AH1-713 Phase I Study Report

v1.00 released 2025-10-29 21:26

Mt. Storm 500kV

14.0 MW Capacity / 0.0 MW Energy

Introduction

This Phase I System Impact Study Report (PH1) has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, sections 307 and 308 for New Service Requests (projects) in Transition Cycle 2. The Project Developer/Eligible Customer (developer) is Virginia Electric and Power Company (d/b/a) Dominion Energy Virginia, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Virginia Electric and Power Company (d/b/a Dominion Energy Virginia).

Preface

The Phase I System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle executive summary format and (ii) an individual project-level basis. The Phase I System Impact Study Results (for both the executive summary and individual reports) will be publicly available on PJM’s website. Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.3, PJM takes the following actions during the Phase I System Impact Study:
  1. PJM studies each New Service Request on a summer peak, winter peak and light load RTEP base case study. The case year is dependent on the new services cycle under study. PJM will identify the base case year to be used in the study of a specific cycle on its website.
  2. PJM will only perform load flow analysis during the Phase I System Impact Study.
  3. In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with Affected System impacts and provides each Affected System Operator with a list of New Service Request in the Cycle with potential impacts to their respective system.
  4. PJM will create both the short circuit and stability base cases to be used in the Phase II System Impact Study.
  5. The Phase I System Impact Study results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.
The Transmission Owner takes the following actions during the Phase I System Impact Study:
  1. Identify required Interconnection Facilities to accommodate the New Service Request.
  2. Identify required Network Upgrades to mitigate system violations from the Phase I System Impact Study.
  3. Provide planning-level preliminary estimates of Interconnection Facilities and Network Upgrades including scope, cost and elapsed time to complete the work.

Decision Point I Requirements

At the close of Phase I System Impact Study, PJM will initiate Decision Point I (DP1). During DP1, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.A.1. Additional information on these elements is available in PJM Manual 14H sections 4.4, 6, and 7.

Allowable project modifications at Decision Point I are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

General

The Project Developer has proposed a Coal generating facility located in the Virginia Electric and Power Company (d/b/a Dominion Energy Virginia) zone — Grant County, West Virginia. The installed facilities will have a total capability of 538.0 MW with 14.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AH1-713
Project Name:
Mt. Storm 500kV
Project Developer Name:
Virginia Electric and Power Company (d/b/a) Dominion Energy Virginia
State:
West Virginia
County:
Grant
Transmission Owner:
Virginia Electric and Power Company (d/b/a Dominion Energy Virginia)
MFO:
538.0
MWE:
0.0
MWC:
14.0
Fuel Type:
Coal
Basecase Study Year:
2028

Physical Interconnection Facility Study

Physical Interconnection Facilities Study is not performed as part of the Phase I System Impact Study. Physical Interconnection Facilities Study will commence in the Phase II System Impact Study.

Point of Interconnection

AH1-713 will interconnect on the Virginia Electric and Power Company (d/b/a Dominion Energy Virginia) transmission system at the Mt. Storm 500 kV Substation.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In the Phase I SIS, the costs shown are subject to change as a result of a facility study performed by the TO during the Phase II or Phase III System Impact Study.

Based on the Phase I SIS results, the AH1-713 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit are also shown below.

Cost Summary
DescriptionCost Allocated to AH1-713Cost Subject to Readiness*
Transmission Owner Interconnection Facilities (TOIF)$0$0
Other Scope$0$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0
Network Upgrades$0$0
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$0$0
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$0$0
Total$0$0

* Contributes to calculation for Readiness Deposit #2 (RD2). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 309 (Decision Point I) A.1.a.i and PJM Manual 14H, section 6.2, Readiness Deposit #2 (RD2) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point I (DP1), the Project Developer or Eligible Customer is required to submit Readiness Deposit #2, which is calculated as 10% of cost allocation for required Phase I Network Upgrades minus Readiness Deposit #1.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Readiness Deposit #2 Due for Project AH1-713

Readiness Deposit #2 has been calculated for the project based on the Phase I System Impact Study results and is shown in the table below. This Readiness Deposit #2 must be provided at Decision Point I through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit
Project ID10% of cost allocation for Phase I Network UpgradesReadiness Deposit #1 Received (RD1)Readiness Deposit #2 (RD2) for AH1-713 Project due at DP1
ABA - B
AH1-713$0$56,000$0

Note: Failure to provide an acceptable form of Readiness Deposit #2 by the end of Decision Point I will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Interconnection Facilities
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)AH1-713 is sharing a POI and the TOIF with Mt.Storm Unit 3, so there are no associated interconnection costs for this project.$0 $0

Based on the scope of work for the Interconnection Facilities, it is expected to take a range of 50 to 54 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

The schedule for any required Network Impact Reinforcements will be more clearly identified in the Phase II and Phase III System Impact Studies.

Transmission Owner Analysis

PJM performed a power flow analysis of the transmission system using a 2028 load flow model and the results were verified by Dominion.

 

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. Dominion interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AH1-713 was evaluated as a 0.0 MW (14.0 MW Capacity) injection in the Dominion area.

AH1-713 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 538.0 MW (0.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2DVP/PEPCO
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
AP_P2-3_PE-500-019B_SRT-A
BreakerAC131.46 %1417.0B1862.720.7
GD2DVP
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
AP_P2-3_PE-500-019B_SRT-A
BreakerAC105.55 %1809.0C1909.410.7
GD2DVP
8FRONT ROYAL-8MORRSVL 500.0 kV Ckt 1 line
AP_P1-2_PE-500-404T_SRT-A
SingleAC103.1 %3220.44B3320.142.04

Details for 6EDFERRY-DICKH230 230.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019B_SRT-A


Base Case Flowgate

Area:DVP/PEPCO
Facility Description:
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.46 %
Rating:1417.0 MVA
Rating Type:B
MVA to Mitigate:1862.72
MW Contribution:0.7
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
Adder
0.185
3144293JTRSVLE
Adder
0.22
3144293JTRSVLE
Adder
0.22
3144293JTRSVLE
Adder
0.22
3147043LAWRENC
Adder
0.626
20390526W1-045 C
Solar/Wind Helper
0.226
23544701WINZ1-113
Adder
0.24
20671828STAW2-080
Solar/Wind Helper
0.02
20671928W4-073
Solar/Wind Helper
0.066
20673628F1S_V4-069
Solar/Wind Helper
0.022
20673728F2S_V4-070
Solar/Wind Helper
0.022
20673828FLE_V3-070
Solar/Wind Helper
0.068
20674128FR_U2-059
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.017
20674628WNG_W3-110
Solar/Wind Helper
0.066
20674828DL_W4-046
Solar/Wind Helper
0.006
20674928WA_W3-044
Solar/Wind Helper
0.072
20675128HRM_W1-127
Solar/Wind Helper
0.022
20675428EAM_W2-061
Solar/Wind Helper
0.012
20675528CPH_W2-050
Solar/Wind Helper
0.065
20675728RH_W2-091
Solar/Wind Helper
0.1
20675828AU_W4-064
Solar/Wind Helper
0.022
20675928HOL_W4-097
Solar/Wind Helper
0.037
20676128MHD_W3-029
Solar/Wind Helper
0.072
20676228FRD_X1-012
Solar/Wind Helper
0.067
20676328BVR_Y1-020
Solar/Wind Helper
0.02
20676428JCR_X2-075
Solar/Wind Helper
0.051
20676728BRNX1-095
Solar/Wind Helper
0.022
20714528FRN_Y2-051
Solar/Wind Helper
0.043
20714828MDF_W3-079
Solar/Wind Helper
0.099
20714928UPF_X1-085
Solar/Wind Helper
0.004
20715028HAN_X4-015
Solar/Wind Helper
0.043
20715228NPK_W1-113
Solar/Wind Helper
0.059
20715728PEM_W1-119
Solar/Wind Helper
0.073
20715828PEM_W1-120
Solar/Wind Helper
0.073
20716028EGP_W2-019
Solar/Wind Helper
0.014
20716928W4-060COL
Solar/Wind Helper
0.039
20720528MAN_W1-024
Solar/Wind Helper
0.021
20720628TIN_W1-124
Solar/Wind Helper
0.143
20720728JCB_W1-129
Solar/Wind Helper
0.043
20720828JCB_W4-025
Solar/Wind Helper
0.048
207408W3-077 C
Solar/Wind Helper
0.062
207439AE1-081 C O1
Solar/Wind Helper
0.014
214067T20SOLAR
Solar/Wind Helper
0.009
217206BARNGR HS C
Solar/Wind Helper
0.005
217208PARK ELE C
Solar/Wind Helper
0.003
217209CENTRL HS C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
217213AMBOY SO C
Solar/Wind Helper
0.021
232404W1-003 C
Solar/Wind Helper
0.4
232408W1-005 C
Solar/Wind Helper
0.4
232410W1-006 C
Solar/Wind Helper
0.4
232426Y1-080 FULL
Solar/Wind Helper
0.031
232428Y3-058 C
Solar/Wind Helper
0.266
23777801MSM_W1-116
Solar/Wind Helper
0.11
3137176SLIGO L2192
Solar/Wind Harmer
-0.033
3140676OCCOQUN
Adder
0.237
3141316ARNOLDS
Adder
0.192
3141346CRANES
Adder
0.098
3141426STAFORD
Solar/Wind Harmer
-0.002
3141843SHACKLE
Adder
0.389
3141843SHACKLE
Adder
0.389
3141906WESTMOR
Solar/Wind Harmer
-0.003
3142296MT RD221
Adder
0.244
3142366NRTHEST
Adder
0.249
3142416OLDCHRC
Solar/Wind Harmer
-0.022
3142416OLDCHRC
Solar/Wind Harmer
0.867
3142416OLDCHRC
Solar/Wind Harmer
-0.008
3142433PROV 92
Solar/Wind Harmer
-0.034
3142433PROV 92
Adder
0.148
3142433PROV 92
Adder
0.148
3142433PROV 92
Adder
0.148
3142433PROV 92
Adder
0.148
3142433PROV 92
Adder
0.148
3142433PROV 92
Adder
0.148
3142956BIRDNECK
Solar/Wind Harmer
0.446
3143096IRON208
Adder
0.312
3143096IRON208
Adder
0.319
3143096IRON208
Adder
0.319
3143316POE
Solar/Wind Harmer
-0.033
3143336POWHATN
Solar/Wind Harmer
0.991
3143336POWHATN
Solar/Wind Harmer
0.843
3144216WINCHST
Adder
0.283
3144356SAPONY
Solar/Wind Harmer
0.285
3145506HICKORY
Solar/Wind Harmer
-0.033
3145506HICKORY
Solar/Wind Harmer
-0.02
3145506HICKORY
Solar/Wind Harmer
-0.005
3146386ELIZ CT
Solar/Wind Harmer
-0.008
3146396TANGLEW
Solar/Wind Harmer
0.151
3146776BUCKING
Solar/Wind Harmer
-0.032
3146776BUCKING
Solar/Wind Harmer
-0.003
3146776BUCKING
Solar/Wind Harmer
-0.003
3146776BUCKING
Solar/Wind Harmer
-0.003
3150071POSSM 5
Adder
38.76
3150151POSSMC1
Adder
0.848
3150151POSSMC1
Adder
0.848
3150151POSSMC1
Adder
0.848
3150181POSSMC2
Adder
0.848
3150181POSSMC2
Adder
0.848
3150181POSSMC2
Adder
0.855
3150211REMNGT1
Adder
12.476
3150221REMNGT2
Adder
12.559
3150231REMNGT3
Adder
13.559
3150241REMNGT4
Adder
12.643
3150281M RUN A
Adder
13.444
3150291M RUN B
Adder
13.336
3150301M RUN C
Adder
13.435
3150331BIRCHWDA
Adder
13.842
3150341NORNECKC1
Adder
0.802
3150341NORNECKC1
Adder
0.809
3150351NORNECKC2
Adder
0.783
3150351NORNECKC2
Adder
0.77
3150391LDYSMT3
Adder
10.854
3150401LDYSMT4
Adder
10.874
3150411LDYSMT5
Adder
10.908
3150671DARBY 1
Adder
5.465
3150681DARBY 2
Adder
5.471
3150691DARBY 3
Adder
5.491
3150701DARBY 4
Adder
5.478
3150921YORKTN3
Adder
1.885
209027LOR2_Q27
Solar/Wind Helper
0.712
212266LOR1
Solar/Wind Helper
0.033
217081WEATEXAS C
Solar/Wind Helper
0.009
217169METRODIV C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.002
217202FBANKSOLAR C
Solar/Wind Helper
0.002
218428ETC SOLAR C
Solar/Wind Helper
0.004
218438BLK ROCK C
Solar/Wind Helper
0.02
218440SUMMTASSOC C
Solar/Wind Helper
0.012
218660EHAMPSOLAR C
Solar/Wind Helper
0.025
219236SOUTHERNHQ C
Solar/Wind Helper
0.004
219249CENTRALDIV C
Solar/Wind Helper
0.008
219272CLEANLIGHT C
Solar/Wind Helper
0.019
219276PARKLANDSO C
Solar/Wind Helper
0.068
219291REEVESSOUT C
Solar/Wind Helper
0.009
219348LDSOLAR C
Solar/Wind Helper
0.088
219607WPEMNERT C
Solar/Wind Helper
0.061
219612MATRIX C
Solar/Wind Helper
0.018
219615MILLCREEK C
Solar/Wind Helper
0.02
219620RIDERU C
Solar/Wind Helper
0.001
219766PARADISE C
Solar/Wind Helper
0.042
227927V4-067C
Solar/Wind Helper
0.008
3150981CHESPKA
Adder
0.925
3150991CHESPKB
Adder
0.757
3150991CHESPKB
Adder
0.776
3151081ELIZAR1
Adder
6.79
3151091ELIZAR2
Adder
6.672
3151101ELIZAR3
Adder
6.877
3151171GRAVELC
Adder
0.794
3151171GRAVELC
Adder
1.044
3151191GRAVEL3
Adder
5.364
3151201GRAVEL4
Adder
5.433
3151211GRAVEL5
Adder
5.364
3151221GRAVEL6
Adder
5.427
3151721LOISA A
Adder
5.397
3151731LOISA B
Adder
5.425
3151751LOISA D
Adder
5.425
3151761LOISA E
Adder
11.06
3151861LOWMORA
Adder
0.674
3151861LOWMORA
Adder
0.648
3151881LOWMORC
Adder
0.659
3151881LOWMORC
Adder
0.669
3152111X4-039 GT1
50/50
2.007
3152121X4-039 GT2
50/50
2.001
3152131X4-039 ST
50/50
3.158
3152541MT STMG
Adder
0.593
3152601GOSPORTA
Adder
0.738
3152611GOSPORTB
Adder
0.943
3152621GOSPORTC
Adder
0.801
316075AC2-137 C
Solar/Wind Harmer
0.231
316077AC2-138 C
Solar/Wind Harmer
0.183
228728W1-130C
Solar/Wind Helper
0.041
228729W2-030 C
Solar/Wind Helper
0.085
3138133OCRAN
Solar/Wind Harmer
-0.003
3138133OCRAN
Solar/Wind Harmer
-0.005
3138283WHITEMARSH
Solar/Wind Harmer
0.013
3141766HARMONY
Solar/Wind Harmer
0.762
3141766HARMONY
Solar/Wind Harmer
-0.002
3141783LANCAST
Solar/Wind Harmer
-0.005
3141783LANCAST
Solar/Wind Harmer
-0.003
3141813NORNECK
Solar/Wind Harmer
-0.009
3141913WHIT STONE
Solar/Wind Harmer
-0.009
3143226MDLTHAN
Solar/Wind Harmer
-0.009
3143873LANEXA
Solar/Wind Harmer
-0.005
3145273HOLLAND
Solar/Wind Harmer
-0.006
3146376EDENTON
Solar/Wind Harmer
-0.008
3146376EDENTON
Solar/Wind Harmer
0.24
3146376EDENTON
Solar/Wind Harmer
0.24
3146456SLIGO L269
Solar/Wind Harmer
0.977
3146456SLIGO L269
Solar/Wind Harmer
-0.008
3146456SLIGO L269
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146926FARMVIL
Solar/Wind Harmer
-0.005
3146926FARMVIL
Solar/Wind Harmer
-0.005
3147346CASHSCORNER
Solar/Wind Harmer
0.143
3147666LOUISA
Solar/Wind Harmer
-0.038
3147666LOUISA
Solar/Wind Harmer
-0.022
232406W1-004 FULL
Solar/Wind Helper
0.4
232436AB1-176 C
Solar/Wind Helper
0.035
3141726DUNNSVL
Solar/Wind Harmer
-0.034
3145663CRESWEL
Solar/Wind Harmer
-0.022
316036AC1-147 C
Solar/Wind Harmer
0.225
316059AD1-063 C
Solar/Wind Harmer
0.193
316159AE1-175 C
Solar/Wind Harmer
0.227
316240AF1-291 C
Solar/Wind Harmer
0.255
316246AF1-032 C
Solar/Wind Harmer
0.167
316258AE1-075 C
Solar/Wind Harmer
0.203
316305AF2-043 C
Solar/Wind Harmer
0.249
316314AB2-024 C
Solar/Wind Harmer
0.732
316315AB2-025 C
Solar/Wind Harmer
0.22
316316AC1-027 C
Solar/Wind Harmer
0.255
316336AC2-165 C
Solar/Wind Harmer
1.441
316382AG1-145 C
Solar/Wind Harmer
0.255
316405AF2-144 C
Solar/Wind Harmer
0.214
223402AF1-300 C
Solar/Wind Helper
0.379
230415AB2-049 C
Solar/Wind Helper
0.023
20742028HF_AC1-207
Solar/Wind Helper
0.106
207454AA2-184 E
Solar/Wind Helper
0.234
207459AE1-142 C O1
Solar/Wind Helper
0.22
207471AF2-354 C
Solar/Wind Helper
0.124
208835TUHI V3-051
Solar/Wind Helper
0.021
208835TUHI V3-051
Solar/Wind Helper
0.021
232424Y1-079 C
Solar/Wind Helper
0.092
3150371LDYSMT1
Adder
10.507
3150381LDYSMT2
Adder
10.439
218524CNTRALGAS1 C
Solar/Wind Helper
0.12
218526CNTRALGAS2 C
Solar/Wind Helper
0.12
226910AB2-157 C
Solar/Wind Helper
0.012
233901CHERRYDALE C
Solar/Wind Helper
0.183
233939AC1-091 C
Solar/Wind Helper
0.275
233940AF2-379 C
Solar/Wind Helper
0.049
233970AC1-092 C
Solar/Wind Helper
0.275
233971AC1-093 C
Solar/Wind Helper
0.281
233972AC1-094 C
Solar/Wind Helper
0.238
212507AE2-042_GEN
Solar/Wind Helper
1.058
219907AC1-030 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.088
237025AB1-124 C
Solar/Wind Helper
0.168
237030AB1-096 C
Solar/Wind Helper
0.073
237034AC2-136 C
Solar/Wind Helper
0.157
237038AE2-054 C
Solar/Wind Helper
0.119
3130156CHOWAN
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.008
3145336SMITFLD
Solar/Wind Harmer
-0.033
3145336SMITFLD
Solar/Wind Harmer
-0.003
3141196NOKESVL
Solar/Wind Harmer
-0.049
3141873WAN 176
Solar/Wind Harmer
1.015
3141873WAN 176
Solar/Wind Harmer
-0.002
3143526WINTERP
Solar/Wind Harmer
-0.044
3143526WINTERP
Solar/Wind Harmer
-0.044
316411AF1-147_GEN1
Solar/Wind Harmer
1.2
316415AF1-147_GEN2
Solar/Wind Harmer
1.2
316404AE1-155 C
Solar/Wind Harmer
1.667
316017AA1-139 ULT1
Solar/Wind Harmer
0.67
316018AA1-139 ULT2
Solar/Wind Harmer
0.71
316033AB2-134 GEN
Solar/Wind Harmer
2.716
228754AB1-001 C
Solar/Wind Helper
0.02
316388AE2-253 GEN
Solar/Wind Harmer
0.559
235062AE1-101 C1
Solar/Wind Helper
0.747
205956AE1-196_GEN
Solar/Wind Helper
0.422
217204WCALDSOLAR C
Solar/Wind Helper
0.002
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
3132273ORANGE
Solar/Wind Harmer
-0.002
3142543TWELFTH
Solar/Wind Harmer
-0.001
237080AD1-060 GEN
Solar/Wind Helper
0.151
235067AD1-061 GEN
Solar/Wind Helper
0.214
237001AB1-127_GEN
Solar/Wind Helper
0.221
237002AB1-128_GEN
Solar/Wind Helper
0.212
238221AF1-254 C O1
Solar/Wind Helper
0.122
316203AE2-005 GEN
Solar/Wind Harmer
3.607
316441AF1-014 GEN
Solar/Wind Harmer
0.577
235063AE1-101 C2
Solar/Wind Helper
0.747
316484AD2-074 GEN
Solar/Wind Harmer
2.171
233944AB2-135 GEN
Solar/Wind Helper
0.465
233946AB2-136 GEN
Solar/Wind Helper
0.448
3156081AA2-088 GEN
Solar/Wind Harmer
2.58
233994AC2-023 GEN
Solar/Wind Helper
0.757
234033AF1-007_GEN
Solar/Wind Helper
5.529
315614AA2-178 GEN
Solar/Wind Harmer
0.864
315816AE2-034 GEN
Solar/Wind Harmer
0.648
316312AB1-027
Solar/Wind Harmer
0.29
315833AF1-017_GEN
Solar/Wind Harmer
1.574
316369SG1_INVT
Solar/Wind Harmer
1.505
315651AD1-115 GEN
Solar/Wind Harmer
4.557
316023GEN1_S
Solar/Wind Harmer
0.534
316365GEN2_N
Solar/Wind Harmer
0.534
237006AB1-125 GEN
Solar/Wind Helper
0.126
23779801AA1-109
Solar/Wind Helper
0.182
316487AF1-042 GEN
Solar/Wind Harmer
1.136
315839AE2-212 C
Solar/Wind Harmer
0.254
233982AB2-133 GEN
Solar/Wind Helper
0.282
233915AB1-141 GEN
Solar/Wind Helper
0.397
233918AB1-142 GEN
Solar/Wind Helper
0.397
315835AF2-110_GEN
Solar/Wind Harmer
1.032
315814AE2-033 C
Solar/Wind Harmer
7.6
315671AE2-027_GEN
Solar/Wind Harmer
6.335
315747AE2-019 GEN
50/50
14.059
233930AB2-032 GEN
Solar/Wind Helper
0.301
233987AB2-037 GEN
Solar/Wind Helper
1.847
315662AE1-191 GEN
Solar/Wind Harmer
1.031
315666AE1-190 GEN
Solar/Wind Harmer
0.258
315673AE1-157 GEN
Solar/Wind Harmer
6.752
315813AE1-149 C
Solar/Wind Harmer
5.23
315683AE1-153 C
Solar/Wind Harmer
9.363
315742AE1-103 GEN
Solar/Wind Harmer
0.849
319010AE1-072 C
Solar/Wind Harmer
1.673
316065AD1-022 GEN
Solar/Wind Harmer
3.958
315697AD1-025 GEN
Solar/Wind Harmer
1.703
316185AD1-033 GEN
Solar/Wind Harmer
0.876
233933AB2-153 GEN
Solar/Wind Helper
0.184
315773AC2-141 GEN
Solar/Wind Harmer
3.497
316280AD1-041 GEN
Solar/Wind Harmer
0.645
233935AB2-179 C
Solar/Wind Helper
1.004
315732AD1-074 GEN1
Solar/Wind Harmer
1.605
315733AD1-074 GEN2
Solar/Wind Harmer
1.605
315735AD1-075 GEN1
Solar/Wind Harmer
0.803
315737AD1-076 GEN
Solar/Wind Harmer
1.509
316473AC1-191 GEN
Solar/Wind Harmer
0.931
316447AC1-158 HLD
Solar/Wind Harmer
2.184
316044AC1-158 PL1
Solar/Wind Harmer
0.993
316045AC1-158 PL2
Solar/Wind Harmer
3.177
316450AC1-158 RIC
Solar/Wind Harmer
0.265
316468AD1-105 GEN
Solar/Wind Harmer
0.981
316072AD1-144
Solar/Wind Harmer
0.168
315778AD1-151 GEN
Solar/Wind Harmer
7.304
316156AD2-030 GEN
Solar/Wind Harmer
0.228
316337AD2-073 GEN
Solar/Wind Harmer
0.235
234015AF2-250 C
Solar/Wind Helper
0.03
234036AF2-325 C
Solar/Wind Helper
0.033
233990AG1-397 GEN
Solar/Wind Helper
0.024
207528AF2-192 GEN
Solar/Wind Helper
0.057
207484AF2-139 C O1
Solar/Wind Helper
0.062
207510AF2-138 C
Solar/Wind Helper
0.06
207518AF1-320_GEN
Solar/Wind Helper
1.156
207442AE1-156 GEN
Solar/Wind Helper
0.243
226929AD2-058 GEN
Solar/Wind Helper
0.066
207437AD2-070 GEN
Solar/Wind Helper
0.101
209054AE2-059 GEN
Solar/Wind Helper
0.054
313526AB2-022
Solar/Wind Harmer
0.222
316313AB2-026
Solar/Wind Harmer
0.225
207445AB1-138_GEN
Solar/Wind Helper
0.079
209071AE2-133 GEN
Solar/Wind Helper
0.054
209116AE2-175 GEN
Solar/Wind Helper
1.289
233923SMA
Solar/Wind Helper
0.755
230433AD2-135 GEN
Solar/Wind Helper
0.013
230430AE1-229_GEN
Solar/Wind Helper
2.603
219680HOPEWELLV C1
Solar/Wind Helper
0.002
219686LUMSOLAR_N C
Solar/Wind Helper
0.031
219688LUMSOLAR_S C
Solar/Wind Helper
0.031
219908AB1-139 C
Solar/Wind Helper
0.055
219904AC1-010 C
Solar/Wind Helper
0.047
219906AC1-017 C
Solar/Wind Helper
0.032
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219258KINSLEYDEP C
Solar/Wind Helper
0.059
219304NAMERICA C
Solar/Wind Helper
0.1
219921AF1-264
Solar/Wind Helper
0.039
203975AE1-071-GEN
Solar/Wind Helper
1.563
211065PSPA IPP
Solar/Wind Helper
0.109
211065PSPA IPP
Solar/Wind Helper
0.109
207530AG1-191 GEN
Solar/Wind Helper
0.049
230511AF1-262
Solar/Wind Helper
0.011
205932AD2-116_GEN
Solar/Wind Helper
0.422
205941AD2-115 GEN
Solar/Wind Helper
0.375
205943AE1-185 GEN
Solar/Wind Helper
0.423
205917AD1-020 ES
Solar/Wind Helper
0.322
205916AD1-020 GEN
Solar/Wind Helper
1.496
209067AE2-060 GEN
Solar/Wind Helper
0.051
209137AF2-361 C
Solar/Wind Helper
0.864
3146206CASHIE
Solar/Wind Harmer
-0.008
3146206CASHIE
Solar/Wind Harmer
-0.008
3146206CASHIE
Solar/Wind Harmer
-0.008
316349AD2-085 GEN
Solar/Wind Harmer
0.737
316006AB2-029 C
Solar/Wind Harmer
0.632
316322AB2-045
Solar/Wind Harmer
0.267
316192AB2-158 GEN
Solar/Wind Harmer
1.122
316083AB2-161 GEN
Solar/Wind Harmer
1.353
316132AB2-190 GEN1
Solar/Wind Harmer
0.854
316458AB2-190 GEN2
Solar/Wind Harmer
0.854
316254AC1-120 GEN1
Solar/Wind Harmer
0.825
316170AC1-121 GEN2
Solar/Wind Harmer
0.275
316375AC2-012 GEN
Solar/Wind Harmer
2.88
316311AC2-079 GEN
Solar/Wind Harmer
4.18
316339AD2-160 GEN
Solar/Wind Harmer
0.559
316164AC1-076 GEN
Solar/Wind Harmer
0.848
316223AC1-118
Solar/Wind Harmer
0.237
316294AC1-161 GEN
Solar/Wind Harmer
2.704
315975AC1-164 GENB
Solar/Wind Harmer
0.267
315976AC1-164 GENA
Solar/Wind Harmer
9.028
316169AC1-164_GENC
Solar/Wind Harmer
7.799
316381AD1-082 GEN
Solar/Wind Harmer
0.765
316233AE1-074 FULL
Solar/Wind Harmer
0.231
316236AE1-162_GEN
Solar/Wind Harmer
0.252
316093AE2-104_GEN
Solar/Wind Harmer
2.401
3150851SPRUNCC
Adder
0.351
3150861SPRUNCD
Adder
0.351
230434AG1-499 GEN
Solar/Wind Helper
0.177
233964AF2-378 GEN
Solar/Wind Helper
0.033
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
208972BECR K09
Solar/Wind Helper
0.227
209029WAYMART-WD
Solar/Wind Helper
0.566
223401AF1-299 GEN
Solar/Wind Helper
0.379
230407AD2-065 C
Solar/Wind Helper
0.031
232422X3-066 FULL
Solar/Wind Helper
0.09
232432Z2-076 GEN
Solar/Wind Helper
0.053
232434Z2-077 GEN
Solar/Wind Helper
0.1
233996TM1833_GEN
Solar/Wind Helper
0.206
233997TMININ_4.2
Solar/Wind Helper
0.206
233998TM1NIN_3.36
Solar/Wind Helper
0.206
3130086AYDLETT
Solar/Wind Harmer
-0.033
3138126ROCKLANDING
Solar/Wind Harmer
0.026
3138216PACIFIC
Solar/Wind Harmer
-0.003
3138266HYDRAULIC
Solar/Wind Harmer
0
3138266HYDRAULIC
Solar/Wind Harmer
0
3142946ENON
Solar/Wind Harmer
-0.001
3142946ENON
Solar/Wind Harmer
-0.003
3144536CHRHLND
Solar/Wind Harmer
-0.001
3144873MCLAUGH
Solar/Wind Harmer
0
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
0.234
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.021
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3146406KITTY HAWK
Solar/Wind Harmer
0.007
315611Z1-036_GEN2
Solar/Wind Harmer
2.009
315800Z1-036_GEN1
Solar/Wind Harmer
2.009
316318V4-068
Solar/Wind Harmer
0.197
316320Y1-086
Solar/Wind Harmer
0.483
316321Z2-027
Solar/Wind Harmer
0.222
944011AF1-069 GEN
Solar/Wind Harmer
4.798
944491AF1-114 GEN
Solar/Wind Harmer
2.612
944581AF1-123 GEN
Solar/Wind Harmer
37.845
944591AF1-124 GEN
Solar/Wind Harmer
37.981
944601AF1-125 GEN
Solar/Wind Harmer
37.254
944631AF1-128 GEN
Adder
36.159
944641AF1-129 GEN
Adder
35.924
946691AF1-333 GEN
Solar/Wind Helper
0.297
946731AF1-337 GEN
Solar/Wind Helper
0.297
946741AF1-338 GEN
Solar/Wind Helper
0.297
946751AF1-339 GEN
Solar/Wind Helper
0.297
959381AF2-229 GEN
Solar/Wind Helper
0.23
959421AF2-233 GEN
Solar/Wind Helper
0.297
959431AF2-234 GEN
Solar/Wind Helper
0.594
959561AF2-247 GEN
Solar/Wind Helper
0.016
960921AF2-383 GEN
Solar/Wind Helper
0.152
961261AF2-417 GEN
Solar/Wind Helper
0.308
961301AF2-421 GEN
Solar/Wind Helper
0.309
961331AF2-424 GEN
Solar/Wind Helper
0.302
961341AF2-425 GEN
Solar/Wind Helper
0.302
961421AF2-433 GEN
Solar/Wind Helper
0.302
961431AF2-434 GEN
Solar/Wind Helper
0.302
961611AG1-000B GEN
Solar/Wind Harmer
4.146
961611AG1-000B GEN
Solar/Wind Harmer
1.769
961681AG1-008 GEN
Solar/Wind Harmer
6.214
961951AG1-038 GEN
Solar/Wind Harmer
1.136
962861AG1-135 GEN
Solar/Wind Harmer
3.239
962971AG1-146 GEN
Solar/Wind Harmer
1.614
962981AG1-147 GEN
Solar/Wind Harmer
3.767
963071AG1-156 GEN
Solar/Wind Helper
1.001
963151AG1-164 GEN
Solar/Wind Helper
0.309
963161AG1-165 GEN
Solar/Wind Helper
0.309
963391AG1-188 GEN
Solar/Wind Helper
0.062
963401AG1-189 GEN
Solar/Wind Helper
0.043
966871AG1-558 GEN
Solar/Wind Harmer
0.26
966871AG1-558 GEN
Solar/Wind Harmer
0.089
966881AG1-559 GEN
Solar/Wind Harmer
0.269
966881AG1-559 GEN
Solar/Wind Harmer
0.092
970009AG2-005 GEN
Solar/Wind Harmer
1.078
970053AG2-049 GEN
Adder
1.707
970085AG2-068 GEN
Solar/Wind Harmer
4.94
970087AG2-069 GEN
Solar/Wind Harmer
7.409
970099AG2-077 GEN
Solar/Wind Harmer
2.697
970129AG2-093 GEN
Solar/Wind Harmer
4.756
970129AG2-093 GEN
Solar/Wind Harmer
1.926
970133AG2-095 GEN
Solar/Wind Harmer
0.953
970285AG2-188 GEN
Solar/Wind Harmer
6.934
970293AG2-193 GEN
Solar/Wind Harmer
1.071
970301AG2-198 GEN
Solar/Wind Harmer
3.936
970317AG2-208 GEN
Solar/Wind Harmer
3.912
970467AG2-304 GEN
50/50
15.27
970581AG2-369 GEN
Solar/Wind Harmer
4.248
970601AG2-382 GEN
Solar/Wind Harmer
3.458
970657AG2-426 GEN
Solar/Wind Harmer
2.604
970657AG2-426 GEN
Solar/Wind Harmer
0.544
970659AG2-427 GEN
Solar/Wind Harmer
4.431
970659AG2-427 GEN
Solar/Wind Harmer
0.785
970661AG2-428 GEN
Solar/Wind Harmer
8.843
970661AG2-428 GEN
Solar/Wind Harmer
1.567
970673AG2-436 GEN
Solar/Wind Harmer
17.036
970673AG2-436 GEN
Solar/Wind Harmer
8.626
970737AG2-469 GEN
Solar/Wind Harmer
4.42
970909AG2-566 GEN
Solar/Wind Harmer
0.747
970917AG2-570 GEN
Solar/Wind Harmer
19.793
970919AG2-571 GEN
Solar/Wind Harmer
2.505
970933AG2-581 GEN
Solar/Wind Harmer
7.52
970937AG2-583 GEN
Solar/Wind Harmer
5.84
971069AG2-661 GEN
Solar/Wind Harmer
1.334
971153AH1-033 GEN
Solar/Wind Harmer
1.009
971157AH1-035 GEN
Solar/Wind Harmer
0.994
971163AH1-040 GEN
Solar/Wind Harmer
7.509
971167AH1-042 GEN
Solar/Wind Harmer
8.225
971223AH1-071 GEN
Solar/Wind Harmer
1.075
971281AH1-106 GEN
Solar/Wind Harmer
1.396
971283AH1-107 GEN
Solar/Wind Harmer
1.396
971285AH1-108 GEN
Adder
0.574
971317AH1-138 GEN
Solar/Wind Harmer
1.057
971445AH1-216 GEN
Solar/Wind Harmer
5.176
971455AH1-223 GEN
Solar/Wind Harmer
2.52
971547AH1-271 GEN
Solar/Wind Harmer
1.976
971647AH1-324 GEN
Solar/Wind Harmer
4.206
971685AH1-345 GEN
Solar/Wind Harmer
0.963
219912AD2-042 GEN
Solar/Wind Helper
0.115
219919AE1-041 FULL
Solar/Wind Helper
0.003
227287AC2-120 GEN
Solar/Wind Helper
0.266
316431W1029_GEN1
Solar/Wind Harmer
1.486
316433W1029_GEN2
Solar/Wind Harmer
1.486
316435W1029_GEN3
Solar/Wind Harmer
1.486
939411AE1-173 GEN
Solar/Wind Harmer
41.494
940641AE2-051 GEN
Solar/Wind Harmer
7.777
941031AE2-094 GEN
Solar/Wind Harmer
15.312
957411AF2-035 GEN
Solar/Wind Harmer
4.024
957481AF2-042 GEN
Solar/Wind Harmer
6.742
957521AF2-046 GEN
Solar/Wind Harmer
6.214
957601AF2-054 GEN
Solar/Wind Harmer
0.256
957831AF2-077 GEN
Solar/Wind Harmer
0.255
957871AF2-081 GEN
Solar/Wind Harmer
4.142
957921AF2-086 GEN
Solar/Wind Helper
0.298
957971AF2-091 GEN
Solar/Wind Harmer
0.888
958261AF2-120 GEN
Solar/Wind Harmer
3.349
963691AG1-221 GEN
Solar/Wind Harmer
2.52
963711AG1-223 GEN
Solar/Wind Helper
0.048
964001AG1-254 GEN
Solar/Wind Helper
0.738
964051AG1-259 GEN
Solar/Wind Helper
0.044
964061AG1-260 GEN
Solar/Wind Helper
0.044
964211AG1-282 GEN
Solar/Wind Harmer
0.261
964851AG1-348 GEN
Solar/Wind Helper
0.059
965281AG1-393 GEN
Solar/Wind Harmer
1.054
965291AG1-394 GEN
Solar/Wind Harmer
0.704
966001AG1-469 GEN
Solar/Wind Harmer
0.179
966111AG1-480 GEN
Solar/Wind Helper
0.032
966131AG1-482 GEN
Solar/Wind Helper
0.066
966261AG1-495 GEN
Solar/Wind Helper
0.06
971741AH1-377 GEN
Solar/Wind Harmer
9.144
971761AH1-387 GEN
Solar/Wind Harmer
4.579
971777AH1-397 GEN
Solar/Wind Harmer
1.006
971781AH1-399 GEN
Solar/Wind Harmer
0.543
971845AH1-439 GEN
Solar/Wind Harmer
4.213
971967AH1-528 GEN
Solar/Wind Harmer
15.195
972003AH1-546 GEN
Solar/Wind Harmer
3.978
972135AH1-637 GEN
Solar/Wind Harmer
0.887
972183AH1-676 GEN
Adder
89.287
972185AH1-677 GEN
Adder
4.036
972187AH1-678 GEN
Adder
2.039
972189AH1-679 GEN
Adder
1.305
972193AH1-681 GEN
Adder
1.595
972195AH1-682 GEN
Adder
1.426
972197AH1-683 GEN
Adder
1.698
972199AH1-684 GEN
Adder
1.917
972201AH1-685 GEN
Adder
2.167
972205AH1-687 GEN
Adder
3.036
972213AH1-691 GEN
Adder
1.766
972215AH1-692 GEN
Adder
1.766
972217AH1-693 GEN
Adder
1.667
972219AH1-694 GEN
Adder
1.223
972223AH1-696 GEN
Adder
6.699
972255AH1-712 GEN
Adder
35.693
972257AH1-713 GEN
Adder
0.697
972265AH1-717 GEN
Adder
5.796
972277AH1-723 GEN
Adder
41.593
972289AH1-729 GEN
50/50
14.564
233950AC2-186 GEN
Solar/Wind Helper
0.091
233952AC2-187 GEN
Solar/Wind Helper
0.183
233954AC2-188 GEN
Solar/Wind Helper
0.183
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.819
CBM West 2LTFEXP_CBM-W2->PJM
CBM
43.81
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.851
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.786
NYPJM->LTFIMP_NY
CLTF
3.269
LGEELTFEXP_LGEE->PJM
CLTF
2.098
WECLTFEXP_WEC->PJM
CLTF
1.126
CPLELTFEXP_CPLE->PJM
CLTF
5.01
TVALTFEXP_TVA->PJM
CLTF
3.503
MECLTFEXP_MEC->PJM
CLTF
5.133
LAGNLTFEXP_LAGN->PJM
CLTF
6.958
SIGELTFEXP_SIGE->PJM
CLTF
0.162
AG2-052LTFEXP_AG2-052->PJM
LTF
0.067
AH1-155LTFEXP_AH1-155->PJM
LTF
0.101

Details for 6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019B_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.55 %
Rating:1809.0 MVA
Rating Type:C
MVA to Mitigate:1909.41
MW Contribution:0.7
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
Adder
0.185
3144293JTRSVLE
Adder
0.22
3144293JTRSVLE
Adder
0.22
3144293JTRSVLE
Adder
0.22
3147043LAWRENC
Adder
0.626
20390526W1-045 C
Solar/Wind Helper
0.226
23544701WINZ1-113
Adder
0.24
20671828STAW2-080
Solar/Wind Helper
0.02
20671928W4-073
Solar/Wind Helper
0.066
20673628F1S_V4-069
Solar/Wind Helper
0.022
20673728F2S_V4-070
Solar/Wind Helper
0.022
20673828FLE_V3-070
Solar/Wind Helper
0.068
20674128FR_U2-059
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.017
20674628WNG_W3-110
Solar/Wind Helper
0.066
20674828DL_W4-046
Solar/Wind Helper
0.006
20674928WA_W3-044
Solar/Wind Helper
0.072
20675128HRM_W1-127
Solar/Wind Helper
0.022
20675428EAM_W2-061
Solar/Wind Helper
0.012
20675528CPH_W2-050
Solar/Wind Helper
0.065
20675728RH_W2-091
Solar/Wind Helper
0.1
20675828AU_W4-064
Solar/Wind Helper
0.022
20675928HOL_W4-097
Solar/Wind Helper
0.037
20676128MHD_W3-029
Solar/Wind Helper
0.072
20676228FRD_X1-012
Solar/Wind Helper
0.067
20676328BVR_Y1-020
Solar/Wind Helper
0.02
20676428JCR_X2-075
Solar/Wind Helper
0.051
20676728BRNX1-095
Solar/Wind Helper
0.022
20714528FRN_Y2-051
Solar/Wind Helper
0.043
20714828MDF_W3-079
Solar/Wind Helper
0.099
20714928UPF_X1-085
Solar/Wind Helper
0.004
20715028HAN_X4-015
Solar/Wind Helper
0.043
20715228NPK_W1-113
Solar/Wind Helper
0.059
20715728PEM_W1-119
Solar/Wind Helper
0.073
20715828PEM_W1-120
Solar/Wind Helper
0.073
20716028EGP_W2-019
Solar/Wind Helper
0.014
20716928W4-060COL
Solar/Wind Helper
0.039
20720528MAN_W1-024
Solar/Wind Helper
0.021
20720628TIN_W1-124
Solar/Wind Helper
0.143
20720728JCB_W1-129
Solar/Wind Helper
0.043
20720828JCB_W4-025
Solar/Wind Helper
0.048
207408W3-077 C
Solar/Wind Helper
0.062
207439AE1-081 C O1
Solar/Wind Helper
0.014
214067T20SOLAR
Solar/Wind Helper
0.009
217206BARNGR HS C
Solar/Wind Helper
0.005
217208PARK ELE C
Solar/Wind Helper
0.003
217209CENTRL HS C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
217213AMBOY SO C
Solar/Wind Helper
0.021
232404W1-003 C
Solar/Wind Helper
0.4
232408W1-005 C
Solar/Wind Helper
0.4
232410W1-006 C
Solar/Wind Helper
0.4
232426Y1-080 FULL
Solar/Wind Helper
0.031
232428Y3-058 C
Solar/Wind Helper
0.266
23777801MSM_W1-116
Solar/Wind Helper
0.11
3137176SLIGO L2192
Solar/Wind Harmer
-0.033
3140676OCCOQUN
Adder
0.237
3141316ARNOLDS
Adder
0.192
3141346CRANES
Adder
0.098
3141426STAFORD
Solar/Wind Harmer
-0.002
3141843SHACKLE
Adder
0.389
3141843SHACKLE
Adder
0.389
3141906WESTMOR
Solar/Wind Harmer
-0.003
3142296MT RD221
Adder
0.244
3142366NRTHEST
Adder
0.249
3142416OLDCHRC
Solar/Wind Harmer
-0.022
3142416OLDCHRC
Solar/Wind Harmer
0.867
3142416OLDCHRC
Solar/Wind Harmer
-0.008
3142433PROV 92
Solar/Wind Harmer
-0.034
3142433PROV 92
Adder
0.148
3142433PROV 92
Adder
0.148
3142433PROV 92
Adder
0.148
3142433PROV 92
Adder
0.148
3142433PROV 92
Adder
0.148
3142433PROV 92
Adder
0.148
3142956BIRDNECK
Solar/Wind Harmer
0.446
3143096IRON208
Adder
0.312
3143096IRON208
Adder
0.319
3143096IRON208
Adder
0.319
3143316POE
Solar/Wind Harmer
-0.033
3143336POWHATN
Solar/Wind Harmer
0.991
3143336POWHATN
Solar/Wind Harmer
0.843
3144216WINCHST
Adder
0.283
3144356SAPONY
Solar/Wind Harmer
0.285
3145506HICKORY
Solar/Wind Harmer
-0.033
3145506HICKORY
Solar/Wind Harmer
-0.02
3145506HICKORY
Solar/Wind Harmer
-0.005
3146386ELIZ CT
Solar/Wind Harmer
-0.008
3146396TANGLEW
Solar/Wind Harmer
0.151
3146776BUCKING
Solar/Wind Harmer
-0.032
3146776BUCKING
Solar/Wind Harmer
-0.003
3146776BUCKING
Solar/Wind Harmer
-0.003
3146776BUCKING
Solar/Wind Harmer
-0.003
3150071POSSM 5
Adder
38.76
3150151POSSMC1
Adder
0.848
3150151POSSMC1
Adder
0.848
3150151POSSMC1
Adder
0.848
3150181POSSMC2
Adder
0.848
3150181POSSMC2
Adder
0.848
3150181POSSMC2
Adder
0.855
3150211REMNGT1
Adder
12.476
3150221REMNGT2
Adder
12.559
3150231REMNGT3
Adder
13.559
3150241REMNGT4
Adder
12.643
3150281M RUN A
Adder
13.444
3150291M RUN B
Adder
13.336
3150301M RUN C
Adder
13.435
3150331BIRCHWDA
Adder
13.842
3150341NORNECKC1
Adder
0.802
3150341NORNECKC1
Adder
0.809
3150351NORNECKC2
Adder
0.783
3150351NORNECKC2
Adder
0.77
3150391LDYSMT3
Adder
10.854
3150401LDYSMT4
Adder
10.874
3150411LDYSMT5
Adder
10.908
3150671DARBY 1
Adder
5.465
3150681DARBY 2
Adder
5.471
3150691DARBY 3
Adder
5.491
3150701DARBY 4
Adder
5.478
3150921YORKTN3
Adder
1.885
209027LOR2_Q27
Solar/Wind Helper
0.712
212266LOR1
Solar/Wind Helper
0.033
217081WEATEXAS C
Solar/Wind Helper
0.009
217169METRODIV C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.002
217202FBANKSOLAR C
Solar/Wind Helper
0.002
218428ETC SOLAR C
Solar/Wind Helper
0.004
218438BLK ROCK C
Solar/Wind Helper
0.02
218440SUMMTASSOC C
Solar/Wind Helper
0.012
218660EHAMPSOLAR C
Solar/Wind Helper
0.025
219236SOUTHERNHQ C
Solar/Wind Helper
0.004
219249CENTRALDIV C
Solar/Wind Helper
0.008
219272CLEANLIGHT C
Solar/Wind Helper
0.019
219276PARKLANDSO C
Solar/Wind Helper
0.068
219291REEVESSOUT C
Solar/Wind Helper
0.009
219348LDSOLAR C
Solar/Wind Helper
0.088
219607WPEMNERT C
Solar/Wind Helper
0.061
219612MATRIX C
Solar/Wind Helper
0.018
219615MILLCREEK C
Solar/Wind Helper
0.02
219620RIDERU C
Solar/Wind Helper
0.001
219766PARADISE C
Solar/Wind Helper
0.042
227927V4-067C
Solar/Wind Helper
0.008
3150981CHESPKA
Adder
0.925
3150991CHESPKB
Adder
0.757
3150991CHESPKB
Adder
0.776
3151081ELIZAR1
Adder
6.79
3151091ELIZAR2
Adder
6.672
3151101ELIZAR3
Adder
6.877
3151171GRAVELC
Adder
0.794
3151171GRAVELC
Adder
1.044
3151191GRAVEL3
Adder
5.364
3151201GRAVEL4
Adder
5.433
3151211GRAVEL5
Adder
5.364
3151221GRAVEL6
Adder
5.427
3151721LOISA A
Adder
5.397
3151731LOISA B
Adder
5.425
3151751LOISA D
Adder
5.425
3151761LOISA E
Adder
11.06
3151861LOWMORA
Adder
0.674
3151861LOWMORA
Adder
0.648
3151881LOWMORC
Adder
0.659
3151881LOWMORC
Adder
0.669
3152111X4-039 GT1
50/50
2.007
3152121X4-039 GT2
50/50
2.001
3152131X4-039 ST
50/50
3.158
3152541MT STMG
Adder
0.593
3152601GOSPORTA
Adder
0.738
3152611GOSPORTB
Adder
0.943
3152621GOSPORTC
Adder
0.801
316075AC2-137 C
Solar/Wind Harmer
0.231
316077AC2-138 C
Solar/Wind Harmer
0.183
228728W1-130C
Solar/Wind Helper
0.041
228729W2-030 C
Solar/Wind Helper
0.085
3138133OCRAN
Solar/Wind Harmer
-0.003
3138133OCRAN
Solar/Wind Harmer
-0.005
3138283WHITEMARSH
Solar/Wind Harmer
0.013
3141766HARMONY
Solar/Wind Harmer
0.762
3141766HARMONY
Solar/Wind Harmer
-0.002
3141783LANCAST
Solar/Wind Harmer
-0.005
3141783LANCAST
Solar/Wind Harmer
-0.003
3141813NORNECK
Solar/Wind Harmer
-0.009
3141913WHIT STONE
Solar/Wind Harmer
-0.009
3143226MDLTHAN
Solar/Wind Harmer
-0.009
3143873LANEXA
Solar/Wind Harmer
-0.005
3145273HOLLAND
Solar/Wind Harmer
-0.006
3146376EDENTON
Solar/Wind Harmer
-0.008
3146376EDENTON
Solar/Wind Harmer
0.24
3146376EDENTON
Solar/Wind Harmer
0.24
3146456SLIGO L269
Solar/Wind Harmer
0.977
3146456SLIGO L269
Solar/Wind Harmer
-0.008
3146456SLIGO L269
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146926FARMVIL
Solar/Wind Harmer
-0.005
3146926FARMVIL
Solar/Wind Harmer
-0.005
3147346CASHSCORNER
Solar/Wind Harmer
0.143
3147666LOUISA
Solar/Wind Harmer
-0.038
3147666LOUISA
Solar/Wind Harmer
-0.022
232406W1-004 FULL
Solar/Wind Helper
0.4
232436AB1-176 C
Solar/Wind Helper
0.035
3141726DUNNSVL
Solar/Wind Harmer
-0.034
3145663CRESWEL
Solar/Wind Harmer
-0.022
316036AC1-147 C
Solar/Wind Harmer
0.225
316059AD1-063 C
Solar/Wind Harmer
0.193
316159AE1-175 C
Solar/Wind Harmer
0.227
316240AF1-291 C
Solar/Wind Harmer
0.255
316246AF1-032 C
Solar/Wind Harmer
0.167
316258AE1-075 C
Solar/Wind Harmer
0.203
316305AF2-043 C
Solar/Wind Harmer
0.249
316314AB2-024 C
Solar/Wind Harmer
0.732
316315AB2-025 C
Solar/Wind Harmer
0.22
316316AC1-027 C
Solar/Wind Harmer
0.255
316336AC2-165 C
Solar/Wind Harmer
1.441
316382AG1-145 C
Solar/Wind Harmer
0.255
316405AF2-144 C
Solar/Wind Harmer
0.214
223402AF1-300 C
Solar/Wind Helper
0.379
230415AB2-049 C
Solar/Wind Helper
0.023
20742028HF_AC1-207
Solar/Wind Helper
0.106
207454AA2-184 E
Solar/Wind Helper
0.234
207459AE1-142 C O1
Solar/Wind Helper
0.22
207471AF2-354 C
Solar/Wind Helper
0.124
208835TUHI V3-051
Solar/Wind Helper
0.021
208835TUHI V3-051
Solar/Wind Helper
0.021
232424Y1-079 C
Solar/Wind Helper
0.092
3150371LDYSMT1
Adder
10.507
3150381LDYSMT2
Adder
10.439
218524CNTRALGAS1 C
Solar/Wind Helper
0.12
218526CNTRALGAS2 C
Solar/Wind Helper
0.12
226910AB2-157 C
Solar/Wind Helper
0.012
233901CHERRYDALE C
Solar/Wind Helper
0.183
233939AC1-091 C
Solar/Wind Helper
0.275
233940AF2-379 C
Solar/Wind Helper
0.049
233970AC1-092 C
Solar/Wind Helper
0.275
233971AC1-093 C
Solar/Wind Helper
0.281
233972AC1-094 C
Solar/Wind Helper
0.238
212507AE2-042_GEN
Solar/Wind Helper
1.058
219907AC1-030 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.088
237025AB1-124 C
Solar/Wind Helper
0.168
237030AB1-096 C
Solar/Wind Helper
0.073
237034AC2-136 C
Solar/Wind Helper
0.157
237038AE2-054 C
Solar/Wind Helper
0.119
3130156CHOWAN
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.008
3145336SMITFLD
Solar/Wind Harmer
-0.033
3145336SMITFLD
Solar/Wind Harmer
-0.003
3141196NOKESVL
Solar/Wind Harmer
-0.049
3141873WAN 176
Solar/Wind Harmer
1.015
3141873WAN 176
Solar/Wind Harmer
-0.002
3143526WINTERP
Solar/Wind Harmer
-0.044
3143526WINTERP
Solar/Wind Harmer
-0.044
316411AF1-147_GEN1
Solar/Wind Harmer
1.2
316415AF1-147_GEN2
Solar/Wind Harmer
1.2
316404AE1-155 C
Solar/Wind Harmer
1.667
316017AA1-139 ULT1
Solar/Wind Harmer
0.67
316018AA1-139 ULT2
Solar/Wind Harmer
0.71
316033AB2-134 GEN
Solar/Wind Harmer
2.716
228754AB1-001 C
Solar/Wind Helper
0.02
316388AE2-253 GEN
Solar/Wind Harmer
0.559
235062AE1-101 C1
Solar/Wind Helper
0.747
205956AE1-196_GEN
Solar/Wind Helper
0.422
217204WCALDSOLAR C
Solar/Wind Helper
0.002
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
3132273ORANGE
Solar/Wind Harmer
-0.002
3142543TWELFTH
Solar/Wind Harmer
-0.001
237080AD1-060 GEN
Solar/Wind Helper
0.151
235067AD1-061 GEN
Solar/Wind Helper
0.214
237001AB1-127_GEN
Solar/Wind Helper
0.221
237002AB1-128_GEN
Solar/Wind Helper
0.212
238221AF1-254 C O1
Solar/Wind Helper
0.122
316203AE2-005 GEN
Solar/Wind Harmer
3.607
316441AF1-014 GEN
Solar/Wind Harmer
0.577
235063AE1-101 C2
Solar/Wind Helper
0.747
316484AD2-074 GEN
Solar/Wind Harmer
2.171
233944AB2-135 GEN
Solar/Wind Helper
0.465
233946AB2-136 GEN
Solar/Wind Helper
0.448
3156081AA2-088 GEN
Solar/Wind Harmer
2.58
233994AC2-023 GEN
Solar/Wind Helper
0.757
234033AF1-007_GEN
Solar/Wind Helper
5.529
315614AA2-178 GEN
Solar/Wind Harmer
0.864
315816AE2-034 GEN
Solar/Wind Harmer
0.648
316312AB1-027
Solar/Wind Harmer
0.29
315833AF1-017_GEN
Solar/Wind Harmer
1.574
316369SG1_INVT
Solar/Wind Harmer
1.505
315651AD1-115 GEN
Solar/Wind Harmer
4.557
316023GEN1_S
Solar/Wind Harmer
0.534
316365GEN2_N
Solar/Wind Harmer
0.534
237006AB1-125 GEN
Solar/Wind Helper
0.126
23779801AA1-109
Solar/Wind Helper
0.182
316487AF1-042 GEN
Solar/Wind Harmer
1.136
315839AE2-212 C
Solar/Wind Harmer
0.254
233982AB2-133 GEN
Solar/Wind Helper
0.282
233915AB1-141 GEN
Solar/Wind Helper
0.397
233918AB1-142 GEN
Solar/Wind Helper
0.397
315835AF2-110_GEN
Solar/Wind Harmer
1.032
315814AE2-033 C
Solar/Wind Harmer
7.6
315671AE2-027_GEN
Solar/Wind Harmer
6.335
315747AE2-019 GEN
50/50
14.059
233930AB2-032 GEN
Solar/Wind Helper
0.301
233987AB2-037 GEN
Solar/Wind Helper
1.847
315662AE1-191 GEN
Solar/Wind Harmer
1.031
315666AE1-190 GEN
Solar/Wind Harmer
0.258
315673AE1-157 GEN
Solar/Wind Harmer
6.752
315813AE1-149 C
Solar/Wind Harmer
5.23
315683AE1-153 C
Solar/Wind Harmer
9.363
315742AE1-103 GEN
Solar/Wind Harmer
0.849
319010AE1-072 C
Solar/Wind Harmer
1.673
316065AD1-022 GEN
Solar/Wind Harmer
3.958
315697AD1-025 GEN
Solar/Wind Harmer
1.703
316185AD1-033 GEN
Solar/Wind Harmer
0.876
233933AB2-153 GEN
Solar/Wind Helper
0.184
315773AC2-141 GEN
Solar/Wind Harmer
3.497
316280AD1-041 GEN
Solar/Wind Harmer
0.645
233935AB2-179 C
Solar/Wind Helper
1.004
315732AD1-074 GEN1
Solar/Wind Harmer
1.605
315733AD1-074 GEN2
Solar/Wind Harmer
1.605
315735AD1-075 GEN1
Solar/Wind Harmer
0.803
315737AD1-076 GEN
Solar/Wind Harmer
1.509
316473AC1-191 GEN
Solar/Wind Harmer
0.931
316447AC1-158 HLD
Solar/Wind Harmer
2.184
316044AC1-158 PL1
Solar/Wind Harmer
0.993
316045AC1-158 PL2
Solar/Wind Harmer
3.177
316450AC1-158 RIC
Solar/Wind Harmer
0.265
316468AD1-105 GEN
Solar/Wind Harmer
0.981
316072AD1-144
Solar/Wind Harmer
0.168
315778AD1-151 GEN
Solar/Wind Harmer
7.304
316156AD2-030 GEN
Solar/Wind Harmer
0.228
316337AD2-073 GEN
Solar/Wind Harmer
0.235
234015AF2-250 C
Solar/Wind Helper
0.03
234036AF2-325 C
Solar/Wind Helper
0.033
233990AG1-397 GEN
Solar/Wind Helper
0.024
207528AF2-192 GEN
Solar/Wind Helper
0.057
207484AF2-139 C O1
Solar/Wind Helper
0.062
207510AF2-138 C
Solar/Wind Helper
0.06
207518AF1-320_GEN
Solar/Wind Helper
1.156
207442AE1-156 GEN
Solar/Wind Helper
0.243
226929AD2-058 GEN
Solar/Wind Helper
0.066
207437AD2-070 GEN
Solar/Wind Helper
0.101
209054AE2-059 GEN
Solar/Wind Helper
0.054
313526AB2-022
Solar/Wind Harmer
0.222
316313AB2-026
Solar/Wind Harmer
0.225
207445AB1-138_GEN
Solar/Wind Helper
0.079
209071AE2-133 GEN
Solar/Wind Helper
0.054
209116AE2-175 GEN
Solar/Wind Helper
1.289
233923SMA
Solar/Wind Helper
0.755
230433AD2-135 GEN
Solar/Wind Helper
0.013
230430AE1-229_GEN
Solar/Wind Helper
2.603
219680HOPEWELLV C1
Solar/Wind Helper
0.002
219686LUMSOLAR_N C
Solar/Wind Helper
0.031
219688LUMSOLAR_S C
Solar/Wind Helper
0.031
219908AB1-139 C
Solar/Wind Helper
0.055
219904AC1-010 C
Solar/Wind Helper
0.047
219906AC1-017 C
Solar/Wind Helper
0.032
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219258KINSLEYDEP C
Solar/Wind Helper
0.059
219304NAMERICA C
Solar/Wind Helper
0.1
219921AF1-264
Solar/Wind Helper
0.039
203975AE1-071-GEN
Solar/Wind Helper
1.563
211065PSPA IPP
Solar/Wind Helper
0.109
211065PSPA IPP
Solar/Wind Helper
0.109
207530AG1-191 GEN
Solar/Wind Helper
0.049
230511AF1-262
Solar/Wind Helper
0.011
205932AD2-116_GEN
Solar/Wind Helper
0.422
205941AD2-115 GEN
Solar/Wind Helper
0.375
205943AE1-185 GEN
Solar/Wind Helper
0.423
205917AD1-020 ES
Solar/Wind Helper
0.322
205916AD1-020 GEN
Solar/Wind Helper
1.496
209067AE2-060 GEN
Solar/Wind Helper
0.051
209137AF2-361 C
Solar/Wind Helper
0.864
3146206CASHIE
Solar/Wind Harmer
-0.008
3146206CASHIE
Solar/Wind Harmer
-0.008
3146206CASHIE
Solar/Wind Harmer
-0.008
316349AD2-085 GEN
Solar/Wind Harmer
0.737
316006AB2-029 C
Solar/Wind Harmer
0.632
316322AB2-045
Solar/Wind Harmer
0.267
316192AB2-158 GEN
Solar/Wind Harmer
1.122
316083AB2-161 GEN
Solar/Wind Harmer
1.353
316132AB2-190 GEN1
Solar/Wind Harmer
0.854
316458AB2-190 GEN2
Solar/Wind Harmer
0.854
316254AC1-120 GEN1
Solar/Wind Harmer
0.825
316170AC1-121 GEN2
Solar/Wind Harmer
0.275
316375AC2-012 GEN
Solar/Wind Harmer
2.88
316311AC2-079 GEN
Solar/Wind Harmer
4.18
316339AD2-160 GEN
Solar/Wind Harmer
0.559
316164AC1-076 GEN
Solar/Wind Harmer
0.848
316223AC1-118
Solar/Wind Harmer
0.237
316294AC1-161 GEN
Solar/Wind Harmer
2.704
315975AC1-164 GENB
Solar/Wind Harmer
0.267
315976AC1-164 GENA
Solar/Wind Harmer
9.028
316169AC1-164_GENC
Solar/Wind Harmer
7.799
316381AD1-082 GEN
Solar/Wind Harmer
0.765
316233AE1-074 FULL
Solar/Wind Harmer
0.231
316236AE1-162_GEN
Solar/Wind Harmer
0.252
316093AE2-104_GEN
Solar/Wind Harmer
2.401
3150851SPRUNCC
Adder
0.351
3150861SPRUNCD
Adder
0.351
230434AG1-499 GEN
Solar/Wind Helper
0.177
233964AF2-378 GEN
Solar/Wind Helper
0.033
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
208972BECR K09
Solar/Wind Helper
0.227
209029WAYMART-WD
Solar/Wind Helper
0.566
223401AF1-299 GEN
Solar/Wind Helper
0.379
230407AD2-065 C
Solar/Wind Helper
0.031
232422X3-066 FULL
Solar/Wind Helper
0.09
232432Z2-076 GEN
Solar/Wind Helper
0.053
232434Z2-077 GEN
Solar/Wind Helper
0.1
233996TM1833_GEN
Solar/Wind Helper
0.206
233997TMININ_4.2
Solar/Wind Helper
0.206
233998TM1NIN_3.36
Solar/Wind Helper
0.206
3130086AYDLETT
Solar/Wind Harmer
-0.033
3138126ROCKLANDING
Solar/Wind Harmer
0.026
3138216PACIFIC
Solar/Wind Harmer
-0.003
3138266HYDRAULIC
Solar/Wind Harmer
0
3138266HYDRAULIC
Solar/Wind Harmer
0
3142946ENON
Solar/Wind Harmer
-0.001
3142946ENON
Solar/Wind Harmer
-0.003
3144536CHRHLND
Solar/Wind Harmer
-0.001
3144873MCLAUGH
Solar/Wind Harmer
0
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
0.234
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.021
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3146406KITTY HAWK
Solar/Wind Harmer
0.007
315611Z1-036_GEN2
Solar/Wind Harmer
2.009
315800Z1-036_GEN1
Solar/Wind Harmer
2.009
316318V4-068
Solar/Wind Harmer
0.197
316320Y1-086
Solar/Wind Harmer
0.483
316321Z2-027
Solar/Wind Harmer
0.222
944011AF1-069 GEN
Solar/Wind Harmer
4.798
944491AF1-114 GEN
Solar/Wind Harmer
2.612
944581AF1-123 GEN
Solar/Wind Harmer
37.845
944591AF1-124 GEN
Solar/Wind Harmer
37.981
944601AF1-125 GEN
Solar/Wind Harmer
37.254
944631AF1-128 GEN
Adder
36.159
944641AF1-129 GEN
Adder
35.924
946691AF1-333 GEN
Solar/Wind Helper
0.297
946731AF1-337 GEN
Solar/Wind Helper
0.297
946741AF1-338 GEN
Solar/Wind Helper
0.297
946751AF1-339 GEN
Solar/Wind Helper
0.297
959381AF2-229 GEN
Solar/Wind Helper
0.23
959421AF2-233 GEN
Solar/Wind Helper
0.297
959431AF2-234 GEN
Solar/Wind Helper
0.594
959561AF2-247 GEN
Solar/Wind Helper
0.016
960921AF2-383 GEN
Solar/Wind Helper
0.152
961261AF2-417 GEN
Solar/Wind Helper
0.308
961301AF2-421 GEN
Solar/Wind Helper
0.309
961331AF2-424 GEN
Solar/Wind Helper
0.302
961341AF2-425 GEN
Solar/Wind Helper
0.302
961421AF2-433 GEN
Solar/Wind Helper
0.302
961431AF2-434 GEN
Solar/Wind Helper
0.302
961611AG1-000B GEN
Solar/Wind Harmer
4.146
961611AG1-000B GEN
Solar/Wind Harmer
1.769
961681AG1-008 GEN
Solar/Wind Harmer
6.214
961951AG1-038 GEN
Solar/Wind Harmer
1.136
962861AG1-135 GEN
Solar/Wind Harmer
3.239
962971AG1-146 GEN
Solar/Wind Harmer
1.614
962981AG1-147 GEN
Solar/Wind Harmer
3.767
963071AG1-156 GEN
Solar/Wind Helper
1.001
963151AG1-164 GEN
Solar/Wind Helper
0.309
963161AG1-165 GEN
Solar/Wind Helper
0.309
963391AG1-188 GEN
Solar/Wind Helper
0.062
963401AG1-189 GEN
Solar/Wind Helper
0.043
966871AG1-558 GEN
Solar/Wind Harmer
0.26
966871AG1-558 GEN
Solar/Wind Harmer
0.089
966881AG1-559 GEN
Solar/Wind Harmer
0.269
966881AG1-559 GEN
Solar/Wind Harmer
0.092
970009AG2-005 GEN
Solar/Wind Harmer
1.078
970053AG2-049 GEN
Adder
1.707
970085AG2-068 GEN
Solar/Wind Harmer
4.94
970087AG2-069 GEN
Solar/Wind Harmer
7.409
970099AG2-077 GEN
Solar/Wind Harmer
2.697
970129AG2-093 GEN
Solar/Wind Harmer
4.756
970129AG2-093 GEN
Solar/Wind Harmer
1.926
970133AG2-095 GEN
Solar/Wind Harmer
0.953
970285AG2-188 GEN
Solar/Wind Harmer
6.934
970293AG2-193 GEN
Solar/Wind Harmer
1.071
970301AG2-198 GEN
Solar/Wind Harmer
3.936
970317AG2-208 GEN
Solar/Wind Harmer
3.912
970467AG2-304 GEN
50/50
15.27
970581AG2-369 GEN
Solar/Wind Harmer
4.248
970601AG2-382 GEN
Solar/Wind Harmer
3.458
970657AG2-426 GEN
Solar/Wind Harmer
2.604
970657AG2-426 GEN
Solar/Wind Harmer
0.544
970659AG2-427 GEN
Solar/Wind Harmer
4.431
970659AG2-427 GEN
Solar/Wind Harmer
0.785
970661AG2-428 GEN
Solar/Wind Harmer
8.843
970661AG2-428 GEN
Solar/Wind Harmer
1.567
970673AG2-436 GEN
Solar/Wind Harmer
17.036
970673AG2-436 GEN
Solar/Wind Harmer
8.626
970737AG2-469 GEN
Solar/Wind Harmer
4.42
970909AG2-566 GEN
Solar/Wind Harmer
0.747
970917AG2-570 GEN
Solar/Wind Harmer
19.793
970919AG2-571 GEN
Solar/Wind Harmer
2.505
970933AG2-581 GEN
Solar/Wind Harmer
7.52
970937AG2-583 GEN
Solar/Wind Harmer
5.84
971069AG2-661 GEN
Solar/Wind Harmer
1.334
971153AH1-033 GEN
Solar/Wind Harmer
1.009
971157AH1-035 GEN
Solar/Wind Harmer
0.994
971163AH1-040 GEN
Solar/Wind Harmer
7.509
971167AH1-042 GEN
Solar/Wind Harmer
8.225
971223AH1-071 GEN
Solar/Wind Harmer
1.075
971281AH1-106 GEN
Solar/Wind Harmer
1.396
971283AH1-107 GEN
Solar/Wind Harmer
1.396
971285AH1-108 GEN
Adder
0.574
971317AH1-138 GEN
Solar/Wind Harmer
1.057
971445AH1-216 GEN
Solar/Wind Harmer
5.176
971455AH1-223 GEN
Solar/Wind Harmer
2.52
971547AH1-271 GEN
Solar/Wind Harmer
1.976
971647AH1-324 GEN
Solar/Wind Harmer
4.206
971685AH1-345 GEN
Solar/Wind Harmer
0.963
219912AD2-042 GEN
Solar/Wind Helper
0.115
219919AE1-041 FULL
Solar/Wind Helper
0.003
227287AC2-120 GEN
Solar/Wind Helper
0.266
316431W1029_GEN1
Solar/Wind Harmer
1.486
316433W1029_GEN2
Solar/Wind Harmer
1.486
316435W1029_GEN3
Solar/Wind Harmer
1.486
939411AE1-173 GEN
Solar/Wind Harmer
41.494
940641AE2-051 GEN
Solar/Wind Harmer
7.777
941031AE2-094 GEN
Solar/Wind Harmer
15.312
957411AF2-035 GEN
Solar/Wind Harmer
4.024
957481AF2-042 GEN
Solar/Wind Harmer
6.742
957521AF2-046 GEN
Solar/Wind Harmer
6.214
957601AF2-054 GEN
Solar/Wind Harmer
0.256
957831AF2-077 GEN
Solar/Wind Harmer
0.255
957871AF2-081 GEN
Solar/Wind Harmer
4.142
957921AF2-086 GEN
Solar/Wind Helper
0.298
957971AF2-091 GEN
Solar/Wind Harmer
0.888
958261AF2-120 GEN
Solar/Wind Harmer
3.349
963691AG1-221 GEN
Solar/Wind Harmer
2.52
963711AG1-223 GEN
Solar/Wind Helper
0.048
964001AG1-254 GEN
Solar/Wind Helper
0.738
964051AG1-259 GEN
Solar/Wind Helper
0.044
964061AG1-260 GEN
Solar/Wind Helper
0.044
964211AG1-282 GEN
Solar/Wind Harmer
0.261
964851AG1-348 GEN
Solar/Wind Helper
0.059
965281AG1-393 GEN
Solar/Wind Harmer
1.054
965291AG1-394 GEN
Solar/Wind Harmer
0.704
966001AG1-469 GEN
Solar/Wind Harmer
0.179
966111AG1-480 GEN
Solar/Wind Helper
0.032
966131AG1-482 GEN
Solar/Wind Helper
0.066
966261AG1-495 GEN
Solar/Wind Helper
0.06
971741AH1-377 GEN
Solar/Wind Harmer
9.144
971761AH1-387 GEN
Solar/Wind Harmer
4.579
971777AH1-397 GEN
Solar/Wind Harmer
1.006
971781AH1-399 GEN
Solar/Wind Harmer
0.543
971845AH1-439 GEN
Solar/Wind Harmer
4.213
971967AH1-528 GEN
Solar/Wind Harmer
15.195
972003AH1-546 GEN
Solar/Wind Harmer
3.978
972135AH1-637 GEN
Solar/Wind Harmer
0.887
972183AH1-676 GEN
Adder
89.287
972185AH1-677 GEN
Adder
4.036
972187AH1-678 GEN
Adder
2.039
972189AH1-679 GEN
Adder
1.305
972193AH1-681 GEN
Adder
1.595
972195AH1-682 GEN
Adder
1.426
972197AH1-683 GEN
Adder
1.698
972199AH1-684 GEN
Adder
1.917
972201AH1-685 GEN
Adder
2.167
972205AH1-687 GEN
Adder
3.036
972213AH1-691 GEN
Adder
1.766
972215AH1-692 GEN
Adder
1.766
972217AH1-693 GEN
Adder
1.667
972219AH1-694 GEN
Adder
1.223
972223AH1-696 GEN
Adder
6.699
972255AH1-712 GEN
Adder
35.693
972257AH1-713 GEN
Adder
0.697
972265AH1-717 GEN
Adder
5.796
972277AH1-723 GEN
Adder
41.593
972289AH1-729 GEN
50/50
14.564
233950AC2-186 GEN
Solar/Wind Helper
0.091
233952AC2-187 GEN
Solar/Wind Helper
0.183
233954AC2-188 GEN
Solar/Wind Helper
0.183
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.819
CBM West 2LTFEXP_CBM-W2->PJM
CBM
43.81
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.851
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.786
NYPJM->LTFIMP_NY
CLTF
3.269
LGEELTFEXP_LGEE->PJM
CLTF
2.098
WECLTFEXP_WEC->PJM
CLTF
1.126
CPLELTFEXP_CPLE->PJM
CLTF
5.01
TVALTFEXP_TVA->PJM
CLTF
3.503
MECLTFEXP_MEC->PJM
CLTF
5.133
LAGNLTFEXP_LAGN->PJM
CLTF
6.958
SIGELTFEXP_SIGE->PJM
CLTF
0.162
AG2-052LTFEXP_AG2-052->PJM
LTF
0.067
AH1-155LTFEXP_AH1-155->PJM
LTF
0.101

Details for 8FRONT ROYAL-8MORRSVL 500.0 kV Ckt 1 line l/o AP_P1-2_PE-500-404T_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8FRONT ROYAL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-500-404T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.1 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3320.14
MW Contribution:2.04
Bus #Bus NameTypeMW Contribution
23503301WHY_Z2-039
50/50
0.01
23503901LHY_Z2-039
50/50
0.005
23544701WINZ1-113
50/50
1.002
23546401DTGZ2-030
Solar/Wind Harmer
0.001
23503401SHY_Z2-039
50/50
0.005
23503501NHY_Z2-039
50/50
0.007
3141426STAFORD
Solar/Wind Helper
0.056
3152511MT STM1
50/50
2.136
3152511MT STM1
50/50
2.153
3152521MT STM2
50/50
2.198
3152521MT STM2
50/50
2.207
3152531MT STM3
50/50
4.165
3152541MT STMG
50/50
1.735
3152701WARREN G1
50/50
6.315
3152711WARREN G2
50/50
6.315
3152721WARREN G3
50/50
6.315
3152731WARREN S1
50/50
11.789
3147666LOUISA
Solar/Wind Helper
0.962
3147666LOUISA
Solar/Wind Helper
0.553
3141196NOKESVL
Solar/Wind Helper
1.178
316411AF1-147_GEN1
Solar/Wind Helper
0.812
316415AF1-147_GEN2
Solar/Wind Helper
0.812
3132123MT JACKSON
Solar/Wind Harmer
0.414
3132273ORANGE
Solar/Wind Helper
0.05
238223AG1-045 C
Solar/Wind Harmer
4.62
238152AF2-075_GEN
Solar/Wind Harmer
0.006
238149AF1-291A_GEN
Solar/Wind Harmer
0.001
238147AE2-230_GEN1
Solar/Wind Harmer
0.004
315651AD1-115 GEN
Solar/Wind Helper
1.01
237061AD1-155 GEN
Solar/Wind Harmer
0.007
23583801GRNGAP
Solar/Wind Harmer
0.004
316447AC1-158 HLD
Solar/Wind Helper
3.97
316044AC1-158 PL1
Solar/Wind Helper
1.804
316045AC1-158 PL2
Solar/Wind Helper
5.774
316450AC1-158 RIC
Solar/Wind Helper
0.481
316006AB2-029 C
Solar/Wind Helper
0.159
316192AB2-158 GEN
Solar/Wind Helper
1.604
316254AC1-120 GEN1
Solar/Wind Helper
1.345
316170AC1-121 GEN2
Solar/Wind Helper
0.448
316164AC1-076 GEN
Solar/Wind Helper
1.413
3138216PACIFIC
Solar/Wind Helper
0.038
316095T157 G97
Solar/Wind Harmer
0.001
316097T157 G90
Solar/Wind Harmer
0.001
966881AG1-559 GEN
Solar/Wind Helper
0.311
970117AG2-086 GEN
Solar/Wind Harmer
3.18
970117AG2-086 GEN
Solar/Wind Harmer
2.12
970459AG2-300 GEN
50/50
18.942
970617AG2-403 GEN
Solar/Wind Harmer
10.871
970619AG2-404 GEN
Solar/Wind Harmer
10.871
971513AH1-254 GEN
Solar/Wind Harmer
5.725
971569AH1-283 GEN
Solar/Wind Harmer
15.934
964441AG1-307 GEN
Solar/Wind Harmer
5.331
964441AG1-307 GEN
Solar/Wind Harmer
0.888
965471AG1-415 GEN
Solar/Wind Harmer
4.21
971761AH1-387 GEN
Solar/Wind Harmer
6.674
972257AH1-713 GEN
50/50
2.041
CBM West 1LTFEXP_CBM-W1->PJM
CBM
32.542
CBM West 2LTFEXP_CBM-W2->PJM
CBM
20.677
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.884
NYPJM->LTFIMP_NY
CLTF
1.258
LGEELTFEXP_LGEE->PJM
CLTF
1.464
WECLTFEXP_WEC->PJM
CLTF
0.832
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.213
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.346
TVALTFEXP_TVA->PJM
CLTF
1.118
MECLTFEXP_MEC->PJM
CLTF
3.299
LAGNLTFEXP_LAGN->PJM
CLTF
2.241
SIGELTFEXP_SIGE->PJM
CLTF
0.107
CONTINGENCY 'AP_P2-3_PE-500-019B_SRT-A'
 DISCONNECT BRANCH FROM BUS 235105 TO BUS 200003 CKT 1   /*01DOUBS      500.0 - BRIGHTON     500.0
 DISCONNECT BRANCH FROM BUS 270095 TO BUS 235105 CKT 1   /*CHAN         500.0 - 01DOUBS      500.0
END
CONTINGENCY 'AP_P1-2_PE-500-404T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235110 TO BUS 313440 CKT 1   /*01MDWBRK     500.0 - 8VINTHIL     500.0
END
314290 to 223938 ckt 1
313911 to 314290 ckt 1
314929 to 314916 ckt 1

Winter Peak Analysis

The New Service Request AH1-713 was evaluated as a 0.0 MW (14.0 MW Capacity) injection in the Dominion area.

AH1-713 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 538.0 MW (0.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

(No impacts were found for this analysis)

Light Load Analysis

The New Service Request AH1-713 was evaluated as a 0.0 MW injection

AH1-713 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 538.0 MW (0.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

(No impacts were found for this analysis)

Short Circuit Analysis

Short Circuit analysis is not performed as part of the Phase I System Impact Study. Short Circuit analysis will commence in the Phase II System Impact Study.

Stability Analysis

Stability Analysis is Not Required.

Reactive Power Analysis

Reactive Power analysis is not performed as part of the Phase I System Impact Study. Reactive Power analysis will commence in the Phase II System Impact Study.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-139Hickory-Shawboro 230kVIn Service
AA2-178Mackeys 230kVIn Service
AA2-184Atlantic-Red Bank 34kVIn Service
AB1-001Absecon 12 kVIn Service
AB1-027Old Church 34.5 KVIn Service
AB1-096Carroll-Mt. Airy 34.5kVIn Service
AB1-124Carroll-Monocacy 34.5kVPartially in Service - Under Construction
AB1-125Carroll-Monocacy 34.5kVIn Service
AB1-127St. Thomas-Guilford 34.5kVIn Service
AB1-128St. Thomas-Mercersburg 34.5kVIn Service
AB1-138Navy 34.5kVIn Service
AB1-139Metuchen 26kVIn Service
AB1-141Church-Wye Mills 138 kV IIn Service
AB1-142Church-Wye Mills 138 kV IIIn Service
AB1-176Price 25kV IIEngineering & Procurement
AB2-022Elizabeth City 34.5kVIn Service
AB2-024Correctional 34.5kVIn Service
AB2-025Sapony 34.5kVIn Service
AB2-026Powhatan 34.5kVIn Service
AB2-029Remington 34.5kVIn Service
AB2-032Church-Wye Mills 138 kVIn Service
AB2-037Keeney-Steele 230kVUnder Construction
AB2-045Buckingham 34.5kVIn Service
AB2-049Gloucester Township 12kVIn Service
AB2-133Chestertown 69kVUnder Construction
AB2-134Hopewell-Surry 230kVIn Service
AB2-135Church-Kent 69kVIn Service
AB2-136Cambridge-West Cambridge 69kVUnder Construction
AB2-153Church-Wye Mills 138 kVIn Service
AB2-157Prince George's County 12kVIn Service
AB2-158Louisa-South Anna 230kVIn Service
AB2-161Waverly #2 DP 115kVIn Service
AB2-179Townsend 138kVIn Service
AB2-190Hopewell-Surry 230kVIn Service
AC1-010Gloucester 26kVUnder Construction
AC1-017Levittown 13 kVIn Service
AC1-027Pendleton 34.5kVIn Service
AC1-030Cinnaminson 13kVIn Service
AC1-076Locust Grove-Paytes 115kVIn Service
AC1-091Cedar Creek 138kV IEngineering & Procurement
AC1-092Cedar Creek 138kV IIEngineering & Procurement
AC1-093Cedar Creek 138kV IIIEngineering & Procurement
AC1-094Cedar Creek 138kV IVEngineering & Procurement
AC1-118Westmoreland 34.5kVIn Service
AC1-120Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-121Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-147Grassfield 34.5kVIn Service
AC1-158Spotsylvania 500kVIn Service
AC1-161Septa 500kVIn Service
AC1-164Chickahominy 230kVPartially in Service - Under Construction
AC1-191Elmont 115kVEngineering & Procurement
AC2-012Grassfield-Great Bridge 115kVIn Service
AC2-023Hebron 69kVEngineering & Procurement
AC2-079Ivor-Oak Ridge 115kVSuspended
AC2-120Ripley 69kVIn Service
AC2-136East Hagerstown 12kVUnder Construction
AC2-137Elko 34.5kVIn Service
AC2-138Northern Neck 34.5kVIn Service
AC2-141Septa 500kVEngineering & Procurement
AC2-165Bremo-Powhatan 230kVSuspended
AC2-186Harrington 25kVUnder Construction
AC2-187Harrington 69kVUnder Construction
AC2-188Harrington 69 kVUnder Construction
AD1-020Hunterstown-Lincoln 115 kVIn Service
AD1-022Cashie-Trowbridge 230 kVEngineering & Procurement
AD1-025Hopewell-Surry 230 kVUnder Construction
AD1-033Fentress-Landstown 230 kVIn Service
AD1-041Harmony Village-Shackleford 115 kVIn Service
AD1-060Mercersburg-Milnor 34.5 kVIn Service
AD1-061McConnelsburg-Mercersburg 34 kVIn Service
AD1-063Harmony Village 34.5 kVIn Service
AD1-074Trowbridge 230 kVEngineering & Procurement
AD1-075Trowbridge 230 kVEngineering & Procurement
AD1-076Trowbridge 230 kVEngineering & Procurement
AD1-082Bakers Pond-Ivor 115kVIn Service
AD1-105Kings Dominion DP 115 kVUnder Construction
AD1-115Mountain Run-Mitchell 115 kVEngineering & Procurement
AD1-144Kings Fork 34.5 kVIn Service
AD1-151Hopewell-Surry 230 kVSuspended
AD1-155Meadow Brook-Strasburg 138 kVIn Service
AD2-027Camden Switch 26 kVIn Service
AD2-030Wan 34.5 kVIn Service
AD2-042Camden Switch 26 kV IIIn Service
AD2-058St. Barnabas 13 kVIn Service
AD2-065Atco 12 kVIn Service
AD2-070Gilbert-Morris Park 34.5kVIn Service
AD2-073Sanders DP 230 kVIn Service
AD2-074Garner DP-Lancaster 115 kVEngineering & Procurement
AD2-085Myrtle-Windsor DP 115kVEngineering & Procurement
AD2-115Lyons-Moselem 69kVIn Service
AD2-116Hokes-Grantley 69 kVIn Service
AD2-135Williamstown 12kVPartially in Service - Under Construction
AD2-160Hickory-Moyock 230kVIn Service
AE1-041Edison 4kVIn Service
AE1-071Shade Gap-Roxbury 115 kVIn Service
AE1-072Shawboro-Sligo 230 kVUnder Construction
AE1-074Winterpock 34.5 kVUnder Construction
AE1-075Powhatan 34.5 kVIn Service
AE1-081Landing 12.47 kVIn Service
AE1-101McConnellsburg-Texas Eastern 138 kVIn Service
AE1-103Holland-Union Camp 115 kVUnder Construction
AE1-142Manitou-Pleasant Plains 34.5 kVIn Service
AE1-149Disputanta-Poe 115 kVSuspended
AE1-153Remington-Gordonsville 230 kVSuspended
AE1-155Garner-Northern Neck 115 kVIn Service
AE1-156Quakertown Solar II 34.5 kVPartially in Service - Under Construction
AE1-157Ladysmith CT-St. Johns 230 kVSuspended
AE1-162Smithfield 34.5 kVIn Service
AE1-173Carson-Suffolk 500 kVUnder Construction
AE1-175Light Foot 34.5 kVIn Service
AE1-185Hokes-Jackson 69 kVIn Service
AE1-190Harmony Village-Shackleford 115 kVPartially in Service - Under Construction
AE1-191Harmony Village-Shackleford 115 kVPartially in Service - Under Construction
AE1-196Hokes-Jackson 69 kV IIIn Service
AE1-229Deepwater-Upper Pittsgrove 138 kVSuspended
AE2-005Harmony Village-Shackleford 115 kVUnder Construction
AE2-019New Road 230 kVUnder Construction
AE2-027Harrowgate-Locks 115kVUnder Construction
AE2-033Clubhouse-Sapony 230 kVSuspended
AE2-034Mackeys 230 kVPartially in Service - Under Construction
AE2-042Milton 69 kVIn Service
AE2-051Carson-Septa 500 kVEngineering & Procurement
AE2-054Warfordsburg 34 kVIn Service
AE2-059Derry Tap-Derry Bus 69 kVIn Service
AE2-060Mifflintown Bus-Mifflintown Tap 69 kVIn Service
AE2-094Carson-Rogers Road 500 kVEngineering & Procurement
AE2-104Suffolk 115 kVSuspended
AE2-133Penns Tap-Richfield Tie 69 kVIn Service
AE2-175Jackson-Long Pond 69 kVPartially in Service - Under Construction
AE2-212Harrowgate 34 kVEngineering & Procurement
AE2-230Bartonsville-Meadow Brook 138 kVIn Service
AE2-253Hickory-Moyock 230 kVIn Service
AF1-007Indian River 230 kV ISuspended
AF1-014Harmony Village-Shackleford 115 kVUnder Construction
AF1-017Myrtle-Windsor 115 kVEngineering & Procurement
AF1-032Suffolk 34.5 kVIn Service
AF1-042Garner DP-Lancaster 115 kVEngineering & Procurement
AF1-069Carson-Rogers Rd 500 kVEngineering & Procurement
AF1-114Oak Grove-Dahlgren 230 kVEngineering & Procurement
AF1-123Harper 230 kVActive
AF1-124Harper 230 kVActive
AF1-125Harper 230 kVActive
AF1-128Chesterfield 230 kVActive
AF1-129Chesterfield 230 kVEngineering & Procurement
AF1-147Poland Rd-Runway DP 230kVUnder Construction
AF1-254Milnor-Huyetts 34.5 kVUnder Construction
AF1-262Upper Pittsgrove 12 kVIn Service
AF1-264Runnemede 13 kVIn Service
AF1-291Tyler 34.5 kVEngineering & Procurement
AF1-291ABartonsville-Meadow Brook 138 kVIn Service
AF1-299Otter Point 34.5 kV IIn Service
AF1-300Otter Point 34.5 kV IIIn Service
AF1-320Merrill Creek 115 kVEngineering & Procurement
AF1-333Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-337Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-338Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-339Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF2-035St. Johns 115 kVActive
AF2-042Clover-Rawlings 500 kVActive
AF2-043Suffolk 34.5 kVIn Service
AF2-046Tunis-Mapleton 115 kVActive
AF2-054Wan 34.5 kVIn Service
AF2-075Bartonsville-Meadow Brook 138 kV IIIIn Service
AF2-077White Marsh 34.5 kVIn Service
AF2-081Moyock 230 kVActive
AF2-086Scott Tap-Bowmans Mill Tap 69 kVEngineering & Procurement
AF2-091Oak Grove-Dahlgren 230 kVEngineering & Procurement
AF2-110Suffolk 115 kVSuspended
AF2-120Garner-Northern Neck 115 kVActive
AF2-138Flanders-West Wharton 34.5 kVIn Service
AF2-139Gilbert-Warren Glen 34.5 kVIn Service
AF2-144Powhatan 34.5 kVIn Service
AF2-192Frenchtown Solar-West Flemington 34.5 kVSuspended
AF2-229Roxbury 23 kVEngineering & Procurement
AF2-233Penns-Richfield Tie #1 69 kVEngineering & Procurement
AF2-234Sunbury Yard #1-Richfield Tie #2 69 kVEngineering & Procurement
AF2-247Bustleton 13.2 kVIn Service
AF2-250Edgewood 12 kV IIIIn Service
AF2-325Jacktown 12 kVEngineering & Procurement
AF2-354Washington 34.5 kV IIEngineering & Procurement
AF2-361Mifflintown Tap 69 kVEngineering & Procurement
AF2-378Cambridge 12 kVEngineering & Procurement
AF2-379Princess Anne 25 kVUnder Construction
AF2-383Tolna 115 kVWithdrawn
AF2-417West Damascus Tap-West Damascus 69 kVEngineering & Procurement
AF2-421East Hazelton-Weatherly Tap 69Engineering & Procurement
AF2-424Reed-Reed Tap #1 69 kVEngineering & Procurement
AF2-425Reed-Reed Tap#1 69 kVEngineering & Procurement
AF2-433Columbia-Geisinger Tap #1 69 kVEngineering & Procurement
AF2-434Columbia-Geisinger Tap #1 69 kVEngineering & Procurement
AG1-008Tunis-Mapleton 115 kVActive
AG1-038Garner DP-Lancaster 115 kVEngineering & Procurement
AG1-045Redbud-Gaylord 34.5 kVSuspended
AG1-135Garner-Lancaster 115 kVActive
AG1-145Lightfoot 34.5 kVIn Service
AG1-146Garner DP-Lancaster 115 kVActive
AG1-147Garner DP-Lancaster 115 kVActive
AG1-156Jack Frost-Lake Harmony 69 kVEngineering & Procurement
AG1-164East Hazelton-Weatherly Tap 69 kVEngineering & Procurement
AG1-165East Hazelton-Weatherly Tap 69 kVEngineering & Procurement
AG1-188Manitou-Oyster Creek 34.5 kVEngineering & Procurement
AG1-189Oyster Creek-Bamber Lake 34.5Engineering & Procurement
AG1-191Chester-Pohatcong Mountain 34.5 kVPartially in Service - Under Construction
AG1-221Poland Rd-Runway DP 230 kVUnder Construction
AG1-223Larrabee-Allaire 34.5 kVUnder Construction
AG1-254Salem-Woodstown 69 kVEngineering & Procurement
AG1-259Sunbury-Dalmatia 69 kVEngineering & Procurement
AG1-260Sunbury-Dalmatia 69 kVEngineering & Procurement
AG1-282Dunnsville 34.5 kVEngineering & Procurement
AG1-307Old Chapel-Millville 138 kVEngineering & Procurement
AG1-348Pequest River-Washington 34.5 kVIn Service
AG1-393Sapony 34.5 kVActive
AG1-394Boykins 34.5 kVActive
AG1-397Walston 12 kVWithdrawn
AG1-415Double Toll Gate-Old Chapel 138 kVEngineering & Procurement
AG1-469Gordonsville 34.5 kVEngineering & Procurement
AG1-480Shawnee 34.5 kVEngineering & Procurement
AG1-482Hamilton 115 kVWithdrawn
AG1-495Gilbert-Rocktown 34.5 kVEngineering & Procurement
AG1-499Lambs 12.47 kVUnder Construction
AG1-558Buckner 34.5 kVEngineering & Procurement
AG1-559Caroline Pines 22 kVEngineering & Procurement
AG2-005Garner DP-Lancaster 115 kVActive
AG2-049Van Dorn 34.5 kVActive
AG2-068Heritage - Wake 500 kVActive
AG2-069Heritage - Wake 500 kVActive
AG2-077Clover-Rawlings 500 kVActive
AG2-086Mt. Jackson DP-Mt. Jackson 115 kVActive
AG2-093Colonial Trail-Hopewell 230 kVActive
AG2-095Hopewell 34.5 kV (Circuit 313)Active
AG2-188Farmville - Buckingham 230 kVActive
AG2-193Turner 34.5 kVActive
AG2-198Briery - Finneywood 230 kVActive
AG2-208Greenwood DP - St. Johns DP 115 kVActive
AG2-300Meadow Brook 138 kVActive
AG2-304Liberty 230 kVActive
AG2-369Heritage - Wake 500 kVActive
AG2-382Cashie 230 kVActive
AG2-403Meadow Brook - Mt. Storm 500 kVActive
AG2-404Meadow Brook - Mt. Storm 500 kV IIActive
AG2-426Wakefield - Waverly 115 kVActive
AG2-427Waverly 115 kVActive
AG2-428Wakefield 115 kVActive
AG2-436Carson - Rogers Road 500 kVActive
AG2-469Westmoreland – Oak Grove 230 kVActive
AG2-566Briery - Finneywood 230 kVActive
AG2-570Heritage - Wake 500 kVActive
AG2-571Heritage - Wake 500 kVActive
AG2-581Rawlings-Clover 500 kVActive
AG2-583Bremo - Cartersville 230 kVActive
AG2-661Hopewell - Colonial Trail 230 kVActive
AH1-033Sligo 34.5 kVActive
AH1-035Plymouth 34.5 kVActive
AH1-040Mackeys - Creswell 115 kVActive
AH1-042Providence Forge-Turner 115kVActive
AH1-071Midlothian 34.5 kVActive
AH1-106Winterpock 34.5kVActive
AH1-107Winterpock 34.5kVActive
AH1-108Spruance NUG 230 kVActive
AH1-138Penniman 34.5 kVActive
AH1-216Smithfield-Surry 230 kVActive
AH1-223Poland Rd-Runway DP 230 kVActive
AH1-254Greenland Gap 500 kV IIActive
AH1-271Cashie 230 kVActive
AH1-283Mount Storm-Pruntytown 500kVActive
AH1-324Colonial Trail – Surry 230 kVActive
AH1-345Remington 324 34.5 kVActive
AH1-377Clover- Farmville 230kVActive
AH1-387Meadowbrook-Greenland Gap 500kVActive
AH1-397Shacklesford 34.5 kVActive
AH1-399North Doswell 12.5 kVActive
AH1-439Buckingham- Farmville 230kVActive
AH1-528Rawlings - Unity 500 kVActive
AH1-546Bremo - Buckingham 230 kVActive
AH1-637Oak Grove 34.5 kVActive
AH1-676Gordonsville 230 kVActive
AH1-677Rogers Road 500 kVActive
AH1-678Heritage 500 kVActive
AH1-679Four Rivers 230 kVActive
AH1-681Cunningham 500 kVActive
AH1-682Ladysmith CT 230 kVActive
AH1-683Ladysmith CT 230 kVActive
AH1-684Remington CT 230 kVActive
AH1-685Remington CT 230 kVActive
AH1-687Bear Garden 230kVActive
AH1-691Ladysmith CT 230 kVActive
AH1-692Ladysmith CT 230 kVActive
AH1-693Remington CT 230 kVActive
AH1-694Ladysmith CT 230 kVActive
AH1-696Possum Point 230kVActive
AH1-712Cunningham 500 kVActive
AH1-717Surry 230kVActive
AH1-723Cunningham 500 kVActive
AH1-729Ocean Court 230 kVActive
V4-067Cates Road Egg Harbor Township 12kVDeactivated
V4-068Murphy's 34.5kVIn Service
W1-003Oak HallIn Service
W1-004Oak HallIn Service
W1-005Oak HallIn Service
W1-006Oak HallIn Service
W1-130Vine Road 12kVIn Service
W2-030Egg Harbor TownshipIn Service
W3-077Broadway-Stewartsville 34.5kVIn Service
X3-066Church Hill 69kVIn Service
Y1-079Wye Mills 69kVIn Service
Y1-080Dorchester 12kVIn Service
Y1-086Morgans CornerIn Service
Y3-058Rockawalkin 69kVIn Service
Z1-036WinFall-Chowan 230kVIn Service
Z2-027Pasquotank 34.5kVIn Service
Z2-076Worcester South 25kVIn Service
Z2-077Worcester North 25kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with potential Affected System impacts. PJM initiates coordination with each Affected System Operator by providing a list of New Service Requests in the Cycle with potential impacts to their respective system. If the Affected System Operator indicates an Affected System Study is required, PJM will notify the Project Developer or Eligible Customer of the need for an Affected System Study. See below if any Affected System Operator requires a study for this project:

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

No cost allocated system reinforcements were identified for this project in the Phase I System Impact Study load flow analysis.

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: b4000.327
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.327
Title
Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.
Description
Upgrade/install equipment at Ladysmith substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230kV strings of breaker and a half scheme.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AH1-713 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-713 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8FRONT ROYAL 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Kraken to accommodate the new 500kV line from North Anna to Kraken.
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-713 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-713 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8FRONT ROYAL 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029

Not Contingent

Note: AH1-713 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-713 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8FRONT ROYAL 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-713 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-713 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8FRONT ROYAL 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AH1-713 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-713 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8FRONT ROYAL 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AH1-713 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-713 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8FRONT ROYAL 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AH1-713 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-713 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8FRONT ROYAL 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.325
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.325
Title
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Description
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AH1-713 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-713 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8FRONT ROYAL 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Kraken substation into Yeat substation
Description
Cut-in 500kV line from Kraken substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-713 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-713 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8FRONT ROYAL 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.356
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-713 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-713 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8FRONT ROYAL 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AH1-713 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-713 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8FRONT ROYAL 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AH1-713 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-713 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8FRONT ROYAL 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.326
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.326
Title
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Description
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AH1-713 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-713 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8FRONT ROYAL 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029

Not Contingent

Note: AH1-713 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-713 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8FRONT ROYAL 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.355
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.355
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AH1-713 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-713 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8FRONT ROYAL 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AH1-713 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-713 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8FRONT ROYAL 500.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2097
Title
Build a new 11.95 mile line from Aspen 230 kV to Dickerson 230 kV with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor at 250 degrees C.
Description
Build a new 11.95 mile line from Aspen 230 kV to Dickerson 230 kV with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor at 250 degrees C.
Total Cost ($USD)
$33,230,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-713 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-713 could receive cost allocation. Although AH1-713 may not presently have cost responsibility for this upgrade, AH1-713 is a potential Aggregate Pool Contributor.

FacilityContingency
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 linePEPCO_P1_5070_SRT-A
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 lineAP_P2-3_PE-500-019B_SRT-A
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 lineAP_P2-3_PE-500-019F_SRT-SL
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 lineAP_P1-2_PE-500-406T_SRT-A
DICKH230-6EDFERRY 230.0 kV Ckt 1 lineAP_P2-3_PE-500-019F_SRT-SL
DICKH230-6EDFERRY 230.0 kV Ckt 1 lineAP_P2-3_PE-500-019B_SRT-A
DICKH230-6EDFERRY 230.0 kV Ckt 1 linePEPCO_P1_5070_SRT-A
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.242
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.242
Title
Upgrading switches 20366M and 20369M and line leads to 4000A continuous current rating of 230kV Line #203 at Edwards Ferry substation
Description
Upgrading switches 20366M and 20369M and line leads to 4000A continuous current rating of 230kV Line #203 at Edwards Ferry substation
Cost Information
Time Estimate
Sep 13 2030

Not Contingent

Note: AH1-713 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-713 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.244
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b3800.244
Title
Rebuild 7.26 miles of existing 230 kV circuit from Dickerson Station H to Ed's Ferry area to accommodate the new 500 kV circuit between Doubs and Aspen. (The 230kV portion of the project)
Description
Rebuild 7.26 miles of existing 230 kV circuit from Dickerson Station H to Ed's Ferry area to accommodate the new 500 kV circuit between Doubs and Aspen. (The 230kV portion of the project)
Cost Information
Time Estimate
Dec 31 2030

Not Contingent

Note: AH1-713 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-713 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
(Pending) / (Pending)
Title
Additional Aspen to Dickerson H 230 kV line
Description
PEPCO’s substation cost to accommodate an additional circuit at Dickerson H to be approximately $7.86 million. The cost for the remaining 7.25 miles of 230 kV transmission line is estimated at $78.62 million.
Total Cost ($USD)
$86,480,000
Allocated Cost ($USD)
$0
Time Estimate
24 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-713 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-713 could receive cost allocation. Although AH1-713 may not presently have cost responsibility for this upgrade, AH1-713 is a potential Aggregate Pool Contributor.

FacilityContingency
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)

Attachments

AH1-713 One Line Diagram

AH1-713 One Line Diagram.pdf
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.