AH1-699 Phase I Study Report

v1.00 released 2025-10-29 21:27

Wellsville 345 kV

69.0 MW Capacity / 58.0 MW Energy

Introduction

This Phase I System Impact Study Report (PH1) has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, sections 307 and 308 for New Service Requests (projects) in Transition Cycle 2. The Project Developer/Eligible Customer (developer) is South Field Energy LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is American Transmission Systems, Incorporated.

Preface

The Phase I System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle executive summary format and (ii) an individual project-level basis. The Phase I System Impact Study Results (for both the executive summary and individual reports) will be publicly available on PJM’s website. Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.3, PJM takes the following actions during the Phase I System Impact Study:
  1. PJM studies each New Service Request on a summer peak, winter peak and light load RTEP base case study. The case year is dependent on the new services cycle under study. PJM will identify the base case year to be used in the study of a specific cycle on its website.
  2. PJM will only perform load flow analysis during the Phase I System Impact Study.
  3. In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with Affected System impacts and provides each Affected System Operator with a list of New Service Request in the Cycle with potential impacts to their respective system.
  4. PJM will create both the short circuit and stability base cases to be used in the Phase II System Impact Study.
  5. The Phase I System Impact Study results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.
The Transmission Owner takes the following actions during the Phase I System Impact Study:
  1. Identify required Interconnection Facilities to accommodate the New Service Request.
  2. Identify required Network Upgrades to mitigate system violations from the Phase I System Impact Study.
  3. Provide planning-level preliminary estimates of Interconnection Facilities and Network Upgrades including scope, cost and elapsed time to complete the work.

Decision Point I Requirements

At the close of Phase I System Impact Study, PJM will initiate Decision Point I (DP1). During DP1, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.A.1. Additional information on these elements is available in PJM Manual 14H sections 4.4, 6, and 7.

Allowable project modifications at Decision Point I are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

General

The Project Developer has proposed an uprate to a planned/existing Natural Gas facility located in the American Transmission Systems, Incorporated zone — Columbiana County, Ohio. This project is an increase to the developer’s AA1-123 project(s), which will share the same Point of Interconnection. The AH1-699 project is a 58.0 MW uprate (69.0 MW Capacity uprate) to the previous project(s). The total installed facilities will have a capability of 1210.0 MW with 1174.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AH1-699
Project Name:
Wellsville 345 kV
Project Developer Name:
South Field Energy LLC
State:
Ohio
County:
Columbiana
Transmission Owner:
American Transmission Systems, Incorporated
MFO:
1210.0
MWE:
58.0
MWC:
69.0
Fuel Type:
Natural Gas
Basecase Study Year:
2028

Physical Interconnection Facility Study

Physical Interconnection Facilities Study is not performed as part of the Phase I System Impact Study. Physical Interconnection Facilities Study will commence in the Phase II System Impact Study.

Point of Interconnection

AH1-699 will interconnect on the American Transmission Systems, Incorporated transmission system at the Wellsville 345 kV substation as an uprate to AA1-123. 

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In the Phase I SIS, the costs shown are subject to change as a result of a facility study performed by the TO during the Phase II or Phase III System Impact Study.

Based on the Phase I SIS results, the AH1-699 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit are also shown below.

Cost Summary
DescriptionCost Allocated to AH1-699Cost Subject to Readiness*
Transmission Owner Interconnection Facilities (TOIF)$58,800$0
Other Scope$7,000$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0
Network Upgrades$49,000$49,000
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$0$0
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$0$0
Total$114,800$49,000

* Contributes to calculation for Readiness Deposit #2 (RD2). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 309 (Decision Point I) A.1.a.i and PJM Manual 14H, section 6.2, Readiness Deposit #2 (RD2) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point I (DP1), the Project Developer or Eligible Customer is required to submit Readiness Deposit #2, which is calculated as 10% of cost allocation for required Phase I Network Upgrades minus Readiness Deposit #1.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Readiness Deposit #2 Due for Project AH1-699

Readiness Deposit #2 has been calculated for the project based on the Phase I System Impact Study results and is shown in the table below. This Readiness Deposit #2 must be provided at Decision Point I through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit
Project ID10% of cost allocation for Phase I Network UpgradesReadiness Deposit #1 Received (RD1)Readiness Deposit #2 (RD2) for AH1-699 Project due at DP1
ABA - B
AH1-699$4,900$276,000$0

Note: Failure to provide an acceptable form of Readiness Deposit #2 by the end of Decision Point I will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Interconnection Facilities
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)Integrate Interconnection Facilities protection and controls to the Transmission Owner system.$58,800 $58,800
Network Upgrades
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)Revise relay settings at Wellsville substation as required.$49,000 $49,000
Physical Interconnection
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)Support for existing revenue metering coordination.$7,000 $7,000

Based on the scope of work for the Interconnection Facilities, it is expected to take 9 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

The schedule for any required Network Impact Reinforcements will be more clearly identified in the Phase II and Phase III System Impact Studies.

Transmission Owner Analysis

FE performed an analysis of its underlying transmission system <100 kV system. New Service Request Project AH1-699 did not contribute to any overloads on the FE transmission <100 kV system.

 

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. FirstEnergy interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AH1-699 was evaluated as a 58.0 MW (69.0 MW Capacity) injection in the ATSI area.

AH1-699 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 1210.0 MW (58.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AP
01HARRSN-01PRNTY 500.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT6_SRT-SL
BreakerAC104.19 %3792.0B3950.776.98
GD2AP
01HARRSN-01PRNTY 500.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT9_SRT-SL
BreakerAC104.01 %3792.0B3943.97.03
GD2AP
01HARRSN-01PRNTY 500.0 kV Ckt 1 line
AP_P1-2_MP-500-022_SRT-A
SingleAC103.61 %3792.0B3929.016.98

Details for 01HARRSN-01PRNTY 500.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT6_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01HARRSN-01PRNTY 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT6_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.19 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:3950.77
MW Contribution:6.98
Bus #Bus NameTypeMW Contribution
23546401DTGZ2-030
Solar/Wind Helper
0.09
23585401KL_K28_T16
Solar/Wind Helper
1.427
23750701CROSSCHOOL
Solar/Wind Helper
1.319
23751201ROTHROCK
Solar/Wind Helper
0.825
23562501BACKB
Solar/Wind Helper
1.009
23777901MDS_W4-102
Solar/Wind Helper
0.149
23908902SAMMG5
Adder
21.019
23909002SAMMG6
Adder
26.274
23909102SAMMG7
Adder
26.274
3141426STAFORD
Solar/Wind Helper
0.05
235020AA1-095 C
Solar/Wind Helper
0.044
23558501HARRN1
50/50
18.438
23558601HARRN2
50/50
18.438
23558701HARRN3
50/50
18.438
23559001PLEAS1
50/50
7.018
23559101PLEAS2
50/50
7.018
23684101S70BUS1
50/50
0.194
23684201S70BUS2
50/50
0.198
237034AC2-136 C
Solar/Wind Helper
0.189
237038AE2-054 C
Solar/Wind Helper
0.225
3141196NOKESVL
Solar/Wind Helper
0.971
316411AF1-147_GEN1
Solar/Wind Helper
0.814
316415AF1-147_GEN2
Solar/Wind Helper
0.814
23751101LEADS_P59
Solar/Wind Helper
1.587
235062AE1-101 C1
Solar/Wind Helper
1.363
3132123MT JACKSON
Solar/Wind Helper
0.749
238185AF2-356 C
Solar/Wind Helper
2.412
237080AD1-060 GEN
Solar/Wind Helper
0.284
235067AD1-061 GEN
Solar/Wind Helper
0.41
237001AB1-127_GEN
Solar/Wind Helper
0.363
237002AB1-128_GEN
Solar/Wind Helper
0.365
238152AF2-075_GEN
Solar/Wind Helper
0.709
238149AF1-291A_GEN
Solar/Wind Helper
0.142
238175AF1-290_GEN
Solar/Wind Helper
0.137
238221AF1-254 C O1
Solar/Wind Helper
0.228
238208AF1-136 C
Solar/Wind Helper
0.185
238120AE2-309 GEN
Solar/Wind Helper
0.47
238147AE2-230_GEN1
Solar/Wind Helper
0.496
238148AE2-230_GEN2
Solar/Wind Helper
0.498
238169AE2-226 GEN1
Solar/Wind Helper
0.648
238170AE2-226 GEN2
Solar/Wind Helper
0.648
238108AE1-109 GEN1
Solar/Wind Helper
0.102
238109AE1-109 GEN2
Solar/Wind Helper
0.102
238110AE1-109 GEN3
Solar/Wind Helper
0.102
235063AE1-101 C2
Solar/Wind Helper
1.363
237085AD2-009_GEN
Solar/Wind Helper
1.363
235054AD2-180 GEN
Solar/Wind Helper
1.912
315651AD1-115 GEN
Solar/Wind Helper
0.774
237061AD1-155 GEN
Solar/Wind Helper
0.054
235531U2-073 GEN
Solar/Wind Helper
2.932
23583801GRNGAP
Solar/Wind Helper
6.238
316447AC1-158 HLD
Solar/Wind Helper
2.799
316044AC1-158 PL1
Solar/Wind Helper
1.272
316045AC1-158 PL2
Solar/Wind Helper
4.07
316450AC1-158 RIC
Solar/Wind Helper
0.339
226929AD2-058 GEN
Solar/Wind Helper
0.087
238127S14_GEN_2
Solar/Wind Helper
0.739
238126S14_GEN_1
Solar/Wind Helper
0.739
238117U2-030
Solar/Wind Helper
0.306
238118U2-030_1
Solar/Wind Helper
0.306
241859AE2-194_GEN
Solar/Wind Harmer
13.418
316006AB2-029 C
Solar/Wind Helper
0.113
316254AC1-120 GEN1
Solar/Wind Helper
1.051
316170AC1-121 GEN2
Solar/Wind Helper
0.35
316164AC1-076 GEN
Solar/Wind Helper
1.086
3138216PACIFIC
Solar/Wind Helper
0.04
316095T157 G97
Solar/Wind Helper
1.645
316097T157 G90
Solar/Wind Helper
1.645
970935AG2-582 GEN
50/50
814.67
964991AG1-363 GEN
Solar/Wind Helper
3.934
972001AH1-545 GEN
Solar/Wind Harmer
19.946
972229AH1-699 GEN
Adder
6.976
CBM West 1LTFEXP_CBM-W1->PJM
CBM
76.715
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.962
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.619
NYPJM->LTFIMP_NY
CLTF
2.516
LGEELTFEXP_LGEE->PJM
CLTF
3.38
WECLTFEXP_WEC->PJM
CLTF
1.942
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.848
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.069
TVALTFEXP_TVA->PJM
CLTF
3.017
MECLTFEXP_MEC->PJM
CLTF
7.849
LAGNLTFEXP_LAGN->PJM
CLTF
6.222
SIGELTFEXP_SIGE->PJM
CLTF
0.25
AG2-052LTFEXP_AG2-052->PJM
LTF
0.124
AH1-155LTFEXP_AH1-155->PJM
LTF
0.185

Details for 01HARRSN-01PRNTY 500.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT9_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01HARRSN-01PRNTY 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT9_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.01 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:3943.9
MW Contribution:7.03
Bus #Bus NameTypeMW Contribution
23546401DTGZ2-030
Solar/Wind Helper
0.09
23585401KL_K28_T16
Solar/Wind Helper
1.384
23750701CROSSCHOOL
Solar/Wind Helper
1.298
23751201ROTHROCK
Solar/Wind Helper
0.798
23562501BACKB
Solar/Wind Helper
0.976
23777901MDS_W4-102
Solar/Wind Helper
0.149
23908902SAMMG5
Adder
21.162
23909002SAMMG6
Adder
26.452
23909102SAMMG7
Adder
26.452
3141426STAFORD
Solar/Wind Helper
0.05
235020AA1-095 C
Solar/Wind Helper
0.045
23558501HARRN1
50/50
18.452
23558601HARRN2
50/50
18.452
23558701HARRN3
50/50
18.452
23559001PLEAS1
50/50
7.034
23559101PLEAS2
50/50
7.034
23684101S70BUS1
50/50
0.195
23684201S70BUS2
50/50
0.199
3147983MERCK5
Solar/Wind Helper
0.089
237034AC2-136 C
Solar/Wind Helper
0.19
237038AE2-054 C
Solar/Wind Helper
0.226
3141196NOKESVL
Solar/Wind Helper
0.976
316411AF1-147_GEN1
Solar/Wind Helper
0.819
316415AF1-147_GEN2
Solar/Wind Helper
0.819
23751101LEADS_P59
Solar/Wind Helper
1.548
235062AE1-101 C1
Solar/Wind Helper
1.366
3132123MT JACKSON
Solar/Wind Helper
0.753
3132273ORANGE
Solar/Wind Helper
0.045
238185AF2-356 C
Solar/Wind Helper
2.359
237080AD1-060 GEN
Solar/Wind Helper
0.284
235067AD1-061 GEN
Solar/Wind Helper
0.411
237001AB1-127_GEN
Solar/Wind Helper
0.364
237002AB1-128_GEN
Solar/Wind Helper
0.366
238152AF2-075_GEN
Solar/Wind Helper
0.712
238149AF1-291A_GEN
Solar/Wind Helper
0.142
238175AF1-290_GEN
Solar/Wind Helper
0.138
238221AF1-254 C O1
Solar/Wind Helper
0.229
238208AF1-136 C
Solar/Wind Helper
0.185
238120AE2-309 GEN
Solar/Wind Helper
0.461
238147AE2-230_GEN1
Solar/Wind Helper
0.498
238148AE2-230_GEN2
Solar/Wind Helper
0.5
238169AE2-226 GEN1
Solar/Wind Helper
0.651
238170AE2-226 GEN2
Solar/Wind Helper
0.651
238108AE1-109 GEN1
Solar/Wind Helper
0.101
238109AE1-109 GEN2
Solar/Wind Helper
0.101
238110AE1-109 GEN3
Solar/Wind Helper
0.101
235063AE1-101 C2
Solar/Wind Helper
1.366
237085AD2-009_GEN
Solar/Wind Helper
1.365
235054AD2-180 GEN
Solar/Wind Helper
1.864
315651AD1-115 GEN
Solar/Wind Helper
0.779
237061AD1-155 GEN
Solar/Wind Helper
0.055
235531U2-073 GEN
Solar/Wind Helper
2.855
23583801GRNGAP
Solar/Wind Helper
6.269
316447AC1-158 HLD
Solar/Wind Helper
2.814
316044AC1-158 PL1
Solar/Wind Helper
1.278
316045AC1-158 PL2
Solar/Wind Helper
4.092
316450AC1-158 RIC
Solar/Wind Helper
0.341
226929AD2-058 GEN
Solar/Wind Helper
0.087
238127S14_GEN_2
Solar/Wind Helper
0.724
238126S14_GEN_1
Solar/Wind Helper
0.724
238117U2-030
Solar/Wind Helper
0.296
238118U2-030_1
Solar/Wind Helper
0.296
241859AE2-194_GEN
Solar/Wind Harmer
13.505
316006AB2-029 C
Solar/Wind Helper
0.114
316254AC1-120 GEN1
Solar/Wind Helper
1.056
316170AC1-121 GEN2
Solar/Wind Helper
0.352
316164AC1-076 GEN
Solar/Wind Helper
1.092
3138216PACIFIC
Solar/Wind Helper
0.041
316095T157 G97
Solar/Wind Helper
1.653
316097T157 G90
Solar/Wind Helper
1.653
970935AG2-582 GEN
50/50
815.909
227287AC2-120 GEN
Solar/Wind Helper
0.302
964991AG1-363 GEN
Solar/Wind Helper
3.954
972001AH1-545 GEN
Solar/Wind Harmer
20.073
972229AH1-699 GEN
Adder
7.026
CBM West 1LTFEXP_CBM-W1->PJM
CBM
76.913
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.04
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.633
NYPJM->LTFIMP_NY
CLTF
2.514
LGEELTFEXP_LGEE->PJM
CLTF
3.387
WECLTFEXP_WEC->PJM
CLTF
1.946
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.858
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.073
TVALTFEXP_TVA->PJM
CLTF
3.019
MECLTFEXP_MEC->PJM
CLTF
7.864
LAGNLTFEXP_LAGN->PJM
CLTF
6.227
SIGELTFEXP_SIGE->PJM
CLTF
0.251
AG2-052LTFEXP_AG2-052->PJM
LTF
0.124
AH1-155LTFEXP_AH1-155->PJM
LTF
0.186

Details for 01HARRSN-01PRNTY 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-022_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01HARRSN-01PRNTY 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-022_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.61 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:3929.01
MW Contribution:6.98
Bus #Bus NameTypeMW Contribution
23546401DTGZ2-030
Solar/Wind Helper
0.09
23585401KL_K28_T16
Solar/Wind Helper
1.427
23750701CROSSCHOOL
Solar/Wind Helper
1.319
23751201ROTHROCK
Solar/Wind Helper
0.825
23562501BACKB
Solar/Wind Helper
1.009
23777901MDS_W4-102
Solar/Wind Helper
0.149
23908902SAMMG5
Adder
21.019
23909002SAMMG6
Adder
26.274
23909102SAMMG7
Adder
26.274
3141426STAFORD
Solar/Wind Helper
0.05
235020AA1-095 C
Solar/Wind Helper
0.044
23558501HARRN1
50/50
18.438
23558601HARRN2
50/50
18.438
23558701HARRN3
50/50
18.438
23559001PLEAS1
50/50
7.018
23559101PLEAS2
50/50
7.018
23684101S70BUS1
50/50
0.194
23684201S70BUS2
50/50
0.198
237034AC2-136 C
Solar/Wind Helper
0.189
237038AE2-054 C
Solar/Wind Helper
0.225
3141196NOKESVL
Solar/Wind Helper
0.971
316411AF1-147_GEN1
Solar/Wind Helper
0.814
316415AF1-147_GEN2
Solar/Wind Helper
0.814
23751101LEADS_P59
Solar/Wind Helper
1.587
235062AE1-101 C1
Solar/Wind Helper
1.363
3132123MT JACKSON
Solar/Wind Helper
0.749
238185AF2-356 C
Solar/Wind Helper
2.412
237080AD1-060 GEN
Solar/Wind Helper
0.284
235067AD1-061 GEN
Solar/Wind Helper
0.41
237001AB1-127_GEN
Solar/Wind Helper
0.363
237002AB1-128_GEN
Solar/Wind Helper
0.365
238152AF2-075_GEN
Solar/Wind Helper
0.709
238149AF1-291A_GEN
Solar/Wind Helper
0.142
238175AF1-290_GEN
Solar/Wind Helper
0.137
238221AF1-254 C O1
Solar/Wind Helper
0.228
238208AF1-136 C
Solar/Wind Helper
0.185
238120AE2-309 GEN
Solar/Wind Helper
0.47
238147AE2-230_GEN1
Solar/Wind Helper
0.496
238148AE2-230_GEN2
Solar/Wind Helper
0.498
238169AE2-226 GEN1
Solar/Wind Helper
0.648
238170AE2-226 GEN2
Solar/Wind Helper
0.648
238108AE1-109 GEN1
Solar/Wind Helper
0.102
238109AE1-109 GEN2
Solar/Wind Helper
0.102
238110AE1-109 GEN3
Solar/Wind Helper
0.102
235063AE1-101 C2
Solar/Wind Helper
1.363
237085AD2-009_GEN
Solar/Wind Helper
1.363
235054AD2-180 GEN
Solar/Wind Helper
1.912
315651AD1-115 GEN
Solar/Wind Helper
0.774
237061AD1-155 GEN
Solar/Wind Helper
0.054
235531U2-073 GEN
Solar/Wind Helper
2.932
23583801GRNGAP
Solar/Wind Helper
6.238
316447AC1-158 HLD
Solar/Wind Helper
2.799
316044AC1-158 PL1
Solar/Wind Helper
1.272
316045AC1-158 PL2
Solar/Wind Helper
4.07
316450AC1-158 RIC
Solar/Wind Helper
0.339
226929AD2-058 GEN
Solar/Wind Helper
0.087
238127S14_GEN_2
Solar/Wind Helper
0.739
238126S14_GEN_1
Solar/Wind Helper
0.739
238117U2-030
Solar/Wind Helper
0.306
238118U2-030_1
Solar/Wind Helper
0.306
241859AE2-194_GEN
Solar/Wind Harmer
9.039
316006AB2-029 C
Solar/Wind Helper
0.113
316254AC1-120 GEN1
Solar/Wind Helper
1.051
316170AC1-121 GEN2
Solar/Wind Helper
0.35
316164AC1-076 GEN
Solar/Wind Helper
1.086
3138216PACIFIC
Solar/Wind Helper
0.04
316095T157 G97
Solar/Wind Helper
1.645
316097T157 G90
Solar/Wind Helper
1.645
970935AG2-582 GEN
50/50
814.67
964991AG1-363 GEN
Solar/Wind Helper
3.934
972001AH1-545 GEN
Solar/Wind Harmer
2.319
972229AH1-699 GEN
Adder
6.976
CBM West 1LTFEXP_CBM-W1->PJM
CBM
76.715
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.962
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.619
NYPJM->LTFIMP_NY
CLTF
2.516
LGEELTFEXP_LGEE->PJM
CLTF
3.38
WECLTFEXP_WEC->PJM
CLTF
1.942
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.848
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.069
TVALTFEXP_TVA->PJM
CLTF
3.017
MECLTFEXP_MEC->PJM
CLTF
7.849
LAGNLTFEXP_LAGN->PJM
CLTF
6.222
SIGELTFEXP_SIGE->PJM
CLTF
0.25
AG2-052LTFEXP_AG2-052->PJM
LTF
0.124
AH1-155LTFEXP_AH1-155->PJM
LTF
0.185
CONTINGENCY 'AP_P2-3_WP-500-DRT6_SRT-SL'
 OPEN BRANCH FROM BUS 235111 TO BUS 235107 CKT 1                /*01 502 J     500.0 - 01HARRSN     500.0
 SET POSTCONTRATING 4289 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3546 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3753 BRANCH FROM BUS 235111 TO BUS 235098 CKT 1 /*01 502 J     500.0 - WOODSIDE     500.0
END
CONTINGENCY 'AP_P2-3_WP-500-DRT9_SRT-SL'
 OPEN BRANCH FROM BUS 235111 TO BUS 235107 CKT 1                /*01 502 J     500.0 - 01HARRSN     500.0
 OPEN BRANCH FROM BUS 235111 TO BUS 235113 CKT 2                /*01 502 J     500.0 - 01 502JCT    138.0
 SET POSTCONTRATING 4289 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3546 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3753 BRANCH FROM BUS 235111 TO BUS 235098 CKT 1 /*01 502 J     500.0 - WOODSIDE     500.0
END
CONTINGENCY 'AP_P1-2_MP-500-022_SRT-A'
 DISCONNECT BRANCH FROM BUS 235107 TO BUS 235111 CKT 1   /*01HARRSN     500.0 - 01 502 J     500.0
END
235107 to 235112 ckt 1

Winter Peak Analysis

The New Service Request AH1-699 was evaluated as a 58.0 MW (69.0 MW Capacity) injection in the ATSI area.

AH1-699 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 1210.0 MW (58.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

(No impacts were found for this analysis)

Light Load Analysis

The New Service Request AH1-699 was evaluated as a 58.0 MW injection

AH1-699 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 1210.0 MW (58.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

(No impacts were found for this analysis)

Short Circuit Analysis

Short Circuit analysis is not performed as part of the Phase I System Impact Study. Short Circuit analysis will commence in the Phase II System Impact Study.

Stability Analysis

Stability analysis is not performed as part of the Phase I System Impact Study. Stability analysis will commence in the Phase II System Impact Study.

Reactive Power Analysis

Reactive Power analysis is not performed as part of the Phase I System Impact Study. Reactive Power analysis will commence in the Phase II System Impact Study.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-095Halfway-Marlowe 34.5kVIn Service
AB1-127St. Thomas-Guilford 34.5kVIn Service
AB1-128St. Thomas-Mercersburg 34.5kVIn Service
AB2-029Remington 34.5kVIn Service
AC1-076Locust Grove-Paytes 115kVIn Service
AC1-120Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-121Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-158Spotsylvania 500kVIn Service
AC2-120Ripley 69kVIn Service
AC2-136East Hagerstown 12kVUnder Construction
AD1-060Mercersburg-Milnor 34.5 kVIn Service
AD1-061McConnelsburg-Mercersburg 34 kVIn Service
AD1-115Mountain Run-Mitchell 115 kVEngineering & Procurement
AD1-155Meadow Brook-Strasburg 138 kVIn Service
AD2-009McConnellsburg 138 kVIn Service
AD2-058St. Barnabas 13 kVIn Service
AD2-180Elk Garden-Parr Run 138kVIn Service
AE1-101McConnellsburg-Texas Eastern 138 kVIn Service
AE1-109Frenchs Mill 34 kVIn Service
AE2-054Warfordsburg 34 kVIn Service
AE2-194Congress-Toronto 138 kVSuspended
AE2-226Millville-Old Chapel 138 kVEngineering & Procurement
AE2-230Bartonsville-Meadow Brook 138 kVIn Service
AE2-309Carlos Junction-Lonaconing 34.5 kVIn Service
AF1-136Warfordsburg-Purcell Junction 34.5 kVEngineering & Procurement
AF1-147Poland Rd-Runway DP 230kVUnder Construction
AF1-254Milnor-Huyetts 34.5 kVUnder Construction
AF1-290Feagans Mill-Millville 138 kVIn Service
AF1-291ABartonsville-Meadow Brook 138 kVIn Service
AF2-075Bartonsville-Meadow Brook 138 kV IIIIn Service
AF2-356Albright-Mt. Zion 138 kVUnder Construction
AG1-363Black Oak-Hatfield 500 kVEngineering & Procurement
AG2-582Flint Run 500 kVActive
AH1-545Wylie Ridge-Tidd 345kVActive
U2-030Four Mile Ridge Wind 138kVIn Service
U2-073Frostburg 138kV IIIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with potential Affected System impacts. PJM initiates coordination with each Affected System Operator by providing a list of New Service Requests in the Cycle with potential impacts to their respective system. If the Affected System Operator indicates an Affected System Study is required, PJM will notify the Project Developer or Eligible Customer of the need for an Affected System Study. See below if any Affected System Operator requires a study for this project:

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

No cost allocated system reinforcements were identified for this project in the Phase I System Impact Study load flow analysis.

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: s3191.1
Type
Load Flow
TO
APS
RTEP ID / TO ID
s3191.1 / APS-2023-056
Title
Harrison – Pruntytown 500 kV Misoperation Relays (Projected ISD by end of 2025)
Description
- Replace wave trap, line metering and relaying at Harrison Substation- - Replace wave trap, line metering and relaying at Pruntytown Substation
Cost Information
Time Estimate
Dec 31 2024

Not Contingent

Note: AH1-699 contributes to the loading of an overloaded facility that is being mitigated by a planned supplemental project. AH1-699 is not contingent on this supplemental project as it is already in-service.

FacilityContingency
01HARRSN-01PRNTY 500.0 kV Ckt 1 line(Any)

Attachments

AH1-699 One Line Diagram

AH1-699 One Line Diagram.pdf
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.