0.069
3143226MDLTHAN
Solar/Wind Helper
0.299
316045AC1-158 PL2
Solar/Wind Helper
4.09
LAGNLTFEXP_LAGN->PJM
CLTF
9.15
CBM South 2LTFEXP_CBM-S2->PJM
CBM
29.306
TVALTFEXP_TVA->PJM
CLTF
4.569
CPLELTFEXP_CPLE->PJM
CLTF
13.67
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.627
CBM West 1LTFEXP_CBM-W1->PJM
CBM
27.362
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.575
MECLTFEXP_MEC->PJM
CLTF
4.294
SIGELTFEXP_SIGE->PJM
CLTF
0.128
NYPJM->LTFIMP_NY
CLTF
2.148
LGEELTFEXP_LGEE->PJM
CLTF
1.532
WECLTFEXP_WEC->PJM
CLTF
0.787

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o AEP_P2-2_#1377_05J.FERR 765_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:104.67 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4124.05
MW Contribution:12.79
Bus #Bus NameTypeMW Contribution
315244AE2-183_ST
50/50
9.276
963041AG1-153 GEN
50/50
8.526
3151541CLOVER2
50/50
5.413
315779AE2-040
50/50
3.53
941031AE2-094 GEN
Solar/Wind Harmer
70.83
944011AF1-069 GEN
Solar/Wind Harmer
22.193
970673AG2-436 GEN
Solar/Wind Harmer
77.572
970673AG2-436 GEN
Solar/Wind Harmer
39.277
971967AH1-528 GEN
Solar/Wind Harmer
67.508
970085AG2-068 GEN
Solar/Wind Harmer
21.475
970581AG2-369 GEN
Solar/Wind Harmer
18.469
316315AB2-025 C
Solar/Wind Harmer
0.766
315814AE2-033 C
Solar/Wind Harmer
26.373
957871AF2-081 GEN
Solar/Wind Harmer
12.934
319010AE1-072 C
Solar/Wind Harmer
5.226
3146406KITTY HAWK
Solar/Wind Harmer
0.021
946281AF1-292 GEN
Solar/Wind Harmer
0.578
313526AB2-022
Solar/Wind Harmer
0.694
316321Z2-027
Solar/Wind Harmer
0.693
3146396TANGLEW
Solar/Wind Harmer
0.473
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
316087AB2-174 GEN
Solar/Wind Harmer
3.659
315652AC1-086 GEN
Solar/Wind Harmer
28.827
3151081ELIZAR1
Adder
20.887
3151091ELIZAR2
Adder
20.524
3146486SUNBURY
Solar/Wind Harmer
-0.026
3146486SUNBURY
Solar/Wind Harmer
-0.026
316305AF2-043 C
Solar/Wind Harmer
0.771
315611Z1-036_GEN2
Solar/Wind Harmer
6.305
3152611GOSPORTB
Adder
2.889
3152621GOSPORTC
Adder
2.452
3152601GOSPORTA
Adder
2.262
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.081
3145796HORNRTN
Solar/Wind Harmer
-0.01
3137643SOCKMAN
Solar/Wind Harmer
-0.101
315816AE2-034 GEN
Solar/Wind Harmer
2.05
315607AA1-063A GEN
Solar/Wind Harmer
2.551
3146043SEABORD
Solar/Wind Harmer
-0.025
3130546PLYMOUTH
Solar/Wind Harmer
-0.025
315732AD1-074 GEN1
Solar/Wind Harmer
5.102
315733AD1-074 GEN2
Solar/Wind Harmer
5.102
315735AD1-075 GEN1
Solar/Wind Harmer
2.552
965291AG1-394 GEN
Solar/Wind Harmer
2.237
3146206CASHIE
Solar/Wind Harmer
-0.025
970601AG2-382 GEN
Solar/Wind Harmer
11.025
316318V4-068
Solar/Wind Harmer
0.628
3145893MURPHYS
Solar/Wind Harmer
-0.068
3145893MURPHYS
Solar/Wind Harmer
-0.025
3145513AHOSKIE
Solar/Wind Harmer
0.219
961941AG1-037 GEN
Solar/Wind Harmer
0.189
3145513AHOSKIE
Solar/Wind Harmer
-0.025
3145683EARLEYS
Solar/Wind Harmer
-0.05
3145683EARLEYS
Solar/Wind Harmer
-0.025
3145683EARLEYS
Solar/Wind Harmer
-0.025
315835AF2-110_GEN
Solar/Wind Harmer
3.142
3146033SCOT NK
Solar/Wind Harmer
-0.099
970831AG2-522 GEN
Solar/Wind Harmer
12.462
316005AA1-067
Solar/Wind Harmer
0.494
3145746EVERETS
Solar/Wind Harmer
-0.097
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
3151031BRUNSWICKG2
50/50
4.211
970413AG2-270 GEN
50/50
23.737
3151391GASTONA
50/50
0.617
3151411GASTONB
50/50
0.617
3151101ELIZAR3
50/50
22.447
970917AG2-570 GEN
Solar/Wind Harmer
86.292
316478AD1-087 GEN
Solar/Wind Harmer
2.471
316486AD2-202 GEN
Solar/Wind Harmer
0.724
315773AC2-141 GEN
Solar/Wind Harmer
11.15
316365GEN2_N
Solar/Wind Harmer
1.79
944581AF1-123 GEN
Solar/Wind Harmer
119.802
944601AF1-125 GEN
Solar/Wind Harmer
117.933
3146456SLIGO L269
Solar/Wind Harmer
-0.026
971153AH1-033 GEN
Solar/Wind Harmer
3.15
966621AG1-532 GEN
Solar/Wind Harmer
0.524
316320Y1-086
Solar/Wind Harmer
1.508
3146516WINFALL
Solar/Wind Harmer
-0.026
316435W1029_GEN3
Solar/Wind Harmer
4.638
313506AB2-031 GEN
Solar/Wind Harmer
2.056
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146376EDENTON
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.101
3145796HORNRTN
Solar/Wind Harmer
-0.025
315614AA2-178 GEN
Solar/Wind Harmer
2.733
971157AH1-035 GEN
Solar/Wind Harmer
3.155
315737AD1-076 GEN
Solar/Wind Harmer
4.795
3156081AA2-088 GEN
Solar/Wind Harmer
8.181
3146206CASHIE
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
0.176
3145893MURPHYS
Solar/Wind Harmer
-0.025
3146263WOODLND
Solar/Wind Harmer
-0.025
957521AF2-046 GEN
Solar/Wind Harmer
19.831
961681AG1-008 GEN
Solar/Wind Harmer
19.831
970533AG2-339 GEN
50/50
29.886
970531AG2-338 GEN
50/50
11.954
315242AE2-183_GT2
50/50
5.365
315241AE2-183_GT1
50/50
5.332
972185AH1-677 GEN
50/50
19.342
3151041BRUNSWICKG3
50/50
4.211
972187AH1-678 GEN
50/50
9.663
970933AG2-581 GEN
Solar/Wind Harmer
32.122
970099AG2-077 GEN
Solar/Wind Harmer
37.73
3144356SAPONY
Solar/Wind Harmer
0.991
3145506HICKORY
Solar/Wind Harmer
-0.103
3145506HICKORY
Solar/Wind Harmer
-0.062
3145506HICKORY
Solar/Wind Harmer
-0.015
316185AD1-033 GEN
Solar/Wind Harmer
2.733
316339AD2-160 GEN
Solar/Wind Harmer
1.745
316018AA1-139 ULT2
Solar/Wind Harmer
2.216
316017AA1-139 ULT1
Solar/Wind Harmer
2.093
3137176SLIGO L2192
Solar/Wind Harmer
-0.102
3146456SLIGO L269
Solar/Wind Harmer
3.052
3130086AYDLETT
Solar/Wind Harmer
-0.103
3146386ELIZ CT
Solar/Wind Harmer
-0.026
3142956BIRDNECK
Solar/Wind Harmer
1.38
316316AC1-027 C
Solar/Wind Harmer
0.789
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
316431W1029_GEN1
Solar/Wind Harmer
4.638
316433W1029_GEN2
Solar/Wind Harmer
4.638
316181AB2-040 GEN
Solar/Wind Harmer
3.567
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
315243AE2-183_GT3
50/50
5.365
3151051BRUNSWICKS1
50/50
8.74
3151021BRUNSWICKG1
50/50
4.211
971451AH1-221 GEN
50/50
12.79
3151531CLOVER1
50/50
5.439
3151391GASTONA
50/50
0.617
3151411GASTONB
50/50
0.617
940641AE2-051 GEN
Solar/Wind Harmer
34.798
970919AG2-571 GEN
Solar/Wind Harmer
10.923
970087AG2-069 GEN
Solar/Wind Harmer
32.213
939411AE1-173 GEN
Solar/Wind Harmer
171.7
957481AF2-042 GEN
Solar/Wind Harmer
94.326
315693AD1-088 GEN
Solar/Wind Harmer
13.943
962491AG1-098 GEN
Solar/Wind Harmer
18.368
315687AD1-152 GEN
Solar/Wind Harmer
3.227
316294AC1-161 GEN
Solar/Wind Harmer
8.621
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.015
316036AC1-147 C
Solar/Wind Harmer
0.688
3150991CHESPKB
Adder
2.376
3150991CHESPKB
Adder
2.319
3146376EDENTON
Solar/Wind Harmer
0.755
3146376EDENTON
Solar/Wind Harmer
0.755
3145796HORNRTN
Solar/Wind Harmer
-0.076
3145593CAROLNA
Solar/Wind Harmer
-0.025
3145593CAROLNA
Solar/Wind Harmer
-0.025
966811AG1-552 GEN
Solar/Wind Harmer
2.845
3145593CAROLNA
Solar/Wind Harmer
0.21
316426AA2-053 GEN
Solar/Wind Harmer
2.552
3145783HORNRTN
Solar/Wind Harmer
2.992
3145783HORNRTN
Solar/Wind Harmer
2.394
3145783HORNRTN
Solar/Wind Harmer
0.748
3145783HORNRTN
Solar/Wind Harmer
0.299
316065AD1-022 GEN
Solar/Wind Harmer
12.605
3145893MURPHYS
Solar/Wind Harmer
0.703
3145893MURPHYS
Solar/Wind Harmer
-0.045
3146173TUNIS
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.025
315742AE1-103 GEN
Solar/Wind Harmer
2.631
316274AC1-208 GEN
Solar/Wind Harmer
2.679
3145933PARMELE
Solar/Wind Harmer
-0.049
3145933PARMELE
Solar/Wind Harmer
-0.025
939181AE1-148 GEN
Solar/Wind Harmer
13.708
3145493TOT1
Solar/Wind Harmer
0.376
3145453TOT5
Solar/Wind Harmer
0.226
3145603CNETO
Solar/Wind Harmer
0.151
961601AG1-000A GEN
Solar/Wind Harmer
9.538
316263AC1-034 GEN
Solar/Wind Harmer
11.37
3146843MT LREL
Solar/Wind Harmer
-0.023
3146843MT LREL
Solar/Wind Harmer
-0.023
964791AG1-342 GEN
Solar/Wind Harmer
4.916
962561AG1-105 GEN
Solar/Wind Harmer
12.943
313527AB2-043 GEN
Solar/Wind Harmer
3.735
316222AC1-221 GEN
Solar/Wind Harmer
2.263
970657AG2-426 GEN
Solar/Wind Harmer
6.965
970657AG2-426 GEN
Solar/Wind Harmer
1.456
316236AE1-162_GEN
Solar/Wind Harmer
0.669
971741AH1-377 GEN
Solar/Wind Harmer
25.152
970323AG2-213 GEN
Solar/Wind Harmer
10.321
971775AH1-396 GEN
Solar/Wind Harmer
1.47
316034AC1-036 C
Solar/Wind Harmer
0.383
970301AG2-198 GEN
Solar/Wind Harmer
9.888
3144293JTRSVLE
Adder
0.527
3144293JTRSVLE
Adder
0.444
944641AF1-129 GEN
Adder
54.839
316447AC1-158 HLD
Solar/Wind Helper
2.734
3145746EVERETS
Solar/Wind Harmer
-0.024
970181AG2-120 GEN
Solar/Wind Harmer
3.208
316319Z2-044 C
Solar/Wind Harmer
1.348
957861AF2-080 GEN
Solar/Wind Harmer
10.667
316420AA1-050 GEN
Solar/Wind Harmer
2.781
3145573BETHELC
Solar/Wind Harmer
-0.024
3145573BETHELC
Solar/Wind Harmer
-0.024
316311AC2-079 GEN
Solar/Wind Harmer
12.096
315833AF1-017_GEN
Solar/Wind Harmer
4.55
316349AD2-085 GEN
Solar/Wind Harmer
2.131
316239AB2-077_GEN
Solar/Wind Harmer
0.695
316238AB2-078_GEN
Solar/Wind Harmer
0.695
3147173SINAI
Solar/Wind Harmer
-0.023
3147243WELCO
Solar/Wind Harmer
-0.014
316118AC1-105 GEN
Solar/Wind Harmer
1.583
3143316POE
Solar/Wind Harmer
-0.09
971445AH1-216 GEN
Solar/Wind Harmer
13.611
971443AH1-215 GEN
Solar/Wind Harmer
4.082
3144303KENBRDG
Solar/Wind Harmer
-0.016
972265AH1-717 GEN
Adder
13.901
3151201GRAVEL4
Adder
13.031
3151191GRAVEL3
Adder
12.866
3151211GRAVEL5
Adder
12.866
970683AG2-441 GEN
Solar/Wind Harmer
15.31
970681AG2-440 GEN
Solar/Wind Harmer
12.248
970865AG2-541 GEN
Solar/Wind Harmer
7.877
270455AD2-022 GEN
Solar/Wind Harmer
3.414
270457AD2-023 GEN
Solar/Wind Harmer
1.731
3146173TUNIS
Solar/Wind Harmer
-0.025
3156021HOLLOMANSOL
Solar/Wind Harmer
3.39
3145273HOLLAND
Solar/Wind Harmer
-0.019
316463AE2-346 GEN
Solar/Wind Harmer
0.407
316140AB2-099
Solar/Wind Harmer
0.17
962331AG1-082 GEN
Solar/Wind Harmer
3.145
316317KELFORD C
Solar/Wind Harmer
1.18
3145823KELFORD
Solar/Wind Harmer
-0.025
3147043LAWRENC
Solar/Wind Harmer
-0.015
3145963POPLR C
Solar/Wind Harmer
-0.025
316210AC1-098 GEN
Solar/Wind Harmer
3.898
315724AD1-057 GEN
Solar/Wind Harmer
1.426
3145933PARMELE
Solar/Wind Harmer
-0.025
966801AG1-551 GEN
Solar/Wind Harmer
3.071
3144536CHRHLND
Solar/Wind Harmer
-0.004
316327AA2-057 GEN
Solar/Wind Harmer
2.481
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
3146233WITAKRS
Solar/Wind Harmer
0.511
3146233WITAKRS
Solar/Wind Harmer
-0.016
3138543CONSLDL
Solar/Wind Harmer
-0.016
3146073TAR RVR
Solar/Wind Harmer
-0.024
3146083TARBORO
Solar/Wind Harmer
-0.024
961601AG1-000A GEN
Solar/Wind Harmer
9.659
3145543BTLEBRO
Solar/Wind Harmer
-0.024
3145543BTLEBRO
Solar/Wind Harmer
-0.024
316248AF1-058 C
Solar/Wind Harmer
0.694
960061AF2-297 GEN
Solar/Wind Harmer
11.515
316131AB2-060 GEN
Solar/Wind Harmer
2.463
970661AG2-428 GEN
Solar/Wind Harmer
4.26
316283AC2-100 C
Solar/Wind Harmer
2.097
3145336SMITFLD
Solar/Wind Harmer
-0.009
964241AG1-285 GEN
Solar/Wind Harmer
17.312
316083AB2-161 GEN
Solar/Wind Harmer
3.584
970659AG2-427 GEN
Solar/Wind Harmer
2.061
315785AD2-033 C
Solar/Wind Harmer
4.772
315813AE1-149 C
Solar/Wind Harmer
13.059
970257AG2-171 GEN
Solar/Wind Harmer
7.741
971683AH1-343 GEN
Solar/Wind Harmer
8.872
959311AF2-222 GEN
Solar/Wind Harmer
21.233
3151221GRAVEL6
Adder
13.016
3151171GRAVELC
Adder
2.504
970909AG2-566 GEN
Solar/Wind Harmer
1.877
3144216WINCHST
Adder
0.639
3150921YORKTN3
Adder
4.218
3144293JTRSVLE
Adder
0.527
316044AC1-158 PL1
Solar/Wind Helper
1.242
316450AC1-158 RIC
Solar/Wind Helper
0.331
961611AG1-000B GEN
Solar/Wind Harmer
0.889
316023GEN1_S
Solar/Wind Harmer
1.79
944591AF1-124 GEN
Solar/Wind Harmer
120.234
316388AE2-253 GEN
Solar/Wind Harmer
1.745
3146456SLIGO L269
Solar/Wind Harmer
-0.026
960081AF2-299 GEN
Solar/Wind Harmer
2.906
316011AB1-132 GEN
Solar/Wind Harmer
5.361
962571AG1-106 GEN
Solar/Wind Harmer
3.683
3146516WINFALL
Solar/Wind Harmer
-0.082
3146516WINFALL
Solar/Wind Harmer
-0.026
316246AF1-032 C
Solar/Wind Harmer
0.518
315800Z1-036_GEN1
Solar/Wind Harmer
6.305
316375AC2-012 GEN
Solar/Wind Harmer
8.82
3150981CHESPKA
Adder
2.832
3130156CHOWAN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.083
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145663CRESWEL
Solar/Wind Harmer
-0.071
971163AH1-040 GEN
Solar/Wind Harmer
23.751
316190AA2-174 GEN
Solar/Wind Harmer
0.31
971795AH1-408 GEN
Solar/Wind Harmer
18.929
3145783HORNRTN
Solar/Wind Harmer
-0.025
3146206CASHIE
Solar/Wind Harmer
-0.025
971547AH1-271 GEN
Solar/Wind Harmer
6.3
3145893MURPHYS
Solar/Wind Harmer
-0.1
3145893MURPHYS
Solar/Wind Harmer
0.747
3146263WOODLND
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.025
3145683EARLEYS
Solar/Wind Harmer
-0.025
316093AE2-104_GEN
Solar/Wind Harmer
7.308
3145823KELFORD
Solar/Wind Harmer
-0.025
3147043LAWRENC
Adder
2.01
316129AC1-054 GEN
Solar/Wind Harmer
2.182
3145963POPLR C
Solar/Wind Harmer
-0.025
971065AG2-659 GEN
Solar/Wind Harmer
12.425
316212AC1-099_GEN
Solar/Wind Harmer
2.165
316174AB2-169 GEN
Solar/Wind Harmer
3.827
315722AD1-056 GEN
Solar/Wind Harmer
2.593
3146293MARTNCO
Solar/Wind Harmer
0.152
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
3146233WITAKRS
Solar/Wind Harmer
-0.097
316494AC1-189 GEN
Solar/Wind Harmer
2.623
961671AG1-007 GEN
Solar/Wind Harmer
0.308
3146083TARBORO
Solar/Wind Harmer
-0.024
3145493TOT1
Solar/Wind Harmer
0.722
316359AB2-059 GEN
Solar/Wind Harmer
3.27
316049AB1-081 GEN
Solar/Wind Harmer
2.617
3142053HEARTS
Solar/Wind Harmer
0.285
3145543BTLEBRO
Solar/Wind Harmer
-0.024
3145543BTLEBRO
Solar/Wind Harmer
-0.019
316072AD1-144
Solar/Wind Harmer
0.489
316237AB2-079_GEN
Solar/Wind Harmer
0.695
970401AG2-262 GEN
Solar/Wind Harmer
1.502
970661AG2-428 GEN
Solar/Wind Harmer
24.038
3145336SMITFLD
Solar/Wind Harmer
-0.088
316381AD1-082 GEN
Solar/Wind Harmer
2.025
970659AG2-427 GEN
Solar/Wind Harmer
11.632
316003AC1-222 GEN
Solar/Wind Harmer
2.12
3151171GRAVELC
Adder
1.904
970685AG2-442 GEN
Solar/Wind Harmer
17.147
3138126ROCKLANDING
Solar/Wind Harmer
0.058
3144293JTRSVLE
Adder
0.527
3143226MDLTHAN
Solar/Wind Helper
0.287
316045AC1-158 PL2
Solar/Wind Helper
3.977
961611AG1-000B GEN
Solar/Wind Harmer
2.084
LAGNLTFEXP_LAGN->PJM
CLTF
10.658
CBM South 2LTFEXP_CBM-S2->PJM
CBM
36.715
TVALTFEXP_TVA->PJM
CLTF
5.269
CPLELTFEXP_CPLE->PJM
CLTF
15.822
CBM West 2LTFEXP_CBM-W2->PJM
CBM
53.369
CBM West 1LTFEXP_CBM-W1->PJM
CBM
27.217
CBM South 1LTFEXP_CBM-S1->PJM
CBM
17.694
MECLTFEXP_MEC->PJM
CLTF
4.528
SIGELTFEXP_SIGE->PJM
CLTF
0.13
NYPJM->LTFIMP_NY
CLTF
2.139
LGEELTFEXP_LGEE->PJM
CLTF
1.496
WECLTFEXP_WEC->PJM
CLTF
0.787

Details for 8HERITAGE-8RAWLINGS 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
8HERITAGE-8RAWLINGS 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 585_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.18 %
Rating:4124.72 MVA
Rating Type:B
MVA to Mitigate:4338.48
MW Contribution:32.62
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
10.742
970917AG2-570 GEN
Solar/Wind Harmer
67.092
316283AC2-100 C
Solar/Wind Harmer
0.248
315773AC2-141 GEN
Solar/Wind Helper
5.724
3144873MCLAUGH
Solar/Wind Helper
0.006
3144536CHRHLND
Solar/Wind Helper
0.037
315839AE2-212 C
Solar/Wind Helper
0.326
3145336SMITFLD
Solar/Wind Helper
0.096
316478AD1-087 GEN
Solar/Wind Helper
1.138
316486AD2-202 GEN
Solar/Wind Helper
0.333
316382AG1-145 C
Solar/Wind Helper
0.309
3146456SLIGO L269
Solar/Wind Helper
0.226
3151051BRUNSWICKS1
50/50
22.294
3151021BRUNSWICKG1
50/50
10.742
971451AH1-221 GEN
50/50
32.625
315243AE2-183_GT3
50/50
13.474
971629AH1-314 GEN
50/50
11.242
970919AG2-571 GEN
Solar/Wind Harmer
26.837
970087AG2-069 GEN
Solar/Wind Harmer
59.841
316294AC1-161 GEN
Solar/Wind Helper
4.863
316375AC2-012 GEN
Solar/Wind Helper
0.64
3145336SMITFLD
Solar/Wind Helper
0.956
316381AD1-082 GEN
Solar/Wind Helper
1.204
316388AE2-253 GEN
Solar/Wind Helper
0.879
316458AB2-190 GEN2
Solar/Wind Helper
1.317
316159AE1-175 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.258
3146456SLIGO L269
Solar/Wind Helper
0.226
316246AF1-032 C
Solar/Wind Helper
0.255
963041AG1-153 GEN
50/50
21.75
315244AE2-183_ST
50/50
23.295
970673AG2-436 GEN
Solar/Wind Harmer
173.991
970673AG2-436 GEN
Solar/Wind Harmer
115.994
941031AE2-094 GEN
Solar/Wind Harmer
150.205
944011AF1-069 GEN
Solar/Wind Harmer
49.078
970085AG2-068 GEN
Solar/Wind Harmer
39.894
970581AG2-369 GEN
Solar/Wind Harmer
34.309
3143316POE
Solar/Wind Helper
1.005
316369SG1_INVT
Solar/Wind Helper
1.116
316132AB2-190 GEN1
Solar/Wind Helper
1.317
957831AF2-077 GEN
Solar/Wind Helper
0.307
319010AE1-072 C
Solar/Wind Helper
2.564
316305AF2-043 C
Solar/Wind Helper
0.3
3151041BRUNSWICKG3
50/50
10.742
972187AH1-678 GEN
50/50
24.65
315242AE2-183_GT2
50/50
13.474
315241AE2-183_GT1
50/50
13.391
972185AH1-677 GEN
50/50
48.574
970533AG2-339 GEN
50/50
72.493
970531AG2-338 GEN
50/50
28.997
316222AC1-221 GEN
Solar/Wind Harmer
0.514
316036AC1-147 C
Solar/Wind Helper
0.372
316316AC1-027 C
Solar/Wind Helper
0.382
3142956BIRDNECK
Solar/Wind Helper
0.163
316185AD1-033 GEN
Solar/Wind Helper
1.132
316236AE1-162_GEN
Solar/Wind Helper
0.321
3145506HICKORY
Solar/Wind Helper
0.948
3145506HICKORY
Solar/Wind Helper
0.569
3145506HICKORY
Solar/Wind Helper
0.142
316240AF1-291 C
Solar/Wind Helper
0.315
316033AB2-134 GEN
Solar/Wind Helper
0.798
315697AD1-025 GEN
Solar/Wind Helper
2.652
316339AD2-160 GEN
Solar/Wind Helper
0.879
316018AA1-139 ULT2
Solar/Wind Helper
0.985
316017AA1-139 ULT1
Solar/Wind Helper
1.047
3137176SLIGO L2192
Solar/Wind Helper
0.9
3130086AYDLETT
Solar/Wind Helper
0.893
LAGNLTFEXP_LAGN->PJM
CLTF
11.909
CBM South 2LTFEXP_CBM-S2->PJM
CBM
37.406
TVALTFEXP_TVA->PJM
CLTF
5.902
CPLELTFEXP_CPLE->PJM
CLTF
16.693
CBM West 2LTFEXP_CBM-W2->PJM
CBM
62.053
CBM West 1LTFEXP_CBM-W1->PJM
CBM
36.883
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.119
MECLTFEXP_MEC->PJM
CLTF
5.643
SIGELTFEXP_SIGE->PJM
CLTF
0.166
NYPJM->LTFIMP_NY
CLTF
1.845
LGEELTFEXP_LGEE->PJM
CLTF
1.979
WECLTFEXP_WEC->PJM
CLTF
1.044

Details for 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:127.08 %
Rating:1057.5 MVA
Rating Type:B
MVA to Mitigate:1343.9
MW Contribution:5.44
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
2.294
3151051BRUNSWICKS1
50/50
3.716
3151021BRUNSWICKG1
50/50
1.791
971451AH1-221 GEN
50/50
5.439
3151531CLOVER1
50/50
2.053
3151391GASTONA
50/50
0.214
3151411GASTONB
50/50
0.214
940641AE2-051 GEN
Solar/Wind Harmer
11.353
970919AG2-571 GEN
Solar/Wind Harmer
4.592
970087AG2-069 GEN
Solar/Wind Harmer
10.271
939411AE1-173 GEN
Solar/Wind Harmer
54.111
957481AF2-042 GEN
Solar/Wind Harmer
27.71
315693AD1-088 GEN
Solar/Wind Harmer
4.301
315687AD1-152 GEN
Solar/Wind Harmer
0.003
316294AC1-161 GEN
Solar/Wind Harmer
1.513
962491AG1-098 GEN
Solar/Wind Harmer
4.96
944591AF1-124 GEN
Solar/Wind Harmer
18.908
316023GEN1_S
Solar/Wind Harmer
0.183
316388AE2-253 GEN
Solar/Wind Harmer
0.253
3146456SLIGO L269
Solar/Wind Harmer
0.08
3146516WINFALL
Solar/Wind Harmer
0.257
3146516WINFALL
Solar/Wind Harmer
0.079
316011AB1-132 GEN
Solar/Wind Harmer
1.438
962571AG1-106 GEN
Solar/Wind Harmer
1.125
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.079
316246AF1-032 C
Solar/Wind Harmer
0.035
3145796HORNRTN
Solar/Wind Harmer
0.259
3145796HORNRTN
Solar/Wind Harmer
0.079
960081AF2-299 GEN
Solar/Wind Harmer
0.754
3145663CRESWEL
Solar/Wind Harmer
0.22
971163AH1-040 GEN
Solar/Wind Harmer
6.276
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
0.974
3146206CASHIE
Solar/Wind Harmer
0.078
971547AH1-271 GEN
Solar/Wind Harmer
1.663
316190AA2-174 GEN
Solar/Wind Harmer
0
3146263WOODLND
Solar/Wind Harmer
0.078
3145683EARLEYS
Solar/Wind Harmer
0.078
3145783HORNRTN
Solar/Wind Harmer
0.077
3145823KELFORD
Solar/Wind Harmer
0.077
3146173TUNIS
Solar/Wind Harmer
0.077
3145963POPLR C
Solar/Wind Harmer
0.077
3145893MURPHYS
Solar/Wind Harmer
0.308
3145893MURPHYS
Solar/Wind Harmer
0.342
315722AD1-056 GEN
Solar/Wind Harmer
0.488
316174AB2-169 GEN
Solar/Wind Harmer
0.002
316212AC1-099_GEN
Solar/Wind Harmer
0.398
3146293MARTNCO
Solar/Wind Harmer
0.071
316129AC1-054 GEN
Solar/Wind Harmer
0.286
3145746EVERETS
Solar/Wind Harmer
0.076
3145746EVERETS
Solar/Wind Harmer
0.076
3146233WITAKRS
Solar/Wind Harmer
0.302
971065AG2-659 GEN
Solar/Wind Harmer
3.242
316494AC1-189 GEN
Solar/Wind Harmer
0.256
961671AG1-007 GEN
Solar/Wind Harmer
0.012
3146083TARBORO
Solar/Wind Harmer
0.076
3145493TOT1
Solar/Wind Harmer
0.337
316359AB2-059 GEN
Solar/Wind Harmer
0.272
316049AB1-081 GEN
Solar/Wind Harmer
0.433
3142053HEARTS
Solar/Wind Harmer
0.133
3145543BTLEBRO
Solar/Wind Harmer
0.076
3145543BTLEBRO
Solar/Wind Harmer
0.06
971795AH1-408 GEN
Solar/Wind Harmer
5.038
316093AE2-104_GEN
Solar/Wind Harmer
1.261
3147043LAWRENC
Adder
0.671
316072AD1-144
Solar/Wind Harmer
0.025
970401AG2-262 GEN
Solar/Wind Harmer
0.405
316003AC1-222 GEN
Solar/Wind Harmer
0.002
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3143226MDLTHAN
Solar/Wind Helper
0.68
3143526WINTERP
Solar/Wind Helper
2.674
316336AC2-165 C
Solar/Wind Helper
2.289
3142543TWELFTH
Solar/Wind Helper
0.016
315244AE2-183_ST
50/50
3.966
963041AG1-153 GEN
50/50
3.626
3151541CLOVER2
50/50
2.044
315779AE2-040
50/50
1.222
941031AE2-094 GEN
Solar/Wind Harmer
26.792
944011AF1-069 GEN
Solar/Wind Harmer
8.754
970673AG2-436 GEN
Solar/Wind Harmer
30.101
970673AG2-436 GEN
Solar/Wind Harmer
20.067
971967AH1-528 GEN
Solar/Wind Harmer
21.652
970085AG2-068 GEN
Solar/Wind Harmer
6.847
970581AG2-369 GEN
Solar/Wind Harmer
5.888
316315AB2-025 C
Solar/Wind Harmer
0.071
315814AE2-033 C
Solar/Wind Harmer
6.9
957871AF2-081 GEN
Solar/Wind Harmer
4.015
319010AE1-072 C
Solar/Wind Harmer
0.405
3146406KITTY HAWK
Solar/Wind Harmer
0.01
313526AB2-022
Solar/Wind Harmer
0.043
316321Z2-027
Solar/Wind Harmer
0.015
3145176PASQUOTANK
Solar/Wind Harmer
0.049
3146396TANGLEW
Solar/Wind Harmer
0.22
315652AC1-086 GEN
Solar/Wind Harmer
8.7
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3146486SUNBURY
Solar/Wind Harmer
0.079
3146486SUNBURY
Solar/Wind Harmer
0.079
3130156CHOWAN
Solar/Wind Harmer
0.079
3130156CHOWAN
Solar/Wind Harmer
0.079
3151081ELIZAR1
Adder
7.217
3151091ELIZAR2
Adder
7.092
316305AF2-043 C
Solar/Wind Harmer
0.001
3145796HORNRTN
Solar/Wind Harmer
0.251
3145796HORNRTN
Solar/Wind Harmer
0.031
315816AE2-034 GEN
Solar/Wind Harmer
0.337
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3130546PLYMOUTH
Solar/Wind Harmer
0.078
315732AD1-074 GEN1
Solar/Wind Harmer
0.449
315733AD1-074 GEN2
Solar/Wind Harmer
0.449
315735AD1-075 GEN1
Solar/Wind Harmer
0.225
3152611GOSPORTB
Adder
0.993
3152621GOSPORTC
Adder
0.843
3152601GOSPORTA
Adder
0.777
3146206CASHIE
Solar/Wind Harmer
0.078
970601AG2-382 GEN
Solar/Wind Harmer
2.911
3137643SOCKMAN
Solar/Wind Harmer
0.311
3145683EARLEYS
Solar/Wind Harmer
0.155
3145683EARLEYS
Solar/Wind Harmer
0.078
3145683EARLEYS
Solar/Wind Harmer
0.078
3145513AHOSKIE
Solar/Wind Harmer
0.162
3145513AHOSKIE
Solar/Wind Harmer
0.077
315607AA1-063A GEN
Solar/Wind Harmer
0.158
3146043SEABORD
Solar/Wind Harmer
0.077
3146033SCOT NK
Solar/Wind Harmer
0.308
3145893MURPHYS
Solar/Wind Harmer
0.208
3145893MURPHYS
Solar/Wind Harmer
0.077
965291AG1-394 GEN
Solar/Wind Harmer
0.341
970831AG2-522 GEN
Solar/Wind Harmer
3.254
316005AA1-067
Solar/Wind Harmer
0.082
3145746EVERETS
Solar/Wind Harmer
0.302
3145746EVERETS
Solar/Wind Harmer
0.076
3145746EVERETS
Solar/Wind Harmer
0.076
3145746EVERETS
Solar/Wind Harmer
0.076
970181AG2-120 GEN
Solar/Wind Harmer
0.946
316319Z2-044 C
Solar/Wind Harmer
0
957861AF2-080 GEN
Solar/Wind Harmer
3.273
316420AA1-050 GEN
Solar/Wind Harmer
0.002
3145573BETHELC
Solar/Wind Harmer
0.076
3145573BETHELC
Solar/Wind Harmer
0.076
315835AF2-110_GEN
Solar/Wind Harmer
0.515
3147173SINAI
Solar/Wind Harmer
0.072
3147243WELCO
Solar/Wind Harmer
0.045
316118AC1-105 GEN
Solar/Wind Harmer
0.183
316311AC2-079 GEN
Solar/Wind Harmer
1.874
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.045
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
970865AG2-541 GEN
Solar/Wind Harmer
2.076
316233AE1-074 FULL
Solar/Wind Helper
0.785
270494AE1-108_GEN
Solar/Wind Helper
1.529
970533AG2-339 GEN
50/50
12.931
970531AG2-338 GEN
50/50
5.172
315242AE2-183_GT2
50/50
2.294
315241AE2-183_GT1
50/50
2.28
972185AH1-677 GEN
50/50
8.27
3151041BRUNSWICKG3
50/50
1.791
972187AH1-678 GEN
50/50
4.109
970933AG2-581 GEN
Solar/Wind Harmer
10.096
970099AG2-077 GEN
Solar/Wind Harmer
11.084
3144356SAPONY
Solar/Wind Harmer
0.732
3145506HICKORY
Solar/Wind Harmer
0.323
3145506HICKORY
Solar/Wind Harmer
0.194
3145506HICKORY
Solar/Wind Harmer
0.049
316185AD1-033 GEN
Solar/Wind Harmer
0.002
316339AD2-160 GEN
Solar/Wind Harmer
0.131
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.045
3137176SLIGO L2192
Solar/Wind Harmer
0.32
3146456SLIGO L269
Solar/Wind Harmer
1.425
3130086AYDLETT
Solar/Wind Harmer
0.322
3146386ELIZ CT
Solar/Wind Harmer
0.08
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.076
3146516WINFALL
Solar/Wind Harmer
0.079
3146516WINFALL
Solar/Wind Harmer
0.079
3146516WINFALL
Solar/Wind Harmer
0.079
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3146626S HERTFORD
Solar/Wind Harmer
0.079
3146626S HERTFORD
Solar/Wind Harmer
0.079
3142666NORTHAMPTON
Solar/Wind Harmer
0.079
3142666NORTHAMPTON
Solar/Wind Harmer
0.079
3142666NORTHAMPTON
Solar/Wind Harmer
0.079
3142666NORTHAMPTON
Solar/Wind Harmer
0.047
3146376EDENTON
Solar/Wind Harmer
0.35
3146376EDENTON
Solar/Wind Harmer
0.35
3145796HORNRTN
Solar/Wind Harmer
0.236
316181AB2-040 GEN
Solar/Wind Harmer
0.113
316065AD1-022 GEN
Solar/Wind Harmer
3.592
316036AC1-147 C
Solar/Wind Harmer
0.014
3150991CHESPKB
Adder
0.817
3150991CHESPKB
Adder
0.797
3145593CAROLNA
Solar/Wind Harmer
0.078
3145593CAROLNA
Solar/Wind Harmer
0.078
966811AG1-552 GEN
Solar/Wind Harmer
0.842
3145593CAROLNA
Solar/Wind Harmer
0.097
316426AA2-053 GEN
Solar/Wind Harmer
0.262
3145783HORNRTN
Solar/Wind Harmer
1.378
3145783HORNRTN
Solar/Wind Harmer
1.102
3145783HORNRTN
Solar/Wind Harmer
0.345
3145783HORNRTN
Solar/Wind Harmer
0.138
3146173TUNIS
Solar/Wind Harmer
0.077
3146173TUNIS
Solar/Wind Harmer
0.077
3145893MURPHYS
Solar/Wind Harmer
0.515
3145893MURPHYS
Solar/Wind Harmer
0.139
316274AC1-208 GEN
Solar/Wind Harmer
0.399
3145933PARMELE
Solar/Wind Harmer
0.153
3145933PARMELE
Solar/Wind Harmer
0.076
3145493TOT1
Solar/Wind Harmer
0.176
3145453TOT5
Solar/Wind Harmer
0.105
3145603CNETO
Solar/Wind Harmer
0.07
315742AE1-103 GEN
Solar/Wind Harmer
0.001
961601AG1-000A GEN
Solar/Wind Harmer
1.347
316263AC1-034 GEN
Solar/Wind Harmer
2.877
939181AE1-148 GEN
Solar/Wind Harmer
3.519
316222AC1-221 GEN
Solar/Wind Harmer
0.294
3146843MT LREL
Solar/Wind Harmer
0.069
3146843MT LREL
Solar/Wind Harmer
0.069
964791AG1-342 GEN
Solar/Wind Harmer
1.325
962561AG1-105 GEN
Solar/Wind Harmer
3.278
313527AB2-043 GEN
Solar/Wind Harmer
0.001
3143526WINTERP
Solar/Wind Helper
2.674
966871AG1-558 GEN
Solar/Wind Helper
0.173
315821AE2-092 GEN
Solar/Wind Helper
1.114
3151031BRUNSWICKG2
50/50
1.791
970413AG2-270 GEN
50/50
8.961
3151391GASTONA
50/50
0.214
3151411GASTONB
50/50
0.214
3151101ELIZAR3
50/50
7.756
970917AG2-570 GEN
Solar/Wind Harmer
11.479
316478AD1-087 GEN
Solar/Wind Harmer
0.335
316486AD2-202 GEN
Solar/Wind Harmer
0.098
315773AC2-141 GEN
Solar/Wind Harmer
3.189
944581AF1-123 GEN
Solar/Wind Harmer
18.841
944601AF1-125 GEN
Solar/Wind Harmer
18.551
316365GEN2_N
Solar/Wind Harmer
0.183
3146456SLIGO L269
Solar/Wind Harmer
0.08
971153AH1-033 GEN
Solar/Wind Harmer
0.931
316320Y1-086
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.079
316435W1029_GEN3
Solar/Wind Harmer
0
3146626S HERTFORD
Solar/Wind Harmer
0.079
3142666NORTHAMPTON
Solar/Wind Harmer
0.079
3146376EDENTON
Solar/Wind Harmer
0.079
3145796HORNRTN
Solar/Wind Harmer
0.314
3145796HORNRTN
Solar/Wind Harmer
0.079
315614AA2-178 GEN
Solar/Wind Harmer
0.449
971157AH1-035 GEN
Solar/Wind Harmer
0.938
313506AB2-031 GEN
Solar/Wind Harmer
0.241
315737AD1-076 GEN
Solar/Wind Harmer
1.005
3144873MCLAUGH
Solar/Wind Harmer
0.002
3146206CASHIE
Solar/Wind Harmer
0.078
3156021HOLLOMANSOL
Solar/Wind Harmer
0.353
3146263WOODLND
Solar/Wind Harmer
0.078
316463AE2-346 GEN
Solar/Wind Harmer
0.067
316140AB2-099
Solar/Wind Harmer
0.028
962331AG1-082 GEN
Solar/Wind Harmer
0.826
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.077
3146173TUNIS
Solar/Wind Harmer
0.077
3145963POPLR C
Solar/Wind Harmer
0.077
957521AF2-046 GEN
Solar/Wind Harmer
5.738
961681AG1-008 GEN
Solar/Wind Harmer
5.738
3145893MURPHYS
Solar/Wind Harmer
0.129
3145893MURPHYS
Solar/Wind Harmer
0.077
315724AD1-057 GEN
Solar/Wind Harmer
0.289
316210AC1-098 GEN
Solar/Wind Harmer
0.713
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3145933PARMELE
Solar/Wind Harmer
0.076
966801AG1-551 GEN
Solar/Wind Harmer
0.89
316327AA2-057 GEN
Solar/Wind Harmer
0.115
3145746EVERETS
Solar/Wind Harmer
0.076
3145746EVERETS
Solar/Wind Harmer
0.076
3146233WITAKRS
Solar/Wind Harmer
0.381
3146233WITAKRS
Solar/Wind Harmer
0.052
3138543CONSLDL
Solar/Wind Harmer
0.05
3146073TAR RVR
Solar/Wind Harmer
0.076
3146083TARBORO
Solar/Wind Harmer
0.076
961601AG1-000A GEN
Solar/Wind Harmer
5.386
971623AH1-311 GEN
Solar/Wind Harmer
0.151
3145543BTLEBRO
Solar/Wind Harmer
0.076
3145543BTLEBRO
Solar/Wind Harmer
0.076
3145273HOLLAND
Solar/Wind Harmer
0.057
3147043LAWRENC
Solar/Wind Harmer
0.045
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.092
3144536CHRHLND
Solar/Wind Harmer
0.011
316283AC2-100 C
Solar/Wind Harmer
0.138
971683AH1-343 GEN
Solar/Wind Harmer
2.355
316131AB2-060 GEN
Solar/Wind Harmer
0.198
964241AG1-285 GEN
Solar/Wind Harmer
3.891
316313AB2-026
Solar/Wind Helper
0.727
316258AE1-075 C
Solar/Wind Helper
0.654
316405AF2-144 C
Solar/Wind Helper
0.545
316473AC1-191 GEN
Solar/Wind Helper
0.782
LAGNLTFEXP_LAGN->PJM
CLTF
3.43
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.518
TVALTFEXP_TVA->PJM
CLTF
1.701
CPLELTFEXP_CPLE->PJM
CLTF
5.449
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.56
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.686
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.763
MECLTFEXP_MEC->PJM
CLTF
1.546
SIGELTFEXP_SIGE->PJM
CLTF
0.045
NYPJM->LTFIMP_NY
CLTF
0.638
LGEELTFEXP_LGEE->PJM
CLTF
0.533
WECLTFEXP_WEC->PJM
CLTF
0.278

Details for 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: WT576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-2: WT576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:122.5 %
Rating:1265.1 MVA
Rating Type:C
MVA to Mitigate:1549.8
MW Contribution:5.44
Bus #Bus NameTypeMW Contribution
315244AE2-183_ST
50/50
3.966
963041AG1-153 GEN
50/50
3.626
941031AE2-094 GEN
Solar/Wind Harmer
30.645
944011AF1-069 GEN
Solar/Wind Harmer
9.602
970673AG2-436 GEN
Solar/Wind Harmer
33.304
970673AG2-436 GEN
Solar/Wind Harmer
16.863
970533AG2-339 GEN
50/50
12.93
970531AG2-338 GEN
50/50
5.172
315242AE2-183_GT2
50/50
2.294
315241AE2-183_GT1
50/50
2.28
972185AH1-677 GEN
50/50
8.27
3151041BRUNSWICKG3
50/50
1.791
972187AH1-678 GEN
50/50
4.109
970933AG2-581 GEN
Solar/Wind Harmer
13.293
970099AG2-077 GEN
Solar/Wind Harmer
14.593
3144356SAPONY
Solar/Wind Harmer
0.343
3145506HICKORY
Solar/Wind Harmer
-0.036
3145506HICKORY
Solar/Wind Harmer
-0.022
3145506HICKORY
Solar/Wind Harmer
-0.005
316185AD1-033 GEN
Solar/Wind Harmer
0.958
316339AD2-160 GEN
Solar/Wind Harmer
0.612
316018AA1-139 ULT2
Solar/Wind Harmer
0.776
316017AA1-139 ULT1
Solar/Wind Harmer
0.733
3137176SLIGO L2192
Solar/Wind Harmer
-0.036
3146456SLIGO L269
Solar/Wind Harmer
1.069
3130086AYDLETT
Solar/Wind Harmer
-0.036
3146386ELIZ CT
Solar/Wind Harmer
-0.009
3142956BIRDNECK
Solar/Wind Harmer
0.48
316316AC1-027 C
Solar/Wind Harmer
0.274
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
316431W1029_GEN1
Solar/Wind Harmer
1.613
316433W1029_GEN2
Solar/Wind Harmer
1.613
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3146376EDENTON
Solar/Wind Harmer
0.263
3146376EDENTON
Solar/Wind Harmer
0.263
3145796HORNRTN
Solar/Wind Harmer
-0.026
316181AB2-040 GEN
Solar/Wind Harmer
1.224
316065AD1-022 GEN
Solar/Wind Harmer
4.383
316036AC1-147 C
Solar/Wind Harmer
0.236
3150991CHESPKB
Adder
0.817
3150991CHESPKB
Adder
0.797
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
0.981
3145593CAROLNA
Solar/Wind Harmer
0.072
316426AA2-053 GEN
Solar/Wind Harmer
0.881
3145783HORNRTN
Solar/Wind Harmer
1.034
3145783HORNRTN
Solar/Wind Harmer
0.827
3145783HORNRTN
Solar/Wind Harmer
0.258
3145783HORNRTN
Solar/Wind Harmer
0.103
3146173TUNIS
Solar/Wind Harmer
-0.009
3146173TUNIS
Solar/Wind Harmer
-0.009
3145893MURPHYS
Solar/Wind Harmer
0.241
3145893MURPHYS
Solar/Wind Harmer
-0.016
316274AC1-208 GEN
Solar/Wind Harmer
0.931
3145933PARMELE
Solar/Wind Harmer
-0.017
971967AH1-528 GEN
Solar/Wind Harmer
28.583
970085AG2-068 GEN
Solar/Wind Harmer
9.015
970581AG2-369 GEN
Solar/Wind Harmer
7.753
316315AB2-025 C
Solar/Wind Harmer
0.265
315814AE2-033 C
Solar/Wind Harmer
9.126
957871AF2-081 GEN
Solar/Wind Harmer
4.531
319010AE1-072 C
Solar/Wind Harmer
1.83
3146406KITTY HAWK
Solar/Wind Harmer
0.008
313526AB2-022
Solar/Wind Harmer
0.242
316321Z2-027
Solar/Wind Harmer
0.242
3146396TANGLEW
Solar/Wind Harmer
0.165
3145176PASQUOTANK
Solar/Wind Harmer
-0.006
315652AC1-086 GEN
Solar/Wind Harmer
10.001
315611Z1-036_GEN2
Solar/Wind Harmer
2.194
3146486SUNBURY
Solar/Wind Harmer
-0.009
3146486SUNBURY
Solar/Wind Harmer
-0.009
3130156CHOWAN
Solar/Wind Harmer
-0.009
3130156CHOWAN
Solar/Wind Harmer
-0.009
3151081ELIZAR1
Adder
7.217
3151091ELIZAR2
Adder
7.092
316305AF2-043 C
Solar/Wind Harmer
0.266
3145796HORNRTN
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.003
946281AF1-292 GEN
Solar/Wind Harmer
0.198
315816AE2-034 GEN
Solar/Wind Harmer
0.713
316087AB2-174 GEN
Solar/Wind Harmer
1.254
3130546PLYMOUTH
Solar/Wind Harmer
-0.009
315732AD1-074 GEN1
Solar/Wind Harmer
1.775
315733AD1-074 GEN2
Solar/Wind Harmer
1.775
315735AD1-075 GEN1
Solar/Wind Harmer
0.888
3152611GOSPORTB
Adder
0.993
3152621GOSPORTC
Adder
0.843
3152601GOSPORTA
Adder
0.777
3146206CASHIE
Solar/Wind Harmer
-0.009
970601AG2-382 GEN
Solar/Wind Harmer
3.833
3137643SOCKMAN
Solar/Wind Harmer
-0.035
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.009
3145683EARLEYS
Solar/Wind Harmer
-0.009
3145513AHOSKIE
Solar/Wind Harmer
0.076
961941AG1-037 GEN
Solar/Wind Harmer
0.065
3145513AHOSKIE
Solar/Wind Harmer
-0.009
315607AA1-063A GEN
Solar/Wind Harmer
0.877
3146043SEABORD
Solar/Wind Harmer
-0.009
3146033SCOT NK
Solar/Wind Harmer
-0.034
316318V4-068
Solar/Wind Harmer
0.216
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.009
965291AG1-394 GEN
Solar/Wind Harmer
0.766
970831AG2-522 GEN
Solar/Wind Harmer
4.284
316005AA1-067
Solar/Wind Harmer
0.173
3145746EVERETS
Solar/Wind Harmer
-0.034
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
970181AG2-120 GEN
Solar/Wind Harmer
1.121
316319Z2-044 C
Solar/Wind Harmer
0.472
957861AF2-080 GEN
Solar/Wind Harmer
3.732
3145933PARMELE
Solar/Wind Harmer
-0.009
3145493TOT1
Solar/Wind Harmer
0.132
3145453TOT5
Solar/Wind Harmer
0.079
3145603CNETO
Solar/Wind Harmer
0.053
315742AE1-103 GEN
Solar/Wind Harmer
0.89
961601AG1-000A GEN
Solar/Wind Harmer
3.345
316263AC1-034 GEN
Solar/Wind Harmer
3.987
939181AE1-148 GEN
Solar/Wind Harmer
4.633
316222AC1-221 GEN
Solar/Wind Harmer
0.805
3146843MT LREL
Solar/Wind Harmer
-0.008
3146843MT LREL
Solar/Wind Harmer
-0.008
964791AG1-342 GEN
Solar/Wind Harmer
1.656
962561AG1-105 GEN
Solar/Wind Harmer
4.315
313527AB2-043 GEN
Solar/Wind Harmer
1.172
3143526WINTERP
Solar/Wind Helper
2.674
966871AG1-558 GEN
Solar/Wind Helper
0.173
315821AE2-092 GEN
Solar/Wind Helper
1.115
3151031BRUNSWICKG2
50/50
1.791
970917AG2-570 GEN
Solar/Wind Harmer
36.273
316478AD1-087 GEN
Solar/Wind Harmer
0.932
316486AD2-202 GEN
Solar/Wind Harmer
0.273
315773AC2-141 GEN
Solar/Wind Harmer
4.105
944581AF1-123 GEN
Solar/Wind Harmer
42.771
944601AF1-125 GEN
Solar/Wind Harmer
42.103
316365GEN2_N
Solar/Wind Harmer
0.619
3146456SLIGO L269
Solar/Wind Harmer
-0.009
971153AH1-033 GEN
Solar/Wind Harmer
1.103
316320Y1-086
Solar/Wind Harmer
0.527
3146516WINFALL
Solar/Wind Harmer
-0.009
316435W1029_GEN3
Solar/Wind Harmer
1.613
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3146376EDENTON
Solar/Wind Harmer
-0.009
3151101ELIZAR3
Adder
7.309
3145796HORNRTN
Solar/Wind Harmer
-0.035
3145796HORNRTN
Solar/Wind Harmer
-0.009
966621AG1-532 GEN
Solar/Wind Harmer
0.179
315614AA2-178 GEN
Solar/Wind Harmer
0.951
971157AH1-035 GEN
Solar/Wind Harmer
1.098
313506AB2-031 GEN
Solar/Wind Harmer
0.706
315737AD1-076 GEN
Solar/Wind Harmer
1.668
3144873MCLAUGH
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
-0.009
3156021HOLLOMANSOL
Solar/Wind Harmer
1.177
3146263WOODLND
Solar/Wind Harmer
-0.009
316463AE2-346 GEN
Solar/Wind Harmer
0.141
316140AB2-099
Solar/Wind Harmer
0.059
962331AG1-082 GEN
Solar/Wind Harmer
1.088
316317KELFORD C
Solar/Wind Harmer
0.41
3145823KELFORD
Solar/Wind Harmer
-0.009
3146173TUNIS
Solar/Wind Harmer
-0.009
3145963POPLR C
Solar/Wind Harmer
-0.009
957521AF2-046 GEN
Solar/Wind Harmer
6.824
316420AA1-050 GEN
Solar/Wind Harmer
0.974
3145573BETHELC
Solar/Wind Harmer
-0.008
3145573BETHELC
Solar/Wind Harmer
-0.008
315835AF2-110_GEN
Solar/Wind Harmer
1.053
3147173SINAI
Solar/Wind Harmer
-0.008
3147243WELCO
Solar/Wind Harmer
-0.005
316118AC1-105 GEN
Solar/Wind Harmer
0.547
316311AC2-079 GEN
Solar/Wind Harmer
3.698
315833AF1-017_GEN
Solar/Wind Harmer
1.388
316349AD2-085 GEN
Solar/Wind Harmer
0.65
316239AB2-077_GEN
Solar/Wind Harmer
0.22
316238AB2-078_GEN
Solar/Wind Harmer
0.22
970865AG2-541 GEN
Solar/Wind Harmer
2.733
270455AD2-022 GEN
Solar/Wind Harmer
1.2
270457AD2-023 GEN
Solar/Wind Harmer
0.608
316233AE1-074 FULL
Solar/Wind Helper
0.785
270494AE1-108_GEN
Solar/Wind Helper
1.53
315243AE2-183_GT3
50/50
2.294
3151051BRUNSWICKS1
50/50
3.716
3151021BRUNSWICKG1
50/50
1.791
971451AH1-221 GEN
50/50
5.438
940641AE2-051 GEN
Solar/Wind Harmer
14.948
970919AG2-571 GEN
Solar/Wind Harmer
4.592
970087AG2-069 GEN
Solar/Wind Harmer
13.523
939411AE1-173 GEN
Solar/Wind Harmer
71.246
957481AF2-042 GEN
Solar/Wind Harmer
36.481
315693AD1-088 GEN
Solar/Wind Harmer
5.033
315687AD1-152 GEN
Solar/Wind Harmer
1.199
316294AC1-161 GEN
Solar/Wind Harmer
3.174
962491AG1-098 GEN
Solar/Wind Harmer
6.529
944591AF1-124 GEN
Solar/Wind Harmer
42.925
316023GEN1_S
Solar/Wind Harmer
0.619
316388AE2-253 GEN
Solar/Wind Harmer
0.612
3146456SLIGO L269
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.029
3146516WINFALL
Solar/Wind Harmer
-0.009
316011AB1-132 GEN
Solar/Wind Harmer
1.86
962571AG1-106 GEN
Solar/Wind Harmer
1.278
315800Z1-036_GEN1
Solar/Wind Harmer
2.194
3130156CHOWAN
Solar/Wind Harmer
-0.009
316246AF1-032 C
Solar/Wind Harmer
0.179
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.009
960081AF2-299 GEN
Solar/Wind Harmer
0.993
3145663CRESWEL
Solar/Wind Harmer
-0.025
971163AH1-040 GEN
Solar/Wind Harmer
8.264
316375AC2-012 GEN
Solar/Wind Harmer
3.032
3150981CHESPKA
Adder
0.974
3146206CASHIE
Solar/Wind Harmer
-0.009
971547AH1-271 GEN
Solar/Wind Harmer
2.19
316190AA2-174 GEN
Solar/Wind Harmer
0.107
3146263WOODLND
Solar/Wind Harmer
-0.009
3145683EARLEYS
Solar/Wind Harmer
-0.009
3145783HORNRTN
Solar/Wind Harmer
-0.009
3145823KELFORD
Solar/Wind Harmer
-0.009
3146173TUNIS
Solar/Wind Harmer
-0.009
3145963POPLR C
Solar/Wind Harmer
-0.009
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.257
315722AD1-056 GEN
Solar/Wind Harmer
0.905
316174AB2-169 GEN
Solar/Wind Harmer
1.334
316212AC1-099_GEN
Solar/Wind Harmer
0.753
3146293MARTNCO
Solar/Wind Harmer
0.053
316129AC1-054 GEN
Solar/Wind Harmer
0.75
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
3146233WITAKRS
Solar/Wind Harmer
-0.034
971065AG2-659 GEN
Solar/Wind Harmer
4.268
316494AC1-189 GEN
Solar/Wind Harmer
0.918
961671AG1-007 GEN
Solar/Wind Harmer
0.108
3146083TARBORO
Solar/Wind Harmer
-0.008
3145493TOT1
Solar/Wind Harmer
0.253
316359AB2-059 GEN
Solar/Wind Harmer
1.147
316049AB1-081 GEN
Solar/Wind Harmer
0.918
3142053HEARTS
Solar/Wind Harmer
0.1
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3145543BTLEBRO
Solar/Wind Harmer
-0.007
971795AH1-408 GEN
Solar/Wind Harmer
6.367
316093AE2-104_GEN
Solar/Wind Harmer
2.449
3147043LAWRENC
Adder
0.671
316072AD1-144
Solar/Wind Harmer
0.159
970401AG2-262 GEN
Solar/Wind Harmer
0.506
316003AC1-222 GEN
Solar/Wind Harmer
0.745
316237AB2-079_GEN
Solar/Wind Harmer
0.22
3143226MDLTHAN
Solar/Wind Helper
0.68
3143526WINTERP
Solar/Wind Helper
2.674
316336AC2-165 C
Solar/Wind Helper
2.289
3142543TWELFTH
Solar/Wind Helper
0.016
961681AG1-008 GEN
Solar/Wind Harmer
6.824
3145893MURPHYS
Solar/Wind Harmer
0.06
3145893MURPHYS
Solar/Wind Harmer
-0.009
315724AD1-057 GEN
Solar/Wind Harmer
0.498
316210AC1-098 GEN
Solar/Wind Harmer
1.355
3156081AA2-088 GEN
Solar/Wind Harmer
2.797
3145933PARMELE
Solar/Wind Harmer
-0.009
966801AG1-551 GEN
Solar/Wind Harmer
1.072
316327AA2-057 GEN
Solar/Wind Harmer
0.866
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
3146233WITAKRS
Solar/Wind Harmer
0.179
3146233WITAKRS
Solar/Wind Harmer
-0.006
3138543CONSLDL
Solar/Wind Harmer
-0.006
3146073TAR RVR
Solar/Wind Harmer
-0.008
3146083TARBORO
Solar/Wind Harmer
-0.008
961601AG1-000A GEN
Solar/Wind Harmer
3.388
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3145273HOLLAND
Solar/Wind Harmer
-0.006
3147043LAWRENC
Solar/Wind Harmer
-0.005
316248AF1-058 C
Solar/Wind Harmer
0.245
960061AF2-297 GEN
Solar/Wind Harmer
4.071
3144536CHRHLND
Solar/Wind Harmer
-0.001
316283AC2-100 C
Solar/Wind Harmer
0.745
971683AH1-343 GEN
Solar/Wind Harmer
3.1
316131AB2-060 GEN
Solar/Wind Harmer
0.765
964241AG1-285 GEN
Solar/Wind Harmer
5.121
316313AB2-026
Solar/Wind Helper
0.727
316258AE1-075 C
Solar/Wind Helper
0.655
316405AF2-144 C
Solar/Wind Helper
0.545
316473AC1-191 GEN
Solar/Wind Helper
0.782
LAGNLTFEXP_LAGN->PJM
CLTF
3.429
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.517
TVALTFEXP_TVA->PJM
CLTF
1.701
CPLELTFEXP_CPLE->PJM
CLTF
5.449
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.555
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.681
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.761
MECLTFEXP_MEC->PJM
CLTF
1.546
SIGELTFEXP_SIGE->PJM
CLTF
0.045
NYPJM->LTFIMP_NY
CLTF
0.637
LGEELTFEXP_LGEE->PJM
CLTF
0.533
WECLTFEXP_WEC->PJM
CLTF
0.278

Details for 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 57602_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-2: 57602_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:122.5 %
Rating:1265.1 MVA
Rating Type:C
MVA to Mitigate:1549.8
MW Contribution:5.44
Bus #Bus NameTypeMW Contribution
970533AG2-339 GEN
50/50
12.93
970531AG2-338 GEN
50/50
5.172
315242AE2-183_GT2
50/50
2.294
315241AE2-183_GT1
50/50
2.28
972185AH1-677 GEN
50/50
8.27
3151041BRUNSWICKG3
50/50
1.791
972187AH1-678 GEN
50/50
4.109
970933AG2-581 GEN
Solar/Wind Harmer
13.293
970099AG2-077 GEN
Solar/Wind Harmer
14.593
3144356SAPONY
Solar/Wind Harmer
0.343
3145506HICKORY
Solar/Wind Harmer
-0.036
3145506HICKORY
Solar/Wind Harmer
-0.022
3145506HICKORY
Solar/Wind Harmer
-0.005
316185AD1-033 GEN
Solar/Wind Harmer
0.958
316339AD2-160 GEN
Solar/Wind Harmer
0.612
316018AA1-139 ULT2
Solar/Wind Harmer
0.776
316017AA1-139 ULT1
Solar/Wind Harmer
0.733
3137176SLIGO L2192
Solar/Wind Harmer
-0.036
3146456SLIGO L269
Solar/Wind Harmer
1.069
3130086AYDLETT
Solar/Wind Harmer
-0.036
3146386ELIZ CT
Solar/Wind Harmer
-0.009
3142956BIRDNECK
Solar/Wind Harmer
0.48
316316AC1-027 C
Solar/Wind Harmer
0.274
315244AE2-183_ST
50/50
3.966
963041AG1-153 GEN
50/50
3.626
941031AE2-094 GEN
Solar/Wind Harmer
30.645
944011AF1-069 GEN
Solar/Wind Harmer
9.602
970673AG2-436 GEN
Solar/Wind Harmer
33.304
970673AG2-436 GEN
Solar/Wind Harmer
16.863
971967AH1-528 GEN
Solar/Wind Harmer
28.583
970085AG2-068 GEN
Solar/Wind Harmer
9.015
970581AG2-369 GEN
Solar/Wind Harmer
7.753
316315AB2-025 C
Solar/Wind Harmer
0.265
315814AE2-033 C
Solar/Wind Harmer
9.126
957871AF2-081 GEN
Solar/Wind Harmer
4.531
319010AE1-072 C
Solar/Wind Harmer
1.83
3146406KITTY HAWK
Solar/Wind Harmer
0.008
313526AB2-022
Solar/Wind Harmer
0.242
316321Z2-027
Solar/Wind Harmer
0.242
3146396TANGLEW
Solar/Wind Harmer
0.165
3145176PASQUOTANK
Solar/Wind Harmer
-0.006
315652AC1-086 GEN
Solar/Wind Harmer
10.001
315611Z1-036_GEN2
Solar/Wind Harmer
2.194
3146486SUNBURY
Solar/Wind Harmer
-0.009
3146486SUNBURY
Solar/Wind Harmer
-0.009
3130156CHOWAN
Solar/Wind Harmer
-0.009
3130156CHOWAN
Solar/Wind Harmer
-0.009
3151081ELIZAR1
Adder
7.217
3151091ELIZAR2
Adder
7.092
316305AF2-043 C
Solar/Wind Harmer
0.266
3145796HORNRTN
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.003
946281AF1-292 GEN
Solar/Wind Harmer
0.198
315816AE2-034 GEN
Solar/Wind Harmer
0.713
316087AB2-174 GEN
Solar/Wind Harmer
1.254
3130546PLYMOUTH
Solar/Wind Harmer
-0.009
315732AD1-074 GEN1
Solar/Wind Harmer
1.775
315733AD1-074 GEN2
Solar/Wind Harmer
1.775
315735AD1-075 GEN1
Solar/Wind Harmer
0.888
3152611GOSPORTB
Adder
0.993
3152621GOSPORTC
Adder
0.843
3152601GOSPORTA
Adder
0.777
3146206CASHIE
Solar/Wind Harmer
-0.009
970601AG2-382 GEN
Solar/Wind Harmer
3.833
3137643SOCKMAN
Solar/Wind Harmer
-0.035
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.009
3145683EARLEYS
Solar/Wind Harmer
-0.009
3145513AHOSKIE
Solar/Wind Harmer
0.076
961941AG1-037 GEN
Solar/Wind Harmer
0.065
3145513AHOSKIE
Solar/Wind Harmer
-0.009
315607AA1-063A GEN
Solar/Wind Harmer
0.877
3146043SEABORD
Solar/Wind Harmer
-0.009
3146033SCOT NK
Solar/Wind Harmer
-0.034
316318V4-068
Solar/Wind Harmer
0.216
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.009
965291AG1-394 GEN
Solar/Wind Harmer
0.766
970831AG2-522 GEN
Solar/Wind Harmer
4.284
316005AA1-067
Solar/Wind Harmer
0.173
3145746EVERETS
Solar/Wind Harmer
-0.034
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
970181AG2-120 GEN
Solar/Wind Harmer
1.121
316319Z2-044 C
Solar/Wind Harmer
0.472
957861AF2-080 GEN
Solar/Wind Harmer
3.732
316420AA1-050 GEN
Solar/Wind Harmer
0.974
3145573BETHELC
Solar/Wind Harmer
-0.008
3145573BETHELC
Solar/Wind Harmer
-0.008
315835AF2-110_GEN
Solar/Wind Harmer
1.053
3147173SINAI
Solar/Wind Harmer
-0.008
3147243WELCO
Solar/Wind Harmer
-0.005
316118AC1-105 GEN
Solar/Wind Harmer
0.547
316311AC2-079 GEN
Solar/Wind Harmer
3.698
315833AF1-017_GEN
Solar/Wind Harmer
1.388
316349AD2-085 GEN
Solar/Wind Harmer
0.65
316239AB2-077_GEN
Solar/Wind Harmer
0.22
316238AB2-078_GEN
Solar/Wind Harmer
0.22
970865AG2-541 GEN
Solar/Wind Harmer
2.733
270455AD2-022 GEN
Solar/Wind Harmer
1.2
270457AD2-023 GEN
Solar/Wind Harmer
0.608
316233AE1-074 FULL
Solar/Wind Helper
0.785
270494AE1-108_GEN
Solar/Wind Helper
1.53
315243AE2-183_GT3
50/50
2.294
3151051BRUNSWICKS1
50/50
3.716
3151021BRUNSWICKG1
50/50
1.791
971451AH1-221 GEN
50/50
5.438
940641AE2-051 GEN
Solar/Wind Harmer
14.948
970919AG2-571 GEN
Solar/Wind Harmer
4.592
970087AG2-069 GEN
Solar/Wind Harmer
13.523
939411AE1-173 GEN
Solar/Wind Harmer
71.246
957481AF2-042 GEN
Solar/Wind Harmer
36.481
315693AD1-088 GEN
Solar/Wind Harmer
5.033
315687AD1-152 GEN
Solar/Wind Harmer
1.199
316294AC1-161 GEN
Solar/Wind Harmer
3.174
962491AG1-098 GEN
Solar/Wind Harmer
6.529
944591AF1-124 GEN
Solar/Wind Harmer
42.925
316023GEN1_S
Solar/Wind Harmer
0.619
316388AE2-253 GEN
Solar/Wind Harmer
0.612
3146456SLIGO L269
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.029
3146516WINFALL
Solar/Wind Harmer
-0.009
316011AB1-132 GEN
Solar/Wind Harmer
1.86
962571AG1-106 GEN
Solar/Wind Harmer
1.278
315800Z1-036_GEN1
Solar/Wind Harmer
2.194
3130156CHOWAN
Solar/Wind Harmer
-0.009
316246AF1-032 C
Solar/Wind Harmer
0.179
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.009
960081AF2-299 GEN
Solar/Wind Harmer
0.993
3145663CRESWEL
Solar/Wind Harmer
-0.025
971163AH1-040 GEN
Solar/Wind Harmer
8.264
316375AC2-012 GEN
Solar/Wind Harmer
3.032
3150981CHESPKA
Adder
0.974
3146206CASHIE
Solar/Wind Harmer
-0.009
971547AH1-271 GEN
Solar/Wind Harmer
2.19
316190AA2-174 GEN
Solar/Wind Harmer
0.107
3146263WOODLND
Solar/Wind Harmer
-0.009
3145683EARLEYS
Solar/Wind Harmer
-0.009
3145783HORNRTN
Solar/Wind Harmer
-0.009
3145823KELFORD
Solar/Wind Harmer
-0.009
3146173TUNIS
Solar/Wind Harmer
-0.009
3145963POPLR C
Solar/Wind Harmer
-0.009
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.257
315722AD1-056 GEN
Solar/Wind Harmer
0.905
316174AB2-169 GEN
Solar/Wind Harmer
1.334
316212AC1-099_GEN
Solar/Wind Harmer
0.753
3146293MARTNCO
Solar/Wind Harmer
0.053
316129AC1-054 GEN
Solar/Wind Harmer
0.75
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
3146233WITAKRS
Solar/Wind Harmer
-0.034
971065AG2-659 GEN
Solar/Wind Harmer
4.268
316494AC1-189 GEN
Solar/Wind Harmer
0.918
961671AG1-007 GEN
Solar/Wind Harmer
0.108
3151031BRUNSWICKG2
50/50
1.791
970917AG2-570 GEN
Solar/Wind Harmer
36.273
316478AD1-087 GEN
Solar/Wind Harmer
0.932
316486AD2-202 GEN
Solar/Wind Harmer
0.273
315773AC2-141 GEN
Solar/Wind Harmer
4.105
944581AF1-123 GEN
Solar/Wind Harmer
42.771
944601AF1-125 GEN
Solar/Wind Harmer
42.103
316365GEN2_N
Solar/Wind Harmer
0.619
3146456SLIGO L269
Solar/Wind Harmer
-0.009
971153AH1-033 GEN
Solar/Wind Harmer
1.103
316320Y1-086
Solar/Wind Harmer
0.527
3146516WINFALL
Solar/Wind Harmer
-0.009
316435W1029_GEN3
Solar/Wind Harmer
1.613
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3146376EDENTON
Solar/Wind Harmer
-0.009
3151101ELIZAR3
Adder
7.309
3145796HORNRTN
Solar/Wind Harmer
-0.035
3145796HORNRTN
Solar/Wind Harmer
-0.009
966621AG1-532 GEN
Solar/Wind Harmer
0.179
315614AA2-178 GEN
Solar/Wind Harmer
0.951
971157AH1-035 GEN
Solar/Wind Harmer
1.098
313506AB2-031 GEN
Solar/Wind Harmer
0.706
315737AD1-076 GEN
Solar/Wind Harmer
1.668
3144873MCLAUGH
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
-0.009
3156021HOLLOMANSOL
Solar/Wind Harmer
1.177
3146263WOODLND
Solar/Wind Harmer
-0.009
316463AE2-346 GEN
Solar/Wind Harmer
0.141
316140AB2-099
Solar/Wind Harmer
0.059
962331AG1-082 GEN
Solar/Wind Harmer
1.088
316317KELFORD C
Solar/Wind Harmer
0.41
3145823KELFORD
Solar/Wind Harmer
-0.009
3146173TUNIS
Solar/Wind Harmer
-0.009
3145963POPLR C
Solar/Wind Harmer
-0.009
957521AF2-046 GEN
Solar/Wind Harmer
6.824
961681AG1-008 GEN
Solar/Wind Harmer
6.824
3145893MURPHYS
Solar/Wind Harmer
0.06
3145893MURPHYS
Solar/Wind Harmer
-0.009
315724AD1-057 GEN
Solar/Wind Harmer
0.498
316210AC1-098 GEN
Solar/Wind Harmer
1.355
3156081AA2-088 GEN
Solar/Wind Harmer
2.797
3145933PARMELE
Solar/Wind Harmer
-0.009
966801AG1-551 GEN
Solar/Wind Harmer
1.072
316327AA2-057 GEN
Solar/Wind Harmer
0.866
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
3146233WITAKRS
Solar/Wind Harmer
0.179
3146233WITAKRS
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
316431W1029_GEN1
Solar/Wind Harmer
1.613
316433W1029_GEN2
Solar/Wind Harmer
1.613
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3146376EDENTON
Solar/Wind Harmer
0.263
3146376EDENTON
Solar/Wind Harmer
0.263
3145796HORNRTN
Solar/Wind Harmer
-0.026
316181AB2-040 GEN
Solar/Wind Harmer
1.224
316065AD1-022 GEN
Solar/Wind Harmer
4.383
316036AC1-147 C
Solar/Wind Harmer
0.236
3150991CHESPKB
Adder
0.817
3150991CHESPKB
Adder
0.797
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
0.981
3145593CAROLNA
Solar/Wind Harmer
0.072
316426AA2-053 GEN
Solar/Wind Harmer
0.881
3145783HORNRTN
Solar/Wind Harmer
1.034
3145783HORNRTN
Solar/Wind Harmer
0.827
3145783HORNRTN
Solar/Wind Harmer
0.258
3145783HORNRTN
Solar/Wind Harmer
0.103
3146173TUNIS
Solar/Wind Harmer
-0.009
3146173TUNIS
Solar/Wind Harmer
-0.009
3145893MURPHYS
Solar/Wind Harmer
0.241
3145893MURPHYS
Solar/Wind Harmer
-0.016
316274AC1-208 GEN
Solar/Wind Harmer
0.931
3145933PARMELE
Solar/Wind Harmer
-0.017
3145933PARMELE
Solar/Wind Harmer
-0.009
3145493TOT1
Solar/Wind Harmer
0.132
3145453TOT5
Solar/Wind Harmer
0.079
3145603CNETO
Solar/Wind Harmer
0.053
315742AE1-103 GEN
Solar/Wind Harmer
0.89
961601AG1-000A GEN
Solar/Wind Harmer
3.345
316263AC1-034 GEN
Solar/Wind Harmer
3.987
939181AE1-148 GEN
Solar/Wind Harmer
4.633
316222AC1-221 GEN
Solar/Wind Harmer
0.805
3146843MT LREL
Solar/Wind Harmer
-0.008
3146843MT LREL
Solar/Wind Harmer
-0.008
964791AG1-342 GEN
Solar/Wind Harmer
1.656
962561AG1-105 GEN
Solar/Wind Harmer
4.315
313527AB2-043 GEN
Solar/Wind Harmer
1.172
3143526WINTERP
Solar/Wind Helper
2.674
966871AG1-558 GEN
Solar/Wind Helper
0.173
315821AE2-092 GEN
Solar/Wind Helper
1.115
3138543CONSLDL
Solar/Wind Harmer
-0.006
3146073TAR RVR
Solar/Wind Harmer
-0.008
3146083TARBORO
Solar/Wind Harmer
-0.008
961601AG1-000A GEN
Solar/Wind Harmer
3.388
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3145273HOLLAND
Solar/Wind Harmer
-0.006
3147043LAWRENC
Solar/Wind Harmer
-0.005
316248AF1-058 C
Solar/Wind Harmer
0.245
960061AF2-297 GEN
Solar/Wind Harmer
4.071
3144536CHRHLND
Solar/Wind Harmer
-0.001
316283AC2-100 C
Solar/Wind Harmer
0.745
971683AH1-343 GEN
Solar/Wind Harmer
3.1
316131AB2-060 GEN
Solar/Wind Harmer
0.765
964241AG1-285 GEN
Solar/Wind Harmer
5.121
316313AB2-026
Solar/Wind Helper
0.727
316258AE1-075 C
Solar/Wind Helper
0.655
316405AF2-144 C
Solar/Wind Helper
0.545
316473AC1-191 GEN
Solar/Wind Helper
0.782
3146083TARBORO
Solar/Wind Harmer
-0.008
3145493TOT1
Solar/Wind Harmer
0.253
316359AB2-059 GEN
Solar/Wind Harmer
1.147
316049AB1-081 GEN
Solar/Wind Harmer
0.918
3142053HEARTS
Solar/Wind Harmer
0.1
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3145543BTLEBRO
Solar/Wind Harmer
-0.007
971795AH1-408 GEN
Solar/Wind Harmer
6.367
316093AE2-104_GEN
Solar/Wind Harmer
2.449
3147043LAWRENC
Adder
0.671
316072AD1-144
Solar/Wind Harmer
0.159
970401AG2-262 GEN
Solar/Wind Harmer
0.506
316003AC1-222 GEN
Solar/Wind Harmer
0.745
316237AB2-079_GEN
Solar/Wind Harmer
0.22
3143226MDLTHAN
Solar/Wind Helper
0.68
3143526WINTERP
Solar/Wind Helper
2.674
316336AC2-165 C
Solar/Wind Helper
2.289
3142543TWELFTH
Solar/Wind Helper
0.016
LAGNLTFEXP_LAGN->PJM
CLTF
3.429
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.517
TVALTFEXP_TVA->PJM
CLTF
1.701
CPLELTFEXP_CPLE->PJM
CLTF
5.449
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.555
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.681
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.761
MECLTFEXP_MEC->PJM
CLTF
1.546
SIGELTFEXP_SIGE->PJM
CLTF
0.045
NYPJM->LTFIMP_NY
CLTF
0.637
LGEELTFEXP_LGEE->PJM
CLTF
0.533
WECLTFEXP_WEC->PJM
CLTF
0.278

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:175.45 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:5650.14
MW Contribution:13.28
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
4.373
3151101ELIZAR3
50/50
30.305
3150861SPRUNCD
50/50
1.461
3151161SURRY 1
50/50
11.304
970917AG2-570 GEN
Solar/Wind Harmer
28.408
315773AC2-141 GEN
Solar/Wind Harmer
11.382
944581AF1-123 GEN
Solar/Wind Harmer
69.733
944601AF1-125 GEN
Solar/Wind Harmer
68.658
3144873MCLAUGH
Solar/Wind Harmer
0.008
970533AG2-339 GEN
50/50
30.786
970531AG2-338 GEN
50/50
12.314
315242AE2-183_GT2
50/50
5.558
315241AE2-183_GT1
50/50
5.524
972185AH1-677 GEN
50/50
20.036
3151041BRUNSWICKG3
50/50
4.373
972187AH1-678 GEN
50/50
10.036
3150991CHESPKB
50/50
3.415
3150991CHESPKB
50/50
3.333
971223AH1-071 GEN
Solar/Wind Harmer
3.931
3143526WINTERP
Solar/Wind Harmer
1.742
970933AG2-581 GEN
Solar/Wind Harmer
25.944
3144356SAPONY
Solar/Wind Harmer
2.645
316185AD1-033 GEN
Solar/Wind Harmer
0.009
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.295
3145506HICKORY
Solar/Wind Harmer
1.229
3145506HICKORY
Solar/Wind Harmer
0.737
3145506HICKORY
Solar/Wind Harmer
0.184
316036AC1-147 C
Solar/Wind Harmer
0.057
316339AD2-160 GEN
Solar/Wind Harmer
0.497
316018AA1-139 ULT2
Solar/Wind Harmer
0.008
316017AA1-139 ULT1
Solar/Wind Harmer
0.171
316303AF2-085
50/50
6.551
315244AE2-183_ST
50/50
9.609
963041AG1-153 GEN
50/50
8.856
315779AE2-040
50/50
4.414
3151081ELIZAR1
50/50
29.922
3151091ELIZAR2
50/50
29.403
941591AE2-156 GEN
50/50
27.332
3152611GOSPORTB
50/50
4.152
3152621GOSPORTC
50/50
3.523
3152601GOSPORTA
50/50
3.25
971285AH1-108 GEN
50/50
2.391
972263AH1-716 GEN
50/50
170.662
941031AE2-094 GEN
Solar/Wind Harmer
63.788
944011AF1-069 GEN
Solar/Wind Harmer
20.842
970673AG2-436 GEN
Solar/Wind Harmer
72.487
970673AG2-436 GEN
Solar/Wind Harmer
48.325
316233AE1-074 FULL
Solar/Wind Harmer
0.268
971281AH1-106 GEN
Solar/Wind Harmer
4.649
971283AH1-107 GEN
Solar/Wind Harmer
4.649
971967AH1-528 GEN
Solar/Wind Harmer
53.477
970085AG2-068 GEN
Solar/Wind Harmer
16.971
970581AG2-369 GEN
Solar/Wind Harmer
14.595
316315AB2-025 C
Solar/Wind Harmer
0.256
315814AE2-033 C
Solar/Wind Harmer
24.917
3143316POE
Solar/Wind Harmer
1.232
957871AF2-081 GEN
Solar/Wind Harmer
15.244
319010AE1-072 C
Solar/Wind Harmer
1.539
3146406KITTY HAWK
Solar/Wind Harmer
0.038
316305AF2-043 C
Solar/Wind Harmer
0.002
313526AB2-022
Solar/Wind Harmer
0.164
315835AF2-110_GEN
Solar/Wind Harmer
2.081
315833AF1-017_GEN
Solar/Wind Harmer
0.002
316349AD2-085 GEN
Solar/Wind Harmer
0.208
316311AC2-079 GEN
Solar/Wind Harmer
8.702
3146486SUNBURY
Solar/Wind Harmer
0.302
3146486SUNBURY
Solar/Wind Harmer
0.302
316321Z2-027
Solar/Wind Harmer
0.056
3146396TANGLEW
Solar/Wind Harmer
0.833
3145176PASQUOTANK
Solar/Wind Harmer
0.187
971445AH1-216 GEN
Solar/Wind Harmer
21.042
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.294
3130156CHOWAN
Solar/Wind Harmer
0.294
972265AH1-717 GEN
Adder
22.85
3151201GRAVEL4
Adder
21.42
3151191GRAVEL3
Adder
21.149
3151211GRAVEL5
Adder
21.149
316369SG1_INVT
Solar/Wind Harmer
0.011
315816AE2-034 GEN
Solar/Wind Harmer
1.242
316132AB2-190 GEN1
Solar/Wind Harmer
1.538
3130546PLYMOUTH
Solar/Wind Harmer
0.286
965291AG1-394 GEN
Solar/Wind Harmer
1.269
315732AD1-074 GEN1
Solar/Wind Harmer
1.639
315733AD1-074 GEN2
Solar/Wind Harmer
1.639
315735AD1-075 GEN1
Solar/Wind Harmer
0.82
3145893MURPHYS
Solar/Wind Harmer
0.765
3145893MURPHYS
Solar/Wind Harmer
0.283
3146206CASHIE
Solar/Wind Harmer
0.283
970601AG2-382 GEN
Solar/Wind Harmer
10.575
316087AB2-174 GEN
Solar/Wind Harmer
0.008
3146043SEABORD
Solar/Wind Harmer
0.28
3145513AHOSKIE
Solar/Wind Harmer
0.586
3145513AHOSKIE
Solar/Wind Harmer
0.28
315607AA1-063A GEN
Solar/Wind Harmer
0.572
3145683EARLEYS
Solar/Wind Harmer
0.558
3145683EARLEYS
Solar/Wind Harmer
0.279
3145683EARLEYS
Solar/Wind Harmer
0.279
315652AC1-086 GEN
Solar/Wind Harmer
30.678
3137643SOCKMAN
Solar/Wind Harmer
1.111
3145796HORNRTN
Solar/Wind Harmer
0.88
3145796HORNRTN
Solar/Wind Harmer
0.11
3146033SCOT NK
Solar/Wind Harmer
1.084
3137176SLIGO L2192
Solar/Wind Harmer
1.217
3146456SLIGO L269
Solar/Wind Harmer
5.409
3130086AYDLETT
Solar/Wind Harmer
1.221
3146386ELIZ CT
Solar/Wind Harmer
0.303
970657AG2-426 GEN
Solar/Wind Harmer
10.611
970657AG2-426 GEN
Solar/Wind Harmer
2.224
316431W1029_GEN1
Solar/Wind Harmer
0.002
316433W1029_GEN2
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.3
3146516WINFALL
Solar/Wind Harmer
0.3
3146516WINFALL
Solar/Wind Harmer
0.3
316236AE1-162_GEN
Solar/Wind Harmer
0.002
3146626S HERTFORD
Solar/Wind Harmer
0.299
3146626S HERTFORD
Solar/Wind Harmer
0.299
970099AG2-077 GEN
Solar/Wind Harmer
31.878
315742AE1-103 GEN
Solar/Wind Harmer
0.003
3146376EDENTON
Solar/Wind Harmer
1.308
3146376EDENTON
Solar/Wind Harmer
1.308
316240AF1-291 C
Solar/Wind Harmer
0.002
316033AB2-134 GEN
Solar/Wind Harmer
0.017
315697AD1-025 GEN
Solar/Wind Harmer
0.325
944641AF1-129 GEN
Adder
137.21
316065AD1-022 GEN
Solar/Wind Harmer
13.074
3145893MURPHYS
Solar/Wind Harmer
1.897
3145893MURPHYS
Solar/Wind Harmer
0.51
3146173TUNIS
Solar/Wind Harmer
0.281
3146173TUNIS
Solar/Wind Harmer
0.281
316181AB2-040 GEN
Solar/Wind Harmer
0.407
3142666NORTHAMPTON
Solar/Wind Harmer
0.279
3142666NORTHAMPTON
Solar/Wind Harmer
0.279
3142666NORTHAMPTON
Solar/Wind Harmer
0.279
3142666NORTHAMPTON
Solar/Wind Harmer
0.167
316426AA2-053 GEN
Solar/Wind Harmer
0.935
3145593CAROLNA
Solar/Wind Harmer
0.276
3145593CAROLNA
Solar/Wind Harmer
0.276
966811AG1-552 GEN
Solar/Wind Harmer
2.997
3145593CAROLNA
Solar/Wind Harmer
0.344
3145796HORNRTN
Solar/Wind Harmer
0.825
3145783HORNRTN
Solar/Wind Harmer
4.886
3145783HORNRTN
Solar/Wind Harmer
3.909
3145783HORNRTN
Solar/Wind Harmer
1.222
3145783HORNRTN
Solar/Wind Harmer
0.489
316274AC1-208 GEN
Solar/Wind Harmer
1.384
3145933PARMELE
Solar/Wind Harmer
0.531
3145933PARMELE
Solar/Wind Harmer
0.265
3142946ENON
Solar/Wind Harmer
0.026
971741AH1-377 GEN
Solar/Wind Harmer
26.27
939181AE1-148 GEN
Solar/Wind Harmer
12.567
3142366NRTHEST
Adder
0.844
313527AB2-043 GEN
Solar/Wind Harmer
0.003
970301AG2-198 GEN
Solar/Wind Harmer
10.992
3150691DARBY 3
Adder
18.496
3150701DARBY 4
Adder
18.453
3150681DARBY 2
Adder
18.432
3150671DARBY 1
Adder
18.41
3145493TOT1
Solar/Wind Harmer
0.592
3145453TOT5
Solar/Wind Harmer
0.355
3145603CNETO
Solar/Wind Harmer
0.237
961601AG1-000A GEN
Solar/Wind Harmer
4.486
316263AC1-034 GEN
Solar/Wind Harmer
9.586
316075AC2-137 C
Solar/Wind Harmer
0.069
970323AG2-213 GEN
Solar/Wind Harmer
10.747
971775AH1-396 GEN
Solar/Wind Harmer
0.403
316034AC1-036 C
Solar/Wind Harmer
0.018
962561AG1-105 GEN
Solar/Wind Harmer
11.957
964791AG1-342 GEN
Solar/Wind Harmer
4.752
3146843MT LREL
Solar/Wind Harmer
0.247
3146843MT LREL
Solar/Wind Harmer
0.247
958211AF2-115 GEN
Solar/Wind Harmer
2.961
963191AG1-168 GEN
Solar/Wind Harmer
0.987
3144293JTRSVLE
Adder
0.785
3144293JTRSVLE
Adder
0.661
3147133PAMPLIN
Solar/Wind Harmer
0.245
3147133PAMPLIN
Solar/Wind Harmer
0.196
3146456SLIGO L269
Solar/Wind Harmer
0.306
971153AH1-033 GEN
Solar/Wind Harmer
3.534
3144536CHRHLND
Solar/Wind Harmer
0.046
316320Y1-086
Solar/Wind Harmer
0.002
970661AG2-428 GEN
Solar/Wind Harmer
6.41
316083AB2-161 GEN
Solar/Wind Harmer
0.004
970659AG2-427 GEN
Solar/Wind Harmer
3.204
315813AE1-149 C
Solar/Wind Harmer
16.153
316435W1029_GEN3
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.3
3145336SMITFLD
Solar/Wind Harmer
0.12
3146626S HERTFORD
Solar/Wind Harmer
0.299
315839AE2-212 C
Solar/Wind Harmer
0.002
3145273HOLLAND
Solar/Wind Harmer
0.223
316313AB2-026
Solar/Wind Harmer
0.186
316258AE1-075 C
Solar/Wind Harmer
0.223
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
4.463
965281AG1-393 GEN
Solar/Wind Harmer
3.139
3151221GRAVEL6
Adder
21.396
3151171GRAVELC
Adder
4.116
3146376EDENTON
Solar/Wind Harmer
0.294
961611AG1-000B GEN
Solar/Wind Harmer
7.797
316365GEN2_N
Solar/Wind Harmer
0.655
315614AA2-178 GEN
Solar/Wind Harmer
1.657
315778AD1-151 GEN
Solar/Wind Harmer
23.065
3156081AA2-088 GEN
Solar/Wind Harmer
0.007
970129AG2-093 GEN
Solar/Wind Harmer
17.309
316478AD1-087 GEN
Solar/Wind Harmer
0.999
316486AD2-202 GEN
Solar/Wind Harmer
0.293
971157AH1-035 GEN
Solar/Wind Harmer
3.43
315737AD1-076 GEN
Solar/Wind Harmer
3.669
3144216WINCHST
Adder
1.072
970133AG2-095 GEN
Solar/Wind Harmer
2.723
3145893MURPHYS
Solar/Wind Harmer
0.474
3145893MURPHYS
Solar/Wind Harmer
0.283
3146206CASHIE
Solar/Wind Harmer
0.283
957521AF2-046 GEN
Solar/Wind Harmer
21.052
961681AG1-008 GEN
Solar/Wind Harmer
21.052
3150921YORKTN3
Adder
7.103
3146173TUNIS
Solar/Wind Harmer
0.281
313506AB2-031 GEN
Solar/Wind Harmer
0.867
3156021HOLLOMANSOL
Solar/Wind Harmer
1.274
316463AE2-346 GEN
Solar/Wind Harmer
0.241
316140AB2-099
Solar/Wind Harmer
0.1
962331AG1-082 GEN
Solar/Wind Harmer
2.99
3142666NORTHAMPTON
Solar/Wind Harmer
0.279
3146263WOODLND
Solar/Wind Harmer
0.278
3147043LAWRENC
Solar/Wind Harmer
0.166
316317KELFORD C
Solar/Wind Harmer
0.027
3145823KELFORD
Solar/Wind Harmer
0.275
3145796HORNRTN
Solar/Wind Harmer
1.1
3145796HORNRTN
Solar/Wind Harmer
0.275
3145963POPLR C
Solar/Wind Harmer
0.274
3143096IRON208
Adder
1.147
3143096IRON208
Adder
1.124
316382AG1-145 C
Solar/Wind Harmer
0.002
316210AC1-098 GEN
Solar/Wind Harmer
2.485
3145933PARMELE
Solar/Wind Harmer
0.265
966801AG1-551 GEN
Solar/Wind Harmer
3.091
3142946ENON
Solar/Wind Harmer
0.089
315724AD1-057 GEN
Solar/Wind Harmer
0.985
3145746EVERETS
Solar/Wind Harmer
0.261
3145746EVERETS
Solar/Wind Harmer
0.261
316327AA2-057 GEN
Solar/Wind Harmer
0.393
970909AG2-566 GEN
Solar/Wind Harmer
2.748
316131AB2-060 GEN
Solar/Wind Harmer
0.81
3146233WITAKRS
Solar/Wind Harmer
1.286
3146233WITAKRS
Solar/Wind Harmer
0.174
3138543CONSLDL
Solar/Wind Harmer
0.169
964241AG1-285 GEN
Solar/Wind Harmer
17.051
3146073TAR RVR
Solar/Wind Harmer
0.255
3146083TARBORO
Solar/Wind Harmer
0.255
970293AG2-193 GEN
Solar/Wind Harmer
2.717
3142433PROV 92
Adder
0.492
3142433PROV 92
Adder
0.492
315785AD2-033 C
Solar/Wind Harmer
2.056
961601AG1-000A GEN
Solar/Wind Harmer
17.946
3145543BTLEBRO
Solar/Wind Harmer
0.252
3145543BTLEBRO
Solar/Wind Harmer
0.252
971623AH1-311 GEN
Solar/Wind Harmer
0.505
970257AG2-171 GEN
Solar/Wind Harmer
8.061
959311AF2-222 GEN
Solar/Wind Harmer
22.323
963181AG1-167 GEN
Solar/Wind Harmer
0.987
3144293JTRSVLE
Adder
0.785
3147133PAMPLIN
Solar/Wind Harmer
0.769
971193AH1-056 GEN
Solar/Wind Harmer
14.916
3141843SHACKLE
Adder
1.244
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316280AD1-041 GEN
Solar/Wind Harmer
0.005
3141766HARMONY
Solar/Wind Harmer
3.224
316156AD2-030 GEN
Solar/Wind Harmer
0.179
3141873WAN 176
Solar/Wind Harmer
4.293
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
10.242
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3142416OLDCHRC
Solar/Wind Harmer
2.323
3146926FARMVIL
Solar/Wind Harmer
0.141
971683AH1-343 GEN
Solar/Wind Harmer
8.112
962971AG1-146 GEN
Solar/Wind Harmer
3.502
316283AC2-100 C
Solar/Wind Harmer
0.428
316473AC1-191 GEN
Solar/Wind Harmer
0.734
970009AG2-005 GEN
Solar/Wind Harmer
1.596
3146776BUCKING
Solar/Wind Harmer
0.076
316404AE1-155 C
Solar/Wind Harmer
0.046
3150351NORNECKC2
Adder
1.933
970221AG2-151 GEN
Solar/Wind Harmer
9.113
971781AH1-399 GEN
Solar/Wind Harmer
0.197
3141906WESTMOR
Solar/Wind Harmer
0.057
270197AD1-017 GEN1
Solar/Wind Harmer
0.888
270018AE2-047 C O1
Solar/Wind Harmer
0.003
3147312GRETNA
Solar/Wind Harmer
0.026
941821AE2-187 GEN
Solar/Wind Harmer
4.176
972255AH1-712 GEN
Adder
66.009
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
970737AG2-469 GEN
Solar/Wind Harmer
5.167
958131AF2-107 GEN
Solar/Wind Harmer
3.333
316044AC1-158 PL1
Solar/Wind Helper
2.198
316450AC1-158 RIC
Solar/Wind Helper
0.586
3147666LOUISA
Solar/Wind Helper
0.715
316170AC1-121 GEN2
Solar/Wind Helper
0.429
3141196NOKESVL
Solar/Wind Helper
1.038
3132273ORANGE
Solar/Wind Helper
0.047
227287AC2-120 GEN
Solar/Wind Helper
0.311
226910AB2-157 C
Solar/Wind Helper
0.013
970831AG2-522 GEN
Solar/Wind Harmer
11.448
3138283WHITEMARSH
Solar/Wind Harmer
0.061
316005AA1-067
Solar/Wind Harmer
0.28
3145746EVERETS
Solar/Wind Harmer
1.039
3145746EVERETS
Solar/Wind Harmer
0.261
3145746EVERETS
Solar/Wind Harmer
0.261
3145746EVERETS
Solar/Wind Harmer
0.261
970181AG2-120 GEN
Solar/Wind Harmer
3.25
957861AF2-080 GEN
Solar/Wind Harmer
11.129
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316420AA1-050 GEN
Solar/Wind Harmer
0.008
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.255
3145573BETHELC
Solar/Wind Harmer
0.255
971167AH1-042 GEN
Solar/Wind Harmer
22.645
315976AC1-164 GENA
Solar/Wind Harmer
26.291
316169AC1-164_GENC
Solar/Wind Harmer
22.713
315975AC1-164 GENB
Solar/Wind Harmer
0.778
3142433PROV 92
Adder
0.492
3142433PROV 92
Adder
0.492
971443AH1-215 GEN
Solar/Wind Harmer
4.236
3144303KENBRDG
Solar/Wind Harmer
0.201
970683AG2-441 GEN
Solar/Wind Harmer
16.616
970681AG2-440 GEN
Solar/Wind Harmer
13.292
946301AF1-294 GEN
Solar/Wind Harmer
4.868
961791AG1-021 GEN
Solar/Wind Harmer
2.368
3143873LANEXA
Solar/Wind Harmer
0.148
315657AE1-056 GEN
Solar/Wind Harmer
8.449
316118AC1-105 GEN
Solar/Wind Harmer
0.629
970189AG2-124 GEN
Solar/Wind Harmer
7.213
315662AE1-191 GEN
Solar/Wind Harmer
0.008
315666AE1-190 GEN
Solar/Wind Harmer
0.002
316314AB2-024 C
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.002
3141873WAN 176
Solar/Wind Harmer
0.048
3147173SINAI
Solar/Wind Harmer
0.24
3147243WELCO
Solar/Wind Harmer
0.15
316312AB1-027
Solar/Wind Harmer
0.429
3141913WHIT STONE
Solar/Wind Harmer
0.234
970119AG2-088 GEN
50/50
49.132
315243AE2-183_GT3
50/50
5.558
3151051BRUNSWICKS1
50/50
9.077
3151021BRUNSWICKG1
50/50
4.373
971451AH1-221 GEN
50/50
13.283
3150981CHESPKA
50/50
4.07
3150851SPRUNCC
50/50
1.461
3152331SURRY 2
50/50
12.331
3143226MDLTHAN
Solar/Wind Harmer
0.368
940641AE2-051 GEN
Solar/Wind Harmer
28.054
939411AE1-173 GEN
Solar/Wind Harmer
145.057
3143526WINTERP
Solar/Wind Harmer
1.742
970919AG2-571 GEN
Solar/Wind Harmer
11.363
970087AG2-069 GEN
Solar/Wind Harmer
25.456
316294AC1-161 GEN
Solar/Wind Harmer
5.4
944591AF1-124 GEN
Solar/Wind Harmer
69.98
316375AC2-012 GEN
Solar/Wind Harmer
0.008
316388AE2-253 GEN
Solar/Wind Harmer
0.96
3146456SLIGO L269
Solar/Wind Harmer
0.306
316246AF1-032 C
Solar/Wind Harmer
0.137
316093AE2-104_GEN
Solar/Wind Harmer
5.099
970661AG2-428 GEN
Solar/Wind Harmer
30.138
316381AD1-082 GEN
Solar/Wind Harmer
0.316
970659AG2-427 GEN
Solar/Wind Harmer
14.649
316072AD1-144
Solar/Wind Harmer
0.109
3146516WINFALL
Solar/Wind Harmer
0.972
3146516WINFALL
Solar/Wind Harmer
0.3
3145336SMITFLD
Solar/Wind Harmer
1.197
957481AF2-042 GEN
Solar/Wind Harmer
79.695
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
5.25
3130156CHOWAN
Solar/Wind Harmer
0.294
3151171GRAVELC
Adder
3.13
961611AG1-000B GEN
Solar/Wind Harmer
15.335
315671AE2-027_GEN
Solar/Wind Harmer
18.679
316023GEN1_S
Solar/Wind Harmer
0.655
971647AH1-324 GEN
Solar/Wind Harmer
12.413
3145663CRESWEL
Solar/Wind Harmer
0.81
971163AH1-040 GEN
Solar/Wind Harmer
23.157
315693AD1-088 GEN
Solar/Wind Harmer
13.873
971069AG2-661 GEN
Solar/Wind Harmer
5.126
962491AG1-098 GEN
Solar/Wind Harmer
16.401
316458AB2-190 GEN2
Solar/Wind Harmer
1.538
970129AG2-093 GEN
Solar/Wind Harmer
8.145
960081AF2-299 GEN
Solar/Wind Harmer
2.73
3138126ROCKLANDING
Solar/Wind Harmer
0.13
3145893MURPHYS
Solar/Wind Harmer
1.134
3145893MURPHYS
Solar/Wind Harmer
1.26
3146206CASHIE
Solar/Wind Harmer
0.283
971547AH1-271 GEN
Solar/Wind Harmer
6.043
3146173TUNIS
Solar/Wind Harmer
0.281
3142543TWELFTH
Solar/Wind Harmer
0.027
3145683EARLEYS
Solar/Wind Harmer
0.279
316011AB1-132 GEN
Solar/Wind Harmer
5.071
962571AG1-106 GEN
Solar/Wind Harmer
3.968
971795AH1-408 GEN
Solar/Wind Harmer
18.591
3146263WOODLND
Solar/Wind Harmer
0.278
316190AA2-174 GEN
Solar/Wind Harmer
0
3147043LAWRENC
Adder
2.5
316336AC2-165 C
Solar/Wind Harmer
0.011
971317AH1-138 GEN
Solar/Wind Harmer
2.057
3145823KELFORD
Solar/Wind Harmer
0.275
3145796HORNRTN
Solar/Wind Harmer
0.907
3145796HORNRTN
Solar/Wind Harmer
0.275
3145783HORNRTN
Solar/Wind Harmer
0.275
3145963POPLR C
Solar/Wind Harmer
0.274
3143096IRON208
Adder
1.147
316174AB2-169 GEN
Solar/Wind Harmer
0.007
316159AE1-175 C
Solar/Wind Harmer
0.235
944631AF1-128 GEN
Adder
128.871
315687AD1-152 GEN
Solar/Wind Harmer
0.009
316212AC1-099_GEN
Solar/Wind Harmer
1.386
316129AC1-054 GEN
Solar/Wind Harmer
1.006
971065AG2-659 GEN
Solar/Wind Harmer
11.378
3146293MARTNCO
Solar/Wind Harmer
0.246
315722AD1-056 GEN
Solar/Wind Harmer
1.662
3145746EVERETS
Solar/Wind Harmer
0.261
3145746EVERETS
Solar/Wind Harmer
0.261
316494AC1-189 GEN
Solar/Wind Harmer
0.872
316237AB2-079_GEN
Solar/Wind Harmer
0.002
3146233WITAKRS
Solar/Wind Harmer
1.019
961671AG1-007 GEN
Solar/Wind Harmer
0.039
3146083TARBORO
Solar/Wind Harmer
0.255
3145493TOT1
Solar/Wind Harmer
1.136
3142433PROV 92
Solar/Wind Harmer
1.012
3142433PROV 92
Adder
0.492
3142433PROV 92
Adder
0.492
316359AB2-059 GEN
Solar/Wind Harmer
0.906
316049AB1-081 GEN
Solar/Wind Harmer
1.444
3145543BTLEBRO
Solar/Wind Harmer
0.252
3145543BTLEBRO
Solar/Wind Harmer
0.202
3142053HEARTS
Solar/Wind Harmer
0.444
970685AG2-442 GEN
Solar/Wind Harmer
18.609
970401AG2-262 GEN
Solar/Wind Harmer
1.452
963171AG1-166 GEN
Solar/Wind Harmer
1.316
971563AH1-280 GEN
Solar/Wind Harmer
2.632
3144293JTRSVLE
Adder
0.785
971777AH1-397 GEN
Solar/Wind Harmer
0.643
3141843SHACKLE
Adder
1.244
3141766HARMONY
Solar/Wind Harmer
0.048
3142416OLDCHRC
Solar/Wind Harmer
0.623
3142416OLDCHRC
Solar/Wind Harmer
0.239
3146926FARMVIL
Solar/Wind Harmer
0.141
3138133OCRAN
Solar/Wind Harmer
0.139
316003AC1-222 GEN
Solar/Wind Harmer
0.006
970937AG2-583 GEN
Solar/Wind Harmer
13.92
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.085
962861AG1-135 GEN
Solar/Wind Harmer
6.647
3141726DUNNSVL
Solar/Wind Harmer
0.786
3150351NORNECKC2
Adder
1.901
972003AH1-546 GEN
Solar/Wind Harmer
8.083
971377AH1-170 GEN
Solar/Wind Harmer
1.823
3147623JAMES R
Solar/Wind Harmer
0.396
316337AD2-073 GEN
Solar/Wind Harmer
0.146
970223AG2-152 GEN
Solar/Wind Harmer
10.672
270016AE1-250 BESS
Solar/Wind Harmer
0.004
3147123OTTER R
Solar/Wind Harmer
0.084
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
3147312GRETNA
Solar/Wind Harmer
0.104
3146802CHATHAM
Solar/Wind Harmer
0.098
941801AE2-185 GEN
Solar/Wind Harmer
4.176
972277AH1-723 GEN
Adder
76.921
270030AE2-140 GEN
Solar/Wind Harmer
12.711
316045AC1-158 PL2
Solar/Wind Helper
7.036
3147666LOUISA
Solar/Wind Helper
1.244
316192AB2-158 GEN
Solar/Wind Helper
2.045
316254AC1-120 GEN1
Solar/Wind Helper
1.287
316006AB2-029 C
Solar/Wind Helper
0.13
3138133OCRAN
Solar/Wind Harmer
0.069
3141783LANCAST
Solar/Wind Harmer
0.137
3141783LANCAST
Solar/Wind Harmer
0.091
962981AG1-147 GEN
Solar/Wind Harmer
8.172
970285AG2-188 GEN
Solar/Wind Harmer
17.223
971845AH1-439 GEN
Solar/Wind Harmer
9.707
970327AG2-215 GEN
Solar/Wind Harmer
7.016
970865AG2-541 GEN
Solar/Wind Harmer
7.314
316123AC1-075 GEN
Solar/Wind Harmer
0.262
970165AG2-112 GEN
Solar/Wind Harmer
1.554
970163AG2-111 GEN
Solar/Wind Harmer
1.483
3141813NORNECK
Solar/Wind Harmer
0.191
972205AH1-687 GEN
Adder
7.916
971447AH1-217 GEN
Solar/Wind Harmer
4.969
270494AE1-108_GEN
Solar/Wind Harmer
1.845
972189AH1-679 GEN
Adder
2.488
316223AC1-118
Solar/Wind Harmer
0.103
972193AH1-681 GEN
Adder
2.949
316164AC1-076 GEN
Solar/Wind Helper
1.496
316411AF1-147_GEN1
Solar/Wind Helper
0.807
316415AF1-147_GEN2
Solar/Wind Helper
0.807
3138216PACIFIC
Solar/Wind Helper
0.039
3142296MT RD221
Adder
0.748
316222AC1-221 GEN
Solar/Wind Harmer
0.912
966871AG1-558 GEN
Solar/Wind Harmer
0.251
3146776BUCKING
Solar/Wind Harmer
0.848
3146776BUCKING
Solar/Wind Harmer
0.069
958261AF2-120 GEN
Solar/Wind Harmer
6.796
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
1.997
3150341NORNECKC1
Adder
1.981
942751AE2-291 GEN
Solar/Wind Harmer
9.768
971489AH1-241 GEN
Solar/Wind Harmer
9.113
316468AD1-105 GEN
Solar/Wind Harmer
-0.049
270013AE1-250 PV
Solar/Wind Harmer
0.004
315821AE2-092 GEN
Solar/Wind Harmer
0.008
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
3.248
316447AC1-158 HLD
Solar/Wind Helper
4.837
315651AD1-115 GEN
Solar/Wind Helper
0.937
226929AD2-058 GEN
Solar/Wind Helper
0.091
LAGNLTFEXP_LAGN->PJM
CLTF
12.487
CBM South 2LTFEXP_CBM-S2->PJM
CBM
36.918
TVALTFEXP_TVA->PJM
CLTF
6.285
CPLELTFEXP_CPLE->PJM
CLTF
16.793
CBM West 2LTFEXP_CBM-W2->PJM
CBM
66.855
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.504
CBM South 1LTFEXP_CBM-S1->PJM
CBM
21.654
MECLTFEXP_MEC->PJM
CLTF
6.28
SIGELTFEXP_SIGE->PJM
CLTF
0.191
NYPJM->LTFIMP_NY
CLTF
3.567
LGEELTFEXP_LGEE->PJM
CLTF
2.341
WECLTFEXP_WEC->PJM
CLTF
1.189
AG2-052LTFEXP_AG2-052->PJM
LTF
0.064
AH1-155LTFEXP_AH1-155->PJM
LTF
0.096

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:154.63 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:6092.43
MW Contribution:13.38
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
6.608
315244AE2-183_ST
50/50
9.677
963041AG1-153 GEN
50/50
8.919
315779AE2-040
50/50
4.458
3151081ELIZAR1
50/50
30.271
3151031BRUNSWICKG2
50/50
4.405
3151101ELIZAR3
50/50
30.659
3150861SPRUNCD
50/50
1.485
3151161SURRY 1
50/50
11.463
970917AG2-570 GEN
Solar/Wind Harmer
90.418
315773AC2-141 GEN
Solar/Wind Harmer
14.817
944581AF1-123 GEN
Solar/Wind Harmer
160.093
944601AF1-125 GEN
Solar/Wind Harmer
157.595
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146456SLIGO L269
Solar/Wind Harmer
-0.035
971153AH1-033 GEN
Solar/Wind Harmer
4.235
3144536CHRHLND
Solar/Wind Harmer
-0.005
315813AE1-149 C
Solar/Wind Harmer
21.552
970659AG2-427 GEN
Solar/Wind Harmer
3.246
316083AB2-161 GEN
Solar/Wind Harmer
5.596
970661AG2-428 GEN
Solar/Wind Harmer
6.491
316320Y1-086
Solar/Wind Harmer
2.02
316435W1029_GEN3
Solar/Wind Harmer
6.192
3146516WINFALL
Solar/Wind Harmer
-0.034
3145336SMITFLD
Solar/Wind Harmer
-0.013
315839AE2-212 C
Solar/Wind Harmer
1.026
3146626S HERTFORD
Solar/Wind Harmer
-0.034
3145273HOLLAND
Solar/Wind Harmer
-0.025
965281AG1-393 GEN
Solar/Wind Harmer
4.197
3151221GRAVEL6
Adder
21.696
3151171GRAVELC
Adder
4.174
316313AB2-026
Solar/Wind Harmer
0.903
316258AE1-075 C
Solar/Wind Harmer
0.813
316405AF2-144 C
Solar/Wind Harmer
0.857
3143336POWHATN
Solar/Wind Harmer
3.376
3146376EDENTON
Solar/Wind Harmer
-0.033
961611AG1-000B GEN
Solar/Wind Harmer
7.019
316365GEN2_N
Solar/Wind Harmer
2.232
315778AD1-151 GEN
Solar/Wind Harmer
28.5
315614AA2-178 GEN
Solar/Wind Harmer
3.547
970129AG2-093 GEN
Solar/Wind Harmer
18.408
3156081AA2-088 GEN
Solar/Wind Harmer
10.555
971157AH1-035 GEN
Solar/Wind Harmer
4.057
3144216WINCHST
Adder
1.088
970133AG2-095 GEN
Solar/Wind Harmer
3.645
316478AD1-087 GEN
Solar/Wind Harmer
2.805
316486AD2-202 GEN
Solar/Wind Harmer
0.821
315737AD1-076 GEN
Solar/Wind Harmer
6.155
966621AG1-532 GEN
Solar/Wind Harmer
0.655
3150921YORKTN3
Adder
7.214
3145893MURPHYS
Solar/Wind Harmer
0.225
3151091ELIZAR2
50/50
29.745
941591AE2-156 GEN
50/50
27.651
3152611GOSPORTB
50/50
4.2
3152621GOSPORTC
50/50
3.565
3152601GOSPORTA
50/50
3.288
971285AH1-108 GEN
50/50
2.43
972263AH1-716 GEN
50/50
172.931
941031AE2-094 GEN
Solar/Wind Harmer
73.475
944011AF1-069 GEN
Solar/Wind Harmer
23.022
970673AG2-436 GEN
Solar/Wind Harmer
80.77
970673AG2-436 GEN
Solar/Wind Harmer
40.896
316233AE1-074 FULL
Solar/Wind Harmer
1.026
971281AH1-106 GEN
Solar/Wind Harmer
6.195
971283AH1-107 GEN
Solar/Wind Harmer
6.195
971967AH1-528 GEN
Solar/Wind Harmer
71.103
970085AG2-068 GEN
Solar/Wind Harmer
22.506
970581AG2-369 GEN
Solar/Wind Harmer
19.356
316315AB2-025 C
Solar/Wind Harmer
0.968
315814AE2-033 C
Solar/Wind Harmer
33.285
3143316POE
Solar/Wind Harmer
-0.139
957871AF2-081 GEN
Solar/Wind Harmer
17.401
319010AE1-072 C
Solar/Wind Harmer
7.024
3146406KITTY HAWK
Solar/Wind Harmer
0.029
316305AF2-043 C
Solar/Wind Harmer
1.044
313526AB2-022
Solar/Wind Harmer
0.93
315833AF1-017_GEN
Solar/Wind Harmer
6.546
316349AD2-085 GEN
Solar/Wind Harmer
3.065
316311AC2-079 GEN
Solar/Wind Harmer
17.383
315835AF2-110_GEN
Solar/Wind Harmer
4.308
3146486SUNBURY
Solar/Wind Harmer
-0.034
3146486SUNBURY
Solar/Wind Harmer
-0.034
316321Z2-027
Solar/Wind Harmer
0.926
3146396TANGLEW
Solar/Wind Harmer
0.632
3145176PASQUOTANK
Solar/Wind Harmer
-0.021
971445AH1-216 GEN
Solar/Wind Harmer
21.053
315611Z1-036_GEN2
Solar/Wind Harmer
8.332
972265AH1-717 GEN
Adder
23.171
3151201GRAVEL4
Adder
21.721
3151191GRAVEL3
Adder
21.446
3151211GRAVEL5
Adder
21.446
3130156CHOWAN
Solar/Wind Harmer
-0.033
3130156CHOWAN
Solar/Wind Harmer
-0.033
316369SG1_INVT
Solar/Wind Harmer
5.9
315816AE2-034 GEN
Solar/Wind Harmer
2.66
316132AB2-190 GEN1
Solar/Wind Harmer
3.31
3130546PLYMOUTH
Solar/Wind Harmer
-0.032
965291AG1-394 GEN
Solar/Wind Harmer
2.878
315732AD1-074 GEN1
Solar/Wind Harmer
6.549
315733AD1-074 GEN2
Solar/Wind Harmer
6.549
315735AD1-075 GEN1
Solar/Wind Harmer
3.275
946281AF1-292 GEN
Solar/Wind Harmer
0.723
316318V4-068
Solar/Wind Harmer
0.802
3145893MURPHYS
Solar/Wind Harmer
-0.086
3145893MURPHYS
Solar/Wind Harmer
-0.032
3146206CASHIE
Solar/Wind Harmer
-0.032
970601AG2-382 GEN
Solar/Wind Harmer
14.071
316087AB2-174 GEN
Solar/Wind Harmer
4.56
3146043SEABORD
Solar/Wind Harmer
-0.032
3145513AHOSKIE
Solar/Wind Harmer
0.277
961941AG1-037 GEN
Solar/Wind Harmer
0.239
3145513AHOSKIE
Solar/Wind Harmer
-0.032
315607AA1-063A GEN
Solar/Wind Harmer
3.21
3145683EARLEYS
Solar/Wind Harmer
-0.063
3145683EARLEYS
Solar/Wind Harmer
-0.032
3145683EARLEYS
Solar/Wind Harmer
-0.032
315652AC1-086 GEN
Solar/Wind Harmer
35.613
3137643SOCKMAN
Solar/Wind Harmer
-0.126
3145796HORNRTN
Solar/Wind Harmer
-0.099
3145796HORNRTN
Solar/Wind Harmer
-0.012
3146033SCOT NK
Solar/Wind Harmer
-0.122
970831AG2-522 GEN
Solar/Wind Harmer
15.209
957831AF2-077 GEN
Solar/Wind Harmer
0.905
3138283WHITEMARSH
Solar/Wind Harmer
0.047
316005AA1-067
Solar/Wind Harmer
0.599
3145746EVERETS
Solar/Wind Harmer
-0.117
3145746EVERETS
Solar/Wind Harmer
-0.03
3145746EVERETS
Solar/Wind Harmer
-0.03
3145746EVERETS
Solar/Wind Harmer
-0.03
970181AG2-120 GEN
Solar/Wind Harmer
3.889
957861AF2-080 GEN
Solar/Wind Harmer
12.812
971167AH1-042 GEN
Solar/Wind Harmer
28.174
316239AB2-077_GEN
Solar/Wind Harmer
0.879
316238AB2-078_GEN
Solar/Wind Harmer
0.879
316420AA1-050 GEN
Solar/Wind Harmer
3.326
315976AC1-164 GENA
Solar/Wind Harmer
30.748
316169AC1-164_GENC
Solar/Wind Harmer
26.564
315975AC1-164 GENB
Solar/Wind Harmer
0.91
3142433PROV 92
Adder
0.503
3142433PROV 92
Adder
0.503
316319Z2-044 C
Solar/Wind Harmer
1.605
3145573BETHELC
Solar/Wind Harmer
-0.029
3145573BETHELC
Solar/Wind Harmer
-0.029
972205AH1-687 GEN
Adder
7.988
972189AH1-679 GEN
Adder
2.712
972193AH1-681 GEN
Adder
3.018
316164AC1-076 GEN
Solar/Wind Helper
1.525
316411AF1-147_GEN1
Solar/Wind Helper
0.816
316415AF1-147_GEN2
Solar/Wind Helper
0.816
3138216PACIFIC
Solar/Wind Helper
0.04
3145893MURPHYS
Solar/Wind Harmer
-0.032
3146206CASHIE
Solar/Wind Harmer
-0.032
957521AF2-046 GEN
Solar/Wind Harmer
25.297
961681AG1-008 GEN
Solar/Wind Harmer
25.297
3146173TUNIS
Solar/Wind Harmer
-0.032
3156021HOLLOMANSOL
Solar/Wind Harmer
4.291
313506AB2-031 GEN
Solar/Wind Harmer
2.559
316463AE2-346 GEN
Solar/Wind Harmer
0.515
316140AB2-099
Solar/Wind Harmer
0.215
962331AG1-082 GEN
Solar/Wind Harmer
3.978
3142666NORTHAMPTON
Solar/Wind Harmer
-0.032
3146263WOODLND
Solar/Wind Harmer
-0.032
3143096IRON208
Adder
1.169
3143096IRON208
Adder
1.146
3147043LAWRENC
Solar/Wind Harmer
-0.019
316317KELFORD C
Solar/Wind Harmer
1.473
3145823KELFORD
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.124
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145963POPLR C
Solar/Wind Harmer
-0.031
316382AG1-145 C
Solar/Wind Harmer
0.939
3142946ENON
Solar/Wind Harmer
-0.01
316210AC1-098 GEN
Solar/Wind Harmer
4.769
3145933PARMELE
Solar/Wind Harmer
-0.03
966801AG1-551 GEN
Solar/Wind Harmer
3.764
315724AD1-057 GEN
Solar/Wind Harmer
1.713
3145746EVERETS
Solar/Wind Harmer
-0.03
3145746EVERETS
Solar/Wind Harmer
-0.03
316327AA2-057 GEN
Solar/Wind Harmer
2.98
970293AG2-193 GEN
Solar/Wind Harmer
3.658
970909AG2-566 GEN
Solar/Wind Harmer
2.77
316131AB2-060 GEN
Solar/Wind Harmer
3.147
3142433PROV 92
Adder
0.503
3142433PROV 92
Adder
0.503
3146233WITAKRS
Solar/Wind Harmer
0.608
3146233WITAKRS
Solar/Wind Harmer
-0.02
3138543CONSLDL
Solar/Wind Harmer
-0.019
3146073TAR RVR
Solar/Wind Harmer
-0.029
3146083TARBORO
Solar/Wind Harmer
-0.029
964241AG1-285 GEN
Solar/Wind Harmer
22.639
3141843SHACKLE
Adder
1.273
3144293JTRSVLE
Adder
0.792
3150351NORNECKC2
Adder
2.004
972255AH1-712 GEN
Adder
67.55
316044AC1-158 PL1
Solar/Wind Helper
2.235
316450AC1-158 RIC
Solar/Wind Helper
0.596
3147666LOUISA
Solar/Wind Helper
0.727
316170AC1-121 GEN2
Solar/Wind Helper
0.437
3141196NOKESVL
Solar/Wind Helper
1.052
3132273ORANGE
Solar/Wind Helper
0.048
227287AC2-120 GEN
Solar/Wind Helper
0.315
226910AB2-157 C
Solar/Wind Helper
0.013
970119AG2-088 GEN
50/50
49.56
315243AE2-183_GT3
50/50
5.597
3151051BRUNSWICKS1
50/50
9.142
3151021BRUNSWICKG1
50/50
4.405
971451AH1-221 GEN
50/50
13.378
3150981CHESPKA
50/50
4.118
3150851SPRUNCC
50/50
1.485
3152331SURRY 2
50/50
12.49
3143226MDLTHAN
Solar/Wind Harmer
-0.042
940641AE2-051 GEN
Solar/Wind Harmer
37.221
939411AE1-173 GEN
Solar/Wind Harmer
192.62
3143526WINTERP
Solar/Wind Harmer
-0.197
970919AG2-571 GEN
Solar/Wind Harmer
11.445
970087AG2-069 GEN
Solar/Wind Harmer
33.76
316294AC1-161 GEN
Solar/Wind Harmer
11.456
944591AF1-124 GEN
Solar/Wind Harmer
160.67
316375AC2-012 GEN
Solar/Wind Harmer
12.086
316388AE2-253 GEN
Solar/Wind Harmer
2.349
3146456SLIGO L269
Solar/Wind Harmer
-0.035
316246AF1-032 C
Solar/Wind Harmer
0.701
970659AG2-427 GEN
Solar/Wind Harmer
18.316
316381AD1-082 GEN
Solar/Wind Harmer
3.162
970661AG2-428 GEN
Solar/Wind Harmer
36.628
316093AE2-104_GEN
Solar/Wind Harmer
10.019
316072AD1-144
Solar/Wind Harmer
0.693
3146516WINFALL
Solar/Wind Harmer
-0.11
3146516WINFALL
Solar/Wind Harmer
-0.034
3145336SMITFLD
Solar/Wind Harmer
-0.136
957481AF2-042 GEN
Solar/Wind Harmer
105.713
315800Z1-036_GEN1
Solar/Wind Harmer
8.332
3151171GRAVELC
Adder
3.174
3143336POWHATN
Solar/Wind Harmer
3.972
3130156CHOWAN
Solar/Wind Harmer
-0.033
961611AG1-000B GEN
Solar/Wind Harmer
16.45
315671AE2-027_GEN
Solar/Wind Harmer
24.982
971647AH1-324 GEN
Solar/Wind Harmer
16.587
316023GEN1_S
Solar/Wind Harmer
2.232
971069AG2-661 GEN
Solar/Wind Harmer
5.205
3145663CRESWEL
Solar/Wind Harmer
-0.092
971163AH1-040 GEN
Solar/Wind Harmer
30.822
316458AB2-190 GEN2
Solar/Wind Harmer
3.31
315693AD1-088 GEN
Solar/Wind Harmer
16.359
970129AG2-093 GEN
Solar/Wind Harmer
7.456
962491AG1-098 GEN
Solar/Wind Harmer
21.758
3138126ROCKLANDING
Solar/Wind Harmer
0.099
960081AF2-299 GEN
Solar/Wind Harmer
3.629
3145893MURPHYS
Solar/Wind Harmer
-0.128
3145893MURPHYS
Solar/Wind Harmer
0.955
3142543TWELFTH
Solar/Wind Harmer
-0.003
3146206CASHIE
Solar/Wind Harmer
-0.032
971547AH1-271 GEN
Solar/Wind Harmer
8.041
3146173TUNIS
Solar/Wind Harmer
-0.032
3145683EARLEYS
Solar/Wind Harmer
-0.032
316011AB1-132 GEN
Solar/Wind Harmer
6.623
962571AG1-106 GEN
Solar/Wind Harmer
4.551
971795AH1-408 GEN
Solar/Wind Harmer
23.72
3146263WOODLND
Solar/Wind Harmer
-0.032
971317AH1-138 GEN
Solar/Wind Harmer
3.934
316190AA2-174 GEN
Solar/Wind Harmer
0.386
3143096IRON208
Adder
1.169
3147043LAWRENC
Adder
2.523
316336AC2-165 C
Solar/Wind Harmer
5.44
3145823KELFORD
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.102
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145783HORNRTN
Solar/Wind Harmer
-0.031
3145963POPLR C
Solar/Wind Harmer
-0.031
316159AE1-175 C
Solar/Wind Harmer
0.836
944631AF1-128 GEN
Adder
131.354
316174AB2-169 GEN
Solar/Wind Harmer
4.773
315687AD1-152 GEN
Solar/Wind Harmer
3.672
316212AC1-099_GEN
Solar/Wind Harmer
2.649
316129AC1-054 GEN
Solar/Wind Harmer
2.658
971065AG2-659 GEN
Solar/Wind Harmer
15.113
3146293MARTNCO
Solar/Wind Harmer
0.186
315722AD1-056 GEN
Solar/Wind Harmer
3.115
3145746EVERETS
Solar/Wind Harmer
-0.03
3145746EVERETS
Solar/Wind Harmer
-0.03
316494AC1-189 GEN
Solar/Wind Harmer
3.151
316237AB2-079_GEN
Solar/Wind Harmer
0.879
3142433PROV 92
Solar/Wind Harmer
-0.116
3142433PROV 92
Adder
0.503
3142433PROV 92
Adder
0.503
3146233WITAKRS
Solar/Wind Harmer
-0.115
961671AG1-007 GEN
Solar/Wind Harmer
0.366
3146083TARBORO
Solar/Wind Harmer
-0.029
3145493TOT1
Solar/Wind Harmer
0.86
3141843SHACKLE
Adder
1.273
3144293JTRSVLE
Adder
0.792
3150351NORNECKC2
Adder
1.971
972277AH1-723 GEN
Adder
78.716
316045AC1-158 PL2
Solar/Wind Helper
7.153
3147666LOUISA
Solar/Wind Helper
1.265
316192AB2-158 GEN
Solar/Wind Helper
2.08
316254AC1-120 GEN1
Solar/Wind Helper
1.311
316006AB2-029 C
Solar/Wind Helper
0.132
970533AG2-339 GEN
50/50
31.002
970531AG2-338 GEN
50/50
12.401
315242AE2-183_GT2
50/50
5.597
315241AE2-183_GT1
50/50
5.563
972185AH1-677 GEN
50/50
20.179
3151041BRUNSWICKG3
50/50
4.405
972187AH1-678 GEN
50/50
10.108
3150991CHESPKB
50/50
3.455
3150991CHESPKB
50/50
3.372
971223AH1-071 GEN
Solar/Wind Harmer
5.22
3143526WINTERP
Solar/Wind Harmer
-0.197
970933AG2-581 GEN
Solar/Wind Harmer
34.405
3144356SAPONY
Solar/Wind Harmer
1.252
316185AD1-033 GEN
Solar/Wind Harmer
3.69
3142956BIRDNECK
Solar/Wind Harmer
1.875
316316AC1-027 C
Solar/Wind Harmer
1.073
316036AC1-147 C
Solar/Wind Harmer
0.942
3145506HICKORY
Solar/Wind Harmer
-0.139
3145506HICKORY
Solar/Wind Harmer
-0.083
3145506HICKORY
Solar/Wind Harmer
-0.021
316339AD2-160 GEN
Solar/Wind Harmer
2.349
316018AA1-139 ULT2
Solar/Wind Harmer
2.981
316017AA1-139 ULT1
Solar/Wind Harmer
2.816
3137176SLIGO L2192
Solar/Wind Harmer
-0.137
3146456SLIGO L269
Solar/Wind Harmer
4.103
3130086AYDLETT
Solar/Wind Harmer
-0.138
970657AG2-426 GEN
Solar/Wind Harmer
10.774
970657AG2-426 GEN
Solar/Wind Harmer
2.253
3146386ELIZ CT
Solar/Wind Harmer
-0.034
316431W1029_GEN1
Solar/Wind Harmer
6.192
316433W1029_GEN2
Solar/Wind Harmer
6.192
3146516WINFALL
Solar/Wind Harmer
-0.034
3146516WINFALL
Solar/Wind Harmer
-0.034
3146516WINFALL
Solar/Wind Harmer
-0.034
316236AE1-162_GEN
Solar/Wind Harmer
1.027
3146626S HERTFORD
Solar/Wind Harmer
-0.034
3146626S HERTFORD
Solar/Wind Harmer
-0.034
970099AG2-077 GEN
Solar/Wind Harmer
42.285
315742AE1-103 GEN
Solar/Wind Harmer
3.51
3146376EDENTON
Solar/Wind Harmer
0.992
3146376EDENTON
Solar/Wind Harmer
0.992
316240AF1-291 C
Solar/Wind Harmer
1
316033AB2-134 GEN
Solar/Wind Harmer
10.649
315697AD1-025 GEN
Solar/Wind Harmer
6.679
944641AF1-129 GEN
Adder
139.506
316065AD1-022 GEN
Solar/Wind Harmer
16.121
3145893MURPHYS
Solar/Wind Harmer
0.898
3145893MURPHYS
Solar/Wind Harmer
-0.058
3146173TUNIS
Solar/Wind Harmer
-0.032
3146173TUNIS
Solar/Wind Harmer
-0.032
316181AB2-040 GEN
Solar/Wind Harmer
4.441
3142666NORTHAMPTON
Solar/Wind Harmer
-0.032
3142666NORTHAMPTON
Solar/Wind Harmer
-0.032
3142666NORTHAMPTON
Solar/Wind Harmer
-0.032
3142666NORTHAMPTON
Solar/Wind Harmer
-0.019
316426AA2-053 GEN
Solar/Wind Harmer
3.174
3145593CAROLNA
Solar/Wind Harmer
-0.031
3145593CAROLNA
Solar/Wind Harmer
-0.031
966811AG1-552 GEN
Solar/Wind Harmer
3.528
3145593CAROLNA
Solar/Wind Harmer
0.26
3145796HORNRTN
Solar/Wind Harmer
-0.093
3145783HORNRTN
Solar/Wind Harmer
3.7
3145783HORNRTN
Solar/Wind Harmer
2.96
3145783HORNRTN
Solar/Wind Harmer
0.925
3145783HORNRTN
Solar/Wind Harmer
0.37
3142946ENON
Solar/Wind Harmer
-0.003
316274AC1-208 GEN
Solar/Wind Harmer
3.264
3145933PARMELE
Solar/Wind Harmer
-0.06
3145933PARMELE
Solar/Wind Harmer
-0.03
971741AH1-377 GEN
Solar/Wind Harmer
34.86
3142366NRTHEST
Adder
0.864
939181AE1-148 GEN
Solar/Wind Harmer
16.686
3150691DARBY 3
Adder
18.921
3150701DARBY 4
Adder
18.877
3150681DARBY 2
Adder
18.855
3150671DARBY 1
Adder
18.833
313527AB2-043 GEN
Solar/Wind Harmer
4.747
970301AG2-198 GEN
Solar/Wind Harmer
14.587
3145493TOT1
Solar/Wind Harmer
0.448
3145453TOT5
Solar/Wind Harmer
0.269
3145603CNETO
Solar/Wind Harmer
0.179
3144293JTRSVLE
Adder
0.792
3144293JTRSVLE
Adder
0.667
3142296MT RD221
Adder
0.77
3150341NORNECKC1
Adder
2.071
3150341NORNECKC1
Adder
2.054
316447AC1-158 HLD
Solar/Wind Helper
4.918
315651AD1-115 GEN
Solar/Wind Helper
0.954
226929AD2-058 GEN
Solar/Wind Helper
0.092
316075AC2-137 C
Solar/Wind Harmer
0.319
LAGNLTFEXP_LAGN->PJM
CLTF
12.593
CBM South 2LTFEXP_CBM-S2->PJM
CBM
37.232
TVALTFEXP_TVA->PJM
CLTF
6.338
CPLELTFEXP_CPLE->PJM
CLTF
16.935
CBM West 2LTFEXP_CBM-W2->PJM
CBM
67.417
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.824
CBM South 1LTFEXP_CBM-S1->PJM
CBM
21.839
MECLTFEXP_MEC->PJM
CLTF
6.331
SIGELTFEXP_SIGE->PJM
CLTF
0.193
NYPJM->LTFIMP_NY
CLTF
3.61
LGEELTFEXP_LGEE->PJM
CLTF
2.36
WECLTFEXP_WEC->PJM
CLTF
1.198
AG2-052LTFEXP_AG2-052->PJM
LTF
0.064
AH1-155LTFEXP_AH1-155->PJM
LTF
0.097

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 557T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:154.23 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:6076.8
MW Contribution:13.94
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
6.615
315244AE2-183_ST
50/50
10.085
963041AG1-153 GEN
50/50
9.293
3151081ELIZAR1
50/50
32.533
3151091ELIZAR2
50/50
31.968
941591AE2-156 GEN
50/50
29.713
3152611GOSPORTB
50/50
4.513
3152621GOSPORTC
50/50
3.83
3151031BRUNSWICKG2
50/50
4.589
3151101ELIZAR3
50/50
32.949
3151161SURRY 1
50/50
12.195
315773AC2-141 GEN
Solar/Wind Harmer
16.075
944581AF1-123 GEN
Solar/Wind Harmer
172.322
944601AF1-125 GEN
Solar/Wind Harmer
169.633
970917AG2-570 GEN
Solar/Wind Harmer
94.165
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146456SLIGO L269
Solar/Wind Harmer
-0.037
971153AH1-033 GEN
Solar/Wind Harmer
4.547
3144536CHRHLND
Solar/Wind Harmer
-0.006
316320Y1-086
Solar/Wind Harmer
2.165
316435W1029_GEN3
Solar/Wind Harmer
6.628
3146516WINFALL
Solar/Wind Harmer
-0.036
3145336SMITFLD
Solar/Wind Harmer
-0.014
3146626S HERTFORD
Solar/Wind Harmer
-0.036
970661AG2-428 GEN
Solar/Wind Harmer
6.819
316083AB2-161 GEN
Solar/Wind Harmer
5.857
3145273HOLLAND
Solar/Wind Harmer
-0.027
970659AG2-427 GEN
Solar/Wind Harmer
3.393
315813AE1-149 C
Solar/Wind Harmer
22.383
3151221GRAVEL6
Adder
23.081
3151171GRAVELC
Adder
4.441
3146376EDENTON
Solar/Wind Harmer
-0.036
961611AG1-000B GEN
Solar/Wind Harmer
7.432
3144216WINCHST
Adder
1.179
3150921YORKTN3
Adder
7.837
315614AA2-178 GEN
Solar/Wind Harmer
3.774
315839AE2-212 C
Solar/Wind Harmer
1.048
316365GEN2_N
Solar/Wind Harmer
2.328
315778AD1-151 GEN
Solar/Wind Harmer
29.865
971157AH1-035 GEN
Solar/Wind Harmer
4.308
965281AG1-393 GEN
Solar/Wind Harmer
4.3
315737AD1-076 GEN
Solar/Wind Harmer
6.532
3156081AA2-088 GEN
Solar/Wind Harmer
11.148
3150861SPRUNCD
Adder
1.401
970129AG2-093 GEN
Solar/Wind Harmer
19.191
3146206CASHIE
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.237
3145893MURPHYS
Solar/Wind Harmer
-0.034
957521AF2-046 GEN
Solar/Wind Harmer
26.697
961681AG1-008 GEN
Solar/Wind Harmer
26.697
316382AG1-145 C
Solar/Wind Harmer
1.02
3146173TUNIS
Solar/Wind Harmer
-0.034
3156021HOLLOMANSOL
Solar/Wind Harmer
4.534
966621AG1-532 GEN
Solar/Wind Harmer
0.682
316478AD1-087 GEN
Solar/Wind Harmer
2.909
316486AD2-202 GEN
Solar/Wind Harmer
0.852
316463AE2-346 GEN
Solar/Wind Harmer
0.543
316140AB2-099
Solar/Wind Harmer
0.226
962331AG1-082 GEN
Solar/Wind Harmer
4.197
970133AG2-095 GEN
Solar/Wind Harmer
3.773
316313AB2-026
Solar/Wind Harmer
0.901
316258AE1-075 C
Solar/Wind Harmer
0.811
316405AF2-144 C
Solar/Wind Harmer
0.856
3143336POWHATN
Solar/Wind Harmer
3.371
3146263WOODLND
Solar/Wind Harmer
-0.033
313506AB2-031 GEN
Solar/Wind Harmer
2.672
3142666NORTHAMPTON
Solar/Wind Harmer
-0.033
3145963POPLR C
Solar/Wind Harmer
-0.033
316317KELFORD C
Solar/Wind Harmer
1.55
3145823KELFORD
Solar/Wind Harmer
-0.033
3145796HORNRTN
Solar/Wind Harmer
-0.13
3145796HORNRTN
Solar/Wind Harmer
-0.033
3147043LAWRENC
Solar/Wind Harmer
-0.019
3142946ENON
Solar/Wind Harmer
-0.01
3143096IRON208
Adder
1.188
3143096IRON208
Adder
1.164
316210AC1-098 GEN
Solar/Wind Harmer
5
3145933PARMELE
Solar/Wind Harmer
-0.032
966801AG1-551 GEN
Solar/Wind Harmer
3.962
3145746EVERETS
Solar/Wind Harmer
-0.031
3145746EVERETS
Solar/Wind Harmer
-0.031
315724AD1-057 GEN
Solar/Wind Harmer
1.79
316327AA2-057 GEN
Solar/Wind Harmer
3.117
3142433PROV 92
Adder
0.53
3142433PROV 92
Adder
0.53
3146233WITAKRS
Solar/Wind Harmer
0.636
3146233WITAKRS
Solar/Wind Harmer
-0.02
3146073TAR RVR
Solar/Wind Harmer
-0.03
3146083TARBORO
Solar/Wind Harmer
-0.03
3138543CONSLDL
Solar/Wind Harmer
-0.02
316131AB2-060 GEN
Solar/Wind Harmer
3.254
3141843SHACKLE
Adder
1.366
316203AE2-005 GEN
Solar/Wind Harmer
12.66
316280AD1-041 GEN
Solar/Wind Harmer
2.258
3144293JTRSVLE
Adder
0.813
3150351NORNECKC2
Adder
2.146
316044AC1-158 PL1
Solar/Wind Helper
2.186
316450AC1-158 RIC
Solar/Wind Helper
0.583
3147666LOUISA
Solar/Wind Helper
0.716
316170AC1-121 GEN2
Solar/Wind Helper
0.43
3141196NOKESVL
Solar/Wind Helper
1.041
3132273ORANGE
Solar/Wind Helper
0.048
227287AC2-120 GEN
Solar/Wind Helper
0.313
226910AB2-157 C
Solar/Wind Helper
0.013
970909AG2-566 GEN
Solar/Wind Harmer
2.713
970119AG2-088 GEN
50/50
49.614
315243AE2-183_GT3
50/50
5.833
3151051BRUNSWICKS1
50/50
9.525
3151021BRUNSWICKG1
50/50
4.589
971451AH1-221 GEN
50/50
13.939
3150981CHESPKA
50/50
4.425
3152331SURRY 2
50/50
13.773
3143226MDLTHAN
Solar/Wind Harmer
-0.042
940641AE2-051 GEN
Solar/Wind Harmer
39.09
939411AE1-173 GEN
Solar/Wind Harmer
203.387
316294AC1-161 GEN
Solar/Wind Harmer
12.429
3143526WINTERP
Solar/Wind Harmer
-0.197
944591AF1-124 GEN
Solar/Wind Harmer
172.943
970919AG2-571 GEN
Solar/Wind Harmer
11.92
316375AC2-012 GEN
Solar/Wind Harmer
12.985
970087AG2-069 GEN
Solar/Wind Harmer
35.157
316388AE2-253 GEN
Solar/Wind Harmer
2.523
3146456SLIGO L269
Solar/Wind Harmer
-0.037
316246AF1-032 C
Solar/Wind Harmer
0.751
316093AE2-104_GEN
Solar/Wind Harmer
10.699
316072AD1-144
Solar/Wind Harmer
0.743
3146516WINFALL
Solar/Wind Harmer
-0.118
3146516WINFALL
Solar/Wind Harmer
-0.036
3145336SMITFLD
Solar/Wind Harmer
-0.145
970661AG2-428 GEN
Solar/Wind Harmer
38.478
316381AD1-082 GEN
Solar/Wind Harmer
3.31
970659AG2-427 GEN
Solar/Wind Harmer
19.149
315800Z1-036_GEN1
Solar/Wind Harmer
8.901
3151171GRAVELC
Adder
3.377
3130156CHOWAN
Solar/Wind Harmer
-0.036
961611AG1-000B GEN
Solar/Wind Harmer
17.419
957481AF2-042 GEN
Solar/Wind Harmer
109.742
3138126ROCKLANDING
Solar/Wind Harmer
0.108
971647AH1-324 GEN
Solar/Wind Harmer
17.499
3145663CRESWEL
Solar/Wind Harmer
-0.097
971163AH1-040 GEN
Solar/Wind Harmer
32.791
316023GEN1_S
Solar/Wind Harmer
2.328
971069AG2-661 GEN
Solar/Wind Harmer
5.455
971317AH1-138 GEN
Solar/Wind Harmer
4.281
3150851SPRUNCC
Adder
1.401
316458AB2-190 GEN2
Solar/Wind Harmer
3.453
315671AE2-027_GEN
Solar/Wind Harmer
25.569
970129AG2-093 GEN
Solar/Wind Harmer
7.774
3146206CASHIE
Solar/Wind Harmer
-0.034
971547AH1-271 GEN
Solar/Wind Harmer
8.518
3145893MURPHYS
Solar/Wind Harmer
-0.135
3145893MURPHYS
Solar/Wind Harmer
1.008
315693AD1-088 GEN
Solar/Wind Harmer
16.949
316159AE1-175 C
Solar/Wind Harmer
0.909
3146173TUNIS
Solar/Wind Harmer
-0.034
962491AG1-098 GEN
Solar/Wind Harmer
22.532
960081AF2-299 GEN
Solar/Wind Harmer
3.783
3145683EARLEYS
Solar/Wind Harmer
-0.033
3143336POWHATN
Solar/Wind Harmer
3.966
3146263WOODLND
Solar/Wind Harmer
-0.033
316011AB1-132 GEN
Solar/Wind Harmer
6.928
962571AG1-106 GEN
Solar/Wind Harmer
4.76
3145963POPLR C
Solar/Wind Harmer
-0.033
316190AA2-174 GEN
Solar/Wind Harmer
0.404
971795AH1-408 GEN
Solar/Wind Harmer
24.687
3145823KELFORD
Solar/Wind Harmer
-0.033
316174AB2-169 GEN
Solar/Wind Harmer
5.041
3145796HORNRTN
Solar/Wind Harmer
-0.107
3145796HORNRTN
Solar/Wind Harmer
-0.033
3145783HORNRTN
Solar/Wind Harmer
-0.033
3147043LAWRENC
Adder
2.624
3142543TWELFTH
Solar/Wind Harmer
-0.003
944631AF1-128 GEN
Adder
136.543
3143096IRON208
Adder
1.188
316212AC1-099_GEN
Solar/Wind Harmer
2.778
3146293MARTNCO
Solar/Wind Harmer
0.196
315687AD1-152 GEN
Solar/Wind Harmer
3.804
316129AC1-054 GEN
Solar/Wind Harmer
2.766
971065AG2-659 GEN
Solar/Wind Harmer
15.722
316336AC2-165 C
Solar/Wind Harmer
5.426
3145746EVERETS
Solar/Wind Harmer
-0.031
3145746EVERETS
Solar/Wind Harmer
-0.031
315722AD1-056 GEN
Solar/Wind Harmer
3.254
316494AC1-189 GEN
Solar/Wind Harmer
3.304
3142433PROV 92
Solar/Wind Harmer
-0.122
3142433PROV 92
Adder
0.53
3142433PROV 92
Adder
0.53
3146233WITAKRS
Solar/Wind Harmer
-0.12
961671AG1-007 GEN
Solar/Wind Harmer
0.384
3146083TARBORO
Solar/Wind Harmer
-0.03
3145493TOT1
Solar/Wind Harmer
0.9
316237AB2-079_GEN
Solar/Wind Harmer
0.91
971777AH1-397 GEN
Solar/Wind Harmer
3.531
3141843SHACKLE
Adder
1.366
3152601GOSPORTA
50/50
3.533
315779AE2-040
50/50
4.628
972263AH1-716 GEN
50/50
190.384
941031AE2-094 GEN
Solar/Wind Harmer
76.612
944011AF1-069 GEN
Solar/Wind Harmer
24.005
970673AG2-436 GEN
Solar/Wind Harmer
84.191
970673AG2-436 GEN
Solar/Wind Harmer
42.628
971967AH1-528 GEN
Solar/Wind Harmer
74.07
316233AE1-074 FULL
Solar/Wind Harmer
1.025
971281AH1-106 GEN
Solar/Wind Harmer
6.19
971283AH1-107 GEN
Solar/Wind Harmer
6.19
970085AG2-068 GEN
Solar/Wind Harmer
23.438
970581AG2-369 GEN
Solar/Wind Harmer
20.157
957871AF2-081 GEN
Solar/Wind Harmer
18.688
319010AE1-072 C
Solar/Wind Harmer
7.541
3146406KITTY HAWK
Solar/Wind Harmer
0.031
316315AB2-025 C
Solar/Wind Harmer
1.005
316305AF2-043 C
Solar/Wind Harmer
1.119
315814AE2-033 C
Solar/Wind Harmer
34.559
313526AB2-022
Solar/Wind Harmer
0.997
3146486SUNBURY
Solar/Wind Harmer
-0.037
3146486SUNBURY
Solar/Wind Harmer
-0.037
316321Z2-027
Solar/Wind Harmer
0.993
3146396TANGLEW
Solar/Wind Harmer
0.677
3145176PASQUOTANK
Solar/Wind Harmer
-0.023
315835AF2-110_GEN
Solar/Wind Harmer
4.6
316311AC2-079 GEN
Solar/Wind Harmer
18.424
315833AF1-017_GEN
Solar/Wind Harmer
6.937
316349AD2-085 GEN
Solar/Wind Harmer
3.248
3143316POE
Solar/Wind Harmer
-0.143
971445AH1-216 GEN
Solar/Wind Harmer
22.478
315611Z1-036_GEN2
Solar/Wind Harmer
8.901
972265AH1-717 GEN
Adder
24.649
3151201GRAVEL4
Adder
23.107
3151191GRAVEL3
Adder
22.815
3151211GRAVEL5
Adder
22.815
3130156CHOWAN
Solar/Wind Harmer
-0.036
3130156CHOWAN
Solar/Wind Harmer
-0.036
315816AE2-034 GEN
Solar/Wind Harmer
2.83
316369SG1_INVT
Solar/Wind Harmer
6.201
3130546PLYMOUTH
Solar/Wind Harmer
-0.034
315732AD1-074 GEN1
Solar/Wind Harmer
6.95
315733AD1-074 GEN2
Solar/Wind Harmer
6.95
315735AD1-075 GEN1
Solar/Wind Harmer
3.476
965291AG1-394 GEN
Solar/Wind Harmer
3.038
971285AH1-108 GEN
Adder
2.292
316132AB2-190 GEN1
Solar/Wind Harmer
3.453
3146206CASHIE
Solar/Wind Harmer
-0.034
970601AG2-382 GEN
Solar/Wind Harmer
14.907
316318V4-068
Solar/Wind Harmer
0.847
3145893MURPHYS
Solar/Wind Harmer
-0.091
3145893MURPHYS
Solar/Wind Harmer
-0.034
946281AF1-292 GEN
Solar/Wind Harmer
0.753
3145513AHOSKIE
Solar/Wind Harmer
0.293
961941AG1-037 GEN
Solar/Wind Harmer
0.252
3145513AHOSKIE
Solar/Wind Harmer
-0.033
3146043SEABORD
Solar/Wind Harmer
-0.033
3145683EARLEYS
Solar/Wind Harmer
-0.066
3145683EARLEYS
Solar/Wind Harmer
-0.033
3145683EARLEYS
Solar/Wind Harmer
-0.033
315607AA1-063A GEN
Solar/Wind Harmer
3.371
316087AB2-174 GEN
Solar/Wind Harmer
4.759
315652AC1-086 GEN
Solar/Wind Harmer
37.252
3137643SOCKMAN
Solar/Wind Harmer
-0.131
3145796HORNRTN
Solar/Wind Harmer
-0.104
3145796HORNRTN
Solar/Wind Harmer
-0.013
957831AF2-077 GEN
Solar/Wind Harmer
0.98
3138283WHITEMARSH
Solar/Wind Harmer
0.05
3146033SCOT NK
Solar/Wind Harmer
-0.129
970831AG2-522 GEN
Solar/Wind Harmer
15.839
315976AC1-164 GENA
Solar/Wind Harmer
33.15
316169AC1-164_GENC
Solar/Wind Harmer
28.639
315975AC1-164 GENB
Solar/Wind Harmer
0.981
316005AA1-067
Solar/Wind Harmer
0.63
3145746EVERETS
Solar/Wind Harmer
-0.123
3145746EVERETS
Solar/Wind Harmer
-0.031
3145746EVERETS
Solar/Wind Harmer
-0.031
3145746EVERETS
Solar/Wind Harmer
-0.031
970181AG2-120 GEN
Solar/Wind Harmer
4.087
971167AH1-042 GEN
Solar/Wind Harmer
29.578
957861AF2-080 GEN
Solar/Wind Harmer
13.434
3142433PROV 92
Adder
0.53
3142433PROV 92
Adder
0.53
316420AA1-050 GEN
Solar/Wind Harmer
3.484
316319Z2-044 C
Solar/Wind Harmer
1.678
3145573BETHELC
Solar/Wind Harmer
-0.03
3145573BETHELC
Solar/Wind Harmer
-0.03
3143873LANEXA
Solar/Wind Harmer
-0.018
316239AB2-077_GEN
Solar/Wind Harmer
0.91
316238AB2-078_GEN
Solar/Wind Harmer
0.91
316314AB2-024 C
Solar/Wind Harmer
2.562
315662AE1-191 GEN
Solar/Wind Harmer
3.613
315666AE1-190 GEN
Solar/Wind Harmer
0.903
972205AH1-687 GEN
Adder
7.91
972189AH1-679 GEN
Adder
2.347
316164AC1-076 GEN
Solar/Wind Helper
1.495
316411AF1-147_GEN1
Solar/Wind Helper
0.81
316415AF1-147_GEN2
Solar/Wind Helper
0.81
3138216PACIFIC
Solar/Wind Helper
0.04
3144293JTRSVLE
Adder
0.813
3150351NORNECKC2
Adder
2.111
316045AC1-158 PL2
Solar/Wind Helper
6.998
3147666LOUISA
Solar/Wind Helper
1.245
316192AB2-158 GEN
Solar/Wind Helper
2.049
316254AC1-120 GEN1
Solar/Wind Helper
1.291
316006AB2-029 C
Solar/Wind Helper
0.13
970533AG2-339 GEN
50/50
32.326
970531AG2-338 GEN
50/50
12.93
315242AE2-183_GT2
50/50
5.833
315241AE2-183_GT1
50/50
5.797
972185AH1-677 GEN
50/50
21.03
3151041BRUNSWICKG3
50/50
4.589
972187AH1-678 GEN
50/50
10.532
3150991CHESPKB
50/50
3.712
3150991CHESPKB
50/50
3.623
971223AH1-071 GEN
Solar/Wind Harmer
5.226
970933AG2-581 GEN
Solar/Wind Harmer
35.807
3143526WINTERP
Solar/Wind Harmer
-0.197
316185AD1-033 GEN
Solar/Wind Harmer
3.966
3142956BIRDNECK
Solar/Wind Harmer
2.015
316316AC1-027 C
Solar/Wind Harmer
1.153
316036AC1-147 C
Solar/Wind Harmer
1.012
3145506HICKORY
Solar/Wind Harmer
-0.149
3145506HICKORY
Solar/Wind Harmer
-0.09
3145506HICKORY
Solar/Wind Harmer
-0.022
316339AD2-160 GEN
Solar/Wind Harmer
2.523
316018AA1-139 ULT2
Solar/Wind Harmer
3.202
316017AA1-139 ULT1
Solar/Wind Harmer
3.024
3137176SLIGO L2192
Solar/Wind Harmer
-0.148
3146456SLIGO L269
Solar/Wind Harmer
4.406
3130086AYDLETT
Solar/Wind Harmer
-0.148
3144356SAPONY
Solar/Wind Harmer
1.299
3146386ELIZ CT
Solar/Wind Harmer
-0.037
316431W1029_GEN1
Solar/Wind Harmer
6.628
316433W1029_GEN2
Solar/Wind Harmer
6.628
3146516WINFALL
Solar/Wind Harmer
-0.036
3146516WINFALL
Solar/Wind Harmer
-0.036
3146516WINFALL
Solar/Wind Harmer
-0.036
316236AE1-162_GEN
Solar/Wind Harmer
1.097
3146626S HERTFORD
Solar/Wind Harmer
-0.036
3146626S HERTFORD
Solar/Wind Harmer
-0.036
970657AG2-426 GEN
Solar/Wind Harmer
11.293
970657AG2-426 GEN
Solar/Wind Harmer
2.361
315742AE1-103 GEN
Solar/Wind Harmer
3.73
3146376EDENTON
Solar/Wind Harmer
1.058
3146376EDENTON
Solar/Wind Harmer
1.058
970099AG2-077 GEN
Solar/Wind Harmer
43.897
316033AB2-134 GEN
Solar/Wind Harmer
11.193
315697AD1-025 GEN
Solar/Wind Harmer
7.02
316065AD1-022 GEN
Solar/Wind Harmer
17.09
3145893MURPHYS
Solar/Wind Harmer
0.948
3145893MURPHYS
Solar/Wind Harmer
-0.061
316240AF1-291 C
Solar/Wind Harmer
1.017
3146173TUNIS
Solar/Wind Harmer
-0.034
3146173TUNIS
Solar/Wind Harmer
-0.034
944641AF1-129 GEN
Adder
141.653
316181AB2-040 GEN
Solar/Wind Harmer
4.638
3142666NORTHAMPTON
Solar/Wind Harmer
-0.033
3142666NORTHAMPTON
Solar/Wind Harmer
-0.033
3142666NORTHAMPTON
Solar/Wind Harmer
-0.033
3142666NORTHAMPTON
Solar/Wind Harmer
-0.02
316426AA2-053 GEN
Solar/Wind Harmer
3.327
3145593CAROLNA
Solar/Wind Harmer
-0.033
3145593CAROLNA
Solar/Wind Harmer
-0.033
966811AG1-552 GEN
Solar/Wind Harmer
3.692
3145593CAROLNA
Solar/Wind Harmer
0.273
3145796HORNRTN
Solar/Wind Harmer
-0.097
3145783HORNRTN
Solar/Wind Harmer
3.873
3145783HORNRTN
Solar/Wind Harmer
3.098
3145783HORNRTN
Solar/Wind Harmer
0.968
3145783HORNRTN
Solar/Wind Harmer
0.387
3142946ENON
Solar/Wind Harmer
-0.003
3145933PARMELE
Solar/Wind Harmer
-0.063
3145933PARMELE
Solar/Wind Harmer
-0.032
316274AC1-208 GEN
Solar/Wind Harmer
3.418
971741AH1-377 GEN
Solar/Wind Harmer
35.868
939181AE1-148 GEN
Solar/Wind Harmer
17.303
3145493TOT1
Solar/Wind Harmer
0.469
3145453TOT5
Solar/Wind Harmer
0.282
3145603CNETO
Solar/Wind Harmer
0.188
316075AC2-137 C
Solar/Wind Harmer
0.818
313527AB2-043 GEN
Solar/Wind Harmer
4.909
316441AF1-014 GEN
Solar/Wind Harmer
2.024
3150691DARBY 3
Adder
18.946
3150701DARBY 4
Adder
18.902
3150681DARBY 2
Adder
18.88
3150671DARBY 1
Adder
18.858
3142366NRTHEST
Adder
0.854
3144293JTRSVLE
Adder
0.813
3144293JTRSVLE
Adder
0.685
3142296MT RD221
Adder
0.722
3150341NORNECKC1
Adder
2.217
3150341NORNECKC1
Adder
2.199
316447AC1-158 HLD
Solar/Wind Helper
4.811
315651AD1-115 GEN
Solar/Wind Helper
0.939
226929AD2-058 GEN
Solar/Wind Helper
0.091
970301AG2-198 GEN
Solar/Wind Harmer
14.287
LAGNLTFEXP_LAGN->PJM
CLTF
12.7
CBM South 2LTFEXP_CBM-S2->PJM
CBM
38.248
TVALTFEXP_TVA->PJM
CLTF
6.385
CPLELTFEXP_CPLE->PJM
CLTF
17.51
CBM West 2LTFEXP_CBM-W2->PJM
CBM
67.525
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.006
CBM South 1LTFEXP_CBM-S1->PJM
CBM
21.942
MECLTFEXP_MEC->PJM
CLTF
6.275
SIGELTFEXP_SIGE->PJM
CLTF
0.19
NYPJM->LTFIMP_NY
CLTF
3.623
LGEELTFEXP_LGEE->PJM
CLTF
2.32
WECLTFEXP_WEC->PJM
CLTF
1.178
AG2-052LTFEXP_AG2-052->PJM
LTF
0.063
AH1-155LTFEXP_AH1-155->PJM
LTF
0.094

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:152.97 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:6027.13
MW Contribution:13.29
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
4.377
3151101ELIZAR3
50/50
30.313
3150861SPRUNCD
50/50
1.471
3151161SURRY 1
50/50
11.323
970917AG2-570 GEN
Solar/Wind Harmer
89.846
315773AC2-141 GEN
Solar/Wind Harmer
14.644
944581AF1-123 GEN
Solar/Wind Harmer
158.305
944601AF1-125 GEN
Solar/Wind Harmer
155.834
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146456SLIGO L269
Solar/Wind Harmer
-0.034
971153AH1-033 GEN
Solar/Wind Harmer
4.188
3144536CHRHLND
Solar/Wind Harmer
-0.005
315813AE1-149 C
Solar/Wind Harmer
21.335
970659AG2-427 GEN
Solar/Wind Harmer
3.213
316083AB2-161 GEN
Solar/Wind Harmer
5.538
970661AG2-428 GEN
Solar/Wind Harmer
6.424
316320Y1-086
Solar/Wind Harmer
1.998
316435W1029_GEN3
Solar/Wind Harmer
6.125
3146516WINFALL
Solar/Wind Harmer
-0.034
315839AE2-212 C
Solar/Wind Harmer
1.016
3145336SMITFLD
Solar/Wind Harmer
-0.013
3146626S HERTFORD
Solar/Wind Harmer
-0.033
3145273HOLLAND
Solar/Wind Harmer
-0.025
316313AB2-026
Solar/Wind Harmer
0.898
316258AE1-075 C
Solar/Wind Harmer
0.808
316405AF2-144 C
Solar/Wind Harmer
0.853
3143336POWHATN
Solar/Wind Harmer
3.359
965281AG1-393 GEN
Solar/Wind Harmer
4.153
3151221GRAVEL6
Adder
21.431
3151171GRAVELC
Adder
4.123
3146376EDENTON
Solar/Wind Harmer
-0.033
961611AG1-000B GEN
Solar/Wind Harmer
6.933
316365GEN2_N
Solar/Wind Harmer
2.214
315614AA2-178 GEN
Solar/Wind Harmer
3.511
315778AD1-151 GEN
Solar/Wind Harmer
28.152
970129AG2-093 GEN
Solar/Wind Harmer
18.183
3156081AA2-088 GEN
Solar/Wind Harmer
10.453
316478AD1-087 GEN
Solar/Wind Harmer
2.786
316486AD2-202 GEN
Solar/Wind Harmer
0.816
971157AH1-035 GEN
Solar/Wind Harmer
4.016
315737AD1-076 GEN
Solar/Wind Harmer
6.093
970133AG2-095 GEN
Solar/Wind Harmer
3.601
966621AG1-532 GEN
Solar/Wind Harmer
0.649
3144216WINCHST
Adder
1.073
3145893MURPHYS
Solar/Wind Harmer
0.222
3145893MURPHYS
Solar/Wind Harmer
-0.032
3146206CASHIE
Solar/Wind Harmer
-0.032
957521AF2-046 GEN
Solar/Wind Harmer
25.055
961681AG1-008 GEN
Solar/Wind Harmer
25.055
3150921YORKTN3
Adder
7.106
3146173TUNIS
Solar/Wind Harmer
-0.032
313506AB2-031 GEN
Solar/Wind Harmer
2.537
3156021HOLLOMANSOL
Solar/Wind Harmer
4.249
316463AE2-346 GEN
Solar/Wind Harmer
0.51
316140AB2-099
Solar/Wind Harmer
0.212
962331AG1-082 GEN
Solar/Wind Harmer
3.94
3142666NORTHAMPTON
Solar/Wind Harmer
-0.031
3146263WOODLND
Solar/Wind Harmer
-0.031
3147043LAWRENC
Solar/Wind Harmer
-0.018
3143096IRON208
Adder
1.154
3143096IRON208
Adder
1.131
316317KELFORD C
Solar/Wind Harmer
1.459
3145823KELFORD
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.123
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145963POPLR C
Solar/Wind Harmer
-0.031
316382AG1-145 C
Solar/Wind Harmer
0.924
316210AC1-098 GEN
Solar/Wind Harmer
4.726
3142946ENON
Solar/Wind Harmer
-0.01
3145933PARMELE
Solar/Wind Harmer
-0.03
966801AG1-551 GEN
Solar/Wind Harmer
3.729
315724AD1-057 GEN
Solar/Wind Harmer
1.698
3145746EVERETS
Solar/Wind Harmer
-0.029
3145746EVERETS
Solar/Wind Harmer
-0.029
316327AA2-057 GEN
Solar/Wind Harmer
2.954
970909AG2-566 GEN
Solar/Wind Harmer
2.75
316131AB2-060 GEN
Solar/Wind Harmer
3.123
970293AG2-193 GEN
Solar/Wind Harmer
3.602
3146233WITAKRS
Solar/Wind Harmer
0.603
3146233WITAKRS
Solar/Wind Harmer
-0.019
3138543CONSLDL
Solar/Wind Harmer
-0.019
964241AG1-285 GEN
Solar/Wind Harmer
22.468
3146073TAR RVR
Solar/Wind Harmer
-0.029
970119AG2-088 GEN
50/50
49.347
315243AE2-183_GT3
50/50
5.563
3151051BRUNSWICKS1
50/50
9.085
3151021BRUNSWICKG1
50/50
4.377
971451AH1-221 GEN
50/50
13.295
3150981CHESPKA
50/50
4.072
3150851SPRUNCC
50/50
1.471
3152331SURRY 2
50/50
12.317
3143226MDLTHAN
Solar/Wind Harmer
-0.041
940641AE2-051 GEN
Solar/Wind Harmer
36.965
939411AE1-173 GEN
Solar/Wind Harmer
191.106
3143526WINTERP
Solar/Wind Harmer
-0.196
970919AG2-571 GEN
Solar/Wind Harmer
11.373
970087AG2-069 GEN
Solar/Wind Harmer
33.546
316294AC1-161 GEN
Solar/Wind Harmer
11.322
944591AF1-124 GEN
Solar/Wind Harmer
158.875
316375AC2-012 GEN
Solar/Wind Harmer
11.949
316388AE2-253 GEN
Solar/Wind Harmer
2.323
3146456SLIGO L269
Solar/Wind Harmer
-0.034
316246AF1-032 C
Solar/Wind Harmer
0.693
970659AG2-427 GEN
Solar/Wind Harmer
18.128
316381AD1-082 GEN
Solar/Wind Harmer
3.129
970661AG2-428 GEN
Solar/Wind Harmer
36.248
316093AE2-104_GEN
Solar/Wind Harmer
9.91
316072AD1-144
Solar/Wind Harmer
0.685
3146516WINFALL
Solar/Wind Harmer
-0.109
3146516WINFALL
Solar/Wind Harmer
-0.034
3145336SMITFLD
Solar/Wind Harmer
-0.134
957481AF2-042 GEN
Solar/Wind Harmer
105.016
315800Z1-036_GEN1
Solar/Wind Harmer
8.244
3143336POWHATN
Solar/Wind Harmer
3.951
3151171GRAVELC
Adder
3.136
3130156CHOWAN
Solar/Wind Harmer
-0.033
315671AE2-027_GEN
Solar/Wind Harmer
24.714
961611AG1-000B GEN
Solar/Wind Harmer
16.249
316023GEN1_S
Solar/Wind Harmer
2.214
971647AH1-324 GEN
Solar/Wind Harmer
16.385
3145663CRESWEL
Solar/Wind Harmer
-0.091
971163AH1-040 GEN
Solar/Wind Harmer
30.505
315693AD1-088 GEN
Solar/Wind Harmer
16.249
971069AG2-661 GEN
Solar/Wind Harmer
5.142
316458AB2-190 GEN2
Solar/Wind Harmer
3.27
962491AG1-098 GEN
Solar/Wind Harmer
21.612
970129AG2-093 GEN
Solar/Wind Harmer
7.365
960081AF2-299 GEN
Solar/Wind Harmer
3.599
3138126ROCKLANDING
Solar/Wind Harmer
0.098
3145893MURPHYS
Solar/Wind Harmer
-0.127
3145893MURPHYS
Solar/Wind Harmer
0.946
3146206CASHIE
Solar/Wind Harmer
-0.032
971547AH1-271 GEN
Solar/Wind Harmer
7.961
3142543TWELFTH
Solar/Wind Harmer
-0.003
3146173TUNIS
Solar/Wind Harmer
-0.032
3145683EARLEYS
Solar/Wind Harmer
-0.031
316011AB1-132 GEN
Solar/Wind Harmer
6.566
316303AF2-085
50/50
6.58
315244AE2-183_ST
50/50
9.618
963041AG1-153 GEN
50/50
8.863
315779AE2-040
50/50
4.423
3151081ELIZAR1
50/50
29.93
3151091ELIZAR2
50/50
29.41
941591AE2-156 GEN
50/50
27.339
3152611GOSPORTB
50/50
4.153
3152621GOSPORTC
50/50
3.524
3152601GOSPORTA
50/50
3.251
971285AH1-108 GEN
50/50
2.407
972263AH1-716 GEN
50/50
170.499
941031AE2-094 GEN
Solar/Wind Harmer
73.029
944011AF1-069 GEN
Solar/Wind Harmer
22.883
970673AG2-436 GEN
Solar/Wind Harmer
80.276
970673AG2-436 GEN
Solar/Wind Harmer
40.646
316233AE1-074 FULL
Solar/Wind Harmer
1.019
971281AH1-106 GEN
Solar/Wind Harmer
6.156
971283AH1-107 GEN
Solar/Wind Harmer
6.156
971967AH1-528 GEN
Solar/Wind Harmer
70.663
970085AG2-068 GEN
Solar/Wind Harmer
22.364
970533AG2-339 GEN
50/50
30.814
970531AG2-338 GEN
50/50
12.326
315242AE2-183_GT2
50/50
5.563
315241AE2-183_GT1
50/50
5.529
972185AH1-677 GEN
50/50
20.054
3151041BRUNSWICKG3
50/50
4.377
972187AH1-678 GEN
50/50
10.045
3150991CHESPKB
50/50
3.416
3150991CHESPKB
50/50
3.334
971223AH1-071 GEN
Solar/Wind Harmer
5.198
3143526WINTERP
Solar/Wind Harmer
-0.196
970933AG2-581 GEN
Solar/Wind Harmer
34.189
3144356SAPONY
Solar/Wind Harmer
1.242
316185AD1-033 GEN
Solar/Wind Harmer
3.648
3142956BIRDNECK
Solar/Wind Harmer
1.854
316316AC1-027 C
Solar/Wind Harmer
1.061
316036AC1-147 C
Solar/Wind Harmer
0.932
3145506HICKORY
Solar/Wind Harmer
-0.137
3145506HICKORY
Solar/Wind Harmer
-0.083
3145506HICKORY
Solar/Wind Harmer
-0.02
316339AD2-160 GEN
Solar/Wind Harmer
2.323
316018AA1-139 ULT2
Solar/Wind Harmer
2.948
316017AA1-139 ULT1
Solar/Wind Harmer
2.785
3137176SLIGO L2192
Solar/Wind Harmer
-0.136
3146456SLIGO L269
Solar/Wind Harmer
4.058
3130086AYDLETT
Solar/Wind Harmer
-0.137
970657AG2-426 GEN
Solar/Wind Harmer
10.662
970657AG2-426 GEN
Solar/Wind Harmer
2.23
3146386ELIZ CT
Solar/Wind Harmer
-0.034
316431W1029_GEN1
Solar/Wind Harmer
6.125
316433W1029_GEN2
Solar/Wind Harmer
6.125
3146516WINFALL
Solar/Wind Harmer
-0.034
3146516WINFALL
Solar/Wind Harmer
-0.034
3146516WINFALL
Solar/Wind Harmer
-0.034
316236AE1-162_GEN
Solar/Wind Harmer
1.015
970099AG2-077 GEN
Solar/Wind Harmer
42.007
3146626S HERTFORD
Solar/Wind Harmer
-0.033
3146626S HERTFORD
Solar/Wind Harmer
-0.033
315742AE1-103 GEN
Solar/Wind Harmer
3.474
3146376EDENTON
Solar/Wind Harmer
0.981
3146376EDENTON
Solar/Wind Harmer
0.981
316240AF1-291 C
Solar/Wind Harmer
0.989
316033AB2-134 GEN
Solar/Wind Harmer
10.519
315697AD1-025 GEN
Solar/Wind Harmer
6.597
944641AF1-129 GEN
Adder
138.008
316065AD1-022 GEN
Solar/Wind Harmer
15.96
3145893MURPHYS
Solar/Wind Harmer
0.889
3145893MURPHYS
Solar/Wind Harmer
-0.057
3146173TUNIS
Solar/Wind Harmer
-0.032
3146173TUNIS
Solar/Wind Harmer
-0.032
316181AB2-040 GEN
Solar/Wind Harmer
4.403
3142666NORTHAMPTON
Solar/Wind Harmer
-0.031
3142666NORTHAMPTON
Solar/Wind Harmer
-0.031
3142666NORTHAMPTON
Solar/Wind Harmer
-0.031
3142666NORTHAMPTON
Solar/Wind Harmer
-0.019
316426AA2-053 GEN
Solar/Wind Harmer
3.146
3145593CAROLNA
Solar/Wind Harmer
-0.031
3145593CAROLNA
Solar/Wind Harmer
-0.031
966811AG1-552 GEN
Solar/Wind Harmer
3.497
3145593CAROLNA
Solar/Wind Harmer
0.258
3145796HORNRTN
Solar/Wind Harmer
-0.092
3145783HORNRTN
Solar/Wind Harmer
3.668
3145783HORNRTN
Solar/Wind Harmer
2.934
3145783HORNRTN
Solar/Wind Harmer
0.917
3145783HORNRTN
Solar/Wind Harmer
0.367
316274AC1-208 GEN
Solar/Wind Harmer
3.236
3142946ENON
Solar/Wind Harmer
-0.003
3145933PARMELE
Solar/Wind Harmer
-0.059
3145933PARMELE
Solar/Wind Harmer
-0.03
971741AH1-377 GEN
Solar/Wind Harmer
34.617
939181AE1-148 GEN
Solar/Wind Harmer
16.559
3142366NRTHEST
Adder
0.852
3150691DARBY 3
Adder
18.657
3150701DARBY 4
Adder
18.614
3150681DARBY 2
Adder
18.592
3150671DARBY 1
Adder
18.57
313527AB2-043 GEN
Solar/Wind Harmer
4.711
970301AG2-198 GEN
Solar/Wind Harmer
14.484
3145493TOT1
Solar/Wind Harmer
0.444
3145453TOT5
Solar/Wind Harmer
0.267
3145603CNETO
Solar/Wind Harmer
0.178
3144293JTRSVLE
Adder
0.786
3144293JTRSVLE
Adder
0.662
3142296MT RD221
Adder
0.76
3150341NORNECKC1
Adder
2.003
3150341NORNECKC1
Adder
1.987
316447AC1-158 HLD
Solar/Wind Helper
4.827
315651AD1-115 GEN
Solar/Wind Helper
0.935
226929AD2-058 GEN
Solar/Wind Helper
0.091
316075AC2-137 C
Solar/Wind Harmer
0.313
970581AG2-369 GEN
Solar/Wind Harmer
19.233
316315AB2-025 C
Solar/Wind Harmer
0.96
315814AE2-033 C
Solar/Wind Harmer
33.023
3143316POE
Solar/Wind Harmer
-0.138
957871AF2-081 GEN
Solar/Wind Harmer
17.208
319010AE1-072 C
Solar/Wind Harmer
6.946
3146406KITTY HAWK
Solar/Wind Harmer
0.029
316305AF2-043 C
Solar/Wind Harmer
1.032
315833AF1-017_GEN
Solar/Wind Harmer
6.476
316349AD2-085 GEN
Solar/Wind Harmer
3.033
316311AC2-079 GEN
Solar/Wind Harmer
17.198
313526AB2-022
Solar/Wind Harmer
0.919
315835AF2-110_GEN
Solar/Wind Harmer
4.261
3146486SUNBURY
Solar/Wind Harmer
-0.034
3146486SUNBURY
Solar/Wind Harmer
-0.034
316321Z2-027
Solar/Wind Harmer
0.916
3146396TANGLEW
Solar/Wind Harmer
0.625
3145176PASQUOTANK
Solar/Wind Harmer
-0.021
971445AH1-216 GEN
Solar/Wind Harmer
20.803
315611Z1-036_GEN2
Solar/Wind Harmer
8.244
972265AH1-717 GEN
Adder
22.888
3151201GRAVEL4
Adder
21.456
3151191GRAVEL3
Adder
21.184
3151211GRAVEL5
Adder
21.184
3130156CHOWAN
Solar/Wind Harmer
-0.033
3130156CHOWAN
Solar/Wind Harmer
-0.033
316369SG1_INVT
Solar/Wind Harmer
5.828
315816AE2-034 GEN
Solar/Wind Harmer
2.633
316132AB2-190 GEN1
Solar/Wind Harmer
3.27
3130546PLYMOUTH
Solar/Wind Harmer
-0.032
965291AG1-394 GEN
Solar/Wind Harmer
2.85
315732AD1-074 GEN1
Solar/Wind Harmer
6.483
315733AD1-074 GEN2
Solar/Wind Harmer
6.483
315735AD1-075 GEN1
Solar/Wind Harmer
3.242
946281AF1-292 GEN
Solar/Wind Harmer
0.717
316318V4-068
Solar/Wind Harmer
0.794
3145893MURPHYS
Solar/Wind Harmer
-0.086
3145893MURPHYS
Solar/Wind Harmer
-0.032
3146206CASHIE
Solar/Wind Harmer
-0.032
970601AG2-382 GEN
Solar/Wind Harmer
13.932
316087AB2-174 GEN
Solar/Wind Harmer
4.521
3146043SEABORD
Solar/Wind Harmer
-0.031
3145513AHOSKIE
Solar/Wind Harmer
0.275
961941AG1-037 GEN
Solar/Wind Harmer
0.237
3145513AHOSKIE
Solar/Wind Harmer
-0.031
315607AA1-063A GEN
Solar/Wind Harmer
3.181
3145683EARLEYS
Solar/Wind Harmer
-0.062
3145683EARLEYS
Solar/Wind Harmer
-0.031
3145683EARLEYS
Solar/Wind Harmer
-0.031
315652AC1-086 GEN
Solar/Wind Harmer
35.304
3137643SOCKMAN
Solar/Wind Harmer
-0.124
3145796HORNRTN
Solar/Wind Harmer
-0.098
3145796HORNRTN
Solar/Wind Harmer
-0.012
3146033SCOT NK
Solar/Wind Harmer
-0.121
970831AG2-522 GEN
Solar/Wind Harmer
15.086
957831AF2-077 GEN
Solar/Wind Harmer
0.889
3138283WHITEMARSH
Solar/Wind Harmer
0.046
316005AA1-067
Solar/Wind Harmer
0.594
3145746EVERETS
Solar/Wind Harmer
-0.116
3145746EVERETS
Solar/Wind Harmer
-0.029
3145746EVERETS
Solar/Wind Harmer
-0.029
3145746EVERETS
Solar/Wind Harmer
-0.029
970181AG2-120 GEN
Solar/Wind Harmer
3.854
957861AF2-080 GEN
Solar/Wind Harmer
12.697
316239AB2-077_GEN
Solar/Wind Harmer
0.873
316238AB2-078_GEN
Solar/Wind Harmer
0.873
316420AA1-050 GEN
Solar/Wind Harmer
3.296
316319Z2-044 C
Solar/Wind Harmer
1.592
971167AH1-042 GEN
Solar/Wind Harmer
27.693
3145573BETHELC
Solar/Wind Harmer
-0.029
3145573BETHELC
Solar/Wind Harmer
-0.029
315976AC1-164 GENA
Solar/Wind Harmer
30.185
316169AC1-164_GENC
Solar/Wind Harmer
26.077
315975AC1-164 GENB
Solar/Wind Harmer
0.893
3142433PROV 92
Adder
0.494
3142433PROV 92
Adder
0.494
972205AH1-687 GEN
Adder
7.923
972189AH1-679 GEN
Adder
2.542
972193AH1-681 GEN
Adder
2.896
316164AC1-076 GEN
Solar/Wind Helper
1.492
316411AF1-147_GEN1
Solar/Wind Helper
0.805
316415AF1-147_GEN2
Solar/Wind Helper
0.805
3138216PACIFIC
Solar/Wind Helper
0.039
3146083TARBORO
Solar/Wind Harmer
-0.029
3142433PROV 92
Adder
0.494
3142433PROV 92
Adder
0.494
3144293JTRSVLE
Adder
0.786
3141843SHACKLE
Adder
1.247
3150351NORNECKC2
Adder
1.939
972255AH1-712 GEN
Adder
64.825
316044AC1-158 PL1
Solar/Wind Helper
2.193
316450AC1-158 RIC
Solar/Wind Helper
0.585
3147666LOUISA
Solar/Wind Helper
0.714
316170AC1-121 GEN2
Solar/Wind Helper
0.428
3141196NOKESVL
Solar/Wind Helper
1.035
3132273ORANGE
Solar/Wind Helper
0.047
227287AC2-120 GEN
Solar/Wind Helper
0.311
226910AB2-157 C
Solar/Wind Helper
0.013
962571AG1-106 GEN
Solar/Wind Harmer
4.511
971795AH1-408 GEN
Solar/Wind Harmer
23.527
3146263WOODLND
Solar/Wind Harmer
-0.031
316190AA2-174 GEN
Solar/Wind Harmer
0.382
316336AC2-165 C
Solar/Wind Harmer
5.409
3147043LAWRENC
Adder
2.503
971317AH1-138 GEN
Solar/Wind Harmer
3.871
3143096IRON208
Adder
1.154
3145823KELFORD
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.102
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145783HORNRTN
Solar/Wind Harmer
-0.031
3145963POPLR C
Solar/Wind Harmer
-0.031
316159AE1-175 C
Solar/Wind Harmer
0.823
316174AB2-169 GEN
Solar/Wind Harmer
4.727
944631AF1-128 GEN
Adder
129.496
315687AD1-152 GEN
Solar/Wind Harmer
3.646
316212AC1-099_GEN
Solar/Wind Harmer
2.626
316129AC1-054 GEN
Solar/Wind Harmer
2.637
971065AG2-659 GEN
Solar/Wind Harmer
14.993
3146293MARTNCO
Solar/Wind Harmer
0.185
315722AD1-056 GEN
Solar/Wind Harmer
3.088
3145746EVERETS
Solar/Wind Harmer
-0.029
3145746EVERETS
Solar/Wind Harmer
-0.029
316494AC1-189 GEN
Solar/Wind Harmer
3.123
316237AB2-079_GEN
Solar/Wind Harmer
0.873
3146233WITAKRS
Solar/Wind Harmer
-0.114
961671AG1-007 GEN
Solar/Wind Harmer
0.363
3146083TARBORO
Solar/Wind Harmer
-0.029
3145493TOT1
Solar/Wind Harmer
0.852
3142433PROV 92
Solar/Wind Harmer
-0.114
3142433PROV 92
Adder
0.494
3142433PROV 92
Adder
0.494
3144293JTRSVLE
Adder
0.786
3141843SHACKLE
Adder
1.247
3150351NORNECKC2
Adder
1.907
972277AH1-723 GEN
Adder
75.541
316045AC1-158 PL2
Solar/Wind Helper
7.02
3147666LOUISA
Solar/Wind Helper
1.242
316192AB2-158 GEN
Solar/Wind Helper
2.041
316254AC1-120 GEN1
Solar/Wind Helper
1.285
316006AB2-029 C
Solar/Wind Helper
0.129
LAGNLTFEXP_LAGN->PJM
CLTF
12.464
CBM South 2LTFEXP_CBM-S2->PJM
CBM
36.906
TVALTFEXP_TVA->PJM
CLTF
6.273
CPLELTFEXP_CPLE->PJM
CLTF
16.795
CBM West 2LTFEXP_CBM-W2->PJM
CBM
66.696
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.329
CBM South 1LTFEXP_CBM-S1->PJM
CBM
21.608
MECLTFEXP_MEC->PJM
CLTF
6.26
SIGELTFEXP_SIGE->PJM
CLTF
0.19
NYPJM->LTFIMP_NY
CLTF
3.562
LGEELTFEXP_LGEE->PJM
CLTF
2.331
WECLTFEXP_WEC->PJM
CLTF
1.184
AG2-052LTFEXP_AG2-052->PJM
LTF
0.064
AH1-155LTFEXP_AH1-155->PJM
LTF
0.096

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:136.69 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:4402.07
MW Contribution:12.67
Bus #Bus NameTypeMW Contribution
970119AG2-088 GEN
50/50
43.39
315243AE2-183_GT3
50/50
5.306
3151051BRUNSWICKS1
50/50
8.655
3151021BRUNSWICKG1
50/50
4.17
971451AH1-221 GEN
50/50
12.666
3150981CHESPKA
50/50
3.862
3152331SURRY 2
50/50
11.978
940641AE2-051 GEN
Solar/Wind Harmer
26.972
3151031BRUNSWICKG2
50/50
4.17
3151101ELIZAR3
50/50
28.777
3151161SURRY 1
50/50
10.302
970917AG2-570 GEN
Solar/Wind Harmer
27.004
315773AC2-141 GEN
Solar/Wind Harmer
10.994
944581AF1-123 GEN
Solar/Wind Harmer
66.571
944601AF1-125 GEN
Solar/Wind Harmer
65.546
3144873MCLAUGH
Solar/Wind Harmer
0.007
3146456SLIGO L269
Solar/Wind Harmer
0.29
971153AH1-033 GEN
Solar/Wind Harmer
3.357
316320Y1-086
Solar/Wind Harmer
0.002
3144536CHRHLND
Solar/Wind Harmer
0.043
316435W1029_GEN3
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.284
3146626S HERTFORD
Solar/Wind Harmer
0.282
3145273HOLLAND
Solar/Wind Harmer
0.209
3146376EDENTON
Solar/Wind Harmer
0.277
3145336SMITFLD
Solar/Wind Harmer
0.111
970661AG2-428 GEN
Solar/Wind Harmer
5.809
316083AB2-161 GEN
Solar/Wind Harmer
0.004
315614AA2-178 GEN
Solar/Wind Harmer
1.557
970659AG2-427 GEN
Solar/Wind Harmer
2.872
316365GEN2_N
Solar/Wind Harmer
0.603
3151221GRAVEL6
Adder
19.5
3151171GRAVELC
Adder
3.752
971157AH1-035 GEN
Solar/Wind Harmer
3.217
315813AE1-149 C
Solar/Wind Harmer
14.26
315737AD1-076 GEN
Solar/Wind Harmer
3.44
316478AD1-087 GEN
Solar/Wind Harmer
0.932
316486AD2-202 GEN
Solar/Wind Harmer
0.274
3156081AA2-088 GEN
Solar/Wind Harmer
0.006
3146206CASHIE
Solar/Wind Harmer
0.265
3144216WINCHST
Adder
0.999
3145893MURPHYS
Solar/Wind Harmer
0.442
3145893MURPHYS
Solar/Wind Harmer
0.264
3150921YORKTN3
Adder
6.638
957521AF2-046 GEN
Solar/Wind Harmer
19.613
961681AG1-008 GEN
Solar/Wind Harmer
19.613
961611AG1-000B GEN
Solar/Wind Harmer
7.014
3146173TUNIS
Solar/Wind Harmer
0.262
3156021HOLLOMANSOL
Solar/Wind Harmer
1.189
316463AE2-346 GEN
Solar/Wind Harmer
0.224
316140AB2-099
Solar/Wind Harmer
0.093
962331AG1-082 GEN
Solar/Wind Harmer
2.786
3146263WOODLND
Solar/Wind Harmer
0.259
313506AB2-031 GEN
Solar/Wind Harmer
0.8
3142666NORTHAMPTON
Solar/Wind Harmer
0.258
3145963POPLR C
Solar/Wind Harmer
0.256
316317KELFORD C
Solar/Wind Harmer
0.025
3145823KELFORD
Solar/Wind Harmer
0.256
316313AB2-026
Solar/Wind Harmer
0.16
316258AE1-075 C
Solar/Wind Harmer
0.192
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.845
3145796HORNRTN
Solar/Wind Harmer
1.016
3145796HORNRTN
Solar/Wind Harmer
0.254
3147043LAWRENC
Solar/Wind Harmer
0.152
315839AE2-212 C
Solar/Wind Harmer
0.002
315778AD1-151 GEN
Solar/Wind Harmer
20.127
316382AG1-145 C
Solar/Wind Harmer
0.002
965281AG1-393 GEN
Solar/Wind Harmer
2.647
316210AC1-098 GEN
Solar/Wind Harmer
2.301
3145933PARMELE
Solar/Wind Harmer
0.247
966801AG1-551 GEN
Solar/Wind Harmer
2.873
970129AG2-093 GEN
Solar/Wind Harmer
14.877
3145746EVERETS
Solar/Wind Harmer
0.242
3145746EVERETS
Solar/Wind Harmer
0.242
315724AD1-057 GEN
Solar/Wind Harmer
0.909
316327AA2-057 GEN
Solar/Wind Harmer
0.363
3150861SPRUNCD
Adder
1.101
970133AG2-095 GEN
Solar/Wind Harmer
2.289
3146233WITAKRS
Solar/Wind Harmer
1.186
3146233WITAKRS
Solar/Wind Harmer
0.161
3146073TAR RVR
Solar/Wind Harmer
0.236
3146083TARBORO
Solar/Wind Harmer
0.236
3138543CONSLDL
Solar/Wind Harmer
0.156
316131AB2-060 GEN
Solar/Wind Harmer
0.739
964241AG1-285 GEN
Solar/Wind Harmer
15.529
970909AG2-566 GEN
Solar/Wind Harmer
2.481
961601AG1-000A GEN
Solar/Wind Harmer
16.539
3145543BTLEBRO
Solar/Wind Harmer
0.232
3145543BTLEBRO
Solar/Wind Harmer
0.232
971623AH1-311 GEN
Solar/Wind Harmer
0.465
315785AD2-033 C
Solar/Wind Harmer
1.864
970257AG2-171 GEN
Solar/Wind Harmer
7.295
959311AF2-222 GEN
Solar/Wind Harmer
20.178
3142946ENON
Solar/Wind Harmer
0.074
963181AG1-167 GEN
Solar/Wind Harmer
0.885
3144293JTRSVLE
Adder
0.705
3147133PAMPLIN
Solar/Wind Harmer
0.687
971193AH1-056 GEN
Solar/Wind Harmer
13.34
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
9.346
316156AD2-030 GEN
Solar/Wind Harmer
0.16
3141873WAN 176
Solar/Wind Harmer
3.848
316280AD1-041 GEN
Solar/Wind Harmer
0.004
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3141843SHACKLE
Adder
1.102
3143096IRON208
Adder
0.902
3143096IRON208
Adder
0.884
3141766HARMONY
Solar/Wind Harmer
2.867
3142433PROV 92
Adder
0.418
3142433PROV 92
Adder
0.418
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.123
316283AC2-100 C
Solar/Wind Harmer
0.389
971683AH1-343 GEN
Solar/Wind Harmer
7.294
962971AG1-146 GEN
Solar/Wind Harmer
3.148
970293AG2-193 GEN
Solar/Wind Harmer
2.064
970009AG2-005 GEN
Solar/Wind Harmer
1.436
316404AE1-155 C
Solar/Wind Harmer
0.042
3146776BUCKING
Solar/Wind Harmer
0.065
3150351NORNECKC2
Adder
1.745
3142416OLDCHRC
Solar/Wind Harmer
1.55
3141906WESTMOR
Solar/Wind Harmer
0.053
970221AG2-151 GEN
Solar/Wind Harmer
7.048
316473AC1-191 GEN
Solar/Wind Harmer
0.412
970737AG2-469 GEN
Solar/Wind Harmer
4.87
316044AC1-158 PL1
Solar/Wind Helper
1.723
316450AC1-158 RIC
Solar/Wind Helper
0.459
3147666LOUISA
Solar/Wind Helper
0.596
939411AE1-173 GEN
Solar/Wind Harmer
139.157
3143226MDLTHAN
Solar/Wind Harmer
0.325
970919AG2-571 GEN
Solar/Wind Harmer
10.802
970087AG2-069 GEN
Solar/Wind Harmer
24.19
316294AC1-161 GEN
Solar/Wind Harmer
5.215
944591AF1-124 GEN
Solar/Wind Harmer
66.808
316375AC2-012 GEN
Solar/Wind Harmer
0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.912
3146456SLIGO L269
Solar/Wind Harmer
0.29
316246AF1-032 C
Solar/Wind Harmer
0.13
316093AE2-104_GEN
Solar/Wind Harmer
4.794
3146516WINFALL
Solar/Wind Harmer
0.92
3146516WINFALL
Solar/Wind Harmer
0.284
316072AD1-144
Solar/Wind Harmer
0.103
3143526WINTERP
Solar/Wind Harmer
1.47
957481AF2-042 GEN
Solar/Wind Harmer
74.795
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.277
3145336SMITFLD
Solar/Wind Harmer
1.108
970661AG2-428 GEN
Solar/Wind Harmer
27.311
316381AD1-082 GEN
Solar/Wind Harmer
0.284
3145663CRESWEL
Solar/Wind Harmer
0.761
971163AH1-040 GEN
Solar/Wind Harmer
21.769
970659AG2-427 GEN
Solar/Wind Harmer
13.13
315693AD1-088 GEN
Solar/Wind Harmer
12.923
316023GEN1_S
Solar/Wind Harmer
0.603
3151171GRAVELC
Adder
2.853
962491AG1-098 GEN
Solar/Wind Harmer
15.256
3146206CASHIE
Solar/Wind Harmer
0.265
971547AH1-271 GEN
Solar/Wind Harmer
5.655
3138126ROCKLANDING
Solar/Wind Harmer
0.121
3145893MURPHYS
Solar/Wind Harmer
1.056
3145893MURPHYS
Solar/Wind Harmer
1.174
961611AG1-000B GEN
Solar/Wind Harmer
13.793
3146173TUNIS
Solar/Wind Harmer
0.262
960081AF2-299 GEN
Solar/Wind Harmer
2.514
3145683EARLEYS
Solar/Wind Harmer
0.26
3146263WOODLND
Solar/Wind Harmer
0.259
971647AH1-324 GEN
Solar/Wind Harmer
11.046
316011AB1-132 GEN
Solar/Wind Harmer
4.685
962571AG1-106 GEN
Solar/Wind Harmer
3.666
316190AA2-174 GEN
Solar/Wind Harmer
0
971795AH1-408 GEN
Solar/Wind Harmer
17.096
3145963POPLR C
Solar/Wind Harmer
0.256
971317AH1-138 GEN
Solar/Wind Harmer
1.913
3145823KELFORD
Solar/Wind Harmer
0.256
3143336POWHATN
Solar/Wind Harmer
4.523
316174AB2-169 GEN
Solar/Wind Harmer
0.007
3145783HORNRTN
Solar/Wind Harmer
0.254
3145796HORNRTN
Solar/Wind Harmer
0.838
3145796HORNRTN
Solar/Wind Harmer
0.254
316303AF2-085
50/50
5.785
315244AE2-183_ST
50/50
9.174
963041AG1-153 GEN
50/50
8.444
3151081ELIZAR1
50/50
28.413
3151091ELIZAR2
50/50
27.92
941591AE2-156 GEN
50/50
25.939
3152611GOSPORTB
50/50
3.939
3152621GOSPORTC
50/50
3.343
3152601GOSPORTA
50/50
3.084
315779AE2-040
50/50
4.048
972263AH1-716 GEN
50/50
164.964
941031AE2-094 GEN
Solar/Wind Harmer
61.065
944011AF1-069 GEN
Solar/Wind Harmer
19.952
970673AG2-436 GEN
Solar/Wind Harmer
69.269
970673AG2-436 GEN
Solar/Wind Harmer
46.179
971967AH1-528 GEN
Solar/Wind Harmer
50.977
970085AG2-068 GEN
Solar/Wind Harmer
16.126
970581AG2-369 GEN
Solar/Wind Harmer
13.869
957871AF2-081 GEN
Solar/Wind Harmer
14.487
319010AE1-072 C
Solar/Wind Harmer
1.462
3146406KITTY HAWK
Solar/Wind Harmer
0.036
316315AB2-025 C
Solar/Wind Harmer
0.234
315814AE2-033 C
Solar/Wind Harmer
22.859
316305AF2-043 C
Solar/Wind Harmer
0.002
313526AB2-022
Solar/Wind Harmer
0.156
316321Z2-027
Solar/Wind Harmer
0.053
3146396TANGLEW
Solar/Wind Harmer
0.789
3145176PASQUOTANK
Solar/Wind Harmer
0.177
3146486SUNBURY
Solar/Wind Harmer
0.286
3146486SUNBURY
Solar/Wind Harmer
0.286
315835AF2-110_GEN
Solar/Wind Harmer
1.956
316233AE1-074 FULL
Solar/Wind Harmer
0.226
971281AH1-106 GEN
Solar/Wind Harmer
3.922
971283AH1-107 GEN
Solar/Wind Harmer
3.922
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
316311AC2-079 GEN
Solar/Wind Harmer
8.046
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.192
3130156CHOWAN
Solar/Wind Harmer
0.277
3130156CHOWAN
Solar/Wind Harmer
0.277
971445AH1-216 GEN
Solar/Wind Harmer
19.461
3143316POE
Solar/Wind Harmer
1.085
315816AE2-034 GEN
Solar/Wind Harmer
1.168
972265AH1-717 GEN
Adder
20.825
3151201GRAVEL4
Adder
19.522
3151191GRAVEL3
Adder
19.275
3151211GRAVEL5
Adder
19.275
3130546PLYMOUTH
Solar/Wind Harmer
0.268
315732AD1-074 GEN1
Solar/Wind Harmer
1.536
315733AD1-074 GEN2
Solar/Wind Harmer
1.536
315735AD1-075 GEN1
Solar/Wind Harmer
0.769
965291AG1-394 GEN
Solar/Wind Harmer
1.182
3146206CASHIE
Solar/Wind Harmer
0.265
970601AG2-382 GEN
Solar/Wind Harmer
9.896
3145893MURPHYS
Solar/Wind Harmer
0.713
3145893MURPHYS
Solar/Wind Harmer
0.264
3145513AHOSKIE
Solar/Wind Harmer
0.546
3145513AHOSKIE
Solar/Wind Harmer
0.261
3146043SEABORD
Solar/Wind Harmer
0.26
3145683EARLEYS
Solar/Wind Harmer
0.52
3145683EARLEYS
Solar/Wind Harmer
0.26
3145683EARLEYS
Solar/Wind Harmer
0.26
316087AB2-174 GEN
Solar/Wind Harmer
0.007
315607AA1-063A GEN
Solar/Wind Harmer
0.531
315652AC1-086 GEN
Solar/Wind Harmer
28.344
3137643SOCKMAN
Solar/Wind Harmer
1.027
316369SG1_INVT
Solar/Wind Harmer
0.01
3145796HORNRTN
Solar/Wind Harmer
0.813
3145796HORNRTN
Solar/Wind Harmer
0.102
3146033SCOT NK
Solar/Wind Harmer
1.006
970831AG2-522 GEN
Solar/Wind Harmer
10.563
316132AB2-190 GEN1
Solar/Wind Harmer
1.325
316005AA1-067
Solar/Wind Harmer
0.26
3145746EVERETS
Solar/Wind Harmer
0.964
3145746EVERETS
Solar/Wind Harmer
0.242
3145746EVERETS
Solar/Wind Harmer
0.242
3145746EVERETS
Solar/Wind Harmer
0.242
970181AG2-120 GEN
Solar/Wind Harmer
3.014
3138283WHITEMARSH
Solar/Wind Harmer
0.056
971285AH1-108 GEN
Adder
1.802
957861AF2-080 GEN
Solar/Wind Harmer
10.3
316420AA1-050 GEN
Solar/Wind Harmer
0.008
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.236
3145573BETHELC
Solar/Wind Harmer
0.236
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
3.835
3144303KENBRDG
Solar/Wind Harmer
0.182
970683AG2-441 GEN
Solar/Wind Harmer
14.971
970681AG2-440 GEN
Solar/Wind Harmer
11.976
316118AC1-105 GEN
Solar/Wind Harmer
0.574
946301AF1-294 GEN
Solar/Wind Harmer
4.367
961791AG1-021 GEN
Solar/Wind Harmer
2.125
315657AE1-056 GEN
Solar/Wind Harmer
7.556
3147173SINAI
Solar/Wind Harmer
0.219
3147243WELCO
Solar/Wind Harmer
0.137
315976AC1-164 GENA
Solar/Wind Harmer
22.6
316169AC1-164_GENC
Solar/Wind Harmer
19.524
315975AC1-164 GENB
Solar/Wind Harmer
0.669
3141873WAN 176
Solar/Wind Harmer
0.043
315662AE1-191 GEN
Solar/Wind Harmer
0.007
315666AE1-190 GEN
Solar/Wind Harmer
0.002
970189AG2-124 GEN
Solar/Wind Harmer
6.392
971167AH1-042 GEN
Solar/Wind Harmer
19.104
316059AD1-063 C
Solar/Wind Harmer
0.001
3142433PROV 92
Adder
0.418
3142433PROV 92
Adder
0.418
3143873LANEXA
Solar/Wind Harmer
0.129
316314AB2-024 C
Solar/Wind Harmer
0.001
3141913WHIT STONE
Solar/Wind Harmer
0.21
3138133OCRAN
Solar/Wind Harmer
0.062
3141783LANCAST
Solar/Wind Harmer
0.123
3141783LANCAST
Solar/Wind Harmer
0.082
962981AG1-147 GEN
Solar/Wind Harmer
7.345
970327AG2-215 GEN
Solar/Wind Harmer
6.31
970865AG2-541 GEN
Solar/Wind Harmer
6.523
970285AG2-188 GEN
Solar/Wind Harmer
14.703
971845AH1-439 GEN
Solar/Wind Harmer
8.235
3141813NORNECK
Solar/Wind Harmer
0.172
316123AC1-075 GEN
Solar/Wind Harmer
0.229
970165AG2-112 GEN
Solar/Wind Harmer
1.36
970163AG2-111 GEN
Solar/Wind Harmer
1.297
316312AB1-027
Solar/Wind Harmer
0.286
972205AH1-687 GEN
Adder
6.309
316223AC1-118
Solar/Wind Harmer
0.095
971447AH1-217 GEN
Solar/Wind Harmer
3.746
270494AE1-108_GEN
Solar/Wind Harmer
1.403
316164AC1-076 GEN
Solar/Wind Helper
1.139
3147043LAWRENC
Adder
2.297
971069AG2-661 GEN
Solar/Wind Harmer
4.473
315687AD1-152 GEN
Solar/Wind Harmer
0.008
316159AE1-175 C
Solar/Wind Harmer
0.215
316212AC1-099_GEN
Solar/Wind Harmer
1.283
316458AB2-190 GEN2
Solar/Wind Harmer
1.325
3146293MARTNCO
Solar/Wind Harmer
0.229
316129AC1-054 GEN
Solar/Wind Harmer
0.928
970129AG2-093 GEN
Solar/Wind Harmer
7.001
971065AG2-659 GEN
Solar/Wind Harmer
10.492
315671AE2-027_GEN
Solar/Wind Harmer
15.643
3145746EVERETS
Solar/Wind Harmer
0.242
3145746EVERETS
Solar/Wind Harmer
0.242
315722AD1-056 GEN
Solar/Wind Harmer
1.533
3150851SPRUNCC
Adder
1.101
316494AC1-189 GEN
Solar/Wind Harmer
0.807
3146233WITAKRS
Solar/Wind Harmer
0.94
961671AG1-007 GEN
Solar/Wind Harmer
0.036
3146083TARBORO
Solar/Wind Harmer
0.236
3145493TOT1
Solar/Wind Harmer
1.049
316336AC2-165 C
Solar/Wind Harmer
0.009
316237AB2-079_GEN
Solar/Wind Harmer
0.002
3145543BTLEBRO
Solar/Wind Harmer
0.232
3145543BTLEBRO
Solar/Wind Harmer
0.186
316359AB2-059 GEN
Solar/Wind Harmer
0.835
316049AB1-081 GEN
Solar/Wind Harmer
1.331
3142053HEARTS
Solar/Wind Harmer
0.409
970401AG2-262 GEN
Solar/Wind Harmer
1.326
970685AG2-442 GEN
Solar/Wind Harmer
16.767
944631AF1-128 GEN
Adder
106.166
963171AG1-166 GEN
Solar/Wind Harmer
1.18
971563AH1-280 GEN
Solar/Wind Harmer
2.361
3144293JTRSVLE
Adder
0.705
3142543TWELFTH
Solar/Wind Harmer
0.021
971777AH1-397 GEN
Solar/Wind Harmer
0.569
3141843SHACKLE
Adder
1.102
3143096IRON208
Adder
0.902
3141766HARMONY
Solar/Wind Harmer
0.043
3142433PROV 92
Solar/Wind Harmer
0.86
3142433PROV 92
Adder
0.418
3142433PROV 92
Adder
0.418
3138133OCRAN
Solar/Wind Harmer
0.125
316003AC1-222 GEN
Solar/Wind Harmer
0.006
3146926FARMVIL
Solar/Wind Harmer
0.123
970937AG2-583 GEN
Solar/Wind Harmer
11.537
962861AG1-135 GEN
Solar/Wind Harmer
5.983
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.072
3141726DUNNSVL
Solar/Wind Harmer
0.706
3150351NORNECKC2
Adder
1.716
3142416OLDCHRC
Solar/Wind Harmer
0.416
3142416OLDCHRC
Solar/Wind Harmer
0.159
972003AH1-546 GEN
Solar/Wind Harmer
6.522
316337AD2-073 GEN
Solar/Wind Harmer
0.133
971377AH1-170 GEN
Solar/Wind Harmer
1.41
3147623JAMES R
Solar/Wind Harmer
0.306
970223AG2-152 GEN
Solar/Wind Harmer
9.004
270016AE1-250 BESS
Solar/Wind Harmer
0.004
3147123OTTER R
Solar/Wind Harmer
0.068
316045AC1-158 PL2
Solar/Wind Helper
5.515
3147666LOUISA
Solar/Wind Helper
1.037
316192AB2-158 GEN
Solar/Wind Helper
1.708
970533AG2-339 GEN
50/50
29.471
970531AG2-338 GEN
50/50
11.789
315242AE2-183_GT2
50/50
5.306
315241AE2-183_GT1
50/50
5.273
972185AH1-677 GEN
50/50
19.129
3151041BRUNSWICKG3
50/50
4.17
972187AH1-678 GEN
50/50
9.57
3150991CHESPKB
50/50
3.24
3150991CHESPKB
50/50
3.162
971223AH1-071 GEN
Solar/Wind Harmer
3.471
970933AG2-581 GEN
Solar/Wind Harmer
24.629
316185AD1-033 GEN
Solar/Wind Harmer
0.008
3145506HICKORY
Solar/Wind Harmer
1.168
3145506HICKORY
Solar/Wind Harmer
0.701
3145506HICKORY
Solar/Wind Harmer
0.175
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.28
316036AC1-147 C
Solar/Wind Harmer
0.054
316339AD2-160 GEN
Solar/Wind Harmer
0.472
316018AA1-139 ULT2
Solar/Wind Harmer
0.007
316017AA1-139 ULT1
Solar/Wind Harmer
0.162
3137176SLIGO L2192
Solar/Wind Harmer
1.156
3146456SLIGO L269
Solar/Wind Harmer
5.139
3130086AYDLETT
Solar/Wind Harmer
1.16
3144356SAPONY
Solar/Wind Harmer
2.426
3146386ELIZ CT
Solar/Wind Harmer
0.287
316431W1029_GEN1
Solar/Wind Harmer
0.002
316433W1029_GEN2
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.284
3146516WINFALL
Solar/Wind Harmer
0.284
3146516WINFALL
Solar/Wind Harmer
0.284
3143526WINTERP
Solar/Wind Harmer
1.47
3146626S HERTFORD
Solar/Wind Harmer
0.282
3146626S HERTFORD
Solar/Wind Harmer
0.282
970099AG2-077 GEN
Solar/Wind Harmer
29.918
3146376EDENTON
Solar/Wind Harmer
1.233
3146376EDENTON
Solar/Wind Harmer
1.233
316236AE1-162_GEN
Solar/Wind Harmer
0.002
315742AE1-103 GEN
Solar/Wind Harmer
0.003
970657AG2-426 GEN
Solar/Wind Harmer
9.567
970657AG2-426 GEN
Solar/Wind Harmer
2.006
316065AD1-022 GEN
Solar/Wind Harmer
12.243
3145893MURPHYS
Solar/Wind Harmer
1.767
3145893MURPHYS
Solar/Wind Harmer
0.475
3146173TUNIS
Solar/Wind Harmer
0.262
3146173TUNIS
Solar/Wind Harmer
0.262
316181AB2-040 GEN
Solar/Wind Harmer
0.376
3142666NORTHAMPTON
Solar/Wind Harmer
0.258
3142666NORTHAMPTON
Solar/Wind Harmer
0.258
3142666NORTHAMPTON
Solar/Wind Harmer
0.258
3142666NORTHAMPTON
Solar/Wind Harmer
0.155
316426AA2-053 GEN
Solar/Wind Harmer
0.866
3145593CAROLNA
Solar/Wind Harmer
0.255
3145593CAROLNA
Solar/Wind Harmer
0.255
966811AG1-552 GEN
Solar/Wind Harmer
2.773
3145593CAROLNA
Solar/Wind Harmer
0.318
316033AB2-134 GEN
Solar/Wind Harmer
0.015
315697AD1-025 GEN
Solar/Wind Harmer
0.287
3145783HORNRTN
Solar/Wind Harmer
4.52
3145783HORNRTN
Solar/Wind Harmer
3.616
3145783HORNRTN
Solar/Wind Harmer
1.13
3145783HORNRTN
Solar/Wind Harmer
0.452
3145796HORNRTN
Solar/Wind Harmer
0.762
3145933PARMELE
Solar/Wind Harmer
0.493
3145933PARMELE
Solar/Wind Harmer
0.247
316274AC1-208 GEN
Solar/Wind Harmer
1.28
971741AH1-377 GEN
Solar/Wind Harmer
23.908
939181AE1-148 GEN
Solar/Wind Harmer
11.558
316240AF1-291 C
Solar/Wind Harmer
0.002
3145493TOT1
Solar/Wind Harmer
0.547
3145453TOT5
Solar/Wind Harmer
0.328
3145603CNETO
Solar/Wind Harmer
0.219
313527AB2-043 GEN
Solar/Wind Harmer
0.003
944641AF1-129 GEN
Adder
111.535
970301AG2-198 GEN
Solar/Wind Harmer
9.924
961601AG1-000A GEN
Solar/Wind Harmer
4.135
316263AC1-034 GEN
Solar/Wind Harmer
8.835
970323AG2-213 GEN
Solar/Wind Harmer
9.727
971775AH1-396 GEN
Solar/Wind Harmer
0.365
316034AC1-036 C
Solar/Wind Harmer
0.017
962561AG1-105 GEN
Solar/Wind Harmer
10.919
964791AG1-342 GEN
Solar/Wind Harmer
4.339
3146843MT LREL
Solar/Wind Harmer
0.226
3146843MT LREL
Solar/Wind Harmer
0.226
3142946ENON
Solar/Wind Harmer
0.022
958211AF2-115 GEN
Solar/Wind Harmer
2.656
963191AG1-168 GEN
Solar/Wind Harmer
0.885
3144293JTRSVLE
Adder
0.705
3144293JTRSVLE
Adder
0.593
3147133PAMPLIN
Solar/Wind Harmer
0.219
3147133PAMPLIN
Solar/Wind Harmer
0.175
316075AC2-137 C
Solar/Wind Harmer
0.055
316222AC1-221 GEN
Solar/Wind Harmer
0.83
3150691DARBY 3
Adder
13.407
3150701DARBY 4
Adder
13.376
3150681DARBY 2
Adder
13.36
3150671DARBY 1
Adder
13.345
958261AF2-120 GEN
Solar/Wind Harmer
6.119
3142366NRTHEST
Adder
0.595
3146776BUCKING
Solar/Wind Harmer
0.717
3146776BUCKING
Solar/Wind Harmer
0.058
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
1.803
3150341NORNECKC1
Adder
1.788
942751AE2-291 GEN
Solar/Wind Harmer
8.42
971489AH1-241 GEN
Solar/Wind Harmer
7.048
3142296MT RD221
Adder
0.414
270013AE1-250 PV
Solar/Wind Harmer
0.004
966871AG1-558 GEN
Solar/Wind Harmer
0.141
316447AC1-158 HLD
Solar/Wind Helper
3.792
LAGNLTFEXP_LAGN->PJM
CLTF
10.194
CBM South 2LTFEXP_CBM-S2->PJM
CBM
32.592
TVALTFEXP_TVA->PJM
CLTF
5.103
CPLELTFEXP_CPLE->PJM
CLTF
15.205
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.962
CBM West 1LTFEXP_CBM-W1->PJM
CBM
29.866
CBM South 1LTFEXP_CBM-S1->PJM
CBM
17.385
MECLTFEXP_MEC->PJM
CLTF
4.747
SIGELTFEXP_SIGE->PJM
CLTF
0.142
NYPJM->LTFIMP_NY
CLTF
2.749
LGEELTFEXP_LGEE->PJM
CLTF
1.702
WECLTFEXP_WEC->PJM
CLTF
0.865

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 574T575_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 574T575_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.12 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:5205.6
MW Contribution:12.06
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
5.96
315244AE2-183_ST
50/50
8.724
963041AG1-153 GEN
50/50
8.039
315779AE2-040
50/50
4.026
3151081ELIZAR1
50/50
27.372
3151091ELIZAR2
50/50
26.896
941591AE2-156 GEN
50/50
25.004
3152611GOSPORTB
50/50
3.798
3152621GOSPORTC
50/50
3.223
3152601GOSPORTA
50/50
2.973
971285AH1-108 GEN
50/50
2.203
972263AH1-716 GEN
50/50
156.512
941031AE2-094 GEN
Solar/Wind Harmer
66.256
944011AF1-069 GEN
Solar/Wind Harmer
20.76
970673AG2-436 GEN
Solar/Wind Harmer
72.821
970673AG2-436 GEN
Solar/Wind Harmer
36.871
316233AE1-074 FULL
Solar/Wind Harmer
0.927
971281AH1-106 GEN
Solar/Wind Harmer
5.6
971283AH1-107 GEN
Solar/Wind Harmer
5.6
971967AH1-528 GEN
Solar/Wind Harmer
64.075
970085AG2-068 GEN
Solar/Wind Harmer
20.283
970581AG2-369 GEN
Solar/Wind Harmer
17.443
316315AB2-025 C
Solar/Wind Harmer
0.874
315814AE2-033 C
Solar/Wind Harmer
30.059
3143316POE
Solar/Wind Harmer
-0.126
957871AF2-081 GEN
Solar/Wind Harmer
15.731
319010AE1-072 C
Solar/Wind Harmer
6.35
3146406KITTY HAWK
Solar/Wind Harmer
0.026
316305AF2-043 C
Solar/Wind Harmer
0.944
315833AF1-017_GEN
Solar/Wind Harmer
5.92
316349AD2-085 GEN
Solar/Wind Harmer
2.772
316311AC2-079 GEN
Solar/Wind Harmer
15.721
313526AB2-022
Solar/Wind Harmer
0.84
315835AF2-110_GEN
Solar/Wind Harmer
3.894
3146486SUNBURY
Solar/Wind Harmer
-0.031
3146486SUNBURY
Solar/Wind Harmer
-0.031
316321Z2-027
Solar/Wind Harmer
0.837
3146396TANGLEW
Solar/Wind Harmer
0.571
3145176PASQUOTANK
Solar/Wind Harmer
-0.019
971445AH1-216 GEN
Solar/Wind Harmer
19.056
315611Z1-036_GEN2
Solar/Wind Harmer
7.529
972265AH1-717 GEN
Adder
20.984
3151201GRAVEL4
Adder
19.671
3151191GRAVEL3
Adder
19.422
3151211GRAVEL5
Adder
19.422
3130156CHOWAN
Solar/Wind Harmer
-0.03
3130156CHOWAN
Solar/Wind Harmer
-0.03
316369SG1_INVT
Solar/Wind Harmer
5.347
315816AE2-034 GEN
Solar/Wind Harmer
2.403
316132AB2-190 GEN1
Solar/Wind Harmer
3.001
3130546PLYMOUTH
Solar/Wind Harmer
-0.029
965291AG1-394 GEN
Solar/Wind Harmer
2.597
315732AD1-074 GEN1
Solar/Wind Harmer
5.913
315733AD1-074 GEN2
Solar/Wind Harmer
5.913
315735AD1-075 GEN1
Solar/Wind Harmer
2.957
946281AF1-292 GEN
Solar/Wind Harmer
0.651
316318V4-068
Solar/Wind Harmer
0.724
3145893MURPHYS
Solar/Wind Harmer
-0.078
3145893MURPHYS
Solar/Wind Harmer
-0.029
3146206CASHIE
Solar/Wind Harmer
-0.029
970601AG2-382 GEN
Solar/Wind Harmer
12.703
316087AB2-174 GEN
Solar/Wind Harmer
4.11
3151031BRUNSWICKG2
50/50
3.97
3151101ELIZAR3
50/50
27.722
3150861SPRUNCD
50/50
1.346
3151161SURRY 1
50/50
10.381
970917AG2-570 GEN
Solar/Wind Harmer
81.486
315773AC2-141 GEN
Solar/Wind Harmer
13.395
944581AF1-123 GEN
Solar/Wind Harmer
144.734
944601AF1-125 GEN
Solar/Wind Harmer
142.475
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146456SLIGO L269
Solar/Wind Harmer
-0.031
971153AH1-033 GEN
Solar/Wind Harmer
3.829
3144536CHRHLND
Solar/Wind Harmer
-0.005
315813AE1-149 C
Solar/Wind Harmer
19.509
970659AG2-427 GEN
Solar/Wind Harmer
2.937
316083AB2-161 GEN
Solar/Wind Harmer
5.063
970661AG2-428 GEN
Solar/Wind Harmer
5.873
316320Y1-086
Solar/Wind Harmer
1.826
316435W1029_GEN3
Solar/Wind Harmer
5.597
315839AE2-212 C
Solar/Wind Harmer
0.929
3145336SMITFLD
Solar/Wind Harmer
-0.012
3146516WINFALL
Solar/Wind Harmer
-0.031
3146626S HERTFORD
Solar/Wind Harmer
-0.031
3145273HOLLAND
Solar/Wind Harmer
-0.023
965281AG1-393 GEN
Solar/Wind Harmer
3.804
3151221GRAVEL6
Adder
19.649
3151171GRAVELC
Adder
3.78
3146376EDENTON
Solar/Wind Harmer
-0.03
961611AG1-000B GEN
Solar/Wind Harmer
6.358
316365GEN2_N
Solar/Wind Harmer
2.014
316313AB2-026
Solar/Wind Harmer
0.805
316258AE1-075 C
Solar/Wind Harmer
0.725
316405AF2-144 C
Solar/Wind Harmer
0.765
3143336POWHATN
Solar/Wind Harmer
3.012
315778AD1-151 GEN
Solar/Wind Harmer
25.835
315614AA2-178 GEN
Solar/Wind Harmer
3.204
970129AG2-093 GEN
Solar/Wind Harmer
16.692
3144216WINCHST
Adder
0.987
970133AG2-095 GEN
Solar/Wind Harmer
3.307
3156081AA2-088 GEN
Solar/Wind Harmer
9.526
971157AH1-035 GEN
Solar/Wind Harmer
3.664
3150921YORKTN3
Adder
6.541
315737AD1-076 GEN
Solar/Wind Harmer
5.557
316478AD1-087 GEN
Solar/Wind Harmer
2.52
316486AD2-202 GEN
Solar/Wind Harmer
0.738
966621AG1-532 GEN
Solar/Wind Harmer
0.59
3145893MURPHYS
Solar/Wind Harmer
0.203
3145893MURPHYS
Solar/Wind Harmer
-0.029
3146206CASHIE
Solar/Wind Harmer
-0.029
957521AF2-046 GEN
Solar/Wind Harmer
22.828
961681AG1-008 GEN
Solar/Wind Harmer
22.828
3146173TUNIS
Solar/Wind Harmer
-0.029
3156021HOLLOMANSOL
Solar/Wind Harmer
3.873
316463AE2-346 GEN
Solar/Wind Harmer
0.465
316140AB2-099
Solar/Wind Harmer
0.194
962331AG1-082 GEN
Solar/Wind Harmer
3.59
313506AB2-031 GEN
Solar/Wind Harmer
2.306
3142666NORTHAMPTON
Solar/Wind Harmer
-0.028
3146263WOODLND
Solar/Wind Harmer
-0.028
3143096IRON208
Adder
1.062
3143096IRON208
Adder
1.041
316382AG1-145 C
Solar/Wind Harmer
0.853
3147043LAWRENC
Solar/Wind Harmer
-0.017
316317KELFORD C
Solar/Wind Harmer
1.328
3145823KELFORD
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.112
3145796HORNRTN
Solar/Wind Harmer
-0.028
3145963POPLR C
Solar/Wind Harmer
-0.028
3142946ENON
Solar/Wind Harmer
-0.009
316210AC1-098 GEN
Solar/Wind Harmer
4.299
3145933PARMELE
Solar/Wind Harmer
-0.027
966801AG1-551 GEN
Solar/Wind Harmer
3.395
315724AD1-057 GEN
Solar/Wind Harmer
1.544
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
970293AG2-193 GEN
Solar/Wind Harmer
3.331
316327AA2-057 GEN
Solar/Wind Harmer
2.686
3142433PROV 92
Adder
0.458
3142433PROV 92
Adder
0.458
3146233WITAKRS
Solar/Wind Harmer
0.548
3146233WITAKRS
Solar/Wind Harmer
-0.018
3138543CONSLDL
Solar/Wind Harmer
-0.017
316131AB2-060 GEN
Solar/Wind Harmer
2.82
3146073TAR RVR
Solar/Wind Harmer
-0.026
3146083TARBORO
Solar/Wind Harmer
-0.026
970909AG2-566 GEN
Solar/Wind Harmer
2.466
3141843SHACKLE
Adder
1.162
3144293JTRSVLE
Adder
0.705
3150351NORNECKC2
Adder
1.858
972255AH1-712 GEN
Adder
59.932
316044AC1-158 PL1
Solar/Wind Helper
2.745
316450AC1-158 RIC
Solar/Wind Helper
0.732
3147666LOUISA
Solar/Wind Helper
0.987
316170AC1-121 GEN2
Solar/Wind Helper
0.472
3132273ORANGE
Solar/Wind Helper
0.057
3141196NOKESVL
Solar/Wind Helper
0.931
964241AG1-285 GEN
Solar/Wind Harmer
19.851
970119AG2-088 GEN
50/50
44.697
315243AE2-183_GT3
50/50
5.046
3151051BRUNSWICKS1
50/50
8.24
3151021BRUNSWICKG1
50/50
3.97
971451AH1-221 GEN
50/50
12.059
3150981CHESPKA
50/50
3.724
3150851SPRUNCC
50/50
1.346
3152331SURRY 2
50/50
11.301
3143226MDLTHAN
Solar/Wind Harmer
-0.038
940641AE2-051 GEN
Solar/Wind Harmer
33.588
939411AE1-173 GEN
Solar/Wind Harmer
173.894
3143526WINTERP
Solar/Wind Harmer
-0.178
970919AG2-571 GEN
Solar/Wind Harmer
10.315
970087AG2-069 GEN
Solar/Wind Harmer
30.424
316294AC1-161 GEN
Solar/Wind Harmer
10.357
944591AF1-124 GEN
Solar/Wind Harmer
145.255
316375AC2-012 GEN
Solar/Wind Harmer
10.929
316388AE2-253 GEN
Solar/Wind Harmer
2.123
3146456SLIGO L269
Solar/Wind Harmer
-0.031
316246AF1-032 C
Solar/Wind Harmer
0.634
970659AG2-427 GEN
Solar/Wind Harmer
16.575
316381AD1-082 GEN
Solar/Wind Harmer
2.861
970661AG2-428 GEN
Solar/Wind Harmer
33.139
316093AE2-104_GEN
Solar/Wind Harmer
9.058
316072AD1-144
Solar/Wind Harmer
0.627
3145336SMITFLD
Solar/Wind Harmer
-0.123
3146516WINFALL
Solar/Wind Harmer
-0.099
3146516WINFALL
Solar/Wind Harmer
-0.031
315800Z1-036_GEN1
Solar/Wind Harmer
7.529
957481AF2-042 GEN
Solar/Wind Harmer
95.029
3151171GRAVELC
Adder
2.875
3130156CHOWAN
Solar/Wind Harmer
-0.03
315671AE2-027_GEN
Solar/Wind Harmer
22.65
961611AG1-000B GEN
Solar/Wind Harmer
14.902
971647AH1-324 GEN
Solar/Wind Harmer
15.03
316023GEN1_S
Solar/Wind Harmer
2.014
3143336POWHATN
Solar/Wind Harmer
3.544
971069AG2-661 GEN
Solar/Wind Harmer
4.719
3145663CRESWEL
Solar/Wind Harmer
-0.083
971163AH1-040 GEN
Solar/Wind Harmer
27.837
316458AB2-190 GEN2
Solar/Wind Harmer
3.001
970129AG2-093 GEN
Solar/Wind Harmer
6.761
315693AD1-088 GEN
Solar/Wind Harmer
14.68
3138126ROCKLANDING
Solar/Wind Harmer
0.09
3142543TWELFTH
Solar/Wind Harmer
-0.003
962491AG1-098 GEN
Solar/Wind Harmer
19.518
960081AF2-299 GEN
Solar/Wind Harmer
3.271
3145893MURPHYS
Solar/Wind Harmer
-0.116
3145893MURPHYS
Solar/Wind Harmer
0.862
3146206CASHIE
Solar/Wind Harmer
-0.029
971547AH1-271 GEN
Solar/Wind Harmer
7.259
3146173TUNIS
Solar/Wind Harmer
-0.029
3145683EARLEYS
Solar/Wind Harmer
-0.029
971317AH1-138 GEN
Solar/Wind Harmer
3.571
316011AB1-132 GEN
Solar/Wind Harmer
5.973
962571AG1-106 GEN
Solar/Wind Harmer
4.104
3146263WOODLND
Solar/Wind Harmer
-0.028
3143096IRON208
Adder
1.062
971795AH1-408 GEN
Solar/Wind Harmer
21.355
316190AA2-174 GEN
Solar/Wind Harmer
0.348
316159AE1-175 C
Solar/Wind Harmer
0.759
3147043LAWRENC
Adder
2.27
3145823KELFORD
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.092
3145796HORNRTN
Solar/Wind Harmer
-0.028
944631AF1-128 GEN
Adder
119.343
3145963POPLR C
Solar/Wind Harmer
-0.028
3145783HORNRTN
Solar/Wind Harmer
-0.028
316174AB2-169 GEN
Solar/Wind Harmer
4.307
316336AC2-165 C
Solar/Wind Harmer
4.835
316212AC1-099_GEN
Solar/Wind Harmer
2.388
315687AD1-152 GEN
Solar/Wind Harmer
3.298
316129AC1-054 GEN
Solar/Wind Harmer
2.39
971065AG2-659 GEN
Solar/Wind Harmer
13.588
3146293MARTNCO
Solar/Wind Harmer
0.168
315722AD1-056 GEN
Solar/Wind Harmer
2.807
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
3142433PROV 92
Solar/Wind Harmer
-0.105
3142433PROV 92
Adder
0.458
3142433PROV 92
Adder
0.458
316494AC1-189 GEN
Solar/Wind Harmer
2.84
3146233WITAKRS
Solar/Wind Harmer
-0.104
316237AB2-079_GEN
Solar/Wind Harmer
0.788
961671AG1-007 GEN
Solar/Wind Harmer
0.33
3146083TARBORO
Solar/Wind Harmer
-0.026
3145493TOT1
Solar/Wind Harmer
0.775
3141843SHACKLE
Adder
1.162
3144293JTRSVLE
Adder
0.705
3150351NORNECKC2
Adder
1.828
972277AH1-723 GEN
Adder
69.838
316045AC1-158 PL2
Solar/Wind Helper
8.788
3147666LOUISA
Solar/Wind Helper
1.717
316192AB2-158 GEN
Solar/Wind Helper
2.822
316254AC1-120 GEN1
Solar/Wind Helper
1.415
316006AB2-029 C
Solar/Wind Helper
0.131
3146043SEABORD
Solar/Wind Harmer
-0.029
3145513AHOSKIE
Solar/Wind Harmer
0.25
961941AG1-037 GEN
Solar/Wind Harmer
0.216
3145513AHOSKIE
Solar/Wind Harmer
-0.029
315607AA1-063A GEN
Solar/Wind Harmer
2.895
3145683EARLEYS
Solar/Wind Harmer
-0.057
3145683EARLEYS
Solar/Wind Harmer
-0.029
3145683EARLEYS
Solar/Wind Harmer
-0.029
315652AC1-086 GEN
Solar/Wind Harmer
32.119
3137643SOCKMAN
Solar/Wind Harmer
-0.113
3145796HORNRTN
Solar/Wind Harmer
-0.09
3145796HORNRTN
Solar/Wind Harmer
-0.011
3146033SCOT NK
Solar/Wind Harmer
-0.11
957831AF2-077 GEN
Solar/Wind Harmer
0.824
3138283WHITEMARSH
Solar/Wind Harmer
0.042
970831AG2-522 GEN
Solar/Wind Harmer
13.68
316005AA1-067
Solar/Wind Harmer
0.541
3145746EVERETS
Solar/Wind Harmer
-0.106
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
970181AG2-120 GEN
Solar/Wind Harmer
3.507
971167AH1-042 GEN
Solar/Wind Harmer
25.67
3142433PROV 92
Adder
0.458
3142433PROV 92
Adder
0.458
315976AC1-164 GENA
Solar/Wind Harmer
27.981
316169AC1-164_GENC
Solar/Wind Harmer
24.173
315975AC1-164 GENB
Solar/Wind Harmer
0.828
957861AF2-080 GEN
Solar/Wind Harmer
11.55
316420AA1-050 GEN
Solar/Wind Harmer
2.998
316319Z2-044 C
Solar/Wind Harmer
1.447
316239AB2-077_GEN
Solar/Wind Harmer
0.788
316238AB2-078_GEN
Solar/Wind Harmer
0.788
3145573BETHELC
Solar/Wind Harmer
-0.026
3145573BETHELC
Solar/Wind Harmer
-0.026
972205AH1-687 GEN
Adder
6.895
972189AH1-679 GEN
Adder
2.574
972193AH1-681 GEN
Adder
2.678
316164AC1-076 GEN
Solar/Wind Helper
1.627
970533AG2-339 GEN
50/50
27.956
970531AG2-338 GEN
50/50
11.182
315242AE2-183_GT2
50/50
5.046
315241AE2-183_GT1
50/50
5.015
972185AH1-677 GEN
50/50
18.191
3151041BRUNSWICKG3
50/50
3.97
972187AH1-678 GEN
50/50
9.111
3150991CHESPKB
50/50
3.124
3150991CHESPKB
50/50
3.049
971223AH1-071 GEN
Solar/Wind Harmer
4.708
3143526WINTERP
Solar/Wind Harmer
-0.178
970933AG2-581 GEN
Solar/Wind Harmer
30.984
3144356SAPONY
Solar/Wind Harmer
1.13
316185AD1-033 GEN
Solar/Wind Harmer
3.336
3142956BIRDNECK
Solar/Wind Harmer
1.696
316316AC1-027 C
Solar/Wind Harmer
0.97
316036AC1-147 C
Solar/Wind Harmer
0.852
3145506HICKORY
Solar/Wind Harmer
-0.126
3145506HICKORY
Solar/Wind Harmer
-0.075
3145506HICKORY
Solar/Wind Harmer
-0.019
316339AD2-160 GEN
Solar/Wind Harmer
2.123
316018AA1-139 ULT2
Solar/Wind Harmer
2.695
316017AA1-139 ULT1
Solar/Wind Harmer
2.546
3137176SLIGO L2192
Solar/Wind Harmer
-0.124
3146456SLIGO L269
Solar/Wind Harmer
3.71
3130086AYDLETT
Solar/Wind Harmer
-0.125
970657AG2-426 GEN
Solar/Wind Harmer
9.748
970657AG2-426 GEN
Solar/Wind Harmer
2.039
3146386ELIZ CT
Solar/Wind Harmer
-0.031
316431W1029_GEN1
Solar/Wind Harmer
5.597
316433W1029_GEN2
Solar/Wind Harmer
5.597
316236AE1-162_GEN
Solar/Wind Harmer
0.929
3146516WINFALL
Solar/Wind Harmer
-0.031
3146516WINFALL
Solar/Wind Harmer
-0.031
3146516WINFALL
Solar/Wind Harmer
-0.031
3146626S HERTFORD
Solar/Wind Harmer
-0.031
3146626S HERTFORD
Solar/Wind Harmer
-0.031
970099AG2-077 GEN
Solar/Wind Harmer
38.011
315742AE1-103 GEN
Solar/Wind Harmer
3.171
3146376EDENTON
Solar/Wind Harmer
0.896
3146376EDENTON
Solar/Wind Harmer
0.896
316240AF1-291 C
Solar/Wind Harmer
0.906
316033AB2-134 GEN
Solar/Wind Harmer
9.651
315697AD1-025 GEN
Solar/Wind Harmer
6.053
944641AF1-129 GEN
Adder
126.539
316065AD1-022 GEN
Solar/Wind Harmer
14.554
3145893MURPHYS
Solar/Wind Harmer
0.81
3145893MURPHYS
Solar/Wind Harmer
-0.052
3146173TUNIS
Solar/Wind Harmer
-0.029
3146173TUNIS
Solar/Wind Harmer
-0.029
316181AB2-040 GEN
Solar/Wind Harmer
4.002
3142666NORTHAMPTON
Solar/Wind Harmer
-0.028
3142666NORTHAMPTON
Solar/Wind Harmer
-0.028
3142666NORTHAMPTON
Solar/Wind Harmer
-0.028
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
316426AA2-053 GEN
Solar/Wind Harmer
2.861
3145593CAROLNA
Solar/Wind Harmer
-0.028
3145593CAROLNA
Solar/Wind Harmer
-0.028
966811AG1-552 GEN
Solar/Wind Harmer
3.179
3145593CAROLNA
Solar/Wind Harmer
0.235
3145796HORNRTN
Solar/Wind Harmer
-0.084
3145783HORNRTN
Solar/Wind Harmer
3.335
3145783HORNRTN
Solar/Wind Harmer
2.668
3145783HORNRTN
Solar/Wind Harmer
0.834
3145783HORNRTN
Solar/Wind Harmer
0.334
3142946ENON
Solar/Wind Harmer
-0.003
316274AC1-208 GEN
Solar/Wind Harmer
2.942
3145933PARMELE
Solar/Wind Harmer
-0.054
3145933PARMELE
Solar/Wind Harmer
-0.027
3142366NRTHEST
Adder
0.786
3150691DARBY 3
Adder
17.226
3150701DARBY 4
Adder
17.185
3150681DARBY 2
Adder
17.165
3150671DARBY 1
Adder
17.145
971741AH1-377 GEN
Solar/Wind Harmer
31.097
939181AE1-148 GEN
Solar/Wind Harmer
14.98
316075AC2-137 C
Solar/Wind Harmer
0.711
313527AB2-043 GEN
Solar/Wind Harmer
4.254
3145493TOT1
Solar/Wind Harmer
0.404
3145453TOT5
Solar/Wind Harmer
0.242
3145603CNETO
Solar/Wind Harmer
0.162
970301AG2-198 GEN
Solar/Wind Harmer
12.986
3144293JTRSVLE
Adder
0.705
3144293JTRSVLE
Adder
0.594
3142296MT RD221
Adder
0.704
3150341NORNECKC1
Adder
1.92
3150341NORNECKC1
Adder
1.904
316447AC1-158 HLD
Solar/Wind Helper
6.042
315651AD1-115 GEN
Solar/Wind Helper
1.014
966001AG1-469 GEN
Solar/Wind Helper
0.285
LAGNLTFEXP_LAGN->PJM
CLTF
11.269
CBM South 2LTFEXP_CBM-S2->PJM
CBM
33.419
TVALTFEXP_TVA->PJM
CLTF
5.67
CPLELTFEXP_CPLE->PJM
CLTF
15.222
CBM West 2LTFEXP_CBM-W2->PJM
CBM
60.286
CBM West 1LTFEXP_CBM-W1->PJM
CBM
37.367
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.53
MECLTFEXP_MEC->PJM
CLTF
5.657
SIGELTFEXP_SIGE->PJM
CLTF
0.172
NYPJM->LTFIMP_NY
CLTF
3.09
LGEELTFEXP_LGEE->PJM
CLTF
2.105
WECLTFEXP_WEC->PJM
CLTF
1.07

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-1: G202_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-1: G202_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.07 %
Rating:3118.0 MVA
Rating Type:C
MVA to Mitigate:4086.88
MW Contribution:10.85
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
3.571
970413AG2-270 GEN
50/50
21.45
3151101ELIZAR3
50/50
21.759
970917AG2-570 GEN
Solar/Wind Harmer
73.039
316313AB2-026
Solar/Wind Harmer
0.72
316258AE1-075 C
Solar/Wind Harmer
0.648
316405AF2-144 C
Solar/Wind Harmer
0.684
3143336POWHATN
Solar/Wind Harmer
2.693
316478AD1-087 GEN
Solar/Wind Harmer
2.233
316486AD2-202 GEN
Solar/Wind Harmer
0.654
316365GEN2_N
Solar/Wind Harmer
1.694
944581AF1-123 GEN
Solar/Wind Harmer
114.149
944601AF1-125 GEN
Solar/Wind Harmer
112.367
315773AC2-141 GEN
Solar/Wind Harmer
10.461
3146456SLIGO L269
Solar/Wind Harmer
-0.025
971153AH1-033 GEN
Solar/Wind Harmer
3.022
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316320Y1-086
Solar/Wind Harmer
1.445
970661AG2-428 GEN
Solar/Wind Harmer
4.62
966621AG1-532 GEN
Solar/Wind Harmer
0.498
316435W1029_GEN3
Solar/Wind Harmer
4.441
316083AB2-161 GEN
Solar/Wind Harmer
3.979
970659AG2-427 GEN
Solar/Wind Harmer
2.307
3146516WINFALL
Solar/Wind Harmer
-0.024
315813AE1-149 C
Solar/Wind Harmer
15.291
3144536CHRHLND
Solar/Wind Harmer
-0.004
3145273HOLLAND
Solar/Wind Harmer
-0.018
3146626S HERTFORD
Solar/Wind Harmer
-0.024
3146376EDENTON
Solar/Wind Harmer
-0.024
313506AB2-031 GEN
Solar/Wind Harmer
1.938
3156081AA2-088 GEN
Solar/Wind Harmer
7.776
3147043LAWRENC
Solar/Wind Harmer
-0.014
315614AA2-178 GEN
Solar/Wind Harmer
2.579
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3145893MURPHYS
Solar/Wind Harmer
0.166
3145893MURPHYS
Solar/Wind Harmer
-0.024
315839AE2-212 C
Solar/Wind Harmer
0.716
957521AF2-046 GEN
Solar/Wind Harmer
18.692
961681AG1-008 GEN
Solar/Wind Harmer
18.692
971157AH1-035 GEN
Solar/Wind Harmer
2.963
315737AD1-076 GEN
Solar/Wind Harmer
4.498
3146173TUNIS
Solar/Wind Harmer
-0.024
3146206CASHIE
Solar/Wind Harmer
-0.024
3145336SMITFLD
Solar/Wind Harmer
-0.009
316463AE2-346 GEN
Solar/Wind Harmer
0.381
316140AB2-099
Solar/Wind Harmer
0.159
962331AG1-082 GEN
Solar/Wind Harmer
2.944
3145796HORNRTN
Solar/Wind Harmer
-0.094
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146263WOODLND
Solar/Wind Harmer
-0.023
3150861SPRUNCD
Adder
0.964
3156021HOLLOMANSOL
Solar/Wind Harmer
3.164
316317KELFORD C
Solar/Wind Harmer
1.095
3145823KELFORD
Solar/Wind Harmer
-0.023
965281AG1-393 GEN
Solar/Wind Harmer
2.888
3145963POPLR C
Solar/Wind Harmer
-0.023
970909AG2-566 GEN
Solar/Wind Harmer
2.169
3151221GRAVEL6
Adder
14.771
3151171GRAVELC
Adder
2.842
316210AC1-098 GEN
Solar/Wind Harmer
3.58
316131AB2-060 GEN
Solar/Wind Harmer
2.441
961611AG1-000B GEN
Solar/Wind Harmer
4.747
315724AD1-057 GEN
Solar/Wind Harmer
1.295
964241AG1-285 GEN
Solar/Wind Harmer
17.552
3145933PARMELE
Solar/Wind Harmer
-0.022
966801AG1-551 GEN
Solar/Wind Harmer
2.798
316327AA2-057 GEN
Solar/Wind Harmer
2.249
315785AD2-033 C
Solar/Wind Harmer
5.032
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
970257AG2-171 GEN
Solar/Wind Harmer
8.289
959311AF2-222 GEN
Solar/Wind Harmer
22.999
3146233WITAKRS
Solar/Wind Harmer
0.46
3146233WITAKRS
Solar/Wind Harmer
-0.015
3138543CONSLDL
Solar/Wind Harmer
-0.014
315778AD1-151 GEN
Solar/Wind Harmer
18.993
3144293JTRSVLE
Adder
0.613
3144216WINCHST
Adder
0.711
3150921YORKTN3
Adder
4.681
970119AG2-088 GEN
50/50
40.525
315243AE2-183_GT3
50/50
4.543
3151051BRUNSWICKS1
50/50
7.411
3151021BRUNSWICKG1
50/50
3.571
971451AH1-221 GEN
50/50
10.845
3151531CLOVER1
50/50
4.915
3143226MDLTHAN
Solar/Wind Harmer
-0.034
940641AE2-051 GEN
Solar/Wind Harmer
29.721
939411AE1-173 GEN
Solar/Wind Harmer
150.037
970919AG2-571 GEN
Solar/Wind Harmer
9.245
970087AG2-069 GEN
Solar/Wind Harmer
27.26
3143526WINTERP
Solar/Wind Harmer
-0.15
957481AF2-042 GEN
Solar/Wind Harmer
84.586
3143336POWHATN
Solar/Wind Harmer
3.168
315693AD1-088 GEN
Solar/Wind Harmer
13.025
962491AG1-098 GEN
Solar/Wind Harmer
17.31
316023GEN1_S
Solar/Wind Harmer
1.694
944591AF1-124 GEN
Solar/Wind Harmer
114.56
316294AC1-161 GEN
Solar/Wind Harmer
8.089
316388AE2-253 GEN
Solar/Wind Harmer
1.675
3146456SLIGO L269
Solar/Wind Harmer
-0.025
316375AC2-012 GEN
Solar/Wind Harmer
8.572
3150981CHESPKA
Adder
2.753
316336AC2-165 C
Solar/Wind Harmer
4.3
316246AF1-032 C
Solar/Wind Harmer
0.5
316093AE2-104_GEN
Solar/Wind Harmer
7.163
970661AG2-428 GEN
Solar/Wind Harmer
26.068
960081AF2-299 GEN
Solar/Wind Harmer
2.759
316381AD1-082 GEN
Solar/Wind Harmer
2.248
970659AG2-427 GEN
Solar/Wind Harmer
13.019
3146516WINFALL
Solar/Wind Harmer
-0.079
3146516WINFALL
Solar/Wind Harmer
-0.024
315800Z1-036_GEN1
Solar/Wind Harmer
6.004
3130156CHOWAN
Solar/Wind Harmer
-0.024
971795AH1-408 GEN
Solar/Wind Harmer
18.101
316072AD1-144
Solar/Wind Harmer
0.488
315687AD1-152 GEN
Solar/Wind Harmer
2.903
3147043LAWRENC
Adder
1.929
3145663CRESWEL
Solar/Wind Harmer
-0.067
971163AH1-040 GEN
Solar/Wind Harmer
22.406
316011AB1-132 GEN
Solar/Wind Harmer
4.994
962571AG1-106 GEN
Solar/Wind Harmer
3.431
3145893MURPHYS
Solar/Wind Harmer
-0.095
3145893MURPHYS
Solar/Wind Harmer
0.706
3146173TUNIS
Solar/Wind Harmer
-0.024
316190AA2-174 GEN
Solar/Wind Harmer
0.29
3146206CASHIE
Solar/Wind Harmer
-0.024
971547AH1-271 GEN
Solar/Wind Harmer
5.898
3145336SMITFLD
Solar/Wind Harmer
-0.094
3145796HORNRTN
Solar/Wind Harmer
-0.077
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146263WOODLND
Solar/Wind Harmer
-0.023
3150851SPRUNCC
Adder
0.964
3145783HORNRTN
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
316129AC1-054 GEN
Solar/Wind Harmer
2.042
971065AG2-659 GEN
Solar/Wind Harmer
11.627
3145823KELFORD
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.023
316174AB2-169 GEN
Solar/Wind Harmer
3.526
3151171GRAVELC
Adder
2.161
316212AC1-099_GEN
Solar/Wind Harmer
1.989
315671AE2-027_GEN
Solar/Wind Harmer
17.038
316237AB2-079_GEN
Solar/Wind Harmer
0.682
961611AG1-000B GEN
Solar/Wind Harmer
11.126
315722AD1-056 GEN
Solar/Wind Harmer
2.354
3146293MARTNCO
Solar/Wind Harmer
0.139
971647AH1-324 GEN
Solar/Wind Harmer
11.16
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
316494AC1-189 GEN
Solar/Wind Harmer
2.363
3146233WITAKRS
Solar/Wind Harmer
-0.087
971069AG2-661 GEN
Solar/Wind Harmer
3.469
970685AG2-442 GEN
Solar/Wind Harmer
19.125
3144293JTRSVLE
Adder
0.613
3143096IRON208
Adder
0.73
944631AF1-128 GEN
Adder
80.725
3142433PROV 92
Adder
0.303
3142433PROV 92
Adder
0.303
3141843SHACKLE
Adder
0.759
3150351NORNECKC2
Adder
1.14
316045AC1-158 PL2
Solar/Wind Helper
5.258
3147666LOUISA
Solar/Wind Helper
0.902
316303AF2-085
50/50
5.403
315244AE2-183_ST
50/50
7.855
963041AG1-153 GEN
50/50
7.23
315779AE2-040
50/50
3.41
3151541CLOVER2
50/50
4.892
941031AE2-094 GEN
Solar/Wind Harmer
59.803
944011AF1-069 GEN
Solar/Wind Harmer
18.738
970673AG2-436 GEN
Solar/Wind Harmer
65.622
970673AG2-436 GEN
Solar/Wind Harmer
33.227
971967AH1-528 GEN
Solar/Wind Harmer
57.655
970085AG2-068 GEN
Solar/Wind Harmer
18.173
970581AG2-369 GEN
Solar/Wind Harmer
15.629
316233AE1-074 FULL
Solar/Wind Harmer
0.781
971281AH1-106 GEN
Solar/Wind Harmer
4.721
971283AH1-107 GEN
Solar/Wind Harmer
4.721
316315AB2-025 C
Solar/Wind Harmer
0.74
315814AE2-033 C
Solar/Wind Harmer
25.448
3143316POE
Solar/Wind Harmer
-0.102
3151081ELIZAR1
Adder
20.247
3151091ELIZAR2
Adder
19.895
957871AF2-081 GEN
Solar/Wind Harmer
12.412
319010AE1-072 C
Solar/Wind Harmer
5.013
3146406KITTY HAWK
Solar/Wind Harmer
0.021
3152611GOSPORTB
Adder
2.808
3152621GOSPORTC
Adder
2.383
3152601GOSPORTA
Adder
2.198
316305AF2-043 C
Solar/Wind Harmer
0.745
313526AB2-022
Solar/Wind Harmer
0.665
315835AF2-110_GEN
Solar/Wind Harmer
3.079
316321Z2-027
Solar/Wind Harmer
0.663
3146396TANGLEW
Solar/Wind Harmer
0.452
3145176PASQUOTANK
Solar/Wind Harmer
-0.015
3146486SUNBURY
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
316311AC2-079 GEN
Solar/Wind Harmer
12.402
315833AF1-017_GEN
Solar/Wind Harmer
4.67
316349AD2-085 GEN
Solar/Wind Harmer
2.187
946281AF1-292 GEN
Solar/Wind Harmer
0.549
315611Z1-036_GEN2
Solar/Wind Harmer
6.004
316087AB2-174 GEN
Solar/Wind Harmer
3.457
3130156CHOWAN
Solar/Wind Harmer
-0.024
3130156CHOWAN
Solar/Wind Harmer
-0.024
965291AG1-394 GEN
Solar/Wind Harmer
2.123
315816AE2-034 GEN
Solar/Wind Harmer
1.934
315652AC1-086 GEN
Solar/Wind Harmer
26.851
3137643SOCKMAN
Solar/Wind Harmer
-0.095
316318V4-068
Solar/Wind Harmer
0.593
3145893MURPHYS
Solar/Wind Harmer
-0.064
3145893MURPHYS
Solar/Wind Harmer
-0.024
3146043SEABORD
Solar/Wind Harmer
-0.024
315607AA1-063A GEN
Solar/Wind Harmer
2.4
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.786
315733AD1-074 GEN2
Solar/Wind Harmer
4.786
315735AD1-075 GEN1
Solar/Wind Harmer
2.394
3146206CASHIE
Solar/Wind Harmer
-0.024
970601AG2-382 GEN
Solar/Wind Harmer
10.322
3145513AHOSKIE
Solar/Wind Harmer
0.205
961941AG1-037 GEN
Solar/Wind Harmer
0.177
3145513AHOSKIE
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.075
3145796HORNRTN
Solar/Wind Harmer
-0.009
971285AH1-108 GEN
Adder
1.578
971445AH1-216 GEN
Solar/Wind Harmer
14.547
3145683EARLEYS
Solar/Wind Harmer
-0.047
3145683EARLEYS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
970831AG2-522 GEN
Solar/Wind Harmer
11.661
3146033SCOT NK
Solar/Wind Harmer
-0.092
972265AH1-717 GEN
Adder
15.775
3151201GRAVEL4
Adder
14.788
3151191GRAVEL3
Adder
14.601
3151211GRAVEL5
Adder
14.601
316239AB2-077_GEN
Solar/Wind Harmer
0.682
316238AB2-078_GEN
Solar/Wind Harmer
0.682
971443AH1-215 GEN
Solar/Wind Harmer
4.356
316005AA1-067
Solar/Wind Harmer
0.448
3145746EVERETS
Solar/Wind Harmer
-0.088
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
970181AG2-120 GEN
Solar/Wind Harmer
2.904
3144303KENBRDG
Solar/Wind Harmer
-0.018
316369SG1_INVT
Solar/Wind Harmer
3.949
957861AF2-080 GEN
Solar/Wind Harmer
9.609
316319Z2-044 C
Solar/Wind Harmer
1.213
316420AA1-050 GEN
Solar/Wind Harmer
2.5
3142433PROV 92
Adder
0.303
3142433PROV 92
Adder
0.303
972205AH1-687 GEN
Adder
5.892
970683AG2-441 GEN
Solar/Wind Harmer
7.481
970681AG2-440 GEN
Solar/Wind Harmer
5.985
970533AG2-339 GEN
50/50
25.233
970531AG2-338 GEN
50/50
10.093
315242AE2-183_GT2
50/50
4.543
315241AE2-183_GT1
50/50
4.515
972185AH1-677 GEN
50/50
16.379
3151041BRUNSWICKG3
50/50
3.571
972187AH1-678 GEN
50/50
8.194
971223AH1-071 GEN
Solar/Wind Harmer
4.269
970933AG2-581 GEN
Solar/Wind Harmer
27.802
3143526WINTERP
Solar/Wind Harmer
-0.15
3144356SAPONY
Solar/Wind Harmer
0.957
970099AG2-077 GEN
Solar/Wind Harmer
33.834
316185AD1-033 GEN
Solar/Wind Harmer
2.627
3145506HICKORY
Solar/Wind Harmer
-0.099
3145506HICKORY
Solar/Wind Harmer
-0.059
3145506HICKORY
Solar/Wind Harmer
-0.015
3142956BIRDNECK
Solar/Wind Harmer
1.333
316316AC1-027 C
Solar/Wind Harmer
0.762
316339AD2-160 GEN
Solar/Wind Harmer
1.675
316018AA1-139 ULT2
Solar/Wind Harmer
2.126
316017AA1-139 ULT1
Solar/Wind Harmer
2.009
3137176SLIGO L2192
Solar/Wind Harmer
-0.098
3146456SLIGO L269
Solar/Wind Harmer
2.928
3130086AYDLETT
Solar/Wind Harmer
-0.099
316036AC1-147 C
Solar/Wind Harmer
0.668
3150991CHESPKB
Adder
2.309
3150991CHESPKB
Adder
2.254
3146386ELIZ CT
Solar/Wind Harmer
-0.025
970657AG2-426 GEN
Solar/Wind Harmer
7.663
970657AG2-426 GEN
Solar/Wind Harmer
1.602
316431W1029_GEN1
Solar/Wind Harmer
4.441
316433W1029_GEN2
Solar/Wind Harmer
4.441
3146516WINFALL
Solar/Wind Harmer
-0.024
3146516WINFALL
Solar/Wind Harmer
-0.024
3146516WINFALL
Solar/Wind Harmer
-0.024
3146626S HERTFORD
Solar/Wind Harmer
-0.024
3146626S HERTFORD
Solar/Wind Harmer
-0.024
315742AE1-103 GEN
Solar/Wind Harmer
2.543
3146376EDENTON
Solar/Wind Harmer
0.717
3146376EDENTON
Solar/Wind Harmer
0.717
316181AB2-040 GEN
Solar/Wind Harmer
3.363
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3145893MURPHYS
Solar/Wind Harmer
0.663
3145893MURPHYS
Solar/Wind Harmer
-0.043
3145593CAROLNA
Solar/Wind Harmer
-0.024
3145593CAROLNA
Solar/Wind Harmer
-0.024
966811AG1-552 GEN
Solar/Wind Harmer
2.661
3145593CAROLNA
Solar/Wind Harmer
0.196
3146173TUNIS
Solar/Wind Harmer
-0.024
3146173TUNIS
Solar/Wind Harmer
-0.024
316426AA2-053 GEN
Solar/Wind Harmer
2.386
316065AD1-022 GEN
Solar/Wind Harmer
11.81
316236AE1-162_GEN
Solar/Wind Harmer
0.711
971741AH1-377 GEN
Solar/Wind Harmer
27.409
3145796HORNRTN
Solar/Wind Harmer
-0.07
3145783HORNRTN
Solar/Wind Harmer
2.79
3145783HORNRTN
Solar/Wind Harmer
2.232
3145783HORNRTN
Solar/Wind Harmer
0.698
3145783HORNRTN
Solar/Wind Harmer
0.279
939181AE1-148 GEN
Solar/Wind Harmer
12.946
970301AG2-198 GEN
Solar/Wind Harmer
11.421
316274AC1-208 GEN
Solar/Wind Harmer
2.458
313527AB2-043 GEN
Solar/Wind Harmer
3.682
316240AF1-291 C
Solar/Wind Harmer
0.675
3145933PARMELE
Solar/Wind Harmer
-0.044
3145933PARMELE
Solar/Wind Harmer
-0.022
970323AG2-213 GEN
Solar/Wind Harmer
11.053
971775AH1-396 GEN
Solar/Wind Harmer
1.574
316034AC1-036 C
Solar/Wind Harmer
0.41
316033AB2-134 GEN
Solar/Wind Harmer
7.127
315697AD1-025 GEN
Solar/Wind Harmer
4.47
944641AF1-129 GEN
Adder
93.238
962561AG1-105 GEN
Solar/Wind Harmer
12.325
3144293JTRSVLE
Adder
0.613
3144293JTRSVLE
Adder
0.516
3142366NRTHEST
Adder
0.501
3150691DARBY 3
Adder
10.867
3150701DARBY 4
Adder
10.841
3150681DARBY 2
Adder
10.829
3150671DARBY 1
Adder
10.816
3142296MT RD221
Adder
0.386
3150341NORNECKC1
Adder
1.198
3150341NORNECKC1
Adder
1.188
316447AC1-158 HLD
Solar/Wind Helper
3.615
3143096IRON208
Adder
0.73
3143096IRON208
Adder
0.715
3142433PROV 92
Adder
0.303
3142433PROV 92
Adder
0.303
3141843SHACKLE
Adder
0.759
3150351NORNECKC2
Adder
1.16
316044AC1-158 PL1
Solar/Wind Helper
1.642
316450AC1-158 RIC
Solar/Wind Helper
0.438
3147666LOUISA
Solar/Wind Helper
0.519
LAGNLTFEXP_LAGN->PJM
CLTF
8.918
CBM South 2LTFEXP_CBM-S2->PJM
CBM
27.956
TVALTFEXP_TVA->PJM
CLTF
4.471
CPLELTFEXP_CPLE->PJM
CLTF
12.94
CBM West 2LTFEXP_CBM-W2->PJM
CBM
46.681
CBM West 1LTFEXP_CBM-W1->PJM
CBM
26.974
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.275
MECLTFEXP_MEC->PJM
CLTF
4.234
SIGELTFEXP_SIGE->PJM
CLTF
0.127
NYPJM->LTFIMP_NY
CLTF
2.444
LGEELTFEXP_LGEE->PJM
CLTF
1.534
WECLTFEXP_WEC->PJM
CLTF
0.779

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P2-2: NORTH ANNA B1_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: NORTH ANNA B1_SRT-S
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:126.92 %
Rating:3118.0 MVA
Rating Type:C
MVA to Mitigate:3957.44
MW Contribution:10.89
Bus #Bus NameTypeMW Contribution
970533AG2-339 GEN
50/50
25.341
970531AG2-338 GEN
50/50
10.136
315242AE2-183_GT2
50/50
4.563
315241AE2-183_GT1
50/50
4.535
972185AH1-677 GEN
50/50
16.45
3151041BRUNSWICKG3
50/50
3.586
972187AH1-678 GEN
50/50
8.23
971223AH1-071 GEN
Solar/Wind Harmer
4.285
970933AG2-581 GEN
Solar/Wind Harmer
27.922
3143526WINTERP
Solar/Wind Harmer
-0.151
3144356SAPONY
Solar/Wind Harmer
0.962
970099AG2-077 GEN
Solar/Wind Harmer
33.984
316185AD1-033 GEN
Solar/Wind Harmer
2.641
3145506HICKORY
Solar/Wind Harmer
-0.1
3145506HICKORY
Solar/Wind Harmer
-0.06
3145506HICKORY
Solar/Wind Harmer
-0.015
3142956BIRDNECK
Solar/Wind Harmer
1.34
316316AC1-027 C
Solar/Wind Harmer
0.766
316339AD2-160 GEN
Solar/Wind Harmer
1.684
316018AA1-139 ULT2
Solar/Wind Harmer
2.138
316017AA1-139 ULT1
Solar/Wind Harmer
2.02
3137176SLIGO L2192
Solar/Wind Harmer
-0.099
3146456SLIGO L269
Solar/Wind Harmer
2.944
316036AC1-147 C
Solar/Wind Harmer
0.672
3130086AYDLETT
Solar/Wind Harmer
-0.099
3150991CHESPKB
Adder
2.322
3150991CHESPKB
Adder
2.266
3146386ELIZ CT
Solar/Wind Harmer
-0.025
970657AG2-426 GEN
Solar/Wind Harmer
7.706
970657AG2-426 GEN
Solar/Wind Harmer
1.611
316431W1029_GEN1
Solar/Wind Harmer
4.466
316433W1029_GEN2
Solar/Wind Harmer
4.466
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.024
3146626S HERTFORD
Solar/Wind Harmer
-0.024
315742AE1-103 GEN
Solar/Wind Harmer
2.557
3146376EDENTON
Solar/Wind Harmer
0.721
3146376EDENTON
Solar/Wind Harmer
0.721
316181AB2-040 GEN
Solar/Wind Harmer
3.381
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3145893MURPHYS
Solar/Wind Harmer
0.667
3145893MURPHYS
Solar/Wind Harmer
-0.043
3145593CAROLNA
Solar/Wind Harmer
-0.024
3145593CAROLNA
Solar/Wind Harmer
-0.024
966811AG1-552 GEN
Solar/Wind Harmer
2.675
3145593CAROLNA
Solar/Wind Harmer
0.198
3146173TUNIS
Solar/Wind Harmer
-0.024
3146173TUNIS
Solar/Wind Harmer
-0.024
316065AD1-022 GEN
Solar/Wind Harmer
11.875
316426AA2-053 GEN
Solar/Wind Harmer
2.399
316236AE1-162_GEN
Solar/Wind Harmer
0.715
3145796HORNRTN
Solar/Wind Harmer
-0.071
971741AH1-377 GEN
Solar/Wind Harmer
27.515
3145783HORNRTN
Solar/Wind Harmer
2.805
3145783HORNRTN
Solar/Wind Harmer
2.244
3145783HORNRTN
Solar/Wind Harmer
0.701
3145783HORNRTN
Solar/Wind Harmer
0.281
939181AE1-148 GEN
Solar/Wind Harmer
13.009
970301AG2-198 GEN
Solar/Wind Harmer
11.463
316274AC1-208 GEN
Solar/Wind Harmer
2.472
313527AB2-043 GEN
Solar/Wind Harmer
3.699
316240AF1-291 C
Solar/Wind Harmer
0.679
3145933PARMELE
Solar/Wind Harmer
-0.045
3145933PARMELE
Solar/Wind Harmer
-0.022
316033AB2-134 GEN
Solar/Wind Harmer
7.172
315697AD1-025 GEN
Solar/Wind Harmer
4.498
970323AG2-213 GEN
Solar/Wind Harmer
11.1
971775AH1-396 GEN
Solar/Wind Harmer
1.581
316034AC1-036 C
Solar/Wind Harmer
0.412
944641AF1-129 GEN
Adder
93.824
962561AG1-105 GEN
Solar/Wind Harmer
12.386
3145493TOT1
Solar/Wind Harmer
0.34
3145453TOT5
Solar/Wind Harmer
0.204
3145603CNETO
Solar/Wind Harmer
0.136
3144293JTRSVLE
Adder
0.615
3144293JTRSVLE
Adder
0.518
3142366NRTHEST
Adder
0.505
3150691DARBY 3
Adder
10.955
3150701DARBY 4
Adder
10.93
3150681DARBY 2
Adder
10.917
3150671DARBY 1
Adder
10.904
3142296MT RD221
Adder
0.39
3150341NORNECKC1
Adder
1.211
3150341NORNECKC1
Adder
1.201
316447AC1-158 HLD
Solar/Wind Helper
3.579
3151031BRUNSWICKG2
50/50
3.586
970413AG2-270 GEN
50/50
21.547
3151101ELIZAR3
50/50
21.88
970917AG2-570 GEN
Solar/Wind Harmer
73.368
316313AB2-026
Solar/Wind Harmer
0.722
316258AE1-075 C
Solar/Wind Harmer
0.65
316405AF2-144 C
Solar/Wind Harmer
0.686
3143336POWHATN
Solar/Wind Harmer
2.702
316478AD1-087 GEN
Solar/Wind Harmer
2.243
316486AD2-202 GEN
Solar/Wind Harmer
0.657
316365GEN2_N
Solar/Wind Harmer
1.702
944581AF1-123 GEN
Solar/Wind Harmer
114.775
944601AF1-125 GEN
Solar/Wind Harmer
112.984
315773AC2-141 GEN
Solar/Wind Harmer
10.519
3146456SLIGO L269
Solar/Wind Harmer
-0.025
971153AH1-033 GEN
Solar/Wind Harmer
3.039
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316320Y1-086
Solar/Wind Harmer
1.453
970661AG2-428 GEN
Solar/Wind Harmer
4.646
316435W1029_GEN3
Solar/Wind Harmer
4.466
316083AB2-161 GEN
Solar/Wind Harmer
4.001
966621AG1-532 GEN
Solar/Wind Harmer
0.5
970659AG2-427 GEN
Solar/Wind Harmer
2.32
3146516WINFALL
Solar/Wind Harmer
-0.025
315813AE1-149 C
Solar/Wind Harmer
15.377
3144536CHRHLND
Solar/Wind Harmer
-0.004
3145273HOLLAND
Solar/Wind Harmer
-0.018
3146626S HERTFORD
Solar/Wind Harmer
-0.024
3146376EDENTON
Solar/Wind Harmer
-0.024
313506AB2-031 GEN
Solar/Wind Harmer
1.948
3156081AA2-088 GEN
Solar/Wind Harmer
7.818
3147043LAWRENC
Solar/Wind Harmer
-0.014
315614AA2-178 GEN
Solar/Wind Harmer
2.593
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3145893MURPHYS
Solar/Wind Harmer
0.167
3145893MURPHYS
Solar/Wind Harmer
-0.024
315839AE2-212 C
Solar/Wind Harmer
0.72
957521AF2-046 GEN
Solar/Wind Harmer
18.794
961681AG1-008 GEN
Solar/Wind Harmer
18.794
971157AH1-035 GEN
Solar/Wind Harmer
2.979
315737AD1-076 GEN
Solar/Wind Harmer
4.523
3146173TUNIS
Solar/Wind Harmer
-0.024
3146206CASHIE
Solar/Wind Harmer
-0.024
3145336SMITFLD
Solar/Wind Harmer
-0.009
316463AE2-346 GEN
Solar/Wind Harmer
0.383
316140AB2-099
Solar/Wind Harmer
0.16
962331AG1-082 GEN
Solar/Wind Harmer
2.96
3145796HORNRTN
Solar/Wind Harmer
-0.094
3145796HORNRTN
Solar/Wind Harmer
-0.024
3150861SPRUNCD
Adder
0.97
3146263WOODLND
Solar/Wind Harmer
-0.024
3156021HOLLOMANSOL
Solar/Wind Harmer
3.182
316317KELFORD C
Solar/Wind Harmer
1.101
3145823KELFORD
Solar/Wind Harmer
-0.023
965281AG1-393 GEN
Solar/Wind Harmer
2.906
3145963POPLR C
Solar/Wind Harmer
-0.023
3151221GRAVEL6
Adder
14.86
3151171GRAVELC
Adder
2.859
316210AC1-098 GEN
Solar/Wind Harmer
3.599
970909AG2-566 GEN
Solar/Wind Harmer
2.177
316131AB2-060 GEN
Solar/Wind Harmer
2.453
961611AG1-000B GEN
Solar/Wind Harmer
4.776
315724AD1-057 GEN
Solar/Wind Harmer
1.302
964241AG1-285 GEN
Solar/Wind Harmer
17.632
3145933PARMELE
Solar/Wind Harmer
-0.022
966801AG1-551 GEN
Solar/Wind Harmer
2.814
316327AA2-057 GEN
Solar/Wind Harmer
2.261
315785AD2-033 C
Solar/Wind Harmer
5.054
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
970257AG2-171 GEN
Solar/Wind Harmer
8.325
959311AF2-222 GEN
Solar/Wind Harmer
23.096
3146233WITAKRS
Solar/Wind Harmer
0.462
3146233WITAKRS
Solar/Wind Harmer
-0.015
315778AD1-151 GEN
Solar/Wind Harmer
19.113
3138543CONSLDL
Solar/Wind Harmer
-0.014
3146073TAR RVR
Solar/Wind Harmer
-0.022
3146083TARBORO
Solar/Wind Harmer
-0.022
3144293JTRSVLE
Adder
0.615
3144216WINCHST
Adder
0.716
3150921YORKTN3
Adder
4.712
3143096IRON208
Adder
0.735
3143096IRON208
Adder
0.72
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
3141843SHACKLE
Adder
0.766
3150351NORNECKC2
Adder
1.172
316044AC1-158 PL1
Solar/Wind Helper
1.626
316450AC1-158 RIC
Solar/Wind Helper
0.434
3147666LOUISA
Solar/Wind Helper
0.562
316303AF2-085
50/50
5.424
315244AE2-183_ST
50/50
7.889
963041AG1-153 GEN
50/50
7.262
315779AE2-040
50/50
3.426
3151541CLOVER2
50/50
4.914
941031AE2-094 GEN
Solar/Wind Harmer
60.059
944011AF1-069 GEN
Solar/Wind Harmer
18.818
970673AG2-436 GEN
Solar/Wind Harmer
65.906
970673AG2-436 GEN
Solar/Wind Harmer
33.37
971967AH1-528 GEN
Solar/Wind Harmer
57.904
970085AG2-068 GEN
Solar/Wind Harmer
18.255
970581AG2-369 GEN
Solar/Wind Harmer
15.699
316233AE1-074 FULL
Solar/Wind Harmer
0.785
971281AH1-106 GEN
Solar/Wind Harmer
4.743
971283AH1-107 GEN
Solar/Wind Harmer
4.743
316315AB2-025 C
Solar/Wind Harmer
0.744
315814AE2-033 C
Solar/Wind Harmer
25.573
3143316POE
Solar/Wind Harmer
-0.102
957871AF2-081 GEN
Solar/Wind Harmer
12.48
3151081ELIZAR1
Adder
20.359
3151091ELIZAR2
Adder
20.005
319010AE1-072 C
Solar/Wind Harmer
5.041
3146406KITTY HAWK
Solar/Wind Harmer
0.021
3152611GOSPORTB
Adder
2.823
3152621GOSPORTC
Adder
2.396
3152601GOSPORTA
Adder
2.21
316305AF2-043 C
Solar/Wind Harmer
0.749
313526AB2-022
Solar/Wind Harmer
0.669
315835AF2-110_GEN
Solar/Wind Harmer
3.096
316321Z2-027
Solar/Wind Harmer
0.667
3146396TANGLEW
Solar/Wind Harmer
0.455
3145176PASQUOTANK
Solar/Wind Harmer
-0.015
3146486SUNBURY
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
316311AC2-079 GEN
Solar/Wind Harmer
12.471
315833AF1-017_GEN
Solar/Wind Harmer
4.696
316349AD2-085 GEN
Solar/Wind Harmer
2.199
946281AF1-292 GEN
Solar/Wind Harmer
0.552
315611Z1-036_GEN2
Solar/Wind Harmer
6.037
316087AB2-174 GEN
Solar/Wind Harmer
3.475
3130156CHOWAN
Solar/Wind Harmer
-0.024
3130156CHOWAN
Solar/Wind Harmer
-0.024
965291AG1-394 GEN
Solar/Wind Harmer
2.135
315816AE2-034 GEN
Solar/Wind Harmer
1.945
315652AC1-086 GEN
Solar/Wind Harmer
26.995
3137643SOCKMAN
Solar/Wind Harmer
-0.095
316318V4-068
Solar/Wind Harmer
0.596
3145893MURPHYS
Solar/Wind Harmer
-0.064
3145893MURPHYS
Solar/Wind Harmer
-0.024
3146043SEABORD
Solar/Wind Harmer
-0.024
315607AA1-063A GEN
Solar/Wind Harmer
2.413
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.813
315733AD1-074 GEN2
Solar/Wind Harmer
4.813
315735AD1-075 GEN1
Solar/Wind Harmer
2.407
3146206CASHIE
Solar/Wind Harmer
-0.024
970601AG2-382 GEN
Solar/Wind Harmer
10.379
3145513AHOSKIE
Solar/Wind Harmer
0.206
961941AG1-037 GEN
Solar/Wind Harmer
0.178
3145513AHOSKIE
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.075
3145796HORNRTN
Solar/Wind Harmer
-0.009
971285AH1-108 GEN
Adder
1.587
971445AH1-216 GEN
Solar/Wind Harmer
14.632
3145683EARLEYS
Solar/Wind Harmer
-0.047
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
970831AG2-522 GEN
Solar/Wind Harmer
11.72
3146033SCOT NK
Solar/Wind Harmer
-0.092
972265AH1-717 GEN
Adder
15.87
3151201GRAVEL4
Adder
14.877
3151191GRAVEL3
Adder
14.689
3151211GRAVEL5
Adder
14.689
316239AB2-077_GEN
Solar/Wind Harmer
0.685
316238AB2-078_GEN
Solar/Wind Harmer
0.685
316005AA1-067
Solar/Wind Harmer
0.45
3145746EVERETS
Solar/Wind Harmer
-0.088
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
970181AG2-120 GEN
Solar/Wind Harmer
2.92
316369SG1_INVT
Solar/Wind Harmer
3.973
971443AH1-215 GEN
Solar/Wind Harmer
4.375
3144303KENBRDG
Solar/Wind Harmer
-0.018
957861AF2-080 GEN
Solar/Wind Harmer
9.664
316319Z2-044 C
Solar/Wind Harmer
1.22
316420AA1-050 GEN
Solar/Wind Harmer
2.514
3145573BETHELC
Solar/Wind Harmer
-0.022
3145573BETHELC
Solar/Wind Harmer
-0.022
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
972205AH1-687 GEN
Adder
5.897
970683AG2-441 GEN
Solar/Wind Harmer
6.68
970681AG2-440 GEN
Solar/Wind Harmer
5.344
970119AG2-088 GEN
50/50
40.684
315243AE2-183_GT3
50/50
4.563
3151051BRUNSWICKS1
50/50
7.443
3151021BRUNSWICKG1
50/50
3.586
971451AH1-221 GEN
50/50
10.893
3151531CLOVER1
50/50
4.938
3143226MDLTHAN
Solar/Wind Harmer
-0.034
940641AE2-051 GEN
Solar/Wind Harmer
29.852
939411AE1-173 GEN
Solar/Wind Harmer
150.731
970919AG2-571 GEN
Solar/Wind Harmer
9.287
970087AG2-069 GEN
Solar/Wind Harmer
27.383
3143526WINTERP
Solar/Wind Harmer
-0.151
957481AF2-042 GEN
Solar/Wind Harmer
84.959
3143336POWHATN
Solar/Wind Harmer
3.179
315693AD1-088 GEN
Solar/Wind Harmer
13.081
962491AG1-098 GEN
Solar/Wind Harmer
17.384
316023GEN1_S
Solar/Wind Harmer
1.702
944591AF1-124 GEN
Solar/Wind Harmer
115.189
316294AC1-161 GEN
Solar/Wind Harmer
8.133
316388AE2-253 GEN
Solar/Wind Harmer
1.684
3146456SLIGO L269
Solar/Wind Harmer
-0.025
316375AC2-012 GEN
Solar/Wind Harmer
8.62
3150981CHESPKA
Adder
2.768
316246AF1-032 C
Solar/Wind Harmer
0.503
316336AC2-165 C
Solar/Wind Harmer
4.313
316093AE2-104_GEN
Solar/Wind Harmer
7.202
970661AG2-428 GEN
Solar/Wind Harmer
26.214
316381AD1-082 GEN
Solar/Wind Harmer
2.261
960081AF2-299 GEN
Solar/Wind Harmer
2.773
970659AG2-427 GEN
Solar/Wind Harmer
13.092
3146516WINFALL
Solar/Wind Harmer
-0.079
3146516WINFALL
Solar/Wind Harmer
-0.025
315800Z1-036_GEN1
Solar/Wind Harmer
6.037
3130156CHOWAN
Solar/Wind Harmer
-0.024
971795AH1-408 GEN
Solar/Wind Harmer
18.192
316072AD1-144
Solar/Wind Harmer
0.491
315687AD1-152 GEN
Solar/Wind Harmer
2.916
3147043LAWRENC
Adder
1.939
3145663CRESWEL
Solar/Wind Harmer
-0.067
971163AH1-040 GEN
Solar/Wind Harmer
22.53
316011AB1-132 GEN
Solar/Wind Harmer
5.02
962571AG1-106 GEN
Solar/Wind Harmer
3.449
3145893MURPHYS
Solar/Wind Harmer
-0.095
3145893MURPHYS
Solar/Wind Harmer
0.709
3146173TUNIS
Solar/Wind Harmer
-0.024
316190AA2-174 GEN
Solar/Wind Harmer
0.292
3146206CASHIE
Solar/Wind Harmer
-0.024
971547AH1-271 GEN
Solar/Wind Harmer
5.931
3145336SMITFLD
Solar/Wind Harmer
-0.094
3145796HORNRTN
Solar/Wind Harmer
-0.078
3145796HORNRTN
Solar/Wind Harmer
-0.024
3150851SPRUNCC
Adder
0.97
3146263WOODLND
Solar/Wind Harmer
-0.024
3145783HORNRTN
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
316129AC1-054 GEN
Solar/Wind Harmer
2.052
971065AG2-659 GEN
Solar/Wind Harmer
11.686
3145823KELFORD
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.023
316174AB2-169 GEN
Solar/Wind Harmer
3.546
3151171GRAVELC
Adder
2.174
316212AC1-099_GEN
Solar/Wind Harmer
2
315671AE2-027_GEN
Solar/Wind Harmer
17.142
316237AB2-079_GEN
Solar/Wind Harmer
0.685
961611AG1-000B GEN
Solar/Wind Harmer
11.194
315722AD1-056 GEN
Solar/Wind Harmer
2.367
3146293MARTNCO
Solar/Wind Harmer
0.139
971647AH1-324 GEN
Solar/Wind Harmer
11.229
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
316494AC1-189 GEN
Solar/Wind Harmer
2.377
3146233WITAKRS
Solar/Wind Harmer
-0.087
971069AG2-661 GEN
Solar/Wind Harmer
3.491
961671AG1-007 GEN
Solar/Wind Harmer
0.278
3146083TARBORO
Solar/Wind Harmer
-0.022
3145493TOT1
Solar/Wind Harmer
0.651
970685AG2-442 GEN
Solar/Wind Harmer
19.204
3144293JTRSVLE
Adder
0.615
3143096IRON208
Adder
0.735
944631AF1-128 GEN
Adder
81.311
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
3141843SHACKLE
Adder
0.766
3150351NORNECKC2
Adder
1.153
316045AC1-158 PL2
Solar/Wind Helper
5.205
3147666LOUISA
Solar/Wind Helper
0.977
316192AB2-158 GEN
Solar/Wind Helper
1.608
LAGNLTFEXP_LAGN->PJM
CLTF
9.063
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.182
TVALTFEXP_TVA->PJM
CLTF
4.543
CPLELTFEXP_CPLE->PJM
CLTF
13.025
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.637
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.006
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.545
MECLTFEXP_MEC->PJM
CLTF
4.353
SIGELTFEXP_SIGE->PJM
CLTF
0.131
NYPJM->LTFIMP_NY
CLTF
2.393
LGEELTFEXP_LGEE->PJM
CLTF
1.582
WECLTFEXP_WEC->PJM
CLTF
0.806

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P2-2: NORTH ANNA B2_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: NORTH ANNA B2_SRT-S
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:126.92 %
Rating:3118.0 MVA
Rating Type:C
MVA to Mitigate:3957.44
MW Contribution:10.89
Bus #Bus NameTypeMW Contribution
970119AG2-088 GEN
50/50
40.684
315243AE2-183_GT3
50/50
4.563
3151051BRUNSWICKS1
50/50
7.443
3151021BRUNSWICKG1
50/50
3.586
971451AH1-221 GEN
50/50
10.893
3151531CLOVER1
50/50
4.938
3143226MDLTHAN
Solar/Wind Harmer
-0.034
940641AE2-051 GEN
Solar/Wind Harmer
29.852
939411AE1-173 GEN
Solar/Wind Harmer
150.731
970919AG2-571 GEN
Solar/Wind Harmer
9.287
970087AG2-069 GEN
Solar/Wind Harmer
27.383
3143526WINTERP
Solar/Wind Harmer
-0.151
957481AF2-042 GEN
Solar/Wind Harmer
84.959
3143336POWHATN
Solar/Wind Harmer
3.179
970533AG2-339 GEN
50/50
25.341
970531AG2-338 GEN
50/50
10.136
315242AE2-183_GT2
50/50
4.563
315241AE2-183_GT1
50/50
4.535
972185AH1-677 GEN
50/50
16.45
3151041BRUNSWICKG3
50/50
3.586
972187AH1-678 GEN
50/50
8.23
971223AH1-071 GEN
Solar/Wind Harmer
4.285
970933AG2-581 GEN
Solar/Wind Harmer
27.922
3143526WINTERP
Solar/Wind Harmer
-0.151
3144356SAPONY
Solar/Wind Harmer
0.962
970099AG2-077 GEN
Solar/Wind Harmer
33.984
316185AD1-033 GEN
Solar/Wind Harmer
2.641
3145506HICKORY
Solar/Wind Harmer
-0.1
316303AF2-085
50/50
5.424
315244AE2-183_ST
50/50
7.889
963041AG1-153 GEN
50/50
7.262
315779AE2-040
50/50
3.426
3151541CLOVER2
50/50
4.914
941031AE2-094 GEN
Solar/Wind Harmer
60.059
944011AF1-069 GEN
Solar/Wind Harmer
18.818
970673AG2-436 GEN
Solar/Wind Harmer
65.906
970673AG2-436 GEN
Solar/Wind Harmer
33.37
971967AH1-528 GEN
Solar/Wind Harmer
57.904
970085AG2-068 GEN
Solar/Wind Harmer
18.255
970581AG2-369 GEN
Solar/Wind Harmer
15.699
316233AE1-074 FULL
Solar/Wind Harmer
0.785
971281AH1-106 GEN
Solar/Wind Harmer
4.743
971283AH1-107 GEN
Solar/Wind Harmer
4.743
316315AB2-025 C
Solar/Wind Harmer
0.744
315814AE2-033 C
Solar/Wind Harmer
25.573
3143316POE
Solar/Wind Harmer
-0.102
957871AF2-081 GEN
Solar/Wind Harmer
12.48
3151081ELIZAR1
Adder
20.359
3151091ELIZAR2
Adder
20.005
319010AE1-072 C
Solar/Wind Harmer
5.041
3146406KITTY HAWK
Solar/Wind Harmer
0.021
3152611GOSPORTB
Adder
2.823
3152621GOSPORTC
Adder
2.396
3152601GOSPORTA
Adder
2.21
316305AF2-043 C
Solar/Wind Harmer
0.749
313526AB2-022
Solar/Wind Harmer
0.669
315835AF2-110_GEN
Solar/Wind Harmer
3.096
316321Z2-027
Solar/Wind Harmer
0.667
3146396TANGLEW
Solar/Wind Harmer
0.455
3145176PASQUOTANK
Solar/Wind Harmer
-0.015
3146486SUNBURY
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
316311AC2-079 GEN
Solar/Wind Harmer
12.471
315833AF1-017_GEN
Solar/Wind Harmer
4.696
316349AD2-085 GEN
Solar/Wind Harmer
2.199
946281AF1-292 GEN
Solar/Wind Harmer
0.552
315611Z1-036_GEN2
Solar/Wind Harmer
6.037
316087AB2-174 GEN
Solar/Wind Harmer
3.475
3130156CHOWAN
Solar/Wind Harmer
-0.024
3130156CHOWAN
Solar/Wind Harmer
-0.024
965291AG1-394 GEN
Solar/Wind Harmer
2.135
315816AE2-034 GEN
Solar/Wind Harmer
1.945
315652AC1-086 GEN
Solar/Wind Harmer
26.995
3137643SOCKMAN
Solar/Wind Harmer
-0.095
316318V4-068
Solar/Wind Harmer
0.596
3145893MURPHYS
Solar/Wind Harmer
-0.064
3145893MURPHYS
Solar/Wind Harmer
-0.024
3146043SEABORD
Solar/Wind Harmer
-0.024
315607AA1-063A GEN
Solar/Wind Harmer
2.413
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.813
315733AD1-074 GEN2
Solar/Wind Harmer
4.813
315735AD1-075 GEN1
Solar/Wind Harmer
2.407
3146206CASHIE
Solar/Wind Harmer
-0.024
970601AG2-382 GEN
Solar/Wind Harmer
10.379
3145513AHOSKIE
Solar/Wind Harmer
0.206
961941AG1-037 GEN
Solar/Wind Harmer
0.178
3145513AHOSKIE
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.075
3145796HORNRTN
Solar/Wind Harmer
-0.009
971285AH1-108 GEN
Adder
1.587
971445AH1-216 GEN
Solar/Wind Harmer
14.632
3145683EARLEYS
Solar/Wind Harmer
-0.047
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
970831AG2-522 GEN
Solar/Wind Harmer
11.72
3146033SCOT NK
Solar/Wind Harmer
-0.092
972265AH1-717 GEN
Adder
15.87
3151201GRAVEL4
Adder
14.877
3151191GRAVEL3
Adder
14.689
3151211GRAVEL5
Adder
14.689
316239AB2-077_GEN
Solar/Wind Harmer
0.685
316238AB2-078_GEN
Solar/Wind Harmer
0.685
316005AA1-067
Solar/Wind Harmer
0.45
3145746EVERETS
Solar/Wind Harmer
-0.088
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
970181AG2-120 GEN
Solar/Wind Harmer
2.92
316369SG1_INVT
Solar/Wind Harmer
3.973
971443AH1-215 GEN
Solar/Wind Harmer
4.375
3144303KENBRDG
Solar/Wind Harmer
-0.018
957861AF2-080 GEN
Solar/Wind Harmer
9.664
316319Z2-044 C
Solar/Wind Harmer
1.22
316420AA1-050 GEN
Solar/Wind Harmer
2.514
3145573BETHELC
Solar/Wind Harmer
-0.022
3145573BETHELC
Solar/Wind Harmer
-0.022
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
972205AH1-687 GEN
Adder
5.897
970683AG2-441 GEN
Solar/Wind Harmer
6.68
970681AG2-440 GEN
Solar/Wind Harmer
5.344
3145506HICKORY
Solar/Wind Harmer
-0.06
3145506HICKORY
Solar/Wind Harmer
-0.015
3142956BIRDNECK
Solar/Wind Harmer
1.34
316316AC1-027 C
Solar/Wind Harmer
0.766
316339AD2-160 GEN
Solar/Wind Harmer
1.684
316018AA1-139 ULT2
Solar/Wind Harmer
2.138
316017AA1-139 ULT1
Solar/Wind Harmer
2.02
3137176SLIGO L2192
Solar/Wind Harmer
-0.099
3146456SLIGO L269
Solar/Wind Harmer
2.944
316036AC1-147 C
Solar/Wind Harmer
0.672
3130086AYDLETT
Solar/Wind Harmer
-0.099
3150991CHESPKB
Adder
2.322
3150991CHESPKB
Adder
2.266
3146386ELIZ CT
Solar/Wind Harmer
-0.025
970657AG2-426 GEN
Solar/Wind Harmer
7.706
970657AG2-426 GEN
Solar/Wind Harmer
1.611
316431W1029_GEN1
Solar/Wind Harmer
4.466
316433W1029_GEN2
Solar/Wind Harmer
4.466
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.024
3146626S HERTFORD
Solar/Wind Harmer
-0.024
315742AE1-103 GEN
Solar/Wind Harmer
2.557
3146376EDENTON
Solar/Wind Harmer
0.721
3146376EDENTON
Solar/Wind Harmer
0.721
316181AB2-040 GEN
Solar/Wind Harmer
3.381
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3145893MURPHYS
Solar/Wind Harmer
0.667
3145893MURPHYS
Solar/Wind Harmer
-0.043
3145593CAROLNA
Solar/Wind Harmer
-0.024
3145593CAROLNA
Solar/Wind Harmer
-0.024
966811AG1-552 GEN
Solar/Wind Harmer
2.675
3145593CAROLNA
Solar/Wind Harmer
0.198
3146173TUNIS
Solar/Wind Harmer
-0.024
3146173TUNIS
Solar/Wind Harmer
-0.024
316065AD1-022 GEN
Solar/Wind Harmer
11.875
316426AA2-053 GEN
Solar/Wind Harmer
2.399
316236AE1-162_GEN
Solar/Wind Harmer
0.715
3145796HORNRTN
Solar/Wind Harmer
-0.071
971741AH1-377 GEN
Solar/Wind Harmer
27.515
3145783HORNRTN
Solar/Wind Harmer
2.805
3145783HORNRTN
Solar/Wind Harmer
2.244
3145783HORNRTN
Solar/Wind Harmer
0.701
3145783HORNRTN
Solar/Wind Harmer
0.281
939181AE1-148 GEN
Solar/Wind Harmer
13.009
970301AG2-198 GEN
Solar/Wind Harmer
11.463
316274AC1-208 GEN
Solar/Wind Harmer
2.472
313527AB2-043 GEN
Solar/Wind Harmer
3.699
316240AF1-291 C
Solar/Wind Harmer
0.679
3145933PARMELE
Solar/Wind Harmer
-0.045
3145933PARMELE
Solar/Wind Harmer
-0.022
316033AB2-134 GEN
Solar/Wind Harmer
7.172
315697AD1-025 GEN
Solar/Wind Harmer
4.498
970323AG2-213 GEN
Solar/Wind Harmer
11.1
971775AH1-396 GEN
Solar/Wind Harmer
1.581
316034AC1-036 C
Solar/Wind Harmer
0.412
944641AF1-129 GEN
Adder
93.824
962561AG1-105 GEN
Solar/Wind Harmer
12.386
3145493TOT1
Solar/Wind Harmer
0.34
3145453TOT5
Solar/Wind Harmer
0.204
3145603CNETO
Solar/Wind Harmer
0.136
3144293JTRSVLE
Adder
0.615
3144293JTRSVLE
Adder
0.518
3142366NRTHEST
Adder
0.505
3150691DARBY 3
Adder
10.955
3150701DARBY 4
Adder
10.93
3150681DARBY 2
Adder
10.917
3150671DARBY 1
Adder
10.904
3142296MT RD221
Adder
0.39
3150341NORNECKC1
Adder
1.211
3150341NORNECKC1
Adder
1.201
316447AC1-158 HLD
Solar/Wind Helper
3.579
3151031BRUNSWICKG2
50/50
3.586
970413AG2-270 GEN
50/50
21.547
3151101ELIZAR3
50/50
21.88
970917AG2-570 GEN
Solar/Wind Harmer
73.368
316313AB2-026
Solar/Wind Harmer
0.722
316258AE1-075 C
Solar/Wind Harmer
0.65
316405AF2-144 C
Solar/Wind Harmer
0.686
3143336POWHATN
Solar/Wind Harmer
2.702
316478AD1-087 GEN
Solar/Wind Harmer
2.243
316486AD2-202 GEN
Solar/Wind Harmer
0.657
316365GEN2_N
Solar/Wind Harmer
1.702
944581AF1-123 GEN
Solar/Wind Harmer
114.775
944601AF1-125 GEN
Solar/Wind Harmer
112.984
315773AC2-141 GEN
Solar/Wind Harmer
10.519
3146456SLIGO L269
Solar/Wind Harmer
-0.025
971153AH1-033 GEN
Solar/Wind Harmer
3.039
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316320Y1-086
Solar/Wind Harmer
1.453
970661AG2-428 GEN
Solar/Wind Harmer
4.646
316435W1029_GEN3
Solar/Wind Harmer
4.466
316083AB2-161 GEN
Solar/Wind Harmer
4.001
966621AG1-532 GEN
Solar/Wind Harmer
0.5
970659AG2-427 GEN
Solar/Wind Harmer
2.32
3146516WINFALL
Solar/Wind Harmer
-0.025
315813AE1-149 C
Solar/Wind Harmer
15.377
3144536CHRHLND
Solar/Wind Harmer
-0.004
3145273HOLLAND
Solar/Wind Harmer
-0.018
3146626S HERTFORD
Solar/Wind Harmer
-0.024
3146376EDENTON
Solar/Wind Harmer
-0.024
313506AB2-031 GEN
Solar/Wind Harmer
1.948
3156081AA2-088 GEN
Solar/Wind Harmer
7.818
3147043LAWRENC
Solar/Wind Harmer
-0.014
315614AA2-178 GEN
Solar/Wind Harmer
2.593
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3145893MURPHYS
Solar/Wind Harmer
0.167
3145893MURPHYS
Solar/Wind Harmer
-0.024
315839AE2-212 C
Solar/Wind Harmer
0.72
957521AF2-046 GEN
Solar/Wind Harmer
18.794
961681AG1-008 GEN
Solar/Wind Harmer
18.794
971157AH1-035 GEN
Solar/Wind Harmer
2.979
315737AD1-076 GEN
Solar/Wind Harmer
4.523
3146173TUNIS
Solar/Wind Harmer
-0.024
3146206CASHIE
Solar/Wind Harmer
-0.024
3145336SMITFLD
Solar/Wind Harmer
-0.009
316463AE2-346 GEN
Solar/Wind Harmer
0.383
316140AB2-099
Solar/Wind Harmer
0.16
962331AG1-082 GEN
Solar/Wind Harmer
2.96
3145796HORNRTN
Solar/Wind Harmer
-0.094
3145796HORNRTN
Solar/Wind Harmer
-0.024
3150861SPRUNCD
Adder
0.97
3146263WOODLND
Solar/Wind Harmer
-0.024
3156021HOLLOMANSOL
Solar/Wind Harmer
3.182
316317KELFORD C
Solar/Wind Harmer
1.101
3145823KELFORD
Solar/Wind Harmer
-0.023
965281AG1-393 GEN
Solar/Wind Harmer
2.906
3145963POPLR C
Solar/Wind Harmer
-0.023
3151221GRAVEL6
Adder
14.86
3151171GRAVELC
Adder
2.859
316210AC1-098 GEN
Solar/Wind Harmer
3.599
970909AG2-566 GEN
Solar/Wind Harmer
2.177
316131AB2-060 GEN
Solar/Wind Harmer
2.453
961611AG1-000B GEN
Solar/Wind Harmer
4.776
315724AD1-057 GEN
Solar/Wind Harmer
1.302
964241AG1-285 GEN
Solar/Wind Harmer
17.632
3145933PARMELE
Solar/Wind Harmer
-0.022
966801AG1-551 GEN
Solar/Wind Harmer
2.814
316327AA2-057 GEN
Solar/Wind Harmer
2.261
315785AD2-033 C
Solar/Wind Harmer
5.054
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
970257AG2-171 GEN
Solar/Wind Harmer
8.325
959311AF2-222 GEN
Solar/Wind Harmer
23.096
3146233WITAKRS
Solar/Wind Harmer
0.462
3146233WITAKRS
Solar/Wind Harmer
-0.015
315778AD1-151 GEN
Solar/Wind Harmer
19.113
3138543CONSLDL
Solar/Wind Harmer
-0.014
3146073TAR RVR
Solar/Wind Harmer
-0.022
3146083TARBORO
Solar/Wind Harmer
-0.022
3144293JTRSVLE
Adder
0.615
3144216WINCHST
Adder
0.716
3150921YORKTN3
Adder
4.712
3143096IRON208
Adder
0.735
3143096IRON208
Adder
0.72
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
3141843SHACKLE
Adder
0.766
3150351NORNECKC2
Adder
1.172
316044AC1-158 PL1
Solar/Wind Helper
1.626
316450AC1-158 RIC
Solar/Wind Helper
0.434
3147666LOUISA
Solar/Wind Helper
0.562
315693AD1-088 GEN
Solar/Wind Harmer
13.081
962491AG1-098 GEN
Solar/Wind Harmer
17.384
316023GEN1_S
Solar/Wind Harmer
1.702
944591AF1-124 GEN
Solar/Wind Harmer
115.189
316294AC1-161 GEN
Solar/Wind Harmer
8.133
316388AE2-253 GEN
Solar/Wind Harmer
1.684
3146456SLIGO L269
Solar/Wind Harmer
-0.025
316375AC2-012 GEN
Solar/Wind Harmer
8.62
3150981CHESPKA
Adder
2.768
316246AF1-032 C
Solar/Wind Harmer
0.503
316336AC2-165 C
Solar/Wind Harmer
4.313
316093AE2-104_GEN
Solar/Wind Harmer
7.202
970661AG2-428 GEN
Solar/Wind Harmer
26.214
316381AD1-082 GEN
Solar/Wind Harmer
2.261
960081AF2-299 GEN
Solar/Wind Harmer
2.773
970659AG2-427 GEN
Solar/Wind Harmer
13.092
3146516WINFALL
Solar/Wind Harmer
-0.079
3146516WINFALL
Solar/Wind Harmer
-0.025
315800Z1-036_GEN1
Solar/Wind Harmer
6.037
3130156CHOWAN
Solar/Wind Harmer
-0.024
971795AH1-408 GEN
Solar/Wind Harmer
18.192
316072AD1-144
Solar/Wind Harmer
0.491
315687AD1-152 GEN
Solar/Wind Harmer
2.916
3147043LAWRENC
Adder
1.939
3145663CRESWEL
Solar/Wind Harmer
-0.067
971163AH1-040 GEN
Solar/Wind Harmer
22.53
316011AB1-132 GEN
Solar/Wind Harmer
5.02
962571AG1-106 GEN
Solar/Wind Harmer
3.449
3145893MURPHYS
Solar/Wind Harmer
-0.095
3145893MURPHYS
Solar/Wind Harmer
0.709
3146173TUNIS
Solar/Wind Harmer
-0.024
316190AA2-174 GEN
Solar/Wind Harmer
0.292
3146206CASHIE
Solar/Wind Harmer
-0.024
971547AH1-271 GEN
Solar/Wind Harmer
5.931
3145336SMITFLD
Solar/Wind Harmer
-0.094
3145796HORNRTN
Solar/Wind Harmer
-0.078
3145796HORNRTN
Solar/Wind Harmer
-0.024
3150851SPRUNCC
Adder
0.97
3146263WOODLND
Solar/Wind Harmer
-0.024
3145783HORNRTN
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
316129AC1-054 GEN
Solar/Wind Harmer
2.052
971065AG2-659 GEN
Solar/Wind Harmer
11.686
3145823KELFORD
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.023
316174AB2-169 GEN
Solar/Wind Harmer
3.546
3151171GRAVELC
Adder
2.174
316212AC1-099_GEN
Solar/Wind Harmer
2
315671AE2-027_GEN
Solar/Wind Harmer
17.142
316237AB2-079_GEN
Solar/Wind Harmer
0.685
961611AG1-000B GEN
Solar/Wind Harmer
11.194
315722AD1-056 GEN
Solar/Wind Harmer
2.367
3146293MARTNCO
Solar/Wind Harmer
0.139
971647AH1-324 GEN
Solar/Wind Harmer
11.229
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
316494AC1-189 GEN
Solar/Wind Harmer
2.377
3146233WITAKRS
Solar/Wind Harmer
-0.087
971069AG2-661 GEN
Solar/Wind Harmer
3.491
961671AG1-007 GEN
Solar/Wind Harmer
0.278
3146083TARBORO
Solar/Wind Harmer
-0.022
3145493TOT1
Solar/Wind Harmer
0.651
970685AG2-442 GEN
Solar/Wind Harmer
19.204
3144293JTRSVLE
Adder
0.615
3143096IRON208
Adder
0.735
944631AF1-128 GEN
Adder
81.311
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
3141843SHACKLE
Adder
0.766
3150351NORNECKC2
Adder
1.153
316045AC1-158 PL2
Solar/Wind Helper
5.205
3147666LOUISA
Solar/Wind Helper
0.977
316192AB2-158 GEN
Solar/Wind Helper
1.608
LAGNLTFEXP_LAGN->PJM
CLTF
9.063
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.182
TVALTFEXP_TVA->PJM
CLTF
4.543
CPLELTFEXP_CPLE->PJM
CLTF
13.025
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.637
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.006
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.545
MECLTFEXP_MEC->PJM
CLTF
4.353
SIGELTFEXP_SIGE->PJM
CLTF
0.131
NYPJM->LTFIMP_NY
CLTF
2.393
LGEELTFEXP_LGEE->PJM
CLTF
1.582
WECLTFEXP_WEC->PJM
CLTF
0.806

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.34 %
Rating:3193.18 MVA
Rating Type:A
MVA to Mitigate:3619.13
MW Contribution:10.89
Bus #Bus NameTypeMW Contribution
970533AG2-339 GEN
50/50
25.341
970531AG2-338 GEN
50/50
10.136
315242AE2-183_GT2
50/50
4.563
315241AE2-183_GT1
50/50
4.535
972185AH1-677 GEN
50/50
16.45
3151041BRUNSWICKG3
50/50
3.586
972187AH1-678 GEN
50/50
8.23
971223AH1-071 GEN
Solar/Wind Harmer
3.255
970933AG2-581 GEN
Solar/Wind Harmer
21.207
3143526WINTERP
Solar/Wind Harmer
1.35
3144356SAPONY
Solar/Wind Harmer
2.053
970099AG2-077 GEN
Solar/Wind Harmer
25.81
316185AD1-033 GEN
Solar/Wind Harmer
0.006
3145506HICKORY
Solar/Wind Harmer
0.89
3145506HICKORY
Solar/Wind Harmer
0.534
3145506HICKORY
Solar/Wind Harmer
0.134
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.213
316339AD2-160 GEN
Solar/Wind Harmer
0.36
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
316017AA1-139 ULT1
Solar/Wind Harmer
0.124
3137176SLIGO L2192
Solar/Wind Harmer
0.883
3146456SLIGO L269
Solar/Wind Harmer
3.926
316036AC1-147 C
Solar/Wind Harmer
0.041
3130086AYDLETT
Solar/Wind Harmer
0.886
3151031BRUNSWICKG2
50/50
3.586
970413AG2-270 GEN
50/50
21.547
3151101ELIZAR3
50/50
21.88
970917AG2-570 GEN
Solar/Wind Harmer
23.218
316313AB2-026
Solar/Wind Harmer
0.15
316258AE1-075 C
Solar/Wind Harmer
0.18
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.602
316478AD1-087 GEN
Solar/Wind Harmer
0.805
316486AD2-202 GEN
Solar/Wind Harmer
0.236
316365GEN2_N
Solar/Wind Harmer
0.504
944581AF1-123 GEN
Solar/Wind Harmer
50.561
944601AF1-125 GEN
Solar/Wind Harmer
49.783
315773AC2-141 GEN
Solar/Wind Harmer
8.172
3146456SLIGO L269
Solar/Wind Harmer
0.222
971153AH1-033 GEN
Solar/Wind Harmer
2.565
3144873MCLAUGH
Solar/Wind Harmer
0.006
316320Y1-086
Solar/Wind Harmer
0.001
970661AG2-428 GEN
Solar/Wind Harmer
4.646
316435W1029_GEN3
Solar/Wind Harmer
0.001
316083AB2-161 GEN
Solar/Wind Harmer
0.003
970659AG2-427 GEN
Solar/Wind Harmer
2.32
3146516WINFALL
Solar/Wind Harmer
0.219
315813AE1-149 C
Solar/Wind Harmer
11.679
3144536CHRHLND
Solar/Wind Harmer
0.033
3145273HOLLAND
Solar/Wind Harmer
0.164
3146626S HERTFORD
Solar/Wind Harmer
0.218
3146376EDENTON
Solar/Wind Harmer
0.216
313506AB2-031 GEN
Solar/Wind Harmer
0.667
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
3147043LAWRENC
Solar/Wind Harmer
0.129
315614AA2-178 GEN
Solar/Wind Harmer
1.224
970119AG2-088 GEN
50/50
40.684
315243AE2-183_GT3
50/50
4.563
3151051BRUNSWICKS1
50/50
7.443
3151021BRUNSWICKG1
50/50
3.586
971451AH1-221 GEN
50/50
10.893
3151531CLOVER1
50/50
4.938
3143226MDLTHAN
Solar/Wind Harmer
0.305
940641AE2-051 GEN
Solar/Wind Harmer
22.672
939411AE1-173 GEN
Solar/Wind Harmer
114.479
970919AG2-571 GEN
Solar/Wind Harmer
9.287
970087AG2-069 GEN
Solar/Wind Harmer
20.797
3143526WINTERP
Solar/Wind Harmer
1.35
957481AF2-042 GEN
Solar/Wind Harmer
64.526
3143336POWHATN
Solar/Wind Harmer
4.238
315693AD1-088 GEN
Solar/Wind Harmer
11.177
962491AG1-098 GEN
Solar/Wind Harmer
13.203
316023GEN1_S
Solar/Wind Harmer
0.504
944591AF1-124 GEN
Solar/Wind Harmer
50.741
316294AC1-161 GEN
Solar/Wind Harmer
3.877
316388AE2-253 GEN
Solar/Wind Harmer
0.696
3146456SLIGO L269
Solar/Wind Harmer
0.222
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
2.768
316246AF1-032 C
Solar/Wind Harmer
0.1
316336AC2-165 C
Solar/Wind Harmer
0.009
316093AE2-104_GEN
Solar/Wind Harmer
3.708
970661AG2-428 GEN
Solar/Wind Harmer
21.842
316381AD1-082 GEN
Solar/Wind Harmer
0.229
960081AF2-299 GEN
Solar/Wind Harmer
2.106
970659AG2-427 GEN
Solar/Wind Harmer
10.606
3146516WINFALL
Solar/Wind Harmer
0.71
3146516WINFALL
Solar/Wind Harmer
0.219
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.216
971795AH1-408 GEN
Solar/Wind Harmer
14.392
316072AD1-144
Solar/Wind Harmer
0.078
315687AD1-152 GEN
Solar/Wind Harmer
0.007
3147043LAWRENC
Adder
1.939
3145663CRESWEL
Solar/Wind Harmer
0.599
971163AH1-040 GEN
Solar/Wind Harmer
17.112
316011AB1-132 GEN
Solar/Wind Harmer
3.881
962571AG1-106 GEN
Solar/Wind Harmer
3.037
3145893MURPHYS
Solar/Wind Harmer
0.851
3145893MURPHYS
Solar/Wind Harmer
0.946
3146173TUNIS
Solar/Wind Harmer
0.211
316190AA2-174 GEN
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
0.211
971547AH1-271 GEN
Solar/Wind Harmer
4.504
3145336SMITFLD
Solar/Wind Harmer
0.844
3145796HORNRTN
Solar/Wind Harmer
0.695
3145796HORNRTN
Solar/Wind Harmer
0.211
3150851SPRUNCC
Adder
0.97
3146263WOODLND
Solar/Wind Harmer
0.21
3145783HORNRTN
Solar/Wind Harmer
0.21
3145683EARLEYS
Solar/Wind Harmer
0.21
316129AC1-054 GEN
Solar/Wind Harmer
0.783
971065AG2-659 GEN
Solar/Wind Harmer
8.875
3145823KELFORD
Solar/Wind Harmer
0.208
3145963POPLR C
Solar/Wind Harmer
0.206
316174AB2-169 GEN
Solar/Wind Harmer
0.005
3151171GRAVELC
Adder
2.174
316212AC1-099_GEN
Solar/Wind Harmer
1.056
315671AE2-027_GEN
Solar/Wind Harmer
13.019
316237AB2-079_GEN
Solar/Wind Harmer
0.002
961611AG1-000B GEN
Solar/Wind Harmer
10.587
315722AD1-056 GEN
Solar/Wind Harmer
1.275
3146293MARTNCO
Solar/Wind Harmer
0.186
971647AH1-324 GEN
Solar/Wind Harmer
8.529
3145746EVERETS
Solar/Wind Harmer
0.198
3145746EVERETS
Solar/Wind Harmer
0.198
316494AC1-189 GEN
Solar/Wind Harmer
0.664
3146233WITAKRS
Solar/Wind Harmer
0.782
971069AG2-661 GEN
Solar/Wind Harmer
3.491
961671AG1-007 GEN
Solar/Wind Harmer
0.03
3146083TARBORO
Solar/Wind Harmer
0.195
3145493TOT1
Solar/Wind Harmer
0.868
970685AG2-442 GEN
Solar/Wind Harmer
14.585
970401AG2-262 GEN
Solar/Wind Harmer
1.143
316458AB2-190 GEN2
Solar/Wind Harmer
1.041
316359AB2-059 GEN
Solar/Wind Harmer
0.696
316049AB1-081 GEN
Solar/Wind Harmer
1.109
3145543BTLEBRO
Solar/Wind Harmer
0.194
3145543BTLEBRO
Solar/Wind Harmer
0.155
3142053HEARTS
Solar/Wind Harmer
0.341
970129AG2-093 GEN
Solar/Wind Harmer
5.511
963171AG1-166 GEN
Solar/Wind Harmer
1.03
971563AH1-280 GEN
Solar/Wind Harmer
2.061
3144293JTRSVLE
Adder
0.615
3138126ROCKLANDING
Solar/Wind Harmer
0.087
316303AF2-085
50/50
5.424
315244AE2-183_ST
50/50
7.889
963041AG1-153 GEN
50/50
7.262
315779AE2-040
50/50
3.426
3151541CLOVER2
50/50
4.914
941031AE2-094 GEN
Solar/Wind Harmer
52.507
944011AF1-069 GEN
Solar/Wind Harmer
17.156
970673AG2-436 GEN
Solar/Wind Harmer
59.565
970673AG2-436 GEN
Solar/Wind Harmer
39.71
971967AH1-528 GEN
Solar/Wind Harmer
43.86
970085AG2-068 GEN
Solar/Wind Harmer
13.865
970581AG2-369 GEN
Solar/Wind Harmer
11.924
316233AE1-074 FULL
Solar/Wind Harmer
0.208
971281AH1-106 GEN
Solar/Wind Harmer
3.602
971283AH1-107 GEN
Solar/Wind Harmer
3.602
316315AB2-025 C
Solar/Wind Harmer
0.198
315814AE2-033 C
Solar/Wind Harmer
19.336
3143316POE
Solar/Wind Harmer
0.915
957871AF2-081 GEN
Solar/Wind Harmer
11.058
3151081ELIZAR1
Adder
20.359
3151091ELIZAR2
Adder
20.005
319010AE1-072 C
Solar/Wind Harmer
1.117
3146406KITTY HAWK
Solar/Wind Harmer
0.028
3152611GOSPORTB
Adder
2.823
3152621GOSPORTC
Adder
2.396
3152601GOSPORTA
Adder
2.21
316305AF2-043 C
Solar/Wind Harmer
0.002
313526AB2-022
Solar/Wind Harmer
0.119
315835AF2-110_GEN
Solar/Wind Harmer
1.513
316321Z2-027
Solar/Wind Harmer
0.041
3146396TANGLEW
Solar/Wind Harmer
0.607
3145176PASQUOTANK
Solar/Wind Harmer
0.136
3146486SUNBURY
Solar/Wind Harmer
0.22
3146486SUNBURY
Solar/Wind Harmer
0.22
316311AC2-079 GEN
Solar/Wind Harmer
6.318
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.151
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
316087AB2-174 GEN
Solar/Wind Harmer
0.006
3130156CHOWAN
Solar/Wind Harmer
0.216
3130156CHOWAN
Solar/Wind Harmer
0.216
965291AG1-394 GEN
Solar/Wind Harmer
0.951
315816AE2-034 GEN
Solar/Wind Harmer
0.918
315652AC1-086 GEN
Solar/Wind Harmer
23.483
3137643SOCKMAN
Solar/Wind Harmer
0.852
3145893MURPHYS
Solar/Wind Harmer
0.574
3145893MURPHYS
Solar/Wind Harmer
0.213
3146043SEABORD
Solar/Wind Harmer
0.213
315607AA1-063A GEN
Solar/Wind Harmer
0.434
3130546PLYMOUTH
Solar/Wind Harmer
0.212
315732AD1-074 GEN1
Solar/Wind Harmer
1.217
315733AD1-074 GEN2
Solar/Wind Harmer
1.217
315735AD1-075 GEN1
Solar/Wind Harmer
0.609
3146206CASHIE
Solar/Wind Harmer
0.211
970601AG2-382 GEN
Solar/Wind Harmer
7.883
3145513AHOSKIE
Solar/Wind Harmer
0.441
3145513AHOSKIE
Solar/Wind Harmer
0.211
3145796HORNRTN
Solar/Wind Harmer
0.674
3145796HORNRTN
Solar/Wind Harmer
0.084
971285AH1-108 GEN
Adder
1.587
971445AH1-216 GEN
Solar/Wind Harmer
14.817
3145683EARLEYS
Solar/Wind Harmer
0.42
3145683EARLEYS
Solar/Wind Harmer
0.21
3145683EARLEYS
Solar/Wind Harmer
0.21
970831AG2-522 GEN
Solar/Wind Harmer
8.902
3146033SCOT NK
Solar/Wind Harmer
0.823
972265AH1-717 GEN
Adder
15.87
3151201GRAVEL4
Adder
14.877
3151191GRAVEL3
Adder
14.689
3151211GRAVEL5
Adder
14.689
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316005AA1-067
Solar/Wind Harmer
0.212
3145746EVERETS
Solar/Wind Harmer
0.788
3145746EVERETS
Solar/Wind Harmer
0.198
3145746EVERETS
Solar/Wind Harmer
0.198
3145746EVERETS
Solar/Wind Harmer
0.198
970181AG2-120 GEN
Solar/Wind Harmer
2.464
316369SG1_INVT
Solar/Wind Harmer
0.007
971443AH1-215 GEN
Solar/Wind Harmer
3.323
3144303KENBRDG
Solar/Wind Harmer
0.158
957861AF2-080 GEN
Solar/Wind Harmer
8.475
316319Z2-044 C
Solar/Wind Harmer
0
316420AA1-050 GEN
Solar/Wind Harmer
0.006
3145573BETHELC
Solar/Wind Harmer
0.195
3145573BETHELC
Solar/Wind Harmer
0.195
970683AG2-441 GEN
Solar/Wind Harmer
13.022
970681AG2-440 GEN
Solar/Wind Harmer
10.418
316132AB2-190 GEN1
Solar/Wind Harmer
1.041
946301AF1-294 GEN
Solar/Wind Harmer
3.812
961791AG1-021 GEN
Solar/Wind Harmer
1.855
316118AC1-105 GEN
Solar/Wind Harmer
0.495
315657AE1-056 GEN
Solar/Wind Harmer
6.612
3147173SINAI
Solar/Wind Harmer
0.189
3147243WELCO
Solar/Wind Harmer
0.118
3138283WHITEMARSH
Solar/Wind Harmer
0.039
970285AG2-188 GEN
Solar/Wind Harmer
13.256
971845AH1-439 GEN
Solar/Wind Harmer
7.448
970865AG2-541 GEN
Solar/Wind Harmer
5.665
971167AH1-042 GEN
Solar/Wind Harmer
14.133
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
3143873LANEXA
Solar/Wind Harmer
0.09
970189AG2-124 GEN
Solar/Wind Harmer
4.44
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.03
316059AD1-063 C
Solar/Wind Harmer
0.001
316123AC1-075 GEN
Solar/Wind Harmer
0.2
970165AG2-112 GEN
Solar/Wind Harmer
1.187
970163AG2-111 GEN
Solar/Wind Harmer
1.132
316314AB2-024 C
Solar/Wind Harmer
0.001
315976AC1-164 GENA
Solar/Wind Harmer
15.083
316169AC1-164_GENC
Solar/Wind Harmer
13.031
315975AC1-164 GENB
Solar/Wind Harmer
0.446
3141913WHIT STONE
Solar/Wind Harmer
0.144
3138133OCRAN
Solar/Wind Harmer
0.043
3141783LANCAST
Solar/Wind Harmer
0.084
3141783LANCAST
Solar/Wind Harmer
0.056
3142543TWELFTH
Solar/Wind Harmer
0.018
3146926FARMVIL
Solar/Wind Harmer
0.11
316003AC1-222 GEN
Solar/Wind Harmer
0.005
971317AH1-138 GEN
Solar/Wind Harmer
1.337
970937AG2-583 GEN
Solar/Wind Harmer
10.797
3143096IRON208
Adder
0.735
316159AE1-175 C
Solar/Wind Harmer
0.149
944631AF1-128 GEN
Adder
81.311
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.065
3142433PROV 92
Solar/Wind Harmer
0.629
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
971777AH1-397 GEN
Solar/Wind Harmer
0.396
3141843SHACKLE
Adder
0.766
3141766HARMONY
Solar/Wind Harmer
0.029
3138133OCRAN
Solar/Wind Harmer
0.086
972003AH1-546 GEN
Solar/Wind Harmer
6.056
3142416OLDCHRC
Solar/Wind Harmer
0.332
3142416OLDCHRC
Solar/Wind Harmer
0.127
962861AG1-135 GEN
Solar/Wind Harmer
4.063
971377AH1-170 GEN
Solar/Wind Harmer
1.327
3147623JAMES R
Solar/Wind Harmer
0.288
3141726DUNNSVL
Solar/Wind Harmer
0.474
3150351NORNECKC2
Adder
1.153
970223AG2-152 GEN
Solar/Wind Harmer
7.902
316045AC1-158 PL2
Solar/Wind Helper
5.205
3147666LOUISA
Solar/Wind Helper
0.977
316192AB2-158 GEN
Solar/Wind Helper
1.608
3150991CHESPKB
Adder
2.322
3150991CHESPKB
Adder
2.266
3146386ELIZ CT
Solar/Wind Harmer
0.22
970657AG2-426 GEN
Solar/Wind Harmer
7.686
970657AG2-426 GEN
Solar/Wind Harmer
1.611
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.219
3146516WINFALL
Solar/Wind Harmer
0.219
3146516WINFALL
Solar/Wind Harmer
0.219
3146626S HERTFORD
Solar/Wind Harmer
0.218
3146626S HERTFORD
Solar/Wind Harmer
0.218
315742AE1-103 GEN
Solar/Wind Harmer
0.003
3146376EDENTON
Solar/Wind Harmer
0.961
3146376EDENTON
Solar/Wind Harmer
0.961
316181AB2-040 GEN
Solar/Wind Harmer
0.313
3142666NORTHAMPTON
Solar/Wind Harmer
0.213
3142666NORTHAMPTON
Solar/Wind Harmer
0.213
3142666NORTHAMPTON
Solar/Wind Harmer
0.213
3142666NORTHAMPTON
Solar/Wind Harmer
0.128
3145893MURPHYS
Solar/Wind Harmer
1.424
3145893MURPHYS
Solar/Wind Harmer
0.383
3145593CAROLNA
Solar/Wind Harmer
0.211
3145593CAROLNA
Solar/Wind Harmer
0.211
966811AG1-552 GEN
Solar/Wind Harmer
2.295
3145593CAROLNA
Solar/Wind Harmer
0.263
3146173TUNIS
Solar/Wind Harmer
0.211
3146173TUNIS
Solar/Wind Harmer
0.211
316065AD1-022 GEN
Solar/Wind Harmer
9.733
316426AA2-053 GEN
Solar/Wind Harmer
0.714
316236AE1-162_GEN
Solar/Wind Harmer
0.002
3145796HORNRTN
Solar/Wind Harmer
0.632
971741AH1-377 GEN
Solar/Wind Harmer
20.897
3145783HORNRTN
Solar/Wind Harmer
3.74
3145783HORNRTN
Solar/Wind Harmer
2.992
3145783HORNRTN
Solar/Wind Harmer
0.935
3145783HORNRTN
Solar/Wind Harmer
0.374
939181AE1-148 GEN
Solar/Wind Harmer
9.88
970301AG2-198 GEN
Solar/Wind Harmer
8.706
316274AC1-208 GEN
Solar/Wind Harmer
1.058
313527AB2-043 GEN
Solar/Wind Harmer
0.003
316240AF1-291 C
Solar/Wind Harmer
0.002
3145933PARMELE
Solar/Wind Harmer
0.401
3145933PARMELE
Solar/Wind Harmer
0.2
316033AB2-134 GEN
Solar/Wind Harmer
0.012
315697AD1-025 GEN
Solar/Wind Harmer
0.223
970323AG2-213 GEN
Solar/Wind Harmer
8.431
971775AH1-396 GEN
Solar/Wind Harmer
0.316
316034AC1-036 C
Solar/Wind Harmer
0.014
944641AF1-129 GEN
Adder
93.824
962561AG1-105 GEN
Solar/Wind Harmer
9.407
3145493TOT1
Solar/Wind Harmer
0.453
3145453TOT5
Solar/Wind Harmer
0.272
3145603CNETO
Solar/Wind Harmer
0.181
964791AG1-342 GEN
Solar/Wind Harmer
3.74
3146843MT LREL
Solar/Wind Harmer
0.195
3146843MT LREL
Solar/Wind Harmer
0.195
961601AG1-000A GEN
Solar/Wind Harmer
3.447
316263AC1-034 GEN
Solar/Wind Harmer
7.365
958211AF2-115 GEN
Solar/Wind Harmer
2.318
963191AG1-168 GEN
Solar/Wind Harmer
0.773
3144293JTRSVLE
Adder
0.615
3144293JTRSVLE
Adder
0.518
3147133PAMPLIN
Solar/Wind Harmer
0.192
3147133PAMPLIN
Solar/Wind Harmer
0.153
316222AC1-221 GEN
Solar/Wind Harmer
0.714
3142946ENON
Solar/Wind Harmer
0.016
3146776BUCKING
Solar/Wind Harmer
0.65
3146776BUCKING
Solar/Wind Harmer
0.053
3142366NRTHEST
Adder
0.505
3150691DARBY 3
Adder
10.955
3150701DARBY 4
Adder
10.93
3150681DARBY 2
Adder
10.917
3150671DARBY 1
Adder
10.904
316075AC2-137 C
Solar/Wind Harmer
0.04
942751AE2-291 GEN
Solar/Wind Harmer
7.378
958261AF2-120 GEN
Solar/Wind Harmer
4.15
971489AH1-241 GEN
Solar/Wind Harmer
6.633
3142296MT RD221
Adder
0.39
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
1.211
3150341NORNECKC1
Adder
1.201
966871AG1-558 GEN
Solar/Wind Harmer
0.131
316447AC1-158 HLD
Solar/Wind Helper
3.579
3142666NORTHAMPTON
Solar/Wind Harmer
0.213
3145893MURPHYS
Solar/Wind Harmer
0.356
3145893MURPHYS
Solar/Wind Harmer
0.213
315839AE2-212 C
Solar/Wind Harmer
0.002
957521AF2-046 GEN
Solar/Wind Harmer
15.803
961681AG1-008 GEN
Solar/Wind Harmer
15.803
971157AH1-035 GEN
Solar/Wind Harmer
2.546
315737AD1-076 GEN
Solar/Wind Harmer
2.725
3146173TUNIS
Solar/Wind Harmer
0.211
3146206CASHIE
Solar/Wind Harmer
0.211
3145336SMITFLD
Solar/Wind Harmer
0.084
316463AE2-346 GEN
Solar/Wind Harmer
0.181
316140AB2-099
Solar/Wind Harmer
0.075
962331AG1-082 GEN
Solar/Wind Harmer
2.248
3145796HORNRTN
Solar/Wind Harmer
0.842
3145796HORNRTN
Solar/Wind Harmer
0.211
3150861SPRUNCD
Adder
0.97
3146263WOODLND
Solar/Wind Harmer
0.21
3156021HOLLOMANSOL
Solar/Wind Harmer
0.954
316317KELFORD C
Solar/Wind Harmer
0.02
3145823KELFORD
Solar/Wind Harmer
0.208
965281AG1-393 GEN
Solar/Wind Harmer
2.207
3145963POPLR C
Solar/Wind Harmer
0.206
3151221GRAVEL6
Adder
14.86
3151171GRAVELC
Adder
2.859
316210AC1-098 GEN
Solar/Wind Harmer
1.894
970909AG2-566 GEN
Solar/Wind Harmer
2.177
316131AB2-060 GEN
Solar/Wind Harmer
0.636
961611AG1-000B GEN
Solar/Wind Harmer
5.383
315724AD1-057 GEN
Solar/Wind Harmer
0.756
964241AG1-285 GEN
Solar/Wind Harmer
13.392
3145933PARMELE
Solar/Wind Harmer
0.2
966801AG1-551 GEN
Solar/Wind Harmer
2.335
316327AA2-057 GEN
Solar/Wind Harmer
0.301
315785AD2-033 C
Solar/Wind Harmer
1.614
3145746EVERETS
Solar/Wind Harmer
0.198
3145746EVERETS
Solar/Wind Harmer
0.198
970257AG2-171 GEN
Solar/Wind Harmer
6.323
959311AF2-222 GEN
Solar/Wind Harmer
17.507
3146233WITAKRS
Solar/Wind Harmer
0.986
3146233WITAKRS
Solar/Wind Harmer
0.134
315778AD1-151 GEN
Solar/Wind Harmer
15.709
3138543CONSLDL
Solar/Wind Harmer
0.129
3146073TAR RVR
Solar/Wind Harmer
0.195
3146083TARBORO
Solar/Wind Harmer
0.195
961601AG1-000A GEN
Solar/Wind Harmer
13.786
3145543BTLEBRO
Solar/Wind Harmer
0.194
3145543BTLEBRO
Solar/Wind Harmer
0.194
971623AH1-311 GEN
Solar/Wind Harmer
0.388
970129AG2-093 GEN
Solar/Wind Harmer
11.71
963181AG1-167 GEN
Solar/Wind Harmer
0.773
3144293JTRSVLE
Adder
0.615
3147133PAMPLIN
Solar/Wind Harmer
0.602
971193AH1-056 GEN
Solar/Wind Harmer
11.673
970133AG2-095 GEN
Solar/Wind Harmer
1.824
3144216WINCHST
Adder
0.716
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
8.068
3150921YORKTN3
Adder
4.712
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.11
3143096IRON208
Adder
0.735
3143096IRON208
Adder
0.72
316382AG1-145 C
Solar/Wind Harmer
0.001
971683AH1-343 GEN
Solar/Wind Harmer
6.321
316283AC2-100 C
Solar/Wind Harmer
0.335
3142946ENON
Solar/Wind Harmer
0.055
3146776BUCKING
Solar/Wind Harmer
0.059
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
3141843SHACKLE
Adder
0.766
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316280AD1-041 GEN
Solar/Wind Harmer
0.003
316156AD2-030 GEN
Solar/Wind Harmer
0.111
3141873WAN 176
Solar/Wind Harmer
2.658
970293AG2-193 GEN
Solar/Wind Harmer
1.582
3141766HARMONY
Solar/Wind Harmer
1.964
962971AG1-146 GEN
Solar/Wind Harmer
2.151
970009AG2-005 GEN
Solar/Wind Harmer
0.978
3142416OLDCHRC
Solar/Wind Harmer
1.237
316404AE1-155 C
Solar/Wind Harmer
0.028
970221AG2-151 GEN
Solar/Wind Harmer
6.633
3150351NORNECKC2
Adder
1.172
316473AC1-191 GEN
Solar/Wind Harmer
0.383
316044AC1-158 PL1
Solar/Wind Helper
1.626
316450AC1-158 RIC
Solar/Wind Helper
0.434
972205AH1-687 GEN
Adder
5.897
962981AG1-147 GEN
Solar/Wind Harmer
5.019
970327AG2-215 GEN
Solar/Wind Harmer
4.3
316312AB1-027
Solar/Wind Harmer
0.228
971447AH1-217 GEN
Solar/Wind Harmer
3.55
3141813NORNECK
Solar/Wind Harmer
0.116
3147666LOUISA
Solar/Wind Helper
0.562
LAGNLTFEXP_LAGN->PJM
CLTF
9.063
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.182
TVALTFEXP_TVA->PJM
CLTF
4.543
CPLELTFEXP_CPLE->PJM
CLTF
13.025
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.637
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.006
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.545
MECLTFEXP_MEC->PJM
CLTF
4.353
SIGELTFEXP_SIGE->PJM
CLTF
0.131
NYPJM->LTFIMP_NY
CLTF
2.393
LGEELTFEXP_LGEE->PJM
CLTF
1.582
WECLTFEXP_WEC->PJM
CLTF
0.806

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2090-256_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2090-256_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.73 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4126.18
MW Contribution:11.16
Bus #Bus NameTypeMW Contribution
970533AG2-339 GEN
50/50
25.956
970531AG2-338 GEN
50/50
10.382
316303AF2-085
50/50
5.624
315244AE2-183_ST
50/50
8.082
963041AG1-153 GEN
50/50
7.44
315779AE2-040
50/50
3.552
3151541CLOVER2
50/50
5.042
941031AE2-094 GEN
Solar/Wind Harmer
61.515
944011AF1-069 GEN
Solar/Wind Harmer
19.275
970673AG2-436 GEN
Solar/Wind Harmer
67.512
970673AG2-436 GEN
Solar/Wind Harmer
34.183
971967AH1-528 GEN
Solar/Wind Harmer
59.326
316233AE1-074 FULL
Solar/Wind Harmer
0.825
971281AH1-106 GEN
Solar/Wind Harmer
4.985
971283AH1-107 GEN
Solar/Wind Harmer
4.985
970085AG2-068 GEN
Solar/Wind Harmer
18.707
970581AG2-369 GEN
Solar/Wind Harmer
16.088
316315AB2-025 C
Solar/Wind Harmer
0.771
970119AG2-088 GEN
50/50
42.178
315243AE2-183_GT3
50/50
4.674
3151051BRUNSWICKS1
50/50
7.626
3151021BRUNSWICKG1
50/50
3.674
3151031BRUNSWICKG2
50/50
3.674
970413AG2-270 GEN
50/50
22.109
3151101ELIZAR3
50/50
22.735
970917AG2-570 GEN
Solar/Wind Harmer
75.183
316313AB2-026
Solar/Wind Harmer
0.749
316258AE1-075 C
Solar/Wind Harmer
0.674
316405AF2-144 C
Solar/Wind Harmer
0.711
3143336POWHATN
Solar/Wind Harmer
2.8
316478AD1-087 GEN
Solar/Wind Harmer
2.301
316486AD2-202 GEN
Solar/Wind Harmer
0.674
944581AF1-123 GEN
Solar/Wind Harmer
119.099
944601AF1-125 GEN
Solar/Wind Harmer
117.241
316365GEN2_N
Solar/Wind Harmer
1.762
315773AC2-141 GEN
Solar/Wind Harmer
10.906
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146456SLIGO L269
Solar/Wind Harmer
-0.026
971153AH1-033 GEN
Solar/Wind Harmer
3.155
315813AE1-149 C
Solar/Wind Harmer
16.172
970659AG2-427 GEN
Solar/Wind Harmer
2.433
316083AB2-161 GEN
Solar/Wind Harmer
4.194
970661AG2-428 GEN
Solar/Wind Harmer
4.863
316320Y1-086
Solar/Wind Harmer
1.508
3144536CHRHLND
Solar/Wind Harmer
-0.004
316435W1029_GEN3
Solar/Wind Harmer
4.635
3146516WINFALL
Solar/Wind Harmer
-0.025
3145273HOLLAND
Solar/Wind Harmer
-0.019
966621AG1-532 GEN
Solar/Wind Harmer
0.517
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3150861SPRUNCD
Adder
1.039
315839AE2-212 C
Solar/Wind Harmer
0.764
3146376EDENTON
Solar/Wind Harmer
-0.025
313506AB2-031 GEN
Solar/Wind Harmer
2.014
3156081AA2-088 GEN
Solar/Wind Harmer
8.101
315614AA2-178 GEN
Solar/Wind Harmer
2.688
3147043LAWRENC
Solar/Wind Harmer
-0.015
3145336SMITFLD
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
0.173
315242AE2-183_GT2
50/50
4.674
315241AE2-183_GT1
50/50
4.646
972185AH1-677 GEN
50/50
16.852
3151041BRUNSWICKG3
50/50
3.674
972187AH1-678 GEN
50/50
8.432
971223AH1-071 GEN
Solar/Wind Harmer
4.443
3143526WINTERP
Solar/Wind Harmer
-0.159
970933AG2-581 GEN
Solar/Wind Harmer
28.617
3144356SAPONY
Solar/Wind Harmer
0.997
970099AG2-077 GEN
Solar/Wind Harmer
34.857
316185AD1-033 GEN
Solar/Wind Harmer
2.743
3145506HICKORY
Solar/Wind Harmer
-0.103
3145506HICKORY
Solar/Wind Harmer
-0.062
3145506HICKORY
Solar/Wind Harmer
-0.015
3142956BIRDNECK
Solar/Wind Harmer
1.392
316316AC1-027 C
Solar/Wind Harmer
0.796
316339AD2-160 GEN
Solar/Wind Harmer
1.749
316018AA1-139 ULT2
Solar/Wind Harmer
2.22
316017AA1-139 ULT1
Solar/Wind Harmer
2.097
316036AC1-147 C
Solar/Wind Harmer
0.698
3150991CHESPKB
Adder
2.413
3150991CHESPKB
Adder
2.355
3137176SLIGO L2192
Solar/Wind Harmer
-0.102
3146456SLIGO L269
Solar/Wind Harmer
3.057
3130086AYDLETT
Solar/Wind Harmer
-0.103
970657AG2-426 GEN
Solar/Wind Harmer
8.074
970657AG2-426 GEN
Solar/Wind Harmer
1.688
3146386ELIZ CT
Solar/Wind Harmer
-0.026
316431W1029_GEN1
Solar/Wind Harmer
4.635
316433W1029_GEN2
Solar/Wind Harmer
4.635
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
315742AE1-103 GEN
Solar/Wind Harmer
2.654
3146376EDENTON
Solar/Wind Harmer
0.747
3146376EDENTON
Solar/Wind Harmer
0.747
316181AB2-040 GEN
Solar/Wind Harmer
3.495
316236AE1-162_GEN
Solar/Wind Harmer
0.748
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.015
3145893MURPHYS
Solar/Wind Harmer
0.691
3145893MURPHYS
Solar/Wind Harmer
-0.044
316065AD1-022 GEN
Solar/Wind Harmer
12.302
3146173TUNIS
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.025
3145593CAROLNA
Solar/Wind Harmer
-0.024
3145593CAROLNA
Solar/Wind Harmer
-0.024
966811AG1-552 GEN
Solar/Wind Harmer
2.765
3145593CAROLNA
Solar/Wind Harmer
0.204
316426AA2-053 GEN
Solar/Wind Harmer
2.48
3145796HORNRTN
Solar/Wind Harmer
-0.073
3145783HORNRTN
Solar/Wind Harmer
2.899
3145783HORNRTN
Solar/Wind Harmer
2.32
3145783HORNRTN
Solar/Wind Harmer
0.725
3145783HORNRTN
Solar/Wind Harmer
0.29
971741AH1-377 GEN
Solar/Wind Harmer
28.28
316240AF1-291 C
Solar/Wind Harmer
0.727
939181AE1-148 GEN
Solar/Wind Harmer
13.388
944641AF1-129 GEN
Adder
100.657
316274AC1-208 GEN
Solar/Wind Harmer
2.554
970301AG2-198 GEN
Solar/Wind Harmer
11.788
316033AB2-134 GEN
Solar/Wind Harmer
7.598
315697AD1-025 GEN
Solar/Wind Harmer
4.765
313527AB2-043 GEN
Solar/Wind Harmer
3.807
315814AE2-033 C
Solar/Wind Harmer
26.508
3143316POE
Solar/Wind Harmer
-0.107
3151081ELIZAR1
Adder
21.155
3151091ELIZAR2
Adder
20.788
957871AF2-081 GEN
Solar/Wind Harmer
12.957
3152611GOSPORTB
Adder
2.934
3152621GOSPORTC
Adder
2.49
3152601GOSPORTA
Adder
2.297
319010AE1-072 C
Solar/Wind Harmer
5.234
3146406KITTY HAWK
Solar/Wind Harmer
0.021
316305AF2-043 C
Solar/Wind Harmer
0.778
315833AF1-017_GEN
Solar/Wind Harmer
4.898
316349AD2-085 GEN
Solar/Wind Harmer
2.293
316311AC2-079 GEN
Solar/Wind Harmer
13.006
315835AF2-110_GEN
Solar/Wind Harmer
3.219
313526AB2-022
Solar/Wind Harmer
0.694
3146486SUNBURY
Solar/Wind Harmer
-0.026
3146486SUNBURY
Solar/Wind Harmer
-0.026
316321Z2-027
Solar/Wind Harmer
0.692
3146396TANGLEW
Solar/Wind Harmer
0.472
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
946281AF1-292 GEN
Solar/Wind Harmer
0.571
315611Z1-036_GEN2
Solar/Wind Harmer
6.264
971285AH1-108 GEN
Adder
1.701
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
316087AB2-174 GEN
Solar/Wind Harmer
3.593
965291AG1-394 GEN
Solar/Wind Harmer
2.212
315816AE2-034 GEN
Solar/Wind Harmer
2.016
315652AC1-086 GEN
Solar/Wind Harmer
27.921
3137643SOCKMAN
Solar/Wind Harmer
-0.099
316318V4-068
Solar/Wind Harmer
0.617
3145893MURPHYS
Solar/Wind Harmer
-0.066
3145893MURPHYS
Solar/Wind Harmer
-0.025
971445AH1-216 GEN
Solar/Wind Harmer
15.317
3146043SEABORD
Solar/Wind Harmer
-0.025
315607AA1-063A GEN
Solar/Wind Harmer
2.496
3130546PLYMOUTH
Solar/Wind Harmer
-0.025
315732AD1-074 GEN1
Solar/Wind Harmer
4.987
315733AD1-074 GEN2
Solar/Wind Harmer
4.987
315735AD1-075 GEN1
Solar/Wind Harmer
2.494
3146206CASHIE
Solar/Wind Harmer
-0.024
970601AG2-382 GEN
Solar/Wind Harmer
10.751
3145513AHOSKIE
Solar/Wind Harmer
0.214
961941AG1-037 GEN
Solar/Wind Harmer
0.184
3145513AHOSKIE
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.078
3145796HORNRTN
Solar/Wind Harmer
-0.01
3145683EARLEYS
Solar/Wind Harmer
-0.049
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
970831AG2-522 GEN
Solar/Wind Harmer
12.084
972265AH1-717 GEN
Adder
16.682
3151201GRAVEL4
Adder
15.639
3151191GRAVEL3
Adder
15.441
3151211GRAVEL5
Adder
15.441
3146033SCOT NK
Solar/Wind Harmer
-0.095
316369SG1_INVT
Solar/Wind Harmer
4.209
316239AB2-077_GEN
Solar/Wind Harmer
0.705
316238AB2-078_GEN
Solar/Wind Harmer
0.705
316132AB2-190 GEN1
Solar/Wind Harmer
2.348
316005AA1-067
Solar/Wind Harmer
0.465
3145746EVERETS
Solar/Wind Harmer
-0.091
3145746EVERETS
Solar/Wind Harmer
-0.023
3145746EVERETS
Solar/Wind Harmer
-0.023
3145746EVERETS
Solar/Wind Harmer
-0.023
970181AG2-120 GEN
Solar/Wind Harmer
3.018
971443AH1-215 GEN
Solar/Wind Harmer
4.504
3144303KENBRDG
Solar/Wind Harmer
-0.018
957861AF2-080 GEN
Solar/Wind Harmer
9.982
316319Z2-044 C
Solar/Wind Harmer
1.259
316420AA1-050 GEN
Solar/Wind Harmer
2.596
3145573BETHELC
Solar/Wind Harmer
-0.023
3145573BETHELC
Solar/Wind Harmer
-0.023
3142433PROV 92
Adder
0.331
3142433PROV 92
Adder
0.331
972205AH1-687 GEN
Adder
6.109
972189AH1-679 GEN
Adder
2.243
316164AC1-076 GEN
Solar/Wind Helper
1.087
3145933PARMELE
Solar/Wind Harmer
-0.046
3145933PARMELE
Solar/Wind Harmer
-0.023
970323AG2-213 GEN
Solar/Wind Harmer
11.427
971775AH1-396 GEN
Solar/Wind Harmer
1.627
316034AC1-036 C
Solar/Wind Harmer
0.424
3145493TOT1
Solar/Wind Harmer
0.351
3145453TOT5
Solar/Wind Harmer
0.21
3145603CNETO
Solar/Wind Harmer
0.14
962561AG1-105 GEN
Solar/Wind Harmer
12.738
3144293JTRSVLE
Adder
0.633
3144293JTRSVLE
Adder
0.533
3142366NRTHEST
Adder
0.564
3150691DARBY 3
Adder
12.219
3150701DARBY 4
Adder
12.191
3150681DARBY 2
Adder
12.177
3150671DARBY 1
Adder
12.163
3142296MT RD221
Adder
0.462
3150341NORNECKC1
Adder
1.318
3150341NORNECKC1
Adder
1.308
316447AC1-158 HLD
Solar/Wind Helper
3.689
3145893MURPHYS
Solar/Wind Harmer
-0.025
957521AF2-046 GEN
Solar/Wind Harmer
19.463
961681AG1-008 GEN
Solar/Wind Harmer
19.463
965281AG1-393 GEN
Solar/Wind Harmer
3.089
971157AH1-035 GEN
Solar/Wind Harmer
3.087
315737AD1-076 GEN
Solar/Wind Harmer
4.686
3146173TUNIS
Solar/Wind Harmer
-0.025
3146206CASHIE
Solar/Wind Harmer
-0.024
316463AE2-346 GEN
Solar/Wind Harmer
0.397
316140AB2-099
Solar/Wind Harmer
0.165
962331AG1-082 GEN
Solar/Wind Harmer
3.064
3145796HORNRTN
Solar/Wind Harmer
-0.097
3145796HORNRTN
Solar/Wind Harmer
-0.024
3146263WOODLND
Solar/Wind Harmer
-0.024
3156021HOLLOMANSOL
Solar/Wind Harmer
3.295
316317KELFORD C
Solar/Wind Harmer
1.139
3145823KELFORD
Solar/Wind Harmer
-0.024
3151221GRAVEL6
Adder
15.621
3151171GRAVELC
Adder
3.005
3145963POPLR C
Solar/Wind Harmer
-0.024
961611AG1-000B GEN
Solar/Wind Harmer
5.036
316210AC1-098 GEN
Solar/Wind Harmer
3.72
970909AG2-566 GEN
Solar/Wind Harmer
2.238
315778AD1-151 GEN
Solar/Wind Harmer
20.288
316131AB2-060 GEN
Solar/Wind Harmer
2.524
315724AD1-057 GEN
Solar/Wind Harmer
1.345
3145933PARMELE
Solar/Wind Harmer
-0.023
966801AG1-551 GEN
Solar/Wind Harmer
2.91
964241AG1-285 GEN
Solar/Wind Harmer
18.149
970129AG2-093 GEN
Solar/Wind Harmer
13.053
316327AA2-057 GEN
Solar/Wind Harmer
2.335
3145746EVERETS
Solar/Wind Harmer
-0.023
3145746EVERETS
Solar/Wind Harmer
-0.023
315785AD2-033 C
Solar/Wind Harmer
5.203
970257AG2-171 GEN
Solar/Wind Harmer
8.57
970133AG2-095 GEN
Solar/Wind Harmer
2.571
3146233WITAKRS
Solar/Wind Harmer
0.477
3146233WITAKRS
Solar/Wind Harmer
-0.015
959311AF2-222 GEN
Solar/Wind Harmer
23.777
3138543CONSLDL
Solar/Wind Harmer
-0.015
3146073TAR RVR
Solar/Wind Harmer
-0.023
3146083TARBORO
Solar/Wind Harmer
-0.023
3144216WINCHST
Adder
0.753
3144293JTRSVLE
Adder
0.633
3150921YORKTN3
Adder
4.961
3143096IRON208
Adder
0.8
3143096IRON208
Adder
0.784
3142433PROV 92
Adder
0.331
3142433PROV 92
Adder
0.331
3141843SHACKLE
Adder
0.825
3150351NORNECKC2
Adder
1.276
316044AC1-158 PL1
Solar/Wind Helper
1.676
316450AC1-158 RIC
Solar/Wind Helper
0.447
3147666LOUISA
Solar/Wind Helper
0.577
971451AH1-221 GEN
50/50
11.16
3151531CLOVER1
50/50
5.066
3143226MDLTHAN
Solar/Wind Harmer
-0.035
940641AE2-051 GEN
Solar/Wind Harmer
30.624
939411AE1-173 GEN
Solar/Wind Harmer
155.015
3143526WINTERP
Solar/Wind Harmer
-0.159
970919AG2-571 GEN
Solar/Wind Harmer
9.517
970087AG2-069 GEN
Solar/Wind Harmer
28.061
957481AF2-042 GEN
Solar/Wind Harmer
87.144
3143336POWHATN
Solar/Wind Harmer
3.295
315693AD1-088 GEN
Solar/Wind Harmer
13.425
962491AG1-098 GEN
Solar/Wind Harmer
17.843
944591AF1-124 GEN
Solar/Wind Harmer
119.528
316023GEN1_S
Solar/Wind Harmer
1.762
316294AC1-161 GEN
Solar/Wind Harmer
8.432
316388AE2-253 GEN
Solar/Wind Harmer
1.749
316375AC2-012 GEN
Solar/Wind Harmer
8.959
3150981CHESPKA
Adder
2.877
3146456SLIGO L269
Solar/Wind Harmer
-0.026
970659AG2-427 GEN
Solar/Wind Harmer
13.731
316381AD1-082 GEN
Solar/Wind Harmer
2.37
970661AG2-428 GEN
Solar/Wind Harmer
27.441
316246AF1-032 C
Solar/Wind Harmer
0.522
316093AE2-104_GEN
Solar/Wind Harmer
7.488
316336AC2-165 C
Solar/Wind Harmer
4.471
3146516WINFALL
Solar/Wind Harmer
-0.082
3146516WINFALL
Solar/Wind Harmer
-0.025
960081AF2-299 GEN
Solar/Wind Harmer
2.867
315800Z1-036_GEN1
Solar/Wind Harmer
6.264
3150851SPRUNCC
Adder
1.039
316072AD1-144
Solar/Wind Harmer
0.511
3130156CHOWAN
Solar/Wind Harmer
-0.025
971795AH1-408 GEN
Solar/Wind Harmer
18.794
3145663CRESWEL
Solar/Wind Harmer
-0.069
971163AH1-040 GEN
Solar/Wind Harmer
23.356
3147043LAWRENC
Adder
2.002
315687AD1-152 GEN
Solar/Wind Harmer
2.994
316011AB1-132 GEN
Solar/Wind Harmer
5.193
962571AG1-106 GEN
Solar/Wind Harmer
3.568
3145336SMITFLD
Solar/Wind Harmer
-0.099
3145893MURPHYS
Solar/Wind Harmer
-0.099
3145893MURPHYS
Solar/Wind Harmer
0.735
3146173TUNIS
Solar/Wind Harmer
-0.025
3146206CASHIE
Solar/Wind Harmer
-0.024
971547AH1-271 GEN
Solar/Wind Harmer
6.143
316190AA2-174 GEN
Solar/Wind Harmer
0.301
3145796HORNRTN
Solar/Wind Harmer
-0.08
3145796HORNRTN
Solar/Wind Harmer
-0.024
3146263WOODLND
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145783HORNRTN
Solar/Wind Harmer
-0.024
315671AE2-027_GEN
Solar/Wind Harmer
18.264
3145823KELFORD
Solar/Wind Harmer
-0.024
3151171GRAVELC
Adder
2.286
316129AC1-054 GEN
Solar/Wind Harmer
2.115
971065AG2-659 GEN
Solar/Wind Harmer
12.042
3145963POPLR C
Solar/Wind Harmer
-0.024
961611AG1-000B GEN
Solar/Wind Harmer
11.802
316174AB2-169 GEN
Solar/Wind Harmer
3.669
971647AH1-324 GEN
Solar/Wind Harmer
11.868
316212AC1-099_GEN
Solar/Wind Harmer
2.067
971069AG2-661 GEN
Solar/Wind Harmer
3.706
316237AB2-079_GEN
Solar/Wind Harmer
0.705
315722AD1-056 GEN
Solar/Wind Harmer
2.445
3146293MARTNCO
Solar/Wind Harmer
0.144
316458AB2-190 GEN2
Solar/Wind Harmer
2.348
970129AG2-093 GEN
Solar/Wind Harmer
5.287
3145746EVERETS
Solar/Wind Harmer
-0.023
3145746EVERETS
Solar/Wind Harmer
-0.023
316494AC1-189 GEN
Solar/Wind Harmer
2.455
3146233WITAKRS
Solar/Wind Harmer
-0.09
3142543TWELFTH
Solar/Wind Harmer
-0.002
961671AG1-007 GEN
Solar/Wind Harmer
0.287
3146083TARBORO
Solar/Wind Harmer
-0.023
3145493TOT1
Solar/Wind Harmer
0.672
3144293JTRSVLE
Adder
0.633
3143096IRON208
Adder
0.8
944631AF1-128 GEN
Adder
88.052
3142433PROV 92
Adder
0.331
3142433PROV 92
Adder
0.331
3141843SHACKLE
Adder
0.825
3150351NORNECKC2
Adder
1.255
316045AC1-158 PL2
Solar/Wind Helper
5.365
3147666LOUISA
Solar/Wind Helper
1.003
316192AB2-158 GEN
Solar/Wind Helper
1.65
970685AG2-442 GEN
Solar/Wind Harmer
7.163
LAGNLTFEXP_LAGN->PJM
CLTF
9.293
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.961
TVALTFEXP_TVA->PJM
CLTF
4.659
CPLELTFEXP_CPLE->PJM
CLTF
13.39
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.781
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.498
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.936
MECLTFEXP_MEC->PJM
CLTF
4.446
SIGELTFEXP_SIGE->PJM
CLTF
0.134
NYPJM->LTFIMP_NY
CLTF
2.509
LGEELTFEXP_LGEE->PJM
CLTF
1.615
WECLTFEXP_WEC->PJM
CLTF
0.822

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2054-2135_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2054-2135_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.47 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4115.95
MW Contribution:10.94
Bus #Bus NameTypeMW Contribution
970119AG2-088 GEN
50/50
40.916
315243AE2-183_GT3
50/50
4.579
3151051BRUNSWICKS1
50/50
7.473
3151021BRUNSWICKG1
50/50
3.601
971451AH1-221 GEN
50/50
10.937
3151531CLOVER1
50/50
5.026
3143226MDLTHAN
Solar/Wind Harmer
-0.034
940641AE2-051 GEN
Solar/Wind Harmer
29.864
939411AE1-173 GEN
Solar/Wind Harmer
150.793
970919AG2-571 GEN
Solar/Wind Harmer
9.333
970087AG2-069 GEN
Solar/Wind Harmer
27.522
3143526WINTERP
Solar/Wind Harmer
-0.152
3143336POWHATN
Solar/Wind Harmer
3.333
957481AF2-042 GEN
Solar/Wind Harmer
86.276
315693AD1-088 GEN
Solar/Wind Harmer
13.378
962491AG1-098 GEN
Solar/Wind Harmer
17.804
316336AC2-165 C
Solar/Wind Harmer
4.589
316023GEN1_S
Solar/Wind Harmer
1.714
944591AF1-124 GEN
Solar/Wind Harmer
115.211
316294AC1-161 GEN
Solar/Wind Harmer
8.131
316388AE2-253 GEN
Solar/Wind Harmer
1.685
3146456SLIGO L269
Solar/Wind Harmer
-0.025
316375AC2-012 GEN
Solar/Wind Harmer
8.622
3150981CHESPKA
Adder
2.768
960081AF2-299 GEN
Solar/Wind Harmer
2.801
316246AF1-032 C
Solar/Wind Harmer
0.503
316093AE2-104_GEN
Solar/Wind Harmer
7.211
970661AG2-428 GEN
Solar/Wind Harmer
26.234
316381AD1-082 GEN
Solar/Wind Harmer
2.262
3146516WINFALL
Solar/Wind Harmer
-0.079
3146516WINFALL
Solar/Wind Harmer
-0.025
970659AG2-427 GEN
Solar/Wind Harmer
13.1
315687AD1-152 GEN
Solar/Wind Harmer
2.972
971795AH1-408 GEN
Solar/Wind Harmer
18.452
315800Z1-036_GEN1
Solar/Wind Harmer
6.052
3147043LAWRENC
Adder
1.97
3130156CHOWAN
Solar/Wind Harmer
-0.024
316072AD1-144
Solar/Wind Harmer
0.491
316011AB1-132 GEN
Solar/Wind Harmer
5.061
962571AG1-106 GEN
Solar/Wind Harmer
3.477
3145663CRESWEL
Solar/Wind Harmer
-0.067
971163AH1-040 GEN
Solar/Wind Harmer
22.621
3145893MURPHYS
Solar/Wind Harmer
-0.096
3145893MURPHYS
Solar/Wind Harmer
0.714
316190AA2-174 GEN
Solar/Wind Harmer
0.294
3146173TUNIS
Solar/Wind Harmer
-0.024
3145783HORNRTN
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.078
3145796HORNRTN
Solar/Wind Harmer
-0.024
3146206CASHIE
Solar/Wind Harmer
-0.024
971547AH1-271 GEN
Solar/Wind Harmer
5.963
3146263WOODLND
Solar/Wind Harmer
-0.024
316129AC1-054 GEN
Solar/Wind Harmer
2.089
971065AG2-659 GEN
Solar/Wind Harmer
11.903
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145336SMITFLD
Solar/Wind Harmer
-0.094
3150851SPRUNCC
Adder
0.972
3145823KELFORD
Solar/Wind Harmer
-0.023
316237AB2-079_GEN
Solar/Wind Harmer
0.706
3145963POPLR C
Solar/Wind Harmer
-0.023
316212AC1-099_GEN
Solar/Wind Harmer
2.019
316174AB2-169 GEN
Solar/Wind Harmer
3.571
970685AG2-442 GEN
Solar/Wind Harmer
20.162
3151171GRAVELC
Adder
2.174
963171AG1-166 GEN
Solar/Wind Harmer
2.865
3151031BRUNSWICKG2
50/50
3.601
970413AG2-270 GEN
50/50
21.932
3151101ELIZAR3
50/50
21.884
970917AG2-570 GEN
Solar/Wind Harmer
73.734
316313AB2-026
Solar/Wind Harmer
0.757
316258AE1-075 C
Solar/Wind Harmer
0.682
316405AF2-144 C
Solar/Wind Harmer
0.719
3143336POWHATN
Solar/Wind Harmer
2.833
316478AD1-087 GEN
Solar/Wind Harmer
2.283
316486AD2-202 GEN
Solar/Wind Harmer
0.669
316365GEN2_N
Solar/Wind Harmer
1.714
944581AF1-123 GEN
Solar/Wind Harmer
114.798
944601AF1-125 GEN
Solar/Wind Harmer
113.006
315773AC2-141 GEN
Solar/Wind Harmer
10.516
3146456SLIGO L269
Solar/Wind Harmer
-0.025
971153AH1-033 GEN
Solar/Wind Harmer
3.041
3144873MCLAUGH
Solar/Wind Harmer
-0.001
966621AG1-532 GEN
Solar/Wind Harmer
0.505
316320Y1-086
Solar/Wind Harmer
1.455
316435W1029_GEN3
Solar/Wind Harmer
4.473
970661AG2-428 GEN
Solar/Wind Harmer
4.649
316083AB2-161 GEN
Solar/Wind Harmer
4.004
3146516WINFALL
Solar/Wind Harmer
-0.025
970659AG2-427 GEN
Solar/Wind Harmer
2.322
3145273HOLLAND
Solar/Wind Harmer
-0.018
315813AE1-149 C
Solar/Wind Harmer
15.384
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3144536CHRHLND
Solar/Wind Harmer
-0.004
313506AB2-031 GEN
Solar/Wind Harmer
1.969
3147043LAWRENC
Solar/Wind Harmer
-0.015
3146376EDENTON
Solar/Wind Harmer
-0.024
3156081AA2-088 GEN
Solar/Wind Harmer
7.869
970909AG2-566 GEN
Solar/Wind Harmer
2.298
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
315614AA2-178 GEN
Solar/Wind Harmer
2.603
3145893MURPHYS
Solar/Wind Harmer
0.168
3145893MURPHYS
Solar/Wind Harmer
-0.024
957521AF2-046 GEN
Solar/Wind Harmer
18.923
961681AG1-008 GEN
Solar/Wind Harmer
18.923
971157AH1-035 GEN
Solar/Wind Harmer
2.994
3146173TUNIS
Solar/Wind Harmer
-0.024
315737AD1-076 GEN
Solar/Wind Harmer
4.545
315839AE2-212 C
Solar/Wind Harmer
0.72
3145796HORNRTN
Solar/Wind Harmer
-0.095
3145796HORNRTN
Solar/Wind Harmer
-0.024
3146206CASHIE
Solar/Wind Harmer
-0.024
316463AE2-346 GEN
Solar/Wind Harmer
0.386
316140AB2-099
Solar/Wind Harmer
0.161
962331AG1-082 GEN
Solar/Wind Harmer
2.98
3146263WOODLND
Solar/Wind Harmer
-0.024
3156021HOLLOMANSOL
Solar/Wind Harmer
3.202
3145336SMITFLD
Solar/Wind Harmer
-0.009
3150861SPRUNCD
Adder
0.972
316317KELFORD C
Solar/Wind Harmer
1.11
3145823KELFORD
Solar/Wind Harmer
-0.023
316131AB2-060 GEN
Solar/Wind Harmer
2.53
964241AG1-285 GEN
Solar/Wind Harmer
18.252
3145963POPLR C
Solar/Wind Harmer
-0.023
965281AG1-393 GEN
Solar/Wind Harmer
2.905
315785AD2-033 C
Solar/Wind Harmer
5.263
970257AG2-171 GEN
Solar/Wind Harmer
8.69
316210AC1-098 GEN
Solar/Wind Harmer
3.635
959311AF2-222 GEN
Solar/Wind Harmer
24.148
3151221GRAVEL6
Adder
14.856
3151171GRAVELC
Adder
2.858
963181AG1-167 GEN
Solar/Wind Harmer
2.149
3144293JTRSVLE
Adder
0.649
315724AD1-057 GEN
Solar/Wind Harmer
1.315
3147133PAMPLIN
Solar/Wind Harmer
-0.071
971193AH1-056 GEN
Solar/Wind Harmer
14.27
316303AF2-085
50/50
5.455
315244AE2-183_ST
50/50
7.916
963041AG1-153 GEN
50/50
7.291
315779AE2-040
50/50
3.435
3151541CLOVER2
50/50
5.002
941031AE2-094 GEN
Solar/Wind Harmer
60.188
944011AF1-069 GEN
Solar/Wind Harmer
18.859
970673AG2-436 GEN
Solar/Wind Harmer
66.104
970673AG2-436 GEN
Solar/Wind Harmer
33.47
971967AH1-528 GEN
Solar/Wind Harmer
58.188
970085AG2-068 GEN
Solar/Wind Harmer
18.348
970581AG2-369 GEN
Solar/Wind Harmer
15.779
316233AE1-074 FULL
Solar/Wind Harmer
0.788
971281AH1-106 GEN
Solar/Wind Harmer
4.763
971283AH1-107 GEN
Solar/Wind Harmer
4.763
316315AB2-025 C
Solar/Wind Harmer
0.746
315814AE2-033 C
Solar/Wind Harmer
25.646
3143316POE
Solar/Wind Harmer
-0.102
957871AF2-081 GEN
Solar/Wind Harmer
12.489
3151081ELIZAR1
Adder
20.363
3151091ELIZAR2
Adder
20.009
319010AE1-072 C
Solar/Wind Harmer
5.045
3146406KITTY HAWK
Solar/Wind Harmer
0.021
3152611GOSPORTB
Adder
2.824
3152621GOSPORTC
Adder
2.397
3152601GOSPORTA
Adder
2.211
946281AF1-292 GEN
Solar/Wind Harmer
0.558
316305AF2-043 C
Solar/Wind Harmer
0.75
313526AB2-022
Solar/Wind Harmer
0.67
315835AF2-110_GEN
Solar/Wind Harmer
3.1
316321Z2-027
Solar/Wind Harmer
0.668
3146396TANGLEW
Solar/Wind Harmer
0.456
3145176PASQUOTANK
Solar/Wind Harmer
-0.015
3146486SUNBURY
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
315833AF1-017_GEN
Solar/Wind Harmer
4.701
316349AD2-085 GEN
Solar/Wind Harmer
2.201
316311AC2-079 GEN
Solar/Wind Harmer
12.483
316087AB2-174 GEN
Solar/Wind Harmer
3.511
315611Z1-036_GEN2
Solar/Wind Harmer
6.052
3130156CHOWAN
Solar/Wind Harmer
-0.024
3130156CHOWAN
Solar/Wind Harmer
-0.024
3137643SOCKMAN
Solar/Wind Harmer
-0.096
965291AG1-394 GEN
Solar/Wind Harmer
2.149
315652AC1-086 GEN
Solar/Wind Harmer
27.213
315816AE2-034 GEN
Solar/Wind Harmer
1.952
3146043SEABORD
Solar/Wind Harmer
-0.024
315607AA1-063A GEN
Solar/Wind Harmer
2.435
316318V4-068
Solar/Wind Harmer
0.6
3145893MURPHYS
Solar/Wind Harmer
-0.065
3145893MURPHYS
Solar/Wind Harmer
-0.024
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.837
315733AD1-074 GEN2
Solar/Wind Harmer
4.837
315735AD1-075 GEN1
Solar/Wind Harmer
2.419
3145796HORNRTN
Solar/Wind Harmer
-0.076
3145796HORNRTN
Solar/Wind Harmer
-0.009
3146206CASHIE
Solar/Wind Harmer
-0.024
970601AG2-382 GEN
Solar/Wind Harmer
10.436
3145513AHOSKIE
Solar/Wind Harmer
0.208
961941AG1-037 GEN
Solar/Wind Harmer
0.179
3145513AHOSKIE
Solar/Wind Harmer
-0.024
970831AG2-522 GEN
Solar/Wind Harmer
11.922
3145683EARLEYS
Solar/Wind Harmer
-0.047
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
971285AH1-108 GEN
Adder
1.59
971445AH1-216 GEN
Solar/Wind Harmer
14.631
316239AB2-077_GEN
Solar/Wind Harmer
0.706
316238AB2-078_GEN
Solar/Wind Harmer
0.706
3146033SCOT NK
Solar/Wind Harmer
-0.093
971443AH1-215 GEN
Solar/Wind Harmer
4.564
3144303KENBRDG
Solar/Wind Harmer
-0.019
970683AG2-441 GEN
Solar/Wind Harmer
18.002
970681AG2-440 GEN
Solar/Wind Harmer
14.401
972265AH1-717 GEN
Adder
15.866
3151201GRAVEL4
Adder
14.873
3151191GRAVEL3
Adder
14.685
3151211GRAVEL5
Adder
14.685
946301AF1-294 GEN
Solar/Wind Harmer
5.873
970533AG2-339 GEN
50/50
25.396
970531AG2-338 GEN
50/50
10.158
315242AE2-183_GT2
50/50
4.579
315241AE2-183_GT1
50/50
4.551
972185AH1-677 GEN
50/50
16.507
3151041BRUNSWICKG3
50/50
3.601
972187AH1-678 GEN
50/50
8.263
971223AH1-071 GEN
Solar/Wind Harmer
4.31
970933AG2-581 GEN
Solar/Wind Harmer
28.14
3143526WINTERP
Solar/Wind Harmer
-0.152
3144356SAPONY
Solar/Wind Harmer
0.965
970099AG2-077 GEN
Solar/Wind Harmer
34.511
316185AD1-033 GEN
Solar/Wind Harmer
2.642
3145506HICKORY
Solar/Wind Harmer
-0.1
3145506HICKORY
Solar/Wind Harmer
-0.06
3145506HICKORY
Solar/Wind Harmer
-0.015
3142956BIRDNECK
Solar/Wind Harmer
1.341
316339AD2-160 GEN
Solar/Wind Harmer
1.685
316316AC1-027 C
Solar/Wind Harmer
0.767
316018AA1-139 ULT2
Solar/Wind Harmer
2.14
316017AA1-139 ULT1
Solar/Wind Harmer
2.021
3137176SLIGO L2192
Solar/Wind Harmer
-0.099
3146456SLIGO L269
Solar/Wind Harmer
2.947
3130086AYDLETT
Solar/Wind Harmer
-0.099
316036AC1-147 C
Solar/Wind Harmer
0.672
3150991CHESPKB
Adder
2.323
3150991CHESPKB
Adder
2.267
3146386ELIZ CT
Solar/Wind Harmer
-0.025
971741AH1-377 GEN
Solar/Wind Harmer
28.815
316431W1029_GEN1
Solar/Wind Harmer
4.473
316433W1029_GEN2
Solar/Wind Harmer
4.473
970657AG2-426 GEN
Solar/Wind Harmer
7.711
970657AG2-426 GEN
Solar/Wind Harmer
1.613
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
315742AE1-103 GEN
Solar/Wind Harmer
2.566
316181AB2-040 GEN
Solar/Wind Harmer
3.416
3146376EDENTON
Solar/Wind Harmer
0.723
3146376EDENTON
Solar/Wind Harmer
0.723
970301AG2-198 GEN
Solar/Wind Harmer
12.1
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3145893MURPHYS
Solar/Wind Harmer
0.672
3145893MURPHYS
Solar/Wind Harmer
-0.043
3145593CAROLNA
Solar/Wind Harmer
-0.024
3145593CAROLNA
Solar/Wind Harmer
-0.024
966811AG1-552 GEN
Solar/Wind Harmer
2.703
3145593CAROLNA
Solar/Wind Harmer
0.2
316426AA2-053 GEN
Solar/Wind Harmer
2.423
3146173TUNIS
Solar/Wind Harmer
-0.024
3146173TUNIS
Solar/Wind Harmer
-0.024
3145783HORNRTN
Solar/Wind Harmer
2.835
3145783HORNRTN
Solar/Wind Harmer
2.268
3145783HORNRTN
Solar/Wind Harmer
0.709
3145783HORNRTN
Solar/Wind Harmer
0.283
3145796HORNRTN
Solar/Wind Harmer
-0.071
316065AD1-022 GEN
Solar/Wind Harmer
11.938
316236AE1-162_GEN
Solar/Wind Harmer
0.715
939181AE1-148 GEN
Solar/Wind Harmer
13.315
313527AB2-043 GEN
Solar/Wind Harmer
3.812
970323AG2-213 GEN
Solar/Wind Harmer
11.586
971775AH1-396 GEN
Solar/Wind Harmer
1.65
316034AC1-036 C
Solar/Wind Harmer
0.43
316274AC1-208 GEN
Solar/Wind Harmer
2.497
958211AF2-115 GEN
Solar/Wind Harmer
3.581
963191AG1-168 GEN
Solar/Wind Harmer
2.149
3144293JTRSVLE
Adder
0.649
3144293JTRSVLE
Adder
0.547
3147133PAMPLIN
Solar/Wind Harmer
-0.023
3147133PAMPLIN
Solar/Wind Harmer
-0.018
3145933PARMELE
Solar/Wind Harmer
-0.045
3145933PARMELE
Solar/Wind Harmer
-0.023
962561AG1-105 GEN
Solar/Wind Harmer
12.73
316240AF1-291 C
Solar/Wind Harmer
0.679
944641AF1-129 GEN
Adder
93.798
3142366NRTHEST
Adder
0.504
3150691DARBY 3
Adder
10.929
3150701DARBY 4
Adder
10.903
3150681DARBY 2
Adder
10.891
3150671DARBY 1
Adder
10.878
3142296MT RD221
Adder
0.387
3150341NORNECKC1
Adder
1.196
3150341NORNECKC1
Adder
1.186
316447AC1-158 HLD
Solar/Wind Helper
3.787
966001AG1-469 GEN
Solar/Wind Helper
0.322
315651AD1-115 GEN
Solar/Wind Helper
0.849
964791AG1-342 GEN
Solar/Wind Harmer
3.241
961791AG1-021 GEN
Solar/Wind Harmer
2.865
315657AE1-056 GEN
Solar/Wind Harmer
8.562
972205AH1-687 GEN
Adder
7.023
3142433PROV 92
Adder
0.305
3142433PROV 92
Adder
0.305
316164AC1-076 GEN
Solar/Wind Helper
1.276
3145933PARMELE
Solar/Wind Harmer
-0.023
966801AG1-551 GEN
Solar/Wind Harmer
2.838
961611AG1-000B GEN
Solar/Wind Harmer
4.775
316327AA2-057 GEN
Solar/Wind Harmer
2.286
942461AE2-259 GEN
Solar/Wind Harmer
3.394
3144216WINCHST
Adder
0.715
3150921YORKTN3
Adder
4.706
3143096IRON208
Adder
0.735
3143096IRON208
Adder
0.72
3142433PROV 92
Adder
0.305
3142433PROV 92
Adder
0.305
3141843SHACKLE
Adder
0.762
3150351NORNECKC2
Adder
1.158
3147666LOUISA
Solar/Wind Helper
0.782
316044AC1-158 PL1
Solar/Wind Helper
1.721
316450AC1-158 RIC
Solar/Wind Helper
0.459
3132273ORANGE
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.398
971563AH1-280 GEN
Solar/Wind Harmer
2.865
3144293JTRSVLE
Adder
0.649
315722AD1-056 GEN
Solar/Wind Harmer
2.391
315671AE2-027_GEN
Solar/Wind Harmer
17.138
3146293MARTNCO
Solar/Wind Harmer
0.141
961611AG1-000B GEN
Solar/Wind Harmer
11.191
3143096IRON208
Adder
0.735
944631AF1-128 GEN
Adder
81.193
3142433PROV 92
Adder
0.305
3142433PROV 92
Adder
0.305
3141843SHACKLE
Adder
0.762
3150351NORNECKC2
Adder
1.139
3147666LOUISA
Solar/Wind Helper
1.36
316192AB2-158 GEN
Solar/Wind Helper
2.271
316045AC1-158 PL2
Solar/Wind Helper
5.508
316254AC1-120 GEN1
Solar/Wind Helper
1.194
970401AG2-262 GEN
Solar/Wind Harmer
0.99
LAGNLTFEXP_LAGN->PJM
CLTF
9.537
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.961
TVALTFEXP_TVA->PJM
CLTF
4.788
CPLELTFEXP_CPLE->PJM
CLTF
13.285
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.607
CBM West 1LTFEXP_CBM-W1->PJM
CBM
30.685
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.441
MECLTFEXP_MEC->PJM
CLTF
4.694
SIGELTFEXP_SIGE->PJM
CLTF
0.142
NYPJM->LTFIMP_NY
CLTF
2.522
LGEELTFEXP_LGEE->PJM
CLTF
1.726
WECLTFEXP_WEC->PJM
CLTF
0.88

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57302_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57302_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:161.07 %
Rating:3118.0 MVA
Rating Type:C
MVA to Mitigate:5022.16
MW Contribution:8.27
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
4.154
315244AE2-183_ST
50/50
5.99
963041AG1-153 GEN
50/50
5.516
315779AE2-040
50/50
2.503
3147346CASHSCORNER
Solar/Wind Harmer
0.403
941031AE2-094 GEN
Solar/Wind Harmer
45.568
944011AF1-069 GEN
Solar/Wind Harmer
14.278
970673AG2-436 GEN
Solar/Wind Harmer
50.031
970673AG2-436 GEN
Solar/Wind Harmer
25.332
971967AH1-528 GEN
Solar/Wind Harmer
44.101
970085AG2-068 GEN
Solar/Wind Harmer
13.851
970581AG2-369 GEN
Solar/Wind Harmer
11.912
316233AE1-074 FULL
Solar/Wind Harmer
0.574
971281AH1-106 GEN
Solar/Wind Harmer
3.465
971283AH1-107 GEN
Solar/Wind Harmer
3.465
316315AB2-025 C
Solar/Wind Harmer
0.543
315814AE2-033 C
Solar/Wind Harmer
18.684
3143316POE
Solar/Wind Harmer
-0.072
946281AF1-292 GEN
Solar/Wind Harmer
0.409
315657AE1-056 GEN
Solar/Wind Harmer
6.784
946301AF1-294 GEN
Solar/Wind Harmer
4.628
961791AG1-021 GEN
Solar/Wind Harmer
2.258
970683AG2-441 GEN
Solar/Wind Harmer
14.079
970681AG2-440 GEN
Solar/Wind Harmer
11.263
316087AB2-174 GEN
Solar/Wind Harmer
2.568
3144303KENBRDG
Solar/Wind Harmer
-0.014
971443AH1-215 GEN
Solar/Wind Harmer
3.538
316239AB2-077_GEN
Solar/Wind Harmer
0.537
316238AB2-078_GEN
Solar/Wind Harmer
0.537
970831AG2-522 GEN
Solar/Wind Harmer
8.853
3137643SOCKMAN
Solar/Wind Harmer
-0.07
970285AG2-188 GEN
Solar/Wind Harmer
15.458
315652AC1-086 GEN
Solar/Wind Harmer
19.749
971845AH1-439 GEN
Solar/Wind Harmer
9.317
315607AA1-063A GEN
Solar/Wind Harmer
1.762
3146043SEABORD
Solar/Wind Harmer
-0.017
957871AF2-081 GEN
Solar/Wind Harmer
8.713
319010AE1-072 C
Solar/Wind Harmer
3.521
3146406KITTY HAWK
Solar/Wind Harmer
0.014
313526AB2-022
Solar/Wind Harmer
0.468
316305AF2-043 C
Solar/Wind Harmer
0.523
3151081ELIZAR1
Adder
14.152
3151091ELIZAR2
Adder
13.906
965291AG1-394 GEN
Solar/Wind Harmer
1.539
3145796HORNRTN
Solar/Wind Harmer
-0.055
3145796HORNRTN
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.467
3145176PASQUOTANK
Solar/Wind Harmer
-0.011
3146396TANGLEW
Solar/Wind Harmer
0.319
315835AF2-110_GEN
Solar/Wind Harmer
2.165
3146486SUNBURY
Solar/Wind Harmer
-0.017
3146486SUNBURY
Solar/Wind Harmer
-0.017
3152611GOSPORTB
Adder
1.962
3152621GOSPORTC
Adder
1.665
3152601GOSPORTA
Adder
1.536
316318V4-068
Solar/Wind Harmer
0.43
3145893MURPHYS
Solar/Wind Harmer
-0.046
3145893MURPHYS
Solar/Wind Harmer
-0.017
316311AC2-079 GEN
Solar/Wind Harmer
8.691
315833AF1-017_GEN
Solar/Wind Harmer
3.272
316349AD2-085 GEN
Solar/Wind Harmer
1.532
315611Z1-036_GEN2
Solar/Wind Harmer
4.254
3130156CHOWAN
Solar/Wind Harmer
-0.017
3130156CHOWAN
Solar/Wind Harmer
-0.017
3145513AHOSKIE
Solar/Wind Harmer
0.149
961941AG1-037 GEN
Solar/Wind Harmer
0.129
3145513AHOSKIE
Solar/Wind Harmer
-0.017
315816AE2-034 GEN
Solar/Wind Harmer
1.381
3145683EARLEYS
Solar/Wind Harmer
-0.034
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.017
3130546PLYMOUTH
Solar/Wind Harmer
-0.017
3146206CASHIE
Solar/Wind Harmer
-0.017
970601AG2-382 GEN
Solar/Wind Harmer
7.432
315732AD1-074 GEN1
Solar/Wind Harmer
3.435
315733AD1-074 GEN2
Solar/Wind Harmer
3.435
315735AD1-075 GEN1
Solar/Wind Harmer
1.718
3146033SCOT NK
Solar/Wind Harmer
-0.067
316118AC1-105 GEN
Solar/Wind Harmer
1.149
972205AH1-687 GEN
Adder
6.275
971285AH1-108 GEN
Adder
1.072
972265AH1-717 GEN
Adder
10.649
3151201GRAVEL4
Adder
9.982
3151191GRAVEL3
Adder
9.856
3151211GRAVEL5
Adder
9.856
3152261N ANNA2
50/50
36.75
3151771S ANNAG1
50/50
0.935
3151801S ANNAS2
50/50
0.481
3151761LOISA E
50/50
35.514
972183AH1-676 GEN
50/50
276.382
3151031BRUNSWICKG2
50/50
2.724
3147666LOUISA
Solar/Wind Harmer
-0.113
316313AB2-026
Solar/Wind Harmer
0.603
316258AE1-075 C
Solar/Wind Harmer
0.543
316405AF2-144 C
Solar/Wind Harmer
0.573
3143336POWHATN
Solar/Wind Harmer
2.255
970917AG2-570 GEN
Solar/Wind Harmer
55.674
316478AD1-087 GEN
Solar/Wind Harmer
1.738
316486AD2-202 GEN
Solar/Wind Harmer
0.509
970909AG2-566 GEN
Solar/Wind Harmer
1.825
316365GEN2_N
Solar/Wind Harmer
1.247
3146926FARMVIL
Solar/Wind Harmer
-0.011
966621AG1-532 GEN
Solar/Wind Harmer
0.37
942461AE2-259 GEN
Solar/Wind Harmer
2.731
3147043LAWRENC
Solar/Wind Harmer
-0.011
3147133PAMPLIN
Solar/Wind Harmer
-0.057
971193AH1-056 GEN
Solar/Wind Harmer
11.307
963181AG1-167 GEN
Solar/Wind Harmer
1.693
3144293JTRSVLE
Adder
0.512
959311AF2-222 GEN
Solar/Wind Harmer
18.777
970257AG2-171 GEN
Solar/Wind Harmer
6.741
315785AD2-033 C
Solar/Wind Harmer
4.07
964241AG1-285 GEN
Solar/Wind Harmer
13.995
313506AB2-031 GEN
Solar/Wind Harmer
1.439
316131AB2-060 GEN
Solar/Wind Harmer
1.93
944581AF1-123 GEN
Solar/Wind Harmer
80.086
944601AF1-125 GEN
Solar/Wind Harmer
78.837
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3146776BUCKING
Solar/Wind Harmer
-0.006
315773AC2-141 GEN
Solar/Wind Harmer
7.296
3146456SLIGO L269
Solar/Wind Harmer
-0.017
971153AH1-033 GEN
Solar/Wind Harmer
2.122
316320Y1-086
Solar/Wind Harmer
1.017
3151101ELIZAR3
Adder
14.333
3156081AA2-088 GEN
Solar/Wind Harmer
5.629
3145796HORNRTN
Solar/Wind Harmer
-0.069
3145796HORNRTN
Solar/Wind Harmer
-0.017
3145273HOLLAND
Solar/Wind Harmer
-0.013
3144873MCLAUGH
Solar/Wind Harmer
0
316435W1029_GEN3
Solar/Wind Harmer
3.133
3146516WINFALL
Solar/Wind Harmer
-0.017
3146626S HERTFORD
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
0.12
3145893MURPHYS
Solar/Wind Harmer
-0.017
957521AF2-046 GEN
Solar/Wind Harmer
13.562
961681AG1-008 GEN
Solar/Wind Harmer
13.562
3146263WOODLND
Solar/Wind Harmer
-0.017
3146376EDENTON
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.017
970661AG2-428 GEN
Solar/Wind Harmer
3.225
316463AE2-346 GEN
Solar/Wind Harmer
0.277
316140AB2-099
Solar/Wind Harmer
0.115
962331AG1-082 GEN
Solar/Wind Harmer
2.137
316083AB2-161 GEN
Solar/Wind Harmer
2.773
970659AG2-427 GEN
Solar/Wind Harmer
1.607
315614AA2-178 GEN
Solar/Wind Harmer
1.842
971157AH1-035 GEN
Solar/Wind Harmer
2.125
315813AE1-149 C
Solar/Wind Harmer
10.623
3156021HOLLOMANSOL
Solar/Wind Harmer
2.289
3146206CASHIE
Solar/Wind Harmer
-0.017
315737AD1-076 GEN
Solar/Wind Harmer
3.228
3144536CHRHLND
Solar/Wind Harmer
-0.003
316317KELFORD C
Solar/Wind Harmer
0.799
3145823KELFORD
Solar/Wind Harmer
-0.017
316210AC1-098 GEN
Solar/Wind Harmer
2.634
3150861SPRUNCD
Adder
0.655
3151221GRAVEL6
Adder
9.971
3151171GRAVELC
Adder
1.918
3144216WINCHST
Adder
0.464
3150921YORKTN3
Adder
3.034
3152251N ANNA1
50/50
36.753
3151791S ANNAG2
50/50
0.935
3151781S ANNAS1
50/50
0.481
3151741LOISA C
50/50
0.953
3151751LOISA D
50/50
17.42
970119AG2-088 GEN
50/50
31.154
315243AE2-183_GT3
50/50
3.465
3151051BRUNSWICKS1
50/50
5.654
3151021BRUNSWICKG1
50/50
2.724
971451AH1-221 GEN
50/50
8.274
3147666LOUISA
Solar/Wind Harmer
-0.196
316192AB2-158 GEN
Solar/Wind Harmer
5.718
3143226MDLTHAN
Solar/Wind Harmer
-0.026
940641AE2-051 GEN
Solar/Wind Harmer
22.347
3143336POWHATN
Solar/Wind Harmer
2.653
970919AG2-571 GEN
Solar/Wind Harmer
7.047
939411AE1-173 GEN
Solar/Wind Harmer
111.228
970087AG2-069 GEN
Solar/Wind Harmer
20.777
316336AC2-165 C
Solar/Wind Harmer
3.708
3143526WINTERP
Solar/Wind Harmer
-0.11
957481AF2-042 GEN
Solar/Wind Harmer
65.731
315693AD1-088 GEN
Solar/Wind Harmer
10.265
962491AG1-098 GEN
Solar/Wind Harmer
13.684
970937AG2-583 GEN
Solar/Wind Harmer
13.455
315687AD1-152 GEN
Solar/Wind Harmer
2.252
316023GEN1_S
Solar/Wind Harmer
1.247
3146926FARMVIL
Solar/Wind Harmer
-0.011
960081AF2-299 GEN
Solar/Wind Harmer
2.052
971795AH1-408 GEN
Solar/Wind Harmer
13.624
3147043LAWRENC
Adder
1.46
963171AG1-166 GEN
Solar/Wind Harmer
2.258
971563AH1-280 GEN
Solar/Wind Harmer
2.258
3144293JTRSVLE
Adder
0.512
970685AG2-442 GEN
Solar/Wind Harmer
15.768
316237AB2-079_GEN
Solar/Wind Harmer
0.537
971065AG2-659 GEN
Solar/Wind Harmer
8.873
316129AC1-054 GEN
Solar/Wind Harmer
1.554
944591AF1-124 GEN
Solar/Wind Harmer
80.375
316011AB1-132 GEN
Solar/Wind Harmer
3.673
962571AG1-106 GEN
Solar/Wind Harmer
2.523
316322AB2-045
Solar/Wind Harmer
0.588
3146776BUCKING
Solar/Wind Harmer
-0.007
316294AC1-161 GEN
Solar/Wind Harmer
5.641
316388AE2-253 GEN
Solar/Wind Harmer
1.175
316190AA2-174 GEN
Solar/Wind Harmer
0.214
3146456SLIGO L269
Solar/Wind Harmer
-0.017
3145783HORNRTN
Solar/Wind Harmer
-0.017
316246AF1-032 C
Solar/Wind Harmer
0.351
3145796HORNRTN
Solar/Wind Harmer
-0.057
3145796HORNRTN
Solar/Wind Harmer
-0.017
316093AE2-104_GEN
Solar/Wind Harmer
5.036
316375AC2-012 GEN
Solar/Wind Harmer
5.989
3150981CHESPKA
Adder
1.923
3146516WINFALL
Solar/Wind Harmer
-0.056
3146516WINFALL
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.069
3145893MURPHYS
Solar/Wind Harmer
0.512
315800Z1-036_GEN1
Solar/Wind Harmer
4.254
3146263WOODLND
Solar/Wind Harmer
-0.017
3130156CHOWAN
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.017
970661AG2-428 GEN
Solar/Wind Harmer
18.199
316381AD1-082 GEN
Solar/Wind Harmer
1.567
970659AG2-427 GEN
Solar/Wind Harmer
9.07
3145663CRESWEL
Solar/Wind Harmer
-0.048
971163AH1-040 GEN
Solar/Wind Harmer
16.003
3145683EARLEYS
Solar/Wind Harmer
-0.017
970401AG2-262 GEN
Solar/Wind Harmer
1.111
3146206CASHIE
Solar/Wind Harmer
-0.017
971547AH1-271 GEN
Solar/Wind Harmer
4.247
3145823KELFORD
Solar/Wind Harmer
-0.017
316212AC1-099_GEN
Solar/Wind Harmer
1.463
316072AD1-144
Solar/Wind Harmer
0.339
3150851SPRUNCC
Adder
0.655
3151171GRAVELC
Adder
1.459
972003AH1-546 GEN
Solar/Wind Harmer
6.164
971133AH1-012 GEN
50/50
9.167
3151731LOISA B
50/50
17.42
3151721LOISA A
50/50
17.33
970533AG2-339 GEN
50/50
19.227
970531AG2-338 GEN
50/50
7.691
315242AE2-183_GT2
50/50
3.465
315241AE2-183_GT1
50/50
3.443
972185AH1-677 GEN
50/50
12.491
3151041BRUNSWICKG3
50/50
2.724
972187AH1-678 GEN
50/50
6.252
971223AH1-071 GEN
Solar/Wind Harmer
3.282
966001AG1-469 GEN
Solar/Wind Harmer
0.464
970933AG2-581 GEN
Solar/Wind Harmer
21.362
3143526WINTERP
Solar/Wind Harmer
-0.11
970099AG2-077 GEN
Solar/Wind Harmer
26.292
3144356SAPONY
Solar/Wind Harmer
0.703
971741AH1-377 GEN
Solar/Wind Harmer
22.699
970301AG2-198 GEN
Solar/Wind Harmer
9.614
3147133PAMPLIN
Solar/Wind Harmer
-0.018
3147133PAMPLIN
Solar/Wind Harmer
-0.014
958211AF2-115 GEN
Solar/Wind Harmer
2.822
963191AG1-168 GEN
Solar/Wind Harmer
1.693
3144293JTRSVLE
Adder
0.512
3144293JTRSVLE
Adder
0.431
316034AC1-036 C
Solar/Wind Harmer
0.333
970323AG2-213 GEN
Solar/Wind Harmer
8.988
971775AH1-396 GEN
Solar/Wind Harmer
1.28
316181AB2-040 GEN
Solar/Wind Harmer
2.496
313527AB2-043 GEN
Solar/Wind Harmer
2.904
939181AE1-148 GEN
Solar/Wind Harmer
10.04
3145593CAROLNA
Solar/Wind Harmer
-0.017
3145593CAROLNA
Solar/Wind Harmer
-0.017
966811AG1-552 GEN
Solar/Wind Harmer
1.97
3145593CAROLNA
Solar/Wind Harmer
0.145
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3146776BUCKING
Solar/Wind Harmer
-0.07
3146776BUCKING
Solar/Wind Harmer
-0.006
316185AD1-033 GEN
Solar/Wind Harmer
1.841
3145506HICKORY
Solar/Wind Harmer
-0.069
3145506HICKORY
Solar/Wind Harmer
-0.042
3145506HICKORY
Solar/Wind Harmer
-0.01
316339AD2-160 GEN
Solar/Wind Harmer
1.175
316426AA2-053 GEN
Solar/Wind Harmer
1.761
316018AA1-139 ULT2
Solar/Wind Harmer
1.493
316017AA1-139 ULT1
Solar/Wind Harmer
1.41
3137176SLIGO L2192
Solar/Wind Harmer
-0.069
3146456SLIGO L269
Solar/Wind Harmer
2.056
3130086AYDLETT
Solar/Wind Harmer
-0.069
3145783HORNRTN
Solar/Wind Harmer
2.065
3145783HORNRTN
Solar/Wind Harmer
1.652
3145783HORNRTN
Solar/Wind Harmer
0.516
3145783HORNRTN
Solar/Wind Harmer
0.206
3142956BIRDNECK
Solar/Wind Harmer
0.933
316316AC1-027 C
Solar/Wind Harmer
0.533
3146386ELIZ CT
Solar/Wind Harmer
-0.017
3145796HORNRTN
Solar/Wind Harmer
-0.052
315742AE1-103 GEN
Solar/Wind Harmer
1.812
316036AC1-147 C
Solar/Wind Harmer
0.467
3150991CHESPKB
Adder
1.613
3150991CHESPKB
Adder
1.575
316431W1029_GEN1
Solar/Wind Harmer
3.133
316433W1029_GEN2
Solar/Wind Harmer
3.133
3146516WINFALL
Solar/Wind Harmer
-0.017
3146516WINFALL
Solar/Wind Harmer
-0.017
3146516WINFALL
Solar/Wind Harmer
-0.017
3146626S HERTFORD
Solar/Wind Harmer
-0.017
3146626S HERTFORD
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
0.481
3145893MURPHYS
Solar/Wind Harmer
-0.031
3146376EDENTON
Solar/Wind Harmer
0.509
3146376EDENTON
Solar/Wind Harmer
0.509
3146173TUNIS
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.017
962561AG1-105 GEN
Solar/Wind Harmer
9.645
970657AG2-426 GEN
Solar/Wind Harmer
5.345
970657AG2-426 GEN
Solar/Wind Harmer
1.118
964791AG1-342 GEN
Solar/Wind Harmer
3.634
3146843MT LREL
Solar/Wind Harmer
-0.017
3146843MT LREL
Solar/Wind Harmer
-0.017
316065AD1-022 GEN
Solar/Wind Harmer
8.493
316274AC1-208 GEN
Solar/Wind Harmer
1.814
944641AF1-129 GEN
Adder
61.579
LAGNLTFEXP_LAGN->PJM
CLTF
6.179
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.792
TVALTFEXP_TVA->PJM
CLTF
3.107
CPLELTFEXP_CPLE->PJM
CLTF
9.705
CBM West 2LTFEXP_CBM-W2->PJM
CBM
30.98
CBM West 1LTFEXP_CBM-W1->PJM
CBM
14.411
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.458
MECLTFEXP_MEC->PJM
CLTF
2.584
SIGELTFEXP_SIGE->PJM
CLTF
0.077
NYPJM->LTFIMP_NY
CLTF
2.601
LGEELTFEXP_LGEE->PJM
CLTF
0.905
WECLTFEXP_WEC->PJM
CLTF
0.439

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 594_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:150.27 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:4839.45
MW Contribution:7.8
Bus #Bus NameTypeMW Contribution
3152261N ANNA2
50/50
35.375
3151771S ANNAG1
50/50
1.098
3151801S ANNAS2
50/50
0.564
3151761LOISA E
50/50
42.002
972183AH1-676 GEN
50/50
328.628
3151031BRUNSWICKG2
50/50
2.568
316044AC1-158 PL1
Solar/Wind Harmer
3.595
316450AC1-158 RIC
Solar/Wind Harmer
0.958
3147666LOUISA
Solar/Wind Harmer
1.12
3132273ORANGE
Solar/Wind Harmer
0.054
316170AC1-121 GEN2
Solar/Wind Harmer
0.236
316313AB2-026
Solar/Wind Harmer
0.12
316258AE1-075 C
Solar/Wind Harmer
0.144
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
2.888
970917AG2-570 GEN
Solar/Wind Harmer
16.604
316478AD1-087 GEN
Solar/Wind Harmer
0.59
316486AD2-202 GEN
Solar/Wind Harmer
0.173
970909AG2-566 GEN
Solar/Wind Harmer
1.755
3146926FARMVIL
Solar/Wind Harmer
0.095
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3147133PAMPLIN
Solar/Wind Harmer
0.486
971193AH1-056 GEN
Solar/Wind Harmer
9.427
963181AG1-167 GEN
Solar/Wind Harmer
0.617
3144293JTRSVLE
Adder
0.491
316365GEN2_N
Solar/Wind Harmer
0.345
959311AF2-222 GEN
Solar/Wind Harmer
13.6
3146776BUCKING
Solar/Wind Harmer
0.055
970257AG2-171 GEN
Solar/Wind Harmer
4.889
315785AD2-033 C
Solar/Wind Harmer
1.239
3147043LAWRENC
Solar/Wind Harmer
0.091
964241AG1-285 GEN
Solar/Wind Harmer
10.109
316131AB2-060 GEN
Solar/Wind Harmer
0.475
313506AB2-031 GEN
Solar/Wind Harmer
0.461
3142666NORTHAMPTON
Solar/Wind Harmer
0.145
944581AF1-123 GEN
Solar/Wind Harmer
32.61
944601AF1-125 GEN
Solar/Wind Harmer
32.107
3145796HORNRTN
Solar/Wind Harmer
0.577
3145796HORNRTN
Solar/Wind Harmer
0.144
3156081AA2-088 GEN
Solar/Wind Harmer
0.003
3146456SLIGO L269
Solar/Wind Harmer
0.143
971153AH1-033 GEN
Solar/Wind Harmer
1.656
315773AC2-141 GEN
Solar/Wind Harmer
5.232
3145893MURPHYS
Solar/Wind Harmer
0.239
3145893MURPHYS
Solar/Wind Harmer
0.143
3145273HOLLAND
Solar/Wind Harmer
0.107
316320Y1-086
Solar/Wind Harmer
0.001
957521AF2-046 GEN
Solar/Wind Harmer
10.626
961681AG1-008 GEN
Solar/Wind Harmer
10.626
3146263WOODLND
Solar/Wind Harmer
0.143
3151101ELIZAR3
Adder
13.236
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.142
3146173TUNIS
Solar/Wind Harmer
0.142
3144873MCLAUGH
Solar/Wind Harmer
0.004
3146626S HERTFORD
Solar/Wind Harmer
0.142
316463AE2-346 GEN
Solar/Wind Harmer
0.122
316140AB2-099
Solar/Wind Harmer
0.051
962331AG1-082 GEN
Solar/Wind Harmer
1.513
3146376EDENTON
Solar/Wind Harmer
0.142
315614AA2-178 GEN
Solar/Wind Harmer
0.807
3156021HOLLOMANSOL
Solar/Wind Harmer
0.639
316317KELFORD C
Solar/Wind Harmer
0.014
3145823KELFORD
Solar/Wind Harmer
0.141
970661AG2-428 GEN
Solar/Wind Harmer
2.977
3146206CASHIE
Solar/Wind Harmer
0.14
971157AH1-035 GEN
Solar/Wind Harmer
1.687
315737AD1-076 GEN
Solar/Wind Harmer
1.808
316083AB2-161 GEN
Solar/Wind Harmer
0.002
970659AG2-427 GEN
Solar/Wind Harmer
1.483
316210AC1-098 GEN
Solar/Wind Harmer
1.296
315813AE1-149 C
Solar/Wind Harmer
7.439
3144536CHRHLND
Solar/Wind Harmer
0.021
315724AD1-057 GEN
Solar/Wind Harmer
0.519
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
5.888
3145963POPLR C
Solar/Wind Harmer
0.138
316327AA2-057 GEN
Solar/Wind Harmer
0.207
3152251N ANNA1
50/50
35.378
3151791S ANNAG2
50/50
1.098
3151781S ANNAS1
50/50
0.564
3151741LOISA C
50/50
1.127
3151751LOISA D
50/50
20.602
970119AG2-088 GEN
50/50
29.412
315243AE2-183_GT3
50/50
3.266
3151051BRUNSWICKS1
50/50
5.329
3151021BRUNSWICKG1
50/50
2.568
971451AH1-221 GEN
50/50
7.799
316045AC1-158 PL2
Solar/Wind Harmer
11.495
3147666LOUISA
Solar/Wind Harmer
1.947
316192AB2-158 GEN
Solar/Wind Harmer
2.693
316254AC1-120 GEN1
Solar/Wind Harmer
0.471
3143226MDLTHAN
Solar/Wind Harmer
0.22
940641AE2-051 GEN
Solar/Wind Harmer
15.946
3143336POWHATN
Solar/Wind Harmer
3.398
970919AG2-571 GEN
Solar/Wind Harmer
6.642
970087AG2-069 GEN
Solar/Wind Harmer
14.871
939411AE1-173 GEN
Solar/Wind Harmer
79.115
316336AC2-165 C
Solar/Wind Harmer
0.007
3143526WINTERP
Solar/Wind Harmer
0.921
957481AF2-042 GEN
Solar/Wind Harmer
47.237
315693AD1-088 GEN
Solar/Wind Harmer
8.323
962491AG1-098 GEN
Solar/Wind Harmer
9.868
315683AE1-153 C
Solar/Wind Harmer
13.39
970937AG2-583 GEN
Solar/Wind Harmer
10.032
3146926FARMVIL
Solar/Wind Harmer
0.095
315687AD1-152 GEN
Solar/Wind Harmer
0.005
963171AG1-166 GEN
Solar/Wind Harmer
0.823
971563AH1-280 GEN
Solar/Wind Harmer
1.646
3144293JTRSVLE
Adder
0.491
316023GEN1_S
Solar/Wind Harmer
0.345
970685AG2-442 GEN
Solar/Wind Harmer
11.466
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.061
960081AF2-299 GEN
Solar/Wind Harmer
1.461
971795AH1-408 GEN
Solar/Wind Harmer
10.127
3147043LAWRENC
Adder
1.373
316237AB2-079_GEN
Solar/Wind Harmer
0.001
971065AG2-659 GEN
Solar/Wind Harmer
6.351
316129AC1-054 GEN
Solar/Wind Harmer
0.559
972003AH1-546 GEN
Solar/Wind Harmer
6.284
316011AB1-132 GEN
Solar/Wind Harmer
2.654
962571AG1-106 GEN
Solar/Wind Harmer
2.077
316190AA2-174 GEN
Solar/Wind Harmer
0
3145783HORNRTN
Solar/Wind Harmer
0.145
944591AF1-124 GEN
Solar/Wind Harmer
32.725
3145796HORNRTN
Solar/Wind Harmer
0.476
3145796HORNRTN
Solar/Wind Harmer
0.144
970401AG2-262 GEN
Solar/Wind Harmer
0.842
316388AE2-253 GEN
Solar/Wind Harmer
0.449
3146456SLIGO L269
Solar/Wind Harmer
0.143
316294AC1-161 GEN
Solar/Wind Harmer
2.482
3145893MURPHYS
Solar/Wind Harmer
0.572
3145893MURPHYS
Solar/Wind Harmer
0.636
316246AF1-032 C
Solar/Wind Harmer
0.064
3146263WOODLND
Solar/Wind Harmer
0.143
316093AE2-104_GEN
Solar/Wind Harmer
2.398
3146516WINFALL
Solar/Wind Harmer
0.461
3146516WINFALL
Solar/Wind Harmer
0.142
3146173TUNIS
Solar/Wind Harmer
0.142
316375AC2-012 GEN
Solar/Wind Harmer
0.004
3150981CHESPKA
Adder
1.776
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.142
3145683EARLEYS
Solar/Wind Harmer
0.141
3145663CRESWEL
Solar/Wind Harmer
0.395
971163AH1-040 GEN
Solar/Wind Harmer
11.283
3145823KELFORD
Solar/Wind Harmer
0.141
970661AG2-428 GEN
Solar/Wind Harmer
13.998
3146206CASHIE
Solar/Wind Harmer
0.14
971547AH1-271 GEN
Solar/Wind Harmer
3
316381AD1-082 GEN
Solar/Wind Harmer
0.146
970659AG2-427 GEN
Solar/Wind Harmer
6.78
316212AC1-099_GEN
Solar/Wind Harmer
0.722
315722AD1-056 GEN
Solar/Wind Harmer
0.876
3145963POPLR C
Solar/Wind Harmer
0.138
316174AB2-169 GEN
Solar/Wind Harmer
0.004
316072AD1-144
Solar/Wind Harmer
0.05
3146293MARTNCO
Solar/Wind Harmer
0.126
3146233WITAKRS
Solar/Wind Harmer
0.538
3145746EVERETS
Solar/Wind Harmer
0.134
3145746EVERETS
Solar/Wind Harmer
0.134
971377AH1-170 GEN
Solar/Wind Harmer
1.433
3147623JAMES R
Solar/Wind Harmer
0.311
316494AC1-189 GEN
Solar/Wind Harmer
0.453
316303AF2-085
50/50
3.922
315244AE2-183_ST
50/50
5.646
963041AG1-153 GEN
50/50
5.199
316164AC1-076 GEN
Solar/Wind Harmer
0.44
3147346CASHSCORNER
Solar/Wind Harmer
0.637
941031AE2-094 GEN
Solar/Wind Harmer
37.541
944011AF1-069 GEN
Solar/Wind Harmer
12.266
970673AG2-436 GEN
Solar/Wind Harmer
42.616
970673AG2-436 GEN
Solar/Wind Harmer
28.411
971967AH1-528 GEN
Solar/Wind Harmer
31.505
970085AG2-068 GEN
Solar/Wind Harmer
9.914
970581AG2-369 GEN
Solar/Wind Harmer
8.526
316233AE1-074 FULL
Solar/Wind Harmer
0.142
971281AH1-106 GEN
Solar/Wind Harmer
2.458
971283AH1-107 GEN
Solar/Wind Harmer
2.458
316315AB2-025 C
Solar/Wind Harmer
0.135
315814AE2-033 C
Solar/Wind Harmer
13.201
315657AE1-056 GEN
Solar/Wind Harmer
5.34
946301AF1-294 GEN
Solar/Wind Harmer
3.045
961791AG1-021 GEN
Solar/Wind Harmer
1.481
970285AG2-188 GEN
Solar/Wind Harmer
12.195
970683AG2-441 GEN
Solar/Wind Harmer
10.238
970681AG2-440 GEN
Solar/Wind Harmer
8.19
971845AH1-439 GEN
Solar/Wind Harmer
6.951
3144303KENBRDG
Solar/Wind Harmer
0.122
971443AH1-215 GEN
Solar/Wind Harmer
2.566
3143316POE
Solar/Wind Harmer
0.596
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316087AB2-174 GEN
Solar/Wind Harmer
0.004
970831AG2-522 GEN
Solar/Wind Harmer
6.33
3137643SOCKMAN
Solar/Wind Harmer
0.589
972205AH1-687 GEN
Adder
6.271
315652AC1-086 GEN
Solar/Wind Harmer
16.059
315607AA1-063A GEN
Solar/Wind Harmer
0.296
3146043SEABORD
Solar/Wind Harmer
0.145
3145796HORNRTN
Solar/Wind Harmer
0.461
3145796HORNRTN
Solar/Wind Harmer
0.058
965291AG1-394 GEN
Solar/Wind Harmer
0.639
957871AF2-081 GEN
Solar/Wind Harmer
7.137
319010AE1-072 C
Solar/Wind Harmer
0.721
3146406KITTY HAWK
Solar/Wind Harmer
0.018
3145893MURPHYS
Solar/Wind Harmer
0.386
3145893MURPHYS
Solar/Wind Harmer
0.143
313526AB2-022
Solar/Wind Harmer
0.077
316305AF2-043 C
Solar/Wind Harmer
0.001
316321Z2-027
Solar/Wind Harmer
0.027
3146396TANGLEW
Solar/Wind Harmer
0.393
3145176PASQUOTANK
Solar/Wind Harmer
0.088
3151081ELIZAR1
Adder
13.069
3151091ELIZAR2
Adder
12.842
3146486SUNBURY
Solar/Wind Harmer
0.142
3146486SUNBURY
Solar/Wind Harmer
0.142
315835AF2-110_GEN
Solar/Wind Harmer
0.978
3152611GOSPORTB
Adder
1.811
3152621GOSPORTC
Adder
1.537
3152601GOSPORTA
Adder
1.418
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3145513AHOSKIE
Solar/Wind Harmer
0.297
3145513AHOSKIE
Solar/Wind Harmer
0.142
316311AC2-079 GEN
Solar/Wind Harmer
4.069
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.097
3130156CHOWAN
Solar/Wind Harmer
0.142
3130156CHOWAN
Solar/Wind Harmer
0.142
3145683EARLEYS
Solar/Wind Harmer
0.283
3145683EARLEYS
Solar/Wind Harmer
0.141
3145683EARLEYS
Solar/Wind Harmer
0.141
315816AE2-034 GEN
Solar/Wind Harmer
0.605
316118AC1-105 GEN
Solar/Wind Harmer
0.363
3146206CASHIE
Solar/Wind Harmer
0.14
970601AG2-382 GEN
Solar/Wind Harmer
5.25
3130546PLYMOUTH
Solar/Wind Harmer
0.14
315732AD1-074 GEN1
Solar/Wind Harmer
0.807
315733AD1-074 GEN2
Solar/Wind Harmer
0.807
315735AD1-075 GEN1
Solar/Wind Harmer
0.404
3146033SCOT NK
Solar/Wind Harmer
0.56
3147173SINAI
Solar/Wind Harmer
0.138
3147243WELCO
Solar/Wind Harmer
0.086
316319Z2-044 C
Solar/Wind Harmer
0
316005AA1-067
Solar/Wind Harmer
0.144
3145746EVERETS
Solar/Wind Harmer
0.535
3145746EVERETS
Solar/Wind Harmer
0.134
3145746EVERETS
Solar/Wind Harmer
0.134
3145746EVERETS
Solar/Wind Harmer
0.134
970181AG2-120 GEN
Solar/Wind Harmer
1.673
957861AF2-080 GEN
Solar/Wind Harmer
5.784
316420AA1-050 GEN
Solar/Wind Harmer
0.004
3145573BETHELC
Solar/Wind Harmer
0.134
3145573BETHELC
Solar/Wind Harmer
0.134
971445AH1-216 GEN
Solar/Wind Harmer
9.249
971285AH1-108 GEN
Adder
0.983
971447AH1-217 GEN
Solar/Wind Harmer
3.898
972265AH1-717 GEN
Adder
9.747
3151201GRAVEL4
Adder
9.137
3151191GRAVEL3
Adder
9.022
3151211GRAVEL5
Adder
9.022
970865AG2-541 GEN
Solar/Wind Harmer
4.136
316369SG1_INVT
Solar/Wind Harmer
0.004
316132AB2-190 GEN1
Solar/Wind Harmer
0.619
270494AE1-108_GEN
Solar/Wind Harmer
1.368
961671AG1-007 GEN
Solar/Wind Harmer
0.02
3146083TARBORO
Solar/Wind Harmer
0.134
3145493TOT1
Solar/Wind Harmer
0.595
3145543BTLEBRO
Solar/Wind Harmer
0.134
3145543BTLEBRO
Solar/Wind Harmer
0.107
316359AB2-059 GEN
Solar/Wind Harmer
0.48
316049AB1-081 GEN
Solar/Wind Harmer
0.765
3142053HEARTS
Solar/Wind Harmer
0.235
3145336SMITFLD
Solar/Wind Harmer
0.528
316003AC1-222 GEN
Solar/Wind Harmer
0.003
3150851SPRUNCC
Adder
0.601
3151171GRAVELC
Adder
1.335
315671AE2-027_GEN
Solar/Wind Harmer
7.939
961611AG1-000B GEN
Solar/Wind Harmer
6.453
971647AH1-324 GEN
Solar/Wind Harmer
5.166
971069AG2-661 GEN
Solar/Wind Harmer
2.09
316458AB2-190 GEN2
Solar/Wind Harmer
0.619
970129AG2-093 GEN
Solar/Wind Harmer
3.27
3145933PARMELE
Solar/Wind Harmer
0.135
966801AG1-551 GEN
Solar/Wind Harmer
1.578
3146233WITAKRS
Solar/Wind Harmer
0.679
3146233WITAKRS
Solar/Wind Harmer
0.092
3138543CONSLDL
Solar/Wind Harmer
0.089
3145746EVERETS
Solar/Wind Harmer
0.134
3145746EVERETS
Solar/Wind Harmer
0.134
970221AG2-151 GEN
Solar/Wind Harmer
7.167
3146073TAR RVR
Solar/Wind Harmer
0.134
3146083TARBORO
Solar/Wind Harmer
0.134
3145543BTLEBRO
Solar/Wind Harmer
0.134
3145543BTLEBRO
Solar/Wind Harmer
0.134
971623AH1-311 GEN
Solar/Wind Harmer
0.267
961601AG1-000A GEN
Solar/Wind Harmer
9.498
315839AE2-212 C
Solar/Wind Harmer
0.001
3145336SMITFLD
Solar/Wind Harmer
0.053
3150861SPRUNCD
Adder
0.601
965281AG1-393 GEN
Solar/Wind Harmer
1.359
3151221GRAVEL6
Adder
9.127
3151171GRAVELC
Adder
1.756
971683AH1-343 GEN
Solar/Wind Harmer
4.614
961611AG1-000B GEN
Solar/Wind Harmer
3.281
316283AC2-100 C
Solar/Wind Harmer
0.239
315778AD1-151 GEN
Solar/Wind Harmer
9.406
970129AG2-093 GEN
Solar/Wind Harmer
6.948
971133AH1-012 GEN
50/50
10.055
3151731LOISA B
50/50
20.602
3151721LOISA A
50/50
20.496
970533AG2-339 GEN
50/50
18.118
970531AG2-338 GEN
50/50
7.247
315242AE2-183_GT2
50/50
3.266
315241AE2-183_GT1
50/50
3.246
972185AH1-677 GEN
50/50
11.773
3151041BRUNSWICKG3
50/50
2.568
972187AH1-678 GEN
50/50
5.893
316447AC1-158 HLD
Solar/Wind Harmer
7.902
966001AG1-469 GEN
Solar/Wind Harmer
0.166
971223AH1-071 GEN
Solar/Wind Harmer
2.353
970933AG2-581 GEN
Solar/Wind Harmer
15.316
315651AD1-115 GEN
Solar/Wind Harmer
0.006
3143526WINTERP
Solar/Wind Harmer
0.921
970099AG2-077 GEN
Solar/Wind Harmer
18.895
3144356SAPONY
Solar/Wind Harmer
1.401
971741AH1-377 GEN
Solar/Wind Harmer
16.521
970301AG2-198 GEN
Solar/Wind Harmer
7.019
3147133PAMPLIN
Solar/Wind Harmer
0.155
3147133PAMPLIN
Solar/Wind Harmer
0.124
958211AF2-115 GEN
Solar/Wind Harmer
1.852
963191AG1-168 GEN
Solar/Wind Harmer
0.617
3144293JTRSVLE
Adder
0.491
3144293JTRSVLE
Adder
0.414
3146776BUCKING
Solar/Wind Harmer
0.611
3146776BUCKING
Solar/Wind Harmer
0.049
316034AC1-036 C
Solar/Wind Harmer
0.011
970323AG2-213 GEN
Solar/Wind Harmer
6.518
971775AH1-396 GEN
Solar/Wind Harmer
0.244
313527AB2-043 GEN
Solar/Wind Harmer
0.002
939181AE1-148 GEN
Solar/Wind Harmer
7.211
316181AB2-040 GEN
Solar/Wind Harmer
0.216
3145593CAROLNA
Solar/Wind Harmer
0.146
3145593CAROLNA
Solar/Wind Harmer
0.146
966811AG1-552 GEN
Solar/Wind Harmer
1.582
3145593CAROLNA
Solar/Wind Harmer
0.182
3142666NORTHAMPTON
Solar/Wind Harmer
0.145
3142666NORTHAMPTON
Solar/Wind Harmer
0.145
3142666NORTHAMPTON
Solar/Wind Harmer
0.145
3142666NORTHAMPTON
Solar/Wind Harmer
0.087
316426AA2-053 GEN
Solar/Wind Harmer
0.49
3145783HORNRTN
Solar/Wind Harmer
2.577
3145783HORNRTN
Solar/Wind Harmer
2.062
3145783HORNRTN
Solar/Wind Harmer
0.644
3145783HORNRTN
Solar/Wind Harmer
0.258
962561AG1-105 GEN
Solar/Wind Harmer
6.941
3145796HORNRTN
Solar/Wind Harmer
0.432
3145506HICKORY
Solar/Wind Harmer
0.574
3145506HICKORY
Solar/Wind Harmer
0.344
3145506HICKORY
Solar/Wind Harmer
0.086
316185AD1-033 GEN
Solar/Wind Harmer
0.004
964791AG1-342 GEN
Solar/Wind Harmer
2.754
316339AD2-160 GEN
Solar/Wind Harmer
0.233
3146843MT LREL
Solar/Wind Harmer
0.143
3146843MT LREL
Solar/Wind Harmer
0.143
316018AA1-139 ULT2
Solar/Wind Harmer
0.004
316017AA1-139 ULT1
Solar/Wind Harmer
0.08
3137176SLIGO L2192
Solar/Wind Harmer
0.57
3146456SLIGO L269
Solar/Wind Harmer
2.535
3130086AYDLETT
Solar/Wind Harmer
0.573
315742AE1-103 GEN
Solar/Wind Harmer
0.002
3145893MURPHYS
Solar/Wind Harmer
0.957
3145893MURPHYS
Solar/Wind Harmer
0.257
3142956BIRDNECK
Solar/Wind Harmer
0
3146386ELIZ CT
Solar/Wind Harmer
0.143
316316AC1-027 C
Solar/Wind Harmer
0.137
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.142
3146516WINFALL
Solar/Wind Harmer
0.142
3146516WINFALL
Solar/Wind Harmer
0.142
3146173TUNIS
Solar/Wind Harmer
0.142
3146173TUNIS
Solar/Wind Harmer
0.142
316036AC1-147 C
Solar/Wind Harmer
0.026
3150991CHESPKB
Adder
1.49
3150991CHESPKB
Adder
1.454
3146626S HERTFORD
Solar/Wind Harmer
0.142
3146626S HERTFORD
Solar/Wind Harmer
0.142
3146376EDENTON
Solar/Wind Harmer
0.63
3146376EDENTON
Solar/Wind Harmer
0.63
316065AD1-022 GEN
Solar/Wind Harmer
6.472
970657AG2-426 GEN
Solar/Wind Harmer
4.92
970657AG2-426 GEN
Solar/Wind Harmer
1.032
316274AC1-208 GEN
Solar/Wind Harmer
0.727
3145933PARMELE
Solar/Wind Harmer
0.271
3145933PARMELE
Solar/Wind Harmer
0.135
971489AH1-241 GEN
Solar/Wind Harmer
7.167
3145493TOT1
Solar/Wind Harmer
0.31
3145453TOT5
Solar/Wind Harmer
0.186
3145603CNETO
Solar/Wind Harmer
0.124
316263AC1-034 GEN
Solar/Wind Harmer
5.078
961601AG1-000A GEN
Solar/Wind Harmer
2.374
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316222AC1-221 GEN
Solar/Wind Harmer
0.509
316240AF1-291 C
Solar/Wind Harmer
0.001
316033AB2-134 GEN
Solar/Wind Harmer
0.007
315697AD1-025 GEN
Solar/Wind Harmer
0.134
944641AF1-129 GEN
Adder
56.042
LAGNLTFEXP_LAGN->PJM
CLTF
5.7
CBM South 2LTFEXP_CBM-S2->PJM
CBM
19.49
TVALTFEXP_TVA->PJM
CLTF
2.869
CPLELTFEXP_CPLE->PJM
CLTF
9.114
CBM West 2LTFEXP_CBM-W2->PJM
CBM
28.291
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.38
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.621
MECLTFEXP_MEC->PJM
CLTF
2.309
SIGELTFEXP_SIGE->PJM
CLTF
0.069
NYPJM->LTFIMP_NY
CLTF
2.592
LGEELTFEXP_LGEE->PJM
CLTF
0.801
WECLTFEXP_WEC->PJM
CLTF
0.384

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 573_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:147.45 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:4748.6
MW Contribution:8.19
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
4.114
315244AE2-183_ST
50/50
5.93
963041AG1-153 GEN
50/50
5.461
3147346CASHSCORNER
Solar/Wind Harmer
0.597
941031AE2-094 GEN
Solar/Wind Harmer
39.425
944011AF1-069 GEN
Solar/Wind Harmer
12.882
970673AG2-436 GEN
Solar/Wind Harmer
44.756
970673AG2-436 GEN
Solar/Wind Harmer
29.837
971967AH1-528 GEN
Solar/Wind Harmer
33.079
970085AG2-068 GEN
Solar/Wind Harmer
10.416
970581AG2-369 GEN
Solar/Wind Harmer
8.958
316233AE1-074 FULL
Solar/Wind Harmer
0.15
971281AH1-106 GEN
Solar/Wind Harmer
2.6
971283AH1-107 GEN
Solar/Wind Harmer
2.6
316315AB2-025 C
Solar/Wind Harmer
0.143
315814AE2-033 C
Solar/Wind Harmer
13.959
315657AE1-056 GEN
Solar/Wind Harmer
5.562
946301AF1-294 GEN
Solar/Wind Harmer
3.175
961791AG1-021 GEN
Solar/Wind Harmer
1.544
3143316POE
Solar/Wind Harmer
0.635
970683AG2-441 GEN
Solar/Wind Harmer
10.688
970681AG2-440 GEN
Solar/Wind Harmer
8.55
3144303KENBRDG
Solar/Wind Harmer
0.128
971443AH1-215 GEN
Solar/Wind Harmer
2.682
970285AG2-188 GEN
Solar/Wind Harmer
12.58
316087AB2-174 GEN
Solar/Wind Harmer
0.005
971845AH1-439 GEN
Solar/Wind Harmer
7.164
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
970831AG2-522 GEN
Solar/Wind Harmer
6.67
3137643SOCKMAN
Solar/Wind Harmer
0.622
315652AC1-086 GEN
Solar/Wind Harmer
16.994
315607AA1-063A GEN
Solar/Wind Harmer
0.314
3146043SEABORD
Solar/Wind Harmer
0.153
957871AF2-081 GEN
Solar/Wind Harmer
7.61
319010AE1-072 C
Solar/Wind Harmer
0.769
3146406KITTY HAWK
Solar/Wind Harmer
0.019
3145796HORNRTN
Solar/Wind Harmer
0.488
3145796HORNRTN
Solar/Wind Harmer
0.061
965291AG1-394 GEN
Solar/Wind Harmer
0.678
313526AB2-022
Solar/Wind Harmer
0.082
316305AF2-043 C
Solar/Wind Harmer
0.001
3151081ELIZAR1
Adder
13.946
3151091ELIZAR2
Adder
13.704
316321Z2-027
Solar/Wind Harmer
0.028
3146396TANGLEW
Solar/Wind Harmer
0.419
3145176PASQUOTANK
Solar/Wind Harmer
0.094
315835AF2-110_GEN
Solar/Wind Harmer
1.043
3146486SUNBURY
Solar/Wind Harmer
0.152
3146486SUNBURY
Solar/Wind Harmer
0.152
3152611GOSPORTB
Adder
1.933
3152621GOSPORTC
Adder
1.641
3152601GOSPORTA
Adder
1.513
3145893MURPHYS
Solar/Wind Harmer
0.41
3145893MURPHYS
Solar/Wind Harmer
0.152
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
316311AC2-079 GEN
Solar/Wind Harmer
4.34
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.104
3130156CHOWAN
Solar/Wind Harmer
0.151
3130156CHOWAN
Solar/Wind Harmer
0.151
3145513AHOSKIE
Solar/Wind Harmer
0.314
3145513AHOSKIE
Solar/Wind Harmer
0.15
972205AH1-687 GEN
Adder
6.411
3145683EARLEYS
Solar/Wind Harmer
0.3
3145683EARLEYS
Solar/Wind Harmer
0.15
3145683EARLEYS
Solar/Wind Harmer
0.15
315816AE2-034 GEN
Solar/Wind Harmer
0.644
3130546PLYMOUTH
Solar/Wind Harmer
0.149
3146206CASHIE
Solar/Wind Harmer
0.149
970601AG2-382 GEN
Solar/Wind Harmer
5.575
315732AD1-074 GEN1
Solar/Wind Harmer
0.858
315733AD1-074 GEN2
Solar/Wind Harmer
0.858
315735AD1-075 GEN1
Solar/Wind Harmer
0.429
3146033SCOT NK
Solar/Wind Harmer
0.593
316118AC1-105 GEN
Solar/Wind Harmer
0.382
3147173SINAI
Solar/Wind Harmer
0.145
3147243WELCO
Solar/Wind Harmer
0.091
316319Z2-044 C
Solar/Wind Harmer
0
316005AA1-067
Solar/Wind Harmer
0.153
3145746EVERETS
Solar/Wind Harmer
0.567
3145746EVERETS
Solar/Wind Harmer
0.142
3145746EVERETS
Solar/Wind Harmer
0.142
3145746EVERETS
Solar/Wind Harmer
0.142
970181AG2-120 GEN
Solar/Wind Harmer
1.773
957861AF2-080 GEN
Solar/Wind Harmer
6.125
316420AA1-050 GEN
Solar/Wind Harmer
0.005
3145573BETHELC
Solar/Wind Harmer
0.142
3145573BETHELC
Solar/Wind Harmer
0.142
971445AH1-216 GEN
Solar/Wind Harmer
9.913
971285AH1-108 GEN
Adder
1.055
972265AH1-717 GEN
Adder
10.474
3151201GRAVEL4
Adder
9.819
3151191GRAVEL3
Adder
9.695
3151211GRAVEL5
Adder
9.695
971447AH1-217 GEN
Solar/Wind Harmer
3.983
316369SG1_INVT
Solar/Wind Harmer
0.005
970865AG2-541 GEN
Solar/Wind Harmer
4.353
316132AB2-190 GEN1
Solar/Wind Harmer
0.669
270494AE1-108_GEN
Solar/Wind Harmer
1.404
316123AC1-075 GEN
Solar/Wind Harmer
0.154
970165AG2-112 GEN
Solar/Wind Harmer
0.913
970163AG2-111 GEN
Solar/Wind Harmer
0.871
3152251N ANNA1
50/50
36.46
3151791S ANNAG2
50/50
1.04
3151781S ANNAS1
50/50
0.534
3151741LOISA C
50/50
1.06
3151751LOISA D
50/50
19.381
970119AG2-088 GEN
50/50
30.855
315243AE2-183_GT3
50/50
3.43
3151051BRUNSWICKS1
50/50
5.597
3151021BRUNSWICKG1
50/50
2.697
971451AH1-221 GEN
50/50
8.191
3147666LOUISA
Solar/Wind Harmer
1.943
316192AB2-158 GEN
Solar/Wind Harmer
2.682
3143226MDLTHAN
Solar/Wind Harmer
0.231
940641AE2-051 GEN
Solar/Wind Harmer
16.781
3143336POWHATN
Solar/Wind Harmer
3.536
970919AG2-571 GEN
Solar/Wind Harmer
6.978
939411AE1-173 GEN
Solar/Wind Harmer
83.474
970087AG2-069 GEN
Solar/Wind Harmer
15.624
316336AC2-165 C
Solar/Wind Harmer
0.007
3143526WINTERP
Solar/Wind Harmer
0.974
957481AF2-042 GEN
Solar/Wind Harmer
49.548
315693AD1-088 GEN
Solar/Wind Harmer
8.718
962491AG1-098 GEN
Solar/Wind Harmer
10.335
970937AG2-583 GEN
Solar/Wind Harmer
10.339
315687AD1-152 GEN
Solar/Wind Harmer
0.005
3146926FARMVIL
Solar/Wind Harmer
0.098
316023GEN1_S
Solar/Wind Harmer
0.365
963171AG1-166 GEN
Solar/Wind Harmer
0.858
971563AH1-280 GEN
Solar/Wind Harmer
1.716
3144293JTRSVLE
Adder
0.512
960081AF2-299 GEN
Solar/Wind Harmer
1.543
970685AG2-442 GEN
Solar/Wind Harmer
11.971
971795AH1-408 GEN
Solar/Wind Harmer
10.682
3147043LAWRENC
Adder
1.448
316237AB2-079_GEN
Solar/Wind Harmer
0.001
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.063
971065AG2-659 GEN
Solar/Wind Harmer
6.688
316129AC1-054 GEN
Solar/Wind Harmer
0.589
316011AB1-132 GEN
Solar/Wind Harmer
2.809
962571AG1-106 GEN
Solar/Wind Harmer
2.198
944591AF1-124 GEN
Solar/Wind Harmer
34.895
316190AA2-174 GEN
Solar/Wind Harmer
0
3145783HORNRTN
Solar/Wind Harmer
0.153
316388AE2-253 GEN
Solar/Wind Harmer
0.479
316294AC1-161 GEN
Solar/Wind Harmer
2.649
3146456SLIGO L269
Solar/Wind Harmer
0.153
3145796HORNRTN
Solar/Wind Harmer
0.503
3145796HORNRTN
Solar/Wind Harmer
0.152
315683AE1-153 C
Solar/Wind Harmer
12.128
316246AF1-032 C
Solar/Wind Harmer
0.069
316093AE2-104_GEN
Solar/Wind Harmer
2.556
316375AC2-012 GEN
Solar/Wind Harmer
0.004
3150981CHESPKA
Adder
1.895
3145893MURPHYS
Solar/Wind Harmer
0.607
3145893MURPHYS
Solar/Wind Harmer
0.674
3146516WINFALL
Solar/Wind Harmer
0.491
3146516WINFALL
Solar/Wind Harmer
0.152
972003AH1-546 GEN
Solar/Wind Harmer
6.434
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3146263WOODLND
Solar/Wind Harmer
0.151
3146173TUNIS
Solar/Wind Harmer
0.151
3130156CHOWAN
Solar/Wind Harmer
0.151
970401AG2-262 GEN
Solar/Wind Harmer
0.884
970661AG2-428 GEN
Solar/Wind Harmer
14.943
3145683EARLEYS
Solar/Wind Harmer
0.15
3145663CRESWEL
Solar/Wind Harmer
0.42
971163AH1-040 GEN
Solar/Wind Harmer
11.998
316381AD1-082 GEN
Solar/Wind Harmer
0.156
970659AG2-427 GEN
Solar/Wind Harmer
7.24
3146206CASHIE
Solar/Wind Harmer
0.149
971547AH1-271 GEN
Solar/Wind Harmer
3.186
3145823KELFORD
Solar/Wind Harmer
0.149
316212AC1-099_GEN
Solar/Wind Harmer
0.765
316072AD1-144
Solar/Wind Harmer
0.053
315722AD1-056 GEN
Solar/Wind Harmer
0.927
3145963POPLR C
Solar/Wind Harmer
0.146
316174AB2-169 GEN
Solar/Wind Harmer
0.004
3146293MARTNCO
Solar/Wind Harmer
0.133
3146233WITAKRS
Solar/Wind Harmer
0.569
3145746EVERETS
Solar/Wind Harmer
0.142
3145746EVERETS
Solar/Wind Harmer
0.142
316494AC1-189 GEN
Solar/Wind Harmer
0.48
961671AG1-007 GEN
Solar/Wind Harmer
0.022
3146083TARBORO
Solar/Wind Harmer
0.142
3145493TOT1
Solar/Wind Harmer
0.63
3145336SMITFLD
Solar/Wind Harmer
0.565
3145543BTLEBRO
Solar/Wind Harmer
0.141
3145543BTLEBRO
Solar/Wind Harmer
0.113
316359AB2-059 GEN
Solar/Wind Harmer
0.508
316049AB1-081 GEN
Solar/Wind Harmer
0.809
3142053HEARTS
Solar/Wind Harmer
0.249
3150851SPRUNCC
Adder
0.645
316003AC1-222 GEN
Solar/Wind Harmer
0.004
971377AH1-170 GEN
Solar/Wind Harmer
1.465
3147623JAMES R
Solar/Wind Harmer
0.318
3151171GRAVELC
Adder
1.435
315671AE2-027_GEN
Solar/Wind Harmer
8.542
961611AG1-000B GEN
Solar/Wind Harmer
6.943
971647AH1-324 GEN
Solar/Wind Harmer
5.564
971069AG2-661 GEN
Solar/Wind Harmer
2.256
316458AB2-190 GEN2
Solar/Wind Harmer
0.669
970129AG2-093 GEN
Solar/Wind Harmer
3.534
3138126ROCKLANDING
Solar/Wind Harmer
0.055
3142543TWELFTH
Solar/Wind Harmer
0.011
3152261N ANNA2
50/50
36.457
3151771S ANNAG1
50/50
1.04
3151801S ANNAS2
50/50
0.534
3151761LOISA E
50/50
39.513
972183AH1-676 GEN
50/50
307.587
3151031BRUNSWICKG2
50/50
2.697
3147666LOUISA
Solar/Wind Harmer
1.117
316313AB2-026
Solar/Wind Harmer
0.125
316258AE1-075 C
Solar/Wind Harmer
0.15
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
3.006
970917AG2-570 GEN
Solar/Wind Harmer
17.445
316478AD1-087 GEN
Solar/Wind Harmer
0.619
316486AD2-202 GEN
Solar/Wind Harmer
0.182
970909AG2-566 GEN
Solar/Wind Harmer
1.827
3146926FARMVIL
Solar/Wind Harmer
0.098
316365GEN2_N
Solar/Wind Harmer
0.365
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3147133PAMPLIN
Solar/Wind Harmer
0.506
971193AH1-056 GEN
Solar/Wind Harmer
9.82
963181AG1-167 GEN
Solar/Wind Harmer
0.644
3144293JTRSVLE
Adder
0.512
3147043LAWRENC
Solar/Wind Harmer
0.096
959311AF2-222 GEN
Solar/Wind Harmer
14.213
970257AG2-171 GEN
Solar/Wind Harmer
5.111
315785AD2-033 C
Solar/Wind Harmer
1.297
964241AG1-285 GEN
Solar/Wind Harmer
10.591
316131AB2-060 GEN
Solar/Wind Harmer
0.498
313506AB2-031 GEN
Solar/Wind Harmer
0.487
3146776BUCKING
Solar/Wind Harmer
0.057
944581AF1-123 GEN
Solar/Wind Harmer
34.771
944601AF1-125 GEN
Solar/Wind Harmer
34.236
3142666NORTHAMPTON
Solar/Wind Harmer
0.154
3132273ORANGE
Solar/Wind Harmer
0.031
315773AC2-141 GEN
Solar/Wind Harmer
5.584
3146456SLIGO L269
Solar/Wind Harmer
0.153
971153AH1-033 GEN
Solar/Wind Harmer
1.766
3145796HORNRTN
Solar/Wind Harmer
0.61
3145796HORNRTN
Solar/Wind Harmer
0.152
3156081AA2-088 GEN
Solar/Wind Harmer
0.004
316320Y1-086
Solar/Wind Harmer
0.001
3151101ELIZAR3
Adder
14.124
3145273HOLLAND
Solar/Wind Harmer
0.114
3144873MCLAUGH
Solar/Wind Harmer
0.004
316435W1029_GEN3
Solar/Wind Harmer
0.001
3145893MURPHYS
Solar/Wind Harmer
0.254
3145893MURPHYS
Solar/Wind Harmer
0.152
3146516WINFALL
Solar/Wind Harmer
0.152
3146626S HERTFORD
Solar/Wind Harmer
0.151
957521AF2-046 GEN
Solar/Wind Harmer
11.271
961681AG1-008 GEN
Solar/Wind Harmer
11.271
3146263WOODLND
Solar/Wind Harmer
0.151
3146173TUNIS
Solar/Wind Harmer
0.151
3146376EDENTON
Solar/Wind Harmer
0.151
316463AE2-346 GEN
Solar/Wind Harmer
0.129
316140AB2-099
Solar/Wind Harmer
0.054
962331AG1-082 GEN
Solar/Wind Harmer
1.604
970661AG2-428 GEN
Solar/Wind Harmer
3.178
315614AA2-178 GEN
Solar/Wind Harmer
0.858
316083AB2-161 GEN
Solar/Wind Harmer
0.002
970659AG2-427 GEN
Solar/Wind Harmer
1.584
3156021HOLLOMANSOL
Solar/Wind Harmer
0.678
971157AH1-035 GEN
Solar/Wind Harmer
1.793
3146206CASHIE
Solar/Wind Harmer
0.149
315737AD1-076 GEN
Solar/Wind Harmer
1.921
316317KELFORD C
Solar/Wind Harmer
0.014
3145823KELFORD
Solar/Wind Harmer
0.149
315813AE1-149 C
Solar/Wind Harmer
7.948
3144536CHRHLND
Solar/Wind Harmer
0.022
316210AC1-098 GEN
Solar/Wind Harmer
1.371
315724AD1-057 GEN
Solar/Wind Harmer
0.549
3145963POPLR C
Solar/Wind Harmer
0.146
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
6.188
316327AA2-057 GEN
Solar/Wind Harmer
0.219
3145933PARMELE
Solar/Wind Harmer
0.144
966801AG1-551 GEN
Solar/Wind Harmer
1.673
3146233WITAKRS
Solar/Wind Harmer
0.718
3146233WITAKRS
Solar/Wind Harmer
0.097
3138543CONSLDL
Solar/Wind Harmer
0.094
3145746EVERETS
Solar/Wind Harmer
0.142
3145746EVERETS
Solar/Wind Harmer
0.142
315839AE2-212 C
Solar/Wind Harmer
0.001
3146073TAR RVR
Solar/Wind Harmer
0.142
3146083TARBORO
Solar/Wind Harmer
0.142
3145336SMITFLD
Solar/Wind Harmer
0.057
3145543BTLEBRO
Solar/Wind Harmer
0.141
3145543BTLEBRO
Solar/Wind Harmer
0.141
971623AH1-311 GEN
Solar/Wind Harmer
0.283
961601AG1-000A GEN
Solar/Wind Harmer
10.046
3150861SPRUNCD
Adder
0.645
970221AG2-151 GEN
Solar/Wind Harmer
7.325
965281AG1-393 GEN
Solar/Wind Harmer
1.459
3151221GRAVEL6
Adder
9.808
3151171GRAVELC
Adder
1.887
961611AG1-000B GEN
Solar/Wind Harmer
3.53
971683AH1-343 GEN
Solar/Wind Harmer
4.854
316283AC2-100 C
Solar/Wind Harmer
0.252
315778AD1-151 GEN
Solar/Wind Harmer
10.15
970129AG2-093 GEN
Solar/Wind Harmer
7.509
3144216WINCHST
Adder
0.455
970133AG2-095 GEN
Solar/Wind Harmer
1.157
3150921YORKTN3
Adder
2.978
971133AH1-012 GEN
50/50
10.162
3151731LOISA B
50/50
19.381
3151721LOISA A
50/50
19.281
970533AG2-339 GEN
50/50
19.027
970531AG2-338 GEN
50/50
7.611
315242AE2-183_GT2
50/50
3.43
315241AE2-183_GT1
50/50
3.409
972185AH1-677 GEN
50/50
12.365
3151041BRUNSWICKG3
50/50
2.697
972187AH1-678 GEN
50/50
6.189
966001AG1-469 GEN
Solar/Wind Harmer
0.142
971223AH1-071 GEN
Solar/Wind Harmer
2.468
970933AG2-581 GEN
Solar/Wind Harmer
16.076
3143526WINTERP
Solar/Wind Harmer
0.974
970099AG2-077 GEN
Solar/Wind Harmer
19.819
3144356SAPONY
Solar/Wind Harmer
1.482
971741AH1-377 GEN
Solar/Wind Harmer
17.227
970301AG2-198 GEN
Solar/Wind Harmer
7.308
3147133PAMPLIN
Solar/Wind Harmer
0.161
3147133PAMPLIN
Solar/Wind Harmer
0.129
958211AF2-115 GEN
Solar/Wind Harmer
1.931
963191AG1-168 GEN
Solar/Wind Harmer
0.644
3144293JTRSVLE
Adder
0.512
3144293JTRSVLE
Adder
0.431
316034AC1-036 C
Solar/Wind Harmer
0.012
970323AG2-213 GEN
Solar/Wind Harmer
6.815
971775AH1-396 GEN
Solar/Wind Harmer
0.256
313527AB2-043 GEN
Solar/Wind Harmer
0.002
939181AE1-148 GEN
Solar/Wind Harmer
7.578
316181AB2-040 GEN
Solar/Wind Harmer
0.229
3146776BUCKING
Solar/Wind Harmer
0.63
3146776BUCKING
Solar/Wind Harmer
0.051
3145593CAROLNA
Solar/Wind Harmer
0.154
3145593CAROLNA
Solar/Wind Harmer
0.154
966811AG1-552 GEN
Solar/Wind Harmer
1.673
3145593CAROLNA
Solar/Wind Harmer
0.192
3142666NORTHAMPTON
Solar/Wind Harmer
0.154
3142666NORTHAMPTON
Solar/Wind Harmer
0.154
3142666NORTHAMPTON
Solar/Wind Harmer
0.154
3142666NORTHAMPTON
Solar/Wind Harmer
0.092
316426AA2-053 GEN
Solar/Wind Harmer
0.518
3145783HORNRTN
Solar/Wind Harmer
2.725
3145783HORNRTN
Solar/Wind Harmer
2.18
3145783HORNRTN
Solar/Wind Harmer
0.681
3145783HORNRTN
Solar/Wind Harmer
0.273
316185AD1-033 GEN
Solar/Wind Harmer
0.004
3145506HICKORY
Solar/Wind Harmer
0.612
3145506HICKORY
Solar/Wind Harmer
0.367
3145506HICKORY
Solar/Wind Harmer
0.092
316339AD2-160 GEN
Solar/Wind Harmer
0.248
316018AA1-139 ULT2
Solar/Wind Harmer
0.004
316017AA1-139 ULT1
Solar/Wind Harmer
0.085
3137176SLIGO L2192
Solar/Wind Harmer
0.608
3146456SLIGO L269
Solar/Wind Harmer
2.703
3130086AYDLETT
Solar/Wind Harmer
0.61
3145796HORNRTN
Solar/Wind Harmer
0.458
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.146
3146386ELIZ CT
Solar/Wind Harmer
0.152
315742AE1-103 GEN
Solar/Wind Harmer
0.002
316036AC1-147 C
Solar/Wind Harmer
0.028
3150991CHESPKB
Adder
1.59
3150991CHESPKB
Adder
1.552
962561AG1-105 GEN
Solar/Wind Harmer
7.287
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3145893MURPHYS
Solar/Wind Harmer
1.015
3145893MURPHYS
Solar/Wind Harmer
0.273
3146516WINFALL
Solar/Wind Harmer
0.152
3146516WINFALL
Solar/Wind Harmer
0.152
3146516WINFALL
Solar/Wind Harmer
0.152
3146626S HERTFORD
Solar/Wind Harmer
0.151
3146626S HERTFORD
Solar/Wind Harmer
0.151
3146173TUNIS
Solar/Wind Harmer
0.151
3146173TUNIS
Solar/Wind Harmer
0.151
3146376EDENTON
Solar/Wind Harmer
0.67
3146376EDENTON
Solar/Wind Harmer
0.67
964791AG1-342 GEN
Solar/Wind Harmer
2.892
3146843MT LREL
Solar/Wind Harmer
0.15
3146843MT LREL
Solar/Wind Harmer
0.15
970657AG2-426 GEN
Solar/Wind Harmer
5.253
970657AG2-426 GEN
Solar/Wind Harmer
1.101
316065AD1-022 GEN
Solar/Wind Harmer
6.875
316274AC1-208 GEN
Solar/Wind Harmer
0.769
3145933PARMELE
Solar/Wind Harmer
0.287
3145933PARMELE
Solar/Wind Harmer
0.144
3145493TOT1
Solar/Wind Harmer
0.328
3145453TOT5
Solar/Wind Harmer
0.197
3145603CNETO
Solar/Wind Harmer
0.131
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316263AC1-034 GEN
Solar/Wind Harmer
5.37
961601AG1-000A GEN
Solar/Wind Harmer
2.512
971489AH1-241 GEN
Solar/Wind Harmer
7.325
316240AF1-291 C
Solar/Wind Harmer
0.001
316222AC1-221 GEN
Solar/Wind Harmer
0.537
316033AB2-134 GEN
Solar/Wind Harmer
0.008
315697AD1-025 GEN
Solar/Wind Harmer
0.144
944641AF1-129 GEN
Adder
60.502
LAGNLTFEXP_LAGN->PJM
CLTF
6.172
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.668
TVALTFEXP_TVA->PJM
CLTF
3.105
CPLELTFEXP_CPLE->PJM
CLTF
9.633
CBM West 2LTFEXP_CBM-W2->PJM
CBM
31.022
CBM West 1LTFEXP_CBM-W1->PJM
CBM
14.582
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.459
MECLTFEXP_MEC->PJM
CLTF
2.598
SIGELTFEXP_SIGE->PJM
CLTF
0.077
NYPJM->LTFIMP_NY
CLTF
2.601
LGEELTFEXP_LGEE->PJM
CLTF
0.913
WECLTFEXP_WEC->PJM
CLTF
0.444

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: SPOTS H1T594_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.78 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:5310.49
MW Contribution:8.15
Bus #Bus NameTypeMW Contribution
3152251N ANNA1
50/50
36.417
3151791S ANNAG2
50/50
1.042
3151781S ANNAS1
50/50
0.535
3151741LOISA C
50/50
1.062
3151751LOISA D
50/50
19.419
970119AG2-088 GEN
50/50
30.719
315243AE2-183_GT3
50/50
3.412
3151051BRUNSWICKS1
50/50
5.568
3151021BRUNSWICKG1
50/50
2.683
971451AH1-221 GEN
50/50
8.148
316045AC1-158 PL2
Solar/Wind Harmer
27.544
3147666LOUISA
Solar/Wind Harmer
-0.217
316192AB2-158 GEN
Solar/Wind Harmer
6.343
3143226MDLTHAN
Solar/Wind Harmer
-0.026
940641AE2-051 GEN
Solar/Wind Harmer
21.983
316303AF2-085
50/50
4.096
315244AE2-183_ST
50/50
5.899
963041AG1-153 GEN
50/50
5.432
3147346CASHSCORNER
Solar/Wind Harmer
0.449
941031AE2-094 GEN
Solar/Wind Harmer
44.868
944011AF1-069 GEN
Solar/Wind Harmer
14.059
970673AG2-436 GEN
Solar/Wind Harmer
49.264
970673AG2-436 GEN
Solar/Wind Harmer
24.944
971967AH1-528 GEN
Solar/Wind Harmer
43.441
970085AG2-068 GEN
Solar/Wind Harmer
13.637
970581AG2-369 GEN
Solar/Wind Harmer
11.728
316233AE1-074 FULL
Solar/Wind Harmer
0.564
971281AH1-106 GEN
Solar/Wind Harmer
3.405
971283AH1-107 GEN
Solar/Wind Harmer
3.405
316315AB2-025 C
Solar/Wind Harmer
0.534
315814AE2-033 C
Solar/Wind Harmer
18.349
315657AE1-056 GEN
Solar/Wind Harmer
6.751
946301AF1-294 GEN
Solar/Wind Harmer
4.601
961791AG1-021 GEN
Solar/Wind Harmer
2.245
946281AF1-292 GEN
Solar/Wind Harmer
0.402
3143316POE
Solar/Wind Harmer
-0.07
970683AG2-441 GEN
Solar/Wind Harmer
13.979
970681AG2-440 GEN
Solar/Wind Harmer
11.183
3144303KENBRDG
Solar/Wind Harmer
-0.014
971443AH1-215 GEN
Solar/Wind Harmer
3.508
970285AG2-188 GEN
Solar/Wind Harmer
15.538
316087AB2-174 GEN
Solar/Wind Harmer
2.524
971845AH1-439 GEN
Solar/Wind Harmer
9.375
316239AB2-077_GEN
Solar/Wind Harmer
0.531
316238AB2-078_GEN
Solar/Wind Harmer
0.531
970831AG2-522 GEN
Solar/Wind Harmer
8.718
3137643SOCKMAN
Solar/Wind Harmer
-0.069
315652AC1-086 GEN
Solar/Wind Harmer
19.393
315607AA1-063A GEN
Solar/Wind Harmer
1.731
3146043SEABORD
Solar/Wind Harmer
-0.017
957871AF2-081 GEN
Solar/Wind Harmer
8.527
319010AE1-072 C
Solar/Wind Harmer
3.447
3146406KITTY HAWK
Solar/Wind Harmer
0.014
3145796HORNRTN
Solar/Wind Harmer
-0.054
3145796HORNRTN
Solar/Wind Harmer
-0.007
965291AG1-394 GEN
Solar/Wind Harmer
1.51
313526AB2-022
Solar/Wind Harmer
0.458
316305AF2-043 C
Solar/Wind Harmer
0.512
3151081ELIZAR1
Adder
13.847
3151091ELIZAR2
Adder
13.607
316321Z2-027
Solar/Wind Harmer
0.458
3145176PASQUOTANK
Solar/Wind Harmer
-0.01
3146396TANGLEW
Solar/Wind Harmer
0.312
315835AF2-110_GEN
Solar/Wind Harmer
2.119
3146486SUNBURY
Solar/Wind Harmer
-0.017
3146486SUNBURY
Solar/Wind Harmer
-0.017
3152611GOSPORTB
Adder
1.919
3152621GOSPORTC
Adder
1.629
3152601GOSPORTA
Adder
1.503
316318V4-068
Solar/Wind Harmer
0.422
3145893MURPHYS
Solar/Wind Harmer
-0.045
3145893MURPHYS
Solar/Wind Harmer
-0.017
316311AC2-079 GEN
Solar/Wind Harmer
8.505
315611Z1-036_GEN2
Solar/Wind Harmer
4.166
315833AF1-017_GEN
Solar/Wind Harmer
3.202
316349AD2-085 GEN
Solar/Wind Harmer
1.5
3130156CHOWAN
Solar/Wind Harmer
-0.017
3130156CHOWAN
Solar/Wind Harmer
-0.017
3145513AHOSKIE
Solar/Wind Harmer
0.146
961941AG1-037 GEN
Solar/Wind Harmer
0.126
3145513AHOSKIE
Solar/Wind Harmer
-0.017
972205AH1-687 GEN
Adder
6.372
315816AE2-034 GEN
Solar/Wind Harmer
1.353
3145683EARLEYS
Solar/Wind Harmer
-0.033
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.017
3130546PLYMOUTH
Solar/Wind Harmer
-0.017
3146206CASHIE
Solar/Wind Harmer
-0.017
970601AG2-382 GEN
Solar/Wind Harmer
7.286
971285AH1-108 GEN
Adder
1.047
972265AH1-717 GEN
Adder
10.391
3151201GRAVEL4
Adder
9.741
3151191GRAVEL3
Adder
9.617
3151211GRAVEL5
Adder
9.617
315732AD1-074 GEN1
Solar/Wind Harmer
0.429
315733AD1-074 GEN2
Solar/Wind Harmer
0.429
315735AD1-075 GEN1
Solar/Wind Harmer
0.214
3143336POWHATN
Solar/Wind Harmer
2.639
970919AG2-571 GEN
Solar/Wind Harmer
6.939
939411AE1-173 GEN
Solar/Wind Harmer
109.306
970087AG2-069 GEN
Solar/Wind Harmer
20.456
316336AC2-165 C
Solar/Wind Harmer
3.699
3143526WINTERP
Solar/Wind Harmer
-0.108
957481AF2-042 GEN
Solar/Wind Harmer
64.853
315693AD1-088 GEN
Solar/Wind Harmer
10.143
962491AG1-098 GEN
Solar/Wind Harmer
13.526
970937AG2-583 GEN
Solar/Wind Harmer
13.537
315687AD1-152 GEN
Solar/Wind Harmer
2.221
3146926FARMVIL
Solar/Wind Harmer
-0.011
316023GEN1_S
Solar/Wind Harmer
1.225
963171AG1-166 GEN
Solar/Wind Harmer
2.245
971563AH1-280 GEN
Solar/Wind Harmer
2.245
3144293JTRSVLE
Adder
0.509
960081AF2-299 GEN
Solar/Wind Harmer
2.018
970685AG2-442 GEN
Solar/Wind Harmer
15.656
971795AH1-408 GEN
Solar/Wind Harmer
13.409
3147043LAWRENC
Adder
1.438
316237AB2-079_GEN
Solar/Wind Harmer
0.531
316322AB2-045
Solar/Wind Harmer
0.592
3146776BUCKING
Solar/Wind Harmer
-0.007
971065AG2-659 GEN
Solar/Wind Harmer
8.742
316129AC1-054 GEN
Solar/Wind Harmer
1.531
316011AB1-132 GEN
Solar/Wind Harmer
3.607
962571AG1-106 GEN
Solar/Wind Harmer
2.478
944591AF1-124 GEN
Solar/Wind Harmer
78.664
315683AE1-153 C
Solar/Wind Harmer
15.955
316190AA2-174 GEN
Solar/Wind Harmer
0.21
3145783HORNRTN
Solar/Wind Harmer
-0.017
316388AE2-253 GEN
Solar/Wind Harmer
1.15
316294AC1-161 GEN
Solar/Wind Harmer
5.519
3146456SLIGO L269
Solar/Wind Harmer
-0.017
3145796HORNRTN
Solar/Wind Harmer
-0.056
3145796HORNRTN
Solar/Wind Harmer
-0.017
316246AF1-032 C
Solar/Wind Harmer
0.344
316093AE2-104_GEN
Solar/Wind Harmer
4.929
316375AC2-012 GEN
Solar/Wind Harmer
5.859
3150981CHESPKA
Adder
1.882
3146516WINFALL
Solar/Wind Harmer
-0.054
3146516WINFALL
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.067
3145893MURPHYS
Solar/Wind Harmer
0.502
972003AH1-546 GEN
Solar/Wind Harmer
8.434
315800Z1-036_GEN1
Solar/Wind Harmer
4.166
3146263WOODLND
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.017
3130156CHOWAN
Solar/Wind Harmer
-0.017
970401AG2-262 GEN
Solar/Wind Harmer
1.096
970661AG2-428 GEN
Solar/Wind Harmer
17.805
3145663CRESWEL
Solar/Wind Harmer
-0.047
3145683EARLEYS
Solar/Wind Harmer
-0.017
971163AH1-040 GEN
Solar/Wind Harmer
15.681
316381AD1-082 GEN
Solar/Wind Harmer
1.533
970659AG2-427 GEN
Solar/Wind Harmer
8.872
3146206CASHIE
Solar/Wind Harmer
-0.017
971547AH1-271 GEN
Solar/Wind Harmer
4.163
3150851SPRUNCC
Adder
0.64
3151171GRAVELC
Adder
1.424
971133AH1-012 GEN
50/50
10.157
3151731LOISA B
50/50
19.419
3151721LOISA A
50/50
19.318
970533AG2-339 GEN
50/50
18.931
970531AG2-338 GEN
50/50
7.573
315242AE2-183_GT2
50/50
3.412
315241AE2-183_GT1
50/50
3.391
972185AH1-677 GEN
50/50
12.3
3151041BRUNSWICKG3
50/50
2.683
972187AH1-678 GEN
50/50
6.156
316447AC1-158 HLD
Solar/Wind Harmer
18.935
966001AG1-469 GEN
Solar/Wind Harmer
0.523
971223AH1-071 GEN
Solar/Wind Harmer
3.236
970933AG2-581 GEN
Solar/Wind Harmer
21.052
3143526WINTERP
Solar/Wind Harmer
-0.108
970099AG2-077 GEN
Solar/Wind Harmer
25.941
3144356SAPONY
Solar/Wind Harmer
0.69
971741AH1-377 GEN
Solar/Wind Harmer
22.545
970301AG2-198 GEN
Solar/Wind Harmer
9.564
3147133PAMPLIN
Solar/Wind Harmer
-0.018
3147133PAMPLIN
Solar/Wind Harmer
-0.014
958211AF2-115 GEN
Solar/Wind Harmer
2.806
963191AG1-168 GEN
Solar/Wind Harmer
1.683
3144293JTRSVLE
Adder
0.509
3144293JTRSVLE
Adder
0.428
316034AC1-036 C
Solar/Wind Harmer
0.331
970323AG2-213 GEN
Solar/Wind Harmer
8.912
971775AH1-396 GEN
Solar/Wind Harmer
1.269
313527AB2-043 GEN
Solar/Wind Harmer
2.871
939181AE1-148 GEN
Solar/Wind Harmer
9.906
316181AB2-040 GEN
Solar/Wind Harmer
2.454
3146776BUCKING
Solar/Wind Harmer
-0.07
3146776BUCKING
Solar/Wind Harmer
-0.006
3145593CAROLNA
Solar/Wind Harmer
-0.017
3145593CAROLNA
Solar/Wind Harmer
-0.017
966811AG1-552 GEN
Solar/Wind Harmer
1.936
3145593CAROLNA
Solar/Wind Harmer
0.143
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
316426AA2-053 GEN
Solar/Wind Harmer
1.73
3145783HORNRTN
Solar/Wind Harmer
2.029
3145783HORNRTN
Solar/Wind Harmer
1.623
3145783HORNRTN
Solar/Wind Harmer
0.507
3145783HORNRTN
Solar/Wind Harmer
0.203
316185AD1-033 GEN
Solar/Wind Harmer
1.801
3145506HICKORY
Solar/Wind Harmer
-0.068
3145506HICKORY
Solar/Wind Harmer
-0.041
3145506HICKORY
Solar/Wind Harmer
-0.01
316339AD2-160 GEN
Solar/Wind Harmer
1.15
316018AA1-139 ULT2
Solar/Wind Harmer
1.461
316017AA1-139 ULT1
Solar/Wind Harmer
1.38
3137176SLIGO L2192
Solar/Wind Harmer
-0.067
3146456SLIGO L269
Solar/Wind Harmer
2.013
3130086AYDLETT
Solar/Wind Harmer
-0.068
3145796HORNRTN
Solar/Wind Harmer
-0.051
3142956BIRDNECK
Solar/Wind Harmer
0.913
316316AC1-027 C
Solar/Wind Harmer
0.522
3146386ELIZ CT
Solar/Wind Harmer
-0.017
315742AE1-103 GEN
Solar/Wind Harmer
1.775
316036AC1-147 C
Solar/Wind Harmer
0.457
3150991CHESPKB
Adder
1.578
3150991CHESPKB
Adder
1.541
316431W1029_GEN1
Solar/Wind Harmer
3.067
316433W1029_GEN2
Solar/Wind Harmer
3.067
962561AG1-105 GEN
Solar/Wind Harmer
9.523
3146516WINFALL
Solar/Wind Harmer
-0.017
3146516WINFALL
Solar/Wind Harmer
-0.017
3146516WINFALL
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
0.472
3145893MURPHYS
Solar/Wind Harmer
-0.03
3146626S HERTFORD
Solar/Wind Harmer
-0.017
3146626S HERTFORD
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.017
3146376EDENTON
Solar/Wind Harmer
0.499
3146376EDENTON
Solar/Wind Harmer
0.499
964791AG1-342 GEN
Solar/Wind Harmer
3.588
3146843MT LREL
Solar/Wind Harmer
-0.017
3146843MT LREL
Solar/Wind Harmer
-0.017
970657AG2-426 GEN
Solar/Wind Harmer
5.229
970657AG2-426 GEN
Solar/Wind Harmer
1.093
316065AD1-022 GEN
Solar/Wind Harmer
8.326
944641AF1-129 GEN
Adder
59.993
3152261N ANNA2
50/50
36.414
3151771S ANNAG1
50/50
1.042
3151801S ANNAS2
50/50
0.535
3151761LOISA E
50/50
39.589
972183AH1-676 GEN
50/50
308.231
3151031BRUNSWICKG2
50/50
2.683
316044AC1-158 PL1
Solar/Wind Harmer
8.611
316450AC1-158 RIC
Solar/Wind Harmer
2.296
3147666LOUISA
Solar/Wind Harmer
-0.125
316313AB2-026
Solar/Wind Harmer
0.6
316258AE1-075 C
Solar/Wind Harmer
0.54
316405AF2-144 C
Solar/Wind Harmer
0.57
3143336POWHATN
Solar/Wind Harmer
2.243
970917AG2-570 GEN
Solar/Wind Harmer
54.816
316478AD1-087 GEN
Solar/Wind Harmer
1.715
316486AD2-202 GEN
Solar/Wind Harmer
0.502
970909AG2-566 GEN
Solar/Wind Harmer
1.816
3146926FARMVIL
Solar/Wind Harmer
-0.011
316365GEN2_N
Solar/Wind Harmer
1.225
942461AE2-259 GEN
Solar/Wind Harmer
2.724
3132273ORANGE
Solar/Wind Harmer
-0.004
3147133PAMPLIN
Solar/Wind Harmer
-0.056
971193AH1-056 GEN
Solar/Wind Harmer
11.252
963181AG1-167 GEN
Solar/Wind Harmer
1.683
3144293JTRSVLE
Adder
0.509
966621AG1-532 GEN
Solar/Wind Harmer
0.364
3147043LAWRENC
Solar/Wind Harmer
-0.011
959311AF2-222 GEN
Solar/Wind Harmer
18.625
970257AG2-171 GEN
Solar/Wind Harmer
6.684
315785AD2-033 C
Solar/Wind Harmer
4.033
964241AG1-285 GEN
Solar/Wind Harmer
13.848
316131AB2-060 GEN
Solar/Wind Harmer
1.908
313506AB2-031 GEN
Solar/Wind Harmer
1.414
3146776BUCKING
Solar/Wind Harmer
-0.006
944581AF1-123 GEN
Solar/Wind Harmer
78.382
944601AF1-125 GEN
Solar/Wind Harmer
77.158
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
315773AC2-141 GEN
Solar/Wind Harmer
7.138
3146456SLIGO L269
Solar/Wind Harmer
-0.017
971153AH1-033 GEN
Solar/Wind Harmer
2.077
3145796HORNRTN
Solar/Wind Harmer
-0.068
3145796HORNRTN
Solar/Wind Harmer
-0.017
3156081AA2-088 GEN
Solar/Wind Harmer
5.522
316320Y1-086
Solar/Wind Harmer
0.996
3151101ELIZAR3
Adder
14.024
3145273HOLLAND
Solar/Wind Harmer
-0.013
3144873MCLAUGH
Solar/Wind Harmer
0
316435W1029_GEN3
Solar/Wind Harmer
3.067
3146516WINFALL
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
0.118
3145893MURPHYS
Solar/Wind Harmer
-0.017
3146626S HERTFORD
Solar/Wind Harmer
-0.017
957521AF2-046 GEN
Solar/Wind Harmer
13.305
961681AG1-008 GEN
Solar/Wind Harmer
13.305
3146263WOODLND
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.017
3146376EDENTON
Solar/Wind Harmer
-0.017
316463AE2-346 GEN
Solar/Wind Harmer
0.272
316140AB2-099
Solar/Wind Harmer
0.113
962331AG1-082 GEN
Solar/Wind Harmer
2.097
970661AG2-428 GEN
Solar/Wind Harmer
3.155
315614AA2-178 GEN
Solar/Wind Harmer
1.805
316083AB2-161 GEN
Solar/Wind Harmer
2.713
970659AG2-427 GEN
Solar/Wind Harmer
1.572
3156021HOLLOMANSOL
Solar/Wind Harmer
2.245
971157AH1-035 GEN
Solar/Wind Harmer
2.083
3146206CASHIE
Solar/Wind Harmer
-0.017
3150861SPRUNCD
Adder
0.64
3151221GRAVEL6
Adder
9.73
3151171GRAVELC
Adder
1.872
3144216WINCHST
Adder
0.451
3150921YORKTN3
Adder
2.951
315737AD1-076 GEN
Solar/Wind Harmer
0.403
LAGNLTFEXP_LAGN->PJM
CLTF
5.952
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.368
TVALTFEXP_TVA->PJM
CLTF
2.995
CPLELTFEXP_CPLE->PJM
CLTF
9.529
CBM West 2LTFEXP_CBM-W2->PJM
CBM
29.532
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.913
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.044
MECLTFEXP_MEC->PJM
CLTF
2.409
SIGELTFEXP_SIGE->PJM
CLTF
0.072
NYPJM->LTFIMP_NY
CLTF
2.685
LGEELTFEXP_LGEE->PJM
CLTF
0.835
WECLTFEXP_WEC->PJM
CLTF
0.4

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T594_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T594_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:130.91 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:5157.73
MW Contribution:7.82
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
3.93
315244AE2-183_ST
50/50
5.657
963041AG1-153 GEN
50/50
5.21
316164AC1-076 GEN
Solar/Wind Harmer
3.006
3147346CASHSCORNER
Solar/Wind Harmer
0.486
941031AE2-094 GEN
Solar/Wind Harmer
43.024
944011AF1-069 GEN
Solar/Wind Harmer
13.481
970673AG2-436 GEN
Solar/Wind Harmer
47.245
970673AG2-436 GEN
Solar/Wind Harmer
23.921
971967AH1-528 GEN
Solar/Wind Harmer
41.678
970085AG2-068 GEN
Solar/Wind Harmer
13.08
970581AG2-369 GEN
Solar/Wind Harmer
11.249
316233AE1-074 FULL
Solar/Wind Harmer
0.537
971281AH1-106 GEN
Solar/Wind Harmer
3.245
971283AH1-107 GEN
Solar/Wind Harmer
3.245
316315AB2-025 C
Solar/Wind Harmer
0.509
315814AE2-033 C
Solar/Wind Harmer
17.498
315657AE1-056 GEN
Solar/Wind Harmer
6.551
970285AG2-188 GEN
Solar/Wind Harmer
15.241
946301AF1-294 GEN
Solar/Wind Harmer
4.461
961791AG1-021 GEN
Solar/Wind Harmer
2.176
971845AH1-439 GEN
Solar/Wind Harmer
9.206
970683AG2-441 GEN
Solar/Wind Harmer
13.532
970681AG2-440 GEN
Solar/Wind Harmer
10.825
3144303KENBRDG
Solar/Wind Harmer
-0.014
971443AH1-215 GEN
Solar/Wind Harmer
3.39
946281AF1-292 GEN
Solar/Wind Harmer
0.384
316239AB2-077_GEN
Solar/Wind Harmer
0.511
316238AB2-078_GEN
Solar/Wind Harmer
0.511
3143316POE
Solar/Wind Harmer
-0.067
316087AB2-174 GEN
Solar/Wind Harmer
2.412
970831AG2-522 GEN
Solar/Wind Harmer
8.357
972205AH1-687 GEN
Adder
6.317
3137643SOCKMAN
Solar/Wind Harmer
-0.066
315652AC1-086 GEN
Solar/Wind Harmer
18.506
315607AA1-063A GEN
Solar/Wind Harmer
1.651
3146043SEABORD
Solar/Wind Harmer
-0.016
3145796HORNRTN
Solar/Wind Harmer
-0.052
3145796HORNRTN
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
1.438
957871AF2-081 GEN
Solar/Wind Harmer
8.074
319010AE1-072 C
Solar/Wind Harmer
3.264
3146406KITTY HAWK
Solar/Wind Harmer
0.013
316318V4-068
Solar/Wind Harmer
0.401
3145893MURPHYS
Solar/Wind Harmer
-0.043
3145893MURPHYS
Solar/Wind Harmer
-0.016
313526AB2-022
Solar/Wind Harmer
0.434
316305AF2-043 C
Solar/Wind Harmer
0.485
316321Z2-027
Solar/Wind Harmer
0.434
3145176PASQUOTANK
Solar/Wind Harmer
-0.01
3146396TANGLEW
Solar/Wind Harmer
0.296
3151081ELIZAR1
Adder
13.101
3151091ELIZAR2
Adder
12.874
3146486SUNBURY
Solar/Wind Harmer
-0.016
3146486SUNBURY
Solar/Wind Harmer
-0.016
315835AF2-110_GEN
Solar/Wind Harmer
2.007
3152611GOSPORTB
Adder
1.816
3152621GOSPORTC
Adder
1.541
3152601GOSPORTA
Adder
1.422
315611Z1-036_GEN2
Solar/Wind Harmer
3.951
3145513AHOSKIE
Solar/Wind Harmer
0.139
961941AG1-037 GEN
Solar/Wind Harmer
0.12
3145513AHOSKIE
Solar/Wind Harmer
-0.016
316311AC2-079 GEN
Solar/Wind Harmer
8.051
315833AF1-017_GEN
Solar/Wind Harmer
3.031
316349AD2-085 GEN
Solar/Wind Harmer
1.419
3130156CHOWAN
Solar/Wind Harmer
-0.016
3130156CHOWAN
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.032
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.016
315816AE2-034 GEN
Solar/Wind Harmer
1.285
316118AC1-105 GEN
Solar/Wind Harmer
1.09
3146206CASHIE
Solar/Wind Harmer
-0.016
970601AG2-382 GEN
Solar/Wind Harmer
6.929
3130546PLYMOUTH
Solar/Wind Harmer
-0.016
971285AH1-108 GEN
Adder
0.985
972265AH1-717 GEN
Adder
9.774
3151201GRAVEL4
Adder
9.162
3151191GRAVEL3
Adder
9.046
3151211GRAVEL5
Adder
9.046
315732AD1-074 GEN1
Solar/Wind Harmer
1.025
315733AD1-074 GEN2
Solar/Wind Harmer
1.025
315735AD1-075 GEN1
Solar/Wind Harmer
0.513
3152251N ANNA1
50/50
35.404
3151791S ANNAG2
50/50
1.115
3151781S ANNAS1
50/50
0.573
3151741LOISA C
50/50
1.146
3151751LOISA D
50/50
20.962
970119AG2-088 GEN
50/50
29.475
315243AE2-183_GT3
50/50
3.272
3151051BRUNSWICKS1
50/50
5.34
3151021BRUNSWICKG1
50/50
2.573
971451AH1-221 GEN
50/50
7.815
316045AC1-158 PL2
Solar/Wind Harmer
26.051
3147666LOUISA
Solar/Wind Harmer
-0.219
316192AB2-158 GEN
Solar/Wind Harmer
6.415
316254AC1-120 GEN1
Solar/Wind Harmer
2.072
3143226MDLTHAN
Solar/Wind Harmer
-0.025
940641AE2-051 GEN
Solar/Wind Harmer
21.037
3143336POWHATN
Solar/Wind Harmer
2.558
970919AG2-571 GEN
Solar/Wind Harmer
6.655
970087AG2-069 GEN
Solar/Wind Harmer
19.62
939411AE1-173 GEN
Solar/Wind Harmer
104.381
316336AC2-165 C
Solar/Wind Harmer
3.596
315683AE1-153 C
Solar/Wind Harmer
18.631
3143526WINTERP
Solar/Wind Harmer
-0.103
957481AF2-042 GEN
Solar/Wind Harmer
62.351
315693AD1-088 GEN
Solar/Wind Harmer
9.768
962491AG1-098 GEN
Solar/Wind Harmer
13.03
970937AG2-583 GEN
Solar/Wind Harmer
13.286
3146926FARMVIL
Solar/Wind Harmer
-0.011
315687AD1-152 GEN
Solar/Wind Harmer
2.135
963171AG1-166 GEN
Solar/Wind Harmer
2.176
971563AH1-280 GEN
Solar/Wind Harmer
2.176
3144293JTRSVLE
Adder
0.493
316023GEN1_S
Solar/Wind Harmer
1.169
970685AG2-442 GEN
Solar/Wind Harmer
15.155
316322AB2-045
Solar/Wind Harmer
0.581
3146776BUCKING
Solar/Wind Harmer
-0.007
960081AF2-299 GEN
Solar/Wind Harmer
1.928
971795AH1-408 GEN
Solar/Wind Harmer
12.835
3147043LAWRENC
Adder
1.377
316237AB2-079_GEN
Solar/Wind Harmer
0.511
971065AG2-659 GEN
Solar/Wind Harmer
8.385
316129AC1-054 GEN
Solar/Wind Harmer
1.468
972003AH1-546 GEN
Solar/Wind Harmer
8.347
316011AB1-132 GEN
Solar/Wind Harmer
3.442
962571AG1-106 GEN
Solar/Wind Harmer
2.365
316190AA2-174 GEN
Solar/Wind Harmer
0.201
3145783HORNRTN
Solar/Wind Harmer
-0.016
944591AF1-124 GEN
Solar/Wind Harmer
74.473
3145796HORNRTN
Solar/Wind Harmer
-0.053
3145796HORNRTN
Solar/Wind Harmer
-0.016
970401AG2-262 GEN
Solar/Wind Harmer
1.055
316388AE2-253 GEN
Solar/Wind Harmer
1.089
3146456SLIGO L269
Solar/Wind Harmer
-0.016
316294AC1-161 GEN
Solar/Wind Harmer
5.219
3145893MURPHYS
Solar/Wind Harmer
-0.064
3145893MURPHYS
Solar/Wind Harmer
0.478
316246AF1-032 C
Solar/Wind Harmer
0.325
3146263WOODLND
Solar/Wind Harmer
-0.016
316093AE2-104_GEN
Solar/Wind Harmer
4.669
3146516WINFALL
Solar/Wind Harmer
-0.052
3146516WINFALL
Solar/Wind Harmer
-0.016
3146173TUNIS
Solar/Wind Harmer
-0.016
316375AC2-012 GEN
Solar/Wind Harmer
5.543
3150981CHESPKA
Adder
1.78
315800Z1-036_GEN1
Solar/Wind Harmer
3.951
3130156CHOWAN
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145663CRESWEL
Solar/Wind Harmer
-0.044
971163AH1-040 GEN
Solar/Wind Harmer
14.893
3152261N ANNA2
50/50
35.401
3151771S ANNAG1
50/50
1.115
3151801S ANNAS2
50/50
0.573
3151761LOISA E
50/50
42.735
972183AH1-676 GEN
50/50
334.654
3151031BRUNSWICKG2
50/50
2.573
316044AC1-158 PL1
Solar/Wind Harmer
8.144
316450AC1-158 RIC
Solar/Wind Harmer
2.171
3147666LOUISA
Solar/Wind Harmer
-0.126
3132273ORANGE
Solar/Wind Harmer
-0.006
316170AC1-121 GEN2
Solar/Wind Harmer
0.691
316313AB2-026
Solar/Wind Harmer
0.581
316258AE1-075 C
Solar/Wind Harmer
0.523
316405AF2-144 C
Solar/Wind Harmer
0.552
3143336POWHATN
Solar/Wind Harmer
2.174
970917AG2-570 GEN
Solar/Wind Harmer
52.576
316478AD1-087 GEN
Solar/Wind Harmer
1.649
316486AD2-202 GEN
Solar/Wind Harmer
0.483
970909AG2-566 GEN
Solar/Wind Harmer
1.762
3146926FARMVIL
Solar/Wind Harmer
-0.011
942461AE2-259 GEN
Solar/Wind Harmer
2.651
3147133PAMPLIN
Solar/Wind Harmer
-0.055
971193AH1-056 GEN
Solar/Wind Harmer
10.918
963181AG1-167 GEN
Solar/Wind Harmer
1.632
3144293JTRSVLE
Adder
0.493
316365GEN2_N
Solar/Wind Harmer
1.169
3146776BUCKING
Solar/Wind Harmer
-0.006
959311AF2-222 GEN
Solar/Wind Harmer
18.009
970257AG2-171 GEN
Solar/Wind Harmer
6.46
315785AD2-033 C
Solar/Wind Harmer
3.896
966621AG1-532 GEN
Solar/Wind Harmer
0.348
3147043LAWRENC
Solar/Wind Harmer
-0.01
964241AG1-285 GEN
Solar/Wind Harmer
13.355
316131AB2-060 GEN
Solar/Wind Harmer
1.838
313506AB2-031 GEN
Solar/Wind Harmer
1.351
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
944581AF1-123 GEN
Solar/Wind Harmer
74.206
944601AF1-125 GEN
Solar/Wind Harmer
73.048
3145796HORNRTN
Solar/Wind Harmer
-0.065
3145796HORNRTN
Solar/Wind Harmer
-0.016
3156081AA2-088 GEN
Solar/Wind Harmer
5.256
3146456SLIGO L269
Solar/Wind Harmer
-0.016
971153AH1-033 GEN
Solar/Wind Harmer
1.967
315773AC2-141 GEN
Solar/Wind Harmer
6.751
3145893MURPHYS
Solar/Wind Harmer
0.112
3145893MURPHYS
Solar/Wind Harmer
-0.016
3145273HOLLAND
Solar/Wind Harmer
-0.012
316320Y1-086
Solar/Wind Harmer
0.943
957521AF2-046 GEN
Solar/Wind Harmer
12.668
961681AG1-008 GEN
Solar/Wind Harmer
12.668
3146263WOODLND
Solar/Wind Harmer
-0.016
3151101ELIZAR3
Adder
13.269
316435W1029_GEN3
Solar/Wind Harmer
2.907
3146516WINFALL
Solar/Wind Harmer
-0.016
3146173TUNIS
Solar/Wind Harmer
-0.016
3144873MCLAUGH
Solar/Wind Harmer
0
3146626S HERTFORD
Solar/Wind Harmer
-0.016
316463AE2-346 GEN
Solar/Wind Harmer
0.259
316140AB2-099
Solar/Wind Harmer
0.108
962331AG1-082 GEN
Solar/Wind Harmer
1.997
3146376EDENTON
Solar/Wind Harmer
-0.016
315614AA2-178 GEN
Solar/Wind Harmer
1.714
316317KELFORD C
Solar/Wind Harmer
0.748
3145823KELFORD
Solar/Wind Harmer
-0.016
3156021HOLLOMANSOL
Solar/Wind Harmer
2.136
970661AG2-428 GEN
Solar/Wind Harmer
2.985
3146206CASHIE
Solar/Wind Harmer
-0.016
971157AH1-035 GEN
Solar/Wind Harmer
1.979
3150861SPRUNCD
Adder
0.602
3151221GRAVEL6
Adder
9.152
3151171GRAVELC
Adder
1.761
315737AD1-076 GEN
Solar/Wind Harmer
0.963
3145823KELFORD
Solar/Wind Harmer
-0.016
970661AG2-428 GEN
Solar/Wind Harmer
16.843
3146206CASHIE
Solar/Wind Harmer
-0.016
971547AH1-271 GEN
Solar/Wind Harmer
3.96
3150851SPRUNCC
Adder
0.602
3151171GRAVELC
Adder
1.339
971133AH1-012 GEN
50/50
10.1
3151731LOISA B
50/50
20.962
3151721LOISA A
50/50
20.854
970533AG2-339 GEN
50/50
18.154
970531AG2-338 GEN
50/50
7.261
315242AE2-183_GT2
50/50
3.272
315241AE2-183_GT1
50/50
3.252
972185AH1-677 GEN
50/50
11.796
3151041BRUNSWICKG3
50/50
2.573
972187AH1-678 GEN
50/50
5.905
316447AC1-158 HLD
Solar/Wind Harmer
17.909
966001AG1-469 GEN
Solar/Wind Harmer
0.617
971223AH1-071 GEN
Solar/Wind Harmer
3.105
970933AG2-581 GEN
Solar/Wind Harmer
20.21
315651AD1-115 GEN
Solar/Wind Harmer
9.377
3143526WINTERP
Solar/Wind Harmer
-0.103
970099AG2-077 GEN
Solar/Wind Harmer
24.94
3144356SAPONY
Solar/Wind Harmer
0.658
971741AH1-377 GEN
Solar/Wind Harmer
21.833
970301AG2-198 GEN
Solar/Wind Harmer
9.278
3147133PAMPLIN
Solar/Wind Harmer
-0.017
3147133PAMPLIN
Solar/Wind Harmer
-0.014
958211AF2-115 GEN
Solar/Wind Harmer
2.72
963191AG1-168 GEN
Solar/Wind Harmer
1.632
3144293JTRSVLE
Adder
0.493
3144293JTRSVLE
Adder
0.415
3146776BUCKING
Solar/Wind Harmer
-0.069
3146776BUCKING
Solar/Wind Harmer
-0.006
316034AC1-036 C
Solar/Wind Harmer
0.32
970323AG2-213 GEN
Solar/Wind Harmer
8.614
971775AH1-396 GEN
Solar/Wind Harmer
1.227
313527AB2-043 GEN
Solar/Wind Harmer
2.765
939181AE1-148 GEN
Solar/Wind Harmer
9.523
316181AB2-040 GEN
Solar/Wind Harmer
2.344
3145593CAROLNA
Solar/Wind Harmer
-0.016
3145593CAROLNA
Solar/Wind Harmer
-0.016
966811AG1-552 GEN
Solar/Wind Harmer
1.849
3145593CAROLNA
Solar/Wind Harmer
0.137
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
316426AA2-053 GEN
Solar/Wind Harmer
1.651
3145783HORNRTN
Solar/Wind Harmer
1.938
3145783HORNRTN
Solar/Wind Harmer
1.55
3145783HORNRTN
Solar/Wind Harmer
0.484
3145783HORNRTN
Solar/Wind Harmer
0.194
962561AG1-105 GEN
Solar/Wind Harmer
9.166
3145796HORNRTN
Solar/Wind Harmer
-0.048
3145506HICKORY
Solar/Wind Harmer
-0.064
3145506HICKORY
Solar/Wind Harmer
-0.039
3145506HICKORY
Solar/Wind Harmer
-0.01
316185AD1-033 GEN
Solar/Wind Harmer
1.705
964791AG1-342 GEN
Solar/Wind Harmer
3.453
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
316339AD2-160 GEN
Solar/Wind Harmer
1.089
316018AA1-139 ULT2
Solar/Wind Harmer
1.383
316017AA1-139 ULT1
Solar/Wind Harmer
1.307
3137176SLIGO L2192
Solar/Wind Harmer
-0.064
3146456SLIGO L269
Solar/Wind Harmer
1.906
3130086AYDLETT
Solar/Wind Harmer
-0.064
315742AE1-103 GEN
Solar/Wind Harmer
1.685
3145893MURPHYS
Solar/Wind Harmer
0.449
3145893MURPHYS
Solar/Wind Harmer
-0.029
3142956BIRDNECK
Solar/Wind Harmer
0.864
3146386ELIZ CT
Solar/Wind Harmer
-0.016
316316AC1-027 C
Solar/Wind Harmer
0.494
316431W1029_GEN1
Solar/Wind Harmer
2.907
316433W1029_GEN2
Solar/Wind Harmer
2.907
3146516WINFALL
Solar/Wind Harmer
-0.016
3146516WINFALL
Solar/Wind Harmer
-0.016
3146516WINFALL
Solar/Wind Harmer
-0.016
3146173TUNIS
Solar/Wind Harmer
-0.016
3146173TUNIS
Solar/Wind Harmer
-0.016
316036AC1-147 C
Solar/Wind Harmer
0.432
3150991CHESPKB
Adder
1.493
3150991CHESPKB
Adder
1.457
3146626S HERTFORD
Solar/Wind Harmer
-0.016
3146626S HERTFORD
Solar/Wind Harmer
-0.016
3146376EDENTON
Solar/Wind Harmer
0.473
3146376EDENTON
Solar/Wind Harmer
0.473
316065AD1-022 GEN
Solar/Wind Harmer
7.917
970657AG2-426 GEN
Solar/Wind Harmer
4.945
970657AG2-426 GEN
Solar/Wind Harmer
1.034
944641AF1-129 GEN
Adder
56.207
LAGNLTFEXP_LAGN->PJM
CLTF
5.721
CBM South 2LTFEXP_CBM-S2->PJM
CBM
19.547
TVALTFEXP_TVA->PJM
CLTF
2.88
CPLELTFEXP_CPLE->PJM
CLTF
9.138
CBM West 2LTFEXP_CBM-W2->PJM
CBM
28.402
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.442
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.658
MECLTFEXP_MEC->PJM
CLTF
2.319
SIGELTFEXP_SIGE->PJM
CLTF
0.069
NYPJM->LTFIMP_NY
CLTF
2.601
LGEELTFEXP_LGEE->PJM
CLTF
0.805
WECLTFEXP_WEC->PJM
CLTF
0.386

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T594_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 515T594_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:130.47 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:5140.46
MW Contribution:7.8
Bus #Bus NameTypeMW Contribution
3152251N ANNA1
50/50
35.378
3151791S ANNAG2
50/50
1.098
3151781S ANNAS1
50/50
0.564
3151741LOISA C
50/50
1.127
3151751LOISA D
50/50
20.602
970119AG2-088 GEN
50/50
29.412
315243AE2-183_GT3
50/50
3.266
3151051BRUNSWICKS1
50/50
5.329
3151021BRUNSWICKG1
50/50
2.568
971451AH1-221 GEN
50/50
7.799
316045AC1-158 PL2
Solar/Wind Harmer
26.028
3147666LOUISA
Solar/Wind Harmer
-0.218
316192AB2-158 GEN
Solar/Wind Harmer
6.369
316254AC1-120 GEN1
Solar/Wind Harmer
2.003
3143226MDLTHAN
Solar/Wind Harmer
-0.025
940641AE2-051 GEN
Solar/Wind Harmer
20.996
3143336POWHATN
Solar/Wind Harmer
2.548
970919AG2-571 GEN
Solar/Wind Harmer
6.642
970087AG2-069 GEN
Solar/Wind Harmer
19.58
939411AE1-173 GEN
Solar/Wind Harmer
104.168
316336AC2-165 C
Solar/Wind Harmer
3.581
3143526WINTERP
Solar/Wind Harmer
-0.103
957481AF2-042 GEN
Solar/Wind Harmer
62.195
315693AD1-088 GEN
Solar/Wind Harmer
9.741
962491AG1-098 GEN
Solar/Wind Harmer
12.993
971133AH1-012 GEN
50/50
10.055
3151731LOISA B
50/50
20.602
3151721LOISA A
50/50
20.496
970533AG2-339 GEN
50/50
18.118
970531AG2-338 GEN
50/50
7.247
315242AE2-183_GT2
50/50
3.266
315241AE2-183_GT1
50/50
3.246
972185AH1-677 GEN
50/50
11.773
3151041BRUNSWICKG3
50/50
2.568
972187AH1-678 GEN
50/50
5.893
316447AC1-158 HLD
Solar/Wind Harmer
17.893
966001AG1-469 GEN
Solar/Wind Harmer
0.606
971223AH1-071 GEN
Solar/Wind Harmer
3.098
970933AG2-581 GEN
Solar/Wind Harmer
20.166
315651AD1-115 GEN
Solar/Wind Harmer
8.933
3143526WINTERP
Solar/Wind Harmer
-0.103
970099AG2-077 GEN
Solar/Wind Harmer
24.878
3144356SAPONY
Solar/Wind Harmer
0.657
971741AH1-377 GEN
Solar/Wind Harmer
21.753
970301AG2-198 GEN
Solar/Wind Harmer
9.241
3147133PAMPLIN
Solar/Wind Harmer
-0.017
3147133PAMPLIN
Solar/Wind Harmer
-0.014
958211AF2-115 GEN
Solar/Wind Harmer
2.709
963191AG1-168 GEN
Solar/Wind Harmer
1.625
3144293JTRSVLE
Adder
0.491
3144293JTRSVLE
Adder
0.414
3146776BUCKING
Solar/Wind Harmer
-0.068
3146776BUCKING
Solar/Wind Harmer
-0.006
316034AC1-036 C
Solar/Wind Harmer
0.318
970323AG2-213 GEN
Solar/Wind Harmer
8.582
971775AH1-396 GEN
Solar/Wind Harmer
1.222
313527AB2-043 GEN
Solar/Wind Harmer
2.756
939181AE1-148 GEN
Solar/Wind Harmer
9.495
316181AB2-040 GEN
Solar/Wind Harmer
2.338
3145593CAROLNA
Solar/Wind Harmer
-0.016
3145593CAROLNA
Solar/Wind Harmer
-0.016
966811AG1-552 GEN
Solar/Wind Harmer
1.844
3145593CAROLNA
Solar/Wind Harmer
0.136
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
316426AA2-053 GEN
Solar/Wind Harmer
1.647
3145783HORNRTN
Solar/Wind Harmer
1.933
3145783HORNRTN
Solar/Wind Harmer
1.546
3145783HORNRTN
Solar/Wind Harmer
0.483
3145783HORNRTN
Solar/Wind Harmer
0.193
962561AG1-105 GEN
Solar/Wind Harmer
9.138
316303AF2-085
50/50
3.922
315244AE2-183_ST
50/50
5.646
963041AG1-153 GEN
50/50
5.199
316164AC1-076 GEN
Solar/Wind Harmer
2.965
3147346CASHSCORNER
Solar/Wind Harmer
0.478
941031AE2-094 GEN
Solar/Wind Harmer
42.941
944011AF1-069 GEN
Solar/Wind Harmer
13.455
970673AG2-436 GEN
Solar/Wind Harmer
47.152
970673AG2-436 GEN
Solar/Wind Harmer
23.874
971967AH1-528 GEN
Solar/Wind Harmer
41.593
970085AG2-068 GEN
Solar/Wind Harmer
13.053
970581AG2-369 GEN
Solar/Wind Harmer
11.226
316233AE1-074 FULL
Solar/Wind Harmer
0.536
971281AH1-106 GEN
Solar/Wind Harmer
3.237
971283AH1-107 GEN
Solar/Wind Harmer
3.237
316315AB2-025 C
Solar/Wind Harmer
0.508
315814AE2-033 C
Solar/Wind Harmer
17.459
315657AE1-056 GEN
Solar/Wind Harmer
6.523
946301AF1-294 GEN
Solar/Wind Harmer
4.443
961791AG1-021 GEN
Solar/Wind Harmer
2.167
970285AG2-188 GEN
Solar/Wind Harmer
15.154
970683AG2-441 GEN
Solar/Wind Harmer
13.48
970681AG2-440 GEN
Solar/Wind Harmer
10.784
971845AH1-439 GEN
Solar/Wind Harmer
9.152
3144303KENBRDG
Solar/Wind Harmer
-0.014
971443AH1-215 GEN
Solar/Wind Harmer
3.378
946281AF1-292 GEN
Solar/Wind Harmer
0.383
3143316POE
Solar/Wind Harmer
-0.067
316239AB2-077_GEN
Solar/Wind Harmer
0.51
316238AB2-078_GEN
Solar/Wind Harmer
0.51
316087AB2-174 GEN
Solar/Wind Harmer
2.406
970831AG2-522 GEN
Solar/Wind Harmer
8.334
3137643SOCKMAN
Solar/Wind Harmer
-0.066
972205AH1-687 GEN
Adder
6.271
315652AC1-086 GEN
Solar/Wind Harmer
18.46
315607AA1-063A GEN
Solar/Wind Harmer
1.647
3146043SEABORD
Solar/Wind Harmer
-0.016
3145796HORNRTN
Solar/Wind Harmer
-0.052
3145796HORNRTN
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
1.434
957871AF2-081 GEN
Solar/Wind Harmer
8.054
319010AE1-072 C
Solar/Wind Harmer
3.256
3146406KITTY HAWK
Solar/Wind Harmer
0.013
316318V4-068
Solar/Wind Harmer
0.4
3145893MURPHYS
Solar/Wind Harmer
-0.043
3145893MURPHYS
Solar/Wind Harmer
-0.016
313526AB2-022
Solar/Wind Harmer
0.433
316305AF2-043 C
Solar/Wind Harmer
0.483
316321Z2-027
Solar/Wind Harmer
0.433
3146396TANGLEW
Solar/Wind Harmer
0.295
3145176PASQUOTANK
Solar/Wind Harmer
-0.01
3151081ELIZAR1
Adder
13.069
3151091ELIZAR2
Adder
12.842
3146486SUNBURY
Solar/Wind Harmer
-0.016
3146486SUNBURY
Solar/Wind Harmer
-0.016
315835AF2-110_GEN
Solar/Wind Harmer
2.002
3152611GOSPORTB
Adder
1.811
3152621GOSPORTC
Adder
1.537
3152601GOSPORTA
Adder
1.418
315611Z1-036_GEN2
Solar/Wind Harmer
3.941
3145513AHOSKIE
Solar/Wind Harmer
0.139
961941AG1-037 GEN
Solar/Wind Harmer
0.12
3145513AHOSKIE
Solar/Wind Harmer
-0.016
316311AC2-079 GEN
Solar/Wind Harmer
8.031
315833AF1-017_GEN
Solar/Wind Harmer
3.024
316349AD2-085 GEN
Solar/Wind Harmer
1.416
3130156CHOWAN
Solar/Wind Harmer
-0.016
3130156CHOWAN
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.032
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.016
315816AE2-034 GEN
Solar/Wind Harmer
1.282
316118AC1-105 GEN
Solar/Wind Harmer
1.087
3146206CASHIE
Solar/Wind Harmer
-0.016
970601AG2-382 GEN
Solar/Wind Harmer
6.912
3130546PLYMOUTH
Solar/Wind Harmer
-0.016
971285AH1-108 GEN
Adder
0.983
972265AH1-717 GEN
Adder
9.747
3151201GRAVEL4
Adder
9.137
3151191GRAVEL3
Adder
9.022
3151211GRAVEL5
Adder
9.022
315732AD1-074 GEN1
Solar/Wind Harmer
2.756
315733AD1-074 GEN2
Solar/Wind Harmer
2.756
315735AD1-075 GEN1
Solar/Wind Harmer
1.378
3152261N ANNA2
50/50
35.375
3151771S ANNAG1
50/50
1.098
3151801S ANNAS2
50/50
0.564
3151761LOISA E
50/50
42.002
972183AH1-676 GEN
50/50
328.628
3151031BRUNSWICKG2
50/50
2.568
316044AC1-158 PL1
Solar/Wind Harmer
8.137
316450AC1-158 RIC
Solar/Wind Harmer
2.17
3147666LOUISA
Solar/Wind Harmer
-0.125
3132273ORANGE
Solar/Wind Harmer
-0.006
316170AC1-121 GEN2
Solar/Wind Harmer
0.668
316313AB2-026
Solar/Wind Harmer
0.579
316258AE1-075 C
Solar/Wind Harmer
0.521
316405AF2-144 C
Solar/Wind Harmer
0.55
3143336POWHATN
Solar/Wind Harmer
2.166
970917AG2-570 GEN
Solar/Wind Harmer
52.468
316478AD1-087 GEN
Solar/Wind Harmer
1.645
316486AD2-202 GEN
Solar/Wind Harmer
0.482
970909AG2-566 GEN
Solar/Wind Harmer
1.755
3146926FARMVIL
Solar/Wind Harmer
-0.011
942461AE2-259 GEN
Solar/Wind Harmer
2.639
3147133PAMPLIN
Solar/Wind Harmer
-0.054
971193AH1-056 GEN
Solar/Wind Harmer
10.872
963181AG1-167 GEN
Solar/Wind Harmer
1.625
3144293JTRSVLE
Adder
0.491
316365GEN2_N
Solar/Wind Harmer
1.166
959311AF2-222 GEN
Solar/Wind Harmer
17.943
3146776BUCKING
Solar/Wind Harmer
-0.006
970257AG2-171 GEN
Solar/Wind Harmer
6.437
315785AD2-033 C
Solar/Wind Harmer
3.882
966621AG1-532 GEN
Solar/Wind Harmer
0.347
3147043LAWRENC
Solar/Wind Harmer
-0.01
964241AG1-285 GEN
Solar/Wind Harmer
13.31
316131AB2-060 GEN
Solar/Wind Harmer
1.832
313506AB2-031 GEN
Solar/Wind Harmer
1.347
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
944581AF1-123 GEN
Solar/Wind Harmer
74.024
944601AF1-125 GEN
Solar/Wind Harmer
72.869
3145796HORNRTN
Solar/Wind Harmer
-0.064
3145796HORNRTN
Solar/Wind Harmer
-0.016
3156081AA2-088 GEN
Solar/Wind Harmer
5.243
3146456SLIGO L269
Solar/Wind Harmer
-0.016
971153AH1-033 GEN
Solar/Wind Harmer
1.962
315773AC2-141 GEN
Solar/Wind Harmer
6.734
315683AE1-153 C
Solar/Wind Harmer
17.63
970937AG2-583 GEN
Solar/Wind Harmer
13.209
3146926FARMVIL
Solar/Wind Harmer
-0.011
315687AD1-152 GEN
Solar/Wind Harmer
2.13
963171AG1-166 GEN
Solar/Wind Harmer
2.167
971563AH1-280 GEN
Solar/Wind Harmer
2.167
3144293JTRSVLE
Adder
0.491
316023GEN1_S
Solar/Wind Harmer
1.166
970685AG2-442 GEN
Solar/Wind Harmer
15.097
316322AB2-045
Solar/Wind Harmer
0.578
3146776BUCKING
Solar/Wind Harmer
-0.007
960081AF2-299 GEN
Solar/Wind Harmer
1.923
971795AH1-408 GEN
Solar/Wind Harmer
12.801
3147043LAWRENC
Adder
1.373
316237AB2-079_GEN
Solar/Wind Harmer
0.51
971065AG2-659 GEN
Solar/Wind Harmer
8.362
316129AC1-054 GEN
Solar/Wind Harmer
1.464
972003AH1-546 GEN
Solar/Wind Harmer
8.288
316011AB1-132 GEN
Solar/Wind Harmer
3.433
962571AG1-106 GEN
Solar/Wind Harmer
2.359
316190AA2-174 GEN
Solar/Wind Harmer
0.2
3145783HORNRTN
Solar/Wind Harmer
-0.016
944591AF1-124 GEN
Solar/Wind Harmer
74.291
3145796HORNRTN
Solar/Wind Harmer
-0.053
3145796HORNRTN
Solar/Wind Harmer
-0.016
970401AG2-262 GEN
Solar/Wind Harmer
1.052
316388AE2-253 GEN
Solar/Wind Harmer
1.087
3146456SLIGO L269
Solar/Wind Harmer
-0.016
316294AC1-161 GEN
Solar/Wind Harmer
5.207
3145893MURPHYS
Solar/Wind Harmer
-0.064
3145893MURPHYS
Solar/Wind Harmer
0.477
316246AF1-032 C
Solar/Wind Harmer
0.325
3146263WOODLND
Solar/Wind Harmer
-0.016
316093AE2-104_GEN
Solar/Wind Harmer
4.657
3146516WINFALL
Solar/Wind Harmer
-0.052
3146516WINFALL
Solar/Wind Harmer
-0.016
3146173TUNIS
Solar/Wind Harmer
-0.016
316375AC2-012 GEN
Solar/Wind Harmer
5.53
3150981CHESPKA
Adder
1.776
315800Z1-036_GEN1
Solar/Wind Harmer
3.941
3130156CHOWAN
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145663CRESWEL
Solar/Wind Harmer
-0.044
971163AH1-040 GEN
Solar/Wind Harmer
14.856
3145823KELFORD
Solar/Wind Harmer
-0.016
970661AG2-428 GEN
Solar/Wind Harmer
16.801
3146206CASHIE
Solar/Wind Harmer
-0.016
971547AH1-271 GEN
Solar/Wind Harmer
3.95
3150851SPRUNCC
Adder
0.601
3151171GRAVELC
Adder
1.335
3145893MURPHYS
Solar/Wind Harmer
0.112
3145893MURPHYS
Solar/Wind Harmer
-0.016
3145273HOLLAND
Solar/Wind Harmer
-0.012
316320Y1-086
Solar/Wind Harmer
0.941
957521AF2-046 GEN
Solar/Wind Harmer
12.636
961681AG1-008 GEN
Solar/Wind Harmer
12.636
3146263WOODLND
Solar/Wind Harmer
-0.016
3151101ELIZAR3
Adder
13.236
316435W1029_GEN3
Solar/Wind Harmer
2.9
3146516WINFALL
Solar/Wind Harmer
-0.016
3146173TUNIS
Solar/Wind Harmer
-0.016
3144873MCLAUGH
Solar/Wind Harmer
0
3146626S HERTFORD
Solar/Wind Harmer
-0.016
316463AE2-346 GEN
Solar/Wind Harmer
0.258
316140AB2-099
Solar/Wind Harmer
0.107
962331AG1-082 GEN
Solar/Wind Harmer
1.992
3146376EDENTON
Solar/Wind Harmer
-0.016
315614AA2-178 GEN
Solar/Wind Harmer
1.71
3156021HOLLOMANSOL
Solar/Wind Harmer
2.131
316317KELFORD C
Solar/Wind Harmer
0.746
3145823KELFORD
Solar/Wind Harmer
-0.016
970661AG2-428 GEN
Solar/Wind Harmer
2.977
3146206CASHIE
Solar/Wind Harmer
-0.016
971157AH1-035 GEN
Solar/Wind Harmer
1.974
3150861SPRUNCD
Adder
0.601
3151221GRAVEL6
Adder
9.127
3151171GRAVELC
Adder
1.756
315737AD1-076 GEN
Solar/Wind Harmer
2.59
3145796HORNRTN
Solar/Wind Harmer
-0.048
3145506HICKORY
Solar/Wind Harmer
-0.064
3145506HICKORY
Solar/Wind Harmer
-0.039
3145506HICKORY
Solar/Wind Harmer
-0.01
316185AD1-033 GEN
Solar/Wind Harmer
1.701
964791AG1-342 GEN
Solar/Wind Harmer
3.443
316339AD2-160 GEN
Solar/Wind Harmer
1.087
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
316018AA1-139 ULT2
Solar/Wind Harmer
1.38
316017AA1-139 ULT1
Solar/Wind Harmer
1.303
3137176SLIGO L2192
Solar/Wind Harmer
-0.064
3146456SLIGO L269
Solar/Wind Harmer
1.901
3130086AYDLETT
Solar/Wind Harmer
-0.064
315742AE1-103 GEN
Solar/Wind Harmer
1.681
3145893MURPHYS
Solar/Wind Harmer
0.448
3145893MURPHYS
Solar/Wind Harmer
-0.029
3142956BIRDNECK
Solar/Wind Harmer
0.862
3146386ELIZ CT
Solar/Wind Harmer
-0.016
316316AC1-027 C
Solar/Wind Harmer
0.493
316431W1029_GEN1
Solar/Wind Harmer
2.9
316433W1029_GEN2
Solar/Wind Harmer
2.9
3146516WINFALL
Solar/Wind Harmer
-0.016
3146516WINFALL
Solar/Wind Harmer
-0.016
3146516WINFALL
Solar/Wind Harmer
-0.016
3146173TUNIS
Solar/Wind Harmer
-0.016
3146173TUNIS
Solar/Wind Harmer
-0.016
316036AC1-147 C
Solar/Wind Harmer
0.431
3150991CHESPKB
Adder
1.49
3150991CHESPKB
Adder
1.454
3146626S HERTFORD
Solar/Wind Harmer
-0.016
3146626S HERTFORD
Solar/Wind Harmer
-0.016
3146376EDENTON
Solar/Wind Harmer
0.472
3146376EDENTON
Solar/Wind Harmer
0.472
316065AD1-022 GEN
Solar/Wind Harmer
7.897
944641AF1-129 GEN
Adder
56.042
LAGNLTFEXP_LAGN->PJM
CLTF
5.7
CBM South 2LTFEXP_CBM-S2->PJM
CBM
19.49
TVALTFEXP_TVA->PJM
CLTF
2.869
CPLELTFEXP_CPLE->PJM
CLTF
9.114
CBM West 2LTFEXP_CBM-W2->PJM
CBM
28.291
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.38
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.621
MECLTFEXP_MEC->PJM
CLTF
2.309
SIGELTFEXP_SIGE->PJM
CLTF
0.069
NYPJM->LTFIMP_NY
CLTF
2.592
LGEELTFEXP_LGEE->PJM
CLTF
0.801
WECLTFEXP_WEC->PJM
CLTF
0.384

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T573_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:128.18 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:5050.25
MW Contribution:8.21
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
4.123
315244AE2-183_ST
50/50
5.943
963041AG1-153 GEN
50/50
5.473
3147346CASHSCORNER
Solar/Wind Harmer
0.451
941031AE2-094 GEN
Solar/Wind Harmer
45.192
944011AF1-069 GEN
Solar/Wind Harmer
14.16
970673AG2-436 GEN
Solar/Wind Harmer
49.627
970673AG2-436 GEN
Solar/Wind Harmer
25.128
971967AH1-528 GEN
Solar/Wind Harmer
43.766
970085AG2-068 GEN
Solar/Wind Harmer
13.745
970581AG2-369 GEN
Solar/Wind Harmer
11.821
316233AE1-074 FULL
Solar/Wind Harmer
0.568
971281AH1-106 GEN
Solar/Wind Harmer
3.433
971283AH1-107 GEN
Solar/Wind Harmer
3.433
316315AB2-025 C
Solar/Wind Harmer
0.538
315814AE2-033 C
Solar/Wind Harmer
18.51
315657AE1-056 GEN
Solar/Wind Harmer
6.816
946301AF1-294 GEN
Solar/Wind Harmer
4.646
961791AG1-021 GEN
Solar/Wind Harmer
2.266
946281AF1-292 GEN
Solar/Wind Harmer
0.406
3143316POE
Solar/Wind Harmer
-0.071
970683AG2-441 GEN
Solar/Wind Harmer
14.114
970681AG2-440 GEN
Solar/Wind Harmer
11.291
3144303KENBRDG
Solar/Wind Harmer
-0.014
971443AH1-215 GEN
Solar/Wind Harmer
3.542
970285AG2-188 GEN
Solar/Wind Harmer
15.689
316087AB2-174 GEN
Solar/Wind Harmer
2.549
971845AH1-439 GEN
Solar/Wind Harmer
9.467
316239AB2-077_GEN
Solar/Wind Harmer
0.536
316238AB2-078_GEN
Solar/Wind Harmer
0.536
970831AG2-522 GEN
Solar/Wind Harmer
8.805
3137643SOCKMAN
Solar/Wind Harmer
-0.07
315652AC1-086 GEN
Solar/Wind Harmer
19.588
315607AA1-063A GEN
Solar/Wind Harmer
1.748
3146043SEABORD
Solar/Wind Harmer
-0.017
957871AF2-081 GEN
Solar/Wind Harmer
8.614
319010AE1-072 C
Solar/Wind Harmer
3.482
3146406KITTY HAWK
Solar/Wind Harmer
0.014
3145796HORNRTN
Solar/Wind Harmer
-0.055
3145796HORNRTN
Solar/Wind Harmer
-0.007
965291AG1-394 GEN
Solar/Wind Harmer
1.526
313526AB2-022
Solar/Wind Harmer
0.463
316305AF2-043 C
Solar/Wind Harmer
0.517
3151081ELIZAR1
Adder
13.988
3151091ELIZAR2
Adder
13.745
316321Z2-027
Solar/Wind Harmer
0.462
3145176PASQUOTANK
Solar/Wind Harmer
-0.011
3146396TANGLEW
Solar/Wind Harmer
0.315
315835AF2-110_GEN
Solar/Wind Harmer
2.141
3146486SUNBURY
Solar/Wind Harmer
-0.017
3146486SUNBURY
Solar/Wind Harmer
-0.017
3152611GOSPORTB
Adder
1.939
3152621GOSPORTC
Adder
1.646
3152601GOSPORTA
Adder
1.518
316318V4-068
Solar/Wind Harmer
0.426
3145893MURPHYS
Solar/Wind Harmer
-0.046
3145893MURPHYS
Solar/Wind Harmer
-0.017
316311AC2-079 GEN
Solar/Wind Harmer
8.593
315611Z1-036_GEN2
Solar/Wind Harmer
4.209
315833AF1-017_GEN
Solar/Wind Harmer
3.235
316349AD2-085 GEN
Solar/Wind Harmer
1.515
3130156CHOWAN
Solar/Wind Harmer
-0.017
3130156CHOWAN
Solar/Wind Harmer
-0.017
3145513AHOSKIE
Solar/Wind Harmer
0.148
961941AG1-037 GEN
Solar/Wind Harmer
0.127
3145513AHOSKIE
Solar/Wind Harmer
-0.017
972205AH1-687 GEN
Adder
6.438
3145683EARLEYS
Solar/Wind Harmer
-0.034
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.017
315816AE2-034 GEN
Solar/Wind Harmer
1.367
3130546PLYMOUTH
Solar/Wind Harmer
-0.017
3146206CASHIE
Solar/Wind Harmer
-0.017
970601AG2-382 GEN
Solar/Wind Harmer
7.362
315732AD1-074 GEN1
Solar/Wind Harmer
3.402
315733AD1-074 GEN2
Solar/Wind Harmer
3.402
315735AD1-075 GEN1
Solar/Wind Harmer
1.701
971285AH1-108 GEN
Adder
1.059
972265AH1-717 GEN
Adder
10.51
3151201GRAVEL4
Adder
9.853
3151191GRAVEL3
Adder
9.728
3151211GRAVEL5
Adder
9.728
971133AH1-012 GEN
50/50
10.184
3151731LOISA B
50/50
19.525
3151721LOISA A
50/50
19.424
970533AG2-339 GEN
50/50
19.068
970531AG2-338 GEN
50/50
7.627
315242AE2-183_GT2
50/50
3.437
315241AE2-183_GT1
50/50
3.416
972185AH1-677 GEN
50/50
12.391
3151041BRUNSWICKG3
50/50
2.703
972187AH1-678 GEN
50/50
6.203
966001AG1-469 GEN
Solar/Wind Harmer
0.526
971223AH1-071 GEN
Solar/Wind Harmer
3.257
970933AG2-581 GEN
Solar/Wind Harmer
21.214
3143526WINTERP
Solar/Wind Harmer
-0.109
970099AG2-077 GEN
Solar/Wind Harmer
26.157
3144356SAPONY
Solar/Wind Harmer
0.696
971741AH1-377 GEN
Solar/Wind Harmer
22.746
970301AG2-198 GEN
Solar/Wind Harmer
9.65
3147133PAMPLIN
Solar/Wind Harmer
-0.018
3147133PAMPLIN
Solar/Wind Harmer
-0.015
958211AF2-115 GEN
Solar/Wind Harmer
2.833
963191AG1-168 GEN
Solar/Wind Harmer
1.7
3144293JTRSVLE
Adder
0.514
3144293JTRSVLE
Adder
0.433
316034AC1-036 C
Solar/Wind Harmer
0.334
970323AG2-213 GEN
Solar/Wind Harmer
8.998
971775AH1-396 GEN
Solar/Wind Harmer
1.281
313527AB2-043 GEN
Solar/Wind Harmer
2.899
939181AE1-148 GEN
Solar/Wind Harmer
10.003
316181AB2-040 GEN
Solar/Wind Harmer
2.478
3146776BUCKING
Solar/Wind Harmer
-0.071
3146776BUCKING
Solar/Wind Harmer
-0.006
3145593CAROLNA
Solar/Wind Harmer
-0.017
3145593CAROLNA
Solar/Wind Harmer
-0.017
966811AG1-552 GEN
Solar/Wind Harmer
1.955
3145593CAROLNA
Solar/Wind Harmer
0.144
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
316426AA2-053 GEN
Solar/Wind Harmer
1.747
3145783HORNRTN
Solar/Wind Harmer
2.049
3145783HORNRTN
Solar/Wind Harmer
1.64
3145783HORNRTN
Solar/Wind Harmer
0.512
3145783HORNRTN
Solar/Wind Harmer
0.205
316185AD1-033 GEN
Solar/Wind Harmer
1.82
3145506HICKORY
Solar/Wind Harmer
-0.069
3145506HICKORY
Solar/Wind Harmer
-0.041
3145506HICKORY
Solar/Wind Harmer
-0.01
316339AD2-160 GEN
Solar/Wind Harmer
1.162
316018AA1-139 ULT2
Solar/Wind Harmer
1.476
316017AA1-139 ULT1
Solar/Wind Harmer
1.394
3137176SLIGO L2192
Solar/Wind Harmer
-0.068
3152251N ANNA1
50/50
36.489
3151791S ANNAG2
50/50
1.047
3151781S ANNAS1
50/50
0.538
3151741LOISA C
50/50
1.068
3151751LOISA D
50/50
19.525
970119AG2-088 GEN
50/50
30.924
315243AE2-183_GT3
50/50
3.437
3151051BRUNSWICKS1
50/50
5.61
3151021BRUNSWICKG1
50/50
2.703
971451AH1-221 GEN
50/50
8.209
3147666LOUISA
Solar/Wind Harmer
-0.218
316192AB2-158 GEN
Solar/Wind Harmer
6.364
3143226MDLTHAN
Solar/Wind Harmer
-0.026
940641AE2-051 GEN
Solar/Wind Harmer
22.145
3143336POWHATN
Solar/Wind Harmer
2.66
970919AG2-571 GEN
Solar/Wind Harmer
6.993
939411AE1-173 GEN
Solar/Wind Harmer
110.17
970087AG2-069 GEN
Solar/Wind Harmer
20.618
316336AC2-165 C
Solar/Wind Harmer
3.729
3143526WINTERP
Solar/Wind Harmer
-0.109
957481AF2-042 GEN
Solar/Wind Harmer
65.393
315693AD1-088 GEN
Solar/Wind Harmer
10.229
962491AG1-098 GEN
Solar/Wind Harmer
13.642
970937AG2-583 GEN
Solar/Wind Harmer
13.661
315687AD1-152 GEN
Solar/Wind Harmer
2.242
3146926FARMVIL
Solar/Wind Harmer
-0.011
316023GEN1_S
Solar/Wind Harmer
1.237
963171AG1-166 GEN
Solar/Wind Harmer
2.266
971563AH1-280 GEN
Solar/Wind Harmer
2.266
3144293JTRSVLE
Adder
0.514
960081AF2-299 GEN
Solar/Wind Harmer
2.037
970685AG2-442 GEN
Solar/Wind Harmer
15.808
971795AH1-408 GEN
Solar/Wind Harmer
13.539
3152261N ANNA2
50/50
36.486
3151771S ANNAG1
50/50
1.047
3151801S ANNAS2
50/50
0.538
3151761LOISA E
50/50
39.805
972183AH1-676 GEN
50/50
309.976
3151031BRUNSWICKG2
50/50
2.703
3147666LOUISA
Solar/Wind Harmer
-0.125
316313AB2-026
Solar/Wind Harmer
0.604
316258AE1-075 C
Solar/Wind Harmer
0.544
316405AF2-144 C
Solar/Wind Harmer
0.574
3143336POWHATN
Solar/Wind Harmer
2.261
970917AG2-570 GEN
Solar/Wind Harmer
55.248
316478AD1-087 GEN
Solar/Wind Harmer
1.73
316486AD2-202 GEN
Solar/Wind Harmer
0.507
970909AG2-566 GEN
Solar/Wind Harmer
1.832
3146926FARMVIL
Solar/Wind Harmer
-0.011
316365GEN2_N
Solar/Wind Harmer
1.237
942461AE2-259 GEN
Solar/Wind Harmer
2.75
3132273ORANGE
Solar/Wind Harmer
-0.004
3147133PAMPLIN
Solar/Wind Harmer
-0.057
971193AH1-056 GEN
Solar/Wind Harmer
11.36
963181AG1-167 GEN
Solar/Wind Harmer
1.7
3144293JTRSVLE
Adder
0.514
966621AG1-532 GEN
Solar/Wind Harmer
0.367
3147043LAWRENC
Solar/Wind Harmer
-0.011
959311AF2-222 GEN
Solar/Wind Harmer
18.805
970257AG2-171 GEN
Solar/Wind Harmer
6.749
315785AD2-033 C
Solar/Wind Harmer
4.072
964241AG1-285 GEN
Solar/Wind Harmer
13.983
316131AB2-060 GEN
Solar/Wind Harmer
1.926
313506AB2-031 GEN
Solar/Wind Harmer
1.428
3146776BUCKING
Solar/Wind Harmer
-0.006
944581AF1-123 GEN
Solar/Wind Harmer
79.168
944601AF1-125 GEN
Solar/Wind Harmer
77.932
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
315773AC2-141 GEN
Solar/Wind Harmer
7.21
3146456SLIGO L269
Solar/Wind Harmer
-0.017
971153AH1-033 GEN
Solar/Wind Harmer
2.098
3145796HORNRTN
Solar/Wind Harmer
-0.068
3145796HORNRTN
Solar/Wind Harmer
-0.017
3156081AA2-088 GEN
Solar/Wind Harmer
5.579
316320Y1-086
Solar/Wind Harmer
1.006
3151101ELIZAR3
Adder
14.167
3145273HOLLAND
Solar/Wind Harmer
-0.013
3144873MCLAUGH
Solar/Wind Harmer
0
316435W1029_GEN3
Solar/Wind Harmer
3.099
3145893MURPHYS
Solar/Wind Harmer
0.119
3145893MURPHYS
Solar/Wind Harmer
-0.017
3146516WINFALL
Solar/Wind Harmer
-0.017
3146626S HERTFORD
Solar/Wind Harmer
-0.017
957521AF2-046 GEN
Solar/Wind Harmer
13.441
961681AG1-008 GEN
Solar/Wind Harmer
13.441
3146263WOODLND
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.017
3146376EDENTON
Solar/Wind Harmer
-0.017
316463AE2-346 GEN
Solar/Wind Harmer
0.274
316140AB2-099
Solar/Wind Harmer
0.114
962331AG1-082 GEN
Solar/Wind Harmer
2.118
970661AG2-428 GEN
Solar/Wind Harmer
3.188
315614AA2-178 GEN
Solar/Wind Harmer
1.823
316083AB2-161 GEN
Solar/Wind Harmer
2.741
970659AG2-427 GEN
Solar/Wind Harmer
1.589
3156021HOLLOMANSOL
Solar/Wind Harmer
2.268
971157AH1-035 GEN
Solar/Wind Harmer
2.104
3146206CASHIE
Solar/Wind Harmer
-0.017
315737AD1-076 GEN
Solar/Wind Harmer
3.197
3150861SPRUNCD
Adder
0.647
3151221GRAVEL6
Adder
9.841
3151171GRAVELC
Adder
1.893
3144216WINCHST
Adder
0.457
3150921YORKTN3
Adder
2.989
316317KELFORD C
Solar/Wind Harmer
0.786
3147043LAWRENC
Adder
1.452
316237AB2-079_GEN
Solar/Wind Harmer
0.536
316322AB2-045
Solar/Wind Harmer
0.597
3146776BUCKING
Solar/Wind Harmer
-0.007
971065AG2-659 GEN
Solar/Wind Harmer
8.829
316129AC1-054 GEN
Solar/Wind Harmer
1.546
316011AB1-132 GEN
Solar/Wind Harmer
3.643
962571AG1-106 GEN
Solar/Wind Harmer
2.503
944591AF1-124 GEN
Solar/Wind Harmer
79.453
315683AE1-153 C
Solar/Wind Harmer
16.116
316190AA2-174 GEN
Solar/Wind Harmer
0.212
3145783HORNRTN
Solar/Wind Harmer
-0.017
316388AE2-253 GEN
Solar/Wind Harmer
1.162
316294AC1-161 GEN
Solar/Wind Harmer
5.575
3146456SLIGO L269
Solar/Wind Harmer
-0.017
3145796HORNRTN
Solar/Wind Harmer
-0.056
3145796HORNRTN
Solar/Wind Harmer
-0.017
316246AF1-032 C
Solar/Wind Harmer
0.347
316093AE2-104_GEN
Solar/Wind Harmer
4.98
316375AC2-012 GEN
Solar/Wind Harmer
5.919
3150981CHESPKA
Adder
1.901
3145893MURPHYS
Solar/Wind Harmer
-0.068
3146516WINFALL
Solar/Wind Harmer
-0.055
3146516WINFALL
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
0.507
972003AH1-546 GEN
Solar/Wind Harmer
8.52
315800Z1-036_GEN1
Solar/Wind Harmer
4.209
3146263WOODLND
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.017
3130156CHOWAN
Solar/Wind Harmer
-0.017
970401AG2-262 GEN
Solar/Wind Harmer
1.108
970661AG2-428 GEN
Solar/Wind Harmer
17.989
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145663CRESWEL
Solar/Wind Harmer
-0.047
971163AH1-040 GEN
Solar/Wind Harmer
15.843
316381AD1-082 GEN
Solar/Wind Harmer
1.549
970659AG2-427 GEN
Solar/Wind Harmer
8.964
3146206CASHIE
Solar/Wind Harmer
-0.017
971547AH1-271 GEN
Solar/Wind Harmer
4.207
3150851SPRUNCC
Adder
0.647
3151171GRAVELC
Adder
1.44
3146456SLIGO L269
Solar/Wind Harmer
2.033
3130086AYDLETT
Solar/Wind Harmer
-0.068
3145796HORNRTN
Solar/Wind Harmer
-0.051
3142956BIRDNECK
Solar/Wind Harmer
0.922
316316AC1-027 C
Solar/Wind Harmer
0.527
3146386ELIZ CT
Solar/Wind Harmer
-0.017
315742AE1-103 GEN
Solar/Wind Harmer
1.793
316036AC1-147 C
Solar/Wind Harmer
0.461
3150991CHESPKB
Adder
1.595
3150991CHESPKB
Adder
1.556
316431W1029_GEN1
Solar/Wind Harmer
3.099
316433W1029_GEN2
Solar/Wind Harmer
3.099
962561AG1-105 GEN
Solar/Wind Harmer
9.62
3145893MURPHYS
Solar/Wind Harmer
0.477
3145893MURPHYS
Solar/Wind Harmer
-0.031
3146516WINFALL
Solar/Wind Harmer
-0.017
3146516WINFALL
Solar/Wind Harmer
-0.017
3146516WINFALL
Solar/Wind Harmer
-0.017
3146626S HERTFORD
Solar/Wind Harmer
-0.017
3146626S HERTFORD
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.017
3146376EDENTON
Solar/Wind Harmer
0.504
3146376EDENTON
Solar/Wind Harmer
0.504
964791AG1-342 GEN
Solar/Wind Harmer
3.625
3146843MT LREL
Solar/Wind Harmer
-0.017
3146843MT LREL
Solar/Wind Harmer
-0.017
970657AG2-426 GEN
Solar/Wind Harmer
5.283
970657AG2-426 GEN
Solar/Wind Harmer
1.105
316065AD1-022 GEN
Solar/Wind Harmer
8.412
944641AF1-129 GEN
Adder
60.727
LAGNLTFEXP_LAGN->PJM
CLTF
6.191
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.725
TVALTFEXP_TVA->PJM
CLTF
3.115
CPLELTFEXP_CPLE->PJM
CLTF
9.658
CBM West 2LTFEXP_CBM-W2->PJM
CBM
31.121
CBM West 1LTFEXP_CBM-W1->PJM
CBM
14.634
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.492
MECLTFEXP_MEC->PJM
CLTF
2.607
SIGELTFEXP_SIGE->PJM
CLTF
0.078
NYPJM->LTFIMP_NY
CLTF
2.609
LGEELTFEXP_LGEE->PJM
CLTF
0.916
WECLTFEXP_WEC->PJM
CLTF
0.445

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 574T575_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 574T575_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:174.96 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:6893.4
MW Contribution:10.89
Bus #Bus NameTypeMW Contribution
971133AH1-012 GEN
50/50
8.834
970533AG2-339 GEN
50/50
25.186
970531AG2-338 GEN
50/50
10.074
315242AE2-183_GT2
50/50
4.555
315241AE2-183_GT1
50/50
4.527
972185AH1-677 GEN
50/50
16.42
3151041BRUNSWICKG3
50/50
3.587
972187AH1-678 GEN
50/50
8.232
3150991CHESPKB
50/50
2.821
3150991CHESPKB
50/50
2.753
971223AH1-071 GEN
Solar/Wind Harmer
4.287
3143526WINTERP
Solar/Wind Harmer
-0.162
970933AG2-581 GEN
Solar/Wind Harmer
28.21
3144356SAPONY
Solar/Wind Harmer
1.021
316185AD1-033 GEN
Solar/Wind Harmer
3.013
3142956BIRDNECK
Solar/Wind Harmer
1.531
316316AC1-027 C
Solar/Wind Harmer
0.876
316036AC1-147 C
Solar/Wind Harmer
0.769
3145506HICKORY
Solar/Wind Harmer
-0.113
3145506HICKORY
Solar/Wind Harmer
-0.068
3145506HICKORY
Solar/Wind Harmer
-0.017
316339AD2-160 GEN
Solar/Wind Harmer
1.918
316018AA1-139 ULT2
Solar/Wind Harmer
2.435
316017AA1-139 ULT1
Solar/Wind Harmer
2.3
3137176SLIGO L2192
Solar/Wind Harmer
-0.112
3146456SLIGO L269
Solar/Wind Harmer
3.351
3130086AYDLETT
Solar/Wind Harmer
-0.113
970657AG2-426 GEN
Solar/Wind Harmer
8.805
970657AG2-426 GEN
Solar/Wind Harmer
1.841
3146386ELIZ CT
Solar/Wind Harmer
-0.028
970099AG2-077 GEN
Solar/Wind Harmer
35.099
316431W1029_GEN1
Solar/Wind Harmer
5.059
316433W1029_GEN2
Solar/Wind Harmer
5.059
3146516WINFALL
Solar/Wind Harmer
-0.028
3146516WINFALL
Solar/Wind Harmer
-0.028
3146516WINFALL
Solar/Wind Harmer
-0.028
316236AE1-162_GEN
Solar/Wind Harmer
0.839
3146626S HERTFORD
Solar/Wind Harmer
-0.028
3146626S HERTFORD
Solar/Wind Harmer
-0.028
315742AE1-103 GEN
Solar/Wind Harmer
2.873
3146376EDENTON
Solar/Wind Harmer
0.811
3146376EDENTON
Solar/Wind Harmer
0.811
316240AF1-291 C
Solar/Wind Harmer
0.819
316033AB2-134 GEN
Solar/Wind Harmer
8.722
315697AD1-025 GEN
Solar/Wind Harmer
5.47
944641AF1-129 GEN
Adder
114.368
3151731LOISA B
Adder
15.367
3151721LOISA A
Adder
15.287
3145893MURPHYS
Solar/Wind Harmer
0.736
3145893MURPHYS
Solar/Wind Harmer
-0.047
316065AD1-022 GEN
Solar/Wind Harmer
13.191
971741AH1-377 GEN
Solar/Wind Harmer
30.569
316181AB2-040 GEN
Solar/Wind Harmer
3.656
3146173TUNIS
Solar/Wind Harmer
-0.026
3152261N ANNA2
50/50
31.958
3151031BRUNSWICKG2
50/50
3.587
3151101ELIZAR3
50/50
25.035
3147666LOUISA
Solar/Wind Harmer
-0.108
316313AB2-026
Solar/Wind Harmer
0.798
316258AE1-075 C
Solar/Wind Harmer
0.719
316405AF2-144 C
Solar/Wind Harmer
0.758
3143336POWHATN
Solar/Wind Harmer
2.986
970917AG2-570 GEN
Solar/Wind Harmer
73.668
315773AC2-141 GEN
Solar/Wind Harmer
12.096
944581AF1-123 GEN
Solar/Wind Harmer
130.69
944601AF1-125 GEN
Solar/Wind Harmer
128.65
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146456SLIGO L269
Solar/Wind Harmer
-0.028
971153AH1-033 GEN
Solar/Wind Harmer
3.459
3144536CHRHLND
Solar/Wind Harmer
-0.004
315813AE1-149 C
Solar/Wind Harmer
17.615
316083AB2-161 GEN
Solar/Wind Harmer
4.573
970659AG2-427 GEN
Solar/Wind Harmer
2.653
970661AG2-428 GEN
Solar/Wind Harmer
5.305
316320Y1-086
Solar/Wind Harmer
1.65
3150861SPRUNCD
Adder
1.15
316435W1029_GEN3
Solar/Wind Harmer
5.059
3146516WINFALL
Solar/Wind Harmer
-0.028
3145336SMITFLD
Solar/Wind Harmer
-0.011
315839AE2-212 C
Solar/Wind Harmer
0.839
3146626S HERTFORD
Solar/Wind Harmer
-0.028
3145273HOLLAND
Solar/Wind Harmer
-0.021
965281AG1-393 GEN
Solar/Wind Harmer
3.435
3151221GRAVEL6
Adder
17.751
3151171GRAVELC
Adder
3.415
3146376EDENTON
Solar/Wind Harmer
-0.027
961611AG1-000B GEN
Solar/Wind Harmer
5.745
316365GEN2_N
Solar/Wind Harmer
1.828
316478AD1-087 GEN
Solar/Wind Harmer
2.335
316486AD2-202 GEN
Solar/Wind Harmer
0.684
315778AD1-151 GEN
Solar/Wind Harmer
23.348
315614AA2-178 GEN
Solar/Wind Harmer
2.901
970129AG2-093 GEN
Solar/Wind Harmer
15.087
3156081AA2-088 GEN
Solar/Wind Harmer
8.655
3151761LOISA E
Adder
31.328
3152251N ANNA1
50/50
31.961
970119AG2-088 GEN
50/50
40.696
315243AE2-183_GT3
50/50
4.555
3151051BRUNSWICKS1
50/50
7.445
3151021BRUNSWICKG1
50/50
3.587
971451AH1-221 GEN
50/50
10.895
3150981CHESPKA
50/50
3.363
3147666LOUISA
Solar/Wind Harmer
-0.188
316192AB2-158 GEN
Solar/Wind Harmer
5.479
970133AG2-095 GEN
Solar/Wind Harmer
2.99
966621AG1-532 GEN
Solar/Wind Harmer
0.539
3144216WINCHST
Adder
0.891
971157AH1-035 GEN
Solar/Wind Harmer
3.319
315737AD1-076 GEN
Solar/Wind Harmer
5.035
3150921YORKTN3
Adder
5.907
3145893MURPHYS
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
-0.026
957521AF2-046 GEN
Solar/Wind Harmer
20.741
961681AG1-008 GEN
Solar/Wind Harmer
20.741
3146206CASHIE
Solar/Wind Harmer
-0.026
313506AB2-031 GEN
Solar/Wind Harmer
2.107
3146173TUNIS
Solar/Wind Harmer
-0.026
316463AE2-346 GEN
Solar/Wind Harmer
0.422
316140AB2-099
Solar/Wind Harmer
0.176
962331AG1-082 GEN
Solar/Wind Harmer
3.26
3156021HOLLOMANSOL
Solar/Wind Harmer
3.513
3147043LAWRENC
Solar/Wind Harmer
-0.015
3142666NORTHAMPTON
Solar/Wind Harmer
-0.026
3146263WOODLND
Solar/Wind Harmer
-0.026
970909AG2-566 GEN
Solar/Wind Harmer
2.462
3143096IRON208
Adder
0.962
3143096IRON208
Adder
0.943
316317KELFORD C
Solar/Wind Harmer
1.207
3145823KELFORD
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.102
3145796HORNRTN
Solar/Wind Harmer
-0.026
972183AH1-676 GEN
Adder
243.274
316382AG1-145 C
Solar/Wind Harmer
0.77
3145963POPLR C
Solar/Wind Harmer
-0.025
3142946ENON
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
3.914
316131AB2-060 GEN
Solar/Wind Harmer
2.677
964241AG1-285 GEN
Solar/Wind Harmer
19.386
315785AD2-033 C
Solar/Wind Harmer
5.622
970257AG2-171 GEN
Solar/Wind Harmer
9.302
959311AF2-222 GEN
Solar/Wind Harmer
25.891
3144293JTRSVLE
Adder
0.703
3142433PROV 92
Adder
0.412
3142433PROV 92
Adder
0.412
3141843SHACKLE
Adder
1.042
3150351NORNECKC2
Adder
1.625
972255AH1-712 GEN
Adder
63.154
316044AC1-158 PL1
Solar/Wind Helper
3.502
316450AC1-158 RIC
Solar/Wind Helper
0.934
3141196NOKESVL
Solar/Wind Helper
1.078
227287AC2-120 GEN
Solar/Wind Helper
0.305
226910AB2-157 C
Solar/Wind Helper
0.012
3143226MDLTHAN
Solar/Wind Harmer
-0.034
940641AE2-051 GEN
Solar/Wind Harmer
30.211
3143526WINTERP
Solar/Wind Harmer
-0.162
939411AE1-173 GEN
Solar/Wind Harmer
156.554
3143336POWHATN
Solar/Wind Harmer
3.513
970919AG2-571 GEN
Solar/Wind Harmer
9.325
970087AG2-069 GEN
Solar/Wind Harmer
27.507
316294AC1-161 GEN
Solar/Wind Harmer
9.352
944591AF1-124 GEN
Solar/Wind Harmer
131.161
316375AC2-012 GEN
Solar/Wind Harmer
9.869
316388AE2-253 GEN
Solar/Wind Harmer
1.918
3146456SLIGO L269
Solar/Wind Harmer
-0.028
316336AC2-165 C
Solar/Wind Harmer
4.931
316246AF1-032 C
Solar/Wind Harmer
0.572
316381AD1-082 GEN
Solar/Wind Harmer
2.584
970659AG2-427 GEN
Solar/Wind Harmer
14.969
970661AG2-428 GEN
Solar/Wind Harmer
29.933
316093AE2-104_GEN
Solar/Wind Harmer
8.186
957481AF2-042 GEN
Solar/Wind Harmer
87.747
3150851SPRUNCC
Adder
1.15
316072AD1-144
Solar/Wind Harmer
0.567
3146516WINFALL
Solar/Wind Harmer
-0.09
3146516WINFALL
Solar/Wind Harmer
-0.028
3145336SMITFLD
Solar/Wind Harmer
-0.111
315800Z1-036_GEN1
Solar/Wind Harmer
6.81
315693AD1-088 GEN
Solar/Wind Harmer
13.752
3151171GRAVELC
Adder
2.597
962491AG1-098 GEN
Solar/Wind Harmer
18.339
3130156CHOWAN
Solar/Wind Harmer
-0.027
961611AG1-000B GEN
Solar/Wind Harmer
13.464
315671AE2-027_GEN
Solar/Wind Harmer
20.456
971647AH1-324 GEN
Solar/Wind Harmer
13.581
316023GEN1_S
Solar/Wind Harmer
1.828
971069AG2-661 GEN
Solar/Wind Harmer
4.264
3145663CRESWEL
Solar/Wind Harmer
-0.075
971163AH1-040 GEN
Solar/Wind Harmer
25.206
316458AB2-190 GEN2
Solar/Wind Harmer
2.713
970129AG2-093 GEN
Solar/Wind Harmer
6.111
3151751LOISA D
Adder
15.367
960081AF2-299 GEN
Solar/Wind Harmer
2.989
3138126ROCKLANDING
Solar/Wind Harmer
0.081
3142543TWELFTH
Solar/Wind Harmer
-0.003
3145893MURPHYS
Solar/Wind Harmer
-0.105
3145893MURPHYS
Solar/Wind Harmer
0.783
3146206CASHIE
Solar/Wind Harmer
-0.026
971547AH1-271 GEN
Solar/Wind Harmer
6.58
971795AH1-408 GEN
Solar/Wind Harmer
19.653
3146173TUNIS
Solar/Wind Harmer
-0.026
3147043LAWRENC
Adder
2.097
3145683EARLEYS
Solar/Wind Harmer
-0.026
316011AB1-132 GEN
Solar/Wind Harmer
5.429
962571AG1-106 GEN
Solar/Wind Harmer
3.73
3146263WOODLND
Solar/Wind Harmer
-0.026
316190AA2-174 GEN
Solar/Wind Harmer
0.317
3143096IRON208
Adder
0.962
971317AH1-138 GEN
Solar/Wind Harmer
3.222
3145783HORNRTN
Solar/Wind Harmer
-0.026
3145823KELFORD
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.084
3145796HORNRTN
Solar/Wind Harmer
-0.026
316159AE1-175 C
Solar/Wind Harmer
0.686
3145963POPLR C
Solar/Wind Harmer
-0.025
944631AF1-128 GEN
Adder
107.977
315687AD1-152 GEN
Solar/Wind Harmer
3.055
316174AB2-169 GEN
Solar/Wind Harmer
3.908
970937AG2-583 GEN
Solar/Wind Harmer
18.128
316129AC1-054 GEN
Solar/Wind Harmer
2.211
971065AG2-659 GEN
Solar/Wind Harmer
12.582
316212AC1-099_GEN
Solar/Wind Harmer
2.175
970685AG2-442 GEN
Solar/Wind Harmer
21.702
3144293JTRSVLE
Adder
0.703
3142433PROV 92
Adder
0.412
3142433PROV 92
Adder
0.412
3141843SHACKLE
Adder
1.042
3150351NORNECKC2
Adder
1.599
972277AH1-723 GEN
Adder
73.593
316045AC1-158 PL2
Solar/Wind Helper
11.209
316303AF2-085
50/50
5.426
315244AE2-183_ST
50/50
7.875
963041AG1-153 GEN
50/50
7.263
315779AE2-040
50/50
3.636
3151081ELIZAR1
50/50
24.718
3151091ELIZAR2
50/50
24.289
941591AE2-156 GEN
50/50
22.58
3152611GOSPORTB
50/50
3.43
3152621GOSPORTC
50/50
2.911
3152601GOSPORTA
50/50
2.685
941031AE2-094 GEN
Solar/Wind Harmer
59.691
944011AF1-069 GEN
Solar/Wind Harmer
18.703
316233AE1-074 FULL
Solar/Wind Harmer
0.843
971281AH1-106 GEN
Solar/Wind Harmer
5.091
971283AH1-107 GEN
Solar/Wind Harmer
5.091
970673AG2-436 GEN
Solar/Wind Harmer
65.689
970673AG2-436 GEN
Solar/Wind Harmer
33.26
971967AH1-528 GEN
Solar/Wind Harmer
58.02
970085AG2-068 GEN
Solar/Wind Harmer
18.338
970581AG2-369 GEN
Solar/Wind Harmer
15.771
316315AB2-025 C
Solar/Wind Harmer
0.79
315814AE2-033 C
Solar/Wind Harmer
27.155
3143316POE
Solar/Wind Harmer
-0.114
957871AF2-081 GEN
Solar/Wind Harmer
14.21
319010AE1-072 C
Solar/Wind Harmer
5.736
3146406KITTY HAWK
Solar/Wind Harmer
0.024
316305AF2-043 C
Solar/Wind Harmer
0.853
315833AF1-017_GEN
Solar/Wind Harmer
5.349
316349AD2-085 GEN
Solar/Wind Harmer
2.505
316311AC2-079 GEN
Solar/Wind Harmer
14.204
313526AB2-022
Solar/Wind Harmer
0.759
315835AF2-110_GEN
Solar/Wind Harmer
3.519
3146486SUNBURY
Solar/Wind Harmer
-0.028
3146486SUNBURY
Solar/Wind Harmer
-0.028
316321Z2-027
Solar/Wind Harmer
0.757
3146396TANGLEW
Solar/Wind Harmer
0.516
3145176PASQUOTANK
Solar/Wind Harmer
-0.017
971285AH1-108 GEN
Adder
1.882
971445AH1-216 GEN
Solar/Wind Harmer
17.213
315611Z1-036_GEN2
Solar/Wind Harmer
6.81
972265AH1-717 GEN
Adder
18.958
3151201GRAVEL4
Adder
17.771
3151191GRAVEL3
Adder
17.547
3151211GRAVEL5
Adder
17.547
3130156CHOWAN
Solar/Wind Harmer
-0.027
3130156CHOWAN
Solar/Wind Harmer
-0.027
316369SG1_INVT
Solar/Wind Harmer
4.832
315816AE2-034 GEN
Solar/Wind Harmer
2.176
316132AB2-190 GEN1
Solar/Wind Harmer
2.713
965291AG1-394 GEN
Solar/Wind Harmer
2.36
946281AF1-292 GEN
Solar/Wind Harmer
0.595
3130546PLYMOUTH
Solar/Wind Harmer
-0.026
315732AD1-074 GEN1
Solar/Wind Harmer
5.358
315733AD1-074 GEN2
Solar/Wind Harmer
5.358
315735AD1-075 GEN1
Solar/Wind Harmer
2.68
316318V4-068
Solar/Wind Harmer
0.658
3145893MURPHYS
Solar/Wind Harmer
-0.071
3145893MURPHYS
Solar/Wind Harmer
-0.026
3146206CASHIE
Solar/Wind Harmer
-0.026
970601AG2-382 GEN
Solar/Wind Harmer
11.515
316087AB2-174 GEN
Solar/Wind Harmer
3.755
3146043SEABORD
Solar/Wind Harmer
-0.026
315607AA1-063A GEN
Solar/Wind Harmer
2.638
3145513AHOSKIE
Solar/Wind Harmer
0.227
961941AG1-037 GEN
Solar/Wind Harmer
0.196
3145513AHOSKIE
Solar/Wind Harmer
-0.026
3137643SOCKMAN
Solar/Wind Harmer
-0.103
3145683EARLEYS
Solar/Wind Harmer
-0.052
3145683EARLEYS
Solar/Wind Harmer
-0.026
3145683EARLEYS
Solar/Wind Harmer
-0.026
315652AC1-086 GEN
Solar/Wind Harmer
29.194
3145796HORNRTN
Solar/Wind Harmer
-0.081
3145796HORNRTN
Solar/Wind Harmer
-0.01
970831AG2-522 GEN
Solar/Wind Harmer
12.637
3146033SCOT NK
Solar/Wind Harmer
-0.1
971443AH1-215 GEN
Solar/Wind Harmer
4.884
3144303KENBRDG
Solar/Wind Harmer
-0.02
3147346CASHSCORNER
Solar/Wind Harmer
0.384
3142433PROV 92
Adder
0.412
3142433PROV 92
Adder
0.412
972205AH1-687 GEN
Adder
8.575
972189AH1-679 GEN
Adder
2.228
972193AH1-681 GEN
Adder
2.822
316411AF1-147_GEN1
Solar/Wind Helper
0.847
316415AF1-147_GEN2
Solar/Wind Helper
0.847
3138216PACIFIC
Solar/Wind Helper
0.041
316164AC1-076 GEN
Solar/Wind Helper
1.148
970683AG2-441 GEN
Solar/Wind Harmer
5.411
970681AG2-440 GEN
Solar/Wind Harmer
4.329
3146173TUNIS
Solar/Wind Harmer
-0.026
3142666NORTHAMPTON
Solar/Wind Harmer
-0.026
3142666NORTHAMPTON
Solar/Wind Harmer
-0.026
3142666NORTHAMPTON
Solar/Wind Harmer
-0.026
3142666NORTHAMPTON
Solar/Wind Harmer
-0.015
970301AG2-198 GEN
Solar/Wind Harmer
12.968
316426AA2-053 GEN
Solar/Wind Harmer
2.61
3145593CAROLNA
Solar/Wind Harmer
-0.026
3145593CAROLNA
Solar/Wind Harmer
-0.026
966811AG1-552 GEN
Solar/Wind Harmer
2.903
3145593CAROLNA
Solar/Wind Harmer
0.214
3145783HORNRTN
Solar/Wind Harmer
3.044
3145783HORNRTN
Solar/Wind Harmer
2.436
3145783HORNRTN
Solar/Wind Harmer
0.761
3145783HORNRTN
Solar/Wind Harmer
0.304
3145796HORNRTN
Solar/Wind Harmer
-0.076
3142946ENON
Solar/Wind Harmer
-0.003
939181AE1-148 GEN
Solar/Wind Harmer
13.998
316274AC1-208 GEN
Solar/Wind Harmer
2.681
313527AB2-043 GEN
Solar/Wind Harmer
4.032
316034AC1-036 C
Solar/Wind Harmer
0.46
970323AG2-213 GEN
Solar/Wind Harmer
12.403
971775AH1-396 GEN
Solar/Wind Harmer
1.766
3144293JTRSVLE
Adder
0.703
3144293JTRSVLE
Adder
0.592
3142366NRTHEST
Adder
0.712
3150691DARBY 3
Adder
15.594
3150701DARBY 4
Adder
15.558
3150681DARBY 2
Adder
15.54
3150671DARBY 1
Adder
15.522
3142296MT RD221
Adder
0.637
3150341NORNECKC1
Adder
1.679
3150341NORNECKC1
Adder
1.666
316447AC1-158 HLD
Solar/Wind Helper
7.707
226929AD2-058 GEN
Solar/Wind Helper
0.088
LAGNLTFEXP_LAGN->PJM
CLTF
9.821
CBM South 2LTFEXP_CBM-S2->PJM
CBM
30.397
TVALTFEXP_TVA->PJM
CLTF
4.963
CPLELTFEXP_CPLE->PJM
CLTF
13.878
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.117
CBM West 1LTFEXP_CBM-W1->PJM
CBM
27.809
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.931
MECLTFEXP_MEC->PJM
CLTF
4.554
SIGELTFEXP_SIGE->PJM
CLTF
0.138
NYPJM->LTFIMP_NY
CLTF
3.837
LGEELTFEXP_LGEE->PJM
CLTF
1.676
WECLTFEXP_WEC->PJM
CLTF
0.823

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 57502_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57502_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:169.18 %
Rating:3118.0 MVA
Rating Type:C
MVA to Mitigate:5274.99
MW Contribution:8.94
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
4.498
315244AE2-183_ST
50/50
6.466
963041AG1-153 GEN
50/50
5.958
315779AE2-040
50/50
2.865
941031AE2-094 GEN
Solar/Wind Harmer
49.114
944011AF1-069 GEN
Solar/Wind Harmer
15.389
970673AG2-436 GEN
Solar/Wind Harmer
53.974
970673AG2-436 GEN
Solar/Wind Harmer
27.329
971967AH1-528 GEN
Solar/Wind Harmer
47.608
316233AE1-074 FULL
Solar/Wind Harmer
0.665
971281AH1-106 GEN
Solar/Wind Harmer
4.02
971283AH1-107 GEN
Solar/Wind Harmer
4.02
970085AG2-068 GEN
Solar/Wind Harmer
14.996
970581AG2-369 GEN
Solar/Wind Harmer
12.896
316315AB2-025 C
Solar/Wind Harmer
0.622
315814AE2-033 C
Solar/Wind Harmer
21.391
3143316POE
Solar/Wind Harmer
-0.087
3147346CASHSCORNER
Solar/Wind Harmer
0.337
3151081ELIZAR1
Adder
17.387
3151091ELIZAR2
Adder
17.085
957871AF2-081 GEN
Solar/Wind Harmer
10.642
3152611GOSPORTB
Adder
2.412
3152621GOSPORTC
Adder
2.047
3152601GOSPORTA
Adder
1.888
319010AE1-072 C
Solar/Wind Harmer
4.298
3146406KITTY HAWK
Solar/Wind Harmer
0.018
316305AF2-043 C
Solar/Wind Harmer
0.639
315835AF2-110_GEN
Solar/Wind Harmer
2.641
313526AB2-022
Solar/Wind Harmer
0.57
315833AF1-017_GEN
Solar/Wind Harmer
4.012
316349AD2-085 GEN
Solar/Wind Harmer
1.879
316311AC2-079 GEN
Solar/Wind Harmer
10.655
3146486SUNBURY
Solar/Wind Harmer
-0.021
3146486SUNBURY
Solar/Wind Harmer
-0.021
316321Z2-027
Solar/Wind Harmer
0.568
3146396TANGLEW
Solar/Wind Harmer
0.388
3145176PASQUOTANK
Solar/Wind Harmer
-0.013
946281AF1-292 GEN
Solar/Wind Harmer
0.467
315611Z1-036_GEN2
Solar/Wind Harmer
5.136
971285AH1-108 GEN
Adder
1.388
3130156CHOWAN
Solar/Wind Harmer
-0.021
3130156CHOWAN
Solar/Wind Harmer
-0.021
316087AB2-174 GEN
Solar/Wind Harmer
2.938
971445AH1-216 GEN
Solar/Wind Harmer
12.633
965291AG1-394 GEN
Solar/Wind Harmer
1.811
315816AE2-034 GEN
Solar/Wind Harmer
1.651
3137643SOCKMAN
Solar/Wind Harmer
-0.081
316318V4-068
Solar/Wind Harmer
0.505
3145893MURPHYS
Solar/Wind Harmer
-0.054
3145893MURPHYS
Solar/Wind Harmer
-0.02
3146043SEABORD
Solar/Wind Harmer
-0.02
315607AA1-063A GEN
Solar/Wind Harmer
2.043
3130546PLYMOUTH
Solar/Wind Harmer
-0.02
315652AC1-086 GEN
Solar/Wind Harmer
22.742
315732AD1-074 GEN1
Solar/Wind Harmer
4.081
315733AD1-074 GEN2
Solar/Wind Harmer
4.081
315735AD1-075 GEN1
Solar/Wind Harmer
2.041
3146206CASHIE
Solar/Wind Harmer
-0.02
970601AG2-382 GEN
Solar/Wind Harmer
8.795
3145513AHOSKIE
Solar/Wind Harmer
0.175
961941AG1-037 GEN
Solar/Wind Harmer
0.151
3145513AHOSKIE
Solar/Wind Harmer
-0.02
3145683EARLEYS
Solar/Wind Harmer
-0.04
3145683EARLEYS
Solar/Wind Harmer
-0.02
3145683EARLEYS
Solar/Wind Harmer
-0.02
972265AH1-717 GEN
Adder
13.785
3151201GRAVEL4
Adder
12.922
3151191GRAVEL3
Adder
12.759
3151211GRAVEL5
Adder
12.759
3145796HORNRTN
Solar/Wind Harmer
-0.063
3145796HORNRTN
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
9.966
315657AE1-056 GEN
Solar/Wind Harmer
7.413
946301AF1-294 GEN
Solar/Wind Harmer
5.065
961791AG1-021 GEN
Solar/Wind Harmer
2.471
970683AG2-441 GEN
Solar/Wind Harmer
15.441
970681AG2-440 GEN
Solar/Wind Harmer
12.353
3144303KENBRDG
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
3.891
316239AB2-077_GEN
Solar/Wind Harmer
0.594
316238AB2-078_GEN
Solar/Wind Harmer
0.594
3146033SCOT NK
Solar/Wind Harmer
-0.078
972205AH1-687 GEN
Adder
6.743
3142433PROV 92
Adder
0.28
3142433PROV 92
Adder
0.28
3152261N ANNA2
50/50
32.427
3151031BRUNSWICKG2
50/50
2.942
3151771S ANNAG1
50/50
0.782
3151801S ANNAS2
50/50
0.402
3151761LOISA E
50/50
29.536
972183AH1-676 GEN
50/50
229.088
3147666LOUISA
Solar/Wind Harmer
-0.097
316313AB2-026
Solar/Wind Harmer
0.652
316258AE1-075 C
Solar/Wind Harmer
0.587
316405AF2-144 C
Solar/Wind Harmer
0.619
3143336POWHATN
Solar/Wind Harmer
2.437
970917AG2-570 GEN
Solar/Wind Harmer
60.26
316478AD1-087 GEN
Solar/Wind Harmer
1.891
316486AD2-202 GEN
Solar/Wind Harmer
0.554
944581AF1-123 GEN
Solar/Wind Harmer
97.831
944601AF1-125 GEN
Solar/Wind Harmer
96.304
315773AC2-141 GEN
Solar/Wind Harmer
8.987
3151101ELIZAR3
Adder
17.61
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146456SLIGO L269
Solar/Wind Harmer
-0.021
971153AH1-033 GEN
Solar/Wind Harmer
2.591
316365GEN2_N
Solar/Wind Harmer
1.431
316320Y1-086
Solar/Wind Harmer
1.238
970661AG2-428 GEN
Solar/Wind Harmer
3.976
316083AB2-161 GEN
Solar/Wind Harmer
3.427
970659AG2-427 GEN
Solar/Wind Harmer
1.988
315813AE1-149 C
Solar/Wind Harmer
13.193
3144536CHRHLND
Solar/Wind Harmer
-0.003
316435W1029_GEN3
Solar/Wind Harmer
3.804
3146516WINFALL
Solar/Wind Harmer
-0.021
3145273HOLLAND
Solar/Wind Harmer
-0.016
3146626S HERTFORD
Solar/Wind Harmer
-0.021
970909AG2-566 GEN
Solar/Wind Harmer
1.979
966621AG1-532 GEN
Solar/Wind Harmer
0.423
3150861SPRUNCD
Adder
0.848
315839AE2-212 C
Solar/Wind Harmer
0.622
3146376EDENTON
Solar/Wind Harmer
-0.021
3147043LAWRENC
Solar/Wind Harmer
-0.012
313506AB2-031 GEN
Solar/Wind Harmer
1.647
3145336SMITFLD
Solar/Wind Harmer
-0.008
3156081AA2-088 GEN
Solar/Wind Harmer
6.634
315614AA2-178 GEN
Solar/Wind Harmer
2.202
3145893MURPHYS
Solar/Wind Harmer
0.141
3145893MURPHYS
Solar/Wind Harmer
-0.02
957521AF2-046 GEN
Solar/Wind Harmer
15.928
961681AG1-008 GEN
Solar/Wind Harmer
15.928
971157AH1-035 GEN
Solar/Wind Harmer
2.527
965281AG1-393 GEN
Solar/Wind Harmer
2.525
3142666NORTHAMPTON
Solar/Wind Harmer
-0.02
315737AD1-076 GEN
Solar/Wind Harmer
3.836
3146173TUNIS
Solar/Wind Harmer
-0.02
3146206CASHIE
Solar/Wind Harmer
-0.02
316463AE2-346 GEN
Solar/Wind Harmer
0.324
316140AB2-099
Solar/Wind Harmer
0.135
962331AG1-082 GEN
Solar/Wind Harmer
2.506
3146263WOODLND
Solar/Wind Harmer
-0.02
3156021HOLLOMANSOL
Solar/Wind Harmer
2.693
3151221GRAVEL6
Adder
12.908
3151171GRAVELC
Adder
2.483
3145796HORNRTN
Solar/Wind Harmer
-0.079
3145796HORNRTN
Solar/Wind Harmer
-0.02
3146926FARMVIL
Solar/Wind Harmer
-0.012
942461AE2-259 GEN
Solar/Wind Harmer
2.971
3147133PAMPLIN
Solar/Wind Harmer
-0.062
971193AH1-056 GEN
Solar/Wind Harmer
12.355
963181AG1-167 GEN
Solar/Wind Harmer
1.853
3144293JTRSVLE
Adder
0.56
959311AF2-222 GEN
Solar/Wind Harmer
20.628
970257AG2-171 GEN
Solar/Wind Harmer
7.411
961611AG1-000B GEN
Solar/Wind Harmer
4.161
315785AD2-033 C
Solar/Wind Harmer
4.478
964241AG1-285 GEN
Solar/Wind Harmer
15.437
316317KELFORD C
Solar/Wind Harmer
0.931
3145823KELFORD
Solar/Wind Harmer
-0.02
316131AB2-060 GEN
Solar/Wind Harmer
2.132
3145963POPLR C
Solar/Wind Harmer
-0.019
3144216WINCHST
Adder
0.63
3150921YORKTN3
Adder
4.159
3143096IRON208
Adder
0.665
3143096IRON208
Adder
0.651
3142433PROV 92
Adder
0.28
3142433PROV 92
Adder
0.28
3141843SHACKLE
Adder
0.703
316044AC1-158 PL1
Solar/Wind Helper
3.277
316450AC1-158 RIC
Solar/Wind Helper
0.874
3152251N ANNA1
50/50
32.429
970119AG2-088 GEN
50/50
33.739
315243AE2-183_GT3
50/50
3.74
3151051BRUNSWICKS1
50/50
6.107
3151021BRUNSWICKG1
50/50
2.942
971451AH1-221 GEN
50/50
8.937
3151791S ANNAG2
50/50
0.782
3151781S ANNAS1
50/50
0.402
3151741LOISA C
50/50
0.792
3151751LOISA D
50/50
14.488
3147666LOUISA
Solar/Wind Harmer
-0.169
316192AB2-158 GEN
Solar/Wind Harmer
4.93
3143226MDLTHAN
Solar/Wind Harmer
-0.028
940641AE2-051 GEN
Solar/Wind Harmer
24.512
939411AE1-173 GEN
Solar/Wind Harmer
124.766
3143526WINTERP
Solar/Wind Harmer
-0.128
3143336POWHATN
Solar/Wind Harmer
2.867
970919AG2-571 GEN
Solar/Wind Harmer
7.628
970087AG2-069 GEN
Solar/Wind Harmer
22.494
316336AC2-165 C
Solar/Wind Harmer
4.004
957481AF2-042 GEN
Solar/Wind Harmer
71.332
315693AD1-088 GEN
Solar/Wind Harmer
11.147
962491AG1-098 GEN
Solar/Wind Harmer
14.859
944591AF1-124 GEN
Solar/Wind Harmer
98.183
316294AC1-161 GEN
Solar/Wind Harmer
6.948
316388AE2-253 GEN
Solar/Wind Harmer
1.436
316375AC2-012 GEN
Solar/Wind Harmer
7.364
3150981CHESPKA
Adder
2.365
3146456SLIGO L269
Solar/Wind Harmer
-0.021
316023GEN1_S
Solar/Wind Harmer
1.431
316246AF1-032 C
Solar/Wind Harmer
0.429
316093AE2-104_GEN
Solar/Wind Harmer
6.144
970661AG2-428 GEN
Solar/Wind Harmer
22.438
316381AD1-082 GEN
Solar/Wind Harmer
1.936
970659AG2-427 GEN
Solar/Wind Harmer
11.217
3146516WINFALL
Solar/Wind Harmer
-0.068
3146516WINFALL
Solar/Wind Harmer
-0.021
960081AF2-299 GEN
Solar/Wind Harmer
2.343
316072AD1-144
Solar/Wind Harmer
0.421
315800Z1-036_GEN1
Solar/Wind Harmer
5.136
3150851SPRUNCC
Adder
0.848
3130156CHOWAN
Solar/Wind Harmer
-0.021
971795AH1-408 GEN
Solar/Wind Harmer
15.455
3147043LAWRENC
Adder
1.651
3145336SMITFLD
Solar/Wind Harmer
-0.081
315687AD1-152 GEN
Solar/Wind Harmer
2.461
3145663CRESWEL
Solar/Wind Harmer
-0.057
971163AH1-040 GEN
Solar/Wind Harmer
19.129
3145893MURPHYS
Solar/Wind Harmer
-0.081
3145893MURPHYS
Solar/Wind Harmer
0.601
316011AB1-132 GEN
Solar/Wind Harmer
4.229
962571AG1-106 GEN
Solar/Wind Harmer
2.906
970937AG2-583 GEN
Solar/Wind Harmer
14.494
3146173TUNIS
Solar/Wind Harmer
-0.02
3146206CASHIE
Solar/Wind Harmer
-0.02
971547AH1-271 GEN
Solar/Wind Harmer
5.026
316190AA2-174 GEN
Solar/Wind Harmer
0.247
3146263WOODLND
Solar/Wind Harmer
-0.02
3145783HORNRTN
Solar/Wind Harmer
-0.02
3145683EARLEYS
Solar/Wind Harmer
-0.02
3151171GRAVELC
Adder
1.889
3145796HORNRTN
Solar/Wind Harmer
-0.065
3145796HORNRTN
Solar/Wind Harmer
-0.02
315671AE2-027_GEN
Solar/Wind Harmer
14.951
316129AC1-054 GEN
Solar/Wind Harmer
1.746
971065AG2-659 GEN
Solar/Wind Harmer
9.947
3146926FARMVIL
Solar/Wind Harmer
-0.012
963171AG1-166 GEN
Solar/Wind Harmer
2.471
971563AH1-280 GEN
Solar/Wind Harmer
2.471
3144293JTRSVLE
Adder
0.56
970685AG2-442 GEN
Solar/Wind Harmer
17.294
961611AG1-000B GEN
Solar/Wind Harmer
9.753
3145823KELFORD
Solar/Wind Harmer
-0.02
316237AB2-079_GEN
Solar/Wind Harmer
0.594
971647AH1-324 GEN
Solar/Wind Harmer
9.808
3145963POPLR C
Solar/Wind Harmer
-0.019
3143096IRON208
Adder
0.665
944631AF1-128 GEN
Adder
73.735
3142433PROV 92
Adder
0.28
3142433PROV 92
Adder
0.28
3141843SHACKLE
Adder
0.703
316045AC1-158 PL2
Solar/Wind Helper
10.491
971133AH1-012 GEN
50/50
7.972
970533AG2-339 GEN
50/50
20.723
970531AG2-338 GEN
50/50
8.289
315242AE2-183_GT2
50/50
3.74
315241AE2-183_GT1
50/50
3.717
972185AH1-677 GEN
50/50
13.482
3151041BRUNSWICKG3
50/50
2.942
972187AH1-678 GEN
50/50
6.752
3151731LOISA B
50/50
14.488
3151721LOISA A
50/50
14.413
971223AH1-071 GEN
Solar/Wind Harmer
3.554
3143526WINTERP
Solar/Wind Harmer
-0.128
970933AG2-581 GEN
Solar/Wind Harmer
23.091
3144356SAPONY
Solar/Wind Harmer
0.804
970099AG2-077 GEN
Solar/Wind Harmer
28.533
316185AD1-033 GEN
Solar/Wind Harmer
2.253
3145506HICKORY
Solar/Wind Harmer
-0.085
3145506HICKORY
Solar/Wind Harmer
-0.051
3145506HICKORY
Solar/Wind Harmer
-0.013
3142956BIRDNECK
Solar/Wind Harmer
1.144
316316AC1-027 C
Solar/Wind Harmer
0.654
316339AD2-160 GEN
Solar/Wind Harmer
1.436
316036AC1-147 C
Solar/Wind Harmer
0.574
3150991CHESPKB
Adder
1.984
3150991CHESPKB
Adder
1.936
316018AA1-139 ULT2
Solar/Wind Harmer
1.823
316017AA1-139 ULT1
Solar/Wind Harmer
1.722
3137176SLIGO L2192
Solar/Wind Harmer
-0.084
3146456SLIGO L269
Solar/Wind Harmer
2.51
3130086AYDLETT
Solar/Wind Harmer
-0.085
971741AH1-377 GEN
Solar/Wind Harmer
24.619
3146386ELIZ CT
Solar/Wind Harmer
-0.021
970657AG2-426 GEN
Solar/Wind Harmer
6.599
970657AG2-426 GEN
Solar/Wind Harmer
1.38
316431W1029_GEN1
Solar/Wind Harmer
3.804
316433W1029_GEN2
Solar/Wind Harmer
3.804
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.021
3146626S HERTFORD
Solar/Wind Harmer
-0.021
3146626S HERTFORD
Solar/Wind Harmer
-0.021
970301AG2-198 GEN
Solar/Wind Harmer
10.423
315742AE1-103 GEN
Solar/Wind Harmer
2.176
3146376EDENTON
Solar/Wind Harmer
0.613
3146376EDENTON
Solar/Wind Harmer
0.613
316181AB2-040 GEN
Solar/Wind Harmer
2.859
316236AE1-162_GEN
Solar/Wind Harmer
0.617
3145893MURPHYS
Solar/Wind Harmer
0.565
3145893MURPHYS
Solar/Wind Harmer
-0.036
3142666NORTHAMPTON
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.012
316065AD1-022 GEN
Solar/Wind Harmer
10.065
3146173TUNIS
Solar/Wind Harmer
-0.02
3146173TUNIS
Solar/Wind Harmer
-0.02
3145593CAROLNA
Solar/Wind Harmer
-0.02
3145593CAROLNA
Solar/Wind Harmer
-0.02
966811AG1-552 GEN
Solar/Wind Harmer
2.263
3145593CAROLNA
Solar/Wind Harmer
0.167
316426AA2-053 GEN
Solar/Wind Harmer
2.029
3145783HORNRTN
Solar/Wind Harmer
2.372
3145783HORNRTN
Solar/Wind Harmer
1.898
3145783HORNRTN
Solar/Wind Harmer
0.593
3145783HORNRTN
Solar/Wind Harmer
0.237
3145796HORNRTN
Solar/Wind Harmer
-0.059
939181AE1-148 GEN
Solar/Wind Harmer
11.135
3147133PAMPLIN
Solar/Wind Harmer
-0.02
3147133PAMPLIN
Solar/Wind Harmer
-0.016
958211AF2-115 GEN
Solar/Wind Harmer
3.088
963191AG1-168 GEN
Solar/Wind Harmer
1.853
3144293JTRSVLE
Adder
0.56
3144293JTRSVLE
Adder
0.472
316034AC1-036 C
Solar/Wind Harmer
0.367
970323AG2-213 GEN
Solar/Wind Harmer
9.881
971775AH1-396 GEN
Solar/Wind Harmer
1.407
313527AB2-043 GEN
Solar/Wind Harmer
3.21
316240AF1-291 C
Solar/Wind Harmer
0.595
966001AG1-469 GEN
Solar/Wind Harmer
0.369
944641AF1-129 GEN
Adder
82.518
3142366NRTHEST
Adder
0.471
3150691DARBY 3
Adder
10.241
3150701DARBY 4
Adder
10.217
3150681DARBY 2
Adder
10.205
3150671DARBY 1
Adder
10.193
3142296MT RD221
Adder
0.388
316447AC1-158 HLD
Solar/Wind Helper
7.213
316033AB2-134 GEN
Solar/Wind Harmer
5.503
LAGNLTFEXP_LAGN->PJM
CLTF
7.115
CBM South 2LTFEXP_CBM-S2->PJM
CBM
23.438
TVALTFEXP_TVA->PJM
CLTF
3.587
CPLELTFEXP_CPLE->PJM
CLTF
10.87
CBM West 2LTFEXP_CBM-W2->PJM
CBM
35.96
CBM West 1LTFEXP_CBM-W1->PJM
CBM
17.227
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.109
MECLTFEXP_MEC->PJM
CLTF
3.039
SIGELTFEXP_SIGE->PJM
CLTF
0.091
NYPJM->LTFIMP_NY
CLTF
2.887
LGEELTFEXP_LGEE->PJM
CLTF
1.081
WECLTFEXP_WEC->PJM
CLTF
0.523

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 575_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 575_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:156.39 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:5036.56
MW Contribution:8.89
Bus #Bus NameTypeMW Contribution
971133AH1-012 GEN
50/50
8.867
3151731LOISA B
50/50
16.24
3151721LOISA A
50/50
16.156
970533AG2-339 GEN
50/50
20.601
970531AG2-338 GEN
50/50
8.24
315242AE2-183_GT2
50/50
3.719
315241AE2-183_GT1
50/50
3.696
972185AH1-677 GEN
50/50
13.406
3151041BRUNSWICKG3
50/50
2.926
972187AH1-678 GEN
50/50
6.715
971223AH1-071 GEN
Solar/Wind Harmer
2.685
3143526WINTERP
Solar/Wind Harmer
1.138
970933AG2-581 GEN
Solar/Wind Harmer
17.453
3144356SAPONY
Solar/Wind Harmer
1.707
970099AG2-077 GEN
Solar/Wind Harmer
21.598
966001AG1-469 GEN
Solar/Wind Harmer
0.114
316185AD1-033 GEN
Solar/Wind Harmer
0.005
971741AH1-377 GEN
Solar/Wind Harmer
18.741
3145506HICKORY
Solar/Wind Harmer
0.755
3145506HICKORY
Solar/Wind Harmer
0.453
3145506HICKORY
Solar/Wind Harmer
0.113
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.181
316339AD2-160 GEN
Solar/Wind Harmer
0.305
316018AA1-139 ULT2
Solar/Wind Harmer
0.005
3152261N ANNA2
50/50
32.141
3151771S ANNAG1
50/50
0.875
3151801S ANNAS2
50/50
0.45
3151761LOISA E
50/50
33.109
972183AH1-676 GEN
50/50
256.948
3151031BRUNSWICKG2
50/50
2.926
3147666LOUISA
Solar/Wind Harmer
0.968
316313AB2-026
Solar/Wind Harmer
0.136
316258AE1-075 C
Solar/Wind Harmer
0.163
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.257
970917AG2-570 GEN
Solar/Wind Harmer
18.967
316478AD1-087 GEN
Solar/Wind Harmer
0.676
316486AD2-202 GEN
Solar/Wind Harmer
0.199
944581AF1-123 GEN
Solar/Wind Harmer
42.835
944601AF1-125 GEN
Solar/Wind Harmer
42.176
315773AC2-141 GEN
Solar/Wind Harmer
6.939
3151101ELIZAR3
Adder
17.503
3144873MCLAUGH
Solar/Wind Harmer
0.005
3146456SLIGO L269
Solar/Wind Harmer
0.188
971153AH1-033 GEN
Solar/Wind Harmer
2.174
316365GEN2_N
Solar/Wind Harmer
0.422
316320Y1-086
Solar/Wind Harmer
0.001
970661AG2-428 GEN
Solar/Wind Harmer
3.953
316083AB2-161 GEN
Solar/Wind Harmer
0.002
970659AG2-427 GEN
Solar/Wind Harmer
1.976
315813AE1-149 C
Solar/Wind Harmer
9.96
3144536CHRHLND
Solar/Wind Harmer
0.028
970909AG2-566 GEN
Solar/Wind Harmer
1.986
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.185
3145273HOLLAND
Solar/Wind Harmer
0.139
3146626S HERTFORD
Solar/Wind Harmer
0.185
3150861SPRUNCD
Adder
0.844
3146376EDENTON
Solar/Wind Harmer
0.183
315839AE2-212 C
Solar/Wind Harmer
0.001
3147043LAWRENC
Solar/Wind Harmer
0.109
313506AB2-031 GEN
Solar/Wind Harmer
0.561
3145336SMITFLD
Solar/Wind Harmer
0.072
3156081AA2-088 GEN
Solar/Wind Harmer
0.004
315614AA2-178 GEN
Solar/Wind Harmer
1.034
3145893MURPHYS
Solar/Wind Harmer
0.3
3145893MURPHYS
Solar/Wind Harmer
0.179
957521AF2-046 GEN
Solar/Wind Harmer
13.328
961681AG1-008 GEN
Solar/Wind Harmer
13.328
971157AH1-035 GEN
Solar/Wind Harmer
2.148
3142666NORTHAMPTON
Solar/Wind Harmer
0.179
965281AG1-393 GEN
Solar/Wind Harmer
1.906
315737AD1-076 GEN
Solar/Wind Harmer
2.299
3146173TUNIS
Solar/Wind Harmer
0.178
3146206CASHIE
Solar/Wind Harmer
0.178
316463AE2-346 GEN
Solar/Wind Harmer
0.152
316140AB2-099
Solar/Wind Harmer
0.063
962331AG1-082 GEN
Solar/Wind Harmer
1.894
3146926FARMVIL
Solar/Wind Harmer
0.106
3146263WOODLND
Solar/Wind Harmer
0.177
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3156021HOLLOMANSOL
Solar/Wind Harmer
0.804
3147133PAMPLIN
Solar/Wind Harmer
0.554
316303AF2-085
50/50
4.475
315244AE2-183_ST
50/50
6.429
963041AG1-153 GEN
50/50
5.925
315779AE2-040
50/50
2.849
941031AE2-094 GEN
Solar/Wind Harmer
42.685
944011AF1-069 GEN
Solar/Wind Harmer
13.947
970673AG2-436 GEN
Solar/Wind Harmer
48.502
970673AG2-436 GEN
Solar/Wind Harmer
32.335
971967AH1-528 GEN
Solar/Wind Harmer
35.869
316233AE1-074 FULL
Solar/Wind Harmer
0.175
971281AH1-106 GEN
Solar/Wind Harmer
3.037
971283AH1-107 GEN
Solar/Wind Harmer
3.037
3147346CASHSCORNER
Solar/Wind Harmer
0.503
970085AG2-068 GEN
Solar/Wind Harmer
11.328
970581AG2-369 GEN
Solar/Wind Harmer
9.742
316315AB2-025 C
Solar/Wind Harmer
0.165
315814AE2-033 C
Solar/Wind Harmer
16.082
3143316POE
Solar/Wind Harmer
0.773
3151081ELIZAR1
Adder
17.282
3151091ELIZAR2
Adder
16.982
957871AF2-081 GEN
Solar/Wind Harmer
9.373
3152611GOSPORTB
Adder
2.397
3152621GOSPORTC
Adder
2.035
3152601GOSPORTA
Adder
1.877
319010AE1-072 C
Solar/Wind Harmer
0.947
3146406KITTY HAWK
Solar/Wind Harmer
0.023
316305AF2-043 C
Solar/Wind Harmer
0.002
315835AF2-110_GEN
Solar/Wind Harmer
1.283
313526AB2-022
Solar/Wind Harmer
0.101
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.128
316311AC2-079 GEN
Solar/Wind Harmer
5.367
3146486SUNBURY
Solar/Wind Harmer
0.186
3146486SUNBURY
Solar/Wind Harmer
0.186
316321Z2-027
Solar/Wind Harmer
0.035
3146396TANGLEW
Solar/Wind Harmer
0.514
3145176PASQUOTANK
Solar/Wind Harmer
0.116
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
971285AH1-108 GEN
Adder
1.381
3130156CHOWAN
Solar/Wind Harmer
0.183
3130156CHOWAN
Solar/Wind Harmer
0.183
316087AB2-174 GEN
Solar/Wind Harmer
0.005
965291AG1-394 GEN
Solar/Wind Harmer
0.803
315816AE2-034 GEN
Solar/Wind Harmer
0.775
971445AH1-216 GEN
Solar/Wind Harmer
12.715
3137643SOCKMAN
Solar/Wind Harmer
0.718
3145893MURPHYS
Solar/Wind Harmer
0.484
3145893MURPHYS
Solar/Wind Harmer
0.179
3146043SEABORD
Solar/Wind Harmer
0.179
315607AA1-063A GEN
Solar/Wind Harmer
0.366
315652AC1-086 GEN
Solar/Wind Harmer
19.69
3130546PLYMOUTH
Solar/Wind Harmer
0.179
315732AD1-074 GEN1
Solar/Wind Harmer
1.027
315733AD1-074 GEN2
Solar/Wind Harmer
1.027
315735AD1-075 GEN1
Solar/Wind Harmer
0.514
3152251N ANNA1
50/50
32.143
970119AG2-088 GEN
50/50
33.565
3151791S ANNAG2
50/50
0.875
3151781S ANNAS1
50/50
0.45
3151741LOISA C
50/50
0.888
3151751LOISA D
50/50
16.24
315243AE2-183_GT3
50/50
3.719
3151051BRUNSWICKS1
50/50
6.073
3151021BRUNSWICKG1
50/50
2.926
971451AH1-221 GEN
50/50
8.887
3147666LOUISA
Solar/Wind Harmer
1.684
316192AB2-158 GEN
Solar/Wind Harmer
2.322
3143226MDLTHAN
Solar/Wind Harmer
0.252
940641AE2-051 GEN
Solar/Wind Harmer
18.502
939411AE1-173 GEN
Solar/Wind Harmer
94.175
3143526WINTERP
Solar/Wind Harmer
1.138
3143336POWHATN
Solar/Wind Harmer
3.832
970919AG2-571 GEN
Solar/Wind Harmer
7.587
970087AG2-069 GEN
Solar/Wind Harmer
16.992
316336AC2-165 C
Solar/Wind Harmer
0.008
957481AF2-042 GEN
Solar/Wind Harmer
53.995
315693AD1-088 GEN
Solar/Wind Harmer
9.505
962491AG1-098 GEN
Solar/Wind Harmer
11.265
944591AF1-124 GEN
Solar/Wind Harmer
42.988
316294AC1-161 GEN
Solar/Wind Harmer
3.292
316388AE2-253 GEN
Solar/Wind Harmer
0.59
316375AC2-012 GEN
Solar/Wind Harmer
0.005
3150981CHESPKA
Adder
2.35
3146456SLIGO L269
Solar/Wind Harmer
0.188
316023GEN1_S
Solar/Wind Harmer
0.422
316246AF1-032 C
Solar/Wind Harmer
0.085
316093AE2-104_GEN
Solar/Wind Harmer
3.145
970661AG2-428 GEN
Solar/Wind Harmer
18.585
316381AD1-082 GEN
Solar/Wind Harmer
0.195
970659AG2-427 GEN
Solar/Wind Harmer
9.033
3146516WINFALL
Solar/Wind Harmer
0.601
3146516WINFALL
Solar/Wind Harmer
0.185
960081AF2-299 GEN
Solar/Wind Harmer
1.772
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
316072AD1-144
Solar/Wind Harmer
0.067
3150851SPRUNCC
Adder
0.844
3130156CHOWAN
Solar/Wind Harmer
0.183
971795AH1-408 GEN
Solar/Wind Harmer
12.184
3147043LAWRENC
Adder
1.646
970937AG2-583 GEN
Solar/Wind Harmer
11.147
315687AD1-152 GEN
Solar/Wind Harmer
0.006
3145336SMITFLD
Solar/Wind Harmer
0.724
3145663CRESWEL
Solar/Wind Harmer
0.505
971163AH1-040 GEN
Solar/Wind Harmer
14.45
3145893MURPHYS
Solar/Wind Harmer
0.718
3145893MURPHYS
Solar/Wind Harmer
0.798
316011AB1-132 GEN
Solar/Wind Harmer
3.254
962571AG1-106 GEN
Solar/Wind Harmer
2.547
3146173TUNIS
Solar/Wind Harmer
0.178
316190AA2-174 GEN
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
0.178
971547AH1-271 GEN
Solar/Wind Harmer
3.797
3146926FARMVIL
Solar/Wind Harmer
0.106
3146263WOODLND
Solar/Wind Harmer
0.177
3145783HORNRTN
Solar/Wind Harmer
0.177
3145683EARLEYS
Solar/Wind Harmer
0.177
316129AC1-054 GEN
Solar/Wind Harmer
0.665
3145796HORNRTN
Solar/Wind Harmer
0.582
3145796HORNRTN
Solar/Wind Harmer
0.176
316017AA1-139 ULT1
Solar/Wind Harmer
0.105
316036AC1-147 C
Solar/Wind Harmer
0.035
3150991CHESPKB
Adder
1.972
3150991CHESPKB
Adder
1.924
3137176SLIGO L2192
Solar/Wind Harmer
0.748
3146456SLIGO L269
Solar/Wind Harmer
3.327
3130086AYDLETT
Solar/Wind Harmer
0.751
3146386ELIZ CT
Solar/Wind Harmer
0.187
970657AG2-426 GEN
Solar/Wind Harmer
6.543
970657AG2-426 GEN
Solar/Wind Harmer
1.372
970301AG2-198 GEN
Solar/Wind Harmer
7.945
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.185
3146516WINFALL
Solar/Wind Harmer
0.185
3146516WINFALL
Solar/Wind Harmer
0.185
3146626S HERTFORD
Solar/Wind Harmer
0.185
3146626S HERTFORD
Solar/Wind Harmer
0.185
315742AE1-103 GEN
Solar/Wind Harmer
0.002
3146376EDENTON
Solar/Wind Harmer
0.812
3146376EDENTON
Solar/Wind Harmer
0.812
316181AB2-040 GEN
Solar/Wind Harmer
0.263
316236AE1-162_GEN
Solar/Wind Harmer
0.001
3145893MURPHYS
Solar/Wind Harmer
1.201
3145893MURPHYS
Solar/Wind Harmer
0.323
3142666NORTHAMPTON
Solar/Wind Harmer
0.179
3142666NORTHAMPTON
Solar/Wind Harmer
0.179
3142666NORTHAMPTON
Solar/Wind Harmer
0.179
3142666NORTHAMPTON
Solar/Wind Harmer
0.107
3146173TUNIS
Solar/Wind Harmer
0.178
3146173TUNIS
Solar/Wind Harmer
0.178
3145593CAROLNA
Solar/Wind Harmer
0.178
3145593CAROLNA
Solar/Wind Harmer
0.178
966811AG1-552 GEN
Solar/Wind Harmer
1.933
3145593CAROLNA
Solar/Wind Harmer
0.222
316065AD1-022 GEN
Solar/Wind Harmer
8.207
316426AA2-053 GEN
Solar/Wind Harmer
0.601
3145783HORNRTN
Solar/Wind Harmer
3.149
3145783HORNRTN
Solar/Wind Harmer
2.519
3145783HORNRTN
Solar/Wind Harmer
0.787
3145783HORNRTN
Solar/Wind Harmer
0.315
3147133PAMPLIN
Solar/Wind Harmer
0.177
3147133PAMPLIN
Solar/Wind Harmer
0.141
3145796HORNRTN
Solar/Wind Harmer
0.53
958211AF2-115 GEN
Solar/Wind Harmer
2.119
963191AG1-168 GEN
Solar/Wind Harmer
0.706
3144293JTRSVLE
Adder
0.562
3144293JTRSVLE
Adder
0.473
316034AC1-036 C
Solar/Wind Harmer
0.013
970323AG2-213 GEN
Solar/Wind Harmer
7.517
971775AH1-396 GEN
Solar/Wind Harmer
0.282
939181AE1-148 GEN
Solar/Wind Harmer
8.441
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316240AF1-291 C
Solar/Wind Harmer
0.001
316033AB2-134 GEN
Solar/Wind Harmer
0.01
315697AD1-025 GEN
Solar/Wind Harmer
0.194
944641AF1-129 GEN
Adder
82.024
316274AC1-208 GEN
Solar/Wind Harmer
0.889
3146776BUCKING
Solar/Wind Harmer
0.68
3146776BUCKING
Solar/Wind Harmer
0.055
3145933PARMELE
Solar/Wind Harmer
0.337
3145933PARMELE
Solar/Wind Harmer
0.168
962561AG1-105 GEN
Solar/Wind Harmer
8.081
964791AG1-342 GEN
Solar/Wind Harmer
3.207
3146843MT LREL
Solar/Wind Harmer
0.167
3146843MT LREL
Solar/Wind Harmer
0.167
3145493TOT1
Solar/Wind Harmer
0.379
3145453TOT5
Solar/Wind Harmer
0.228
3145603CNETO
Solar/Wind Harmer
0.152
961601AG1-000A GEN
Solar/Wind Harmer
2.885
316263AC1-034 GEN
Solar/Wind Harmer
6.167
971489AH1-241 GEN
Solar/Wind Harmer
7.927
3142946ENON
Solar/Wind Harmer
0.015
316222AC1-221 GEN
Solar/Wind Harmer
0.599
3142366NRTHEST
Adder
0.468
3150691DARBY 3
Adder
10.179
3150701DARBY 4
Adder
10.155
3150681DARBY 2
Adder
10.143
3150671DARBY 1
Adder
10.132
3146206CASHIE
Solar/Wind Harmer
0.178
970601AG2-382 GEN
Solar/Wind Harmer
6.645
3145513AHOSKIE
Solar/Wind Harmer
0.371
3145513AHOSKIE
Solar/Wind Harmer
0.177
3145683EARLEYS
Solar/Wind Harmer
0.354
3145683EARLEYS
Solar/Wind Harmer
0.177
3145683EARLEYS
Solar/Wind Harmer
0.177
970831AG2-522 GEN
Solar/Wind Harmer
7.546
315657AE1-056 GEN
Solar/Wind Harmer
6.094
3145796HORNRTN
Solar/Wind Harmer
0.565
3145796HORNRTN
Solar/Wind Harmer
0.071
946301AF1-294 GEN
Solar/Wind Harmer
3.484
961791AG1-021 GEN
Solar/Wind Harmer
1.695
972265AH1-717 GEN
Adder
13.702
3151201GRAVEL4
Adder
12.844
3151191GRAVEL3
Adder
12.682
3151211GRAVEL5
Adder
12.682
970683AG2-441 GEN
Solar/Wind Harmer
11.759
970681AG2-440 GEN
Solar/Wind Harmer
9.407
3144303KENBRDG
Solar/Wind Harmer
0.141
971443AH1-215 GEN
Solar/Wind Harmer
2.96
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
3146033SCOT NK
Solar/Wind Harmer
0.692
316369SG1_INVT
Solar/Wind Harmer
0.006
970285AG2-188 GEN
Solar/Wind Harmer
13.601
971845AH1-439 GEN
Solar/Wind Harmer
7.74
316132AB2-190 GEN1
Solar/Wind Harmer
0.911
316005AA1-067
Solar/Wind Harmer
0.178
3145746EVERETS
Solar/Wind Harmer
0.661
3145746EVERETS
Solar/Wind Harmer
0.166
3145746EVERETS
Solar/Wind Harmer
0.166
3145746EVERETS
Solar/Wind Harmer
0.166
970181AG2-120 GEN
Solar/Wind Harmer
2.068
957861AF2-080 GEN
Solar/Wind Harmer
7.107
316319Z2-044 C
Solar/Wind Harmer
0
316420AA1-050 GEN
Solar/Wind Harmer
0.005
316118AC1-105 GEN
Solar/Wind Harmer
0.423
3145573BETHELC
Solar/Wind Harmer
0.164
3145573BETHELC
Solar/Wind Harmer
0.164
972205AH1-687 GEN
Adder
6.884
3147173SINAI
Solar/Wind Harmer
0.161
3147243WELCO
Solar/Wind Harmer
0.1
3138283WHITEMARSH
Solar/Wind Harmer
0.035
971167AH1-042 GEN
Solar/Wind Harmer
12.818
3142433PROV 92
Adder
0.278
3142433PROV 92
Adder
0.278
971447AH1-217 GEN
Solar/Wind Harmer
4.335
970865AG2-541 GEN
Solar/Wind Harmer
4.866
3143873LANEXA
Solar/Wind Harmer
0.082
970189AG2-124 GEN
Solar/Wind Harmer
4.05
315662AE1-191 GEN
Solar/Wind Harmer
0.004
315666AE1-190 GEN
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.027
315976AC1-164 GENA
Solar/Wind Harmer
14.078
316169AC1-164_GENC
Solar/Wind Harmer
12.162
315975AC1-164 GENB
Solar/Wind Harmer
0.416
316059AD1-063 C
Solar/Wind Harmer
0.001
316314AB2-024 C
Solar/Wind Harmer
0
3141913WHIT STONE
Solar/Wind Harmer
0.132
3138133OCRAN
Solar/Wind Harmer
0.039
3141783LANCAST
Solar/Wind Harmer
0.077
3141783LANCAST
Solar/Wind Harmer
0.051
270494AE1-108_GEN
Solar/Wind Harmer
1.539
316123AC1-075 GEN
Solar/Wind Harmer
0.173
970165AG2-112 GEN
Solar/Wind Harmer
1.028
970163AG2-111 GEN
Solar/Wind Harmer
0.981
316312AB1-027
Solar/Wind Harmer
0.222
962981AG1-147 GEN
Solar/Wind Harmer
4.619
970327AG2-215 GEN
Solar/Wind Harmer
3.969
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
971193AH1-056 GEN
Solar/Wind Harmer
10.759
3145796HORNRTN
Solar/Wind Harmer
0.706
3145796HORNRTN
Solar/Wind Harmer
0.176
963181AG1-167 GEN
Solar/Wind Harmer
0.706
3144293JTRSVLE
Adder
0.562
3151221GRAVEL6
Adder
12.83
3151171GRAVELC
Adder
2.468
959311AF2-222 GEN
Solar/Wind Harmer
15.666
970257AG2-171 GEN
Solar/Wind Harmer
5.638
315785AD2-033 C
Solar/Wind Harmer
1.432
964241AG1-285 GEN
Solar/Wind Harmer
11.727
316131AB2-060 GEN
Solar/Wind Harmer
0.553
316317KELFORD C
Solar/Wind Harmer
0.017
3145823KELFORD
Solar/Wind Harmer
0.175
961611AG1-000B GEN
Solar/Wind Harmer
4.662
3145963POPLR C
Solar/Wind Harmer
0.173
316210AC1-098 GEN
Solar/Wind Harmer
1.592
315778AD1-151 GEN
Solar/Wind Harmer
13.699
3146776BUCKING
Solar/Wind Harmer
0.061
970129AG2-093 GEN
Solar/Wind Harmer
10.247
315724AD1-057 GEN
Solar/Wind Harmer
0.633
3145933PARMELE
Solar/Wind Harmer
0.168
966801AG1-551 GEN
Solar/Wind Harmer
1.961
316327AA2-057 GEN
Solar/Wind Harmer
0.252
970133AG2-095 GEN
Solar/Wind Harmer
1.604
3145746EVERETS
Solar/Wind Harmer
0.166
3145746EVERETS
Solar/Wind Harmer
0.166
3144216WINCHST
Adder
0.626
3146233WITAKRS
Solar/Wind Harmer
0.827
3146233WITAKRS
Solar/Wind Harmer
0.112
3138543CONSLDL
Solar/Wind Harmer
0.108
3150921YORKTN3
Adder
4.133
3146073TAR RVR
Solar/Wind Harmer
0.164
3146083TARBORO
Solar/Wind Harmer
0.164
3145543BTLEBRO
Solar/Wind Harmer
0.162
3145543BTLEBRO
Solar/Wind Harmer
0.162
961601AG1-000A GEN
Solar/Wind Harmer
11.54
971623AH1-311 GEN
Solar/Wind Harmer
0.325
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
6.859
3143096IRON208
Adder
0.661
3143096IRON208
Adder
0.648
316382AG1-145 C
Solar/Wind Harmer
0.001
970221AG2-151 GEN
Solar/Wind Harmer
7.927
3142946ENON
Solar/Wind Harmer
0.05
971683AH1-343 GEN
Solar/Wind Harmer
5.409
316283AC2-100 C
Solar/Wind Harmer
0.281
3142433PROV 92
Adder
0.278
3142433PROV 92
Adder
0.278
970293AG2-193 GEN
Solar/Wind Harmer
1.477
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3141843SHACKLE
Adder
0.698
316280AD1-041 GEN
Solar/Wind Harmer
0.003
316156AD2-030 GEN
Solar/Wind Harmer
0.101
3141873WAN 176
Solar/Wind Harmer
2.419
3141766HARMONY
Solar/Wind Harmer
1.798
3142416OLDCHRC
Solar/Wind Harmer
1.203
962971AG1-146 GEN
Solar/Wind Harmer
1.98
970009AG2-005 GEN
Solar/Wind Harmer
0.903
316404AE1-155 C
Solar/Wind Harmer
0.026
316473AC1-191 GEN
Solar/Wind Harmer
0.381
316044AC1-158 PL1
Solar/Wind Helper
3.318
316450AC1-158 RIC
Solar/Wind Helper
0.885
971065AG2-659 GEN
Solar/Wind Harmer
7.534
963171AG1-166 GEN
Solar/Wind Harmer
0.942
971563AH1-280 GEN
Solar/Wind Harmer
1.883
3144293JTRSVLE
Adder
0.562
3151171GRAVELC
Adder
1.877
970685AG2-442 GEN
Solar/Wind Harmer
13.17
315671AE2-027_GEN
Solar/Wind Harmer
11.287
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3145823KELFORD
Solar/Wind Harmer
0.175
961611AG1-000B GEN
Solar/Wind Harmer
9.169
971647AH1-324 GEN
Solar/Wind Harmer
7.404
3145963POPLR C
Solar/Wind Harmer
0.173
316174AB2-169 GEN
Solar/Wind Harmer
0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.887
971069AG2-661 GEN
Solar/Wind Harmer
3.044
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.068
316458AB2-190 GEN2
Solar/Wind Harmer
0.911
970129AG2-093 GEN
Solar/Wind Harmer
4.822
315722AD1-056 GEN
Solar/Wind Harmer
1.068
3146293MARTNCO
Solar/Wind Harmer
0.156
970401AG2-262 GEN
Solar/Wind Harmer
0.98
3145746EVERETS
Solar/Wind Harmer
0.166
3145746EVERETS
Solar/Wind Harmer
0.166
3142543TWELFTH
Solar/Wind Harmer
0.016
3138126ROCKLANDING
Solar/Wind Harmer
0.076
316494AC1-189 GEN
Solar/Wind Harmer
0.557
3146233WITAKRS
Solar/Wind Harmer
0.655
961671AG1-007 GEN
Solar/Wind Harmer
0.025
3146083TARBORO
Solar/Wind Harmer
0.164
3145493TOT1
Solar/Wind Harmer
0.728
972003AH1-546 GEN
Solar/Wind Harmer
6.917
3145543BTLEBRO
Solar/Wind Harmer
0.162
3145543BTLEBRO
Solar/Wind Harmer
0.13
316359AB2-059 GEN
Solar/Wind Harmer
0.583
316049AB1-081 GEN
Solar/Wind Harmer
0.929
3142053HEARTS
Solar/Wind Harmer
0.286
971317AH1-138 GEN
Solar/Wind Harmer
1.183
3143096IRON208
Adder
0.661
316159AE1-175 C
Solar/Wind Harmer
0.133
944631AF1-128 GEN
Adder
73.29
316003AC1-222 GEN
Solar/Wind Harmer
0.004
971377AH1-170 GEN
Solar/Wind Harmer
1.585
3147623JAMES R
Solar/Wind Harmer
0.344
3142433PROV 92
Solar/Wind Harmer
0.571
3142433PROV 92
Adder
0.278
3142433PROV 92
Adder
0.278
971777AH1-397 GEN
Solar/Wind Harmer
0.361
3141843SHACKLE
Adder
0.698
3141766HARMONY
Solar/Wind Harmer
0.027
3138133OCRAN
Solar/Wind Harmer
0.079
3142416OLDCHRC
Solar/Wind Harmer
0.323
3142416OLDCHRC
Solar/Wind Harmer
0.124
962861AG1-135 GEN
Solar/Wind Harmer
3.763
316045AC1-158 PL2
Solar/Wind Helper
10.623
316075AC2-137 C
Solar/Wind Harmer
0.037
3142296MT RD221
Adder
0.385
315821AE2-092 GEN
Solar/Wind Harmer
0.007
942751AE2-291 GEN
Solar/Wind Harmer
6.435
958261AF2-120 GEN
Solar/Wind Harmer
3.849
966871AG1-558 GEN
Solar/Wind Harmer
0.13
316447AC1-158 HLD
Solar/Wind Helper
7.304
LAGNLTFEXP_LAGN->PJM
CLTF
7.136
CBM South 2LTFEXP_CBM-S2->PJM
CBM
23.407
TVALTFEXP_TVA->PJM
CLTF
3.599
CPLELTFEXP_CPLE->PJM
CLTF
10.841
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.138
CBM West 1LTFEXP_CBM-W1->PJM
CBM
17.457
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.158
MECLTFEXP_MEC->PJM
CLTF
3.064
SIGELTFEXP_SIGE->PJM
CLTF
0.092
NYPJM->LTFIMP_NY
CLTF
2.896
LGEELTFEXP_LGEE->PJM
CLTF
1.093
WECLTFEXP_WEC->PJM
CLTF
0.529

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 550_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:139.38 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:4488.57
MW Contribution:7.77
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
3.9
971285AH1-108 GEN
50/50
1.587
315244AE2-183_ST
50/50
5.608
963041AG1-153 GEN
50/50
5.18
3151081ELIZAR1
50/50
18.835
3151091ELIZAR2
50/50
18.507
941591AE2-156 GEN
50/50
17.211
3152611GOSPORTB
50/50
2.615
3152621GOSPORTC
50/50
2.219
3152601GOSPORTA
50/50
2.047
315779AE2-040
50/50
2.695
316233AE1-074 FULL
Solar/Wind Harmer
0.168
971281AH1-106 GEN
Solar/Wind Harmer
2.908
971283AH1-107 GEN
Solar/Wind Harmer
2.908
941031AE2-094 GEN
Solar/Wind Harmer
37.055
944011AF1-069 GEN
Solar/Wind Harmer
12.107
970673AG2-436 GEN
Solar/Wind Harmer
42.239
970673AG2-436 GEN
Solar/Wind Harmer
28.159
3143316POE
Solar/Wind Harmer
0.778
971967AH1-528 GEN
Solar/Wind Harmer
31.346
316315AB2-025 C
Solar/Wind Harmer
0.156
315814AE2-033 C
Solar/Wind Harmer
15.221
957871AF2-081 GEN
Solar/Wind Harmer
9.573
971445AH1-216 GEN
Solar/Wind Harmer
13.53
319010AE1-072 C
Solar/Wind Harmer
0.966
3146406KITTY HAWK
Solar/Wind Harmer
0.024
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.131
316311AC2-079 GEN
Solar/Wind Harmer
5.504
316305AF2-043 C
Solar/Wind Harmer
0.002
972265AH1-717 GEN
Adder
14.862
3151201GRAVEL4
Adder
13.932
3151191GRAVEL3
Adder
13.756
3151211GRAVEL5
Adder
13.756
316369SG1_INVT
Solar/Wind Harmer
0.007
316132AB2-190 GEN1
Solar/Wind Harmer
1.025
315835AF2-110_GEN
Solar/Wind Harmer
1.31
313526AB2-022
Solar/Wind Harmer
0.103
3146486SUNBURY
Solar/Wind Harmer
0.19
3146486SUNBURY
Solar/Wind Harmer
0.19
316321Z2-027
Solar/Wind Harmer
0.035
3146396TANGLEW
Solar/Wind Harmer
0.523
3145176PASQUOTANK
Solar/Wind Harmer
0.118
970085AG2-068 GEN
Solar/Wind Harmer
9.972
970581AG2-369 GEN
Solar/Wind Harmer
8.576
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.184
3130156CHOWAN
Solar/Wind Harmer
0.184
315976AC1-164 GENA
Solar/Wind Harmer
18.981
316169AC1-164_GENC
Solar/Wind Harmer
16.398
315975AC1-164 GENB
Solar/Wind Harmer
0.562
316312AB1-027
Solar/Wind Harmer
0.327
3138283WHITEMARSH
Solar/Wind Harmer
0.042
971167AH1-042 GEN
Solar/Wind Harmer
16.183
3142433PROV 92
Adder
0.353
3142433PROV 92
Adder
0.353
315816AE2-034 GEN
Solar/Wind Harmer
0.777
3143873LANEXA
Solar/Wind Harmer
0.107
3130546PLYMOUTH
Solar/Wind Harmer
0.179
965291AG1-394 GEN
Solar/Wind Harmer
0.793
315732AD1-074 GEN1
Solar/Wind Harmer
1.024
315733AD1-074 GEN2
Solar/Wind Harmer
1.024
315735AD1-075 GEN1
Solar/Wind Harmer
0.513
970189AG2-124 GEN
Solar/Wind Harmer
5.251
316314AB2-024 C
Solar/Wind Harmer
0.001
3145893MURPHYS
Solar/Wind Harmer
0.478
3145893MURPHYS
Solar/Wind Harmer
0.177
3146206CASHIE
Solar/Wind Harmer
0.177
970601AG2-382 GEN
Solar/Wind Harmer
6.604
316059AD1-063 C
Solar/Wind Harmer
0.001
315662AE1-191 GEN
Solar/Wind Harmer
0.006
315666AE1-190 GEN
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.035
316087AB2-174 GEN
Solar/Wind Harmer
0.005
3146043SEABORD
Solar/Wind Harmer
0.175
3145513AHOSKIE
Solar/Wind Harmer
0.366
3145513AHOSKIE
Solar/Wind Harmer
0.175
315607AA1-063A GEN
Solar/Wind Harmer
0.356
3145683EARLEYS
Solar/Wind Harmer
0.348
3145683EARLEYS
Solar/Wind Harmer
0.174
3145683EARLEYS
Solar/Wind Harmer
0.174
3141913WHIT STONE
Solar/Wind Harmer
0.173
3137643SOCKMAN
Solar/Wind Harmer
0.691
315652AC1-086 GEN
Solar/Wind Harmer
18.996
3138133OCRAN
Solar/Wind Harmer
0.052
972189AH1-679 GEN
Adder
2.886
3141783LANCAST
Solar/Wind Harmer
0.103
3141783LANCAST
Solar/Wind Harmer
0.068
3145796HORNRTN
Solar/Wind Harmer
0.545
3145796HORNRTN
Solar/Wind Harmer
0.068
3146033SCOT NK
Solar/Wind Harmer
0.675
962981AG1-147 GEN
Solar/Wind Harmer
6.27
970831AG2-522 GEN
Solar/Wind Harmer
7.146
970327AG2-215 GEN
Solar/Wind Harmer
5.451
315657AE1-056 GEN
Solar/Wind Harmer
5.719
946301AF1-294 GEN
Solar/Wind Harmer
3.269
961791AG1-021 GEN
Solar/Wind Harmer
1.59
970683AG2-441 GEN
Solar/Wind Harmer
11.025
970681AG2-440 GEN
Solar/Wind Harmer
8.82
3144303KENBRDG
Solar/Wind Harmer
0.132
971443AH1-215 GEN
Solar/Wind Harmer
2.773
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
970285AG2-188 GEN
Solar/Wind Harmer
12.969
971845AH1-439 GEN
Solar/Wind Harmer
7.403
316005AA1-067
Solar/Wind Harmer
0.174
3145746EVERETS
Solar/Wind Harmer
0.646
3145746EVERETS
Solar/Wind Harmer
0.162
3145746EVERETS
Solar/Wind Harmer
0.162
3145746EVERETS
Solar/Wind Harmer
0.162
970181AG2-120 GEN
Solar/Wind Harmer
2.022
957861AF2-080 GEN
Solar/Wind Harmer
6.916
316420AA1-050 GEN
Solar/Wind Harmer
0.005
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.159
3145573BETHELC
Solar/Wind Harmer
0.159
972205AH1-687 GEN
Adder
6.755
3141813NORNECK
Solar/Wind Harmer
0.158
316118AC1-105 GEN
Solar/Wind Harmer
0.398
3147173SINAI
Solar/Wind Harmer
0.151
3147243WELCO
Solar/Wind Harmer
0.095
971447AH1-217 GEN
Solar/Wind Harmer
4.524
3150411LDYSMT5
Adder
19.288
3150381LDYSMT2
Adder
18.459
972213AH1-691 GEN
Adder
3.123
972215AH1-692 GEN
Adder
3.123
972193AH1-681 GEN
Adder
3.21
316223AC1-118
Solar/Wind Harmer
0.101
970865AG2-541 GEN
Solar/Wind Harmer
4.757
270494AE1-108_GEN
Solar/Wind Harmer
1.624
3138266HYDRAULIC
Solar/Wind Harmer
0.006
3138266HYDRAULIC
Solar/Wind Harmer
0.004
316123AC1-075 GEN
Solar/Wind Harmer
0.175
970165AG2-112 GEN
Solar/Wind Harmer
1.037
970163AG2-111 GEN
Solar/Wind Harmer
0.989
3147346CASHSCORNER
Solar/Wind Harmer
0.287
3148133STUARTS
Solar/Wind Harmer
0.072
3148013FISHERV
Solar/Wind Harmer
0.069
944491AF1-114 GEN
Solar/Wind Harmer
0
316164AC1-076 GEN
Solar/Wind Helper
1.589
3152251N ANNA1
50/50
17.859
970119AG2-088 GEN
50/50
29.254
3150851SPRUNCC
50/50
0.97
315243AE2-183_GT3
50/50
3.244
3151051BRUNSWICKS1
50/50
5.309
3151021BRUNSWICKG1
50/50
2.558
971451AH1-221 GEN
50/50
7.77
3150981CHESPKA
50/50
2.564
3147666LOUISA
Solar/Wind Harmer
0.93
316192AB2-158 GEN
Solar/Wind Harmer
1.282
3143226MDLTHAN
Solar/Wind Harmer
0.219
3143526WINTERP
Solar/Wind Harmer
1.09
940641AE2-051 GEN
Solar/Wind Harmer
16.431
939411AE1-173 GEN
Solar/Wind Harmer
86.344
316294AC1-161 GEN
Solar/Wind Harmer
3.388
3143336POWHATN
Solar/Wind Harmer
3.465
944591AF1-124 GEN
Solar/Wind Harmer
43.867
316375AC2-012 GEN
Solar/Wind Harmer
0.005
970659AG2-427 GEN
Solar/Wind Harmer
9.344
316381AD1-082 GEN
Solar/Wind Harmer
0.201
315671AE2-027_GEN
Solar/Wind Harmer
12.348
3142543TWELFTH
Solar/Wind Harmer
0.019
970661AG2-428 GEN
Solar/Wind Harmer
19.168
316388AE2-253 GEN
Solar/Wind Harmer
0.603
3145336SMITFLD
Solar/Wind Harmer
0.769
3146456SLIGO L269
Solar/Wind Harmer
0.192
316246AF1-032 C
Solar/Wind Harmer
0.086
3151171GRAVELC
Adder
2.036
316072AD1-144
Solar/Wind Harmer
0.069
961611AG1-000B GEN
Solar/Wind Harmer
10.034
971647AH1-324 GEN
Solar/Wind Harmer
8.16
971069AG2-661 GEN
Solar/Wind Harmer
3.398
316458AB2-190 GEN2
Solar/Wind Harmer
1.025
970129AG2-093 GEN
Solar/Wind Harmer
5.435
316093AE2-104_GEN
Solar/Wind Harmer
3.21
3143096IRON208
Adder
0.798
3138126ROCKLANDING
Solar/Wind Harmer
0.086
316336AC2-165 C
Solar/Wind Harmer
0.007
3146516WINFALL
Solar/Wind Harmer
0.61
3146516WINFALL
Solar/Wind Harmer
0.188
944631AF1-128 GEN
Adder
89.768
970919AG2-571 GEN
Solar/Wind Harmer
6.674
970087AG2-069 GEN
Solar/Wind Harmer
14.958
316159AE1-175 C
Solar/Wind Harmer
0.161
971317AH1-138 GEN
Solar/Wind Harmer
1.392
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.184
3142416OLDCHRC
Solar/Wind Harmer
0.475
3142416OLDCHRC
Solar/Wind Harmer
0.182
3142433PROV 92
Solar/Wind Harmer
0.726
3142433PROV 92
Adder
0.353
3142433PROV 92
Adder
0.353
3145663CRESWEL
Solar/Wind Harmer
0.507
971163AH1-040 GEN
Solar/Wind Harmer
14.49
957481AF2-042 GEN
Solar/Wind Harmer
48.274
316023GEN1_S
Solar/Wind Harmer
0.403
315693AD1-088 GEN
Solar/Wind Harmer
8.563
962491AG1-098 GEN
Solar/Wind Harmer
10.161
971777AH1-397 GEN
Solar/Wind Harmer
0.468
3141843SHACKLE
Adder
0.905
3145893MURPHYS
Solar/Wind Harmer
0.708
3145893MURPHYS
Solar/Wind Harmer
0.787
3152261N ANNA2
50/50
17.858
3150861SPRUNCD
50/50
0.97
3151031BRUNSWICKG2
50/50
2.558
3151101ELIZAR3
50/50
19.076
3147666LOUISA
Solar/Wind Harmer
0.535
315773AC2-141 GEN
Solar/Wind Harmer
7.141
316313AB2-026
Solar/Wind Harmer
0.123
316258AE1-075 C
Solar/Wind Harmer
0.147
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
2.946
315839AE2-212 C
Solar/Wind Harmer
0.002
944581AF1-123 GEN
Solar/Wind Harmer
43.712
944601AF1-125 GEN
Solar/Wind Harmer
43.039
315813AE1-149 C
Solar/Wind Harmer
10.345
3144873MCLAUGH
Solar/Wind Harmer
0.005
965281AG1-393 GEN
Solar/Wind Harmer
2.063
3144536CHRHLND
Solar/Wind Harmer
0.029
970659AG2-427 GEN
Solar/Wind Harmer
2.044
316083AB2-161 GEN
Solar/Wind Harmer
0.003
970661AG2-428 GEN
Solar/Wind Harmer
4.077
3145336SMITFLD
Solar/Wind Harmer
0.077
3146456SLIGO L269
Solar/Wind Harmer
0.192
971153AH1-033 GEN
Solar/Wind Harmer
2.219
3151221GRAVEL6
Adder
13.916
3151171GRAVELC
Adder
2.677
961611AG1-000B GEN
Solar/Wind Harmer
5.102
315778AD1-151 GEN
Solar/Wind Harmer
15.292
970129AG2-093 GEN
Solar/Wind Harmer
11.549
970133AG2-095 GEN
Solar/Wind Harmer
1.833
3143096IRON208
Adder
0.798
3143096IRON208
Adder
0.782
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3144216WINCHST
Adder
0.711
3146516WINFALL
Solar/Wind Harmer
0.188
3150921YORKTN3
Adder
4.73
970917AG2-570 GEN
Solar/Wind Harmer
16.684
3146626S HERTFORD
Solar/Wind Harmer
0.187
3145273HOLLAND
Solar/Wind Harmer
0.14
3142946ENON
Solar/Wind Harmer
0.062
316382AG1-145 C
Solar/Wind Harmer
0.001
970293AG2-193 GEN
Solar/Wind Harmer
1.978
3146376EDENTON
Solar/Wind Harmer
0.184
3142416OLDCHRC
Solar/Wind Harmer
1.77
3142433PROV 92
Adder
0.353
3142433PROV 92
Adder
0.353
315614AA2-178 GEN
Solar/Wind Harmer
1.037
316365GEN2_N
Solar/Wind Harmer
0.403
3156081AA2-088 GEN
Solar/Wind Harmer
0.004
971157AH1-035 GEN
Solar/Wind Harmer
2.144
315737AD1-076 GEN
Solar/Wind Harmer
2.293
3141843SHACKLE
Adder
0.905
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3145893MURPHYS
Solar/Wind Harmer
0.296
3145893MURPHYS
Solar/Wind Harmer
0.177
3146206CASHIE
Solar/Wind Harmer
0.177
3141766HARMONY
Solar/Wind Harmer
2.356
971133AH1-012 GEN
50/50
4.909
970533AG2-339 GEN
50/50
17.884
970531AG2-338 GEN
50/50
7.154
315242AE2-183_GT2
50/50
3.244
315241AE2-183_GT1
50/50
3.224
972185AH1-677 GEN
50/50
11.694
3151041BRUNSWICKG3
50/50
2.558
972187AH1-678 GEN
50/50
5.87
3150991CHESPKB
50/50
2.151
3150991CHESPKB
50/50
2.099
971223AH1-071 GEN
Solar/Wind Harmer
2.34
3143526WINTERP
Solar/Wind Harmer
1.09
316036AC1-147 C
Solar/Wind Harmer
0.036
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.186
316185AD1-033 GEN
Solar/Wind Harmer
0.006
316240AF1-291 C
Solar/Wind Harmer
0.002
3144356SAPONY
Solar/Wind Harmer
1.615
3145506HICKORY
Solar/Wind Harmer
0.772
3145506HICKORY
Solar/Wind Harmer
0.463
3145506HICKORY
Solar/Wind Harmer
0.116
970657AG2-426 GEN
Solar/Wind Harmer
6.758
970657AG2-426 GEN
Solar/Wind Harmer
1.417
944641AF1-129 GEN
Adder
91.865
316339AD2-160 GEN
Solar/Wind Harmer
0.312
316018AA1-139 ULT2
Solar/Wind Harmer
0.005
316017AA1-139 ULT1
Solar/Wind Harmer
0.107
316236AE1-162_GEN
Solar/Wind Harmer
0.002
3137176SLIGO L2192
Solar/Wind Harmer
0.764
3146456SLIGO L269
Solar/Wind Harmer
3.397
970933AG2-581 GEN
Solar/Wind Harmer
15.345
3130086AYDLETT
Solar/Wind Harmer
0.767
316033AB2-134 GEN
Solar/Wind Harmer
0.011
315697AD1-025 GEN
Solar/Wind Harmer
0.215
3146386ELIZ CT
Solar/Wind Harmer
0.19
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.188
3146516WINFALL
Solar/Wind Harmer
0.188
3146516WINFALL
Solar/Wind Harmer
0.188
3142366NRTHEST
Adder
0.613
3146626S HERTFORD
Solar/Wind Harmer
0.187
3146626S HERTFORD
Solar/Wind Harmer
0.187
3150691DARBY 3
Adder
13.444
3150701DARBY 4
Adder
13.412
3150681DARBY 2
Adder
13.397
3150671DARBY 1
Adder
13.381
3142946ENON
Solar/Wind Harmer
0.019
315742AE1-103 GEN
Solar/Wind Harmer
0.002
3146376EDENTON
Solar/Wind Harmer
0.819
3146376EDENTON
Solar/Wind Harmer
0.819
316075AC2-137 C
Solar/Wind Harmer
0.051
3142296MT RD221
Adder
0.584
970099AG2-077 GEN
Solar/Wind Harmer
19.31
316065AD1-022 GEN
Solar/Wind Harmer
8.167
3145893MURPHYS
Solar/Wind Harmer
1.184
3145893MURPHYS
Solar/Wind Harmer
0.318
966871AG1-558 GEN
Solar/Wind Harmer
0.203
3146173TUNIS
Solar/Wind Harmer
0.175
3146173TUNIS
Solar/Wind Harmer
0.175
316181AB2-040 GEN
Solar/Wind Harmer
0.253
971741AH1-377 GEN
Solar/Wind Harmer
17.193
3142666NORTHAMPTON
Solar/Wind Harmer
0.173
3142666NORTHAMPTON
Solar/Wind Harmer
0.173
3142666NORTHAMPTON
Solar/Wind Harmer
0.173
3142666NORTHAMPTON
Solar/Wind Harmer
0.104
316426AA2-053 GEN
Solar/Wind Harmer
0.582
3145593CAROLNA
Solar/Wind Harmer
0.172
3145593CAROLNA
Solar/Wind Harmer
0.172
966811AG1-552 GEN
Solar/Wind Harmer
1.864
3145593CAROLNA
Solar/Wind Harmer
0.214
970301AG2-198 GEN
Solar/Wind Harmer
7.33
3145783HORNRTN
Solar/Wind Harmer
3.038
3145783HORNRTN
Solar/Wind Harmer
2.431
3145783HORNRTN
Solar/Wind Harmer
0.76
3145783HORNRTN
Solar/Wind Harmer
0.304
3145796HORNRTN
Solar/Wind Harmer
0.511
3147133PAMPLIN
Solar/Wind Harmer
0.166
3147133PAMPLIN
Solar/Wind Harmer
0.133
316274AC1-208 GEN
Solar/Wind Harmer
0.86
958211AF2-115 GEN
Solar/Wind Harmer
1.988
963191AG1-168 GEN
Solar/Wind Harmer
0.663
3144293JTRSVLE
Adder
0.527
3144293JTRSVLE
Adder
0.444
3145933PARMELE
Solar/Wind Harmer
0.33
3145933PARMELE
Solar/Wind Harmer
0.165
316034AC1-036 C
Solar/Wind Harmer
0.012
970323AG2-213 GEN
Solar/Wind Harmer
7.044
971775AH1-396 GEN
Solar/Wind Harmer
0.264
313527AB2-043 GEN
Solar/Wind Harmer
0.002
939181AE1-148 GEN
Solar/Wind Harmer
7.892
958261AF2-120 GEN
Solar/Wind Harmer
5.394
3146776BUCKING
Solar/Wind Harmer
0.651
3146776BUCKING
Solar/Wind Harmer
0.053
3145493TOT1
Solar/Wind Harmer
0.368
3145453TOT5
Solar/Wind Harmer
0.221
3145603CNETO
Solar/Wind Harmer
0.147
316280AD1-041 GEN
Solar/Wind Harmer
0.004
957521AF2-046 GEN
Solar/Wind Harmer
13.141
961681AG1-008 GEN
Solar/Wind Harmer
13.141
316156AD2-030 GEN
Solar/Wind Harmer
0.13
3141873WAN 176
Solar/Wind Harmer
3.131
316473AC1-191 GEN
Solar/Wind Harmer
0.594
3146173TUNIS
Solar/Wind Harmer
0.175
3156021HOLLOMANSOL
Solar/Wind Harmer
0.794
316463AE2-346 GEN
Solar/Wind Harmer
0.15
316140AB2-099
Solar/Wind Harmer
0.062
962331AG1-082 GEN
Solar/Wind Harmer
1.865
316478AD1-087 GEN
Solar/Wind Harmer
0.61
316486AD2-202 GEN
Solar/Wind Harmer
0.179
313506AB2-031 GEN
Solar/Wind Harmer
0.538
3146263WOODLND
Solar/Wind Harmer
0.173
3142666NORTHAMPTON
Solar/Wind Harmer
0.173
3147043LAWRENC
Solar/Wind Harmer
0.104
970909AG2-566 GEN
Solar/Wind Harmer
1.833
316317KELFORD C
Solar/Wind Harmer
0.017
3145823KELFORD
Solar/Wind Harmer
0.171
3145963POPLR C
Solar/Wind Harmer
0.171
3145796HORNRTN
Solar/Wind Harmer
0.681
3145796HORNRTN
Solar/Wind Harmer
0.17
962971AG1-146 GEN
Solar/Wind Harmer
2.687
3146926FARMVIL
Solar/Wind Harmer
0.1
316210AC1-098 GEN
Solar/Wind Harmer
1.545
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970009AG2-005 GEN
Solar/Wind Harmer
1.24
3147133PAMPLIN
Solar/Wind Harmer
0.52
971193AH1-056 GEN
Solar/Wind Harmer
10.097
963181AG1-167 GEN
Solar/Wind Harmer
0.663
3144293JTRSVLE
Adder
0.527
3145933PARMELE
Solar/Wind Harmer
0.165
966801AG1-551 GEN
Solar/Wind Harmer
1.925
959311AF2-222 GEN
Solar/Wind Harmer
14.682
970257AG2-171 GEN
Solar/Wind Harmer
5.283
315785AD2-033 C
Solar/Wind Harmer
1.341
964241AG1-285 GEN
Solar/Wind Harmer
10.979
316131AB2-060 GEN
Solar/Wind Harmer
0.517
3146206CASHIE
Solar/Wind Harmer
0.177
971547AH1-271 GEN
Solar/Wind Harmer
3.773
3141766HARMONY
Solar/Wind Harmer
0.035
960081AF2-299 GEN
Solar/Wind Harmer
1.693
3146173TUNIS
Solar/Wind Harmer
0.175
3145683EARLEYS
Solar/Wind Harmer
0.174
971795AH1-408 GEN
Solar/Wind Harmer
11.591
3146263WOODLND
Solar/Wind Harmer
0.173
316011AB1-132 GEN
Solar/Wind Harmer
3.14
962571AG1-106 GEN
Solar/Wind Harmer
2.457
3147043LAWRENC
Adder
1.563
3138133OCRAN
Solar/Wind Harmer
0.104
316190AA2-174 GEN
Solar/Wind Harmer
0
970937AG2-583 GEN
Solar/Wind Harmer
10.553
3145823KELFORD
Solar/Wind Harmer
0.171
3145963POPLR C
Solar/Wind Harmer
0.171
3145783HORNRTN
Solar/Wind Harmer
0.171
3145796HORNRTN
Solar/Wind Harmer
0.562
3145796HORNRTN
Solar/Wind Harmer
0.17
316174AB2-169 GEN
Solar/Wind Harmer
0.005
316129AC1-054 GEN
Solar/Wind Harmer
0.628
3146926FARMVIL
Solar/Wind Harmer
0.1
971065AG2-659 GEN
Solar/Wind Harmer
7.107
316212AC1-099_GEN
Solar/Wind Harmer
0.862
963171AG1-166 GEN
Solar/Wind Harmer
0.883
971563AH1-280 GEN
Solar/Wind Harmer
1.767
3144293JTRSVLE
Adder
0.527
315687AD1-152 GEN
Solar/Wind Harmer
0.005
970685AG2-442 GEN
Solar/Wind Harmer
12.348
3146293MARTNCO
Solar/Wind Harmer
0.153
316237AB2-079_GEN
Solar/Wind Harmer
0.001
962861AG1-135 GEN
Solar/Wind Harmer
5.245
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.065
315722AD1-056 GEN
Solar/Wind Harmer
1.03
3145746EVERETS
Solar/Wind Harmer
0.162
3145746EVERETS
Solar/Wind Harmer
0.162
316494AC1-189 GEN
Solar/Wind Harmer
0.542
3141726DUNNSVL
Solar/Wind Harmer
0.64
3146233WITAKRS
Solar/Wind Harmer
0.633
972003AH1-546 GEN
Solar/Wind Harmer
6.756
961671AG1-007 GEN
Solar/Wind Harmer
0.024
3146083TARBORO
Solar/Wind Harmer
0.159
3145493TOT1
Solar/Wind Harmer
0.705
3150351NORNECKC2
Adder
1.573
970401AG2-262 GEN
Solar/Wind Harmer
0.92
966881AG1-559 GEN
Solar/Wind Harmer
0.181
3145543BTLEBRO
Solar/Wind Harmer
0.156
3145543BTLEBRO
Solar/Wind Harmer
0.125
316359AB2-059 GEN
Solar/Wind Harmer
0.562
316049AB1-081 GEN
Solar/Wind Harmer
0.896
3142053HEARTS
Solar/Wind Harmer
0.276
971377AH1-170 GEN
Solar/Wind Harmer
1.611
3147623JAMES R
Solar/Wind Harmer
0.35
316337AD2-073 GEN
Solar/Wind Harmer
0.13
316003AC1-222 GEN
Solar/Wind Harmer
0.004
972197AH1-683 GEN
Adder
3.003
972219AH1-694 GEN
Adder
2.162
972277AH1-723 GEN
Adder
83.718
3151751LOISA D
Adder
8.35
972135AH1-637 GEN
Solar/Wind Harmer
1.077
316045AC1-158 PL2
Solar/Wind Helper
17.1
316006AB2-029 C
Solar/Wind Helper
0.112
316404AE1-155 C
Solar/Wind Harmer
0.037
3146776BUCKING
Solar/Wind Harmer
0.059
315724AD1-057 GEN
Solar/Wind Harmer
0.611
3145746EVERETS
Solar/Wind Harmer
0.162
3145746EVERETS
Solar/Wind Harmer
0.162
316327AA2-057 GEN
Solar/Wind Harmer
0.244
3146233WITAKRS
Solar/Wind Harmer
0.798
3146233WITAKRS
Solar/Wind Harmer
0.108
3138543CONSLDL
Solar/Wind Harmer
0.105
3146073TAR RVR
Solar/Wind Harmer
0.159
3146083TARBORO
Solar/Wind Harmer
0.159
3150351NORNECKC2
Adder
1.599
961601AG1-000A GEN
Solar/Wind Harmer
11.13
3145543BTLEBRO
Solar/Wind Harmer
0.156
3145543BTLEBRO
Solar/Wind Harmer
0.156
971623AH1-311 GEN
Solar/Wind Harmer
0.313
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
6.457
970221AG2-151 GEN
Solar/Wind Harmer
8.055
971781AH1-399 GEN
Solar/Wind Harmer
0.196
3150401LDYSMT4
Adder
19.228
3150371LDYSMT1
Adder
18.579
971683AH1-343 GEN
Solar/Wind Harmer
5.218
972255AH1-712 GEN
Adder
71.842
3141906WESTMOR
Solar/Wind Harmer
0.056
316283AC2-100 C
Solar/Wind Harmer
0.267
970737AG2-469 GEN
Solar/Wind Harmer
5.623
3151761LOISA E
Adder
17.023
972183AH1-676 GEN
Adder
131.964
3148013FISHERV
Solar/Wind Harmer
0.119
316044AC1-158 PL1
Solar/Wind Helper
5.342
316450AC1-158 RIC
Solar/Wind Helper
1.425
962561AG1-105 GEN
Solar/Wind Harmer
7.584
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
1.652
3150341NORNECKC1
Adder
1.639
957411AF2-035 GEN
Solar/Wind Harmer
6.692
970317AG2-208 GEN
Solar/Wind Harmer
6.2
964791AG1-342 GEN
Solar/Wind Harmer
3.011
3146843MT LREL
Solar/Wind Harmer
0.157
3146843MT LREL
Solar/Wind Harmer
0.157
961601AG1-000A GEN
Solar/Wind Harmer
2.783
316263AC1-034 GEN
Solar/Wind Harmer
5.946
315673AE1-157 GEN
Solar/Wind Harmer
10.504
971489AH1-241 GEN
Solar/Wind Harmer
8.055
316468AD1-105 GEN
Solar/Wind Harmer
-0.048
3150391LDYSMT3
Adder
19.192
972195AH1-682 GEN
Adder
2.522
315821AE2-092 GEN
Solar/Wind Harmer
0.008
316222AC1-221 GEN
Solar/Wind Harmer
0.569
3151731LOISA B
Adder
8.35
3151721LOISA A
Adder
8.307
942751AE2-291 GEN
Solar/Wind Harmer
6.634
316447AC1-158 HLD
Solar/Wind Helper
11.757
LAGNLTFEXP_LAGN->PJM
CLTF
7.614
CBM South 2LTFEXP_CBM-S2->PJM
CBM
23.287
TVALTFEXP_TVA->PJM
CLTF
3.882
CPLELTFEXP_CPLE->PJM
CLTF
10.454
CBM West 2LTFEXP_CBM-W2->PJM
CBM
39.305
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.914
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.208
MECLTFEXP_MEC->PJM
CLTF
3.421
SIGELTFEXP_SIGE->PJM
CLTF
0.105
NYPJM->LTFIMP_NY
CLTF
2.812
LGEELTFEXP_LGEE->PJM
CLTF
1.277
WECLTFEXP_WEC->PJM
CLTF
0.604

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P2-2: NORTH ANNA B2_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: NORTH ANNA B2_SRT-S
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:128.28 %
Rating:3118.0 MVA
Rating Type:C
MVA to Mitigate:3999.66
MW Contribution:7.19
Bus #Bus NameTypeMW Contribution
3152251N ANNA1
50/50
17.599
970119AG2-088 GEN
50/50
27.254
3150851SPRUNCC
50/50
0.898
315243AE2-183_GT3
50/50
3.006
3151051BRUNSWICKS1
50/50
4.913
3151021BRUNSWICKG1
50/50
2.367
971451AH1-221 GEN
50/50
7.19
3150981CHESPKA
50/50
2.372
3147666LOUISA
Solar/Wind Harmer
-0.099
316192AB2-158 GEN
Solar/Wind Harmer
2.866
3143226MDLTHAN
Solar/Wind Harmer
-0.023
3143526WINTERP
Solar/Wind Harmer
-0.113
940641AE2-051 GEN
Solar/Wind Harmer
20.147
939411AE1-173 GEN
Solar/Wind Harmer
105.7
316294AC1-161 GEN
Solar/Wind Harmer
6.579
944591AF1-124 GEN
Solar/Wind Harmer
92.147
316375AC2-012 GEN
Solar/Wind Harmer
6.96
970659AG2-427 GEN
Solar/Wind Harmer
10.669
316381AD1-082 GEN
Solar/Wind Harmer
1.84
315671AE2-027_GEN
Solar/Wind Harmer
15.038
970661AG2-428 GEN
Solar/Wind Harmer
21.272
3142543TWELFTH
Solar/Wind Harmer
-0.002
316388AE2-253 GEN
Solar/Wind Harmer
1.348
3145336SMITFLD
Solar/Wind Harmer
-0.079
3146456SLIGO L269
Solar/Wind Harmer
-0.02
316246AF1-032 C
Solar/Wind Harmer
0.403
3151171GRAVELC
Adder
1.882
316072AD1-144
Solar/Wind Harmer
0.402
961611AG1-000B GEN
Solar/Wind Harmer
9.803
971647AH1-324 GEN
Solar/Wind Harmer
9.928
971069AG2-661 GEN
Solar/Wind Harmer
3.14
316458AB2-190 GEN2
Solar/Wind Harmer
2.006
970129AG2-093 GEN
Solar/Wind Harmer
4.523
316093AE2-104_GEN
Solar/Wind Harmer
5.759
3143096IRON208
Adder
0.737
3143336POWHATN
Solar/Wind Harmer
2.321
3138126ROCKLANDING
Solar/Wind Harmer
0.06
3146516WINFALL
Solar/Wind Harmer
-0.063
3146516WINFALL
Solar/Wind Harmer
-0.019
944631AF1-128 GEN
Adder
82.804
970919AG2-571 GEN
Solar/Wind Harmer
6.156
970087AG2-069 GEN
Solar/Wind Harmer
18.16
971317AH1-138 GEN
Solar/Wind Harmer
2.416
316159AE1-175 C
Solar/Wind Harmer
0.519
315800Z1-036_GEN1
Solar/Wind Harmer
4.76
3130156CHOWAN
Solar/Wind Harmer
-0.019
3142416OLDCHRC
Solar/Wind Harmer
-0.049
3142416OLDCHRC
Solar/Wind Harmer
-0.019
3142433PROV 92
Solar/Wind Harmer
-0.075
3142433PROV 92
Adder
0.325
3142433PROV 92
Adder
0.325
3145663CRESWEL
Solar/Wind Harmer
-0.052
971163AH1-040 GEN
Solar/Wind Harmer
17.53
316336AC2-165 C
Solar/Wind Harmer
3.244
316023GEN1_S
Solar/Wind Harmer
1.25
957481AF2-042 GEN
Solar/Wind Harmer
57.87
971777AH1-397 GEN
Solar/Wind Harmer
2.159
3141843SHACKLE
Adder
0.835
3141766HARMONY
Solar/Wind Harmer
-0.004
3146206CASHIE
Solar/Wind Harmer
-0.018
971547AH1-271 GEN
Solar/Wind Harmer
4.553
3145893MURPHYS
Solar/Wind Harmer
-0.072
3145893MURPHYS
Solar/Wind Harmer
0.54
315693AD1-088 GEN
Solar/Wind Harmer
9.06
960081AF2-299 GEN
Solar/Wind Harmer
2.034
962491AG1-098 GEN
Solar/Wind Harmer
12.078
3146173TUNIS
Solar/Wind Harmer
-0.018
3138133OCRAN
Solar/Wind Harmer
-0.011
3145683EARLEYS
Solar/Wind Harmer
-0.018
3146263WOODLND
Solar/Wind Harmer
-0.018
971795AH1-408 GEN
Solar/Wind Harmer
13.31
316011AB1-132 GEN
Solar/Wind Harmer
3.709
962571AG1-106 GEN
Solar/Wind Harmer
2.548
316190AA2-174 GEN
Solar/Wind Harmer
0.217
3147043LAWRENC
Adder
1.417
3145963POPLR C
Solar/Wind Harmer
-0.018
3145823KELFORD
Solar/Wind Harmer
-0.018
3145783HORNRTN
Solar/Wind Harmer
-0.017
3145796HORNRTN
Solar/Wind Harmer
-0.057
316303AF2-085
50/50
3.634
971285AH1-108 GEN
50/50
1.469
315244AE2-183_ST
50/50
5.196
963041AG1-153 GEN
50/50
4.793
3151081ELIZAR1
50/50
17.423
3151091ELIZAR2
50/50
17.121
941591AE2-156 GEN
50/50
15.921
3152611GOSPORTB
50/50
2.419
3152621GOSPORTC
50/50
2.053
3152601GOSPORTA
50/50
1.894
315779AE2-040
50/50
2.493
316233AE1-074 FULL
Solar/Wind Harmer
0.589
971281AH1-106 GEN
Solar/Wind Harmer
3.557
971283AH1-107 GEN
Solar/Wind Harmer
3.557
941031AE2-094 GEN
Solar/Wind Harmer
39.382
944011AF1-069 GEN
Solar/Wind Harmer
12.34
970673AG2-436 GEN
Solar/Wind Harmer
43.344
970673AG2-436 GEN
Solar/Wind Harmer
21.946
3143316POE
Solar/Wind Harmer
-0.08
971967AH1-528 GEN
Solar/Wind Harmer
38.278
316315AB2-025 C
Solar/Wind Harmer
0.541
315814AE2-033 C
Solar/Wind Harmer
18.612
957871AF2-081 GEN
Solar/Wind Harmer
9.987
971445AH1-216 GEN
Solar/Wind Harmer
12.352
319010AE1-072 C
Solar/Wind Harmer
4.03
3146406KITTY HAWK
Solar/Wind Harmer
0.017
315833AF1-017_GEN
Solar/Wind Harmer
3.781
316349AD2-085 GEN
Solar/Wind Harmer
1.77
316311AC2-079 GEN
Solar/Wind Harmer
10.04
316305AF2-043 C
Solar/Wind Harmer
0.6
972265AH1-717 GEN
Adder
13.734
3151201GRAVEL4
Adder
12.875
3151191GRAVEL3
Adder
12.712
3151211GRAVEL5
Adder
12.712
316369SG1_INVT
Solar/Wind Harmer
3.546
316132AB2-190 GEN1
Solar/Wind Harmer
2.006
315835AF2-110_GEN
Solar/Wind Harmer
2.476
313526AB2-022
Solar/Wind Harmer
0.533
3146486SUNBURY
Solar/Wind Harmer
-0.02
3146486SUNBURY
Solar/Wind Harmer
-0.02
316321Z2-027
Solar/Wind Harmer
0.531
3146396TANGLEW
Solar/Wind Harmer
0.362
3145176PASQUOTANK
Solar/Wind Harmer
-0.012
970085AG2-068 GEN
Solar/Wind Harmer
12.107
970581AG2-369 GEN
Solar/Wind Harmer
10.412
315611Z1-036_GEN2
Solar/Wind Harmer
4.76
3130156CHOWAN
Solar/Wind Harmer
-0.019
3130156CHOWAN
Solar/Wind Harmer
-0.019
315976AC1-164 GENA
Solar/Wind Harmer
19.998
316169AC1-164_GENC
Solar/Wind Harmer
17.276
315975AC1-164 GENB
Solar/Wind Harmer
0.592
957831AF2-077 GEN
Solar/Wind Harmer
0.569
3138283WHITEMARSH
Solar/Wind Harmer
0.029
971167AH1-042 GEN
Solar/Wind Harmer
18.178
316312AB1-027
Solar/Wind Harmer
0.636
3142433PROV 92
Adder
0.325
3142433PROV 92
Adder
0.325
315816AE2-034 GEN
Solar/Wind Harmer
1.513
3143873LANEXA
Solar/Wind Harmer
-0.011
3130546PLYMOUTH
Solar/Wind Harmer
-0.018
315732AD1-074 GEN1
Solar/Wind Harmer
3.714
315733AD1-074 GEN2
Solar/Wind Harmer
3.714
315735AD1-075 GEN1
Solar/Wind Harmer
1.858
965291AG1-394 GEN
Solar/Wind Harmer
1.63
316314AB2-024 C
Solar/Wind Harmer
1.568
3145796HORNRTN
Solar/Wind Harmer
-0.017
316174AB2-169 GEN
Solar/Wind Harmer
2.689
961951AG1-038 GEN
Solar/Wind Harmer
2.268
316212AC1-099_GEN
Solar/Wind Harmer
1.483
962861AG1-135 GEN
Solar/Wind Harmer
6.373
316129AC1-054 GEN
Solar/Wind Harmer
1.485
3150351NORNECKC2
Adder
1.452
3144293JTRSVLE
Adder
0.462
972197AH1-683 GEN
Adder
2.865
972219AH1-694 GEN
Adder
2.063
316045AC1-158 PL2
Solar/Wind Helper
17.173
316006AB2-029 C
Solar/Wind Helper
0.112
971133AH1-012 GEN
50/50
4.727
970533AG2-339 GEN
50/50
16.617
970531AG2-338 GEN
50/50
6.647
315242AE2-183_GT2
50/50
3.006
315241AE2-183_GT1
50/50
2.987
972185AH1-677 GEN
50/50
10.835
3151041BRUNSWICKG3
50/50
2.367
972187AH1-678 GEN
50/50
5.432
3150991CHESPKB
50/50
1.99
3150991CHESPKB
50/50
1.942
971223AH1-071 GEN
Solar/Wind Harmer
2.871
3143526WINTERP
Solar/Wind Harmer
-0.113
316036AC1-147 C
Solar/Wind Harmer
0.543
3142956BIRDNECK
Solar/Wind Harmer
1.078
316316AC1-027 C
Solar/Wind Harmer
0.617
316185AD1-033 GEN
Solar/Wind Harmer
2.119
316240AF1-291 C
Solar/Wind Harmer
0.605
3144356SAPONY
Solar/Wind Harmer
0.7
3145506HICKORY
Solar/Wind Harmer
-0.08
3145506HICKORY
Solar/Wind Harmer
-0.048
3145506HICKORY
Solar/Wind Harmer
-0.012
970657AG2-426 GEN
Solar/Wind Harmer
6.265
970657AG2-426 GEN
Solar/Wind Harmer
1.31
944641AF1-129 GEN
Adder
84.93
316339AD2-160 GEN
Solar/Wind Harmer
1.348
316018AA1-139 ULT2
Solar/Wind Harmer
1.711
316017AA1-139 ULT1
Solar/Wind Harmer
1.616
316236AE1-162_GEN
Solar/Wind Harmer
0.602
3137176SLIGO L2192
Solar/Wind Harmer
-0.079
3146456SLIGO L269
Solar/Wind Harmer
2.355
3130086AYDLETT
Solar/Wind Harmer
-0.079
970933AG2-581 GEN
Solar/Wind Harmer
18.608
316033AB2-134 GEN
Solar/Wind Harmer
6.401
315697AD1-025 GEN
Solar/Wind Harmer
4.014
3146386ELIZ CT
Solar/Wind Harmer
-0.02
316431W1029_GEN1
Solar/Wind Harmer
3.546
316433W1029_GEN2
Solar/Wind Harmer
3.546
3146516WINFALL
Solar/Wind Harmer
-0.019
3146516WINFALL
Solar/Wind Harmer
-0.019
3146516WINFALL
Solar/Wind Harmer
-0.019
3142366NRTHEST
Adder
0.565
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3142946ENON
Solar/Wind Harmer
-0.002
3150691DARBY 3
Adder
12.388
3150701DARBY 4
Adder
12.359
3150681DARBY 2
Adder
12.344
3150671DARBY 1
Adder
12.33
315742AE1-103 GEN
Solar/Wind Harmer
2.005
3146376EDENTON
Solar/Wind Harmer
0.566
3146376EDENTON
Solar/Wind Harmer
0.566
316075AC2-137 C
Solar/Wind Harmer
0.513
3142296MT RD221
Adder
0.537
970099AG2-077 GEN
Solar/Wind Harmer
23.148
316441AF1-014 GEN
Solar/Wind Harmer
1.237
316065AD1-022 GEN
Solar/Wind Harmer
9.134
3145893MURPHYS
Solar/Wind Harmer
0.508
3145893MURPHYS
Solar/Wind Harmer
-0.033
966871AG1-558 GEN
Solar/Wind Harmer
0.547
966871AG1-558 GEN
Solar/Wind Harmer
0.187
3146173TUNIS
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
316181AB2-040 GEN
Solar/Wind Harmer
2.49
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.011
316426AA2-053 GEN
Solar/Wind Harmer
1.782
3145593CAROLNA
Solar/Wind Harmer
-0.018
3145593CAROLNA
Solar/Wind Harmer
-0.018
966811AG1-552 GEN
Solar/Wind Harmer
1.979
3145593CAROLNA
Solar/Wind Harmer
0.146
3145783HORNRTN
Solar/Wind Harmer
2.075
3145783HORNRTN
Solar/Wind Harmer
1.66
3145783HORNRTN
Solar/Wind Harmer
0.519
3145783HORNRTN
Solar/Wind Harmer
0.207
3145796HORNRTN
Solar/Wind Harmer
-0.052
971741AH1-377 GEN
Solar/Wind Harmer
20.037
316487AF1-042 GEN
Solar/Wind Harmer
2.268
970301AG2-198 GEN
Solar/Wind Harmer
8.487
316274AC1-208 GEN
Solar/Wind Harmer
1.826
3150341NORNECKC1
Adder
1.525
3150341NORNECKC1
Adder
1.513
3144293JTRSVLE
Adder
0.462
3144293JTRSVLE
Adder
0.389
3150391LDYSMT3
Adder
18.314
972195AH1-682 GEN
Adder
2.407
316447AC1-158 HLD
Solar/Wind Helper
11.807
958261AF2-120 GEN
Solar/Wind Harmer
3.594
315662AE1-191 GEN
Solar/Wind Harmer
2.207
315666AE1-190 GEN
Solar/Wind Harmer
0.552
316059AD1-063 C
Solar/Wind Harmer
0.414
957601AF2-054 GEN
Solar/Wind Harmer
0.546
3141873WAN 176
Solar/Wind Harmer
-0.004
3146206CASHIE
Solar/Wind Harmer
-0.018
970601AG2-382 GEN
Solar/Wind Harmer
7.968
316318V4-068
Solar/Wind Harmer
0.454
3145893MURPHYS
Solar/Wind Harmer
-0.049
3145893MURPHYS
Solar/Wind Harmer
-0.018
946281AF1-292 GEN
Solar/Wind Harmer
0.405
3145513AHOSKIE
Solar/Wind Harmer
0.157
961941AG1-037 GEN
Solar/Wind Harmer
0.135
3145513AHOSKIE
Solar/Wind Harmer
-0.018
3141913WHIT STONE
Solar/Wind Harmer
-0.018
3146043SEABORD
Solar/Wind Harmer
-0.018
316087AB2-174 GEN
Solar/Wind Harmer
2.556
972189AH1-679 GEN
Adder
2.672
3138133OCRAN
Solar/Wind Harmer
-0.005
315607AA1-063A GEN
Solar/Wind Harmer
1.808
3145683EARLEYS
Solar/Wind Harmer
-0.036
3145683EARLEYS
Solar/Wind Harmer
-0.018
3145683EARLEYS
Solar/Wind Harmer
-0.018
3141783LANCAST
Solar/Wind Harmer
-0.011
3141783LANCAST
Solar/Wind Harmer
-0.007
315652AC1-086 GEN
Solar/Wind Harmer
19.944
3137643SOCKMAN
Solar/Wind Harmer
-0.07
3145796HORNRTN
Solar/Wind Harmer
-0.056
3145796HORNRTN
Solar/Wind Harmer
-0.007
962981AG1-147 GEN
Solar/Wind Harmer
7.617
3146033SCOT NK
Solar/Wind Harmer
-0.069
970831AG2-522 GEN
Solar/Wind Harmer
8.501
3150411LDYSMT5
Adder
18.406
3150381LDYSMT2
Adder
17.615
972213AH1-691 GEN
Adder
2.98
972215AH1-692 GEN
Adder
2.98
972205AH1-687 GEN
Adder
5.489
316164AC1-076 GEN
Solar/Wind Helper
1.636
3152261N ANNA2
50/50
17.597
3150861SPRUNCD
50/50
0.898
3151031BRUNSWICKG2
50/50
2.367
3151101ELIZAR3
50/50
17.646
3147666LOUISA
Solar/Wind Harmer
-0.057
315773AC2-141 GEN
Solar/Wind Harmer
8.509
315839AE2-212 C
Solar/Wind Harmer
0.609
944581AF1-123 GEN
Solar/Wind Harmer
91.816
944601AF1-125 GEN
Solar/Wind Harmer
90.383
315813AE1-149 C
Solar/Wind Harmer
12.605
3144873MCLAUGH
Solar/Wind Harmer
-0.001
965281AG1-393 GEN
Solar/Wind Harmer
2.513
970659AG2-427 GEN
Solar/Wind Harmer
1.891
3144536CHRHLND
Solar/Wind Harmer
-0.003
316083AB2-161 GEN
Solar/Wind Harmer
3.257
970661AG2-428 GEN
Solar/Wind Harmer
3.77
3145336SMITFLD
Solar/Wind Harmer
-0.008
3146456SLIGO L269
Solar/Wind Harmer
-0.02
971153AH1-033 GEN
Solar/Wind Harmer
2.43
3151221GRAVEL6
Adder
12.86
3151171GRAVELC
Adder
2.474
961611AG1-000B GEN
Solar/Wind Harmer
4.183
315778AD1-151 GEN
Solar/Wind Harmer
17.189
970129AG2-093 GEN
Solar/Wind Harmer
11.167
970133AG2-095 GEN
Solar/Wind Harmer
2.23
3143096IRON208
Adder
0.737
3143096IRON208
Adder
0.722
316320Y1-086
Solar/Wind Harmer
1.158
3144216WINCHST
Adder
0.657
316435W1029_GEN3
Solar/Wind Harmer
3.546
316313AB2-026
Solar/Wind Harmer
0.527
316258AE1-075 C
Solar/Wind Harmer
0.475
316405AF2-144 C
Solar/Wind Harmer
0.501
3143336POWHATN
Solar/Wind Harmer
1.973
3146516WINFALL
Solar/Wind Harmer
-0.019
3150921YORKTN3
Adder
4.366
970917AG2-570 GEN
Solar/Wind Harmer
48.634
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3145273HOLLAND
Solar/Wind Harmer
-0.014
3142946ENON
Solar/Wind Harmer
-0.006
316382AG1-145 C
Solar/Wind Harmer
0.582
970293AG2-193 GEN
Solar/Wind Harmer
2.398
3146376EDENTON
Solar/Wind Harmer
-0.019
3142416OLDCHRC
Solar/Wind Harmer
1.904
3142433PROV 92
Adder
0.325
3142433PROV 92
Adder
0.325
315614AA2-178 GEN
Solar/Wind Harmer
2.017
316365GEN2_N
Solar/Wind Harmer
1.25
3156081AA2-088 GEN
Solar/Wind Harmer
5.982
971157AH1-035 GEN
Solar/Wind Harmer
2.302
315737AD1-076 GEN
Solar/Wind Harmer
3.491
3141843SHACKLE
Adder
0.835
316203AE2-005 GEN
Solar/Wind Harmer
7.74
316280AD1-041 GEN
Solar/Wind Harmer
1.38
3141766HARMONY
Solar/Wind Harmer
1.629
316156AD2-030 GEN
Solar/Wind Harmer
0.487
3141873WAN 176
Solar/Wind Harmer
2.165
3146206CASHIE
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
0.127
3145893MURPHYS
Solar/Wind Harmer
-0.018
316473AC1-191 GEN
Solar/Wind Harmer
1.956
957521AF2-046 GEN
Solar/Wind Harmer
14.304
961681AG1-008 GEN
Solar/Wind Harmer
14.304
966621AG1-532 GEN
Solar/Wind Harmer
0.367
3146173TUNIS
Solar/Wind Harmer
-0.018
3156021HOLLOMANSOL
Solar/Wind Harmer
2.424
316463AE2-346 GEN
Solar/Wind Harmer
0.291
316140AB2-099
Solar/Wind Harmer
0.121
962331AG1-082 GEN
Solar/Wind Harmer
2.246
313506AB2-031 GEN
Solar/Wind Harmer
1.435
3146263WOODLND
Solar/Wind Harmer
-0.018
316478AD1-087 GEN
Solar/Wind Harmer
1.541
316486AD2-202 GEN
Solar/Wind Harmer
0.451
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3147043LAWRENC
Solar/Wind Harmer
-0.01
3145963POPLR C
Solar/Wind Harmer
-0.018
316317KELFORD C
Solar/Wind Harmer
0.829
3145823KELFORD
Solar/Wind Harmer
-0.018
3145796HORNRTN
Solar/Wind Harmer
-0.069
3145796HORNRTN
Solar/Wind Harmer
-0.017
962971AG1-146 GEN
Solar/Wind Harmer
3.264
316484AD2-074 GEN
Solar/Wind Harmer
4.335
970009AG2-005 GEN
Solar/Wind Harmer
2.153
316210AC1-098 GEN
Solar/Wind Harmer
2.67
970909AG2-566 GEN
Solar/Wind Harmer
1.611
316404AE1-155 C
Solar/Wind Harmer
3.263
3150351NORNECKC2
Adder
1.476
3144293JTRSVLE
Adder
0.462
3150401LDYSMT4
Adder
18.348
3150371LDYSMT1
Adder
17.729
316044AC1-158 PL1
Solar/Wind Helper
5.365
316450AC1-158 RIC
Solar/Wind Helper
1.431
LAGNLTFEXP_LAGN->PJM
CLTF
6.271
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.05
TVALTFEXP_TVA->PJM
CLTF
3.173
CPLELTFEXP_CPLE->PJM
CLTF
9.213
CBM West 2LTFEXP_CBM-W2->PJM
CBM
32.048
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.977
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.753
MECLTFEXP_MEC->PJM
CLTF
2.757
SIGELTFEXP_SIGE->PJM
CLTF
0.083
NYPJM->LTFIMP_NY
CLTF
2.427
LGEELTFEXP_LGEE->PJM
CLTF
1
WECLTFEXP_WEC->PJM
CLTF
0.483

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P2-2: NORTH ANNA B1_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: NORTH ANNA B1_SRT-S
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:128.28 %
Rating:3118.0 MVA
Rating Type:C
MVA to Mitigate:3999.66
MW Contribution:7.19
Bus #Bus NameTypeMW Contribution
3152251N ANNA1
50/50
17.599
970119AG2-088 GEN
50/50
27.254
3150851SPRUNCC
50/50
0.898
315243AE2-183_GT3
50/50
3.006
3151051BRUNSWICKS1
50/50
4.913
3151021BRUNSWICKG1
50/50
2.367
971451AH1-221 GEN
50/50
7.19
971133AH1-012 GEN
50/50
4.727
970533AG2-339 GEN
50/50
16.617
970531AG2-338 GEN
50/50
6.647
315242AE2-183_GT2
50/50
3.006
315241AE2-183_GT1
50/50
2.987
972185AH1-677 GEN
50/50
10.835
3151041BRUNSWICKG3
50/50
2.367
972187AH1-678 GEN
50/50
5.432
3150991CHESPKB
50/50
1.99
3150991CHESPKB
50/50
1.942
971223AH1-071 GEN
Solar/Wind Harmer
2.871
3143526WINTERP
Solar/Wind Harmer
-0.113
316036AC1-147 C
Solar/Wind Harmer
0.543
3142956BIRDNECK
Solar/Wind Harmer
1.078
316316AC1-027 C
Solar/Wind Harmer
0.617
316185AD1-033 GEN
Solar/Wind Harmer
2.119
316240AF1-291 C
Solar/Wind Harmer
0.605
3144356SAPONY
Solar/Wind Harmer
0.7
3145506HICKORY
Solar/Wind Harmer
-0.08
3145506HICKORY
Solar/Wind Harmer
-0.048
3145506HICKORY
Solar/Wind Harmer
-0.012
970657AG2-426 GEN
Solar/Wind Harmer
6.265
970657AG2-426 GEN
Solar/Wind Harmer
1.31
944641AF1-129 GEN
Adder
84.93
316339AD2-160 GEN
Solar/Wind Harmer
1.348
316018AA1-139 ULT2
Solar/Wind Harmer
1.711
316017AA1-139 ULT1
Solar/Wind Harmer
1.616
316236AE1-162_GEN
Solar/Wind Harmer
0.602
3137176SLIGO L2192
Solar/Wind Harmer
-0.079
3146456SLIGO L269
Solar/Wind Harmer
2.355
3130086AYDLETT
Solar/Wind Harmer
-0.079
970933AG2-581 GEN
Solar/Wind Harmer
18.608
316033AB2-134 GEN
Solar/Wind Harmer
6.401
315697AD1-025 GEN
Solar/Wind Harmer
4.014
3146386ELIZ CT
Solar/Wind Harmer
-0.02
316431W1029_GEN1
Solar/Wind Harmer
3.546
316433W1029_GEN2
Solar/Wind Harmer
3.546
3146516WINFALL
Solar/Wind Harmer
-0.019
3146516WINFALL
Solar/Wind Harmer
-0.019
3146516WINFALL
Solar/Wind Harmer
-0.019
3142366NRTHEST
Adder
0.565
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3142946ENON
Solar/Wind Harmer
-0.002
3150691DARBY 3
Adder
12.388
3150701DARBY 4
Adder
12.359
3150681DARBY 2
Adder
12.344
3150671DARBY 1
Adder
12.33
315742AE1-103 GEN
Solar/Wind Harmer
2.005
3146376EDENTON
Solar/Wind Harmer
0.566
3146376EDENTON
Solar/Wind Harmer
0.566
316075AC2-137 C
Solar/Wind Harmer
0.513
3142296MT RD221
Adder
0.537
970099AG2-077 GEN
Solar/Wind Harmer
23.148
316441AF1-014 GEN
Solar/Wind Harmer
1.237
316065AD1-022 GEN
Solar/Wind Harmer
9.134
3145893MURPHYS
Solar/Wind Harmer
0.508
3145893MURPHYS
Solar/Wind Harmer
-0.033
966871AG1-558 GEN
Solar/Wind Harmer
0.547
966871AG1-558 GEN
Solar/Wind Harmer
0.187
3146173TUNIS
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
316181AB2-040 GEN
Solar/Wind Harmer
2.49
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.011
316426AA2-053 GEN
Solar/Wind Harmer
1.782
3145593CAROLNA
Solar/Wind Harmer
-0.018
3145593CAROLNA
Solar/Wind Harmer
-0.018
966811AG1-552 GEN
Solar/Wind Harmer
1.979
3145593CAROLNA
Solar/Wind Harmer
0.146
3145783HORNRTN
Solar/Wind Harmer
2.075
3145783HORNRTN
Solar/Wind Harmer
1.66
3145783HORNRTN
Solar/Wind Harmer
0.519
3145783HORNRTN
Solar/Wind Harmer
0.207
3145796HORNRTN
Solar/Wind Harmer
-0.052
971741AH1-377 GEN
Solar/Wind Harmer
20.037
316487AF1-042 GEN
Solar/Wind Harmer
2.268
970301AG2-198 GEN
Solar/Wind Harmer
8.487
316274AC1-208 GEN
Solar/Wind Harmer
1.826
3150341NORNECKC1
Adder
1.525
3150341NORNECKC1
Adder
1.513
3144293JTRSVLE
Adder
0.462
3144293JTRSVLE
Adder
0.389
3150391LDYSMT3
Adder
18.314
972195AH1-682 GEN
Adder
2.407
316447AC1-158 HLD
Solar/Wind Helper
11.807
958261AF2-120 GEN
Solar/Wind Harmer
3.594
3152261N ANNA2
50/50
17.597
3150861SPRUNCD
50/50
0.898
3151031BRUNSWICKG2
50/50
2.367
3151101ELIZAR3
50/50
17.646
3147666LOUISA
Solar/Wind Harmer
-0.057
315773AC2-141 GEN
Solar/Wind Harmer
8.509
315839AE2-212 C
Solar/Wind Harmer
0.609
944581AF1-123 GEN
Solar/Wind Harmer
91.816
944601AF1-125 GEN
Solar/Wind Harmer
90.383
315813AE1-149 C
Solar/Wind Harmer
12.605
3144873MCLAUGH
Solar/Wind Harmer
-0.001
965281AG1-393 GEN
Solar/Wind Harmer
2.513
970659AG2-427 GEN
Solar/Wind Harmer
1.891
3144536CHRHLND
Solar/Wind Harmer
-0.003
316083AB2-161 GEN
Solar/Wind Harmer
3.257
970661AG2-428 GEN
Solar/Wind Harmer
3.77
3145336SMITFLD
Solar/Wind Harmer
-0.008
3146456SLIGO L269
Solar/Wind Harmer
-0.02
971153AH1-033 GEN
Solar/Wind Harmer
2.43
3151221GRAVEL6
Adder
12.86
3151171GRAVELC
Adder
2.474
961611AG1-000B GEN
Solar/Wind Harmer
4.183
315778AD1-151 GEN
Solar/Wind Harmer
17.189
970129AG2-093 GEN
Solar/Wind Harmer
11.167
970133AG2-095 GEN
Solar/Wind Harmer
2.23
3143096IRON208
Adder
0.737
3143096IRON208
Adder
0.722
316320Y1-086
Solar/Wind Harmer
1.158
3144216WINCHST
Adder
0.657
316435W1029_GEN3
Solar/Wind Harmer
3.546
316313AB2-026
Solar/Wind Harmer
0.527
316258AE1-075 C
Solar/Wind Harmer
0.475
316405AF2-144 C
Solar/Wind Harmer
0.501
3143336POWHATN
Solar/Wind Harmer
1.973
3146516WINFALL
Solar/Wind Harmer
-0.019
3150921YORKTN3
Adder
4.366
970917AG2-570 GEN
Solar/Wind Harmer
48.634
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3145273HOLLAND
Solar/Wind Harmer
-0.014
3142946ENON
Solar/Wind Harmer
-0.006
316382AG1-145 C
Solar/Wind Harmer
0.582
970293AG2-193 GEN
Solar/Wind Harmer
2.398
3146376EDENTON
Solar/Wind Harmer
-0.019
3142416OLDCHRC
Solar/Wind Harmer
1.904
3142433PROV 92
Adder
0.325
3142433PROV 92
Adder
0.325
315614AA2-178 GEN
Solar/Wind Harmer
2.017
316365GEN2_N
Solar/Wind Harmer
1.25
3156081AA2-088 GEN
Solar/Wind Harmer
5.982
971157AH1-035 GEN
Solar/Wind Harmer
2.302
315737AD1-076 GEN
Solar/Wind Harmer
3.491
3141843SHACKLE
Adder
0.835
316203AE2-005 GEN
Solar/Wind Harmer
7.74
316280AD1-041 GEN
Solar/Wind Harmer
1.38
3141766HARMONY
Solar/Wind Harmer
1.629
316156AD2-030 GEN
Solar/Wind Harmer
0.487
3141873WAN 176
Solar/Wind Harmer
2.165
3146206CASHIE
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
0.127
3145893MURPHYS
Solar/Wind Harmer
-0.018
316473AC1-191 GEN
Solar/Wind Harmer
1.956
957521AF2-046 GEN
Solar/Wind Harmer
14.304
961681AG1-008 GEN
Solar/Wind Harmer
14.304
966621AG1-532 GEN
Solar/Wind Harmer
0.367
3146173TUNIS
Solar/Wind Harmer
-0.018
3156021HOLLOMANSOL
Solar/Wind Harmer
2.424
316463AE2-346 GEN
Solar/Wind Harmer
0.291
316140AB2-099
Solar/Wind Harmer
0.121
962331AG1-082 GEN
Solar/Wind Harmer
2.246
313506AB2-031 GEN
Solar/Wind Harmer
1.435
3146263WOODLND
Solar/Wind Harmer
-0.018
316478AD1-087 GEN
Solar/Wind Harmer
1.541
316486AD2-202 GEN
Solar/Wind Harmer
0.451
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3147043LAWRENC
Solar/Wind Harmer
-0.01
3145963POPLR C
Solar/Wind Harmer
-0.018
316317KELFORD C
Solar/Wind Harmer
0.829
3145823KELFORD
Solar/Wind Harmer
-0.018
3145796HORNRTN
Solar/Wind Harmer
-0.069
3145796HORNRTN
Solar/Wind Harmer
-0.017
962971AG1-146 GEN
Solar/Wind Harmer
3.264
316484AD2-074 GEN
Solar/Wind Harmer
4.335
970009AG2-005 GEN
Solar/Wind Harmer
2.153
316210AC1-098 GEN
Solar/Wind Harmer
2.67
970909AG2-566 GEN
Solar/Wind Harmer
1.611
316404AE1-155 C
Solar/Wind Harmer
3.263
3150351NORNECKC2
Adder
1.476
3144293JTRSVLE
Adder
0.462
3150401LDYSMT4
Adder
18.348
3150371LDYSMT1
Adder
17.729
316044AC1-158 PL1
Solar/Wind Helper
5.365
316450AC1-158 RIC
Solar/Wind Helper
1.431
316303AF2-085
50/50
3.634
971285AH1-108 GEN
50/50
1.469
315244AE2-183_ST
50/50
5.196
963041AG1-153 GEN
50/50
4.793
3151081ELIZAR1
50/50
17.423
3151091ELIZAR2
50/50
17.121
941591AE2-156 GEN
50/50
15.921
3152611GOSPORTB
50/50
2.419
3152621GOSPORTC
50/50
2.053
3152601GOSPORTA
50/50
1.894
315779AE2-040
50/50
2.493
316233AE1-074 FULL
Solar/Wind Harmer
0.589
971281AH1-106 GEN
Solar/Wind Harmer
3.557
971283AH1-107 GEN
Solar/Wind Harmer
3.557
941031AE2-094 GEN
Solar/Wind Harmer
39.382
944011AF1-069 GEN
Solar/Wind Harmer
12.34
970673AG2-436 GEN
Solar/Wind Harmer
43.344
970673AG2-436 GEN
Solar/Wind Harmer
21.946
3143316POE
Solar/Wind Harmer
-0.08
971967AH1-528 GEN
Solar/Wind Harmer
38.278
316315AB2-025 C
Solar/Wind Harmer
0.541
315814AE2-033 C
Solar/Wind Harmer
18.612
957871AF2-081 GEN
Solar/Wind Harmer
9.987
971445AH1-216 GEN
Solar/Wind Harmer
12.352
319010AE1-072 C
Solar/Wind Harmer
4.03
3146406KITTY HAWK
Solar/Wind Harmer
0.017
315833AF1-017_GEN
Solar/Wind Harmer
3.781
316349AD2-085 GEN
Solar/Wind Harmer
1.77
316311AC2-079 GEN
Solar/Wind Harmer
10.04
316305AF2-043 C
Solar/Wind Harmer
0.6
972265AH1-717 GEN
Adder
13.734
3151201GRAVEL4
Adder
12.875
3151191GRAVEL3
Adder
12.712
3151211GRAVEL5
Adder
12.712
316369SG1_INVT
Solar/Wind Harmer
3.546
316132AB2-190 GEN1
Solar/Wind Harmer
2.006
315835AF2-110_GEN
Solar/Wind Harmer
2.476
313526AB2-022
Solar/Wind Harmer
0.533
3146486SUNBURY
Solar/Wind Harmer
-0.02
3146486SUNBURY
Solar/Wind Harmer
-0.02
316321Z2-027
Solar/Wind Harmer
0.531
3146396TANGLEW
Solar/Wind Harmer
0.362
3145176PASQUOTANK
Solar/Wind Harmer
-0.012
970085AG2-068 GEN
Solar/Wind Harmer
12.107
970581AG2-369 GEN
Solar/Wind Harmer
10.412
315611Z1-036_GEN2
Solar/Wind Harmer
4.76
3130156CHOWAN
Solar/Wind Harmer
-0.019
3130156CHOWAN
Solar/Wind Harmer
-0.019
315976AC1-164 GENA
Solar/Wind Harmer
19.998
316169AC1-164_GENC
Solar/Wind Harmer
17.276
315975AC1-164 GENB
Solar/Wind Harmer
0.592
957831AF2-077 GEN
Solar/Wind Harmer
0.569
3138283WHITEMARSH
Solar/Wind Harmer
0.029
971167AH1-042 GEN
Solar/Wind Harmer
18.178
316312AB1-027
Solar/Wind Harmer
0.636
3142433PROV 92
Adder
0.325
3142433PROV 92
Adder
0.325
315816AE2-034 GEN
Solar/Wind Harmer
1.513
3143873LANEXA
Solar/Wind Harmer
-0.011
3130546PLYMOUTH
Solar/Wind Harmer
-0.018
315732AD1-074 GEN1
Solar/Wind Harmer
3.714
315733AD1-074 GEN2
Solar/Wind Harmer
3.714
315735AD1-075 GEN1
Solar/Wind Harmer
1.858
965291AG1-394 GEN
Solar/Wind Harmer
1.63
316314AB2-024 C
Solar/Wind Harmer
1.568
315662AE1-191 GEN
Solar/Wind Harmer
2.207
315666AE1-190 GEN
Solar/Wind Harmer
0.552
316059AD1-063 C
Solar/Wind Harmer
0.414
957601AF2-054 GEN
Solar/Wind Harmer
0.546
3141873WAN 176
Solar/Wind Harmer
-0.004
3146206CASHIE
Solar/Wind Harmer
-0.018
970601AG2-382 GEN
Solar/Wind Harmer
7.968
316318V4-068
Solar/Wind Harmer
0.454
3145893MURPHYS
Solar/Wind Harmer
-0.049
3145893MURPHYS
Solar/Wind Harmer
-0.018
946281AF1-292 GEN
Solar/Wind Harmer
0.405
3145513AHOSKIE
Solar/Wind Harmer
0.157
961941AG1-037 GEN
Solar/Wind Harmer
0.135
3145513AHOSKIE
Solar/Wind Harmer
-0.018
3141913WHIT STONE
Solar/Wind Harmer
-0.018
3146043SEABORD
Solar/Wind Harmer
-0.018
316087AB2-174 GEN
Solar/Wind Harmer
2.556
972189AH1-679 GEN
Adder
2.672
3138133OCRAN
Solar/Wind Harmer
-0.005
315607AA1-063A GEN
Solar/Wind Harmer
1.808
3145683EARLEYS
Solar/Wind Harmer
-0.036
3145683EARLEYS
Solar/Wind Harmer
-0.018
3145683EARLEYS
Solar/Wind Harmer
-0.018
3141783LANCAST
Solar/Wind Harmer
-0.011
3141783LANCAST
Solar/Wind Harmer
-0.007
315652AC1-086 GEN
Solar/Wind Harmer
19.944
3137643SOCKMAN
Solar/Wind Harmer
-0.07
3145796HORNRTN
Solar/Wind Harmer
-0.056
3145796HORNRTN
Solar/Wind Harmer
-0.007
962981AG1-147 GEN
Solar/Wind Harmer
7.617
3146033SCOT NK
Solar/Wind Harmer
-0.069
970831AG2-522 GEN
Solar/Wind Harmer
8.501
3150411LDYSMT5
Adder
18.406
3150381LDYSMT2
Adder
17.615
972213AH1-691 GEN
Adder
2.98
972215AH1-692 GEN
Adder
2.98
972205AH1-687 GEN
Adder
5.489
316164AC1-076 GEN
Solar/Wind Helper
1.636
3150981CHESPKA
50/50
2.372
3147666LOUISA
Solar/Wind Harmer
-0.099
316192AB2-158 GEN
Solar/Wind Harmer
2.866
3143226MDLTHAN
Solar/Wind Harmer
-0.023
3143526WINTERP
Solar/Wind Harmer
-0.113
940641AE2-051 GEN
Solar/Wind Harmer
20.147
939411AE1-173 GEN
Solar/Wind Harmer
105.7
316294AC1-161 GEN
Solar/Wind Harmer
6.579
944591AF1-124 GEN
Solar/Wind Harmer
92.147
316375AC2-012 GEN
Solar/Wind Harmer
6.96
970659AG2-427 GEN
Solar/Wind Harmer
10.669
316381AD1-082 GEN
Solar/Wind Harmer
1.84
315671AE2-027_GEN
Solar/Wind Harmer
15.038
970661AG2-428 GEN
Solar/Wind Harmer
21.272
3142543TWELFTH
Solar/Wind Harmer
-0.002
316388AE2-253 GEN
Solar/Wind Harmer
1.348
3145336SMITFLD
Solar/Wind Harmer
-0.079
3146456SLIGO L269
Solar/Wind Harmer
-0.02
316246AF1-032 C
Solar/Wind Harmer
0.403
3151171GRAVELC
Adder
1.882
316072AD1-144
Solar/Wind Harmer
0.402
961611AG1-000B GEN
Solar/Wind Harmer
9.803
971647AH1-324 GEN
Solar/Wind Harmer
9.928
971069AG2-661 GEN
Solar/Wind Harmer
3.14
316458AB2-190 GEN2
Solar/Wind Harmer
2.006
970129AG2-093 GEN
Solar/Wind Harmer
4.523
316093AE2-104_GEN
Solar/Wind Harmer
5.759
3143096IRON208
Adder
0.737
3143336POWHATN
Solar/Wind Harmer
2.321
3138126ROCKLANDING
Solar/Wind Harmer
0.06
3146516WINFALL
Solar/Wind Harmer
-0.063
3146516WINFALL
Solar/Wind Harmer
-0.019
944631AF1-128 GEN
Adder
82.804
970919AG2-571 GEN
Solar/Wind Harmer
6.156
970087AG2-069 GEN
Solar/Wind Harmer
18.16
971317AH1-138 GEN
Solar/Wind Harmer
2.416
316159AE1-175 C
Solar/Wind Harmer
0.519
315800Z1-036_GEN1
Solar/Wind Harmer
4.76
3130156CHOWAN
Solar/Wind Harmer
-0.019
3142416OLDCHRC
Solar/Wind Harmer
-0.049
3142416OLDCHRC
Solar/Wind Harmer
-0.019
3142433PROV 92
Solar/Wind Harmer
-0.075
3142433PROV 92
Adder
0.325
3142433PROV 92
Adder
0.325
3145663CRESWEL
Solar/Wind Harmer
-0.052
971163AH1-040 GEN
Solar/Wind Harmer
17.53
316336AC2-165 C
Solar/Wind Harmer
3.244
316023GEN1_S
Solar/Wind Harmer
1.25
957481AF2-042 GEN
Solar/Wind Harmer
57.87
971777AH1-397 GEN
Solar/Wind Harmer
2.159
3141843SHACKLE
Adder
0.835
3141766HARMONY
Solar/Wind Harmer
-0.004
3146206CASHIE
Solar/Wind Harmer
-0.018
971547AH1-271 GEN
Solar/Wind Harmer
4.553
3145893MURPHYS
Solar/Wind Harmer
-0.072
3145893MURPHYS
Solar/Wind Harmer
0.54
315693AD1-088 GEN
Solar/Wind Harmer
9.06
960081AF2-299 GEN
Solar/Wind Harmer
2.034
962491AG1-098 GEN
Solar/Wind Harmer
12.078
3146173TUNIS
Solar/Wind Harmer
-0.018
3138133OCRAN
Solar/Wind Harmer
-0.011
3145683EARLEYS
Solar/Wind Harmer
-0.018
3146263WOODLND
Solar/Wind Harmer
-0.018
971795AH1-408 GEN
Solar/Wind Harmer
13.31
316011AB1-132 GEN
Solar/Wind Harmer
3.709
962571AG1-106 GEN
Solar/Wind Harmer
2.548
316190AA2-174 GEN
Solar/Wind Harmer
0.217
3147043LAWRENC
Adder
1.417
3145963POPLR C
Solar/Wind Harmer
-0.018
3145823KELFORD
Solar/Wind Harmer
-0.018
3145783HORNRTN
Solar/Wind Harmer
-0.017
3145796HORNRTN
Solar/Wind Harmer
-0.057
3145796HORNRTN
Solar/Wind Harmer
-0.017
316174AB2-169 GEN
Solar/Wind Harmer
2.689
961951AG1-038 GEN
Solar/Wind Harmer
2.268
316212AC1-099_GEN
Solar/Wind Harmer
1.483
962861AG1-135 GEN
Solar/Wind Harmer
6.373
316129AC1-054 GEN
Solar/Wind Harmer
1.485
3150351NORNECKC2
Adder
1.452
3144293JTRSVLE
Adder
0.462
972197AH1-683 GEN
Adder
2.865
972219AH1-694 GEN
Adder
2.063
316045AC1-158 PL2
Solar/Wind Helper
17.173
316006AB2-029 C
Solar/Wind Helper
0.112
LAGNLTFEXP_LAGN->PJM
CLTF
6.271
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.05
TVALTFEXP_TVA->PJM
CLTF
3.173
CPLELTFEXP_CPLE->PJM
CLTF
9.213
CBM West 2LTFEXP_CBM-W2->PJM
CBM
32.048
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.977
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.753
MECLTFEXP_MEC->PJM
CLTF
2.757
SIGELTFEXP_SIGE->PJM
CLTF
0.083
NYPJM->LTFIMP_NY
CLTF
2.427
LGEELTFEXP_LGEE->PJM
CLTF
1
WECLTFEXP_WEC->PJM
CLTF
0.483

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.49 %
Rating:3193.18 MVA
Rating Type:A
MVA to Mitigate:3783.56
MW Contribution:7.19
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
3.634
971285AH1-108 GEN
50/50
1.469
315244AE2-183_ST
50/50
5.196
963041AG1-153 GEN
50/50
4.793
3151081ELIZAR1
50/50
17.423
3151091ELIZAR2
50/50
17.121
941591AE2-156 GEN
50/50
15.921
3152611GOSPORTB
50/50
2.419
3152621GOSPORTC
50/50
2.053
3152601GOSPORTA
50/50
1.894
315779AE2-040
50/50
2.493
316233AE1-074 FULL
Solar/Wind Harmer
0.156
971281AH1-106 GEN
Solar/Wind Harmer
2.702
3152251N ANNA1
50/50
17.599
970119AG2-088 GEN
50/50
27.254
3150851SPRUNCC
50/50
0.898
315243AE2-183_GT3
50/50
3.006
3151051BRUNSWICKS1
50/50
4.913
3151021BRUNSWICKG1
50/50
2.367
971451AH1-221 GEN
50/50
7.19
3150981CHESPKA
50/50
2.372
3147666LOUISA
Solar/Wind Harmer
0.882
316192AB2-158 GEN
Solar/Wind Harmer
1.212
3143226MDLTHAN
Solar/Wind Harmer
0.204
3143526WINTERP
Solar/Wind Harmer
1.012
940641AE2-051 GEN
Solar/Wind Harmer
15.302
939411AE1-173 GEN
Solar/Wind Harmer
80.278
316294AC1-161 GEN
Solar/Wind Harmer
3.136
944591AF1-124 GEN
Solar/Wind Harmer
40.591
316375AC2-012 GEN
Solar/Wind Harmer
0.005
970659AG2-427 GEN
Solar/Wind Harmer
8.643
316381AD1-082 GEN
Solar/Wind Harmer
0.186
315671AE2-027_GEN
Solar/Wind Harmer
11.421
970661AG2-428 GEN
Solar/Wind Harmer
17.724
3142543TWELFTH
Solar/Wind Harmer
0.017
316388AE2-253 GEN
Solar/Wind Harmer
0.557
3145336SMITFLD
Solar/Wind Harmer
0.711
3146456SLIGO L269
Solar/Wind Harmer
0.177
316246AF1-032 C
Solar/Wind Harmer
0.08
3151171GRAVELC
Adder
1.882
316072AD1-144
Solar/Wind Harmer
0.064
961611AG1-000B GEN
Solar/Wind Harmer
9.271
971647AH1-324 GEN
Solar/Wind Harmer
7.54
971069AG2-661 GEN
Solar/Wind Harmer
3.14
316458AB2-190 GEN2
Solar/Wind Harmer
0.947
970129AG2-093 GEN
Solar/Wind Harmer
5.021
316093AE2-104_GEN
Solar/Wind Harmer
2.965
3143096IRON208
Adder
0.737
3143336POWHATN
Solar/Wind Harmer
3.095
3138126ROCKLANDING
Solar/Wind Harmer
0.08
3146516WINFALL
Solar/Wind Harmer
0.563
3146516WINFALL
Solar/Wind Harmer
0.174
944631AF1-128 GEN
Adder
82.804
970919AG2-571 GEN
Solar/Wind Harmer
6.156
970087AG2-069 GEN
Solar/Wind Harmer
13.793
971317AH1-138 GEN
Solar/Wind Harmer
1.284
316159AE1-175 C
Solar/Wind Harmer
0.148
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.17
3142416OLDCHRC
Solar/Wind Harmer
0.437
3142416OLDCHRC
Solar/Wind Harmer
0.167
3142433PROV 92
Solar/Wind Harmer
0.669
3142433PROV 92
Adder
0.325
3142433PROV 92
Adder
0.325
3145663CRESWEL
Solar/Wind Harmer
0.466
971163AH1-040 GEN
Solar/Wind Harmer
13.314
316336AC2-165 C
Solar/Wind Harmer
0.006
316023GEN1_S
Solar/Wind Harmer
0.37
957481AF2-042 GEN
Solar/Wind Harmer
43.952
971777AH1-397 GEN
Solar/Wind Harmer
0.431
3141843SHACKLE
Adder
0.835
3141766HARMONY
Solar/Wind Harmer
0.033
3146206CASHIE
Solar/Wind Harmer
0.162
971547AH1-271 GEN
Solar/Wind Harmer
3.458
3145893MURPHYS
Solar/Wind Harmer
0.648
3145893MURPHYS
Solar/Wind Harmer
0.72
315693AD1-088 GEN
Solar/Wind Harmer
7.741
960081AF2-299 GEN
Solar/Wind Harmer
1.545
962491AG1-098 GEN
Solar/Wind Harmer
9.173
3146173TUNIS
Solar/Wind Harmer
0.161
3138133OCRAN
Solar/Wind Harmer
0.096
3145683EARLEYS
Solar/Wind Harmer
0.159
3146263WOODLND
Solar/Wind Harmer
0.158
971795AH1-408 GEN
Solar/Wind Harmer
10.53
316011AB1-132 GEN
Solar/Wind Harmer
2.868
962571AG1-106 GEN
Solar/Wind Harmer
2.244
316190AA2-174 GEN
Solar/Wind Harmer
0
3147043LAWRENC
Adder
1.417
3145963POPLR C
Solar/Wind Harmer
0.156
3145823KELFORD
Solar/Wind Harmer
0.156
3145783HORNRTN
Solar/Wind Harmer
0.155
3145796HORNRTN
Solar/Wind Harmer
0.512
3145796HORNRTN
Solar/Wind Harmer
0.155
316174AB2-169 GEN
Solar/Wind Harmer
0.004
316212AC1-099_GEN
Solar/Wind Harmer
0.783
962861AG1-135 GEN
Solar/Wind Harmer
4.841
316129AC1-054 GEN
Solar/Wind Harmer
0.567
3146293MARTNCO
Solar/Wind Harmer
0.139
971065AG2-659 GEN
Solar/Wind Harmer
6.41
315687AD1-152 GEN
Solar/Wind Harmer
0.005
3141726DUNNSVL
Solar/Wind Harmer
0.591
315722AD1-056 GEN
Solar/Wind Harmer
0.935
3145746EVERETS
Solar/Wind Harmer
0.147
3145746EVERETS
Solar/Wind Harmer
0.147
966881AG1-559 GEN
Solar/Wind Harmer
0.17
316237AB2-079_GEN
Solar/Wind Harmer
0.001
970937AG2-583 GEN
Solar/Wind Harmer
8.939
3150351NORNECKC2
Adder
1.452
316494AC1-189 GEN
Solar/Wind Harmer
0.491
970685AG2-442 GEN
Solar/Wind Harmer
10.862
963171AG1-166 GEN
Solar/Wind Harmer
0.774
971563AH1-280 GEN
Solar/Wind Harmer
1.548
3144293JTRSVLE
Adder
0.462
3146233WITAKRS
Solar/Wind Harmer
0.573
961671AG1-007 GEN
Solar/Wind Harmer
0.022
3146083TARBORO
Solar/Wind Harmer
0.144
3145493TOT1
Solar/Wind Harmer
0.639
3146926FARMVIL
Solar/Wind Harmer
0.086
3145543BTLEBRO
Solar/Wind Harmer
0.141
3145543BTLEBRO
Solar/Wind Harmer
0.113
316359AB2-059 GEN
Solar/Wind Harmer
0.508
316049AB1-081 GEN
Solar/Wind Harmer
0.809
3142053HEARTS
Solar/Wind Harmer
0.249
970401AG2-262 GEN
Solar/Wind Harmer
0.817
316337AD2-073 GEN
Solar/Wind Harmer
0.12
972197AH1-683 GEN
Adder
2.865
972219AH1-694 GEN
Adder
2.063
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.055
972003AH1-546 GEN
Solar/Wind Harmer
5.523
316003AC1-222 GEN
Solar/Wind Harmer
0.003
971377AH1-170 GEN
Solar/Wind Harmer
1.278
971283AH1-107 GEN
Solar/Wind Harmer
2.702
941031AE2-094 GEN
Solar/Wind Harmer
34.43
944011AF1-069 GEN
Solar/Wind Harmer
11.25
970673AG2-436 GEN
Solar/Wind Harmer
39.174
970673AG2-436 GEN
Solar/Wind Harmer
26.116
3143316POE
Solar/Wind Harmer
0.721
971967AH1-528 GEN
Solar/Wind Harmer
28.994
316315AB2-025 C
Solar/Wind Harmer
0.144
315814AE2-033 C
Solar/Wind Harmer
14.072
957871AF2-081 GEN
Solar/Wind Harmer
8.849
971445AH1-216 GEN
Solar/Wind Harmer
12.508
319010AE1-072 C
Solar/Wind Harmer
0.893
3146406KITTY HAWK
Solar/Wind Harmer
0.022
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.121
316311AC2-079 GEN
Solar/Wind Harmer
5.087
316305AF2-043 C
Solar/Wind Harmer
0.001
972265AH1-717 GEN
Adder
13.734
3151201GRAVEL4
Adder
12.875
3151191GRAVEL3
Adder
12.712
3151211GRAVEL5
Adder
12.712
316369SG1_INVT
Solar/Wind Harmer
0.007
316132AB2-190 GEN1
Solar/Wind Harmer
0.947
315835AF2-110_GEN
Solar/Wind Harmer
1.21
313526AB2-022
Solar/Wind Harmer
0.095
3146486SUNBURY
Solar/Wind Harmer
0.175
3146486SUNBURY
Solar/Wind Harmer
0.175
316321Z2-027
Solar/Wind Harmer
0.033
3146396TANGLEW
Solar/Wind Harmer
0.483
3145176PASQUOTANK
Solar/Wind Harmer
0.109
970085AG2-068 GEN
Solar/Wind Harmer
9.195
970581AG2-369 GEN
Solar/Wind Harmer
7.908
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.17
3130156CHOWAN
Solar/Wind Harmer
0.17
315976AC1-164 GENA
Solar/Wind Harmer
17.467
316169AC1-164_GENC
Solar/Wind Harmer
15.09
315975AC1-164 GENB
Solar/Wind Harmer
0.517
3138283WHITEMARSH
Solar/Wind Harmer
0.039
971167AH1-042 GEN
Solar/Wind Harmer
14.927
971133AH1-012 GEN
50/50
4.727
970533AG2-339 GEN
50/50
16.617
970531AG2-338 GEN
50/50
6.647
315242AE2-183_GT2
50/50
3.006
315241AE2-183_GT1
50/50
2.987
972185AH1-677 GEN
50/50
10.835
3151041BRUNSWICKG3
50/50
2.367
972187AH1-678 GEN
50/50
5.432
3150991CHESPKB
50/50
1.99
3150991CHESPKB
50/50
1.942
971223AH1-071 GEN
Solar/Wind Harmer
2.18
3143526WINTERP
Solar/Wind Harmer
1.012
316036AC1-147 C
Solar/Wind Harmer
0.033
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.172
316185AD1-033 GEN
Solar/Wind Harmer
0.005
316240AF1-291 C
Solar/Wind Harmer
0.001
3144356SAPONY
Solar/Wind Harmer
1.494
3145506HICKORY
Solar/Wind Harmer
0.714
3145506HICKORY
Solar/Wind Harmer
0.428
3145506HICKORY
Solar/Wind Harmer
0.107
970657AG2-426 GEN
Solar/Wind Harmer
6.25
970657AG2-426 GEN
Solar/Wind Harmer
1.31
944641AF1-129 GEN
Adder
84.93
316339AD2-160 GEN
Solar/Wind Harmer
0.288
316018AA1-139 ULT2
Solar/Wind Harmer
0.004
316017AA1-139 ULT1
Solar/Wind Harmer
0.099
316236AE1-162_GEN
Solar/Wind Harmer
0.001
3137176SLIGO L2192
Solar/Wind Harmer
0.706
3146456SLIGO L269
Solar/Wind Harmer
3.14
3130086AYDLETT
Solar/Wind Harmer
0.709
970933AG2-581 GEN
Solar/Wind Harmer
14.133
316033AB2-134 GEN
Solar/Wind Harmer
0.01
315697AD1-025 GEN
Solar/Wind Harmer
0.199
3146386ELIZ CT
Solar/Wind Harmer
0.176
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.174
3146516WINFALL
Solar/Wind Harmer
0.174
3146516WINFALL
Solar/Wind Harmer
0.174
3142366NRTHEST
Adder
0.565
3146626S HERTFORD
Solar/Wind Harmer
0.173
3146626S HERTFORD
Solar/Wind Harmer
0.173
3142946ENON
Solar/Wind Harmer
0.017
3150691DARBY 3
Adder
12.388
3150701DARBY 4
Adder
12.359
3150681DARBY 2
Adder
12.344
316312AB1-027
Solar/Wind Harmer
0.3
3142433PROV 92
Adder
0.325
3142433PROV 92
Adder
0.325
315816AE2-034 GEN
Solar/Wind Harmer
0.714
3143873LANEXA
Solar/Wind Harmer
0.099
3130546PLYMOUTH
Solar/Wind Harmer
0.164
315732AD1-074 GEN1
Solar/Wind Harmer
0.939
315733AD1-074 GEN2
Solar/Wind Harmer
0.939
315735AD1-075 GEN1
Solar/Wind Harmer
0.47
965291AG1-394 GEN
Solar/Wind Harmer
0.726
970189AG2-124 GEN
Solar/Wind Harmer
4.842
316314AB2-024 C
Solar/Wind Harmer
0.001
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.032
3146206CASHIE
Solar/Wind Harmer
0.162
970601AG2-382 GEN
Solar/Wind Harmer
6.052
3145893MURPHYS
Solar/Wind Harmer
0.437
3145893MURPHYS
Solar/Wind Harmer
0.162
3145513AHOSKIE
Solar/Wind Harmer
0.334
3145513AHOSKIE
Solar/Wind Harmer
0.16
3141913WHIT STONE
Solar/Wind Harmer
0.16
3146043SEABORD
Solar/Wind Harmer
0.16
316087AB2-174 GEN
Solar/Wind Harmer
0.005
972189AH1-679 GEN
Adder
2.672
3138133OCRAN
Solar/Wind Harmer
0.048
315607AA1-063A GEN
Solar/Wind Harmer
0.325
3145683EARLEYS
Solar/Wind Harmer
0.318
3145683EARLEYS
Solar/Wind Harmer
0.159
3145683EARLEYS
Solar/Wind Harmer
0.159
3141783LANCAST
Solar/Wind Harmer
0.095
3141783LANCAST
Solar/Wind Harmer
0.063
315652AC1-086 GEN
Solar/Wind Harmer
17.349
3137643SOCKMAN
Solar/Wind Harmer
0.629
3145796HORNRTN
Solar/Wind Harmer
0.497
3145796HORNRTN
Solar/Wind Harmer
0.062
962981AG1-147 GEN
Solar/Wind Harmer
5.785
3146033SCOT NK
Solar/Wind Harmer
0.614
970327AG2-215 GEN
Solar/Wind Harmer
5.03
970831AG2-522 GEN
Solar/Wind Harmer
6.456
316005AA1-067
Solar/Wind Harmer
0.158
3145746EVERETS
Solar/Wind Harmer
0.587
3145746EVERETS
Solar/Wind Harmer
0.147
3145746EVERETS
Solar/Wind Harmer
0.147
3145746EVERETS
Solar/Wind Harmer
0.147
970181AG2-120 GEN
Solar/Wind Harmer
1.837
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
971443AH1-215 GEN
Solar/Wind Harmer
2.45
3144303KENBRDG
Solar/Wind Harmer
0.117
3141813NORNECK
Solar/Wind Harmer
0.146
957861AF2-080 GEN
Solar/Wind Harmer
6.272
970683AG2-441 GEN
Solar/Wind Harmer
9.698
970681AG2-440 GEN
Solar/Wind Harmer
7.758
946301AF1-294 GEN
Solar/Wind Harmer
2.864
961791AG1-021 GEN
Solar/Wind Harmer
1.393
315657AE1-056 GEN
Solar/Wind Harmer
4.998
316420AA1-050 GEN
Solar/Wind Harmer
0.005
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.144
3145573BETHELC
Solar/Wind Harmer
0.144
970285AG2-188 GEN
Solar/Wind Harmer
10.95
971845AH1-439 GEN
Solar/Wind Harmer
6.225
3150411LDYSMT5
Adder
18.406
3150381LDYSMT2
Adder
17.615
972213AH1-691 GEN
Adder
2.98
972215AH1-692 GEN
Adder
2.98
316118AC1-105 GEN
Solar/Wind Harmer
0.352
3147173SINAI
Solar/Wind Harmer
0.134
3147243WELCO
Solar/Wind Harmer
0.084
316223AC1-118
Solar/Wind Harmer
0.093
972205AH1-687 GEN
Adder
5.489
970865AG2-541 GEN
Solar/Wind Harmer
4.099
3152261N ANNA2
50/50
17.597
3150861SPRUNCD
50/50
0.898
3151031BRUNSWICKG2
50/50
2.367
3151101ELIZAR3
50/50
17.646
3147666LOUISA
Solar/Wind Harmer
0.507
315773AC2-141 GEN
Solar/Wind Harmer
6.611
315839AE2-212 C
Solar/Wind Harmer
0.001
944581AF1-123 GEN
Solar/Wind Harmer
40.447
944601AF1-125 GEN
Solar/Wind Harmer
39.824
315813AE1-149 C
Solar/Wind Harmer
9.573
3144873MCLAUGH
Solar/Wind Harmer
0.004
965281AG1-393 GEN
Solar/Wind Harmer
1.908
970659AG2-427 GEN
Solar/Wind Harmer
1.891
3144536CHRHLND
Solar/Wind Harmer
0.027
316083AB2-161 GEN
Solar/Wind Harmer
0.002
970661AG2-428 GEN
Solar/Wind Harmer
3.77
3145336SMITFLD
Solar/Wind Harmer
0.071
3146456SLIGO L269
Solar/Wind Harmer
0.177
971153AH1-033 GEN
Solar/Wind Harmer
2.051
3151221GRAVEL6
Adder
12.86
3151171GRAVELC
Adder
2.474
961611AG1-000B GEN
Solar/Wind Harmer
4.714
315778AD1-151 GEN
Solar/Wind Harmer
14.128
970129AG2-093 GEN
Solar/Wind Harmer
10.67
970133AG2-095 GEN
Solar/Wind Harmer
1.693
3143096IRON208
Adder
0.737
3143096IRON208
Adder
0.722
316320Y1-086
Solar/Wind Harmer
0.001
3144216WINCHST
Adder
0.657
316435W1029_GEN3
Solar/Wind Harmer
0.001
316313AB2-026
Solar/Wind Harmer
0.11
316258AE1-075 C
Solar/Wind Harmer
0.131
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
2.631
3146516WINFALL
Solar/Wind Harmer
0.174
3150921YORKTN3
Adder
4.366
970917AG2-570 GEN
Solar/Wind Harmer
15.39
3146626S HERTFORD
Solar/Wind Harmer
0.173
3145273HOLLAND
Solar/Wind Harmer
0.129
3142946ENON
Solar/Wind Harmer
0.058
316382AG1-145 C
Solar/Wind Harmer
0.001
970293AG2-193 GEN
Solar/Wind Harmer
1.821
3146376EDENTON
Solar/Wind Harmer
0.17
3142416OLDCHRC
Solar/Wind Harmer
1.628
3142433PROV 92
Adder
0.325
3142433PROV 92
Adder
0.325
315614AA2-178 GEN
Solar/Wind Harmer
0.952
316365GEN2_N
Solar/Wind Harmer
0.37
3156081AA2-088 GEN
Solar/Wind Harmer
0.004
971157AH1-035 GEN
Solar/Wind Harmer
1.967
315737AD1-076 GEN
Solar/Wind Harmer
2.103
3141843SHACKLE
Adder
0.835
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
2.172
316156AD2-030 GEN
Solar/Wind Harmer
0.12
3141873WAN 176
Solar/Wind Harmer
2.887
3146206CASHIE
Solar/Wind Harmer
0.162
3145893MURPHYS
Solar/Wind Harmer
0.271
3145893MURPHYS
Solar/Wind Harmer
0.162
316473AC1-191 GEN
Solar/Wind Harmer
0.547
957521AF2-046 GEN
Solar/Wind Harmer
12.028
961681AG1-008 GEN
Solar/Wind Harmer
12.028
3146173TUNIS
Solar/Wind Harmer
0.161
3156021HOLLOMANSOL
Solar/Wind Harmer
0.727
316463AE2-346 GEN
Solar/Wind Harmer
0.137
316140AB2-099
Solar/Wind Harmer
0.057
962331AG1-082 GEN
Solar/Wind Harmer
1.706
313506AB2-031 GEN
Solar/Wind Harmer
0.491
3146263WOODLND
Solar/Wind Harmer
0.158
316478AD1-087 GEN
Solar/Wind Harmer
0.553
316486AD2-202 GEN
Solar/Wind Harmer
0.162
3142666NORTHAMPTON
Solar/Wind Harmer
0.158
3147043LAWRENC
Solar/Wind Harmer
0.094
3145963POPLR C
Solar/Wind Harmer
0.156
316317KELFORD C
Solar/Wind Harmer
0.015
3145823KELFORD
Solar/Wind Harmer
0.156
3145796HORNRTN
Solar/Wind Harmer
0.621
3145796HORNRTN
Solar/Wind Harmer
0.155
962971AG1-146 GEN
Solar/Wind Harmer
2.479
970009AG2-005 GEN
Solar/Wind Harmer
1.144
316210AC1-098 GEN
Solar/Wind Harmer
1.405
970909AG2-566 GEN
Solar/Wind Harmer
1.611
316404AE1-155 C
Solar/Wind Harmer
0.034
3145933PARMELE
Solar/Wind Harmer
0.15
966801AG1-551 GEN
Solar/Wind Harmer
1.752
315724AD1-057 GEN
Solar/Wind Harmer
0.554
3145746EVERETS
Solar/Wind Harmer
0.147
3145746EVERETS
Solar/Wind Harmer
0.147
316131AB2-060 GEN
Solar/Wind Harmer
0.461
316327AA2-057 GEN
Solar/Wind Harmer
0.221
964241AG1-285 GEN
Solar/Wind Harmer
9.755
315785AD2-033 C
Solar/Wind Harmer
1.187
970257AG2-171 GEN
Solar/Wind Harmer
4.666
959311AF2-222 GEN
Solar/Wind Harmer
12.953
3150351NORNECKC2
Adder
1.476
963181AG1-167 GEN
Solar/Wind Harmer
0.581
3144293JTRSVLE
Adder
0.462
3147133PAMPLIN
Solar/Wind Harmer
0.455
971193AH1-056 GEN
Solar/Wind Harmer
8.824
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146233WITAKRS
Solar/Wind Harmer
0.722
3146233WITAKRS
Solar/Wind Harmer
0.098
3146073TAR RVR
Solar/Wind Harmer
0.144
3146083TARBORO
Solar/Wind Harmer
0.144
3138543CONSLDL
Solar/Wind Harmer
0.095
3146926FARMVIL
Solar/Wind Harmer
0.086
961601AG1-000A GEN
Solar/Wind Harmer
10.061
971447AH1-217 GEN
Solar/Wind Harmer
3.524
316164AC1-076 GEN
Solar/Wind Helper
1.636
3150671DARBY 1
Adder
12.33
315742AE1-103 GEN
Solar/Wind Harmer
0.002
3146376EDENTON
Solar/Wind Harmer
0.754
3146376EDENTON
Solar/Wind Harmer
0.754
316075AC2-137 C
Solar/Wind Harmer
0.046
3142296MT RD221
Adder
0.537
970099AG2-077 GEN
Solar/Wind Harmer
17.581
316065AD1-022 GEN
Solar/Wind Harmer
7.487
3145893MURPHYS
Solar/Wind Harmer
1.084
3145893MURPHYS
Solar/Wind Harmer
0.291
966871AG1-558 GEN
Solar/Wind Harmer
0.187
3146173TUNIS
Solar/Wind Harmer
0.161
3146173TUNIS
Solar/Wind Harmer
0.161
316181AB2-040 GEN
Solar/Wind Harmer
0.23
3142666NORTHAMPTON
Solar/Wind Harmer
0.158
3142666NORTHAMPTON
Solar/Wind Harmer
0.158
3142666NORTHAMPTON
Solar/Wind Harmer
0.158
3142666NORTHAMPTON
Solar/Wind Harmer
0.095
316426AA2-053 GEN
Solar/Wind Harmer
0.53
3145593CAROLNA
Solar/Wind Harmer
0.156
3145593CAROLNA
Solar/Wind Harmer
0.156
966811AG1-552 GEN
Solar/Wind Harmer
1.698
3145593CAROLNA
Solar/Wind Harmer
0.195
3145783HORNRTN
Solar/Wind Harmer
2.766
3145783HORNRTN
Solar/Wind Harmer
2.213
3145783HORNRTN
Solar/Wind Harmer
0.692
3145783HORNRTN
Solar/Wind Harmer
0.277
3145796HORNRTN
Solar/Wind Harmer
0.466
971741AH1-377 GEN
Solar/Wind Harmer
15.218
970301AG2-198 GEN
Solar/Wind Harmer
6.446
316274AC1-208 GEN
Solar/Wind Harmer
0.781
958261AF2-120 GEN
Solar/Wind Harmer
4.978
3145933PARMELE
Solar/Wind Harmer
0.301
3145933PARMELE
Solar/Wind Harmer
0.15
939181AE1-148 GEN
Solar/Wind Harmer
7.079
957411AF2-035 GEN
Solar/Wind Harmer
6.288
970317AG2-208 GEN
Solar/Wind Harmer
5.826
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.011
970323AG2-213 GEN
Solar/Wind Harmer
6.221
971775AH1-396 GEN
Solar/Wind Harmer
0.233
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
1.525
3150341NORNECKC1
Adder
1.513
958211AF2-115 GEN
Solar/Wind Harmer
1.742
963191AG1-168 GEN
Solar/Wind Harmer
0.581
3144293JTRSVLE
Adder
0.462
3144293JTRSVLE
Adder
0.389
3147133PAMPLIN
Solar/Wind Harmer
0.145
3147133PAMPLIN
Solar/Wind Harmer
0.116
3145493TOT1
Solar/Wind Harmer
0.333
3145453TOT5
Solar/Wind Harmer
0.2
3145603CNETO
Solar/Wind Harmer
0.133
315673AE1-157 GEN
Solar/Wind Harmer
9.924
961601AG1-000A GEN
Solar/Wind Harmer
2.515
316263AC1-034 GEN
Solar/Wind Harmer
5.374
962561AG1-105 GEN
Solar/Wind Harmer
6.736
964791AG1-342 GEN
Solar/Wind Harmer
2.673
3146843MT LREL
Solar/Wind Harmer
0.139
3146843MT LREL
Solar/Wind Harmer
0.139
316468AD1-105 GEN
Solar/Wind Harmer
-0.045
3150391LDYSMT3
Adder
18.314
972195AH1-682 GEN
Adder
2.407
3146776BUCKING
Solar/Wind Harmer
0.547
3146776BUCKING
Solar/Wind Harmer
0.044
316222AC1-221 GEN
Solar/Wind Harmer
0.503
971489AH1-241 GEN
Solar/Wind Harmer
6.389
316447AC1-158 HLD
Solar/Wind Helper
11.807
3145543BTLEBRO
Solar/Wind Harmer
0.141
3145543BTLEBRO
Solar/Wind Harmer
0.141
971623AH1-311 GEN
Solar/Wind Harmer
0.283
971781AH1-399 GEN
Solar/Wind Harmer
0.181
3150401LDYSMT4
Adder
18.348
3150371LDYSMT1
Adder
17.729
3146776BUCKING
Solar/Wind Harmer
0.049
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
5.713
3141906WESTMOR
Solar/Wind Harmer
0.052
971683AH1-343 GEN
Solar/Wind Harmer
4.538
970737AG2-469 GEN
Solar/Wind Harmer
5.206
316283AC2-100 C
Solar/Wind Harmer
0.236
970221AG2-151 GEN
Solar/Wind Harmer
6.389
316044AC1-158 PL1
Solar/Wind Helper
5.365
316450AC1-158 RIC
Solar/Wind Helper
1.431
3147623JAMES R
Solar/Wind Harmer
0.278
972135AH1-637 GEN
Solar/Wind Harmer
0.998
316045AC1-158 PL2
Solar/Wind Helper
17.173
316006AB2-029 C
Solar/Wind Helper
0.112
LAGNLTFEXP_LAGN->PJM
CLTF
6.271
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.05
TVALTFEXP_TVA->PJM
CLTF
3.173
CPLELTFEXP_CPLE->PJM
CLTF
9.213
CBM West 2LTFEXP_CBM-W2->PJM
CBM
32.048
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.977
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.753
MECLTFEXP_MEC->PJM
CLTF
2.757
SIGELTFEXP_SIGE->PJM
CLTF
0.083
NYPJM->LTFIMP_NY
CLTF
2.427
LGEELTFEXP_LGEE->PJM
CLTF
1
WECLTFEXP_WEC->PJM
CLTF
0.483

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 11-2199_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 11-2199_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:118.03 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4650.58
MW Contribution:7.43
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
3.765
971285AH1-108 GEN
50/50
1.513
315244AE2-183_ST
50/50
5.368
963041AG1-153 GEN
50/50
4.955
3147346CASHSCORNER
Solar/Wind Harmer
0.41
316233AE1-074 FULL
Solar/Wind Harmer
0.609
971281AH1-106 GEN
Solar/Wind Harmer
3.677
971283AH1-107 GEN
Solar/Wind Harmer
3.677
941031AE2-094 GEN
Solar/Wind Harmer
40.621
944011AF1-069 GEN
Solar/Wind Harmer
12.728
970673AG2-436 GEN
Solar/Wind Harmer
44.754
970673AG2-436 GEN
Solar/Wind Harmer
22.66
971967AH1-528 GEN
Solar/Wind Harmer
39.617
3143316POE
Solar/Wind Harmer
-0.083
3151081ELIZAR1
Adder
16.891
3151091ELIZAR2
Adder
16.598
316315AB2-025 C
Solar/Wind Harmer
0.558
3152611GOSPORTB
Adder
2.345
3152621GOSPORTC
Adder
1.99
3152601GOSPORTA
Adder
1.836
315814AE2-033 C
Solar/Wind Harmer
19.205
957871AF2-081 GEN
Solar/Wind Harmer
10.278
971445AH1-216 GEN
Solar/Wind Harmer
12.702
319010AE1-072 C
Solar/Wind Harmer
4.148
3146406KITTY HAWK
Solar/Wind Harmer
0.017
315833AF1-017_GEN
Solar/Wind Harmer
3.893
316349AD2-085 GEN
Solar/Wind Harmer
1.823
316311AC2-079 GEN
Solar/Wind Harmer
10.336
316305AF2-043 C
Solar/Wind Harmer
0.617
972265AH1-717 GEN
Adder
14.121
3151201GRAVEL4
Adder
13.238
3151191GRAVEL3
Adder
13.07
3151211GRAVEL5
Adder
13.07
316369SG1_INVT
Solar/Wind Harmer
3.645
315835AF2-110_GEN
Solar/Wind Harmer
2.55
316132AB2-190 GEN1
Solar/Wind Harmer
2.062
313526AB2-022
Solar/Wind Harmer
0.549
3146486SUNBURY
Solar/Wind Harmer
-0.02
3146486SUNBURY
Solar/Wind Harmer
-0.02
316321Z2-027
Solar/Wind Harmer
0.547
3146396TANGLEW
Solar/Wind Harmer
0.373
3145176PASQUOTANK
Solar/Wind Harmer
-0.013
970085AG2-068 GEN
Solar/Wind Harmer
12.532
970581AG2-369 GEN
Solar/Wind Harmer
10.778
315611Z1-036_GEN2
Solar/Wind Harmer
4.908
3130156CHOWAN
Solar/Wind Harmer
-0.02
3130156CHOWAN
Solar/Wind Harmer
-0.02
315976AC1-164 GENA
Solar/Wind Harmer
20.509
316169AC1-164_GENC
Solar/Wind Harmer
17.718
315975AC1-164 GENB
Solar/Wind Harmer
0.607
957831AF2-077 GEN
Solar/Wind Harmer
0.583
3138283WHITEMARSH
Solar/Wind Harmer
0.03
971167AH1-042 GEN
Solar/Wind Harmer
18.644
316312AB1-027
Solar/Wind Harmer
0.652
315816AE2-034 GEN
Solar/Wind Harmer
1.563
3142433PROV 92
Adder
0.334
3142433PROV 92
Adder
0.334
3130546PLYMOUTH
Solar/Wind Harmer
-0.019
965291AG1-394 GEN
Solar/Wind Harmer
1.688
315732AD1-074 GEN1
Solar/Wind Harmer
3.84
315733AD1-074 GEN2
Solar/Wind Harmer
3.84
315735AD1-075 GEN1
Solar/Wind Harmer
1.921
3143873LANEXA
Solar/Wind Harmer
-0.011
316318V4-068
Solar/Wind Harmer
0.47
3145893MURPHYS
Solar/Wind Harmer
-0.051
3152251N ANNA1
50/50
17.76
3151791S ANNAG2
50/50
0.883
3151781S ANNAS1
50/50
0.454
3151741LOISA C
50/50
0.935
3151751LOISA D
50/50
17.091
970119AG2-088 GEN
50/50
28.238
3150851SPRUNCC
50/50
0.925
315243AE2-183_GT3
50/50
3.105
3151051BRUNSWICKS1
50/50
5.079
3151021BRUNSWICKG1
50/50
2.447
971451AH1-221 GEN
50/50
7.433
3147666LOUISA
Solar/Wind Harmer
-0.135
316192AB2-158 GEN
Solar/Wind Harmer
4.001
315683AE1-153 C
Solar/Wind Harmer
25.661
3143226MDLTHAN
Solar/Wind Harmer
-0.024
3143526WINTERP
Solar/Wind Harmer
-0.117
940641AE2-051 GEN
Solar/Wind Harmer
20.735
939411AE1-173 GEN
Solar/Wind Harmer
108.776
3143336POWHATN
Solar/Wind Harmer
2.52
316294AC1-161 GEN
Solar/Wind Harmer
6.764
944591AF1-124 GEN
Solar/Wind Harmer
94.789
316375AC2-012 GEN
Solar/Wind Harmer
7.16
3150981CHESPKA
Adder
2.299
970659AG2-427 GEN
Solar/Wind Harmer
10.98
316381AD1-082 GEN
Solar/Wind Harmer
1.894
315671AE2-027_GEN
Solar/Wind Harmer
15.462
970661AG2-428 GEN
Solar/Wind Harmer
21.895
3142543TWELFTH
Solar/Wind Harmer
-0.002
316388AE2-253 GEN
Solar/Wind Harmer
1.387
316336AC2-165 C
Solar/Wind Harmer
3.574
3145336SMITFLD
Solar/Wind Harmer
-0.082
3152261N ANNA2
50/50
17.758
3151771S ANNAG1
50/50
0.883
3151801S ANNAS2
50/50
0.454
3151761LOISA E
50/50
34.843
972183AH1-676 GEN
50/50
278.318
3150861SPRUNCD
50/50
0.925
3151031BRUNSWICKG2
50/50
2.447
3147666LOUISA
Solar/Wind Harmer
-0.078
316313AB2-026
Solar/Wind Harmer
0.573
316258AE1-075 C
Solar/Wind Harmer
0.516
316405AF2-144 C
Solar/Wind Harmer
0.544
3143336POWHATN
Solar/Wind Harmer
2.142
315773AC2-141 GEN
Solar/Wind Harmer
8.749
315839AE2-212 C
Solar/Wind Harmer
0.627
944581AF1-123 GEN
Solar/Wind Harmer
94.449
944601AF1-125 GEN
Solar/Wind Harmer
92.975
315813AE1-149 C
Solar/Wind Harmer
12.969
3151101ELIZAR3
Adder
17.107
3144873MCLAUGH
Solar/Wind Harmer
-0.001
965281AG1-393 GEN
Solar/Wind Harmer
2.584
970659AG2-427 GEN
Solar/Wind Harmer
1.946
3144536CHRHLND
Solar/Wind Harmer
-0.003
316083AB2-161 GEN
Solar/Wind Harmer
3.352
970661AG2-428 GEN
Solar/Wind Harmer
3.88
3145336SMITFLD
Solar/Wind Harmer
-0.008
3146456SLIGO L269
Solar/Wind Harmer
-0.02
971153AH1-033 GEN
Solar/Wind Harmer
2.501
3151221GRAVEL6
Adder
13.222
3151171GRAVELC
Adder
2.544
961611AG1-000B GEN
Solar/Wind Harmer
4.3
315778AD1-151 GEN
Solar/Wind Harmer
17.67
970129AG2-093 GEN
Solar/Wind Harmer
11.479
970133AG2-095 GEN
Solar/Wind Harmer
2.292
316320Y1-086
Solar/Wind Harmer
1.192
3143096IRON208
Adder
0.757
3143096IRON208
Adder
0.742
316435W1029_GEN3
Solar/Wind Harmer
3.654
970917AG2-570 GEN
Solar/Wind Harmer
50.335
3146516WINFALL
Solar/Wind Harmer
-0.02
3144216WINCHST
Adder
0.675
3150921YORKTN3
Adder
4.485
3146626S HERTFORD
Solar/Wind Harmer
-0.02
3145273HOLLAND
Solar/Wind Harmer
-0.015
3142946ENON
Solar/Wind Harmer
-0.007
971133AH1-012 GEN
50/50
5.78
3151731LOISA B
50/50
17.091
3151721LOISA A
50/50
17.002
970533AG2-339 GEN
50/50
17.139
970531AG2-338 GEN
50/50
6.856
315242AE2-183_GT2
50/50
3.105
315241AE2-183_GT1
50/50
3.086
972185AH1-677 GEN
50/50
11.194
3151041BRUNSWICKG3
50/50
2.447
972187AH1-678 GEN
50/50
5.616
966001AG1-469 GEN
Solar/Wind Harmer
0.521
971223AH1-071 GEN
Solar/Wind Harmer
2.974
3143526WINTERP
Solar/Wind Harmer
-0.117
3144356SAPONY
Solar/Wind Harmer
0.722
316036AC1-147 C
Solar/Wind Harmer
0.558
3150991CHESPKB
Adder
1.929
3150991CHESPKB
Adder
1.882
3142956BIRDNECK
Solar/Wind Harmer
1.109
316316AC1-027 C
Solar/Wind Harmer
0.635
316185AD1-033 GEN
Solar/Wind Harmer
2.18
3145506HICKORY
Solar/Wind Harmer
-0.082
3145506HICKORY
Solar/Wind Harmer
-0.049
3145506HICKORY
Solar/Wind Harmer
-0.012
316240AF1-291 C
Solar/Wind Harmer
0.622
970657AG2-426 GEN
Solar/Wind Harmer
6.448
970657AG2-426 GEN
Solar/Wind Harmer
1.348
970933AG2-581 GEN
Solar/Wind Harmer
19.327
944641AF1-129 GEN
Adder
87.32
316339AD2-160 GEN
Solar/Wind Harmer
1.387
316018AA1-139 ULT2
Solar/Wind Harmer
1.761
316017AA1-139 ULT1
Solar/Wind Harmer
1.663
316236AE1-162_GEN
Solar/Wind Harmer
0.619
3137176SLIGO L2192
Solar/Wind Harmer
-0.081
3146456SLIGO L269
Solar/Wind Harmer
2.424
3130086AYDLETT
Solar/Wind Harmer
-0.082
316033AB2-134 GEN
Solar/Wind Harmer
6.58
315697AD1-025 GEN
Solar/Wind Harmer
4.127
3146386ELIZ CT
Solar/Wind Harmer
-0.02
316431W1029_GEN1
Solar/Wind Harmer
3.654
316433W1029_GEN2
Solar/Wind Harmer
3.654
3146516WINFALL
Solar/Wind Harmer
-0.02
3146516WINFALL
Solar/Wind Harmer
-0.02
3146516WINFALL
Solar/Wind Harmer
-0.02
3146626S HERTFORD
Solar/Wind Harmer
-0.02
3146626S HERTFORD
Solar/Wind Harmer
-0.02
3142366NRTHEST
Adder
0.58
3142946ENON
Solar/Wind Harmer
-0.002
3150691DARBY 3
Adder
12.715
3150701DARBY 4
Adder
12.685
3150681DARBY 2
Adder
12.67
3150671DARBY 1
Adder
12.655
315742AE1-103 GEN
Solar/Wind Harmer
2.07
3146376EDENTON
Solar/Wind Harmer
0.584
3146376EDENTON
Solar/Wind Harmer
0.584
316075AC2-137 C
Solar/Wind Harmer
0.526
3142296MT RD221
Adder
0.55
970099AG2-077 GEN
Solar/Wind Harmer
24.26
316065AD1-022 GEN
Solar/Wind Harmer
9.447
3145893MURPHYS
Solar/Wind Harmer
0.526
3145893MURPHYS
Solar/Wind Harmer
-0.034
316441AF1-014 GEN
Solar/Wind Harmer
1.268
3146173TUNIS
Solar/Wind Harmer
-0.019
3146173TUNIS
Solar/Wind Harmer
-0.019
971741AH1-377 GEN
Solar/Wind Harmer
21.726
966871AG1-558 GEN
Solar/Wind Harmer
0.559
966871AG1-558 GEN
Solar/Wind Harmer
0.191
316181AB2-040 GEN
Solar/Wind Harmer
2.591
970301AG2-198 GEN
Solar/Wind Harmer
9.277
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.011
316426AA2-053 GEN
Solar/Wind Harmer
1.853
3145593CAROLNA
Solar/Wind Harmer
-0.018
3145593CAROLNA
Solar/Wind Harmer
-0.018
966811AG1-552 GEN
Solar/Wind Harmer
2.059
3145593CAROLNA
Solar/Wind Harmer
0.152
3145783HORNRTN
Solar/Wind Harmer
2.159
3145783HORNRTN
Solar/Wind Harmer
1.727
3145783HORNRTN
Solar/Wind Harmer
0.54
3145783HORNRTN
Solar/Wind Harmer
0.216
3145796HORNRTN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.018
3147133PAMPLIN
Solar/Wind Harmer
-0.014
3144293JTRSVLE
Adder
0.505
3144293JTRSVLE
Adder
0.425
3150341NORNECKC1
Adder
1.555
3150341NORNECKC1
Adder
1.542
3150391LDYSMT3
Adder
18.23
972195AH1-682 GEN
Adder
2.396
316447AC1-158 HLD
Solar/Wind Helper
11.902
315651AD1-115 GEN
Solar/Wind Helper
1.457
316382AG1-145 C
Solar/Wind Harmer
0.598
970293AG2-193 GEN
Solar/Wind Harmer
2.461
3146376EDENTON
Solar/Wind Harmer
-0.02
3142416OLDCHRC
Solar/Wind Harmer
1.951
315614AA2-178 GEN
Solar/Wind Harmer
2.084
3142433PROV 92
Adder
0.334
3142433PROV 92
Adder
0.334
316365GEN2_N
Solar/Wind Harmer
1.295
3156081AA2-088 GEN
Solar/Wind Harmer
6.195
971157AH1-035 GEN
Solar/Wind Harmer
2.38
315737AD1-076 GEN
Solar/Wind Harmer
3.609
3145893MURPHYS
Solar/Wind Harmer
0.132
3145893MURPHYS
Solar/Wind Harmer
-0.019
3146206CASHIE
Solar/Wind Harmer
-0.019
957521AF2-046 GEN
Solar/Wind Harmer
14.82
961681AG1-008 GEN
Solar/Wind Harmer
14.82
966621AG1-532 GEN
Solar/Wind Harmer
0.382
3141843SHACKLE
Adder
0.855
316203AE2-005 GEN
Solar/Wind Harmer
7.929
316280AD1-041 GEN
Solar/Wind Harmer
1.413
3141766HARMONY
Solar/Wind Harmer
1.669
3146173TUNIS
Solar/Wind Harmer
-0.019
316478AD1-087 GEN
Solar/Wind Harmer
1.619
316486AD2-202 GEN
Solar/Wind Harmer
0.474
316156AD2-030 GEN
Solar/Wind Harmer
0.499
3141873WAN 176
Solar/Wind Harmer
2.218
3156021HOLLOMANSOL
Solar/Wind Harmer
2.51
316463AE2-346 GEN
Solar/Wind Harmer
0.301
316140AB2-099
Solar/Wind Harmer
0.125
962331AG1-082 GEN
Solar/Wind Harmer
2.327
316473AC1-191 GEN
Solar/Wind Harmer
2.002
313506AB2-031 GEN
Solar/Wind Harmer
1.493
970909AG2-566 GEN
Solar/Wind Harmer
1.761
3146263WOODLND
Solar/Wind Harmer
-0.018
3147043LAWRENC
Solar/Wind Harmer
-0.011
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
316317KELFORD C
Solar/Wind Harmer
0.86
3145823KELFORD
Solar/Wind Harmer
-0.018
3145963POPLR C
Solar/Wind Harmer
-0.018
3145796HORNRTN
Solar/Wind Harmer
-0.072
3145796HORNRTN
Solar/Wind Harmer
-0.018
3146926FARMVIL
Solar/Wind Harmer
-0.011
942461AE2-259 GEN
Solar/Wind Harmer
2.701
3147133PAMPLIN
Solar/Wind Harmer
-0.056
3144293JTRSVLE
Adder
0.505
3150351NORNECKC2
Adder
1.505
3150401LDYSMT4
Adder
18.264
3150371LDYSMT1
Adder
17.648
316044AC1-158 PL1
Solar/Wind Helper
5.408
316450AC1-158 RIC
Solar/Wind Helper
1.442
316170AC1-121 GEN2
Solar/Wind Helper
0.698
971193AH1-056 GEN
Solar/Wind Harmer
5.031
3146456SLIGO L269
Solar/Wind Harmer
-0.02
316246AF1-032 C
Solar/Wind Harmer
0.414
316072AD1-144
Solar/Wind Harmer
0.413
3151171GRAVELC
Adder
1.935
961611AG1-000B GEN
Solar/Wind Harmer
10.078
971647AH1-324 GEN
Solar/Wind Harmer
10.206
316093AE2-104_GEN
Solar/Wind Harmer
5.931
971069AG2-661 GEN
Solar/Wind Harmer
3.227
316458AB2-190 GEN2
Solar/Wind Harmer
2.062
970129AG2-093 GEN
Solar/Wind Harmer
4.65
3143096IRON208
Adder
0.757
970919AG2-571 GEN
Solar/Wind Harmer
6.372
3146516WINFALL
Solar/Wind Harmer
-0.065
3146516WINFALL
Solar/Wind Harmer
-0.02
3138126ROCKLANDING
Solar/Wind Harmer
0.062
970087AG2-069 GEN
Solar/Wind Harmer
18.798
944631AF1-128 GEN
Adder
85.046
315800Z1-036_GEN1
Solar/Wind Harmer
4.908
971317AH1-138 GEN
Solar/Wind Harmer
2.48
316159AE1-175 C
Solar/Wind Harmer
0.532
3130156CHOWAN
Solar/Wind Harmer
-0.02
957481AF2-042 GEN
Solar/Wind Harmer
60.65
3142416OLDCHRC
Solar/Wind Harmer
-0.05
3142416OLDCHRC
Solar/Wind Harmer
-0.019
3145663CRESWEL
Solar/Wind Harmer
-0.054
971163AH1-040 GEN
Solar/Wind Harmer
18.105
3142433PROV 92
Solar/Wind Harmer
-0.077
3142433PROV 92
Adder
0.334
3142433PROV 92
Adder
0.334
316023GEN1_S
Solar/Wind Harmer
1.295
315693AD1-088 GEN
Solar/Wind Harmer
9.573
962491AG1-098 GEN
Solar/Wind Harmer
12.783
3145893MURPHYS
Solar/Wind Harmer
-0.075
3145893MURPHYS
Solar/Wind Harmer
0.56
970937AG2-583 GEN
Solar/Wind Harmer
13.548
3146206CASHIE
Solar/Wind Harmer
-0.019
971547AH1-271 GEN
Solar/Wind Harmer
4.71
960081AF2-299 GEN
Solar/Wind Harmer
2.117
971777AH1-397 GEN
Solar/Wind Harmer
2.211
3141843SHACKLE
Adder
0.855
3141766HARMONY
Solar/Wind Harmer
-0.004
3146173TUNIS
Solar/Wind Harmer
-0.019
971795AH1-408 GEN
Solar/Wind Harmer
13.912
3145683EARLEYS
Solar/Wind Harmer
-0.018
3146263WOODLND
Solar/Wind Harmer
-0.018
3147043LAWRENC
Adder
1.484
316011AB1-132 GEN
Solar/Wind Harmer
3.849
962571AG1-106 GEN
Solar/Wind Harmer
2.644
316190AA2-174 GEN
Solar/Wind Harmer
0.225
3138133OCRAN
Solar/Wind Harmer
-0.011
3145823KELFORD
Solar/Wind Harmer
-0.018
3145963POPLR C
Solar/Wind Harmer
-0.018
3145783HORNRTN
Solar/Wind Harmer
-0.018
3145796HORNRTN
Solar/Wind Harmer
-0.06
3145796HORNRTN
Solar/Wind Harmer
-0.018
3146926FARMVIL
Solar/Wind Harmer
-0.011
316174AB2-169 GEN
Solar/Wind Harmer
2.787
3144293JTRSVLE
Adder
0.505
3150351NORNECKC2
Adder
1.48
972197AH1-683 GEN
Adder
2.852
972219AH1-694 GEN
Adder
2.053
316045AC1-158 PL2
Solar/Wind Helper
17.311
316254AC1-120 GEN1
Solar/Wind Helper
2.093
316006AB2-029 C
Solar/Wind Helper
0.162
3145893MURPHYS
Solar/Wind Harmer
-0.019
3146206CASHIE
Solar/Wind Harmer
-0.019
970601AG2-382 GEN
Solar/Wind Harmer
8.243
946281AF1-292 GEN
Solar/Wind Harmer
0.421
316314AB2-024 C
Solar/Wind Harmer
1.606
315662AE1-191 GEN
Solar/Wind Harmer
2.261
315666AE1-190 GEN
Solar/Wind Harmer
0.565
316059AD1-063 C
Solar/Wind Harmer
0.424
957601AF2-054 GEN
Solar/Wind Harmer
0.559
3141873WAN 176
Solar/Wind Harmer
-0.004
316087AB2-174 GEN
Solar/Wind Harmer
2.66
3146043SEABORD
Solar/Wind Harmer
-0.019
3145513AHOSKIE
Solar/Wind Harmer
0.162
961941AG1-037 GEN
Solar/Wind Harmer
0.14
3145513AHOSKIE
Solar/Wind Harmer
-0.019
315607AA1-063A GEN
Solar/Wind Harmer
1.878
3145683EARLEYS
Solar/Wind Harmer
-0.037
3145683EARLEYS
Solar/Wind Harmer
-0.018
3145683EARLEYS
Solar/Wind Harmer
-0.018
3137643SOCKMAN
Solar/Wind Harmer
-0.073
315652AC1-086 GEN
Solar/Wind Harmer
20.696
3141913WHIT STONE
Solar/Wind Harmer
-0.018
3138133OCRAN
Solar/Wind Harmer
-0.006
972189AH1-679 GEN
Adder
2.721
3141783LANCAST
Solar/Wind Harmer
-0.011
3141783LANCAST
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.058
3145796HORNRTN
Solar/Wind Harmer
-0.007
3146033SCOT NK
Solar/Wind Harmer
-0.071
970285AG2-188 GEN
Solar/Wind Harmer
15.636
972205AH1-687 GEN
Adder
6.614
3150411LDYSMT5
Adder
18.321
3150381LDYSMT2
Adder
17.534
972213AH1-691 GEN
Adder
2.966
972215AH1-692 GEN
Adder
2.966
316164AC1-076 GEN
Solar/Wind Helper
2.448
LAGNLTFEXP_LAGN->PJM
CLTF
6.822
CBM South 2LTFEXP_CBM-S2->PJM
CBM
21.257
TVALTFEXP_TVA->PJM
CLTF
3.456
CPLELTFEXP_CPLE->PJM
CLTF
9.69
CBM West 2LTFEXP_CBM-W2->PJM
CBM
35.259
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.42
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.761
MECLTFEXP_MEC->PJM
CLTF
3.094
SIGELTFEXP_SIGE->PJM
CLTF
0.094
NYPJM->LTFIMP_NY
CLTF
2.632
LGEELTFEXP_LGEE->PJM
CLTF
1.138
WECLTFEXP_WEC->PJM
CLTF
0.551

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 11-2199_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 11-2199_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:117.81 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4641.56
MW Contribution:7.43
Bus #Bus NameTypeMW Contribution
971133AH1-012 GEN
50/50
5.78
3151731LOISA B
50/50
17.091
3151721LOISA A
50/50
17.002
970533AG2-339 GEN
50/50
17.139
970531AG2-338 GEN
50/50
6.856
315242AE2-183_GT2
50/50
3.105
315241AE2-183_GT1
50/50
3.086
972185AH1-677 GEN
50/50
11.194
3151041BRUNSWICKG3
50/50
2.447
972187AH1-678 GEN
50/50
5.616
966001AG1-469 GEN
Solar/Wind Harmer
0.521
971223AH1-071 GEN
Solar/Wind Harmer
2.974
3143526WINTERP
Solar/Wind Harmer
-0.117
3144356SAPONY
Solar/Wind Harmer
0.722
316036AC1-147 C
Solar/Wind Harmer
0.558
3150991CHESPKB
Adder
1.929
3150991CHESPKB
Adder
1.882
3142956BIRDNECK
Solar/Wind Harmer
1.109
316316AC1-027 C
Solar/Wind Harmer
0.635
316185AD1-033 GEN
Solar/Wind Harmer
2.18
3145506HICKORY
Solar/Wind Harmer
-0.082
3145506HICKORY
Solar/Wind Harmer
-0.049
3145506HICKORY
Solar/Wind Harmer
-0.012
316240AF1-291 C
Solar/Wind Harmer
0.622
970657AG2-426 GEN
Solar/Wind Harmer
6.448
970657AG2-426 GEN
Solar/Wind Harmer
1.348
970933AG2-581 GEN
Solar/Wind Harmer
19.327
944641AF1-129 GEN
Adder
87.32
316339AD2-160 GEN
Solar/Wind Harmer
1.387
316018AA1-139 ULT2
Solar/Wind Harmer
1.761
316017AA1-139 ULT1
Solar/Wind Harmer
1.663
316236AE1-162_GEN
Solar/Wind Harmer
0.619
3137176SLIGO L2192
Solar/Wind Harmer
-0.081
3146456SLIGO L269
Solar/Wind Harmer
2.424
3152261N ANNA2
50/50
17.758
3151771S ANNAG1
50/50
0.883
3151801S ANNAS2
50/50
0.454
3130086AYDLETT
Solar/Wind Harmer
-0.082
316033AB2-134 GEN
Solar/Wind Harmer
6.58
315697AD1-025 GEN
Solar/Wind Harmer
4.127
3146386ELIZ CT
Solar/Wind Harmer
-0.02
316431W1029_GEN1
Solar/Wind Harmer
3.654
316433W1029_GEN2
Solar/Wind Harmer
3.654
3146516WINFALL
Solar/Wind Harmer
-0.02
3146516WINFALL
Solar/Wind Harmer
-0.02
3146516WINFALL
Solar/Wind Harmer
-0.02
3146626S HERTFORD
Solar/Wind Harmer
-0.02
3146626S HERTFORD
Solar/Wind Harmer
-0.02
3142366NRTHEST
Adder
0.58
3142946ENON
Solar/Wind Harmer
-0.002
3150691DARBY 3
Adder
12.715
3150701DARBY 4
Adder
12.685
3150681DARBY 2
Adder
12.67
3150671DARBY 1
Adder
12.655
315742AE1-103 GEN
Solar/Wind Harmer
2.07
3146376EDENTON
Solar/Wind Harmer
0.584
3146376EDENTON
Solar/Wind Harmer
0.584
316075AC2-137 C
Solar/Wind Harmer
0.526
3142296MT RD221
Adder
0.55
970099AG2-077 GEN
Solar/Wind Harmer
24.26
316065AD1-022 GEN
Solar/Wind Harmer
9.447
3145893MURPHYS
Solar/Wind Harmer
0.526
3145893MURPHYS
Solar/Wind Harmer
-0.034
316441AF1-014 GEN
Solar/Wind Harmer
1.268
3146173TUNIS
Solar/Wind Harmer
-0.019
3146173TUNIS
Solar/Wind Harmer
-0.019
971741AH1-377 GEN
Solar/Wind Harmer
21.726
966871AG1-558 GEN
Solar/Wind Harmer
0.559
966871AG1-558 GEN
Solar/Wind Harmer
0.191
316181AB2-040 GEN
Solar/Wind Harmer
2.591
970301AG2-198 GEN
Solar/Wind Harmer
9.277
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.011
316426AA2-053 GEN
Solar/Wind Harmer
1.853
3145593CAROLNA
Solar/Wind Harmer
-0.018
3145593CAROLNA
Solar/Wind Harmer
-0.018
966811AG1-552 GEN
Solar/Wind Harmer
2.059
3145593CAROLNA
Solar/Wind Harmer
0.152
3145783HORNRTN
Solar/Wind Harmer
2.159
3145783HORNRTN
Solar/Wind Harmer
1.727
3145783HORNRTN
Solar/Wind Harmer
0.54
3145783HORNRTN
Solar/Wind Harmer
0.216
3145796HORNRTN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.018
3147133PAMPLIN
Solar/Wind Harmer
-0.014
3144293JTRSVLE
Adder
0.505
3144293JTRSVLE
Adder
0.425
3150341NORNECKC1
Adder
1.555
3150341NORNECKC1
Adder
1.542
3150391LDYSMT3
Adder
18.23
972195AH1-682 GEN
Adder
2.396
316447AC1-158 HLD
Solar/Wind Helper
11.902
315651AD1-115 GEN
Solar/Wind Helper
1.457
3152251N ANNA1
50/50
17.76
3151791S ANNAG2
50/50
0.883
3151781S ANNAS1
50/50
0.454
3151741LOISA C
50/50
0.935
3151751LOISA D
50/50
17.091
970119AG2-088 GEN
50/50
28.238
3150851SPRUNCC
50/50
0.925
315243AE2-183_GT3
50/50
3.105
3151051BRUNSWICKS1
50/50
5.079
3151021BRUNSWICKG1
50/50
2.447
971451AH1-221 GEN
50/50
7.433
3147666LOUISA
Solar/Wind Harmer
-0.135
316192AB2-158 GEN
Solar/Wind Harmer
4.001
3143226MDLTHAN
Solar/Wind Harmer
-0.024
3143526WINTERP
Solar/Wind Harmer
-0.117
940641AE2-051 GEN
Solar/Wind Harmer
20.735
939411AE1-173 GEN
Solar/Wind Harmer
108.776
3143336POWHATN
Solar/Wind Harmer
2.52
316294AC1-161 GEN
Solar/Wind Harmer
6.764
944591AF1-124 GEN
Solar/Wind Harmer
94.789
316375AC2-012 GEN
Solar/Wind Harmer
7.16
3150981CHESPKA
Adder
2.299
970659AG2-427 GEN
Solar/Wind Harmer
10.98
316381AD1-082 GEN
Solar/Wind Harmer
1.894
315671AE2-027_GEN
Solar/Wind Harmer
15.462
970661AG2-428 GEN
Solar/Wind Harmer
21.895
3142543TWELFTH
Solar/Wind Harmer
-0.002
316303AF2-085
50/50
3.765
971285AH1-108 GEN
50/50
1.513
315244AE2-183_ST
50/50
5.368
963041AG1-153 GEN
50/50
4.955
3147346CASHSCORNER
Solar/Wind Harmer
0.41
316233AE1-074 FULL
Solar/Wind Harmer
0.609
971281AH1-106 GEN
Solar/Wind Harmer
3.677
971283AH1-107 GEN
Solar/Wind Harmer
3.677
941031AE2-094 GEN
Solar/Wind Harmer
40.621
944011AF1-069 GEN
Solar/Wind Harmer
12.728
970673AG2-436 GEN
Solar/Wind Harmer
44.754
970673AG2-436 GEN
Solar/Wind Harmer
22.66
971967AH1-528 GEN
Solar/Wind Harmer
39.617
3143316POE
Solar/Wind Harmer
-0.083
3151081ELIZAR1
Adder
16.891
3151091ELIZAR2
Adder
16.598
316315AB2-025 C
Solar/Wind Harmer
0.558
3152611GOSPORTB
Adder
2.345
3152621GOSPORTC
Adder
1.99
3152601GOSPORTA
Adder
1.836
315814AE2-033 C
Solar/Wind Harmer
19.205
957871AF2-081 GEN
Solar/Wind Harmer
10.278
971445AH1-216 GEN
Solar/Wind Harmer
12.702
319010AE1-072 C
Solar/Wind Harmer
4.148
3146406KITTY HAWK
Solar/Wind Harmer
0.017
315833AF1-017_GEN
Solar/Wind Harmer
3.893
316349AD2-085 GEN
Solar/Wind Harmer
1.823
316311AC2-079 GEN
Solar/Wind Harmer
10.336
316305AF2-043 C
Solar/Wind Harmer
0.617
972265AH1-717 GEN
Adder
14.121
3151201GRAVEL4
Adder
13.238
3151191GRAVEL3
Adder
13.07
3151211GRAVEL5
Adder
13.07
316369SG1_INVT
Solar/Wind Harmer
3.645
315835AF2-110_GEN
Solar/Wind Harmer
2.55
316132AB2-190 GEN1
Solar/Wind Harmer
2.062
313526AB2-022
Solar/Wind Harmer
0.549
3146486SUNBURY
Solar/Wind Harmer
-0.02
3146486SUNBURY
Solar/Wind Harmer
-0.02
316321Z2-027
Solar/Wind Harmer
0.547
3146396TANGLEW
Solar/Wind Harmer
0.373
3145176PASQUOTANK
Solar/Wind Harmer
-0.013
970085AG2-068 GEN
Solar/Wind Harmer
12.532
970581AG2-369 GEN
Solar/Wind Harmer
10.778
315611Z1-036_GEN2
Solar/Wind Harmer
4.908
3130156CHOWAN
Solar/Wind Harmer
-0.02
3130156CHOWAN
Solar/Wind Harmer
-0.02
315976AC1-164 GENA
Solar/Wind Harmer
20.509
316169AC1-164_GENC
Solar/Wind Harmer
17.718
315975AC1-164 GENB
Solar/Wind Harmer
0.607
957831AF2-077 GEN
Solar/Wind Harmer
0.583
3138283WHITEMARSH
Solar/Wind Harmer
0.03
971167AH1-042 GEN
Solar/Wind Harmer
18.644
316312AB1-027
Solar/Wind Harmer
0.652
315816AE2-034 GEN
Solar/Wind Harmer
1.563
3142433PROV 92
Adder
0.334
3142433PROV 92
Adder
0.334
3130546PLYMOUTH
Solar/Wind Harmer
-0.019
965291AG1-394 GEN
Solar/Wind Harmer
1.688
315732AD1-074 GEN1
Solar/Wind Harmer
3.84
315733AD1-074 GEN2
Solar/Wind Harmer
3.84
315735AD1-075 GEN1
Solar/Wind Harmer
1.921
3143873LANEXA
Solar/Wind Harmer
-0.011
316318V4-068
Solar/Wind Harmer
0.47
3145893MURPHYS
Solar/Wind Harmer
-0.051
3145893MURPHYS
Solar/Wind Harmer
-0.019
3146206CASHIE
Solar/Wind Harmer
-0.019
970601AG2-382 GEN
Solar/Wind Harmer
8.243
946281AF1-292 GEN
Solar/Wind Harmer
0.421
316314AB2-024 C
Solar/Wind Harmer
1.606
315662AE1-191 GEN
Solar/Wind Harmer
2.261
315666AE1-190 GEN
Solar/Wind Harmer
0.565
316059AD1-063 C
Solar/Wind Harmer
0.424
957601AF2-054 GEN
Solar/Wind Harmer
0.559
3141873WAN 176
Solar/Wind Harmer
-0.004
316087AB2-174 GEN
Solar/Wind Harmer
2.66
3146043SEABORD
Solar/Wind Harmer
-0.019
3145513AHOSKIE
Solar/Wind Harmer
0.162
961941AG1-037 GEN
Solar/Wind Harmer
0.14
3145513AHOSKIE
Solar/Wind Harmer
-0.019
315607AA1-063A GEN
Solar/Wind Harmer
1.878
3145683EARLEYS
Solar/Wind Harmer
-0.037
3145683EARLEYS
Solar/Wind Harmer
-0.018
3145683EARLEYS
Solar/Wind Harmer
-0.018
3137643SOCKMAN
Solar/Wind Harmer
-0.073
315652AC1-086 GEN
Solar/Wind Harmer
20.696
3141913WHIT STONE
Solar/Wind Harmer
-0.018
3138133OCRAN
Solar/Wind Harmer
-0.006
972189AH1-679 GEN
Adder
2.721
3141783LANCAST
Solar/Wind Harmer
-0.011
3141783LANCAST
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.058
3145796HORNRTN
Solar/Wind Harmer
-0.007
3146033SCOT NK
Solar/Wind Harmer
-0.071
970285AG2-188 GEN
Solar/Wind Harmer
15.636
315657AE1-056 GEN
Solar/Wind Harmer
6.696
972205AH1-687 GEN
Adder
6.614
3150411LDYSMT5
Adder
18.321
3150381LDYSMT2
Adder
17.534
972213AH1-691 GEN
Adder
2.966
972215AH1-692 GEN
Adder
2.966
316164AC1-076 GEN
Solar/Wind Helper
2.448
970831AG2-522 GEN
Solar/Wind Harmer
3.798
316388AE2-253 GEN
Solar/Wind Harmer
1.387
316336AC2-165 C
Solar/Wind Harmer
3.574
3145336SMITFLD
Solar/Wind Harmer
-0.082
3146456SLIGO L269
Solar/Wind Harmer
-0.02
316246AF1-032 C
Solar/Wind Harmer
0.414
316072AD1-144
Solar/Wind Harmer
0.413
3151171GRAVELC
Adder
1.935
961611AG1-000B GEN
Solar/Wind Harmer
10.078
971647AH1-324 GEN
Solar/Wind Harmer
10.206
316093AE2-104_GEN
Solar/Wind Harmer
5.931
971069AG2-661 GEN
Solar/Wind Harmer
3.227
316458AB2-190 GEN2
Solar/Wind Harmer
2.062
970129AG2-093 GEN
Solar/Wind Harmer
4.65
3143096IRON208
Adder
0.757
970919AG2-571 GEN
Solar/Wind Harmer
6.372
3146516WINFALL
Solar/Wind Harmer
-0.065
3146516WINFALL
Solar/Wind Harmer
-0.02
3138126ROCKLANDING
Solar/Wind Harmer
0.062
970087AG2-069 GEN
Solar/Wind Harmer
18.798
944631AF1-128 GEN
Adder
85.046
315800Z1-036_GEN1
Solar/Wind Harmer
4.908
971317AH1-138 GEN
Solar/Wind Harmer
2.48
316159AE1-175 C
Solar/Wind Harmer
0.532
3130156CHOWAN
Solar/Wind Harmer
-0.02
957481AF2-042 GEN
Solar/Wind Harmer
60.65
3142416OLDCHRC
Solar/Wind Harmer
-0.05
3142416OLDCHRC
Solar/Wind Harmer
-0.019
3145663CRESWEL
Solar/Wind Harmer
-0.054
971163AH1-040 GEN
Solar/Wind Harmer
18.105
3142433PROV 92
Solar/Wind Harmer
-0.077
3142433PROV 92
Adder
0.334
3142433PROV 92
Adder
0.334
316023GEN1_S
Solar/Wind Harmer
1.295
315693AD1-088 GEN
Solar/Wind Harmer
9.573
962491AG1-098 GEN
Solar/Wind Harmer
12.783
3145893MURPHYS
Solar/Wind Harmer
-0.075
3145893MURPHYS
Solar/Wind Harmer
0.56
970937AG2-583 GEN
Solar/Wind Harmer
13.548
3146206CASHIE
Solar/Wind Harmer
-0.019
971547AH1-271 GEN
Solar/Wind Harmer
4.71
960081AF2-299 GEN
Solar/Wind Harmer
2.117
971777AH1-397 GEN
Solar/Wind Harmer
2.211
3141843SHACKLE
Adder
0.855
3141766HARMONY
Solar/Wind Harmer
-0.004
3146173TUNIS
Solar/Wind Harmer
-0.019
971795AH1-408 GEN
Solar/Wind Harmer
13.912
3145683EARLEYS
Solar/Wind Harmer
-0.018
3146263WOODLND
Solar/Wind Harmer
-0.018
3147043LAWRENC
Adder
1.484
316011AB1-132 GEN
Solar/Wind Harmer
3.849
962571AG1-106 GEN
Solar/Wind Harmer
2.644
316190AA2-174 GEN
Solar/Wind Harmer
0.225
3138133OCRAN
Solar/Wind Harmer
-0.011
3145823KELFORD
Solar/Wind Harmer
-0.018
3145963POPLR C
Solar/Wind Harmer
-0.018
3145783HORNRTN
Solar/Wind Harmer
-0.018
3145796HORNRTN
Solar/Wind Harmer
-0.06
3145796HORNRTN
Solar/Wind Harmer
-0.018
3146926FARMVIL
Solar/Wind Harmer
-0.011
316174AB2-169 GEN
Solar/Wind Harmer
2.787
3144293JTRSVLE
Adder
0.505
3150351NORNECKC2
Adder
1.48
972197AH1-683 GEN
Adder
2.852
972219AH1-694 GEN
Adder
2.053
316045AC1-158 PL2
Solar/Wind Helper
17.311
316254AC1-120 GEN1
Solar/Wind Helper
2.093
316006AB2-029 C
Solar/Wind Helper
0.162
3151761LOISA E
50/50
34.843
972183AH1-676 GEN
50/50
278.318
3150861SPRUNCD
50/50
0.925
3151031BRUNSWICKG2
50/50
2.447
3147666LOUISA
Solar/Wind Harmer
-0.078
316313AB2-026
Solar/Wind Harmer
0.573
316258AE1-075 C
Solar/Wind Harmer
0.516
316405AF2-144 C
Solar/Wind Harmer
0.544
3143336POWHATN
Solar/Wind Harmer
2.142
315773AC2-141 GEN
Solar/Wind Harmer
8.749
315839AE2-212 C
Solar/Wind Harmer
0.627
944581AF1-123 GEN
Solar/Wind Harmer
94.449
944601AF1-125 GEN
Solar/Wind Harmer
92.975
315813AE1-149 C
Solar/Wind Harmer
12.969
3151101ELIZAR3
Adder
17.107
3144873MCLAUGH
Solar/Wind Harmer
-0.001
965281AG1-393 GEN
Solar/Wind Harmer
2.584
970659AG2-427 GEN
Solar/Wind Harmer
1.946
3144536CHRHLND
Solar/Wind Harmer
-0.003
316083AB2-161 GEN
Solar/Wind Harmer
3.352
970661AG2-428 GEN
Solar/Wind Harmer
3.88
3145336SMITFLD
Solar/Wind Harmer
-0.008
3146456SLIGO L269
Solar/Wind Harmer
-0.02
971153AH1-033 GEN
Solar/Wind Harmer
2.501
3151221GRAVEL6
Adder
13.222
3151171GRAVELC
Adder
2.544
961611AG1-000B GEN
Solar/Wind Harmer
4.3
315778AD1-151 GEN
Solar/Wind Harmer
17.67
970129AG2-093 GEN
Solar/Wind Harmer
11.479
970133AG2-095 GEN
Solar/Wind Harmer
2.292
316320Y1-086
Solar/Wind Harmer
1.192
3143096IRON208
Adder
0.757
3143096IRON208
Adder
0.742
316435W1029_GEN3
Solar/Wind Harmer
3.654
970917AG2-570 GEN
Solar/Wind Harmer
50.335
3146516WINFALL
Solar/Wind Harmer
-0.02
3144216WINCHST
Adder
0.675
3150921YORKTN3
Adder
4.485
3146626S HERTFORD
Solar/Wind Harmer
-0.02
3145273HOLLAND
Solar/Wind Harmer
-0.015
3142946ENON
Solar/Wind Harmer
-0.007
316382AG1-145 C
Solar/Wind Harmer
0.598
970293AG2-193 GEN
Solar/Wind Harmer
2.461
3146376EDENTON
Solar/Wind Harmer
-0.02
3142416OLDCHRC
Solar/Wind Harmer
1.951
315614AA2-178 GEN
Solar/Wind Harmer
2.084
3142433PROV 92
Adder
0.334
3142433PROV 92
Adder
0.334
316365GEN2_N
Solar/Wind Harmer
1.295
3156081AA2-088 GEN
Solar/Wind Harmer
6.195
971157AH1-035 GEN
Solar/Wind Harmer
2.38
315737AD1-076 GEN
Solar/Wind Harmer
3.609
3145893MURPHYS
Solar/Wind Harmer
0.132
3145893MURPHYS
Solar/Wind Harmer
-0.019
3146206CASHIE
Solar/Wind Harmer
-0.019
957521AF2-046 GEN
Solar/Wind Harmer
14.82
961681AG1-008 GEN
Solar/Wind Harmer
14.82
966621AG1-532 GEN
Solar/Wind Harmer
0.382
3141843SHACKLE
Adder
0.855
316203AE2-005 GEN
Solar/Wind Harmer
7.929
316280AD1-041 GEN
Solar/Wind Harmer
1.413
3141766HARMONY
Solar/Wind Harmer
1.669
3146173TUNIS
Solar/Wind Harmer
-0.019
316478AD1-087 GEN
Solar/Wind Harmer
1.619
316486AD2-202 GEN
Solar/Wind Harmer
0.474
316156AD2-030 GEN
Solar/Wind Harmer
0.499
3141873WAN 176
Solar/Wind Harmer
2.218
3156021HOLLOMANSOL
Solar/Wind Harmer
2.51
316463AE2-346 GEN
Solar/Wind Harmer
0.301
316140AB2-099
Solar/Wind Harmer
0.125
962331AG1-082 GEN
Solar/Wind Harmer
2.327
316473AC1-191 GEN
Solar/Wind Harmer
2.002
313506AB2-031 GEN
Solar/Wind Harmer
1.493
970909AG2-566 GEN
Solar/Wind Harmer
1.761
3146263WOODLND
Solar/Wind Harmer
-0.018
3147043LAWRENC
Solar/Wind Harmer
-0.011
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
316317KELFORD C
Solar/Wind Harmer
0.86
3145823KELFORD
Solar/Wind Harmer
-0.018
3145963POPLR C
Solar/Wind Harmer
-0.018
3145796HORNRTN
Solar/Wind Harmer
-0.072
3145796HORNRTN
Solar/Wind Harmer
-0.018
3146926FARMVIL
Solar/Wind Harmer
-0.011
942461AE2-259 GEN
Solar/Wind Harmer
2.701
3147133PAMPLIN
Solar/Wind Harmer
-0.056
971193AH1-056 GEN
Solar/Wind Harmer
11.159
3144293JTRSVLE
Adder
0.505
3150351NORNECKC2
Adder
1.505
3150401LDYSMT4
Adder
18.264
3150371LDYSMT1
Adder
17.648
316044AC1-158 PL1
Solar/Wind Helper
5.408
316450AC1-158 RIC
Solar/Wind Helper
1.442
316170AC1-121 GEN2
Solar/Wind Helper
0.698
LAGNLTFEXP_LAGN->PJM
CLTF
6.822
CBM South 2LTFEXP_CBM-S2->PJM
CBM
21.257
TVALTFEXP_TVA->PJM
CLTF
3.456
CPLELTFEXP_CPLE->PJM
CLTF
9.69
CBM West 2LTFEXP_CBM-W2->PJM
CBM
35.259
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.42
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.761
MECLTFEXP_MEC->PJM
CLTF
3.094
SIGELTFEXP_SIGE->PJM
CLTF
0.094
NYPJM->LTFIMP_NY
CLTF
2.632
LGEELTFEXP_LGEE->PJM
CLTF
1.138
WECLTFEXP_WEC->PJM
CLTF
0.551

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 585_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:139.73 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5687.33
MW Contribution:25.83
Bus #Bus NameTypeMW Contribution
963041AG1-153 GEN
50/50
17.22
315244AE2-183_ST
50/50
18.443
3151541CLOVER2
50/50
10.593
3151611KERR 4
50/50
0.604
3151621KERR 5
50/50
0.604
3151631KERR 6
50/50
0.604
3151641KERR 7
50/50
0.604
971967AH1-528 GEN
Solar/Wind Harmer
109.53
970673AG2-436 GEN
Solar/Wind Harmer
137.75
970673AG2-436 GEN
Solar/Wind Harmer
91.833
941031AE2-094 GEN
Solar/Wind Harmer
118.914
944011AF1-069 GEN
Solar/Wind Harmer
38.854
970085AG2-068 GEN
Solar/Wind Harmer
32.15
970581AG2-369 GEN
Solar/Wind Harmer
27.649
3147173SINAI
Solar/Wind Harmer
0.345
3147243WELCO
Solar/Wind Harmer
0.216
316118AC1-105 GEN
Solar/Wind Harmer
0.86
970865AG2-541 GEN
Solar/Wind Harmer
10.119
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
4.678
3144303KENBRDG
Solar/Wind Harmer
0.222
970683AG2-441 GEN
Solar/Wind Harmer
18.278
970681AG2-440 GEN
Solar/Wind Harmer
14.623
946301AF1-294 GEN
Solar/Wind Harmer
5.338
961791AG1-021 GEN
Solar/Wind Harmer
2.597
315657AE1-056 GEN
Solar/Wind Harmer
9.239
316123AC1-075 GEN
Solar/Wind Harmer
0.351
970165AG2-112 GEN
Solar/Wind Harmer
2.08
970163AG2-111 GEN
Solar/Wind Harmer
1.985
970831AG2-522 GEN
Solar/Wind Harmer
8.286
970285AG2-188 GEN
Solar/Wind Harmer
14.461
971845AH1-439 GEN
Solar/Wind Harmer
7.612
270069AE2-166 C O1
Solar/Wind Harmer
0.005
3143316POE
Solar/Wind Helper
1.64
319010AE1-072 C
Solar/Wind Helper
4.299
316369SG1_INVT
Solar/Wind Helper
1.8
316305AF2-043 C
Solar/Wind Helper
0.499
316132AB2-190 GEN1
Solar/Wind Helper
2.107
957831AF2-077 GEN
Solar/Wind Helper
0.495
316349AD2-085 GEN
Solar/Wind Helper
1.649
313526AB2-022
Solar/Wind Helper
0.533
957601AF2-054 GEN
Solar/Wind Helper
0.467
3141873WAN 176
Solar/Wind Helper
0.07
315662AE1-191 GEN
Solar/Wind Helper
1.865
315666AE1-190 GEN
Solar/Wind Helper
0.466
316059AD1-063 C
Solar/Wind Helper
0.348
3141913WHIT STONE
Solar/Wind Helper
0.345
3138133OCRAN
Solar/Wind Helper
0.103
3143873LANEXA
Solar/Wind Helper
0.206
3141783LANCAST
Solar/Wind Helper
0.205
3141783LANCAST
Solar/Wind Helper
0.137
3146486SUNBURY
Solar/Wind Helper
0.341
3146486SUNBURY
Solar/Wind Helper
0.341
316321Z2-027
Solar/Wind Helper
0.514
3151051BRUNSWICKS1
50/50
17.651
3151021BRUNSWICKG1
50/50
8.505
971451AH1-221 GEN
50/50
25.831
315243AE2-183_GT3
50/50
10.667
3151531CLOVER1
50/50
10.644
3151601KERR 3
50/50
0.604
3151581KERR 1
50/50
0.216
3144293JTRSVLE
50/50
0.914
971629AH1-314 GEN
50/50
19.06
3151561HALLBR1
50/50
0.404
970919AG2-571 GEN
Solar/Wind Harmer
21.586
970087AG2-069 GEN
Solar/Wind Harmer
48.225
957481AF2-042 GEN
Solar/Wind Harmer
144.711
315693AD1-088 GEN
Solar/Wind Harmer
23.762
962491AG1-098 GEN
Solar/Wind Harmer
27.839
315687AD1-152 GEN
Solar/Wind Harmer
0.015
316003AC1-222 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.882
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970685AG2-442 GEN
Solar/Wind Harmer
20.472
963171AG1-166 GEN
Solar/Wind Harmer
1.443
971563AH1-280 GEN
Solar/Wind Harmer
2.885
3146926FARMVIL
Solar/Wind Harmer
0.151
971065AG2-659 GEN
Solar/Wind Harmer
9.511
316129AC1-054 GEN
Solar/Wind Harmer
0.786
970223AG2-152 GEN
Solar/Wind Harmer
12.908
270016AE1-250 BESS
Solar/Wind Harmer
0.005
3147123OTTER R
Solar/Wind Harmer
0.097
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.064
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
3147312GRETNA
Solar/Wind Harmer
0.115
3146802CHATHAM
Solar/Wind Harmer
0.108
941801AE2-185 GEN
Solar/Wind Harmer
4.622
270030AE2-140 GEN
Solar/Wind Harmer
14.688
3145543BTLEBRO
Solar/Wind Harmer
0.123
3145543BTLEBRO
Solar/Wind Harmer
0.099
316359AB2-059 GEN
Solar/Wind Harmer
0.442
316049AB1-081 GEN
Solar/Wind Harmer
0.704
3142053HEARTS
Solar/Wind Harmer
0.217
316294AC1-161 GEN
Solar/Wind Helper
8.153
316375AC2-012 GEN
Solar/Wind Helper
1.068
3145336SMITFLD
Solar/Wind Helper
1.575
316388AE2-253 GEN
Solar/Wind Helper
1.472
3146456SLIGO L269
Solar/Wind Helper
0.379
316381AD1-082 GEN
Solar/Wind Helper
1.955
316072AD1-144
Solar/Wind Helper
0.428
316246AF1-032 C
Solar/Wind Helper
0.424
316159AE1-175 C
Solar/Wind Helper
0.562
316458AB2-190 GEN2
Solar/Wind Helper
2.107
3141766HARMONY
Solar/Wind Helper
0.069
3142433PROV 92
Solar/Wind Helper
1.376
3138133OCRAN
Solar/Wind Helper
0.206
3142543TWELFTH
Solar/Wind Helper
0.032
964211AG1-282 GEN
Solar/Wind Helper
0.439
3141726DUNNSVL
Solar/Wind Helper
1.304
316337AD2-073 GEN
Solar/Wind Helper
0.478
3142416OLDCHRC
Solar/Wind Helper
0.816
3142416OLDCHRC
Solar/Wind Helper
0.312
3146516WINFALL
Solar/Wind Helper
1.016
3146516WINFALL
Solar/Wind Helper
0.314
3143526WINTERP
Solar/Wind Helper
1.596
3143226MDLTHAN
Solar/Wind Helper
0.3
315800Z1-036_GEN1
Solar/Wind Helper
1.497
3130156CHOWAN
Solar/Wind Helper
0.241
3145176PASQUOTANK
Solar/Wind Helper
0.209
316315AB2-025 C
Solar/Wind Helper
0.507
3141813NORNECK
Solar/Wind Helper
0.325
316312AB1-027
Solar/Wind Helper
0.597
316233AE1-074 FULL
Solar/Wind Helper
0.469
316223AC1-118
Solar/Wind Helper
0.466
315611Z1-036_GEN2
Solar/Wind Helper
1.497
3130156CHOWAN
Solar/Wind Helper
0.241
3130156CHOWAN
Solar/Wind Helper
0.241
3151031BRUNSWICKG2
50/50
8.505
970413AG2-270 GEN
50/50
46.449
3151591KERR 2
50/50
0.604
3144293JTRSVLE
50/50
0.914
970917AG2-570 GEN
Solar/Wind Harmer
53.965
316478AD1-087 GEN
Solar/Wind Harmer
1.733
316486AD2-202 GEN
Solar/Wind Harmer
0.509
970909AG2-566 GEN
Solar/Wind Harmer
3.791
316248AF1-058 C
Solar/Wind Harmer
0.003
960061AF2-297 GEN
Solar/Wind Harmer
14.727
971683AH1-343 GEN
Solar/Wind Harmer
11.379
316283AC2-100 C
Solar/Wind Harmer
0.592
316131AB2-060 GEN
Solar/Wind Harmer
0.901
964241AG1-285 GEN
Solar/Wind Harmer
18.92
315785AD2-033 C
Solar/Wind Harmer
2.274
970257AG2-171 GEN
Solar/Wind Harmer
8.9
959311AF2-222 GEN
Solar/Wind Harmer
24.62
963181AG1-167 GEN
Solar/Wind Harmer
1.082
3147133PAMPLIN
Solar/Wind Harmer
0.841
971193AH1-056 GEN
Solar/Wind Harmer
16.311
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
3146926FARMVIL
Solar/Wind Harmer
0.151
3146776BUCKING
Solar/Wind Harmer
0.058
270018AE2-047 C O1
Solar/Wind Harmer
0.003
270197AD1-017 GEN1
Solar/Wind Harmer
1.012
3147312GRETNA
Solar/Wind Harmer
0.029
941821AE2-187 GEN
Solar/Wind Harmer
4.622
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
270336AE1-100 GEN
Solar/Wind Harmer
0.004
3145543BTLEBRO
Solar/Wind Harmer
0.123
3145543BTLEBRO
Solar/Wind Harmer
0.123
971623AH1-311 GEN
Solar/Wind Harmer
0.246
961601AG1-000A GEN
Solar/Wind Harmer
8.544
315773AC2-141 GEN
Solar/Wind Helper
9.595
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.061
3145336SMITFLD
Solar/Wind Helper
0.157
315839AE2-212 C
Solar/Wind Helper
0.523
3146456SLIGO L269
Solar/Wind Helper
0.379
316382AG1-145 C
Solar/Wind Helper
0.498
316320Y1-086
Solar/Wind Helper
0.156
316156AD2-030 GEN
Solar/Wind Helper
0.525
316280AD1-041 GEN
Solar/Wind Helper
1.166
3142946ENON
Solar/Wind Helper
0.114
316484AD2-074 GEN
Solar/Wind Helper
0.648
316404AE1-155 C
Solar/Wind Helper
2.8
316435W1029_GEN3
Solar/Wind Helper
1.295
3146516WINFALL
Solar/Wind Helper
0.314
3141906WESTMOR
Solar/Wind Helper
0.122
316473AC1-191 GEN
Solar/Wind Helper
1.829
3146626S HERTFORD
Solar/Wind Helper
0.296
3145273HOLLAND
Solar/Wind Helper
0.201
966881AG1-559 GEN
Solar/Wind Helper
0.35
3146376EDENTON
Solar/Wind Helper
0.24
3151041BRUNSWICKG3
50/50
8.505
972187AH1-678 GEN
50/50
19.517
315242AE2-183_GT2
50/50
10.667
315241AE2-183_GT1
50/50
10.602
972185AH1-677 GEN
50/50
38.457
970533AG2-339 GEN
50/50
57.391
970531AG2-338 GEN
50/50
22.956
3152661PLYWOOD A
50/50
0.751
970535AG2-341 GEN
50/50
5.149
3144293JTRSVLE
50/50
0.914
3144293JTRSVLE
50/50
0.769
970933AG2-581 GEN
Solar/Wind Harmer
51.542
970099AG2-077 GEN
Solar/Wind Harmer
57.884
971741AH1-377 GEN
Solar/Wind Harmer
38.437
970301AG2-198 GEN
Solar/Wind Harmer
15.165
3146843MT LREL
Solar/Wind Harmer
0.321
3146843MT LREL
Solar/Wind Harmer
0.321
964791AG1-342 GEN
Solar/Wind Harmer
6.159
962561AG1-105 GEN
Solar/Wind Harmer
15.15
316222AC1-221 GEN
Solar/Wind Harmer
1.267
939181AE1-148 GEN
Solar/Wind Harmer
13.97
313527AB2-043 GEN
Solar/Wind Harmer
0.004
970323AG2-213 GEN
Solar/Wind Harmer
11.867
971775AH1-396 GEN
Solar/Wind Harmer
0.445
316034AC1-036 C
Solar/Wind Harmer
0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.246
963191AG1-168 GEN
Solar/Wind Harmer
1.082
3147133PAMPLIN
Solar/Wind Harmer
0.268
3147133PAMPLIN
Solar/Wind Harmer
0.214
942751AE2-291 GEN
Solar/Wind Harmer
12.744
270013AE1-250 PV
Solar/Wind Harmer
0.005
3146776BUCKING
Solar/Wind Harmer
0.64
3146776BUCKING
Solar/Wind Harmer
0.052
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.002
942671AE2-283 GEN
Solar/Wind Harmer
3.595
316263AC1-034 GEN
Solar/Wind Harmer
4.676
961601AG1-000A GEN
Solar/Wind Harmer
2.136
316036AC1-147 C
Solar/Wind Helper
0.621
3142956BIRDNECK
Solar/Wind Helper
0.272
316316AC1-027 C
Solar/Wind Helper
0.638
316185AD1-033 GEN
Solar/Wind Helper
1.893
3145506HICKORY
Solar/Wind Helper
1.587
3145506HICKORY
Solar/Wind Helper
0.952
3145506HICKORY
Solar/Wind Helper
0.238
316236AE1-162_GEN
Solar/Wind Helper
0.529
316339AD2-160 GEN
Solar/Wind Helper
1.472
316018AA1-139 ULT2
Solar/Wind Helper
1.65
316017AA1-139 ULT1
Solar/Wind Helper
1.754
3137176SLIGO L2192
Solar/Wind Helper
1.508
3130086AYDLETT
Solar/Wind Helper
1.498
316033AB2-134 GEN
Solar/Wind Helper
1.287
315697AD1-025 GEN
Solar/Wind Helper
4.277
316240AF1-291 C
Solar/Wind Helper
0.501
3146386ELIZ CT
Solar/Wind Helper
0.35
3142946ENON
Solar/Wind Helper
0.034
316487AF1-042 GEN
Solar/Wind Helper
0.339
3144356SAPONY
Solar/Wind Helper
0.597
316075AC2-137 C
Solar/Wind Helper
0.502
316077AC2-138 C
Solar/Wind Helper
0.305
316431W1029_GEN1
Solar/Wind Helper
1.295
316433W1029_GEN2
Solar/Wind Helper
1.295
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3143526WINTERP
Solar/Wind Helper
1.596
966871AG1-558 GEN
Solar/Wind Helper
0.403
3146626S HERTFORD
Solar/Wind Helper
0.296
3146626S HERTFORD
Solar/Wind Helper
0.296
316468AD1-105 GEN
Solar/Wind Helper
1.402
315742AE1-103 GEN
Solar/Wind Helper
0.368
LAGNLTFEXP_LAGN->PJM
CLTF
15.403
CBM South 2LTFEXP_CBM-S2->PJM
CBM
46.288
TVALTFEXP_TVA->PJM
CLTF
7.684
CPLELTFEXP_CPLE->PJM
CLTF
20.639
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.343
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.697
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.447
MECLTFEXP_MEC->PJM
CLTF
7.78
SIGELTFEXP_SIGE->PJM
CLTF
0.233
NYPJM->LTFIMP_NY
CLTF
2.484
LGEELTFEXP_LGEE->PJM
CLTF
2.833
WECLTFEXP_WEC->PJM
CLTF
1.482
AG2-052LTFEXP_AG2-052->PJM
LTF
0.08
AH1-155LTFEXP_AH1-155->PJM
LTF
0.12

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 585_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:133.78 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5445.28
MW Contribution:25.83
Bus #Bus NameTypeMW Contribution
963041AG1-153 GEN
50/50
17.22
315244AE2-183_ST
50/50
18.443
3151541CLOVER2
50/50
10.593
3151611KERR 4
50/50
0.604
3151621KERR 5
50/50
0.604
3151631KERR 6
50/50
0.604
3151641KERR 7
50/50
0.604
971967AH1-528 GEN
Solar/Wind Harmer
109.53
970673AG2-436 GEN
Solar/Wind Harmer
137.75
970673AG2-436 GEN
Solar/Wind Harmer
91.833
970085AG2-068 GEN
Solar/Wind Harmer
32.15
970581AG2-369 GEN
Solar/Wind Harmer
27.649
3147173SINAI
Solar/Wind Harmer
0.345
3147243WELCO
Solar/Wind Harmer
0.216
316118AC1-105 GEN
Solar/Wind Harmer
0.86
970865AG2-541 GEN
Solar/Wind Harmer
10.119
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
4.678
3144303KENBRDG
Solar/Wind Harmer
0.222
970683AG2-441 GEN
Solar/Wind Harmer
18.278
970681AG2-440 GEN
Solar/Wind Harmer
14.623
946301AF1-294 GEN
Solar/Wind Harmer
5.338
961791AG1-021 GEN
Solar/Wind Harmer
2.597
315657AE1-056 GEN
Solar/Wind Harmer
9.239
316123AC1-075 GEN
Solar/Wind Harmer
0.351
970165AG2-112 GEN
Solar/Wind Harmer
2.08
970163AG2-111 GEN
Solar/Wind Harmer
1.985
970831AG2-522 GEN
Solar/Wind Harmer
8.286
970285AG2-188 GEN
Solar/Wind Harmer
14.461
971845AH1-439 GEN
Solar/Wind Harmer
7.612
270069AE2-166 C O1
Solar/Wind Harmer
0.005
3143316POE
Solar/Wind Helper
1.64
319010AE1-072 C
Solar/Wind Helper
4.299
3151051BRUNSWICKS1
50/50
17.651
3151021BRUNSWICKG1
50/50
8.505
971451AH1-221 GEN
50/50
25.831
315243AE2-183_GT3
50/50
10.667
3151531CLOVER1
50/50
10.644
3151601KERR 3
50/50
0.604
3151581KERR 1
50/50
0.216
3144293JTRSVLE
50/50
0.914
971629AH1-314 GEN
50/50
19.06
3151561HALLBR1
50/50
0.404
970919AG2-571 GEN
Solar/Wind Harmer
21.586
970087AG2-069 GEN
Solar/Wind Harmer
48.225
957481AF2-042 GEN
Solar/Wind Harmer
144.711
315693AD1-088 GEN
Solar/Wind Harmer
23.762
962491AG1-098 GEN
Solar/Wind Harmer
27.839
315687AD1-152 GEN
Solar/Wind Harmer
0.015
316003AC1-222 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.882
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970685AG2-442 GEN
Solar/Wind Harmer
20.472
963171AG1-166 GEN
Solar/Wind Harmer
1.443
971563AH1-280 GEN
Solar/Wind Harmer
2.885
3146926FARMVIL
Solar/Wind Harmer
0.151
971065AG2-659 GEN
Solar/Wind Harmer
9.511
316129AC1-054 GEN
Solar/Wind Harmer
0.786
970223AG2-152 GEN
Solar/Wind Harmer
12.908
270016AE1-250 BESS
Solar/Wind Harmer
0.005
3147123OTTER R
Solar/Wind Harmer
0.097
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.064
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
3147312GRETNA
Solar/Wind Harmer
0.115
3146802CHATHAM
Solar/Wind Harmer
0.108
941801AE2-185 GEN
Solar/Wind Harmer
4.622
270030AE2-140 GEN
Solar/Wind Harmer
14.688
3145543BTLEBRO
Solar/Wind Harmer
0.123
3145543BTLEBRO
Solar/Wind Harmer
0.099
316359AB2-059 GEN
Solar/Wind Harmer
0.442
316049AB1-081 GEN
Solar/Wind Harmer
0.704
3142053HEARTS
Solar/Wind Harmer
0.217
316294AC1-161 GEN
Solar/Wind Helper
8.153
316375AC2-012 GEN
Solar/Wind Helper
1.068
3145336SMITFLD
Solar/Wind Helper
1.575
316388AE2-253 GEN
Solar/Wind Helper
1.472
3146456SLIGO L269
Solar/Wind Helper
0.379
316381AD1-082 GEN
Solar/Wind Helper
1.955
316072AD1-144
Solar/Wind Helper
0.428
316246AF1-032 C
Solar/Wind Helper
0.424
316159AE1-175 C
Solar/Wind Helper
0.562
316458AB2-190 GEN2
Solar/Wind Helper
2.107
3141766HARMONY
Solar/Wind Helper
0.069
3142433PROV 92
Solar/Wind Helper
1.376
3138133OCRAN
Solar/Wind Helper
0.206
3142543TWELFTH
Solar/Wind Helper
0.032
964211AG1-282 GEN
Solar/Wind Helper
0.439
3141726DUNNSVL
Solar/Wind Helper
1.304
316337AD2-073 GEN
Solar/Wind Helper
0.478
3142416OLDCHRC
Solar/Wind Helper
0.816
3142416OLDCHRC
Solar/Wind Helper
0.312
3146516WINFALL
Solar/Wind Helper
1.016
3146516WINFALL
Solar/Wind Helper
0.314
3143526WINTERP
Solar/Wind Helper
1.596
3143226MDLTHAN
Solar/Wind Helper
0.3
315800Z1-036_GEN1
Solar/Wind Helper
1.497
3130156CHOWAN
Solar/Wind Helper
0.241
3151031BRUNSWICKG2
50/50
8.505
970413AG2-270 GEN
50/50
46.449
3151591KERR 2
50/50
0.604
3144293JTRSVLE
50/50
0.914
970917AG2-570 GEN
Solar/Wind Harmer
53.965
316478AD1-087 GEN
Solar/Wind Harmer
1.733
316486AD2-202 GEN
Solar/Wind Harmer
0.509
970909AG2-566 GEN
Solar/Wind Harmer
3.791
316248AF1-058 C
Solar/Wind Harmer
0.003
960061AF2-297 GEN
Solar/Wind Harmer
14.727
971683AH1-343 GEN
Solar/Wind Harmer
11.379
316283AC2-100 C
Solar/Wind Harmer
0.592
316131AB2-060 GEN
Solar/Wind Harmer
0.901
964241AG1-285 GEN
Solar/Wind Harmer
18.92
315785AD2-033 C
Solar/Wind Harmer
2.274
970257AG2-171 GEN
Solar/Wind Harmer
8.9
959311AF2-222 GEN
Solar/Wind Harmer
24.62
963181AG1-167 GEN
Solar/Wind Harmer
1.082
3147133PAMPLIN
Solar/Wind Harmer
0.841
971193AH1-056 GEN
Solar/Wind Harmer
16.311
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
3146926FARMVIL
Solar/Wind Harmer
0.151
3146776BUCKING
Solar/Wind Harmer
0.058
270018AE2-047 C O1
Solar/Wind Harmer
0.003
270197AD1-017 GEN1
Solar/Wind Harmer
1.012
3147312GRETNA
Solar/Wind Harmer
0.029
941821AE2-187 GEN
Solar/Wind Harmer
4.622
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
270336AE1-100 GEN
Solar/Wind Harmer
0.004
3145543BTLEBRO
Solar/Wind Harmer
0.123
3145543BTLEBRO
Solar/Wind Harmer
0.123
971623AH1-311 GEN
Solar/Wind Harmer
0.246
961601AG1-000A GEN
Solar/Wind Harmer
8.544
315773AC2-141 GEN
Solar/Wind Helper
9.595
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.061
3145336SMITFLD
Solar/Wind Helper
0.157
315839AE2-212 C
Solar/Wind Helper
0.523
3146456SLIGO L269
Solar/Wind Helper
0.379
316382AG1-145 C
Solar/Wind Helper
0.498
316320Y1-086
Solar/Wind Helper
0.156
316156AD2-030 GEN
Solar/Wind Helper
0.525
316280AD1-041 GEN
Solar/Wind Helper
1.166
3142946ENON
Solar/Wind Helper
0.114
316484AD2-074 GEN
Solar/Wind Helper
0.648
316404AE1-155 C
Solar/Wind Helper
2.8
316435W1029_GEN3
Solar/Wind Helper
1.295
3146516WINFALL
Solar/Wind Helper
0.314
3141906WESTMOR
Solar/Wind Helper
0.122
316473AC1-191 GEN
Solar/Wind Helper
1.829
3146626S HERTFORD
Solar/Wind Helper
0.296
3145273HOLLAND
Solar/Wind Helper
0.201
966881AG1-559 GEN
Solar/Wind Helper
0.35
3146376EDENTON
Solar/Wind Helper
0.24
316369SG1_INVT
Solar/Wind Helper
1.8
316305AF2-043 C
Solar/Wind Helper
0.499
316132AB2-190 GEN1
Solar/Wind Helper
2.107
957831AF2-077 GEN
Solar/Wind Helper
0.495
316349AD2-085 GEN
Solar/Wind Helper
1.649
313526AB2-022
Solar/Wind Helper
0.533
957601AF2-054 GEN
Solar/Wind Helper
0.467
3141873WAN 176
Solar/Wind Helper
0.07
315662AE1-191 GEN
Solar/Wind Helper
1.865
315666AE1-190 GEN
Solar/Wind Helper
0.466
316059AD1-063 C
Solar/Wind Helper
0.348
3141913WHIT STONE
Solar/Wind Helper
0.345
3138133OCRAN
Solar/Wind Helper
0.103
3143873LANEXA
Solar/Wind Helper
0.206
3141783LANCAST
Solar/Wind Helper
0.205
3141783LANCAST
Solar/Wind Helper
0.137
3146486SUNBURY
Solar/Wind Helper
0.341
3146486SUNBURY
Solar/Wind Helper
0.341
316321Z2-027
Solar/Wind Helper
0.514
3145176PASQUOTANK
Solar/Wind Helper
0.209
316315AB2-025 C
Solar/Wind Helper
0.507
3141813NORNECK
Solar/Wind Helper
0.325
316312AB1-027
Solar/Wind Helper
0.597
316233AE1-074 FULL
Solar/Wind Helper
0.469
316223AC1-118
Solar/Wind Helper
0.466
315611Z1-036_GEN2
Solar/Wind Helper
1.497
3130156CHOWAN
Solar/Wind Helper
0.241
3130156CHOWAN
Solar/Wind Helper
0.241
3151041BRUNSWICKG3
50/50
8.505
972187AH1-678 GEN
50/50
19.517
315242AE2-183_GT2
50/50
10.667
315241AE2-183_GT1
50/50
10.602
972185AH1-677 GEN
50/50
38.457
3152661PLYWOOD A
50/50
0.751
970535AG2-341 GEN
50/50
5.149
3144293JTRSVLE
50/50
0.914
3144293JTRSVLE
50/50
0.769
970933AG2-581 GEN
Solar/Wind Harmer
51.542
970099AG2-077 GEN
Solar/Wind Harmer
57.884
971741AH1-377 GEN
Solar/Wind Harmer
38.437
970301AG2-198 GEN
Solar/Wind Harmer
15.165
3146843MT LREL
Solar/Wind Harmer
0.321
3146843MT LREL
Solar/Wind Harmer
0.321
964791AG1-342 GEN
Solar/Wind Harmer
6.159
962561AG1-105 GEN
Solar/Wind Harmer
15.15
316222AC1-221 GEN
Solar/Wind Harmer
1.267
939181AE1-148 GEN
Solar/Wind Harmer
13.97
313527AB2-043 GEN
Solar/Wind Harmer
0.004
970323AG2-213 GEN
Solar/Wind Harmer
11.867
971775AH1-396 GEN
Solar/Wind Harmer
0.445
316034AC1-036 C
Solar/Wind Harmer
0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.246
963191AG1-168 GEN
Solar/Wind Harmer
1.082
3147133PAMPLIN
Solar/Wind Harmer
0.268
3147133PAMPLIN
Solar/Wind Harmer
0.214
942751AE2-291 GEN
Solar/Wind Harmer
12.744
270013AE1-250 PV
Solar/Wind Harmer
0.005
3146776BUCKING
Solar/Wind Harmer
0.64
3146776BUCKING
Solar/Wind Harmer
0.052
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.002
942671AE2-283 GEN
Solar/Wind Harmer
3.595
316263AC1-034 GEN
Solar/Wind Harmer
4.676
961601AG1-000A GEN
Solar/Wind Harmer
2.136
316036AC1-147 C
Solar/Wind Helper
0.621
3142956BIRDNECK
Solar/Wind Helper
0.272
316316AC1-027 C
Solar/Wind Helper
0.638
316185AD1-033 GEN
Solar/Wind Helper
1.893
3145506HICKORY
Solar/Wind Helper
1.587
3145506HICKORY
Solar/Wind Helper
0.952
3145506HICKORY
Solar/Wind Helper
0.238
316236AE1-162_GEN
Solar/Wind Helper
0.529
316339AD2-160 GEN
Solar/Wind Helper
1.472
316018AA1-139 ULT2
Solar/Wind Helper
1.65
316017AA1-139 ULT1
Solar/Wind Helper
1.754
3137176SLIGO L2192
Solar/Wind Helper
1.508
3130086AYDLETT
Solar/Wind Helper
1.498
316033AB2-134 GEN
Solar/Wind Helper
1.287
315697AD1-025 GEN
Solar/Wind Helper
4.277
316240AF1-291 C
Solar/Wind Helper
0.501
3146386ELIZ CT
Solar/Wind Helper
0.35
3142946ENON
Solar/Wind Helper
0.034
316487AF1-042 GEN
Solar/Wind Helper
0.339
3144356SAPONY
Solar/Wind Helper
0.597
316075AC2-137 C
Solar/Wind Helper
0.502
316077AC2-138 C
Solar/Wind Helper
0.305
316431W1029_GEN1
Solar/Wind Helper
1.295
316433W1029_GEN2
Solar/Wind Helper
1.295
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3143526WINTERP
Solar/Wind Helper
1.596
966871AG1-558 GEN
Solar/Wind Helper
0.403
3146626S HERTFORD
Solar/Wind Helper
0.296
3146626S HERTFORD
Solar/Wind Helper
0.296
316468AD1-105 GEN
Solar/Wind Helper
1.402
315742AE1-103 GEN
Solar/Wind Helper
0.368
LAGNLTFEXP_LAGN->PJM
CLTF
15.403
CBM South 2LTFEXP_CBM-S2->PJM
CBM
46.288
TVALTFEXP_TVA->PJM
CLTF
7.684
CPLELTFEXP_CPLE->PJM
CLTF
20.639
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.343
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.697
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.447
MECLTFEXP_MEC->PJM
CLTF
7.78
SIGELTFEXP_SIGE->PJM
CLTF
0.233
NYPJM->LTFIMP_NY
CLTF
2.484
LGEELTFEXP_LGEE->PJM
CLTF
2.833
WECLTFEXP_WEC->PJM
CLTF
1.482
AG2-052LTFEXP_AG2-052->PJM
LTF
0.08
AH1-155LTFEXP_AH1-155->PJM
LTF
0.12

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-2: 58572_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 58572_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.04 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:6196.95
MW Contribution:25.83
Bus #Bus NameTypeMW Contribution
963041AG1-153 GEN
50/50
17.22
315244AE2-183_ST
50/50
18.443
3151541CLOVER2
50/50
10.593
3151611KERR 4
50/50
0.604
3151621KERR 5
50/50
0.604
3151631KERR 6
50/50
0.604
3151641KERR 7
50/50
0.604
971967AH1-528 GEN
Solar/Wind Harmer
144.6
970673AG2-436 GEN
Solar/Wind Harmer
152.413
970673AG2-436 GEN
Solar/Wind Harmer
77.171
941031AE2-094 GEN
Solar/Wind Harmer
136.017
3151031BRUNSWICKG2
50/50
8.505
970413AG2-270 GEN
50/50
46.449
3151591KERR 2
50/50
0.604
3144293JTRSVLE
50/50
0.914
970917AG2-570 GEN
Solar/Wind Harmer
170.53
316478AD1-087 GEN
Solar/Wind Harmer
4.831
316486AD2-202 GEN
Solar/Wind Harmer
1.415
970909AG2-566 GEN
Solar/Wind Harmer
3.791
316248AF1-058 C
Solar/Wind Harmer
1.169
960061AF2-297 GEN
Solar/Wind Harmer
19.391
971683AH1-343 GEN
Solar/Wind Harmer
14.982
316283AC2-100 C
Solar/Wind Harmer
3.205
316131AB2-060 GEN
Solar/Wind Harmer
3.471
964241AG1-285 GEN
Solar/Wind Harmer
24.911
315785AD2-033 C
Solar/Wind Harmer
7.122
970257AG2-171 GEN
Solar/Wind Harmer
11.718
959311AF2-222 GEN
Solar/Wind Harmer
32.481
963181AG1-167 GEN
Solar/Wind Harmer
2.849
3147133PAMPLIN
Solar/Wind Harmer
-0.094
971193AH1-056 GEN
Solar/Wind Harmer
18.811
942461AE2-259 GEN
Solar/Wind Harmer
4.399
3146926FARMVIL
Solar/Wind Harmer
-0.017
3146776BUCKING
Solar/Wind Harmer
-0.006
270018AE2-047 C O1
Solar/Wind Harmer
1.466
270197AD1-017 GEN1
Solar/Wind Harmer
1.802
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
6.086
943811AF1-049 GEN
Solar/Wind Harmer
4.09
270336AE1-100 GEN
Solar/Wind Harmer
1.669
3145543BTLEBRO
Solar/Wind Harmer
-0.014
3145543BTLEBRO
Solar/Wind Harmer
-0.014
961601AG1-000A GEN
Solar/Wind Harmer
5.373
315773AC2-141 GEN
Solar/Wind Helper
9.595
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.061
3145336SMITFLD
Solar/Wind Helper
0.157
315839AE2-212 C
Solar/Wind Helper
0.523
3146456SLIGO L269
Solar/Wind Helper
0.379
316382AG1-145 C
Solar/Wind Helper
0.498
316320Y1-086
Solar/Wind Helper
0.156
316156AD2-030 GEN
Solar/Wind Helper
0.525
316280AD1-041 GEN
Solar/Wind Helper
1.166
3142946ENON
Solar/Wind Helper
0.114
316484AD2-074 GEN
Solar/Wind Helper
0.648
316404AE1-155 C
Solar/Wind Helper
2.8
316435W1029_GEN3
Solar/Wind Helper
1.295
3146516WINFALL
Solar/Wind Helper
0.314
3141906WESTMOR
Solar/Wind Helper
0.122
316473AC1-191 GEN
Solar/Wind Helper
1.829
3146626S HERTFORD
Solar/Wind Helper
0.296
3145273HOLLAND
Solar/Wind Helper
0.201
966881AG1-559 GEN
Solar/Wind Helper
0.35
3146376EDENTON
Solar/Wind Helper
0.24
944011AF1-069 GEN
Solar/Wind Harmer
42.619
970085AG2-068 GEN
Solar/Wind Harmer
42.331
970581AG2-369 GEN
Solar/Wind Harmer
36.404
3147173SINAI
Solar/Wind Harmer
-0.039
3147243WELCO
Solar/Wind Harmer
-0.024
316118AC1-105 GEN
Solar/Wind Harmer
2.575
970865AG2-541 GEN
Solar/Wind Harmer
13.323
316239AB2-077_GEN
Solar/Wind Harmer
0.978
316238AB2-078_GEN
Solar/Wind Harmer
0.978
971443AH1-215 GEN
Solar/Wind Harmer
6.159
3144303KENBRDG
Solar/Wind Harmer
-0.025
970683AG2-441 GEN
Solar/Wind Harmer
24.066
970681AG2-440 GEN
Solar/Wind Harmer
19.253
946301AF1-294 GEN
Solar/Wind Harmer
7.788
961791AG1-021 GEN
Solar/Wind Harmer
3.799
315657AE1-056 GEN
Solar/Wind Harmer
11.287
316123AC1-075 GEN
Solar/Wind Harmer
3.111
970165AG2-112 GEN
Solar/Wind Harmer
2.739
970163AG2-111 GEN
Solar/Wind Harmer
2.613
270455AD2-022 GEN
Solar/Wind Harmer
5.008
270457AD2-023 GEN
Solar/Wind Harmer
2.539
970831AG2-522 GEN
Solar/Wind Harmer
10.909
970285AG2-188 GEN
Solar/Wind Harmer
17.971
971845AH1-439 GEN
Solar/Wind Harmer
10.023
270069AE2-166 C O1
Solar/Wind Harmer
2.578
3143316POE
Solar/Wind Helper
1.64
319010AE1-072 C
Solar/Wind Helper
4.299
316369SG1_INVT
Solar/Wind Helper
1.8
316305AF2-043 C
Solar/Wind Helper
0.499
316132AB2-190 GEN1
Solar/Wind Helper
2.107
957831AF2-077 GEN
Solar/Wind Helper
0.495
316349AD2-085 GEN
Solar/Wind Helper
1.649
313526AB2-022
Solar/Wind Helper
0.533
957601AF2-054 GEN
Solar/Wind Helper
0.467
3141873WAN 176
Solar/Wind Helper
0.07
315662AE1-191 GEN
Solar/Wind Helper
1.865
315666AE1-190 GEN
Solar/Wind Helper
0.466
316059AD1-063 C
Solar/Wind Helper
0.348
3141913WHIT STONE
Solar/Wind Helper
0.345
3138133OCRAN
Solar/Wind Helper
0.103
3143873LANEXA
Solar/Wind Helper
0.206
3141783LANCAST
Solar/Wind Helper
0.205
3141783LANCAST
Solar/Wind Helper
0.137
3146486SUNBURY
Solar/Wind Helper
0.341
3146486SUNBURY
Solar/Wind Helper
0.341
316321Z2-027
Solar/Wind Helper
0.514
3145176PASQUOTANK
Solar/Wind Helper
0.209
316315AB2-025 C
Solar/Wind Helper
0.507
3141813NORNECK
Solar/Wind Helper
0.325
316312AB1-027
Solar/Wind Helper
0.597
316233AE1-074 FULL
Solar/Wind Helper
0.469
316223AC1-118
Solar/Wind Helper
0.466
315611Z1-036_GEN2
Solar/Wind Helper
1.497
3130156CHOWAN
Solar/Wind Helper
0.241
3130156CHOWAN
Solar/Wind Helper
0.241
3151051BRUNSWICKS1
50/50
17.651
3151021BRUNSWICKG1
50/50
8.505
971451AH1-221 GEN
50/50
25.831
315243AE2-183_GT3
50/50
10.667
3151531CLOVER1
50/50
10.644
3151601KERR 3
50/50
0.604
3151581KERR 1
50/50
0.216
3144293JTRSVLE
50/50
0.914
971629AH1-314 GEN
50/50
19.06
3151561HALLBR1
50/50
0.404
970919AG2-571 GEN
Solar/Wind Harmer
21.586
970087AG2-069 GEN
Solar/Wind Harmer
63.496
957481AF2-042 GEN
Solar/Wind Harmer
190.536
315693AD1-088 GEN
Solar/Wind Harmer
27.811
962491AG1-098 GEN
Solar/Wind Harmer
36.654
315687AD1-152 GEN
Solar/Wind Harmer
6.022
316003AC1-222 GEN
Solar/Wind Harmer
3.575
970401AG2-262 GEN
Solar/Wind Harmer
2.352
316237AB2-079_GEN
Solar/Wind Harmer
0.978
970685AG2-442 GEN
Solar/Wind Harmer
26.954
963171AG1-166 GEN
Solar/Wind Harmer
3.799
971563AH1-280 GEN
Solar/Wind Harmer
3.799
3146926FARMVIL
Solar/Wind Harmer
-0.017
971065AG2-659 GEN
Solar/Wind Harmer
12.523
316129AC1-054 GEN
Solar/Wind Harmer
2.059
970223AG2-152 GEN
Solar/Wind Harmer
18.408
270016AE1-250 BESS
Solar/Wind Harmer
3.042
3147123OTTER R
Solar/Wind Harmer
-0.011
316322AB2-045
Solar/Wind Harmer
0.605
3146776BUCKING
Solar/Wind Harmer
-0.007
270574AD1-017 GEN2
Solar/Wind Harmer
5.998
3147312GRETNA
Solar/Wind Harmer
-0.013
3146802CHATHAM
Solar/Wind Harmer
-0.012
941801AE2-185 GEN
Solar/Wind Harmer
6.086
270030AE2-140 GEN
Solar/Wind Harmer
21.053
3145543BTLEBRO
Solar/Wind Harmer
-0.014
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.864
316049AB1-081 GEN
Solar/Wind Harmer
1.492
3142053HEARTS
Solar/Wind Harmer
0.163
316294AC1-161 GEN
Solar/Wind Helper
8.153
316375AC2-012 GEN
Solar/Wind Helper
1.068
3145336SMITFLD
Solar/Wind Helper
1.575
316388AE2-253 GEN
Solar/Wind Helper
1.472
3146456SLIGO L269
Solar/Wind Helper
0.379
316381AD1-082 GEN
Solar/Wind Helper
1.955
316072AD1-144
Solar/Wind Helper
0.428
316246AF1-032 C
Solar/Wind Helper
0.424
316159AE1-175 C
Solar/Wind Helper
0.562
316458AB2-190 GEN2
Solar/Wind Helper
2.107
3141766HARMONY
Solar/Wind Helper
0.069
3142433PROV 92
Solar/Wind Helper
1.376
3138133OCRAN
Solar/Wind Helper
0.206
3142543TWELFTH
Solar/Wind Helper
0.032
964211AG1-282 GEN
Solar/Wind Helper
0.439
3141726DUNNSVL
Solar/Wind Helper
1.304
316337AD2-073 GEN
Solar/Wind Helper
0.478
3142416OLDCHRC
Solar/Wind Helper
0.816
3142416OLDCHRC
Solar/Wind Helper
0.312
3146516WINFALL
Solar/Wind Helper
1.016
3146516WINFALL
Solar/Wind Helper
0.314
3143526WINTERP
Solar/Wind Helper
1.596
3143226MDLTHAN
Solar/Wind Helper
0.3
315800Z1-036_GEN1
Solar/Wind Helper
1.497
3130156CHOWAN
Solar/Wind Helper
0.241
3151041BRUNSWICKG3
50/50
8.505
972187AH1-678 GEN
50/50
19.517
315242AE2-183_GT2
50/50
10.667
315241AE2-183_GT1
50/50
10.602
972185AH1-677 GEN
50/50
38.457
970533AG2-339 GEN
50/50
57.391
970531AG2-338 GEN
50/50
22.956
3152661PLYWOOD A
50/50
0.751
970535AG2-341 GEN
50/50
5.149
3144293JTRSVLE
50/50
0.914
3144293JTRSVLE
50/50
0.769
970933AG2-581 GEN
Solar/Wind Harmer
67.863
970099AG2-077 GEN
Solar/Wind Harmer
76.214
971741AH1-377 GEN
Solar/Wind Harmer
50.609
970301AG2-198 GEN
Solar/Wind Harmer
19.968
3146843MT LREL
Solar/Wind Harmer
-0.036
3146843MT LREL
Solar/Wind Harmer
-0.036
964791AG1-342 GEN
Solar/Wind Harmer
7.699
962561AG1-105 GEN
Solar/Wind Harmer
19.948
316222AC1-221 GEN
Solar/Wind Harmer
3.472
939181AE1-148 GEN
Solar/Wind Harmer
18.394
313527AB2-043 GEN
Solar/Wind Harmer
5.237
970323AG2-213 GEN
Solar/Wind Harmer
15.625
971775AH1-396 GEN
Solar/Wind Harmer
2.225
316034AC1-036 C
Solar/Wind Harmer
0.579
958211AF2-115 GEN
Solar/Wind Harmer
4.748
963191AG1-168 GEN
Solar/Wind Harmer
2.849
3147133PAMPLIN
Solar/Wind Harmer
-0.03
3147133PAMPLIN
Solar/Wind Harmer
-0.024
942751AE2-291 GEN
Solar/Wind Harmer
16.78
270013AE1-250 PV
Solar/Wind Harmer
3.042
3146776BUCKING
Solar/Wind Harmer
-0.072
3146776BUCKING
Solar/Wind Harmer
-0.006
316217AC1-145 GEN
Solar/Wind Harmer
2.634
316197AC1-042 GEN
Solar/Wind Harmer
1.997
942671AE2-283 GEN
Solar/Wind Harmer
5.376
316263AC1-034 GEN
Solar/Wind Harmer
6.481
961601AG1-000A GEN
Solar/Wind Harmer
5.306
316036AC1-147 C
Solar/Wind Helper
0.621
3142956BIRDNECK
Solar/Wind Helper
0.272
316316AC1-027 C
Solar/Wind Helper
0.638
316185AD1-033 GEN
Solar/Wind Helper
1.893
3145506HICKORY
Solar/Wind Helper
1.587
3145506HICKORY
Solar/Wind Helper
0.952
3145506HICKORY
Solar/Wind Helper
0.238
316236AE1-162_GEN
Solar/Wind Helper
0.529
316339AD2-160 GEN
Solar/Wind Helper
1.472
316018AA1-139 ULT2
Solar/Wind Helper
1.65
316017AA1-139 ULT1
Solar/Wind Helper
1.754
3137176SLIGO L2192
Solar/Wind Helper
1.508
3130086AYDLETT
Solar/Wind Helper
1.498
316033AB2-134 GEN
Solar/Wind Helper
1.287
315697AD1-025 GEN
Solar/Wind Helper
4.277
316240AF1-291 C
Solar/Wind Helper
0.501
3146386ELIZ CT
Solar/Wind Helper
0.35
3142946ENON
Solar/Wind Helper
0.034
316487AF1-042 GEN
Solar/Wind Helper
0.339
3144356SAPONY
Solar/Wind Helper
0.597
316075AC2-137 C
Solar/Wind Helper
0.502
316077AC2-138 C
Solar/Wind Helper
0.305
316431W1029_GEN1
Solar/Wind Helper
1.295
316433W1029_GEN2
Solar/Wind Helper
1.295
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3143526WINTERP
Solar/Wind Helper
1.596
966871AG1-558 GEN
Solar/Wind Helper
0.403
3146626S HERTFORD
Solar/Wind Helper
0.296
3146626S HERTFORD
Solar/Wind Helper
0.296
316468AD1-105 GEN
Solar/Wind Helper
1.402
315742AE1-103 GEN
Solar/Wind Helper
0.368
LAGNLTFEXP_LAGN->PJM
CLTF
15.403
CBM South 2LTFEXP_CBM-S2->PJM
CBM
46.288
TVALTFEXP_TVA->PJM
CLTF
7.684
CPLELTFEXP_CPLE->PJM
CLTF
20.639
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.343
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.697
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.447
MECLTFEXP_MEC->PJM
CLTF
7.78
SIGELTFEXP_SIGE->PJM
CLTF
0.233
NYPJM->LTFIMP_NY
CLTF
2.484
LGEELTFEXP_LGEE->PJM
CLTF
2.833
WECLTFEXP_WEC->PJM
CLTF
1.482
AG2-052LTFEXP_AG2-052->PJM
LTF
0.08
AH1-155LTFEXP_AH1-155->PJM
LTF
0.12

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-5: W72_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: W72_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:123.43 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:6166.56
MW Contribution:25.64
Bus #Bus NameTypeMW Contribution
3151051BRUNSWICKS1
50/50
17.522
3151021BRUNSWICKG1
50/50
8.442
971451AH1-221 GEN
50/50
25.642
315243AE2-183_GT3
50/50
10.589
3151531CLOVER1
50/50
10.578
3151601KERR 3
50/50
0.604
3151581KERR 1
50/50
0.216
3144293JTRSVLE
50/50
0.912
971629AH1-314 GEN
50/50
18.997
3151561HALLBR1
50/50
0.403
970919AG2-571 GEN
Solar/Wind Harmer
21.433
970087AG2-069 GEN
Solar/Wind Harmer
63.047
957481AF2-042 GEN
Solar/Wind Harmer
189.269
315693AD1-088 GEN
Solar/Wind Harmer
27.634
962491AG1-098 GEN
Solar/Wind Harmer
36.422
315687AD1-152 GEN
Solar/Wind Harmer
5.988
316003AC1-222 GEN
Solar/Wind Harmer
3.561
970401AG2-262 GEN
Solar/Wind Harmer
2.348
316237AB2-079_GEN
Solar/Wind Harmer
0.98
970685AG2-442 GEN
Solar/Wind Harmer
26.929
963171AG1-166 GEN
Solar/Wind Harmer
3.793
971563AH1-280 GEN
Solar/Wind Harmer
3.793
3146926FARMVIL
Solar/Wind Harmer
-0.017
971065AG2-659 GEN
Solar/Wind Harmer
12.621
316129AC1-054 GEN
Solar/Wind Harmer
2.079
970223AG2-152 GEN
Solar/Wind Harmer
18.347
270016AE1-250 BESS
Solar/Wind Harmer
3.032
3147123OTTER R
Solar/Wind Harmer
-0.011
316322AB2-045
Solar/Wind Harmer
0.602
3146776BUCKING
Solar/Wind Harmer
-0.007
270574AD1-017 GEN2
Solar/Wind Harmer
5.978
3147312GRETNA
Solar/Wind Harmer
-0.013
3146802CHATHAM
Solar/Wind Harmer
-0.012
941801AE2-185 GEN
Solar/Wind Harmer
6.064
270030AE2-140 GEN
Solar/Wind Harmer
20.984
3145543BTLEBRO
Solar/Wind Harmer
-0.014
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.909
316049AB1-081 GEN
Solar/Wind Harmer
1.528
963041AG1-153 GEN
50/50
17.095
315244AE2-183_ST
50/50
18.308
3151541CLOVER2
50/50
10.527
3151611KERR 4
50/50
0.604
3151621KERR 5
50/50
0.604
3151631KERR 6
50/50
0.604
3151641KERR 7
50/50
0.604
971967AH1-528 GEN
Solar/Wind Harmer
143.519
970673AG2-436 GEN
Solar/Wind Harmer
151.3
970673AG2-436 GEN
Solar/Wind Harmer
76.608
941031AE2-094 GEN
Solar/Wind Harmer
135.024
944011AF1-069 GEN
Solar/Wind Harmer
42.308
970085AG2-068 GEN
Solar/Wind Harmer
42.031
970581AG2-369 GEN
Solar/Wind Harmer
36.147
3147173SINAI
Solar/Wind Harmer
-0.039
3147243WELCO
Solar/Wind Harmer
-0.024
316118AC1-105 GEN
Solar/Wind Harmer
2.567
970865AG2-541 GEN
Solar/Wind Harmer
13.271
316239AB2-077_GEN
Solar/Wind Harmer
0.98
316238AB2-078_GEN
Solar/Wind Harmer
0.98
971443AH1-215 GEN
Solar/Wind Harmer
6.158
3144303KENBRDG
Solar/Wind Harmer
-0.025
970683AG2-441 GEN
Solar/Wind Harmer
24.044
970681AG2-440 GEN
Solar/Wind Harmer
19.235
946301AF1-294 GEN
Solar/Wind Harmer
7.775
961791AG1-021 GEN
Solar/Wind Harmer
3.793
315657AE1-056 GEN
Solar/Wind Harmer
11.263
316123AC1-075 GEN
Solar/Wind Harmer
3.099
970165AG2-112 GEN
Solar/Wind Harmer
2.728
970163AG2-111 GEN
Solar/Wind Harmer
2.603
270455AD2-022 GEN
Solar/Wind Harmer
4.991
270457AD2-023 GEN
Solar/Wind Harmer
2.531
970831AG2-522 GEN
Solar/Wind Harmer
11.041
970285AG2-188 GEN
Solar/Wind Harmer
17.881
971845AH1-439 GEN
Solar/Wind Harmer
9.974
270069AE2-166 C O1
Solar/Wind Harmer
2.569
319010AE1-072 C
Solar/Wind Helper
4.32
3143316POE
Solar/Wind Helper
1.486
316305AF2-043 C
Solar/Wind Helper
0.5
316369SG1_INVT
Solar/Wind Helper
1.758
957831AF2-077 GEN
Solar/Wind Helper
0.492
316132AB2-190 GEN1
Solar/Wind Helper
2.041
316349AD2-085 GEN
Solar/Wind Helper
1.61
313526AB2-022
Solar/Wind Helper
0.535
957601AF2-054 GEN
Solar/Wind Helper
0.462
3141873WAN 176
Solar/Wind Helper
0.069
315662AE1-191 GEN
Solar/Wind Helper
1.844
315666AE1-190 GEN
Solar/Wind Helper
0.461
3146486SUNBURY
Solar/Wind Helper
0.341
3146486SUNBURY
Solar/Wind Helper
0.341
316059AD1-063 C
Solar/Wind Helper
0.344
3141913WHIT STONE
Solar/Wind Helper
0.341
3138133OCRAN
Solar/Wind Helper
0.102
3143873LANEXA
Solar/Wind Helper
0.203
3141783LANCAST
Solar/Wind Helper
0.203
3141783LANCAST
Solar/Wind Helper
0.135
316321Z2-027
Solar/Wind Helper
0.515
3145176PASQUOTANK
Solar/Wind Helper
0.209
3141813NORNECK
Solar/Wind Helper
0.321
316312AB1-027
Solar/Wind Helper
0.585
316223AC1-118
Solar/Wind Helper
0.461
316233AE1-074 FULL
Solar/Wind Helper
0.462
316315AB2-025 C
Solar/Wind Helper
0.44
315611Z1-036_GEN2
Solar/Wind Helper
1.494
3130156CHOWAN
Solar/Wind Helper
0.24
3130156CHOWAN
Solar/Wind Helper
0.24
3151041BRUNSWICKG3
50/50
8.442
972187AH1-678 GEN
50/50
19.374
315242AE2-183_GT2
50/50
10.589
315241AE2-183_GT1
50/50
10.524
972185AH1-677 GEN
50/50
38.176
970533AG2-339 GEN
50/50
56.972
970531AG2-338 GEN
50/50
22.789
3152661PLYWOOD A
50/50
0.749
970535AG2-341 GEN
50/50
5.154
3144293JTRSVLE
50/50
0.912
3144293JTRSVLE
50/50
0.768
970933AG2-581 GEN
Solar/Wind Harmer
67.369
970099AG2-077 GEN
Solar/Wind Harmer
75.708
971741AH1-377 GEN
Solar/Wind Harmer
50.305
970301AG2-198 GEN
Solar/Wind Harmer
19.85
3146843MT LREL
Solar/Wind Harmer
-0.036
3146843MT LREL
Solar/Wind Harmer
-0.036
964791AG1-342 GEN
Solar/Wind Harmer
7.683
962561AG1-105 GEN
Solar/Wind Harmer
19.916
316222AC1-221 GEN
Solar/Wind Harmer
3.458
939181AE1-148 GEN
Solar/Wind Harmer
18.413
313527AB2-043 GEN
Solar/Wind Harmer
5.244
970323AG2-213 GEN
Solar/Wind Harmer
15.621
971775AH1-396 GEN
Solar/Wind Harmer
2.225
316034AC1-036 C
Solar/Wind Harmer
0.579
958211AF2-115 GEN
Solar/Wind Harmer
4.741
963191AG1-168 GEN
Solar/Wind Harmer
2.845
3147133PAMPLIN
Solar/Wind Harmer
-0.03
3147133PAMPLIN
Solar/Wind Harmer
-0.024
942751AE2-291 GEN
Solar/Wind Harmer
16.715
270013AE1-250 PV
Solar/Wind Harmer
3.032
3146776BUCKING
Solar/Wind Harmer
-0.071
3146776BUCKING
Solar/Wind Harmer
-0.006
316217AC1-145 GEN
Solar/Wind Harmer
2.625
316197AC1-042 GEN
Solar/Wind Harmer
1.99
942671AE2-283 GEN
Solar/Wind Harmer
5.357
316263AC1-034 GEN
Solar/Wind Harmer
6.638
961601AG1-000A GEN
Solar/Wind Harmer
5.443
316036AC1-147 C
Solar/Wind Helper
0.624
3142956BIRDNECK
Solar/Wind Helper
0.274
316316AC1-027 C
Solar/Wind Helper
0.642
316185AD1-033 GEN
Solar/Wind Helper
1.905
3145506HICKORY
Solar/Wind Helper
1.596
3145506HICKORY
Solar/Wind Helper
0.958
3145506HICKORY
Solar/Wind Helper
0.239
316236AE1-162_GEN
Solar/Wind Helper
0.527
316339AD2-160 GEN
Solar/Wind Helper
1.48
316018AA1-139 ULT2
Solar/Wind Helper
1.659
316017AA1-139 ULT1
Solar/Wind Helper
1.763
3137176SLIGO L2192
Solar/Wind Helper
1.516
3130086AYDLETT
Solar/Wind Helper
1.505
316033AB2-134 GEN
Solar/Wind Helper
1.257
315697AD1-025 GEN
Solar/Wind Helper
4.177
3146386ELIZ CT
Solar/Wind Helper
0.351
316240AF1-291 C
Solar/Wind Helper
0.468
3142946ENON
Solar/Wind Helper
0.033
316487AF1-042 GEN
Solar/Wind Helper
0.335
316075AC2-137 C
Solar/Wind Helper
0.492
316077AC2-138 C
Solar/Wind Helper
0.302
316431W1029_GEN1
Solar/Wind Helper
1.297
316433W1029_GEN2
Solar/Wind Helper
1.297
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3143526WINTERP
Solar/Wind Helper
1.573
3146626S HERTFORD
Solar/Wind Helper
0.296
3146626S HERTFORD
Solar/Wind Helper
0.296
966871AG1-558 GEN
Solar/Wind Helper
0.394
3144356SAPONY
Solar/Wind Helper
0.518
316468AD1-105 GEN
Solar/Wind Helper
1.373
315742AE1-103 GEN
Solar/Wind Helper
0.362
3142053HEARTS
Solar/Wind Harmer
0.166
316294AC1-161 GEN
Solar/Wind Helper
8.246
316375AC2-012 GEN
Solar/Wind Helper
1.074
3145336SMITFLD
Solar/Wind Helper
1.568
316388AE2-253 GEN
Solar/Wind Helper
1.48
3146456SLIGO L269
Solar/Wind Helper
0.38
316072AD1-144
Solar/Wind Helper
0.428
316246AF1-032 C
Solar/Wind Helper
0.426
316159AE1-175 C
Solar/Wind Helper
0.559
316381AD1-082 GEN
Solar/Wind Helper
1.857
316458AB2-190 GEN2
Solar/Wind Helper
2.041
3141766HARMONY
Solar/Wind Helper
0.068
3138133OCRAN
Solar/Wind Helper
0.204
3142433PROV 92
Solar/Wind Helper
1.345
3142543TWELFTH
Solar/Wind Helper
0.031
964211AG1-282 GEN
Solar/Wind Helper
0.434
3141726DUNNSVL
Solar/Wind Helper
1.289
3146516WINFALL
Solar/Wind Helper
1.017
3146516WINFALL
Solar/Wind Helper
0.314
316337AD2-073 GEN
Solar/Wind Helper
0.473
3142416OLDCHRC
Solar/Wind Helper
0.799
3151031BRUNSWICKG2
50/50
8.442
970413AG2-270 GEN
50/50
46.159
3151591KERR 2
50/50
0.604
3144293JTRSVLE
50/50
0.912
970917AG2-570 GEN
Solar/Wind Harmer
169.32
316478AD1-087 GEN
Solar/Wind Harmer
4.801
316486AD2-202 GEN
Solar/Wind Harmer
1.406
970909AG2-566 GEN
Solar/Wind Harmer
3.769
316248AF1-058 C
Solar/Wind Harmer
1.164
960061AF2-297 GEN
Solar/Wind Harmer
19.314
971683AH1-343 GEN
Solar/Wind Harmer
14.923
316283AC2-100 C
Solar/Wind Harmer
3.192
316131AB2-060 GEN
Solar/Wind Harmer
3.475
964241AG1-285 GEN
Solar/Wind Harmer
24.93
315785AD2-033 C
Solar/Wind Harmer
7.122
970257AG2-171 GEN
Solar/Wind Harmer
11.716
959311AF2-222 GEN
Solar/Wind Harmer
32.468
963181AG1-167 GEN
Solar/Wind Harmer
2.845
3147133PAMPLIN
Solar/Wind Harmer
-0.094
971193AH1-056 GEN
Solar/Wind Harmer
18.772
942461AE2-259 GEN
Solar/Wind Harmer
4.384
3146926FARMVIL
Solar/Wind Harmer
-0.017
3146776BUCKING
Solar/Wind Harmer
-0.006
270018AE2-047 C O1
Solar/Wind Harmer
1.461
270197AD1-017 GEN1
Solar/Wind Harmer
1.796
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
6.064
943811AF1-049 GEN
Solar/Wind Harmer
4.077
270336AE1-100 GEN
Solar/Wind Harmer
1.664
3145543BTLEBRO
Solar/Wind Harmer
-0.014
3145543BTLEBRO
Solar/Wind Harmer
-0.014
961601AG1-000A GEN
Solar/Wind Harmer
5.512
3138543CONSLDL
Solar/Wind Harmer
-0.008
315773AC2-141 GEN
Solar/Wind Helper
9.706
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.061
3145336SMITFLD
Solar/Wind Helper
0.157
3146456SLIGO L269
Solar/Wind Helper
0.38
316382AG1-145 C
Solar/Wind Helper
0.496
315839AE2-212 C
Solar/Wind Helper
0.483
316320Y1-086
Solar/Wind Helper
0.157
316156AD2-030 GEN
Solar/Wind Helper
0.52
316280AD1-041 GEN
Solar/Wind Helper
1.152
3142946ENON
Solar/Wind Helper
0.111
316484AD2-074 GEN
Solar/Wind Helper
0.641
316404AE1-155 C
Solar/Wind Helper
2.769
316435W1029_GEN3
Solar/Wind Helper
1.297
3146516WINFALL
Solar/Wind Helper
0.314
3141906WESTMOR
Solar/Wind Helper
0.121
3146626S HERTFORD
Solar/Wind Helper
0.296
316473AC1-191 GEN
Solar/Wind Helper
1.785
3145273HOLLAND
Solar/Wind Helper
0.198
966881AG1-559 GEN
Solar/Wind Helper
0.346
3146376EDENTON
Solar/Wind Helper
0.239
3142416OLDCHRC
Solar/Wind Helper
0.306
3143526WINTERP
Solar/Wind Helper
1.573
3143226MDLTHAN
Solar/Wind Helper
0.298
315800Z1-036_GEN1
Solar/Wind Helper
1.494
3130156CHOWAN
Solar/Wind Helper
0.24
LAGNLTFEXP_LAGN->PJM
CLTF
15.349
CBM South 2LTFEXP_CBM-S2->PJM
CBM
46.145
TVALTFEXP_TVA->PJM
CLTF
7.657
CPLELTFEXP_CPLE->PJM
CLTF
20.587
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.048
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.486
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.354
MECLTFEXP_MEC->PJM
CLTF
7.751
SIGELTFEXP_SIGE->PJM
CLTF
0.232
NYPJM->LTFIMP_NY
CLTF
2.481
LGEELTFEXP_LGEE->PJM
CLTF
2.822
WECLTFEXP_WEC->PJM
CLTF
1.476
AG2-052LTFEXP_AG2-052->PJM
LTF
0.08
AH1-155LTFEXP_AH1-155->PJM
LTF
0.12

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-2: XT585_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: XT585_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.16 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5703.66
MW Contribution:25.83
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
8.505
970413AG2-270 GEN
50/50
46.449
3151591KERR 2
50/50
0.604
3144293JTRSVLE
50/50
0.914
970917AG2-570 GEN
Solar/Wind Harmer
170.53
316478AD1-087 GEN
Solar/Wind Harmer
4.831
316486AD2-202 GEN
Solar/Wind Harmer
1.415
970909AG2-566 GEN
Solar/Wind Harmer
3.791
316248AF1-058 C
Solar/Wind Harmer
1.169
960061AF2-297 GEN
Solar/Wind Harmer
19.391
971683AH1-343 GEN
Solar/Wind Harmer
14.982
316283AC2-100 C
Solar/Wind Harmer
3.205
316131AB2-060 GEN
Solar/Wind Harmer
3.471
964241AG1-285 GEN
Solar/Wind Harmer
24.911
315785AD2-033 C
Solar/Wind Harmer
7.122
970257AG2-171 GEN
Solar/Wind Harmer
11.718
959311AF2-222 GEN
Solar/Wind Harmer
32.481
963181AG1-167 GEN
Solar/Wind Harmer
2.849
3147133PAMPLIN
Solar/Wind Harmer
-0.094
971193AH1-056 GEN
Solar/Wind Harmer
18.811
942461AE2-259 GEN
Solar/Wind Harmer
4.399
3146926FARMVIL
Solar/Wind Harmer
-0.017
3146776BUCKING
Solar/Wind Harmer
-0.006
270018AE2-047 C O1
Solar/Wind Harmer
1.466
270197AD1-017 GEN1
Solar/Wind Harmer
1.802
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
6.086
943811AF1-049 GEN
Solar/Wind Harmer
4.09
270336AE1-100 GEN
Solar/Wind Harmer
1.669
3145543BTLEBRO
Solar/Wind Harmer
-0.014
3151051BRUNSWICKS1
50/50
17.651
3151021BRUNSWICKG1
50/50
8.505
971451AH1-221 GEN
50/50
25.831
315243AE2-183_GT3
50/50
10.667
3151531CLOVER1
50/50
10.644
3151601KERR 3
50/50
0.604
3151581KERR 1
50/50
0.216
3144293JTRSVLE
50/50
0.914
971629AH1-314 GEN
50/50
19.06
3151561HALLBR1
50/50
0.404
970919AG2-571 GEN
Solar/Wind Harmer
21.586
970087AG2-069 GEN
Solar/Wind Harmer
63.496
957481AF2-042 GEN
Solar/Wind Harmer
190.536
315693AD1-088 GEN
Solar/Wind Harmer
27.811
962491AG1-098 GEN
Solar/Wind Harmer
36.654
315687AD1-152 GEN
Solar/Wind Harmer
6.022
316003AC1-222 GEN
Solar/Wind Harmer
3.575
970401AG2-262 GEN
Solar/Wind Harmer
2.352
316237AB2-079_GEN
Solar/Wind Harmer
0.978
970685AG2-442 GEN
Solar/Wind Harmer
26.954
963171AG1-166 GEN
Solar/Wind Harmer
3.799
971563AH1-280 GEN
Solar/Wind Harmer
3.799
3146926FARMVIL
Solar/Wind Harmer
-0.017
971065AG2-659 GEN
Solar/Wind Harmer
12.523
316129AC1-054 GEN
Solar/Wind Harmer
2.059
970223AG2-152 GEN
Solar/Wind Harmer
18.408
270016AE1-250 BESS
Solar/Wind Harmer
3.042
3147123OTTER R
Solar/Wind Harmer
-0.011
316322AB2-045
Solar/Wind Harmer
0.605
3146776BUCKING
Solar/Wind Harmer
-0.007
270574AD1-017 GEN2
Solar/Wind Harmer
5.998
3147312GRETNA
Solar/Wind Harmer
-0.013
3146802CHATHAM
Solar/Wind Harmer
-0.012
941801AE2-185 GEN
Solar/Wind Harmer
6.086
270030AE2-140 GEN
Solar/Wind Harmer
21.053
3145543BTLEBRO
Solar/Wind Harmer
-0.014
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.864
316049AB1-081 GEN
Solar/Wind Harmer
1.492
3142053HEARTS
Solar/Wind Harmer
0.163
316294AC1-161 GEN
Solar/Wind Helper
8.153
316375AC2-012 GEN
Solar/Wind Helper
1.068
3145336SMITFLD
Solar/Wind Helper
1.575
316388AE2-253 GEN
Solar/Wind Helper
1.472
3146456SLIGO L269
Solar/Wind Helper
0.379
316381AD1-082 GEN
Solar/Wind Helper
1.955
316072AD1-144
Solar/Wind Helper
0.428
316246AF1-032 C
Solar/Wind Helper
0.424
316159AE1-175 C
Solar/Wind Helper
0.562
316458AB2-190 GEN2
Solar/Wind Helper
2.107
3141766HARMONY
Solar/Wind Helper
0.069
3142433PROV 92
Solar/Wind Helper
1.376
3138133OCRAN
Solar/Wind Helper
0.206
3142543TWELFTH
Solar/Wind Helper
0.032
964211AG1-282 GEN
Solar/Wind Helper
0.439
3141726DUNNSVL
Solar/Wind Helper
1.304
316337AD2-073 GEN
Solar/Wind Helper
0.478
3142416OLDCHRC
Solar/Wind Helper
0.816
3142416OLDCHRC
Solar/Wind Helper
0.312
3146516WINFALL
Solar/Wind Helper
1.016
3146516WINFALL
Solar/Wind Helper
0.314
3143526WINTERP
Solar/Wind Helper
1.596
3143226MDLTHAN
Solar/Wind Helper
0.3
315800Z1-036_GEN1
Solar/Wind Helper
1.497
3130156CHOWAN
Solar/Wind Helper
0.241
3151041BRUNSWICKG3
50/50
8.505
972187AH1-678 GEN
50/50
19.517
315242AE2-183_GT2
50/50
10.667
315241AE2-183_GT1
50/50
10.602
972185AH1-677 GEN
50/50
38.457
3152661PLYWOOD A
50/50
0.751
970535AG2-341 GEN
50/50
5.149
3144293JTRSVLE
50/50
0.914
3144293JTRSVLE
50/50
0.769
970933AG2-581 GEN
Solar/Wind Harmer
67.863
970099AG2-077 GEN
Solar/Wind Harmer
76.214
971741AH1-377 GEN
Solar/Wind Harmer
50.609
970301AG2-198 GEN
Solar/Wind Harmer
19.968
3146843MT LREL
Solar/Wind Harmer
-0.036
3146843MT LREL
Solar/Wind Harmer
-0.036
964791AG1-342 GEN
Solar/Wind Harmer
7.699
962561AG1-105 GEN
Solar/Wind Harmer
19.948
316222AC1-221 GEN
Solar/Wind Harmer
3.472
939181AE1-148 GEN
Solar/Wind Harmer
18.394
313527AB2-043 GEN
Solar/Wind Harmer
5.237
970323AG2-213 GEN
Solar/Wind Harmer
15.625
971775AH1-396 GEN
Solar/Wind Harmer
2.225
316034AC1-036 C
Solar/Wind Harmer
0.579
958211AF2-115 GEN
Solar/Wind Harmer
4.748
963191AG1-168 GEN
Solar/Wind Harmer
2.849
3147133PAMPLIN
Solar/Wind Harmer
-0.03
3147133PAMPLIN
Solar/Wind Harmer
-0.024
942751AE2-291 GEN
Solar/Wind Harmer
16.78
270013AE1-250 PV
Solar/Wind Harmer
3.042
3146776BUCKING
Solar/Wind Harmer
-0.072
3146776BUCKING
Solar/Wind Harmer
-0.006
316217AC1-145 GEN
Solar/Wind Harmer
2.634
316197AC1-042 GEN
Solar/Wind Harmer
1.997
942671AE2-283 GEN
Solar/Wind Harmer
5.376
316263AC1-034 GEN
Solar/Wind Harmer
6.481
961601AG1-000A GEN
Solar/Wind Harmer
5.306
316036AC1-147 C
Solar/Wind Helper
0.621
3142956BIRDNECK
Solar/Wind Helper
0.272
316316AC1-027 C
Solar/Wind Helper
0.638
316185AD1-033 GEN
Solar/Wind Helper
1.893
3145506HICKORY
Solar/Wind Helper
1.587
3145506HICKORY
Solar/Wind Helper
0.952
3145506HICKORY
Solar/Wind Helper
0.238
316236AE1-162_GEN
Solar/Wind Helper
0.529
316339AD2-160 GEN
Solar/Wind Helper
1.472
316018AA1-139 ULT2
Solar/Wind Helper
1.65
316017AA1-139 ULT1
Solar/Wind Helper
1.754
3137176SLIGO L2192
Solar/Wind Helper
1.508
3130086AYDLETT
Solar/Wind Helper
1.498
316033AB2-134 GEN
Solar/Wind Helper
1.287
315697AD1-025 GEN
Solar/Wind Helper
4.277
316240AF1-291 C
Solar/Wind Helper
0.501
3146386ELIZ CT
Solar/Wind Helper
0.35
3142946ENON
Solar/Wind Helper
0.034
316487AF1-042 GEN
Solar/Wind Helper
0.339
3144356SAPONY
Solar/Wind Helper
0.597
316075AC2-137 C
Solar/Wind Helper
0.502
316077AC2-138 C
Solar/Wind Helper
0.305
316431W1029_GEN1
Solar/Wind Helper
1.295
316433W1029_GEN2
Solar/Wind Helper
1.295
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3143526WINTERP
Solar/Wind Helper
1.596
966871AG1-558 GEN
Solar/Wind Helper
0.403
3146626S HERTFORD
Solar/Wind Helper
0.296
3146626S HERTFORD
Solar/Wind Helper
0.296
316468AD1-105 GEN
Solar/Wind Helper
1.402
315742AE1-103 GEN
Solar/Wind Helper
0.368
963041AG1-153 GEN
50/50
17.22
315244AE2-183_ST
50/50
18.443
3151541CLOVER2
50/50
10.593
3151611KERR 4
50/50
0.604
3151621KERR 5
50/50
0.604
3151631KERR 6
50/50
0.604
3151641KERR 7
50/50
0.604
971967AH1-528 GEN
Solar/Wind Harmer
144.6
970085AG2-068 GEN
Solar/Wind Harmer
42.331
970581AG2-369 GEN
Solar/Wind Harmer
36.404
3147173SINAI
Solar/Wind Harmer
-0.039
3147243WELCO
Solar/Wind Harmer
-0.024
316118AC1-105 GEN
Solar/Wind Harmer
2.575
970865AG2-541 GEN
Solar/Wind Harmer
13.323
316239AB2-077_GEN
Solar/Wind Harmer
0.978
316238AB2-078_GEN
Solar/Wind Harmer
0.978
971443AH1-215 GEN
Solar/Wind Harmer
6.159
3144303KENBRDG
Solar/Wind Harmer
-0.025
970683AG2-441 GEN
Solar/Wind Harmer
24.066
970681AG2-440 GEN
Solar/Wind Harmer
19.253
946301AF1-294 GEN
Solar/Wind Harmer
7.788
961791AG1-021 GEN
Solar/Wind Harmer
3.799
315657AE1-056 GEN
Solar/Wind Harmer
11.287
316123AC1-075 GEN
Solar/Wind Harmer
3.111
970165AG2-112 GEN
Solar/Wind Harmer
2.739
970163AG2-111 GEN
Solar/Wind Harmer
2.613
270455AD2-022 GEN
Solar/Wind Harmer
5.008
270457AD2-023 GEN
Solar/Wind Harmer
2.539
970831AG2-522 GEN
Solar/Wind Harmer
10.909
970285AG2-188 GEN
Solar/Wind Harmer
17.971
971845AH1-439 GEN
Solar/Wind Harmer
10.023
270069AE2-166 C O1
Solar/Wind Harmer
2.578
3143316POE
Solar/Wind Helper
1.64
319010AE1-072 C
Solar/Wind Helper
4.299
316369SG1_INVT
Solar/Wind Helper
1.8
316305AF2-043 C
Solar/Wind Helper
0.499
316132AB2-190 GEN1
Solar/Wind Helper
2.107
957831AF2-077 GEN
Solar/Wind Helper
0.495
316349AD2-085 GEN
Solar/Wind Helper
1.649
313526AB2-022
Solar/Wind Helper
0.533
957601AF2-054 GEN
Solar/Wind Helper
0.467
3141873WAN 176
Solar/Wind Helper
0.07
315662AE1-191 GEN
Solar/Wind Helper
1.865
315666AE1-190 GEN
Solar/Wind Helper
0.466
316059AD1-063 C
Solar/Wind Helper
0.348
3141913WHIT STONE
Solar/Wind Helper
0.345
3138133OCRAN
Solar/Wind Helper
0.103
3143873LANEXA
Solar/Wind Helper
0.206
3141783LANCAST
Solar/Wind Helper
0.205
3141783LANCAST
Solar/Wind Helper
0.137
3146486SUNBURY
Solar/Wind Helper
0.341
3146486SUNBURY
Solar/Wind Helper
0.341
316321Z2-027
Solar/Wind Helper
0.514
3145176PASQUOTANK
Solar/Wind Helper
0.209
316315AB2-025 C
Solar/Wind Helper
0.507
3141813NORNECK
Solar/Wind Helper
0.325
316312AB1-027
Solar/Wind Helper
0.597
316233AE1-074 FULL
Solar/Wind Helper
0.469
316223AC1-118
Solar/Wind Helper
0.466
315611Z1-036_GEN2
Solar/Wind Helper
1.497
3130156CHOWAN
Solar/Wind Helper
0.241
3130156CHOWAN
Solar/Wind Helper
0.241
3145543BTLEBRO
Solar/Wind Harmer
-0.014
961601AG1-000A GEN
Solar/Wind Harmer
5.373
315773AC2-141 GEN
Solar/Wind Helper
9.595
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.061
3145336SMITFLD
Solar/Wind Helper
0.157
315839AE2-212 C
Solar/Wind Helper
0.523
3146456SLIGO L269
Solar/Wind Helper
0.379
316382AG1-145 C
Solar/Wind Helper
0.498
316320Y1-086
Solar/Wind Helper
0.156
316156AD2-030 GEN
Solar/Wind Helper
0.525
316280AD1-041 GEN
Solar/Wind Helper
1.166
3142946ENON
Solar/Wind Helper
0.114
316484AD2-074 GEN
Solar/Wind Helper
0.648
316404AE1-155 C
Solar/Wind Helper
2.8
316435W1029_GEN3
Solar/Wind Helper
1.295
3146516WINFALL
Solar/Wind Helper
0.314
3141906WESTMOR
Solar/Wind Helper
0.122
316473AC1-191 GEN
Solar/Wind Helper
1.829
3146626S HERTFORD
Solar/Wind Helper
0.296
3145273HOLLAND
Solar/Wind Helper
0.201
966881AG1-559 GEN
Solar/Wind Helper
0.35
3146376EDENTON
Solar/Wind Helper
0.24
LAGNLTFEXP_LAGN->PJM
CLTF
15.403
CBM South 2LTFEXP_CBM-S2->PJM
CBM
46.288
TVALTFEXP_TVA->PJM
CLTF
7.684
CPLELTFEXP_CPLE->PJM
CLTF
20.639
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.343
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.697
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.447
MECLTFEXP_MEC->PJM
CLTF
7.78
SIGELTFEXP_SIGE->PJM
CLTF
0.233
NYPJM->LTFIMP_NY
CLTF
2.484
LGEELTFEXP_LGEE->PJM
CLTF
2.833
WECLTFEXP_WEC->PJM
CLTF
1.482
AG2-052LTFEXP_AG2-052->PJM
LTF
0.08
AH1-155LTFEXP_AH1-155->PJM
LTF
0.12

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-2: 54472_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 54472_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.74 %
Rating:2858.0 MVA
Rating Type:C
MVA to Mitigate:3193.49
MW Contribution:12.55
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
7.968
3151051BRUNSWICKS1
50/50
8.574
3151021BRUNSWICKG1
50/50
4.131
971451AH1-221 GEN
50/50
12.548
315243AE2-183_GT3
50/50
3.874
3151601KERR 3
50/50
0.44
3151581KERR 1
50/50
0.157
3144293JTRSVLE
50/50
0.691
971629AH1-314 GEN
50/50
11.594
957481AF2-042 GEN
Solar/Wind Harmer
144.035
315693AD1-088 GEN
Solar/Wind Harmer
21.036
962491AG1-098 GEN
Solar/Wind Harmer
27.737
315687AD1-152 GEN
Solar/Wind Harmer
4.411
970919AG2-571 GEN
Solar/Wind Harmer
10.566
970087AG2-069 GEN
Solar/Wind Harmer
31.107
970401AG2-262 GEN
Solar/Wind Harmer
1.7
316003AC1-222 GEN
Solar/Wind Harmer
2.544
316237AB2-079_GEN
Solar/Wind Harmer
0.722
970685AG2-442 GEN
Solar/Wind Harmer
20.27
963171AG1-166 GEN
Solar/Wind Harmer
2.872
971563AH1-280 GEN
Solar/Wind Harmer
2.872
3146926FARMVIL
Solar/Wind Harmer
-0.013
971065AG2-659 GEN
Solar/Wind Harmer
9.218
316129AC1-054 GEN
Solar/Wind Harmer
1.52
316322AB2-045
Solar/Wind Harmer
0.488
3146776BUCKING
Solar/Wind Harmer
-0.006
970223AG2-152 GEN
Solar/Wind Harmer
11.343
316294AC1-161 GEN
Solar/Wind Helper
4.653
3151041BRUNSWICKG3
50/50
4.131
972187AH1-678 GEN
50/50
9.481
3152661PLYWOOD A
50/50
0.538
315242AE2-183_GT2
50/50
3.874
315241AE2-183_GT1
50/50
3.85
972185AH1-677 GEN
50/50
13.967
970535AG2-341 GEN
50/50
3.778
3144293JTRSVLE
50/50
0.691
3144293JTRSVLE
50/50
0.582
970933AG2-581 GEN
Solar/Wind Harmer
51.852
970099AG2-077 GEN
Solar/Wind Harmer
57.614
971741AH1-377 GEN
Solar/Wind Harmer
38.586
970301AG2-198 GEN
Solar/Wind Harmer
15.274
3146843MT LREL
Solar/Wind Harmer
-0.026
3146843MT LREL
Solar/Wind Harmer
-0.026
964791AG1-342 GEN
Solar/Wind Harmer
5.564
962561AG1-105 GEN
Solar/Wind Harmer
14.462
939181AE1-148 GEN
Solar/Wind Harmer
13.444
313527AB2-043 GEN
Solar/Wind Harmer
3.87
970323AG2-213 GEN
Solar/Wind Harmer
11.685
971775AH1-396 GEN
Solar/Wind Harmer
1.664
316034AC1-036 C
Solar/Wind Harmer
0.433
958211AF2-115 GEN
Solar/Wind Harmer
3.59
963191AG1-168 GEN
Solar/Wind Harmer
2.154
3147133PAMPLIN
Solar/Wind Harmer
-0.023
3147133PAMPLIN
Solar/Wind Harmer
-0.018
316222AC1-221 GEN
Solar/Wind Harmer
2.218
942751AE2-291 GEN
Solar/Wind Harmer
11.754
3146776BUCKING
Solar/Wind Harmer
-0.058
3146776BUCKING
Solar/Wind Harmer
-0.005
316240AF1-291 C
Solar/Wind Helper
0.299
3151541CLOVER2
50/50
7.93
963041AG1-153 GEN
50/50
8.365
315244AE2-183_ST
50/50
6.698
3151611KERR 4
50/50
0.44
3151621KERR 5
50/50
0.44
3151631KERR 6
50/50
0.44
3151641KERR 7
50/50
0.44
971967AH1-528 GEN
Solar/Wind Harmer
110.812
970085AG2-068 GEN
Solar/Wind Harmer
20.738
970581AG2-369 GEN
Solar/Wind Harmer
17.835
3147173SINAI
Solar/Wind Harmer
-0.028
3147243WELCO
Solar/Wind Harmer
-0.017
316118AC1-105 GEN
Solar/Wind Harmer
1.848
316239AB2-077_GEN
Solar/Wind Harmer
0.722
316238AB2-078_GEN
Solar/Wind Harmer
0.722
971443AH1-215 GEN
Solar/Wind Harmer
4.604
3144303KENBRDG
Solar/Wind Harmer
-0.019
970865AG2-541 GEN
Solar/Wind Harmer
9.435
970683AG2-441 GEN
Solar/Wind Harmer
18.098
970681AG2-440 GEN
Solar/Wind Harmer
14.478
946301AF1-294 GEN
Solar/Wind Harmer
5.887
961791AG1-021 GEN
Solar/Wind Harmer
2.872
315657AE1-056 GEN
Solar/Wind Harmer
8.565
316123AC1-075 GEN
Solar/Wind Harmer
2.19
970165AG2-112 GEN
Solar/Wind Harmer
1.928
970163AG2-111 GEN
Solar/Wind Harmer
1.839
970673AG2-436 GEN
Solar/Wind Harmer
40.956
970673AG2-436 GEN
Solar/Wind Harmer
20.737
270455AD2-022 GEN
Solar/Wind Harmer
3.036
270457AD2-023 GEN
Solar/Wind Harmer
1.539
970285AG2-188 GEN
Solar/Wind Harmer
14.324
970831AG2-522 GEN
Solar/Wind Harmer
8.077
971845AH1-439 GEN
Solar/Wind Harmer
8.053
3143316POE
Solar/Wind Helper
1.004
970413AG2-270 GEN
50/50
34.77
3151031BRUNSWICKG2
50/50
4.131
3151591KERR 2
50/50
0.44
3144293JTRSVLE
50/50
0.691
316478AD1-087 GEN
Solar/Wind Harmer
3.615
316486AD2-202 GEN
Solar/Wind Harmer
1.059
970917AG2-570 GEN
Solar/Wind Harmer
83.468
970909AG2-566 GEN
Solar/Wind Harmer
2.9
316248AF1-058 C
Solar/Wind Harmer
0.833
960061AF2-297 GEN
Solar/Wind Harmer
13.826
971683AH1-343 GEN
Solar/Wind Harmer
10.636
316131AB2-060 GEN
Solar/Wind Harmer
2.567
964241AG1-285 GEN
Solar/Wind Harmer
18.486
315785AD2-033 C
Solar/Wind Harmer
5.315
970257AG2-171 GEN
Solar/Wind Harmer
8.764
959311AF2-222 GEN
Solar/Wind Harmer
24.33
963181AG1-167 GEN
Solar/Wind Harmer
2.154
3147133PAMPLIN
Solar/Wind Harmer
-0.071
971193AH1-056 GEN
Solar/Wind Harmer
14.275
942461AE2-259 GEN
Solar/Wind Harmer
3.375
3146926FARMVIL
Solar/Wind Harmer
-0.013
316283AC2-100 C
Solar/Wind Harmer
2.04
3146776BUCKING
Solar/Wind Harmer
-0.005
315773AC2-141 GEN
Solar/Wind Helper
5.476
315839AE2-212 C
Solar/Wind Helper
0.317
LAGNLTFEXP_LAGN->PJM
CLTF
8.928
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.434
TVALTFEXP_TVA->PJM
CLTF
4.461
CPLELTFEXP_CPLE->PJM
CLTF
11.786
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.116
CBM West 1LTFEXP_CBM-W1->PJM
CBM
31.523
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.401
MECLTFEXP_MEC->PJM
CLTF
4.601
SIGELTFEXP_SIGE->PJM
CLTF
0.139
NYPJM->LTFIMP_NY
CLTF
1.417
LGEELTFEXP_LGEE->PJM
CLTF
1.692
WECLTFEXP_WEC->PJM
CLTF
0.884

Details for 8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 511_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:123.06 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5008.65
MW Contribution:25.61
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
8.432
970413AG2-270 GEN
50/50
40.853
3151591KERR 2
50/50
0.537
3144293JTRSVLE
50/50
0.801
970917AG2-570 GEN
Solar/Wind Harmer
53.421
316478AD1-087 GEN
Solar/Wind Harmer
1.525
316486AD2-202 GEN
Solar/Wind Harmer
0.448
970909AG2-566 GEN
Solar/Wind Harmer
3.307
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
13.182
316283AC2-100 C
Solar/Wind Harmer
0.55
971683AH1-343 GEN
Solar/Wind Harmer
10.2
316131AB2-060 GEN
Solar/Wind Harmer
0.796
964241AG1-285 GEN
Solar/Wind Harmer
16.703
315785AD2-033 C
Solar/Wind Harmer
2.003
970257AG2-171 GEN
Solar/Wind Harmer
7.834
959311AF2-222 GEN
Solar/Wind Harmer
21.656
963181AG1-167 GEN
Solar/Wind Harmer
0.948
3147133PAMPLIN
Solar/Wind Harmer
0.736
971193AH1-056 GEN
Solar/Wind Harmer
14.274
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.131
270018AE2-047 C O1
Solar/Wind Harmer
0.003
270197AD1-017 GEN1
Solar/Wind Harmer
0.943
3146776BUCKING
Solar/Wind Harmer
0.049
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3147312GRETNA
Solar/Wind Harmer
0.026
941821AE2-187 GEN
Solar/Wind Harmer
4.212
270336AE1-100 GEN
Solar/Wind Harmer
0.003
3145543BTLEBRO
Solar/Wind Harmer
0.117
3145543BTLEBRO
Solar/Wind Harmer
0.117
971623AH1-311 GEN
Solar/Wind Harmer
0.234
961601AG1-000A GEN
Solar/Wind Harmer
8.141
315773AC2-141 GEN
Solar/Wind Helper
9.054
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.057
3145336SMITFLD
Solar/Wind Helper
0.149
315839AE2-212 C
Solar/Wind Helper
0.495
3146456SLIGO L269
Solar/Wind Helper
0.357
316382AG1-145 C
Solar/Wind Helper
0.471
316320Y1-086
Solar/Wind Helper
0.147
316156AD2-030 GEN
Solar/Wind Helper
0.497
316280AD1-041 GEN
Solar/Wind Helper
1.104
3142946ENON
Solar/Wind Helper
0.108
316484AD2-074 GEN
Solar/Wind Helper
0.613
316404AE1-155 C
Solar/Wind Helper
2.651
316435W1029_GEN3
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3141906WESTMOR
Solar/Wind Helper
0.116
316473AC1-191 GEN
Solar/Wind Helper
1.736
3146626S HERTFORD
Solar/Wind Helper
0.28
3145273HOLLAND
Solar/Wind Helper
0.191
966881AG1-559 GEN
Solar/Wind Helper
0.333
3146376EDENTON
Solar/Wind Helper
0.227
315244AE2-183_ST
50/50
19.249
963041AG1-153 GEN
50/50
17.073
3151541CLOVER2
50/50
9.317
3151611KERR 4
50/50
0.537
3151621KERR 5
50/50
0.537
3151631KERR 6
50/50
0.537
3151641KERR 7
50/50
0.537
971967AH1-528 GEN
Solar/Wind Harmer
95.481
970085AG2-068 GEN
Solar/Wind Harmer
31.82
970581AG2-369 GEN
Solar/Wind Harmer
27.365
3147173SINAI
Solar/Wind Harmer
0.309
3147243WELCO
Solar/Wind Harmer
0.193
316118AC1-105 GEN
Solar/Wind Harmer
0.768
970865AG2-541 GEN
Solar/Wind Harmer
9.078
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
4.118
3144303KENBRDG
Solar/Wind Harmer
0.196
970683AG2-441 GEN
Solar/Wind Harmer
16.053
970681AG2-440 GEN
Solar/Wind Harmer
12.842
946301AF1-294 GEN
Solar/Wind Harmer
4.678
961791AG1-021 GEN
Solar/Wind Harmer
2.276
315657AE1-056 GEN
Solar/Wind Harmer
8.085
316123AC1-075 GEN
Solar/Wind Harmer
0.315
970165AG2-112 GEN
Solar/Wind Harmer
1.87
970163AG2-111 GEN
Solar/Wind Harmer
1.784
970831AG2-522 GEN
Solar/Wind Harmer
7.35
970285AG2-188 GEN
Solar/Wind Harmer
12.402
971845AH1-439 GEN
Solar/Wind Harmer
6.507
270069AE2-166 C O1
Solar/Wind Harmer
0.004
3143316POE
Solar/Wind Helper
1.55
319010AE1-072 C
Solar/Wind Helper
4.057
316369SG1_INVT
Solar/Wind Helper
1.702
316305AF2-043 C
Solar/Wind Helper
0.471
316132AB2-190 GEN1
Solar/Wind Helper
1.993
957831AF2-077 GEN
Solar/Wind Helper
0.468
316349AD2-085 GEN
Solar/Wind Helper
1.559
313526AB2-022
Solar/Wind Helper
0.503
957601AF2-054 GEN
Solar/Wind Helper
0.442
3141873WAN 176
Solar/Wind Helper
0.066
315662AE1-191 GEN
Solar/Wind Helper
1.766
315666AE1-190 GEN
Solar/Wind Helper
0.441
316059AD1-063 C
Solar/Wind Helper
0.329
3141913WHIT STONE
Solar/Wind Helper
0.326
3138133OCRAN
Solar/Wind Helper
0.098
3143873LANEXA
Solar/Wind Helper
0.195
3141783LANCAST
Solar/Wind Helper
0.194
3141783LANCAST
Solar/Wind Helper
0.129
3146486SUNBURY
Solar/Wind Helper
0.322
3146486SUNBURY
Solar/Wind Helper
0.322
316321Z2-027
Solar/Wind Helper
0.485
3145176PASQUOTANK
Solar/Wind Helper
0.197
316315AB2-025 C
Solar/Wind Helper
0.48
3141813NORNECK
Solar/Wind Helper
0.308
316312AB1-027
Solar/Wind Helper
0.567
316233AE1-074 FULL
Solar/Wind Helper
0.447
316223AC1-118
Solar/Wind Helper
0.442
315611Z1-036_GEN2
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
315243AE2-183_GT3
50/50
11.133
3151051BRUNSWICKS1
50/50
17.499
3151021BRUNSWICKG1
50/50
8.432
971451AH1-221 GEN
50/50
25.609
3151531CLOVER1
50/50
9.362
3151601KERR 3
50/50
0.537
3151581KERR 1
50/50
0.192
3144293JTRSVLE
50/50
0.801
971629AH1-314 GEN
50/50
17.923
3151561HALLBR1
50/50
0.367
970919AG2-571 GEN
Solar/Wind Harmer
21.368
970087AG2-069 GEN
Solar/Wind Harmer
47.73
957481AF2-042 GEN
Solar/Wind Harmer
126.807
315693AD1-088 GEN
Solar/Wind Harmer
20.818
962491AG1-098 GEN
Solar/Wind Harmer
24.385
315687AD1-152 GEN
Solar/Wind Harmer
0.013
316003AC1-222 GEN
Solar/Wind Harmer
0.008
970401AG2-262 GEN
Solar/Wind Harmer
1.677
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970685AG2-442 GEN
Solar/Wind Harmer
17.979
963171AG1-166 GEN
Solar/Wind Harmer
1.264
971563AH1-280 GEN
Solar/Wind Harmer
2.529
3146926FARMVIL
Solar/Wind Harmer
0.131
971065AG2-659 GEN
Solar/Wind Harmer
8.445
316129AC1-054 GEN
Solar/Wind Harmer
0.698
970223AG2-152 GEN
Solar/Wind Harmer
12.094
270016AE1-250 BESS
Solar/Wind Harmer
0.005
3147123OTTER R
Solar/Wind Harmer
0.088
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.055
3147312GRETNA
Solar/Wind Harmer
0.105
3146802CHATHAM
Solar/Wind Harmer
0.099
941801AE2-185 GEN
Solar/Wind Harmer
4.212
270030AE2-140 GEN
Solar/Wind Harmer
13.804
3145543BTLEBRO
Solar/Wind Harmer
0.117
3145543BTLEBRO
Solar/Wind Harmer
0.094
316359AB2-059 GEN
Solar/Wind Harmer
0.421
316049AB1-081 GEN
Solar/Wind Harmer
0.67
3142053HEARTS
Solar/Wind Harmer
0.206
316294AC1-161 GEN
Solar/Wind Helper
7.693
316375AC2-012 GEN
Solar/Wind Helper
1.008
3145336SMITFLD
Solar/Wind Helper
1.487
316388AE2-253 GEN
Solar/Wind Helper
1.389
3146456SLIGO L269
Solar/Wind Helper
0.357
316381AD1-082 GEN
Solar/Wind Helper
1.848
316072AD1-144
Solar/Wind Helper
0.404
316246AF1-032 C
Solar/Wind Helper
0.401
316159AE1-175 C
Solar/Wind Helper
0.531
316458AB2-190 GEN2
Solar/Wind Helper
1.993
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.303
3138133OCRAN
Solar/Wind Helper
0.195
3142543TWELFTH
Solar/Wind Helper
0.03
964211AG1-282 GEN
Solar/Wind Helper
0.416
3141726DUNNSVL
Solar/Wind Helper
1.235
316337AD2-073 GEN
Solar/Wind Helper
0.453
3142416OLDCHRC
Solar/Wind Helper
0.774
3142416OLDCHRC
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.959
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
3143226MDLTHAN
Solar/Wind Helper
0.286
315800Z1-036_GEN1
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
315242AE2-183_GT2
50/50
11.133
315241AE2-183_GT1
50/50
11.065
972185AH1-677 GEN
50/50
40.137
3151041BRUNSWICKG3
50/50
8.432
972187AH1-678 GEN
50/50
19.349
3152661PLYWOOD A
50/50
0.671
970535AG2-341 GEN
50/50
4.566
3144293JTRSVLE
50/50
0.801
3144293JTRSVLE
50/50
0.674
970933AG2-581 GEN
Solar/Wind Harmer
44.982
970099AG2-077 GEN
Solar/Wind Harmer
50.723
971741AH1-377 GEN
Solar/Wind Harmer
33.569
970301AG2-198 GEN
Solar/Wind Harmer
13.228
3146843MT LREL
Solar/Wind Harmer
0.286
3146843MT LREL
Solar/Wind Harmer
0.286
964791AG1-342 GEN
Solar/Wind Harmer
5.488
316222AC1-221 GEN
Solar/Wind Harmer
1.175
962561AG1-105 GEN
Solar/Wind Harmer
13.485
939181AE1-148 GEN
Solar/Wind Harmer
12.41
313527AB2-043 GEN
Solar/Wind Harmer
0.003
970323AG2-213 GEN
Solar/Wind Harmer
10.445
971775AH1-396 GEN
Solar/Wind Harmer
0.392
316034AC1-036 C
Solar/Wind Harmer
0.018
958211AF2-115 GEN
Solar/Wind Harmer
2.845
963191AG1-168 GEN
Solar/Wind Harmer
0.948
3147133PAMPLIN
Solar/Wind Harmer
0.234
3147133PAMPLIN
Solar/Wind Harmer
0.187
942751AE2-291 GEN
Solar/Wind Harmer
11.476
270013AE1-250 PV
Solar/Wind Harmer
0.005
3146776BUCKING
Solar/Wind Harmer
0.546
3146776BUCKING
Solar/Wind Harmer
0.044
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
3.276
316263AC1-034 GEN
Solar/Wind Harmer
4.449
961601AG1-000A GEN
Solar/Wind Harmer
2.035
316036AC1-147 C
Solar/Wind Helper
0.586
3142956BIRDNECK
Solar/Wind Helper
0.257
316316AC1-027 C
Solar/Wind Helper
0.602
316185AD1-033 GEN
Solar/Wind Helper
1.787
3145506HICKORY
Solar/Wind Helper
1.497
3145506HICKORY
Solar/Wind Helper
0.899
3145506HICKORY
Solar/Wind Helper
0.225
316236AE1-162_GEN
Solar/Wind Helper
0.5
316339AD2-160 GEN
Solar/Wind Helper
1.389
316018AA1-139 ULT2
Solar/Wind Helper
1.557
316017AA1-139 ULT1
Solar/Wind Helper
1.655
3137176SLIGO L2192
Solar/Wind Helper
1.424
316033AB2-134 GEN
Solar/Wind Helper
1.217
315697AD1-025 GEN
Solar/Wind Helper
4.045
3130086AYDLETT
Solar/Wind Helper
1.414
316240AF1-291 C
Solar/Wind Helper
0.474
3146386ELIZ CT
Solar/Wind Helper
0.33
3142946ENON
Solar/Wind Helper
0.032
316487AF1-042 GEN
Solar/Wind Helper
0.321
3144356SAPONY
Solar/Wind Helper
0.565
316075AC2-137 C
Solar/Wind Helper
0.475
316077AC2-138 C
Solar/Wind Helper
0.289
316431W1029_GEN1
Solar/Wind Helper
1.222
316433W1029_GEN2
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
966871AG1-558 GEN
Solar/Wind Helper
0.383
3146626S HERTFORD
Solar/Wind Helper
0.28
3146626S HERTFORD
Solar/Wind Helper
0.28
316468AD1-105 GEN
Solar/Wind Helper
1.331
LAGNLTFEXP_LAGN->PJM
CLTF
14.669
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.275
TVALTFEXP_TVA->PJM
CLTF
7.315
CPLELTFEXP_CPLE->PJM
CLTF
19.748
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.24
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.721
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.156
MECLTFEXP_MEC->PJM
CLTF
7.366
SIGELTFEXP_SIGE->PJM
CLTF
0.221
NYPJM->LTFIMP_NY
CLTF
2.382
LGEELTFEXP_LGEE->PJM
CLTF
2.675
WECLTFEXP_WEC->PJM
CLTF
1.4
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113

Details for 8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 51192_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 51192_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.25 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5458.06
MW Contribution:25.61
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
11.133
3151051BRUNSWICKS1
50/50
17.499
3151021BRUNSWICKG1
50/50
8.432
971451AH1-221 GEN
50/50
25.609
3151531CLOVER1
50/50
9.362
3151601KERR 3
50/50
0.537
3151581KERR 1
50/50
0.192
3144293JTRSVLE
50/50
0.801
971629AH1-314 GEN
50/50
17.923
3151561HALLBR1
50/50
0.367
970919AG2-571 GEN
Solar/Wind Harmer
21.368
970087AG2-069 GEN
Solar/Wind Harmer
62.844
957481AF2-042 GEN
Solar/Wind Harmer
166.962
315693AD1-088 GEN
Solar/Wind Harmer
24.364
962491AG1-098 GEN
Solar/Wind Harmer
32.107
315687AD1-152 GEN
Solar/Wind Harmer
5.339
316003AC1-222 GEN
Solar/Wind Harmer
3.203
970401AG2-262 GEN
Solar/Wind Harmer
2.096
316237AB2-079_GEN
Solar/Wind Harmer
0.866
970685AG2-442 GEN
Solar/Wind Harmer
23.673
963171AG1-166 GEN
Solar/Wind Harmer
3.329
971563AH1-280 GEN
Solar/Wind Harmer
3.329
3146926FARMVIL
Solar/Wind Harmer
-0.015
971065AG2-659 GEN
Solar/Wind Harmer
11.119
316129AC1-054 GEN
Solar/Wind Harmer
1.828
970223AG2-152 GEN
Solar/Wind Harmer
17.247
315242AE2-183_GT2
50/50
11.133
315241AE2-183_GT1
50/50
11.065
972185AH1-677 GEN
50/50
40.137
3151041BRUNSWICKG3
50/50
8.432
972187AH1-678 GEN
50/50
19.349
3152661PLYWOOD A
50/50
0.671
970535AG2-341 GEN
50/50
4.566
3144293JTRSVLE
50/50
0.801
3144293JTRSVLE
50/50
0.674
970933AG2-581 GEN
Solar/Wind Harmer
59.226
970099AG2-077 GEN
Solar/Wind Harmer
66.785
971741AH1-377 GEN
Solar/Wind Harmer
44.199
970301AG2-198 GEN
Solar/Wind Harmer
17.416
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.86
316222AC1-221 GEN
Solar/Wind Harmer
3.218
962561AG1-105 GEN
Solar/Wind Harmer
17.755
939181AE1-148 GEN
Solar/Wind Harmer
16.34
313527AB2-043 GEN
Solar/Wind Harmer
4.631
970323AG2-213 GEN
Solar/Wind Harmer
13.752
315244AE2-183_ST
50/50
19.249
963041AG1-153 GEN
50/50
17.073
3151541CLOVER2
50/50
9.317
3151611KERR 4
50/50
0.537
3151621KERR 5
50/50
0.537
3151631KERR 6
50/50
0.537
3151641KERR 7
50/50
0.537
971967AH1-528 GEN
Solar/Wind Harmer
126.052
970085AG2-068 GEN
Solar/Wind Harmer
41.896
970581AG2-369 GEN
Solar/Wind Harmer
36.031
3147173SINAI
Solar/Wind Harmer
-0.035
3147243WELCO
Solar/Wind Harmer
-0.021
316118AC1-105 GEN
Solar/Wind Harmer
2.3
970865AG2-541 GEN
Solar/Wind Harmer
11.953
316239AB2-077_GEN
Solar/Wind Harmer
0.866
270016AE1-250 BESS
Solar/Wind Harmer
2.846
3147123OTTER R
Solar/Wind Harmer
-0.01
270574AD1-017 GEN2
Solar/Wind Harmer
5.591
316322AB2-045
Solar/Wind Harmer
0.516
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.545
270030AE2-140 GEN
Solar/Wind Harmer
19.786
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.774
316049AB1-081 GEN
Solar/Wind Harmer
1.419
3142053HEARTS
Solar/Wind Harmer
0.155
316294AC1-161 GEN
Solar/Wind Helper
7.693
316375AC2-012 GEN
Solar/Wind Helper
1.008
3145336SMITFLD
Solar/Wind Helper
1.487
316388AE2-253 GEN
Solar/Wind Helper
1.389
3146456SLIGO L269
Solar/Wind Helper
0.357
316381AD1-082 GEN
Solar/Wind Helper
1.848
316072AD1-144
Solar/Wind Helper
0.404
316246AF1-032 C
Solar/Wind Helper
0.401
316159AE1-175 C
Solar/Wind Helper
0.531
316458AB2-190 GEN2
Solar/Wind Helper
1.993
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.303
3138133OCRAN
Solar/Wind Helper
0.195
3142543TWELFTH
Solar/Wind Helper
0.03
964211AG1-282 GEN
Solar/Wind Helper
0.416
3141726DUNNSVL
Solar/Wind Helper
1.235
316337AD2-073 GEN
Solar/Wind Helper
0.453
3142416OLDCHRC
Solar/Wind Helper
0.774
3142416OLDCHRC
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.959
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
3143226MDLTHAN
Solar/Wind Helper
0.286
315800Z1-036_GEN1
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
971775AH1-396 GEN
Solar/Wind Harmer
1.958
316034AC1-036 C
Solar/Wind Harmer
0.51
958211AF2-115 GEN
Solar/Wind Harmer
4.162
963191AG1-168 GEN
Solar/Wind Harmer
2.497
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
15.11
270013AE1-250 PV
Solar/Wind Harmer
2.846
3146776BUCKING
Solar/Wind Harmer
-0.061
3146776BUCKING
Solar/Wind Harmer
-0.005
316217AC1-145 GEN
Solar/Wind Harmer
2.4
316197AC1-042 GEN
Solar/Wind Harmer
1.819
942671AE2-283 GEN
Solar/Wind Harmer
4.898
316263AC1-034 GEN
Solar/Wind Harmer
6.166
961601AG1-000A GEN
Solar/Wind Harmer
5.056
316036AC1-147 C
Solar/Wind Helper
0.586
3142956BIRDNECK
Solar/Wind Helper
0.257
316316AC1-027 C
Solar/Wind Helper
0.602
316185AD1-033 GEN
Solar/Wind Helper
1.787
3145506HICKORY
Solar/Wind Helper
1.497
3145506HICKORY
Solar/Wind Helper
0.899
3145506HICKORY
Solar/Wind Helper
0.225
316236AE1-162_GEN
Solar/Wind Helper
0.5
316339AD2-160 GEN
Solar/Wind Helper
1.389
316018AA1-139 ULT2
Solar/Wind Helper
1.557
316017AA1-139 ULT1
Solar/Wind Helper
1.655
3137176SLIGO L2192
Solar/Wind Helper
1.424
316033AB2-134 GEN
Solar/Wind Helper
1.217
315697AD1-025 GEN
Solar/Wind Helper
4.045
3130086AYDLETT
Solar/Wind Helper
1.414
316240AF1-291 C
Solar/Wind Helper
0.474
3146386ELIZ CT
Solar/Wind Helper
0.33
3142946ENON
Solar/Wind Helper
0.032
316487AF1-042 GEN
Solar/Wind Helper
0.321
3144356SAPONY
Solar/Wind Helper
0.565
316075AC2-137 C
Solar/Wind Helper
0.475
316077AC2-138 C
Solar/Wind Helper
0.289
316431W1029_GEN1
Solar/Wind Helper
1.222
316433W1029_GEN2
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
966871AG1-558 GEN
Solar/Wind Helper
0.383
3146626S HERTFORD
Solar/Wind Helper
0.28
3146626S HERTFORD
Solar/Wind Helper
0.28
316468AD1-105 GEN
Solar/Wind Helper
1.331
3151031BRUNSWICKG2
50/50
8.432
970413AG2-270 GEN
50/50
40.853
3151591KERR 2
50/50
0.537
3144293JTRSVLE
50/50
0.801
970917AG2-570 GEN
Solar/Wind Harmer
168.81
316478AD1-087 GEN
Solar/Wind Harmer
4.25
316486AD2-202 GEN
Solar/Wind Harmer
1.245
970909AG2-566 GEN
Solar/Wind Harmer
3.307
316248AF1-058 C
Solar/Wind Harmer
1.046
960061AF2-297 GEN
Solar/Wind Harmer
17.357
316283AC2-100 C
Solar/Wind Harmer
2.974
971683AH1-343 GEN
Solar/Wind Harmer
13.43
316131AB2-060 GEN
Solar/Wind Harmer
3.068
964241AG1-285 GEN
Solar/Wind Harmer
21.992
315785AD2-033 C
Solar/Wind Harmer
6.274
970257AG2-171 GEN
Solar/Wind Harmer
10.314
959311AF2-222 GEN
Solar/Wind Harmer
28.571
963181AG1-167 GEN
Solar/Wind Harmer
2.497
3147133PAMPLIN
Solar/Wind Harmer
-0.082
971193AH1-056 GEN
Solar/Wind Harmer
16.462
942461AE2-259 GEN
Solar/Wind Harmer
3.832
3146926FARMVIL
Solar/Wind Harmer
-0.015
270018AE2-047 C O1
Solar/Wind Harmer
1.378
270197AD1-017 GEN1
Solar/Wind Harmer
1.68
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.844
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.545
270336AE1-100 GEN
Solar/Wind Harmer
1.569
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
961601AG1-000A GEN
Solar/Wind Harmer
5.12
315773AC2-141 GEN
Solar/Wind Helper
9.054
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.057
3145336SMITFLD
Solar/Wind Helper
0.149
315839AE2-212 C
Solar/Wind Helper
0.495
3146456SLIGO L269
Solar/Wind Helper
0.357
316382AG1-145 C
Solar/Wind Helper
0.471
316320Y1-086
Solar/Wind Helper
0.147
316156AD2-030 GEN
Solar/Wind Helper
0.497
316280AD1-041 GEN
Solar/Wind Helper
1.104
3142946ENON
Solar/Wind Helper
0.108
316484AD2-074 GEN
Solar/Wind Helper
0.613
316404AE1-155 C
Solar/Wind Helper
2.651
316435W1029_GEN3
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3141906WESTMOR
Solar/Wind Helper
0.116
316473AC1-191 GEN
Solar/Wind Helper
1.736
3146626S HERTFORD
Solar/Wind Helper
0.28
3145273HOLLAND
Solar/Wind Helper
0.191
966881AG1-559 GEN
Solar/Wind Helper
0.333
3146376EDENTON
Solar/Wind Helper
0.227
316238AB2-078_GEN
Solar/Wind Harmer
0.866
971443AH1-215 GEN
Solar/Wind Harmer
5.422
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
21.136
970681AG2-440 GEN
Solar/Wind Harmer
16.909
946301AF1-294 GEN
Solar/Wind Harmer
6.825
961791AG1-021 GEN
Solar/Wind Harmer
3.329
270455AD2-022 GEN
Solar/Wind Harmer
4.714
270457AD2-023 GEN
Solar/Wind Harmer
2.39
315657AE1-056 GEN
Solar/Wind Harmer
9.877
316123AC1-075 GEN
Solar/Wind Harmer
2.797
970165AG2-112 GEN
Solar/Wind Harmer
2.462
970163AG2-111 GEN
Solar/Wind Harmer
2.349
970831AG2-522 GEN
Solar/Wind Harmer
9.678
970285AG2-188 GEN
Solar/Wind Harmer
15.412
971845AH1-439 GEN
Solar/Wind Harmer
8.567
270069AE2-166 C O1
Solar/Wind Harmer
2.422
3143316POE
Solar/Wind Helper
1.55
319010AE1-072 C
Solar/Wind Helper
4.057
316369SG1_INVT
Solar/Wind Helper
1.702
316305AF2-043 C
Solar/Wind Helper
0.471
316132AB2-190 GEN1
Solar/Wind Helper
1.993
957831AF2-077 GEN
Solar/Wind Helper
0.468
316349AD2-085 GEN
Solar/Wind Helper
1.559
313526AB2-022
Solar/Wind Helper
0.503
957601AF2-054 GEN
Solar/Wind Helper
0.442
3141873WAN 176
Solar/Wind Helper
0.066
315662AE1-191 GEN
Solar/Wind Helper
1.766
315666AE1-190 GEN
Solar/Wind Helper
0.441
316059AD1-063 C
Solar/Wind Helper
0.329
3141913WHIT STONE
Solar/Wind Helper
0.326
3138133OCRAN
Solar/Wind Helper
0.098
3143873LANEXA
Solar/Wind Helper
0.195
3141783LANCAST
Solar/Wind Helper
0.194
3141783LANCAST
Solar/Wind Helper
0.129
3146486SUNBURY
Solar/Wind Helper
0.322
3146486SUNBURY
Solar/Wind Helper
0.322
316321Z2-027
Solar/Wind Helper
0.485
3145176PASQUOTANK
Solar/Wind Helper
0.197
316315AB2-025 C
Solar/Wind Helper
0.48
3141813NORNECK
Solar/Wind Helper
0.308
316312AB1-027
Solar/Wind Helper
0.567
316233AE1-074 FULL
Solar/Wind Helper
0.447
316223AC1-118
Solar/Wind Helper
0.442
315611Z1-036_GEN2
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
LAGNLTFEXP_LAGN->PJM
CLTF
14.669
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.275
TVALTFEXP_TVA->PJM
CLTF
7.315
CPLELTFEXP_CPLE->PJM
CLTF
19.748
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.24
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.721
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.156
MECLTFEXP_MEC->PJM
CLTF
7.366
SIGELTFEXP_SIGE->PJM
CLTF
0.221
NYPJM->LTFIMP_NY
CLTF
2.382
LGEELTFEXP_LGEE->PJM
CLTF
2.675
WECLTFEXP_WEC->PJM
CLTF
1.4
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113

Details for 8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 51172_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 51172_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.79 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5435.07
MW Contribution:25.43
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
11.056
3151051BRUNSWICKS1
50/50
17.38
3151021BRUNSWICKG1
50/50
8.374
971451AH1-221 GEN
50/50
25.435
3151531CLOVER1
50/50
9.312
3151601KERR 3
50/50
0.538
3151581KERR 1
50/50
0.192
3144293JTRSVLE
50/50
0.8
971629AH1-314 GEN
50/50
17.875
3151561HALLBR1
50/50
0.366
970919AG2-571 GEN
Solar/Wind Harmer
21.227
970087AG2-069 GEN
Solar/Wind Harmer
62.431
957481AF2-042 GEN
Solar/Wind Harmer
166.01
315693AD1-088 GEN
Solar/Wind Harmer
24.233
962491AG1-098 GEN
Solar/Wind Harmer
31.935
315687AD1-152 GEN
Solar/Wind Harmer
5.313
316003AC1-222 GEN
Solar/Wind Harmer
3.193
970401AG2-262 GEN
Solar/Wind Harmer
2.094
316237AB2-079_GEN
Solar/Wind Harmer
0.868
970685AG2-442 GEN
Solar/Wind Harmer
23.682
963171AG1-166 GEN
Solar/Wind Harmer
3.328
971563AH1-280 GEN
Solar/Wind Harmer
3.328
3146926FARMVIL
Solar/Wind Harmer
-0.015
971065AG2-659 GEN
Solar/Wind Harmer
11.224
316129AC1-054 GEN
Solar/Wind Harmer
1.849
970223AG2-152 GEN
Solar/Wind Harmer
17.201
270016AE1-250 BESS
Solar/Wind Harmer
2.839
3147123OTTER R
Solar/Wind Harmer
-0.01
270574AD1-017 GEN2
Solar/Wind Harmer
5.577
316322AB2-045
Solar/Wind Harmer
0.514
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.53
270030AE2-140 GEN
Solar/Wind Harmer
19.734
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.817
316049AB1-081 GEN
Solar/Wind Harmer
1.454
3142053HEARTS
Solar/Wind Harmer
0.158
316294AC1-161 GEN
Solar/Wind Helper
7.785
316375AC2-012 GEN
Solar/Wind Helper
1.014
3145336SMITFLD
Solar/Wind Helper
1.482
315242AE2-183_GT2
50/50
11.056
315241AE2-183_GT1
50/50
10.988
972185AH1-677 GEN
50/50
39.858
3151041BRUNSWICKG3
50/50
8.374
972187AH1-678 GEN
50/50
19.217
3152661PLYWOOD A
50/50
0.67
970535AG2-341 GEN
50/50
4.577
3144293JTRSVLE
50/50
0.8
3144293JTRSVLE
50/50
0.674
970933AG2-581 GEN
Solar/Wind Harmer
58.849
970099AG2-077 GEN
Solar/Wind Harmer
66.404
971741AH1-377 GEN
Solar/Wind Harmer
43.978
970301AG2-198 GEN
Solar/Wind Harmer
17.332
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.854
316222AC1-221 GEN
Solar/Wind Harmer
3.208
962561AG1-105 GEN
Solar/Wind Harmer
17.747
939181AE1-148 GEN
Solar/Wind Harmer
16.378
313527AB2-043 GEN
Solar/Wind Harmer
4.643
970323AG2-213 GEN
Solar/Wind Harmer
13.768
971775AH1-396 GEN
Solar/Wind Harmer
1.961
316034AC1-036 C
Solar/Wind Harmer
0.511
958211AF2-115 GEN
Solar/Wind Harmer
4.16
963191AG1-168 GEN
Solar/Wind Harmer
2.496
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
15.066
270013AE1-250 PV
Solar/Wind Harmer
2.839
3146776BUCKING
Solar/Wind Harmer
-0.061
3146776BUCKING
Solar/Wind Harmer
-0.005
316217AC1-145 GEN
Solar/Wind Harmer
2.394
316197AC1-042 GEN
Solar/Wind Harmer
1.815
942671AE2-283 GEN
Solar/Wind Harmer
4.885
316263AC1-034 GEN
Solar/Wind Harmer
6.316
961601AG1-000A GEN
Solar/Wind Harmer
5.186
316036AC1-147 C
Solar/Wind Helper
0.59
3142956BIRDNECK
Solar/Wind Helper
0.259
316316AC1-027 C
Solar/Wind Helper
0.606
316185AD1-033 GEN
Solar/Wind Helper
1.799
3145506HICKORY
Solar/Wind Helper
1.507
3145506HICKORY
Solar/Wind Helper
0.904
3145506HICKORY
Solar/Wind Helper
0.226
316236AE1-162_GEN
Solar/Wind Helper
0.498
316339AD2-160 GEN
Solar/Wind Helper
1.397
316018AA1-139 ULT2
Solar/Wind Helper
1.567
316017AA1-139 ULT1
Solar/Wind Helper
1.665
3137176SLIGO L2192
Solar/Wind Helper
1.432
3130086AYDLETT
Solar/Wind Helper
1.421
316033AB2-134 GEN
Solar/Wind Helper
1.19
315697AD1-025 GEN
Solar/Wind Helper
3.953
3146386ELIZ CT
Solar/Wind Helper
0.331
316240AF1-291 C
Solar/Wind Helper
0.444
3142946ENON
Solar/Wind Helper
0.032
316487AF1-042 GEN
Solar/Wind Helper
0.318
316075AC2-137 C
Solar/Wind Helper
0.467
316077AC2-138 C
Solar/Wind Helper
0.286
316431W1029_GEN1
Solar/Wind Helper
1.225
3151031BRUNSWICKG2
50/50
8.374
970413AG2-270 GEN
50/50
40.637
3151591KERR 2
50/50
0.538
3144293JTRSVLE
50/50
0.8
970917AG2-570 GEN
Solar/Wind Harmer
167.695
316478AD1-087 GEN
Solar/Wind Harmer
4.227
316486AD2-202 GEN
Solar/Wind Harmer
1.238
970909AG2-566 GEN
Solar/Wind Harmer
3.291
316248AF1-058 C
Solar/Wind Harmer
1.043
960061AF2-297 GEN
Solar/Wind Harmer
17.305
316283AC2-100 C
Solar/Wind Harmer
2.965
971683AH1-343 GEN
Solar/Wind Harmer
13.39
316131AB2-060 GEN
Solar/Wind Harmer
3.076
964241AG1-285 GEN
Solar/Wind Harmer
22.038
315785AD2-033 C
Solar/Wind Harmer
6.282
970257AG2-171 GEN
Solar/Wind Harmer
10.326
959311AF2-222 GEN
Solar/Wind Harmer
28.597
963181AG1-167 GEN
Solar/Wind Harmer
2.496
3147133PAMPLIN
Solar/Wind Harmer
-0.082
971193AH1-056 GEN
Solar/Wind Harmer
16.449
942461AE2-259 GEN
Solar/Wind Harmer
3.824
3146926FARMVIL
Solar/Wind Harmer
-0.015
270018AE2-047 C O1
Solar/Wind Harmer
1.375
270197AD1-017 GEN1
Solar/Wind Harmer
1.676
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.834
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.53
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
270336AE1-100 GEN
Solar/Wind Harmer
1.564
961601AG1-000A GEN
Solar/Wind Harmer
5.252
315773AC2-141 GEN
Solar/Wind Helper
9.163
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.058
3145336SMITFLD
Solar/Wind Helper
0.148
3146456SLIGO L269
Solar/Wind Helper
0.359
316382AG1-145 C
Solar/Wind Helper
0.469
315244AE2-183_ST
50/50
19.115
963041AG1-153 GEN
50/50
16.957
3151541CLOVER2
50/50
9.268
3151611KERR 4
50/50
0.538
3151621KERR 5
50/50
0.538
3151631KERR 6
50/50
0.538
3151641KERR 7
50/50
0.538
971967AH1-528 GEN
Solar/Wind Harmer
125.223
970085AG2-068 GEN
Solar/Wind Harmer
41.62
970581AG2-369 GEN
Solar/Wind Harmer
35.794
3147173SINAI
Solar/Wind Harmer
-0.034
3147243WELCO
Solar/Wind Harmer
-0.021
316118AC1-105 GEN
Solar/Wind Harmer
2.295
970865AG2-541 GEN
Solar/Wind Harmer
11.917
316239AB2-077_GEN
Solar/Wind Harmer
0.868
316238AB2-078_GEN
Solar/Wind Harmer
0.868
971443AH1-215 GEN
Solar/Wind Harmer
5.428
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
21.145
970681AG2-440 GEN
Solar/Wind Harmer
16.916
946301AF1-294 GEN
Solar/Wind Harmer
6.823
961791AG1-021 GEN
Solar/Wind Harmer
3.328
270455AD2-022 GEN
Solar/Wind Harmer
4.701
270457AD2-023 GEN
Solar/Wind Harmer
2.384
315657AE1-056 GEN
Solar/Wind Harmer
9.869
316123AC1-075 GEN
Solar/Wind Harmer
2.789
970165AG2-112 GEN
Solar/Wind Harmer
2.455
970163AG2-111 GEN
Solar/Wind Harmer
2.342
970831AG2-522 GEN
Solar/Wind Harmer
9.813
970285AG2-188 GEN
Solar/Wind Harmer
15.354
971845AH1-439 GEN
Solar/Wind Harmer
8.535
270069AE2-166 C O1
Solar/Wind Harmer
2.415
319010AE1-072 C
Solar/Wind Helper
4.079
3143316POE
Solar/Wind Helper
1.407
316305AF2-043 C
Solar/Wind Helper
0.473
316369SG1_INVT
Solar/Wind Helper
1.664
957831AF2-077 GEN
Solar/Wind Helper
0.466
316132AB2-190 GEN1
Solar/Wind Helper
1.933
316349AD2-085 GEN
Solar/Wind Helper
1.523
313526AB2-022
Solar/Wind Helper
0.505
957601AF2-054 GEN
Solar/Wind Helper
0.438
3141873WAN 176
Solar/Wind Helper
0.065
315662AE1-191 GEN
Solar/Wind Helper
1.747
315666AE1-190 GEN
Solar/Wind Helper
0.437
316059AD1-063 C
Solar/Wind Helper
0.326
315839AE2-212 C
Solar/Wind Helper
0.457
316320Y1-086
Solar/Wind Helper
0.148
316156AD2-030 GEN
Solar/Wind Helper
0.492
316280AD1-041 GEN
Solar/Wind Helper
1.092
3142946ENON
Solar/Wind Helper
0.105
316484AD2-074 GEN
Solar/Wind Helper
0.607
316404AE1-155 C
Solar/Wind Helper
2.624
316435W1029_GEN3
Solar/Wind Helper
1.225
3146516WINFALL
Solar/Wind Helper
0.297
3141906WESTMOR
Solar/Wind Helper
0.115
3146626S HERTFORD
Solar/Wind Helper
0.28
316473AC1-191 GEN
Solar/Wind Helper
1.696
3145273HOLLAND
Solar/Wind Helper
0.188
966881AG1-559 GEN
Solar/Wind Helper
0.329
3146376EDENTON
Solar/Wind Helper
0.226
316388AE2-253 GEN
Solar/Wind Helper
1.397
3146456SLIGO L269
Solar/Wind Helper
0.359
316072AD1-144
Solar/Wind Helper
0.404
316246AF1-032 C
Solar/Wind Helper
0.402
316159AE1-175 C
Solar/Wind Helper
0.529
316381AD1-082 GEN
Solar/Wind Helper
1.758
316458AB2-190 GEN2
Solar/Wind Helper
1.933
3141766HARMONY
Solar/Wind Helper
0.065
3138133OCRAN
Solar/Wind Helper
0.193
3142433PROV 92
Solar/Wind Helper
1.275
3142543TWELFTH
Solar/Wind Helper
0.029
964211AG1-282 GEN
Solar/Wind Helper
0.412
3141726DUNNSVL
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.961
3146516WINFALL
Solar/Wind Helper
0.297
316337AD2-073 GEN
Solar/Wind Helper
0.448
3142416OLDCHRC
Solar/Wind Helper
0.759
3142416OLDCHRC
Solar/Wind Helper
0.291
3143526WINTERP
Solar/Wind Helper
1.499
3143226MDLTHAN
Solar/Wind Helper
0.284
315800Z1-036_GEN1
Solar/Wind Helper
1.411
3130156CHOWAN
Solar/Wind Helper
0.226
3141913WHIT STONE
Solar/Wind Helper
0.323
3146486SUNBURY
Solar/Wind Helper
0.323
3146486SUNBURY
Solar/Wind Helper
0.323
3138133OCRAN
Solar/Wind Helper
0.097
3143873LANEXA
Solar/Wind Helper
0.192
3141783LANCAST
Solar/Wind Helper
0.192
3141783LANCAST
Solar/Wind Helper
0.128
316321Z2-027
Solar/Wind Helper
0.487
3145176PASQUOTANK
Solar/Wind Helper
0.198
3141813NORNECK
Solar/Wind Helper
0.304
316312AB1-027
Solar/Wind Helper
0.556
316233AE1-074 FULL
Solar/Wind Helper
0.44
316223AC1-118
Solar/Wind Helper
0.438
316315AB2-025 C
Solar/Wind Helper
0.418
315611Z1-036_GEN2
Solar/Wind Helper
1.411
3130156CHOWAN
Solar/Wind Helper
0.226
3130156CHOWAN
Solar/Wind Helper
0.226
316433W1029_GEN2
Solar/Wind Helper
1.225
3146516WINFALL
Solar/Wind Helper
0.297
3146516WINFALL
Solar/Wind Helper
0.297
3146516WINFALL
Solar/Wind Helper
0.297
3143526WINTERP
Solar/Wind Helper
1.499
3146626S HERTFORD
Solar/Wind Helper
0.28
3146626S HERTFORD
Solar/Wind Helper
0.28
966871AG1-558 GEN
Solar/Wind Helper
0.374
3144356SAPONY
Solar/Wind Helper
0.492
316468AD1-105 GEN
Solar/Wind Helper
1.305
LAGNLTFEXP_LAGN->PJM
CLTF
14.626
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.161
TVALTFEXP_TVA->PJM
CLTF
7.294
CPLELTFEXP_CPLE->PJM
CLTF
19.708
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.004
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.554
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.081
MECLTFEXP_MEC->PJM
CLTF
7.343
SIGELTFEXP_SIGE->PJM
CLTF
0.22
NYPJM->LTFIMP_NY
CLTF
2.38
LGEELTFEXP_LGEE->PJM
CLTF
2.666
WECLTFEXP_WEC->PJM
CLTF
1.395
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113

Details for 8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 511T544_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T544_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.19 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5355.19
MW Contribution:25.22
Bus #Bus NameTypeMW Contribution
315242AE2-183_GT2
50/50
10.962
315241AE2-183_GT1
50/50
10.894
972185AH1-677 GEN
50/50
39.518
3151041BRUNSWICKG3
50/50
8.303
972187AH1-678 GEN
50/50
19.053
3152661PLYWOOD A
50/50
0.663
970535AG2-341 GEN
50/50
4.519
3144293JTRSVLE
50/50
0.79
3144293JTRSVLE
50/50
0.665
970933AG2-581 GEN
Solar/Wind Harmer
58.334
970099AG2-077 GEN
Solar/Wind Harmer
65.804
971741AH1-377 GEN
Solar/Wind Harmer
43.523
970301AG2-198 GEN
Solar/Wind Harmer
17.145
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.775
3151031BRUNSWICKG2
50/50
8.303
970413AG2-270 GEN
50/50
40.265
3151591KERR 2
50/50
0.532
3144293JTRSVLE
50/50
0.79
970917AG2-570 GEN
Solar/Wind Harmer
166.275
316478AD1-087 GEN
Solar/Wind Harmer
4.189
316486AD2-202 GEN
Solar/Wind Harmer
1.227
970909AG2-566 GEN
Solar/Wind Harmer
3.255
316248AF1-058 C
Solar/Wind Harmer
1.033
960061AF2-297 GEN
Solar/Wind Harmer
17.135
316283AC2-100 C
Solar/Wind Harmer
2.94
971683AH1-343 GEN
Solar/Wind Harmer
13.259
316131AB2-060 GEN
Solar/Wind Harmer
3.032
964241AG1-285 GEN
Solar/Wind Harmer
21.724
315785AD2-033 C
Solar/Wind Harmer
6.194
970257AG2-171 GEN
Solar/Wind Harmer
10.181
959311AF2-222 GEN
Solar/Wind Harmer
28.197
963181AG1-167 GEN
Solar/Wind Harmer
2.462
3147133PAMPLIN
Solar/Wind Harmer
-0.081
971193AH1-056 GEN
Solar/Wind Harmer
16.225
942461AE2-259 GEN
Solar/Wind Harmer
3.773
3146926FARMVIL
Solar/Wind Harmer
-0.014
270018AE2-047 C O1
Solar/Wind Harmer
1.363
270197AD1-017 GEN1
Solar/Wind Harmer
1.661
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.802
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.477
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
270336AE1-100 GEN
Solar/Wind Harmer
1.551
961601AG1-000A GEN
Solar/Wind Harmer
5.225
315773AC2-141 GEN
Solar/Wind Helper
8.525
315839AE2-212 C
Solar/Wind Helper
0.497
3144536CHRHLND
Solar/Wind Helper
0.05
3144873MCLAUGH
Solar/Wind Helper
0.008
3145336SMITFLD
Solar/Wind Helper
0.133
316382AG1-145 C
Solar/Wind Helper
0.441
316156AD2-030 GEN
Solar/Wind Helper
0.47
3142946ENON
Solar/Wind Helper
0.104
316280AD1-041 GEN
Solar/Wind Helper
1.046
3146456SLIGO L269
Solar/Wind Helper
0.308
316484AD2-074 GEN
Solar/Wind Helper
0.583
316404AE1-155 C
Solar/Wind Helper
2.523
315244AE2-183_ST
50/50
18.952
963041AG1-153 GEN
50/50
16.812
3151541CLOVER2
50/50
9.183
3151611KERR 4
50/50
0.532
3151621KERR 5
50/50
0.532
3151631KERR 6
50/50
0.532
3151641KERR 7
50/50
0.532
971967AH1-528 GEN
Solar/Wind Harmer
124.141
970085AG2-068 GEN
Solar/Wind Harmer
41.268
970581AG2-369 GEN
Solar/Wind Harmer
35.491
3147173SINAI
Solar/Wind Harmer
-0.034
3147243WELCO
Solar/Wind Harmer
-0.021
316118AC1-105 GEN
Solar/Wind Harmer
2.271
970865AG2-541 GEN
Solar/Wind Harmer
11.801
316239AB2-077_GEN
Solar/Wind Harmer
0.856
316238AB2-078_GEN
Solar/Wind Harmer
0.856
971443AH1-215 GEN
Solar/Wind Harmer
5.352
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
20.851
970681AG2-440 GEN
Solar/Wind Harmer
16.681
946301AF1-294 GEN
Solar/Wind Harmer
6.73
961791AG1-021 GEN
Solar/Wind Harmer
3.283
270455AD2-022 GEN
Solar/Wind Harmer
4.664
270457AD2-023 GEN
Solar/Wind Harmer
2.365
315657AE1-056 GEN
Solar/Wind Harmer
9.735
316123AC1-075 GEN
Solar/Wind Harmer
2.761
970165AG2-112 GEN
Solar/Wind Harmer
2.431
970163AG2-111 GEN
Solar/Wind Harmer
2.319
970831AG2-522 GEN
Solar/Wind Harmer
9.696
970285AG2-188 GEN
Solar/Wind Harmer
15.118
971845AH1-439 GEN
Solar/Wind Harmer
8.397
270069AE2-166 C O1
Solar/Wind Harmer
2.394
3143316POE
Solar/Wind Helper
1.57
316132AB2-190 GEN1
Solar/Wind Helper
1.893
316369SG1_INVT
Solar/Wind Helper
1.59
957831AF2-077 GEN
Solar/Wind Helper
0.437
316315AB2-025 C
Solar/Wind Helper
0.494
957601AF2-054 GEN
Solar/Wind Helper
0.418
3141873WAN 176
Solar/Wind Helper
0.062
315662AE1-191 GEN
Solar/Wind Helper
1.674
315666AE1-190 GEN
Solar/Wind Helper
0.419
3143873LANEXA
Solar/Wind Helper
0.186
316059AD1-063 C
Solar/Wind Helper
0.312
3141913WHIT STONE
Solar/Wind Helper
0.309
3138133OCRAN
Solar/Wind Helper
0.093
3141783LANCAST
Solar/Wind Helper
0.184
3141783LANCAST
Solar/Wind Helper
0.123
319010AE1-072 C
Solar/Wind Helper
3.5
316349AD2-085 GEN
Solar/Wind Helper
1.396
316222AC1-221 GEN
Solar/Wind Harmer
3.182
962561AG1-105 GEN
Solar/Wind Harmer
17.536
939181AE1-148 GEN
Solar/Wind Harmer
16.186
313527AB2-043 GEN
Solar/Wind Harmer
4.576
970323AG2-213 GEN
Solar/Wind Harmer
13.574
971775AH1-396 GEN
Solar/Wind Harmer
1.933
316034AC1-036 C
Solar/Wind Harmer
0.503
958211AF2-115 GEN
Solar/Wind Harmer
4.103
963191AG1-168 GEN
Solar/Wind Harmer
2.462
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
14.918
270013AE1-250 PV
Solar/Wind Harmer
2.815
3146776BUCKING
Solar/Wind Harmer
-0.06
3146776BUCKING
Solar/Wind Harmer
-0.005
316217AC1-145 GEN
Solar/Wind Harmer
2.37
316197AC1-042 GEN
Solar/Wind Harmer
1.797
942671AE2-283 GEN
Solar/Wind Harmer
4.838
316263AC1-034 GEN
Solar/Wind Harmer
6.29
961601AG1-000A GEN
Solar/Wind Harmer
5.16
316240AF1-291 C
Solar/Wind Helper
0.471
316036AC1-147 C
Solar/Wind Helper
0.511
316236AE1-162_GEN
Solar/Wind Helper
0.447
316316AC1-027 C
Solar/Wind Helper
0.524
3142956BIRDNECK
Solar/Wind Helper
0.223
316033AB2-134 GEN
Solar/Wind Helper
1.137
315697AD1-025 GEN
Solar/Wind Helper
3.779
316185AD1-033 GEN
Solar/Wind Helper
1.551
3145506HICKORY
Solar/Wind Helper
1.298
3145506HICKORY
Solar/Wind Helper
0.779
3145506HICKORY
Solar/Wind Helper
0.195
3144356SAPONY
Solar/Wind Helper
0.581
316339AD2-160 GEN
Solar/Wind Helper
1.201
316018AA1-139 ULT2
Solar/Wind Helper
1.346
316017AA1-139 ULT1
Solar/Wind Helper
1.43
3142946ENON
Solar/Wind Helper
0.031
3137176SLIGO L2192
Solar/Wind Helper
1.229
3130086AYDLETT
Solar/Wind Helper
1.219
316487AF1-042 GEN
Solar/Wind Helper
0.305
316075AC2-137 C
Solar/Wind Helper
0.459
316077AC2-138 C
Solar/Wind Helper
0.276
3143526WINTERP
Solar/Wind Helper
1.519
3146386ELIZ CT
Solar/Wind Helper
0.283
966871AG1-558 GEN
Solar/Wind Helper
0.376
316468AD1-105 GEN
Solar/Wind Helper
1.308
316431W1029_GEN1
Solar/Wind Helper
1.037
316433W1029_GEN2
Solar/Wind Helper
1.037
3146516WINFALL
Solar/Wind Helper
0.251
3146516WINFALL
Solar/Wind Helper
0.251
3146516WINFALL
Solar/Wind Helper
0.251
3146626S HERTFORD
Solar/Wind Helper
0.236
3146626S HERTFORD
Solar/Wind Helper
0.236
316305AF2-043 C
Solar/Wind Helper
0.402
3141813NORNECK
Solar/Wind Helper
0.293
316233AE1-074 FULL
Solar/Wind Helper
0.446
316312AB1-027
Solar/Wind Helper
0.55
313526AB2-022
Solar/Wind Helper
0.431
316223AC1-118
Solar/Wind Helper
0.424
3146486SUNBURY
Solar/Wind Helper
0.274
3146486SUNBURY
Solar/Wind Helper
0.274
316321Z2-027
Solar/Wind Helper
0.414
3145176PASQUOTANK
Solar/Wind Helper
0.168
316320Y1-086
Solar/Wind Helper
0.126
316473AC1-191 GEN
Solar/Wind Helper
1.704
3141906WESTMOR
Solar/Wind Helper
0.111
316435W1029_GEN3
Solar/Wind Helper
1.037
3146516WINFALL
Solar/Wind Helper
0.251
966881AG1-559 GEN
Solar/Wind Helper
0.328
3146626S HERTFORD
Solar/Wind Helper
0.236
315243AE2-183_GT3
50/50
10.962
3151051BRUNSWICKS1
50/50
17.232
3151021BRUNSWICKG1
50/50
8.303
971451AH1-221 GEN
50/50
25.218
3151531CLOVER1
50/50
9.227
3151601KERR 3
50/50
0.532
3151581KERR 1
50/50
0.19
3144293JTRSVLE
50/50
0.79
971629AH1-314 GEN
50/50
17.731
3151561HALLBR1
50/50
0.363
970919AG2-571 GEN
Solar/Wind Harmer
21.047
970087AG2-069 GEN
Solar/Wind Harmer
61.902
957481AF2-042 GEN
Solar/Wind Harmer
164.509
315693AD1-088 GEN
Solar/Wind Harmer
24.007
962491AG1-098 GEN
Solar/Wind Harmer
31.634
315687AD1-152 GEN
Solar/Wind Harmer
5.265
316003AC1-222 GEN
Solar/Wind Harmer
3.162
970401AG2-262 GEN
Solar/Wind Harmer
2.07
316237AB2-079_GEN
Solar/Wind Harmer
0.856
970685AG2-442 GEN
Solar/Wind Harmer
23.354
963171AG1-166 GEN
Solar/Wind Harmer
3.283
971563AH1-280 GEN
Solar/Wind Harmer
3.283
3146926FARMVIL
Solar/Wind Harmer
-0.014
971065AG2-659 GEN
Solar/Wind Harmer
11.094
316129AC1-054 GEN
Solar/Wind Harmer
1.827
970223AG2-152 GEN
Solar/Wind Harmer
17.059
270016AE1-250 BESS
Solar/Wind Harmer
2.815
3147123OTTER R
Solar/Wind Harmer
-0.01
270574AD1-017 GEN2
Solar/Wind Harmer
5.528
316322AB2-045
Solar/Wind Harmer
0.506
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.477
270030AE2-140 GEN
Solar/Wind Harmer
19.567
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.809
316049AB1-081 GEN
Solar/Wind Harmer
1.448
3142053HEARTS
Solar/Wind Harmer
0.158
316294AC1-161 GEN
Solar/Wind Helper
7.244
316381AD1-082 GEN
Solar/Wind Helper
1.747
316375AC2-012 GEN
Solar/Wind Helper
0.879
3145336SMITFLD
Solar/Wind Helper
1.331
316458AB2-190 GEN2
Solar/Wind Helper
1.893
316159AE1-175 C
Solar/Wind Helper
0.497
316388AE2-253 GEN
Solar/Wind Helper
1.201
3142433PROV 92
Solar/Wind Helper
1.254
3142543TWELFTH
Solar/Wind Helper
0.03
3141766HARMONY
Solar/Wind Helper
0.062
3146456SLIGO L269
Solar/Wind Helper
0.308
3138133OCRAN
Solar/Wind Helper
0.185
316072AD1-144
Solar/Wind Helper
0.35
316246AF1-032 C
Solar/Wind Helper
0.342
964211AG1-282 GEN
Solar/Wind Helper
0.397
3141726DUNNSVL
Solar/Wind Helper
1.179
3143526WINTERP
Solar/Wind Helper
1.519
3142416OLDCHRC
Solar/Wind Helper
0.752
3143226MDLTHAN
Solar/Wind Helper
0.289
3142416OLDCHRC
Solar/Wind Helper
0.288
316337AD2-073 GEN
Solar/Wind Helper
0.434
3146516WINFALL
Solar/Wind Helper
0.813
3146516WINFALL
Solar/Wind Helper
0.251
LAGNLTFEXP_LAGN->PJM
CLTF
14.499
CBM South 2LTFEXP_CBM-S2->PJM
CBM
43.842
TVALTFEXP_TVA->PJM
CLTF
7.231
CPLELTFEXP_CPLE->PJM
CLTF
19.58
CBM West 2LTFEXP_CBM-W2->PJM
CBM
77.279
CBM West 1LTFEXP_CBM-W1->PJM
CBM
48.979
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.858
MECLTFEXP_MEC->PJM
CLTF
7.267
SIGELTFEXP_SIGE->PJM
CLTF
0.218
NYPJM->LTFIMP_NY
CLTF
2.38
LGEELTFEXP_LGEE->PJM
CLTF
2.637
WECLTFEXP_WEC->PJM
CLTF
1.38
AG2-052LTFEXP_AG2-052->PJM
LTF
0.074
AH1-155LTFEXP_AH1-155->PJM
LTF
0.111

Details for 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8SEPTA-8SURRY 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56372_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.87 %
Rating:2931.0 MVA
Rating Type:C
MVA to Mitigate:3044.37
MW Contribution:10.28
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
3.386
970413AG2-270 GEN
50/50
18.7
3151101ELIZAR3
50/50
18.555
315773AC2-141 GEN
Solar/Wind Harmer
27.544
970917AG2-570 GEN
Solar/Wind Harmer
68.686
944581AF1-123 GEN
Solar/Wind Harmer
109.673
944601AF1-125 GEN
Solar/Wind Harmer
107.961
316478AD1-087 GEN
Solar/Wind Harmer
1.946
316486AD2-202 GEN
Solar/Wind Harmer
0.57
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146456SLIGO L269
Solar/Wind Harmer
-0.02
971153AH1-033 GEN
Solar/Wind Harmer
2.454
316320Y1-086
Solar/Wind Harmer
1.083
3144536CHRHLND
Solar/Wind Harmer
-0.003
316248AF1-058 C
Solar/Wind Harmer
0.522
960061AF2-297 GEN
Solar/Wind Harmer
8.669
316131AB2-060 GEN
Solar/Wind Harmer
1.825
964241AG1-285 GEN
Solar/Wind Harmer
12.927
3146516WINFALL
Solar/Wind Harmer
-0.016
3146626S HERTFORD
Solar/Wind Harmer
-0.016
970909AG2-566 GEN
Solar/Wind Harmer
1.549
3147043LAWRENC
Solar/Wind Harmer
-0.01
3146376EDENTON
Solar/Wind Harmer
-0.016
315785AD2-033 C
Solar/Wind Harmer
3.613
316435W1029_GEN3
Solar/Wind Harmer
2.886
966621AG1-532 GEN
Solar/Wind Harmer
0.323
316283AC2-100 C
Solar/Wind Harmer
1.496
313506AB2-031 GEN
Solar/Wind Harmer
1.271
316365GEN2_N
Solar/Wind Harmer
1.06
315614AA2-178 GEN
Solar/Wind Harmer
1.696
970257AG2-171 GEN
Solar/Wind Harmer
5.892
959311AF2-222 GEN
Solar/Wind Harmer
16.228
971683AH1-343 GEN
Solar/Wind Harmer
6.691
3145543BTLEBRO
Solar/Wind Harmer
-0.015
3145543BTLEBRO
Solar/Wind Harmer
-0.015
3145796HORNRTN
Solar/Wind Harmer
-0.062
3145796HORNRTN
Solar/Wind Harmer
-0.015
315724AD1-057 GEN
Solar/Wind Harmer
0.892
3138543CONSLDL
Solar/Wind Harmer
-0.01
3146233WITAKRS
Solar/Wind Harmer
0.324
3146233WITAKRS
Solar/Wind Harmer
-0.01
961601AG1-000A GEN
Solar/Wind Harmer
6.167
316327AA2-057 GEN
Solar/Wind Harmer
1.564
971157AH1-035 GEN
Solar/Wind Harmer
1.935
315737AD1-076 GEN
Solar/Wind Harmer
2.934
3142666NORTHAMPTON
Solar/Wind Harmer
-0.015
3146073TAR RVR
Solar/Wind Harmer
-0.015
3146083TARBORO
Solar/Wind Harmer
-0.015
316210AC1-098 GEN
Solar/Wind Harmer
2.411
3145963POPLR C
Solar/Wind Harmer
-0.015
3145933PARMELE
Solar/Wind Harmer
-0.015
966801AG1-551 GEN
Solar/Wind Harmer
1.9
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3146206CASHIE
Solar/Wind Harmer
-0.015
3146263WOODLND
Solar/Wind Harmer
-0.015
316317KELFORD C
Solar/Wind Harmer
0.709
3145823KELFORD
Solar/Wind Harmer
-0.015
316463AE2-346 GEN
Solar/Wind Harmer
0.239
316140AB2-099
Solar/Wind Harmer
0.1
962331AG1-082 GEN
Solar/Wind Harmer
1.848
3156021HOLLOMANSOL
Solar/Wind Harmer
1.987
3146173TUNIS
Solar/Wind Harmer
-0.015
963181AG1-167 GEN
Solar/Wind Harmer
1.368
3144293JTRSVLE
Adder
0.414
957521AF2-046 GEN
Solar/Wind Harmer
11.482
961681AG1-008 GEN
Solar/Wind Harmer
11.482
3145893MURPHYS
Solar/Wind Harmer
0.101
3145893MURPHYS
Solar/Wind Harmer
-0.014
3156081AA2-088 GEN
Solar/Wind Harmer
4.63
3147133PAMPLIN
Solar/Wind Harmer
-0.044
971193AH1-056 GEN
Solar/Wind Harmer
8.887
942461AE2-259 GEN
Solar/Wind Harmer
1.975
3145273HOLLAND
Solar/Wind Harmer
-0.01
316382AG1-145 C
Solar/Wind Helper
0.451
316156AD2-030 GEN
Solar/Wind Helper
0.379
316280AD1-041 GEN
Solar/Wind Helper
0.819
316484AD2-074 GEN
Solar/Wind Helper
0.458
316404AE1-155 C
Solar/Wind Helper
1.965
315243AE2-183_GT3
50/50
4.325
3151051BRUNSWICKS1
50/50
7.027
3151021BRUNSWICKG1
50/50
3.386
971451AH1-221 GEN
50/50
10.283
3151531CLOVER1
50/50
4.285
316294AC1-161 GEN
Solar/Wind Harmer
21.297
940641AE2-051 GEN
Solar/Wind Harmer
36.033
970919AG2-571 GEN
Solar/Wind Harmer
8.694
970087AG2-069 GEN
Solar/Wind Harmer
25.61
944591AF1-124 GEN
Solar/Wind Harmer
110.068
957481AF2-042 GEN
Solar/Wind Harmer
75.055
939411AE1-173 GEN
Solar/Wind Harmer
119.429
315693AD1-088 GEN
Solar/Wind Harmer
11.114
962491AG1-098 GEN
Solar/Wind Harmer
14.661
315687AD1-152 GEN
Solar/Wind Harmer
2.497
316375AC2-012 GEN
Solar/Wind Harmer
7.148
3150981CHESPKA
Adder
2.295
316388AE2-253 GEN
Solar/Wind Harmer
1.388
3146456SLIGO L269
Solar/Wind Harmer
-0.02
971065AG2-659 GEN
Solar/Wind Harmer
8.623
970401AG2-262 GEN
Solar/Wind Harmer
1.122
316129AC1-054 GEN
Solar/Wind Harmer
1.501
316237AB2-079_GEN
Solar/Wind Harmer
0.514
3146516WINFALL
Solar/Wind Harmer
-0.053
3146516WINFALL
Solar/Wind Harmer
-0.016
316003AC1-222 GEN
Solar/Wind Harmer
1.598
3147043LAWRENC
Adder
1.308
315800Z1-036_GEN1
Solar/Wind Harmer
4.001
971795AH1-408 GEN
Solar/Wind Harmer
12.102
3130156CHOWAN
Solar/Wind Harmer
-0.016
960081AF2-299 GEN
Solar/Wind Harmer
1.79
316023GEN1_S
Solar/Wind Harmer
1.06
3145663CRESWEL
Solar/Wind Harmer
-0.044
971163AH1-040 GEN
Solar/Wind Harmer
14.733
3145783HORNRTN
Solar/Wind Harmer
-0.016
316190AA2-174 GEN
Solar/Wind Harmer
0.191
3145543BTLEBRO
Solar/Wind Harmer
-0.015
3145543BTLEBRO
Solar/Wind Harmer
-0.012
316359AB2-059 GEN
Solar/Wind Harmer
2.091
316049AB1-081 GEN
Solar/Wind Harmer
1.673
3142053HEARTS
Solar/Wind Harmer
0.182
316011AB1-132 GEN
Solar/Wind Harmer
3.244
962571AG1-106 GEN
Solar/Wind Harmer
2.229
3145796HORNRTN
Solar/Wind Harmer
-0.051
3145796HORNRTN
Solar/Wind Harmer
-0.015
315722AD1-056 GEN
Solar/Wind Harmer
1.622
3146233WITAKRS
Solar/Wind Harmer
-0.061
961671AG1-007 GEN
Solar/Wind Harmer
0.194
3146083TARBORO
Solar/Wind Harmer
-0.015
3145493TOT1
Solar/Wind Harmer
0.456
316212AC1-099_GEN
Solar/Wind Harmer
1.34
3145963POPLR C
Solar/Wind Harmer
-0.015
316174AB2-169 GEN
Solar/Wind Harmer
2.357
316494AC1-189 GEN
Solar/Wind Harmer
1.643
3146293MARTNCO
Solar/Wind Harmer
0.094
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3146206CASHIE
Solar/Wind Harmer
-0.015
315244AE2-183_ST
50/50
7.478
963041AG1-153 GEN
50/50
6.855
3151541CLOVER2
50/50
4.265
3151081ELIZAR1
50/50
18.321
941031AE2-094 GEN
Solar/Wind Harmer
57.43
944011AF1-069 GEN
Solar/Wind Harmer
17.995
970673AG2-436 GEN
Solar/Wind Harmer
62.661
970673AG2-436 GEN
Solar/Wind Harmer
31.727
971967AH1-528 GEN
Solar/Wind Harmer
54.485
970085AG2-068 GEN
Solar/Wind Harmer
17.073
970581AG2-369 GEN
Solar/Wind Harmer
14.683
3151091ELIZAR2
Adder
16.966
3152611GOSPORTB
Adder
2.331
3152621GOSPORTC
Adder
1.978
3152601GOSPORTA
Adder
1.825
957871AF2-081 GEN
Solar/Wind Harmer
10.216
319010AE1-072 C
Solar/Wind Harmer
4.045
3146406KITTY HAWK
Solar/Wind Harmer
0.017
313526AB2-022
Solar/Wind Harmer
0.498
316321Z2-027
Solar/Wind Harmer
0.479
3146396TANGLEW
Solar/Wind Harmer
0.327
971547AH1-271 GEN
Solar/Wind Harmer
3.788
970685AG2-442 GEN
Solar/Wind Harmer
13.246
3146263WOODLND
Solar/Wind Harmer
-0.015
3145823KELFORD
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.015
3146173TUNIS
Solar/Wind Harmer
-0.015
963171AG1-166 GEN
Solar/Wind Harmer
1.825
971563AH1-280 GEN
Solar/Wind Harmer
1.825
3144293JTRSVLE
Adder
0.414
3145893MURPHYS
Solar/Wind Harmer
-0.058
3145893MURPHYS
Solar/Wind Harmer
0.431
316159AE1-175 C
Solar/Wind Helper
0.509
3141766HARMONY
Solar/Wind Helper
0.049
3138133OCRAN
Solar/Wind Helper
0.148
964211AG1-282 GEN
Solar/Wind Helper
0.305
3141726DUNNSVL
Solar/Wind Helper
0.905
970533AG2-339 GEN
50/50
24.232
970531AG2-338 GEN
50/50
9.693
315242AE2-183_GT2
50/50
4.325
315241AE2-183_GT1
50/50
4.299
972185AH1-677 GEN
50/50
15.592
3151041BRUNSWICKG3
50/50
3.386
972187AH1-678 GEN
50/50
7.769
970933AG2-581 GEN
Solar/Wind Harmer
25.842
970099AG2-077 GEN
Solar/Wind Harmer
30.022
316185AD1-033 GEN
Solar/Wind Harmer
2.257
3145506HICKORY
Solar/Wind Harmer
-0.084
3145506HICKORY
Solar/Wind Harmer
-0.051
3145506HICKORY
Solar/Wind Harmer
-0.013
3142956BIRDNECK
Solar/Wind Harmer
1.119
316316AC1-027 C
Solar/Wind Harmer
0.638
316036AC1-147 C
Solar/Wind Harmer
0.557
3150991CHESPKB
Adder
1.926
3150991CHESPKB
Adder
1.879
316339AD2-160 GEN
Solar/Wind Harmer
1.388
316018AA1-139 ULT2
Solar/Wind Harmer
1.75
316017AA1-139 ULT1
Solar/Wind Harmer
1.653
3137176SLIGO L2192
Solar/Wind Harmer
-0.08
3146456SLIGO L269
Solar/Wind Harmer
2.378
3130086AYDLETT
Solar/Wind Harmer
-0.079
3146386ELIZ CT
Solar/Wind Harmer
-0.018
939181AE1-148 GEN
Solar/Wind Harmer
9.967
971741AH1-377 GEN
Solar/Wind Harmer
20.543
3146843MT LREL
Solar/Wind Harmer
-0.017
3146843MT LREL
Solar/Wind Harmer
-0.017
964791AG1-342 GEN
Solar/Wind Harmer
3.674
962561AG1-105 GEN
Solar/Wind Harmer
9.657
313527AB2-043 GEN
Solar/Wind Harmer
2.762
3146516WINFALL
Solar/Wind Harmer
-0.016
3146516WINFALL
Solar/Wind Harmer
-0.016
3146516WINFALL
Solar/Wind Harmer
-0.016
3146626S HERTFORD
Solar/Wind Harmer
-0.016
3146626S HERTFORD
Solar/Wind Harmer
-0.016
970301AG2-198 GEN
Solar/Wind Harmer
8.157
3146376EDENTON
Solar/Wind Harmer
0.475
3146376EDENTON
Solar/Wind Harmer
0.475
3144356SAPONY
Solar/Wind Harmer
0.557
316222AC1-221 GEN
Solar/Wind Harmer
1.617
316431W1029_GEN1
Solar/Wind Harmer
2.886
316433W1029_GEN2
Solar/Wind Harmer
2.886
316181AB2-040 GEN
Solar/Wind Harmer
2.206
970323AG2-213 GEN
Solar/Wind Harmer
7.857
971775AH1-396 GEN
Solar/Wind Harmer
1.119
3145593CAROLNA
Solar/Wind Harmer
-0.016
3145593CAROLNA
Solar/Wind Harmer
-0.016
966811AG1-552 GEN
Solar/Wind Harmer
1.767
3145593CAROLNA
Solar/Wind Harmer
0.13
316034AC1-036 C
Solar/Wind Harmer
0.291
3145783HORNRTN
Solar/Wind Harmer
1.86
3145783HORNRTN
Solar/Wind Harmer
1.488
3145783HORNRTN
Solar/Wind Harmer
0.465
3145783HORNRTN
Solar/Wind Harmer
0.186
316426AA2-053 GEN
Solar/Wind Harmer
1.572
316263AC1-034 GEN
Solar/Wind Harmer
7.27
3145796HORNRTN
Solar/Wind Harmer
-0.046
961601AG1-000A GEN
Solar/Wind Harmer
6.09
316274AC1-208 GEN
Solar/Wind Harmer
1.672
3142666NORTHAMPTON
Solar/Wind Harmer
-0.015
3142666NORTHAMPTON
Solar/Wind Harmer
-0.015
3142666NORTHAMPTON
Solar/Wind Harmer
-0.015
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3145493TOT1
Solar/Wind Harmer
0.238
3145453TOT5
Solar/Wind Harmer
0.143
3145603CNETO
Solar/Wind Harmer
0.095
316065AD1-022 GEN
Solar/Wind Harmer
7.628
3145933PARMELE
Solar/Wind Harmer
-0.03
3145933PARMELE
Solar/Wind Harmer
-0.015
3146173TUNIS
Solar/Wind Harmer
-0.015
3146173TUNIS
Solar/Wind Harmer
-0.015
958211AF2-115 GEN
Solar/Wind Harmer
2.281
963191AG1-168 GEN
Solar/Wind Harmer
1.368
3144293JTRSVLE
Adder
0.414
3144293JTRSVLE
Adder
0.348
3145893MURPHYS
Solar/Wind Harmer
0.405
3145893MURPHYS
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.014
3147133PAMPLIN
Solar/Wind Harmer
-0.011
315742AE1-103 GEN
Solar/Wind Harmer
1.368
316487AF1-042 GEN
Solar/Wind Helper
0.24
316077AC2-138 C
Solar/Wind Helper
0.212
3145176PASQUOTANK
Solar/Wind Harmer
-0.011
3147173SINAI
Solar/Wind Harmer
-0.017
3147243WELCO
Solar/Wind Harmer
-0.011
316118AC1-105 GEN
Solar/Wind Harmer
1.188
316239AB2-077_GEN
Solar/Wind Harmer
0.514
316238AB2-078_GEN
Solar/Wind Harmer
0.514
970831AG2-522 GEN
Solar/Wind Harmer
8.491
315611Z1-036_GEN2
Solar/Wind Harmer
4.001
3130156CHOWAN
Solar/Wind Harmer
-0.016
3130156CHOWAN
Solar/Wind Harmer
-0.016
316315AB2-025 C
Solar/Wind Harmer
0.431
315814AE2-033 C
Solar/Wind Harmer
14.87
946281AF1-292 GEN
Solar/Wind Harmer
0.356
316087AB2-174 GEN
Solar/Wind Harmer
2.26
971443AH1-215 GEN
Solar/Wind Harmer
3.103
3137643SOCKMAN
Solar/Wind Harmer
-0.063
315816AE2-034 GEN
Solar/Wind Harmer
1.272
3144303KENBRDG
Solar/Wind Harmer
-0.013
315652AC1-086 GEN
Solar/Wind Harmer
17.441
3145796HORNRTN
Solar/Wind Harmer
-0.049
3145796HORNRTN
Solar/Wind Harmer
-0.006
316319Z2-044 C
Solar/Wind Harmer
0.856
3130546PLYMOUTH
Solar/Wind Harmer
-0.015
315732AD1-074 GEN1
Solar/Wind Harmer
3.122
315733AD1-074 GEN2
Solar/Wind Harmer
3.122
315735AD1-075 GEN1
Solar/Wind Harmer
1.561
3145573BETHELC
Solar/Wind Harmer
-0.015
3145573BETHELC
Solar/Wind Harmer
-0.015
316420AA1-050 GEN
Solar/Wind Harmer
1.751
957861AF2-080 GEN
Solar/Wind Harmer
6.681
3146033SCOT NK
Solar/Wind Harmer
-0.061
315607AA1-063A GEN
Solar/Wind Harmer
1.534
316005AA1-067
Solar/Wind Harmer
0.307
3145746EVERETS
Solar/Wind Harmer
-0.06
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
970181AG2-120 GEN
Solar/Wind Harmer
1.989
3146206CASHIE
Solar/Wind Harmer
-0.015
970601AG2-382 GEN
Solar/Wind Harmer
6.629
970683AG2-441 GEN
Solar/Wind Harmer
11.827
970681AG2-440 GEN
Solar/Wind Harmer
9.461
3146043SEABORD
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.03
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145513AHOSKIE
Solar/Wind Harmer
0.129
961941AG1-037 GEN
Solar/Wind Harmer
0.111
3145513AHOSKIE
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
5.947
946301AF1-294 GEN
Solar/Wind Harmer
3.74
961791AG1-021 GEN
Solar/Wind Harmer
1.825
316318V4-068
Solar/Wind Harmer
0.362
3145893MURPHYS
Solar/Wind Harmer
-0.039
3145893MURPHYS
Solar/Wind Harmer
-0.014
3146486SUNBURY
Solar/Wind Harmer
-0.014
3146486SUNBURY
Solar/Wind Harmer
-0.014
965291AG1-394 GEN
Solar/Wind Harmer
1.275
315657AE1-056 GEN
Solar/Wind Harmer
5.332
270455AD2-022 GEN
Solar/Wind Harmer
2.402
270457AD2-023 GEN
Solar/Wind Harmer
1.218
316123AC1-075 GEN
Solar/Wind Harmer
1.387
970165AG2-112 GEN
Solar/Wind Harmer
1.221
970163AG2-111 GEN
Solar/Wind Harmer
1.165
957831AF2-077 GEN
Solar/Wind Helper
0.39
957601AF2-054 GEN
Solar/Wind Helper
0.337
3141873WAN 176
Solar/Wind Helper
0.05
3141913WHIT STONE
Solar/Wind Helper
0.247
316059AD1-063 C
Solar/Wind Helper
0.249
3138133OCRAN
Solar/Wind Helper
0.074
3141783LANCAST
Solar/Wind Helper
0.146
3141783LANCAST
Solar/Wind Helper
0.098
315662AE1-191 GEN
Solar/Wind Helper
1.31
315666AE1-190 GEN
Solar/Wind Helper
0.327
3141813NORNECK
Solar/Wind Helper
0.225
LAGNLTFEXP_LAGN->PJM
CLTF
7.136
CBM South 2LTFEXP_CBM-S2->PJM
CBM
22.765
TVALTFEXP_TVA->PJM
CLTF
3.554
CPLELTFEXP_CPLE->PJM
CLTF
10.589
CBM West 2LTFEXP_CBM-W2->PJM
CBM
37.328
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.129
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.134
MECLTFEXP_MEC->PJM
CLTF
3.403
SIGELTFEXP_SIGE->PJM
CLTF
0.101
NYPJM->LTFIMP_NY
CLTF
1.354
LGEELTFEXP_LGEE->PJM
CLTF
1.211
WECLTFEXP_WEC->PJM
CLTF
0.63

Details for 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8SEPTA-8SURRY 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.05 %
Rating:2931.0 MVA
Rating Type:C
MVA to Mitigate:2961.86
MW Contribution:9.86
Bus #Bus NameTypeMW Contribution
970533AG2-339 GEN
50/50
23.192
970531AG2-338 GEN
50/50
9.277
315242AE2-183_GT2
50/50
4.144
315241AE2-183_GT1
50/50
4.119
972185AH1-677 GEN
50/50
14.94
3151041BRUNSWICKG3
50/50
3.245
972187AH1-678 GEN
50/50
7.448
970933AG2-581 GEN
Solar/Wind Harmer
24.816
970099AG2-077 GEN
Solar/Wind Harmer
28.974
316185AD1-033 GEN
Solar/Wind Harmer
2.226
3145506HICKORY
Solar/Wind Harmer
-0.083
3145506HICKORY
Solar/Wind Harmer
-0.05
3145506HICKORY
Solar/Wind Harmer
-0.012
3142956BIRDNECK
Solar/Wind Harmer
1.104
316316AC1-027 C
Solar/Wind Harmer
0.63
316036AC1-147 C
Solar/Wind Harmer
0.55
3150991CHESPKB
Adder
1.902
3150991CHESPKB
Adder
1.857
316339AD2-160 GEN
Solar/Wind Harmer
1.371
316018AA1-139 ULT2
Solar/Wind Harmer
1.729
316017AA1-139 ULT1
Solar/Wind Harmer
1.633
3137176SLIGO L2192
Solar/Wind Harmer
-0.079
3146456SLIGO L269
Solar/Wind Harmer
2.349
3130086AYDLETT
Solar/Wind Harmer
-0.078
3144356SAPONY
Solar/Wind Harmer
0.685
3146386ELIZ CT
Solar/Wind Harmer
-0.018
939181AE1-148 GEN
Solar/Wind Harmer
9.927
971741AH1-377 GEN
Solar/Wind Harmer
20.052
316181AB2-040 GEN
Solar/Wind Harmer
2.37
313527AB2-043 GEN
Solar/Wind Harmer
2.758
962561AG1-105 GEN
Solar/Wind Harmer
9.546
3146843MT LREL
Solar/Wind Harmer
-0.017
3146843MT LREL
Solar/Wind Harmer
-0.017
964791AG1-342 GEN
Solar/Wind Harmer
3.625
3145796HORNRTN
Solar/Wind Harmer
-0.049
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.016
3145593CAROLNA
Solar/Wind Harmer
-0.016
966811AG1-552 GEN
Solar/Wind Harmer
1.856
315244AE2-183_ST
50/50
7.165
963041AG1-153 GEN
50/50
6.572
3151541CLOVER2
50/50
4.126
3151081ELIZAR1
50/50
18.089
941031AE2-094 GEN
Solar/Wind Harmer
54.965
944011AF1-069 GEN
Solar/Wind Harmer
17.222
970673AG2-436 GEN
Solar/Wind Harmer
60.015
970673AG2-436 GEN
Solar/Wind Harmer
30.387
971967AH1-528 GEN
Solar/Wind Harmer
52.234
970085AG2-068 GEN
Solar/Wind Harmer
16.391
970581AG2-369 GEN
Solar/Wind Harmer
14.096
3151091ELIZAR2
Adder
16.751
3152611GOSPORTB
Adder
2.303
3152621GOSPORTC
Adder
1.954
3152601GOSPORTA
Adder
1.803
957871AF2-081 GEN
Solar/Wind Harmer
10.089
319010AE1-072 C
Solar/Wind Harmer
3.997
3146406KITTY HAWK
Solar/Wind Harmer
0.016
316315AB2-025 C
Solar/Wind Harmer
0.53
315814AE2-033 C
Solar/Wind Harmer
18.209
313526AB2-022
Solar/Wind Harmer
0.493
316321Z2-027
Solar/Wind Harmer
0.475
3146396TANGLEW
Solar/Wind Harmer
0.324
3145176PASQUOTANK
Solar/Wind Harmer
-0.011
946281AF1-292 GEN
Solar/Wind Harmer
0.39
970831AG2-522 GEN
Solar/Wind Harmer
8.629
316087AB2-174 GEN
Solar/Wind Harmer
2.442
316239AB2-077_GEN
Solar/Wind Harmer
0.513
316238AB2-078_GEN
Solar/Wind Harmer
0.513
316118AC1-105 GEN
Solar/Wind Harmer
1.167
3147173SINAI
Solar/Wind Harmer
-0.017
3147243WELCO
Solar/Wind Harmer
-0.011
3137643SOCKMAN
Solar/Wind Harmer
-0.066
315652AC1-086 GEN
Solar/Wind Harmer
18.802
3145796HORNRTN
Solar/Wind Harmer
-0.053
3145796HORNRTN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
3.991
3130156CHOWAN
Solar/Wind Harmer
-0.016
3130156CHOWAN
Solar/Wind Harmer
-0.016
316319Z2-044 C
Solar/Wind Harmer
0.879
315607AA1-063A GEN
Solar/Wind Harmer
1.601
315816AE2-034 GEN
Solar/Wind Harmer
1.28
3146043SEABORD
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
3.096
3146033SCOT NK
Solar/Wind Harmer
-0.063
3145573BETHELC
Solar/Wind Harmer
-0.016
3145573BETHELC
Solar/Wind Harmer
-0.016
3144303KENBRDG
Solar/Wind Harmer
-0.013
316420AA1-050 GEN
Solar/Wind Harmer
1.787
3130546PLYMOUTH
Solar/Wind Harmer
-0.016
315732AD1-074 GEN1
Solar/Wind Harmer
3.159
315733AD1-074 GEN2
Solar/Wind Harmer
3.159
315735AD1-075 GEN1
Solar/Wind Harmer
1.58
957861AF2-080 GEN
Solar/Wind Harmer
6.812
3146206CASHIE
Solar/Wind Harmer
-0.015
970601AG2-382 GEN
Solar/Wind Harmer
6.746
316005AA1-067
Solar/Wind Harmer
0.312
3145746EVERETS
Solar/Wind Harmer
-0.061
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
970181AG2-120 GEN
Solar/Wind Harmer
2.022
3145683EARLEYS
Solar/Wind Harmer
-0.03
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145513AHOSKIE
Solar/Wind Harmer
0.133
961941AG1-037 GEN
Solar/Wind Harmer
0.115
3145513AHOSKIE
Solar/Wind Harmer
-0.015
970683AG2-441 GEN
Solar/Wind Harmer
11.796
970681AG2-440 GEN
Solar/Wind Harmer
9.436
316318V4-068
Solar/Wind Harmer
0.374
3145893MURPHYS
Solar/Wind Harmer
-0.04
3145893MURPHYS
Solar/Wind Harmer
-0.015
965291AG1-394 GEN
Solar/Wind Harmer
1.319
946301AF1-294 GEN
Solar/Wind Harmer
3.729
961791AG1-021 GEN
Solar/Wind Harmer
1.819
3145593CAROLNA
Solar/Wind Harmer
0.137
3145783HORNRTN
Solar/Wind Harmer
1.949
3145783HORNRTN
Solar/Wind Harmer
1.559
3145783HORNRTN
Solar/Wind Harmer
0.487
3145783HORNRTN
Solar/Wind Harmer
0.195
3146516WINFALL
Solar/Wind Harmer
-0.016
3146516WINFALL
Solar/Wind Harmer
-0.016
3146516WINFALL
Solar/Wind Harmer
-0.016
316426AA2-053 GEN
Solar/Wind Harmer
1.645
3146626S HERTFORD
Solar/Wind Harmer
-0.016
3146626S HERTFORD
Solar/Wind Harmer
-0.016
316274AC1-208 GEN
Solar/Wind Harmer
1.732
3146376EDENTON
Solar/Wind Harmer
0.476
3146376EDENTON
Solar/Wind Harmer
0.476
970301AG2-198 GEN
Solar/Wind Harmer
7.988
961601AG1-000A GEN
Solar/Wind Harmer
6.245
316263AC1-034 GEN
Solar/Wind Harmer
7.445
316431W1029_GEN1
Solar/Wind Harmer
2.865
316433W1029_GEN2
Solar/Wind Harmer
2.865
3145493TOT1
Solar/Wind Harmer
0.243
3145453TOT5
Solar/Wind Harmer
0.146
3145603CNETO
Solar/Wind Harmer
0.097
970323AG2-213 GEN
Solar/Wind Harmer
7.839
971775AH1-396 GEN
Solar/Wind Harmer
1.116
316034AC1-036 C
Solar/Wind Harmer
0.291
316222AC1-221 GEN
Solar/Wind Harmer
1.581
316065AD1-022 GEN
Solar/Wind Harmer
7.746
3145933PARMELE
Solar/Wind Harmer
-0.031
3145933PARMELE
Solar/Wind Harmer
-0.015
3146173TUNIS
Solar/Wind Harmer
-0.015
3146173TUNIS
Solar/Wind Harmer
-0.015
3145893MURPHYS
Solar/Wind Harmer
0.419
3145893MURPHYS
Solar/Wind Harmer
-0.027
958211AF2-115 GEN
Solar/Wind Harmer
2.274
963191AG1-168 GEN
Solar/Wind Harmer
1.364
3151031BRUNSWICKG2
50/50
3.245
970413AG2-270 GEN
50/50
18.093
3151101ELIZAR3
50/50
18.321
315773AC2-141 GEN
Solar/Wind Harmer
27.318
970917AG2-570 GEN
Solar/Wind Harmer
65.93
944581AF1-123 GEN
Solar/Wind Harmer
107.997
944601AF1-125 GEN
Solar/Wind Harmer
106.312
316478AD1-087 GEN
Solar/Wind Harmer
1.883
316486AD2-202 GEN
Solar/Wind Harmer
0.551
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146456SLIGO L269
Solar/Wind Harmer
-0.02
971153AH1-033 GEN
Solar/Wind Harmer
2.424
316320Y1-086
Solar/Wind Harmer
1.072
3144536CHRHLND
Solar/Wind Harmer
-0.003
316365GEN2_N
Solar/Wind Harmer
1.198
966621AG1-532 GEN
Solar/Wind Harmer
0.354
3147043LAWRENC
Solar/Wind Harmer
-0.01
313506AB2-031 GEN
Solar/Wind Harmer
1.365
316248AF1-058 C
Solar/Wind Harmer
0.511
960061AF2-297 GEN
Solar/Wind Harmer
8.482
316131AB2-060 GEN
Solar/Wind Harmer
1.822
3145796HORNRTN
Solar/Wind Harmer
-0.066
3145796HORNRTN
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
964241AG1-285 GEN
Solar/Wind Harmer
12.904
3146516WINFALL
Solar/Wind Harmer
-0.016
3146626S HERTFORD
Solar/Wind Harmer
-0.016
315724AD1-057 GEN
Solar/Wind Harmer
0.933
3146376EDENTON
Solar/Wind Harmer
-0.016
970909AG2-566 GEN
Solar/Wind Harmer
1.517
316327AA2-057 GEN
Solar/Wind Harmer
1.611
3146233WITAKRS
Solar/Wind Harmer
0.333
3146233WITAKRS
Solar/Wind Harmer
-0.011
3138543CONSLDL
Solar/Wind Harmer
-0.01
315785AD2-033 C
Solar/Wind Harmer
3.605
315243AE2-183_GT3
50/50
4.144
3151051BRUNSWICKS1
50/50
6.736
3151021BRUNSWICKG1
50/50
3.245
971451AH1-221 GEN
50/50
9.857
3151531CLOVER1
50/50
4.146
316294AC1-161 GEN
Solar/Wind Harmer
21.122
940641AE2-051 GEN
Solar/Wind Harmer
34.85
970919AG2-571 GEN
Solar/Wind Harmer
8.346
970087AG2-069 GEN
Solar/Wind Harmer
24.586
944591AF1-124 GEN
Solar/Wind Harmer
108.386
957481AF2-042 GEN
Solar/Wind Harmer
72.436
939411AE1-173 GEN
Solar/Wind Harmer
114.333
315693AD1-088 GEN
Solar/Wind Harmer
10.761
962491AG1-098 GEN
Solar/Wind Harmer
14.201
316375AC2-012 GEN
Solar/Wind Harmer
7.061
3150981CHESPKA
Adder
2.267
316388AE2-253 GEN
Solar/Wind Harmer
1.371
315687AD1-152 GEN
Solar/Wind Harmer
2.422
3146456SLIGO L269
Solar/Wind Harmer
-0.02
316023GEN1_S
Solar/Wind Harmer
1.198
960081AF2-299 GEN
Solar/Wind Harmer
1.961
971065AG2-659 GEN
Solar/Wind Harmer
8.708
316129AC1-054 GEN
Solar/Wind Harmer
1.52
971795AH1-408 GEN
Solar/Wind Harmer
13
3147043LAWRENC
Adder
1.392
316237AB2-079_GEN
Solar/Wind Harmer
0.513
970401AG2-262 GEN
Solar/Wind Harmer
1.108
316011AB1-132 GEN
Solar/Wind Harmer
3.497
962571AG1-106 GEN
Solar/Wind Harmer
2.402
3145796HORNRTN
Solar/Wind Harmer
-0.054
3145796HORNRTN
Solar/Wind Harmer
-0.017
3145783HORNRTN
Solar/Wind Harmer
-0.016
3146516WINFALL
Solar/Wind Harmer
-0.053
3146516WINFALL
Solar/Wind Harmer
-0.016
316190AA2-174 GEN
Solar/Wind Harmer
0.2
315722AD1-056 GEN
Solar/Wind Harmer
1.696
315800Z1-036_GEN1
Solar/Wind Harmer
3.991
3130156CHOWAN
Solar/Wind Harmer
-0.016
316003AC1-222 GEN
Solar/Wind Harmer
1.563
3146233WITAKRS
Solar/Wind Harmer
-0.063
316359AB2-059 GEN
Solar/Wind Harmer
2.141
316049AB1-081 GEN
Solar/Wind Harmer
1.714
3142053HEARTS
Solar/Wind Harmer
0.187
316212AC1-099_GEN
Solar/Wind Harmer
1.384
3145543BTLEBRO
Solar/Wind Harmer
-0.016
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145663CRESWEL
Solar/Wind Harmer
-0.044
971163AH1-040 GEN
Solar/Wind Harmer
14.826
961671AG1-007 GEN
Solar/Wind Harmer
0.199
3146083TARBORO
Solar/Wind Harmer
-0.016
3145493TOT1
Solar/Wind Harmer
0.466
3146263WOODLND
Solar/Wind Harmer
-0.016
316494AC1-189 GEN
Solar/Wind Harmer
1.675
3145963POPLR C
Solar/Wind Harmer
-0.015
3145823KELFORD
Solar/Wind Harmer
-0.015
316174AB2-169 GEN
Solar/Wind Harmer
2.391
3146293MARTNCO
Solar/Wind Harmer
0.096
3146206CASHIE
Solar/Wind Harmer
-0.015
971547AH1-271 GEN
Solar/Wind Harmer
3.855
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.015
3146173TUNIS
Solar/Wind Harmer
-0.015
970685AG2-442 GEN
Solar/Wind Harmer
13.211
3145893MURPHYS
Solar/Wind Harmer
-0.06
3145893MURPHYS
Solar/Wind Harmer
0.445
3146486SUNBURY
Solar/Wind Harmer
-0.014
3146486SUNBURY
Solar/Wind Harmer
-0.014
970865AG2-541 GEN
Solar/Wind Harmer
5.823
315657AE1-056 GEN
Solar/Wind Harmer
5.314
3143316POE
Solar/Wind Harmer
-0.054
270455AD2-022 GEN
Solar/Wind Harmer
2.354
270457AD2-023 GEN
Solar/Wind Harmer
1.194
957831AF2-077 GEN
Solar/Wind Helper
0.384
957601AF2-054 GEN
Solar/Wind Helper
0.326
3141873WAN 176
Solar/Wind Helper
0.049
3141913WHIT STONE
Solar/Wind Helper
0.239
3138133OCRAN
Solar/Wind Helper
0.072
316059AD1-063 C
Solar/Wind Helper
0.24
3141783LANCAST
Solar/Wind Helper
0.142
3141783LANCAST
Solar/Wind Helper
0.094
315662AE1-191 GEN
Solar/Wind Helper
1.261
315666AE1-190 GEN
Solar/Wind Helper
0.315
963171AG1-166 GEN
Solar/Wind Harmer
1.819
971563AH1-280 GEN
Solar/Wind Harmer
1.819
3144293JTRSVLE
Adder
0.412
316159AE1-175 C
Solar/Wind Helper
0.502
3138133OCRAN
Solar/Wind Helper
0.143
3141766HARMONY
Solar/Wind Helper
0.048
961601AG1-000A GEN
Solar/Wind Harmer
6.324
316210AC1-098 GEN
Solar/Wind Harmer
2.492
3145543BTLEBRO
Solar/Wind Harmer
-0.016
3145543BTLEBRO
Solar/Wind Harmer
-0.016
315614AA2-178 GEN
Solar/Wind Harmer
1.706
316435W1029_GEN3
Solar/Wind Harmer
2.865
3146073TAR RVR
Solar/Wind Harmer
-0.016
3146083TARBORO
Solar/Wind Harmer
-0.016
970257AG2-171 GEN
Solar/Wind Harmer
5.879
971157AH1-035 GEN
Solar/Wind Harmer
1.956
3146263WOODLND
Solar/Wind Harmer
-0.016
315737AD1-076 GEN
Solar/Wind Harmer
2.968
316283AC2-100 C
Solar/Wind Harmer
1.463
3145963POPLR C
Solar/Wind Harmer
-0.015
316317KELFORD C
Solar/Wind Harmer
0.731
3145823KELFORD
Solar/Wind Harmer
-0.015
959311AF2-222 GEN
Solar/Wind Harmer
16.19
3145933PARMELE
Solar/Wind Harmer
-0.015
966801AG1-551 GEN
Solar/Wind Harmer
1.929
3146206CASHIE
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
316463AE2-346 GEN
Solar/Wind Harmer
0.247
316140AB2-099
Solar/Wind Harmer
0.103
962331AG1-082 GEN
Solar/Wind Harmer
1.905
971683AH1-343 GEN
Solar/Wind Harmer
6.55
3146173TUNIS
Solar/Wind Harmer
-0.015
3156021HOLLOMANSOL
Solar/Wind Harmer
2.039
957521AF2-046 GEN
Solar/Wind Harmer
11.856
961681AG1-008 GEN
Solar/Wind Harmer
11.856
3145893MURPHYS
Solar/Wind Harmer
0.105
3145893MURPHYS
Solar/Wind Harmer
-0.015
3156081AA2-088 GEN
Solar/Wind Harmer
4.785
963181AG1-167 GEN
Solar/Wind Harmer
1.364
3144293JTRSVLE
Adder
0.412
3147133PAMPLIN
Solar/Wind Harmer
-0.044
971193AH1-056 GEN
Solar/Wind Harmer
8.857
942461AE2-259 GEN
Solar/Wind Harmer
1.967
3145273HOLLAND
Solar/Wind Harmer
-0.01
316382AG1-145 C
Solar/Wind Helper
0.445
316156AD2-030 GEN
Solar/Wind Helper
0.367
316280AD1-041 GEN
Solar/Wind Helper
0.788
316484AD2-074 GEN
Solar/Wind Helper
0.442
316404AE1-155 C
Solar/Wind Helper
1.895
3144293JTRSVLE
Adder
0.412
3144293JTRSVLE
Adder
0.347
3147133PAMPLIN
Solar/Wind Harmer
-0.014
3147133PAMPLIN
Solar/Wind Harmer
-0.011
315742AE1-103 GEN
Solar/Wind Harmer
1.397
316487AF1-042 GEN
Solar/Wind Helper
0.231
LAGNLTFEXP_LAGN->PJM
CLTF
6.991
CBM South 2LTFEXP_CBM-S2->PJM
CBM
22.32
TVALTFEXP_TVA->PJM
CLTF
3.482
CPLELTFEXP_CPLE->PJM
CLTF
10.401
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.559
CBM West 1LTFEXP_CBM-W1->PJM
CBM
21.641
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.888
MECLTFEXP_MEC->PJM
CLTF
3.331
SIGELTFEXP_SIGE->PJM
CLTF
0.099
NYPJM->LTFIMP_NY
CLTF
1.344
LGEELTFEXP_LGEE->PJM
CLTF
1.186
WECLTFEXP_WEC->PJM
CLTF
0.616

Details for 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8SEPTA-8SURRY 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.05 %
Rating:2931.0 MVA
Rating Type:C
MVA to Mitigate:2961.86
MW Contribution:9.86
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
4.144
3151051BRUNSWICKS1
50/50
6.736
3151021BRUNSWICKG1
50/50
3.245
971451AH1-221 GEN
50/50
9.857
970533AG2-339 GEN
50/50
23.192
970531AG2-338 GEN
50/50
9.277
315242AE2-183_GT2
50/50
4.144
315241AE2-183_GT1
50/50
4.119
972185AH1-677 GEN
50/50
14.94
3151041BRUNSWICKG3
50/50
3.245
972187AH1-678 GEN
50/50
7.448
970933AG2-581 GEN
Solar/Wind Harmer
24.816
970099AG2-077 GEN
Solar/Wind Harmer
28.974
316185AD1-033 GEN
Solar/Wind Harmer
2.226
3151531CLOVER1
50/50
4.146
316294AC1-161 GEN
Solar/Wind Harmer
21.122
940641AE2-051 GEN
Solar/Wind Harmer
34.85
970919AG2-571 GEN
Solar/Wind Harmer
8.346
970087AG2-069 GEN
Solar/Wind Harmer
24.586
944591AF1-124 GEN
Solar/Wind Harmer
108.386
957481AF2-042 GEN
Solar/Wind Harmer
72.436
939411AE1-173 GEN
Solar/Wind Harmer
114.333
315693AD1-088 GEN
Solar/Wind Harmer
10.761
962491AG1-098 GEN
Solar/Wind Harmer
14.201
316375AC2-012 GEN
Solar/Wind Harmer
7.061
3150981CHESPKA
Adder
2.267
316388AE2-253 GEN
Solar/Wind Harmer
1.371
315687AD1-152 GEN
Solar/Wind Harmer
2.422
3146456SLIGO L269
Solar/Wind Harmer
-0.02
316023GEN1_S
Solar/Wind Harmer
1.198
960081AF2-299 GEN
Solar/Wind Harmer
1.961
971065AG2-659 GEN
Solar/Wind Harmer
8.708
316129AC1-054 GEN
Solar/Wind Harmer
1.52
971795AH1-408 GEN
Solar/Wind Harmer
13
3147043LAWRENC
Adder
1.392
316237AB2-079_GEN
Solar/Wind Harmer
0.513
970401AG2-262 GEN
Solar/Wind Harmer
1.108
316011AB1-132 GEN
Solar/Wind Harmer
3.497
962571AG1-106 GEN
Solar/Wind Harmer
2.402
3145796HORNRTN
Solar/Wind Harmer
-0.054
3145796HORNRTN
Solar/Wind Harmer
-0.017
3145783HORNRTN
Solar/Wind Harmer
-0.016
3146516WINFALL
Solar/Wind Harmer
-0.053
3146516WINFALL
Solar/Wind Harmer
-0.016
316190AA2-174 GEN
Solar/Wind Harmer
0.2
315722AD1-056 GEN
Solar/Wind Harmer
1.696
315800Z1-036_GEN1
Solar/Wind Harmer
3.991
3130156CHOWAN
Solar/Wind Harmer
-0.016
316003AC1-222 GEN
Solar/Wind Harmer
1.563
3146233WITAKRS
Solar/Wind Harmer
-0.063
316359AB2-059 GEN
Solar/Wind Harmer
2.141
316049AB1-081 GEN
Solar/Wind Harmer
1.714
3142053HEARTS
Solar/Wind Harmer
0.187
316212AC1-099_GEN
Solar/Wind Harmer
1.384
3145543BTLEBRO
Solar/Wind Harmer
-0.016
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145663CRESWEL
Solar/Wind Harmer
-0.044
971163AH1-040 GEN
Solar/Wind Harmer
14.826
961671AG1-007 GEN
Solar/Wind Harmer
0.199
3146083TARBORO
Solar/Wind Harmer
-0.016
3145493TOT1
Solar/Wind Harmer
0.466
3146263WOODLND
Solar/Wind Harmer
-0.016
316494AC1-189 GEN
Solar/Wind Harmer
1.675
3145963POPLR C
Solar/Wind Harmer
-0.015
3145823KELFORD
Solar/Wind Harmer
-0.015
316174AB2-169 GEN
Solar/Wind Harmer
2.391
3146293MARTNCO
Solar/Wind Harmer
0.096
3146206CASHIE
Solar/Wind Harmer
-0.015
971547AH1-271 GEN
Solar/Wind Harmer
3.855
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.015
3146173TUNIS
Solar/Wind Harmer
-0.015
970685AG2-442 GEN
Solar/Wind Harmer
13.211
3145893MURPHYS
Solar/Wind Harmer
-0.06
3145893MURPHYS
Solar/Wind Harmer
0.445
963171AG1-166 GEN
Solar/Wind Harmer
1.819
971563AH1-280 GEN
Solar/Wind Harmer
1.819
3144293JTRSVLE
Adder
0.412
316159AE1-175 C
Solar/Wind Helper
0.502
3138133OCRAN
Solar/Wind Helper
0.143
3141766HARMONY
Solar/Wind Helper
0.048
315244AE2-183_ST
50/50
7.165
963041AG1-153 GEN
50/50
6.572
3151541CLOVER2
50/50
4.126
3151081ELIZAR1
50/50
18.089
941031AE2-094 GEN
Solar/Wind Harmer
54.965
944011AF1-069 GEN
Solar/Wind Harmer
17.222
970673AG2-436 GEN
Solar/Wind Harmer
60.015
970673AG2-436 GEN
Solar/Wind Harmer
30.387
971967AH1-528 GEN
Solar/Wind Harmer
52.234
970085AG2-068 GEN
Solar/Wind Harmer
16.391
970581AG2-369 GEN
Solar/Wind Harmer
14.096
3151091ELIZAR2
Adder
16.751
3152611GOSPORTB
Adder
2.303
3152621GOSPORTC
Adder
1.954
3152601GOSPORTA
Adder
1.803
957871AF2-081 GEN
Solar/Wind Harmer
10.089
319010AE1-072 C
Solar/Wind Harmer
3.997
3146406KITTY HAWK
Solar/Wind Harmer
0.016
316315AB2-025 C
Solar/Wind Harmer
0.53
315814AE2-033 C
Solar/Wind Harmer
18.209
313526AB2-022
Solar/Wind Harmer
0.493
316321Z2-027
Solar/Wind Harmer
0.475
3146396TANGLEW
Solar/Wind Harmer
0.324
3145176PASQUOTANK
Solar/Wind Harmer
-0.011
946281AF1-292 GEN
Solar/Wind Harmer
0.39
970831AG2-522 GEN
Solar/Wind Harmer
8.629
316087AB2-174 GEN
Solar/Wind Harmer
2.442
316239AB2-077_GEN
Solar/Wind Harmer
0.513
316238AB2-078_GEN
Solar/Wind Harmer
0.513
316118AC1-105 GEN
Solar/Wind Harmer
1.167
3147173SINAI
Solar/Wind Harmer
-0.017
3147243WELCO
Solar/Wind Harmer
-0.011
3137643SOCKMAN
Solar/Wind Harmer
-0.066
315652AC1-086 GEN
Solar/Wind Harmer
18.802
3145796HORNRTN
Solar/Wind Harmer
-0.053
3145796HORNRTN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
3.991
3130156CHOWAN
Solar/Wind Harmer
-0.016
3130156CHOWAN
Solar/Wind Harmer
-0.016
316319Z2-044 C
Solar/Wind Harmer
0.879
315607AA1-063A GEN
Solar/Wind Harmer
1.601
315816AE2-034 GEN
Solar/Wind Harmer
1.28
3146043SEABORD
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
3.096
3146033SCOT NK
Solar/Wind Harmer
-0.063
3145573BETHELC
Solar/Wind Harmer
-0.016
3145573BETHELC
Solar/Wind Harmer
-0.016
3144303KENBRDG
Solar/Wind Harmer
-0.013
316420AA1-050 GEN
Solar/Wind Harmer
1.787
3130546PLYMOUTH
Solar/Wind Harmer
-0.016
315732AD1-074 GEN1
Solar/Wind Harmer
3.159
315733AD1-074 GEN2
Solar/Wind Harmer
3.159
315735AD1-075 GEN1
Solar/Wind Harmer
1.58
957861AF2-080 GEN
Solar/Wind Harmer
6.812
3146206CASHIE
Solar/Wind Harmer
-0.015
970601AG2-382 GEN
Solar/Wind Harmer
6.746
316005AA1-067
Solar/Wind Harmer
0.312
3145746EVERETS
Solar/Wind Harmer
-0.061
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
970181AG2-120 GEN
Solar/Wind Harmer
2.022
3145683EARLEYS
Solar/Wind Harmer
-0.03
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145513AHOSKIE
Solar/Wind Harmer
0.133
961941AG1-037 GEN
Solar/Wind Harmer
0.115
3145513AHOSKIE
Solar/Wind Harmer
-0.015
970683AG2-441 GEN
Solar/Wind Harmer
11.796
970681AG2-440 GEN
Solar/Wind Harmer
9.436
316318V4-068
Solar/Wind Harmer
0.374
3145893MURPHYS
Solar/Wind Harmer
-0.04
3145893MURPHYS
Solar/Wind Harmer
-0.015
965291AG1-394 GEN
Solar/Wind Harmer
1.319
946301AF1-294 GEN
Solar/Wind Harmer
3.729
961791AG1-021 GEN
Solar/Wind Harmer
1.819
3146486SUNBURY
Solar/Wind Harmer
-0.014
3146486SUNBURY
Solar/Wind Harmer
-0.014
970865AG2-541 GEN
Solar/Wind Harmer
5.823
315657AE1-056 GEN
Solar/Wind Harmer
5.314
3143316POE
Solar/Wind Harmer
-0.054
270455AD2-022 GEN
Solar/Wind Harmer
2.354
270457AD2-023 GEN
Solar/Wind Harmer
1.194
957831AF2-077 GEN
Solar/Wind Helper
0.384
957601AF2-054 GEN
Solar/Wind Helper
0.326
3141873WAN 176
Solar/Wind Helper
0.049
3141913WHIT STONE
Solar/Wind Helper
0.239
3138133OCRAN
Solar/Wind Helper
0.072
316059AD1-063 C
Solar/Wind Helper
0.24
3141783LANCAST
Solar/Wind Helper
0.142
3141783LANCAST
Solar/Wind Helper
0.094
315662AE1-191 GEN
Solar/Wind Helper
1.261
315666AE1-190 GEN
Solar/Wind Helper
0.315
3145506HICKORY
Solar/Wind Harmer
-0.083
3145506HICKORY
Solar/Wind Harmer
-0.05
3145506HICKORY
Solar/Wind Harmer
-0.012
3142956BIRDNECK
Solar/Wind Harmer
1.104
316316AC1-027 C
Solar/Wind Harmer
0.63
316036AC1-147 C
Solar/Wind Harmer
0.55
3150991CHESPKB
Adder
1.902
3150991CHESPKB
Adder
1.857
316339AD2-160 GEN
Solar/Wind Harmer
1.371
316018AA1-139 ULT2
Solar/Wind Harmer
1.729
316017AA1-139 ULT1
Solar/Wind Harmer
1.633
3137176SLIGO L2192
Solar/Wind Harmer
-0.079
3146456SLIGO L269
Solar/Wind Harmer
2.349
3130086AYDLETT
Solar/Wind Harmer
-0.078
3144356SAPONY
Solar/Wind Harmer
0.685
3146386ELIZ CT
Solar/Wind Harmer
-0.018
939181AE1-148 GEN
Solar/Wind Harmer
9.927
971741AH1-377 GEN
Solar/Wind Harmer
20.052
316181AB2-040 GEN
Solar/Wind Harmer
2.37
313527AB2-043 GEN
Solar/Wind Harmer
2.758
962561AG1-105 GEN
Solar/Wind Harmer
9.546
3146843MT LREL
Solar/Wind Harmer
-0.017
3146843MT LREL
Solar/Wind Harmer
-0.017
964791AG1-342 GEN
Solar/Wind Harmer
3.625
3145796HORNRTN
Solar/Wind Harmer
-0.049
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.016
3145593CAROLNA
Solar/Wind Harmer
-0.016
966811AG1-552 GEN
Solar/Wind Harmer
1.856
3145593CAROLNA
Solar/Wind Harmer
0.137
3145783HORNRTN
Solar/Wind Harmer
1.949
3145783HORNRTN
Solar/Wind Harmer
1.559
3145783HORNRTN
Solar/Wind Harmer
0.487
3145783HORNRTN
Solar/Wind Harmer
0.195
3146516WINFALL
Solar/Wind Harmer
-0.016
3146516WINFALL
Solar/Wind Harmer
-0.016
3146516WINFALL
Solar/Wind Harmer
-0.016
316426AA2-053 GEN
Solar/Wind Harmer
1.645
3146626S HERTFORD
Solar/Wind Harmer
-0.016
3146626S HERTFORD
Solar/Wind Harmer
-0.016
316274AC1-208 GEN
Solar/Wind Harmer
1.732
3146376EDENTON
Solar/Wind Harmer
0.476
3146376EDENTON
Solar/Wind Harmer
0.476
970301AG2-198 GEN
Solar/Wind Harmer
7.988
961601AG1-000A GEN
Solar/Wind Harmer
6.245
316263AC1-034 GEN
Solar/Wind Harmer
7.445
316431W1029_GEN1
Solar/Wind Harmer
2.865
316433W1029_GEN2
Solar/Wind Harmer
2.865
3145493TOT1
Solar/Wind Harmer
0.243
3145453TOT5
Solar/Wind Harmer
0.146
3145603CNETO
Solar/Wind Harmer
0.097
970323AG2-213 GEN
Solar/Wind Harmer
7.839
971775AH1-396 GEN
Solar/Wind Harmer
1.116
316034AC1-036 C
Solar/Wind Harmer
0.291
316222AC1-221 GEN
Solar/Wind Harmer
1.581
316065AD1-022 GEN
Solar/Wind Harmer
7.746
3145933PARMELE
Solar/Wind Harmer
-0.031
3145933PARMELE
Solar/Wind Harmer
-0.015
3146173TUNIS
Solar/Wind Harmer
-0.015
3146173TUNIS
Solar/Wind Harmer
-0.015
3145893MURPHYS
Solar/Wind Harmer
0.419
3145893MURPHYS
Solar/Wind Harmer
-0.027
958211AF2-115 GEN
Solar/Wind Harmer
2.274
963191AG1-168 GEN
Solar/Wind Harmer
1.364
3144293JTRSVLE
Adder
0.412
3144293JTRSVLE
Adder
0.347
3147133PAMPLIN
Solar/Wind Harmer
-0.014
3147133PAMPLIN
Solar/Wind Harmer
-0.011
315742AE1-103 GEN
Solar/Wind Harmer
1.397
316487AF1-042 GEN
Solar/Wind Helper
0.231
3151031BRUNSWICKG2
50/50
3.245
970413AG2-270 GEN
50/50
18.093
3151101ELIZAR3
50/50
18.321
315773AC2-141 GEN
Solar/Wind Harmer
27.318
970917AG2-570 GEN
Solar/Wind Harmer
65.93
944581AF1-123 GEN
Solar/Wind Harmer
107.997
944601AF1-125 GEN
Solar/Wind Harmer
106.312
316478AD1-087 GEN
Solar/Wind Harmer
1.883
316486AD2-202 GEN
Solar/Wind Harmer
0.551
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146456SLIGO L269
Solar/Wind Harmer
-0.02
971153AH1-033 GEN
Solar/Wind Harmer
2.424
316320Y1-086
Solar/Wind Harmer
1.072
3144536CHRHLND
Solar/Wind Harmer
-0.003
316365GEN2_N
Solar/Wind Harmer
1.198
966621AG1-532 GEN
Solar/Wind Harmer
0.354
3147043LAWRENC
Solar/Wind Harmer
-0.01
313506AB2-031 GEN
Solar/Wind Harmer
1.365
316248AF1-058 C
Solar/Wind Harmer
0.511
960061AF2-297 GEN
Solar/Wind Harmer
8.482
316131AB2-060 GEN
Solar/Wind Harmer
1.822
3145796HORNRTN
Solar/Wind Harmer
-0.066
3145796HORNRTN
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
964241AG1-285 GEN
Solar/Wind Harmer
12.904
3146516WINFALL
Solar/Wind Harmer
-0.016
3146626S HERTFORD
Solar/Wind Harmer
-0.016
315724AD1-057 GEN
Solar/Wind Harmer
0.933
3146376EDENTON
Solar/Wind Harmer
-0.016
970909AG2-566 GEN
Solar/Wind Harmer
1.517
316327AA2-057 GEN
Solar/Wind Harmer
1.611
3146233WITAKRS
Solar/Wind Harmer
0.333
3146233WITAKRS
Solar/Wind Harmer
-0.011
3138543CONSLDL
Solar/Wind Harmer
-0.01
315785AD2-033 C
Solar/Wind Harmer
3.605
961601AG1-000A GEN
Solar/Wind Harmer
6.324
316210AC1-098 GEN
Solar/Wind Harmer
2.492
3145543BTLEBRO
Solar/Wind Harmer
-0.016
3145543BTLEBRO
Solar/Wind Harmer
-0.016
315614AA2-178 GEN
Solar/Wind Harmer
1.706
316435W1029_GEN3
Solar/Wind Harmer
2.865
3146073TAR RVR
Solar/Wind Harmer
-0.016
3146083TARBORO
Solar/Wind Harmer
-0.016
970257AG2-171 GEN
Solar/Wind Harmer
5.879
971157AH1-035 GEN
Solar/Wind Harmer
1.956
3146263WOODLND
Solar/Wind Harmer
-0.016
315737AD1-076 GEN
Solar/Wind Harmer
2.968
316283AC2-100 C
Solar/Wind Harmer
1.463
3145963POPLR C
Solar/Wind Harmer
-0.015
316317KELFORD C
Solar/Wind Harmer
0.731
3145823KELFORD
Solar/Wind Harmer
-0.015
959311AF2-222 GEN
Solar/Wind Harmer
16.19
3145933PARMELE
Solar/Wind Harmer
-0.015
966801AG1-551 GEN
Solar/Wind Harmer
1.929
3146206CASHIE
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
316463AE2-346 GEN
Solar/Wind Harmer
0.247
316140AB2-099
Solar/Wind Harmer
0.103
962331AG1-082 GEN
Solar/Wind Harmer
1.905
971683AH1-343 GEN
Solar/Wind Harmer
6.55
3146173TUNIS
Solar/Wind Harmer
-0.015
3156021HOLLOMANSOL
Solar/Wind Harmer
2.039
957521AF2-046 GEN
Solar/Wind Harmer
11.856
961681AG1-008 GEN
Solar/Wind Harmer
11.856
3145893MURPHYS
Solar/Wind Harmer
0.105
3145893MURPHYS
Solar/Wind Harmer
-0.015
3156081AA2-088 GEN
Solar/Wind Harmer
4.785
963181AG1-167 GEN
Solar/Wind Harmer
1.364
3144293JTRSVLE
Adder
0.412
3147133PAMPLIN
Solar/Wind Harmer
-0.044
971193AH1-056 GEN
Solar/Wind Harmer
8.857
942461AE2-259 GEN
Solar/Wind Harmer
1.967
3145273HOLLAND
Solar/Wind Harmer
-0.01
316382AG1-145 C
Solar/Wind Helper
0.445
316156AD2-030 GEN
Solar/Wind Helper
0.367
316280AD1-041 GEN
Solar/Wind Helper
0.788
316484AD2-074 GEN
Solar/Wind Helper
0.442
316404AE1-155 C
Solar/Wind Helper
1.895
LAGNLTFEXP_LAGN->PJM
CLTF
6.991
CBM South 2LTFEXP_CBM-S2->PJM
CBM
22.32
TVALTFEXP_TVA->PJM
CLTF
3.482
CPLELTFEXP_CPLE->PJM
CLTF
10.401
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.559
CBM West 1LTFEXP_CBM-W1->PJM
CBM
21.641
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.888
MECLTFEXP_MEC->PJM
CLTF
3.331
SIGELTFEXP_SIGE->PJM
CLTF
0.099
NYPJM->LTFIMP_NY
CLTF
1.344
LGEELTFEXP_LGEE->PJM
CLTF
1.186
WECLTFEXP_WEC->PJM
CLTF
0.616

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 574T575_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 574T575_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:179.37 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:7067.14
MW Contribution:10.54
Bus #Bus NameTypeMW Contribution
971133AH1-012 GEN
50/50
8.748
970533AG2-339 GEN
50/50
24.369
970531AG2-338 GEN
50/50
9.748
315242AE2-183_GT2
50/50
4.407
315241AE2-183_GT1
50/50
4.38
972185AH1-677 GEN
50/50
15.889
3151041BRUNSWICKG3
50/50
3.471
972187AH1-678 GEN
50/50
7.965
3151731LOISA B
50/50
17.992
3151721LOISA A
50/50
17.899
316447AC1-158 HLD
Solar/Wind Harmer
18.712
971223AH1-071 GEN
Solar/Wind Harmer
4.156
3143526WINTERP
Solar/Wind Harmer
-0.157
970933AG2-581 GEN
Solar/Wind Harmer
27.317
3144356SAPONY
Solar/Wind Harmer
0.989
966001AG1-469 GEN
Solar/Wind Harmer
0.532
316185AD1-033 GEN
Solar/Wind Harmer
2.919
3142956BIRDNECK
Solar/Wind Harmer
1.484
316316AC1-027 C
Solar/Wind Harmer
0.849
316036AC1-147 C
Solar/Wind Harmer
0.746
3150991CHESPKB
Adder
2.576
3150991CHESPKB
Adder
2.515
3145506HICKORY
Solar/Wind Harmer
-0.11
3145506HICKORY
Solar/Wind Harmer
-0.066
3145506HICKORY
Solar/Wind Harmer
-0.016
316339AD2-160 GEN
Solar/Wind Harmer
1.858
316018AA1-139 ULT2
Solar/Wind Harmer
2.359
316017AA1-139 ULT1
Solar/Wind Harmer
2.228
3137176SLIGO L2192
Solar/Wind Harmer
-0.109
3146456SLIGO L269
Solar/Wind Harmer
3.247
3130086AYDLETT
Solar/Wind Harmer
-0.109
970657AG2-426 GEN
Solar/Wind Harmer
8.535
970657AG2-426 GEN
Solar/Wind Harmer
1.785
3146386ELIZ CT
Solar/Wind Harmer
-0.027
970099AG2-077 GEN
Solar/Wind Harmer
34.024
316431W1029_GEN1
Solar/Wind Harmer
4.902
316433W1029_GEN2
Solar/Wind Harmer
4.902
316236AE1-162_GEN
Solar/Wind Harmer
0.814
3146516WINFALL
Solar/Wind Harmer
-0.027
3146516WINFALL
Solar/Wind Harmer
-0.027
3146516WINFALL
Solar/Wind Harmer
-0.027
3146626S HERTFORD
Solar/Wind Harmer
-0.027
3146626S HERTFORD
Solar/Wind Harmer
-0.027
315742AE1-103 GEN
Solar/Wind Harmer
2.783
3146376EDENTON
Solar/Wind Harmer
0.785
3146376EDENTON
Solar/Wind Harmer
0.785
316240AF1-291 C
Solar/Wind Harmer
0.795
316033AB2-134 GEN
Solar/Wind Harmer
8.462
315697AD1-025 GEN
Solar/Wind Harmer
5.307
944641AF1-129 GEN
Adder
111.019
971741AH1-377 GEN
Solar/Wind Harmer
29.798
3145893MURPHYS
Solar/Wind Harmer
0.713
3145893MURPHYS
Solar/Wind Harmer
-0.046
3152261N ANNA2
50/50
30.741
3151771S ANNAG1
50/50
0.958
3151801S ANNAS2
50/50
0.492
3151031BRUNSWICKG2
50/50
3.471
3151761LOISA E
50/50
36.68
972183AH1-676 GEN
50/50
287.058
316044AC1-158 PL1
Solar/Wind Harmer
8.509
316450AC1-158 RIC
Solar/Wind Harmer
2.269
3147666LOUISA
Solar/Wind Harmer
-0.109
316313AB2-026
Solar/Wind Harmer
0.78
316258AE1-075 C
Solar/Wind Harmer
0.702
316405AF2-144 C
Solar/Wind Harmer
0.741
3143336POWHATN
Solar/Wind Harmer
2.916
970917AG2-570 GEN
Solar/Wind Harmer
71.277
315773AC2-141 GEN
Solar/Wind Harmer
11.72
944581AF1-123 GEN
Solar/Wind Harmer
126.633
944601AF1-125 GEN
Solar/Wind Harmer
124.656
3151101ELIZAR3
Adder
22.862
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146456SLIGO L269
Solar/Wind Harmer
-0.027
971153AH1-033 GEN
Solar/Wind Harmer
3.351
3144536CHRHLND
Solar/Wind Harmer
-0.004
315813AE1-149 C
Solar/Wind Harmer
17.079
970659AG2-427 GEN
Solar/Wind Harmer
2.572
316083AB2-161 GEN
Solar/Wind Harmer
4.433
970661AG2-428 GEN
Solar/Wind Harmer
5.142
316320Y1-086
Solar/Wind Harmer
1.598
3132273ORANGE
Solar/Wind Harmer
-0.005
3150861SPRUNCD
Adder
1.117
316435W1029_GEN3
Solar/Wind Harmer
4.902
315839AE2-212 C
Solar/Wind Harmer
0.814
3146516WINFALL
Solar/Wind Harmer
-0.027
3145336SMITFLD
Solar/Wind Harmer
-0.011
3146626S HERTFORD
Solar/Wind Harmer
-0.027
3145273HOLLAND
Solar/Wind Harmer
-0.02
965281AG1-393 GEN
Solar/Wind Harmer
3.333
3151221GRAVEL6
Adder
17.215
3151171GRAVELC
Adder
3.312
3146376EDENTON
Solar/Wind Harmer
-0.026
961611AG1-000B GEN
Solar/Wind Harmer
5.572
316365GEN2_N
Solar/Wind Harmer
1.771
315778AD1-151 GEN
Solar/Wind Harmer
22.655
316478AD1-087 GEN
Solar/Wind Harmer
2.264
316486AD2-202 GEN
Solar/Wind Harmer
0.663
315614AA2-178 GEN
Solar/Wind Harmer
2.81
970129AG2-093 GEN
Solar/Wind Harmer
14.642
3156081AA2-088 GEN
Solar/Wind Harmer
8.385
970133AG2-095 GEN
Solar/Wind Harmer
2.902
3144216WINCHST
Adder
0.865
966621AG1-532 GEN
Solar/Wind Harmer
0.522
971157AH1-035 GEN
Solar/Wind Harmer
3.215
315737AD1-076 GEN
Solar/Wind Harmer
4.877
3150921YORKTN3
Adder
5.73
3145893MURPHYS
Solar/Wind Harmer
0.178
3145893MURPHYS
Solar/Wind Harmer
-0.025
957521AF2-046 GEN
Solar/Wind Harmer
20.091
961681AG1-008 GEN
Solar/Wind Harmer
20.091
3146206CASHIE
Solar/Wind Harmer
-0.025
313506AB2-031 GEN
Solar/Wind Harmer
2.041
316303AF2-085
50/50
5.261
315244AE2-183_ST
50/50
7.62
963041AG1-153 GEN
50/50
7.028
315779AE2-040
50/50
3.522
316164AC1-076 GEN
Solar/Wind Harmer
2.938
941031AE2-094 GEN
Solar/Wind Harmer
57.754
944011AF1-069 GEN
Solar/Wind Harmer
18.096
316233AE1-074 FULL
Solar/Wind Harmer
0.818
971281AH1-106 GEN
Solar/Wind Harmer
4.94
971283AH1-107 GEN
Solar/Wind Harmer
4.94
970673AG2-436 GEN
Solar/Wind Harmer
63.56
970673AG2-436 GEN
Solar/Wind Harmer
32.182
971967AH1-528 GEN
Solar/Wind Harmer
56.158
970085AG2-068 GEN
Solar/Wind Harmer
17.743
970581AG2-369 GEN
Solar/Wind Harmer
15.259
316315AB2-025 C
Solar/Wind Harmer
0.765
315814AE2-033 C
Solar/Wind Harmer
26.3
3143316POE
Solar/Wind Harmer
-0.11
3151081ELIZAR1
Adder
22.573
3151091ELIZAR2
Adder
22.181
3152611GOSPORTB
Adder
3.132
3152621GOSPORTC
Adder
2.658
3152601GOSPORTA
Adder
2.452
957871AF2-081 GEN
Solar/Wind Harmer
13.769
319010AE1-072 C
Solar/Wind Harmer
5.558
3147346CASHSCORNER
Solar/Wind Harmer
0.425
3146406KITTY HAWK
Solar/Wind Harmer
0.023
316305AF2-043 C
Solar/Wind Harmer
0.826
315833AF1-017_GEN
Solar/Wind Harmer
5.184
316349AD2-085 GEN
Solar/Wind Harmer
2.427
316311AC2-079 GEN
Solar/Wind Harmer
13.767
315835AF2-110_GEN
Solar/Wind Harmer
3.41
313526AB2-022
Solar/Wind Harmer
0.736
971285AH1-108 GEN
Adder
1.828
3146486SUNBURY
Solar/Wind Harmer
-0.027
3146486SUNBURY
Solar/Wind Harmer
-0.027
316321Z2-027
Solar/Wind Harmer
0.733
3146396TANGLEW
Solar/Wind Harmer
0.5
3145176PASQUOTANK
Solar/Wind Harmer
-0.017
971445AH1-216 GEN
Solar/Wind Harmer
16.689
315611Z1-036_GEN2
Solar/Wind Harmer
6.597
972265AH1-717 GEN
Adder
18.385
3151201GRAVEL4
Adder
17.235
3151191GRAVEL3
Adder
17.017
3151211GRAVEL5
Adder
17.017
3130156CHOWAN
Solar/Wind Harmer
-0.026
3130156CHOWAN
Solar/Wind Harmer
-0.026
316369SG1_INVT
Solar/Wind Harmer
4.688
315816AE2-034 GEN
Solar/Wind Harmer
2.107
316132AB2-190 GEN1
Solar/Wind Harmer
2.633
965291AG1-394 GEN
Solar/Wind Harmer
2.286
946281AF1-292 GEN
Solar/Wind Harmer
0.577
3130546PLYMOUTH
Solar/Wind Harmer
-0.026
315732AD1-074 GEN1
Solar/Wind Harmer
5.189
315733AD1-074 GEN2
Solar/Wind Harmer
5.189
315735AD1-075 GEN1
Solar/Wind Harmer
2.595
316318V4-068
Solar/Wind Harmer
0.637
3145893MURPHYS
Solar/Wind Harmer
-0.069
3145893MURPHYS
Solar/Wind Harmer
-0.025
316087AB2-174 GEN
Solar/Wind Harmer
3.638
3146206CASHIE
Solar/Wind Harmer
-0.025
970601AG2-382 GEN
Solar/Wind Harmer
11.153
3146043SEABORD
Solar/Wind Harmer
-0.025
315607AA1-063A GEN
Solar/Wind Harmer
2.556
3145513AHOSKIE
Solar/Wind Harmer
0.22
3152251N ANNA1
50/50
30.744
970119AG2-088 GEN
50/50
39.456
3151791S ANNAG2
50/50
0.958
3151781S ANNAS1
50/50
0.492
315243AE2-183_GT3
50/50
4.407
3151051BRUNSWICKS1
50/50
7.204
3151021BRUNSWICKG1
50/50
3.471
971451AH1-221 GEN
50/50
10.542
3151741LOISA C
50/50
0.984
3151751LOISA D
50/50
17.992
316065AD1-022 GEN
Solar/Wind Harmer
12.776
316181AB2-040 GEN
Solar/Wind Harmer
3.542
3146173TUNIS
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.025
970301AG2-198 GEN
Solar/Wind Harmer
12.658
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.015
316426AA2-053 GEN
Solar/Wind Harmer
2.529
3145593CAROLNA
Solar/Wind Harmer
-0.025
3145593CAROLNA
Solar/Wind Harmer
-0.025
966811AG1-552 GEN
Solar/Wind Harmer
2.813
3145593CAROLNA
Solar/Wind Harmer
0.208
3145783HORNRTN
Solar/Wind Harmer
2.949
3145783HORNRTN
Solar/Wind Harmer
2.359
3145783HORNRTN
Solar/Wind Harmer
0.737
3145783HORNRTN
Solar/Wind Harmer
0.295
3145796HORNRTN
Solar/Wind Harmer
-0.074
3142946ENON
Solar/Wind Harmer
-0.002
3147133PAMPLIN
Solar/Wind Harmer
-0.024
3147133PAMPLIN
Solar/Wind Harmer
-0.019
958211AF2-115 GEN
Solar/Wind Harmer
3.781
963191AG1-168 GEN
Solar/Wind Harmer
2.268
3144293JTRSVLE
Adder
0.686
3144293JTRSVLE
Adder
0.577
3142366NRTHEST
Adder
0.692
3150691DARBY 3
Adder
15.167
3150701DARBY 4
Adder
15.132
3150681DARBY 2
Adder
15.114
3150671DARBY 1
Adder
15.096
3142296MT RD221
Adder
0.621
3150341NORNECKC1
Adder
1.636
3150341NORNECKC1
Adder
1.623
226929AD2-058 GEN
Solar/Wind Helper
0.087
3146173TUNIS
Solar/Wind Harmer
-0.025
970909AG2-566 GEN
Solar/Wind Harmer
2.403
316463AE2-346 GEN
Solar/Wind Harmer
0.409
316140AB2-099
Solar/Wind Harmer
0.17
962331AG1-082 GEN
Solar/Wind Harmer
3.158
3156021HOLLOMANSOL
Solar/Wind Harmer
3.402
3147043LAWRENC
Solar/Wind Harmer
-0.015
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3146263WOODLND
Solar/Wind Harmer
-0.025
3143096IRON208
Adder
0.935
3143096IRON208
Adder
0.916
316382AG1-145 C
Solar/Wind Harmer
0.748
316317KELFORD C
Solar/Wind Harmer
1.169
3145823KELFORD
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.099
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145963POPLR C
Solar/Wind Harmer
-0.025
3142946ENON
Solar/Wind Harmer
-0.008
3146926FARMVIL
Solar/Wind Harmer
-0.014
942461AE2-259 GEN
Solar/Wind Harmer
3.644
3147133PAMPLIN
Solar/Wind Harmer
-0.076
971193AH1-056 GEN
Solar/Wind Harmer
15.132
963181AG1-167 GEN
Solar/Wind Harmer
2.268
3144293JTRSVLE
Adder
0.686
3142433PROV 92
Adder
0.401
3142433PROV 92
Adder
0.401
3141843SHACKLE
Adder
1.013
3150351NORNECKC2
Adder
1.583
972255AH1-712 GEN
Adder
61.879
3141196NOKESVL
Solar/Wind Helper
1.074
959311AF2-222 GEN
Solar/Wind Harmer
12.268
316045AC1-158 PL2
Solar/Wind Harmer
27.219
3147666LOUISA
Solar/Wind Harmer
-0.19
316192AB2-158 GEN
Solar/Wind Harmer
5.545
3143226MDLTHAN
Solar/Wind Harmer
-0.033
940641AE2-051 GEN
Solar/Wind Harmer
29.235
3143526WINTERP
Solar/Wind Harmer
-0.157
939411AE1-173 GEN
Solar/Wind Harmer
151.543
3143336POWHATN
Solar/Wind Harmer
3.431
970919AG2-571 GEN
Solar/Wind Harmer
9.022
970087AG2-069 GEN
Solar/Wind Harmer
26.614
316294AC1-161 GEN
Solar/Wind Harmer
9.062
944591AF1-124 GEN
Solar/Wind Harmer
127.089
316336AC2-165 C
Solar/Wind Harmer
4.826
316375AC2-012 GEN
Solar/Wind Harmer
9.564
3150981CHESPKA
Adder
3.071
316388AE2-253 GEN
Solar/Wind Harmer
1.858
3146456SLIGO L269
Solar/Wind Harmer
-0.027
316246AF1-032 C
Solar/Wind Harmer
0.555
970659AG2-427 GEN
Solar/Wind Harmer
14.512
316381AD1-082 GEN
Solar/Wind Harmer
2.505
970661AG2-428 GEN
Solar/Wind Harmer
29.016
316093AE2-104_GEN
Solar/Wind Harmer
7.933
3150851SPRUNCC
Adder
1.117
957481AF2-042 GEN
Solar/Wind Harmer
85.059
316072AD1-144
Solar/Wind Harmer
0.549
3145336SMITFLD
Solar/Wind Harmer
-0.107
3146516WINFALL
Solar/Wind Harmer
-0.087
3146516WINFALL
Solar/Wind Harmer
-0.027
315800Z1-036_GEN1
Solar/Wind Harmer
6.597
315693AD1-088 GEN
Solar/Wind Harmer
13.348
962491AG1-098 GEN
Solar/Wind Harmer
17.806
3151171GRAVELC
Adder
2.519
3130156CHOWAN
Solar/Wind Harmer
-0.026
315671AE2-027_GEN
Solar/Wind Harmer
19.85
961611AG1-000B GEN
Solar/Wind Harmer
13.059
971647AH1-324 GEN
Solar/Wind Harmer
13.175
316023GEN1_S
Solar/Wind Harmer
1.771
971069AG2-661 GEN
Solar/Wind Harmer
4.138
3145663CRESWEL
Solar/Wind Harmer
-0.073
971163AH1-040 GEN
Solar/Wind Harmer
24.415
316458AB2-190 GEN2
Solar/Wind Harmer
2.633
970129AG2-093 GEN
Solar/Wind Harmer
5.931
960081AF2-299 GEN
Solar/Wind Harmer
2.896
3138126ROCKLANDING
Solar/Wind Harmer
0.079
3142543TWELFTH
Solar/Wind Harmer
-0.002
3145893MURPHYS
Solar/Wind Harmer
-0.102
3145893MURPHYS
Solar/Wind Harmer
0.759
3146206CASHIE
Solar/Wind Harmer
-0.025
971547AH1-271 GEN
Solar/Wind Harmer
6.373
971795AH1-408 GEN
Solar/Wind Harmer
19.052
3146173TUNIS
Solar/Wind Harmer
-0.025
3147043LAWRENC
Adder
2.033
3145683EARLEYS
Solar/Wind Harmer
-0.025
316011AB1-132 GEN
Solar/Wind Harmer
5.258
962571AG1-106 GEN
Solar/Wind Harmer
3.612
3146263WOODLND
Solar/Wind Harmer
-0.025
3143096IRON208
Adder
0.935
316190AA2-174 GEN
Solar/Wind Harmer
0.307
971317AH1-138 GEN
Solar/Wind Harmer
3.127
970937AG2-583 GEN
Solar/Wind Harmer
17.864
3145783HORNRTN
Solar/Wind Harmer
-0.025
316159AE1-175 C
Solar/Wind Harmer
0.666
3145823KELFORD
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.081
3145796HORNRTN
Solar/Wind Harmer
-0.025
944631AF1-128 GEN
Adder
104.9
3145963POPLR C
Solar/Wind Harmer
-0.025
315687AD1-152 GEN
Solar/Wind Harmer
2.961
316174AB2-169 GEN
Solar/Wind Harmer
3.783
316129AC1-054 GEN
Solar/Wind Harmer
2.143
971065AG2-659 GEN
Solar/Wind Harmer
12.198
3146926FARMVIL
Solar/Wind Harmer
-0.014
963171AG1-166 GEN
Solar/Wind Harmer
3.025
971563AH1-280 GEN
Solar/Wind Harmer
3.025
3144293JTRSVLE
Adder
0.686
970685AG2-442 GEN
Solar/Wind Harmer
21.155
3142433PROV 92
Adder
0.401
3142433PROV 92
Adder
0.401
3141843SHACKLE
Adder
1.013
3150351NORNECKC2
Adder
1.557
972277AH1-723 GEN
Adder
72.107
961941AG1-037 GEN
Solar/Wind Harmer
0.19
3145513AHOSKIE
Solar/Wind Harmer
-0.025
3137643SOCKMAN
Solar/Wind Harmer
-0.1
3145683EARLEYS
Solar/Wind Harmer
-0.05
3145683EARLEYS
Solar/Wind Harmer
-0.025
3145683EARLEYS
Solar/Wind Harmer
-0.025
315652AC1-086 GEN
Solar/Wind Harmer
28.271
3145796HORNRTN
Solar/Wind Harmer
-0.079
3145796HORNRTN
Solar/Wind Harmer
-0.01
970831AG2-522 GEN
Solar/Wind Harmer
12.25
3146033SCOT NK
Solar/Wind Harmer
-0.097
315657AE1-056 GEN
Solar/Wind Harmer
9.079
946301AF1-294 GEN
Solar/Wind Harmer
6.2
961791AG1-021 GEN
Solar/Wind Harmer
3.025
970683AG2-441 GEN
Solar/Wind Harmer
18.888
970681AG2-440 GEN
Solar/Wind Harmer
15.111
3142433PROV 92
Adder
0.401
3142433PROV 92
Adder
0.401
972205AH1-687 GEN
Adder
8.511
972189AH1-679 GEN
Adder
2.2
972193AH1-681 GEN
Adder
2.765
316411AF1-147_GEN1
Solar/Wind Helper
0.849
316415AF1-147_GEN2
Solar/Wind Helper
0.849
3138216PACIFIC
Solar/Wind Helper
0.042
LAGNLTFEXP_LAGN->PJM
CLTF
9.308
CBM South 2LTFEXP_CBM-S2->PJM
CBM
29.279
TVALTFEXP_TVA->PJM
CLTF
4.707
CPLELTFEXP_CPLE->PJM
CLTF
13.402
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.993
CBM West 1LTFEXP_CBM-W1->PJM
CBM
24.945
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.004
MECLTFEXP_MEC->PJM
CLTF
4.2
SIGELTFEXP_SIGE->PJM
CLTF
0.127
NYPJM->LTFIMP_NY
CLTF
3.877
LGEELTFEXP_LGEE->PJM
CLTF
1.536
WECLTFEXP_WEC->PJM
CLTF
0.747

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 550_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:146.89 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:4730.38
MW Contribution:7.64
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
3.841
971285AH1-108 GEN
50/50
1.565
315244AE2-183_ST
50/50
5.513
963041AG1-153 GEN
50/50
5.092
3151081ELIZAR1
50/50
18.543
3151091ELIZAR2
50/50
18.221
316164AC1-076 GEN
Solar/Wind Harmer
0.373
316233AE1-074 FULL
Solar/Wind Harmer
0.165
971281AH1-106 GEN
Solar/Wind Harmer
2.866
971283AH1-107 GEN
Solar/Wind Harmer
2.866
941031AE2-094 GEN
Solar/Wind Harmer
36.413
944011AF1-069 GEN
Solar/Wind Harmer
11.897
970673AG2-436 GEN
Solar/Wind Harmer
41.514
970673AG2-436 GEN
Solar/Wind Harmer
27.676
3143316POE
Solar/Wind Harmer
0.766
971967AH1-528 GEN
Solar/Wind Harmer
30.826
3152611GOSPORTB
Adder
2.426
3152621GOSPORTC
Adder
2.059
3152601GOSPORTA
Adder
1.899
316315AB2-025 C
Solar/Wind Harmer
0.154
957871AF2-081 GEN
Solar/Wind Harmer
9.424
315814AE2-033 C
Solar/Wind Harmer
14.975
971445AH1-216 GEN
Solar/Wind Harmer
13.326
319010AE1-072 C
Solar/Wind Harmer
0.951
3146406KITTY HAWK
Solar/Wind Harmer
0.023
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.129
316311AC2-079 GEN
Solar/Wind Harmer
5.42
316305AF2-043 C
Solar/Wind Harmer
0.002
972265AH1-717 GEN
Adder
14.641
3151201GRAVEL4
Adder
13.725
3151191GRAVEL3
Adder
13.552
3151211GRAVEL5
Adder
13.552
316369SG1_INVT
Solar/Wind Harmer
0.007
316132AB2-190 GEN1
Solar/Wind Harmer
1.01
315835AF2-110_GEN
Solar/Wind Harmer
1.29
313526AB2-022
Solar/Wind Harmer
0.101
3146486SUNBURY
Solar/Wind Harmer
0.187
3146486SUNBURY
Solar/Wind Harmer
0.187
316321Z2-027
Solar/Wind Harmer
0.035
3146396TANGLEW
Solar/Wind Harmer
0.515
3145176PASQUOTANK
Solar/Wind Harmer
0.116
970085AG2-068 GEN
Solar/Wind Harmer
9.803
970581AG2-369 GEN
Solar/Wind Harmer
8.43
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.181
3130156CHOWAN
Solar/Wind Harmer
0.181
315976AC1-164 GENA
Solar/Wind Harmer
18.734
316169AC1-164_GENC
Solar/Wind Harmer
16.185
315975AC1-164 GENB
Solar/Wind Harmer
0.554
316312AB1-027
Solar/Wind Harmer
0.323
3138283WHITEMARSH
Solar/Wind Harmer
0.042
971167AH1-042 GEN
Solar/Wind Harmer
15.959
3142433PROV 92
Adder
0.348
3142433PROV 92
Adder
0.348
315816AE2-034 GEN
Solar/Wind Harmer
0.765
3143873LANEXA
Solar/Wind Harmer
0.106
3130546PLYMOUTH
Solar/Wind Harmer
0.176
965291AG1-394 GEN
Solar/Wind Harmer
0.781
315732AD1-074 GEN1
Solar/Wind Harmer
1.008
315733AD1-074 GEN2
Solar/Wind Harmer
1.008
315735AD1-075 GEN1
Solar/Wind Harmer
0.505
970189AG2-124 GEN
Solar/Wind Harmer
5.177
316314AB2-024 C
Solar/Wind Harmer
0.001
3145893MURPHYS
Solar/Wind Harmer
0.471
3145893MURPHYS
Solar/Wind Harmer
0.174
316059AD1-063 C
Solar/Wind Harmer
0.001
315662AE1-191 GEN
Solar/Wind Harmer
0.006
315666AE1-190 GEN
Solar/Wind Harmer
0.001
3146206CASHIE
Solar/Wind Harmer
0.174
970601AG2-382 GEN
Solar/Wind Harmer
6.501
3141873WAN 176
Solar/Wind Harmer
0.035
316087AB2-174 GEN
Solar/Wind Harmer
0.005
3146043SEABORD
Solar/Wind Harmer
0.172
3145513AHOSKIE
Solar/Wind Harmer
0.36
3145513AHOSKIE
Solar/Wind Harmer
0.172
315607AA1-063A GEN
Solar/Wind Harmer
0.351
3145683EARLEYS
Solar/Wind Harmer
0.343
3145683EARLEYS
Solar/Wind Harmer
0.171
3145683EARLEYS
Solar/Wind Harmer
0.171
3141913WHIT STONE
Solar/Wind Harmer
0.171
3137643SOCKMAN
Solar/Wind Harmer
0.68
972189AH1-679 GEN
Adder
2.853
3138133OCRAN
Solar/Wind Harmer
0.051
315652AC1-086 GEN
Solar/Wind Harmer
18.701
3141783LANCAST
Solar/Wind Harmer
0.101
3141783LANCAST
Solar/Wind Harmer
0.067
3145796HORNRTN
Solar/Wind Harmer
0.536
3145796HORNRTN
Solar/Wind Harmer
0.067
3146033SCOT NK
Solar/Wind Harmer
0.664
970285AG2-188 GEN
Solar/Wind Harmer
13.092
962981AG1-147 GEN
Solar/Wind Harmer
6.178
315657AE1-056 GEN
Solar/Wind Harmer
5.706
970831AG2-522 GEN
Solar/Wind Harmer
7.049
946301AF1-294 GEN
Solar/Wind Harmer
3.257
961791AG1-021 GEN
Solar/Wind Harmer
1.585
971845AH1-439 GEN
Solar/Wind Harmer
7.482
970683AG2-441 GEN
Solar/Wind Harmer
10.971
970681AG2-440 GEN
Solar/Wind Harmer
8.777
3144303KENBRDG
Solar/Wind Harmer
0.131
971443AH1-215 GEN
Solar/Wind Harmer
2.755
970327AG2-215 GEN
Solar/Wind Harmer
5.37
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
972205AH1-687 GEN
Adder
6.897
316005AA1-067
Solar/Wind Harmer
0.172
3145746EVERETS
Solar/Wind Harmer
0.636
3145746EVERETS
Solar/Wind Harmer
0.16
3145746EVERETS
Solar/Wind Harmer
0.16
3145746EVERETS
Solar/Wind Harmer
0.16
970181AG2-120 GEN
Solar/Wind Harmer
1.99
957861AF2-080 GEN
Solar/Wind Harmer
6.807
316420AA1-050 GEN
Solar/Wind Harmer
0.005
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.156
3145573BETHELC
Solar/Wind Harmer
0.156
3141813NORNECK
Solar/Wind Harmer
0.155
3147346CASHSCORNER
Solar/Wind Harmer
0.356
971447AH1-217 GEN
Solar/Wind Harmer
4.628
316118AC1-105 GEN
Solar/Wind Harmer
0.393
3147173SINAI
Solar/Wind Harmer
0.149
3147243WELCO
Solar/Wind Harmer
0.093
3150411LDYSMT5
Adder
19.065
3150381LDYSMT2
Adder
18.246
972213AH1-691 GEN
Adder
3.086
972215AH1-692 GEN
Adder
3.086
972193AH1-681 GEN
Adder
3.231
316223AC1-118
Solar/Wind Harmer
0.099
270494AE1-108_GEN
Solar/Wind Harmer
1.653
3138266HYDRAULIC
Solar/Wind Harmer
0.006
3138266HYDRAULIC
Solar/Wind Harmer
0.004
970865AG2-541 GEN
Solar/Wind Harmer
4.701
316123AC1-075 GEN
Solar/Wind Harmer
0.173
970165AG2-112 GEN
Solar/Wind Harmer
1.025
970163AG2-111 GEN
Solar/Wind Harmer
0.978
3148133STUARTS
Solar/Wind Harmer
0.074
3148013FISHERV
Solar/Wind Harmer
0.071
944491AF1-114 GEN
Solar/Wind Harmer
0
3152251N ANNA1
50/50
17.337
971507AH1-251 GEN
50/50
10.725
970119AG2-088 GEN
50/50
28.809
3150851SPRUNCC
50/50
0.956
315243AE2-183_GT3
50/50
3.188
3151051BRUNSWICKS1
50/50
5.219
3151021BRUNSWICKG1
50/50
2.515
971451AH1-221 GEN
50/50
7.638
316045AC1-158 PL2
Solar/Wind Harmer
9.531
3147666LOUISA
Solar/Wind Harmer
0.985
316192AB2-158 GEN
Solar/Wind Harmer
1.365
3143226MDLTHAN
Solar/Wind Harmer
0.216
3143526WINTERP
Solar/Wind Harmer
1.074
940641AE2-051 GEN
Solar/Wind Harmer
16.147
939411AE1-173 GEN
Solar/Wind Harmer
84.888
3143336POWHATN
Solar/Wind Harmer
3.453
316294AC1-161 GEN
Solar/Wind Harmer
3.335
944591AF1-124 GEN
Solar/Wind Harmer
43.185
316375AC2-012 GEN
Solar/Wind Harmer
0.005
3150981CHESPKA
Adder
2.379
970659AG2-427 GEN
Solar/Wind Harmer
9.201
316381AD1-082 GEN
Solar/Wind Harmer
0.198
315671AE2-027_GEN
Solar/Wind Harmer
12.167
3142543TWELFTH
Solar/Wind Harmer
0.018
970661AG2-428 GEN
Solar/Wind Harmer
18.874
316388AE2-253 GEN
Solar/Wind Harmer
0.594
3145336SMITFLD
Solar/Wind Harmer
0.757
3146456SLIGO L269
Solar/Wind Harmer
0.189
316246AF1-032 C
Solar/Wind Harmer
0.085
316336AC2-165 C
Solar/Wind Harmer
0.007
3151171GRAVELC
Adder
2.006
961611AG1-000B GEN
Solar/Wind Harmer
9.885
971647AH1-324 GEN
Solar/Wind Harmer
8.041
316072AD1-144
Solar/Wind Harmer
0.068
971069AG2-661 GEN
Solar/Wind Harmer
3.349
316458AB2-190 GEN2
Solar/Wind Harmer
1.01
970129AG2-093 GEN
Solar/Wind Harmer
5.357
3143096IRON208
Adder
0.788
316093AE2-104_GEN
Solar/Wind Harmer
3.16
3138126ROCKLANDING
Solar/Wind Harmer
0.085
944631AF1-128 GEN
Adder
88.55
3146516WINFALL
Solar/Wind Harmer
0.601
3146516WINFALL
Solar/Wind Harmer
0.185
970919AG2-571 GEN
Solar/Wind Harmer
6.561
316159AE1-175 C
Solar/Wind Harmer
0.159
970087AG2-069 GEN
Solar/Wind Harmer
14.704
971317AH1-138 GEN
Solar/Wind Harmer
1.372
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.181
3142416OLDCHRC
Solar/Wind Harmer
0.469
3142416OLDCHRC
Solar/Wind Harmer
0.18
3142433PROV 92
Solar/Wind Harmer
0.716
3142433PROV 92
Adder
0.348
3142433PROV 92
Adder
0.348
957481AF2-042 GEN
Solar/Wind Harmer
47.61
3145663CRESWEL
Solar/Wind Harmer
0.499
971163AH1-040 GEN
Solar/Wind Harmer
14.264
316023GEN1_S
Solar/Wind Harmer
0.397
315693AD1-088 GEN
Solar/Wind Harmer
8.463
962491AG1-098 GEN
Solar/Wind Harmer
10.047
971777AH1-397 GEN
Solar/Wind Harmer
0.461
3141843SHACKLE
Adder
0.893
3145893MURPHYS
Solar/Wind Harmer
0.697
3145893MURPHYS
Solar/Wind Harmer
0.775
3141766HARMONY
Solar/Wind Harmer
0.035
3146206CASHIE
Solar/Wind Harmer
0.174
971547AH1-271 GEN
Solar/Wind Harmer
3.715
970937AG2-583 GEN
Solar/Wind Harmer
10.664
960081AF2-299 GEN
Solar/Wind Harmer
1.668
3146173TUNIS
Solar/Wind Harmer
0.173
3145683EARLEYS
Solar/Wind Harmer
0.171
971795AH1-408 GEN
Solar/Wind Harmer
11.43
3146263WOODLND
Solar/Wind Harmer
0.171
3147043LAWRENC
Adder
1.542
3138133OCRAN
Solar/Wind Harmer
0.102
316011AB1-132 GEN
Solar/Wind Harmer
3.091
962571AG1-106 GEN
Solar/Wind Harmer
2.419
316190AA2-174 GEN
Solar/Wind Harmer
0
3145823KELFORD
Solar/Wind Harmer
0.169
3145963POPLR C
Solar/Wind Harmer
0.168
3145783HORNRTN
Solar/Wind Harmer
0.168
3145796HORNRTN
Solar/Wind Harmer
0.553
3145796HORNRTN
Solar/Wind Harmer
0.168
3146926FARMVIL
Solar/Wind Harmer
0.101
316174AB2-169 GEN
Solar/Wind Harmer
0.004
963171AG1-166 GEN
Solar/Wind Harmer
0.88
971563AH1-280 GEN
Solar/Wind Harmer
1.761
3144293JTRSVLE
Adder
0.525
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.066
316129AC1-054 GEN
Solar/Wind Harmer
0.62
970685AG2-442 GEN
Solar/Wind Harmer
12.287
971065AG2-659 GEN
Solar/Wind Harmer
7.013
316212AC1-099_GEN
Solar/Wind Harmer
0.848
315687AD1-152 GEN
Solar/Wind Harmer
0.005
3146293MARTNCO
Solar/Wind Harmer
0.151
316237AB2-079_GEN
Solar/Wind Harmer
0.001
972003AH1-546 GEN
Solar/Wind Harmer
6.886
962861AG1-135 GEN
Solar/Wind Harmer
5.167
315722AD1-056 GEN
Solar/Wind Harmer
1.014
3145746EVERETS
Solar/Wind Harmer
0.16
3145746EVERETS
Solar/Wind Harmer
0.16
3151751LOISA D
Adder
10.359
316494AC1-189 GEN
Solar/Wind Harmer
0.533
3141726DUNNSVL
Solar/Wind Harmer
0.63
3146233WITAKRS
Solar/Wind Harmer
0.623
961671AG1-007 GEN
Solar/Wind Harmer
0.024
3146083TARBORO
Solar/Wind Harmer
0.156
3145493TOT1
Solar/Wind Harmer
0.694
3150351NORNECKC2
Adder
1.549
966881AG1-559 GEN
Solar/Wind Harmer
0.179
970401AG2-262 GEN
Solar/Wind Harmer
0.909
971377AH1-170 GEN
Solar/Wind Harmer
1.646
3147623JAMES R
Solar/Wind Harmer
0.358
3145543BTLEBRO
Solar/Wind Harmer
0.154
3145543BTLEBRO
Solar/Wind Harmer
0.123
316359AB2-059 GEN
Solar/Wind Harmer
0.553
316049AB1-081 GEN
Solar/Wind Harmer
0.881
3142053HEARTS
Solar/Wind Harmer
0.271
316254AC1-120 GEN1
Solar/Wind Harmer
0.32
316337AD2-073 GEN
Solar/Wind Harmer
0.128
316003AC1-222 GEN
Solar/Wind Harmer
0.004
972197AH1-683 GEN
Adder
2.968
972219AH1-694 GEN
Adder
2.137
972277AH1-723 GEN
Adder
84.254
972135AH1-637 GEN
Solar/Wind Harmer
1.058
3152261N ANNA2
50/50
17.335
3150861SPRUNCD
50/50
0.956
3151031BRUNSWICKG2
50/50
2.515
3151101ELIZAR3
50/50
18.78
316044AC1-158 PL1
Solar/Wind Harmer
2.981
316450AC1-158 RIC
Solar/Wind Harmer
0.795
3147666LOUISA
Solar/Wind Harmer
0.566
316313AB2-026
Solar/Wind Harmer
0.122
316258AE1-075 C
Solar/Wind Harmer
0.147
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
2.935
315773AC2-141 GEN
Solar/Wind Harmer
7.031
315839AE2-212 C
Solar/Wind Harmer
0.002
944581AF1-123 GEN
Solar/Wind Harmer
43.032
944601AF1-125 GEN
Solar/Wind Harmer
42.369
315813AE1-149 C
Solar/Wind Harmer
10.188
965281AG1-393 GEN
Solar/Wind Harmer
2.032
3144873MCLAUGH
Solar/Wind Harmer
0.005
3144536CHRHLND
Solar/Wind Harmer
0.028
970659AG2-427 GEN
Solar/Wind Harmer
2.013
316083AB2-161 GEN
Solar/Wind Harmer
0.003
970661AG2-428 GEN
Solar/Wind Harmer
4.014
3145336SMITFLD
Solar/Wind Harmer
0.076
3146456SLIGO L269
Solar/Wind Harmer
0.189
971153AH1-033 GEN
Solar/Wind Harmer
2.184
3151221GRAVEL6
Adder
13.71
3151171GRAVELC
Adder
2.638
961611AG1-000B GEN
Solar/Wind Harmer
5.027
315778AD1-151 GEN
Solar/Wind Harmer
15.07
970129AG2-093 GEN
Solar/Wind Harmer
11.383
970133AG2-095 GEN
Solar/Wind Harmer
1.807
3143096IRON208
Adder
0.788
3143096IRON208
Adder
0.772
316320Y1-086
Solar/Wind Harmer
0.001
3144216WINCHST
Adder
0.701
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.185
3150921YORKTN3
Adder
4.662
3146626S HERTFORD
Solar/Wind Harmer
0.184
970917AG2-570 GEN
Solar/Wind Harmer
16.401
3145273HOLLAND
Solar/Wind Harmer
0.138
3142946ENON
Solar/Wind Harmer
0.062
316382AG1-145 C
Solar/Wind Harmer
0.001
970293AG2-193 GEN
Solar/Wind Harmer
1.952
3146376EDENTON
Solar/Wind Harmer
0.181
3142416OLDCHRC
Solar/Wind Harmer
1.749
3142433PROV 92
Adder
0.348
3142433PROV 92
Adder
0.348
315614AA2-178 GEN
Solar/Wind Harmer
1.02
316365GEN2_N
Solar/Wind Harmer
0.397
3156081AA2-088 GEN
Solar/Wind Harmer
0.004
971157AH1-035 GEN
Solar/Wind Harmer
2.111
315737AD1-076 GEN
Solar/Wind Harmer
2.257
3141843SHACKLE
Adder
0.893
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3145893MURPHYS
Solar/Wind Harmer
0.292
3145893MURPHYS
Solar/Wind Harmer
0.174
3141766HARMONY
Solar/Wind Harmer
2.323
316280AD1-041 GEN
Solar/Wind Harmer
0.004
3146206CASHIE
Solar/Wind Harmer
0.174
957521AF2-046 GEN
Solar/Wind Harmer
12.94
961681AG1-008 GEN
Solar/Wind Harmer
12.94
316473AC1-191 GEN
Solar/Wind Harmer
0.587
316156AD2-030 GEN
Solar/Wind Harmer
0.129
3141873WAN 176
Solar/Wind Harmer
3.086
3146173TUNIS
Solar/Wind Harmer
0.173
316478AD1-087 GEN
Solar/Wind Harmer
0.602
316486AD2-202 GEN
Solar/Wind Harmer
0.177
3156021HOLLOMANSOL
Solar/Wind Harmer
0.782
316463AE2-346 GEN
Solar/Wind Harmer
0.148
316140AB2-099
Solar/Wind Harmer
0.062
962331AG1-082 GEN
Solar/Wind Harmer
1.836
313506AB2-031 GEN
Solar/Wind Harmer
0.53
970909AG2-566 GEN
Solar/Wind Harmer
1.827
3146263WOODLND
Solar/Wind Harmer
0.171
3147043LAWRENC
Solar/Wind Harmer
0.102
3142666NORTHAMPTON
Solar/Wind Harmer
0.17
3132273ORANGE
Solar/Wind Harmer
0.034
316317KELFORD C
Solar/Wind Harmer
0.016
3145823KELFORD
Solar/Wind Harmer
0.169
3145963POPLR C
Solar/Wind Harmer
0.168
3145796HORNRTN
Solar/Wind Harmer
0.671
3145796HORNRTN
Solar/Wind Harmer
0.168
3146926FARMVIL
Solar/Wind Harmer
0.101
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
962971AG1-146 GEN
Solar/Wind Harmer
2.648
3147133PAMPLIN
Solar/Wind Harmer
0.519
971193AH1-056 GEN
Solar/Wind Harmer
10.073
963181AG1-167 GEN
Solar/Wind Harmer
0.66
3144293JTRSVLE
Adder
0.525
3146776BUCKING
Solar/Wind Harmer
0.059
959311AF2-222 GEN
Solar/Wind Harmer
14.593
970257AG2-171 GEN
Solar/Wind Harmer
5.248
316210AC1-098 GEN
Solar/Wind Harmer
1.521
315785AD2-033 C
Solar/Wind Harmer
1.332
970009AG2-005 GEN
Solar/Wind Harmer
1.222
964241AG1-285 GEN
Solar/Wind Harmer
10.882
316131AB2-060 GEN
Solar/Wind Harmer
0.512
3145933PARMELE
Solar/Wind Harmer
0.163
966801AG1-551 GEN
Solar/Wind Harmer
1.894
316404AE1-155 C
Solar/Wind Harmer
0.036
315724AD1-057 GEN
Solar/Wind Harmer
0.601
3145746EVERETS
Solar/Wind Harmer
0.16
3145746EVERETS
Solar/Wind Harmer
0.16
3151761LOISA E
Adder
21.12
316327AA2-057 GEN
Solar/Wind Harmer
0.24
3146233WITAKRS
Solar/Wind Harmer
0.786
3146233WITAKRS
Solar/Wind Harmer
0.106
3138543CONSLDL
Solar/Wind Harmer
0.103
3146073TAR RVR
Solar/Wind Harmer
0.156
3146083TARBORO
Solar/Wind Harmer
0.156
3150351NORNECKC2
Adder
1.575
972183AH1-676 GEN
Adder
165.957
970221AG2-151 GEN
Solar/Wind Harmer
8.231
961601AG1-000A GEN
Solar/Wind Harmer
10.953
3145543BTLEBRO
Solar/Wind Harmer
0.154
3145543BTLEBRO
Solar/Wind Harmer
0.154
971623AH1-311 GEN
Solar/Wind Harmer
0.308
316170AC1-121 GEN2
Solar/Wind Harmer
0.16
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
6.375
971781AH1-399 GEN
Solar/Wind Harmer
0.193
3150401LDYSMT4
Adder
19.006
971133AH1-012 GEN
50/50
5.025
970533AG2-339 GEN
50/50
17.574
970531AG2-338 GEN
50/50
7.029
315242AE2-183_GT2
50/50
3.188
315241AE2-183_GT1
50/50
3.169
972185AH1-677 GEN
50/50
11.495
3151041BRUNSWICKG3
50/50
2.515
972187AH1-678 GEN
50/50
5.771
316447AC1-158 HLD
Solar/Wind Harmer
6.552
971223AH1-071 GEN
Solar/Wind Harmer
2.305
3143526WINTERP
Solar/Wind Harmer
1.074
316036AC1-147 C
Solar/Wind Harmer
0.035
3150991CHESPKB
Adder
1.996
3150991CHESPKB
Adder
1.948
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.183
316185AD1-033 GEN
Solar/Wind Harmer
0.005
316240AF1-291 C
Solar/Wind Harmer
0.002
3145506HICKORY
Solar/Wind Harmer
0.76
3145506HICKORY
Solar/Wind Harmer
0.456
3145506HICKORY
Solar/Wind Harmer
0.114
970657AG2-426 GEN
Solar/Wind Harmer
6.654
970657AG2-426 GEN
Solar/Wind Harmer
1.395
3144356SAPONY
Solar/Wind Harmer
1.589
944641AF1-129 GEN
Adder
90.549
316339AD2-160 GEN
Solar/Wind Harmer
0.307
316236AE1-162_GEN
Solar/Wind Harmer
0.002
316018AA1-139 ULT2
Solar/Wind Harmer
0.005
316017AA1-139 ULT1
Solar/Wind Harmer
0.106
3137176SLIGO L2192
Solar/Wind Harmer
0.752
3146456SLIGO L269
Solar/Wind Harmer
3.344
3130086AYDLETT
Solar/Wind Harmer
0.755
970933AG2-581 GEN
Solar/Wind Harmer
15.103
316033AB2-134 GEN
Solar/Wind Harmer
0.011
315697AD1-025 GEN
Solar/Wind Harmer
0.212
3146386ELIZ CT
Solar/Wind Harmer
0.187
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.185
3146516WINFALL
Solar/Wind Harmer
0.185
3146516WINFALL
Solar/Wind Harmer
0.185
3142366NRTHEST
Adder
0.605
3146626S HERTFORD
Solar/Wind Harmer
0.184
3146626S HERTFORD
Solar/Wind Harmer
0.184
3150691DARBY 3
Adder
13.271
3150701DARBY 4
Adder
13.24
3150681DARBY 2
Adder
13.225
3150671DARBY 1
Adder
13.209
3142946ENON
Solar/Wind Harmer
0.018
315742AE1-103 GEN
Solar/Wind Harmer
0.002
316075AC2-137 C
Solar/Wind Harmer
0.05
3146376EDENTON
Solar/Wind Harmer
0.807
3146376EDENTON
Solar/Wind Harmer
0.807
3142296MT RD221
Adder
0.577
970099AG2-077 GEN
Solar/Wind Harmer
19.044
316065AD1-022 GEN
Solar/Wind Harmer
8.039
3145893MURPHYS
Solar/Wind Harmer
1.166
3145893MURPHYS
Solar/Wind Harmer
0.314
966871AG1-558 GEN
Solar/Wind Harmer
0.201
3146173TUNIS
Solar/Wind Harmer
0.173
3146173TUNIS
Solar/Wind Harmer
0.173
971741AH1-377 GEN
Solar/Wind Harmer
17.107
316181AB2-040 GEN
Solar/Wind Harmer
0.249
970301AG2-198 GEN
Solar/Wind Harmer
7.308
3142666NORTHAMPTON
Solar/Wind Harmer
0.17
3142666NORTHAMPTON
Solar/Wind Harmer
0.17
3142666NORTHAMPTON
Solar/Wind Harmer
0.17
3142666NORTHAMPTON
Solar/Wind Harmer
0.102
316426AA2-053 GEN
Solar/Wind Harmer
0.573
3145593CAROLNA
Solar/Wind Harmer
0.169
3145593CAROLNA
Solar/Wind Harmer
0.169
966811AG1-552 GEN
Solar/Wind Harmer
1.836
3145593CAROLNA
Solar/Wind Harmer
0.211
3145783HORNRTN
Solar/Wind Harmer
2.993
3145783HORNRTN
Solar/Wind Harmer
2.394
3145783HORNRTN
Solar/Wind Harmer
0.748
3145783HORNRTN
Solar/Wind Harmer
0.299
3145796HORNRTN
Solar/Wind Harmer
0.503
3147133PAMPLIN
Solar/Wind Harmer
0.165
3147133PAMPLIN
Solar/Wind Harmer
0.132
958211AF2-115 GEN
Solar/Wind Harmer
1.981
963191AG1-168 GEN
Solar/Wind Harmer
0.66
3144293JTRSVLE
Adder
0.525
3144293JTRSVLE
Adder
0.442
3146776BUCKING
Solar/Wind Harmer
0.659
3146776BUCKING
Solar/Wind Harmer
0.053
316034AC1-036 C
Solar/Wind Harmer
0.012
970323AG2-213 GEN
Solar/Wind Harmer
6.998
971775AH1-396 GEN
Solar/Wind Harmer
0.262
316274AC1-208 GEN
Solar/Wind Harmer
0.847
313527AB2-043 GEN
Solar/Wind Harmer
0.002
3145933PARMELE
Solar/Wind Harmer
0.325
3145933PARMELE
Solar/Wind Harmer
0.163
939181AE1-148 GEN
Solar/Wind Harmer
7.796
958261AF2-120 GEN
Solar/Wind Harmer
5.313
3151731LOISA B
Adder
10.359
3151721LOISA A
Adder
10.306
966001AG1-469 GEN
Solar/Wind Harmer
0.092
962561AG1-105 GEN
Solar/Wind Harmer
7.498
3145493TOT1
Solar/Wind Harmer
0.362
3145453TOT5
Solar/Wind Harmer
0.217
3145603CNETO
Solar/Wind Harmer
0.145
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
1.627
3150341NORNECKC1
Adder
1.614
957411AF2-035 GEN
Solar/Wind Harmer
6.615
970317AG2-208 GEN
Solar/Wind Harmer
6.128
964791AG1-342 GEN
Solar/Wind Harmer
2.976
3146843MT LREL
Solar/Wind Harmer
0.155
3146843MT LREL
Solar/Wind Harmer
0.155
971489AH1-241 GEN
Solar/Wind Harmer
8.231
961601AG1-000A GEN
Solar/Wind Harmer
2.738
316263AC1-034 GEN
Solar/Wind Harmer
5.852
315673AE1-157 GEN
Solar/Wind Harmer
10.383
316468AD1-105 GEN
Solar/Wind Harmer
-0.048
315821AE2-092 GEN
Solar/Wind Harmer
0.009
3150391LDYSMT3
Adder
18.97
972195AH1-682 GEN
Adder
2.493
316222AC1-221 GEN
Solar/Wind Harmer
0.561
942751AE2-291 GEN
Solar/Wind Harmer
6.565
3150371LDYSMT1
Adder
18.365
972255AH1-712 GEN
Adder
72.302
971683AH1-343 GEN
Solar/Wind Harmer
5.156
3141906WESTMOR
Solar/Wind Harmer
0.055
316283AC2-100 C
Solar/Wind Harmer
0.263
970737AG2-469 GEN
Solar/Wind Harmer
5.524
3148013FISHERV
Solar/Wind Harmer
0.123
LAGNLTFEXP_LAGN->PJM
CLTF
7.344
CBM South 2LTFEXP_CBM-S2->PJM
CBM
22.849
TVALTFEXP_TVA->PJM
CLTF
3.749
CPLELTFEXP_CPLE->PJM
CLTF
10.276
CBM West 2LTFEXP_CBM-W2->PJM
CBM
37.498
CBM West 1LTFEXP_CBM-W1->PJM
CBM
17.866
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.71
MECLTFEXP_MEC->PJM
CLTF
3.192
SIGELTFEXP_SIGE->PJM
CLTF
0.098
NYPJM->LTFIMP_NY
CLTF
2.943
LGEELTFEXP_LGEE->PJM
CLTF
1.185
WECLTFEXP_WEC->PJM
CLTF
0.552

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P2-2: MORRISVILLE B1_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: MORRISVILLE B1_SRT-S
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:140.84 %
Rating:3118.0 MVA
Rating Type:C
MVA to Mitigate:4391.4
MW Contribution:7.04
Bus #Bus NameTypeMW Contribution
3152251N ANNA1
50/50
17.069
971507AH1-251 GEN
50/50
10.56
970119AG2-088 GEN
50/50
26.753
3150851SPRUNCC
50/50
0.882
315243AE2-183_GT3
50/50
2.943
3151051BRUNSWICKS1
50/50
4.812
3151021BRUNSWICKG1
50/50
2.318
971451AH1-221 GEN
50/50
7.041
316045AC1-158 PL2
Solar/Wind Harmer
21.506
3147666LOUISA
Solar/Wind Harmer
-0.105
316192AB2-158 GEN
Solar/Wind Harmer
3.057
3143226MDLTHAN
Solar/Wind Harmer
-0.022
3143526WINTERP
Solar/Wind Harmer
-0.111
940641AE2-051 GEN
Solar/Wind Harmer
19.731
939411AE1-173 GEN
Solar/Wind Harmer
103.557
316294AC1-161 GEN
Solar/Wind Harmer
6.454
944591AF1-124 GEN
Solar/Wind Harmer
90.387
316375AC2-012 GEN
Solar/Wind Harmer
6.828
3150981CHESPKA
Adder
2.192
970659AG2-427 GEN
Solar/Wind Harmer
10.468
316381AD1-082 GEN
Solar/Wind Harmer
1.806
315671AE2-027_GEN
Solar/Wind Harmer
14.765
3142543TWELFTH
Solar/Wind Harmer
-0.002
970661AG2-428 GEN
Solar/Wind Harmer
20.871
316388AE2-253 GEN
Solar/Wind Harmer
1.322
3145336SMITFLD
Solar/Wind Harmer
-0.078
3146456SLIGO L269
Solar/Wind Harmer
-0.019
316246AF1-032 C
Solar/Wind Harmer
0.395
3151171GRAVELC
Adder
1.847
961611AG1-000B GEN
Solar/Wind Harmer
9.624
971647AH1-324 GEN
Solar/Wind Harmer
9.747
316072AD1-144
Solar/Wind Harmer
0.394
971069AG2-661 GEN
Solar/Wind Harmer
3.083
316458AB2-190 GEN2
Solar/Wind Harmer
1.97
970129AG2-093 GEN
Solar/Wind Harmer
4.442
3143096IRON208
Adder
0.724
316093AE2-104_GEN
Solar/Wind Harmer
5.649
3143336POWHATN
Solar/Wind Harmer
2.304
3138126ROCKLANDING
Solar/Wind Harmer
0.059
944631AF1-128 GEN
Adder
81.389
3146516WINFALL
Solar/Wind Harmer
-0.062
3146516WINFALL
Solar/Wind Harmer
-0.019
970919AG2-571 GEN
Solar/Wind Harmer
6.028
316159AE1-175 C
Solar/Wind Harmer
0.509
971317AH1-138 GEN
Solar/Wind Harmer
2.373
970087AG2-069 GEN
Solar/Wind Harmer
17.783
315800Z1-036_GEN1
Solar/Wind Harmer
4.669
3130156CHOWAN
Solar/Wind Harmer
-0.019
316336AC2-165 C
Solar/Wind Harmer
3.232
3142416OLDCHRC
Solar/Wind Harmer
-0.048
3142416OLDCHRC
Solar/Wind Harmer
-0.018
3142433PROV 92
Solar/Wind Harmer
-0.074
3142433PROV 92
Adder
0.32
3142433PROV 92
Adder
0.32
3145663CRESWEL
Solar/Wind Harmer
-0.051
971163AH1-040 GEN
Solar/Wind Harmer
17.189
957481AF2-042 GEN
Solar/Wind Harmer
56.834
316023GEN1_S
Solar/Wind Harmer
1.225
971777AH1-397 GEN
Solar/Wind Harmer
2.121
3141843SHACKLE
Adder
0.82
3141766HARMONY
Solar/Wind Harmer
-0.004
3145893MURPHYS
Solar/Wind Harmer
-0.071
3145893MURPHYS
Solar/Wind Harmer
0.53
3146206CASHIE
Solar/Wind Harmer
-0.018
971547AH1-271 GEN
Solar/Wind Harmer
4.464
315693AD1-088 GEN
Solar/Wind Harmer
8.916
962491AG1-098 GEN
Solar/Wind Harmer
11.891
960081AF2-299 GEN
Solar/Wind Harmer
1.996
3146173TUNIS
Solar/Wind Harmer
-0.018
3138133OCRAN
Solar/Wind Harmer
-0.01
3145683EARLEYS
Solar/Wind Harmer
-0.017
3146263WOODLND
Solar/Wind Harmer
-0.017
971795AH1-408 GEN
Solar/Wind Harmer
13.07
316011AB1-132 GEN
Solar/Wind Harmer
3.636
962571AG1-106 GEN
Solar/Wind Harmer
2.498
316190AA2-174 GEN
Solar/Wind Harmer
0.212
3147043LAWRENC
Adder
1.392
3145823KELFORD
Solar/Wind Harmer
-0.017
3145963POPLR C
Solar/Wind Harmer
-0.017
3145783HORNRTN
Solar/Wind Harmer
-0.017
3145796HORNRTN
Solar/Wind Harmer
-0.056
3145796HORNRTN
Solar/Wind Harmer
-0.017
316174AB2-169 GEN
Solar/Wind Harmer
2.636
961951AG1-038 GEN
Solar/Wind Harmer
2.227
962861AG1-135 GEN
Solar/Wind Harmer
6.255
3144293JTRSVLE
Adder
0.458
3150351NORNECKC2
Adder
1.425
3151751LOISA D
Adder
9.244
972197AH1-683 GEN
Adder
2.827
972219AH1-694 GEN
Adder
2.035
316212AC1-099_GEN
Solar/Wind Harmer
0.638
316303AF2-085
50/50
3.567
971285AH1-108 GEN
50/50
1.443
315244AE2-183_ST
50/50
5.089
963041AG1-153 GEN
50/50
4.694
3151081ELIZAR1
50/50
17.092
3151091ELIZAR2
50/50
16.795
316164AC1-076 GEN
Solar/Wind Harmer
2.467
316233AE1-074 FULL
Solar/Wind Harmer
0.578
971281AH1-106 GEN
Solar/Wind Harmer
3.494
971283AH1-107 GEN
Solar/Wind Harmer
3.494
941031AE2-094 GEN
Solar/Wind Harmer
38.562
944011AF1-069 GEN
Solar/Wind Harmer
12.083
970673AG2-436 GEN
Solar/Wind Harmer
42.445
970673AG2-436 GEN
Solar/Wind Harmer
21.491
3143316POE
Solar/Wind Harmer
-0.079
971967AH1-528 GEN
Solar/Wind Harmer
37.503
3152611GOSPORTB
Adder
2.236
3152621GOSPORTC
Adder
1.898
3152601GOSPORTA
Adder
1.751
316315AB2-025 C
Solar/Wind Harmer
0.531
957871AF2-081 GEN
Solar/Wind Harmer
9.796
315814AE2-033 C
Solar/Wind Harmer
18.244
971445AH1-216 GEN
Solar/Wind Harmer
12.122
319010AE1-072 C
Solar/Wind Harmer
3.953
3146406KITTY HAWK
Solar/Wind Harmer
0.016
315833AF1-017_GEN
Solar/Wind Harmer
3.709
316349AD2-085 GEN
Solar/Wind Harmer
1.737
316311AC2-079 GEN
Solar/Wind Harmer
9.849
316305AF2-043 C
Solar/Wind Harmer
0.588
972265AH1-717 GEN
Adder
13.481
3151201GRAVEL4
Adder
12.638
3151191GRAVEL3
Adder
12.478
3151211GRAVEL5
Adder
12.478
316369SG1_INVT
Solar/Wind Harmer
3.482
316132AB2-190 GEN1
Solar/Wind Harmer
1.97
315835AF2-110_GEN
Solar/Wind Harmer
2.429
313526AB2-022
Solar/Wind Harmer
0.523
3146486SUNBURY
Solar/Wind Harmer
-0.019
3146486SUNBURY
Solar/Wind Harmer
-0.019
316321Z2-027
Solar/Wind Harmer
0.521
3146396TANGLEW
Solar/Wind Harmer
0.355
3145176PASQUOTANK
Solar/Wind Harmer
-0.012
970085AG2-068 GEN
Solar/Wind Harmer
11.856
970581AG2-369 GEN
Solar/Wind Harmer
10.196
315611Z1-036_GEN2
Solar/Wind Harmer
4.669
3130156CHOWAN
Solar/Wind Harmer
-0.019
3130156CHOWAN
Solar/Wind Harmer
-0.019
315976AC1-164 GENA
Solar/Wind Harmer
19.666
316169AC1-164_GENC
Solar/Wind Harmer
16.99
315975AC1-164 GENB
Solar/Wind Harmer
0.582
316312AB1-027
Solar/Wind Harmer
0.626
957831AF2-077 GEN
Solar/Wind Harmer
0.558
3138283WHITEMARSH
Solar/Wind Harmer
0.029
971167AH1-042 GEN
Solar/Wind Harmer
17.862
3142433PROV 92
Adder
0.32
3142433PROV 92
Adder
0.32
315816AE2-034 GEN
Solar/Wind Harmer
1.484
3143873LANEXA
Solar/Wind Harmer
-0.011
3130546PLYMOUTH
Solar/Wind Harmer
-0.018
316314AB2-024 C
Solar/Wind Harmer
1.54
965291AG1-394 GEN
Solar/Wind Harmer
1.598
315732AD1-074 GEN1
Solar/Wind Harmer
3.642
315733AD1-074 GEN2
Solar/Wind Harmer
3.642
315735AD1-075 GEN1
Solar/Wind Harmer
1.821
315662AE1-191 GEN
Solar/Wind Harmer
2.168
315666AE1-190 GEN
Solar/Wind Harmer
0.542
316059AD1-063 C
Solar/Wind Harmer
0.406
957601AF2-054 GEN
Solar/Wind Harmer
0.536
3141873WAN 176
Solar/Wind Harmer
-0.004
316318V4-068
Solar/Wind Harmer
0.445
3145893MURPHYS
Solar/Wind Harmer
-0.048
3145893MURPHYS
Solar/Wind Harmer
-0.018
3146206CASHIE
Solar/Wind Harmer
-0.018
970601AG2-382 GEN
Solar/Wind Harmer
7.812
946281AF1-292 GEN
Solar/Wind Harmer
0.397
972189AH1-679 GEN
Adder
2.633
3141913WHIT STONE
Solar/Wind Harmer
-0.018
3145513AHOSKIE
Solar/Wind Harmer
0.154
961941AG1-037 GEN
Solar/Wind Harmer
0.132
3145513AHOSKIE
Solar/Wind Harmer
-0.018
3146043SEABORD
Solar/Wind Harmer
-0.018
316087AB2-174 GEN
Solar/Wind Harmer
2.508
3138133OCRAN
Solar/Wind Harmer
-0.005
315607AA1-063A GEN
Solar/Wind Harmer
1.773
3145683EARLEYS
Solar/Wind Harmer
-0.035
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.017
3141783LANCAST
Solar/Wind Harmer
-0.01
3141783LANCAST
Solar/Wind Harmer
-0.007
315652AC1-086 GEN
Solar/Wind Harmer
19.55
3137643SOCKMAN
Solar/Wind Harmer
-0.069
3145796HORNRTN
Solar/Wind Harmer
-0.054
3145796HORNRTN
Solar/Wind Harmer
-0.007
962981AG1-147 GEN
Solar/Wind Harmer
7.478
3146033SCOT NK
Solar/Wind Harmer
-0.067
970831AG2-522 GEN
Solar/Wind Harmer
8.348
3150411LDYSMT5
Adder
18.158
3150381LDYSMT2
Adder
17.377
972213AH1-691 GEN
Adder
2.94
972215AH1-692 GEN
Adder
2.94
972205AH1-687 GEN
Adder
5.595
971133AH1-012 GEN
50/50
4.837
970533AG2-339 GEN
50/50
16.271
970531AG2-338 GEN
50/50
6.508
315242AE2-183_GT2
50/50
2.943
315241AE2-183_GT1
50/50
2.925
972185AH1-677 GEN
50/50
10.611
3151041BRUNSWICKG3
50/50
2.318
972187AH1-678 GEN
50/50
5.32
316447AC1-158 HLD
Solar/Wind Harmer
14.784
971223AH1-071 GEN
Solar/Wind Harmer
2.818
3143526WINTERP
Solar/Wind Harmer
-0.111
316036AC1-147 C
Solar/Wind Harmer
0.532
3150991CHESPKB
Adder
1.839
3150991CHESPKB
Adder
1.795
3142956BIRDNECK
Solar/Wind Harmer
1.058
316316AC1-027 C
Solar/Wind Harmer
0.605
316185AD1-033 GEN
Solar/Wind Harmer
2.079
316240AF1-291 C
Solar/Wind Harmer
0.594
3145506HICKORY
Solar/Wind Harmer
-0.078
3145506HICKORY
Solar/Wind Harmer
-0.047
3145506HICKORY
Solar/Wind Harmer
-0.012
970657AG2-426 GEN
Solar/Wind Harmer
6.147
970657AG2-426 GEN
Solar/Wind Harmer
1.286
3144356SAPONY
Solar/Wind Harmer
0.686
944641AF1-129 GEN
Adder
83.418
316339AD2-160 GEN
Solar/Wind Harmer
1.322
316236AE1-162_GEN
Solar/Wind Harmer
0.591
316018AA1-139 ULT2
Solar/Wind Harmer
1.678
316017AA1-139 ULT1
Solar/Wind Harmer
1.585
3137176SLIGO L2192
Solar/Wind Harmer
-0.077
3146456SLIGO L269
Solar/Wind Harmer
2.31
3130086AYDLETT
Solar/Wind Harmer
-0.078
316033AB2-134 GEN
Solar/Wind Harmer
6.285
315697AD1-025 GEN
Solar/Wind Harmer
3.942
970933AG2-581 GEN
Solar/Wind Harmer
18.245
3146386ELIZ CT
Solar/Wind Harmer
-0.019
316431W1029_GEN1
Solar/Wind Harmer
3.478
316433W1029_GEN2
Solar/Wind Harmer
3.478
3146516WINFALL
Solar/Wind Harmer
-0.019
3146516WINFALL
Solar/Wind Harmer
-0.019
3146516WINFALL
Solar/Wind Harmer
-0.019
3142366NRTHEST
Adder
0.556
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3150691DARBY 3
Adder
12.185
3150701DARBY 4
Adder
12.157
3150681DARBY 2
Adder
12.142
3150671DARBY 1
Adder
12.128
3142946ENON
Solar/Wind Harmer
-0.002
315742AE1-103 GEN
Solar/Wind Harmer
1.967
316075AC2-137 C
Solar/Wind Harmer
0.504
3146376EDENTON
Solar/Wind Harmer
0.555
3146376EDENTON
Solar/Wind Harmer
0.555
3142296MT RD221
Adder
0.528
970099AG2-077 GEN
Solar/Wind Harmer
22.734
316441AF1-014 GEN
Solar/Wind Harmer
1.216
316065AD1-022 GEN
Solar/Wind Harmer
8.955
966871AG1-558 GEN
Solar/Wind Harmer
0.538
966871AG1-558 GEN
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
0.498
3145893MURPHYS
Solar/Wind Harmer
-0.032
3146173TUNIS
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
316181AB2-040 GEN
Solar/Wind Harmer
2.443
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
316426AA2-053 GEN
Solar/Wind Harmer
1.748
3145593CAROLNA
Solar/Wind Harmer
-0.017
3145593CAROLNA
Solar/Wind Harmer
-0.017
966811AG1-552 GEN
Solar/Wind Harmer
1.941
3145593CAROLNA
Solar/Wind Harmer
0.143
3145783HORNRTN
Solar/Wind Harmer
2.035
3145783HORNRTN
Solar/Wind Harmer
1.628
3145783HORNRTN
Solar/Wind Harmer
0.509
3145783HORNRTN
Solar/Wind Harmer
0.203
3145796HORNRTN
Solar/Wind Harmer
-0.051
971741AH1-377 GEN
Solar/Wind Harmer
19.85
316487AF1-042 GEN
Solar/Wind Harmer
2.227
970301AG2-198 GEN
Solar/Wind Harmer
8.425
3144293JTRSVLE
Adder
0.458
3144293JTRSVLE
Adder
0.386
3150341NORNECKC1
Adder
1.496
3150341NORNECKC1
Adder
1.484
3151731LOISA B
Adder
9.244
3151721LOISA A
Adder
9.197
3150391LDYSMT3
Adder
18.067
972195AH1-682 GEN
Adder
2.374
3152261N ANNA2
50/50
17.068
3150861SPRUNCD
50/50
0.882
3151031BRUNSWICKG2
50/50
2.318
3151101ELIZAR3
50/50
17.311
316044AC1-158 PL1
Solar/Wind Harmer
6.723
316450AC1-158 RIC
Solar/Wind Harmer
1.793
3147666LOUISA
Solar/Wind Harmer
-0.06
315773AC2-141 GEN
Solar/Wind Harmer
8.348
315839AE2-212 C
Solar/Wind Harmer
0.598
944581AF1-123 GEN
Solar/Wind Harmer
90.063
944601AF1-125 GEN
Solar/Wind Harmer
88.657
315813AE1-149 C
Solar/Wind Harmer
12.369
965281AG1-393 GEN
Solar/Wind Harmer
2.467
3144873MCLAUGH
Solar/Wind Harmer
-0.001
970659AG2-427 GEN
Solar/Wind Harmer
1.855
3144536CHRHLND
Solar/Wind Harmer
-0.003
316083AB2-161 GEN
Solar/Wind Harmer
3.196
970661AG2-428 GEN
Solar/Wind Harmer
3.699
3145336SMITFLD
Solar/Wind Harmer
-0.008
3146456SLIGO L269
Solar/Wind Harmer
-0.019
971153AH1-033 GEN
Solar/Wind Harmer
2.384
3151221GRAVEL6
Adder
12.623
3151171GRAVELC
Adder
2.429
961611AG1-000B GEN
Solar/Wind Harmer
4.106
315778AD1-151 GEN
Solar/Wind Harmer
16.88
970129AG2-093 GEN
Solar/Wind Harmer
10.967
970133AG2-095 GEN
Solar/Wind Harmer
2.19
3143096IRON208
Adder
0.724
3143096IRON208
Adder
0.71
316313AB2-026
Solar/Wind Harmer
0.524
316258AE1-075 C
Solar/Wind Harmer
0.471
316405AF2-144 C
Solar/Wind Harmer
0.497
3143336POWHATN
Solar/Wind Harmer
1.959
316320Y1-086
Solar/Wind Harmer
1.136
3144216WINCHST
Adder
0.645
316435W1029_GEN3
Solar/Wind Harmer
3.478
3150921YORKTN3
Adder
4.287
3146516WINFALL
Solar/Wind Harmer
-0.019
970917AG2-570 GEN
Solar/Wind Harmer
47.625
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3142946ENON
Solar/Wind Harmer
-0.006
3145273HOLLAND
Solar/Wind Harmer
-0.014
316382AG1-145 C
Solar/Wind Harmer
0.572
970293AG2-193 GEN
Solar/Wind Harmer
2.359
3146376EDENTON
Solar/Wind Harmer
-0.019
3142416OLDCHRC
Solar/Wind Harmer
1.874
3142433PROV 92
Adder
0.32
3142433PROV 92
Adder
0.32
315614AA2-178 GEN
Solar/Wind Harmer
1.978
316365GEN2_N
Solar/Wind Harmer
1.225
3156081AA2-088 GEN
Solar/Wind Harmer
5.867
971157AH1-035 GEN
Solar/Wind Harmer
2.257
3141843SHACKLE
Adder
0.82
316203AE2-005 GEN
Solar/Wind Harmer
7.603
315737AD1-076 GEN
Solar/Wind Harmer
3.423
316280AD1-041 GEN
Solar/Wind Harmer
1.355
3141766HARMONY
Solar/Wind Harmer
1.601
316156AD2-030 GEN
Solar/Wind Harmer
0.479
3141873WAN 176
Solar/Wind Harmer
2.127
316473AC1-191 GEN
Solar/Wind Harmer
1.925
3145893MURPHYS
Solar/Wind Harmer
0.125
3145893MURPHYS
Solar/Wind Harmer
-0.018
3146206CASHIE
Solar/Wind Harmer
-0.018
957521AF2-046 GEN
Solar/Wind Harmer
14.027
961681AG1-008 GEN
Solar/Wind Harmer
14.027
3132273ORANGE
Solar/Wind Harmer
-0.004
966621AG1-532 GEN
Solar/Wind Harmer
0.36
3146173TUNIS
Solar/Wind Harmer
-0.018
3156021HOLLOMANSOL
Solar/Wind Harmer
2.376
316463AE2-346 GEN
Solar/Wind Harmer
0.285
316140AB2-099
Solar/Wind Harmer
0.119
962331AG1-082 GEN
Solar/Wind Harmer
2.202
313506AB2-031 GEN
Solar/Wind Harmer
1.407
316478AD1-087 GEN
Solar/Wind Harmer
1.513
316486AD2-202 GEN
Solar/Wind Harmer
0.443
3146263WOODLND
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3147043LAWRENC
Solar/Wind Harmer
-0.01
316317KELFORD C
Solar/Wind Harmer
0.812
3145823KELFORD
Solar/Wind Harmer
-0.017
3145963POPLR C
Solar/Wind Harmer
-0.017
3145796HORNRTN
Solar/Wind Harmer
-0.068
3145796HORNRTN
Solar/Wind Harmer
-0.017
962971AG1-146 GEN
Solar/Wind Harmer
3.205
316484AD2-074 GEN
Solar/Wind Harmer
4.255
970009AG2-005 GEN
Solar/Wind Harmer
2.113
970909AG2-566 GEN
Solar/Wind Harmer
1.6
3144293JTRSVLE
Adder
0.458
3150351NORNECKC2
Adder
1.449
3151761LOISA E
Adder
18.847
972183AH1-676 GEN
Adder
147.354
3150401LDYSMT4
Adder
18.101
3150371LDYSMT1
Adder
17.49
316210AC1-098 GEN
Solar/Wind Harmer
1.148
LAGNLTFEXP_LAGN->PJM
CLTF
5.963
CBM South 2LTFEXP_CBM-S2->PJM
CBM
19.52
TVALTFEXP_TVA->PJM
CLTF
3.02
CPLELTFEXP_CPLE->PJM
CLTF
9
CBM West 2LTFEXP_CBM-W2->PJM
CBM
30.036
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.817
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.186
MECLTFEXP_MEC->PJM
CLTF
2.509
SIGELTFEXP_SIGE->PJM
CLTF
0.076
NYPJM->LTFIMP_NY
CLTF
2.547
LGEELTFEXP_LGEE->PJM
CLTF
0.9
WECLTFEXP_WEC->PJM
CLTF
0.426

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:129.41 %
Rating:3220.44 MVA
Rating Type:A
MVA to Mitigate:4167.61
MW Contribution:7.04
Bus #Bus NameTypeMW Contribution
3152251N ANNA1
50/50
17.069
971507AH1-251 GEN
50/50
10.56
970119AG2-088 GEN
50/50
26.753
3150851SPRUNCC
50/50
0.882
315243AE2-183_GT3
50/50
2.943
3151051BRUNSWICKS1
50/50
4.812
3151021BRUNSWICKG1
50/50
2.318
971451AH1-221 GEN
50/50
7.041
316045AC1-158 PL2
Solar/Wind Harmer
9.498
3147666LOUISA
Solar/Wind Harmer
0.935
316192AB2-158 GEN
Solar/Wind Harmer
1.293
3143226MDLTHAN
Solar/Wind Harmer
0.2
3143526WINTERP
Solar/Wind Harmer
0.994
940641AE2-051 GEN
Solar/Wind Harmer
14.986
939411AE1-173 GEN
Solar/Wind Harmer
78.651
316294AC1-161 GEN
Solar/Wind Harmer
3.077
944591AF1-124 GEN
Solar/Wind Harmer
39.816
316375AC2-012 GEN
Solar/Wind Harmer
0.004
3150981CHESPKA
Adder
2.192
970659AG2-427 GEN
Solar/Wind Harmer
8.481
316381AD1-082 GEN
Solar/Wind Harmer
0.183
315671AE2-027_GEN
Solar/Wind Harmer
11.214
3142543TWELFTH
Solar/Wind Harmer
0.017
970661AG2-428 GEN
Solar/Wind Harmer
17.39
316388AE2-253 GEN
Solar/Wind Harmer
0.547
3145336SMITFLD
Solar/Wind Harmer
0.697
3146456SLIGO L269
Solar/Wind Harmer
0.174
316246AF1-032 C
Solar/Wind Harmer
0.078
3151171GRAVELC
Adder
1.847
961611AG1-000B GEN
Solar/Wind Harmer
9.102
971647AH1-324 GEN
Solar/Wind Harmer
7.403
316072AD1-144
Solar/Wind Harmer
0.063
971069AG2-661 GEN
Solar/Wind Harmer
3.083
316458AB2-190 GEN2
Solar/Wind Harmer
0.93
970129AG2-093 GEN
Solar/Wind Harmer
4.931
3143096IRON208
Adder
0.724
316093AE2-104_GEN
Solar/Wind Harmer
2.908
3143336POWHATN
Solar/Wind Harmer
3.072
3138126ROCKLANDING
Solar/Wind Harmer
0.078
944631AF1-128 GEN
Adder
81.389
3146516WINFALL
Solar/Wind Harmer
0.552
3146516WINFALL
Solar/Wind Harmer
0.17
970919AG2-571 GEN
Solar/Wind Harmer
6.028
316159AE1-175 C
Solar/Wind Harmer
0.146
971317AH1-138 GEN
Solar/Wind Harmer
1.261
970087AG2-069 GEN
Solar/Wind Harmer
13.506
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.166
316336AC2-165 C
Solar/Wind Harmer
0.006
3142416OLDCHRC
Solar/Wind Harmer
0.43
3142416OLDCHRC
Solar/Wind Harmer
0.165
3142433PROV 92
Solar/Wind Harmer
0.658
3142433PROV 92
Adder
0.32
3142433PROV 92
Adder
0.32
3145663CRESWEL
Solar/Wind Harmer
0.457
971163AH1-040 GEN
Solar/Wind Harmer
13.055
957481AF2-042 GEN
Solar/Wind Harmer
43.165
316023GEN1_S
Solar/Wind Harmer
0.363
971777AH1-397 GEN
Solar/Wind Harmer
0.424
3141843SHACKLE
Adder
0.82
3141766HARMONY
Solar/Wind Harmer
0.032
3145893MURPHYS
Solar/Wind Harmer
0.635
3145893MURPHYS
Solar/Wind Harmer
0.706
3146206CASHIE
Solar/Wind Harmer
0.159
971547AH1-271 GEN
Solar/Wind Harmer
3.39
315693AD1-088 GEN
Solar/Wind Harmer
7.618
962491AG1-098 GEN
Solar/Wind Harmer
9.031
960081AF2-299 GEN
Solar/Wind Harmer
1.516
3146173TUNIS
Solar/Wind Harmer
0.157
3138133OCRAN
Solar/Wind Harmer
0.094
3145683EARLEYS
Solar/Wind Harmer
0.156
3146263WOODLND
Solar/Wind Harmer
0.155
971795AH1-408 GEN
Solar/Wind Harmer
10.34
316011AB1-132 GEN
Solar/Wind Harmer
2.811
962571AG1-106 GEN
Solar/Wind Harmer
2.2
316190AA2-174 GEN
Solar/Wind Harmer
0
3147043LAWRENC
Adder
1.392
3145823KELFORD
Solar/Wind Harmer
0.153
3145963POPLR C
Solar/Wind Harmer
0.153
3145783HORNRTN
Solar/Wind Harmer
0.152
3145796HORNRTN
Solar/Wind Harmer
0.502
3145796HORNRTN
Solar/Wind Harmer
0.152
316174AB2-169 GEN
Solar/Wind Harmer
0.004
962861AG1-135 GEN
Solar/Wind Harmer
4.751
316212AC1-099_GEN
Solar/Wind Harmer
0.768
316129AC1-054 GEN
Solar/Wind Harmer
0.557
971065AG2-659 GEN
Solar/Wind Harmer
6.296
3146293MARTNCO
Solar/Wind Harmer
0.137
970937AG2-583 GEN
Solar/Wind Harmer
9.004
315687AD1-152 GEN
Solar/Wind Harmer
0.005
966881AG1-559 GEN
Solar/Wind Harmer
0.168
3141726DUNNSVL
Solar/Wind Harmer
0.58
315722AD1-056 GEN
Solar/Wind Harmer
0.916
3145746EVERETS
Solar/Wind Harmer
0.144
3145746EVERETS
Solar/Wind Harmer
0.144
970685AG2-442 GEN
Solar/Wind Harmer
10.759
316254AC1-120 GEN1
Solar/Wind Harmer
0.307
316237AB2-079_GEN
Solar/Wind Harmer
0.001
963171AG1-166 GEN
Solar/Wind Harmer
0.768
971563AH1-280 GEN
Solar/Wind Harmer
1.536
3144293JTRSVLE
Adder
0.458
3146926FARMVIL
Solar/Wind Harmer
0.086
3150351NORNECKC2
Adder
1.425
316494AC1-189 GEN
Solar/Wind Harmer
0.481
3151751LOISA D
Adder
9.244
3146233WITAKRS
Solar/Wind Harmer
0.561
961671AG1-007 GEN
Solar/Wind Harmer
0.022
3146083TARBORO
Solar/Wind Harmer
0.141
3145493TOT1
Solar/Wind Harmer
0.626
3145543BTLEBRO
Solar/Wind Harmer
0.138
3145543BTLEBRO
Solar/Wind Harmer
0.111
316359AB2-059 GEN
Solar/Wind Harmer
0.498
316049AB1-081 GEN
Solar/Wind Harmer
0.793
3142053HEARTS
Solar/Wind Harmer
0.244
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.055
970401AG2-262 GEN
Solar/Wind Harmer
0.803
316337AD2-073 GEN
Solar/Wind Harmer
0.118
972197AH1-683 GEN
Adder
2.827
972219AH1-694 GEN
Adder
2.035
972003AH1-546 GEN
Solar/Wind Harmer
5.618
316003AC1-222 GEN
Solar/Wind Harmer
0.003
971377AH1-170 GEN
Solar/Wind Harmer
1.304
3147623JAMES R
Solar/Wind Harmer
0.283
972135AH1-637 GEN
Solar/Wind Harmer
0.976
316303AF2-085
50/50
3.567
971285AH1-108 GEN
50/50
1.443
315244AE2-183_ST
50/50
5.089
963041AG1-153 GEN
50/50
4.694
3151081ELIZAR1
50/50
17.092
3151091ELIZAR2
50/50
16.795
316164AC1-076 GEN
Solar/Wind Harmer
0.366
316233AE1-074 FULL
Solar/Wind Harmer
0.153
971281AH1-106 GEN
Solar/Wind Harmer
2.654
971283AH1-107 GEN
Solar/Wind Harmer
2.654
941031AE2-094 GEN
Solar/Wind Harmer
33.713
944011AF1-069 GEN
Solar/Wind Harmer
11.015
970673AG2-436 GEN
Solar/Wind Harmer
38.362
970673AG2-436 GEN
Solar/Wind Harmer
25.574
3143316POE
Solar/Wind Harmer
0.707
971967AH1-528 GEN
Solar/Wind Harmer
28.408
3152611GOSPORTB
Adder
2.236
3152621GOSPORTC
Adder
1.898
3152601GOSPORTA
Adder
1.751
316315AB2-025 C
Solar/Wind Harmer
0.141
957871AF2-081 GEN
Solar/Wind Harmer
8.68
315814AE2-033 C
Solar/Wind Harmer
13.794
971445AH1-216 GEN
Solar/Wind Harmer
12.275
319010AE1-072 C
Solar/Wind Harmer
0.876
3146406KITTY HAWK
Solar/Wind Harmer
0.022
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.119
316311AC2-079 GEN
Solar/Wind Harmer
4.99
316305AF2-043 C
Solar/Wind Harmer
0.001
972265AH1-717 GEN
Adder
13.481
3151201GRAVEL4
Adder
12.638
3151191GRAVEL3
Adder
12.478
3151211GRAVEL5
Adder
12.478
316369SG1_INVT
Solar/Wind Harmer
0.006
316132AB2-190 GEN1
Solar/Wind Harmer
0.93
315835AF2-110_GEN
Solar/Wind Harmer
1.187
313526AB2-022
Solar/Wind Harmer
0.093
3146486SUNBURY
Solar/Wind Harmer
0.172
3146486SUNBURY
Solar/Wind Harmer
0.172
316321Z2-027
Solar/Wind Harmer
0.032
3146396TANGLEW
Solar/Wind Harmer
0.473
3145176PASQUOTANK
Solar/Wind Harmer
0.106
970085AG2-068 GEN
Solar/Wind Harmer
9.004
970581AG2-369 GEN
Solar/Wind Harmer
7.744
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.166
3130156CHOWAN
Solar/Wind Harmer
0.166
315976AC1-164 GENA
Solar/Wind Harmer
17.177
316169AC1-164_GENC
Solar/Wind Harmer
14.839
315975AC1-164 GENB
Solar/Wind Harmer
0.508
316312AB1-027
Solar/Wind Harmer
0.296
3138283WHITEMARSH
Solar/Wind Harmer
0.038
971167AH1-042 GEN
Solar/Wind Harmer
14.667
3142433PROV 92
Adder
0.32
3142433PROV 92
Adder
0.32
315816AE2-034 GEN
Solar/Wind Harmer
0.7
3143873LANEXA
Solar/Wind Harmer
0.097
3130546PLYMOUTH
Solar/Wind Harmer
0.161
970189AG2-124 GEN
Solar/Wind Harmer
4.756
316314AB2-024 C
Solar/Wind Harmer
0.001
965291AG1-394 GEN
Solar/Wind Harmer
0.712
315732AD1-074 GEN1
Solar/Wind Harmer
0.921
315733AD1-074 GEN2
Solar/Wind Harmer
0.921
315735AD1-075 GEN1
Solar/Wind Harmer
0.461
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.032
3145893MURPHYS
Solar/Wind Harmer
0.429
3145893MURPHYS
Solar/Wind Harmer
0.159
3146206CASHIE
Solar/Wind Harmer
0.159
970601AG2-382 GEN
Solar/Wind Harmer
5.933
972189AH1-679 GEN
Adder
2.633
3141913WHIT STONE
Solar/Wind Harmer
0.157
3145513AHOSKIE
Solar/Wind Harmer
0.328
3145513AHOSKIE
Solar/Wind Harmer
0.157
3146043SEABORD
Solar/Wind Harmer
0.156
316087AB2-174 GEN
Solar/Wind Harmer
0.004
3138133OCRAN
Solar/Wind Harmer
0.047
315607AA1-063A GEN
Solar/Wind Harmer
0.319
3145683EARLEYS
Solar/Wind Harmer
0.312
3145683EARLEYS
Solar/Wind Harmer
0.156
3145683EARLEYS
Solar/Wind Harmer
0.156
3141783LANCAST
Solar/Wind Harmer
0.093
3141783LANCAST
Solar/Wind Harmer
0.062
315652AC1-086 GEN
Solar/Wind Harmer
17.007
3137643SOCKMAN
Solar/Wind Harmer
0.617
3145796HORNRTN
Solar/Wind Harmer
0.487
3145796HORNRTN
Solar/Wind Harmer
0.061
962981AG1-147 GEN
Solar/Wind Harmer
5.679
3146033SCOT NK
Solar/Wind Harmer
0.602
970327AG2-215 GEN
Solar/Wind Harmer
4.937
970831AG2-522 GEN
Solar/Wind Harmer
6.34
316005AA1-067
Solar/Wind Harmer
0.155
3145746EVERETS
Solar/Wind Harmer
0.575
3145746EVERETS
Solar/Wind Harmer
0.144
3145746EVERETS
Solar/Wind Harmer
0.144
3145746EVERETS
Solar/Wind Harmer
0.144
970181AG2-120 GEN
Solar/Wind Harmer
1.799
971443AH1-215 GEN
Solar/Wind Harmer
2.423
3144303KENBRDG
Solar/Wind Harmer
0.115
970683AG2-441 GEN
Solar/Wind Harmer
9.607
970681AG2-440 GEN
Solar/Wind Harmer
7.685
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
946301AF1-294 GEN
Solar/Wind Harmer
2.841
961791AG1-021 GEN
Solar/Wind Harmer
1.382
315657AE1-056 GEN
Solar/Wind Harmer
4.964
3141813NORNECK
Solar/Wind Harmer
0.143
957861AF2-080 GEN
Solar/Wind Harmer
6.144
316420AA1-050 GEN
Solar/Wind Harmer
0.005
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.141
3145573BETHELC
Solar/Wind Harmer
0.141
970285AG2-188 GEN
Solar/Wind Harmer
11.015
971845AH1-439 GEN
Solar/Wind Harmer
6.271
3150411LDYSMT5
Adder
18.158
3150381LDYSMT2
Adder
17.377
972213AH1-691 GEN
Adder
2.94
972215AH1-692 GEN
Adder
2.94
3147346CASHSCORNER
Solar/Wind Harmer
0.311
316118AC1-105 GEN
Solar/Wind Harmer
0.346
3147173SINAI
Solar/Wind Harmer
0.131
3147243WELCO
Solar/Wind Harmer
0.082
972205AH1-687 GEN
Adder
5.595
316223AC1-118
Solar/Wind Harmer
0.091
971447AH1-217 GEN
Solar/Wind Harmer
3.599
970865AG2-541 GEN
Solar/Wind Harmer
4.024
971133AH1-012 GEN
50/50
4.837
970533AG2-339 GEN
50/50
16.271
970531AG2-338 GEN
50/50
6.508
315242AE2-183_GT2
50/50
2.943
315241AE2-183_GT1
50/50
2.925
972185AH1-677 GEN
50/50
10.611
3151041BRUNSWICKG3
50/50
2.318
972187AH1-678 GEN
50/50
5.32
316447AC1-158 HLD
Solar/Wind Harmer
6.529
971223AH1-071 GEN
Solar/Wind Harmer
2.14
3143526WINTERP
Solar/Wind Harmer
0.994
316036AC1-147 C
Solar/Wind Harmer
0.033
3150991CHESPKB
Adder
1.839
3150991CHESPKB
Adder
1.795
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.168
316185AD1-033 GEN
Solar/Wind Harmer
0.005
316240AF1-291 C
Solar/Wind Harmer
0.001
3145506HICKORY
Solar/Wind Harmer
0.7
3145506HICKORY
Solar/Wind Harmer
0.42
3145506HICKORY
Solar/Wind Harmer
0.105
970657AG2-426 GEN
Solar/Wind Harmer
6.132
970657AG2-426 GEN
Solar/Wind Harmer
1.286
3144356SAPONY
Solar/Wind Harmer
1.464
944641AF1-129 GEN
Adder
83.418
316339AD2-160 GEN
Solar/Wind Harmer
0.283
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316018AA1-139 ULT2
Solar/Wind Harmer
0.004
316017AA1-139 ULT1
Solar/Wind Harmer
0.097
3137176SLIGO L2192
Solar/Wind Harmer
0.693
3146456SLIGO L269
Solar/Wind Harmer
3.08
3130086AYDLETT
Solar/Wind Harmer
0.695
316033AB2-134 GEN
Solar/Wind Harmer
0.01
315697AD1-025 GEN
Solar/Wind Harmer
0.195
970933AG2-581 GEN
Solar/Wind Harmer
13.857
3146386ELIZ CT
Solar/Wind Harmer
0.172
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.17
3146516WINFALL
Solar/Wind Harmer
0.17
3146516WINFALL
Solar/Wind Harmer
0.17
3142366NRTHEST
Adder
0.556
3146626S HERTFORD
Solar/Wind Harmer
0.169
3146626S HERTFORD
Solar/Wind Harmer
0.169
3150691DARBY 3
Adder
12.185
3150701DARBY 4
Adder
12.157
3150681DARBY 2
Adder
12.142
3150671DARBY 1
Adder
12.128
3142946ENON
Solar/Wind Harmer
0.017
315742AE1-103 GEN
Solar/Wind Harmer
0.002
316075AC2-137 C
Solar/Wind Harmer
0.046
3146376EDENTON
Solar/Wind Harmer
0.74
3146376EDENTON
Solar/Wind Harmer
0.74
3142296MT RD221
Adder
0.528
970099AG2-077 GEN
Solar/Wind Harmer
17.266
316065AD1-022 GEN
Solar/Wind Harmer
7.34
966871AG1-558 GEN
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
1.063
3145893MURPHYS
Solar/Wind Harmer
0.286
3146173TUNIS
Solar/Wind Harmer
0.157
3146173TUNIS
Solar/Wind Harmer
0.157
316181AB2-040 GEN
Solar/Wind Harmer
0.226
3142666NORTHAMPTON
Solar/Wind Harmer
0.155
3142666NORTHAMPTON
Solar/Wind Harmer
0.155
3142666NORTHAMPTON
Solar/Wind Harmer
0.155
3142666NORTHAMPTON
Solar/Wind Harmer
0.093
316426AA2-053 GEN
Solar/Wind Harmer
0.52
3145593CAROLNA
Solar/Wind Harmer
0.153
3145593CAROLNA
Solar/Wind Harmer
0.153
966811AG1-552 GEN
Solar/Wind Harmer
1.665
3145593CAROLNA
Solar/Wind Harmer
0.191
3145783HORNRTN
Solar/Wind Harmer
2.713
3145783HORNRTN
Solar/Wind Harmer
2.17
3145783HORNRTN
Solar/Wind Harmer
0.678
3145783HORNRTN
Solar/Wind Harmer
0.271
3145796HORNRTN
Solar/Wind Harmer
0.457
971741AH1-377 GEN
Solar/Wind Harmer
15.076
970301AG2-198 GEN
Solar/Wind Harmer
6.399
958261AF2-120 GEN
Solar/Wind Harmer
4.886
316274AC1-208 GEN
Solar/Wind Harmer
0.766
3145933PARMELE
Solar/Wind Harmer
0.295
3145933PARMELE
Solar/Wind Harmer
0.147
957411AF2-035 GEN
Solar/Wind Harmer
6.2
970317AG2-208 GEN
Solar/Wind Harmer
5.744
939181AE1-148 GEN
Solar/Wind Harmer
6.96
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.011
970323AG2-213 GEN
Solar/Wind Harmer
6.152
971775AH1-396 GEN
Solar/Wind Harmer
0.231
958211AF2-115 GEN
Solar/Wind Harmer
1.728
963191AG1-168 GEN
Solar/Wind Harmer
0.576
3144293JTRSVLE
Adder
0.458
3144293JTRSVLE
Adder
0.386
3147133PAMPLIN
Solar/Wind Harmer
0.144
3147133PAMPLIN
Solar/Wind Harmer
0.115
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
1.496
3150341NORNECKC1
Adder
1.484
966001AG1-469 GEN
Solar/Wind Harmer
0.083
3151731LOISA B
Adder
9.244
3151721LOISA A
Adder
9.197
315673AE1-157 GEN
Solar/Wind Harmer
9.786
3145493TOT1
Solar/Wind Harmer
0.326
3145453TOT5
Solar/Wind Harmer
0.196
3145603CNETO
Solar/Wind Harmer
0.13
961601AG1-000A GEN
Solar/Wind Harmer
2.463
316263AC1-034 GEN
Solar/Wind Harmer
5.264
962561AG1-105 GEN
Solar/Wind Harmer
6.627
3146776BUCKING
Solar/Wind Harmer
0.551
3146776BUCKING
Solar/Wind Harmer
0.045
964791AG1-342 GEN
Solar/Wind Harmer
2.629
3146843MT LREL
Solar/Wind Harmer
0.137
3146843MT LREL
Solar/Wind Harmer
0.137
3150391LDYSMT3
Adder
18.067
972195AH1-682 GEN
Adder
2.374
316468AD1-105 GEN
Solar/Wind Harmer
-0.044
971489AH1-241 GEN
Solar/Wind Harmer
6.519
316222AC1-221 GEN
Solar/Wind Harmer
0.492
3152261N ANNA2
50/50
17.068
3150861SPRUNCD
50/50
0.882
3151031BRUNSWICKG2
50/50
2.318
3151101ELIZAR3
50/50
17.311
316044AC1-158 PL1
Solar/Wind Harmer
2.971
316450AC1-158 RIC
Solar/Wind Harmer
0.792
3147666LOUISA
Solar/Wind Harmer
0.538
315773AC2-141 GEN
Solar/Wind Harmer
6.485
315839AE2-212 C
Solar/Wind Harmer
0.001
944581AF1-123 GEN
Solar/Wind Harmer
39.675
944601AF1-125 GEN
Solar/Wind Harmer
39.064
315813AE1-149 C
Solar/Wind Harmer
9.394
965281AG1-393 GEN
Solar/Wind Harmer
1.874
3144873MCLAUGH
Solar/Wind Harmer
0.004
970659AG2-427 GEN
Solar/Wind Harmer
1.855
3144536CHRHLND
Solar/Wind Harmer
0.026
316083AB2-161 GEN
Solar/Wind Harmer
0.002
970661AG2-428 GEN
Solar/Wind Harmer
3.699
3145336SMITFLD
Solar/Wind Harmer
0.07
3146456SLIGO L269
Solar/Wind Harmer
0.174
971153AH1-033 GEN
Solar/Wind Harmer
2.012
3151221GRAVEL6
Adder
12.623
3151171GRAVELC
Adder
2.429
961611AG1-000B GEN
Solar/Wind Harmer
4.628
315778AD1-151 GEN
Solar/Wind Harmer
13.874
970129AG2-093 GEN
Solar/Wind Harmer
10.479
970133AG2-095 GEN
Solar/Wind Harmer
1.663
3143096IRON208
Adder
0.724
3143096IRON208
Adder
0.71
316313AB2-026
Solar/Wind Harmer
0.109
316258AE1-075 C
Solar/Wind Harmer
0.13
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
2.611
316320Y1-086
Solar/Wind Harmer
0.001
3144216WINCHST
Adder
0.645
316435W1029_GEN3
Solar/Wind Harmer
0.001
3150921YORKTN3
Adder
4.287
3146516WINFALL
Solar/Wind Harmer
0.17
970917AG2-570 GEN
Solar/Wind Harmer
15.071
3146626S HERTFORD
Solar/Wind Harmer
0.169
3142946ENON
Solar/Wind Harmer
0.057
3145273HOLLAND
Solar/Wind Harmer
0.127
316382AG1-145 C
Solar/Wind Harmer
0.001
970293AG2-193 GEN
Solar/Wind Harmer
1.792
3146376EDENTON
Solar/Wind Harmer
0.166
3142416OLDCHRC
Solar/Wind Harmer
1.602
3142433PROV 92
Adder
0.32
3142433PROV 92
Adder
0.32
315614AA2-178 GEN
Solar/Wind Harmer
0.934
316365GEN2_N
Solar/Wind Harmer
0.363
3156081AA2-088 GEN
Solar/Wind Harmer
0.004
971157AH1-035 GEN
Solar/Wind Harmer
1.929
3141843SHACKLE
Adder
0.82
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
315737AD1-076 GEN
Solar/Wind Harmer
2.062
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
2.134
316156AD2-030 GEN
Solar/Wind Harmer
0.118
3141873WAN 176
Solar/Wind Harmer
2.836
316473AC1-191 GEN
Solar/Wind Harmer
0.538
3145893MURPHYS
Solar/Wind Harmer
0.266
3145893MURPHYS
Solar/Wind Harmer
0.159
3146206CASHIE
Solar/Wind Harmer
0.159
957521AF2-046 GEN
Solar/Wind Harmer
11.795
961681AG1-008 GEN
Solar/Wind Harmer
11.795
3132273ORANGE
Solar/Wind Harmer
0.032
3146173TUNIS
Solar/Wind Harmer
0.157
3156021HOLLOMANSOL
Solar/Wind Harmer
0.713
316463AE2-346 GEN
Solar/Wind Harmer
0.135
316140AB2-099
Solar/Wind Harmer
0.056
962331AG1-082 GEN
Solar/Wind Harmer
1.672
313506AB2-031 GEN
Solar/Wind Harmer
0.482
316478AD1-087 GEN
Solar/Wind Harmer
0.543
316486AD2-202 GEN
Solar/Wind Harmer
0.159
3146263WOODLND
Solar/Wind Harmer
0.155
3142666NORTHAMPTON
Solar/Wind Harmer
0.155
3147043LAWRENC
Solar/Wind Harmer
0.092
316317KELFORD C
Solar/Wind Harmer
0.015
3145823KELFORD
Solar/Wind Harmer
0.153
3145963POPLR C
Solar/Wind Harmer
0.153
3145796HORNRTN
Solar/Wind Harmer
0.609
3145796HORNRTN
Solar/Wind Harmer
0.152
962971AG1-146 GEN
Solar/Wind Harmer
2.434
970009AG2-005 GEN
Solar/Wind Harmer
1.123
970909AG2-566 GEN
Solar/Wind Harmer
1.6
316210AC1-098 GEN
Solar/Wind Harmer
1.377
316404AE1-155 C
Solar/Wind Harmer
0.033
3145933PARMELE
Solar/Wind Harmer
0.147
966801AG1-551 GEN
Solar/Wind Harmer
1.716
315724AD1-057 GEN
Solar/Wind Harmer
0.543
3145746EVERETS
Solar/Wind Harmer
0.144
3145746EVERETS
Solar/Wind Harmer
0.144
316131AB2-060 GEN
Solar/Wind Harmer
0.454
964241AG1-285 GEN
Solar/Wind Harmer
9.624
315785AD2-033 C
Solar/Wind Harmer
1.173
970257AG2-171 GEN
Solar/Wind Harmer
4.614
959311AF2-222 GEN
Solar/Wind Harmer
12.815
316170AC1-121 GEN2
Solar/Wind Harmer
0.154
963181AG1-167 GEN
Solar/Wind Harmer
0.576
3144293JTRSVLE
Adder
0.458
3147133PAMPLIN
Solar/Wind Harmer
0.452
971193AH1-056 GEN
Solar/Wind Harmer
8.764
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.086
316327AA2-057 GEN
Solar/Wind Harmer
0.217
3150351NORNECKC2
Adder
1.449
3151761LOISA E
Adder
18.847
3146233WITAKRS
Solar/Wind Harmer
0.708
3146233WITAKRS
Solar/Wind Harmer
0.096
3138543CONSLDL
Solar/Wind Harmer
0.093
3146073TAR RVR
Solar/Wind Harmer
0.141
3146083TARBORO
Solar/Wind Harmer
0.141
961601AG1-000A GEN
Solar/Wind Harmer
9.854
3145543BTLEBRO
Solar/Wind Harmer
0.138
3145543BTLEBRO
Solar/Wind Harmer
0.138
971623AH1-311 GEN
Solar/Wind Harmer
0.277
972183AH1-676 GEN
Adder
147.354
3146776BUCKING
Solar/Wind Harmer
0.05
3150401LDYSMT4
Adder
18.101
3150371LDYSMT1
Adder
17.49
971781AH1-399 GEN
Solar/Wind Harmer
0.177
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
5.61
3141906WESTMOR
Solar/Wind Harmer
0.051
970221AG2-151 GEN
Solar/Wind Harmer
6.519
971683AH1-343 GEN
Solar/Wind Harmer
4.456
970737AG2-469 GEN
Solar/Wind Harmer
5.095
316283AC2-100 C
Solar/Wind Harmer
0.231
LAGNLTFEXP_LAGN->PJM
CLTF
5.963
CBM South 2LTFEXP_CBM-S2->PJM
CBM
19.52
TVALTFEXP_TVA->PJM
CLTF
3.02
CPLELTFEXP_CPLE->PJM
CLTF
9
CBM West 2LTFEXP_CBM-W2->PJM
CBM
30.036
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.817
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.186
MECLTFEXP_MEC->PJM
CLTF
2.509
SIGELTFEXP_SIGE->PJM
CLTF
0.076
NYPJM->LTFIMP_NY
CLTF
2.547
LGEELTFEXP_LGEE->PJM
CLTF
0.9
WECLTFEXP_WEC->PJM
CLTF
0.426

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o AP_P2-2_WP-500-DRT14_SRT-SL


Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-500-DRT14_SRT-SL
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:113.81 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4484.12
MW Contribution:7.03
Bus #Bus NameTypeMW Contribution
971133AH1-012 GEN
50/50
4.834
970533AG2-339 GEN
50/50
16.254
970531AG2-338 GEN
50/50
6.502
315242AE2-183_GT2
50/50
2.94
315241AE2-183_GT1
50/50
2.922
972185AH1-677 GEN
50/50
10.6
3151041BRUNSWICKG3
50/50
2.316
972187AH1-678 GEN
50/50
5.314
316447AC1-158 HLD
Solar/Wind Harmer
14.78
971223AH1-071 GEN
Solar/Wind Harmer
2.815
3143526WINTERP
Solar/Wind Harmer
-0.111
316036AC1-147 C
Solar/Wind Harmer
0.532
3150991CHESPKB
Adder
1.837
3150991CHESPKB
Adder
1.793
3142956BIRDNECK
Solar/Wind Harmer
1.057
316316AC1-027 C
Solar/Wind Harmer
0.604
316185AD1-033 GEN
Solar/Wind Harmer
2.077
316240AF1-291 C
Solar/Wind Harmer
0.593
3145506HICKORY
Solar/Wind Harmer
-0.078
3145506HICKORY
Solar/Wind Harmer
-0.047
3145506HICKORY
Solar/Wind Harmer
-0.012
970657AG2-426 GEN
Solar/Wind Harmer
6.141
970657AG2-426 GEN
Solar/Wind Harmer
1.284
3144356SAPONY
Solar/Wind Harmer
0.685
944641AF1-129 GEN
Adder
83.329
316339AD2-160 GEN
Solar/Wind Harmer
1.321
316236AE1-162_GEN
Solar/Wind Harmer
0.59
316018AA1-139 ULT2
Solar/Wind Harmer
1.677
316017AA1-139 ULT1
Solar/Wind Harmer
1.584
3137176SLIGO L2192
Solar/Wind Harmer
-0.077
3146456SLIGO L269
Solar/Wind Harmer
2.307
3130086AYDLETT
Solar/Wind Harmer
-0.078
316033AB2-134 GEN
Solar/Wind Harmer
6.278
315697AD1-025 GEN
Solar/Wind Harmer
3.937
970933AG2-581 GEN
Solar/Wind Harmer
18.225
3146386ELIZ CT
Solar/Wind Harmer
-0.019
316431W1029_GEN1
Solar/Wind Harmer
3.474
316433W1029_GEN2
Solar/Wind Harmer
3.474
3146516WINFALL
Solar/Wind Harmer
-0.019
3146516WINFALL
Solar/Wind Harmer
-0.019
3146516WINFALL
Solar/Wind Harmer
-0.019
3142366NRTHEST
Adder
0.555
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3150691DARBY 3
Adder
12.171
3150701DARBY 4
Adder
12.143
3150681DARBY 2
Adder
12.129
3150671DARBY 1
Adder
12.115
3142946ENON
Solar/Wind Harmer
-0.002
315742AE1-103 GEN
Solar/Wind Harmer
1.965
316075AC2-137 C
Solar/Wind Harmer
0.504
3146376EDENTON
Solar/Wind Harmer
0.554
3146376EDENTON
Solar/Wind Harmer
0.554
3142296MT RD221
Adder
0.528
970099AG2-077 GEN
Solar/Wind Harmer
22.707
316441AF1-014 GEN
Solar/Wind Harmer
1.214
316065AD1-022 GEN
Solar/Wind Harmer
8.945
966871AG1-558 GEN
Solar/Wind Harmer
0.537
966871AG1-558 GEN
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
0.498
3145893MURPHYS
Solar/Wind Harmer
-0.032
3146173TUNIS
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
316181AB2-040 GEN
Solar/Wind Harmer
2.44
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
316426AA2-053 GEN
Solar/Wind Harmer
1.746
3145593CAROLNA
Solar/Wind Harmer
-0.017
3145593CAROLNA
Solar/Wind Harmer
-0.017
966811AG1-552 GEN
Solar/Wind Harmer
1.938
3145593CAROLNA
Solar/Wind Harmer
0.143
3145783HORNRTN
Solar/Wind Harmer
2.032
3145783HORNRTN
Solar/Wind Harmer
1.626
3145783HORNRTN
Solar/Wind Harmer
0.508
3145783HORNRTN
Solar/Wind Harmer
0.203
3145796HORNRTN
Solar/Wind Harmer
-0.051
971741AH1-377 GEN
Solar/Wind Harmer
19.825
316487AF1-042 GEN
Solar/Wind Harmer
2.224
970301AG2-198 GEN
Solar/Wind Harmer
8.414
3144293JTRSVLE
Adder
0.458
3144293JTRSVLE
Adder
0.385
3150341NORNECKC1
Adder
1.494
3150341NORNECKC1
Adder
1.483
3151731LOISA B
Adder
9.232
3151721LOISA A
Adder
9.185
3150391LDYSMT3
Adder
18.042
972195AH1-682 GEN
Adder
2.371
3152261N ANNA2
50/50
17.059
3150861SPRUNCD
50/50
0.881
3151031BRUNSWICKG2
50/50
2.316
3151101ELIZAR3
50/50
17.292
316044AC1-158 PL1
Solar/Wind Harmer
6.721
316450AC1-158 RIC
Solar/Wind Harmer
1.792
3147666LOUISA
Solar/Wind Harmer
-0.06
315773AC2-141 GEN
Solar/Wind Harmer
8.339
315839AE2-212 C
Solar/Wind Harmer
0.598
944581AF1-123 GEN
Solar/Wind Harmer
89.967
944601AF1-125 GEN
Solar/Wind Harmer
88.563
315813AE1-149 C
Solar/Wind Harmer
12.356
965281AG1-393 GEN
Solar/Wind Harmer
2.464
3144873MCLAUGH
Solar/Wind Harmer
-0.001
970659AG2-427 GEN
Solar/Wind Harmer
1.853
3144536CHRHLND
Solar/Wind Harmer
-0.003
316083AB2-161 GEN
Solar/Wind Harmer
3.192
970661AG2-428 GEN
Solar/Wind Harmer
3.695
3145336SMITFLD
Solar/Wind Harmer
-0.008
3146456SLIGO L269
Solar/Wind Harmer
-0.019
971153AH1-033 GEN
Solar/Wind Harmer
2.381
3151221GRAVEL6
Adder
12.61
3151171GRAVELC
Adder
2.426
961611AG1-000B GEN
Solar/Wind Harmer
4.102
315778AD1-151 GEN
Solar/Wind Harmer
16.861
970129AG2-093 GEN
Solar/Wind Harmer
10.955
970133AG2-095 GEN
Solar/Wind Harmer
2.188
3143096IRON208
Adder
0.724
3143096IRON208
Adder
0.709
316313AB2-026
Solar/Wind Harmer
0.523
316258AE1-075 C
Solar/Wind Harmer
0.471
316405AF2-144 C
Solar/Wind Harmer
0.497
3143336POWHATN
Solar/Wind Harmer
1.956
316320Y1-086
Solar/Wind Harmer
1.134
3144216WINCHST
Adder
0.644
316435W1029_GEN3
Solar/Wind Harmer
3.474
3150921YORKTN3
Adder
4.283
3146516WINFALL
Solar/Wind Harmer
-0.019
970917AG2-570 GEN
Solar/Wind Harmer
47.572
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3142946ENON
Solar/Wind Harmer
-0.006
316303AF2-085
50/50
3.564
971285AH1-108 GEN
50/50
1.442
315244AE2-183_ST
50/50
5.083
963041AG1-153 GEN
50/50
4.689
3151081ELIZAR1
50/50
17.074
3151091ELIZAR2
50/50
16.777
316164AC1-076 GEN
Solar/Wind Harmer
2.466
316233AE1-074 FULL
Solar/Wind Harmer
0.578
971281AH1-106 GEN
Solar/Wind Harmer
3.49
971283AH1-107 GEN
Solar/Wind Harmer
3.49
941031AE2-094 GEN
Solar/Wind Harmer
38.523
944011AF1-069 GEN
Solar/Wind Harmer
12.07
970673AG2-436 GEN
Solar/Wind Harmer
42.401
970673AG2-436 GEN
Solar/Wind Harmer
21.469
3143316POE
Solar/Wind Harmer
-0.079
971967AH1-528 GEN
Solar/Wind Harmer
37.464
3152611GOSPORTB
Adder
2.234
3152621GOSPORTC
Adder
1.896
3152601GOSPORTA
Adder
1.749
316315AB2-025 C
Solar/Wind Harmer
0.53
957871AF2-081 GEN
Solar/Wind Harmer
9.786
315814AE2-033 C
Solar/Wind Harmer
18.225
971445AH1-216 GEN
Solar/Wind Harmer
12.109
319010AE1-072 C
Solar/Wind Harmer
3.949
3146406KITTY HAWK
Solar/Wind Harmer
0.016
315833AF1-017_GEN
Solar/Wind Harmer
3.705
316349AD2-085 GEN
Solar/Wind Harmer
1.735
316311AC2-079 GEN
Solar/Wind Harmer
9.838
316305AF2-043 C
Solar/Wind Harmer
0.588
972265AH1-717 GEN
Adder
13.467
3151201GRAVEL4
Adder
12.624
3151191GRAVEL3
Adder
12.465
3151211GRAVEL5
Adder
12.465
316369SG1_INVT
Solar/Wind Harmer
3.478
316132AB2-190 GEN1
Solar/Wind Harmer
1.968
315835AF2-110_GEN
Solar/Wind Harmer
2.426
313526AB2-022
Solar/Wind Harmer
0.522
3146486SUNBURY
Solar/Wind Harmer
-0.019
3146486SUNBURY
Solar/Wind Harmer
-0.019
316321Z2-027
Solar/Wind Harmer
0.52
3146396TANGLEW
Solar/Wind Harmer
0.355
3145176PASQUOTANK
Solar/Wind Harmer
-0.012
970085AG2-068 GEN
Solar/Wind Harmer
11.842
970581AG2-369 GEN
Solar/Wind Harmer
10.184
315611Z1-036_GEN2
Solar/Wind Harmer
4.663
3130156CHOWAN
Solar/Wind Harmer
-0.019
3130156CHOWAN
Solar/Wind Harmer
-0.019
315976AC1-164 GENA
Solar/Wind Harmer
19.644
316169AC1-164_GENC
Solar/Wind Harmer
16.971
315975AC1-164 GENB
Solar/Wind Harmer
0.581
316312AB1-027
Solar/Wind Harmer
0.626
957831AF2-077 GEN
Solar/Wind Harmer
0.558
3138283WHITEMARSH
Solar/Wind Harmer
0.029
971167AH1-042 GEN
Solar/Wind Harmer
17.842
3142433PROV 92
Adder
0.319
3142433PROV 92
Adder
0.319
315816AE2-034 GEN
Solar/Wind Harmer
1.482
3143873LANEXA
Solar/Wind Harmer
-0.011
3130546PLYMOUTH
Solar/Wind Harmer
-0.018
316314AB2-024 C
Solar/Wind Harmer
1.538
965291AG1-394 GEN
Solar/Wind Harmer
1.596
315732AD1-074 GEN1
Solar/Wind Harmer
3.638
315733AD1-074 GEN2
Solar/Wind Harmer
3.638
315735AD1-075 GEN1
Solar/Wind Harmer
1.819
315662AE1-191 GEN
Solar/Wind Harmer
2.166
315666AE1-190 GEN
Solar/Wind Harmer
0.541
316059AD1-063 C
Solar/Wind Harmer
0.406
957601AF2-054 GEN
Solar/Wind Harmer
0.535
3141873WAN 176
Solar/Wind Harmer
-0.004
316318V4-068
Solar/Wind Harmer
0.444
3145893MURPHYS
Solar/Wind Harmer
-0.048
3145893MURPHYS
Solar/Wind Harmer
-0.018
3146206CASHIE
Solar/Wind Harmer
-0.018
970601AG2-382 GEN
Solar/Wind Harmer
7.803
946281AF1-292 GEN
Solar/Wind Harmer
0.397
972189AH1-679 GEN
Adder
2.63
3141913WHIT STONE
Solar/Wind Harmer
-0.018
3145513AHOSKIE
Solar/Wind Harmer
0.153
961941AG1-037 GEN
Solar/Wind Harmer
0.132
3145513AHOSKIE
Solar/Wind Harmer
-0.018
3146043SEABORD
Solar/Wind Harmer
-0.018
316087AB2-174 GEN
Solar/Wind Harmer
2.505
3138133OCRAN
Solar/Wind Harmer
-0.005
315607AA1-063A GEN
Solar/Wind Harmer
1.771
3145683EARLEYS
Solar/Wind Harmer
-0.035
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.017
3141783LANCAST
Solar/Wind Harmer
-0.01
3141783LANCAST
Solar/Wind Harmer
-0.007
315652AC1-086 GEN
Solar/Wind Harmer
19.526
3137643SOCKMAN
Solar/Wind Harmer
-0.069
3145796HORNRTN
Solar/Wind Harmer
-0.054
3145796HORNRTN
Solar/Wind Harmer
-0.007
962981AG1-147 GEN
Solar/Wind Harmer
7.468
3146033SCOT NK
Solar/Wind Harmer
-0.067
970831AG2-522 GEN
Solar/Wind Harmer
8.337
3150411LDYSMT5
Adder
18.132
3150381LDYSMT2
Adder
17.353
972213AH1-691 GEN
Adder
2.935
972215AH1-692 GEN
Adder
2.935
972205AH1-687 GEN
Adder
5.587
3145273HOLLAND
Solar/Wind Harmer
-0.014
316382AG1-145 C
Solar/Wind Harmer
0.571
970293AG2-193 GEN
Solar/Wind Harmer
2.356
3146376EDENTON
Solar/Wind Harmer
-0.019
3142416OLDCHRC
Solar/Wind Harmer
1.872
3142433PROV 92
Adder
0.319
3142433PROV 92
Adder
0.319
315614AA2-178 GEN
Solar/Wind Harmer
1.976
316365GEN2_N
Solar/Wind Harmer
1.224
3156081AA2-088 GEN
Solar/Wind Harmer
5.86
971157AH1-035 GEN
Solar/Wind Harmer
2.255
3141843SHACKLE
Adder
0.819
316203AE2-005 GEN
Solar/Wind Harmer
7.594
315737AD1-076 GEN
Solar/Wind Harmer
3.419
316280AD1-041 GEN
Solar/Wind Harmer
1.353
3141766HARMONY
Solar/Wind Harmer
1.599
316156AD2-030 GEN
Solar/Wind Harmer
0.478
3141873WAN 176
Solar/Wind Harmer
2.124
316473AC1-191 GEN
Solar/Wind Harmer
1.923
3145893MURPHYS
Solar/Wind Harmer
0.124
3145893MURPHYS
Solar/Wind Harmer
-0.018
3146206CASHIE
Solar/Wind Harmer
-0.018
957521AF2-046 GEN
Solar/Wind Harmer
14.011
961681AG1-008 GEN
Solar/Wind Harmer
14.011
3132273ORANGE
Solar/Wind Harmer
-0.004
966621AG1-532 GEN
Solar/Wind Harmer
0.36
3146173TUNIS
Solar/Wind Harmer
-0.018
3156021HOLLOMANSOL
Solar/Wind Harmer
2.374
316463AE2-346 GEN
Solar/Wind Harmer
0.285
316140AB2-099
Solar/Wind Harmer
0.119
962331AG1-082 GEN
Solar/Wind Harmer
2.199
313506AB2-031 GEN
Solar/Wind Harmer
1.406
316478AD1-087 GEN
Solar/Wind Harmer
1.512
316486AD2-202 GEN
Solar/Wind Harmer
0.443
3146263WOODLND
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3147043LAWRENC
Solar/Wind Harmer
-0.01
316317KELFORD C
Solar/Wind Harmer
0.811
3145823KELFORD
Solar/Wind Harmer
-0.017
3145963POPLR C
Solar/Wind Harmer
-0.017
3145796HORNRTN
Solar/Wind Harmer
-0.068
3145796HORNRTN
Solar/Wind Harmer
-0.017
962971AG1-146 GEN
Solar/Wind Harmer
3.201
316484AD2-074 GEN
Solar/Wind Harmer
4.25
970009AG2-005 GEN
Solar/Wind Harmer
2.11
970909AG2-566 GEN
Solar/Wind Harmer
1.598
3144293JTRSVLE
Adder
0.458
3150351NORNECKC2
Adder
1.447
3151761LOISA E
Adder
18.822
972183AH1-676 GEN
Adder
147.154
3150401LDYSMT4
Adder
18.076
3150371LDYSMT1
Adder
17.466
316210AC1-098 GEN
Solar/Wind Harmer
1.146
3152251N ANNA1
50/50
17.06
971507AH1-251 GEN
50/50
10.552
970119AG2-088 GEN
50/50
26.728
3150851SPRUNCC
50/50
0.881
315243AE2-183_GT3
50/50
2.94
3151051BRUNSWICKS1
50/50
4.806
3151021BRUNSWICKG1
50/50
2.316
971451AH1-221 GEN
50/50
7.034
316045AC1-158 PL2
Solar/Wind Harmer
21.499
3147666LOUISA
Solar/Wind Harmer
-0.104
316192AB2-158 GEN
Solar/Wind Harmer
3.055
3143226MDLTHAN
Solar/Wind Harmer
-0.022
3143526WINTERP
Solar/Wind Harmer
-0.111
940641AE2-051 GEN
Solar/Wind Harmer
19.711
939411AE1-173 GEN
Solar/Wind Harmer
103.452
316294AC1-161 GEN
Solar/Wind Harmer
6.447
944591AF1-124 GEN
Solar/Wind Harmer
90.291
316375AC2-012 GEN
Solar/Wind Harmer
6.82
3150981CHESPKA
Adder
2.19
970659AG2-427 GEN
Solar/Wind Harmer
10.457
316381AD1-082 GEN
Solar/Wind Harmer
1.804
315671AE2-027_GEN
Solar/Wind Harmer
14.75
3142543TWELFTH
Solar/Wind Harmer
-0.002
970661AG2-428 GEN
Solar/Wind Harmer
20.849
316388AE2-253 GEN
Solar/Wind Harmer
1.321
3145336SMITFLD
Solar/Wind Harmer
-0.078
3146456SLIGO L269
Solar/Wind Harmer
-0.019
316246AF1-032 C
Solar/Wind Harmer
0.394
3151171GRAVELC
Adder
1.845
961611AG1-000B GEN
Solar/Wind Harmer
9.613
971647AH1-324 GEN
Solar/Wind Harmer
9.737
316072AD1-144
Solar/Wind Harmer
0.394
971069AG2-661 GEN
Solar/Wind Harmer
3.08
316458AB2-190 GEN2
Solar/Wind Harmer
1.968
970129AG2-093 GEN
Solar/Wind Harmer
4.438
3143096IRON208
Adder
0.724
316093AE2-104_GEN
Solar/Wind Harmer
5.643
3143336POWHATN
Solar/Wind Harmer
2.302
3138126ROCKLANDING
Solar/Wind Harmer
0.059
944631AF1-128 GEN
Adder
81.3
3146516WINFALL
Solar/Wind Harmer
-0.062
3146516WINFALL
Solar/Wind Harmer
-0.019
970919AG2-571 GEN
Solar/Wind Harmer
6.022
316159AE1-175 C
Solar/Wind Harmer
0.509
971317AH1-138 GEN
Solar/Wind Harmer
2.37
970087AG2-069 GEN
Solar/Wind Harmer
17.764
315800Z1-036_GEN1
Solar/Wind Harmer
4.663
3130156CHOWAN
Solar/Wind Harmer
-0.019
316336AC2-165 C
Solar/Wind Harmer
3.228
3142416OLDCHRC
Solar/Wind Harmer
-0.048
3142416OLDCHRC
Solar/Wind Harmer
-0.018
3142433PROV 92
Solar/Wind Harmer
-0.073
3142433PROV 92
Adder
0.319
3142433PROV 92
Adder
0.319
3145663CRESWEL
Solar/Wind Harmer
-0.051
971163AH1-040 GEN
Solar/Wind Harmer
17.169
957481AF2-042 GEN
Solar/Wind Harmer
56.769
316023GEN1_S
Solar/Wind Harmer
1.224
971777AH1-397 GEN
Solar/Wind Harmer
2.118
3141843SHACKLE
Adder
0.819
3141766HARMONY
Solar/Wind Harmer
-0.004
3145893MURPHYS
Solar/Wind Harmer
-0.071
3145893MURPHYS
Solar/Wind Harmer
0.529
3146206CASHIE
Solar/Wind Harmer
-0.018
971547AH1-271 GEN
Solar/Wind Harmer
4.459
315693AD1-088 GEN
Solar/Wind Harmer
8.905
962491AG1-098 GEN
Solar/Wind Harmer
11.877
960081AF2-299 GEN
Solar/Wind Harmer
1.994
3146173TUNIS
Solar/Wind Harmer
-0.018
3138133OCRAN
Solar/Wind Harmer
-0.01
3145683EARLEYS
Solar/Wind Harmer
-0.017
3146263WOODLND
Solar/Wind Harmer
-0.017
971795AH1-408 GEN
Solar/Wind Harmer
13.054
316011AB1-132 GEN
Solar/Wind Harmer
3.631
962571AG1-106 GEN
Solar/Wind Harmer
2.495
316190AA2-174 GEN
Solar/Wind Harmer
0.212
3147043LAWRENC
Adder
1.39
3145823KELFORD
Solar/Wind Harmer
-0.017
3145963POPLR C
Solar/Wind Harmer
-0.017
3145783HORNRTN
Solar/Wind Harmer
-0.017
3145796HORNRTN
Solar/Wind Harmer
-0.056
3145796HORNRTN
Solar/Wind Harmer
-0.017
316174AB2-169 GEN
Solar/Wind Harmer
2.633
961951AG1-038 GEN
Solar/Wind Harmer
2.224
962861AG1-135 GEN
Solar/Wind Harmer
6.247
3144293JTRSVLE
Adder
0.458
3150351NORNECKC2
Adder
1.423
3151751LOISA D
Adder
9.232
972197AH1-683 GEN
Adder
2.823
972219AH1-694 GEN
Adder
2.032
316212AC1-099_GEN
Solar/Wind Harmer
0.637
LAGNLTFEXP_LAGN->PJM
CLTF
5.934
CBM South 2LTFEXP_CBM-S2->PJM
CBM
19.477
TVALTFEXP_TVA->PJM
CLTF
3.006
CPLELTFEXP_CPLE->PJM
CLTF
8.984
CBM West 2LTFEXP_CBM-W2->PJM
CBM
29.843
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.608
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.131
MECLTFEXP_MEC->PJM
CLTF
2.485
SIGELTFEXP_SIGE->PJM
CLTF
0.075
NYPJM->LTFIMP_NY
CLTF
2.556
LGEELTFEXP_LGEE->PJM
CLTF
0.891
WECLTFEXP_WEC->PJM
CLTF
0.421

Details for AE2-094 TP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 511_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:136.1 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5539.41
MW Contribution:25.61
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
11.133
3151051BRUNSWICKS1
50/50
17.499
3151021BRUNSWICKG1
50/50
8.432
971451AH1-221 GEN
50/50
25.609
3151531CLOVER1
50/50
9.362
3151601KERR 3
50/50
0.537
3151581KERR 1
50/50
0.192
3144293JTRSVLE
50/50
0.801
971629AH1-314 GEN
50/50
17.923
3151561HALLBR1
50/50
0.367
970919AG2-571 GEN
Solar/Wind Harmer
21.368
970087AG2-069 GEN
Solar/Wind Harmer
47.73
957481AF2-042 GEN
Solar/Wind Harmer
126.807
315693AD1-088 GEN
Solar/Wind Harmer
20.818
962491AG1-098 GEN
Solar/Wind Harmer
24.385
315687AD1-152 GEN
Solar/Wind Harmer
0.013
316003AC1-222 GEN
Solar/Wind Harmer
0.008
970401AG2-262 GEN
Solar/Wind Harmer
1.677
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970685AG2-442 GEN
Solar/Wind Harmer
17.979
963171AG1-166 GEN
Solar/Wind Harmer
1.264
971563AH1-280 GEN
Solar/Wind Harmer
2.529
3146926FARMVIL
Solar/Wind Harmer
0.131
971065AG2-659 GEN
Solar/Wind Harmer
8.445
316129AC1-054 GEN
Solar/Wind Harmer
0.698
970223AG2-152 GEN
Solar/Wind Harmer
12.094
270016AE1-250 BESS
Solar/Wind Harmer
0.005
3147123OTTER R
Solar/Wind Harmer
0.088
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.055
3147312GRETNA
Solar/Wind Harmer
0.105
3146802CHATHAM
Solar/Wind Harmer
0.099
941801AE2-185 GEN
Solar/Wind Harmer
4.212
270030AE2-140 GEN
Solar/Wind Harmer
13.804
3145543BTLEBRO
Solar/Wind Harmer
0.117
3145543BTLEBRO
Solar/Wind Harmer
0.094
316359AB2-059 GEN
Solar/Wind Harmer
0.421
316049AB1-081 GEN
Solar/Wind Harmer
0.67
3142053HEARTS
Solar/Wind Harmer
0.206
316294AC1-161 GEN
Solar/Wind Helper
7.693
316375AC2-012 GEN
Solar/Wind Helper
1.008
3145336SMITFLD
Solar/Wind Helper
1.487
316388AE2-253 GEN
Solar/Wind Helper
1.389
3146456SLIGO L269
Solar/Wind Helper
0.357
316381AD1-082 GEN
Solar/Wind Helper
1.848
316072AD1-144
Solar/Wind Helper
0.404
316246AF1-032 C
Solar/Wind Helper
0.401
316159AE1-175 C
Solar/Wind Helper
0.531
316458AB2-190 GEN2
Solar/Wind Helper
1.993
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.303
3138133OCRAN
Solar/Wind Helper
0.195
3142543TWELFTH
Solar/Wind Helper
0.03
964211AG1-282 GEN
Solar/Wind Helper
0.416
3141726DUNNSVL
Solar/Wind Helper
1.235
316337AD2-073 GEN
Solar/Wind Helper
0.453
3142416OLDCHRC
Solar/Wind Helper
0.774
3142416OLDCHRC
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.959
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
3143226MDLTHAN
Solar/Wind Helper
0.286
315800Z1-036_GEN1
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
315244AE2-183_ST
50/50
19.249
963041AG1-153 GEN
50/50
17.073
3151541CLOVER2
50/50
9.317
3151611KERR 4
50/50
0.537
3151621KERR 5
50/50
0.537
3151631KERR 6
50/50
0.537
3151641KERR 7
50/50
0.537
941031AE2-094 GEN
Solar/Wind Harmer
138.271
944011AF1-069 GEN
Solar/Wind Harmer
45.178
970673AG2-436 GEN
Solar/Wind Harmer
149.315
970673AG2-436 GEN
Solar/Wind Harmer
99.544
971967AH1-528 GEN
Solar/Wind Harmer
95.481
970085AG2-068 GEN
Solar/Wind Harmer
31.82
970581AG2-369 GEN
Solar/Wind Harmer
27.365
3147173SINAI
Solar/Wind Harmer
0.309
3147243WELCO
Solar/Wind Harmer
0.193
316118AC1-105 GEN
Solar/Wind Harmer
0.768
970865AG2-541 GEN
Solar/Wind Harmer
9.078
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
4.118
3144303KENBRDG
Solar/Wind Harmer
0.196
970683AG2-441 GEN
Solar/Wind Harmer
16.053
970681AG2-440 GEN
Solar/Wind Harmer
12.842
946301AF1-294 GEN
Solar/Wind Harmer
4.678
961791AG1-021 GEN
Solar/Wind Harmer
2.276
315657AE1-056 GEN
Solar/Wind Harmer
8.085
316123AC1-075 GEN
Solar/Wind Harmer
0.315
970165AG2-112 GEN
Solar/Wind Harmer
1.87
970163AG2-111 GEN
Solar/Wind Harmer
1.784
970831AG2-522 GEN
Solar/Wind Harmer
7.35
970285AG2-188 GEN
Solar/Wind Harmer
12.402
971845AH1-439 GEN
Solar/Wind Harmer
6.507
270069AE2-166 C O1
Solar/Wind Harmer
0.004
3143316POE
Solar/Wind Helper
1.55
319010AE1-072 C
Solar/Wind Helper
4.057
316369SG1_INVT
Solar/Wind Helper
1.702
316305AF2-043 C
Solar/Wind Helper
0.471
316132AB2-190 GEN1
Solar/Wind Helper
1.993
957831AF2-077 GEN
Solar/Wind Helper
0.468
316349AD2-085 GEN
Solar/Wind Helper
1.559
313526AB2-022
Solar/Wind Helper
0.503
957601AF2-054 GEN
Solar/Wind Helper
0.442
3141873WAN 176
Solar/Wind Helper
0.066
315662AE1-191 GEN
Solar/Wind Helper
1.766
315666AE1-190 GEN
Solar/Wind Helper
0.441
316059AD1-063 C
Solar/Wind Helper
0.329
3141913WHIT STONE
Solar/Wind Helper
0.326
3138133OCRAN
Solar/Wind Helper
0.098
3143873LANEXA
Solar/Wind Helper
0.195
3141783LANCAST
Solar/Wind Helper
0.194
3141783LANCAST
Solar/Wind Helper
0.129
3146486SUNBURY
Solar/Wind Helper
0.322
3146486SUNBURY
Solar/Wind Helper
0.322
316321Z2-027
Solar/Wind Helper
0.485
3145176PASQUOTANK
Solar/Wind Helper
0.197
316315AB2-025 C
Solar/Wind Helper
0.48
3141813NORNECK
Solar/Wind Helper
0.308
316312AB1-027
Solar/Wind Helper
0.567
316233AE1-074 FULL
Solar/Wind Helper
0.447
316223AC1-118
Solar/Wind Helper
0.442
315611Z1-036_GEN2
Solar/Wind Helper
1.413
3151031BRUNSWICKG2
50/50
8.432
970413AG2-270 GEN
50/50
40.853
3151591KERR 2
50/50
0.537
3144293JTRSVLE
50/50
0.801
970917AG2-570 GEN
Solar/Wind Harmer
53.421
316478AD1-087 GEN
Solar/Wind Harmer
1.525
316486AD2-202 GEN
Solar/Wind Harmer
0.448
970909AG2-566 GEN
Solar/Wind Harmer
3.307
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
13.182
316283AC2-100 C
Solar/Wind Harmer
0.55
971683AH1-343 GEN
Solar/Wind Harmer
10.2
316131AB2-060 GEN
Solar/Wind Harmer
0.796
964241AG1-285 GEN
Solar/Wind Harmer
16.703
315785AD2-033 C
Solar/Wind Harmer
2.003
970257AG2-171 GEN
Solar/Wind Harmer
7.834
959311AF2-222 GEN
Solar/Wind Harmer
21.656
963181AG1-167 GEN
Solar/Wind Harmer
0.948
3147133PAMPLIN
Solar/Wind Harmer
0.736
971193AH1-056 GEN
Solar/Wind Harmer
14.274
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.131
270018AE2-047 C O1
Solar/Wind Harmer
0.003
270197AD1-017 GEN1
Solar/Wind Harmer
0.943
3146776BUCKING
Solar/Wind Harmer
0.049
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
970533AG2-339 GEN
50/50
66.733
970531AG2-338 GEN
50/50
26.693
315242AE2-183_GT2
50/50
11.133
315241AE2-183_GT1
50/50
11.065
972185AH1-677 GEN
50/50
40.137
3151041BRUNSWICKG3
50/50
8.432
972187AH1-678 GEN
50/50
19.349
3152661PLYWOOD A
50/50
0.671
970535AG2-341 GEN
50/50
4.566
3144293JTRSVLE
50/50
0.801
3144293JTRSVLE
50/50
0.674
970933AG2-581 GEN
Solar/Wind Harmer
44.982
970099AG2-077 GEN
Solar/Wind Harmer
50.723
971741AH1-377 GEN
Solar/Wind Harmer
33.569
970301AG2-198 GEN
Solar/Wind Harmer
13.228
3146843MT LREL
Solar/Wind Harmer
0.286
3146843MT LREL
Solar/Wind Harmer
0.286
964791AG1-342 GEN
Solar/Wind Harmer
5.488
316222AC1-221 GEN
Solar/Wind Harmer
1.175
962561AG1-105 GEN
Solar/Wind Harmer
13.485
939181AE1-148 GEN
Solar/Wind Harmer
12.41
313527AB2-043 GEN
Solar/Wind Harmer
0.003
970323AG2-213 GEN
Solar/Wind Harmer
10.445
971775AH1-396 GEN
Solar/Wind Harmer
0.392
316034AC1-036 C
Solar/Wind Harmer
0.018
958211AF2-115 GEN
Solar/Wind Harmer
2.845
963191AG1-168 GEN
Solar/Wind Harmer
0.948
3147133PAMPLIN
Solar/Wind Harmer
0.234
3147133PAMPLIN
Solar/Wind Harmer
0.187
942751AE2-291 GEN
Solar/Wind Harmer
11.476
270013AE1-250 PV
Solar/Wind Harmer
0.005
3146776BUCKING
Solar/Wind Harmer
0.546
3146776BUCKING
Solar/Wind Harmer
0.044
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
3.276
316263AC1-034 GEN
Solar/Wind Harmer
4.449
961601AG1-000A GEN
Solar/Wind Harmer
2.035
316036AC1-147 C
Solar/Wind Helper
0.586
3142956BIRDNECK
Solar/Wind Helper
0.257
316316AC1-027 C
Solar/Wind Helper
0.602
316185AD1-033 GEN
Solar/Wind Helper
1.787
3145506HICKORY
Solar/Wind Helper
1.497
3145506HICKORY
Solar/Wind Helper
0.899
3145506HICKORY
Solar/Wind Helper
0.225
316236AE1-162_GEN
Solar/Wind Helper
0.5
316339AD2-160 GEN
Solar/Wind Helper
1.389
316018AA1-139 ULT2
Solar/Wind Helper
1.557
316017AA1-139 ULT1
Solar/Wind Helper
1.655
3137176SLIGO L2192
Solar/Wind Helper
1.424
316033AB2-134 GEN
Solar/Wind Helper
1.217
315697AD1-025 GEN
Solar/Wind Helper
4.045
3130086AYDLETT
Solar/Wind Helper
1.414
316240AF1-291 C
Solar/Wind Helper
0.474
3146386ELIZ CT
Solar/Wind Helper
0.33
3142946ENON
Solar/Wind Helper
0.032
316487AF1-042 GEN
Solar/Wind Helper
0.321
3144356SAPONY
Solar/Wind Helper
0.565
316075AC2-137 C
Solar/Wind Helper
0.475
316077AC2-138 C
Solar/Wind Helper
0.289
316431W1029_GEN1
Solar/Wind Helper
1.222
316433W1029_GEN2
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
966871AG1-558 GEN
Solar/Wind Helper
0.383
3146626S HERTFORD
Solar/Wind Helper
0.28
3146626S HERTFORD
Solar/Wind Helper
0.28
316468AD1-105 GEN
Solar/Wind Helper
1.331
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3147312GRETNA
Solar/Wind Harmer
0.026
941821AE2-187 GEN
Solar/Wind Harmer
4.212
270336AE1-100 GEN
Solar/Wind Harmer
0.003
3145543BTLEBRO
Solar/Wind Harmer
0.117
3145543BTLEBRO
Solar/Wind Harmer
0.117
971623AH1-311 GEN
Solar/Wind Harmer
0.234
961601AG1-000A GEN
Solar/Wind Harmer
8.141
315773AC2-141 GEN
Solar/Wind Helper
9.054
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.057
3145336SMITFLD
Solar/Wind Helper
0.149
315839AE2-212 C
Solar/Wind Helper
0.495
3146456SLIGO L269
Solar/Wind Helper
0.357
316382AG1-145 C
Solar/Wind Helper
0.471
316320Y1-086
Solar/Wind Helper
0.147
316156AD2-030 GEN
Solar/Wind Helper
0.497
316280AD1-041 GEN
Solar/Wind Helper
1.104
3142946ENON
Solar/Wind Helper
0.108
316484AD2-074 GEN
Solar/Wind Helper
0.613
316404AE1-155 C
Solar/Wind Helper
2.651
316435W1029_GEN3
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3141906WESTMOR
Solar/Wind Helper
0.116
316473AC1-191 GEN
Solar/Wind Helper
1.736
3146626S HERTFORD
Solar/Wind Helper
0.28
3145273HOLLAND
Solar/Wind Helper
0.191
966881AG1-559 GEN
Solar/Wind Helper
0.333
3146376EDENTON
Solar/Wind Helper
0.227
LAGNLTFEXP_LAGN->PJM
CLTF
14.669
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.275
TVALTFEXP_TVA->PJM
CLTF
7.315
CPLELTFEXP_CPLE->PJM
CLTF
19.748
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.24
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.721
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.156
MECLTFEXP_MEC->PJM
CLTF
7.366
SIGELTFEXP_SIGE->PJM
CLTF
0.221
NYPJM->LTFIMP_NY
CLTF
2.382
LGEELTFEXP_LGEE->PJM
CLTF
2.675
WECLTFEXP_WEC->PJM
CLTF
1.4
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113

Details for AE2-094 TP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-2: 51192_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 51192_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.36 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:6013.11
MW Contribution:25.61
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
8.432
970413AG2-270 GEN
50/50
40.853
3151591KERR 2
50/50
0.537
3144293JTRSVLE
50/50
0.801
970917AG2-570 GEN
Solar/Wind Harmer
168.81
316478AD1-087 GEN
Solar/Wind Harmer
4.25
316486AD2-202 GEN
Solar/Wind Harmer
1.245
970909AG2-566 GEN
Solar/Wind Harmer
3.307
315244AE2-183_ST
50/50
19.249
963041AG1-153 GEN
50/50
17.073
3151541CLOVER2
50/50
9.317
3151611KERR 4
50/50
0.537
3151621KERR 5
50/50
0.537
3151631KERR 6
50/50
0.537
3151641KERR 7
50/50
0.537
941031AE2-094 GEN
Solar/Wind Harmer
158.157
944011AF1-069 GEN
Solar/Wind Harmer
49.556
970673AG2-436 GEN
Solar/Wind Harmer
165.209
970673AG2-436 GEN
Solar/Wind Harmer
83.65
971967AH1-528 GEN
Solar/Wind Harmer
126.052
970085AG2-068 GEN
Solar/Wind Harmer
41.896
970581AG2-369 GEN
Solar/Wind Harmer
36.031
3147173SINAI
Solar/Wind Harmer
-0.035
3147243WELCO
Solar/Wind Harmer
-0.021
316118AC1-105 GEN
Solar/Wind Harmer
2.3
970865AG2-541 GEN
Solar/Wind Harmer
11.953
316239AB2-077_GEN
Solar/Wind Harmer
0.866
316238AB2-078_GEN
Solar/Wind Harmer
0.866
971443AH1-215 GEN
Solar/Wind Harmer
5.422
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
21.136
970681AG2-440 GEN
Solar/Wind Harmer
16.909
946301AF1-294 GEN
Solar/Wind Harmer
6.825
961791AG1-021 GEN
Solar/Wind Harmer
3.329
270455AD2-022 GEN
Solar/Wind Harmer
4.714
270457AD2-023 GEN
Solar/Wind Harmer
2.39
315657AE1-056 GEN
Solar/Wind Harmer
9.877
316123AC1-075 GEN
Solar/Wind Harmer
2.797
970165AG2-112 GEN
Solar/Wind Harmer
2.462
970163AG2-111 GEN
Solar/Wind Harmer
2.349
970831AG2-522 GEN
Solar/Wind Harmer
9.678
970285AG2-188 GEN
Solar/Wind Harmer
15.412
971845AH1-439 GEN
Solar/Wind Harmer
8.567
270069AE2-166 C O1
Solar/Wind Harmer
2.422
3143316POE
Solar/Wind Helper
1.55
319010AE1-072 C
Solar/Wind Helper
4.057
316369SG1_INVT
Solar/Wind Helper
1.702
316305AF2-043 C
Solar/Wind Helper
0.471
316132AB2-190 GEN1
Solar/Wind Helper
1.993
957831AF2-077 GEN
Solar/Wind Helper
0.468
316349AD2-085 GEN
Solar/Wind Helper
1.559
313526AB2-022
Solar/Wind Helper
0.503
957601AF2-054 GEN
Solar/Wind Helper
0.442
3141873WAN 176
Solar/Wind Helper
0.066
315662AE1-191 GEN
Solar/Wind Helper
1.766
315666AE1-190 GEN
Solar/Wind Helper
0.441
316059AD1-063 C
Solar/Wind Helper
0.329
3141913WHIT STONE
Solar/Wind Helper
0.326
3138133OCRAN
Solar/Wind Helper
0.098
3143873LANEXA
Solar/Wind Helper
0.195
3141783LANCAST
Solar/Wind Helper
0.194
3141783LANCAST
Solar/Wind Helper
0.129
315243AE2-183_GT3
50/50
11.133
3151051BRUNSWICKS1
50/50
17.499
3151021BRUNSWICKG1
50/50
8.432
971451AH1-221 GEN
50/50
25.609
3151531CLOVER1
50/50
9.362
3151601KERR 3
50/50
0.537
3151581KERR 1
50/50
0.192
3144293JTRSVLE
50/50
0.801
971629AH1-314 GEN
50/50
17.923
3151561HALLBR1
50/50
0.367
970919AG2-571 GEN
Solar/Wind Harmer
21.368
970087AG2-069 GEN
Solar/Wind Harmer
62.844
957481AF2-042 GEN
Solar/Wind Harmer
166.962
315693AD1-088 GEN
Solar/Wind Harmer
24.364
962491AG1-098 GEN
Solar/Wind Harmer
32.107
315687AD1-152 GEN
Solar/Wind Harmer
5.339
316003AC1-222 GEN
Solar/Wind Harmer
3.203
970401AG2-262 GEN
Solar/Wind Harmer
2.096
316237AB2-079_GEN
Solar/Wind Harmer
0.866
970685AG2-442 GEN
Solar/Wind Harmer
23.673
963171AG1-166 GEN
Solar/Wind Harmer
3.329
971563AH1-280 GEN
Solar/Wind Harmer
3.329
3146926FARMVIL
Solar/Wind Harmer
-0.015
971065AG2-659 GEN
Solar/Wind Harmer
11.119
316129AC1-054 GEN
Solar/Wind Harmer
1.828
970223AG2-152 GEN
Solar/Wind Harmer
17.247
270016AE1-250 BESS
Solar/Wind Harmer
2.846
3147123OTTER R
Solar/Wind Harmer
-0.01
270574AD1-017 GEN2
Solar/Wind Harmer
5.591
316322AB2-045
Solar/Wind Harmer
0.516
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.545
270030AE2-140 GEN
Solar/Wind Harmer
19.786
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.774
316049AB1-081 GEN
Solar/Wind Harmer
1.419
3142053HEARTS
Solar/Wind Harmer
0.155
316294AC1-161 GEN
Solar/Wind Helper
7.693
316375AC2-012 GEN
Solar/Wind Helper
1.008
3145336SMITFLD
Solar/Wind Helper
1.487
316388AE2-253 GEN
Solar/Wind Helper
1.389
3146456SLIGO L269
Solar/Wind Helper
0.357
316381AD1-082 GEN
Solar/Wind Helper
1.848
316072AD1-144
Solar/Wind Helper
0.404
316246AF1-032 C
Solar/Wind Helper
0.401
316159AE1-175 C
Solar/Wind Helper
0.531
316458AB2-190 GEN2
Solar/Wind Helper
1.993
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.303
3138133OCRAN
Solar/Wind Helper
0.195
3142543TWELFTH
Solar/Wind Helper
0.03
964211AG1-282 GEN
Solar/Wind Helper
0.416
3141726DUNNSVL
Solar/Wind Helper
1.235
316248AF1-058 C
Solar/Wind Harmer
1.046
960061AF2-297 GEN
Solar/Wind Harmer
17.357
316283AC2-100 C
Solar/Wind Harmer
2.974
971683AH1-343 GEN
Solar/Wind Harmer
13.43
316131AB2-060 GEN
Solar/Wind Harmer
3.068
964241AG1-285 GEN
Solar/Wind Harmer
21.992
315785AD2-033 C
Solar/Wind Harmer
6.274
970257AG2-171 GEN
Solar/Wind Harmer
10.314
959311AF2-222 GEN
Solar/Wind Harmer
28.571
963181AG1-167 GEN
Solar/Wind Harmer
2.497
3147133PAMPLIN
Solar/Wind Harmer
-0.082
971193AH1-056 GEN
Solar/Wind Harmer
16.462
942461AE2-259 GEN
Solar/Wind Harmer
3.832
3146926FARMVIL
Solar/Wind Harmer
-0.015
270018AE2-047 C O1
Solar/Wind Harmer
1.378
270197AD1-017 GEN1
Solar/Wind Harmer
1.68
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.844
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.545
270336AE1-100 GEN
Solar/Wind Harmer
1.569
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
961601AG1-000A GEN
Solar/Wind Harmer
5.12
315773AC2-141 GEN
Solar/Wind Helper
9.054
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.057
3145336SMITFLD
Solar/Wind Helper
0.149
315839AE2-212 C
Solar/Wind Helper
0.495
3146456SLIGO L269
Solar/Wind Helper
0.357
316382AG1-145 C
Solar/Wind Helper
0.471
316320Y1-086
Solar/Wind Helper
0.147
316156AD2-030 GEN
Solar/Wind Helper
0.497
316280AD1-041 GEN
Solar/Wind Helper
1.104
3142946ENON
Solar/Wind Helper
0.108
316484AD2-074 GEN
Solar/Wind Helper
0.613
316404AE1-155 C
Solar/Wind Helper
2.651
316435W1029_GEN3
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3141906WESTMOR
Solar/Wind Helper
0.116
316473AC1-191 GEN
Solar/Wind Helper
1.736
3146626S HERTFORD
Solar/Wind Helper
0.28
3145273HOLLAND
Solar/Wind Helper
0.191
966881AG1-559 GEN
Solar/Wind Helper
0.333
3146376EDENTON
Solar/Wind Helper
0.227
316337AD2-073 GEN
Solar/Wind Helper
0.453
3142416OLDCHRC
Solar/Wind Helper
0.774
3142416OLDCHRC
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.959
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
3143226MDLTHAN
Solar/Wind Helper
0.286
315800Z1-036_GEN1
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
3146486SUNBURY
Solar/Wind Helper
0.322
3146486SUNBURY
Solar/Wind Helper
0.322
316321Z2-027
Solar/Wind Helper
0.485
3145176PASQUOTANK
Solar/Wind Helper
0.197
316315AB2-025 C
Solar/Wind Helper
0.48
3141813NORNECK
Solar/Wind Helper
0.308
316312AB1-027
Solar/Wind Helper
0.567
316233AE1-074 FULL
Solar/Wind Helper
0.447
316223AC1-118
Solar/Wind Helper
0.442
315611Z1-036_GEN2
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
970533AG2-339 GEN
50/50
66.733
970531AG2-338 GEN
50/50
26.693
315242AE2-183_GT2
50/50
11.133
315241AE2-183_GT1
50/50
11.065
972185AH1-677 GEN
50/50
40.137
3151041BRUNSWICKG3
50/50
8.432
972187AH1-678 GEN
50/50
19.349
3152661PLYWOOD A
50/50
0.671
970535AG2-341 GEN
50/50
4.566
3144293JTRSVLE
50/50
0.801
3144293JTRSVLE
50/50
0.674
970933AG2-581 GEN
Solar/Wind Harmer
59.226
970099AG2-077 GEN
Solar/Wind Harmer
66.785
971741AH1-377 GEN
Solar/Wind Harmer
44.199
970301AG2-198 GEN
Solar/Wind Harmer
17.416
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.86
316222AC1-221 GEN
Solar/Wind Harmer
3.218
962561AG1-105 GEN
Solar/Wind Harmer
17.755
939181AE1-148 GEN
Solar/Wind Harmer
16.34
313527AB2-043 GEN
Solar/Wind Harmer
4.631
970323AG2-213 GEN
Solar/Wind Harmer
13.752
971775AH1-396 GEN
Solar/Wind Harmer
1.958
316034AC1-036 C
Solar/Wind Harmer
0.51
958211AF2-115 GEN
Solar/Wind Harmer
4.162
963191AG1-168 GEN
Solar/Wind Harmer
2.497
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
15.11
270013AE1-250 PV
Solar/Wind Harmer
2.846
3146776BUCKING
Solar/Wind Harmer
-0.061
3146776BUCKING
Solar/Wind Harmer
-0.005
316217AC1-145 GEN
Solar/Wind Harmer
2.4
316197AC1-042 GEN
Solar/Wind Harmer
1.819
942671AE2-283 GEN
Solar/Wind Harmer
4.898
316263AC1-034 GEN
Solar/Wind Harmer
6.166
961601AG1-000A GEN
Solar/Wind Harmer
5.056
316036AC1-147 C
Solar/Wind Helper
0.586
3142956BIRDNECK
Solar/Wind Helper
0.257
316316AC1-027 C
Solar/Wind Helper
0.602
316185AD1-033 GEN
Solar/Wind Helper
1.787
3145506HICKORY
Solar/Wind Helper
1.497
3145506HICKORY
Solar/Wind Helper
0.899
3145506HICKORY
Solar/Wind Helper
0.225
316236AE1-162_GEN
Solar/Wind Helper
0.5
316339AD2-160 GEN
Solar/Wind Helper
1.389
316018AA1-139 ULT2
Solar/Wind Helper
1.557
316017AA1-139 ULT1
Solar/Wind Helper
1.655
3137176SLIGO L2192
Solar/Wind Helper
1.424
316033AB2-134 GEN
Solar/Wind Helper
1.217
315697AD1-025 GEN
Solar/Wind Helper
4.045
3130086AYDLETT
Solar/Wind Helper
1.414
316240AF1-291 C
Solar/Wind Helper
0.474
3146386ELIZ CT
Solar/Wind Helper
0.33
3142946ENON
Solar/Wind Helper
0.032
316487AF1-042 GEN
Solar/Wind Helper
0.321
3144356SAPONY
Solar/Wind Helper
0.565
316075AC2-137 C
Solar/Wind Helper
0.475
316077AC2-138 C
Solar/Wind Helper
0.289
316431W1029_GEN1
Solar/Wind Helper
1.222
316433W1029_GEN2
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
966871AG1-558 GEN
Solar/Wind Helper
0.383
3146626S HERTFORD
Solar/Wind Helper
0.28
3146626S HERTFORD
Solar/Wind Helper
0.28
316468AD1-105 GEN
Solar/Wind Helper
1.331
LAGNLTFEXP_LAGN->PJM
CLTF
14.669
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.275
TVALTFEXP_TVA->PJM
CLTF
7.315
CPLELTFEXP_CPLE->PJM
CLTF
19.748
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.24
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.721
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.156
MECLTFEXP_MEC->PJM
CLTF
7.366
SIGELTFEXP_SIGE->PJM
CLTF
0.221
NYPJM->LTFIMP_NY
CLTF
2.382
LGEELTFEXP_LGEE->PJM
CLTF
2.675
WECLTFEXP_WEC->PJM
CLTF
1.4
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113

Details for AE2-094 TP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-2: 51172_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 51172_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.82 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5986.29
MW Contribution:25.43
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
8.374
970413AG2-270 GEN
50/50
40.637
3151591KERR 2
50/50
0.538
3144293JTRSVLE
50/50
0.8
970917AG2-570 GEN
Solar/Wind Harmer
167.695
316478AD1-087 GEN
Solar/Wind Harmer
4.227
316486AD2-202 GEN
Solar/Wind Harmer
1.238
970909AG2-566 GEN
Solar/Wind Harmer
3.291
316248AF1-058 C
Solar/Wind Harmer
1.043
960061AF2-297 GEN
Solar/Wind Harmer
17.305
316283AC2-100 C
Solar/Wind Harmer
2.965
971683AH1-343 GEN
Solar/Wind Harmer
13.39
316131AB2-060 GEN
Solar/Wind Harmer
3.076
964241AG1-285 GEN
Solar/Wind Harmer
22.038
315785AD2-033 C
Solar/Wind Harmer
6.282
970257AG2-171 GEN
Solar/Wind Harmer
10.326
959311AF2-222 GEN
Solar/Wind Harmer
28.597
963181AG1-167 GEN
Solar/Wind Harmer
2.496
3147133PAMPLIN
Solar/Wind Harmer
-0.082
971193AH1-056 GEN
Solar/Wind Harmer
16.449
942461AE2-259 GEN
Solar/Wind Harmer
3.824
3146926FARMVIL
Solar/Wind Harmer
-0.015
270018AE2-047 C O1
Solar/Wind Harmer
1.375
270197AD1-017 GEN1
Solar/Wind Harmer
1.676
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.834
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.53
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
270336AE1-100 GEN
Solar/Wind Harmer
1.564
961601AG1-000A GEN
Solar/Wind Harmer
5.252
315773AC2-141 GEN
Solar/Wind Helper
9.163
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.058
3145336SMITFLD
Solar/Wind Helper
0.148
3146456SLIGO L269
Solar/Wind Helper
0.359
316382AG1-145 C
Solar/Wind Helper
0.469
315839AE2-212 C
Solar/Wind Helper
0.457
316320Y1-086
Solar/Wind Helper
0.148
316156AD2-030 GEN
Solar/Wind Helper
0.492
316280AD1-041 GEN
Solar/Wind Helper
1.092
3142946ENON
Solar/Wind Helper
0.105
316484AD2-074 GEN
Solar/Wind Helper
0.607
316404AE1-155 C
Solar/Wind Helper
2.624
316435W1029_GEN3
Solar/Wind Helper
1.225
3146516WINFALL
Solar/Wind Helper
0.297
3141906WESTMOR
Solar/Wind Helper
0.115
3146626S HERTFORD
Solar/Wind Helper
0.28
316473AC1-191 GEN
Solar/Wind Helper
1.696
3145273HOLLAND
Solar/Wind Helper
0.188
966881AG1-559 GEN
Solar/Wind Helper
0.329
3146376EDENTON
Solar/Wind Helper
0.226
315243AE2-183_GT3
50/50
11.056
3151051BRUNSWICKS1
50/50
17.38
3151021BRUNSWICKG1
50/50
8.374
971451AH1-221 GEN
50/50
25.435
3151531CLOVER1
50/50
9.312
3151601KERR 3
50/50
0.538
3151581KERR 1
50/50
0.192
3144293JTRSVLE
50/50
0.8
971629AH1-314 GEN
50/50
17.875
3151561HALLBR1
50/50
0.366
970919AG2-571 GEN
Solar/Wind Harmer
21.227
970087AG2-069 GEN
Solar/Wind Harmer
62.431
957481AF2-042 GEN
Solar/Wind Harmer
166.01
315693AD1-088 GEN
Solar/Wind Harmer
24.233
962491AG1-098 GEN
Solar/Wind Harmer
31.935
315687AD1-152 GEN
Solar/Wind Harmer
5.313
316003AC1-222 GEN
Solar/Wind Harmer
3.193
970401AG2-262 GEN
Solar/Wind Harmer
2.094
316237AB2-079_GEN
Solar/Wind Harmer
0.868
970685AG2-442 GEN
Solar/Wind Harmer
23.682
963171AG1-166 GEN
Solar/Wind Harmer
3.328
971563AH1-280 GEN
Solar/Wind Harmer
3.328
3146926FARMVIL
Solar/Wind Harmer
-0.015
971065AG2-659 GEN
Solar/Wind Harmer
11.224
316129AC1-054 GEN
Solar/Wind Harmer
1.849
970223AG2-152 GEN
Solar/Wind Harmer
17.201
270016AE1-250 BESS
Solar/Wind Harmer
2.839
3147123OTTER R
Solar/Wind Harmer
-0.01
270574AD1-017 GEN2
Solar/Wind Harmer
5.577
316322AB2-045
Solar/Wind Harmer
0.514
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.53
270030AE2-140 GEN
Solar/Wind Harmer
19.734
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.817
316049AB1-081 GEN
Solar/Wind Harmer
1.454
3142053HEARTS
Solar/Wind Harmer
0.158
316294AC1-161 GEN
Solar/Wind Helper
7.785
316375AC2-012 GEN
Solar/Wind Helper
1.014
3145336SMITFLD
Solar/Wind Helper
1.482
316388AE2-253 GEN
Solar/Wind Helper
1.397
3146456SLIGO L269
Solar/Wind Helper
0.359
316072AD1-144
Solar/Wind Helper
0.404
316246AF1-032 C
Solar/Wind Helper
0.402
316159AE1-175 C
Solar/Wind Helper
0.529
316381AD1-082 GEN
Solar/Wind Helper
1.758
316458AB2-190 GEN2
Solar/Wind Helper
1.933
3141766HARMONY
Solar/Wind Helper
0.065
3138133OCRAN
Solar/Wind Helper
0.193
3142433PROV 92
Solar/Wind Helper
1.275
3142543TWELFTH
Solar/Wind Helper
0.029
964211AG1-282 GEN
Solar/Wind Helper
0.412
3141726DUNNSVL
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.961
3146516WINFALL
Solar/Wind Helper
0.297
316337AD2-073 GEN
Solar/Wind Helper
0.448
3142416OLDCHRC
Solar/Wind Helper
0.759
3142416OLDCHRC
Solar/Wind Helper
0.291
3143526WINTERP
Solar/Wind Helper
1.499
3143226MDLTHAN
Solar/Wind Helper
0.284
315800Z1-036_GEN1
Solar/Wind Helper
1.411
3130156CHOWAN
Solar/Wind Helper
0.226
315244AE2-183_ST
50/50
19.115
963041AG1-153 GEN
50/50
16.957
3151541CLOVER2
50/50
9.268
3151611KERR 4
50/50
0.538
3151621KERR 5
50/50
0.538
3151631KERR 6
50/50
0.538
3151641KERR 7
50/50
0.538
941031AE2-094 GEN
Solar/Wind Harmer
157.012
944011AF1-069 GEN
Solar/Wind Harmer
49.197
970673AG2-436 GEN
Solar/Wind Harmer
164.043
970533AG2-339 GEN
50/50
66.25
970531AG2-338 GEN
50/50
26.5
315242AE2-183_GT2
50/50
11.056
315241AE2-183_GT1
50/50
10.988
972185AH1-677 GEN
50/50
39.858
3151041BRUNSWICKG3
50/50
8.374
972187AH1-678 GEN
50/50
19.217
3152661PLYWOOD A
50/50
0.67
970535AG2-341 GEN
50/50
4.577
3144293JTRSVLE
50/50
0.8
3144293JTRSVLE
50/50
0.674
970933AG2-581 GEN
Solar/Wind Harmer
58.849
970099AG2-077 GEN
Solar/Wind Harmer
66.404
971741AH1-377 GEN
Solar/Wind Harmer
43.978
970301AG2-198 GEN
Solar/Wind Harmer
17.332
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.854
316222AC1-221 GEN
Solar/Wind Harmer
3.208
962561AG1-105 GEN
Solar/Wind Harmer
17.747
939181AE1-148 GEN
Solar/Wind Harmer
16.378
313527AB2-043 GEN
Solar/Wind Harmer
4.643
970323AG2-213 GEN
Solar/Wind Harmer
13.768
971775AH1-396 GEN
Solar/Wind Harmer
1.961
316034AC1-036 C
Solar/Wind Harmer
0.511
958211AF2-115 GEN
Solar/Wind Harmer
4.16
963191AG1-168 GEN
Solar/Wind Harmer
2.496
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
15.066
270013AE1-250 PV
Solar/Wind Harmer
2.839
3146776BUCKING
Solar/Wind Harmer
-0.061
3146776BUCKING
Solar/Wind Harmer
-0.005
316217AC1-145 GEN
Solar/Wind Harmer
2.394
316197AC1-042 GEN
Solar/Wind Harmer
1.815
942671AE2-283 GEN
Solar/Wind Harmer
4.885
316263AC1-034 GEN
Solar/Wind Harmer
6.316
961601AG1-000A GEN
Solar/Wind Harmer
5.186
316036AC1-147 C
Solar/Wind Helper
0.59
3142956BIRDNECK
Solar/Wind Helper
0.259
316316AC1-027 C
Solar/Wind Helper
0.606
316185AD1-033 GEN
Solar/Wind Helper
1.799
3145506HICKORY
Solar/Wind Helper
1.507
3145506HICKORY
Solar/Wind Helper
0.904
3145506HICKORY
Solar/Wind Helper
0.226
316236AE1-162_GEN
Solar/Wind Helper
0.498
316339AD2-160 GEN
Solar/Wind Helper
1.397
316018AA1-139 ULT2
Solar/Wind Helper
1.567
316017AA1-139 ULT1
Solar/Wind Helper
1.665
3137176SLIGO L2192
Solar/Wind Helper
1.432
3130086AYDLETT
Solar/Wind Helper
1.421
316033AB2-134 GEN
Solar/Wind Helper
1.19
315697AD1-025 GEN
Solar/Wind Helper
3.953
3146386ELIZ CT
Solar/Wind Helper
0.331
316240AF1-291 C
Solar/Wind Helper
0.444
3142946ENON
Solar/Wind Helper
0.032
316487AF1-042 GEN
Solar/Wind Helper
0.318
316075AC2-137 C
Solar/Wind Helper
0.467
316077AC2-138 C
Solar/Wind Helper
0.286
316431W1029_GEN1
Solar/Wind Helper
1.225
316433W1029_GEN2
Solar/Wind Helper
1.225
3146516WINFALL
Solar/Wind Helper
0.297
3146516WINFALL
Solar/Wind Helper
0.297
3146516WINFALL
Solar/Wind Helper
0.297
3143526WINTERP
Solar/Wind Helper
1.499
3146626S HERTFORD
Solar/Wind Helper
0.28
3146626S HERTFORD
Solar/Wind Helper
0.28
966871AG1-558 GEN
Solar/Wind Helper
0.374
3144356SAPONY
Solar/Wind Helper
0.492
316468AD1-105 GEN
Solar/Wind Helper
1.305
970673AG2-436 GEN
Solar/Wind Harmer
83.06
971967AH1-528 GEN
Solar/Wind Harmer
125.223
970085AG2-068 GEN
Solar/Wind Harmer
41.62
970581AG2-369 GEN
Solar/Wind Harmer
35.794
3147173SINAI
Solar/Wind Harmer
-0.034
3147243WELCO
Solar/Wind Harmer
-0.021
316118AC1-105 GEN
Solar/Wind Harmer
2.295
970865AG2-541 GEN
Solar/Wind Harmer
11.917
316239AB2-077_GEN
Solar/Wind Harmer
0.868
316238AB2-078_GEN
Solar/Wind Harmer
0.868
971443AH1-215 GEN
Solar/Wind Harmer
5.428
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
21.145
970681AG2-440 GEN
Solar/Wind Harmer
16.916
946301AF1-294 GEN
Solar/Wind Harmer
6.823
961791AG1-021 GEN
Solar/Wind Harmer
3.328
270455AD2-022 GEN
Solar/Wind Harmer
4.701
270457AD2-023 GEN
Solar/Wind Harmer
2.384
315657AE1-056 GEN
Solar/Wind Harmer
9.869
316123AC1-075 GEN
Solar/Wind Harmer
2.789
970165AG2-112 GEN
Solar/Wind Harmer
2.455
970163AG2-111 GEN
Solar/Wind Harmer
2.342
970831AG2-522 GEN
Solar/Wind Harmer
9.813
970285AG2-188 GEN
Solar/Wind Harmer
15.354
971845AH1-439 GEN
Solar/Wind Harmer
8.535
270069AE2-166 C O1
Solar/Wind Harmer
2.415
319010AE1-072 C
Solar/Wind Helper
4.079
3143316POE
Solar/Wind Helper
1.407
316305AF2-043 C
Solar/Wind Helper
0.473
316369SG1_INVT
Solar/Wind Helper
1.664
957831AF2-077 GEN
Solar/Wind Helper
0.466
316132AB2-190 GEN1
Solar/Wind Helper
1.933
316349AD2-085 GEN
Solar/Wind Helper
1.523
313526AB2-022
Solar/Wind Helper
0.505
957601AF2-054 GEN
Solar/Wind Helper
0.438
3141873WAN 176
Solar/Wind Helper
0.065
315662AE1-191 GEN
Solar/Wind Helper
1.747
315666AE1-190 GEN
Solar/Wind Helper
0.437
316059AD1-063 C
Solar/Wind Helper
0.326
3141913WHIT STONE
Solar/Wind Helper
0.323
3146486SUNBURY
Solar/Wind Helper
0.323
3146486SUNBURY
Solar/Wind Helper
0.323
3138133OCRAN
Solar/Wind Helper
0.097
3143873LANEXA
Solar/Wind Helper
0.192
3141783LANCAST
Solar/Wind Helper
0.192
3141783LANCAST
Solar/Wind Helper
0.128
316321Z2-027
Solar/Wind Helper
0.487
3145176PASQUOTANK
Solar/Wind Helper
0.198
3141813NORNECK
Solar/Wind Helper
0.304
316312AB1-027
Solar/Wind Helper
0.556
316233AE1-074 FULL
Solar/Wind Helper
0.44
316223AC1-118
Solar/Wind Helper
0.438
316315AB2-025 C
Solar/Wind Helper
0.418
315611Z1-036_GEN2
Solar/Wind Helper
1.411
3130156CHOWAN
Solar/Wind Helper
0.226
3130156CHOWAN
Solar/Wind Helper
0.226
LAGNLTFEXP_LAGN->PJM
CLTF
14.626
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.161
TVALTFEXP_TVA->PJM
CLTF
7.294
CPLELTFEXP_CPLE->PJM
CLTF
19.708
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.004
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.554
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.081
MECLTFEXP_MEC->PJM
CLTF
7.343
SIGELTFEXP_SIGE->PJM
CLTF
0.22
NYPJM->LTFIMP_NY
CLTF
2.38
LGEELTFEXP_LGEE->PJM
CLTF
2.666
WECLTFEXP_WEC->PJM
CLTF
1.395
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113

Details for AE2-094 TP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-2: 511T544_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T544_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.15 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5902.9
MW Contribution:25.22
Bus #Bus NameTypeMW Contribution
315244AE2-183_ST
50/50
18.952
963041AG1-153 GEN
50/50
16.812
3151541CLOVER2
50/50
9.183
3151611KERR 4
50/50
0.532
3151621KERR 5
50/50
0.532
3151631KERR 6
50/50
0.532
3151641KERR 7
50/50
0.532
941031AE2-094 GEN
Solar/Wind Harmer
155.676
944011AF1-069 GEN
Solar/Wind Harmer
48.778
970673AG2-436 GEN
Solar/Wind Harmer
162.646
970673AG2-436 GEN
Solar/Wind Harmer
82.352
971967AH1-528 GEN
Solar/Wind Harmer
124.141
970085AG2-068 GEN
Solar/Wind Harmer
41.268
970581AG2-369 GEN
Solar/Wind Harmer
35.491
3147173SINAI
Solar/Wind Harmer
-0.034
3147243WELCO
Solar/Wind Harmer
-0.021
316118AC1-105 GEN
Solar/Wind Harmer
2.271
970865AG2-541 GEN
Solar/Wind Harmer
11.801
316239AB2-077_GEN
Solar/Wind Harmer
0.856
316238AB2-078_GEN
Solar/Wind Harmer
0.856
971443AH1-215 GEN
Solar/Wind Harmer
5.352
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
20.851
970681AG2-440 GEN
Solar/Wind Harmer
16.681
946301AF1-294 GEN
Solar/Wind Harmer
6.73
961791AG1-021 GEN
Solar/Wind Harmer
3.283
270455AD2-022 GEN
Solar/Wind Harmer
4.664
270457AD2-023 GEN
Solar/Wind Harmer
2.365
315657AE1-056 GEN
Solar/Wind Harmer
9.735
316123AC1-075 GEN
Solar/Wind Harmer
2.761
970165AG2-112 GEN
Solar/Wind Harmer
2.431
970163AG2-111 GEN
Solar/Wind Harmer
2.319
970831AG2-522 GEN
Solar/Wind Harmer
9.696
970285AG2-188 GEN
Solar/Wind Harmer
15.118
971845AH1-439 GEN
Solar/Wind Harmer
8.397
270069AE2-166 C O1
Solar/Wind Harmer
2.394
3143316POE
Solar/Wind Helper
1.57
316132AB2-190 GEN1
Solar/Wind Helper
1.893
316369SG1_INVT
Solar/Wind Helper
1.59
957831AF2-077 GEN
Solar/Wind Helper
0.437
316315AB2-025 C
Solar/Wind Helper
0.494
957601AF2-054 GEN
Solar/Wind Helper
0.418
3141873WAN 176
Solar/Wind Helper
0.062
3151031BRUNSWICKG2
50/50
8.303
970413AG2-270 GEN
50/50
40.265
3151591KERR 2
50/50
0.532
3144293JTRSVLE
50/50
0.79
970917AG2-570 GEN
Solar/Wind Harmer
166.275
316478AD1-087 GEN
Solar/Wind Harmer
4.189
316486AD2-202 GEN
Solar/Wind Harmer
1.227
970909AG2-566 GEN
Solar/Wind Harmer
3.255
316248AF1-058 C
Solar/Wind Harmer
1.033
960061AF2-297 GEN
Solar/Wind Harmer
17.135
316283AC2-100 C
Solar/Wind Harmer
2.94
971683AH1-343 GEN
Solar/Wind Harmer
13.259
316131AB2-060 GEN
Solar/Wind Harmer
3.032
964241AG1-285 GEN
Solar/Wind Harmer
21.724
315785AD2-033 C
Solar/Wind Harmer
6.194
970257AG2-171 GEN
Solar/Wind Harmer
10.181
959311AF2-222 GEN
Solar/Wind Harmer
28.197
963181AG1-167 GEN
Solar/Wind Harmer
2.462
315243AE2-183_GT3
50/50
10.962
3151051BRUNSWICKS1
50/50
17.232
3151021BRUNSWICKG1
50/50
8.303
971451AH1-221 GEN
50/50
25.218
3151531CLOVER1
50/50
9.227
3151601KERR 3
50/50
0.532
3151581KERR 1
50/50
0.19
3144293JTRSVLE
50/50
0.79
971629AH1-314 GEN
50/50
17.731
3151561HALLBR1
50/50
0.363
970919AG2-571 GEN
Solar/Wind Harmer
21.047
970087AG2-069 GEN
Solar/Wind Harmer
61.902
957481AF2-042 GEN
Solar/Wind Harmer
164.509
315693AD1-088 GEN
Solar/Wind Harmer
24.007
962491AG1-098 GEN
Solar/Wind Harmer
31.634
315687AD1-152 GEN
Solar/Wind Harmer
5.265
316003AC1-222 GEN
Solar/Wind Harmer
3.162
970401AG2-262 GEN
Solar/Wind Harmer
2.07
316237AB2-079_GEN
Solar/Wind Harmer
0.856
970685AG2-442 GEN
Solar/Wind Harmer
23.354
963171AG1-166 GEN
Solar/Wind Harmer
3.283
971563AH1-280 GEN
Solar/Wind Harmer
3.283
3146926FARMVIL
Solar/Wind Harmer
-0.014
971065AG2-659 GEN
Solar/Wind Harmer
11.094
316129AC1-054 GEN
Solar/Wind Harmer
1.827
970223AG2-152 GEN
Solar/Wind Harmer
17.059
270016AE1-250 BESS
Solar/Wind Harmer
2.815
3147123OTTER R
Solar/Wind Harmer
-0.01
270574AD1-017 GEN2
Solar/Wind Harmer
5.528
316322AB2-045
Solar/Wind Harmer
0.506
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.477
270030AE2-140 GEN
Solar/Wind Harmer
19.567
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.809
316049AB1-081 GEN
Solar/Wind Harmer
1.448
3142053HEARTS
Solar/Wind Harmer
0.158
316294AC1-161 GEN
Solar/Wind Helper
7.244
316381AD1-082 GEN
Solar/Wind Helper
1.747
316375AC2-012 GEN
Solar/Wind Helper
0.879
3145336SMITFLD
Solar/Wind Helper
1.331
316458AB2-190 GEN2
Solar/Wind Helper
1.893
316159AE1-175 C
Solar/Wind Helper
0.497
316388AE2-253 GEN
Solar/Wind Helper
1.201
3142433PROV 92
Solar/Wind Helper
1.254
3142543TWELFTH
Solar/Wind Helper
0.03
3141766HARMONY
Solar/Wind Helper
0.062
3146456SLIGO L269
Solar/Wind Helper
0.308
3138133OCRAN
Solar/Wind Helper
0.185
316072AD1-144
Solar/Wind Helper
0.35
316246AF1-032 C
Solar/Wind Helper
0.342
964211AG1-282 GEN
Solar/Wind Helper
0.397
3141726DUNNSVL
Solar/Wind Helper
1.179
3143526WINTERP
Solar/Wind Helper
1.519
3142416OLDCHRC
Solar/Wind Helper
0.752
3143226MDLTHAN
Solar/Wind Helper
0.289
3142416OLDCHRC
Solar/Wind Helper
0.288
316337AD2-073 GEN
Solar/Wind Helper
0.434
3146516WINFALL
Solar/Wind Helper
0.813
3146516WINFALL
Solar/Wind Helper
0.251
3147133PAMPLIN
Solar/Wind Harmer
-0.081
971193AH1-056 GEN
Solar/Wind Harmer
16.225
942461AE2-259 GEN
Solar/Wind Harmer
3.773
3146926FARMVIL
Solar/Wind Harmer
-0.014
270018AE2-047 C O1
Solar/Wind Harmer
1.363
270197AD1-017 GEN1
Solar/Wind Harmer
1.661
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.802
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.477
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
270336AE1-100 GEN
Solar/Wind Harmer
1.551
961601AG1-000A GEN
Solar/Wind Harmer
5.225
315773AC2-141 GEN
Solar/Wind Helper
8.525
315839AE2-212 C
Solar/Wind Helper
0.497
3144536CHRHLND
Solar/Wind Helper
0.05
3144873MCLAUGH
Solar/Wind Helper
0.008
3145336SMITFLD
Solar/Wind Helper
0.133
316382AG1-145 C
Solar/Wind Helper
0.441
316156AD2-030 GEN
Solar/Wind Helper
0.47
3142946ENON
Solar/Wind Helper
0.104
316280AD1-041 GEN
Solar/Wind Helper
1.046
3146456SLIGO L269
Solar/Wind Helper
0.308
316484AD2-074 GEN
Solar/Wind Helper
0.583
316404AE1-155 C
Solar/Wind Helper
2.523
316320Y1-086
Solar/Wind Helper
0.126
316473AC1-191 GEN
Solar/Wind Helper
1.704
3141906WESTMOR
Solar/Wind Helper
0.111
316435W1029_GEN3
Solar/Wind Helper
1.037
3146516WINFALL
Solar/Wind Helper
0.251
966881AG1-559 GEN
Solar/Wind Helper
0.328
3146626S HERTFORD
Solar/Wind Helper
0.236
970533AG2-339 GEN
50/50
65.686
970531AG2-338 GEN
50/50
26.274
315242AE2-183_GT2
50/50
10.962
315241AE2-183_GT1
50/50
10.894
972185AH1-677 GEN
50/50
39.518
3151041BRUNSWICKG3
50/50
8.303
972187AH1-678 GEN
50/50
19.053
3152661PLYWOOD A
50/50
0.663
970535AG2-341 GEN
50/50
4.519
3144293JTRSVLE
50/50
0.79
3144293JTRSVLE
50/50
0.665
970933AG2-581 GEN
Solar/Wind Harmer
58.334
970099AG2-077 GEN
Solar/Wind Harmer
65.804
971741AH1-377 GEN
Solar/Wind Harmer
43.523
970301AG2-198 GEN
Solar/Wind Harmer
17.145
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.775
316222AC1-221 GEN
Solar/Wind Harmer
3.182
962561AG1-105 GEN
Solar/Wind Harmer
17.536
939181AE1-148 GEN
Solar/Wind Harmer
16.186
313527AB2-043 GEN
Solar/Wind Harmer
4.576
970323AG2-213 GEN
Solar/Wind Harmer
13.574
971775AH1-396 GEN
Solar/Wind Harmer
1.933
316034AC1-036 C
Solar/Wind Harmer
0.503
958211AF2-115 GEN
Solar/Wind Harmer
4.103
963191AG1-168 GEN
Solar/Wind Harmer
2.462
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
14.918
270013AE1-250 PV
Solar/Wind Harmer
2.815
3146776BUCKING
Solar/Wind Harmer
-0.06
3146776BUCKING
Solar/Wind Harmer
-0.005
316217AC1-145 GEN
Solar/Wind Harmer
2.37
316197AC1-042 GEN
Solar/Wind Harmer
1.797
942671AE2-283 GEN
Solar/Wind Harmer
4.838
316263AC1-034 GEN
Solar/Wind Harmer
6.29
961601AG1-000A GEN
Solar/Wind Harmer
5.16
316240AF1-291 C
Solar/Wind Helper
0.471
316036AC1-147 C
Solar/Wind Helper
0.511
316236AE1-162_GEN
Solar/Wind Helper
0.447
316316AC1-027 C
Solar/Wind Helper
0.524
3142956BIRDNECK
Solar/Wind Helper
0.223
316033AB2-134 GEN
Solar/Wind Helper
1.137
315697AD1-025 GEN
Solar/Wind Helper
3.779
316185AD1-033 GEN
Solar/Wind Helper
1.551
3145506HICKORY
Solar/Wind Helper
1.298
3145506HICKORY
Solar/Wind Helper
0.779
3145506HICKORY
Solar/Wind Helper
0.195
3144356SAPONY
Solar/Wind Helper
0.581
316339AD2-160 GEN
Solar/Wind Helper
1.201
316018AA1-139 ULT2
Solar/Wind Helper
1.346
316017AA1-139 ULT1
Solar/Wind Helper
1.43
3142946ENON
Solar/Wind Helper
0.031
3137176SLIGO L2192
Solar/Wind Helper
1.229
3130086AYDLETT
Solar/Wind Helper
1.219
316487AF1-042 GEN
Solar/Wind Helper
0.305
316075AC2-137 C
Solar/Wind Helper
0.459
316077AC2-138 C
Solar/Wind Helper
0.276
3143526WINTERP
Solar/Wind Helper
1.519
3146386ELIZ CT
Solar/Wind Helper
0.283
966871AG1-558 GEN
Solar/Wind Helper
0.376
316468AD1-105 GEN
Solar/Wind Helper
1.308
316431W1029_GEN1
Solar/Wind Helper
1.037
316433W1029_GEN2
Solar/Wind Helper
1.037
3146516WINFALL
Solar/Wind Helper
0.251
3146516WINFALL
Solar/Wind Helper
0.251
3146516WINFALL
Solar/Wind Helper
0.251
3146626S HERTFORD
Solar/Wind Helper
0.236
3146626S HERTFORD
Solar/Wind Helper
0.236
315662AE1-191 GEN
Solar/Wind Helper
1.674
315666AE1-190 GEN
Solar/Wind Helper
0.419
3143873LANEXA
Solar/Wind Helper
0.186
316059AD1-063 C
Solar/Wind Helper
0.312
3141913WHIT STONE
Solar/Wind Helper
0.309
3138133OCRAN
Solar/Wind Helper
0.093
3141783LANCAST
Solar/Wind Helper
0.184
3141783LANCAST
Solar/Wind Helper
0.123
319010AE1-072 C
Solar/Wind Helper
3.5
316349AD2-085 GEN
Solar/Wind Helper
1.396
316305AF2-043 C
Solar/Wind Helper
0.402
3141813NORNECK
Solar/Wind Helper
0.293
316233AE1-074 FULL
Solar/Wind Helper
0.446
316312AB1-027
Solar/Wind Helper
0.55
313526AB2-022
Solar/Wind Helper
0.431
316223AC1-118
Solar/Wind Helper
0.424
3146486SUNBURY
Solar/Wind Helper
0.274
3146486SUNBURY
Solar/Wind Helper
0.274
316321Z2-027
Solar/Wind Helper
0.414
3145176PASQUOTANK
Solar/Wind Helper
0.168
LAGNLTFEXP_LAGN->PJM
CLTF
14.499
CBM South 2LTFEXP_CBM-S2->PJM
CBM
43.842
TVALTFEXP_TVA->PJM
CLTF
7.231
CPLELTFEXP_CPLE->PJM
CLTF
19.58
CBM West 2LTFEXP_CBM-W2->PJM
CBM
77.279
CBM West 1LTFEXP_CBM-W1->PJM
CBM
48.979
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.858
MECLTFEXP_MEC->PJM
CLTF
7.267
SIGELTFEXP_SIGE->PJM
CLTF
0.218
NYPJM->LTFIMP_NY
CLTF
2.38
LGEELTFEXP_LGEE->PJM
CLTF
2.637
WECLTFEXP_WEC->PJM
CLTF
1.38
AG2-052LTFEXP_AG2-052->PJM
LTF
0.074
AH1-155LTFEXP_AH1-155->PJM
LTF
0.111

Details for AE2-094 TP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 591_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 591_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.48 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4374.45
MW Contribution:31.28
Bus #Bus NameTypeMW Contribution
315244AE2-183_ST
50/50
23.093
963041AG1-153 GEN
50/50
20.853
941031AE2-094 GEN
Solar/Wind Harmer
160.06
944011AF1-069 GEN
Solar/Wind Harmer
52.298
970673AG2-436 GEN
Solar/Wind Harmer
176.854
970673AG2-436 GEN
Solar/Wind Harmer
117.903
970085AG2-068 GEN
Solar/Wind Harmer
38.301
970581AG2-369 GEN
Solar/Wind Harmer
32.939
3143316POE
Solar/Wind Helper
1.046
316369SG1_INVT
Solar/Wind Helper
1.16
316132AB2-190 GEN1
Solar/Wind Helper
1.367
957831AF2-077 GEN
Solar/Wind Helper
0.32
319010AE1-072 C
Solar/Wind Helper
2.682
316305AF2-043 C
Solar/Wind Helper
0.313
316349AD2-085 GEN
Solar/Wind Helper
1.054
957601AF2-054 GEN
Solar/Wind Helper
0.305
3141873WAN 176
Solar/Wind Helper
0.046
315662AE1-191 GEN
Solar/Wind Helper
1.221
315666AE1-190 GEN
Solar/Wind Helper
0.305
316059AD1-063 C
Solar/Wind Helper
0.228
3143873LANEXA
Solar/Wind Helper
0.136
3141913WHIT STONE
Solar/Wind Helper
0.226
3138133OCRAN
Solar/Wind Helper
0.068
3141783LANCAST
Solar/Wind Helper
0.134
3141783LANCAST
Solar/Wind Helper
0.09
3151031BRUNSWICKG2
50/50
10.298
970917AG2-570 GEN
Solar/Wind Harmer
64.403
316283AC2-100 C
Solar/Wind Harmer
0.275
315773AC2-141 GEN
Solar/Wind Helper
5.984
3144873MCLAUGH
Solar/Wind Helper
0.006
3144536CHRHLND
Solar/Wind Helper
0.038
315839AE2-212 C
Solar/Wind Helper
0.339
3145336SMITFLD
Solar/Wind Helper
0.1
316382AG1-145 C
Solar/Wind Helper
0.322
3146456SLIGO L269
Solar/Wind Helper
0.236
316156AD2-030 GEN
Solar/Wind Helper
0.343
316280AD1-041 GEN
Solar/Wind Helper
0.763
3142946ENON
Solar/Wind Helper
0.075
315243AE2-183_GT3
50/50
13.357
3151051BRUNSWICKS1
50/50
21.374
3151021BRUNSWICKG1
50/50
10.298
971451AH1-221 GEN
50/50
31.279
971629AH1-314 GEN
50/50
11.732
970919AG2-571 GEN
Solar/Wind Harmer
25.761
970087AG2-069 GEN
Solar/Wind Harmer
57.452
316294AC1-161 GEN
Solar/Wind Helper
5.084
316375AC2-012 GEN
Solar/Wind Helper
0.669
3145336SMITFLD
Solar/Wind Helper
0.997
316381AD1-082 GEN
Solar/Wind Helper
1.253
316388AE2-253 GEN
Solar/Wind Helper
0.919
316458AB2-190 GEN2
Solar/Wind Helper
1.367
316159AE1-175 C
Solar/Wind Helper
0.363
3146456SLIGO L269
Solar/Wind Helper
0.236
316072AD1-144
Solar/Wind Helper
0.269
316246AF1-032 C
Solar/Wind Helper
0.266
3142433PROV 92
Solar/Wind Helper
0.908
3141766HARMONY
Solar/Wind Helper
0.045
3142543TWELFTH
Solar/Wind Helper
0.022
3138133OCRAN
Solar/Wind Helper
0.135
970533AG2-339 GEN
50/50
77.249
970531AG2-338 GEN
50/50
30.9
315242AE2-183_GT2
50/50
13.357
315241AE2-183_GT1
50/50
13.275
972185AH1-677 GEN
50/50
48.153
3151041BRUNSWICKG3
50/50
10.298
972187AH1-678 GEN
50/50
23.633
316222AC1-221 GEN
Solar/Wind Harmer
0.574
316036AC1-147 C
Solar/Wind Helper
0.389
316316AC1-027 C
Solar/Wind Helper
0.399
3142956BIRDNECK
Solar/Wind Helper
0.17
316185AD1-033 GEN
Solar/Wind Helper
1.183
316236AE1-162_GEN
Solar/Wind Helper
0.335
3145506HICKORY
Solar/Wind Helper
0.991
3145506HICKORY
Solar/Wind Helper
0.595
3145506HICKORY
Solar/Wind Helper
0.149
316240AF1-291 C
Solar/Wind Helper
0.327
316033AB2-134 GEN
Solar/Wind Helper
0.83
315697AD1-025 GEN
Solar/Wind Helper
2.757
316339AD2-160 GEN
Solar/Wind Helper
0.919
316018AA1-139 ULT2
Solar/Wind Helper
1.03
316017AA1-139 ULT1
Solar/Wind Helper
1.094
3137176SLIGO L2192
Solar/Wind Helper
0.941
3130086AYDLETT
Solar/Wind Helper
0.934
3142946ENON
Solar/Wind Helper
0.023
LAGNLTFEXP_LAGN->PJM
CLTF
11.955
CBM South 2LTFEXP_CBM-S2->PJM
CBM
37.412
TVALTFEXP_TVA->PJM
CLTF
5.929
CPLELTFEXP_CPLE->PJM
CLTF
16.699
CBM West 2LTFEXP_CBM-W2->PJM
CBM
62.441
CBM West 1LTFEXP_CBM-W1->PJM
CBM
37.352
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.231
MECLTFEXP_MEC->PJM
CLTF
5.698
SIGELTFEXP_SIGE->PJM
CLTF
0.168
NYPJM->LTFIMP_NY
CLTF
1.879
LGEELTFEXP_LGEE->PJM
CLTF
2.007
WECLTFEXP_WEC->PJM
CLTF
1.057

Details for AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:176.17 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:985.35
MW Contribution:3.37
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
3.284
3151611KERR 4
50/50
0.315
3151621KERR 5
50/50
0.315
3151631KERR 6
50/50
0.315
3151641KERR 7
50/50
0.315
3151281ROARAP4
50/50
0.107
3151281ROARAP4
50/50
0.1
963041AG1-153 GEN
50/50
2.246
315244AE2-183_ST
50/50
2.348
970285AG2-188 GEN
Solar/Wind Harmer
51.681
315657AE1-056 GEN
Solar/Wind Harmer
13.387
946301AF1-294 GEN
Solar/Wind Harmer
7.171
961791AG1-021 GEN
Solar/Wind Harmer
3.489
970683AG2-441 GEN
Solar/Wind Harmer
21.861
970681AG2-440 GEN
Solar/Wind Harmer
17.489
3144303KENBRDG
Solar/Wind Harmer
0.232
971443AH1-215 GEN
Solar/Wind Harmer
4.821
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.369
3147173SINAI
Solar/Wind Harmer
0.127
3147243WELCO
Solar/Wind Harmer
0.079
970831AG2-522 GEN
Solar/Wind Harmer
5.372
970865AG2-541 GEN
Solar/Wind Harmer
3.489
971967AH1-528 GEN
Solar/Wind Harmer
15.071
316087AB2-174 GEN
Solar/Wind Harmer
0.003
3137643SOCKMAN
Solar/Wind Harmer
0.359
316123AC1-075 GEN
Solar/Wind Harmer
0.114
970165AG2-112 GEN
Solar/Wind Harmer
0.676
970163AG2-111 GEN
Solar/Wind Harmer
0.645
315607AA1-063A GEN
Solar/Wind Harmer
0.167
970085AG2-068 GEN
Solar/Wind Harmer
4.361
970581AG2-369 GEN
Solar/Wind Harmer
3.75
3146043SEABORD
Solar/Wind Harmer
0.081
970673AG2-436 GEN
Solar/Wind Harmer
17.208
970673AG2-436 GEN
Solar/Wind Harmer
11.472
941031AE2-094 GEN
Solar/Wind Harmer
14.299
944011AF1-069 GEN
Solar/Wind Harmer
4.672
315652AC1-086 GEN
Solar/Wind Harmer
8.029
3146033SCOT NK
Solar/Wind Harmer
0.291
3145796HORNRTN
Solar/Wind Harmer
0.232
3145796HORNRTN
Solar/Wind Harmer
0.029
965291AG1-394 GEN
Solar/Wind Harmer
0.32
316319Z2-044 C
Solar/Wind Harmer
0
3145893MURPHYS
Solar/Wind Harmer
0.191
3145893MURPHYS
Solar/Wind Harmer
0.071
3145513AHOSKIE
Solar/Wind Harmer
0.144
3145513AHOSKIE
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.136
3145683EARLEYS
Solar/Wind Harmer
0.068
3145683EARLEYS
Solar/Wind Harmer
0.068
3145573BETHELC
Solar/Wind Harmer
0.067
3145573BETHELC
Solar/Wind Harmer
0.067
316420AA1-050 GEN
Solar/Wind Harmer
0.002
957861AF2-080 GEN
Solar/Wind Harmer
2.854
316005AA1-067
Solar/Wind Harmer
0.069
3145746EVERETS
Solar/Wind Harmer
0.257
3145746EVERETS
Solar/Wind Harmer
0.065
3145746EVERETS
Solar/Wind Harmer
0.065
3145746EVERETS
Solar/Wind Harmer
0.065
970181AG2-120 GEN
Solar/Wind Harmer
0.805
315814AE2-033 C
Solar/Wind Harmer
4.945
316315AB2-025 C
Solar/Wind Harmer
0.05
3146206CASHIE
Solar/Wind Harmer
0.062
970601AG2-382 GEN
Solar/Wind Harmer
2.302
315732AD1-074 GEN1
Solar/Wind Harmer
0.345
315733AD1-074 GEN2
Solar/Wind Harmer
0.345
315735AD1-075 GEN1
Solar/Wind Harmer
0.173
3130546PLYMOUTH
Solar/Wind Harmer
0.06
315816AE2-034 GEN
Solar/Wind Harmer
0.249
270494AE1-108_GEN
Solar/Wind Helper
4.45
3138266HYDRAULIC
Solar/Wind Helper
0.009
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3144293JTRSVLE
50/50
1.227
3151531CLOVER1
50/50
3.3
3151601KERR 3
50/50
0.315
3151581KERR 1
50/50
0.112
3147043LAWRENC
50/50
1.233
3151261ROARAP2
50/50
0.11
3151051BRUNSWICKS1
50/50
2.302
3151021BRUNSWICKG1
50/50
1.109
971451AH1-221 GEN
50/50
3.369
315243AE2-183_GT3
50/50
1.358
3151391GASTONA
50/50
0.198
3151411GASTONB
50/50
0.198
3146926FARMVIL
Solar/Wind Harmer
0.322
963171AG1-166 GEN
Solar/Wind Harmer
1.938
971563AH1-280 GEN
Solar/Wind Harmer
3.876
970685AG2-442 GEN
Solar/Wind Harmer
24.484
962491AG1-098 GEN
Solar/Wind Harmer
11.925
316237AB2-079_GEN
Solar/Wind Harmer
0.002
315693AD1-088 GEN
Solar/Wind Harmer
9.548
970401AG2-262 GEN
Solar/Wind Harmer
0.937
957481AF2-042 GEN
Solar/Wind Harmer
40.4
315687AD1-152 GEN
Solar/Wind Harmer
0.005
971065AG2-659 GEN
Solar/Wind Harmer
5.702
316129AC1-054 GEN
Solar/Wind Harmer
0.489
971795AH1-408 GEN
Solar/Wind Harmer
7.855
316003AC1-222 GEN
Solar/Wind Harmer
0.003
960081AF2-299 GEN
Solar/Wind Harmer
0.909
3145783HORNRTN
Solar/Wind Harmer
0.086
316190AA2-174 GEN
Solar/Wind Harmer
0
970919AG2-571 GEN
Solar/Wind Harmer
2.916
970087AG2-069 GEN
Solar/Wind Harmer
6.541
316212AC1-099_GEN
Solar/Wind Harmer
0.387
3146263WOODLND
Solar/Wind Harmer
0.074
316011AB1-132 GEN
Solar/Wind Harmer
1.327
316023GEN1_S
Solar/Wind Harmer
0.164
962571AG1-106 GEN
Solar/Wind Harmer
1.039
3145796HORNRTN
Solar/Wind Harmer
0.239
3145796HORNRTN
Solar/Wind Harmer
0.072
3146233WITAKRS
Solar/Wind Harmer
0.286
3145893MURPHYS
Solar/Wind Harmer
0.283
3145893MURPHYS
Solar/Wind Harmer
0.314
315722AD1-056 GEN
Solar/Wind Harmer
0.447
3145823KELFORD
Solar/Wind Harmer
0.07
3145543BTLEBRO
Solar/Wind Harmer
0.07
3145543BTLEBRO
Solar/Wind Harmer
0.056
316359AB2-059 GEN
Solar/Wind Harmer
0.251
316049AB1-081 GEN
Solar/Wind Harmer
0.4
3142053HEARTS
Solar/Wind Harmer
0.123
3146173TUNIS
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.068
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.067
3145493TOT1
Solar/Wind Harmer
0.3
940641AE2-051 GEN
Solar/Wind Harmer
5.396
316494AC1-189 GEN
Solar/Wind Harmer
0.224
3145746EVERETS
Solar/Wind Harmer
0.065
3145746EVERETS
Solar/Wind Harmer
0.065
3146293MARTNCO
Solar/Wind Harmer
0.059
939411AE1-173 GEN
Solar/Wind Harmer
26.923
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3145963POPLR C
Solar/Wind Harmer
0.062
3146206CASHIE
Solar/Wind Harmer
0.062
971547AH1-271 GEN
Solar/Wind Harmer
1.316
3145663CRESWEL
Solar/Wind Harmer
0.162
971163AH1-040 GEN
Solar/Wind Harmer
4.641
316322AB2-045
Solar/Wind Helper
0.957
3146776BUCKING
Solar/Wind Helper
0.343
316336AC2-165 C
Solar/Wind Helper
1.513
3144293JTRSVLE
50/50
1.227
970413AG2-270 GEN
50/50
14.4
3151591KERR 2
50/50
0.315
3151261ROARAP2
50/50
0.107
3151031BRUNSWICKG2
50/50
1.109
3151391GASTONA
50/50
0.198
3151411GASTONB
50/50
0.198
3146926FARMVIL
Solar/Wind Harmer
0.322
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
4.196
3147133PAMPLIN
Solar/Wind Harmer
1.218
971193AH1-056 GEN
Solar/Wind Harmer
23.635
963181AG1-167 GEN
Solar/Wind Harmer
1.454
959311AF2-222 GEN
Solar/Wind Harmer
26.76
970257AG2-171 GEN
Solar/Wind Harmer
9.287
315785AD2-033 C
Solar/Wind Harmer
2.238
964241AG1-285 GEN
Solar/Wind Harmer
15.712
316131AB2-060 GEN
Solar/Wind Harmer
0.665
316478AD1-087 GEN
Solar/Wind Harmer
0.537
316486AD2-202 GEN
Solar/Wind Harmer
0.158
3147043LAWRENC
Solar/Wind Harmer
0.077
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
5.403
971683AH1-343 GEN
Solar/Wind Harmer
4.014
313506AB2-031 GEN
Solar/Wind Harmer
0.283
316283AC2-100 C
Solar/Wind Harmer
0.162
970917AG2-570 GEN
Solar/Wind Harmer
7.29
316210AC1-098 GEN
Solar/Wind Harmer
0.693
316327AA2-057 GEN
Solar/Wind Harmer
0.111
3146263WOODLND
Solar/Wind Harmer
0.074
316365GEN2_N
Solar/Wind Harmer
0.164
3142666NORTHAMPTON
Solar/Wind Harmer
0.072
3145796HORNRTN
Solar/Wind Harmer
0.29
3145796HORNRTN
Solar/Wind Harmer
0.072
3146233WITAKRS
Solar/Wind Harmer
0.361
3146233WITAKRS
Solar/Wind Harmer
0.049
3138543CONSLDL
Solar/Wind Harmer
0.047
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3145893MURPHYS
Solar/Wind Harmer
0.118
3145893MURPHYS
Solar/Wind Harmer
0.071
315724AD1-057 GEN
Solar/Wind Harmer
0.265
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.07
957521AF2-046 GEN
Solar/Wind Harmer
5.233
961681AG1-008 GEN
Solar/Wind Harmer
5.233
3145543BTLEBRO
Solar/Wind Harmer
0.07
3145543BTLEBRO
Solar/Wind Harmer
0.07
971623AH1-311 GEN
Solar/Wind Harmer
0.14
3146173TUNIS
Solar/Wind Harmer
0.069
961601AG1-000A GEN
Solar/Wind Harmer
4.909
316463AE2-346 GEN
Solar/Wind Harmer
0.059
316140AB2-099
Solar/Wind Harmer
0.025
962331AG1-082 GEN
Solar/Wind Harmer
0.733
3146073TAR RVR
Solar/Wind Harmer
0.067
3146083TARBORO
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.065
3145746EVERETS
Solar/Wind Harmer
0.065
3156021HOLLOMANSOL
Solar/Wind Harmer
0.291
3145933PARMELE
Solar/Wind Harmer
0.064
966801AG1-551 GEN
Solar/Wind Harmer
0.744
3145963POPLR C
Solar/Wind Harmer
0.062
3146206CASHIE
Solar/Wind Harmer
0.062
315737AD1-076 GEN
Solar/Wind Harmer
0.772
971157AH1-035 GEN
Solar/Wind Harmer
0.716
315614AA2-178 GEN
Solar/Wind Harmer
0.332
3145273HOLLAND
Solar/Wind Harmer
0.043
3146776BUCKING
Solar/Wind Helper
0.309
316313AB2-026
Solar/Wind Helper
0.361
316258AE1-075 C
Solar/Wind Helper
0.325
316405AF2-144 C
Solar/Wind Helper
0.271
3148013FISHERV
Solar/Wind Helper
0.126
3144293JTRSVLE
50/50
1.227
3144293JTRSVLE
50/50
1.034
970535AG2-341 GEN
50/50
3.152
3152661PLYWOOD A
50/50
0.306
3151041BRUNSWICKG3
50/50
1.109
972187AH1-678 GEN
50/50
2.545
315242AE2-183_GT2
50/50
1.358
315241AE2-183_GT1
50/50
1.35
972185AH1-677 GEN
50/50
4.896
970533AG2-339 GEN
50/50
6.901
970531AG2-338 GEN
50/50
2.76
3151361ROSEMG1
50/50
0.261
3151371ROSEMS1
50/50
0.162
3151381ROSEMG2
50/50
0.122
970301AG2-198 GEN
Solar/Wind Harmer
16.784
3147133PAMPLIN
Solar/Wind Harmer
0.388
3147133PAMPLIN
Solar/Wind Harmer
0.31
958211AF2-115 GEN
Solar/Wind Harmer
4.361
963191AG1-168 GEN
Solar/Wind Harmer
1.454
971741AH1-377 GEN
Solar/Wind Harmer
34.597
316034AC1-036 C
Solar/Wind Harmer
0.021
970323AG2-213 GEN
Solar/Wind Harmer
12.383
971775AH1-396 GEN
Solar/Wind Harmer
0.464
313527AB2-043 GEN
Solar/Wind Harmer
0.003
962561AG1-105 GEN
Solar/Wind Harmer
8.006
939181AE1-148 GEN
Solar/Wind Harmer
7.768
964791AG1-342 GEN
Solar/Wind Harmer
3.068
3146843MT LREL
Solar/Wind Harmer
0.159
3146843MT LREL
Solar/Wind Harmer
0.159
970099AG2-077 GEN
Solar/Wind Harmer
16.16
970933AG2-581 GEN
Solar/Wind Harmer
8.957
316181AB2-040 GEN
Solar/Wind Harmer
0.133
3145593CAROLNA
Solar/Wind Harmer
0.088
3145593CAROLNA
Solar/Wind Harmer
0.088
966811AG1-552 GEN
Solar/Wind Harmer
0.957
3145593CAROLNA
Solar/Wind Harmer
0.11
3145783HORNRTN
Solar/Wind Harmer
1.539
3145783HORNRTN
Solar/Wind Harmer
1.231
3145783HORNRTN
Solar/Wind Harmer
0.385
3145783HORNRTN
Solar/Wind Harmer
0.154
316426AA2-053 GEN
Solar/Wind Harmer
0.286
316222AC1-221 GEN
Solar/Wind Harmer
0.347
316274AC1-208 GEN
Solar/Wind Harmer
0.402
3142666NORTHAMPTON
Solar/Wind Harmer
0.072
3142666NORTHAMPTON
Solar/Wind Harmer
0.072
3142666NORTHAMPTON
Solar/Wind Harmer
0.072
3142666NORTHAMPTON
Solar/Wind Harmer
0.044
942751AE2-291 GEN
Solar/Wind Harmer
3.947
3145796HORNRTN
Solar/Wind Harmer
0.217
3145893MURPHYS
Solar/Wind Harmer
0.473
3145893MURPHYS
Solar/Wind Harmer
0.127
316263AC1-034 GEN
Solar/Wind Harmer
2.657
3146173TUNIS
Solar/Wind Harmer
0.069
3146173TUNIS
Solar/Wind Harmer
0.069
961601AG1-000A GEN
Solar/Wind Harmer
1.227
3145493TOT1
Solar/Wind Harmer
0.156
3145453TOT5
Solar/Wind Harmer
0.094
3145603CNETO
Solar/Wind Harmer
0.063
3145933PARMELE
Solar/Wind Harmer
0.128
3145933PARMELE
Solar/Wind Harmer
0.064
3144356SAPONY
Solar/Wind Harmer
0.517
316065AD1-022 GEN
Solar/Wind Harmer
2.811
315742AE1-103 GEN
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Helper
3.433
3146776BUCKING
Solar/Wind Helper
0.278
315821AE2-092 GEN
Solar/Wind Helper
2.985
LAGNLTFEXP_LAGN->PJM
CLTF
2.753
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.143
TVALTFEXP_TVA->PJM
CLTF
1.358
CPLELTFEXP_CPLE->PJM
CLTF
4.949
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.581
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.475
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.539
MECLTFEXP_MEC->PJM
CLTF
1.12
SIGELTFEXP_SIGE->PJM
CLTF
0.032
NYPJM->LTFIMP_NY
CLTF
0.48
LGEELTFEXP_LGEE->PJM
CLTF
0.362
WECLTFEXP_WEC->PJM
CLTF
0.189

Details for AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.37 %
Rating:559.3 MVA
Rating Type:A
MVA to Mitigate:617.32
MW Contribution:2.32
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.183
3151591KERR 2
50/50
0.279
970413AG2-270 GEN
50/50
12.485
3151261ROARAP2
50/50
0.086
3144293JTRSVLE
50/50
1.183
3151601KERR 3
50/50
0.279
3151581KERR 1
50/50
0.1
3151531CLOVER1
50/50
2.861
3147043LAWRENC
50/50
1.063
3151261ROARAP2
50/50
0.088
3151051BRUNSWICKS1
50/50
1.588
3151021BRUNSWICKG1
50/50
0.765
971451AH1-221 GEN
50/50
2.324
3146926FARMVIL
Solar/Wind Harmer
0.316
963171AG1-166 GEN
Solar/Wind Harmer
1.868
971563AH1-280 GEN
Solar/Wind Harmer
3.736
970685AG2-442 GEN
Solar/Wind Harmer
23.448
962491AG1-098 GEN
Solar/Wind Harmer
10.797
3144293JTRSVLE
50/50
1.183
3144293JTRSVLE
50/50
0.996
970535AG2-341 GEN
50/50
2.851
3152661PLYWOOD A
50/50
0.269
3151041BRUNSWICKG3
50/50
0.765
972187AH1-678 GEN
50/50
1.756
970301AG2-198 GEN
Solar/Wind Harmer
16.182
3147133PAMPLIN
Solar/Wind Harmer
0.375
3147133PAMPLIN
Solar/Wind Harmer
0.3
3151031BRUNSWICKG2
50/50
0.765
3146926FARMVIL
Solar/Wind Harmer
0.316
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
4.045
3147133PAMPLIN
Solar/Wind Harmer
1.178
971193AH1-056 GEN
Solar/Wind Harmer
22.863
963181AG1-167 GEN
Solar/Wind Harmer
1.401
959311AF2-222 GEN
Solar/Wind Harmer
25.479
970257AG2-171 GEN
Solar/Wind Harmer
8.819
315785AD2-033 C
Solar/Wind Harmer
2.117
964241AG1-285 GEN
Solar/Wind Harmer
14.665
316131AB2-060 GEN
Solar/Wind Harmer
0.615
316478AD1-087 GEN
Solar/Wind Harmer
0.466
316486AD2-202 GEN
Solar/Wind Harmer
0.137
3147043LAWRENC
Solar/Wind Harmer
0.066
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
4.708
971683AH1-343 GEN
Solar/Wind Harmer
3.476
313506AB2-031 GEN
Solar/Wind Harmer
0.227
316283AC2-100 C
Solar/Wind Harmer
0.132
316210AC1-098 GEN
Solar/Wind Harmer
0.531
970917AG2-570 GEN
Solar/Wind Harmer
5.072
316327AA2-057 GEN
Solar/Wind Harmer
0.085
3146776BUCKING
Solar/Wind Helper
0.313
316313AB2-026
Solar/Wind Helper
0.338
316258AE1-075 C
Solar/Wind Helper
0.304
316405AF2-144 C
Solar/Wind Helper
0.253
3148013FISHERV
Solar/Wind Helper
0.123
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
8.584
970401AG2-262 GEN
Solar/Wind Harmer
0.842
957481AF2-042 GEN
Solar/Wind Harmer
34.592
315687AD1-152 GEN
Solar/Wind Harmer
0.004
971065AG2-659 GEN
Solar/Wind Harmer
4.952
316129AC1-054 GEN
Solar/Wind Harmer
0.422
316003AC1-222 GEN
Solar/Wind Harmer
0.003
971795AH1-408 GEN
Solar/Wind Harmer
6.656
960081AF2-299 GEN
Solar/Wind Harmer
0.732
3145783HORNRTN
Solar/Wind Harmer
0.069
316190AA2-174 GEN
Solar/Wind Harmer
0
316212AC1-099_GEN
Solar/Wind Harmer
0.296
970919AG2-571 GEN
Solar/Wind Harmer
2.029
970087AG2-069 GEN
Solar/Wind Harmer
4.556
316322AB2-045
Solar/Wind Helper
0.968
3146776BUCKING
Solar/Wind Helper
0.347
316336AC2-165 C
Solar/Wind Helper
1.445
3151611KERR 4
50/50
0.279
3151621KERR 5
50/50
0.279
3151631KERR 6
50/50
0.279
3151641KERR 7
50/50
0.279
3151541CLOVER2
50/50
2.847
3151281ROARAP4
50/50
0.085
3151281ROARAP4
50/50
0.08
963041AG1-153 GEN
50/50
1.549
970285AG2-188 GEN
Solar/Wind Harmer
51.175
315657AE1-056 GEN
Solar/Wind Harmer
12.95
946301AF1-294 GEN
Solar/Wind Harmer
6.911
961791AG1-021 GEN
Solar/Wind Harmer
3.362
970683AG2-441 GEN
Solar/Wind Harmer
20.935
970681AG2-440 GEN
Solar/Wind Harmer
16.748
3144303KENBRDG
Solar/Wind Harmer
0.22
971443AH1-215 GEN
Solar/Wind Harmer
4.574
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.327
3147173SINAI
Solar/Wind Harmer
0.11
3147243WELCO
Solar/Wind Harmer
0.069
970831AG2-522 GEN
Solar/Wind Harmer
4.619
970865AG2-541 GEN
Solar/Wind Harmer
3.009
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.287
316123AC1-075 GEN
Solar/Wind Harmer
0.097
970165AG2-112 GEN
Solar/Wind Harmer
0.577
970163AG2-111 GEN
Solar/Wind Harmer
0.551
971967AH1-528 GEN
Solar/Wind Harmer
10.885
315607AA1-063A GEN
Solar/Wind Harmer
0.13
3146043SEABORD
Solar/Wind Harmer
0.063
970085AG2-068 GEN
Solar/Wind Harmer
3.037
970581AG2-369 GEN
Solar/Wind Harmer
2.612
270494AE1-108_GEN
Solar/Wind Helper
4.476
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
958211AF2-115 GEN
Solar/Wind Harmer
4.203
963191AG1-168 GEN
Solar/Wind Harmer
1.401
971741AH1-377 GEN
Solar/Wind Harmer
33.06
316034AC1-036 C
Solar/Wind Harmer
0.02
970323AG2-213 GEN
Solar/Wind Harmer
11.759
971775AH1-396 GEN
Solar/Wind Harmer
0.441
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
7.224
939181AE1-148 GEN
Solar/Wind Harmer
6.94
964791AG1-342 GEN
Solar/Wind Harmer
2.755
3146843MT LREL
Solar/Wind Harmer
0.143
3146843MT LREL
Solar/Wind Harmer
0.143
970099AG2-077 GEN
Solar/Wind Harmer
13.837
970933AG2-581 GEN
Solar/Wind Harmer
6.964
316181AB2-040 GEN
Solar/Wind Harmer
0.107
3145593CAROLNA
Solar/Wind Harmer
0.07
3145593CAROLNA
Solar/Wind Harmer
0.07
966811AG1-552 GEN
Solar/Wind Harmer
0.763
3145593CAROLNA
Solar/Wind Harmer
0.088
3145783HORNRTN
Solar/Wind Harmer
1.221
3145783HORNRTN
Solar/Wind Harmer
0.977
3145783HORNRTN
Solar/Wind Harmer
0.305
3145783HORNRTN
Solar/Wind Harmer
0.122
316222AC1-221 GEN
Solar/Wind Harmer
0.284
316426AA2-053 GEN
Solar/Wind Harmer
0.225
942751AE2-291 GEN
Solar/Wind Harmer
3.338
316274AC1-208 GEN
Solar/Wind Harmer
0.311
3146776BUCKING
Solar/Wind Helper
3.475
3146776BUCKING
Solar/Wind Helper
0.282
315821AE2-092 GEN
Solar/Wind Helper
2.978
LAGNLTFEXP_LAGN->PJM
CLTF
1.976
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.656
TVALTFEXP_TVA->PJM
CLTF
0.971
CPLELTFEXP_CPLE->PJM
CLTF
3.789
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.54
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.153
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.217
MECLTFEXP_MEC->PJM
CLTF
0.756
SIGELTFEXP_SIGE->PJM
CLTF
0.021
NYPJM->LTFIMP_NY
CLTF
0.298
LGEELTFEXP_LGEE->PJM
CLTF
0.232
WECLTFEXP_WEC->PJM
CLTF
0.123

Details for AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 511_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:129.2 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5258.72
MW Contribution:25.61
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
11.133
3151051BRUNSWICKS1
50/50
17.499
3151021BRUNSWICKG1
50/50
8.432
3151031BRUNSWICKG2
50/50
8.432
970413AG2-270 GEN
50/50
40.853
3151591KERR 2
50/50
0.537
3144293JTRSVLE
50/50
0.801
970917AG2-570 GEN
Solar/Wind Harmer
53.421
316478AD1-087 GEN
Solar/Wind Harmer
1.525
316486AD2-202 GEN
Solar/Wind Harmer
0.448
970909AG2-566 GEN
Solar/Wind Harmer
3.307
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
13.182
316283AC2-100 C
Solar/Wind Harmer
0.55
971683AH1-343 GEN
Solar/Wind Harmer
10.2
316131AB2-060 GEN
Solar/Wind Harmer
0.796
964241AG1-285 GEN
Solar/Wind Harmer
16.703
315785AD2-033 C
Solar/Wind Harmer
2.003
970257AG2-171 GEN
Solar/Wind Harmer
7.834
959311AF2-222 GEN
Solar/Wind Harmer
21.656
963181AG1-167 GEN
Solar/Wind Harmer
0.948
3147133PAMPLIN
Solar/Wind Harmer
0.736
971193AH1-056 GEN
Solar/Wind Harmer
14.274
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.131
270018AE2-047 C O1
Solar/Wind Harmer
0.003
270197AD1-017 GEN1
Solar/Wind Harmer
0.943
3146776BUCKING
Solar/Wind Harmer
0.049
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3147312GRETNA
Solar/Wind Harmer
0.026
941821AE2-187 GEN
Solar/Wind Harmer
4.212
270336AE1-100 GEN
Solar/Wind Harmer
0.003
3145543BTLEBRO
Solar/Wind Harmer
0.117
3145543BTLEBRO
Solar/Wind Harmer
0.117
971623AH1-311 GEN
Solar/Wind Harmer
0.234
961601AG1-000A GEN
Solar/Wind Harmer
8.141
315773AC2-141 GEN
Solar/Wind Helper
9.054
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.057
3145336SMITFLD
Solar/Wind Helper
0.149
315839AE2-212 C
Solar/Wind Helper
0.495
3146456SLIGO L269
Solar/Wind Helper
0.357
316382AG1-145 C
Solar/Wind Helper
0.471
316320Y1-086
Solar/Wind Helper
0.147
316156AD2-030 GEN
Solar/Wind Helper
0.497
316280AD1-041 GEN
Solar/Wind Helper
1.104
3142946ENON
Solar/Wind Helper
0.108
316484AD2-074 GEN
Solar/Wind Helper
0.613
316404AE1-155 C
Solar/Wind Helper
2.651
316435W1029_GEN3
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3141906WESTMOR
Solar/Wind Helper
0.116
316473AC1-191 GEN
Solar/Wind Helper
1.736
3146626S HERTFORD
Solar/Wind Helper
0.28
3145273HOLLAND
Solar/Wind Helper
0.191
966881AG1-559 GEN
Solar/Wind Helper
0.333
3146376EDENTON
Solar/Wind Helper
0.227
971451AH1-221 GEN
50/50
25.609
3151531CLOVER1
50/50
9.362
3151601KERR 3
50/50
0.537
3151581KERR 1
50/50
0.192
3144293JTRSVLE
50/50
0.801
971629AH1-314 GEN
50/50
17.923
3151561HALLBR1
50/50
0.367
970919AG2-571 GEN
Solar/Wind Harmer
21.368
970087AG2-069 GEN
Solar/Wind Harmer
47.73
957481AF2-042 GEN
Solar/Wind Harmer
126.807
315693AD1-088 GEN
Solar/Wind Harmer
20.818
962491AG1-098 GEN
Solar/Wind Harmer
24.385
315687AD1-152 GEN
Solar/Wind Harmer
0.013
316003AC1-222 GEN
Solar/Wind Harmer
0.008
970401AG2-262 GEN
Solar/Wind Harmer
1.677
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970685AG2-442 GEN
Solar/Wind Harmer
17.979
963171AG1-166 GEN
Solar/Wind Harmer
1.264
971563AH1-280 GEN
Solar/Wind Harmer
2.529
3146926FARMVIL
Solar/Wind Harmer
0.131
971065AG2-659 GEN
Solar/Wind Harmer
8.445
316129AC1-054 GEN
Solar/Wind Harmer
0.698
970223AG2-152 GEN
Solar/Wind Harmer
12.094
270016AE1-250 BESS
Solar/Wind Harmer
0.005
3147123OTTER R
Solar/Wind Harmer
0.088
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.055
3147312GRETNA
Solar/Wind Harmer
0.105
3146802CHATHAM
Solar/Wind Harmer
0.099
941801AE2-185 GEN
Solar/Wind Harmer
4.212
270030AE2-140 GEN
Solar/Wind Harmer
13.804
3145543BTLEBRO
Solar/Wind Harmer
0.117
3145543BTLEBRO
Solar/Wind Harmer
0.094
316359AB2-059 GEN
Solar/Wind Harmer
0.421
316049AB1-081 GEN
Solar/Wind Harmer
0.67
3142053HEARTS
Solar/Wind Harmer
0.206
316294AC1-161 GEN
Solar/Wind Helper
7.693
316375AC2-012 GEN
Solar/Wind Helper
1.008
3145336SMITFLD
Solar/Wind Helper
1.487
316388AE2-253 GEN
Solar/Wind Helper
1.389
3146456SLIGO L269
Solar/Wind Helper
0.357
316381AD1-082 GEN
Solar/Wind Helper
1.848
316072AD1-144
Solar/Wind Helper
0.404
316246AF1-032 C
Solar/Wind Helper
0.401
316159AE1-175 C
Solar/Wind Helper
0.531
316458AB2-190 GEN2
Solar/Wind Helper
1.993
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.303
3138133OCRAN
Solar/Wind Helper
0.195
3142543TWELFTH
Solar/Wind Helper
0.03
964211AG1-282 GEN
Solar/Wind Helper
0.416
3141726DUNNSVL
Solar/Wind Helper
1.235
316337AD2-073 GEN
Solar/Wind Helper
0.453
3142416OLDCHRC
Solar/Wind Helper
0.774
3142416OLDCHRC
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.959
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
3143226MDLTHAN
Solar/Wind Helper
0.286
315800Z1-036_GEN1
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
315244AE2-183_ST
50/50
19.249
963041AG1-153 GEN
50/50
17.073
3151541CLOVER2
50/50
9.317
3151611KERR 4
50/50
0.537
3151621KERR 5
50/50
0.537
3151631KERR 6
50/50
0.537
3151641KERR 7
50/50
0.537
970673AG2-436 GEN
Solar/Wind Harmer
149.315
970673AG2-436 GEN
Solar/Wind Harmer
99.544
971967AH1-528 GEN
Solar/Wind Harmer
95.481
970085AG2-068 GEN
Solar/Wind Harmer
31.82
970581AG2-369 GEN
Solar/Wind Harmer
27.365
3147173SINAI
Solar/Wind Harmer
0.309
3147243WELCO
Solar/Wind Harmer
0.193
316118AC1-105 GEN
Solar/Wind Harmer
0.768
970865AG2-541 GEN
Solar/Wind Harmer
9.078
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
4.118
3144303KENBRDG
Solar/Wind Harmer
0.196
970683AG2-441 GEN
Solar/Wind Harmer
16.053
970681AG2-440 GEN
Solar/Wind Harmer
12.842
946301AF1-294 GEN
Solar/Wind Harmer
4.678
961791AG1-021 GEN
Solar/Wind Harmer
2.276
315657AE1-056 GEN
Solar/Wind Harmer
8.085
316123AC1-075 GEN
Solar/Wind Harmer
0.315
970165AG2-112 GEN
Solar/Wind Harmer
1.87
970163AG2-111 GEN
Solar/Wind Harmer
1.784
970831AG2-522 GEN
Solar/Wind Harmer
7.35
970285AG2-188 GEN
Solar/Wind Harmer
12.402
971845AH1-439 GEN
Solar/Wind Harmer
6.507
270069AE2-166 C O1
Solar/Wind Harmer
0.004
3143316POE
Solar/Wind Helper
1.55
319010AE1-072 C
Solar/Wind Helper
4.057
316369SG1_INVT
Solar/Wind Helper
1.702
316305AF2-043 C
Solar/Wind Helper
0.471
316132AB2-190 GEN1
Solar/Wind Helper
1.993
957831AF2-077 GEN
Solar/Wind Helper
0.468
316349AD2-085 GEN
Solar/Wind Helper
1.559
313526AB2-022
Solar/Wind Helper
0.503
957601AF2-054 GEN
Solar/Wind Helper
0.442
3141873WAN 176
Solar/Wind Helper
0.066
315662AE1-191 GEN
Solar/Wind Helper
1.766
315666AE1-190 GEN
Solar/Wind Helper
0.441
316059AD1-063 C
Solar/Wind Helper
0.329
3141913WHIT STONE
Solar/Wind Helper
0.326
3138133OCRAN
Solar/Wind Helper
0.098
3143873LANEXA
Solar/Wind Helper
0.195
3141783LANCAST
Solar/Wind Helper
0.194
3141783LANCAST
Solar/Wind Helper
0.129
3146486SUNBURY
Solar/Wind Helper
0.322
3146486SUNBURY
Solar/Wind Helper
0.322
316321Z2-027
Solar/Wind Helper
0.485
3145176PASQUOTANK
Solar/Wind Helper
0.197
316315AB2-025 C
Solar/Wind Helper
0.48
3141813NORNECK
Solar/Wind Helper
0.308
316312AB1-027
Solar/Wind Helper
0.567
316233AE1-074 FULL
Solar/Wind Helper
0.447
316223AC1-118
Solar/Wind Helper
0.442
315611Z1-036_GEN2
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
315242AE2-183_GT2
50/50
11.133
315241AE2-183_GT1
50/50
11.065
972185AH1-677 GEN
50/50
40.137
3151041BRUNSWICKG3
50/50
8.432
972187AH1-678 GEN
50/50
19.349
3152661PLYWOOD A
50/50
0.671
970535AG2-341 GEN
50/50
4.566
3144293JTRSVLE
50/50
0.801
3144293JTRSVLE
50/50
0.674
970933AG2-581 GEN
Solar/Wind Harmer
44.982
970099AG2-077 GEN
Solar/Wind Harmer
50.723
971741AH1-377 GEN
Solar/Wind Harmer
33.569
970301AG2-198 GEN
Solar/Wind Harmer
13.228
3146843MT LREL
Solar/Wind Harmer
0.286
3146843MT LREL
Solar/Wind Harmer
0.286
964791AG1-342 GEN
Solar/Wind Harmer
5.488
316222AC1-221 GEN
Solar/Wind Harmer
1.175
962561AG1-105 GEN
Solar/Wind Harmer
13.485
939181AE1-148 GEN
Solar/Wind Harmer
12.41
313527AB2-043 GEN
Solar/Wind Harmer
0.003
970323AG2-213 GEN
Solar/Wind Harmer
10.445
971775AH1-396 GEN
Solar/Wind Harmer
0.392
316034AC1-036 C
Solar/Wind Harmer
0.018
958211AF2-115 GEN
Solar/Wind Harmer
2.845
963191AG1-168 GEN
Solar/Wind Harmer
0.948
3147133PAMPLIN
Solar/Wind Harmer
0.234
3147133PAMPLIN
Solar/Wind Harmer
0.187
942751AE2-291 GEN
Solar/Wind Harmer
11.476
270013AE1-250 PV
Solar/Wind Harmer
0.005
3146776BUCKING
Solar/Wind Harmer
0.546
3146776BUCKING
Solar/Wind Harmer
0.044
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
3.276
316263AC1-034 GEN
Solar/Wind Harmer
4.449
961601AG1-000A GEN
Solar/Wind Harmer
2.035
316036AC1-147 C
Solar/Wind Helper
0.586
3142956BIRDNECK
Solar/Wind Helper
0.257
316316AC1-027 C
Solar/Wind Helper
0.602
316185AD1-033 GEN
Solar/Wind Helper
1.787
3145506HICKORY
Solar/Wind Helper
1.497
3145506HICKORY
Solar/Wind Helper
0.899
3145506HICKORY
Solar/Wind Helper
0.225
316236AE1-162_GEN
Solar/Wind Helper
0.5
316339AD2-160 GEN
Solar/Wind Helper
1.389
316018AA1-139 ULT2
Solar/Wind Helper
1.557
316017AA1-139 ULT1
Solar/Wind Helper
1.655
3137176SLIGO L2192
Solar/Wind Helper
1.424
316033AB2-134 GEN
Solar/Wind Helper
1.217
315697AD1-025 GEN
Solar/Wind Helper
4.045
3130086AYDLETT
Solar/Wind Helper
1.414
316240AF1-291 C
Solar/Wind Helper
0.474
3146386ELIZ CT
Solar/Wind Helper
0.33
3142946ENON
Solar/Wind Helper
0.032
316487AF1-042 GEN
Solar/Wind Helper
0.321
3144356SAPONY
Solar/Wind Helper
0.565
316075AC2-137 C
Solar/Wind Helper
0.475
316077AC2-138 C
Solar/Wind Helper
0.289
316431W1029_GEN1
Solar/Wind Helper
1.222
316433W1029_GEN2
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
966871AG1-558 GEN
Solar/Wind Helper
0.383
3146626S HERTFORD
Solar/Wind Helper
0.28
3146626S HERTFORD
Solar/Wind Helper
0.28
316468AD1-105 GEN
Solar/Wind Helper
1.331
LAGNLTFEXP_LAGN->PJM
CLTF
14.669
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.275
TVALTFEXP_TVA->PJM
CLTF
7.315
CPLELTFEXP_CPLE->PJM
CLTF
19.748
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.24
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.721
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.156
MECLTFEXP_MEC->PJM
CLTF
7.366
SIGELTFEXP_SIGE->PJM
CLTF
0.221
NYPJM->LTFIMP_NY
CLTF
2.382
LGEELTFEXP_LGEE->PJM
CLTF
2.675
WECLTFEXP_WEC->PJM
CLTF
1.4
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113

Details for AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 51192_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 51192_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.25 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5708.12
MW Contribution:25.61
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
8.432
970413AG2-270 GEN
50/50
40.853
3151591KERR 2
50/50
0.537
3144293JTRSVLE
50/50
0.801
970917AG2-570 GEN
Solar/Wind Harmer
168.81
316478AD1-087 GEN
Solar/Wind Harmer
4.25
316486AD2-202 GEN
Solar/Wind Harmer
1.245
970909AG2-566 GEN
Solar/Wind Harmer
3.307
316248AF1-058 C
Solar/Wind Harmer
1.046
960061AF2-297 GEN
Solar/Wind Harmer
17.357
316283AC2-100 C
Solar/Wind Harmer
2.974
971683AH1-343 GEN
Solar/Wind Harmer
13.43
316131AB2-060 GEN
Solar/Wind Harmer
3.068
964241AG1-285 GEN
Solar/Wind Harmer
21.992
315785AD2-033 C
Solar/Wind Harmer
6.274
970257AG2-171 GEN
Solar/Wind Harmer
10.314
315244AE2-183_ST
50/50
19.249
963041AG1-153 GEN
50/50
17.073
3151541CLOVER2
50/50
9.317
3151611KERR 4
50/50
0.537
3151621KERR 5
50/50
0.537
3151631KERR 6
50/50
0.537
3151641KERR 7
50/50
0.537
970673AG2-436 GEN
Solar/Wind Harmer
165.209
970673AG2-436 GEN
Solar/Wind Harmer
83.65
971967AH1-528 GEN
Solar/Wind Harmer
126.052
970085AG2-068 GEN
Solar/Wind Harmer
41.896
970581AG2-369 GEN
Solar/Wind Harmer
36.031
3147173SINAI
Solar/Wind Harmer
-0.035
3147243WELCO
Solar/Wind Harmer
-0.021
316118AC1-105 GEN
Solar/Wind Harmer
2.3
970865AG2-541 GEN
Solar/Wind Harmer
11.953
316239AB2-077_GEN
Solar/Wind Harmer
0.866
316238AB2-078_GEN
Solar/Wind Harmer
0.866
971443AH1-215 GEN
Solar/Wind Harmer
5.422
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
21.136
970681AG2-440 GEN
Solar/Wind Harmer
16.909
946301AF1-294 GEN
Solar/Wind Harmer
6.825
961791AG1-021 GEN
Solar/Wind Harmer
3.329
270455AD2-022 GEN
Solar/Wind Harmer
4.714
270457AD2-023 GEN
Solar/Wind Harmer
2.39
315657AE1-056 GEN
Solar/Wind Harmer
9.877
316123AC1-075 GEN
Solar/Wind Harmer
2.797
970165AG2-112 GEN
Solar/Wind Harmer
2.462
970163AG2-111 GEN
Solar/Wind Harmer
2.349
970831AG2-522 GEN
Solar/Wind Harmer
9.678
970285AG2-188 GEN
Solar/Wind Harmer
15.412
971845AH1-439 GEN
Solar/Wind Harmer
8.567
315243AE2-183_GT3
50/50
11.133
3151051BRUNSWICKS1
50/50
17.499
3151021BRUNSWICKG1
50/50
8.432
971451AH1-221 GEN
50/50
25.609
3151531CLOVER1
50/50
9.362
3151601KERR 3
50/50
0.537
3151581KERR 1
50/50
0.192
3144293JTRSVLE
50/50
0.801
971629AH1-314 GEN
50/50
17.923
3151561HALLBR1
50/50
0.367
970919AG2-571 GEN
Solar/Wind Harmer
21.368
970087AG2-069 GEN
Solar/Wind Harmer
62.844
957481AF2-042 GEN
Solar/Wind Harmer
166.962
315693AD1-088 GEN
Solar/Wind Harmer
24.364
962491AG1-098 GEN
Solar/Wind Harmer
32.107
315687AD1-152 GEN
Solar/Wind Harmer
5.339
316003AC1-222 GEN
Solar/Wind Harmer
3.203
970401AG2-262 GEN
Solar/Wind Harmer
2.096
316237AB2-079_GEN
Solar/Wind Harmer
0.866
970685AG2-442 GEN
Solar/Wind Harmer
23.673
963171AG1-166 GEN
Solar/Wind Harmer
3.329
971563AH1-280 GEN
Solar/Wind Harmer
3.329
3146926FARMVIL
Solar/Wind Harmer
-0.015
971065AG2-659 GEN
Solar/Wind Harmer
11.119
316129AC1-054 GEN
Solar/Wind Harmer
1.828
970223AG2-152 GEN
Solar/Wind Harmer
17.247
270016AE1-250 BESS
Solar/Wind Harmer
2.846
3147123OTTER R
Solar/Wind Harmer
-0.01
270574AD1-017 GEN2
Solar/Wind Harmer
5.591
316322AB2-045
Solar/Wind Harmer
0.516
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.545
270030AE2-140 GEN
Solar/Wind Harmer
19.786
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.774
316049AB1-081 GEN
Solar/Wind Harmer
1.419
3142053HEARTS
Solar/Wind Harmer
0.155
316294AC1-161 GEN
Solar/Wind Helper
7.693
316375AC2-012 GEN
Solar/Wind Helper
1.008
3145336SMITFLD
Solar/Wind Helper
1.487
316388AE2-253 GEN
Solar/Wind Helper
1.389
3146456SLIGO L269
Solar/Wind Helper
0.357
316381AD1-082 GEN
Solar/Wind Helper
1.848
316072AD1-144
Solar/Wind Helper
0.404
316246AF1-032 C
Solar/Wind Helper
0.401
316159AE1-175 C
Solar/Wind Helper
0.531
316458AB2-190 GEN2
Solar/Wind Helper
1.993
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.303
3138133OCRAN
Solar/Wind Helper
0.195
3142543TWELFTH
Solar/Wind Helper
0.03
964211AG1-282 GEN
Solar/Wind Helper
0.416
3141726DUNNSVL
Solar/Wind Helper
1.235
316337AD2-073 GEN
Solar/Wind Helper
0.453
3142416OLDCHRC
Solar/Wind Helper
0.774
3142416OLDCHRC
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.959
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
3143226MDLTHAN
Solar/Wind Helper
0.286
315800Z1-036_GEN1
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
315242AE2-183_GT2
50/50
11.133
315241AE2-183_GT1
50/50
11.065
972185AH1-677 GEN
50/50
40.137
3151041BRUNSWICKG3
50/50
8.432
972187AH1-678 GEN
50/50
19.349
3152661PLYWOOD A
50/50
0.671
970535AG2-341 GEN
50/50
4.566
3144293JTRSVLE
50/50
0.801
3144293JTRSVLE
50/50
0.674
970933AG2-581 GEN
Solar/Wind Harmer
59.226
970099AG2-077 GEN
Solar/Wind Harmer
66.785
971741AH1-377 GEN
Solar/Wind Harmer
44.199
970301AG2-198 GEN
Solar/Wind Harmer
17.416
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.86
316222AC1-221 GEN
Solar/Wind Harmer
3.218
962561AG1-105 GEN
Solar/Wind Harmer
17.755
939181AE1-148 GEN
Solar/Wind Harmer
16.34
313527AB2-043 GEN
Solar/Wind Harmer
4.631
970323AG2-213 GEN
Solar/Wind Harmer
13.752
971775AH1-396 GEN
Solar/Wind Harmer
1.958
316034AC1-036 C
Solar/Wind Harmer
0.51
958211AF2-115 GEN
Solar/Wind Harmer
4.162
963191AG1-168 GEN
Solar/Wind Harmer
2.497
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
15.11
270013AE1-250 PV
Solar/Wind Harmer
2.846
3146776BUCKING
Solar/Wind Harmer
-0.061
3146776BUCKING
Solar/Wind Harmer
-0.005
316217AC1-145 GEN
Solar/Wind Harmer
2.4
316197AC1-042 GEN
Solar/Wind Harmer
1.819
942671AE2-283 GEN
Solar/Wind Harmer
4.898
316263AC1-034 GEN
Solar/Wind Harmer
6.166
961601AG1-000A GEN
Solar/Wind Harmer
5.056
316036AC1-147 C
Solar/Wind Helper
0.586
3142956BIRDNECK
Solar/Wind Helper
0.257
316316AC1-027 C
Solar/Wind Helper
0.602
316185AD1-033 GEN
Solar/Wind Helper
1.787
3145506HICKORY
Solar/Wind Helper
1.497
3145506HICKORY
Solar/Wind Helper
0.899
3145506HICKORY
Solar/Wind Helper
0.225
316236AE1-162_GEN
Solar/Wind Helper
0.5
316339AD2-160 GEN
Solar/Wind Helper
1.389
316018AA1-139 ULT2
Solar/Wind Helper
1.557
316017AA1-139 ULT1
Solar/Wind Helper
1.655
3137176SLIGO L2192
Solar/Wind Helper
1.424
316033AB2-134 GEN
Solar/Wind Helper
1.217
315697AD1-025 GEN
Solar/Wind Helper
4.045
3130086AYDLETT
Solar/Wind Helper
1.414
316240AF1-291 C
Solar/Wind Helper
0.474
3146386ELIZ CT
Solar/Wind Helper
0.33
3142946ENON
Solar/Wind Helper
0.032
316487AF1-042 GEN
Solar/Wind Helper
0.321
3144356SAPONY
Solar/Wind Helper
0.565
316075AC2-137 C
Solar/Wind Helper
0.475
316077AC2-138 C
Solar/Wind Helper
0.289
316431W1029_GEN1
Solar/Wind Helper
1.222
316433W1029_GEN2
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
966871AG1-558 GEN
Solar/Wind Helper
0.383
3146626S HERTFORD
Solar/Wind Helper
0.28
3146626S HERTFORD
Solar/Wind Helper
0.28
316468AD1-105 GEN
Solar/Wind Helper
1.331
270069AE2-166 C O1
Solar/Wind Harmer
2.422
3143316POE
Solar/Wind Helper
1.55
319010AE1-072 C
Solar/Wind Helper
4.057
316369SG1_INVT
Solar/Wind Helper
1.702
316305AF2-043 C
Solar/Wind Helper
0.471
316132AB2-190 GEN1
Solar/Wind Helper
1.993
957831AF2-077 GEN
Solar/Wind Helper
0.468
316349AD2-085 GEN
Solar/Wind Helper
1.559
313526AB2-022
Solar/Wind Helper
0.503
957601AF2-054 GEN
Solar/Wind Helper
0.442
3141873WAN 176
Solar/Wind Helper
0.066
315662AE1-191 GEN
Solar/Wind Helper
1.766
315666AE1-190 GEN
Solar/Wind Helper
0.441
316059AD1-063 C
Solar/Wind Helper
0.329
3141913WHIT STONE
Solar/Wind Helper
0.326
3138133OCRAN
Solar/Wind Helper
0.098
3143873LANEXA
Solar/Wind Helper
0.195
3141783LANCAST
Solar/Wind Helper
0.194
3141783LANCAST
Solar/Wind Helper
0.129
3146486SUNBURY
Solar/Wind Helper
0.322
3146486SUNBURY
Solar/Wind Helper
0.322
316321Z2-027
Solar/Wind Helper
0.485
3145176PASQUOTANK
Solar/Wind Helper
0.197
316315AB2-025 C
Solar/Wind Helper
0.48
3141813NORNECK
Solar/Wind Helper
0.308
316312AB1-027
Solar/Wind Helper
0.567
316233AE1-074 FULL
Solar/Wind Helper
0.447
316223AC1-118
Solar/Wind Helper
0.442
315611Z1-036_GEN2
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
959311AF2-222 GEN
Solar/Wind Harmer
28.571
963181AG1-167 GEN
Solar/Wind Harmer
2.497
3147133PAMPLIN
Solar/Wind Harmer
-0.082
971193AH1-056 GEN
Solar/Wind Harmer
16.462
942461AE2-259 GEN
Solar/Wind Harmer
3.832
3146926FARMVIL
Solar/Wind Harmer
-0.015
270018AE2-047 C O1
Solar/Wind Harmer
1.378
270197AD1-017 GEN1
Solar/Wind Harmer
1.68
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.844
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.545
270336AE1-100 GEN
Solar/Wind Harmer
1.569
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
961601AG1-000A GEN
Solar/Wind Harmer
5.12
315773AC2-141 GEN
Solar/Wind Helper
9.054
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.057
3145336SMITFLD
Solar/Wind Helper
0.149
315839AE2-212 C
Solar/Wind Helper
0.495
3146456SLIGO L269
Solar/Wind Helper
0.357
316382AG1-145 C
Solar/Wind Helper
0.471
316320Y1-086
Solar/Wind Helper
0.147
316156AD2-030 GEN
Solar/Wind Helper
0.497
316280AD1-041 GEN
Solar/Wind Helper
1.104
3142946ENON
Solar/Wind Helper
0.108
316484AD2-074 GEN
Solar/Wind Helper
0.613
316404AE1-155 C
Solar/Wind Helper
2.651
316435W1029_GEN3
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3141906WESTMOR
Solar/Wind Helper
0.116
316473AC1-191 GEN
Solar/Wind Helper
1.736
3146626S HERTFORD
Solar/Wind Helper
0.28
3145273HOLLAND
Solar/Wind Helper
0.191
966881AG1-559 GEN
Solar/Wind Helper
0.333
3146376EDENTON
Solar/Wind Helper
0.227
LAGNLTFEXP_LAGN->PJM
CLTF
14.669
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.275
TVALTFEXP_TVA->PJM
CLTF
7.315
CPLELTFEXP_CPLE->PJM
CLTF
19.748
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.24
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.721
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.156
MECLTFEXP_MEC->PJM
CLTF
7.366
SIGELTFEXP_SIGE->PJM
CLTF
0.221
NYPJM->LTFIMP_NY
CLTF
2.382
LGEELTFEXP_LGEE->PJM
CLTF
2.675
WECLTFEXP_WEC->PJM
CLTF
1.4
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113

Details for AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 51172_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 51172_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.76 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5683.44
MW Contribution:25.43
Bus #Bus NameTypeMW Contribution
315244AE2-183_ST
50/50
19.115
963041AG1-153 GEN
50/50
16.957
3151541CLOVER2
50/50
9.268
3151611KERR 4
50/50
0.538
3151621KERR 5
50/50
0.538
3151631KERR 6
50/50
0.538
3151641KERR 7
50/50
0.538
970673AG2-436 GEN
Solar/Wind Harmer
164.043
970673AG2-436 GEN
Solar/Wind Harmer
83.06
971967AH1-528 GEN
Solar/Wind Harmer
125.223
970085AG2-068 GEN
Solar/Wind Harmer
41.62
970581AG2-369 GEN
Solar/Wind Harmer
35.794
3147173SINAI
Solar/Wind Harmer
-0.034
3147243WELCO
Solar/Wind Harmer
-0.021
316118AC1-105 GEN
Solar/Wind Harmer
2.295
970865AG2-541 GEN
Solar/Wind Harmer
11.917
316239AB2-077_GEN
Solar/Wind Harmer
0.868
316238AB2-078_GEN
Solar/Wind Harmer
0.868
971443AH1-215 GEN
Solar/Wind Harmer
5.428
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
21.145
970681AG2-440 GEN
Solar/Wind Harmer
16.916
946301AF1-294 GEN
Solar/Wind Harmer
6.823
961791AG1-021 GEN
Solar/Wind Harmer
3.328
270455AD2-022 GEN
Solar/Wind Harmer
4.701
270457AD2-023 GEN
Solar/Wind Harmer
2.384
315657AE1-056 GEN
Solar/Wind Harmer
9.869
316123AC1-075 GEN
Solar/Wind Harmer
2.789
970165AG2-112 GEN
Solar/Wind Harmer
2.455
970163AG2-111 GEN
Solar/Wind Harmer
2.342
970831AG2-522 GEN
Solar/Wind Harmer
9.813
970285AG2-188 GEN
Solar/Wind Harmer
15.354
315242AE2-183_GT2
50/50
11.056
315241AE2-183_GT1
50/50
10.988
972185AH1-677 GEN
50/50
39.858
3151041BRUNSWICKG3
50/50
8.374
972187AH1-678 GEN
50/50
19.217
3152661PLYWOOD A
50/50
0.67
970535AG2-341 GEN
50/50
4.577
3144293JTRSVLE
50/50
0.8
3144293JTRSVLE
50/50
0.674
970933AG2-581 GEN
Solar/Wind Harmer
58.849
970099AG2-077 GEN
Solar/Wind Harmer
66.404
971741AH1-377 GEN
Solar/Wind Harmer
43.978
970301AG2-198 GEN
Solar/Wind Harmer
17.332
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.854
316222AC1-221 GEN
Solar/Wind Harmer
3.208
962561AG1-105 GEN
Solar/Wind Harmer
17.747
939181AE1-148 GEN
Solar/Wind Harmer
16.378
313527AB2-043 GEN
Solar/Wind Harmer
4.643
970323AG2-213 GEN
Solar/Wind Harmer
13.768
971775AH1-396 GEN
Solar/Wind Harmer
1.961
316034AC1-036 C
Solar/Wind Harmer
0.511
958211AF2-115 GEN
Solar/Wind Harmer
4.16
963191AG1-168 GEN
Solar/Wind Harmer
2.496
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
15.066
270013AE1-250 PV
Solar/Wind Harmer
2.839
3146776BUCKING
Solar/Wind Harmer
-0.061
3146776BUCKING
Solar/Wind Harmer
-0.005
316217AC1-145 GEN
Solar/Wind Harmer
2.394
316197AC1-042 GEN
Solar/Wind Harmer
1.815
942671AE2-283 GEN
Solar/Wind Harmer
4.885
316263AC1-034 GEN
Solar/Wind Harmer
6.316
961601AG1-000A GEN
Solar/Wind Harmer
5.186
316036AC1-147 C
Solar/Wind Helper
0.59
3142956BIRDNECK
Solar/Wind Helper
0.259
316316AC1-027 C
Solar/Wind Helper
0.606
316185AD1-033 GEN
Solar/Wind Helper
1.799
3145506HICKORY
Solar/Wind Helper
1.507
3145506HICKORY
Solar/Wind Helper
0.904
3145506HICKORY
Solar/Wind Helper
0.226
316236AE1-162_GEN
Solar/Wind Helper
0.498
316339AD2-160 GEN
Solar/Wind Helper
1.397
316018AA1-139 ULT2
Solar/Wind Helper
1.567
316017AA1-139 ULT1
Solar/Wind Helper
1.665
3137176SLIGO L2192
Solar/Wind Helper
1.432
3130086AYDLETT
Solar/Wind Helper
1.421
316033AB2-134 GEN
Solar/Wind Helper
1.19
315697AD1-025 GEN
Solar/Wind Helper
3.953
3146386ELIZ CT
Solar/Wind Helper
0.331
316240AF1-291 C
Solar/Wind Helper
0.444
3142946ENON
Solar/Wind Helper
0.032
316487AF1-042 GEN
Solar/Wind Helper
0.318
316075AC2-137 C
Solar/Wind Helper
0.467
316077AC2-138 C
Solar/Wind Helper
0.286
316431W1029_GEN1
Solar/Wind Helper
1.225
316433W1029_GEN2
Solar/Wind Helper
1.225
3146516WINFALL
Solar/Wind Helper
0.297
3146516WINFALL
Solar/Wind Helper
0.297
3146516WINFALL
Solar/Wind Helper
0.297
3143526WINTERP
Solar/Wind Helper
1.499
3146626S HERTFORD
Solar/Wind Helper
0.28
3146626S HERTFORD
Solar/Wind Helper
0.28
966871AG1-558 GEN
Solar/Wind Helper
0.374
3144356SAPONY
Solar/Wind Helper
0.492
316468AD1-105 GEN
Solar/Wind Helper
1.305
971845AH1-439 GEN
Solar/Wind Harmer
8.535
270069AE2-166 C O1
Solar/Wind Harmer
2.415
319010AE1-072 C
Solar/Wind Helper
4.079
3143316POE
Solar/Wind Helper
1.407
316305AF2-043 C
Solar/Wind Helper
0.473
316369SG1_INVT
Solar/Wind Helper
1.664
957831AF2-077 GEN
Solar/Wind Helper
0.466
316132AB2-190 GEN1
Solar/Wind Helper
1.933
316349AD2-085 GEN
Solar/Wind Helper
1.523
313526AB2-022
Solar/Wind Helper
0.505
957601AF2-054 GEN
Solar/Wind Helper
0.438
3141873WAN 176
Solar/Wind Helper
0.065
315662AE1-191 GEN
Solar/Wind Helper
1.747
315666AE1-190 GEN
Solar/Wind Helper
0.437
316059AD1-063 C
Solar/Wind Helper
0.326
3141913WHIT STONE
Solar/Wind Helper
0.323
3146486SUNBURY
Solar/Wind Helper
0.323
3146486SUNBURY
Solar/Wind Helper
0.323
3138133OCRAN
Solar/Wind Helper
0.097
3143873LANEXA
Solar/Wind Helper
0.192
3141783LANCAST
Solar/Wind Helper
0.192
3141783LANCAST
Solar/Wind Helper
0.128
316321Z2-027
Solar/Wind Helper
0.487
3145176PASQUOTANK
Solar/Wind Helper
0.198
3141813NORNECK
Solar/Wind Helper
0.304
316312AB1-027
Solar/Wind Helper
0.556
316233AE1-074 FULL
Solar/Wind Helper
0.44
316223AC1-118
Solar/Wind Helper
0.438
316315AB2-025 C
Solar/Wind Helper
0.418
315611Z1-036_GEN2
Solar/Wind Helper
1.411
3130156CHOWAN
Solar/Wind Helper
0.226
3130156CHOWAN
Solar/Wind Helper
0.226
3151031BRUNSWICKG2
50/50
8.374
970413AG2-270 GEN
50/50
40.637
3151591KERR 2
50/50
0.538
3144293JTRSVLE
50/50
0.8
970917AG2-570 GEN
Solar/Wind Harmer
167.695
316478AD1-087 GEN
Solar/Wind Harmer
4.227
316486AD2-202 GEN
Solar/Wind Harmer
1.238
970909AG2-566 GEN
Solar/Wind Harmer
3.291
316248AF1-058 C
Solar/Wind Harmer
1.043
960061AF2-297 GEN
Solar/Wind Harmer
17.305
316283AC2-100 C
Solar/Wind Harmer
2.965
971683AH1-343 GEN
Solar/Wind Harmer
13.39
316131AB2-060 GEN
Solar/Wind Harmer
3.076
964241AG1-285 GEN
Solar/Wind Harmer
22.038
315785AD2-033 C
Solar/Wind Harmer
6.282
970257AG2-171 GEN
Solar/Wind Harmer
10.326
959311AF2-222 GEN
Solar/Wind Harmer
28.597
963181AG1-167 GEN
Solar/Wind Harmer
2.496
3147133PAMPLIN
Solar/Wind Harmer
-0.082
971193AH1-056 GEN
Solar/Wind Harmer
16.449
942461AE2-259 GEN
Solar/Wind Harmer
3.824
3146926FARMVIL
Solar/Wind Harmer
-0.015
270018AE2-047 C O1
Solar/Wind Harmer
1.375
270197AD1-017 GEN1
Solar/Wind Harmer
1.676
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.834
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.53
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
270336AE1-100 GEN
Solar/Wind Harmer
1.564
961601AG1-000A GEN
Solar/Wind Harmer
5.252
315773AC2-141 GEN
Solar/Wind Helper
9.163
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.058
3145336SMITFLD
Solar/Wind Helper
0.148
3146456SLIGO L269
Solar/Wind Helper
0.359
316382AG1-145 C
Solar/Wind Helper
0.469
315839AE2-212 C
Solar/Wind Helper
0.457
316320Y1-086
Solar/Wind Helper
0.148
316156AD2-030 GEN
Solar/Wind Helper
0.492
316280AD1-041 GEN
Solar/Wind Helper
1.092
3142946ENON
Solar/Wind Helper
0.105
316484AD2-074 GEN
Solar/Wind Helper
0.607
316404AE1-155 C
Solar/Wind Helper
2.624
316435W1029_GEN3
Solar/Wind Helper
1.225
3146516WINFALL
Solar/Wind Helper
0.297
3141906WESTMOR
Solar/Wind Helper
0.115
3146626S HERTFORD
Solar/Wind Helper
0.28
316473AC1-191 GEN
Solar/Wind Helper
1.696
3145273HOLLAND
Solar/Wind Helper
0.188
966881AG1-559 GEN
Solar/Wind Helper
0.329
3146376EDENTON
Solar/Wind Helper
0.226
315243AE2-183_GT3
50/50
11.056
3151051BRUNSWICKS1
50/50
17.38
3151021BRUNSWICKG1
50/50
8.374
971451AH1-221 GEN
50/50
25.435
3151531CLOVER1
50/50
9.312
3151601KERR 3
50/50
0.538
3151581KERR 1
50/50
0.192
3144293JTRSVLE
50/50
0.8
971629AH1-314 GEN
50/50
17.875
3151561HALLBR1
50/50
0.366
970919AG2-571 GEN
Solar/Wind Harmer
21.227
970087AG2-069 GEN
Solar/Wind Harmer
62.431
957481AF2-042 GEN
Solar/Wind Harmer
166.01
315693AD1-088 GEN
Solar/Wind Harmer
24.233
962491AG1-098 GEN
Solar/Wind Harmer
31.935
315687AD1-152 GEN
Solar/Wind Harmer
5.313
316003AC1-222 GEN
Solar/Wind Harmer
3.193
970401AG2-262 GEN
Solar/Wind Harmer
2.094
316237AB2-079_GEN
Solar/Wind Harmer
0.868
970685AG2-442 GEN
Solar/Wind Harmer
23.682
963171AG1-166 GEN
Solar/Wind Harmer
3.328
971563AH1-280 GEN
Solar/Wind Harmer
3.328
3146926FARMVIL
Solar/Wind Harmer
-0.015
971065AG2-659 GEN
Solar/Wind Harmer
11.224
316129AC1-054 GEN
Solar/Wind Harmer
1.849
970223AG2-152 GEN
Solar/Wind Harmer
17.201
270016AE1-250 BESS
Solar/Wind Harmer
2.839
3147123OTTER R
Solar/Wind Harmer
-0.01
270574AD1-017 GEN2
Solar/Wind Harmer
5.577
316322AB2-045
Solar/Wind Harmer
0.514
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.53
270030AE2-140 GEN
Solar/Wind Harmer
19.734
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.817
316049AB1-081 GEN
Solar/Wind Harmer
1.454
3142053HEARTS
Solar/Wind Harmer
0.158
316294AC1-161 GEN
Solar/Wind Helper
7.785
316375AC2-012 GEN
Solar/Wind Helper
1.014
3145336SMITFLD
Solar/Wind Helper
1.482
316388AE2-253 GEN
Solar/Wind Helper
1.397
3146456SLIGO L269
Solar/Wind Helper
0.359
316072AD1-144
Solar/Wind Helper
0.404
316246AF1-032 C
Solar/Wind Helper
0.402
316159AE1-175 C
Solar/Wind Helper
0.529
316381AD1-082 GEN
Solar/Wind Helper
1.758
316458AB2-190 GEN2
Solar/Wind Helper
1.933
3141766HARMONY
Solar/Wind Helper
0.065
3138133OCRAN
Solar/Wind Helper
0.193
3142433PROV 92
Solar/Wind Helper
1.275
3142543TWELFTH
Solar/Wind Helper
0.029
964211AG1-282 GEN
Solar/Wind Helper
0.412
3141726DUNNSVL
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.961
3146516WINFALL
Solar/Wind Helper
0.297
316337AD2-073 GEN
Solar/Wind Helper
0.448
3142416OLDCHRC
Solar/Wind Helper
0.759
3142416OLDCHRC
Solar/Wind Helper
0.291
3143526WINTERP
Solar/Wind Helper
1.499
3143226MDLTHAN
Solar/Wind Helper
0.284
315800Z1-036_GEN1
Solar/Wind Helper
1.411
3130156CHOWAN
Solar/Wind Helper
0.226
LAGNLTFEXP_LAGN->PJM
CLTF
14.626
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.161
TVALTFEXP_TVA->PJM
CLTF
7.294
CPLELTFEXP_CPLE->PJM
CLTF
19.708
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.004
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.554
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.081
MECLTFEXP_MEC->PJM
CLTF
7.343
SIGELTFEXP_SIGE->PJM
CLTF
0.22
NYPJM->LTFIMP_NY
CLTF
2.38
LGEELTFEXP_LGEE->PJM
CLTF
2.666
WECLTFEXP_WEC->PJM
CLTF
1.395
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113

Details for AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 511T544_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T544_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.13 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5601.8
MW Contribution:25.22
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
10.962
3151051BRUNSWICKS1
50/50
17.232
3151021BRUNSWICKG1
50/50
8.303
971451AH1-221 GEN
50/50
25.218
3151531CLOVER1
50/50
9.227
3151601KERR 3
50/50
0.532
3151581KERR 1
50/50
0.19
3144293JTRSVLE
50/50
0.79
971629AH1-314 GEN
50/50
17.731
3151561HALLBR1
50/50
0.363
970919AG2-571 GEN
Solar/Wind Harmer
21.047
970087AG2-069 GEN
Solar/Wind Harmer
61.902
957481AF2-042 GEN
Solar/Wind Harmer
164.509
315693AD1-088 GEN
Solar/Wind Harmer
24.007
962491AG1-098 GEN
Solar/Wind Harmer
31.634
315687AD1-152 GEN
Solar/Wind Harmer
5.265
316003AC1-222 GEN
Solar/Wind Harmer
3.162
970401AG2-262 GEN
Solar/Wind Harmer
2.07
316237AB2-079_GEN
Solar/Wind Harmer
0.856
970685AG2-442 GEN
Solar/Wind Harmer
23.354
963171AG1-166 GEN
Solar/Wind Harmer
3.283
971563AH1-280 GEN
Solar/Wind Harmer
3.283
3146926FARMVIL
Solar/Wind Harmer
-0.014
971065AG2-659 GEN
Solar/Wind Harmer
11.094
316129AC1-054 GEN
Solar/Wind Harmer
1.827
970223AG2-152 GEN
Solar/Wind Harmer
17.059
270016AE1-250 BESS
Solar/Wind Harmer
2.815
3147123OTTER R
Solar/Wind Harmer
-0.01
270574AD1-017 GEN2
Solar/Wind Harmer
5.528
316322AB2-045
Solar/Wind Harmer
0.506
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.477
270030AE2-140 GEN
Solar/Wind Harmer
19.567
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.809
316049AB1-081 GEN
Solar/Wind Harmer
1.448
3142053HEARTS
Solar/Wind Harmer
0.158
316294AC1-161 GEN
Solar/Wind Helper
7.244
316381AD1-082 GEN
Solar/Wind Helper
1.747
316375AC2-012 GEN
Solar/Wind Helper
0.879
3145336SMITFLD
Solar/Wind Helper
1.331
316458AB2-190 GEN2
Solar/Wind Helper
1.893
316159AE1-175 C
Solar/Wind Helper
0.497
316388AE2-253 GEN
Solar/Wind Helper
1.201
3142433PROV 92
Solar/Wind Helper
1.254
3142543TWELFTH
Solar/Wind Helper
0.03
3141766HARMONY
Solar/Wind Helper
0.062
3146456SLIGO L269
Solar/Wind Helper
0.308
3138133OCRAN
Solar/Wind Helper
0.185
316072AD1-144
Solar/Wind Helper
0.35
316246AF1-032 C
Solar/Wind Helper
0.342
964211AG1-282 GEN
Solar/Wind Helper
0.397
3141726DUNNSVL
Solar/Wind Helper
1.179
3143526WINTERP
Solar/Wind Helper
1.519
3142416OLDCHRC
Solar/Wind Helper
0.752
3143226MDLTHAN
Solar/Wind Helper
0.289
3142416OLDCHRC
Solar/Wind Helper
0.288
316337AD2-073 GEN
Solar/Wind Helper
0.434
3146516WINFALL
Solar/Wind Helper
0.813
3151031BRUNSWICKG2
50/50
8.303
970413AG2-270 GEN
50/50
40.265
3151591KERR 2
50/50
0.532
3144293JTRSVLE
50/50
0.79
970917AG2-570 GEN
Solar/Wind Harmer
166.275
316478AD1-087 GEN
Solar/Wind Harmer
4.189
316486AD2-202 GEN
Solar/Wind Harmer
1.227
970909AG2-566 GEN
Solar/Wind Harmer
3.255
316248AF1-058 C
Solar/Wind Harmer
1.033
960061AF2-297 GEN
Solar/Wind Harmer
17.135
316283AC2-100 C
Solar/Wind Harmer
2.94
971683AH1-343 GEN
Solar/Wind Harmer
13.259
316131AB2-060 GEN
Solar/Wind Harmer
3.032
964241AG1-285 GEN
Solar/Wind Harmer
21.724
315785AD2-033 C
Solar/Wind Harmer
6.194
970257AG2-171 GEN
Solar/Wind Harmer
10.181
959311AF2-222 GEN
Solar/Wind Harmer
28.197
963181AG1-167 GEN
Solar/Wind Harmer
2.462
3147133PAMPLIN
Solar/Wind Harmer
-0.081
971193AH1-056 GEN
Solar/Wind Harmer
16.225
942461AE2-259 GEN
Solar/Wind Harmer
3.773
3146926FARMVIL
Solar/Wind Harmer
-0.014
270018AE2-047 C O1
Solar/Wind Harmer
1.363
270197AD1-017 GEN1
Solar/Wind Harmer
1.661
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.802
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.477
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
270336AE1-100 GEN
Solar/Wind Harmer
1.551
961601AG1-000A GEN
Solar/Wind Harmer
5.225
315773AC2-141 GEN
Solar/Wind Helper
8.525
315839AE2-212 C
Solar/Wind Helper
0.497
3144536CHRHLND
Solar/Wind Helper
0.05
3144873MCLAUGH
Solar/Wind Helper
0.008
3145336SMITFLD
Solar/Wind Helper
0.133
315242AE2-183_GT2
50/50
10.962
315241AE2-183_GT1
50/50
10.894
972185AH1-677 GEN
50/50
39.518
3151041BRUNSWICKG3
50/50
8.303
972187AH1-678 GEN
50/50
19.053
3152661PLYWOOD A
50/50
0.663
970535AG2-341 GEN
50/50
4.519
3144293JTRSVLE
50/50
0.79
3144293JTRSVLE
50/50
0.665
970933AG2-581 GEN
Solar/Wind Harmer
58.334
970099AG2-077 GEN
Solar/Wind Harmer
65.804
971741AH1-377 GEN
Solar/Wind Harmer
43.523
970301AG2-198 GEN
Solar/Wind Harmer
17.145
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.775
316222AC1-221 GEN
Solar/Wind Harmer
3.182
962561AG1-105 GEN
Solar/Wind Harmer
17.536
939181AE1-148 GEN
Solar/Wind Harmer
16.186
313527AB2-043 GEN
Solar/Wind Harmer
4.576
970323AG2-213 GEN
Solar/Wind Harmer
13.574
971775AH1-396 GEN
Solar/Wind Harmer
1.933
316034AC1-036 C
Solar/Wind Harmer
0.503
958211AF2-115 GEN
Solar/Wind Harmer
4.103
963191AG1-168 GEN
Solar/Wind Harmer
2.462
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
14.918
270013AE1-250 PV
Solar/Wind Harmer
2.815
3146776BUCKING
Solar/Wind Harmer
-0.06
3146776BUCKING
Solar/Wind Harmer
-0.005
316217AC1-145 GEN
Solar/Wind Harmer
2.37
316197AC1-042 GEN
Solar/Wind Harmer
1.797
942671AE2-283 GEN
Solar/Wind Harmer
4.838
316263AC1-034 GEN
Solar/Wind Harmer
6.29
961601AG1-000A GEN
Solar/Wind Harmer
5.16
316240AF1-291 C
Solar/Wind Helper
0.471
316036AC1-147 C
Solar/Wind Helper
0.511
316236AE1-162_GEN
Solar/Wind Helper
0.447
316316AC1-027 C
Solar/Wind Helper
0.524
3142956BIRDNECK
Solar/Wind Helper
0.223
316033AB2-134 GEN
Solar/Wind Helper
1.137
315697AD1-025 GEN
Solar/Wind Helper
3.779
316185AD1-033 GEN
Solar/Wind Helper
1.551
3145506HICKORY
Solar/Wind Helper
1.298
3145506HICKORY
Solar/Wind Helper
0.779
3145506HICKORY
Solar/Wind Helper
0.195
3144356SAPONY
Solar/Wind Helper
0.581
316339AD2-160 GEN
Solar/Wind Helper
1.201
316018AA1-139 ULT2
Solar/Wind Helper
1.346
316017AA1-139 ULT1
Solar/Wind Helper
1.43
3142946ENON
Solar/Wind Helper
0.031
3137176SLIGO L2192
Solar/Wind Helper
1.229
3130086AYDLETT
Solar/Wind Helper
1.219
316487AF1-042 GEN
Solar/Wind Helper
0.305
316075AC2-137 C
Solar/Wind Helper
0.459
316077AC2-138 C
Solar/Wind Helper
0.276
3143526WINTERP
Solar/Wind Helper
1.519
3146386ELIZ CT
Solar/Wind Helper
0.283
966871AG1-558 GEN
Solar/Wind Helper
0.376
316468AD1-105 GEN
Solar/Wind Helper
1.308
316431W1029_GEN1
Solar/Wind Helper
1.037
316433W1029_GEN2
Solar/Wind Helper
1.037
3146516WINFALL
Solar/Wind Helper
0.251
3146516WINFALL
Solar/Wind Helper
0.251
3146516WINFALL
Solar/Wind Helper
0.251
3146626S HERTFORD
Solar/Wind Helper
0.236
3146626S HERTFORD
Solar/Wind Helper
0.236
316382AG1-145 C
Solar/Wind Helper
0.441
316156AD2-030 GEN
Solar/Wind Helper
0.47
3142946ENON
Solar/Wind Helper
0.104
316280AD1-041 GEN
Solar/Wind Helper
1.046
3146456SLIGO L269
Solar/Wind Helper
0.308
316484AD2-074 GEN
Solar/Wind Helper
0.583
316404AE1-155 C
Solar/Wind Helper
2.523
316320Y1-086
Solar/Wind Helper
0.126
316473AC1-191 GEN
Solar/Wind Helper
1.704
3141906WESTMOR
Solar/Wind Helper
0.111
316435W1029_GEN3
Solar/Wind Helper
1.037
3146516WINFALL
Solar/Wind Helper
0.251
966881AG1-559 GEN
Solar/Wind Helper
0.328
3146626S HERTFORD
Solar/Wind Helper
0.236
315244AE2-183_ST
50/50
18.952
963041AG1-153 GEN
50/50
16.812
3151541CLOVER2
50/50
9.183
3151611KERR 4
50/50
0.532
3151621KERR 5
50/50
0.532
3151631KERR 6
50/50
0.532
3151641KERR 7
50/50
0.532
970673AG2-436 GEN
Solar/Wind Harmer
162.646
970673AG2-436 GEN
Solar/Wind Harmer
82.352
971967AH1-528 GEN
Solar/Wind Harmer
124.141
970085AG2-068 GEN
Solar/Wind Harmer
41.268
970581AG2-369 GEN
Solar/Wind Harmer
35.491
3147173SINAI
Solar/Wind Harmer
-0.034
3147243WELCO
Solar/Wind Harmer
-0.021
316118AC1-105 GEN
Solar/Wind Harmer
2.271
970865AG2-541 GEN
Solar/Wind Harmer
11.801
316239AB2-077_GEN
Solar/Wind Harmer
0.856
316238AB2-078_GEN
Solar/Wind Harmer
0.856
971443AH1-215 GEN
Solar/Wind Harmer
5.352
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
20.851
970681AG2-440 GEN
Solar/Wind Harmer
16.681
946301AF1-294 GEN
Solar/Wind Harmer
6.73
961791AG1-021 GEN
Solar/Wind Harmer
3.283
270455AD2-022 GEN
Solar/Wind Harmer
4.664
270457AD2-023 GEN
Solar/Wind Harmer
2.365
315657AE1-056 GEN
Solar/Wind Harmer
9.735
316123AC1-075 GEN
Solar/Wind Harmer
2.761
970165AG2-112 GEN
Solar/Wind Harmer
2.431
970163AG2-111 GEN
Solar/Wind Harmer
2.319
970831AG2-522 GEN
Solar/Wind Harmer
9.696
970285AG2-188 GEN
Solar/Wind Harmer
15.118
971845AH1-439 GEN
Solar/Wind Harmer
8.397
270069AE2-166 C O1
Solar/Wind Harmer
2.394
3143316POE
Solar/Wind Helper
1.57
316132AB2-190 GEN1
Solar/Wind Helper
1.893
316369SG1_INVT
Solar/Wind Helper
1.59
957831AF2-077 GEN
Solar/Wind Helper
0.437
316315AB2-025 C
Solar/Wind Helper
0.494
957601AF2-054 GEN
Solar/Wind Helper
0.418
3141873WAN 176
Solar/Wind Helper
0.062
315662AE1-191 GEN
Solar/Wind Helper
1.674
315666AE1-190 GEN
Solar/Wind Helper
0.419
3143873LANEXA
Solar/Wind Helper
0.186
316059AD1-063 C
Solar/Wind Helper
0.312
3141913WHIT STONE
Solar/Wind Helper
0.309
3138133OCRAN
Solar/Wind Helper
0.093
3141783LANCAST
Solar/Wind Helper
0.184
3141783LANCAST
Solar/Wind Helper
0.123
319010AE1-072 C
Solar/Wind Helper
3.5
316349AD2-085 GEN
Solar/Wind Helper
1.396
316305AF2-043 C
Solar/Wind Helper
0.402
3141813NORNECK
Solar/Wind Helper
0.293
316233AE1-074 FULL
Solar/Wind Helper
0.446
316312AB1-027
Solar/Wind Helper
0.55
313526AB2-022
Solar/Wind Helper
0.431
316223AC1-118
Solar/Wind Helper
0.424
3146486SUNBURY
Solar/Wind Helper
0.274
3146486SUNBURY
Solar/Wind Helper
0.274
316321Z2-027
Solar/Wind Helper
0.414
3145176PASQUOTANK
Solar/Wind Helper
0.168
3146516WINFALL
Solar/Wind Helper
0.251
LAGNLTFEXP_LAGN->PJM
CLTF
14.499
CBM South 2LTFEXP_CBM-S2->PJM
CBM
43.842
TVALTFEXP_TVA->PJM
CLTF
7.231
CPLELTFEXP_CPLE->PJM
CLTF
19.58
CBM West 2LTFEXP_CBM-W2->PJM
CBM
77.279
CBM West 1LTFEXP_CBM-W1->PJM
CBM
48.979
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.858
MECLTFEXP_MEC->PJM
CLTF
7.267
SIGELTFEXP_SIGE->PJM
CLTF
0.218
NYPJM->LTFIMP_NY
CLTF
2.38
LGEELTFEXP_LGEE->PJM
CLTF
2.637
WECLTFEXP_WEC->PJM
CLTF
1.38
AG2-052LTFEXP_AG2-052->PJM
LTF
0.074
AH1-155LTFEXP_AH1-155->PJM
LTF
0.111

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:181.65 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:1015.96
MW Contribution:3.37
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
3.284
3151611KERR 4
50/50
0.315
3151621KERR 5
50/50
0.315
3151631KERR 6
50/50
0.315
3151641KERR 7
50/50
0.315
3151281ROARAP4
50/50
0.107
3151281ROARAP4
50/50
0.1
963041AG1-153 GEN
50/50
2.246
315244AE2-183_ST
50/50
2.348
971845AH1-439 GEN
Solar/Wind Harmer
30.743
970285AG2-188 GEN
Solar/Wind Harmer
51.681
315657AE1-056 GEN
Solar/Wind Harmer
13.387
946301AF1-294 GEN
Solar/Wind Harmer
7.171
961791AG1-021 GEN
Solar/Wind Harmer
3.489
970683AG2-441 GEN
Solar/Wind Harmer
21.861
970681AG2-440 GEN
Solar/Wind Harmer
17.489
3144303KENBRDG
Solar/Wind Harmer
0.232
971443AH1-215 GEN
Solar/Wind Harmer
4.821
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.369
3147173SINAI
Solar/Wind Harmer
0.127
3147243WELCO
Solar/Wind Harmer
0.079
970831AG2-522 GEN
Solar/Wind Harmer
5.372
970865AG2-541 GEN
Solar/Wind Harmer
3.489
971967AH1-528 GEN
Solar/Wind Harmer
15.071
316087AB2-174 GEN
Solar/Wind Harmer
0.003
3137643SOCKMAN
Solar/Wind Harmer
0.359
316123AC1-075 GEN
Solar/Wind Harmer
0.114
970165AG2-112 GEN
Solar/Wind Harmer
0.676
970163AG2-111 GEN
Solar/Wind Harmer
0.645
315607AA1-063A GEN
Solar/Wind Harmer
0.167
970085AG2-068 GEN
Solar/Wind Harmer
4.361
970581AG2-369 GEN
Solar/Wind Harmer
3.75
3146043SEABORD
Solar/Wind Harmer
0.081
970673AG2-436 GEN
Solar/Wind Harmer
17.208
970673AG2-436 GEN
Solar/Wind Harmer
11.472
941031AE2-094 GEN
Solar/Wind Harmer
14.299
944011AF1-069 GEN
Solar/Wind Harmer
4.672
315652AC1-086 GEN
Solar/Wind Harmer
8.029
3146033SCOT NK
Solar/Wind Harmer
0.291
3145796HORNRTN
Solar/Wind Harmer
0.232
3145796HORNRTN
Solar/Wind Harmer
0.029
965291AG1-394 GEN
Solar/Wind Harmer
0.32
316319Z2-044 C
Solar/Wind Harmer
0
3145893MURPHYS
Solar/Wind Harmer
0.191
3145893MURPHYS
Solar/Wind Harmer
0.071
3145513AHOSKIE
Solar/Wind Harmer
0.144
3145513AHOSKIE
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.136
3145683EARLEYS
Solar/Wind Harmer
0.068
3145683EARLEYS
Solar/Wind Harmer
0.068
3145573BETHELC
Solar/Wind Harmer
0.067
3145573BETHELC
Solar/Wind Harmer
0.067
316420AA1-050 GEN
Solar/Wind Harmer
0.002
957861AF2-080 GEN
Solar/Wind Harmer
2.854
316005AA1-067
Solar/Wind Harmer
0.069
3145746EVERETS
Solar/Wind Harmer
0.257
3144293JTRSVLE
50/50
1.227
970413AG2-270 GEN
50/50
14.4
3151591KERR 2
50/50
0.315
3151261ROARAP2
50/50
0.107
3151031BRUNSWICKG2
50/50
1.109
3151391GASTONA
50/50
0.198
3151411GASTONB
50/50
0.198
3146926FARMVIL
Solar/Wind Harmer
0.322
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
4.196
3147133PAMPLIN
Solar/Wind Harmer
1.218
971193AH1-056 GEN
Solar/Wind Harmer
23.635
963181AG1-167 GEN
Solar/Wind Harmer
1.454
959311AF2-222 GEN
Solar/Wind Harmer
26.76
970257AG2-171 GEN
Solar/Wind Harmer
9.287
315785AD2-033 C
Solar/Wind Harmer
2.238
964241AG1-285 GEN
Solar/Wind Harmer
15.712
316131AB2-060 GEN
Solar/Wind Harmer
0.665
316478AD1-087 GEN
Solar/Wind Harmer
0.537
316486AD2-202 GEN
Solar/Wind Harmer
0.158
3147043LAWRENC
Solar/Wind Harmer
0.077
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
5.403
971683AH1-343 GEN
Solar/Wind Harmer
4.014
313506AB2-031 GEN
Solar/Wind Harmer
0.283
316283AC2-100 C
Solar/Wind Harmer
0.162
970917AG2-570 GEN
Solar/Wind Harmer
7.29
316210AC1-098 GEN
Solar/Wind Harmer
0.693
316327AA2-057 GEN
Solar/Wind Harmer
0.111
3146263WOODLND
Solar/Wind Harmer
0.074
316365GEN2_N
Solar/Wind Harmer
0.164
3142666NORTHAMPTON
Solar/Wind Harmer
0.072
3145796HORNRTN
Solar/Wind Harmer
0.29
3145796HORNRTN
Solar/Wind Harmer
0.072
3146233WITAKRS
Solar/Wind Harmer
0.361
3146233WITAKRS
Solar/Wind Harmer
0.049
3138543CONSLDL
Solar/Wind Harmer
0.047
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3145893MURPHYS
Solar/Wind Harmer
0.118
3145893MURPHYS
Solar/Wind Harmer
0.071
315724AD1-057 GEN
Solar/Wind Harmer
0.265
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.07
957521AF2-046 GEN
Solar/Wind Harmer
5.233
961681AG1-008 GEN
Solar/Wind Harmer
5.233
3145543BTLEBRO
Solar/Wind Harmer
0.07
3145543BTLEBRO
Solar/Wind Harmer
0.07
971623AH1-311 GEN
Solar/Wind Harmer
0.14
3146173TUNIS
Solar/Wind Harmer
0.069
961601AG1-000A GEN
Solar/Wind Harmer
4.909
316463AE2-346 GEN
Solar/Wind Harmer
0.059
316140AB2-099
Solar/Wind Harmer
0.025
962331AG1-082 GEN
Solar/Wind Harmer
0.733
3146073TAR RVR
Solar/Wind Harmer
0.067
3146083TARBORO
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.065
3145746EVERETS
Solar/Wind Harmer
0.065
3156021HOLLOMANSOL
Solar/Wind Harmer
0.291
3145933PARMELE
Solar/Wind Harmer
0.064
966801AG1-551 GEN
Solar/Wind Harmer
0.744
3145963POPLR C
Solar/Wind Harmer
0.062
3146206CASHIE
Solar/Wind Harmer
0.062
315737AD1-076 GEN
Solar/Wind Harmer
0.772
971157AH1-035 GEN
Solar/Wind Harmer
0.716
315614AA2-178 GEN
Solar/Wind Harmer
0.332
3145273HOLLAND
Solar/Wind Harmer
0.043
3146776BUCKING
Solar/Wind Helper
0.309
316313AB2-026
Solar/Wind Helper
0.361
316258AE1-075 C
Solar/Wind Helper
0.325
316405AF2-144 C
Solar/Wind Helper
0.271
3148013FISHERV
Solar/Wind Helper
0.126
3144293JTRSVLE
50/50
1.227
3144293JTRSVLE
50/50
1.034
970535AG2-341 GEN
50/50
3.152
3152661PLYWOOD A
50/50
0.306
3151041BRUNSWICKG3
50/50
1.109
972187AH1-678 GEN
50/50
2.545
315242AE2-183_GT2
50/50
1.358
315241AE2-183_GT1
50/50
1.35
972185AH1-677 GEN
50/50
4.896
970533AG2-339 GEN
50/50
6.901
970531AG2-338 GEN
50/50
2.76
3151361ROSEMG1
50/50
0.261
3151371ROSEMS1
50/50
0.162
3151381ROSEMG2
50/50
0.122
970301AG2-198 GEN
Solar/Wind Harmer
16.784
3147133PAMPLIN
Solar/Wind Harmer
0.388
3147133PAMPLIN
Solar/Wind Harmer
0.31
958211AF2-115 GEN
Solar/Wind Harmer
4.361
963191AG1-168 GEN
Solar/Wind Harmer
1.454
971741AH1-377 GEN
Solar/Wind Harmer
34.597
316034AC1-036 C
Solar/Wind Harmer
0.021
970323AG2-213 GEN
Solar/Wind Harmer
12.383
971775AH1-396 GEN
Solar/Wind Harmer
0.464
313527AB2-043 GEN
Solar/Wind Harmer
0.003
962561AG1-105 GEN
Solar/Wind Harmer
8.006
939181AE1-148 GEN
Solar/Wind Harmer
7.768
964791AG1-342 GEN
Solar/Wind Harmer
3.068
3146843MT LREL
Solar/Wind Harmer
0.159
3146843MT LREL
Solar/Wind Harmer
0.159
970099AG2-077 GEN
Solar/Wind Harmer
16.16
970933AG2-581 GEN
Solar/Wind Harmer
8.957
316181AB2-040 GEN
Solar/Wind Harmer
0.133
3145593CAROLNA
Solar/Wind Harmer
0.088
3145593CAROLNA
Solar/Wind Harmer
0.088
966811AG1-552 GEN
Solar/Wind Harmer
0.957
3145593CAROLNA
Solar/Wind Harmer
0.11
3145783HORNRTN
Solar/Wind Harmer
1.539
3145783HORNRTN
Solar/Wind Harmer
1.231
3145783HORNRTN
Solar/Wind Harmer
0.385
3145783HORNRTN
Solar/Wind Harmer
0.154
316426AA2-053 GEN
Solar/Wind Harmer
0.286
316222AC1-221 GEN
Solar/Wind Harmer
0.347
316274AC1-208 GEN
Solar/Wind Harmer
0.402
3142666NORTHAMPTON
Solar/Wind Harmer
0.072
3142666NORTHAMPTON
Solar/Wind Harmer
0.072
3142666NORTHAMPTON
Solar/Wind Harmer
0.072
3142666NORTHAMPTON
Solar/Wind Harmer
0.044
942751AE2-291 GEN
Solar/Wind Harmer
3.947
3145796HORNRTN
Solar/Wind Harmer
0.217
3145893MURPHYS
Solar/Wind Harmer
0.473
3145893MURPHYS
Solar/Wind Harmer
0.127
316263AC1-034 GEN
Solar/Wind Harmer
2.657
3146173TUNIS
Solar/Wind Harmer
0.069
3146173TUNIS
Solar/Wind Harmer
0.069
3145746EVERETS
Solar/Wind Harmer
0.065
3145746EVERETS
Solar/Wind Harmer
0.065
3145746EVERETS
Solar/Wind Harmer
0.065
970181AG2-120 GEN
Solar/Wind Harmer
0.805
315814AE2-033 C
Solar/Wind Harmer
4.945
316315AB2-025 C
Solar/Wind Harmer
0.05
3146206CASHIE
Solar/Wind Harmer
0.062
970601AG2-382 GEN
Solar/Wind Harmer
2.302
315732AD1-074 GEN1
Solar/Wind Harmer
0.345
315733AD1-074 GEN2
Solar/Wind Harmer
0.345
315735AD1-075 GEN1
Solar/Wind Harmer
0.173
3130546PLYMOUTH
Solar/Wind Harmer
0.06
315816AE2-034 GEN
Solar/Wind Harmer
0.249
270494AE1-108_GEN
Solar/Wind Helper
4.45
3138266HYDRAULIC
Solar/Wind Helper
0.009
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3144293JTRSVLE
50/50
1.227
3151531CLOVER1
50/50
3.3
3151601KERR 3
50/50
0.315
3151581KERR 1
50/50
0.112
3147043LAWRENC
50/50
1.233
3151261ROARAP2
50/50
0.11
3151051BRUNSWICKS1
50/50
2.302
3151021BRUNSWICKG1
50/50
1.109
971451AH1-221 GEN
50/50
3.369
315243AE2-183_GT3
50/50
1.358
3151391GASTONA
50/50
0.198
3151411GASTONB
50/50
0.198
3146926FARMVIL
Solar/Wind Harmer
0.322
963171AG1-166 GEN
Solar/Wind Harmer
1.938
971563AH1-280 GEN
Solar/Wind Harmer
3.876
970685AG2-442 GEN
Solar/Wind Harmer
24.484
962491AG1-098 GEN
Solar/Wind Harmer
11.925
316237AB2-079_GEN
Solar/Wind Harmer
0.002
315693AD1-088 GEN
Solar/Wind Harmer
9.548
970401AG2-262 GEN
Solar/Wind Harmer
0.937
957481AF2-042 GEN
Solar/Wind Harmer
40.4
315687AD1-152 GEN
Solar/Wind Harmer
0.005
971065AG2-659 GEN
Solar/Wind Harmer
5.702
316129AC1-054 GEN
Solar/Wind Harmer
0.489
971795AH1-408 GEN
Solar/Wind Harmer
7.855
316003AC1-222 GEN
Solar/Wind Harmer
0.003
960081AF2-299 GEN
Solar/Wind Harmer
0.909
3145783HORNRTN
Solar/Wind Harmer
0.086
316190AA2-174 GEN
Solar/Wind Harmer
0
970919AG2-571 GEN
Solar/Wind Harmer
2.916
970087AG2-069 GEN
Solar/Wind Harmer
6.541
316212AC1-099_GEN
Solar/Wind Harmer
0.387
3146263WOODLND
Solar/Wind Harmer
0.074
316011AB1-132 GEN
Solar/Wind Harmer
1.327
316023GEN1_S
Solar/Wind Harmer
0.164
962571AG1-106 GEN
Solar/Wind Harmer
1.039
3145796HORNRTN
Solar/Wind Harmer
0.239
3145796HORNRTN
Solar/Wind Harmer
0.072
3146233WITAKRS
Solar/Wind Harmer
0.286
3145893MURPHYS
Solar/Wind Harmer
0.283
3145893MURPHYS
Solar/Wind Harmer
0.314
315722AD1-056 GEN
Solar/Wind Harmer
0.447
3145823KELFORD
Solar/Wind Harmer
0.07
3145543BTLEBRO
Solar/Wind Harmer
0.07
3145543BTLEBRO
Solar/Wind Harmer
0.056
316359AB2-059 GEN
Solar/Wind Harmer
0.251
316049AB1-081 GEN
Solar/Wind Harmer
0.4
3142053HEARTS
Solar/Wind Harmer
0.123
3146173TUNIS
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.068
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.067
3145493TOT1
Solar/Wind Harmer
0.3
940641AE2-051 GEN
Solar/Wind Harmer
5.396
316494AC1-189 GEN
Solar/Wind Harmer
0.224
3145746EVERETS
Solar/Wind Harmer
0.065
3145746EVERETS
Solar/Wind Harmer
0.065
3146293MARTNCO
Solar/Wind Harmer
0.059
939411AE1-173 GEN
Solar/Wind Harmer
26.923
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3145963POPLR C
Solar/Wind Harmer
0.062
3146206CASHIE
Solar/Wind Harmer
0.062
971547AH1-271 GEN
Solar/Wind Harmer
1.316
3145663CRESWEL
Solar/Wind Harmer
0.162
971163AH1-040 GEN
Solar/Wind Harmer
4.641
316322AB2-045
Solar/Wind Helper
0.957
3146776BUCKING
Solar/Wind Helper
0.343
316336AC2-165 C
Solar/Wind Helper
1.513
961601AG1-000A GEN
Solar/Wind Harmer
1.227
3145493TOT1
Solar/Wind Harmer
0.156
3145453TOT5
Solar/Wind Harmer
0.094
3145603CNETO
Solar/Wind Harmer
0.063
3145933PARMELE
Solar/Wind Harmer
0.128
3145933PARMELE
Solar/Wind Harmer
0.064
3144356SAPONY
Solar/Wind Harmer
0.517
316065AD1-022 GEN
Solar/Wind Harmer
2.811
315742AE1-103 GEN
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Helper
3.433
3146776BUCKING
Solar/Wind Helper
0.278
315821AE2-092 GEN
Solar/Wind Helper
2.985
LAGNLTFEXP_LAGN->PJM
CLTF
2.753
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.143
TVALTFEXP_TVA->PJM
CLTF
1.358
CPLELTFEXP_CPLE->PJM
CLTF
4.949
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.581
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.475
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.539
MECLTFEXP_MEC->PJM
CLTF
1.12
SIGELTFEXP_SIGE->PJM
CLTF
0.032
NYPJM->LTFIMP_NY
CLTF
0.48
LGEELTFEXP_LGEE->PJM
CLTF
0.362
WECLTFEXP_WEC->PJM
CLTF
0.189

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.81 %
Rating:559.3 MVA
Rating Type:A
MVA to Mitigate:647.7
MW Contribution:2.32
Bus #Bus NameTypeMW Contribution
3151611KERR 4
50/50
0.279
3151621KERR 5
50/50
0.279
3151631KERR 6
50/50
0.279
3151641KERR 7
50/50
0.279
3151541CLOVER2
50/50
2.847
3151281ROARAP4
50/50
0.085
3151281ROARAP4
50/50
0.08
963041AG1-153 GEN
50/50
1.549
971845AH1-439 GEN
Solar/Wind Harmer
30.485
970285AG2-188 GEN
Solar/Wind Harmer
51.175
315657AE1-056 GEN
Solar/Wind Harmer
12.95
946301AF1-294 GEN
Solar/Wind Harmer
6.911
961791AG1-021 GEN
Solar/Wind Harmer
3.362
970683AG2-441 GEN
Solar/Wind Harmer
20.935
970681AG2-440 GEN
Solar/Wind Harmer
16.748
3144303KENBRDG
Solar/Wind Harmer
0.22
971443AH1-215 GEN
Solar/Wind Harmer
4.574
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.327
3147173SINAI
Solar/Wind Harmer
0.11
3147243WELCO
Solar/Wind Harmer
0.069
970831AG2-522 GEN
Solar/Wind Harmer
4.619
970865AG2-541 GEN
Solar/Wind Harmer
3.009
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.287
316123AC1-075 GEN
Solar/Wind Harmer
0.097
970165AG2-112 GEN
Solar/Wind Harmer
0.577
970163AG2-111 GEN
Solar/Wind Harmer
0.551
971967AH1-528 GEN
Solar/Wind Harmer
10.885
315607AA1-063A GEN
Solar/Wind Harmer
0.13
3146043SEABORD
Solar/Wind Harmer
0.063
970085AG2-068 GEN
Solar/Wind Harmer
3.037
970581AG2-369 GEN
Solar/Wind Harmer
2.612
270494AE1-108_GEN
Solar/Wind Helper
4.476
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
3144293JTRSVLE
50/50
1.183
3151591KERR 2
50/50
0.279
970413AG2-270 GEN
50/50
12.485
3151261ROARAP2
50/50
0.086
3151031BRUNSWICKG2
50/50
0.765
3146926FARMVIL
Solar/Wind Harmer
0.316
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
4.045
3147133PAMPLIN
Solar/Wind Harmer
1.178
971193AH1-056 GEN
Solar/Wind Harmer
22.863
963181AG1-167 GEN
Solar/Wind Harmer
1.401
959311AF2-222 GEN
Solar/Wind Harmer
25.479
970257AG2-171 GEN
Solar/Wind Harmer
8.819
315785AD2-033 C
Solar/Wind Harmer
2.117
964241AG1-285 GEN
Solar/Wind Harmer
14.665
316131AB2-060 GEN
Solar/Wind Harmer
0.615
316478AD1-087 GEN
Solar/Wind Harmer
0.466
316486AD2-202 GEN
Solar/Wind Harmer
0.137
3147043LAWRENC
Solar/Wind Harmer
0.066
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
4.708
971683AH1-343 GEN
Solar/Wind Harmer
3.476
313506AB2-031 GEN
Solar/Wind Harmer
0.227
316283AC2-100 C
Solar/Wind Harmer
0.132
316210AC1-098 GEN
Solar/Wind Harmer
0.531
970917AG2-570 GEN
Solar/Wind Harmer
5.072
316327AA2-057 GEN
Solar/Wind Harmer
0.085
3146776BUCKING
Solar/Wind Helper
0.313
316313AB2-026
Solar/Wind Helper
0.338
316258AE1-075 C
Solar/Wind Helper
0.304
316405AF2-144 C
Solar/Wind Helper
0.253
3148013FISHERV
Solar/Wind Helper
0.123
3144293JTRSVLE
50/50
1.183
3151601KERR 3
50/50
0.279
3151581KERR 1
50/50
0.1
3151531CLOVER1
50/50
2.861
3147043LAWRENC
50/50
1.063
3151261ROARAP2
50/50
0.088
3151051BRUNSWICKS1
50/50
1.588
3151021BRUNSWICKG1
50/50
0.765
971451AH1-221 GEN
50/50
2.324
3146926FARMVIL
Solar/Wind Harmer
0.316
963171AG1-166 GEN
Solar/Wind Harmer
1.868
971563AH1-280 GEN
Solar/Wind Harmer
3.736
970685AG2-442 GEN
Solar/Wind Harmer
23.448
962491AG1-098 GEN
Solar/Wind Harmer
10.797
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
8.584
970401AG2-262 GEN
Solar/Wind Harmer
0.842
957481AF2-042 GEN
Solar/Wind Harmer
34.592
315687AD1-152 GEN
Solar/Wind Harmer
0.004
971065AG2-659 GEN
Solar/Wind Harmer
4.952
316129AC1-054 GEN
Solar/Wind Harmer
0.422
316003AC1-222 GEN
Solar/Wind Harmer
0.003
971795AH1-408 GEN
Solar/Wind Harmer
6.656
960081AF2-299 GEN
Solar/Wind Harmer
0.732
3145783HORNRTN
Solar/Wind Harmer
0.069
316190AA2-174 GEN
Solar/Wind Harmer
0
316212AC1-099_GEN
Solar/Wind Harmer
0.296
970919AG2-571 GEN
Solar/Wind Harmer
2.029
970087AG2-069 GEN
Solar/Wind Harmer
4.556
316322AB2-045
Solar/Wind Helper
0.968
3146776BUCKING
Solar/Wind Helper
0.347
316336AC2-165 C
Solar/Wind Helper
1.445
3144293JTRSVLE
50/50
1.183
3144293JTRSVLE
50/50
0.996
970535AG2-341 GEN
50/50
2.851
3152661PLYWOOD A
50/50
0.269
3151041BRUNSWICKG3
50/50
0.765
972187AH1-678 GEN
50/50
1.756
970301AG2-198 GEN
Solar/Wind Harmer
16.182
3147133PAMPLIN
Solar/Wind Harmer
0.375
3147133PAMPLIN
Solar/Wind Harmer
0.3
958211AF2-115 GEN
Solar/Wind Harmer
4.203
963191AG1-168 GEN
Solar/Wind Harmer
1.401
971741AH1-377 GEN
Solar/Wind Harmer
33.06
316034AC1-036 C
Solar/Wind Harmer
0.02
970323AG2-213 GEN
Solar/Wind Harmer
11.759
971775AH1-396 GEN
Solar/Wind Harmer
0.441
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
7.224
939181AE1-148 GEN
Solar/Wind Harmer
6.94
964791AG1-342 GEN
Solar/Wind Harmer
2.755
3146843MT LREL
Solar/Wind Harmer
0.143
3146843MT LREL
Solar/Wind Harmer
0.143
970099AG2-077 GEN
Solar/Wind Harmer
13.837
970933AG2-581 GEN
Solar/Wind Harmer
6.964
316181AB2-040 GEN
Solar/Wind Harmer
0.107
3145593CAROLNA
Solar/Wind Harmer
0.07
3145593CAROLNA
Solar/Wind Harmer
0.07
966811AG1-552 GEN
Solar/Wind Harmer
0.763
3145593CAROLNA
Solar/Wind Harmer
0.088
3145783HORNRTN
Solar/Wind Harmer
1.221
3145783HORNRTN
Solar/Wind Harmer
0.977
3145783HORNRTN
Solar/Wind Harmer
0.305
3145783HORNRTN
Solar/Wind Harmer
0.122
316222AC1-221 GEN
Solar/Wind Harmer
0.284
316426AA2-053 GEN
Solar/Wind Harmer
0.225
942751AE2-291 GEN
Solar/Wind Harmer
3.338
316274AC1-208 GEN
Solar/Wind Harmer
0.311
3146776BUCKING
Solar/Wind Helper
3.475
3146776BUCKING
Solar/Wind Helper
0.282
315821AE2-092 GEN
Solar/Wind Helper
2.978
LAGNLTFEXP_LAGN->PJM
CLTF
1.976
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.656
TVALTFEXP_TVA->PJM
CLTF
0.971
CPLELTFEXP_CPLE->PJM
CLTF
3.789
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.54
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.153
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.217
MECLTFEXP_MEC->PJM
CLTF
0.756
SIGELTFEXP_SIGE->PJM
CLTF
0.021
NYPJM->LTFIMP_NY
CLTF
0.298
LGEELTFEXP_LGEE->PJM
CLTF
0.232
WECLTFEXP_WEC->PJM
CLTF
0.123

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:183.2 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:1047.0
MW Contribution:3.36
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.227
970413AG2-270 GEN
50/50
14.381
3151591KERR 2
50/50
0.314
3151261ROARAP2
50/50
0.107
3151031BRUNSWICKG2
50/50
1.106
3151391GASTONA
50/50
0.197
3151411GASTONB
50/50
0.197
3146776BUCKING
Solar/Wind Harmer
0.249
3146926FARMVIL
Solar/Wind Harmer
0.322
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
4.194
3147133PAMPLIN
Solar/Wind Harmer
1.217
971193AH1-056 GEN
Solar/Wind Harmer
23.622
963181AG1-167 GEN
Solar/Wind Harmer
1.453
959311AF2-222 GEN
Solar/Wind Harmer
26.742
970257AG2-171 GEN
Solar/Wind Harmer
9.28
315785AD2-033 C
Solar/Wind Harmer
2.237
964241AG1-285 GEN
Solar/Wind Harmer
15.699
316131AB2-060 GEN
Solar/Wind Harmer
0.665
316478AD1-087 GEN
Solar/Wind Harmer
0.537
316486AD2-202 GEN
Solar/Wind Harmer
0.158
3147043LAWRENC
Solar/Wind Harmer
0.077
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
5.394
971683AH1-343 GEN
Solar/Wind Harmer
4.007
313506AB2-031 GEN
Solar/Wind Harmer
0.283
316283AC2-100 C
Solar/Wind Harmer
0.161
970917AG2-570 GEN
Solar/Wind Harmer
7.271
316210AC1-098 GEN
Solar/Wind Harmer
0.691
316327AA2-057 GEN
Solar/Wind Harmer
0.111
3146263WOODLND
Solar/Wind Harmer
0.073
316365GEN2_N
Solar/Wind Harmer
0.163
3142666NORTHAMPTON
Solar/Wind Harmer
0.072
3145796HORNRTN
Solar/Wind Harmer
0.289
3145796HORNRTN
Solar/Wind Harmer
0.072
3146233WITAKRS
Solar/Wind Harmer
0.36
3146233WITAKRS
Solar/Wind Harmer
0.049
3138543CONSLDL
Solar/Wind Harmer
0.047
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3145893MURPHYS
Solar/Wind Harmer
0.118
3145893MURPHYS
Solar/Wind Harmer
0.07
315724AD1-057 GEN
Solar/Wind Harmer
0.264
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.07
957521AF2-046 GEN
Solar/Wind Harmer
5.218
961681AG1-008 GEN
Solar/Wind Harmer
5.218
3145543BTLEBRO
Solar/Wind Harmer
0.07
3145543BTLEBRO
Solar/Wind Harmer
0.07
971623AH1-311 GEN
Solar/Wind Harmer
0.139
3146173TUNIS
Solar/Wind Harmer
0.069
961601AG1-000A GEN
Solar/Wind Harmer
4.894
316463AE2-346 GEN
Solar/Wind Harmer
0.059
316140AB2-099
Solar/Wind Harmer
0.024
962331AG1-082 GEN
Solar/Wind Harmer
0.731
3146073TAR RVR
Solar/Wind Harmer
0.067
3146083TARBORO
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.064
3145746EVERETS
Solar/Wind Harmer
0.064
3156021HOLLOMANSOL
Solar/Wind Harmer
0.29
3145933PARMELE
Solar/Wind Harmer
0.064
966801AG1-551 GEN
Solar/Wind Harmer
0.741
3145963POPLR C
Solar/Wind Harmer
0.062
3146206CASHIE
Solar/Wind Harmer
0.061
315737AD1-076 GEN
Solar/Wind Harmer
0.769
971157AH1-035 GEN
Solar/Wind Harmer
0.714
315614AA2-178 GEN
Solar/Wind Harmer
0.331
3145273HOLLAND
Solar/Wind Harmer
0.043
316313AB2-026
Solar/Wind Helper
0.362
316258AE1-075 C
Solar/Wind Helper
0.326
316405AF2-144 C
Solar/Wind Helper
0.271
3148013FISHERV
Solar/Wind Helper
0.126
3151541CLOVER2
50/50
3.28
3151611KERR 4
50/50
0.314
3151621KERR 5
50/50
0.314
3151631KERR 6
50/50
0.314
3151641KERR 7
50/50
0.314
3151281ROARAP4
50/50
0.107
3151281ROARAP4
50/50
0.1
963041AG1-153 GEN
50/50
2.24
315244AE2-183_ST
50/50
2.342
971845AH1-439 GEN
Solar/Wind Harmer
30.733
970285AG2-188 GEN
Solar/Wind Harmer
51.665
315657AE1-056 GEN
Solar/Wind Harmer
13.38
946301AF1-294 GEN
Solar/Wind Harmer
7.167
961791AG1-021 GEN
Solar/Wind Harmer
3.487
970683AG2-441 GEN
Solar/Wind Harmer
21.847
970681AG2-440 GEN
Solar/Wind Harmer
17.477
3144303KENBRDG
Solar/Wind Harmer
0.232
971443AH1-215 GEN
Solar/Wind Harmer
4.818
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.368
3147173SINAI
Solar/Wind Harmer
0.126
3147243WELCO
Solar/Wind Harmer
0.079
970831AG2-522 GEN
Solar/Wind Harmer
5.363
970865AG2-541 GEN
Solar/Wind Harmer
3.482
971967AH1-528 GEN
Solar/Wind Harmer
15.038
316087AB2-174 GEN
Solar/Wind Harmer
0.003
3137643SOCKMAN
Solar/Wind Harmer
0.358
316123AC1-075 GEN
Solar/Wind Harmer
0.114
970165AG2-112 GEN
Solar/Wind Harmer
0.675
970163AG2-111 GEN
Solar/Wind Harmer
0.644
315607AA1-063A GEN
Solar/Wind Harmer
0.167
970085AG2-068 GEN
Solar/Wind Harmer
4.35
970581AG2-369 GEN
Solar/Wind Harmer
3.741
3146043SEABORD
Solar/Wind Harmer
0.081
970673AG2-436 GEN
Solar/Wind Harmer
17.164
970673AG2-436 GEN
Solar/Wind Harmer
11.442
941031AE2-094 GEN
Solar/Wind Harmer
14.261
944011AF1-069 GEN
Solar/Wind Harmer
4.66
315652AC1-086 GEN
Solar/Wind Harmer
8.006
3146033SCOT NK
Solar/Wind Harmer
0.29
3145796HORNRTN
Solar/Wind Harmer
0.231
3145796HORNRTN
Solar/Wind Harmer
0.029
965291AG1-394 GEN
Solar/Wind Harmer
0.319
316319Z2-044 C
Solar/Wind Harmer
0
3145893MURPHYS
Solar/Wind Harmer
0.19
3145893MURPHYS
Solar/Wind Harmer
0.07
3145513AHOSKIE
Solar/Wind Harmer
0.143
3145513AHOSKIE
Solar/Wind Harmer
0.068
3145683EARLEYS
Solar/Wind Harmer
0.136
3145683EARLEYS
Solar/Wind Harmer
0.068
3145683EARLEYS
Solar/Wind Harmer
0.068
3145573BETHELC
Solar/Wind Harmer
0.067
3145573BETHELC
Solar/Wind Harmer
0.067
316420AA1-050 GEN
Solar/Wind Harmer
0.002
957861AF2-080 GEN
Solar/Wind Harmer
2.845
316005AA1-067
Solar/Wind Harmer
0.069
3145746EVERETS
Solar/Wind Harmer
0.257
3145746EVERETS
Solar/Wind Harmer
0.064
3145746EVERETS
Solar/Wind Harmer
0.064
3145746EVERETS
Solar/Wind Harmer
0.064
970181AG2-120 GEN
Solar/Wind Harmer
0.803
315814AE2-033 C
Solar/Wind Harmer
4.928
316315AB2-025 C
Solar/Wind Harmer
0.05
3146206CASHIE
Solar/Wind Harmer
0.061
970601AG2-382 GEN
Solar/Wind Harmer
2.295
315732AD1-074 GEN1
Solar/Wind Harmer
0.344
315733AD1-074 GEN2
Solar/Wind Harmer
0.344
315735AD1-075 GEN1
Solar/Wind Harmer
0.172
3130546PLYMOUTH
Solar/Wind Harmer
0.059
315816AE2-034 GEN
Solar/Wind Harmer
0.248
270494AE1-108_GEN
Solar/Wind Helper
4.456
3138266HYDRAULIC
Solar/Wind Helper
0.009
3144293JTRSVLE
50/50
1.227
3144293JTRSVLE
50/50
1.033
970535AG2-341 GEN
50/50
3.148
3152661PLYWOOD A
50/50
0.306
3151041BRUNSWICKG3
50/50
1.106
972187AH1-678 GEN
50/50
2.539
315242AE2-183_GT2
50/50
1.355
315241AE2-183_GT1
50/50
1.346
972185AH1-677 GEN
50/50
4.884
970533AG2-339 GEN
50/50
6.883
970531AG2-338 GEN
50/50
2.753
3151361ROSEMG1
50/50
0.26
3151371ROSEMS1
50/50
0.161
3151381ROSEMG2
50/50
0.122
3146776BUCKING
Solar/Wind Harmer
2.762
3146776BUCKING
Solar/Wind Harmer
0.224
970301AG2-198 GEN
Solar/Wind Harmer
16.775
3147133PAMPLIN
Solar/Wind Harmer
0.388
3147133PAMPLIN
Solar/Wind Harmer
0.31
958211AF2-115 GEN
Solar/Wind Harmer
4.358
963191AG1-168 GEN
Solar/Wind Harmer
1.453
971741AH1-377 GEN
Solar/Wind Harmer
34.576
316034AC1-036 C
Solar/Wind Harmer
0.021
970323AG2-213 GEN
Solar/Wind Harmer
12.374
971775AH1-396 GEN
Solar/Wind Harmer
0.464
313527AB2-043 GEN
Solar/Wind Harmer
0.003
962561AG1-105 GEN
Solar/Wind Harmer
7.996
939181AE1-148 GEN
Solar/Wind Harmer
7.758
964791AG1-342 GEN
Solar/Wind Harmer
3.064
3146843MT LREL
Solar/Wind Harmer
0.159
3146843MT LREL
Solar/Wind Harmer
0.159
970099AG2-077 GEN
Solar/Wind Harmer
16.138
970933AG2-581 GEN
Solar/Wind Harmer
8.941
316181AB2-040 GEN
Solar/Wind Harmer
0.133
3145593CAROLNA
Solar/Wind Harmer
0.088
3145593CAROLNA
Solar/Wind Harmer
0.088
966811AG1-552 GEN
Solar/Wind Harmer
0.955
3145593CAROLNA
Solar/Wind Harmer
0.11
3145783HORNRTN
Solar/Wind Harmer
1.535
3145783HORNRTN
Solar/Wind Harmer
1.228
3145783HORNRTN
Solar/Wind Harmer
0.384
3145783HORNRTN
Solar/Wind Harmer
0.153
316426AA2-053 GEN
Solar/Wind Harmer
0.285
316222AC1-221 GEN
Solar/Wind Harmer
0.347
316274AC1-208 GEN
Solar/Wind Harmer
0.401
3142666NORTHAMPTON
Solar/Wind Harmer
0.072
3142666NORTHAMPTON
Solar/Wind Harmer
0.072
3142666NORTHAMPTON
Solar/Wind Harmer
0.072
3142666NORTHAMPTON
Solar/Wind Harmer
0.043
942751AE2-291 GEN
Solar/Wind Harmer
3.936
3145796HORNRTN
Solar/Wind Harmer
0.217
3145893MURPHYS
Solar/Wind Harmer
0.472
3145893MURPHYS
Solar/Wind Harmer
0.127
316263AC1-034 GEN
Solar/Wind Harmer
2.649
3146173TUNIS
Solar/Wind Harmer
0.069
3146173TUNIS
Solar/Wind Harmer
0.069
961601AG1-000A GEN
Solar/Wind Harmer
1.224
3145493TOT1
Solar/Wind Harmer
0.156
3145453TOT5
Solar/Wind Harmer
0.094
3145603CNETO
Solar/Wind Harmer
0.062
3145933PARMELE
Solar/Wind Harmer
0.127
3145933PARMELE
Solar/Wind Harmer
0.064
3144356SAPONY
Solar/Wind Harmer
0.516
316065AD1-022 GEN
Solar/Wind Harmer
2.802
315742AE1-103 GEN
Solar/Wind Harmer
0.001
315821AE2-092 GEN
Solar/Wind Helper
2.989
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.076
3148013FISHERV
Solar/Wind Helper
0.072
3144293JTRSVLE
50/50
1.227
3151531CLOVER1
50/50
3.295
3151601KERR 3
50/50
0.314
3151581KERR 1
50/50
0.112
3147043LAWRENC
50/50
1.231
3151261ROARAP2
50/50
0.11
3151051BRUNSWICKS1
50/50
2.296
3151021BRUNSWICKG1
50/50
1.106
971451AH1-221 GEN
50/50
3.36
315243AE2-183_GT3
50/50
1.355
3151391GASTONA
50/50
0.197
3151411GASTONB
50/50
0.197
972003AH1-546 GEN
Solar/Wind Harmer
35.869
316322AB2-045
Solar/Wind Harmer
0.006
3146776BUCKING
Solar/Wind Harmer
0.276
3146926FARMVIL
Solar/Wind Harmer
0.322
963171AG1-166 GEN
Solar/Wind Harmer
1.937
971563AH1-280 GEN
Solar/Wind Harmer
3.874
970685AG2-442 GEN
Solar/Wind Harmer
24.468
962491AG1-098 GEN
Solar/Wind Harmer
11.913
316237AB2-079_GEN
Solar/Wind Harmer
0.002
315693AD1-088 GEN
Solar/Wind Harmer
9.538
970401AG2-262 GEN
Solar/Wind Harmer
0.936
957481AF2-042 GEN
Solar/Wind Harmer
40.345
315687AD1-152 GEN
Solar/Wind Harmer
0.005
971065AG2-659 GEN
Solar/Wind Harmer
5.693
316129AC1-054 GEN
Solar/Wind Harmer
0.488
971795AH1-408 GEN
Solar/Wind Harmer
7.841
316003AC1-222 GEN
Solar/Wind Harmer
0.003
960081AF2-299 GEN
Solar/Wind Harmer
0.907
3145783HORNRTN
Solar/Wind Harmer
0.086
316190AA2-174 GEN
Solar/Wind Harmer
0
970919AG2-571 GEN
Solar/Wind Harmer
2.909
970087AG2-069 GEN
Solar/Wind Harmer
6.525
316212AC1-099_GEN
Solar/Wind Harmer
0.386
3146263WOODLND
Solar/Wind Harmer
0.073
316011AB1-132 GEN
Solar/Wind Harmer
1.323
316023GEN1_S
Solar/Wind Harmer
0.163
962571AG1-106 GEN
Solar/Wind Harmer
1.036
3145796HORNRTN
Solar/Wind Harmer
0.238
3145796HORNRTN
Solar/Wind Harmer
0.072
3146233WITAKRS
Solar/Wind Harmer
0.285
3145893MURPHYS
Solar/Wind Harmer
0.282
3145893MURPHYS
Solar/Wind Harmer
0.313
315722AD1-056 GEN
Solar/Wind Harmer
0.446
3145823KELFORD
Solar/Wind Harmer
0.07
3145543BTLEBRO
Solar/Wind Harmer
0.07
3145543BTLEBRO
Solar/Wind Harmer
0.056
316359AB2-059 GEN
Solar/Wind Harmer
0.25
316049AB1-081 GEN
Solar/Wind Harmer
0.399
3142053HEARTS
Solar/Wind Harmer
0.123
3146173TUNIS
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.068
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.067
3145493TOT1
Solar/Wind Harmer
0.299
940641AE2-051 GEN
Solar/Wind Harmer
5.379
316494AC1-189 GEN
Solar/Wind Harmer
0.223
3145746EVERETS
Solar/Wind Harmer
0.064
3145746EVERETS
Solar/Wind Harmer
0.064
3146293MARTNCO
Solar/Wind Harmer
0.059
939411AE1-173 GEN
Solar/Wind Harmer
26.834
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3145963POPLR C
Solar/Wind Harmer
0.062
3146206CASHIE
Solar/Wind Harmer
0.061
971547AH1-271 GEN
Solar/Wind Harmer
1.311
3145663CRESWEL
Solar/Wind Harmer
0.162
971163AH1-040 GEN
Solar/Wind Harmer
4.625
316336AC2-165 C
Solar/Wind Helper
1.515
LAGNLTFEXP_LAGN->PJM
CLTF
2.721
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.095
TVALTFEXP_TVA->PJM
CLTF
1.342
CPLELTFEXP_CPLE->PJM
CLTF
4.932
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.368
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.244
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.478
MECLTFEXP_MEC->PJM
CLTF
1.093
SIGELTFEXP_SIGE->PJM
CLTF
0.031
NYPJM->LTFIMP_NY
CLTF
0.491
LGEELTFEXP_LGEE->PJM
CLTF
0.351
WECLTFEXP_WEC->PJM
CLTF
0.183

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.94 %
Rating:571.52 MVA
Rating Type:A
MVA to Mitigate:679.77
MW Contribution:2.31
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.182
3151591KERR 2
50/50
0.278
970413AG2-270 GEN
50/50
12.466
3151261ROARAP2
50/50
0.085
3151031BRUNSWICKG2
50/50
0.762
3146776BUCKING
Solar/Wind Harmer
0.247
3146926FARMVIL
Solar/Wind Harmer
0.316
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
4.043
3147133PAMPLIN
Solar/Wind Harmer
1.178
971193AH1-056 GEN
Solar/Wind Harmer
22.85
963181AG1-167 GEN
Solar/Wind Harmer
1.4
959311AF2-222 GEN
Solar/Wind Harmer
25.461
970257AG2-171 GEN
Solar/Wind Harmer
8.812
315785AD2-033 C
Solar/Wind Harmer
2.115
964241AG1-285 GEN
Solar/Wind Harmer
14.651
316131AB2-060 GEN
Solar/Wind Harmer
0.614
316478AD1-087 GEN
Solar/Wind Harmer
0.465
3151611KERR 4
50/50
0.278
3151621KERR 5
50/50
0.278
3151631KERR 6
50/50
0.278
3151641KERR 7
50/50
0.278
3151541CLOVER2
50/50
2.843
3151281ROARAP4
50/50
0.085
3151281ROARAP4
50/50
0.079
963041AG1-153 GEN
50/50
1.544
971845AH1-439 GEN
Solar/Wind Harmer
30.475
970285AG2-188 GEN
Solar/Wind Harmer
51.158
315657AE1-056 GEN
Solar/Wind Harmer
12.943
946301AF1-294 GEN
Solar/Wind Harmer
6.907
961791AG1-021 GEN
Solar/Wind Harmer
3.36
970683AG2-441 GEN
Solar/Wind Harmer
20.922
970681AG2-440 GEN
Solar/Wind Harmer
16.737
3144303KENBRDG
Solar/Wind Harmer
0.22
3144293JTRSVLE
50/50
1.182
3151601KERR 3
50/50
0.278
3151581KERR 1
50/50
0.099
3151531CLOVER1
50/50
2.857
3147043LAWRENC
50/50
1.061
3151261ROARAP2
50/50
0.087
3151051BRUNSWICKS1
50/50
1.582
3151021BRUNSWICKG1
50/50
0.762
971451AH1-221 GEN
50/50
2.315
972003AH1-546 GEN
Solar/Wind Harmer
35.828
316322AB2-045
Solar/Wind Harmer
0.005
3146776BUCKING
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Harmer
0.316
963171AG1-166 GEN
Solar/Wind Harmer
1.867
971563AH1-280 GEN
Solar/Wind Harmer
3.734
970685AG2-442 GEN
Solar/Wind Harmer
23.432
962491AG1-098 GEN
Solar/Wind Harmer
10.785
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
8.574
970401AG2-262 GEN
Solar/Wind Harmer
0.841
957481AF2-042 GEN
Solar/Wind Harmer
34.537
315687AD1-152 GEN
Solar/Wind Harmer
0.004
971065AG2-659 GEN
Solar/Wind Harmer
4.943
316129AC1-054 GEN
Solar/Wind Harmer
0.422
316003AC1-222 GEN
Solar/Wind Harmer
0.003
971795AH1-408 GEN
Solar/Wind Harmer
6.643
960081AF2-299 GEN
Solar/Wind Harmer
0.73
3145783HORNRTN
Solar/Wind Harmer
0.068
316190AA2-174 GEN
Solar/Wind Harmer
0
316212AC1-099_GEN
Solar/Wind Harmer
0.295
970919AG2-571 GEN
Solar/Wind Harmer
2.021
970087AG2-069 GEN
Solar/Wind Harmer
4.539
316336AC2-165 C
Solar/Wind Helper
1.447
3144293JTRSVLE
50/50
1.182
316486AD2-202 GEN
Solar/Wind Harmer
0.137
3147043LAWRENC
Solar/Wind Harmer
0.066
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
4.699
971683AH1-343 GEN
Solar/Wind Harmer
3.468
313506AB2-031 GEN
Solar/Wind Harmer
0.226
316283AC2-100 C
Solar/Wind Harmer
0.132
316210AC1-098 GEN
Solar/Wind Harmer
0.53
970917AG2-570 GEN
Solar/Wind Harmer
5.054
316327AA2-057 GEN
Solar/Wind Harmer
0.085
316313AB2-026
Solar/Wind Helper
0.339
316258AE1-075 C
Solar/Wind Helper
0.305
316405AF2-144 C
Solar/Wind Helper
0.254
3148013FISHERV
Solar/Wind Helper
0.124
3144293JTRSVLE
50/50
0.996
970535AG2-341 GEN
50/50
2.848
3152661PLYWOOD A
50/50
0.269
3151041BRUNSWICKG3
50/50
0.762
972187AH1-678 GEN
50/50
1.749
3146776BUCKING
Solar/Wind Harmer
2.741
3146776BUCKING
Solar/Wind Harmer
0.222
970301AG2-198 GEN
Solar/Wind Harmer
16.173
3147133PAMPLIN
Solar/Wind Harmer
0.375
3147133PAMPLIN
Solar/Wind Harmer
0.3
958211AF2-115 GEN
Solar/Wind Harmer
4.2
963191AG1-168 GEN
Solar/Wind Harmer
1.4
971741AH1-377 GEN
Solar/Wind Harmer
33.04
316034AC1-036 C
Solar/Wind Harmer
0.02
970323AG2-213 GEN
Solar/Wind Harmer
11.75
971775AH1-396 GEN
Solar/Wind Harmer
0.441
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
7.214
939181AE1-148 GEN
Solar/Wind Harmer
6.93
964791AG1-342 GEN
Solar/Wind Harmer
2.751
3146843MT LREL
Solar/Wind Harmer
0.143
3146843MT LREL
Solar/Wind Harmer
0.143
970099AG2-077 GEN
Solar/Wind Harmer
13.815
970933AG2-581 GEN
Solar/Wind Harmer
6.948
316181AB2-040 GEN
Solar/Wind Harmer
0.106
3145593CAROLNA
Solar/Wind Harmer
0.07
3145593CAROLNA
Solar/Wind Harmer
0.07
966811AG1-552 GEN
Solar/Wind Harmer
0.761
3145593CAROLNA
Solar/Wind Harmer
0.087
3145783HORNRTN
Solar/Wind Harmer
1.218
3145783HORNRTN
Solar/Wind Harmer
0.974
3145783HORNRTN
Solar/Wind Harmer
0.304
3145783HORNRTN
Solar/Wind Harmer
0.122
316222AC1-221 GEN
Solar/Wind Harmer
0.283
316426AA2-053 GEN
Solar/Wind Harmer
0.225
942751AE2-291 GEN
Solar/Wind Harmer
3.327
316274AC1-208 GEN
Solar/Wind Harmer
0.31
315821AE2-092 GEN
Solar/Wind Helper
2.982
971443AH1-215 GEN
Solar/Wind Harmer
4.571
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.326
3147173SINAI
Solar/Wind Harmer
0.11
3147243WELCO
Solar/Wind Harmer
0.069
970831AG2-522 GEN
Solar/Wind Harmer
4.61
970865AG2-541 GEN
Solar/Wind Harmer
3.002
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.286
316123AC1-075 GEN
Solar/Wind Harmer
0.097
970165AG2-112 GEN
Solar/Wind Harmer
0.576
970163AG2-111 GEN
Solar/Wind Harmer
0.549
971967AH1-528 GEN
Solar/Wind Harmer
10.852
315607AA1-063A GEN
Solar/Wind Harmer
0.13
3146043SEABORD
Solar/Wind Harmer
0.063
970085AG2-068 GEN
Solar/Wind Harmer
3.026
970581AG2-369 GEN
Solar/Wind Harmer
2.602
270494AE1-108_GEN
Solar/Wind Helper
4.482
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
LAGNLTFEXP_LAGN->PJM
CLTF
1.944
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.608
TVALTFEXP_TVA->PJM
CLTF
0.955
CPLELTFEXP_CPLE->PJM
CLTF
3.771
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.922
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.157
MECLTFEXP_MEC->PJM
CLTF
0.729
SIGELTFEXP_SIGE->PJM
CLTF
0.02
NYPJM->LTFIMP_NY
CLTF
0.308
LGEELTFEXP_LGEE->PJM
CLTF
0.221
WECLTFEXP_WEC->PJM
CLTF
0.117
CONTINGENCY 'DVP_P1-2: LN 576_SRT-S'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P4-2: 562T563_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1   /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 940640 CKT 1   /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 2002_SRT-A'
 OPEN BRANCH FROM BUS 314282 TO BUS 314331 CKT 1   /*6CARSON      230.0 - 6POE         230.0
 OPEN BRANCH FROM BUS 314329 TO BUS 314331 CKT 1   /*3POE         115.0 - 6POE         230.0
END
CONTINGENCY 'DVP_P1-2: LN 249_SRT-A'
 OPEN BRANCH FROM BUS 313014 TO BUS 314285 CKT 1   /*6CHAPARRAL   230.0 - 6CHAPARRAL T 230.0
 OPEN BRANCH FROM BUS 314282 TO BUS 314285 CKT 1   /*6CARSON      230.0 - 6CHAPARRAL T 230.0
 OPEN BRANCH FROM BUS 314285 TO BUS 314316 CKT 1   /*6CHAPARRAL T 230.0 - 6LOCKS       230.0
 OPEN BRANCH FROM BUS 314314 TO BUS 314316 CKT 2   /*3LOCKS       115.0 - 6LOCKS       230.0
 OPEN BUS 313014                                   /*6CHAPARRAL   230.0
 OPEN BUS 314285                                   /*6CHAPARRAL T 230.0
END
CONTINGENCY 'DVP_P4-2: 56372_SRT-S'
 OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1                /*6CARSON      230.0 - 8CARSON      500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 574_SRT-S'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3966 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 3572 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: 557T574_SRT-S'
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3966 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 3572 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: 56272_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 940640 CKT 1                /*8CARSON      500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 314927 CKT 1 /*8SEPTA       500.0 - 8YADKIN      500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314923 TO BUS 314927 CKT 1 /*8SEPTA       500.0 - 8YADKIN      500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON      500.0 - 8MDLTHAN     500.0
END
CONTINGENCY 'DVP_P1-2: LN 567_SRT-A'
 OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1   /*8CHCKAHM     500.0 - 8SURRY       500.0
END
CONTINGENCY 'DVP_P4-2: H2T574_SRT-S'
 OPEN BRANCH FROM BUS 314196 TO BUS 314911 CKT 2                /*6LADYSMITH   230.0 - 8LADYSMITH   500.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3966 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 3572 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: H1T574_SRT-S'
 OPEN BRANCH FROM BUS 314218 TO BUS 314908 CKT 1                /*6ELMONT      230.0 - 8ELMONT      500.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT      500.0 - 8CUNINGHAM   500.0
 SET POSTCONTRATING 3966 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT      500.0 - 8CUNINGHAM   500.0
 SET PRECONTRATING 3572 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: 56722_SRT-A'
 OPEN BRANCH FROM BUS 314214 TO BUS 314903 CKT 1   /*6CHCKAHM     230.0 - 8CHCKAHM     500.0
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1   /*8CHCKAHM     500.0 - 8ELMONT      500.0
 OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1   /*8CHCKAHM     500.0 - 8SURRY       500.0
END
CONTINGENCY 'DVP_P2-2: BREMO B1_SRT-A'
 OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1   /*6BREMODIST   230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 1   /*6BEARGRDN    230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 2   /*6BEARGRDN    230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 1   /*3BREMO       115.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 970936 TO BUS 314747 CKT 1   /*AG2-583 TP   230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 972002 TO BUS 314747 CKT 1   /*AH1-546 TP   230.0 - 6BREMO       230.0
 OPEN BUS 314326                                   /*6BEARGRDN    230.0
 OPEN BUS 314747                                   /*6BREMO       230.0
 OPEN BUS 315191                                   /*1BEARGRDN G1  18.0
 OPEN BUS 315192                                   /*1BEARGRDN G2  18.0
 OPEN BUS 315193                                   /*1BEARGRDN S1  18.0
END
CONTINGENCY 'DVP_P7-1: LN 2003-205_SRT-S'
 OPEN BRANCH FROM BUS 314263 TO BUS 314287 CKT 1                /*6TYLER1      230.0 - 6CHESTF B    230.0
 OPEN BRANCH FROM BUS 314263 TO BUS 314331 CKT 1                /*6TYLER1      230.0 - 6POE         230.0
 OPEN BRANCH FROM BUS 314287 TO BUS 314346 CKT 1                /*6CHESTF B    230.0 - 6TYLER       230.0
 OPEN BRANCH FROM BUS 314301 TO BUS 314316 CKT 1                /*6HARR205     230.0 - 6LOCKS       230.0
 OPEN BRANCH FROM BUS 314301 TO BUS 314346 CKT 1                /*6HARR205     230.0 - 6TYLER       230.0
 OPEN BRANCH FROM BUS 314314 TO BUS 314316 CKT 1                /*3LOCKS       115.0 - 6LOCKS       230.0
 OPEN BRANCH FROM BUS 314329 TO BUS 314331 CKT 2                /*3POE         115.0 - 6POE         230.0
 OPEN BUS 314263                                                /*6TYLER1      230.0
 OPEN BUS 314301                                                /*6HARR205     230.0
 OPEN BUS 314346                                                /*6TYLER       230.0
 OPEN BUS 315839                                                /*AE2-212 C    230.0
 OPEN BUS 316240                                                /*AF1-291 C    230.0
 SET POSTCONTRATING 956 BRANCH FROM BUS 314260 TO BUS 314287 CKT 1 /*6VARINA      230.0 - 6CHESTF B    230.0
 SET PRECONTRATING 876 BRANCH FROM BUS 314260 TO BUS 314287 CKT 1 /*6VARINA      230.0 - 6CHESTF B    230.0
END
CONTINGENCY 'DVP_P7-1: LN 208-259_SRT-S'
 OPEN BRANCH FROM BUS 314276 TO BUS 314287 CKT 1                /*6BASIN       230.0 - 6CHESTF B    230.0
 OPEN BRANCH FROM BUS 314286 TO BUS 314309 CKT 1                /*6CHESTF A    230.0 - 6IRON208     230.0
 OPEN BRANCH FROM BUS 314309 TO BUS 314338 CKT 1                /*6IRON208     230.0 - 6SOUWEST     230.0
 OPEN BUS 314309                                                /*6IRON208     230.0
 SET POSTCONTRATING 876 BRANCH FROM BUS 314263 TO BUS 314287 CKT 1 /*6TYLER1      230.0 - 6CHESTF B    230.0
 SET PRECONTRATING 813 BRANCH FROM BUS 314263 TO BUS 314287 CKT 1 /*6TYLER1      230.0 - 6CHESTF B    230.0
END
CONTINGENCY 'AEP_P2-2_#1377_05J.FERR 765_1_SRT-A'
 OPEN BRANCH FROM BUS 242514 TO BUS 290022 CKT 1   /*05J.FERR     765.0 - 05J.FERR 1EQ   1.0
 OPEN BRANCH FROM BUS 242520 TO BUS 290022 CKT 1   /*05J.FERR     500.0 - 05J.FERR 1EQ   1.0
 OPEN BRANCH FROM BUS 242520 TO BUS 306719 CKT 1   /*05J.FERR     500.0 - 8ANTIOCH     500.0
 OPEN BRANCH FROM BUS 290022 TO BUS 290023 CKT 1   /*05J.FERR 1EQ   1.0 - 05J.FERR T1   13.8
END
CONTINGENCY 'DVP_P1-2: LN 585_SRT-A-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 941030 CKT 1   /*8CARSON      500.0 - AE2-094 TP   500.0
END
CONTINGENCY 'DVP_P4-2: WT576_SRT-S'
 OPEN BRANCH FROM BUS 314232 TO BUS 314918 CKT 2                /*6NO ANNA     230.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P4-2: 57602_SRT-S'
 OPEN BRANCH FROM BUS 314232 TO BUS 314918 CKT 1                /*6NO ANNA     230.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 557_SRT-S'
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: 574T575_SRT-S'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 OPEN BRANCH FROM BUS 314911 TO BUS 314918 CKT 1                /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
 SET POSTCONTRATING 3966 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
 SET PRECONTRATING 3572 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-1: G202_SRT-S'
 OPEN BRANCH FROM BUS 314232 TO BUS 314918 CKT 2                /*6NO ANNA     230.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314918 TO BUS 315226 CKT 1                /*8NO ANNA     500.0 - 1N ANNA2      22.0
 OPEN BUS 315226                                                /*1N ANNA2      22.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P2-2: NORTH ANNA B1_SRT-S'
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P2-2: NORTH ANNA B2_SRT-S'
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P7-1: LN 2090-256_SRT-S'
 OPEN BRANCH FROM BUS 313837 TO BUS 314138 CKT 1                /*6SUMMIT      230.0 - 6MINE RD     230.0
 OPEN BRANCH FROM BUS 313837 TO BUS 314197 CKT 1                /*6SUMMIT      230.0 - 6LDYSMITH CT 230.0
 OPEN BRANCH FROM BUS 314137 TO BUS 314138 CKT 1                /*6FREDBRG     230.0 - 6MINE RD     230.0
 OPEN BRANCH FROM BUS 314150 TO BUS 314212 CKT 1                /*6STJOHN      230.0 - 6FOUR RIVERS 230.0
 OPEN BRANCH FROM BUS 314197 TO BUS 315672 CKT 1                /*6LDYSMITH CT 230.0 - AE1-157 TAP  230.0
 OPEN BUS 313837                                                /*6SUMMIT      230.0
 OPEN BUS 314138                                                /*6MINE RD     230.0
 OPEN BUS 314149                                                /*3STJOHND     115.0
 OPEN BUS 314150                                                /*6STJOHN      230.0
 OPEN BUS 314154                                                /*3STJOHNS     115.0
 OPEN BUS 315672                                                /*AE1-157 TAP  230.0
 OPEN BUS 315673                                                /*AE1-157 GEN    0.6
 OPEN BUS 315803                                                /*AE1-157 MAIN 230.0
 OPEN BUS 315804                                                /*AE1-157 COL1  34.5
 OPEN BUS 315805                                                /*AE1-157 COL2  34.5
 SET POSTCONTRATING 657 BRANCH FROM BUS 313027 TO BUS 314212 CKT 1 /*6FOUR RIVER1 230.0 - 6FOUR RIVERS 230.0
 SET POSTCONTRATING 876 BRANCH FROM BUS 314212 TO BUS 315610 CKT 1 /*6FOUR RIVERS 230.0 - AA1-145 MAIN 230.0
 SET PRECONTRATING 598 BRANCH FROM BUS 313027 TO BUS 314212 CKT 1 /*6FOUR RIVER1 230.0 - 6FOUR RIVERS 230.0
 SET PRECONTRATING 813 BRANCH FROM BUS 314212 TO BUS 315610 CKT 1 /*6FOUR RIVERS 230.0 - AA1-145 MAIN 230.0
END
CONTINGENCY 'DVP_P7-1: LN 2054-2135_SRT-A'
 OPEN BRANCH FROM BUS 314734 TO BUS 314758 CKT 1   /*6CASHSCORNER 230.0 - 6GORDNVL     230.0
 OPEN BRANCH FROM BUS 314734 TO BUS 314759 CKT 1   /*6CASHSCORNER 230.0 - 6HOLLYMD     230.0
 OPEN BRANCH FROM BUS 314749 TO BUS 314772 CKT 1   /*6CHARLVL     230.0 - 6PROFFIT     230.0
 OPEN BRANCH FROM BUS 314759 TO BUS 314772 CKT 1   /*6HOLLYMD     230.0 - 6PROFFIT     230.0
 OPEN BUS 314734                                   /*6CASHSCORNER 230.0
 OPEN BUS 314772                                   /*6PROFFIT     230.0
END
CONTINGENCY 'DVP_P4-2: 57302_SRT-S'
 OPEN BRANCH FROM BUS 314232 TO BUS 314918 CKT 1                /*6NO ANNA     230.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314918 TO BUS 314934 CKT 1                /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P1-2: LN 594_SRT-S'
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 573_SRT-S'
 OPEN BRANCH FROM BUS 314918 TO BUS 314934 CKT 1                /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
END
CONTINGENCY 'DVP_P4-2: SPOTS H1T594_SRT-S'
 OPEN BRANCH FROM BUS 314755 TO BUS 314934 CKT 1                /*3SPOTSYL     115.0 - 8SPOTSYL     500.0
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P4-2: H1T594_SRT-S'
 OPEN BRANCH FROM BUS 314063 TO BUS 314916 CKT 1                /*6MORRSVL     230.0 - 8MORRSVL     500.0
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 OPEN BUS 314897                                                /*8MORRS_1     500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314916 TO BUS 314929 CKT 1 /*8MORRSVL     500.0 - 8FRONT ROYAL 500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314916 TO BUS 314929 CKT 1 /*8MORRSVL     500.0 - 8FRONT ROYAL 500.0
END
CONTINGENCY 'DVP_P4-2: 515T594_SRT-S'
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 OPEN BRANCH FROM BUS 314934 TO BUS 314944 CKT 1                /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 OPEN BUS 314944                                                /*8SPOTSYL EC  500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P4-2: H1T573_SRT-S'
 OPEN BRANCH FROM BUS 314755 TO BUS 314934 CKT 1                /*3SPOTSYL     115.0 - 8SPOTSYL     500.0
 OPEN BRANCH FROM BUS 314918 TO BUS 314934 CKT 1                /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
END
CONTINGENCY 'DVP_P4-2: 57502_SRT-S'
 OPEN BRANCH FROM BUS 314232 TO BUS 314918 CKT 1                /*6NO ANNA     230.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314911 TO BUS 314918 CKT 1                /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 575_SRT-S'
 OPEN BRANCH FROM BUS 314911 TO BUS 314918 CKT 1                /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
END
CONTINGENCY 'DVP_P1-2: LN 550_SRT-A'
 OPEN BRANCH FROM BUS 314917 TO BUS 314926 CKT 1   /*8MT STM      500.0 - 8VALLEY      500.0
END
CONTINGENCY 'DVP_P7-1: LN 11-2199_SRT-A-1'
 OPEN BRANCH FROM BUS 313227 TO BUS 314769 CKT 1   /*3ORANGE      115.0 - 3ORANGE TAP  115.0
 OPEN BRANCH FROM BUS 313671 TO BUS 315678 CKT 1   /*6GERMANNA    230.0 - AE1-153 TAP  230.0
 OPEN BRANCH FROM BUS 314756 TO BUS 314769 CKT 1   /*3DOUBLDY     115.0 - 3ORANGE TAP  115.0
 OPEN BRANCH FROM BUS 314756 TO BUS 314776 CKT 1   /*3DOUBLDY     115.0 - 3SOMRSET     115.0
 OPEN BRANCH FROM BUS 314757 TO BUS 314776 CKT 1   /*3GORDNVL     115.0 - 3SOMRSET     115.0
 OPEN BRANCH FROM BUS 314769 TO BUS 314815 CKT 1   /*3ORANGE TAP  115.0 - 3OAK GRE     115.0
 OPEN BRANCH FROM BUS 314776 TO BUS 314884 CKT 1   /*3SOMRSET     115.0 - 3SOMRS_1     115.0
 OPEN BUS 313227                                   /*3ORANGE      115.0
 OPEN BUS 314756                                   /*3DOUBLDY     115.0
 OPEN BUS 314769                                   /*3ORANGE TAP  115.0
 OPEN BUS 314776                                   /*3SOMRSET     115.0
 OPEN BUS 314884                                   /*3SOMRS_1     115.0
END
CONTINGENCY 'DVP_P7-1: LN 11-2199_SRT-A-2'
 OPEN BRANCH FROM BUS 313227 TO BUS 314769 CKT 1   /*3ORANGE      115.0 - 3ORANGE TAP  115.0
 OPEN BRANCH FROM BUS 314756 TO BUS 314769 CKT 1   /*3DOUBLDY     115.0 - 3ORANGE TAP  115.0
 OPEN BRANCH FROM BUS 314756 TO BUS 314776 CKT 1   /*3DOUBLDY     115.0 - 3SOMRSET     115.0
 OPEN BRANCH FROM BUS 314757 TO BUS 314776 CKT 1   /*3GORDNVL     115.0 - 3SOMRSET     115.0
 OPEN BRANCH FROM BUS 314758 TO BUS 315678 CKT 1   /*6GORDNVL     230.0 - AE1-153 TAP  230.0
 OPEN BRANCH FROM BUS 314769 TO BUS 314815 CKT 1   /*3ORANGE TAP  115.0 - 3OAK GRE     115.0
 OPEN BRANCH FROM BUS 314776 TO BUS 314884 CKT 1   /*3SOMRSET     115.0 - 3SOMRS_1     115.0
 OPEN BUS 313227                                   /*3ORANGE      115.0
 OPEN BUS 314756                                   /*3DOUBLDY     115.0
 OPEN BUS 314769                                   /*3ORANGE TAP  115.0
 OPEN BUS 314776                                   /*3SOMRSET     115.0
 OPEN BUS 314884                                   /*3SOMRS_1     115.0
END
CONTINGENCY 'DVP_P1-2: LN 585_SRT-A-2'
 OPEN BRANCH FROM BUS 941030 TO BUS 970672 CKT 1   /*AE2-094 TP   500.0 - AG2-436 TP   500.0
END
CONTINGENCY 'DVP_P4-2: 58572_SRT-A'
 OPEN BRANCH FROM BUS 314902 TO BUS 941030 CKT 1   /*8CARSON      500.0 - AE2-094 TP   500.0
END
CONTINGENCY 'DVP_P4-5: W72_SRT-A'
 OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1   /*6CARSON      230.0 - 8CARSON      500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 941030 CKT 1   /*8CARSON      500.0 - AE2-094 TP   500.0
END
CONTINGENCY 'DVP_P4-2: XT585_SRT-S'
 OPEN BRANCH FROM BUS 970672 TO BUS 314940 CKT 1                /*AG2-436 TP   500.0 - 8ROGERS RD   500.0
 SET POSTCONTRATING 3464 BRANCH FROM BUS 314935 TO BUS 314940 CKT 1 /*8HERITAGE    500.0 - 8ROGERS RD   500.0
 SET PRECONTRATING 3464 BRANCH FROM BUS 314935 TO BUS 314940 CKT 1 /*8HERITAGE    500.0 - 8ROGERS RD   500.0
END
CONTINGENCY 'DVP_P4-2: 54472_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 939410 CKT 1                /*8CARSON      500.0 - AE1-173 TP   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P1-2: LN 511_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 51192_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 OPEN BUS 314921                                                /*8RAWLIN_STC2 500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 51172_SRT-S'
 OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1                /*6CARSON      230.0 - 8CARSON      500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 511T544_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 939410 CKT 1                /*8CARSON      500.0 - AE1-173 TP   500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: H6T576_SRT-A'
 OPEN BRANCH FROM BUS 314322 TO BUS 314914 CKT 1   /*6MDLTHAN     230.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1   /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P4-2: H6T563_SRT-S'
 OPEN BRANCH FROM BUS 314322 TO BUS 314914 CKT 1                /*6MDLTHAN     230.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P2-2: MORRISVILLE B1_SRT-S'
 OPEN BUS 314897                                                /*8MORRS_1     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314916 TO BUS 314929 CKT 1 /*8MORRSVL     500.0 - 8FRONT ROYAL 500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314916 TO BUS 314934 CKT 1 /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314916 TO BUS 314929 CKT 1 /*8MORRSVL     500.0 - 8FRONT ROYAL 500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314916 TO BUS 314934 CKT 1 /*8MORRSVL     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'AP_P2-2_WP-500-DRT14_SRT-SL'
 OPEN BRANCH FROM BUS 235109 TO BUS 235081 CKT 1                /*AB1-106 POI  500.0 - T-174  1     500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235108 TO BUS 235109 CKT 1 /*01HATFLD     500.0 - AB1-106 POI  500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235116 TO BUS 235109 CKT 1 /*01YUKON      500.0 - AB1-106 POI  500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235108 TO BUS 235109 CKT 1 /*01HATFLD     500.0 - AB1-106 POI  500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235116 TO BUS 235109 CKT 1 /*01YUKON      500.0 - AB1-106 POI  500.0
END
CONTINGENCY 'DVP_P1-2: LN 591_SRT-S'
 OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1                /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
END
314747 to 313867 ckt 1
313867 to 313707 ckt 1
314677 to 972002 ckt 1
314282 to 314285 ckt 1
314282 to 314331 ckt 1
314285 to 314316 ckt 1
314692 to 970284 ckt 1
313707 to 313373 ckt 1
313373 to 314765 ckt 1
314765 to 314749 ckt 1
314331 to 314263 ckt 1
314346 to 314287 ckt 1
314902 to 314282 ckt 1
314902 to 314282 ckt 2
314902 to 314914 ckt 1
314935 to 314936 ckt 1
314914 to 314322 ckt 1
314914 to 314918 ckt 1
314918 to 314911 ckt 1
314918 to 314934 ckt 1
314936 to 314902 ckt 1
314940 to 970672 ckt 1
314923 to 314924 ckt 1
314934 to 314916 ckt 1
941030 to 314902 ckt 1
970284 to 971844 ckt 1
970672 to 941030 ckt 1
971844 to 314677 ckt 1
972002 to 314747 ckt 1

Winter Peak Analysis

The New Service Request AH1-221 was evaluated as a 0.0 MW (45.0 MW Capacity) injection in the Dominion area.

AH1-221 was evaluated as part of a plant. The plant consists of AH1-221. The total Energy output of the plant was evaluated at its maximum seasonal capability of 75.0 MW (45.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

(No impacts were found for this analysis)

Light Load Analysis

The New Service Request AH1-221 was evaluated as a 0.0 MW injection

AH1-221 was evaluated as part of a plant. The plant consists of AH1-221. The total Energy output of the plant was evaluated at its maximum seasonal capability of 75.0 MW (0.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

(No impacts were found for this analysis)

Short Circuit Analysis

Short Circuit analysis is not performed as part of the Phase I System Impact Study. Short Circuit analysis will commence in the Phase II System Impact Study.

Stability Analysis

Stability Analysis is Not Required.

Reactive Power Analysis

Reactive Power analysis is not performed as part of the Phase I System Impact Study. Reactive Power analysis will commence in the Phase II System Impact Study.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-038Lexington-Low Moor 230kVUnder Construction
AA1-050Tarboro-Everetts 230kVIn Service
AA1-063ACarolina–Seaboard 115kVIn Service
AA1-067Everetts 34.5kVIn Service
AA1-139Hickory-Shawboro 230kVIn Service
AA2-053Carolina-Jackson 115kVIn Service
AA2-057Hornertown-Whitakers 115kVIn Service
AA2-174Carolina-Jackson 115kVIn Service
AA2-178Mackeys 230kVIn Service
AB1-027Old Church 34.5 KVIn Service
AB1-081Anaconda-Mayo Dunbar 115kVIn Service
AB1-132Thelma 230kVIn Service
AB2-022Elizabeth City 34.5kVIn Service
AB2-024Correctional 34.5kVIn Service
AB2-025Sapony 34.5kVIn Service
AB2-026Powhatan 34.5kVIn Service
AB2-029Remington 34.5kVIn Service
AB2-031Brink-Trego 115kVIn Service
AB2-040Brink 115kVIn Service
AB2-043Chase City 115kVIn Service
AB2-045Buckingham 34.5kVIn Service
AB2-059Benson-Dunbar 115kVIn Service
AB2-060Chase City-Lunenburg 115kVIn Service
AB2-077Buggs Island-Chase City 115kVIn Service
AB2-078Buggs Island-Chase City 115kVIn Service
AB2-079Buggs Island-Chase City 115kVIn Service
AB2-099Ahoskie 34.5kVIn Service
AB2-134Hopewell-Surry 230kVIn Service
AB2-157Prince George's County 12kVIn Service
AB2-158Louisa-South Anna 230kVIn Service
AB2-161Waverly #2 DP 115kVIn Service
AB2-169Pantago-Five Points 115kVIn Service
AB2-174Emporia-Trego 115kVIn Service
AB2-190Hopewell-Surry 230kVIn Service
AC1-027Pendleton 34.5kVIn Service
AC1-034Heartsease DP - Mayo Dunbar 115kVSuspended
AC1-036Twittys Creek 34.5kVIn Service
AC1-042Altavista-Mt. Airy 69kVIn Service
AC1-054Kerr Dam–Eatons Ferry 115 kVIn Service
AC1-075Perth-Hickory Grove 115kVIn Service
AC1-076Locust Grove-Paytes 115kVIn Service
AC1-086Thelma 230kVSuspended
AC1-098Dawson-South Justice 115kVPartially in Service - Under Construction
AC1-099Dawson-South Justice 115kVPartially in Service - Under Construction
AC1-105Halifax-Mt. Laurel 115kVIn Service
AC1-118Westmoreland 34.5kVIn Service
AC1-120Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-121Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-145Gretna DP 69 kVIn Service
AC1-147Grassfield 34.5kVIn Service
AC1-158Spotsylvania 500kVIn Service
AC1-161Septa 500kVIn Service
AC1-164Chickahominy 230kVPartially in Service - Under Construction
AC1-189Chinquapin-Everetts 230kVUnder Construction
AC1-191Elmont 115kVEngineering & Procurement
AC1-208Cox-Whitakers 115kVUnder Construction
AC1-221Halifax-Person 230kVIn Service
AC1-222Crystal Hill-Halifax 115kVIn Service
AC2-012Grassfield-Great Bridge 115kVIn Service
AC2-079Ivor-Oak Ridge 115kVSuspended
AC2-100Halifax-Person 230kVIn Service
AC2-120Ripley 69kVIn Service
AC2-137Elko 34.5kVIn Service
AC2-138Northern Neck 34.5kVIn Service
AC2-141Septa 500kVEngineering & Procurement
AC2-165Bremo-Powhatan 230kVSuspended
AD1-017Smith Mountain-Bearskin 138 kVIn Service
AD1-022Cashie-Trowbridge 230 kVEngineering & Procurement
AD1-025Hopewell-Surry 230 kVUnder Construction
AD1-033Fentress-Landstown 230 kVIn Service
AD1-041Harmony Village-Shackleford 115 kVIn Service
AD1-056Hornertown-Hathaway 230 kVSuspended
AD1-057Hornertown-Hathaway 230 kVSuspended
AD1-063Harmony Village 34.5 kVIn Service
AD1-074Trowbridge 230 kVEngineering & Procurement
AD1-075Trowbridge 230 kVEngineering & Procurement
AD1-076Trowbridge 230 kVEngineering & Procurement
AD1-082Bakers Pond-Ivor 115kVIn Service
AD1-087Clover-Sedge Hill 230 kVIn Service
AD1-088Briery-Clover 230 kVSuspended
AD1-105Kings Dominion DP 115 kVUnder Construction
AD1-115Mountain Run-Mitchell 115 kVEngineering & Procurement
AD1-144Kings Fork 34.5 kVIn Service
AD1-151Hopewell-Surry 230 kVSuspended
AD1-152Clover-Sedge Hill 230 kVIn Service
AD2-022East Danville - Roxborough 230 kVEngineering & Procurement
AD2-023East Danville - Roxborough 230 kVEngineering & Procurement
AD2-030Wan 34.5 kVIn Service
AD2-033Chase City-Lunenburg 115 kVUnder Construction
AD2-058St. Barnabas 13 kVIn Service
AD2-073Sanders DP 230 kVIn Service
AD2-074Garner DP-Lancaster 115 kVEngineering & Procurement
AD2-085Myrtle-Windsor DP 115kVEngineering & Procurement
AD2-160Hickory-Moyock 230kVIn Service
AD2-202Clover-Sedge Hill 230kVIn Service
AE1-056Red House-South Creek 115 kVWithdrawn
AE1-072Shawboro-Sligo 230 kVUnder Construction
AE1-074Winterpock 34.5 kVUnder Construction
AE1-075Powhatan 34.5 kVIn Service
AE1-100Axton 138 kVIn Service
AE1-103Holland-Union Camp 115 kVUnder Construction
AE1-108Bremo-Scottsville 138 kVEngineering & Procurement
AE1-148Kerr Dam-Ridge Rd 115 kVActive
AE1-149Disputanta-Poe 115 kVSuspended
AE1-153Remington-Gordonsville 230 kVSuspended
AE1-155Garner-Northern Neck 115 kVIn Service
AE1-157Ladysmith CT-St. Johns 230 kVSuspended
AE1-162Smithfield 34.5 kVIn Service
AE1-173Carson-Suffolk 500 kVUnder Construction
AE1-175Light Foot 34.5 kVIn Service
AE1-190Harmony Village-Shackleford 115 kVPartially in Service - Under Construction
AE1-191Harmony Village-Shackleford 115 kVPartially in Service - Under Construction
AE1-250Smith Mountain-E. Danville 138 kVEngineering & Procurement
AE2-005Harmony Village-Shackleford 115 kVUnder Construction
AE2-027Harrowgate-Locks 115kVUnder Construction
AE2-029Grottoes-Merck 115kVUnder Construction
AE2-033Clubhouse-Sapony 230 kVSuspended
AE2-034Mackeys 230 kVPartially in Service - Under Construction
AE2-040Sapony 34.5 kVPartially in Service - Under Construction
AE2-047Ridgeway-Solite 69 kVEngineering & Procurement
AE2-051Carson-Septa 500 kVEngineering & Procurement
AE2-092Kidds Store-Sherwood 115 kVEngineering & Procurement
AE2-094Carson-Rogers Road 500 kVEngineering & Procurement
AE2-104Suffolk 115 kVSuspended
AE2-140Axton-Danville 138 kVSuspended
AE2-156Yadkin 115 kVActive
AE2-166Stockton 138 kVSuspended
AE2-183Rogers Road 500 kVIn Service
AE2-185Gladys DP-Stonemill Switching Station 69 kVActive
AE2-187Shockoe DP-Chatham 69 kVActive
AE2-212Harrowgate 34 kVEngineering & Procurement
AE2-253Hickory-Moyock 230 kVIn Service
AE2-259Curdsville-Willis Mtn 115 kVEngineering & Procurement
AE2-283Gladys-Stone Mill 69 kVActive
AE2-291Grit DP-Perth 115 kVActive
AE2-346Ahoskie 34.5 kVIn Service
AF1-014Harmony Village-Shackleford 115 kVUnder Construction
AF1-017Myrtle-Windsor 115 kVEngineering & Procurement
AF1-032Suffolk 34.5 kVIn Service
AF1-042Garner DP-Lancaster 115 kVEngineering & Procurement
AF1-049Berry Hill 138 kVUnder Construction
AF1-058Welco 34.5 kVIn Service
AF1-069Carson-Rogers Rd 500 kVEngineering & Procurement
AF1-114Oak Grove-Dahlgren 230 kVEngineering & Procurement
AF1-123Harper 230 kVActive
AF1-124Harper 230 kVActive
AF1-125Harper 230 kVActive
AF1-128Chesterfield 230 kVActive
AF1-129Chesterfield 230 kVEngineering & Procurement
AF1-147Poland Rd-Runway DP 230kVUnder Construction
AF1-291Tyler 34.5 kVEngineering & Procurement
AF1-292Fields 34.5kVEngineering & Procurement
AF1-294Jetersville-Ponton 115 kVActive
AF2-035St. Johns 115 kVActive
AF2-042Clover-Rawlings 500 kVActive
AF2-043Suffolk 34.5 kVIn Service
AF2-046Tunis-Mapleton 115 kVActive
AF2-054Wan 34.5 kVIn Service
AF2-077White Marsh 34.5 kVIn Service
AF2-080Chinquapin-Everetts 230 kVActive
AF2-081Moyock 230 kVActive
AF2-085Midlothian 34.5 kVIn Service
AF2-107Clifford 138 kVEngineering & Procurement
AF2-110Suffolk 115 kVSuspended
AF2-115Jetersville-Ponton 115 kVActive
AF2-120Garner-Northern Neck 115 kVActive
AF2-144Powhatan 34.5 kVIn Service
AF2-222Madisonville DP-Twitty's Creek 115 kVActive
AF2-297Sedge Hill 115 kVActive
AF2-299Fields 34.5 kVActive
AG1-007Tar River 12.5 kVEngineering & Procurement
AG1-008Tunis-Mapleton 115 kVActive
AG1-021Jetersville-Ponton 115 kVActive
AG1-037Ahoskie 34.5 kVEngineering & Procurement
AG1-038Garner DP-Lancaster 115 kVEngineering & Procurement
AG1-082Ahoskie 34.5 kVActive
AG1-098Briery-Clover 230 kVActive
AG1-105Mount Laurel-Barnes Junction 115 kVActive
AG1-106Thelma 230 kVActive
AG1-135Garner-Lancaster 115 kVActive
AG1-145Lightfoot 34.5 kVIn Service
AG1-146Garner DP-Lancaster 115 kVActive
AG1-147Garner DP-Lancaster 115 kVActive
AG1-153Heritage 500 kVActive
AG1-166Lone Pine 115 kVActive
AG1-167Lone Pine 115 kVActive
AG1-168Lone Pine 115 kVActive
AG1-282Dunnsville 34.5 kVEngineering & Procurement
AG1-285Chase City-Central 115 kVActive
AG1-342Dryburg 115 kVActive
AG1-393Sapony 34.5 kVActive
AG1-394Boykins 34.5 kVActive
AG1-469Gordonsville 34.5 kVEngineering & Procurement
AG1-494Boxwood-Riverville 138 kVActive
AG1-532Fields 34.5 kVEngineering & Procurement
AG1-551Parmele 34.5 kVActive
AG1-552Carolina 34.5 kVActive
AG1-558Buckner 34.5 kVEngineering & Procurement
AG1-559Caroline Pines 22 kVEngineering & Procurement
AG2-005Garner DP-Lancaster 115 kVActive
AG2-068Heritage - Wake 500 kVActive
AG2-069Heritage - Wake 500 kVActive
AG2-077Clover-Rawlings 500 kVActive
AG2-088Midlothian 230 kVActive
AG2-093Colonial Trail-Hopewell 230 kVActive
AG2-095Hopewell 34.5 kV (Circuit 313)Active
AG2-111Perth 34.5 kV Substation (Circuit 408)Active
AG2-112Perth 34.5 kV Substation (Circuit 404)Active
AG2-120Everetts 34.5 kVActive
AG2-124Shackleford-Harmony 115 kVActive
AG2-151Trices Lake - James River Tap 115 kVActive
AG2-152Banister-Bear Skin 138 kVActive
AG2-171Lunenburg-Nutbush 115 kVActive
AG2-188Farmville - Buckingham 230 kVActive
AG2-193Turner 34.5 kVActive
AG2-198Briery - Finneywood 230 kVActive
AG2-208Greenwood DP - St. Johns DP 115 kVActive
AG2-213Gary D.P Tap - Gary D.P 115 kVActive
AG2-215Garner DP-Lancaster 115 kVActive
AG2-262Dryburg 115 kVActive
AG2-270Clover 230 kVActive
AG2-338Rogers Road - Carson 500 kVActive
AG2-339Rogers Road - Carson 500 kVActive
AG2-341Ridge Road 115 kVActive
AG2-369Heritage - Wake 500 kVActive
AG2-382Cashie 230 kVActive
AG2-426Wakefield - Waverly 115 kVActive
AG2-427Waverly 115 kVActive
AG2-428Wakefield 115 kVActive
AG2-436Carson - Rogers Road 500 kVActive
AG2-440Twittys Creek - Madisonville 115 kVActive
AG2-441Twittys Creek - Madisonville 115 kVActive
AG2-442Twittys Creek - Madisonville 115 kVActive
AG2-469Westmoreland – Oak Grove 230 kVActive
AG2-522Five Forks DP 115 kVActive
AG2-541Perth - Crystal Hill 115 kVActive
AG2-566Briery - Finneywood 230 kVActive
AG2-570Heritage - Wake 500 kVActive
AG2-571Heritage - Wake 500 kVActive
AG2-581Rawlings-Clover 500 kVActive
AG2-583Bremo - Cartersville 230 kVActive
AG2-659Kerr Dam – Hawtree 115 kVActive
AG2-661Hopewell - Colonial Trail 230 kVActive
AH1-012Louisa - North Anna 230 kVActive
AH1-033Sligo 34.5 kVActive
AH1-035Plymouth 34.5 kVActive
AH1-040Mackeys - Creswell 115 kVActive
AH1-042Providence Forge-Turner 115kVActive
AH1-056Red House DP 115kVActive
AH1-071Midlothian 34.5 kVActive
AH1-106Winterpock 34.5kVActive
AH1-107Winterpock 34.5kVActive
AH1-108Spruance NUG 230 kVActive
AH1-138Penniman 34.5 kVActive
AH1-170Columbia DP 115kVActive
AH1-215Central VA-Twitty 115 kVActive
AH1-216Smithfield-Surry 230 kVActive
AH1-217Kidds Store - Fork Union 115 kV IIActive
AH1-241Cobbs Creek - James River Industrial 115kVActive
AH1-251Todds Tavern- Spotsylvania/Goldsdale 115kVActive
AH1-271Cashie 230 kVActive
AH1-280Jetersville-Ponton 115 kVActive
AH1-311Heartsease DP - Mayo Dunbar 115kVActive
AH1-314East Danville 138 kVActive
AH1-324Colonial Trail – Surry 230 kVActive
AH1-343Crystal Hill DP- Perth 115kVActive
AH1-377Clover- Farmville 230kVActive
AH1-396Gary 24.94 kVActive
AH1-397Shacklesford 34.5 kVActive
AH1-399North Doswell 12.5 kVActive
AH1-408Freeman DP – Lawrenceville 115 kVActive
AH1-439Buckingham- Farmville 230kVActive
AH1-528Rawlings - Unity 500 kVActive
AH1-546Bremo - Buckingham 230 kVActive
AH1-637Oak Grove 34.5 kVActive
AH1-676Gordonsville 230 kVActive
AH1-677Rogers Road 500 kVActive
AH1-678Heritage 500 kVActive
AH1-679Four Rivers 230 kVActive
AH1-681Cunningham 500 kVActive
AH1-682Ladysmith CT 230 kVActive
AH1-683Ladysmith CT 230 kVActive
AH1-687Bear Garden 230kVActive
AH1-691Ladysmith CT 230 kVActive
AH1-692Ladysmith CT 230 kVActive
AH1-694Ladysmith CT 230 kVActive
AH1-712Cunningham 500 kVActive
AH1-716Surry-Skiffes Creek 500kVActive
AH1-717Surry 230kVActive
AH1-723Cunningham 500 kVActive
V4-068Murphy's 34.5kVIn Service
Y1-086Morgans CornerIn Service
Z1-036WinFall-Chowan 230kVIn Service
Z2-027Pasquotank 34.5kVIn Service
Z2-044Whitakers 34.5kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with potential Affected System impacts. PJM initiates coordination with each Affected System Operator by providing a list of New Service Requests in the Cycle with potential impacts to their respective system. If the Affected System Operator indicates an Affected System Study is required, PJM will notify the Project Developer or Eligible Customer of the need for an Affected System Study. See below if any Affected System Operator requires a study for this project:

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

No cost allocated system reinforcements were identified for this project in the Phase I System Impact Study load flow analysis.

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2077
Title
Replace switches 29824 and 29825 at Bremo 230 kV
Description
Replace switches 29824 and 29825 at Bremo 230 kV
Total Cost ($USD)
$800,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-221 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-221 could receive cost allocation. Although AH1-221 may not presently have cost responsibility for this upgrade, AH1-221 is a potential Aggregate Pool Contributor.

FacilityContingency
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2076
Title
Replace wave trap 298 WT at Bremo 230 kV
Description
Replace wave trap 298 WT at Bremo 230 kV
Total Cost ($USD)
$400,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-221 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-221 could receive cost allocation. Although AH1-221 may not presently have cost responsibility for this upgrade, AH1-221 is a potential Aggregate Pool Contributor.

FacilityContingency
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2078
Title
Replace 2-636 ACSR line lead on line 298 at Bremo 230 kV
Description
Replace 2-636 ACSR line lead on line 298 at Bremo 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-221 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-221 could receive cost allocation. Although AH1-221 may not presently have cost responsibility for this upgrade, AH1-221 is a potential Aggregate Pool Contributor.

FacilityContingency
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2065
Title
Replace switches 219324 and 219325 at Bremo 230 kV
Description
Replace switches 219324 and 219325 at Bremo 230 kV
Total Cost ($USD)
$800,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-221 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-221 could receive cost allocation. Although AH1-221 may not presently have cost responsibility for this upgrade, AH1-221 is a potential Aggregate Pool Contributor.

FacilityContingency
6BREMODIST-6BREMO 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2067
Title
Replace 3 1/2" pipe line lead on line 2193 at Bremo 230 kV
Description
Replace 3 1/2" pipe line lead on line 2193 at Bremo 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-221 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-221 could receive cost allocation. Although AH1-221 may not presently have cost responsibility for this upgrade, AH1-221 is a potential Aggregate Pool Contributor.

FacilityContingency
6BREMODIST-6BREMO 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2066
Title
Replace 2-636 ACSR line lead on line 2193 at Bremo 230 kV
Description
Replace 2-636 ACSR line lead on line 2193 at Bremo 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-221 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-221 could receive cost allocation. Although AH1-221 may not presently have cost responsibility for this upgrade, AH1-221 is a potential Aggregate Pool Contributor.

FacilityContingency
6BREMODIST-6BREMO 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9220.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9220.0 / TC1-PH2-DOM-033
Title
Wreck and rebuild 15.42 miles of 230 kV Line #298 from Buckingham to Bremo Substations with twin bundled (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor.
Description
Wreck and rebuild 15.42 miles of 230 kV Line #298 from Buckingham to Bremo Substations with twin bundled (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor.
Total Cost ($USD)
$44,465,922
Allocated Cost ($USD)
$0
Time Estimate
42 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-221 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-221 could receive cost allocation. Although AH1-221 may not presently have cost responsibility for this upgrade, AH1-221 is a potential Aggregate Pool Contributor.

FacilityContingency
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line(Any)
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9221.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9221.0 / TC1-PH3-DOM-015-TC2
Title
Replace 230 kV Breaker 29822 at Bremo with a higher-rated device (Buckingham - Bremo).
Description
Replace 230 kV Breaker 29822 at Bremo with a higher-rated device (Buckingham - Bremo).
Total Cost ($USD)
$2,057,335
Allocated Cost ($USD)
$0
Time Estimate
38 to 39 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-221 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-221 could receive cost allocation. Although AH1-221 may not presently have cost responsibility for this upgrade, AH1-221 is a potential Aggregate Pool Contributor.

FacilityContingency
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9217.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9217.0 / TC1-PH2-DOM-028
Title
Wreck and rebuild 12.73 miles of 230 kV Line 298 from Buckingham to Farmville Substations with twin bundled (2) 768 ACSS/TW (20/7) "MAUMEE" conductor.
Description
Wreck and rebuild 12.73 miles of 230 kV Line 298 from Buckingham to Farmville Substations with twin bundled (2) 768 ACSS/TW (20/7) "MAUMEE" conductor.
Total Cost ($USD)
$40,414,822
Allocated Cost ($USD)
$0
Time Estimate
45 to 46 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-221 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-221 could receive cost allocation. Although AH1-221 may not presently have cost responsibility for this upgrade, AH1-221 is a potential Aggregate Pool Contributor.

FacilityContingency
6BUCKING-AH1-439 TP 230.0 kV Ckt 1 line(Any)
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line(Any)
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3694.8
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3694.8
Title
Partial wreck and rebuild 10.34 miles of 230 kV line #249 Carson-Locks to achieve a minimum summer emergency rating of 1572 MVA.
Description
Partial wreck and rebuild 10.34 miles of 230 kV line #249 Carson-Locks to achieve a minimum summer emergency rating of 1572 MVA. Upgrade terminal equipment at Carson and Locks to not limit the new conductor rating.
Cost Information
Time Estimate
May 03 2025

Not Contingent

Note: AH1-221 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-221 is not contingent on this baseline upgrade as it is already in-service.

FacilityContingency
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.319
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.319
Title
Reconductor 230kV Line #2002 Carson – Poe. New conductor has a summer rating of 1573 MVA.
Description
Reconductor 230kV Line #2002 Carson – Poe. New conductor has a summer rating of 1573 MVA.
Cost Information
Time Estimate
Mar 20 2030

Not Contingent

Note: AH1-221 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-221 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6CARSON-6POE 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.320
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.320
Title
At Carson substation, upgrade all line #2002 terminal equipment at Carson to 4000A. CCVTs will also be replaced due to aging.
Description
At Carson substation, upgrade all line #2002 terminal equipment at Carson to 4000A. CCVTs will also be replaced due to aging.
Cost Information
Time Estimate
Mar 20 2030

Not Contingent

Note: AH1-221 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-221 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6CARSON-6POE 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.321
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.321
Title
At Poe substation, upgrade all line #2002 terminal equipment at Carson to 4000A. CCVTs will also be replaced due to aging.
Description
At Poe substation, upgrade all line #2002 terminal equipment at Carson to 4000A. CCVTs will also be replaced due to aging.
Cost Information
Time Estimate
Mar 20 2030

Not Contingent

Note: AH1-221 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-221 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6CARSON-6POE 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9378.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9378.0 / TC1-PH3-DOM-010
Title
Replace existing 230/500 kV Carson transformer 2 with (4)-480 MVA single phase transformers.
Description
Replace Existing 230/500 kV Carson transformer 2 with (4)-480 MVA Single Phase transformers.
Total Cost ($USD)
$37,801,301
Allocated Cost ($USD)
$0
Time Estimate
Dec 31 2029

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-221 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-221 could receive cost allocation. Although AH1-221 may not presently have cost responsibility for this upgrade, AH1-221 is a potential Aggregate Pool Contributor.

FacilityContingency
6CARSON-8CARSON 230.0/500.0 kV Ckt 2 transformer(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2072
Title
Replace 2500 ACAR line lead on line 2028 at Charlottesville 230 kV
Description
Replace 2500 ACAR line lead on line 2028 at Charlottesville 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-221 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-221 could receive cost allocation. Although AH1-221 may not presently have cost responsibility for this upgrade, AH1-221 is a potential Aggregate Pool Contributor.

FacilityContingency
6CHARLVL-6MTEAGLE 230.0 kV Ckt 1 line(Any)

System Reinforcement: n7568
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n7568 / dom-369-TC2
Title
Wreck and rebuild 6.47 miles of 230 kV transmission line 2028 between Charlottesville and Mt. Eagle with (2) 768.2 ACSS/TW (20/7) ""Maumee"" @ 250C and replace line lead at Mt. Eagle.
Description
Wreck and rebuild 6.47 miles of 230 kV transmission line 2028 between Charlottesville and Mt. Eagle with (2) 768.2 ACSS/TW (20/7) ""Maumee"" @ 250C and replace line lead at Mt. Eagle.
Total Cost ($USD)
$36,802,018
Allocated Cost ($USD)
$0
Time Estimate
43 to 44 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-221 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-221 could receive cost allocation. Although AH1-221 may not presently have cost responsibility for this upgrade, AH1-221 is a potential Aggregate Pool Contributor.

FacilityContingency
6CHARLVL-6MTEAGLE 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2073
Title
Replace 2-1590 line lead on line 2028 at Charlottesville and Mt Eagle 230 kV
Description
Replace 2-1590 line lead on line 2028 at Charlottesville and Mt Eagle 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-221 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-221 could receive cost allocation. Although AH1-221 may not presently have cost responsibility for this upgrade, AH1-221 is a potential Aggregate Pool Contributor.

FacilityContingency
6CHARLVL-6MTEAGLE 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC1-PH3-DOM-007
Title
Replace Wave Trap 2028WT at Charlottesville
Description
Replace Wave Trap 2028WT at Charlottesville
Total Cost ($USD)
$400,000
Allocated Cost ($USD)
$0
Time Estimate
16 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-221 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-221 could receive cost allocation. Although AH1-221 may not presently have cost responsibility for this upgrade, AH1-221 is a potential Aggregate Pool Contributor.

FacilityContingency
6CHARLVL-6MTEAGLE 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.314
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.314
Title
Reconductor 230kV Line #2003 Chesterfield – Tyler segment. New conductor has a summer rating of 1573 MVA
Description
Reconductor 230kV Line #2003 Chesterfield – Tyler segment. New conductor has a summer rating of 1573 MVA
Cost Information
Time Estimate
Apr 22 2030

Not Contingent

Note: AH1-221 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-221 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6CHESTF B-6TYLER 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.317
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.317
Title
At Tyler substation, upgrade the necessary line terminal equipment to maintain 4000A at Tyler substation.
Description
At Tyler substation, upgrade the necessary line terminal equipment to maintain 4000A at Tyler substation.
Cost Information
Time Estimate
Apr 22 2030

Not Contingent

Note: AH1-221 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-221 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6CHESTF B-6TYLER 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9203.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9203.0 / TC1-PH2-DOM-008-TC2
Title
Wreck and rebuild 10.74 miles of line 2028 between Fork Union and Cunningham (Grape Vine) with (2) 768.2 ACSS/TW (20/7) "MAUMEE" @ 250C.
Description
Wreck and rebuild 10.74 miles of line 2028 between Fork Union and Cunningham (Grape Vine) with (2) 768.2 ACSS/TW (20/7) "MAUMEE" @ 250C.
Total Cost ($USD)
$29,539,973
Allocated Cost ($USD)
$0
Time Estimate
45 to 46 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-221 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-221 could receive cost allocation. Although AH1-221 may not presently have cost responsibility for this upgrade, AH1-221 is a potential Aggregate Pool Contributor.

FacilityContingency
6GRAPEVINE-6FORK UNION 230.0 kV Ckt 1 line(Any)

System Reinforcement: n7569
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n7569 / dom-490-TC2
Title
Upgrade a 3.78 mile segment of 230kV transmission line 2028 between Mt. Eagle and Grape Vine Substations at structure 2080/73.
Description
Uograde 3.78 miles of transmission line 2028 between Mt. Eagle and Grape Vine with (2) 768.2 ACSS/TW (20/7) ""MAUMEE"". The segment runs from Mt Eagle to structure 2080/73.
Total Cost ($USD)
$13,360,242
Allocated Cost ($USD)
$0
Time Estimate
43 to 44 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-221 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-221 could receive cost allocation. Although AH1-221 may not presently have cost responsibility for this upgrade, AH1-221 is a potential Aggregate Pool Contributor.

FacilityContingency
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9644.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9644.0 / TC1-PH3-DOM-006-TC2
Title
Upgrade a 2.73 mile segment of 230kV transmission line 2028 between Mt. Eagle and Grape Vine. This segment runs from Grape Vine substation to structure 2080/73.
Description
Rebuild a 2.73 mile segment of 230kV line 2028 between Mt. Eagle and Grape Vinew with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @250 degrees C.
Total Cost ($USD)
$8,415,380
Allocated Cost ($USD)
$0
Time Estimate
Mar 31 2029

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-221 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-221 could receive cost allocation. Although AH1-221 may not presently have cost responsibility for this upgrade, AH1-221 is a potential Aggregate Pool Contributor.

FacilityContingency
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2085
Title
Replace wavetrap 298WT at Farmville 230 kV
Description
Replace wavetrap 298WT at Farmville 230 kV
Total Cost ($USD)
$400,000
Allocated Cost ($USD)
$0
Time Estimate
16 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-221 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-221 could receive cost allocation. Although AH1-221 may not presently have cost responsibility for this upgrade, AH1-221 is a potential Aggregate Pool Contributor.

FacilityContingency
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0080
Title
Replace switch 219326 at Bremo 230 kV
Description
Replace switch 219326 at Bremo 230 kV
Total Cost ($USD)
$400,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-221 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-221 could receive cost allocation. Although AH1-221 may not presently have cost responsibility for this upgrade, AH1-221 is a potential Aggregate Pool Contributor.

FacilityContingency
6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2064
Title
Replace 2-1590 line lead on line 2193 at Fork Union 230 kV
Description
Replace 2-1590 line lead on line 2193 at Fork Union 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-221 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-221 could receive cost allocation. Although AH1-221 may not presently have cost responsibility for this upgrade, AH1-221 is a potential Aggregate Pool Contributor.

FacilityContingency
6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9199.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9199.0 / TC1-PH2-DOM-004
Title
Wreck and rebuild 1.63 miles of line 2193 between Fork Union and Bremo with (2) 768.2 ACSS/TW (20/7) "MAUMEE" @ 250C and replace line lead at Bremo.
Description
Wreck and rebuild 1.63 miles of line 2193 between Fork Union and Bremo with (2) 768.2 ACSS/TW (20/7) "MAUMEE" @ 250C and replace line lead at Bremo.
Total Cost ($USD)
$7,947,612
Allocated Cost ($USD)
$0
Time Estimate
42 to 43 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-221 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-221 could receive cost allocation. Although AH1-221 may not presently have cost responsibility for this upgrade, AH1-221 is a potential Aggregate Pool Contributor.

FacilityContingency
6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line(Any)
6BREMODIST-6BREMO 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2063
Title
Wreck and rebuild 0.11 miles of 230 kV line 2193 between Fork Union and Bremo Dist with (2) 768.2 ACSS/TW (20/7) "Maumee" @ 250C
Description
Wreck and rebuild 0.11 miles of 230 kV line 2193 between Fork Union and Bremo Dist with (2) 768.2 ACSS/TW (20/7) "Maumee" @ 250C
Total Cost ($USD)
$418,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-221 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-221 could receive cost allocation. Although AH1-221 may not presently have cost responsibility for this upgrade, AH1-221 is a potential Aggregate Pool Contributor.

FacilityContingency
6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9198.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9198.0 / TC1-PH2-DOM-003-TC2
Title
Replace Circuit Breaker 219322 and Circuit Breaker Lead at Bremo 230 kV (Bremo - Fork Union).
Description
Replace Circuit Breaker 219322 and Circuit Breaker Lead at Bremo 230 kV (Bremo - Fork Union).
Total Cost ($USD)
$2,113,879
Allocated Cost ($USD)
$0
Time Estimate
40 to 41 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-221 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-221 could receive cost allocation. Although AH1-221 may not presently have cost responsibility for this upgrade, AH1-221 is a potential Aggregate Pool Contributor.

FacilityContingency
6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line(Any)
6BREMODIST-6BREMO 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2070
Title
Replace wave trap 2028WT at Fork Union 230 kV
Description
Replace wave trap 2028WT at Fork Union 230 kV
Total Cost ($USD)
$400,000
Allocated Cost ($USD)
$0
Time Estimate
16 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-221 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-221 could receive cost allocation. Although AH1-221 may not presently have cost responsibility for this upgrade, AH1-221 is a potential Aggregate Pool Contributor.

FacilityContingency
6GRAPEVINE-6FORK UNION 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2068
Title
Wreck and rebuild 0.12 miles of 230 kV line 2028 between Fork Union and Grape Vine with (2) 768.2 ACSS/TW (20/7) "Maumee" @ 250C
Description
Wreck and rebuild 0.12 miles of 230 kV line 2028 between Fork Union and Grape Vine with (2) 768.2 ACSS/TW (20/7) "Maumee" @ 250C
Total Cost ($USD)
$456,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-221 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-221 could receive cost allocation. Although AH1-221 may not presently have cost responsibility for this upgrade, AH1-221 is a potential Aggregate Pool Contributor.

FacilityContingency
6GRAPEVINE-6FORK UNION 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2069
Title
Replace 2-1590 AAC line lead on line 2028 at Fork Union 230 kV
Description
Replace 2-1590 AAC line lead on line 2028 at Fork Union 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-221 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-221 could receive cost allocation. Although AH1-221 may not presently have cost responsibility for this upgrade, AH1-221 is a potential Aggregate Pool Contributor.

FacilityContingency
6GRAPEVINE-6FORK UNION 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2071
Title
Replace 2-1590 line lead on line 2028 at Mt. Eagle 230 kV
Description
Replace 2-1590 line lead on line 2028 at Mt. Eagle 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-221 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-221 could receive cost allocation. Although AH1-221 may not presently have cost responsibility for this upgrade, AH1-221 is a potential Aggregate Pool Contributor.

FacilityContingency
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9379.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9379.0 / TC1-PH3-DOM-011
Title
Replace existing 230/500 kV Transformer 1 at Midlothian with (4)-480 MVA Single Phase transformers.
Description
Replace existing 230/500 kV Transformer 1 at Midlothian with (4)-480 MVA Single Phase 500/230 kV transformers.
Total Cost ($USD)
$37,836,293
Allocated Cost ($USD)
$0
Time Estimate
Dec 31 2029

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-221 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-221 could receive cost allocation. Although AH1-221 may not presently have cost responsibility for this upgrade, AH1-221 is a potential Aggregate Pool Contributor.

FacilityContingency
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer(Any)

System Reinforcement: b4000.355
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.355
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-221 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-221 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
8HERITAGE-8RAWLINGS 500.0 kV Ckt 1 line(Any)
6CARSON-8CARSON 230.0/500.0 kV Ckt 1 transformer(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AH1-221 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-221 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
8HERITAGE-8RAWLINGS 500.0 kV Ckt 1 line(Any)
6CARSON-8CARSON 230.0/500.0 kV Ckt 1 transformer(Any)
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S

System Reinforcement: b4000.327
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.327
Title
Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.
Description
Upgrade/install equipment at Ladysmith substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230kV strings of breaker and a half scheme.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AH1-221 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-221 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
8HERITAGE-8RAWLINGS 500.0 kV Ckt 1 line(Any)
6CARSON-8CARSON 230.0/500.0 kV Ckt 1 transformer(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Kraken to accommodate the new 500kV line from North Anna to Kraken.
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-221 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-221 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
8HERITAGE-8RAWLINGS 500.0 kV Ckt 1 line(Any)
6CARSON-8CARSON 230.0/500.0 kV Ckt 1 transformer(Any)
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S

System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029

Not Contingent

Note: AH1-221 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-221 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
8HERITAGE-8RAWLINGS 500.0 kV Ckt 1 line(Any)
6CARSON-8CARSON 230.0/500.0 kV Ckt 1 transformer(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S

System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-221 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-221 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
8HERITAGE-8RAWLINGS 500.0 kV Ckt 1 line(Any)
6CARSON-8CARSON 230.0/500.0 kV Ckt 1 transformer(Any)
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AH1-221 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-221 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
8HERITAGE-8RAWLINGS 500.0 kV Ckt 1 line(Any)
6CARSON-8CARSON 230.0/500.0 kV Ckt 1 transformer(Any)
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AH1-221 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-221 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
8HERITAGE-8RAWLINGS 500.0 kV Ckt 1 line(Any)
6CARSON-8CARSON 230.0/500.0 kV Ckt 1 transformer(Any)
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AH1-221 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-221 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
8HERITAGE-8RAWLINGS 500.0 kV Ckt 1 line(Any)
6CARSON-8CARSON 230.0/500.0 kV Ckt 1 transformer(Any)
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S

System Reinforcement: b4000.325
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.325
Title
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Description
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AH1-221 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-221 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
8HERITAGE-8RAWLINGS 500.0 kV Ckt 1 line(Any)
6CARSON-8CARSON 230.0/500.0 kV Ckt 1 transformer(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Kraken substation into Yeat substation
Description
Cut-in 500kV line from Kraken substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-221 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-221 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
8HERITAGE-8RAWLINGS 500.0 kV Ckt 1 line(Any)
6CARSON-8CARSON 230.0/500.0 kV Ckt 1 transformer(Any)
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S

System Reinforcement: b4000.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.356
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-221 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-221 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
8HERITAGE-8RAWLINGS 500.0 kV Ckt 1 line(Any)
6CARSON-8CARSON 230.0/500.0 kV Ckt 1 transformer(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AH1-221 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-221 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
8HERITAGE-8RAWLINGS 500.0 kV Ckt 1 line(Any)
6CARSON-8CARSON 230.0/500.0 kV Ckt 1 transformer(Any)
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AH1-221 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-221 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
8HERITAGE-8RAWLINGS 500.0 kV Ckt 1 line(Any)
6CARSON-8CARSON 230.0/500.0 kV Ckt 1 transformer(Any)
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S

System Reinforcement: b4000.326
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.326
Title
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Description
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AH1-221 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-221 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
8HERITAGE-8RAWLINGS 500.0 kV Ckt 1 line(Any)
6CARSON-8CARSON 230.0/500.0 kV Ckt 1 transformer(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S

System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029

Not Contingent

Note: AH1-221 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-221 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
8HERITAGE-8RAWLINGS 500.0 kV Ckt 1 line(Any)
6CARSON-8CARSON 230.0/500.0 kV Ckt 1 transformer(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S

System Reinforcement: b4000.317
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.317
Title
At Tyler substation, upgrade the necessary line terminal equipment to maintain 4000A at Tyler substation.
Description
At Tyler substation, upgrade the necessary line terminal equipment to maintain 4000A at Tyler substation.
Cost Information
Time Estimate
Apr 22 2030

Not Contingent

Note: AH1-221 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-221 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6TYLER1-6POE 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.316
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.316
Title
At Poe substation, uprate all Line #2003 terminal equipment, line leads, and bus to be rated to 4000A.
Description
At Poe substation, uprate all Line #2003 terminal equipment, line leads, and bus to be rated to 4000A.
Cost Information
Time Estimate
Apr 22 2030

Not Contingent

Note: AH1-221 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-221 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6TYLER1-6POE 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.315
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.315
Title
Reconductor 230kV Line #2003 Tyler – Poe segment. New conductor has a summer rating of 1573 MVA.
Description
Reconductor 230kV Line #2003 Tyler – Poe segment. New conductor has a summer rating of 1573 MVA.
Cost Information
Time Estimate
Apr 22 2030

Not Contingent

Note: AH1-221 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-221 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6TYLER1-6POE 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-1036
Title
Wreck and rebuild 37.41 mi of 500 kV line 563 between Carson and Midlothian with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN" at 145 degrees C
Description
Wreck and rebuild 37.41 mi of 500 kV line 563 between Carson and Midlothian with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN" at 145 degrees C
Total Cost ($USD)
$157,122,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-221 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-221 could receive cost allocation. Although AH1-221 may not presently have cost responsibility for this upgrade, AH1-221 is a potential Aggregate Pool Contributor.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-1037
Title
Replace Breaker 56372 at Carson 500 kV with 5000 Amp device
Description
Replace Breaker 56372 at Carson 500 kV with 5000 Amp device
Total Cost ($USD)
$2,750,000
Allocated Cost ($USD)
$0
Time Estimate
42 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-221 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-221 could receive cost allocation. Although AH1-221 may not presently have cost responsibility for this upgrade, AH1-221 is a potential Aggregate Pool Contributor.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 562_SRT-S-1
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: 56272_SRT-S
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: 56272_SRT-S

System Reinforcement: n9139.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9139.0 / TC1-PH1-DOM-073
Title
Wreck and rebuild 37.41 miles of 500kV line 563 between Midlothian and Carson with (3) 1351.5 ACSR (45/7) "Dipper" and associated substation work.
Description
Wreck and rebuild 37.41 miles of 500kV transmission line 563 between Midlothian and Carson with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C and associated substation work to achieve new rating of 4356/4356/5009 MVA. Remove wave traps.
Total Cost ($USD)
$245,455,768
Allocated Cost ($USD)
$0
Time Estimate
69 to 70 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-221 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-221 could receive cost allocation. Although AH1-221 may not presently have cost responsibility for this upgrade, AH1-221 is a potential Aggregate Pool Contributor.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)

System Reinforcement: n9248.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9248.0 / TC1-PH2-DOM-042
Title
Construct new 41.13 mile line between North Anna and Midlothian with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN" at 145 degrees C. Station upgrades at North Anna and Midlothian to accommodate new line.
Description
Construct new 41.13 mile line between North Anna and Midlothian with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN" at 145 degrees C. Station upgrades at North Anna and Midlothian to accommodate new line.
Total Cost ($USD)
$345,766,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-221 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-221 could receive cost allocation. Although AH1-221 may not presently have cost responsibility for this upgrade, AH1-221 is a potential Aggregate Pool Contributor.

FacilityContingency
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 lineDVP_P4-2: 557T574_SRT-S
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 lineDVP_P1-2: LN 557_SRT-S

System Reinforcement: n9191.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9191.0 / TC1-PH1-DOM-090
Title
Rebuild 41.13 miles of line 576 between North Anna and Midlothian with triple bundled (3) 1351.5 ACSR (45/7) "Dipper" conductor and associated substation work.
Description
Rebuild 41.13 miles of line 576 between North Anna and Midlothian with triple bundled (3) 1351.5 ACSR (45/7) "Dipper" conductor at 110 degrees C and associated substation work to achieve new rating of 4356/4356/5009 MVA.
Total Cost ($USD)
$256,706,175
Allocated Cost ($USD)
$0
Time Estimate
74 to 75 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-221 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-221 could receive cost allocation. Although AH1-221 may not presently have cost responsibility for this upgrade, AH1-221 is a potential Aggregate Pool Contributor.

FacilityContingency
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)

System Reinforcement: n9250.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9250.0 / TC1-PH2-DOM-044
Title
Construct a new 22.59 mile line between Carson and Rawlings Substations.
Description
Construct a new 22.59 mile line between Carson and Rawlings Substations.
Total Cost ($USD)
$108,728,086
Allocated Cost ($USD)
$0
Time Estimate
60 to 61 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-221 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-221 could receive cost allocation. Although AH1-221 may not presently have cost responsibility for this upgrade, AH1-221 is a potential Aggregate Pool Contributor.

FacilityContingency
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-A
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-C
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51192_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51172_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 511T544_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51192_SRT-S
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51172_SRT-S
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 511T544_SRT-S
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51192_SRT-S
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51172_SRT-S
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 511T544_SRT-S

System Reinforcement: n9138.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9138.0 / TC1-PH1-DOM-070
Title
Wreck and rebuild 22.59 miles of Line #511 between Carson and Rawlings Substations with three (3) 1351 ACSS/TW and associated substation work.
Description
Wreck and rebuild 22.59 miles of Line 511 between Carson and Rawlings with three (3) 1351 ACSS/TW and associated substation work.
Total Cost ($USD)
$111,130,292
Allocated Cost ($USD)
$0
Time Estimate
60 to 61 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-221 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-221 could receive cost allocation. Although AH1-221 may not presently have cost responsibility for this upgrade, AH1-221 is a potential Aggregate Pool Contributor.

FacilityContingency
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-A
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-C
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51192_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51172_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 511T544_SRT-S
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51192_SRT-S
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51172_SRT-S
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 511T544_SRT-S
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51192_SRT-S
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51172_SRT-S
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 511T544_SRT-S

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0075
Title
Wreck and rebuild 18.75 miles of 500 kV Line 594 between Spotsylvania and Morrisville with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN"
Description
Wreck and rebuild 18.75 miles of 500 kV Line 594 between Spotsylvania and Morrisville with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN"
Total Cost ($USD)
$110,625,000
Allocated Cost ($USD)
$0
Time Estimate
18 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-221 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-221 could receive cost allocation. Although AH1-221 may not presently have cost responsibility for this upgrade, AH1-221 is a potential Aggregate Pool Contributor.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P2-2: MORRISVILLE B1_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P4-2: 545T552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 581_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P4-2: H1T552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P4-2: H3T552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 550_SRT-A

Attachments

AH1-221 One Line Diagram

AH1-221 One Line Diagram.pdf
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.