AH1-723 Phase I Study Report

v1.00 released 2025-10-29 20:18

Cunningham 500 kV

712.0 MW Capacity / 776.0 MW Energy

Introduction

This Phase I System Impact Study Report (PH1) has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, sections 307 and 308 for New Service Requests (projects) in Transition Cycle 2. The Project Developer/Eligible Customer (developer) is Tenaska Power Generation, LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Virginia Electric and Power Company (d/b/a Dominion Energy Virginia).

Preface

The Phase I System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle executive summary format and (ii) an individual project-level basis. The Phase I System Impact Study Results (for both the executive summary and individual reports) will be publicly available on PJM’s website. Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.3, PJM takes the following actions during the Phase I System Impact Study:
  1. PJM studies each New Service Request on a summer peak, winter peak and light load RTEP base case study. The case year is dependent on the new services cycle under study. PJM will identify the base case year to be used in the study of a specific cycle on its website.
  2. PJM will only perform load flow analysis during the Phase I System Impact Study.
  3. In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with Affected System impacts and provides each Affected System Operator with a list of New Service Request in the Cycle with potential impacts to their respective system.
  4. PJM will create both the short circuit and stability base cases to be used in the Phase II System Impact Study.
  5. The Phase I System Impact Study results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.
The Transmission Owner takes the following actions during the Phase I System Impact Study:
  1. Identify required Interconnection Facilities to accommodate the New Service Request.
  2. Identify required Network Upgrades to mitigate system violations from the Phase I System Impact Study.
  3. Provide planning-level preliminary estimates of Interconnection Facilities and Network Upgrades including scope, cost and elapsed time to complete the work.

Decision Point I Requirements

At the close of Phase I System Impact Study, PJM will initiate Decision Point I (DP1). During DP1, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.A.1. Additional information on these elements is available in PJM Manual 14H sections 4.4, 6, and 7.

Allowable project modifications at Decision Point I are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

General

The Project Developer has proposed a Natural Gas generating facility located in the Virginia Electric and Power Company (d/b/a Dominion Energy Virginia) zone — Fluvanna County, Virginia. The installed facilities will have a total capability of 776.0 MW with 712.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AH1-723
Project Name:
Cunningham 500 kV
Project Developer Name:
Tenaska Power Generation, LLC
State:
Virginia
County:
Fluvanna
Transmission Owner:
Virginia Electric and Power Company (d/b/a Dominion Energy Virginia)
MFO:
776.0
MWE:
776.0
MWC:
712.0
Fuel Type:
Natural Gas
Basecase Study Year:
2028

Physical Interconnection Facility Study

Physical Interconnection Facilities Study is not performed as part of the Phase I System Impact Study. Physical Interconnection Facilities Study will commence in the Phase II System Impact Study.

Point of Interconnection

AH1-723 will interconnect on the Virginia Electric and Power Company (d/b/a Dominion Energy Virginia) transmission system at the Cunningham 500 kV substation.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In the Phase I SIS, the costs shown are subject to change as a result of a facility study performed by the TO during the Phase II or Phase III System Impact Study.

Based on the Phase I SIS results, the AH1-723 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit are also shown below.

Cost Summary
DescriptionCost Allocated to AH1-723Cost Subject to Readiness*
Transmission Owner Interconnection Facilities (TOIF)$2,100,000$0
Other Scope$0$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0
Network Upgrades$3,500,000$3,500,000
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$144,696,392$144,696,392
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$0$0
Total$150,296,392$148,196,392

* Contributes to calculation for Readiness Deposit #2 (RD2). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 309 (Decision Point I) A.1.a.i and PJM Manual 14H, section 6.2, Readiness Deposit #2 (RD2) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point I (DP1), the Project Developer or Eligible Customer is required to submit Readiness Deposit #2, which is calculated as 10% of cost allocation for required Phase I Network Upgrades minus Readiness Deposit #1.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Readiness Deposit #2 Due for Project AH1-723

Readiness Deposit #2 has been calculated for the project based on the Phase I System Impact Study results and is shown in the table below. This Readiness Deposit #2 must be provided at Decision Point I through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit
Project ID10% of cost allocation for Phase I Network UpgradesReadiness Deposit #1 Received (RD1)Readiness Deposit #2 (RD2) for AH1-723 Project due at DP1
ABA - B
AH1-723$14,819,639$3,104,000$11,715,639

Note: Failure to provide an acceptable form of Readiness Deposit #2 by the end of Decision Point I will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Interconnection Facilities
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)Install the Point of Change in Ownership (PCO) disconnect switch, the overhead line conductor from the PCO to the bus position that serves as the Point of Interconnection (POI), as well as any metering and associated protection equipment.$4,200,000 $2,100,000 (See Note 1)
Network Upgrades
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)Add two (2) new 500 kV breakers to the existing Cunningham 500 kV Substation. This station will serve as the interconnection location for AH1-712 and AH1-723, where the projects will be sharing interconnection facilities. Additional substation modification/expansion cost may be required after detailed design.$7,000,000 $3,500,000 (See Note 1)

Based on the scope of work for the Interconnection Facilities, it is expected to take a range of 50 to 54 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

The schedule for any required Network Impact Reinforcements will be more clearly identified in the Phase II and Phase III System Impact Studies.

Note 1: A Common Use Upgrade is a Network Upgrade that is needed for the interconnection of Generating Facilities or Merchant Transmission Facilities of more than one Project Developer or Eligible Customer and which is the shared responsibility of each Project Developer or Eligible Customer. If multiple Project Developers request to connect to the same interconnection substation, the Transmission Owner will determine the cost to accommodate all the requests at the substation. The cost for the interconnection will be allocated in proportion to the number of required terminations into the substation.

Transmission Owner Analysis

PJM performed a power flow analysis of the transmission system using a 2028 load flow model and the results were verified by Dominion.

 

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. Dominion interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AH1-723 was evaluated as a 776.0 MW (712.0 MW Capacity) injection in the Dominion area.

AH1-723 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 776.0 MW (776.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2DVP
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line
DVP_P1-2: LN 553_SRT-S
SingleAC122.22 %984.18B1202.8862.57
GD2DVP
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC110.1 %984.18B1083.6237.31
GD2DVP/PEPCO
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
PEPCO_P1_5070_SRT-A
SingleAC152.59 %1331.98B2032.4942.85
GD2DVP/PEPCO
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
DVP_P4-2: H2T560_SRT-A
BreakerAC146.61 %1417.0B2077.4642.84
GD2DVP/PEPCO
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
DVP_P4-2: H1T560_SRT-A
BreakerAC146.6 %1417.0B2077.3942.84
GD2DVP/PEPCO
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
DVP_P4-2: 560T571_SRT-S
BreakerAC145.68 %1417.0B2064.2942.6
GD2DVP/PEPCO
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
AP_P2-3_PE-500-019F_SRT-SL
BreakerAC140.29 %1417.0B1987.8935.15
GD2DVP/PEPCO
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
AP_P2-3_PE-500-019B_SRT-A
BreakerAC131.46 %1417.0B1862.7241.59
GD2DVP/PEPCO
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
DVP_P7-1: LN 514-2098_SRT-S
TowerAC104.66 %1417.0B1482.9933.84
GD2DVP
6ELMONT-6HANOVER 230.0 kV Ckt 1 line
DVP_P4-2: 574T575_SRT-S
BreakerAC121.7 %1409.0C1714.7455.73
GD2DVP
6ELMONT-6HANOVER 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC105.87 %1123.3B1189.2152.28
GD2DVP
6FOUR RIVERS-6STJOHN 230.0 kV Ckt 1 line
DVP_P4-2: 574T575_SRT-S
BreakerAC188.55 %1360.0C2564.351.71
GD2DVP
6FOUR RIVERS-6STJOHN 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC178.97 %1123.3B2010.3448.26
GD2DVP
6FOUR RIVERS-6STJOHN 230.0 kV Ckt 1 line
DVP_P4-2: H1T574_SRT-S
BreakerAC156.82 %1360.0C2132.843.3
GD2DVP
6FOUR RIVERS-6STJOHN 230.0 kV Ckt 1 line
DVP_P4-2: 557T574_SRT-S
BreakerAC155.64 %1360.0C2116.7253.82
GD2DVP
6FOUR RIVERS-6STJOHN 230.0 kV Ckt 1 line
DVP_P4-2: H2T574_SRT-S
BreakerAC153.64 %1360.0C2089.5245.63
GD2DVP
6HANOVER-6FOUR RIVERS 230.0 kV Ckt 1 line
DVP_P4-2: 574T575_SRT-S
BreakerAC121.42 %1360.0C1651.3355.73
GD2DVP
6HANOVER-6FOUR RIVERS 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC100.18 %1123.3B1125.3252.28
GD2DVP
6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line
DVP_P1-2: LN 553_SRT-S
SingleAC114.98 %984.18B1131.5762.57
GD2DVP
6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC103.16 %984.18B1015.2637.31
GD2DVP
6LDYSMITH CT-6SUMMIT 230.0 kV Ckt 1 line
DVP_P4-2: 568T581_SRT-S
BreakerAC135.94 %1809.0C2459.1236.74
GD2DVP
6MINE RD-6FREDBRG 230.0 kV Ckt 1 line
DVP_P4-2: 568T581_SRT-S
BreakerAC166.64 %1303.0C2171.2836.74
GD2DVP
6PROFFIT-6HOLLYMD 230.0 kV Ckt 1 line
DVP_P1-2: LN 553_SRT-S
SingleAC118.67 %984.18B1167.9662.57
GD2DVP
6PROFFIT-6HOLLYMD 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC106.71 %984.18B1050.1837.31
GD2DVP
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 574T575_SRT-S
BreakerAC140.5 %1809.0C2541.7151.66
GD2DVP
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC134.25 %1478.62B1985.0148.21
GD2DVP
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line
DVP_P4-2: H1T574_SRT-S
BreakerAC116.92 %1809.0C2115.1643.25
GD2DVP
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 557T574_SRT-S
BreakerAC116.03 %1809.0C2098.9253.78
GD2DVP
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line
DVP_P4-2: H2T574_SRT-S
BreakerAC114.28 %1809.0C2067.2745.58
GD2DVP
6SUMMIT-6MINE RD 230.0 kV Ckt 1 line
DVP_P4-2: 568T581_SRT-S
BreakerAC165.56 %1360.0C2251.6336.74
GD2DVP
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
PEPCO_P1_5070_SRT-A
SingleAC140.61 %1478.62B2079.0942.85
GD2DVP
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
DVP_P4-2: H2T560_SRT-A
BreakerAC117.42 %1809.0C2124.1542.84
GD2DVP
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
DVP_P4-2: H1T560_SRT-A
BreakerAC117.42 %1809.0C2124.0842.84
GD2DVP
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
DVP_P4-2: 560T571_SRT-S
BreakerAC116.69 %1809.0C2110.9942.6
GD2DVP
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
AP_P2-3_PE-500-019F_SRT-SL
BreakerAC112.48 %1809.0C2034.7835.15
GD2DVP
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
AP_P2-3_PE-500-019B_SRT-A
BreakerAC105.55 %1809.0C1909.4141.59
GD2DVP
8BRAMBLETON-AH1-727 TP 500.0 kV Ckt 1 line
DVP_P1-2: LN 9344_SRT-A
SingleAC106.63 %3256.16B3472.0797.34
GD2DVP
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
DVP_P1-2: LN 594_SRT-S
SingleAC132.78 %4070.2B5404.5298.37
GD2DVP
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
DVP_P1-2: LN 573_SRT-S
SingleAC123.02 %4070.2B5007.0896.94
GD2DVP
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
DVP_P4-2: 545T594_SRT-S
BreakerAC122.59 %3966.0C4861.7381.78
GD2DVP
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
DVP_P4-2: H1T594_SRT-S
BreakerAC113.53 %5010.0C5687.8298.63
GD2DVP
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
DVP_P4-2: SPOTS H1T594_SRT-S
BreakerAC113.37 %5010.0C5679.6398.36
GD2DVP
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
DVP_P4-2: 515T594_SRT-S
BreakerAC113.36 %5010.0C5679.3798.37
GD2DVP
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
DVP_P4-2: H1T573_SRT-S
BreakerAC111.05 %5010.0C5563.7698.9
GD2DVP
8CUNINGHAM-8ELMONT 500.0 kV Ckt 1 line
DVP_P4-1: FLUVANN GT22_SRT-S
BreakerAC103.39 %2858.0C2955.0328.79
GD2DVP
8CUNINGHAM-8ELMONT 500.0 kV Ckt 1 line
DVP_P1-2: LN 542_SRT-S
SingleAC103.0 %2858.0B2943.79328.79
GD2DVP
8ELMONT-6ELMONT 500.0/230.0 kV Ckt 2 transformer
DVP_P4-2: H1T574_SRT-S
BreakerAC108.02 %1052.4C1136.79109.32
GD2DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P2-2: ELMONT B1_SRT-S
BusAC183.41 %2858.0C5241.92204.9
GD2DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P2-2: LADYSMITH B2_SRT-S
BusAC177.49 %2913.0C5170.16196.57
GD2DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC173.01 %4070.2B7041.78191.94
GD2DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P4-2: H4T581_SRT-S
BreakerAC159.56 %2913.0C4648.04184.68
GD2DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P4-2: H1T581_SRT-S
BreakerAC158.77 %2913.0C4624.92183.92
GD2DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S
SingleAC153.9 %4070.2B6264.0183.58
GD2DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P4-2: 57602_SRT-S
BreakerAC149.23 %5011.0C7478.0192.1
GD2DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P4-2: WT576_SRT-S
BreakerAC149.23 %5011.0C7477.96192.1
GD2DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Base Case
SingleAC118.98 %4070.2A4842.75196.77
GD2DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P7-1: LN 2090-256_SRT-S
TowerAC112.2 %5011.0C5622.33190.63
GD2DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P7-1: LN 2076-2145_SRT-A-2
TowerAC110.02 %5011.0C5512.93187.62
GD2DVP
8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
DVP_P1-2: LN 573_SRT-S
SingleAC126.22 %4070.2B5137.2299.58
GD2DVP
8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
DVP_P1-2: LN 594_SRT-S
SingleAC124.64 %4070.2B5073.1597.14
GD2DVP
8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
DVP_P4-2: SPOTS H1T594_SRT-S
BreakerAC110.22 %5011.0C5523.2898.54
GD2DVP
8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
DVP_P4-2: 57302_SRT-S
BreakerAC108.51 %5011.0C5437.6399.54
GD2DVP
8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
DVP_P4-2: XT573_SRT-S
BreakerAC108.51 %5011.0C5437.599.54
GD2DVP
8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
DVP_P4-2: 515T573_SRT-S
BreakerAC108.24 %5011.0C5423.6799.58
GD2DVP
8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
DVP_P4-2: H1T573_SRT-S
BreakerAC107.86 %5011.0C5404.7799.08
GD2DVP
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
DVP_P1-2: LN 581_SRT-S
SingleAC130.67 %3220.44B4208.184.96
GD2DVP
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
DVP_P1-2: LN 552_SRT-S
SingleAC130.56 %3220.44B4204.6384.67
GD2DVP
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
DVP_P4-2: 545T552_SRT-S
BreakerAC119.2 %3940.0C4696.3286.5
GD2DVP
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
DVP_P4-2: 545T594_SRT-S
BreakerAC115.13 %3940.0C4535.9380.59
GD2DVP
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
DVP_P4-2: H4T581_SRT-S
BreakerAC112.18 %3940.0C4419.984.96
GD2DVP
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
DVP_P4-2: H3T552_SRT-S
BreakerAC112.16 %3940.0C4419.2284.69
GD2DVP
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
DVP_P4-2: H1T552_SRT-S
BreakerAC112.08 %3940.0C4415.884.67
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC175.45 %3220.44B5650.1476.92
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P4-2: H2T574_SRT-S
BreakerAC154.63 %3940.0C6092.4378.72
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P4-2: H1T574_SRT-S
BreakerAC152.97 %3940.0C6027.1375.54
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P4-2: 574T575_SRT-S
BreakerAC132.12 %3940.0C5205.669.84
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P4-2: 568T581_SRT-S
BreakerAC210.08 %3940.0C8277.02133.53
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P4-2: 574T575_SRT-S
BreakerAC174.96 %3940.0C6893.473.59
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P1-2: LN 552_SRT-S
SingleAC172.64 %3220.44B5559.8887.35
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P1-2: LN 581_SRT-S
SingleAC171.66 %3220.44B5528.2789.32
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P4-2: H1T581_SRT-S
BreakerAC150.52 %3940.0C5930.6589.64
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P4-2: H1T552_SRT-S
BreakerAC148.0 %3940.0C5831.0487.35
GD2DVP/PJM
8POSSUM-BURCHES 500.0 kV Ckt 1 line
AP_P2-3_PE-500-019B_SRT-A
BreakerAC114.93 %3099.0B3561.8383.44
GD2DVP/PJM
8POSSUM-BURCHES 500.0 kV Ckt 1 line
AP_P2-3_PE-500-019F_SRT-SL
BreakerAC107.21 %3099.0B3322.4269.27
GD2DVP/PJM
8POSSUM-BURCHES 500.0 kV Ckt 1 line
AP_P1-2_PE-500-406T_SRT-A
SingleAC105.05 %2913.06B3060.2168.71
GD2DVP/PJM
8POSSUM-BURCHES 500.0 kV Ckt 1 line
PEPCO_P4_PP41_SRT-A
BreakerAC103.72 %3099.0B3214.4169.2
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P4-2: 568T581_SRT-S
BreakerAC211.93 %3940.0C8350.21129.9
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P4-2: 545T552_SRT-S
BreakerAC182.6 %3118.0C5693.4386.3
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P1-2: LN 552_SRT-S
SingleAC179.85 %3220.44B5791.8288.61
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P4-2: 574T575_SRT-S
BreakerAC179.37 %3940.0C7067.1472.11
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P1-2: LN 581_SRT-S
SingleAC175.06 %3220.44B5637.786.87
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P4-2: H1T552_SRT-S
BreakerAC154.28 %3940.0C6078.7988.61
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P4-2: H3T552_SRT-S
BreakerAC154.01 %3940.0C6067.8988.53
GD2DVP
AE1-157 TAP-6LDYSMITH CT 230.0 kV Ckt 1 line
DVP_P4-2: 574T575_SRT-S
BreakerAC143.48 %1809.0C2595.5951.66
GD2DVP
AE1-157 TAP-6LDYSMITH CT 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC137.7 %1478.62B2036.0148.21
GD2DVP
AE1-157 TAP-6LDYSMITH CT 230.0 kV Ckt 1 line
DVP_P4-2: H1T574_SRT-S
BreakerAC120.09 %1809.0C2172.4943.25
GD2DVP
AE1-157 TAP-6LDYSMITH CT 230.0 kV Ckt 1 line
DVP_P4-2: 557T574_SRT-S
BreakerAC119.2 %1809.0C2156.353.78
GD2DVP
AE1-157 TAP-6LDYSMITH CT 230.0 kV Ckt 1 line
DVP_P4-2: H2T574_SRT-S
BreakerAC117.26 %1809.0C2121.2745.58

Details for 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 553_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:122.22 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1202.88
MW Contribution:62.57
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
5.876
3151881LOWMORC
50/50
1.119
3151881LOWMORC
50/50
1.101
3151861LOWMORA
50/50
1.084
3152181CUNINGC
50/50
0.816
972193AH1-681 GEN
50/50
2.399
3152011BATH 1A
50/50
2.071
3152021BATH 2B
50/50
2.071
3152031BATH 3C
50/50
2.071
3152041BATH 4D
50/50
2.067
3138266HYDRAULIC
Solar/Wind Harmer
0.011
3138266HYDRAULIC
Solar/Wind Harmer
0.007
3148133STUARTS
Solar/Wind Harmer
0.083
3148013FISHERV
Solar/Wind Harmer
0.079
971447AH1-217 GEN
Solar/Wind Harmer
3.945
270494AE1-108_GEN
Solar/Wind Harmer
1.309
3148463FAIRFLD
Solar/Wind Harmer
0.099
971845AH1-439 GEN
Solar/Wind Harmer
4.376
970285AG2-188 GEN
Solar/Wind Harmer
7.313
316164AC1-076 GEN
Solar/Wind Helper
1.19
3151921BEARGRDN G2
50/50
1.205
3137383CUSHAW
50/50
0.022
3151861LOWMORA
50/50
1.128
3152191CUNINGD
50/50
1.776
3152171CUNINGB
50/50
0.767
972255AH1-712 GEN
50/50
53.693
315760AF1-028 GEN
50/50
15.215
3152051BATH 5E
50/50
2.069
3148013FISHERV
Solar/Wind Harmer
0.138
970221AG2-151 GEN
Solar/Wind Harmer
6.84
315616AA1-038_C
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.036
3146926FARMVIL
Solar/Wind Harmer
0.044
958131AF2-107 GEN
Solar/Wind Harmer
1.93
942461AE2-259 GEN
Solar/Wind Harmer
0
3132273ORANGE
Solar/Wind Helper
0.105
3147666LOUISA
Solar/Wind Helper
1.085
316170AC1-121 GEN2
Solar/Wind Helper
0.475
3151931BEARGRDN S1
50/50
1.555
3151911BEARGRDN G1
50/50
1.205
3152161CUNINGA
50/50
0.763
972277AH1-723 GEN
50/50
62.568
3152061BATH 6F
50/50
2.078
23503401SHY_Z2-039
50/50
0.003
971377AH1-170 GEN
Solar/Wind Harmer
1.368
3147623JAMES R
Solar/Wind Harmer
0.297
972003AH1-546 GEN
Solar/Wind Harmer
5.266
315705AF1-075 GEN
Solar/Wind Harmer
4.096
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.039
970937AG2-583 GEN
Solar/Wind Harmer
6.041
3147983MERCK5
Solar/Wind Harmer
0.038
3146926FARMVIL
Solar/Wind Harmer
0.044
316336AC2-165 C
Solar/Wind Harmer
0.002
316192AB2-158 GEN
Solar/Wind Helper
3.262
3147666LOUISA
Solar/Wind Helper
1.887
316254AC1-120 GEN1
Solar/Wind Helper
1.426
316006AB2-029 C
Solar/Wind Helper
0.088
23503501NHY_Z2-039
50/50
0.005
315821AE2-092 GEN
Solar/Wind Harmer
0.008
971489AH1-241 GEN
Solar/Wind Harmer
6.84
3146776BUCKING
Solar/Wind Harmer
0.395
3146776BUCKING
Solar/Wind Harmer
0.032
3132123MT JACKSON
Solar/Wind Harmer
0.208
970117AG2-086 GEN
Solar/Wind Harmer
1.594
970117AG2-086 GEN
Solar/Wind Harmer
1.063
966001AG1-469 GEN
Solar/Wind Helper
0.735
315651AD1-115 GEN
Solar/Wind Helper
0.962
NYPJM->LTFIMP_NY
CLTF
0.747
LGEELTFEXP_LGEE->PJM
CLTF
0.893
WECLTFEXP_WEC->PJM
CLTF
0.458
LAGNLTFEXP_LAGN->PJM
CLTF
2.697
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.536
TVALTFEXP_TVA->PJM
CLTF
1.4
CBM West 1LTFEXP_CBM-W1->PJM
CBM
16.766
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.191
MECLTFEXP_MEC->PJM
CLTF
2.078
SIGELTFEXP_SIGE->PJM
CLTF
0.068
CPLELTFEXP_CPLE->PJM
CLTF
0.939
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.474

Details for 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.1 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1083.62
MW Contribution:37.31
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
1.262
3137383CUSHAW
50/50
0.018
3151861LOWMORA
50/50
0.943
315760AF1-028 GEN
50/50
12.698
3152051BATH 5E
50/50
1.654
3144293JTRSVLE
50/50
0.21
3152191CUNINGD
50/50
1.059
3152171CUNINGB
50/50
0.457
972255AH1-712 GEN
50/50
32.018
970221AG2-151 GEN
Solar/Wind Harmer
7.052
3148013FISHERV
Solar/Wind Harmer
0.123
3146776BUCKING
Solar/Wind Harmer
0.039
3146926FARMVIL
Solar/Wind Harmer
0.052
315616AA1-038_C
Solar/Wind Harmer
0.001
942461AE2-259 GEN
Solar/Wind Harmer
0
316313AB2-026
Solar/Wind Harmer
0.042
316258AE1-075 C
Solar/Wind Harmer
0.05
316405AF2-144 C
Solar/Wind Harmer
0
3143336POWHATN
Solar/Wind Harmer
1.009
958131AF2-107 GEN
Solar/Wind Harmer
1.905
3147133PAMPLIN
Solar/Wind Harmer
0.206
971193AH1-056 GEN
Solar/Wind Harmer
3.999
970909AG2-566 GEN
Solar/Wind Harmer
0.694
963181AG1-167 GEN
Solar/Wind Harmer
0.249
3132273ORANGE
Solar/Wind Helper
0.106
3147666LOUISA
Solar/Wind Helper
1.086
316170AC1-121 GEN2
Solar/Wind Helper
0.478
972205AH1-687 GEN
50/50
6.155
3151881LOWMORC
50/50
0.936
3151881LOWMORC
50/50
0.921
3151861LOWMORA
50/50
0.906
3152011BATH 1A
50/50
1.656
3152021BATH 2B
50/50
1.656
3152031BATH 3C
50/50
1.655
3152041BATH 4D
50/50
1.652
3152181CUNINGC
50/50
0.486
972193AH1-681 GEN
50/50
1.431
3138266HYDRAULIC
Solar/Wind Harmer
0.011
3138266HYDRAULIC
Solar/Wind Harmer
0.007
971447AH1-217 GEN
Solar/Wind Harmer
4.022
3148133STUARTS
Solar/Wind Harmer
0.074
3148013FISHERV
Solar/Wind Harmer
0.071
270494AE1-108_GEN
Solar/Wind Harmer
1.339
971845AH1-439 GEN
Solar/Wind Harmer
4.834
970285AG2-188 GEN
Solar/Wind Harmer
8.151
3148463FAIRFLD
Solar/Wind Harmer
0.083
315657AE1-056 GEN
Solar/Wind Harmer
2.265
946301AF1-294 GEN
Solar/Wind Harmer
1.229
961791AG1-021 GEN
Solar/Wind Harmer
0.598
970683AG2-441 GEN
Solar/Wind Harmer
3.826
970681AG2-440 GEN
Solar/Wind Harmer
3.061
316164AC1-076 GEN
Solar/Wind Helper
1.194
3151931BEARGRDN S1
50/50
1.629
3151911BEARGRDN G1
50/50
1.262
3152061BATH 6F
50/50
1.661
3144293JTRSVLE
50/50
0.21
23503401SHY_Z2-039
50/50
0.002
3152161CUNINGA
50/50
0.455
972277AH1-723 GEN
50/50
37.31
971377AH1-170 GEN
Solar/Wind Harmer
1.41
3147623JAMES R
Solar/Wind Harmer
0.306
972003AH1-546 GEN
Solar/Wind Harmer
5.557
970937AG2-583 GEN
Solar/Wind Harmer
6.724
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.043
3146926FARMVIL
Solar/Wind Harmer
0.052
315705AF1-075 GEN
Solar/Wind Harmer
3.448
3147983MERCK5
Solar/Wind Harmer
0.033
316336AC2-165 C
Solar/Wind Harmer
0.003
3143336POWHATN
Solar/Wind Harmer
1.187
963171AG1-166 GEN
Solar/Wind Harmer
0.332
971563AH1-280 GEN
Solar/Wind Harmer
0.664
970685AG2-442 GEN
Solar/Wind Harmer
4.286
316192AB2-158 GEN
Solar/Wind Helper
3.267
3147666LOUISA
Solar/Wind Helper
1.889
316254AC1-120 GEN1
Solar/Wind Helper
1.434
316006AB2-029 C
Solar/Wind Helper
0.088
3144293JTRSVLE
50/50
0.21
3144293JTRSVLE
50/50
0.177
23503501NHY_Z2-039
50/50
0.004
971489AH1-241 GEN
Solar/Wind Harmer
7.052
315821AE2-092 GEN
Solar/Wind Harmer
0.008
3146776BUCKING
Solar/Wind Harmer
0.434
3146776BUCKING
Solar/Wind Harmer
0.035
3147133PAMPLIN
Solar/Wind Harmer
0.066
3147133PAMPLIN
Solar/Wind Harmer
0.052
970301AG2-198 GEN
Solar/Wind Harmer
2.774
958211AF2-115 GEN
Solar/Wind Harmer
0.747
963191AG1-168 GEN
Solar/Wind Harmer
0.249
971741AH1-377 GEN
Solar/Wind Harmer
5.799
966001AG1-469 GEN
Solar/Wind Helper
0.74
315651AD1-115 GEN
Solar/Wind Helper
0.968
NYPJM->LTFIMP_NY
CLTF
0.852
LGEELTFEXP_LGEE->PJM
CLTF
0.839
WECLTFEXP_WEC->PJM
CLTF
0.429
LAGNLTFEXP_LAGN->PJM
CLTF
2.954
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.46
TVALTFEXP_TVA->PJM
CLTF
1.519
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.521
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.505
MECLTFEXP_MEC->PJM
CLTF
2.015
SIGELTFEXP_SIGE->PJM
CLTF
0.065
CPLELTFEXP_CPLE->PJM
CLTF
1.993
CBM West 2LTFEXP_CBM-W2->PJM
CBM
18.046

Details for 6EDFERRY-DICKH230 230.0 kV Ckt 1 line l/o PEPCO_P1_5070_SRT-A


Base Case Flowgate

Area:DVP/PEPCO
Facility Description:
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
Contingency Name:
PEPCO_P1_5070_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:152.59 %
Rating:1331.98 MVA
Rating Type:B
MVA to Mitigate:2032.49
MW Contribution:42.85
Bus #Bus NameTypeMW Contribution
3152131X4-039 ST
50/50
2.892
3152121X4-039 GT2
50/50
1.833
3150011OMF A
50/50
0.216
3140676OCCOQUN
50/50
0.286
970467AG2-304 GEN
50/50
14.788
972223AH1-696 GEN
50/50
9.026
3150151POSSMC1
50/50
1.143
3141346CRANES
50/50
0.127
3150221REMNGT2
50/50
13.228
972201AH1-685 GEN
50/50
2.282
3150211REMNGT1
Adder
12.383
3150281M RUN A
Adder
13.357
316006AB2-029 C
Solar/Wind Harmer
0.001
971685AH1-345 GEN
Solar/Wind Harmer
0.73
316045AC1-158 PL2
Solar/Wind Harmer
1.475
972197AH1-683 GEN
Adder
1.98
972219AH1-694 GEN
Adder
1.425
316254AC1-120 GEN1
Solar/Wind Harmer
0.2
972135AH1-637 GEN
Solar/Wind Harmer
0.781
966881AG1-559 GEN
Solar/Wind Harmer
0.105
315683AE1-153 C
Solar/Wind Harmer
7.218
3147666LOUISA
Solar/Wind Harmer
0.355
316192AB2-158 GEN
Solar/Wind Harmer
0.501
316337AD2-073 GEN
Solar/Wind Harmer
0.077
3150351NORNECKC2
Adder
0.87
3141726DUNNSVL
Solar/Wind Harmer
0.348
962861AG1-135 GEN
Solar/Wind Harmer
2.764
3151751LOISA D
Adder
5.599
3138133OCRAN
Solar/Wind Harmer
0.051
3142416OLDCHRC
Solar/Wind Harmer
0.22
3142416OLDCHRC
Solar/Wind Harmer
0.084
3141766HARMONY
Solar/Wind Harmer
0.017
971777AH1-397 GEN
Solar/Wind Harmer
0.223
3141843SHACKLE
Adder
0.432
3142433PROV 92
Solar/Wind Harmer
0.337
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
3143096IRON208
Adder
0.351
3143526WINTERP
Solar/Wind Harmer
0.435
3142543TWELFTH
Solar/Wind Harmer
0.008
3150851SPRUNCC
Adder
0.385
944631AF1-128 GEN
Adder
39.853
3143226MDLTHAN
Solar/Wind Harmer
0.083
316159AE1-175 C
Solar/Wind Harmer
0.072
971317AH1-138 GEN
Solar/Wind Harmer
0.618
970129AG2-093 GEN
Solar/Wind Harmer
2.345
316458AB2-190 GEN2
Solar/Wind Harmer
0.442
315671AE2-027_GEN
Solar/Wind Harmer
5.273
3138126ROCKLANDING
Solar/Wind Harmer
0.038
971069AG2-661 GEN
Solar/Wind Harmer
1.462
971647AH1-324 GEN
Solar/Wind Harmer
3.497
961611AG1-000B GEN
Solar/Wind Harmer
4.29
3151171GRAVELC
Adder
0.868
3145336SMITFLD
Solar/Wind Harmer
0.325
316294AC1-161 GEN
Solar/Wind Harmer
1.405
970659AG2-427 GEN
Solar/Wind Harmer
3.913
316381AD1-082 GEN
Solar/Wind Harmer
0.084
316375AC2-012 GEN
Solar/Wind Harmer
0.002
970661AG2-428 GEN
Solar/Wind Harmer
8.025
3150981CHESPKA
Adder
1.007
944591AF1-124 GEN
Solar/Wind Harmer
18.213
316072AD1-144
Solar/Wind Harmer
0.029
316388AE2-253 GEN
Solar/Wind Harmer
0.251
3146456SLIGO L269
Solar/Wind Harmer
0.08
939411AE1-173 GEN
Solar/Wind Harmer
34.166
316246AF1-032 C
Solar/Wind Harmer
0.036
940641AE2-051 GEN
Solar/Wind Harmer
6.396
316093AE2-104_GEN
Solar/Wind Harmer
1.342
3143336POWHATN
Solar/Wind Harmer
1.412
3146516WINFALL
Solar/Wind Harmer
0.256
3146516WINFALL
Solar/Wind Harmer
0.079
316336AC2-165 C
Solar/Wind Harmer
0.003
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.078
3145663CRESWEL
Solar/Wind Harmer
0.215
971163AH1-040 GEN
Solar/Wind Harmer
6.133
970937AG2-583 GEN
Solar/Wind Harmer
4.64
3146206CASHIE
Solar/Wind Harmer
0.075
971547AH1-271 GEN
Solar/Wind Harmer
1.606
316023GEN1_S
Solar/Wind Harmer
0.169
3145893MURPHYS
Solar/Wind Harmer
0.301
3145893MURPHYS
Solar/Wind Harmer
0.334
970919AG2-571 GEN
Solar/Wind Harmer
2.672
970087AG2-069 GEN
Solar/Wind Harmer
5.999
3146173TUNIS
Solar/Wind Harmer
0.075
960081AF2-299 GEN
Solar/Wind Harmer
0.714
3145683EARLEYS
Solar/Wind Harmer
0.074
957481AF2-042 GEN
Solar/Wind Harmer
19.771
3146263WOODLND
Solar/Wind Harmer
0.074
315693AD1-088 GEN
Solar/Wind Harmer
3.545
962491AG1-098 GEN
Solar/Wind Harmer
4.214
971795AH1-408 GEN
Solar/Wind Harmer
4.913
3145963POPLR C
Solar/Wind Harmer
0.074
316011AB1-132 GEN
Solar/Wind Harmer
1.337
962571AG1-106 GEN
Solar/Wind Harmer
1.046
316190AA2-174 GEN
Solar/Wind Harmer
0
3145823KELFORD
Solar/Wind Harmer
0.073
3147043LAWRENC
Adder
0.664
972003AH1-546 GEN
Solar/Wind Harmer
3.117
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.029
3146926FARMVIL
Solar/Wind Harmer
0.044
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3145783HORNRTN
Solar/Wind Harmer
0.073
3145796HORNRTN
Solar/Wind Harmer
0.24
3145796HORNRTN
Solar/Wind Harmer
0.073
963171AG1-166 GEN
Solar/Wind Harmer
0.385
971563AH1-280 GEN
Solar/Wind Harmer
0.77
3144293JTRSVLE
Adder
0.23
316212AC1-099_GEN
Solar/Wind Harmer
0.372
970685AG2-442 GEN
Solar/Wind Harmer
5.37
972277AH1-723 GEN
Adder
42.854
3146293MARTNCO
Solar/Wind Harmer
0.067
316129AC1-054 GEN
Solar/Wind Harmer
0.27
971377AH1-170 GEN
Solar/Wind Harmer
0.763
3147623JAMES R
Solar/Wind Harmer
0.166
971065AG2-659 GEN
Solar/Wind Harmer
3.053
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315722AD1-056 GEN
Solar/Wind Harmer
0.448
315687AD1-152 GEN
Solar/Wind Harmer
0.002
316494AC1-189 GEN
Solar/Wind Harmer
0.238
3146233WITAKRS
Solar/Wind Harmer
0.278
961671AG1-007 GEN
Solar/Wind Harmer
0.011
3146083TARBORO
Solar/Wind Harmer
0.07
3145493TOT1
Solar/Wind Harmer
0.31
316359AB2-059 GEN
Solar/Wind Harmer
0.248
316049AB1-081 GEN
Solar/Wind Harmer
0.395
3145543BTLEBRO
Solar/Wind Harmer
0.069
3145543BTLEBRO
Solar/Wind Harmer
0.055
3142053HEARTS
Solar/Wind Harmer
0.122
970401AG2-262 GEN
Solar/Wind Harmer
0.404
316003AC1-222 GEN
Solar/Wind Harmer
0.002
315705AF1-075 GEN
Solar/Wind Harmer
2.472
3147983MERCK5
Solar/Wind Harmer
0.024
23779801AA1-109
Solar/Wind Helper
0.218
223401AF1-299 GEN
Solar/Wind Helper
0.397
966131AG1-482 GEN
Solar/Wind Helper
0.111
237080AD1-060 GEN
Solar/Wind Helper
0.221
235062AE1-101 C1
Solar/Wind Helper
1.064
237038AE2-054 C
Solar/Wind Helper
0.173
233930AB2-032 GEN
Solar/Wind Helper
0.23
233915AB1-141 GEN
Solar/Wind Helper
0.303
232422X3-066 FULL
Solar/Wind Helper
0.069
233964AF2-378 GEN
Solar/Wind Helper
0.025
232426Y1-080 FULL
Solar/Wind Helper
0.023
233998TM1NIN_3.36
Solar/Wind Helper
0.157
232428Y3-058 C
Solar/Wind Helper
0.203
233954AC2-188 GEN
Solar/Wind Helper
0.139
232404W1-003 C
Solar/Wind Helper
0.304
233950AC2-186 GEN
Solar/Wind Helper
0.07
232434Z2-077 GEN
Solar/Wind Helper
0.076
233972AC1-094 C
Solar/Wind Helper
0.181
205941AD2-115 GEN
Solar/Wind Helper
0.302
230434AG1-499 GEN
Solar/Wind Helper
0.136
230511AF1-262
Solar/Wind Helper
0.009
219258KINSLEYDEP C
Solar/Wind Helper
0.045
228728W1-130C
Solar/Wind Helper
0.032
219904AC1-010 C
Solar/Wind Helper
0.036
219907AC1-030 C
Solar/Wind Helper
0.02
218660EHAMPSOLAR C
Solar/Wind Helper
0.019
219686LUMSOLAR_N C
Solar/Wind Helper
0.023
219304NAMERICA C
Solar/Wind Helper
0.077
20720728JCB_W1-129
Solar/Wind Helper
0.033
207445AB1-138_GEN
Solar/Wind Helper
0.061
963711AG1-223 GEN
Solar/Wind Helper
0.037
20714828MDF_W3-079
Solar/Wind Helper
0.076
219680HOPEWELLV C1
Solar/Wind Helper
0.002
207454AA2-184 E
Solar/Wind Helper
0.18
20715228NPK_W1-113
Solar/Wind Helper
0.045
20742028HF_AC1-207
Solar/Wind Helper
0.082
207528AF2-192 GEN
Solar/Wind Helper
0.044
20673628F1S_V4-069
Solar/Wind Helper
0.017
20675428EAM_W2-061
Solar/Wind Helper
0.009
218428ETC SOLAR C
Solar/Wind Helper
0.003
20676428JCR_X2-075
Solar/Wind Helper
0.039
217213AMBOY SO C
Solar/Wind Helper
0.017
217209CENTRL HS C
Solar/Wind Helper
0.005
217208PARK ELE C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.013
207437AD2-070 GEN
Solar/Wind Helper
0.079
207439AE1-081 C O1
Solar/Wind Helper
0.011
207518AF1-320_GEN
Solar/Wind Helper
0.9
20671928W4-073
Solar/Wind Helper
0.051
20675828AU_W4-064
Solar/Wind Helper
0.017
961301AF2-421 GEN
Solar/Wind Helper
0.242
963151AG1-164 GEN
Solar/Wind Helper
0.242
212266LOR1
Solar/Wind Helper
0.026
961341AF2-425 GEN
Solar/Wind Helper
0.237
212507AE2-042_GEN
Solar/Wind Helper
0.829
946731AF1-337 GEN
Solar/Wind Helper
0.233
209071AE2-133 GEN
Solar/Wind Helper
0.042
970053AG2-049 GEN
50/50
2.022
3138216PACIFIC
Solar/Wind Harmer
0.025
316411AF1-147_GEN1
Solar/Wind Harmer
0.003
316415AF1-147_GEN2
Solar/Wind Harmer
0.003
3141426STAFORD
Solar/Wind Harmer
0.023
3150411LDYSMT5
Adder
12.718
3150381LDYSMT2
Adder
12.172
972213AH1-691 GEN
Adder
2.059
972215AH1-692 GEN
Adder
2.059
316164AC1-076 GEN
Solar/Wind Harmer
0.132
944491AF1-114 GEN
Solar/Wind Harmer
0
316223AC1-118
Solar/Wind Harmer
0.064
972189AH1-679 GEN
Adder
1.467
3141813NORNECK
Solar/Wind Harmer
0.087
970327AG2-215 GEN
Solar/Wind Harmer
2.824
962981AG1-147 GEN
Solar/Wind Harmer
3.203
3141783LANCAST
Solar/Wind Harmer
0.051
3141783LANCAST
Solar/Wind Harmer
0.034
3138133OCRAN
Solar/Wind Harmer
0.025
3141913WHIT STONE
Solar/Wind Harmer
0.085
3147346CASHSCORNER
Solar/Wind Harmer
0.196
316312AB1-027
Solar/Wind Harmer
0.152
316314AB2-024 C
Solar/Wind Harmer
0
316059AD1-063 C
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.017
315662AE1-191 GEN
Solar/Wind Harmer
0.003
315666AE1-190 GEN
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
2.507
3143873LANEXA
Solar/Wind Harmer
0.051
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
971167AH1-042 GEN
Solar/Wind Harmer
7.477
315976AC1-164 GENA
Solar/Wind Harmer
8.72
316169AC1-164_GENC
Solar/Wind Harmer
7.533
315975AC1-164 GENB
Solar/Wind Harmer
0.258
316233AE1-074 FULL
Solar/Wind Harmer
0.067
971281AH1-106 GEN
Solar/Wind Harmer
1.161
971283AH1-107 GEN
Solar/Wind Harmer
1.161
971285AH1-108 GEN
Adder
0.631
3138283WHITEMARSH
Solar/Wind Harmer
0.019
316132AB2-190 GEN1
Solar/Wind Harmer
0.442
316369SG1_INVT
Solar/Wind Harmer
0.003
972265AH1-717 GEN
Adder
6.337
3151201GRAVEL4
Adder
5.94
3151191GRAVEL3
Adder
5.865
3151211GRAVEL5
Adder
5.865
971445AH1-216 GEN
Solar/Wind Harmer
5.723
3143316POE
Solar/Wind Harmer
0.321
3151081ELIZAR1
Adder
7.394
3151091ELIZAR2
Adder
7.266
3152611GOSPORTB
Adder
1.027
3152621GOSPORTC
Adder
0.872
3152601GOSPORTA
Adder
0.804
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.055
316311AC2-079 GEN
Solar/Wind Harmer
2.303
957871AF2-081 GEN
Solar/Wind Harmer
3.99
316305AF2-043 C
Solar/Wind Harmer
0.001
319010AE1-072 C
Solar/Wind Harmer
0.403
3146406KITTY HAWK
Solar/Wind Harmer
0.01
315835AF2-110_GEN
Solar/Wind Harmer
0.548
313526AB2-022
Solar/Wind Harmer
0.043
3146486SUNBURY
Solar/Wind Harmer
0.079
3146486SUNBURY
Solar/Wind Harmer
0.079
316321Z2-027
Solar/Wind Harmer
0.015
3146396TANGLEW
Solar/Wind Harmer
0.219
3145176PASQUOTANK
Solar/Wind Harmer
0.049
316315AB2-025 C
Solar/Wind Harmer
0.064
315814AE2-033 C
Solar/Wind Harmer
6.204
941031AE2-094 GEN
Solar/Wind Harmer
14.412
944011AF1-069 GEN
Solar/Wind Harmer
4.709
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.078
3130156CHOWAN
Solar/Wind Harmer
0.078
970673AG2-436 GEN
Solar/Wind Harmer
16.54
970673AG2-436 GEN
Solar/Wind Harmer
11.027
971967AH1-528 GEN
Solar/Wind Harmer
12.344
315816AE2-034 GEN
Solar/Wind Harmer
0.329
3130546PLYMOUTH
Solar/Wind Harmer
0.076
315732AD1-074 GEN1
Solar/Wind Harmer
0.435
315733AD1-074 GEN2
Solar/Wind Harmer
0.435
315735AD1-075 GEN1
Solar/Wind Harmer
0.218
965291AG1-394 GEN
Solar/Wind Harmer
0.336
3146206CASHIE
Solar/Wind Harmer
0.075
970601AG2-382 GEN
Solar/Wind Harmer
2.811
3145893MURPHYS
Solar/Wind Harmer
0.203
3145893MURPHYS
Solar/Wind Harmer
0.075
970085AG2-068 GEN
Solar/Wind Harmer
4
970581AG2-369 GEN
Solar/Wind Harmer
3.44
3145513AHOSKIE
Solar/Wind Harmer
0.156
3145513AHOSKIE
Solar/Wind Harmer
0.074
3146043SEABORD
Solar/Wind Harmer
0.074
3145683EARLEYS
Solar/Wind Harmer
0.149
3145683EARLEYS
Solar/Wind Harmer
0.074
3145683EARLEYS
Solar/Wind Harmer
0.074
315607AA1-063A GEN
Solar/Wind Harmer
0.152
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.294
315652AC1-086 GEN
Solar/Wind Harmer
8.087
972205AH1-687 GEN
Adder
3.134
970285AG2-188 GEN
Solar/Wind Harmer
5.802
971845AH1-439 GEN
Solar/Wind Harmer
3.325
3145796HORNRTN
Solar/Wind Harmer
0.233
3145796HORNRTN
Solar/Wind Harmer
0.029
3146033SCOT NK
Solar/Wind Harmer
0.29
315657AE1-056 GEN
Solar/Wind Harmer
2.494
946301AF1-294 GEN
Solar/Wind Harmer
1.424
961791AG1-021 GEN
Solar/Wind Harmer
0.693
970683AG2-441 GEN
Solar/Wind Harmer
4.794
970681AG2-440 GEN
Solar/Wind Harmer
3.836
970831AG2-522 GEN
Solar/Wind Harmer
3.066
972193AH1-681 GEN
Adder
1.643
3144303KENBRDG
Solar/Wind Harmer
0.057
971443AH1-215 GEN
Solar/Wind Harmer
1.204
971447AH1-217 GEN
Solar/Wind Harmer
2.163
316005AA1-067
Solar/Wind Harmer
0.076
3145746EVERETS
Solar/Wind Harmer
0.282
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
970181AG2-120 GEN
Solar/Wind Harmer
0.883
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
3138266HYDRAULIC
Solar/Wind Harmer
0.003
3138266HYDRAULIC
Solar/Wind Harmer
0.002
957861AF2-080 GEN
Solar/Wind Harmer
3.032
316420AA1-050 GEN
Solar/Wind Harmer
0.002
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.07
3145573BETHELC
Solar/Wind Harmer
0.07
316118AC1-105 GEN
Solar/Wind Harmer
0.176
3147173SINAI
Solar/Wind Harmer
0.067
3147243WELCO
Solar/Wind Harmer
0.042
270494AE1-108_GEN
Solar/Wind Harmer
0.802
3148133STUARTS
Solar/Wind Harmer
0.039
3148013FISHERV
Solar/Wind Harmer
0.037
970865AG2-541 GEN
Solar/Wind Harmer
2.214
316123AC1-075 GEN
Solar/Wind Harmer
0.084
970165AG2-112 GEN
Solar/Wind Harmer
0.5
970163AG2-111 GEN
Solar/Wind Harmer
0.477
3148463FAIRFLD
Solar/Wind Harmer
0.06
3151881LOWMORC
Adder
0.64
3151881LOWMORC
Adder
0.63
3151861LOWMORA
Adder
0.62
960921AF2-383 GEN
Solar/Wind Helper
0.279
205943AE1-185 GEN
Solar/Wind Helper
0.387
205956AE1-196_GEN
Solar/Wind Helper
0.385
205932AD2-116_GEN
Solar/Wind Helper
0.385
959381AF2-229 GEN
Solar/Wind Helper
0.257
237085AD2-009_GEN
Solar/Wind Helper
0.97
203975AE1-071-GEN
Solar/Wind Helper
1.713
233935AB2-179 C
Solar/Wind Helper
0.772
232436AB1-176 C
Solar/Wind Helper
0.027
233923SMA
Solar/Wind Helper
0.575
233990AG1-397 GEN
Solar/Wind Helper
0.162
232432Z2-076 GEN
Solar/Wind Helper
0.04
234033AF1-007_GEN
Solar/Wind Helper
4.208
964001AG1-254 GEN
Solar/Wind Helper
0.565
219914AD2-027 C
Solar/Wind Helper
0.068
227927V4-067C
Solar/Wind Helper
0.006
228754AB1-001 C
Solar/Wind Helper
0.015
219272CLEANLIGHT C
Solar/Wind Helper
0.015
219688LUMSOLAR_S C
Solar/Wind Helper
0.023
219607WPEMNERT C
Solar/Wind Helper
0.047
214067T20SOLAR
Solar/Wind Helper
0.007
20715728PEM_W1-119
Solar/Wind Helper
0.056
20715828PEM_W1-120
Solar/Wind Helper
0.056
207459AE1-142 C O1
Solar/Wind Helper
0.169
219620RIDERU C
Solar/Wind Helper
0.001
20675528CPH_W2-050
Solar/Wind Helper
0.05
218526CNTRALGAS2 C
Solar/Wind Helper
0.093
218524CNTRALGAS1 C
Solar/Wind Helper
0.093
966261AG1-495 GEN
Solar/Wind Helper
0.047
20675928HOL_W4-097
Solar/Wind Helper
0.029
207530AG1-191 GEN
Solar/Wind Helper
0.038
207484AF2-139 C O1
Solar/Wind Helper
0.048
20676328BVR_Y1-020
Solar/Wind Helper
0.015
20674828DL_W4-046
Solar/Wind Helper
0.004
207408W3-077 C
Solar/Wind Helper
0.048
20675728RH_W2-091
Solar/Wind Helper
0.078
20675128HRM_W1-127
Solar/Wind Helper
0.017
209116AE2-175 GEN
Solar/Wind Helper
1.004
961261AF2-417 GEN
Solar/Wind Helper
0.241
959431AF2-234 GEN
Solar/Wind Helper
0.466
964051AG1-259 GEN
Solar/Wind Helper
0.035
964061AG1-260 GEN
Solar/Wind Helper
0.035
959421AF2-233 GEN
Solar/Wind Helper
0.233
238208AF1-136 C
Solar/Wind Helper
0.089
972289AH1-729 GEN
50/50
13.249
3150091POSSM6B
50/50
0.848
3150071POSSM 5
50/50
52.224
3150181POSSMC2
50/50
1.152
3150181POSSMC2
50/50
1.143
3150181POSSMC2
50/50
1.143
316447AC1-158 HLD
Solar/Wind Harmer
1.014
3150391LDYSMT3
Adder
12.655
972195AH1-682 GEN
Adder
1.663
315651AD1-115 GEN
Solar/Wind Harmer
0.003
315673AE1-157 GEN
Solar/Wind Harmer
6.396
957411AF2-035 GEN
Solar/Wind Harmer
3.895
970317AG2-208 GEN
Solar/Wind Harmer
3.609
316468AD1-105 GEN
Solar/Wind Harmer
-0.029
316077AC2-138 C
Solar/Wind Harmer
0
3150341NORNECKC1
Adder
0.913
3150341NORNECKC1
Adder
0.906
966001AG1-469 GEN
Solar/Wind Harmer
0.051
958261AF2-120 GEN
Solar/Wind Harmer
2.86
3151731LOISA B
Adder
5.599
3151721LOISA A
Adder
5.57
966871AG1-558 GEN
Solar/Wind Harmer
0.099
3142296MT RD221
Adder
0.271
3142366NRTHEST
Adder
0.276
3150691DARBY 3
Adder
6.069
3150701DARBY 4
Adder
6.055
3150681DARBY 2
Adder
6.048
3150671DARBY 1
Adder
6.041
316075AC2-137 C
Solar/Wind Harmer
0.023
3142946ENON
Solar/Wind Harmer
0.008
3143526WINTERP
Solar/Wind Harmer
0.435
971223AH1-071 GEN
Solar/Wind Harmer
0.89
944641AF1-129 GEN
Adder
39.415
316240AF1-291 C
Solar/Wind Harmer
0.001
316033AB2-134 GEN
Solar/Wind Harmer
0.005
315697AD1-025 GEN
Solar/Wind Harmer
0.092
316236AE1-162_GEN
Solar/Wind Harmer
0.001
970657AG2-426 GEN
Solar/Wind Harmer
2.829
970657AG2-426 GEN
Solar/Wind Harmer
0.593
316036AC1-147 C
Solar/Wind Harmer
0.015
3150991CHESPKB
Adder
0.845
3150991CHESPKB
Adder
0.825
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.077
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3145506HICKORY
Solar/Wind Harmer
0.321
3145506HICKORY
Solar/Wind Harmer
0.193
3145506HICKORY
Solar/Wind Harmer
0.048
316339AD2-160 GEN
Solar/Wind Harmer
0.13
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.045
3137176SLIGO L2192
Solar/Wind Harmer
0.319
3146456SLIGO L269
Solar/Wind Harmer
1.416
3130086AYDLETT
Solar/Wind Harmer
0.32
3146386ELIZ CT
Solar/Wind Harmer
0.08
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.079
3146516WINFALL
Solar/Wind Harmer
0.079
3146516WINFALL
Solar/Wind Harmer
0.079
3146626S HERTFORD
Solar/Wind Harmer
0.079
3146626S HERTFORD
Solar/Wind Harmer
0.079
3144356SAPONY
Solar/Wind Harmer
0.657
315742AE1-103 GEN
Solar/Wind Harmer
0.001
3146376EDENTON
Solar/Wind Harmer
0.345
3146376EDENTON
Solar/Wind Harmer
0.345
972185AH1-677 GEN
Adder
4.331
972187AH1-678 GEN
Adder
2.184
970933AG2-581 GEN
Solar/Wind Harmer
6.107
316065AD1-022 GEN
Solar/Wind Harmer
3.475
3145893MURPHYS
Solar/Wind Harmer
0.503
3145893MURPHYS
Solar/Wind Harmer
0.135
3146173TUNIS
Solar/Wind Harmer
0.075
3146173TUNIS
Solar/Wind Harmer
0.075
970099AG2-077 GEN
Solar/Wind Harmer
7.908
316181AB2-040 GEN
Solar/Wind Harmer
0.107
3142666NORTHAMPTON
Solar/Wind Harmer
0.074
3142666NORTHAMPTON
Solar/Wind Harmer
0.074
3142666NORTHAMPTON
Solar/Wind Harmer
0.074
3142666NORTHAMPTON
Solar/Wind Harmer
0.044
971741AH1-377 GEN
Solar/Wind Harmer
7.304
970301AG2-198 GEN
Solar/Wind Harmer
3.138
316426AA2-053 GEN
Solar/Wind Harmer
0.248
3146776BUCKING
Solar/Wind Harmer
0.293
3145593CAROLNA
Solar/Wind Harmer
0.073
3145593CAROLNA
Solar/Wind Harmer
0.073
3146776BUCKING
Solar/Wind Harmer
0.024
966811AG1-552 GEN
Solar/Wind Harmer
0.795
3145593CAROLNA
Solar/Wind Harmer
0.091
3145783HORNRTN
Solar/Wind Harmer
1.299
3145783HORNRTN
Solar/Wind Harmer
1.039
3145783HORNRTN
Solar/Wind Harmer
0.325
3145783HORNRTN
Solar/Wind Harmer
0.13
3145796HORNRTN
Solar/Wind Harmer
0.219
3147133PAMPLIN
Solar/Wind Harmer
0.072
3147133PAMPLIN
Solar/Wind Harmer
0.058
958211AF2-115 GEN
Solar/Wind Harmer
0.866
963191AG1-168 GEN
Solar/Wind Harmer
0.289
3144293JTRSVLE
Adder
0.23
3144293JTRSVLE
Adder
0.193
3145933PARMELE
Solar/Wind Harmer
0.144
3145933PARMELE
Solar/Wind Harmer
0.072
316274AC1-208 GEN
Solar/Wind Harmer
0.372
316034AC1-036 C
Solar/Wind Harmer
0.005
970323AG2-213 GEN
Solar/Wind Harmer
3.057
971775AH1-396 GEN
Solar/Wind Harmer
0.115
971489AH1-241 GEN
Solar/Wind Harmer
3.817
313527AB2-043 GEN
Solar/Wind Harmer
0.001
939181AE1-148 GEN
Solar/Wind Harmer
3.402
3145493TOT1
Solar/Wind Harmer
0.162
3145453TOT5
Solar/Wind Harmer
0.097
3145603CNETO
Solar/Wind Harmer
0.065
315821AE2-092 GEN
Solar/Wind Harmer
0.004
962561AG1-105 GEN
Solar/Wind Harmer
3.322
961601AG1-000A GEN
Solar/Wind Harmer
1.228
316263AC1-034 GEN
Solar/Wind Harmer
2.624
964791AG1-342 GEN
Solar/Wind Harmer
1.322
3146843MT LREL
Solar/Wind Harmer
0.069
3146843MT LREL
Solar/Wind Harmer
0.069
316222AC1-221 GEN
Solar/Wind Harmer
0.264
971761AH1-387 GEN
Solar/Wind Harmer
1.238
942751AE2-291 GEN
Solar/Wind Harmer
3.276
3132123MT JACKSON
Solar/Wind Harmer
0.183
970117AG2-086 GEN
Solar/Wind Harmer
1.401
970117AG2-086 GEN
Solar/Wind Harmer
0.934
226929AD2-058 GEN
Solar/Wind Helper
0.143
237025AB1-124 C
Solar/Wind Helper
0.193
237006AB1-125 GEN
Solar/Wind Helper
0.145
23777801MSM_W1-116
Solar/Wind Helper
0.13
237034AC2-136 C
Solar/Wind Helper
0.205
205916AD1-020 GEN
Solar/Wind Helper
1.48
208835TUHI V3-051
Solar/Wind Helper
0.019
208835TUHI V3-051
Solar/Wind Helper
0.019
237001AB1-127_GEN
Solar/Wind Helper
0.307
237002AB1-128_GEN
Solar/Wind Helper
0.298
235063AE1-101 C2
Solar/Wind Helper
1.064
20390526W1-045 C
Solar/Wind Helper
0.252
23777901MDS_W4-102
Solar/Wind Helper
0.105
235020AA1-095 C
Solar/Wind Helper
0.029
233933AB2-153 GEN
Solar/Wind Helper
0.14
233944AB2-135 GEN
Solar/Wind Helper
0.355
232424Y1-079 C
Solar/Wind Helper
0.07
233987AB2-037 GEN
Solar/Wind Helper
1.406
233946AB2-136 GEN
Solar/Wind Helper
0.341
234036AF2-325 C
Solar/Wind Helper
0.025
233901CHERRYDALE C
Solar/Wind Helper
0.139
232408W1-005 C
Solar/Wind Helper
0.304
232410W1-006 C
Solar/Wind Helper
0.304
233939AC1-091 C
Solar/Wind Helper
0.209
233970AC1-092 C
Solar/Wind Helper
0.209
230433AD2-135 GEN
Solar/Wind Helper
0.01
219921AF1-264
Solar/Wind Helper
0.03
230407AD2-065 C
Solar/Wind Helper
0.024
219615MILLCREEK C
Solar/Wind Helper
0.016
963401AG1-189 GEN
Solar/Wind Helper
0.033
963391AG1-188 GEN
Solar/Wind Helper
0.048
20714928UPF_X1-085
Solar/Wind Helper
0.003
20720628TIN_W1-124
Solar/Wind Helper
0.11
20716928W4-060COL
Solar/Wind Helper
0.03
20673828FLE_V3-070
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.009
207442AE1-156 GEN
Solar/Wind Helper
0.188
20676128MHD_W3-029
Solar/Wind Helper
0.055
20671828STAW2-080
Solar/Wind Helper
0.015
217081WEATEXAS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.004
217204WCALDSOLAR C
Solar/Wind Helper
0.002
207471AF2-354 C
Solar/Wind Helper
0.097
20674928WA_W3-044
Solar/Wind Helper
0.056
964851AG1-348 GEN
Solar/Wind Helper
0.046
20674128FR_U2-059
Solar/Wind Helper
0.002
20676228FRD_X1-012
Solar/Wind Helper
0.052
966111AG1-480 GEN
Solar/Wind Helper
0.042
211065PSPA IPP
Solar/Wind Helper
0.085
211065PSPA IPP
Solar/Wind Helper
0.085
208972BECR K09
Solar/Wind Helper
0.178
961431AF2-434 GEN
Solar/Wind Helper
0.236
209029WAYMART-WD
Solar/Wind Helper
0.443
209054AE2-059 GEN
Solar/Wind Helper
0.042
946751AF1-339 GEN
Solar/Wind Helper
0.233
209137AF2-361 C
Solar/Wind Helper
0.708
3152111X4-039 GT1
50/50
1.838
315747AE2-019 GEN
50/50
13.176
3150021OMF B
50/50
0.216
3150101POSSM6S
50/50
1.296
3150081POSSM6A
50/50
0.848
3150151POSSMC1
50/50
1.143
3150151POSSMC1
50/50
1.143
3150231REMNGT3
50/50
14.281
3150241REMNGT4
50/50
13.316
972217AH1-693 GEN
50/50
1.756
963691AG1-221 GEN
Solar/Wind Harmer
2.312
971455AH1-223 GEN
Solar/Wind Harmer
2.312
3141196NOKESVL
Solar/Wind Harmer
0.429
972199AH1-684 GEN
Adder
1.903
3150301M RUN C
Adder
13.349
3150291M RUN B
Adder
13.25
3150331BIRCHWDA
Adder
16.626
3141316ARNOLDS
Adder
0.229
316044AC1-158 PL1
Solar/Wind Harmer
0.461
316450AC1-158 RIC
Solar/Wind Harmer
0.123
3150401LDYSMT4
Adder
12.678
3150371LDYSMT1
Adder
12.251
316170AC1-121 GEN2
Solar/Wind Harmer
0.1
970737AG2-469 GEN
Solar/Wind Harmer
3.872
3141906WESTMOR
Solar/Wind Harmer
0.036
3132273ORANGE
Solar/Wind Harmer
0.018
971781AH1-399 GEN
Solar/Wind Harmer
0.118
3147666LOUISA
Solar/Wind Harmer
0.204
3150351NORNECKC2
Adder
0.884
316404AE1-155 C
Solar/Wind Harmer
0.019
3151761LOISA E
Adder
11.415
972183AH1-676 GEN
Adder
92.045
970009AG2-005 GEN
Solar/Wind Harmer
0.643
316473AC1-191 GEN
Solar/Wind Harmer
0.29
962971AG1-146 GEN
Solar/Wind Harmer
1.373
3142416OLDCHRC
Solar/Wind Harmer
0.821
3141766HARMONY
Solar/Wind Harmer
1.129
316156AD2-030 GEN
Solar/Wind Harmer
0.063
3141873WAN 176
Solar/Wind Harmer
1.505
316280AD1-041 GEN
Solar/Wind Harmer
0.002
316203AE2-005 GEN
Solar/Wind Harmer
0
3141843SHACKLE
Adder
0.432
970293AG2-193 GEN
Solar/Wind Harmer
0.899
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
3143096IRON208
Adder
0.351
3143096IRON208
Adder
0.344
3142946ENON
Solar/Wind Harmer
0.028
3150861SPRUNCD
Adder
0.385
316382AG1-145 C
Solar/Wind Harmer
0.001
970133AG2-095 GEN
Solar/Wind Harmer
0.794
970129AG2-093 GEN
Solar/Wind Harmer
4.984
3150921YORKTN3
Adder
2.069
315778AD1-151 GEN
Solar/Wind Harmer
6.579
965281AG1-393 GEN
Solar/Wind Harmer
0.877
3144216WINCHST
Adder
0.31
315839AE2-212 C
Solar/Wind Harmer
0.001
961611AG1-000B GEN
Solar/Wind Harmer
2.181
3151221GRAVEL6
Adder
5.934
3151171GRAVELC
Adder
1.142
3145336SMITFLD
Solar/Wind Harmer
0.033
315813AE1-149 C
Solar/Wind Harmer
4.334
315773AC2-141 GEN
Solar/Wind Harmer
2.962
970659AG2-427 GEN
Solar/Wind Harmer
0.856
316083AB2-161 GEN
Solar/Wind Harmer
0.001
3144536CHRHLND
Solar/Wind Harmer
0.012
3151101ELIZAR3
Adder
7.489
970661AG2-428 GEN
Solar/Wind Harmer
1.707
3144873MCLAUGH
Solar/Wind Harmer
0.002
944581AF1-123 GEN
Solar/Wind Harmer
18.149
944601AF1-125 GEN
Solar/Wind Harmer
17.869
3146456SLIGO L269
Solar/Wind Harmer
0.08
971153AH1-033 GEN
Solar/Wind Harmer
0.925
316320Y1-086
Solar/Wind Harmer
0
316313AB2-026
Solar/Wind Harmer
0.05
316258AE1-075 C
Solar/Wind Harmer
0.06
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
1.2
316435W1029_GEN3
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.079
3146626S HERTFORD
Solar/Wind Harmer
0.079
3145273HOLLAND
Solar/Wind Harmer
0.059
3146376EDENTON
Solar/Wind Harmer
0.078
315614AA2-178 GEN
Solar/Wind Harmer
0.439
971157AH1-035 GEN
Solar/Wind Harmer
0.911
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
315737AD1-076 GEN
Solar/Wind Harmer
0.975
3146206CASHIE
Solar/Wind Harmer
0.075
316365GEN2_N
Solar/Wind Harmer
0.169
3145893MURPHYS
Solar/Wind Harmer
0.126
3145893MURPHYS
Solar/Wind Harmer
0.075
970917AG2-570 GEN
Solar/Wind Harmer
6.681
957521AF2-046 GEN
Solar/Wind Harmer
5.587
961681AG1-008 GEN
Solar/Wind Harmer
5.587
3146173TUNIS
Solar/Wind Harmer
0.075
3156021HOLLOMANSOL
Solar/Wind Harmer
0.339
316463AE2-346 GEN
Solar/Wind Harmer
0.064
316140AB2-099
Solar/Wind Harmer
0.027
962331AG1-082 GEN
Solar/Wind Harmer
0.795
3146263WOODLND
Solar/Wind Harmer
0.074
313506AB2-031 GEN
Solar/Wind Harmer
0.228
3142666NORTHAMPTON
Solar/Wind Harmer
0.074
3145963POPLR C
Solar/Wind Harmer
0.074
970909AG2-566 GEN
Solar/Wind Harmer
0.785
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.073
3147043LAWRENC
Solar/Wind Harmer
0.044
3146776BUCKING
Solar/Wind Harmer
0.026
3146926FARMVIL
Solar/Wind Harmer
0.044
3145796HORNRTN
Solar/Wind Harmer
0.291
3145796HORNRTN
Solar/Wind Harmer
0.073
942461AE2-259 GEN
Solar/Wind Harmer
0
316478AD1-087 GEN
Solar/Wind Harmer
0.254
316486AD2-202 GEN
Solar/Wind Harmer
0.075
3147133PAMPLIN
Solar/Wind Harmer
0.227
971193AH1-056 GEN
Solar/Wind Harmer
4.404
963181AG1-167 GEN
Solar/Wind Harmer
0.289
3144293JTRSVLE
Adder
0.23
316210AC1-098 GEN
Solar/Wind Harmer
0.668
972255AH1-712 GEN
Adder
36.775
3145933PARMELE
Solar/Wind Harmer
0.072
966801AG1-551 GEN
Solar/Wind Harmer
0.836
959311AF2-222 GEN
Solar/Wind Harmer
6.376
970257AG2-171 GEN
Solar/Wind Harmer
2.293
970221AG2-151 GEN
Solar/Wind Harmer
3.817
315785AD2-033 C
Solar/Wind Harmer
0.582
964241AG1-285 GEN
Solar/Wind Harmer
4.753
316131AB2-060 GEN
Solar/Wind Harmer
0.224
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
315724AD1-057 GEN
Solar/Wind Harmer
0.266
316327AA2-057 GEN
Solar/Wind Harmer
0.106
3146233WITAKRS
Solar/Wind Harmer
0.35
3146233WITAKRS
Solar/Wind Harmer
0.047
3146073TAR RVR
Solar/Wind Harmer
0.07
3146083TARBORO
Solar/Wind Harmer
0.07
3138543CONSLDL
Solar/Wind Harmer
0.046
3145543BTLEBRO
Solar/Wind Harmer
0.069
3145543BTLEBRO
Solar/Wind Harmer
0.069
961601AG1-000A GEN
Solar/Wind Harmer
4.912
971623AH1-311 GEN
Solar/Wind Harmer
0.138
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
2.87
971683AH1-343 GEN
Solar/Wind Harmer
2.391
3148013FISHERV
Solar/Wind Harmer
0.065
316283AC2-100 C
Solar/Wind Harmer
0.124
315616AA1-038_C
Solar/Wind Harmer
0
3151861LOWMORA
Adder
0.645
958131AF2-107 GEN
Solar/Wind Harmer
1.618
226910AB2-157 C
Solar/Wind Helper
0.02
227287AC2-120 GEN
Solar/Wind Helper
0.49
237030AB1-096 C
Solar/Wind Helper
0.083
223402AF1-300 C
Solar/Wind Helper
0.397
205917AD1-020 ES
Solar/Wind Helper
0.318
238221AF1-254 C O1
Solar/Wind Helper
0.179
235067AD1-061 GEN
Solar/Wind Helper
0.312
233982AB2-133 GEN
Solar/Wind Helper
0.216
233918AB1-142 GEN
Solar/Wind Helper
0.303
233994AC2-023 GEN
Solar/Wind Helper
0.577
233996TM1833_GEN
Solar/Wind Helper
0.157
233997TMININ_4.2
Solar/Wind Helper
0.157
233940AF2-379 C
Solar/Wind Helper
0.037
234015AF2-250 C
Solar/Wind Helper
0.023
233952AC2-187 GEN
Solar/Wind Helper
0.139
232406W1-004 FULL
Solar/Wind Helper
0.304
233971AC1-093 C
Solar/Wind Helper
0.214
230430AE1-229_GEN
Solar/Wind Helper
1.995
230415AB2-049 C
Solar/Wind Helper
0.018
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219766PARADISE C
Solar/Wind Helper
0.032
219912AD2-042 GEN
Solar/Wind Helper
0.089
228729W2-030 C
Solar/Wind Helper
0.065
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.007
219906AC1-017 C
Solar/Wind Helper
0.025
219348LDSOLAR C
Solar/Wind Helper
0.067
959561AF2-247 GEN
Solar/Wind Helper
0.012
20716028EGP_W2-019
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.037
20715028HAN_X4-015
Solar/Wind Helper
0.033
219276PARKLANDSO C
Solar/Wind Helper
0.052
20714528FRN_Y2-051
Solar/Wind Helper
0.033
20720528MAN_W1-024
Solar/Wind Helper
0.016
219612MATRIX C
Solar/Wind Helper
0.014
218438BLK ROCK C
Solar/Wind Helper
0.016
20673728F2S_V4-070
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.043
219919AE1-041 FULL
Solar/Wind Helper
0.002
219249CENTRALDIV C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
217169METRODIV C
Solar/Wind Helper
0.002
20676728BRNX1-095
Solar/Wind Helper
0.017
207510AF2-138 C
Solar/Wind Helper
0.046
20674628WNG_W3-110
Solar/Wind Helper
0.051
963161AG1-165 GEN
Solar/Wind Helper
0.242
963071AG1-156 GEN
Solar/Wind Helper
0.783
209027LOR2_Q27
Solar/Wind Helper
0.557
961331AF2-424 GEN
Solar/Wind Helper
0.237
961421AF2-433 GEN
Solar/Wind Helper
0.236
957921AF2-086 GEN
Solar/Wind Helper
0.234
946691AF1-333 GEN
Solar/Wind Helper
0.233
946741AF1-338 GEN
Solar/Wind Helper
0.233
209067AE2-060 GEN
Solar/Wind Helper
0.042
NYPJM->LTFIMP_NY
CLTF
2.575
LGEELTFEXP_LGEE->PJM
CLTF
1.805
WECLTFEXP_WEC->PJM
CLTF
0.962
LAGNLTFEXP_LAGN->PJM
CLTF
6.324
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.565
TVALTFEXP_TVA->PJM
CLTF
3.188
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.485
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.592
MECLTFEXP_MEC->PJM
CLTF
4.449
SIGELTFEXP_SIGE->PJM
CLTF
0.14
CPLELTFEXP_CPLE->PJM
CLTF
5.065
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.965

Details for 6EDFERRY-DICKH230 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T560_SRT-A


Base Case Flowgate

Area:DVP/PEPCO
Facility Description:
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T560_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:146.61 %
Rating:1417.0 MVA
Rating Type:B
MVA to Mitigate:2077.46
MW Contribution:42.84
Bus #Bus NameTypeMW Contribution
970053AG2-049 GEN
50/50
2.027
3138216PACIFIC
Solar/Wind Harmer
-0.003
316411AF1-147_GEN1
Solar/Wind Harmer
1.101
316415AF1-147_GEN2
Solar/Wind Harmer
1.101
3141426STAFORD
Solar/Wind Harmer
-0.003
3150411LDYSMT5
Adder
12.732
3150381LDYSMT2
Adder
12.185
972213AH1-691 GEN
Adder
2.061
972215AH1-692 GEN
Adder
2.061
316164AC1-076 GEN
Solar/Wind Harmer
0.887
944491AF1-114 GEN
Solar/Wind Harmer
3.051
3152111X4-039 GT1
50/50
1.839
315747AE2-019 GEN
50/50
13.179
963691AG1-221 GEN
Solar/Wind Harmer
2.313
971455AH1-223 GEN
Solar/Wind Harmer
2.313
3150151POSSMC1
Adder
1.085
3150151POSSMC1
Adder
1.085
3141196NOKESVL
Solar/Wind Harmer
-0.048
3150231REMNGT3
Adder
13.456
3150241REMNGT4
Adder
12.546
972199AH1-684 GEN
Adder
1.902
972217AH1-693 GEN
Adder
1.654
3150301M RUN C
Adder
13.346
3150291M RUN B
Adder
13.247
3150331BIRCHWDA
Adder
16.693
3141316ARNOLDS
Adder
0.23
316044AC1-158 PL1
Solar/Wind Harmer
1.043
316450AC1-158 RIC
Solar/Wind Harmer
0.278
3150401LDYSMT4
Adder
12.692
3150371LDYSMT1
Adder
12.264
316170AC1-121 GEN2
Solar/Wind Harmer
0.283
966881AG1-559 GEN
Solar/Wind Harmer
0.309
970737AG2-469 GEN
Solar/Wind Harmer
5.11
3141906WESTMOR
Solar/Wind Harmer
-0.004
3132273ORANGE
Solar/Wind Harmer
-0.002
971781AH1-399 GEN
Solar/Wind Harmer
0.62
3147666LOUISA
Solar/Wind Harmer
-0.023
3150351NORNECKC2
Adder
0.885
316404AE1-155 C
Solar/Wind Harmer
1.876
3151761LOISA E
Adder
11.412
316484AD2-074 GEN
Solar/Wind Harmer
2.436
970009AG2-005 GEN
Solar/Wind Harmer
1.21
972183AH1-676 GEN
Adder
92.015
316473AC1-191 GEN
Solar/Wind Harmer
1.04
962971AG1-146 GEN
Solar/Wind Harmer
1.809
3142416OLDCHRC
Solar/Wind Harmer
0.961
3141766HARMONY
Solar/Wind Harmer
0.847
316156AD2-030 GEN
Solar/Wind Harmer
0.254
3141873WAN 176
Solar/Wind Harmer
1.129
316280AD1-041 GEN
Solar/Wind Harmer
0.717
316203AE2-005 GEN
Solar/Wind Harmer
4.009
3141843SHACKLE
Adder
0.432
970293AG2-193 GEN
Solar/Wind Harmer
1.184
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
3143096IRON208
Adder
0.351
3143096IRON208
Adder
0.344
3142946ENON
Solar/Wind Harmer
-0.003
3150861SPRUNCD
Adder
0.385
316382AG1-145 C
Solar/Wind Harmer
0.281
970133AG2-095 GEN
Solar/Wind Harmer
1.046
970129AG2-093 GEN
Solar/Wind Harmer
5.216
3150921YORKTN3
Adder
2.069
315778AD1-151 GEN
Solar/Wind Harmer
8.005
965281AG1-393 GEN
Solar/Wind Harmer
1.155
3144216WINCHST
Adder
0.31
315839AE2-212 C
Solar/Wind Harmer
0.278
961611AG1-000B GEN
Solar/Wind Harmer
1.935
3151221GRAVEL6
Adder
5.934
3151171GRAVELC
Adder
1.142
3145336SMITFLD
Solar/Wind Harmer
-0.004
315813AE1-149 C
Solar/Wind Harmer
5.707
315773AC2-141 GEN
Solar/Wind Harmer
3.812
970659AG2-427 GEN
Solar/Wind Harmer
0.856
316083AB2-161 GEN
Solar/Wind Harmer
1.475
3144536CHRHLND
Solar/Wind Harmer
-0.001
3151101ELIZAR3
Adder
7.489
970661AG2-428 GEN
Solar/Wind Harmer
1.707
3144873MCLAUGH
Solar/Wind Harmer
0
944581AF1-123 GEN
Solar/Wind Harmer
41.196
944601AF1-125 GEN
Solar/Wind Harmer
40.553
3146456SLIGO L269
Solar/Wind Harmer
-0.009
971153AH1-033 GEN
Solar/Wind Harmer
1.096
316320Y1-086
Solar/Wind Harmer
0.524
316313AB2-026
Solar/Wind Harmer
0.241
316258AE1-075 C
Solar/Wind Harmer
0.217
316405AF2-144 C
Solar/Wind Harmer
0.229
3143336POWHATN
Solar/Wind Harmer
0.9
316435W1029_GEN3
Solar/Wind Harmer
1.61
3146516WINFALL
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3145273HOLLAND
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.009
315614AA2-178 GEN
Solar/Wind Harmer
0.929
971157AH1-035 GEN
Solar/Wind Harmer
1.066
3156081AA2-088 GEN
Solar/Wind Harmer
2.765
315737AD1-076 GEN
Solar/Wind Harmer
1.618
316365GEN2_N
Solar/Wind Harmer
0.57
3146206CASHIE
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.059
3145893MURPHYS
Solar/Wind Harmer
-0.008
970917AG2-570 GEN
Solar/Wind Harmer
21.109
957521AF2-046 GEN
Solar/Wind Harmer
6.644
961681AG1-008 GEN
Solar/Wind Harmer
6.644
3146173TUNIS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1.13
316463AE2-346 GEN
Solar/Wind Harmer
0.136
316140AB2-099
Solar/Wind Harmer
0.056
962331AG1-082 GEN
Solar/Wind Harmer
1.047
966621AG1-532 GEN
Solar/Wind Harmer
0.17
3146263WOODLND
Solar/Wind Harmer
-0.008
313506AB2-031 GEN
Solar/Wind Harmer
0.667
3144293JTRSVLE
Adder
0.23
972255AH1-712 GEN
Adder
36.766
3151861LOWMORA
Adder
0.645
226910AB2-157 C
Solar/Wind Helper
0.02
227287AC2-120 GEN
Solar/Wind Helper
0.49
237030AB1-096 C
Solar/Wind Helper
0.083
223402AF1-300 C
Solar/Wind Helper
0.397
205917AD1-020 ES
Solar/Wind Helper
0.318
238221AF1-254 C O1
Solar/Wind Helper
0.179
235067AD1-061 GEN
Solar/Wind Helper
0.312
233982AB2-133 GEN
Solar/Wind Helper
0.216
233918AB1-142 GEN
Solar/Wind Helper
0.303
233994AC2-023 GEN
Solar/Wind Helper
0.577
233940AF2-379 C
Solar/Wind Helper
0.037
233996TM1833_GEN
Solar/Wind Helper
0.157
233997TMININ_4.2
Solar/Wind Helper
0.157
233952AC2-187 GEN
Solar/Wind Helper
0.139
232406W1-004 FULL
Solar/Wind Helper
0.304
234015AF2-250 C
Solar/Wind Helper
0.023
233971AC1-093 C
Solar/Wind Helper
0.214
230430AE1-229_GEN
Solar/Wind Helper
1.995
230415AB2-049 C
Solar/Wind Helper
0.018
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219766PARADISE C
Solar/Wind Helper
0.032
219912AD2-042 GEN
Solar/Wind Helper
0.089
228729W2-030 C
Solar/Wind Helper
0.065
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.007
219906AC1-017 C
Solar/Wind Helper
0.025
219348LDSOLAR C
Solar/Wind Helper
0.067
959561AF2-247 GEN
Solar/Wind Helper
0.012
20716028EGP_W2-019
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.037
20715028HAN_X4-015
Solar/Wind Helper
0.033
219276PARKLANDSO C
Solar/Wind Helper
0.052
20714528FRN_Y2-051
Solar/Wind Helper
0.033
20720528MAN_W1-024
Solar/Wind Helper
0.016
219612MATRIX C
Solar/Wind Helper
0.014
218438BLK ROCK C
Solar/Wind Helper
0.016
20673728F2S_V4-070
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.043
219919AE1-041 FULL
Solar/Wind Helper
0.002
219249CENTRALDIV C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
217169METRODIV C
Solar/Wind Helper
0.002
20676728BRNX1-095
Solar/Wind Helper
0.017
207510AF2-138 C
Solar/Wind Helper
0.046
20674628WNG_W3-110
Solar/Wind Helper
0.051
963161AG1-165 GEN
Solar/Wind Helper
0.242
963071AG1-156 GEN
Solar/Wind Helper
0.783
209027LOR2_Q27
Solar/Wind Helper
0.557
961331AF2-424 GEN
Solar/Wind Helper
0.237
961421AF2-433 GEN
Solar/Wind Helper
0.236
957921AF2-086 GEN
Solar/Wind Helper
0.234
946691AF1-333 GEN
Solar/Wind Helper
0.233
946741AF1-338 GEN
Solar/Wind Helper
0.233
209067AE2-060 GEN
Solar/Wind Helper
0.042
316223AC1-118
Solar/Wind Harmer
0.272
972189AH1-679 GEN
Adder
1.468
3141813NORNECK
Solar/Wind Harmer
-0.01
962981AG1-147 GEN
Solar/Wind Harmer
4.221
3141783LANCAST
Solar/Wind Harmer
-0.006
3141783LANCAST
Solar/Wind Harmer
-0.004
3138133OCRAN
Solar/Wind Harmer
-0.003
3141913WHIT STONE
Solar/Wind Harmer
-0.01
316312AB1-027
Solar/Wind Harmer
0.321
3147346CASHSCORNER
Solar/Wind Harmer
0.147
316314AB2-024 C
Solar/Wind Harmer
0.813
316059AD1-063 C
Solar/Wind Harmer
0.215
957601AF2-054 GEN
Solar/Wind Harmer
0.285
3141873WAN 176
Solar/Wind Harmer
-0.002
315662AE1-191 GEN
Solar/Wind Harmer
1.146
315666AE1-190 GEN
Solar/Wind Harmer
0.287
3143873LANEXA
Solar/Wind Harmer
-0.006
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
971167AH1-042 GEN
Solar/Wind Harmer
9.109
315976AC1-164 GENA
Solar/Wind Harmer
9.985
316169AC1-164_GENC
Solar/Wind Harmer
8.626
315975AC1-164 GENB
Solar/Wind Harmer
0.295
316233AE1-074 FULL
Solar/Wind Harmer
0.253
971281AH1-106 GEN
Solar/Wind Harmer
1.528
971283AH1-107 GEN
Solar/Wind Harmer
1.528
971285AH1-108 GEN
Adder
0.631
957831AF2-077 GEN
Solar/Wind Harmer
0.282
3138283WHITEMARSH
Solar/Wind Harmer
0.015
316132AB2-190 GEN1
Solar/Wind Harmer
0.937
316369SG1_INVT
Solar/Wind Harmer
1.648
972265AH1-717 GEN
Adder
6.337
3151201GRAVEL4
Adder
5.94
3151191GRAVEL3
Adder
5.865
3151211GRAVEL5
Adder
5.865
971445AH1-216 GEN
Solar/Wind Harmer
5.652
3143316POE
Solar/Wind Harmer
-0.036
3151081ELIZAR1
Adder
7.394
3151091ELIZAR2
Adder
7.266
3152611GOSPORTB
Adder
1.027
3152621GOSPORTC
Adder
0.872
3152601GOSPORTA
Adder
0.804
315833AF1-017_GEN
Solar/Wind Harmer
1.712
316349AD2-085 GEN
Solar/Wind Harmer
0.802
316311AC2-079 GEN
Solar/Wind Harmer
4.545
957871AF2-081 GEN
Solar/Wind Harmer
4.503
316305AF2-043 C
Solar/Wind Harmer
0.271
319010AE1-072 C
Solar/Wind Harmer
1.819
3146406KITTY HAWK
Solar/Wind Harmer
0.007
315835AF2-110_GEN
Solar/Wind Harmer
1.121
313526AB2-022
Solar/Wind Harmer
0.241
3146486SUNBURY
Solar/Wind Harmer
-0.009
3146486SUNBURY
Solar/Wind Harmer
-0.009
316321Z2-027
Solar/Wind Harmer
0.24
3145176PASQUOTANK
Solar/Wind Harmer
-0.006
3146396TANGLEW
Solar/Wind Harmer
0.164
316315AB2-025 C
Solar/Wind Harmer
0.238
315814AE2-033 C
Solar/Wind Harmer
8.205
315611Z1-036_GEN2
Solar/Wind Harmer
2.172
941031AE2-094 GEN
Solar/Wind Harmer
16.483
944011AF1-069 GEN
Solar/Wind Harmer
5.165
3130156CHOWAN
Solar/Wind Harmer
-0.009
3130156CHOWAN
Solar/Wind Harmer
-0.009
970673AG2-436 GEN
Solar/Wind Harmer
18.299
970673AG2-436 GEN
Solar/Wind Harmer
9.265
971967AH1-528 GEN
Solar/Wind Harmer
16.294
315816AE2-034 GEN
Solar/Wind Harmer
0.697
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315732AD1-074 GEN1
Solar/Wind Harmer
1.721
315733AD1-074 GEN2
Solar/Wind Harmer
1.721
315735AD1-075 GEN1
Solar/Wind Harmer
0.861
965291AG1-394 GEN
Solar/Wind Harmer
0.754
3146206CASHIE
Solar/Wind Harmer
-0.008
970601AG2-382 GEN
Solar/Wind Harmer
3.701
316318V4-068
Solar/Wind Harmer
0.211
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
5.265
970581AG2-369 GEN
Solar/Wind Harmer
4.528
3145513AHOSKIE
Solar/Wind Harmer
0.073
961941AG1-037 GEN
Solar/Wind Harmer
0.063
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3146043SEABORD
Solar/Wind Harmer
-0.008
946281AF1-292 GEN
Solar/Wind Harmer
0.187
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315607AA1-063A GEN
Solar/Wind Harmer
0.843
316087AB2-174 GEN
Solar/Wind Harmer
1.187
972205AH1-687 GEN
Adder
3.134
972193AH1-681 GEN
Adder
1.643
3151881LOWMORC
Adder
0.64
3151881LOWMORC
Adder
0.63
3151861LOWMORA
Adder
0.62
960921AF2-383 GEN
Solar/Wind Helper
0.139
205943AE1-185 GEN
Solar/Wind Helper
0.387
205956AE1-196_GEN
Solar/Wind Helper
0.385
205932AD2-116_GEN
Solar/Wind Helper
0.385
959381AF2-229 GEN
Solar/Wind Helper
0.257
237085AD2-009_GEN
Solar/Wind Helper
0.97
203975AE1-071-GEN
Solar/Wind Helper
1.713
233935AB2-179 C
Solar/Wind Helper
0.772
232436AB1-176 C
Solar/Wind Helper
0.027
233923SMA
Solar/Wind Helper
0.575
233990AG1-397 GEN
Solar/Wind Helper
0.018
232432Z2-076 GEN
Solar/Wind Helper
0.04
234033AF1-007_GEN
Solar/Wind Helper
4.208
964001AG1-254 GEN
Solar/Wind Helper
0.565
219914AD2-027 C
Solar/Wind Helper
0.068
228754AB1-001 C
Solar/Wind Helper
0.015
227927V4-067C
Solar/Wind Helper
0.006
219272CLEANLIGHT C
Solar/Wind Helper
0.015
219688LUMSOLAR_S C
Solar/Wind Helper
0.023
219607WPEMNERT C
Solar/Wind Helper
0.047
214067T20SOLAR
Solar/Wind Helper
0.007
20715728PEM_W1-119
Solar/Wind Helper
0.056
20715828PEM_W1-120
Solar/Wind Helper
0.056
207459AE1-142 C O1
Solar/Wind Helper
0.169
219620RIDERU C
Solar/Wind Helper
0.001
20675528CPH_W2-050
Solar/Wind Helper
0.05
218526CNTRALGAS2 C
Solar/Wind Helper
0.093
218524CNTRALGAS1 C
Solar/Wind Helper
0.093
966261AG1-495 GEN
Solar/Wind Helper
0.047
20675928HOL_W4-097
Solar/Wind Helper
0.029
207530AG1-191 GEN
Solar/Wind Helper
0.038
207484AF2-139 C O1
Solar/Wind Helper
0.048
20676328BVR_Y1-020
Solar/Wind Helper
0.015
20674828DL_W4-046
Solar/Wind Helper
0.004
207408W3-077 C
Solar/Wind Helper
0.048
20675728RH_W2-091
Solar/Wind Helper
0.078
20675128HRM_W1-127
Solar/Wind Helper
0.017
209116AE2-175 GEN
Solar/Wind Helper
1.004
961261AF2-417 GEN
Solar/Wind Helper
0.241
959431AF2-234 GEN
Solar/Wind Helper
0.466
964051AG1-259 GEN
Solar/Wind Helper
0.035
964061AG1-260 GEN
Solar/Wind Helper
0.035
959421AF2-233 GEN
Solar/Wind Helper
0.233
238208AF1-136 C
Solar/Wind Helper
0.089
972289AH1-729 GEN
50/50
13.252
3150071POSSM 5
Adder
49.581
3150181POSSMC2
Adder
1.094
3150181POSSMC2
Adder
1.085
3150181POSSMC2
Adder
1.085
316447AC1-158 HLD
Solar/Wind Harmer
2.295
3150391LDYSMT3
Adder
12.669
972195AH1-682 GEN
Adder
1.665
315651AD1-115 GEN
Solar/Wind Harmer
4.661
315673AE1-157 GEN
Solar/Wind Harmer
7.8
957411AF2-035 GEN
Solar/Wind Harmer
4.619
970317AG2-208 GEN
Solar/Wind Harmer
4.491
316468AD1-105 GEN
Solar/Wind Harmer
1.121
316077AC2-138 C
Solar/Wind Harmer
0.207
3150341NORNECKC1
Adder
0.915
3150341NORNECKC1
Adder
0.907
966001AG1-469 GEN
Solar/Wind Harmer
0.184
958261AF2-120 GEN
Solar/Wind Harmer
3.769
3151731LOISA B
Adder
5.598
3151721LOISA A
Adder
5.569
316487AF1-042 GEN
Solar/Wind Harmer
1.275
966871AG1-558 GEN
Solar/Wind Harmer
0.29
966871AG1-558 GEN
Solar/Wind Harmer
0.099
3142296MT RD221
Adder
0.271
316441AF1-014 GEN
Solar/Wind Harmer
0.641
3142366NRTHEST
Adder
0.276
3150691DARBY 3
Adder
6.069
3150701DARBY 4
Adder
6.055
3150681DARBY 2
Adder
6.048
3150671DARBY 1
Adder
6.041
316075AC2-137 C
Solar/Wind Harmer
0.255
3142946ENON
Solar/Wind Harmer
-0.001
3143526WINTERP
Solar/Wind Harmer
-0.049
971223AH1-071 GEN
Solar/Wind Harmer
1.172
944641AF1-129 GEN
Adder
39.415
316240AF1-291 C
Solar/Wind Harmer
0.279
316033AB2-134 GEN
Solar/Wind Harmer
2.975
315697AD1-025 GEN
Solar/Wind Harmer
1.866
316236AE1-162_GEN
Solar/Wind Harmer
0.275
970657AG2-426 GEN
Solar/Wind Harmer
2.837
970657AG2-426 GEN
Solar/Wind Harmer
0.593
316036AC1-147 C
Solar/Wind Harmer
0.244
3150991CHESPKB
Adder
0.845
3150991CHESPKB
Adder
0.825
3142956BIRDNECK
Solar/Wind Harmer
0.486
316316AC1-027 C
Solar/Wind Harmer
0.278
316185AD1-033 GEN
Solar/Wind Harmer
0.954
3145506HICKORY
Solar/Wind Harmer
-0.036
3145506HICKORY
Solar/Wind Harmer
-0.022
3145506HICKORY
Solar/Wind Harmer
-0.005
316339AD2-160 GEN
Solar/Wind Harmer
0.608
316018AA1-139 ULT2
Solar/Wind Harmer
0.771
316017AA1-139 ULT1
Solar/Wind Harmer
0.729
3137176SLIGO L2192
Solar/Wind Harmer
-0.036
3146456SLIGO L269
Solar/Wind Harmer
1.062
3130086AYDLETT
Solar/Wind Harmer
-0.036
3146386ELIZ CT
Solar/Wind Harmer
-0.009
316431W1029_GEN1
Solar/Wind Harmer
1.61
316433W1029_GEN2
Solar/Wind Harmer
1.61
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3144356SAPONY
Solar/Wind Harmer
0.308
315742AE1-103 GEN
Solar/Wind Harmer
0.916
3146376EDENTON
Solar/Wind Harmer
0.259
3146376EDENTON
Solar/Wind Harmer
0.259
972185AH1-677 GEN
Adder
4.33
972187AH1-678 GEN
Adder
2.184
970933AG2-581 GEN
Solar/Wind Harmer
8.04
316065AD1-022 GEN
Solar/Wind Harmer
4.239
3145893MURPHYS
Solar/Wind Harmer
0.236
3145893MURPHYS
Solar/Wind Harmer
-0.015
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
970099AG2-077 GEN
Solar/Wind Harmer
10.411
316181AB2-040 GEN
Solar/Wind Harmer
1.158
3144293JTRSVLE
Adder
0.23
3144293JTRSVLE
Adder
0.193
226929AD2-058 GEN
Solar/Wind Helper
0.143
237025AB1-124 C
Solar/Wind Helper
0.193
237006AB1-125 GEN
Solar/Wind Helper
0.145
23777801MSM_W1-116
Solar/Wind Helper
0.13
237034AC2-136 C
Solar/Wind Helper
0.205
205916AD1-020 GEN
Solar/Wind Helper
1.48
208835TUHI V3-051
Solar/Wind Helper
0.019
208835TUHI V3-051
Solar/Wind Helper
0.019
237001AB1-127_GEN
Solar/Wind Helper
0.307
237002AB1-128_GEN
Solar/Wind Helper
0.298
235063AE1-101 C2
Solar/Wind Helper
1.064
20390526W1-045 C
Solar/Wind Helper
0.252
23777901MDS_W4-102
Solar/Wind Helper
0.105
235020AA1-095 C
Solar/Wind Helper
0.029
233933AB2-153 GEN
Solar/Wind Helper
0.14
233944AB2-135 GEN
Solar/Wind Helper
0.355
232424Y1-079 C
Solar/Wind Helper
0.07
233987AB2-037 GEN
Solar/Wind Helper
1.406
234036AF2-325 C
Solar/Wind Helper
0.025
233946AB2-136 GEN
Solar/Wind Helper
0.341
233901CHERRYDALE C
Solar/Wind Helper
0.139
232408W1-005 C
Solar/Wind Helper
0.304
232410W1-006 C
Solar/Wind Helper
0.304
233939AC1-091 C
Solar/Wind Helper
0.209
233970AC1-092 C
Solar/Wind Helper
0.209
230433AD2-135 GEN
Solar/Wind Helper
0.01
219921AF1-264
Solar/Wind Helper
0.03
230407AD2-065 C
Solar/Wind Helper
0.024
219615MILLCREEK C
Solar/Wind Helper
0.016
963401AG1-189 GEN
Solar/Wind Helper
0.033
963391AG1-188 GEN
Solar/Wind Helper
0.048
20714928UPF_X1-085
Solar/Wind Helper
0.003
20720628TIN_W1-124
Solar/Wind Helper
0.11
20716928W4-060COL
Solar/Wind Helper
0.03
20673828FLE_V3-070
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.009
207442AE1-156 GEN
Solar/Wind Helper
0.188
20676128MHD_W3-029
Solar/Wind Helper
0.055
20671828STAW2-080
Solar/Wind Helper
0.015
217081WEATEXAS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.004
217204WCALDSOLAR C
Solar/Wind Helper
0.002
207471AF2-354 C
Solar/Wind Helper
0.097
20674928WA_W3-044
Solar/Wind Helper
0.056
964851AG1-348 GEN
Solar/Wind Helper
0.046
20674128FR_U2-059
Solar/Wind Helper
0.002
20676228FRD_X1-012
Solar/Wind Helper
0.052
966111AG1-480 GEN
Solar/Wind Helper
0.025
211065PSPA IPP
Solar/Wind Helper
0.085
211065PSPA IPP
Solar/Wind Helper
0.085
208972BECR K09
Solar/Wind Helper
0.178
961431AF2-434 GEN
Solar/Wind Helper
0.236
209029WAYMART-WD
Solar/Wind Helper
0.442
209054AE2-059 GEN
Solar/Wind Helper
0.042
946751AF1-339 GEN
Solar/Wind Helper
0.233
209137AF2-361 C
Solar/Wind Helper
0.708
3152131X4-039 ST
50/50
2.893
3152121X4-039 GT2
50/50
1.833
3140676OCCOQUN
Adder
0.27
972223AH1-696 GEN
Adder
8.569
3150151POSSMC1
Adder
1.085
3141346CRANES
Adder
0.12
3150221REMNGT2
Adder
12.463
3150211REMNGT1
Adder
12.381
972201AH1-685 GEN
Adder
2.15
3150281M RUN A
Adder
13.354
316006AB2-029 C
Solar/Wind Harmer
0.631
971685AH1-345 GEN
Solar/Wind Harmer
0.961
316045AC1-158 PL2
Solar/Wind Harmer
3.338
972197AH1-683 GEN
Adder
1.982
972219AH1-694 GEN
Adder
1.427
316254AC1-120 GEN1
Solar/Wind Harmer
0.849
957971AF2-091 GEN
Solar/Wind Harmer
1.037
972135AH1-637 GEN
Solar/Wind Harmer
1.031
966881AG1-559 GEN
Solar/Wind Harmer
0.106
315683AE1-153 C
Solar/Wind Harmer
9.501
3147666LOUISA
Solar/Wind Harmer
-0.04
316192AB2-158 GEN
Solar/Wind Harmer
1.185
316337AD2-073 GEN
Solar/Wind Harmer
0.267
3150351NORNECKC2
Adder
0.871
964211AG1-282 GEN
Solar/Wind Harmer
0.294
3141726DUNNSVL
Solar/Wind Harmer
-0.039
962861AG1-135 GEN
Solar/Wind Harmer
3.642
3151751LOISA D
Adder
5.598
961951AG1-038 GEN
Solar/Wind Harmer
1.275
3138133OCRAN
Solar/Wind Harmer
-0.006
3142416OLDCHRC
Solar/Wind Harmer
-0.025
3142416OLDCHRC
Solar/Wind Harmer
-0.009
3141766HARMONY
Solar/Wind Harmer
-0.002
971777AH1-397 GEN
Solar/Wind Harmer
1.118
3141843SHACKLE
Adder
0.432
3142433PROV 92
Solar/Wind Harmer
-0.038
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
3143096IRON208
Adder
0.351
3143526WINTERP
Solar/Wind Harmer
-0.049
3142543TWELFTH
Solar/Wind Harmer
-0.001
3150851SPRUNCC
Adder
0.385
944631AF1-128 GEN
Adder
39.856
3143226MDLTHAN
Solar/Wind Harmer
-0.009
316159AE1-175 C
Solar/Wind Harmer
0.25
971317AH1-138 GEN
Solar/Wind Harmer
1.163
970129AG2-093 GEN
Solar/Wind Harmer
2.113
316458AB2-190 GEN2
Solar/Wind Harmer
0.937
315671AE2-027_GEN
Solar/Wind Harmer
6.943
3138126ROCKLANDING
Solar/Wind Harmer
0.028
971069AG2-661 GEN
Solar/Wind Harmer
1.462
971647AH1-324 GEN
Solar/Wind Harmer
4.604
961611AG1-000B GEN
Solar/Wind Harmer
4.536
3151171GRAVELC
Adder
0.868
3145336SMITFLD
Solar/Wind Harmer
-0.036
316294AC1-161 GEN
Solar/Wind Harmer
2.948
970659AG2-427 GEN
Solar/Wind Harmer
4.83
316381AD1-082 GEN
Solar/Wind Harmer
0.833
316375AC2-012 GEN
Solar/Wind Harmer
3.136
3150981CHESPKA
Adder
1.007
970661AG2-428 GEN
Solar/Wind Harmer
9.631
944591AF1-124 GEN
Solar/Wind Harmer
41.344
316072AD1-144
Solar/Wind Harmer
0.183
316388AE2-253 GEN
Solar/Wind Harmer
0.608
3146456SLIGO L269
Solar/Wind Harmer
-0.009
939411AE1-173 GEN
Solar/Wind Harmer
44.981
316246AF1-032 C
Solar/Wind Harmer
0.182
940641AE2-051 GEN
Solar/Wind Harmer
8.42
316093AE2-104_GEN
Solar/Wind Harmer
2.607
3143336POWHATN
Solar/Wind Harmer
1.059
3146516WINFALL
Solar/Wind Harmer
-0.029
3146516WINFALL
Solar/Wind Harmer
-0.009
316336AC2-165 C
Solar/Wind Harmer
1.53
315800Z1-036_GEN1
Solar/Wind Harmer
2.172
3130156CHOWAN
Solar/Wind Harmer
-0.009
3145663CRESWEL
Solar/Wind Harmer
-0.024
971163AH1-040 GEN
Solar/Wind Harmer
8.075
970937AG2-583 GEN
Solar/Wind Harmer
6.109
316023GEN1_S
Solar/Wind Harmer
0.57
3146206CASHIE
Solar/Wind Harmer
-0.008
971547AH1-271 GEN
Solar/Wind Harmer
2.115
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.251
970919AG2-571 GEN
Solar/Wind Harmer
2.672
970087AG2-069 GEN
Solar/Wind Harmer
7.898
3146173TUNIS
Solar/Wind Harmer
-0.008
960081AF2-299 GEN
Solar/Wind Harmer
0.94
3145683EARLEYS
Solar/Wind Harmer
-0.008
957481AF2-042 GEN
Solar/Wind Harmer
26.028
3146263WOODLND
Solar/Wind Harmer
-0.008
3147043LAWRENC
Adder
0.664
3144293JTRSVLE
Adder
0.23
972277AH1-723 GEN
Adder
42.843
23779801AA1-109
Solar/Wind Helper
0.217
223401AF1-299 GEN
Solar/Wind Helper
0.397
966131AG1-482 GEN
Solar/Wind Helper
0.063
237080AD1-060 GEN
Solar/Wind Helper
0.221
235062AE1-101 C1
Solar/Wind Helper
1.064
237038AE2-054 C
Solar/Wind Helper
0.173
233930AB2-032 GEN
Solar/Wind Helper
0.23
233915AB1-141 GEN
Solar/Wind Helper
0.303
232422X3-066 FULL
Solar/Wind Helper
0.069
233964AF2-378 GEN
Solar/Wind Helper
0.025
232426Y1-080 FULL
Solar/Wind Helper
0.023
232428Y3-058 C
Solar/Wind Helper
0.203
233998TM1NIN_3.36
Solar/Wind Helper
0.157
233954AC2-188 GEN
Solar/Wind Helper
0.139
232404W1-003 C
Solar/Wind Helper
0.304
233950AC2-186 GEN
Solar/Wind Helper
0.07
232434Z2-077 GEN
Solar/Wind Helper
0.076
233972AC1-094 C
Solar/Wind Helper
0.181
205941AD2-115 GEN
Solar/Wind Helper
0.302
230434AG1-499 GEN
Solar/Wind Helper
0.136
230511AF1-262
Solar/Wind Helper
0.009
219258KINSLEYDEP C
Solar/Wind Helper
0.045
228728W1-130C
Solar/Wind Helper
0.032
219904AC1-010 C
Solar/Wind Helper
0.036
219907AC1-030 C
Solar/Wind Helper
0.02
218660EHAMPSOLAR C
Solar/Wind Helper
0.019
219686LUMSOLAR_N C
Solar/Wind Helper
0.023
219304NAMERICA C
Solar/Wind Helper
0.077
20720728JCB_W1-129
Solar/Wind Helper
0.033
207445AB1-138_GEN
Solar/Wind Helper
0.061
963711AG1-223 GEN
Solar/Wind Helper
0.037
20714828MDF_W3-079
Solar/Wind Helper
0.076
219680HOPEWELLV C1
Solar/Wind Helper
0.002
207454AA2-184 E
Solar/Wind Helper
0.18
20715228NPK_W1-113
Solar/Wind Helper
0.045
20742028HF_AC1-207
Solar/Wind Helper
0.082
207528AF2-192 GEN
Solar/Wind Helper
0.044
20673628F1S_V4-069
Solar/Wind Helper
0.017
20675428EAM_W2-061
Solar/Wind Helper
0.009
218428ETC SOLAR C
Solar/Wind Helper
0.003
20676428JCR_X2-075
Solar/Wind Helper
0.039
217213AMBOY SO C
Solar/Wind Helper
0.017
217209CENTRL HS C
Solar/Wind Helper
0.005
217208PARK ELE C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.013
207437AD2-070 GEN
Solar/Wind Helper
0.079
207439AE1-081 C O1
Solar/Wind Helper
0.011
207518AF1-320_GEN
Solar/Wind Helper
0.9
20671928W4-073
Solar/Wind Helper
0.051
20675828AU_W4-064
Solar/Wind Helper
0.017
961301AF2-421 GEN
Solar/Wind Helper
0.242
963151AG1-164 GEN
Solar/Wind Helper
0.242
212266LOR1
Solar/Wind Helper
0.026
961341AF2-425 GEN
Solar/Wind Helper
0.237
212507AE2-042_GEN
Solar/Wind Helper
0.829
946731AF1-337 GEN
Solar/Wind Helper
0.233
209071AE2-133 GEN
Solar/Wind Helper
0.042
315693AD1-088 GEN
Solar/Wind Harmer
1.373
NYPJM->LTFIMP_NY
CLTF
2.575
LGEELTFEXP_LGEE->PJM
CLTF
1.805
WECLTFEXP_WEC->PJM
CLTF
0.962
LAGNLTFEXP_LAGN->PJM
CLTF
6.323
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.563
TVALTFEXP_TVA->PJM
CLTF
3.187
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.478
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.59
MECLTFEXP_MEC->PJM
CLTF
4.448
SIGELTFEXP_SIGE->PJM
CLTF
0.14
CPLELTFEXP_CPLE->PJM
CLTF
5.064
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.958

Details for 6EDFERRY-DICKH230 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T560_SRT-A


Base Case Flowgate

Area:DVP/PEPCO
Facility Description:
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T560_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:146.6 %
Rating:1417.0 MVA
Rating Type:B
MVA to Mitigate:2077.39
MW Contribution:42.84
Bus #Bus NameTypeMW Contribution
3152111X4-039 GT1
50/50
1.839
315747AE2-019 GEN
50/50
13.179
963691AG1-221 GEN
Solar/Wind Harmer
2.313
971455AH1-223 GEN
Solar/Wind Harmer
2.313
3150151POSSMC1
Adder
1.085
3150151POSSMC1
Adder
1.085
3141196NOKESVL
Solar/Wind Harmer
-0.048
3150231REMNGT3
Adder
13.456
3150241REMNGT4
Adder
12.546
972199AH1-684 GEN
Adder
1.902
972217AH1-693 GEN
Adder
1.654
970053AG2-049 GEN
50/50
2.028
3138216PACIFIC
Solar/Wind Harmer
-0.003
316411AF1-147_GEN1
Solar/Wind Harmer
1.101
316415AF1-147_GEN2
Solar/Wind Harmer
1.101
3141426STAFORD
Solar/Wind Harmer
-0.003
3150411LDYSMT5
Adder
12.733
3150381LDYSMT2
Adder
12.186
972213AH1-691 GEN
Adder
2.061
972215AH1-692 GEN
Adder
2.061
316164AC1-076 GEN
Solar/Wind Harmer
0.887
944491AF1-114 GEN
Solar/Wind Harmer
3.051
316223AC1-118
Solar/Wind Harmer
0.272
972189AH1-679 GEN
Adder
1.468
3141813NORNECK
Solar/Wind Harmer
-0.01
962981AG1-147 GEN
Solar/Wind Harmer
4.221
3141783LANCAST
Solar/Wind Harmer
-0.006
3141783LANCAST
Solar/Wind Harmer
-0.004
3138133OCRAN
Solar/Wind Harmer
-0.003
3141913WHIT STONE
Solar/Wind Harmer
-0.01
316312AB1-027
Solar/Wind Harmer
0.321
3147346CASHSCORNER
Solar/Wind Harmer
0.147
316314AB2-024 C
Solar/Wind Harmer
0.813
957601AF2-054 GEN
Solar/Wind Harmer
0.285
316059AD1-063 C
Solar/Wind Harmer
0.215
3141873WAN 176
Solar/Wind Harmer
-0.002
315662AE1-191 GEN
Solar/Wind Harmer
1.146
315666AE1-190 GEN
Solar/Wind Harmer
0.287
3143873LANEXA
Solar/Wind Harmer
-0.006
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
971167AH1-042 GEN
Solar/Wind Harmer
9.109
315976AC1-164 GENA
Solar/Wind Harmer
9.985
316169AC1-164_GENC
Solar/Wind Harmer
8.626
315975AC1-164 GENB
Solar/Wind Harmer
0.295
316233AE1-074 FULL
Solar/Wind Harmer
0.253
971281AH1-106 GEN
Solar/Wind Harmer
1.528
971283AH1-107 GEN
Solar/Wind Harmer
1.528
971285AH1-108 GEN
Adder
0.631
957831AF2-077 GEN
Solar/Wind Harmer
0.282
3138283WHITEMARSH
Solar/Wind Harmer
0.015
316132AB2-190 GEN1
Solar/Wind Harmer
0.937
316369SG1_INVT
Solar/Wind Harmer
1.648
972265AH1-717 GEN
Adder
6.337
3151201GRAVEL4
Adder
5.94
3151191GRAVEL3
Adder
5.865
3151211GRAVEL5
Adder
5.865
971445AH1-216 GEN
Solar/Wind Harmer
5.652
3143316POE
Solar/Wind Harmer
-0.036
3151081ELIZAR1
Adder
7.394
3151091ELIZAR2
Adder
7.266
3152611GOSPORTB
Adder
1.027
3152621GOSPORTC
Adder
0.872
3152601GOSPORTA
Adder
0.804
315833AF1-017_GEN
Solar/Wind Harmer
1.712
316349AD2-085 GEN
Solar/Wind Harmer
0.802
316311AC2-079 GEN
Solar/Wind Harmer
4.545
957871AF2-081 GEN
Solar/Wind Harmer
4.503
316305AF2-043 C
Solar/Wind Harmer
0.271
319010AE1-072 C
Solar/Wind Harmer
1.819
3146406KITTY HAWK
Solar/Wind Harmer
0.007
315835AF2-110_GEN
Solar/Wind Harmer
1.121
313526AB2-022
Solar/Wind Harmer
0.241
3146486SUNBURY
Solar/Wind Harmer
-0.009
3146486SUNBURY
Solar/Wind Harmer
-0.009
316321Z2-027
Solar/Wind Harmer
0.24
3145176PASQUOTANK
Solar/Wind Harmer
-0.006
3146396TANGLEW
Solar/Wind Harmer
0.164
316315AB2-025 C
Solar/Wind Harmer
0.238
315814AE2-033 C
Solar/Wind Harmer
8.205
315611Z1-036_GEN2
Solar/Wind Harmer
2.172
941031AE2-094 GEN
Solar/Wind Harmer
16.482
944011AF1-069 GEN
Solar/Wind Harmer
5.164
3130156CHOWAN
Solar/Wind Harmer
-0.009
3130156CHOWAN
Solar/Wind Harmer
-0.009
970673AG2-436 GEN
Solar/Wind Harmer
18.298
970673AG2-436 GEN
Solar/Wind Harmer
9.265
971967AH1-528 GEN
Solar/Wind Harmer
16.294
315816AE2-034 GEN
Solar/Wind Harmer
0.697
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315732AD1-074 GEN1
Solar/Wind Harmer
1.721
315733AD1-074 GEN2
Solar/Wind Harmer
1.721
315735AD1-075 GEN1
Solar/Wind Harmer
0.861
965291AG1-394 GEN
Solar/Wind Harmer
0.754
3146206CASHIE
Solar/Wind Harmer
-0.008
970601AG2-382 GEN
Solar/Wind Harmer
3.701
316318V4-068
Solar/Wind Harmer
0.211
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
5.265
970581AG2-369 GEN
Solar/Wind Harmer
4.528
3145513AHOSKIE
Solar/Wind Harmer
0.073
961941AG1-037 GEN
Solar/Wind Harmer
0.063
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3146043SEABORD
Solar/Wind Harmer
-0.008
946281AF1-292 GEN
Solar/Wind Harmer
0.187
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315607AA1-063A GEN
Solar/Wind Harmer
0.843
316087AB2-174 GEN
Solar/Wind Harmer
1.187
972205AH1-687 GEN
Adder
3.134
972193AH1-681 GEN
Adder
1.643
3151881LOWMORC
Adder
0.64
3151881LOWMORC
Adder
0.63
3151861LOWMORA
Adder
0.62
960921AF2-383 GEN
Solar/Wind Helper
0.139
205943AE1-185 GEN
Solar/Wind Helper
0.387
205956AE1-196_GEN
Solar/Wind Helper
0.385
205932AD2-116_GEN
Solar/Wind Helper
0.385
959381AF2-229 GEN
Solar/Wind Helper
0.257
237085AD2-009_GEN
Solar/Wind Helper
0.97
203975AE1-071-GEN
Solar/Wind Helper
1.713
233935AB2-179 C
Solar/Wind Helper
0.772
232436AB1-176 C
Solar/Wind Helper
0.027
233923SMA
Solar/Wind Helper
0.575
233990AG1-397 GEN
Solar/Wind Helper
0.018
232432Z2-076 GEN
Solar/Wind Helper
0.04
234033AF1-007_GEN
Solar/Wind Helper
4.208
964001AG1-254 GEN
Solar/Wind Helper
0.565
219914AD2-027 C
Solar/Wind Helper
0.068
228754AB1-001 C
Solar/Wind Helper
0.015
227927V4-067C
Solar/Wind Helper
0.006
219272CLEANLIGHT C
Solar/Wind Helper
0.015
219688LUMSOLAR_S C
Solar/Wind Helper
0.023
219607WPEMNERT C
Solar/Wind Helper
0.047
214067T20SOLAR
Solar/Wind Helper
0.007
20715728PEM_W1-119
Solar/Wind Helper
0.056
20715828PEM_W1-120
Solar/Wind Helper
0.056
207459AE1-142 C O1
Solar/Wind Helper
0.169
219620RIDERU C
Solar/Wind Helper
0.001
20675528CPH_W2-050
Solar/Wind Helper
0.05
218526CNTRALGAS2 C
Solar/Wind Helper
0.093
218524CNTRALGAS1 C
Solar/Wind Helper
0.093
966261AG1-495 GEN
Solar/Wind Helper
0.047
20675928HOL_W4-097
Solar/Wind Helper
0.029
207530AG1-191 GEN
Solar/Wind Helper
0.038
207484AF2-139 C O1
Solar/Wind Helper
0.048
20676328BVR_Y1-020
Solar/Wind Helper
0.015
20674828DL_W4-046
Solar/Wind Helper
0.004
207408W3-077 C
Solar/Wind Helper
0.048
20675728RH_W2-091
Solar/Wind Helper
0.078
20675128HRM_W1-127
Solar/Wind Helper
0.017
209116AE2-175 GEN
Solar/Wind Helper
1.004
961261AF2-417 GEN
Solar/Wind Helper
0.241
959431AF2-234 GEN
Solar/Wind Helper
0.466
964051AG1-259 GEN
Solar/Wind Helper
0.035
964061AG1-260 GEN
Solar/Wind Helper
0.035
959421AF2-233 GEN
Solar/Wind Helper
0.233
238208AF1-136 C
Solar/Wind Helper
0.089
3150331BIRCHWDA
Adder
16.699
3150301M RUN C
Adder
13.346
3150291M RUN B
Adder
13.246
3141316ARNOLDS
Adder
0.23
3150401LDYSMT4
Adder
12.694
3150371LDYSMT1
Adder
12.265
316044AC1-158 PL1
Solar/Wind Harmer
1.043
316450AC1-158 RIC
Solar/Wind Harmer
0.278
316170AC1-121 GEN2
Solar/Wind Harmer
0.283
966881AG1-559 GEN
Solar/Wind Harmer
0.309
970737AG2-469 GEN
Solar/Wind Harmer
5.111
3141906WESTMOR
Solar/Wind Harmer
-0.004
3132273ORANGE
Solar/Wind Harmer
-0.002
971781AH1-399 GEN
Solar/Wind Harmer
0.62
3147666LOUISA
Solar/Wind Harmer
-0.023
3150351NORNECKC2
Adder
0.885
316404AE1-155 C
Solar/Wind Harmer
1.876
3151761LOISA E
Adder
11.411
316484AD2-074 GEN
Solar/Wind Harmer
2.436
970009AG2-005 GEN
Solar/Wind Harmer
1.21
972183AH1-676 GEN
Adder
92.013
316473AC1-191 GEN
Solar/Wind Harmer
1.04
962971AG1-146 GEN
Solar/Wind Harmer
1.809
3142416OLDCHRC
Solar/Wind Harmer
0.961
316156AD2-030 GEN
Solar/Wind Harmer
0.254
3141873WAN 176
Solar/Wind Harmer
1.129
3141766HARMONY
Solar/Wind Harmer
0.847
316280AD1-041 GEN
Solar/Wind Harmer
0.717
316203AE2-005 GEN
Solar/Wind Harmer
4.009
3141843SHACKLE
Adder
0.432
970293AG2-193 GEN
Solar/Wind Harmer
1.184
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
3143096IRON208
Adder
0.351
3143096IRON208
Adder
0.344
3142946ENON
Solar/Wind Harmer
-0.003
3150861SPRUNCD
Adder
0.385
316382AG1-145 C
Solar/Wind Harmer
0.281
970133AG2-095 GEN
Solar/Wind Harmer
1.046
970129AG2-093 GEN
Solar/Wind Harmer
5.216
3150921YORKTN3
Adder
2.069
315778AD1-151 GEN
Solar/Wind Harmer
8.005
965281AG1-393 GEN
Solar/Wind Harmer
1.155
3144216WINCHST
Adder
0.31
315839AE2-212 C
Solar/Wind Harmer
0.278
961611AG1-000B GEN
Solar/Wind Harmer
1.935
3151221GRAVEL6
Adder
5.934
3151171GRAVELC
Adder
1.142
3145336SMITFLD
Solar/Wind Harmer
-0.004
315813AE1-149 C
Solar/Wind Harmer
5.707
315773AC2-141 GEN
Solar/Wind Harmer
3.812
970659AG2-427 GEN
Solar/Wind Harmer
0.856
316083AB2-161 GEN
Solar/Wind Harmer
1.475
3144536CHRHLND
Solar/Wind Harmer
-0.001
3151101ELIZAR3
Adder
7.489
970661AG2-428 GEN
Solar/Wind Harmer
1.707
3144873MCLAUGH
Solar/Wind Harmer
0
944581AF1-123 GEN
Solar/Wind Harmer
41.195
944601AF1-125 GEN
Solar/Wind Harmer
40.552
3146456SLIGO L269
Solar/Wind Harmer
-0.009
971153AH1-033 GEN
Solar/Wind Harmer
1.096
316320Y1-086
Solar/Wind Harmer
0.524
316313AB2-026
Solar/Wind Harmer
0.241
316258AE1-075 C
Solar/Wind Harmer
0.217
316405AF2-144 C
Solar/Wind Harmer
0.229
3143336POWHATN
Solar/Wind Harmer
0.9
316435W1029_GEN3
Solar/Wind Harmer
1.61
3146516WINFALL
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3145273HOLLAND
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.009
315614AA2-178 GEN
Solar/Wind Harmer
0.929
971157AH1-035 GEN
Solar/Wind Harmer
1.066
3156081AA2-088 GEN
Solar/Wind Harmer
2.765
315737AD1-076 GEN
Solar/Wind Harmer
1.618
316365GEN2_N
Solar/Wind Harmer
0.57
3146206CASHIE
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.059
3145893MURPHYS
Solar/Wind Harmer
-0.008
970917AG2-570 GEN
Solar/Wind Harmer
21.109
957521AF2-046 GEN
Solar/Wind Harmer
6.644
961681AG1-008 GEN
Solar/Wind Harmer
6.644
3146173TUNIS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1.13
316463AE2-346 GEN
Solar/Wind Harmer
0.136
316140AB2-099
Solar/Wind Harmer
0.056
962331AG1-082 GEN
Solar/Wind Harmer
1.047
966621AG1-532 GEN
Solar/Wind Harmer
0.17
3146263WOODLND
Solar/Wind Harmer
-0.008
313506AB2-031 GEN
Solar/Wind Harmer
0.667
3144293JTRSVLE
Adder
0.23
972255AH1-712 GEN
Adder
36.765
3151861LOWMORA
Adder
0.645
226910AB2-157 C
Solar/Wind Helper
0.02
227287AC2-120 GEN
Solar/Wind Helper
0.49
237030AB1-096 C
Solar/Wind Helper
0.083
223402AF1-300 C
Solar/Wind Helper
0.397
205917AD1-020 ES
Solar/Wind Helper
0.318
238221AF1-254 C O1
Solar/Wind Helper
0.179
235067AD1-061 GEN
Solar/Wind Helper
0.312
233982AB2-133 GEN
Solar/Wind Helper
0.216
233918AB1-142 GEN
Solar/Wind Helper
0.303
233994AC2-023 GEN
Solar/Wind Helper
0.577
233996TM1833_GEN
Solar/Wind Helper
0.157
233997TMININ_4.2
Solar/Wind Helper
0.157
233952AC2-187 GEN
Solar/Wind Helper
0.139
232406W1-004 FULL
Solar/Wind Helper
0.304
233940AF2-379 C
Solar/Wind Helper
0.037
234015AF2-250 C
Solar/Wind Helper
0.023
233971AC1-093 C
Solar/Wind Helper
0.214
230430AE1-229_GEN
Solar/Wind Helper
1.995
230415AB2-049 C
Solar/Wind Helper
0.018
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219766PARADISE C
Solar/Wind Helper
0.032
219912AD2-042 GEN
Solar/Wind Helper
0.089
228729W2-030 C
Solar/Wind Helper
0.065
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.007
219906AC1-017 C
Solar/Wind Helper
0.025
219348LDSOLAR C
Solar/Wind Helper
0.067
959561AF2-247 GEN
Solar/Wind Helper
0.012
20716028EGP_W2-019
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.037
20715028HAN_X4-015
Solar/Wind Helper
0.033
219276PARKLANDSO C
Solar/Wind Helper
0.052
20714528FRN_Y2-051
Solar/Wind Helper
0.033
20720528MAN_W1-024
Solar/Wind Helper
0.016
219612MATRIX C
Solar/Wind Helper
0.014
218438BLK ROCK C
Solar/Wind Helper
0.016
20673728F2S_V4-070
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.043
219919AE1-041 FULL
Solar/Wind Helper
0.002
219249CENTRALDIV C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
217169METRODIV C
Solar/Wind Helper
0.002
20676728BRNX1-095
Solar/Wind Helper
0.017
207510AF2-138 C
Solar/Wind Helper
0.046
20674628WNG_W3-110
Solar/Wind Helper
0.051
963161AG1-165 GEN
Solar/Wind Helper
0.242
963071AG1-156 GEN
Solar/Wind Helper
0.783
209027LOR2_Q27
Solar/Wind Helper
0.557
961331AF2-424 GEN
Solar/Wind Helper
0.237
961421AF2-433 GEN
Solar/Wind Helper
0.236
957921AF2-086 GEN
Solar/Wind Helper
0.234
946691AF1-333 GEN
Solar/Wind Helper
0.233
946741AF1-338 GEN
Solar/Wind Helper
0.233
209067AE2-060 GEN
Solar/Wind Helper
0.042
972289AH1-729 GEN
50/50
13.252
3150071POSSM 5
Adder
49.613
3150181POSSMC2
Adder
1.095
3150181POSSMC2
Adder
1.085
3150181POSSMC2
Adder
1.085
3150391LDYSMT3
Adder
12.67
972195AH1-682 GEN
Adder
1.665
316447AC1-158 HLD
Solar/Wind Harmer
2.294
315651AD1-115 GEN
Solar/Wind Harmer
4.661
315673AE1-157 GEN
Solar/Wind Harmer
7.801
957411AF2-035 GEN
Solar/Wind Harmer
4.62
970317AG2-208 GEN
Solar/Wind Harmer
4.491
316468AD1-105 GEN
Solar/Wind Harmer
1.121
316077AC2-138 C
Solar/Wind Harmer
0.207
3150341NORNECKC1
Adder
0.915
3150341NORNECKC1
Adder
0.907
966001AG1-469 GEN
Solar/Wind Harmer
0.184
958261AF2-120 GEN
Solar/Wind Harmer
3.769
3151731LOISA B
Adder
5.597
3151721LOISA A
Adder
5.568
316487AF1-042 GEN
Solar/Wind Harmer
1.275
966871AG1-558 GEN
Solar/Wind Harmer
0.29
966871AG1-558 GEN
Solar/Wind Harmer
0.099
3142296MT RD221
Adder
0.271
316441AF1-014 GEN
Solar/Wind Harmer
0.641
3142366NRTHEST
Adder
0.276
3150691DARBY 3
Adder
6.069
3150701DARBY 4
Adder
6.055
3150681DARBY 2
Adder
6.048
3150671DARBY 1
Adder
6.041
316075AC2-137 C
Solar/Wind Harmer
0.255
3142946ENON
Solar/Wind Harmer
-0.001
3143526WINTERP
Solar/Wind Harmer
-0.049
971223AH1-071 GEN
Solar/Wind Harmer
1.172
944641AF1-129 GEN
Adder
39.415
316240AF1-291 C
Solar/Wind Harmer
0.279
316033AB2-134 GEN
Solar/Wind Harmer
2.975
315697AD1-025 GEN
Solar/Wind Harmer
1.866
316236AE1-162_GEN
Solar/Wind Harmer
0.275
970657AG2-426 GEN
Solar/Wind Harmer
2.837
970657AG2-426 GEN
Solar/Wind Harmer
0.593
316036AC1-147 C
Solar/Wind Harmer
0.244
3150991CHESPKB
Adder
0.845
3150991CHESPKB
Adder
0.825
316316AC1-027 C
Solar/Wind Harmer
0.278
3142956BIRDNECK
Solar/Wind Harmer
0.486
316185AD1-033 GEN
Solar/Wind Harmer
0.954
3145506HICKORY
Solar/Wind Harmer
-0.036
3145506HICKORY
Solar/Wind Harmer
-0.022
3145506HICKORY
Solar/Wind Harmer
-0.005
316339AD2-160 GEN
Solar/Wind Harmer
0.608
316018AA1-139 ULT2
Solar/Wind Harmer
0.771
316017AA1-139 ULT1
Solar/Wind Harmer
0.729
3137176SLIGO L2192
Solar/Wind Harmer
-0.036
3146456SLIGO L269
Solar/Wind Harmer
1.062
3130086AYDLETT
Solar/Wind Harmer
-0.036
3146386ELIZ CT
Solar/Wind Harmer
-0.009
316431W1029_GEN1
Solar/Wind Harmer
1.61
316433W1029_GEN2
Solar/Wind Harmer
1.61
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3144356SAPONY
Solar/Wind Harmer
0.308
315742AE1-103 GEN
Solar/Wind Harmer
0.916
3146376EDENTON
Solar/Wind Harmer
0.259
3146376EDENTON
Solar/Wind Harmer
0.259
972185AH1-677 GEN
Adder
4.33
972187AH1-678 GEN
Adder
2.184
970933AG2-581 GEN
Solar/Wind Harmer
8.04
316065AD1-022 GEN
Solar/Wind Harmer
4.239
3145893MURPHYS
Solar/Wind Harmer
0.236
3145893MURPHYS
Solar/Wind Harmer
-0.015
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
970099AG2-077 GEN
Solar/Wind Harmer
10.411
316181AB2-040 GEN
Solar/Wind Harmer
1.158
3144293JTRSVLE
Adder
0.23
3144293JTRSVLE
Adder
0.193
226929AD2-058 GEN
Solar/Wind Helper
0.143
237025AB1-124 C
Solar/Wind Helper
0.193
237006AB1-125 GEN
Solar/Wind Helper
0.145
23777801MSM_W1-116
Solar/Wind Helper
0.13
237034AC2-136 C
Solar/Wind Helper
0.205
205916AD1-020 GEN
Solar/Wind Helper
1.48
208835TUHI V3-051
Solar/Wind Helper
0.019
208835TUHI V3-051
Solar/Wind Helper
0.019
237001AB1-127_GEN
Solar/Wind Helper
0.307
237002AB1-128_GEN
Solar/Wind Helper
0.298
235063AE1-101 C2
Solar/Wind Helper
1.064
20390526W1-045 C
Solar/Wind Helper
0.252
23777901MDS_W4-102
Solar/Wind Helper
0.105
235020AA1-095 C
Solar/Wind Helper
0.029
233933AB2-153 GEN
Solar/Wind Helper
0.14
233944AB2-135 GEN
Solar/Wind Helper
0.355
232424Y1-079 C
Solar/Wind Helper
0.07
233987AB2-037 GEN
Solar/Wind Helper
1.406
234036AF2-325 C
Solar/Wind Helper
0.025
233946AB2-136 GEN
Solar/Wind Helper
0.341
233901CHERRYDALE C
Solar/Wind Helper
0.139
232408W1-005 C
Solar/Wind Helper
0.304
232410W1-006 C
Solar/Wind Helper
0.304
233939AC1-091 C
Solar/Wind Helper
0.209
233970AC1-092 C
Solar/Wind Helper
0.209
230433AD2-135 GEN
Solar/Wind Helper
0.01
219921AF1-264
Solar/Wind Helper
0.03
230407AD2-065 C
Solar/Wind Helper
0.024
219615MILLCREEK C
Solar/Wind Helper
0.016
963401AG1-189 GEN
Solar/Wind Helper
0.033
963391AG1-188 GEN
Solar/Wind Helper
0.048
20714928UPF_X1-085
Solar/Wind Helper
0.003
20720628TIN_W1-124
Solar/Wind Helper
0.11
20716928W4-060COL
Solar/Wind Helper
0.03
20673828FLE_V3-070
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.009
207442AE1-156 GEN
Solar/Wind Helper
0.188
20676128MHD_W3-029
Solar/Wind Helper
0.055
20671828STAW2-080
Solar/Wind Helper
0.015
217081WEATEXAS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.004
217204WCALDSOLAR C
Solar/Wind Helper
0.002
207471AF2-354 C
Solar/Wind Helper
0.097
20674928WA_W3-044
Solar/Wind Helper
0.056
964851AG1-348 GEN
Solar/Wind Helper
0.046
20674128FR_U2-059
Solar/Wind Helper
0.002
20676228FRD_X1-012
Solar/Wind Helper
0.052
966111AG1-480 GEN
Solar/Wind Helper
0.025
211065PSPA IPP
Solar/Wind Helper
0.085
211065PSPA IPP
Solar/Wind Helper
0.085
208972BECR K09
Solar/Wind Helper
0.178
961431AF2-434 GEN
Solar/Wind Helper
0.236
209029WAYMART-WD
Solar/Wind Helper
0.442
209054AE2-059 GEN
Solar/Wind Helper
0.042
946751AF1-339 GEN
Solar/Wind Helper
0.233
209137AF2-361 C
Solar/Wind Helper
0.708
3152131X4-039 ST
50/50
2.893
3152121X4-039 GT2
50/50
1.833
3140676OCCOQUN
Adder
0.27
972223AH1-696 GEN
Adder
8.574
3150151POSSMC1
Adder
1.085
3141346CRANES
Adder
0.12
3150221REMNGT2
Adder
12.463
3150211REMNGT1
Adder
12.38
972201AH1-685 GEN
Adder
2.15
3150281M RUN A
Adder
13.354
316006AB2-029 C
Solar/Wind Harmer
0.631
971685AH1-345 GEN
Solar/Wind Harmer
0.961
972197AH1-683 GEN
Adder
1.982
972219AH1-694 GEN
Adder
1.427
316045AC1-158 PL2
Solar/Wind Harmer
3.338
316254AC1-120 GEN1
Solar/Wind Harmer
0.849
957971AF2-091 GEN
Solar/Wind Harmer
1.037
972135AH1-637 GEN
Solar/Wind Harmer
1.031
966881AG1-559 GEN
Solar/Wind Harmer
0.106
315683AE1-153 C
Solar/Wind Harmer
9.501
3147666LOUISA
Solar/Wind Harmer
-0.04
316192AB2-158 GEN
Solar/Wind Harmer
1.185
316337AD2-073 GEN
Solar/Wind Harmer
0.267
3150351NORNECKC2
Adder
0.871
964211AG1-282 GEN
Solar/Wind Harmer
0.294
3141726DUNNSVL
Solar/Wind Harmer
-0.039
962861AG1-135 GEN
Solar/Wind Harmer
3.643
3151751LOISA D
Adder
5.597
961951AG1-038 GEN
Solar/Wind Harmer
1.275
3138133OCRAN
Solar/Wind Harmer
-0.006
3142416OLDCHRC
Solar/Wind Harmer
-0.025
3142416OLDCHRC
Solar/Wind Harmer
-0.009
3141766HARMONY
Solar/Wind Harmer
-0.002
971777AH1-397 GEN
Solar/Wind Harmer
1.118
3141843SHACKLE
Adder
0.432
3142433PROV 92
Solar/Wind Harmer
-0.038
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
3143096IRON208
Adder
0.351
3143526WINTERP
Solar/Wind Harmer
-0.049
3142543TWELFTH
Solar/Wind Harmer
-0.001
3150851SPRUNCC
Adder
0.385
944631AF1-128 GEN
Adder
39.856
3143226MDLTHAN
Solar/Wind Harmer
-0.009
316159AE1-175 C
Solar/Wind Harmer
0.25
971317AH1-138 GEN
Solar/Wind Harmer
1.163
970129AG2-093 GEN
Solar/Wind Harmer
2.113
316458AB2-190 GEN2
Solar/Wind Harmer
0.937
315671AE2-027_GEN
Solar/Wind Harmer
6.943
3138126ROCKLANDING
Solar/Wind Harmer
0.028
971069AG2-661 GEN
Solar/Wind Harmer
1.462
971647AH1-324 GEN
Solar/Wind Harmer
4.604
961611AG1-000B GEN
Solar/Wind Harmer
4.536
3151171GRAVELC
Adder
0.868
3145336SMITFLD
Solar/Wind Harmer
-0.036
316294AC1-161 GEN
Solar/Wind Harmer
2.948
970659AG2-427 GEN
Solar/Wind Harmer
4.83
316381AD1-082 GEN
Solar/Wind Harmer
0.833
316375AC2-012 GEN
Solar/Wind Harmer
3.136
3150981CHESPKA
Adder
1.007
970661AG2-428 GEN
Solar/Wind Harmer
9.631
944591AF1-124 GEN
Solar/Wind Harmer
41.344
316072AD1-144
Solar/Wind Harmer
0.183
316388AE2-253 GEN
Solar/Wind Harmer
0.608
3146456SLIGO L269
Solar/Wind Harmer
-0.009
939411AE1-173 GEN
Solar/Wind Harmer
44.98
316246AF1-032 C
Solar/Wind Harmer
0.182
940641AE2-051 GEN
Solar/Wind Harmer
8.42
316093AE2-104_GEN
Solar/Wind Harmer
2.607
3143336POWHATN
Solar/Wind Harmer
1.059
3146516WINFALL
Solar/Wind Harmer
-0.029
3146516WINFALL
Solar/Wind Harmer
-0.009
316336AC2-165 C
Solar/Wind Harmer
1.53
315800Z1-036_GEN1
Solar/Wind Harmer
2.172
3130156CHOWAN
Solar/Wind Harmer
-0.009
3145663CRESWEL
Solar/Wind Harmer
-0.024
971163AH1-040 GEN
Solar/Wind Harmer
8.075
970937AG2-583 GEN
Solar/Wind Harmer
6.109
316023GEN1_S
Solar/Wind Harmer
0.57
3146206CASHIE
Solar/Wind Harmer
-0.008
971547AH1-271 GEN
Solar/Wind Harmer
2.115
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.251
970919AG2-571 GEN
Solar/Wind Harmer
2.672
970087AG2-069 GEN
Solar/Wind Harmer
7.898
3146173TUNIS
Solar/Wind Harmer
-0.008
960081AF2-299 GEN
Solar/Wind Harmer
0.94
3145683EARLEYS
Solar/Wind Harmer
-0.008
957481AF2-042 GEN
Solar/Wind Harmer
26.028
3146263WOODLND
Solar/Wind Harmer
-0.008
3147043LAWRENC
Adder
0.664
3144293JTRSVLE
Adder
0.23
972277AH1-723 GEN
Adder
42.842
23779801AA1-109
Solar/Wind Helper
0.217
223401AF1-299 GEN
Solar/Wind Helper
0.397
966131AG1-482 GEN
Solar/Wind Helper
0.063
237080AD1-060 GEN
Solar/Wind Helper
0.221
235062AE1-101 C1
Solar/Wind Helper
1.064
237038AE2-054 C
Solar/Wind Helper
0.173
233930AB2-032 GEN
Solar/Wind Helper
0.23
233915AB1-141 GEN
Solar/Wind Helper
0.303
232422X3-066 FULL
Solar/Wind Helper
0.069
233964AF2-378 GEN
Solar/Wind Helper
0.025
232426Y1-080 FULL
Solar/Wind Helper
0.023
232428Y3-058 C
Solar/Wind Helper
0.203
233998TM1NIN_3.36
Solar/Wind Helper
0.157
233954AC2-188 GEN
Solar/Wind Helper
0.139
232404W1-003 C
Solar/Wind Helper
0.304
233950AC2-186 GEN
Solar/Wind Helper
0.07
232434Z2-077 GEN
Solar/Wind Helper
0.076
233972AC1-094 C
Solar/Wind Helper
0.181
205941AD2-115 GEN
Solar/Wind Helper
0.302
230434AG1-499 GEN
Solar/Wind Helper
0.136
230511AF1-262
Solar/Wind Helper
0.009
219258KINSLEYDEP C
Solar/Wind Helper
0.045
228728W1-130C
Solar/Wind Helper
0.032
219904AC1-010 C
Solar/Wind Helper
0.036
219907AC1-030 C
Solar/Wind Helper
0.02
218660EHAMPSOLAR C
Solar/Wind Helper
0.019
219686LUMSOLAR_N C
Solar/Wind Helper
0.023
219304NAMERICA C
Solar/Wind Helper
0.077
20720728JCB_W1-129
Solar/Wind Helper
0.033
207445AB1-138_GEN
Solar/Wind Helper
0.061
963711AG1-223 GEN
Solar/Wind Helper
0.037
20714828MDF_W3-079
Solar/Wind Helper
0.076
219680HOPEWELLV C1
Solar/Wind Helper
0.002
207454AA2-184 E
Solar/Wind Helper
0.18
20715228NPK_W1-113
Solar/Wind Helper
0.045
20742028HF_AC1-207
Solar/Wind Helper
0.082
207528AF2-192 GEN
Solar/Wind Helper
0.044
20673628F1S_V4-069
Solar/Wind Helper
0.017
20675428EAM_W2-061
Solar/Wind Helper
0.009
218428ETC SOLAR C
Solar/Wind Helper
0.003
20676428JCR_X2-075
Solar/Wind Helper
0.039
217213AMBOY SO C
Solar/Wind Helper
0.017
217209CENTRL HS C
Solar/Wind Helper
0.005
217208PARK ELE C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.013
207437AD2-070 GEN
Solar/Wind Helper
0.079
207439AE1-081 C O1
Solar/Wind Helper
0.011
207518AF1-320_GEN
Solar/Wind Helper
0.9
20671928W4-073
Solar/Wind Helper
0.051
20675828AU_W4-064
Solar/Wind Helper
0.017
961301AF2-421 GEN
Solar/Wind Helper
0.242
963151AG1-164 GEN
Solar/Wind Helper
0.242
212266LOR1
Solar/Wind Helper
0.026
961341AF2-425 GEN
Solar/Wind Helper
0.237
212507AE2-042_GEN
Solar/Wind Helper
0.829
946731AF1-337 GEN
Solar/Wind Helper
0.233
209071AE2-133 GEN
Solar/Wind Helper
0.042
315693AD1-088 GEN
Solar/Wind Harmer
1.373
NYPJM->LTFIMP_NY
CLTF
2.575
LGEELTFEXP_LGEE->PJM
CLTF
1.805
WECLTFEXP_WEC->PJM
CLTF
0.962
LAGNLTFEXP_LAGN->PJM
CLTF
6.323
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.563
TVALTFEXP_TVA->PJM
CLTF
3.187
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.478
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.59
MECLTFEXP_MEC->PJM
CLTF
4.448
SIGELTFEXP_SIGE->PJM
CLTF
0.14
CPLELTFEXP_CPLE->PJM
CLTF
5.064
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.958

Details for 6EDFERRY-DICKH230 230.0 kV Ckt 1 line l/o DVP_P4-2: 560T571_SRT-S


Base Case Flowgate

Area:DVP/PEPCO
Facility Description:
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 560T571_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:145.68 %
Rating:1417.0 MVA
Rating Type:B
MVA to Mitigate:2064.29
MW Contribution:42.6
Bus #Bus NameTypeMW Contribution
970053AG2-049 GEN
50/50
2.02
3138216PACIFIC
Solar/Wind Harmer
-0.003
316411AF1-147_GEN1
Solar/Wind Harmer
1.104
316415AF1-147_GEN2
Solar/Wind Harmer
1.104
3141426STAFORD
Solar/Wind Harmer
-0.002
3150411LDYSMT5
Adder
12.596
3150381LDYSMT2
Adder
12.055
972213AH1-691 GEN
Adder
2.039
972215AH1-692 GEN
Adder
2.039
316164AC1-076 GEN
Solar/Wind Harmer
0.886
944491AF1-114 GEN
Solar/Wind Harmer
3.014
316223AC1-118
Solar/Wind Harmer
0.269
972189AH1-679 GEN
Adder
1.455
3141813NORNECK
Solar/Wind Harmer
-0.01
962981AG1-147 GEN
Solar/Wind Harmer
4.183
3141783LANCAST
Solar/Wind Harmer
-0.006
3141783LANCAST
Solar/Wind Harmer
-0.004
3147346CASHSCORNER
Solar/Wind Harmer
0.147
3138133OCRAN
Solar/Wind Harmer
-0.003
3141913WHIT STONE
Solar/Wind Harmer
-0.009
316312AB1-027
Solar/Wind Harmer
0.319
316314AB2-024 C
Solar/Wind Harmer
0.807
316059AD1-063 C
Solar/Wind Harmer
0.213
957601AF2-054 GEN
Solar/Wind Harmer
0.282
3141873WAN 176
Solar/Wind Harmer
-0.002
315662AE1-191 GEN
Solar/Wind Harmer
1.137
315666AE1-190 GEN
Solar/Wind Harmer
0.284
3143873LANEXA
Solar/Wind Harmer
-0.006
3142433PROV 92
Adder
0.162
3142433PROV 92
Adder
0.162
971167AH1-042 GEN
Solar/Wind Harmer
9.035
315976AC1-164 GENA
Solar/Wind Harmer
9.907
316169AC1-164_GENC
Solar/Wind Harmer
8.558
315975AC1-164 GENB
Solar/Wind Harmer
0.293
316233AE1-074 FULL
Solar/Wind Harmer
0.251
971281AH1-106 GEN
Solar/Wind Harmer
1.517
971283AH1-107 GEN
Solar/Wind Harmer
1.517
971285AH1-108 GEN
Adder
0.626
957831AF2-077 GEN
Solar/Wind Harmer
0.28
3138283WHITEMARSH
Solar/Wind Harmer
0.014
316132AB2-190 GEN1
Solar/Wind Harmer
0.93
316369SG1_INVT
Solar/Wind Harmer
1.636
972265AH1-717 GEN
Adder
6.291
3151201GRAVEL4
Adder
5.897
3151191GRAVEL3
Adder
5.822
3151211GRAVEL5
Adder
5.822
971445AH1-216 GEN
Solar/Wind Harmer
5.611
3143316POE
Solar/Wind Harmer
-0.036
3151081ELIZAR1
Adder
7.342
3151091ELIZAR2
Adder
7.214
3152611GOSPORTB
Adder
1.02
3152621GOSPORTC
Adder
0.866
3152601GOSPORTA
Adder
0.798
315833AF1-017_GEN
Solar/Wind Harmer
1.7
316349AD2-085 GEN
Solar/Wind Harmer
0.796
316311AC2-079 GEN
Solar/Wind Harmer
4.513
957871AF2-081 GEN
Solar/Wind Harmer
4.471
319010AE1-072 C
Solar/Wind Harmer
1.806
316305AF2-043 C
Solar/Wind Harmer
0.269
3146406KITTY HAWK
Solar/Wind Harmer
0.007
315835AF2-110_GEN
Solar/Wind Harmer
1.113
313526AB2-022
Solar/Wind Harmer
0.239
3146486SUNBURY
Solar/Wind Harmer
-0.009
3146486SUNBURY
Solar/Wind Harmer
-0.009
316321Z2-027
Solar/Wind Harmer
0.239
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
3146396TANGLEW
Solar/Wind Harmer
0.163
316315AB2-025 C
Solar/Wind Harmer
0.237
315814AE2-033 C
Solar/Wind Harmer
8.149
941031AE2-094 GEN
Solar/Wind Harmer
16.374
944011AF1-069 GEN
Solar/Wind Harmer
5.131
315611Z1-036_GEN2
Solar/Wind Harmer
2.157
3130156CHOWAN
Solar/Wind Harmer
-0.009
3130156CHOWAN
Solar/Wind Harmer
-0.009
970673AG2-436 GEN
Solar/Wind Harmer
18.179
970673AG2-436 GEN
Solar/Wind Harmer
9.205
971967AH1-528 GEN
Solar/Wind Harmer
16.189
315816AE2-034 GEN
Solar/Wind Harmer
0.692
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315732AD1-074 GEN1
Solar/Wind Harmer
1.71
315733AD1-074 GEN2
Solar/Wind Harmer
1.71
315735AD1-075 GEN1
Solar/Wind Harmer
0.855
965291AG1-394 GEN
Solar/Wind Harmer
0.749
3146206CASHIE
Solar/Wind Harmer
-0.008
970601AG2-382 GEN
Solar/Wind Harmer
3.676
316318V4-068
Solar/Wind Harmer
0.209
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
5.232
970581AG2-369 GEN
Solar/Wind Harmer
4.499
3145513AHOSKIE
Solar/Wind Harmer
0.073
961941AG1-037 GEN
Solar/Wind Harmer
0.063
3145513AHOSKIE
Solar/Wind Harmer
-0.008
946281AF1-292 GEN
Solar/Wind Harmer
0.186
3146043SEABORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315607AA1-063A GEN
Solar/Wind Harmer
0.837
316087AB2-174 GEN
Solar/Wind Harmer
1.179
972205AH1-687 GEN
Adder
3.118
972193AH1-681 GEN
Adder
1.633
3151881LOWMORC
Adder
0.638
3151881LOWMORC
Adder
0.628
3151861LOWMORA
Adder
0.618
960921AF2-383 GEN
Solar/Wind Helper
0.139
205943AE1-185 GEN
Solar/Wind Helper
0.386
205956AE1-196_GEN
Solar/Wind Helper
0.384
205932AD2-116_GEN
Solar/Wind Helper
0.384
959381AF2-229 GEN
Solar/Wind Helper
0.256
237085AD2-009_GEN
Solar/Wind Helper
0.968
203975AE1-071-GEN
Solar/Wind Helper
1.709
233935AB2-179 C
Solar/Wind Helper
0.769
232436AB1-176 C
Solar/Wind Helper
0.027
233923SMA
Solar/Wind Helper
0.573
233990AG1-397 GEN
Solar/Wind Helper
0.018
232432Z2-076 GEN
Solar/Wind Helper
0.04
234033AF1-007_GEN
Solar/Wind Helper
4.196
964001AG1-254 GEN
Solar/Wind Helper
0.564
219914AD2-027 C
Solar/Wind Helper
0.068
227927V4-067C
Solar/Wind Helper
0.006
228754AB1-001 C
Solar/Wind Helper
0.015
219272CLEANLIGHT C
Solar/Wind Helper
0.015
219688LUMSOLAR_S C
Solar/Wind Helper
0.023
219607WPEMNERT C
Solar/Wind Helper
0.047
214067T20SOLAR
Solar/Wind Helper
0.007
20715728PEM_W1-119
Solar/Wind Helper
0.056
20715828PEM_W1-120
Solar/Wind Helper
0.056
207459AE1-142 C O1
Solar/Wind Helper
0.169
219620RIDERU C
Solar/Wind Helper
0.001
20675528CPH_W2-050
Solar/Wind Helper
0.05
218526CNTRALGAS2 C
Solar/Wind Helper
0.093
218524CNTRALGAS1 C
Solar/Wind Helper
0.092
966261AG1-495 GEN
Solar/Wind Helper
0.047
20675928HOL_W4-097
Solar/Wind Helper
0.029
207530AG1-191 GEN
Solar/Wind Helper
0.038
3152111X4-039 GT1
50/50
1.841
315747AE2-019 GEN
50/50
13.211
963691AG1-221 GEN
Solar/Wind Harmer
2.318
971455AH1-223 GEN
Solar/Wind Harmer
2.318
3141196NOKESVL
Solar/Wind Harmer
-0.048
3150151POSSMC1
Adder
1.063
3150151POSSMC1
Adder
1.063
3150231REMNGT3
Adder
13.478
3150241REMNGT4
Adder
12.566
972199AH1-684 GEN
Adder
1.905
972217AH1-693 GEN
Adder
1.657
3150301M RUN C
Adder
13.368
3150291M RUN B
Adder
13.268
3150331BIRCHWDA
Adder
16.45
3141316ARNOLDS
Adder
0.227
316044AC1-158 PL1
Solar/Wind Harmer
1.041
316450AC1-158 RIC
Solar/Wind Harmer
0.278
3150401LDYSMT4
Adder
12.557
3150371LDYSMT1
Adder
12.133
316170AC1-121 GEN2
Solar/Wind Harmer
0.283
966881AG1-559 GEN
Solar/Wind Harmer
0.306
970737AG2-469 GEN
Solar/Wind Harmer
5.052
3132273ORANGE
Solar/Wind Harmer
-0.002
3141906WESTMOR
Solar/Wind Harmer
-0.004
971781AH1-399 GEN
Solar/Wind Harmer
0.614
3147666LOUISA
Solar/Wind Harmer
-0.023
3150351NORNECKC2
Adder
0.877
3151761LOISA E
Adder
11.381
972183AH1-676 GEN
Adder
91.775
316404AE1-155 C
Solar/Wind Harmer
1.859
316484AD2-074 GEN
Solar/Wind Harmer
2.414
970009AG2-005 GEN
Solar/Wind Harmer
1.199
316473AC1-191 GEN
Solar/Wind Harmer
1.031
962971AG1-146 GEN
Solar/Wind Harmer
1.793
3142416OLDCHRC
Solar/Wind Harmer
0.953
3141766HARMONY
Solar/Wind Harmer
0.84
316156AD2-030 GEN
Solar/Wind Harmer
0.252
3141873WAN 176
Solar/Wind Harmer
1.12
316280AD1-041 GEN
Solar/Wind Harmer
0.711
316203AE2-005 GEN
Solar/Wind Harmer
3.975
3141843SHACKLE
Adder
0.429
970293AG2-193 GEN
Solar/Wind Harmer
1.175
3142433PROV 92
Adder
0.162
3142433PROV 92
Adder
0.162
3143096IRON208
Adder
0.349
3143096IRON208
Adder
0.342
3142946ENON
Solar/Wind Harmer
-0.003
3150861SPRUNCD
Adder
0.383
316382AG1-145 C
Solar/Wind Harmer
0.279
970133AG2-095 GEN
Solar/Wind Harmer
1.038
970129AG2-093 GEN
Solar/Wind Harmer
5.177
3150921YORKTN3
Adder
2.053
315778AD1-151 GEN
Solar/Wind Harmer
7.946
965281AG1-393 GEN
Solar/Wind Harmer
1.147
3144216WINCHST
Adder
0.308
315839AE2-212 C
Solar/Wind Harmer
0.276
961611AG1-000B GEN
Solar/Wind Harmer
1.921
3151221GRAVEL6
Adder
5.89
3151171GRAVELC
Adder
1.133
3145336SMITFLD
Solar/Wind Harmer
-0.004
315813AE1-149 C
Solar/Wind Harmer
5.666
315773AC2-141 GEN
Solar/Wind Harmer
3.785
970659AG2-427 GEN
Solar/Wind Harmer
0.85
316083AB2-161 GEN
Solar/Wind Harmer
1.464
3144536CHRHLND
Solar/Wind Harmer
-0.001
3151101ELIZAR3
Adder
7.435
970661AG2-428 GEN
Solar/Wind Harmer
1.695
3144873MCLAUGH
Solar/Wind Harmer
0
944581AF1-123 GEN
Solar/Wind Harmer
40.904
944601AF1-125 GEN
Solar/Wind Harmer
40.266
3146456SLIGO L269
Solar/Wind Harmer
-0.009
971153AH1-033 GEN
Solar/Wind Harmer
1.089
316320Y1-086
Solar/Wind Harmer
0.52
316313AB2-026
Solar/Wind Harmer
0.239
316258AE1-075 C
Solar/Wind Harmer
0.215
316405AF2-144 C
Solar/Wind Harmer
0.227
3143336POWHATN
Solar/Wind Harmer
0.895
316435W1029_GEN3
Solar/Wind Harmer
1.599
3146516WINFALL
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3145273HOLLAND
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.009
315614AA2-178 GEN
Solar/Wind Harmer
0.923
971157AH1-035 GEN
Solar/Wind Harmer
1.059
3156081AA2-088 GEN
Solar/Wind Harmer
2.747
315737AD1-076 GEN
Solar/Wind Harmer
1.607
316365GEN2_N
Solar/Wind Harmer
0.567
3146206CASHIE
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.059
3145893MURPHYS
Solar/Wind Harmer
-0.008
970917AG2-570 GEN
Solar/Wind Harmer
20.974
957521AF2-046 GEN
Solar/Wind Harmer
6.6
961681AG1-008 GEN
Solar/Wind Harmer
6.6
3146173TUNIS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1.123
316463AE2-346 GEN
Solar/Wind Harmer
0.135
316140AB2-099
Solar/Wind Harmer
0.056
962331AG1-082 GEN
Solar/Wind Harmer
1.04
966621AG1-532 GEN
Solar/Wind Harmer
0.168
3146263WOODLND
Solar/Wind Harmer
-0.008
313506AB2-031 GEN
Solar/Wind Harmer
0.663
3144293JTRSVLE
Adder
0.228
972255AH1-712 GEN
Adder
36.554
3151861LOWMORA
Adder
0.643
226910AB2-157 C
Solar/Wind Helper
0.02
227287AC2-120 GEN
Solar/Wind Helper
0.489
237030AB1-096 C
Solar/Wind Helper
0.083
223402AF1-300 C
Solar/Wind Helper
0.396
205917AD1-020 ES
Solar/Wind Helper
0.318
238221AF1-254 C O1
Solar/Wind Helper
0.179
235067AD1-061 GEN
Solar/Wind Helper
0.311
233982AB2-133 GEN
Solar/Wind Helper
0.215
233918AB1-142 GEN
Solar/Wind Helper
0.302
233994AC2-023 GEN
Solar/Wind Helper
0.575
233996TM1833_GEN
Solar/Wind Helper
0.156
233997TMININ_4.2
Solar/Wind Helper
0.156
233952AC2-187 GEN
Solar/Wind Helper
0.139
232406W1-004 FULL
Solar/Wind Helper
0.303
233940AF2-379 C
Solar/Wind Helper
0.037
234015AF2-250 C
Solar/Wind Helper
0.023
233971AC1-093 C
Solar/Wind Helper
0.213
230430AE1-229_GEN
Solar/Wind Helper
1.988
230415AB2-049 C
Solar/Wind Helper
0.018
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219766PARADISE C
Solar/Wind Helper
0.032
219912AD2-042 GEN
Solar/Wind Helper
0.088
228729W2-030 C
Solar/Wind Helper
0.065
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.007
219906AC1-017 C
Solar/Wind Helper
0.025
219348LDSOLAR C
Solar/Wind Helper
0.067
959561AF2-247 GEN
Solar/Wind Helper
0.012
20716028EGP_W2-019
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.037
20715028HAN_X4-015
Solar/Wind Helper
0.033
219276PARKLANDSO C
Solar/Wind Helper
0.052
20714528FRN_Y2-051
Solar/Wind Helper
0.033
20720528MAN_W1-024
Solar/Wind Helper
0.016
219612MATRIX C
Solar/Wind Helper
0.014
218438BLK ROCK C
Solar/Wind Helper
0.016
20673728F2S_V4-070
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.042
219919AE1-041 FULL
Solar/Wind Helper
0.002
219249CENTRALDIV C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
217169METRODIV C
Solar/Wind Helper
0.002
20676728BRNX1-095
Solar/Wind Helper
0.017
207510AF2-138 C
Solar/Wind Helper
0.046
20674628WNG_W3-110
Solar/Wind Helper
0.051
963161AG1-165 GEN
Solar/Wind Helper
0.241
963071AG1-156 GEN
Solar/Wind Helper
0.78
209027LOR2_Q27
Solar/Wind Helper
0.555
961331AF2-424 GEN
Solar/Wind Helper
0.236
961421AF2-433 GEN
Solar/Wind Helper
0.235
957921AF2-086 GEN
Solar/Wind Helper
0.233
946691AF1-333 GEN
Solar/Wind Helper
0.232
946741AF1-338 GEN
Solar/Wind Helper
0.232
209067AE2-060 GEN
Solar/Wind Helper
0.042
972289AH1-729 GEN
50/50
13.276
3150071POSSM 5
Adder
48.607
3150181POSSMC2
Adder
1.072
3150181POSSMC2
Adder
1.063
3150181POSSMC2
Adder
1.063
316447AC1-158 HLD
Solar/Wind Harmer
2.29
315651AD1-115 GEN
Solar/Wind Harmer
4.658
3150391LDYSMT3
Adder
12.533
972195AH1-682 GEN
Adder
1.647
315673AE1-157 GEN
Solar/Wind Harmer
7.721
957411AF2-035 GEN
Solar/Wind Harmer
4.574
970317AG2-208 GEN
Solar/Wind Harmer
4.447
316468AD1-105 GEN
Solar/Wind Harmer
1.109
966001AG1-469 GEN
Solar/Wind Harmer
0.184
316077AC2-138 C
Solar/Wind Harmer
0.205
3150341NORNECKC1
Adder
0.906
3150341NORNECKC1
Adder
0.898
3151731LOISA B
Adder
5.583
3151721LOISA A
Adder
5.554
958261AF2-120 GEN
Solar/Wind Harmer
3.734
316487AF1-042 GEN
Solar/Wind Harmer
1.263
966871AG1-558 GEN
Solar/Wind Harmer
0.288
966871AG1-558 GEN
Solar/Wind Harmer
0.099
3142296MT RD221
Adder
0.269
316441AF1-014 GEN
Solar/Wind Harmer
0.636
3142366NRTHEST
Adder
0.273
3150691DARBY 3
Adder
6.022
3150701DARBY 4
Adder
6.008
3150681DARBY 2
Adder
6.001
3150671DARBY 1
Adder
5.994
316075AC2-137 C
Solar/Wind Harmer
0.253
3143526WINTERP
Solar/Wind Harmer
-0.048
3142946ENON
Solar/Wind Harmer
-0.001
971223AH1-071 GEN
Solar/Wind Harmer
1.164
944641AF1-129 GEN
Adder
39.124
316240AF1-291 C
Solar/Wind Harmer
0.277
316033AB2-134 GEN
Solar/Wind Harmer
2.953
315697AD1-025 GEN
Solar/Wind Harmer
1.852
316236AE1-162_GEN
Solar/Wind Harmer
0.273
970657AG2-426 GEN
Solar/Wind Harmer
2.816
970657AG2-426 GEN
Solar/Wind Harmer
0.589
316036AC1-147 C
Solar/Wind Harmer
0.243
3150991CHESPKB
Adder
0.839
3150991CHESPKB
Adder
0.819
3142956BIRDNECK
Solar/Wind Harmer
0.482
316316AC1-027 C
Solar/Wind Harmer
0.276
316185AD1-033 GEN
Solar/Wind Harmer
0.947
3145506HICKORY
Solar/Wind Harmer
-0.036
3145506HICKORY
Solar/Wind Harmer
-0.021
3145506HICKORY
Solar/Wind Harmer
-0.005
316339AD2-160 GEN
Solar/Wind Harmer
0.603
316018AA1-139 ULT2
Solar/Wind Harmer
0.766
316017AA1-139 ULT1
Solar/Wind Harmer
0.724
3137176SLIGO L2192
Solar/Wind Harmer
-0.035
3146456SLIGO L269
Solar/Wind Harmer
1.055
3130086AYDLETT
Solar/Wind Harmer
-0.036
3146386ELIZ CT
Solar/Wind Harmer
-0.009
316431W1029_GEN1
Solar/Wind Harmer
1.599
316433W1029_GEN2
Solar/Wind Harmer
1.599
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3144356SAPONY
Solar/Wind Harmer
0.306
315742AE1-103 GEN
Solar/Wind Harmer
0.91
3146376EDENTON
Solar/Wind Harmer
0.257
3146376EDENTON
Solar/Wind Harmer
0.257
972185AH1-677 GEN
Adder
4.302
972187AH1-678 GEN
Adder
2.17
970933AG2-581 GEN
Solar/Wind Harmer
7.988
316065AD1-022 GEN
Solar/Wind Harmer
4.211
3145893MURPHYS
Solar/Wind Harmer
0.234
3145893MURPHYS
Solar/Wind Harmer
-0.015
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
970099AG2-077 GEN
Solar/Wind Harmer
10.347
316181AB2-040 GEN
Solar/Wind Harmer
1.151
3144293JTRSVLE
Adder
0.228
3144293JTRSVLE
Adder
0.192
226929AD2-058 GEN
Solar/Wind Helper
0.143
237025AB1-124 C
Solar/Wind Helper
0.193
237006AB1-125 GEN
Solar/Wind Helper
0.145
23777801MSM_W1-116
Solar/Wind Helper
0.13
237034AC2-136 C
Solar/Wind Helper
0.204
205916AD1-020 GEN
Solar/Wind Helper
1.477
208835TUHI V3-051
Solar/Wind Helper
0.019
208835TUHI V3-051
Solar/Wind Helper
0.019
237001AB1-127_GEN
Solar/Wind Helper
0.306
237002AB1-128_GEN
Solar/Wind Helper
0.297
235063AE1-101 C2
Solar/Wind Helper
1.061
20390526W1-045 C
Solar/Wind Helper
0.251
23777901MDS_W4-102
Solar/Wind Helper
0.105
235020AA1-095 C
Solar/Wind Helper
0.029
233933AB2-153 GEN
Solar/Wind Helper
0.14
233944AB2-135 GEN
Solar/Wind Helper
0.354
232424Y1-079 C
Solar/Wind Helper
0.07
233987AB2-037 GEN
Solar/Wind Helper
1.402
234036AF2-325 C
Solar/Wind Helper
0.025
233946AB2-136 GEN
Solar/Wind Helper
0.34
233901CHERRYDALE C
Solar/Wind Helper
0.139
232408W1-005 C
Solar/Wind Helper
0.303
232410W1-006 C
Solar/Wind Helper
0.303
233939AC1-091 C
Solar/Wind Helper
0.209
233970AC1-092 C
Solar/Wind Helper
0.209
230433AD2-135 GEN
Solar/Wind Helper
0.01
219921AF1-264
Solar/Wind Helper
0.03
230407AD2-065 C
Solar/Wind Helper
0.024
219615MILLCREEK C
Solar/Wind Helper
0.016
963401AG1-189 GEN
Solar/Wind Helper
0.033
963391AG1-188 GEN
Solar/Wind Helper
0.048
20714928UPF_X1-085
Solar/Wind Helper
0.003
20720628TIN_W1-124
Solar/Wind Helper
0.11
20716928W4-060COL
Solar/Wind Helper
0.03
20673828FLE_V3-070
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.009
207442AE1-156 GEN
Solar/Wind Helper
0.188
20676128MHD_W3-029
Solar/Wind Helper
0.055
20671828STAW2-080
Solar/Wind Helper
0.015
217081WEATEXAS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.004
217204WCALDSOLAR C
Solar/Wind Helper
0.002
207471AF2-354 C
Solar/Wind Helper
0.096
20674928WA_W3-044
Solar/Wind Helper
0.056
964851AG1-348 GEN
Solar/Wind Helper
0.046
20674128FR_U2-059
Solar/Wind Helper
0.002
20676228FRD_X1-012
Solar/Wind Helper
0.052
966111AG1-480 GEN
Solar/Wind Helper
0.025
211065PSPA IPP
Solar/Wind Helper
0.085
211065PSPA IPP
Solar/Wind Helper
0.085
208972BECR K09
Solar/Wind Helper
0.177
961431AF2-434 GEN
Solar/Wind Helper
0.235
209029WAYMART-WD
Solar/Wind Helper
0.441
209054AE2-059 GEN
Solar/Wind Helper
0.042
946751AF1-339 GEN
Solar/Wind Helper
0.232
209137AF2-361 C
Solar/Wind Helper
0.706
207484AF2-139 C O1
Solar/Wind Helper
0.048
20676328BVR_Y1-020
Solar/Wind Helper
0.015
20674828DL_W4-046
Solar/Wind Helper
0.004
207408W3-077 C
Solar/Wind Helper
0.048
20675728RH_W2-091
Solar/Wind Helper
0.078
20675128HRM_W1-127
Solar/Wind Helper
0.017
209116AE2-175 GEN
Solar/Wind Helper
1.001
961261AF2-417 GEN
Solar/Wind Helper
0.24
959431AF2-234 GEN
Solar/Wind Helper
0.464
964051AG1-259 GEN
Solar/Wind Helper
0.035
964061AG1-260 GEN
Solar/Wind Helper
0.035
959421AF2-233 GEN
Solar/Wind Helper
0.232
238208AF1-136 C
Solar/Wind Helper
0.089
3152131X4-039 ST
50/50
2.897
3152121X4-039 GT2
50/50
1.836
3140676OCCOQUN
Adder
0.27
972223AH1-696 GEN
Adder
8.401
3150151POSSMC1
Adder
1.063
3141346CRANES
Adder
0.118
3150221REMNGT2
Adder
12.484
3150211REMNGT1
Adder
12.401
972201AH1-685 GEN
Adder
2.154
3150281M RUN A
Adder
13.376
316006AB2-029 C
Solar/Wind Harmer
0.631
971685AH1-345 GEN
Solar/Wind Harmer
0.962
316045AC1-158 PL2
Solar/Wind Harmer
3.331
972197AH1-683 GEN
Adder
1.961
972219AH1-694 GEN
Adder
1.412
316254AC1-120 GEN1
Solar/Wind Harmer
0.848
957971AF2-091 GEN
Solar/Wind Harmer
1.025
315683AE1-153 C
Solar/Wind Harmer
9.493
972135AH1-637 GEN
Solar/Wind Harmer
1.018
966881AG1-559 GEN
Solar/Wind Harmer
0.105
3147666LOUISA
Solar/Wind Harmer
-0.04
316192AB2-158 GEN
Solar/Wind Harmer
1.181
316337AD2-073 GEN
Solar/Wind Harmer
0.265
3150351NORNECKC2
Adder
0.862
964211AG1-282 GEN
Solar/Wind Harmer
0.291
3141726DUNNSVL
Solar/Wind Harmer
-0.039
3151751LOISA D
Adder
5.583
962861AG1-135 GEN
Solar/Wind Harmer
3.609
961951AG1-038 GEN
Solar/Wind Harmer
1.263
3138133OCRAN
Solar/Wind Harmer
-0.006
3142416OLDCHRC
Solar/Wind Harmer
-0.024
3142416OLDCHRC
Solar/Wind Harmer
-0.009
3141766HARMONY
Solar/Wind Harmer
-0.002
971777AH1-397 GEN
Solar/Wind Harmer
1.109
3141843SHACKLE
Adder
0.429
3142433PROV 92
Solar/Wind Harmer
-0.037
3142433PROV 92
Adder
0.162
3142433PROV 92
Adder
0.162
3143096IRON208
Adder
0.349
3143526WINTERP
Solar/Wind Harmer
-0.048
3142543TWELFTH
Solar/Wind Harmer
-0.001
3150851SPRUNCC
Adder
0.383
944631AF1-128 GEN
Adder
39.551
3143226MDLTHAN
Solar/Wind Harmer
-0.009
316159AE1-175 C
Solar/Wind Harmer
0.248
971317AH1-138 GEN
Solar/Wind Harmer
1.154
970129AG2-093 GEN
Solar/Wind Harmer
2.097
316458AB2-190 GEN2
Solar/Wind Harmer
0.93
315671AE2-027_GEN
Solar/Wind Harmer
6.892
3138126ROCKLANDING
Solar/Wind Harmer
0.028
971069AG2-661 GEN
Solar/Wind Harmer
1.451
971647AH1-324 GEN
Solar/Wind Harmer
4.571
961611AG1-000B GEN
Solar/Wind Harmer
4.503
3151171GRAVELC
Adder
0.862
3145336SMITFLD
Solar/Wind Harmer
-0.036
316294AC1-161 GEN
Solar/Wind Harmer
2.927
970659AG2-427 GEN
Solar/Wind Harmer
4.796
316381AD1-082 GEN
Solar/Wind Harmer
0.827
316375AC2-012 GEN
Solar/Wind Harmer
3.114
3150981CHESPKA
Adder
1
970661AG2-428 GEN
Solar/Wind Harmer
9.562
944591AF1-124 GEN
Solar/Wind Harmer
41.052
316072AD1-144
Solar/Wind Harmer
0.182
316388AE2-253 GEN
Solar/Wind Harmer
0.603
939411AE1-173 GEN
Solar/Wind Harmer
44.674
3146456SLIGO L269
Solar/Wind Harmer
-0.009
316246AF1-032 C
Solar/Wind Harmer
0.181
940641AE2-051 GEN
Solar/Wind Harmer
8.364
316093AE2-104_GEN
Solar/Wind Harmer
2.589
3143336POWHATN
Solar/Wind Harmer
1.052
3146516WINFALL
Solar/Wind Harmer
-0.028
3146516WINFALL
Solar/Wind Harmer
-0.009
316336AC2-165 C
Solar/Wind Harmer
1.521
315800Z1-036_GEN1
Solar/Wind Harmer
2.157
3130156CHOWAN
Solar/Wind Harmer
-0.009
3145663CRESWEL
Solar/Wind Harmer
-0.024
971163AH1-040 GEN
Solar/Wind Harmer
8.02
970937AG2-583 GEN
Solar/Wind Harmer
6.075
316023GEN1_S
Solar/Wind Harmer
0.567
3146206CASHIE
Solar/Wind Harmer
-0.008
971547AH1-271 GEN
Solar/Wind Harmer
2.101
3145893MURPHYS
Solar/Wind Harmer
-0.033
3145893MURPHYS
Solar/Wind Harmer
0.249
970919AG2-571 GEN
Solar/Wind Harmer
2.655
970087AG2-069 GEN
Solar/Wind Harmer
7.848
3146173TUNIS
Solar/Wind Harmer
-0.008
960081AF2-299 GEN
Solar/Wind Harmer
0.934
3145683EARLEYS
Solar/Wind Harmer
-0.008
957481AF2-042 GEN
Solar/Wind Harmer
25.866
3146263WOODLND
Solar/Wind Harmer
-0.008
3147043LAWRENC
Adder
0.66
3144293JTRSVLE
Adder
0.228
972277AH1-723 GEN
Adder
42.597
23779801AA1-109
Solar/Wind Helper
0.217
223401AF1-299 GEN
Solar/Wind Helper
0.396
966131AG1-482 GEN
Solar/Wind Helper
0.063
237080AD1-060 GEN
Solar/Wind Helper
0.22
235062AE1-101 C1
Solar/Wind Helper
1.061
237038AE2-054 C
Solar/Wind Helper
0.173
233930AB2-032 GEN
Solar/Wind Helper
0.229
233915AB1-141 GEN
Solar/Wind Helper
0.302
232422X3-066 FULL
Solar/Wind Helper
0.069
233964AF2-378 GEN
Solar/Wind Helper
0.025
232426Y1-080 FULL
Solar/Wind Helper
0.023
232428Y3-058 C
Solar/Wind Helper
0.202
233998TM1NIN_3.36
Solar/Wind Helper
0.156
233954AC2-188 GEN
Solar/Wind Helper
0.139
232404W1-003 C
Solar/Wind Helper
0.303
233950AC2-186 GEN
Solar/Wind Helper
0.069
232434Z2-077 GEN
Solar/Wind Helper
0.076
233972AC1-094 C
Solar/Wind Helper
0.18
205941AD2-115 GEN
Solar/Wind Helper
0.301
230434AG1-499 GEN
Solar/Wind Helper
0.136
230511AF1-262
Solar/Wind Helper
0.009
219258KINSLEYDEP C
Solar/Wind Helper
0.045
228728W1-130C
Solar/Wind Helper
0.032
219904AC1-010 C
Solar/Wind Helper
0.036
219907AC1-030 C
Solar/Wind Helper
0.02
218660EHAMPSOLAR C
Solar/Wind Helper
0.019
219686LUMSOLAR_N C
Solar/Wind Helper
0.023
219304NAMERICA C
Solar/Wind Helper
0.077
20720728JCB_W1-129
Solar/Wind Helper
0.033
207445AB1-138_GEN
Solar/Wind Helper
0.061
963711AG1-223 GEN
Solar/Wind Helper
0.037
20714828MDF_W3-079
Solar/Wind Helper
0.076
219680HOPEWELLV C1
Solar/Wind Helper
0.002
207454AA2-184 E
Solar/Wind Helper
0.18
20715228NPK_W1-113
Solar/Wind Helper
0.045
20742028HF_AC1-207
Solar/Wind Helper
0.081
207528AF2-192 GEN
Solar/Wind Helper
0.044
20673628F1S_V4-069
Solar/Wind Helper
0.017
20675428EAM_W2-061
Solar/Wind Helper
0.009
218428ETC SOLAR C
Solar/Wind Helper
0.003
20676428JCR_X2-075
Solar/Wind Helper
0.039
217213AMBOY SO C
Solar/Wind Helper
0.016
217209CENTRL HS C
Solar/Wind Helper
0.005
217208PARK ELE C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.013
207437AD2-070 GEN
Solar/Wind Helper
0.079
207439AE1-081 C O1
Solar/Wind Helper
0.011
207518AF1-320_GEN
Solar/Wind Helper
0.897
20671928W4-073
Solar/Wind Helper
0.051
20675828AU_W4-064
Solar/Wind Helper
0.017
961301AF2-421 GEN
Solar/Wind Helper
0.241
963151AG1-164 GEN
Solar/Wind Helper
0.241
212266LOR1
Solar/Wind Helper
0.026
961341AF2-425 GEN
Solar/Wind Helper
0.236
212507AE2-042_GEN
Solar/Wind Helper
0.826
946731AF1-337 GEN
Solar/Wind Helper
0.232
209071AE2-133 GEN
Solar/Wind Helper
0.042
315693AD1-088 GEN
Solar/Wind Harmer
1.364
NYPJM->LTFIMP_NY
CLTF
2.566
LGEELTFEXP_LGEE->PJM
CLTF
1.801
WECLTFEXP_WEC->PJM
CLTF
0.96
LAGNLTFEXP_LAGN->PJM
CLTF
6.303
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.503
TVALTFEXP_TVA->PJM
CLTF
3.177
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.419
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.556
MECLTFEXP_MEC->PJM
CLTF
4.438
SIGELTFEXP_SIGE->PJM
CLTF
0.139
CPLELTFEXP_CPLE->PJM
CLTF
5.037
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.853

Details for 6EDFERRY-DICKH230 230.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019F_SRT-SL


Base Case Flowgate

Area:DVP/PEPCO
Facility Description:
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019F_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:140.29 %
Rating:1417.0 MVA
Rating Type:B
MVA to Mitigate:1987.89
MW Contribution:35.15
Bus #Bus NameTypeMW Contribution
3138216PACIFIC
Solar/Wind Harmer
-0.003
316411AF1-147_GEN1
Solar/Wind Harmer
1.076
316415AF1-147_GEN2
Solar/Wind Harmer
1.076
970053AG2-049 GEN
Adder
1.475
316164AC1-076 GEN
Solar/Wind Harmer
0.73
3147346CASHSCORNER
Solar/Wind Harmer
0.123
3141426STAFORD
Solar/Wind Harmer
-0.002
3150411LDYSMT5
Adder
9.22
3150381LDYSMT2
Adder
8.824
972213AH1-691 GEN
Adder
1.493
972215AH1-692 GEN
Adder
1.493
944491AF1-114 GEN
Solar/Wind Harmer
2.206
316223AC1-118
Solar/Wind Harmer
0.2
972189AH1-679 GEN
Adder
1.104
3141813NORNECK
Solar/Wind Harmer
-0.007
962981AG1-147 GEN
Solar/Wind Harmer
3.188
316233AE1-074 FULL
Solar/Wind Harmer
0.196
971281AH1-106 GEN
Solar/Wind Harmer
1.184
971283AH1-107 GEN
Solar/Wind Harmer
1.184
316312AB1-027
Solar/Wind Harmer
0.245
3141783LANCAST
Solar/Wind Harmer
-0.004
3141783LANCAST
Solar/Wind Harmer
-0.003
3138133OCRAN
Solar/Wind Harmer
-0.002
3141913WHIT STONE
Solar/Wind Harmer
-0.007
971285AH1-108 GEN
Adder
0.486
316314AB2-024 C
Solar/Wind Harmer
0.62
316059AD1-063 C
Solar/Wind Harmer
0.164
3143873LANEXA
Solar/Wind Harmer
-0.004
315662AE1-191 GEN
Solar/Wind Harmer
0.873
315666AE1-190 GEN
Solar/Wind Harmer
0.218
957601AF2-054 GEN
Solar/Wind Harmer
0.217
3141873WAN 176
Solar/Wind Harmer
-0.001
315976AC1-164 GENA
Solar/Wind Harmer
7.645
316169AC1-164_GENC
Solar/Wind Harmer
6.604
315975AC1-164 GENB
Solar/Wind Harmer
0.226
3142433PROV 92
Adder
0.125
3142433PROV 92
Adder
0.125
971167AH1-042 GEN
Solar/Wind Harmer
6.965
957831AF2-077 GEN
Solar/Wind Harmer
0.216
3138283WHITEMARSH
Solar/Wind Harmer
0.011
316132AB2-190 GEN1
Solar/Wind Harmer
0.724
316369SG1_INVT
Solar/Wind Harmer
1.275
972265AH1-717 GEN
Adder
4.91
3151201GRAVEL4
Adder
4.603
3151191GRAVEL3
Adder
4.545
3151211GRAVEL5
Adder
4.545
3143316POE
Solar/Wind Harmer
-0.028
971445AH1-216 GEN
Solar/Wind Harmer
4.385
3151081ELIZAR1
Adder
5.753
3151091ELIZAR2
Adder
5.653
3152611GOSPORTB
Adder
0.799
3152621GOSPORTC
Adder
0.678
3152601GOSPORTA
Adder
0.626
315833AF1-017_GEN
Solar/Wind Harmer
1.334
316349AD2-085 GEN
Solar/Wind Harmer
0.624
316311AC2-079 GEN
Solar/Wind Harmer
3.541
957871AF2-081 GEN
Solar/Wind Harmer
3.509
319010AE1-072 C
Solar/Wind Harmer
1.418
316305AF2-043 C
Solar/Wind Harmer
0.211
3146406KITTY HAWK
Solar/Wind Harmer
0.006
315835AF2-110_GEN
Solar/Wind Harmer
0.874
313526AB2-022
Solar/Wind Harmer
0.188
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.188
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.128
316315AB2-025 C
Solar/Wind Harmer
0.187
941031AE2-094 GEN
Solar/Wind Harmer
12.98
944011AF1-069 GEN
Solar/Wind Harmer
4.067
315814AE2-033 C
Solar/Wind Harmer
6.44
315611Z1-036_GEN2
Solar/Wind Harmer
1.702
970673AG2-436 GEN
Solar/Wind Harmer
14.439
970673AG2-436 GEN
Solar/Wind Harmer
7.311
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
971967AH1-528 GEN
Solar/Wind Harmer
12.878
315816AE2-034 GEN
Solar/Wind Harmer
0.549
972205AH1-687 GEN
Adder
2.574
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315732AD1-074 GEN1
Solar/Wind Harmer
1.359
315733AD1-074 GEN2
Solar/Wind Harmer
1.359
315735AD1-075 GEN1
Solar/Wind Harmer
0.68
971845AH1-439 GEN
Solar/Wind Harmer
3.571
965291AG1-394 GEN
Solar/Wind Harmer
0.596
970285AG2-188 GEN
Solar/Wind Harmer
5.876
3138266HYDRAULIC
Solar/Wind Harmer
0
3138266HYDRAULIC
Solar/Wind Harmer
0
970085AG2-068 GEN
Solar/Wind Harmer
4.185
970581AG2-369 GEN
Solar/Wind Harmer
3.599
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.928
316318V4-068
Solar/Wind Harmer
0.167
3145893MURPHYS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
-0.007
972193AH1-681 GEN
Adder
1.348
960921AF2-383 GEN
Solar/Wind Helper
0.147
959381AF2-229 GEN
Solar/Wind Helper
0.283
205943AE1-185 GEN
Solar/Wind Helper
0.409
205956AE1-196_GEN
Solar/Wind Helper
0.406
205932AD2-116_GEN
Solar/Wind Helper
0.406
237085AD2-009_GEN
Solar/Wind Helper
1.049
203975AE1-071-GEN
Solar/Wind Helper
1.871
233935AB2-179 C
Solar/Wind Helper
0.773
232436AB1-176 C
Solar/Wind Helper
0.027
233923SMA
Solar/Wind Helper
0.576
233990AG1-397 GEN
Solar/Wind Helper
0.018
232432Z2-076 GEN
Solar/Wind Helper
0.04
234033AF1-007_GEN
Solar/Wind Helper
4.217
964001AG1-254 GEN
Solar/Wind Helper
0.565
219914AD2-027 C
Solar/Wind Helper
0.068
228754AB1-001 C
Solar/Wind Helper
0.015
227927V4-067C
Solar/Wind Helper
0.006
219272CLEANLIGHT C
Solar/Wind Helper
0.015
219688LUMSOLAR_S C
Solar/Wind Helper
0.023
219607WPEMNERT C
Solar/Wind Helper
0.047
214067T20SOLAR
Solar/Wind Helper
0.007
20715728PEM_W1-119
Solar/Wind Helper
0.056
20715828PEM_W1-120
Solar/Wind Helper
0.056
207459AE1-142 C O1
Solar/Wind Helper
0.169
219620RIDERU C
Solar/Wind Helper
0.001
20675528CPH_W2-050
Solar/Wind Helper
0.05
218526CNTRALGAS2 C
Solar/Wind Helper
0.092
218524CNTRALGAS1 C
Solar/Wind Helper
0.092
966261AG1-495 GEN
Solar/Wind Helper
0.047
20675928HOL_W4-097
Solar/Wind Helper
0.028
207530AG1-191 GEN
Solar/Wind Helper
0.037
207484AF2-139 C O1
Solar/Wind Helper
0.048
20676328BVR_Y1-020
Solar/Wind Helper
0.015
20674828DL_W4-046
Solar/Wind Helper
0.004
207408W3-077 C
Solar/Wind Helper
0.048
20675728RH_W2-091
Solar/Wind Helper
0.078
20675128HRM_W1-127
Solar/Wind Helper
0.017
209116AE2-175 GEN
Solar/Wind Helper
0.994
961261AF2-417 GEN
Solar/Wind Helper
0.238
959431AF2-234 GEN
Solar/Wind Helper
0.459
964051AG1-259 GEN
Solar/Wind Helper
0.034
964061AG1-260 GEN
Solar/Wind Helper
0.034
959421AF2-233 GEN
Solar/Wind Helper
0.229
238208AF1-136 C
Solar/Wind Helper
0.089
3152111X4-039 GT1
50/50
1.829
315747AE2-019 GEN
50/50
12.54
963691AG1-221 GEN
Solar/Wind Harmer
2.26
971455AH1-223 GEN
Solar/Wind Harmer
2.26
3141196NOKESVL
Solar/Wind Harmer
-0.043
3150231REMNGT3
Adder
11.81
3150241REMNGT4
Adder
11.012
972199AH1-684 GEN
Adder
1.67
972217AH1-693 GEN
Adder
1.452
3150301M RUN C
Adder
11.698
3150291M RUN B
Adder
11.611
316170AC1-121 GEN2
Solar/Wind Harmer
0.237
316044AC1-158 PL1
Solar/Wind Harmer
0.855
316450AC1-158 RIC
Solar/Wind Harmer
0.228
3132273ORANGE
Solar/Wind Harmer
-0.002
3147666LOUISA
Solar/Wind Harmer
-0.018
3151761LOISA E
Adder
9.484
972183AH1-676 GEN
Adder
76.571
3150151POSSMC1
Adder
0.713
3150151POSSMC1
Adder
0.713
3150331BIRCHWDA
Adder
11.674
3150401LDYSMT4
Adder
9.192
3150371LDYSMT1
Adder
8.882
3141316ARNOLDS
Adder
0.162
966881AG1-559 GEN
Solar/Wind Harmer
0.227
970737AG2-469 GEN
Solar/Wind Harmer
3.736
971781AH1-399 GEN
Solar/Wind Harmer
0.459
3141906WESTMOR
Solar/Wind Harmer
-0.003
3150351NORNECKC2
Adder
0.662
316473AC1-191 GEN
Solar/Wind Harmer
0.788
316404AE1-155 C
Solar/Wind Harmer
1.411
316484AD2-074 GEN
Solar/Wind Harmer
1.837
970009AG2-005 GEN
Solar/Wind Harmer
0.912
962971AG1-146 GEN
Solar/Wind Harmer
1.366
3142416OLDCHRC
Solar/Wind Harmer
0.734
970293AG2-193 GEN
Solar/Wind Harmer
0.907
3150861SPRUNCD
Adder
0.297
3141766HARMONY
Solar/Wind Harmer
0.645
316203AE2-005 GEN
Solar/Wind Harmer
3.054
316280AD1-041 GEN
Solar/Wind Harmer
0.546
316156AD2-030 GEN
Solar/Wind Harmer
0.193
3141873WAN 176
Solar/Wind Harmer
0.86
3141843SHACKLE
Adder
0.329
3143096IRON208
Adder
0.27
3143096IRON208
Adder
0.265
3142433PROV 92
Adder
0.125
3142433PROV 92
Adder
0.125
3142946ENON
Solar/Wind Harmer
-0.002
316382AG1-145 C
Solar/Wind Harmer
0.216
970133AG2-095 GEN
Solar/Wind Harmer
0.807
970129AG2-093 GEN
Solar/Wind Harmer
4.029
965281AG1-393 GEN
Solar/Wind Harmer
0.893
315778AD1-151 GEN
Solar/Wind Harmer
6.188
3150921YORKTN3
Adder
1.597
315839AE2-212 C
Solar/Wind Harmer
0.215
3144216WINCHST
Adder
0.239
961611AG1-000B GEN
Solar/Wind Harmer
1.499
3151221GRAVEL6
Adder
4.598
3151171GRAVELC
Adder
0.885
315813AE1-149 C
Solar/Wind Harmer
4.431
316313AB2-026
Solar/Wind Harmer
0.191
316258AE1-075 C
Solar/Wind Harmer
0.172
316405AF2-144 C
Solar/Wind Harmer
0.182
3143336POWHATN
Solar/Wind Harmer
0.715
3145336SMITFLD
Solar/Wind Harmer
-0.003
315773AC2-141 GEN
Solar/Wind Harmer
2.964
970659AG2-427 GEN
Solar/Wind Harmer
0.665
316083AB2-161 GEN
Solar/Wind Harmer
1.146
3144536CHRHLND
Solar/Wind Harmer
-0.001
3151101ELIZAR3
Adder
5.827
3144873MCLAUGH
Solar/Wind Harmer
0
944581AF1-123 GEN
Solar/Wind Harmer
32.067
944601AF1-125 GEN
Solar/Wind Harmer
31.566
970661AG2-428 GEN
Solar/Wind Harmer
1.328
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.855
316320Y1-086
Solar/Wind Harmer
0.409
316435W1029_GEN3
Solar/Wind Harmer
1.259
3146516WINFALL
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3145273HOLLAND
Solar/Wind Harmer
-0.005
3146376EDENTON
Solar/Wind Harmer
-0.007
315614AA2-178 GEN
Solar/Wind Harmer
0.732
3156081AA2-088 GEN
Solar/Wind Harmer
2.185
971157AH1-035 GEN
Solar/Wind Harmer
0.841
3146776BUCKING
Solar/Wind Harmer
-0.002
315737AD1-076 GEN
Solar/Wind Harmer
1.278
970917AG2-570 GEN
Solar/Wind Harmer
16.768
316365GEN2_N
Solar/Wind Harmer
0.452
3146206CASHIE
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
0.047
3145893MURPHYS
Solar/Wind Harmer
-0.007
3146926FARMVIL
Solar/Wind Harmer
-0.004
957521AF2-046 GEN
Solar/Wind Harmer
5.262
961681AG1-008 GEN
Solar/Wind Harmer
5.262
970909AG2-566 GEN
Solar/Wind Harmer
0.633
3146173TUNIS
Solar/Wind Harmer
-0.007
972255AH1-712 GEN
Adder
30.164
3144293JTRSVLE
Adder
0.186
237030AB1-096 C
Solar/Wind Helper
0.1
223402AF1-300 C
Solar/Wind Helper
0.385
226910AB2-157 C
Solar/Wind Helper
0.014
205917AD1-020 ES
Solar/Wind Helper
0.357
227287AC2-120 GEN
Solar/Wind Helper
0.309
238221AF1-254 C O1
Solar/Wind Helper
0.197
235067AD1-061 GEN
Solar/Wind Helper
0.341
233982AB2-133 GEN
Solar/Wind Helper
0.216
233918AB1-142 GEN
Solar/Wind Helper
0.304
233994AC2-023 GEN
Solar/Wind Helper
0.578
233996TM1833_GEN
Solar/Wind Helper
0.157
233997TMININ_4.2
Solar/Wind Helper
0.157
233940AF2-379 C
Solar/Wind Helper
0.037
234015AF2-250 C
Solar/Wind Helper
0.023
233952AC2-187 GEN
Solar/Wind Helper
0.14
232406W1-004 FULL
Solar/Wind Helper
0.305
233971AC1-093 C
Solar/Wind Helper
0.214
230430AE1-229_GEN
Solar/Wind Helper
1.992
230415AB2-049 C
Solar/Wind Helper
0.018
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219766PARADISE C
Solar/Wind Helper
0.032
219912AD2-042 GEN
Solar/Wind Helper
0.088
228729W2-030 C
Solar/Wind Helper
0.065
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.007
219906AC1-017 C
Solar/Wind Helper
0.025
219348LDSOLAR C
Solar/Wind Helper
0.067
959561AF2-247 GEN
Solar/Wind Helper
0.012
20716028EGP_W2-019
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.037
20715028HAN_X4-015
Solar/Wind Helper
0.033
219276PARKLANDSO C
Solar/Wind Helper
0.052
20714528FRN_Y2-051
Solar/Wind Helper
0.033
20720528MAN_W1-024
Solar/Wind Helper
0.016
219612MATRIX C
Solar/Wind Helper
0.014
218438BLK ROCK C
Solar/Wind Helper
0.016
20673728F2S_V4-070
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.042
219919AE1-041 FULL
Solar/Wind Helper
0.002
219249CENTRALDIV C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
217169METRODIV C
Solar/Wind Helper
0.002
20676728BRNX1-095
Solar/Wind Helper
0.017
207510AF2-138 C
Solar/Wind Helper
0.046
20674628WNG_W3-110
Solar/Wind Helper
0.051
963161AG1-165 GEN
Solar/Wind Helper
0.239
963071AG1-156 GEN
Solar/Wind Helper
0.773
209027LOR2_Q27
Solar/Wind Helper
0.55
961331AF2-424 GEN
Solar/Wind Helper
0.233
961421AF2-433 GEN
Solar/Wind Helper
0.233
957921AF2-086 GEN
Solar/Wind Helper
0.23
209067AE2-060 GEN
Solar/Wind Helper
0.042
946691AF1-333 GEN
Solar/Wind Helper
0.23
946741AF1-338 GEN
Solar/Wind Helper
0.23
972289AH1-729 GEN
50/50
13.169
315651AD1-115 GEN
Solar/Wind Harmer
3.939
316447AC1-158 HLD
Solar/Wind Harmer
1.879
966001AG1-469 GEN
Solar/Wind Harmer
0.153
3151731LOISA B
Adder
4.652
3151721LOISA A
Adder
4.628
3150071POSSM 5
Adder
32.578
3150181POSSMC2
Adder
0.719
3150181POSSMC2
Adder
0.713
3150181POSSMC2
Adder
0.713
3150391LDYSMT3
Adder
9.175
972195AH1-682 GEN
Adder
1.206
315673AE1-157 GEN
Solar/Wind Harmer
5.71
957411AF2-035 GEN
Solar/Wind Harmer
3.403
970317AG2-208 GEN
Solar/Wind Harmer
3.309
316468AD1-105 GEN
Solar/Wind Harmer
0.83
316077AC2-138 C
Solar/Wind Harmer
0.155
3150341NORNECKC1
Adder
0.684
3150341NORNECKC1
Adder
0.679
966871AG1-558 GEN
Solar/Wind Harmer
0.22
966871AG1-558 GEN
Solar/Wind Harmer
0.075
958261AF2-120 GEN
Solar/Wind Harmer
2.834
3142296MT RD221
Adder
0.207
316487AF1-042 GEN
Solar/Wind Harmer
0.961
971223AH1-071 GEN
Solar/Wind Harmer
0.912
3143526WINTERP
Solar/Wind Harmer
-0.038
3142366NRTHEST
Adder
0.211
3150691DARBY 3
Adder
4.65
3150701DARBY 4
Adder
4.64
3150681DARBY 2
Adder
4.634
3150671DARBY 1
Adder
4.629
316075AC2-137 C
Solar/Wind Harmer
0.196
316441AF1-014 GEN
Solar/Wind Harmer
0.488
3142946ENON
Solar/Wind Harmer
-0.001
944641AF1-129 GEN
Adder
30.436
316240AF1-291 C
Solar/Wind Harmer
0.216
316033AB2-134 GEN
Solar/Wind Harmer
2.301
315697AD1-025 GEN
Solar/Wind Harmer
1.443
316236AE1-162_GEN
Solar/Wind Harmer
0.214
970657AG2-426 GEN
Solar/Wind Harmer
2.206
970657AG2-426 GEN
Solar/Wind Harmer
0.461
316036AC1-147 C
Solar/Wind Harmer
0.19
3150991CHESPKB
Adder
0.657
3150991CHESPKB
Adder
0.642
3142956BIRDNECK
Solar/Wind Harmer
0.378
316316AC1-027 C
Solar/Wind Harmer
0.216
316185AD1-033 GEN
Solar/Wind Harmer
0.743
3145506HICKORY
Solar/Wind Harmer
-0.028
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
316339AD2-160 GEN
Solar/Wind Harmer
0.474
316018AA1-139 ULT2
Solar/Wind Harmer
0.601
316017AA1-139 ULT1
Solar/Wind Harmer
0.568
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.828
3130086AYDLETT
Solar/Wind Harmer
-0.028
3146386ELIZ CT
Solar/Wind Harmer
-0.007
971761AH1-387 GEN
Solar/Wind Harmer
3.885
316431W1029_GEN1
Solar/Wind Harmer
1.259
316433W1029_GEN2
Solar/Wind Harmer
1.259
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3144356SAPONY
Solar/Wind Harmer
0.242
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
315742AE1-103 GEN
Solar/Wind Harmer
0.719
3146376EDENTON
Solar/Wind Harmer
0.203
3146376EDENTON
Solar/Wind Harmer
0.203
972185AH1-677 GEN
Adder
3.421
972187AH1-678 GEN
Adder
1.728
970933AG2-581 GEN
Solar/Wind Harmer
6.373
3146776BUCKING
Solar/Wind Harmer
-0.027
3146776BUCKING
Solar/Wind Harmer
-0.002
316065AD1-022 GEN
Solar/Wind Harmer
3.351
3145893MURPHYS
Solar/Wind Harmer
0.187
3145893MURPHYS
Solar/Wind Harmer
-0.012
970301AG2-198 GEN
Solar/Wind Harmer
3.335
971741AH1-377 GEN
Solar/Wind Harmer
7.747
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
3144293JTRSVLE
Adder
0.186
3144293JTRSVLE
Adder
0.157
237025AB1-124 C
Solar/Wind Helper
0.233
237006AB1-125 GEN
Solar/Wind Helper
0.175
23777801MSM_W1-116
Solar/Wind Helper
0.156
237034AC2-136 C
Solar/Wind Helper
0.239
205916AD1-020 GEN
Solar/Wind Helper
1.658
237001AB1-127_GEN
Solar/Wind Helper
0.342
237002AB1-128_GEN
Solar/Wind Helper
0.33
226929AD2-058 GEN
Solar/Wind Helper
0.078
208835TUHI V3-051
Solar/Wind Helper
0.02
208835TUHI V3-051
Solar/Wind Helper
0.02
235063AE1-101 C2
Solar/Wind Helper
1.169
20390526W1-045 C
Solar/Wind Helper
0.277
23777901MDS_W4-102
Solar/Wind Helper
0.113
235020AA1-095 C
Solar/Wind Helper
0.03
233933AB2-153 GEN
Solar/Wind Helper
0.141
233944AB2-135 GEN
Solar/Wind Helper
0.356
232424Y1-079 C
Solar/Wind Helper
0.07
233987AB2-037 GEN
Solar/Wind Helper
1.409
233946AB2-136 GEN
Solar/Wind Helper
0.342
234036AF2-325 C
Solar/Wind Helper
0.025
233901CHERRYDALE C
Solar/Wind Helper
0.14
232408W1-005 C
Solar/Wind Helper
0.305
232410W1-006 C
Solar/Wind Helper
0.305
233939AC1-091 C
Solar/Wind Helper
0.21
233970AC1-092 C
Solar/Wind Helper
0.21
230433AD2-135 GEN
Solar/Wind Helper
0.01
230407AD2-065 C
Solar/Wind Helper
0.024
219921AF1-264
Solar/Wind Helper
0.03
219615MILLCREEK C
Solar/Wind Helper
0.016
963401AG1-189 GEN
Solar/Wind Helper
0.033
963391AG1-188 GEN
Solar/Wind Helper
0.048
20714928UPF_X1-085
Solar/Wind Helper
0.003
20720628TIN_W1-124
Solar/Wind Helper
0.11
20716928W4-060COL
Solar/Wind Helper
0.03
20673828FLE_V3-070
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.009
207442AE1-156 GEN
Solar/Wind Helper
0.187
20676128MHD_W3-029
Solar/Wind Helper
0.055
20671828STAW2-080
Solar/Wind Helper
0.015
217081WEATEXAS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.004
217204WCALDSOLAR C
Solar/Wind Helper
0.002
207471AF2-354 C
Solar/Wind Helper
0.096
20674928WA_W3-044
Solar/Wind Helper
0.056
964851AG1-348 GEN
Solar/Wind Helper
0.046
20674128FR_U2-059
Solar/Wind Helper
0.002
20676228FRD_X1-012
Solar/Wind Helper
0.052
966111AG1-480 GEN
Solar/Wind Helper
0.025
211065PSPA IPP
Solar/Wind Helper
0.084
211065PSPA IPP
Solar/Wind Helper
0.084
208972BECR K09
Solar/Wind Helper
0.176
961431AF2-434 GEN
Solar/Wind Helper
0.233
209029WAYMART-WD
Solar/Wind Helper
0.437
209137AF2-361 C
Solar/Wind Helper
0.703
209054AE2-059 GEN
Solar/Wind Helper
0.042
946751AF1-339 GEN
Solar/Wind Helper
0.23
970099AG2-077 GEN
Solar/Wind Harmer
2.284
3152131X4-039 ST
50/50
2.877
3152121X4-039 GT2
50/50
1.823
3150221REMNGT2
Adder
10.939
3150211REMNGT1
Adder
10.866
972201AH1-685 GEN
Adder
1.887
3150281M RUN A
Adder
11.705
316006AB2-029 C
Solar/Wind Harmer
0.549
971685AH1-345 GEN
Solar/Wind Harmer
0.837
3140676OCCOQUN
Adder
0.203
316254AC1-120 GEN1
Solar/Wind Harmer
0.712
316045AC1-158 PL2
Solar/Wind Harmer
2.734
315683AE1-153 C
Solar/Wind Harmer
8.082
3147666LOUISA
Solar/Wind Harmer
-0.032
316192AB2-158 GEN
Solar/Wind Harmer
0.961
3151751LOISA D
Adder
4.652
972223AH1-696 GEN
Adder
5.63
3150151POSSMC1
Adder
0.713
3141346CRANES
Adder
0.082
972197AH1-683 GEN
Adder
1.435
972219AH1-694 GEN
Adder
1.033
966881AG1-559 GEN
Solar/Wind Harmer
0.078
957971AF2-091 GEN
Solar/Wind Harmer
0.75
972135AH1-637 GEN
Solar/Wind Harmer
0.75
316337AD2-073 GEN
Solar/Wind Harmer
0.198
3150351NORNECKC2
Adder
0.651
964211AG1-282 GEN
Solar/Wind Harmer
0.22
3141726DUNNSVL
Solar/Wind Harmer
-0.029
962861AG1-135 GEN
Solar/Wind Harmer
2.741
961951AG1-038 GEN
Solar/Wind Harmer
0.961
3143226MDLTHAN
Solar/Wind Harmer
-0.007
3143526WINTERP
Solar/Wind Harmer
-0.038
3142416OLDCHRC
Solar/Wind Harmer
-0.019
3142416OLDCHRC
Solar/Wind Harmer
-0.007
3138133OCRAN
Solar/Wind Harmer
-0.004
3150851SPRUNCC
Adder
0.297
3141766HARMONY
Solar/Wind Harmer
-0.001
971777AH1-397 GEN
Solar/Wind Harmer
0.852
3141843SHACKLE
Adder
0.329
3143096IRON208
Adder
0.27
3142433PROV 92
Solar/Wind Harmer
-0.029
3142433PROV 92
Adder
0.125
3142433PROV 92
Adder
0.125
3142543TWELFTH
Solar/Wind Harmer
-0.001
944631AF1-128 GEN
Adder
30.629
316159AE1-175 C
Solar/Wind Harmer
0.193
971317AH1-138 GEN
Solar/Wind Harmer
0.895
315671AE2-027_GEN
Solar/Wind Harmer
5.367
970129AG2-093 GEN
Solar/Wind Harmer
1.632
316458AB2-190 GEN2
Solar/Wind Harmer
0.724
971069AG2-661 GEN
Solar/Wind Harmer
1.13
3138126ROCKLANDING
Solar/Wind Harmer
0.022
971647AH1-324 GEN
Solar/Wind Harmer
3.563
961611AG1-000B GEN
Solar/Wind Harmer
3.512
3151171GRAVELC
Adder
0.673
3143336POWHATN
Solar/Wind Harmer
0.841
3145336SMITFLD
Solar/Wind Harmer
-0.028
316294AC1-161 GEN
Solar/Wind Harmer
2.291
970659AG2-427 GEN
Solar/Wind Harmer
3.755
316381AD1-082 GEN
Solar/Wind Harmer
0.648
316375AC2-012 GEN
Solar/Wind Harmer
2.44
3150981CHESPKA
Adder
0.784
944591AF1-124 GEN
Solar/Wind Harmer
32.182
970661AG2-428 GEN
Solar/Wind Harmer
7.492
316072AD1-144
Solar/Wind Harmer
0.142
939411AE1-173 GEN
Solar/Wind Harmer
35.173
940641AE2-051 GEN
Solar/Wind Harmer
6.594
316336AC2-165 C
Solar/Wind Harmer
1.222
316388AE2-253 GEN
Solar/Wind Harmer
0.474
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316246AF1-032 C
Solar/Wind Harmer
0.142
316093AE2-104_GEN
Solar/Wind Harmer
2.034
3146516WINFALL
Solar/Wind Harmer
-0.022
3146516WINFALL
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.702
970937AG2-583 GEN
Solar/Wind Harmer
4.952
3130156CHOWAN
Solar/Wind Harmer
-0.007
3145663CRESWEL
Solar/Wind Harmer
-0.019
971163AH1-040 GEN
Solar/Wind Harmer
6.359
972003AH1-546 GEN
Solar/Wind Harmer
3.372
316322AB2-045
Solar/Wind Harmer
0.226
3146776BUCKING
Solar/Wind Harmer
-0.003
970919AG2-571 GEN
Solar/Wind Harmer
2.123
316023GEN1_S
Solar/Wind Harmer
0.452
970087AG2-069 GEN
Solar/Wind Harmer
6.277
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.673
3145893MURPHYS
Solar/Wind Harmer
-0.027
3145893MURPHYS
Solar/Wind Harmer
0.198
3146926FARMVIL
Solar/Wind Harmer
-0.004
3146173TUNIS
Solar/Wind Harmer
-0.007
972277AH1-723 GEN
Adder
35.15
3147043LAWRENC
Adder
0.53
3144293JTRSVLE
Adder
0.186
23779801AA1-109
Solar/Wind Helper
0.261
223401AF1-299 GEN
Solar/Wind Helper
0.385
966131AG1-482 GEN
Solar/Wind Helper
0.069
237080AD1-060 GEN
Solar/Wind Helper
0.242
235062AE1-101 C1
Solar/Wind Helper
1.169
237038AE2-054 C
Solar/Wind Helper
0.19
233930AB2-032 GEN
Solar/Wind Helper
0.23
233915AB1-141 GEN
Solar/Wind Helper
0.304
232422X3-066 FULL
Solar/Wind Helper
0.069
233964AF2-378 GEN
Solar/Wind Helper
0.025
232426Y1-080 FULL
Solar/Wind Helper
0.023
232428Y3-058 C
Solar/Wind Helper
0.203
233998TM1NIN_3.36
Solar/Wind Helper
0.157
233954AC2-188 GEN
Solar/Wind Helper
0.14
232404W1-003 C
Solar/Wind Helper
0.305
233950AC2-186 GEN
Solar/Wind Helper
0.07
232434Z2-077 GEN
Solar/Wind Helper
0.076
233972AC1-094 C
Solar/Wind Helper
0.181
205941AD2-115 GEN
Solar/Wind Helper
0.302
230511AF1-262
Solar/Wind Helper
0.009
230434AG1-499 GEN
Solar/Wind Helper
0.136
228728W1-130C
Solar/Wind Helper
0.032
219258KINSLEYDEP C
Solar/Wind Helper
0.045
219904AC1-010 C
Solar/Wind Helper
0.036
219907AC1-030 C
Solar/Wind Helper
0.02
218660EHAMPSOLAR C
Solar/Wind Helper
0.019
219686LUMSOLAR_N C
Solar/Wind Helper
0.023
219304NAMERICA C
Solar/Wind Helper
0.077
20720728JCB_W1-129
Solar/Wind Helper
0.033
207445AB1-138_GEN
Solar/Wind Helper
0.061
963711AG1-223 GEN
Solar/Wind Helper
0.037
20714828MDF_W3-079
Solar/Wind Helper
0.076
219680HOPEWELLV C1
Solar/Wind Helper
0.002
207454AA2-184 E
Solar/Wind Helper
0.179
20715228NPK_W1-113
Solar/Wind Helper
0.045
20742028HF_AC1-207
Solar/Wind Helper
0.081
207528AF2-192 GEN
Solar/Wind Helper
0.044
20673628F1S_V4-069
Solar/Wind Helper
0.017
20675428EAM_W2-061
Solar/Wind Helper
0.009
218428ETC SOLAR C
Solar/Wind Helper
0.003
20676428JCR_X2-075
Solar/Wind Helper
0.039
217213AMBOY SO C
Solar/Wind Helper
0.016
217209CENTRL HS C
Solar/Wind Helper
0.005
217208PARK ELE C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.013
207437AD2-070 GEN
Solar/Wind Helper
0.078
207439AE1-081 C O1
Solar/Wind Helper
0.011
207518AF1-320_GEN
Solar/Wind Helper
0.893
20671928W4-073
Solar/Wind Helper
0.051
20675828AU_W4-064
Solar/Wind Helper
0.017
961301AF2-421 GEN
Solar/Wind Helper
0.239
963151AG1-164 GEN
Solar/Wind Helper
0.239
212266LOR1
Solar/Wind Helper
0.025
961341AF2-425 GEN
Solar/Wind Helper
0.233
212507AE2-042_GEN
Solar/Wind Helper
0.817
946731AF1-337 GEN
Solar/Wind Helper
0.23
209071AE2-133 GEN
Solar/Wind Helper
0.041
957481AF2-042 GEN
Solar/Wind Harmer
5.711
NYPJM->LTFIMP_NY
CLTF
2.532
LGEELTFEXP_LGEE->PJM
CLTF
1.753
WECLTFEXP_WEC->PJM
CLTF
0.941
LAGNLTFEXP_LAGN->PJM
CLTF
5.835
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.776
TVALTFEXP_TVA->PJM
CLTF
2.938
CBM West 1LTFEXP_CBM-W1->PJM
CBM
34.919
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.772
MECLTFEXP_MEC->PJM
CLTF
4.292
SIGELTFEXP_SIGE->PJM
CLTF
0.135
CPLELTFEXP_CPLE->PJM
CLTF
4.229
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.691

Details for 6EDFERRY-DICKH230 230.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019B_SRT-A


Base Case Flowgate

Area:DVP/PEPCO
Facility Description:
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.46 %
Rating:1417.0 MVA
Rating Type:B
MVA to Mitigate:1862.72
MW Contribution:41.59
Bus #Bus NameTypeMW Contribution
3152111X4-039 GT1
50/50
2.007
315747AE2-019 GEN
50/50
14.059
963691AG1-221 GEN
Solar/Wind Harmer
2.52
971455AH1-223 GEN
Solar/Wind Harmer
2.52
3141196NOKESVL
Solar/Wind Harmer
-0.049
3150231REMNGT3
Adder
13.559
3150241REMNGT4
Adder
12.643
972199AH1-684 GEN
Adder
1.917
972217AH1-693 GEN
Adder
1.667
3150301M RUN C
Adder
13.435
3150291M RUN B
Adder
13.336
316170AC1-121 GEN2
Solar/Wind Harmer
0.275
316044AC1-158 PL1
Solar/Wind Harmer
0.993
316450AC1-158 RIC
Solar/Wind Harmer
0.265
3132273ORANGE
Solar/Wind Harmer
-0.002
3150151POSSMC1
Adder
0.848
3150151POSSMC1
Adder
0.848
3147666LOUISA
Solar/Wind Harmer
-0.022
3151761LOISA E
Adder
11.06
972183AH1-676 GEN
Adder
89.287
3150331BIRCHWDA
Adder
13.842
3141316ARNOLDS
Adder
0.192
3150401LDYSMT4
Adder
10.874
3150371LDYSMT1
Adder
10.507
966881AG1-559 GEN
Solar/Wind Harmer
0.269
970737AG2-469 GEN
Solar/Wind Harmer
4.42
3152131X4-039 ST
50/50
3.158
3152121X4-039 GT2
50/50
2.001
970467AG2-304 GEN
50/50
15.27
3150221REMNGT2
Adder
12.559
3150211REMNGT1
Adder
12.476
972201AH1-685 GEN
Adder
2.167
3150281M RUN A
Adder
13.444
316006AB2-029 C
Solar/Wind Harmer
0.632
971685AH1-345 GEN
Solar/Wind Harmer
0.963
3140676OCCOQUN
Adder
0.237
316254AC1-120 GEN1
Solar/Wind Harmer
0.825
316045AC1-158 PL2
Solar/Wind Harmer
3.177
315683AE1-153 C
Solar/Wind Harmer
9.363
972223AH1-696 GEN
Adder
6.699
3150151POSSMC1
Adder
0.848
3147666LOUISA
Solar/Wind Harmer
-0.038
316192AB2-158 GEN
Solar/Wind Harmer
1.122
3151751LOISA D
Adder
5.425
3141346CRANES
Adder
0.098
972197AH1-683 GEN
Adder
1.698
972219AH1-694 GEN
Adder
1.223
966881AG1-559 GEN
Solar/Wind Harmer
0.092
957971AF2-091 GEN
Solar/Wind Harmer
0.888
972135AH1-637 GEN
Solar/Wind Harmer
0.887
316337AD2-073 GEN
Solar/Wind Harmer
0.235
3150351NORNECKC2
Adder
0.77
964211AG1-282 GEN
Solar/Wind Harmer
0.261
3141726DUNNSVL
Solar/Wind Harmer
-0.034
962861AG1-135 GEN
Solar/Wind Harmer
3.239
961951AG1-038 GEN
Solar/Wind Harmer
1.136
3143226MDLTHAN
Solar/Wind Harmer
-0.009
3142416OLDCHRC
Solar/Wind Harmer
-0.022
3142416OLDCHRC
Solar/Wind Harmer
-0.008
3143526WINTERP
Solar/Wind Harmer
-0.044
3138133OCRAN
Solar/Wind Harmer
-0.005
3141766HARMONY
Solar/Wind Harmer
-0.002
971777AH1-397 GEN
Solar/Wind Harmer
1.006
3141843SHACKLE
Adder
0.389
3150851SPRUNCC
Adder
0.351
3143096IRON208
Adder
0.319
3142433PROV 92
Solar/Wind Harmer
-0.034
3142433PROV 92
Adder
0.148
3142433PROV 92
Adder
0.148
3142543TWELFTH
Solar/Wind Harmer
-0.001
944631AF1-128 GEN
Adder
36.159
316159AE1-175 C
Solar/Wind Harmer
0.227
971317AH1-138 GEN
Solar/Wind Harmer
1.057
315671AE2-027_GEN
Solar/Wind Harmer
6.335
970129AG2-093 GEN
Solar/Wind Harmer
1.926
316458AB2-190 GEN2
Solar/Wind Harmer
0.854
971069AG2-661 GEN
Solar/Wind Harmer
1.334
3138126ROCKLANDING
Solar/Wind Harmer
0.026
971647AH1-324 GEN
Solar/Wind Harmer
4.206
961611AG1-000B GEN
Solar/Wind Harmer
4.146
3151171GRAVELC
Adder
0.794
3145336SMITFLD
Solar/Wind Harmer
-0.033
316294AC1-161 GEN
Solar/Wind Harmer
2.704
3143336POWHATN
Solar/Wind Harmer
0.991
972289AH1-729 GEN
50/50
14.564
315651AD1-115 GEN
Solar/Wind Harmer
4.557
316447AC1-158 HLD
Solar/Wind Harmer
2.184
3150071POSSM 5
Adder
38.76
3150181POSSMC2
Adder
0.855
3150181POSSMC2
Adder
0.848
3150181POSSMC2
Adder
0.848
966001AG1-469 GEN
Solar/Wind Harmer
0.179
3151731LOISA B
Adder
5.425
3151721LOISA A
Adder
5.397
3150391LDYSMT3
Adder
10.854
972195AH1-682 GEN
Adder
1.426
315673AE1-157 GEN
Solar/Wind Harmer
6.752
957411AF2-035 GEN
Solar/Wind Harmer
4.024
970317AG2-208 GEN
Solar/Wind Harmer
3.912
316468AD1-105 GEN
Solar/Wind Harmer
0.981
316077AC2-138 C
Solar/Wind Harmer
0.183
3150341NORNECKC1
Adder
0.809
3150341NORNECKC1
Adder
0.802
966871AG1-558 GEN
Solar/Wind Harmer
0.26
966871AG1-558 GEN
Solar/Wind Harmer
0.089
958261AF2-120 GEN
Solar/Wind Harmer
3.349
316487AF1-042 GEN
Solar/Wind Harmer
1.136
3142296MT RD221
Adder
0.244
971223AH1-071 GEN
Solar/Wind Harmer
1.075
3143526WINTERP
Solar/Wind Harmer
-0.044
3142366NRTHEST
Adder
0.249
3150691DARBY 3
Adder
5.491
3150701DARBY 4
Adder
5.478
3150681DARBY 2
Adder
5.471
3150671DARBY 1
Adder
5.465
316075AC2-137 C
Solar/Wind Harmer
0.231
316441AF1-014 GEN
Solar/Wind Harmer
0.577
3142946ENON
Solar/Wind Harmer
-0.001
944641AF1-129 GEN
Adder
35.924
316240AF1-291 C
Solar/Wind Harmer
0.255
316033AB2-134 GEN
Solar/Wind Harmer
2.716
315697AD1-025 GEN
Solar/Wind Harmer
1.703
316236AE1-162_GEN
Solar/Wind Harmer
0.252
970657AG2-426 GEN
Solar/Wind Harmer
2.604
970657AG2-426 GEN
Solar/Wind Harmer
0.544
316036AC1-147 C
Solar/Wind Harmer
0.225
3150991CHESPKB
Adder
0.776
3150991CHESPKB
Adder
0.757
316316AC1-027 C
Solar/Wind Harmer
0.255
3142956BIRDNECK
Solar/Wind Harmer
0.446
316185AD1-033 GEN
Solar/Wind Harmer
0.876
3145506HICKORY
Solar/Wind Harmer
-0.033
3145506HICKORY
Solar/Wind Harmer
-0.02
3145506HICKORY
Solar/Wind Harmer
-0.005
316339AD2-160 GEN
Solar/Wind Harmer
0.559
316018AA1-139 ULT2
Solar/Wind Harmer
0.71
316017AA1-139 ULT1
Solar/Wind Harmer
0.67
3137176SLIGO L2192
Solar/Wind Harmer
-0.033
3146456SLIGO L269
Solar/Wind Harmer
0.977
3130086AYDLETT
Solar/Wind Harmer
-0.033
3146386ELIZ CT
Solar/Wind Harmer
-0.008
971761AH1-387 GEN
Solar/Wind Harmer
4.579
316431W1029_GEN1
Solar/Wind Harmer
1.486
316433W1029_GEN2
Solar/Wind Harmer
1.486
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3144356SAPONY
Solar/Wind Harmer
0.285
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.849
3146376EDENTON
Solar/Wind Harmer
0.24
3146376EDENTON
Solar/Wind Harmer
0.24
972185AH1-677 GEN
Adder
4.036
972187AH1-678 GEN
Adder
2.039
970933AG2-581 GEN
Solar/Wind Harmer
7.52
3146776BUCKING
Solar/Wind Harmer
-0.032
3146776BUCKING
Solar/Wind Harmer
-0.003
316065AD1-022 GEN
Solar/Wind Harmer
3.958
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
3.936
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
971741AH1-377 GEN
Solar/Wind Harmer
9.144
3144293JTRSVLE
Adder
0.22
3144293JTRSVLE
Adder
0.185
237025AB1-124 C
Solar/Wind Helper
0.168
237006AB1-125 GEN
Solar/Wind Helper
0.126
23777801MSM_W1-116
Solar/Wind Helper
0.11
205916AD1-020 GEN
Solar/Wind Helper
1.496
208835TUHI V3-051
Solar/Wind Helper
0.021
208835TUHI V3-051
Solar/Wind Helper
0.021
237034AC2-136 C
Solar/Wind Helper
0.157
233933AB2-153 GEN
Solar/Wind Helper
0.184
233944AB2-135 GEN
Solar/Wind Helper
0.465
232424Y1-079 C
Solar/Wind Helper
0.092
233987AB2-037 GEN
Solar/Wind Helper
1.847
233946AB2-136 GEN
Solar/Wind Helper
0.448
234036AF2-325 C
Solar/Wind Helper
0.033
233901CHERRYDALE C
Solar/Wind Helper
0.183
232408W1-005 C
Solar/Wind Helper
0.4
232410W1-006 C
Solar/Wind Helper
0.4
233939AC1-091 C
Solar/Wind Helper
0.275
233970AC1-092 C
Solar/Wind Helper
0.275
230433AD2-135 GEN
Solar/Wind Helper
0.013
230407AD2-065 C
Solar/Wind Helper
0.031
219921AF1-264
Solar/Wind Helper
0.039
219615MILLCREEK C
Solar/Wind Helper
0.02
963401AG1-189 GEN
Solar/Wind Helper
0.043
963391AG1-188 GEN
Solar/Wind Helper
0.062
20714928UPF_X1-085
Solar/Wind Helper
0.004
20720628TIN_W1-124
Solar/Wind Helper
0.143
20716928W4-060COL
Solar/Wind Helper
0.039
218440SUMMTASSOC C
Solar/Wind Helper
0.012
20673828FLE_V3-070
Solar/Wind Helper
0.068
207442AE1-156 GEN
Solar/Wind Helper
0.243
20676128MHD_W3-029
Solar/Wind Helper
0.072
20671828STAW2-080
Solar/Wind Helper
0.02
217081WEATEXAS C
Solar/Wind Helper
0.009
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.005
217204WCALDSOLAR C
Solar/Wind Helper
0.002
226929AD2-058 GEN
Solar/Wind Helper
0.066
207471AF2-354 C
Solar/Wind Helper
0.124
20674928WA_W3-044
Solar/Wind Helper
0.072
20676228FRD_X1-012
Solar/Wind Helper
0.067
964851AG1-348 GEN
Solar/Wind Helper
0.059
20674128FR_U2-059
Solar/Wind Helper
0.003
966111AG1-480 GEN
Solar/Wind Helper
0.032
211065PSPA IPP
Solar/Wind Helper
0.109
211065PSPA IPP
Solar/Wind Helper
0.109
20390526W1-045 C
Solar/Wind Helper
0.226
208972BECR K09
Solar/Wind Helper
0.227
961431AF2-434 GEN
Solar/Wind Helper
0.302
209029WAYMART-WD
Solar/Wind Helper
0.566
209054AE2-059 GEN
Solar/Wind Helper
0.054
946751AF1-339 GEN
Solar/Wind Helper
0.297
209137AF2-361 C
Solar/Wind Helper
0.864
237001AB1-127_GEN
Solar/Wind Helper
0.221
237002AB1-128_GEN
Solar/Wind Helper
0.212
235063AE1-101 C2
Solar/Wind Helper
0.747
970099AG2-077 GEN
Solar/Wind Harmer
2.697
971781AH1-399 GEN
Solar/Wind Harmer
0.543
3141906WESTMOR
Solar/Wind Harmer
-0.003
3150351NORNECKC2
Adder
0.783
316473AC1-191 GEN
Solar/Wind Harmer
0.931
316404AE1-155 C
Solar/Wind Harmer
1.667
316484AD2-074 GEN
Solar/Wind Harmer
2.171
970009AG2-005 GEN
Solar/Wind Harmer
1.078
962971AG1-146 GEN
Solar/Wind Harmer
1.614
3142416OLDCHRC
Solar/Wind Harmer
0.867
970293AG2-193 GEN
Solar/Wind Harmer
1.071
3141766HARMONY
Solar/Wind Harmer
0.762
316203AE2-005 GEN
Solar/Wind Harmer
3.607
316280AD1-041 GEN
Solar/Wind Harmer
0.645
316156AD2-030 GEN
Solar/Wind Harmer
0.228
3141873WAN 176
Solar/Wind Harmer
1.015
3141843SHACKLE
Adder
0.389
3150861SPRUNCD
Adder
0.351
3143096IRON208
Adder
0.319
3143096IRON208
Adder
0.312
3142433PROV 92
Adder
0.148
3142433PROV 92
Adder
0.148
3142946ENON
Solar/Wind Harmer
-0.003
316382AG1-145 C
Solar/Wind Harmer
0.255
970133AG2-095 GEN
Solar/Wind Harmer
0.953
970129AG2-093 GEN
Solar/Wind Harmer
4.756
965281AG1-393 GEN
Solar/Wind Harmer
1.054
315778AD1-151 GEN
Solar/Wind Harmer
7.304
3150921YORKTN3
Adder
1.885
315839AE2-212 C
Solar/Wind Harmer
0.254
3144216WINCHST
Adder
0.283
961611AG1-000B GEN
Solar/Wind Harmer
1.769
3151221GRAVEL6
Adder
5.427
3151171GRAVELC
Adder
1.044
315813AE1-149 C
Solar/Wind Harmer
5.23
3145336SMITFLD
Solar/Wind Harmer
-0.003
315773AC2-141 GEN
Solar/Wind Harmer
3.497
316313AB2-026
Solar/Wind Harmer
0.225
316258AE1-075 C
Solar/Wind Harmer
0.203
316405AF2-144 C
Solar/Wind Harmer
0.214
3143336POWHATN
Solar/Wind Harmer
0.843
970659AG2-427 GEN
Solar/Wind Harmer
0.785
316083AB2-161 GEN
Solar/Wind Harmer
1.353
3144536CHRHLND
Solar/Wind Harmer
-0.001
3151101ELIZAR3
Adder
6.877
3144873MCLAUGH
Solar/Wind Harmer
0
944581AF1-123 GEN
Solar/Wind Harmer
37.845
944601AF1-125 GEN
Solar/Wind Harmer
37.254
970661AG2-428 GEN
Solar/Wind Harmer
1.567
3146456SLIGO L269
Solar/Wind Harmer
-0.008
971153AH1-033 GEN
Solar/Wind Harmer
1.009
316320Y1-086
Solar/Wind Harmer
0.483
316435W1029_GEN3
Solar/Wind Harmer
1.486
3146516WINFALL
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3145273HOLLAND
Solar/Wind Harmer
-0.006
3146376EDENTON
Solar/Wind Harmer
-0.008
315614AA2-178 GEN
Solar/Wind Harmer
0.864
3156081AA2-088 GEN
Solar/Wind Harmer
2.58
971157AH1-035 GEN
Solar/Wind Harmer
0.994
315737AD1-076 GEN
Solar/Wind Harmer
1.509
3146776BUCKING
Solar/Wind Harmer
-0.003
970917AG2-570 GEN
Solar/Wind Harmer
19.793
316365GEN2_N
Solar/Wind Harmer
0.534
3146206CASHIE
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
3146926FARMVIL
Solar/Wind Harmer
-0.005
957521AF2-046 GEN
Solar/Wind Harmer
6.214
961681AG1-008 GEN
Solar/Wind Harmer
6.214
970909AG2-566 GEN
Solar/Wind Harmer
0.747
3146173TUNIS
Solar/Wind Harmer
-0.008
972255AH1-712 GEN
Adder
35.693
3144293JTRSVLE
Adder
0.22
3151861LOWMORA
Adder
0.674
3152541MT STMG
Adder
0.593
237030AB1-096 C
Solar/Wind Helper
0.073
223402AF1-300 C
Solar/Wind Helper
0.379
226910AB2-157 C
Solar/Wind Helper
0.012
205917AD1-020 ES
Solar/Wind Helper
0.322
227287AC2-120 GEN
Solar/Wind Helper
0.266
233918AB1-142 GEN
Solar/Wind Helper
0.397
233982AB2-133 GEN
Solar/Wind Helper
0.282
233994AC2-023 GEN
Solar/Wind Helper
0.757
233996TM1833_GEN
Solar/Wind Helper
0.206
233997TMININ_4.2
Solar/Wind Helper
0.206
233940AF2-379 C
Solar/Wind Helper
0.049
234015AF2-250 C
Solar/Wind Helper
0.03
232406W1-004 FULL
Solar/Wind Helper
0.4
233952AC2-187 GEN
Solar/Wind Helper
0.183
233971AC1-093 C
Solar/Wind Helper
0.281
230430AE1-229_GEN
Solar/Wind Helper
2.603
230415AB2-049 C
Solar/Wind Helper
0.023
228729W2-030 C
Solar/Wind Helper
0.085
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.042
219912AD2-042 GEN
Solar/Wind Helper
0.115
219291REEVESSOUT C
Solar/Wind Helper
0.009
219236SOUTHERNHQ C
Solar/Wind Helper
0.004
219906AC1-017 C
Solar/Wind Helper
0.032
219348LDSOLAR C
Solar/Wind Helper
0.088
959561AF2-247 GEN
Solar/Wind Helper
0.016
20716028EGP_W2-019
Solar/Wind Helper
0.014
20720828JCB_W4-025
Solar/Wind Helper
0.048
20715028HAN_X4-015
Solar/Wind Helper
0.043
219276PARKLANDSO C
Solar/Wind Helper
0.068
20714528FRN_Y2-051
Solar/Wind Helper
0.043
970659AG2-427 GEN
Solar/Wind Harmer
4.431
316381AD1-082 GEN
Solar/Wind Harmer
0.765
316375AC2-012 GEN
Solar/Wind Harmer
2.88
3150981CHESPKA
Adder
0.925
944591AF1-124 GEN
Solar/Wind Harmer
37.981
970661AG2-428 GEN
Solar/Wind Harmer
8.843
316072AD1-144
Solar/Wind Harmer
0.168
939411AE1-173 GEN
Solar/Wind Harmer
41.494
940641AE2-051 GEN
Solar/Wind Harmer
7.777
316336AC2-165 C
Solar/Wind Harmer
1.441
316388AE2-253 GEN
Solar/Wind Harmer
0.559
3146456SLIGO L269
Solar/Wind Harmer
-0.008
316246AF1-032 C
Solar/Wind Harmer
0.167
316093AE2-104_GEN
Solar/Wind Harmer
2.401
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.008
315800Z1-036_GEN1
Solar/Wind Harmer
2.009
970937AG2-583 GEN
Solar/Wind Harmer
5.84
3130156CHOWAN
Solar/Wind Harmer
-0.008
3145663CRESWEL
Solar/Wind Harmer
-0.022
971163AH1-040 GEN
Solar/Wind Harmer
7.509
972003AH1-546 GEN
Solar/Wind Harmer
3.978
316322AB2-045
Solar/Wind Harmer
0.267
3146776BUCKING
Solar/Wind Harmer
-0.003
970919AG2-571 GEN
Solar/Wind Harmer
2.505
316023GEN1_S
Solar/Wind Harmer
0.534
3146206CASHIE
Solar/Wind Harmer
-0.008
970087AG2-069 GEN
Solar/Wind Harmer
7.409
971547AH1-271 GEN
Solar/Wind Harmer
1.976
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
3146926FARMVIL
Solar/Wind Harmer
-0.005
3146173TUNIS
Solar/Wind Harmer
-0.008
972277AH1-723 GEN
Adder
41.593
3147043LAWRENC
Adder
0.626
3144293JTRSVLE
Adder
0.22
223401AF1-299 GEN
Solar/Wind Helper
0.379
23779801AA1-109
Solar/Wind Helper
0.182
966131AG1-482 GEN
Solar/Wind Helper
0.066
233930AB2-032 GEN
Solar/Wind Helper
0.301
233915AB1-141 GEN
Solar/Wind Helper
0.397
232422X3-066 FULL
Solar/Wind Helper
0.09
233964AF2-378 GEN
Solar/Wind Helper
0.033
232426Y1-080 FULL
Solar/Wind Helper
0.031
233998TM1NIN_3.36
Solar/Wind Helper
0.206
232428Y3-058 C
Solar/Wind Helper
0.266
232404W1-003 C
Solar/Wind Helper
0.4
233954AC2-188 GEN
Solar/Wind Helper
0.183
233950AC2-186 GEN
Solar/Wind Helper
0.091
232434Z2-077 GEN
Solar/Wind Helper
0.1
233972AC1-094 C
Solar/Wind Helper
0.238
230511AF1-262
Solar/Wind Helper
0.011
230434AG1-499 GEN
Solar/Wind Helper
0.177
228728W1-130C
Solar/Wind Helper
0.041
219258KINSLEYDEP C
Solar/Wind Helper
0.059
219904AC1-010 C
Solar/Wind Helper
0.047
219907AC1-030 C
Solar/Wind Helper
0.026
218660EHAMPSOLAR C
Solar/Wind Helper
0.025
219686LUMSOLAR_N C
Solar/Wind Helper
0.031
219304NAMERICA C
Solar/Wind Helper
0.1
20720728JCB_W1-129
Solar/Wind Helper
0.043
207445AB1-138_GEN
Solar/Wind Helper
0.079
963711AG1-223 GEN
Solar/Wind Helper
0.048
20714828MDF_W3-079
Solar/Wind Helper
0.099
205941AD2-115 GEN
Solar/Wind Helper
0.375
219680HOPEWELLV C1
Solar/Wind Helper
0.002
207454AA2-184 E
Solar/Wind Helper
0.234
20715228NPK_W1-113
Solar/Wind Helper
0.059
20742028HF_AC1-207
Solar/Wind Helper
0.106
218428ETC SOLAR C
Solar/Wind Helper
0.004
217213AMBOY SO C
Solar/Wind Helper
0.021
207528AF2-192 GEN
Solar/Wind Helper
0.057
20673628F1S_V4-069
Solar/Wind Helper
0.022
20675428EAM_W2-061
Solar/Wind Helper
0.012
20676428JCR_X2-075
Solar/Wind Helper
0.051
217209CENTRL HS C
Solar/Wind Helper
0.006
217208PARK ELE C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.017
207439AE1-081 C O1
Solar/Wind Helper
0.014
207437AD2-070 GEN
Solar/Wind Helper
0.101
20675828AU_W4-064
Solar/Wind Helper
0.022
207518AF1-320_GEN
Solar/Wind Helper
1.156
20671928W4-073
Solar/Wind Helper
0.066
961301AF2-421 GEN
Solar/Wind Helper
0.309
963151AG1-164 GEN
Solar/Wind Helper
0.309
212266LOR1
Solar/Wind Helper
0.033
961341AF2-425 GEN
Solar/Wind Helper
0.302
212507AE2-042_GEN
Solar/Wind Helper
1.058
946731AF1-337 GEN
Solar/Wind Helper
0.297
209071AE2-133 GEN
Solar/Wind Helper
0.054
235062AE1-101 C1
Solar/Wind Helper
0.747
237080AD1-060 GEN
Solar/Wind Helper
0.151
237038AE2-054 C
Solar/Wind Helper
0.119
957481AF2-042 GEN
Solar/Wind Harmer
6.742
3138216PACIFIC
Solar/Wind Harmer
-0.003
316411AF1-147_GEN1
Solar/Wind Harmer
1.2
316415AF1-147_GEN2
Solar/Wind Harmer
1.2
970053AG2-049 GEN
Adder
1.707
316164AC1-076 GEN
Solar/Wind Harmer
0.848
3141426STAFORD
Solar/Wind Harmer
-0.002
3147346CASHSCORNER
Solar/Wind Harmer
0.143
3150411LDYSMT5
Adder
10.908
3150381LDYSMT2
Adder
10.439
972213AH1-691 GEN
Adder
1.766
972215AH1-692 GEN
Adder
1.766
944491AF1-114 GEN
Solar/Wind Harmer
2.612
316223AC1-118
Solar/Wind Harmer
0.237
972189AH1-679 GEN
Adder
1.305
3141813NORNECK
Solar/Wind Harmer
-0.009
962981AG1-147 GEN
Solar/Wind Harmer
3.767
316312AB1-027
Solar/Wind Harmer
0.29
316233AE1-074 FULL
Solar/Wind Harmer
0.231
971281AH1-106 GEN
Solar/Wind Harmer
1.396
971283AH1-107 GEN
Solar/Wind Harmer
1.396
3141783LANCAST
Solar/Wind Harmer
-0.005
3141783LANCAST
Solar/Wind Harmer
-0.003
3138133OCRAN
Solar/Wind Harmer
-0.003
3141913WHIT STONE
Solar/Wind Harmer
-0.009
316314AB2-024 C
Solar/Wind Harmer
0.732
316059AD1-063 C
Solar/Wind Harmer
0.193
315662AE1-191 GEN
Solar/Wind Harmer
1.031
315666AE1-190 GEN
Solar/Wind Harmer
0.258
957601AF2-054 GEN
Solar/Wind Harmer
0.256
3143873LANEXA
Solar/Wind Harmer
-0.005
3141873WAN 176
Solar/Wind Harmer
-0.002
971285AH1-108 GEN
Adder
0.574
3142433PROV 92
Adder
0.148
3142433PROV 92
Adder
0.148
315976AC1-164 GENA
Solar/Wind Harmer
9.028
316169AC1-164_GENC
Solar/Wind Harmer
7.799
315975AC1-164 GENB
Solar/Wind Harmer
0.267
971167AH1-042 GEN
Solar/Wind Harmer
8.225
957831AF2-077 GEN
Solar/Wind Harmer
0.255
3138283WHITEMARSH
Solar/Wind Harmer
0.013
316132AB2-190 GEN1
Solar/Wind Harmer
0.854
316369SG1_INVT
Solar/Wind Harmer
1.505
972265AH1-717 GEN
Adder
5.796
3151201GRAVEL4
Adder
5.433
3151191GRAVEL3
Adder
5.364
3151211GRAVEL5
Adder
5.364
3143316POE
Solar/Wind Harmer
-0.033
971445AH1-216 GEN
Solar/Wind Harmer
5.176
3151081ELIZAR1
Adder
6.79
3151091ELIZAR2
Adder
6.672
3152611GOSPORTB
Adder
0.943
3152621GOSPORTC
Adder
0.801
3152601GOSPORTA
Adder
0.738
315833AF1-017_GEN
Solar/Wind Harmer
1.574
316349AD2-085 GEN
Solar/Wind Harmer
0.737
316311AC2-079 GEN
Solar/Wind Harmer
4.18
957871AF2-081 GEN
Solar/Wind Harmer
4.142
319010AE1-072 C
Solar/Wind Harmer
1.673
316305AF2-043 C
Solar/Wind Harmer
0.249
3146406KITTY HAWK
Solar/Wind Harmer
0.007
315835AF2-110_GEN
Solar/Wind Harmer
1.032
313526AB2-022
Solar/Wind Harmer
0.222
3146486SUNBURY
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.008
316321Z2-027
Solar/Wind Harmer
0.222
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
3146396TANGLEW
Solar/Wind Harmer
0.151
316315AB2-025 C
Solar/Wind Harmer
0.22
941031AE2-094 GEN
Solar/Wind Harmer
15.312
944011AF1-069 GEN
Solar/Wind Harmer
4.798
315814AE2-033 C
Solar/Wind Harmer
7.6
315611Z1-036_GEN2
Solar/Wind Harmer
2.009
970673AG2-436 GEN
Solar/Wind Harmer
17.036
970673AG2-436 GEN
Solar/Wind Harmer
8.626
3130156CHOWAN
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.008
971967AH1-528 GEN
Solar/Wind Harmer
15.195
315816AE2-034 GEN
Solar/Wind Harmer
0.648
972205AH1-687 GEN
Adder
3.036
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315732AD1-074 GEN1
Solar/Wind Harmer
1.605
315733AD1-074 GEN2
Solar/Wind Harmer
1.605
315735AD1-075 GEN1
Solar/Wind Harmer
0.803
965291AG1-394 GEN
Solar/Wind Harmer
0.704
971845AH1-439 GEN
Solar/Wind Harmer
4.213
970285AG2-188 GEN
Solar/Wind Harmer
6.934
3138266HYDRAULIC
Solar/Wind Harmer
0
3138266HYDRAULIC
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.94
970581AG2-369 GEN
Solar/Wind Harmer
4.248
970601AG2-382 GEN
Solar/Wind Harmer
3.458
316318V4-068
Solar/Wind Harmer
0.197
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
972193AH1-681 GEN
Adder
1.595
3151881LOWMORC
Adder
0.669
3151881LOWMORC
Adder
0.659
3151861LOWMORA
Adder
0.648
972257AH1-713 GEN
Adder
0.697
23544701WINZ1-113
Adder
0.24
960921AF2-383 GEN
Solar/Wind Helper
0.152
205943AE1-185 GEN
Solar/Wind Helper
0.423
205932AD2-116_GEN
Solar/Wind Helper
0.422
205956AE1-196_GEN
Solar/Wind Helper
0.422
233935AB2-179 C
Solar/Wind Helper
1.004
232436AB1-176 C
Solar/Wind Helper
0.035
233923SMA
Solar/Wind Helper
0.755
233990AG1-397 GEN
Solar/Wind Helper
0.024
234033AF1-007_GEN
Solar/Wind Helper
5.529
232432Z2-076 GEN
Solar/Wind Helper
0.053
964001AG1-254 GEN
Solar/Wind Helper
0.738
227927V4-067C
Solar/Wind Helper
0.008
228754AB1-001 C
Solar/Wind Helper
0.02
219914AD2-027 C
Solar/Wind Helper
0.088
219272CLEANLIGHT C
Solar/Wind Helper
0.019
219688LUMSOLAR_S C
Solar/Wind Helper
0.031
219607WPEMNERT C
Solar/Wind Helper
0.061
214067T20SOLAR
Solar/Wind Helper
0.009
20715728PEM_W1-119
Solar/Wind Helper
0.073
20715828PEM_W1-120
Solar/Wind Helper
0.073
207459AE1-142 C O1
Solar/Wind Helper
0.22
219620RIDERU C
Solar/Wind Helper
0.001
20675528CPH_W2-050
Solar/Wind Helper
0.065
218526CNTRALGAS2 C
Solar/Wind Helper
0.12
218524CNTRALGAS1 C
Solar/Wind Helper
0.12
966261AG1-495 GEN
Solar/Wind Helper
0.06
207530AG1-191 GEN
Solar/Wind Helper
0.049
20676328BVR_Y1-020
Solar/Wind Helper
0.02
20675928HOL_W4-097
Solar/Wind Helper
0.037
20674828DL_W4-046
Solar/Wind Helper
0.006
207484AF2-139 C O1
Solar/Wind Helper
0.062
207408W3-077 C
Solar/Wind Helper
0.062
20675728RH_W2-091
Solar/Wind Helper
0.1
20675128HRM_W1-127
Solar/Wind Helper
0.022
209116AE2-175 GEN
Solar/Wind Helper
1.289
961261AF2-417 GEN
Solar/Wind Helper
0.308
959381AF2-229 GEN
Solar/Wind Helper
0.23
959431AF2-234 GEN
Solar/Wind Helper
0.594
964051AG1-259 GEN
Solar/Wind Helper
0.044
964061AG1-260 GEN
Solar/Wind Helper
0.044
959421AF2-233 GEN
Solar/Wind Helper
0.297
203975AE1-071-GEN
Solar/Wind Helper
1.563
20720528MAN_W1-024
Solar/Wind Helper
0.021
219612MATRIX C
Solar/Wind Helper
0.018
218438BLK ROCK C
Solar/Wind Helper
0.02
219908AB1-139 C
Solar/Wind Helper
0.055
219919AE1-041 FULL
Solar/Wind Helper
0.003
219249CENTRALDIV C
Solar/Wind Helper
0.008
20673728F2S_V4-070
Solar/Wind Helper
0.022
217211CAMDEN ST C
Solar/Wind Helper
0.003
217169METRODIV C
Solar/Wind Helper
0.003
20676728BRNX1-095
Solar/Wind Helper
0.022
207510AF2-138 C
Solar/Wind Helper
0.06
20674628WNG_W3-110
Solar/Wind Helper
0.066
963161AG1-165 GEN
Solar/Wind Helper
0.309
963071AG1-156 GEN
Solar/Wind Helper
1.001
209027LOR2_Q27
Solar/Wind Helper
0.712
961331AF2-424 GEN
Solar/Wind Helper
0.302
961421AF2-433 GEN
Solar/Wind Helper
0.302
957921AF2-086 GEN
Solar/Wind Helper
0.298
946691AF1-333 GEN
Solar/Wind Helper
0.297
946741AF1-338 GEN
Solar/Wind Helper
0.297
209067AE2-060 GEN
Solar/Wind Helper
0.051
238221AF1-254 C O1
Solar/Wind Helper
0.122
235067AD1-061 GEN
Solar/Wind Helper
0.214
NYPJM->LTFIMP_NY
CLTF
3.269
LGEELTFEXP_LGEE->PJM
CLTF
2.098
WECLTFEXP_WEC->PJM
CLTF
1.126
AG2-052LTFEXP_AG2-052->PJM
LTF
0.067
AH1-155LTFEXP_AH1-155->PJM
LTF
0.101
LAGNLTFEXP_LAGN->PJM
CLTF
6.958
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.786
TVALTFEXP_TVA->PJM
CLTF
3.503
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.819
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.851
MECLTFEXP_MEC->PJM
CLTF
5.133
SIGELTFEXP_SIGE->PJM
CLTF
0.162
CPLELTFEXP_CPLE->PJM
CLTF
5.01
CBM West 2LTFEXP_CBM-W2->PJM
CBM
43.81

Details for 6EDFERRY-DICKH230 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 514-2098_SRT-S


Base Case Flowgate

Area:DVP/PEPCO
Facility Description:
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 514-2098_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.66 %
Rating:1417.0 MVA
Rating Type:B
MVA to Mitigate:1482.99
MW Contribution:33.84
Bus #Bus NameTypeMW Contribution
3152131X4-039 ST
50/50
2.978
3152121X4-039 GT2
50/50
1.887
3140676OCCOQUN
Adder
0.219
3150221REMNGT2
Adder
11.204
3150211REMNGT1
Adder
11.13
972201AH1-685 GEN
Adder
1.933
3150281M RUN A
Adder
11.989
316006AB2-029 C
Solar/Wind Harmer
0.563
971685AH1-345 GEN
Solar/Wind Harmer
0.858
316254AC1-120 GEN1
Solar/Wind Harmer
0.729
316045AC1-158 PL2
Solar/Wind Harmer
2.821
972223AH1-696 GEN
Adder
6.238
3150151POSSMC1
Adder
0.79
315683AE1-153 C
Solar/Wind Harmer
8.198
3141346CRANES
Adder
0.089
3147666LOUISA
Solar/Wind Harmer
-0.033
316192AB2-158 GEN
Solar/Wind Harmer
0.98
972197AH1-683 GEN
Adder
1.519
972219AH1-694 GEN
Adder
1.094
3151751LOISA D
Adder
4.689
957971AF2-091 GEN
Solar/Wind Harmer
0.79
966881AG1-559 GEN
Solar/Wind Harmer
0.081
972135AH1-637 GEN
Solar/Wind Harmer
0.787
316337AD2-073 GEN
Solar/Wind Harmer
0.206
3150351NORNECKC2
Adder
0.673
964211AG1-282 GEN
Solar/Wind Harmer
0.228
3141726DUNNSVL
Solar/Wind Harmer
-0.03
962861AG1-135 GEN
Solar/Wind Harmer
2.824
961951AG1-038 GEN
Solar/Wind Harmer
0.989
3138133OCRAN
Solar/Wind Harmer
-0.004
3142416OLDCHRC
Solar/Wind Harmer
-0.019
3142416OLDCHRC
Solar/Wind Harmer
-0.007
3141766HARMONY
Solar/Wind Harmer
-0.001
3143226MDLTHAN
Solar/Wind Harmer
-0.007
3143526WINTERP
Solar/Wind Harmer
-0.038
971777AH1-397 GEN
Solar/Wind Harmer
0.872
3141843SHACKLE
Adder
0.337
3142433PROV 92
Solar/Wind Harmer
-0.029
3142433PROV 92
Adder
0.128
3142433PROV 92
Adder
0.128
3143096IRON208
Adder
0.275
3150851SPRUNCC
Adder
0.303
3142543TWELFTH
Solar/Wind Harmer
-0.001
944631AF1-128 GEN
Adder
31.219
316159AE1-175 C
Solar/Wind Harmer
0.196
971317AH1-138 GEN
Solar/Wind Harmer
0.911
970129AG2-093 GEN
Solar/Wind Harmer
1.657
315671AE2-027_GEN
Solar/Wind Harmer
5.45
316458AB2-190 GEN2
Solar/Wind Harmer
0.735
971069AG2-661 GEN
Solar/Wind Harmer
1.147
3138126ROCKLANDING
Solar/Wind Harmer
0.022
971647AH1-324 GEN
Solar/Wind Harmer
3.613
961611AG1-000B GEN
Solar/Wind Harmer
3.56
3151171GRAVELC
Adder
0.681
3145336SMITFLD
Solar/Wind Harmer
-0.029
316294AC1-161 GEN
Solar/Wind Harmer
2.317
970659AG2-427 GEN
Solar/Wind Harmer
3.796
316381AD1-082 GEN
Solar/Wind Harmer
0.655
316375AC2-012 GEN
Solar/Wind Harmer
2.465
3150981CHESPKA
Adder
0.791
970661AG2-428 GEN
Solar/Wind Harmer
7.568
944591AF1-124 GEN
Solar/Wind Harmer
32.501
316072AD1-144
Solar/Wind Harmer
0.144
939411AE1-173 GEN
Solar/Wind Harmer
35.449
3143336POWHATN
Solar/Wind Harmer
0.841
940641AE2-051 GEN
Solar/Wind Harmer
6.642
316388AE2-253 GEN
Solar/Wind Harmer
0.478
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316246AF1-032 C
Solar/Wind Harmer
0.143
316093AE2-104_GEN
Solar/Wind Harmer
2.049
316336AC2-165 C
Solar/Wind Harmer
1.216
3146516WINFALL
Solar/Wind Harmer
-0.022
3146516WINFALL
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.707
3130156CHOWAN
Solar/Wind Harmer
-0.007
970937AG2-583 GEN
Solar/Wind Harmer
4.871
3145663CRESWEL
Solar/Wind Harmer
-0.019
971163AH1-040 GEN
Solar/Wind Harmer
6.345
970919AG2-571 GEN
Solar/Wind Harmer
2.106
316023GEN1_S
Solar/Wind Harmer
0.449
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.662
3145893MURPHYS
Solar/Wind Harmer
-0.026
3145893MURPHYS
Solar/Wind Harmer
0.197
970087AG2-069 GEN
Solar/Wind Harmer
6.225
3146173TUNIS
Solar/Wind Harmer
-0.007
972003AH1-546 GEN
Solar/Wind Harmer
3.284
960081AF2-299 GEN
Solar/Wind Harmer
0.74
957481AF2-042 GEN
Solar/Wind Harmer
20.536
316322AB2-045
Solar/Wind Harmer
0.221
3145683EARLEYS
Solar/Wind Harmer
-0.007
3146776BUCKING
Solar/Wind Harmer
-0.003
3147043LAWRENC
Adder
0.523
3144293JTRSVLE
Adder
0.182
972277AH1-723 GEN
Adder
33.84
23779801AA1-109
Solar/Wind Helper
0.218
223401AF1-299 GEN
Solar/Wind Helper
0.282
237080AD1-060 GEN
Solar/Wind Helper
0.235
237038AE2-054 C
Solar/Wind Helper
0.184
235062AE1-101 C1
Solar/Wind Helper
1.123
3138216PACIFIC
Solar/Wind Harmer
-0.003
316411AF1-147_GEN1
Solar/Wind Harmer
1.107
316415AF1-147_GEN2
Solar/Wind Harmer
1.107
970053AG2-049 GEN
Adder
1.58
316164AC1-076 GEN
Solar/Wind Harmer
0.75
3141426STAFORD
Solar/Wind Harmer
-0.002
3150411LDYSMT5
Adder
9.757
3150381LDYSMT2
Adder
9.338
972213AH1-691 GEN
Adder
1.58
972215AH1-692 GEN
Adder
1.58
3147346CASHSCORNER
Solar/Wind Harmer
0.123
944491AF1-114 GEN
Solar/Wind Harmer
2.324
316223AC1-118
Solar/Wind Harmer
0.209
972189AH1-679 GEN
Adder
1.141
3141813NORNECK
Solar/Wind Harmer
-0.008
962981AG1-147 GEN
Solar/Wind Harmer
3.278
3141783LANCAST
Solar/Wind Harmer
-0.004
3141783LANCAST
Solar/Wind Harmer
-0.003
3138133OCRAN
Solar/Wind Harmer
-0.002
316312AB1-027
Solar/Wind Harmer
0.251
3141913WHIT STONE
Solar/Wind Harmer
-0.007
316314AB2-024 C
Solar/Wind Harmer
0.634
316059AD1-063 C
Solar/Wind Harmer
0.168
3152111X4-039 GT1
50/50
1.893
315747AE2-019 GEN
50/50
12.918
963691AG1-221 GEN
Solar/Wind Harmer
2.324
971455AH1-223 GEN
Solar/Wind Harmer
2.324
3141196NOKESVL
Solar/Wind Harmer
-0.045
3150231REMNGT3
Adder
12.096
3150241REMNGT4
Adder
11.278
972199AH1-684 GEN
Adder
1.71
972217AH1-693 GEN
Adder
1.487
3150301M RUN C
Adder
11.982
3150291M RUN B
Adder
11.893
316170AC1-121 GEN2
Solar/Wind Harmer
0.243
316044AC1-158 PL1
Solar/Wind Harmer
0.882
316450AC1-158 RIC
Solar/Wind Harmer
0.235
3150151POSSMC1
Adder
0.79
3150151POSSMC1
Adder
0.79
3132273ORANGE
Solar/Wind Harmer
-0.002
3150331BIRCHWDA
Adder
12.528
3147666LOUISA
Solar/Wind Harmer
-0.019
3141316ARNOLDS
Adder
0.173
3150401LDYSMT4
Adder
9.727
3150371LDYSMT1
Adder
9.399
3151761LOISA E
Adder
9.559
972183AH1-676 GEN
Adder
77.132
966881AG1-559 GEN
Solar/Wind Harmer
0.238
970737AG2-469 GEN
Solar/Wind Harmer
3.911
3141906WESTMOR
Solar/Wind Harmer
-0.003
971781AH1-399 GEN
Solar/Wind Harmer
0.478
3150351NORNECKC2
Adder
0.685
316404AE1-155 C
Solar/Wind Harmer
1.454
316473AC1-191 GEN
Solar/Wind Harmer
0.81
316484AD2-074 GEN
Solar/Wind Harmer
1.891
970009AG2-005 GEN
Solar/Wind Harmer
0.939
962971AG1-146 GEN
Solar/Wind Harmer
1.405
3142416OLDCHRC
Solar/Wind Harmer
0.751
3141766HARMONY
Solar/Wind Harmer
0.66
316280AD1-041 GEN
Solar/Wind Harmer
0.559
316156AD2-030 GEN
Solar/Wind Harmer
0.198
3141873WAN 176
Solar/Wind Harmer
0.88
316203AE2-005 GEN
Solar/Wind Harmer
3.126
3141843SHACKLE
Adder
0.337
970293AG2-193 GEN
Solar/Wind Harmer
0.926
3142433PROV 92
Adder
0.128
3142433PROV 92
Adder
0.128
3143096IRON208
Adder
0.275
3143096IRON208
Adder
0.27
3150861SPRUNCD
Adder
0.303
3142946ENON
Solar/Wind Harmer
-0.002
316382AG1-145 C
Solar/Wind Harmer
0.22
970133AG2-095 GEN
Solar/Wind Harmer
0.82
970129AG2-093 GEN
Solar/Wind Harmer
4.092
965281AG1-393 GEN
Solar/Wind Harmer
0.907
315778AD1-151 GEN
Solar/Wind Harmer
6.281
3150921YORKTN3
Adder
1.622
3144216WINCHST
Adder
0.243
315839AE2-212 C
Solar/Wind Harmer
0.218
961611AG1-000B GEN
Solar/Wind Harmer
1.519
3151221GRAVEL6
Adder
4.658
3151171GRAVELC
Adder
0.896
315813AE1-149 C
Solar/Wind Harmer
4.484
3145336SMITFLD
Solar/Wind Harmer
-0.003
315773AC2-141 GEN
Solar/Wind Harmer
2.997
970659AG2-427 GEN
Solar/Wind Harmer
0.673
316083AB2-161 GEN
Solar/Wind Harmer
1.159
315662AE1-191 GEN
Solar/Wind Harmer
0.894
315666AE1-190 GEN
Solar/Wind Harmer
0.223
957601AF2-054 GEN
Solar/Wind Harmer
0.222
3141873WAN 176
Solar/Wind Harmer
-0.001
316233AE1-074 FULL
Solar/Wind Harmer
0.199
971281AH1-106 GEN
Solar/Wind Harmer
1.205
971283AH1-107 GEN
Solar/Wind Harmer
1.205
3143873LANEXA
Solar/Wind Harmer
-0.004
3142433PROV 92
Adder
0.128
3142433PROV 92
Adder
0.128
971167AH1-042 GEN
Solar/Wind Harmer
7.117
315976AC1-164 GENA
Solar/Wind Harmer
7.807
316169AC1-164_GENC
Solar/Wind Harmer
6.744
315975AC1-164 GENB
Solar/Wind Harmer
0.231
971285AH1-108 GEN
Adder
0.495
957831AF2-077 GEN
Solar/Wind Harmer
0.22
3138283WHITEMARSH
Solar/Wind Harmer
0.011
316132AB2-190 GEN1
Solar/Wind Harmer
0.735
316369SG1_INVT
Solar/Wind Harmer
1.293
972265AH1-717 GEN
Adder
4.974
3151201GRAVEL4
Adder
4.663
3151191GRAVEL3
Adder
4.604
3151211GRAVEL5
Adder
4.604
971445AH1-216 GEN
Solar/Wind Harmer
4.438
3143316POE
Solar/Wind Harmer
-0.028
3151081ELIZAR1
Adder
5.812
3151091ELIZAR2
Adder
5.711
3152611GOSPORTB
Adder
0.807
3152621GOSPORTC
Adder
0.685
3152601GOSPORTA
Adder
0.632
315833AF1-017_GEN
Solar/Wind Harmer
1.345
316349AD2-085 GEN
Solar/Wind Harmer
0.63
316311AC2-079 GEN
Solar/Wind Harmer
3.572
957871AF2-081 GEN
Solar/Wind Harmer
3.539
319010AE1-072 C
Solar/Wind Harmer
1.429
316305AF2-043 C
Solar/Wind Harmer
0.213
3146406KITTY HAWK
Solar/Wind Harmer
0.006
315835AF2-110_GEN
Solar/Wind Harmer
0.881
313526AB2-022
Solar/Wind Harmer
0.19
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.189
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.129
316315AB2-025 C
Solar/Wind Harmer
0.187
941031AE2-094 GEN
Solar/Wind Harmer
13.006
944011AF1-069 GEN
Solar/Wind Harmer
4.075
315814AE2-033 C
Solar/Wind Harmer
6.458
315611Z1-036_GEN2
Solar/Wind Harmer
1.707
970673AG2-436 GEN
Solar/Wind Harmer
14.436
970673AG2-436 GEN
Solar/Wind Harmer
7.309
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
971967AH1-528 GEN
Solar/Wind Harmer
12.856
315816AE2-034 GEN
Solar/Wind Harmer
0.548
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315732AD1-074 GEN1
Solar/Wind Harmer
1.352
315733AD1-074 GEN2
Solar/Wind Harmer
1.352
315735AD1-075 GEN1
Solar/Wind Harmer
0.676
965291AG1-394 GEN
Solar/Wind Harmer
0.593
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.908
316318V4-068
Solar/Wind Harmer
0.165
3145893MURPHYS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.15
970581AG2-369 GEN
Solar/Wind Harmer
3.569
972205AH1-687 GEN
Adder
2.506
3145513AHOSKIE
Solar/Wind Harmer
0.057
961941AG1-037 GEN
Solar/Wind Harmer
0.049
3145513AHOSKIE
Solar/Wind Harmer
-0.007
946281AF1-292 GEN
Solar/Wind Harmer
0.147
3146043SEABORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.013
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
972193AH1-681 GEN
Adder
1.298
237085AD2-009_GEN
Solar/Wind Helper
1.037
959381AF2-229 GEN
Solar/Wind Helper
0.251
960921AF2-383 GEN
Solar/Wind Helper
0.119
205943AE1-185 GEN
Solar/Wind Helper
0.335
203975AE1-071-GEN
Solar/Wind Helper
1.667
205956AE1-196_GEN
Solar/Wind Helper
0.332
205932AD2-116_GEN
Solar/Wind Helper
0.332
238208AF1-136 C
Solar/Wind Helper
0.101
233935AB2-179 C
Solar/Wind Helper
0.644
232436AB1-176 C
Solar/Wind Helper
0.022
233923SMA
Solar/Wind Helper
0.482
233990AG1-397 GEN
Solar/Wind Helper
0.015
232432Z2-076 GEN
Solar/Wind Helper
0.034
234033AF1-007_GEN
Solar/Wind Helper
3.527
964001AG1-254 GEN
Solar/Wind Helper
0.476
219914AD2-027 C
Solar/Wind Helper
0.057
227927V4-067C
Solar/Wind Helper
0.005
228754AB1-001 C
Solar/Wind Helper
0.013
219272CLEANLIGHT C
Solar/Wind Helper
0.013
219688LUMSOLAR_S C
Solar/Wind Helper
0.02
219607WPEMNERT C
Solar/Wind Helper
0.04
214067T20SOLAR
Solar/Wind Helper
0.006
20715728PEM_W1-119
Solar/Wind Helper
0.047
20715828PEM_W1-120
Solar/Wind Helper
0.047
207459AE1-142 C O1
Solar/Wind Helper
0.143
219620RIDERU C
Solar/Wind Helper
0.001
20675528CPH_W2-050
Solar/Wind Helper
0.042
218526CNTRALGAS2 C
Solar/Wind Helper
0.079
218524CNTRALGAS1 C
Solar/Wind Helper
0.079
972289AH1-729 GEN
50/50
13.565
315651AD1-115 GEN
Solar/Wind Harmer
4.033
316447AC1-158 HLD
Solar/Wind Harmer
1.939
3150071POSSM 5
Adder
36.095
3150181POSSMC2
Adder
0.796
3150181POSSMC2
Adder
0.79
3150181POSSMC2
Adder
0.79
966001AG1-469 GEN
Solar/Wind Harmer
0.155
3150391LDYSMT3
Adder
9.709
972195AH1-682 GEN
Adder
1.276
3151731LOISA B
Adder
4.689
3151721LOISA A
Adder
4.665
315673AE1-157 GEN
Solar/Wind Harmer
6.001
957411AF2-035 GEN
Solar/Wind Harmer
3.562
970317AG2-208 GEN
Solar/Wind Harmer
3.463
316468AD1-105 GEN
Solar/Wind Harmer
0.864
316077AC2-138 C
Solar/Wind Harmer
0.16
3150341NORNECKC1
Adder
0.707
3150341NORNECKC1
Adder
0.702
958261AF2-120 GEN
Solar/Wind Harmer
2.921
966871AG1-558 GEN
Solar/Wind Harmer
0.226
966871AG1-558 GEN
Solar/Wind Harmer
0.077
316487AF1-042 GEN
Solar/Wind Harmer
0.989
3142296MT RD221
Adder
0.212
3142366NRTHEST
Adder
0.216
3150691DARBY 3
Adder
4.75
3150701DARBY 4
Adder
4.739
3150681DARBY 2
Adder
4.734
3150671DARBY 1
Adder
4.728
971223AH1-071 GEN
Solar/Wind Harmer
0.927
316441AF1-014 GEN
Solar/Wind Harmer
0.5
3143526WINTERP
Solar/Wind Harmer
-0.038
316075AC2-137 C
Solar/Wind Harmer
0.2
3142946ENON
Solar/Wind Harmer
-0.001
944641AF1-129 GEN
Adder
30.931
316240AF1-291 C
Solar/Wind Harmer
0.219
316033AB2-134 GEN
Solar/Wind Harmer
2.335
315697AD1-025 GEN
Solar/Wind Harmer
1.464
316236AE1-162_GEN
Solar/Wind Harmer
0.216
970657AG2-426 GEN
Solar/Wind Harmer
2.229
3144536CHRHLND
Solar/Wind Harmer
-0.001
3151101ELIZAR3
Adder
5.886
3144873MCLAUGH
Solar/Wind Harmer
0
970661AG2-428 GEN
Solar/Wind Harmer
1.341
944581AF1-123 GEN
Solar/Wind Harmer
32.385
944601AF1-125 GEN
Solar/Wind Harmer
31.879
316313AB2-026
Solar/Wind Harmer
0.191
316258AE1-075 C
Solar/Wind Harmer
0.172
316405AF2-144 C
Solar/Wind Harmer
0.182
3143336POWHATN
Solar/Wind Harmer
0.715
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.862
316320Y1-086
Solar/Wind Harmer
0.412
316435W1029_GEN3
Solar/Wind Harmer
1.265
3146516WINFALL
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3145273HOLLAND
Solar/Wind Harmer
-0.005
3146376EDENTON
Solar/Wind Harmer
-0.007
315614AA2-178 GEN
Solar/Wind Harmer
0.73
971157AH1-035 GEN
Solar/Wind Harmer
0.837
3156081AA2-088 GEN
Solar/Wind Harmer
2.173
315737AD1-076 GEN
Solar/Wind Harmer
1.271
970917AG2-570 GEN
Solar/Wind Harmer
16.639
316365GEN2_N
Solar/Wind Harmer
0.449
3146206CASHIE
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
0.046
3145893MURPHYS
Solar/Wind Harmer
-0.007
957521AF2-046 GEN
Solar/Wind Harmer
5.222
961681AG1-008 GEN
Solar/Wind Harmer
5.222
3146173TUNIS
Solar/Wind Harmer
-0.007
3156021HOLLOMANSOL
Solar/Wind Harmer
0.888
316463AE2-346 GEN
Solar/Wind Harmer
0.107
316140AB2-099
Solar/Wind Harmer
0.044
962331AG1-082 GEN
Solar/Wind Harmer
0.823
966621AG1-532 GEN
Solar/Wind Harmer
0.133
3146776BUCKING
Solar/Wind Harmer
-0.002
3144293JTRSVLE
Adder
0.182
972255AH1-712 GEN
Adder
29.04
237030AB1-096 C
Solar/Wind Helper
0.082
238221AF1-254 C O1
Solar/Wind Helper
0.191
205917AD1-020 ES
Solar/Wind Helper
0.292
223402AF1-300 C
Solar/Wind Helper
0.282
235067AD1-061 GEN
Solar/Wind Helper
0.331
226910AB2-157 C
Solar/Wind Helper
0.01
227287AC2-120 GEN
Solar/Wind Helper
0.203
233982AB2-133 GEN
Solar/Wind Helper
0.181
233918AB1-142 GEN
Solar/Wind Helper
0.254
233994AC2-023 GEN
Solar/Wind Helper
0.483
233996TM1833_GEN
Solar/Wind Helper
0.131
233997TMININ_4.2
Solar/Wind Helper
0.131
233940AF2-379 C
Solar/Wind Helper
0.031
234015AF2-250 C
Solar/Wind Helper
0.019
233952AC2-187 GEN
Solar/Wind Helper
0.117
232406W1-004 FULL
Solar/Wind Helper
0.255
233971AC1-093 C
Solar/Wind Helper
0.179
230430AE1-229_GEN
Solar/Wind Helper
1.678
230415AB2-049 C
Solar/Wind Helper
0.015
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219766PARADISE C
Solar/Wind Helper
0.027
219912AD2-042 GEN
Solar/Wind Helper
0.074
228729W2-030 C
Solar/Wind Helper
0.055
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.006
219906AC1-017 C
Solar/Wind Helper
0.021
219348LDSOLAR C
Solar/Wind Helper
0.057
959561AF2-247 GEN
Solar/Wind Helper
0.01
20716028EGP_W2-019
Solar/Wind Helper
0.009
20720828JCB_W4-025
Solar/Wind Helper
0.031
20715028HAN_X4-015
Solar/Wind Helper
0.028
219276PARKLANDSO C
Solar/Wind Helper
0.044
20714528FRN_Y2-051
Solar/Wind Helper
0.028
20720528MAN_W1-024
Solar/Wind Helper
0.014
219612MATRIX C
Solar/Wind Helper
0.012
218438BLK ROCK C
Solar/Wind Helper
0.013
20673728F2S_V4-070
Solar/Wind Helper
0.015
219908AB1-139 C
Solar/Wind Helper
0.036
219919AE1-041 FULL
Solar/Wind Helper
0.002
219249CENTRALDIV C
Solar/Wind Helper
0.005
217211CAMDEN ST C
Solar/Wind Helper
0.002
217169METRODIV C
Solar/Wind Helper
0.002
966131AG1-482 GEN
Solar/Wind Helper
0.056
233930AB2-032 GEN
Solar/Wind Helper
0.192
233915AB1-141 GEN
Solar/Wind Helper
0.254
232422X3-066 FULL
Solar/Wind Helper
0.058
205941AD2-115 GEN
Solar/Wind Helper
0.256
233964AF2-378 GEN
Solar/Wind Helper
0.021
232426Y1-080 FULL
Solar/Wind Helper
0.02
233998TM1NIN_3.36
Solar/Wind Helper
0.131
232428Y3-058 C
Solar/Wind Helper
0.17
233954AC2-188 GEN
Solar/Wind Helper
0.117
232404W1-003 C
Solar/Wind Helper
0.255
233950AC2-186 GEN
Solar/Wind Helper
0.058
232434Z2-077 GEN
Solar/Wind Helper
0.064
233972AC1-094 C
Solar/Wind Helper
0.152
230511AF1-262
Solar/Wind Helper
0.007
230434AG1-499 GEN
Solar/Wind Helper
0.114
219258KINSLEYDEP C
Solar/Wind Helper
0.038
228728W1-130C
Solar/Wind Helper
0.027
219904AC1-010 C
Solar/Wind Helper
0.03
219907AC1-030 C
Solar/Wind Helper
0.017
218660EHAMPSOLAR C
Solar/Wind Helper
0.016
219686LUMSOLAR_N C
Solar/Wind Helper
0.02
219304NAMERICA C
Solar/Wind Helper
0.065
20720728JCB_W1-129
Solar/Wind Helper
0.028
207445AB1-138_GEN
Solar/Wind Helper
0.051
963711AG1-223 GEN
Solar/Wind Helper
0.032
20714828MDF_W3-079
Solar/Wind Helper
0.064
219680HOPEWELLV C1
Solar/Wind Helper
0.002
207454AA2-184 E
Solar/Wind Helper
0.152
20715228NPK_W1-113
Solar/Wind Helper
0.038
20742028HF_AC1-207
Solar/Wind Helper
0.069
207528AF2-192 GEN
Solar/Wind Helper
0.037
20673628F1S_V4-069
Solar/Wind Helper
0.015
20675428EAM_W2-061
Solar/Wind Helper
0.008
20676428JCR_X2-075
Solar/Wind Helper
0.033
218428ETC SOLAR C
Solar/Wind Helper
0.002
217213AMBOY SO C
Solar/Wind Helper
0.014
217209CENTRL HS C
Solar/Wind Helper
0.004
217208PARK ELE C
Solar/Wind Helper
0.002
966261AG1-495 GEN
Solar/Wind Helper
0.04
971845AH1-439 GEN
Solar/Wind Harmer
0.654
970657AG2-426 GEN
Solar/Wind Harmer
0.466
316036AC1-147 C
Solar/Wind Harmer
0.192
3150991CHESPKB
Adder
0.664
3150991CHESPKB
Adder
0.648
3142956BIRDNECK
Solar/Wind Harmer
0.382
316316AC1-027 C
Solar/Wind Harmer
0.218
316185AD1-033 GEN
Solar/Wind Harmer
0.75
3145506HICKORY
Solar/Wind Harmer
-0.028
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
316339AD2-160 GEN
Solar/Wind Harmer
0.478
316018AA1-139 ULT2
Solar/Wind Harmer
0.606
316017AA1-139 ULT1
Solar/Wind Harmer
0.573
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.835
3130086AYDLETT
Solar/Wind Harmer
-0.028
3146386ELIZ CT
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.265
316433W1029_GEN2
Solar/Wind Harmer
1.265
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3144356SAPONY
Solar/Wind Harmer
0.242
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
315742AE1-103 GEN
Solar/Wind Harmer
0.72
3146376EDENTON
Solar/Wind Harmer
0.203
3146376EDENTON
Solar/Wind Harmer
0.203
972185AH1-677 GEN
Adder
3.416
972187AH1-678 GEN
Adder
1.723
970933AG2-581 GEN
Solar/Wind Harmer
6.344
316065AD1-022 GEN
Solar/Wind Harmer
3.331
3145893MURPHYS
Solar/Wind Harmer
0.185
3145893MURPHYS
Solar/Wind Harmer
-0.012
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
970099AG2-077 GEN
Solar/Wind Harmer
8.214
3146776BUCKING
Solar/Wind Harmer
-0.026
3146776BUCKING
Solar/Wind Harmer
-0.002
3144293JTRSVLE
Adder
0.182
3144293JTRSVLE
Adder
0.153
237025AB1-124 C
Solar/Wind Helper
0.191
237006AB1-125 GEN
Solar/Wind Helper
0.143
23777801MSM_W1-116
Solar/Wind Helper
0.13
237034AC2-136 C
Solar/Wind Helper
0.211
237001AB1-127_GEN
Solar/Wind Helper
0.322
237002AB1-128_GEN
Solar/Wind Helper
0.314
205916AD1-020 GEN
Solar/Wind Helper
1.357
235063AE1-101 C2
Solar/Wind Helper
1.123
23777901MDS_W4-102
Solar/Wind Helper
0.114
235020AA1-095 C
Solar/Wind Helper
0.032
20390526W1-045 C
Solar/Wind Helper
0.246
208835TUHI V3-051
Solar/Wind Helper
0.015
208835TUHI V3-051
Solar/Wind Helper
0.015
226929AD2-058 GEN
Solar/Wind Helper
0.051
233933AB2-153 GEN
Solar/Wind Helper
0.117
233944AB2-135 GEN
Solar/Wind Helper
0.297
232424Y1-079 C
Solar/Wind Helper
0.059
233987AB2-037 GEN
Solar/Wind Helper
1.178
234036AF2-325 C
Solar/Wind Helper
0.021
233946AB2-136 GEN
Solar/Wind Helper
0.286
233901CHERRYDALE C
Solar/Wind Helper
0.117
232408W1-005 C
Solar/Wind Helper
0.255
232410W1-006 C
Solar/Wind Helper
0.255
233939AC1-091 C
Solar/Wind Helper
0.176
233970AC1-092 C
Solar/Wind Helper
0.176
230433AD2-135 GEN
Solar/Wind Helper
0.008
230407AD2-065 C
Solar/Wind Helper
0.02
219921AF1-264
Solar/Wind Helper
0.025
219615MILLCREEK C
Solar/Wind Helper
0.013
963401AG1-189 GEN
Solar/Wind Helper
0.028
963391AG1-188 GEN
Solar/Wind Helper
0.041
20714928UPF_X1-085
Solar/Wind Helper
0.003
20720628TIN_W1-124
Solar/Wind Helper
0.093
20716928W4-060COL
Solar/Wind Helper
0.025
20673828FLE_V3-070
Solar/Wind Helper
0.044
218440SUMMTASSOC C
Solar/Wind Helper
0.008
207442AE1-156 GEN
Solar/Wind Helper
0.159
20676128MHD_W3-029
Solar/Wind Helper
0.047
20671828STAW2-080
Solar/Wind Helper
0.013
217081WEATEXAS C
Solar/Wind Helper
0.006
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.003
NYPJM->LTFIMP_NY
CLTF
2.219
LGEELTFEXP_LGEE->PJM
CLTF
1.359
WECLTFEXP_WEC->PJM
CLTF
0.721
LAGNLTFEXP_LAGN->PJM
CLTF
4.834
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.78
TVALTFEXP_TVA->PJM
CLTF
2.439
CBM West 1LTFEXP_CBM-W1->PJM
CBM
26.501
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.848
MECLTFEXP_MEC->PJM
CLTF
3.353
SIGELTFEXP_SIGE->PJM
CLTF
0.105
CPLELTFEXP_CPLE->PJM
CLTF
3.96
CBM West 2LTFEXP_CBM-W2->PJM
CBM
29.603

Details for 6ELMONT-6HANOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 574T575_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6ELMONT-6HANOVER 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 574T575_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.7 %
Rating:1409.0 MVA
Rating Type:C
MVA to Mitigate:1714.74
MW Contribution:55.73
Bus #Bus NameTypeMW Contribution
3143096IRON208
50/50
0.674
3150851SPRUNCC
50/50
0.716
3150641CHESTS8
50/50
0.466
3142416OLDCHRC
Solar/Wind Harmer
-0.051
3142416OLDCHRC
Solar/Wind Harmer
-0.02
3142543TWELFTH
Solar/Wind Harmer
-0.002
944631AF1-128 GEN
Adder
68.961
315671AE2-027_GEN
Solar/Wind Harmer
11.518
970129AG2-093 GEN
Solar/Wind Harmer
3.456
316458AB2-190 GEN2
Solar/Wind Harmer
1.528
3143526WINTERP
Solar/Wind Harmer
-0.078
971069AG2-661 GEN
Solar/Wind Harmer
2.346
3142433PROV 92
Solar/Wind Harmer
-0.058
3142433PROV 92
Adder
0.254
3142433PROV 92
Adder
0.254
971647AH1-324 GEN
Solar/Wind Harmer
7.198
316159AE1-175 C
Solar/Wind Harmer
0.386
961611AG1-000B GEN
Solar/Wind Harmer
6.985
3151171GRAVELC
Adder
1.311
970659AG2-427 GEN
Solar/Wind Harmer
7.3
316381AD1-082 GEN
Solar/Wind Harmer
1.254
971317AH1-138 GEN
Solar/Wind Harmer
1.707
3138126ROCKLANDING
Solar/Wind Harmer
0.042
970661AG2-428 GEN
Solar/Wind Harmer
14.327
3145336SMITFLD
Solar/Wind Harmer
-0.053
3143226MDLTHAN
Solar/Wind Harmer
-0.013
971777AH1-397 GEN
Solar/Wind Harmer
1.569
3141843SHACKLE
Adder
0.607
3141766HARMONY
Solar/Wind Harmer
-0.003
316072AD1-144
Solar/Wind Harmer
0.26
316375AC2-012 GEN
Solar/Wind Harmer
4.419
3150981CHESPKA
Adder
1.419
316294AC1-161 GEN
Solar/Wind Harmer
4.101
944591AF1-124 GEN
Solar/Wind Harmer
57.652
316093AE2-104_GEN
Solar/Wind Harmer
3.663
316388AE2-253 GEN
Solar/Wind Harmer
0.848
316246AF1-032 C
Solar/Wind Harmer
0.254
3146456SLIGO L269
Solar/Wind Harmer
-0.012
3146516WINFALL
Solar/Wind Harmer
-0.039
3146516WINFALL
Solar/Wind Harmer
-0.012
3138133OCRAN
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
2.975
3130156CHOWAN
Solar/Wind Harmer
-0.012
939411AE1-173 GEN
Solar/Wind Harmer
58.022
3145663CRESWEL
Solar/Wind Harmer
-0.032
971163AH1-040 GEN
Solar/Wind Harmer
10.876
3143336POWHATN
Solar/Wind Harmer
1.346
940641AE2-051 GEN
Solar/Wind Harmer
10.561
3146206CASHIE
Solar/Wind Harmer
-0.011
971547AH1-271 GEN
Solar/Wind Harmer
2.804
316023GEN1_S
Solar/Wind Harmer
0.754
3145893MURPHYS
Solar/Wind Harmer
-0.044
3145893MURPHYS
Solar/Wind Harmer
0.331
3146173TUNIS
Solar/Wind Harmer
-0.011
961951AG1-038 GEN
Solar/Wind Harmer
1.441
3145683EARLEYS
Solar/Wind Harmer
-0.011
3146263WOODLND
Solar/Wind Harmer
-0.011
316336AC2-165 C
Solar/Wind Harmer
1.878
960081AF2-299 GEN
Solar/Wind Harmer
1.215
3145963POPLR C
Solar/Wind Harmer
-0.011
316011AB1-132 GEN
Solar/Wind Harmer
2.236
962571AG1-106 GEN
Solar/Wind Harmer
1.537
3145823KELFORD
Solar/Wind Harmer
-0.011
316174AB2-169 GEN
Solar/Wind Harmer
1.645
316190AA2-174 GEN
Solar/Wind Harmer
0.13
962861AG1-135 GEN
Solar/Wind Harmer
3.943
3145796HORNRTN
Solar/Wind Harmer
-0.035
3145796HORNRTN
Solar/Wind Harmer
-0.01
972277AH1-723 GEN
Adder
55.733
971795AH1-408 GEN
Solar/Wind Harmer
7.859
3145783HORNRTN
Solar/Wind Harmer
-0.01
3147043LAWRENC
Adder
0.832
3146293MARTNCO
Solar/Wind Harmer
0.064
316212AC1-099_GEN
Solar/Wind Harmer
0.893
970919AG2-571 GEN
Solar/Wind Harmer
3.189
970087AG2-069 GEN
Solar/Wind Harmer
9.419
3145746EVERETS
Solar/Wind Harmer
-0.01
3145746EVERETS
Solar/Wind Harmer
-0.01
315722AD1-056 GEN
Solar/Wind Harmer
1.04
964211AG1-282 GEN
Solar/Wind Harmer
0.298
3141726DUNNSVL
Solar/Wind Harmer
-0.039
316494AC1-189 GEN
Solar/Wind Harmer
1.06
316129AC1-054 GEN
Solar/Wind Harmer
0.857
957481AF2-042 GEN
Solar/Wind Harmer
30.531
971065AG2-659 GEN
Solar/Wind Harmer
4.854
961671AG1-007 GEN
Solar/Wind Harmer
0.122
3146083TARBORO
Solar/Wind Harmer
-0.01
3145493TOT1
Solar/Wind Harmer
0.287
3146233WITAKRS
Solar/Wind Harmer
-0.038
315693AD1-088 GEN
Solar/Wind Harmer
4.82
3150351NORNECKC2
Adder
0.827
3144293JTRSVLE
Adder
0.258
962491AG1-098 GEN
Solar/Wind Harmer
4.301
3142296MT RD221
50/50
0.655
3142366NRTHEST
50/50
0.581
3150691DARBY 3
50/50
12.553
3150701DARBY 4
50/50
12.524
3150681DARBY 2
50/50
12.51
3150671DARBY 1
50/50
12.495
3150621CHESTS7
50/50
0.422
966871AG1-558 GEN
Solar/Wind Harmer
0.589
966871AG1-558 GEN
Solar/Wind Harmer
0.201
316075AC2-137 C
Solar/Wind Harmer
0.462
3142946ENON
Solar/Wind Harmer
-0.002
944641AF1-129 GEN
Adder
68.324
316240AF1-291 C
Solar/Wind Harmer
0.478
3143526WINTERP
Solar/Wind Harmer
-0.078
316033AB2-134 GEN
Solar/Wind Harmer
4.72
315697AD1-025 GEN
Solar/Wind Harmer
2.96
970657AG2-426 GEN
Solar/Wind Harmer
4.251
970657AG2-426 GEN
Solar/Wind Harmer
0.889
316236AE1-162_GEN
Solar/Wind Harmer
0.405
971223AH1-071 GEN
Solar/Wind Harmer
1.675
316441AF1-014 GEN
Solar/Wind Harmer
0.899
316036AC1-147 C
Solar/Wind Harmer
0.344
3150991CHESPKB
Adder
1.19
3150991CHESPKB
Adder
1.162
316316AC1-027 C
Solar/Wind Harmer
0.39
3142956BIRDNECK
Solar/Wind Harmer
0.681
316185AD1-033 GEN
Solar/Wind Harmer
1.335
3145506HICKORY
Solar/Wind Harmer
-0.05
3145506HICKORY
Solar/Wind Harmer
-0.03
3145506HICKORY
Solar/Wind Harmer
-0.007
316339AD2-160 GEN
Solar/Wind Harmer
0.848
316018AA1-139 ULT2
Solar/Wind Harmer
1.076
316017AA1-139 ULT1
Solar/Wind Harmer
1.016
3137176SLIGO L2192
Solar/Wind Harmer
-0.05
3146456SLIGO L269
Solar/Wind Harmer
1.48
3130086AYDLETT
Solar/Wind Harmer
-0.05
3146386ELIZ CT
Solar/Wind Harmer
-0.012
316431W1029_GEN1
Solar/Wind Harmer
2.225
316433W1029_GEN2
Solar/Wind Harmer
2.225
316468AD1-105 GEN
Solar/Wind Harmer
1.366
3146516WINFALL
Solar/Wind Harmer
-0.012
3146516WINFALL
Solar/Wind Harmer
-0.012
3146516WINFALL
Solar/Wind Harmer
-0.012
3146626S HERTFORD
Solar/Wind Harmer
-0.012
3146626S HERTFORD
Solar/Wind Harmer
-0.012
3144356SAPONY
Solar/Wind Harmer
0.424
315742AE1-103 GEN
Solar/Wind Harmer
1.257
3146376EDENTON
Solar/Wind Harmer
0.353
3146376EDENTON
Solar/Wind Harmer
0.353
316065AD1-022 GEN
Solar/Wind Harmer
5.632
3145893MURPHYS
Solar/Wind Harmer
0.311
3145893MURPHYS
Solar/Wind Harmer
-0.02
3146173TUNIS
Solar/Wind Harmer
-0.011
3146173TUNIS
Solar/Wind Harmer
-0.011
316487AF1-042 GEN
Solar/Wind Harmer
1.441
3142666NORTHAMPTON
Solar/Wind Harmer
-0.011
3142666NORTHAMPTON
Solar/Wind Harmer
-0.011
3142666NORTHAMPTON
Solar/Wind Harmer
-0.011
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
316181AB2-040 GEN
Solar/Wind Harmer
1.488
316426AA2-053 GEN
Solar/Wind Harmer
1.071
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.184
3145593CAROLNA
Solar/Wind Harmer
0.087
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145783HORNRTN
Solar/Wind Harmer
1.242
3145783HORNRTN
Solar/Wind Harmer
0.994
3145783HORNRTN
Solar/Wind Harmer
0.311
3145783HORNRTN
Solar/Wind Harmer
0.124
972185AH1-677 GEN
Adder
5.222
958261AF2-120 GEN
Solar/Wind Harmer
4.015
972187AH1-678 GEN
Adder
2.627
3145933PARMELE
Solar/Wind Harmer
-0.02
3145933PARMELE
Solar/Wind Harmer
-0.01
970933AG2-581 GEN
Solar/Wind Harmer
9.608
316274AC1-208 GEN
Solar/Wind Harmer
1.095
970099AG2-077 GEN
Solar/Wind Harmer
12.213
3145493TOT1
Solar/Wind Harmer
0.15
3145453TOT5
Solar/Wind Harmer
0.09
3145603CNETO
Solar/Wind Harmer
0.06
3150341NORNECKC1
Adder
0.869
3150341NORNECKC1
Adder
0.862
3144293JTRSVLE
Adder
0.258
3144293JTRSVLE
Adder
0.217
971285AH1-108 GEN
50/50
1.171
3150611CHESTG7
50/50
0.919
3150631CHESTG8
50/50
0.904
316312AB1-027
Solar/Wind Harmer
0.666
315976AC1-164 GENA
Solar/Wind Harmer
16.808
316169AC1-164_GENC
Solar/Wind Harmer
14.521
315975AC1-164 GENB
Solar/Wind Harmer
0.497
316132AB2-190 GEN1
Solar/Wind Harmer
1.528
316233AE1-074 FULL
Solar/Wind Harmer
0.403
971281AH1-106 GEN
Solar/Wind Harmer
2.436
971283AH1-107 GEN
Solar/Wind Harmer
2.436
971167AH1-042 GEN
Solar/Wind Harmer
14.288
3142433PROV 92
Adder
0.254
3142433PROV 92
Adder
0.254
316369SG1_INVT
Solar/Wind Harmer
2.615
3143873LANEXA
Solar/Wind Harmer
-0.008
3143316POE
Solar/Wind Harmer
-0.055
972265AH1-717 GEN
Adder
9.57
3151201GRAVEL4
Adder
8.972
3151191GRAVEL3
Adder
8.858
3151211GRAVEL5
Adder
8.858
316314AB2-024 C
Solar/Wind Harmer
1.163
971445AH1-216 GEN
Solar/Wind Harmer
8.338
316059AD1-063 C
Solar/Wind Harmer
0.301
957831AF2-077 GEN
Solar/Wind Harmer
0.399
3138283WHITEMARSH
Solar/Wind Harmer
0.021
315662AE1-191 GEN
Solar/Wind Harmer
1.585
315666AE1-190 GEN
Solar/Wind Harmer
0.396
315833AF1-017_GEN
Solar/Wind Harmer
2.472
316349AD2-085 GEN
Solar/Wind Harmer
1.157
316311AC2-079 GEN
Solar/Wind Harmer
6.56
957601AF2-054 GEN
Solar/Wind Harmer
0.386
3141873WAN 176
Solar/Wind Harmer
-0.003
3152611GOSPORTB
Adder
1.447
3152621GOSPORTC
Adder
1.228
3152601GOSPORTA
Adder
1.133
3151081ELIZAR1
Adder
10.405
3151091ELIZAR2
Adder
10.225
315835AF2-110_GEN
Solar/Wind Harmer
1.575
957871AF2-081 GEN
Solar/Wind Harmer
6.28
316305AF2-043 C
Solar/Wind Harmer
0.378
319010AE1-072 C
Solar/Wind Harmer
2.534
3146406KITTY HAWK
Solar/Wind Harmer
0.01
313526AB2-022
Solar/Wind Harmer
0.335
3146486SUNBURY
Solar/Wind Harmer
-0.012
3146486SUNBURY
Solar/Wind Harmer
-0.012
3141913WHIT STONE
Solar/Wind Harmer
-0.012
316321Z2-027
Solar/Wind Harmer
0.333
3146396TANGLEW
Solar/Wind Harmer
0.227
3145176PASQUOTANK
Solar/Wind Harmer
-0.008
3138133OCRAN
Solar/Wind Harmer
-0.004
316315AB2-025 C
Solar/Wind Harmer
0.328
315814AE2-033 C
Solar/Wind Harmer
11.272
315611Z1-036_GEN2
Solar/Wind Harmer
2.975
3141783LANCAST
Solar/Wind Harmer
-0.007
3141783LANCAST
Solar/Wind Harmer
-0.005
3130156CHOWAN
Solar/Wind Harmer
-0.012
3130156CHOWAN
Solar/Wind Harmer
-0.012
315816AE2-034 GEN
Solar/Wind Harmer
0.939
3130546PLYMOUTH
Solar/Wind Harmer
-0.011
315732AD1-074 GEN1
Solar/Wind Harmer
2.294
315733AD1-074 GEN2
Solar/Wind Harmer
2.294
315735AD1-075 GEN1
Solar/Wind Harmer
1.148
962981AG1-147 GEN
Solar/Wind Harmer
4.945
965291AG1-394 GEN
Solar/Wind Harmer
1.001
3146206CASHIE
Solar/Wind Harmer
-0.011
970601AG2-382 GEN
Solar/Wind Harmer
4.907
316318V4-068
Solar/Wind Harmer
0.278
3145893MURPHYS
Solar/Wind Harmer
-0.03
3145893MURPHYS
Solar/Wind Harmer
-0.011
3145513AHOSKIE
Solar/Wind Harmer
0.096
961941AG1-037 GEN
Solar/Wind Harmer
0.083
3145513AHOSKIE
Solar/Wind Harmer
-0.011
3145683EARLEYS
Solar/Wind Harmer
-0.022
3145683EARLEYS
Solar/Wind Harmer
-0.011
3145683EARLEYS
Solar/Wind Harmer
-0.011
3146043SEABORD
Solar/Wind Harmer
-0.011
315607AA1-063A GEN
Solar/Wind Harmer
1.093
946281AF1-292 GEN
Solar/Wind Harmer
0.242
316087AB2-174 GEN
Solar/Wind Harmer
1.527
315652AC1-086 GEN
Solar/Wind Harmer
12.025
941031AE2-094 GEN
Solar/Wind Harmer
19.997
944011AF1-069 GEN
Solar/Wind Harmer
6.266
3137643SOCKMAN
Solar/Wind Harmer
-0.042
970673AG2-436 GEN
Solar/Wind Harmer
22.112
970673AG2-436 GEN
Solar/Wind Harmer
11.196
3145796HORNRTN
Solar/Wind Harmer
-0.033
3145796HORNRTN
Solar/Wind Harmer
-0.004
972193AH1-681 GEN
Adder
2.137
3146033SCOT NK
Solar/Wind Harmer
-0.042
971967AH1-528 GEN
Solar/Wind Harmer
19.61
970085AG2-068 GEN
Solar/Wind Harmer
6.279
970581AG2-369 GEN
Solar/Wind Harmer
5.4
316005AA1-067
Solar/Wind Harmer
0.203
3145746EVERETS
Solar/Wind Harmer
-0.04
3145746EVERETS
Solar/Wind Harmer
-0.01
3145746EVERETS
Solar/Wind Harmer
-0.01
3145746EVERETS
Solar/Wind Harmer
-0.01
970181AG2-120 GEN
Solar/Wind Harmer
1.318
957861AF2-080 GEN
Solar/Wind Harmer
4.31
970831AG2-522 GEN
Solar/Wind Harmer
4.924
316420AA1-050 GEN
Solar/Wind Harmer
1.115
3145573BETHELC
Solar/Wind Harmer
-0.01
3145573BETHELC
Solar/Wind Harmer
-0.01
316319Z2-044 C
Solar/Wind Harmer
0.534
972205AH1-687 GEN
Adder
3.136
3141426STAFORD
Solar/Wind Helper
0.04
971645AH1-323 GEN
50/50
17.982
3143096IRON208
50/50
0.674
3143096IRON208
50/50
0.66
3150861SPRUNCD
50/50
0.716
3142416OLDCHRC
Solar/Wind Harmer
1.991
316473AC1-191 GEN
Solar/Wind Harmer
2.107
970293AG2-193 GEN
Solar/Wind Harmer
2.228
3142946ENON
Solar/Wind Harmer
-0.005
970133AG2-095 GEN
Solar/Wind Harmer
1.756
965281AG1-393 GEN
Solar/Wind Harmer
1.898
970129AG2-093 GEN
Solar/Wind Harmer
8.532
315839AE2-212 C
Solar/Wind Harmer
0.456
315778AD1-151 GEN
Solar/Wind Harmer
12.847
3142433PROV 92
Adder
0.254
3142433PROV 92
Adder
0.254
316382AG1-145 C
Solar/Wind Harmer
0.433
961611AG1-000B GEN
Solar/Wind Harmer
2.98
315813AE1-149 C
Solar/Wind Harmer
8.808
3151221GRAVEL6
Adder
8.961
3151171GRAVELC
Adder
1.724
970659AG2-427 GEN
Solar/Wind Harmer
1.294
316083AB2-161 GEN
Solar/Wind Harmer
2.219
3144216WINCHST
Adder
0.458
3150921YORKTN3
Adder
3.041
970661AG2-428 GEN
Solar/Wind Harmer
2.539
3145336SMITFLD
Solar/Wind Harmer
-0.005
3141843SHACKLE
Adder
0.607
316203AE2-005 GEN
Solar/Wind Harmer
5.625
3141766HARMONY
Solar/Wind Harmer
1.187
316280AD1-041 GEN
Solar/Wind Harmer
0.991
3144536CHRHLND
Solar/Wind Harmer
-0.002
316156AD2-030 GEN
Solar/Wind Harmer
0.344
3141873WAN 176
Solar/Wind Harmer
1.53
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
10.538
315773AC2-141 GEN
Solar/Wind Harmer
5.304
944581AF1-123 GEN
Solar/Wind Harmer
57.445
944601AF1-125 GEN
Solar/Wind Harmer
56.548
3146456SLIGO L269
Solar/Wind Harmer
-0.012
971153AH1-033 GEN
Solar/Wind Harmer
1.528
316320Y1-086
Solar/Wind Harmer
0.727
316435W1029_GEN3
Solar/Wind Harmer
2.225
971781AH1-399 GEN
Solar/Wind Harmer
0.756
3146516WINFALL
Solar/Wind Harmer
-0.012
3145273HOLLAND
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.012
3146376EDENTON
Solar/Wind Harmer
-0.012
315614AA2-178 GEN
Solar/Wind Harmer
1.252
971157AH1-035 GEN
Solar/Wind Harmer
1.423
315737AD1-076 GEN
Solar/Wind Harmer
2.156
316313AB2-026
Solar/Wind Harmer
0.306
316258AE1-075 C
Solar/Wind Harmer
0.275
316405AF2-144 C
Solar/Wind Harmer
0.291
3143336POWHATN
Solar/Wind Harmer
1.144
3156081AA2-088 GEN
Solar/Wind Harmer
3.68
962971AG1-146 GEN
Solar/Wind Harmer
2.119
3146206CASHIE
Solar/Wind Harmer
-0.011
316365GEN2_N
Solar/Wind Harmer
0.754
3145893MURPHYS
Solar/Wind Harmer
0.078
3145893MURPHYS
Solar/Wind Harmer
-0.011
957521AF2-046 GEN
Solar/Wind Harmer
8.766
961681AG1-008 GEN
Solar/Wind Harmer
8.766
3146173TUNIS
Solar/Wind Harmer
-0.011
3156021HOLLOMANSOL
Solar/Wind Harmer
1.487
316463AE2-346 GEN
Solar/Wind Harmer
0.178
316140AB2-099
Solar/Wind Harmer
0.074
962331AG1-082 GEN
Solar/Wind Harmer
1.373
316484AD2-074 GEN
Solar/Wind Harmer
2.755
970009AG2-005 GEN
Solar/Wind Harmer
1.368
3146263WOODLND
Solar/Wind Harmer
-0.011
966621AG1-532 GEN
Solar/Wind Harmer
0.219
3145963POPLR C
Solar/Wind Harmer
-0.011
3142666NORTHAMPTON
Solar/Wind Harmer
-0.011
316317KELFORD C
Solar/Wind Harmer
0.504
3145823KELFORD
Solar/Wind Harmer
-0.011
313506AB2-031 GEN
Solar/Wind Harmer
0.858
3145796HORNRTN
Solar/Wind Harmer
-0.042
3145796HORNRTN
Solar/Wind Harmer
-0.01
972255AH1-712 GEN
Adder
47.827
316404AE1-155 C
Solar/Wind Harmer
1.999
3147043LAWRENC
Solar/Wind Harmer
-0.006
3145933PARMELE
Solar/Wind Harmer
-0.01
966801AG1-551 GEN
Solar/Wind Harmer
1.283
316210AC1-098 GEN
Solar/Wind Harmer
1.607
970917AG2-570 GEN
Solar/Wind Harmer
25.195
3145746EVERETS
Solar/Wind Harmer
-0.01
3145746EVERETS
Solar/Wind Harmer
-0.01
315724AD1-057 GEN
Solar/Wind Harmer
0.572
316327AA2-057 GEN
Solar/Wind Harmer
0.995
3146073TAR RVR
Solar/Wind Harmer
-0.01
3146083TARBORO
Solar/Wind Harmer
-0.01
3146233WITAKRS
Solar/Wind Harmer
0.202
3146233WITAKRS
Solar/Wind Harmer
-0.007
3138543CONSLDL
Solar/Wind Harmer
-0.006
3150351NORNECKC2
Adder
0.841
3144293JTRSVLE
Adder
0.258
966881AG1-559 GEN
Solar/Wind Helper
1.258
NYPJM->LTFIMP_NY
CLTF
1.203
LGEELTFEXP_LGEE->PJM
CLTF
1.109
WECLTFEXP_WEC->PJM
CLTF
0.572
LAGNLTFEXP_LAGN->PJM
CLTF
4.914
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.542
TVALTFEXP_TVA->PJM
CLTF
2.484
CBM West 1LTFEXP_CBM-W1->PJM
CBM
20.492
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.74
MECLTFEXP_MEC->PJM
CLTF
2.841
SIGELTFEXP_SIGE->PJM
CLTF
0.088
CPLELTFEXP_CPLE->PJM
CLTF
5.473
CBM West 2LTFEXP_CBM-W2->PJM
CBM
27.827

Details for 6ELMONT-6HANOVER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6ELMONT-6HANOVER 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.87 %
Rating:1123.3 MVA
Rating Type:B
MVA to Mitigate:1189.21
MW Contribution:52.28
Bus #Bus NameTypeMW Contribution
971645AH1-323 GEN
50/50
17.435
3143096IRON208
50/50
0.63
3143096IRON208
50/50
0.617
316473AC1-191 GEN
Solar/Wind Harmer
0.571
3142416OLDCHRC
Solar/Wind Harmer
1.631
970293AG2-193 GEN
Solar/Wind Harmer
1.601
3150861SPRUNCD
Adder
0.622
3142946ENON
Solar/Wind Harmer
0.045
970133AG2-095 GEN
Solar/Wind Harmer
1.231
970129AG2-093 GEN
Solar/Wind Harmer
7.489
965281AG1-393 GEN
Solar/Wind Harmer
1.32
315839AE2-212 C
Solar/Wind Harmer
0.001
3142433PROV 92
Adder
0.237
3142433PROV 92
Adder
0.237
315778AD1-151 GEN
Solar/Wind Harmer
9.667
316382AG1-145 C
Solar/Wind Harmer
0.001
961611AG1-000B GEN
Solar/Wind Harmer
3.052
315813AE1-149 C
Solar/Wind Harmer
6.039
3151221GRAVEL6
Adder
8.11
3151171GRAVELC
Adder
1.56
3141766HARMONY
Solar/Wind Harmer
1.48
3141843SHACKLE
Adder
0.567
316203AE2-005 GEN
Solar/Wind Harmer
0
3144216WINCHST
Adder
0.416
3150921YORKTN3
Adder
2.767
970659AG2-427 GEN
Solar/Wind Harmer
1.163
316083AB2-161 GEN
Solar/Wind Harmer
0.001
316280AD1-041 GEN
Solar/Wind Harmer
0.002
971781AH1-399 GEN
Solar/Wind Harmer
0.143
970661AG2-428 GEN
Solar/Wind Harmer
2.277
3145336SMITFLD
Solar/Wind Harmer
0.043
316156AD2-030 GEN
Solar/Wind Harmer
0.079
3141873WAN 176
Solar/Wind Harmer
1.904
3144536CHRHLND
Solar/Wind Harmer
0.015
3144873MCLAUGH
Solar/Wind Harmer
0.003
3151101ELIZAR3
Adder
9.352
315773AC2-141 GEN
Solar/Wind Harmer
3.646
944581AF1-123 GEN
Solar/Wind Harmer
22.395
944601AF1-125 GEN
Solar/Wind Harmer
22.05
3146456SLIGO L269
Solar/Wind Harmer
0.099
971153AH1-033 GEN
Solar/Wind Harmer
1.142
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.096
3145273HOLLAND
Solar/Wind Harmer
0.072
3146626S HERTFORD
Solar/Wind Harmer
0.096
962971AG1-146 GEN
Solar/Wind Harmer
1.516
3146376EDENTON
Solar/Wind Harmer
0.093
970009AG2-005 GEN
Solar/Wind Harmer
0.687
315614AA2-178 GEN
Solar/Wind Harmer
0.521
971157AH1-035 GEN
Solar/Wind Harmer
1.07
315737AD1-076 GEN
Solar/Wind Harmer
1.143
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3146206CASHIE
Solar/Wind Harmer
0.088
972255AH1-712 GEN
Adder
44.866
316404AE1-155 C
Solar/Wind Harmer
0.02
3145893MURPHYS
Solar/Wind Harmer
0.146
3145893MURPHYS
Solar/Wind Harmer
0.087
957521AF2-046 GEN
Solar/Wind Harmer
6.466
961681AG1-008 GEN
Solar/Wind Harmer
6.466
316365GEN2_N
Solar/Wind Harmer
0.195
316313AB2-026
Solar/Wind Harmer
0.055
316258AE1-075 C
Solar/Wind Harmer
0.065
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
1.308
3146173TUNIS
Solar/Wind Harmer
0.086
3156021HOLLOMANSOL
Solar/Wind Harmer
0.391
316463AE2-346 GEN
Solar/Wind Harmer
0.074
316140AB2-099
Solar/Wind Harmer
0.031
962331AG1-082 GEN
Solar/Wind Harmer
0.914
3146263WOODLND
Solar/Wind Harmer
0.084
3145963POPLR C
Solar/Wind Harmer
0.084
3142666NORTHAMPTON
Solar/Wind Harmer
0.083
316317KELFORD C
Solar/Wind Harmer
0.008
3145823KELFORD
Solar/Wind Harmer
0.083
313506AB2-031 GEN
Solar/Wind Harmer
0.255
3145796HORNRTN
Solar/Wind Harmer
0.326
3145796HORNRTN
Solar/Wind Harmer
0.082
3145933PARMELE
Solar/Wind Harmer
0.08
966801AG1-551 GEN
Solar/Wind Harmer
0.93
3147043LAWRENC
Solar/Wind Harmer
0.048
316210AC1-098 GEN
Solar/Wind Harmer
0.737
3150351NORNECKC2
Adder
0.804
3145746EVERETS
Solar/Wind Harmer
0.078
3145746EVERETS
Solar/Wind Harmer
0.078
315724AD1-057 GEN
Solar/Wind Harmer
0.289
316327AA2-057 GEN
Solar/Wind Harmer
0.115
970917AG2-570 GEN
Solar/Wind Harmer
6.696
3146073TAR RVR
Solar/Wind Harmer
0.075
3146083TARBORO
Solar/Wind Harmer
0.075
3146233WITAKRS
Solar/Wind Harmer
0.375
3146233WITAKRS
Solar/Wind Harmer
0.051
3138543CONSLDL
Solar/Wind Harmer
0.049
961601AG1-000A GEN
Solar/Wind Harmer
5.215
3145543BTLEBRO
Solar/Wind Harmer
0.073
3145543BTLEBRO
Solar/Wind Harmer
0.073
971623AH1-311 GEN
Solar/Wind Harmer
0.147
316478AD1-087 GEN
Solar/Wind Harmer
0.249
316486AD2-202 GEN
Solar/Wind Harmer
0.073
316131AB2-060 GEN
Solar/Wind Harmer
0.221
964241AG1-285 GEN
Solar/Wind Harmer
4.675
315785AD2-033 C
Solar/Wind Harmer
0.567
970257AG2-171 GEN
Solar/Wind Harmer
2.225
959311AF2-222 GEN
Solar/Wind Harmer
6.171
970909AG2-566 GEN
Solar/Wind Harmer
0.738
963181AG1-167 GEN
Solar/Wind Harmer
0.275
3144293JTRSVLE
Adder
0.219
3147133PAMPLIN
Solar/Wind Harmer
0.215
971193AH1-056 GEN
Solar/Wind Harmer
4.17
942461AE2-259 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.04
3146776BUCKING
Solar/Wind Harmer
0.023
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
2.742
971683AH1-343 GEN
Solar/Wind Harmer
2.232
316283AC2-100 C
Solar/Wind Harmer
0.116
970221AG2-151 GEN
Solar/Wind Harmer
3.149
966881AG1-559 GEN
Solar/Wind Helper
1.213
3150611CHESTG7
50/50
0.857
3150631CHESTG8
50/50
0.843
316312AB1-027
Solar/Wind Harmer
0.301
971285AH1-108 GEN
Adder
1.017
315976AC1-164 GENA
Solar/Wind Harmer
13.778
316169AC1-164_GENC
Solar/Wind Harmer
11.903
315975AC1-164 GENB
Solar/Wind Harmer
0.408
971167AH1-042 GEN
Solar/Wind Harmer
10.969
316132AB2-190 GEN1
Solar/Wind Harmer
0.662
3142433PROV 92
Adder
0.237
3142433PROV 92
Adder
0.237
316233AE1-074 FULL
Solar/Wind Harmer
0.096
971281AH1-106 GEN
Solar/Wind Harmer
1.657
971283AH1-107 GEN
Solar/Wind Harmer
1.657
316369SG1_INVT
Solar/Wind Harmer
0.004
3143873LANEXA
Solar/Wind Harmer
0.07
316314AB2-024 C
Solar/Wind Harmer
0
3143316POE
Solar/Wind Harmer
0.442
972265AH1-717 GEN
Adder
8.661
3151201GRAVEL4
Adder
8.12
3151191GRAVEL3
Adder
8.017
3151211GRAVEL5
Adder
8.017
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
3.288
315662AE1-191 GEN
Solar/Wind Harmer
0.004
315666AE1-190 GEN
Solar/Wind Harmer
0.001
3138283WHITEMARSH
Solar/Wind Harmer
0.025
971445AH1-216 GEN
Solar/Wind Harmer
7.593
3141873WAN 176
Solar/Wind Harmer
0.021
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.071
316311AC2-079 GEN
Solar/Wind Harmer
2.965
3141913WHIT STONE
Solar/Wind Harmer
0.103
3138133OCRAN
Solar/Wind Harmer
0.031
3152611GOSPORTB
Adder
1.285
3152621GOSPORTC
Adder
1.09
3152601GOSPORTA
Adder
1.006
3151081ELIZAR1
Adder
9.234
3151091ELIZAR2
Adder
9.074
3141783LANCAST
Solar/Wind Harmer
0.06
3141783LANCAST
Solar/Wind Harmer
0.04
315835AF2-110_GEN
Solar/Wind Harmer
0.683
316305AF2-043 C
Solar/Wind Harmer
0.001
957871AF2-081 GEN
Solar/Wind Harmer
4.929
319010AE1-072 C
Solar/Wind Harmer
0.497
3146406KITTY HAWK
Solar/Wind Harmer
0.012
313526AB2-022
Solar/Wind Harmer
0.053
3146486SUNBURY
Solar/Wind Harmer
0.098
3146486SUNBURY
Solar/Wind Harmer
0.098
316321Z2-027
Solar/Wind Harmer
0.018
3146396TANGLEW
Solar/Wind Harmer
0.268
3145176PASQUOTANK
Solar/Wind Harmer
0.06
962981AG1-147 GEN
Solar/Wind Harmer
3.537
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
316315AB2-025 C
Solar/Wind Harmer
0.076
315814AE2-033 C
Solar/Wind Harmer
7.456
3130156CHOWAN
Solar/Wind Harmer
0.093
3130156CHOWAN
Solar/Wind Harmer
0.093
970327AG2-215 GEN
Solar/Wind Harmer
3.018
315816AE2-034 GEN
Solar/Wind Harmer
0.39
3130546PLYMOUTH
Solar/Wind Harmer
0.089
315732AD1-074 GEN1
Solar/Wind Harmer
0.51
315733AD1-074 GEN2
Solar/Wind Harmer
0.51
315735AD1-075 GEN1
Solar/Wind Harmer
0.255
965291AG1-394 GEN
Solar/Wind Harmer
0.392
3146206CASHIE
Solar/Wind Harmer
0.088
970601AG2-382 GEN
Solar/Wind Harmer
3.275
972193AH1-681 GEN
Adder
2.005
3145893MURPHYS
Solar/Wind Harmer
0.235
3145893MURPHYS
Solar/Wind Harmer
0.087
3145513AHOSKIE
Solar/Wind Harmer
0.179
3145513AHOSKIE
Solar/Wind Harmer
0.086
3145683EARLEYS
Solar/Wind Harmer
0.17
3145683EARLEYS
Solar/Wind Harmer
0.085
3145683EARLEYS
Solar/Wind Harmer
0.085
3146043SEABORD
Solar/Wind Harmer
0.084
315607AA1-063A GEN
Solar/Wind Harmer
0.172
315652AC1-086 GEN
Solar/Wind Harmer
9.127
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.328
3145796HORNRTN
Solar/Wind Harmer
0.261
3145796HORNRTN
Solar/Wind Harmer
0.033
3146033SCOT NK
Solar/Wind Harmer
0.324
941031AE2-094 GEN
Solar/Wind Harmer
14.626
944011AF1-069 GEN
Solar/Wind Harmer
4.779
3141813NORNECK
Solar/Wind Harmer
0.079
970673AG2-436 GEN
Solar/Wind Harmer
16.734
970673AG2-436 GEN
Solar/Wind Harmer
11.156
316005AA1-067
Solar/Wind Harmer
0.084
3145746EVERETS
Solar/Wind Harmer
0.31
3145746EVERETS
Solar/Wind Harmer
0.078
3145746EVERETS
Solar/Wind Harmer
0.078
3145746EVERETS
Solar/Wind Harmer
0.078
970181AG2-120 GEN
Solar/Wind Harmer
0.97
971967AH1-528 GEN
Solar/Wind Harmer
12.447
957861AF2-080 GEN
Solar/Wind Harmer
3.293
316420AA1-050 GEN
Solar/Wind Harmer
0.002
970831AG2-522 GEN
Solar/Wind Harmer
3.224
970085AG2-068 GEN
Solar/Wind Harmer
4.006
970581AG2-369 GEN
Solar/Wind Harmer
3.445
3145573BETHELC
Solar/Wind Harmer
0.075
3145573BETHELC
Solar/Wind Harmer
0.075
316319Z2-044 C
Solar/Wind Harmer
0
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
971443AH1-215 GEN
Solar/Wind Harmer
1.169
3144303KENBRDG
Solar/Wind Harmer
0.056
970683AG2-441 GEN
Solar/Wind Harmer
4.609
970681AG2-440 GEN
Solar/Wind Harmer
3.687
946301AF1-294 GEN
Solar/Wind Harmer
1.357
961791AG1-021 GEN
Solar/Wind Harmer
0.66
315657AE1-056 GEN
Solar/Wind Harmer
2.362
316118AC1-105 GEN
Solar/Wind Harmer
0.169
970285AG2-188 GEN
Solar/Wind Harmer
5.153
971845AH1-439 GEN
Solar/Wind Harmer
2.936
3147173SINAI
Solar/Wind Harmer
0.064
3147243WELCO
Solar/Wind Harmer
0.04
972205AH1-687 GEN
Adder
2.638
970865AG2-541 GEN
Solar/Wind Harmer
2.043
971447AH1-217 GEN
Solar/Wind Harmer
1.766
3141426STAFORD
Solar/Wind Helper
0.033
3143096IRON208
50/50
0.63
3150641CHESTS8
50/50
0.434
3142416OLDCHRC
Solar/Wind Harmer
0.437
3142416OLDCHRC
Solar/Wind Harmer
0.168
3142543TWELFTH
Solar/Wind Harmer
0.014
944631AF1-128 GEN
Adder
64.319
3150851SPRUNCC
Adder
0.622
315671AE2-027_GEN
Solar/Wind Harmer
8.029
970129AG2-093 GEN
Solar/Wind Harmer
3.524
316458AB2-190 GEN2
Solar/Wind Harmer
0.662
3142433PROV 92
Solar/Wind Harmer
0.488
3142433PROV 92
Adder
0.237
3142433PROV 92
Adder
0.237
971069AG2-661 GEN
Solar/Wind Harmer
2.148
3143526WINTERP
Solar/Wind Harmer
0.621
316159AE1-175 C
Solar/Wind Harmer
0.102
971647AH1-324 GEN
Solar/Wind Harmer
4.981
961611AG1-000B GEN
Solar/Wind Harmer
6.001
3151171GRAVELC
Adder
1.187
971317AH1-138 GEN
Solar/Wind Harmer
0.83
3141766HARMONY
Solar/Wind Harmer
0.022
971777AH1-397 GEN
Solar/Wind Harmer
0.293
3141843SHACKLE
Adder
0.567
3138126ROCKLANDING
Solar/Wind Harmer
0.051
970659AG2-427 GEN
Solar/Wind Harmer
5.319
316381AD1-082 GEN
Solar/Wind Harmer
0.114
970661AG2-428 GEN
Solar/Wind Harmer
10.707
3145336SMITFLD
Solar/Wind Harmer
0.43
3143226MDLTHAN
Solar/Wind Harmer
0.103
316072AD1-144
Solar/Wind Harmer
0.037
3138133OCRAN
Solar/Wind Harmer
0.061
316375AC2-012 GEN
Solar/Wind Harmer
0.003
3150981CHESPKA
Adder
1.26
316294AC1-161 GEN
Solar/Wind Harmer
1.73
316093AE2-104_GEN
Solar/Wind Harmer
1.674
944591AF1-124 GEN
Solar/Wind Harmer
22.475
316388AE2-253 GEN
Solar/Wind Harmer
0.31
316246AF1-032 C
Solar/Wind Harmer
0.045
3146456SLIGO L269
Solar/Wind Harmer
0.099
3146516WINFALL
Solar/Wind Harmer
0.312
3146516WINFALL
Solar/Wind Harmer
0.096
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.093
3145663CRESWEL
Solar/Wind Harmer
0.255
971163AH1-040 GEN
Solar/Wind Harmer
7.278
962861AG1-135 GEN
Solar/Wind Harmer
2.836
939411AE1-173 GEN
Solar/Wind Harmer
37.741
3146206CASHIE
Solar/Wind Harmer
0.088
971547AH1-271 GEN
Solar/Wind Harmer
1.872
972277AH1-723 GEN
Adder
52.282
3145893MURPHYS
Solar/Wind Harmer
0.349
3145893MURPHYS
Solar/Wind Harmer
0.388
316023GEN1_S
Solar/Wind Harmer
0.195
3143336POWHATN
Solar/Wind Harmer
1.539
3146173TUNIS
Solar/Wind Harmer
0.086
3145683EARLEYS
Solar/Wind Harmer
0.085
940641AE2-051 GEN
Solar/Wind Harmer
6.781
3146263WOODLND
Solar/Wind Harmer
0.084
3141726DUNNSVL
Solar/Wind Harmer
0.336
3145963POPLR C
Solar/Wind Harmer
0.084
960081AF2-299 GEN
Solar/Wind Harmer
0.803
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3145823KELFORD
Solar/Wind Harmer
0.083
316011AB1-132 GEN
Solar/Wind Harmer
1.509
962571AG1-106 GEN
Solar/Wind Harmer
1.181
316336AC2-165 C
Solar/Wind Harmer
0.003
316190AA2-174 GEN
Solar/Wind Harmer
0
3145796HORNRTN
Solar/Wind Harmer
0.269
3145796HORNRTN
Solar/Wind Harmer
0.082
3145783HORNRTN
Solar/Wind Harmer
0.081
971795AH1-408 GEN
Solar/Wind Harmer
5.392
3146293MARTNCO
Solar/Wind Harmer
0.074
3147043LAWRENC
Adder
0.72
316212AC1-099_GEN
Solar/Wind Harmer
0.411
3150351NORNECKC2
Adder
0.791
3145746EVERETS
Solar/Wind Harmer
0.078
3145746EVERETS
Solar/Wind Harmer
0.078
315722AD1-056 GEN
Solar/Wind Harmer
0.488
316494AC1-189 GEN
Solar/Wind Harmer
0.258
970919AG2-571 GEN
Solar/Wind Harmer
2.678
970087AG2-069 GEN
Solar/Wind Harmer
6.009
961671AG1-007 GEN
Solar/Wind Harmer
0.011
3146083TARBORO
Solar/Wind Harmer
0.075
3145493TOT1
Solar/Wind Harmer
0.333
316129AC1-054 GEN
Solar/Wind Harmer
0.282
3146233WITAKRS
Solar/Wind Harmer
0.297
971065AG2-659 GEN
Solar/Wind Harmer
3.171
316359AB2-059 GEN
Solar/Wind Harmer
0.263
316049AB1-081 GEN
Solar/Wind Harmer
0.419
3145543BTLEBRO
Solar/Wind Harmer
0.073
3145543BTLEBRO
Solar/Wind Harmer
0.059
3142053HEARTS
Solar/Wind Harmer
0.129
957481AF2-042 GEN
Solar/Wind Harmer
19.524
315693AD1-088 GEN
Solar/Wind Harmer
3.47
962491AG1-098 GEN
Solar/Wind Harmer
4.117
970937AG2-583 GEN
Solar/Wind Harmer
4.364
316237AB2-079_GEN
Solar/Wind Harmer
0.001
970685AG2-442 GEN
Solar/Wind Harmer
5.162
963171AG1-166 GEN
Solar/Wind Harmer
0.367
971563AH1-280 GEN
Solar/Wind Harmer
0.733
3144293JTRSVLE
Adder
0.219
315687AD1-152 GEN
Solar/Wind Harmer
0.002
3146926FARMVIL
Solar/Wind Harmer
0.04
970401AG2-262 GEN
Solar/Wind Harmer
0.392
316337AD2-073 GEN
Solar/Wind Harmer
0.057
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.026
316003AC1-222 GEN
Solar/Wind Harmer
0.002
972003AH1-546 GEN
Solar/Wind Harmer
2.646
971377AH1-170 GEN
Solar/Wind Harmer
0.63
3147623JAMES R
Solar/Wind Harmer
0.137
3142296MT RD221
50/50
0.632
3142366NRTHEST
50/50
0.551
3150691DARBY 3
50/50
11.896
3150701DARBY 4
50/50
11.869
3150681DARBY 2
50/50
11.855
3150671DARBY 1
50/50
11.841
3150621CHESTS7
50/50
0.394
966871AG1-558 GEN
Solar/Wind Harmer
0.195
316075AC2-137 C
Solar/Wind Harmer
0.04
3142946ENON
Solar/Wind Harmer
0.013
944641AF1-129 GEN
Adder
63.125
316240AF1-291 C
Solar/Wind Harmer
0.001
3143526WINTERP
Solar/Wind Harmer
0.621
316033AB2-134 GEN
Solar/Wind Harmer
0.007
315697AD1-025 GEN
Solar/Wind Harmer
0.134
316468AD1-105 GEN
Solar/Wind Harmer
-0.035
970657AG2-426 GEN
Solar/Wind Harmer
3.808
970657AG2-426 GEN
Solar/Wind Harmer
0.798
316236AE1-162_GEN
Solar/Wind Harmer
0.001
971223AH1-071 GEN
Solar/Wind Harmer
1.1
316036AC1-147 C
Solar/Wind Harmer
0.019
3150991CHESPKB
Adder
1.057
3150991CHESPKB
Adder
1.031
316316AC1-027 C
Solar/Wind Harmer
0.096
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.003
3145506HICKORY
Solar/Wind Harmer
0.398
3145506HICKORY
Solar/Wind Harmer
0.239
3145506HICKORY
Solar/Wind Harmer
0.06
316339AD2-160 GEN
Solar/Wind Harmer
0.161
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.055
3137176SLIGO L2192
Solar/Wind Harmer
0.393
3146456SLIGO L269
Solar/Wind Harmer
1.748
3130086AYDLETT
Solar/Wind Harmer
0.394
3146386ELIZ CT
Solar/Wind Harmer
0.098
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.096
3146516WINFALL
Solar/Wind Harmer
0.096
3146516WINFALL
Solar/Wind Harmer
0.096
3146626S HERTFORD
Solar/Wind Harmer
0.096
3146626S HERTFORD
Solar/Wind Harmer
0.096
3144356SAPONY
Solar/Wind Harmer
0.792
315742AE1-103 GEN
Solar/Wind Harmer
0.001
3146376EDENTON
Solar/Wind Harmer
0.415
3146376EDENTON
Solar/Wind Harmer
0.415
316065AD1-022 GEN
Solar/Wind Harmer
4.058
958261AF2-120 GEN
Solar/Wind Harmer
2.891
3145893MURPHYS
Solar/Wind Harmer
0.583
3145893MURPHYS
Solar/Wind Harmer
0.157
3146173TUNIS
Solar/Wind Harmer
0.086
3146173TUNIS
Solar/Wind Harmer
0.086
3142666NORTHAMPTON
Solar/Wind Harmer
0.083
3142666NORTHAMPTON
Solar/Wind Harmer
0.083
3142666NORTHAMPTON
Solar/Wind Harmer
0.083
3142666NORTHAMPTON
Solar/Wind Harmer
0.05
316181AB2-040 GEN
Solar/Wind Harmer
0.12
316426AA2-053 GEN
Solar/Wind Harmer
0.278
3145796HORNRTN
Solar/Wind Harmer
0.245
3145593CAROLNA
Solar/Wind Harmer
0.082
3145593CAROLNA
Solar/Wind Harmer
0.082
966811AG1-552 GEN
Solar/Wind Harmer
0.885
3145593CAROLNA
Solar/Wind Harmer
0.102
3145783HORNRTN
Solar/Wind Harmer
1.442
3145783HORNRTN
Solar/Wind Harmer
1.154
3145783HORNRTN
Solar/Wind Harmer
0.361
3145783HORNRTN
Solar/Wind Harmer
0.144
3145933PARMELE
Solar/Wind Harmer
0.16
3145933PARMELE
Solar/Wind Harmer
0.08
316077AC2-138 C
Solar/Wind Harmer
0
3150341NORNECKC1
Adder
0.831
3150341NORNECKC1
Adder
0.824
316274AC1-208 GEN
Solar/Wind Harmer
0.408
972185AH1-677 GEN
Adder
4.375
972187AH1-678 GEN
Adder
2.202
970933AG2-581 GEN
Solar/Wind Harmer
6.122
3145493TOT1
Solar/Wind Harmer
0.174
3145453TOT5
Solar/Wind Harmer
0.104
3145603CNETO
Solar/Wind Harmer
0.07
961601AG1-000A GEN
Solar/Wind Harmer
1.304
316263AC1-034 GEN
Solar/Wind Harmer
2.784
970099AG2-077 GEN
Solar/Wind Harmer
7.81
939181AE1-148 GEN
Solar/Wind Harmer
3.417
313527AB2-043 GEN
Solar/Wind Harmer
0.001
971741AH1-377 GEN
Solar/Wind Harmer
6.934
316034AC1-036 C
Solar/Wind Harmer
0.005
970323AG2-213 GEN
Solar/Wind Harmer
2.967
971775AH1-396 GEN
Solar/Wind Harmer
0.111
970301AG2-198 GEN
Solar/Wind Harmer
2.952
958211AF2-115 GEN
Solar/Wind Harmer
0.825
963191AG1-168 GEN
Solar/Wind Harmer
0.275
3144293JTRSVLE
Adder
0.219
3144293JTRSVLE
Adder
0.184
3147133PAMPLIN
Solar/Wind Harmer
0.068
3147133PAMPLIN
Solar/Wind Harmer
0.055
962561AG1-105 GEN
Solar/Wind Harmer
3.235
964791AG1-342 GEN
Solar/Wind Harmer
1.284
3146843MT LREL
Solar/Wind Harmer
0.067
3146843MT LREL
Solar/Wind Harmer
0.067
3146776BUCKING
Solar/Wind Harmer
0.258
3146776BUCKING
Solar/Wind Harmer
0.021
316222AC1-221 GEN
Solar/Wind Harmer
0.248
971489AH1-241 GEN
Solar/Wind Harmer
3.149
NYPJM->LTFIMP_NY
CLTF
0.971
LGEELTFEXP_LGEE->PJM
CLTF
0.994
WECLTFEXP_WEC->PJM
CLTF
0.514
LAGNLTFEXP_LAGN->PJM
CLTF
4.321
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.837
TVALTFEXP_TVA->PJM
CLTF
2.185
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.477
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.705
MECLTFEXP_MEC->PJM
CLTF
2.537
SIGELTFEXP_SIGE->PJM
CLTF
0.079
CPLELTFEXP_CPLE->PJM
CLTF
4.707
CBM West 2LTFEXP_CBM-W2->PJM
CBM
24.626

Details for 6FOUR RIVERS-6STJOHN 230.0 kV Ckt 1 line l/o DVP_P4-2: 574T575_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FOUR RIVERS-6STJOHN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 574T575_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:188.55 %
Rating:1360.0 MVA
Rating Type:C
MVA to Mitigate:2564.3
MW Contribution:51.71
Bus #Bus NameTypeMW Contribution
972189AH1-679 GEN
50/50
6.498
316312AB1-027
Solar/Wind Harmer
0.64
971285AH1-108 GEN
Adder
1.053
315976AC1-164 GENA
Solar/Wind Harmer
16.007
316169AC1-164_GENC
Solar/Wind Harmer
13.829
315975AC1-164 GENB
Solar/Wind Harmer
0.474
316132AB2-190 GEN1
Solar/Wind Harmer
1.451
316233AE1-074 FULL
Solar/Wind Harmer
0.383
971281AH1-106 GEN
Solar/Wind Harmer
2.312
971283AH1-107 GEN
Solar/Wind Harmer
2.312
971167AH1-042 GEN
Solar/Wind Harmer
13.558
3142433PROV 92
Adder
0.241
3142433PROV 92
Adder
0.241
316369SG1_INVT
Solar/Wind Harmer
2.48
3143873LANEXA
Solar/Wind Harmer
-0.008
3143316POE
Solar/Wind Harmer
-0.052
972265AH1-717 GEN
Adder
9.046
3151201GRAVEL4
Adder
8.48
3151191GRAVEL3
Adder
8.373
3151211GRAVEL5
Adder
8.373
316314AB2-024 C
Solar/Wind Harmer
1.099
971445AH1-216 GEN
Solar/Wind Harmer
7.869
316059AD1-063 C
Solar/Wind Harmer
0.284
957831AF2-077 GEN
Solar/Wind Harmer
0.376
3138283WHITEMARSH
Solar/Wind Harmer
0.019
315662AE1-191 GEN
Solar/Wind Harmer
1.494
315666AE1-190 GEN
Solar/Wind Harmer
0.373
315833AF1-017_GEN
Solar/Wind Harmer
2.328
316349AD2-085 GEN
Solar/Wind Harmer
1.09
316311AC2-079 GEN
Solar/Wind Harmer
6.177
957601AF2-054 GEN
Solar/Wind Harmer
0.363
3141873WAN 176
Solar/Wind Harmer
-0.002
3152611GOSPORTB
Adder
1.361
3152621GOSPORTC
Adder
1.155
3152601GOSPORTA
Adder
1.066
3151081ELIZAR1
Adder
9.787
3151091ELIZAR2
Adder
9.617
315835AF2-110_GEN
Solar/Wind Harmer
1.48
957871AF2-081 GEN
Solar/Wind Harmer
5.901
316305AF2-043 C
Solar/Wind Harmer
0.356
319010AE1-072 C
Solar/Wind Harmer
2.38
3146406KITTY HAWK
Solar/Wind Harmer
0.01
313526AB2-022
Solar/Wind Harmer
0.314
3146486SUNBURY
Solar/Wind Harmer
-0.012
3146486SUNBURY
Solar/Wind Harmer
-0.012
3141913WHIT STONE
Solar/Wind Harmer
-0.012
316321Z2-027
Solar/Wind Harmer
0.313
3146396TANGLEW
Solar/Wind Harmer
0.213
3145176PASQUOTANK
Solar/Wind Harmer
-0.007
3138133OCRAN
Solar/Wind Harmer
-0.003
316315AB2-025 C
Solar/Wind Harmer
0.307
315814AE2-033 C
Solar/Wind Harmer
10.566
315611Z1-036_GEN2
Solar/Wind Harmer
2.787
3141783LANCAST
Solar/Wind Harmer
-0.007
3141783LANCAST
Solar/Wind Harmer
-0.004
3130156CHOWAN
Solar/Wind Harmer
-0.011
3130156CHOWAN
Solar/Wind Harmer
-0.011
315816AE2-034 GEN
Solar/Wind Harmer
0.877
3130546PLYMOUTH
Solar/Wind Harmer
-0.011
315732AD1-074 GEN1
Solar/Wind Harmer
2.141
315733AD1-074 GEN2
Solar/Wind Harmer
2.141
315735AD1-075 GEN1
Solar/Wind Harmer
1.071
962981AG1-147 GEN
Solar/Wind Harmer
4.613
965291AG1-394 GEN
Solar/Wind Harmer
0.934
3146206CASHIE
Solar/Wind Harmer
-0.01
970601AG2-382 GEN
Solar/Wind Harmer
4.576
316318V4-068
Solar/Wind Harmer
0.259
3145893MURPHYS
Solar/Wind Harmer
-0.028
3145893MURPHYS
Solar/Wind Harmer
-0.01
3145513AHOSKIE
Solar/Wind Harmer
0.089
961941AG1-037 GEN
Solar/Wind Harmer
0.077
3145513AHOSKIE
Solar/Wind Harmer
-0.01
3145683EARLEYS
Solar/Wind Harmer
-0.02
3145683EARLEYS
Solar/Wind Harmer
-0.01
3145683EARLEYS
Solar/Wind Harmer
-0.01
3146043SEABORD
Solar/Wind Harmer
-0.01
315607AA1-063A GEN
Solar/Wind Harmer
1.017
946281AF1-292 GEN
Solar/Wind Harmer
0.225
316087AB2-174 GEN
Solar/Wind Harmer
1.419
315652AC1-086 GEN
Solar/Wind Harmer
11.172
941031AE2-094 GEN
Solar/Wind Harmer
18.575
944011AF1-069 GEN
Solar/Wind Harmer
5.82
3137643SOCKMAN
Solar/Wind Harmer
-0.039
970673AG2-436 GEN
Solar/Wind Harmer
20.519
970673AG2-436 GEN
Solar/Wind Harmer
10.39
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.004
972193AH1-681 GEN
Adder
1.983
3146033SCOT NK
Solar/Wind Harmer
-0.039
971967AH1-528 GEN
Solar/Wind Harmer
18.185
970085AG2-068 GEN
Solar/Wind Harmer
5.805
970581AG2-369 GEN
Solar/Wind Harmer
4.992
316005AA1-067
Solar/Wind Harmer
0.188
3145746EVERETS
Solar/Wind Harmer
-0.037
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
970181AG2-120 GEN
Solar/Wind Harmer
1.218
957861AF2-080 GEN
Solar/Wind Harmer
3.978
970831AG2-522 GEN
Solar/Wind Harmer
4.545
316420AA1-050 GEN
Solar/Wind Harmer
1.028
3145573BETHELC
Solar/Wind Harmer
-0.009
3145573BETHELC
Solar/Wind Harmer
-0.009
316319Z2-044 C
Solar/Wind Harmer
0.492
972205AH1-687 GEN
Adder
2.848
3141426STAFORD
Solar/Wind Helper
0.043
315052AA1-145 CT2
50/50
2.911
3142416OLDCHRC
Solar/Wind Harmer
-0.049
3142416OLDCHRC
Solar/Wind Harmer
-0.019
3143096IRON208
Adder
0.607
3142543TWELFTH
Solar/Wind Harmer
-0.002
3150851SPRUNCC
Adder
0.644
944631AF1-128 GEN
Adder
65.745
315671AE2-027_GEN
Solar/Wind Harmer
10.95
970129AG2-093 GEN
Solar/Wind Harmer
3.283
316458AB2-190 GEN2
Solar/Wind Harmer
1.451
3143526WINTERP
Solar/Wind Harmer
-0.074
971069AG2-661 GEN
Solar/Wind Harmer
2.226
3142433PROV 92
Solar/Wind Harmer
-0.055
3142433PROV 92
Adder
0.241
3142433PROV 92
Adder
0.241
971647AH1-324 GEN
Solar/Wind Harmer
6.819
316159AE1-175 C
Solar/Wind Harmer
0.365
961611AG1-000B GEN
Solar/Wind Harmer
6.611
3151171GRAVELC
Adder
1.239
970659AG2-427 GEN
Solar/Wind Harmer
6.897
316381AD1-082 GEN
Solar/Wind Harmer
1.185
971317AH1-138 GEN
Solar/Wind Harmer
1.612
3138126ROCKLANDING
Solar/Wind Harmer
0.039
970661AG2-428 GEN
Solar/Wind Harmer
13.521
3145336SMITFLD
Solar/Wind Harmer
-0.05
3143226MDLTHAN
Solar/Wind Harmer
-0.013
971777AH1-397 GEN
Solar/Wind Harmer
1.48
3141843SHACKLE
Adder
0.573
3141766HARMONY
Solar/Wind Harmer
-0.002
316072AD1-144
Solar/Wind Harmer
0.244
316375AC2-012 GEN
Solar/Wind Harmer
4.156
3150981CHESPKA
Adder
1.335
316294AC1-161 GEN
Solar/Wind Harmer
3.856
944591AF1-124 GEN
Solar/Wind Harmer
54.192
316093AE2-104_GEN
Solar/Wind Harmer
3.443
316388AE2-253 GEN
Solar/Wind Harmer
0.797
316246AF1-032 C
Solar/Wind Harmer
0.239
3146456SLIGO L269
Solar/Wind Harmer
-0.012
3146516WINFALL
Solar/Wind Harmer
-0.037
3146516WINFALL
Solar/Wind Harmer
-0.011
3138133OCRAN
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
2.787
3130156CHOWAN
Solar/Wind Harmer
-0.011
939411AE1-173 GEN
Solar/Wind Harmer
54.232
3145663CRESWEL
Solar/Wind Harmer
-0.03
971163AH1-040 GEN
Solar/Wind Harmer
10.165
3143336POWHATN
Solar/Wind Harmer
1.256
940641AE2-051 GEN
Solar/Wind Harmer
9.85
3146206CASHIE
Solar/Wind Harmer
-0.01
971547AH1-271 GEN
Solar/Wind Harmer
2.615
316023GEN1_S
Solar/Wind Harmer
0.702
3145893MURPHYS
Solar/Wind Harmer
-0.041
3145893MURPHYS
Solar/Wind Harmer
0.309
3146173TUNIS
Solar/Wind Harmer
-0.01
961951AG1-038 GEN
Solar/Wind Harmer
1.342
3145683EARLEYS
Solar/Wind Harmer
-0.01
3146263WOODLND
Solar/Wind Harmer
-0.01
316336AC2-165 C
Solar/Wind Harmer
1.746
960081AF2-299 GEN
Solar/Wind Harmer
1.129
3145963POPLR C
Solar/Wind Harmer
-0.01
316011AB1-132 GEN
Solar/Wind Harmer
2.078
962571AG1-106 GEN
Solar/Wind Harmer
1.428
3145823KELFORD
Solar/Wind Harmer
-0.01
316174AB2-169 GEN
Solar/Wind Harmer
1.528
316190AA2-174 GEN
Solar/Wind Harmer
0.121
962861AG1-135 GEN
Solar/Wind Harmer
3.659
3145796HORNRTN
Solar/Wind Harmer
-0.032
3145796HORNRTN
Solar/Wind Harmer
-0.01
972277AH1-723 GEN
Adder
51.708
971795AH1-408 GEN
Solar/Wind Harmer
7.291
3145783HORNRTN
Solar/Wind Harmer
-0.01
3147043LAWRENC
Adder
0.771
3146293MARTNCO
Solar/Wind Harmer
0.059
316212AC1-099_GEN
Solar/Wind Harmer
0.827
970919AG2-571 GEN
Solar/Wind Harmer
2.949
970087AG2-069 GEN
Solar/Wind Harmer
8.708
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
315722AD1-056 GEN
Solar/Wind Harmer
0.961
964211AG1-282 GEN
Solar/Wind Harmer
0.275
3141726DUNNSVL
Solar/Wind Harmer
-0.036
316494AC1-189 GEN
Solar/Wind Harmer
0.978
316129AC1-054 GEN
Solar/Wind Harmer
0.791
957481AF2-042 GEN
Solar/Wind Harmer
28.162
971065AG2-659 GEN
Solar/Wind Harmer
4.475
961671AG1-007 GEN
Solar/Wind Harmer
0.113
3146083TARBORO
Solar/Wind Harmer
-0.009
3145493TOT1
Solar/Wind Harmer
0.265
3146233WITAKRS
Solar/Wind Harmer
-0.035
315693AD1-088 GEN
Solar/Wind Harmer
4.441
3150351NORNECKC2
Adder
0.76
3144293JTRSVLE
Adder
0.236
962491AG1-098 GEN
Solar/Wind Harmer
3.962
3142296MT RD221
50/50
0.632
3142366NRTHEST
50/50
0.558
3150691DARBY 3
50/50
12.038
3150701DARBY 4
50/50
12.01
3150681DARBY 2
50/50
11.996
966871AG1-558 GEN
Solar/Wind Harmer
0.566
966871AG1-558 GEN
Solar/Wind Harmer
0.194
3150671DARBY 1
Adder
11.292
316075AC2-137 C
Solar/Wind Harmer
0.441
3142946ENON
Solar/Wind Harmer
-0.002
944641AF1-129 GEN
Adder
65.107
316240AF1-291 C
Solar/Wind Harmer
0.455
3143526WINTERP
Solar/Wind Harmer
-0.074
316033AB2-134 GEN
Solar/Wind Harmer
4.476
315697AD1-025 GEN
Solar/Wind Harmer
2.807
970657AG2-426 GEN
Solar/Wind Harmer
4.014
970657AG2-426 GEN
Solar/Wind Harmer
0.839
316236AE1-162_GEN
Solar/Wind Harmer
0.382
971223AH1-071 GEN
Solar/Wind Harmer
1.581
316441AF1-014 GEN
Solar/Wind Harmer
0.848
316036AC1-147 C
Solar/Wind Harmer
0.324
3150991CHESPKB
Adder
1.12
3150991CHESPKB
Adder
1.093
316316AC1-027 C
Solar/Wind Harmer
0.367
3142956BIRDNECK
Solar/Wind Harmer
0.641
316185AD1-033 GEN
Solar/Wind Harmer
1.255
3145506HICKORY
Solar/Wind Harmer
-0.047
3145506HICKORY
Solar/Wind Harmer
-0.028
3145506HICKORY
Solar/Wind Harmer
-0.007
316339AD2-160 GEN
Solar/Wind Harmer
0.797
316018AA1-139 ULT2
Solar/Wind Harmer
1.011
316017AA1-139 ULT1
Solar/Wind Harmer
0.955
3137176SLIGO L2192
Solar/Wind Harmer
-0.047
3146456SLIGO L269
Solar/Wind Harmer
1.391
3130086AYDLETT
Solar/Wind Harmer
-0.047
3146386ELIZ CT
Solar/Wind Harmer
-0.012
316431W1029_GEN1
Solar/Wind Harmer
2.088
316433W1029_GEN2
Solar/Wind Harmer
2.088
316468AD1-105 GEN
Solar/Wind Harmer
1.281
3146516WINFALL
Solar/Wind Harmer
-0.011
3146516WINFALL
Solar/Wind Harmer
-0.011
3146516WINFALL
Solar/Wind Harmer
-0.011
3146626S HERTFORD
Solar/Wind Harmer
-0.011
3146626S HERTFORD
Solar/Wind Harmer
-0.011
3144356SAPONY
Solar/Wind Harmer
0.397
315742AE1-103 GEN
Solar/Wind Harmer
1.178
3146376EDENTON
Solar/Wind Harmer
0.33
3146376EDENTON
Solar/Wind Harmer
0.33
316065AD1-022 GEN
Solar/Wind Harmer
5.253
3145893MURPHYS
Solar/Wind Harmer
0.29
3145893MURPHYS
Solar/Wind Harmer
-0.019
3146173TUNIS
Solar/Wind Harmer
-0.01
3146173TUNIS
Solar/Wind Harmer
-0.01
316487AF1-042 GEN
Solar/Wind Harmer
1.342
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
315051AA1-145 CT1
50/50
2.899
971645AH1-323 GEN
50/50
17.383
3142416OLDCHRC
Solar/Wind Harmer
1.915
316473AC1-191 GEN
Solar/Wind Harmer
2.026
970293AG2-193 GEN
Solar/Wind Harmer
2.133
3143096IRON208
Adder
0.607
3143096IRON208
Adder
0.594
3150861SPRUNCD
Adder
0.644
3142946ENON
Solar/Wind Harmer
-0.005
970133AG2-095 GEN
Solar/Wind Harmer
1.67
965281AG1-393 GEN
Solar/Wind Harmer
1.803
970129AG2-093 GEN
Solar/Wind Harmer
8.105
315839AE2-212 C
Solar/Wind Harmer
0.433
315778AD1-151 GEN
Solar/Wind Harmer
12.19
3142433PROV 92
Adder
0.241
3142433PROV 92
Adder
0.241
316382AG1-145 C
Solar/Wind Harmer
0.41
961611AG1-000B GEN
Solar/Wind Harmer
2.821
315813AE1-149 C
Solar/Wind Harmer
8.334
3151221GRAVEL6
Adder
8.471
3151171GRAVELC
Adder
1.63
970659AG2-427 GEN
Solar/Wind Harmer
1.222
316083AB2-161 GEN
Solar/Wind Harmer
2.096
3144216WINCHST
Adder
0.432
3150921YORKTN3
Adder
2.872
970661AG2-428 GEN
Solar/Wind Harmer
2.396
3145336SMITFLD
Solar/Wind Harmer
-0.005
3141843SHACKLE
Adder
0.573
316203AE2-005 GEN
Solar/Wind Harmer
5.305
3141766HARMONY
Solar/Wind Harmer
1.12
316280AD1-041 GEN
Solar/Wind Harmer
0.934
3144536CHRHLND
Solar/Wind Harmer
-0.002
316156AD2-030 GEN
Solar/Wind Harmer
0.324
3141873WAN 176
Solar/Wind Harmer
1.44
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
9.912
315773AC2-141 GEN
Solar/Wind Harmer
4.987
944581AF1-123 GEN
Solar/Wind Harmer
53.997
944601AF1-125 GEN
Solar/Wind Harmer
53.155
3146456SLIGO L269
Solar/Wind Harmer
-0.012
971153AH1-033 GEN
Solar/Wind Harmer
1.436
316320Y1-086
Solar/Wind Harmer
0.683
316435W1029_GEN3
Solar/Wind Harmer
2.088
971781AH1-399 GEN
Solar/Wind Harmer
0.709
3146516WINFALL
Solar/Wind Harmer
-0.011
3145273HOLLAND
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.011
3146376EDENTON
Solar/Wind Harmer
-0.011
315614AA2-178 GEN
Solar/Wind Harmer
1.17
971157AH1-035 GEN
Solar/Wind Harmer
1.328
315737AD1-076 GEN
Solar/Wind Harmer
2.012
316313AB2-026
Solar/Wind Harmer
0.285
316258AE1-075 C
Solar/Wind Harmer
0.257
316405AF2-144 C
Solar/Wind Harmer
0.271
3143336POWHATN
Solar/Wind Harmer
1.068
3156081AA2-088 GEN
Solar/Wind Harmer
3.434
962971AG1-146 GEN
Solar/Wind Harmer
1.977
3146206CASHIE
Solar/Wind Harmer
-0.01
316365GEN2_N
Solar/Wind Harmer
0.702
3145893MURPHYS
Solar/Wind Harmer
0.073
3145893MURPHYS
Solar/Wind Harmer
-0.01
957521AF2-046 GEN
Solar/Wind Harmer
8.169
961681AG1-008 GEN
Solar/Wind Harmer
8.169
3146173TUNIS
Solar/Wind Harmer
-0.01
3156021HOLLOMANSOL
Solar/Wind Harmer
1.385
316463AE2-346 GEN
Solar/Wind Harmer
0.166
316140AB2-099
Solar/Wind Harmer
0.069
962331AG1-082 GEN
Solar/Wind Harmer
1.278
316484AD2-074 GEN
Solar/Wind Harmer
2.564
970009AG2-005 GEN
Solar/Wind Harmer
1.273
3146263WOODLND
Solar/Wind Harmer
-0.01
966621AG1-532 GEN
Solar/Wind Harmer
0.204
3145963POPLR C
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
316317KELFORD C
Solar/Wind Harmer
0.468
3145823KELFORD
Solar/Wind Harmer
-0.01
313506AB2-031 GEN
Solar/Wind Harmer
0.797
3145796HORNRTN
Solar/Wind Harmer
-0.039
3145796HORNRTN
Solar/Wind Harmer
-0.01
972255AH1-712 GEN
Adder
44.373
316404AE1-155 C
Solar/Wind Harmer
1.853
3147043LAWRENC
Solar/Wind Harmer
-0.006
3145933PARMELE
Solar/Wind Harmer
-0.009
966801AG1-551 GEN
Solar/Wind Harmer
1.189
316210AC1-098 GEN
Solar/Wind Harmer
1.488
970917AG2-570 GEN
Solar/Wind Harmer
23.3
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
315724AD1-057 GEN
Solar/Wind Harmer
0.529
316327AA2-057 GEN
Solar/Wind Harmer
0.918
3146073TAR RVR
Solar/Wind Harmer
-0.009
3146083TARBORO
Solar/Wind Harmer
-0.009
3146233WITAKRS
Solar/Wind Harmer
0.186
3146233WITAKRS
Solar/Wind Harmer
-0.006
3138543CONSLDL
Solar/Wind Harmer
-0.006
3150351NORNECKC2
Adder
0.772
3144293JTRSVLE
Adder
0.236
966881AG1-559 GEN
Solar/Wind Helper
1.276
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
316181AB2-040 GEN
Solar/Wind Harmer
1.383
316426AA2-053 GEN
Solar/Wind Harmer
0.994
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.099
3145593CAROLNA
Solar/Wind Harmer
0.081
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145783HORNRTN
Solar/Wind Harmer
1.152
3145783HORNRTN
Solar/Wind Harmer
0.922
3145783HORNRTN
Solar/Wind Harmer
0.288
3145783HORNRTN
Solar/Wind Harmer
0.115
972185AH1-677 GEN
Adder
4.843
958261AF2-120 GEN
Solar/Wind Harmer
3.721
972187AH1-678 GEN
Adder
2.434
3145933PARMELE
Solar/Wind Harmer
-0.019
3145933PARMELE
Solar/Wind Harmer
-0.009
970933AG2-581 GEN
Solar/Wind Harmer
8.897
316274AC1-208 GEN
Solar/Wind Harmer
1.013
970099AG2-077 GEN
Solar/Wind Harmer
11.265
3145493TOT1
Solar/Wind Harmer
0.138
3145453TOT5
Solar/Wind Harmer
0.083
3145603CNETO
Solar/Wind Harmer
0.055
3150341NORNECKC1
Adder
0.798
3150341NORNECKC1
Adder
0.792
3144293JTRSVLE
Adder
0.236
3144293JTRSVLE
Adder
0.199
226929AD2-058 GEN
Solar/Wind Helper
0.044
NYPJM->LTFIMP_NY
CLTF
1.534
LGEELTFEXP_LGEE->PJM
CLTF
0.752
WECLTFEXP_WEC->PJM
CLTF
0.375
LAGNLTFEXP_LAGN->PJM
CLTF
3.865
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.977
TVALTFEXP_TVA->PJM
CLTF
1.959
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.941
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.773
MECLTFEXP_MEC->PJM
CLTF
1.972
SIGELTFEXP_SIGE->PJM
CLTF
0.061
CPLELTFEXP_CPLE->PJM
CLTF
4.906
CBM West 2LTFEXP_CBM-W2->PJM
CBM
20.857

Details for 6FOUR RIVERS-6STJOHN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FOUR RIVERS-6STJOHN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:178.97 %
Rating:1123.3 MVA
Rating Type:B
MVA to Mitigate:2010.34
MW Contribution:48.26
Bus #Bus NameTypeMW Contribution
315051AA1-145 CT1
50/50
2.918
971645AH1-323 GEN
50/50
16.835
316473AC1-191 GEN
Solar/Wind Harmer
0.548
3142416OLDCHRC
Solar/Wind Harmer
1.565
970293AG2-193 GEN
Solar/Wind Harmer
1.529
3143096IRON208
Adder
0.565
3143096IRON208
Adder
0.554
3150861SPRUNCD
Adder
0.591
3142946ENON
Solar/Wind Harmer
0.043
970133AG2-095 GEN
Solar/Wind Harmer
1.166
970129AG2-093 GEN
Solar/Wind Harmer
7.081
965281AG1-393 GEN
Solar/Wind Harmer
1.248
315839AE2-212 C
Solar/Wind Harmer
0.001
3142433PROV 92
Adder
0.224
3142433PROV 92
Adder
0.224
315778AD1-151 GEN
Solar/Wind Harmer
9.127
316382AG1-145 C
Solar/Wind Harmer
0.001
961611AG1-000B GEN
Solar/Wind Harmer
2.872
315813AE1-149 C
Solar/Wind Harmer
5.679
3151221GRAVEL6
Adder
7.62
3151171GRAVELC
Adder
1.466
3141766HARMONY
Solar/Wind Harmer
1.39
3141843SHACKLE
Adder
0.533
316203AE2-005 GEN
Solar/Wind Harmer
0
3144216WINCHST
Adder
0.391
3150921YORKTN3
Adder
2.597
970659AG2-427 GEN
Solar/Wind Harmer
1.092
316083AB2-161 GEN
Solar/Wind Harmer
0.001
316280AD1-041 GEN
Solar/Wind Harmer
0.002
971781AH1-399 GEN
Solar/Wind Harmer
0.134
970661AG2-428 GEN
Solar/Wind Harmer
2.134
3145336SMITFLD
Solar/Wind Harmer
0.04
316156AD2-030 GEN
Solar/Wind Harmer
0.074
3141873WAN 176
Solar/Wind Harmer
1.784
3144536CHRHLND
Solar/Wind Harmer
0.014
3144873MCLAUGH
Solar/Wind Harmer
0.002
3151101ELIZAR3
Adder
8.726
315773AC2-141 GEN
Solar/Wind Harmer
3.399
944581AF1-123 GEN
Solar/Wind Harmer
20.877
944601AF1-125 GEN
Solar/Wind Harmer
20.555
3146456SLIGO L269
Solar/Wind Harmer
0.092
971153AH1-033 GEN
Solar/Wind Harmer
1.064
316320Y1-086
Solar/Wind Harmer
0
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.09
3145273HOLLAND
Solar/Wind Harmer
0.067
3146626S HERTFORD
Solar/Wind Harmer
0.089
962971AG1-146 GEN
Solar/Wind Harmer
1.408
3146376EDENTON
Solar/Wind Harmer
0.087
970009AG2-005 GEN
Solar/Wind Harmer
0.636
315614AA2-178 GEN
Solar/Wind Harmer
0.482
971157AH1-035 GEN
Solar/Wind Harmer
0.989
315737AD1-076 GEN
Solar/Wind Harmer
1.056
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3146206CASHIE
Solar/Wind Harmer
0.081
972255AH1-712 GEN
Adder
41.412
316404AE1-155 C
Solar/Wind Harmer
0.018
3145893MURPHYS
Solar/Wind Harmer
0.135
3145893MURPHYS
Solar/Wind Harmer
0.08
957521AF2-046 GEN
Solar/Wind Harmer
5.964
961681AG1-008 GEN
Solar/Wind Harmer
5.964
316365GEN2_N
Solar/Wind Harmer
0.18
316313AB2-026
Solar/Wind Harmer
0.05
316258AE1-075 C
Solar/Wind Harmer
0.06
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
1.206
3146173TUNIS
Solar/Wind Harmer
0.079
3156021HOLLOMANSOL
Solar/Wind Harmer
0.361
316463AE2-346 GEN
Solar/Wind Harmer
0.068
316140AB2-099
Solar/Wind Harmer
0.028
962331AG1-082 GEN
Solar/Wind Harmer
0.842
3146263WOODLND
Solar/Wind Harmer
0.077
3145963POPLR C
Solar/Wind Harmer
0.077
3142666NORTHAMPTON
Solar/Wind Harmer
0.077
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.076
313506AB2-031 GEN
Solar/Wind Harmer
0.235
3145796HORNRTN
Solar/Wind Harmer
0.299
3145796HORNRTN
Solar/Wind Harmer
0.075
3145933PARMELE
Solar/Wind Harmer
0.073
966801AG1-551 GEN
Solar/Wind Harmer
0.852
3147043LAWRENC
Solar/Wind Harmer
0.044
316210AC1-098 GEN
Solar/Wind Harmer
0.675
3150351NORNECKC2
Adder
0.736
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
315724AD1-057 GEN
Solar/Wind Harmer
0.264
316327AA2-057 GEN
Solar/Wind Harmer
0.105
970917AG2-570 GEN
Solar/Wind Harmer
6.096
3146073TAR RVR
Solar/Wind Harmer
0.068
3146083TARBORO
Solar/Wind Harmer
0.068
3146233WITAKRS
Solar/Wind Harmer
0.341
3146233WITAKRS
Solar/Wind Harmer
0.046
3138543CONSLDL
Solar/Wind Harmer
0.045
961601AG1-000A GEN
Solar/Wind Harmer
4.735
3145543BTLEBRO
Solar/Wind Harmer
0.066
3145543BTLEBRO
Solar/Wind Harmer
0.066
971623AH1-311 GEN
Solar/Wind Harmer
0.133
316478AD1-087 GEN
Solar/Wind Harmer
0.226
316486AD2-202 GEN
Solar/Wind Harmer
0.066
316131AB2-060 GEN
Solar/Wind Harmer
0.2
964241AG1-285 GEN
Solar/Wind Harmer
4.226
315785AD2-033 C
Solar/Wind Harmer
0.512
970257AG2-171 GEN
Solar/Wind Harmer
2.009
959311AF2-222 GEN
Solar/Wind Harmer
5.571
970909AG2-566 GEN
Solar/Wind Harmer
0.666
963181AG1-167 GEN
Solar/Wind Harmer
0.248
3144293JTRSVLE
Adder
0.197
3147133PAMPLIN
Solar/Wind Harmer
0.194
971193AH1-056 GEN
Solar/Wind Harmer
3.759
942461AE2-259 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.036
3146776BUCKING
Solar/Wind Harmer
0.021
316248AF1-058 C
Solar/Wind Harmer
0
960061AF2-297 GEN
Solar/Wind Harmer
2.454
966881AG1-559 GEN
Solar/Wind Helper
1.231
315052AA1-145 CT2
50/50
2.931
3142416OLDCHRC
Solar/Wind Harmer
0.42
3142416OLDCHRC
Solar/Wind Harmer
0.161
3143096IRON208
Adder
0.565
3142543TWELFTH
Solar/Wind Harmer
0.013
944631AF1-128 GEN
Adder
61.103
3150851SPRUNCC
Adder
0.591
315671AE2-027_GEN
Solar/Wind Harmer
7.597
970129AG2-093 GEN
Solar/Wind Harmer
3.332
316458AB2-190 GEN2
Solar/Wind Harmer
0.626
3142433PROV 92
Solar/Wind Harmer
0.461
3142433PROV 92
Adder
0.224
3142433PROV 92
Adder
0.224
971069AG2-661 GEN
Solar/Wind Harmer
2.028
3143526WINTERP
Solar/Wind Harmer
0.586
316159AE1-175 C
Solar/Wind Harmer
0.096
971647AH1-324 GEN
Solar/Wind Harmer
4.693
961611AG1-000B GEN
Solar/Wind Harmer
5.648
3151171GRAVELC
Adder
1.115
971317AH1-138 GEN
Solar/Wind Harmer
0.78
3141766HARMONY
Solar/Wind Harmer
0.021
971777AH1-397 GEN
Solar/Wind Harmer
0.275
3141843SHACKLE
Adder
0.533
3138126ROCKLANDING
Solar/Wind Harmer
0.047
970659AG2-427 GEN
Solar/Wind Harmer
4.993
316381AD1-082 GEN
Solar/Wind Harmer
0.107
970661AG2-428 GEN
Solar/Wind Harmer
10.035
3145336SMITFLD
Solar/Wind Harmer
0.403
3143226MDLTHAN
Solar/Wind Harmer
0.096
316072AD1-144
Solar/Wind Harmer
0.034
3138133OCRAN
Solar/Wind Harmer
0.057
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
1.175
316294AC1-161 GEN
Solar/Wind Harmer
1.613
316093AE2-104_GEN
Solar/Wind Harmer
1.56
944591AF1-124 GEN
Solar/Wind Harmer
20.951
316388AE2-253 GEN
Solar/Wind Harmer
0.289
316246AF1-032 C
Solar/Wind Harmer
0.042
3146456SLIGO L269
Solar/Wind Harmer
0.092
3146516WINFALL
Solar/Wind Harmer
0.29
3146516WINFALL
Solar/Wind Harmer
0.09
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.087
3145663CRESWEL
Solar/Wind Harmer
0.236
971163AH1-040 GEN
Solar/Wind Harmer
6.739
962861AG1-135 GEN
Solar/Wind Harmer
2.62
939411AE1-173 GEN
Solar/Wind Harmer
34.862
3146206CASHIE
Solar/Wind Harmer
0.081
971547AH1-271 GEN
Solar/Wind Harmer
1.728
972277AH1-723 GEN
Adder
48.257
3145893MURPHYS
Solar/Wind Harmer
0.322
3145893MURPHYS
Solar/Wind Harmer
0.358
316023GEN1_S
Solar/Wind Harmer
0.18
3143336POWHATN
Solar/Wind Harmer
1.419
3146173TUNIS
Solar/Wind Harmer
0.079
3145683EARLEYS
Solar/Wind Harmer
0.078
940641AE2-051 GEN
Solar/Wind Harmer
6.242
3146263WOODLND
Solar/Wind Harmer
0.077
3141726DUNNSVL
Solar/Wind Harmer
0.309
3145963POPLR C
Solar/Wind Harmer
0.077
960081AF2-299 GEN
Solar/Wind Harmer
0.738
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3145823KELFORD
Solar/Wind Harmer
0.076
316011AB1-132 GEN
Solar/Wind Harmer
1.386
962571AG1-106 GEN
Solar/Wind Harmer
1.085
316336AC2-165 C
Solar/Wind Harmer
0.003
316190AA2-174 GEN
Solar/Wind Harmer
0
3145796HORNRTN
Solar/Wind Harmer
0.247
3145796HORNRTN
Solar/Wind Harmer
0.075
3145783HORNRTN
Solar/Wind Harmer
0.074
971795AH1-408 GEN
Solar/Wind Harmer
4.942
3146293MARTNCO
Solar/Wind Harmer
0.068
3147043LAWRENC
Adder
0.659
316212AC1-099_GEN
Solar/Wind Harmer
0.376
3150351NORNECKC2
Adder
0.724
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
315722AD1-056 GEN
Solar/Wind Harmer
0.445
316494AC1-189 GEN
Solar/Wind Harmer
0.235
970919AG2-571 GEN
Solar/Wind Harmer
2.438
970087AG2-069 GEN
Solar/Wind Harmer
5.469
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.068
3145493TOT1
Solar/Wind Harmer
0.303
316129AC1-054 GEN
Solar/Wind Harmer
0.256
3146233WITAKRS
Solar/Wind Harmer
0.271
971065AG2-659 GEN
Solar/Wind Harmer
2.883
316359AB2-059 GEN
Solar/Wind Harmer
0.239
316049AB1-081 GEN
Solar/Wind Harmer
0.381
3145543BTLEBRO
Solar/Wind Harmer
0.066
3145543BTLEBRO
Solar/Wind Harmer
0.053
3142053HEARTS
Solar/Wind Harmer
0.117
957481AF2-042 GEN
Solar/Wind Harmer
17.725
315693AD1-088 GEN
Solar/Wind Harmer
3.146
962491AG1-098 GEN
Solar/Wind Harmer
3.732
970937AG2-583 GEN
Solar/Wind Harmer
3.951
316237AB2-079_GEN
Solar/Wind Harmer
0.001
970685AG2-442 GEN
Solar/Wind Harmer
4.658
963171AG1-166 GEN
Solar/Wind Harmer
0.331
971563AH1-280 GEN
Solar/Wind Harmer
0.661
3144293JTRSVLE
Adder
0.197
315687AD1-152 GEN
Solar/Wind Harmer
0.002
3146926FARMVIL
Solar/Wind Harmer
0.036
970401AG2-262 GEN
Solar/Wind Harmer
0.353
316337AD2-073 GEN
Solar/Wind Harmer
0.051
316322AB2-045
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
0.023
972189AH1-679 GEN
50/50
6.542
316312AB1-027
Solar/Wind Harmer
0.289
971285AH1-108 GEN
Adder
0.966
315976AC1-164 GENA
Solar/Wind Harmer
13.079
316169AC1-164_GENC
Solar/Wind Harmer
11.299
315975AC1-164 GENB
Solar/Wind Harmer
0.387
971167AH1-042 GEN
Solar/Wind Harmer
10.37
316132AB2-190 GEN1
Solar/Wind Harmer
0.626
3142433PROV 92
Adder
0.224
3142433PROV 92
Adder
0.224
316233AE1-074 FULL
Solar/Wind Harmer
0.09
971281AH1-106 GEN
Solar/Wind Harmer
1.563
971283AH1-107 GEN
Solar/Wind Harmer
1.563
316369SG1_INVT
Solar/Wind Harmer
0.004
3143873LANEXA
Solar/Wind Harmer
0.066
316314AB2-024 C
Solar/Wind Harmer
0
3143316POE
Solar/Wind Harmer
0.415
972265AH1-717 GEN
Adder
8.137
3151201GRAVEL4
Adder
7.628
3151191GRAVEL3
Adder
7.532
3151211GRAVEL5
Adder
7.532
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
3.088
315662AE1-191 GEN
Solar/Wind Harmer
0.003
315666AE1-190 GEN
Solar/Wind Harmer
0.001
3138283WHITEMARSH
Solar/Wind Harmer
0.024
971445AH1-216 GEN
Solar/Wind Harmer
7.118
3141873WAN 176
Solar/Wind Harmer
0.02
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.066
316311AC2-079 GEN
Solar/Wind Harmer
2.771
3141913WHIT STONE
Solar/Wind Harmer
0.096
3138133OCRAN
Solar/Wind Harmer
0.029
3152611GOSPORTB
Adder
1.199
3152621GOSPORTC
Adder
1.017
3152601GOSPORTA
Adder
0.939
3151081ELIZAR1
Adder
8.616
3151091ELIZAR2
Adder
8.466
3141783LANCAST
Solar/Wind Harmer
0.056
3141783LANCAST
Solar/Wind Harmer
0.037
315835AF2-110_GEN
Solar/Wind Harmer
0.637
316305AF2-043 C
Solar/Wind Harmer
0.001
957871AF2-081 GEN
Solar/Wind Harmer
4.593
319010AE1-072 C
Solar/Wind Harmer
0.463
3146406KITTY HAWK
Solar/Wind Harmer
0.011
313526AB2-022
Solar/Wind Harmer
0.049
3146486SUNBURY
Solar/Wind Harmer
0.091
3146486SUNBURY
Solar/Wind Harmer
0.091
316321Z2-027
Solar/Wind Harmer
0.017
3145176PASQUOTANK
Solar/Wind Harmer
0.056
3146396TANGLEW
Solar/Wind Harmer
0.249
962981AG1-147 GEN
Solar/Wind Harmer
3.285
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
316315AB2-025 C
Solar/Wind Harmer
0.071
315814AE2-033 C
Solar/Wind Harmer
6.922
3130156CHOWAN
Solar/Wind Harmer
0.087
3130156CHOWAN
Solar/Wind Harmer
0.087
970327AG2-215 GEN
Solar/Wind Harmer
2.796
315816AE2-034 GEN
Solar/Wind Harmer
0.361
3130546PLYMOUTH
Solar/Wind Harmer
0.082
315732AD1-074 GEN1
Solar/Wind Harmer
0.472
315733AD1-074 GEN2
Solar/Wind Harmer
0.472
315735AD1-075 GEN1
Solar/Wind Harmer
0.236
965291AG1-394 GEN
Solar/Wind Harmer
0.362
3146206CASHIE
Solar/Wind Harmer
0.081
970601AG2-382 GEN
Solar/Wind Harmer
3.023
972193AH1-681 GEN
Adder
1.85
3145893MURPHYS
Solar/Wind Harmer
0.217
3145893MURPHYS
Solar/Wind Harmer
0.08
3145513AHOSKIE
Solar/Wind Harmer
0.165
3145513AHOSKIE
Solar/Wind Harmer
0.079
3145683EARLEYS
Solar/Wind Harmer
0.157
3145683EARLEYS
Solar/Wind Harmer
0.078
3145683EARLEYS
Solar/Wind Harmer
0.078
3146043SEABORD
Solar/Wind Harmer
0.078
315607AA1-063A GEN
Solar/Wind Harmer
0.158
315652AC1-086 GEN
Solar/Wind Harmer
8.385
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.301
3145796HORNRTN
Solar/Wind Harmer
0.239
3145796HORNRTN
Solar/Wind Harmer
0.03
3146033SCOT NK
Solar/Wind Harmer
0.297
941031AE2-094 GEN
Solar/Wind Harmer
13.383
944011AF1-069 GEN
Solar/Wind Harmer
4.373
3141813NORNECK
Solar/Wind Harmer
0.073
970673AG2-436 GEN
Solar/Wind Harmer
15.295
970673AG2-436 GEN
Solar/Wind Harmer
10.197
316005AA1-067
Solar/Wind Harmer
0.076
3145746EVERETS
Solar/Wind Harmer
0.283
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
970181AG2-120 GEN
Solar/Wind Harmer
0.886
971967AH1-528 GEN
Solar/Wind Harmer
11.367
957861AF2-080 GEN
Solar/Wind Harmer
3.002
316420AA1-050 GEN
Solar/Wind Harmer
0.002
970831AG2-522 GEN
Solar/Wind Harmer
2.936
970085AG2-068 GEN
Solar/Wind Harmer
3.646
970581AG2-369 GEN
Solar/Wind Harmer
3.135
3145573BETHELC
Solar/Wind Harmer
0.068
3145573BETHELC
Solar/Wind Harmer
0.068
316319Z2-044 C
Solar/Wind Harmer
0
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
971443AH1-215 GEN
Solar/Wind Harmer
1.056
3144303KENBRDG
Solar/Wind Harmer
0.05
970683AG2-441 GEN
Solar/Wind Harmer
4.159
970681AG2-440 GEN
Solar/Wind Harmer
3.327
946301AF1-294 GEN
Solar/Wind Harmer
1.224
961791AG1-021 GEN
Solar/Wind Harmer
0.595
315657AE1-056 GEN
Solar/Wind Harmer
2.129
316118AC1-105 GEN
Solar/Wind Harmer
0.152
970285AG2-188 GEN
Solar/Wind Harmer
4.619
971845AH1-439 GEN
Solar/Wind Harmer
2.63
3147173SINAI
Solar/Wind Harmer
0.057
3147243WELCO
Solar/Wind Harmer
0.036
3141426STAFORD
Solar/Wind Helper
0.036
3142296MT RD221
50/50
0.609
3142366NRTHEST
50/50
0.528
3150691DARBY 3
50/50
11.381
3150701DARBY 4
50/50
11.355
3150681DARBY 2
50/50
11.341
966871AG1-558 GEN
Solar/Wind Harmer
0.187
3150671DARBY 1
Adder
10.676
316075AC2-137 C
Solar/Wind Harmer
0.038
3142946ENON
Solar/Wind Harmer
0.013
944641AF1-129 GEN
Adder
59.909
316240AF1-291 C
Solar/Wind Harmer
0.001
3143526WINTERP
Solar/Wind Harmer
0.586
316033AB2-134 GEN
Solar/Wind Harmer
0.007
315697AD1-025 GEN
Solar/Wind Harmer
0.126
316468AD1-105 GEN
Solar/Wind Harmer
-0.033
970657AG2-426 GEN
Solar/Wind Harmer
3.572
970657AG2-426 GEN
Solar/Wind Harmer
0.749
316236AE1-162_GEN
Solar/Wind Harmer
0.001
971223AH1-071 GEN
Solar/Wind Harmer
1.028
316036AC1-147 C
Solar/Wind Harmer
0.017
3150991CHESPKB
Adder
0.986
3150991CHESPKB
Adder
0.962
316316AC1-027 C
Solar/Wind Harmer
0.09
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.003
3145506HICKORY
Solar/Wind Harmer
0.371
3145506HICKORY
Solar/Wind Harmer
0.222
3145506HICKORY
Solar/Wind Harmer
0.056
316339AD2-160 GEN
Solar/Wind Harmer
0.15
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.052
3137176SLIGO L2192
Solar/Wind Harmer
0.366
3146456SLIGO L269
Solar/Wind Harmer
1.629
3130086AYDLETT
Solar/Wind Harmer
0.367
3146386ELIZ CT
Solar/Wind Harmer
0.091
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.09
3146516WINFALL
Solar/Wind Harmer
0.09
3146516WINFALL
Solar/Wind Harmer
0.09
3146626S HERTFORD
Solar/Wind Harmer
0.089
3146626S HERTFORD
Solar/Wind Harmer
0.089
3144356SAPONY
Solar/Wind Harmer
0.735
315742AE1-103 GEN
Solar/Wind Harmer
0.001
3146376EDENTON
Solar/Wind Harmer
0.385
3146376EDENTON
Solar/Wind Harmer
0.385
316065AD1-022 GEN
Solar/Wind Harmer
3.747
958261AF2-120 GEN
Solar/Wind Harmer
2.668
3145893MURPHYS
Solar/Wind Harmer
0.538
3145893MURPHYS
Solar/Wind Harmer
0.145
3146173TUNIS
Solar/Wind Harmer
0.079
3146173TUNIS
Solar/Wind Harmer
0.079
3142666NORTHAMPTON
Solar/Wind Harmer
0.077
3142666NORTHAMPTON
Solar/Wind Harmer
0.077
3142666NORTHAMPTON
Solar/Wind Harmer
0.077
3142666NORTHAMPTON
Solar/Wind Harmer
0.046
316181AB2-040 GEN
Solar/Wind Harmer
0.11
316426AA2-053 GEN
Solar/Wind Harmer
0.255
3145796HORNRTN
Solar/Wind Harmer
0.224
3145593CAROLNA
Solar/Wind Harmer
0.075
3145593CAROLNA
Solar/Wind Harmer
0.075
966811AG1-552 GEN
Solar/Wind Harmer
0.812
3145593CAROLNA
Solar/Wind Harmer
0.093
3145783HORNRTN
Solar/Wind Harmer
1.322
3145783HORNRTN
Solar/Wind Harmer
1.058
3145783HORNRTN
Solar/Wind Harmer
0.331
3145783HORNRTN
Solar/Wind Harmer
0.132
3145933PARMELE
Solar/Wind Harmer
0.146
3145933PARMELE
Solar/Wind Harmer
0.073
316077AC2-138 C
Solar/Wind Harmer
0
3150341NORNECKC1
Adder
0.76
3150341NORNECKC1
Adder
0.754
316274AC1-208 GEN
Solar/Wind Harmer
0.373
972185AH1-677 GEN
Adder
3.996
972187AH1-678 GEN
Adder
2.009
970933AG2-581 GEN
Solar/Wind Harmer
5.582
3145493TOT1
Solar/Wind Harmer
0.158
3145453TOT5
Solar/Wind Harmer
0.095
3145603CNETO
Solar/Wind Harmer
0.063
961601AG1-000A GEN
Solar/Wind Harmer
1.184
316263AC1-034 GEN
Solar/Wind Harmer
2.527
970099AG2-077 GEN
Solar/Wind Harmer
7.09
939181AE1-148 GEN
Solar/Wind Harmer
3.093
313527AB2-043 GEN
Solar/Wind Harmer
0.001
971741AH1-377 GEN
Solar/Wind Harmer
6.264
316034AC1-036 C
Solar/Wind Harmer
0.005
970323AG2-213 GEN
Solar/Wind Harmer
2.679
971775AH1-396 GEN
Solar/Wind Harmer
0.1
970301AG2-198 GEN
Solar/Wind Harmer
2.664
958211AF2-115 GEN
Solar/Wind Harmer
0.744
963191AG1-168 GEN
Solar/Wind Harmer
0.248
3144293JTRSVLE
Adder
0.197
3144293JTRSVLE
Adder
0.166
3147133PAMPLIN
Solar/Wind Harmer
0.062
3147133PAMPLIN
Solar/Wind Harmer
0.049
962561AG1-105 GEN
Solar/Wind Harmer
2.911
964791AG1-342 GEN
Solar/Wind Harmer
1.154
3146843MT LREL
Solar/Wind Harmer
0.06
3146843MT LREL
Solar/Wind Harmer
0.06
3146776BUCKING
Solar/Wind Harmer
0.231
3146776BUCKING
Solar/Wind Harmer
0.019
NYPJM->LTFIMP_NY
CLTF
1.302
LGEELTFEXP_LGEE->PJM
CLTF
0.637
WECLTFEXP_WEC->PJM
CLTF
0.317
LAGNLTFEXP_LAGN->PJM
CLTF
3.272
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.272
TVALTFEXP_TVA->PJM
CLTF
1.66
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.925
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.738
MECLTFEXP_MEC->PJM
CLTF
1.668
SIGELTFEXP_SIGE->PJM
CLTF
0.052
CPLELTFEXP_CPLE->PJM
CLTF
4.14
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.656

Details for 6FOUR RIVERS-6STJOHN 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FOUR RIVERS-6STJOHN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:156.82 %
Rating:1360.0 MVA
Rating Type:C
MVA to Mitigate:2132.8
MW Contribution:43.3
Bus #Bus NameTypeMW Contribution
972189AH1-679 GEN
50/50
6.747
316312AB1-027
Solar/Wind Harmer
0.646
971285AH1-108 GEN
Adder
1.02
315976AC1-164 GENA
Solar/Wind Harmer
15.274
316169AC1-164_GENC
Solar/Wind Harmer
13.195
315975AC1-164 GENB
Solar/Wind Harmer
0.452
971167AH1-042 GEN
Solar/Wind Harmer
13.044
316132AB2-190 GEN1
Solar/Wind Harmer
1.369
316233AE1-074 FULL
Solar/Wind Harmer
0.361
971281AH1-106 GEN
Solar/Wind Harmer
2.179
971283AH1-107 GEN
Solar/Wind Harmer
2.179
3142433PROV 92
Adder
0.231
3142433PROV 92
Adder
0.231
316369SG1_INVT
Solar/Wind Harmer
2.314
3143873LANEXA
Solar/Wind Harmer
-0.007
316314AB2-024 C
Solar/Wind Harmer
1.044
3143316POE
Solar/Wind Harmer
-0.048
972265AH1-717 GEN
Adder
8.273
3151201GRAVEL4
Adder
7.756
3151191GRAVEL3
Adder
7.657
3151211GRAVEL5
Adder
7.657
316059AD1-063 C
Solar/Wind Harmer
0.27
315662AE1-191 GEN
Solar/Wind Harmer
1.417
315666AE1-190 GEN
Solar/Wind Harmer
0.354
957831AF2-077 GEN
Solar/Wind Harmer
0.348
3138283WHITEMARSH
Solar/Wind Harmer
0.018
971445AH1-216 GEN
Solar/Wind Harmer
7.116
957601AF2-054 GEN
Solar/Wind Harmer
0.344
3141873WAN 176
Solar/Wind Harmer
-0.002
3141913WHIT STONE
Solar/Wind Harmer
-0.011
315833AF1-017_GEN
Solar/Wind Harmer
2.092
316349AD2-085 GEN
Solar/Wind Harmer
0.98
316311AC2-079 GEN
Solar/Wind Harmer
5.55
3138133OCRAN
Solar/Wind Harmer
-0.003
3141783LANCAST
Solar/Wind Harmer
-0.006
3141783LANCAST
Solar/Wind Harmer
-0.004
3152611GOSPORTB
Adder
1.203
3152621GOSPORTC
Adder
1.021
3152601GOSPORTA
Adder
0.942
3151081ELIZAR1
Adder
8.641
3151091ELIZAR2
Adder
8.491
315835AF2-110_GEN
Solar/Wind Harmer
1.313
316305AF2-043 C
Solar/Wind Harmer
0.314
957871AF2-081 GEN
Solar/Wind Harmer
5.197
319010AE1-072 C
Solar/Wind Harmer
2.096
3146406KITTY HAWK
Solar/Wind Harmer
0.009
313526AB2-022
Solar/Wind Harmer
0.277
3146486SUNBURY
Solar/Wind Harmer
-0.01
3146486SUNBURY
Solar/Wind Harmer
-0.01
316321Z2-027
Solar/Wind Harmer
0.275
3146396TANGLEW
Solar/Wind Harmer
0.188
3145176PASQUOTANK
Solar/Wind Harmer
-0.006
316315AB2-025 C
Solar/Wind Harmer
0.274
962981AG1-147 GEN
Solar/Wind Harmer
4.424
315814AE2-033 C
Solar/Wind Harmer
9.398
315611Z1-036_GEN2
Solar/Wind Harmer
2.452
3130156CHOWAN
Solar/Wind Harmer
-0.01
3130156CHOWAN
Solar/Wind Harmer
-0.01
315816AE2-034 GEN
Solar/Wind Harmer
0.77
3130546PLYMOUTH
Solar/Wind Harmer
-0.009
315732AD1-074 GEN1
Solar/Wind Harmer
1.877
315733AD1-074 GEN2
Solar/Wind Harmer
1.877
315735AD1-075 GEN1
Solar/Wind Harmer
0.939
965291AG1-394 GEN
Solar/Wind Harmer
0.819
3146206CASHIE
Solar/Wind Harmer
-0.009
970601AG2-382 GEN
Solar/Wind Harmer
4.01
316318V4-068
Solar/Wind Harmer
0.227
3145893MURPHYS
Solar/Wind Harmer
-0.024
3145893MURPHYS
Solar/Wind Harmer
-0.009
3145513AHOSKIE
Solar/Wind Harmer
0.078
961941AG1-037 GEN
Solar/Wind Harmer
0.067
3145513AHOSKIE
Solar/Wind Harmer
-0.009
3145683EARLEYS
Solar/Wind Harmer
-0.018
3145683EARLEYS
Solar/Wind Harmer
-0.009
3145683EARLEYS
Solar/Wind Harmer
-0.009
3146043SEABORD
Solar/Wind Harmer
-0.009
315607AA1-063A GEN
Solar/Wind Harmer
0.889
946281AF1-292 GEN
Solar/Wind Harmer
0.197
316087AB2-174 GEN
Solar/Wind Harmer
1.24
315652AC1-086 GEN
Solar/Wind Harmer
9.778
3137643SOCKMAN
Solar/Wind Harmer
-0.034
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.034
3141813NORNECK
Solar/Wind Harmer
-0.008
941031AE2-094 GEN
Solar/Wind Harmer
15.551
944011AF1-069 GEN
Solar/Wind Harmer
4.873
970673AG2-436 GEN
Solar/Wind Harmer
17.185
970673AG2-436 GEN
Solar/Wind Harmer
8.701
972193AH1-681 GEN
Adder
1.66
971967AH1-528 GEN
Solar/Wind Harmer
15.234
316005AA1-067
Solar/Wind Harmer
0.163
3145746EVERETS
Solar/Wind Harmer
-0.032
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
970181AG2-120 GEN
Solar/Wind Harmer
1.058
957861AF2-080 GEN
Solar/Wind Harmer
3.451
970831AG2-522 GEN
Solar/Wind Harmer
3.911
316420AA1-050 GEN
Solar/Wind Harmer
0.891
970085AG2-068 GEN
Solar/Wind Harmer
4.868
970581AG2-369 GEN
Solar/Wind Harmer
4.186
3145573BETHELC
Solar/Wind Harmer
-0.008
3145573BETHELC
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.426
3141426STAFORD
Solar/Wind Helper
0.035
315052AA1-145 CT2
50/50
3.023
3142416OLDCHRC
Solar/Wind Harmer
-0.05
3142416OLDCHRC
Solar/Wind Harmer
-0.019
3143096IRON208
Adder
0.592
3142543TWELFTH
Solar/Wind Harmer
-0.002
3150851SPRUNCC
Adder
0.623
944631AF1-128 GEN
Adder
63.348
315671AE2-027_GEN
Solar/Wind Harmer
10.436
970129AG2-093 GEN
Solar/Wind Harmer
3.1
316458AB2-190 GEN2
Solar/Wind Harmer
1.369
3143526WINTERP
Solar/Wind Harmer
-0.069
3142433PROV 92
Solar/Wind Harmer
-0.053
3142433PROV 92
Adder
0.231
3142433PROV 92
Adder
0.231
971069AG2-661 GEN
Solar/Wind Harmer
2.087
971647AH1-324 GEN
Solar/Wind Harmer
6.327
316159AE1-175 C
Solar/Wind Harmer
0.338
961611AG1-000B GEN
Solar/Wind Harmer
6.095
3151171GRAVELC
Adder
1.133
971777AH1-397 GEN
Solar/Wind Harmer
1.406
3141843SHACKLE
Adder
0.544
3141766HARMONY
Solar/Wind Harmer
-0.002
970659AG2-427 GEN
Solar/Wind Harmer
6.329
316381AD1-082 GEN
Solar/Wind Harmer
1.085
971317AH1-138 GEN
Solar/Wind Harmer
1.474
3138126ROCKLANDING
Solar/Wind Harmer
0.036
970661AG2-428 GEN
Solar/Wind Harmer
12.321
3143226MDLTHAN
Solar/Wind Harmer
-0.011
3145336SMITFLD
Solar/Wind Harmer
-0.046
3138133OCRAN
Solar/Wind Harmer
-0.006
316072AD1-144
Solar/Wind Harmer
0.218
316375AC2-012 GEN
Solar/Wind Harmer
3.673
3150981CHESPKA
Adder
1.179
316093AE2-104_GEN
Solar/Wind Harmer
3.053
944591AF1-124 GEN
Solar/Wind Harmer
47.599
316246AF1-032 C
Solar/Wind Harmer
0.211
316388AE2-253 GEN
Solar/Wind Harmer
0.702
316294AC1-161 GEN
Solar/Wind Harmer
3.364
3146456SLIGO L269
Solar/Wind Harmer
-0.01
3146516WINFALL
Solar/Wind Harmer
-0.033
3146516WINFALL
Solar/Wind Harmer
-0.01
315800Z1-036_GEN1
Solar/Wind Harmer
2.452
961951AG1-038 GEN
Solar/Wind Harmer
1.291
3130156CHOWAN
Solar/Wind Harmer
-0.01
3145663CRESWEL
Solar/Wind Harmer
-0.027
971163AH1-040 GEN
Solar/Wind Harmer
8.923
962861AG1-135 GEN
Solar/Wind Harmer
3.537
3143336POWHATN
Solar/Wind Harmer
1.114
939411AE1-173 GEN
Solar/Wind Harmer
46.312
316023GEN1_S
Solar/Wind Harmer
0.618
3146206CASHIE
Solar/Wind Harmer
-0.009
971547AH1-271 GEN
Solar/Wind Harmer
2.291
3145893MURPHYS
Solar/Wind Harmer
-0.036
3145893MURPHYS
Solar/Wind Harmer
0.271
3146173TUNIS
Solar/Wind Harmer
-0.009
964211AG1-282 GEN
Solar/Wind Harmer
0.269
3141726DUNNSVL
Solar/Wind Harmer
-0.036
3145683EARLEYS
Solar/Wind Harmer
-0.009
940641AE2-051 GEN
Solar/Wind Harmer
8.315
316336AC2-165 C
Solar/Wind Harmer
1.536
3146263WOODLND
Solar/Wind Harmer
-0.009
960081AF2-299 GEN
Solar/Wind Harmer
0.988
3145963POPLR C
Solar/Wind Harmer
-0.009
316011AB1-132 GEN
Solar/Wind Harmer
1.818
962571AG1-106 GEN
Solar/Wind Harmer
1.249
3145823KELFORD
Solar/Wind Harmer
-0.009
316174AB2-169 GEN
Solar/Wind Harmer
1.334
316190AA2-174 GEN
Solar/Wind Harmer
0.105
3145796HORNRTN
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.008
971795AH1-408 GEN
Solar/Wind Harmer
6.346
3145783HORNRTN
Solar/Wind Harmer
-0.008
3150351NORNECKC2
Adder
0.745
3147043LAWRENC
Adder
0.669
3146293MARTNCO
Solar/Wind Harmer
0.051
316212AC1-099_GEN
Solar/Wind Harmer
0.72
972277AH1-723 GEN
Adder
43.302
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
315722AD1-056 GEN
Solar/Wind Harmer
0.835
316494AC1-189 GEN
Solar/Wind Harmer
0.849
970919AG2-571 GEN
Solar/Wind Harmer
2.473
970087AG2-069 GEN
Solar/Wind Harmer
7.301
316129AC1-054 GEN
Solar/Wind Harmer
0.679
961671AG1-007 GEN
Solar/Wind Harmer
0.098
3146083TARBORO
Solar/Wind Harmer
-0.008
3145493TOT1
Solar/Wind Harmer
0.23
3146233WITAKRS
Solar/Wind Harmer
-0.031
971065AG2-659 GEN
Solar/Wind Harmer
3.84
957481AF2-042 GEN
Solar/Wind Harmer
23.642
316359AB2-059 GEN
Solar/Wind Harmer
1.017
3144293JTRSVLE
Adder
0.2
316049AB1-081 GEN
Solar/Wind Harmer
0.009
315051AA1-145 CT1
50/50
3.01
971645AH1-323 GEN
50/50
18.076
316473AC1-191 GEN
Solar/Wind Harmer
2.106
3142416OLDCHRC
Solar/Wind Harmer
1.934
970293AG2-193 GEN
Solar/Wind Harmer
2.104
3143096IRON208
Adder
0.592
3143096IRON208
Adder
0.58
3150861SPRUNCD
Adder
0.623
3142946ENON
Solar/Wind Harmer
-0.005
970133AG2-095 GEN
Solar/Wind Harmer
1.593
965281AG1-393 GEN
Solar/Wind Harmer
1.713
315839AE2-212 C
Solar/Wind Harmer
0.411
970129AG2-093 GEN
Solar/Wind Harmer
7.654
3142433PROV 92
Adder
0.231
3142433PROV 92
Adder
0.231
315778AD1-151 GEN
Solar/Wind Harmer
11.428
971781AH1-399 GEN
Solar/Wind Harmer
0.777
316382AG1-145 C
Solar/Wind Harmer
0.379
315813AE1-149 C
Solar/Wind Harmer
7.719
961611AG1-000B GEN
Solar/Wind Harmer
2.601
3151221GRAVEL6
Adder
7.747
3151171GRAVELC
Adder
1.49
3141843SHACKLE
Adder
0.544
316203AE2-005 GEN
Solar/Wind Harmer
5.04
3141766HARMONY
Solar/Wind Harmer
1.063
970659AG2-427 GEN
Solar/Wind Harmer
1.122
316083AB2-161 GEN
Solar/Wind Harmer
1.92
316280AD1-041 GEN
Solar/Wind Harmer
0.886
3144216WINCHST
Adder
0.393
3142296MT RD221
50/50
0.652
3142366NRTHEST
50/50
0.559
3150691DARBY 3
50/50
11.994
3150701DARBY 4
50/50
11.966
3150681DARBY 2
50/50
11.952
966871AG1-558 GEN
Solar/Wind Harmer
0.588
966871AG1-558 GEN
Solar/Wind Harmer
0.201
3150671DARBY 1
Adder
11.25
316075AC2-137 C
Solar/Wind Harmer
0.43
944641AF1-129 GEN
Adder
62.773
3142946ENON
Solar/Wind Harmer
-0.002
316240AF1-291 C
Solar/Wind Harmer
0.437
3143526WINTERP
Solar/Wind Harmer
-0.069
316033AB2-134 GEN
Solar/Wind Harmer
4.177
315697AD1-025 GEN
Solar/Wind Harmer
2.62
316468AD1-105 GEN
Solar/Wind Harmer
1.404
316441AF1-014 GEN
Solar/Wind Harmer
0.806
970657AG2-426 GEN
Solar/Wind Harmer
3.67
970657AG2-426 GEN
Solar/Wind Harmer
0.767
971223AH1-071 GEN
Solar/Wind Harmer
1.434
316236AE1-162_GEN
Solar/Wind Harmer
0.345
316036AC1-147 C
Solar/Wind Harmer
0.286
3150991CHESPKB
Adder
0.989
3150991CHESPKB
Adder
0.966
316316AC1-027 C
Solar/Wind Harmer
0.324
3142956BIRDNECK
Solar/Wind Harmer
0.565
316185AD1-033 GEN
Solar/Wind Harmer
1.105
3145506HICKORY
Solar/Wind Harmer
-0.042
3145506HICKORY
Solar/Wind Harmer
-0.025
3145506HICKORY
Solar/Wind Harmer
-0.006
316339AD2-160 GEN
Solar/Wind Harmer
0.702
316018AA1-139 ULT2
Solar/Wind Harmer
0.89
316017AA1-139 ULT1
Solar/Wind Harmer
0.841
3137176SLIGO L2192
Solar/Wind Harmer
-0.041
3146456SLIGO L269
Solar/Wind Harmer
1.225
3130086AYDLETT
Solar/Wind Harmer
-0.041
3146386ELIZ CT
Solar/Wind Harmer
-0.01
316431W1029_GEN1
Solar/Wind Harmer
1.839
316433W1029_GEN2
Solar/Wind Harmer
1.839
3144356SAPONY
Solar/Wind Harmer
0.354
3146516WINFALL
Solar/Wind Harmer
-0.01
3146516WINFALL
Solar/Wind Harmer
-0.01
3146516WINFALL
Solar/Wind Harmer
-0.01
3146626S HERTFORD
Solar/Wind Harmer
-0.01
3146626S HERTFORD
Solar/Wind Harmer
-0.01
315742AE1-103 GEN
Solar/Wind Harmer
1.04
316487AF1-042 GEN
Solar/Wind Harmer
1.291
3146376EDENTON
Solar/Wind Harmer
0.29
3146376EDENTON
Solar/Wind Harmer
0.29
958261AF2-120 GEN
Solar/Wind Harmer
3.604
316065AD1-022 GEN
Solar/Wind Harmer
4.604
3145893MURPHYS
Solar/Wind Harmer
0.255
3145893MURPHYS
Solar/Wind Harmer
-0.016
3146173TUNIS
Solar/Wind Harmer
-0.009
3146173TUNIS
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
316181AB2-040 GEN
Solar/Wind Harmer
1.208
316426AA2-053 GEN
Solar/Wind Harmer
0.867
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.958
3145593CAROLNA
Solar/Wind Harmer
0.071
3145783HORNRTN
Solar/Wind Harmer
1.004
3145783HORNRTN
Solar/Wind Harmer
0.803
3145783HORNRTN
Solar/Wind Harmer
0.251
3145783HORNRTN
Solar/Wind Harmer
0.1
316077AC2-138 C
Solar/Wind Harmer
0.177
3150341NORNECKC1
Adder
0.783
3150341NORNECKC1
Adder
0.777
3145933PARMELE
Solar/Wind Harmer
-0.016
3145933PARMELE
Solar/Wind Harmer
-0.008
316274AC1-208 GEN
Solar/Wind Harmer
0.881
972185AH1-677 GEN
Adder
4.057
972187AH1-678 GEN
Adder
2.04
970933AG2-581 GEN
Solar/Wind Harmer
7.457
3145493TOT1
Solar/Wind Harmer
0.12
3145453TOT5
Solar/Wind Harmer
0.072
3145603CNETO
Solar/Wind Harmer
0.048
970099AG2-077 GEN
Solar/Wind Harmer
9.457
961601AG1-000A GEN
Solar/Wind Harmer
2.969
3144293JTRSVLE
Adder
0.2
3144293JTRSVLE
Adder
0.168
3150921YORKTN3
Adder
2.608
970661AG2-428 GEN
Solar/Wind Harmer
2.183
316156AD2-030 GEN
Solar/Wind Harmer
0.307
3141873WAN 176
Solar/Wind Harmer
1.363
3145336SMITFLD
Solar/Wind Harmer
-0.005
3144536CHRHLND
Solar/Wind Harmer
-0.002
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
8.752
944581AF1-123 GEN
Solar/Wind Harmer
47.428
944601AF1-125 GEN
Solar/Wind Harmer
46.688
315773AC2-141 GEN
Solar/Wind Harmer
4.351
3146456SLIGO L269
Solar/Wind Harmer
-0.01
971153AH1-033 GEN
Solar/Wind Harmer
1.264
316320Y1-086
Solar/Wind Harmer
0.601
316435W1029_GEN3
Solar/Wind Harmer
1.839
3145273HOLLAND
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.01
962971AG1-146 GEN
Solar/Wind Harmer
1.896
3146626S HERTFORD
Solar/Wind Harmer
-0.01
316484AD2-074 GEN
Solar/Wind Harmer
2.467
970009AG2-005 GEN
Solar/Wind Harmer
1.225
3146376EDENTON
Solar/Wind Harmer
-0.01
315614AA2-178 GEN
Solar/Wind Harmer
1.027
316313AB2-026
Solar/Wind Harmer
0.253
316258AE1-075 C
Solar/Wind Harmer
0.228
316405AF2-144 C
Solar/Wind Harmer
0.24
3143336POWHATN
Solar/Wind Harmer
0.947
971157AH1-035 GEN
Solar/Wind Harmer
1.165
316404AE1-155 C
Solar/Wind Harmer
1.794
3156081AA2-088 GEN
Solar/Wind Harmer
3.016
315737AD1-076 GEN
Solar/Wind Harmer
1.764
316365GEN2_N
Solar/Wind Harmer
0.618
3146206CASHIE
Solar/Wind Harmer
-0.009
3145893MURPHYS
Solar/Wind Harmer
0.064
3145893MURPHYS
Solar/Wind Harmer
-0.009
957521AF2-046 GEN
Solar/Wind Harmer
7.161
961681AG1-008 GEN
Solar/Wind Harmer
7.161
3146173TUNIS
Solar/Wind Harmer
-0.009
3156021HOLLOMANSOL
Solar/Wind Harmer
1.212
316463AE2-346 GEN
Solar/Wind Harmer
0.145
316140AB2-099
Solar/Wind Harmer
0.06
962331AG1-082 GEN
Solar/Wind Harmer
1.119
3146263WOODLND
Solar/Wind Harmer
-0.009
966621AG1-532 GEN
Solar/Wind Harmer
0.178
3145963POPLR C
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
316317KELFORD C
Solar/Wind Harmer
0.409
3145823KELFORD
Solar/Wind Harmer
-0.009
313506AB2-031 GEN
Solar/Wind Harmer
0.696
3145796HORNRTN
Solar/Wind Harmer
-0.034
3145796HORNRTN
Solar/Wind Harmer
-0.008
3150351NORNECKC2
Adder
0.758
3147043LAWRENC
Solar/Wind Harmer
-0.005
3145933PARMELE
Solar/Wind Harmer
-0.008
966801AG1-551 GEN
Solar/Wind Harmer
1.035
316210AC1-098 GEN
Solar/Wind Harmer
1.295
972255AH1-712 GEN
Adder
37.159
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
315724AD1-057 GEN
Solar/Wind Harmer
0.459
316327AA2-057 GEN
Solar/Wind Harmer
0.797
970917AG2-570 GEN
Solar/Wind Harmer
19.535
3146073TAR RVR
Solar/Wind Harmer
-0.008
3146083TARBORO
Solar/Wind Harmer
-0.008
3146233WITAKRS
Solar/Wind Harmer
0.161
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
961601AG1-000A GEN
Solar/Wind Harmer
3.006
3144293JTRSVLE
Adder
0.2
966881AG1-559 GEN
Solar/Wind Helper
1.211
NYPJM->LTFIMP_NY
CLTF
1.284
LGEELTFEXP_LGEE->PJM
CLTF
0.605
WECLTFEXP_WEC->PJM
CLTF
0.3
LAGNLTFEXP_LAGN->PJM
CLTF
3.19
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.228
TVALTFEXP_TVA->PJM
CLTF
1.617
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.295
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.575
MECLTFEXP_MEC->PJM
CLTF
1.594
SIGELTFEXP_SIGE->PJM
CLTF
0.049
CPLELTFEXP_CPLE->PJM
CLTF
4.149
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.083

Details for 6FOUR RIVERS-6STJOHN 230.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FOUR RIVERS-6STJOHN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 557T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:155.64 %
Rating:1360.0 MVA
Rating Type:C
MVA to Mitigate:2116.72
MW Contribution:53.82
Bus #Bus NameTypeMW Contribution
972189AH1-679 GEN
50/50
6.599
316312AB1-027
Solar/Wind Harmer
0.606
971285AH1-108 GEN
Adder
0.952
315976AC1-164 GENA
Solar/Wind Harmer
13.818
316169AC1-164_GENC
Solar/Wind Harmer
11.937
315975AC1-164 GENB
Solar/Wind Harmer
0.409
316233AE1-074 FULL
Solar/Wind Harmer
0.336
971281AH1-106 GEN
Solar/Wind Harmer
2.032
971283AH1-107 GEN
Solar/Wind Harmer
2.032
316132AB2-190 GEN1
Solar/Wind Harmer
1.252
971167AH1-042 GEN
Solar/Wind Harmer
11.871
3142433PROV 92
Adder
0.21
3142433PROV 92
Adder
0.21
316369SG1_INVT
Solar/Wind Harmer
2.106
3143873LANEXA
Solar/Wind Harmer
-0.007
3143316POE
Solar/Wind Harmer
-0.044
316314AB2-024 C
Solar/Wind Harmer
0.934
972265AH1-717 GEN
Adder
7.455
3151201GRAVEL4
Adder
6.989
3151191GRAVEL3
Adder
6.9
3151211GRAVEL5
Adder
6.9
316059AD1-063 C
Solar/Wind Harmer
0.241
315662AE1-191 GEN
Solar/Wind Harmer
1.265
315666AE1-190 GEN
Solar/Wind Harmer
0.316
971445AH1-216 GEN
Solar/Wind Harmer
6.385
957831AF2-077 GEN
Solar/Wind Harmer
0.31
3138283WHITEMARSH
Solar/Wind Harmer
0.016
957601AF2-054 GEN
Solar/Wind Harmer
0.306
3141873WAN 176
Solar/Wind Harmer
-0.002
972193AH1-681 GEN
Adder
2.064
315833AF1-017_GEN
Solar/Wind Harmer
1.883
316349AD2-085 GEN
Solar/Wind Harmer
0.882
316311AC2-079 GEN
Solar/Wind Harmer
4.995
3141913WHIT STONE
Solar/Wind Harmer
-0.01
3138133OCRAN
Solar/Wind Harmer
-0.003
3152611GOSPORTB
Adder
1.07
3152621GOSPORTC
Adder
0.908
3152601GOSPORTA
Adder
0.838
3141783LANCAST
Solar/Wind Harmer
-0.006
3141783LANCAST
Solar/Wind Harmer
-0.004
3151081ELIZAR1
Adder
7.683
3151091ELIZAR2
Adder
7.549
315835AF2-110_GEN
Solar/Wind Harmer
1.173
316305AF2-043 C
Solar/Wind Harmer
0.28
957871AF2-081 GEN
Solar/Wind Harmer
4.621
316315AB2-025 C
Solar/Wind Harmer
0.249
319010AE1-072 C
Solar/Wind Harmer
1.864
3146406KITTY HAWK
Solar/Wind Harmer
0.008
315814AE2-033 C
Solar/Wind Harmer
8.547
3146486SUNBURY
Solar/Wind Harmer
-0.009
3146486SUNBURY
Solar/Wind Harmer
-0.009
313526AB2-022
Solar/Wind Harmer
0.246
316321Z2-027
Solar/Wind Harmer
0.245
3146396TANGLEW
Solar/Wind Harmer
0.167
3145176PASQUOTANK
Solar/Wind Harmer
-0.006
962981AG1-147 GEN
Solar/Wind Harmer
3.897
315611Z1-036_GEN2
Solar/Wind Harmer
2.19
3130156CHOWAN
Solar/Wind Harmer
-0.009
3130156CHOWAN
Solar/Wind Harmer
-0.009
315816AE2-034 GEN
Solar/Wind Harmer
0.691
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315732AD1-074 GEN1
Solar/Wind Harmer
1.687
315733AD1-074 GEN2
Solar/Wind Harmer
1.687
315735AD1-075 GEN1
Solar/Wind Harmer
0.844
965291AG1-394 GEN
Solar/Wind Harmer
0.739
3146206CASHIE
Solar/Wind Harmer
-0.008
970601AG2-382 GEN
Solar/Wind Harmer
3.608
316318V4-068
Solar/Wind Harmer
0.205
3145893MURPHYS
Solar/Wind Harmer
-0.022
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145513AHOSKIE
Solar/Wind Harmer
0.07
961941AG1-037 GEN
Solar/Wind Harmer
0.061
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3146043SEABORD
Solar/Wind Harmer
-0.008
946281AF1-292 GEN
Solar/Wind Harmer
0.179
315607AA1-063A GEN
Solar/Wind Harmer
0.805
316087AB2-174 GEN
Solar/Wind Harmer
1.129
315652AC1-086 GEN
Solar/Wind Harmer
8.886
3137643SOCKMAN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.03
941031AE2-094 GEN
Solar/Wind Harmer
13.924
944011AF1-069 GEN
Solar/Wind Harmer
4.363
970673AG2-436 GEN
Solar/Wind Harmer
15.41
970673AG2-436 GEN
Solar/Wind Harmer
7.803
316005AA1-067
Solar/Wind Harmer
0.148
3145746EVERETS
Solar/Wind Harmer
-0.029
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
970181AG2-120 GEN
Solar/Wind Harmer
0.961
971967AH1-528 GEN
Solar/Wind Harmer
13.691
3141813NORNECK
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
3.14
970831AG2-522 GEN
Solar/Wind Harmer
3.576
316420AA1-050 GEN
Solar/Wind Harmer
0.812
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
316319Z2-044 C
Solar/Wind Harmer
0.389
970085AG2-068 GEN
Solar/Wind Harmer
4.386
970581AG2-369 GEN
Solar/Wind Harmer
3.772
3141426STAFORD
Solar/Wind Helper
0.036
315052AA1-145 CT2
50/50
2.957
3142416OLDCHRC
Solar/Wind Harmer
-0.046
3142416OLDCHRC
Solar/Wind Harmer
-0.018
3142543TWELFTH
Solar/Wind Harmer
-0.001
3143096IRON208
Adder
0.55
3150851SPRUNCC
Adder
0.582
944631AF1-128 GEN
Adder
58.193
315671AE2-027_GEN
Solar/Wind Harmer
9.633
3143526WINTERP
Solar/Wind Harmer
-0.065
970129AG2-093 GEN
Solar/Wind Harmer
2.837
316458AB2-190 GEN2
Solar/Wind Harmer
1.252
3142433PROV 92
Solar/Wind Harmer
-0.048
3142433PROV 92
Adder
0.21
3142433PROV 92
Adder
0.21
971069AG2-661 GEN
Solar/Wind Harmer
1.903
971647AH1-324 GEN
Solar/Wind Harmer
5.741
316159AE1-175 C
Solar/Wind Harmer
0.302
961611AG1-000B GEN
Solar/Wind Harmer
5.514
970659AG2-427 GEN
Solar/Wind Harmer
5.758
3151171GRAVELC
Adder
1.021
316381AD1-082 GEN
Solar/Wind Harmer
0.986
971777AH1-397 GEN
Solar/Wind Harmer
1.258
3141843SHACKLE
Adder
0.487
3143226MDLTHAN
Solar/Wind Harmer
-0.011
3141766HARMONY
Solar/Wind Harmer
-0.002
970661AG2-428 GEN
Solar/Wind Harmer
11.169
971317AH1-138 GEN
Solar/Wind Harmer
1.31
3138126ROCKLANDING
Solar/Wind Harmer
0.032
3145336SMITFLD
Solar/Wind Harmer
-0.041
972277AH1-723 GEN
Adder
53.824
3138133OCRAN
Solar/Wind Harmer
-0.006
316072AD1-144
Solar/Wind Harmer
0.194
316375AC2-012 GEN
Solar/Wind Harmer
3.267
3150981CHESPKA
Adder
1.049
316093AE2-104_GEN
Solar/Wind Harmer
2.729
316246AF1-032 C
Solar/Wind Harmer
0.188
944591AF1-124 GEN
Solar/Wind Harmer
42.223
316388AE2-253 GEN
Solar/Wind Harmer
0.624
3146456SLIGO L269
Solar/Wind Harmer
-0.009
316294AC1-161 GEN
Solar/Wind Harmer
2.965
3146516WINFALL
Solar/Wind Harmer
-0.029
3146516WINFALL
Solar/Wind Harmer
-0.009
3143336POWHATN
Solar/Wind Harmer
1.054
315800Z1-036_GEN1
Solar/Wind Harmer
2.19
3130156CHOWAN
Solar/Wind Harmer
-0.009
961951AG1-038 GEN
Solar/Wind Harmer
1.134
3145663CRESWEL
Solar/Wind Harmer
-0.024
971163AH1-040 GEN
Solar/Wind Harmer
8
316336AC2-165 C
Solar/Wind Harmer
1.462
316023GEN1_S
Solar/Wind Harmer
0.562
962861AG1-135 GEN
Solar/Wind Harmer
3.096
3146206CASHIE
Solar/Wind Harmer
-0.008
971547AH1-271 GEN
Solar/Wind Harmer
2.062
939411AE1-173 GEN
Solar/Wind Harmer
41.202
3145893MURPHYS
Solar/Wind Harmer
-0.033
3145893MURPHYS
Solar/Wind Harmer
0.244
3146173TUNIS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
960081AF2-299 GEN
Solar/Wind Harmer
0.9
3146263WOODLND
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.653
962571AG1-106 GEN
Solar/Wind Harmer
1.135
940641AE2-051 GEN
Solar/Wind Harmer
7.402
3145963POPLR C
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
316174AB2-169 GEN
Solar/Wind Harmer
1.205
316190AA2-174 GEN
Solar/Wind Harmer
0.096
964211AG1-282 GEN
Solar/Wind Harmer
0.234
3141726DUNNSVL
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.008
971795AH1-408 GEN
Solar/Wind Harmer
5.796
3145783HORNRTN
Solar/Wind Harmer
-0.008
3147043LAWRENC
Adder
0.612
3146293MARTNCO
Solar/Wind Harmer
0.046
316212AC1-099_GEN
Solar/Wind Harmer
0.654
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.761
3150351NORNECKC2
Adder
0.644
970937AG2-583 GEN
Solar/Wind Harmer
5.179
316494AC1-189 GEN
Solar/Wind Harmer
0.772
316129AC1-054 GEN
Solar/Wind Harmer
0.621
961671AG1-007 GEN
Solar/Wind Harmer
0.089
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.209
3146233WITAKRS
Solar/Wind Harmer
-0.028
970919AG2-571 GEN
Solar/Wind Harmer
2.227
971065AG2-659 GEN
Solar/Wind Harmer
3.515
970087AG2-069 GEN
Solar/Wind Harmer
6.579
316359AB2-059 GEN
Solar/Wind Harmer
0.929
316049AB1-081 GEN
Solar/Wind Harmer
0.744
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3142053HEARTS
Solar/Wind Harmer
0.081
3144293JTRSVLE
Adder
0.187
957481AF2-042 GEN
Solar/Wind Harmer
15.11
3142296MT RD221
50/50
0.619
3142366NRTHEST
50/50
0.524
3150691DARBY 3
50/50
11.2
3150701DARBY 4
50/50
11.174
3150681DARBY 2
50/50
11.161
966871AG1-558 GEN
Solar/Wind Harmer
0.556
966871AG1-558 GEN
Solar/Wind Harmer
0.19
3150671DARBY 1
Adder
10.506
316075AC2-137 C
Solar/Wind Harmer
0.395
944641AF1-129 GEN
Adder
58.224
3142946ENON
Solar/Wind Harmer
-0.001
316240AF1-291 C
Solar/Wind Harmer
0.405
3143526WINTERP
Solar/Wind Harmer
-0.065
316033AB2-134 GEN
Solar/Wind Harmer
3.801
315697AD1-025 GEN
Solar/Wind Harmer
2.384
316468AD1-105 GEN
Solar/Wind Harmer
1.304
316441AF1-014 GEN
Solar/Wind Harmer
0.721
971223AH1-071 GEN
Solar/Wind Harmer
1.334
970657AG2-426 GEN
Solar/Wind Harmer
3.332
970657AG2-426 GEN
Solar/Wind Harmer
0.697
316236AE1-162_GEN
Solar/Wind Harmer
0.31
316036AC1-147 C
Solar/Wind Harmer
0.255
3150991CHESPKB
Adder
0.88
3150991CHESPKB
Adder
0.859
316316AC1-027 C
Solar/Wind Harmer
0.288
3142956BIRDNECK
Solar/Wind Harmer
0.502
316185AD1-033 GEN
Solar/Wind Harmer
0.982
3145506HICKORY
Solar/Wind Harmer
-0.037
3145506HICKORY
Solar/Wind Harmer
-0.022
3145506HICKORY
Solar/Wind Harmer
-0.006
316339AD2-160 GEN
Solar/Wind Harmer
0.624
316018AA1-139 ULT2
Solar/Wind Harmer
0.792
316017AA1-139 ULT1
Solar/Wind Harmer
0.748
3137176SLIGO L2192
Solar/Wind Harmer
-0.037
3144356SAPONY
Solar/Wind Harmer
0.322
3146456SLIGO L269
Solar/Wind Harmer
1.089
3130086AYDLETT
Solar/Wind Harmer
-0.037
3146386ELIZ CT
Solar/Wind Harmer
-0.009
316431W1029_GEN1
Solar/Wind Harmer
1.64
316433W1029_GEN2
Solar/Wind Harmer
1.64
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
315742AE1-103 GEN
Solar/Wind Harmer
0.934
3146376EDENTON
Solar/Wind Harmer
0.26
3146376EDENTON
Solar/Wind Harmer
0.26
316487AF1-042 GEN
Solar/Wind Harmer
1.134
316065AD1-022 GEN
Solar/Wind Harmer
4.14
3145893MURPHYS
Solar/Wind Harmer
0.23
3145893MURPHYS
Solar/Wind Harmer
-0.015
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
958261AF2-120 GEN
Solar/Wind Harmer
3.149
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
316181AB2-040 GEN
Solar/Wind Harmer
1.099
316426AA2-053 GEN
Solar/Wind Harmer
0.787
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.871
3145593CAROLNA
Solar/Wind Harmer
0.064
3145783HORNRTN
Solar/Wind Harmer
0.913
3145783HORNRTN
Solar/Wind Harmer
0.73
3145783HORNRTN
Solar/Wind Harmer
0.228
3145783HORNRTN
Solar/Wind Harmer
0.091
3145933PARMELE
Solar/Wind Harmer
-0.015
3145933PARMELE
Solar/Wind Harmer
-0.007
316274AC1-208 GEN
Solar/Wind Harmer
0.802
972185AH1-677 GEN
Adder
3.641
316077AC2-138 C
Solar/Wind Harmer
0.153
3150341NORNECKC1
Adder
0.677
3150341NORNECKC1
Adder
0.671
972187AH1-678 GEN
Adder
1.832
970933AG2-581 GEN
Solar/Wind Harmer
6.725
3145493TOT1
Solar/Wind Harmer
0.109
3145453TOT5
Solar/Wind Harmer
0.065
3145603CNETO
Solar/Wind Harmer
0.044
961601AG1-000A GEN
Solar/Wind Harmer
2.713
316263AC1-034 GEN
Solar/Wind Harmer
3.231
3144293JTRSVLE
Adder
0.187
3144293JTRSVLE
Adder
0.157
970099AG2-077 GEN
Solar/Wind Harmer
6.044
315051AA1-145 CT1
50/50
2.944
971645AH1-323 GEN
50/50
17.203
316473AC1-191 GEN
Solar/Wind Harmer
1.991
3142416OLDCHRC
Solar/Wind Harmer
1.812
970293AG2-193 GEN
Solar/Wind Harmer
1.95
3143096IRON208
Adder
0.55
3143096IRON208
Adder
0.539
3150861SPRUNCD
Adder
0.582
3142946ENON
Solar/Wind Harmer
-0.004
970133AG2-095 GEN
Solar/Wind Harmer
1.464
965281AG1-393 GEN
Solar/Wind Harmer
1.58
315839AE2-212 C
Solar/Wind Harmer
0.379
970129AG2-093 GEN
Solar/Wind Harmer
7.004
3142433PROV 92
Adder
0.21
3142433PROV 92
Adder
0.21
315778AD1-151 GEN
Solar/Wind Harmer
10.421
971781AH1-399 GEN
Solar/Wind Harmer
0.721
315813AE1-149 C
Solar/Wind Harmer
7.054
316382AG1-145 C
Solar/Wind Harmer
0.339
961611AG1-000B GEN
Solar/Wind Harmer
2.353
970659AG2-427 GEN
Solar/Wind Harmer
1.02
3151221GRAVEL6
Adder
6.981
3151171GRAVELC
Adder
1.343
316083AB2-161 GEN
Solar/Wind Harmer
1.746
3141843SHACKLE
Adder
0.487
316203AE2-005 GEN
Solar/Wind Harmer
4.508
3141766HARMONY
Solar/Wind Harmer
0.949
970661AG2-428 GEN
Solar/Wind Harmer
1.979
316280AD1-041 GEN
Solar/Wind Harmer
0.791
3144216WINCHST
Adder
0.35
3150921YORKTN3
Adder
2.319
3145336SMITFLD
Solar/Wind Harmer
-0.004
316156AD2-030 GEN
Solar/Wind Harmer
0.273
3141873WAN 176
Solar/Wind Harmer
1.214
972255AH1-712 GEN
Adder
46.189
3144536CHRHLND
Solar/Wind Harmer
-0.001
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
7.781
944581AF1-123 GEN
Solar/Wind Harmer
42.072
944601AF1-125 GEN
Solar/Wind Harmer
41.415
3146456SLIGO L269
Solar/Wind Harmer
-0.009
971153AH1-033 GEN
Solar/Wind Harmer
1.124
315773AC2-141 GEN
Solar/Wind Harmer
3.835
316320Y1-086
Solar/Wind Harmer
0.535
3145273HOLLAND
Solar/Wind Harmer
-0.007
316435W1029_GEN3
Solar/Wind Harmer
1.64
3146516WINFALL
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
962971AG1-146 GEN
Solar/Wind Harmer
1.67
316313AB2-026
Solar/Wind Harmer
0.239
316258AE1-075 C
Solar/Wind Harmer
0.216
316405AF2-144 C
Solar/Wind Harmer
0.227
3143336POWHATN
Solar/Wind Harmer
0.896
3146376EDENTON
Solar/Wind Harmer
-0.009
316484AD2-074 GEN
Solar/Wind Harmer
2.167
970009AG2-005 GEN
Solar/Wind Harmer
1.076
315614AA2-178 GEN
Solar/Wind Harmer
0.921
3156081AA2-088 GEN
Solar/Wind Harmer
2.72
971157AH1-035 GEN
Solar/Wind Harmer
1.046
315737AD1-076 GEN
Solar/Wind Harmer
1.585
316365GEN2_N
Solar/Wind Harmer
0.562
3146206CASHIE
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.057
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.463
961681AG1-008 GEN
Solar/Wind Harmer
6.463
3146173TUNIS
Solar/Wind Harmer
-0.008
316404AE1-155 C
Solar/Wind Harmer
1.568
3156021HOLLOMANSOL
Solar/Wind Harmer
1.093
316463AE2-346 GEN
Solar/Wind Harmer
0.131
316140AB2-099
Solar/Wind Harmer
0.054
962331AG1-082 GEN
Solar/Wind Harmer
1.011
966621AG1-532 GEN
Solar/Wind Harmer
0.162
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145963POPLR C
Solar/Wind Harmer
-0.008
313506AB2-031 GEN
Solar/Wind Harmer
0.633
316317KELFORD C
Solar/Wind Harmer
0.37
3145823KELFORD
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.005
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.938
316210AC1-098 GEN
Solar/Wind Harmer
1.177
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.419
3150351NORNECKC2
Adder
0.655
316327AA2-057 GEN
Solar/Wind Harmer
0.726
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
0.147
3146233WITAKRS
Solar/Wind Harmer
-0.005
970917AG2-570 GEN
Solar/Wind Harmer
17.597
3138543CONSLDL
Solar/Wind Harmer
-0.005
961601AG1-000A GEN
Solar/Wind Harmer
2.747
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3144293JTRSVLE
Adder
0.187
966881AG1-559 GEN
Solar/Wind Helper
1.226
NYPJM->LTFIMP_NY
CLTF
1.281
LGEELTFEXP_LGEE->PJM
CLTF
0.645
WECLTFEXP_WEC->PJM
CLTF
0.321
LAGNLTFEXP_LAGN->PJM
CLTF
3.191
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.768
TVALTFEXP_TVA->PJM
CLTF
1.622
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.114
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.629
MECLTFEXP_MEC->PJM
CLTF
1.67
SIGELTFEXP_SIGE->PJM
CLTF
0.052
CPLELTFEXP_CPLE->PJM
CLTF
3.869
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.403

Details for 6FOUR RIVERS-6STJOHN 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FOUR RIVERS-6STJOHN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:153.64 %
Rating:1360.0 MVA
Rating Type:C
MVA to Mitigate:2089.52
MW Contribution:45.63
Bus #Bus NameTypeMW Contribution
972189AH1-679 GEN
50/50
6.194
316312AB1-027
Solar/Wind Harmer
0.576
971285AH1-108 GEN
Adder
0.913
315976AC1-164 GENA
Solar/Wind Harmer
14.026
316169AC1-164_GENC
Solar/Wind Harmer
12.118
315975AC1-164 GENB
Solar/Wind Harmer
0.415
316132AB2-190 GEN1
Solar/Wind Harmer
1.25
971167AH1-042 GEN
Solar/Wind Harmer
11.756
3142433PROV 92
Adder
0.208
3142433PROV 92
Adder
0.208
316233AE1-074 FULL
Solar/Wind Harmer
0.323
971281AH1-106 GEN
Solar/Wind Harmer
1.95
971283AH1-107 GEN
Solar/Wind Harmer
1.95
316369SG1_INVT
Solar/Wind Harmer
2.124
3143873LANEXA
Solar/Wind Harmer
-0.007
3143316POE
Solar/Wind Harmer
-0.044
972265AH1-717 GEN
Adder
7.667
3151201GRAVEL4
Adder
7.188
3151191GRAVEL3
Adder
7.097
3151211GRAVEL5
Adder
7.097
316314AB2-024 C
Solar/Wind Harmer
0.945
316059AD1-063 C
Solar/Wind Harmer
0.244
971445AH1-216 GEN
Solar/Wind Harmer
6.627
957831AF2-077 GEN
Solar/Wind Harmer
0.32
3138283WHITEMARSH
Solar/Wind Harmer
0.016
315662AE1-191 GEN
Solar/Wind Harmer
1.277
315666AE1-190 GEN
Solar/Wind Harmer
0.319
957601AF2-054 GEN
Solar/Wind Harmer
0.309
3141873WAN 176
Solar/Wind Harmer
-0.002
315833AF1-017_GEN
Solar/Wind Harmer
1.946
316349AD2-085 GEN
Solar/Wind Harmer
0.911
316311AC2-079 GEN
Solar/Wind Harmer
5.164
3152611GOSPORTB
Adder
1.132
3152621GOSPORTC
Adder
0.961
3152601GOSPORTA
Adder
0.886
3151081ELIZAR1
Adder
8.134
3151091ELIZAR2
Adder
7.993
3141913WHIT STONE
Solar/Wind Harmer
-0.01
315835AF2-110_GEN
Solar/Wind Harmer
1.23
316305AF2-043 C
Solar/Wind Harmer
0.295
957871AF2-081 GEN
Solar/Wind Harmer
4.895
319010AE1-072 C
Solar/Wind Harmer
1.974
3146406KITTY HAWK
Solar/Wind Harmer
0.008
3138133OCRAN
Solar/Wind Harmer
-0.003
313526AB2-022
Solar/Wind Harmer
0.26
3146486SUNBURY
Solar/Wind Harmer
-0.01
3146486SUNBURY
Solar/Wind Harmer
-0.01
316321Z2-027
Solar/Wind Harmer
0.259
3146396TANGLEW
Solar/Wind Harmer
0.177
3145176PASQUOTANK
Solar/Wind Harmer
-0.006
3141783LANCAST
Solar/Wind Harmer
-0.006
3141783LANCAST
Solar/Wind Harmer
-0.004
316315AB2-025 C
Solar/Wind Harmer
0.252
315611Z1-036_GEN2
Solar/Wind Harmer
2.306
315814AE2-033 C
Solar/Wind Harmer
8.672
3130156CHOWAN
Solar/Wind Harmer
-0.009
3130156CHOWAN
Solar/Wind Harmer
-0.009
315816AE2-034 GEN
Solar/Wind Harmer
0.724
962981AG1-147 GEN
Solar/Wind Harmer
3.875
3130546PLYMOUTH
Solar/Wind Harmer
-0.009
315732AD1-074 GEN1
Solar/Wind Harmer
1.763
315733AD1-074 GEN2
Solar/Wind Harmer
1.763
315735AD1-075 GEN1
Solar/Wind Harmer
0.882
965291AG1-394 GEN
Solar/Wind Harmer
0.768
3146206CASHIE
Solar/Wind Harmer
-0.009
970601AG2-382 GEN
Solar/Wind Harmer
3.765
972193AH1-681 GEN
Adder
1.749
316318V4-068
Solar/Wind Harmer
0.213
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.009
3145513AHOSKIE
Solar/Wind Harmer
0.073
961941AG1-037 GEN
Solar/Wind Harmer
0.063
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3146043SEABORD
Solar/Wind Harmer
-0.008
315607AA1-063A GEN
Solar/Wind Harmer
0.832
946281AF1-292 GEN
Solar/Wind Harmer
0.183
315652AC1-086 GEN
Solar/Wind Harmer
9.13
316087AB2-174 GEN
Solar/Wind Harmer
1.157
3137643SOCKMAN
Solar/Wind Harmer
-0.032
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.031
941031AE2-094 GEN
Solar/Wind Harmer
14.557
944011AF1-069 GEN
Solar/Wind Harmer
4.561
970673AG2-436 GEN
Solar/Wind Harmer
16.092
970673AG2-436 GEN
Solar/Wind Harmer
8.148
971967AH1-528 GEN
Solar/Wind Harmer
14.27
316005AA1-067
Solar/Wind Harmer
0.153
3145746EVERETS
Solar/Wind Harmer
-0.03
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
970181AG2-120 GEN
Solar/Wind Harmer
0.995
957861AF2-080 GEN
Solar/Wind Harmer
3.242
970831AG2-522 GEN
Solar/Wind Harmer
3.667
316420AA1-050 GEN
Solar/Wind Harmer
0.837
970085AG2-068 GEN
Solar/Wind Harmer
4.564
970581AG2-369 GEN
Solar/Wind Harmer
3.925
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
316319Z2-044 C
Solar/Wind Harmer
0.4
3141426STAFORD
Solar/Wind Helper
0.041
3142296MT RD221
50/50
0.575
3142366NRTHEST
50/50
0.498
3150691DARBY 3
50/50
10.722
3150701DARBY 4
50/50
10.697
3150681DARBY 2
50/50
10.684
966871AG1-558 GEN
Solar/Wind Harmer
0.512
966871AG1-558 GEN
Solar/Wind Harmer
0.175
3150671DARBY 1
Adder
10.057
316075AC2-137 C
Solar/Wind Harmer
0.39
3142946ENON
Solar/Wind Harmer
-0.001
944641AF1-129 GEN
Adder
56.545
316240AF1-291 C
Solar/Wind Harmer
0.394
3143526WINTERP
Solar/Wind Harmer
-0.062
316033AB2-134 GEN
Solar/Wind Harmer
3.833
315697AD1-025 GEN
Solar/Wind Harmer
2.404
970657AG2-426 GEN
Solar/Wind Harmer
3.381
970657AG2-426 GEN
Solar/Wind Harmer
0.707
316441AF1-014 GEN
Solar/Wind Harmer
0.727
316236AE1-162_GEN
Solar/Wind Harmer
0.322
971223AH1-071 GEN
Solar/Wind Harmer
1.287
316468AD1-105 GEN
Solar/Wind Harmer
1.118
316036AC1-147 C
Solar/Wind Harmer
0.269
3150991CHESPKB
Adder
0.931
3150991CHESPKB
Adder
0.909
316316AC1-027 C
Solar/Wind Harmer
0.305
3142956BIRDNECK
Solar/Wind Harmer
0.532
316185AD1-033 GEN
Solar/Wind Harmer
1.041
3145506HICKORY
Solar/Wind Harmer
-0.039
3145506HICKORY
Solar/Wind Harmer
-0.024
3145506HICKORY
Solar/Wind Harmer
-0.006
316339AD2-160 GEN
Solar/Wind Harmer
0.661
316018AA1-139 ULT2
Solar/Wind Harmer
0.839
316017AA1-139 ULT1
Solar/Wind Harmer
0.792
3137176SLIGO L2192
Solar/Wind Harmer
-0.039
3146456SLIGO L269
Solar/Wind Harmer
1.154
3130086AYDLETT
Solar/Wind Harmer
-0.039
3146386ELIZ CT
Solar/Wind Harmer
-0.01
316431W1029_GEN1
Solar/Wind Harmer
1.73
316433W1029_GEN2
Solar/Wind Harmer
1.73
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3144356SAPONY
Solar/Wind Harmer
0.326
315742AE1-103 GEN
Solar/Wind Harmer
0.975
3146376EDENTON
Solar/Wind Harmer
0.273
3146376EDENTON
Solar/Wind Harmer
0.273
316065AD1-022 GEN
Solar/Wind Harmer
4.323
3145893MURPHYS
Solar/Wind Harmer
0.239
3145893MURPHYS
Solar/Wind Harmer
-0.015
316487AF1-042 GEN
Solar/Wind Harmer
1.122
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
316181AB2-040 GEN
Solar/Wind Harmer
1.127
316426AA2-053 GEN
Solar/Wind Harmer
0.812
958261AF2-120 GEN
Solar/Wind Harmer
3.091
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.896
3145593CAROLNA
Solar/Wind Harmer
0.066
3145783HORNRTN
Solar/Wind Harmer
0.939
3145783HORNRTN
Solar/Wind Harmer
0.751
3145783HORNRTN
Solar/Wind Harmer
0.235
3145783HORNRTN
Solar/Wind Harmer
0.094
3145933PARMELE
Solar/Wind Harmer
-0.015
3145933PARMELE
Solar/Wind Harmer
-0.008
316274AC1-208 GEN
Solar/Wind Harmer
0.826
972185AH1-677 GEN
Adder
3.8
972187AH1-678 GEN
Adder
1.911
970933AG2-581 GEN
Solar/Wind Harmer
6.989
3145493TOT1
Solar/Wind Harmer
0.112
3145453TOT5
Solar/Wind Harmer
0.067
3145603CNETO
Solar/Wind Harmer
0.045
970099AG2-077 GEN
Solar/Wind Harmer
8.877
961601AG1-000A GEN
Solar/Wind Harmer
2.788
3150341NORNECKC1
Adder
0.653
3150341NORNECKC1
Adder
0.647
3144293JTRSVLE
Adder
0.188
3144293JTRSVLE
Adder
0.158
315052AA1-145 CT2
50/50
2.775
3142416OLDCHRC
Solar/Wind Harmer
-0.044
3142416OLDCHRC
Solar/Wind Harmer
-0.017
3143096IRON208
Adder
0.533
3142543TWELFTH
Solar/Wind Harmer
-0.001
3150851SPRUNCC
Adder
0.558
944631AF1-128 GEN
Adder
57.465
315671AE2-027_GEN
Solar/Wind Harmer
9.434
970129AG2-093 GEN
Solar/Wind Harmer
2.829
316458AB2-190 GEN2
Solar/Wind Harmer
1.25
971069AG2-661 GEN
Solar/Wind Harmer
1.911
3142433PROV 92
Solar/Wind Harmer
-0.048
3142433PROV 92
Adder
0.208
3142433PROV 92
Adder
0.208
3143526WINTERP
Solar/Wind Harmer
-0.062
316159AE1-175 C
Solar/Wind Harmer
0.314
971647AH1-324 GEN
Solar/Wind Harmer
5.822
961611AG1-000B GEN
Solar/Wind Harmer
5.626
3151171GRAVELC
Adder
1.05
971317AH1-138 GEN
Solar/Wind Harmer
1.372
970659AG2-427 GEN
Solar/Wind Harmer
5.82
3138126ROCKLANDING
Solar/Wind Harmer
0.033
316381AD1-082 GEN
Solar/Wind Harmer
0.999
971777AH1-397 GEN
Solar/Wind Harmer
1.268
3141843SHACKLE
Adder
0.49
3141766HARMONY
Solar/Wind Harmer
-0.002
970661AG2-428 GEN
Solar/Wind Harmer
11.374
3145336SMITFLD
Solar/Wind Harmer
-0.042
3143226MDLTHAN
Solar/Wind Harmer
-0.01
316072AD1-144
Solar/Wind Harmer
0.204
316375AC2-012 GEN
Solar/Wind Harmer
3.456
3150981CHESPKA
Adder
1.11
316294AC1-161 GEN
Solar/Wind Harmer
3.195
316093AE2-104_GEN
Solar/Wind Harmer
2.862
944591AF1-124 GEN
Solar/Wind Harmer
44.917
316388AE2-253 GEN
Solar/Wind Harmer
0.661
316246AF1-032 C
Solar/Wind Harmer
0.198
3146456SLIGO L269
Solar/Wind Harmer
-0.01
3138133OCRAN
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.031
3146516WINFALL
Solar/Wind Harmer
-0.009
315800Z1-036_GEN1
Solar/Wind Harmer
2.306
3130156CHOWAN
Solar/Wind Harmer
-0.009
3145663CRESWEL
Solar/Wind Harmer
-0.025
971163AH1-040 GEN
Solar/Wind Harmer
8.387
939411AE1-173 GEN
Solar/Wind Harmer
43.516
3146206CASHIE
Solar/Wind Harmer
-0.009
971547AH1-271 GEN
Solar/Wind Harmer
2.151
972277AH1-723 GEN
Adder
45.628
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.254
3143336POWHATN
Solar/Wind Harmer
1.014
316023GEN1_S
Solar/Wind Harmer
0.575
961951AG1-038 GEN
Solar/Wind Harmer
1.122
3146173TUNIS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
940641AE2-051 GEN
Solar/Wind Harmer
7.803
3146263WOODLND
Solar/Wind Harmer
-0.008
3145963POPLR C
Solar/Wind Harmer
-0.008
960081AF2-299 GEN
Solar/Wind Harmer
0.921
3145823KELFORD
Solar/Wind Harmer
-0.008
316174AB2-169 GEN
Solar/Wind Harmer
1.253
962861AG1-135 GEN
Solar/Wind Harmer
3.045
316011AB1-132 GEN
Solar/Wind Harmer
1.698
962571AG1-106 GEN
Solar/Wind Harmer
1.167
316336AC2-165 C
Solar/Wind Harmer
1.404
316190AA2-174 GEN
Solar/Wind Harmer
0.099
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
3145783HORNRTN
Solar/Wind Harmer
-0.008
971795AH1-408 GEN
Solar/Wind Harmer
5.922
3146293MARTNCO
Solar/Wind Harmer
0.048
3147043LAWRENC
Adder
0.625
316212AC1-099_GEN
Solar/Wind Harmer
0.675
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
964211AG1-282 GEN
Solar/Wind Harmer
0.227
3141726DUNNSVL
Solar/Wind Harmer
-0.03
315722AD1-056 GEN
Solar/Wind Harmer
0.782
316494AC1-189 GEN
Solar/Wind Harmer
0.797
970919AG2-571 GEN
Solar/Wind Harmer
2.318
970087AG2-069 GEN
Solar/Wind Harmer
6.846
316129AC1-054 GEN
Solar/Wind Harmer
0.637
961671AG1-007 GEN
Solar/Wind Harmer
0.092
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.216
3146233WITAKRS
Solar/Wind Harmer
-0.029
971065AG2-659 GEN
Solar/Wind Harmer
3.603
957481AF2-042 GEN
Solar/Wind Harmer
22.193
316359AB2-059 GEN
Solar/Wind Harmer
0.955
3150351NORNECKC2
Adder
0.621
3144293JTRSVLE
Adder
0.188
316049AB1-081 GEN
Solar/Wind Harmer
0.15
315051AA1-145 CT1
50/50
2.763
971645AH1-323 GEN
50/50
15.894
3142416OLDCHRC
Solar/Wind Harmer
1.724
316473AC1-191 GEN
Solar/Wind Harmer
1.831
970293AG2-193 GEN
Solar/Wind Harmer
1.894
3143096IRON208
Adder
0.533
3143096IRON208
Adder
0.522
3150861SPRUNCD
Adder
0.558
3142946ENON
Solar/Wind Harmer
-0.004
970133AG2-095 GEN
Solar/Wind Harmer
1.446
970129AG2-093 GEN
Solar/Wind Harmer
6.983
965281AG1-393 GEN
Solar/Wind Harmer
1.55
315839AE2-212 C
Solar/Wind Harmer
0.372
315778AD1-151 GEN
Solar/Wind Harmer
10.463
3142433PROV 92
Adder
0.208
3142433PROV 92
Adder
0.208
316382AG1-145 C
Solar/Wind Harmer
0.352
961611AG1-000B GEN
Solar/Wind Harmer
2.401
315813AE1-149 C
Solar/Wind Harmer
7.061
3151221GRAVEL6
Adder
7.179
3151171GRAVELC
Adder
1.381
970659AG2-427 GEN
Solar/Wind Harmer
1.031
3144216WINCHST
Adder
0.367
316083AB2-161 GEN
Solar/Wind Harmer
1.768
3150921YORKTN3
Adder
2.436
3141843SHACKLE
Adder
0.49
3141766HARMONY
Solar/Wind Harmer
0.96
316203AE2-005 GEN
Solar/Wind Harmer
4.545
970661AG2-428 GEN
Solar/Wind Harmer
2.016
3145336SMITFLD
Solar/Wind Harmer
-0.004
316280AD1-041 GEN
Solar/Wind Harmer
0.798
316156AD2-030 GEN
Solar/Wind Harmer
0.276
3141873WAN 176
Solar/Wind Harmer
1.227
3144536CHRHLND
Solar/Wind Harmer
-0.002
971781AH1-399 GEN
Solar/Wind Harmer
0.619
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
8.238
315773AC2-141 GEN
Solar/Wind Harmer
4.132
944581AF1-123 GEN
Solar/Wind Harmer
44.756
944601AF1-125 GEN
Solar/Wind Harmer
44.057
3146456SLIGO L269
Solar/Wind Harmer
-0.01
971153AH1-033 GEN
Solar/Wind Harmer
1.191
316320Y1-086
Solar/Wind Harmer
0.566
316435W1029_GEN3
Solar/Wind Harmer
1.73
3146516WINFALL
Solar/Wind Harmer
-0.009
3145273HOLLAND
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3146376EDENTON
Solar/Wind Harmer
-0.009
315614AA2-178 GEN
Solar/Wind Harmer
0.965
962971AG1-146 GEN
Solar/Wind Harmer
1.661
971157AH1-035 GEN
Solar/Wind Harmer
1.094
315737AD1-076 GEN
Solar/Wind Harmer
1.657
3156081AA2-088 GEN
Solar/Wind Harmer
2.825
3146206CASHIE
Solar/Wind Harmer
-0.009
972255AH1-712 GEN
Adder
39.155
3145893MURPHYS
Solar/Wind Harmer
0.06
3145893MURPHYS
Solar/Wind Harmer
-0.009
316313AB2-026
Solar/Wind Harmer
0.23
316258AE1-075 C
Solar/Wind Harmer
0.207
316405AF2-144 C
Solar/Wind Harmer
0.219
3143336POWHATN
Solar/Wind Harmer
0.862
316365GEN2_N
Solar/Wind Harmer
0.575
957521AF2-046 GEN
Solar/Wind Harmer
6.711
961681AG1-008 GEN
Solar/Wind Harmer
6.711
316484AD2-074 GEN
Solar/Wind Harmer
2.145
970009AG2-005 GEN
Solar/Wind Harmer
1.065
3146173TUNIS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1.137
316463AE2-346 GEN
Solar/Wind Harmer
0.136
316140AB2-099
Solar/Wind Harmer
0.057
962331AG1-082 GEN
Solar/Wind Harmer
1.049
3146263WOODLND
Solar/Wind Harmer
-0.008
3145963POPLR C
Solar/Wind Harmer
-0.008
966621AG1-532 GEN
Solar/Wind Harmer
0.166
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
316317KELFORD C
Solar/Wind Harmer
0.383
3145823KELFORD
Solar/Wind Harmer
-0.008
313506AB2-031 GEN
Solar/Wind Harmer
0.65
316404AE1-155 C
Solar/Wind Harmer
1.539
3145796HORNRTN
Solar/Wind Harmer
-0.032
3145796HORNRTN
Solar/Wind Harmer
-0.008
3145933PARMELE
Solar/Wind Harmer
-0.008
966801AG1-551 GEN
Solar/Wind Harmer
0.972
3147043LAWRENC
Solar/Wind Harmer
-0.005
316210AC1-098 GEN
Solar/Wind Harmer
1.214
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
315724AD1-057 GEN
Solar/Wind Harmer
0.43
316327AA2-057 GEN
Solar/Wind Harmer
0.747
970917AG2-570 GEN
Solar/Wind Harmer
18.315
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
0.152
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
961601AG1-000A GEN
Solar/Wind Harmer
2.823
3150351NORNECKC2
Adder
0.632
3144293JTRSVLE
Adder
0.188
966881AG1-559 GEN
Solar/Wind Helper
1.322
NYPJM->LTFIMP_NY
CLTF
1.238
LGEELTFEXP_LGEE->PJM
CLTF
0.609
WECLTFEXP_WEC->PJM
CLTF
0.303
LAGNLTFEXP_LAGN->PJM
CLTF
3.116
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.813
TVALTFEXP_TVA->PJM
CLTF
1.581
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.456
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.467
MECLTFEXP_MEC->PJM
CLTF
1.593
SIGELTFEXP_SIGE->PJM
CLTF
0.049
CPLELTFEXP_CPLE->PJM
CLTF
3.933
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.834

Details for 6HANOVER-6FOUR RIVERS 230.0 kV Ckt 1 line l/o DVP_P4-2: 574T575_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6HANOVER-6FOUR RIVERS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 574T575_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.42 %
Rating:1360.0 MVA
Rating Type:C
MVA to Mitigate:1651.33
MW Contribution:55.73
Bus #Bus NameTypeMW Contribution
3143096IRON208
50/50
0.674
3150851SPRUNCC
50/50
0.716
3150641CHESTS8
50/50
0.466
3142416OLDCHRC
Solar/Wind Harmer
-0.051
3142416OLDCHRC
Solar/Wind Harmer
-0.02
3142543TWELFTH
Solar/Wind Harmer
-0.002
944631AF1-128 GEN
Adder
68.961
315671AE2-027_GEN
Solar/Wind Harmer
11.518
970129AG2-093 GEN
Solar/Wind Harmer
3.456
316458AB2-190 GEN2
Solar/Wind Harmer
1.528
3143526WINTERP
Solar/Wind Harmer
-0.078
971069AG2-661 GEN
Solar/Wind Harmer
2.346
3142433PROV 92
Solar/Wind Harmer
-0.058
3142433PROV 92
Adder
0.254
3142433PROV 92
Adder
0.254
971647AH1-324 GEN
Solar/Wind Harmer
7.198
316159AE1-175 C
Solar/Wind Harmer
0.386
961611AG1-000B GEN
Solar/Wind Harmer
6.985
3151171GRAVELC
Adder
1.311
970659AG2-427 GEN
Solar/Wind Harmer
7.3
316381AD1-082 GEN
Solar/Wind Harmer
1.254
971317AH1-138 GEN
Solar/Wind Harmer
1.707
3138126ROCKLANDING
Solar/Wind Harmer
0.042
970661AG2-428 GEN
Solar/Wind Harmer
14.327
3145336SMITFLD
Solar/Wind Harmer
-0.053
3143226MDLTHAN
Solar/Wind Harmer
-0.013
971777AH1-397 GEN
Solar/Wind Harmer
1.569
3141843SHACKLE
Adder
0.607
3141766HARMONY
Solar/Wind Harmer
-0.003
316072AD1-144
Solar/Wind Harmer
0.26
316375AC2-012 GEN
Solar/Wind Harmer
4.419
3150981CHESPKA
Adder
1.419
316294AC1-161 GEN
Solar/Wind Harmer
4.101
944591AF1-124 GEN
Solar/Wind Harmer
57.652
316093AE2-104_GEN
Solar/Wind Harmer
3.663
316388AE2-253 GEN
Solar/Wind Harmer
0.848
316246AF1-032 C
Solar/Wind Harmer
0.254
3146456SLIGO L269
Solar/Wind Harmer
-0.012
3146516WINFALL
Solar/Wind Harmer
-0.039
3146516WINFALL
Solar/Wind Harmer
-0.012
3138133OCRAN
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
2.975
3130156CHOWAN
Solar/Wind Harmer
-0.012
939411AE1-173 GEN
Solar/Wind Harmer
58.022
3145663CRESWEL
Solar/Wind Harmer
-0.032
971163AH1-040 GEN
Solar/Wind Harmer
10.876
3143336POWHATN
Solar/Wind Harmer
1.346
940641AE2-051 GEN
Solar/Wind Harmer
10.561
3146206CASHIE
Solar/Wind Harmer
-0.011
971547AH1-271 GEN
Solar/Wind Harmer
2.804
316023GEN1_S
Solar/Wind Harmer
0.754
3145893MURPHYS
Solar/Wind Harmer
-0.044
3145893MURPHYS
Solar/Wind Harmer
0.331
3146173TUNIS
Solar/Wind Harmer
-0.011
961951AG1-038 GEN
Solar/Wind Harmer
1.441
3145683EARLEYS
Solar/Wind Harmer
-0.011
3146263WOODLND
Solar/Wind Harmer
-0.011
316336AC2-165 C
Solar/Wind Harmer
1.878
960081AF2-299 GEN
Solar/Wind Harmer
1.215
3145963POPLR C
Solar/Wind Harmer
-0.011
316011AB1-132 GEN
Solar/Wind Harmer
2.236
962571AG1-106 GEN
Solar/Wind Harmer
1.537
3145823KELFORD
Solar/Wind Harmer
-0.011
316174AB2-169 GEN
Solar/Wind Harmer
1.645
316190AA2-174 GEN
Solar/Wind Harmer
0.13
962861AG1-135 GEN
Solar/Wind Harmer
3.943
3145796HORNRTN
Solar/Wind Harmer
-0.035
3145796HORNRTN
Solar/Wind Harmer
-0.01
972277AH1-723 GEN
Adder
55.732
971795AH1-408 GEN
Solar/Wind Harmer
7.859
3145783HORNRTN
Solar/Wind Harmer
-0.01
3147043LAWRENC
Adder
0.832
3146293MARTNCO
Solar/Wind Harmer
0.064
316212AC1-099_GEN
Solar/Wind Harmer
0.893
970919AG2-571 GEN
Solar/Wind Harmer
3.189
970087AG2-069 GEN
Solar/Wind Harmer
9.419
3145746EVERETS
Solar/Wind Harmer
-0.01
3145746EVERETS
Solar/Wind Harmer
-0.01
315722AD1-056 GEN
Solar/Wind Harmer
1.04
964211AG1-282 GEN
Solar/Wind Harmer
0.298
3141726DUNNSVL
Solar/Wind Harmer
-0.039
316494AC1-189 GEN
Solar/Wind Harmer
1.06
316129AC1-054 GEN
Solar/Wind Harmer
0.857
957481AF2-042 GEN
Solar/Wind Harmer
30.531
971065AG2-659 GEN
Solar/Wind Harmer
4.854
961671AG1-007 GEN
Solar/Wind Harmer
0.122
3146083TARBORO
Solar/Wind Harmer
-0.01
3145493TOT1
Solar/Wind Harmer
0.287
3146233WITAKRS
Solar/Wind Harmer
-0.038
315693AD1-088 GEN
Solar/Wind Harmer
4.82
3150351NORNECKC2
Adder
0.827
3144293JTRSVLE
Adder
0.258
962491AG1-098 GEN
Solar/Wind Harmer
4.301
3142296MT RD221
50/50
0.655
3142366NRTHEST
50/50
0.581
3150691DARBY 3
50/50
12.553
3150701DARBY 4
50/50
12.524
3150681DARBY 2
50/50
12.51
3150671DARBY 1
50/50
12.495
3150621CHESTS7
50/50
0.422
966871AG1-558 GEN
Solar/Wind Harmer
0.589
966871AG1-558 GEN
Solar/Wind Harmer
0.201
316075AC2-137 C
Solar/Wind Harmer
0.462
3142946ENON
Solar/Wind Harmer
-0.002
944641AF1-129 GEN
Adder
68.324
316240AF1-291 C
Solar/Wind Harmer
0.478
3143526WINTERP
Solar/Wind Harmer
-0.078
316033AB2-134 GEN
Solar/Wind Harmer
4.72
315697AD1-025 GEN
Solar/Wind Harmer
2.96
970657AG2-426 GEN
Solar/Wind Harmer
4.251
970657AG2-426 GEN
Solar/Wind Harmer
0.889
316236AE1-162_GEN
Solar/Wind Harmer
0.405
971223AH1-071 GEN
Solar/Wind Harmer
1.675
316441AF1-014 GEN
Solar/Wind Harmer
0.899
316036AC1-147 C
Solar/Wind Harmer
0.344
3150991CHESPKB
Adder
1.19
3150991CHESPKB
Adder
1.162
316316AC1-027 C
Solar/Wind Harmer
0.39
3142956BIRDNECK
Solar/Wind Harmer
0.681
316185AD1-033 GEN
Solar/Wind Harmer
1.335
3145506HICKORY
Solar/Wind Harmer
-0.05
3145506HICKORY
Solar/Wind Harmer
-0.03
3145506HICKORY
Solar/Wind Harmer
-0.007
316339AD2-160 GEN
Solar/Wind Harmer
0.848
316018AA1-139 ULT2
Solar/Wind Harmer
1.076
316017AA1-139 ULT1
Solar/Wind Harmer
1.016
3137176SLIGO L2192
Solar/Wind Harmer
-0.05
3146456SLIGO L269
Solar/Wind Harmer
1.48
3130086AYDLETT
Solar/Wind Harmer
-0.05
3146386ELIZ CT
Solar/Wind Harmer
-0.012
316431W1029_GEN1
Solar/Wind Harmer
2.225
316433W1029_GEN2
Solar/Wind Harmer
2.225
316468AD1-105 GEN
Solar/Wind Harmer
1.366
3146516WINFALL
Solar/Wind Harmer
-0.012
3146516WINFALL
Solar/Wind Harmer
-0.012
3146516WINFALL
Solar/Wind Harmer
-0.012
3146626S HERTFORD
Solar/Wind Harmer
-0.012
3146626S HERTFORD
Solar/Wind Harmer
-0.012
3144356SAPONY
Solar/Wind Harmer
0.424
315742AE1-103 GEN
Solar/Wind Harmer
1.257
3146376EDENTON
Solar/Wind Harmer
0.353
3146376EDENTON
Solar/Wind Harmer
0.353
316065AD1-022 GEN
Solar/Wind Harmer
5.632
3145893MURPHYS
Solar/Wind Harmer
0.311
3145893MURPHYS
Solar/Wind Harmer
-0.02
3146173TUNIS
Solar/Wind Harmer
-0.011
3146173TUNIS
Solar/Wind Harmer
-0.011
316487AF1-042 GEN
Solar/Wind Harmer
1.441
3142666NORTHAMPTON
Solar/Wind Harmer
-0.011
3142666NORTHAMPTON
Solar/Wind Harmer
-0.011
3142666NORTHAMPTON
Solar/Wind Harmer
-0.011
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
316181AB2-040 GEN
Solar/Wind Harmer
1.488
316426AA2-053 GEN
Solar/Wind Harmer
1.071
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.184
3145593CAROLNA
Solar/Wind Harmer
0.087
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145783HORNRTN
Solar/Wind Harmer
1.242
3145783HORNRTN
Solar/Wind Harmer
0.994
3145783HORNRTN
Solar/Wind Harmer
0.311
3145783HORNRTN
Solar/Wind Harmer
0.124
972185AH1-677 GEN
Adder
5.222
958261AF2-120 GEN
Solar/Wind Harmer
4.015
972187AH1-678 GEN
Adder
2.627
3145933PARMELE
Solar/Wind Harmer
-0.02
3145933PARMELE
Solar/Wind Harmer
-0.01
970933AG2-581 GEN
Solar/Wind Harmer
9.608
316274AC1-208 GEN
Solar/Wind Harmer
1.095
970099AG2-077 GEN
Solar/Wind Harmer
12.212
3145493TOT1
Solar/Wind Harmer
0.15
3145453TOT5
Solar/Wind Harmer
0.09
3145603CNETO
Solar/Wind Harmer
0.06
3150341NORNECKC1
Adder
0.869
3150341NORNECKC1
Adder
0.862
3144293JTRSVLE
Adder
0.258
3144293JTRSVLE
Adder
0.217
971285AH1-108 GEN
50/50
1.171
3150611CHESTG7
50/50
0.919
3150631CHESTG8
50/50
0.904
316312AB1-027
Solar/Wind Harmer
0.666
315976AC1-164 GENA
Solar/Wind Harmer
16.808
316169AC1-164_GENC
Solar/Wind Harmer
14.521
315975AC1-164 GENB
Solar/Wind Harmer
0.497
316132AB2-190 GEN1
Solar/Wind Harmer
1.528
316233AE1-074 FULL
Solar/Wind Harmer
0.403
971281AH1-106 GEN
Solar/Wind Harmer
2.436
971283AH1-107 GEN
Solar/Wind Harmer
2.436
971167AH1-042 GEN
Solar/Wind Harmer
14.288
3142433PROV 92
Adder
0.254
3142433PROV 92
Adder
0.254
316369SG1_INVT
Solar/Wind Harmer
2.615
3143873LANEXA
Solar/Wind Harmer
-0.008
3143316POE
Solar/Wind Harmer
-0.055
972265AH1-717 GEN
Adder
9.57
3151201GRAVEL4
Adder
8.972
3151191GRAVEL3
Adder
8.858
3151211GRAVEL5
Adder
8.858
316314AB2-024 C
Solar/Wind Harmer
1.163
971445AH1-216 GEN
Solar/Wind Harmer
8.338
316059AD1-063 C
Solar/Wind Harmer
0.301
957831AF2-077 GEN
Solar/Wind Harmer
0.399
3138283WHITEMARSH
Solar/Wind Harmer
0.021
315662AE1-191 GEN
Solar/Wind Harmer
1.585
315666AE1-190 GEN
Solar/Wind Harmer
0.396
315833AF1-017_GEN
Solar/Wind Harmer
2.472
316349AD2-085 GEN
Solar/Wind Harmer
1.157
316311AC2-079 GEN
Solar/Wind Harmer
6.56
957601AF2-054 GEN
Solar/Wind Harmer
0.386
3141873WAN 176
Solar/Wind Harmer
-0.003
3152611GOSPORTB
Adder
1.447
3152621GOSPORTC
Adder
1.228
3152601GOSPORTA
Adder
1.133
3151081ELIZAR1
Adder
10.405
3151091ELIZAR2
Adder
10.224
315835AF2-110_GEN
Solar/Wind Harmer
1.575
957871AF2-081 GEN
Solar/Wind Harmer
6.28
316305AF2-043 C
Solar/Wind Harmer
0.378
319010AE1-072 C
Solar/Wind Harmer
2.534
3146406KITTY HAWK
Solar/Wind Harmer
0.01
313526AB2-022
Solar/Wind Harmer
0.335
3146486SUNBURY
Solar/Wind Harmer
-0.012
3146486SUNBURY
Solar/Wind Harmer
-0.012
3141913WHIT STONE
Solar/Wind Harmer
-0.012
316321Z2-027
Solar/Wind Harmer
0.333
3145176PASQUOTANK
Solar/Wind Harmer
-0.008
3146396TANGLEW
Solar/Wind Harmer
0.227
3138133OCRAN
Solar/Wind Harmer
-0.004
316315AB2-025 C
Solar/Wind Harmer
0.328
315814AE2-033 C
Solar/Wind Harmer
11.272
315611Z1-036_GEN2
Solar/Wind Harmer
2.975
3141783LANCAST
Solar/Wind Harmer
-0.007
3141783LANCAST
Solar/Wind Harmer
-0.005
3130156CHOWAN
Solar/Wind Harmer
-0.012
3130156CHOWAN
Solar/Wind Harmer
-0.012
315816AE2-034 GEN
Solar/Wind Harmer
0.939
3130546PLYMOUTH
Solar/Wind Harmer
-0.011
315732AD1-074 GEN1
Solar/Wind Harmer
2.294
315733AD1-074 GEN2
Solar/Wind Harmer
2.294
315735AD1-075 GEN1
Solar/Wind Harmer
1.148
962981AG1-147 GEN
Solar/Wind Harmer
4.945
965291AG1-394 GEN
Solar/Wind Harmer
1.001
3146206CASHIE
Solar/Wind Harmer
-0.011
970601AG2-382 GEN
Solar/Wind Harmer
4.907
316318V4-068
Solar/Wind Harmer
0.278
3145893MURPHYS
Solar/Wind Harmer
-0.03
3145893MURPHYS
Solar/Wind Harmer
-0.011
3145513AHOSKIE
Solar/Wind Harmer
0.096
961941AG1-037 GEN
Solar/Wind Harmer
0.083
3145513AHOSKIE
Solar/Wind Harmer
-0.011
3145683EARLEYS
Solar/Wind Harmer
-0.022
3145683EARLEYS
Solar/Wind Harmer
-0.011
3145683EARLEYS
Solar/Wind Harmer
-0.011
3146043SEABORD
Solar/Wind Harmer
-0.011
315607AA1-063A GEN
Solar/Wind Harmer
1.093
946281AF1-292 GEN
Solar/Wind Harmer
0.242
316087AB2-174 GEN
Solar/Wind Harmer
1.527
315652AC1-086 GEN
Solar/Wind Harmer
12.025
941031AE2-094 GEN
Solar/Wind Harmer
19.997
944011AF1-069 GEN
Solar/Wind Harmer
6.266
3137643SOCKMAN
Solar/Wind Harmer
-0.042
970673AG2-436 GEN
Solar/Wind Harmer
22.112
970673AG2-436 GEN
Solar/Wind Harmer
11.196
3145796HORNRTN
Solar/Wind Harmer
-0.033
3145796HORNRTN
Solar/Wind Harmer
-0.004
972193AH1-681 GEN
Adder
2.137
3146033SCOT NK
Solar/Wind Harmer
-0.042
971967AH1-528 GEN
Solar/Wind Harmer
19.61
970085AG2-068 GEN
Solar/Wind Harmer
6.279
970581AG2-369 GEN
Solar/Wind Harmer
5.4
316005AA1-067
Solar/Wind Harmer
0.203
3145746EVERETS
Solar/Wind Harmer
-0.04
3145746EVERETS
Solar/Wind Harmer
-0.01
3145746EVERETS
Solar/Wind Harmer
-0.01
3145746EVERETS
Solar/Wind Harmer
-0.01
970181AG2-120 GEN
Solar/Wind Harmer
1.318
957861AF2-080 GEN
Solar/Wind Harmer
4.31
970831AG2-522 GEN
Solar/Wind Harmer
4.924
316420AA1-050 GEN
Solar/Wind Harmer
1.115
3145573BETHELC
Solar/Wind Harmer
-0.01
3145573BETHELC
Solar/Wind Harmer
-0.01
316319Z2-044 C
Solar/Wind Harmer
0.534
972205AH1-687 GEN
Adder
3.136
3141426STAFORD
Solar/Wind Helper
0.04
971645AH1-323 GEN
50/50
17.982
3143096IRON208
50/50
0.674
3143096IRON208
50/50
0.66
3150861SPRUNCD
50/50
0.716
3142416OLDCHRC
Solar/Wind Harmer
1.991
316473AC1-191 GEN
Solar/Wind Harmer
2.107
970293AG2-193 GEN
Solar/Wind Harmer
2.228
3142946ENON
Solar/Wind Harmer
-0.005
970133AG2-095 GEN
Solar/Wind Harmer
1.756
965281AG1-393 GEN
Solar/Wind Harmer
1.898
970129AG2-093 GEN
Solar/Wind Harmer
8.532
315839AE2-212 C
Solar/Wind Harmer
0.456
315778AD1-151 GEN
Solar/Wind Harmer
12.847
3142433PROV 92
Adder
0.254
3142433PROV 92
Adder
0.254
316382AG1-145 C
Solar/Wind Harmer
0.433
961611AG1-000B GEN
Solar/Wind Harmer
2.98
315813AE1-149 C
Solar/Wind Harmer
8.808
3151221GRAVEL6
Adder
8.961
3151171GRAVELC
Adder
1.724
970659AG2-427 GEN
Solar/Wind Harmer
1.294
316083AB2-161 GEN
Solar/Wind Harmer
2.219
3144216WINCHST
Adder
0.458
3150921YORKTN3
Adder
3.041
970661AG2-428 GEN
Solar/Wind Harmer
2.539
3145336SMITFLD
Solar/Wind Harmer
-0.005
3141843SHACKLE
Adder
0.607
316203AE2-005 GEN
Solar/Wind Harmer
5.625
3141766HARMONY
Solar/Wind Harmer
1.187
316280AD1-041 GEN
Solar/Wind Harmer
0.991
3144536CHRHLND
Solar/Wind Harmer
-0.002
316156AD2-030 GEN
Solar/Wind Harmer
0.344
3141873WAN 176
Solar/Wind Harmer
1.53
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
10.538
315773AC2-141 GEN
Solar/Wind Harmer
5.304
944581AF1-123 GEN
Solar/Wind Harmer
57.445
944601AF1-125 GEN
Solar/Wind Harmer
56.548
3146456SLIGO L269
Solar/Wind Harmer
-0.012
971153AH1-033 GEN
Solar/Wind Harmer
1.528
316320Y1-086
Solar/Wind Harmer
0.727
316435W1029_GEN3
Solar/Wind Harmer
2.225
971781AH1-399 GEN
Solar/Wind Harmer
0.756
3146516WINFALL
Solar/Wind Harmer
-0.012
3145273HOLLAND
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.012
3146376EDENTON
Solar/Wind Harmer
-0.012
315614AA2-178 GEN
Solar/Wind Harmer
1.252
971157AH1-035 GEN
Solar/Wind Harmer
1.423
315737AD1-076 GEN
Solar/Wind Harmer
2.156
316313AB2-026
Solar/Wind Harmer
0.306
316258AE1-075 C
Solar/Wind Harmer
0.275
316405AF2-144 C
Solar/Wind Harmer
0.291
3143336POWHATN
Solar/Wind Harmer
1.144
3156081AA2-088 GEN
Solar/Wind Harmer
3.68
962971AG1-146 GEN
Solar/Wind Harmer
2.119
3146206CASHIE
Solar/Wind Harmer
-0.011
316365GEN2_N
Solar/Wind Harmer
0.754
3145893MURPHYS
Solar/Wind Harmer
0.078
3145893MURPHYS
Solar/Wind Harmer
-0.011
957521AF2-046 GEN
Solar/Wind Harmer
8.766
961681AG1-008 GEN
Solar/Wind Harmer
8.766
3146173TUNIS
Solar/Wind Harmer
-0.011
3156021HOLLOMANSOL
Solar/Wind Harmer
1.487
316463AE2-346 GEN
Solar/Wind Harmer
0.178
316140AB2-099
Solar/Wind Harmer
0.074
962331AG1-082 GEN
Solar/Wind Harmer
1.373
316484AD2-074 GEN
Solar/Wind Harmer
2.755
970009AG2-005 GEN
Solar/Wind Harmer
1.368
3146263WOODLND
Solar/Wind Harmer
-0.011
966621AG1-532 GEN
Solar/Wind Harmer
0.219
3145963POPLR C
Solar/Wind Harmer
-0.011
3142666NORTHAMPTON
Solar/Wind Harmer
-0.011
316317KELFORD C
Solar/Wind Harmer
0.504
3145823KELFORD
Solar/Wind Harmer
-0.011
313506AB2-031 GEN
Solar/Wind Harmer
0.858
3145796HORNRTN
Solar/Wind Harmer
-0.042
3145796HORNRTN
Solar/Wind Harmer
-0.01
972255AH1-712 GEN
Adder
47.827
316404AE1-155 C
Solar/Wind Harmer
1.999
3147043LAWRENC
Solar/Wind Harmer
-0.006
3145933PARMELE
Solar/Wind Harmer
-0.01
966801AG1-551 GEN
Solar/Wind Harmer
1.283
316210AC1-098 GEN
Solar/Wind Harmer
1.607
970917AG2-570 GEN
Solar/Wind Harmer
25.195
3145746EVERETS
Solar/Wind Harmer
-0.01
3145746EVERETS
Solar/Wind Harmer
-0.01
315724AD1-057 GEN
Solar/Wind Harmer
0.572
316327AA2-057 GEN
Solar/Wind Harmer
0.995
3146073TAR RVR
Solar/Wind Harmer
-0.01
3146083TARBORO
Solar/Wind Harmer
-0.01
3146233WITAKRS
Solar/Wind Harmer
0.202
3146233WITAKRS
Solar/Wind Harmer
-0.007
3138543CONSLDL
Solar/Wind Harmer
-0.006
3150351NORNECKC2
Adder
0.841
3144293JTRSVLE
Adder
0.258
966881AG1-559 GEN
Solar/Wind Helper
1.258
NYPJM->LTFIMP_NY
CLTF
1.203
LGEELTFEXP_LGEE->PJM
CLTF
1.109
WECLTFEXP_WEC->PJM
CLTF
0.572
LAGNLTFEXP_LAGN->PJM
CLTF
4.914
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.542
TVALTFEXP_TVA->PJM
CLTF
2.484
CBM West 1LTFEXP_CBM-W1->PJM
CBM
20.492
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.74
MECLTFEXP_MEC->PJM
CLTF
2.841
SIGELTFEXP_SIGE->PJM
CLTF
0.088
CPLELTFEXP_CPLE->PJM
CLTF
5.473
CBM West 2LTFEXP_CBM-W2->PJM
CBM
27.827

Details for 6HANOVER-6FOUR RIVERS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6HANOVER-6FOUR RIVERS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.18 %
Rating:1123.3 MVA
Rating Type:B
MVA to Mitigate:1125.32
MW Contribution:52.28
Bus #Bus NameTypeMW Contribution
3150611CHESTG7
50/50
0.857
3150631CHESTG8
50/50
0.843
316312AB1-027
Solar/Wind Harmer
0.301
971285AH1-108 GEN
Adder
1.017
315976AC1-164 GENA
Solar/Wind Harmer
13.778
316169AC1-164_GENC
Solar/Wind Harmer
11.903
315975AC1-164 GENB
Solar/Wind Harmer
0.408
971167AH1-042 GEN
Solar/Wind Harmer
10.969
316132AB2-190 GEN1
Solar/Wind Harmer
0.662
3142433PROV 92
Adder
0.237
3142433PROV 92
Adder
0.237
316233AE1-074 FULL
Solar/Wind Harmer
0.096
971281AH1-106 GEN
Solar/Wind Harmer
1.657
971283AH1-107 GEN
Solar/Wind Harmer
1.657
316369SG1_INVT
Solar/Wind Harmer
0.004
3143873LANEXA
Solar/Wind Harmer
0.07
316314AB2-024 C
Solar/Wind Harmer
0
3143316POE
Solar/Wind Harmer
0.442
972265AH1-717 GEN
Adder
8.661
3151201GRAVEL4
Adder
8.12
3151191GRAVEL3
Adder
8.017
3151211GRAVEL5
Adder
8.017
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
3.288
315662AE1-191 GEN
Solar/Wind Harmer
0.004
315666AE1-190 GEN
Solar/Wind Harmer
0.001
3138283WHITEMARSH
Solar/Wind Harmer
0.025
971445AH1-216 GEN
Solar/Wind Harmer
7.593
3141873WAN 176
Solar/Wind Harmer
0.021
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.071
316311AC2-079 GEN
Solar/Wind Harmer
2.965
3141913WHIT STONE
Solar/Wind Harmer
0.103
3138133OCRAN
Solar/Wind Harmer
0.031
3152611GOSPORTB
Adder
1.285
3152621GOSPORTC
Adder
1.09
3152601GOSPORTA
Adder
1.006
3151081ELIZAR1
Adder
9.234
3151091ELIZAR2
Adder
9.074
3141783LANCAST
Solar/Wind Harmer
0.06
3141783LANCAST
Solar/Wind Harmer
0.04
315835AF2-110_GEN
Solar/Wind Harmer
0.683
316305AF2-043 C
Solar/Wind Harmer
0.001
957871AF2-081 GEN
Solar/Wind Harmer
4.929
319010AE1-072 C
Solar/Wind Harmer
0.497
3146406KITTY HAWK
Solar/Wind Harmer
0.012
313526AB2-022
Solar/Wind Harmer
0.053
3146486SUNBURY
Solar/Wind Harmer
0.098
3146486SUNBURY
Solar/Wind Harmer
0.098
316321Z2-027
Solar/Wind Harmer
0.018
3146396TANGLEW
Solar/Wind Harmer
0.268
3145176PASQUOTANK
Solar/Wind Harmer
0.06
962981AG1-147 GEN
Solar/Wind Harmer
3.537
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
316315AB2-025 C
Solar/Wind Harmer
0.076
315814AE2-033 C
Solar/Wind Harmer
7.456
3130156CHOWAN
Solar/Wind Harmer
0.093
3130156CHOWAN
Solar/Wind Harmer
0.093
970327AG2-215 GEN
Solar/Wind Harmer
3.018
315816AE2-034 GEN
Solar/Wind Harmer
0.39
3130546PLYMOUTH
Solar/Wind Harmer
0.089
315732AD1-074 GEN1
Solar/Wind Harmer
0.51
315733AD1-074 GEN2
Solar/Wind Harmer
0.51
315735AD1-075 GEN1
Solar/Wind Harmer
0.255
965291AG1-394 GEN
Solar/Wind Harmer
0.392
3146206CASHIE
Solar/Wind Harmer
0.088
970601AG2-382 GEN
Solar/Wind Harmer
3.275
972193AH1-681 GEN
Adder
2.005
3145893MURPHYS
Solar/Wind Harmer
0.235
3145893MURPHYS
Solar/Wind Harmer
0.087
3145513AHOSKIE
Solar/Wind Harmer
0.179
3145513AHOSKIE
Solar/Wind Harmer
0.086
3145683EARLEYS
Solar/Wind Harmer
0.17
3145683EARLEYS
Solar/Wind Harmer
0.085
3145683EARLEYS
Solar/Wind Harmer
0.085
3146043SEABORD
Solar/Wind Harmer
0.084
315607AA1-063A GEN
Solar/Wind Harmer
0.172
315652AC1-086 GEN
Solar/Wind Harmer
9.127
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.328
3145796HORNRTN
Solar/Wind Harmer
0.261
3145796HORNRTN
Solar/Wind Harmer
0.033
3146033SCOT NK
Solar/Wind Harmer
0.324
941031AE2-094 GEN
Solar/Wind Harmer
14.626
944011AF1-069 GEN
Solar/Wind Harmer
4.779
3141813NORNECK
Solar/Wind Harmer
0.079
970673AG2-436 GEN
Solar/Wind Harmer
16.734
970673AG2-436 GEN
Solar/Wind Harmer
11.156
316005AA1-067
Solar/Wind Harmer
0.084
3145746EVERETS
Solar/Wind Harmer
0.31
3145746EVERETS
Solar/Wind Harmer
0.078
3145746EVERETS
Solar/Wind Harmer
0.078
3145746EVERETS
Solar/Wind Harmer
0.078
970181AG2-120 GEN
Solar/Wind Harmer
0.97
971967AH1-528 GEN
Solar/Wind Harmer
12.447
957861AF2-080 GEN
Solar/Wind Harmer
3.293
316420AA1-050 GEN
Solar/Wind Harmer
0.002
970831AG2-522 GEN
Solar/Wind Harmer
3.224
970085AG2-068 GEN
Solar/Wind Harmer
4.006
970581AG2-369 GEN
Solar/Wind Harmer
3.445
3145573BETHELC
Solar/Wind Harmer
0.075
3145573BETHELC
Solar/Wind Harmer
0.075
316319Z2-044 C
Solar/Wind Harmer
0
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
971443AH1-215 GEN
Solar/Wind Harmer
1.169
3144303KENBRDG
Solar/Wind Harmer
0.056
970683AG2-441 GEN
Solar/Wind Harmer
4.609
970681AG2-440 GEN
Solar/Wind Harmer
3.687
946301AF1-294 GEN
Solar/Wind Harmer
1.357
961791AG1-021 GEN
Solar/Wind Harmer
0.66
315657AE1-056 GEN
Solar/Wind Harmer
2.362
316118AC1-105 GEN
Solar/Wind Harmer
0.169
970285AG2-188 GEN
Solar/Wind Harmer
5.153
971845AH1-439 GEN
Solar/Wind Harmer
2.936
3147173SINAI
Solar/Wind Harmer
0.064
3147243WELCO
Solar/Wind Harmer
0.04
972205AH1-687 GEN
Adder
2.638
970865AG2-541 GEN
Solar/Wind Harmer
2.043
971447AH1-217 GEN
Solar/Wind Harmer
1.766
3141426STAFORD
Solar/Wind Helper
0.033
3143096IRON208
50/50
0.63
3150641CHESTS8
50/50
0.434
3142416OLDCHRC
Solar/Wind Harmer
0.437
3142416OLDCHRC
Solar/Wind Harmer
0.168
3142543TWELFTH
Solar/Wind Harmer
0.014
944631AF1-128 GEN
Adder
64.319
3150851SPRUNCC
Adder
0.622
315671AE2-027_GEN
Solar/Wind Harmer
8.029
970129AG2-093 GEN
Solar/Wind Harmer
3.524
316458AB2-190 GEN2
Solar/Wind Harmer
0.662
3142433PROV 92
Solar/Wind Harmer
0.488
3142433PROV 92
Adder
0.237
3142433PROV 92
Adder
0.237
971069AG2-661 GEN
Solar/Wind Harmer
2.148
3143526WINTERP
Solar/Wind Harmer
0.621
316159AE1-175 C
Solar/Wind Harmer
0.102
971647AH1-324 GEN
Solar/Wind Harmer
4.981
961611AG1-000B GEN
Solar/Wind Harmer
6.001
3151171GRAVELC
Adder
1.187
971317AH1-138 GEN
Solar/Wind Harmer
0.83
3141766HARMONY
Solar/Wind Harmer
0.022
971777AH1-397 GEN
Solar/Wind Harmer
0.293
3141843SHACKLE
Adder
0.567
3138126ROCKLANDING
Solar/Wind Harmer
0.051
970659AG2-427 GEN
Solar/Wind Harmer
5.319
316381AD1-082 GEN
Solar/Wind Harmer
0.114
970661AG2-428 GEN
Solar/Wind Harmer
10.707
3145336SMITFLD
Solar/Wind Harmer
0.43
3143226MDLTHAN
Solar/Wind Harmer
0.103
316072AD1-144
Solar/Wind Harmer
0.037
3138133OCRAN
Solar/Wind Harmer
0.061
316375AC2-012 GEN
Solar/Wind Harmer
0.003
3150981CHESPKA
Adder
1.26
316294AC1-161 GEN
Solar/Wind Harmer
1.73
316093AE2-104_GEN
Solar/Wind Harmer
1.674
944591AF1-124 GEN
Solar/Wind Harmer
22.475
316388AE2-253 GEN
Solar/Wind Harmer
0.31
316246AF1-032 C
Solar/Wind Harmer
0.045
3146456SLIGO L269
Solar/Wind Harmer
0.099
3146516WINFALL
Solar/Wind Harmer
0.312
3146516WINFALL
Solar/Wind Harmer
0.096
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.093
3145663CRESWEL
Solar/Wind Harmer
0.255
971163AH1-040 GEN
Solar/Wind Harmer
7.278
962861AG1-135 GEN
Solar/Wind Harmer
2.836
939411AE1-173 GEN
Solar/Wind Harmer
37.741
3146206CASHIE
Solar/Wind Harmer
0.088
971547AH1-271 GEN
Solar/Wind Harmer
1.872
972277AH1-723 GEN
Adder
52.282
3145893MURPHYS
Solar/Wind Harmer
0.349
3145893MURPHYS
Solar/Wind Harmer
0.388
316023GEN1_S
Solar/Wind Harmer
0.195
3143336POWHATN
Solar/Wind Harmer
1.539
3146173TUNIS
Solar/Wind Harmer
0.086
3145683EARLEYS
Solar/Wind Harmer
0.085
940641AE2-051 GEN
Solar/Wind Harmer
6.781
3146263WOODLND
Solar/Wind Harmer
0.084
3141726DUNNSVL
Solar/Wind Harmer
0.336
3145963POPLR C
Solar/Wind Harmer
0.084
960081AF2-299 GEN
Solar/Wind Harmer
0.803
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3145823KELFORD
Solar/Wind Harmer
0.083
316011AB1-132 GEN
Solar/Wind Harmer
1.509
962571AG1-106 GEN
Solar/Wind Harmer
1.181
316336AC2-165 C
Solar/Wind Harmer
0.003
316190AA2-174 GEN
Solar/Wind Harmer
0
3145796HORNRTN
Solar/Wind Harmer
0.269
3145796HORNRTN
Solar/Wind Harmer
0.082
3145783HORNRTN
Solar/Wind Harmer
0.081
971795AH1-408 GEN
Solar/Wind Harmer
5.392
3146293MARTNCO
Solar/Wind Harmer
0.074
3147043LAWRENC
Adder
0.72
316212AC1-099_GEN
Solar/Wind Harmer
0.411
3150351NORNECKC2
Adder
0.791
3145746EVERETS
Solar/Wind Harmer
0.078
3145746EVERETS
Solar/Wind Harmer
0.078
315722AD1-056 GEN
Solar/Wind Harmer
0.488
316494AC1-189 GEN
Solar/Wind Harmer
0.258
970919AG2-571 GEN
Solar/Wind Harmer
2.678
970087AG2-069 GEN
Solar/Wind Harmer
6.009
961671AG1-007 GEN
Solar/Wind Harmer
0.011
3146083TARBORO
Solar/Wind Harmer
0.075
3145493TOT1
Solar/Wind Harmer
0.333
316129AC1-054 GEN
Solar/Wind Harmer
0.282
3146233WITAKRS
Solar/Wind Harmer
0.297
971065AG2-659 GEN
Solar/Wind Harmer
3.171
316359AB2-059 GEN
Solar/Wind Harmer
0.263
316049AB1-081 GEN
Solar/Wind Harmer
0.419
3145543BTLEBRO
Solar/Wind Harmer
0.073
3145543BTLEBRO
Solar/Wind Harmer
0.059
3142053HEARTS
Solar/Wind Harmer
0.129
957481AF2-042 GEN
Solar/Wind Harmer
19.524
315693AD1-088 GEN
Solar/Wind Harmer
3.47
962491AG1-098 GEN
Solar/Wind Harmer
4.117
970937AG2-583 GEN
Solar/Wind Harmer
4.364
316237AB2-079_GEN
Solar/Wind Harmer
0.001
970685AG2-442 GEN
Solar/Wind Harmer
5.162
963171AG1-166 GEN
Solar/Wind Harmer
0.367
971563AH1-280 GEN
Solar/Wind Harmer
0.733
3144293JTRSVLE
Adder
0.219
315687AD1-152 GEN
Solar/Wind Harmer
0.002
3146926FARMVIL
Solar/Wind Harmer
0.04
970401AG2-262 GEN
Solar/Wind Harmer
0.392
316337AD2-073 GEN
Solar/Wind Harmer
0.057
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.026
316003AC1-222 GEN
Solar/Wind Harmer
0.002
972003AH1-546 GEN
Solar/Wind Harmer
2.646
971377AH1-170 GEN
Solar/Wind Harmer
0.63
3147623JAMES R
Solar/Wind Harmer
0.137
3142296MT RD221
50/50
0.632
3142366NRTHEST
50/50
0.551
3150691DARBY 3
50/50
11.896
3150701DARBY 4
50/50
11.869
3150681DARBY 2
50/50
11.855
3150671DARBY 1
50/50
11.841
3150621CHESTS7
50/50
0.394
966871AG1-558 GEN
Solar/Wind Harmer
0.195
316075AC2-137 C
Solar/Wind Harmer
0.04
3142946ENON
Solar/Wind Harmer
0.013
944641AF1-129 GEN
Adder
63.125
316240AF1-291 C
Solar/Wind Harmer
0.001
3143526WINTERP
Solar/Wind Harmer
0.621
316033AB2-134 GEN
Solar/Wind Harmer
0.007
315697AD1-025 GEN
Solar/Wind Harmer
0.134
316468AD1-105 GEN
Solar/Wind Harmer
-0.035
970657AG2-426 GEN
Solar/Wind Harmer
3.808
970657AG2-426 GEN
Solar/Wind Harmer
0.798
316236AE1-162_GEN
Solar/Wind Harmer
0.001
971223AH1-071 GEN
Solar/Wind Harmer
1.1
316036AC1-147 C
Solar/Wind Harmer
0.019
3150991CHESPKB
Adder
1.057
3150991CHESPKB
Adder
1.031
316316AC1-027 C
Solar/Wind Harmer
0.096
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.003
3145506HICKORY
Solar/Wind Harmer
0.398
3145506HICKORY
Solar/Wind Harmer
0.239
3145506HICKORY
Solar/Wind Harmer
0.06
316339AD2-160 GEN
Solar/Wind Harmer
0.161
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.055
3137176SLIGO L2192
Solar/Wind Harmer
0.393
3146456SLIGO L269
Solar/Wind Harmer
1.748
3130086AYDLETT
Solar/Wind Harmer
0.394
3146386ELIZ CT
Solar/Wind Harmer
0.098
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.096
3146516WINFALL
Solar/Wind Harmer
0.096
3146516WINFALL
Solar/Wind Harmer
0.096
3146626S HERTFORD
Solar/Wind Harmer
0.096
3146626S HERTFORD
Solar/Wind Harmer
0.096
3144356SAPONY
Solar/Wind Harmer
0.792
315742AE1-103 GEN
Solar/Wind Harmer
0.001
3146376EDENTON
Solar/Wind Harmer
0.415
3146376EDENTON
Solar/Wind Harmer
0.415
316065AD1-022 GEN
Solar/Wind Harmer
4.058
958261AF2-120 GEN
Solar/Wind Harmer
2.891
3145893MURPHYS
Solar/Wind Harmer
0.583
3145893MURPHYS
Solar/Wind Harmer
0.157
3146173TUNIS
Solar/Wind Harmer
0.086
3146173TUNIS
Solar/Wind Harmer
0.086
3142666NORTHAMPTON
Solar/Wind Harmer
0.083
3142666NORTHAMPTON
Solar/Wind Harmer
0.083
3142666NORTHAMPTON
Solar/Wind Harmer
0.083
3142666NORTHAMPTON
Solar/Wind Harmer
0.05
316181AB2-040 GEN
Solar/Wind Harmer
0.12
316426AA2-053 GEN
Solar/Wind Harmer
0.278
3145796HORNRTN
Solar/Wind Harmer
0.245
3145593CAROLNA
Solar/Wind Harmer
0.082
3145593CAROLNA
Solar/Wind Harmer
0.082
966811AG1-552 GEN
Solar/Wind Harmer
0.885
3145593CAROLNA
Solar/Wind Harmer
0.102
3145783HORNRTN
Solar/Wind Harmer
1.442
3145783HORNRTN
Solar/Wind Harmer
1.154
3145783HORNRTN
Solar/Wind Harmer
0.361
3145783HORNRTN
Solar/Wind Harmer
0.144
3145933PARMELE
Solar/Wind Harmer
0.16
3145933PARMELE
Solar/Wind Harmer
0.08
316077AC2-138 C
Solar/Wind Harmer
0
3150341NORNECKC1
Adder
0.831
3150341NORNECKC1
Adder
0.824
316274AC1-208 GEN
Solar/Wind Harmer
0.408
972185AH1-677 GEN
Adder
4.375
972187AH1-678 GEN
Adder
2.202
970933AG2-581 GEN
Solar/Wind Harmer
6.122
3145493TOT1
Solar/Wind Harmer
0.174
3145453TOT5
Solar/Wind Harmer
0.104
3145603CNETO
Solar/Wind Harmer
0.07
961601AG1-000A GEN
Solar/Wind Harmer
1.304
316263AC1-034 GEN
Solar/Wind Harmer
2.784
970099AG2-077 GEN
Solar/Wind Harmer
7.81
939181AE1-148 GEN
Solar/Wind Harmer
3.417
313527AB2-043 GEN
Solar/Wind Harmer
0.001
971741AH1-377 GEN
Solar/Wind Harmer
6.934
316034AC1-036 C
Solar/Wind Harmer
0.005
970323AG2-213 GEN
Solar/Wind Harmer
2.967
971775AH1-396 GEN
Solar/Wind Harmer
0.111
970301AG2-198 GEN
Solar/Wind Harmer
2.952
958211AF2-115 GEN
Solar/Wind Harmer
0.825
963191AG1-168 GEN
Solar/Wind Harmer
0.275
3144293JTRSVLE
Adder
0.219
3144293JTRSVLE
Adder
0.184
3147133PAMPLIN
Solar/Wind Harmer
0.068
3147133PAMPLIN
Solar/Wind Harmer
0.055
962561AG1-105 GEN
Solar/Wind Harmer
3.235
964791AG1-342 GEN
Solar/Wind Harmer
1.284
3146843MT LREL
Solar/Wind Harmer
0.067
3146843MT LREL
Solar/Wind Harmer
0.067
3146776BUCKING
Solar/Wind Harmer
0.258
3146776BUCKING
Solar/Wind Harmer
0.021
316222AC1-221 GEN
Solar/Wind Harmer
0.248
971489AH1-241 GEN
Solar/Wind Harmer
3.149
971645AH1-323 GEN
50/50
17.435
3143096IRON208
50/50
0.63
3143096IRON208
50/50
0.617
316473AC1-191 GEN
Solar/Wind Harmer
0.571
3142416OLDCHRC
Solar/Wind Harmer
1.631
970293AG2-193 GEN
Solar/Wind Harmer
1.601
3150861SPRUNCD
Adder
0.622
3142946ENON
Solar/Wind Harmer
0.045
970133AG2-095 GEN
Solar/Wind Harmer
1.231
970129AG2-093 GEN
Solar/Wind Harmer
7.489
965281AG1-393 GEN
Solar/Wind Harmer
1.32
315839AE2-212 C
Solar/Wind Harmer
0.001
3142433PROV 92
Adder
0.237
3142433PROV 92
Adder
0.237
315778AD1-151 GEN
Solar/Wind Harmer
9.667
316382AG1-145 C
Solar/Wind Harmer
0.001
961611AG1-000B GEN
Solar/Wind Harmer
3.052
315813AE1-149 C
Solar/Wind Harmer
6.039
3151221GRAVEL6
Adder
8.11
3151171GRAVELC
Adder
1.56
3141766HARMONY
Solar/Wind Harmer
1.48
3141843SHACKLE
Adder
0.567
316203AE2-005 GEN
Solar/Wind Harmer
0
3144216WINCHST
Adder
0.416
3150921YORKTN3
Adder
2.767
970659AG2-427 GEN
Solar/Wind Harmer
1.163
316083AB2-161 GEN
Solar/Wind Harmer
0.001
316280AD1-041 GEN
Solar/Wind Harmer
0.002
971781AH1-399 GEN
Solar/Wind Harmer
0.143
970661AG2-428 GEN
Solar/Wind Harmer
2.277
3145336SMITFLD
Solar/Wind Harmer
0.043
316156AD2-030 GEN
Solar/Wind Harmer
0.079
3141873WAN 176
Solar/Wind Harmer
1.904
3144536CHRHLND
Solar/Wind Harmer
0.015
3144873MCLAUGH
Solar/Wind Harmer
0.003
3151101ELIZAR3
Adder
9.352
315773AC2-141 GEN
Solar/Wind Harmer
3.646
944581AF1-123 GEN
Solar/Wind Harmer
22.395
944601AF1-125 GEN
Solar/Wind Harmer
22.05
3146456SLIGO L269
Solar/Wind Harmer
0.099
971153AH1-033 GEN
Solar/Wind Harmer
1.142
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.096
3145273HOLLAND
Solar/Wind Harmer
0.072
3146626S HERTFORD
Solar/Wind Harmer
0.096
962971AG1-146 GEN
Solar/Wind Harmer
1.516
3146376EDENTON
Solar/Wind Harmer
0.093
970009AG2-005 GEN
Solar/Wind Harmer
0.687
315614AA2-178 GEN
Solar/Wind Harmer
0.521
971157AH1-035 GEN
Solar/Wind Harmer
1.07
315737AD1-076 GEN
Solar/Wind Harmer
1.143
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3146206CASHIE
Solar/Wind Harmer
0.088
972255AH1-712 GEN
Adder
44.865
316404AE1-155 C
Solar/Wind Harmer
0.02
3145893MURPHYS
Solar/Wind Harmer
0.146
3145893MURPHYS
Solar/Wind Harmer
0.087
957521AF2-046 GEN
Solar/Wind Harmer
6.466
961681AG1-008 GEN
Solar/Wind Harmer
6.466
316365GEN2_N
Solar/Wind Harmer
0.195
316313AB2-026
Solar/Wind Harmer
0.055
316258AE1-075 C
Solar/Wind Harmer
0.065
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
1.308
3146173TUNIS
Solar/Wind Harmer
0.086
3156021HOLLOMANSOL
Solar/Wind Harmer
0.391
316463AE2-346 GEN
Solar/Wind Harmer
0.074
316140AB2-099
Solar/Wind Harmer
0.031
962331AG1-082 GEN
Solar/Wind Harmer
0.914
3146263WOODLND
Solar/Wind Harmer
0.084
3145963POPLR C
Solar/Wind Harmer
0.084
3142666NORTHAMPTON
Solar/Wind Harmer
0.083
316317KELFORD C
Solar/Wind Harmer
0.008
3145823KELFORD
Solar/Wind Harmer
0.083
313506AB2-031 GEN
Solar/Wind Harmer
0.255
3145796HORNRTN
Solar/Wind Harmer
0.326
3145796HORNRTN
Solar/Wind Harmer
0.082
3145933PARMELE
Solar/Wind Harmer
0.08
966801AG1-551 GEN
Solar/Wind Harmer
0.93
3147043LAWRENC
Solar/Wind Harmer
0.048
316210AC1-098 GEN
Solar/Wind Harmer
0.737
3150351NORNECKC2
Adder
0.804
3145746EVERETS
Solar/Wind Harmer
0.078
3145746EVERETS
Solar/Wind Harmer
0.078
315724AD1-057 GEN
Solar/Wind Harmer
0.289
316327AA2-057 GEN
Solar/Wind Harmer
0.115
970917AG2-570 GEN
Solar/Wind Harmer
6.696
3146073TAR RVR
Solar/Wind Harmer
0.075
3146083TARBORO
Solar/Wind Harmer
0.075
3146233WITAKRS
Solar/Wind Harmer
0.375
3146233WITAKRS
Solar/Wind Harmer
0.051
3138543CONSLDL
Solar/Wind Harmer
0.049
961601AG1-000A GEN
Solar/Wind Harmer
5.215
3145543BTLEBRO
Solar/Wind Harmer
0.073
3145543BTLEBRO
Solar/Wind Harmer
0.073
971623AH1-311 GEN
Solar/Wind Harmer
0.147
316478AD1-087 GEN
Solar/Wind Harmer
0.249
316486AD2-202 GEN
Solar/Wind Harmer
0.073
316131AB2-060 GEN
Solar/Wind Harmer
0.221
964241AG1-285 GEN
Solar/Wind Harmer
4.675
315785AD2-033 C
Solar/Wind Harmer
0.567
970257AG2-171 GEN
Solar/Wind Harmer
2.225
959311AF2-222 GEN
Solar/Wind Harmer
6.171
970909AG2-566 GEN
Solar/Wind Harmer
0.738
963181AG1-167 GEN
Solar/Wind Harmer
0.275
3144293JTRSVLE
Adder
0.219
3147133PAMPLIN
Solar/Wind Harmer
0.215
971193AH1-056 GEN
Solar/Wind Harmer
4.17
942461AE2-259 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.04
3146776BUCKING
Solar/Wind Harmer
0.023
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
2.742
971683AH1-343 GEN
Solar/Wind Harmer
2.232
316283AC2-100 C
Solar/Wind Harmer
0.116
970221AG2-151 GEN
Solar/Wind Harmer
3.149
966881AG1-559 GEN
Solar/Wind Helper
1.213
NYPJM->LTFIMP_NY
CLTF
0.971
LGEELTFEXP_LGEE->PJM
CLTF
0.994
WECLTFEXP_WEC->PJM
CLTF
0.514
LAGNLTFEXP_LAGN->PJM
CLTF
4.321
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.837
TVALTFEXP_TVA->PJM
CLTF
2.185
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.476
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.705
MECLTFEXP_MEC->PJM
CLTF
2.537
SIGELTFEXP_SIGE->PJM
CLTF
0.079
CPLELTFEXP_CPLE->PJM
CLTF
4.707
CBM West 2LTFEXP_CBM-W2->PJM
CBM
24.626

Details for 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 553_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.98 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1131.57
MW Contribution:62.57
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
1.205
3137383CUSHAW
50/50
0.022
3151861LOWMORA
50/50
1.128
3152191CUNINGD
50/50
1.776
3152171CUNINGB
50/50
0.767
972255AH1-712 GEN
50/50
53.693
315760AF1-028 GEN
50/50
15.215
3152051BATH 5E
50/50
2.069
3148013FISHERV
Solar/Wind Harmer
0.138
970221AG2-151 GEN
Solar/Wind Harmer
6.84
315616AA1-038_C
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.036
3146926FARMVIL
Solar/Wind Harmer
0.044
958131AF2-107 GEN
Solar/Wind Harmer
1.93
942461AE2-259 GEN
Solar/Wind Harmer
0
3132273ORANGE
Solar/Wind Helper
0.105
3147666LOUISA
Solar/Wind Helper
1.085
316170AC1-121 GEN2
Solar/Wind Helper
0.475
972205AH1-687 GEN
50/50
5.876
3151881LOWMORC
50/50
1.119
3151881LOWMORC
50/50
1.101
3151861LOWMORA
50/50
1.084
3152181CUNINGC
50/50
0.816
972193AH1-681 GEN
50/50
2.399
3152011BATH 1A
50/50
2.071
3152021BATH 2B
50/50
2.071
3152031BATH 3C
50/50
2.071
3152041BATH 4D
50/50
2.067
3138266HYDRAULIC
Solar/Wind Harmer
0.011
3138266HYDRAULIC
Solar/Wind Harmer
0.007
3148133STUARTS
Solar/Wind Harmer
0.083
3148013FISHERV
Solar/Wind Harmer
0.079
971447AH1-217 GEN
Solar/Wind Harmer
3.945
270494AE1-108_GEN
Solar/Wind Harmer
1.309
3148463FAIRFLD
Solar/Wind Harmer
0.099
971845AH1-439 GEN
Solar/Wind Harmer
4.376
970285AG2-188 GEN
Solar/Wind Harmer
7.313
316164AC1-076 GEN
Solar/Wind Helper
1.19
3151931BEARGRDN S1
50/50
1.555
3151911BEARGRDN G1
50/50
1.205
3152161CUNINGA
50/50
0.763
972277AH1-723 GEN
50/50
62.568
3152061BATH 6F
50/50
2.078
23503401SHY_Z2-039
50/50
0.003
971377AH1-170 GEN
Solar/Wind Harmer
1.368
3147623JAMES R
Solar/Wind Harmer
0.297
972003AH1-546 GEN
Solar/Wind Harmer
5.266
315705AF1-075 GEN
Solar/Wind Harmer
4.096
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.039
970937AG2-583 GEN
Solar/Wind Harmer
6.041
3147983MERCK5
Solar/Wind Harmer
0.038
3146926FARMVIL
Solar/Wind Harmer
0.044
316336AC2-165 C
Solar/Wind Harmer
0.002
316192AB2-158 GEN
Solar/Wind Helper
3.262
3147666LOUISA
Solar/Wind Helper
1.887
316254AC1-120 GEN1
Solar/Wind Helper
1.426
316006AB2-029 C
Solar/Wind Helper
0.088
23503501NHY_Z2-039
50/50
0.005
315821AE2-092 GEN
Solar/Wind Harmer
0.008
971489AH1-241 GEN
Solar/Wind Harmer
6.84
3146776BUCKING
Solar/Wind Harmer
0.395
3146776BUCKING
Solar/Wind Harmer
0.032
3132123MT JACKSON
Solar/Wind Harmer
0.208
970117AG2-086 GEN
Solar/Wind Harmer
1.594
970117AG2-086 GEN
Solar/Wind Harmer
1.063
966001AG1-469 GEN
Solar/Wind Helper
0.735
315651AD1-115 GEN
Solar/Wind Helper
0.962
NYPJM->LTFIMP_NY
CLTF
0.747
LGEELTFEXP_LGEE->PJM
CLTF
0.893
WECLTFEXP_WEC->PJM
CLTF
0.458
LAGNLTFEXP_LAGN->PJM
CLTF
2.697
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.536
TVALTFEXP_TVA->PJM
CLTF
1.4
CBM West 1LTFEXP_CBM-W1->PJM
CBM
16.766
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.191
MECLTFEXP_MEC->PJM
CLTF
2.078
SIGELTFEXP_SIGE->PJM
CLTF
0.068
CPLELTFEXP_CPLE->PJM
CLTF
0.939
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.474

Details for 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.16 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1015.26
MW Contribution:37.31
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
1.262
3137383CUSHAW
50/50
0.018
3151861LOWMORA
50/50
0.943
315760AF1-028 GEN
50/50
12.698
3152051BATH 5E
50/50
1.654
3144293JTRSVLE
50/50
0.21
3152191CUNINGD
50/50
1.059
3152171CUNINGB
50/50
0.457
972255AH1-712 GEN
50/50
32.018
970221AG2-151 GEN
Solar/Wind Harmer
7.052
3148013FISHERV
Solar/Wind Harmer
0.123
3146776BUCKING
Solar/Wind Harmer
0.039
3146926FARMVIL
Solar/Wind Harmer
0.052
315616AA1-038_C
Solar/Wind Harmer
0.001
942461AE2-259 GEN
Solar/Wind Harmer
0
316313AB2-026
Solar/Wind Harmer
0.042
316258AE1-075 C
Solar/Wind Harmer
0.05
316405AF2-144 C
Solar/Wind Harmer
0
3143336POWHATN
Solar/Wind Harmer
1.009
958131AF2-107 GEN
Solar/Wind Harmer
1.905
3147133PAMPLIN
Solar/Wind Harmer
0.206
971193AH1-056 GEN
Solar/Wind Harmer
3.999
970909AG2-566 GEN
Solar/Wind Harmer
0.694
963181AG1-167 GEN
Solar/Wind Harmer
0.249
3132273ORANGE
Solar/Wind Helper
0.106
3147666LOUISA
Solar/Wind Helper
1.086
316170AC1-121 GEN2
Solar/Wind Helper
0.478
972205AH1-687 GEN
50/50
6.155
3151881LOWMORC
50/50
0.936
3151881LOWMORC
50/50
0.921
3151861LOWMORA
50/50
0.906
3152011BATH 1A
50/50
1.656
3152021BATH 2B
50/50
1.656
3152031BATH 3C
50/50
1.655
3152041BATH 4D
50/50
1.652
3151931BEARGRDN S1
50/50
1.629
3151911BEARGRDN G1
50/50
1.262
3152061BATH 6F
50/50
1.661
3144293JTRSVLE
50/50
0.21
23503401SHY_Z2-039
50/50
0.002
3152161CUNINGA
50/50
0.455
972277AH1-723 GEN
50/50
37.31
971377AH1-170 GEN
Solar/Wind Harmer
1.41
3147623JAMES R
Solar/Wind Harmer
0.306
972003AH1-546 GEN
Solar/Wind Harmer
5.557
970937AG2-583 GEN
Solar/Wind Harmer
6.724
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.043
3146926FARMVIL
Solar/Wind Harmer
0.052
315705AF1-075 GEN
Solar/Wind Harmer
3.448
3147983MERCK5
Solar/Wind Harmer
0.033
316336AC2-165 C
Solar/Wind Harmer
0.003
3143336POWHATN
Solar/Wind Harmer
1.187
963171AG1-166 GEN
Solar/Wind Harmer
0.332
971563AH1-280 GEN
Solar/Wind Harmer
0.664
970685AG2-442 GEN
Solar/Wind Harmer
4.286
316192AB2-158 GEN
Solar/Wind Helper
3.267
3147666LOUISA
Solar/Wind Helper
1.889
316254AC1-120 GEN1
Solar/Wind Helper
1.434
316006AB2-029 C
Solar/Wind Helper
0.088
3144293JTRSVLE
50/50
0.21
3144293JTRSVLE
50/50
0.177
23503501NHY_Z2-039
50/50
0.004
971489AH1-241 GEN
Solar/Wind Harmer
7.052
315821AE2-092 GEN
Solar/Wind Harmer
0.008
3146776BUCKING
Solar/Wind Harmer
0.434
3146776BUCKING
Solar/Wind Harmer
0.035
3147133PAMPLIN
Solar/Wind Harmer
0.066
3147133PAMPLIN
Solar/Wind Harmer
0.052
970301AG2-198 GEN
Solar/Wind Harmer
2.774
958211AF2-115 GEN
Solar/Wind Harmer
0.747
963191AG1-168 GEN
Solar/Wind Harmer
0.249
971741AH1-377 GEN
Solar/Wind Harmer
5.799
966001AG1-469 GEN
Solar/Wind Helper
0.74
315651AD1-115 GEN
Solar/Wind Helper
0.968
3152181CUNINGC
50/50
0.486
972193AH1-681 GEN
50/50
1.431
3138266HYDRAULIC
Solar/Wind Harmer
0.011
3138266HYDRAULIC
Solar/Wind Harmer
0.007
971447AH1-217 GEN
Solar/Wind Harmer
4.022
3148133STUARTS
Solar/Wind Harmer
0.074
3148013FISHERV
Solar/Wind Harmer
0.071
270494AE1-108_GEN
Solar/Wind Harmer
1.339
971845AH1-439 GEN
Solar/Wind Harmer
4.834
970285AG2-188 GEN
Solar/Wind Harmer
8.151
3148463FAIRFLD
Solar/Wind Harmer
0.083
315657AE1-056 GEN
Solar/Wind Harmer
2.265
946301AF1-294 GEN
Solar/Wind Harmer
1.229
961791AG1-021 GEN
Solar/Wind Harmer
0.598
970683AG2-441 GEN
Solar/Wind Harmer
3.826
970681AG2-440 GEN
Solar/Wind Harmer
3.061
316164AC1-076 GEN
Solar/Wind Helper
1.194
NYPJM->LTFIMP_NY
CLTF
0.852
LGEELTFEXP_LGEE->PJM
CLTF
0.839
WECLTFEXP_WEC->PJM
CLTF
0.429
LAGNLTFEXP_LAGN->PJM
CLTF
2.954
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.46
TVALTFEXP_TVA->PJM
CLTF
1.519
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.521
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.505
MECLTFEXP_MEC->PJM
CLTF
2.015
SIGELTFEXP_SIGE->PJM
CLTF
0.065
CPLELTFEXP_CPLE->PJM
CLTF
1.993
CBM West 2LTFEXP_CBM-W2->PJM
CBM
18.046

Details for 6LDYSMITH CT-6SUMMIT 230.0 kV Ckt 1 line l/o DVP_P4-2: 568T581_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6LDYSMITH CT-6SUMMIT 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 568T581_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:135.94 %
Rating:1809.0 MVA
Rating Type:C
MVA to Mitigate:2459.12
MW Contribution:36.74
Bus #Bus NameTypeMW Contribution
3150411LDYSMT5
50/50
43.365
3150381LDYSMT2
50/50
41.502
972213AH1-691 GEN
50/50
7.02
972215AH1-692 GEN
50/50
7.02
963051AG1-154 GEN
50/50
5.4
972189AH1-679 GEN
50/50
2.64
316312AB1-027
Solar/Wind Harmer
0.323
971285AH1-108 GEN
Adder
0.606
316233AE1-074 FULL
Solar/Wind Harmer
0.24
971281AH1-106 GEN
Solar/Wind Harmer
1.451
971283AH1-107 GEN
Solar/Wind Harmer
1.451
316132AB2-190 GEN1
Solar/Wind Harmer
0.831
3143316POE
Solar/Wind Harmer
-0.032
316369SG1_INVT
Solar/Wind Harmer
1.442
972265AH1-717 GEN
Adder
5.416
3151201GRAVEL4
Adder
5.077
3151191GRAVEL3
Adder
5.013
3151211GRAVEL5
Adder
5.013
971445AH1-216 GEN
Solar/Wind Harmer
4.834
315833AF1-017_GEN
Solar/Wind Harmer
1.477
316349AD2-085 GEN
Solar/Wind Harmer
0.692
316311AC2-079 GEN
Solar/Wind Harmer
3.921
3151081ELIZAR1
Adder
6.332
3151091ELIZAR2
Adder
6.222
3152611GOSPORTB
Adder
0.879
3152621GOSPORTC
Adder
0.746
3152601GOSPORTA
Adder
0.688
957871AF2-081 GEN
Solar/Wind Harmer
3.844
319010AE1-072 C
Solar/Wind Harmer
1.551
3146406KITTY HAWK
Solar/Wind Harmer
0.006
316315AB2-025 C
Solar/Wind Harmer
0.206
316305AF2-043 C
Solar/Wind Harmer
0.23
315835AF2-110_GEN
Solar/Wind Harmer
0.955
315976AC1-164 GENA
Solar/Wind Harmer
8.065
316169AC1-164_GENC
Solar/Wind Harmer
6.967
315975AC1-164 GENB
Solar/Wind Harmer
0.239
315814AE2-033 C
Solar/Wind Harmer
7.093
313526AB2-022
Solar/Wind Harmer
0.205
3146486SUNBURY
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.008
316321Z2-027
Solar/Wind Harmer
0.204
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
3146396TANGLEW
Solar/Wind Harmer
0.139
941031AE2-094 GEN
Solar/Wind Harmer
13.945
944011AF1-069 GEN
Solar/Wind Harmer
4.369
315611Z1-036_GEN2
Solar/Wind Harmer
1.83
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
970673AG2-436 GEN
Solar/Wind Harmer
15.399
970673AG2-436 GEN
Solar/Wind Harmer
7.797
971967AH1-528 GEN
Solar/Wind Harmer
13.65
315816AE2-034 GEN
Solar/Wind Harmer
0.582
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315732AD1-074 GEN1
Solar/Wind Harmer
1.428
315733AD1-074 GEN2
Solar/Wind Harmer
1.428
315735AD1-075 GEN1
Solar/Wind Harmer
0.714
965291AG1-394 GEN
Solar/Wind Harmer
0.626
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.063
316318V4-068
Solar/Wind Harmer
0.174
3145893MURPHYS
Solar/Wind Harmer
-0.019
3145893MURPHYS
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.35
970581AG2-369 GEN
Solar/Wind Harmer
3.741
972193AH1-681 GEN
Adder
1.409
946281AF1-292 GEN
Solar/Wind Harmer
0.155
3145513AHOSKIE
Solar/Wind Harmer
0.06
961941AG1-037 GEN
Solar/Wind Harmer
0.052
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3146043SEABORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315607AA1-063A GEN
Solar/Wind Harmer
0.693
316087AB2-174 GEN
Solar/Wind Harmer
0.977
315652AC1-086 GEN
Solar/Wind Harmer
7.643
3137643SOCKMAN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.026
970831AG2-522 GEN
Solar/Wind Harmer
3.234
316005AA1-067
Solar/Wind Harmer
0.129
3145746EVERETS
Solar/Wind Harmer
-0.025
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
970181AG2-120 GEN
Solar/Wind Harmer
0.838
3141426STAFORD
Solar/Wind Helper
0.114
316223AC1-118
Solar/Wind Helper
0.271
3150401LDYSMT4
50/50
43.23
3150371LDYSMT1
50/50
41.772
970497AG2-320 GEN
50/50
24.535
315051AA1-145 CT1
50/50
1.178
966881AG1-559 GEN
Solar/Wind Harmer
0.782
3142416OLDCHRC
Solar/Wind Harmer
0.967
3150861SPRUNCD
Adder
0.37
970293AG2-193 GEN
Solar/Wind Harmer
1.099
3143096IRON208
Adder
0.327
3143096IRON208
Adder
0.321
315839AE2-212 C
Solar/Wind Harmer
0.256
970133AG2-095 GEN
Solar/Wind Harmer
0.941
965281AG1-393 GEN
Solar/Wind Harmer
1.043
970129AG2-093 GEN
Solar/Wind Harmer
4.632
315778AD1-151 GEN
Solar/Wind Harmer
7.043
315813AE1-149 C
Solar/Wind Harmer
5.08
3142946ENON
Solar/Wind Harmer
-0.003
970659AG2-427 GEN
Solar/Wind Harmer
0.754
316083AB2-161 GEN
Solar/Wind Harmer
1.297
970661AG2-428 GEN
Solar/Wind Harmer
1.493
961611AG1-000B GEN
Solar/Wind Harmer
1.669
315773AC2-141 GEN
Solar/Wind Harmer
3.289
3151221GRAVEL6
Adder
5.071
3151171GRAVELC
Adder
0.976
3145336SMITFLD
Solar/Wind Harmer
-0.003
3144536CHRHLND
Solar/Wind Harmer
-0.001
944581AF1-123 GEN
Solar/Wind Harmer
35.31
944601AF1-125 GEN
Solar/Wind Harmer
34.759
3151101ELIZAR3
Adder
6.413
3144873MCLAUGH
Solar/Wind Harmer
0
3146456SLIGO L269
Solar/Wind Harmer
-0.008
971153AH1-033 GEN
Solar/Wind Harmer
0.935
316313AB2-026
Solar/Wind Harmer
0.206
316258AE1-075 C
Solar/Wind Harmer
0.185
316405AF2-144 C
Solar/Wind Harmer
0.196
3143336POWHATN
Solar/Wind Harmer
0.77
316320Y1-086
Solar/Wind Harmer
0.445
316435W1029_GEN3
Solar/Wind Harmer
1.364
3146516WINFALL
Solar/Wind Harmer
-0.007
3145273HOLLAND
Solar/Wind Harmer
-0.006
3146626S HERTFORD
Solar/Wind Harmer
-0.007
316473AC1-191 GEN
Solar/Wind Harmer
0.8
316382AG1-145 C
Solar/Wind Harmer
0.221
3146376EDENTON
Solar/Wind Harmer
-0.007
3144216WINCHST
Adder
0.245
3150921YORKTN3
Adder
1.611
315614AA2-178 GEN
Solar/Wind Harmer
0.776
316365GEN2_N
Solar/Wind Harmer
0.478
971157AH1-035 GEN
Solar/Wind Harmer
0.885
3156081AA2-088 GEN
Solar/Wind Harmer
2.298
315737AD1-076 GEN
Solar/Wind Harmer
1.342
3146206CASHIE
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
0.049
3145893MURPHYS
Solar/Wind Harmer
-0.007
970917AG2-570 GEN
Solar/Wind Harmer
17.459
957521AF2-046 GEN
Solar/Wind Harmer
5.494
961681AG1-008 GEN
Solar/Wind Harmer
5.494
3146173TUNIS
Solar/Wind Harmer
-0.007
972255AH1-712 GEN
Adder
31.532
3156021HOLLOMANSOL
Solar/Wind Harmer
0.931
966621AG1-532 GEN
Solar/Wind Harmer
0.14
316463AE2-346 GEN
Solar/Wind Harmer
0.112
316140AB2-099
Solar/Wind Harmer
0.047
962331AG1-082 GEN
Solar/Wind Harmer
0.863
3146263WOODLND
Solar/Wind Harmer
-0.007
313506AB2-031 GEN
Solar/Wind Harmer
0.549
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.318
3145823KELFORD
Solar/Wind Harmer
-0.007
3147043LAWRENC
Solar/Wind Harmer
-0.004
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
316478AD1-087 GEN
Solar/Wind Harmer
0.568
316486AD2-202 GEN
Solar/Wind Harmer
0.166
316210AC1-098 GEN
Solar/Wind Harmer
1.025
3145933PARMELE
Solar/Wind Harmer
-0.006
966801AG1-551 GEN
Solar/Wind Harmer
0.813
970909AG2-566 GEN
Solar/Wind Harmer
0.613
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
315724AD1-057 GEN
Solar/Wind Harmer
0.367
316327AA2-057 GEN
Solar/Wind Harmer
0.639
3141906WESTMOR
Solar/Wind Helper
0.071
3150391LDYSMT3
50/50
43.149
972195AH1-682 GEN
50/50
5.67
315673AE1-157 GEN
Solar/Wind Harmer
21.737
957411AF2-035 GEN
Solar/Wind Harmer
11.699
970317AG2-208 GEN
Solar/Wind Harmer
11.374
3142296MT RD221
Adder
0.302
3142366NRTHEST
Adder
0.276
3150691DARBY 3
Adder
5.91
3150701DARBY 4
Adder
5.896
3150681DARBY 2
Adder
5.889
3150671DARBY 1
Adder
5.882
3143526WINTERP
Solar/Wind Harmer
-0.046
944641AF1-129 GEN
Adder
37.086
971223AH1-071 GEN
Solar/Wind Harmer
1.092
316240AF1-291 C
Solar/Wind Harmer
0.262
316075AC2-137 C
Solar/Wind Harmer
0.224
3142946ENON
Solar/Wind Harmer
-0.001
316033AB2-134 GEN
Solar/Wind Harmer
2.603
315697AD1-025 GEN
Solar/Wind Harmer
1.633
970657AG2-426 GEN
Solar/Wind Harmer
2.49
970657AG2-426 GEN
Solar/Wind Harmer
0.521
316236AE1-162_GEN
Solar/Wind Harmer
0.235
316036AC1-147 C
Solar/Wind Harmer
0.209
3150991CHESPKB
Adder
0.723
3150991CHESPKB
Adder
0.706
3142956BIRDNECK
Solar/Wind Harmer
0.415
316316AC1-027 C
Solar/Wind Harmer
0.238
316185AD1-033 GEN
Solar/Wind Harmer
0.816
3145506HICKORY
Solar/Wind Harmer
-0.031
3145506HICKORY
Solar/Wind Harmer
-0.018
3145506HICKORY
Solar/Wind Harmer
-0.005
316339AD2-160 GEN
Solar/Wind Harmer
0.519
316018AA1-139 ULT2
Solar/Wind Harmer
0.659
316017AA1-139 ULT1
Solar/Wind Harmer
0.622
3137176SLIGO L2192
Solar/Wind Harmer
-0.03
3146456SLIGO L269
Solar/Wind Harmer
0.906
3130086AYDLETT
Solar/Wind Harmer
-0.03
3144356SAPONY
Solar/Wind Harmer
0.267
3146386ELIZ CT
Solar/Wind Harmer
-0.008
316431W1029_GEN1
Solar/Wind Harmer
1.364
316433W1029_GEN2
Solar/Wind Harmer
1.364
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
966871AG1-558 GEN
Solar/Wind Harmer
0.223
966871AG1-558 GEN
Solar/Wind Harmer
0.076
315742AE1-103 GEN
Solar/Wind Harmer
0.772
3146376EDENTON
Solar/Wind Harmer
0.217
3146376EDENTON
Solar/Wind Harmer
0.217
972185AH1-677 GEN
Adder
3.634
972187AH1-678 GEN
Adder
1.826
970933AG2-581 GEN
Solar/Wind Harmer
6.679
316065AD1-022 GEN
Solar/Wind Harmer
3.511
3145893MURPHYS
Solar/Wind Harmer
0.195
3145893MURPHYS
Solar/Wind Harmer
-0.013
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316181AB2-040 GEN
Solar/Wind Harmer
0.952
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
970099AG2-077 GEN
Solar/Wind Harmer
8.455
316426AA2-053 GEN
Solar/Wind Harmer
0.683
972197AH1-683 GEN
50/50
6.75
972219AH1-694 GEN
50/50
4.86
315052AA1-145 CT2
50/50
1.183
966881AG1-559 GEN
Solar/Wind Harmer
0.267
3142416OLDCHRC
Solar/Wind Harmer
-0.025
3142416OLDCHRC
Solar/Wind Harmer
-0.009
3150851SPRUNCC
Adder
0.37
3143526WINTERP
Solar/Wind Harmer
-0.046
3142543TWELFTH
Solar/Wind Harmer
-0.001
3143096IRON208
Adder
0.327
3143226MDLTHAN
Solar/Wind Harmer
-0.009
315671AE2-027_GEN
Solar/Wind Harmer
6.265
944631AF1-128 GEN
Adder
35.154
970129AG2-093 GEN
Solar/Wind Harmer
1.876
316458AB2-190 GEN2
Solar/Wind Harmer
0.831
971069AG2-661 GEN
Solar/Wind Harmer
1.286
970659AG2-427 GEN
Solar/Wind Harmer
4.257
971647AH1-324 GEN
Solar/Wind Harmer
4
316381AD1-082 GEN
Solar/Wind Harmer
0.733
970661AG2-428 GEN
Solar/Wind Harmer
8.426
961611AG1-000B GEN
Solar/Wind Harmer
3.913
316294AC1-161 GEN
Solar/Wind Harmer
2.543
3151171GRAVELC
Adder
0.742
3145336SMITFLD
Solar/Wind Harmer
-0.031
944591AF1-124 GEN
Solar/Wind Harmer
35.438
316375AC2-012 GEN
Solar/Wind Harmer
2.685
3150981CHESPKA
Adder
0.862
939411AE1-173 GEN
Solar/Wind Harmer
38.501
316388AE2-253 GEN
Solar/Wind Harmer
0.519
940641AE2-051 GEN
Solar/Wind Harmer
7.21
3146456SLIGO L269
Solar/Wind Harmer
-0.008
316246AF1-032 C
Solar/Wind Harmer
0.155
316093AE2-104_GEN
Solar/Wind Harmer
2.222
316072AD1-144
Solar/Wind Harmer
0.154
3143336POWHATN
Solar/Wind Harmer
0.906
3146516WINFALL
Solar/Wind Harmer
-0.024
3146516WINFALL
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.83
316159AE1-175 C
Solar/Wind Harmer
0.197
316336AC2-165 C
Solar/Wind Harmer
1.276
3130156CHOWAN
Solar/Wind Harmer
-0.007
3138126ROCKLANDING
Solar/Wind Harmer
0.022
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.74
316023GEN1_S
Solar/Wind Harmer
0.478
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.75
3145893MURPHYS
Solar/Wind Harmer
-0.028
3145893MURPHYS
Solar/Wind Harmer
0.208
970919AG2-571 GEN
Solar/Wind Harmer
2.21
970087AG2-069 GEN
Solar/Wind Harmer
6.524
3146173TUNIS
Solar/Wind Harmer
-0.007
972277AH1-723 GEN
Adder
36.745
960081AF2-299 GEN
Solar/Wind Harmer
0.777
3145683EARLEYS
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
971317AH1-138 GEN
Solar/Wind Harmer
0.852
316011AB1-132 GEN
Solar/Wind Harmer
1.421
962571AG1-106 GEN
Solar/Wind Harmer
0.977
971795AH1-408 GEN
Solar/Wind Harmer
5.082
3145963POPLR C
Solar/Wind Harmer
-0.007
957481AF2-042 GEN
Solar/Wind Harmer
21.138
316190AA2-174 GEN
Solar/Wind Harmer
0.083
3145823KELFORD
Solar/Wind Harmer
-0.007
3147043LAWRENC
Adder
0.541
316174AB2-169 GEN
Solar/Wind Harmer
1.035
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145783HORNRTN
Solar/Wind Harmer
-0.007
315693AD1-088 GEN
Solar/Wind Harmer
3.339
962491AG1-098 GEN
Solar/Wind Harmer
4.459
970937AG2-583 GEN
Solar/Wind Harmer
4.746
316212AC1-099_GEN
Solar/Wind Harmer
0.57
3146293MARTNCO
Solar/Wind Harmer
0.04
316129AC1-054 GEN
Solar/Wind Harmer
0.565
971065AG2-659 GEN
Solar/Wind Harmer
3.207
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
315722AD1-056 GEN
Solar/Wind Harmer
0.667
316337AD2-073 GEN
Solar/Wind Helper
0.174
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.757
3145593CAROLNA
Solar/Wind Harmer
0.056
3145796HORNRTN
Solar/Wind Harmer
-0.02
3145783HORNRTN
Solar/Wind Harmer
0.794
3145783HORNRTN
Solar/Wind Harmer
0.635
3145783HORNRTN
Solar/Wind Harmer
0.199
3145783HORNRTN
Solar/Wind Harmer
0.079
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.006
971741AH1-377 GEN
Solar/Wind Harmer
7.563
316274AC1-208 GEN
Solar/Wind Harmer
0.701
970301AG2-198 GEN
Solar/Wind Harmer
3.227
NYPJM->LTFIMP_NY
CLTF
1.15
LGEELTFEXP_LGEE->PJM
CLTF
0.646
WECLTFEXP_WEC->PJM
CLTF
0.327
LAGNLTFEXP_LAGN->PJM
CLTF
3.071
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.25
TVALTFEXP_TVA->PJM
CLTF
1.556
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.485
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.426
MECLTFEXP_MEC->PJM
CLTF
1.669
SIGELTFEXP_SIGE->PJM
CLTF
0.052
CPLELTFEXP_CPLE->PJM
CLTF
3.627
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.979

Details for 6MINE RD-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 568T581_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6MINE RD-6FREDBRG 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 568T581_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:166.64 %
Rating:1303.0 MVA
Rating Type:C
MVA to Mitigate:2171.28
MW Contribution:36.74
Bus #Bus NameTypeMW Contribution
972197AH1-683 GEN
50/50
6.75
972219AH1-694 GEN
50/50
4.86
315052AA1-145 CT2
50/50
1.183
966881AG1-559 GEN
Solar/Wind Harmer
0.267
3142416OLDCHRC
Solar/Wind Harmer
-0.025
3142416OLDCHRC
Solar/Wind Harmer
-0.009
3150851SPRUNCC
Adder
0.37
3143526WINTERP
Solar/Wind Harmer
-0.046
3142543TWELFTH
Solar/Wind Harmer
-0.001
3143096IRON208
Adder
0.327
3143226MDLTHAN
Solar/Wind Harmer
-0.009
315671AE2-027_GEN
Solar/Wind Harmer
6.265
944631AF1-128 GEN
Adder
35.154
970129AG2-093 GEN
Solar/Wind Harmer
1.876
316458AB2-190 GEN2
Solar/Wind Harmer
0.831
971069AG2-661 GEN
Solar/Wind Harmer
1.286
970659AG2-427 GEN
Solar/Wind Harmer
4.257
971647AH1-324 GEN
Solar/Wind Harmer
4
316381AD1-082 GEN
Solar/Wind Harmer
0.733
970661AG2-428 GEN
Solar/Wind Harmer
8.426
961611AG1-000B GEN
Solar/Wind Harmer
3.913
316294AC1-161 GEN
Solar/Wind Harmer
2.543
3151171GRAVELC
Adder
0.742
3145336SMITFLD
Solar/Wind Harmer
-0.031
944591AF1-124 GEN
Solar/Wind Harmer
35.438
316375AC2-012 GEN
Solar/Wind Harmer
2.685
3150981CHESPKA
Adder
0.862
939411AE1-173 GEN
Solar/Wind Harmer
38.501
316388AE2-253 GEN
Solar/Wind Harmer
0.519
940641AE2-051 GEN
Solar/Wind Harmer
7.21
3146456SLIGO L269
Solar/Wind Harmer
-0.008
316246AF1-032 C
Solar/Wind Harmer
0.155
316093AE2-104_GEN
Solar/Wind Harmer
2.222
316072AD1-144
Solar/Wind Harmer
0.154
3143336POWHATN
Solar/Wind Harmer
0.906
3146516WINFALL
Solar/Wind Harmer
-0.024
3146516WINFALL
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.83
316159AE1-175 C
Solar/Wind Harmer
0.197
316336AC2-165 C
Solar/Wind Harmer
1.276
3130156CHOWAN
Solar/Wind Harmer
-0.007
3138126ROCKLANDING
Solar/Wind Harmer
0.022
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.74
316023GEN1_S
Solar/Wind Harmer
0.478
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.75
3145893MURPHYS
Solar/Wind Harmer
-0.028
3145893MURPHYS
Solar/Wind Harmer
0.208
970919AG2-571 GEN
Solar/Wind Harmer
2.21
970087AG2-069 GEN
Solar/Wind Harmer
6.524
3146173TUNIS
Solar/Wind Harmer
-0.007
972277AH1-723 GEN
Adder
36.745
960081AF2-299 GEN
Solar/Wind Harmer
0.777
3145683EARLEYS
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
971317AH1-138 GEN
Solar/Wind Harmer
0.852
316011AB1-132 GEN
Solar/Wind Harmer
1.421
962571AG1-106 GEN
Solar/Wind Harmer
0.977
971795AH1-408 GEN
Solar/Wind Harmer
5.082
3145963POPLR C
Solar/Wind Harmer
-0.007
957481AF2-042 GEN
Solar/Wind Harmer
21.138
316190AA2-174 GEN
Solar/Wind Harmer
0.083
3145823KELFORD
Solar/Wind Harmer
-0.007
3147043LAWRENC
Adder
0.541
316174AB2-169 GEN
Solar/Wind Harmer
1.035
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145783HORNRTN
Solar/Wind Harmer
-0.007
315693AD1-088 GEN
Solar/Wind Harmer
3.339
962491AG1-098 GEN
Solar/Wind Harmer
4.459
970937AG2-583 GEN
Solar/Wind Harmer
4.746
316212AC1-099_GEN
Solar/Wind Harmer
0.57
3146293MARTNCO
Solar/Wind Harmer
0.04
316129AC1-054 GEN
Solar/Wind Harmer
0.565
971065AG2-659 GEN
Solar/Wind Harmer
3.207
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
315722AD1-056 GEN
Solar/Wind Harmer
0.667
316337AD2-073 GEN
Solar/Wind Helper
0.174
3150401LDYSMT4
50/50
43.23
3150371LDYSMT1
50/50
41.772
970497AG2-320 GEN
50/50
24.535
315051AA1-145 CT1
50/50
1.178
966881AG1-559 GEN
Solar/Wind Harmer
0.782
3142416OLDCHRC
Solar/Wind Harmer
0.967
3150861SPRUNCD
Adder
0.37
970293AG2-193 GEN
Solar/Wind Harmer
1.099
3143096IRON208
Adder
0.327
3143096IRON208
Adder
0.321
315839AE2-212 C
Solar/Wind Harmer
0.256
970133AG2-095 GEN
Solar/Wind Harmer
0.941
965281AG1-393 GEN
Solar/Wind Harmer
1.043
970129AG2-093 GEN
Solar/Wind Harmer
4.632
315778AD1-151 GEN
Solar/Wind Harmer
7.043
315813AE1-149 C
Solar/Wind Harmer
5.08
3142946ENON
Solar/Wind Harmer
-0.003
970659AG2-427 GEN
Solar/Wind Harmer
0.754
316083AB2-161 GEN
Solar/Wind Harmer
1.297
970661AG2-428 GEN
Solar/Wind Harmer
1.493
961611AG1-000B GEN
Solar/Wind Harmer
1.669
315773AC2-141 GEN
Solar/Wind Harmer
3.289
3151221GRAVEL6
Adder
5.071
3151171GRAVELC
Adder
0.976
3145336SMITFLD
Solar/Wind Harmer
-0.003
3144536CHRHLND
Solar/Wind Harmer
-0.001
944581AF1-123 GEN
Solar/Wind Harmer
35.31
944601AF1-125 GEN
Solar/Wind Harmer
34.759
3151101ELIZAR3
Adder
6.413
3144873MCLAUGH
Solar/Wind Harmer
0
3146456SLIGO L269
Solar/Wind Harmer
-0.008
971153AH1-033 GEN
Solar/Wind Harmer
0.935
316313AB2-026
Solar/Wind Harmer
0.206
316258AE1-075 C
Solar/Wind Harmer
0.185
316405AF2-144 C
Solar/Wind Harmer
0.196
3143336POWHATN
Solar/Wind Harmer
0.77
316320Y1-086
Solar/Wind Harmer
0.445
316435W1029_GEN3
Solar/Wind Harmer
1.364
3146516WINFALL
Solar/Wind Harmer
-0.007
3145273HOLLAND
Solar/Wind Harmer
-0.006
3146626S HERTFORD
Solar/Wind Harmer
-0.007
316473AC1-191 GEN
Solar/Wind Harmer
0.8
316382AG1-145 C
Solar/Wind Harmer
0.221
3146376EDENTON
Solar/Wind Harmer
-0.007
3144216WINCHST
Adder
0.245
3150921YORKTN3
Adder
1.611
315614AA2-178 GEN
Solar/Wind Harmer
0.776
316365GEN2_N
Solar/Wind Harmer
0.478
971157AH1-035 GEN
Solar/Wind Harmer
0.885
3156081AA2-088 GEN
Solar/Wind Harmer
2.298
315737AD1-076 GEN
Solar/Wind Harmer
1.342
3146206CASHIE
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
0.049
3145893MURPHYS
Solar/Wind Harmer
-0.007
970917AG2-570 GEN
Solar/Wind Harmer
17.459
957521AF2-046 GEN
Solar/Wind Harmer
5.494
961681AG1-008 GEN
Solar/Wind Harmer
5.494
3146173TUNIS
Solar/Wind Harmer
-0.007
972255AH1-712 GEN
Adder
31.532
3156021HOLLOMANSOL
Solar/Wind Harmer
0.931
966621AG1-532 GEN
Solar/Wind Harmer
0.14
316463AE2-346 GEN
Solar/Wind Harmer
0.112
316140AB2-099
Solar/Wind Harmer
0.047
962331AG1-082 GEN
Solar/Wind Harmer
0.863
3146263WOODLND
Solar/Wind Harmer
-0.007
313506AB2-031 GEN
Solar/Wind Harmer
0.549
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.318
3145823KELFORD
Solar/Wind Harmer
-0.007
3147043LAWRENC
Solar/Wind Harmer
-0.004
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
316478AD1-087 GEN
Solar/Wind Harmer
0.568
316486AD2-202 GEN
Solar/Wind Harmer
0.166
316210AC1-098 GEN
Solar/Wind Harmer
1.025
3145933PARMELE
Solar/Wind Harmer
-0.006
966801AG1-551 GEN
Solar/Wind Harmer
0.813
970909AG2-566 GEN
Solar/Wind Harmer
0.613
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
315724AD1-057 GEN
Solar/Wind Harmer
0.367
316327AA2-057 GEN
Solar/Wind Harmer
0.639
3141906WESTMOR
Solar/Wind Helper
0.071
3150391LDYSMT3
50/50
43.149
972195AH1-682 GEN
50/50
5.67
315673AE1-157 GEN
Solar/Wind Harmer
21.737
957411AF2-035 GEN
Solar/Wind Harmer
11.699
970317AG2-208 GEN
Solar/Wind Harmer
11.374
3142296MT RD221
Adder
0.302
3142366NRTHEST
Adder
0.276
3150691DARBY 3
Adder
5.91
3150701DARBY 4
Adder
5.896
3150681DARBY 2
Adder
5.889
3150671DARBY 1
Adder
5.882
3143526WINTERP
Solar/Wind Harmer
-0.046
944641AF1-129 GEN
Adder
37.086
971223AH1-071 GEN
Solar/Wind Harmer
1.092
316240AF1-291 C
Solar/Wind Harmer
0.262
316075AC2-137 C
Solar/Wind Harmer
0.224
3142946ENON
Solar/Wind Harmer
-0.001
316033AB2-134 GEN
Solar/Wind Harmer
2.603
315697AD1-025 GEN
Solar/Wind Harmer
1.633
970657AG2-426 GEN
Solar/Wind Harmer
2.49
970657AG2-426 GEN
Solar/Wind Harmer
0.521
316236AE1-162_GEN
Solar/Wind Harmer
0.235
316036AC1-147 C
Solar/Wind Harmer
0.209
3150991CHESPKB
Adder
0.723
3150991CHESPKB
Adder
0.706
3142956BIRDNECK
Solar/Wind Harmer
0.415
316316AC1-027 C
Solar/Wind Harmer
0.238
316185AD1-033 GEN
Solar/Wind Harmer
0.816
3145506HICKORY
Solar/Wind Harmer
-0.031
3145506HICKORY
Solar/Wind Harmer
-0.018
3145506HICKORY
Solar/Wind Harmer
-0.005
316339AD2-160 GEN
Solar/Wind Harmer
0.519
316018AA1-139 ULT2
Solar/Wind Harmer
0.659
316017AA1-139 ULT1
Solar/Wind Harmer
0.622
3137176SLIGO L2192
Solar/Wind Harmer
-0.03
3146456SLIGO L269
Solar/Wind Harmer
0.906
3130086AYDLETT
Solar/Wind Harmer
-0.03
3144356SAPONY
Solar/Wind Harmer
0.267
3146386ELIZ CT
Solar/Wind Harmer
-0.008
316431W1029_GEN1
Solar/Wind Harmer
1.364
316433W1029_GEN2
Solar/Wind Harmer
1.364
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
966871AG1-558 GEN
Solar/Wind Harmer
0.223
966871AG1-558 GEN
Solar/Wind Harmer
0.076
315742AE1-103 GEN
Solar/Wind Harmer
0.772
3146376EDENTON
Solar/Wind Harmer
0.217
3146376EDENTON
Solar/Wind Harmer
0.217
972185AH1-677 GEN
Adder
3.634
972187AH1-678 GEN
Adder
1.826
970933AG2-581 GEN
Solar/Wind Harmer
6.679
316065AD1-022 GEN
Solar/Wind Harmer
3.511
3145893MURPHYS
Solar/Wind Harmer
0.195
3145893MURPHYS
Solar/Wind Harmer
-0.013
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316181AB2-040 GEN
Solar/Wind Harmer
0.952
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
970099AG2-077 GEN
Solar/Wind Harmer
8.455
316426AA2-053 GEN
Solar/Wind Harmer
0.683
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.757
3145593CAROLNA
Solar/Wind Harmer
0.056
3145796HORNRTN
Solar/Wind Harmer
-0.02
3145783HORNRTN
Solar/Wind Harmer
0.794
3145783HORNRTN
Solar/Wind Harmer
0.635
3145783HORNRTN
Solar/Wind Harmer
0.199
3145783HORNRTN
Solar/Wind Harmer
0.079
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.006
971741AH1-377 GEN
Solar/Wind Harmer
7.563
316274AC1-208 GEN
Solar/Wind Harmer
0.701
970301AG2-198 GEN
Solar/Wind Harmer
3.227
3150411LDYSMT5
50/50
43.365
3150381LDYSMT2
50/50
41.502
972213AH1-691 GEN
50/50
7.02
972215AH1-692 GEN
50/50
7.02
963051AG1-154 GEN
50/50
5.4
972189AH1-679 GEN
50/50
2.64
316312AB1-027
Solar/Wind Harmer
0.323
971285AH1-108 GEN
Adder
0.606
316233AE1-074 FULL
Solar/Wind Harmer
0.24
971281AH1-106 GEN
Solar/Wind Harmer
1.451
971283AH1-107 GEN
Solar/Wind Harmer
1.451
316132AB2-190 GEN1
Solar/Wind Harmer
0.831
3143316POE
Solar/Wind Harmer
-0.032
316369SG1_INVT
Solar/Wind Harmer
1.442
972265AH1-717 GEN
Adder
5.416
3151201GRAVEL4
Adder
5.077
3151191GRAVEL3
Adder
5.013
3151211GRAVEL5
Adder
5.013
971445AH1-216 GEN
Solar/Wind Harmer
4.834
315833AF1-017_GEN
Solar/Wind Harmer
1.477
316349AD2-085 GEN
Solar/Wind Harmer
0.692
316311AC2-079 GEN
Solar/Wind Harmer
3.921
3151081ELIZAR1
Adder
6.332
3151091ELIZAR2
Adder
6.222
3152611GOSPORTB
Adder
0.879
3152621GOSPORTC
Adder
0.746
3152601GOSPORTA
Adder
0.688
957871AF2-081 GEN
Solar/Wind Harmer
3.844
319010AE1-072 C
Solar/Wind Harmer
1.551
3146406KITTY HAWK
Solar/Wind Harmer
0.006
316315AB2-025 C
Solar/Wind Harmer
0.206
316305AF2-043 C
Solar/Wind Harmer
0.23
315835AF2-110_GEN
Solar/Wind Harmer
0.955
315976AC1-164 GENA
Solar/Wind Harmer
8.065
316169AC1-164_GENC
Solar/Wind Harmer
6.967
315975AC1-164 GENB
Solar/Wind Harmer
0.239
315814AE2-033 C
Solar/Wind Harmer
7.093
313526AB2-022
Solar/Wind Harmer
0.205
3146486SUNBURY
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.008
316321Z2-027
Solar/Wind Harmer
0.204
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
3146396TANGLEW
Solar/Wind Harmer
0.139
941031AE2-094 GEN
Solar/Wind Harmer
13.945
944011AF1-069 GEN
Solar/Wind Harmer
4.369
315611Z1-036_GEN2
Solar/Wind Harmer
1.83
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
970673AG2-436 GEN
Solar/Wind Harmer
15.399
970673AG2-436 GEN
Solar/Wind Harmer
7.797
971967AH1-528 GEN
Solar/Wind Harmer
13.65
315816AE2-034 GEN
Solar/Wind Harmer
0.582
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315732AD1-074 GEN1
Solar/Wind Harmer
1.428
315733AD1-074 GEN2
Solar/Wind Harmer
1.428
315735AD1-075 GEN1
Solar/Wind Harmer
0.714
965291AG1-394 GEN
Solar/Wind Harmer
0.626
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.063
316318V4-068
Solar/Wind Harmer
0.174
3145893MURPHYS
Solar/Wind Harmer
-0.019
3145893MURPHYS
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.35
970581AG2-369 GEN
Solar/Wind Harmer
3.741
972193AH1-681 GEN
Adder
1.409
946281AF1-292 GEN
Solar/Wind Harmer
0.155
3145513AHOSKIE
Solar/Wind Harmer
0.06
961941AG1-037 GEN
Solar/Wind Harmer
0.052
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3146043SEABORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315607AA1-063A GEN
Solar/Wind Harmer
0.693
316087AB2-174 GEN
Solar/Wind Harmer
0.977
315652AC1-086 GEN
Solar/Wind Harmer
7.643
3137643SOCKMAN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.026
970831AG2-522 GEN
Solar/Wind Harmer
3.234
316005AA1-067
Solar/Wind Harmer
0.129
3145746EVERETS
Solar/Wind Harmer
-0.025
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
970181AG2-120 GEN
Solar/Wind Harmer
0.838
3141426STAFORD
Solar/Wind Helper
0.114
316223AC1-118
Solar/Wind Helper
0.271
NYPJM->LTFIMP_NY
CLTF
1.15
LGEELTFEXP_LGEE->PJM
CLTF
0.646
WECLTFEXP_WEC->PJM
CLTF
0.327
LAGNLTFEXP_LAGN->PJM
CLTF
3.071
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.25
TVALTFEXP_TVA->PJM
CLTF
1.556
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.485
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.426
MECLTFEXP_MEC->PJM
CLTF
1.669
SIGELTFEXP_SIGE->PJM
CLTF
0.052
CPLELTFEXP_CPLE->PJM
CLTF
3.627
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.979

Details for 6PROFFIT-6HOLLYMD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6PROFFIT-6HOLLYMD 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 553_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.67 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1167.96
MW Contribution:62.57
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
1.205
3137383CUSHAW
50/50
0.022
3151861LOWMORA
50/50
1.128
3152191CUNINGD
50/50
1.776
3152171CUNINGB
50/50
0.767
972255AH1-712 GEN
50/50
53.693
315760AF1-028 GEN
50/50
15.215
3152051BATH 5E
50/50
2.069
3148013FISHERV
Solar/Wind Harmer
0.138
970221AG2-151 GEN
Solar/Wind Harmer
6.84
315616AA1-038_C
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.036
3146926FARMVIL
Solar/Wind Harmer
0.044
958131AF2-107 GEN
Solar/Wind Harmer
1.93
942461AE2-259 GEN
Solar/Wind Harmer
0
3132273ORANGE
Solar/Wind Helper
0.105
3147666LOUISA
Solar/Wind Helper
1.085
316170AC1-121 GEN2
Solar/Wind Helper
0.475
972205AH1-687 GEN
50/50
5.876
3151881LOWMORC
50/50
1.119
3151881LOWMORC
50/50
1.101
3151861LOWMORA
50/50
1.084
3152181CUNINGC
50/50
0.816
972193AH1-681 GEN
50/50
2.399
3152011BATH 1A
50/50
2.071
3152021BATH 2B
50/50
2.071
3152031BATH 3C
50/50
2.071
3152041BATH 4D
50/50
2.067
3138266HYDRAULIC
Solar/Wind Harmer
0.011
3138266HYDRAULIC
Solar/Wind Harmer
0.007
3148133STUARTS
Solar/Wind Harmer
0.083
3148013FISHERV
Solar/Wind Harmer
0.079
971447AH1-217 GEN
Solar/Wind Harmer
3.945
270494AE1-108_GEN
Solar/Wind Harmer
1.309
3148463FAIRFLD
Solar/Wind Harmer
0.099
971845AH1-439 GEN
Solar/Wind Harmer
4.376
970285AG2-188 GEN
Solar/Wind Harmer
7.313
316164AC1-076 GEN
Solar/Wind Helper
1.19
3151931BEARGRDN S1
50/50
1.555
3151911BEARGRDN G1
50/50
1.205
3152161CUNINGA
50/50
0.763
972277AH1-723 GEN
50/50
62.568
3152061BATH 6F
50/50
2.078
23503401SHY_Z2-039
50/50
0.003
971377AH1-170 GEN
Solar/Wind Harmer
1.368
3147623JAMES R
Solar/Wind Harmer
0.297
972003AH1-546 GEN
Solar/Wind Harmer
5.266
315705AF1-075 GEN
Solar/Wind Harmer
4.096
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.039
970937AG2-583 GEN
Solar/Wind Harmer
6.041
3147983MERCK5
Solar/Wind Harmer
0.038
3146926FARMVIL
Solar/Wind Harmer
0.044
316336AC2-165 C
Solar/Wind Harmer
0.002
316192AB2-158 GEN
Solar/Wind Helper
3.262
3147666LOUISA
Solar/Wind Helper
1.887
316254AC1-120 GEN1
Solar/Wind Helper
1.426
316006AB2-029 C
Solar/Wind Helper
0.088
23503501NHY_Z2-039
50/50
0.005
315821AE2-092 GEN
Solar/Wind Harmer
0.008
971489AH1-241 GEN
Solar/Wind Harmer
6.84
3146776BUCKING
Solar/Wind Harmer
0.395
3146776BUCKING
Solar/Wind Harmer
0.032
3132123MT JACKSON
Solar/Wind Harmer
0.208
970117AG2-086 GEN
Solar/Wind Harmer
1.594
970117AG2-086 GEN
Solar/Wind Harmer
1.063
966001AG1-469 GEN
Solar/Wind Helper
0.735
315651AD1-115 GEN
Solar/Wind Helper
0.962
NYPJM->LTFIMP_NY
CLTF
0.747
LGEELTFEXP_LGEE->PJM
CLTF
0.893
WECLTFEXP_WEC->PJM
CLTF
0.458
LAGNLTFEXP_LAGN->PJM
CLTF
2.697
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.536
TVALTFEXP_TVA->PJM
CLTF
1.4
CBM West 1LTFEXP_CBM-W1->PJM
CBM
16.766
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.191
MECLTFEXP_MEC->PJM
CLTF
2.078
SIGELTFEXP_SIGE->PJM
CLTF
0.068
CPLELTFEXP_CPLE->PJM
CLTF
0.939
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.474

Details for 6PROFFIT-6HOLLYMD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6PROFFIT-6HOLLYMD 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.71 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1050.18
MW Contribution:37.31
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
1.262
3137383CUSHAW
50/50
0.018
3151861LOWMORA
50/50
0.943
315760AF1-028 GEN
50/50
12.698
3152051BATH 5E
50/50
1.654
3144293JTRSVLE
50/50
0.21
3152191CUNINGD
50/50
1.059
3152171CUNINGB
50/50
0.457
972255AH1-712 GEN
50/50
32.018
970221AG2-151 GEN
Solar/Wind Harmer
7.052
3148013FISHERV
Solar/Wind Harmer
0.123
3146776BUCKING
Solar/Wind Harmer
0.039
3146926FARMVIL
Solar/Wind Harmer
0.052
315616AA1-038_C
Solar/Wind Harmer
0.001
942461AE2-259 GEN
Solar/Wind Harmer
0
316313AB2-026
Solar/Wind Harmer
0.042
316258AE1-075 C
Solar/Wind Harmer
0.05
316405AF2-144 C
Solar/Wind Harmer
0
3143336POWHATN
Solar/Wind Harmer
1.009
958131AF2-107 GEN
Solar/Wind Harmer
1.905
3147133PAMPLIN
Solar/Wind Harmer
0.206
971193AH1-056 GEN
Solar/Wind Harmer
3.999
970909AG2-566 GEN
Solar/Wind Harmer
0.694
963181AG1-167 GEN
Solar/Wind Harmer
0.249
3132273ORANGE
Solar/Wind Helper
0.106
3147666LOUISA
Solar/Wind Helper
1.086
316170AC1-121 GEN2
Solar/Wind Helper
0.478
972205AH1-687 GEN
50/50
6.155
3151881LOWMORC
50/50
0.936
3151881LOWMORC
50/50
0.921
3151861LOWMORA
50/50
0.906
3152011BATH 1A
50/50
1.656
3152021BATH 2B
50/50
1.656
3152031BATH 3C
50/50
1.655
3152041BATH 4D
50/50
1.652
3152181CUNINGC
50/50
0.486
972193AH1-681 GEN
50/50
1.431
3138266HYDRAULIC
Solar/Wind Harmer
0.011
3138266HYDRAULIC
Solar/Wind Harmer
0.007
971447AH1-217 GEN
Solar/Wind Harmer
4.022
3148133STUARTS
Solar/Wind Harmer
0.074
3148013FISHERV
Solar/Wind Harmer
0.071
270494AE1-108_GEN
Solar/Wind Harmer
1.339
971845AH1-439 GEN
Solar/Wind Harmer
4.834
970285AG2-188 GEN
Solar/Wind Harmer
8.151
3148463FAIRFLD
Solar/Wind Harmer
0.083
315657AE1-056 GEN
Solar/Wind Harmer
2.265
946301AF1-294 GEN
Solar/Wind Harmer
1.229
961791AG1-021 GEN
Solar/Wind Harmer
0.598
970683AG2-441 GEN
Solar/Wind Harmer
3.826
970681AG2-440 GEN
Solar/Wind Harmer
3.061
316164AC1-076 GEN
Solar/Wind Helper
1.194
3151931BEARGRDN S1
50/50
1.629
3151911BEARGRDN G1
50/50
1.262
3152061BATH 6F
50/50
1.661
3144293JTRSVLE
50/50
0.21
23503401SHY_Z2-039
50/50
0.002
3152161CUNINGA
50/50
0.455
972277AH1-723 GEN
50/50
37.31
971377AH1-170 GEN
Solar/Wind Harmer
1.41
3147623JAMES R
Solar/Wind Harmer
0.306
972003AH1-546 GEN
Solar/Wind Harmer
5.557
970937AG2-583 GEN
Solar/Wind Harmer
6.724
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.043
3146926FARMVIL
Solar/Wind Harmer
0.052
315705AF1-075 GEN
Solar/Wind Harmer
3.448
3147983MERCK5
Solar/Wind Harmer
0.033
316336AC2-165 C
Solar/Wind Harmer
0.003
3143336POWHATN
Solar/Wind Harmer
1.187
963171AG1-166 GEN
Solar/Wind Harmer
0.332
971563AH1-280 GEN
Solar/Wind Harmer
0.664
970685AG2-442 GEN
Solar/Wind Harmer
4.286
316192AB2-158 GEN
Solar/Wind Helper
3.267
3147666LOUISA
Solar/Wind Helper
1.889
316254AC1-120 GEN1
Solar/Wind Helper
1.434
316006AB2-029 C
Solar/Wind Helper
0.088
3144293JTRSVLE
50/50
0.21
3144293JTRSVLE
50/50
0.177
23503501NHY_Z2-039
50/50
0.004
971489AH1-241 GEN
Solar/Wind Harmer
7.052
315821AE2-092 GEN
Solar/Wind Harmer
0.008
3146776BUCKING
Solar/Wind Harmer
0.434
3146776BUCKING
Solar/Wind Harmer
0.035
3147133PAMPLIN
Solar/Wind Harmer
0.066
3147133PAMPLIN
Solar/Wind Harmer
0.052
970301AG2-198 GEN
Solar/Wind Harmer
2.774
958211AF2-115 GEN
Solar/Wind Harmer
0.747
963191AG1-168 GEN
Solar/Wind Harmer
0.249
971741AH1-377 GEN
Solar/Wind Harmer
5.799
966001AG1-469 GEN
Solar/Wind Helper
0.74
315651AD1-115 GEN
Solar/Wind Helper
0.968
NYPJM->LTFIMP_NY
CLTF
0.852
LGEELTFEXP_LGEE->PJM
CLTF
0.839
WECLTFEXP_WEC->PJM
CLTF
0.429
LAGNLTFEXP_LAGN->PJM
CLTF
2.954
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.46
TVALTFEXP_TVA->PJM
CLTF
1.519
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.521
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.505
MECLTFEXP_MEC->PJM
CLTF
2.015
SIGELTFEXP_SIGE->PJM
CLTF
0.065
CPLELTFEXP_CPLE->PJM
CLTF
1.993
CBM West 2LTFEXP_CBM-W2->PJM
CBM
18.046

Details for 6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 574T575_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 574T575_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:140.5 %
Rating:1809.0 MVA
Rating Type:C
MVA to Mitigate:2541.71
MW Contribution:51.66
Bus #Bus NameTypeMW Contribution
972189AH1-679 GEN
50/50
6.496
316312AB1-027
Solar/Wind Harmer
0.64
971285AH1-108 GEN
Adder
1.052
315976AC1-164 GENA
Solar/Wind Harmer
15.998
316169AC1-164_GENC
Solar/Wind Harmer
13.821
315975AC1-164 GENB
Solar/Wind Harmer
0.473
316132AB2-190 GEN1
Solar/Wind Harmer
1.45
316233AE1-074 FULL
Solar/Wind Harmer
0.383
971281AH1-106 GEN
Solar/Wind Harmer
2.311
971283AH1-107 GEN
Solar/Wind Harmer
2.311
971167AH1-042 GEN
Solar/Wind Harmer
13.55
3142433PROV 92
Adder
0.24
3142433PROV 92
Adder
0.24
316369SG1_INVT
Solar/Wind Harmer
2.478
3143873LANEXA
Solar/Wind Harmer
-0.008
3143316POE
Solar/Wind Harmer
-0.052
972265AH1-717 GEN
Adder
9.04
3151201GRAVEL4
Adder
8.475
3151191GRAVEL3
Adder
8.367
3151211GRAVEL5
Adder
8.367
316314AB2-024 C
Solar/Wind Harmer
1.098
971445AH1-216 GEN
Solar/Wind Harmer
7.863
316059AD1-063 C
Solar/Wind Harmer
0.284
957831AF2-077 GEN
Solar/Wind Harmer
0.376
3138283WHITEMARSH
Solar/Wind Harmer
0.019
315662AE1-191 GEN
Solar/Wind Harmer
1.493
315666AE1-190 GEN
Solar/Wind Harmer
0.373
315833AF1-017_GEN
Solar/Wind Harmer
2.326
316349AD2-085 GEN
Solar/Wind Harmer
1.089
316311AC2-079 GEN
Solar/Wind Harmer
6.173
957601AF2-054 GEN
Solar/Wind Harmer
0.363
3141873WAN 176
Solar/Wind Harmer
-0.002
3152611GOSPORTB
Adder
1.36
3152621GOSPORTC
Adder
1.154
3152601GOSPORTA
Adder
1.065
3151081ELIZAR1
Adder
9.78
3151091ELIZAR2
Adder
9.61
315835AF2-110_GEN
Solar/Wind Harmer
1.479
957871AF2-081 GEN
Solar/Wind Harmer
5.897
316305AF2-043 C
Solar/Wind Harmer
0.355
319010AE1-072 C
Solar/Wind Harmer
2.378
3146406KITTY HAWK
Solar/Wind Harmer
0.01
313526AB2-022
Solar/Wind Harmer
0.314
3146486SUNBURY
Solar/Wind Harmer
-0.012
3146486SUNBURY
Solar/Wind Harmer
-0.012
3141913WHIT STONE
Solar/Wind Harmer
-0.012
316321Z2-027
Solar/Wind Harmer
0.312
3146396TANGLEW
Solar/Wind Harmer
0.213
3145176PASQUOTANK
Solar/Wind Harmer
-0.007
3138133OCRAN
Solar/Wind Harmer
-0.003
316315AB2-025 C
Solar/Wind Harmer
0.307
315814AE2-033 C
Solar/Wind Harmer
10.558
315611Z1-036_GEN2
Solar/Wind Harmer
2.785
3141783LANCAST
Solar/Wind Harmer
-0.007
3141783LANCAST
Solar/Wind Harmer
-0.004
3130156CHOWAN
Solar/Wind Harmer
-0.011
3130156CHOWAN
Solar/Wind Harmer
-0.011
315816AE2-034 GEN
Solar/Wind Harmer
0.877
3130546PLYMOUTH
Solar/Wind Harmer
-0.011
315732AD1-074 GEN1
Solar/Wind Harmer
2.139
315733AD1-074 GEN2
Solar/Wind Harmer
2.139
315735AD1-075 GEN1
Solar/Wind Harmer
1.07
962981AG1-147 GEN
Solar/Wind Harmer
4.609
965291AG1-394 GEN
Solar/Wind Harmer
0.933
3146206CASHIE
Solar/Wind Harmer
-0.01
970601AG2-382 GEN
Solar/Wind Harmer
4.572
316318V4-068
Solar/Wind Harmer
0.259
3145893MURPHYS
Solar/Wind Harmer
-0.028
3145893MURPHYS
Solar/Wind Harmer
-0.01
3145513AHOSKIE
Solar/Wind Harmer
0.089
961941AG1-037 GEN
Solar/Wind Harmer
0.077
3145513AHOSKIE
Solar/Wind Harmer
-0.01
3145683EARLEYS
Solar/Wind Harmer
-0.02
3145683EARLEYS
Solar/Wind Harmer
-0.01
3145683EARLEYS
Solar/Wind Harmer
-0.01
3146043SEABORD
Solar/Wind Harmer
-0.01
315607AA1-063A GEN
Solar/Wind Harmer
1.016
946281AF1-292 GEN
Solar/Wind Harmer
0.225
316087AB2-174 GEN
Solar/Wind Harmer
1.418
315652AC1-086 GEN
Solar/Wind Harmer
11.162
941031AE2-094 GEN
Solar/Wind Harmer
18.558
944011AF1-069 GEN
Solar/Wind Harmer
5.815
3137643SOCKMAN
Solar/Wind Harmer
-0.039
970673AG2-436 GEN
Solar/Wind Harmer
20.5
970673AG2-436 GEN
Solar/Wind Harmer
10.38
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.004
972193AH1-681 GEN
Adder
1.981
3146033SCOT NK
Solar/Wind Harmer
-0.038
971967AH1-528 GEN
Solar/Wind Harmer
18.168
970085AG2-068 GEN
Solar/Wind Harmer
5.8
970581AG2-369 GEN
Solar/Wind Harmer
4.988
316005AA1-067
Solar/Wind Harmer
0.188
3145746EVERETS
Solar/Wind Harmer
-0.037
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
970181AG2-120 GEN
Solar/Wind Harmer
1.217
957861AF2-080 GEN
Solar/Wind Harmer
3.974
970831AG2-522 GEN
Solar/Wind Harmer
4.54
316420AA1-050 GEN
Solar/Wind Harmer
1.027
3145573BETHELC
Solar/Wind Harmer
-0.009
3145573BETHELC
Solar/Wind Harmer
-0.009
316319Z2-044 C
Solar/Wind Harmer
0.492
972205AH1-687 GEN
Adder
2.844
3141426STAFORD
Solar/Wind Helper
0.043
315051AA1-145 CT1
50/50
2.898
971645AH1-323 GEN
50/50
17.376
966881AG1-559 GEN
Solar/Wind Harmer
2.184
3142416OLDCHRC
Solar/Wind Harmer
1.914
316473AC1-191 GEN
Solar/Wind Harmer
2.025
970293AG2-193 GEN
Solar/Wind Harmer
2.132
3143096IRON208
Adder
0.606
3143096IRON208
Adder
0.594
3150861SPRUNCD
Adder
0.643
3142946ENON
Solar/Wind Harmer
-0.005
970133AG2-095 GEN
Solar/Wind Harmer
1.669
965281AG1-393 GEN
Solar/Wind Harmer
1.802
970129AG2-093 GEN
Solar/Wind Harmer
8.1
315839AE2-212 C
Solar/Wind Harmer
0.433
315778AD1-151 GEN
Solar/Wind Harmer
12.182
3142433PROV 92
Adder
0.24
3142433PROV 92
Adder
0.24
316382AG1-145 C
Solar/Wind Harmer
0.41
961611AG1-000B GEN
Solar/Wind Harmer
2.819
315813AE1-149 C
Solar/Wind Harmer
8.328
3151221GRAVEL6
Adder
8.465
3151171GRAVELC
Adder
1.629
970659AG2-427 GEN
Solar/Wind Harmer
1.221
316083AB2-161 GEN
Solar/Wind Harmer
2.095
3144216WINCHST
Adder
0.432
3150921YORKTN3
Adder
2.87
970661AG2-428 GEN
Solar/Wind Harmer
2.394
3145336SMITFLD
Solar/Wind Harmer
-0.005
3141843SHACKLE
Adder
0.572
316203AE2-005 GEN
Solar/Wind Harmer
5.302
3141766HARMONY
Solar/Wind Harmer
1.119
316280AD1-041 GEN
Solar/Wind Harmer
0.933
3144536CHRHLND
Solar/Wind Harmer
-0.002
316156AD2-030 GEN
Solar/Wind Harmer
0.324
3141873WAN 176
Solar/Wind Harmer
1.439
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
9.905
315773AC2-141 GEN
Solar/Wind Harmer
4.984
944581AF1-123 GEN
Solar/Wind Harmer
53.957
944601AF1-125 GEN
Solar/Wind Harmer
53.115
3146456SLIGO L269
Solar/Wind Harmer
-0.012
971153AH1-033 GEN
Solar/Wind Harmer
1.434
316320Y1-086
Solar/Wind Harmer
0.682
316435W1029_GEN3
Solar/Wind Harmer
2.086
971781AH1-399 GEN
Solar/Wind Harmer
0.708
3146516WINFALL
Solar/Wind Harmer
-0.011
3145273HOLLAND
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.011
3146376EDENTON
Solar/Wind Harmer
-0.011
315614AA2-178 GEN
Solar/Wind Harmer
1.169
971157AH1-035 GEN
Solar/Wind Harmer
1.327
315737AD1-076 GEN
Solar/Wind Harmer
2.01
316313AB2-026
Solar/Wind Harmer
0.285
316258AE1-075 C
Solar/Wind Harmer
0.257
316405AF2-144 C
Solar/Wind Harmer
0.271
3143336POWHATN
Solar/Wind Harmer
1.067
3156081AA2-088 GEN
Solar/Wind Harmer
3.431
962971AG1-146 GEN
Solar/Wind Harmer
1.975
3146206CASHIE
Solar/Wind Harmer
-0.01
316365GEN2_N
Solar/Wind Harmer
0.702
3145893MURPHYS
Solar/Wind Harmer
0.073
3145893MURPHYS
Solar/Wind Harmer
-0.01
957521AF2-046 GEN
Solar/Wind Harmer
8.162
961681AG1-008 GEN
Solar/Wind Harmer
8.162
3146173TUNIS
Solar/Wind Harmer
-0.01
3156021HOLLOMANSOL
Solar/Wind Harmer
1.383
316463AE2-346 GEN
Solar/Wind Harmer
0.165
316140AB2-099
Solar/Wind Harmer
0.069
962331AG1-082 GEN
Solar/Wind Harmer
1.277
316484AD2-074 GEN
Solar/Wind Harmer
2.562
970009AG2-005 GEN
Solar/Wind Harmer
1.272
3146263WOODLND
Solar/Wind Harmer
-0.01
966621AG1-532 GEN
Solar/Wind Harmer
0.204
3145963POPLR C
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
316317KELFORD C
Solar/Wind Harmer
0.468
3145823KELFORD
Solar/Wind Harmer
-0.01
313506AB2-031 GEN
Solar/Wind Harmer
0.796
3145796HORNRTN
Solar/Wind Harmer
-0.039
3145796HORNRTN
Solar/Wind Harmer
-0.01
972255AH1-712 GEN
Adder
44.332
316404AE1-155 C
Solar/Wind Harmer
1.851
3147043LAWRENC
Solar/Wind Harmer
-0.006
3145933PARMELE
Solar/Wind Harmer
-0.009
966801AG1-551 GEN
Solar/Wind Harmer
1.188
316210AC1-098 GEN
Solar/Wind Harmer
1.487
970917AG2-570 GEN
Solar/Wind Harmer
23.277
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
315724AD1-057 GEN
Solar/Wind Harmer
0.528
316327AA2-057 GEN
Solar/Wind Harmer
0.917
3146073TAR RVR
Solar/Wind Harmer
-0.009
3146083TARBORO
Solar/Wind Harmer
-0.009
3146233WITAKRS
Solar/Wind Harmer
0.186
3146233WITAKRS
Solar/Wind Harmer
-0.006
3138543CONSLDL
Solar/Wind Harmer
-0.006
3150351NORNECKC2
Adder
0.772
3144293JTRSVLE
Adder
0.236
3142296MT RD221
50/50
0.631
3142366NRTHEST
50/50
0.558
3150691DARBY 3
50/50
12.032
3150701DARBY 4
50/50
12.004
3150681DARBY 2
50/50
11.99
957411AF2-035 GEN
Solar/Wind Harmer
32.692
970317AG2-208 GEN
Solar/Wind Harmer
31.784
966871AG1-558 GEN
Solar/Wind Harmer
0.566
966871AG1-558 GEN
Solar/Wind Harmer
0.194
3150671DARBY 1
Adder
11.286
316075AC2-137 C
Solar/Wind Harmer
0.441
3142946ENON
Solar/Wind Harmer
-0.002
944641AF1-129 GEN
Adder
65.069
316240AF1-291 C
Solar/Wind Harmer
0.455
3143526WINTERP
Solar/Wind Harmer
-0.074
316033AB2-134 GEN
Solar/Wind Harmer
4.473
315697AD1-025 GEN
Solar/Wind Harmer
2.805
970657AG2-426 GEN
Solar/Wind Harmer
4.011
970657AG2-426 GEN
Solar/Wind Harmer
0.839
316236AE1-162_GEN
Solar/Wind Harmer
0.382
971223AH1-071 GEN
Solar/Wind Harmer
1.579
316441AF1-014 GEN
Solar/Wind Harmer
0.848
316036AC1-147 C
Solar/Wind Harmer
0.324
3150991CHESPKB
Adder
1.119
3150991CHESPKB
Adder
1.092
316316AC1-027 C
Solar/Wind Harmer
0.366
3142956BIRDNECK
Solar/Wind Harmer
0.64
316185AD1-033 GEN
Solar/Wind Harmer
1.254
3145506HICKORY
Solar/Wind Harmer
-0.047
3145506HICKORY
Solar/Wind Harmer
-0.028
3145506HICKORY
Solar/Wind Harmer
-0.007
316339AD2-160 GEN
Solar/Wind Harmer
0.796
316018AA1-139 ULT2
Solar/Wind Harmer
1.01
316017AA1-139 ULT1
Solar/Wind Harmer
0.954
3137176SLIGO L2192
Solar/Wind Harmer
-0.047
3146456SLIGO L269
Solar/Wind Harmer
1.39
3130086AYDLETT
Solar/Wind Harmer
-0.047
3146386ELIZ CT
Solar/Wind Harmer
-0.012
316431W1029_GEN1
Solar/Wind Harmer
2.086
316433W1029_GEN2
Solar/Wind Harmer
2.086
316468AD1-105 GEN
Solar/Wind Harmer
1.28
3146516WINFALL
Solar/Wind Harmer
-0.011
3146516WINFALL
Solar/Wind Harmer
-0.011
3146516WINFALL
Solar/Wind Harmer
-0.011
3146626S HERTFORD
Solar/Wind Harmer
-0.011
3146626S HERTFORD
Solar/Wind Harmer
-0.011
3144356SAPONY
Solar/Wind Harmer
0.397
315742AE1-103 GEN
Solar/Wind Harmer
1.177
3146376EDENTON
Solar/Wind Harmer
0.33
3146376EDENTON
Solar/Wind Harmer
0.33
316065AD1-022 GEN
Solar/Wind Harmer
5.248
3145893MURPHYS
Solar/Wind Harmer
0.29
3145893MURPHYS
Solar/Wind Harmer
-0.019
3146173TUNIS
Solar/Wind Harmer
-0.01
3146173TUNIS
Solar/Wind Harmer
-0.01
316487AF1-042 GEN
Solar/Wind Harmer
1.34
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
316181AB2-040 GEN
Solar/Wind Harmer
1.381
316426AA2-053 GEN
Solar/Wind Harmer
0.993
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.098
3145593CAROLNA
Solar/Wind Harmer
0.081
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145783HORNRTN
Solar/Wind Harmer
1.151
3145783HORNRTN
Solar/Wind Harmer
0.921
3145783HORNRTN
Solar/Wind Harmer
0.288
3145783HORNRTN
Solar/Wind Harmer
0.115
972185AH1-677 GEN
Adder
4.839
958261AF2-120 GEN
Solar/Wind Harmer
3.718
972187AH1-678 GEN
Adder
2.432
3145933PARMELE
Solar/Wind Harmer
-0.019
3145933PARMELE
Solar/Wind Harmer
-0.009
970933AG2-581 GEN
Solar/Wind Harmer
8.889
316274AC1-208 GEN
Solar/Wind Harmer
1.012
970099AG2-077 GEN
Solar/Wind Harmer
11.254
3145493TOT1
Solar/Wind Harmer
0.138
3145453TOT5
Solar/Wind Harmer
0.083
3145603CNETO
Solar/Wind Harmer
0.055
3150341NORNECKC1
Adder
0.797
3150341NORNECKC1
Adder
0.791
3144293JTRSVLE
Adder
0.236
3144293JTRSVLE
Adder
0.199
226929AD2-058 GEN
Solar/Wind Helper
0.044
315052AA1-145 CT2
50/50
2.911
966881AG1-559 GEN
Solar/Wind Harmer
0.747
3142416OLDCHRC
Solar/Wind Harmer
-0.049
3142416OLDCHRC
Solar/Wind Harmer
-0.019
3143096IRON208
Adder
0.606
3142543TWELFTH
Solar/Wind Harmer
-0.002
3150851SPRUNCC
Adder
0.643
944631AF1-128 GEN
Adder
65.707
315671AE2-027_GEN
Solar/Wind Harmer
10.943
970129AG2-093 GEN
Solar/Wind Harmer
3.281
316458AB2-190 GEN2
Solar/Wind Harmer
1.45
3143526WINTERP
Solar/Wind Harmer
-0.074
971069AG2-661 GEN
Solar/Wind Harmer
2.225
3142433PROV 92
Solar/Wind Harmer
-0.055
3142433PROV 92
Adder
0.24
3142433PROV 92
Adder
0.24
971647AH1-324 GEN
Solar/Wind Harmer
6.815
316159AE1-175 C
Solar/Wind Harmer
0.365
961611AG1-000B GEN
Solar/Wind Harmer
6.606
3151171GRAVELC
Adder
1.239
970659AG2-427 GEN
Solar/Wind Harmer
6.892
316381AD1-082 GEN
Solar/Wind Harmer
1.184
971317AH1-138 GEN
Solar/Wind Harmer
1.611
3138126ROCKLANDING
Solar/Wind Harmer
0.039
970661AG2-428 GEN
Solar/Wind Harmer
13.512
3145336SMITFLD
Solar/Wind Harmer
-0.05
3143226MDLTHAN
Solar/Wind Harmer
-0.013
971777AH1-397 GEN
Solar/Wind Harmer
1.479
3141843SHACKLE
Adder
0.572
3141766HARMONY
Solar/Wind Harmer
-0.002
316072AD1-144
Solar/Wind Harmer
0.244
316375AC2-012 GEN
Solar/Wind Harmer
4.153
3150981CHESPKA
Adder
1.334
316294AC1-161 GEN
Solar/Wind Harmer
3.853
944591AF1-124 GEN
Solar/Wind Harmer
54.151
316093AE2-104_GEN
Solar/Wind Harmer
3.44
316388AE2-253 GEN
Solar/Wind Harmer
0.796
316246AF1-032 C
Solar/Wind Harmer
0.239
3146456SLIGO L269
Solar/Wind Harmer
-0.012
3146516WINFALL
Solar/Wind Harmer
-0.037
3146516WINFALL
Solar/Wind Harmer
-0.011
3138133OCRAN
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
2.785
3130156CHOWAN
Solar/Wind Harmer
-0.011
939411AE1-173 GEN
Solar/Wind Harmer
54.187
3145663CRESWEL
Solar/Wind Harmer
-0.03
971163AH1-040 GEN
Solar/Wind Harmer
10.157
3143336POWHATN
Solar/Wind Harmer
1.255
940641AE2-051 GEN
Solar/Wind Harmer
9.841
3146206CASHIE
Solar/Wind Harmer
-0.01
971547AH1-271 GEN
Solar/Wind Harmer
2.612
316023GEN1_S
Solar/Wind Harmer
0.702
3145893MURPHYS
Solar/Wind Harmer
-0.041
3145893MURPHYS
Solar/Wind Harmer
0.309
3146173TUNIS
Solar/Wind Harmer
-0.01
961951AG1-038 GEN
Solar/Wind Harmer
1.34
3145683EARLEYS
Solar/Wind Harmer
-0.01
3146263WOODLND
Solar/Wind Harmer
-0.01
316336AC2-165 C
Solar/Wind Harmer
1.744
960081AF2-299 GEN
Solar/Wind Harmer
1.128
3145963POPLR C
Solar/Wind Harmer
-0.01
316011AB1-132 GEN
Solar/Wind Harmer
2.076
962571AG1-106 GEN
Solar/Wind Harmer
1.426
3145823KELFORD
Solar/Wind Harmer
-0.01
316174AB2-169 GEN
Solar/Wind Harmer
1.527
316190AA2-174 GEN
Solar/Wind Harmer
0.121
962861AG1-135 GEN
Solar/Wind Harmer
3.656
3145796HORNRTN
Solar/Wind Harmer
-0.032
3145796HORNRTN
Solar/Wind Harmer
-0.01
972277AH1-723 GEN
Adder
51.66
971795AH1-408 GEN
Solar/Wind Harmer
7.284
3145783HORNRTN
Solar/Wind Harmer
-0.01
3147043LAWRENC
Adder
0.77
3146293MARTNCO
Solar/Wind Harmer
0.059
316212AC1-099_GEN
Solar/Wind Harmer
0.826
970919AG2-571 GEN
Solar/Wind Harmer
2.946
970087AG2-069 GEN
Solar/Wind Harmer
8.699
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
315722AD1-056 GEN
Solar/Wind Harmer
0.96
964211AG1-282 GEN
Solar/Wind Harmer
0.275
3141726DUNNSVL
Solar/Wind Harmer
-0.036
316494AC1-189 GEN
Solar/Wind Harmer
0.977
316129AC1-054 GEN
Solar/Wind Harmer
0.79
957481AF2-042 GEN
Solar/Wind Harmer
28.134
971065AG2-659 GEN
Solar/Wind Harmer
4.471
961671AG1-007 GEN
Solar/Wind Harmer
0.113
3146083TARBORO
Solar/Wind Harmer
-0.009
3145493TOT1
Solar/Wind Harmer
0.265
3146233WITAKRS
Solar/Wind Harmer
-0.035
3150351NORNECKC2
Adder
0.759
3144293JTRSVLE
Adder
0.236
315693AD1-088 GEN
Solar/Wind Harmer
0.172
NYPJM->LTFIMP_NY
CLTF
1.538
LGEELTFEXP_LGEE->PJM
CLTF
0.748
WECLTFEXP_WEC->PJM
CLTF
0.372
LAGNLTFEXP_LAGN->PJM
CLTF
3.852
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.958
TVALTFEXP_TVA->PJM
CLTF
1.953
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.851
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.75
MECLTFEXP_MEC->PJM
CLTF
1.962
SIGELTFEXP_SIGE->PJM
CLTF
0.06
CPLELTFEXP_CPLE->PJM
CLTF
4.899
CBM West 2LTFEXP_CBM-W2->PJM
CBM
20.775

Details for 6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:134.25 %
Rating:1478.62 MVA
Rating Type:B
MVA to Mitigate:1985.01
MW Contribution:48.21
Bus #Bus NameTypeMW Contribution
3142296MT RD221
50/50
0.608
3142366NRTHEST
50/50
0.528
3150691DARBY 3
50/50
11.375
3150701DARBY 4
50/50
11.349
3150681DARBY 2
50/50
11.335
957411AF2-035 GEN
Solar/Wind Harmer
28.305
970317AG2-208 GEN
Solar/Wind Harmer
26.223
966871AG1-558 GEN
Solar/Wind Harmer
0.187
3150671DARBY 1
Adder
10.67
316075AC2-137 C
Solar/Wind Harmer
0.038
3142946ENON
Solar/Wind Harmer
0.013
944641AF1-129 GEN
Adder
59.87
316240AF1-291 C
Solar/Wind Harmer
0.001
3143526WINTERP
Solar/Wind Harmer
0.585
316033AB2-134 GEN
Solar/Wind Harmer
0.007
315697AD1-025 GEN
Solar/Wind Harmer
0.126
316468AD1-105 GEN
Solar/Wind Harmer
-0.033
970657AG2-426 GEN
Solar/Wind Harmer
3.569
970657AG2-426 GEN
Solar/Wind Harmer
0.748
316236AE1-162_GEN
Solar/Wind Harmer
0.001
971223AH1-071 GEN
Solar/Wind Harmer
1.027
316036AC1-147 C
Solar/Wind Harmer
0.017
3150991CHESPKB
Adder
0.985
3150991CHESPKB
Adder
0.962
316316AC1-027 C
Solar/Wind Harmer
0.09
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.003
3145506HICKORY
Solar/Wind Harmer
0.37
3145506HICKORY
Solar/Wind Harmer
0.222
3145506HICKORY
Solar/Wind Harmer
0.056
316339AD2-160 GEN
Solar/Wind Harmer
0.15
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.051
3137176SLIGO L2192
Solar/Wind Harmer
0.366
3146456SLIGO L269
Solar/Wind Harmer
1.627
3130086AYDLETT
Solar/Wind Harmer
0.367
3146386ELIZ CT
Solar/Wind Harmer
0.091
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.089
3146516WINFALL
Solar/Wind Harmer
0.089
3146516WINFALL
Solar/Wind Harmer
0.089
3146626S HERTFORD
Solar/Wind Harmer
0.089
3146626S HERTFORD
Solar/Wind Harmer
0.089
3144356SAPONY
Solar/Wind Harmer
0.735
315742AE1-103 GEN
Solar/Wind Harmer
0.001
3146376EDENTON
Solar/Wind Harmer
0.385
3146376EDENTON
Solar/Wind Harmer
0.385
316065AD1-022 GEN
Solar/Wind Harmer
3.744
958261AF2-120 GEN
Solar/Wind Harmer
2.666
3145893MURPHYS
Solar/Wind Harmer
0.538
3145893MURPHYS
Solar/Wind Harmer
0.145
3146173TUNIS
Solar/Wind Harmer
0.079
3146173TUNIS
Solar/Wind Harmer
0.079
3142666NORTHAMPTON
Solar/Wind Harmer
0.076
3142666NORTHAMPTON
Solar/Wind Harmer
0.076
3142666NORTHAMPTON
Solar/Wind Harmer
0.076
3142666NORTHAMPTON
Solar/Wind Harmer
0.046
316181AB2-040 GEN
Solar/Wind Harmer
0.11
316426AA2-053 GEN
Solar/Wind Harmer
0.255
3145796HORNRTN
Solar/Wind Harmer
0.224
3145593CAROLNA
Solar/Wind Harmer
0.075
3145593CAROLNA
Solar/Wind Harmer
0.075
966811AG1-552 GEN
Solar/Wind Harmer
0.811
3145593CAROLNA
Solar/Wind Harmer
0.093
3145783HORNRTN
Solar/Wind Harmer
1.321
3145783HORNRTN
Solar/Wind Harmer
1.057
3145783HORNRTN
Solar/Wind Harmer
0.33
3145783HORNRTN
Solar/Wind Harmer
0.132
3145933PARMELE
Solar/Wind Harmer
0.146
3145933PARMELE
Solar/Wind Harmer
0.073
316077AC2-138 C
Solar/Wind Harmer
0
3150341NORNECKC1
Adder
0.759
3150341NORNECKC1
Adder
0.753
316274AC1-208 GEN
Solar/Wind Harmer
0.373
972185AH1-677 GEN
Adder
3.992
972187AH1-678 GEN
Adder
2.007
970933AG2-581 GEN
Solar/Wind Harmer
5.576
3145493TOT1
Solar/Wind Harmer
0.158
3145453TOT5
Solar/Wind Harmer
0.095
3145603CNETO
Solar/Wind Harmer
0.063
961601AG1-000A GEN
Solar/Wind Harmer
1.182
316263AC1-034 GEN
Solar/Wind Harmer
2.524
970099AG2-077 GEN
Solar/Wind Harmer
7.081
939181AE1-148 GEN
Solar/Wind Harmer
3.089
313527AB2-043 GEN
Solar/Wind Harmer
0.001
971741AH1-377 GEN
Solar/Wind Harmer
6.257
316034AC1-036 C
Solar/Wind Harmer
0.005
970323AG2-213 GEN
Solar/Wind Harmer
2.676
971775AH1-396 GEN
Solar/Wind Harmer
0.1
970301AG2-198 GEN
Solar/Wind Harmer
2.661
958211AF2-115 GEN
Solar/Wind Harmer
0.743
963191AG1-168 GEN
Solar/Wind Harmer
0.248
3144293JTRSVLE
Adder
0.197
3144293JTRSVLE
Adder
0.166
3147133PAMPLIN
Solar/Wind Harmer
0.062
3147133PAMPLIN
Solar/Wind Harmer
0.049
962561AG1-105 GEN
Solar/Wind Harmer
2.907
964791AG1-342 GEN
Solar/Wind Harmer
1.152
3146843MT LREL
Solar/Wind Harmer
0.06
3146843MT LREL
Solar/Wind Harmer
0.06
3146776BUCKING
Solar/Wind Harmer
0.231
3146776BUCKING
Solar/Wind Harmer
0.019
972189AH1-679 GEN
50/50
6.54
316312AB1-027
Solar/Wind Harmer
0.289
971285AH1-108 GEN
Adder
0.966
315976AC1-164 GENA
Solar/Wind Harmer
13.07
316169AC1-164_GENC
Solar/Wind Harmer
11.292
315975AC1-164 GENB
Solar/Wind Harmer
0.387
971167AH1-042 GEN
Solar/Wind Harmer
10.363
316132AB2-190 GEN1
Solar/Wind Harmer
0.626
3142433PROV 92
Adder
0.224
3142433PROV 92
Adder
0.224
316233AE1-074 FULL
Solar/Wind Harmer
0.09
971281AH1-106 GEN
Solar/Wind Harmer
1.562
971283AH1-107 GEN
Solar/Wind Harmer
1.562
316369SG1_INVT
Solar/Wind Harmer
0.004
3143873LANEXA
Solar/Wind Harmer
0.066
316314AB2-024 C
Solar/Wind Harmer
0
3143316POE
Solar/Wind Harmer
0.414
972265AH1-717 GEN
Adder
8.131
3151201GRAVEL4
Adder
7.623
3151191GRAVEL3
Adder
7.526
3151211GRAVEL5
Adder
7.526
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
3.086
315662AE1-191 GEN
Solar/Wind Harmer
0.003
315666AE1-190 GEN
Solar/Wind Harmer
0.001
3138283WHITEMARSH
Solar/Wind Harmer
0.024
971445AH1-216 GEN
Solar/Wind Harmer
7.113
3141873WAN 176
Solar/Wind Harmer
0.02
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.066
316311AC2-079 GEN
Solar/Wind Harmer
2.768
3141913WHIT STONE
Solar/Wind Harmer
0.096
3138133OCRAN
Solar/Wind Harmer
0.028
3152611GOSPORTB
Adder
1.198
3152621GOSPORTC
Adder
1.017
3152601GOSPORTA
Adder
0.938
3151081ELIZAR1
Adder
8.608
3151091ELIZAR2
Adder
8.459
3141783LANCAST
Solar/Wind Harmer
0.056
3141783LANCAST
Solar/Wind Harmer
0.037
315835AF2-110_GEN
Solar/Wind Harmer
0.636
316305AF2-043 C
Solar/Wind Harmer
0.001
957871AF2-081 GEN
Solar/Wind Harmer
4.589
319010AE1-072 C
Solar/Wind Harmer
0.463
3146406KITTY HAWK
Solar/Wind Harmer
0.011
313526AB2-022
Solar/Wind Harmer
0.049
3146486SUNBURY
Solar/Wind Harmer
0.091
3146486SUNBURY
Solar/Wind Harmer
0.091
316321Z2-027
Solar/Wind Harmer
0.017
3146396TANGLEW
Solar/Wind Harmer
0.249
3145176PASQUOTANK
Solar/Wind Harmer
0.056
962981AG1-147 GEN
Solar/Wind Harmer
3.282
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
316315AB2-025 C
Solar/Wind Harmer
0.071
315814AE2-033 C
Solar/Wind Harmer
6.916
3130156CHOWAN
Solar/Wind Harmer
0.086
3130156CHOWAN
Solar/Wind Harmer
0.086
970327AG2-215 GEN
Solar/Wind Harmer
2.794
315816AE2-034 GEN
Solar/Wind Harmer
0.361
3130546PLYMOUTH
Solar/Wind Harmer
0.082
315732AD1-074 GEN1
Solar/Wind Harmer
0.471
315733AD1-074 GEN2
Solar/Wind Harmer
0.471
315735AD1-075 GEN1
Solar/Wind Harmer
0.236
965291AG1-394 GEN
Solar/Wind Harmer
0.361
3146206CASHIE
Solar/Wind Harmer
0.081
970601AG2-382 GEN
Solar/Wind Harmer
3.02
972193AH1-681 GEN
Adder
1.848
3145893MURPHYS
Solar/Wind Harmer
0.217
3145893MURPHYS
Solar/Wind Harmer
0.08
3145513AHOSKIE
Solar/Wind Harmer
0.165
3145513AHOSKIE
Solar/Wind Harmer
0.079
3145683EARLEYS
Solar/Wind Harmer
0.157
3145683EARLEYS
Solar/Wind Harmer
0.078
3145683EARLEYS
Solar/Wind Harmer
0.078
3146043SEABORD
Solar/Wind Harmer
0.078
315607AA1-063A GEN
Solar/Wind Harmer
0.158
315652AC1-086 GEN
Solar/Wind Harmer
8.376
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.3
3145796HORNRTN
Solar/Wind Harmer
0.239
3145796HORNRTN
Solar/Wind Harmer
0.03
3146033SCOT NK
Solar/Wind Harmer
0.297
941031AE2-094 GEN
Solar/Wind Harmer
13.369
944011AF1-069 GEN
Solar/Wind Harmer
4.368
3141813NORNECK
Solar/Wind Harmer
0.072
970673AG2-436 GEN
Solar/Wind Harmer
15.278
970673AG2-436 GEN
Solar/Wind Harmer
10.185
316005AA1-067
Solar/Wind Harmer
0.076
3145746EVERETS
Solar/Wind Harmer
0.283
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
970181AG2-120 GEN
Solar/Wind Harmer
0.885
971967AH1-528 GEN
Solar/Wind Harmer
11.354
957861AF2-080 GEN
Solar/Wind Harmer
2.998
316420AA1-050 GEN
Solar/Wind Harmer
0.002
970831AG2-522 GEN
Solar/Wind Harmer
2.933
970085AG2-068 GEN
Solar/Wind Harmer
3.642
970581AG2-369 GEN
Solar/Wind Harmer
3.132
3145573BETHELC
Solar/Wind Harmer
0.068
3145573BETHELC
Solar/Wind Harmer
0.068
316319Z2-044 C
Solar/Wind Harmer
0
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
971443AH1-215 GEN
Solar/Wind Harmer
1.054
3144303KENBRDG
Solar/Wind Harmer
0.05
970683AG2-441 GEN
Solar/Wind Harmer
4.154
970681AG2-440 GEN
Solar/Wind Harmer
3.323
946301AF1-294 GEN
Solar/Wind Harmer
1.222
961791AG1-021 GEN
Solar/Wind Harmer
0.594
315657AE1-056 GEN
Solar/Wind Harmer
2.127
316118AC1-105 GEN
Solar/Wind Harmer
0.152
970285AG2-188 GEN
Solar/Wind Harmer
4.613
971845AH1-439 GEN
Solar/Wind Harmer
2.627
3147173SINAI
Solar/Wind Harmer
0.057
3147243WELCO
Solar/Wind Harmer
0.036
3141426STAFORD
Solar/Wind Helper
0.036
315051AA1-145 CT1
50/50
2.918
971645AH1-323 GEN
50/50
16.828
316473AC1-191 GEN
Solar/Wind Harmer
0.547
3142416OLDCHRC
Solar/Wind Harmer
1.565
970293AG2-193 GEN
Solar/Wind Harmer
1.528
3143096IRON208
Adder
0.565
3143096IRON208
Adder
0.554
3150861SPRUNCD
Adder
0.59
3142946ENON
Solar/Wind Harmer
0.043
970133AG2-095 GEN
Solar/Wind Harmer
1.165
970129AG2-093 GEN
Solar/Wind Harmer
7.076
965281AG1-393 GEN
Solar/Wind Harmer
1.247
315839AE2-212 C
Solar/Wind Harmer
0.001
3142433PROV 92
Adder
0.224
3142433PROV 92
Adder
0.224
315778AD1-151 GEN
Solar/Wind Harmer
9.121
316382AG1-145 C
Solar/Wind Harmer
0.001
961611AG1-000B GEN
Solar/Wind Harmer
2.869
315813AE1-149 C
Solar/Wind Harmer
5.675
3151221GRAVEL6
Adder
7.614
3151171GRAVELC
Adder
1.465
3141766HARMONY
Solar/Wind Harmer
1.389
3141843SHACKLE
Adder
0.532
316203AE2-005 GEN
Solar/Wind Harmer
0
3144216WINCHST
Adder
0.39
3150921YORKTN3
Adder
2.595
970659AG2-427 GEN
Solar/Wind Harmer
1.091
316083AB2-161 GEN
Solar/Wind Harmer
0.001
316280AD1-041 GEN
Solar/Wind Harmer
0.002
971781AH1-399 GEN
Solar/Wind Harmer
0.134
970661AG2-428 GEN
Solar/Wind Harmer
2.133
3145336SMITFLD
Solar/Wind Harmer
0.04
316156AD2-030 GEN
Solar/Wind Harmer
0.074
3141873WAN 176
Solar/Wind Harmer
1.782
3144536CHRHLND
Solar/Wind Harmer
0.014
3144873MCLAUGH
Solar/Wind Harmer
0.002
3151101ELIZAR3
Adder
8.719
315773AC2-141 GEN
Solar/Wind Harmer
3.396
944581AF1-123 GEN
Solar/Wind Harmer
20.859
944601AF1-125 GEN
Solar/Wind Harmer
20.537
3146456SLIGO L269
Solar/Wind Harmer
0.092
971153AH1-033 GEN
Solar/Wind Harmer
1.063
316320Y1-086
Solar/Wind Harmer
0
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.089
3145273HOLLAND
Solar/Wind Harmer
0.067
3146626S HERTFORD
Solar/Wind Harmer
0.089
962971AG1-146 GEN
Solar/Wind Harmer
1.407
3146376EDENTON
Solar/Wind Harmer
0.086
970009AG2-005 GEN
Solar/Wind Harmer
0.636
315614AA2-178 GEN
Solar/Wind Harmer
0.482
971157AH1-035 GEN
Solar/Wind Harmer
0.988
315737AD1-076 GEN
Solar/Wind Harmer
1.055
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3146206CASHIE
Solar/Wind Harmer
0.081
972255AH1-712 GEN
Adder
41.371
316404AE1-155 C
Solar/Wind Harmer
0.018
3145893MURPHYS
Solar/Wind Harmer
0.134
3145893MURPHYS
Solar/Wind Harmer
0.08
957521AF2-046 GEN
Solar/Wind Harmer
5.958
961681AG1-008 GEN
Solar/Wind Harmer
5.958
316365GEN2_N
Solar/Wind Harmer
0.179
316313AB2-026
Solar/Wind Harmer
0.05
316258AE1-075 C
Solar/Wind Harmer
0.06
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
1.205
3146173TUNIS
Solar/Wind Harmer
0.079
3156021HOLLOMANSOL
Solar/Wind Harmer
0.36
316463AE2-346 GEN
Solar/Wind Harmer
0.068
316140AB2-099
Solar/Wind Harmer
0.028
962331AG1-082 GEN
Solar/Wind Harmer
0.841
3146263WOODLND
Solar/Wind Harmer
0.077
3145963POPLR C
Solar/Wind Harmer
0.077
3142666NORTHAMPTON
Solar/Wind Harmer
0.076
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.076
313506AB2-031 GEN
Solar/Wind Harmer
0.234
3145796HORNRTN
Solar/Wind Harmer
0.299
3145796HORNRTN
Solar/Wind Harmer
0.075
3145933PARMELE
Solar/Wind Harmer
0.073
966801AG1-551 GEN
Solar/Wind Harmer
0.851
3147043LAWRENC
Solar/Wind Harmer
0.044
316210AC1-098 GEN
Solar/Wind Harmer
0.674
3150351NORNECKC2
Adder
0.735
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
315724AD1-057 GEN
Solar/Wind Harmer
0.263
316327AA2-057 GEN
Solar/Wind Harmer
0.105
970917AG2-570 GEN
Solar/Wind Harmer
6.089
3146073TAR RVR
Solar/Wind Harmer
0.068
3146083TARBORO
Solar/Wind Harmer
0.068
3146233WITAKRS
Solar/Wind Harmer
0.341
3146233WITAKRS
Solar/Wind Harmer
0.046
3138543CONSLDL
Solar/Wind Harmer
0.045
961601AG1-000A GEN
Solar/Wind Harmer
4.729
3145543BTLEBRO
Solar/Wind Harmer
0.066
3145543BTLEBRO
Solar/Wind Harmer
0.066
971623AH1-311 GEN
Solar/Wind Harmer
0.133
316478AD1-087 GEN
Solar/Wind Harmer
0.225
316486AD2-202 GEN
Solar/Wind Harmer
0.066
316131AB2-060 GEN
Solar/Wind Harmer
0.2
964241AG1-285 GEN
Solar/Wind Harmer
4.22
315785AD2-033 C
Solar/Wind Harmer
0.511
970257AG2-171 GEN
Solar/Wind Harmer
2.007
959311AF2-222 GEN
Solar/Wind Harmer
5.564
970909AG2-566 GEN
Solar/Wind Harmer
0.665
963181AG1-167 GEN
Solar/Wind Harmer
0.248
3144293JTRSVLE
Adder
0.197
3147133PAMPLIN
Solar/Wind Harmer
0.193
971193AH1-056 GEN
Solar/Wind Harmer
3.754
942461AE2-259 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.036
3146776BUCKING
Solar/Wind Harmer
0.021
316248AF1-058 C
Solar/Wind Harmer
0
960061AF2-297 GEN
Solar/Wind Harmer
2.45
315052AA1-145 CT2
50/50
2.93
966881AG1-559 GEN
Solar/Wind Harmer
0.767
3142416OLDCHRC
Solar/Wind Harmer
0.42
3142416OLDCHRC
Solar/Wind Harmer
0.161
3143096IRON208
Adder
0.565
3142543TWELFTH
Solar/Wind Harmer
0.013
944631AF1-128 GEN
Adder
61.065
3150851SPRUNCC
Adder
0.59
315671AE2-027_GEN
Solar/Wind Harmer
7.592
970129AG2-093 GEN
Solar/Wind Harmer
3.33
316458AB2-190 GEN2
Solar/Wind Harmer
0.626
3142433PROV 92
Solar/Wind Harmer
0.461
3142433PROV 92
Adder
0.224
3142433PROV 92
Adder
0.224
971069AG2-661 GEN
Solar/Wind Harmer
2.027
3143526WINTERP
Solar/Wind Harmer
0.585
316159AE1-175 C
Solar/Wind Harmer
0.096
971647AH1-324 GEN
Solar/Wind Harmer
4.69
961611AG1-000B GEN
Solar/Wind Harmer
5.643
3151171GRAVELC
Adder
1.114
971317AH1-138 GEN
Solar/Wind Harmer
0.779
3141766HARMONY
Solar/Wind Harmer
0.021
971777AH1-397 GEN
Solar/Wind Harmer
0.275
3141843SHACKLE
Adder
0.532
3138126ROCKLANDING
Solar/Wind Harmer
0.047
970659AG2-427 GEN
Solar/Wind Harmer
4.989
316381AD1-082 GEN
Solar/Wind Harmer
0.107
970661AG2-428 GEN
Solar/Wind Harmer
10.027
3145336SMITFLD
Solar/Wind Harmer
0.402
3143226MDLTHAN
Solar/Wind Harmer
0.096
316072AD1-144
Solar/Wind Harmer
0.034
3138133OCRAN
Solar/Wind Harmer
0.057
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
1.175
316294AC1-161 GEN
Solar/Wind Harmer
1.611
316093AE2-104_GEN
Solar/Wind Harmer
1.559
944591AF1-124 GEN
Solar/Wind Harmer
20.933
316388AE2-253 GEN
Solar/Wind Harmer
0.289
316246AF1-032 C
Solar/Wind Harmer
0.042
3146456SLIGO L269
Solar/Wind Harmer
0.092
3146516WINFALL
Solar/Wind Harmer
0.29
3146516WINFALL
Solar/Wind Harmer
0.089
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.086
3145663CRESWEL
Solar/Wind Harmer
0.235
971163AH1-040 GEN
Solar/Wind Harmer
6.732
962861AG1-135 GEN
Solar/Wind Harmer
2.618
939411AE1-173 GEN
Solar/Wind Harmer
34.828
3146206CASHIE
Solar/Wind Harmer
0.081
971547AH1-271 GEN
Solar/Wind Harmer
1.726
972277AH1-723 GEN
Adder
48.21
3145893MURPHYS
Solar/Wind Harmer
0.321
3145893MURPHYS
Solar/Wind Harmer
0.357
316023GEN1_S
Solar/Wind Harmer
0.179
3143336POWHATN
Solar/Wind Harmer
1.418
3146173TUNIS
Solar/Wind Harmer
0.079
3145683EARLEYS
Solar/Wind Harmer
0.078
940641AE2-051 GEN
Solar/Wind Harmer
6.235
3146263WOODLND
Solar/Wind Harmer
0.077
3141726DUNNSVL
Solar/Wind Harmer
0.309
3145963POPLR C
Solar/Wind Harmer
0.077
960081AF2-299 GEN
Solar/Wind Harmer
0.737
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3145823KELFORD
Solar/Wind Harmer
0.076
316011AB1-132 GEN
Solar/Wind Harmer
1.384
962571AG1-106 GEN
Solar/Wind Harmer
1.083
316336AC2-165 C
Solar/Wind Harmer
0.003
316190AA2-174 GEN
Solar/Wind Harmer
0
3145796HORNRTN
Solar/Wind Harmer
0.247
3145796HORNRTN
Solar/Wind Harmer
0.075
3145783HORNRTN
Solar/Wind Harmer
0.074
971795AH1-408 GEN
Solar/Wind Harmer
4.936
3146293MARTNCO
Solar/Wind Harmer
0.068
3147043LAWRENC
Adder
0.658
316212AC1-099_GEN
Solar/Wind Harmer
0.376
3150351NORNECKC2
Adder
0.723
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
315722AD1-056 GEN
Solar/Wind Harmer
0.444
316494AC1-189 GEN
Solar/Wind Harmer
0.235
970919AG2-571 GEN
Solar/Wind Harmer
2.436
970087AG2-069 GEN
Solar/Wind Harmer
5.462
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.068
3145493TOT1
Solar/Wind Harmer
0.303
316129AC1-054 GEN
Solar/Wind Harmer
0.256
3146233WITAKRS
Solar/Wind Harmer
0.27
971065AG2-659 GEN
Solar/Wind Harmer
2.88
316359AB2-059 GEN
Solar/Wind Harmer
0.239
316049AB1-081 GEN
Solar/Wind Harmer
0.38
3145543BTLEBRO
Solar/Wind Harmer
0.066
3145543BTLEBRO
Solar/Wind Harmer
0.053
3142053HEARTS
Solar/Wind Harmer
0.117
957481AF2-042 GEN
Solar/Wind Harmer
17.703
315693AD1-088 GEN
Solar/Wind Harmer
3.143
962491AG1-098 GEN
Solar/Wind Harmer
3.727
970937AG2-583 GEN
Solar/Wind Harmer
3.946
316237AB2-079_GEN
Solar/Wind Harmer
0.001
970685AG2-442 GEN
Solar/Wind Harmer
4.652
963171AG1-166 GEN
Solar/Wind Harmer
0.33
971563AH1-280 GEN
Solar/Wind Harmer
0.661
3144293JTRSVLE
Adder
0.197
315687AD1-152 GEN
Solar/Wind Harmer
0.002
3146926FARMVIL
Solar/Wind Harmer
0.036
970401AG2-262 GEN
Solar/Wind Harmer
0.352
316337AD2-073 GEN
Solar/Wind Harmer
0.051
316322AB2-045
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
0.023
NYPJM->LTFIMP_NY
CLTF
1.306
LGEELTFEXP_LGEE->PJM
CLTF
0.633
WECLTFEXP_WEC->PJM
CLTF
0.314
LAGNLTFEXP_LAGN->PJM
CLTF
3.259
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.253
TVALTFEXP_TVA->PJM
CLTF
1.654
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.836
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.715
MECLTFEXP_MEC->PJM
CLTF
1.658
SIGELTFEXP_SIGE->PJM
CLTF
0.051
CPLELTFEXP_CPLE->PJM
CLTF
4.134
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.574

Details for 6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.92 %
Rating:1809.0 MVA
Rating Type:C
MVA to Mitigate:2115.16
MW Contribution:43.25
Bus #Bus NameTypeMW Contribution
972189AH1-679 GEN
50/50
6.745
316312AB1-027
Solar/Wind Harmer
0.646
971285AH1-108 GEN
Adder
1.02
315976AC1-164 GENA
Solar/Wind Harmer
15.264
316169AC1-164_GENC
Solar/Wind Harmer
13.187
315975AC1-164 GENB
Solar/Wind Harmer
0.452
971167AH1-042 GEN
Solar/Wind Harmer
13.036
316132AB2-190 GEN1
Solar/Wind Harmer
1.368
316233AE1-074 FULL
Solar/Wind Harmer
0.36
971281AH1-106 GEN
Solar/Wind Harmer
2.178
971283AH1-107 GEN
Solar/Wind Harmer
2.178
3142433PROV 92
Adder
0.231
3142433PROV 92
Adder
0.231
316369SG1_INVT
Solar/Wind Harmer
2.313
3143873LANEXA
Solar/Wind Harmer
-0.007
316314AB2-024 C
Solar/Wind Harmer
1.044
3143316POE
Solar/Wind Harmer
-0.048
972265AH1-717 GEN
Adder
8.267
3151201GRAVEL4
Adder
7.75
3151191GRAVEL3
Adder
7.652
3151211GRAVEL5
Adder
7.652
316059AD1-063 C
Solar/Wind Harmer
0.27
315662AE1-191 GEN
Solar/Wind Harmer
1.416
315666AE1-190 GEN
Solar/Wind Harmer
0.354
957831AF2-077 GEN
Solar/Wind Harmer
0.348
3138283WHITEMARSH
Solar/Wind Harmer
0.018
971445AH1-216 GEN
Solar/Wind Harmer
7.11
957601AF2-054 GEN
Solar/Wind Harmer
0.343
3141873WAN 176
Solar/Wind Harmer
-0.002
3141913WHIT STONE
Solar/Wind Harmer
-0.011
315833AF1-017_GEN
Solar/Wind Harmer
2.09
316349AD2-085 GEN
Solar/Wind Harmer
0.979
316311AC2-079 GEN
Solar/Wind Harmer
5.546
3138133OCRAN
Solar/Wind Harmer
-0.003
3141783LANCAST
Solar/Wind Harmer
-0.006
3141783LANCAST
Solar/Wind Harmer
-0.004
3152611GOSPORTB
Adder
1.202
3152621GOSPORTC
Adder
1.02
3152601GOSPORTA
Adder
0.941
3151081ELIZAR1
Adder
8.634
3151091ELIZAR2
Adder
8.484
315835AF2-110_GEN
Solar/Wind Harmer
1.312
316305AF2-043 C
Solar/Wind Harmer
0.314
957871AF2-081 GEN
Solar/Wind Harmer
5.192
319010AE1-072 C
Solar/Wind Harmer
2.094
3146406KITTY HAWK
Solar/Wind Harmer
0.009
313526AB2-022
Solar/Wind Harmer
0.276
3146486SUNBURY
Solar/Wind Harmer
-0.01
3146486SUNBURY
Solar/Wind Harmer
-0.01
316321Z2-027
Solar/Wind Harmer
0.275
3145176PASQUOTANK
Solar/Wind Harmer
-0.006
3146396TANGLEW
Solar/Wind Harmer
0.188
316315AB2-025 C
Solar/Wind Harmer
0.273
962981AG1-147 GEN
Solar/Wind Harmer
4.42
315814AE2-033 C
Solar/Wind Harmer
9.389
315611Z1-036_GEN2
Solar/Wind Harmer
2.45
3130156CHOWAN
Solar/Wind Harmer
-0.01
3130156CHOWAN
Solar/Wind Harmer
-0.01
315816AE2-034 GEN
Solar/Wind Harmer
0.769
3130546PLYMOUTH
Solar/Wind Harmer
-0.009
315732AD1-074 GEN1
Solar/Wind Harmer
1.875
315733AD1-074 GEN2
Solar/Wind Harmer
1.875
315735AD1-075 GEN1
Solar/Wind Harmer
0.938
965291AG1-394 GEN
Solar/Wind Harmer
0.819
3146206CASHIE
Solar/Wind Harmer
-0.009
970601AG2-382 GEN
Solar/Wind Harmer
4.006
316318V4-068
Solar/Wind Harmer
0.227
3145893MURPHYS
Solar/Wind Harmer
-0.024
3145893MURPHYS
Solar/Wind Harmer
-0.009
3145513AHOSKIE
Solar/Wind Harmer
0.078
961941AG1-037 GEN
Solar/Wind Harmer
0.067
3145513AHOSKIE
Solar/Wind Harmer
-0.009
3145683EARLEYS
Solar/Wind Harmer
-0.018
3145683EARLEYS
Solar/Wind Harmer
-0.009
3145683EARLEYS
Solar/Wind Harmer
-0.009
3146043SEABORD
Solar/Wind Harmer
-0.009
315607AA1-063A GEN
Solar/Wind Harmer
0.888
946281AF1-292 GEN
Solar/Wind Harmer
0.197
316087AB2-174 GEN
Solar/Wind Harmer
1.239
315652AC1-086 GEN
Solar/Wind Harmer
9.768
3137643SOCKMAN
Solar/Wind Harmer
-0.034
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.034
3141813NORNECK
Solar/Wind Harmer
-0.008
941031AE2-094 GEN
Solar/Wind Harmer
15.534
944011AF1-069 GEN
Solar/Wind Harmer
4.867
970673AG2-436 GEN
Solar/Wind Harmer
17.166
970673AG2-436 GEN
Solar/Wind Harmer
8.692
972193AH1-681 GEN
Adder
1.658
971967AH1-528 GEN
Solar/Wind Harmer
15.218
316005AA1-067
Solar/Wind Harmer
0.163
3145746EVERETS
Solar/Wind Harmer
-0.032
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
970181AG2-120 GEN
Solar/Wind Harmer
1.057
957861AF2-080 GEN
Solar/Wind Harmer
3.447
970831AG2-522 GEN
Solar/Wind Harmer
3.906
316420AA1-050 GEN
Solar/Wind Harmer
0.89
970085AG2-068 GEN
Solar/Wind Harmer
4.862
970581AG2-369 GEN
Solar/Wind Harmer
4.181
3145573BETHELC
Solar/Wind Harmer
-0.008
3145573BETHELC
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.426
3141426STAFORD
Solar/Wind Helper
0.035
315052AA1-145 CT2
50/50
3.022
966881AG1-559 GEN
Solar/Wind Harmer
0.775
3142416OLDCHRC
Solar/Wind Harmer
-0.05
3142416OLDCHRC
Solar/Wind Harmer
-0.019
3143096IRON208
Adder
0.592
3142543TWELFTH
Solar/Wind Harmer
-0.002
3150851SPRUNCC
Adder
0.623
944631AF1-128 GEN
Adder
63.31
315671AE2-027_GEN
Solar/Wind Harmer
10.43
970129AG2-093 GEN
Solar/Wind Harmer
3.098
316458AB2-190 GEN2
Solar/Wind Harmer
1.368
3143526WINTERP
Solar/Wind Harmer
-0.069
3142433PROV 92
Solar/Wind Harmer
-0.053
3142433PROV 92
Adder
0.231
3142433PROV 92
Adder
0.231
971069AG2-661 GEN
Solar/Wind Harmer
2.086
971647AH1-324 GEN
Solar/Wind Harmer
6.322
316159AE1-175 C
Solar/Wind Harmer
0.337
961611AG1-000B GEN
Solar/Wind Harmer
6.091
3151171GRAVELC
Adder
1.133
971777AH1-397 GEN
Solar/Wind Harmer
1.405
3141843SHACKLE
Adder
0.543
3141766HARMONY
Solar/Wind Harmer
-0.002
970659AG2-427 GEN
Solar/Wind Harmer
6.325
316381AD1-082 GEN
Solar/Wind Harmer
1.084
971317AH1-138 GEN
Solar/Wind Harmer
1.473
3138126ROCKLANDING
Solar/Wind Harmer
0.036
970661AG2-428 GEN
Solar/Wind Harmer
12.312
3143226MDLTHAN
Solar/Wind Harmer
-0.011
3145336SMITFLD
Solar/Wind Harmer
-0.046
3138133OCRAN
Solar/Wind Harmer
-0.006
316072AD1-144
Solar/Wind Harmer
0.217
316375AC2-012 GEN
Solar/Wind Harmer
3.67
3150981CHESPKA
Adder
1.178
316093AE2-104_GEN
Solar/Wind Harmer
3.051
944591AF1-124 GEN
Solar/Wind Harmer
47.558
316246AF1-032 C
Solar/Wind Harmer
0.211
316388AE2-253 GEN
Solar/Wind Harmer
0.701
316294AC1-161 GEN
Solar/Wind Harmer
3.361
3146456SLIGO L269
Solar/Wind Harmer
-0.01
3146516WINFALL
Solar/Wind Harmer
-0.033
3146516WINFALL
Solar/Wind Harmer
-0.01
315800Z1-036_GEN1
Solar/Wind Harmer
2.45
961951AG1-038 GEN
Solar/Wind Harmer
1.29
3130156CHOWAN
Solar/Wind Harmer
-0.01
3145663CRESWEL
Solar/Wind Harmer
-0.026
971163AH1-040 GEN
Solar/Wind Harmer
8.915
962861AG1-135 GEN
Solar/Wind Harmer
3.534
3143336POWHATN
Solar/Wind Harmer
1.113
939411AE1-173 GEN
Solar/Wind Harmer
46.267
316023GEN1_S
Solar/Wind Harmer
0.618
3146206CASHIE
Solar/Wind Harmer
-0.009
971547AH1-271 GEN
Solar/Wind Harmer
2.289
3145893MURPHYS
Solar/Wind Harmer
-0.036
3145893MURPHYS
Solar/Wind Harmer
0.27
3146173TUNIS
Solar/Wind Harmer
-0.009
964211AG1-282 GEN
Solar/Wind Harmer
0.269
3141726DUNNSVL
Solar/Wind Harmer
-0.036
3145683EARLEYS
Solar/Wind Harmer
-0.009
940641AE2-051 GEN
Solar/Wind Harmer
8.306
316336AC2-165 C
Solar/Wind Harmer
1.534
3146263WOODLND
Solar/Wind Harmer
-0.009
960081AF2-299 GEN
Solar/Wind Harmer
0.987
3145963POPLR C
Solar/Wind Harmer
-0.009
316011AB1-132 GEN
Solar/Wind Harmer
1.817
962571AG1-106 GEN
Solar/Wind Harmer
1.248
3145823KELFORD
Solar/Wind Harmer
-0.009
316174AB2-169 GEN
Solar/Wind Harmer
1.333
316190AA2-174 GEN
Solar/Wind Harmer
0.105
3145796HORNRTN
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.008
971795AH1-408 GEN
Solar/Wind Harmer
6.339
3145783HORNRTN
Solar/Wind Harmer
-0.008
3150351NORNECKC2
Adder
0.745
3147043LAWRENC
Adder
0.669
3146293MARTNCO
Solar/Wind Harmer
0.051
316212AC1-099_GEN
Solar/Wind Harmer
0.719
972277AH1-723 GEN
Adder
43.254
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
315722AD1-056 GEN
Solar/Wind Harmer
0.834
316494AC1-189 GEN
Solar/Wind Harmer
0.848
970919AG2-571 GEN
Solar/Wind Harmer
2.47
970087AG2-069 GEN
Solar/Wind Harmer
7.293
316129AC1-054 GEN
Solar/Wind Harmer
0.678
961671AG1-007 GEN
Solar/Wind Harmer
0.098
3146083TARBORO
Solar/Wind Harmer
-0.008
3145493TOT1
Solar/Wind Harmer
0.229
3146233WITAKRS
Solar/Wind Harmer
-0.03
971065AG2-659 GEN
Solar/Wind Harmer
3.835
3144293JTRSVLE
Adder
0.199
957481AF2-042 GEN
Solar/Wind Harmer
23.61
3142296MT RD221
50/50
0.652
3142366NRTHEST
50/50
0.558
3150691DARBY 3
50/50
11.988
3150701DARBY 4
50/50
11.96
3150681DARBY 2
50/50
11.946
957411AF2-035 GEN
Solar/Wind Harmer
33.919
970317AG2-208 GEN
Solar/Wind Harmer
32.977
966871AG1-558 GEN
Solar/Wind Harmer
0.588
966871AG1-558 GEN
Solar/Wind Harmer
0.201
3150671DARBY 1
Adder
11.244
316075AC2-137 C
Solar/Wind Harmer
0.43
944641AF1-129 GEN
Adder
62.735
3142946ENON
Solar/Wind Harmer
-0.002
316240AF1-291 C
Solar/Wind Harmer
0.437
3143526WINTERP
Solar/Wind Harmer
-0.069
316033AB2-134 GEN
Solar/Wind Harmer
4.174
315697AD1-025 GEN
Solar/Wind Harmer
2.618
316468AD1-105 GEN
Solar/Wind Harmer
1.403
316441AF1-014 GEN
Solar/Wind Harmer
0.805
970657AG2-426 GEN
Solar/Wind Harmer
3.667
970657AG2-426 GEN
Solar/Wind Harmer
0.767
971223AH1-071 GEN
Solar/Wind Harmer
1.433
316236AE1-162_GEN
Solar/Wind Harmer
0.345
316036AC1-147 C
Solar/Wind Harmer
0.286
3150991CHESPKB
Adder
0.989
3150991CHESPKB
Adder
0.965
316316AC1-027 C
Solar/Wind Harmer
0.323
3142956BIRDNECK
Solar/Wind Harmer
0.565
316185AD1-033 GEN
Solar/Wind Harmer
1.104
3145506HICKORY
Solar/Wind Harmer
-0.042
3145506HICKORY
Solar/Wind Harmer
-0.025
3145506HICKORY
Solar/Wind Harmer
-0.006
316339AD2-160 GEN
Solar/Wind Harmer
0.701
316018AA1-139 ULT2
Solar/Wind Harmer
0.89
316017AA1-139 ULT1
Solar/Wind Harmer
0.84
3137176SLIGO L2192
Solar/Wind Harmer
-0.041
3146456SLIGO L269
Solar/Wind Harmer
1.224
3130086AYDLETT
Solar/Wind Harmer
-0.041
3146386ELIZ CT
Solar/Wind Harmer
-0.01
316431W1029_GEN1
Solar/Wind Harmer
1.837
316433W1029_GEN2
Solar/Wind Harmer
1.837
3144356SAPONY
Solar/Wind Harmer
0.353
3146516WINFALL
Solar/Wind Harmer
-0.01
3146516WINFALL
Solar/Wind Harmer
-0.01
3146516WINFALL
Solar/Wind Harmer
-0.01
3146626S HERTFORD
Solar/Wind Harmer
-0.01
3146626S HERTFORD
Solar/Wind Harmer
-0.01
315742AE1-103 GEN
Solar/Wind Harmer
1.039
316487AF1-042 GEN
Solar/Wind Harmer
1.29
3146376EDENTON
Solar/Wind Harmer
0.29
3146376EDENTON
Solar/Wind Harmer
0.29
958261AF2-120 GEN
Solar/Wind Harmer
3.6
316065AD1-022 GEN
Solar/Wind Harmer
4.599
3145893MURPHYS
Solar/Wind Harmer
0.254
3145893MURPHYS
Solar/Wind Harmer
-0.016
3146173TUNIS
Solar/Wind Harmer
-0.009
3146173TUNIS
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
316181AB2-040 GEN
Solar/Wind Harmer
1.206
316426AA2-053 GEN
Solar/Wind Harmer
0.866
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.957
3145593CAROLNA
Solar/Wind Harmer
0.071
3145783HORNRTN
Solar/Wind Harmer
1.003
3145783HORNRTN
Solar/Wind Harmer
0.802
3145783HORNRTN
Solar/Wind Harmer
0.251
3145783HORNRTN
Solar/Wind Harmer
0.1
316077AC2-138 C
Solar/Wind Harmer
0.177
3150341NORNECKC1
Adder
0.782
3150341NORNECKC1
Adder
0.776
3145933PARMELE
Solar/Wind Harmer
-0.016
3145933PARMELE
Solar/Wind Harmer
-0.008
316274AC1-208 GEN
Solar/Wind Harmer
0.88
972185AH1-677 GEN
Adder
4.053
972187AH1-678 GEN
Adder
2.037
970933AG2-581 GEN
Solar/Wind Harmer
7.449
3145493TOT1
Solar/Wind Harmer
0.12
3145453TOT5
Solar/Wind Harmer
0.072
3145603CNETO
Solar/Wind Harmer
0.048
3144293JTRSVLE
Adder
0.199
3144293JTRSVLE
Adder
0.168
970099AG2-077 GEN
Solar/Wind Harmer
9.444
315051AA1-145 CT1
50/50
3.009
971645AH1-323 GEN
50/50
18.069
966881AG1-559 GEN
Solar/Wind Harmer
2.266
316473AC1-191 GEN
Solar/Wind Harmer
2.105
3142416OLDCHRC
Solar/Wind Harmer
1.933
970293AG2-193 GEN
Solar/Wind Harmer
2.103
3143096IRON208
Adder
0.592
3143096IRON208
Adder
0.58
3150861SPRUNCD
Adder
0.623
3142946ENON
Solar/Wind Harmer
-0.005
970133AG2-095 GEN
Solar/Wind Harmer
1.592
965281AG1-393 GEN
Solar/Wind Harmer
1.712
315839AE2-212 C
Solar/Wind Harmer
0.411
970129AG2-093 GEN
Solar/Wind Harmer
7.649
3142433PROV 92
Adder
0.231
3142433PROV 92
Adder
0.231
315778AD1-151 GEN
Solar/Wind Harmer
11.42
971781AH1-399 GEN
Solar/Wind Harmer
0.776
316382AG1-145 C
Solar/Wind Harmer
0.379
315813AE1-149 C
Solar/Wind Harmer
7.713
961611AG1-000B GEN
Solar/Wind Harmer
2.599
3151221GRAVEL6
Adder
7.741
3151171GRAVELC
Adder
1.489
3141843SHACKLE
Adder
0.543
316203AE2-005 GEN
Solar/Wind Harmer
5.036
3141766HARMONY
Solar/Wind Harmer
1.062
970659AG2-427 GEN
Solar/Wind Harmer
1.121
316083AB2-161 GEN
Solar/Wind Harmer
1.919
316280AD1-041 GEN
Solar/Wind Harmer
0.885
3144216WINCHST
Adder
0.393
3150921YORKTN3
Adder
2.606
970661AG2-428 GEN
Solar/Wind Harmer
2.182
316156AD2-030 GEN
Solar/Wind Harmer
0.306
3141873WAN 176
Solar/Wind Harmer
1.362
3145336SMITFLD
Solar/Wind Harmer
-0.005
3144536CHRHLND
Solar/Wind Harmer
-0.002
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
8.744
944581AF1-123 GEN
Solar/Wind Harmer
47.387
944601AF1-125 GEN
Solar/Wind Harmer
46.647
315773AC2-141 GEN
Solar/Wind Harmer
4.348
3146456SLIGO L269
Solar/Wind Harmer
-0.01
971153AH1-033 GEN
Solar/Wind Harmer
1.263
316320Y1-086
Solar/Wind Harmer
0.6
316435W1029_GEN3
Solar/Wind Harmer
1.837
3145273HOLLAND
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.01
962971AG1-146 GEN
Solar/Wind Harmer
1.894
3146626S HERTFORD
Solar/Wind Harmer
-0.01
316484AD2-074 GEN
Solar/Wind Harmer
2.465
970009AG2-005 GEN
Solar/Wind Harmer
1.224
3146376EDENTON
Solar/Wind Harmer
-0.01
315614AA2-178 GEN
Solar/Wind Harmer
1.026
316313AB2-026
Solar/Wind Harmer
0.253
316258AE1-075 C
Solar/Wind Harmer
0.228
316405AF2-144 C
Solar/Wind Harmer
0.24
3143336POWHATN
Solar/Wind Harmer
0.946
971157AH1-035 GEN
Solar/Wind Harmer
1.164
316404AE1-155 C
Solar/Wind Harmer
1.792
3156081AA2-088 GEN
Solar/Wind Harmer
3.013
315737AD1-076 GEN
Solar/Wind Harmer
1.762
316365GEN2_N
Solar/Wind Harmer
0.618
3146206CASHIE
Solar/Wind Harmer
-0.009
3145893MURPHYS
Solar/Wind Harmer
0.064
3145893MURPHYS
Solar/Wind Harmer
-0.009
957521AF2-046 GEN
Solar/Wind Harmer
7.153
961681AG1-008 GEN
Solar/Wind Harmer
7.153
3146173TUNIS
Solar/Wind Harmer
-0.009
3156021HOLLOMANSOL
Solar/Wind Harmer
1.211
316463AE2-346 GEN
Solar/Wind Harmer
0.145
316140AB2-099
Solar/Wind Harmer
0.06
962331AG1-082 GEN
Solar/Wind Harmer
1.118
3146263WOODLND
Solar/Wind Harmer
-0.009
966621AG1-532 GEN
Solar/Wind Harmer
0.178
3145963POPLR C
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
316317KELFORD C
Solar/Wind Harmer
0.408
3145823KELFORD
Solar/Wind Harmer
-0.009
313506AB2-031 GEN
Solar/Wind Harmer
0.695
3145796HORNRTN
Solar/Wind Harmer
-0.034
3145796HORNRTN
Solar/Wind Harmer
-0.008
3150351NORNECKC2
Adder
0.757
3147043LAWRENC
Solar/Wind Harmer
-0.005
3145933PARMELE
Solar/Wind Harmer
-0.008
966801AG1-551 GEN
Solar/Wind Harmer
1.034
316210AC1-098 GEN
Solar/Wind Harmer
1.294
972255AH1-712 GEN
Adder
37.118
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
315724AD1-057 GEN
Solar/Wind Harmer
0.459
316327AA2-057 GEN
Solar/Wind Harmer
0.796
970917AG2-570 GEN
Solar/Wind Harmer
19.512
3146073TAR RVR
Solar/Wind Harmer
-0.008
3146083TARBORO
Solar/Wind Harmer
-0.008
3146233WITAKRS
Solar/Wind Harmer
0.161
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3144293JTRSVLE
Adder
0.199
NYPJM->LTFIMP_NY
CLTF
1.288
LGEELTFEXP_LGEE->PJM
CLTF
0.601
WECLTFEXP_WEC->PJM
CLTF
0.297
LAGNLTFEXP_LAGN->PJM
CLTF
3.178
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.209
TVALTFEXP_TVA->PJM
CLTF
1.611
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.206
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.551
MECLTFEXP_MEC->PJM
CLTF
1.584
SIGELTFEXP_SIGE->PJM
CLTF
0.049
CPLELTFEXP_CPLE->PJM
CLTF
4.142
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.001

Details for 6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 557T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.03 %
Rating:1809.0 MVA
Rating Type:C
MVA to Mitigate:2098.92
MW Contribution:53.78
Bus #Bus NameTypeMW Contribution
972189AH1-679 GEN
50/50
6.597
316312AB1-027
Solar/Wind Harmer
0.605
971285AH1-108 GEN
Adder
0.951
315976AC1-164 GENA
Solar/Wind Harmer
13.809
316169AC1-164_GENC
Solar/Wind Harmer
11.929
315975AC1-164 GENB
Solar/Wind Harmer
0.409
316233AE1-074 FULL
Solar/Wind Harmer
0.336
971281AH1-106 GEN
Solar/Wind Harmer
2.031
971283AH1-107 GEN
Solar/Wind Harmer
2.031
316132AB2-190 GEN1
Solar/Wind Harmer
1.251
971167AH1-042 GEN
Solar/Wind Harmer
11.862
3142433PROV 92
Adder
0.21
3142433PROV 92
Adder
0.21
316369SG1_INVT
Solar/Wind Harmer
2.104
3143873LANEXA
Solar/Wind Harmer
-0.007
3143316POE
Solar/Wind Harmer
-0.044
316314AB2-024 C
Solar/Wind Harmer
0.933
972265AH1-717 GEN
Adder
7.449
3151201GRAVEL4
Adder
6.983
3151191GRAVEL3
Adder
6.894
3151211GRAVEL5
Adder
6.894
316059AD1-063 C
Solar/Wind Harmer
0.241
315662AE1-191 GEN
Solar/Wind Harmer
1.264
315666AE1-190 GEN
Solar/Wind Harmer
0.316
971445AH1-216 GEN
Solar/Wind Harmer
6.379
957831AF2-077 GEN
Solar/Wind Harmer
0.309
3138283WHITEMARSH
Solar/Wind Harmer
0.016
957601AF2-054 GEN
Solar/Wind Harmer
0.306
3141873WAN 176
Solar/Wind Harmer
-0.002
972193AH1-681 GEN
Adder
2.062
315833AF1-017_GEN
Solar/Wind Harmer
1.881
316349AD2-085 GEN
Solar/Wind Harmer
0.881
316311AC2-079 GEN
Solar/Wind Harmer
4.991
3141913WHIT STONE
Solar/Wind Harmer
-0.01
3138133OCRAN
Solar/Wind Harmer
-0.003
3152611GOSPORTB
Adder
1.069
3152621GOSPORTC
Adder
0.907
3152601GOSPORTA
Adder
0.837
3141783LANCAST
Solar/Wind Harmer
-0.006
3141783LANCAST
Solar/Wind Harmer
-0.004
3151081ELIZAR1
Adder
7.676
3151091ELIZAR2
Adder
7.542
315835AF2-110_GEN
Solar/Wind Harmer
1.172
316305AF2-043 C
Solar/Wind Harmer
0.279
957871AF2-081 GEN
Solar/Wind Harmer
4.617
316315AB2-025 C
Solar/Wind Harmer
0.249
319010AE1-072 C
Solar/Wind Harmer
1.863
3146406KITTY HAWK
Solar/Wind Harmer
0.008
315814AE2-033 C
Solar/Wind Harmer
8.538
3146486SUNBURY
Solar/Wind Harmer
-0.009
3146486SUNBURY
Solar/Wind Harmer
-0.009
313526AB2-022
Solar/Wind Harmer
0.246
316321Z2-027
Solar/Wind Harmer
0.245
3146396TANGLEW
Solar/Wind Harmer
0.167
3145176PASQUOTANK
Solar/Wind Harmer
-0.006
962981AG1-147 GEN
Solar/Wind Harmer
3.893
315611Z1-036_GEN2
Solar/Wind Harmer
2.188
3130156CHOWAN
Solar/Wind Harmer
-0.009
3130156CHOWAN
Solar/Wind Harmer
-0.009
315816AE2-034 GEN
Solar/Wind Harmer
0.69
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315732AD1-074 GEN1
Solar/Wind Harmer
1.685
315733AD1-074 GEN2
Solar/Wind Harmer
1.685
315735AD1-075 GEN1
Solar/Wind Harmer
0.843
965291AG1-394 GEN
Solar/Wind Harmer
0.739
3146206CASHIE
Solar/Wind Harmer
-0.008
970601AG2-382 GEN
Solar/Wind Harmer
3.604
316318V4-068
Solar/Wind Harmer
0.205
3145893MURPHYS
Solar/Wind Harmer
-0.022
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145513AHOSKIE
Solar/Wind Harmer
0.07
961941AG1-037 GEN
Solar/Wind Harmer
0.061
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3146043SEABORD
Solar/Wind Harmer
-0.008
946281AF1-292 GEN
Solar/Wind Harmer
0.179
315607AA1-063A GEN
Solar/Wind Harmer
0.804
316087AB2-174 GEN
Solar/Wind Harmer
1.128
315652AC1-086 GEN
Solar/Wind Harmer
8.876
3137643SOCKMAN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.03
941031AE2-094 GEN
Solar/Wind Harmer
13.907
944011AF1-069 GEN
Solar/Wind Harmer
4.358
970673AG2-436 GEN
Solar/Wind Harmer
15.392
970673AG2-436 GEN
Solar/Wind Harmer
7.793
316005AA1-067
Solar/Wind Harmer
0.148
3145746EVERETS
Solar/Wind Harmer
-0.029
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
970181AG2-120 GEN
Solar/Wind Harmer
0.96
971967AH1-528 GEN
Solar/Wind Harmer
13.674
3141813NORNECK
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
3.136
970831AG2-522 GEN
Solar/Wind Harmer
3.571
316420AA1-050 GEN
Solar/Wind Harmer
0.811
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
316319Z2-044 C
Solar/Wind Harmer
0.388
970085AG2-068 GEN
Solar/Wind Harmer
4.38
970581AG2-369 GEN
Solar/Wind Harmer
3.767
3141426STAFORD
Solar/Wind Helper
0.036
315052AA1-145 CT2
50/50
2.956
966881AG1-559 GEN
Solar/Wind Harmer
0.768
3142416OLDCHRC
Solar/Wind Harmer
-0.046
3142416OLDCHRC
Solar/Wind Harmer
-0.018
3142543TWELFTH
Solar/Wind Harmer
-0.001
3143096IRON208
Adder
0.549
3150851SPRUNCC
Adder
0.581
944631AF1-128 GEN
Adder
58.155
315671AE2-027_GEN
Solar/Wind Harmer
9.626
3143526WINTERP
Solar/Wind Harmer
-0.065
970129AG2-093 GEN
Solar/Wind Harmer
2.835
316458AB2-190 GEN2
Solar/Wind Harmer
1.251
3142433PROV 92
Solar/Wind Harmer
-0.048
3142433PROV 92
Adder
0.21
3142433PROV 92
Adder
0.21
971069AG2-661 GEN
Solar/Wind Harmer
1.902
971647AH1-324 GEN
Solar/Wind Harmer
5.736
316159AE1-175 C
Solar/Wind Harmer
0.302
961611AG1-000B GEN
Solar/Wind Harmer
5.51
970659AG2-427 GEN
Solar/Wind Harmer
5.753
3151171GRAVELC
Adder
1.021
316381AD1-082 GEN
Solar/Wind Harmer
0.985
971777AH1-397 GEN
Solar/Wind Harmer
1.257
3141843SHACKLE
Adder
0.486
3143226MDLTHAN
Solar/Wind Harmer
-0.011
3141766HARMONY
Solar/Wind Harmer
-0.002
970661AG2-428 GEN
Solar/Wind Harmer
11.16
971317AH1-138 GEN
Solar/Wind Harmer
1.309
3138126ROCKLANDING
Solar/Wind Harmer
0.032
3145336SMITFLD
Solar/Wind Harmer
-0.041
972277AH1-723 GEN
Adder
53.776
3138133OCRAN
Solar/Wind Harmer
-0.006
316072AD1-144
Solar/Wind Harmer
0.194
316375AC2-012 GEN
Solar/Wind Harmer
3.263
3150981CHESPKA
Adder
1.048
316093AE2-104_GEN
Solar/Wind Harmer
2.727
316246AF1-032 C
Solar/Wind Harmer
0.188
944591AF1-124 GEN
Solar/Wind Harmer
42.182
316388AE2-253 GEN
Solar/Wind Harmer
0.623
3146456SLIGO L269
Solar/Wind Harmer
-0.009
316294AC1-161 GEN
Solar/Wind Harmer
2.962
3146516WINFALL
Solar/Wind Harmer
-0.029
3146516WINFALL
Solar/Wind Harmer
-0.009
3143336POWHATN
Solar/Wind Harmer
1.053
315800Z1-036_GEN1
Solar/Wind Harmer
2.188
3130156CHOWAN
Solar/Wind Harmer
-0.009
961951AG1-038 GEN
Solar/Wind Harmer
1.133
3145663CRESWEL
Solar/Wind Harmer
-0.024
971163AH1-040 GEN
Solar/Wind Harmer
7.992
316336AC2-165 C
Solar/Wind Harmer
1.46
316023GEN1_S
Solar/Wind Harmer
0.562
962861AG1-135 GEN
Solar/Wind Harmer
3.092
3146206CASHIE
Solar/Wind Harmer
-0.008
971547AH1-271 GEN
Solar/Wind Harmer
2.059
939411AE1-173 GEN
Solar/Wind Harmer
41.157
3145893MURPHYS
Solar/Wind Harmer
-0.033
3145893MURPHYS
Solar/Wind Harmer
0.244
3146173TUNIS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
960081AF2-299 GEN
Solar/Wind Harmer
0.899
3146263WOODLND
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.651
962571AG1-106 GEN
Solar/Wind Harmer
1.134
940641AE2-051 GEN
Solar/Wind Harmer
7.394
3145963POPLR C
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
316174AB2-169 GEN
Solar/Wind Harmer
1.203
316190AA2-174 GEN
Solar/Wind Harmer
0.096
964211AG1-282 GEN
Solar/Wind Harmer
0.234
3141726DUNNSVL
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.008
971795AH1-408 GEN
Solar/Wind Harmer
5.789
3145783HORNRTN
Solar/Wind Harmer
-0.008
3147043LAWRENC
Adder
0.611
3146293MARTNCO
Solar/Wind Harmer
0.046
316212AC1-099_GEN
Solar/Wind Harmer
0.653
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.76
3150351NORNECKC2
Adder
0.644
970937AG2-583 GEN
Solar/Wind Harmer
5.173
316494AC1-189 GEN
Solar/Wind Harmer
0.771
316129AC1-054 GEN
Solar/Wind Harmer
0.621
961671AG1-007 GEN
Solar/Wind Harmer
0.089
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.209
3146233WITAKRS
Solar/Wind Harmer
-0.028
970919AG2-571 GEN
Solar/Wind Harmer
2.225
971065AG2-659 GEN
Solar/Wind Harmer
3.511
970087AG2-069 GEN
Solar/Wind Harmer
6.571
316359AB2-059 GEN
Solar/Wind Harmer
0.928
316049AB1-081 GEN
Solar/Wind Harmer
0.743
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
3142053HEARTS
Solar/Wind Harmer
0.081
3144293JTRSVLE
Adder
0.187
957481AF2-042 GEN
Solar/Wind Harmer
10.534
3142296MT RD221
50/50
0.619
3142366NRTHEST
50/50
0.524
3150691DARBY 3
50/50
11.194
3150701DARBY 4
50/50
11.168
3150681DARBY 2
50/50
11.155
957411AF2-035 GEN
Solar/Wind Harmer
33.623
970317AG2-208 GEN
Solar/Wind Harmer
32.689
966871AG1-558 GEN
Solar/Wind Harmer
0.556
966871AG1-558 GEN
Solar/Wind Harmer
0.19
3150671DARBY 1
Adder
10.5
316075AC2-137 C
Solar/Wind Harmer
0.395
944641AF1-129 GEN
Adder
58.186
3142946ENON
Solar/Wind Harmer
-0.001
316240AF1-291 C
Solar/Wind Harmer
0.405
3143526WINTERP
Solar/Wind Harmer
-0.065
316033AB2-134 GEN
Solar/Wind Harmer
3.798
315697AD1-025 GEN
Solar/Wind Harmer
2.382
316468AD1-105 GEN
Solar/Wind Harmer
1.303
316441AF1-014 GEN
Solar/Wind Harmer
0.72
971223AH1-071 GEN
Solar/Wind Harmer
1.333
970657AG2-426 GEN
Solar/Wind Harmer
3.33
970657AG2-426 GEN
Solar/Wind Harmer
0.696
316236AE1-162_GEN
Solar/Wind Harmer
0.309
316036AC1-147 C
Solar/Wind Harmer
0.254
3150991CHESPKB
Adder
0.879
3150991CHESPKB
Adder
0.858
316316AC1-027 C
Solar/Wind Harmer
0.287
3142956BIRDNECK
Solar/Wind Harmer
0.502
316185AD1-033 GEN
Solar/Wind Harmer
0.981
3145506HICKORY
Solar/Wind Harmer
-0.037
3145506HICKORY
Solar/Wind Harmer
-0.022
3145506HICKORY
Solar/Wind Harmer
-0.006
316339AD2-160 GEN
Solar/Wind Harmer
0.623
316018AA1-139 ULT2
Solar/Wind Harmer
0.791
316017AA1-139 ULT1
Solar/Wind Harmer
0.747
3137176SLIGO L2192
Solar/Wind Harmer
-0.036
3144356SAPONY
Solar/Wind Harmer
0.321
3146456SLIGO L269
Solar/Wind Harmer
1.088
3130086AYDLETT
Solar/Wind Harmer
-0.037
3146386ELIZ CT
Solar/Wind Harmer
-0.009
316431W1029_GEN1
Solar/Wind Harmer
1.638
316433W1029_GEN2
Solar/Wind Harmer
1.638
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
315742AE1-103 GEN
Solar/Wind Harmer
0.933
3146376EDENTON
Solar/Wind Harmer
0.259
3146376EDENTON
Solar/Wind Harmer
0.259
316487AF1-042 GEN
Solar/Wind Harmer
1.133
316065AD1-022 GEN
Solar/Wind Harmer
4.136
3145893MURPHYS
Solar/Wind Harmer
0.23
3145893MURPHYS
Solar/Wind Harmer
-0.015
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
958261AF2-120 GEN
Solar/Wind Harmer
3.146
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
316181AB2-040 GEN
Solar/Wind Harmer
1.098
316426AA2-053 GEN
Solar/Wind Harmer
0.786
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.87
3145593CAROLNA
Solar/Wind Harmer
0.064
3145783HORNRTN
Solar/Wind Harmer
0.911
3145783HORNRTN
Solar/Wind Harmer
0.729
3145783HORNRTN
Solar/Wind Harmer
0.228
3145783HORNRTN
Solar/Wind Harmer
0.091
3145933PARMELE
Solar/Wind Harmer
-0.015
3145933PARMELE
Solar/Wind Harmer
-0.007
316274AC1-208 GEN
Solar/Wind Harmer
0.801
972185AH1-677 GEN
Adder
3.637
316077AC2-138 C
Solar/Wind Harmer
0.153
3150341NORNECKC1
Adder
0.676
3150341NORNECKC1
Adder
0.671
972187AH1-678 GEN
Adder
1.83
970933AG2-581 GEN
Solar/Wind Harmer
6.716
3145493TOT1
Solar/Wind Harmer
0.109
3145453TOT5
Solar/Wind Harmer
0.065
3145603CNETO
Solar/Wind Harmer
0.044
961601AG1-000A GEN
Solar/Wind Harmer
2.709
316263AC1-034 GEN
Solar/Wind Harmer
3.226
3144293JTRSVLE
Adder
0.187
3144293JTRSVLE
Adder
0.157
970099AG2-077 GEN
Solar/Wind Harmer
4.213
315051AA1-145 CT1
50/50
2.943
971645AH1-323 GEN
50/50
17.196
966881AG1-559 GEN
Solar/Wind Harmer
2.246
316473AC1-191 GEN
Solar/Wind Harmer
1.99
3142416OLDCHRC
Solar/Wind Harmer
1.811
970293AG2-193 GEN
Solar/Wind Harmer
1.949
3143096IRON208
Adder
0.549
3143096IRON208
Adder
0.538
3150861SPRUNCD
Adder
0.581
3142946ENON
Solar/Wind Harmer
-0.004
970133AG2-095 GEN
Solar/Wind Harmer
1.463
965281AG1-393 GEN
Solar/Wind Harmer
1.579
315839AE2-212 C
Solar/Wind Harmer
0.379
970129AG2-093 GEN
Solar/Wind Harmer
6.999
3142433PROV 92
Adder
0.21
3142433PROV 92
Adder
0.21
315778AD1-151 GEN
Solar/Wind Harmer
10.413
971781AH1-399 GEN
Solar/Wind Harmer
0.721
315813AE1-149 C
Solar/Wind Harmer
7.049
316382AG1-145 C
Solar/Wind Harmer
0.339
961611AG1-000B GEN
Solar/Wind Harmer
2.351
970659AG2-427 GEN
Solar/Wind Harmer
1.02
3151221GRAVEL6
Adder
6.975
3151171GRAVELC
Adder
1.342
316083AB2-161 GEN
Solar/Wind Harmer
1.744
3141843SHACKLE
Adder
0.486
316203AE2-005 GEN
Solar/Wind Harmer
4.504
3141766HARMONY
Solar/Wind Harmer
0.948
970661AG2-428 GEN
Solar/Wind Harmer
1.978
316280AD1-041 GEN
Solar/Wind Harmer
0.79
3144216WINCHST
Adder
0.35
3150921YORKTN3
Adder
2.317
3145336SMITFLD
Solar/Wind Harmer
-0.004
316156AD2-030 GEN
Solar/Wind Harmer
0.273
3141873WAN 176
Solar/Wind Harmer
1.213
972255AH1-712 GEN
Adder
46.148
3144536CHRHLND
Solar/Wind Harmer
-0.001
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
7.774
944581AF1-123 GEN
Solar/Wind Harmer
42.031
944601AF1-125 GEN
Solar/Wind Harmer
41.375
3146456SLIGO L269
Solar/Wind Harmer
-0.009
971153AH1-033 GEN
Solar/Wind Harmer
1.123
315773AC2-141 GEN
Solar/Wind Harmer
3.831
316320Y1-086
Solar/Wind Harmer
0.535
3145273HOLLAND
Solar/Wind Harmer
-0.007
316435W1029_GEN3
Solar/Wind Harmer
1.638
3146516WINFALL
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
962971AG1-146 GEN
Solar/Wind Harmer
1.669
316313AB2-026
Solar/Wind Harmer
0.239
316258AE1-075 C
Solar/Wind Harmer
0.215
316405AF2-144 C
Solar/Wind Harmer
0.227
3143336POWHATN
Solar/Wind Harmer
0.895
3146376EDENTON
Solar/Wind Harmer
-0.009
316484AD2-074 GEN
Solar/Wind Harmer
2.165
970009AG2-005 GEN
Solar/Wind Harmer
1.075
315614AA2-178 GEN
Solar/Wind Harmer
0.92
3156081AA2-088 GEN
Solar/Wind Harmer
2.717
971157AH1-035 GEN
Solar/Wind Harmer
1.045
315737AD1-076 GEN
Solar/Wind Harmer
1.583
316365GEN2_N
Solar/Wind Harmer
0.562
3146206CASHIE
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.057
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.456
961681AG1-008 GEN
Solar/Wind Harmer
6.456
3146173TUNIS
Solar/Wind Harmer
-0.008
316404AE1-155 C
Solar/Wind Harmer
1.566
3156021HOLLOMANSOL
Solar/Wind Harmer
1.092
316463AE2-346 GEN
Solar/Wind Harmer
0.131
316140AB2-099
Solar/Wind Harmer
0.054
962331AG1-082 GEN
Solar/Wind Harmer
1.009
966621AG1-532 GEN
Solar/Wind Harmer
0.162
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145963POPLR C
Solar/Wind Harmer
-0.008
313506AB2-031 GEN
Solar/Wind Harmer
0.633
316317KELFORD C
Solar/Wind Harmer
0.369
3145823KELFORD
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.005
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.936
316210AC1-098 GEN
Solar/Wind Harmer
1.176
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.418
3150351NORNECKC2
Adder
0.654
316327AA2-057 GEN
Solar/Wind Harmer
0.725
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
0.147
3146233WITAKRS
Solar/Wind Harmer
-0.005
970917AG2-570 GEN
Solar/Wind Harmer
17.575
3138543CONSLDL
Solar/Wind Harmer
-0.005
961601AG1-000A GEN
Solar/Wind Harmer
2.743
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3144293JTRSVLE
Adder
0.187
NYPJM->LTFIMP_NY
CLTF
1.285
LGEELTFEXP_LGEE->PJM
CLTF
0.641
WECLTFEXP_WEC->PJM
CLTF
0.318
LAGNLTFEXP_LAGN->PJM
CLTF
3.178
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.749
TVALTFEXP_TVA->PJM
CLTF
1.616
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.025
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.605
MECLTFEXP_MEC->PJM
CLTF
1.66
SIGELTFEXP_SIGE->PJM
CLTF
0.051
CPLELTFEXP_CPLE->PJM
CLTF
3.862
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.32

Details for 6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.28 %
Rating:1809.0 MVA
Rating Type:C
MVA to Mitigate:2067.27
MW Contribution:45.58
Bus #Bus NameTypeMW Contribution
972189AH1-679 GEN
50/50
6.193
316312AB1-027
Solar/Wind Harmer
0.576
971285AH1-108 GEN
Adder
0.913
315976AC1-164 GENA
Solar/Wind Harmer
14.017
316169AC1-164_GENC
Solar/Wind Harmer
12.109
315975AC1-164 GENB
Solar/Wind Harmer
0.415
316132AB2-190 GEN1
Solar/Wind Harmer
1.249
971167AH1-042 GEN
Solar/Wind Harmer
11.747
3142433PROV 92
Adder
0.208
3142433PROV 92
Adder
0.208
316233AE1-074 FULL
Solar/Wind Harmer
0.323
971281AH1-106 GEN
Solar/Wind Harmer
1.949
971283AH1-107 GEN
Solar/Wind Harmer
1.949
316369SG1_INVT
Solar/Wind Harmer
2.122
3143873LANEXA
Solar/Wind Harmer
-0.007
3143316POE
Solar/Wind Harmer
-0.044
972265AH1-717 GEN
Adder
7.661
3151201GRAVEL4
Adder
7.182
3151191GRAVEL3
Adder
7.091
3151211GRAVEL5
Adder
7.091
316314AB2-024 C
Solar/Wind Harmer
0.944
316059AD1-063 C
Solar/Wind Harmer
0.244
971445AH1-216 GEN
Solar/Wind Harmer
6.622
957831AF2-077 GEN
Solar/Wind Harmer
0.319
3138283WHITEMARSH
Solar/Wind Harmer
0.016
315662AE1-191 GEN
Solar/Wind Harmer
1.276
315666AE1-190 GEN
Solar/Wind Harmer
0.319
957601AF2-054 GEN
Solar/Wind Harmer
0.309
3141873WAN 176
Solar/Wind Harmer
-0.002
315833AF1-017_GEN
Solar/Wind Harmer
1.944
316349AD2-085 GEN
Solar/Wind Harmer
0.911
316311AC2-079 GEN
Solar/Wind Harmer
5.16
3152611GOSPORTB
Adder
1.131
3152621GOSPORTC
Adder
0.96
3152601GOSPORTA
Adder
0.885
3151081ELIZAR1
Adder
8.127
3151091ELIZAR2
Adder
7.986
3141913WHIT STONE
Solar/Wind Harmer
-0.01
315835AF2-110_GEN
Solar/Wind Harmer
1.229
316305AF2-043 C
Solar/Wind Harmer
0.295
957871AF2-081 GEN
Solar/Wind Harmer
4.891
319010AE1-072 C
Solar/Wind Harmer
1.972
3146406KITTY HAWK
Solar/Wind Harmer
0.008
3138133OCRAN
Solar/Wind Harmer
-0.003
313526AB2-022
Solar/Wind Harmer
0.26
3146486SUNBURY
Solar/Wind Harmer
-0.01
3146486SUNBURY
Solar/Wind Harmer
-0.01
316321Z2-027
Solar/Wind Harmer
0.259
3146396TANGLEW
Solar/Wind Harmer
0.177
3145176PASQUOTANK
Solar/Wind Harmer
-0.006
3141783LANCAST
Solar/Wind Harmer
-0.006
3141783LANCAST
Solar/Wind Harmer
-0.004
316315AB2-025 C
Solar/Wind Harmer
0.252
315611Z1-036_GEN2
Solar/Wind Harmer
2.304
315814AE2-033 C
Solar/Wind Harmer
8.664
3130156CHOWAN
Solar/Wind Harmer
-0.009
3130156CHOWAN
Solar/Wind Harmer
-0.009
315816AE2-034 GEN
Solar/Wind Harmer
0.723
962981AG1-147 GEN
Solar/Wind Harmer
3.871
3130546PLYMOUTH
Solar/Wind Harmer
-0.009
315732AD1-074 GEN1
Solar/Wind Harmer
1.762
315733AD1-074 GEN2
Solar/Wind Harmer
1.762
315735AD1-075 GEN1
Solar/Wind Harmer
0.881
965291AG1-394 GEN
Solar/Wind Harmer
0.767
3146206CASHIE
Solar/Wind Harmer
-0.009
970601AG2-382 GEN
Solar/Wind Harmer
3.761
972193AH1-681 GEN
Adder
1.748
316318V4-068
Solar/Wind Harmer
0.213
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.009
3145513AHOSKIE
Solar/Wind Harmer
0.073
961941AG1-037 GEN
Solar/Wind Harmer
0.063
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3146043SEABORD
Solar/Wind Harmer
-0.008
315607AA1-063A GEN
Solar/Wind Harmer
0.831
946281AF1-292 GEN
Solar/Wind Harmer
0.183
315652AC1-086 GEN
Solar/Wind Harmer
9.12
316087AB2-174 GEN
Solar/Wind Harmer
1.156
3137643SOCKMAN
Solar/Wind Harmer
-0.032
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.031
941031AE2-094 GEN
Solar/Wind Harmer
14.54
944011AF1-069 GEN
Solar/Wind Harmer
4.556
970673AG2-436 GEN
Solar/Wind Harmer
16.073
970673AG2-436 GEN
Solar/Wind Harmer
8.138
971967AH1-528 GEN
Solar/Wind Harmer
14.253
316005AA1-067
Solar/Wind Harmer
0.153
3145746EVERETS
Solar/Wind Harmer
-0.03
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
970181AG2-120 GEN
Solar/Wind Harmer
0.993
957861AF2-080 GEN
Solar/Wind Harmer
3.238
970831AG2-522 GEN
Solar/Wind Harmer
3.663
316420AA1-050 GEN
Solar/Wind Harmer
0.836
970085AG2-068 GEN
Solar/Wind Harmer
4.559
970581AG2-369 GEN
Solar/Wind Harmer
3.92
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
316319Z2-044 C
Solar/Wind Harmer
0.4
3141426STAFORD
Solar/Wind Helper
0.041
315052AA1-145 CT2
50/50
2.775
966881AG1-559 GEN
Solar/Wind Harmer
0.727
3142416OLDCHRC
Solar/Wind Harmer
-0.044
3142416OLDCHRC
Solar/Wind Harmer
-0.017
3143096IRON208
Adder
0.532
3142543TWELFTH
Solar/Wind Harmer
-0.001
3150851SPRUNCC
Adder
0.558
944631AF1-128 GEN
Adder
57.426
315671AE2-027_GEN
Solar/Wind Harmer
9.427
970129AG2-093 GEN
Solar/Wind Harmer
2.827
316458AB2-190 GEN2
Solar/Wind Harmer
1.249
971069AG2-661 GEN
Solar/Wind Harmer
1.91
3142433PROV 92
Solar/Wind Harmer
-0.048
3142433PROV 92
Adder
0.208
3142433PROV 92
Adder
0.208
3143526WINTERP
Solar/Wind Harmer
-0.062
316159AE1-175 C
Solar/Wind Harmer
0.313
971647AH1-324 GEN
Solar/Wind Harmer
5.818
961611AG1-000B GEN
Solar/Wind Harmer
5.622
3151171GRAVELC
Adder
1.05
971317AH1-138 GEN
Solar/Wind Harmer
1.371
970659AG2-427 GEN
Solar/Wind Harmer
5.815
3138126ROCKLANDING
Solar/Wind Harmer
0.033
316381AD1-082 GEN
Solar/Wind Harmer
0.998
971777AH1-397 GEN
Solar/Wind Harmer
1.267
3141843SHACKLE
Adder
0.49
3141766HARMONY
Solar/Wind Harmer
-0.002
970661AG2-428 GEN
Solar/Wind Harmer
11.365
3145336SMITFLD
Solar/Wind Harmer
-0.042
3143226MDLTHAN
Solar/Wind Harmer
-0.01
316072AD1-144
Solar/Wind Harmer
0.204
316375AC2-012 GEN
Solar/Wind Harmer
3.453
3150981CHESPKA
Adder
1.109
316294AC1-161 GEN
Solar/Wind Harmer
3.192
316093AE2-104_GEN
Solar/Wind Harmer
2.859
944591AF1-124 GEN
Solar/Wind Harmer
44.876
316388AE2-253 GEN
Solar/Wind Harmer
0.66
316246AF1-032 C
Solar/Wind Harmer
0.198
3146456SLIGO L269
Solar/Wind Harmer
-0.01
3138133OCRAN
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.031
3146516WINFALL
Solar/Wind Harmer
-0.009
315800Z1-036_GEN1
Solar/Wind Harmer
2.304
3130156CHOWAN
Solar/Wind Harmer
-0.009
3145663CRESWEL
Solar/Wind Harmer
-0.025
971163AH1-040 GEN
Solar/Wind Harmer
8.378
939411AE1-173 GEN
Solar/Wind Harmer
43.471
3146206CASHIE
Solar/Wind Harmer
-0.009
971547AH1-271 GEN
Solar/Wind Harmer
2.149
972277AH1-723 GEN
Adder
45.58
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.253
3143336POWHATN
Solar/Wind Harmer
1.013
316023GEN1_S
Solar/Wind Harmer
0.574
961951AG1-038 GEN
Solar/Wind Harmer
1.121
3146173TUNIS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
940641AE2-051 GEN
Solar/Wind Harmer
7.795
3146263WOODLND
Solar/Wind Harmer
-0.008
3145963POPLR C
Solar/Wind Harmer
-0.008
960081AF2-299 GEN
Solar/Wind Harmer
0.92
3145823KELFORD
Solar/Wind Harmer
-0.008
316174AB2-169 GEN
Solar/Wind Harmer
1.252
962861AG1-135 GEN
Solar/Wind Harmer
3.042
316011AB1-132 GEN
Solar/Wind Harmer
1.696
962571AG1-106 GEN
Solar/Wind Harmer
1.165
316336AC2-165 C
Solar/Wind Harmer
1.403
316190AA2-174 GEN
Solar/Wind Harmer
0.099
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
3145783HORNRTN
Solar/Wind Harmer
-0.008
971795AH1-408 GEN
Solar/Wind Harmer
5.915
3146293MARTNCO
Solar/Wind Harmer
0.048
3147043LAWRENC
Adder
0.624
316212AC1-099_GEN
Solar/Wind Harmer
0.674
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
3142296MT RD221
50/50
0.574
3142366NRTHEST
50/50
0.497
3150691DARBY 3
50/50
10.715
3150701DARBY 4
50/50
10.691
3150681DARBY 2
50/50
10.678
957411AF2-035 GEN
Solar/Wind Harmer
31.802
970317AG2-208 GEN
Solar/Wind Harmer
30.918
966871AG1-558 GEN
Solar/Wind Harmer
0.511
966871AG1-558 GEN
Solar/Wind Harmer
0.175
3150671DARBY 1
Adder
10.051
316075AC2-137 C
Solar/Wind Harmer
0.39
3142946ENON
Solar/Wind Harmer
-0.001
944641AF1-129 GEN
Adder
56.507
316240AF1-291 C
Solar/Wind Harmer
0.394
3143526WINTERP
Solar/Wind Harmer
-0.062
316033AB2-134 GEN
Solar/Wind Harmer
3.83
315697AD1-025 GEN
Solar/Wind Harmer
2.402
970657AG2-426 GEN
Solar/Wind Harmer
3.379
970657AG2-426 GEN
Solar/Wind Harmer
0.707
316441AF1-014 GEN
Solar/Wind Harmer
0.726
316236AE1-162_GEN
Solar/Wind Harmer
0.321
971223AH1-071 GEN
Solar/Wind Harmer
1.286
316468AD1-105 GEN
Solar/Wind Harmer
1.117
316036AC1-147 C
Solar/Wind Harmer
0.269
3150991CHESPKB
Adder
0.93
3150991CHESPKB
Adder
0.908
316316AC1-027 C
Solar/Wind Harmer
0.304
3142956BIRDNECK
Solar/Wind Harmer
0.532
316185AD1-033 GEN
Solar/Wind Harmer
1.04
3145506HICKORY
Solar/Wind Harmer
-0.039
3145506HICKORY
Solar/Wind Harmer
-0.023
3145506HICKORY
Solar/Wind Harmer
-0.006
316339AD2-160 GEN
Solar/Wind Harmer
0.66
316018AA1-139 ULT2
Solar/Wind Harmer
0.838
316017AA1-139 ULT1
Solar/Wind Harmer
0.791
3137176SLIGO L2192
Solar/Wind Harmer
-0.039
3146456SLIGO L269
Solar/Wind Harmer
1.153
3130086AYDLETT
Solar/Wind Harmer
-0.039
3146386ELIZ CT
Solar/Wind Harmer
-0.01
316431W1029_GEN1
Solar/Wind Harmer
1.728
316433W1029_GEN2
Solar/Wind Harmer
1.728
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3144356SAPONY
Solar/Wind Harmer
0.326
315742AE1-103 GEN
Solar/Wind Harmer
0.974
3146376EDENTON
Solar/Wind Harmer
0.273
3146376EDENTON
Solar/Wind Harmer
0.273
316065AD1-022 GEN
Solar/Wind Harmer
4.319
3145893MURPHYS
Solar/Wind Harmer
0.238
3145893MURPHYS
Solar/Wind Harmer
-0.015
316487AF1-042 GEN
Solar/Wind Harmer
1.121
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
316181AB2-040 GEN
Solar/Wind Harmer
1.126
316426AA2-053 GEN
Solar/Wind Harmer
0.811
958261AF2-120 GEN
Solar/Wind Harmer
3.088
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.895
3145593CAROLNA
Solar/Wind Harmer
0.066
3145783HORNRTN
Solar/Wind Harmer
0.938
3145783HORNRTN
Solar/Wind Harmer
0.751
3145783HORNRTN
Solar/Wind Harmer
0.235
3145783HORNRTN
Solar/Wind Harmer
0.094
3145933PARMELE
Solar/Wind Harmer
-0.015
3145933PARMELE
Solar/Wind Harmer
-0.008
316274AC1-208 GEN
Solar/Wind Harmer
0.825
972185AH1-677 GEN
Adder
3.795
972187AH1-678 GEN
Adder
1.908
970933AG2-581 GEN
Solar/Wind Harmer
6.981
3145493TOT1
Solar/Wind Harmer
0.112
3145453TOT5
Solar/Wind Harmer
0.067
3145603CNETO
Solar/Wind Harmer
0.045
970099AG2-077 GEN
Solar/Wind Harmer
8.866
3150341NORNECKC1
Adder
0.652
3150341NORNECKC1
Adder
0.647
3144293JTRSVLE
Adder
0.188
3144293JTRSVLE
Adder
0.158
961601AG1-000A GEN
Solar/Wind Harmer
0.068
964211AG1-282 GEN
Solar/Wind Harmer
0.227
3141726DUNNSVL
Solar/Wind Harmer
-0.03
315722AD1-056 GEN
Solar/Wind Harmer
0.781
316494AC1-189 GEN
Solar/Wind Harmer
0.796
970919AG2-571 GEN
Solar/Wind Harmer
2.316
970087AG2-069 GEN
Solar/Wind Harmer
6.838
316129AC1-054 GEN
Solar/Wind Harmer
0.636
961671AG1-007 GEN
Solar/Wind Harmer
0.092
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.215
3146233WITAKRS
Solar/Wind Harmer
-0.029
971065AG2-659 GEN
Solar/Wind Harmer
3.598
957481AF2-042 GEN
Solar/Wind Harmer
22.165
3150351NORNECKC2
Adder
0.621
3144293JTRSVLE
Adder
0.188
315051AA1-145 CT1
50/50
2.763
971645AH1-323 GEN
50/50
15.887
966881AG1-559 GEN
Solar/Wind Harmer
2.125
3142416OLDCHRC
Solar/Wind Harmer
1.724
316473AC1-191 GEN
Solar/Wind Harmer
1.83
970293AG2-193 GEN
Solar/Wind Harmer
1.893
3143096IRON208
Adder
0.532
3143096IRON208
Adder
0.522
3150861SPRUNCD
Adder
0.558
3142946ENON
Solar/Wind Harmer
-0.004
970133AG2-095 GEN
Solar/Wind Harmer
1.445
970129AG2-093 GEN
Solar/Wind Harmer
6.978
965281AG1-393 GEN
Solar/Wind Harmer
1.549
315839AE2-212 C
Solar/Wind Harmer
0.372
315778AD1-151 GEN
Solar/Wind Harmer
10.456
3142433PROV 92
Adder
0.208
3142433PROV 92
Adder
0.208
316382AG1-145 C
Solar/Wind Harmer
0.352
961611AG1-000B GEN
Solar/Wind Harmer
2.399
315813AE1-149 C
Solar/Wind Harmer
7.056
3151221GRAVEL6
Adder
7.174
3151171GRAVELC
Adder
1.38
970659AG2-427 GEN
Solar/Wind Harmer
1.031
3144216WINCHST
Adder
0.366
3150921YORKTN3
Adder
2.434
316083AB2-161 GEN
Solar/Wind Harmer
1.766
3141843SHACKLE
Adder
0.49
3141766HARMONY
Solar/Wind Harmer
0.959
316203AE2-005 GEN
Solar/Wind Harmer
4.541
970661AG2-428 GEN
Solar/Wind Harmer
2.014
3145336SMITFLD
Solar/Wind Harmer
-0.004
316280AD1-041 GEN
Solar/Wind Harmer
0.798
316156AD2-030 GEN
Solar/Wind Harmer
0.276
3141873WAN 176
Solar/Wind Harmer
1.226
3144536CHRHLND
Solar/Wind Harmer
-0.002
971781AH1-399 GEN
Solar/Wind Harmer
0.618
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
8.231
315773AC2-141 GEN
Solar/Wind Harmer
4.129
944581AF1-123 GEN
Solar/Wind Harmer
44.715
944601AF1-125 GEN
Solar/Wind Harmer
44.017
3146456SLIGO L269
Solar/Wind Harmer
-0.01
971153AH1-033 GEN
Solar/Wind Harmer
1.19
316320Y1-086
Solar/Wind Harmer
0.565
316435W1029_GEN3
Solar/Wind Harmer
1.728
3146516WINFALL
Solar/Wind Harmer
-0.009
3145273HOLLAND
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3146376EDENTON
Solar/Wind Harmer
-0.009
315614AA2-178 GEN
Solar/Wind Harmer
0.964
962971AG1-146 GEN
Solar/Wind Harmer
1.659
971157AH1-035 GEN
Solar/Wind Harmer
1.093
315737AD1-076 GEN
Solar/Wind Harmer
1.656
3156081AA2-088 GEN
Solar/Wind Harmer
2.822
3146206CASHIE
Solar/Wind Harmer
-0.009
972255AH1-712 GEN
Adder
39.114
3145893MURPHYS
Solar/Wind Harmer
0.06
3145893MURPHYS
Solar/Wind Harmer
-0.009
316313AB2-026
Solar/Wind Harmer
0.23
316258AE1-075 C
Solar/Wind Harmer
0.207
316405AF2-144 C
Solar/Wind Harmer
0.219
3143336POWHATN
Solar/Wind Harmer
0.861
316365GEN2_N
Solar/Wind Harmer
0.574
957521AF2-046 GEN
Solar/Wind Harmer
6.704
961681AG1-008 GEN
Solar/Wind Harmer
6.704
316484AD2-074 GEN
Solar/Wind Harmer
2.143
970009AG2-005 GEN
Solar/Wind Harmer
1.064
3146173TUNIS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1.136
316463AE2-346 GEN
Solar/Wind Harmer
0.136
316140AB2-099
Solar/Wind Harmer
0.057
962331AG1-082 GEN
Solar/Wind Harmer
1.048
3146263WOODLND
Solar/Wind Harmer
-0.008
3145963POPLR C
Solar/Wind Harmer
-0.008
966621AG1-532 GEN
Solar/Wind Harmer
0.166
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
316317KELFORD C
Solar/Wind Harmer
0.383
3145823KELFORD
Solar/Wind Harmer
-0.008
313506AB2-031 GEN
Solar/Wind Harmer
0.649
316404AE1-155 C
Solar/Wind Harmer
1.537
3145796HORNRTN
Solar/Wind Harmer
-0.032
3145796HORNRTN
Solar/Wind Harmer
-0.008
3145933PARMELE
Solar/Wind Harmer
-0.008
966801AG1-551 GEN
Solar/Wind Harmer
0.971
3147043LAWRENC
Solar/Wind Harmer
-0.005
316210AC1-098 GEN
Solar/Wind Harmer
1.213
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
315724AD1-057 GEN
Solar/Wind Harmer
0.43
316327AA2-057 GEN
Solar/Wind Harmer
0.746
970917AG2-570 GEN
Solar/Wind Harmer
18.293
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
0.151
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3150351NORNECKC2
Adder
0.631
3144293JTRSVLE
Adder
0.188
961601AG1-000A GEN
Solar/Wind Harmer
0.069
NYPJM->LTFIMP_NY
CLTF
1.242
LGEELTFEXP_LGEE->PJM
CLTF
0.605
WECLTFEXP_WEC->PJM
CLTF
0.3
LAGNLTFEXP_LAGN->PJM
CLTF
3.104
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.794
TVALTFEXP_TVA->PJM
CLTF
1.575
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.367
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.444
MECLTFEXP_MEC->PJM
CLTF
1.583
SIGELTFEXP_SIGE->PJM
CLTF
0.049
CPLELTFEXP_CPLE->PJM
CLTF
3.926
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.752

Details for 6SUMMIT-6MINE RD 230.0 kV Ckt 1 line l/o DVP_P4-2: 568T581_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6SUMMIT-6MINE RD 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 568T581_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:165.56 %
Rating:1360.0 MVA
Rating Type:C
MVA to Mitigate:2251.63
MW Contribution:36.74
Bus #Bus NameTypeMW Contribution
972197AH1-683 GEN
50/50
6.75
972219AH1-694 GEN
50/50
4.86
315052AA1-145 CT2
50/50
1.183
966881AG1-559 GEN
Solar/Wind Harmer
0.267
3142416OLDCHRC
Solar/Wind Harmer
-0.025
3142416OLDCHRC
Solar/Wind Harmer
-0.009
3150851SPRUNCC
Adder
0.37
3143526WINTERP
Solar/Wind Harmer
-0.046
3142543TWELFTH
Solar/Wind Harmer
-0.001
3143096IRON208
Adder
0.327
3143226MDLTHAN
Solar/Wind Harmer
-0.009
315671AE2-027_GEN
Solar/Wind Harmer
6.265
944631AF1-128 GEN
Adder
35.154
970129AG2-093 GEN
Solar/Wind Harmer
1.876
316458AB2-190 GEN2
Solar/Wind Harmer
0.831
971069AG2-661 GEN
Solar/Wind Harmer
1.286
970659AG2-427 GEN
Solar/Wind Harmer
4.257
971647AH1-324 GEN
Solar/Wind Harmer
4
316381AD1-082 GEN
Solar/Wind Harmer
0.733
970661AG2-428 GEN
Solar/Wind Harmer
8.426
961611AG1-000B GEN
Solar/Wind Harmer
3.913
316294AC1-161 GEN
Solar/Wind Harmer
2.543
3151171GRAVELC
Adder
0.742
3145336SMITFLD
Solar/Wind Harmer
-0.031
944591AF1-124 GEN
Solar/Wind Harmer
35.438
316375AC2-012 GEN
Solar/Wind Harmer
2.685
3150981CHESPKA
Adder
0.862
939411AE1-173 GEN
Solar/Wind Harmer
38.501
316388AE2-253 GEN
Solar/Wind Harmer
0.519
940641AE2-051 GEN
Solar/Wind Harmer
7.21
3146456SLIGO L269
Solar/Wind Harmer
-0.008
316246AF1-032 C
Solar/Wind Harmer
0.155
316093AE2-104_GEN
Solar/Wind Harmer
2.222
316072AD1-144
Solar/Wind Harmer
0.154
3143336POWHATN
Solar/Wind Harmer
0.906
3146516WINFALL
Solar/Wind Harmer
-0.024
3146516WINFALL
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.83
316159AE1-175 C
Solar/Wind Harmer
0.197
316336AC2-165 C
Solar/Wind Harmer
1.276
3130156CHOWAN
Solar/Wind Harmer
-0.007
3138126ROCKLANDING
Solar/Wind Harmer
0.022
3150401LDYSMT4
50/50
43.23
3150371LDYSMT1
50/50
41.772
970497AG2-320 GEN
50/50
24.535
315051AA1-145 CT1
50/50
1.178
966881AG1-559 GEN
Solar/Wind Harmer
0.782
3142416OLDCHRC
Solar/Wind Harmer
0.967
3150861SPRUNCD
Adder
0.37
970293AG2-193 GEN
Solar/Wind Harmer
1.099
3143096IRON208
Adder
0.327
3143096IRON208
Adder
0.321
315839AE2-212 C
Solar/Wind Harmer
0.256
970133AG2-095 GEN
Solar/Wind Harmer
0.941
965281AG1-393 GEN
Solar/Wind Harmer
1.043
970129AG2-093 GEN
Solar/Wind Harmer
4.632
315778AD1-151 GEN
Solar/Wind Harmer
7.043
315813AE1-149 C
Solar/Wind Harmer
5.08
3142946ENON
Solar/Wind Harmer
-0.003
970659AG2-427 GEN
Solar/Wind Harmer
0.754
316083AB2-161 GEN
Solar/Wind Harmer
1.297
970661AG2-428 GEN
Solar/Wind Harmer
1.493
961611AG1-000B GEN
Solar/Wind Harmer
1.669
315773AC2-141 GEN
Solar/Wind Harmer
3.289
3151221GRAVEL6
Adder
5.071
3151171GRAVELC
Adder
0.976
3145336SMITFLD
Solar/Wind Harmer
-0.003
3144536CHRHLND
Solar/Wind Harmer
-0.001
944581AF1-123 GEN
Solar/Wind Harmer
35.31
944601AF1-125 GEN
Solar/Wind Harmer
34.759
3151101ELIZAR3
Adder
6.413
3144873MCLAUGH
Solar/Wind Harmer
0
3146456SLIGO L269
Solar/Wind Harmer
-0.008
971153AH1-033 GEN
Solar/Wind Harmer
0.935
316313AB2-026
Solar/Wind Harmer
0.206
316258AE1-075 C
Solar/Wind Harmer
0.185
316405AF2-144 C
Solar/Wind Harmer
0.196
3143336POWHATN
Solar/Wind Harmer
0.77
316320Y1-086
Solar/Wind Harmer
0.445
316435W1029_GEN3
Solar/Wind Harmer
1.364
3146516WINFALL
Solar/Wind Harmer
-0.007
3145273HOLLAND
Solar/Wind Harmer
-0.006
3146626S HERTFORD
Solar/Wind Harmer
-0.007
316473AC1-191 GEN
Solar/Wind Harmer
0.8
316382AG1-145 C
Solar/Wind Harmer
0.221
3146376EDENTON
Solar/Wind Harmer
-0.007
3144216WINCHST
Adder
0.245
3150921YORKTN3
Adder
1.611
315614AA2-178 GEN
Solar/Wind Harmer
0.776
316365GEN2_N
Solar/Wind Harmer
0.478
971157AH1-035 GEN
Solar/Wind Harmer
0.885
3156081AA2-088 GEN
Solar/Wind Harmer
2.298
315737AD1-076 GEN
Solar/Wind Harmer
1.342
3146206CASHIE
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
0.049
3145893MURPHYS
Solar/Wind Harmer
-0.007
970917AG2-570 GEN
Solar/Wind Harmer
17.459
957521AF2-046 GEN
Solar/Wind Harmer
5.494
961681AG1-008 GEN
Solar/Wind Harmer
5.494
3146173TUNIS
Solar/Wind Harmer
-0.007
972255AH1-712 GEN
Adder
31.532
3156021HOLLOMANSOL
Solar/Wind Harmer
0.931
966621AG1-532 GEN
Solar/Wind Harmer
0.14
316463AE2-346 GEN
Solar/Wind Harmer
0.112
316140AB2-099
Solar/Wind Harmer
0.047
962331AG1-082 GEN
Solar/Wind Harmer
0.863
3146263WOODLND
Solar/Wind Harmer
-0.007
313506AB2-031 GEN
Solar/Wind Harmer
0.549
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.318
3145823KELFORD
Solar/Wind Harmer
-0.007
3147043LAWRENC
Solar/Wind Harmer
-0.004
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
316478AD1-087 GEN
Solar/Wind Harmer
0.568
316486AD2-202 GEN
Solar/Wind Harmer
0.166
316210AC1-098 GEN
Solar/Wind Harmer
1.025
3145933PARMELE
Solar/Wind Harmer
-0.006
966801AG1-551 GEN
Solar/Wind Harmer
0.813
970909AG2-566 GEN
Solar/Wind Harmer
0.613
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
315724AD1-057 GEN
Solar/Wind Harmer
0.367
316327AA2-057 GEN
Solar/Wind Harmer
0.639
3141906WESTMOR
Solar/Wind Helper
0.071
3150391LDYSMT3
50/50
43.149
972195AH1-682 GEN
50/50
5.67
315673AE1-157 GEN
Solar/Wind Harmer
21.737
957411AF2-035 GEN
Solar/Wind Harmer
11.699
970317AG2-208 GEN
Solar/Wind Harmer
11.374
3142296MT RD221
Adder
0.302
3142366NRTHEST
Adder
0.276
3150691DARBY 3
Adder
5.91
3150701DARBY 4
Adder
5.896
3150681DARBY 2
Adder
5.889
3150671DARBY 1
Adder
5.882
3143526WINTERP
Solar/Wind Harmer
-0.046
944641AF1-129 GEN
Adder
37.086
971223AH1-071 GEN
Solar/Wind Harmer
1.092
316240AF1-291 C
Solar/Wind Harmer
0.262
316075AC2-137 C
Solar/Wind Harmer
0.224
3142946ENON
Solar/Wind Harmer
-0.001
316033AB2-134 GEN
Solar/Wind Harmer
2.603
315697AD1-025 GEN
Solar/Wind Harmer
1.633
970657AG2-426 GEN
Solar/Wind Harmer
2.49
970657AG2-426 GEN
Solar/Wind Harmer
0.521
316236AE1-162_GEN
Solar/Wind Harmer
0.235
316036AC1-147 C
Solar/Wind Harmer
0.209
3150991CHESPKB
Adder
0.723
3150991CHESPKB
Adder
0.706
3142956BIRDNECK
Solar/Wind Harmer
0.415
316316AC1-027 C
Solar/Wind Harmer
0.238
316185AD1-033 GEN
Solar/Wind Harmer
0.816
3145506HICKORY
Solar/Wind Harmer
-0.031
3145506HICKORY
Solar/Wind Harmer
-0.018
3145506HICKORY
Solar/Wind Harmer
-0.005
316339AD2-160 GEN
Solar/Wind Harmer
0.519
316018AA1-139 ULT2
Solar/Wind Harmer
0.659
316017AA1-139 ULT1
Solar/Wind Harmer
0.622
3137176SLIGO L2192
Solar/Wind Harmer
-0.03
3146456SLIGO L269
Solar/Wind Harmer
0.906
3130086AYDLETT
Solar/Wind Harmer
-0.03
3144356SAPONY
Solar/Wind Harmer
0.267
3146386ELIZ CT
Solar/Wind Harmer
-0.008
316431W1029_GEN1
Solar/Wind Harmer
1.364
316433W1029_GEN2
Solar/Wind Harmer
1.364
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
966871AG1-558 GEN
Solar/Wind Harmer
0.223
966871AG1-558 GEN
Solar/Wind Harmer
0.076
315742AE1-103 GEN
Solar/Wind Harmer
0.772
3146376EDENTON
Solar/Wind Harmer
0.217
3146376EDENTON
Solar/Wind Harmer
0.217
972185AH1-677 GEN
Adder
3.634
972187AH1-678 GEN
Adder
1.826
970933AG2-581 GEN
Solar/Wind Harmer
6.679
316065AD1-022 GEN
Solar/Wind Harmer
3.511
3145893MURPHYS
Solar/Wind Harmer
0.195
3145893MURPHYS
Solar/Wind Harmer
-0.013
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316181AB2-040 GEN
Solar/Wind Harmer
0.952
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
970099AG2-077 GEN
Solar/Wind Harmer
8.455
316426AA2-053 GEN
Solar/Wind Harmer
0.683
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.757
3145593CAROLNA
Solar/Wind Harmer
0.056
3145796HORNRTN
Solar/Wind Harmer
-0.02
3145783HORNRTN
Solar/Wind Harmer
0.794
3145783HORNRTN
Solar/Wind Harmer
0.635
3145783HORNRTN
Solar/Wind Harmer
0.199
3145783HORNRTN
Solar/Wind Harmer
0.079
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.006
971741AH1-377 GEN
Solar/Wind Harmer
7.563
316274AC1-208 GEN
Solar/Wind Harmer
0.701
970301AG2-198 GEN
Solar/Wind Harmer
3.227
3150411LDYSMT5
50/50
43.365
3150381LDYSMT2
50/50
41.502
972213AH1-691 GEN
50/50
7.02
972215AH1-692 GEN
50/50
7.02
963051AG1-154 GEN
50/50
5.4
972189AH1-679 GEN
50/50
2.64
316312AB1-027
Solar/Wind Harmer
0.323
971285AH1-108 GEN
Adder
0.606
316233AE1-074 FULL
Solar/Wind Harmer
0.24
971281AH1-106 GEN
Solar/Wind Harmer
1.451
971283AH1-107 GEN
Solar/Wind Harmer
1.451
316132AB2-190 GEN1
Solar/Wind Harmer
0.831
3143316POE
Solar/Wind Harmer
-0.032
316369SG1_INVT
Solar/Wind Harmer
1.442
972265AH1-717 GEN
Adder
5.416
3151201GRAVEL4
Adder
5.077
3151191GRAVEL3
Adder
5.013
3151211GRAVEL5
Adder
5.013
971445AH1-216 GEN
Solar/Wind Harmer
4.834
315833AF1-017_GEN
Solar/Wind Harmer
1.477
316349AD2-085 GEN
Solar/Wind Harmer
0.692
316311AC2-079 GEN
Solar/Wind Harmer
3.921
3151081ELIZAR1
Adder
6.332
3151091ELIZAR2
Adder
6.222
3152611GOSPORTB
Adder
0.879
3152621GOSPORTC
Adder
0.746
3152601GOSPORTA
Adder
0.688
957871AF2-081 GEN
Solar/Wind Harmer
3.844
319010AE1-072 C
Solar/Wind Harmer
1.551
3146406KITTY HAWK
Solar/Wind Harmer
0.006
316315AB2-025 C
Solar/Wind Harmer
0.206
316305AF2-043 C
Solar/Wind Harmer
0.23
315835AF2-110_GEN
Solar/Wind Harmer
0.955
315976AC1-164 GENA
Solar/Wind Harmer
8.065
316169AC1-164_GENC
Solar/Wind Harmer
6.967
315975AC1-164 GENB
Solar/Wind Harmer
0.239
315814AE2-033 C
Solar/Wind Harmer
7.093
313526AB2-022
Solar/Wind Harmer
0.205
3146486SUNBURY
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.008
316321Z2-027
Solar/Wind Harmer
0.204
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
3146396TANGLEW
Solar/Wind Harmer
0.139
941031AE2-094 GEN
Solar/Wind Harmer
13.945
944011AF1-069 GEN
Solar/Wind Harmer
4.369
315611Z1-036_GEN2
Solar/Wind Harmer
1.83
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
970673AG2-436 GEN
Solar/Wind Harmer
15.399
970673AG2-436 GEN
Solar/Wind Harmer
7.797
971967AH1-528 GEN
Solar/Wind Harmer
13.65
315816AE2-034 GEN
Solar/Wind Harmer
0.582
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315732AD1-074 GEN1
Solar/Wind Harmer
1.428
315733AD1-074 GEN2
Solar/Wind Harmer
1.428
315735AD1-075 GEN1
Solar/Wind Harmer
0.714
965291AG1-394 GEN
Solar/Wind Harmer
0.626
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.063
316318V4-068
Solar/Wind Harmer
0.174
3145893MURPHYS
Solar/Wind Harmer
-0.019
3145893MURPHYS
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.35
970581AG2-369 GEN
Solar/Wind Harmer
3.741
972193AH1-681 GEN
Adder
1.409
946281AF1-292 GEN
Solar/Wind Harmer
0.155
3145513AHOSKIE
Solar/Wind Harmer
0.06
961941AG1-037 GEN
Solar/Wind Harmer
0.052
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3146043SEABORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315607AA1-063A GEN
Solar/Wind Harmer
0.693
316087AB2-174 GEN
Solar/Wind Harmer
0.977
315652AC1-086 GEN
Solar/Wind Harmer
7.643
3137643SOCKMAN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.026
970831AG2-522 GEN
Solar/Wind Harmer
3.234
316005AA1-067
Solar/Wind Harmer
0.129
3145746EVERETS
Solar/Wind Harmer
-0.025
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
970181AG2-120 GEN
Solar/Wind Harmer
0.838
3141426STAFORD
Solar/Wind Helper
0.114
316223AC1-118
Solar/Wind Helper
0.271
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.74
316023GEN1_S
Solar/Wind Harmer
0.478
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.75
3145893MURPHYS
Solar/Wind Harmer
-0.028
3145893MURPHYS
Solar/Wind Harmer
0.208
970919AG2-571 GEN
Solar/Wind Harmer
2.21
970087AG2-069 GEN
Solar/Wind Harmer
6.524
3146173TUNIS
Solar/Wind Harmer
-0.007
972277AH1-723 GEN
Adder
36.745
960081AF2-299 GEN
Solar/Wind Harmer
0.777
3145683EARLEYS
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
971317AH1-138 GEN
Solar/Wind Harmer
0.852
316011AB1-132 GEN
Solar/Wind Harmer
1.421
962571AG1-106 GEN
Solar/Wind Harmer
0.977
971795AH1-408 GEN
Solar/Wind Harmer
5.082
3145963POPLR C
Solar/Wind Harmer
-0.007
957481AF2-042 GEN
Solar/Wind Harmer
21.138
316190AA2-174 GEN
Solar/Wind Harmer
0.083
3145823KELFORD
Solar/Wind Harmer
-0.007
3147043LAWRENC
Adder
0.541
316174AB2-169 GEN
Solar/Wind Harmer
1.035
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145783HORNRTN
Solar/Wind Harmer
-0.007
315693AD1-088 GEN
Solar/Wind Harmer
3.339
962491AG1-098 GEN
Solar/Wind Harmer
4.459
970937AG2-583 GEN
Solar/Wind Harmer
4.746
316212AC1-099_GEN
Solar/Wind Harmer
0.57
3146293MARTNCO
Solar/Wind Harmer
0.04
316129AC1-054 GEN
Solar/Wind Harmer
0.565
971065AG2-659 GEN
Solar/Wind Harmer
3.207
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
315722AD1-056 GEN
Solar/Wind Harmer
0.667
316337AD2-073 GEN
Solar/Wind Helper
0.174
NYPJM->LTFIMP_NY
CLTF
1.15
LGEELTFEXP_LGEE->PJM
CLTF
0.646
WECLTFEXP_WEC->PJM
CLTF
0.327
LAGNLTFEXP_LAGN->PJM
CLTF
3.071
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.25
TVALTFEXP_TVA->PJM
CLTF
1.556
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.485
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.426
MECLTFEXP_MEC->PJM
CLTF
1.669
SIGELTFEXP_SIGE->PJM
CLTF
0.052
CPLELTFEXP_CPLE->PJM
CLTF
3.627
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.979

Details for 6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line l/o PEPCO_P1_5070_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
Contingency Name:
PEPCO_P1_5070_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:140.61 %
Rating:1478.62 MVA
Rating Type:B
MVA to Mitigate:2079.09
MW Contribution:42.85
Bus #Bus NameTypeMW Contribution
3152131X4-039 ST
50/50
2.892
3152121X4-039 GT2
50/50
1.833
3150011OMF A
50/50
0.216
3140676OCCOQUN
50/50
0.286
970467AG2-304 GEN
50/50
14.788
972223AH1-696 GEN
50/50
9.026
3150151POSSMC1
50/50
1.143
3141346CRANES
50/50
0.127
3150221REMNGT2
50/50
13.228
972201AH1-685 GEN
50/50
2.282
3150211REMNGT1
Adder
12.383
3150281M RUN A
Adder
13.357
316006AB2-029 C
Solar/Wind Harmer
0.001
971685AH1-345 GEN
Solar/Wind Harmer
0.73
316045AC1-158 PL2
Solar/Wind Harmer
1.475
972197AH1-683 GEN
Adder
1.98
972219AH1-694 GEN
Adder
1.425
316254AC1-120 GEN1
Solar/Wind Harmer
0.2
972135AH1-637 GEN
Solar/Wind Harmer
0.781
966881AG1-559 GEN
Solar/Wind Harmer
0.105
970053AG2-049 GEN
50/50
2.022
3138216PACIFIC
Solar/Wind Harmer
0.025
316411AF1-147_GEN1
Solar/Wind Harmer
0.003
316415AF1-147_GEN2
Solar/Wind Harmer
0.003
3141426STAFORD
Solar/Wind Harmer
0.023
3150411LDYSMT5
Adder
12.718
3150381LDYSMT2
Adder
12.172
972213AH1-691 GEN
Adder
2.059
972215AH1-692 GEN
Adder
2.059
316164AC1-076 GEN
Solar/Wind Harmer
0.132
944491AF1-114 GEN
Solar/Wind Harmer
0
316223AC1-118
Solar/Wind Harmer
0.064
972189AH1-679 GEN
Adder
1.467
3141813NORNECK
Solar/Wind Harmer
0.087
970327AG2-215 GEN
Solar/Wind Harmer
2.824
962981AG1-147 GEN
Solar/Wind Harmer
3.203
3141783LANCAST
Solar/Wind Harmer
0.051
3141783LANCAST
Solar/Wind Harmer
0.034
3138133OCRAN
Solar/Wind Harmer
0.025
3141913WHIT STONE
Solar/Wind Harmer
0.085
3147346CASHSCORNER
Solar/Wind Harmer
0.196
316312AB1-027
Solar/Wind Harmer
0.152
316314AB2-024 C
Solar/Wind Harmer
0
316059AD1-063 C
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.017
315662AE1-191 GEN
Solar/Wind Harmer
0.003
315666AE1-190 GEN
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
2.507
3143873LANEXA
Solar/Wind Harmer
0.051
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
971167AH1-042 GEN
Solar/Wind Harmer
7.477
315976AC1-164 GENA
Solar/Wind Harmer
8.72
316169AC1-164_GENC
Solar/Wind Harmer
7.533
315975AC1-164 GENB
Solar/Wind Harmer
0.258
316233AE1-074 FULL
Solar/Wind Harmer
0.067
971281AH1-106 GEN
Solar/Wind Harmer
1.161
971283AH1-107 GEN
Solar/Wind Harmer
1.161
971285AH1-108 GEN
Adder
0.631
3138283WHITEMARSH
Solar/Wind Harmer
0.019
316132AB2-190 GEN1
Solar/Wind Harmer
0.442
316369SG1_INVT
Solar/Wind Harmer
0.003
972265AH1-717 GEN
Adder
6.337
3151201GRAVEL4
Adder
5.94
3151191GRAVEL3
Adder
5.865
3151211GRAVEL5
Adder
5.865
971445AH1-216 GEN
Solar/Wind Harmer
5.723
3143316POE
Solar/Wind Harmer
0.321
3151081ELIZAR1
Adder
7.394
3151091ELIZAR2
Adder
7.266
3152611GOSPORTB
Adder
1.027
3152621GOSPORTC
Adder
0.872
3152601GOSPORTA
Adder
0.804
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.055
316311AC2-079 GEN
Solar/Wind Harmer
2.303
957871AF2-081 GEN
Solar/Wind Harmer
3.99
316305AF2-043 C
Solar/Wind Harmer
0.001
319010AE1-072 C
Solar/Wind Harmer
0.403
3146406KITTY HAWK
Solar/Wind Harmer
0.01
315835AF2-110_GEN
Solar/Wind Harmer
0.548
313526AB2-022
Solar/Wind Harmer
0.043
3146486SUNBURY
Solar/Wind Harmer
0.079
3146486SUNBURY
Solar/Wind Harmer
0.079
316321Z2-027
Solar/Wind Harmer
0.015
3146396TANGLEW
Solar/Wind Harmer
0.219
3145176PASQUOTANK
Solar/Wind Harmer
0.049
316315AB2-025 C
Solar/Wind Harmer
0.064
315814AE2-033 C
Solar/Wind Harmer
6.204
941031AE2-094 GEN
Solar/Wind Harmer
14.412
944011AF1-069 GEN
Solar/Wind Harmer
4.709
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.078
3130156CHOWAN
Solar/Wind Harmer
0.078
970673AG2-436 GEN
Solar/Wind Harmer
16.54
970673AG2-436 GEN
Solar/Wind Harmer
11.027
971967AH1-528 GEN
Solar/Wind Harmer
12.344
315816AE2-034 GEN
Solar/Wind Harmer
0.329
3130546PLYMOUTH
Solar/Wind Harmer
0.076
315732AD1-074 GEN1
Solar/Wind Harmer
0.435
315733AD1-074 GEN2
Solar/Wind Harmer
0.435
315735AD1-075 GEN1
Solar/Wind Harmer
0.218
965291AG1-394 GEN
Solar/Wind Harmer
0.336
3146206CASHIE
Solar/Wind Harmer
0.075
970601AG2-382 GEN
Solar/Wind Harmer
2.811
3145893MURPHYS
Solar/Wind Harmer
0.203
972289AH1-729 GEN
50/50
13.249
3150091POSSM6B
50/50
0.848
3150071POSSM 5
50/50
52.224
3150181POSSMC2
50/50
1.152
3150181POSSMC2
50/50
1.143
3150181POSSMC2
50/50
1.143
316447AC1-158 HLD
Solar/Wind Harmer
1.014
3150391LDYSMT3
Adder
12.655
972195AH1-682 GEN
Adder
1.663
315651AD1-115 GEN
Solar/Wind Harmer
0.003
315673AE1-157 GEN
Solar/Wind Harmer
6.396
957411AF2-035 GEN
Solar/Wind Harmer
3.895
970317AG2-208 GEN
Solar/Wind Harmer
3.609
316468AD1-105 GEN
Solar/Wind Harmer
-0.029
316077AC2-138 C
Solar/Wind Harmer
0
3150341NORNECKC1
Adder
0.913
3150341NORNECKC1
Adder
0.906
966001AG1-469 GEN
Solar/Wind Harmer
0.051
958261AF2-120 GEN
Solar/Wind Harmer
2.86
3151731LOISA B
Adder
5.599
3151721LOISA A
Adder
5.57
966871AG1-558 GEN
Solar/Wind Harmer
0.099
3142296MT RD221
Adder
0.271
3142366NRTHEST
Adder
0.276
3150691DARBY 3
Adder
6.069
3150701DARBY 4
Adder
6.055
3150681DARBY 2
Adder
6.048
3150671DARBY 1
Adder
6.041
316075AC2-137 C
Solar/Wind Harmer
0.023
3142946ENON
Solar/Wind Harmer
0.008
3143526WINTERP
Solar/Wind Harmer
0.435
971223AH1-071 GEN
Solar/Wind Harmer
0.89
944641AF1-129 GEN
Adder
39.415
316240AF1-291 C
Solar/Wind Harmer
0.001
316033AB2-134 GEN
Solar/Wind Harmer
0.005
315697AD1-025 GEN
Solar/Wind Harmer
0.092
316236AE1-162_GEN
Solar/Wind Harmer
0.001
970657AG2-426 GEN
Solar/Wind Harmer
2.829
970657AG2-426 GEN
Solar/Wind Harmer
0.593
316036AC1-147 C
Solar/Wind Harmer
0.015
3150991CHESPKB
Adder
0.845
3150991CHESPKB
Adder
0.825
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.077
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3145506HICKORY
Solar/Wind Harmer
0.321
3145506HICKORY
Solar/Wind Harmer
0.193
3145506HICKORY
Solar/Wind Harmer
0.048
316339AD2-160 GEN
Solar/Wind Harmer
0.13
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.045
3137176SLIGO L2192
Solar/Wind Harmer
0.319
3146456SLIGO L269
Solar/Wind Harmer
1.416
3130086AYDLETT
Solar/Wind Harmer
0.32
3146386ELIZ CT
Solar/Wind Harmer
0.08
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.079
3146516WINFALL
Solar/Wind Harmer
0.079
3146516WINFALL
Solar/Wind Harmer
0.079
3146626S HERTFORD
Solar/Wind Harmer
0.079
3146626S HERTFORD
Solar/Wind Harmer
0.079
3144356SAPONY
Solar/Wind Harmer
0.657
315742AE1-103 GEN
Solar/Wind Harmer
0.001
3146376EDENTON
Solar/Wind Harmer
0.345
3146376EDENTON
Solar/Wind Harmer
0.345
972185AH1-677 GEN
Adder
4.331
972187AH1-678 GEN
Adder
2.184
970933AG2-581 GEN
Solar/Wind Harmer
6.107
316065AD1-022 GEN
Solar/Wind Harmer
3.475
3145893MURPHYS
Solar/Wind Harmer
0.503
3145893MURPHYS
Solar/Wind Harmer
0.135
3146173TUNIS
Solar/Wind Harmer
0.075
3146173TUNIS
Solar/Wind Harmer
0.075
970099AG2-077 GEN
Solar/Wind Harmer
7.908
316181AB2-040 GEN
Solar/Wind Harmer
0.107
3142666NORTHAMPTON
Solar/Wind Harmer
0.074
3142666NORTHAMPTON
Solar/Wind Harmer
0.074
3142666NORTHAMPTON
Solar/Wind Harmer
0.074
3142666NORTHAMPTON
Solar/Wind Harmer
0.044
971741AH1-377 GEN
Solar/Wind Harmer
7.304
970301AG2-198 GEN
Solar/Wind Harmer
3.138
316426AA2-053 GEN
Solar/Wind Harmer
0.248
3146776BUCKING
Solar/Wind Harmer
0.293
3145593CAROLNA
Solar/Wind Harmer
0.073
3145593CAROLNA
Solar/Wind Harmer
0.073
3146776BUCKING
Solar/Wind Harmer
0.024
966811AG1-552 GEN
Solar/Wind Harmer
0.795
3145593CAROLNA
Solar/Wind Harmer
0.091
3145783HORNRTN
Solar/Wind Harmer
1.299
3145783HORNRTN
Solar/Wind Harmer
1.039
3145783HORNRTN
Solar/Wind Harmer
0.325
3145783HORNRTN
Solar/Wind Harmer
0.13
3145796HORNRTN
Solar/Wind Harmer
0.219
3147133PAMPLIN
Solar/Wind Harmer
0.072
3147133PAMPLIN
Solar/Wind Harmer
0.058
958211AF2-115 GEN
Solar/Wind Harmer
0.866
963191AG1-168 GEN
Solar/Wind Harmer
0.289
3144293JTRSVLE
Adder
0.23
3144293JTRSVLE
Adder
0.193
3145933PARMELE
Solar/Wind Harmer
0.144
3145933PARMELE
Solar/Wind Harmer
0.072
316274AC1-208 GEN
Solar/Wind Harmer
0.372
316034AC1-036 C
Solar/Wind Harmer
0.005
970323AG2-213 GEN
Solar/Wind Harmer
3.057
971775AH1-396 GEN
Solar/Wind Harmer
0.115
971489AH1-241 GEN
Solar/Wind Harmer
3.817
313527AB2-043 GEN
Solar/Wind Harmer
0.001
939181AE1-148 GEN
Solar/Wind Harmer
3.402
3145493TOT1
Solar/Wind Harmer
0.162
3145453TOT5
Solar/Wind Harmer
0.097
3145603CNETO
Solar/Wind Harmer
0.065
315821AE2-092 GEN
Solar/Wind Harmer
0.004
962561AG1-105 GEN
Solar/Wind Harmer
3.322
961601AG1-000A GEN
Solar/Wind Harmer
1.228
316263AC1-034 GEN
Solar/Wind Harmer
2.624
964791AG1-342 GEN
Solar/Wind Harmer
1.322
3146843MT LREL
Solar/Wind Harmer
0.069
3146843MT LREL
Solar/Wind Harmer
0.069
316222AC1-221 GEN
Solar/Wind Harmer
0.264
971761AH1-387 GEN
Solar/Wind Harmer
1.238
942751AE2-291 GEN
Solar/Wind Harmer
3.276
3132123MT JACKSON
Solar/Wind Harmer
0.183
970117AG2-086 GEN
Solar/Wind Harmer
1.401
970117AG2-086 GEN
Solar/Wind Harmer
0.934
226929AD2-058 GEN
Solar/Wind Helper
0.143
237025AB1-124 C
Solar/Wind Helper
0.193
237006AB1-125 GEN
Solar/Wind Helper
0.145
23777801MSM_W1-116
Solar/Wind Helper
0.13
237034AC2-136 C
Solar/Wind Helper
0.205
205916AD1-020 GEN
Solar/Wind Helper
1.48
208835TUHI V3-051
Solar/Wind Helper
0.019
208835TUHI V3-051
Solar/Wind Helper
0.019
237001AB1-127_GEN
Solar/Wind Helper
0.307
237002AB1-128_GEN
Solar/Wind Helper
0.298
235063AE1-101 C2
Solar/Wind Helper
1.064
20390526W1-045 C
Solar/Wind Helper
0.252
23777901MDS_W4-102
Solar/Wind Helper
0.105
235020AA1-095 C
Solar/Wind Helper
0.029
233933AB2-153 GEN
Solar/Wind Helper
0.14
233944AB2-135 GEN
Solar/Wind Helper
0.355
232424Y1-079 C
Solar/Wind Helper
0.07
233987AB2-037 GEN
Solar/Wind Helper
1.406
233946AB2-136 GEN
Solar/Wind Helper
0.341
234036AF2-325 C
Solar/Wind Helper
0.025
233901CHERRYDALE C
Solar/Wind Helper
0.139
232408W1-005 C
Solar/Wind Helper
0.304
232410W1-006 C
Solar/Wind Helper
0.304
233939AC1-091 C
Solar/Wind Helper
0.209
233970AC1-092 C
Solar/Wind Helper
0.209
230433AD2-135 GEN
Solar/Wind Helper
0.01
219921AF1-264
Solar/Wind Helper
0.03
230407AD2-065 C
Solar/Wind Helper
0.024
219615MILLCREEK C
Solar/Wind Helper
0.016
963401AG1-189 GEN
Solar/Wind Helper
0.033
963391AG1-188 GEN
Solar/Wind Helper
0.048
20714928UPF_X1-085
Solar/Wind Helper
0.003
20720628TIN_W1-124
Solar/Wind Helper
0.11
20716928W4-060COL
Solar/Wind Helper
0.03
20673828FLE_V3-070
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.009
207442AE1-156 GEN
Solar/Wind Helper
0.188
20676128MHD_W3-029
Solar/Wind Helper
0.055
3145893MURPHYS
Solar/Wind Harmer
0.075
970085AG2-068 GEN
Solar/Wind Harmer
4
970581AG2-369 GEN
Solar/Wind Harmer
3.44
3145513AHOSKIE
Solar/Wind Harmer
0.156
3145513AHOSKIE
Solar/Wind Harmer
0.074
3146043SEABORD
Solar/Wind Harmer
0.074
3145683EARLEYS
Solar/Wind Harmer
0.149
3145683EARLEYS
Solar/Wind Harmer
0.074
3145683EARLEYS
Solar/Wind Harmer
0.074
315607AA1-063A GEN
Solar/Wind Harmer
0.152
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.294
315652AC1-086 GEN
Solar/Wind Harmer
8.087
972205AH1-687 GEN
Adder
3.134
970285AG2-188 GEN
Solar/Wind Harmer
5.802
971845AH1-439 GEN
Solar/Wind Harmer
3.325
3145796HORNRTN
Solar/Wind Harmer
0.233
3145796HORNRTN
Solar/Wind Harmer
0.029
3146033SCOT NK
Solar/Wind Harmer
0.29
315657AE1-056 GEN
Solar/Wind Harmer
2.494
946301AF1-294 GEN
Solar/Wind Harmer
1.424
961791AG1-021 GEN
Solar/Wind Harmer
0.693
970683AG2-441 GEN
Solar/Wind Harmer
4.794
970681AG2-440 GEN
Solar/Wind Harmer
3.836
970831AG2-522 GEN
Solar/Wind Harmer
3.066
972193AH1-681 GEN
Adder
1.643
3144303KENBRDG
Solar/Wind Harmer
0.057
971443AH1-215 GEN
Solar/Wind Harmer
1.204
971447AH1-217 GEN
Solar/Wind Harmer
2.163
316005AA1-067
Solar/Wind Harmer
0.076
3145746EVERETS
Solar/Wind Harmer
0.282
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
970181AG2-120 GEN
Solar/Wind Harmer
0.883
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
3138266HYDRAULIC
Solar/Wind Harmer
0.003
3138266HYDRAULIC
Solar/Wind Harmer
0.002
957861AF2-080 GEN
Solar/Wind Harmer
3.032
316420AA1-050 GEN
Solar/Wind Harmer
0.002
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.07
3145573BETHELC
Solar/Wind Harmer
0.07
316118AC1-105 GEN
Solar/Wind Harmer
0.176
3147173SINAI
Solar/Wind Harmer
0.067
3147243WELCO
Solar/Wind Harmer
0.042
270494AE1-108_GEN
Solar/Wind Harmer
0.802
3148133STUARTS
Solar/Wind Harmer
0.039
3148013FISHERV
Solar/Wind Harmer
0.037
970865AG2-541 GEN
Solar/Wind Harmer
2.214
316123AC1-075 GEN
Solar/Wind Harmer
0.084
970165AG2-112 GEN
Solar/Wind Harmer
0.5
970163AG2-111 GEN
Solar/Wind Harmer
0.477
3148463FAIRFLD
Solar/Wind Harmer
0.06
3151881LOWMORC
Adder
0.64
3151881LOWMORC
Adder
0.63
3151861LOWMORA
Adder
0.62
960921AF2-383 GEN
Solar/Wind Helper
0.279
205943AE1-185 GEN
Solar/Wind Helper
0.387
205956AE1-196_GEN
Solar/Wind Helper
0.385
205932AD2-116_GEN
Solar/Wind Helper
0.385
959381AF2-229 GEN
Solar/Wind Helper
0.257
237085AD2-009_GEN
Solar/Wind Helper
0.97
203975AE1-071-GEN
Solar/Wind Helper
1.713
233935AB2-179 C
Solar/Wind Helper
0.772
232436AB1-176 C
Solar/Wind Helper
0.027
233923SMA
Solar/Wind Helper
0.575
233990AG1-397 GEN
Solar/Wind Helper
0.162
232432Z2-076 GEN
Solar/Wind Helper
0.04
234033AF1-007_GEN
Solar/Wind Helper
4.208
964001AG1-254 GEN
Solar/Wind Helper
0.565
219914AD2-027 C
Solar/Wind Helper
0.068
227927V4-067C
Solar/Wind Helper
0.006
228754AB1-001 C
Solar/Wind Helper
0.015
219272CLEANLIGHT C
Solar/Wind Helper
0.015
219688LUMSOLAR_S C
Solar/Wind Helper
0.023
219607WPEMNERT C
Solar/Wind Helper
0.047
214067T20SOLAR
Solar/Wind Helper
0.007
20715728PEM_W1-119
Solar/Wind Helper
0.056
20715828PEM_W1-120
Solar/Wind Helper
0.056
207459AE1-142 C O1
Solar/Wind Helper
0.169
219620RIDERU C
Solar/Wind Helper
0.001
20675528CPH_W2-050
Solar/Wind Helper
0.05
218526CNTRALGAS2 C
Solar/Wind Helper
0.093
218524CNTRALGAS1 C
Solar/Wind Helper
0.093
966261AG1-495 GEN
Solar/Wind Helper
0.047
20675928HOL_W4-097
Solar/Wind Helper
0.029
207530AG1-191 GEN
Solar/Wind Helper
0.038
207484AF2-139 C O1
Solar/Wind Helper
0.048
20676328BVR_Y1-020
Solar/Wind Helper
0.015
20674828DL_W4-046
Solar/Wind Helper
0.004
207408W3-077 C
Solar/Wind Helper
0.048
20675728RH_W2-091
Solar/Wind Helper
0.078
20675128HRM_W1-127
Solar/Wind Helper
0.017
209116AE2-175 GEN
Solar/Wind Helper
1.004
961261AF2-417 GEN
Solar/Wind Helper
0.241
959431AF2-234 GEN
Solar/Wind Helper
0.466
964051AG1-259 GEN
Solar/Wind Helper
0.035
964061AG1-260 GEN
Solar/Wind Helper
0.035
959421AF2-233 GEN
Solar/Wind Helper
0.233
238208AF1-136 C
Solar/Wind Helper
0.089
20671828STAW2-080
Solar/Wind Helper
0.015
217081WEATEXAS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.004
217204WCALDSOLAR C
Solar/Wind Helper
0.002
207471AF2-354 C
Solar/Wind Helper
0.097
20674928WA_W3-044
Solar/Wind Helper
0.056
964851AG1-348 GEN
Solar/Wind Helper
0.046
20674128FR_U2-059
Solar/Wind Helper
0.002
20676228FRD_X1-012
Solar/Wind Helper
0.052
966111AG1-480 GEN
Solar/Wind Helper
0.042
211065PSPA IPP
Solar/Wind Helper
0.085
211065PSPA IPP
Solar/Wind Helper
0.085
208972BECR K09
Solar/Wind Helper
0.178
961431AF2-434 GEN
Solar/Wind Helper
0.236
209029WAYMART-WD
Solar/Wind Helper
0.443
209054AE2-059 GEN
Solar/Wind Helper
0.042
946751AF1-339 GEN
Solar/Wind Helper
0.233
209137AF2-361 C
Solar/Wind Helper
0.708
315683AE1-153 C
Solar/Wind Harmer
7.218
3147666LOUISA
Solar/Wind Harmer
0.355
316192AB2-158 GEN
Solar/Wind Harmer
0.501
316337AD2-073 GEN
Solar/Wind Harmer
0.077
3150351NORNECKC2
Adder
0.87
3141726DUNNSVL
Solar/Wind Harmer
0.348
962861AG1-135 GEN
Solar/Wind Harmer
2.764
3151751LOISA D
Adder
5.599
3138133OCRAN
Solar/Wind Harmer
0.051
3142416OLDCHRC
Solar/Wind Harmer
0.22
3142416OLDCHRC
Solar/Wind Harmer
0.084
3141766HARMONY
Solar/Wind Harmer
0.017
971777AH1-397 GEN
Solar/Wind Harmer
0.223
3141843SHACKLE
Adder
0.432
3142433PROV 92
Solar/Wind Harmer
0.337
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
3143096IRON208
Adder
0.351
3143526WINTERP
Solar/Wind Harmer
0.435
3142543TWELFTH
Solar/Wind Harmer
0.008
3150851SPRUNCC
Adder
0.385
944631AF1-128 GEN
Adder
39.853
3143226MDLTHAN
Solar/Wind Harmer
0.083
316159AE1-175 C
Solar/Wind Harmer
0.072
971317AH1-138 GEN
Solar/Wind Harmer
0.618
970129AG2-093 GEN
Solar/Wind Harmer
2.345
316458AB2-190 GEN2
Solar/Wind Harmer
0.442
315671AE2-027_GEN
Solar/Wind Harmer
5.273
3138126ROCKLANDING
Solar/Wind Harmer
0.038
971069AG2-661 GEN
Solar/Wind Harmer
1.462
971647AH1-324 GEN
Solar/Wind Harmer
3.497
961611AG1-000B GEN
Solar/Wind Harmer
4.29
3151171GRAVELC
Adder
0.868
3145336SMITFLD
Solar/Wind Harmer
0.325
316294AC1-161 GEN
Solar/Wind Harmer
1.405
970659AG2-427 GEN
Solar/Wind Harmer
3.913
316381AD1-082 GEN
Solar/Wind Harmer
0.084
316375AC2-012 GEN
Solar/Wind Harmer
0.002
970661AG2-428 GEN
Solar/Wind Harmer
8.025
3150981CHESPKA
Adder
1.007
944591AF1-124 GEN
Solar/Wind Harmer
18.213
316072AD1-144
Solar/Wind Harmer
0.029
316388AE2-253 GEN
Solar/Wind Harmer
0.251
3146456SLIGO L269
Solar/Wind Harmer
0.08
939411AE1-173 GEN
Solar/Wind Harmer
34.166
316246AF1-032 C
Solar/Wind Harmer
0.036
940641AE2-051 GEN
Solar/Wind Harmer
6.396
316093AE2-104_GEN
Solar/Wind Harmer
1.342
3143336POWHATN
Solar/Wind Harmer
1.412
3146516WINFALL
Solar/Wind Harmer
0.256
3146516WINFALL
Solar/Wind Harmer
0.079
316336AC2-165 C
Solar/Wind Harmer
0.003
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.078
3145663CRESWEL
Solar/Wind Harmer
0.215
971163AH1-040 GEN
Solar/Wind Harmer
6.133
970937AG2-583 GEN
Solar/Wind Harmer
4.64
3146206CASHIE
Solar/Wind Harmer
0.075
971547AH1-271 GEN
Solar/Wind Harmer
1.606
316023GEN1_S
Solar/Wind Harmer
0.169
3145893MURPHYS
Solar/Wind Harmer
0.301
3145893MURPHYS
Solar/Wind Harmer
0.334
970919AG2-571 GEN
Solar/Wind Harmer
2.672
970087AG2-069 GEN
Solar/Wind Harmer
5.999
3146173TUNIS
Solar/Wind Harmer
0.075
960081AF2-299 GEN
Solar/Wind Harmer
0.714
3145683EARLEYS
Solar/Wind Harmer
0.074
957481AF2-042 GEN
Solar/Wind Harmer
19.771
3146263WOODLND
Solar/Wind Harmer
0.074
315693AD1-088 GEN
Solar/Wind Harmer
3.545
962491AG1-098 GEN
Solar/Wind Harmer
4.214
971795AH1-408 GEN
Solar/Wind Harmer
4.913
3145963POPLR C
Solar/Wind Harmer
0.074
316011AB1-132 GEN
Solar/Wind Harmer
1.337
962571AG1-106 GEN
Solar/Wind Harmer
1.046
316190AA2-174 GEN
Solar/Wind Harmer
0
3145823KELFORD
Solar/Wind Harmer
0.073
3147043LAWRENC
Adder
0.664
972003AH1-546 GEN
Solar/Wind Harmer
3.117
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.029
3146926FARMVIL
Solar/Wind Harmer
0.044
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3145783HORNRTN
Solar/Wind Harmer
0.073
3145796HORNRTN
Solar/Wind Harmer
0.24
3145796HORNRTN
Solar/Wind Harmer
0.073
963171AG1-166 GEN
Solar/Wind Harmer
0.385
971563AH1-280 GEN
Solar/Wind Harmer
0.77
3144293JTRSVLE
Adder
0.23
316212AC1-099_GEN
Solar/Wind Harmer
0.372
970685AG2-442 GEN
Solar/Wind Harmer
5.37
972277AH1-723 GEN
Adder
42.854
3146293MARTNCO
Solar/Wind Harmer
0.067
316129AC1-054 GEN
Solar/Wind Harmer
0.27
971377AH1-170 GEN
Solar/Wind Harmer
0.763
3147623JAMES R
Solar/Wind Harmer
0.166
971065AG2-659 GEN
Solar/Wind Harmer
3.053
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315722AD1-056 GEN
Solar/Wind Harmer
0.448
315687AD1-152 GEN
Solar/Wind Harmer
0.002
316494AC1-189 GEN
Solar/Wind Harmer
0.238
3146233WITAKRS
Solar/Wind Harmer
0.278
961671AG1-007 GEN
Solar/Wind Harmer
0.011
3146083TARBORO
Solar/Wind Harmer
0.07
3152111X4-039 GT1
50/50
1.838
315747AE2-019 GEN
50/50
13.176
3150021OMF B
50/50
0.216
3150101POSSM6S
50/50
1.296
3150081POSSM6A
50/50
0.848
3150151POSSMC1
50/50
1.143
3150151POSSMC1
50/50
1.143
3150231REMNGT3
50/50
14.281
3150241REMNGT4
50/50
13.316
972217AH1-693 GEN
50/50
1.756
963691AG1-221 GEN
Solar/Wind Harmer
2.312
971455AH1-223 GEN
Solar/Wind Harmer
2.312
3141196NOKESVL
Solar/Wind Harmer
0.429
972199AH1-684 GEN
Adder
1.903
3150301M RUN C
Adder
13.349
3150291M RUN B
Adder
13.25
3150331BIRCHWDA
Adder
16.626
3141316ARNOLDS
Adder
0.229
316044AC1-158 PL1
Solar/Wind Harmer
0.461
316450AC1-158 RIC
Solar/Wind Harmer
0.123
3150401LDYSMT4
Adder
12.678
3150371LDYSMT1
Adder
12.251
316170AC1-121 GEN2
Solar/Wind Harmer
0.1
970737AG2-469 GEN
Solar/Wind Harmer
3.872
3141906WESTMOR
Solar/Wind Harmer
0.036
3132273ORANGE
Solar/Wind Harmer
0.018
971781AH1-399 GEN
Solar/Wind Harmer
0.118
3147666LOUISA
Solar/Wind Harmer
0.204
3150351NORNECKC2
Adder
0.884
316404AE1-155 C
Solar/Wind Harmer
0.019
3151761LOISA E
Adder
11.415
972183AH1-676 GEN
Adder
92.045
970009AG2-005 GEN
Solar/Wind Harmer
0.643
316473AC1-191 GEN
Solar/Wind Harmer
0.29
962971AG1-146 GEN
Solar/Wind Harmer
1.373
3142416OLDCHRC
Solar/Wind Harmer
0.821
3141766HARMONY
Solar/Wind Harmer
1.129
316156AD2-030 GEN
Solar/Wind Harmer
0.063
3141873WAN 176
Solar/Wind Harmer
1.505
316280AD1-041 GEN
Solar/Wind Harmer
0.002
316203AE2-005 GEN
Solar/Wind Harmer
0
3141843SHACKLE
Adder
0.432
970293AG2-193 GEN
Solar/Wind Harmer
0.899
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
3143096IRON208
Adder
0.351
3143096IRON208
Adder
0.344
3142946ENON
Solar/Wind Harmer
0.028
3150861SPRUNCD
Adder
0.385
316382AG1-145 C
Solar/Wind Harmer
0.001
970133AG2-095 GEN
Solar/Wind Harmer
0.794
970129AG2-093 GEN
Solar/Wind Harmer
4.984
3150921YORKTN3
Adder
2.069
315778AD1-151 GEN
Solar/Wind Harmer
6.579
965281AG1-393 GEN
Solar/Wind Harmer
0.877
3144216WINCHST
Adder
0.31
315839AE2-212 C
Solar/Wind Harmer
0.001
961611AG1-000B GEN
Solar/Wind Harmer
2.181
3151221GRAVEL6
Adder
5.934
3151171GRAVELC
Adder
1.142
3145336SMITFLD
Solar/Wind Harmer
0.033
315813AE1-149 C
Solar/Wind Harmer
4.334
315773AC2-141 GEN
Solar/Wind Harmer
2.962
970659AG2-427 GEN
Solar/Wind Harmer
0.856
316083AB2-161 GEN
Solar/Wind Harmer
0.001
3144536CHRHLND
Solar/Wind Harmer
0.012
3151101ELIZAR3
Adder
7.489
970661AG2-428 GEN
Solar/Wind Harmer
1.707
3144873MCLAUGH
Solar/Wind Harmer
0.002
944581AF1-123 GEN
Solar/Wind Harmer
18.149
944601AF1-125 GEN
Solar/Wind Harmer
17.869
3146456SLIGO L269
Solar/Wind Harmer
0.08
971153AH1-033 GEN
Solar/Wind Harmer
0.925
316320Y1-086
Solar/Wind Harmer
0
316313AB2-026
Solar/Wind Harmer
0.05
316258AE1-075 C
Solar/Wind Harmer
0.06
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
1.2
316435W1029_GEN3
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.079
3146626S HERTFORD
Solar/Wind Harmer
0.079
3145273HOLLAND
Solar/Wind Harmer
0.059
3146376EDENTON
Solar/Wind Harmer
0.078
315614AA2-178 GEN
Solar/Wind Harmer
0.439
971157AH1-035 GEN
Solar/Wind Harmer
0.911
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
315737AD1-076 GEN
Solar/Wind Harmer
0.975
3146206CASHIE
Solar/Wind Harmer
0.075
316365GEN2_N
Solar/Wind Harmer
0.169
3145893MURPHYS
Solar/Wind Harmer
0.126
3145893MURPHYS
Solar/Wind Harmer
0.075
970917AG2-570 GEN
Solar/Wind Harmer
6.681
957521AF2-046 GEN
Solar/Wind Harmer
5.587
961681AG1-008 GEN
Solar/Wind Harmer
5.587
3146173TUNIS
Solar/Wind Harmer
0.075
3156021HOLLOMANSOL
Solar/Wind Harmer
0.339
316463AE2-346 GEN
Solar/Wind Harmer
0.064
316140AB2-099
Solar/Wind Harmer
0.027
962331AG1-082 GEN
Solar/Wind Harmer
0.795
3146263WOODLND
Solar/Wind Harmer
0.074
313506AB2-031 GEN
Solar/Wind Harmer
0.228
3142666NORTHAMPTON
Solar/Wind Harmer
0.074
3145963POPLR C
Solar/Wind Harmer
0.074
970909AG2-566 GEN
Solar/Wind Harmer
0.785
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.073
3147043LAWRENC
Solar/Wind Harmer
0.044
3146776BUCKING
Solar/Wind Harmer
0.026
3146926FARMVIL
Solar/Wind Harmer
0.044
3145796HORNRTN
Solar/Wind Harmer
0.291
3145796HORNRTN
Solar/Wind Harmer
0.073
942461AE2-259 GEN
Solar/Wind Harmer
0
316478AD1-087 GEN
Solar/Wind Harmer
0.254
316486AD2-202 GEN
Solar/Wind Harmer
0.075
3147133PAMPLIN
Solar/Wind Harmer
0.227
971193AH1-056 GEN
Solar/Wind Harmer
4.404
963181AG1-167 GEN
Solar/Wind Harmer
0.289
3144293JTRSVLE
Adder
0.23
316210AC1-098 GEN
Solar/Wind Harmer
0.668
972255AH1-712 GEN
Adder
36.775
3145933PARMELE
Solar/Wind Harmer
0.072
966801AG1-551 GEN
Solar/Wind Harmer
0.836
959311AF2-222 GEN
Solar/Wind Harmer
6.376
970257AG2-171 GEN
Solar/Wind Harmer
2.293
970221AG2-151 GEN
Solar/Wind Harmer
3.817
315785AD2-033 C
Solar/Wind Harmer
0.582
964241AG1-285 GEN
Solar/Wind Harmer
4.753
316131AB2-060 GEN
Solar/Wind Harmer
0.224
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
315724AD1-057 GEN
Solar/Wind Harmer
0.266
316327AA2-057 GEN
Solar/Wind Harmer
0.106
3146233WITAKRS
Solar/Wind Harmer
0.35
3146233WITAKRS
Solar/Wind Harmer
0.047
3146073TAR RVR
Solar/Wind Harmer
0.07
3146083TARBORO
Solar/Wind Harmer
0.07
3138543CONSLDL
Solar/Wind Harmer
0.046
3145543BTLEBRO
Solar/Wind Harmer
0.069
3145543BTLEBRO
Solar/Wind Harmer
0.069
961601AG1-000A GEN
Solar/Wind Harmer
4.912
971623AH1-311 GEN
Solar/Wind Harmer
0.138
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
2.87
971683AH1-343 GEN
Solar/Wind Harmer
2.391
3148013FISHERV
Solar/Wind Harmer
0.065
316283AC2-100 C
Solar/Wind Harmer
0.124
315616AA1-038_C
Solar/Wind Harmer
0
3151861LOWMORA
Adder
0.645
958131AF2-107 GEN
Solar/Wind Harmer
1.618
226910AB2-157 C
Solar/Wind Helper
0.02
227287AC2-120 GEN
Solar/Wind Helper
0.49
237030AB1-096 C
Solar/Wind Helper
0.083
223402AF1-300 C
Solar/Wind Helper
0.397
205917AD1-020 ES
Solar/Wind Helper
0.318
238221AF1-254 C O1
Solar/Wind Helper
0.179
235067AD1-061 GEN
Solar/Wind Helper
0.312
233982AB2-133 GEN
Solar/Wind Helper
0.216
233918AB1-142 GEN
Solar/Wind Helper
0.303
233994AC2-023 GEN
Solar/Wind Helper
0.577
233996TM1833_GEN
Solar/Wind Helper
0.157
233997TMININ_4.2
Solar/Wind Helper
0.157
233940AF2-379 C
Solar/Wind Helper
0.037
234015AF2-250 C
Solar/Wind Helper
0.023
233952AC2-187 GEN
Solar/Wind Helper
0.139
232406W1-004 FULL
Solar/Wind Helper
0.304
233971AC1-093 C
Solar/Wind Helper
0.214
230430AE1-229_GEN
Solar/Wind Helper
1.995
230415AB2-049 C
Solar/Wind Helper
0.018
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219766PARADISE C
Solar/Wind Helper
0.032
219912AD2-042 GEN
Solar/Wind Helper
0.089
228729W2-030 C
Solar/Wind Helper
0.065
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.007
219906AC1-017 C
Solar/Wind Helper
0.025
219348LDSOLAR C
Solar/Wind Helper
0.067
959561AF2-247 GEN
Solar/Wind Helper
0.012
20716028EGP_W2-019
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.037
20715028HAN_X4-015
Solar/Wind Helper
0.033
219276PARKLANDSO C
Solar/Wind Helper
0.052
20714528FRN_Y2-051
Solar/Wind Helper
0.033
20720528MAN_W1-024
Solar/Wind Helper
0.016
219612MATRIX C
Solar/Wind Helper
0.014
218438BLK ROCK C
Solar/Wind Helper
0.016
20673728F2S_V4-070
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.043
219919AE1-041 FULL
Solar/Wind Helper
0.002
219249CENTRALDIV C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
217169METRODIV C
Solar/Wind Helper
0.002
20676728BRNX1-095
Solar/Wind Helper
0.017
207510AF2-138 C
Solar/Wind Helper
0.046
20674628WNG_W3-110
Solar/Wind Helper
0.051
963161AG1-165 GEN
Solar/Wind Helper
0.242
963071AG1-156 GEN
Solar/Wind Helper
0.783
209027LOR2_Q27
Solar/Wind Helper
0.557
961331AF2-424 GEN
Solar/Wind Helper
0.237
961421AF2-433 GEN
Solar/Wind Helper
0.236
957921AF2-086 GEN
Solar/Wind Helper
0.234
946691AF1-333 GEN
Solar/Wind Helper
0.233
946741AF1-338 GEN
Solar/Wind Helper
0.233
209067AE2-060 GEN
Solar/Wind Helper
0.042
3145493TOT1
Solar/Wind Harmer
0.31
316359AB2-059 GEN
Solar/Wind Harmer
0.248
316049AB1-081 GEN
Solar/Wind Harmer
0.395
3145543BTLEBRO
Solar/Wind Harmer
0.069
3145543BTLEBRO
Solar/Wind Harmer
0.055
3142053HEARTS
Solar/Wind Harmer
0.122
970401AG2-262 GEN
Solar/Wind Harmer
0.404
316003AC1-222 GEN
Solar/Wind Harmer
0.002
315705AF1-075 GEN
Solar/Wind Harmer
2.472
3147983MERCK5
Solar/Wind Harmer
0.024
23779801AA1-109
Solar/Wind Helper
0.218
223401AF1-299 GEN
Solar/Wind Helper
0.397
966131AG1-482 GEN
Solar/Wind Helper
0.111
237080AD1-060 GEN
Solar/Wind Helper
0.221
235062AE1-101 C1
Solar/Wind Helper
1.064
237038AE2-054 C
Solar/Wind Helper
0.173
233930AB2-032 GEN
Solar/Wind Helper
0.23
233915AB1-141 GEN
Solar/Wind Helper
0.303
232422X3-066 FULL
Solar/Wind Helper
0.069
233964AF2-378 GEN
Solar/Wind Helper
0.025
232426Y1-080 FULL
Solar/Wind Helper
0.023
233998TM1NIN_3.36
Solar/Wind Helper
0.157
232428Y3-058 C
Solar/Wind Helper
0.203
233954AC2-188 GEN
Solar/Wind Helper
0.139
232404W1-003 C
Solar/Wind Helper
0.304
233950AC2-186 GEN
Solar/Wind Helper
0.07
232434Z2-077 GEN
Solar/Wind Helper
0.076
233972AC1-094 C
Solar/Wind Helper
0.181
205941AD2-115 GEN
Solar/Wind Helper
0.302
230434AG1-499 GEN
Solar/Wind Helper
0.136
230511AF1-262
Solar/Wind Helper
0.009
219258KINSLEYDEP C
Solar/Wind Helper
0.045
228728W1-130C
Solar/Wind Helper
0.032
219904AC1-010 C
Solar/Wind Helper
0.036
219907AC1-030 C
Solar/Wind Helper
0.02
218660EHAMPSOLAR C
Solar/Wind Helper
0.019
219686LUMSOLAR_N C
Solar/Wind Helper
0.023
219304NAMERICA C
Solar/Wind Helper
0.077
20720728JCB_W1-129
Solar/Wind Helper
0.033
207445AB1-138_GEN
Solar/Wind Helper
0.061
963711AG1-223 GEN
Solar/Wind Helper
0.037
20714828MDF_W3-079
Solar/Wind Helper
0.076
219680HOPEWELLV C1
Solar/Wind Helper
0.002
207454AA2-184 E
Solar/Wind Helper
0.18
20715228NPK_W1-113
Solar/Wind Helper
0.045
20742028HF_AC1-207
Solar/Wind Helper
0.082
207528AF2-192 GEN
Solar/Wind Helper
0.044
20673628F1S_V4-069
Solar/Wind Helper
0.017
20675428EAM_W2-061
Solar/Wind Helper
0.009
218428ETC SOLAR C
Solar/Wind Helper
0.003
20676428JCR_X2-075
Solar/Wind Helper
0.039
217213AMBOY SO C
Solar/Wind Helper
0.017
217209CENTRL HS C
Solar/Wind Helper
0.005
217208PARK ELE C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.013
207437AD2-070 GEN
Solar/Wind Helper
0.079
207439AE1-081 C O1
Solar/Wind Helper
0.011
207518AF1-320_GEN
Solar/Wind Helper
0.9
20671928W4-073
Solar/Wind Helper
0.051
20675828AU_W4-064
Solar/Wind Helper
0.017
961301AF2-421 GEN
Solar/Wind Helper
0.242
963151AG1-164 GEN
Solar/Wind Helper
0.242
212266LOR1
Solar/Wind Helper
0.026
961341AF2-425 GEN
Solar/Wind Helper
0.237
212507AE2-042_GEN
Solar/Wind Helper
0.829
946731AF1-337 GEN
Solar/Wind Helper
0.233
209071AE2-133 GEN
Solar/Wind Helper
0.042
NYPJM->LTFIMP_NY
CLTF
2.575
LGEELTFEXP_LGEE->PJM
CLTF
1.805
WECLTFEXP_WEC->PJM
CLTF
0.962
LAGNLTFEXP_LAGN->PJM
CLTF
6.324
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.565
TVALTFEXP_TVA->PJM
CLTF
3.188
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.485
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.592
MECLTFEXP_MEC->PJM
CLTF
4.449
SIGELTFEXP_SIGE->PJM
CLTF
0.14
CPLELTFEXP_CPLE->PJM
CLTF
5.065
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.965

Details for 6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T560_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T560_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.42 %
Rating:1809.0 MVA
Rating Type:C
MVA to Mitigate:2124.15
MW Contribution:42.84
Bus #Bus NameTypeMW Contribution
972289AH1-729 GEN
50/50
13.252
3150071POSSM 5
Adder
49.581
3150181POSSMC2
Adder
1.094
3150181POSSMC2
Adder
1.085
3150181POSSMC2
Adder
1.085
316447AC1-158 HLD
Solar/Wind Harmer
2.295
3150391LDYSMT3
Adder
12.669
972195AH1-682 GEN
Adder
1.665
315651AD1-115 GEN
Solar/Wind Harmer
4.661
315673AE1-157 GEN
Solar/Wind Harmer
7.8
957411AF2-035 GEN
Solar/Wind Harmer
4.619
970317AG2-208 GEN
Solar/Wind Harmer
4.491
316468AD1-105 GEN
Solar/Wind Harmer
1.121
316077AC2-138 C
Solar/Wind Harmer
0.207
3150341NORNECKC1
Adder
0.915
3150341NORNECKC1
Adder
0.907
966001AG1-469 GEN
Solar/Wind Harmer
0.184
958261AF2-120 GEN
Solar/Wind Harmer
3.769
3151731LOISA B
Adder
5.598
3151721LOISA A
Adder
5.569
316487AF1-042 GEN
Solar/Wind Harmer
1.275
966871AG1-558 GEN
Solar/Wind Harmer
0.29
966871AG1-558 GEN
Solar/Wind Harmer
0.099
3142296MT RD221
Adder
0.271
316441AF1-014 GEN
Solar/Wind Harmer
0.641
3142366NRTHEST
Adder
0.276
3150691DARBY 3
Adder
6.069
3150701DARBY 4
Adder
6.055
3150681DARBY 2
Adder
6.048
3150671DARBY 1
Adder
6.041
316075AC2-137 C
Solar/Wind Harmer
0.255
3142946ENON
Solar/Wind Harmer
-0.001
3143526WINTERP
Solar/Wind Harmer
-0.049
971223AH1-071 GEN
Solar/Wind Harmer
1.172
944641AF1-129 GEN
Adder
39.415
316240AF1-291 C
Solar/Wind Harmer
0.279
316033AB2-134 GEN
Solar/Wind Harmer
2.975
315697AD1-025 GEN
Solar/Wind Harmer
1.866
316236AE1-162_GEN
Solar/Wind Harmer
0.275
970657AG2-426 GEN
Solar/Wind Harmer
2.837
970657AG2-426 GEN
Solar/Wind Harmer
0.593
316036AC1-147 C
Solar/Wind Harmer
0.244
3150991CHESPKB
Adder
0.845
3150991CHESPKB
Adder
0.825
3142956BIRDNECK
Solar/Wind Harmer
0.486
316316AC1-027 C
Solar/Wind Harmer
0.278
316185AD1-033 GEN
Solar/Wind Harmer
0.954
3145506HICKORY
Solar/Wind Harmer
-0.036
3145506HICKORY
Solar/Wind Harmer
-0.022
3145506HICKORY
Solar/Wind Harmer
-0.005
316339AD2-160 GEN
Solar/Wind Harmer
0.608
316018AA1-139 ULT2
Solar/Wind Harmer
0.771
316017AA1-139 ULT1
Solar/Wind Harmer
0.729
3137176SLIGO L2192
Solar/Wind Harmer
-0.036
3146456SLIGO L269
Solar/Wind Harmer
1.062
3130086AYDLETT
Solar/Wind Harmer
-0.036
3146386ELIZ CT
Solar/Wind Harmer
-0.009
316431W1029_GEN1
Solar/Wind Harmer
1.61
316433W1029_GEN2
Solar/Wind Harmer
1.61
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3144356SAPONY
Solar/Wind Harmer
0.308
315742AE1-103 GEN
Solar/Wind Harmer
0.916
3146376EDENTON
Solar/Wind Harmer
0.259
3146376EDENTON
Solar/Wind Harmer
0.259
972185AH1-677 GEN
Adder
4.33
972187AH1-678 GEN
Adder
2.184
970933AG2-581 GEN
Solar/Wind Harmer
8.04
316065AD1-022 GEN
Solar/Wind Harmer
4.239
3145893MURPHYS
Solar/Wind Harmer
0.236
3145893MURPHYS
Solar/Wind Harmer
-0.015
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
970099AG2-077 GEN
Solar/Wind Harmer
10.411
316181AB2-040 GEN
Solar/Wind Harmer
1.158
3144293JTRSVLE
Adder
0.23
3144293JTRSVLE
Adder
0.193
226929AD2-058 GEN
Solar/Wind Helper
0.143
237025AB1-124 C
Solar/Wind Helper
0.193
237006AB1-125 GEN
Solar/Wind Helper
0.145
23777801MSM_W1-116
Solar/Wind Helper
0.13
237034AC2-136 C
Solar/Wind Helper
0.205
205916AD1-020 GEN
Solar/Wind Helper
1.48
208835TUHI V3-051
Solar/Wind Helper
0.019
208835TUHI V3-051
Solar/Wind Helper
0.019
237001AB1-127_GEN
Solar/Wind Helper
0.307
237002AB1-128_GEN
Solar/Wind Helper
0.298
235063AE1-101 C2
Solar/Wind Helper
1.064
970053AG2-049 GEN
50/50
2.027
3138216PACIFIC
Solar/Wind Harmer
-0.003
316411AF1-147_GEN1
Solar/Wind Harmer
1.101
316415AF1-147_GEN2
Solar/Wind Harmer
1.101
3141426STAFORD
Solar/Wind Harmer
-0.003
3150411LDYSMT5
Adder
12.732
3150381LDYSMT2
Adder
12.185
972213AH1-691 GEN
Adder
2.061
972215AH1-692 GEN
Adder
2.061
316164AC1-076 GEN
Solar/Wind Harmer
0.887
944491AF1-114 GEN
Solar/Wind Harmer
3.051
316223AC1-118
Solar/Wind Harmer
0.272
972189AH1-679 GEN
Adder
1.468
3141813NORNECK
Solar/Wind Harmer
-0.01
962981AG1-147 GEN
Solar/Wind Harmer
4.221
3141783LANCAST
Solar/Wind Harmer
-0.006
3141783LANCAST
Solar/Wind Harmer
-0.004
3138133OCRAN
Solar/Wind Harmer
-0.003
3141913WHIT STONE
Solar/Wind Harmer
-0.01
316312AB1-027
Solar/Wind Harmer
0.321
3147346CASHSCORNER
Solar/Wind Harmer
0.147
316314AB2-024 C
Solar/Wind Harmer
0.813
316059AD1-063 C
Solar/Wind Harmer
0.215
957601AF2-054 GEN
Solar/Wind Harmer
0.285
3141873WAN 176
Solar/Wind Harmer
-0.002
315662AE1-191 GEN
Solar/Wind Harmer
1.146
315666AE1-190 GEN
Solar/Wind Harmer
0.287
3143873LANEXA
Solar/Wind Harmer
-0.006
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
971167AH1-042 GEN
Solar/Wind Harmer
9.109
315976AC1-164 GENA
Solar/Wind Harmer
9.985
316169AC1-164_GENC
Solar/Wind Harmer
8.626
315975AC1-164 GENB
Solar/Wind Harmer
0.295
316233AE1-074 FULL
Solar/Wind Harmer
0.253
971281AH1-106 GEN
Solar/Wind Harmer
1.528
971283AH1-107 GEN
Solar/Wind Harmer
1.528
971285AH1-108 GEN
Adder
0.631
957831AF2-077 GEN
Solar/Wind Harmer
0.282
3138283WHITEMARSH
Solar/Wind Harmer
0.015
316132AB2-190 GEN1
Solar/Wind Harmer
0.937
316369SG1_INVT
Solar/Wind Harmer
1.648
972265AH1-717 GEN
Adder
6.337
3151201GRAVEL4
Adder
5.94
3151191GRAVEL3
Adder
5.865
3151211GRAVEL5
Adder
5.865
971445AH1-216 GEN
Solar/Wind Harmer
5.652
3143316POE
Solar/Wind Harmer
-0.036
3151081ELIZAR1
Adder
7.394
3151091ELIZAR2
Adder
7.266
3152611GOSPORTB
Adder
1.027
3152621GOSPORTC
Adder
0.872
3152601GOSPORTA
Adder
0.804
315833AF1-017_GEN
Solar/Wind Harmer
1.712
316349AD2-085 GEN
Solar/Wind Harmer
0.802
316311AC2-079 GEN
Solar/Wind Harmer
4.545
957871AF2-081 GEN
Solar/Wind Harmer
4.503
316305AF2-043 C
Solar/Wind Harmer
0.271
319010AE1-072 C
Solar/Wind Harmer
1.819
3146406KITTY HAWK
Solar/Wind Harmer
0.007
315835AF2-110_GEN
Solar/Wind Harmer
1.121
313526AB2-022
Solar/Wind Harmer
0.241
3146486SUNBURY
Solar/Wind Harmer
-0.009
3146486SUNBURY
Solar/Wind Harmer
-0.009
3152111X4-039 GT1
50/50
1.839
315747AE2-019 GEN
50/50
13.179
963691AG1-221 GEN
Solar/Wind Harmer
2.313
971455AH1-223 GEN
Solar/Wind Harmer
2.313
3150151POSSMC1
Adder
1.085
3150151POSSMC1
Adder
1.085
3141196NOKESVL
Solar/Wind Harmer
-0.048
3150231REMNGT3
Adder
13.456
3150241REMNGT4
Adder
12.546
972199AH1-684 GEN
Adder
1.902
972217AH1-693 GEN
Adder
1.654
3150301M RUN C
Adder
13.346
3150291M RUN B
Adder
13.247
3150331BIRCHWDA
Adder
16.693
3141316ARNOLDS
Adder
0.23
316044AC1-158 PL1
Solar/Wind Harmer
1.043
316450AC1-158 RIC
Solar/Wind Harmer
0.278
3150401LDYSMT4
Adder
12.692
3150371LDYSMT1
Adder
12.264
316170AC1-121 GEN2
Solar/Wind Harmer
0.283
966881AG1-559 GEN
Solar/Wind Harmer
0.309
970737AG2-469 GEN
Solar/Wind Harmer
5.11
3141906WESTMOR
Solar/Wind Harmer
-0.004
3132273ORANGE
Solar/Wind Harmer
-0.002
971781AH1-399 GEN
Solar/Wind Harmer
0.62
3147666LOUISA
Solar/Wind Harmer
-0.023
3150351NORNECKC2
Adder
0.885
316404AE1-155 C
Solar/Wind Harmer
1.876
3151761LOISA E
Adder
11.412
316484AD2-074 GEN
Solar/Wind Harmer
2.436
970009AG2-005 GEN
Solar/Wind Harmer
1.21
972183AH1-676 GEN
Adder
92.015
316473AC1-191 GEN
Solar/Wind Harmer
1.04
962971AG1-146 GEN
Solar/Wind Harmer
1.809
3142416OLDCHRC
Solar/Wind Harmer
0.961
3152131X4-039 ST
50/50
2.893
3152121X4-039 GT2
50/50
1.833
3140676OCCOQUN
Adder
0.27
972223AH1-696 GEN
Adder
8.569
3150151POSSMC1
Adder
1.085
3141346CRANES
Adder
0.12
3150221REMNGT2
Adder
12.463
3150211REMNGT1
Adder
12.381
972201AH1-685 GEN
Adder
2.15
3150281M RUN A
Adder
13.354
316006AB2-029 C
Solar/Wind Harmer
0.631
971685AH1-345 GEN
Solar/Wind Harmer
0.961
316045AC1-158 PL2
Solar/Wind Harmer
3.338
972197AH1-683 GEN
Adder
1.982
972219AH1-694 GEN
Adder
1.427
316254AC1-120 GEN1
Solar/Wind Harmer
0.849
957971AF2-091 GEN
Solar/Wind Harmer
1.037
972135AH1-637 GEN
Solar/Wind Harmer
1.031
966881AG1-559 GEN
Solar/Wind Harmer
0.106
315683AE1-153 C
Solar/Wind Harmer
9.501
3147666LOUISA
Solar/Wind Harmer
-0.04
316192AB2-158 GEN
Solar/Wind Harmer
1.185
316337AD2-073 GEN
Solar/Wind Harmer
0.267
3150351NORNECKC2
Adder
0.871
964211AG1-282 GEN
Solar/Wind Harmer
0.294
3141726DUNNSVL
Solar/Wind Harmer
-0.039
962861AG1-135 GEN
Solar/Wind Harmer
3.642
3151751LOISA D
Adder
5.598
961951AG1-038 GEN
Solar/Wind Harmer
1.275
3138133OCRAN
Solar/Wind Harmer
-0.006
3142416OLDCHRC
Solar/Wind Harmer
-0.025
3142416OLDCHRC
Solar/Wind Harmer
-0.009
3141766HARMONY
Solar/Wind Harmer
-0.002
971777AH1-397 GEN
Solar/Wind Harmer
1.118
3141843SHACKLE
Adder
0.432
3142433PROV 92
Solar/Wind Harmer
-0.038
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
3143096IRON208
Adder
0.351
3143526WINTERP
Solar/Wind Harmer
-0.049
3142543TWELFTH
Solar/Wind Harmer
-0.001
3150851SPRUNCC
Adder
0.385
944631AF1-128 GEN
Adder
39.856
3143226MDLTHAN
Solar/Wind Harmer
-0.009
316159AE1-175 C
Solar/Wind Harmer
0.25
971317AH1-138 GEN
Solar/Wind Harmer
1.163
970129AG2-093 GEN
Solar/Wind Harmer
2.113
316458AB2-190 GEN2
Solar/Wind Harmer
0.937
315671AE2-027_GEN
Solar/Wind Harmer
6.943
3138126ROCKLANDING
Solar/Wind Harmer
0.028
971069AG2-661 GEN
Solar/Wind Harmer
1.462
971647AH1-324 GEN
Solar/Wind Harmer
4.604
961611AG1-000B GEN
Solar/Wind Harmer
4.536
3151171GRAVELC
Adder
0.868
3145336SMITFLD
Solar/Wind Harmer
-0.036
316294AC1-161 GEN
Solar/Wind Harmer
2.948
970659AG2-427 GEN
Solar/Wind Harmer
4.83
316381AD1-082 GEN
Solar/Wind Harmer
0.833
316375AC2-012 GEN
Solar/Wind Harmer
3.136
3150981CHESPKA
Adder
1.007
970661AG2-428 GEN
Solar/Wind Harmer
9.631
944591AF1-124 GEN
Solar/Wind Harmer
41.344
316072AD1-144
Solar/Wind Harmer
0.183
316388AE2-253 GEN
Solar/Wind Harmer
0.608
3146456SLIGO L269
Solar/Wind Harmer
-0.009
939411AE1-173 GEN
Solar/Wind Harmer
44.981
316246AF1-032 C
Solar/Wind Harmer
0.182
940641AE2-051 GEN
Solar/Wind Harmer
8.42
316093AE2-104_GEN
Solar/Wind Harmer
2.607
3143336POWHATN
Solar/Wind Harmer
1.059
3146516WINFALL
Solar/Wind Harmer
-0.029
3146516WINFALL
Solar/Wind Harmer
-0.009
316336AC2-165 C
Solar/Wind Harmer
1.53
315800Z1-036_GEN1
Solar/Wind Harmer
2.172
3130156CHOWAN
Solar/Wind Harmer
-0.009
3145663CRESWEL
Solar/Wind Harmer
-0.024
971163AH1-040 GEN
Solar/Wind Harmer
8.075
970937AG2-583 GEN
Solar/Wind Harmer
6.109
316023GEN1_S
Solar/Wind Harmer
0.57
3146206CASHIE
Solar/Wind Harmer
-0.008
971547AH1-271 GEN
Solar/Wind Harmer
2.115
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.251
970919AG2-571 GEN
Solar/Wind Harmer
2.672
970087AG2-069 GEN
Solar/Wind Harmer
7.898
3146173TUNIS
Solar/Wind Harmer
-0.008
960081AF2-299 GEN
Solar/Wind Harmer
0.94
3145683EARLEYS
Solar/Wind Harmer
-0.008
957481AF2-042 GEN
Solar/Wind Harmer
26.028
3146263WOODLND
Solar/Wind Harmer
-0.008
3147043LAWRENC
Adder
0.664
3144293JTRSVLE
Adder
0.23
972277AH1-723 GEN
Adder
42.843
23779801AA1-109
Solar/Wind Helper
0.217
223401AF1-299 GEN
Solar/Wind Helper
0.397
966131AG1-482 GEN
Solar/Wind Helper
0.063
237080AD1-060 GEN
Solar/Wind Helper
0.221
20390526W1-045 C
Solar/Wind Helper
0.252
23777901MDS_W4-102
Solar/Wind Helper
0.105
235020AA1-095 C
Solar/Wind Helper
0.029
233933AB2-153 GEN
Solar/Wind Helper
0.14
233944AB2-135 GEN
Solar/Wind Helper
0.355
232424Y1-079 C
Solar/Wind Helper
0.07
233987AB2-037 GEN
Solar/Wind Helper
1.406
234036AF2-325 C
Solar/Wind Helper
0.025
233946AB2-136 GEN
Solar/Wind Helper
0.341
233901CHERRYDALE C
Solar/Wind Helper
0.139
232408W1-005 C
Solar/Wind Helper
0.304
232410W1-006 C
Solar/Wind Helper
0.304
233939AC1-091 C
Solar/Wind Helper
0.209
233970AC1-092 C
Solar/Wind Helper
0.209
230433AD2-135 GEN
Solar/Wind Helper
0.01
219921AF1-264
Solar/Wind Helper
0.03
230407AD2-065 C
Solar/Wind Helper
0.024
219615MILLCREEK C
Solar/Wind Helper
0.016
963401AG1-189 GEN
Solar/Wind Helper
0.033
963391AG1-188 GEN
Solar/Wind Helper
0.048
20714928UPF_X1-085
Solar/Wind Helper
0.003
20720628TIN_W1-124
Solar/Wind Helper
0.11
20716928W4-060COL
Solar/Wind Helper
0.03
20673828FLE_V3-070
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.009
207442AE1-156 GEN
Solar/Wind Helper
0.188
20676128MHD_W3-029
Solar/Wind Helper
0.055
20671828STAW2-080
Solar/Wind Helper
0.015
217081WEATEXAS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.004
217204WCALDSOLAR C
Solar/Wind Helper
0.002
207471AF2-354 C
Solar/Wind Helper
0.097
20674928WA_W3-044
Solar/Wind Helper
0.056
964851AG1-348 GEN
Solar/Wind Helper
0.046
20674128FR_U2-059
Solar/Wind Helper
0.002
20676228FRD_X1-012
Solar/Wind Helper
0.052
966111AG1-480 GEN
Solar/Wind Helper
0.025
211065PSPA IPP
Solar/Wind Helper
0.085
211065PSPA IPP
Solar/Wind Helper
0.085
208972BECR K09
Solar/Wind Helper
0.178
961431AF2-434 GEN
Solar/Wind Helper
0.236
209029WAYMART-WD
Solar/Wind Helper
0.442
209054AE2-059 GEN
Solar/Wind Helper
0.042
946751AF1-339 GEN
Solar/Wind Helper
0.233
209137AF2-361 C
Solar/Wind Helper
0.708
3141766HARMONY
Solar/Wind Harmer
0.847
316156AD2-030 GEN
Solar/Wind Harmer
0.254
3141873WAN 176
Solar/Wind Harmer
1.129
316280AD1-041 GEN
Solar/Wind Harmer
0.717
316203AE2-005 GEN
Solar/Wind Harmer
4.009
3141843SHACKLE
Adder
0.432
970293AG2-193 GEN
Solar/Wind Harmer
1.184
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
3143096IRON208
Adder
0.351
3143096IRON208
Adder
0.344
3142946ENON
Solar/Wind Harmer
-0.003
3150861SPRUNCD
Adder
0.385
316382AG1-145 C
Solar/Wind Harmer
0.281
970133AG2-095 GEN
Solar/Wind Harmer
1.046
970129AG2-093 GEN
Solar/Wind Harmer
5.216
3150921YORKTN3
Adder
2.069
315778AD1-151 GEN
Solar/Wind Harmer
8.005
965281AG1-393 GEN
Solar/Wind Harmer
1.155
3144216WINCHST
Adder
0.31
315839AE2-212 C
Solar/Wind Harmer
0.278
961611AG1-000B GEN
Solar/Wind Harmer
1.935
3151221GRAVEL6
Adder
5.934
3151171GRAVELC
Adder
1.142
3145336SMITFLD
Solar/Wind Harmer
-0.004
315813AE1-149 C
Solar/Wind Harmer
5.707
315773AC2-141 GEN
Solar/Wind Harmer
3.812
970659AG2-427 GEN
Solar/Wind Harmer
0.856
316083AB2-161 GEN
Solar/Wind Harmer
1.475
3144536CHRHLND
Solar/Wind Harmer
-0.001
3151101ELIZAR3
Adder
7.489
970661AG2-428 GEN
Solar/Wind Harmer
1.707
3144873MCLAUGH
Solar/Wind Harmer
0
944581AF1-123 GEN
Solar/Wind Harmer
41.196
944601AF1-125 GEN
Solar/Wind Harmer
40.553
3146456SLIGO L269
Solar/Wind Harmer
-0.009
971153AH1-033 GEN
Solar/Wind Harmer
1.096
316320Y1-086
Solar/Wind Harmer
0.524
316313AB2-026
Solar/Wind Harmer
0.241
316258AE1-075 C
Solar/Wind Harmer
0.217
316405AF2-144 C
Solar/Wind Harmer
0.229
3143336POWHATN
Solar/Wind Harmer
0.9
316435W1029_GEN3
Solar/Wind Harmer
1.61
3146516WINFALL
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3145273HOLLAND
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.009
315614AA2-178 GEN
Solar/Wind Harmer
0.929
971157AH1-035 GEN
Solar/Wind Harmer
1.066
3156081AA2-088 GEN
Solar/Wind Harmer
2.765
315737AD1-076 GEN
Solar/Wind Harmer
1.618
316365GEN2_N
Solar/Wind Harmer
0.57
3146206CASHIE
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.059
3145893MURPHYS
Solar/Wind Harmer
-0.008
970917AG2-570 GEN
Solar/Wind Harmer
21.109
957521AF2-046 GEN
Solar/Wind Harmer
6.644
961681AG1-008 GEN
Solar/Wind Harmer
6.644
3146173TUNIS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1.13
316463AE2-346 GEN
Solar/Wind Harmer
0.136
316140AB2-099
Solar/Wind Harmer
0.056
962331AG1-082 GEN
Solar/Wind Harmer
1.047
966621AG1-532 GEN
Solar/Wind Harmer
0.17
3146263WOODLND
Solar/Wind Harmer
-0.008
313506AB2-031 GEN
Solar/Wind Harmer
0.667
3144293JTRSVLE
Adder
0.23
972255AH1-712 GEN
Adder
36.766
3151861LOWMORA
Adder
0.645
226910AB2-157 C
Solar/Wind Helper
0.02
227287AC2-120 GEN
Solar/Wind Helper
0.49
237030AB1-096 C
Solar/Wind Helper
0.083
223402AF1-300 C
Solar/Wind Helper
0.397
205917AD1-020 ES
Solar/Wind Helper
0.318
238221AF1-254 C O1
Solar/Wind Helper
0.179
235067AD1-061 GEN
Solar/Wind Helper
0.312
233982AB2-133 GEN
Solar/Wind Helper
0.216
233918AB1-142 GEN
Solar/Wind Helper
0.303
233994AC2-023 GEN
Solar/Wind Helper
0.577
233940AF2-379 C
Solar/Wind Helper
0.037
233996TM1833_GEN
Solar/Wind Helper
0.157
233997TMININ_4.2
Solar/Wind Helper
0.157
233952AC2-187 GEN
Solar/Wind Helper
0.139
232406W1-004 FULL
Solar/Wind Helper
0.304
234015AF2-250 C
Solar/Wind Helper
0.023
233971AC1-093 C
Solar/Wind Helper
0.214
230430AE1-229_GEN
Solar/Wind Helper
1.995
230415AB2-049 C
Solar/Wind Helper
0.018
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219766PARADISE C
Solar/Wind Helper
0.032
219912AD2-042 GEN
Solar/Wind Helper
0.089
228729W2-030 C
Solar/Wind Helper
0.065
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.007
219906AC1-017 C
Solar/Wind Helper
0.025
219348LDSOLAR C
Solar/Wind Helper
0.067
959561AF2-247 GEN
Solar/Wind Helper
0.012
20716028EGP_W2-019
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.037
20715028HAN_X4-015
Solar/Wind Helper
0.033
219276PARKLANDSO C
Solar/Wind Helper
0.052
20714528FRN_Y2-051
Solar/Wind Helper
0.033
20720528MAN_W1-024
Solar/Wind Helper
0.016
219612MATRIX C
Solar/Wind Helper
0.014
218438BLK ROCK C
Solar/Wind Helper
0.016
20673728F2S_V4-070
Solar/Wind Helper
0.017
316321Z2-027
Solar/Wind Harmer
0.24
3145176PASQUOTANK
Solar/Wind Harmer
-0.006
3146396TANGLEW
Solar/Wind Harmer
0.164
316315AB2-025 C
Solar/Wind Harmer
0.238
315814AE2-033 C
Solar/Wind Harmer
8.205
315611Z1-036_GEN2
Solar/Wind Harmer
2.172
941031AE2-094 GEN
Solar/Wind Harmer
16.483
944011AF1-069 GEN
Solar/Wind Harmer
5.165
3130156CHOWAN
Solar/Wind Harmer
-0.009
3130156CHOWAN
Solar/Wind Harmer
-0.009
970673AG2-436 GEN
Solar/Wind Harmer
18.299
970673AG2-436 GEN
Solar/Wind Harmer
9.265
971967AH1-528 GEN
Solar/Wind Harmer
16.294
315816AE2-034 GEN
Solar/Wind Harmer
0.697
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315732AD1-074 GEN1
Solar/Wind Harmer
1.721
315733AD1-074 GEN2
Solar/Wind Harmer
1.721
315735AD1-075 GEN1
Solar/Wind Harmer
0.861
965291AG1-394 GEN
Solar/Wind Harmer
0.754
3146206CASHIE
Solar/Wind Harmer
-0.008
970601AG2-382 GEN
Solar/Wind Harmer
3.701
316318V4-068
Solar/Wind Harmer
0.211
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
5.265
970581AG2-369 GEN
Solar/Wind Harmer
4.528
3145513AHOSKIE
Solar/Wind Harmer
0.073
961941AG1-037 GEN
Solar/Wind Harmer
0.063
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3146043SEABORD
Solar/Wind Harmer
-0.008
946281AF1-292 GEN
Solar/Wind Harmer
0.187
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315607AA1-063A GEN
Solar/Wind Harmer
0.843
316087AB2-174 GEN
Solar/Wind Harmer
1.187
972205AH1-687 GEN
Adder
3.134
972193AH1-681 GEN
Adder
1.643
3151881LOWMORC
Adder
0.64
3151881LOWMORC
Adder
0.63
3151861LOWMORA
Adder
0.62
960921AF2-383 GEN
Solar/Wind Helper
0.139
205943AE1-185 GEN
Solar/Wind Helper
0.387
205956AE1-196_GEN
Solar/Wind Helper
0.385
205932AD2-116_GEN
Solar/Wind Helper
0.385
959381AF2-229 GEN
Solar/Wind Helper
0.257
237085AD2-009_GEN
Solar/Wind Helper
0.97
203975AE1-071-GEN
Solar/Wind Helper
1.713
233935AB2-179 C
Solar/Wind Helper
0.772
232436AB1-176 C
Solar/Wind Helper
0.027
233923SMA
Solar/Wind Helper
0.575
233990AG1-397 GEN
Solar/Wind Helper
0.018
232432Z2-076 GEN
Solar/Wind Helper
0.04
234033AF1-007_GEN
Solar/Wind Helper
4.208
964001AG1-254 GEN
Solar/Wind Helper
0.565
219914AD2-027 C
Solar/Wind Helper
0.068
228754AB1-001 C
Solar/Wind Helper
0.015
227927V4-067C
Solar/Wind Helper
0.006
219272CLEANLIGHT C
Solar/Wind Helper
0.015
219688LUMSOLAR_S C
Solar/Wind Helper
0.023
219607WPEMNERT C
Solar/Wind Helper
0.047
214067T20SOLAR
Solar/Wind Helper
0.007
20715728PEM_W1-119
Solar/Wind Helper
0.056
20715828PEM_W1-120
Solar/Wind Helper
0.056
207459AE1-142 C O1
Solar/Wind Helper
0.169
219620RIDERU C
Solar/Wind Helper
0.001
20675528CPH_W2-050
Solar/Wind Helper
0.05
218526CNTRALGAS2 C
Solar/Wind Helper
0.093
218524CNTRALGAS1 C
Solar/Wind Helper
0.093
966261AG1-495 GEN
Solar/Wind Helper
0.047
20675928HOL_W4-097
Solar/Wind Helper
0.029
207530AG1-191 GEN
Solar/Wind Helper
0.038
207484AF2-139 C O1
Solar/Wind Helper
0.048
20676328BVR_Y1-020
Solar/Wind Helper
0.015
20674828DL_W4-046
Solar/Wind Helper
0.004
207408W3-077 C
Solar/Wind Helper
0.048
20675728RH_W2-091
Solar/Wind Helper
0.078
20675128HRM_W1-127
Solar/Wind Helper
0.017
209116AE2-175 GEN
Solar/Wind Helper
1.004
961261AF2-417 GEN
Solar/Wind Helper
0.241
959431AF2-234 GEN
Solar/Wind Helper
0.466
964051AG1-259 GEN
Solar/Wind Helper
0.035
964061AG1-260 GEN
Solar/Wind Helper
0.035
959421AF2-233 GEN
Solar/Wind Helper
0.233
238208AF1-136 C
Solar/Wind Helper
0.089
235062AE1-101 C1
Solar/Wind Helper
1.064
237038AE2-054 C
Solar/Wind Helper
0.173
233930AB2-032 GEN
Solar/Wind Helper
0.23
233915AB1-141 GEN
Solar/Wind Helper
0.303
232422X3-066 FULL
Solar/Wind Helper
0.069
233964AF2-378 GEN
Solar/Wind Helper
0.025
232426Y1-080 FULL
Solar/Wind Helper
0.023
232428Y3-058 C
Solar/Wind Helper
0.203
233998TM1NIN_3.36
Solar/Wind Helper
0.157
233954AC2-188 GEN
Solar/Wind Helper
0.139
232404W1-003 C
Solar/Wind Helper
0.304
233950AC2-186 GEN
Solar/Wind Helper
0.07
232434Z2-077 GEN
Solar/Wind Helper
0.076
233972AC1-094 C
Solar/Wind Helper
0.181
205941AD2-115 GEN
Solar/Wind Helper
0.302
230434AG1-499 GEN
Solar/Wind Helper
0.136
230511AF1-262
Solar/Wind Helper
0.009
219258KINSLEYDEP C
Solar/Wind Helper
0.045
228728W1-130C
Solar/Wind Helper
0.032
219904AC1-010 C
Solar/Wind Helper
0.036
219907AC1-030 C
Solar/Wind Helper
0.02
218660EHAMPSOLAR C
Solar/Wind Helper
0.019
219686LUMSOLAR_N C
Solar/Wind Helper
0.023
219304NAMERICA C
Solar/Wind Helper
0.077
20720728JCB_W1-129
Solar/Wind Helper
0.033
207445AB1-138_GEN
Solar/Wind Helper
0.061
963711AG1-223 GEN
Solar/Wind Helper
0.037
20714828MDF_W3-079
Solar/Wind Helper
0.076
219680HOPEWELLV C1
Solar/Wind Helper
0.002
207454AA2-184 E
Solar/Wind Helper
0.18
20715228NPK_W1-113
Solar/Wind Helper
0.045
20742028HF_AC1-207
Solar/Wind Helper
0.082
207528AF2-192 GEN
Solar/Wind Helper
0.044
20673628F1S_V4-069
Solar/Wind Helper
0.017
20675428EAM_W2-061
Solar/Wind Helper
0.009
218428ETC SOLAR C
Solar/Wind Helper
0.003
20676428JCR_X2-075
Solar/Wind Helper
0.039
217213AMBOY SO C
Solar/Wind Helper
0.017
217209CENTRL HS C
Solar/Wind Helper
0.005
217208PARK ELE C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.013
207437AD2-070 GEN
Solar/Wind Helper
0.079
207439AE1-081 C O1
Solar/Wind Helper
0.011
207518AF1-320_GEN
Solar/Wind Helper
0.9
20671928W4-073
Solar/Wind Helper
0.051
20675828AU_W4-064
Solar/Wind Helper
0.017
961301AF2-421 GEN
Solar/Wind Helper
0.242
963151AG1-164 GEN
Solar/Wind Helper
0.242
212266LOR1
Solar/Wind Helper
0.026
961341AF2-425 GEN
Solar/Wind Helper
0.237
212507AE2-042_GEN
Solar/Wind Helper
0.829
946731AF1-337 GEN
Solar/Wind Helper
0.233
209071AE2-133 GEN
Solar/Wind Helper
0.042
315693AD1-088 GEN
Solar/Wind Harmer
1.373
219908AB1-139 C
Solar/Wind Helper
0.043
219919AE1-041 FULL
Solar/Wind Helper
0.002
219249CENTRALDIV C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
217169METRODIV C
Solar/Wind Helper
0.002
20676728BRNX1-095
Solar/Wind Helper
0.017
207510AF2-138 C
Solar/Wind Helper
0.046
20674628WNG_W3-110
Solar/Wind Helper
0.051
963161AG1-165 GEN
Solar/Wind Helper
0.242
963071AG1-156 GEN
Solar/Wind Helper
0.783
209027LOR2_Q27
Solar/Wind Helper
0.557
961331AF2-424 GEN
Solar/Wind Helper
0.237
961421AF2-433 GEN
Solar/Wind Helper
0.236
957921AF2-086 GEN
Solar/Wind Helper
0.234
946691AF1-333 GEN
Solar/Wind Helper
0.233
946741AF1-338 GEN
Solar/Wind Helper
0.233
209067AE2-060 GEN
Solar/Wind Helper
0.042
NYPJM->LTFIMP_NY
CLTF
2.575
LGEELTFEXP_LGEE->PJM
CLTF
1.805
WECLTFEXP_WEC->PJM
CLTF
0.962
LAGNLTFEXP_LAGN->PJM
CLTF
6.323
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.563
TVALTFEXP_TVA->PJM
CLTF
3.187
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.478
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.59
MECLTFEXP_MEC->PJM
CLTF
4.448
SIGELTFEXP_SIGE->PJM
CLTF
0.14
CPLELTFEXP_CPLE->PJM
CLTF
5.064
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.958

Details for 6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T560_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T560_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.42 %
Rating:1809.0 MVA
Rating Type:C
MVA to Mitigate:2124.08
MW Contribution:42.84
Bus #Bus NameTypeMW Contribution
972289AH1-729 GEN
50/50
13.252
3150071POSSM 5
Adder
49.613
3150181POSSMC2
Adder
1.095
3150181POSSMC2
Adder
1.085
3150181POSSMC2
Adder
1.085
3150391LDYSMT3
Adder
12.67
972195AH1-682 GEN
Adder
1.665
316447AC1-158 HLD
Solar/Wind Harmer
2.294
315651AD1-115 GEN
Solar/Wind Harmer
4.661
315673AE1-157 GEN
Solar/Wind Harmer
7.801
957411AF2-035 GEN
Solar/Wind Harmer
4.62
970317AG2-208 GEN
Solar/Wind Harmer
4.491
316468AD1-105 GEN
Solar/Wind Harmer
1.121
316077AC2-138 C
Solar/Wind Harmer
0.207
3150341NORNECKC1
Adder
0.915
3150341NORNECKC1
Adder
0.907
966001AG1-469 GEN
Solar/Wind Harmer
0.184
958261AF2-120 GEN
Solar/Wind Harmer
3.769
3151731LOISA B
Adder
5.597
3151721LOISA A
Adder
5.568
316487AF1-042 GEN
Solar/Wind Harmer
1.275
966871AG1-558 GEN
Solar/Wind Harmer
0.29
966871AG1-558 GEN
Solar/Wind Harmer
0.099
3142296MT RD221
Adder
0.271
316441AF1-014 GEN
Solar/Wind Harmer
0.641
3142366NRTHEST
Adder
0.276
3150691DARBY 3
Adder
6.069
3150701DARBY 4
Adder
6.055
3150681DARBY 2
Adder
6.048
3150671DARBY 1
Adder
6.041
316075AC2-137 C
Solar/Wind Harmer
0.255
3142946ENON
Solar/Wind Harmer
-0.001
3143526WINTERP
Solar/Wind Harmer
-0.049
971223AH1-071 GEN
Solar/Wind Harmer
1.172
944641AF1-129 GEN
Adder
39.415
316240AF1-291 C
Solar/Wind Harmer
0.279
316033AB2-134 GEN
Solar/Wind Harmer
2.975
315697AD1-025 GEN
Solar/Wind Harmer
1.866
316236AE1-162_GEN
Solar/Wind Harmer
0.275
970657AG2-426 GEN
Solar/Wind Harmer
2.837
970657AG2-426 GEN
Solar/Wind Harmer
0.593
316036AC1-147 C
Solar/Wind Harmer
0.244
3150991CHESPKB
Adder
0.845
3150991CHESPKB
Adder
0.825
316316AC1-027 C
Solar/Wind Harmer
0.278
3142956BIRDNECK
Solar/Wind Harmer
0.486
316185AD1-033 GEN
Solar/Wind Harmer
0.954
3145506HICKORY
Solar/Wind Harmer
-0.036
3145506HICKORY
Solar/Wind Harmer
-0.022
3145506HICKORY
Solar/Wind Harmer
-0.005
316339AD2-160 GEN
Solar/Wind Harmer
0.608
316018AA1-139 ULT2
Solar/Wind Harmer
0.771
316017AA1-139 ULT1
Solar/Wind Harmer
0.729
3137176SLIGO L2192
Solar/Wind Harmer
-0.036
3146456SLIGO L269
Solar/Wind Harmer
1.062
3130086AYDLETT
Solar/Wind Harmer
-0.036
3146386ELIZ CT
Solar/Wind Harmer
-0.009
316431W1029_GEN1
Solar/Wind Harmer
1.61
316433W1029_GEN2
Solar/Wind Harmer
1.61
970053AG2-049 GEN
50/50
2.028
3138216PACIFIC
Solar/Wind Harmer
-0.003
316411AF1-147_GEN1
Solar/Wind Harmer
1.101
316415AF1-147_GEN2
Solar/Wind Harmer
1.101
3141426STAFORD
Solar/Wind Harmer
-0.003
3150411LDYSMT5
Adder
12.733
3150381LDYSMT2
Adder
12.186
972213AH1-691 GEN
Adder
2.061
972215AH1-692 GEN
Adder
2.061
316164AC1-076 GEN
Solar/Wind Harmer
0.887
944491AF1-114 GEN
Solar/Wind Harmer
3.051
316223AC1-118
Solar/Wind Harmer
0.272
972189AH1-679 GEN
Adder
1.468
3141813NORNECK
Solar/Wind Harmer
-0.01
962981AG1-147 GEN
Solar/Wind Harmer
4.221
3141783LANCAST
Solar/Wind Harmer
-0.006
3141783LANCAST
Solar/Wind Harmer
-0.004
3138133OCRAN
Solar/Wind Harmer
-0.003
3141913WHIT STONE
Solar/Wind Harmer
-0.01
316312AB1-027
Solar/Wind Harmer
0.321
3147346CASHSCORNER
Solar/Wind Harmer
0.147
316314AB2-024 C
Solar/Wind Harmer
0.813
957601AF2-054 GEN
Solar/Wind Harmer
0.285
316059AD1-063 C
Solar/Wind Harmer
0.215
3141873WAN 176
Solar/Wind Harmer
-0.002
315662AE1-191 GEN
Solar/Wind Harmer
1.146
315666AE1-190 GEN
Solar/Wind Harmer
0.287
3143873LANEXA
Solar/Wind Harmer
-0.006
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
971167AH1-042 GEN
Solar/Wind Harmer
9.109
315976AC1-164 GENA
Solar/Wind Harmer
9.985
316169AC1-164_GENC
Solar/Wind Harmer
8.626
315975AC1-164 GENB
Solar/Wind Harmer
0.295
316233AE1-074 FULL
Solar/Wind Harmer
0.253
971281AH1-106 GEN
Solar/Wind Harmer
1.528
971283AH1-107 GEN
Solar/Wind Harmer
1.528
971285AH1-108 GEN
Adder
0.631
957831AF2-077 GEN
Solar/Wind Harmer
0.282
3138283WHITEMARSH
Solar/Wind Harmer
0.015
316132AB2-190 GEN1
Solar/Wind Harmer
0.937
316369SG1_INVT
Solar/Wind Harmer
1.648
972265AH1-717 GEN
Adder
6.337
3151201GRAVEL4
Adder
5.94
3151191GRAVEL3
Adder
5.865
3151211GRAVEL5
Adder
5.865
971445AH1-216 GEN
Solar/Wind Harmer
5.652
3143316POE
Solar/Wind Harmer
-0.036
3151081ELIZAR1
Adder
7.394
3151091ELIZAR2
Adder
7.266
3152611GOSPORTB
Adder
1.027
3152621GOSPORTC
Adder
0.872
3152601GOSPORTA
Adder
0.804
315833AF1-017_GEN
Solar/Wind Harmer
1.712
316349AD2-085 GEN
Solar/Wind Harmer
0.802
316311AC2-079 GEN
Solar/Wind Harmer
4.545
957871AF2-081 GEN
Solar/Wind Harmer
4.503
316305AF2-043 C
Solar/Wind Harmer
0.271
319010AE1-072 C
Solar/Wind Harmer
1.819
3146406KITTY HAWK
Solar/Wind Harmer
0.007
315835AF2-110_GEN
Solar/Wind Harmer
1.121
313526AB2-022
Solar/Wind Harmer
0.241
3146486SUNBURY
Solar/Wind Harmer
-0.009
3146486SUNBURY
Solar/Wind Harmer
-0.009
316321Z2-027
Solar/Wind Harmer
0.24
3145176PASQUOTANK
Solar/Wind Harmer
-0.006
3146396TANGLEW
Solar/Wind Harmer
0.164
316315AB2-025 C
Solar/Wind Harmer
0.238
315814AE2-033 C
Solar/Wind Harmer
8.205
315611Z1-036_GEN2
Solar/Wind Harmer
2.172
941031AE2-094 GEN
Solar/Wind Harmer
16.482
944011AF1-069 GEN
Solar/Wind Harmer
5.164
3130156CHOWAN
Solar/Wind Harmer
-0.009
3130156CHOWAN
Solar/Wind Harmer
-0.009
970673AG2-436 GEN
Solar/Wind Harmer
18.298
970673AG2-436 GEN
Solar/Wind Harmer
9.265
971967AH1-528 GEN
Solar/Wind Harmer
16.294
315816AE2-034 GEN
Solar/Wind Harmer
0.697
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315732AD1-074 GEN1
Solar/Wind Harmer
1.721
315733AD1-074 GEN2
Solar/Wind Harmer
1.721
315735AD1-075 GEN1
Solar/Wind Harmer
0.861
965291AG1-394 GEN
Solar/Wind Harmer
0.754
3146206CASHIE
Solar/Wind Harmer
-0.008
970601AG2-382 GEN
Solar/Wind Harmer
3.701
316318V4-068
Solar/Wind Harmer
0.211
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
5.265
970581AG2-369 GEN
Solar/Wind Harmer
4.528
3145513AHOSKIE
Solar/Wind Harmer
0.073
961941AG1-037 GEN
Solar/Wind Harmer
0.063
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3146043SEABORD
Solar/Wind Harmer
-0.008
946281AF1-292 GEN
Solar/Wind Harmer
0.187
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315607AA1-063A GEN
Solar/Wind Harmer
0.843
316087AB2-174 GEN
Solar/Wind Harmer
1.187
972205AH1-687 GEN
Adder
3.134
972193AH1-681 GEN
Adder
1.643
3151881LOWMORC
Adder
0.64
3151881LOWMORC
Adder
0.63
3151861LOWMORA
Adder
0.62
960921AF2-383 GEN
Solar/Wind Helper
0.139
205943AE1-185 GEN
Solar/Wind Helper
0.387
205956AE1-196_GEN
Solar/Wind Helper
0.385
205932AD2-116_GEN
Solar/Wind Helper
0.385
959381AF2-229 GEN
Solar/Wind Helper
0.257
237085AD2-009_GEN
Solar/Wind Helper
0.97
203975AE1-071-GEN
Solar/Wind Helper
1.713
233935AB2-179 C
Solar/Wind Helper
0.772
232436AB1-176 C
Solar/Wind Helper
0.027
233923SMA
Solar/Wind Helper
0.575
233990AG1-397 GEN
Solar/Wind Helper
0.018
232432Z2-076 GEN
Solar/Wind Helper
0.04
234033AF1-007_GEN
Solar/Wind Helper
4.208
964001AG1-254 GEN
Solar/Wind Helper
0.565
219914AD2-027 C
Solar/Wind Helper
0.068
228754AB1-001 C
Solar/Wind Helper
0.015
227927V4-067C
Solar/Wind Helper
0.006
219272CLEANLIGHT C
Solar/Wind Helper
0.015
219688LUMSOLAR_S C
Solar/Wind Helper
0.023
219607WPEMNERT C
Solar/Wind Helper
0.047
214067T20SOLAR
Solar/Wind Helper
0.007
20715728PEM_W1-119
Solar/Wind Helper
0.056
20715828PEM_W1-120
Solar/Wind Helper
0.056
207459AE1-142 C O1
Solar/Wind Helper
0.169
219620RIDERU C
Solar/Wind Helper
0.001
20675528CPH_W2-050
Solar/Wind Helper
0.05
218526CNTRALGAS2 C
Solar/Wind Helper
0.093
218524CNTRALGAS1 C
Solar/Wind Helper
0.093
966261AG1-495 GEN
Solar/Wind Helper
0.047
20675928HOL_W4-097
Solar/Wind Helper
0.029
207530AG1-191 GEN
Solar/Wind Helper
0.038
207484AF2-139 C O1
Solar/Wind Helper
0.048
20676328BVR_Y1-020
Solar/Wind Helper
0.015
20674828DL_W4-046
Solar/Wind Helper
0.004
207408W3-077 C
Solar/Wind Helper
0.048
20675728RH_W2-091
Solar/Wind Helper
0.078
20675128HRM_W1-127
Solar/Wind Helper
0.017
209116AE2-175 GEN
Solar/Wind Helper
1.004
961261AF2-417 GEN
Solar/Wind Helper
0.241
959431AF2-234 GEN
Solar/Wind Helper
0.466
964051AG1-259 GEN
Solar/Wind Helper
0.035
964061AG1-260 GEN
Solar/Wind Helper
0.035
959421AF2-233 GEN
Solar/Wind Helper
0.233
238208AF1-136 C
Solar/Wind Helper
0.089
3152131X4-039 ST
50/50
2.893
3152121X4-039 GT2
50/50
1.833
3140676OCCOQUN
Adder
0.27
972223AH1-696 GEN
Adder
8.574
3150151POSSMC1
Adder
1.085
3141346CRANES
Adder
0.12
3150221REMNGT2
Adder
12.463
3150211REMNGT1
Adder
12.38
972201AH1-685 GEN
Adder
2.15
3150281M RUN A
Adder
13.354
316006AB2-029 C
Solar/Wind Harmer
0.631
971685AH1-345 GEN
Solar/Wind Harmer
0.961
972197AH1-683 GEN
Adder
1.982
972219AH1-694 GEN
Adder
1.427
316045AC1-158 PL2
Solar/Wind Harmer
3.338
316254AC1-120 GEN1
Solar/Wind Harmer
0.849
957971AF2-091 GEN
Solar/Wind Harmer
1.037
972135AH1-637 GEN
Solar/Wind Harmer
1.031
966881AG1-559 GEN
Solar/Wind Harmer
0.106
315683AE1-153 C
Solar/Wind Harmer
9.501
3147666LOUISA
Solar/Wind Harmer
-0.04
316192AB2-158 GEN
Solar/Wind Harmer
1.185
316337AD2-073 GEN
Solar/Wind Harmer
0.267
3150351NORNECKC2
Adder
0.871
964211AG1-282 GEN
Solar/Wind Harmer
0.294
3141726DUNNSVL
Solar/Wind Harmer
-0.039
962861AG1-135 GEN
Solar/Wind Harmer
3.643
3151751LOISA D
Adder
5.597
961951AG1-038 GEN
Solar/Wind Harmer
1.275
3138133OCRAN
Solar/Wind Harmer
-0.006
3142416OLDCHRC
Solar/Wind Harmer
-0.025
3142416OLDCHRC
Solar/Wind Harmer
-0.009
3141766HARMONY
Solar/Wind Harmer
-0.002
971777AH1-397 GEN
Solar/Wind Harmer
1.118
3141843SHACKLE
Adder
0.432
3142433PROV 92
Solar/Wind Harmer
-0.038
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
3143096IRON208
Adder
0.351
3143526WINTERP
Solar/Wind Harmer
-0.049
3142543TWELFTH
Solar/Wind Harmer
-0.001
3150851SPRUNCC
Adder
0.385
944631AF1-128 GEN
Adder
39.856
3143226MDLTHAN
Solar/Wind Harmer
-0.009
316159AE1-175 C
Solar/Wind Harmer
0.25
971317AH1-138 GEN
Solar/Wind Harmer
1.163
970129AG2-093 GEN
Solar/Wind Harmer
2.113
316458AB2-190 GEN2
Solar/Wind Harmer
0.937
315671AE2-027_GEN
Solar/Wind Harmer
6.943
3138126ROCKLANDING
Solar/Wind Harmer
0.028
971069AG2-661 GEN
Solar/Wind Harmer
1.462
971647AH1-324 GEN
Solar/Wind Harmer
4.604
961611AG1-000B GEN
Solar/Wind Harmer
4.536
3151171GRAVELC
Adder
0.868
3145336SMITFLD
Solar/Wind Harmer
-0.036
316294AC1-161 GEN
Solar/Wind Harmer
2.948
970659AG2-427 GEN
Solar/Wind Harmer
4.83
316381AD1-082 GEN
Solar/Wind Harmer
0.833
316375AC2-012 GEN
Solar/Wind Harmer
3.136
3150981CHESPKA
Adder
1.007
970661AG2-428 GEN
Solar/Wind Harmer
9.631
944591AF1-124 GEN
Solar/Wind Harmer
41.344
316072AD1-144
Solar/Wind Harmer
0.183
316388AE2-253 GEN
Solar/Wind Harmer
0.608
3146456SLIGO L269
Solar/Wind Harmer
-0.009
939411AE1-173 GEN
Solar/Wind Harmer
44.98
316246AF1-032 C
Solar/Wind Harmer
0.182
940641AE2-051 GEN
Solar/Wind Harmer
8.42
316093AE2-104_GEN
Solar/Wind Harmer
2.607
3143336POWHATN
Solar/Wind Harmer
1.059
3146516WINFALL
Solar/Wind Harmer
-0.029
3146516WINFALL
Solar/Wind Harmer
-0.009
316336AC2-165 C
Solar/Wind Harmer
1.53
315800Z1-036_GEN1
Solar/Wind Harmer
2.172
3130156CHOWAN
Solar/Wind Harmer
-0.009
3145663CRESWEL
Solar/Wind Harmer
-0.024
971163AH1-040 GEN
Solar/Wind Harmer
8.075
970937AG2-583 GEN
Solar/Wind Harmer
6.109
316023GEN1_S
Solar/Wind Harmer
0.57
3146206CASHIE
Solar/Wind Harmer
-0.008
971547AH1-271 GEN
Solar/Wind Harmer
2.115
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.251
970919AG2-571 GEN
Solar/Wind Harmer
2.672
970087AG2-069 GEN
Solar/Wind Harmer
7.898
3146173TUNIS
Solar/Wind Harmer
-0.008
960081AF2-299 GEN
Solar/Wind Harmer
0.94
3145683EARLEYS
Solar/Wind Harmer
-0.008
957481AF2-042 GEN
Solar/Wind Harmer
26.028
3146263WOODLND
Solar/Wind Harmer
-0.008
3147043LAWRENC
Adder
0.664
3144293JTRSVLE
Adder
0.23
972277AH1-723 GEN
Adder
42.842
23779801AA1-109
Solar/Wind Helper
0.217
223401AF1-299 GEN
Solar/Wind Helper
0.397
966131AG1-482 GEN
Solar/Wind Helper
0.063
237080AD1-060 GEN
Solar/Wind Helper
0.221
235062AE1-101 C1
Solar/Wind Helper
1.064
237038AE2-054 C
Solar/Wind Helper
0.173
233930AB2-032 GEN
Solar/Wind Helper
0.23
233915AB1-141 GEN
Solar/Wind Helper
0.303
232422X3-066 FULL
Solar/Wind Helper
0.069
233964AF2-378 GEN
Solar/Wind Helper
0.025
232426Y1-080 FULL
Solar/Wind Helper
0.023
232428Y3-058 C
Solar/Wind Helper
0.203
233998TM1NIN_3.36
Solar/Wind Helper
0.157
233954AC2-188 GEN
Solar/Wind Helper
0.139
232404W1-003 C
Solar/Wind Helper
0.304
233950AC2-186 GEN
Solar/Wind Helper
0.07
232434Z2-077 GEN
Solar/Wind Helper
0.076
233972AC1-094 C
Solar/Wind Helper
0.181
205941AD2-115 GEN
Solar/Wind Helper
0.302
230434AG1-499 GEN
Solar/Wind Helper
0.136
230511AF1-262
Solar/Wind Helper
0.009
219258KINSLEYDEP C
Solar/Wind Helper
0.045
228728W1-130C
Solar/Wind Helper
0.032
219904AC1-010 C
Solar/Wind Helper
0.036
219907AC1-030 C
Solar/Wind Helper
0.02
218660EHAMPSOLAR C
Solar/Wind Helper
0.019
219686LUMSOLAR_N C
Solar/Wind Helper
0.023
219304NAMERICA C
Solar/Wind Helper
0.077
20720728JCB_W1-129
Solar/Wind Helper
0.033
207445AB1-138_GEN
Solar/Wind Helper
0.061
963711AG1-223 GEN
Solar/Wind Helper
0.037
20714828MDF_W3-079
Solar/Wind Helper
0.076
219680HOPEWELLV C1
Solar/Wind Helper
0.002
207454AA2-184 E
Solar/Wind Helper
0.18
20715228NPK_W1-113
Solar/Wind Helper
0.045
20742028HF_AC1-207
Solar/Wind Helper
0.082
207528AF2-192 GEN
Solar/Wind Helper
0.044
20673628F1S_V4-069
Solar/Wind Helper
0.017
20675428EAM_W2-061
Solar/Wind Helper
0.009
218428ETC SOLAR C
Solar/Wind Helper
0.003
20676428JCR_X2-075
Solar/Wind Helper
0.039
217213AMBOY SO C
Solar/Wind Helper
0.017
217209CENTRL HS C
Solar/Wind Helper
0.005
217208PARK ELE C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.013
207437AD2-070 GEN
Solar/Wind Helper
0.079
207439AE1-081 C O1
Solar/Wind Helper
0.011
207518AF1-320_GEN
Solar/Wind Helper
0.9
20671928W4-073
Solar/Wind Helper
0.051
20675828AU_W4-064
Solar/Wind Helper
0.017
961301AF2-421 GEN
Solar/Wind Helper
0.242
963151AG1-164 GEN
Solar/Wind Helper
0.242
212266LOR1
Solar/Wind Helper
0.026
961341AF2-425 GEN
Solar/Wind Helper
0.237
212507AE2-042_GEN
Solar/Wind Helper
0.829
946731AF1-337 GEN
Solar/Wind Helper
0.233
209071AE2-133 GEN
Solar/Wind Helper
0.042
315693AD1-088 GEN
Solar/Wind Harmer
1.373
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3144356SAPONY
Solar/Wind Harmer
0.308
315742AE1-103 GEN
Solar/Wind Harmer
0.916
3146376EDENTON
Solar/Wind Harmer
0.259
3146376EDENTON
Solar/Wind Harmer
0.259
972185AH1-677 GEN
Adder
4.33
972187AH1-678 GEN
Adder
2.184
970933AG2-581 GEN
Solar/Wind Harmer
8.04
316065AD1-022 GEN
Solar/Wind Harmer
4.239
3145893MURPHYS
Solar/Wind Harmer
0.236
3145893MURPHYS
Solar/Wind Harmer
-0.015
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
970099AG2-077 GEN
Solar/Wind Harmer
10.411
316181AB2-040 GEN
Solar/Wind Harmer
1.158
3144293JTRSVLE
Adder
0.23
3144293JTRSVLE
Adder
0.193
226929AD2-058 GEN
Solar/Wind Helper
0.143
237025AB1-124 C
Solar/Wind Helper
0.193
237006AB1-125 GEN
Solar/Wind Helper
0.145
23777801MSM_W1-116
Solar/Wind Helper
0.13
237034AC2-136 C
Solar/Wind Helper
0.205
205916AD1-020 GEN
Solar/Wind Helper
1.48
208835TUHI V3-051
Solar/Wind Helper
0.019
208835TUHI V3-051
Solar/Wind Helper
0.019
237001AB1-127_GEN
Solar/Wind Helper
0.307
237002AB1-128_GEN
Solar/Wind Helper
0.298
235063AE1-101 C2
Solar/Wind Helper
1.064
20390526W1-045 C
Solar/Wind Helper
0.252
23777901MDS_W4-102
Solar/Wind Helper
0.105
235020AA1-095 C
Solar/Wind Helper
0.029
233933AB2-153 GEN
Solar/Wind Helper
0.14
233944AB2-135 GEN
Solar/Wind Helper
0.355
232424Y1-079 C
Solar/Wind Helper
0.07
233987AB2-037 GEN
Solar/Wind Helper
1.406
234036AF2-325 C
Solar/Wind Helper
0.025
233946AB2-136 GEN
Solar/Wind Helper
0.341
233901CHERRYDALE C
Solar/Wind Helper
0.139
232408W1-005 C
Solar/Wind Helper
0.304
232410W1-006 C
Solar/Wind Helper
0.304
233939AC1-091 C
Solar/Wind Helper
0.209
233970AC1-092 C
Solar/Wind Helper
0.209
230433AD2-135 GEN
Solar/Wind Helper
0.01
219921AF1-264
Solar/Wind Helper
0.03
230407AD2-065 C
Solar/Wind Helper
0.024
219615MILLCREEK C
Solar/Wind Helper
0.016
963401AG1-189 GEN
Solar/Wind Helper
0.033
963391AG1-188 GEN
Solar/Wind Helper
0.048
20714928UPF_X1-085
Solar/Wind Helper
0.003
20720628TIN_W1-124
Solar/Wind Helper
0.11
20716928W4-060COL
Solar/Wind Helper
0.03
20673828FLE_V3-070
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.009
207442AE1-156 GEN
Solar/Wind Helper
0.188
20676128MHD_W3-029
Solar/Wind Helper
0.055
20671828STAW2-080
Solar/Wind Helper
0.015
217081WEATEXAS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.004
217204WCALDSOLAR C
Solar/Wind Helper
0.002
207471AF2-354 C
Solar/Wind Helper
0.097
20674928WA_W3-044
Solar/Wind Helper
0.056
964851AG1-348 GEN
Solar/Wind Helper
0.046
20674128FR_U2-059
Solar/Wind Helper
0.002
20676228FRD_X1-012
Solar/Wind Helper
0.052
966111AG1-480 GEN
Solar/Wind Helper
0.025
211065PSPA IPP
Solar/Wind Helper
0.085
211065PSPA IPP
Solar/Wind Helper
0.085
208972BECR K09
Solar/Wind Helper
0.178
961431AF2-434 GEN
Solar/Wind Helper
0.236
209029WAYMART-WD
Solar/Wind Helper
0.442
209054AE2-059 GEN
Solar/Wind Helper
0.042
946751AF1-339 GEN
Solar/Wind Helper
0.233
209137AF2-361 C
Solar/Wind Helper
0.708
3152111X4-039 GT1
50/50
1.839
315747AE2-019 GEN
50/50
13.179
963691AG1-221 GEN
Solar/Wind Harmer
2.313
971455AH1-223 GEN
Solar/Wind Harmer
2.313
3150151POSSMC1
Adder
1.085
3150151POSSMC1
Adder
1.085
3141196NOKESVL
Solar/Wind Harmer
-0.048
3150231REMNGT3
Adder
13.456
3150241REMNGT4
Adder
12.546
972199AH1-684 GEN
Adder
1.902
972217AH1-693 GEN
Adder
1.654
3150331BIRCHWDA
Adder
16.699
3150301M RUN C
Adder
13.346
3150291M RUN B
Adder
13.246
3141316ARNOLDS
Adder
0.23
3150401LDYSMT4
Adder
12.694
3150371LDYSMT1
Adder
12.265
316044AC1-158 PL1
Solar/Wind Harmer
1.043
316450AC1-158 RIC
Solar/Wind Harmer
0.278
316170AC1-121 GEN2
Solar/Wind Harmer
0.283
966881AG1-559 GEN
Solar/Wind Harmer
0.309
970737AG2-469 GEN
Solar/Wind Harmer
5.111
3141906WESTMOR
Solar/Wind Harmer
-0.004
3132273ORANGE
Solar/Wind Harmer
-0.002
971781AH1-399 GEN
Solar/Wind Harmer
0.62
3147666LOUISA
Solar/Wind Harmer
-0.023
3150351NORNECKC2
Adder
0.885
316404AE1-155 C
Solar/Wind Harmer
1.876
3151761LOISA E
Adder
11.411
316484AD2-074 GEN
Solar/Wind Harmer
2.436
970009AG2-005 GEN
Solar/Wind Harmer
1.21
972183AH1-676 GEN
Adder
92.013
316473AC1-191 GEN
Solar/Wind Harmer
1.04
962971AG1-146 GEN
Solar/Wind Harmer
1.809
3142416OLDCHRC
Solar/Wind Harmer
0.961
316156AD2-030 GEN
Solar/Wind Harmer
0.254
3141873WAN 176
Solar/Wind Harmer
1.129
3141766HARMONY
Solar/Wind Harmer
0.847
316280AD1-041 GEN
Solar/Wind Harmer
0.717
316203AE2-005 GEN
Solar/Wind Harmer
4.009
3141843SHACKLE
Adder
0.432
970293AG2-193 GEN
Solar/Wind Harmer
1.184
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
3143096IRON208
Adder
0.351
3143096IRON208
Adder
0.344
3142946ENON
Solar/Wind Harmer
-0.003
3150861SPRUNCD
Adder
0.385
316382AG1-145 C
Solar/Wind Harmer
0.281
970133AG2-095 GEN
Solar/Wind Harmer
1.046
970129AG2-093 GEN
Solar/Wind Harmer
5.216
3150921YORKTN3
Adder
2.069
315778AD1-151 GEN
Solar/Wind Harmer
8.005
965281AG1-393 GEN
Solar/Wind Harmer
1.155
3144216WINCHST
Adder
0.31
315839AE2-212 C
Solar/Wind Harmer
0.278
961611AG1-000B GEN
Solar/Wind Harmer
1.935
3151221GRAVEL6
Adder
5.934
3151171GRAVELC
Adder
1.142
3145336SMITFLD
Solar/Wind Harmer
-0.004
315813AE1-149 C
Solar/Wind Harmer
5.707
315773AC2-141 GEN
Solar/Wind Harmer
3.812
970659AG2-427 GEN
Solar/Wind Harmer
0.856
316083AB2-161 GEN
Solar/Wind Harmer
1.475
3144536CHRHLND
Solar/Wind Harmer
-0.001
3151101ELIZAR3
Adder
7.489
970661AG2-428 GEN
Solar/Wind Harmer
1.707
3144873MCLAUGH
Solar/Wind Harmer
0
944581AF1-123 GEN
Solar/Wind Harmer
41.195
944601AF1-125 GEN
Solar/Wind Harmer
40.552
3146456SLIGO L269
Solar/Wind Harmer
-0.009
971153AH1-033 GEN
Solar/Wind Harmer
1.096
316320Y1-086
Solar/Wind Harmer
0.524
316313AB2-026
Solar/Wind Harmer
0.241
316258AE1-075 C
Solar/Wind Harmer
0.217
316405AF2-144 C
Solar/Wind Harmer
0.229
3143336POWHATN
Solar/Wind Harmer
0.9
316435W1029_GEN3
Solar/Wind Harmer
1.61
3146516WINFALL
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3145273HOLLAND
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.009
315614AA2-178 GEN
Solar/Wind Harmer
0.929
971157AH1-035 GEN
Solar/Wind Harmer
1.066
3156081AA2-088 GEN
Solar/Wind Harmer
2.765
315737AD1-076 GEN
Solar/Wind Harmer
1.618
316365GEN2_N
Solar/Wind Harmer
0.57
3146206CASHIE
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.059
3145893MURPHYS
Solar/Wind Harmer
-0.008
970917AG2-570 GEN
Solar/Wind Harmer
21.109
957521AF2-046 GEN
Solar/Wind Harmer
6.644
961681AG1-008 GEN
Solar/Wind Harmer
6.644
3146173TUNIS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1.13
316463AE2-346 GEN
Solar/Wind Harmer
0.136
316140AB2-099
Solar/Wind Harmer
0.056
962331AG1-082 GEN
Solar/Wind Harmer
1.047
966621AG1-532 GEN
Solar/Wind Harmer
0.17
3146263WOODLND
Solar/Wind Harmer
-0.008
313506AB2-031 GEN
Solar/Wind Harmer
0.667
3144293JTRSVLE
Adder
0.23
972255AH1-712 GEN
Adder
36.765
3151861LOWMORA
Adder
0.645
226910AB2-157 C
Solar/Wind Helper
0.02
227287AC2-120 GEN
Solar/Wind Helper
0.49
237030AB1-096 C
Solar/Wind Helper
0.083
223402AF1-300 C
Solar/Wind Helper
0.397
205917AD1-020 ES
Solar/Wind Helper
0.318
238221AF1-254 C O1
Solar/Wind Helper
0.179
235067AD1-061 GEN
Solar/Wind Helper
0.312
233982AB2-133 GEN
Solar/Wind Helper
0.216
233918AB1-142 GEN
Solar/Wind Helper
0.303
233994AC2-023 GEN
Solar/Wind Helper
0.577
233996TM1833_GEN
Solar/Wind Helper
0.157
233997TMININ_4.2
Solar/Wind Helper
0.157
233952AC2-187 GEN
Solar/Wind Helper
0.139
232406W1-004 FULL
Solar/Wind Helper
0.304
233940AF2-379 C
Solar/Wind Helper
0.037
234015AF2-250 C
Solar/Wind Helper
0.023
233971AC1-093 C
Solar/Wind Helper
0.214
230430AE1-229_GEN
Solar/Wind Helper
1.995
230415AB2-049 C
Solar/Wind Helper
0.018
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219766PARADISE C
Solar/Wind Helper
0.032
219912AD2-042 GEN
Solar/Wind Helper
0.089
228729W2-030 C
Solar/Wind Helper
0.065
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.007
219906AC1-017 C
Solar/Wind Helper
0.025
219348LDSOLAR C
Solar/Wind Helper
0.067
959561AF2-247 GEN
Solar/Wind Helper
0.012
20716028EGP_W2-019
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.037
20715028HAN_X4-015
Solar/Wind Helper
0.033
219276PARKLANDSO C
Solar/Wind Helper
0.052
20714528FRN_Y2-051
Solar/Wind Helper
0.033
20720528MAN_W1-024
Solar/Wind Helper
0.016
219612MATRIX C
Solar/Wind Helper
0.014
218438BLK ROCK C
Solar/Wind Helper
0.016
20673728F2S_V4-070
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.043
219919AE1-041 FULL
Solar/Wind Helper
0.002
219249CENTRALDIV C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
217169METRODIV C
Solar/Wind Helper
0.002
20676728BRNX1-095
Solar/Wind Helper
0.017
207510AF2-138 C
Solar/Wind Helper
0.046
20674628WNG_W3-110
Solar/Wind Helper
0.051
963161AG1-165 GEN
Solar/Wind Helper
0.242
963071AG1-156 GEN
Solar/Wind Helper
0.783
209027LOR2_Q27
Solar/Wind Helper
0.557
961331AF2-424 GEN
Solar/Wind Helper
0.237
961421AF2-433 GEN
Solar/Wind Helper
0.236
957921AF2-086 GEN
Solar/Wind Helper
0.234
946691AF1-333 GEN
Solar/Wind Helper
0.233
946741AF1-338 GEN
Solar/Wind Helper
0.233
209067AE2-060 GEN
Solar/Wind Helper
0.042
NYPJM->LTFIMP_NY
CLTF
2.575
LGEELTFEXP_LGEE->PJM
CLTF
1.805
WECLTFEXP_WEC->PJM
CLTF
0.962
LAGNLTFEXP_LAGN->PJM
CLTF
6.323
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.563
TVALTFEXP_TVA->PJM
CLTF
3.187
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.478
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.59
MECLTFEXP_MEC->PJM
CLTF
4.448
SIGELTFEXP_SIGE->PJM
CLTF
0.14
CPLELTFEXP_CPLE->PJM
CLTF
5.064
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.958

Details for 6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line l/o DVP_P4-2: 560T571_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 560T571_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.69 %
Rating:1809.0 MVA
Rating Type:C
MVA to Mitigate:2110.99
MW Contribution:42.6
Bus #Bus NameTypeMW Contribution
970053AG2-049 GEN
50/50
2.02
3138216PACIFIC
Solar/Wind Harmer
-0.003
316411AF1-147_GEN1
Solar/Wind Harmer
1.104
316415AF1-147_GEN2
Solar/Wind Harmer
1.104
3141426STAFORD
Solar/Wind Harmer
-0.002
3150411LDYSMT5
Adder
12.596
3150381LDYSMT2
Adder
12.055
972213AH1-691 GEN
Adder
2.039
972215AH1-692 GEN
Adder
2.039
316164AC1-076 GEN
Solar/Wind Harmer
0.886
944491AF1-114 GEN
Solar/Wind Harmer
3.014
316223AC1-118
Solar/Wind Harmer
0.269
972189AH1-679 GEN
Adder
1.455
3141813NORNECK
Solar/Wind Harmer
-0.01
962981AG1-147 GEN
Solar/Wind Harmer
4.183
3141783LANCAST
Solar/Wind Harmer
-0.006
3141783LANCAST
Solar/Wind Harmer
-0.004
3147346CASHSCORNER
Solar/Wind Harmer
0.147
3138133OCRAN
Solar/Wind Harmer
-0.003
3141913WHIT STONE
Solar/Wind Harmer
-0.009
316312AB1-027
Solar/Wind Harmer
0.319
316314AB2-024 C
Solar/Wind Harmer
0.807
316059AD1-063 C
Solar/Wind Harmer
0.213
957601AF2-054 GEN
Solar/Wind Harmer
0.282
3141873WAN 176
Solar/Wind Harmer
-0.002
315662AE1-191 GEN
Solar/Wind Harmer
1.137
315666AE1-190 GEN
Solar/Wind Harmer
0.284
3143873LANEXA
Solar/Wind Harmer
-0.006
3142433PROV 92
Adder
0.162
3142433PROV 92
Adder
0.162
971167AH1-042 GEN
Solar/Wind Harmer
9.035
315976AC1-164 GENA
Solar/Wind Harmer
9.907
316169AC1-164_GENC
Solar/Wind Harmer
8.558
315975AC1-164 GENB
Solar/Wind Harmer
0.293
316233AE1-074 FULL
Solar/Wind Harmer
0.251
971281AH1-106 GEN
Solar/Wind Harmer
1.517
971283AH1-107 GEN
Solar/Wind Harmer
1.517
971285AH1-108 GEN
Adder
0.626
957831AF2-077 GEN
Solar/Wind Harmer
0.28
3138283WHITEMARSH
Solar/Wind Harmer
0.014
316132AB2-190 GEN1
Solar/Wind Harmer
0.93
316369SG1_INVT
Solar/Wind Harmer
1.636
972265AH1-717 GEN
Adder
6.291
3151201GRAVEL4
Adder
5.897
3151191GRAVEL3
Adder
5.822
3151211GRAVEL5
Adder
5.822
971445AH1-216 GEN
Solar/Wind Harmer
5.611
3143316POE
Solar/Wind Harmer
-0.036
3151081ELIZAR1
Adder
7.342
3151091ELIZAR2
Adder
7.214
3152611GOSPORTB
Adder
1.02
3152621GOSPORTC
Adder
0.866
3152601GOSPORTA
Adder
0.798
315833AF1-017_GEN
Solar/Wind Harmer
1.7
316349AD2-085 GEN
Solar/Wind Harmer
0.796
316311AC2-079 GEN
Solar/Wind Harmer
4.513
957871AF2-081 GEN
Solar/Wind Harmer
4.471
319010AE1-072 C
Solar/Wind Harmer
1.806
316305AF2-043 C
Solar/Wind Harmer
0.269
3146406KITTY HAWK
Solar/Wind Harmer
0.007
315835AF2-110_GEN
Solar/Wind Harmer
1.113
313526AB2-022
Solar/Wind Harmer
0.239
3146486SUNBURY
Solar/Wind Harmer
-0.009
3146486SUNBURY
Solar/Wind Harmer
-0.009
316321Z2-027
Solar/Wind Harmer
0.239
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
3146396TANGLEW
Solar/Wind Harmer
0.163
316315AB2-025 C
Solar/Wind Harmer
0.237
315814AE2-033 C
Solar/Wind Harmer
8.149
941031AE2-094 GEN
Solar/Wind Harmer
16.374
944011AF1-069 GEN
Solar/Wind Harmer
5.131
315611Z1-036_GEN2
Solar/Wind Harmer
2.157
3130156CHOWAN
Solar/Wind Harmer
-0.009
3130156CHOWAN
Solar/Wind Harmer
-0.009
970673AG2-436 GEN
Solar/Wind Harmer
18.179
970673AG2-436 GEN
Solar/Wind Harmer
9.205
971967AH1-528 GEN
Solar/Wind Harmer
16.189
315816AE2-034 GEN
Solar/Wind Harmer
0.692
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315732AD1-074 GEN1
Solar/Wind Harmer
1.71
315733AD1-074 GEN2
Solar/Wind Harmer
1.71
315735AD1-075 GEN1
Solar/Wind Harmer
0.855
965291AG1-394 GEN
Solar/Wind Harmer
0.749
3146206CASHIE
Solar/Wind Harmer
-0.008
970601AG2-382 GEN
Solar/Wind Harmer
3.676
316318V4-068
Solar/Wind Harmer
0.209
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
5.232
970581AG2-369 GEN
Solar/Wind Harmer
4.499
3145513AHOSKIE
Solar/Wind Harmer
0.073
961941AG1-037 GEN
Solar/Wind Harmer
0.063
3145513AHOSKIE
Solar/Wind Harmer
-0.008
946281AF1-292 GEN
Solar/Wind Harmer
0.186
3146043SEABORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315607AA1-063A GEN
Solar/Wind Harmer
0.837
316087AB2-174 GEN
Solar/Wind Harmer
1.179
972205AH1-687 GEN
Adder
3.118
972193AH1-681 GEN
Adder
1.633
3151881LOWMORC
Adder
0.638
3151881LOWMORC
Adder
0.628
3151861LOWMORA
Adder
0.618
960921AF2-383 GEN
Solar/Wind Helper
0.139
205943AE1-185 GEN
Solar/Wind Helper
0.386
205956AE1-196_GEN
Solar/Wind Helper
0.384
205932AD2-116_GEN
Solar/Wind Helper
0.384
959381AF2-229 GEN
Solar/Wind Helper
0.256
237085AD2-009_GEN
Solar/Wind Helper
0.968
203975AE1-071-GEN
Solar/Wind Helper
1.709
233935AB2-179 C
Solar/Wind Helper
0.769
232436AB1-176 C
Solar/Wind Helper
0.027
233923SMA
Solar/Wind Helper
0.573
233990AG1-397 GEN
Solar/Wind Helper
0.018
232432Z2-076 GEN
Solar/Wind Helper
0.04
234033AF1-007_GEN
Solar/Wind Helper
4.196
964001AG1-254 GEN
Solar/Wind Helper
0.564
219914AD2-027 C
Solar/Wind Helper
0.068
227927V4-067C
Solar/Wind Helper
0.006
228754AB1-001 C
Solar/Wind Helper
0.015
219272CLEANLIGHT C
Solar/Wind Helper
0.015
219688LUMSOLAR_S C
Solar/Wind Helper
0.023
219607WPEMNERT C
Solar/Wind Helper
0.047
214067T20SOLAR
Solar/Wind Helper
0.007
20715728PEM_W1-119
Solar/Wind Helper
0.056
20715828PEM_W1-120
Solar/Wind Helper
0.056
207459AE1-142 C O1
Solar/Wind Helper
0.169
219620RIDERU C
Solar/Wind Helper
0.001
20675528CPH_W2-050
Solar/Wind Helper
0.05
218526CNTRALGAS2 C
Solar/Wind Helper
0.093
218524CNTRALGAS1 C
Solar/Wind Helper
0.092
966261AG1-495 GEN
Solar/Wind Helper
0.047
20675928HOL_W4-097
Solar/Wind Helper
0.029
207530AG1-191 GEN
Solar/Wind Helper
0.038
207484AF2-139 C O1
Solar/Wind Helper
0.048
20676328BVR_Y1-020
Solar/Wind Helper
0.015
20674828DL_W4-046
Solar/Wind Helper
0.004
207408W3-077 C
Solar/Wind Helper
0.048
20675728RH_W2-091
Solar/Wind Helper
0.078
20675128HRM_W1-127
Solar/Wind Helper
0.017
209116AE2-175 GEN
Solar/Wind Helper
1.001
961261AF2-417 GEN
Solar/Wind Helper
0.24
959431AF2-234 GEN
Solar/Wind Helper
0.464
964051AG1-259 GEN
Solar/Wind Helper
0.035
964061AG1-260 GEN
Solar/Wind Helper
0.035
959421AF2-233 GEN
Solar/Wind Helper
0.232
238208AF1-136 C
Solar/Wind Helper
0.089
3152131X4-039 ST
50/50
2.897
3152121X4-039 GT2
50/50
1.836
3140676OCCOQUN
Adder
0.27
972223AH1-696 GEN
Adder
8.401
3150151POSSMC1
Adder
1.063
3141346CRANES
Adder
0.118
3150221REMNGT2
Adder
12.484
3150211REMNGT1
Adder
12.401
972201AH1-685 GEN
Adder
2.154
3150281M RUN A
Adder
13.376
316006AB2-029 C
Solar/Wind Harmer
0.631
971685AH1-345 GEN
Solar/Wind Harmer
0.962
316045AC1-158 PL2
Solar/Wind Harmer
3.331
972197AH1-683 GEN
Adder
1.961
972219AH1-694 GEN
Adder
1.412
316254AC1-120 GEN1
Solar/Wind Harmer
0.848
957971AF2-091 GEN
Solar/Wind Harmer
1.025
315683AE1-153 C
Solar/Wind Harmer
9.493
972135AH1-637 GEN
Solar/Wind Harmer
1.018
966881AG1-559 GEN
Solar/Wind Harmer
0.105
3147666LOUISA
Solar/Wind Harmer
-0.04
316192AB2-158 GEN
Solar/Wind Harmer
1.181
316337AD2-073 GEN
Solar/Wind Harmer
0.265
3150351NORNECKC2
Adder
0.862
964211AG1-282 GEN
Solar/Wind Harmer
0.291
3141726DUNNSVL
Solar/Wind Harmer
-0.039
3151751LOISA D
Adder
5.583
962861AG1-135 GEN
Solar/Wind Harmer
3.609
961951AG1-038 GEN
Solar/Wind Harmer
1.263
3138133OCRAN
Solar/Wind Harmer
-0.006
3142416OLDCHRC
Solar/Wind Harmer
-0.024
3142416OLDCHRC
Solar/Wind Harmer
-0.009
3141766HARMONY
Solar/Wind Harmer
-0.002
971777AH1-397 GEN
Solar/Wind Harmer
1.109
3141843SHACKLE
Adder
0.429
3142433PROV 92
Solar/Wind Harmer
-0.037
3142433PROV 92
Adder
0.162
3142433PROV 92
Adder
0.162
3143096IRON208
Adder
0.349
3143526WINTERP
Solar/Wind Harmer
-0.048
3142543TWELFTH
Solar/Wind Harmer
-0.001
3150851SPRUNCC
Adder
0.383
944631AF1-128 GEN
Adder
39.551
3143226MDLTHAN
Solar/Wind Harmer
-0.009
316159AE1-175 C
Solar/Wind Harmer
0.248
971317AH1-138 GEN
Solar/Wind Harmer
1.154
970129AG2-093 GEN
Solar/Wind Harmer
2.097
316458AB2-190 GEN2
Solar/Wind Harmer
0.93
315671AE2-027_GEN
Solar/Wind Harmer
6.892
3138126ROCKLANDING
Solar/Wind Harmer
0.028
971069AG2-661 GEN
Solar/Wind Harmer
1.451
971647AH1-324 GEN
Solar/Wind Harmer
4.571
961611AG1-000B GEN
Solar/Wind Harmer
4.503
3151171GRAVELC
Adder
0.862
3145336SMITFLD
Solar/Wind Harmer
-0.036
316294AC1-161 GEN
Solar/Wind Harmer
2.927
970659AG2-427 GEN
Solar/Wind Harmer
4.796
316381AD1-082 GEN
Solar/Wind Harmer
0.827
316375AC2-012 GEN
Solar/Wind Harmer
3.114
3150981CHESPKA
Adder
1
970661AG2-428 GEN
Solar/Wind Harmer
9.562
944591AF1-124 GEN
Solar/Wind Harmer
41.052
316072AD1-144
Solar/Wind Harmer
0.182
316388AE2-253 GEN
Solar/Wind Harmer
0.603
939411AE1-173 GEN
Solar/Wind Harmer
44.674
3146456SLIGO L269
Solar/Wind Harmer
-0.009
316246AF1-032 C
Solar/Wind Harmer
0.181
940641AE2-051 GEN
Solar/Wind Harmer
8.364
316093AE2-104_GEN
Solar/Wind Harmer
2.589
3143336POWHATN
Solar/Wind Harmer
1.052
3146516WINFALL
Solar/Wind Harmer
-0.028
3146516WINFALL
Solar/Wind Harmer
-0.009
316336AC2-165 C
Solar/Wind Harmer
1.521
315800Z1-036_GEN1
Solar/Wind Harmer
2.157
3130156CHOWAN
Solar/Wind Harmer
-0.009
3145663CRESWEL
Solar/Wind Harmer
-0.024
971163AH1-040 GEN
Solar/Wind Harmer
8.02
970937AG2-583 GEN
Solar/Wind Harmer
6.075
316023GEN1_S
Solar/Wind Harmer
0.567
3146206CASHIE
Solar/Wind Harmer
-0.008
971547AH1-271 GEN
Solar/Wind Harmer
2.101
3145893MURPHYS
Solar/Wind Harmer
-0.033
3145893MURPHYS
Solar/Wind Harmer
0.249
970919AG2-571 GEN
Solar/Wind Harmer
2.655
970087AG2-069 GEN
Solar/Wind Harmer
7.848
3146173TUNIS
Solar/Wind Harmer
-0.008
960081AF2-299 GEN
Solar/Wind Harmer
0.934
3145683EARLEYS
Solar/Wind Harmer
-0.008
957481AF2-042 GEN
Solar/Wind Harmer
25.866
3146263WOODLND
Solar/Wind Harmer
-0.008
3147043LAWRENC
Adder
0.66
3144293JTRSVLE
Adder
0.228
972277AH1-723 GEN
Adder
42.597
23779801AA1-109
Solar/Wind Helper
0.217
223401AF1-299 GEN
Solar/Wind Helper
0.396
966131AG1-482 GEN
Solar/Wind Helper
0.063
237080AD1-060 GEN
Solar/Wind Helper
0.22
235062AE1-101 C1
Solar/Wind Helper
1.061
237038AE2-054 C
Solar/Wind Helper
0.173
233930AB2-032 GEN
Solar/Wind Helper
0.229
233915AB1-141 GEN
Solar/Wind Helper
0.302
232422X3-066 FULL
Solar/Wind Helper
0.069
233964AF2-378 GEN
Solar/Wind Helper
0.025
232426Y1-080 FULL
Solar/Wind Helper
0.023
232428Y3-058 C
Solar/Wind Helper
0.202
233998TM1NIN_3.36
Solar/Wind Helper
0.156
233954AC2-188 GEN
Solar/Wind Helper
0.139
232404W1-003 C
Solar/Wind Helper
0.303
233950AC2-186 GEN
Solar/Wind Helper
0.069
232434Z2-077 GEN
Solar/Wind Helper
0.076
233972AC1-094 C
Solar/Wind Helper
0.18
205941AD2-115 GEN
Solar/Wind Helper
0.301
230434AG1-499 GEN
Solar/Wind Helper
0.136
230511AF1-262
Solar/Wind Helper
0.009
219258KINSLEYDEP C
Solar/Wind Helper
0.045
228728W1-130C
Solar/Wind Helper
0.032
219904AC1-010 C
Solar/Wind Helper
0.036
219907AC1-030 C
Solar/Wind Helper
0.02
218660EHAMPSOLAR C
Solar/Wind Helper
0.019
219686LUMSOLAR_N C
Solar/Wind Helper
0.023
219304NAMERICA C
Solar/Wind Helper
0.077
20720728JCB_W1-129
Solar/Wind Helper
0.033
207445AB1-138_GEN
Solar/Wind Helper
0.061
963711AG1-223 GEN
Solar/Wind Helper
0.037
20714828MDF_W3-079
Solar/Wind Helper
0.076
219680HOPEWELLV C1
Solar/Wind Helper
0.002
207454AA2-184 E
Solar/Wind Helper
0.18
20715228NPK_W1-113
Solar/Wind Helper
0.045
20742028HF_AC1-207
Solar/Wind Helper
0.081
207528AF2-192 GEN
Solar/Wind Helper
0.044
20673628F1S_V4-069
Solar/Wind Helper
0.017
20675428EAM_W2-061
Solar/Wind Helper
0.009
218428ETC SOLAR C
Solar/Wind Helper
0.003
20676428JCR_X2-075
Solar/Wind Helper
0.039
217213AMBOY SO C
Solar/Wind Helper
0.016
217209CENTRL HS C
Solar/Wind Helper
0.005
217208PARK ELE C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.013
207437AD2-070 GEN
Solar/Wind Helper
0.079
207439AE1-081 C O1
Solar/Wind Helper
0.011
207518AF1-320_GEN
Solar/Wind Helper
0.897
20671928W4-073
Solar/Wind Helper
0.051
20675828AU_W4-064
Solar/Wind Helper
0.017
961301AF2-421 GEN
Solar/Wind Helper
0.241
963151AG1-164 GEN
Solar/Wind Helper
0.241
212266LOR1
Solar/Wind Helper
0.026
961341AF2-425 GEN
Solar/Wind Helper
0.236
212507AE2-042_GEN
Solar/Wind Helper
0.826
946731AF1-337 GEN
Solar/Wind Helper
0.232
209071AE2-133 GEN
Solar/Wind Helper
0.042
315693AD1-088 GEN
Solar/Wind Harmer
1.364
972289AH1-729 GEN
50/50
13.276
3150071POSSM 5
Adder
48.607
3150181POSSMC2
Adder
1.072
3150181POSSMC2
Adder
1.063
3150181POSSMC2
Adder
1.063
316447AC1-158 HLD
Solar/Wind Harmer
2.29
315651AD1-115 GEN
Solar/Wind Harmer
4.658
3150391LDYSMT3
Adder
12.533
972195AH1-682 GEN
Adder
1.647
315673AE1-157 GEN
Solar/Wind Harmer
7.721
957411AF2-035 GEN
Solar/Wind Harmer
4.574
970317AG2-208 GEN
Solar/Wind Harmer
4.447
316468AD1-105 GEN
Solar/Wind Harmer
1.109
966001AG1-469 GEN
Solar/Wind Harmer
0.184
316077AC2-138 C
Solar/Wind Harmer
0.205
3150341NORNECKC1
Adder
0.906
3150341NORNECKC1
Adder
0.898
3151731LOISA B
Adder
5.583
3151721LOISA A
Adder
5.554
958261AF2-120 GEN
Solar/Wind Harmer
3.734
316487AF1-042 GEN
Solar/Wind Harmer
1.263
966871AG1-558 GEN
Solar/Wind Harmer
0.288
966871AG1-558 GEN
Solar/Wind Harmer
0.099
3142296MT RD221
Adder
0.269
316441AF1-014 GEN
Solar/Wind Harmer
0.636
3142366NRTHEST
Adder
0.273
3150691DARBY 3
Adder
6.022
3150701DARBY 4
Adder
6.008
3150681DARBY 2
Adder
6.001
3150671DARBY 1
Adder
5.994
316075AC2-137 C
Solar/Wind Harmer
0.253
3143526WINTERP
Solar/Wind Harmer
-0.048
3142946ENON
Solar/Wind Harmer
-0.001
971223AH1-071 GEN
Solar/Wind Harmer
1.164
944641AF1-129 GEN
Adder
39.124
316240AF1-291 C
Solar/Wind Harmer
0.277
316033AB2-134 GEN
Solar/Wind Harmer
2.953
315697AD1-025 GEN
Solar/Wind Harmer
1.852
316236AE1-162_GEN
Solar/Wind Harmer
0.273
970657AG2-426 GEN
Solar/Wind Harmer
2.816
970657AG2-426 GEN
Solar/Wind Harmer
0.589
316036AC1-147 C
Solar/Wind Harmer
0.243
3150991CHESPKB
Adder
0.839
3150991CHESPKB
Adder
0.819
3142956BIRDNECK
Solar/Wind Harmer
0.482
316316AC1-027 C
Solar/Wind Harmer
0.276
316185AD1-033 GEN
Solar/Wind Harmer
0.947
3145506HICKORY
Solar/Wind Harmer
-0.036
3145506HICKORY
Solar/Wind Harmer
-0.021
3145506HICKORY
Solar/Wind Harmer
-0.005
316339AD2-160 GEN
Solar/Wind Harmer
0.603
316018AA1-139 ULT2
Solar/Wind Harmer
0.766
316017AA1-139 ULT1
Solar/Wind Harmer
0.724
3137176SLIGO L2192
Solar/Wind Harmer
-0.035
3146456SLIGO L269
Solar/Wind Harmer
1.055
3130086AYDLETT
Solar/Wind Harmer
-0.036
3146386ELIZ CT
Solar/Wind Harmer
-0.009
316431W1029_GEN1
Solar/Wind Harmer
1.599
316433W1029_GEN2
Solar/Wind Harmer
1.599
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3144356SAPONY
Solar/Wind Harmer
0.306
315742AE1-103 GEN
Solar/Wind Harmer
0.91
3146376EDENTON
Solar/Wind Harmer
0.257
3146376EDENTON
Solar/Wind Harmer
0.257
972185AH1-677 GEN
Adder
4.302
972187AH1-678 GEN
Adder
2.17
970933AG2-581 GEN
Solar/Wind Harmer
7.988
316065AD1-022 GEN
Solar/Wind Harmer
4.211
3145893MURPHYS
Solar/Wind Harmer
0.234
3145893MURPHYS
Solar/Wind Harmer
-0.015
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
970099AG2-077 GEN
Solar/Wind Harmer
10.347
316181AB2-040 GEN
Solar/Wind Harmer
1.151
3144293JTRSVLE
Adder
0.228
3144293JTRSVLE
Adder
0.192
226929AD2-058 GEN
Solar/Wind Helper
0.143
237025AB1-124 C
Solar/Wind Helper
0.193
237006AB1-125 GEN
Solar/Wind Helper
0.145
23777801MSM_W1-116
Solar/Wind Helper
0.13
237034AC2-136 C
Solar/Wind Helper
0.204
205916AD1-020 GEN
Solar/Wind Helper
1.477
208835TUHI V3-051
Solar/Wind Helper
0.019
208835TUHI V3-051
Solar/Wind Helper
0.019
237001AB1-127_GEN
Solar/Wind Helper
0.306
237002AB1-128_GEN
Solar/Wind Helper
0.297
235063AE1-101 C2
Solar/Wind Helper
1.061
20390526W1-045 C
Solar/Wind Helper
0.251
23777901MDS_W4-102
Solar/Wind Helper
0.105
235020AA1-095 C
Solar/Wind Helper
0.029
233933AB2-153 GEN
Solar/Wind Helper
0.14
233944AB2-135 GEN
Solar/Wind Helper
0.354
232424Y1-079 C
Solar/Wind Helper
0.07
233987AB2-037 GEN
Solar/Wind Helper
1.402
234036AF2-325 C
Solar/Wind Helper
0.025
233946AB2-136 GEN
Solar/Wind Helper
0.34
233901CHERRYDALE C
Solar/Wind Helper
0.139
232408W1-005 C
Solar/Wind Helper
0.303
232410W1-006 C
Solar/Wind Helper
0.303
233939AC1-091 C
Solar/Wind Helper
0.209
233970AC1-092 C
Solar/Wind Helper
0.209
230433AD2-135 GEN
Solar/Wind Helper
0.01
219921AF1-264
Solar/Wind Helper
0.03
230407AD2-065 C
Solar/Wind Helper
0.024
219615MILLCREEK C
Solar/Wind Helper
0.016
963401AG1-189 GEN
Solar/Wind Helper
0.033
963391AG1-188 GEN
Solar/Wind Helper
0.048
20714928UPF_X1-085
Solar/Wind Helper
0.003
20720628TIN_W1-124
Solar/Wind Helper
0.11
20716928W4-060COL
Solar/Wind Helper
0.03
20673828FLE_V3-070
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.009
207442AE1-156 GEN
Solar/Wind Helper
0.188
20676128MHD_W3-029
Solar/Wind Helper
0.055
20671828STAW2-080
Solar/Wind Helper
0.015
217081WEATEXAS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.004
217204WCALDSOLAR C
Solar/Wind Helper
0.002
207471AF2-354 C
Solar/Wind Helper
0.096
20674928WA_W3-044
Solar/Wind Helper
0.056
964851AG1-348 GEN
Solar/Wind Helper
0.046
20674128FR_U2-059
Solar/Wind Helper
0.002
20676228FRD_X1-012
Solar/Wind Helper
0.052
966111AG1-480 GEN
Solar/Wind Helper
0.025
211065PSPA IPP
Solar/Wind Helper
0.085
211065PSPA IPP
Solar/Wind Helper
0.085
208972BECR K09
Solar/Wind Helper
0.177
961431AF2-434 GEN
Solar/Wind Helper
0.235
209029WAYMART-WD
Solar/Wind Helper
0.441
209054AE2-059 GEN
Solar/Wind Helper
0.042
946751AF1-339 GEN
Solar/Wind Helper
0.232
209137AF2-361 C
Solar/Wind Helper
0.706
3152111X4-039 GT1
50/50
1.841
315747AE2-019 GEN
50/50
13.211
963691AG1-221 GEN
Solar/Wind Harmer
2.318
971455AH1-223 GEN
Solar/Wind Harmer
2.318
3141196NOKESVL
Solar/Wind Harmer
-0.048
3150151POSSMC1
Adder
1.063
3150151POSSMC1
Adder
1.063
3150231REMNGT3
Adder
13.478
3150241REMNGT4
Adder
12.566
972199AH1-684 GEN
Adder
1.905
972217AH1-693 GEN
Adder
1.657
3150301M RUN C
Adder
13.368
3150291M RUN B
Adder
13.268
3150331BIRCHWDA
Adder
16.45
3141316ARNOLDS
Adder
0.227
316044AC1-158 PL1
Solar/Wind Harmer
1.041
316450AC1-158 RIC
Solar/Wind Harmer
0.278
3150401LDYSMT4
Adder
12.557
3150371LDYSMT1
Adder
12.133
316170AC1-121 GEN2
Solar/Wind Harmer
0.283
966881AG1-559 GEN
Solar/Wind Harmer
0.306
970737AG2-469 GEN
Solar/Wind Harmer
5.052
3132273ORANGE
Solar/Wind Harmer
-0.002
3141906WESTMOR
Solar/Wind Harmer
-0.004
971781AH1-399 GEN
Solar/Wind Harmer
0.614
3147666LOUISA
Solar/Wind Harmer
-0.023
3150351NORNECKC2
Adder
0.877
3151761LOISA E
Adder
11.381
972183AH1-676 GEN
Adder
91.775
316404AE1-155 C
Solar/Wind Harmer
1.859
316484AD2-074 GEN
Solar/Wind Harmer
2.414
970009AG2-005 GEN
Solar/Wind Harmer
1.199
316473AC1-191 GEN
Solar/Wind Harmer
1.031
962971AG1-146 GEN
Solar/Wind Harmer
1.793
3142416OLDCHRC
Solar/Wind Harmer
0.953
3141766HARMONY
Solar/Wind Harmer
0.84
316156AD2-030 GEN
Solar/Wind Harmer
0.252
3141873WAN 176
Solar/Wind Harmer
1.12
316280AD1-041 GEN
Solar/Wind Harmer
0.711
316203AE2-005 GEN
Solar/Wind Harmer
3.975
3141843SHACKLE
Adder
0.429
970293AG2-193 GEN
Solar/Wind Harmer
1.175
3142433PROV 92
Adder
0.162
3142433PROV 92
Adder
0.162
3143096IRON208
Adder
0.349
3143096IRON208
Adder
0.342
3142946ENON
Solar/Wind Harmer
-0.003
3150861SPRUNCD
Adder
0.383
316382AG1-145 C
Solar/Wind Harmer
0.279
970133AG2-095 GEN
Solar/Wind Harmer
1.038
970129AG2-093 GEN
Solar/Wind Harmer
5.177
3150921YORKTN3
Adder
2.053
315778AD1-151 GEN
Solar/Wind Harmer
7.946
965281AG1-393 GEN
Solar/Wind Harmer
1.147
3144216WINCHST
Adder
0.308
315839AE2-212 C
Solar/Wind Harmer
0.276
961611AG1-000B GEN
Solar/Wind Harmer
1.921
3151221GRAVEL6
Adder
5.89
3151171GRAVELC
Adder
1.133
3145336SMITFLD
Solar/Wind Harmer
-0.004
315813AE1-149 C
Solar/Wind Harmer
5.666
315773AC2-141 GEN
Solar/Wind Harmer
3.785
970659AG2-427 GEN
Solar/Wind Harmer
0.85
316083AB2-161 GEN
Solar/Wind Harmer
1.464
3144536CHRHLND
Solar/Wind Harmer
-0.001
3151101ELIZAR3
Adder
7.435
970661AG2-428 GEN
Solar/Wind Harmer
1.695
3144873MCLAUGH
Solar/Wind Harmer
0
944581AF1-123 GEN
Solar/Wind Harmer
40.904
944601AF1-125 GEN
Solar/Wind Harmer
40.266
3146456SLIGO L269
Solar/Wind Harmer
-0.009
971153AH1-033 GEN
Solar/Wind Harmer
1.089
316320Y1-086
Solar/Wind Harmer
0.52
316313AB2-026
Solar/Wind Harmer
0.239
316258AE1-075 C
Solar/Wind Harmer
0.215
316405AF2-144 C
Solar/Wind Harmer
0.227
3143336POWHATN
Solar/Wind Harmer
0.895
316435W1029_GEN3
Solar/Wind Harmer
1.599
3146516WINFALL
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3145273HOLLAND
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.009
315614AA2-178 GEN
Solar/Wind Harmer
0.923
971157AH1-035 GEN
Solar/Wind Harmer
1.059
3156081AA2-088 GEN
Solar/Wind Harmer
2.747
315737AD1-076 GEN
Solar/Wind Harmer
1.607
316365GEN2_N
Solar/Wind Harmer
0.567
3146206CASHIE
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.059
3145893MURPHYS
Solar/Wind Harmer
-0.008
970917AG2-570 GEN
Solar/Wind Harmer
20.974
957521AF2-046 GEN
Solar/Wind Harmer
6.6
961681AG1-008 GEN
Solar/Wind Harmer
6.6
3146173TUNIS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1.123
316463AE2-346 GEN
Solar/Wind Harmer
0.135
316140AB2-099
Solar/Wind Harmer
0.056
962331AG1-082 GEN
Solar/Wind Harmer
1.04
966621AG1-532 GEN
Solar/Wind Harmer
0.168
3146263WOODLND
Solar/Wind Harmer
-0.008
313506AB2-031 GEN
Solar/Wind Harmer
0.663
3144293JTRSVLE
Adder
0.228
972255AH1-712 GEN
Adder
36.554
3151861LOWMORA
Adder
0.643
226910AB2-157 C
Solar/Wind Helper
0.02
227287AC2-120 GEN
Solar/Wind Helper
0.489
237030AB1-096 C
Solar/Wind Helper
0.083
223402AF1-300 C
Solar/Wind Helper
0.396
205917AD1-020 ES
Solar/Wind Helper
0.318
238221AF1-254 C O1
Solar/Wind Helper
0.179
235067AD1-061 GEN
Solar/Wind Helper
0.311
233982AB2-133 GEN
Solar/Wind Helper
0.215
233918AB1-142 GEN
Solar/Wind Helper
0.302
233994AC2-023 GEN
Solar/Wind Helper
0.575
233996TM1833_GEN
Solar/Wind Helper
0.156
233997TMININ_4.2
Solar/Wind Helper
0.156
233952AC2-187 GEN
Solar/Wind Helper
0.139
232406W1-004 FULL
Solar/Wind Helper
0.303
233940AF2-379 C
Solar/Wind Helper
0.037
234015AF2-250 C
Solar/Wind Helper
0.023
233971AC1-093 C
Solar/Wind Helper
0.213
230430AE1-229_GEN
Solar/Wind Helper
1.988
230415AB2-049 C
Solar/Wind Helper
0.018
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219766PARADISE C
Solar/Wind Helper
0.032
219912AD2-042 GEN
Solar/Wind Helper
0.088
228729W2-030 C
Solar/Wind Helper
0.065
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.007
219906AC1-017 C
Solar/Wind Helper
0.025
219348LDSOLAR C
Solar/Wind Helper
0.067
959561AF2-247 GEN
Solar/Wind Helper
0.012
20716028EGP_W2-019
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.037
20715028HAN_X4-015
Solar/Wind Helper
0.033
219276PARKLANDSO C
Solar/Wind Helper
0.052
20714528FRN_Y2-051
Solar/Wind Helper
0.033
20720528MAN_W1-024
Solar/Wind Helper
0.016
219612MATRIX C
Solar/Wind Helper
0.014
218438BLK ROCK C
Solar/Wind Helper
0.016
20673728F2S_V4-070
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.042
219919AE1-041 FULL
Solar/Wind Helper
0.002
219249CENTRALDIV C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
217169METRODIV C
Solar/Wind Helper
0.002
20676728BRNX1-095
Solar/Wind Helper
0.017
207510AF2-138 C
Solar/Wind Helper
0.046
20674628WNG_W3-110
Solar/Wind Helper
0.051
963161AG1-165 GEN
Solar/Wind Helper
0.241
963071AG1-156 GEN
Solar/Wind Helper
0.78
209027LOR2_Q27
Solar/Wind Helper
0.555
961331AF2-424 GEN
Solar/Wind Helper
0.236
961421AF2-433 GEN
Solar/Wind Helper
0.235
957921AF2-086 GEN
Solar/Wind Helper
0.233
946691AF1-333 GEN
Solar/Wind Helper
0.232
946741AF1-338 GEN
Solar/Wind Helper
0.232
209067AE2-060 GEN
Solar/Wind Helper
0.042
NYPJM->LTFIMP_NY
CLTF
2.566
LGEELTFEXP_LGEE->PJM
CLTF
1.801
WECLTFEXP_WEC->PJM
CLTF
0.96
LAGNLTFEXP_LAGN->PJM
CLTF
6.303
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.503
TVALTFEXP_TVA->PJM
CLTF
3.177
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.419
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.556
MECLTFEXP_MEC->PJM
CLTF
4.438
SIGELTFEXP_SIGE->PJM
CLTF
0.139
CPLELTFEXP_CPLE->PJM
CLTF
5.037
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.853

Details for 6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019F_SRT-SL


Base Case Flowgate

Area:DVP
Facility Description:
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019F_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.48 %
Rating:1809.0 MVA
Rating Type:C
MVA to Mitigate:2034.78
MW Contribution:35.15
Bus #Bus NameTypeMW Contribution
972289AH1-729 GEN
50/50
13.169
315651AD1-115 GEN
Solar/Wind Harmer
3.939
316447AC1-158 HLD
Solar/Wind Harmer
1.879
966001AG1-469 GEN
Solar/Wind Harmer
0.153
3151731LOISA B
Adder
4.652
3151721LOISA A
Adder
4.628
3150071POSSM 5
Adder
32.578
3150181POSSMC2
Adder
0.719
3150181POSSMC2
Adder
0.713
3150181POSSMC2
Adder
0.713
3150391LDYSMT3
Adder
9.175
972195AH1-682 GEN
Adder
1.206
315673AE1-157 GEN
Solar/Wind Harmer
5.71
957411AF2-035 GEN
Solar/Wind Harmer
3.403
970317AG2-208 GEN
Solar/Wind Harmer
3.309
316468AD1-105 GEN
Solar/Wind Harmer
0.83
316077AC2-138 C
Solar/Wind Harmer
0.155
3150341NORNECKC1
Adder
0.684
3150341NORNECKC1
Adder
0.679
966871AG1-558 GEN
Solar/Wind Harmer
0.22
966871AG1-558 GEN
Solar/Wind Harmer
0.075
958261AF2-120 GEN
Solar/Wind Harmer
2.834
3142296MT RD221
Adder
0.207
316487AF1-042 GEN
Solar/Wind Harmer
0.961
971223AH1-071 GEN
Solar/Wind Harmer
0.912
3143526WINTERP
Solar/Wind Harmer
-0.038
3142366NRTHEST
Adder
0.211
3150691DARBY 3
Adder
4.65
3150701DARBY 4
Adder
4.64
3150681DARBY 2
Adder
4.634
3150671DARBY 1
Adder
4.629
316075AC2-137 C
Solar/Wind Harmer
0.196
316441AF1-014 GEN
Solar/Wind Harmer
0.488
3142946ENON
Solar/Wind Harmer
-0.001
944641AF1-129 GEN
Adder
30.436
316240AF1-291 C
Solar/Wind Harmer
0.216
316033AB2-134 GEN
Solar/Wind Harmer
2.301
315697AD1-025 GEN
Solar/Wind Harmer
1.443
316236AE1-162_GEN
Solar/Wind Harmer
0.214
970657AG2-426 GEN
Solar/Wind Harmer
2.206
970657AG2-426 GEN
Solar/Wind Harmer
0.461
316036AC1-147 C
Solar/Wind Harmer
0.19
3150991CHESPKB
Adder
0.657
3150991CHESPKB
Adder
0.642
3142956BIRDNECK
Solar/Wind Harmer
0.378
316316AC1-027 C
Solar/Wind Harmer
0.216
316185AD1-033 GEN
Solar/Wind Harmer
0.743
3145506HICKORY
Solar/Wind Harmer
-0.028
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
316339AD2-160 GEN
Solar/Wind Harmer
0.474
316018AA1-139 ULT2
Solar/Wind Harmer
0.601
316017AA1-139 ULT1
Solar/Wind Harmer
0.568
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.828
3130086AYDLETT
Solar/Wind Harmer
-0.028
3146386ELIZ CT
Solar/Wind Harmer
-0.007
971761AH1-387 GEN
Solar/Wind Harmer
3.885
316431W1029_GEN1
Solar/Wind Harmer
1.259
316433W1029_GEN2
Solar/Wind Harmer
1.259
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3144356SAPONY
Solar/Wind Harmer
0.242
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
315742AE1-103 GEN
Solar/Wind Harmer
0.719
3146376EDENTON
Solar/Wind Harmer
0.203
3146376EDENTON
Solar/Wind Harmer
0.203
972185AH1-677 GEN
Adder
3.421
972187AH1-678 GEN
Adder
1.728
970933AG2-581 GEN
Solar/Wind Harmer
6.373
3146776BUCKING
Solar/Wind Harmer
-0.027
3146776BUCKING
Solar/Wind Harmer
-0.002
316065AD1-022 GEN
Solar/Wind Harmer
3.351
3145893MURPHYS
Solar/Wind Harmer
0.187
3145893MURPHYS
Solar/Wind Harmer
-0.012
970301AG2-198 GEN
Solar/Wind Harmer
3.335
971741AH1-377 GEN
Solar/Wind Harmer
7.747
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
3144293JTRSVLE
Adder
0.186
3144293JTRSVLE
Adder
0.157
237025AB1-124 C
Solar/Wind Helper
0.233
237006AB1-125 GEN
Solar/Wind Helper
0.175
23777801MSM_W1-116
Solar/Wind Helper
0.156
237034AC2-136 C
Solar/Wind Helper
0.239
205916AD1-020 GEN
Solar/Wind Helper
1.658
237001AB1-127_GEN
Solar/Wind Helper
0.342
237002AB1-128_GEN
Solar/Wind Helper
0.33
226929AD2-058 GEN
Solar/Wind Helper
0.078
208835TUHI V3-051
Solar/Wind Helper
0.02
208835TUHI V3-051
Solar/Wind Helper
0.02
235063AE1-101 C2
Solar/Wind Helper
1.169
20390526W1-045 C
Solar/Wind Helper
0.277
23777901MDS_W4-102
Solar/Wind Helper
0.113
235020AA1-095 C
Solar/Wind Helper
0.03
233933AB2-153 GEN
Solar/Wind Helper
0.141
233944AB2-135 GEN
Solar/Wind Helper
0.356
232424Y1-079 C
Solar/Wind Helper
0.07
233987AB2-037 GEN
Solar/Wind Helper
1.409
233946AB2-136 GEN
Solar/Wind Helper
0.342
234036AF2-325 C
Solar/Wind Helper
0.025
233901CHERRYDALE C
Solar/Wind Helper
0.14
232408W1-005 C
Solar/Wind Helper
0.305
232410W1-006 C
Solar/Wind Helper
0.305
233939AC1-091 C
Solar/Wind Helper
0.21
233970AC1-092 C
Solar/Wind Helper
0.21
230433AD2-135 GEN
Solar/Wind Helper
0.01
230407AD2-065 C
Solar/Wind Helper
0.024
219921AF1-264
Solar/Wind Helper
0.03
219615MILLCREEK C
Solar/Wind Helper
0.016
963401AG1-189 GEN
Solar/Wind Helper
0.033
963391AG1-188 GEN
Solar/Wind Helper
0.048
20714928UPF_X1-085
Solar/Wind Helper
0.003
20720628TIN_W1-124
Solar/Wind Helper
0.11
20716928W4-060COL
Solar/Wind Helper
0.03
20673828FLE_V3-070
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.009
207442AE1-156 GEN
Solar/Wind Helper
0.187
20676128MHD_W3-029
Solar/Wind Helper
0.055
20671828STAW2-080
Solar/Wind Helper
0.015
217081WEATEXAS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.004
217204WCALDSOLAR C
Solar/Wind Helper
0.002
207471AF2-354 C
Solar/Wind Helper
0.096
20674928WA_W3-044
Solar/Wind Helper
0.056
964851AG1-348 GEN
Solar/Wind Helper
0.046
20674128FR_U2-059
Solar/Wind Helper
0.002
20676228FRD_X1-012
Solar/Wind Helper
0.052
966111AG1-480 GEN
Solar/Wind Helper
0.025
211065PSPA IPP
Solar/Wind Helper
0.084
211065PSPA IPP
Solar/Wind Helper
0.084
208972BECR K09
Solar/Wind Helper
0.176
961431AF2-434 GEN
Solar/Wind Helper
0.233
209029WAYMART-WD
Solar/Wind Helper
0.437
209137AF2-361 C
Solar/Wind Helper
0.703
209054AE2-059 GEN
Solar/Wind Helper
0.042
946751AF1-339 GEN
Solar/Wind Helper
0.23
970099AG2-077 GEN
Solar/Wind Harmer
2.284
3138216PACIFIC
Solar/Wind Harmer
-0.003
316411AF1-147_GEN1
Solar/Wind Harmer
1.076
316415AF1-147_GEN2
Solar/Wind Harmer
1.076
970053AG2-049 GEN
Adder
1.475
316164AC1-076 GEN
Solar/Wind Harmer
0.73
3147346CASHSCORNER
Solar/Wind Harmer
0.123
3141426STAFORD
Solar/Wind Harmer
-0.002
3150411LDYSMT5
Adder
9.22
3150381LDYSMT2
Adder
8.824
972213AH1-691 GEN
Adder
1.493
972215AH1-692 GEN
Adder
1.493
944491AF1-114 GEN
Solar/Wind Harmer
2.206
316223AC1-118
Solar/Wind Harmer
0.2
972189AH1-679 GEN
Adder
1.104
3141813NORNECK
Solar/Wind Harmer
-0.007
962981AG1-147 GEN
Solar/Wind Harmer
3.188
316233AE1-074 FULL
Solar/Wind Harmer
0.196
971281AH1-106 GEN
Solar/Wind Harmer
1.184
971283AH1-107 GEN
Solar/Wind Harmer
1.184
316312AB1-027
Solar/Wind Harmer
0.245
3141783LANCAST
Solar/Wind Harmer
-0.004
3141783LANCAST
Solar/Wind Harmer
-0.003
3138133OCRAN
Solar/Wind Harmer
-0.002
3141913WHIT STONE
Solar/Wind Harmer
-0.007
971285AH1-108 GEN
Adder
0.486
316314AB2-024 C
Solar/Wind Harmer
0.62
316059AD1-063 C
Solar/Wind Harmer
0.164
3143873LANEXA
Solar/Wind Harmer
-0.004
315662AE1-191 GEN
Solar/Wind Harmer
0.873
315666AE1-190 GEN
Solar/Wind Harmer
0.218
957601AF2-054 GEN
Solar/Wind Harmer
0.217
3141873WAN 176
Solar/Wind Harmer
-0.001
315976AC1-164 GENA
Solar/Wind Harmer
7.645
316169AC1-164_GENC
Solar/Wind Harmer
6.604
315975AC1-164 GENB
Solar/Wind Harmer
0.226
3142433PROV 92
Adder
0.125
3142433PROV 92
Adder
0.125
971167AH1-042 GEN
Solar/Wind Harmer
6.965
957831AF2-077 GEN
Solar/Wind Harmer
0.216
3138283WHITEMARSH
Solar/Wind Harmer
0.011
316132AB2-190 GEN1
Solar/Wind Harmer
0.724
316369SG1_INVT
Solar/Wind Harmer
1.275
972265AH1-717 GEN
Adder
4.91
3151201GRAVEL4
Adder
4.603
3151191GRAVEL3
Adder
4.545
3151211GRAVEL5
Adder
4.545
3143316POE
Solar/Wind Harmer
-0.028
971445AH1-216 GEN
Solar/Wind Harmer
4.385
3151081ELIZAR1
Adder
5.753
3151091ELIZAR2
Adder
5.653
3152611GOSPORTB
Adder
0.799
3152621GOSPORTC
Adder
0.678
3152601GOSPORTA
Adder
0.626
315833AF1-017_GEN
Solar/Wind Harmer
1.334
316349AD2-085 GEN
Solar/Wind Harmer
0.624
316311AC2-079 GEN
Solar/Wind Harmer
3.541
957871AF2-081 GEN
Solar/Wind Harmer
3.509
319010AE1-072 C
Solar/Wind Harmer
1.418
316305AF2-043 C
Solar/Wind Harmer
0.211
3146406KITTY HAWK
Solar/Wind Harmer
0.006
315835AF2-110_GEN
Solar/Wind Harmer
0.874
313526AB2-022
Solar/Wind Harmer
0.188
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.188
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.128
316315AB2-025 C
Solar/Wind Harmer
0.187
941031AE2-094 GEN
Solar/Wind Harmer
12.98
944011AF1-069 GEN
Solar/Wind Harmer
4.067
315814AE2-033 C
Solar/Wind Harmer
6.44
315611Z1-036_GEN2
Solar/Wind Harmer
1.702
970673AG2-436 GEN
Solar/Wind Harmer
14.439
970673AG2-436 GEN
Solar/Wind Harmer
7.311
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
971967AH1-528 GEN
Solar/Wind Harmer
12.878
315816AE2-034 GEN
Solar/Wind Harmer
0.549
972205AH1-687 GEN
Adder
2.574
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315732AD1-074 GEN1
Solar/Wind Harmer
1.359
315733AD1-074 GEN2
Solar/Wind Harmer
1.359
315735AD1-075 GEN1
Solar/Wind Harmer
0.68
971845AH1-439 GEN
Solar/Wind Harmer
3.571
965291AG1-394 GEN
Solar/Wind Harmer
0.596
970285AG2-188 GEN
Solar/Wind Harmer
5.876
3138266HYDRAULIC
Solar/Wind Harmer
0
3138266HYDRAULIC
Solar/Wind Harmer
0
970085AG2-068 GEN
Solar/Wind Harmer
4.185
970581AG2-369 GEN
Solar/Wind Harmer
3.599
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.928
316318V4-068
Solar/Wind Harmer
0.167
3145893MURPHYS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
-0.007
972193AH1-681 GEN
Adder
1.348
960921AF2-383 GEN
Solar/Wind Helper
0.147
959381AF2-229 GEN
Solar/Wind Helper
0.283
205943AE1-185 GEN
Solar/Wind Helper
0.409
205956AE1-196_GEN
Solar/Wind Helper
0.406
205932AD2-116_GEN
Solar/Wind Helper
0.406
237085AD2-009_GEN
Solar/Wind Helper
1.049
203975AE1-071-GEN
Solar/Wind Helper
1.871
233935AB2-179 C
Solar/Wind Helper
0.773
232436AB1-176 C
Solar/Wind Helper
0.027
233923SMA
Solar/Wind Helper
0.576
233990AG1-397 GEN
Solar/Wind Helper
0.018
232432Z2-076 GEN
Solar/Wind Helper
0.04
234033AF1-007_GEN
Solar/Wind Helper
4.217
964001AG1-254 GEN
Solar/Wind Helper
0.565
219914AD2-027 C
Solar/Wind Helper
0.068
228754AB1-001 C
Solar/Wind Helper
0.015
227927V4-067C
Solar/Wind Helper
0.006
219272CLEANLIGHT C
Solar/Wind Helper
0.015
219688LUMSOLAR_S C
Solar/Wind Helper
0.023
219607WPEMNERT C
Solar/Wind Helper
0.047
214067T20SOLAR
Solar/Wind Helper
0.007
20715728PEM_W1-119
Solar/Wind Helper
0.056
20715828PEM_W1-120
Solar/Wind Helper
0.056
207459AE1-142 C O1
Solar/Wind Helper
0.169
219620RIDERU C
Solar/Wind Helper
0.001
20675528CPH_W2-050
Solar/Wind Helper
0.05
218526CNTRALGAS2 C
Solar/Wind Helper
0.092
218524CNTRALGAS1 C
Solar/Wind Helper
0.092
966261AG1-495 GEN
Solar/Wind Helper
0.047
20675928HOL_W4-097
Solar/Wind Helper
0.028
207530AG1-191 GEN
Solar/Wind Helper
0.037
207484AF2-139 C O1
Solar/Wind Helper
0.048
20676328BVR_Y1-020
Solar/Wind Helper
0.015
20674828DL_W4-046
Solar/Wind Helper
0.004
207408W3-077 C
Solar/Wind Helper
0.048
20675728RH_W2-091
Solar/Wind Helper
0.078
20675128HRM_W1-127
Solar/Wind Helper
0.017
209116AE2-175 GEN
Solar/Wind Helper
0.994
961261AF2-417 GEN
Solar/Wind Helper
0.238
959431AF2-234 GEN
Solar/Wind Helper
0.459
964051AG1-259 GEN
Solar/Wind Helper
0.034
964061AG1-260 GEN
Solar/Wind Helper
0.034
959421AF2-233 GEN
Solar/Wind Helper
0.229
238208AF1-136 C
Solar/Wind Helper
0.089
3152111X4-039 GT1
50/50
1.829
315747AE2-019 GEN
50/50
12.54
963691AG1-221 GEN
Solar/Wind Harmer
2.26
971455AH1-223 GEN
Solar/Wind Harmer
2.26
3141196NOKESVL
Solar/Wind Harmer
-0.043
3150231REMNGT3
Adder
11.81
3150241REMNGT4
Adder
11.012
972199AH1-684 GEN
Adder
1.67
972217AH1-693 GEN
Adder
1.452
3150301M RUN C
Adder
11.698
3150291M RUN B
Adder
11.611
316170AC1-121 GEN2
Solar/Wind Harmer
0.237
316044AC1-158 PL1
Solar/Wind Harmer
0.855
316450AC1-158 RIC
Solar/Wind Harmer
0.228
3132273ORANGE
Solar/Wind Harmer
-0.002
3147666LOUISA
Solar/Wind Harmer
-0.018
3151761LOISA E
Adder
9.484
972183AH1-676 GEN
Adder
76.571
3150151POSSMC1
Adder
0.713
3150151POSSMC1
Adder
0.713
3150331BIRCHWDA
Adder
11.674
3150401LDYSMT4
Adder
9.192
3150371LDYSMT1
Adder
8.882
3141316ARNOLDS
Adder
0.162
966881AG1-559 GEN
Solar/Wind Harmer
0.227
970737AG2-469 GEN
Solar/Wind Harmer
3.736
971781AH1-399 GEN
Solar/Wind Harmer
0.459
3141906WESTMOR
Solar/Wind Harmer
-0.003
3150351NORNECKC2
Adder
0.662
316473AC1-191 GEN
Solar/Wind Harmer
0.788
316404AE1-155 C
Solar/Wind Harmer
1.411
316484AD2-074 GEN
Solar/Wind Harmer
1.837
970009AG2-005 GEN
Solar/Wind Harmer
0.912
962971AG1-146 GEN
Solar/Wind Harmer
1.366
3142416OLDCHRC
Solar/Wind Harmer
0.734
970293AG2-193 GEN
Solar/Wind Harmer
0.907
3150861SPRUNCD
Adder
0.297
3141766HARMONY
Solar/Wind Harmer
0.645
316203AE2-005 GEN
Solar/Wind Harmer
3.054
316280AD1-041 GEN
Solar/Wind Harmer
0.546
316156AD2-030 GEN
Solar/Wind Harmer
0.193
3141873WAN 176
Solar/Wind Harmer
0.86
3141843SHACKLE
Adder
0.329
3143096IRON208
Adder
0.27
3143096IRON208
Adder
0.265
3142433PROV 92
Adder
0.125
3142433PROV 92
Adder
0.125
3142946ENON
Solar/Wind Harmer
-0.002
316382AG1-145 C
Solar/Wind Harmer
0.216
970133AG2-095 GEN
Solar/Wind Harmer
0.807
970129AG2-093 GEN
Solar/Wind Harmer
4.029
965281AG1-393 GEN
Solar/Wind Harmer
0.893
315778AD1-151 GEN
Solar/Wind Harmer
6.188
3150921YORKTN3
Adder
1.597
315839AE2-212 C
Solar/Wind Harmer
0.215
3144216WINCHST
Adder
0.239
961611AG1-000B GEN
Solar/Wind Harmer
1.499
3151221GRAVEL6
Adder
4.598
3151171GRAVELC
Adder
0.885
315813AE1-149 C
Solar/Wind Harmer
4.431
316313AB2-026
Solar/Wind Harmer
0.191
316258AE1-075 C
Solar/Wind Harmer
0.172
316405AF2-144 C
Solar/Wind Harmer
0.182
3143336POWHATN
Solar/Wind Harmer
0.715
3145336SMITFLD
Solar/Wind Harmer
-0.003
315773AC2-141 GEN
Solar/Wind Harmer
2.964
970659AG2-427 GEN
Solar/Wind Harmer
0.665
316083AB2-161 GEN
Solar/Wind Harmer
1.146
3144536CHRHLND
Solar/Wind Harmer
-0.001
3151101ELIZAR3
Adder
5.827
3144873MCLAUGH
Solar/Wind Harmer
0
944581AF1-123 GEN
Solar/Wind Harmer
32.067
944601AF1-125 GEN
Solar/Wind Harmer
31.566
970661AG2-428 GEN
Solar/Wind Harmer
1.328
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.855
316320Y1-086
Solar/Wind Harmer
0.409
316435W1029_GEN3
Solar/Wind Harmer
1.259
3146516WINFALL
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3145273HOLLAND
Solar/Wind Harmer
-0.005
3146376EDENTON
Solar/Wind Harmer
-0.007
315614AA2-178 GEN
Solar/Wind Harmer
0.732
3156081AA2-088 GEN
Solar/Wind Harmer
2.185
971157AH1-035 GEN
Solar/Wind Harmer
0.841
3146776BUCKING
Solar/Wind Harmer
-0.002
315737AD1-076 GEN
Solar/Wind Harmer
1.278
970917AG2-570 GEN
Solar/Wind Harmer
16.768
316365GEN2_N
Solar/Wind Harmer
0.452
3146206CASHIE
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
0.047
3145893MURPHYS
Solar/Wind Harmer
-0.007
3146926FARMVIL
Solar/Wind Harmer
-0.004
957521AF2-046 GEN
Solar/Wind Harmer
5.262
961681AG1-008 GEN
Solar/Wind Harmer
5.262
970909AG2-566 GEN
Solar/Wind Harmer
0.633
3146173TUNIS
Solar/Wind Harmer
-0.007
972255AH1-712 GEN
Adder
30.164
3144293JTRSVLE
Adder
0.186
237030AB1-096 C
Solar/Wind Helper
0.1
223402AF1-300 C
Solar/Wind Helper
0.385
226910AB2-157 C
Solar/Wind Helper
0.014
205917AD1-020 ES
Solar/Wind Helper
0.357
227287AC2-120 GEN
Solar/Wind Helper
0.309
238221AF1-254 C O1
Solar/Wind Helper
0.197
235067AD1-061 GEN
Solar/Wind Helper
0.341
233982AB2-133 GEN
Solar/Wind Helper
0.216
233918AB1-142 GEN
Solar/Wind Helper
0.304
233994AC2-023 GEN
Solar/Wind Helper
0.578
233996TM1833_GEN
Solar/Wind Helper
0.157
233997TMININ_4.2
Solar/Wind Helper
0.157
233940AF2-379 C
Solar/Wind Helper
0.037
234015AF2-250 C
Solar/Wind Helper
0.023
233952AC2-187 GEN
Solar/Wind Helper
0.14
232406W1-004 FULL
Solar/Wind Helper
0.305
233971AC1-093 C
Solar/Wind Helper
0.214
230430AE1-229_GEN
Solar/Wind Helper
1.992
230415AB2-049 C
Solar/Wind Helper
0.018
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219766PARADISE C
Solar/Wind Helper
0.032
219912AD2-042 GEN
Solar/Wind Helper
0.088
228729W2-030 C
Solar/Wind Helper
0.065
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.007
219906AC1-017 C
Solar/Wind Helper
0.025
219348LDSOLAR C
Solar/Wind Helper
0.067
959561AF2-247 GEN
Solar/Wind Helper
0.012
20716028EGP_W2-019
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.037
20715028HAN_X4-015
Solar/Wind Helper
0.033
219276PARKLANDSO C
Solar/Wind Helper
0.052
20714528FRN_Y2-051
Solar/Wind Helper
0.033
20720528MAN_W1-024
Solar/Wind Helper
0.016
219612MATRIX C
Solar/Wind Helper
0.014
218438BLK ROCK C
Solar/Wind Helper
0.016
20673728F2S_V4-070
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.042
219919AE1-041 FULL
Solar/Wind Helper
0.002
219249CENTRALDIV C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
217169METRODIV C
Solar/Wind Helper
0.002
20676728BRNX1-095
Solar/Wind Helper
0.017
207510AF2-138 C
Solar/Wind Helper
0.046
20674628WNG_W3-110
Solar/Wind Helper
0.051
963161AG1-165 GEN
Solar/Wind Helper
0.239
963071AG1-156 GEN
Solar/Wind Helper
0.773
209027LOR2_Q27
Solar/Wind Helper
0.55
961331AF2-424 GEN
Solar/Wind Helper
0.233
961421AF2-433 GEN
Solar/Wind Helper
0.233
957921AF2-086 GEN
Solar/Wind Helper
0.23
209067AE2-060 GEN
Solar/Wind Helper
0.042
946691AF1-333 GEN
Solar/Wind Helper
0.23
946741AF1-338 GEN
Solar/Wind Helper
0.23
3152131X4-039 ST
50/50
2.877
3152121X4-039 GT2
50/50
1.823
3150221REMNGT2
Adder
10.939
3150211REMNGT1
Adder
10.866
972201AH1-685 GEN
Adder
1.887
3150281M RUN A
Adder
11.705
316006AB2-029 C
Solar/Wind Harmer
0.549
971685AH1-345 GEN
Solar/Wind Harmer
0.837
3140676OCCOQUN
Adder
0.203
316254AC1-120 GEN1
Solar/Wind Harmer
0.712
316045AC1-158 PL2
Solar/Wind Harmer
2.734
315683AE1-153 C
Solar/Wind Harmer
8.082
3147666LOUISA
Solar/Wind Harmer
-0.032
316192AB2-158 GEN
Solar/Wind Harmer
0.961
3151751LOISA D
Adder
4.652
972223AH1-696 GEN
Adder
5.63
3150151POSSMC1
Adder
0.713
3141346CRANES
Adder
0.082
972197AH1-683 GEN
Adder
1.435
972219AH1-694 GEN
Adder
1.033
966881AG1-559 GEN
Solar/Wind Harmer
0.078
957971AF2-091 GEN
Solar/Wind Harmer
0.75
972135AH1-637 GEN
Solar/Wind Harmer
0.75
316337AD2-073 GEN
Solar/Wind Harmer
0.198
3150351NORNECKC2
Adder
0.651
964211AG1-282 GEN
Solar/Wind Harmer
0.22
3141726DUNNSVL
Solar/Wind Harmer
-0.029
962861AG1-135 GEN
Solar/Wind Harmer
2.741
961951AG1-038 GEN
Solar/Wind Harmer
0.961
3143226MDLTHAN
Solar/Wind Harmer
-0.007
3143526WINTERP
Solar/Wind Harmer
-0.038
3142416OLDCHRC
Solar/Wind Harmer
-0.019
3142416OLDCHRC
Solar/Wind Harmer
-0.007
3138133OCRAN
Solar/Wind Harmer
-0.004
3150851SPRUNCC
Adder
0.297
3141766HARMONY
Solar/Wind Harmer
-0.001
971777AH1-397 GEN
Solar/Wind Harmer
0.852
3141843SHACKLE
Adder
0.329
3143096IRON208
Adder
0.27
3142433PROV 92
Solar/Wind Harmer
-0.029
3142433PROV 92
Adder
0.125
3142433PROV 92
Adder
0.125
3142543TWELFTH
Solar/Wind Harmer
-0.001
944631AF1-128 GEN
Adder
30.629
316159AE1-175 C
Solar/Wind Harmer
0.193
971317AH1-138 GEN
Solar/Wind Harmer
0.895
315671AE2-027_GEN
Solar/Wind Harmer
5.367
970129AG2-093 GEN
Solar/Wind Harmer
1.632
316458AB2-190 GEN2
Solar/Wind Harmer
0.724
971069AG2-661 GEN
Solar/Wind Harmer
1.13
3138126ROCKLANDING
Solar/Wind Harmer
0.022
971647AH1-324 GEN
Solar/Wind Harmer
3.563
961611AG1-000B GEN
Solar/Wind Harmer
3.512
3151171GRAVELC
Adder
0.673
3143336POWHATN
Solar/Wind Harmer
0.841
3145336SMITFLD
Solar/Wind Harmer
-0.028
316294AC1-161 GEN
Solar/Wind Harmer
2.291
970659AG2-427 GEN
Solar/Wind Harmer
3.755
316381AD1-082 GEN
Solar/Wind Harmer
0.648
316375AC2-012 GEN
Solar/Wind Harmer
2.44
3150981CHESPKA
Adder
0.784
944591AF1-124 GEN
Solar/Wind Harmer
32.182
970661AG2-428 GEN
Solar/Wind Harmer
7.492
316072AD1-144
Solar/Wind Harmer
0.142
939411AE1-173 GEN
Solar/Wind Harmer
35.173
940641AE2-051 GEN
Solar/Wind Harmer
6.594
316336AC2-165 C
Solar/Wind Harmer
1.222
316388AE2-253 GEN
Solar/Wind Harmer
0.474
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316246AF1-032 C
Solar/Wind Harmer
0.142
316093AE2-104_GEN
Solar/Wind Harmer
2.034
3146516WINFALL
Solar/Wind Harmer
-0.022
3146516WINFALL
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.702
970937AG2-583 GEN
Solar/Wind Harmer
4.952
3130156CHOWAN
Solar/Wind Harmer
-0.007
3145663CRESWEL
Solar/Wind Harmer
-0.019
971163AH1-040 GEN
Solar/Wind Harmer
6.359
972003AH1-546 GEN
Solar/Wind Harmer
3.372
316322AB2-045
Solar/Wind Harmer
0.226
3146776BUCKING
Solar/Wind Harmer
-0.003
970919AG2-571 GEN
Solar/Wind Harmer
2.123
316023GEN1_S
Solar/Wind Harmer
0.452
970087AG2-069 GEN
Solar/Wind Harmer
6.277
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.673
3145893MURPHYS
Solar/Wind Harmer
-0.027
3145893MURPHYS
Solar/Wind Harmer
0.198
3146926FARMVIL
Solar/Wind Harmer
-0.004
3146173TUNIS
Solar/Wind Harmer
-0.007
972277AH1-723 GEN
Adder
35.15
3147043LAWRENC
Adder
0.53
3144293JTRSVLE
Adder
0.186
23779801AA1-109
Solar/Wind Helper
0.261
223401AF1-299 GEN
Solar/Wind Helper
0.385
966131AG1-482 GEN
Solar/Wind Helper
0.069
237080AD1-060 GEN
Solar/Wind Helper
0.242
235062AE1-101 C1
Solar/Wind Helper
1.169
237038AE2-054 C
Solar/Wind Helper
0.19
233930AB2-032 GEN
Solar/Wind Helper
0.23
233915AB1-141 GEN
Solar/Wind Helper
0.304
232422X3-066 FULL
Solar/Wind Helper
0.069
233964AF2-378 GEN
Solar/Wind Helper
0.025
232426Y1-080 FULL
Solar/Wind Helper
0.023
232428Y3-058 C
Solar/Wind Helper
0.203
233998TM1NIN_3.36
Solar/Wind Helper
0.157
233954AC2-188 GEN
Solar/Wind Helper
0.14
232404W1-003 C
Solar/Wind Helper
0.305
233950AC2-186 GEN
Solar/Wind Helper
0.07
232434Z2-077 GEN
Solar/Wind Helper
0.076
233972AC1-094 C
Solar/Wind Helper
0.181
205941AD2-115 GEN
Solar/Wind Helper
0.302
230511AF1-262
Solar/Wind Helper
0.009
230434AG1-499 GEN
Solar/Wind Helper
0.136
228728W1-130C
Solar/Wind Helper
0.032
219258KINSLEYDEP C
Solar/Wind Helper
0.045
219904AC1-010 C
Solar/Wind Helper
0.036
219907AC1-030 C
Solar/Wind Helper
0.02
218660EHAMPSOLAR C
Solar/Wind Helper
0.019
219686LUMSOLAR_N C
Solar/Wind Helper
0.023
219304NAMERICA C
Solar/Wind Helper
0.077
20720728JCB_W1-129
Solar/Wind Helper
0.033
207445AB1-138_GEN
Solar/Wind Helper
0.061
963711AG1-223 GEN
Solar/Wind Helper
0.037
20714828MDF_W3-079
Solar/Wind Helper
0.076
219680HOPEWELLV C1
Solar/Wind Helper
0.002
207454AA2-184 E
Solar/Wind Helper
0.179
20715228NPK_W1-113
Solar/Wind Helper
0.045
20742028HF_AC1-207
Solar/Wind Helper
0.081
207528AF2-192 GEN
Solar/Wind Helper
0.044
20673628F1S_V4-069
Solar/Wind Helper
0.017
20675428EAM_W2-061
Solar/Wind Helper
0.009
218428ETC SOLAR C
Solar/Wind Helper
0.003
20676428JCR_X2-075
Solar/Wind Helper
0.039
217213AMBOY SO C
Solar/Wind Helper
0.016
217209CENTRL HS C
Solar/Wind Helper
0.005
217208PARK ELE C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.013
207437AD2-070 GEN
Solar/Wind Helper
0.078
207439AE1-081 C O1
Solar/Wind Helper
0.011
207518AF1-320_GEN
Solar/Wind Helper
0.893
20671928W4-073
Solar/Wind Helper
0.051
20675828AU_W4-064
Solar/Wind Helper
0.017
961301AF2-421 GEN
Solar/Wind Helper
0.239
963151AG1-164 GEN
Solar/Wind Helper
0.239
212266LOR1
Solar/Wind Helper
0.025
961341AF2-425 GEN
Solar/Wind Helper
0.233
212507AE2-042_GEN
Solar/Wind Helper
0.817
946731AF1-337 GEN
Solar/Wind Helper
0.23
209071AE2-133 GEN
Solar/Wind Helper
0.041
957481AF2-042 GEN
Solar/Wind Harmer
5.711
NYPJM->LTFIMP_NY
CLTF
2.532
LGEELTFEXP_LGEE->PJM
CLTF
1.753
WECLTFEXP_WEC->PJM
CLTF
0.941
LAGNLTFEXP_LAGN->PJM
CLTF
5.835
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.776
TVALTFEXP_TVA->PJM
CLTF
2.938
CBM West 1LTFEXP_CBM-W1->PJM
CBM
34.919
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.772
MECLTFEXP_MEC->PJM
CLTF
4.292
SIGELTFEXP_SIGE->PJM
CLTF
0.135
CPLELTFEXP_CPLE->PJM
CLTF
4.229
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.691

Details for 6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019B_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.55 %
Rating:1809.0 MVA
Rating Type:C
MVA to Mitigate:1909.41
MW Contribution:41.59
Bus #Bus NameTypeMW Contribution
3138216PACIFIC
Solar/Wind Harmer
-0.003
316411AF1-147_GEN1
Solar/Wind Harmer
1.2
316415AF1-147_GEN2
Solar/Wind Harmer
1.2
970053AG2-049 GEN
Adder
1.707
316164AC1-076 GEN
Solar/Wind Harmer
0.848
3141426STAFORD
Solar/Wind Harmer
-0.002
3147346CASHSCORNER
Solar/Wind Harmer
0.143
3150411LDYSMT5
Adder
10.908
3150381LDYSMT2
Adder
10.439
972213AH1-691 GEN
Adder
1.766
972215AH1-692 GEN
Adder
1.766
944491AF1-114 GEN
Solar/Wind Harmer
2.612
316223AC1-118
Solar/Wind Harmer
0.237
972189AH1-679 GEN
Adder
1.305
3141813NORNECK
Solar/Wind Harmer
-0.009
962981AG1-147 GEN
Solar/Wind Harmer
3.767
316312AB1-027
Solar/Wind Harmer
0.29
316233AE1-074 FULL
Solar/Wind Harmer
0.231
971281AH1-106 GEN
Solar/Wind Harmer
1.396
971283AH1-107 GEN
Solar/Wind Harmer
1.396
3141783LANCAST
Solar/Wind Harmer
-0.005
3141783LANCAST
Solar/Wind Harmer
-0.003
3138133OCRAN
Solar/Wind Harmer
-0.003
3141913WHIT STONE
Solar/Wind Harmer
-0.009
316314AB2-024 C
Solar/Wind Harmer
0.732
316059AD1-063 C
Solar/Wind Harmer
0.193
315662AE1-191 GEN
Solar/Wind Harmer
1.031
315666AE1-190 GEN
Solar/Wind Harmer
0.258
957601AF2-054 GEN
Solar/Wind Harmer
0.256
3143873LANEXA
Solar/Wind Harmer
-0.005
3141873WAN 176
Solar/Wind Harmer
-0.002
971285AH1-108 GEN
Adder
0.574
3142433PROV 92
Adder
0.148
3142433PROV 92
Adder
0.148
315976AC1-164 GENA
Solar/Wind Harmer
9.028
316169AC1-164_GENC
Solar/Wind Harmer
7.799
315975AC1-164 GENB
Solar/Wind Harmer
0.267
971167AH1-042 GEN
Solar/Wind Harmer
8.225
957831AF2-077 GEN
Solar/Wind Harmer
0.255
3138283WHITEMARSH
Solar/Wind Harmer
0.013
316132AB2-190 GEN1
Solar/Wind Harmer
0.854
316369SG1_INVT
Solar/Wind Harmer
1.505
972265AH1-717 GEN
Adder
5.796
3151201GRAVEL4
Adder
5.433
3151191GRAVEL3
Adder
5.364
3151211GRAVEL5
Adder
5.364
3143316POE
Solar/Wind Harmer
-0.033
971445AH1-216 GEN
Solar/Wind Harmer
5.176
3151081ELIZAR1
Adder
6.79
3151091ELIZAR2
Adder
6.672
3152611GOSPORTB
Adder
0.943
3152621GOSPORTC
Adder
0.801
3152601GOSPORTA
Adder
0.738
315833AF1-017_GEN
Solar/Wind Harmer
1.574
316349AD2-085 GEN
Solar/Wind Harmer
0.737
316311AC2-079 GEN
Solar/Wind Harmer
4.18
957871AF2-081 GEN
Solar/Wind Harmer
4.142
319010AE1-072 C
Solar/Wind Harmer
1.673
316305AF2-043 C
Solar/Wind Harmer
0.249
3146406KITTY HAWK
Solar/Wind Harmer
0.007
315835AF2-110_GEN
Solar/Wind Harmer
1.032
313526AB2-022
Solar/Wind Harmer
0.222
3146486SUNBURY
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.008
316321Z2-027
Solar/Wind Harmer
0.222
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
3146396TANGLEW
Solar/Wind Harmer
0.151
316315AB2-025 C
Solar/Wind Harmer
0.22
941031AE2-094 GEN
Solar/Wind Harmer
15.312
944011AF1-069 GEN
Solar/Wind Harmer
4.798
315814AE2-033 C
Solar/Wind Harmer
7.6
315611Z1-036_GEN2
Solar/Wind Harmer
2.009
970673AG2-436 GEN
Solar/Wind Harmer
17.036
970673AG2-436 GEN
Solar/Wind Harmer
8.626
3130156CHOWAN
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.008
971967AH1-528 GEN
Solar/Wind Harmer
15.195
315816AE2-034 GEN
Solar/Wind Harmer
0.648
972205AH1-687 GEN
Adder
3.036
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315732AD1-074 GEN1
Solar/Wind Harmer
1.605
315733AD1-074 GEN2
Solar/Wind Harmer
1.605
315735AD1-075 GEN1
Solar/Wind Harmer
0.803
965291AG1-394 GEN
Solar/Wind Harmer
0.704
971845AH1-439 GEN
Solar/Wind Harmer
4.213
970285AG2-188 GEN
Solar/Wind Harmer
6.934
3138266HYDRAULIC
Solar/Wind Harmer
0
3138266HYDRAULIC
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.94
970581AG2-369 GEN
Solar/Wind Harmer
4.248
970601AG2-382 GEN
Solar/Wind Harmer
3.458
316318V4-068
Solar/Wind Harmer
0.197
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
972193AH1-681 GEN
Adder
1.595
3151881LOWMORC
Adder
0.669
3151881LOWMORC
Adder
0.659
3151861LOWMORA
Adder
0.648
972257AH1-713 GEN
Adder
0.697
23544701WINZ1-113
Adder
0.24
960921AF2-383 GEN
Solar/Wind Helper
0.152
205943AE1-185 GEN
Solar/Wind Helper
0.423
205932AD2-116_GEN
Solar/Wind Helper
0.422
205956AE1-196_GEN
Solar/Wind Helper
0.422
233935AB2-179 C
Solar/Wind Helper
1.004
232436AB1-176 C
Solar/Wind Helper
0.035
233923SMA
Solar/Wind Helper
0.755
233990AG1-397 GEN
Solar/Wind Helper
0.024
234033AF1-007_GEN
Solar/Wind Helper
5.529
232432Z2-076 GEN
Solar/Wind Helper
0.053
964001AG1-254 GEN
Solar/Wind Helper
0.738
227927V4-067C
Solar/Wind Helper
0.008
228754AB1-001 C
Solar/Wind Helper
0.02
3152111X4-039 GT1
50/50
2.007
315747AE2-019 GEN
50/50
14.059
963691AG1-221 GEN
Solar/Wind Harmer
2.52
971455AH1-223 GEN
Solar/Wind Harmer
2.52
3141196NOKESVL
Solar/Wind Harmer
-0.049
3150231REMNGT3
Adder
13.559
3150241REMNGT4
Adder
12.643
972199AH1-684 GEN
Adder
1.917
972217AH1-693 GEN
Adder
1.667
3150301M RUN C
Adder
13.435
3150291M RUN B
Adder
13.336
316170AC1-121 GEN2
Solar/Wind Harmer
0.275
316044AC1-158 PL1
Solar/Wind Harmer
0.993
316450AC1-158 RIC
Solar/Wind Harmer
0.265
3132273ORANGE
Solar/Wind Harmer
-0.002
3150151POSSMC1
Adder
0.848
3150151POSSMC1
Adder
0.848
3147666LOUISA
Solar/Wind Harmer
-0.022
3151761LOISA E
Adder
11.06
972183AH1-676 GEN
Adder
89.287
3150331BIRCHWDA
Adder
13.842
3141316ARNOLDS
Adder
0.192
3150401LDYSMT4
Adder
10.874
3150371LDYSMT1
Adder
10.507
966881AG1-559 GEN
Solar/Wind Harmer
0.269
970737AG2-469 GEN
Solar/Wind Harmer
4.42
971781AH1-399 GEN
Solar/Wind Harmer
0.543
3141906WESTMOR
Solar/Wind Harmer
-0.003
3150351NORNECKC2
Adder
0.783
316473AC1-191 GEN
Solar/Wind Harmer
0.931
316404AE1-155 C
Solar/Wind Harmer
1.667
316484AD2-074 GEN
Solar/Wind Harmer
2.171
970009AG2-005 GEN
Solar/Wind Harmer
1.078
962971AG1-146 GEN
Solar/Wind Harmer
1.614
3142416OLDCHRC
Solar/Wind Harmer
0.867
970293AG2-193 GEN
Solar/Wind Harmer
1.071
3141766HARMONY
Solar/Wind Harmer
0.762
316203AE2-005 GEN
Solar/Wind Harmer
3.607
316280AD1-041 GEN
Solar/Wind Harmer
0.645
316156AD2-030 GEN
Solar/Wind Harmer
0.228
3141873WAN 176
Solar/Wind Harmer
1.015
3141843SHACKLE
Adder
0.389
3150861SPRUNCD
Adder
0.351
3143096IRON208
Adder
0.319
3143096IRON208
Adder
0.312
3142433PROV 92
Adder
0.148
3142433PROV 92
Adder
0.148
3142946ENON
Solar/Wind Harmer
-0.003
316382AG1-145 C
Solar/Wind Harmer
0.255
970133AG2-095 GEN
Solar/Wind Harmer
0.953
970129AG2-093 GEN
Solar/Wind Harmer
4.756
965281AG1-393 GEN
Solar/Wind Harmer
1.054
315778AD1-151 GEN
Solar/Wind Harmer
7.304
3150921YORKTN3
Adder
1.885
315839AE2-212 C
Solar/Wind Harmer
0.254
3144216WINCHST
Adder
0.283
961611AG1-000B GEN
Solar/Wind Harmer
1.769
3151221GRAVEL6
Adder
5.427
3151171GRAVELC
Adder
1.044
315813AE1-149 C
Solar/Wind Harmer
5.23
3145336SMITFLD
Solar/Wind Harmer
-0.003
315773AC2-141 GEN
Solar/Wind Harmer
3.497
316313AB2-026
Solar/Wind Harmer
0.225
316258AE1-075 C
Solar/Wind Harmer
0.203
316405AF2-144 C
Solar/Wind Harmer
0.214
3143336POWHATN
Solar/Wind Harmer
0.843
970659AG2-427 GEN
Solar/Wind Harmer
0.785
316083AB2-161 GEN
Solar/Wind Harmer
1.353
3144536CHRHLND
Solar/Wind Harmer
-0.001
3151101ELIZAR3
Adder
6.877
3144873MCLAUGH
Solar/Wind Harmer
0
944581AF1-123 GEN
Solar/Wind Harmer
37.845
944601AF1-125 GEN
Solar/Wind Harmer
37.254
970661AG2-428 GEN
Solar/Wind Harmer
1.567
3146456SLIGO L269
Solar/Wind Harmer
-0.008
971153AH1-033 GEN
Solar/Wind Harmer
1.009
316320Y1-086
Solar/Wind Harmer
0.483
316435W1029_GEN3
Solar/Wind Harmer
1.486
3146516WINFALL
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3145273HOLLAND
Solar/Wind Harmer
-0.006
3146376EDENTON
Solar/Wind Harmer
-0.008
315614AA2-178 GEN
Solar/Wind Harmer
0.864
3156081AA2-088 GEN
Solar/Wind Harmer
2.58
971157AH1-035 GEN
Solar/Wind Harmer
0.994
315737AD1-076 GEN
Solar/Wind Harmer
1.509
3146776BUCKING
Solar/Wind Harmer
-0.003
970917AG2-570 GEN
Solar/Wind Harmer
19.793
316365GEN2_N
Solar/Wind Harmer
0.534
3146206CASHIE
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
3146926FARMVIL
Solar/Wind Harmer
-0.005
957521AF2-046 GEN
Solar/Wind Harmer
6.214
961681AG1-008 GEN
Solar/Wind Harmer
6.214
970909AG2-566 GEN
Solar/Wind Harmer
0.747
3146173TUNIS
Solar/Wind Harmer
-0.008
972255AH1-712 GEN
Adder
35.693
3144293JTRSVLE
Adder
0.22
3151861LOWMORA
Adder
0.674
3152541MT STMG
Adder
0.593
237030AB1-096 C
Solar/Wind Helper
0.073
223402AF1-300 C
Solar/Wind Helper
0.379
226910AB2-157 C
Solar/Wind Helper
0.012
205917AD1-020 ES
Solar/Wind Helper
0.322
227287AC2-120 GEN
Solar/Wind Helper
0.266
233918AB1-142 GEN
Solar/Wind Helper
0.397
233982AB2-133 GEN
Solar/Wind Helper
0.282
233994AC2-023 GEN
Solar/Wind Helper
0.757
233996TM1833_GEN
Solar/Wind Helper
0.206
233997TMININ_4.2
Solar/Wind Helper
0.206
233940AF2-379 C
Solar/Wind Helper
0.049
234015AF2-250 C
Solar/Wind Helper
0.03
232406W1-004 FULL
Solar/Wind Helper
0.4
233952AC2-187 GEN
Solar/Wind Helper
0.183
233971AC1-093 C
Solar/Wind Helper
0.281
230430AE1-229_GEN
Solar/Wind Helper
2.603
230415AB2-049 C
Solar/Wind Helper
0.023
228729W2-030 C
Solar/Wind Helper
0.085
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.042
219912AD2-042 GEN
Solar/Wind Helper
0.115
219291REEVESSOUT C
Solar/Wind Helper
0.009
219236SOUTHERNHQ C
Solar/Wind Helper
0.004
219914AD2-027 C
Solar/Wind Helper
0.088
219272CLEANLIGHT C
Solar/Wind Helper
0.019
219688LUMSOLAR_S C
Solar/Wind Helper
0.031
219607WPEMNERT C
Solar/Wind Helper
0.061
214067T20SOLAR
Solar/Wind Helper
0.009
20715728PEM_W1-119
Solar/Wind Helper
0.073
20715828PEM_W1-120
Solar/Wind Helper
0.073
207459AE1-142 C O1
Solar/Wind Helper
0.22
219620RIDERU C
Solar/Wind Helper
0.001
20675528CPH_W2-050
Solar/Wind Helper
0.065
218526CNTRALGAS2 C
Solar/Wind Helper
0.12
218524CNTRALGAS1 C
Solar/Wind Helper
0.12
966261AG1-495 GEN
Solar/Wind Helper
0.06
207530AG1-191 GEN
Solar/Wind Helper
0.049
20676328BVR_Y1-020
Solar/Wind Helper
0.02
20675928HOL_W4-097
Solar/Wind Helper
0.037
20674828DL_W4-046
Solar/Wind Helper
0.006
207484AF2-139 C O1
Solar/Wind Helper
0.062
207408W3-077 C
Solar/Wind Helper
0.062
20675728RH_W2-091
Solar/Wind Helper
0.1
20675128HRM_W1-127
Solar/Wind Helper
0.022
209116AE2-175 GEN
Solar/Wind Helper
1.289
961261AF2-417 GEN
Solar/Wind Helper
0.308
959381AF2-229 GEN
Solar/Wind Helper
0.23
959431AF2-234 GEN
Solar/Wind Helper
0.594
964051AG1-259 GEN
Solar/Wind Helper
0.044
964061AG1-260 GEN
Solar/Wind Helper
0.044
959421AF2-233 GEN
Solar/Wind Helper
0.297
203975AE1-071-GEN
Solar/Wind Helper
1.563
219906AC1-017 C
Solar/Wind Helper
0.032
219348LDSOLAR C
Solar/Wind Helper
0.088
959561AF2-247 GEN
Solar/Wind Helper
0.016
20716028EGP_W2-019
Solar/Wind Helper
0.014
20720828JCB_W4-025
Solar/Wind Helper
0.048
20715028HAN_X4-015
Solar/Wind Helper
0.043
219276PARKLANDSO C
Solar/Wind Helper
0.068
20714528FRN_Y2-051
Solar/Wind Helper
0.043
20720528MAN_W1-024
Solar/Wind Helper
0.021
219612MATRIX C
Solar/Wind Helper
0.018
218438BLK ROCK C
Solar/Wind Helper
0.02
219908AB1-139 C
Solar/Wind Helper
0.055
219919AE1-041 FULL
Solar/Wind Helper
0.003
219249CENTRALDIV C
Solar/Wind Helper
0.008
20673728F2S_V4-070
Solar/Wind Helper
0.022
217211CAMDEN ST C
Solar/Wind Helper
0.003
217169METRODIV C
Solar/Wind Helper
0.003
20676728BRNX1-095
Solar/Wind Helper
0.022
207510AF2-138 C
Solar/Wind Helper
0.06
20674628WNG_W3-110
Solar/Wind Helper
0.066
963161AG1-165 GEN
Solar/Wind Helper
0.309
963071AG1-156 GEN
Solar/Wind Helper
1.001
209027LOR2_Q27
Solar/Wind Helper
0.712
961331AF2-424 GEN
Solar/Wind Helper
0.302
961421AF2-433 GEN
Solar/Wind Helper
0.302
957921AF2-086 GEN
Solar/Wind Helper
0.298
946691AF1-333 GEN
Solar/Wind Helper
0.297
946741AF1-338 GEN
Solar/Wind Helper
0.297
209067AE2-060 GEN
Solar/Wind Helper
0.051
238221AF1-254 C O1
Solar/Wind Helper
0.122
235067AD1-061 GEN
Solar/Wind Helper
0.214
972289AH1-729 GEN
50/50
14.564
315651AD1-115 GEN
Solar/Wind Harmer
4.557
316447AC1-158 HLD
Solar/Wind Harmer
2.184
3150071POSSM 5
Adder
38.76
3150181POSSMC2
Adder
0.855
3150181POSSMC2
Adder
0.848
3150181POSSMC2
Adder
0.848
966001AG1-469 GEN
Solar/Wind Harmer
0.179
3151731LOISA B
Adder
5.425
3151721LOISA A
Adder
5.397
3150391LDYSMT3
Adder
10.854
972195AH1-682 GEN
Adder
1.426
315673AE1-157 GEN
Solar/Wind Harmer
6.752
957411AF2-035 GEN
Solar/Wind Harmer
4.024
970317AG2-208 GEN
Solar/Wind Harmer
3.912
316468AD1-105 GEN
Solar/Wind Harmer
0.981
316077AC2-138 C
Solar/Wind Harmer
0.183
3150341NORNECKC1
Adder
0.809
3150341NORNECKC1
Adder
0.802
966871AG1-558 GEN
Solar/Wind Harmer
0.26
966871AG1-558 GEN
Solar/Wind Harmer
0.089
958261AF2-120 GEN
Solar/Wind Harmer
3.349
316487AF1-042 GEN
Solar/Wind Harmer
1.136
3142296MT RD221
Adder
0.244
971223AH1-071 GEN
Solar/Wind Harmer
1.075
3143526WINTERP
Solar/Wind Harmer
-0.044
3142366NRTHEST
Adder
0.249
3150691DARBY 3
Adder
5.491
3150701DARBY 4
Adder
5.478
3150681DARBY 2
Adder
5.471
3150671DARBY 1
Adder
5.465
316075AC2-137 C
Solar/Wind Harmer
0.231
316441AF1-014 GEN
Solar/Wind Harmer
0.577
3142946ENON
Solar/Wind Harmer
-0.001
944641AF1-129 GEN
Adder
35.924
316240AF1-291 C
Solar/Wind Harmer
0.255
316033AB2-134 GEN
Solar/Wind Harmer
2.716
315697AD1-025 GEN
Solar/Wind Harmer
1.703
316236AE1-162_GEN
Solar/Wind Harmer
0.252
970657AG2-426 GEN
Solar/Wind Harmer
2.604
970657AG2-426 GEN
Solar/Wind Harmer
0.544
316036AC1-147 C
Solar/Wind Harmer
0.225
3150991CHESPKB
Adder
0.776
3150991CHESPKB
Adder
0.757
316316AC1-027 C
Solar/Wind Harmer
0.255
3142956BIRDNECK
Solar/Wind Harmer
0.446
316185AD1-033 GEN
Solar/Wind Harmer
0.876
3145506HICKORY
Solar/Wind Harmer
-0.033
3145506HICKORY
Solar/Wind Harmer
-0.02
3145506HICKORY
Solar/Wind Harmer
-0.005
316339AD2-160 GEN
Solar/Wind Harmer
0.559
316018AA1-139 ULT2
Solar/Wind Harmer
0.71
316017AA1-139 ULT1
Solar/Wind Harmer
0.67
3137176SLIGO L2192
Solar/Wind Harmer
-0.033
3146456SLIGO L269
Solar/Wind Harmer
0.977
3130086AYDLETT
Solar/Wind Harmer
-0.033
3146386ELIZ CT
Solar/Wind Harmer
-0.008
971761AH1-387 GEN
Solar/Wind Harmer
4.579
316431W1029_GEN1
Solar/Wind Harmer
1.486
316433W1029_GEN2
Solar/Wind Harmer
1.486
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3144356SAPONY
Solar/Wind Harmer
0.285
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.849
3146376EDENTON
Solar/Wind Harmer
0.24
3146376EDENTON
Solar/Wind Harmer
0.24
972185AH1-677 GEN
Adder
4.036
972187AH1-678 GEN
Adder
2.039
970933AG2-581 GEN
Solar/Wind Harmer
7.52
3146776BUCKING
Solar/Wind Harmer
-0.032
3146776BUCKING
Solar/Wind Harmer
-0.003
316065AD1-022 GEN
Solar/Wind Harmer
3.958
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
3.936
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
971741AH1-377 GEN
Solar/Wind Harmer
9.144
3144293JTRSVLE
Adder
0.22
3144293JTRSVLE
Adder
0.185
237025AB1-124 C
Solar/Wind Helper
0.168
237006AB1-125 GEN
Solar/Wind Helper
0.126
23777801MSM_W1-116
Solar/Wind Helper
0.11
205916AD1-020 GEN
Solar/Wind Helper
1.496
208835TUHI V3-051
Solar/Wind Helper
0.021
208835TUHI V3-051
Solar/Wind Helper
0.021
237034AC2-136 C
Solar/Wind Helper
0.157
233933AB2-153 GEN
Solar/Wind Helper
0.184
233944AB2-135 GEN
Solar/Wind Helper
0.465
232424Y1-079 C
Solar/Wind Helper
0.092
233987AB2-037 GEN
Solar/Wind Helper
1.847
233946AB2-136 GEN
Solar/Wind Helper
0.448
234036AF2-325 C
Solar/Wind Helper
0.033
233901CHERRYDALE C
Solar/Wind Helper
0.183
232408W1-005 C
Solar/Wind Helper
0.4
232410W1-006 C
Solar/Wind Helper
0.4
233939AC1-091 C
Solar/Wind Helper
0.275
233970AC1-092 C
Solar/Wind Helper
0.275
230433AD2-135 GEN
Solar/Wind Helper
0.013
230407AD2-065 C
Solar/Wind Helper
0.031
219921AF1-264
Solar/Wind Helper
0.039
219615MILLCREEK C
Solar/Wind Helper
0.02
963401AG1-189 GEN
Solar/Wind Helper
0.043
963391AG1-188 GEN
Solar/Wind Helper
0.062
20714928UPF_X1-085
Solar/Wind Helper
0.004
20720628TIN_W1-124
Solar/Wind Helper
0.143
20716928W4-060COL
Solar/Wind Helper
0.039
218440SUMMTASSOC C
Solar/Wind Helper
0.012
20673828FLE_V3-070
Solar/Wind Helper
0.068
207442AE1-156 GEN
Solar/Wind Helper
0.243
20676128MHD_W3-029
Solar/Wind Helper
0.072
20671828STAW2-080
Solar/Wind Helper
0.02
217081WEATEXAS C
Solar/Wind Helper
0.009
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.005
217204WCALDSOLAR C
Solar/Wind Helper
0.002
226929AD2-058 GEN
Solar/Wind Helper
0.066
207471AF2-354 C
Solar/Wind Helper
0.124
20674928WA_W3-044
Solar/Wind Helper
0.072
20676228FRD_X1-012
Solar/Wind Helper
0.067
964851AG1-348 GEN
Solar/Wind Helper
0.059
20674128FR_U2-059
Solar/Wind Helper
0.003
966111AG1-480 GEN
Solar/Wind Helper
0.032
211065PSPA IPP
Solar/Wind Helper
0.109
211065PSPA IPP
Solar/Wind Helper
0.109
20390526W1-045 C
Solar/Wind Helper
0.226
208972BECR K09
Solar/Wind Helper
0.227
961431AF2-434 GEN
Solar/Wind Helper
0.302
209029WAYMART-WD
Solar/Wind Helper
0.566
209054AE2-059 GEN
Solar/Wind Helper
0.054
946751AF1-339 GEN
Solar/Wind Helper
0.297
209137AF2-361 C
Solar/Wind Helper
0.864
237001AB1-127_GEN
Solar/Wind Helper
0.221
237002AB1-128_GEN
Solar/Wind Helper
0.212
235063AE1-101 C2
Solar/Wind Helper
0.747
970099AG2-077 GEN
Solar/Wind Harmer
2.697
3152131X4-039 ST
50/50
3.158
3152121X4-039 GT2
50/50
2.001
970467AG2-304 GEN
50/50
15.27
3150221REMNGT2
Adder
12.559
3150211REMNGT1
Adder
12.476
972201AH1-685 GEN
Adder
2.167
3150281M RUN A
Adder
13.444
316006AB2-029 C
Solar/Wind Harmer
0.632
971685AH1-345 GEN
Solar/Wind Harmer
0.963
3140676OCCOQUN
Adder
0.237
316254AC1-120 GEN1
Solar/Wind Harmer
0.825
316045AC1-158 PL2
Solar/Wind Harmer
3.177
315683AE1-153 C
Solar/Wind Harmer
9.363
972223AH1-696 GEN
Adder
6.699
3150151POSSMC1
Adder
0.848
3147666LOUISA
Solar/Wind Harmer
-0.038
316192AB2-158 GEN
Solar/Wind Harmer
1.122
3151751LOISA D
Adder
5.425
3141346CRANES
Adder
0.098
972197AH1-683 GEN
Adder
1.698
972219AH1-694 GEN
Adder
1.223
966881AG1-559 GEN
Solar/Wind Harmer
0.092
957971AF2-091 GEN
Solar/Wind Harmer
0.888
972135AH1-637 GEN
Solar/Wind Harmer
0.887
316337AD2-073 GEN
Solar/Wind Harmer
0.235
3150351NORNECKC2
Adder
0.77
964211AG1-282 GEN
Solar/Wind Harmer
0.261
3141726DUNNSVL
Solar/Wind Harmer
-0.034
962861AG1-135 GEN
Solar/Wind Harmer
3.239
961951AG1-038 GEN
Solar/Wind Harmer
1.136
3143226MDLTHAN
Solar/Wind Harmer
-0.009
3142416OLDCHRC
Solar/Wind Harmer
-0.022
3142416OLDCHRC
Solar/Wind Harmer
-0.008
3143526WINTERP
Solar/Wind Harmer
-0.044
3138133OCRAN
Solar/Wind Harmer
-0.005
3141766HARMONY
Solar/Wind Harmer
-0.002
971777AH1-397 GEN
Solar/Wind Harmer
1.006
3141843SHACKLE
Adder
0.389
3150851SPRUNCC
Adder
0.351
3143096IRON208
Adder
0.319
3142433PROV 92
Solar/Wind Harmer
-0.034
3142433PROV 92
Adder
0.148
3142433PROV 92
Adder
0.148
3142543TWELFTH
Solar/Wind Harmer
-0.001
944631AF1-128 GEN
Adder
36.159
316159AE1-175 C
Solar/Wind Harmer
0.227
971317AH1-138 GEN
Solar/Wind Harmer
1.057
315671AE2-027_GEN
Solar/Wind Harmer
6.335
970129AG2-093 GEN
Solar/Wind Harmer
1.926
316458AB2-190 GEN2
Solar/Wind Harmer
0.854
971069AG2-661 GEN
Solar/Wind Harmer
1.334
3138126ROCKLANDING
Solar/Wind Harmer
0.026
971647AH1-324 GEN
Solar/Wind Harmer
4.206
961611AG1-000B GEN
Solar/Wind Harmer
4.146
3151171GRAVELC
Adder
0.794
3145336SMITFLD
Solar/Wind Harmer
-0.033
316294AC1-161 GEN
Solar/Wind Harmer
2.704
3143336POWHATN
Solar/Wind Harmer
0.991
970659AG2-427 GEN
Solar/Wind Harmer
4.431
316381AD1-082 GEN
Solar/Wind Harmer
0.765
316375AC2-012 GEN
Solar/Wind Harmer
2.88
3150981CHESPKA
Adder
0.925
944591AF1-124 GEN
Solar/Wind Harmer
37.981
970661AG2-428 GEN
Solar/Wind Harmer
8.843
316072AD1-144
Solar/Wind Harmer
0.168
939411AE1-173 GEN
Solar/Wind Harmer
41.494
940641AE2-051 GEN
Solar/Wind Harmer
7.777
316336AC2-165 C
Solar/Wind Harmer
1.441
316388AE2-253 GEN
Solar/Wind Harmer
0.559
3146456SLIGO L269
Solar/Wind Harmer
-0.008
316246AF1-032 C
Solar/Wind Harmer
0.167
316093AE2-104_GEN
Solar/Wind Harmer
2.401
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.008
315800Z1-036_GEN1
Solar/Wind Harmer
2.009
970937AG2-583 GEN
Solar/Wind Harmer
5.84
3130156CHOWAN
Solar/Wind Harmer
-0.008
3145663CRESWEL
Solar/Wind Harmer
-0.022
971163AH1-040 GEN
Solar/Wind Harmer
7.509
972003AH1-546 GEN
Solar/Wind Harmer
3.978
316322AB2-045
Solar/Wind Harmer
0.267
3146776BUCKING
Solar/Wind Harmer
-0.003
970919AG2-571 GEN
Solar/Wind Harmer
2.505
316023GEN1_S
Solar/Wind Harmer
0.534
3146206CASHIE
Solar/Wind Harmer
-0.008
970087AG2-069 GEN
Solar/Wind Harmer
7.409
971547AH1-271 GEN
Solar/Wind Harmer
1.976
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
3146926FARMVIL
Solar/Wind Harmer
-0.005
3146173TUNIS
Solar/Wind Harmer
-0.008
972277AH1-723 GEN
Adder
41.593
3147043LAWRENC
Adder
0.626
3144293JTRSVLE
Adder
0.22
223401AF1-299 GEN
Solar/Wind Helper
0.379
23779801AA1-109
Solar/Wind Helper
0.182
966131AG1-482 GEN
Solar/Wind Helper
0.066
233930AB2-032 GEN
Solar/Wind Helper
0.301
233915AB1-141 GEN
Solar/Wind Helper
0.397
232422X3-066 FULL
Solar/Wind Helper
0.09
233964AF2-378 GEN
Solar/Wind Helper
0.033
232426Y1-080 FULL
Solar/Wind Helper
0.031
233998TM1NIN_3.36
Solar/Wind Helper
0.206
232428Y3-058 C
Solar/Wind Helper
0.266
232404W1-003 C
Solar/Wind Helper
0.4
233954AC2-188 GEN
Solar/Wind Helper
0.183
233950AC2-186 GEN
Solar/Wind Helper
0.091
232434Z2-077 GEN
Solar/Wind Helper
0.1
233972AC1-094 C
Solar/Wind Helper
0.238
230511AF1-262
Solar/Wind Helper
0.011
230434AG1-499 GEN
Solar/Wind Helper
0.177
228728W1-130C
Solar/Wind Helper
0.041
219258KINSLEYDEP C
Solar/Wind Helper
0.059
219904AC1-010 C
Solar/Wind Helper
0.047
219907AC1-030 C
Solar/Wind Helper
0.026
218660EHAMPSOLAR C
Solar/Wind Helper
0.025
219686LUMSOLAR_N C
Solar/Wind Helper
0.031
219304NAMERICA C
Solar/Wind Helper
0.1
20720728JCB_W1-129
Solar/Wind Helper
0.043
207445AB1-138_GEN
Solar/Wind Helper
0.079
963711AG1-223 GEN
Solar/Wind Helper
0.048
20714828MDF_W3-079
Solar/Wind Helper
0.099
205941AD2-115 GEN
Solar/Wind Helper
0.375
219680HOPEWELLV C1
Solar/Wind Helper
0.002
207454AA2-184 E
Solar/Wind Helper
0.234
20715228NPK_W1-113
Solar/Wind Helper
0.059
20742028HF_AC1-207
Solar/Wind Helper
0.106
218428ETC SOLAR C
Solar/Wind Helper
0.004
217213AMBOY SO C
Solar/Wind Helper
0.021
207528AF2-192 GEN
Solar/Wind Helper
0.057
20673628F1S_V4-069
Solar/Wind Helper
0.022
20675428EAM_W2-061
Solar/Wind Helper
0.012
20676428JCR_X2-075
Solar/Wind Helper
0.051
217209CENTRL HS C
Solar/Wind Helper
0.006
217208PARK ELE C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.017
207439AE1-081 C O1
Solar/Wind Helper
0.014
207437AD2-070 GEN
Solar/Wind Helper
0.101
20675828AU_W4-064
Solar/Wind Helper
0.022
207518AF1-320_GEN
Solar/Wind Helper
1.156
20671928W4-073
Solar/Wind Helper
0.066
961301AF2-421 GEN
Solar/Wind Helper
0.309
963151AG1-164 GEN
Solar/Wind Helper
0.309
212266LOR1
Solar/Wind Helper
0.033
961341AF2-425 GEN
Solar/Wind Helper
0.302
212507AE2-042_GEN
Solar/Wind Helper
1.058
946731AF1-337 GEN
Solar/Wind Helper
0.297
209071AE2-133 GEN
Solar/Wind Helper
0.054
235062AE1-101 C1
Solar/Wind Helper
0.747
237080AD1-060 GEN
Solar/Wind Helper
0.151
237038AE2-054 C
Solar/Wind Helper
0.119
957481AF2-042 GEN
Solar/Wind Harmer
6.742
NYPJM->LTFIMP_NY
CLTF
3.269
LGEELTFEXP_LGEE->PJM
CLTF
2.098
WECLTFEXP_WEC->PJM
CLTF
1.126
AG2-052LTFEXP_AG2-052->PJM
LTF
0.067
AH1-155LTFEXP_AH1-155->PJM
LTF
0.101
LAGNLTFEXP_LAGN->PJM
CLTF
6.958
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.786
TVALTFEXP_TVA->PJM
CLTF
3.503
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.819
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.851
MECLTFEXP_MEC->PJM
CLTF
5.133
SIGELTFEXP_SIGE->PJM
CLTF
0.162
CPLELTFEXP_CPLE->PJM
CLTF
5.01
CBM West 2LTFEXP_CBM-W2->PJM
CBM
43.81

Details for 8BRAMBLETON-AH1-727 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 9344_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8BRAMBLETON-AH1-727 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 9344_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.63 %
Rating:3256.16 MVA
Rating Type:B
MVA to Mitigate:3472.07
MW Contribution:97.34
Bus #Bus NameTypeMW Contribution
971253AH1-086 GEN
50/50
24.442
971257AH1-088 GEN
50/50
5.432
3150301M RUN C
50/50
43.549
3150291M RUN B
50/50
43.226
3150231REMNGT3
50/50
43.711
3150241REMNGT4
50/50
40.756
972217AH1-693 GEN
50/50
5.373
972199AH1-684 GEN
Adder
5.823
3141196NOKESVL
Solar/Wind Harmer
1.195
316044AC1-158 PL1
Solar/Wind Harmer
1.369
316450AC1-158 RIC
Solar/Wind Harmer
0.365
316170AC1-121 GEN2
Solar/Wind Harmer
0.291
3132273ORANGE
Solar/Wind Harmer
0.051
3147666LOUISA
Solar/Wind Harmer
0.563
3150401LDYSMT4
Adder
31.841
3150371LDYSMT1
Adder
30.767
3151761LOISA E
Adder
31.228
972183AH1-676 GEN
Adder
251.695
3150331BIRCHWDA
Adder
38.122
3150151POSSMC1
Adder
2.229
3150151POSSMC1
Adder
2.229
3141316ARNOLDS
Adder
0.53
971781AH1-399 GEN
Solar/Wind Harmer
0.287
970737AG2-469 GEN
Solar/Wind Harmer
9.258
3141906WESTMOR
Solar/Wind Harmer
0.086
316473AC1-191 GEN
Solar/Wind Harmer
0.726
3142416OLDCHRC
Solar/Wind Harmer
2.065
3150351NORNECKC2
Adder
2.16
316404AE1-155 C
Solar/Wind Harmer
0.048
970293AG2-193 GEN
Solar/Wind Harmer
2.259
970009AG2-005 GEN
Solar/Wind Harmer
1.58
962971AG1-146 GEN
Solar/Wind Harmer
3.381
3150861SPRUNCD
Adder
0.972
3143096IRON208
Adder
0.883
3143096IRON208
Adder
0.866
3141766HARMONY
Solar/Wind Harmer
2.802
3142433PROV 92
Adder
0.408
3142433PROV 92
Adder
0.408
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3141843SHACKLE
Adder
1.073
3142946ENON
Solar/Wind Harmer
0.07
316280AD1-041 GEN
Solar/Wind Harmer
0.004
316156AD2-030 GEN
Solar/Wind Harmer
0.155
3141873WAN 176
Solar/Wind Harmer
3.731
316382AG1-145 C
Solar/Wind Harmer
0.002
970133AG2-095 GEN
Solar/Wind Harmer
1.99
970129AG2-093 GEN
Solar/Wind Harmer
12.476
965281AG1-393 GEN
Solar/Wind Harmer
2.197
315778AD1-151 GEN
Solar/Wind Harmer
16.459
3150921YORKTN3
Adder
5.164
315839AE2-212 C
Solar/Wind Harmer
0.002
3144216WINCHST
Adder
0.774
961611AG1-000B GEN
Solar/Wind Harmer
5.45
3151221GRAVEL6
Adder
14.814
3151171GRAVELC
Adder
2.85
315813AE1-149 C
Solar/Wind Harmer
10.825
3145336SMITFLD
Solar/Wind Harmer
0.081
315773AC2-141 GEN
Solar/Wind Harmer
7.404
970659AG2-427 GEN
Solar/Wind Harmer
2.135
3144536CHRHLND
Solar/Wind Harmer
0.03
316083AB2-161 GEN
Solar/Wind Harmer
0.003
3151101ELIZAR3
Adder
18.67
3144873MCLAUGH
Solar/Wind Harmer
0.005
944581AF1-123 GEN
Solar/Wind Harmer
45.254
944601AF1-125 GEN
Solar/Wind Harmer
44.557
316164AC1-076 GEN
Solar/Wind Harmer
0.382
3150411LDYSMT5
Adder
31.941
3150381LDYSMT2
Adder
30.569
972213AH1-691 GEN
Adder
5.171
972215AH1-692 GEN
Adder
5.171
3147346CASHSCORNER
Solar/Wind Harmer
0.532
3141426STAFORD
Solar/Wind Harmer
0.05
972189AH1-679 GEN
Adder
3.695
944491AF1-114 GEN
Solar/Wind Harmer
0.001
316223AC1-118
Solar/Wind Harmer
0.155
316312AB1-027
Solar/Wind Harmer
0.381
3141813NORNECK
Solar/Wind Harmer
0.213
316233AE1-074 FULL
Solar/Wind Harmer
0.17
971281AH1-106 GEN
Solar/Wind Harmer
2.946
971283AH1-107 GEN
Solar/Wind Harmer
2.946
970053AG2-049 GEN
Adder
3.548
970327AG2-215 GEN
Solar/Wind Harmer
6.945
962981AG1-147 GEN
Solar/Wind Harmer
7.889
971285AH1-108 GEN
Adder
1.591
3141783LANCAST
Solar/Wind Harmer
0.126
3141783LANCAST
Solar/Wind Harmer
0.084
315976AC1-164 GENA
Solar/Wind Harmer
21.836
316169AC1-164_GENC
Solar/Wind Harmer
18.864
315975AC1-164 GENB
Solar/Wind Harmer
0.646
3138133OCRAN
Solar/Wind Harmer
0.063
316314AB2-024 C
Solar/Wind Harmer
0.001
3141913WHIT STONE
Solar/Wind Harmer
0.21
3143873LANEXA
Solar/Wind Harmer
0.126
316059AD1-063 C
Solar/Wind Harmer
0.001
3142433PROV 92
Adder
0.408
3142433PROV 92
Adder
0.408
971167AH1-042 GEN
Solar/Wind Harmer
18.654
970189AG2-124 GEN
Solar/Wind Harmer
6.224
315662AE1-191 GEN
Solar/Wind Harmer
0.007
315666AE1-190 GEN
Solar/Wind Harmer
0.002
3141873WAN 176
Solar/Wind Harmer
0.042
3138283WHITEMARSH
Solar/Wind Harmer
0.048
316132AB2-190 GEN1
Solar/Wind Harmer
1.107
316369SG1_INVT
Solar/Wind Harmer
0.008
972265AH1-717 GEN
Adder
15.821
3151201GRAVEL4
Adder
14.831
3151191GRAVEL3
Adder
14.643
3151211GRAVEL5
Adder
14.643
3143316POE
Solar/Wind Harmer
0.803
971445AH1-216 GEN
Solar/Wind Harmer
14.282
3151081ELIZAR1
Adder
18.434
3151091ELIZAR2
Adder
18.114
3152611GOSPORTB
Adder
2.56
3152621GOSPORTC
Adder
2.173
3152601GOSPORTA
Adder
2.005
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.137
316311AC2-079 GEN
Solar/Wind Harmer
5.725
957871AF2-081 GEN
Solar/Wind Harmer
9.922
319010AE1-072 C
Solar/Wind Harmer
1.001
316305AF2-043 C
Solar/Wind Harmer
0.002
3146406KITTY HAWK
Solar/Wind Harmer
0.025
315835AF2-110_GEN
Solar/Wind Harmer
1.359
313526AB2-022
Solar/Wind Harmer
0.107
3146486SUNBURY
Solar/Wind Harmer
0.197
3146486SUNBURY
Solar/Wind Harmer
0.197
316321Z2-027
Solar/Wind Harmer
0.037
3146396TANGLEW
Solar/Wind Harmer
0.542
3145176PASQUOTANK
Solar/Wind Harmer
0.122
316315AB2-025 C
Solar/Wind Harmer
0.157
941031AE2-094 GEN
Solar/Wind Harmer
35.747
944011AF1-069 GEN
Solar/Wind Harmer
11.68
315814AE2-033 C
Solar/Wind Harmer
15.327
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
970673AG2-436 GEN
Solar/Wind Harmer
40.848
970673AG2-436 GEN
Solar/Wind Harmer
27.232
3130156CHOWAN
Solar/Wind Harmer
0.19
3130156CHOWAN
Solar/Wind Harmer
0.19
971967AH1-528 GEN
Solar/Wind Harmer
30.407
315816AE2-034 GEN
Solar/Wind Harmer
0.803
3130546PLYMOUTH
Solar/Wind Harmer
0.184
315732AD1-074 GEN1
Solar/Wind Harmer
1.056
315733AD1-074 GEN2
Solar/Wind Harmer
1.056
315735AD1-075 GEN1
Solar/Wind Harmer
0.529
965291AG1-394 GEN
Solar/Wind Harmer
0.815
970085AG2-068 GEN
Solar/Wind Harmer
9.72
970581AG2-369 GEN
Solar/Wind Harmer
8.359
3146206CASHIE
Solar/Wind Harmer
0.182
970601AG2-382 GEN
Solar/Wind Harmer
6.803
3145893MURPHYS
Solar/Wind Harmer
0.491
3145893MURPHYS
Solar/Wind Harmer
0.182
3145513AHOSKIE
Solar/Wind Harmer
0.376
3145513AHOSKIE
Solar/Wind Harmer
0.179
3146043SEABORD
Solar/Wind Harmer
0.179
3145683EARLEYS
Solar/Wind Harmer
0.358
3145683EARLEYS
Solar/Wind Harmer
0.179
3145683EARLEYS
Solar/Wind Harmer
0.179
315607AA1-063A GEN
Solar/Wind Harmer
0.365
316087AB2-174 GEN
Solar/Wind Harmer
0.005
3137643SOCKMAN
Solar/Wind Harmer
0.704
315652AC1-086 GEN
Solar/Wind Harmer
19.374
970285AG2-188 GEN
Solar/Wind Harmer
13.847
971845AH1-439 GEN
Solar/Wind Harmer
7.933
972205AH1-687 GEN
Adder
7.463
3145796HORNRTN
Solar/Wind Harmer
0.556
3145796HORNRTN
Solar/Wind Harmer
0.07
3146033SCOT NK
Solar/Wind Harmer
0.691
315657AE1-056 GEN
Solar/Wind Harmer
5.923
946301AF1-294 GEN
Solar/Wind Harmer
3.377
961791AG1-021 GEN
Solar/Wind Harmer
1.643
970683AG2-441 GEN
Solar/Wind Harmer
11.355
970681AG2-440 GEN
Solar/Wind Harmer
9.084
970831AG2-522 GEN
Solar/Wind Harmer
7.264
3144303KENBRDG
Solar/Wind Harmer
0.135
971443AH1-215 GEN
Solar/Wind Harmer
2.845
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316005AA1-067
Solar/Wind Harmer
0.179
3145746EVERETS
Solar/Wind Harmer
0.664
3145746EVERETS
Solar/Wind Harmer
0.167
3145746EVERETS
Solar/Wind Harmer
0.167
3145746EVERETS
Solar/Wind Harmer
0.167
970181AG2-120 GEN
Solar/Wind Harmer
2.078
971447AH1-217 GEN
Solar/Wind Harmer
5.04
971255AH1-087 GEN
50/50
5.432
971259AH1-089 GEN
50/50
5.432
3150281M RUN A
50/50
43.576
3150221REMNGT2
50/50
40.487
972201AH1-685 GEN
50/50
6.985
3150211REMNGT1
Adder
37.902
316006AB2-029 C
Solar/Wind Harmer
0.002
971685AH1-345 GEN
Solar/Wind Harmer
2.219
316045AC1-158 PL2
Solar/Wind Harmer
4.376
316254AC1-120 GEN1
Solar/Wind Harmer
0.583
315683AE1-153 C
Solar/Wind Harmer
20.71
3147666LOUISA
Solar/Wind Harmer
0.979
316192AB2-158 GEN
Solar/Wind Harmer
1.381
972197AH1-683 GEN
Adder
4.972
972219AH1-694 GEN
Adder
3.58
3151751LOISA D
Adder
15.317
3140676OCCOQUN
Adder
0.566
966881AG1-559 GEN
Solar/Wind Harmer
0.265
3141346CRANES
Adder
0.266
972223AH1-696 GEN
Adder
17.606
3150151POSSMC1
Adder
2.229
972135AH1-637 GEN
Solar/Wind Harmer
1.858
316337AD2-073 GEN
Solar/Wind Harmer
0.187
3142416OLDCHRC
Solar/Wind Harmer
0.554
3142416OLDCHRC
Solar/Wind Harmer
0.212
3150351NORNECKC2
Adder
2.124
3141726DUNNSVL
Solar/Wind Harmer
0.851
3143226MDLTHAN
Solar/Wind Harmer
0.212
3143526WINTERP
Solar/Wind Harmer
1.104
962861AG1-135 GEN
Solar/Wind Harmer
6.784
3150851SPRUNCC
Adder
0.972
3143096IRON208
Adder
0.883
3142543TWELFTH
Solar/Wind Harmer
0.02
3138133OCRAN
Solar/Wind Harmer
0.126
3141766HARMONY
Solar/Wind Harmer
0.042
3142433PROV 92
Solar/Wind Harmer
0.84
3142433PROV 92
Adder
0.408
3142433PROV 92
Adder
0.408
971777AH1-397 GEN
Solar/Wind Harmer
0.554
3141843SHACKLE
Adder
1.073
944631AF1-128 GEN
Adder
99.968
316159AE1-175 C
Solar/Wind Harmer
0.179
971317AH1-138 GEN
Solar/Wind Harmer
1.542
970129AG2-093 GEN
Solar/Wind Harmer
5.871
315671AE2-027_GEN
Solar/Wind Harmer
13.209
316458AB2-190 GEN2
Solar/Wind Harmer
1.107
971069AG2-661 GEN
Solar/Wind Harmer
3.658
3138126ROCKLANDING
Solar/Wind Harmer
0.094
971647AH1-324 GEN
Solar/Wind Harmer
8.741
961611AG1-000B GEN
Solar/Wind Harmer
10.718
3151171GRAVELC
Adder
2.168
3145336SMITFLD
Solar/Wind Harmer
0.811
316294AC1-161 GEN
Solar/Wind Harmer
3.512
970659AG2-427 GEN
Solar/Wind Harmer
9.759
316381AD1-082 GEN
Solar/Wind Harmer
0.21
316375AC2-012 GEN
Solar/Wind Harmer
0.005
3150981CHESPKA
Adder
2.51
944591AF1-124 GEN
Solar/Wind Harmer
45.415
970661AG2-428 GEN
Solar/Wind Harmer
19.99
316072AD1-144
Solar/Wind Harmer
0.072
939411AE1-173 GEN
Solar/Wind Harmer
85.364
940641AE2-051 GEN
Solar/Wind Harmer
15.997
316388AE2-253 GEN
Solar/Wind Harmer
0.625
3146456SLIGO L269
Solar/Wind Harmer
0.199
316246AF1-032 C
Solar/Wind Harmer
0.09
316093AE2-104_GEN
Solar/Wind Harmer
3.331
3143336POWHATN
Solar/Wind Harmer
3.511
3146516WINFALL
Solar/Wind Harmer
0.632
3146516WINFALL
Solar/Wind Harmer
0.195
316336AC2-165 C
Solar/Wind Harmer
0.008
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.19
3145663CRESWEL
Solar/Wind Harmer
0.523
971163AH1-040 GEN
Solar/Wind Harmer
14.962
970937AG2-583 GEN
Solar/Wind Harmer
11.244
970919AG2-571 GEN
Solar/Wind Harmer
6.502
316023GEN1_S
Solar/Wind Harmer
0.409
970087AG2-069 GEN
Solar/Wind Harmer
14.579
3146206CASHIE
Solar/Wind Harmer
0.182
971547AH1-271 GEN
Solar/Wind Harmer
3.887
3145893MURPHYS
Solar/Wind Harmer
0.727
3145893MURPHYS
Solar/Wind Harmer
0.809
3146173TUNIS
Solar/Wind Harmer
0.18
960081AF2-299 GEN
Solar/Wind Harmer
1.72
3145683EARLEYS
Solar/Wind Harmer
0.179
957481AF2-042 GEN
Solar/Wind Harmer
47.712
3146263WOODLND
Solar/Wind Harmer
0.178
315693AD1-088 GEN
Solar/Wind Harmer
8.533
962491AG1-098 GEN
Solar/Wind Harmer
10.141
971795AH1-408 GEN
Solar/Wind Harmer
11.784
3145963POPLR C
Solar/Wind Harmer
0.176
316011AB1-132 GEN
Solar/Wind Harmer
3.202
962571AG1-106 GEN
Solar/Wind Harmer
2.506
316190AA2-174 GEN
Solar/Wind Harmer
0
3145823KELFORD
Solar/Wind Harmer
0.176
3147043LAWRENC
Adder
1.589
3146926FARMVIL
Solar/Wind Harmer
0.105
316174AB2-169 GEN
Solar/Wind Harmer
0.005
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.07
972003AH1-546 GEN
Solar/Wind Harmer
7.424
3145783HORNRTN
Solar/Wind Harmer
0.174
3145796HORNRTN
Solar/Wind Harmer
0.573
3145796HORNRTN
Solar/Wind Harmer
0.174
963171AG1-166 GEN
Solar/Wind Harmer
0.913
971563AH1-280 GEN
Solar/Wind Harmer
1.826
3144293JTRSVLE
Adder
0.545
316212AC1-099_GEN
Solar/Wind Harmer
0.882
970685AG2-442 GEN
Solar/Wind Harmer
12.717
3146293MARTNCO
Solar/Wind Harmer
0.158
316129AC1-054 GEN
Solar/Wind Harmer
0.638
971065AG2-659 GEN
Solar/Wind Harmer
7.218
971377AH1-170 GEN
Solar/Wind Harmer
1.79
3147623JAMES R
Solar/Wind Harmer
0.389
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3145746EVERETS
Solar/Wind Harmer
0.167
3145746EVERETS
Solar/Wind Harmer
0.167
315722AD1-056 GEN
Solar/Wind Harmer
1.053
315687AD1-152 GEN
Solar/Wind Harmer
0.005
316494AC1-189 GEN
Solar/Wind Harmer
0.556
972277AH1-723 GEN
Adder
97.342
3146233WITAKRS
Solar/Wind Harmer
0.648
961671AG1-007 GEN
Solar/Wind Harmer
0.025
3146083TARBORO
Solar/Wind Harmer
0.163
3145493TOT1
Solar/Wind Harmer
0.723
3145543BTLEBRO
Solar/Wind Harmer
0.16
3145543BTLEBRO
Solar/Wind Harmer
0.128
316359AB2-059 GEN
Solar/Wind Harmer
0.576
316049AB1-081 GEN
Solar/Wind Harmer
0.917
3142053HEARTS
Solar/Wind Harmer
0.282
970401AG2-262 GEN
Solar/Wind Harmer
0.935
316003AC1-222 GEN
Solar/Wind Harmer
0.004
3147983MERCK5
Solar/Wind Harmer
0.05
315705AF1-075 GEN
Solar/Wind Harmer
4.991
23779801AA1-109
Solar/Wind Helper
0.222
237080AD1-060 GEN
Solar/Wind Helper
0.373
237038AE2-054 C
Solar/Wind Helper
0.293
235062AE1-101 C1
Solar/Wind Helper
1.773
233998TM1NIN_3.36
Solar/Wind Helper
0.269
233972AC1-094 C
Solar/Wind Helper
0.312
232404W1-003 C
Solar/Wind Helper
0.523
232428Y3-058 C
Solar/Wind Helper
0.348
232434Z2-077 GEN
Solar/Wind Helper
0.131
232426Y1-080 FULL
Solar/Wind Helper
0.04
233964AF2-378 GEN
Solar/Wind Helper
0.043
233954AC2-188 GEN
Solar/Wind Helper
0.239
233950AC2-186 GEN
Solar/Wind Helper
0.12
232422X3-066 FULL
Solar/Wind Helper
0.117
233930AB2-032 GEN
Solar/Wind Helper
0.391
970661AG2-428 GEN
Solar/Wind Harmer
4.252
3146456SLIGO L269
Solar/Wind Harmer
0.199
971153AH1-033 GEN
Solar/Wind Harmer
2.3
316313AB2-026
Solar/Wind Harmer
0.124
316258AE1-075 C
Solar/Wind Harmer
0.149
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
2.984
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.195
3146626S HERTFORD
Solar/Wind Harmer
0.194
3145273HOLLAND
Solar/Wind Harmer
0.145
3146376EDENTON
Solar/Wind Harmer
0.19
315614AA2-178 GEN
Solar/Wind Harmer
1.07
971157AH1-035 GEN
Solar/Wind Harmer
2.212
3156081AA2-088 GEN
Solar/Wind Harmer
0.004
315737AD1-076 GEN
Solar/Wind Harmer
2.365
970917AG2-570 GEN
Solar/Wind Harmer
16.254
316365GEN2_N
Solar/Wind Harmer
0.409
3146206CASHIE
Solar/Wind Harmer
0.182
3145893MURPHYS
Solar/Wind Harmer
0.304
3145893MURPHYS
Solar/Wind Harmer
0.182
957521AF2-046 GEN
Solar/Wind Harmer
13.506
961681AG1-008 GEN
Solar/Wind Harmer
13.506
3146173TUNIS
Solar/Wind Harmer
0.18
3156021HOLLOMANSOL
Solar/Wind Harmer
0.817
316463AE2-346 GEN
Solar/Wind Harmer
0.154
316140AB2-099
Solar/Wind Harmer
0.064
962331AG1-082 GEN
Solar/Wind Harmer
1.916
3146263WOODLND
Solar/Wind Harmer
0.178
313506AB2-031 GEN
Solar/Wind Harmer
0.548
3142666NORTHAMPTON
Solar/Wind Harmer
0.176
3145963POPLR C
Solar/Wind Harmer
0.176
970909AG2-566 GEN
Solar/Wind Harmer
1.881
316317KELFORD C
Solar/Wind Harmer
0.017
3145823KELFORD
Solar/Wind Harmer
0.176
3147043LAWRENC
Solar/Wind Harmer
0.105
3146926FARMVIL
Solar/Wind Harmer
0.105
3146776BUCKING
Solar/Wind Harmer
0.063
3145796HORNRTN
Solar/Wind Harmer
0.695
3145796HORNRTN
Solar/Wind Harmer
0.174
316478AD1-087 GEN
Solar/Wind Harmer
0.607
316486AD2-202 GEN
Solar/Wind Harmer
0.178
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3147133PAMPLIN
Solar/Wind Harmer
0.539
971193AH1-056 GEN
Solar/Wind Harmer
10.456
963181AG1-167 GEN
Solar/Wind Harmer
0.685
3144293JTRSVLE
Adder
0.545
316210AC1-098 GEN
Solar/Wind Harmer
1.582
3145933PARMELE
Solar/Wind Harmer
0.17
966801AG1-551 GEN
Solar/Wind Harmer
1.979
959311AF2-222 GEN
Solar/Wind Harmer
15.084
970257AG2-171 GEN
Solar/Wind Harmer
5.422
315785AD2-033 C
Solar/Wind Harmer
1.375
964241AG1-285 GEN
Solar/Wind Harmer
11.211
970221AG2-151 GEN
Solar/Wind Harmer
8.948
316131AB2-060 GEN
Solar/Wind Harmer
0.527
3145746EVERETS
Solar/Wind Harmer
0.167
3145746EVERETS
Solar/Wind Harmer
0.167
315724AD1-057 GEN
Solar/Wind Harmer
0.624
316327AA2-057 GEN
Solar/Wind Harmer
0.25
972255AH1-712 GEN
Adder
83.534
3146233WITAKRS
Solar/Wind Harmer
0.817
3146233WITAKRS
Solar/Wind Harmer
0.111
3146073TAR RVR
Solar/Wind Harmer
0.163
3146083TARBORO
Solar/Wind Harmer
0.163
3138543CONSLDL
Solar/Wind Harmer
0.107
961601AG1-000A GEN
Solar/Wind Harmer
11.396
3145543BTLEBRO
Solar/Wind Harmer
0.16
3145543BTLEBRO
Solar/Wind Harmer
0.16
971623AH1-311 GEN
Solar/Wind Harmer
0.32
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
6.556
971683AH1-343 GEN
Solar/Wind Harmer
5.342
316283AC2-100 C
Solar/Wind Harmer
0.274
3148013FISHERV
Solar/Wind Harmer
0.138
315616AA1-038_C
Solar/Wind Harmer
0.001
3151861LOWMORA
Adder
1.283
237061AD1-155 GEN
Solar/Wind Harmer
0.003
238221AF1-254 C O1
Solar/Wind Helper
0.304
237030AB1-096 C
Solar/Wind Helper
0.08
235067AD1-061 GEN
Solar/Wind Helper
0.532
205917AD1-020 ES
Solar/Wind Helper
0.38
233994AC2-023 GEN
Solar/Wind Helper
0.99
233996TM1833_GEN
Solar/Wind Helper
0.269
233997TMININ_4.2
Solar/Wind Helper
0.269
233971AC1-093 C
Solar/Wind Helper
0.369
232406W1-004 FULL
Solar/Wind Helper
0.523
233940AF2-379 C
Solar/Wind Helper
0.064
234015AF2-250 C
Solar/Wind Helper
0.039
233952AC2-187 GEN
Solar/Wind Helper
0.239
233918AB1-142 GEN
Solar/Wind Helper
0.516
233982AB2-133 GEN
Solar/Wind Helper
0.368
230430AE1-229_GEN
Solar/Wind Helper
3.449
230415AB2-049 C
Solar/Wind Helper
0.031
228729W2-030 C
Solar/Wind Helper
0.113
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.056
219291REEVESSOUT C
Solar/Wind Helper
0.012
219912AD2-042 GEN
Solar/Wind Helper
0.153
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.043
219348LDSOLAR C
Solar/Wind Helper
0.117
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.064
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.058
20714528FRN_Y2-051
Solar/Wind Helper
0.058
219276PARKLANDSO C
Solar/Wind Helper
0.091
20720528MAN_W1-024
Solar/Wind Helper
0.029
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.028
219908AB1-139 C
Solar/Wind Helper
0.075
219249CENTRALDIV C
Solar/Wind Helper
0.01
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.09
957861AF2-080 GEN
Solar/Wind Harmer
7.098
316420AA1-050 GEN
Solar/Wind Harmer
0.005
972193AH1-681 GEN
Adder
3.732
316319Z2-044 C
Solar/Wind Harmer
0
3138266HYDRAULIC
Solar/Wind Harmer
0.007
3138266HYDRAULIC
Solar/Wind Harmer
0.004
3145573BETHELC
Solar/Wind Harmer
0.163
3145573BETHELC
Solar/Wind Harmer
0.163
316118AC1-105 GEN
Solar/Wind Harmer
0.404
3147173SINAI
Solar/Wind Harmer
0.154
3147243WELCO
Solar/Wind Harmer
0.096
270494AE1-108_GEN
Solar/Wind Harmer
1.806
970865AG2-541 GEN
Solar/Wind Harmer
4.891
3148133STUARTS
Solar/Wind Harmer
0.083
3148013FISHERV
Solar/Wind Harmer
0.079
316123AC1-075 GEN
Solar/Wind Harmer
0.181
970165AG2-112 GEN
Solar/Wind Harmer
1.076
970163AG2-111 GEN
Solar/Wind Harmer
1.027
3148463FAIRFLD
Solar/Wind Harmer
0.12
3151881LOWMORC
Adder
1.273
3151881LOWMORC
Adder
1.253
3151861LOWMORA
Adder
1.233
237085AD2-009_GEN
Solar/Wind Helper
1.73
238208AF1-136 C
Solar/Wind Helper
0.215
959381AF2-229 GEN
Solar/Wind Helper
0.375
234033AF1-007_GEN
Solar/Wind Helper
7.236
233923SMA
Solar/Wind Helper
0.988
233990AG1-397 GEN
Solar/Wind Helper
0.278
232432Z2-076 GEN
Solar/Wind Helper
0.069
232436AB1-176 C
Solar/Wind Helper
0.046
233935AB2-179 C
Solar/Wind Helper
1.3
203975AE1-071-GEN
Solar/Wind Helper
2.597
964001AG1-254 GEN
Solar/Wind Helper
0.977
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.027
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.117
219688LUMSOLAR_S C
Solar/Wind Helper
0.041
219607WPEMNERT C
Solar/Wind Helper
0.082
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.097
20715828PEM_W1-120
Solar/Wind Helper
0.097
207459AE1-142 C O1
Solar/Wind Helper
0.295
219620RIDERU C
Solar/Wind Helper
0.001
205943AE1-185 GEN
Solar/Wind Helper
0.503
205956AE1-196_GEN
Solar/Wind Helper
0.502
205932AD2-116_GEN
Solar/Wind Helper
0.502
960921AF2-383 GEN
Solar/Wind Helper
0.358
218526CNTRALGAS2 C
Solar/Wind Helper
0.163
20675528CPH_W2-050
Solar/Wind Helper
0.088
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
966261AG1-495 GEN
Solar/Wind Helper
0.082
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20674828DL_W4-046
Solar/Wind Helper
0.008
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
20675128HRM_W1-127
Solar/Wind Helper
0.03
209116AE2-175 GEN
Solar/Wind Helper
1.78
233915AB1-141 GEN
Solar/Wind Helper
0.516
966131AG1-482 GEN
Solar/Wind Helper
0.138
230511AF1-262
Solar/Wind Helper
0.015
228728W1-130C
Solar/Wind Helper
0.055
230434AG1-499 GEN
Solar/Wind Helper
0.235
219258KINSLEYDEP C
Solar/Wind Helper
0.078
219904AC1-010 C
Solar/Wind Helper
0.062
218660EHAMPSOLAR C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.041
219907AC1-030 C
Solar/Wind Helper
0.035
219304NAMERICA C
Solar/Wind Helper
0.134
20720728JCB_W1-129
Solar/Wind Helper
0.058
207445AB1-138_GEN
Solar/Wind Helper
0.106
963711AG1-223 GEN
Solar/Wind Helper
0.065
20714828MDF_W3-079
Solar/Wind Helper
0.132
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.079
207454AA2-184 E
Solar/Wind Helper
0.315
20742028HF_AC1-207
Solar/Wind Helper
0.143
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.077
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.023
205941AD2-115 GEN
Solar/Wind Helper
0.494
207439AE1-081 C O1
Solar/Wind Helper
0.019
20675828AU_W4-064
Solar/Wind Helper
0.03
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.579
20671928W4-073
Solar/Wind Helper
0.09
316447AC1-158 HLD
Solar/Wind Harmer
3.008
315651AD1-115 GEN
Solar/Wind Harmer
0.009
966001AG1-469 GEN
Solar/Wind Harmer
0.139
3150391LDYSMT3
Adder
31.782
972195AH1-682 GEN
Adder
4.177
3151731LOISA B
Adder
15.317
3151721LOISA A
Adder
15.238
315673AE1-157 GEN
Solar/Wind Harmer
16.074
957411AF2-035 GEN
Solar/Wind Harmer
9.794
970317AG2-208 GEN
Solar/Wind Harmer
9.074
3150071POSSM 5
Adder
101.873
3150181POSSMC2
Adder
2.248
3150181POSSMC2
Adder
2.229
3150181POSSMC2
Adder
2.229
316468AD1-105 GEN
Solar/Wind Harmer
-0.071
966871AG1-558 GEN
Solar/Wind Harmer
0.248
3142296MT RD221
Adder
0.683
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.231
3150341NORNECKC1
Adder
2.213
971223AH1-071 GEN
Solar/Wind Harmer
2.268
3143526WINTERP
Solar/Wind Harmer
1.104
3142366NRTHEST
Adder
0.693
958261AF2-120 GEN
Solar/Wind Harmer
7.015
3150691DARBY 3
Adder
15.26
3150701DARBY 4
Adder
15.225
3150681DARBY 2
Adder
15.207
3150671DARBY 1
Adder
15.189
316075AC2-137 C
Solar/Wind Harmer
0.058
3142946ENON
Solar/Wind Harmer
0.021
944641AF1-129 GEN
Adder
98.867
316240AF1-291 C
Solar/Wind Harmer
0.002
316033AB2-134 GEN
Solar/Wind Harmer
0.012
315697AD1-025 GEN
Solar/Wind Harmer
0.231
316236AE1-162_GEN
Solar/Wind Harmer
0.002
970657AG2-426 GEN
Solar/Wind Harmer
7.052
970657AG2-426 GEN
Solar/Wind Harmer
1.478
316036AC1-147 C
Solar/Wind Harmer
0.037
3150991CHESPKB
Adder
2.106
3150991CHESPKB
Adder
2.056
316316AC1-027 C
Solar/Wind Harmer
0.193
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.006
3145506HICKORY
Solar/Wind Harmer
0.8
3145506HICKORY
Solar/Wind Harmer
0.48
3145506HICKORY
Solar/Wind Harmer
0.12
316339AD2-160 GEN
Solar/Wind Harmer
0.323
316018AA1-139 ULT2
Solar/Wind Harmer
0.005
316017AA1-139 ULT1
Solar/Wind Harmer
0.111
3137176SLIGO L2192
Solar/Wind Harmer
0.792
3146456SLIGO L269
Solar/Wind Harmer
3.521
3130086AYDLETT
Solar/Wind Harmer
0.795
3146386ELIZ CT
Solar/Wind Harmer
0.197
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.195
3146516WINFALL
Solar/Wind Harmer
0.195
3146516WINFALL
Solar/Wind Harmer
0.195
3144356SAPONY
Solar/Wind Harmer
1.625
3146626S HERTFORD
Solar/Wind Harmer
0.194
3146626S HERTFORD
Solar/Wind Harmer
0.194
315742AE1-103 GEN
Solar/Wind Harmer
0.002
3146376EDENTON
Solar/Wind Harmer
0.847
3146376EDENTON
Solar/Wind Harmer
0.847
972185AH1-677 GEN
Adder
10.672
972187AH1-678 GEN
Adder
5.366
970933AG2-581 GEN
Solar/Wind Harmer
14.962
316065AD1-022 GEN
Solar/Wind Harmer
8.417
3145893MURPHYS
Solar/Wind Harmer
1.217
3145893MURPHYS
Solar/Wind Harmer
0.327
3146173TUNIS
Solar/Wind Harmer
0.18
3146173TUNIS
Solar/Wind Harmer
0.18
970099AG2-077 GEN
Solar/Wind Harmer
19.085
316181AB2-040 GEN
Solar/Wind Harmer
0.257
971741AH1-377 GEN
Solar/Wind Harmer
17.523
3142666NORTHAMPTON
Solar/Wind Harmer
0.176
3142666NORTHAMPTON
Solar/Wind Harmer
0.176
3142666NORTHAMPTON
Solar/Wind Harmer
0.176
3142666NORTHAMPTON
Solar/Wind Harmer
0.106
970301AG2-198 GEN
Solar/Wind Harmer
7.522
316426AA2-053 GEN
Solar/Wind Harmer
0.594
3145593CAROLNA
Solar/Wind Harmer
0.175
3145593CAROLNA
Solar/Wind Harmer
0.175
966811AG1-552 GEN
Solar/Wind Harmer
1.903
3145593CAROLNA
Solar/Wind Harmer
0.218
3146776BUCKING
Solar/Wind Harmer
0.699
3146776BUCKING
Solar/Wind Harmer
0.057
3145783HORNRTN
Solar/Wind Harmer
3.102
3145783HORNRTN
Solar/Wind Harmer
2.482
3145783HORNRTN
Solar/Wind Harmer
0.776
3145783HORNRTN
Solar/Wind Harmer
0.31
3145796HORNRTN
Solar/Wind Harmer
0.521
3147133PAMPLIN
Solar/Wind Harmer
0.172
3147133PAMPLIN
Solar/Wind Harmer
0.137
958211AF2-115 GEN
Solar/Wind Harmer
2.054
963191AG1-168 GEN
Solar/Wind Harmer
0.685
3144293JTRSVLE
Adder
0.545
3144293JTRSVLE
Adder
0.459
3145933PARMELE
Solar/Wind Harmer
0.34
3145933PARMELE
Solar/Wind Harmer
0.17
316274AC1-208 GEN
Solar/Wind Harmer
0.88
316034AC1-036 C
Solar/Wind Harmer
0.012
970323AG2-213 GEN
Solar/Wind Harmer
7.229
971775AH1-396 GEN
Solar/Wind Harmer
0.271
971489AH1-241 GEN
Solar/Wind Harmer
8.948
313527AB2-043 GEN
Solar/Wind Harmer
0.002
939181AE1-148 GEN
Solar/Wind Harmer
8.005
3145493TOT1
Solar/Wind Harmer
0.377
3145453TOT5
Solar/Wind Harmer
0.226
3145603CNETO
Solar/Wind Harmer
0.151
962561AG1-105 GEN
Solar/Wind Harmer
7.712
961601AG1-000A GEN
Solar/Wind Harmer
2.849
316263AC1-034 GEN
Solar/Wind Harmer
6.088
964791AG1-342 GEN
Solar/Wind Harmer
3.061
3146843MT LREL
Solar/Wind Harmer
0.159
3146843MT LREL
Solar/Wind Harmer
0.159
315821AE2-092 GEN
Solar/Wind Harmer
0.01
971761AH1-387 GEN
Solar/Wind Harmer
2.843
316222AC1-221 GEN
Solar/Wind Harmer
0.583
942751AE2-291 GEN
Solar/Wind Harmer
6.934
3132123MT JACKSON
Solar/Wind Harmer
0.381
970117AG2-086 GEN
Solar/Wind Harmer
2.919
970117AG2-086 GEN
Solar/Wind Harmer
1.946
235020AA1-095 C
Solar/Wind Helper
0.059
23777901MDS_W4-102
Solar/Wind Helper
0.197
237034AC2-136 C
Solar/Wind Helper
0.259
23777801MSM_W1-116
Solar/Wind Helper
0.131
237001AB1-127_GEN
Solar/Wind Helper
0.481
237025AB1-124 C
Solar/Wind Helper
0.187
237006AB1-125 GEN
Solar/Wind Helper
0.14
237002AB1-128_GEN
Solar/Wind Helper
0.48
235063AE1-101 C2
Solar/Wind Helper
1.773
20390526W1-045 C
Solar/Wind Helper
0.368
205916AD1-020 GEN
Solar/Wind Helper
1.767
233987AB2-037 GEN
Solar/Wind Helper
2.414
233901CHERRYDALE C
Solar/Wind Helper
0.239
233939AC1-091 C
Solar/Wind Helper
0.361
233970AC1-092 C
Solar/Wind Helper
0.361
232408W1-005 C
Solar/Wind Helper
0.523
232410W1-006 C
Solar/Wind Helper
0.523
233946AB2-136 GEN
Solar/Wind Helper
0.585
234036AF2-325 C
Solar/Wind Helper
0.043
232424Y1-079 C
Solar/Wind Helper
0.12
233944AB2-135 GEN
Solar/Wind Helper
0.605
233933AB2-153 GEN
Solar/Wind Helper
0.239
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.041
219921AF1-264
Solar/Wind Helper
0.052
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.057
963391AG1-188 GEN
Solar/Wind Helper
0.084
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.192
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.017
20673828FLE_V3-070
Solar/Wind Helper
0.092
207442AE1-156 GEN
Solar/Wind Helper
0.329
20676128MHD_W3-029
Solar/Wind Helper
0.097
217081WEATEXAS C
Solar/Wind Helper
0.013
20671828STAW2-080
Solar/Wind Helper
0.027
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20676228FRD_X1-012
Solar/Wind Helper
0.092
207471AF2-354 C
Solar/Wind Helper
0.169
20674928WA_W3-044
Solar/Wind Helper
0.099
964851AG1-348 GEN
Solar/Wind Helper
0.081
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.074
211065PSPA IPP
Solar/Wind Helper
0.151
211065PSPA IPP
Solar/Wind Helper
0.151
NYPJM->LTFIMP_NY
CLTF
4.891
LGEELTFEXP_LGEE->PJM
CLTF
2.004
WECLTFEXP_WEC->PJM
CLTF
1.006
LAGNLTFEXP_LAGN->PJM
CLTF
9.398
CBM South 2LTFEXP_CBM-S2->PJM
CBM
24.867
TVALTFEXP_TVA->PJM
CLTF
4.772
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.101
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.667
MECLTFEXP_MEC->PJM
CLTF
5.134
SIGELTFEXP_SIGE->PJM
CLTF
0.16
CPLELTFEXP_CPLE->PJM
CLTF
10.838
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.117

Details for 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 594_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:132.78 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5404.52
MW Contribution:98.37
Bus #Bus NameTypeMW Contribution
3150391LDYSMT3
50/50
37.176
972195AH1-682 GEN
50/50
4.885
316447AC1-158 HLD
Solar/Wind Harmer
3.348
315673AE1-157 GEN
Solar/Wind Harmer
17.981
957411AF2-035 GEN
Solar/Wind Harmer
11.052
970317AG2-208 GEN
Solar/Wind Harmer
10.239
3142296MT RD221
Adder
0.803
3142366NRTHEST
Adder
0.809
3150691DARBY 3
Adder
17.772
3150701DARBY 4
Adder
17.73
3150681DARBY 2
Adder
17.71
3150671DARBY 1
Adder
17.689
3143526WINTERP
Solar/Wind Harmer
1.273
316075AC2-137 C
Solar/Wind Harmer
0.067
971223AH1-071 GEN
Solar/Wind Harmer
2.604
966871AG1-558 GEN
Solar/Wind Harmer
0.281
3142946ENON
Solar/Wind Harmer
0.024
944641AF1-129 GEN
Adder
114.635
316240AF1-291 C
Solar/Wind Harmer
0.002
316033AB2-134 GEN
Solar/Wind Harmer
0.014
315697AD1-025 GEN
Solar/Wind Harmer
0.267
316236AE1-162_GEN
Solar/Wind Harmer
0.002
316036AC1-147 C
Solar/Wind Harmer
0.043
3150991CHESPKB
Adder
2.436
3150991CHESPKB
Adder
2.378
970657AG2-426 GEN
Solar/Wind Harmer
8.137
970657AG2-426 GEN
Solar/Wind Harmer
1.706
316316AC1-027 C
Solar/Wind Harmer
0.223
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.007
3145506HICKORY
Solar/Wind Harmer
0.925
3145506HICKORY
Solar/Wind Harmer
0.555
3145506HICKORY
Solar/Wind Harmer
0.139
316339AD2-160 GEN
Solar/Wind Harmer
0.374
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
316017AA1-139 ULT1
Solar/Wind Harmer
0.129
3137176SLIGO L2192
Solar/Wind Harmer
0.914
3146456SLIGO L269
Solar/Wind Harmer
4.065
3130086AYDLETT
Solar/Wind Harmer
0.917
3146386ELIZ CT
Solar/Wind Harmer
0.227
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.224
3146516WINFALL
Solar/Wind Harmer
0.224
3146516WINFALL
Solar/Wind Harmer
0.224
3146626S HERTFORD
Solar/Wind Harmer
0.223
3146626S HERTFORD
Solar/Wind Harmer
0.223
3144356SAPONY
Solar/Wind Harmer
1.861
315742AE1-103 GEN
Solar/Wind Harmer
0.003
3146376EDENTON
Solar/Wind Harmer
0.969
3146376EDENTON
Solar/Wind Harmer
0.969
958261AF2-120 GEN
Solar/Wind Harmer
7.183
972185AH1-677 GEN
Adder
12.157
972187AH1-678 GEN
Adder
6.1
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.219
3150341NORNECKC1
Adder
2.202
316468AD1-105 GEN
Solar/Wind Harmer
-0.069
970933AG2-581 GEN
Solar/Wind Harmer
16.879
316065AD1-022 GEN
Solar/Wind Harmer
9.548
3145893MURPHYS
Solar/Wind Harmer
1.376
3145893MURPHYS
Solar/Wind Harmer
0.37
3146173TUNIS
Solar/Wind Harmer
0.204
3146173TUNIS
Solar/Wind Harmer
0.204
316181AB2-040 GEN
Solar/Wind Harmer
0.288
3142666NORTHAMPTON
Solar/Wind Harmer
0.198
3142666NORTHAMPTON
Solar/Wind Harmer
0.198
3142666NORTHAMPTON
Solar/Wind Harmer
0.198
3142666NORTHAMPTON
Solar/Wind Harmer
0.119
970099AG2-077 GEN
Solar/Wind Harmer
21.134
316426AA2-053 GEN
Solar/Wind Harmer
0.666
3145593CAROLNA
Solar/Wind Harmer
0.196
3145593CAROLNA
Solar/Wind Harmer
0.196
966811AG1-552 GEN
Solar/Wind Harmer
2.127
3145593CAROLNA
Solar/Wind Harmer
0.244
3145783HORNRTN
Solar/Wind Harmer
3.466
3145783HORNRTN
Solar/Wind Harmer
2.773
3145783HORNRTN
Solar/Wind Harmer
0.866
3145783HORNRTN
Solar/Wind Harmer
0.347
3145796HORNRTN
Solar/Wind Harmer
0.584
3145933PARMELE
Solar/Wind Harmer
0.38
3145933PARMELE
Solar/Wind Harmer
0.19
316274AC1-208 GEN
Solar/Wind Harmer
0.98
971741AH1-377 GEN
Solar/Wind Harmer
18.489
970301AG2-198 GEN
Solar/Wind Harmer
7.849
939181AE1-148 GEN
Solar/Wind Harmer
8.688
3145493TOT1
Solar/Wind Harmer
0.417
3145453TOT5
Solar/Wind Harmer
0.25
3145603CNETO
Solar/Wind Harmer
0.167
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.013
970323AG2-213 GEN
Solar/Wind Harmer
7.634
971775AH1-396 GEN
Solar/Wind Harmer
0.286
958211AF2-115 GEN
Solar/Wind Harmer
2.137
963191AG1-168 GEN
Solar/Wind Harmer
0.712
3144293JTRSVLE
Adder
0.567
3144293JTRSVLE
Adder
0.477
3147133PAMPLIN
Solar/Wind Harmer
0.178
3147133PAMPLIN
Solar/Wind Harmer
0.142
961601AG1-000A GEN
Solar/Wind Harmer
3.141
316263AC1-034 GEN
Solar/Wind Harmer
6.71
962561AG1-105 GEN
Solar/Wind Harmer
8.256
964791AG1-342 GEN
Solar/Wind Harmer
3.275
3146843MT LREL
Solar/Wind Harmer
0.17
3146843MT LREL
Solar/Wind Harmer
0.17
3146776BUCKING
Solar/Wind Harmer
0.676
3146776BUCKING
Solar/Wind Harmer
0.055
971489AH1-241 GEN
Solar/Wind Harmer
8.062
316222AC1-221 GEN
Solar/Wind Harmer
0.618
315821AE2-092 GEN
Solar/Wind Harmer
0.008
942751AE2-291 GEN
Solar/Wind Harmer
6.907
966001AG1-469 GEN
Solar/Wind Harmer
0.072
3151731LOISA B
Adder
8.04
3151721LOISA A
Adder
7.998
971531AH1-263 GEN
50/50
86.379
3150411LDYSMT5
50/50
37.362
3150381LDYSMT2
50/50
35.757
972213AH1-691 GEN
50/50
6.049
972215AH1-692 GEN
50/50
6.049
963051AG1-154 GEN
50/50
4.653
972189AH1-679 GEN
Adder
4.288
316312AB1-027
Solar/Wind Harmer
0.446
316233AE1-074 FULL
Solar/Wind Harmer
0.196
971281AH1-106 GEN
Solar/Wind Harmer
3.397
971283AH1-107 GEN
Solar/Wind Harmer
3.397
971285AH1-108 GEN
Adder
1.844
315976AC1-164 GENA
Solar/Wind Harmer
25.197
316169AC1-164_GENC
Solar/Wind Harmer
21.768
315975AC1-164 GENB
Solar/Wind Harmer
0.745
316164AC1-076 GEN
Solar/Wind Harmer
0.34
316132AB2-190 GEN1
Solar/Wind Harmer
1.28
316369SG1_INVT
Solar/Wind Harmer
0.009
971167AH1-042 GEN
Solar/Wind Harmer
21.021
3142433PROV 92
Adder
0.459
3142433PROV 92
Adder
0.459
972265AH1-717 GEN
Adder
18.278
3151201GRAVEL4
Adder
17.134
3151191GRAVEL3
Adder
16.917
3151211GRAVEL5
Adder
16.917
971445AH1-216 GEN
Solar/Wind Harmer
16.508
3143316POE
Solar/Wind Harmer
0.927
3143873LANEXA
Solar/Wind Harmer
0.14
3138283WHITEMARSH
Solar/Wind Harmer
0.054
316314AB2-024 C
Solar/Wind Harmer
0.001
3151081ELIZAR1
Adder
21.327
3151091ELIZAR2
Adder
20.956
3152611GOSPORTB
Adder
2.962
3152621GOSPORTC
Adder
2.514
3152601GOSPORTA
Adder
2.319
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
6.866
315662AE1-191 GEN
Solar/Wind Harmer
0.008
315666AE1-190 GEN
Solar/Wind Harmer
0.002
957871AF2-081 GEN
Solar/Wind Harmer
11.461
3141873WAN 176
Solar/Wind Harmer
0.046
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.158
316311AC2-079 GEN
Solar/Wind Harmer
6.6
319010AE1-072 C
Solar/Wind Harmer
1.156
3146406KITTY HAWK
Solar/Wind Harmer
0.029
316305AF2-043 C
Solar/Wind Harmer
0.002
315835AF2-110_GEN
Solar/Wind Harmer
1.566
313526AB2-022
Solar/Wind Harmer
0.123
3141913WHIT STONE
Solar/Wind Harmer
0.227
3146486SUNBURY
Solar/Wind Harmer
0.227
3146486SUNBURY
Solar/Wind Harmer
0.227
3138133OCRAN
Solar/Wind Harmer
0.068
316321Z2-027
Solar/Wind Harmer
0.042
3146396TANGLEW
Solar/Wind Harmer
0.624
3145176PASQUOTANK
Solar/Wind Harmer
0.14
3141783LANCAST
Solar/Wind Harmer
0.135
3141783LANCAST
Solar/Wind Harmer
0.09
316315AB2-025 C
Solar/Wind Harmer
0.18
941031AE2-094 GEN
Solar/Wind Harmer
40.915
944011AF1-069 GEN
Solar/Wind Harmer
13.368
962981AG1-147 GEN
Solar/Wind Harmer
8.287
315814AE2-033 C
Solar/Wind Harmer
17.537
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
970327AG2-215 GEN
Solar/Wind Harmer
7.225
970673AG2-436 GEN
Solar/Wind Harmer
46.61
970673AG2-436 GEN
Solar/Wind Harmer
31.073
3130156CHOWAN
Solar/Wind Harmer
0.218
3130156CHOWAN
Solar/Wind Harmer
0.218
971967AH1-528 GEN
Solar/Wind Harmer
34.545
315816AE2-034 GEN
Solar/Wind Harmer
0.915
3141813NORNECK
Solar/Wind Harmer
0.212
3130546PLYMOUTH
Solar/Wind Harmer
0.209
315732AD1-074 GEN1
Solar/Wind Harmer
1.2
315733AD1-074 GEN2
Solar/Wind Harmer
1.2
315735AD1-075 GEN1
Solar/Wind Harmer
0.6
965291AG1-394 GEN
Solar/Wind Harmer
0.923
3146206CASHIE
Solar/Wind Harmer
0.206
970601AG2-382 GEN
Solar/Wind Harmer
7.712
970085AG2-068 GEN
Solar/Wind Harmer
10.986
970581AG2-369 GEN
Solar/Wind Harmer
9.448
3145893MURPHYS
Solar/Wind Harmer
0.555
3145893MURPHYS
Solar/Wind Harmer
0.206
3145513AHOSKIE
Solar/Wind Harmer
0.424
3145513AHOSKIE
Solar/Wind Harmer
0.203
3145683EARLEYS
Solar/Wind Harmer
0.403
3145683EARLEYS
Solar/Wind Harmer
0.202
3145683EARLEYS
Solar/Wind Harmer
0.202
3146043SEABORD
Solar/Wind Harmer
0.201
315607AA1-063A GEN
Solar/Wind Harmer
0.41
316087AB2-174 GEN
Solar/Wind Harmer
0.006
315652AC1-086 GEN
Solar/Wind Harmer
21.753
3137643SOCKMAN
Solar/Wind Harmer
0.788
3145796HORNRTN
Solar/Wind Harmer
0.623
3145796HORNRTN
Solar/Wind Harmer
0.078
3146033SCOT NK
Solar/Wind Harmer
0.774
316223AC1-118
Solar/Wind Harmer
0.139
970831AG2-522 GEN
Solar/Wind Harmer
7.995
316005AA1-067
Solar/Wind Harmer
0.2
3145746EVERETS
Solar/Wind Harmer
0.74
3145746EVERETS
Solar/Wind Harmer
0.186
3145746EVERETS
Solar/Wind Harmer
0.186
3145746EVERETS
Solar/Wind Harmer
0.186
970181AG2-120 GEN
Solar/Wind Harmer
2.314
957861AF2-080 GEN
Solar/Wind Harmer
7.879
316420AA1-050 GEN
Solar/Wind Harmer
0.006
3145573BETHELC
Solar/Wind Harmer
0.18
3145573BETHELC
Solar/Wind Harmer
0.18
316319Z2-044 C
Solar/Wind Harmer
0
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
971443AH1-215 GEN
Solar/Wind Harmer
3.007
3144303KENBRDG
Solar/Wind Harmer
0.143
970683AG2-441 GEN
Solar/Wind Harmer
11.901
970681AG2-440 GEN
Solar/Wind Harmer
9.521
946301AF1-294 GEN
Solar/Wind Harmer
3.515
961791AG1-021 GEN
Solar/Wind Harmer
1.71
315657AE1-056 GEN
Solar/Wind Harmer
6.134
970285AG2-188 GEN
Solar/Wind Harmer
13.517
944491AF1-114 GEN
Solar/Wind Harmer
0.001
971845AH1-439 GEN
Solar/Wind Harmer
7.694
316118AC1-105 GEN
Solar/Wind Harmer
0.432
972193AH1-681 GEN
Adder
3.772
3147173SINAI
Solar/Wind Harmer
0.164
3147243WELCO
Solar/Wind Harmer
0.102
972205AH1-687 GEN
Adder
6.859
971447AH1-217 GEN
Solar/Wind Harmer
4.479
970865AG2-541 GEN
Solar/Wind Harmer
5.067
316123AC1-075 GEN
Solar/Wind Harmer
0.184
970165AG2-112 GEN
Solar/Wind Harmer
1.09
970163AG2-111 GEN
Solar/Wind Harmer
1.039
270494AE1-108_GEN
Solar/Wind Harmer
1.609
3147346CASHSCORNER
Solar/Wind Harmer
0.278
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316411AF1-147_GEN1
Solar/Wind Helper
0.807
316415AF1-147_GEN2
Solar/Wind Helper
0.807
3138216PACIFIC
Solar/Wind Helper
0.039
3152261N ANNA2
50/50
14.578
970497AG2-320 GEN
50/50
26.215
3150401LDYSMT4
50/50
37.246
3150371LDYSMT1
50/50
35.99
315051AA1-145 CT1
50/50
2.03
316044AC1-158 PL1
Solar/Wind Harmer
1.523
316450AC1-158 RIC
Solar/Wind Harmer
0.406
3142416OLDCHRC
Solar/Wind Harmer
2.415
970293AG2-193 GEN
Solar/Wind Harmer
2.624
3143096IRON208
Adder
1.025
3143096IRON208
Adder
1.004
3150861SPRUNCD
Adder
1.127
316473AC1-191 GEN
Solar/Wind Harmer
0.822
3142946ENON
Solar/Wind Harmer
0.081
970133AG2-095 GEN
Solar/Wind Harmer
2.304
316382AG1-145 C
Solar/Wind Harmer
0.002
970129AG2-093 GEN
Solar/Wind Harmer
14.433
315778AD1-151 GEN
Solar/Wind Harmer
19.035
965281AG1-393 GEN
Solar/Wind Harmer
2.538
315839AE2-212 C
Solar/Wind Harmer
0.002
3150921YORKTN3
Adder
5.938
3144216WINCHST
Adder
0.891
3142433PROV 92
Adder
0.459
3142433PROV 92
Adder
0.459
961611AG1-000B GEN
Solar/Wind Harmer
6.298
315773AC2-141 GEN
Solar/Wind Harmer
8.598
3151221GRAVEL6
Adder
17.114
3151171GRAVELC
Adder
3.293
3145336SMITFLD
Solar/Wind Harmer
0.094
315813AE1-149 C
Solar/Wind Harmer
12.5
3144536CHRHLND
Solar/Wind Harmer
0.035
970659AG2-427 GEN
Solar/Wind Harmer
2.464
944581AF1-123 GEN
Solar/Wind Harmer
52.379
944601AF1-125 GEN
Solar/Wind Harmer
51.572
3151101ELIZAR3
Adder
21.599
316083AB2-161 GEN
Solar/Wind Harmer
0.003
3144873MCLAUGH
Solar/Wind Harmer
0.006
3141766HARMONY
Solar/Wind Harmer
3.092
970661AG2-428 GEN
Solar/Wind Harmer
4.905
3141843SHACKLE
Adder
1.184
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316280AD1-041 GEN
Solar/Wind Harmer
0.005
316156AD2-030 GEN
Solar/Wind Harmer
0.17
3141873WAN 176
Solar/Wind Harmer
4.089
3146456SLIGO L269
Solar/Wind Harmer
0.23
971153AH1-033 GEN
Solar/Wind Harmer
2.655
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.224
3146626S HERTFORD
Solar/Wind Harmer
0.223
3145273HOLLAND
Solar/Wind Harmer
0.166
962971AG1-146 GEN
Solar/Wind Harmer
3.551
970009AG2-005 GEN
Solar/Wind Harmer
1.644
3146376EDENTON
Solar/Wind Harmer
0.218
316404AE1-155 C
Solar/Wind Harmer
0.049
315614AA2-178 GEN
Solar/Wind Harmer
1.22
3150351NORNECKC2
Adder
2.148
971781AH1-399 GEN
Solar/Wind Harmer
0.278
316313AB2-026
Solar/Wind Harmer
0.133
316258AE1-075 C
Solar/Wind Harmer
0.159
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
3.185
971157AH1-035 GEN
Solar/Wind Harmer
2.514
315737AD1-076 GEN
Solar/Wind Harmer
2.686
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
970917AG2-570 GEN
Solar/Wind Harmer
18.383
3146206CASHIE
Solar/Wind Harmer
0.206
316365GEN2_N
Solar/Wind Harmer
0.463
3145893MURPHYS
Solar/Wind Harmer
0.344
3145893MURPHYS
Solar/Wind Harmer
0.206
957521AF2-046 GEN
Solar/Wind Harmer
15.264
961681AG1-008 GEN
Solar/Wind Harmer
15.264
3146173TUNIS
Solar/Wind Harmer
0.204
3156021HOLLOMANSOL
Solar/Wind Harmer
0.924
316463AE2-346 GEN
Solar/Wind Harmer
0.174
316140AB2-099
Solar/Wind Harmer
0.072
962331AG1-082 GEN
Solar/Wind Harmer
2.163
3147666LOUISA
Solar/Wind Harmer
0.462
3146263WOODLND
Solar/Wind Harmer
0.2
3145963POPLR C
Solar/Wind Harmer
0.199
313506AB2-031 GEN
Solar/Wind Harmer
0.614
3142666NORTHAMPTON
Solar/Wind Harmer
0.198
316317KELFORD C
Solar/Wind Harmer
0.019
3145823KELFORD
Solar/Wind Harmer
0.198
3145796HORNRTN
Solar/Wind Harmer
0.778
3145796HORNRTN
Solar/Wind Harmer
0.195
3147043LAWRENC
Solar/Wind Harmer
0.117
3141906WESTMOR
Solar/Wind Harmer
0.077
316478AD1-087 GEN
Solar/Wind Harmer
0.667
316486AD2-202 GEN
Solar/Wind Harmer
0.196
316210AC1-098 GEN
Solar/Wind Harmer
1.765
3145933PARMELE
Solar/Wind Harmer
0.19
966801AG1-551 GEN
Solar/Wind Harmer
2.213
3145746EVERETS
Solar/Wind Harmer
0.186
3145746EVERETS
Solar/Wind Harmer
0.186
315724AD1-057 GEN
Solar/Wind Harmer
0.693
970737AG2-469 GEN
Solar/Wind Harmer
7.863
970909AG2-566 GEN
Solar/Wind Harmer
1.962
316327AA2-057 GEN
Solar/Wind Harmer
0.277
3146073TAR RVR
Solar/Wind Harmer
0.18
3146083TARBORO
Solar/Wind Harmer
0.18
3146233WITAKRS
Solar/Wind Harmer
0.903
3146233WITAKRS
Solar/Wind Harmer
0.122
316131AB2-060 GEN
Solar/Wind Harmer
0.565
3138543CONSLDL
Solar/Wind Harmer
0.118
964241AG1-285 GEN
Solar/Wind Harmer
11.97
315785AD2-033 C
Solar/Wind Harmer
1.456
970257AG2-171 GEN
Solar/Wind Harmer
5.726
959311AF2-222 GEN
Solar/Wind Harmer
15.895
963181AG1-167 GEN
Solar/Wind Harmer
0.712
3144293JTRSVLE
Adder
0.567
3147133PAMPLIN
Solar/Wind Harmer
0.558
971193AH1-056 GEN
Solar/Wind Harmer
10.829
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
961601AG1-000A GEN
Solar/Wind Harmer
12.564
3145543BTLEBRO
Solar/Wind Harmer
0.176
3145543BTLEBRO
Solar/Wind Harmer
0.176
971623AH1-311 GEN
Solar/Wind Harmer
0.353
3146926FARMVIL
Solar/Wind Harmer
0.106
3146776BUCKING
Solar/Wind Harmer
0.061
972255AH1-712 GEN
Adder
84.412
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
6.993
971683AH1-343 GEN
Solar/Wind Harmer
5.591
970221AG2-151 GEN
Solar/Wind Harmer
8.062
316283AC2-100 C
Solar/Wind Harmer
0.29
3132273ORANGE
Solar/Wind Harmer
0.028
3141316ARNOLDS
Adder
0.324
3150331BIRCHWDA
Adder
21.287
3151761LOISA E
Adder
16.391
316170AC1-121 GEN2
Solar/Wind Harmer
0.131
972183AH1-676 GEN
Adder
128.276
3141196NOKESVL
Solar/Wind Helper
1.252
971507AH1-251 GEN
50/50
17.73
3152251N ANNA1
50/50
14.579
972197AH1-683 GEN
50/50
5.816
972219AH1-694 GEN
50/50
4.188
315052AA1-145 CT2
50/50
2.039
316045AC1-158 PL2
Solar/Wind Harmer
4.87
966881AG1-559 GEN
Solar/Wind Harmer
0.299
3142416OLDCHRC
Solar/Wind Harmer
0.648
3142416OLDCHRC
Solar/Wind Harmer
0.248
3143526WINTERP
Solar/Wind Harmer
1.273
3143096IRON208
Adder
1.025
3150851SPRUNCC
Adder
1.127
3143226MDLTHAN
Solar/Wind Harmer
0.244
3142543TWELFTH
Solar/Wind Harmer
0.023
944631AF1-128 GEN
Adder
115.654
316159AE1-175 C
Solar/Wind Harmer
0.206
970129AG2-093 GEN
Solar/Wind Harmer
6.792
316458AB2-190 GEN2
Solar/Wind Harmer
1.28
315671AE2-027_GEN
Solar/Wind Harmer
15.26
971069AG2-661 GEN
Solar/Wind Harmer
4.23
971647AH1-324 GEN
Solar/Wind Harmer
10.104
971317AH1-138 GEN
Solar/Wind Harmer
1.765
3138126ROCKLANDING
Solar/Wind Harmer
0.108
3142433PROV 92
Solar/Wind Harmer
0.944
3142433PROV 92
Adder
0.459
3142433PROV 92
Adder
0.459
961611AG1-000B GEN
Solar/Wind Harmer
12.386
316294AC1-161 GEN
Solar/Wind Harmer
4.079
3151171GRAVELC
Adder
2.504
3145336SMITFLD
Solar/Wind Harmer
0.937
970659AG2-427 GEN
Solar/Wind Harmer
11.263
944591AF1-124 GEN
Solar/Wind Harmer
52.565
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
2.904
316381AD1-082 GEN
Solar/Wind Harmer
0.242
3141766HARMONY
Solar/Wind Harmer
0.046
970661AG2-428 GEN
Solar/Wind Harmer
23.062
971777AH1-397 GEN
Solar/Wind Harmer
0.612
3141843SHACKLE
Adder
1.184
316072AD1-144
Solar/Wind Harmer
0.084
939411AE1-173 GEN
Solar/Wind Harmer
98.509
940641AE2-051 GEN
Solar/Wind Harmer
18.448
316388AE2-253 GEN
Solar/Wind Harmer
0.722
3146456SLIGO L269
Solar/Wind Harmer
0.23
316246AF1-032 C
Solar/Wind Harmer
0.103
316093AE2-104_GEN
Solar/Wind Harmer
3.838
3138133OCRAN
Solar/Wind Harmer
0.136
3146516WINFALL
Solar/Wind Harmer
0.727
3146516WINFALL
Solar/Wind Harmer
0.224
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.218
962861AG1-135 GEN
Solar/Wind Harmer
6.976
3141726DUNNSVL
Solar/Wind Harmer
0.859
3145663CRESWEL
Solar/Wind Harmer
0.597
971163AH1-040 GEN
Solar/Wind Harmer
17.057
3150351NORNECKC2
Adder
2.113
3143336POWHATN
Solar/Wind Harmer
3.747
970919AG2-571 GEN
Solar/Wind Harmer
7.353
3146206CASHIE
Solar/Wind Harmer
0.206
971547AH1-271 GEN
Solar/Wind Harmer
4.407
316023GEN1_S
Solar/Wind Harmer
0.463
970087AG2-069 GEN
Solar/Wind Harmer
16.479
3145893MURPHYS
Solar/Wind Harmer
0.822
3145893MURPHYS
Solar/Wind Harmer
0.914
3146173TUNIS
Solar/Wind Harmer
0.204
316337AD2-073 GEN
Solar/Wind Harmer
0.177
316336AC2-165 C
Solar/Wind Harmer
0.008
3145683EARLEYS
Solar/Wind Harmer
0.202
3147666LOUISA
Solar/Wind Harmer
0.804
960081AF2-299 GEN
Solar/Wind Harmer
1.928
3146263WOODLND
Solar/Wind Harmer
0.2
3145963POPLR C
Solar/Wind Harmer
0.199
957481AF2-042 GEN
Solar/Wind Harmer
52.836
316011AB1-132 GEN
Solar/Wind Harmer
3.595
962571AG1-106 GEN
Solar/Wind Harmer
2.814
3145823KELFORD
Solar/Wind Harmer
0.198
316190AA2-174 GEN
Solar/Wind Harmer
0
316174AB2-169 GEN
Solar/Wind Harmer
0.005
316192AB2-158 GEN
Solar/Wind Harmer
1.112
971795AH1-408 GEN
Solar/Wind Harmer
13.096
3145783HORNRTN
Solar/Wind Harmer
0.195
3145796HORNRTN
Solar/Wind Harmer
0.642
3145796HORNRTN
Solar/Wind Harmer
0.195
315693AD1-088 GEN
Solar/Wind Harmer
9.336
3147043LAWRENC
Adder
1.759
962491AG1-098 GEN
Solar/Wind Harmer
11.068
316212AC1-099_GEN
Solar/Wind Harmer
0.984
3146293MARTNCO
Solar/Wind Harmer
0.176
316129AC1-054 GEN
Solar/Wind Harmer
0.701
3145746EVERETS
Solar/Wind Harmer
0.186
3145746EVERETS
Solar/Wind Harmer
0.186
971065AG2-659 GEN
Solar/Wind Harmer
7.918
315722AD1-056 GEN
Solar/Wind Harmer
1.169
316494AC1-189 GEN
Solar/Wind Harmer
0.617
315687AD1-152 GEN
Solar/Wind Harmer
0.006
961671AG1-007 GEN
Solar/Wind Harmer
0.028
3146083TARBORO
Solar/Wind Harmer
0.18
3145493TOT1
Solar/Wind Harmer
0.8
3146233WITAKRS
Solar/Wind Harmer
0.716
970937AG2-583 GEN
Solar/Wind Harmer
11.013
316237AB2-079_GEN
Solar/Wind Harmer
0.001
970685AG2-442 GEN
Solar/Wind Harmer
13.329
972135AH1-637 GEN
Solar/Wind Harmer
1.522
963171AG1-166 GEN
Solar/Wind Harmer
0.95
971563AH1-280 GEN
Solar/Wind Harmer
1.9
3144293JTRSVLE
Adder
0.567
3145543BTLEBRO
Solar/Wind Harmer
0.176
3145543BTLEBRO
Solar/Wind Harmer
0.141
316359AB2-059 GEN
Solar/Wind Harmer
0.634
316049AB1-081 GEN
Solar/Wind Harmer
1.011
3142053HEARTS
Solar/Wind Harmer
0.311
3146926FARMVIL
Solar/Wind Harmer
0.106
970401AG2-262 GEN
Solar/Wind Harmer
1.001
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.068
972277AH1-723 GEN
Adder
98.366
972003AH1-546 GEN
Solar/Wind Harmer
6.888
316003AC1-222 GEN
Solar/Wind Harmer
0.004
971377AH1-170 GEN
Solar/Wind Harmer
1.612
3147623JAMES R
Solar/Wind Harmer
0.35
3151751LOISA D
Adder
8.04
316254AC1-120 GEN1
Solar/Wind Harmer
0.262
NYPJM->LTFIMP_NY
CLTF
3.261
LGEELTFEXP_LGEE->PJM
CLTF
1.336
WECLTFEXP_WEC->PJM
CLTF
0.644
LAGNLTFEXP_LAGN->PJM
CLTF
8.029
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.001
TVALTFEXP_TVA->PJM
CLTF
4.071
CBM West 1LTFEXP_CBM-W1->PJM
CBM
21.423
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.85
MECLTFEXP_MEC->PJM
CLTF
3.626
SIGELTFEXP_SIGE->PJM
CLTF
0.111
CPLELTFEXP_CPLE->PJM
CLTF
11.392
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.447

Details for 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 573_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:123.02 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5007.08
MW Contribution:96.94
Bus #Bus NameTypeMW Contribution
971531AH1-263 GEN
50/50
73.177
3150411LDYSMT5
50/50
36.98
3150381LDYSMT2
50/50
35.391
972213AH1-691 GEN
50/50
5.987
972215AH1-692 GEN
50/50
5.987
963051AG1-154 GEN
50/50
4.605
972189AH1-679 GEN
Adder
4.237
316312AB1-027
Solar/Wind Harmer
0.44
316233AE1-074 FULL
Solar/Wind Harmer
0.193
971281AH1-106 GEN
Solar/Wind Harmer
3.35
971283AH1-107 GEN
Solar/Wind Harmer
3.35
971285AH1-108 GEN
Adder
1.819
315976AC1-164 GENA
Solar/Wind Harmer
24.88
316169AC1-164_GENC
Solar/Wind Harmer
21.494
315975AC1-164 GENB
Solar/Wind Harmer
0.736
316132AB2-190 GEN1
Solar/Wind Harmer
1.264
316369SG1_INVT
Solar/Wind Harmer
0.009
971167AH1-042 GEN
Solar/Wind Harmer
20.755
3142433PROV 92
Adder
0.453
3142433PROV 92
Adder
0.453
972265AH1-717 GEN
Adder
18.039
3151201GRAVEL4
Adder
16.911
3151191GRAVEL3
Adder
16.697
3151211GRAVEL5
Adder
16.697
971445AH1-216 GEN
Solar/Wind Harmer
16.292
3143316POE
Solar/Wind Harmer
0.915
3143873LANEXA
Solar/Wind Harmer
0.139
3138283WHITEMARSH
Solar/Wind Harmer
0.053
316314AB2-024 C
Solar/Wind Harmer
0.001
3151081ELIZAR1
Adder
21.046
3151091ELIZAR2
Adder
20.681
3152611GOSPORTB
Adder
2.923
3152621GOSPORTC
Adder
2.481
3152601GOSPORTA
Adder
2.288
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
6.781
315662AE1-191 GEN
Solar/Wind Harmer
0.008
315666AE1-190 GEN
Solar/Wind Harmer
0.002
957871AF2-081 GEN
Solar/Wind Harmer
11.31
3141873WAN 176
Solar/Wind Harmer
0.045
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.155
316311AC2-079 GEN
Solar/Wind Harmer
6.513
319010AE1-072 C
Solar/Wind Harmer
1.141
3146406KITTY HAWK
Solar/Wind Harmer
0.028
316305AF2-043 C
Solar/Wind Harmer
0.002
315835AF2-110_GEN
Solar/Wind Harmer
1.545
3141913WHIT STONE
Solar/Wind Harmer
0.224
313526AB2-022
Solar/Wind Harmer
0.121
3138133OCRAN
Solar/Wind Harmer
0.067
3146486SUNBURY
Solar/Wind Harmer
0.224
3146486SUNBURY
Solar/Wind Harmer
0.224
316321Z2-027
Solar/Wind Harmer
0.041
3146396TANGLEW
Solar/Wind Harmer
0.616
3145176PASQUOTANK
Solar/Wind Harmer
0.138
3141783LANCAST
Solar/Wind Harmer
0.133
3141783LANCAST
Solar/Wind Harmer
0.089
316315AB2-025 C
Solar/Wind Harmer
0.177
962981AG1-147 GEN
Solar/Wind Harmer
8.186
941031AE2-094 GEN
Solar/Wind Harmer
40.356
944011AF1-069 GEN
Solar/Wind Harmer
13.186
315814AE2-033 C
Solar/Wind Harmer
17.302
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
970327AG2-215 GEN
Solar/Wind Harmer
7.138
970673AG2-436 GEN
Solar/Wind Harmer
45.972
970673AG2-436 GEN
Solar/Wind Harmer
30.648
3130156CHOWAN
Solar/Wind Harmer
0.215
3130156CHOWAN
Solar/Wind Harmer
0.215
971967AH1-528 GEN
Solar/Wind Harmer
34.067
3150391LDYSMT3
50/50
36.796
972195AH1-682 GEN
50/50
4.835
315673AE1-157 GEN
Solar/Wind Harmer
17.789
957411AF2-035 GEN
Solar/Wind Harmer
10.93
970317AG2-208 GEN
Solar/Wind Harmer
10.126
3142296MT RD221
Adder
0.793
3142366NRTHEST
Adder
0.798
3150691DARBY 3
Adder
17.545
3150701DARBY 4
Adder
17.505
3150681DARBY 2
Adder
17.484
3150671DARBY 1
Adder
17.464
316075AC2-137 C
Solar/Wind Harmer
0.066
3143526WINTERP
Solar/Wind Harmer
1.255
971223AH1-071 GEN
Solar/Wind Harmer
2.567
966871AG1-558 GEN
Solar/Wind Harmer
0.278
3142946ENON
Solar/Wind Harmer
0.024
944641AF1-129 GEN
Adder
113.139
316240AF1-291 C
Solar/Wind Harmer
0.002
316033AB2-134 GEN
Solar/Wind Harmer
0.014
315697AD1-025 GEN
Solar/Wind Harmer
0.263
316236AE1-162_GEN
Solar/Wind Harmer
0.002
316036AC1-147 C
Solar/Wind Harmer
0.043
3150991CHESPKB
Adder
2.404
3150991CHESPKB
Adder
2.347
970657AG2-426 GEN
Solar/Wind Harmer
8.03
970657AG2-426 GEN
Solar/Wind Harmer
1.684
316316AC1-027 C
Solar/Wind Harmer
0.22
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.007
3145506HICKORY
Solar/Wind Harmer
0.912
3145506HICKORY
Solar/Wind Harmer
0.547
3145506HICKORY
Solar/Wind Harmer
0.137
316339AD2-160 GEN
Solar/Wind Harmer
0.369
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
316017AA1-139 ULT1
Solar/Wind Harmer
0.127
3137176SLIGO L2192
Solar/Wind Harmer
0.902
3146456SLIGO L269
Solar/Wind Harmer
4.012
3130086AYDLETT
Solar/Wind Harmer
0.905
3146386ELIZ CT
Solar/Wind Harmer
0.224
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.221
3146516WINFALL
Solar/Wind Harmer
0.221
3146516WINFALL
Solar/Wind Harmer
0.221
3146626S HERTFORD
Solar/Wind Harmer
0.22
3146626S HERTFORD
Solar/Wind Harmer
0.22
3144356SAPONY
Solar/Wind Harmer
1.836
315742AE1-103 GEN
Solar/Wind Harmer
0.003
3146376EDENTON
Solar/Wind Harmer
0.957
3146376EDENTON
Solar/Wind Harmer
0.957
958261AF2-120 GEN
Solar/Wind Harmer
7.097
972185AH1-677 GEN
Adder
11.991
972187AH1-678 GEN
Adder
6.016
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.193
3150341NORNECKC1
Adder
2.176
316468AD1-105 GEN
Solar/Wind Harmer
-0.068
970933AG2-581 GEN
Solar/Wind Harmer
16.641
316065AD1-022 GEN
Solar/Wind Harmer
9.423
3145893MURPHYS
Solar/Wind Harmer
1.358
3145893MURPHYS
Solar/Wind Harmer
0.365
3146173TUNIS
Solar/Wind Harmer
0.201
3146173TUNIS
Solar/Wind Harmer
0.201
316181AB2-040 GEN
Solar/Wind Harmer
0.284
3142666NORTHAMPTON
Solar/Wind Harmer
0.196
3142666NORTHAMPTON
Solar/Wind Harmer
0.196
3142666NORTHAMPTON
Solar/Wind Harmer
0.196
3142666NORTHAMPTON
Solar/Wind Harmer
0.117
970099AG2-077 GEN
Solar/Wind Harmer
20.826
316426AA2-053 GEN
Solar/Wind Harmer
0.657
3145593CAROLNA
Solar/Wind Harmer
0.193
315816AE2-034 GEN
Solar/Wind Harmer
0.903
3141813NORNECK
Solar/Wind Harmer
0.209
3130546PLYMOUTH
Solar/Wind Harmer
0.207
315732AD1-074 GEN1
Solar/Wind Harmer
1.184
315733AD1-074 GEN2
Solar/Wind Harmer
1.184
315735AD1-075 GEN1
Solar/Wind Harmer
0.593
965291AG1-394 GEN
Solar/Wind Harmer
0.91
3146206CASHIE
Solar/Wind Harmer
0.204
970601AG2-382 GEN
Solar/Wind Harmer
7.61
970085AG2-068 GEN
Solar/Wind Harmer
10.836
970581AG2-369 GEN
Solar/Wind Harmer
9.319
3145893MURPHYS
Solar/Wind Harmer
0.548
3145893MURPHYS
Solar/Wind Harmer
0.203
3145513AHOSKIE
Solar/Wind Harmer
0.418
3145513AHOSKIE
Solar/Wind Harmer
0.2
3145683EARLEYS
Solar/Wind Harmer
0.398
3145683EARLEYS
Solar/Wind Harmer
0.199
3145683EARLEYS
Solar/Wind Harmer
0.199
3146043SEABORD
Solar/Wind Harmer
0.198
315607AA1-063A GEN
Solar/Wind Harmer
0.404
316087AB2-174 GEN
Solar/Wind Harmer
0.006
315652AC1-086 GEN
Solar/Wind Harmer
21.462
3137643SOCKMAN
Solar/Wind Harmer
0.777
3145796HORNRTN
Solar/Wind Harmer
0.615
3145796HORNRTN
Solar/Wind Harmer
0.077
3146033SCOT NK
Solar/Wind Harmer
0.764
316223AC1-118
Solar/Wind Harmer
0.137
970831AG2-522 GEN
Solar/Wind Harmer
7.881
316005AA1-067
Solar/Wind Harmer
0.197
3145746EVERETS
Solar/Wind Harmer
0.73
3145746EVERETS
Solar/Wind Harmer
0.183
3145746EVERETS
Solar/Wind Harmer
0.183
3145746EVERETS
Solar/Wind Harmer
0.183
970181AG2-120 GEN
Solar/Wind Harmer
2.284
957861AF2-080 GEN
Solar/Wind Harmer
7.776
316420AA1-050 GEN
Solar/Wind Harmer
0.006
3145573BETHELC
Solar/Wind Harmer
0.178
3145573BETHELC
Solar/Wind Harmer
0.178
316319Z2-044 C
Solar/Wind Harmer
0
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
971443AH1-215 GEN
Solar/Wind Harmer
2.956
3144303KENBRDG
Solar/Wind Harmer
0.141
970683AG2-441 GEN
Solar/Wind Harmer
11.694
970681AG2-440 GEN
Solar/Wind Harmer
9.355
946301AF1-294 GEN
Solar/Wind Harmer
3.451
961791AG1-021 GEN
Solar/Wind Harmer
1.679
315657AE1-056 GEN
Solar/Wind Harmer
6.021
944491AF1-114 GEN
Solar/Wind Harmer
0.001
970285AG2-188 GEN
Solar/Wind Harmer
13.206
971845AH1-439 GEN
Solar/Wind Harmer
7.514
316118AC1-105 GEN
Solar/Wind Harmer
0.425
972193AH1-681 GEN
Adder
3.717
3147173SINAI
Solar/Wind Harmer
0.161
3147243WELCO
Solar/Wind Harmer
0.101
972205AH1-687 GEN
Adder
6.67
970865AG2-541 GEN
Solar/Wind Harmer
4.995
971447AH1-217 GEN
Solar/Wind Harmer
4.355
316123AC1-075 GEN
Solar/Wind Harmer
0.181
970165AG2-112 GEN
Solar/Wind Harmer
1.074
970163AG2-111 GEN
Solar/Wind Harmer
1.025
270494AE1-108_GEN
Solar/Wind Harmer
1.568
316411AF1-147_GEN1
Solar/Wind Helper
0.784
316415AF1-147_GEN2
Solar/Wind Helper
0.784
3138216PACIFIC
Solar/Wind Helper
0.038
3152261N ANNA2
50/50
14.366
970497AG2-320 GEN
50/50
25.942
3150401LDYSMT4
50/50
36.865
3150371LDYSMT1
50/50
35.621
315051AA1-145 CT1
50/50
2.006
3142416OLDCHRC
Solar/Wind Harmer
2.384
970293AG2-193 GEN
Solar/Wind Harmer
2.591
3143096IRON208
Adder
1.011
3143096IRON208
Adder
0.991
3150861SPRUNCD
Adder
1.112
316473AC1-191 GEN
Solar/Wind Harmer
0.812
3142946ENON
Solar/Wind Harmer
0.08
970133AG2-095 GEN
Solar/Wind Harmer
2.274
316382AG1-145 C
Solar/Wind Harmer
0.002
970129AG2-093 GEN
Solar/Wind Harmer
14.245
315778AD1-151 GEN
Solar/Wind Harmer
18.787
965281AG1-393 GEN
Solar/Wind Harmer
2.505
315839AE2-212 C
Solar/Wind Harmer
0.002
3150921YORKTN3
Adder
5.862
3144216WINCHST
Adder
0.879
3142433PROV 92
Adder
0.453
3142433PROV 92
Adder
0.453
961611AG1-000B GEN
Solar/Wind Harmer
6.216
315773AC2-141 GEN
Solar/Wind Harmer
8.485
3151221GRAVEL6
Adder
16.891
3151171GRAVELC
Adder
3.25
3145336SMITFLD
Solar/Wind Harmer
0.093
315813AE1-149 C
Solar/Wind Harmer
12.335
3144536CHRHLND
Solar/Wind Harmer
0.034
970659AG2-427 GEN
Solar/Wind Harmer
2.431
944581AF1-123 GEN
Solar/Wind Harmer
51.69
944601AF1-125 GEN
Solar/Wind Harmer
50.894
3151101ELIZAR3
Adder
21.316
316083AB2-161 GEN
Solar/Wind Harmer
0.003
3144873MCLAUGH
Solar/Wind Harmer
0.006
3141766HARMONY
Solar/Wind Harmer
3.053
3141843SHACKLE
Adder
1.169
970661AG2-428 GEN
Solar/Wind Harmer
4.841
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316280AD1-041 GEN
Solar/Wind Harmer
0.005
316156AD2-030 GEN
Solar/Wind Harmer
0.168
3141873WAN 176
Solar/Wind Harmer
4.038
3146456SLIGO L269
Solar/Wind Harmer
0.227
971153AH1-033 GEN
Solar/Wind Harmer
2.621
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.221
3146626S HERTFORD
Solar/Wind Harmer
0.22
962971AG1-146 GEN
Solar/Wind Harmer
3.508
3145273HOLLAND
Solar/Wind Harmer
0.164
970009AG2-005 GEN
Solar/Wind Harmer
1.624
3146376EDENTON
Solar/Wind Harmer
0.215
316404AE1-155 C
Solar/Wind Harmer
0.048
315614AA2-178 GEN
Solar/Wind Harmer
1.204
3150351NORNECKC2
Adder
2.123
971781AH1-399 GEN
Solar/Wind Harmer
0.275
316313AB2-026
Solar/Wind Harmer
0.13
316258AE1-075 C
Solar/Wind Harmer
0.156
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
3.126
971157AH1-035 GEN
Solar/Wind Harmer
2.481
315737AD1-076 GEN
Solar/Wind Harmer
2.651
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
970917AG2-570 GEN
Solar/Wind Harmer
18.132
3146206CASHIE
Solar/Wind Harmer
0.204
316365GEN2_N
Solar/Wind Harmer
0.456
3145893MURPHYS
Solar/Wind Harmer
0.34
3145893MURPHYS
Solar/Wind Harmer
0.203
957521AF2-046 GEN
Solar/Wind Harmer
15.061
961681AG1-008 GEN
Solar/Wind Harmer
15.061
3146173TUNIS
Solar/Wind Harmer
0.201
3156021HOLLOMANSOL
Solar/Wind Harmer
0.911
316463AE2-346 GEN
Solar/Wind Harmer
0.172
316140AB2-099
Solar/Wind Harmer
0.071
962331AG1-082 GEN
Solar/Wind Harmer
2.134
3146263WOODLND
Solar/Wind Harmer
0.197
3145963POPLR C
Solar/Wind Harmer
0.196
313506AB2-031 GEN
Solar/Wind Harmer
0.605
3142666NORTHAMPTON
Solar/Wind Harmer
0.196
316317KELFORD C
Solar/Wind Harmer
0.019
3145823KELFORD
Solar/Wind Harmer
0.195
3145796HORNRTN
Solar/Wind Harmer
0.768
3145796HORNRTN
Solar/Wind Harmer
0.192
3147043LAWRENC
Solar/Wind Harmer
0.115
3141906WESTMOR
Solar/Wind Harmer
0.076
3147666LOUISA
Solar/Wind Harmer
0.435
316478AD1-087 GEN
Solar/Wind Harmer
0.657
316486AD2-202 GEN
Solar/Wind Harmer
0.193
316210AC1-098 GEN
Solar/Wind Harmer
1.741
3145933PARMELE
Solar/Wind Harmer
0.187
966801AG1-551 GEN
Solar/Wind Harmer
2.184
3145746EVERETS
Solar/Wind Harmer
0.183
3145746EVERETS
Solar/Wind Harmer
0.183
970737AG2-469 GEN
Solar/Wind Harmer
7.78
315724AD1-057 GEN
Solar/Wind Harmer
0.684
316327AA2-057 GEN
Solar/Wind Harmer
0.273
970909AG2-566 GEN
Solar/Wind Harmer
1.926
3146073TAR RVR
Solar/Wind Harmer
0.178
3146083TARBORO
Solar/Wind Harmer
0.178
3146233WITAKRS
Solar/Wind Harmer
0.891
3146233WITAKRS
Solar/Wind Harmer
0.121
3138543CONSLDL
Solar/Wind Harmer
0.117
316131AB2-060 GEN
Solar/Wind Harmer
0.557
964241AG1-285 GEN
Solar/Wind Harmer
11.779
315785AD2-033 C
Solar/Wind Harmer
1.432
970257AG2-171 GEN
Solar/Wind Harmer
5.629
959311AF2-222 GEN
Solar/Wind Harmer
15.624
963181AG1-167 GEN
Solar/Wind Harmer
0.7
3144293JTRSVLE
Adder
0.557
3147133PAMPLIN
Solar/Wind Harmer
0.548
971193AH1-056 GEN
Solar/Wind Harmer
10.629
961601AG1-000A GEN
Solar/Wind Harmer
12.399
3145543BTLEBRO
Solar/Wind Harmer
0.174
3145543BTLEBRO
Solar/Wind Harmer
0.174
971623AH1-311 GEN
Solar/Wind Harmer
0.349
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.104
3146776BUCKING
Solar/Wind Harmer
0.059
972255AH1-712 GEN
Adder
83.19
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
6.893
971683AH1-343 GEN
Solar/Wind Harmer
5.511
970221AG2-151 GEN
Solar/Wind Harmer
7.84
316283AC2-100 C
Solar/Wind Harmer
0.286
3141316ARNOLDS
Adder
0.322
3150331BIRCHWDA
Adder
21.148
316044AC1-158 PL1
Solar/Wind Helper
1.891
316450AC1-158 RIC
Solar/Wind Helper
0.504
3141196NOKESVL
Solar/Wind Helper
1.226
3152251N ANNA1
50/50
14.367
972197AH1-683 GEN
50/50
5.757
972219AH1-694 GEN
50/50
4.145
315052AA1-145 CT2
50/50
2.014
966881AG1-559 GEN
Solar/Wind Harmer
0.296
3142416OLDCHRC
Solar/Wind Harmer
0.639
3142416OLDCHRC
Solar/Wind Harmer
0.245
3143526WINTERP
Solar/Wind Harmer
1.255
3143096IRON208
Adder
1.011
3150851SPRUNCC
Adder
1.112
3142543TWELFTH
Solar/Wind Harmer
0.023
3143226MDLTHAN
Solar/Wind Harmer
0.24
944631AF1-128 GEN
Adder
114.169
316159AE1-175 C
Solar/Wind Harmer
0.204
970129AG2-093 GEN
Solar/Wind Harmer
6.704
316458AB2-190 GEN2
Solar/Wind Harmer
1.264
315671AE2-027_GEN
Solar/Wind Harmer
15.06
971069AG2-661 GEN
Solar/Wind Harmer
4.175
971647AH1-324 GEN
Solar/Wind Harmer
9.972
971317AH1-138 GEN
Solar/Wind Harmer
1.742
3138126ROCKLANDING
Solar/Wind Harmer
0.107
3142433PROV 92
Solar/Wind Harmer
0.932
3142433PROV 92
Adder
0.453
3142433PROV 92
Adder
0.453
961611AG1-000B GEN
Solar/Wind Harmer
12.225
316294AC1-161 GEN
Solar/Wind Harmer
4.025
3151171GRAVELC
Adder
2.471
3145336SMITFLD
Solar/Wind Harmer
0.925
970659AG2-427 GEN
Solar/Wind Harmer
11.115
944591AF1-124 GEN
Solar/Wind Harmer
51.874
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
2.866
316381AD1-082 GEN
Solar/Wind Harmer
0.239
3141766HARMONY
Solar/Wind Harmer
0.046
971777AH1-397 GEN
Solar/Wind Harmer
0.604
3141843SHACKLE
Adder
1.169
970661AG2-428 GEN
Solar/Wind Harmer
22.759
316072AD1-144
Solar/Wind Harmer
0.082
939411AE1-173 GEN
Solar/Wind Harmer
97.185
940641AE2-051 GEN
Solar/Wind Harmer
18.198
316388AE2-253 GEN
Solar/Wind Harmer
0.712
3146456SLIGO L269
Solar/Wind Harmer
0.227
316246AF1-032 C
Solar/Wind Harmer
0.102
316093AE2-104_GEN
Solar/Wind Harmer
3.787
3138133OCRAN
Solar/Wind Harmer
0.134
3146516WINFALL
Solar/Wind Harmer
0.717
3146516WINFALL
Solar/Wind Harmer
0.221
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
962861AG1-135 GEN
Solar/Wind Harmer
6.892
3130156CHOWAN
Solar/Wind Harmer
0.215
3141726DUNNSVL
Solar/Wind Harmer
0.848
3145663CRESWEL
Solar/Wind Harmer
0.589
971163AH1-040 GEN
Solar/Wind Harmer
16.833
3150351NORNECKC2
Adder
2.088
3143336POWHATN
Solar/Wind Harmer
3.678
970919AG2-571 GEN
Solar/Wind Harmer
7.253
3146206CASHIE
Solar/Wind Harmer
0.204
971547AH1-271 GEN
Solar/Wind Harmer
4.349
316023GEN1_S
Solar/Wind Harmer
0.456
970087AG2-069 GEN
Solar/Wind Harmer
16.254
3145893MURPHYS
Solar/Wind Harmer
0.811
3145893MURPHYS
Solar/Wind Harmer
0.902
3146173TUNIS
Solar/Wind Harmer
0.201
316337AD2-073 GEN
Solar/Wind Harmer
0.175
3145683EARLEYS
Solar/Wind Harmer
0.199
316336AC2-165 C
Solar/Wind Harmer
0.008
960081AF2-299 GEN
Solar/Wind Harmer
1.901
3146263WOODLND
Solar/Wind Harmer
0.197
3145963POPLR C
Solar/Wind Harmer
0.196
957481AF2-042 GEN
Solar/Wind Harmer
52.064
316011AB1-132 GEN
Solar/Wind Harmer
3.547
962571AG1-106 GEN
Solar/Wind Harmer
2.776
3145823KELFORD
Solar/Wind Harmer
0.195
316190AA2-174 GEN
Solar/Wind Harmer
0
316174AB2-169 GEN
Solar/Wind Harmer
0.005
971795AH1-408 GEN
Solar/Wind Harmer
12.912
3145783HORNRTN
Solar/Wind Harmer
0.192
3145796HORNRTN
Solar/Wind Harmer
0.634
3145796HORNRTN
Solar/Wind Harmer
0.192
3147043LAWRENC
Adder
1.734
315693AD1-088 GEN
Solar/Wind Harmer
9.193
962491AG1-098 GEN
Solar/Wind Harmer
10.897
3147666LOUISA
Solar/Wind Harmer
0.757
316212AC1-099_GEN
Solar/Wind Harmer
0.971
3146293MARTNCO
Solar/Wind Harmer
0.174
316192AB2-158 GEN
Solar/Wind Harmer
1.044
316129AC1-054 GEN
Solar/Wind Harmer
0.691
3145746EVERETS
Solar/Wind Harmer
0.183
3145746EVERETS
Solar/Wind Harmer
0.183
971065AG2-659 GEN
Solar/Wind Harmer
7.805
315722AD1-056 GEN
Solar/Wind Harmer
1.154
316494AC1-189 GEN
Solar/Wind Harmer
0.609
315687AD1-152 GEN
Solar/Wind Harmer
0.006
961671AG1-007 GEN
Solar/Wind Harmer
0.027
3146083TARBORO
Solar/Wind Harmer
0.178
3145493TOT1
Solar/Wind Harmer
0.79
3146233WITAKRS
Solar/Wind Harmer
0.707
316237AB2-079_GEN
Solar/Wind Harmer
0.001
972135AH1-637 GEN
Solar/Wind Harmer
1.506
970685AG2-442 GEN
Solar/Wind Harmer
13.097
970937AG2-583 GEN
Solar/Wind Harmer
10.754
963171AG1-166 GEN
Solar/Wind Harmer
0.933
971563AH1-280 GEN
Solar/Wind Harmer
1.866
3144293JTRSVLE
Adder
0.557
3145543BTLEBRO
Solar/Wind Harmer
0.174
3145543BTLEBRO
Solar/Wind Harmer
0.139
316359AB2-059 GEN
Solar/Wind Harmer
0.626
316049AB1-081 GEN
Solar/Wind Harmer
0.997
3142053HEARTS
Solar/Wind Harmer
0.307
3146926FARMVIL
Solar/Wind Harmer
0.104
970401AG2-262 GEN
Solar/Wind Harmer
0.986
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.066
972277AH1-723 GEN
Adder
96.942
972003AH1-546 GEN
Solar/Wind Harmer
6.703
316003AC1-222 GEN
Solar/Wind Harmer
0.004
971377AH1-170 GEN
Solar/Wind Harmer
1.568
3147623JAMES R
Solar/Wind Harmer
0.341
316045AC1-158 PL2
Solar/Wind Helper
6.052
316006AB2-029 C
Solar/Wind Helper
0.11
3145593CAROLNA
Solar/Wind Harmer
0.193
966811AG1-552 GEN
Solar/Wind Harmer
2.098
3145593CAROLNA
Solar/Wind Harmer
0.241
3145783HORNRTN
Solar/Wind Harmer
3.419
3145783HORNRTN
Solar/Wind Harmer
2.735
3145783HORNRTN
Solar/Wind Harmer
0.855
3145783HORNRTN
Solar/Wind Harmer
0.342
3145796HORNRTN
Solar/Wind Harmer
0.576
3145933PARMELE
Solar/Wind Harmer
0.375
3145933PARMELE
Solar/Wind Harmer
0.187
316274AC1-208 GEN
Solar/Wind Harmer
0.967
971741AH1-377 GEN
Solar/Wind Harmer
18.163
970301AG2-198 GEN
Solar/Wind Harmer
7.705
939181AE1-148 GEN
Solar/Wind Harmer
8.56
3145493TOT1
Solar/Wind Harmer
0.412
3145453TOT5
Solar/Wind Harmer
0.247
3145603CNETO
Solar/Wind Harmer
0.165
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.013
970323AG2-213 GEN
Solar/Wind Harmer
7.506
971775AH1-396 GEN
Solar/Wind Harmer
0.281
958211AF2-115 GEN
Solar/Wind Harmer
2.099
963191AG1-168 GEN
Solar/Wind Harmer
0.7
3144293JTRSVLE
Adder
0.557
3144293JTRSVLE
Adder
0.469
3147133PAMPLIN
Solar/Wind Harmer
0.174
3147133PAMPLIN
Solar/Wind Harmer
0.139
961601AG1-000A GEN
Solar/Wind Harmer
3.1
316263AC1-034 GEN
Solar/Wind Harmer
6.622
962561AG1-105 GEN
Solar/Wind Harmer
8.133
964791AG1-342 GEN
Solar/Wind Harmer
3.227
3146843MT LREL
Solar/Wind Harmer
0.168
3146843MT LREL
Solar/Wind Harmer
0.168
3146776BUCKING
Solar/Wind Harmer
0.66
3146776BUCKING
Solar/Wind Harmer
0.053
971489AH1-241 GEN
Solar/Wind Harmer
7.84
316222AC1-221 GEN
Solar/Wind Harmer
0.61
315821AE2-092 GEN
Solar/Wind Harmer
0.008
942751AE2-291 GEN
Solar/Wind Harmer
6.812
316447AC1-158 HLD
Solar/Wind Helper
4.161
NYPJM->LTFIMP_NY
CLTF
3.144
LGEELTFEXP_LGEE->PJM
CLTF
1.356
WECLTFEXP_WEC->PJM
CLTF
0.657
LAGNLTFEXP_LAGN->PJM
CLTF
8.007
CBM South 2LTFEXP_CBM-S2->PJM
CBM
24.726
TVALTFEXP_TVA->PJM
CLTF
4.059
CBM West 1LTFEXP_CBM-W1->PJM
CBM
21.991
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.831
MECLTFEXP_MEC->PJM
CLTF
3.667
SIGELTFEXP_SIGE->PJM
CLTF
0.112
CPLELTFEXP_CPLE->PJM
CLTF
11.252
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.535

Details for 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T594_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 545T594_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:122.59 %
Rating:3966.0 MVA
Rating Type:C
MVA to Mitigate:4861.73
MW Contribution:81.78
Bus #Bus NameTypeMW Contribution
3150391LDYSMT3
50/50
29.114
972195AH1-682 GEN
50/50
3.826
316447AC1-158 HLD
Solar/Wind Harmer
6.165
315673AE1-157 GEN
Solar/Wind Harmer
17.268
957411AF2-035 GEN
Solar/Wind Harmer
10.36
970317AG2-208 GEN
Solar/Wind Harmer
10.072
3142296MT RD221
Adder
0.648
3142366NRTHEST
Adder
0.652
3150691DARBY 3
Adder
14.334
3150701DARBY 4
Adder
14.301
3150681DARBY 2
Adder
14.284
3150671DARBY 1
Adder
14.268
3143526WINTERP
Solar/Wind Harmer
-0.115
971223AH1-071 GEN
Solar/Wind Harmer
2.782
316075AC2-137 C
Solar/Wind Harmer
0.598
3142946ENON
Solar/Wind Harmer
-0.002
966871AG1-558 GEN
Solar/Wind Harmer
0.658
966871AG1-558 GEN
Solar/Wind Harmer
0.225
944641AF1-129 GEN
Adder
92.674
316240AF1-291 C
Solar/Wind Harmer
0.657
316033AB2-134 GEN
Solar/Wind Harmer
6.956
315697AD1-025 GEN
Solar/Wind Harmer
4.362
316236AE1-162_GEN
Solar/Wind Harmer
0.642
316036AC1-147 C
Solar/Wind Harmer
0.571
3150991CHESPKB
Adder
1.974
3150991CHESPKB
Adder
1.926
970657AG2-426 GEN
Solar/Wind Harmer
6.608
970657AG2-426 GEN
Solar/Wind Harmer
1.382
316316AC1-027 C
Solar/Wind Harmer
0.649
3142956BIRDNECK
Solar/Wind Harmer
1.134
316185AD1-033 GEN
Solar/Wind Harmer
2.226
3145506HICKORY
Solar/Wind Harmer
-0.084
3145506HICKORY
Solar/Wind Harmer
-0.05
3145506HICKORY
Solar/Wind Harmer
-0.012
316339AD2-160 GEN
Solar/Wind Harmer
1.415
316018AA1-139 ULT2
Solar/Wind Harmer
1.796
316017AA1-139 ULT1
Solar/Wind Harmer
1.697
3137176SLIGO L2192
Solar/Wind Harmer
-0.083
3146456SLIGO L269
Solar/Wind Harmer
2.471
3130086AYDLETT
Solar/Wind Harmer
-0.083
316441AF1-014 GEN
Solar/Wind Harmer
1.404
3146386ELIZ CT
Solar/Wind Harmer
-0.021
316431W1029_GEN1
Solar/Wind Harmer
3.714
316433W1029_GEN2
Solar/Wind Harmer
3.714
3146516WINFALL
Solar/Wind Harmer
-0.02
3146516WINFALL
Solar/Wind Harmer
-0.02
3146516WINFALL
Solar/Wind Harmer
-0.02
3146626S HERTFORD
Solar/Wind Harmer
-0.02
3146626S HERTFORD
Solar/Wind Harmer
-0.02
3144356SAPONY
Solar/Wind Harmer
0.708
315742AE1-103 GEN
Solar/Wind Harmer
2.091
3146376EDENTON
Solar/Wind Harmer
0.59
3146376EDENTON
Solar/Wind Harmer
0.59
972185AH1-677 GEN
Adder
9.891
972187AH1-678 GEN
Adder
4.965
316487AF1-042 GEN
Solar/Wind Harmer
2.579
970933AG2-581 GEN
Solar/Wind Harmer
18.105
958261AF2-120 GEN
Solar/Wind Harmer
7.463
316065AD1-022 GEN
Solar/Wind Harmer
9.475
3145893MURPHYS
Solar/Wind Harmer
0.525
3145893MURPHYS
Solar/Wind Harmer
-0.034
316077AC2-138 C
Solar/Wind Harmer
0.394
3150341NORNECKC1
Adder
1.741
3150341NORNECKC1
Adder
1.727
3146173TUNIS
Solar/Wind Harmer
-0.019
3146173TUNIS
Solar/Wind Harmer
-0.019
316468AD1-105 GEN
Solar/Wind Harmer
2.063
316181AB2-040 GEN
Solar/Wind Harmer
2.537
970099AG2-077 GEN
Solar/Wind Harmer
22.731
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.011
316426AA2-053 GEN
Solar/Wind Harmer
1.824
3145593CAROLNA
Solar/Wind Harmer
-0.018
3145593CAROLNA
Solar/Wind Harmer
-0.018
971507AH1-251 GEN
50/50
14.786
3152251N ANNA1
50/50
11.838
972197AH1-683 GEN
50/50
4.555
972219AH1-694 GEN
50/50
3.279
315052AA1-145 CT2
50/50
1.632
316045AC1-158 PL2
Solar/Wind Harmer
8.968
966881AG1-559 GEN
Solar/Wind Harmer
0.237
3142416OLDCHRC
Solar/Wind Harmer
-0.058
3142416OLDCHRC
Solar/Wind Harmer
-0.022
3143526WINTERP
Solar/Wind Harmer
-0.115
3143226MDLTHAN
Solar/Wind Harmer
-0.022
3150851SPRUNCC
Adder
0.911
3143096IRON208
Adder
0.827
3142543TWELFTH
Solar/Wind Harmer
-0.002
944631AF1-128 GEN
Adder
93.32
970129AG2-093 GEN
Solar/Wind Harmer
4.946
316458AB2-190 GEN2
Solar/Wind Harmer
2.192
315671AE2-027_GEN
Solar/Wind Harmer
16.243
316159AE1-175 C
Solar/Wind Harmer
0.581
971069AG2-661 GEN
Solar/Wind Harmer
3.42
971647AH1-324 GEN
Solar/Wind Harmer
10.758
961611AG1-000B GEN
Solar/Wind Harmer
10.592
3138126ROCKLANDING
Solar/Wind Harmer
0.066
316294AC1-161 GEN
Solar/Wind Harmer
6.933
971317AH1-138 GEN
Solar/Wind Harmer
2.677
3151171GRAVELC
Adder
2.026
3145336SMITFLD
Solar/Wind Harmer
-0.085
3142433PROV 92
Solar/Wind Harmer
-0.085
3142433PROV 92
Adder
0.369
3142433PROV 92
Adder
0.369
970659AG2-427 GEN
Solar/Wind Harmer
11.259
944591AF1-124 GEN
Solar/Wind Harmer
96.699
316375AC2-012 GEN
Solar/Wind Harmer
7.327
3150981CHESPKA
Adder
2.353
316381AD1-082 GEN
Solar/Wind Harmer
1.941
970661AG2-428 GEN
Solar/Wind Harmer
22.42
939411AE1-173 GEN
Solar/Wind Harmer
105.248
940641AE2-051 GEN
Solar/Wind Harmer
19.719
316072AD1-144
Solar/Wind Harmer
0.425
316388AE2-253 GEN
Solar/Wind Harmer
1.415
3146456SLIGO L269
Solar/Wind Harmer
-0.021
316246AF1-032 C
Solar/Wind Harmer
0.423
3141766HARMONY
Solar/Wind Harmer
-0.004
971777AH1-397 GEN
Solar/Wind Harmer
2.45
3141843SHACKLE
Adder
0.947
316093AE2-104_GEN
Solar/Wind Harmer
6.043
3146516WINFALL
Solar/Wind Harmer
-0.066
3146516WINFALL
Solar/Wind Harmer
-0.02
3138133OCRAN
Solar/Wind Harmer
-0.012
315800Z1-036_GEN1
Solar/Wind Harmer
4.975
3130156CHOWAN
Solar/Wind Harmer
-0.02
961951AG1-038 GEN
Solar/Wind Harmer
2.579
3145663CRESWEL
Solar/Wind Harmer
-0.054
971163AH1-040 GEN
Solar/Wind Harmer
18.248
3143336POWHATN
Solar/Wind Harmer
2.302
962861AG1-135 GEN
Solar/Wind Harmer
7.254
3147666LOUISA
Solar/Wind Harmer
-0.076
964211AG1-282 GEN
Solar/Wind Harmer
0.571
3141726DUNNSVL
Solar/Wind Harmer
-0.076
970919AG2-571 GEN
Solar/Wind Harmer
5.991
3146206CASHIE
Solar/Wind Harmer
-0.019
971547AH1-271 GEN
Solar/Wind Harmer
4.72
970087AG2-069 GEN
Solar/Wind Harmer
17.679
316023GEN1_S
Solar/Wind Harmer
1.272
316192AB2-158 GEN
Solar/Wind Harmer
2.241
3145893MURPHYS
Solar/Wind Harmer
-0.075
3145893MURPHYS
Solar/Wind Harmer
0.558
3150351NORNECKC2
Adder
1.658
316336AC2-165 C
Solar/Wind Harmer
3.24
3146173TUNIS
Solar/Wind Harmer
-0.019
3145683EARLEYS
Solar/Wind Harmer
-0.018
960081AF2-299 GEN
Solar/Wind Harmer
2.069
3146263WOODLND
Solar/Wind Harmer
-0.018
3145963POPLR C
Solar/Wind Harmer
-0.018
957481AF2-042 GEN
Solar/Wind Harmer
56.829
316011AB1-132 GEN
Solar/Wind Harmer
3.79
962571AG1-106 GEN
Solar/Wind Harmer
2.604
3145823KELFORD
Solar/Wind Harmer
-0.018
316190AA2-174 GEN
Solar/Wind Harmer
0.222
316174AB2-169 GEN
Solar/Wind Harmer
2.78
971795AH1-408 GEN
Solar/Wind Harmer
13.508
315693AD1-088 GEN
Solar/Wind Harmer
8.939
3145783HORNRTN
Solar/Wind Harmer
-0.018
3145796HORNRTN
Solar/Wind Harmer
-0.059
3145796HORNRTN
Solar/Wind Harmer
-0.018
3147043LAWRENC
Adder
1.436
3144293JTRSVLE
Adder
0.467
972277AH1-723 GEN
Adder
81.777
3151751LOISA D
Adder
7.363
962491AG1-098 GEN
Solar/Wind Harmer
11.83
966811AG1-552 GEN
Solar/Wind Harmer
2.021
3145593CAROLNA
Solar/Wind Harmer
0.149
3145783HORNRTN
Solar/Wind Harmer
2.12
3145783HORNRTN
Solar/Wind Harmer
1.696
3145783HORNRTN
Solar/Wind Harmer
0.53
3145783HORNRTN
Solar/Wind Harmer
0.212
3145796HORNRTN
Solar/Wind Harmer
-0.053
3144293JTRSVLE
Adder
0.467
3144293JTRSVLE
Adder
0.393
3151731LOISA B
Adder
7.363
3151721LOISA A
Adder
7.325
971531AH1-263 GEN
50/50
71.798
3150411LDYSMT5
50/50
29.26
3150381LDYSMT2
50/50
28.002
972213AH1-691 GEN
50/50
4.737
972215AH1-692 GEN
50/50
4.737
963051AG1-154 GEN
50/50
3.644
316164AC1-076 GEN
Solar/Wind Harmer
1.977
972189AH1-679 GEN
Adder
3.432
316312AB1-027
Solar/Wind Harmer
0.761
316233AE1-074 FULL
Solar/Wind Harmer
0.6
971281AH1-106 GEN
Solar/Wind Harmer
3.623
971283AH1-107 GEN
Solar/Wind Harmer
3.623
971285AH1-108 GEN
Adder
1.491
315976AC1-164 GENA
Solar/Wind Harmer
23.237
316169AC1-164_GENC
Solar/Wind Harmer
20.075
315975AC1-164 GENB
Solar/Wind Harmer
0.687
316132AB2-190 GEN1
Solar/Wind Harmer
2.192
316369SG1_INVT
Solar/Wind Harmer
3.854
972265AH1-717 GEN
Adder
14.786
3151201GRAVEL4
Adder
13.861
3151191GRAVEL3
Adder
13.685
3151211GRAVEL5
Adder
13.685
971167AH1-042 GEN
Solar/Wind Harmer
20.562
971445AH1-216 GEN
Solar/Wind Harmer
13.194
3143316POE
Solar/Wind Harmer
-0.084
3142433PROV 92
Adder
0.369
3142433PROV 92
Adder
0.369
3151081ELIZAR1
Adder
17.279
3151091ELIZAR2
Adder
16.979
3152611GOSPORTB
Adder
2.4
3152621GOSPORTC
Adder
2.037
3152601GOSPORTA
Adder
1.879
3143873LANEXA
Solar/Wind Harmer
-0.013
957831AF2-077 GEN
Solar/Wind Harmer
0.633
3138283WHITEMARSH
Solar/Wind Harmer
0.033
957871AF2-081 GEN
Solar/Wind Harmer
10.484
316314AB2-024 C
Solar/Wind Harmer
1.791
315833AF1-017_GEN
Solar/Wind Harmer
3.976
316349AD2-085 GEN
Solar/Wind Harmer
1.862
316311AC2-079 GEN
Solar/Wind Harmer
10.556
319010AE1-072 C
Solar/Wind Harmer
4.229
3146406KITTY HAWK
Solar/Wind Harmer
0.017
316305AF2-043 C
Solar/Wind Harmer
0.63
316059AD1-063 C
Solar/Wind Harmer
0.471
315835AF2-110_GEN
Solar/Wind Harmer
2.598
315662AE1-191 GEN
Solar/Wind Harmer
2.502
315666AE1-190 GEN
Solar/Wind Harmer
0.626
313526AB2-022
Solar/Wind Harmer
0.559
957601AF2-054 GEN
Solar/Wind Harmer
0.618
3146486SUNBURY
Solar/Wind Harmer
-0.021
3146486SUNBURY
Solar/Wind Harmer
-0.021
3141873WAN 176
Solar/Wind Harmer
-0.004
316321Z2-027
Solar/Wind Harmer
0.556
3146396TANGLEW
Solar/Wind Harmer
0.379
3145176PASQUOTANK
Solar/Wind Harmer
-0.013
3141913WHIT STONE
Solar/Wind Harmer
-0.02
316315AB2-025 C
Solar/Wind Harmer
0.548
941031AE2-094 GEN
Solar/Wind Harmer
38.047
944011AF1-069 GEN
Solar/Wind Harmer
11.921
3138133OCRAN
Solar/Wind Harmer
-0.006
315814AE2-033 C
Solar/Wind Harmer
18.834
315611Z1-036_GEN2
Solar/Wind Harmer
4.975
3141783LANCAST
Solar/Wind Harmer
-0.012
3141783LANCAST
Solar/Wind Harmer
-0.008
970673AG2-436 GEN
Solar/Wind Harmer
41.947
970673AG2-436 GEN
Solar/Wind Harmer
21.239
3130156CHOWAN
Solar/Wind Harmer
-0.02
3130156CHOWAN
Solar/Wind Harmer
-0.02
962981AG1-147 GEN
Solar/Wind Harmer
8.653
971967AH1-528 GEN
Solar/Wind Harmer
37.117
315816AE2-034 GEN
Solar/Wind Harmer
1.575
3130546PLYMOUTH
Solar/Wind Harmer
-0.019
315732AD1-074 GEN1
Solar/Wind Harmer
3.857
315733AD1-074 GEN2
Solar/Wind Harmer
3.857
315735AD1-075 GEN1
Solar/Wind Harmer
1.929
965291AG1-394 GEN
Solar/Wind Harmer
1.684
3146206CASHIE
Solar/Wind Harmer
-0.019
970601AG2-382 GEN
Solar/Wind Harmer
8.26
970085AG2-068 GEN
Solar/Wind Harmer
11.786
970581AG2-369 GEN
Solar/Wind Harmer
10.136
316318V4-068
Solar/Wind Harmer
0.469
3145893MURPHYS
Solar/Wind Harmer
-0.05
3145893MURPHYS
Solar/Wind Harmer
-0.019
3141813NORNECK
Solar/Wind Harmer
-0.019
3145513AHOSKIE
Solar/Wind Harmer
0.162
961941AG1-037 GEN
Solar/Wind Harmer
0.139
3145513AHOSKIE
Solar/Wind Harmer
-0.018
3145683EARLEYS
Solar/Wind Harmer
-0.037
3145683EARLEYS
Solar/Wind Harmer
-0.018
3145683EARLEYS
Solar/Wind Harmer
-0.018
3146043SEABORD
Solar/Wind Harmer
-0.018
946281AF1-292 GEN
Solar/Wind Harmer
0.412
315607AA1-063A GEN
Solar/Wind Harmer
1.855
316087AB2-174 GEN
Solar/Wind Harmer
2.603
315652AC1-086 GEN
Solar/Wind Harmer
20.378
3137643SOCKMAN
Solar/Wind Harmer
-0.072
3145796HORNRTN
Solar/Wind Harmer
-0.057
3145796HORNRTN
Solar/Wind Harmer
-0.007
972193AH1-681 GEN
Adder
3.136
972205AH1-687 GEN
Adder
5.738
3152261N ANNA2
50/50
11.837
970497AG2-320 GEN
50/50
20.71
3150401LDYSMT4
50/50
29.168
3150371LDYSMT1
50/50
28.185
315051AA1-145 CT1
50/50
1.625
316044AC1-158 PL1
Solar/Wind Harmer
2.804
316450AC1-158 RIC
Solar/Wind Harmer
0.748
966881AG1-559 GEN
Solar/Wind Harmer
0.692
3142416OLDCHRC
Solar/Wind Harmer
2.276
970293AG2-193 GEN
Solar/Wind Harmer
2.786
3150861SPRUNCD
Adder
0.911
3143096IRON208
Adder
0.827
3143096IRON208
Adder
0.81
3142946ENON
Solar/Wind Harmer
-0.007
316473AC1-191 GEN
Solar/Wind Harmer
2.356
970133AG2-095 GEN
Solar/Wind Harmer
2.451
970129AG2-093 GEN
Solar/Wind Harmer
12.209
316382AG1-145 C
Solar/Wind Harmer
0.653
965281AG1-393 GEN
Solar/Wind Harmer
2.702
315778AD1-151 GEN
Solar/Wind Harmer
18.722
315839AE2-212 C
Solar/Wind Harmer
0.651
961611AG1-000B GEN
Solar/Wind Harmer
4.519
3144216WINCHST
Adder
0.719
3150921YORKTN3
Adder
4.794
315773AC2-141 GEN
Solar/Wind Harmer
8.967
3151221GRAVEL6
Adder
13.845
3151171GRAVELC
Adder
2.664
315813AE1-149 C
Solar/Wind Harmer
13.325
3145336SMITFLD
Solar/Wind Harmer
-0.008
3142433PROV 92
Adder
0.369
3142433PROV 92
Adder
0.369
3144536CHRHLND
Solar/Wind Harmer
-0.003
970659AG2-427 GEN
Solar/Wind Harmer
1.995
944581AF1-123 GEN
Solar/Wind Harmer
96.352
944601AF1-125 GEN
Solar/Wind Harmer
94.848
3151101ELIZAR3
Adder
17.5
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316083AB2-161 GEN
Solar/Wind Harmer
3.436
970661AG2-428 GEN
Solar/Wind Harmer
3.973
3146456SLIGO L269
Solar/Wind Harmer
-0.021
971153AH1-033 GEN
Solar/Wind Harmer
2.551
3141766HARMONY
Solar/Wind Harmer
1.855
3141843SHACKLE
Adder
0.947
316203AE2-005 GEN
Solar/Wind Harmer
8.783
316280AD1-041 GEN
Solar/Wind Harmer
1.564
316320Y1-086
Solar/Wind Harmer
1.214
316156AD2-030 GEN
Solar/Wind Harmer
0.552
3141873WAN 176
Solar/Wind Harmer
2.451
316435W1029_GEN3
Solar/Wind Harmer
3.714
3146516WINFALL
Solar/Wind Harmer
-0.02
3146626S HERTFORD
Solar/Wind Harmer
-0.02
3145273HOLLAND
Solar/Wind Harmer
-0.015
3146376EDENTON
Solar/Wind Harmer
-0.02
962971AG1-146 GEN
Solar/Wind Harmer
3.709
316484AD2-074 GEN
Solar/Wind Harmer
4.929
970009AG2-005 GEN
Solar/Wind Harmer
2.448
315614AA2-178 GEN
Solar/Wind Harmer
2.1
316313AB2-026
Solar/Wind Harmer
0.523
316258AE1-075 C
Solar/Wind Harmer
0.471
316405AF2-144 C
Solar/Wind Harmer
0.497
3143336POWHATN
Solar/Wind Harmer
1.956
316404AE1-155 C
Solar/Wind Harmer
3.715
3147666LOUISA
Solar/Wind Harmer
-0.044
971157AH1-035 GEN
Solar/Wind Harmer
2.392
315737AD1-076 GEN
Solar/Wind Harmer
3.625
3156081AA2-088 GEN
Solar/Wind Harmer
6.186
970917AG2-570 GEN
Solar/Wind Harmer
47.325
3146206CASHIE
Solar/Wind Harmer
-0.019
316365GEN2_N
Solar/Wind Harmer
1.272
3145893MURPHYS
Solar/Wind Harmer
0.131
3145893MURPHYS
Solar/Wind Harmer
-0.019
957521AF2-046 GEN
Solar/Wind Harmer
14.773
961681AG1-008 GEN
Solar/Wind Harmer
14.773
3150351NORNECKC2
Adder
1.686
3146173TUNIS
Solar/Wind Harmer
-0.019
3156021HOLLOMANSOL
Solar/Wind Harmer
2.506
316463AE2-346 GEN
Solar/Wind Harmer
0.3
316140AB2-099
Solar/Wind Harmer
0.125
962331AG1-082 GEN
Solar/Wind Harmer
2.318
971781AH1-399 GEN
Solar/Wind Harmer
1.141
966621AG1-532 GEN
Solar/Wind Harmer
0.373
3146263WOODLND
Solar/Wind Harmer
-0.018
313506AB2-031 GEN
Solar/Wind Harmer
1.462
3145963POPLR C
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
316317KELFORD C
Solar/Wind Harmer
0.853
3145823KELFORD
Solar/Wind Harmer
-0.018
3145796HORNRTN
Solar/Wind Harmer
-0.071
3145796HORNRTN
Solar/Wind Harmer
-0.018
3147043LAWRENC
Solar/Wind Harmer
-0.011
3144293JTRSVLE
Adder
0.467
972255AH1-712 GEN
Adder
70.176
3151761LOISA E
Adder
15.011
3141196NOKESVL
Solar/Wind Helper
1.31
NYPJM->LTFIMP_NY
CLTF
2.833
LGEELTFEXP_LGEE->PJM
CLTF
1.274
WECLTFEXP_WEC->PJM
CLTF
0.626
LAGNLTFEXP_LAGN->PJM
CLTF
7.028
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.882
TVALTFEXP_TVA->PJM
CLTF
3.562
CBM West 1LTFEXP_CBM-W1->PJM
CBM
21.314
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.222
MECLTFEXP_MEC->PJM
CLTF
3.393
SIGELTFEXP_SIGE->PJM
CLTF
0.104
CPLELTFEXP_CPLE->PJM
CLTF
9.417
CBM West 2LTFEXP_CBM-W2->PJM
CBM
37.156

Details for 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T594_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T594_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.53 %
Rating:5010.0 MVA
Rating Type:C
MVA to Mitigate:5687.82
MW Contribution:98.63
Bus #Bus NameTypeMW Contribution
971531AH1-263 GEN
50/50
86.479
3150411LDYSMT5
50/50
37.377
3150381LDYSMT2
50/50
35.771
972213AH1-691 GEN
50/50
6.051
972215AH1-692 GEN
50/50
6.051
963051AG1-154 GEN
50/50
4.655
972189AH1-679 GEN
Adder
4.292
316312AB1-027
Solar/Wind Harmer
0.945
316164AC1-076 GEN
Solar/Wind Harmer
2.342
316233AE1-074 FULL
Solar/Wind Harmer
0.742
971281AH1-106 GEN
Solar/Wind Harmer
4.482
971283AH1-107 GEN
Solar/Wind Harmer
4.482
971285AH1-108 GEN
Adder
1.847
315976AC1-164 GENA
Solar/Wind Harmer
28.89
316169AC1-164_GENC
Solar/Wind Harmer
24.958
315975AC1-164 GENB
Solar/Wind Harmer
0.855
316132AB2-190 GEN1
Solar/Wind Harmer
2.717
316369SG1_INVT
Solar/Wind Harmer
4.774
971167AH1-042 GEN
Solar/Wind Harmer
25.638
3142433PROV 92
Adder
0.46
3142433PROV 92
Adder
0.46
972265AH1-717 GEN
Adder
18.308
3151201GRAVEL4
Adder
17.163
3151191GRAVEL3
Adder
16.945
3151211GRAVEL5
Adder
16.945
971445AH1-216 GEN
Solar/Wind Harmer
16.329
3143316POE
Solar/Wind Harmer
-0.104
3143873LANEXA
Solar/Wind Harmer
-0.016
957831AF2-077 GEN
Solar/Wind Harmer
0.789
3138283WHITEMARSH
Solar/Wind Harmer
0.041
316314AB2-024 C
Solar/Wind Harmer
2.241
3151081ELIZAR1
Adder
21.363
3151091ELIZAR2
Adder
20.992
3152611GOSPORTB
Adder
2.967
3152621GOSPORTC
Adder
2.518
3152601GOSPORTA
Adder
2.323
316059AD1-063 C
Solar/Wind Harmer
0.59
315662AE1-191 GEN
Solar/Wind Harmer
3.133
315666AE1-190 GEN
Solar/Wind Harmer
0.783
957871AF2-081 GEN
Solar/Wind Harmer
12.957
315833AF1-017_GEN
Solar/Wind Harmer
4.915
316349AD2-085 GEN
Solar/Wind Harmer
2.301
957601AF2-054 GEN
Solar/Wind Harmer
0.774
3141873WAN 176
Solar/Wind Harmer
-0.005
316311AC2-079 GEN
Solar/Wind Harmer
13.05
319010AE1-072 C
Solar/Wind Harmer
5.227
3146406KITTY HAWK
Solar/Wind Harmer
0.021
316305AF2-043 C
Solar/Wind Harmer
0.778
315835AF2-110_GEN
Solar/Wind Harmer
3.211
313526AB2-022
Solar/Wind Harmer
0.69
3141913WHIT STONE
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
3138133OCRAN
Solar/Wind Harmer
-0.008
316321Z2-027
Solar/Wind Harmer
0.687
3146396TANGLEW
Solar/Wind Harmer
0.469
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
316315AB2-025 C
Solar/Wind Harmer
0.676
941031AE2-094 GEN
Solar/Wind Harmer
46.894
944011AF1-069 GEN
Solar/Wind Harmer
14.693
962981AG1-147 GEN
Solar/Wind Harmer
10.926
315814AE2-033 C
Solar/Wind Harmer
23.239
315611Z1-036_GEN2
Solar/Wind Harmer
6.142
970673AG2-436 GEN
Solar/Wind Harmer
51.677
970673AG2-436 GEN
Solar/Wind Harmer
26.165
3130156CHOWAN
Solar/Wind Harmer
-0.024
3130156CHOWAN
Solar/Wind Harmer
-0.024
971967AH1-528 GEN
Solar/Wind Harmer
45.703
315816AE2-034 GEN
Solar/Wind Harmer
1.942
3141813NORNECK
Solar/Wind Harmer
-0.024
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.753
315733AD1-074 GEN2
Solar/Wind Harmer
4.753
315735AD1-075 GEN1
Solar/Wind Harmer
2.377
965291AG1-394 GEN
Solar/Wind Harmer
2.074
3146206CASHIE
Solar/Wind Harmer
-0.023
970601AG2-382 GEN
Solar/Wind Harmer
10.174
970085AG2-068 GEN
Solar/Wind Harmer
14.495
970581AG2-369 GEN
Solar/Wind Harmer
12.466
316318V4-068
Solar/Wind Harmer
0.577
3145893MURPHYS
Solar/Wind Harmer
-0.062
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145513AHOSKIE
Solar/Wind Harmer
0.199
961941AG1-037 GEN
Solar/Wind Harmer
0.172
3145513AHOSKIE
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.045
3145683EARLEYS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
3146043SEABORD
Solar/Wind Harmer
-0.023
946281AF1-292 GEN
Solar/Wind Harmer
0.506
315607AA1-063A GEN
Solar/Wind Harmer
2.282
316087AB2-174 GEN
Solar/Wind Harmer
3.201
315652AC1-086 GEN
Solar/Wind Harmer
25.058
3137643SOCKMAN
Solar/Wind Harmer
-0.088
3145796HORNRTN
Solar/Wind Harmer
-0.07
3145796HORNRTN
Solar/Wind Harmer
-0.009
972193AH1-681 GEN
Adder
3.782
972205AH1-687 GEN
Adder
6.911
316411AF1-147_GEN1
Solar/Wind Helper
0.808
316415AF1-147_GEN2
Solar/Wind Helper
0.808
3138216PACIFIC
Solar/Wind Helper
0.039
3150391LDYSMT3
50/50
37.191
972195AH1-682 GEN
50/50
4.887
316447AC1-158 HLD
Solar/Wind Harmer
7.599
315673AE1-157 GEN
Solar/Wind Harmer
21.923
957411AF2-035 GEN
Solar/Wind Harmer
13.105
970317AG2-208 GEN
Solar/Wind Harmer
12.741
3142296MT RD221
Adder
0.804
3142366NRTHEST
Adder
0.81
3150691DARBY 3
Adder
17.798
3150701DARBY 4
Adder
17.756
3150681DARBY 2
Adder
17.736
3150671DARBY 1
Adder
17.715
3143526WINTERP
Solar/Wind Harmer
-0.143
316075AC2-137 C
Solar/Wind Harmer
0.743
971223AH1-071 GEN
Solar/Wind Harmer
3.437
966871AG1-558 GEN
Solar/Wind Harmer
0.823
966871AG1-558 GEN
Solar/Wind Harmer
0.281
3142946ENON
Solar/Wind Harmer
-0.003
944641AF1-129 GEN
Adder
114.823
316240AF1-291 C
Solar/Wind Harmer
0.813
316033AB2-134 GEN
Solar/Wind Harmer
8.617
315697AD1-025 GEN
Solar/Wind Harmer
5.404
316236AE1-162_GEN
Solar/Wind Harmer
0.795
316036AC1-147 C
Solar/Wind Harmer
0.706
3150991CHESPKB
Adder
2.44
3150991CHESPKB
Adder
2.382
970657AG2-426 GEN
Solar/Wind Harmer
8.172
970657AG2-426 GEN
Solar/Wind Harmer
1.709
316316AC1-027 C
Solar/Wind Harmer
0.802
3142956BIRDNECK
Solar/Wind Harmer
1.402
316185AD1-033 GEN
Solar/Wind Harmer
2.752
316441AF1-014 GEN
Solar/Wind Harmer
1.757
3145506HICKORY
Solar/Wind Harmer
-0.104
3145506HICKORY
Solar/Wind Harmer
-0.062
3145506HICKORY
Solar/Wind Harmer
-0.015
316339AD2-160 GEN
Solar/Wind Harmer
1.749
316018AA1-139 ULT2
Solar/Wind Harmer
2.22
316017AA1-139 ULT1
Solar/Wind Harmer
2.097
3137176SLIGO L2192
Solar/Wind Harmer
-0.102
3146456SLIGO L269
Solar/Wind Harmer
3.054
3130086AYDLETT
Solar/Wind Harmer
-0.103
3146386ELIZ CT
Solar/Wind Harmer
-0.026
316431W1029_GEN1
Solar/Wind Harmer
4.587
316433W1029_GEN2
Solar/Wind Harmer
4.587
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3144356SAPONY
Solar/Wind Harmer
0.874
316487AF1-042 GEN
Solar/Wind Harmer
3.263
315742AE1-103 GEN
Solar/Wind Harmer
2.58
3146376EDENTON
Solar/Wind Harmer
0.728
3146376EDENTON
Solar/Wind Harmer
0.728
958261AF2-120 GEN
Solar/Wind Harmer
9.47
972185AH1-677 GEN
Adder
12.182
972187AH1-678 GEN
Adder
6.113
316077AC2-138 C
Solar/Wind Harmer
0.503
3150341NORNECKC1
Adder
2.222
3150341NORNECKC1
Adder
2.205
316468AD1-105 GEN
Solar/Wind Harmer
2.653
970933AG2-581 GEN
Solar/Wind Harmer
22.274
316065AD1-022 GEN
Solar/Wind Harmer
11.672
3145893MURPHYS
Solar/Wind Harmer
0.646
3145893MURPHYS
Solar/Wind Harmer
-0.042
3146173TUNIS
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.023
971507AH1-251 GEN
50/50
17.806
3152251N ANNA1
50/50
14.609
972197AH1-683 GEN
50/50
5.818
972219AH1-694 GEN
50/50
4.189
315052AA1-145 CT2
50/50
2.041
316045AC1-158 PL2
Solar/Wind Harmer
11.053
966881AG1-559 GEN
Solar/Wind Harmer
0.3
3142416OLDCHRC
Solar/Wind Harmer
-0.073
3142416OLDCHRC
Solar/Wind Harmer
-0.028
3143526WINTERP
Solar/Wind Harmer
-0.143
3143096IRON208
Adder
1.026
3150851SPRUNCC
Adder
1.129
3143226MDLTHAN
Solar/Wind Harmer
-0.027
3142543TWELFTH
Solar/Wind Harmer
-0.003
944631AF1-128 GEN
Adder
115.833
316159AE1-175 C
Solar/Wind Harmer
0.721
970129AG2-093 GEN
Solar/Wind Harmer
6.129
316458AB2-190 GEN2
Solar/Wind Harmer
2.717
315671AE2-027_GEN
Solar/Wind Harmer
20.126
971069AG2-661 GEN
Solar/Wind Harmer
4.237
971647AH1-324 GEN
Solar/Wind Harmer
13.325
971317AH1-138 GEN
Solar/Wind Harmer
3.325
3138126ROCKLANDING
Solar/Wind Harmer
0.081
961611AG1-000B GEN
Solar/Wind Harmer
13.118
3142433PROV 92
Solar/Wind Harmer
-0.106
3142433PROV 92
Adder
0.46
3142433PROV 92
Adder
0.46
316294AC1-161 GEN
Solar/Wind Harmer
8.571
3151171GRAVELC
Adder
2.508
3145336SMITFLD
Solar/Wind Harmer
-0.105
970659AG2-427 GEN
Solar/Wind Harmer
13.927
944591AF1-124 GEN
Solar/Wind Harmer
119.536
316375AC2-012 GEN
Solar/Wind Harmer
9.059
3150981CHESPKA
Adder
2.909
316381AD1-082 GEN
Solar/Wind Harmer
2.401
970661AG2-428 GEN
Solar/Wind Harmer
27.727
3141766HARMONY
Solar/Wind Harmer
-0.005
971777AH1-397 GEN
Solar/Wind Harmer
3.066
3141843SHACKLE
Adder
1.186
939411AE1-173 GEN
Solar/Wind Harmer
129.946
316072AD1-144
Solar/Wind Harmer
0.526
940641AE2-051 GEN
Solar/Wind Harmer
24.336
316388AE2-253 GEN
Solar/Wind Harmer
1.749
3146456SLIGO L269
Solar/Wind Harmer
-0.026
316246AF1-032 C
Solar/Wind Harmer
0.522
316093AE2-104_GEN
Solar/Wind Harmer
7.468
3138133OCRAN
Solar/Wind Harmer
-0.015
3146516WINFALL
Solar/Wind Harmer
-0.081
3146516WINFALL
Solar/Wind Harmer
-0.025
315800Z1-036_GEN1
Solar/Wind Harmer
6.142
961951AG1-038 GEN
Solar/Wind Harmer
3.263
3130156CHOWAN
Solar/Wind Harmer
-0.024
962861AG1-135 GEN
Solar/Wind Harmer
9.197
964211AG1-282 GEN
Solar/Wind Harmer
0.726
3141726DUNNSVL
Solar/Wind Harmer
-0.096
3145663CRESWEL
Solar/Wind Harmer
-0.067
971163AH1-040 GEN
Solar/Wind Harmer
22.501
3150351NORNECKC2
Adder
2.116
3143336POWHATN
Solar/Wind Harmer
2.821
970919AG2-571 GEN
Solar/Wind Harmer
7.369
3146206CASHIE
Solar/Wind Harmer
-0.023
971547AH1-271 GEN
Solar/Wind Harmer
5.814
316023GEN1_S
Solar/Wind Harmer
1.565
970087AG2-069 GEN
Solar/Wind Harmer
21.743
3145893MURPHYS
Solar/Wind Harmer
-0.092
3145893MURPHYS
Solar/Wind Harmer
0.687
3147666LOUISA
Solar/Wind Harmer
-0.092
3146173TUNIS
Solar/Wind Harmer
-0.023
316337AD2-073 GEN
Solar/Wind Harmer
0.613
316336AC2-165 C
Solar/Wind Harmer
3.962
3145683EARLEYS
Solar/Wind Harmer
-0.023
960081AF2-299 GEN
Solar/Wind Harmer
2.544
3146263WOODLND
Solar/Wind Harmer
-0.022
316192AB2-158 GEN
Solar/Wind Harmer
2.682
3145963POPLR C
Solar/Wind Harmer
-0.022
957481AF2-042 GEN
Solar/Wind Harmer
69.745
316011AB1-132 GEN
Solar/Wind Harmer
4.66
962571AG1-106 GEN
Solar/Wind Harmer
3.202
3145823KELFORD
Solar/Wind Harmer
-0.022
316190AA2-174 GEN
Solar/Wind Harmer
0.273
316174AB2-169 GEN
Solar/Wind Harmer
3.419
971795AH1-408 GEN
Solar/Wind Harmer
16.592
3145783HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.072
3145796HORNRTN
Solar/Wind Harmer
-0.022
315693AD1-088 GEN
Solar/Wind Harmer
10.957
3147043LAWRENC
Adder
1.763
3144293JTRSVLE
Adder
0.569
972277AH1-723 GEN
Adder
98.633
3151751LOISA D
Adder
8.426
962491AG1-098 GEN
Solar/Wind Harmer
13.911
316181AB2-040 GEN
Solar/Wind Harmer
3.119
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
970099AG2-077 GEN
Solar/Wind Harmer
27.898
316426AA2-053 GEN
Solar/Wind Harmer
2.242
3145593CAROLNA
Solar/Wind Harmer
-0.022
3145593CAROLNA
Solar/Wind Harmer
-0.022
966811AG1-552 GEN
Solar/Wind Harmer
2.484
3145593CAROLNA
Solar/Wind Harmer
0.183
3145783HORNRTN
Solar/Wind Harmer
2.605
3145783HORNRTN
Solar/Wind Harmer
2.084
3145783HORNRTN
Solar/Wind Harmer
0.651
3145783HORNRTN
Solar/Wind Harmer
0.26
3145796HORNRTN
Solar/Wind Harmer
-0.065
3144293JTRSVLE
Adder
0.569
3144293JTRSVLE
Adder
0.479
3151731LOISA B
Adder
8.426
3151721LOISA A
Adder
8.382
3152261N ANNA2
50/50
14.608
970497AG2-320 GEN
50/50
26.225
3150401LDYSMT4
50/50
37.261
3150371LDYSMT1
50/50
36.004
315051AA1-145 CT1
50/50
2.032
316044AC1-158 PL1
Solar/Wind Harmer
3.455
316450AC1-158 RIC
Solar/Wind Harmer
0.921
966881AG1-559 GEN
Solar/Wind Harmer
0.876
3142416OLDCHRC
Solar/Wind Harmer
2.828
970293AG2-193 GEN
Solar/Wind Harmer
3.46
3143096IRON208
Adder
1.026
3143096IRON208
Adder
1.006
3150861SPRUNCD
Adder
1.129
316473AC1-191 GEN
Solar/Wind Harmer
2.944
3142946ENON
Solar/Wind Harmer
-0.009
970133AG2-095 GEN
Solar/Wind Harmer
3.038
316382AG1-145 C
Solar/Wind Harmer
0.81
970129AG2-093 GEN
Solar/Wind Harmer
15.13
315778AD1-151 GEN
Solar/Wind Harmer
23.197
965281AG1-393 GEN
Solar/Wind Harmer
3.347
315839AE2-212 C
Solar/Wind Harmer
0.806
3150921YORKTN3
Adder
5.947
3144216WINCHST
Adder
0.892
961611AG1-000B GEN
Solar/Wind Harmer
5.597
3142433PROV 92
Adder
0.46
3142433PROV 92
Adder
0.46
315773AC2-141 GEN
Solar/Wind Harmer
11.086
3151221GRAVEL6
Adder
17.143
3151171GRAVELC
Adder
3.298
3145336SMITFLD
Solar/Wind Harmer
-0.01
315813AE1-149 C
Solar/Wind Harmer
16.487
3144536CHRHLND
Solar/Wind Harmer
-0.004
970659AG2-427 GEN
Solar/Wind Harmer
2.468
944581AF1-123 GEN
Solar/Wind Harmer
119.107
944601AF1-125 GEN
Solar/Wind Harmer
117.248
3151101ELIZAR3
Adder
21.637
316083AB2-161 GEN
Solar/Wind Harmer
4.25
3144873MCLAUGH
Solar/Wind Harmer
-0.001
970661AG2-428 GEN
Solar/Wind Harmer
4.914
3141766HARMONY
Solar/Wind Harmer
2.322
3141843SHACKLE
Adder
1.186
316203AE2-005 GEN
Solar/Wind Harmer
10.992
316280AD1-041 GEN
Solar/Wind Harmer
1.958
316156AD2-030 GEN
Solar/Wind Harmer
0.691
3141873WAN 176
Solar/Wind Harmer
3.071
3146456SLIGO L269
Solar/Wind Harmer
-0.026
971153AH1-033 GEN
Solar/Wind Harmer
3.152
316320Y1-086
Solar/Wind Harmer
1.5
316435W1029_GEN3
Solar/Wind Harmer
4.587
3146516WINFALL
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3145273HOLLAND
Solar/Wind Harmer
-0.019
962971AG1-146 GEN
Solar/Wind Harmer
4.683
316484AD2-074 GEN
Solar/Wind Harmer
6.235
970009AG2-005 GEN
Solar/Wind Harmer
3.096
3146376EDENTON
Solar/Wind Harmer
-0.024
316404AE1-155 C
Solar/Wind Harmer
4.714
315614AA2-178 GEN
Solar/Wind Harmer
2.59
3150351NORNECKC2
Adder
2.151
971781AH1-399 GEN
Solar/Wind Harmer
1.468
316313AB2-026
Solar/Wind Harmer
0.641
316258AE1-075 C
Solar/Wind Harmer
0.577
316405AF2-144 C
Solar/Wind Harmer
0.609
3143336POWHATN
Solar/Wind Harmer
2.398
971157AH1-035 GEN
Solar/Wind Harmer
2.948
315737AD1-076 GEN
Solar/Wind Harmer
4.467
3156081AA2-088 GEN
Solar/Wind Harmer
7.621
970917AG2-570 GEN
Solar/Wind Harmer
58.212
3146206CASHIE
Solar/Wind Harmer
-0.023
316365GEN2_N
Solar/Wind Harmer
1.565
3145893MURPHYS
Solar/Wind Harmer
0.162
3145893MURPHYS
Solar/Wind Harmer
-0.023
957521AF2-046 GEN
Solar/Wind Harmer
18.189
961681AG1-008 GEN
Solar/Wind Harmer
18.189
3147666LOUISA
Solar/Wind Harmer
-0.053
3146173TUNIS
Solar/Wind Harmer
-0.023
3156021HOLLOMANSOL
Solar/Wind Harmer
3.086
316463AE2-346 GEN
Solar/Wind Harmer
0.369
316140AB2-099
Solar/Wind Harmer
0.154
962331AG1-082 GEN
Solar/Wind Harmer
2.853
966621AG1-532 GEN
Solar/Wind Harmer
0.459
3146263WOODLND
Solar/Wind Harmer
-0.022
3145963POPLR C
Solar/Wind Harmer
-0.022
313506AB2-031 GEN
Solar/Wind Harmer
1.797
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
316317KELFORD C
Solar/Wind Harmer
1.049
3145823KELFORD
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.087
3145796HORNRTN
Solar/Wind Harmer
-0.022
3147043LAWRENC
Solar/Wind Harmer
-0.013
3144293JTRSVLE
Adder
0.569
972255AH1-712 GEN
Adder
84.642
3141316ARNOLDS
Adder
0.325
3151761LOISA E
Adder
17.177
972183AH1-676 GEN
Adder
134.74
3150331BIRCHWDA
Adder
21.291
3141196NOKESVL
Solar/Wind Helper
1.243
NYPJM->LTFIMP_NY
CLTF
3.27
LGEELTFEXP_LGEE->PJM
CLTF
1.341
WECLTFEXP_WEC->PJM
CLTF
0.646
LAGNLTFEXP_LAGN->PJM
CLTF
8.052
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.067
TVALTFEXP_TVA->PJM
CLTF
4.084
CBM West 1LTFEXP_CBM-W1->PJM
CBM
21.493
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.892
MECLTFEXP_MEC->PJM
CLTF
3.637
SIGELTFEXP_SIGE->PJM
CLTF
0.111
CPLELTFEXP_CPLE->PJM
CLTF
11.42
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.573

Details for 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: SPOTS H1T594_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.37 %
Rating:5010.0 MVA
Rating Type:C
MVA to Mitigate:5679.63
MW Contribution:98.36
Bus #Bus NameTypeMW Contribution
971531AH1-263 GEN
50/50
86.469
3150411LDYSMT5
50/50
37.359
3150381LDYSMT2
50/50
35.754
972213AH1-691 GEN
50/50
6.048
972215AH1-692 GEN
50/50
6.048
963051AG1-154 GEN
50/50
4.652
972189AH1-679 GEN
Adder
4.287
316312AB1-027
Solar/Wind Harmer
0.944
316233AE1-074 FULL
Solar/Wind Harmer
0.74
971281AH1-106 GEN
Solar/Wind Harmer
4.473
971283AH1-107 GEN
Solar/Wind Harmer
4.473
971285AH1-108 GEN
Adder
1.843
316164AC1-076 GEN
Solar/Wind Harmer
2.308
315976AC1-164 GENA
Solar/Wind Harmer
28.844
316169AC1-164_GENC
Solar/Wind Harmer
24.919
315975AC1-164 GENB
Solar/Wind Harmer
0.853
316132AB2-190 GEN1
Solar/Wind Harmer
2.712
316369SG1_INVT
Solar/Wind Harmer
4.765
971167AH1-042 GEN
Solar/Wind Harmer
25.596
3142433PROV 92
Adder
0.459
3142433PROV 92
Adder
0.459
972265AH1-717 GEN
Adder
18.275
3151201GRAVEL4
Adder
17.131
3151191GRAVEL3
Adder
16.914
3151211GRAVEL5
Adder
16.914
971445AH1-216 GEN
Solar/Wind Harmer
16.299
3143316POE
Solar/Wind Harmer
-0.103
3143873LANEXA
Solar/Wind Harmer
-0.016
957831AF2-077 GEN
Solar/Wind Harmer
0.788
3138283WHITEMARSH
Solar/Wind Harmer
0.041
316314AB2-024 C
Solar/Wind Harmer
2.237
3151081ELIZAR1
Adder
21.323
3151091ELIZAR2
Adder
20.953
3152611GOSPORTB
Adder
2.961
3152621GOSPORTC
Adder
2.513
3152601GOSPORTA
Adder
2.318
316059AD1-063 C
Solar/Wind Harmer
0.589
315662AE1-191 GEN
Solar/Wind Harmer
3.128
315666AE1-190 GEN
Solar/Wind Harmer
0.782
957871AF2-081 GEN
Solar/Wind Harmer
12.932
957601AF2-054 GEN
Solar/Wind Harmer
0.773
3141873WAN 176
Solar/Wind Harmer
-0.005
315833AF1-017_GEN
Solar/Wind Harmer
4.905
316349AD2-085 GEN
Solar/Wind Harmer
2.297
316311AC2-079 GEN
Solar/Wind Harmer
13.025
319010AE1-072 C
Solar/Wind Harmer
5.217
3146406KITTY HAWK
Solar/Wind Harmer
0.021
316305AF2-043 C
Solar/Wind Harmer
0.777
315835AF2-110_GEN
Solar/Wind Harmer
3.205
313526AB2-022
Solar/Wind Harmer
0.689
3141913WHIT STONE
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
3138133OCRAN
Solar/Wind Harmer
-0.008
316321Z2-027
Solar/Wind Harmer
0.686
3146396TANGLEW
Solar/Wind Harmer
0.468
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
316315AB2-025 C
Solar/Wind Harmer
0.674
941031AE2-094 GEN
Solar/Wind Harmer
46.791
944011AF1-069 GEN
Solar/Wind Harmer
14.661
962981AG1-147 GEN
Solar/Wind Harmer
10.909
315814AE2-033 C
Solar/Wind Harmer
23.19
315611Z1-036_GEN2
Solar/Wind Harmer
6.129
970673AG2-436 GEN
Solar/Wind Harmer
51.562
970673AG2-436 GEN
Solar/Wind Harmer
26.107
3130156CHOWAN
Solar/Wind Harmer
-0.024
3130156CHOWAN
Solar/Wind Harmer
-0.024
971967AH1-528 GEN
Solar/Wind Harmer
45.598
315816AE2-034 GEN
Solar/Wind Harmer
1.938
3141813NORNECK
Solar/Wind Harmer
-0.024
3130546PLYMOUTH
Solar/Wind Harmer
-0.023
315732AD1-074 GEN1
Solar/Wind Harmer
4.743
315733AD1-074 GEN2
Solar/Wind Harmer
4.743
315735AD1-075 GEN1
Solar/Wind Harmer
2.372
965291AG1-394 GEN
Solar/Wind Harmer
2.07
3146206CASHIE
Solar/Wind Harmer
-0.023
970601AG2-382 GEN
Solar/Wind Harmer
10.153
970085AG2-068 GEN
Solar/Wind Harmer
14.462
970581AG2-369 GEN
Solar/Wind Harmer
12.437
316318V4-068
Solar/Wind Harmer
0.576
3145893MURPHYS
Solar/Wind Harmer
-0.062
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145513AHOSKIE
Solar/Wind Harmer
0.199
961941AG1-037 GEN
Solar/Wind Harmer
0.171
3145513AHOSKIE
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.045
3145683EARLEYS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
3146043SEABORD
Solar/Wind Harmer
-0.023
946281AF1-292 GEN
Solar/Wind Harmer
0.505
315607AA1-063A GEN
Solar/Wind Harmer
2.277
316087AB2-174 GEN
Solar/Wind Harmer
3.193
315652AC1-086 GEN
Solar/Wind Harmer
25.002
3137643SOCKMAN
Solar/Wind Harmer
-0.088
3145796HORNRTN
Solar/Wind Harmer
-0.07
3145796HORNRTN
Solar/Wind Harmer
-0.009
972193AH1-681 GEN
Adder
3.771
972205AH1-687 GEN
Adder
6.858
316411AF1-147_GEN1
Solar/Wind Helper
0.807
316415AF1-147_GEN2
Solar/Wind Helper
0.807
3138216PACIFIC
Solar/Wind Helper
0.039
971507AH1-251 GEN
50/50
17.78
3152251N ANNA1
50/50
14.575
972197AH1-683 GEN
50/50
5.815
972219AH1-694 GEN
50/50
4.187
315052AA1-145 CT2
50/50
2.038
316045AC1-158 PL2
Solar/Wind Harmer
11.02
966881AG1-559 GEN
Solar/Wind Harmer
0.299
3142416OLDCHRC
Solar/Wind Harmer
-0.072
3142416OLDCHRC
Solar/Wind Harmer
-0.028
3143526WINTERP
Solar/Wind Harmer
-0.142
3143096IRON208
Adder
1.024
3150851SPRUNCC
Adder
1.127
3143226MDLTHAN
Solar/Wind Harmer
-0.027
3142543TWELFTH
Solar/Wind Harmer
-0.003
944631AF1-128 GEN
Adder
115.637
316159AE1-175 C
Solar/Wind Harmer
0.72
970129AG2-093 GEN
Solar/Wind Harmer
6.118
316458AB2-190 GEN2
Solar/Wind Harmer
2.712
315671AE2-027_GEN
Solar/Wind Harmer
20.089
971069AG2-661 GEN
Solar/Wind Harmer
4.229
971647AH1-324 GEN
Solar/Wind Harmer
13.301
971317AH1-138 GEN
Solar/Wind Harmer
3.319
3138126ROCKLANDING
Solar/Wind Harmer
0.081
3142433PROV 92
Solar/Wind Harmer
-0.106
3142433PROV 92
Adder
0.459
3142433PROV 92
Adder
0.459
961611AG1-000B GEN
Solar/Wind Harmer
13.094
316294AC1-161 GEN
Solar/Wind Harmer
8.555
3151171GRAVELC
Adder
2.504
3145336SMITFLD
Solar/Wind Harmer
-0.105
970659AG2-427 GEN
Solar/Wind Harmer
13.9
944591AF1-124 GEN
Solar/Wind Harmer
119.31
316375AC2-012 GEN
Solar/Wind Harmer
9.042
3150981CHESPKA
Adder
2.903
316381AD1-082 GEN
Solar/Wind Harmer
2.397
3141766HARMONY
Solar/Wind Harmer
-0.005
970661AG2-428 GEN
Solar/Wind Harmer
27.675
971777AH1-397 GEN
Solar/Wind Harmer
3.061
3141843SHACKLE
Adder
1.184
316072AD1-144
Solar/Wind Harmer
0.525
939411AE1-173 GEN
Solar/Wind Harmer
129.681
940641AE2-051 GEN
Solar/Wind Harmer
24.285
316388AE2-253 GEN
Solar/Wind Harmer
1.746
3146456SLIGO L269
Solar/Wind Harmer
-0.026
316246AF1-032 C
Solar/Wind Harmer
0.521
316093AE2-104_GEN
Solar/Wind Harmer
7.454
3138133OCRAN
Solar/Wind Harmer
-0.015
3146516WINFALL
Solar/Wind Harmer
-0.081
3146516WINFALL
Solar/Wind Harmer
-0.025
315800Z1-036_GEN1
Solar/Wind Harmer
6.129
961951AG1-038 GEN
Solar/Wind Harmer
3.258
3130156CHOWAN
Solar/Wind Harmer
-0.024
962861AG1-135 GEN
Solar/Wind Harmer
9.184
964211AG1-282 GEN
Solar/Wind Harmer
0.725
3141726DUNNSVL
Solar/Wind Harmer
-0.096
3145663CRESWEL
Solar/Wind Harmer
-0.067
971163AH1-040 GEN
Solar/Wind Harmer
22.455
3150351NORNECKC2
Adder
2.113
3143336POWHATN
Solar/Wind Harmer
2.81
970919AG2-571 GEN
Solar/Wind Harmer
7.352
3146206CASHIE
Solar/Wind Harmer
-0.023
971547AH1-271 GEN
Solar/Wind Harmer
5.801
316023GEN1_S
Solar/Wind Harmer
1.562
970087AG2-069 GEN
Solar/Wind Harmer
21.693
3145893MURPHYS
Solar/Wind Harmer
-0.092
3145893MURPHYS
Solar/Wind Harmer
0.686
3146173TUNIS
Solar/Wind Harmer
-0.023
316337AD2-073 GEN
Solar/Wind Harmer
0.613
316336AC2-165 C
Solar/Wind Harmer
3.944
3145683EARLEYS
Solar/Wind Harmer
-0.023
3147666LOUISA
Solar/Wind Harmer
-0.09
960081AF2-299 GEN
Solar/Wind Harmer
2.538
3146263WOODLND
Solar/Wind Harmer
-0.022
3145963POPLR C
Solar/Wind Harmer
-0.022
957481AF2-042 GEN
Solar/Wind Harmer
69.556
316011AB1-132 GEN
Solar/Wind Harmer
4.65
962571AG1-106 GEN
Solar/Wind Harmer
3.195
3145823KELFORD
Solar/Wind Harmer
-0.022
316190AA2-174 GEN
Solar/Wind Harmer
0.272
316174AB2-169 GEN
Solar/Wind Harmer
3.411
316192AB2-158 GEN
Solar/Wind Harmer
2.63
971795AH1-408 GEN
Solar/Wind Harmer
16.551
3145783HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.072
3145796HORNRTN
Solar/Wind Harmer
-0.022
315693AD1-088 GEN
Solar/Wind Harmer
10.925
3147043LAWRENC
Adder
1.759
3144293JTRSVLE
Adder
0.567
972277AH1-723 GEN
Adder
98.358
3151751LOISA D
Adder
8.045
962491AG1-098 GEN
Solar/Wind Harmer
13.869
3150391LDYSMT3
50/50
37.173
972195AH1-682 GEN
50/50
4.885
316447AC1-158 HLD
Solar/Wind Harmer
7.576
315673AE1-157 GEN
Solar/Wind Harmer
21.908
957411AF2-035 GEN
Solar/Wind Harmer
13.095
970317AG2-208 GEN
Solar/Wind Harmer
12.731
3142296MT RD221
Adder
0.803
3142366NRTHEST
Adder
0.809
3150691DARBY 3
Adder
17.769
3150701DARBY 4
Adder
17.728
3150681DARBY 2
Adder
17.707
3150671DARBY 1
Adder
17.686
3143526WINTERP
Solar/Wind Harmer
-0.142
316075AC2-137 C
Solar/Wind Harmer
0.742
971223AH1-071 GEN
Solar/Wind Harmer
3.429
966871AG1-558 GEN
Solar/Wind Harmer
0.822
966871AG1-558 GEN
Solar/Wind Harmer
0.281
3142946ENON
Solar/Wind Harmer
-0.003
944641AF1-129 GEN
Adder
114.617
316240AF1-291 C
Solar/Wind Harmer
0.812
316033AB2-134 GEN
Solar/Wind Harmer
8.601
315697AD1-025 GEN
Solar/Wind Harmer
5.395
316236AE1-162_GEN
Solar/Wind Harmer
0.793
316036AC1-147 C
Solar/Wind Harmer
0.705
3150991CHESPKB
Adder
2.436
3150991CHESPKB
Adder
2.377
970657AG2-426 GEN
Solar/Wind Harmer
8.157
970657AG2-426 GEN
Solar/Wind Harmer
1.706
316316AC1-027 C
Solar/Wind Harmer
0.8
3142956BIRDNECK
Solar/Wind Harmer
1.399
316185AD1-033 GEN
Solar/Wind Harmer
2.747
316441AF1-014 GEN
Solar/Wind Harmer
1.755
3145506HICKORY
Solar/Wind Harmer
-0.103
3145506HICKORY
Solar/Wind Harmer
-0.062
3145506HICKORY
Solar/Wind Harmer
-0.015
316339AD2-160 GEN
Solar/Wind Harmer
1.746
316018AA1-139 ULT2
Solar/Wind Harmer
2.216
316017AA1-139 ULT1
Solar/Wind Harmer
2.093
3137176SLIGO L2192
Solar/Wind Harmer
-0.102
3146456SLIGO L269
Solar/Wind Harmer
3.048
3130086AYDLETT
Solar/Wind Harmer
-0.103
3146386ELIZ CT
Solar/Wind Harmer
-0.025
316431W1029_GEN1
Solar/Wind Harmer
4.579
316433W1029_GEN2
Solar/Wind Harmer
4.579
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3144356SAPONY
Solar/Wind Harmer
0.872
316487AF1-042 GEN
Solar/Wind Harmer
3.258
315742AE1-103 GEN
Solar/Wind Harmer
2.575
3146376EDENTON
Solar/Wind Harmer
0.727
3146376EDENTON
Solar/Wind Harmer
0.727
958261AF2-120 GEN
Solar/Wind Harmer
9.456
972185AH1-677 GEN
Adder
12.155
972187AH1-678 GEN
Adder
6.099
316077AC2-138 C
Solar/Wind Harmer
0.502
3150341NORNECKC1
Adder
2.219
3150341NORNECKC1
Adder
2.201
316468AD1-105 GEN
Solar/Wind Harmer
2.65
970933AG2-581 GEN
Solar/Wind Harmer
22.22
316065AD1-022 GEN
Solar/Wind Harmer
11.648
3145893MURPHYS
Solar/Wind Harmer
0.645
3145893MURPHYS
Solar/Wind Harmer
-0.042
3146173TUNIS
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.023
316181AB2-040 GEN
Solar/Wind Harmer
3.112
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
970099AG2-077 GEN
Solar/Wind Harmer
27.822
316426AA2-053 GEN
Solar/Wind Harmer
2.237
3145593CAROLNA
Solar/Wind Harmer
-0.022
3145593CAROLNA
Solar/Wind Harmer
-0.022
966811AG1-552 GEN
Solar/Wind Harmer
2.478
3145593CAROLNA
Solar/Wind Harmer
0.183
3145783HORNRTN
Solar/Wind Harmer
2.599
3145783HORNRTN
Solar/Wind Harmer
2.079
3145783HORNRTN
Solar/Wind Harmer
0.65
3145783HORNRTN
Solar/Wind Harmer
0.26
3145796HORNRTN
Solar/Wind Harmer
-0.065
3144293JTRSVLE
Adder
0.567
3144293JTRSVLE
Adder
0.477
3151731LOISA B
Adder
8.045
3151721LOISA A
Adder
8.003
3152261N ANNA2
50/50
14.574
970497AG2-320 GEN
50/50
26.212
3150401LDYSMT4
50/50
37.242
3150371LDYSMT1
50/50
35.986
315051AA1-145 CT1
50/50
2.029
316044AC1-158 PL1
Solar/Wind Harmer
3.445
316450AC1-158 RIC
Solar/Wind Harmer
0.919
966881AG1-559 GEN
Solar/Wind Harmer
0.875
3142416OLDCHRC
Solar/Wind Harmer
2.824
970293AG2-193 GEN
Solar/Wind Harmer
3.455
3143096IRON208
Adder
1.024
3143096IRON208
Adder
1.004
3150861SPRUNCD
Adder
1.127
316473AC1-191 GEN
Solar/Wind Harmer
2.94
3142946ENON
Solar/Wind Harmer
-0.009
970133AG2-095 GEN
Solar/Wind Harmer
3.033
316382AG1-145 C
Solar/Wind Harmer
0.809
970129AG2-093 GEN
Solar/Wind Harmer
15.103
315778AD1-151 GEN
Solar/Wind Harmer
23.155
965281AG1-393 GEN
Solar/Wind Harmer
3.341
315839AE2-212 C
Solar/Wind Harmer
0.805
3150921YORKTN3
Adder
5.937
3144216WINCHST
Adder
0.89
3142433PROV 92
Adder
0.459
3142433PROV 92
Adder
0.459
961611AG1-000B GEN
Solar/Wind Harmer
5.587
315773AC2-141 GEN
Solar/Wind Harmer
11.065
3151221GRAVEL6
Adder
17.112
3151171GRAVELC
Adder
3.292
3145336SMITFLD
Solar/Wind Harmer
-0.01
315813AE1-149 C
Solar/Wind Harmer
16.456
3144536CHRHLND
Solar/Wind Harmer
-0.004
970659AG2-427 GEN
Solar/Wind Harmer
2.463
944581AF1-123 GEN
Solar/Wind Harmer
118.881
944601AF1-125 GEN
Solar/Wind Harmer
117.026
3151101ELIZAR3
Adder
21.596
316083AB2-161 GEN
Solar/Wind Harmer
4.242
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3141766HARMONY
Solar/Wind Harmer
2.318
970661AG2-428 GEN
Solar/Wind Harmer
4.904
3141843SHACKLE
Adder
1.184
316203AE2-005 GEN
Solar/Wind Harmer
10.974
316280AD1-041 GEN
Solar/Wind Harmer
1.955
316156AD2-030 GEN
Solar/Wind Harmer
0.69
3141873WAN 176
Solar/Wind Harmer
3.066
3146456SLIGO L269
Solar/Wind Harmer
-0.026
971153AH1-033 GEN
Solar/Wind Harmer
3.146
316320Y1-086
Solar/Wind Harmer
1.497
316435W1029_GEN3
Solar/Wind Harmer
4.579
3146516WINFALL
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3145273HOLLAND
Solar/Wind Harmer
-0.019
962971AG1-146 GEN
Solar/Wind Harmer
4.675
316484AD2-074 GEN
Solar/Wind Harmer
6.226
970009AG2-005 GEN
Solar/Wind Harmer
3.091
3146376EDENTON
Solar/Wind Harmer
-0.024
316404AE1-155 C
Solar/Wind Harmer
4.707
315614AA2-178 GEN
Solar/Wind Harmer
2.584
3150351NORNECKC2
Adder
2.148
971781AH1-399 GEN
Solar/Wind Harmer
1.466
316313AB2-026
Solar/Wind Harmer
0.639
316258AE1-075 C
Solar/Wind Harmer
0.575
316405AF2-144 C
Solar/Wind Harmer
0.607
3143336POWHATN
Solar/Wind Harmer
2.388
971157AH1-035 GEN
Solar/Wind Harmer
2.941
315737AD1-076 GEN
Solar/Wind Harmer
4.458
3156081AA2-088 GEN
Solar/Wind Harmer
7.605
970917AG2-570 GEN
Solar/Wind Harmer
58.079
3146206CASHIE
Solar/Wind Harmer
-0.023
316365GEN2_N
Solar/Wind Harmer
1.562
3145893MURPHYS
Solar/Wind Harmer
0.161
3145893MURPHYS
Solar/Wind Harmer
-0.023
957521AF2-046 GEN
Solar/Wind Harmer
18.15
961681AG1-008 GEN
Solar/Wind Harmer
18.15
3146173TUNIS
Solar/Wind Harmer
-0.023
3156021HOLLOMANSOL
Solar/Wind Harmer
3.079
316463AE2-346 GEN
Solar/Wind Harmer
0.369
316140AB2-099
Solar/Wind Harmer
0.154
962331AG1-082 GEN
Solar/Wind Harmer
2.847
3147666LOUISA
Solar/Wind Harmer
-0.052
966621AG1-532 GEN
Solar/Wind Harmer
0.458
3146263WOODLND
Solar/Wind Harmer
-0.022
3145963POPLR C
Solar/Wind Harmer
-0.022
313506AB2-031 GEN
Solar/Wind Harmer
1.793
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
316317KELFORD C
Solar/Wind Harmer
1.047
3145823KELFORD
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.087
3145796HORNRTN
Solar/Wind Harmer
-0.022
3147043LAWRENC
Solar/Wind Harmer
-0.013
3144293JTRSVLE
Adder
0.567
972255AH1-712 GEN
Adder
84.405
3141316ARNOLDS
Adder
0.324
3150331BIRCHWDA
Adder
21.284
3151761LOISA E
Adder
16.401
972183AH1-676 GEN
Adder
128.361
3141196NOKESVL
Solar/Wind Helper
1.252
NYPJM->LTFIMP_NY
CLTF
3.26
LGEELTFEXP_LGEE->PJM
CLTF
1.336
WECLTFEXP_WEC->PJM
CLTF
0.644
LAGNLTFEXP_LAGN->PJM
CLTF
8.027
CBM South 2LTFEXP_CBM-S2->PJM
CBM
24.997
TVALTFEXP_TVA->PJM
CLTF
4.071
CBM West 1LTFEXP_CBM-W1->PJM
CBM
21.421
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.849
MECLTFEXP_MEC->PJM
CLTF
3.625
SIGELTFEXP_SIGE->PJM
CLTF
0.111
CPLELTFEXP_CPLE->PJM
CLTF
11.39
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.441

Details for 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T594_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 515T594_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.36 %
Rating:5010.0 MVA
Rating Type:C
MVA to Mitigate:5679.37
MW Contribution:98.37
Bus #Bus NameTypeMW Contribution
971531AH1-263 GEN
50/50
86.379
3150411LDYSMT5
50/50
37.362
3150381LDYSMT2
50/50
35.757
972213AH1-691 GEN
50/50
6.049
972215AH1-692 GEN
50/50
6.049
963051AG1-154 GEN
50/50
4.653
972189AH1-679 GEN
Adder
4.288
316312AB1-027
Solar/Wind Harmer
0.944
316233AE1-074 FULL
Solar/Wind Harmer
0.74
971281AH1-106 GEN
Solar/Wind Harmer
4.473
971283AH1-107 GEN
Solar/Wind Harmer
4.473
971285AH1-108 GEN
Adder
1.844
315976AC1-164 GENA
Solar/Wind Harmer
28.849
316169AC1-164_GENC
Solar/Wind Harmer
24.922
315975AC1-164 GENB
Solar/Wind Harmer
0.854
316164AC1-076 GEN
Solar/Wind Harmer
2.296
316132AB2-190 GEN1
Solar/Wind Harmer
2.712
316369SG1_INVT
Solar/Wind Harmer
4.766
971167AH1-042 GEN
Solar/Wind Harmer
25.599
3142433PROV 92
Adder
0.459
3142433PROV 92
Adder
0.459
972265AH1-717 GEN
Adder
18.278
971507AH1-251 GEN
50/50
17.73
3152251N ANNA1
50/50
14.579
972197AH1-683 GEN
50/50
5.816
972219AH1-694 GEN
50/50
4.188
315052AA1-145 CT2
50/50
2.039
316045AC1-158 PL2
Solar/Wind Harmer
11.027
966881AG1-559 GEN
Solar/Wind Harmer
0.299
3142416OLDCHRC
Solar/Wind Harmer
-0.072
3142416OLDCHRC
Solar/Wind Harmer
-0.028
3143526WINTERP
Solar/Wind Harmer
-0.142
3143096IRON208
Adder
1.025
3150851SPRUNCC
Adder
1.127
3143226MDLTHAN
Solar/Wind Harmer
-0.027
3142543TWELFTH
Solar/Wind Harmer
-0.003
944631AF1-128 GEN
Adder
115.654
316159AE1-175 C
Solar/Wind Harmer
0.72
970129AG2-093 GEN
Solar/Wind Harmer
6.119
316458AB2-190 GEN2
Solar/Wind Harmer
2.712
3150391LDYSMT3
50/50
37.176
972195AH1-682 GEN
50/50
4.885
316447AC1-158 HLD
Solar/Wind Harmer
7.58
315673AE1-157 GEN
Solar/Wind Harmer
21.91
957411AF2-035 GEN
Solar/Wind Harmer
13.096
970317AG2-208 GEN
Solar/Wind Harmer
12.732
3142296MT RD221
Adder
0.803
3142366NRTHEST
Adder
0.809
3150691DARBY 3
Adder
17.772
3150701DARBY 4
Adder
17.73
3150681DARBY 2
Adder
17.71
3150671DARBY 1
Adder
17.689
3143526WINTERP
Solar/Wind Harmer
-0.142
316075AC2-137 C
Solar/Wind Harmer
0.742
971223AH1-071 GEN
Solar/Wind Harmer
3.429
966871AG1-558 GEN
Solar/Wind Harmer
0.822
966871AG1-558 GEN
Solar/Wind Harmer
0.281
3142946ENON
Solar/Wind Harmer
-0.003
944641AF1-129 GEN
Adder
114.635
316240AF1-291 C
Solar/Wind Harmer
0.812
316033AB2-134 GEN
Solar/Wind Harmer
8.603
315697AD1-025 GEN
Solar/Wind Harmer
5.395
316236AE1-162_GEN
Solar/Wind Harmer
0.794
316036AC1-147 C
Solar/Wind Harmer
0.705
3150991CHESPKB
Adder
2.436
3150991CHESPKB
Adder
2.378
970657AG2-426 GEN
Solar/Wind Harmer
8.158
970657AG2-426 GEN
Solar/Wind Harmer
1.706
316316AC1-027 C
Solar/Wind Harmer
0.801
3142956BIRDNECK
Solar/Wind Harmer
1.399
316185AD1-033 GEN
Solar/Wind Harmer
2.747
316441AF1-014 GEN
Solar/Wind Harmer
1.755
3145506HICKORY
Solar/Wind Harmer
-0.103
3145506HICKORY
Solar/Wind Harmer
-0.062
3145506HICKORY
Solar/Wind Harmer
-0.015
316339AD2-160 GEN
Solar/Wind Harmer
1.746
316018AA1-139 ULT2
Solar/Wind Harmer
2.216
316017AA1-139 ULT1
Solar/Wind Harmer
2.093
3137176SLIGO L2192
Solar/Wind Harmer
-0.102
3146456SLIGO L269
Solar/Wind Harmer
3.049
3130086AYDLETT
Solar/Wind Harmer
-0.103
3146386ELIZ CT
Solar/Wind Harmer
-0.025
316431W1029_GEN1
Solar/Wind Harmer
4.579
316433W1029_GEN2
Solar/Wind Harmer
4.579
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3144356SAPONY
Solar/Wind Harmer
0.872
316487AF1-042 GEN
Solar/Wind Harmer
3.258
315742AE1-103 GEN
Solar/Wind Harmer
2.576
3146376EDENTON
Solar/Wind Harmer
0.727
3146376EDENTON
Solar/Wind Harmer
0.727
958261AF2-120 GEN
Solar/Wind Harmer
9.457
972185AH1-677 GEN
Adder
12.157
972187AH1-678 GEN
Adder
6.1
316077AC2-138 C
Solar/Wind Harmer
0.502
3150341NORNECKC1
Adder
2.219
3150341NORNECKC1
Adder
2.202
316468AD1-105 GEN
Solar/Wind Harmer
2.65
970933AG2-581 GEN
Solar/Wind Harmer
22.224
316065AD1-022 GEN
Solar/Wind Harmer
11.65
3145893MURPHYS
Solar/Wind Harmer
0.645
3145893MURPHYS
Solar/Wind Harmer
-0.042
3146173TUNIS
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.023
316181AB2-040 GEN
Solar/Wind Harmer
3.112
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
970099AG2-077 GEN
Solar/Wind Harmer
27.827
316426AA2-053 GEN
Solar/Wind Harmer
2.237
3145593CAROLNA
Solar/Wind Harmer
-0.022
3145593CAROLNA
Solar/Wind Harmer
-0.022
966811AG1-552 GEN
Solar/Wind Harmer
2.479
3145593CAROLNA
Solar/Wind Harmer
0.183
3145783HORNRTN
Solar/Wind Harmer
2.599
3145783HORNRTN
Solar/Wind Harmer
2.079
3145783HORNRTN
Solar/Wind Harmer
0.65
3145783HORNRTN
Solar/Wind Harmer
0.26
3145796HORNRTN
Solar/Wind Harmer
-0.065
3144293JTRSVLE
Adder
0.567
3144293JTRSVLE
Adder
0.477
3151731LOISA B
Adder
8.04
3151721LOISA A
Adder
7.998
3151201GRAVEL4
Adder
17.134
3151191GRAVEL3
Adder
16.917
3151211GRAVEL5
Adder
16.917
971445AH1-216 GEN
Solar/Wind Harmer
16.302
3143316POE
Solar/Wind Harmer
-0.103
3143873LANEXA
Solar/Wind Harmer
-0.016
957831AF2-077 GEN
Solar/Wind Harmer
0.788
3138283WHITEMARSH
Solar/Wind Harmer
0.041
316314AB2-024 C
Solar/Wind Harmer
2.238
3151081ELIZAR1
Adder
21.327
3151091ELIZAR2
Adder
20.956
3152611GOSPORTB
Adder
2.962
3152621GOSPORTC
Adder
2.514
3152601GOSPORTA
Adder
2.319
316059AD1-063 C
Solar/Wind Harmer
0.589
315662AE1-191 GEN
Solar/Wind Harmer
3.128
315666AE1-190 GEN
Solar/Wind Harmer
0.782
957871AF2-081 GEN
Solar/Wind Harmer
12.934
957601AF2-054 GEN
Solar/Wind Harmer
0.773
3141873WAN 176
Solar/Wind Harmer
-0.005
315833AF1-017_GEN
Solar/Wind Harmer
4.906
316349AD2-085 GEN
Solar/Wind Harmer
2.297
316311AC2-079 GEN
Solar/Wind Harmer
13.027
319010AE1-072 C
Solar/Wind Harmer
5.218
3146406KITTY HAWK
Solar/Wind Harmer
0.021
316305AF2-043 C
Solar/Wind Harmer
0.777
315835AF2-110_GEN
Solar/Wind Harmer
3.205
313526AB2-022
Solar/Wind Harmer
0.689
3141913WHIT STONE
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
3138133OCRAN
Solar/Wind Harmer
-0.008
316321Z2-027
Solar/Wind Harmer
0.686
3146396TANGLEW
Solar/Wind Harmer
0.468
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
316315AB2-025 C
Solar/Wind Harmer
0.674
941031AE2-094 GEN
Solar/Wind Harmer
46.799
944011AF1-069 GEN
Solar/Wind Harmer
14.664
962981AG1-147 GEN
Solar/Wind Harmer
10.911
315814AE2-033 C
Solar/Wind Harmer
23.194
315611Z1-036_GEN2
Solar/Wind Harmer
6.13
970673AG2-436 GEN
Solar/Wind Harmer
51.571
970673AG2-436 GEN
Solar/Wind Harmer
26.112
3130156CHOWAN
Solar/Wind Harmer
-0.024
3130156CHOWAN
Solar/Wind Harmer
-0.024
971967AH1-528 GEN
Solar/Wind Harmer
45.606
315816AE2-034 GEN
Solar/Wind Harmer
1.938
3141813NORNECK
Solar/Wind Harmer
-0.024
3130546PLYMOUTH
Solar/Wind Harmer
-0.023
315732AD1-074 GEN1
Solar/Wind Harmer
4.744
315733AD1-074 GEN2
Solar/Wind Harmer
4.744
315735AD1-075 GEN1
Solar/Wind Harmer
2.373
965291AG1-394 GEN
Solar/Wind Harmer
2.07
3146206CASHIE
Solar/Wind Harmer
-0.023
970601AG2-382 GEN
Solar/Wind Harmer
10.154
970085AG2-068 GEN
Solar/Wind Harmer
14.465
970581AG2-369 GEN
Solar/Wind Harmer
12.44
316318V4-068
Solar/Wind Harmer
0.576
3145893MURPHYS
Solar/Wind Harmer
-0.062
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145513AHOSKIE
Solar/Wind Harmer
0.199
961941AG1-037 GEN
Solar/Wind Harmer
0.171
3145513AHOSKIE
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.045
3145683EARLEYS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
3146043SEABORD
Solar/Wind Harmer
-0.023
946281AF1-292 GEN
Solar/Wind Harmer
0.505
315607AA1-063A GEN
Solar/Wind Harmer
2.277
316087AB2-174 GEN
Solar/Wind Harmer
3.194
315652AC1-086 GEN
Solar/Wind Harmer
25.006
3137643SOCKMAN
Solar/Wind Harmer
-0.088
3145796HORNRTN
Solar/Wind Harmer
-0.07
3145796HORNRTN
Solar/Wind Harmer
-0.009
972193AH1-681 GEN
Adder
3.772
972205AH1-687 GEN
Adder
6.859
316411AF1-147_GEN1
Solar/Wind Helper
0.807
316415AF1-147_GEN2
Solar/Wind Helper
0.807
3138216PACIFIC
Solar/Wind Helper
0.039
3152261N ANNA2
50/50
14.578
970497AG2-320 GEN
50/50
26.215
3150401LDYSMT4
50/50
37.246
3150371LDYSMT1
50/50
35.99
315051AA1-145 CT1
50/50
2.03
316044AC1-158 PL1
Solar/Wind Harmer
3.447
316450AC1-158 RIC
Solar/Wind Harmer
0.919
966881AG1-559 GEN
Solar/Wind Harmer
0.875
3142416OLDCHRC
Solar/Wind Harmer
2.824
970293AG2-193 GEN
Solar/Wind Harmer
3.455
3143096IRON208
Adder
1.025
3143096IRON208
Adder
1.004
3150861SPRUNCD
Adder
1.127
316473AC1-191 GEN
Solar/Wind Harmer
2.941
3142946ENON
Solar/Wind Harmer
-0.009
970133AG2-095 GEN
Solar/Wind Harmer
3.033
316382AG1-145 C
Solar/Wind Harmer
0.809
970129AG2-093 GEN
Solar/Wind Harmer
15.106
315778AD1-151 GEN
Solar/Wind Harmer
23.159
965281AG1-393 GEN
Solar/Wind Harmer
3.342
315839AE2-212 C
Solar/Wind Harmer
0.805
3150921YORKTN3
Adder
5.938
3144216WINCHST
Adder
0.891
3142433PROV 92
Adder
0.459
3142433PROV 92
Adder
0.459
961611AG1-000B GEN
Solar/Wind Harmer
5.588
315773AC2-141 GEN
Solar/Wind Harmer
11.067
3151221GRAVEL6
Adder
17.114
3151171GRAVELC
Adder
3.293
3145336SMITFLD
Solar/Wind Harmer
-0.01
315813AE1-149 C
Solar/Wind Harmer
16.458
3144536CHRHLND
Solar/Wind Harmer
-0.004
970659AG2-427 GEN
Solar/Wind Harmer
2.464
944581AF1-123 GEN
Solar/Wind Harmer
118.901
944601AF1-125 GEN
Solar/Wind Harmer
117.045
3151101ELIZAR3
Adder
21.599
316083AB2-161 GEN
Solar/Wind Harmer
4.242
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3141766HARMONY
Solar/Wind Harmer
2.319
970661AG2-428 GEN
Solar/Wind Harmer
4.905
3141843SHACKLE
Adder
1.184
316203AE2-005 GEN
Solar/Wind Harmer
10.976
316280AD1-041 GEN
Solar/Wind Harmer
1.955
316156AD2-030 GEN
Solar/Wind Harmer
0.69
3141873WAN 176
Solar/Wind Harmer
3.067
3146456SLIGO L269
Solar/Wind Harmer
-0.026
971153AH1-033 GEN
Solar/Wind Harmer
3.147
316320Y1-086
Solar/Wind Harmer
1.497
316435W1029_GEN3
Solar/Wind Harmer
4.579
3146516WINFALL
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3145273HOLLAND
Solar/Wind Harmer
-0.019
962971AG1-146 GEN
Solar/Wind Harmer
4.676
316484AD2-074 GEN
Solar/Wind Harmer
6.227
970009AG2-005 GEN
Solar/Wind Harmer
3.092
3146376EDENTON
Solar/Wind Harmer
-0.024
316404AE1-155 C
Solar/Wind Harmer
4.708
315614AA2-178 GEN
Solar/Wind Harmer
2.585
3150351NORNECKC2
Adder
2.148
971781AH1-399 GEN
Solar/Wind Harmer
1.466
316313AB2-026
Solar/Wind Harmer
0.639
316258AE1-075 C
Solar/Wind Harmer
0.575
316405AF2-144 C
Solar/Wind Harmer
0.607
3143336POWHATN
Solar/Wind Harmer
2.389
971157AH1-035 GEN
Solar/Wind Harmer
2.942
315737AD1-076 GEN
Solar/Wind Harmer
4.458
3156081AA2-088 GEN
Solar/Wind Harmer
7.606
970917AG2-570 GEN
Solar/Wind Harmer
58.089
3146206CASHIE
Solar/Wind Harmer
-0.023
316365GEN2_N
Solar/Wind Harmer
1.562
3145893MURPHYS
Solar/Wind Harmer
0.161
3145893MURPHYS
Solar/Wind Harmer
-0.023
957521AF2-046 GEN
Solar/Wind Harmer
18.153
961681AG1-008 GEN
Solar/Wind Harmer
18.153
3146173TUNIS
Solar/Wind Harmer
-0.023
3156021HOLLOMANSOL
Solar/Wind Harmer
3.079
316463AE2-346 GEN
Solar/Wind Harmer
0.369
316140AB2-099
Solar/Wind Harmer
0.154
962331AG1-082 GEN
Solar/Wind Harmer
2.847
3147666LOUISA
Solar/Wind Harmer
-0.052
966621AG1-532 GEN
Solar/Wind Harmer
0.458
3146263WOODLND
Solar/Wind Harmer
-0.022
3145963POPLR C
Solar/Wind Harmer
-0.022
313506AB2-031 GEN
Solar/Wind Harmer
1.793
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
316317KELFORD C
Solar/Wind Harmer
1.047
3145823KELFORD
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.087
3145796HORNRTN
Solar/Wind Harmer
-0.022
3147043LAWRENC
Solar/Wind Harmer
-0.013
3144293JTRSVLE
Adder
0.567
972255AH1-712 GEN
Adder
84.412
3141316ARNOLDS
Adder
0.324
3150331BIRCHWDA
Adder
21.287
3151761LOISA E
Adder
16.391
972183AH1-676 GEN
Adder
128.276
3141196NOKESVL
Solar/Wind Helper
1.252
315671AE2-027_GEN
Solar/Wind Harmer
20.092
971069AG2-661 GEN
Solar/Wind Harmer
4.23
971647AH1-324 GEN
Solar/Wind Harmer
13.303
971317AH1-138 GEN
Solar/Wind Harmer
3.32
3138126ROCKLANDING
Solar/Wind Harmer
0.081
3142433PROV 92
Solar/Wind Harmer
-0.106
3142433PROV 92
Adder
0.459
3142433PROV 92
Adder
0.459
961611AG1-000B GEN
Solar/Wind Harmer
13.096
316294AC1-161 GEN
Solar/Wind Harmer
8.557
3151171GRAVELC
Adder
2.504
3145336SMITFLD
Solar/Wind Harmer
-0.105
970659AG2-427 GEN
Solar/Wind Harmer
13.903
944591AF1-124 GEN
Solar/Wind Harmer
119.329
316375AC2-012 GEN
Solar/Wind Harmer
9.043
3150981CHESPKA
Adder
2.904
316381AD1-082 GEN
Solar/Wind Harmer
2.397
3141766HARMONY
Solar/Wind Harmer
-0.005
970661AG2-428 GEN
Solar/Wind Harmer
27.679
971777AH1-397 GEN
Solar/Wind Harmer
3.061
3141843SHACKLE
Adder
1.184
316072AD1-144
Solar/Wind Harmer
0.525
939411AE1-173 GEN
Solar/Wind Harmer
129.703
940641AE2-051 GEN
Solar/Wind Harmer
24.29
316388AE2-253 GEN
Solar/Wind Harmer
1.746
3146456SLIGO L269
Solar/Wind Harmer
-0.026
316246AF1-032 C
Solar/Wind Harmer
0.521
316093AE2-104_GEN
Solar/Wind Harmer
7.455
3138133OCRAN
Solar/Wind Harmer
-0.015
3146516WINFALL
Solar/Wind Harmer
-0.081
3146516WINFALL
Solar/Wind Harmer
-0.025
315800Z1-036_GEN1
Solar/Wind Harmer
6.13
961951AG1-038 GEN
Solar/Wind Harmer
3.258
3130156CHOWAN
Solar/Wind Harmer
-0.024
962861AG1-135 GEN
Solar/Wind Harmer
9.185
964211AG1-282 GEN
Solar/Wind Harmer
0.726
3141726DUNNSVL
Solar/Wind Harmer
-0.096
3145663CRESWEL
Solar/Wind Harmer
-0.067
971163AH1-040 GEN
Solar/Wind Harmer
22.459
3150351NORNECKC2
Adder
2.113
3143336POWHATN
Solar/Wind Harmer
2.81
970919AG2-571 GEN
Solar/Wind Harmer
7.353
3146206CASHIE
Solar/Wind Harmer
-0.023
971547AH1-271 GEN
Solar/Wind Harmer
5.802
316023GEN1_S
Solar/Wind Harmer
1.562
970087AG2-069 GEN
Solar/Wind Harmer
21.697
3145893MURPHYS
Solar/Wind Harmer
-0.092
3145893MURPHYS
Solar/Wind Harmer
0.686
3146173TUNIS
Solar/Wind Harmer
-0.023
316337AD2-073 GEN
Solar/Wind Harmer
0.613
316336AC2-165 C
Solar/Wind Harmer
3.944
3145683EARLEYS
Solar/Wind Harmer
-0.023
3147666LOUISA
Solar/Wind Harmer
-0.09
960081AF2-299 GEN
Solar/Wind Harmer
2.538
3146263WOODLND
Solar/Wind Harmer
-0.022
3145963POPLR C
Solar/Wind Harmer
-0.022
957481AF2-042 GEN
Solar/Wind Harmer
69.568
316011AB1-132 GEN
Solar/Wind Harmer
4.65
962571AG1-106 GEN
Solar/Wind Harmer
3.195
3145823KELFORD
Solar/Wind Harmer
-0.022
316190AA2-174 GEN
Solar/Wind Harmer
0.272
316174AB2-169 GEN
Solar/Wind Harmer
3.412
316192AB2-158 GEN
Solar/Wind Harmer
2.63
971795AH1-408 GEN
Solar/Wind Harmer
16.554
3145783HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.072
3145796HORNRTN
Solar/Wind Harmer
-0.022
315693AD1-088 GEN
Solar/Wind Harmer
10.927
3147043LAWRENC
Adder
1.759
3144293JTRSVLE
Adder
0.567
972277AH1-723 GEN
Adder
98.366
3151751LOISA D
Adder
8.04
962491AG1-098 GEN
Solar/Wind Harmer
13.871
NYPJM->LTFIMP_NY
CLTF
3.261
LGEELTFEXP_LGEE->PJM
CLTF
1.336
WECLTFEXP_WEC->PJM
CLTF
0.644
LAGNLTFEXP_LAGN->PJM
CLTF
8.029
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.001
TVALTFEXP_TVA->PJM
CLTF
4.071
CBM West 1LTFEXP_CBM-W1->PJM
CBM
21.423
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.85
MECLTFEXP_MEC->PJM
CLTF
3.626
SIGELTFEXP_SIGE->PJM
CLTF
0.111
CPLELTFEXP_CPLE->PJM
CLTF
11.392
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.447

Details for 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T573_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.05 %
Rating:5010.0 MVA
Rating Type:C
MVA to Mitigate:5563.76
MW Contribution:98.9
Bus #Bus NameTypeMW Contribution
3150391LDYSMT3
50/50
37.301
972195AH1-682 GEN
50/50
4.902
315673AE1-157 GEN
Solar/Wind Harmer
21.984
957411AF2-035 GEN
Solar/Wind Harmer
13.14
970317AG2-208 GEN
Solar/Wind Harmer
12.775
3142296MT RD221
Adder
0.806
3142366NRTHEST
Adder
0.811
3150691DARBY 3
Adder
17.834
3150701DARBY 4
Adder
17.793
3150681DARBY 2
Adder
17.772
3150671DARBY 1
Adder
17.751
3143526WINTERP
Solar/Wind Harmer
-0.143
316075AC2-137 C
Solar/Wind Harmer
0.745
971223AH1-071 GEN
Solar/Wind Harmer
3.441
966871AG1-558 GEN
Solar/Wind Harmer
0.825
966871AG1-558 GEN
Solar/Wind Harmer
0.282
3142946ENON
Solar/Wind Harmer
-0.003
944641AF1-129 GEN
Adder
115.049
316240AF1-291 C
Solar/Wind Harmer
0.815
316033AB2-134 GEN
Solar/Wind Harmer
8.634
315697AD1-025 GEN
Solar/Wind Harmer
5.415
316236AE1-162_GEN
Solar/Wind Harmer
0.797
316036AC1-147 C
Solar/Wind Harmer
0.708
3150991CHESPKB
Adder
2.445
3150991CHESPKB
Adder
2.387
970657AG2-426 GEN
Solar/Wind Harmer
8.189
970657AG2-426 GEN
Solar/Wind Harmer
1.712
316316AC1-027 C
Solar/Wind Harmer
0.804
3142956BIRDNECK
Solar/Wind Harmer
1.405
316185AD1-033 GEN
Solar/Wind Harmer
2.758
316441AF1-014 GEN
Solar/Wind Harmer
1.761
3145506HICKORY
Solar/Wind Harmer
-0.104
3145506HICKORY
Solar/Wind Harmer
-0.062
3145506HICKORY
Solar/Wind Harmer
-0.015
316339AD2-160 GEN
Solar/Wind Harmer
1.753
316018AA1-139 ULT2
Solar/Wind Harmer
2.224
316017AA1-139 ULT1
Solar/Wind Harmer
2.101
3137176SLIGO L2192
Solar/Wind Harmer
-0.103
3146456SLIGO L269
Solar/Wind Harmer
3.06
3130086AYDLETT
Solar/Wind Harmer
-0.103
3146386ELIZ CT
Solar/Wind Harmer
-0.026
316431W1029_GEN1
Solar/Wind Harmer
4.597
316433W1029_GEN2
Solar/Wind Harmer
4.597
3146516WINFALL
Solar/Wind Harmer
-0.025
971531AH1-263 GEN
50/50
86.63
3150411LDYSMT5
50/50
37.488
3150381LDYSMT2
50/50
35.877
972213AH1-691 GEN
50/50
6.069
972215AH1-692 GEN
50/50
6.069
963051AG1-154 GEN
50/50
4.668
972189AH1-679 GEN
Adder
4.302
316312AB1-027
Solar/Wind Harmer
0.947
316233AE1-074 FULL
Solar/Wind Harmer
0.743
971281AH1-106 GEN
Solar/Wind Harmer
4.489
971283AH1-107 GEN
Solar/Wind Harmer
4.489
971285AH1-108 GEN
Adder
1.85
316164AC1-076 GEN
Solar/Wind Harmer
2.317
315976AC1-164 GENA
Solar/Wind Harmer
28.952
316169AC1-164_GENC
Solar/Wind Harmer
25.012
315975AC1-164 GENB
Solar/Wind Harmer
0.857
316132AB2-190 GEN1
Solar/Wind Harmer
2.722
316369SG1_INVT
Solar/Wind Harmer
4.784
971167AH1-042 GEN
Solar/Wind Harmer
25.694
3142433PROV 92
Adder
0.461
3142433PROV 92
Adder
0.461
972265AH1-717 GEN
Adder
18.345
3151201GRAVEL4
Adder
17.197
3151191GRAVEL3
Adder
16.979
3151211GRAVEL5
Adder
16.979
971445AH1-216 GEN
Solar/Wind Harmer
16.362
3143316POE
Solar/Wind Harmer
-0.104
3143873LANEXA
Solar/Wind Harmer
-0.016
957831AF2-077 GEN
Solar/Wind Harmer
0.791
3138283WHITEMARSH
Solar/Wind Harmer
0.041
316314AB2-024 C
Solar/Wind Harmer
2.246
3151081ELIZAR1
Adder
21.406
3151091ELIZAR2
Adder
21.034
3152611GOSPORTB
Adder
2.973
3152621GOSPORTC
Adder
2.523
3152601GOSPORTA
Adder
2.327
316059AD1-063 C
Solar/Wind Harmer
0.591
315662AE1-191 GEN
Solar/Wind Harmer
3.14
315666AE1-190 GEN
Solar/Wind Harmer
0.785
957871AF2-081 GEN
Solar/Wind Harmer
12.983
957601AF2-054 GEN
Solar/Wind Harmer
0.776
3141873WAN 176
Solar/Wind Harmer
-0.005
315833AF1-017_GEN
Solar/Wind Harmer
4.925
316349AD2-085 GEN
Solar/Wind Harmer
2.306
316311AC2-079 GEN
Solar/Wind Harmer
13.076
319010AE1-072 C
Solar/Wind Harmer
5.237
3146406KITTY HAWK
Solar/Wind Harmer
0.021
316305AF2-043 C
Solar/Wind Harmer
0.78
315835AF2-110_GEN
Solar/Wind Harmer
3.217
313526AB2-022
Solar/Wind Harmer
0.692
3141913WHIT STONE
Solar/Wind Harmer
-0.026
3146486SUNBURY
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
3138133OCRAN
Solar/Wind Harmer
-0.008
316321Z2-027
Solar/Wind Harmer
0.689
3146396TANGLEW
Solar/Wind Harmer
0.47
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
316315AB2-025 C
Solar/Wind Harmer
0.677
941031AE2-094 GEN
Solar/Wind Harmer
46.982
944011AF1-069 GEN
Solar/Wind Harmer
14.721
962981AG1-147 GEN
Solar/Wind Harmer
10.954
315814AE2-033 C
Solar/Wind Harmer
23.285
315611Z1-036_GEN2
Solar/Wind Harmer
6.155
970673AG2-436 GEN
Solar/Wind Harmer
51.775
970673AG2-436 GEN
Solar/Wind Harmer
26.215
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
971967AH1-528 GEN
Solar/Wind Harmer
45.789
315816AE2-034 GEN
Solar/Wind Harmer
1.946
3141813NORNECK
Solar/Wind Harmer
-0.024
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.764
315733AD1-074 GEN2
Solar/Wind Harmer
4.764
315735AD1-075 GEN1
Solar/Wind Harmer
2.383
965291AG1-394 GEN
Solar/Wind Harmer
2.079
3146206CASHIE
Solar/Wind Harmer
-0.023
970601AG2-382 GEN
Solar/Wind Harmer
10.197
970085AG2-068 GEN
Solar/Wind Harmer
14.526
970581AG2-369 GEN
Solar/Wind Harmer
12.492
316318V4-068
Solar/Wind Harmer
0.578
3145893MURPHYS
Solar/Wind Harmer
-0.062
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145513AHOSKIE
Solar/Wind Harmer
0.199
961941AG1-037 GEN
Solar/Wind Harmer
0.172
3145513AHOSKIE
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.045
3145683EARLEYS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
3146043SEABORD
Solar/Wind Harmer
-0.023
946281AF1-292 GEN
Solar/Wind Harmer
0.507
315607AA1-063A GEN
Solar/Wind Harmer
2.287
316087AB2-174 GEN
Solar/Wind Harmer
3.208
315652AC1-086 GEN
Solar/Wind Harmer
25.116
3137643SOCKMAN
Solar/Wind Harmer
-0.088
3145796HORNRTN
Solar/Wind Harmer
-0.07
3145796HORNRTN
Solar/Wind Harmer
-0.009
3146033SCOT NK
Solar/Wind Harmer
-0.087
316223AC1-118
Solar/Wind Harmer
0.588
972193AH1-681 GEN
Adder
3.792
972205AH1-687 GEN
Adder
6.897
316411AF1-147_GEN1
Solar/Wind Helper
0.801
316415AF1-147_GEN2
Solar/Wind Helper
0.801
3138216PACIFIC
Solar/Wind Helper
0.039
970831AG2-522 GEN
Solar/Wind Harmer
0.169
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3144356SAPONY
Solar/Wind Harmer
0.875
316487AF1-042 GEN
Solar/Wind Harmer
3.271
315742AE1-103 GEN
Solar/Wind Harmer
2.586
3146376EDENTON
Solar/Wind Harmer
0.73
3146376EDENTON
Solar/Wind Harmer
0.73
958261AF2-120 GEN
Solar/Wind Harmer
9.495
972185AH1-677 GEN
Adder
12.206
972187AH1-678 GEN
Adder
6.125
316077AC2-138 C
Solar/Wind Harmer
0.504
3150341NORNECKC1
Adder
2.229
3150341NORNECKC1
Adder
2.211
316468AD1-105 GEN
Solar/Wind Harmer
2.661
970933AG2-581 GEN
Solar/Wind Harmer
22.315
316065AD1-022 GEN
Solar/Wind Harmer
11.699
3145893MURPHYS
Solar/Wind Harmer
0.648
3145893MURPHYS
Solar/Wind Harmer
-0.042
3146173TUNIS
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.023
316181AB2-040 GEN
Solar/Wind Harmer
3.126
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
970099AG2-077 GEN
Solar/Wind Harmer
27.949
316426AA2-053 GEN
Solar/Wind Harmer
2.247
3145593CAROLNA
Solar/Wind Harmer
-0.022
3145593CAROLNA
Solar/Wind Harmer
-0.022
966811AG1-552 GEN
Solar/Wind Harmer
2.49
3145593CAROLNA
Solar/Wind Harmer
0.184
3145783HORNRTN
Solar/Wind Harmer
2.611
3145783HORNRTN
Solar/Wind Harmer
2.089
3145783HORNRTN
Solar/Wind Harmer
0.653
3145783HORNRTN
Solar/Wind Harmer
0.261
3145796HORNRTN
Solar/Wind Harmer
-0.066
3145933PARMELE
Solar/Wind Harmer
-0.043
3145933PARMELE
Solar/Wind Harmer
-0.021
316274AC1-208 GEN
Solar/Wind Harmer
2.299
3144293JTRSVLE
Adder
0.57
3144293JTRSVLE
Adder
0.48
3151731LOISA B
Adder
8.104
3151721LOISA A
Adder
8.062
316447AC1-158 HLD
Solar/Wind Helper
4.724
3152261N ANNA2
50/50
14.616
970497AG2-320 GEN
50/50
26.297
3150401LDYSMT4
50/50
37.371
3150371LDYSMT1
50/50
36.111
315051AA1-145 CT1
50/50
2.037
966881AG1-559 GEN
Solar/Wind Harmer
0.878
3142416OLDCHRC
Solar/Wind Harmer
2.834
970293AG2-193 GEN
Solar/Wind Harmer
3.467
3143096IRON208
Adder
1.028
3143096IRON208
Adder
1.008
3150861SPRUNCD
Adder
1.131
316473AC1-191 GEN
Solar/Wind Harmer
2.951
3142946ENON
Solar/Wind Harmer
-0.009
970133AG2-095 GEN
Solar/Wind Harmer
3.044
316382AG1-145 C
Solar/Wind Harmer
0.812
970129AG2-093 GEN
Solar/Wind Harmer
15.161
315778AD1-151 GEN
Solar/Wind Harmer
23.243
965281AG1-393 GEN
Solar/Wind Harmer
3.354
315839AE2-212 C
Solar/Wind Harmer
0.808
3150921YORKTN3
Adder
5.96
3144216WINCHST
Adder
0.894
3142433PROV 92
Adder
0.461
3142433PROV 92
Adder
0.461
961611AG1-000B GEN
Solar/Wind Harmer
5.608
315773AC2-141 GEN
Solar/Wind Harmer
11.108
3151221GRAVEL6
Adder
17.177
3151171GRAVELC
Adder
3.305
3145336SMITFLD
Solar/Wind Harmer
-0.01
315813AE1-149 C
Solar/Wind Harmer
16.519
3144536CHRHLND
Solar/Wind Harmer
-0.004
970659AG2-427 GEN
Solar/Wind Harmer
2.473
944581AF1-123 GEN
Solar/Wind Harmer
119.344
944601AF1-125 GEN
Solar/Wind Harmer
117.481
3151101ELIZAR3
Adder
21.68
316083AB2-161 GEN
Solar/Wind Harmer
4.258
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3141766HARMONY
Solar/Wind Harmer
2.327
970661AG2-428 GEN
Solar/Wind Harmer
4.923
3141843SHACKLE
Adder
1.188
316203AE2-005 GEN
Solar/Wind Harmer
11.017
316280AD1-041 GEN
Solar/Wind Harmer
1.963
316156AD2-030 GEN
Solar/Wind Harmer
0.693
3141873WAN 176
Solar/Wind Harmer
3.078
3146456SLIGO L269
Solar/Wind Harmer
-0.026
971153AH1-033 GEN
Solar/Wind Harmer
3.159
316320Y1-086
Solar/Wind Harmer
1.503
316435W1029_GEN3
Solar/Wind Harmer
4.597
3146516WINFALL
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3145273HOLLAND
Solar/Wind Harmer
-0.019
962971AG1-146 GEN
Solar/Wind Harmer
4.694
316484AD2-074 GEN
Solar/Wind Harmer
6.252
970009AG2-005 GEN
Solar/Wind Harmer
3.104
3146376EDENTON
Solar/Wind Harmer
-0.025
316404AE1-155 C
Solar/Wind Harmer
4.727
315614AA2-178 GEN
Solar/Wind Harmer
2.595
3150351NORNECKC2
Adder
2.157
971781AH1-399 GEN
Solar/Wind Harmer
1.472
316313AB2-026
Solar/Wind Harmer
0.641
316258AE1-075 C
Solar/Wind Harmer
0.577
316405AF2-144 C
Solar/Wind Harmer
0.609
3143336POWHATN
Solar/Wind Harmer
2.399
971157AH1-035 GEN
Solar/Wind Harmer
2.954
315737AD1-076 GEN
Solar/Wind Harmer
4.477
3156081AA2-088 GEN
Solar/Wind Harmer
7.638
970917AG2-570 GEN
Solar/Wind Harmer
58.333
3146206CASHIE
Solar/Wind Harmer
-0.023
316365GEN2_N
Solar/Wind Harmer
1.569
3145893MURPHYS
Solar/Wind Harmer
0.162
3145893MURPHYS
Solar/Wind Harmer
-0.023
957521AF2-046 GEN
Solar/Wind Harmer
18.23
961681AG1-008 GEN
Solar/Wind Harmer
18.23
3146173TUNIS
Solar/Wind Harmer
-0.023
3156021HOLLOMANSOL
Solar/Wind Harmer
3.093
316463AE2-346 GEN
Solar/Wind Harmer
0.37
316140AB2-099
Solar/Wind Harmer
0.154
962331AG1-082 GEN
Solar/Wind Harmer
2.86
3147666LOUISA
Solar/Wind Harmer
-0.052
966621AG1-532 GEN
Solar/Wind Harmer
0.46
3146263WOODLND
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.022
313506AB2-031 GEN
Solar/Wind Harmer
1.801
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
316317KELFORD C
Solar/Wind Harmer
1.052
3145823KELFORD
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.087
3145796HORNRTN
Solar/Wind Harmer
-0.022
3147043LAWRENC
Solar/Wind Harmer
-0.013
3141906WESTMOR
Solar/Wind Harmer
-0.009
316478AD1-087 GEN
Solar/Wind Harmer
1.867
316486AD2-202 GEN
Solar/Wind Harmer
0.547
316210AC1-098 GEN
Solar/Wind Harmer
3.37
3145933PARMELE
Solar/Wind Harmer
-0.021
966801AG1-551 GEN
Solar/Wind Harmer
2.68
3144293JTRSVLE
Adder
0.57
972255AH1-712 GEN
Adder
84.869
3141316ARNOLDS
Adder
0.327
3150331BIRCHWDA
Adder
21.437
3151761LOISA E
Adder
16.521
972183AH1-676 GEN
Adder
129.328
316044AC1-158 PL1
Solar/Wind Helper
2.146
316450AC1-158 RIC
Solar/Wind Helper
0.572
3141196NOKESVL
Solar/Wind Helper
1.245
971507AH1-251 GEN
50/50
17.82
3152251N ANNA1
50/50
14.617
972197AH1-683 GEN
50/50
5.836
972219AH1-694 GEN
50/50
4.202
315052AA1-145 CT2
50/50
2.046
966881AG1-559 GEN
Solar/Wind Harmer
0.3
3142416OLDCHRC
Solar/Wind Harmer
-0.073
3142416OLDCHRC
Solar/Wind Harmer
-0.028
3143526WINTERP
Solar/Wind Harmer
-0.143
3143096IRON208
Adder
1.028
3150851SPRUNCC
Adder
1.131
3143226MDLTHAN
Solar/Wind Harmer
-0.027
3142543TWELFTH
Solar/Wind Harmer
-0.003
944631AF1-128 GEN
Adder
116.069
316159AE1-175 C
Solar/Wind Harmer
0.723
970129AG2-093 GEN
Solar/Wind Harmer
6.141
316458AB2-190 GEN2
Solar/Wind Harmer
2.722
315671AE2-027_GEN
Solar/Wind Harmer
20.165
971069AG2-661 GEN
Solar/Wind Harmer
4.245
971647AH1-324 GEN
Solar/Wind Harmer
13.352
971317AH1-138 GEN
Solar/Wind Harmer
3.332
3138126ROCKLANDING
Solar/Wind Harmer
0.082
3142433PROV 92
Solar/Wind Harmer
-0.106
3142433PROV 92
Adder
0.461
3142433PROV 92
Adder
0.461
961611AG1-000B GEN
Solar/Wind Harmer
13.144
316294AC1-161 GEN
Solar/Wind Harmer
8.588
3151171GRAVELC
Adder
2.513
3145336SMITFLD
Solar/Wind Harmer
-0.105
970659AG2-427 GEN
Solar/Wind Harmer
13.955
944591AF1-124 GEN
Solar/Wind Harmer
119.774
316375AC2-012 GEN
Solar/Wind Harmer
9.077
3150981CHESPKA
Adder
2.915
316381AD1-082 GEN
Solar/Wind Harmer
2.406
3141766HARMONY
Solar/Wind Harmer
-0.005
970661AG2-428 GEN
Solar/Wind Harmer
27.783
971777AH1-397 GEN
Solar/Wind Harmer
3.073
3141843SHACKLE
Adder
1.188
316072AD1-144
Solar/Wind Harmer
0.527
939411AE1-173 GEN
Solar/Wind Harmer
130.189
940641AE2-051 GEN
Solar/Wind Harmer
24.381
316388AE2-253 GEN
Solar/Wind Harmer
1.753
3146456SLIGO L269
Solar/Wind Harmer
-0.026
316246AF1-032 C
Solar/Wind Harmer
0.523
316093AE2-104_GEN
Solar/Wind Harmer
7.483
3138133OCRAN
Solar/Wind Harmer
-0.015
3146516WINFALL
Solar/Wind Harmer
-0.081
3146516WINFALL
Solar/Wind Harmer
-0.025
315800Z1-036_GEN1
Solar/Wind Harmer
6.155
961951AG1-038 GEN
Solar/Wind Harmer
3.271
3130156CHOWAN
Solar/Wind Harmer
-0.025
962861AG1-135 GEN
Solar/Wind Harmer
9.222
964211AG1-282 GEN
Solar/Wind Harmer
0.728
3141726DUNNSVL
Solar/Wind Harmer
-0.096
3145663CRESWEL
Solar/Wind Harmer
-0.067
971163AH1-040 GEN
Solar/Wind Harmer
22.551
3150351NORNECKC2
Adder
2.122
3143336POWHATN
Solar/Wind Harmer
2.822
970919AG2-571 GEN
Solar/Wind Harmer
7.384
3146206CASHIE
Solar/Wind Harmer
-0.023
971547AH1-271 GEN
Solar/Wind Harmer
5.827
316023GEN1_S
Solar/Wind Harmer
1.569
970087AG2-069 GEN
Solar/Wind Harmer
21.789
3145893MURPHYS
Solar/Wind Harmer
-0.092
3145893MURPHYS
Solar/Wind Harmer
0.689
3146173TUNIS
Solar/Wind Harmer
-0.023
316337AD2-073 GEN
Solar/Wind Harmer
0.615
316336AC2-165 C
Solar/Wind Harmer
3.962
3145683EARLEYS
Solar/Wind Harmer
-0.023
3147666LOUISA
Solar/Wind Harmer
-0.09
960081AF2-299 GEN
Solar/Wind Harmer
2.549
3146263WOODLND
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.022
957481AF2-042 GEN
Solar/Wind Harmer
69.874
316011AB1-132 GEN
Solar/Wind Harmer
4.671
962571AG1-106 GEN
Solar/Wind Harmer
3.209
3145823KELFORD
Solar/Wind Harmer
-0.022
316190AA2-174 GEN
Solar/Wind Harmer
0.273
316174AB2-169 GEN
Solar/Wind Harmer
3.427
316192AB2-158 GEN
Solar/Wind Harmer
2.642
971795AH1-408 GEN
Solar/Wind Harmer
16.627
3145783HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.072
3145796HORNRTN
Solar/Wind Harmer
-0.022
315693AD1-088 GEN
Solar/Wind Harmer
10.976
3147043LAWRENC
Adder
1.767
962491AG1-098 GEN
Solar/Wind Harmer
14.639
316212AC1-099_GEN
Solar/Wind Harmer
1.872
3146293MARTNCO
Solar/Wind Harmer
0.133
3144293JTRSVLE
Adder
0.57
972277AH1-723 GEN
Adder
98.898
3151751LOISA D
Adder
8.104
316045AC1-158 PL2
Solar/Wind Helper
6.871
NYPJM->LTFIMP_NY
CLTF
3.216
LGEELTFEXP_LGEE->PJM
CLTF
1.384
WECLTFEXP_WEC->PJM
CLTF
0.67
LAGNLTFEXP_LAGN->PJM
CLTF
8.168
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.207
TVALTFEXP_TVA->PJM
CLTF
4.141
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.433
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.112
MECLTFEXP_MEC->PJM
CLTF
3.742
SIGELTFEXP_SIGE->PJM
CLTF
0.114
CPLELTFEXP_CPLE->PJM
CLTF
11.466
CBM West 2LTFEXP_CBM-W2->PJM
CBM
42.376

Details for 8CUNINGHAM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-1: FLUVANN GT22_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CUNINGHAM-8ELMONT 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-1: FLUVANN GT22_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.39 %
Rating:2858.0 MVA
Rating Type:C
MVA to Mitigate:2955.0
MW Contribution:328.79
Bus #Bus NameTypeMW Contribution
23503501NHY_Z2-039
50/50
0.01
3132123MT JACKSON
Solar/Wind Harmer
-0.049
970117AG2-086 GEN
Solar/Wind Harmer
7.142
970117AG2-086 GEN
Solar/Wind Harmer
2.17
966871AG1-558 GEN
Solar/Wind Helper
0.487
316075AC2-137 C
Solar/Wind Helper
0.538
3142946ENON
Solar/Wind Helper
0.034
316468AD1-105 GEN
Solar/Wind Helper
1.641
316487AF1-042 GEN
Solar/Wind Helper
0.324
316077AC2-138 C
Solar/Wind Helper
0.297
316240AF1-291 C
Solar/Wind Helper
0.415
316033AB2-134 GEN
Solar/Wind Helper
1.06
315697AD1-025 GEN
Solar/Wind Helper
3.522
316236AE1-162_GEN
Solar/Wind Helper
0.398
316036AC1-147 C
Solar/Wind Helper
0.438
316316AC1-027 C
Solar/Wind Helper
0.451
3142956BIRDNECK
Solar/Wind Helper
0.192
3143526WINTERP
Solar/Wind Helper
1.48
316185AD1-033 GEN
Solar/Wind Helper
1.338
3145506HICKORY
Solar/Wind Helper
1.133
3145506HICKORY
Solar/Wind Helper
0.68
3145506HICKORY
Solar/Wind Helper
0.17
316339AD2-160 GEN
Solar/Wind Helper
1.07
316018AA1-139 ULT2
Solar/Wind Helper
1.206
316017AA1-139 ULT1
Solar/Wind Helper
1.282
3137176SLIGO L2192
Solar/Wind Helper
1.112
3130086AYDLETT
Solar/Wind Helper
1.114
3146386ELIZ CT
Solar/Wind Helper
0.273
316431W1029_GEN1
Solar/Wind Helper
1.079
316433W1029_GEN2
Solar/Wind Helper
1.079
3146516WINFALL
Solar/Wind Helper
0.265
3146516WINFALL
Solar/Wind Helper
0.265
3146516WINFALL
Solar/Wind Helper
0.265
3146626S HERTFORD
Solar/Wind Helper
0.262
3146626S HERTFORD
Solar/Wind Helper
0.262
315742AE1-103 GEN
Solar/Wind Helper
0.403
3144356SAPONY
Solar/Wind Helper
0.438
3152191CUNINGD
50/50
9.333
972255AH1-712 GEN
50/50
282.152
3152051BATH 5E
50/50
5.499
3137383CUSHAW
50/50
0.048
3151861LOWMORA
50/50
2.499
315760AF1-028 GEN
50/50
31.188
315616AA1-038_C
Solar/Wind Harmer
5.053
3148013FISHERV
Solar/Wind Harmer
-0.023
316499AE2-029_GEN
Solar/Wind Harmer
1.625
316473AC1-191 GEN
Solar/Wind Helper
2.207
3142946ENON
Solar/Wind Helper
0.113
316382AG1-145 C
Solar/Wind Helper
0.442
316280AD1-041 GEN
Solar/Wind Helper
1.102
316156AD2-030 GEN
Solar/Wind Helper
0.493
316484AD2-074 GEN
Solar/Wind Helper
0.619
316404AE1-155 C
Solar/Wind Helper
2.692
966881AG1-559 GEN
Solar/Wind Helper
0.421
3141906WESTMOR
Solar/Wind Helper
0.12
315839AE2-212 C
Solar/Wind Helper
0.401
3145336SMITFLD
Solar/Wind Helper
0.118
315773AC2-141 GEN
Solar/Wind Helper
6.345
3144536CHRHLND
Solar/Wind Helper
0.044
3144873MCLAUGH
Solar/Wind Helper
0.007
3146456SLIGO L269
Solar/Wind Helper
0.279
316320Y1-086
Solar/Wind Helper
0.122
316435W1029_GEN3
Solar/Wind Helper
1.079
3146516WINFALL
Solar/Wind Helper
0.265
3146626S HERTFORD
Solar/Wind Helper
0.262
3145273HOLLAND
Solar/Wind Helper
0.194
3146376EDENTON
Solar/Wind Helper
0.249
315614AA2-178 GEN
Solar/Wind Helper
1.443
315737AD1-076 GEN
Solar/Wind Helper
2.202
3152161CUNINGA
50/50
4.011
972277AH1-723 GEN
50/50
328.792
3152061BATH 6F
50/50
5.523
23503401SHY_Z2-039
50/50
0.006
315705AF1-075 GEN
Solar/Wind Harmer
10.639
3147983MERCK5
Solar/Wind Harmer
-0.008
3142416OLDCHRC
Solar/Wind Helper
0.952
3142416OLDCHRC
Solar/Wind Helper
0.365
3141766HARMONY
Solar/Wind Helper
0.066
3142433PROV 92
Solar/Wind Helper
1.324
316159AE1-175 C
Solar/Wind Helper
0.499
3138133OCRAN
Solar/Wind Helper
0.195
3142543TWELFTH
Solar/Wind Helper
0.031
964211AG1-282 GEN
Solar/Wind Helper
0.429
3141726DUNNSVL
Solar/Wind Helper
1.275
316458AB2-190 GEN2
Solar/Wind Helper
1.783
316337AD2-073 GEN
Solar/Wind Helper
0.468
3145336SMITFLD
Solar/Wind Helper
1.185
316294AC1-161 GEN
Solar/Wind Helper
5.391
316375AC2-012 GEN
Solar/Wind Helper
0.753
316072AD1-144
Solar/Wind Helper
0.326
316381AD1-082 GEN
Solar/Wind Helper
1.476
3143526WINTERP
Solar/Wind Helper
1.48
316388AE2-253 GEN
Solar/Wind Helper
1.07
3146456SLIGO L269
Solar/Wind Helper
0.279
316246AF1-032 C
Solar/Wind Helper
0.318
3146516WINFALL
Solar/Wind Helper
0.86
3146516WINFALL
Solar/Wind Helper
0.265
3143226MDLTHAN
Solar/Wind Helper
0.258
315800Z1-036_GEN1
Solar/Wind Helper
1.41
3130156CHOWAN
Solar/Wind Helper
0.25
3145663CRESWEL
Solar/Wind Helper
0.663
972193AH1-681 GEN
50/50
12.607
3152011BATH 1A
50/50
5.503
3152021BATH 2B
50/50
5.503
3152031BATH 3C
50/50
5.502
3152041BATH 4D
50/50
5.493
3151881LOWMORC
50/50
2.48
3151881LOWMORC
50/50
2.441
3151861LOWMORA
50/50
2.402
3148463FAIRFLD
Solar/Wind Harmer
-0.025
3148133STUARTS
Solar/Wind Harmer
-0.014
3148013FISHERV
Solar/Wind Harmer
-0.013
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
3138266HYDRAULIC
Solar/Wind Harmer
0
316312AB1-027
Solar/Wind Helper
0.697
3143873LANEXA
Solar/Wind Helper
0.2
316059AD1-063 C
Solar/Wind Helper
0.334
315662AE1-191 GEN
Solar/Wind Helper
1.763
315666AE1-190 GEN
Solar/Wind Helper
0.441
957601AF2-054 GEN
Solar/Wind Helper
0.438
3141873WAN 176
Solar/Wind Helper
0.065
3141913WHIT STONE
Solar/Wind Helper
0.325
3138133OCRAN
Solar/Wind Helper
0.097
3141783LANCAST
Solar/Wind Helper
0.194
3141783LANCAST
Solar/Wind Helper
0.129
957831AF2-077 GEN
Solar/Wind Helper
0.433
3141813NORNECK
Solar/Wind Helper
0.316
316132AB2-190 GEN1
Solar/Wind Helper
1.783
316369SG1_INVT
Solar/Wind Helper
1.482
316223AC1-118
Solar/Wind Helper
0.457
316233AE1-074 FULL
Solar/Wind Helper
0.435
3143316POE
Solar/Wind Helper
1.118
319010AE1-072 C
Solar/Wind Helper
3.186
316349AD2-085 GEN
Solar/Wind Helper
1.275
316305AF2-043 C
Solar/Wind Helper
0.374
313526AB2-022
Solar/Wind Helper
0.416
3146486SUNBURY
Solar/Wind Helper
0.272
3146486SUNBURY
Solar/Wind Helper
0.272
316321Z2-027
Solar/Wind Helper
0.412
3145176PASQUOTANK
Solar/Wind Helper
0.168
315611Z1-036_GEN2
Solar/Wind Helper
1.41
3130156CHOWAN
Solar/Wind Helper
0.25
3130156CHOWAN
Solar/Wind Helper
0.25
316315AB2-025 C
Solar/Wind Helper
0.372
315816AE2-034 GEN
Solar/Wind Helper
1.082
3130546PLYMOUTH
Solar/Wind Helper
0.227
315732AD1-074 GEN1
Solar/Wind Helper
2.575
315733AD1-074 GEN2
Solar/Wind Helper
2.575
315735AD1-075 GEN1
Solar/Wind Helper
1.287
NYPJM->LTFIMP_NY
CLTF
1.017
LGEELTFEXP_LGEE->PJM
CLTF
1.776
WECLTFEXP_WEC->PJM
CLTF
0.916
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.984
LAGNLTFEXP_LAGN->PJM
CLTF
3.697
TVALTFEXP_TVA->PJM
CLTF
1.977
CBM West 1LTFEXP_CBM-W1->PJM
CBM
34.211
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.837
MECLTFEXP_MEC->PJM
CLTF
3.882
SIGELTFEXP_SIGE->PJM
CLTF
0.13
CBM West 2LTFEXP_CBM-W2->PJM
CBM
28.293

Details for 8CUNINGHAM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 542_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CUNINGHAM-8ELMONT 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 542_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.0 %
Rating:2858.0 MVA
Rating Type:B
MVA to Mitigate:2943.79
MW Contribution:328.79
Bus #Bus NameTypeMW Contribution
3152191CUNINGD
50/50
9.333
972255AH1-712 GEN
50/50
282.152
3152051BATH 5E
50/50
5.499
3137383CUSHAW
50/50
0.048
3151861LOWMORA
50/50
2.499
315760AF1-028 GEN
50/50
31.188
315616AA1-038_C
Solar/Wind Harmer
0.002
3148013FISHERV
Solar/Wind Harmer
0.209
316473AC1-191 GEN
Solar/Wind Helper
2.207
3142946ENON
Solar/Wind Helper
0.113
316382AG1-145 C
Solar/Wind Helper
0.442
316280AD1-041 GEN
Solar/Wind Helper
1.102
316156AD2-030 GEN
Solar/Wind Helper
0.493
316484AD2-074 GEN
Solar/Wind Helper
0.619
316404AE1-155 C
Solar/Wind Helper
2.692
966881AG1-559 GEN
Solar/Wind Helper
0.421
3141906WESTMOR
Solar/Wind Helper
0.12
3152161CUNINGA
50/50
4.011
972277AH1-723 GEN
50/50
328.792
3152061BATH 6F
50/50
5.523
23503401SHY_Z2-039
50/50
0.006
315705AF1-075 GEN
Solar/Wind Harmer
8.394
3147983MERCK5
Solar/Wind Harmer
0.072
3142416OLDCHRC
Solar/Wind Helper
0.952
3142416OLDCHRC
Solar/Wind Helper
0.365
3141766HARMONY
Solar/Wind Helper
0.066
3142433PROV 92
Solar/Wind Helper
1.324
316159AE1-175 C
Solar/Wind Helper
0.499
3138133OCRAN
Solar/Wind Helper
0.195
3142543TWELFTH
Solar/Wind Helper
0.031
964211AG1-282 GEN
Solar/Wind Helper
0.429
3141726DUNNSVL
Solar/Wind Helper
1.275
23503501NHY_Z2-039
50/50
0.01
3132123MT JACKSON
Solar/Wind Harmer
0.437
970117AG2-086 GEN
Solar/Wind Harmer
3.352
970117AG2-086 GEN
Solar/Wind Harmer
2.235
966871AG1-558 GEN
Solar/Wind Helper
0.487
316075AC2-137 C
Solar/Wind Helper
0.538
3142946ENON
Solar/Wind Helper
0.034
316468AD1-105 GEN
Solar/Wind Helper
1.641
316487AF1-042 GEN
Solar/Wind Helper
0.324
316077AC2-138 C
Solar/Wind Helper
0.297
316240AF1-291 C
Solar/Wind Helper
0.415
316033AB2-134 GEN
Solar/Wind Helper
1.06
315697AD1-025 GEN
Solar/Wind Helper
3.522
316236AE1-162_GEN
Solar/Wind Helper
0.398
316036AC1-147 C
Solar/Wind Helper
0.438
972193AH1-681 GEN
50/50
12.607
3152011BATH 1A
50/50
5.503
3152021BATH 2B
50/50
5.503
3152031BATH 3C
50/50
5.502
3152041BATH 4D
50/50
5.493
3151881LOWMORC
50/50
2.48
3151881LOWMORC
50/50
2.441
3151861LOWMORA
50/50
2.402
3148463FAIRFLD
Solar/Wind Harmer
0.219
3148133STUARTS
Solar/Wind Harmer
0.125
3148013FISHERV
Solar/Wind Harmer
0.12
3138266HYDRAULIC
Solar/Wind Harmer
0.006
3138266HYDRAULIC
Solar/Wind Harmer
0.004
316312AB1-027
Solar/Wind Helper
0.697
3143873LANEXA
Solar/Wind Helper
0.2
316059AD1-063 C
Solar/Wind Helper
0.334
315662AE1-191 GEN
Solar/Wind Helper
1.763
315666AE1-190 GEN
Solar/Wind Helper
0.441
957601AF2-054 GEN
Solar/Wind Helper
0.438
3141873WAN 176
Solar/Wind Helper
0.065
3141913WHIT STONE
Solar/Wind Helper
0.325
3138133OCRAN
Solar/Wind Helper
0.097
3141783LANCAST
Solar/Wind Helper
0.194
3141783LANCAST
Solar/Wind Helper
0.129
957831AF2-077 GEN
Solar/Wind Helper
0.433
3141813NORNECK
Solar/Wind Helper
0.316
316132AB2-190 GEN1
Solar/Wind Helper
1.783
316369SG1_INVT
Solar/Wind Helper
1.482
316223AC1-118
Solar/Wind Helper
0.457
316233AE1-074 FULL
Solar/Wind Helper
0.435
3143316POE
Solar/Wind Helper
1.118
319010AE1-072 C
Solar/Wind Helper
3.186
316349AD2-085 GEN
Solar/Wind Helper
1.275
316305AF2-043 C
Solar/Wind Helper
0.374
313526AB2-022
Solar/Wind Helper
0.416
3146486SUNBURY
Solar/Wind Helper
0.272
3146486SUNBURY
Solar/Wind Helper
0.272
316321Z2-027
Solar/Wind Helper
0.412
3145176PASQUOTANK
Solar/Wind Helper
0.168
315611Z1-036_GEN2
Solar/Wind Helper
1.41
3130156CHOWAN
Solar/Wind Helper
0.25
3130156CHOWAN
Solar/Wind Helper
0.25
316315AB2-025 C
Solar/Wind Helper
0.372
315816AE2-034 GEN
Solar/Wind Helper
1.082
3130546PLYMOUTH
Solar/Wind Helper
0.227
315732AD1-074 GEN1
Solar/Wind Helper
2.575
315733AD1-074 GEN2
Solar/Wind Helper
2.575
315735AD1-075 GEN1
Solar/Wind Helper
1.287
316458AB2-190 GEN2
Solar/Wind Helper
1.783
316337AD2-073 GEN
Solar/Wind Helper
0.468
3145336SMITFLD
Solar/Wind Helper
1.185
316294AC1-161 GEN
Solar/Wind Helper
5.391
316375AC2-012 GEN
Solar/Wind Helper
0.753
316072AD1-144
Solar/Wind Helper
0.326
316381AD1-082 GEN
Solar/Wind Helper
1.476
3143526WINTERP
Solar/Wind Helper
1.48
316388AE2-253 GEN
Solar/Wind Helper
1.07
3146456SLIGO L269
Solar/Wind Helper
0.279
316246AF1-032 C
Solar/Wind Helper
0.318
3146516WINFALL
Solar/Wind Helper
0.86
3146516WINFALL
Solar/Wind Helper
0.265
3143226MDLTHAN
Solar/Wind Helper
0.258
315800Z1-036_GEN1
Solar/Wind Helper
1.41
3130156CHOWAN
Solar/Wind Helper
0.25
3145663CRESWEL
Solar/Wind Helper
0.663
316316AC1-027 C
Solar/Wind Helper
0.451
3142956BIRDNECK
Solar/Wind Helper
0.192
3143526WINTERP
Solar/Wind Helper
1.48
316185AD1-033 GEN
Solar/Wind Helper
1.338
3145506HICKORY
Solar/Wind Helper
1.133
3145506HICKORY
Solar/Wind Helper
0.68
3145506HICKORY
Solar/Wind Helper
0.17
316339AD2-160 GEN
Solar/Wind Helper
1.07
316018AA1-139 ULT2
Solar/Wind Helper
1.206
316017AA1-139 ULT1
Solar/Wind Helper
1.282
3137176SLIGO L2192
Solar/Wind Helper
1.112
3130086AYDLETT
Solar/Wind Helper
1.114
3146386ELIZ CT
Solar/Wind Helper
0.273
316431W1029_GEN1
Solar/Wind Helper
1.079
316433W1029_GEN2
Solar/Wind Helper
1.079
3146516WINFALL
Solar/Wind Helper
0.265
3146516WINFALL
Solar/Wind Helper
0.265
3146516WINFALL
Solar/Wind Helper
0.265
3146626S HERTFORD
Solar/Wind Helper
0.262
3146626S HERTFORD
Solar/Wind Helper
0.262
315742AE1-103 GEN
Solar/Wind Helper
0.403
3144356SAPONY
Solar/Wind Helper
0.438
315839AE2-212 C
Solar/Wind Helper
0.401
3145336SMITFLD
Solar/Wind Helper
0.118
315773AC2-141 GEN
Solar/Wind Helper
6.345
3144536CHRHLND
Solar/Wind Helper
0.044
3144873MCLAUGH
Solar/Wind Helper
0.007
3146456SLIGO L269
Solar/Wind Helper
0.279
316320Y1-086
Solar/Wind Helper
0.122
316435W1029_GEN3
Solar/Wind Helper
1.079
3146516WINFALL
Solar/Wind Helper
0.265
3146626S HERTFORD
Solar/Wind Helper
0.262
3145273HOLLAND
Solar/Wind Helper
0.194
3146376EDENTON
Solar/Wind Helper
0.249
315614AA2-178 GEN
Solar/Wind Helper
1.443
315737AD1-076 GEN
Solar/Wind Helper
2.202
NYPJM->LTFIMP_NY
CLTF
1.017
LGEELTFEXP_LGEE->PJM
CLTF
1.776
WECLTFEXP_WEC->PJM
CLTF
0.916
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.984
LAGNLTFEXP_LAGN->PJM
CLTF
3.697
TVALTFEXP_TVA->PJM
CLTF
1.977
CBM West 1LTFEXP_CBM-W1->PJM
CBM
34.211
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.837
MECLTFEXP_MEC->PJM
CLTF
3.882
SIGELTFEXP_SIGE->PJM
CLTF
0.13
CBM West 2LTFEXP_CBM-W2->PJM
CBM
28.293

Details for 8ELMONT-6ELMONT 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: H1T574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-6ELMONT 500.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P4-2: H1T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.02 %
Rating:1052.4 MVA
Rating Type:C
MVA to Mitigate:1136.79
MW Contribution:109.32
Bus #Bus NameTypeMW Contribution
966871AG1-558 GEN
Solar/Wind Helper
0.666
316468AD1-105 GEN
Solar/Wind Helper
2.026
3143526WINTERP
Solar/Wind Helper
1.419
316240AF1-291 C
Solar/Wind Helper
0.319
316075AC2-137 C
Solar/Wind Helper
0.303
3142946ENON
Solar/Wind Helper
0.017
316033AB2-134 GEN
Solar/Wind Helper
0.426
315697AD1-025 GEN
Solar/Wind Helper
1.416
3152191CUNINGD
50/50
3.103
3152171CUNINGB
50/50
1.34
972255AH1-712 GEN
50/50
93.813
315616AA1-038_C
Solar/Wind Harmer
1.64
3151861LOWMORA
Adder
0.764
3148013FISHERV
Solar/Wind Harmer
-0.007
316499AE2-029_GEN
Solar/Wind Harmer
0.518
316473AC1-191 GEN
Solar/Wind Helper
3.018
966881AG1-559 GEN
Solar/Wind Helper
0.415
315839AE2-212 C
Solar/Wind Helper
0.281
3142946ENON
Solar/Wind Helper
0.056
316313AB2-026
Solar/Wind Helper
0.232
316258AE1-075 C
Solar/Wind Helper
0.209
316405AF2-144 C
Solar/Wind Helper
0.174
3152181CUNINGC
50/50
1.425
972193AH1-681 GEN
50/50
4.192
3148463FAIRFLD
Solar/Wind Harmer
-0.008
3151881LOWMORC
Adder
0.759
3151881LOWMORC
Adder
0.747
3151861LOWMORA
Adder
0.735
3148133STUARTS
Solar/Wind Harmer
-0.004
3148013FISHERV
Solar/Wind Harmer
-0.004
316312AB1-027
Solar/Wind Helper
0.71
316233AE1-074 FULL
Solar/Wind Helper
0.417
3143316POE
Solar/Wind Helper
0.634
316132AB2-190 GEN1
Solar/Wind Helper
0.884
316369SG1_INVT
Solar/Wind Helper
0.596
3152161CUNINGA
50/50
1.334
972277AH1-723 GEN
50/50
109.321
315705AF1-075 GEN
Solar/Wind Harmer
3.416
3147983MERCK5
Solar/Wind Harmer
-0.003
3142416OLDCHRC
Solar/Wind Helper
0.97
3142416OLDCHRC
Solar/Wind Helper
0.372
3142543TWELFTH
Solar/Wind Helper
0.028
3143526WINTERP
Solar/Wind Helper
1.419
3143226MDLTHAN
Solar/Wind Helper
0.238
316458AB2-190 GEN2
Solar/Wind Helper
0.884
3142433PROV 92
Solar/Wind Helper
0.592
316336AC2-165 C
Solar/Wind Helper
0.701
NYPJM->LTFIMP_NY
CLTF
0.37
LGEELTFEXP_LGEE->PJM
CLTF
0.679
WECLTFEXP_WEC->PJM
CLTF
0.352
LAGNLTFEXP_LAGN->PJM
CLTF
1.692
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.919
TVALTFEXP_TVA->PJM
CLTF
0.887
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.093
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.398
MECLTFEXP_MEC->PJM
CLTF
1.534
SIGELTFEXP_SIGE->PJM
CLTF
0.05
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.914

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P2-2: ELMONT B1_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: ELMONT B1_SRT-S
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:183.41 %
Rating:2858.0 MVA
Rating Type:C
MVA to Mitigate:5241.92
MW Contribution:204.9
Bus #Bus NameTypeMW Contribution
3142296MT RD221
50/50
0.893
3150691DARBY 3
50/50
19.785
3150701DARBY 4
50/50
19.739
3150681DARBY 2
50/50
19.716
316075AC2-137 C
Solar/Wind Harmer
0.845
3142946ENON
Solar/Wind Harmer
-0.003
3150671DARBY 1
Adder
18.559
3142366NRTHEST
Adder
0.829
316441AF1-014 GEN
Solar/Wind Harmer
1.879
966871AG1-558 GEN
Solar/Wind Harmer
0.822
966871AG1-558 GEN
Solar/Wind Harmer
0.281
316033AB2-134 GEN
Solar/Wind Harmer
8.687
315697AD1-025 GEN
Solar/Wind Harmer
5.448
316236AE1-162_GEN
Solar/Wind Harmer
0.802
316036AC1-147 C
Solar/Wind Harmer
0.705
3150991CHESPKB
Adder
2.435
3150991CHESPKB
Adder
2.376
316316AC1-027 C
Solar/Wind Harmer
0.799
3142956BIRDNECK
Solar/Wind Harmer
1.396
316185AD1-033 GEN
Solar/Wind Harmer
2.738
3145506HICKORY
Solar/Wind Harmer
-0.103
3145506HICKORY
Solar/Wind Harmer
-0.062
3145506HICKORY
Solar/Wind Harmer
-0.015
316339AD2-160 GEN
Solar/Wind Harmer
1.736
316018AA1-139 ULT2
Solar/Wind Harmer
2.202
316017AA1-139 ULT1
Solar/Wind Harmer
2.08
944641AF1-129 GEN
Adder
108.805
3137176SLIGO L2192
Solar/Wind Harmer
-0.101
3146456SLIGO L269
Solar/Wind Harmer
3.026
3130086AYDLETT
Solar/Wind Harmer
-0.102
316240AF1-291 C
Solar/Wind Harmer
0.764
3146386ELIZ CT
Solar/Wind Harmer
-0.025
316431W1029_GEN1
Solar/Wind Harmer
4.499
316433W1029_GEN2
Solar/Wind Harmer
4.499
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
970657AG2-426 GEN
Solar/Wind Harmer
7.702
970657AG2-426 GEN
Solar/Wind Harmer
1.611
316487AF1-042 GEN
Solar/Wind Harmer
3.242
3146626S HERTFORD
Solar/Wind Harmer
-0.024
3146626S HERTFORD
Solar/Wind Harmer
-0.024
3146376EDENTON
Solar/Wind Harmer
0.705
3146376EDENTON
Solar/Wind Harmer
0.705
958261AF2-120 GEN
Solar/Wind Harmer
9.203
315742AE1-103 GEN
Solar/Wind Harmer
2.467
316077AC2-138 C
Solar/Wind Harmer
0.468
3150341NORNECKC1
Adder
2.07
3150341NORNECKC1
Adder
2.053
316065AD1-022 GEN
Solar/Wind Harmer
11.02
3145893MURPHYS
Solar/Wind Harmer
0.597
3145893MURPHYS
Solar/Wind Harmer
-0.038
3146173TUNIS
Solar/Wind Harmer
-0.021
3146173TUNIS
Solar/Wind Harmer
-0.021
3144356SAPONY
Solar/Wind Harmer
0.726
3143526WINTERP
Solar/Wind Harmer
-0.107
3142666NORTHAMPTON
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.012
316426AA2-053 GEN
Solar/Wind Harmer
1.997
3145933PARMELE
Solar/Wind Harmer
-0.039
3145933PARMELE
Solar/Wind Harmer
-0.02
3145593CAROLNA
Solar/Wind Harmer
-0.019
3145593CAROLNA
Solar/Wind Harmer
-0.019
966811AG1-552 GEN
Solar/Wind Harmer
2.195
3145593CAROLNA
Solar/Wind Harmer
0.162
316181AB2-040 GEN
Solar/Wind Harmer
2.717
3145783HORNRTN
Solar/Wind Harmer
2.305
3145783HORNRTN
Solar/Wind Harmer
1.844
3145783HORNRTN
Solar/Wind Harmer
0.576
3145783HORNRTN
Solar/Wind Harmer
0.23
3145796HORNRTN
Solar/Wind Harmer
-0.058
316274AC1-208 GEN
Solar/Wind Harmer
2.047
316468AD1-105 GEN
Solar/Wind Harmer
2.08
3145493TOT1
Solar/Wind Harmer
0.282
3145453TOT5
Solar/Wind Harmer
0.169
3145603CNETO
Solar/Wind Harmer
0.113
3152191CUNINGD
50/50
5.816
3152171CUNINGB
50/50
2.511
972255AH1-712 GEN
50/50
175.835
971645AH1-323 GEN
50/50
24.069
3151161SURRY 1
50/50
9.199
3142416OLDCHRC
Solar/Wind Harmer
3.122
316382AG1-145 C
Solar/Wind Harmer
0.914
970293AG2-193 GEN
Solar/Wind Harmer
3.771
3142946ENON
Solar/Wind Harmer
-0.01
3150921YORKTN3
Adder
6.49
3144216WINCHST
Adder
0.966
3141766HARMONY
Solar/Wind Harmer
2.513
3142433PROV 92
Adder
0.485
3142433PROV 92
Adder
0.485
3141843SHACKLE
Adder
1.268
316203AE2-005 GEN
Solar/Wind Harmer
11.751
316280AD1-041 GEN
Solar/Wind Harmer
2.088
3143096IRON208
Adder
1.033
3143096IRON208
Adder
1.012
316156AD2-030 GEN
Solar/Wind Harmer
0.734
3141873WAN 176
Solar/Wind Harmer
3.263
316473AC1-191 GEN
Solar/Wind Harmer
2.941
315773AC2-141 GEN
Solar/Wind Harmer
11.356
970133AG2-095 GEN
Solar/Wind Harmer
3.035
970129AG2-093 GEN
Solar/Wind Harmer
15.179
315778AD1-151 GEN
Solar/Wind Harmer
23.342
961611AG1-000B GEN
Solar/Wind Harmer
5.668
3151221GRAVEL6
Adder
17.412
3151171GRAVELC
Adder
3.35
3145336SMITFLD
Solar/Wind Harmer
-0.011
3144536CHRHLND
Solar/Wind Harmer
-0.004
3151101ELIZAR3
Adder
21.585
3144873MCLAUGH
Solar/Wind Harmer
-0.001
944581AF1-123 GEN
Solar/Wind Harmer
118.654
944601AF1-125 GEN
Solar/Wind Harmer
116.802
3146456SLIGO L269
Solar/Wind Harmer
-0.026
971153AH1-033 GEN
Solar/Wind Harmer
3.124
316320Y1-086
Solar/Wind Harmer
1.479
962971AG1-146 GEN
Solar/Wind Harmer
4.714
965281AG1-393 GEN
Solar/Wind Harmer
3.117
316435W1029_GEN3
Solar/Wind Harmer
4.499
3146516WINFALL
Solar/Wind Harmer
-0.025
970661AG2-428 GEN
Solar/Wind Harmer
4.651
316083AB2-161 GEN
Solar/Wind Harmer
3.995
316484AD2-074 GEN
Solar/Wind Harmer
6.195
970009AG2-005 GEN
Solar/Wind Harmer
3.076
970659AG2-427 GEN
Solar/Wind Harmer
2.315
3146626S HERTFORD
Solar/Wind Harmer
-0.024
315839AE2-212 C
Solar/Wind Harmer
0.737
315813AE1-149 C
Solar/Wind Harmer
15.266
3150861SPRUNCD
Adder
1.001
3145273HOLLAND
Solar/Wind Harmer
-0.018
3146376EDENTON
Solar/Wind Harmer
-0.024
316404AE1-155 C
Solar/Wind Harmer
4.581
315614AA2-178 GEN
Solar/Wind Harmer
2.481
971157AH1-035 GEN
Solar/Wind Harmer
2.801
315737AD1-076 GEN
Solar/Wind Harmer
4.237
3150351NORNECKC2
Adder
2.004
3146206CASHIE
Solar/Wind Harmer
-0.022
3156081AA2-088 GEN
Solar/Wind Harmer
7.07
3145893MURPHYS
Solar/Wind Harmer
0.149
3145893MURPHYS
Solar/Wind Harmer
-0.021
957521AF2-046 GEN
Solar/Wind Harmer
16.811
961681AG1-008 GEN
Solar/Wind Harmer
16.811
3156021HOLLOMANSOL
Solar/Wind Harmer
2.873
3152161CUNINGA
50/50
2.5
972277AH1-723 GEN
50/50
204.901
3152331SURRY 2
50/50
11.052
971353AH1-157 GEN
50/50
23.216
3142416OLDCHRC
Solar/Wind Harmer
-0.08
3142416OLDCHRC
Solar/Wind Harmer
-0.031
316159AE1-175 C
Solar/Wind Harmer
0.814
971317AH1-138 GEN
Solar/Wind Harmer
3.67
3138126ROCKLANDING
Solar/Wind Harmer
0.088
944631AF1-128 GEN
Adder
122.273
3141766HARMONY
Solar/Wind Harmer
-0.006
3142433PROV 92
Solar/Wind Harmer
-0.112
3142433PROV 92
Adder
0.485
3142433PROV 92
Adder
0.485
971777AH1-397 GEN
Solar/Wind Harmer
3.278
3141843SHACKLE
Adder
1.268
3143096IRON208
Adder
1.033
316294AC1-161 GEN
Solar/Wind Harmer
8.78
970129AG2-093 GEN
Solar/Wind Harmer
6.148
316458AB2-190 GEN2
Solar/Wind Harmer
2.727
971069AG2-661 GEN
Solar/Wind Harmer
4.263
971647AH1-324 GEN
Solar/Wind Harmer
13.464
961611AG1-000B GEN
Solar/Wind Harmer
13.285
3151171GRAVELC
Adder
2.548
3145336SMITFLD
Solar/Wind Harmer
-0.106
3138133OCRAN
Solar/Wind Harmer
-0.016
3142543TWELFTH
Solar/Wind Harmer
-0.002
316375AC2-012 GEN
Solar/Wind Harmer
9.038
3150981CHESPKA
Adder
2.902
944591AF1-124 GEN
Solar/Wind Harmer
119.081
316072AD1-144
Solar/Wind Harmer
0.526
316388AE2-253 GEN
Solar/Wind Harmer
1.736
3146456SLIGO L269
Solar/Wind Harmer
-0.026
316246AF1-032 C
Solar/Wind Harmer
0.516
315671AE2-027_GEN
Solar/Wind Harmer
18.884
316093AE2-104_GEN
Solar/Wind Harmer
7.299
3146516WINFALL
Solar/Wind Harmer
-0.08
3146516WINFALL
Solar/Wind Harmer
-0.025
970661AG2-428 GEN
Solar/Wind Harmer
26.246
316381AD1-082 GEN
Solar/Wind Harmer
2.257
961951AG1-038 GEN
Solar/Wind Harmer
3.242
970659AG2-427 GEN
Solar/Wind Harmer
13.061
3150851SPRUNCC
Adder
1.001
315800Z1-036_GEN1
Solar/Wind Harmer
5.976
962861AG1-135 GEN
Solar/Wind Harmer
8.992
3130156CHOWAN
Solar/Wind Harmer
-0.024
964211AG1-282 GEN
Solar/Wind Harmer
0.695
3141726DUNNSVL
Solar/Wind Harmer
-0.092
3145663CRESWEL
Solar/Wind Harmer
-0.064
971163AH1-040 GEN
Solar/Wind Harmer
21.556
3150351NORNECKC2
Adder
1.971
3146206CASHIE
Solar/Wind Harmer
-0.022
971547AH1-271 GEN
Solar/Wind Harmer
5.474
939411AE1-173 GEN
Solar/Wind Harmer
108.509
3145893MURPHYS
Solar/Wind Harmer
-0.085
3145893MURPHYS
Solar/Wind Harmer
0.635
3146173TUNIS
Solar/Wind Harmer
-0.021
3145683EARLEYS
Solar/Wind Harmer
-0.021
3145963POPLR C
Solar/Wind Harmer
-0.021
316174AB2-169 GEN
Solar/Wind Harmer
3.187
3143526WINTERP
Solar/Wind Harmer
-0.107
3146263WOODLND
Solar/Wind Harmer
-0.021
3145823KELFORD
Solar/Wind Harmer
-0.02
940641AE2-051 GEN
Solar/Wind Harmer
19.015
316023GEN1_S
Solar/Wind Harmer
1.348
316190AA2-174 GEN
Solar/Wind Harmer
0.243
3146293MARTNCO
Solar/Wind Harmer
0.122
316011AB1-132 GEN
Solar/Wind Harmer
4.112
962571AG1-106 GEN
Solar/Wind Harmer
2.825
316337AD2-073 GEN
Solar/Wind Harmer
0.524
960081AF2-299 GEN
Solar/Wind Harmer
2.188
3145783HORNRTN
Solar/Wind Harmer
-0.019
3145796HORNRTN
Solar/Wind Harmer
-0.064
3145796HORNRTN
Solar/Wind Harmer
-0.019
3152181CUNINGC
50/50
2.671
972193AH1-681 GEN
50/50
7.856
972263AH1-716 GEN
50/50
153.789
315976AC1-164 GENA
Solar/Wind Harmer
34.019
316169AC1-164_GENC
Solar/Wind Harmer
29.389
315975AC1-164 GENB
Solar/Wind Harmer
1.006
316312AB1-027
Solar/Wind Harmer
1.044
316314AB2-024 C
Solar/Wind Harmer
2.452
3143873LANEXA
Solar/Wind Harmer
-0.017
957831AF2-077 GEN
Solar/Wind Harmer
0.85
3138283WHITEMARSH
Solar/Wind Harmer
0.044
316059AD1-063 C
Solar/Wind Harmer
0.638
3142433PROV 92
Adder
0.485
3142433PROV 92
Adder
0.485
971167AH1-042 GEN
Solar/Wind Harmer
26.9
315662AE1-191 GEN
Solar/Wind Harmer
3.341
315666AE1-190 GEN
Solar/Wind Harmer
0.835
957601AF2-054 GEN
Solar/Wind Harmer
0.822
3141873WAN 176
Solar/Wind Harmer
-0.005
316132AB2-190 GEN1
Solar/Wind Harmer
2.727
316369SG1_INVT
Solar/Wind Harmer
4.813
972265AH1-717 GEN
Adder
18.595
3151201GRAVEL4
Adder
17.432
3151191GRAVEL3
Adder
17.211
3151211GRAVEL5
Adder
17.211
3141913WHIT STONE
Solar/Wind Harmer
-0.027
971445AH1-216 GEN
Solar/Wind Harmer
16.486
3138133OCRAN
Solar/Wind Harmer
-0.008
3151081ELIZAR1
Adder
21.313
3151091ELIZAR2
Adder
20.942
3152611GOSPORTB
Adder
2.96
3152621GOSPORTC
Adder
2.512
3152601GOSPORTA
Adder
2.317
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
957871AF2-081 GEN
Solar/Wind Harmer
12.85
319010AE1-072 C
Solar/Wind Harmer
5.177
3146406KITTY HAWK
Solar/Wind Harmer
0.021
316305AF2-043 C
Solar/Wind Harmer
0.768
313526AB2-022
Solar/Wind Harmer
0.681
962981AG1-147 GEN
Solar/Wind Harmer
10.999
315835AF2-110_GEN
Solar/Wind Harmer
3.138
3146486SUNBURY
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
316321Z2-027
Solar/Wind Harmer
0.676
3146396TANGLEW
Solar/Wind Harmer
0.461
3145176PASQUOTANK
Solar/Wind Harmer
-0.015
316311AC2-079 GEN
Solar/Wind Harmer
12.568
315833AF1-017_GEN
Solar/Wind Harmer
4.732
316349AD2-085 GEN
Solar/Wind Harmer
2.216
971285AH1-108 GEN
Adder
1.638
315611Z1-036_GEN2
Solar/Wind Harmer
5.976
3130156CHOWAN
Solar/Wind Harmer
-0.024
3130156CHOWAN
Solar/Wind Harmer
-0.024
3143316POE
Solar/Wind Harmer
-0.091
315816AE2-034 GEN
Solar/Wind Harmer
1.861
3130546PLYMOUTH
Solar/Wind Harmer
-0.022
315732AD1-074 GEN1
Solar/Wind Harmer
4.509
315733AD1-074 GEN2
Solar/Wind Harmer
4.509
315735AD1-075 GEN1
Solar/Wind Harmer
2.255
3146173TUNIS
Solar/Wind Harmer
-0.021
316463AE2-346 GEN
Solar/Wind Harmer
0.341
316140AB2-099
Solar/Wind Harmer
0.142
962331AG1-082 GEN
Solar/Wind Harmer
2.635
3145963POPLR C
Solar/Wind Harmer
-0.021
3146263WOODLND
Solar/Wind Harmer
-0.021
316317KELFORD C
Solar/Wind Harmer
0.96
3145823KELFORD
Solar/Wind Harmer
-0.02
316365GEN2_N
Solar/Wind Harmer
1.348
3142666NORTHAMPTON
Solar/Wind Harmer
-0.02
3145933PARMELE
Solar/Wind Harmer
-0.02
966801AG1-551 GEN
Solar/Wind Harmer
2.463
313506AB2-031 GEN
Solar/Wind Harmer
1.565
966621AG1-532 GEN
Solar/Wind Harmer
0.395
3145796HORNRTN
Solar/Wind Harmer
-0.077
3145796HORNRTN
Solar/Wind Harmer
-0.019
316210AC1-098 GEN
Solar/Wind Harmer
3.022
3145746EVERETS
Solar/Wind Harmer
-0.019
3145746EVERETS
Solar/Wind Harmer
-0.019
971781AH1-399 GEN
Solar/Wind Harmer
1.151
3147043LAWRENC
Solar/Wind Harmer
-0.011
315724AD1-057 GEN
Solar/Wind Harmer
1.061
316327AA2-057 GEN
Solar/Wind Harmer
1.859
3146073TAR RVR
Solar/Wind Harmer
-0.018
3146083TARBORO
Solar/Wind Harmer
-0.018
3146233WITAKRS
Solar/Wind Harmer
0.378
3146233WITAKRS
Solar/Wind Harmer
-0.012
3138543CONSLDL
Solar/Wind Harmer
-0.012
961601AG1-000A GEN
Solar/Wind Harmer
7.045
3145543BTLEBRO
Solar/Wind Harmer
-0.018
3145543BTLEBRO
Solar/Wind Harmer
-0.018
970917AG2-570 GEN
Solar/Wind Harmer
43.859
3151861LOWMORA
Adder
1.547
3144293JTRSVLE
Adder
0.457
316044AC1-158 PL1
Solar/Wind Helper
1.619
316450AC1-158 RIC
Solar/Wind Helper
0.432
3141196NOKESVL
Solar/Wind Helper
1.009
227287AC2-120 GEN
Solar/Wind Helper
0.321
226910AB2-157 C
Solar/Wind Helper
0.013
316170AC1-121 GEN2
Solar/Wind Helper
0.353
316212AC1-099_GEN
Solar/Wind Harmer
1.679
3145746EVERETS
Solar/Wind Harmer
-0.019
3145746EVERETS
Solar/Wind Harmer
-0.019
971795AH1-408 GEN
Solar/Wind Harmer
14.15
316494AC1-189 GEN
Solar/Wind Harmer
2.007
3147043LAWRENC
Adder
1.498
315722AD1-056 GEN
Solar/Wind Harmer
1.928
961671AG1-007 GEN
Solar/Wind Harmer
0.23
3146083TARBORO
Solar/Wind Harmer
-0.018
3145493TOT1
Solar/Wind Harmer
0.541
3146233WITAKRS
Solar/Wind Harmer
-0.071
316129AC1-054 GEN
Solar/Wind Harmer
1.564
971065AG2-659 GEN
Solar/Wind Harmer
8.848
3145543BTLEBRO
Solar/Wind Harmer
-0.018
3145543BTLEBRO
Solar/Wind Harmer
-0.014
316359AB2-059 GEN
Solar/Wind Harmer
2.384
316049AB1-081 GEN
Solar/Wind Harmer
1.908
3142053HEARTS
Solar/Wind Harmer
0.208
970919AG2-571 GEN
Solar/Wind Harmer
5.552
970087AG2-069 GEN
Solar/Wind Harmer
16.407
3143226MDLTHAN
Solar/Wind Harmer
-0.017
3144293JTRSVLE
Adder
0.457
316045AC1-158 PL2
Solar/Wind Helper
5.183
316006AB2-029 C
Solar/Wind Helper
0.115
316254AC1-120 GEN1
Solar/Wind Helper
1.06
957481AF2-042 GEN
Solar/Wind Harmer
51.775
972185AH1-677 GEN
Adder
9.021
972187AH1-678 GEN
Adder
4.545
970933AG2-581 GEN
Solar/Wind Harmer
16.661
961601AG1-000A GEN
Solar/Wind Harmer
6.957
316263AC1-034 GEN
Solar/Wind Harmer
8.29
971223AH1-071 GEN
Solar/Wind Harmer
2.156
3144293JTRSVLE
Adder
0.457
3144293JTRSVLE
Adder
0.385
316447AC1-158 HLD
Solar/Wind Helper
3.563
226929AD2-058 GEN
Solar/Wind Helper
0.095
315651AD1-115 GEN
Solar/Wind Helper
0.782
970099AG2-077 GEN
Solar/Wind Harmer
20.71
3141813NORNECK
Solar/Wind Harmer
-0.022
3146206CASHIE
Solar/Wind Harmer
-0.022
970601AG2-382 GEN
Solar/Wind Harmer
9.579
965291AG1-394 GEN
Solar/Wind Harmer
1.919
316318V4-068
Solar/Wind Harmer
0.533
3145893MURPHYS
Solar/Wind Harmer
-0.057
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145513AHOSKIE
Solar/Wind Harmer
0.184
961941AG1-037 GEN
Solar/Wind Harmer
0.158
3145513AHOSKIE
Solar/Wind Harmer
-0.021
3145683EARLEYS
Solar/Wind Harmer
-0.042
3145683EARLEYS
Solar/Wind Harmer
-0.021
3145683EARLEYS
Solar/Wind Harmer
-0.021
316315AB2-025 C
Solar/Wind Harmer
0.561
315814AE2-033 C
Solar/Wind Harmer
19.334
316233AE1-074 FULL
Solar/Wind Harmer
0.556
971281AH1-106 GEN
Solar/Wind Harmer
3.357
971283AH1-107 GEN
Solar/Wind Harmer
3.357
3146043SEABORD
Solar/Wind Harmer
-0.02
315607AA1-063A GEN
Solar/Wind Harmer
2.055
3146033SCOT NK
Solar/Wind Harmer
-0.079
315652AC1-086 GEN
Solar/Wind Harmer
22.109
3137643SOCKMAN
Solar/Wind Harmer
-0.077
316087AB2-174 GEN
Solar/Wind Harmer
2.777
972189AH1-679 GEN
Adder
2.902
946281AF1-292 GEN
Solar/Wind Harmer
0.436
3145796HORNRTN
Solar/Wind Harmer
-0.062
3145796HORNRTN
Solar/Wind Harmer
-0.008
316005AA1-067
Solar/Wind Harmer
0.388
3145746EVERETS
Solar/Wind Harmer
-0.076
3145746EVERETS
Solar/Wind Harmer
-0.019
3145746EVERETS
Solar/Wind Harmer
-0.019
3145746EVERETS
Solar/Wind Harmer
-0.019
970181AG2-120 GEN
Solar/Wind Harmer
2.514
957861AF2-080 GEN
Solar/Wind Harmer
8.162
316420AA1-050 GEN
Solar/Wind Harmer
2.103
941031AE2-094 GEN
Solar/Wind Harmer
34.401
944011AF1-069 GEN
Solar/Wind Harmer
10.779
3145573BETHELC
Solar/Wind Harmer
-0.018
3145573BETHELC
Solar/Wind Harmer
-0.018
970673AG2-436 GEN
Solar/Wind Harmer
38.143
970673AG2-436 GEN
Solar/Wind Harmer
19.313
316319Z2-044 C
Solar/Wind Harmer
0.997
971967AH1-528 GEN
Solar/Wind Harmer
33.887
970831AG2-522 GEN
Solar/Wind Harmer
9.002
970085AG2-068 GEN
Solar/Wind Harmer
10.938
970581AG2-369 GEN
Solar/Wind Harmer
9.406
3151881LOWMORC
Adder
1.535
3151881LOWMORC
Adder
1.511
3151861LOWMORA
Adder
1.486
972205AH1-687 GEN
Adder
5.427
316164AC1-076 GEN
Solar/Wind Helper
1.268
316411AF1-147_GEN1
Solar/Wind Helper
0.783
316415AF1-147_GEN2
Solar/Wind Helper
0.783
3138216PACIFIC
Solar/Wind Helper
0.038
NYPJM->LTFIMP_NY
CLTF
3.263
LGEELTFEXP_LGEE->PJM
CLTF
2.179
WECLTFEXP_WEC->PJM
CLTF
1.101
AG2-052LTFEXP_AG2-052->PJM
LTF
0.062
AH1-155LTFEXP_AH1-155->PJM
LTF
0.093
LAGNLTFEXP_LAGN->PJM
CLTF
9.618
CBM South 2LTFEXP_CBM-S2->PJM
CBM
23.992
TVALTFEXP_TVA->PJM
CLTF
4.896
CBM West 1LTFEXP_CBM-W1->PJM
CBM
38.955
CBM South 1LTFEXP_CBM-S1->PJM
CBM
17.221
MECLTFEXP_MEC->PJM
CLTF
5.508
SIGELTFEXP_SIGE->PJM
CLTF
0.172
CPLELTFEXP_CPLE->PJM
CLTF
10.256
CBM West 2LTFEXP_CBM-W2->PJM
CBM
54.377

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P2-2: LADYSMITH B2_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: LADYSMITH B2_SRT-S
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:177.49 %
Rating:2913.0 MVA
Rating Type:C
MVA to Mitigate:5170.16
MW Contribution:196.57
Bus #Bus NameTypeMW Contribution
971645AH1-323 GEN
50/50
30.156
3152191CUNINGD
50/50
5.58
3152171CUNINGB
50/50
2.409
972255AH1-712 GEN
50/50
168.684
3142416OLDCHRC
Solar/Wind Harmer
3.694
970293AG2-193 GEN
Solar/Wind Harmer
4.338
316473AC1-191 GEN
Solar/Wind Harmer
3.676
3142946ENON
Solar/Wind Harmer
-0.011
316382AG1-145 C
Solar/Wind Harmer
0.981
3143096IRON208
Adder
1.195
3143096IRON208
Adder
1.171
3142433PROV 92
Adder
0.542
3142433PROV 92
Adder
0.542
3141766HARMONY
Solar/Wind Harmer
2.753
3150921YORKTN3
Adder
6.914
3144216WINCHST
Adder
1.031
3141843SHACKLE
Adder
1.393
316203AE2-005 GEN
Solar/Wind Harmer
12.911
970133AG2-095 GEN
Solar/Wind Harmer
3.429
316280AD1-041 GEN
Solar/Wind Harmer
2.291
970129AG2-093 GEN
Solar/Wind Harmer
16.978
316156AD2-030 GEN
Solar/Wind Harmer
0.804
3141873WAN 176
Solar/Wind Harmer
3.573
315778AD1-151 GEN
Solar/Wind Harmer
25.917
961611AG1-000B GEN
Solar/Wind Harmer
6.196
3151221GRAVEL6
Adder
18.899
3151171GRAVELC
Adder
3.636
3150861SPRUNCD
Adder
1.182
3145336SMITFLD
Solar/Wind Harmer
-0.011
965281AG1-393 GEN
Solar/Wind Harmer
3.561
315773AC2-141 GEN
Solar/Wind Harmer
11.911
315839AE2-212 C
Solar/Wind Harmer
0.844
3144536CHRHLND
Solar/Wind Harmer
-0.004
962971AG1-146 GEN
Solar/Wind Harmer
5.218
3151101ELIZAR3
Adder
22.914
3144873MCLAUGH
Solar/Wind Harmer
-0.001
944581AF1-123 GEN
Solar/Wind Harmer
125.547
944601AF1-125 GEN
Solar/Wind Harmer
123.588
316484AD2-074 GEN
Solar/Wind Harmer
6.875
970009AG2-005 GEN
Solar/Wind Harmer
3.414
315813AE1-149 C
Solar/Wind Harmer
17.052
3146456SLIGO L269
Solar/Wind Harmer
-0.027
971153AH1-033 GEN
Solar/Wind Harmer
3.314
970659AG2-427 GEN
Solar/Wind Harmer
2.558
316083AB2-161 GEN
Solar/Wind Harmer
4.407
970661AG2-428 GEN
Solar/Wind Harmer
5.102
316320Y1-086
Solar/Wind Harmer
1.57
316404AE1-155 C
Solar/Wind Harmer
5.107
316435W1029_GEN3
Solar/Wind Harmer
4.783
3146516WINFALL
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3145273HOLLAND
Solar/Wind Harmer
-0.019
3146376EDENTON
Solar/Wind Harmer
-0.025
3150351NORNECKC2
Adder
2.253
971781AH1-399 GEN
Solar/Wind Harmer
1.519
315614AA2-178 GEN
Solar/Wind Harmer
2.643
971157AH1-035 GEN
Solar/Wind Harmer
2.987
315737AD1-076 GEN
Solar/Wind Harmer
4.52
3146206CASHIE
Solar/Wind Harmer
-0.023
3156081AA2-088 GEN
Solar/Wind Harmer
7.579
3145893MURPHYS
Solar/Wind Harmer
0.16
3145893MURPHYS
Solar/Wind Harmer
-0.023
957521AF2-046 GEN
Solar/Wind Harmer
18.013
961681AG1-008 GEN
Solar/Wind Harmer
18.013
3156021HOLLOMANSOL
Solar/Wind Harmer
3.072
3146173TUNIS
Solar/Wind Harmer
-0.023
316463AE2-346 GEN
Solar/Wind Harmer
0.365
316140AB2-099
Solar/Wind Harmer
0.152
962331AG1-082 GEN
Solar/Wind Harmer
2.821
3145963POPLR C
Solar/Wind Harmer
-0.022
3146263WOODLND
Solar/Wind Harmer
-0.022
316317KELFORD C
Solar/Wind Harmer
1.028
3145823KELFORD
Solar/Wind Harmer
-0.022
316365GEN2_N
Solar/Wind Harmer
1.467
3142666NORTHAMPTON
Solar/Wind Harmer
-0.021
966621AG1-532 GEN
Solar/Wind Harmer
0.428
3145933PARMELE
Solar/Wind Harmer
-0.021
966801AG1-551 GEN
Solar/Wind Harmer
2.631
313506AB2-031 GEN
Solar/Wind Harmer
1.691
3145796HORNRTN
Solar/Wind Harmer
-0.083
3145796HORNRTN
Solar/Wind Harmer
-0.021
316210AC1-098 GEN
Solar/Wind Harmer
3.24
3145746EVERETS
Solar/Wind Harmer
-0.02
3145746EVERETS
Solar/Wind Harmer
-0.02
3147043LAWRENC
Solar/Wind Harmer
-0.012
315724AD1-057 GEN
Solar/Wind Harmer
1.139
316327AA2-057 GEN
Solar/Wind Harmer
1.993
3146073TAR RVR
Solar/Wind Harmer
-0.019
3146083TARBORO
Solar/Wind Harmer
-0.019
3146233WITAKRS
Solar/Wind Harmer
0.405
3146233WITAKRS
Solar/Wind Harmer
-0.013
3141906WESTMOR
Solar/Wind Harmer
-0.008
3138543CONSLDL
Solar/Wind Harmer
-0.013
961601AG1-000A GEN
Solar/Wind Harmer
7.544
3145543BTLEBRO
Solar/Wind Harmer
-0.019
3145543BTLEBRO
Solar/Wind Harmer
-0.019
970917AG2-570 GEN
Solar/Wind Harmer
47.275
316313AB2-026
Solar/Wind Harmer
0.499
316258AE1-075 C
Solar/Wind Harmer
0.449
316405AF2-144 C
Solar/Wind Harmer
0.474
3143336POWHATN
Solar/Wind Harmer
1.865
3144293JTRSVLE
Adder
0.491
3151861LOWMORA
Adder
1.493
316044AC1-158 PL1
Solar/Wind Helper
1.669
316450AC1-158 RIC
Solar/Wind Helper
0.445
3141196NOKESVL
Solar/Wind Helper
1.034
227287AC2-120 GEN
Solar/Wind Helper
0.328
316170AC1-121 GEN2
Solar/Wind Helper
0.366
226910AB2-157 C
Solar/Wind Helper
0.013
3152161CUNINGA
50/50
2.398
972277AH1-723 GEN
50/50
196.568
3142416OLDCHRC
Solar/Wind Harmer
-0.095
3142416OLDCHRC
Solar/Wind Harmer
-0.036
316159AE1-175 C
Solar/Wind Harmer
0.873
944631AF1-128 GEN
Adder
137.961
3143096IRON208
Adder
1.195
971317AH1-138 GEN
Solar/Wind Harmer
3.918
3142433PROV 92
Solar/Wind Harmer
-0.125
3142433PROV 92
Adder
0.542
3142433PROV 92
Adder
0.542
3141766HARMONY
Solar/Wind Harmer
-0.006
3138126ROCKLANDING
Solar/Wind Harmer
0.094
3142543TWELFTH
Solar/Wind Harmer
-0.003
971777AH1-397 GEN
Solar/Wind Harmer
3.601
3141843SHACKLE
Adder
1.393
970129AG2-093 GEN
Solar/Wind Harmer
6.877
316458AB2-190 GEN2
Solar/Wind Harmer
3.047
971069AG2-661 GEN
Solar/Wind Harmer
4.734
971647AH1-324 GEN
Solar/Wind Harmer
14.801
961611AG1-000B GEN
Solar/Wind Harmer
14.522
3151171GRAVELC
Adder
2.765
3138133OCRAN
Solar/Wind Harmer
-0.017
3150851SPRUNCC
Adder
1.182
315671AE2-027_GEN
Solar/Wind Harmer
21.615
3145336SMITFLD
Solar/Wind Harmer
-0.114
316294AC1-161 GEN
Solar/Wind Harmer
9.209
316375AC2-012 GEN
Solar/Wind Harmer
9.6
3150981CHESPKA
Adder
3.083
316072AD1-144
Solar/Wind Harmer
0.561
944591AF1-124 GEN
Solar/Wind Harmer
125.999
961951AG1-038 GEN
Solar/Wind Harmer
3.598
316388AE2-253 GEN
Solar/Wind Harmer
1.841
3146456SLIGO L269
Solar/Wind Harmer
-0.027
970659AG2-427 GEN
Solar/Wind Harmer
14.437
316381AD1-082 GEN
Solar/Wind Harmer
2.49
316246AF1-032 C
Solar/Wind Harmer
0.548
970661AG2-428 GEN
Solar/Wind Harmer
28.791
316093AE2-104_GEN
Solar/Wind Harmer
7.8
962861AG1-135 GEN
Solar/Wind Harmer
10.011
3146516WINFALL
Solar/Wind Harmer
-0.085
3146516WINFALL
Solar/Wind Harmer
-0.026
964211AG1-282 GEN
Solar/Wind Harmer
0.779
3141726DUNNSVL
Solar/Wind Harmer
-0.103
315800Z1-036_GEN1
Solar/Wind Harmer
6.358
3130156CHOWAN
Solar/Wind Harmer
-0.025
3150351NORNECKC2
Adder
2.216
3143526WINTERP
Solar/Wind Harmer
-0.127
3145663CRESWEL
Solar/Wind Harmer
-0.068
971163AH1-040 GEN
Solar/Wind Harmer
22.968
3146206CASHIE
Solar/Wind Harmer
-0.023
971547AH1-271 GEN
Solar/Wind Harmer
5.844
939411AE1-173 GEN
Solar/Wind Harmer
116.096
3145893MURPHYS
Solar/Wind Harmer
-0.091
3145893MURPHYS
Solar/Wind Harmer
0.681
3146173TUNIS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.022
3145963POPLR C
Solar/Wind Harmer
-0.022
316337AD2-073 GEN
Solar/Wind Harmer
0.599
316174AB2-169 GEN
Solar/Wind Harmer
3.402
3146263WOODLND
Solar/Wind Harmer
-0.022
3145823KELFORD
Solar/Wind Harmer
-0.022
940641AE2-051 GEN
Solar/Wind Harmer
20.428
316023GEN1_S
Solar/Wind Harmer
1.467
316190AA2-174 GEN
Solar/Wind Harmer
0.261
316011AB1-132 GEN
Solar/Wind Harmer
4.439
962571AG1-106 GEN
Solar/Wind Harmer
3.05
960081AF2-299 GEN
Solar/Wind Harmer
2.372
3146293MARTNCO
Solar/Wind Harmer
0.13
3145783HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.069
3145796HORNRTN
Solar/Wind Harmer
-0.021
316212AC1-099_GEN
Solar/Wind Harmer
1.8
3143226MDLTHAN
Solar/Wind Harmer
-0.021
3145746EVERETS
Solar/Wind Harmer
-0.02
3145746EVERETS
Solar/Wind Harmer
-0.02
971795AH1-408 GEN
Solar/Wind Harmer
15.313
3147043LAWRENC
Adder
1.619
316494AC1-189 GEN
Solar/Wind Harmer
2.146
315722AD1-056 GEN
Solar/Wind Harmer
2.072
961671AG1-007 GEN
Solar/Wind Harmer
0.247
3146083TARBORO
Solar/Wind Harmer
-0.019
3145493TOT1
Solar/Wind Harmer
0.578
3146233WITAKRS
Solar/Wind Harmer
-0.077
316129AC1-054 GEN
Solar/Wind Harmer
1.68
971065AG2-659 GEN
Solar/Wind Harmer
9.499
3145543BTLEBRO
Solar/Wind Harmer
-0.019
3145543BTLEBRO
Solar/Wind Harmer
-0.015
316359AB2-059 GEN
Solar/Wind Harmer
2.553
316049AB1-081 GEN
Solar/Wind Harmer
2.043
3142053HEARTS
Solar/Wind Harmer
0.223
970919AG2-571 GEN
Solar/Wind Harmer
5.984
970087AG2-069 GEN
Solar/Wind Harmer
17.682
3143336POWHATN
Solar/Wind Harmer
2.195
3144293JTRSVLE
Adder
0.491
316045AC1-158 PL2
Solar/Wind Helper
5.343
316006AB2-029 C
Solar/Wind Helper
0.119
316254AC1-120 GEN1
Solar/Wind Helper
1.099
957481AF2-042 GEN
Solar/Wind Harmer
51.461
3142296MT RD221
50/50
1.109
3150691DARBY 3
50/50
23.259
3150701DARBY 4
50/50
23.205
3150681DARBY 2
50/50
23.178
3150671DARBY 1
50/50
23.151
3142366NRTHEST
50/50
1.048
316075AC2-137 C
Solar/Wind Harmer
0.95
966871AG1-558 GEN
Solar/Wind Harmer
1.027
966871AG1-558 GEN
Solar/Wind Harmer
0.351
3142946ENON
Solar/Wind Harmer
-0.003
316441AF1-014 GEN
Solar/Wind Harmer
2.064
316033AB2-134 GEN
Solar/Wind Harmer
9.603
315697AD1-025 GEN
Solar/Wind Harmer
6.023
944641AF1-129 GEN
Adder
125.899
316240AF1-291 C
Solar/Wind Harmer
0.882
316236AE1-162_GEN
Solar/Wind Harmer
0.864
316036AC1-147 C
Solar/Wind Harmer
0.748
3150991CHESPKB
Adder
2.586
3150991CHESPKB
Adder
2.524
316316AC1-027 C
Solar/Wind Harmer
0.848
3142956BIRDNECK
Solar/Wind Harmer
1.482
316185AD1-033 GEN
Solar/Wind Harmer
2.904
3145506HICKORY
Solar/Wind Harmer
-0.109
3145506HICKORY
Solar/Wind Harmer
-0.066
3145506HICKORY
Solar/Wind Harmer
-0.016
316487AF1-042 GEN
Solar/Wind Harmer
3.598
316339AD2-160 GEN
Solar/Wind Harmer
1.841
316018AA1-139 ULT2
Solar/Wind Harmer
2.335
316017AA1-139 ULT1
Solar/Wind Harmer
2.206
3137176SLIGO L2192
Solar/Wind Harmer
-0.108
3146456SLIGO L269
Solar/Wind Harmer
3.211
3130086AYDLETT
Solar/Wind Harmer
-0.108
970657AG2-426 GEN
Solar/Wind Harmer
8.479
970657AG2-426 GEN
Solar/Wind Harmer
1.773
3146386ELIZ CT
Solar/Wind Harmer
-0.027
958261AF2-120 GEN
Solar/Wind Harmer
10.259
316431W1029_GEN1
Solar/Wind Harmer
4.783
316433W1029_GEN2
Solar/Wind Harmer
4.783
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3146376EDENTON
Solar/Wind Harmer
0.75
3146376EDENTON
Solar/Wind Harmer
0.75
315742AE1-103 GEN
Solar/Wind Harmer
2.639
316077AC2-138 C
Solar/Wind Harmer
0.527
3150341NORNECKC1
Adder
2.328
3150341NORNECKC1
Adder
2.309
3143526WINTERP
Solar/Wind Harmer
-0.127
316468AD1-105 GEN
Solar/Wind Harmer
2.745
316065AD1-022 GEN
Solar/Wind Harmer
11.762
3144356SAPONY
Solar/Wind Harmer
0.801
3145893MURPHYS
Solar/Wind Harmer
0.64
3145893MURPHYS
Solar/Wind Harmer
-0.041
3146173TUNIS
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.021
3142666NORTHAMPTON
Solar/Wind Harmer
-0.021
3142666NORTHAMPTON
Solar/Wind Harmer
-0.021
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
316426AA2-053 GEN
Solar/Wind Harmer
2.147
3145933PARMELE
Solar/Wind Harmer
-0.042
3145933PARMELE
Solar/Wind Harmer
-0.021
316181AB2-040 GEN
Solar/Wind Harmer
2.935
3145593CAROLNA
Solar/Wind Harmer
-0.021
3145593CAROLNA
Solar/Wind Harmer
-0.021
966811AG1-552 GEN
Solar/Wind Harmer
2.362
3145593CAROLNA
Solar/Wind Harmer
0.174
3145783HORNRTN
Solar/Wind Harmer
2.48
3145783HORNRTN
Solar/Wind Harmer
1.984
3145783HORNRTN
Solar/Wind Harmer
0.62
3145783HORNRTN
Solar/Wind Harmer
0.248
3145796HORNRTN
Solar/Wind Harmer
-0.062
971223AH1-071 GEN
Solar/Wind Harmer
2.579
316274AC1-208 GEN
Solar/Wind Harmer
2.196
972185AH1-677 GEN
Adder
9.743
3145493TOT1
Solar/Wind Harmer
0.302
3145453TOT5
Solar/Wind Harmer
0.181
3145603CNETO
Solar/Wind Harmer
0.121
972187AH1-678 GEN
Adder
4.907
970933AG2-581 GEN
Solar/Wind Harmer
17.976
961601AG1-000A GEN
Solar/Wind Harmer
7.45
316263AC1-034 GEN
Solar/Wind Harmer
8.876
3144293JTRSVLE
Adder
0.491
3144293JTRSVLE
Adder
0.413
316447AC1-158 HLD
Solar/Wind Helper
3.674
226929AD2-058 GEN
Solar/Wind Helper
0.096
315651AD1-115 GEN
Solar/Wind Helper
0.81
970099AG2-077 GEN
Solar/Wind Harmer
20.584
3152181CUNINGC
50/50
2.563
972193AH1-681 GEN
50/50
7.537
316312AB1-027
Solar/Wind Harmer
1.235
315976AC1-164 GENA
Solar/Wind Harmer
37.189
316169AC1-164_GENC
Solar/Wind Harmer
32.128
315975AC1-164 GENB
Solar/Wind Harmer
1.1
316314AB2-024 C
Solar/Wind Harmer
2.686
3143873LANEXA
Solar/Wind Harmer
-0.019
3142433PROV 92
Adder
0.542
3142433PROV 92
Adder
0.542
971167AH1-042 GEN
Solar/Wind Harmer
30.151
316059AD1-063 C
Solar/Wind Harmer
0.699
957831AF2-077 GEN
Solar/Wind Harmer
0.918
3138283WHITEMARSH
Solar/Wind Harmer
0.047
315662AE1-191 GEN
Solar/Wind Harmer
3.665
315666AE1-190 GEN
Solar/Wind Harmer
0.916
316132AB2-190 GEN1
Solar/Wind Harmer
3.047
957601AF2-054 GEN
Solar/Wind Harmer
0.901
3141873WAN 176
Solar/Wind Harmer
-0.006
316369SG1_INVT
Solar/Wind Harmer
5.32
3141913WHIT STONE
Solar/Wind Harmer
-0.029
972265AH1-717 GEN
Adder
20.184
3151201GRAVEL4
Adder
18.921
3151191GRAVEL3
Adder
18.681
3151211GRAVEL5
Adder
18.681
3138133OCRAN
Solar/Wind Harmer
-0.009
971285AH1-108 GEN
Adder
1.935
3141783LANCAST
Solar/Wind Harmer
-0.017
3141783LANCAST
Solar/Wind Harmer
-0.011
971445AH1-216 GEN
Solar/Wind Harmer
17.762
962981AG1-147 GEN
Solar/Wind Harmer
12.174
3152611GOSPORTB
Adder
3.144
3152621GOSPORTC
Adder
2.668
3152601GOSPORTA
Adder
2.461
3151081ELIZAR1
Adder
22.624
3151091ELIZAR2
Adder
22.231
957871AF2-081 GEN
Solar/Wind Harmer
13.631
319010AE1-072 C
Solar/Wind Harmer
5.493
3146406KITTY HAWK
Solar/Wind Harmer
0.023
316305AF2-043 C
Solar/Wind Harmer
0.817
315833AF1-017_GEN
Solar/Wind Harmer
5.119
316349AD2-085 GEN
Solar/Wind Harmer
2.397
316311AC2-079 GEN
Solar/Wind Harmer
13.593
972189AH1-679 GEN
Adder
4
315835AF2-110_GEN
Solar/Wind Harmer
3.353
313526AB2-022
Solar/Wind Harmer
0.723
3146486SUNBURY
Solar/Wind Harmer
-0.027
3146486SUNBURY
Solar/Wind Harmer
-0.027
316321Z2-027
Solar/Wind Harmer
0.718
3146396TANGLEW
Solar/Wind Harmer
0.49
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
3143316POE
Solar/Wind Harmer
-0.103
315611Z1-036_GEN2
Solar/Wind Harmer
6.358
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
3141813NORNECK
Solar/Wind Harmer
-0.025
316233AE1-074 FULL
Solar/Wind Harmer
0.662
971281AH1-106 GEN
Solar/Wind Harmer
4.002
971283AH1-107 GEN
Solar/Wind Harmer
4.002
315816AE2-034 GEN
Solar/Wind Harmer
1.982
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.809
315733AD1-074 GEN2
Solar/Wind Harmer
4.809
315735AD1-075 GEN1
Solar/Wind Harmer
2.405
3146206CASHIE
Solar/Wind Harmer
-0.023
970601AG2-382 GEN
Solar/Wind Harmer
10.228
965291AG1-394 GEN
Solar/Wind Harmer
2.057
316315AB2-025 C
Solar/Wind Harmer
0.62
316318V4-068
Solar/Wind Harmer
0.572
3145893MURPHYS
Solar/Wind Harmer
-0.062
3145893MURPHYS
Solar/Wind Harmer
-0.023
315814AE2-033 C
Solar/Wind Harmer
21.332
3145513AHOSKIE
Solar/Wind Harmer
0.197
961941AG1-037 GEN
Solar/Wind Harmer
0.17
3145513AHOSKIE
Solar/Wind Harmer
-0.022
3145683EARLEYS
Solar/Wind Harmer
-0.045
3145683EARLEYS
Solar/Wind Harmer
-0.022
3145683EARLEYS
Solar/Wind Harmer
-0.022
3146043SEABORD
Solar/Wind Harmer
-0.022
315607AA1-063A GEN
Solar/Wind Harmer
2.208
315652AC1-086 GEN
Solar/Wind Harmer
23.87
3146033SCOT NK
Solar/Wind Harmer
-0.084
946281AF1-292 GEN
Solar/Wind Harmer
0.472
316087AB2-174 GEN
Solar/Wind Harmer
3.004
3137643SOCKMAN
Solar/Wind Harmer
-0.084
3145796HORNRTN
Solar/Wind Harmer
-0.066
3145796HORNRTN
Solar/Wind Harmer
-0.008
316005AA1-067
Solar/Wind Harmer
0.414
3145746EVERETS
Solar/Wind Harmer
-0.081
3145746EVERETS
Solar/Wind Harmer
-0.02
3145746EVERETS
Solar/Wind Harmer
-0.02
3145746EVERETS
Solar/Wind Harmer
-0.02
970181AG2-120 GEN
Solar/Wind Harmer
2.686
957861AF2-080 GEN
Solar/Wind Harmer
8.726
941031AE2-094 GEN
Solar/Wind Harmer
37.194
944011AF1-069 GEN
Solar/Wind Harmer
11.654
316420AA1-050 GEN
Solar/Wind Harmer
2.249
970673AG2-436 GEN
Solar/Wind Harmer
41.211
970673AG2-436 GEN
Solar/Wind Harmer
20.866
3145573BETHELC
Solar/Wind Harmer
-0.019
3145573BETHELC
Solar/Wind Harmer
-0.019
971967AH1-528 GEN
Solar/Wind Harmer
36.595
316319Z2-044 C
Solar/Wind Harmer
1.068
970831AG2-522 GEN
Solar/Wind Harmer
9.67
316223AC1-118
Solar/Wind Harmer
0.521
970085AG2-068 GEN
Solar/Wind Harmer
11.788
970581AG2-369 GEN
Solar/Wind Harmer
10.137
3151881LOWMORC
Adder
1.481
3151881LOWMORC
Adder
1.458
3151861LOWMORA
Adder
1.434
972205AH1-687 GEN
Adder
5.807
316164AC1-076 GEN
Solar/Wind Helper
1.314
316411AF1-147_GEN1
Solar/Wind Helper
0.8
316415AF1-147_GEN2
Solar/Wind Helper
0.8
3138216PACIFIC
Solar/Wind Helper
0.039
NYPJM->LTFIMP_NY
CLTF
3.379
LGEELTFEXP_LGEE->PJM
CLTF
2.17
WECLTFEXP_WEC->PJM
CLTF
1.094
AG2-052LTFEXP_AG2-052->PJM
LTF
0.061
AH1-155LTFEXP_AH1-155->PJM
LTF
0.092
LAGNLTFEXP_LAGN->PJM
CLTF
9.826
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.132
TVALTFEXP_TVA->PJM
CLTF
4.998
CBM West 1LTFEXP_CBM-W1->PJM
CBM
38.594
CBM South 1LTFEXP_CBM-S1->PJM
CBM
17.524
MECLTFEXP_MEC->PJM
CLTF
5.518
SIGELTFEXP_SIGE->PJM
CLTF
0.172
CPLELTFEXP_CPLE->PJM
CLTF
10.849
CBM West 2LTFEXP_CBM-W2->PJM
CBM
55.102

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:173.01 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:7041.78
MW Contribution:191.94
Bus #Bus NameTypeMW Contribution
971645AH1-323 GEN
50/50
34.852
3151161SURRY 1
50/50
14.066
3142416OLDCHRC
Solar/Wind Harmer
3.771
970293AG2-193 GEN
Solar/Wind Harmer
4.092
3142946ENON
Solar/Wind Harmer
0.127
316382AG1-145 C
Solar/Wind Harmer
0.003
3143096IRON208
Adder
1.57
3143096IRON208
Adder
1.539
3150921YORKTN3
Adder
9.356
3144216WINCHST
Adder
1.402
315773AC2-141 GEN
Solar/Wind Harmer
13.538
970133AG2-095 GEN
Solar/Wind Harmer
3.544
970129AG2-093 GEN
Solar/Wind Harmer
22.266
315778AD1-151 GEN
Solar/Wind Harmer
29.426
961611AG1-000B GEN
Solar/Wind Harmer
9.778
3151221GRAVEL6
Adder
26.624
3151171GRAVELC
Adder
5.122
3150861SPRUNCD
Adder
1.682
3145336SMITFLD
Solar/Wind Harmer
0.146
3144536CHRHLND
Solar/Wind Harmer
0.054
944581AF1-123 GEN
Solar/Wind Harmer
81.792
944601AF1-125 GEN
Solar/Wind Harmer
80.532
3151101ELIZAR3
Adder
33.706
3144873MCLAUGH
Solar/Wind Harmer
0.009
965281AG1-393 GEN
Solar/Wind Harmer
3.845
315839AE2-212 C
Solar/Wind Harmer
0.003
3142433PROV 92
Adder
0.696
3142433PROV 92
Adder
0.696
3146456SLIGO L269
Solar/Wind Harmer
0.358
971153AH1-033 GEN
Solar/Wind Harmer
4.14
316473AC1-191 GEN
Solar/Wind Harmer
1.209
315813AE1-149 C
Solar/Wind Harmer
19.023
970659AG2-427 GEN
Solar/Wind Harmer
3.767
316083AB2-161 GEN
Solar/Wind Harmer
0.005
970661AG2-428 GEN
Solar/Wind Harmer
7.524
316320Y1-086
Solar/Wind Harmer
0.002
316435W1029_GEN3
Solar/Wind Harmer
0.002
3141766HARMONY
Solar/Wind Harmer
4.656
3146516WINFALL
Solar/Wind Harmer
0.349
3141843SHACKLE
Adder
1.778
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3146626S HERTFORD
Solar/Wind Harmer
0.346
316280AD1-041 GEN
Solar/Wind Harmer
0.007
3145273HOLLAND
Solar/Wind Harmer
0.258
316156AD2-030 GEN
Solar/Wind Harmer
0.254
3141873WAN 176
Solar/Wind Harmer
6.098
3146376EDENTON
Solar/Wind Harmer
0.338
315614AA2-178 GEN
Solar/Wind Harmer
1.889
971157AH1-035 GEN
Solar/Wind Harmer
3.886
315737AD1-076 GEN
Solar/Wind Harmer
4.152
972255AH1-712 GEN
Adder
164.714
3156081AA2-088 GEN
Solar/Wind Harmer
0.008
3146206CASHIE
Solar/Wind Harmer
0.318
3145893MURPHYS
Solar/Wind Harmer
0.528
3145893MURPHYS
Solar/Wind Harmer
0.316
957521AF2-046 GEN
Solar/Wind Harmer
23.434
961681AG1-008 GEN
Solar/Wind Harmer
23.434
962971AG1-146 GEN
Solar/Wind Harmer
5.016
3156021HOLLOMANSOL
Solar/Wind Harmer
1.422
3146173TUNIS
Solar/Wind Harmer
0.313
316365GEN2_N
Solar/Wind Harmer
0.699
316463AE2-346 GEN
Solar/Wind Harmer
0.267
316140AB2-099
Solar/Wind Harmer
0.111
962331AG1-082 GEN
Solar/Wind Harmer
3.322
970009AG2-005 GEN
Solar/Wind Harmer
2.291
3146263WOODLND
Solar/Wind Harmer
0.306
3145963POPLR C
Solar/Wind Harmer
0.306
970917AG2-570 GEN
Solar/Wind Harmer
27.198
316317KELFORD C
Solar/Wind Harmer
0.029
3145823KELFORD
Solar/Wind Harmer
0.303
3142666NORTHAMPTON
Solar/Wind Harmer
0.302
313506AB2-031 GEN
Solar/Wind Harmer
0.929
3145796HORNRTN
Solar/Wind Harmer
1.185
3145796HORNRTN
Solar/Wind Harmer
0.296
316404AE1-155 C
Solar/Wind Harmer
0.067
3145933PARMELE
Solar/Wind Harmer
0.292
966801AG1-551 GEN
Solar/Wind Harmer
3.408
3147043LAWRENC
Solar/Wind Harmer
0.175
316210AC1-098 GEN
Solar/Wind Harmer
2.699
316313AB2-026
Solar/Wind Harmer
0.183
316258AE1-075 C
Solar/Wind Harmer
0.219
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
4.377
3145746EVERETS
Solar/Wind Harmer
0.286
3145746EVERETS
Solar/Wind Harmer
0.286
315724AD1-057 GEN
Solar/Wind Harmer
1.059
316478AD1-087 GEN
Solar/Wind Harmer
0.983
316486AD2-202 GEN
Solar/Wind Harmer
0.289
316327AA2-057 GEN
Solar/Wind Harmer
0.423
3150351NORNECKC2
Adder
2.804
3146073TAR RVR
Solar/Wind Harmer
0.276
3146083TARBORO
Solar/Wind Harmer
0.276
3146233WITAKRS
Solar/Wind Harmer
1.382
3146233WITAKRS
Solar/Wind Harmer
0.187
3138543CONSLDL
Solar/Wind Harmer
0.181
961601AG1-000A GEN
Solar/Wind Harmer
19.24
3145543BTLEBRO
Solar/Wind Harmer
0.27
3145543BTLEBRO
Solar/Wind Harmer
0.27
971623AH1-311 GEN
Solar/Wind Harmer
0.541
316131AB2-060 GEN
Solar/Wind Harmer
0.835
964241AG1-285 GEN
Solar/Wind Harmer
17.596
970909AG2-566 GEN
Solar/Wind Harmer
2.793
315785AD2-033 C
Solar/Wind Harmer
2.125
970257AG2-171 GEN
Solar/Wind Harmer
8.336
959311AF2-222 GEN
Solar/Wind Harmer
23.097
963181AG1-167 GEN
Solar/Wind Harmer
1.024
3144293JTRSVLE
Adder
0.815
3147133PAMPLIN
Solar/Wind Harmer
0.798
971193AH1-056 GEN
Solar/Wind Harmer
15.489
971781AH1-399 GEN
Solar/Wind Harmer
0.329
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
10.514
3146926FARMVIL
Solar/Wind Harmer
0.147
971683AH1-343 GEN
Solar/Wind Harmer
8.489
3146776BUCKING
Solar/Wind Harmer
0.082
316283AC2-100 C
Solar/Wind Harmer
0.444
3141906WESTMOR
Solar/Wind Harmer
0.083
970221AG2-151 GEN
Solar/Wind Harmer
10.629
970737AG2-469 GEN
Solar/Wind Harmer
7.511
270197AD1-017 GEN1
Solar/Wind Harmer
1.056
3147312GRETNA
Solar/Wind Harmer
0.032
941821AE2-187 GEN
Solar/Wind Harmer
5.072
270018AE2-047 C O1
Solar/Wind Harmer
0.003
3148013FISHERV
Solar/Wind Harmer
0.154
315616AA1-038_C
Solar/Wind Harmer
0.001
3151861LOWMORA
Adder
1.607
958131AF2-107 GEN
Solar/Wind Harmer
4.297
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
270336AE1-100 GEN
Solar/Wind Harmer
0.004
971367AH1-164 GEN
Solar/Wind Harmer
2.405
316044AC1-158 PL1
Solar/Wind Helper
2.503
316450AC1-158 RIC
Solar/Wind Helper
0.667
3141196NOKESVL
Solar/Wind Helper
1.389
316170AC1-121 GEN2
Solar/Wind Helper
0.521
3147666LOUISA
Solar/Wind Helper
0.737
227287AC2-120 GEN
Solar/Wind Helper
0.432
226910AB2-157 C
Solar/Wind Helper
0.018
223402AF1-300 C
Solar/Wind Helper
0.393
3132273ORANGE
Solar/Wind Helper
0.053
237030AB1-096 C
Solar/Wind Helper
0.069
238221AF1-254 C O1
Solar/Wind Helper
0.238
235067AD1-061 GEN
Solar/Wind Helper
0.424
205917AD1-020 ES
Solar/Wind Helper
0.354
233918AB1-142 GEN
Solar/Wind Helper
0.486
233982AB2-133 GEN
Solar/Wind Helper
0.346
233994AC2-023 GEN
Solar/Wind Helper
0.929
233996TM1833_GEN
Solar/Wind Helper
0.253
233997TMININ_4.2
Solar/Wind Helper
0.253
232406W1-004 FULL
Solar/Wind Helper
0.491
233940AF2-379 C
Solar/Wind Helper
0.06
234015AF2-250 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.225
233971AC1-093 C
Solar/Wind Helper
0.346
230430AE1-229_GEN
Solar/Wind Helper
3.238
230415AB2-049 C
Solar/Wind Helper
0.029
228729W2-030 C
Solar/Wind Helper
0.106
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.052
219912AD2-042 GEN
Solar/Wind Helper
0.144
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
3142296MT RD221
50/50
1.311
3150691DARBY 3
50/50
29.113
3150701DARBY 4
50/50
29.046
3150681DARBY 2
50/50
29.012
3150671DARBY 1
50/50
28.978
3142366NRTHEST
50/50
1.317
316075AC2-137 C
Solar/Wind Harmer
0.106
3142946ENON
Solar/Wind Harmer
0.038
316033AB2-134 GEN
Solar/Wind Harmer
0.022
315697AD1-025 GEN
Solar/Wind Harmer
0.413
944641AF1-129 GEN
Adder
174.18
316236AE1-162_GEN
Solar/Wind Harmer
0.003
316240AF1-291 C
Solar/Wind Harmer
0.003
316036AC1-147 C
Solar/Wind Harmer
0.067
3150991CHESPKB
Adder
3.801
3150991CHESPKB
Adder
3.71
316316AC1-027 C
Solar/Wind Harmer
0.347
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.01
3145506HICKORY
Solar/Wind Harmer
1.442
3145506HICKORY
Solar/Wind Harmer
0.865
3145506HICKORY
Solar/Wind Harmer
0.217
316339AD2-160 GEN
Solar/Wind Harmer
0.583
316018AA1-139 ULT2
Solar/Wind Harmer
0.009
316017AA1-139 ULT1
Solar/Wind Harmer
0.2
3137176SLIGO L2192
Solar/Wind Harmer
1.425
3146456SLIGO L269
Solar/Wind Harmer
6.337
966871AG1-558 GEN
Solar/Wind Harmer
0.414
3130086AYDLETT
Solar/Wind Harmer
1.43
970657AG2-426 GEN
Solar/Wind Harmer
12.462
970657AG2-426 GEN
Solar/Wind Harmer
2.613
3143526WINTERP
Solar/Wind Harmer
1.841
3146386ELIZ CT
Solar/Wind Harmer
0.354
316431W1029_GEN1
Solar/Wind Harmer
0.002
316433W1029_GEN2
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.349
3146516WINFALL
Solar/Wind Harmer
0.349
3146516WINFALL
Solar/Wind Harmer
0.349
3146626S HERTFORD
Solar/Wind Harmer
0.346
3146626S HERTFORD
Solar/Wind Harmer
0.346
971223AH1-071 GEN
Solar/Wind Harmer
3.664
315742AE1-103 GEN
Solar/Wind Harmer
0.004
3146376EDENTON
Solar/Wind Harmer
1.504
3146376EDENTON
Solar/Wind Harmer
1.504
3144356SAPONY
Solar/Wind Harmer
2.786
316065AD1-022 GEN
Solar/Wind Harmer
14.743
972185AH1-677 GEN
Adder
17.914
3145893MURPHYS
Solar/Wind Harmer
2.113
3145893MURPHYS
Solar/Wind Harmer
0.568
972187AH1-678 GEN
Adder
8.995
3146173TUNIS
Solar/Wind Harmer
0.313
3146173TUNIS
Solar/Wind Harmer
0.313
970933AG2-581 GEN
Solar/Wind Harmer
24.83
3142666NORTHAMPTON
Solar/Wind Harmer
0.302
3142666NORTHAMPTON
Solar/Wind Harmer
0.302
3142666NORTHAMPTON
Solar/Wind Harmer
0.302
3142666NORTHAMPTON
Solar/Wind Harmer
0.181
316181AB2-040 GEN
Solar/Wind Harmer
0.436
316426AA2-053 GEN
Solar/Wind Harmer
1.013
3145593CAROLNA
Solar/Wind Harmer
0.298
3145593CAROLNA
Solar/Wind Harmer
0.298
966811AG1-552 GEN
Solar/Wind Harmer
3.231
3145593CAROLNA
Solar/Wind Harmer
0.371
3145796HORNRTN
Solar/Wind Harmer
0.889
3145783HORNRTN
Solar/Wind Harmer
5.27
3145783HORNRTN
Solar/Wind Harmer
4.216
3145783HORNRTN
Solar/Wind Harmer
1.317
3145783HORNRTN
Solar/Wind Harmer
0.527
958261AF2-120 GEN
Solar/Wind Harmer
9.788
3145933PARMELE
Solar/Wind Harmer
0.585
3145933PARMELE
Solar/Wind Harmer
0.292
970099AG2-077 GEN
Solar/Wind Harmer
31.087
316274AC1-208 GEN
Solar/Wind Harmer
1.496
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.897
3150341NORNECKC1
Adder
2.874
3145493TOT1
Solar/Wind Harmer
0.64
3145453TOT5
Solar/Wind Harmer
0.384
3145603CNETO
Solar/Wind Harmer
0.256
961601AG1-000A GEN
Solar/Wind Harmer
4.81
316263AC1-034 GEN
Solar/Wind Harmer
10.275
939181AE1-148 GEN
Solar/Wind Harmer
12.944
971741AH1-377 GEN
Solar/Wind Harmer
26.49
313527AB2-043 GEN
Solar/Wind Harmer
0.003
970301AG2-198 GEN
Solar/Wind Harmer
11.171
970323AG2-213 GEN
Solar/Wind Harmer
11.115
971775AH1-396 GEN
Solar/Wind Harmer
0.417
316034AC1-036 C
Solar/Wind Harmer
0.019
962561AG1-105 GEN
Solar/Wind Harmer
12.3
958211AF2-115 GEN
Solar/Wind Harmer
3.071
963191AG1-168 GEN
Solar/Wind Harmer
1.024
3144293JTRSVLE
Adder
0.815
3144293JTRSVLE
Adder
0.686
964791AG1-342 GEN
Solar/Wind Harmer
4.887
3146843MT LREL
Solar/Wind Harmer
0.254
3146843MT LREL
Solar/Wind Harmer
0.254
3147133PAMPLIN
Solar/Wind Harmer
0.254
3147133PAMPLIN
Solar/Wind Harmer
0.203
316468AD1-105 GEN
Solar/Wind Harmer
-0.081
3146776BUCKING
Solar/Wind Harmer
0.914
3146776BUCKING
Solar/Wind Harmer
0.074
316222AC1-221 GEN
Solar/Wind Harmer
0.945
971489AH1-241 GEN
Solar/Wind Harmer
10.629
942751AE2-291 GEN
Solar/Wind Harmer
10.765
315821AE2-092 GEN
Solar/Wind Harmer
0.011
270013AE1-250 PV
Solar/Wind Harmer
0.005
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.002
942671AE2-283 GEN
Solar/Wind Harmer
3.945
316447AC1-158 HLD
Solar/Wind Helper
5.508
315651AD1-115 GEN
Solar/Wind Helper
1.146
226929AD2-058 GEN
Solar/Wind Helper
0.127
23777801MSM_W1-116
Solar/Wind Helper
0.11
237025AB1-124 C
Solar/Wind Helper
0.159
237006AB1-125 GEN
Solar/Wind Helper
0.12
237034AC2-136 C
Solar/Wind Helper
0.207
23777901MDS_W4-102
Solar/Wind Helper
0.152
235020AA1-095 C
Solar/Wind Helper
0.045
237001AB1-127_GEN
Solar/Wind Helper
0.385
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
237002AB1-128_GEN
Solar/Wind Helper
0.384
235063AE1-101 C2
Solar/Wind Helper
1.423
205916AD1-020 GEN
Solar/Wind Helper
1.645
233933AB2-153 GEN
Solar/Wind Helper
0.225
233944AB2-135 GEN
Solar/Wind Helper
0.569
232424Y1-079 C
Solar/Wind Helper
0.112
233987AB2-037 GEN
Solar/Wind Helper
2.265
233946AB2-136 GEN
Solar/Wind Helper
0.549
234036AF2-325 C
Solar/Wind Helper
0.041
233901CHERRYDALE C
Solar/Wind Helper
0.225
232408W1-005 C
Solar/Wind Helper
0.491
232410W1-006 C
Solar/Wind Helper
0.491
233939AC1-091 C
Solar/Wind Helper
0.338
233970AC1-092 C
Solar/Wind Helper
0.338
238175AF1-290_GEN
Solar/Wind Helper
0.118
230433AD2-135 GEN
Solar/Wind Helper
0.016
230407AD2-065 C
Solar/Wind Helper
0.039
219921AF1-264
Solar/Wind Helper
0.049
972263AH1-716 GEN
50/50
220.54
316312AB1-027
Solar/Wind Harmer
0.696
315976AC1-164 GENA
Solar/Wind Harmer
40.142
316169AC1-164_GENC
Solar/Wind Harmer
34.679
315975AC1-164 GENB
Solar/Wind Harmer
1.188
316132AB2-190 GEN1
Solar/Wind Harmer
1.976
316369SG1_INVT
Solar/Wind Harmer
0.014
972265AH1-717 GEN
Adder
28.433
3151201GRAVEL4
Adder
26.654
3151191GRAVEL3
Adder
26.317
3151211GRAVEL5
Adder
26.317
971445AH1-216 GEN
Solar/Wind Harmer
25.708
971285AH1-108 GEN
Adder
2.752
3151081ELIZAR1
Adder
33.28
3151091ELIZAR2
Adder
32.702
3152611GOSPORTB
Adder
4.621
3152621GOSPORTC
Adder
3.922
3152601GOSPORTA
Adder
3.618
971167AH1-042 GEN
Solar/Wind Harmer
31.907
957871AF2-081 GEN
Solar/Wind Harmer
17.869
3142433PROV 92
Adder
0.696
3142433PROV 92
Adder
0.696
3138283WHITEMARSH
Solar/Wind Harmer
0.083
319010AE1-072 C
Solar/Wind Harmer
1.802
3146406KITTY HAWK
Solar/Wind Harmer
0.045
316305AF2-043 C
Solar/Wind Harmer
0.003
315833AF1-017_GEN
Solar/Wind Harmer
0.002
316349AD2-085 GEN
Solar/Wind Harmer
0.243
316311AC2-079 GEN
Solar/Wind Harmer
10.187
3143873LANEXA
Solar/Wind Harmer
0.213
316233AE1-074 FULL
Solar/Wind Harmer
0.283
971281AH1-106 GEN
Solar/Wind Harmer
4.913
971283AH1-107 GEN
Solar/Wind Harmer
4.913
315835AF2-110_GEN
Solar/Wind Harmer
2.43
313526AB2-022
Solar/Wind Harmer
0.192
316314AB2-024 C
Solar/Wind Harmer
0.001
3146486SUNBURY
Solar/Wind Harmer
0.352
3146486SUNBURY
Solar/Wind Harmer
0.352
3143316POE
Solar/Wind Harmer
1.396
316321Z2-027
Solar/Wind Harmer
0.065
3146396TANGLEW
Solar/Wind Harmer
0.971
3145176PASQUOTANK
Solar/Wind Harmer
0.218
316059AD1-063 C
Solar/Wind Harmer
0.002
970189AG2-124 GEN
Solar/Wind Harmer
10.307
315662AE1-191 GEN
Solar/Wind Harmer
0.011
315666AE1-190 GEN
Solar/Wind Harmer
0.003
3141873WAN 176
Solar/Wind Harmer
0.069
315611Z1-036_GEN2
Solar/Wind Harmer
0.003
3130156CHOWAN
Solar/Wind Harmer
0.338
3130156CHOWAN
Solar/Wind Harmer
0.338
3141913WHIT STONE
Solar/Wind Harmer
0.333
316315AB2-025 C
Solar/Wind Harmer
0.269
315814AE2-033 C
Solar/Wind Harmer
26.26
3138133OCRAN
Solar/Wind Harmer
0.099
315816AE2-034 GEN
Solar/Wind Harmer
1.417
941031AE2-094 GEN
Solar/Wind Harmer
60.194
944011AF1-069 GEN
Solar/Wind Harmer
19.668
3141783LANCAST
Solar/Wind Harmer
0.195
3141783LANCAST
Solar/Wind Harmer
0.13
3130546PLYMOUTH
Solar/Wind Harmer
0.324
315732AD1-074 GEN1
Solar/Wind Harmer
1.854
315733AD1-074 GEN2
Solar/Wind Harmer
1.854
315735AD1-075 GEN1
Solar/Wind Harmer
0.928
972193AH1-681 GEN
Adder
7.36
970673AG2-436 GEN
Solar/Wind Harmer
68.642
970673AG2-436 GEN
Solar/Wind Harmer
45.761
3146206CASHIE
Solar/Wind Harmer
0.318
970601AG2-382 GEN
Solar/Wind Harmer
11.901
965291AG1-394 GEN
Solar/Wind Harmer
1.416
971967AH1-528 GEN
Solar/Wind Harmer
50.838
3145893MURPHYS
Solar/Wind Harmer
0.852
3145893MURPHYS
Solar/Wind Harmer
0.316
962981AG1-147 GEN
Solar/Wind Harmer
11.703
3145513AHOSKIE
Solar/Wind Harmer
0.651
3145513AHOSKIE
Solar/Wind Harmer
0.311
3145683EARLEYS
Solar/Wind Harmer
0.62
3145683EARLEYS
Solar/Wind Harmer
0.31
3145683EARLEYS
Solar/Wind Harmer
0.31
3146043SEABORD
Solar/Wind Harmer
0.307
970327AG2-215 GEN
Solar/Wind Harmer
10.069
315607AA1-063A GEN
Solar/Wind Harmer
0.625
970085AG2-068 GEN
Solar/Wind Harmer
16.26
970581AG2-369 GEN
Solar/Wind Harmer
13.984
316087AB2-174 GEN
Solar/Wind Harmer
0.009
315652AC1-086 GEN
Solar/Wind Harmer
33.087
3137643SOCKMAN
Solar/Wind Harmer
1.194
3145796HORNRTN
Solar/Wind Harmer
0.948
3145796HORNRTN
Solar/Wind Harmer
0.119
3146033SCOT NK
Solar/Wind Harmer
1.185
316005AA1-067
Solar/Wind Harmer
0.307
3145746EVERETS
Solar/Wind Harmer
1.138
3145746EVERETS
Solar/Wind Harmer
0.286
3145746EVERETS
Solar/Wind Harmer
0.286
3145746EVERETS
Solar/Wind Harmer
0.286
970181AG2-120 GEN
Solar/Wind Harmer
3.56
970831AG2-522 GEN
Solar/Wind Harmer
12.024
957861AF2-080 GEN
Solar/Wind Harmer
12.104
316420AA1-050 GEN
Solar/Wind Harmer
0.009
3141813NORNECK
Solar/Wind Harmer
0.276
3145573BETHELC
Solar/Wind Harmer
0.276
3145573BETHELC
Solar/Wind Harmer
0.276
316319Z2-044 C
Solar/Wind Harmer
0
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
4.38
3144303KENBRDG
Solar/Wind Harmer
0.208
3152331SURRY 2
50/50
15.859
3142416OLDCHRC
Solar/Wind Harmer
1.011
3142416OLDCHRC
Solar/Wind Harmer
0.387
316159AE1-175 C
Solar/Wind Harmer
0.327
944631AF1-128 GEN
Adder
179.515
3143096IRON208
Adder
1.57
3138126ROCKLANDING
Solar/Wind Harmer
0.171
972189AH1-679 GEN
Adder
4.36
970683AG2-441 GEN
Solar/Wind Harmer
17.21
970681AG2-440 GEN
Solar/Wind Harmer
13.768
946301AF1-294 GEN
Solar/Wind Harmer
5.05
961791AG1-021 GEN
Solar/Wind Harmer
2.457
315657AE1-056 GEN
Solar/Wind Harmer
8.773
316118AC1-105 GEN
Solar/Wind Harmer
0.646
3147173SINAI
Solar/Wind Harmer
0.246
3147243WELCO
Solar/Wind Harmer
0.154
970285AG2-188 GEN
Solar/Wind Harmer
18.408
971845AH1-439 GEN
Solar/Wind Harmer
10.428
970865AG2-541 GEN
Solar/Wind Harmer
7.734
972205AH1-687 GEN
Adder
8.917
316223AC1-118
Solar/Wind Harmer
0.15
316123AC1-075 GEN
Solar/Wind Harmer
0.284
970165AG2-112 GEN
Solar/Wind Harmer
1.683
970163AG2-111 GEN
Solar/Wind Harmer
1.606
971447AH1-217 GEN
Solar/Wind Harmer
5.953
270494AE1-108_GEN
Solar/Wind Harmer
2.206
3148133STUARTS
Solar/Wind Harmer
0.092
3148013FISHERV
Solar/Wind Harmer
0.088
3148463FAIRFLD
Solar/Wind Harmer
0.15
3151881LOWMORC
Adder
1.595
3151881LOWMORC
Adder
1.57
3151861LOWMORA
Adder
1.545
270069AE2-166 C O1
Solar/Wind Harmer
0.005
944491AF1-114 GEN
Solar/Wind Harmer
0
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316164AC1-076 GEN
Solar/Wind Helper
1.845
316411AF1-147_GEN1
Solar/Wind Helper
1.079
316415AF1-147_GEN2
Solar/Wind Helper
1.079
3138216PACIFIC
Solar/Wind Helper
0.053
3141426STAFORD
Solar/Wind Helper
0.061
237085AD2-009_GEN
Solar/Wind Helper
1.388
960921AF2-383 GEN
Solar/Wind Helper
0.352
233935AB2-179 C
Solar/Wind Helper
1.229
205943AE1-185 GEN
Solar/Wind Helper
0.491
232436AB1-176 C
Solar/Wind Helper
0.043
205932AD2-116_GEN
Solar/Wind Helper
0.491
205956AE1-196_GEN
Solar/Wind Helper
0.491
233923SMA
Solar/Wind Helper
0.927
233990AG1-397 GEN
Solar/Wind Helper
0.261
232432Z2-076 GEN
Solar/Wind Helper
0.065
234033AF1-007_GEN
Solar/Wind Helper
6.788
238208AF1-136 C
Solar/Wind Helper
0.173
964001AG1-254 GEN
Solar/Wind Helper
0.917
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.025
219914AD2-027 C
Solar/Wind Helper
0.11
219272CLEANLIGHT C
Solar/Wind Helper
0.024
219688LUMSOLAR_S C
Solar/Wind Helper
0.038
971317AH1-138 GEN
Solar/Wind Harmer
2.773
316294AC1-161 GEN
Solar/Wind Harmer
6.422
3142543TWELFTH
Solar/Wind Harmer
0.035
970129AG2-093 GEN
Solar/Wind Harmer
10.478
316458AB2-190 GEN2
Solar/Wind Harmer
1.976
971069AG2-661 GEN
Solar/Wind Harmer
6.539
971647AH1-324 GEN
Solar/Wind Harmer
15.662
961611AG1-000B GEN
Solar/Wind Harmer
19.23
3151171GRAVELC
Adder
3.895
3150851SPRUNCC
Adder
1.682
3145336SMITFLD
Solar/Wind Harmer
1.459
944591AF1-124 GEN
Solar/Wind Harmer
82.083
316375AC2-012 GEN
Solar/Wind Harmer
0.009
3150981CHESPKA
Adder
4.531
315671AE2-027_GEN
Solar/Wind Harmer
23.135
316072AD1-144
Solar/Wind Harmer
0.13
316388AE2-253 GEN
Solar/Wind Harmer
1.126
3142433PROV 92
Solar/Wind Harmer
1.432
3142433PROV 92
Adder
0.696
3142433PROV 92
Adder
0.696
3146456SLIGO L269
Solar/Wind Harmer
0.358
316246AF1-032 C
Solar/Wind Harmer
0.161
970659AG2-427 GEN
Solar/Wind Harmer
17.218
316381AD1-082 GEN
Solar/Wind Harmer
0.371
970661AG2-428 GEN
Solar/Wind Harmer
35.374
3143526WINTERP
Solar/Wind Harmer
1.841
316093AE2-104_GEN
Solar/Wind Harmer
5.955
3141766HARMONY
Solar/Wind Harmer
0.07
3146516WINFALL
Solar/Wind Harmer
1.13
3146516WINFALL
Solar/Wind Harmer
0.349
971777AH1-397 GEN
Solar/Wind Harmer
0.918
3141843SHACKLE
Adder
1.778
939411AE1-173 GEN
Solar/Wind Harmer
148.397
3143226MDLTHAN
Solar/Wind Harmer
0.343
940641AE2-051 GEN
Solar/Wind Harmer
27.456
315800Z1-036_GEN1
Solar/Wind Harmer
0.003
3130156CHOWAN
Solar/Wind Harmer
0.338
3138133OCRAN
Solar/Wind Harmer
0.198
3145663CRESWEL
Solar/Wind Harmer
0.924
971163AH1-040 GEN
Solar/Wind Harmer
26.412
972277AH1-723 GEN
Adder
191.941
3146206CASHIE
Solar/Wind Harmer
0.318
971547AH1-271 GEN
Solar/Wind Harmer
6.801
3145893MURPHYS
Solar/Wind Harmer
1.262
3145893MURPHYS
Solar/Wind Harmer
1.404
3146173TUNIS
Solar/Wind Harmer
0.313
316023GEN1_S
Solar/Wind Harmer
0.699
3145683EARLEYS
Solar/Wind Harmer
0.31
3146263WOODLND
Solar/Wind Harmer
0.306
3145963POPLR C
Solar/Wind Harmer
0.306
970919AG2-571 GEN
Solar/Wind Harmer
10.879
970087AG2-069 GEN
Solar/Wind Harmer
24.391
316174AB2-169 GEN
Solar/Wind Harmer
0.008
3145823KELFORD
Solar/Wind Harmer
0.303
960081AF2-299 GEN
Solar/Wind Harmer
2.907
316011AB1-132 GEN
Solar/Wind Harmer
5.469
962571AG1-106 GEN
Solar/Wind Harmer
4.28
316190AA2-174 GEN
Solar/Wind Harmer
0.001
962861AG1-135 GEN
Solar/Wind Harmer
9.564
3145796HORNRTN
Solar/Wind Harmer
0.978
3145796HORNRTN
Solar/Wind Harmer
0.296
3145783HORNRTN
Solar/Wind Harmer
0.296
971795AH1-408 GEN
Solar/Wind Harmer
19.673
3146293MARTNCO
Solar/Wind Harmer
0.271
3147043LAWRENC
Adder
2.638
957481AF2-042 GEN
Solar/Wind Harmer
77.718
316212AC1-099_GEN
Solar/Wind Harmer
1.505
3143336POWHATN
Solar/Wind Harmer
5.15
3141726DUNNSVL
Solar/Wind Harmer
1.146
3145746EVERETS
Solar/Wind Harmer
0.286
3145746EVERETS
Solar/Wind Harmer
0.286
315693AD1-088 GEN
Solar/Wind Harmer
13.658
962491AG1-098 GEN
Solar/Wind Harmer
16.171
315722AD1-056 GEN
Solar/Wind Harmer
1.786
316494AC1-189 GEN
Solar/Wind Harmer
0.948
316129AC1-054 GEN
Solar/Wind Harmer
1.053
971065AG2-659 GEN
Solar/Wind Harmer
11.883
3150351NORNECKC2
Adder
2.758
961671AG1-007 GEN
Solar/Wind Harmer
0.042
3146083TARBORO
Solar/Wind Harmer
0.276
3145493TOT1
Solar/Wind Harmer
1.227
316336AC2-165 C
Solar/Wind Harmer
0.011
3146233WITAKRS
Solar/Wind Harmer
1.096
3145543BTLEBRO
Solar/Wind Harmer
0.27
3145543BTLEBRO
Solar/Wind Harmer
0.216
316359AB2-059 GEN
Solar/Wind Harmer
0.971
316049AB1-081 GEN
Solar/Wind Harmer
1.547
3142053HEARTS
Solar/Wind Harmer
0.476
315687AD1-152 GEN
Solar/Wind Harmer
0.009
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970685AG2-442 GEN
Solar/Wind Harmer
19.275
963171AG1-166 GEN
Solar/Wind Harmer
1.365
971563AH1-280 GEN
Solar/Wind Harmer
2.73
3144293JTRSVLE
Adder
0.815
970401AG2-262 GEN
Solar/Wind Harmer
1.493
3146926FARMVIL
Solar/Wind Harmer
0.147
316337AD2-073 GEN
Solar/Wind Harmer
0.212
970937AG2-583 GEN
Solar/Wind Harmer
14.682
316003AC1-222 GEN
Solar/Wind Harmer
0.006
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.091
972003AH1-546 GEN
Solar/Wind Harmer
9.023
971377AH1-170 GEN
Solar/Wind Harmer
2.126
3147623JAMES R
Solar/Wind Harmer
0.462
970223AG2-152 GEN
Solar/Wind Harmer
12.134
270016AE1-250 BESS
Solar/Wind Harmer
0.005
3147123OTTER R
Solar/Wind Harmer
0.1
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
3147312GRETNA
Solar/Wind Harmer
0.127
3146802CHATHAM
Solar/Wind Harmer
0.119
941801AE2-185 GEN
Solar/Wind Harmer
5.072
972135AH1-637 GEN
Solar/Wind Harmer
1.317
270173AC1-122 GEN
Solar/Wind Harmer
0.358
270030AE2-140 GEN
Solar/Wind Harmer
15.132
962751AG1-124 GEN
Solar/Wind Harmer
6.367
315705AF1-075 GEN
Solar/Wind Harmer
5.115
316045AC1-158 PL2
Solar/Wind Helper
8.011
316006AB2-029 C
Solar/Wind Helper
0.164
316254AC1-120 GEN1
Solar/Wind Helper
1.563
3147666LOUISA
Solar/Wind Helper
1.282
316192AB2-158 GEN
Solar/Wind Helper
2.104
223401AF1-299 GEN
Solar/Wind Helper
0.393
23779801AA1-109
Solar/Wind Helper
0.185
237080AD1-060 GEN
Solar/Wind Helper
0.295
237038AE2-054 C
Solar/Wind Helper
0.233
235062AE1-101 C1
Solar/Wind Helper
1.423
966131AG1-482 GEN
Solar/Wind Helper
0.131
233930AB2-032 GEN
Solar/Wind Helper
0.368
233915AB1-141 GEN
Solar/Wind Helper
0.486
232422X3-066 FULL
Solar/Wind Helper
0.11
233964AF2-378 GEN
Solar/Wind Helper
0.04
232426Y1-080 FULL
Solar/Wind Helper
0.038
232428Y3-058 C
Solar/Wind Helper
0.327
233998TM1NIN_3.36
Solar/Wind Helper
0.253
232404W1-003 C
Solar/Wind Helper
0.491
232434Z2-077 GEN
Solar/Wind Helper
0.123
233954AC2-188 GEN
Solar/Wind Helper
0.225
233950AC2-186 GEN
Solar/Wind Helper
0.112
233972AC1-094 C
Solar/Wind Helper
0.292
230511AF1-262
Solar/Wind Helper
0.014
230434AG1-499 GEN
Solar/Wind Helper
0.221
228728W1-130C
Solar/Wind Helper
0.052
219258KINSLEYDEP C
Solar/Wind Helper
0.074
219904AC1-010 C
Solar/Wind Helper
0.058
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219907AC1-030 C
Solar/Wind Helper
0.032
219686LUMSOLAR_N C
Solar/Wind Helper
0.038
NYPJM->LTFIMP_NY
CLTF
4.634
LGEELTFEXP_LGEE->PJM
CLTF
3.014
WECLTFEXP_WEC->PJM
CLTF
1.525
AG2-052LTFEXP_AG2-052->PJM
LTF
0.084
AH1-155LTFEXP_AH1-155->PJM
LTF
0.126
LAGNLTFEXP_LAGN->PJM
CLTF
14.625
CBM South 2LTFEXP_CBM-S2->PJM
CBM
39.998
TVALTFEXP_TVA->PJM
CLTF
7.404
CBM West 1LTFEXP_CBM-W1->PJM
CBM
53.563
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.762
MECLTFEXP_MEC->PJM
CLTF
7.835
SIGELTFEXP_SIGE->PJM
CLTF
0.242
CPLELTFEXP_CPLE->PJM
CLTF
17.713
CBM West 2LTFEXP_CBM-W2->PJM
CBM
80.377

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H4T581_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H4T581_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:159.56 %
Rating:2913.0 MVA
Rating Type:C
MVA to Mitigate:4648.04
MW Contribution:184.68
Bus #Bus NameTypeMW Contribution
971645AH1-323 GEN
50/50
27.12
3152191CUNINGD
50/50
5.242
3152171CUNINGB
50/50
2.263
972255AH1-712 GEN
50/50
158.483
3142416OLDCHRC
Solar/Wind Harmer
3.328
970293AG2-193 GEN
Solar/Wind Harmer
3.904
316473AC1-191 GEN
Solar/Wind Harmer
3.272
3142946ENON
Solar/Wind Harmer
-0.01
316382AG1-145 C
Solar/Wind Harmer
0.885
3143096IRON208
Adder
1.07
3143096IRON208
Adder
1.048
3142433PROV 92
Adder
0.484
3142433PROV 92
Adder
0.484
3150921YORKTN3
Adder
6.223
3144216WINCHST
Adder
0.927
3141766HARMONY
Solar/Wind Harmer
2.457
3141843SHACKLE
Adder
1.242
316203AE2-005 GEN
Solar/Wind Harmer
11.514
970133AG2-095 GEN
Solar/Wind Harmer
3.068
316280AD1-041 GEN
Solar/Wind Harmer
2.042
970129AG2-093 GEN
Solar/Wind Harmer
15.196
316156AD2-030 GEN
Solar/Wind Harmer
0.716
3141873WAN 176
Solar/Wind Harmer
3.182
315778AD1-151 GEN
Solar/Wind Harmer
23.205
961611AG1-000B GEN
Solar/Wind Harmer
5.551
3151221GRAVEL6
Adder
16.937
3151171GRAVELC
Adder
3.259
3145336SMITFLD
Solar/Wind Harmer
-0.01
3150861SPRUNCD
Adder
1.049
315773AC2-141 GEN
Solar/Wind Harmer
10.693
965281AG1-393 GEN
Solar/Wind Harmer
3.169
3144536CHRHLND
Solar/Wind Harmer
-0.004
315839AE2-212 C
Solar/Wind Harmer
0.751
3151101ELIZAR3
Adder
20.522
3144873MCLAUGH
Solar/Wind Harmer
-0.001
944581AF1-123 GEN
Solar/Wind Harmer
112.441
944601AF1-125 GEN
Solar/Wind Harmer
110.686
962971AG1-146 GEN
Solar/Wind Harmer
4.588
3146456SLIGO L269
Solar/Wind Harmer
-0.024
971153AH1-033 GEN
Solar/Wind Harmer
2.967
315813AE1-149 C
Solar/Wind Harmer
15.174
970659AG2-427 GEN
Solar/Wind Harmer
2.279
316083AB2-161 GEN
Solar/Wind Harmer
3.927
970661AG2-428 GEN
Solar/Wind Harmer
4.549
316320Y1-086
Solar/Wind Harmer
1.405
316484AD2-074 GEN
Solar/Wind Harmer
6.027
970009AG2-005 GEN
Solar/Wind Harmer
2.993
316435W1029_GEN3
Solar/Wind Harmer
4.278
3146516WINFALL
Solar/Wind Harmer
-0.023
3146626S HERTFORD
Solar/Wind Harmer
-0.023
316404AE1-155 C
Solar/Wind Harmer
4.453
3145273HOLLAND
Solar/Wind Harmer
-0.017
3146376EDENTON
Solar/Wind Harmer
-0.023
315614AA2-178 GEN
Solar/Wind Harmer
2.36
3150351NORNECKC2
Adder
1.944
971157AH1-035 GEN
Solar/Wind Harmer
2.665
315737AD1-076 GEN
Solar/Wind Harmer
4.033
3146206CASHIE
Solar/Wind Harmer
-0.021
971781AH1-399 GEN
Solar/Wind Harmer
1.284
3156081AA2-088 GEN
Solar/Wind Harmer
6.75
3145893MURPHYS
Solar/Wind Harmer
0.143
3145893MURPHYS
Solar/Wind Harmer
-0.02
957521AF2-046 GEN
Solar/Wind Harmer
16.039
961681AG1-008 GEN
Solar/Wind Harmer
16.039
3156021HOLLOMANSOL
Solar/Wind Harmer
2.737
3146173TUNIS
Solar/Wind Harmer
-0.02
316463AE2-346 GEN
Solar/Wind Harmer
0.325
316140AB2-099
Solar/Wind Harmer
0.135
962331AG1-082 GEN
Solar/Wind Harmer
2.512
3145963POPLR C
Solar/Wind Harmer
-0.02
3146263WOODLND
Solar/Wind Harmer
-0.02
316317KELFORD C
Solar/Wind Harmer
0.915
3145823KELFORD
Solar/Wind Harmer
-0.019
316365GEN2_N
Solar/Wind Harmer
1.298
3142666NORTHAMPTON
Solar/Wind Harmer
-0.019
3145933PARMELE
Solar/Wind Harmer
-0.019
966801AG1-551 GEN
Solar/Wind Harmer
2.343
966621AG1-532 GEN
Solar/Wind Harmer
0.379
313506AB2-031 GEN
Solar/Wind Harmer
1.499
3145796HORNRTN
Solar/Wind Harmer
-0.074
3145796HORNRTN
Solar/Wind Harmer
-0.018
316210AC1-098 GEN
Solar/Wind Harmer
2.879
3145746EVERETS
Solar/Wind Harmer
-0.018
3145746EVERETS
Solar/Wind Harmer
-0.018
3147043LAWRENC
Solar/Wind Harmer
-0.011
315724AD1-057 GEN
Solar/Wind Harmer
1.011
316327AA2-057 GEN
Solar/Wind Harmer
1.77
3146073TAR RVR
Solar/Wind Harmer
-0.017
3146083TARBORO
Solar/Wind Harmer
-0.017
3146233WITAKRS
Solar/Wind Harmer
0.359
3146233WITAKRS
Solar/Wind Harmer
-0.012
3138543CONSLDL
Solar/Wind Harmer
-0.011
961601AG1-000A GEN
Solar/Wind Harmer
6.7
3145543BTLEBRO
Solar/Wind Harmer
-0.017
3145543BTLEBRO
Solar/Wind Harmer
-0.017
970917AG2-570 GEN
Solar/Wind Harmer
41.291
3144293JTRSVLE
Adder
0.433
3151861LOWMORA
Adder
1.398
316044AC1-158 PL1
Solar/Wind Helper
1.683
316450AC1-158 RIC
Solar/Wind Helper
0.449
227287AC2-120 GEN
Solar/Wind Helper
0.311
226910AB2-157 C
Solar/Wind Helper
0.013
3142296MT RD221
50/50
0.996
3150691DARBY 3
50/50
20.88
3150701DARBY 4
50/50
20.832
3150681DARBY 2
50/50
20.807
3150671DARBY 1
50/50
20.783
3142366NRTHEST
50/50
0.939
316075AC2-137 C
Solar/Wind Harmer
0.857
966871AG1-558 GEN
Solar/Wind Harmer
0.914
966871AG1-558 GEN
Solar/Wind Harmer
0.313
3142946ENON
Solar/Wind Harmer
-0.003
316441AF1-014 GEN
Solar/Wind Harmer
1.841
316033AB2-134 GEN
Solar/Wind Harmer
8.599
315697AD1-025 GEN
Solar/Wind Harmer
5.393
944641AF1-129 GEN
Adder
112.234
316240AF1-291 C
Solar/Wind Harmer
0.786
316236AE1-162_GEN
Solar/Wind Harmer
0.774
316036AC1-147 C
Solar/Wind Harmer
0.67
3150991CHESPKB
Adder
2.316
3150991CHESPKB
Adder
2.26
316316AC1-027 C
Solar/Wind Harmer
0.759
3142956BIRDNECK
Solar/Wind Harmer
1.327
316185AD1-033 GEN
Solar/Wind Harmer
2.6
3145506HICKORY
Solar/Wind Harmer
-0.098
3145506HICKORY
Solar/Wind Harmer
-0.059
3145506HICKORY
Solar/Wind Harmer
-0.015
316339AD2-160 GEN
Solar/Wind Harmer
1.648
316018AA1-139 ULT2
Solar/Wind Harmer
2.091
316017AA1-139 ULT1
Solar/Wind Harmer
1.975
3137176SLIGO L2192
Solar/Wind Harmer
-0.096
3146456SLIGO L269
Solar/Wind Harmer
2.874
3130086AYDLETT
Solar/Wind Harmer
-0.097
970657AG2-426 GEN
Solar/Wind Harmer
7.557
970657AG2-426 GEN
Solar/Wind Harmer
1.58
3146386ELIZ CT
Solar/Wind Harmer
-0.024
316487AF1-042 GEN
Solar/Wind Harmer
3.154
316431W1029_GEN1
Solar/Wind Harmer
4.278
316433W1029_GEN2
Solar/Wind Harmer
4.278
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.023
3146626S HERTFORD
Solar/Wind Harmer
-0.023
3146626S HERTFORD
Solar/Wind Harmer
-0.023
958261AF2-120 GEN
Solar/Wind Harmer
8.946
3146376EDENTON
Solar/Wind Harmer
0.671
3146376EDENTON
Solar/Wind Harmer
0.671
315742AE1-103 GEN
Solar/Wind Harmer
2.356
316077AC2-138 C
Solar/Wind Harmer
0.455
3150341NORNECKC1
Adder
2.009
3150341NORNECKC1
Adder
1.993
3143526WINTERP
Solar/Wind Harmer
-0.111
316065AD1-022 GEN
Solar/Wind Harmer
10.491
316468AD1-105 GEN
Solar/Wind Harmer
2.321
3145893MURPHYS
Solar/Wind Harmer
0.57
3145893MURPHYS
Solar/Wind Harmer
-0.037
3144356SAPONY
Solar/Wind Harmer
0.706
3146173TUNIS
Solar/Wind Harmer
-0.02
3146173TUNIS
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.019
3142666NORTHAMPTON
Solar/Wind Harmer
-0.019
3142666NORTHAMPTON
Solar/Wind Harmer
-0.019
3142666NORTHAMPTON
Solar/Wind Harmer
-0.011
316426AA2-053 GEN
Solar/Wind Harmer
1.906
3145933PARMELE
Solar/Wind Harmer
-0.037
3145933PARMELE
Solar/Wind Harmer
-0.019
316181AB2-040 GEN
Solar/Wind Harmer
2.601
3145593CAROLNA
Solar/Wind Harmer
-0.019
3145593CAROLNA
Solar/Wind Harmer
-0.019
966811AG1-552 GEN
Solar/Wind Harmer
2.096
3145593CAROLNA
Solar/Wind Harmer
0.155
3145783HORNRTN
Solar/Wind Harmer
2.2
3145783HORNRTN
Solar/Wind Harmer
1.76
3145783HORNRTN
Solar/Wind Harmer
0.55
3145783HORNRTN
Solar/Wind Harmer
0.22
3145796HORNRTN
Solar/Wind Harmer
-0.055
316274AC1-208 GEN
Solar/Wind Harmer
1.951
971223AH1-071 GEN
Solar/Wind Harmer
2.213
3145493TOT1
Solar/Wind Harmer
0.268
3145453TOT5
Solar/Wind Harmer
0.161
3145603CNETO
Solar/Wind Harmer
0.107
972185AH1-677 GEN
Adder
8.492
972187AH1-678 GEN
Adder
4.279
961601AG1-000A GEN
Solar/Wind Harmer
6.616
316263AC1-034 GEN
Solar/Wind Harmer
7.882
3152181CUNINGC
50/50
2.408
972193AH1-681 GEN
50/50
7.081
316312AB1-027
Solar/Wind Harmer
1.113
315976AC1-164 GENA
Solar/Wind Harmer
33.627
316169AC1-164_GENC
Solar/Wind Harmer
29.051
315975AC1-164 GENB
Solar/Wind Harmer
0.995
316314AB2-024 C
Solar/Wind Harmer
2.401
3143873LANEXA
Solar/Wind Harmer
-0.017
3142433PROV 92
Adder
0.484
3142433PROV 92
Adder
0.484
971167AH1-042 GEN
Solar/Wind Harmer
26.945
316059AD1-063 C
Solar/Wind Harmer
0.624
957831AF2-077 GEN
Solar/Wind Harmer
0.822
3138283WHITEMARSH
Solar/Wind Harmer
0.042
315662AE1-191 GEN
Solar/Wind Harmer
3.267
315666AE1-190 GEN
Solar/Wind Harmer
0.817
316132AB2-190 GEN1
Solar/Wind Harmer
2.727
957601AF2-054 GEN
Solar/Wind Harmer
0.802
3141873WAN 176
Solar/Wind Harmer
-0.005
316369SG1_INVT
Solar/Wind Harmer
4.764
972265AH1-717 GEN
Adder
18.088
3151201GRAVEL4
Adder
16.956
3151191GRAVEL3
Adder
16.741
3151211GRAVEL5
Adder
16.741
3141913WHIT STONE
Solar/Wind Harmer
-0.026
3138133OCRAN
Solar/Wind Harmer
-0.008
971445AH1-216 GEN
Solar/Wind Harmer
15.914
971285AH1-108 GEN
Adder
1.716
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
3151081ELIZAR1
Adder
20.263
3151091ELIZAR2
Adder
19.911
3152611GOSPORTB
Adder
2.815
3152621GOSPORTC
Adder
2.389
3152601GOSPORTA
Adder
2.204
962981AG1-147 GEN
Solar/Wind Harmer
10.706
957871AF2-081 GEN
Solar/Wind Harmer
12.203
319010AE1-072 C
Solar/Wind Harmer
4.917
3146406KITTY HAWK
Solar/Wind Harmer
0.02
316305AF2-043 C
Solar/Wind Harmer
0.731
315833AF1-017_GEN
Solar/Wind Harmer
4.571
316349AD2-085 GEN
Solar/Wind Harmer
2.14
316311AC2-079 GEN
Solar/Wind Harmer
12.137
315835AF2-110_GEN
Solar/Wind Harmer
2.998
313526AB2-022
Solar/Wind Harmer
0.647
3146486SUNBURY
Solar/Wind Harmer
-0.024
3146486SUNBURY
Solar/Wind Harmer
-0.024
316321Z2-027
Solar/Wind Harmer
0.642
3146396TANGLEW
Solar/Wind Harmer
0.438
3145176PASQUOTANK
Solar/Wind Harmer
-0.015
3143316POE
Solar/Wind Harmer
-0.091
315611Z1-036_GEN2
Solar/Wind Harmer
5.683
3130156CHOWAN
Solar/Wind Harmer
-0.023
3130156CHOWAN
Solar/Wind Harmer
-0.023
315816AE2-034 GEN
Solar/Wind Harmer
1.77
972189AH1-679 GEN
Adder
3.235
3141813NORNECK
Solar/Wind Harmer
-0.021
316233AE1-074 FULL
Solar/Wind Harmer
0.579
971281AH1-106 GEN
Solar/Wind Harmer
3.497
971283AH1-107 GEN
Solar/Wind Harmer
3.497
3130546PLYMOUTH
Solar/Wind Harmer
-0.021
315732AD1-074 GEN1
Solar/Wind Harmer
4.291
315733AD1-074 GEN2
Solar/Wind Harmer
4.291
315735AD1-075 GEN1
Solar/Wind Harmer
2.146
3146206CASHIE
Solar/Wind Harmer
-0.021
970601AG2-382 GEN
Solar/Wind Harmer
9.12
965291AG1-394 GEN
Solar/Wind Harmer
1.832
316318V4-068
Solar/Wind Harmer
0.509
3145893MURPHYS
Solar/Wind Harmer
-0.055
3145893MURPHYS
Solar/Wind Harmer
-0.02
316315AB2-025 C
Solar/Wind Harmer
0.546
315814AE2-033 C
Solar/Wind Harmer
18.813
3145513AHOSKIE
Solar/Wind Harmer
0.175
961941AG1-037 GEN
Solar/Wind Harmer
0.151
3145513AHOSKIE
Solar/Wind Harmer
-0.02
3145683EARLEYS
Solar/Wind Harmer
-0.04
3145683EARLEYS
Solar/Wind Harmer
-0.02
3145683EARLEYS
Solar/Wind Harmer
-0.02
3146043SEABORD
Solar/Wind Harmer
-0.019
315607AA1-063A GEN
Solar/Wind Harmer
1.962
3146033SCOT NK
Solar/Wind Harmer
-0.075
315652AC1-086 GEN
Solar/Wind Harmer
21.172
946281AF1-292 GEN
Solar/Wind Harmer
0.418
316087AB2-174 GEN
Solar/Wind Harmer
2.661
3137643SOCKMAN
Solar/Wind Harmer
-0.074
3145796HORNRTN
Solar/Wind Harmer
-0.059
3145796HORNRTN
Solar/Wind Harmer
-0.007
316005AA1-067
Solar/Wind Harmer
0.368
3145746EVERETS
Solar/Wind Harmer
-0.072
3145746EVERETS
Solar/Wind Harmer
-0.018
3145746EVERETS
Solar/Wind Harmer
-0.018
3145746EVERETS
Solar/Wind Harmer
-0.018
970181AG2-120 GEN
Solar/Wind Harmer
2.39
957861AF2-080 GEN
Solar/Wind Harmer
7.76
316420AA1-050 GEN
Solar/Wind Harmer
2
3145573BETHELC
Solar/Wind Harmer
-0.017
3145573BETHELC
Solar/Wind Harmer
-0.017
941031AE2-094 GEN
Solar/Wind Harmer
32.383
944011AF1-069 GEN
Solar/Wind Harmer
10.147
316319Z2-044 C
Solar/Wind Harmer
0.949
970831AG2-522 GEN
Solar/Wind Harmer
8.556
970673AG2-436 GEN
Solar/Wind Harmer
35.906
970673AG2-436 GEN
Solar/Wind Harmer
18.18
971967AH1-528 GEN
Solar/Wind Harmer
31.905
970085AG2-068 GEN
Solar/Wind Harmer
10.297
970581AG2-369 GEN
Solar/Wind Harmer
8.856
3151881LOWMORC
Adder
1.387
3151881LOWMORC
Adder
1.365
3151861LOWMORA
Adder
1.343
972205AH1-687 GEN
Adder
5.131
316164AC1-076 GEN
Solar/Wind Helper
1.108
3141426STAFORD
Solar/Wind Helper
0.049
3152161CUNINGA
50/50
2.253
972277AH1-723 GEN
50/50
184.681
3142416OLDCHRC
Solar/Wind Harmer
-0.085
3142416OLDCHRC
Solar/Wind Harmer
-0.033
316159AE1-175 C
Solar/Wind Harmer
0.788
944631AF1-128 GEN
Adder
123.875
3143096IRON208
Adder
1.07
971317AH1-138 GEN
Solar/Wind Harmer
3.526
3142433PROV 92
Solar/Wind Harmer
-0.111
3142433PROV 92
Adder
0.484
3142433PROV 92
Adder
0.484
3138126ROCKLANDING
Solar/Wind Harmer
0.085
3141766HARMONY
Solar/Wind Harmer
-0.005
3142543TWELFTH
Solar/Wind Harmer
-0.003
971777AH1-397 GEN
Solar/Wind Harmer
3.212
3141843SHACKLE
Adder
1.242
970129AG2-093 GEN
Solar/Wind Harmer
6.156
316458AB2-190 GEN2
Solar/Wind Harmer
2.727
971069AG2-661 GEN
Solar/Wind Harmer
4.238
971647AH1-324 GEN
Solar/Wind Harmer
13.258
961611AG1-000B GEN
Solar/Wind Harmer
13.011
3151171GRAVELC
Adder
2.478
3138133OCRAN
Solar/Wind Harmer
-0.015
3145336SMITFLD
Solar/Wind Harmer
-0.102
315671AE2-027_GEN
Solar/Wind Harmer
19.245
3150851SPRUNCC
Adder
1.049
316294AC1-161 GEN
Solar/Wind Harmer
8.268
316375AC2-012 GEN
Solar/Wind Harmer
8.597
3150981CHESPKA
Adder
2.761
316072AD1-144
Solar/Wind Harmer
0.503
944591AF1-124 GEN
Solar/Wind Harmer
112.846
316388AE2-253 GEN
Solar/Wind Harmer
1.648
3146456SLIGO L269
Solar/Wind Harmer
-0.024
316246AF1-032 C
Solar/Wind Harmer
0.491
970659AG2-427 GEN
Solar/Wind Harmer
12.861
316381AD1-082 GEN
Solar/Wind Harmer
2.219
970661AG2-428 GEN
Solar/Wind Harmer
25.668
316093AE2-104_GEN
Solar/Wind Harmer
6.973
961951AG1-038 GEN
Solar/Wind Harmer
3.154
3146516WINFALL
Solar/Wind Harmer
-0.076
3146516WINFALL
Solar/Wind Harmer
-0.023
962861AG1-135 GEN
Solar/Wind Harmer
8.742
315800Z1-036_GEN1
Solar/Wind Harmer
5.683
3130156CHOWAN
Solar/Wind Harmer
-0.023
964211AG1-282 GEN
Solar/Wind Harmer
0.676
3141726DUNNSVL
Solar/Wind Harmer
-0.089
3145663CRESWEL
Solar/Wind Harmer
-0.061
971163AH1-040 GEN
Solar/Wind Harmer
20.509
3150351NORNECKC2
Adder
1.912
3143526WINTERP
Solar/Wind Harmer
-0.111
3146206CASHIE
Solar/Wind Harmer
-0.021
971547AH1-271 GEN
Solar/Wind Harmer
5.212
939411AE1-173 GEN
Solar/Wind Harmer
102.389
3145893MURPHYS
Solar/Wind Harmer
-0.081
3145893MURPHYS
Solar/Wind Harmer
0.606
3146173TUNIS
Solar/Wind Harmer
-0.02
3145683EARLEYS
Solar/Wind Harmer
-0.02
3145963POPLR C
Solar/Wind Harmer
-0.02
316174AB2-169 GEN
Solar/Wind Harmer
3.031
3146263WOODLND
Solar/Wind Harmer
-0.02
3145823KELFORD
Solar/Wind Harmer
-0.019
316023GEN1_S
Solar/Wind Harmer
1.298
940641AE2-051 GEN
Solar/Wind Harmer
17.899
316190AA2-174 GEN
Solar/Wind Harmer
0.232
316337AD2-073 GEN
Solar/Wind Harmer
0.506
316011AB1-132 GEN
Solar/Wind Harmer
3.938
962571AG1-106 GEN
Solar/Wind Harmer
2.705
3146293MARTNCO
Solar/Wind Harmer
0.116
960081AF2-299 GEN
Solar/Wind Harmer
2.099
3145783HORNRTN
Solar/Wind Harmer
-0.018
3145796HORNRTN
Solar/Wind Harmer
-0.061
3145796HORNRTN
Solar/Wind Harmer
-0.018
316212AC1-099_GEN
Solar/Wind Harmer
1.599
3145746EVERETS
Solar/Wind Harmer
-0.018
3145746EVERETS
Solar/Wind Harmer
-0.018
971795AH1-408 GEN
Solar/Wind Harmer
13.545
3147043LAWRENC
Adder
1.432
316494AC1-189 GEN
Solar/Wind Harmer
1.908
3143226MDLTHAN
Solar/Wind Harmer
-0.018
315722AD1-056 GEN
Solar/Wind Harmer
1.839
961671AG1-007 GEN
Solar/Wind Harmer
0.219
3146083TARBORO
Solar/Wind Harmer
-0.017
3145493TOT1
Solar/Wind Harmer
0.514
3146233WITAKRS
Solar/Wind Harmer
-0.068
316129AC1-054 GEN
Solar/Wind Harmer
1.486
3145543BTLEBRO
Solar/Wind Harmer
-0.017
3145543BTLEBRO
Solar/Wind Harmer
-0.013
316359AB2-059 GEN
Solar/Wind Harmer
2.267
316049AB1-081 GEN
Solar/Wind Harmer
1.814
3142053HEARTS
Solar/Wind Harmer
0.198
971065AG2-659 GEN
Solar/Wind Harmer
8.4
970919AG2-571 GEN
Solar/Wind Harmer
5.227
970087AG2-069 GEN
Solar/Wind Harmer
15.446
3144293JTRSVLE
Adder
0.433
316045AC1-158 PL2
Solar/Wind Helper
5.387
957481AF2-042 GEN
Solar/Wind Harmer
48.779
970933AG2-581 GEN
Solar/Wind Harmer
15.69
3144293JTRSVLE
Adder
0.433
3144293JTRSVLE
Adder
0.364
316447AC1-158 HLD
Solar/Wind Helper
3.704
226929AD2-058 GEN
Solar/Wind Helper
0.092
970099AG2-077 GEN
Solar/Wind Harmer
19.512
NYPJM->LTFIMP_NY
CLTF
3.038
LGEELTFEXP_LGEE->PJM
CLTF
2.029
WECLTFEXP_WEC->PJM
CLTF
1.027
LAGNLTFEXP_LAGN->PJM
CLTF
8.984
CBM South 2LTFEXP_CBM-S2->PJM
CBM
22.514
TVALTFEXP_TVA->PJM
CLTF
4.571
CBM West 1LTFEXP_CBM-W1->PJM
CBM
36.342
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.071
MECLTFEXP_MEC->PJM
CLTF
5.138
SIGELTFEXP_SIGE->PJM
CLTF
0.161
CPLELTFEXP_CPLE->PJM
CLTF
9.655
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.755

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T581_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T581_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:158.77 %
Rating:2913.0 MVA
Rating Type:C
MVA to Mitigate:4624.92
MW Contribution:183.92
Bus #Bus NameTypeMW Contribution
971645AH1-323 GEN
50/50
27.564
3152191CUNINGD
50/50
5.221
3152171CUNINGB
50/50
2.254
972255AH1-712 GEN
50/50
157.831
3142416OLDCHRC
Solar/Wind Harmer
3.373
970293AG2-193 GEN
Solar/Wind Harmer
3.949
316473AC1-191 GEN
Solar/Wind Harmer
3.342
3142946ENON
Solar/Wind Harmer
-0.01
316382AG1-145 C
Solar/Wind Harmer
0.891
3143096IRON208
Adder
1.082
3143096IRON208
Adder
1.06
3142433PROV 92
Adder
0.491
3142433PROV 92
Adder
0.491
3141766HARMONY
Solar/Wind Harmer
2.493
3150921YORKTN3
Adder
6.26
3144216WINCHST
Adder
0.933
3141843SHACKLE
Adder
1.261
316203AE2-005 GEN
Solar/Wind Harmer
11.686
970133AG2-095 GEN
Solar/Wind Harmer
3.096
316280AD1-041 GEN
Solar/Wind Harmer
2.073
316156AD2-030 GEN
Solar/Wind Harmer
0.727
3141873WAN 176
Solar/Wind Harmer
3.231
970129AG2-093 GEN
Solar/Wind Harmer
15.321
315778AD1-151 GEN
Solar/Wind Harmer
23.381
961611AG1-000B GEN
Solar/Wind Harmer
5.586
3151221GRAVEL6
Adder
17.033
3151171GRAVELC
Adder
3.277
3152181CUNINGC
50/50
2.398
972193AH1-681 GEN
50/50
7.052
316312AB1-027
Solar/Wind Harmer
1.127
315976AC1-164 GENA
Solar/Wind Harmer
33.928
316169AC1-164_GENC
Solar/Wind Harmer
29.311
315975AC1-164 GENB
Solar/Wind Harmer
1.004
316314AB2-024 C
Solar/Wind Harmer
2.435
3143873LANEXA
Solar/Wind Harmer
-0.017
3142433PROV 92
Adder
0.491
3142433PROV 92
Adder
0.491
971167AH1-042 GEN
Solar/Wind Harmer
27.3
316059AD1-063 C
Solar/Wind Harmer
0.633
957831AF2-077 GEN
Solar/Wind Harmer
0.831
3138283WHITEMARSH
Solar/Wind Harmer
0.043
315662AE1-191 GEN
Solar/Wind Harmer
3.317
315666AE1-190 GEN
Solar/Wind Harmer
0.829
957601AF2-054 GEN
Solar/Wind Harmer
0.815
3141873WAN 176
Solar/Wind Harmer
-0.005
316132AB2-190 GEN1
Solar/Wind Harmer
2.749
316369SG1_INVT
Solar/Wind Harmer
4.799
3141913WHIT STONE
Solar/Wind Harmer
-0.026
972265AH1-717 GEN
Adder
18.191
3151201GRAVEL4
Adder
17.053
3151191GRAVEL3
Adder
16.837
3151211GRAVEL5
Adder
16.837
3138133OCRAN
Solar/Wind Harmer
-0.008
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
971285AH1-108 GEN
Adder
1.735
971445AH1-216 GEN
Solar/Wind Harmer
15.991
962981AG1-147 GEN
Solar/Wind Harmer
10.959
3152611GOSPORTB
Adder
2.824
3152621GOSPORTC
Adder
2.397
3152601GOSPORTA
Adder
2.211
3151081ELIZAR1
Adder
20.323
3151091ELIZAR2
Adder
19.97
957871AF2-081 GEN
Solar/Wind Harmer
12.238
319010AE1-072 C
Solar/Wind Harmer
4.931
3146406KITTY HAWK
Solar/Wind Harmer
0.02
316305AF2-043 C
Solar/Wind Harmer
0.733
315833AF1-017_GEN
Solar/Wind Harmer
4.591
316349AD2-085 GEN
Solar/Wind Harmer
2.15
316311AC2-079 GEN
Solar/Wind Harmer
12.19
315835AF2-110_GEN
Solar/Wind Harmer
3.008
313526AB2-022
Solar/Wind Harmer
0.649
3146486SUNBURY
Solar/Wind Harmer
-0.024
3146486SUNBURY
Solar/Wind Harmer
-0.024
316321Z2-027
Solar/Wind Harmer
0.644
3146396TANGLEW
Solar/Wind Harmer
0.439
3145176PASQUOTANK
Solar/Wind Harmer
-0.015
972189AH1-679 GEN
Adder
3.52
3143316POE
Solar/Wind Harmer
-0.092
315611Z1-036_GEN2
Solar/Wind Harmer
5.699
3130156CHOWAN
Solar/Wind Harmer
-0.023
3130156CHOWAN
Solar/Wind Harmer
-0.023
3141813NORNECK
Solar/Wind Harmer
-0.022
315816AE2-034 GEN
Solar/Wind Harmer
1.775
316233AE1-074 FULL
Solar/Wind Harmer
0.585
971281AH1-106 GEN
Solar/Wind Harmer
3.531
971283AH1-107 GEN
Solar/Wind Harmer
3.531
3130546PLYMOUTH
Solar/Wind Harmer
-0.021
315732AD1-074 GEN1
Solar/Wind Harmer
4.302
315733AD1-074 GEN2
Solar/Wind Harmer
4.302
315735AD1-075 GEN1
Solar/Wind Harmer
2.152
3146206CASHIE
Solar/Wind Harmer
-0.021
970601AG2-382 GEN
Solar/Wind Harmer
9.144
965291AG1-394 GEN
Solar/Wind Harmer
1.837
316318V4-068
Solar/Wind Harmer
0.51
3145893MURPHYS
Solar/Wind Harmer
-0.055
3145893MURPHYS
Solar/Wind Harmer
-0.02
316315AB2-025 C
Solar/Wind Harmer
0.549
315814AE2-033 C
Solar/Wind Harmer
18.891
3145513AHOSKIE
Solar/Wind Harmer
0.176
961941AG1-037 GEN
Solar/Wind Harmer
0.151
3145513AHOSKIE
Solar/Wind Harmer
-0.02
3145683EARLEYS
Solar/Wind Harmer
-0.04
3145683EARLEYS
Solar/Wind Harmer
-0.02
3145683EARLEYS
Solar/Wind Harmer
-0.02
3146043SEABORD
Solar/Wind Harmer
-0.02
315607AA1-063A GEN
Solar/Wind Harmer
1.967
315652AC1-086 GEN
Solar/Wind Harmer
21.229
3146033SCOT NK
Solar/Wind Harmer
-0.075
946281AF1-292 GEN
Solar/Wind Harmer
0.419
316087AB2-174 GEN
Solar/Wind Harmer
2.668
3137643SOCKMAN
Solar/Wind Harmer
-0.074
3145796HORNRTN
Solar/Wind Harmer
-0.059
3145796HORNRTN
Solar/Wind Harmer
-0.007
316005AA1-067
Solar/Wind Harmer
0.369
3145746EVERETS
Solar/Wind Harmer
-0.072
3145746EVERETS
Solar/Wind Harmer
-0.018
3145746EVERETS
Solar/Wind Harmer
-0.018
3145746EVERETS
Solar/Wind Harmer
-0.018
970181AG2-120 GEN
Solar/Wind Harmer
2.395
957861AF2-080 GEN
Solar/Wind Harmer
7.775
316420AA1-050 GEN
Solar/Wind Harmer
2.004
3145573BETHELC
Solar/Wind Harmer
-0.017
3145573BETHELC
Solar/Wind Harmer
-0.017
941031AE2-094 GEN
Solar/Wind Harmer
32.394
944011AF1-069 GEN
Solar/Wind Harmer
10.15
316319Z2-044 C
Solar/Wind Harmer
0.95
970831AG2-522 GEN
Solar/Wind Harmer
8.569
970673AG2-436 GEN
Solar/Wind Harmer
35.918
970673AG2-436 GEN
Solar/Wind Harmer
18.187
971967AH1-528 GEN
Solar/Wind Harmer
31.915
316223AC1-118
Solar/Wind Harmer
0.456
970085AG2-068 GEN
Solar/Wind Harmer
10.3
970581AG2-369 GEN
Solar/Wind Harmer
8.858
3151881LOWMORC
Adder
1.379
3151881LOWMORC
Adder
1.357
3151861LOWMORA
Adder
1.336
972205AH1-687 GEN
Adder
5.122
316164AC1-076 GEN
Solar/Wind Helper
1.127
3152161CUNINGA
50/50
2.244
972277AH1-723 GEN
50/50
183.92
3142416OLDCHRC
Solar/Wind Harmer
-0.086
3142416OLDCHRC
Solar/Wind Harmer
-0.033
316159AE1-175 C
Solar/Wind Harmer
0.793
944631AF1-128 GEN
Adder
125.098
3143096IRON208
Adder
1.082
971317AH1-138 GEN
Solar/Wind Harmer
3.551
3142433PROV 92
Solar/Wind Harmer
-0.113
3142433PROV 92
Adder
0.491
3142433PROV 92
Adder
0.491
3141766HARMONY
Solar/Wind Harmer
-0.006
3138126ROCKLANDING
Solar/Wind Harmer
0.085
3142543TWELFTH
Solar/Wind Harmer
-0.003
971777AH1-397 GEN
Solar/Wind Harmer
3.26
3141843SHACKLE
Adder
1.261
970129AG2-093 GEN
Solar/Wind Harmer
6.206
316458AB2-190 GEN2
Solar/Wind Harmer
2.749
971069AG2-661 GEN
Solar/Wind Harmer
4.271
971647AH1-324 GEN
Solar/Wind Harmer
13.347
961611AG1-000B GEN
Solar/Wind Harmer
13.093
3151171GRAVELC
Adder
2.492
3138133OCRAN
Solar/Wind Harmer
-0.016
315671AE2-027_GEN
Solar/Wind Harmer
19.429
3150851SPRUNCC
Adder
1.06
3145336SMITFLD
Solar/Wind Harmer
-0.103
316294AC1-161 GEN
Solar/Wind Harmer
8.284
316072AD1-144
Solar/Wind Harmer
0.505
316375AC2-012 GEN
Solar/Wind Harmer
8.624
3150981CHESPKA
Adder
2.769
944591AF1-124 GEN
Solar/Wind Harmer
113.139
961951AG1-038 GEN
Solar/Wind Harmer
3.235
316388AE2-253 GEN
Solar/Wind Harmer
1.653
3146456SLIGO L269
Solar/Wind Harmer
-0.024
970659AG2-427 GEN
Solar/Wind Harmer
12.939
316381AD1-082 GEN
Solar/Wind Harmer
2.232
316246AF1-032 C
Solar/Wind Harmer
0.492
970661AG2-428 GEN
Solar/Wind Harmer
25.809
316093AE2-104_GEN
Solar/Wind Harmer
6.997
962861AG1-135 GEN
Solar/Wind Harmer
8.988
3146516WINFALL
Solar/Wind Harmer
-0.076
3146516WINFALL
Solar/Wind Harmer
-0.024
964211AG1-282 GEN
Solar/Wind Harmer
0.698
3141726DUNNSVL
Solar/Wind Harmer
-0.092
315800Z1-036_GEN1
Solar/Wind Harmer
5.699
3130156CHOWAN
Solar/Wind Harmer
-0.023
3150351NORNECKC2
Adder
1.981
3145663CRESWEL
Solar/Wind Harmer
-0.061
971163AH1-040 GEN
Solar/Wind Harmer
20.564
3143526WINTERP
Solar/Wind Harmer
-0.112
3146206CASHIE
Solar/Wind Harmer
-0.021
971547AH1-271 GEN
Solar/Wind Harmer
5.225
939411AE1-173 GEN
Solar/Wind Harmer
102.53
3145893MURPHYS
Solar/Wind Harmer
-0.082
3145893MURPHYS
Solar/Wind Harmer
0.608
3146173TUNIS
Solar/Wind Harmer
-0.02
3145683EARLEYS
Solar/Wind Harmer
-0.02
3145963POPLR C
Solar/Wind Harmer
-0.02
316337AD2-073 GEN
Solar/Wind Harmer
0.531
316174AB2-169 GEN
Solar/Wind Harmer
3.039
3146263WOODLND
Solar/Wind Harmer
-0.02
3145823KELFORD
Solar/Wind Harmer
-0.019
316023GEN1_S
Solar/Wind Harmer
1.302
940641AE2-051 GEN
Solar/Wind Harmer
17.913
316190AA2-174 GEN
Solar/Wind Harmer
0.232
316011AB1-132 GEN
Solar/Wind Harmer
3.948
962571AG1-106 GEN
Solar/Wind Harmer
2.713
3146293MARTNCO
Solar/Wind Harmer
0.116
960081AF2-299 GEN
Solar/Wind Harmer
2.105
3145783HORNRTN
Solar/Wind Harmer
-0.019
3145796HORNRTN
Solar/Wind Harmer
-0.061
3145796HORNRTN
Solar/Wind Harmer
-0.019
316212AC1-099_GEN
Solar/Wind Harmer
1.603
3145746EVERETS
Solar/Wind Harmer
-0.018
3145746EVERETS
Solar/Wind Harmer
-0.018
971795AH1-408 GEN
Solar/Wind Harmer
13.577
3143226MDLTHAN
Solar/Wind Harmer
-0.018
3147043LAWRENC
Adder
1.435
316494AC1-189 GEN
Solar/Wind Harmer
1.912
315722AD1-056 GEN
Solar/Wind Harmer
1.843
961671AG1-007 GEN
Solar/Wind Harmer
0.219
3146083TARBORO
Solar/Wind Harmer
-0.017
3145493TOT1
Solar/Wind Harmer
0.515
3146233WITAKRS
Solar/Wind Harmer
-0.068
316129AC1-054 GEN
Solar/Wind Harmer
1.488
3145543BTLEBRO
Solar/Wind Harmer
-0.017
3145543BTLEBRO
Solar/Wind Harmer
-0.013
316359AB2-059 GEN
Solar/Wind Harmer
2.271
316049AB1-081 GEN
Solar/Wind Harmer
1.817
3142053HEARTS
Solar/Wind Harmer
0.198
971065AG2-659 GEN
Solar/Wind Harmer
8.411
970919AG2-571 GEN
Solar/Wind Harmer
5.228
970087AG2-069 GEN
Solar/Wind Harmer
15.45
3144293JTRSVLE
Adder
0.433
316045AC1-158 PL2
Solar/Wind Helper
5.498
3147666LOUISA
Solar/Wind Helper
0.891
957481AF2-042 GEN
Solar/Wind Harmer
48.481
3150861SPRUNCD
Adder
1.06
3145336SMITFLD
Solar/Wind Harmer
-0.01
315773AC2-141 GEN
Solar/Wind Harmer
10.714
965281AG1-393 GEN
Solar/Wind Harmer
3.198
3144536CHRHLND
Solar/Wind Harmer
-0.004
315839AE2-212 C
Solar/Wind Harmer
0.757
962971AG1-146 GEN
Solar/Wind Harmer
4.697
3151101ELIZAR3
Adder
20.583
3144873MCLAUGH
Solar/Wind Harmer
-0.001
944581AF1-123 GEN
Solar/Wind Harmer
112.733
944601AF1-125 GEN
Solar/Wind Harmer
110.974
316484AD2-074 GEN
Solar/Wind Harmer
6.182
970009AG2-005 GEN
Solar/Wind Harmer
3.07
315813AE1-149 C
Solar/Wind Harmer
15.278
3146456SLIGO L269
Solar/Wind Harmer
-0.024
971153AH1-033 GEN
Solar/Wind Harmer
2.975
970659AG2-427 GEN
Solar/Wind Harmer
2.293
316083AB2-161 GEN
Solar/Wind Harmer
3.95
970661AG2-428 GEN
Solar/Wind Harmer
4.574
316320Y1-086
Solar/Wind Harmer
1.409
316404AE1-155 C
Solar/Wind Harmer
4.583
316435W1029_GEN3
Solar/Wind Harmer
4.29
3146516WINFALL
Solar/Wind Harmer
-0.024
3146626S HERTFORD
Solar/Wind Harmer
-0.023
3145273HOLLAND
Solar/Wind Harmer
-0.017
3146376EDENTON
Solar/Wind Harmer
-0.023
3150351NORNECKC2
Adder
2.014
971781AH1-399 GEN
Solar/Wind Harmer
1.353
315614AA2-178 GEN
Solar/Wind Harmer
2.367
971157AH1-035 GEN
Solar/Wind Harmer
2.672
315737AD1-076 GEN
Solar/Wind Harmer
4.043
3146206CASHIE
Solar/Wind Harmer
-0.021
3156081AA2-088 GEN
Solar/Wind Harmer
6.769
3145893MURPHYS
Solar/Wind Harmer
0.143
3145893MURPHYS
Solar/Wind Harmer
-0.02
957521AF2-046 GEN
Solar/Wind Harmer
16.082
961681AG1-008 GEN
Solar/Wind Harmer
16.082
3156021HOLLOMANSOL
Solar/Wind Harmer
2.744
3146173TUNIS
Solar/Wind Harmer
-0.02
316463AE2-346 GEN
Solar/Wind Harmer
0.326
316140AB2-099
Solar/Wind Harmer
0.136
962331AG1-082 GEN
Solar/Wind Harmer
2.518
3145963POPLR C
Solar/Wind Harmer
-0.02
3146263WOODLND
Solar/Wind Harmer
-0.02
316317KELFORD C
Solar/Wind Harmer
0.917
3145823KELFORD
Solar/Wind Harmer
-0.019
316365GEN2_N
Solar/Wind Harmer
1.302
3142666NORTHAMPTON
Solar/Wind Harmer
-0.019
3145933PARMELE
Solar/Wind Harmer
-0.019
966801AG1-551 GEN
Solar/Wind Harmer
2.348
966621AG1-532 GEN
Solar/Wind Harmer
0.38
313506AB2-031 GEN
Solar/Wind Harmer
1.503
3145796HORNRTN
Solar/Wind Harmer
-0.074
3145796HORNRTN
Solar/Wind Harmer
-0.019
316210AC1-098 GEN
Solar/Wind Harmer
2.885
3145746EVERETS
Solar/Wind Harmer
-0.018
3145746EVERETS
Solar/Wind Harmer
-0.018
3147043LAWRENC
Solar/Wind Harmer
-0.011
315724AD1-057 GEN
Solar/Wind Harmer
1.014
316327AA2-057 GEN
Solar/Wind Harmer
1.774
3146073TAR RVR
Solar/Wind Harmer
-0.017
3146083TARBORO
Solar/Wind Harmer
-0.017
3146233WITAKRS
Solar/Wind Harmer
0.36
3146233WITAKRS
Solar/Wind Harmer
-0.012
3138543CONSLDL
Solar/Wind Harmer
-0.011
3141906WESTMOR
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
6.711
3145543BTLEBRO
Solar/Wind Harmer
-0.017
3145543BTLEBRO
Solar/Wind Harmer
-0.017
970917AG2-570 GEN
Solar/Wind Harmer
41.302
3144293JTRSVLE
Adder
0.433
3151861LOWMORA
Adder
1.39
316044AC1-158 PL1
Solar/Wind Helper
1.717
316450AC1-158 RIC
Solar/Wind Helper
0.458
227287AC2-120 GEN
Solar/Wind Helper
0.31
226910AB2-157 C
Solar/Wind Helper
0.013
3147666LOUISA
Solar/Wind Helper
0.512
3142296MT RD221
50/50
1.012
3150691DARBY 3
50/50
21.141
3150701DARBY 4
50/50
21.092
3150681DARBY 2
50/50
21.068
3150671DARBY 1
50/50
21.043
3142366NRTHEST
50/50
0.951
316075AC2-137 C
Solar/Wind Harmer
0.866
966871AG1-558 GEN
Solar/Wind Harmer
0.934
966871AG1-558 GEN
Solar/Wind Harmer
0.319
3142946ENON
Solar/Wind Harmer
-0.003
316441AF1-014 GEN
Solar/Wind Harmer
1.868
316033AB2-134 GEN
Solar/Wind Harmer
8.662
315697AD1-025 GEN
Solar/Wind Harmer
5.432
944641AF1-129 GEN
Adder
113.367
316240AF1-291 C
Solar/Wind Harmer
0.794
316236AE1-162_GEN
Solar/Wind Harmer
0.777
316036AC1-147 C
Solar/Wind Harmer
0.672
3150991CHESPKB
Adder
2.323
3150991CHESPKB
Adder
2.267
316316AC1-027 C
Solar/Wind Harmer
0.761
3142956BIRDNECK
Solar/Wind Harmer
1.331
316185AD1-033 GEN
Solar/Wind Harmer
2.608
3145506HICKORY
Solar/Wind Harmer
-0.098
3145506HICKORY
Solar/Wind Harmer
-0.059
3145506HICKORY
Solar/Wind Harmer
-0.015
316487AF1-042 GEN
Solar/Wind Harmer
3.235
316339AD2-160 GEN
Solar/Wind Harmer
1.653
316018AA1-139 ULT2
Solar/Wind Harmer
2.097
316017AA1-139 ULT1
Solar/Wind Harmer
1.98
3137176SLIGO L2192
Solar/Wind Harmer
-0.097
3146456SLIGO L269
Solar/Wind Harmer
2.882
3130086AYDLETT
Solar/Wind Harmer
-0.097
970657AG2-426 GEN
Solar/Wind Harmer
7.6
970657AG2-426 GEN
Solar/Wind Harmer
1.589
3146386ELIZ CT
Solar/Wind Harmer
-0.024
958261AF2-120 GEN
Solar/Wind Harmer
9.206
316431W1029_GEN1
Solar/Wind Harmer
4.29
316433W1029_GEN2
Solar/Wind Harmer
4.29
3146516WINFALL
Solar/Wind Harmer
-0.024
3146516WINFALL
Solar/Wind Harmer
-0.024
3146516WINFALL
Solar/Wind Harmer
-0.024
3146626S HERTFORD
Solar/Wind Harmer
-0.023
3146626S HERTFORD
Solar/Wind Harmer
-0.023
3146376EDENTON
Solar/Wind Harmer
0.672
3146376EDENTON
Solar/Wind Harmer
0.672
315742AE1-103 GEN
Solar/Wind Harmer
2.363
316077AC2-138 C
Solar/Wind Harmer
0.471
3150341NORNECKC1
Adder
2.081
3150341NORNECKC1
Adder
2.064
316468AD1-105 GEN
Solar/Wind Harmer
2.446
3143526WINTERP
Solar/Wind Harmer
-0.112
316065AD1-022 GEN
Solar/Wind Harmer
10.518
3145893MURPHYS
Solar/Wind Harmer
0.571
3145893MURPHYS
Solar/Wind Harmer
-0.037
3144356SAPONY
Solar/Wind Harmer
0.709
3146173TUNIS
Solar/Wind Harmer
-0.02
3146173TUNIS
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.019
3142666NORTHAMPTON
Solar/Wind Harmer
-0.019
3142666NORTHAMPTON
Solar/Wind Harmer
-0.019
3142666NORTHAMPTON
Solar/Wind Harmer
-0.011
316426AA2-053 GEN
Solar/Wind Harmer
1.911
3145933PARMELE
Solar/Wind Harmer
-0.037
3145933PARMELE
Solar/Wind Harmer
-0.019
316181AB2-040 GEN
Solar/Wind Harmer
2.608
3145593CAROLNA
Solar/Wind Harmer
-0.019
3145593CAROLNA
Solar/Wind Harmer
-0.019
966811AG1-552 GEN
Solar/Wind Harmer
2.101
3145593CAROLNA
Solar/Wind Harmer
0.155
3145783HORNRTN
Solar/Wind Harmer
2.205
3145783HORNRTN
Solar/Wind Harmer
1.764
3145783HORNRTN
Solar/Wind Harmer
0.551
3145783HORNRTN
Solar/Wind Harmer
0.221
3145796HORNRTN
Solar/Wind Harmer
-0.055
316274AC1-208 GEN
Solar/Wind Harmer
1.955
971223AH1-071 GEN
Solar/Wind Harmer
2.229
3145493TOT1
Solar/Wind Harmer
0.269
3145453TOT5
Solar/Wind Harmer
0.161
3145603CNETO
Solar/Wind Harmer
0.107
972185AH1-677 GEN
Adder
8.495
972187AH1-678 GEN
Adder
4.28
961601AG1-000A GEN
Solar/Wind Harmer
6.627
316263AC1-034 GEN
Solar/Wind Harmer
7.895
970933AG2-581 GEN
Solar/Wind Harmer
15.694
3144293JTRSVLE
Adder
0.433
3144293JTRSVLE
Adder
0.364
316447AC1-158 HLD
Solar/Wind Helper
3.78
226929AD2-058 GEN
Solar/Wind Helper
0.092
970099AG2-077 GEN
Solar/Wind Harmer
19.392
NYPJM->LTFIMP_NY
CLTF
3.039
LGEELTFEXP_LGEE->PJM
CLTF
2.018
WECLTFEXP_WEC->PJM
CLTF
1.02
LAGNLTFEXP_LAGN->PJM
CLTF
8.954
CBM South 2LTFEXP_CBM-S2->PJM
CBM
22.492
TVALTFEXP_TVA->PJM
CLTF
4.556
CBM West 1LTFEXP_CBM-W1->PJM
CBM
36.102
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.013
MECLTFEXP_MEC->PJM
CLTF
5.11
SIGELTFEXP_SIGE->PJM
CLTF
0.16
CPLELTFEXP_CPLE->PJM
CLTF
9.654
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.545

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:153.9 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:6264.0
MW Contribution:183.58
Bus #Bus NameTypeMW Contribution
3152331SURRY 2
50/50
13.991
971353AH1-157 GEN
50/50
28.65
970017AG2-010 GEN
50/50
21.737
3150981CHESPKA
50/50
4.162
3142416OLDCHRC
Solar/Wind Harmer
0.86
3142416OLDCHRC
Solar/Wind Harmer
0.33
316159AE1-175 C
Solar/Wind Harmer
0.283
316294AC1-161 GEN
Solar/Wind Harmer
5.617
971317AH1-138 GEN
Solar/Wind Harmer
2.41
3138126ROCKLANDING
Solar/Wind Harmer
0.148
944591AF1-124 GEN
Solar/Wind Harmer
71.262
316375AC2-012 GEN
Solar/Wind Harmer
0.008
3145336SMITFLD
Solar/Wind Harmer
1.25
3151171GRAVELC
Adder
3.316
316388AE2-253 GEN
Solar/Wind Harmer
0.975
316072AD1-144
Solar/Wind Harmer
0.112
3146456SLIGO L269
Solar/Wind Harmer
0.31
961611AG1-000B GEN
Solar/Wind Harmer
16.269
971647AH1-324 GEN
Solar/Wind Harmer
13.184
316246AF1-032 C
Solar/Wind Harmer
0.139
944631AF1-128 GEN
Adder
146.833
972277AH1-723 GEN
Adder
183.583
971069AG2-661 GEN
Solar/Wind Harmer
5.456
316458AB2-190 GEN2
Solar/Wind Harmer
1.639
970129AG2-093 GEN
Solar/Wind Harmer
8.684
316093AE2-104_GEN
Solar/Wind Harmer
5.127
3146516WINFALL
Solar/Wind Harmer
0.976
3146516WINFALL
Solar/Wind Harmer
0.301
3142433PROV 92
Solar/Wind Harmer
1.2
3142433PROV 92
Adder
0.583
3142433PROV 92
Adder
0.583
970661AG2-428 GEN
Solar/Wind Harmer
29.836
3141766HARMONY
Solar/Wind Harmer
0.06
939411AE1-173 GEN
Solar/Wind Harmer
127.601
316381AD1-082 GEN
Solar/Wind Harmer
0.311
970659AG2-427 GEN
Solar/Wind Harmer
14.437
971777AH1-397 GEN
Solar/Wind Harmer
0.785
3141843SHACKLE
Adder
1.519
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
315671AE2-027_GEN
Solar/Wind Harmer
18.84
940641AE2-051 GEN
Solar/Wind Harmer
23.538
3143096IRON208
Adder
1.226
3130156CHOWAN
Solar/Wind Harmer
0.292
3145663CRESWEL
Solar/Wind Harmer
0.795
971163AH1-040 GEN
Solar/Wind Harmer
22.732
3138133OCRAN
Solar/Wind Harmer
0.17
3142543TWELFTH
Solar/Wind Harmer
0.027
3146206CASHIE
Solar/Wind Harmer
0.273
971547AH1-271 GEN
Solar/Wind Harmer
5.835
3145893MURPHYS
Solar/Wind Harmer
1.078
3145893MURPHYS
Solar/Wind Harmer
1.199
3146173TUNIS
Solar/Wind Harmer
0.267
3145683EARLEYS
Solar/Wind Harmer
0.265
316023GEN1_S
Solar/Wind Harmer
0.59
3145963POPLR C
Solar/Wind Harmer
0.263
3146263WOODLND
Solar/Wind Harmer
0.261
316174AB2-169 GEN
Solar/Wind Harmer
0.007
970919AG2-571 GEN
Solar/Wind Harmer
9.256
970087AG2-069 GEN
Solar/Wind Harmer
20.752
3145823KELFORD
Solar/Wind Harmer
0.259
962861AG1-135 GEN
Solar/Wind Harmer
8.175
316011AB1-132 GEN
Solar/Wind Harmer
4.638
962571AG1-106 GEN
Solar/Wind Harmer
3.63
960081AF2-299 GEN
Solar/Wind Harmer
2.448
316190AA2-174 GEN
Solar/Wind Harmer
0
3150851SPRUNCC
Adder
1.161
3145796HORNRTN
Solar/Wind Harmer
0.83
3145796HORNRTN
Solar/Wind Harmer
0.251
3145783HORNRTN
Solar/Wind Harmer
0.251
3146293MARTNCO
Solar/Wind Harmer
0.232
316212AC1-099_GEN
Solar/Wind Harmer
1.281
971795AH1-408 GEN
Solar/Wind Harmer
16.501
3141726DUNNSVL
Solar/Wind Harmer
0.979
3145746EVERETS
Solar/Wind Harmer
0.244
3145746EVERETS
Solar/Wind Harmer
0.244
957481AF2-042 GEN
Solar/Wind Harmer
65.115
3147043LAWRENC
Adder
2.208
315722AD1-056 GEN
Solar/Wind Harmer
1.518
316494AC1-189 GEN
Solar/Wind Harmer
0.81
3150351NORNECKC2
Adder
2.352
315693AD1-088 GEN
Solar/Wind Harmer
11.318
961671AG1-007 GEN
Solar/Wind Harmer
0.036
3146083TARBORO
Solar/Wind Harmer
0.235
3145493TOT1
Solar/Wind Harmer
1.047
316129AC1-054 GEN
Solar/Wind Harmer
0.885
3146233WITAKRS
Solar/Wind Harmer
0.932
962491AG1-098 GEN
Solar/Wind Harmer
13.368
971065AG2-659 GEN
Solar/Wind Harmer
9.97
3145543BTLEBRO
Solar/Wind Harmer
0.23
3145543BTLEBRO
Solar/Wind Harmer
0.184
316359AB2-059 GEN
Solar/Wind Harmer
0.827
316049AB1-081 GEN
Solar/Wind Harmer
1.317
3142053HEARTS
Solar/Wind Harmer
0.405
315687AD1-152 GEN
Solar/Wind Harmer
0.007
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970401AG2-262 GEN
Solar/Wind Harmer
1.243
316337AD2-073 GEN
Solar/Wind Harmer
0.18
970685AG2-442 GEN
Solar/Wind Harmer
15.398
963171AG1-166 GEN
Solar/Wind Harmer
1.08
971563AH1-280 GEN
Solar/Wind Harmer
2.16
3144293JTRSVLE
Adder
0.645
316003AC1-222 GEN
Solar/Wind Harmer
0.005
3143526WINTERP
Solar/Wind Harmer
0.968
3146926FARMVIL
Solar/Wind Harmer
0.111
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.065
970223AG2-152 GEN
Solar/Wind Harmer
10.425
270016AE1-250 BESS
Solar/Wind Harmer
0.004
3147123OTTER R
Solar/Wind Harmer
0.085
972003AH1-546 GEN
Solar/Wind Harmer
5.963
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
3147312GRETNA
Solar/Wind Harmer
0.109
3146802CHATHAM
Solar/Wind Harmer
0.102
941801AE2-185 GEN
Solar/Wind Harmer
4.349
970937AG2-583 GEN
Solar/Wind Harmer
8.286
316336AC2-165 C
Solar/Wind Harmer
0.005
3143336POWHATN
Solar/Wind Harmer
2.393
3143226MDLTHAN
Solar/Wind Harmer
0.134
971377AH1-170 GEN
Solar/Wind Harmer
1.425
3147623JAMES R
Solar/Wind Harmer
0.31
972135AH1-637 GEN
Solar/Wind Harmer
1.098
270173AC1-122 GEN
Solar/Wind Harmer
0.31
270030AE2-140 GEN
Solar/Wind Harmer
13.116
315705AF1-075 GEN
Solar/Wind Harmer
4.718
962751AG1-124 GEN
Solar/Wind Harmer
5.402
316045AC1-158 PL2
Solar/Wind Helper
6.543
316006AB2-029 C
Solar/Wind Helper
0.142
316254AC1-120 GEN1
Solar/Wind Helper
1.333
3147666LOUISA
Solar/Wind Helper
1.029
316192AB2-158 GEN
Solar/Wind Helper
1.689
223401AF1-299 GEN
Solar/Wind Helper
0.346
23779801AA1-109
Solar/Wind Helper
0.161
972263AH1-716 GEN
50/50
194.204
3151081ELIZAR1
50/50
30.584
3151091ELIZAR2
50/50
30.053
941591AE2-156 GEN
50/50
27.947
3152611GOSPORTB
50/50
4.245
3152621GOSPORTC
50/50
3.603
3152601GOSPORTA
50/50
3.323
315976AC1-164 GENA
Solar/Wind Harmer
34.449
316169AC1-164_GENC
Solar/Wind Harmer
29.761
315975AC1-164 GENB
Solar/Wind Harmer
1.019
316312AB1-027
Solar/Wind Harmer
0.592
971445AH1-216 GEN
Solar/Wind Harmer
22.015
972265AH1-717 GEN
Adder
24.205
3151201GRAVEL4
Adder
22.69
3151191GRAVEL3
Adder
22.403
3151211GRAVEL5
Adder
22.403
957871AF2-081 GEN
Solar/Wind Harmer
15.477
319010AE1-072 C
Solar/Wind Harmer
1.561
3146406KITTY HAWK
Solar/Wind Harmer
0.039
3138283WHITEMARSH
Solar/Wind Harmer
0.072
316305AF2-043 C
Solar/Wind Harmer
0.002
316369SG1_INVT
Solar/Wind Harmer
0.011
972193AH1-681 GEN
Adder
7.039
313526AB2-022
Solar/Wind Harmer
0.166
316132AB2-190 GEN1
Solar/Wind Harmer
1.639
3146486SUNBURY
Solar/Wind Harmer
0.305
3146486SUNBURY
Solar/Wind Harmer
0.305
315835AF2-110_GEN
Solar/Wind Harmer
2.092
316321Z2-027
Solar/Wind Harmer
0.057
3146396TANGLEW
Solar/Wind Harmer
0.839
3145176PASQUOTANK
Solar/Wind Harmer
0.189
316314AB2-024 C
Solar/Wind Harmer
0.001
316311AC2-079 GEN
Solar/Wind Harmer
8.688
315833AF1-017_GEN
Solar/Wind Harmer
0.002
316349AD2-085 GEN
Solar/Wind Harmer
0.207
3143873LANEXA
Solar/Wind Harmer
0.181
3142433PROV 92
Adder
0.583
3142433PROV 92
Adder
0.583
971167AH1-042 GEN
Solar/Wind Harmer
26.63
316059AD1-063 C
Solar/Wind Harmer
0.002
970189AG2-124 GEN
Solar/Wind Harmer
8.811
315662AE1-191 GEN
Solar/Wind Harmer
0.01
315666AE1-190 GEN
Solar/Wind Harmer
0.002
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
3141873WAN 176
Solar/Wind Harmer
0.059
3130156CHOWAN
Solar/Wind Harmer
0.292
3130156CHOWAN
Solar/Wind Harmer
0.292
3143316POE
Solar/Wind Harmer
1.153
3141913WHIT STONE
Solar/Wind Harmer
0.285
315816AE2-034 GEN
Solar/Wind Harmer
1.219
3138133OCRAN
Solar/Wind Harmer
0.085
316315AB2-025 C
Solar/Wind Harmer
0.226
315814AE2-033 C
Solar/Wind Harmer
22.041
941031AE2-094 GEN
Solar/Wind Harmer
51.279
944011AF1-069 GEN
Solar/Wind Harmer
16.755
3141783LANCAST
Solar/Wind Harmer
0.167
3141783LANCAST
Solar/Wind Harmer
0.111
3130546PLYMOUTH
Solar/Wind Harmer
0.278
315732AD1-074 GEN1
Solar/Wind Harmer
1.593
315733AD1-074 GEN2
Solar/Wind Harmer
1.593
315735AD1-075 GEN1
Solar/Wind Harmer
0.797
970673AG2-436 GEN
Solar/Wind Harmer
58.436
970673AG2-436 GEN
Solar/Wind Harmer
38.957
3146206CASHIE
Solar/Wind Harmer
0.273
970601AG2-382 GEN
Solar/Wind Harmer
10.212
965291AG1-394 GEN
Solar/Wind Harmer
1.209
971967AH1-528 GEN
Solar/Wind Harmer
43.16
3145893MURPHYS
Solar/Wind Harmer
0.728
3145893MURPHYS
Solar/Wind Harmer
0.269
962981AG1-147 GEN
Solar/Wind Harmer
10.018
3145513AHOSKIE
Solar/Wind Harmer
0.556
3145513AHOSKIE
Solar/Wind Harmer
0.266
3145683EARLEYS
Solar/Wind Harmer
0.53
3145683EARLEYS
Solar/Wind Harmer
0.265
3145683EARLEYS
Solar/Wind Harmer
0.265
970327AG2-215 GEN
Solar/Wind Harmer
8.614
3146043SEABORD
Solar/Wind Harmer
0.261
315607AA1-063A GEN
Solar/Wind Harmer
0.531
970085AG2-068 GEN
Solar/Wind Harmer
13.834
970581AG2-369 GEN
Solar/Wind Harmer
11.898
315652AC1-086 GEN
Solar/Wind Harmer
28.063
316087AB2-174 GEN
Solar/Wind Harmer
0.007
3137643SOCKMAN
Solar/Wind Harmer
1.011
3146033SCOT NK
Solar/Wind Harmer
1.01
971285AH1-108 GEN
Adder
1.899
3145796HORNRTN
Solar/Wind Harmer
0.805
3145796HORNRTN
Solar/Wind Harmer
0.101
316005AA1-067
Solar/Wind Harmer
0.262
3145746EVERETS
Solar/Wind Harmer
0.973
3145746EVERETS
Solar/Wind Harmer
0.244
3145746EVERETS
Solar/Wind Harmer
0.244
3145746EVERETS
Solar/Wind Harmer
0.244
970181AG2-120 GEN
Solar/Wind Harmer
3.044
957861AF2-080 GEN
Solar/Wind Harmer
10.333
316420AA1-050 GEN
Solar/Wind Harmer
0.008
970831AG2-522 GEN
Solar/Wind Harmer
10.106
3141813NORNECK
Solar/Wind Harmer
0.236
3145573BETHELC
Solar/Wind Harmer
0.235
3145573BETHELC
Solar/Wind Harmer
0.235
316319Z2-044 C
Solar/Wind Harmer
0
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
972189AH1-679 GEN
Adder
3.657
971443AH1-215 GEN
Solar/Wind Harmer
3.537
3144303KENBRDG
Solar/Wind Harmer
0.168
316118AC1-105 GEN
Solar/Wind Harmer
0.54
3147173SINAI
Solar/Wind Harmer
0.207
3147243WELCO
Solar/Wind Harmer
0.129
970683AG2-441 GEN
Solar/Wind Harmer
13.748
970681AG2-440 GEN
Solar/Wind Harmer
10.999
946301AF1-294 GEN
Solar/Wind Harmer
3.996
961791AG1-021 GEN
Solar/Wind Harmer
1.944
315657AE1-056 GEN
Solar/Wind Harmer
6.894
970865AG2-541 GEN
Solar/Wind Harmer
6.515
316233AE1-074 FULL
Solar/Wind Harmer
0.149
971281AH1-106 GEN
Solar/Wind Harmer
2.583
971283AH1-107 GEN
Solar/Wind Harmer
2.583
316223AC1-118
Solar/Wind Harmer
0.126
316123AC1-075 GEN
Solar/Wind Harmer
0.24
970165AG2-112 GEN
Solar/Wind Harmer
1.423
970163AG2-111 GEN
Solar/Wind Harmer
1.357
970285AG2-188 GEN
Solar/Wind Harmer
13.264
971845AH1-439 GEN
Solar/Wind Harmer
7.44
3148463FAIRFLD
Solar/Wind Harmer
0.138
3151881LOWMORC
Adder
1.466
3151881LOWMORC
Adder
1.443
3151861LOWMORA
Adder
1.42
3148133STUARTS
Solar/Wind Harmer
0.081
3148013FISHERV
Solar/Wind Harmer
0.078
972205AH1-687 GEN
Adder
5.785
971447AH1-217 GEN
Solar/Wind Harmer
4.064
270494AE1-108_GEN
Solar/Wind Harmer
1.551
270069AE2-166 C O1
Solar/Wind Harmer
0.004
316164AC1-076 GEN
Solar/Wind Helper
1.573
316411AF1-147_GEN1
Solar/Wind Helper
0.945
316415AF1-147_GEN2
Solar/Wind Helper
0.945
3138216PACIFIC
Solar/Wind Helper
0.046
3141426STAFORD
Solar/Wind Helper
0.055
3142296MT RD221
50/50
1.096
3150991CHESPKB
50/50
3.492
3150991CHESPKB
50/50
3.408
316075AC2-137 C
Solar/Wind Harmer
0.09
3142946ENON
Solar/Wind Harmer
0.031
316036AC1-147 C
Solar/Wind Harmer
0.058
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.301
316185AD1-033 GEN
Solar/Wind Harmer
0.009
316236AE1-162_GEN
Solar/Wind Harmer
0.003
3145506HICKORY
Solar/Wind Harmer
1.25
3145506HICKORY
Solar/Wind Harmer
0.75
3145506HICKORY
Solar/Wind Harmer
0.188
316339AD2-160 GEN
Solar/Wind Harmer
0.505
316018AA1-139 ULT2
Solar/Wind Harmer
0.008
316017AA1-139 ULT1
Solar/Wind Harmer
0.174
3150691DARBY 3
Adder
22.343
3150701DARBY 4
Adder
22.291
3150681DARBY 2
Adder
22.265
3150671DARBY 1
Adder
22.239
3137176SLIGO L2192
Solar/Wind Harmer
1.234
3146456SLIGO L269
Solar/Wind Harmer
5.488
3130086AYDLETT
Solar/Wind Harmer
1.238
316033AB2-134 GEN
Solar/Wind Harmer
0.018
315697AD1-025 GEN
Solar/Wind Harmer
0.346
3146386ELIZ CT
Solar/Wind Harmer
0.306
3142366NRTHEST
Adder
1
316431W1029_GEN1
Solar/Wind Harmer
0.002
316433W1029_GEN2
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.301
3146516WINFALL
Solar/Wind Harmer
0.301
3146516WINFALL
Solar/Wind Harmer
0.301
966871AG1-558 GEN
Solar/Wind Harmer
0.347
970657AG2-426 GEN
Solar/Wind Harmer
10.482
970657AG2-426 GEN
Solar/Wind Harmer
2.198
3146626S HERTFORD
Solar/Wind Harmer
0.299
3146626S HERTFORD
Solar/Wind Harmer
0.299
944641AF1-129 GEN
Adder
140.632
316240AF1-291 C
Solar/Wind Harmer
0.002
3146376EDENTON
Solar/Wind Harmer
1.297
3146376EDENTON
Solar/Wind Harmer
1.297
315742AE1-103 GEN
Solar/Wind Harmer
0.003
3144356SAPONY
Solar/Wind Harmer
2.337
316065AD1-022 GEN
Solar/Wind Harmer
12.657
972185AH1-677 GEN
Adder
15.245
3145893MURPHYS
Solar/Wind Harmer
1.804
3145893MURPHYS
Solar/Wind Harmer
0.485
972187AH1-678 GEN
Adder
7.651
3146173TUNIS
Solar/Wind Harmer
0.267
3146173TUNIS
Solar/Wind Harmer
0.267
970933AG2-581 GEN
Solar/Wind Harmer
21
3142666NORTHAMPTON
Solar/Wind Harmer
0.256
3142666NORTHAMPTON
Solar/Wind Harmer
0.256
3142666NORTHAMPTON
Solar/Wind Harmer
0.256
3142666NORTHAMPTON
Solar/Wind Harmer
0.154
316426AA2-053 GEN
Solar/Wind Harmer
0.86
316181AB2-040 GEN
Solar/Wind Harmer
0.368
958261AF2-120 GEN
Solar/Wind Harmer
8.365
3145593CAROLNA
Solar/Wind Harmer
0.252
3145593CAROLNA
Solar/Wind Harmer
0.252
966811AG1-552 GEN
Solar/Wind Harmer
2.738
3145593CAROLNA
Solar/Wind Harmer
0.314
3145796HORNRTN
Solar/Wind Harmer
0.754
3145783HORNRTN
Solar/Wind Harmer
4.467
3145783HORNRTN
Solar/Wind Harmer
3.574
3145783HORNRTN
Solar/Wind Harmer
1.117
3145783HORNRTN
Solar/Wind Harmer
0.447
3145933PARMELE
Solar/Wind Harmer
0.501
3145933PARMELE
Solar/Wind Harmer
0.25
316274AC1-208 GEN
Solar/Wind Harmer
1.272
970099AG2-077 GEN
Solar/Wind Harmer
26.046
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.471
3150341NORNECKC1
Adder
2.451
3145493TOT1
Solar/Wind Harmer
0.546
3145453TOT5
Solar/Wind Harmer
0.327
3145603CNETO
Solar/Wind Harmer
0.218
961601AG1-000A GEN
Solar/Wind Harmer
4.095
316263AC1-034 GEN
Solar/Wind Harmer
8.746
939181AE1-148 GEN
Solar/Wind Harmer
10.786
313527AB2-043 GEN
Solar/Wind Harmer
0.003
971741AH1-377 GEN
Solar/Wind Harmer
21.126
962561AG1-105 GEN
Solar/Wind Harmer
10.222
964791AG1-342 GEN
Solar/Wind Harmer
4.068
3146843MT LREL
Solar/Wind Harmer
0.212
3146843MT LREL
Solar/Wind Harmer
0.212
970323AG2-213 GEN
Solar/Wind Harmer
8.967
971775AH1-396 GEN
Solar/Wind Harmer
0.336
316034AC1-036 C
Solar/Wind Harmer
0.015
316468AD1-105 GEN
Solar/Wind Harmer
-0.067
970301AG2-198 GEN
Solar/Wind Harmer
8.797
958211AF2-115 GEN
Solar/Wind Harmer
2.43
963191AG1-168 GEN
Solar/Wind Harmer
0.81
3144293JTRSVLE
Adder
0.645
3144293JTRSVLE
Adder
0.543
3147133PAMPLIN
Solar/Wind Harmer
0.2
3147133PAMPLIN
Solar/Wind Harmer
0.16
316222AC1-221 GEN
Solar/Wind Harmer
0.802
3143526WINTERP
Solar/Wind Harmer
0.968
942751AE2-291 GEN
Solar/Wind Harmer
9.118
3146776BUCKING
Solar/Wind Harmer
0.649
3146776BUCKING
Solar/Wind Harmer
0.052
270013AE1-250 PV
Solar/Wind Harmer
0.004
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
3.383
315821AE2-092 GEN
Solar/Wind Harmer
0.008
971223AH1-071 GEN
Solar/Wind Harmer
1.43
971489AH1-241 GEN
Solar/Wind Harmer
7.125
316447AC1-158 HLD
Solar/Wind Helper
4.499
315651AD1-115 GEN
Solar/Wind Helper
0.98
226929AD2-058 GEN
Solar/Wind Helper
0.113
23777801MSM_W1-116
Solar/Wind Helper
0.096
237025AB1-124 C
Solar/Wind Helper
0.14
237006AB1-125 GEN
Solar/Wind Helper
0.105
971645AH1-323 GEN
50/50
29.723
3150921YORKTN3
50/50
8.624
3144216WINCHST
50/50
1.289
3151101ELIZAR3
50/50
30.975
3151161SURRY 1
50/50
11.975
3142416OLDCHRC
Solar/Wind Harmer
3.208
316382AG1-145 C
Solar/Wind Harmer
0.003
315773AC2-141 GEN
Solar/Wind Harmer
11.84
970293AG2-193 GEN
Solar/Wind Harmer
3.398
944581AF1-123 GEN
Solar/Wind Harmer
71.01
944601AF1-125 GEN
Solar/Wind Harmer
69.916
3142946ENON
Solar/Wind Harmer
0.105
3144873MCLAUGH
Solar/Wind Harmer
0.008
3144536CHRHLND
Solar/Wind Harmer
0.047
3145336SMITFLD
Solar/Wind Harmer
0.125
3151221GRAVEL6
Adder
22.664
3151171GRAVELC
Adder
4.361
3146456SLIGO L269
Solar/Wind Harmer
0.31
971153AH1-033 GEN
Solar/Wind Harmer
3.585
961611AG1-000B GEN
Solar/Wind Harmer
8.272
972255AH1-712 GEN
Adder
157.541
315778AD1-151 GEN
Solar/Wind Harmer
24.551
316320Y1-086
Solar/Wind Harmer
0.002
970129AG2-093 GEN
Solar/Wind Harmer
18.454
970133AG2-095 GEN
Solar/Wind Harmer
2.91
316435W1029_GEN3
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.301
3142433PROV 92
Adder
0.583
3142433PROV 92
Adder
0.583
316473AC1-191 GEN
Solar/Wind Harmer
1.014
970661AG2-428 GEN
Solar/Wind Harmer
6.346
3141766HARMONY
Solar/Wind Harmer
3.995
3146626S HERTFORD
Solar/Wind Harmer
0.299
316083AB2-161 GEN
Solar/Wind Harmer
0.004
970659AG2-427 GEN
Solar/Wind Harmer
3.158
3141843SHACKLE
Adder
1.519
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
315813AE1-149 C
Solar/Wind Harmer
15.819
316280AD1-041 GEN
Solar/Wind Harmer
0.006
3145273HOLLAND
Solar/Wind Harmer
0.221
316156AD2-030 GEN
Solar/Wind Harmer
0.218
3141873WAN 176
Solar/Wind Harmer
5.232
965281AG1-393 GEN
Solar/Wind Harmer
3.137
315839AE2-212 C
Solar/Wind Harmer
0.002
3143096IRON208
Adder
1.226
3143096IRON208
Adder
1.201
3146376EDENTON
Solar/Wind Harmer
0.291
315614AA2-178 GEN
Solar/Wind Harmer
1.626
971157AH1-035 GEN
Solar/Wind Harmer
3.34
315737AD1-076 GEN
Solar/Wind Harmer
3.567
3146206CASHIE
Solar/Wind Harmer
0.273
3156081AA2-088 GEN
Solar/Wind Harmer
0.006
3145893MURPHYS
Solar/Wind Harmer
0.451
3145893MURPHYS
Solar/Wind Harmer
0.269
957521AF2-046 GEN
Solar/Wind Harmer
20.016
961681AG1-008 GEN
Solar/Wind Harmer
20.016
962971AG1-146 GEN
Solar/Wind Harmer
4.293
3156021HOLLOMANSOL
Solar/Wind Harmer
1.218
3146173TUNIS
Solar/Wind Harmer
0.267
316463AE2-346 GEN
Solar/Wind Harmer
0.229
316140AB2-099
Solar/Wind Harmer
0.095
962331AG1-082 GEN
Solar/Wind Harmer
2.839
316365GEN2_N
Solar/Wind Harmer
0.59
3145963POPLR C
Solar/Wind Harmer
0.263
970009AG2-005 GEN
Solar/Wind Harmer
1.96
3146263WOODLND
Solar/Wind Harmer
0.261
970917AG2-570 GEN
Solar/Wind Harmer
23.14
316317KELFORD C
Solar/Wind Harmer
0.025
3145823KELFORD
Solar/Wind Harmer
0.259
3142666NORTHAMPTON
Solar/Wind Harmer
0.256
313506AB2-031 GEN
Solar/Wind Harmer
0.784
316404AE1-155 C
Solar/Wind Harmer
0.057
3150861SPRUNCD
Adder
1.161
3145796HORNRTN
Solar/Wind Harmer
1.006
3145796HORNRTN
Solar/Wind Harmer
0.251
3145933PARMELE
Solar/Wind Harmer
0.25
966801AG1-551 GEN
Solar/Wind Harmer
2.916
316210AC1-098 GEN
Solar/Wind Harmer
2.297
3145746EVERETS
Solar/Wind Harmer
0.244
3145746EVERETS
Solar/Wind Harmer
0.244
3147043LAWRENC
Solar/Wind Harmer
0.146
315724AD1-057 GEN
Solar/Wind Harmer
0.9
316327AA2-057 GEN
Solar/Wind Harmer
0.36
3150351NORNECKC2
Adder
2.392
316478AD1-087 GEN
Solar/Wind Harmer
0.823
316486AD2-202 GEN
Solar/Wind Harmer
0.242
3146073TAR RVR
Solar/Wind Harmer
0.235
3146083TARBORO
Solar/Wind Harmer
0.235
3146233WITAKRS
Solar/Wind Harmer
1.176
3146233WITAKRS
Solar/Wind Harmer
0.159
3138543CONSLDL
Solar/Wind Harmer
0.154
961601AG1-000A GEN
Solar/Wind Harmer
16.379
3145543BTLEBRO
Solar/Wind Harmer
0.23
3145543BTLEBRO
Solar/Wind Harmer
0.23
971623AH1-311 GEN
Solar/Wind Harmer
0.46
316131AB2-060 GEN
Solar/Wind Harmer
0.687
964241AG1-285 GEN
Solar/Wind Harmer
14.393
315785AD2-033 C
Solar/Wind Harmer
1.721
970257AG2-171 GEN
Solar/Wind Harmer
6.725
959311AF2-222 GEN
Solar/Wind Harmer
18.581
971781AH1-399 GEN
Solar/Wind Harmer
0.272
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
8.82
970909AG2-566 GEN
Solar/Wind Harmer
2.199
963181AG1-167 GEN
Solar/Wind Harmer
0.81
3144293JTRSVLE
Adder
0.645
3147133PAMPLIN
Solar/Wind Harmer
0.627
971193AH1-056 GEN
Solar/Wind Harmer
12.172
971683AH1-343 GEN
Solar/Wind Harmer
7.141
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316283AC2-100 C
Solar/Wind Harmer
0.376
3146926FARMVIL
Solar/Wind Harmer
0.111
3141906WESTMOR
Solar/Wind Harmer
0.07
3146776BUCKING
Solar/Wind Harmer
0.058
970737AG2-469 GEN
Solar/Wind Harmer
6.299
270197AD1-017 GEN1
Solar/Wind Harmer
0.911
315616AA1-038_C
Solar/Wind Harmer
0.001
3151861LOWMORA
Adder
1.478
3147312GRETNA
Solar/Wind Harmer
0.027
941821AE2-187 GEN
Solar/Wind Harmer
4.349
3148013FISHERV
Solar/Wind Harmer
0.135
316313AB2-026
Solar/Wind Harmer
0.085
316258AE1-075 C
Solar/Wind Harmer
0.102
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
2.034
970221AG2-151 GEN
Solar/Wind Harmer
7.125
270018AE2-047 C O1
Solar/Wind Harmer
0.003
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
958131AF2-107 GEN
Solar/Wind Harmer
3.424
270336AE1-100 GEN
Solar/Wind Harmer
0.003
971367AH1-164 GEN
Solar/Wind Harmer
2.104
316044AC1-158 PL1
Solar/Wind Helper
2.044
316450AC1-158 RIC
Solar/Wind Helper
0.545
3141196NOKESVL
Solar/Wind Helper
1.216
316170AC1-121 GEN2
Solar/Wind Helper
0.444
227287AC2-120 GEN
Solar/Wind Helper
0.383
226910AB2-157 C
Solar/Wind Helper
0.016
3147666LOUISA
Solar/Wind Helper
0.591
223402AF1-300 C
Solar/Wind Helper
0.346
237030AB1-096 C
Solar/Wind Helper
0.06
NYPJM->LTFIMP_NY
CLTF
4.044
LGEELTFEXP_LGEE->PJM
CLTF
2.658
WECLTFEXP_WEC->PJM
CLTF
1.346
AG2-052LTFEXP_AG2-052->PJM
LTF
0.074
AH1-155LTFEXP_AH1-155->PJM
LTF
0.112
LAGNLTFEXP_LAGN->PJM
CLTF
12.709
CBM South 2LTFEXP_CBM-S2->PJM
CBM
34.309
TVALTFEXP_TVA->PJM
CLTF
6.437
CBM West 1LTFEXP_CBM-W1->PJM
CBM
47.354
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.437
MECLTFEXP_MEC->PJM
CLTF
6.883
SIGELTFEXP_SIGE->PJM
CLTF
0.213
CPLELTFEXP_CPLE->PJM
CLTF
15.123
CBM West 2LTFEXP_CBM-W2->PJM
CBM
70.159

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57602_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:149.23 %
Rating:5011.0 MVA
Rating Type:C
MVA to Mitigate:7478.0
MW Contribution:192.1
Bus #Bus NameTypeMW Contribution
972263AH1-716 GEN
50/50
220.481
316312AB1-027
Solar/Wind Harmer
1.473
315976AC1-164 GENA
Solar/Wind Harmer
45.938
316169AC1-164_GENC
Solar/Wind Harmer
39.686
315975AC1-164 GENB
Solar/Wind Harmer
1.359
316132AB2-190 GEN1
Solar/Wind Harmer
4.185
316369SG1_INVT
Solar/Wind Harmer
7.375
972265AH1-717 GEN
Adder
28.426
3151201GRAVEL4
Adder
26.648
3151191GRAVEL3
Adder
26.311
3151211GRAVEL5
Adder
26.311
971445AH1-216 GEN
Solar/Wind Harmer
25.381
971285AH1-108 GEN
Adder
2.752
3151081ELIZAR1
Adder
33.275
3151091ELIZAR2
Adder
32.697
3152611GOSPORTB
Adder
4.62
3152621GOSPORTC
Adder
3.921
3152601GOSPORTA
Adder
3.617
971167AH1-042 GEN
Solar/Wind Harmer
38.839
957871AF2-081 GEN
Solar/Wind Harmer
20.163
3142433PROV 92
Adder
0.696
3142433PROV 92
Adder
0.696
957831AF2-077 GEN
Solar/Wind Harmer
1.21
3138283WHITEMARSH
Solar/Wind Harmer
0.062
319010AE1-072 C
Solar/Wind Harmer
8.132
3146406KITTY HAWK
Solar/Wind Harmer
0.033
316305AF2-043 C
Solar/Wind Harmer
1.209
315833AF1-017_GEN
Solar/Wind Harmer
7.57
316349AD2-085 GEN
Solar/Wind Harmer
3.545
316311AC2-079 GEN
Solar/Wind Harmer
20.103
316233AE1-074 FULL
Solar/Wind Harmer
1.071
3143873LANEXA
Solar/Wind Harmer
-0.024
971281AH1-106 GEN
Solar/Wind Harmer
6.47
971283AH1-107 GEN
Solar/Wind Harmer
6.47
315835AF2-110_GEN
Solar/Wind Harmer
4.973
313526AB2-022
Solar/Wind Harmer
1.073
316314AB2-024 C
Solar/Wind Harmer
3.388
3146486SUNBURY
Solar/Wind Harmer
-0.04
3146486SUNBURY
Solar/Wind Harmer
-0.04
3143316POE
Solar/Wind Harmer
-0.156
316321Z2-027
Solar/Wind Harmer
1.067
3146396TANGLEW
Solar/Wind Harmer
0.728
3145176PASQUOTANK
Solar/Wind Harmer
-0.024
316059AD1-063 C
Solar/Wind Harmer
0.886
315662AE1-191 GEN
Solar/Wind Harmer
4.681
315666AE1-190 GEN
Solar/Wind Harmer
1.17
315611Z1-036_GEN2
Solar/Wind Harmer
9.52
957601AF2-054 GEN
Solar/Wind Harmer
1.152
3141873WAN 176
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.038
3130156CHOWAN
Solar/Wind Harmer
-0.038
316315AB2-025 C
Solar/Wind Harmer
1.009
3141913WHIT STONE
Solar/Wind Harmer
-0.037
315814AE2-033 C
Solar/Wind Harmer
34.733
3138133OCRAN
Solar/Wind Harmer
-0.011
315816AE2-034 GEN
Solar/Wind Harmer
3.002
941031AE2-094 GEN
Solar/Wind Harmer
68.862
944011AF1-069 GEN
Solar/Wind Harmer
21.577
3141783LANCAST
Solar/Wind Harmer
-0.022
3141783LANCAST
Solar/Wind Harmer
-0.014
3142296MT RD221
50/50
1.31
3150691DARBY 3
50/50
29.1
3150701DARBY 4
50/50
29.033
3150681DARBY 2
50/50
28.999
3150671DARBY 1
50/50
28.965
3142366NRTHEST
50/50
1.317
316075AC2-137 C
Solar/Wind Harmer
1.17
3142946ENON
Solar/Wind Harmer
-0.004
316033AB2-134 GEN
Solar/Wind Harmer
13.312
315697AD1-025 GEN
Solar/Wind Harmer
8.349
944641AF1-129 GEN
Adder
174.133
316236AE1-162_GEN
Solar/Wind Harmer
1.236
316240AF1-291 C
Solar/Wind Harmer
1.232
316036AC1-147 C
Solar/Wind Harmer
1.1
3150991CHESPKB
Adder
3.801
3150991CHESPKB
Adder
3.709
316316AC1-027 C
Solar/Wind Harmer
1.249
3142956BIRDNECK
Solar/Wind Harmer
2.183
316185AD1-033 GEN
Solar/Wind Harmer
4.286
3145506HICKORY
Solar/Wind Harmer
-0.161
3145506HICKORY
Solar/Wind Harmer
-0.097
3145506HICKORY
Solar/Wind Harmer
-0.024
316339AD2-160 GEN
Solar/Wind Harmer
2.723
316018AA1-139 ULT2
Solar/Wind Harmer
3.455
316017AA1-139 ULT1
Solar/Wind Harmer
3.263
3137176SLIGO L2192
Solar/Wind Harmer
-0.159
3146456SLIGO L269
Solar/Wind Harmer
4.752
966871AG1-558 GEN
Solar/Wind Harmer
1.209
966871AG1-558 GEN
Solar/Wind Harmer
0.413
3130086AYDLETT
Solar/Wind Harmer
-0.16
970657AG2-426 GEN
Solar/Wind Harmer
12.492
970657AG2-426 GEN
Solar/Wind Harmer
2.612
3143526WINTERP
Solar/Wind Harmer
-0.206
3146386ELIZ CT
Solar/Wind Harmer
-0.04
316431W1029_GEN1
Solar/Wind Harmer
7.121
316433W1029_GEN2
Solar/Wind Harmer
7.121
3146516WINFALL
Solar/Wind Harmer
-0.039
3146516WINFALL
Solar/Wind Harmer
-0.039
3146516WINFALL
Solar/Wind Harmer
-0.039
316441AF1-014 GEN
Solar/Wind Harmer
2.633
3146626S HERTFORD
Solar/Wind Harmer
-0.039
3146626S HERTFORD
Solar/Wind Harmer
-0.039
971223AH1-071 GEN
Solar/Wind Harmer
4.826
315742AE1-103 GEN
Solar/Wind Harmer
3.978
3146376EDENTON
Solar/Wind Harmer
1.128
3146376EDENTON
Solar/Wind Harmer
1.128
3144356SAPONY
Solar/Wind Harmer
1.305
316065AD1-022 GEN
Solar/Wind Harmer
17.989
972185AH1-677 GEN
Adder
17.917
972187AH1-678 GEN
Adder
8.997
3145893MURPHYS
Solar/Wind Harmer
0.99
3145893MURPHYS
Solar/Wind Harmer
-0.064
3146173TUNIS
Solar/Wind Harmer
-0.035
3146173TUNIS
Solar/Wind Harmer
-0.035
970933AG2-581 GEN
Solar/Wind Harmer
32.706
316487AF1-042 GEN
Solar/Wind Harmer
4.538
3142666NORTHAMPTON
Solar/Wind Harmer
-0.034
3142666NORTHAMPTON
Solar/Wind Harmer
-0.034
3142666NORTHAMPTON
Solar/Wind Harmer
-0.034
3142666NORTHAMPTON
Solar/Wind Harmer
-0.02
316181AB2-040 GEN
Solar/Wind Harmer
4.712
316426AA2-053 GEN
Solar/Wind Harmer
3.407
3145593CAROLNA
Solar/Wind Harmer
-0.033
3145593CAROLNA
Solar/Wind Harmer
-0.033
966811AG1-552 GEN
Solar/Wind Harmer
3.768
3145593CAROLNA
Solar/Wind Harmer
0.278
3145796HORNRTN
Solar/Wind Harmer
-0.099
3145783HORNRTN
Solar/Wind Harmer
3.954
3145783HORNRTN
Solar/Wind Harmer
3.163
3145783HORNRTN
Solar/Wind Harmer
0.988
3145783HORNRTN
Solar/Wind Harmer
0.395
958261AF2-120 GEN
Solar/Wind Harmer
12.878
3145933PARMELE
Solar/Wind Harmer
-0.065
3145933PARMELE
Solar/Wind Harmer
-0.033
970099AG2-077 GEN
Solar/Wind Harmer
40.962
316274AC1-208 GEN
Solar/Wind Harmer
3.495
316077AC2-138 C
Solar/Wind Harmer
0.655
3150341NORNECKC1
Adder
2.894
3150341NORNECKC1
Adder
2.871
3144293JTRSVLE
Adder
0.817
3144293JTRSVLE
Adder
0.688
316447AC1-158 HLD
Solar/Wind Helper
5.533
315651AD1-115 GEN
Solar/Wind Helper
1.131
226929AD2-058 GEN
Solar/Wind Helper
0.127
23777801MSM_W1-116
Solar/Wind Helper
0.11
237025AB1-124 C
Solar/Wind Helper
0.16
237006AB1-125 GEN
Solar/Wind Helper
0.12
237034AC2-136 C
Solar/Wind Helper
0.207
23777901MDS_W4-102
Solar/Wind Helper
0.152
235020AA1-095 C
Solar/Wind Helper
0.045
237001AB1-127_GEN
Solar/Wind Helper
0.385
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
237002AB1-128_GEN
Solar/Wind Helper
0.384
235063AE1-101 C2
Solar/Wind Helper
1.425
205916AD1-020 GEN
Solar/Wind Helper
1.648
233933AB2-153 GEN
Solar/Wind Helper
0.225
233944AB2-135 GEN
Solar/Wind Helper
0.57
232424Y1-079 C
Solar/Wind Helper
0.113
233987AB2-037 GEN
Solar/Wind Helper
2.269
234036AF2-325 C
Solar/Wind Helper
0.041
233946AB2-136 GEN
Solar/Wind Helper
0.55
233901CHERRYDALE C
Solar/Wind Helper
0.225
232408W1-005 C
Solar/Wind Helper
0.491
232410W1-006 C
Solar/Wind Helper
0.491
233939AC1-091 C
Solar/Wind Helper
0.339
233970AC1-092 C
Solar/Wind Helper
0.339
238175AF1-290_GEN
Solar/Wind Helper
0.118
230433AD2-135 GEN
Solar/Wind Helper
0.016
230407AD2-065 C
Solar/Wind Helper
0.039
219921AF1-264
Solar/Wind Helper
0.049
219615MILLCREEK C
Solar/Wind Helper
0.025
3130546PLYMOUTH
Solar/Wind Harmer
-0.036
315732AD1-074 GEN1
Solar/Wind Harmer
7.333
315733AD1-074 GEN2
Solar/Wind Harmer
7.333
315735AD1-075 GEN1
Solar/Wind Harmer
3.667
972193AH1-681 GEN
Adder
7.366
970673AG2-436 GEN
Solar/Wind Harmer
75.963
970673AG2-436 GEN
Solar/Wind Harmer
38.462
3146206CASHIE
Solar/Wind Harmer
-0.036
970601AG2-382 GEN
Solar/Wind Harmer
15.671
965291AG1-394 GEN
Solar/Wind Harmer
3.177
971967AH1-528 GEN
Solar/Wind Harmer
67.134
316318V4-068
Solar/Wind Harmer
0.884
3145893MURPHYS
Solar/Wind Harmer
-0.095
3145893MURPHYS
Solar/Wind Harmer
-0.035
962981AG1-147 GEN
Solar/Wind Harmer
15.399
3145513AHOSKIE
Solar/Wind Harmer
0.305
961941AG1-037 GEN
Solar/Wind Harmer
0.263
3145513AHOSKIE
Solar/Wind Harmer
-0.035
3145683EARLEYS
Solar/Wind Harmer
-0.069
3145683EARLEYS
Solar/Wind Harmer
-0.035
3145683EARLEYS
Solar/Wind Harmer
-0.035
3146043SEABORD
Solar/Wind Harmer
-0.034
315607AA1-063A GEN
Solar/Wind Harmer
3.475
970085AG2-068 GEN
Solar/Wind Harmer
21.415
970581AG2-369 GEN
Solar/Wind Harmer
18.417
946281AF1-292 GEN
Solar/Wind Harmer
0.762
316087AB2-174 GEN
Solar/Wind Harmer
4.83
315652AC1-086 GEN
Solar/Wind Harmer
38.044
3137643SOCKMAN
Solar/Wind Harmer
-0.134
3145796HORNRTN
Solar/Wind Harmer
-0.106
3145796HORNRTN
Solar/Wind Harmer
-0.013
3146033SCOT NK
Solar/Wind Harmer
-0.133
316005AA1-067
Solar/Wind Harmer
0.65
3145746EVERETS
Solar/Wind Harmer
-0.127
3145746EVERETS
Solar/Wind Harmer
-0.032
3145746EVERETS
Solar/Wind Harmer
-0.032
3145746EVERETS
Solar/Wind Harmer
-0.032
970181AG2-120 GEN
Solar/Wind Harmer
4.22
970831AG2-522 GEN
Solar/Wind Harmer
15.843
957861AF2-080 GEN
Solar/Wind Harmer
13.805
316420AA1-050 GEN
Solar/Wind Harmer
3.571
3141813NORNECK
Solar/Wind Harmer
-0.031
972189AH1-679 GEN
Adder
4.354
972205AH1-687 GEN
Adder
8.98
3151881LOWMORC
Adder
1.603
3151881LOWMORC
Adder
1.578
3151861LOWMORA
Adder
1.553
316164AC1-076 GEN
Solar/Wind Helper
1.831
316411AF1-147_GEN1
Solar/Wind Helper
1.081
316415AF1-147_GEN2
Solar/Wind Helper
1.081
3138216PACIFIC
Solar/Wind Helper
0.053
3141426STAFORD
Solar/Wind Helper
0.061
237085AD2-009_GEN
Solar/Wind Helper
1.391
960921AF2-383 GEN
Solar/Wind Helper
0.176
233935AB2-179 C
Solar/Wind Helper
1.231
205943AE1-185 GEN
Solar/Wind Helper
0.492
232436AB1-176 C
Solar/Wind Helper
0.043
205932AD2-116_GEN
Solar/Wind Helper
0.492
205956AE1-196_GEN
Solar/Wind Helper
0.492
233923SMA
Solar/Wind Helper
0.928
233990AG1-397 GEN
Solar/Wind Helper
0.029
232432Z2-076 GEN
Solar/Wind Helper
0.065
234033AF1-007_GEN
Solar/Wind Helper
6.8
964001AG1-254 GEN
Solar/Wind Helper
0.919
238208AF1-136 C
Solar/Wind Helper
0.173
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.025
219914AD2-027 C
Solar/Wind Helper
0.11
219272CLEANLIGHT C
Solar/Wind Helper
0.024
219688LUMSOLAR_S C
Solar/Wind Helper
0.038
219607WPEMNERT C
Solar/Wind Helper
0.077
971645AH1-323 GEN
50/50
34.83
3151161SURRY 1
50/50
14.063
3142416OLDCHRC
Solar/Wind Harmer
4.408
970293AG2-193 GEN
Solar/Wind Harmer
5.386
3142946ENON
Solar/Wind Harmer
-0.014
316382AG1-145 C
Solar/Wind Harmer
1.281
3143096IRON208
Adder
1.57
3143096IRON208
Adder
1.538
3150921YORKTN3
Adder
9.353
3144216WINCHST
Adder
1.401
315773AC2-141 GEN
Solar/Wind Harmer
17.422
970133AG2-095 GEN
Solar/Wind Harmer
4.665
970129AG2-093 GEN
Solar/Wind Harmer
23.298
315778AD1-151 GEN
Solar/Wind Harmer
35.792
961611AG1-000B GEN
Solar/Wind Harmer
8.673
3151221GRAVEL6
Adder
26.617
3151171GRAVELC
Adder
5.121
3150861SPRUNCD
Adder
1.682
3145336SMITFLD
Solar/Wind Harmer
-0.016
3144536CHRHLND
Solar/Wind Harmer
-0.006
944581AF1-123 GEN
Solar/Wind Harmer
185.641
944601AF1-125 GEN
Solar/Wind Harmer
182.744
3151101ELIZAR3
Adder
33.701
3144873MCLAUGH
Solar/Wind Harmer
-0.001
965281AG1-393 GEN
Solar/Wind Harmer
5.061
315839AE2-212 C
Solar/Wind Harmer
1.217
3142433PROV 92
Adder
0.696
3142433PROV 92
Adder
0.696
3146456SLIGO L269
Solar/Wind Harmer
-0.04
971153AH1-033 GEN
Solar/Wind Harmer
4.905
316473AC1-191 GEN
Solar/Wind Harmer
4.326
315813AE1-149 C
Solar/Wind Harmer
25.043
970659AG2-427 GEN
Solar/Wind Harmer
3.766
316083AB2-161 GEN
Solar/Wind Harmer
6.49
970661AG2-428 GEN
Solar/Wind Harmer
7.523
316320Y1-086
Solar/Wind Harmer
2.331
316435W1029_GEN3
Solar/Wind Harmer
7.121
3141766HARMONY
Solar/Wind Harmer
3.49
3146516WINFALL
Solar/Wind Harmer
-0.039
3141843SHACKLE
Adder
1.777
316203AE2-005 GEN
Solar/Wind Harmer
16.468
3146626S HERTFORD
Solar/Wind Harmer
-0.039
316280AD1-041 GEN
Solar/Wind Harmer
2.926
3145273HOLLAND
Solar/Wind Harmer
-0.029
316156AD2-030 GEN
Solar/Wind Harmer
1.029
3141873WAN 176
Solar/Wind Harmer
4.571
3146376EDENTON
Solar/Wind Harmer
-0.038
315614AA2-178 GEN
Solar/Wind Harmer
4.002
971157AH1-035 GEN
Solar/Wind Harmer
4.549
315737AD1-076 GEN
Solar/Wind Harmer
6.891
972255AH1-712 GEN
Adder
164.849
3156081AA2-088 GEN
Solar/Wind Harmer
11.679
3146206CASHIE
Solar/Wind Harmer
-0.036
3145893MURPHYS
Solar/Wind Harmer
0.248
3145893MURPHYS
Solar/Wind Harmer
-0.035
957521AF2-046 GEN
Solar/Wind Harmer
27.872
961681AG1-008 GEN
Solar/Wind Harmer
27.872
962971AG1-146 GEN
Solar/Wind Harmer
6.6
3156021HOLLOMANSOL
Solar/Wind Harmer
4.742
3146173TUNIS
Solar/Wind Harmer
-0.035
316365GEN2_N
Solar/Wind Harmer
2.36
316463AE2-346 GEN
Solar/Wind Harmer
0.566
316140AB2-099
Solar/Wind Harmer
0.236
962331AG1-082 GEN
Solar/Wind Harmer
4.374
3146263WOODLND
Solar/Wind Harmer
-0.034
3145963POPLR C
Solar/Wind Harmer
-0.034
316484AD2-074 GEN
Solar/Wind Harmer
8.672
970009AG2-005 GEN
Solar/Wind Harmer
4.306
970917AG2-570 GEN
Solar/Wind Harmer
85.969
316317KELFORD C
Solar/Wind Harmer
1.606
3145823KELFORD
Solar/Wind Harmer
-0.034
966621AG1-532 GEN
Solar/Wind Harmer
0.691
3142666NORTHAMPTON
Solar/Wind Harmer
-0.034
313506AB2-031 GEN
Solar/Wind Harmer
2.715
3145796HORNRTN
Solar/Wind Harmer
-0.133
3145796HORNRTN
Solar/Wind Harmer
-0.033
316404AE1-155 C
Solar/Wind Harmer
6.411
3145933PARMELE
Solar/Wind Harmer
-0.033
966801AG1-551 GEN
Solar/Wind Harmer
4.109
3147043LAWRENC
Solar/Wind Harmer
-0.019
316210AC1-098 GEN
Solar/Wind Harmer
5.131
316313AB2-026
Solar/Wind Harmer
0.88
316258AE1-075 C
Solar/Wind Harmer
0.792
316405AF2-144 C
Solar/Wind Harmer
0.836
3143336POWHATN
Solar/Wind Harmer
3.29
3145746EVERETS
Solar/Wind Harmer
-0.032
3145746EVERETS
Solar/Wind Harmer
-0.032
315724AD1-057 GEN
Solar/Wind Harmer
1.824
316478AD1-087 GEN
Solar/Wind Harmer
2.743
316486AD2-202 GEN
Solar/Wind Harmer
0.803
316327AA2-057 GEN
Solar/Wind Harmer
3.182
3150351NORNECKC2
Adder
2.802
3144293JTRSVLE
Adder
0.817
3151861LOWMORA
Adder
1.616
316044AC1-158 PL1
Solar/Wind Helper
2.514
316450AC1-158 RIC
Solar/Wind Helper
0.67
3141196NOKESVL
Solar/Wind Helper
1.391
316170AC1-121 GEN2
Solar/Wind Helper
0.513
227287AC2-120 GEN
Solar/Wind Helper
0.433
226910AB2-157 C
Solar/Wind Helper
0.018
3147666LOUISA
Solar/Wind Helper
0.666
223402AF1-300 C
Solar/Wind Helper
0.394
237030AB1-096 C
Solar/Wind Helper
0.069
3132273ORANGE
Solar/Wind Helper
0.05
238221AF1-254 C O1
Solar/Wind Helper
0.238
235067AD1-061 GEN
Solar/Wind Helper
0.424
205917AD1-020 ES
Solar/Wind Helper
0.354
233982AB2-133 GEN
Solar/Wind Helper
0.347
233918AB1-142 GEN
Solar/Wind Helper
0.487
233994AC2-023 GEN
Solar/Wind Helper
0.931
233996TM1833_GEN
Solar/Wind Helper
0.253
233997TMININ_4.2
Solar/Wind Helper
0.253
232406W1-004 FULL
Solar/Wind Helper
0.491
233940AF2-379 C
Solar/Wind Helper
0.06
234015AF2-250 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.225
233971AC1-093 C
Solar/Wind Helper
0.346
230430AE1-229_GEN
Solar/Wind Helper
3.244
230415AB2-049 C
Solar/Wind Helper
0.029
228729W2-030 C
Solar/Wind Helper
0.106
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.052
219912AD2-042 GEN
Solar/Wind Helper
0.144
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.11
3152331SURRY 2
50/50
15.855
3142416OLDCHRC
Solar/Wind Harmer
-0.113
3142416OLDCHRC
Solar/Wind Harmer
-0.043
316159AE1-175 C
Solar/Wind Harmer
1.141
944631AF1-128 GEN
Adder
179.448
3143096IRON208
Adder
1.57
3138126ROCKLANDING
Solar/Wind Harmer
0.128
971317AH1-138 GEN
Solar/Wind Harmer
5.215
316294AC1-161 GEN
Solar/Wind Harmer
13.471
3142543TWELFTH
Solar/Wind Harmer
-0.004
970129AG2-093 GEN
Solar/Wind Harmer
9.437
316458AB2-190 GEN2
Solar/Wind Harmer
4.185
971069AG2-661 GEN
Solar/Wind Harmer
6.537
971647AH1-324 GEN
Solar/Wind Harmer
20.617
961611AG1-000B GEN
Solar/Wind Harmer
20.327
3151171GRAVELC
Adder
3.894
3150851SPRUNCC
Adder
1.682
3145336SMITFLD
Solar/Wind Harmer
-0.163
944591AF1-124 GEN
Solar/Wind Harmer
186.31
316375AC2-012 GEN
Solar/Wind Harmer
14.108
3150981CHESPKA
Adder
4.53
315671AE2-027_GEN
Solar/Wind Harmer
30.454
316072AD1-144
Solar/Wind Harmer
0.817
316388AE2-253 GEN
Solar/Wind Harmer
2.723
3142433PROV 92
Solar/Wind Harmer
-0.16
3142433PROV 92
Adder
0.696
3142433PROV 92
Adder
0.696
3146456SLIGO L269
Solar/Wind Harmer
-0.04
316246AF1-032 C
Solar/Wind Harmer
0.811
970659AG2-427 GEN
Solar/Wind Harmer
21.25
316381AD1-082 GEN
Solar/Wind Harmer
3.667
970661AG2-428 GEN
Solar/Wind Harmer
42.449
3143526WINTERP
Solar/Wind Harmer
-0.206
316093AE2-104_GEN
Solar/Wind Harmer
11.566
3141766HARMONY
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.126
3146516WINFALL
Solar/Wind Harmer
-0.039
939411AE1-173 GEN
Solar/Wind Harmer
195.386
971777AH1-397 GEN
Solar/Wind Harmer
4.594
3141843SHACKLE
Adder
1.777
3143226MDLTHAN
Solar/Wind Harmer
-0.038
940641AE2-051 GEN
Solar/Wind Harmer
36.152
315800Z1-036_GEN1
Solar/Wind Harmer
9.52
3130156CHOWAN
Solar/Wind Harmer
-0.038
3138133OCRAN
Solar/Wind Harmer
-0.022
3145663CRESWEL
Solar/Wind Harmer
-0.103
971163AH1-040 GEN
Solar/Wind Harmer
34.777
972277AH1-723 GEN
Adder
192.1
3146206CASHIE
Solar/Wind Harmer
-0.036
971547AH1-271 GEN
Solar/Wind Harmer
8.955
3145893MURPHYS
Solar/Wind Harmer
-0.141
3145893MURPHYS
Solar/Wind Harmer
1.053
3146173TUNIS
Solar/Wind Harmer
-0.035
316023GEN1_S
Solar/Wind Harmer
2.36
3145683EARLEYS
Solar/Wind Harmer
-0.035
3146263WOODLND
Solar/Wind Harmer
-0.034
3145963POPLR C
Solar/Wind Harmer
-0.034
961951AG1-038 GEN
Solar/Wind Harmer
4.538
970919AG2-571 GEN
Solar/Wind Harmer
10.882
970087AG2-069 GEN
Solar/Wind Harmer
32.123
316174AB2-169 GEN
Solar/Wind Harmer
5.263
3145823KELFORD
Solar/Wind Harmer
-0.034
960081AF2-299 GEN
Solar/Wind Harmer
3.829
316011AB1-132 GEN
Solar/Wind Harmer
7.075
962571AG1-106 GEN
Solar/Wind Harmer
4.861
316190AA2-174 GEN
Solar/Wind Harmer
0.414
962861AG1-135 GEN
Solar/Wind Harmer
12.583
3145796HORNRTN
Solar/Wind Harmer
-0.109
3145796HORNRTN
Solar/Wind Harmer
-0.033
3145783HORNRTN
Solar/Wind Harmer
-0.033
971795AH1-408 GEN
Solar/Wind Harmer
24.88
3146293MARTNCO
Solar/Wind Harmer
0.204
3147043LAWRENC
Adder
2.639
957481AF2-042 GEN
Solar/Wind Harmer
102.405
316212AC1-099_GEN
Solar/Wind Harmer
2.851
3143336POWHATN
Solar/Wind Harmer
3.871
964211AG1-282 GEN
Solar/Wind Harmer
0.968
3141726DUNNSVL
Solar/Wind Harmer
-0.128
3145746EVERETS
Solar/Wind Harmer
-0.032
3145746EVERETS
Solar/Wind Harmer
-0.032
315693AD1-088 GEN
Solar/Wind Harmer
16.002
962491AG1-098 GEN
Solar/Wind Harmer
21.316
315722AD1-056 GEN
Solar/Wind Harmer
3.316
316494AC1-189 GEN
Solar/Wind Harmer
3.395
316129AC1-054 GEN
Solar/Wind Harmer
2.761
971065AG2-659 GEN
Solar/Wind Harmer
15.657
3150351NORNECKC2
Adder
2.755
3144293JTRSVLE
Adder
0.817
316045AC1-158 PL2
Solar/Wind Helper
8.047
316006AB2-029 C
Solar/Wind Helper
0.164
316254AC1-120 GEN1
Solar/Wind Helper
1.539
3147666LOUISA
Solar/Wind Helper
1.158
316192AB2-158 GEN
Solar/Wind Helper
1.899
223401AF1-299 GEN
Solar/Wind Helper
0.394
23779801AA1-109
Solar/Wind Helper
0.185
237080AD1-060 GEN
Solar/Wind Helper
0.295
237038AE2-054 C
Solar/Wind Helper
0.234
235062AE1-101 C1
Solar/Wind Helper
1.425
966131AG1-482 GEN
Solar/Wind Helper
0.075
233930AB2-032 GEN
Solar/Wind Helper
0.369
233915AB1-141 GEN
Solar/Wind Helper
0.487
232422X3-066 FULL
Solar/Wind Helper
0.111
232426Y1-080 FULL
Solar/Wind Helper
0.038
233964AF2-378 GEN
Solar/Wind Helper
0.04
233998TM1NIN_3.36
Solar/Wind Helper
0.253
232404W1-003 C
Solar/Wind Helper
0.491
232428Y3-058 C
Solar/Wind Helper
0.328
232434Z2-077 GEN
Solar/Wind Helper
0.123
233954AC2-188 GEN
Solar/Wind Helper
0.225
233950AC2-186 GEN
Solar/Wind Helper
0.113
233972AC1-094 C
Solar/Wind Helper
0.293
230511AF1-262
Solar/Wind Helper
0.014
230434AG1-499 GEN
Solar/Wind Helper
0.221
228728W1-130C
Solar/Wind Helper
0.052
219258KINSLEYDEP C
Solar/Wind Helper
0.074
219904AC1-010 C
Solar/Wind Helper
0.058
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219907AC1-030 C
Solar/Wind Helper
0.032
219686LUMSOLAR_N C
Solar/Wind Helper
0.038
219304NAMERICA C
Solar/Wind Helper
0.126
316336AC2-165 C
Solar/Wind Harmer
4.115
NYPJM->LTFIMP_NY
CLTF
4.642
LGEELTFEXP_LGEE->PJM
CLTF
3.021
WECLTFEXP_WEC->PJM
CLTF
1.528
AG2-052LTFEXP_AG2-052->PJM
LTF
0.084
AH1-155LTFEXP_AH1-155->PJM
LTF
0.126
LAGNLTFEXP_LAGN->PJM
CLTF
14.648
CBM South 2LTFEXP_CBM-S2->PJM
CBM
40.037
TVALTFEXP_TVA->PJM
CLTF
7.416
CBM West 1LTFEXP_CBM-W1->PJM
CBM
53.69
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.806
MECLTFEXP_MEC->PJM
CLTF
7.852
SIGELTFEXP_SIGE->PJM
CLTF
0.243
CPLELTFEXP_CPLE->PJM
CLTF
17.726
CBM West 2LTFEXP_CBM-W2->PJM
CBM
80.522

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: WT576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:149.23 %
Rating:5011.0 MVA
Rating Type:C
MVA to Mitigate:7477.96
MW Contribution:192.1
Bus #Bus NameTypeMW Contribution
3142296MT RD221
50/50
1.31
3150691DARBY 3
50/50
29.1
3150701DARBY 4
50/50
29.033
3150681DARBY 2
50/50
28.999
3150671DARBY 1
50/50
28.965
3142366NRTHEST
50/50
1.317
316075AC2-137 C
Solar/Wind Harmer
1.17
3142946ENON
Solar/Wind Harmer
-0.004
316033AB2-134 GEN
Solar/Wind Harmer
13.312
315697AD1-025 GEN
Solar/Wind Harmer
8.349
944641AF1-129 GEN
Adder
174.133
316236AE1-162_GEN
Solar/Wind Harmer
1.236
316240AF1-291 C
Solar/Wind Harmer
1.232
316036AC1-147 C
Solar/Wind Harmer
1.1
3150991CHESPKB
Adder
3.801
3150991CHESPKB
Adder
3.709
316316AC1-027 C
Solar/Wind Harmer
1.249
3142956BIRDNECK
Solar/Wind Harmer
2.183
316185AD1-033 GEN
Solar/Wind Harmer
4.286
3145506HICKORY
Solar/Wind Harmer
-0.161
3145506HICKORY
Solar/Wind Harmer
-0.097
3145506HICKORY
Solar/Wind Harmer
-0.024
316339AD2-160 GEN
Solar/Wind Harmer
2.723
316018AA1-139 ULT2
Solar/Wind Harmer
3.455
316017AA1-139 ULT1
Solar/Wind Harmer
3.263
3137176SLIGO L2192
Solar/Wind Harmer
-0.159
3146456SLIGO L269
Solar/Wind Harmer
4.752
966871AG1-558 GEN
Solar/Wind Harmer
1.209
966871AG1-558 GEN
Solar/Wind Harmer
0.413
3130086AYDLETT
Solar/Wind Harmer
-0.16
970657AG2-426 GEN
Solar/Wind Harmer
12.492
970657AG2-426 GEN
Solar/Wind Harmer
2.612
3143526WINTERP
Solar/Wind Harmer
-0.206
3146386ELIZ CT
Solar/Wind Harmer
-0.04
316431W1029_GEN1
Solar/Wind Harmer
7.121
316433W1029_GEN2
Solar/Wind Harmer
7.121
3146516WINFALL
Solar/Wind Harmer
-0.039
3146516WINFALL
Solar/Wind Harmer
-0.039
3146516WINFALL
Solar/Wind Harmer
-0.039
316441AF1-014 GEN
Solar/Wind Harmer
2.633
3146626S HERTFORD
Solar/Wind Harmer
-0.039
972263AH1-716 GEN
50/50
220.481
316312AB1-027
Solar/Wind Harmer
1.473
315976AC1-164 GENA
Solar/Wind Harmer
45.938
316169AC1-164_GENC
Solar/Wind Harmer
39.686
315975AC1-164 GENB
Solar/Wind Harmer
1.359
316132AB2-190 GEN1
Solar/Wind Harmer
4.185
316369SG1_INVT
Solar/Wind Harmer
7.375
972265AH1-717 GEN
Adder
28.427
3151201GRAVEL4
Adder
26.648
3151191GRAVEL3
Adder
26.311
3151211GRAVEL5
Adder
26.311
971445AH1-216 GEN
Solar/Wind Harmer
25.381
971285AH1-108 GEN
Adder
2.752
3151081ELIZAR1
Adder
33.275
3151091ELIZAR2
Adder
32.697
3152611GOSPORTB
Adder
4.62
3152621GOSPORTC
Adder
3.921
3152601GOSPORTA
Adder
3.617
971167AH1-042 GEN
Solar/Wind Harmer
38.839
957871AF2-081 GEN
Solar/Wind Harmer
20.163
3142433PROV 92
Adder
0.696
3142433PROV 92
Adder
0.696
957831AF2-077 GEN
Solar/Wind Harmer
1.21
3138283WHITEMARSH
Solar/Wind Harmer
0.062
319010AE1-072 C
Solar/Wind Harmer
8.132
3146406KITTY HAWK
Solar/Wind Harmer
0.033
316305AF2-043 C
Solar/Wind Harmer
1.209
315833AF1-017_GEN
Solar/Wind Harmer
7.57
316349AD2-085 GEN
Solar/Wind Harmer
3.545
316311AC2-079 GEN
Solar/Wind Harmer
20.103
316233AE1-074 FULL
Solar/Wind Harmer
1.071
3143873LANEXA
Solar/Wind Harmer
-0.024
971281AH1-106 GEN
Solar/Wind Harmer
6.47
971283AH1-107 GEN
Solar/Wind Harmer
6.47
315835AF2-110_GEN
Solar/Wind Harmer
4.973
313526AB2-022
Solar/Wind Harmer
1.073
316314AB2-024 C
Solar/Wind Harmer
3.388
3146486SUNBURY
Solar/Wind Harmer
-0.04
3146486SUNBURY
Solar/Wind Harmer
-0.04
3143316POE
Solar/Wind Harmer
-0.156
316321Z2-027
Solar/Wind Harmer
1.067
3146396TANGLEW
Solar/Wind Harmer
0.728
3145176PASQUOTANK
Solar/Wind Harmer
-0.024
316059AD1-063 C
Solar/Wind Harmer
0.886
315662AE1-191 GEN
Solar/Wind Harmer
4.681
315666AE1-190 GEN
Solar/Wind Harmer
1.17
315611Z1-036_GEN2
Solar/Wind Harmer
9.52
957601AF2-054 GEN
Solar/Wind Harmer
1.152
3141873WAN 176
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.038
3130156CHOWAN
Solar/Wind Harmer
-0.038
316315AB2-025 C
Solar/Wind Harmer
1.009
3141913WHIT STONE
Solar/Wind Harmer
-0.037
315814AE2-033 C
Solar/Wind Harmer
34.733
3138133OCRAN
Solar/Wind Harmer
-0.011
315816AE2-034 GEN
Solar/Wind Harmer
3.002
941031AE2-094 GEN
Solar/Wind Harmer
68.861
944011AF1-069 GEN
Solar/Wind Harmer
21.577
3141783LANCAST
Solar/Wind Harmer
-0.022
3141783LANCAST
Solar/Wind Harmer
-0.014
3130546PLYMOUTH
Solar/Wind Harmer
-0.036
315732AD1-074 GEN1
Solar/Wind Harmer
7.333
315733AD1-074 GEN2
Solar/Wind Harmer
7.333
315735AD1-075 GEN1
Solar/Wind Harmer
3.667
972193AH1-681 GEN
Adder
7.366
970673AG2-436 GEN
Solar/Wind Harmer
75.963
970673AG2-436 GEN
Solar/Wind Harmer
38.462
3146206CASHIE
Solar/Wind Harmer
-0.036
970601AG2-382 GEN
Solar/Wind Harmer
15.671
965291AG1-394 GEN
Solar/Wind Harmer
3.177
971967AH1-528 GEN
Solar/Wind Harmer
67.133
316318V4-068
Solar/Wind Harmer
0.884
3145893MURPHYS
Solar/Wind Harmer
-0.095
3145893MURPHYS
Solar/Wind Harmer
-0.035
962981AG1-147 GEN
Solar/Wind Harmer
15.399
3145513AHOSKIE
Solar/Wind Harmer
0.305
961941AG1-037 GEN
Solar/Wind Harmer
0.263
3145513AHOSKIE
Solar/Wind Harmer
-0.035
3145683EARLEYS
Solar/Wind Harmer
-0.069
3145683EARLEYS
Solar/Wind Harmer
-0.035
3145683EARLEYS
Solar/Wind Harmer
-0.035
3146043SEABORD
Solar/Wind Harmer
-0.034
315607AA1-063A GEN
Solar/Wind Harmer
3.475
970085AG2-068 GEN
Solar/Wind Harmer
21.415
970581AG2-369 GEN
Solar/Wind Harmer
18.417
946281AF1-292 GEN
Solar/Wind Harmer
0.762
316087AB2-174 GEN
Solar/Wind Harmer
4.83
315652AC1-086 GEN
Solar/Wind Harmer
38.044
3137643SOCKMAN
Solar/Wind Harmer
-0.134
3145796HORNRTN
Solar/Wind Harmer
-0.106
3145796HORNRTN
Solar/Wind Harmer
-0.013
3146033SCOT NK
Solar/Wind Harmer
-0.133
316005AA1-067
Solar/Wind Harmer
0.65
3145746EVERETS
Solar/Wind Harmer
-0.127
3145746EVERETS
Solar/Wind Harmer
-0.032
3145746EVERETS
Solar/Wind Harmer
-0.032
3145746EVERETS
Solar/Wind Harmer
-0.032
970181AG2-120 GEN
Solar/Wind Harmer
4.22
970831AG2-522 GEN
Solar/Wind Harmer
15.842
957861AF2-080 GEN
Solar/Wind Harmer
13.805
316420AA1-050 GEN
Solar/Wind Harmer
3.571
3141813NORNECK
Solar/Wind Harmer
-0.031
972189AH1-679 GEN
Adder
4.354
972205AH1-687 GEN
Adder
8.979
3151881LOWMORC
Adder
1.603
3151881LOWMORC
Adder
1.578
3151861LOWMORA
Adder
1.553
316164AC1-076 GEN
Solar/Wind Helper
1.831
316411AF1-147_GEN1
Solar/Wind Helper
1.081
316415AF1-147_GEN2
Solar/Wind Helper
1.081
3138216PACIFIC
Solar/Wind Helper
0.053
3141426STAFORD
Solar/Wind Helper
0.061
237085AD2-009_GEN
Solar/Wind Helper
1.39
960921AF2-383 GEN
Solar/Wind Helper
0.176
233935AB2-179 C
Solar/Wind Helper
1.231
205943AE1-185 GEN
Solar/Wind Helper
0.492
232436AB1-176 C
Solar/Wind Helper
0.043
205932AD2-116_GEN
Solar/Wind Helper
0.492
205956AE1-196_GEN
Solar/Wind Helper
0.492
233923SMA
Solar/Wind Helper
0.928
233990AG1-397 GEN
Solar/Wind Helper
0.029
234033AF1-007_GEN
Solar/Wind Helper
6.8
232432Z2-076 GEN
Solar/Wind Helper
0.065
964001AG1-254 GEN
Solar/Wind Helper
0.919
238208AF1-136 C
Solar/Wind Helper
0.173
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.025
219914AD2-027 C
Solar/Wind Helper
0.11
219272CLEANLIGHT C
Solar/Wind Helper
0.024
219688LUMSOLAR_S C
Solar/Wind Helper
0.038
219607WPEMNERT C
Solar/Wind Helper
0.077
971645AH1-323 GEN
50/50
34.83
3151161SURRY 1
50/50
14.063
3142416OLDCHRC
Solar/Wind Harmer
4.408
970293AG2-193 GEN
Solar/Wind Harmer
5.386
3142946ENON
Solar/Wind Harmer
-0.014
316382AG1-145 C
Solar/Wind Harmer
1.281
3143096IRON208
Adder
1.57
3143096IRON208
Adder
1.538
3150921YORKTN3
Adder
9.353
3144216WINCHST
Adder
1.401
315773AC2-141 GEN
Solar/Wind Harmer
17.422
970133AG2-095 GEN
Solar/Wind Harmer
4.665
970129AG2-093 GEN
Solar/Wind Harmer
23.298
315778AD1-151 GEN
Solar/Wind Harmer
35.792
961611AG1-000B GEN
Solar/Wind Harmer
8.673
3151221GRAVEL6
Adder
26.617
3151171GRAVELC
Adder
5.121
3150861SPRUNCD
Adder
1.682
3145336SMITFLD
Solar/Wind Harmer
-0.016
3144536CHRHLND
Solar/Wind Harmer
-0.006
944581AF1-123 GEN
Solar/Wind Harmer
185.642
944601AF1-125 GEN
Solar/Wind Harmer
182.744
3151101ELIZAR3
Adder
33.701
3144873MCLAUGH
Solar/Wind Harmer
-0.001
965281AG1-393 GEN
Solar/Wind Harmer
5.061
315839AE2-212 C
Solar/Wind Harmer
1.217
3142433PROV 92
Adder
0.696
3142433PROV 92
Adder
0.696
3146456SLIGO L269
Solar/Wind Harmer
-0.04
971153AH1-033 GEN
Solar/Wind Harmer
4.905
316473AC1-191 GEN
Solar/Wind Harmer
4.326
315813AE1-149 C
Solar/Wind Harmer
25.043
970659AG2-427 GEN
Solar/Wind Harmer
3.766
316083AB2-161 GEN
Solar/Wind Harmer
6.49
970661AG2-428 GEN
Solar/Wind Harmer
7.523
316320Y1-086
Solar/Wind Harmer
2.331
316435W1029_GEN3
Solar/Wind Harmer
7.121
3141766HARMONY
Solar/Wind Harmer
3.49
3146516WINFALL
Solar/Wind Harmer
-0.039
3141843SHACKLE
Adder
1.777
316203AE2-005 GEN
Solar/Wind Harmer
16.469
3146626S HERTFORD
Solar/Wind Harmer
-0.039
316280AD1-041 GEN
Solar/Wind Harmer
2.926
3145273HOLLAND
Solar/Wind Harmer
-0.029
316156AD2-030 GEN
Solar/Wind Harmer
1.029
3141873WAN 176
Solar/Wind Harmer
4.571
3146376EDENTON
Solar/Wind Harmer
-0.038
315614AA2-178 GEN
Solar/Wind Harmer
4.002
971157AH1-035 GEN
Solar/Wind Harmer
4.549
315737AD1-076 GEN
Solar/Wind Harmer
6.891
972255AH1-712 GEN
Adder
164.848
3156081AA2-088 GEN
Solar/Wind Harmer
11.679
3146206CASHIE
Solar/Wind Harmer
-0.036
3145893MURPHYS
Solar/Wind Harmer
0.248
3145893MURPHYS
Solar/Wind Harmer
-0.035
957521AF2-046 GEN
Solar/Wind Harmer
27.872
961681AG1-008 GEN
Solar/Wind Harmer
27.872
962971AG1-146 GEN
Solar/Wind Harmer
6.6
3156021HOLLOMANSOL
Solar/Wind Harmer
4.742
3146173TUNIS
Solar/Wind Harmer
-0.035
316365GEN2_N
Solar/Wind Harmer
2.36
316463AE2-346 GEN
Solar/Wind Harmer
0.566
316140AB2-099
Solar/Wind Harmer
0.236
962331AG1-082 GEN
Solar/Wind Harmer
4.374
3146263WOODLND
Solar/Wind Harmer
-0.034
3145963POPLR C
Solar/Wind Harmer
-0.034
316484AD2-074 GEN
Solar/Wind Harmer
8.672
970009AG2-005 GEN
Solar/Wind Harmer
4.306
970917AG2-570 GEN
Solar/Wind Harmer
85.968
316317KELFORD C
Solar/Wind Harmer
1.606
3145823KELFORD
Solar/Wind Harmer
-0.034
966621AG1-532 GEN
Solar/Wind Harmer
0.691
3142666NORTHAMPTON
Solar/Wind Harmer
-0.034
313506AB2-031 GEN
Solar/Wind Harmer
2.715
3145796HORNRTN
Solar/Wind Harmer
-0.133
3145796HORNRTN
Solar/Wind Harmer
-0.033
316404AE1-155 C
Solar/Wind Harmer
6.411
3145933PARMELE
Solar/Wind Harmer
-0.033
966801AG1-551 GEN
Solar/Wind Harmer
4.109
3147043LAWRENC
Solar/Wind Harmer
-0.019
316210AC1-098 GEN
Solar/Wind Harmer
5.131
316313AB2-026
Solar/Wind Harmer
0.88
316258AE1-075 C
Solar/Wind Harmer
0.792
316405AF2-144 C
Solar/Wind Harmer
0.836
3143336POWHATN
Solar/Wind Harmer
3.29
3145746EVERETS
Solar/Wind Harmer
-0.032
3145746EVERETS
Solar/Wind Harmer
-0.032
315724AD1-057 GEN
Solar/Wind Harmer
1.824
316478AD1-087 GEN
Solar/Wind Harmer
2.743
316486AD2-202 GEN
Solar/Wind Harmer
0.803
316327AA2-057 GEN
Solar/Wind Harmer
3.182
3150351NORNECKC2
Adder
2.802
3144293JTRSVLE
Adder
0.817
3151861LOWMORA
Adder
1.616
316044AC1-158 PL1
Solar/Wind Helper
2.514
316450AC1-158 RIC
Solar/Wind Helper
0.67
3141196NOKESVL
Solar/Wind Helper
1.391
316170AC1-121 GEN2
Solar/Wind Helper
0.513
227287AC2-120 GEN
Solar/Wind Helper
0.433
226910AB2-157 C
Solar/Wind Helper
0.018
3147666LOUISA
Solar/Wind Helper
0.666
223402AF1-300 C
Solar/Wind Helper
0.394
237030AB1-096 C
Solar/Wind Helper
0.069
3132273ORANGE
Solar/Wind Helper
0.05
238221AF1-254 C O1
Solar/Wind Helper
0.238
235067AD1-061 GEN
Solar/Wind Helper
0.424
205917AD1-020 ES
Solar/Wind Helper
0.354
233982AB2-133 GEN
Solar/Wind Helper
0.347
233918AB1-142 GEN
Solar/Wind Helper
0.487
233994AC2-023 GEN
Solar/Wind Helper
0.931
233996TM1833_GEN
Solar/Wind Helper
0.253
233997TMININ_4.2
Solar/Wind Helper
0.253
232406W1-004 FULL
Solar/Wind Helper
0.491
233940AF2-379 C
Solar/Wind Helper
0.06
234015AF2-250 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.225
233971AC1-093 C
Solar/Wind Helper
0.346
230430AE1-229_GEN
Solar/Wind Helper
3.244
230415AB2-049 C
Solar/Wind Helper
0.029
228729W2-030 C
Solar/Wind Helper
0.106
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.052
219912AD2-042 GEN
Solar/Wind Helper
0.144
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.11
3146626S HERTFORD
Solar/Wind Harmer
-0.039
971223AH1-071 GEN
Solar/Wind Harmer
4.826
315742AE1-103 GEN
Solar/Wind Harmer
3.978
3146376EDENTON
Solar/Wind Harmer
1.128
3146376EDENTON
Solar/Wind Harmer
1.128
3144356SAPONY
Solar/Wind Harmer
1.305
316065AD1-022 GEN
Solar/Wind Harmer
17.989
972185AH1-677 GEN
Adder
17.917
972187AH1-678 GEN
Adder
8.997
3145893MURPHYS
Solar/Wind Harmer
0.99
3145893MURPHYS
Solar/Wind Harmer
-0.064
3146173TUNIS
Solar/Wind Harmer
-0.035
3146173TUNIS
Solar/Wind Harmer
-0.035
970933AG2-581 GEN
Solar/Wind Harmer
32.706
316487AF1-042 GEN
Solar/Wind Harmer
4.538
3142666NORTHAMPTON
Solar/Wind Harmer
-0.034
3142666NORTHAMPTON
Solar/Wind Harmer
-0.034
3142666NORTHAMPTON
Solar/Wind Harmer
-0.034
3142666NORTHAMPTON
Solar/Wind Harmer
-0.02
316181AB2-040 GEN
Solar/Wind Harmer
4.712
316426AA2-053 GEN
Solar/Wind Harmer
3.407
3145593CAROLNA
Solar/Wind Harmer
-0.033
3145593CAROLNA
Solar/Wind Harmer
-0.033
966811AG1-552 GEN
Solar/Wind Harmer
3.768
3145593CAROLNA
Solar/Wind Harmer
0.278
3145796HORNRTN
Solar/Wind Harmer
-0.099
3145783HORNRTN
Solar/Wind Harmer
3.954
3145783HORNRTN
Solar/Wind Harmer
3.163
3145783HORNRTN
Solar/Wind Harmer
0.988
3145783HORNRTN
Solar/Wind Harmer
0.395
958261AF2-120 GEN
Solar/Wind Harmer
12.878
3145933PARMELE
Solar/Wind Harmer
-0.065
3145933PARMELE
Solar/Wind Harmer
-0.033
970099AG2-077 GEN
Solar/Wind Harmer
40.962
316274AC1-208 GEN
Solar/Wind Harmer
3.495
316077AC2-138 C
Solar/Wind Harmer
0.655
3150341NORNECKC1
Adder
2.894
3150341NORNECKC1
Adder
2.871
3144293JTRSVLE
Adder
0.817
3144293JTRSVLE
Adder
0.688
316447AC1-158 HLD
Solar/Wind Helper
5.533
315651AD1-115 GEN
Solar/Wind Helper
1.131
226929AD2-058 GEN
Solar/Wind Helper
0.127
23777801MSM_W1-116
Solar/Wind Helper
0.11
237025AB1-124 C
Solar/Wind Helper
0.16
237006AB1-125 GEN
Solar/Wind Helper
0.12
237034AC2-136 C
Solar/Wind Helper
0.207
23777901MDS_W4-102
Solar/Wind Helper
0.152
235020AA1-095 C
Solar/Wind Helper
0.045
237001AB1-127_GEN
Solar/Wind Helper
0.385
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
237002AB1-128_GEN
Solar/Wind Helper
0.384
235063AE1-101 C2
Solar/Wind Helper
1.425
205916AD1-020 GEN
Solar/Wind Helper
1.648
233933AB2-153 GEN
Solar/Wind Helper
0.225
233944AB2-135 GEN
Solar/Wind Helper
0.57
232424Y1-079 C
Solar/Wind Helper
0.113
233987AB2-037 GEN
Solar/Wind Helper
2.269
233946AB2-136 GEN
Solar/Wind Helper
0.55
234036AF2-325 C
Solar/Wind Helper
0.041
233901CHERRYDALE C
Solar/Wind Helper
0.225
232408W1-005 C
Solar/Wind Helper
0.491
232410W1-006 C
Solar/Wind Helper
0.491
233939AC1-091 C
Solar/Wind Helper
0.339
233970AC1-092 C
Solar/Wind Helper
0.339
238175AF1-290_GEN
Solar/Wind Helper
0.118
230433AD2-135 GEN
Solar/Wind Helper
0.016
230407AD2-065 C
Solar/Wind Helper
0.039
219921AF1-264
Solar/Wind Helper
0.049
219615MILLCREEK C
Solar/Wind Helper
0.025
3152331SURRY 2
50/50
15.855
3142416OLDCHRC
Solar/Wind Harmer
-0.113
3142416OLDCHRC
Solar/Wind Harmer
-0.043
316159AE1-175 C
Solar/Wind Harmer
1.141
944631AF1-128 GEN
Adder
179.449
3143096IRON208
Adder
1.57
3138126ROCKLANDING
Solar/Wind Harmer
0.128
971317AH1-138 GEN
Solar/Wind Harmer
5.215
316294AC1-161 GEN
Solar/Wind Harmer
13.471
3142543TWELFTH
Solar/Wind Harmer
-0.004
970129AG2-093 GEN
Solar/Wind Harmer
9.437
316458AB2-190 GEN2
Solar/Wind Harmer
4.185
971069AG2-661 GEN
Solar/Wind Harmer
6.537
971647AH1-324 GEN
Solar/Wind Harmer
20.617
961611AG1-000B GEN
Solar/Wind Harmer
20.327
3151171GRAVELC
Adder
3.894
3150851SPRUNCC
Adder
1.682
3145336SMITFLD
Solar/Wind Harmer
-0.163
944591AF1-124 GEN
Solar/Wind Harmer
186.31
316375AC2-012 GEN
Solar/Wind Harmer
14.108
3150981CHESPKA
Adder
4.53
315671AE2-027_GEN
Solar/Wind Harmer
30.454
316072AD1-144
Solar/Wind Harmer
0.817
316388AE2-253 GEN
Solar/Wind Harmer
2.723
3142433PROV 92
Solar/Wind Harmer
-0.16
3142433PROV 92
Adder
0.696
3142433PROV 92
Adder
0.696
3146456SLIGO L269
Solar/Wind Harmer
-0.04
316246AF1-032 C
Solar/Wind Harmer
0.811
970659AG2-427 GEN
Solar/Wind Harmer
21.251
316381AD1-082 GEN
Solar/Wind Harmer
3.667
970661AG2-428 GEN
Solar/Wind Harmer
42.449
3143526WINTERP
Solar/Wind Harmer
-0.206
316093AE2-104_GEN
Solar/Wind Harmer
11.566
3141766HARMONY
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.126
3146516WINFALL
Solar/Wind Harmer
-0.039
939411AE1-173 GEN
Solar/Wind Harmer
195.386
971777AH1-397 GEN
Solar/Wind Harmer
4.594
3141843SHACKLE
Adder
1.777
3143226MDLTHAN
Solar/Wind Harmer
-0.038
940641AE2-051 GEN
Solar/Wind Harmer
36.152
315800Z1-036_GEN1
Solar/Wind Harmer
9.52
3130156CHOWAN
Solar/Wind Harmer
-0.038
3138133OCRAN
Solar/Wind Harmer
-0.022
3145663CRESWEL
Solar/Wind Harmer
-0.103
971163AH1-040 GEN
Solar/Wind Harmer
34.777
972277AH1-723 GEN
Adder
192.098
3146206CASHIE
Solar/Wind Harmer
-0.036
971547AH1-271 GEN
Solar/Wind Harmer
8.955
3145893MURPHYS
Solar/Wind Harmer
-0.141
3145893MURPHYS
Solar/Wind Harmer
1.053
3146173TUNIS
Solar/Wind Harmer
-0.035
316023GEN1_S
Solar/Wind Harmer
2.36
3145683EARLEYS
Solar/Wind Harmer
-0.035
3146263WOODLND
Solar/Wind Harmer
-0.034
3145963POPLR C
Solar/Wind Harmer
-0.034
961951AG1-038 GEN
Solar/Wind Harmer
4.538
970919AG2-571 GEN
Solar/Wind Harmer
10.882
970087AG2-069 GEN
Solar/Wind Harmer
32.123
316174AB2-169 GEN
Solar/Wind Harmer
5.263
3145823KELFORD
Solar/Wind Harmer
-0.034
960081AF2-299 GEN
Solar/Wind Harmer
3.829
316011AB1-132 GEN
Solar/Wind Harmer
7.075
962571AG1-106 GEN
Solar/Wind Harmer
4.861
316190AA2-174 GEN
Solar/Wind Harmer
0.414
962861AG1-135 GEN
Solar/Wind Harmer
12.583
3145796HORNRTN
Solar/Wind Harmer
-0.109
3145796HORNRTN
Solar/Wind Harmer
-0.033
3145783HORNRTN
Solar/Wind Harmer
-0.033
971795AH1-408 GEN
Solar/Wind Harmer
24.879
3146293MARTNCO
Solar/Wind Harmer
0.204
3147043LAWRENC
Adder
2.639
957481AF2-042 GEN
Solar/Wind Harmer
102.404
316212AC1-099_GEN
Solar/Wind Harmer
2.851
3143336POWHATN
Solar/Wind Harmer
3.871
964211AG1-282 GEN
Solar/Wind Harmer
0.968
3141726DUNNSVL
Solar/Wind Harmer
-0.128
3145746EVERETS
Solar/Wind Harmer
-0.032
3145746EVERETS
Solar/Wind Harmer
-0.032
315693AD1-088 GEN
Solar/Wind Harmer
16.002
962491AG1-098 GEN
Solar/Wind Harmer
21.316
315722AD1-056 GEN
Solar/Wind Harmer
3.316
316494AC1-189 GEN
Solar/Wind Harmer
3.395
316129AC1-054 GEN
Solar/Wind Harmer
2.761
971065AG2-659 GEN
Solar/Wind Harmer
15.657
3150351NORNECKC2
Adder
2.755
3144293JTRSVLE
Adder
0.817
316045AC1-158 PL2
Solar/Wind Helper
8.047
316006AB2-029 C
Solar/Wind Helper
0.164
316254AC1-120 GEN1
Solar/Wind Helper
1.539
3147666LOUISA
Solar/Wind Helper
1.159
316192AB2-158 GEN
Solar/Wind Helper
1.901
223401AF1-299 GEN
Solar/Wind Helper
0.394
23779801AA1-109
Solar/Wind Helper
0.185
237080AD1-060 GEN
Solar/Wind Helper
0.295
237038AE2-054 C
Solar/Wind Helper
0.234
235062AE1-101 C1
Solar/Wind Helper
1.425
966131AG1-482 GEN
Solar/Wind Helper
0.075
233930AB2-032 GEN
Solar/Wind Helper
0.369
233915AB1-141 GEN
Solar/Wind Helper
0.487
232422X3-066 FULL
Solar/Wind Helper
0.111
232426Y1-080 FULL
Solar/Wind Helper
0.038
233964AF2-378 GEN
Solar/Wind Helper
0.04
233998TM1NIN_3.36
Solar/Wind Helper
0.253
232404W1-003 C
Solar/Wind Helper
0.491
232428Y3-058 C
Solar/Wind Helper
0.328
233954AC2-188 GEN
Solar/Wind Helper
0.225
233950AC2-186 GEN
Solar/Wind Helper
0.113
232434Z2-077 GEN
Solar/Wind Helper
0.123
233972AC1-094 C
Solar/Wind Helper
0.293
230511AF1-262
Solar/Wind Helper
0.014
230434AG1-499 GEN
Solar/Wind Helper
0.221
228728W1-130C
Solar/Wind Helper
0.052
219258KINSLEYDEP C
Solar/Wind Helper
0.074
219904AC1-010 C
Solar/Wind Helper
0.058
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219907AC1-030 C
Solar/Wind Helper
0.032
219686LUMSOLAR_N C
Solar/Wind Helper
0.038
219304NAMERICA C
Solar/Wind Helper
0.126
316336AC2-165 C
Solar/Wind Harmer
4.115
NYPJM->LTFIMP_NY
CLTF
4.642
LGEELTFEXP_LGEE->PJM
CLTF
3.02
WECLTFEXP_WEC->PJM
CLTF
1.528
AG2-052LTFEXP_AG2-052->PJM
LTF
0.084
AH1-155LTFEXP_AH1-155->PJM
LTF
0.126
LAGNLTFEXP_LAGN->PJM
CLTF
14.648
CBM South 2LTFEXP_CBM-S2->PJM
CBM
40.037
TVALTFEXP_TVA->PJM
CLTF
7.415
CBM West 1LTFEXP_CBM-W1->PJM
CBM
53.689
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.805
MECLTFEXP_MEC->PJM
CLTF
7.852
SIGELTFEXP_SIGE->PJM
CLTF
0.243
CPLELTFEXP_CPLE->PJM
CLTF
17.726
CBM West 2LTFEXP_CBM-W2->PJM
CBM
80.521

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.98 %
Rating:4070.2 MVA
Rating Type:A
MVA to Mitigate:4842.75
MW Contribution:196.77
Bus #Bus NameTypeMW Contribution
3152181CUNINGC
50/50
2.565
972193AH1-681 GEN
50/50
7.545
316312AB1-027
Solar/Wind Harmer
0.575
315976AC1-164 GENA
Solar/Wind Harmer
32.144
316169AC1-164_GENC
Solar/Wind Harmer
27.769
315975AC1-164 GENB
Solar/Wind Harmer
0.951
316314AB2-024 C
Solar/Wind Harmer
0.001
971167AH1-042 GEN
Solar/Wind Harmer
24.413
3142433PROV 92
Adder
0.534
3142433PROV 92
Adder
0.534
3143873LANEXA
Solar/Wind Harmer
0.165
316059AD1-063 C
Solar/Wind Harmer
0.002
3138283WHITEMARSH
Solar/Wind Harmer
0.062
970189AG2-124 GEN
Solar/Wind Harmer
7.953
315662AE1-191 GEN
Solar/Wind Harmer
0.009
315666AE1-190 GEN
Solar/Wind Harmer
0.002
316132AB2-190 GEN1
Solar/Wind Harmer
1.424
3141873WAN 176
Solar/Wind Harmer
0.053
316369SG1_INVT
Solar/Wind Harmer
0.01
972265AH1-717 GEN
Adder
20.019
3151201GRAVEL4
Adder
18.766
971645AH1-323 GEN
50/50
29.668
3152191CUNINGD
50/50
5.586
3152171CUNINGB
50/50
2.411
972255AH1-712 GEN
50/50
168.86
3142416OLDCHRC
Solar/Wind Harmer
3.115
970293AG2-193 GEN
Solar/Wind Harmer
3.254
316473AC1-191 GEN
Solar/Wind Harmer
1.006
3142946ENON
Solar/Wind Harmer
0.098
316382AG1-145 C
Solar/Wind Harmer
0.002
3143096IRON208
Adder
1.181
3143096IRON208
Adder
1.157
3142433PROV 92
Adder
0.534
3142433PROV 92
Adder
0.534
3150921YORKTN3
Adder
6.858
3144216WINCHST
Adder
1.022
3141766HARMONY
Solar/Wind Harmer
3.615
3141843SHACKLE
Adder
1.372
970133AG2-095 GEN
Solar/Wind Harmer
2.576
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316280AD1-041 GEN
Solar/Wind Harmer
0.005
970129AG2-093 GEN
Solar/Wind Harmer
16.057
316156AD2-030 GEN
Solar/Wind Harmer
0.195
3141873WAN 176
Solar/Wind Harmer
4.689
315778AD1-151 GEN
Solar/Wind Harmer
21.096
961611AG1-000B GEN
Solar/Wind Harmer
6.924
3151221GRAVEL6
Adder
18.744
3151171GRAVELC
Adder
3.606
3150861SPRUNCD
Adder
1.168
3145336SMITFLD
Solar/Wind Harmer
0.101
315773AC2-141 GEN
Solar/Wind Harmer
9.204
965281AG1-393 GEN
Solar/Wind Harmer
2.675
3144536CHRHLND
Solar/Wind Harmer
0.037
315839AE2-212 C
Solar/Wind Harmer
0.002
3151101ELIZAR3
Adder
22.773
3144873MCLAUGH
Solar/Wind Harmer
0.006
944581AF1-123 GEN
Solar/Wind Harmer
54.983
944601AF1-125 GEN
Solar/Wind Harmer
54.137
962971AG1-146 GEN
Solar/Wind Harmer
3.875
315813AE1-149 C
Solar/Wind Harmer
12.831
3146456SLIGO L269
Solar/Wind Harmer
0.24
971153AH1-033 GEN
Solar/Wind Harmer
2.78
970659AG2-427 GEN
Solar/Wind Harmer
2.536
316083AB2-161 GEN
Solar/Wind Harmer
0.003
970661AG2-428 GEN
Solar/Wind Harmer
5.061
970009AG2-005 GEN
Solar/Wind Harmer
1.772
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.232
3146626S HERTFORD
Solar/Wind Harmer
0.23
316404AE1-155 C
Solar/Wind Harmer
0.052
3145273HOLLAND
Solar/Wind Harmer
0.171
3146376EDENTON
Solar/Wind Harmer
0.224
315614AA2-178 GEN
Solar/Wind Harmer
1.24
3150351NORNECKC2
Adder
2.183
971157AH1-035 GEN
Solar/Wind Harmer
2.537
315737AD1-076 GEN
Solar/Wind Harmer
2.707
971781AH1-399 GEN
Solar/Wind Harmer
0.275
3146206CASHIE
Solar/Wind Harmer
0.207
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
3145893MURPHYS
Solar/Wind Harmer
0.34
3145893MURPHYS
Solar/Wind Harmer
0.203
957521AF2-046 GEN
Solar/Wind Harmer
15.055
961681AG1-008 GEN
Solar/Wind Harmer
15.055
3156021HOLLOMANSOL
Solar/Wind Harmer
0.916
3146173TUNIS
Solar/Wind Harmer
0.201
316463AE2-346 GEN
Solar/Wind Harmer
0.171
316140AB2-099
Solar/Wind Harmer
0.071
962331AG1-082 GEN
Solar/Wind Harmer
2.13
3145963POPLR C
Solar/Wind Harmer
0.197
3146263WOODLND
Solar/Wind Harmer
0.195
316317KELFORD C
Solar/Wind Harmer
0.019
3145823KELFORD
Solar/Wind Harmer
0.193
316365GEN2_N
Solar/Wind Harmer
0.432
3142666NORTHAMPTON
Solar/Wind Harmer
0.189
3145933PARMELE
Solar/Wind Harmer
0.186
966801AG1-551 GEN
Solar/Wind Harmer
2.17
313506AB2-031 GEN
Solar/Wind Harmer
0.575
3145796HORNRTN
Solar/Wind Harmer
0.739
3145796HORNRTN
Solar/Wind Harmer
0.185
316210AC1-098 GEN
Solar/Wind Harmer
1.695
3145746EVERETS
Solar/Wind Harmer
0.181
3145746EVERETS
Solar/Wind Harmer
0.181
3147043LAWRENC
Solar/Wind Harmer
0.107
315724AD1-057 GEN
Solar/Wind Harmer
0.658
316327AA2-057 GEN
Solar/Wind Harmer
0.264
3146073TAR RVR
Solar/Wind Harmer
0.172
3146083TARBORO
Solar/Wind Harmer
0.172
3146233WITAKRS
Solar/Wind Harmer
0.859
3146233WITAKRS
Solar/Wind Harmer
0.116
3138543CONSLDL
Solar/Wind Harmer
0.113
961601AG1-000A GEN
Solar/Wind Harmer
11.93
3145543BTLEBRO
Solar/Wind Harmer
0.167
3145543BTLEBRO
Solar/Wind Harmer
0.167
971623AH1-311 GEN
Solar/Wind Harmer
0.335
970917AG2-570 GEN
Solar/Wind Harmer
14.887
316313AB2-026
Solar/Wind Harmer
0.103
316258AE1-075 C
Solar/Wind Harmer
0.123
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
2.467
3141906WESTMOR
Solar/Wind Harmer
0.065
316478AD1-087 GEN
Solar/Wind Harmer
0.557
316486AD2-202 GEN
Solar/Wind Harmer
0.164
316131AB2-060 GEN
Solar/Wind Harmer
0.497
964241AG1-285 GEN
Solar/Wind Harmer
10.495
315785AD2-033 C
Solar/Wind Harmer
1.27
970257AG2-171 GEN
Solar/Wind Harmer
4.984
959311AF2-222 GEN
Solar/Wind Harmer
13.814
970909AG2-566 GEN
Solar/Wind Harmer
1.639
963181AG1-167 GEN
Solar/Wind Harmer
0.614
3144293JTRSVLE
Adder
0.489
3147133PAMPLIN
Solar/Wind Harmer
0.479
971193AH1-056 GEN
Solar/Wind Harmer
9.299
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.089
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
6.236
3146776BUCKING
Solar/Wind Harmer
0.051
3148013FISHERV
Solar/Wind Harmer
0.14
971683AH1-343 GEN
Solar/Wind Harmer
5.137
315616AA1-038_C
Solar/Wind Harmer
0.001
3151861LOWMORA
Adder
1.496
970737AG2-469 GEN
Solar/Wind Harmer
5.853
316283AC2-100 C
Solar/Wind Harmer
0.266
970221AG2-151 GEN
Solar/Wind Harmer
7.112
316044AC1-158 PL1
Solar/Wind Helper
1.64
316450AC1-158 RIC
Solar/Wind Helper
0.438
3141196NOKESVL
Solar/Wind Helper
1.029
227287AC2-120 GEN
Solar/Wind Helper
0.327
226910AB2-157 C
Solar/Wind Helper
0.013
316170AC1-121 GEN2
Solar/Wind Helper
0.36
3151191GRAVEL3
Adder
18.528
3151211GRAVEL5
Adder
18.528
3141913WHIT STONE
Solar/Wind Harmer
0.256
3138133OCRAN
Solar/Wind Harmer
0.076
971445AH1-216 GEN
Solar/Wind Harmer
17.851
971285AH1-108 GEN
Adder
1.911
3141783LANCAST
Solar/Wind Harmer
0.15
3141783LANCAST
Solar/Wind Harmer
0.1
3151081ELIZAR1
Adder
22.486
3151091ELIZAR2
Adder
22.095
3152611GOSPORTB
Adder
3.124
3152621GOSPORTC
Adder
2.651
3152601GOSPORTA
Adder
2.446
962981AG1-147 GEN
Solar/Wind Harmer
9.042
957871AF2-081 GEN
Solar/Wind Harmer
12.005
319010AE1-072 C
Solar/Wind Harmer
1.21
3146406KITTY HAWK
Solar/Wind Harmer
0.03
316305AF2-043 C
Solar/Wind Harmer
0.002
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.163
316311AC2-079 GEN
Solar/Wind Harmer
6.837
970327AG2-215 GEN
Solar/Wind Harmer
7.789
315835AF2-110_GEN
Solar/Wind Harmer
1.628
313526AB2-022
Solar/Wind Harmer
0.128
3146486SUNBURY
Solar/Wind Harmer
0.236
3146486SUNBURY
Solar/Wind Harmer
0.236
316321Z2-027
Solar/Wind Harmer
0.044
3146396TANGLEW
Solar/Wind Harmer
0.649
3145176PASQUOTANK
Solar/Wind Harmer
0.146
3143316POE
Solar/Wind Harmer
0.911
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.224
3130156CHOWAN
Solar/Wind Harmer
0.224
972189AH1-679 GEN
Adder
3.73
315816AE2-034 GEN
Solar/Wind Harmer
0.93
316233AE1-074 FULL
Solar/Wind Harmer
0.173
971281AH1-106 GEN
Solar/Wind Harmer
3.003
971283AH1-107 GEN
Solar/Wind Harmer
3.003
3141813NORNECK
Solar/Wind Harmer
0.215
3130546PLYMOUTH
Solar/Wind Harmer
0.211
315732AD1-074 GEN1
Solar/Wind Harmer
1.209
315733AD1-074 GEN2
Solar/Wind Harmer
1.209
315735AD1-075 GEN1
Solar/Wind Harmer
0.605
3146206CASHIE
Solar/Wind Harmer
0.207
970601AG2-382 GEN
Solar/Wind Harmer
7.721
965291AG1-394 GEN
Solar/Wind Harmer
0.911
3145893MURPHYS
Solar/Wind Harmer
0.548
3145893MURPHYS
Solar/Wind Harmer
0.203
316315AB2-025 C
Solar/Wind Harmer
0.164
315814AE2-033 C
Solar/Wind Harmer
16.008
3145513AHOSKIE
Solar/Wind Harmer
0.417
3145513AHOSKIE
Solar/Wind Harmer
0.199
3145683EARLEYS
Solar/Wind Harmer
0.397
3145683EARLEYS
Solar/Wind Harmer
0.198
3145683EARLEYS
Solar/Wind Harmer
0.198
3146043SEABORD
Solar/Wind Harmer
0.194
315607AA1-063A GEN
Solar/Wind Harmer
0.395
315652AC1-086 GEN
Solar/Wind Harmer
20.636
3146033SCOT NK
Solar/Wind Harmer
0.749
316087AB2-174 GEN
Solar/Wind Harmer
0.005
3137643SOCKMAN
Solar/Wind Harmer
0.742
3145796HORNRTN
Solar/Wind Harmer
0.591
3145796HORNRTN
Solar/Wind Harmer
0.074
316005AA1-067
Solar/Wind Harmer
0.194
3145746EVERETS
Solar/Wind Harmer
0.72
3145746EVERETS
Solar/Wind Harmer
0.181
3145746EVERETS
Solar/Wind Harmer
0.181
3145746EVERETS
Solar/Wind Harmer
0.181
970181AG2-120 GEN
Solar/Wind Harmer
2.254
957861AF2-080 GEN
Solar/Wind Harmer
7.61
941031AE2-094 GEN
Solar/Wind Harmer
32.353
944011AF1-069 GEN
Solar/Wind Harmer
10.571
316420AA1-050 GEN
Solar/Wind Harmer
0.006
970673AG2-436 GEN
Solar/Wind Harmer
37.059
970673AG2-436 GEN
Solar/Wind Harmer
24.706
3145573BETHELC
Solar/Wind Harmer
0.172
3145573BETHELC
Solar/Wind Harmer
0.172
971967AH1-528 GEN
Solar/Wind Harmer
27.582
970831AG2-522 GEN
Solar/Wind Harmer
7.305
316319Z2-044 C
Solar/Wind Harmer
0
970085AG2-068 GEN
Solar/Wind Harmer
8.909
970581AG2-369 GEN
Solar/Wind Harmer
7.662
316223AC1-118
Solar/Wind Harmer
0.117
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
971443AH1-215 GEN
Solar/Wind Harmer
2.618
3144303KENBRDG
Solar/Wind Harmer
0.124
970683AG2-441 GEN
Solar/Wind Harmer
10.305
970681AG2-440 GEN
Solar/Wind Harmer
8.244
946301AF1-294 GEN
Solar/Wind Harmer
3.029
961791AG1-021 GEN
Solar/Wind Harmer
1.473
315657AE1-056 GEN
Solar/Wind Harmer
5.267
316118AC1-105 GEN
Solar/Wind Harmer
0.384
3147173SINAI
Solar/Wind Harmer
0.146
3147243WELCO
Solar/Wind Harmer
0.091
970285AG2-188 GEN
Solar/Wind Harmer
11.379
971845AH1-439 GEN
Solar/Wind Harmer
6.479
3148133STUARTS
Solar/Wind Harmer
0.084
3148013FISHERV
Solar/Wind Harmer
0.081
3148463FAIRFLD
Solar/Wind Harmer
0.139
3151881LOWMORC
Adder
1.484
3151881LOWMORC
Adder
1.461
3151861LOWMORA
Adder
1.437
970865AG2-541 GEN
Solar/Wind Harmer
4.73
972205AH1-687 GEN
Adder
5.79
971447AH1-217 GEN
Solar/Wind Harmer
4.07
316123AC1-075 GEN
Solar/Wind Harmer
0.178
970165AG2-112 GEN
Solar/Wind Harmer
1.054
970163AG2-111 GEN
Solar/Wind Harmer
1.006
270494AE1-108_GEN
Solar/Wind Harmer
1.506
316164AC1-076 GEN
Solar/Wind Helper
1.291
316411AF1-147_GEN1
Solar/Wind Helper
0.798
316415AF1-147_GEN2
Solar/Wind Helper
0.798
3138216PACIFIC
Solar/Wind Helper
0.039
3152161CUNINGA
50/50
2.401
972277AH1-723 GEN
50/50
196.773
3142416OLDCHRC
Solar/Wind Harmer
0.835
3142416OLDCHRC
Solar/Wind Harmer
0.32
316159AE1-175 C
Solar/Wind Harmer
0.248
944631AF1-128 GEN
Adder
136.402
3143096IRON208
Adder
1.181
971317AH1-138 GEN
Solar/Wind Harmer
2.064
3142433PROV 92
Solar/Wind Harmer
1.099
3142433PROV 92
Adder
0.534
3142433PROV 92
Adder
0.534
3138126ROCKLANDING
Solar/Wind Harmer
0.125
3141766HARMONY
Solar/Wind Harmer
0.054
3142543TWELFTH
Solar/Wind Harmer
0.026
971777AH1-397 GEN
Solar/Wind Harmer
0.709
3141843SHACKLE
Adder
1.372
970129AG2-093 GEN
Solar/Wind Harmer
7.556
316458AB2-190 GEN2
Solar/Wind Harmer
1.424
971069AG2-661 GEN
Solar/Wind Harmer
4.688
971647AH1-324 GEN
Solar/Wind Harmer
11.14
961611AG1-000B GEN
Solar/Wind Harmer
13.616
3151171GRAVELC
Adder
2.743
3138133OCRAN
Solar/Wind Harmer
0.153
315671AE2-027_GEN
Solar/Wind Harmer
16.232
3150851SPRUNCC
Adder
1.168
3145336SMITFLD
Solar/Wind Harmer
1.012
316294AC1-161 GEN
Solar/Wind Harmer
4.367
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
3.063
316072AD1-144
Solar/Wind Harmer
0.089
944591AF1-124 GEN
Solar/Wind Harmer
55.179
316388AE2-253 GEN
Solar/Wind Harmer
0.757
3146456SLIGO L269
Solar/Wind Harmer
0.24
970659AG2-427 GEN
Solar/Wind Harmer
11.595
316246AF1-032 C
Solar/Wind Harmer
0.108
316381AD1-082 GEN
Solar/Wind Harmer
0.25
970661AG2-428 GEN
Solar/Wind Harmer
23.793
316093AE2-104_GEN
Solar/Wind Harmer
3.989
3146516WINFALL
Solar/Wind Harmer
0.754
3146516WINFALL
Solar/Wind Harmer
0.232
962861AG1-135 GEN
Solar/Wind Harmer
7.409
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
3141726DUNNSVL
Solar/Wind Harmer
0.895
3130156CHOWAN
Solar/Wind Harmer
0.224
3145663CRESWEL
Solar/Wind Harmer
0.606
971163AH1-040 GEN
Solar/Wind Harmer
17.339
3143526WINTERP
Solar/Wind Harmer
1.125
3150351NORNECKC2
Adder
2.147
3146206CASHIE
Solar/Wind Harmer
0.207
971547AH1-271 GEN
Solar/Wind Harmer
4.412
939411AE1-173 GEN
Solar/Wind Harmer
87.698
3145893MURPHYS
Solar/Wind Harmer
0.811
3145893MURPHYS
Solar/Wind Harmer
0.902
3146173TUNIS
Solar/Wind Harmer
0.201
3145683EARLEYS
Solar/Wind Harmer
0.198
3145963POPLR C
Solar/Wind Harmer
0.197
316174AB2-169 GEN
Solar/Wind Harmer
0.005
3146263WOODLND
Solar/Wind Harmer
0.195
3145823KELFORD
Solar/Wind Harmer
0.193
940641AE2-051 GEN
Solar/Wind Harmer
15.435
316023GEN1_S
Solar/Wind Harmer
0.432
316337AD2-073 GEN
Solar/Wind Harmer
0.166
316190AA2-174 GEN
Solar/Wind Harmer
0
316011AB1-132 GEN
Solar/Wind Harmer
3.411
962571AG1-106 GEN
Solar/Wind Harmer
2.669
960081AF2-299 GEN
Solar/Wind Harmer
1.79
3146293MARTNCO
Solar/Wind Harmer
0.173
3145783HORNRTN
Solar/Wind Harmer
0.185
3145796HORNRTN
Solar/Wind Harmer
0.609
3145796HORNRTN
Solar/Wind Harmer
0.185
316212AC1-099_GEN
Solar/Wind Harmer
0.945
3143226MDLTHAN
Solar/Wind Harmer
0.182
3145746EVERETS
Solar/Wind Harmer
0.181
3145746EVERETS
Solar/Wind Harmer
0.181
971795AH1-408 GEN
Solar/Wind Harmer
12.042
3147043LAWRENC
Adder
1.61
316494AC1-189 GEN
Solar/Wind Harmer
0.596
315722AD1-056 GEN
Solar/Wind Harmer
1.11
961671AG1-007 GEN
Solar/Wind Harmer
0.026
3146083TARBORO
Solar/Wind Harmer
0.172
3145493TOT1
Solar/Wind Harmer
0.767
3146233WITAKRS
Solar/Wind Harmer
0.681
316129AC1-054 GEN
Solar/Wind Harmer
0.638
971065AG2-659 GEN
Solar/Wind Harmer
7.177
3145543BTLEBRO
Solar/Wind Harmer
0.167
3145543BTLEBRO
Solar/Wind Harmer
0.134
316359AB2-059 GEN
Solar/Wind Harmer
0.602
316049AB1-081 GEN
Solar/Wind Harmer
0.959
3142053HEARTS
Solar/Wind Harmer
0.295
970919AG2-571 GEN
Solar/Wind Harmer
5.955
970087AG2-069 GEN
Solar/Wind Harmer
13.364
3143336POWHATN
Solar/Wind Harmer
2.903
957481AF2-042 GEN
Solar/Wind Harmer
43.505
315693AD1-088 GEN
Solar/Wind Harmer
7.732
962491AG1-098 GEN
Solar/Wind Harmer
9.171
316336AC2-165 C
Solar/Wind Harmer
0.006
316237AB2-079_GEN
Solar/Wind Harmer
0.001
970685AG2-442 GEN
Solar/Wind Harmer
11.542
315687AD1-152 GEN
Solar/Wind Harmer
0.005
963171AG1-166 GEN
Solar/Wind Harmer
0.819
971563AH1-280 GEN
Solar/Wind Harmer
1.637
3144293JTRSVLE
Adder
0.489
970401AG2-262 GEN
Solar/Wind Harmer
0.887
3146926FARMVIL
Solar/Wind Harmer
0.089
970937AG2-583 GEN
Solar/Wind Harmer
8.957
316003AC1-222 GEN
Solar/Wind Harmer
0.004
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.057
972003AH1-546 GEN
Solar/Wind Harmer
5.812
971377AH1-170 GEN
Solar/Wind Harmer
1.422
3147623JAMES R
Solar/Wind Harmer
0.309
315705AF1-075 GEN
Solar/Wind Harmer
4.935
972135AH1-637 GEN
Solar/Wind Harmer
1.026
970223AG2-152 GEN
Solar/Wind Harmer
7.945
3147123OTTER R
Solar/Wind Harmer
0.068
316045AC1-158 PL2
Solar/Wind Helper
5.251
316006AB2-029 C
Solar/Wind Helper
0.117
316254AC1-120 GEN1
Solar/Wind Helper
1.08
3142296MT RD221
50/50
1.091
3150691DARBY 3
50/50
22.95
3150701DARBY 4
50/50
22.896
3150681DARBY 2
50/50
22.869
3150671DARBY 1
50/50
22.843
3142366NRTHEST
50/50
1.033
316075AC2-137 C
Solar/Wind Harmer
0.085
966871AG1-558 GEN
Solar/Wind Harmer
0.344
3142946ENON
Solar/Wind Harmer
0.029
316033AB2-134 GEN
Solar/Wind Harmer
0.015
315697AD1-025 GEN
Solar/Wind Harmer
0.295
944641AF1-129 GEN
Adder
124.433
316240AF1-291 C
Solar/Wind Harmer
0.002
316236AE1-162_GEN
Solar/Wind Harmer
0.002
316036AC1-147 C
Solar/Wind Harmer
0.046
3150991CHESPKB
Adder
2.57
3150991CHESPKB
Adder
2.508
316316AC1-027 C
Solar/Wind Harmer
0.234
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.007
3145506HICKORY
Solar/Wind Harmer
0.97
3145506HICKORY
Solar/Wind Harmer
0.582
3145506HICKORY
Solar/Wind Harmer
0.146
316339AD2-160 GEN
Solar/Wind Harmer
0.392
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
316017AA1-139 ULT1
Solar/Wind Harmer
0.135
3137176SLIGO L2192
Solar/Wind Harmer
0.957
3146456SLIGO L269
Solar/Wind Harmer
4.255
3130086AYDLETT
Solar/Wind Harmer
0.96
970657AG2-426 GEN
Solar/Wind Harmer
8.387
970657AG2-426 GEN
Solar/Wind Harmer
1.758
3146386ELIZ CT
Solar/Wind Harmer
0.237
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.232
3146516WINFALL
Solar/Wind Harmer
0.232
3146516WINFALL
Solar/Wind Harmer
0.232
3146626S HERTFORD
Solar/Wind Harmer
0.23
3146626S HERTFORD
Solar/Wind Harmer
0.23
958261AF2-120 GEN
Solar/Wind Harmer
7.587
3146376EDENTON
Solar/Wind Harmer
0.994
3146376EDENTON
Solar/Wind Harmer
0.994
315742AE1-103 GEN
Solar/Wind Harmer
0.003
3143526WINTERP
Solar/Wind Harmer
1.125
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.255
3150341NORNECKC1
Adder
2.237
316468AD1-105 GEN
Solar/Wind Harmer
-0.068
316065AD1-022 GEN
Solar/Wind Harmer
9.583
3145893MURPHYS
Solar/Wind Harmer
1.358
3145893MURPHYS
Solar/Wind Harmer
0.365
3144356SAPONY
Solar/Wind Harmer
1.697
3146173TUNIS
Solar/Wind Harmer
0.201
3146173TUNIS
Solar/Wind Harmer
0.201
3142666NORTHAMPTON
Solar/Wind Harmer
0.189
3142666NORTHAMPTON
Solar/Wind Harmer
0.189
3142666NORTHAMPTON
Solar/Wind Harmer
0.189
3142666NORTHAMPTON
Solar/Wind Harmer
0.114
316426AA2-053 GEN
Solar/Wind Harmer
0.635
3145933PARMELE
Solar/Wind Harmer
0.373
3145933PARMELE
Solar/Wind Harmer
0.186
316181AB2-040 GEN
Solar/Wind Harmer
0.27
3145593CAROLNA
Solar/Wind Harmer
0.186
3145593CAROLNA
Solar/Wind Harmer
0.186
966811AG1-552 GEN
Solar/Wind Harmer
2.014
3145593CAROLNA
Solar/Wind Harmer
0.231
3145783HORNRTN
Solar/Wind Harmer
3.287
3145783HORNRTN
Solar/Wind Harmer
2.629
3145783HORNRTN
Solar/Wind Harmer
0.822
3145783HORNRTN
Solar/Wind Harmer
0.329
3145796HORNRTN
Solar/Wind Harmer
0.554
971223AH1-071 GEN
Solar/Wind Harmer
1.938
316274AC1-208 GEN
Solar/Wind Harmer
0.935
972185AH1-677 GEN
Adder
9.694
3145493TOT1
Solar/Wind Harmer
0.4
3145453TOT5
Solar/Wind Harmer
0.24
3145603CNETO
Solar/Wind Harmer
0.16
972187AH1-678 GEN
Adder
4.882
970933AG2-581 GEN
Solar/Wind Harmer
13.585
961601AG1-000A GEN
Solar/Wind Harmer
2.983
316263AC1-034 GEN
Solar/Wind Harmer
6.369
970099AG2-077 GEN
Solar/Wind Harmer
17.402
939181AE1-148 GEN
Solar/Wind Harmer
7.706
313527AB2-043 GEN
Solar/Wind Harmer
0.002
970323AG2-213 GEN
Solar/Wind Harmer
6.645
971775AH1-396 GEN
Solar/Wind Harmer
0.249
316034AC1-036 C
Solar/Wind Harmer
0.011
971741AH1-377 GEN
Solar/Wind Harmer
15.41
970301AG2-198 GEN
Solar/Wind Harmer
6.555
958211AF2-115 GEN
Solar/Wind Harmer
1.842
963191AG1-168 GEN
Solar/Wind Harmer
0.614
3144293JTRSVLE
Adder
0.489
3144293JTRSVLE
Adder
0.411
3147133PAMPLIN
Solar/Wind Harmer
0.153
3147133PAMPLIN
Solar/Wind Harmer
0.122
962561AG1-105 GEN
Solar/Wind Harmer
7.312
964791AG1-342 GEN
Solar/Wind Harmer
2.904
3146843MT LREL
Solar/Wind Harmer
0.151
3146843MT LREL
Solar/Wind Harmer
0.151
3146776BUCKING
Solar/Wind Harmer
0.569
3146776BUCKING
Solar/Wind Harmer
0.046
316222AC1-221 GEN
Solar/Wind Harmer
0.567
315821AE2-092 GEN
Solar/Wind Harmer
0.008
971489AH1-241 GEN
Solar/Wind Harmer
7.112
942751AE2-291 GEN
Solar/Wind Harmer
6.853
316447AC1-158 HLD
Solar/Wind Helper
3.611
226929AD2-058 GEN
Solar/Wind Helper
0.096
315651AD1-115 GEN
Solar/Wind Helper
0.797
NYPJM->LTFIMP_NY
CLTF
3.366
LGEELTFEXP_LGEE->PJM
CLTF
2.175
WECLTFEXP_WEC->PJM
CLTF
1.097
AG2-052LTFEXP_AG2-052->PJM
LTF
0.061
AH1-155LTFEXP_AH1-155->PJM
LTF
0.092
LAGNLTFEXP_LAGN->PJM
CLTF
9.82
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.055
TVALTFEXP_TVA->PJM
CLTF
4.995
CBM West 1LTFEXP_CBM-W1->PJM
CBM
38.714
CBM South 1LTFEXP_CBM-S1->PJM
CBM
17.519
MECLTFEXP_MEC->PJM
CLTF
5.527
SIGELTFEXP_SIGE->PJM
CLTF
0.173
CPLELTFEXP_CPLE->PJM
CLTF
10.807
CBM West 2LTFEXP_CBM-W2->PJM
CBM
55.119

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2090-256_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2090-256_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:112.2 %
Rating:5011.0 MVA
Rating Type:C
MVA to Mitigate:5622.33
MW Contribution:190.63
Bus #Bus NameTypeMW Contribution
971645AH1-323 GEN
50/50
35.663
315051AA1-145 CT1
50/50
3.181
3142416OLDCHRC
Solar/Wind Harmer
4.258
316473AC1-191 GEN
Solar/Wind Harmer
4.335
970293AG2-193 GEN
Solar/Wind Harmer
4.933
3142946ENON
Solar/Wind Harmer
-0.012
3143096IRON208
Adder
1.363
3143096IRON208
Adder
1.336
972255AH1-712 GEN
Adder
163.588
316382AG1-145 C
Solar/Wind Harmer
1.076
3142433PROV 92
Adder
0.606
3142433PROV 92
Adder
0.606
970133AG2-095 GEN
Solar/Wind Harmer
3.866
3141766HARMONY
Solar/Wind Harmer
3.046
3141843SHACKLE
Adder
1.544
316203AE2-005 GEN
Solar/Wind Harmer
14.309
970129AG2-093 GEN
Solar/Wind Harmer
19.041
3150921YORKTN3
Adder
7.557
316280AD1-041 GEN
Solar/Wind Harmer
2.537
3144216WINCHST
Adder
1.128
315778AD1-151 GEN
Solar/Wind Harmer
28.959
316156AD2-030 GEN
Solar/Wind Harmer
0.889
3141873WAN 176
Solar/Wind Harmer
3.952
3150861SPRUNCD
Adder
1.362
961611AG1-000B GEN
Solar/Wind Harmer
6.869
965281AG1-393 GEN
Solar/Wind Harmer
4.036
3151221GRAVEL6
Adder
20.871
3151171GRAVELC
Adder
4.015
315839AE2-212 C
Solar/Wind Harmer
0.958
3145336SMITFLD
Solar/Wind Harmer
-0.012
315773AC2-141 GEN
Solar/Wind Harmer
12.916
962971AG1-146 GEN
Solar/Wind Harmer
5.787
3144536CHRHLND
Solar/Wind Harmer
-0.005
315813AE1-149 C
Solar/Wind Harmer
19.114
316484AD2-074 GEN
Solar/Wind Harmer
7.63
970009AG2-005 GEN
Solar/Wind Harmer
3.789
970659AG2-427 GEN
Solar/Wind Harmer
2.853
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3151101ELIZAR3
Adder
25.01
316083AB2-161 GEN
Solar/Wind Harmer
4.909
970661AG2-428 GEN
Solar/Wind Harmer
5.666
944581AF1-123 GEN
Solar/Wind Harmer
136.793
944601AF1-125 GEN
Solar/Wind Harmer
134.658
3146456SLIGO L269
Solar/Wind Harmer
-0.03
971153AH1-033 GEN
Solar/Wind Harmer
3.616
316404AE1-155 C
Solar/Wind Harmer
5.675
971781AH1-399 GEN
Solar/Wind Harmer
1.814
316320Y1-086
Solar/Wind Harmer
1.714
316435W1029_GEN3
Solar/Wind Harmer
5.224
3146516WINFALL
Solar/Wind Harmer
-0.029
3146626S HERTFORD
Solar/Wind Harmer
-0.028
3145273HOLLAND
Solar/Wind Harmer
-0.021
3150351NORNECKC2
Adder
2.51
3146376EDENTON
Solar/Wind Harmer
-0.028
315614AA2-178 GEN
Solar/Wind Harmer
2.891
971157AH1-035 GEN
Solar/Wind Harmer
3.267
315737AD1-076 GEN
Solar/Wind Harmer
4.945
3156081AA2-088 GEN
Solar/Wind Harmer
8.314
3146206CASHIE
Solar/Wind Harmer
-0.026
3145893MURPHYS
Solar/Wind Harmer
0.176
3145893MURPHYS
Solar/Wind Harmer
-0.025
957521AF2-046 GEN
Solar/Wind Harmer
19.756
961681AG1-008 GEN
Solar/Wind Harmer
19.756
3156021HOLLOMANSOL
Solar/Wind Harmer
3.366
3146173TUNIS
Solar/Wind Harmer
-0.025
315052AA1-145 CT2
50/50
3.195
3142416OLDCHRC
Solar/Wind Harmer
-0.109
3142416OLDCHRC
Solar/Wind Harmer
-0.042
944631AF1-128 GEN
Adder
155.38
3143096IRON208
Adder
1.363
972277AH1-723 GEN
Adder
190.629
316159AE1-175 C
Solar/Wind Harmer
0.958
3142543TWELFTH
Solar/Wind Harmer
-0.003
3142433PROV 92
Solar/Wind Harmer
-0.14
3142433PROV 92
Adder
0.606
3142433PROV 92
Adder
0.606
971317AH1-138 GEN
Solar/Wind Harmer
4.287
3141766HARMONY
Solar/Wind Harmer
-0.007
971777AH1-397 GEN
Solar/Wind Harmer
3.992
3141843SHACKLE
Adder
1.544
970129AG2-093 GEN
Solar/Wind Harmer
7.713
316458AB2-190 GEN2
Solar/Wind Harmer
3.415
3138126ROCKLANDING
Solar/Wind Harmer
0.103
971069AG2-661 GEN
Solar/Wind Harmer
5.289
3150851SPRUNCC
Adder
1.362
971647AH1-324 GEN
Solar/Wind Harmer
16.455
315671AE2-027_GEN
Solar/Wind Harmer
24.52
961611AG1-000B GEN
Solar/Wind Harmer
16.098
3138133OCRAN
Solar/Wind Harmer
-0.019
3151171GRAVELC
Adder
3.054
3145336SMITFLD
Solar/Wind Harmer
-0.125
316294AC1-161 GEN
Solar/Wind Harmer
9.986
316072AD1-144
Solar/Wind Harmer
0.614
961951AG1-038 GEN
Solar/Wind Harmer
3.993
970659AG2-427 GEN
Solar/Wind Harmer
16.097
316375AC2-012 GEN
Solar/Wind Harmer
10.481
3150981CHESPKA
Adder
3.365
316381AD1-082 GEN
Solar/Wind Harmer
2.774
970661AG2-428 GEN
Solar/Wind Harmer
31.974
944591AF1-124 GEN
Solar/Wind Harmer
137.286
316388AE2-253 GEN
Solar/Wind Harmer
2.009
3146456SLIGO L269
Solar/Wind Harmer
-0.03
962861AG1-135 GEN
Solar/Wind Harmer
11.12
316246AF1-032 C
Solar/Wind Harmer
0.599
316093AE2-104_GEN
Solar/Wind Harmer
8.543
964211AG1-282 GEN
Solar/Wind Harmer
0.867
3141726DUNNSVL
Solar/Wind Harmer
-0.115
3146516WINFALL
Solar/Wind Harmer
-0.093
3146516WINFALL
Solar/Wind Harmer
-0.029
3143526WINTERP
Solar/Wind Harmer
-0.147
315800Z1-036_GEN1
Solar/Wind Harmer
6.947
3150351NORNECKC2
Adder
2.468
3130156CHOWAN
Solar/Wind Harmer
-0.028
3145663CRESWEL
Solar/Wind Harmer
-0.075
971163AH1-040 GEN
Solar/Wind Harmer
25.116
3146206CASHIE
Solar/Wind Harmer
-0.026
971547AH1-271 GEN
Solar/Wind Harmer
6.398
939411AE1-173 GEN
Solar/Wind Harmer
127.264
3145893MURPHYS
Solar/Wind Harmer
-0.1
3145893MURPHYS
Solar/Wind Harmer
0.747
316337AD2-073 GEN
Solar/Wind Harmer
0.67
3146173TUNIS
Solar/Wind Harmer
-0.025
3145683EARLEYS
Solar/Wind Harmer
-0.025
3145963POPLR C
Solar/Wind Harmer
-0.024
3146263WOODLND
Solar/Wind Harmer
-0.024
316174AB2-169 GEN
Solar/Wind Harmer
3.723
316023GEN1_S
Solar/Wind Harmer
1.623
940641AE2-051 GEN
Solar/Wind Harmer
22.443
3145823KELFORD
Solar/Wind Harmer
-0.024
3143226MDLTHAN
Solar/Wind Harmer
-0.024
316011AB1-132 GEN
Solar/Wind Harmer
4.888
962571AG1-106 GEN
Solar/Wind Harmer
3.358
316190AA2-174 GEN
Solar/Wind Harmer
0.287
960081AF2-299 GEN
Solar/Wind Harmer
2.618
3146293MARTNCO
Solar/Wind Harmer
0.143
3145796HORNRTN
Solar/Wind Harmer
-0.075
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145783HORNRTN
Solar/Wind Harmer
-0.023
316212AC1-099_GEN
Solar/Wind Harmer
1.974
971795AH1-408 GEN
Solar/Wind Harmer
16.883
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
3147043LAWRENC
Adder
1.784
316494AC1-189 GEN
Solar/Wind Harmer
2.35
315722AD1-056 GEN
Solar/Wind Harmer
2.275
961671AG1-007 GEN
Solar/Wind Harmer
0.27
3146083TARBORO
Solar/Wind Harmer
-0.021
3145493TOT1
Solar/Wind Harmer
0.634
3146233WITAKRS
Solar/Wind Harmer
-0.084
3143336POWHATN
Solar/Wind Harmer
2.497
316129AC1-054 GEN
Solar/Wind Harmer
1.844
971065AG2-659 GEN
Solar/Wind Harmer
10.428
970919AG2-571 GEN
Solar/Wind Harmer
6.584
3145543BTLEBRO
Solar/Wind Harmer
-0.021
3145543BTLEBRO
Solar/Wind Harmer
-0.017
316359AB2-059 GEN
Solar/Wind Harmer
2.798
316049AB1-081 GEN
Solar/Wind Harmer
2.239
970087AG2-069 GEN
Solar/Wind Harmer
19.453
3142053HEARTS
Solar/Wind Harmer
0.244
316336AC2-165 C
Solar/Wind Harmer
3.526
3144293JTRSVLE
Adder
0.538
316045AC1-158 PL2
Solar/Wind Helper
5.742
316006AB2-029 C
Solar/Wind Helper
0.128
316254AC1-120 GEN1
Solar/Wind Helper
1.186
957481AF2-042 GEN
Solar/Wind Harmer
54.052
3142296MT RD221
50/50
1.306
3150691DARBY 3
50/50
26.725
3150701DARBY 4
50/50
26.663
3150681DARBY 2
50/50
26.632
966871AG1-558 GEN
Solar/Wind Harmer
1.211
966871AG1-558 GEN
Solar/Wind Harmer
0.414
316075AC2-137 C
Solar/Wind Harmer
1.068
3150671DARBY 1
Adder
25.069
3142366NRTHEST
Adder
1.141
3142946ENON
Solar/Wind Harmer
-0.004
316441AF1-014 GEN
Solar/Wind Harmer
2.288
944641AF1-129 GEN
Adder
143.587
316240AF1-291 C
Solar/Wind Harmer
1.005
316033AB2-134 GEN
Solar/Wind Harmer
10.706
315697AD1-025 GEN
Solar/Wind Harmer
6.714
316236AE1-162_GEN
Solar/Wind Harmer
0.95
316487AF1-042 GEN
Solar/Wind Harmer
3.993
316036AC1-147 C
Solar/Wind Harmer
0.817
3150991CHESPKB
Adder
2.823
3150991CHESPKB
Adder
2.756
970657AG2-426 GEN
Solar/Wind Harmer
9.434
970657AG2-426 GEN
Solar/Wind Harmer
1.973
316316AC1-027 C
Solar/Wind Harmer
0.925
3142956BIRDNECK
Solar/Wind Harmer
1.617
316185AD1-033 GEN
Solar/Wind Harmer
3.167
3145506HICKORY
Solar/Wind Harmer
-0.119
3145506HICKORY
Solar/Wind Harmer
-0.072
3145506HICKORY
Solar/Wind Harmer
-0.018
316339AD2-160 GEN
Solar/Wind Harmer
2.009
316018AA1-139 ULT2
Solar/Wind Harmer
2.548
316017AA1-139 ULT1
Solar/Wind Harmer
2.407
3137176SLIGO L2192
Solar/Wind Harmer
-0.117
3146456SLIGO L269
Solar/Wind Harmer
3.503
3130086AYDLETT
Solar/Wind Harmer
-0.118
958261AF2-120 GEN
Solar/Wind Harmer
11.399
316468AD1-105 GEN
Solar/Wind Harmer
3.278
3146386ELIZ CT
Solar/Wind Harmer
-0.029
316431W1029_GEN1
Solar/Wind Harmer
5.224
316433W1029_GEN2
Solar/Wind Harmer
5.224
3146516WINFALL
Solar/Wind Harmer
-0.029
3146516WINFALL
Solar/Wind Harmer
-0.029
3146516WINFALL
Solar/Wind Harmer
-0.029
3143526WINTERP
Solar/Wind Harmer
-0.147
3146626S HERTFORD
Solar/Wind Harmer
-0.028
3146626S HERTFORD
Solar/Wind Harmer
-0.028
316077AC2-138 C
Solar/Wind Harmer
0.587
3150341NORNECKC1
Adder
2.593
3150341NORNECKC1
Adder
2.572
315742AE1-103 GEN
Solar/Wind Harmer
2.893
3146376EDENTON
Solar/Wind Harmer
0.82
3146376EDENTON
Solar/Wind Harmer
0.82
316065AD1-022 GEN
Solar/Wind Harmer
12.873
3144356SAPONY
Solar/Wind Harmer
0.893
3145893MURPHYS
Solar/Wind Harmer
0.702
3145893MURPHYS
Solar/Wind Harmer
-0.045
3146173TUNIS
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.025
971223AH1-071 GEN
Solar/Wind Harmer
2.989
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
316426AA2-053 GEN
Solar/Wind Harmer
2.359
316181AB2-040 GEN
Solar/Wind Harmer
3.234
3145593CAROLNA
Solar/Wind Harmer
-0.023
3145593CAROLNA
Solar/Wind Harmer
-0.023
966811AG1-552 GEN
Solar/Wind Harmer
2.597
3145593CAROLNA
Solar/Wind Harmer
0.192
3145933PARMELE
Solar/Wind Harmer
-0.046
3145933PARMELE
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.069
3145783HORNRTN
Solar/Wind Harmer
2.725
3145783HORNRTN
Solar/Wind Harmer
2.18
3145783HORNRTN
Solar/Wind Harmer
0.681
3145783HORNRTN
Solar/Wind Harmer
0.272
316274AC1-208 GEN
Solar/Wind Harmer
2.41
972185AH1-677 GEN
Adder
10.732
3145493TOT1
Solar/Wind Harmer
0.33
3145453TOT5
Solar/Wind Harmer
0.198
3145603CNETO
Solar/Wind Harmer
0.132
972187AH1-678 GEN
Adder
5.404
970933AG2-581 GEN
Solar/Wind Harmer
19.79
961601AG1-000A GEN
Solar/Wind Harmer
8.165
316263AC1-034 GEN
Solar/Wind Harmer
9.727
3144293JTRSVLE
Adder
0.538
3144293JTRSVLE
Adder
0.453
316447AC1-158 HLD
Solar/Wind Helper
3.948
226929AD2-058 GEN
Solar/Wind Helper
0.104
315651AD1-115 GEN
Solar/Wind Helper
0.874
970099AG2-077 GEN
Solar/Wind Harmer
21.621
972189AH1-679 GEN
50/50
7.13
316312AB1-027
Solar/Wind Harmer
1.423
315976AC1-164 GENA
Solar/Wind Harmer
41.207
316169AC1-164_GENC
Solar/Wind Harmer
35.599
315975AC1-164 GENB
Solar/Wind Harmer
1.219
972193AH1-681 GEN
Adder
7.309
971167AH1-042 GEN
Solar/Wind Harmer
33.798
3142433PROV 92
Adder
0.606
3142433PROV 92
Adder
0.606
3143873LANEXA
Solar/Wind Harmer
-0.021
316314AB2-024 C
Solar/Wind Harmer
2.973
316059AD1-063 C
Solar/Wind Harmer
0.774
316132AB2-190 GEN1
Solar/Wind Harmer
3.415
315662AE1-191 GEN
Solar/Wind Harmer
4.059
315666AE1-190 GEN
Solar/Wind Harmer
1.015
957831AF2-077 GEN
Solar/Wind Harmer
1.009
3138283WHITEMARSH
Solar/Wind Harmer
0.052
957601AF2-054 GEN
Solar/Wind Harmer
0.996
3141873WAN 176
Solar/Wind Harmer
-0.007
971285AH1-108 GEN
Adder
2.229
316369SG1_INVT
Solar/Wind Harmer
5.931
3141913WHIT STONE
Solar/Wind Harmer
-0.032
3138133OCRAN
Solar/Wind Harmer
-0.01
972265AH1-717 GEN
Adder
22.289
3151201GRAVEL4
Adder
20.895
3151191GRAVEL3
Adder
20.63
3151211GRAVEL5
Adder
20.63
3141783LANCAST
Solar/Wind Harmer
-0.019
3141783LANCAST
Solar/Wind Harmer
-0.013
971445AH1-216 GEN
Solar/Wind Harmer
19.539
962981AG1-147 GEN
Solar/Wind Harmer
13.502
3152611GOSPORTB
Adder
3.432
3152621GOSPORTC
Adder
2.913
3152601GOSPORTA
Adder
2.687
3151081ELIZAR1
Adder
24.694
3151091ELIZAR2
Adder
24.265
957871AF2-081 GEN
Solar/Wind Harmer
14.872
315833AF1-017_GEN
Solar/Wind Harmer
5.644
316349AD2-085 GEN
Solar/Wind Harmer
2.643
316311AC2-079 GEN
Solar/Wind Harmer
14.984
319010AE1-072 C
Solar/Wind Harmer
5.994
316305AF2-043 C
Solar/Wind Harmer
0.892
3146406KITTY HAWK
Solar/Wind Harmer
0.025
3143316POE
Solar/Wind Harmer
-0.116
315835AF2-110_GEN
Solar/Wind Harmer
3.673
313526AB2-022
Solar/Wind Harmer
0.789
3146486SUNBURY
Solar/Wind Harmer
-0.029
3146486SUNBURY
Solar/Wind Harmer
-0.029
316321Z2-027
Solar/Wind Harmer
0.784
3146396TANGLEW
Solar/Wind Harmer
0.535
3145176PASQUOTANK
Solar/Wind Harmer
-0.018
316233AE1-074 FULL
Solar/Wind Harmer
0.766
971281AH1-106 GEN
Solar/Wind Harmer
4.629
971283AH1-107 GEN
Solar/Wind Harmer
4.629
315611Z1-036_GEN2
Solar/Wind Harmer
6.947
3141813NORNECK
Solar/Wind Harmer
-0.028
3130156CHOWAN
Solar/Wind Harmer
-0.028
3130156CHOWAN
Solar/Wind Harmer
-0.028
315816AE2-034 GEN
Solar/Wind Harmer
2.168
3130546PLYMOUTH
Solar/Wind Harmer
-0.026
315732AD1-074 GEN1
Solar/Wind Harmer
5.262
315733AD1-074 GEN2
Solar/Wind Harmer
5.262
315735AD1-075 GEN1
Solar/Wind Harmer
2.632
316315AB2-025 C
Solar/Wind Harmer
0.69
3146206CASHIE
Solar/Wind Harmer
-0.026
970601AG2-382 GEN
Solar/Wind Harmer
11.196
315814AE2-033 C
Solar/Wind Harmer
23.761
965291AG1-394 GEN
Solar/Wind Harmer
2.257
316318V4-068
Solar/Wind Harmer
0.627
3145893MURPHYS
Solar/Wind Harmer
-0.068
3145893MURPHYS
Solar/Wind Harmer
-0.025
3145513AHOSKIE
Solar/Wind Harmer
0.216
961941AG1-037 GEN
Solar/Wind Harmer
0.186
3145513AHOSKIE
Solar/Wind Harmer
-0.025
3145683EARLEYS
Solar/Wind Harmer
-0.049
3145683EARLEYS
Solar/Wind Harmer
-0.025
3145683EARLEYS
Solar/Wind Harmer
-0.025
3146043SEABORD
Solar/Wind Harmer
-0.024
315607AA1-063A GEN
Solar/Wind Harmer
2.425
315652AC1-086 GEN
Solar/Wind Harmer
26.283
946281AF1-292 GEN
Solar/Wind Harmer
0.521
3146033SCOT NK
Solar/Wind Harmer
-0.092
316087AB2-174 GEN
Solar/Wind Harmer
3.311
3137643SOCKMAN
Solar/Wind Harmer
-0.092
3145796HORNRTN
Solar/Wind Harmer
-0.073
3145796HORNRTN
Solar/Wind Harmer
-0.009
316005AA1-067
Solar/Wind Harmer
0.453
3145746EVERETS
Solar/Wind Harmer
-0.089
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
970181AG2-120 GEN
Solar/Wind Harmer
2.94
941031AE2-094 GEN
Solar/Wind Harmer
40.999
944011AF1-069 GEN
Solar/Wind Harmer
12.846
957861AF2-080 GEN
Solar/Wind Harmer
9.556
316223AC1-118
Solar/Wind Harmer
0.586
970673AG2-436 GEN
Solar/Wind Harmer
45.407
970673AG2-436 GEN
Solar/Wind Harmer
22.991
316420AA1-050 GEN
Solar/Wind Harmer
2.464
971967AH1-528 GEN
Solar/Wind Harmer
40.31
3145573BETHELC
Solar/Wind Harmer
-0.021
3145573BETHELC
Solar/Wind Harmer
-0.021
970831AG2-522 GEN
Solar/Wind Harmer
10.617
316319Z2-044 C
Solar/Wind Harmer
1.171
970085AG2-068 GEN
Solar/Wind Harmer
12.969
970581AG2-369 GEN
Solar/Wind Harmer
11.153
972205AH1-687 GEN
Adder
6.364
3151881LOWMORC
Adder
1.527
3151881LOWMORC
Adder
1.503
3151861LOWMORA
Adder
1.479
316164AC1-076 GEN
Solar/Wind Helper
1.417
316411AF1-147_GEN1
Solar/Wind Helper
0.862
316415AF1-147_GEN2
Solar/Wind Helper
0.862
3138216PACIFIC
Solar/Wind Helper
0.042
316463AE2-346 GEN
Solar/Wind Harmer
0.401
316140AB2-099
Solar/Wind Harmer
0.167
962331AG1-082 GEN
Solar/Wind Harmer
3.093
3145963POPLR C
Solar/Wind Harmer
-0.024
3146263WOODLND
Solar/Wind Harmer
-0.024
316365GEN2_N
Solar/Wind Harmer
1.623
316317KELFORD C
Solar/Wind Harmer
1.127
3145823KELFORD
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
966621AG1-532 GEN
Solar/Wind Harmer
0.472
313506AB2-031 GEN
Solar/Wind Harmer
1.863
3145933PARMELE
Solar/Wind Harmer
-0.023
966801AG1-551 GEN
Solar/Wind Harmer
2.88
3145796HORNRTN
Solar/Wind Harmer
-0.091
3145796HORNRTN
Solar/Wind Harmer
-0.023
316210AC1-098 GEN
Solar/Wind Harmer
3.554
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
3147043LAWRENC
Solar/Wind Harmer
-0.013
315724AD1-057 GEN
Solar/Wind Harmer
1.251
3141906WESTMOR
Solar/Wind Harmer
-0.009
316327AA2-057 GEN
Solar/Wind Harmer
2.186
3146073TAR RVR
Solar/Wind Harmer
-0.021
3146083TARBORO
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
0.444
3146233WITAKRS
Solar/Wind Harmer
-0.014
3138543CONSLDL
Solar/Wind Harmer
-0.014
316313AB2-026
Solar/Wind Harmer
0.568
316258AE1-075 C
Solar/Wind Harmer
0.511
316405AF2-144 C
Solar/Wind Harmer
0.539
3143336POWHATN
Solar/Wind Harmer
2.123
970917AG2-570 GEN
Solar/Wind Harmer
52.017
961601AG1-000A GEN
Solar/Wind Harmer
8.268
3145543BTLEBRO
Solar/Wind Harmer
-0.021
3145543BTLEBRO
Solar/Wind Harmer
-0.021
3144293JTRSVLE
Adder
0.538
3151861LOWMORA
Adder
1.539
316044AC1-158 PL1
Solar/Wind Helper
1.794
316450AC1-158 RIC
Solar/Wind Helper
0.478
3141196NOKESVL
Solar/Wind Helper
1.114
227287AC2-120 GEN
Solar/Wind Helper
0.353
316170AC1-121 GEN2
Solar/Wind Helper
0.395
226910AB2-157 C
Solar/Wind Helper
0.014
NYPJM->LTFIMP_NY
CLTF
3.681
LGEELTFEXP_LGEE->PJM
CLTF
2.258
WECLTFEXP_WEC->PJM
CLTF
1.136
AG2-052LTFEXP_AG2-052->PJM
LTF
0.063
AH1-155LTFEXP_AH1-155->PJM
LTF
0.095
LAGNLTFEXP_LAGN->PJM
CLTF
10.434
CBM South 2LTFEXP_CBM-S2->PJM
CBM
27.172
TVALTFEXP_TVA->PJM
CLTF
5.305
CBM West 1LTFEXP_CBM-W1->PJM
CBM
39.93
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.557
MECLTFEXP_MEC->PJM
CLTF
5.768
SIGELTFEXP_SIGE->PJM
CLTF
0.18
CPLELTFEXP_CPLE->PJM
CLTF
11.803
CBM West 2LTFEXP_CBM-W2->PJM
CBM
58.138

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2076-2145_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2076-2145_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:110.02 %
Rating:5011.0 MVA
Rating Type:C
MVA to Mitigate:5512.93
MW Contribution:187.62
Bus #Bus NameTypeMW Contribution
3150351NORNECKC2
50/50
3.409
966661AG1-536 GEN
50/50
9.12
3141843SHACKLE
50/50
1.722
3152161CUNINGA
50/50
2.429
3142416OLDCHRC
Solar/Wind Harmer
-0.098
3142416OLDCHRC
Solar/Wind Harmer
-0.037
964211AG1-282 GEN
Solar/Wind Harmer
1.092
3141726DUNNSVL
Solar/Wind Harmer
-0.145
316337AD2-073 GEN
Solar/Wind Harmer
0.975
972135AH1-637 GEN
Solar/Wind Harmer
3.628
957971AF2-091 GEN
Solar/Wind Harmer
3.61
3141766HARMONY
Solar/Wind Harmer
-0.007
962861AG1-135 GEN
Solar/Wind Harmer
13.499
961951AG1-038 GEN
Solar/Wind Harmer
4.732
3138133OCRAN
Solar/Wind Harmer
-0.021
971777AH1-397 GEN
Solar/Wind Harmer
4.196
972277AH1-723 GEN
Adder
187.618
3142433PROV 92
Solar/Wind Harmer
-0.139
3142433PROV 92
Adder
0.606
3142433PROV 92
Adder
0.606
316159AE1-175 C
Solar/Wind Harmer
0.938
944631AF1-128 GEN
Adder
145.494
971317AH1-138 GEN
Solar/Wind Harmer
4.26
3143096IRON208
Adder
1.248
3138126ROCKLANDING
Solar/Wind Harmer
0.101
3142543TWELFTH
Solar/Wind Harmer
-0.003
970129AG2-093 GEN
Solar/Wind Harmer
7.231
316458AB2-190 GEN2
Solar/Wind Harmer
3.204
971069AG2-661 GEN
Solar/Wind Harmer
4.984
971647AH1-324 GEN
Solar/Wind Harmer
15.611
961611AG1-000B GEN
Solar/Wind Harmer
15.333
3151171GRAVELC
Adder
2.923
3145336SMITFLD
Solar/Wind Harmer
-0.12
315671AE2-027_GEN
Solar/Wind Harmer
22.629
316294AC1-161 GEN
Solar/Wind Harmer
9.694
3150851SPRUNCC
Adder
1.226
316072AD1-144
Solar/Wind Harmer
0.593
316375AC2-012 GEN
Solar/Wind Harmer
10.123
3150981CHESPKA
Adder
3.251
944591AF1-124 GEN
Solar/Wind Harmer
132.801
316388AE2-253 GEN
Solar/Wind Harmer
1.941
3146456SLIGO L269
Solar/Wind Harmer
-0.029
316246AF1-032 C
Solar/Wind Harmer
0.579
970659AG2-427 GEN
Solar/Wind Harmer
15.161
316381AD1-082 GEN
Solar/Wind Harmer
2.616
970661AG2-428 GEN
Solar/Wind Harmer
30.261
316093AE2-104_GEN
Solar/Wind Harmer
8.224
3146516WINFALL
Solar/Wind Harmer
-0.089
3146516WINFALL
Solar/Wind Harmer
-0.028
315800Z1-036_GEN1
Solar/Wind Harmer
6.702
3130156CHOWAN
Solar/Wind Harmer
-0.027
3145663CRESWEL
Solar/Wind Harmer
-0.072
971163AH1-040 GEN
Solar/Wind Harmer
24.203
3143526WINTERP
Solar/Wind Harmer
-0.132
3146206CASHIE
Solar/Wind Harmer
-0.025
971547AH1-271 GEN
Solar/Wind Harmer
6.156
939411AE1-173 GEN
Solar/Wind Harmer
122.514
3145893MURPHYS
Solar/Wind Harmer
-0.096
3145893MURPHYS
Solar/Wind Harmer
0.717
3146173TUNIS
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145963POPLR C
Solar/Wind Harmer
-0.023
316174AB2-169 GEN
Solar/Wind Harmer
3.581
3146263WOODLND
Solar/Wind Harmer
-0.023
940641AE2-051 GEN
Solar/Wind Harmer
21.565
3145823KELFORD
Solar/Wind Harmer
-0.023
316023GEN1_S
Solar/Wind Harmer
1.542
316190AA2-174 GEN
Solar/Wind Harmer
0.275
316011AB1-132 GEN
Solar/Wind Harmer
4.668
962571AG1-106 GEN
Solar/Wind Harmer
3.207
960081AF2-299 GEN
Solar/Wind Harmer
2.493
3146293MARTNCO
Solar/Wind Harmer
0.137
3145783HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.072
3145796HORNRTN
Solar/Wind Harmer
-0.022
316212AC1-099_GEN
Solar/Wind Harmer
1.893
3145746EVERETS
Solar/Wind Harmer
-0.021
3145746EVERETS
Solar/Wind Harmer
-0.021
3143226MDLTHAN
Solar/Wind Harmer
-0.021
971795AH1-408 GEN
Solar/Wind Harmer
16.09
3147043LAWRENC
Adder
1.701
316494AC1-189 GEN
Solar/Wind Harmer
2.257
315722AD1-056 GEN
Solar/Wind Harmer
2.178
961671AG1-007 GEN
Solar/Wind Harmer
0.259
3146083TARBORO
Solar/Wind Harmer
-0.02
3145493TOT1
Solar/Wind Harmer
0.608
3146233WITAKRS
Solar/Wind Harmer
-0.08
316129AC1-054 GEN
Solar/Wind Harmer
1.766
971065AG2-659 GEN
Solar/Wind Harmer
9.983
970919AG2-571 GEN
Solar/Wind Harmer
6.312
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.016
316359AB2-059 GEN
Solar/Wind Harmer
2.683
316049AB1-081 GEN
Solar/Wind Harmer
2.147
3142053HEARTS
Solar/Wind Harmer
0.234
970087AG2-069 GEN
Solar/Wind Harmer
18.65
3144293JTRSVLE
Adder
0.514
316045AC1-158 PL2
Solar/Wind Helper
5.315
316006AB2-029 C
Solar/Wind Helper
0.12
316254AC1-120 GEN1
Solar/Wind Helper
1.098
957481AF2-042 GEN
Solar/Wind Harmer
44.546
3142296MT RD221
50/50
1.125
3150341NORNECKC1
50/50
3.581
3150341NORNECKC1
50/50
3.552
963611AG1-210 GEN
50/50
1.146
3150691DARBY 3
50/50
24.142
3150701DARBY 4
50/50
24.085
3150681DARBY 2
50/50
24.057
3150671DARBY 1
50/50
24.029
316075AC2-137 C
Solar/Wind Harmer
1.004
316077AC2-138 C
Solar/Wind Harmer
0.764
958261AF2-120 GEN
Solar/Wind Harmer
13.96
316487AF1-042 GEN
Solar/Wind Harmer
4.732
316441AF1-014 GEN
Solar/Wind Harmer
2.405
3142946ENON
Solar/Wind Harmer
-0.004
3142366NRTHEST
Adder
1.019
966871AG1-558 GEN
Solar/Wind Harmer
1.032
966871AG1-558 GEN
Solar/Wind Harmer
0.353
316033AB2-134 GEN
Solar/Wind Harmer
10.118
315697AD1-025 GEN
Solar/Wind Harmer
6.346
944641AF1-129 GEN
Adder
130.968
316240AF1-291 C
Solar/Wind Harmer
0.918
316236AE1-162_GEN
Solar/Wind Harmer
0.912
316036AC1-147 C
Solar/Wind Harmer
0.789
315759AF1-018 GEN
50/50
11.406
3152181CUNINGC
50/50
2.595
972193AH1-681 GEN
50/50
7.633
316312AB1-027
Solar/Wind Harmer
1.278
315976AC1-164 GENA
Solar/Wind Harmer
39.805
316169AC1-164_GENC
Solar/Wind Harmer
34.388
315975AC1-164 GENB
Solar/Wind Harmer
1.178
316314AB2-024 C
Solar/Wind Harmer
3.105
316223AC1-118
Solar/Wind Harmer
0.979
944491AF1-114 GEN
Solar/Wind Harmer
10.62
3141813NORNECK
Solar/Wind Harmer
-0.036
316059AD1-063 C
Solar/Wind Harmer
0.815
962981AG1-147 GEN
Solar/Wind Harmer
15.689
3143873LANEXA
Solar/Wind Harmer
-0.021
3141783LANCAST
Solar/Wind Harmer
-0.021
3141783LANCAST
Solar/Wind Harmer
-0.014
3138133OCRAN
Solar/Wind Harmer
-0.011
3141913WHIT STONE
Solar/Wind Harmer
-0.036
315662AE1-191 GEN
Solar/Wind Harmer
4.296
315666AE1-190 GEN
Solar/Wind Harmer
1.074
957601AF2-054 GEN
Solar/Wind Harmer
1.064
3141873WAN 176
Solar/Wind Harmer
-0.007
3142433PROV 92
Adder
0.606
3142433PROV 92
Adder
0.606
971167AH1-042 GEN
Solar/Wind Harmer
33.529
957831AF2-077 GEN
Solar/Wind Harmer
1.033
3138283WHITEMARSH
Solar/Wind Harmer
0.053
316132AB2-190 GEN1
Solar/Wind Harmer
3.204
316369SG1_INVT
Solar/Wind Harmer
5.606
972265AH1-717 GEN
Adder
21.338
3151201GRAVEL4
Adder
20.003
3151191GRAVEL3
Adder
19.75
3151211GRAVEL5
Adder
19.75
971445AH1-216 GEN
Solar/Wind Harmer
18.761
971285AH1-108 GEN
Adder
2.006
3152611GOSPORTB
Adder
3.315
3152621GOSPORTC
Adder
2.813
3152601GOSPORTA
Adder
2.595
3151081ELIZAR1
Adder
23.856
3151091ELIZAR2
Adder
23.441
957871AF2-081 GEN
Solar/Wind Harmer
14.371
319010AE1-072 C
Solar/Wind Harmer
5.791
3146406KITTY HAWK
Solar/Wind Harmer
0.024
316305AF2-043 C
Solar/Wind Harmer
0.862
315833AF1-017_GEN
Solar/Wind Harmer
5.389
316349AD2-085 GEN
Solar/Wind Harmer
2.524
316311AC2-079 GEN
Solar/Wind Harmer
14.311
315835AF2-110_GEN
Solar/Wind Harmer
3.536
313526AB2-022
Solar/Wind Harmer
0.762
3146486SUNBURY
Solar/Wind Harmer
-0.028
3146486SUNBURY
Solar/Wind Harmer
-0.028
316321Z2-027
Solar/Wind Harmer
0.757
3146396TANGLEW
Solar/Wind Harmer
0.516
3145176PASQUOTANK
Solar/Wind Harmer
-0.017
3143316POE
Solar/Wind Harmer
-0.107
315611Z1-036_GEN2
Solar/Wind Harmer
6.702
3130156CHOWAN
Solar/Wind Harmer
-0.027
3130156CHOWAN
Solar/Wind Harmer
-0.027
315816AE2-034 GEN
Solar/Wind Harmer
2.089
316233AE1-074 FULL
Solar/Wind Harmer
0.687
971281AH1-106 GEN
Solar/Wind Harmer
4.151
971283AH1-107 GEN
Solar/Wind Harmer
4.151
972189AH1-679 GEN
Adder
3.806
3130546PLYMOUTH
Solar/Wind Harmer
-0.025
315732AD1-074 GEN1
Solar/Wind Harmer
5.066
315733AD1-074 GEN2
Solar/Wind Harmer
5.066
315735AD1-075 GEN1
Solar/Wind Harmer
2.534
3146206CASHIE
Solar/Wind Harmer
-0.025
970601AG2-382 GEN
Solar/Wind Harmer
10.772
965291AG1-394 GEN
Solar/Wind Harmer
2.166
316318V4-068
Solar/Wind Harmer
0.602
3145893MURPHYS
Solar/Wind Harmer
-0.065
3145893MURPHYS
Solar/Wind Harmer
-0.024
316315AB2-025 C
Solar/Wind Harmer
0.651
315814AE2-033 C
Solar/Wind Harmer
22.406
3145513AHOSKIE
Solar/Wind Harmer
0.207
961941AG1-037 GEN
Solar/Wind Harmer
0.179
3145513AHOSKIE
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.047
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
3146043SEABORD
Solar/Wind Harmer
-0.023
315607AA1-063A GEN
Solar/Wind Harmer
2.323
315652AC1-086 GEN
Solar/Wind Harmer
25.099
3146033SCOT NK
Solar/Wind Harmer
-0.089
946281AF1-292 GEN
Solar/Wind Harmer
0.496
316087AB2-174 GEN
Solar/Wind Harmer
3.158
3137643SOCKMAN
Solar/Wind Harmer
-0.088
3145796HORNRTN
Solar/Wind Harmer
-0.07
3145796HORNRTN
Solar/Wind Harmer
-0.009
316005AA1-067
Solar/Wind Harmer
0.436
3145746EVERETS
Solar/Wind Harmer
-0.085
3145746EVERETS
Solar/Wind Harmer
-0.021
3145746EVERETS
Solar/Wind Harmer
-0.021
3145746EVERETS
Solar/Wind Harmer
-0.021
970181AG2-120 GEN
Solar/Wind Harmer
2.826
957861AF2-080 GEN
Solar/Wind Harmer
9.177
941031AE2-094 GEN
Solar/Wind Harmer
39.278
944011AF1-069 GEN
Solar/Wind Harmer
12.307
316420AA1-050 GEN
Solar/Wind Harmer
2.365
970673AG2-436 GEN
Solar/Wind Harmer
43.507
970673AG2-436 GEN
Solar/Wind Harmer
22.029
971967AH1-528 GEN
Solar/Wind Harmer
38.619
3145573BETHELC
Solar/Wind Harmer
-0.02
3145573BETHELC
Solar/Wind Harmer
-0.02
316319Z2-044 C
Solar/Wind Harmer
1.123
970831AG2-522 GEN
Solar/Wind Harmer
10.164
970085AG2-068 GEN
Solar/Wind Harmer
12.433
970581AG2-369 GEN
Solar/Wind Harmer
10.692
3151881LOWMORC
Adder
1.506
3151881LOWMORC
Adder
1.482
3151861LOWMORA
Adder
1.458
972205AH1-687 GEN
Adder
6.025
316164AC1-076 GEN
Solar/Wind Helper
1.309
3141426STAFORD
Solar/Wind Helper
0.058
316411AF1-147_GEN1
Solar/Wind Helper
0.832
316415AF1-147_GEN2
Solar/Wind Helper
0.832
3138216PACIFIC
Solar/Wind Helper
0.041
971645AH1-323 GEN
50/50
30.503
3150351NORNECKC2
50/50
3.466
315749AE2-041 GEN
50/50
11.406
970575AG2-366 GEN
50/50
5.674
3141843SHACKLE
50/50
1.722
3152191CUNINGD
50/50
5.651
3152171CUNINGB
50/50
2.44
3142416OLDCHRC
Solar/Wind Harmer
3.824
970293AG2-193 GEN
Solar/Wind Harmer
4.543
3141906WESTMOR
Solar/Wind Harmer
-0.014
970737AG2-469 GEN
Solar/Wind Harmer
18.144
3141766HARMONY
Solar/Wind Harmer
3.208
316404AE1-155 C
Solar/Wind Harmer
6.949
316484AD2-074 GEN
Solar/Wind Harmer
9.043
970009AG2-005 GEN
Solar/Wind Harmer
4.49
962971AG1-146 GEN
Solar/Wind Harmer
6.724
316203AE2-005 GEN
Solar/Wind Harmer
15.045
316280AD1-041 GEN
Solar/Wind Harmer
2.685
316156AD2-030 GEN
Solar/Wind Harmer
0.95
3141873WAN 176
Solar/Wind Harmer
4.223
972255AH1-712 GEN
Adder
161.004
3142946ENON
Solar/Wind Harmer
-0.012
3142433PROV 92
Adder
0.606
3142433PROV 92
Adder
0.606
316382AG1-145 C
Solar/Wind Harmer
1.053
316473AC1-191 GEN
Solar/Wind Harmer
3.695
3143096IRON208
Adder
1.248
3143096IRON208
Adder
1.223
3150921YORKTN3
Adder
7.437
3144216WINCHST
Adder
1.105
970133AG2-095 GEN
Solar/Wind Harmer
3.599
970129AG2-093 GEN
Solar/Wind Harmer
17.851
315778AD1-151 GEN
Solar/Wind Harmer
27.286
961611AG1-000B GEN
Solar/Wind Harmer
6.542
3151221GRAVEL6
Adder
19.98
3151171GRAVELC
Adder
3.844
3145336SMITFLD
Solar/Wind Harmer
-0.012
315773AC2-141 GEN
Solar/Wind Harmer
12.538
3150861SPRUNCD
Adder
1.226
965281AG1-393 GEN
Solar/Wind Harmer
3.728
3144536CHRHLND
Solar/Wind Harmer
-0.005
3151101ELIZAR3
Adder
24.161
3144873MCLAUGH
Solar/Wind Harmer
-0.001
315839AE2-212 C
Solar/Wind Harmer
0.881
944581AF1-123 GEN
Solar/Wind Harmer
132.324
944601AF1-125 GEN
Solar/Wind Harmer
130.259
3146456SLIGO L269
Solar/Wind Harmer
-0.029
971153AH1-033 GEN
Solar/Wind Harmer
3.494
315813AE1-149 C
Solar/Wind Harmer
17.884
970659AG2-427 GEN
Solar/Wind Harmer
2.687
316083AB2-161 GEN
Solar/Wind Harmer
4.629
970661AG2-428 GEN
Solar/Wind Harmer
5.363
316320Y1-086
Solar/Wind Harmer
1.655
316435W1029_GEN3
Solar/Wind Harmer
5.043
3146516WINFALL
Solar/Wind Harmer
-0.028
3146626S HERTFORD
Solar/Wind Harmer
-0.027
3145273HOLLAND
Solar/Wind Harmer
-0.02
3146376EDENTON
Solar/Wind Harmer
-0.027
315614AA2-178 GEN
Solar/Wind Harmer
2.785
971157AH1-035 GEN
Solar/Wind Harmer
3.146
315737AD1-076 GEN
Solar/Wind Harmer
4.761
3146206CASHIE
Solar/Wind Harmer
-0.025
3156081AA2-088 GEN
Solar/Wind Harmer
7.981
3145893MURPHYS
Solar/Wind Harmer
0.169
3145893MURPHYS
Solar/Wind Harmer
-0.024
957521AF2-046 GEN
Solar/Wind Harmer
18.965
961681AG1-008 GEN
Solar/Wind Harmer
18.965
3156021HOLLOMANSOL
Solar/Wind Harmer
3.235
3146173TUNIS
Solar/Wind Harmer
-0.024
316463AE2-346 GEN
Solar/Wind Harmer
0.385
316140AB2-099
Solar/Wind Harmer
0.16
962331AG1-082 GEN
Solar/Wind Harmer
2.97
3145963POPLR C
Solar/Wind Harmer
-0.023
971781AH1-399 GEN
Solar/Wind Harmer
1.433
3146263WOODLND
Solar/Wind Harmer
-0.023
316317KELFORD C
Solar/Wind Harmer
1.082
3145823KELFORD
Solar/Wind Harmer
-0.023
316365GEN2_N
Solar/Wind Harmer
1.542
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
966621AG1-532 GEN
Solar/Wind Harmer
0.45
3145933PARMELE
Solar/Wind Harmer
-0.022
966801AG1-551 GEN
Solar/Wind Harmer
2.768
313506AB2-031 GEN
Solar/Wind Harmer
1.778
3145796HORNRTN
Solar/Wind Harmer
-0.087
3145796HORNRTN
Solar/Wind Harmer
-0.022
316210AC1-098 GEN
Solar/Wind Harmer
3.408
3145746EVERETS
Solar/Wind Harmer
-0.021
3145746EVERETS
Solar/Wind Harmer
-0.021
3147043LAWRENC
Solar/Wind Harmer
-0.013
315724AD1-057 GEN
Solar/Wind Harmer
1.198
316327AA2-057 GEN
Solar/Wind Harmer
2.095
3146073TAR RVR
Solar/Wind Harmer
-0.02
3146083TARBORO
Solar/Wind Harmer
-0.02
3146233WITAKRS
Solar/Wind Harmer
0.425
3146233WITAKRS
Solar/Wind Harmer
-0.014
3138543CONSLDL
Solar/Wind Harmer
-0.013
970917AG2-570 GEN
Solar/Wind Harmer
49.866
961601AG1-000A GEN
Solar/Wind Harmer
7.929
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3144293JTRSVLE
Adder
0.514
3151861LOWMORA
Adder
1.518
316044AC1-158 PL1
Solar/Wind Helper
1.66
316450AC1-158 RIC
Solar/Wind Helper
0.443
3141196NOKESVL
Solar/Wind Helper
1.065
227287AC2-120 GEN
Solar/Wind Helper
0.341
226910AB2-157 C
Solar/Wind Helper
0.014
316170AC1-121 GEN2
Solar/Wind Helper
0.366
3150991CHESPKB
Adder
2.727
3150991CHESPKB
Adder
2.662
316316AC1-027 C
Solar/Wind Harmer
0.894
3142956BIRDNECK
Solar/Wind Harmer
1.562
316185AD1-033 GEN
Solar/Wind Harmer
3.061
3145506HICKORY
Solar/Wind Harmer
-0.115
3145506HICKORY
Solar/Wind Harmer
-0.069
3145506HICKORY
Solar/Wind Harmer
-0.017
316339AD2-160 GEN
Solar/Wind Harmer
1.941
316018AA1-139 ULT2
Solar/Wind Harmer
2.462
316017AA1-139 ULT1
Solar/Wind Harmer
2.326
3137176SLIGO L2192
Solar/Wind Harmer
-0.113
3146456SLIGO L269
Solar/Wind Harmer
3.385
3130086AYDLETT
Solar/Wind Harmer
-0.114
970657AG2-426 GEN
Solar/Wind Harmer
8.908
970657AG2-426 GEN
Solar/Wind Harmer
1.863
3146386ELIZ CT
Solar/Wind Harmer
-0.028
316431W1029_GEN1
Solar/Wind Harmer
5.043
316433W1029_GEN2
Solar/Wind Harmer
5.043
3146516WINFALL
Solar/Wind Harmer
-0.028
3146516WINFALL
Solar/Wind Harmer
-0.028
3146516WINFALL
Solar/Wind Harmer
-0.028
3146626S HERTFORD
Solar/Wind Harmer
-0.027
3146626S HERTFORD
Solar/Wind Harmer
-0.027
3146376EDENTON
Solar/Wind Harmer
0.791
3146376EDENTON
Solar/Wind Harmer
0.791
315742AE1-103 GEN
Solar/Wind Harmer
2.781
3143526WINTERP
Solar/Wind Harmer
-0.132
316065AD1-022 GEN
Solar/Wind Harmer
12.389
3145893MURPHYS
Solar/Wind Harmer
0.674
3145893MURPHYS
Solar/Wind Harmer
-0.043
3144356SAPONY
Solar/Wind Harmer
0.841
3146173TUNIS
Solar/Wind Harmer
-0.024
3146173TUNIS
Solar/Wind Harmer
-0.024
316468AD1-105 GEN
Solar/Wind Harmer
2.59
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
316426AA2-053 GEN
Solar/Wind Harmer
2.259
3145933PARMELE
Solar/Wind Harmer
-0.044
3145933PARMELE
Solar/Wind Harmer
-0.022
316181AB2-040 GEN
Solar/Wind Harmer
3.086
3145593CAROLNA
Solar/Wind Harmer
-0.022
3145593CAROLNA
Solar/Wind Harmer
-0.022
966811AG1-552 GEN
Solar/Wind Harmer
2.484
3145593CAROLNA
Solar/Wind Harmer
0.183
3145783HORNRTN
Solar/Wind Harmer
2.608
3145783HORNRTN
Solar/Wind Harmer
2.086
3145783HORNRTN
Solar/Wind Harmer
0.652
3145783HORNRTN
Solar/Wind Harmer
0.261
3145796HORNRTN
Solar/Wind Harmer
-0.065
971223AH1-071 GEN
Solar/Wind Harmer
2.682
316274AC1-208 GEN
Solar/Wind Harmer
2.31
972185AH1-677 GEN
Adder
10.284
3145493TOT1
Solar/Wind Harmer
0.317
3145453TOT5
Solar/Wind Harmer
0.19
3145603CNETO
Solar/Wind Harmer
0.127
972187AH1-678 GEN
Adder
5.178
970933AG2-581 GEN
Solar/Wind Harmer
18.958
961601AG1-000A GEN
Solar/Wind Harmer
7.83
316263AC1-034 GEN
Solar/Wind Harmer
9.328
3144293JTRSVLE
Adder
0.514
3144293JTRSVLE
Adder
0.433
316447AC1-158 HLD
Solar/Wind Helper
3.654
226929AD2-058 GEN
Solar/Wind Helper
0.101
315651AD1-115 GEN
Solar/Wind Helper
0.812
970099AG2-077 GEN
Solar/Wind Harmer
17.818
NYPJM->LTFIMP_NY
CLTF
3.519
LGEELTFEXP_LGEE->PJM
CLTF
2.238
WECLTFEXP_WEC->PJM
CLTF
1.128
AG2-052LTFEXP_AG2-052->PJM
LTF
0.063
AH1-155LTFEXP_AH1-155->PJM
LTF
0.094
LAGNLTFEXP_LAGN->PJM
CLTF
10.202
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.271
TVALTFEXP_TVA->PJM
CLTF
5.187
CBM West 1LTFEXP_CBM-W1->PJM
CBM
39.767
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.174
MECLTFEXP_MEC->PJM
CLTF
5.701
SIGELTFEXP_SIGE->PJM
CLTF
0.178
CPLELTFEXP_CPLE->PJM
CLTF
11.373
CBM West 2LTFEXP_CBM-W2->PJM
CBM
57.092

Details for 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 573_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:126.22 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5137.22
MW Contribution:99.58
Bus #Bus NameTypeMW Contribution
3150391LDYSMT3
50/50
38.213
972195AH1-682 GEN
50/50
5.022
315673AE1-157 GEN
Solar/Wind Harmer
18.457
957411AF2-035 GEN
Solar/Wind Harmer
11.334
970317AG2-208 GEN
Solar/Wind Harmer
10.501
3142296MT RD221
Adder
0.82
3142366NRTHEST
Adder
0.825
3150691DARBY 3
Adder
18.133
3150701DARBY 4
Adder
18.091
3150681DARBY 2
Adder
18.07
3150671DARBY 1
Adder
18.049
316075AC2-137 C
Solar/Wind Harmer
0.069
3143526WINTERP
Solar/Wind Harmer
1.295
966871AG1-558 GEN
Solar/Wind Harmer
0.287
971223AH1-071 GEN
Solar/Wind Harmer
2.646
3142946ENON
Solar/Wind Harmer
0.025
944641AF1-129 GEN
Adder
116.855
316240AF1-291 C
Solar/Wind Harmer
0.002
316033AB2-134 GEN
Solar/Wind Harmer
0.014
315697AD1-025 GEN
Solar/Wind Harmer
0.272
316236AE1-162_GEN
Solar/Wind Harmer
0.002
316036AC1-147 C
Solar/Wind Harmer
0.044
3150991CHESPKB
Adder
2.482
3150991CHESPKB
Adder
2.423
970657AG2-426 GEN
Solar/Wind Harmer
8.291
970657AG2-426 GEN
Solar/Wind Harmer
1.738
316316AC1-027 C
Solar/Wind Harmer
0.227
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.007
3145506HICKORY
Solar/Wind Harmer
0.942
3145506HICKORY
Solar/Wind Harmer
0.565
3145506HICKORY
Solar/Wind Harmer
0.141
316339AD2-160 GEN
Solar/Wind Harmer
0.381
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
316017AA1-139 ULT1
Solar/Wind Harmer
0.131
3137176SLIGO L2192
Solar/Wind Harmer
0.931
3146456SLIGO L269
Solar/Wind Harmer
4.141
3130086AYDLETT
Solar/Wind Harmer
0.934
3146386ELIZ CT
Solar/Wind Harmer
0.231
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.228
3146516WINFALL
Solar/Wind Harmer
0.228
3146516WINFALL
Solar/Wind Harmer
0.228
3146626S HERTFORD
Solar/Wind Harmer
0.227
3146626S HERTFORD
Solar/Wind Harmer
0.227
3144356SAPONY
Solar/Wind Harmer
1.894
315742AE1-103 GEN
Solar/Wind Harmer
0.003
3146376EDENTON
Solar/Wind Harmer
0.987
3146376EDENTON
Solar/Wind Harmer
0.987
958261AF2-120 GEN
Solar/Wind Harmer
7.345
972185AH1-677 GEN
Adder
12.364
972187AH1-678 GEN
Adder
6.203
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.271
3150341NORNECKC1
Adder
2.253
316468AD1-105 GEN
Solar/Wind Harmer
-0.071
970933AG2-581 GEN
Solar/Wind Harmer
17.147
316065AD1-022 GEN
Solar/Wind Harmer
9.721
3145893MURPHYS
Solar/Wind Harmer
1.401
3145893MURPHYS
Solar/Wind Harmer
0.376
3146173TUNIS
Solar/Wind Harmer
0.207
3146173TUNIS
Solar/Wind Harmer
0.207
316181AB2-040 GEN
Solar/Wind Harmer
0.293
3142666NORTHAMPTON
Solar/Wind Harmer
0.202
3142666NORTHAMPTON
Solar/Wind Harmer
0.202
3142666NORTHAMPTON
Solar/Wind Harmer
0.202
3142666NORTHAMPTON
Solar/Wind Harmer
0.121
970099AG2-077 GEN
Solar/Wind Harmer
21.434
316426AA2-053 GEN
Solar/Wind Harmer
0.677
3145593CAROLNA
Solar/Wind Harmer
0.199
3145593CAROLNA
Solar/Wind Harmer
0.199
966811AG1-552 GEN
Solar/Wind Harmer
2.162
3145593CAROLNA
Solar/Wind Harmer
0.248
3145783HORNRTN
Solar/Wind Harmer
3.524
3145783HORNRTN
Solar/Wind Harmer
2.819
3145783HORNRTN
Solar/Wind Harmer
0.881
3145783HORNRTN
Solar/Wind Harmer
0.352
3145796HORNRTN
Solar/Wind Harmer
0.594
3145933PARMELE
Solar/Wind Harmer
0.387
3145933PARMELE
Solar/Wind Harmer
0.193
3150411LDYSMT5
50/50
38.405
3150381LDYSMT2
50/50
36.755
972213AH1-691 GEN
50/50
6.217
972215AH1-692 GEN
50/50
6.217
963051AG1-154 GEN
50/50
4.783
972189AH1-679 GEN
50/50
4.654
316312AB1-027
Solar/Wind Harmer
0.455
316233AE1-074 FULL
Solar/Wind Harmer
0.199
971281AH1-106 GEN
Solar/Wind Harmer
3.456
971283AH1-107 GEN
Solar/Wind Harmer
3.456
971285AH1-108 GEN
Adder
1.878
315976AC1-164 GENA
Solar/Wind Harmer
25.718
316169AC1-164_GENC
Solar/Wind Harmer
22.218
315975AC1-164 GENB
Solar/Wind Harmer
0.761
316132AB2-190 GEN1
Solar/Wind Harmer
1.305
316369SG1_INVT
Solar/Wind Harmer
0.009
316274AC1-208 GEN
Solar/Wind Harmer
0.996
971741AH1-377 GEN
Solar/Wind Harmer
18.605
970301AG2-198 GEN
Solar/Wind Harmer
7.883
939181AE1-148 GEN
Solar/Wind Harmer
8.803
3145493TOT1
Solar/Wind Harmer
0.424
3145453TOT5
Solar/Wind Harmer
0.255
3145603CNETO
Solar/Wind Harmer
0.17
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.013
970323AG2-213 GEN
Solar/Wind Harmer
7.695
971775AH1-396 GEN
Solar/Wind Harmer
0.289
961601AG1-000A GEN
Solar/Wind Harmer
3.194
316263AC1-034 GEN
Solar/Wind Harmer
6.824
958211AF2-115 GEN
Solar/Wind Harmer
2.148
963191AG1-168 GEN
Solar/Wind Harmer
0.716
3144293JTRSVLE
Adder
0.57
3144293JTRSVLE
Adder
0.48
3147133PAMPLIN
Solar/Wind Harmer
0.178
3147133PAMPLIN
Solar/Wind Harmer
0.143
962561AG1-105 GEN
Solar/Wind Harmer
8.357
964791AG1-342 GEN
Solar/Wind Harmer
3.316
3146843MT LREL
Solar/Wind Harmer
0.172
3146843MT LREL
Solar/Wind Harmer
0.172
3146776BUCKING
Solar/Wind Harmer
0.67
3146776BUCKING
Solar/Wind Harmer
0.054
316222AC1-221 GEN
Solar/Wind Harmer
0.627
971489AH1-241 GEN
Solar/Wind Harmer
7.9
315821AE2-092 GEN
Solar/Wind Harmer
0.008
942751AE2-291 GEN
Solar/Wind Harmer
6.989
316447AC1-158 HLD
Solar/Wind Helper
4.858
315651AD1-115 GEN
Solar/Wind Helper
0.961
971167AH1-042 GEN
Solar/Wind Harmer
21.453
3142433PROV 92
Adder
0.469
3142433PROV 92
Adder
0.469
972265AH1-717 GEN
Adder
18.63
3151201GRAVEL4
Adder
17.465
3151191GRAVEL3
Adder
17.243
3151211GRAVEL5
Adder
17.243
971445AH1-216 GEN
Solar/Wind Harmer
16.824
3143873LANEXA
Solar/Wind Harmer
0.143
3143316POE
Solar/Wind Harmer
0.945
3138283WHITEMARSH
Solar/Wind Harmer
0.055
316314AB2-024 C
Solar/Wind Harmer
0.001
3151081ELIZAR1
Adder
21.73
3151091ELIZAR2
Adder
21.353
3152611GOSPORTB
Adder
3.018
3152621GOSPORTC
Adder
2.561
3152601GOSPORTA
Adder
2.363
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
7.011
315662AE1-191 GEN
Solar/Wind Harmer
0.008
315666AE1-190 GEN
Solar/Wind Harmer
0.002
3141873WAN 176
Solar/Wind Harmer
0.047
957871AF2-081 GEN
Solar/Wind Harmer
11.676
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.161
316311AC2-079 GEN
Solar/Wind Harmer
6.724
319010AE1-072 C
Solar/Wind Harmer
1.178
3146406KITTY HAWK
Solar/Wind Harmer
0.029
316305AF2-043 C
Solar/Wind Harmer
0.002
315835AF2-110_GEN
Solar/Wind Harmer
1.595
3141913WHIT STONE
Solar/Wind Harmer
0.232
313526AB2-022
Solar/Wind Harmer
0.125
3138133OCRAN
Solar/Wind Harmer
0.069
3146486SUNBURY
Solar/Wind Harmer
0.231
3146486SUNBURY
Solar/Wind Harmer
0.231
316321Z2-027
Solar/Wind Harmer
0.043
3146396TANGLEW
Solar/Wind Harmer
0.635
3145176PASQUOTANK
Solar/Wind Harmer
0.143
3141783LANCAST
Solar/Wind Harmer
0.138
3141783LANCAST
Solar/Wind Harmer
0.092
962981AG1-147 GEN
Solar/Wind Harmer
8.47
316315AB2-025 C
Solar/Wind Harmer
0.183
941031AE2-094 GEN
Solar/Wind Harmer
41.622
944011AF1-069 GEN
Solar/Wind Harmer
13.599
315814AE2-033 C
Solar/Wind Harmer
17.851
970327AG2-215 GEN
Solar/Wind Harmer
7.386
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
970673AG2-436 GEN
Solar/Wind Harmer
47.408
970673AG2-436 GEN
Solar/Wind Harmer
31.605
3130156CHOWAN
Solar/Wind Harmer
0.222
3130156CHOWAN
Solar/Wind Harmer
0.222
971967AH1-528 GEN
Solar/Wind Harmer
35.12
315816AE2-034 GEN
Solar/Wind Harmer
0.932
3141813NORNECK
Solar/Wind Harmer
0.217
3130546PLYMOUTH
Solar/Wind Harmer
0.213
315732AD1-074 GEN1
Solar/Wind Harmer
1.221
315733AD1-074 GEN2
Solar/Wind Harmer
1.221
315735AD1-075 GEN1
Solar/Wind Harmer
0.611
965291AG1-394 GEN
Solar/Wind Harmer
0.939
3146206CASHIE
Solar/Wind Harmer
0.21
970601AG2-382 GEN
Solar/Wind Harmer
7.851
970085AG2-068 GEN
Solar/Wind Harmer
11.171
970581AG2-369 GEN
Solar/Wind Harmer
9.607
3145893MURPHYS
Solar/Wind Harmer
0.565
3145893MURPHYS
Solar/Wind Harmer
0.209
3145513AHOSKIE
Solar/Wind Harmer
0.431
3145513AHOSKIE
Solar/Wind Harmer
0.206
3145683EARLEYS
Solar/Wind Harmer
0.411
3145683EARLEYS
Solar/Wind Harmer
0.205
3145683EARLEYS
Solar/Wind Harmer
0.205
3146043SEABORD
Solar/Wind Harmer
0.205
315607AA1-063A GEN
Solar/Wind Harmer
0.417
316087AB2-174 GEN
Solar/Wind Harmer
0.006
315652AC1-086 GEN
Solar/Wind Harmer
22.128
3137643SOCKMAN
Solar/Wind Harmer
0.801
3145796HORNRTN
Solar/Wind Harmer
0.634
3145796HORNRTN
Solar/Wind Harmer
0.079
316223AC1-118
Solar/Wind Harmer
0.142
3146033SCOT NK
Solar/Wind Harmer
0.787
970831AG2-522 GEN
Solar/Wind Harmer
8.114
316005AA1-067
Solar/Wind Harmer
0.203
3145746EVERETS
Solar/Wind Harmer
0.753
3145746EVERETS
Solar/Wind Harmer
0.189
3145746EVERETS
Solar/Wind Harmer
0.189
3145746EVERETS
Solar/Wind Harmer
0.189
970181AG2-120 GEN
Solar/Wind Harmer
2.355
957861AF2-080 GEN
Solar/Wind Harmer
8.016
316420AA1-050 GEN
Solar/Wind Harmer
0.006
3145573BETHELC
Solar/Wind Harmer
0.183
3145573BETHELC
Solar/Wind Harmer
0.183
316319Z2-044 C
Solar/Wind Harmer
0
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
971443AH1-215 GEN
Solar/Wind Harmer
3.031
3144303KENBRDG
Solar/Wind Harmer
0.144
970683AG2-441 GEN
Solar/Wind Harmer
11.977
970681AG2-440 GEN
Solar/Wind Harmer
9.582
946301AF1-294 GEN
Solar/Wind Harmer
3.532
961791AG1-021 GEN
Solar/Wind Harmer
1.718
315657AE1-056 GEN
Solar/Wind Harmer
6.158
944491AF1-114 GEN
Solar/Wind Harmer
0.001
970285AG2-188 GEN
Solar/Wind Harmer
13.414
316118AC1-105 GEN
Solar/Wind Harmer
0.437
971845AH1-439 GEN
Solar/Wind Harmer
7.626
972193AH1-681 GEN
Adder
3.818
3147173SINAI
Solar/Wind Harmer
0.166
3147243WELCO
Solar/Wind Harmer
0.104
972205AH1-687 GEN
Adder
6.726
970865AG2-541 GEN
Solar/Wind Harmer
5.131
971447AH1-217 GEN
Solar/Wind Harmer
4.386
316123AC1-075 GEN
Solar/Wind Harmer
0.186
970165AG2-112 GEN
Solar/Wind Harmer
1.103
970163AG2-111 GEN
Solar/Wind Harmer
1.052
270494AE1-108_GEN
Solar/Wind Harmer
1.582
316164AC1-076 GEN
Solar/Wind Helper
1.947
316411AF1-147_GEN1
Solar/Wind Helper
0.8
316415AF1-147_GEN2
Solar/Wind Helper
0.8
3138216PACIFIC
Solar/Wind Helper
0.039
3152261N ANNA2
50/50
14.825
970497AG2-320 GEN
50/50
26.932
3150401LDYSMT4
50/50
38.285
3150371LDYSMT1
50/50
36.994
315051AA1-145 CT1
50/50
2.076
3142416OLDCHRC
Solar/Wind Harmer
2.465
970293AG2-193 GEN
Solar/Wind Harmer
2.678
3143096IRON208
Adder
1.045
3143096IRON208
Adder
1.024
3150861SPRUNCD
Adder
1.148
316473AC1-191 GEN
Solar/Wind Harmer
0.839
3142946ENON
Solar/Wind Harmer
0.083
970133AG2-095 GEN
Solar/Wind Harmer
2.349
316382AG1-145 C
Solar/Wind Harmer
0.002
970129AG2-093 GEN
Solar/Wind Harmer
14.714
315778AD1-151 GEN
Solar/Wind Harmer
19.405
965281AG1-393 GEN
Solar/Wind Harmer
2.587
315839AE2-212 C
Solar/Wind Harmer
0.002
3142433PROV 92
Adder
0.469
3142433PROV 92
Adder
0.469
3150921YORKTN3
Adder
6.055
3144216WINCHST
Adder
0.908
961611AG1-000B GEN
Solar/Wind Harmer
6.42
3151221GRAVEL6
Adder
17.444
3151171GRAVELC
Adder
3.356
315773AC2-141 GEN
Solar/Wind Harmer
8.761
3145336SMITFLD
Solar/Wind Harmer
0.096
315813AE1-149 C
Solar/Wind Harmer
12.736
3144536CHRHLND
Solar/Wind Harmer
0.035
970659AG2-427 GEN
Solar/Wind Harmer
2.51
944581AF1-123 GEN
Solar/Wind Harmer
53.367
944601AF1-125 GEN
Solar/Wind Harmer
52.545
3151101ELIZAR3
Adder
22.008
316083AB2-161 GEN
Solar/Wind Harmer
0.003
3144873MCLAUGH
Solar/Wind Harmer
0.006
3141766HARMONY
Solar/Wind Harmer
3.157
3141843SHACKLE
Adder
1.209
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
970661AG2-428 GEN
Solar/Wind Harmer
4.998
316280AD1-041 GEN
Solar/Wind Harmer
0.005
316156AD2-030 GEN
Solar/Wind Harmer
0.174
3141873WAN 176
Solar/Wind Harmer
4.175
3146456SLIGO L269
Solar/Wind Harmer
0.234
971153AH1-033 GEN
Solar/Wind Harmer
2.705
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.228
3146626S HERTFORD
Solar/Wind Harmer
0.227
962971AG1-146 GEN
Solar/Wind Harmer
3.63
3145273HOLLAND
Solar/Wind Harmer
0.17
970009AG2-005 GEN
Solar/Wind Harmer
1.68
3146376EDENTON
Solar/Wind Harmer
0.222
316404AE1-155 C
Solar/Wind Harmer
0.05
315614AA2-178 GEN
Solar/Wind Harmer
1.242
3150351NORNECKC2
Adder
2.198
971781AH1-399 GEN
Solar/Wind Harmer
0.285
971157AH1-035 GEN
Solar/Wind Harmer
2.559
315737AD1-076 GEN
Solar/Wind Harmer
2.735
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
316313AB2-026
Solar/Wind Harmer
0.134
316258AE1-075 C
Solar/Wind Harmer
0.16
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.201
970917AG2-570 GEN
Solar/Wind Harmer
18.693
3146206CASHIE
Solar/Wind Harmer
0.21
316365GEN2_N
Solar/Wind Harmer
0.471
3145893MURPHYS
Solar/Wind Harmer
0.35
3145893MURPHYS
Solar/Wind Harmer
0.209
957521AF2-046 GEN
Solar/Wind Harmer
15.533
961681AG1-008 GEN
Solar/Wind Harmer
15.533
3146173TUNIS
Solar/Wind Harmer
0.207
3156021HOLLOMANSOL
Solar/Wind Harmer
0.94
316463AE2-346 GEN
Solar/Wind Harmer
0.177
316140AB2-099
Solar/Wind Harmer
0.074
962331AG1-082 GEN
Solar/Wind Harmer
2.201
3146263WOODLND
Solar/Wind Harmer
0.204
3145963POPLR C
Solar/Wind Harmer
0.202
313506AB2-031 GEN
Solar/Wind Harmer
0.624
3142666NORTHAMPTON
Solar/Wind Harmer
0.202
316317KELFORD C
Solar/Wind Harmer
0.019
3145823KELFORD
Solar/Wind Harmer
0.201
3145796HORNRTN
Solar/Wind Harmer
0.792
3145796HORNRTN
Solar/Wind Harmer
0.198
3141906WESTMOR
Solar/Wind Harmer
0.079
3147043LAWRENC
Solar/Wind Harmer
0.118
316478AD1-087 GEN
Solar/Wind Harmer
0.676
316486AD2-202 GEN
Solar/Wind Harmer
0.198
316210AC1-098 GEN
Solar/Wind Harmer
1.795
3145933PARMELE
Solar/Wind Harmer
0.193
966801AG1-551 GEN
Solar/Wind Harmer
2.252
970737AG2-469 GEN
Solar/Wind Harmer
8.074
3145746EVERETS
Solar/Wind Harmer
0.189
3145746EVERETS
Solar/Wind Harmer
0.189
315724AD1-057 GEN
Solar/Wind Harmer
0.705
316327AA2-057 GEN
Solar/Wind Harmer
0.281
970909AG2-566 GEN
Solar/Wind Harmer
1.971
3146073TAR RVR
Solar/Wind Harmer
0.183
3146083TARBORO
Solar/Wind Harmer
0.183
3146233WITAKRS
Solar/Wind Harmer
0.919
3146233WITAKRS
Solar/Wind Harmer
0.124
3138543CONSLDL
Solar/Wind Harmer
0.12
3147666LOUISA
Solar/Wind Harmer
0.42
316131AB2-060 GEN
Solar/Wind Harmer
0.572
964241AG1-285 GEN
Solar/Wind Harmer
12.091
315785AD2-033 C
Solar/Wind Harmer
1.468
970257AG2-171 GEN
Solar/Wind Harmer
5.771
959311AF2-222 GEN
Solar/Wind Harmer
16.014
961601AG1-000A GEN
Solar/Wind Harmer
12.778
3145543BTLEBRO
Solar/Wind Harmer
0.179
3145543BTLEBRO
Solar/Wind Harmer
0.179
971623AH1-311 GEN
Solar/Wind Harmer
0.359
963181AG1-167 GEN
Solar/Wind Harmer
0.716
3144293JTRSVLE
Adder
0.57
3147133PAMPLIN
Solar/Wind Harmer
0.56
971193AH1-056 GEN
Solar/Wind Harmer
10.872
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.105
3146776BUCKING
Solar/Wind Harmer
0.06
972255AH1-712 GEN
Adder
85.454
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.086
971683AH1-343 GEN
Solar/Wind Harmer
5.663
316283AC2-100 C
Solar/Wind Harmer
0.294
970221AG2-151 GEN
Solar/Wind Harmer
7.9
3141316ARNOLDS
Adder
0.336
3150331BIRCHWDA
Adder
22.127
316044AC1-158 PL1
Solar/Wind Helper
2.207
316450AC1-158 RIC
Solar/Wind Helper
0.589
3141196NOKESVL
Solar/Wind Helper
1.25
316170AC1-121 GEN2
Solar/Wind Helper
0.431
3152251N ANNA1
50/50
14.826
972197AH1-683 GEN
50/50
5.978
972219AH1-694 GEN
50/50
4.304
315052AA1-145 CT2
50/50
2.085
966881AG1-559 GEN
Solar/Wind Harmer
0.307
3142416OLDCHRC
Solar/Wind Harmer
0.661
3142416OLDCHRC
Solar/Wind Harmer
0.253
3143096IRON208
Adder
1.045
3143526WINTERP
Solar/Wind Harmer
1.295
3150851SPRUNCC
Adder
1.148
3142543TWELFTH
Solar/Wind Harmer
0.024
3143226MDLTHAN
Solar/Wind Harmer
0.248
944631AF1-128 GEN
Adder
117.965
316159AE1-175 C
Solar/Wind Harmer
0.21
970129AG2-093 GEN
Solar/Wind Harmer
6.924
316458AB2-190 GEN2
Solar/Wind Harmer
1.305
315671AE2-027_GEN
Solar/Wind Harmer
15.554
971069AG2-661 GEN
Solar/Wind Harmer
4.312
971647AH1-324 GEN
Solar/Wind Harmer
10.299
971317AH1-138 GEN
Solar/Wind Harmer
1.8
3142433PROV 92
Solar/Wind Harmer
0.964
3142433PROV 92
Adder
0.469
3142433PROV 92
Adder
0.469
3138126ROCKLANDING
Solar/Wind Harmer
0.111
961611AG1-000B GEN
Solar/Wind Harmer
12.625
3151171GRAVELC
Adder
2.552
316294AC1-161 GEN
Solar/Wind Harmer
4.156
3145336SMITFLD
Solar/Wind Harmer
0.955
970659AG2-427 GEN
Solar/Wind Harmer
11.475
944591AF1-124 GEN
Solar/Wind Harmer
53.557
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
2.959
316381AD1-082 GEN
Solar/Wind Harmer
0.247
3141766HARMONY
Solar/Wind Harmer
0.047
971777AH1-397 GEN
Solar/Wind Harmer
0.625
3141843SHACKLE
Adder
1.209
970661AG2-428 GEN
Solar/Wind Harmer
23.497
316072AD1-144
Solar/Wind Harmer
0.085
939411AE1-173 GEN
Solar/Wind Harmer
100.291
316388AE2-253 GEN
Solar/Wind Harmer
0.736
940641AE2-051 GEN
Solar/Wind Harmer
18.777
3146456SLIGO L269
Solar/Wind Harmer
0.234
316246AF1-032 C
Solar/Wind Harmer
0.105
316093AE2-104_GEN
Solar/Wind Harmer
3.91
3138133OCRAN
Solar/Wind Harmer
0.139
3146516WINFALL
Solar/Wind Harmer
0.74
3146516WINFALL
Solar/Wind Harmer
0.228
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
962861AG1-135 GEN
Solar/Wind Harmer
7.133
3130156CHOWAN
Solar/Wind Harmer
0.222
3141726DUNNSVL
Solar/Wind Harmer
0.878
3145663CRESWEL
Solar/Wind Harmer
0.608
971163AH1-040 GEN
Solar/Wind Harmer
17.369
3150351NORNECKC2
Adder
2.162
3143336POWHATN
Solar/Wind Harmer
3.766
970919AG2-571 GEN
Solar/Wind Harmer
7.477
3146206CASHIE
Solar/Wind Harmer
0.21
971547AH1-271 GEN
Solar/Wind Harmer
4.486
316023GEN1_S
Solar/Wind Harmer
0.471
970087AG2-069 GEN
Solar/Wind Harmer
16.757
3145893MURPHYS
Solar/Wind Harmer
0.837
3145893MURPHYS
Solar/Wind Harmer
0.931
316337AD2-073 GEN
Solar/Wind Harmer
0.181
3146173TUNIS
Solar/Wind Harmer
0.207
3145683EARLEYS
Solar/Wind Harmer
0.205
960081AF2-299 GEN
Solar/Wind Harmer
1.959
3146263WOODLND
Solar/Wind Harmer
0.204
316336AC2-165 C
Solar/Wind Harmer
0.008
3145963POPLR C
Solar/Wind Harmer
0.202
316011AB1-132 GEN
Solar/Wind Harmer
3.658
962571AG1-106 GEN
Solar/Wind Harmer
2.862
3145823KELFORD
Solar/Wind Harmer
0.201
957481AF2-042 GEN
Solar/Wind Harmer
53.584
316174AB2-169 GEN
Solar/Wind Harmer
0.005
316190AA2-174 GEN
Solar/Wind Harmer
0
971795AH1-408 GEN
Solar/Wind Harmer
13.299
3145783HORNRTN
Solar/Wind Harmer
0.198
3145796HORNRTN
Solar/Wind Harmer
0.653
3145796HORNRTN
Solar/Wind Harmer
0.198
3147043LAWRENC
Adder
1.785
315693AD1-088 GEN
Solar/Wind Harmer
9.451
962491AG1-098 GEN
Solar/Wind Harmer
11.2
316212AC1-099_GEN
Solar/Wind Harmer
1.001
3146293MARTNCO
Solar/Wind Harmer
0.179
3145746EVERETS
Solar/Wind Harmer
0.189
3145746EVERETS
Solar/Wind Harmer
0.189
316129AC1-054 GEN
Solar/Wind Harmer
0.711
971065AG2-659 GEN
Solar/Wind Harmer
8.033
315722AD1-056 GEN
Solar/Wind Harmer
1.189
316494AC1-189 GEN
Solar/Wind Harmer
0.628
972135AH1-637 GEN
Solar/Wind Harmer
1.564
961671AG1-007 GEN
Solar/Wind Harmer
0.028
3146083TARBORO
Solar/Wind Harmer
0.183
3145493TOT1
Solar/Wind Harmer
0.814
3146233WITAKRS
Solar/Wind Harmer
0.728
315687AD1-152 GEN
Solar/Wind Harmer
0.006
3147666LOUISA
Solar/Wind Harmer
0.73
316237AB2-079_GEN
Solar/Wind Harmer
0.001
970685AG2-442 GEN
Solar/Wind Harmer
13.415
3145543BTLEBRO
Solar/Wind Harmer
0.179
3145543BTLEBRO
Solar/Wind Harmer
0.144
316359AB2-059 GEN
Solar/Wind Harmer
0.645
316049AB1-081 GEN
Solar/Wind Harmer
1.028
3142053HEARTS
Solar/Wind Harmer
0.316
963171AG1-166 GEN
Solar/Wind Harmer
0.955
971563AH1-280 GEN
Solar/Wind Harmer
1.909
3144293JTRSVLE
Adder
0.57
970937AG2-583 GEN
Solar/Wind Harmer
10.92
316192AB2-158 GEN
Solar/Wind Harmer
1.002
3146926FARMVIL
Solar/Wind Harmer
0.105
970401AG2-262 GEN
Solar/Wind Harmer
1.013
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.067
972277AH1-723 GEN
Adder
99.579
316003AC1-222 GEN
Solar/Wind Harmer
0.004
972003AH1-546 GEN
Solar/Wind Harmer
6.768
971377AH1-170 GEN
Solar/Wind Harmer
1.58
3147623JAMES R
Solar/Wind Harmer
0.343
316045AC1-158 PL2
Solar/Wind Helper
7.066
316006AB2-029 C
Solar/Wind Helper
0.145
316254AC1-120 GEN1
Solar/Wind Helper
1.294
NYPJM->LTFIMP_NY
CLTF
3.205
LGEELTFEXP_LGEE->PJM
CLTF
1.386
WECLTFEXP_WEC->PJM
CLTF
0.672
LAGNLTFEXP_LAGN->PJM
CLTF
8.214
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.425
TVALTFEXP_TVA->PJM
CLTF
4.163
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.47
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.182
MECLTFEXP_MEC->PJM
CLTF
3.753
SIGELTFEXP_SIGE->PJM
CLTF
0.114
CPLELTFEXP_CPLE->PJM
CLTF
11.58
CBM West 2LTFEXP_CBM-W2->PJM
CBM
42.571

Details for 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 594_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.64 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5073.15
MW Contribution:97.14
Bus #Bus NameTypeMW Contribution
3150391LDYSMT3
50/50
37.317
972195AH1-682 GEN
50/50
4.904
316447AC1-158 HLD
Solar/Wind Harmer
3.012
315673AE1-157 GEN
Solar/Wind Harmer
17.997
957411AF2-035 GEN
Solar/Wind Harmer
11.043
970317AG2-208 GEN
Solar/Wind Harmer
10.231
3142296MT RD221
Adder
0.795
3142366NRTHEST
Adder
0.798
3150691DARBY 3
Adder
17.546
3150701DARBY 4
Adder
17.506
3150681DARBY 2
Adder
17.485
3150671DARBY 1
Adder
17.465
316075AC2-137 C
Solar/Wind Harmer
0.066
966871AG1-558 GEN
Solar/Wind Harmer
0.278
3143526WINTERP
Solar/Wind Harmer
1.246
3142946ENON
Solar/Wind Harmer
0.024
971223AH1-071 GEN
Solar/Wind Harmer
2.54
944641AF1-129 GEN
Adder
112.782
316240AF1-291 C
Solar/Wind Harmer
0.002
316033AB2-134 GEN
Solar/Wind Harmer
0.014
315697AD1-025 GEN
Solar/Wind Harmer
0.263
316236AE1-162_GEN
Solar/Wind Harmer
0.002
316036AC1-147 C
Solar/Wind Harmer
0.042
3150991CHESPKB
Adder
2.391
3150991CHESPKB
Adder
2.334
970657AG2-426 GEN
Solar/Wind Harmer
7.988
970657AG2-426 GEN
Solar/Wind Harmer
1.675
316316AC1-027 C
Solar/Wind Harmer
0.219
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.006
3145506HICKORY
Solar/Wind Harmer
0.907
3145506HICKORY
Solar/Wind Harmer
0.544
3145506HICKORY
Solar/Wind Harmer
0.136
316339AD2-160 GEN
Solar/Wind Harmer
0.367
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
316017AA1-139 ULT1
Solar/Wind Harmer
0.126
3137176SLIGO L2192
Solar/Wind Harmer
0.897
3146456SLIGO L269
Solar/Wind Harmer
3.989
3130086AYDLETT
Solar/Wind Harmer
0.9
3146386ELIZ CT
Solar/Wind Harmer
0.223
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.22
3146516WINFALL
Solar/Wind Harmer
0.22
3146516WINFALL
Solar/Wind Harmer
0.22
3146626S HERTFORD
Solar/Wind Harmer
0.218
3146626S HERTFORD
Solar/Wind Harmer
0.218
3144356SAPONY
Solar/Wind Harmer
1.822
315742AE1-103 GEN
Solar/Wind Harmer
0.002
958261AF2-120 GEN
Solar/Wind Harmer
7.105
3146376EDENTON
Solar/Wind Harmer
0.951
3146376EDENTON
Solar/Wind Harmer
0.951
972185AH1-677 GEN
Adder
11.862
316468AD1-105 GEN
Solar/Wind Harmer
-0.068
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.197
3150341NORNECKC1
Adder
2.18
972187AH1-678 GEN
Adder
5.952
970933AG2-581 GEN
Solar/Wind Harmer
16.459
316065AD1-022 GEN
Solar/Wind Harmer
9.356
3145893MURPHYS
Solar/Wind Harmer
1.348
3145893MURPHYS
Solar/Wind Harmer
0.362
3146173TUNIS
Solar/Wind Harmer
0.199
3146173TUNIS
Solar/Wind Harmer
0.199
316181AB2-040 GEN
Solar/Wind Harmer
0.282
3142666NORTHAMPTON
Solar/Wind Harmer
0.194
3142666NORTHAMPTON
Solar/Wind Harmer
0.194
3142666NORTHAMPTON
Solar/Wind Harmer
0.194
3142666NORTHAMPTON
Solar/Wind Harmer
0.116
970099AG2-077 GEN
Solar/Wind Harmer
20.59
316426AA2-053 GEN
Solar/Wind Harmer
0.651
3145593CAROLNA
Solar/Wind Harmer
0.192
3145593CAROLNA
Solar/Wind Harmer
0.192
966811AG1-552 GEN
Solar/Wind Harmer
2.08
3145593CAROLNA
Solar/Wind Harmer
0.239
3150411LDYSMT5
50/50
37.503
3150381LDYSMT2
50/50
35.892
972213AH1-691 GEN
50/50
6.072
972215AH1-692 GEN
50/50
6.072
963051AG1-154 GEN
50/50
4.67
972189AH1-679 GEN
50/50
4.522
316312AB1-027
Solar/Wind Harmer
0.441
971285AH1-108 GEN
Adder
1.812
315976AC1-164 GENA
Solar/Wind Harmer
24.889
316169AC1-164_GENC
Solar/Wind Harmer
21.501
315975AC1-164 GENB
Solar/Wind Harmer
0.736
316233AE1-074 FULL
Solar/Wind Harmer
0.192
971281AH1-106 GEN
Solar/Wind Harmer
3.326
971283AH1-107 GEN
Solar/Wind Harmer
3.326
316132AB2-190 GEN1
Solar/Wind Harmer
1.26
971167AH1-042 GEN
Solar/Wind Harmer
20.74
316369SG1_INVT
Solar/Wind Harmer
0.009
3142433PROV 92
Adder
0.453
3142433PROV 92
Adder
0.453
972265AH1-717 GEN
Adder
17.968
3151201GRAVEL4
Adder
16.844
3151191GRAVEL3
Adder
16.63
3151211GRAVEL5
Adder
16.63
3143873LANEXA
Solar/Wind Harmer
0.139
971445AH1-216 GEN
Solar/Wind Harmer
16.22
316314AB2-024 C
Solar/Wind Harmer
0.001
3138283WHITEMARSH
Solar/Wind Harmer
0.053
3143316POE
Solar/Wind Harmer
0.91
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
6.779
3151081ELIZAR1
Adder
20.934
3151091ELIZAR2
Adder
20.57
3152611GOSPORTB
Adder
2.907
3152621GOSPORTC
Adder
2.467
3152601GOSPORTA
Adder
2.276
315662AE1-191 GEN
Solar/Wind Harmer
0.007
315666AE1-190 GEN
Solar/Wind Harmer
0.002
3141873WAN 176
Solar/Wind Harmer
0.045
957871AF2-081 GEN
Solar/Wind Harmer
11.247
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.155
316311AC2-079 GEN
Solar/Wind Harmer
6.478
319010AE1-072 C
Solar/Wind Harmer
1.135
3146406KITTY HAWK
Solar/Wind Harmer
0.028
316305AF2-043 C
Solar/Wind Harmer
0.002
3141913WHIT STONE
Solar/Wind Harmer
0.224
315835AF2-110_GEN
Solar/Wind Harmer
1.537
3138133OCRAN
Solar/Wind Harmer
0.067
313526AB2-022
Solar/Wind Harmer
0.121
3146486SUNBURY
Solar/Wind Harmer
0.222
3146486SUNBURY
Solar/Wind Harmer
0.222
3141783LANCAST
Solar/Wind Harmer
0.133
3141783LANCAST
Solar/Wind Harmer
0.089
316321Z2-027
Solar/Wind Harmer
0.041
3146396TANGLEW
Solar/Wind Harmer
0.612
3145176PASQUOTANK
Solar/Wind Harmer
0.138
962981AG1-147 GEN
Solar/Wind Harmer
8.191
316315AB2-025 C
Solar/Wind Harmer
0.176
970327AG2-215 GEN
Solar/Wind Harmer
7.143
315814AE2-033 C
Solar/Wind Harmer
17.164
941031AE2-094 GEN
Solar/Wind Harmer
39.927
944011AF1-069 GEN
Solar/Wind Harmer
13.046
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.214
3130156CHOWAN
Solar/Wind Harmer
0.214
970673AG2-436 GEN
Solar/Wind Harmer
45.48
970673AG2-436 GEN
Solar/Wind Harmer
30.32
971967AH1-528 GEN
Solar/Wind Harmer
33.699
3141813NORNECK
Solar/Wind Harmer
0.21
315816AE2-034 GEN
Solar/Wind Harmer
0.897
3130546PLYMOUTH
Solar/Wind Harmer
0.205
315732AD1-074 GEN1
Solar/Wind Harmer
1.176
315733AD1-074 GEN2
Solar/Wind Harmer
1.176
315735AD1-075 GEN1
Solar/Wind Harmer
0.588
965291AG1-394 GEN
Solar/Wind Harmer
0.904
3146206CASHIE
Solar/Wind Harmer
0.202
970601AG2-382 GEN
Solar/Wind Harmer
7.556
3145893MURPHYS
Solar/Wind Harmer
0.544
3145893MURPHYS
Solar/Wind Harmer
0.201
970085AG2-068 GEN
Solar/Wind Harmer
10.719
970581AG2-369 GEN
Solar/Wind Harmer
9.218
3145513AHOSKIE
Solar/Wind Harmer
0.415
3145513AHOSKIE
Solar/Wind Harmer
0.198
3145683EARLEYS
Solar/Wind Harmer
0.395
3145683EARLEYS
Solar/Wind Harmer
0.197
3145683EARLEYS
Solar/Wind Harmer
0.197
3146043SEABORD
Solar/Wind Harmer
0.197
315607AA1-063A GEN
Solar/Wind Harmer
0.401
316087AB2-174 GEN
Solar/Wind Harmer
0.006
315652AC1-086 GEN
Solar/Wind Harmer
21.282
3137643SOCKMAN
Solar/Wind Harmer
0.77
316223AC1-118
Solar/Wind Harmer
0.138
3145796HORNRTN
Solar/Wind Harmer
0.609
3145796HORNRTN
Solar/Wind Harmer
0.076
3146033SCOT NK
Solar/Wind Harmer
0.757
970831AG2-522 GEN
Solar/Wind Harmer
7.803
316005AA1-067
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.724
3145746EVERETS
Solar/Wind Harmer
0.182
3145746EVERETS
Solar/Wind Harmer
0.182
3145746EVERETS
Solar/Wind Harmer
0.182
970181AG2-120 GEN
Solar/Wind Harmer
2.265
957861AF2-080 GEN
Solar/Wind Harmer
7.708
316420AA1-050 GEN
Solar/Wind Harmer
0.006
3145573BETHELC
Solar/Wind Harmer
0.176
3145573BETHELC
Solar/Wind Harmer
0.176
316319Z2-044 C
Solar/Wind Harmer
0
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
971443AH1-215 GEN
Solar/Wind Harmer
2.92
3144303KENBRDG
Solar/Wind Harmer
0.139
970683AG2-441 GEN
Solar/Wind Harmer
11.546
970681AG2-440 GEN
Solar/Wind Harmer
9.237
946301AF1-294 GEN
Solar/Wind Harmer
3.407
961791AG1-021 GEN
Solar/Wind Harmer
1.657
315657AE1-056 GEN
Solar/Wind Harmer
5.941
944491AF1-114 GEN
Solar/Wind Harmer
0.001
970285AG2-188 GEN
Solar/Wind Harmer
12.999
971845AH1-439 GEN
Solar/Wind Harmer
7.393
972193AH1-681 GEN
Adder
3.724
316118AC1-105 GEN
Solar/Wind Harmer
0.42
3147173SINAI
Solar/Wind Harmer
0.16
3147243WELCO
Solar/Wind Harmer
0.1
972205AH1-687 GEN
Adder
6.548
970865AG2-541 GEN
Solar/Wind Harmer
4.934
971447AH1-217 GEN
Solar/Wind Harmer
4.275
316123AC1-075 GEN
Solar/Wind Harmer
0.179
970165AG2-112 GEN
Solar/Wind Harmer
1.061
970163AG2-111 GEN
Solar/Wind Harmer
1.012
270494AE1-108_GEN
Solar/Wind Harmer
1.539
316411AF1-147_GEN1
Solar/Wind Helper
0.785
316415AF1-147_GEN2
Solar/Wind Helper
0.785
3138216PACIFIC
Solar/Wind Helper
0.038
3152261N ANNA2
50/50
13.89
970497AG2-320 GEN
50/50
26.316
3150401LDYSMT4
50/50
37.387
3150371LDYSMT1
50/50
36.126
315051AA1-145 CT1
50/50
2.017
316044AC1-158 PL1
Solar/Wind Harmer
1.37
316450AC1-158 RIC
Solar/Wind Harmer
0.365
3142416OLDCHRC
Solar/Wind Harmer
2.389
970293AG2-193 GEN
Solar/Wind Harmer
2.592
3143096IRON208
Adder
1.01
3143096IRON208
Adder
0.989
316473AC1-191 GEN
Solar/Wind Harmer
0.814
3150861SPRUNCD
Adder
1.107
3142946ENON
Solar/Wind Harmer
0.08
970133AG2-095 GEN
Solar/Wind Harmer
2.267
316382AG1-145 C
Solar/Wind Harmer
0.002
970129AG2-093 GEN
Solar/Wind Harmer
14.202
315778AD1-151 GEN
Solar/Wind Harmer
18.726
965281AG1-393 GEN
Solar/Wind Harmer
2.495
315839AE2-212 C
Solar/Wind Harmer
0.002
3142433PROV 92
Adder
0.453
3142433PROV 92
Adder
0.453
3150921YORKTN3
Adder
5.845
3145783HORNRTN
Solar/Wind Harmer
3.389
3145783HORNRTN
Solar/Wind Harmer
2.711
3145783HORNRTN
Solar/Wind Harmer
0.847
3145783HORNRTN
Solar/Wind Harmer
0.339
3145796HORNRTN
Solar/Wind Harmer
0.571
3145933PARMELE
Solar/Wind Harmer
0.372
3145933PARMELE
Solar/Wind Harmer
0.186
316274AC1-208 GEN
Solar/Wind Harmer
0.958
971741AH1-377 GEN
Solar/Wind Harmer
17.929
970301AG2-198 GEN
Solar/Wind Harmer
7.603
939181AE1-148 GEN
Solar/Wind Harmer
8.466
3145493TOT1
Solar/Wind Harmer
0.408
3145453TOT5
Solar/Wind Harmer
0.245
3145603CNETO
Solar/Wind Harmer
0.163
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.013
970323AG2-213 GEN
Solar/Wind Harmer
7.414
971775AH1-396 GEN
Solar/Wind Harmer
0.278
961601AG1-000A GEN
Solar/Wind Harmer
3.071
958211AF2-115 GEN
Solar/Wind Harmer
2.072
963191AG1-168 GEN
Solar/Wind Harmer
0.691
3144293JTRSVLE
Adder
0.55
3144293JTRSVLE
Adder
0.463
316263AC1-034 GEN
Solar/Wind Harmer
6.56
3147133PAMPLIN
Solar/Wind Harmer
0.172
3147133PAMPLIN
Solar/Wind Harmer
0.138
962561AG1-105 GEN
Solar/Wind Harmer
8.039
964791AG1-342 GEN
Solar/Wind Harmer
3.189
3146843MT LREL
Solar/Wind Harmer
0.166
3146843MT LREL
Solar/Wind Harmer
0.166
3146776BUCKING
Solar/Wind Harmer
0.649
3146776BUCKING
Solar/Wind Harmer
0.053
316222AC1-221 GEN
Solar/Wind Harmer
0.603
971489AH1-241 GEN
Solar/Wind Harmer
7.696
315821AE2-092 GEN
Solar/Wind Harmer
0.008
942751AE2-291 GEN
Solar/Wind Harmer
6.723
3144216WINCHST
Adder
0.877
961611AG1-000B GEN
Solar/Wind Harmer
6.193
3151221GRAVEL6
Adder
16.824
3151171GRAVELC
Adder
3.237
315773AC2-141 GEN
Solar/Wind Harmer
8.441
3145336SMITFLD
Solar/Wind Harmer
0.092
315813AE1-149 C
Solar/Wind Harmer
12.273
3144536CHRHLND
Solar/Wind Harmer
0.034
3141766HARMONY
Solar/Wind Harmer
3.053
3141843SHACKLE
Adder
1.169
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
970659AG2-427 GEN
Solar/Wind Harmer
2.419
3151101ELIZAR3
Adder
21.202
944581AF1-123 GEN
Solar/Wind Harmer
51.405
944601AF1-125 GEN
Solar/Wind Harmer
50.613
316083AB2-161 GEN
Solar/Wind Harmer
0.003
3144873MCLAUGH
Solar/Wind Harmer
0.006
316280AD1-041 GEN
Solar/Wind Harmer
0.005
970661AG2-428 GEN
Solar/Wind Harmer
4.815
316156AD2-030 GEN
Solar/Wind Harmer
0.168
3141873WAN 176
Solar/Wind Harmer
4.037
3146456SLIGO L269
Solar/Wind Harmer
0.225
971153AH1-033 GEN
Solar/Wind Harmer
2.606
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.22
962971AG1-146 GEN
Solar/Wind Harmer
3.51
3146626S HERTFORD
Solar/Wind Harmer
0.218
3145273HOLLAND
Solar/Wind Harmer
0.163
970009AG2-005 GEN
Solar/Wind Harmer
1.625
316404AE1-155 C
Solar/Wind Harmer
0.048
3146376EDENTON
Solar/Wind Harmer
0.214
971781AH1-399 GEN
Solar/Wind Harmer
0.276
3150351NORNECKC2
Adder
2.127
315614AA2-178 GEN
Solar/Wind Harmer
1.196
971157AH1-035 GEN
Solar/Wind Harmer
2.463
315737AD1-076 GEN
Solar/Wind Harmer
2.632
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
316313AB2-026
Solar/Wind Harmer
0.129
316258AE1-075 C
Solar/Wind Harmer
0.154
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
3.087
3146206CASHIE
Solar/Wind Harmer
0.202
970917AG2-570 GEN
Solar/Wind Harmer
17.936
316365GEN2_N
Solar/Wind Harmer
0.453
3145893MURPHYS
Solar/Wind Harmer
0.337
3145893MURPHYS
Solar/Wind Harmer
0.201
957521AF2-046 GEN
Solar/Wind Harmer
14.949
961681AG1-008 GEN
Solar/Wind Harmer
14.949
3146173TUNIS
Solar/Wind Harmer
0.199
3156021HOLLOMANSOL
Solar/Wind Harmer
0.905
316463AE2-346 GEN
Solar/Wind Harmer
0.17
316140AB2-099
Solar/Wind Harmer
0.071
962331AG1-082 GEN
Solar/Wind Harmer
2.118
3146263WOODLND
Solar/Wind Harmer
0.196
3145963POPLR C
Solar/Wind Harmer
0.194
313506AB2-031 GEN
Solar/Wind Harmer
0.6
3142666NORTHAMPTON
Solar/Wind Harmer
0.194
316317KELFORD C
Solar/Wind Harmer
0.019
3145823KELFORD
Solar/Wind Harmer
0.193
3141906WESTMOR
Solar/Wind Harmer
0.077
3145796HORNRTN
Solar/Wind Harmer
0.762
3145796HORNRTN
Solar/Wind Harmer
0.19
3147043LAWRENC
Solar/Wind Harmer
0.114
316210AC1-098 GEN
Solar/Wind Harmer
1.726
316478AD1-087 GEN
Solar/Wind Harmer
0.649
316486AD2-202 GEN
Solar/Wind Harmer
0.191
3145933PARMELE
Solar/Wind Harmer
0.186
966801AG1-551 GEN
Solar/Wind Harmer
2.166
970737AG2-469 GEN
Solar/Wind Harmer
7.816
3145746EVERETS
Solar/Wind Harmer
0.182
3145746EVERETS
Solar/Wind Harmer
0.182
315724AD1-057 GEN
Solar/Wind Harmer
0.678
3147666LOUISA
Solar/Wind Harmer
0.412
316327AA2-057 GEN
Solar/Wind Harmer
0.27
970909AG2-566 GEN
Solar/Wind Harmer
1.901
3146073TAR RVR
Solar/Wind Harmer
0.176
3146083TARBORO
Solar/Wind Harmer
0.176
3146233WITAKRS
Solar/Wind Harmer
0.883
3146233WITAKRS
Solar/Wind Harmer
0.12
3138543CONSLDL
Solar/Wind Harmer
0.116
316131AB2-060 GEN
Solar/Wind Harmer
0.55
964241AG1-285 GEN
Solar/Wind Harmer
11.64
315785AD2-033 C
Solar/Wind Harmer
1.415
970257AG2-171 GEN
Solar/Wind Harmer
5.56
959311AF2-222 GEN
Solar/Wind Harmer
15.432
961601AG1-000A GEN
Solar/Wind Harmer
12.283
3145543BTLEBRO
Solar/Wind Harmer
0.172
3145543BTLEBRO
Solar/Wind Harmer
0.172
963181AG1-167 GEN
Solar/Wind Harmer
0.691
3144293JTRSVLE
Adder
0.55
971623AH1-311 GEN
Solar/Wind Harmer
0.345
3147133PAMPLIN
Solar/Wind Harmer
0.541
971193AH1-056 GEN
Solar/Wind Harmer
10.489
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.102
972255AH1-712 GEN
Adder
83.356
3146776BUCKING
Solar/Wind Harmer
0.058
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
6.812
971683AH1-343 GEN
Solar/Wind Harmer
5.445
316283AC2-100 C
Solar/Wind Harmer
0.283
970221AG2-151 GEN
Solar/Wind Harmer
7.696
3141316ARNOLDS
Adder
0.326
3150331BIRCHWDA
Adder
21.467
3141196NOKESVL
Solar/Wind Helper
1.224
3152251N ANNA1
50/50
13.891
972197AH1-683 GEN
50/50
5.838
972219AH1-694 GEN
50/50
4.203
315052AA1-145 CT2
50/50
2.026
316045AC1-158 PL2
Solar/Wind Harmer
4.381
966881AG1-559 GEN
Solar/Wind Harmer
0.299
3142416OLDCHRC
Solar/Wind Harmer
0.641
3142416OLDCHRC
Solar/Wind Harmer
0.245
3143096IRON208
Adder
1.01
3150851SPRUNCC
Adder
1.107
3142543TWELFTH
Solar/Wind Harmer
0.023
3143526WINTERP
Solar/Wind Harmer
1.246
944631AF1-128 GEN
Adder
114.018
3143226MDLTHAN
Solar/Wind Harmer
0.238
316159AE1-175 C
Solar/Wind Harmer
0.203
970129AG2-093 GEN
Solar/Wind Harmer
6.683
316458AB2-190 GEN2
Solar/Wind Harmer
1.26
315671AE2-027_GEN
Solar/Wind Harmer
15.005
971069AG2-661 GEN
Solar/Wind Harmer
4.161
3142433PROV 92
Solar/Wind Harmer
0.932
3142433PROV 92
Adder
0.453
3142433PROV 92
Adder
0.453
971647AH1-324 GEN
Solar/Wind Harmer
9.937
971317AH1-138 GEN
Solar/Wind Harmer
1.739
3138126ROCKLANDING
Solar/Wind Harmer
0.107
961611AG1-000B GEN
Solar/Wind Harmer
12.179
3151171GRAVELC
Adder
2.462
316294AC1-161 GEN
Solar/Wind Harmer
4.004
3145336SMITFLD
Solar/Wind Harmer
0.921
3141766HARMONY
Solar/Wind Harmer
0.046
971777AH1-397 GEN
Solar/Wind Harmer
0.604
3141843SHACKLE
Adder
1.169
970659AG2-427 GEN
Solar/Wind Harmer
11.057
944591AF1-124 GEN
Solar/Wind Harmer
51.588
316381AD1-082 GEN
Solar/Wind Harmer
0.238
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
2.851
970661AG2-428 GEN
Solar/Wind Harmer
22.639
316072AD1-144
Solar/Wind Harmer
0.082
316388AE2-253 GEN
Solar/Wind Harmer
0.708
939411AE1-173 GEN
Solar/Wind Harmer
96.357
3146456SLIGO L269
Solar/Wind Harmer
0.225
940641AE2-051 GEN
Solar/Wind Harmer
18.025
316246AF1-032 C
Solar/Wind Harmer
0.101
316093AE2-104_GEN
Solar/Wind Harmer
3.766
3138133OCRAN
Solar/Wind Harmer
0.134
3146516WINFALL
Solar/Wind Harmer
0.713
3146516WINFALL
Solar/Wind Harmer
0.22
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
962861AG1-135 GEN
Solar/Wind Harmer
6.899
3130156CHOWAN
Solar/Wind Harmer
0.214
3141726DUNNSVL
Solar/Wind Harmer
0.85
3150351NORNECKC2
Adder
2.092
3145663CRESWEL
Solar/Wind Harmer
0.585
971163AH1-040 GEN
Solar/Wind Harmer
16.721
3143336POWHATN
Solar/Wind Harmer
3.631
3146206CASHIE
Solar/Wind Harmer
0.202
971547AH1-271 GEN
Solar/Wind Harmer
4.318
970919AG2-571 GEN
Solar/Wind Harmer
7.174
316023GEN1_S
Solar/Wind Harmer
0.453
3145893MURPHYS
Solar/Wind Harmer
0.805
3145893MURPHYS
Solar/Wind Harmer
0.896
316337AD2-073 GEN
Solar/Wind Harmer
0.175
970087AG2-069 GEN
Solar/Wind Harmer
16.078
3146173TUNIS
Solar/Wind Harmer
0.199
3145683EARLEYS
Solar/Wind Harmer
0.197
960081AF2-299 GEN
Solar/Wind Harmer
1.885
3146263WOODLND
Solar/Wind Harmer
0.196
316336AC2-165 C
Solar/Wind Harmer
0.008
3145963POPLR C
Solar/Wind Harmer
0.194
316011AB1-132 GEN
Solar/Wind Harmer
3.518
962571AG1-106 GEN
Solar/Wind Harmer
2.753
3145823KELFORD
Solar/Wind Harmer
0.193
957481AF2-042 GEN
Solar/Wind Harmer
51.474
316174AB2-169 GEN
Solar/Wind Harmer
0.005
316190AA2-174 GEN
Solar/Wind Harmer
0
971795AH1-408 GEN
Solar/Wind Harmer
12.793
3145783HORNRTN
Solar/Wind Harmer
0.19
3145796HORNRTN
Solar/Wind Harmer
0.628
3145796HORNRTN
Solar/Wind Harmer
0.19
3147043LAWRENC
Adder
1.718
315693AD1-088 GEN
Solar/Wind Harmer
9.086
962491AG1-098 GEN
Solar/Wind Harmer
10.769
316212AC1-099_GEN
Solar/Wind Harmer
0.963
3146293MARTNCO
Solar/Wind Harmer
0.172
3145746EVERETS
Solar/Wind Harmer
0.182
3145746EVERETS
Solar/Wind Harmer
0.182
316129AC1-054 GEN
Solar/Wind Harmer
0.684
971065AG2-659 GEN
Solar/Wind Harmer
7.725
315722AD1-056 GEN
Solar/Wind Harmer
1.144
3147666LOUISA
Solar/Wind Harmer
0.717
316494AC1-189 GEN
Solar/Wind Harmer
0.604
972135AH1-637 GEN
Solar/Wind Harmer
1.514
961671AG1-007 GEN
Solar/Wind Harmer
0.027
3146083TARBORO
Solar/Wind Harmer
0.176
3145493TOT1
Solar/Wind Harmer
0.783
3146233WITAKRS
Solar/Wind Harmer
0.7
315687AD1-152 GEN
Solar/Wind Harmer
0.006
316237AB2-079_GEN
Solar/Wind Harmer
0.001
316192AB2-158 GEN
Solar/Wind Harmer
0.987
970685AG2-442 GEN
Solar/Wind Harmer
12.932
3145543BTLEBRO
Solar/Wind Harmer
0.172
3145543BTLEBRO
Solar/Wind Harmer
0.138
963171AG1-166 GEN
Solar/Wind Harmer
0.921
971563AH1-280 GEN
Solar/Wind Harmer
1.842
3144293JTRSVLE
Adder
0.55
316359AB2-059 GEN
Solar/Wind Harmer
0.62
316049AB1-081 GEN
Solar/Wind Harmer
0.988
3142053HEARTS
Solar/Wind Harmer
0.304
970937AG2-583 GEN
Solar/Wind Harmer
10.585
3146926FARMVIL
Solar/Wind Harmer
0.102
970401AG2-262 GEN
Solar/Wind Harmer
0.974
972277AH1-723 GEN
Adder
97.135
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.065
972003AH1-546 GEN
Solar/Wind Harmer
6.584
316003AC1-222 GEN
Solar/Wind Harmer
0.004
971377AH1-170 GEN
Solar/Wind Harmer
1.539
3147623JAMES R
Solar/Wind Harmer
0.334
316006AB2-029 C
Solar/Wind Helper
0.12
NYPJM->LTFIMP_NY
CLTF
3.157
LGEELTFEXP_LGEE->PJM
CLTF
1.303
WECLTFEXP_WEC->PJM
CLTF
0.629
LAGNLTFEXP_LAGN->PJM
CLTF
7.83
CBM South 2LTFEXP_CBM-S2->PJM
CBM
24.391
TVALTFEXP_TVA->PJM
CLTF
3.97
CBM West 1LTFEXP_CBM-W1->PJM
CBM
20.913
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.507
MECLTFEXP_MEC->PJM
CLTF
3.537
SIGELTFEXP_SIGE->PJM
CLTF
0.108
CPLELTFEXP_CPLE->PJM
CLTF
11.118
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.426

Details for 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: SPOTS H1T594_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.22 %
Rating:5011.0 MVA
Rating Type:C
MVA to Mitigate:5523.28
MW Contribution:98.54
Bus #Bus NameTypeMW Contribution
3150411LDYSMT5
50/50
38.145
3150381LDYSMT2
50/50
36.506
972213AH1-691 GEN
50/50
6.175
972215AH1-692 GEN
50/50
6.175
963051AG1-154 GEN
50/50
4.75
972189AH1-679 GEN
50/50
4.62
316312AB1-027
Solar/Wind Harmer
0.957
316233AE1-074 FULL
Solar/Wind Harmer
0.747
971281AH1-106 GEN
Solar/Wind Harmer
4.513
971283AH1-107 GEN
Solar/Wind Harmer
4.513
3150391LDYSMT3
50/50
37.955
972195AH1-682 GEN
50/50
4.988
316447AC1-158 HLD
Solar/Wind Harmer
7.651
315673AE1-157 GEN
Solar/Wind Harmer
22.335
957411AF2-035 GEN
Solar/Wind Harmer
13.337
970317AG2-208 GEN
Solar/Wind Harmer
12.967
3142296MT RD221
Adder
0.814
3142366NRTHEST
Adder
0.819
3150691DARBY 3
Adder
17.994
3150701DARBY 4
Adder
17.952
3150681DARBY 2
Adder
17.931
3150671DARBY 1
Adder
17.91
316075AC2-137 C
Solar/Wind Harmer
0.752
3143526WINTERP
Solar/Wind Harmer
-0.144
966871AG1-558 GEN
Solar/Wind Harmer
0.833
966871AG1-558 GEN
Solar/Wind Harmer
0.285
971223AH1-071 GEN
Solar/Wind Harmer
3.455
3142946ENON
Solar/Wind Harmer
-0.003
944641AF1-129 GEN
Adder
115.935
316240AF1-291 C
Solar/Wind Harmer
0.821
316033AB2-134 GEN
Solar/Wind Harmer
8.7
315697AD1-025 GEN
Solar/Wind Harmer
5.457
316236AE1-162_GEN
Solar/Wind Harmer
0.802
316036AC1-147 C
Solar/Wind Harmer
0.713
3150991CHESPKB
Adder
2.462
3150991CHESPKB
Adder
2.403
970657AG2-426 GEN
Solar/Wind Harmer
8.245
970657AG2-426 GEN
Solar/Wind Harmer
1.724
316441AF1-014 GEN
Solar/Wind Harmer
1.778
316316AC1-027 C
Solar/Wind Harmer
0.809
3142956BIRDNECK
Solar/Wind Harmer
1.414
316185AD1-033 GEN
Solar/Wind Harmer
2.777
3145506HICKORY
Solar/Wind Harmer
-0.105
3145506HICKORY
Solar/Wind Harmer
-0.063
3145506HICKORY
Solar/Wind Harmer
-0.016
316339AD2-160 GEN
Solar/Wind Harmer
1.765
316018AA1-139 ULT2
Solar/Wind Harmer
2.239
316017AA1-139 ULT1
Solar/Wind Harmer
2.115
3137176SLIGO L2192
Solar/Wind Harmer
-0.103
3146456SLIGO L269
Solar/Wind Harmer
3.081
3130086AYDLETT
Solar/Wind Harmer
-0.104
3146386ELIZ CT
Solar/Wind Harmer
-0.026
316431W1029_GEN1
Solar/Wind Harmer
4.626
316433W1029_GEN2
Solar/Wind Harmer
4.626
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3144356SAPONY
Solar/Wind Harmer
0.88
316487AF1-042 GEN
Solar/Wind Harmer
3.304
315742AE1-103 GEN
Solar/Wind Harmer
2.601
958261AF2-120 GEN
Solar/Wind Harmer
9.593
3146376EDENTON
Solar/Wind Harmer
0.734
3146376EDENTON
Solar/Wind Harmer
0.734
972185AH1-677 GEN
Adder
12.258
972187AH1-678 GEN
Adder
6.15
316077AC2-138 C
Solar/Wind Harmer
0.51
3150341NORNECKC1
Adder
2.253
3150341NORNECKC1
Adder
2.235
316468AD1-105 GEN
Solar/Wind Harmer
2.693
970933AG2-581 GEN
Solar/Wind Harmer
22.379
316065AD1-022 GEN
Solar/Wind Harmer
11.757
3145893MURPHYS
Solar/Wind Harmer
0.65
3145893MURPHYS
Solar/Wind Harmer
-0.042
3146173TUNIS
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.023
316181AB2-040 GEN
Solar/Wind Harmer
3.135
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
970099AG2-077 GEN
Solar/Wind Harmer
27.958
316426AA2-053 GEN
Solar/Wind Harmer
2.255
3145593CAROLNA
Solar/Wind Harmer
-0.022
3145593CAROLNA
Solar/Wind Harmer
-0.022
966811AG1-552 GEN
Solar/Wind Harmer
2.497
3145593CAROLNA
Solar/Wind Harmer
0.184
3145783HORNRTN
Solar/Wind Harmer
2.619
3145783HORNRTN
Solar/Wind Harmer
2.095
3145783HORNRTN
Solar/Wind Harmer
0.655
3145783HORNRTN
Solar/Wind Harmer
0.262
3145796HORNRTN
Solar/Wind Harmer
-0.066
3144293JTRSVLE
Adder
0.564
3144293JTRSVLE
Adder
0.475
315651AD1-115 GEN
Solar/Wind Helper
1.13
971285AH1-108 GEN
Adder
1.863
315976AC1-164 GENA
Solar/Wind Harmer
29.218
316169AC1-164_GENC
Solar/Wind Harmer
25.241
315975AC1-164 GENB
Solar/Wind Harmer
0.864
316132AB2-190 GEN1
Solar/Wind Harmer
2.743
316369SG1_INVT
Solar/Wind Harmer
4.82
971167AH1-042 GEN
Solar/Wind Harmer
25.921
3142433PROV 92
Adder
0.465
3142433PROV 92
Adder
0.465
972265AH1-717 GEN
Adder
18.482
3151201GRAVEL4
Adder
17.325
3151191GRAVEL3
Adder
17.106
3151211GRAVEL5
Adder
17.106
3143873LANEXA
Solar/Wind Harmer
-0.016
971445AH1-216 GEN
Solar/Wind Harmer
16.481
3143316POE
Solar/Wind Harmer
-0.105
957831AF2-077 GEN
Solar/Wind Harmer
0.798
3138283WHITEMARSH
Solar/Wind Harmer
0.041
316314AB2-024 C
Solar/Wind Harmer
2.267
3151081ELIZAR1
Adder
21.555
3151091ELIZAR2
Adder
21.18
3152611GOSPORTB
Adder
2.993
3152621GOSPORTC
Adder
2.54
3152601GOSPORTA
Adder
2.344
316059AD1-063 C
Solar/Wind Harmer
0.597
315662AE1-191 GEN
Solar/Wind Harmer
3.169
315666AE1-190 GEN
Solar/Wind Harmer
0.792
957601AF2-054 GEN
Solar/Wind Harmer
0.783
3141873WAN 176
Solar/Wind Harmer
-0.005
957871AF2-081 GEN
Solar/Wind Harmer
13.071
315833AF1-017_GEN
Solar/Wind Harmer
4.958
316349AD2-085 GEN
Solar/Wind Harmer
2.321
316311AC2-079 GEN
Solar/Wind Harmer
13.164
319010AE1-072 C
Solar/Wind Harmer
5.273
3146406KITTY HAWK
Solar/Wind Harmer
0.022
316305AF2-043 C
Solar/Wind Harmer
0.785
315835AF2-110_GEN
Solar/Wind Harmer
3.238
3141913WHIT STONE
Solar/Wind Harmer
-0.026
313526AB2-022
Solar/Wind Harmer
0.696
3138133OCRAN
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.026
3146486SUNBURY
Solar/Wind Harmer
-0.026
316321Z2-027
Solar/Wind Harmer
0.693
3146396TANGLEW
Solar/Wind Harmer
0.473
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
962981AG1-147 GEN
Solar/Wind Harmer
11.062
316315AB2-025 C
Solar/Wind Harmer
0.681
941031AE2-094 GEN
Solar/Wind Harmer
47.207
944011AF1-069 GEN
Solar/Wind Harmer
14.791
315814AE2-033 C
Solar/Wind Harmer
23.412
315611Z1-036_GEN2
Solar/Wind Harmer
6.192
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
970673AG2-436 GEN
Solar/Wind Harmer
52.007
970673AG2-436 GEN
Solar/Wind Harmer
26.333
971967AH1-528 GEN
Solar/Wind Harmer
45.964
315816AE2-034 GEN
Solar/Wind Harmer
1.957
3141813NORNECK
Solar/Wind Harmer
-0.024
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.788
315733AD1-074 GEN2
Solar/Wind Harmer
4.788
315735AD1-075 GEN1
Solar/Wind Harmer
2.395
965291AG1-394 GEN
Solar/Wind Harmer
2.088
3146206CASHIE
Solar/Wind Harmer
-0.023
970601AG2-382 GEN
Solar/Wind Harmer
10.247
970085AG2-068 GEN
Solar/Wind Harmer
14.579
970581AG2-369 GEN
Solar/Wind Harmer
12.538
316318V4-068
Solar/Wind Harmer
0.581
3145893MURPHYS
Solar/Wind Harmer
-0.063
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145513AHOSKIE
Solar/Wind Harmer
0.2
961941AG1-037 GEN
Solar/Wind Harmer
0.173
3145513AHOSKIE
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.045
3145683EARLEYS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
3146043SEABORD
Solar/Wind Harmer
-0.023
946281AF1-292 GEN
Solar/Wind Harmer
0.509
315607AA1-063A GEN
Solar/Wind Harmer
2.296
316087AB2-174 GEN
Solar/Wind Harmer
3.217
315652AC1-086 GEN
Solar/Wind Harmer
25.21
3137643SOCKMAN
Solar/Wind Harmer
-0.089
316223AC1-118
Solar/Wind Harmer
0.595
3145796HORNRTN
Solar/Wind Harmer
-0.07
3145796HORNRTN
Solar/Wind Harmer
-0.009
3146033SCOT NK
Solar/Wind Harmer
-0.087
972193AH1-681 GEN
Adder
3.778
972205AH1-687 GEN
Adder
6.629
316164AC1-076 GEN
Solar/Wind Helper
2.423
316411AF1-147_GEN1
Solar/Wind Helper
0.802
316415AF1-147_GEN2
Solar/Wind Helper
0.802
3138216PACIFIC
Solar/Wind Helper
0.039
3152261N ANNA2
50/50
14.719
970497AG2-320 GEN
50/50
26.757
3150401LDYSMT4
50/50
38.026
3150371LDYSMT1
50/50
36.744
315051AA1-145 CT1
50/50
2.061
316044AC1-158 PL1
Solar/Wind Harmer
3.479
316450AC1-158 RIC
Solar/Wind Harmer
0.928
966881AG1-559 GEN
Solar/Wind Harmer
0.891
3142416OLDCHRC
Solar/Wind Harmer
2.862
970293AG2-193 GEN
Solar/Wind Harmer
3.499
3143096IRON208
Adder
1.037
3143096IRON208
Adder
1.016
3150861SPRUNCD
Adder
1.139
316473AC1-191 GEN
Solar/Wind Harmer
2.981
3142946ENON
Solar/Wind Harmer
-0.009
970133AG2-095 GEN
Solar/Wind Harmer
3.068
316382AG1-145 C
Solar/Wind Harmer
0.819
970129AG2-093 GEN
Solar/Wind Harmer
15.278
315778AD1-151 GEN
Solar/Wind Harmer
23.422
965281AG1-393 GEN
Solar/Wind Harmer
3.379
315839AE2-212 C
Solar/Wind Harmer
0.814
3142433PROV 92
Adder
0.465
3142433PROV 92
Adder
0.465
3150921YORKTN3
Adder
6.008
3144216WINCHST
Adder
0.901
961611AG1-000B GEN
Solar/Wind Harmer
5.651
3151221GRAVEL6
Adder
17.305
3151171GRAVELC
Adder
3.329
315773AC2-141 GEN
Solar/Wind Harmer
11.187
3145336SMITFLD
Solar/Wind Harmer
-0.011
315813AE1-149 C
Solar/Wind Harmer
16.635
3144536CHRHLND
Solar/Wind Harmer
-0.004
970659AG2-427 GEN
Solar/Wind Harmer
2.49
944581AF1-123 GEN
Solar/Wind Harmer
120.168
944601AF1-125 GEN
Solar/Wind Harmer
118.293
3151101ELIZAR3
Adder
21.831
316083AB2-161 GEN
Solar/Wind Harmer
4.288
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3141766HARMONY
Solar/Wind Harmer
2.349
3141843SHACKLE
Adder
1.199
316203AE2-005 GEN
Solar/Wind Harmer
11.119
970661AG2-428 GEN
Solar/Wind Harmer
4.957
316280AD1-041 GEN
Solar/Wind Harmer
1.981
316156AD2-030 GEN
Solar/Wind Harmer
0.699
3141873WAN 176
Solar/Wind Harmer
3.107
3146456SLIGO L269
Solar/Wind Harmer
-0.026
971153AH1-033 GEN
Solar/Wind Harmer
3.18
316320Y1-086
Solar/Wind Harmer
1.512
316435W1029_GEN3
Solar/Wind Harmer
4.626
3146516WINFALL
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
962971AG1-146 GEN
Solar/Wind Harmer
4.741
3145273HOLLAND
Solar/Wind Harmer
-0.019
316484AD2-074 GEN
Solar/Wind Harmer
6.314
970009AG2-005 GEN
Solar/Wind Harmer
3.135
316404AE1-155 C
Solar/Wind Harmer
4.775
3146376EDENTON
Solar/Wind Harmer
-0.025
315614AA2-178 GEN
Solar/Wind Harmer
2.61
3150351NORNECKC2
Adder
2.18
971781AH1-399 GEN
Solar/Wind Harmer
1.49
971157AH1-035 GEN
Solar/Wind Harmer
2.97
315737AD1-076 GEN
Solar/Wind Harmer
4.5
3156081AA2-088 GEN
Solar/Wind Harmer
7.673
316313AB2-026
Solar/Wind Harmer
0.635
316258AE1-075 C
Solar/Wind Harmer
0.572
316405AF2-144 C
Solar/Wind Harmer
0.604
3143336POWHATN
Solar/Wind Harmer
2.377
3146206CASHIE
Solar/Wind Harmer
-0.023
970917AG2-570 GEN
Solar/Wind Harmer
58.551
316365GEN2_N
Solar/Wind Harmer
1.575
3145893MURPHYS
Solar/Wind Harmer
0.163
3145893MURPHYS
Solar/Wind Harmer
-0.023
957521AF2-046 GEN
Solar/Wind Harmer
18.311
961681AG1-008 GEN
Solar/Wind Harmer
18.311
3146173TUNIS
Solar/Wind Harmer
-0.023
3156021HOLLOMANSOL
Solar/Wind Harmer
3.107
316463AE2-346 GEN
Solar/Wind Harmer
0.372
316140AB2-099
Solar/Wind Harmer
0.155
962331AG1-082 GEN
Solar/Wind Harmer
2.872
966621AG1-532 GEN
Solar/Wind Harmer
0.461
3146263WOODLND
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.022
313506AB2-031 GEN
Solar/Wind Harmer
1.807
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
316317KELFORD C
Solar/Wind Harmer
1.056
3145823KELFORD
Solar/Wind Harmer
-0.022
3141906WESTMOR
Solar/Wind Harmer
-0.009
3145796HORNRTN
Solar/Wind Harmer
-0.088
3145796HORNRTN
Solar/Wind Harmer
-0.022
3147043LAWRENC
Solar/Wind Harmer
-0.013
316478AD1-087 GEN
Solar/Wind Harmer
1.866
316486AD2-202 GEN
Solar/Wind Harmer
0.546
3144293JTRSVLE
Adder
0.564
972255AH1-712 GEN
Adder
84.56
3141316ARNOLDS
Adder
0.333
3150331BIRCHWDA
Adder
21.898
316170AC1-121 GEN2
Solar/Wind Helper
0.522
3141196NOKESVL
Solar/Wind Helper
1.252
316210AC1-098 GEN
Solar/Wind Harmer
0.418
3152251N ANNA1
50/50
14.72
972197AH1-683 GEN
50/50
5.938
972219AH1-694 GEN
50/50
4.275
315052AA1-145 CT2
50/50
2.07
316045AC1-158 PL2
Solar/Wind Harmer
11.13
966881AG1-559 GEN
Solar/Wind Harmer
0.305
3142416OLDCHRC
Solar/Wind Harmer
-0.073
3142416OLDCHRC
Solar/Wind Harmer
-0.028
3143096IRON208
Adder
1.037
3143526WINTERP
Solar/Wind Harmer
-0.144
3150851SPRUNCC
Adder
1.139
3142543TWELFTH
Solar/Wind Harmer
-0.003
3143226MDLTHAN
Solar/Wind Harmer
-0.028
944631AF1-128 GEN
Adder
117.047
316159AE1-175 C
Solar/Wind Harmer
0.729
970129AG2-093 GEN
Solar/Wind Harmer
6.189
316458AB2-190 GEN2
Solar/Wind Harmer
2.743
315671AE2-027_GEN
Solar/Wind Harmer
20.317
971069AG2-661 GEN
Solar/Wind Harmer
4.278
971647AH1-324 GEN
Solar/Wind Harmer
13.453
971317AH1-138 GEN
Solar/Wind Harmer
3.36
3142433PROV 92
Solar/Wind Harmer
-0.107
3142433PROV 92
Adder
0.465
3142433PROV 92
Adder
0.465
3138126ROCKLANDING
Solar/Wind Harmer
0.082
961611AG1-000B GEN
Solar/Wind Harmer
13.243
3151171GRAVELC
Adder
2.532
316294AC1-161 GEN
Solar/Wind Harmer
8.649
3145336SMITFLD
Solar/Wind Harmer
-0.106
970659AG2-427 GEN
Solar/Wind Harmer
14.051
944591AF1-124 GEN
Solar/Wind Harmer
120.601
316375AC2-012 GEN
Solar/Wind Harmer
9.14
3150981CHESPKA
Adder
2.935
316381AD1-082 GEN
Solar/Wind Harmer
2.423
3141766HARMONY
Solar/Wind Harmer
-0.005
971777AH1-397 GEN
Solar/Wind Harmer
3.101
3141843SHACKLE
Adder
1.199
970661AG2-428 GEN
Solar/Wind Harmer
27.972
316072AD1-144
Solar/Wind Harmer
0.53
939411AE1-173 GEN
Solar/Wind Harmer
130.97
316388AE2-253 GEN
Solar/Wind Harmer
1.765
940641AE2-051 GEN
Solar/Wind Harmer
24.52
3146456SLIGO L269
Solar/Wind Harmer
-0.026
316246AF1-032 C
Solar/Wind Harmer
0.527
316093AE2-104_GEN
Solar/Wind Harmer
7.532
3138133OCRAN
Solar/Wind Harmer
-0.015
3146516WINFALL
Solar/Wind Harmer
-0.082
3146516WINFALL
Solar/Wind Harmer
-0.025
961951AG1-038 GEN
Solar/Wind Harmer
3.304
315800Z1-036_GEN1
Solar/Wind Harmer
6.192
962861AG1-135 GEN
Solar/Wind Harmer
9.316
3130156CHOWAN
Solar/Wind Harmer
-0.025
964211AG1-282 GEN
Solar/Wind Harmer
0.736
3141726DUNNSVL
Solar/Wind Harmer
-0.097
3145663CRESWEL
Solar/Wind Harmer
-0.067
971163AH1-040 GEN
Solar/Wind Harmer
22.675
3150351NORNECKC2
Adder
2.144
3143336POWHATN
Solar/Wind Harmer
2.796
3146206CASHIE
Solar/Wind Harmer
-0.023
971547AH1-271 GEN
Solar/Wind Harmer
5.856
970919AG2-571 GEN
Solar/Wind Harmer
7.412
316023GEN1_S
Solar/Wind Harmer
1.575
970087AG2-069 GEN
Solar/Wind Harmer
21.869
3145893MURPHYS
Solar/Wind Harmer
-0.093
3145893MURPHYS
Solar/Wind Harmer
0.692
316337AD2-073 GEN
Solar/Wind Harmer
0.622
3146173TUNIS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
960081AF2-299 GEN
Solar/Wind Harmer
2.557
3146263WOODLND
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.022
316336AC2-165 C
Solar/Wind Harmer
3.909
316011AB1-132 GEN
Solar/Wind Harmer
4.688
962571AG1-106 GEN
Solar/Wind Harmer
3.221
3145823KELFORD
Solar/Wind Harmer
-0.022
957481AF2-042 GEN
Solar/Wind Harmer
69.896
316174AB2-169 GEN
Solar/Wind Harmer
3.442
316190AA2-174 GEN
Solar/Wind Harmer
0.274
971795AH1-408 GEN
Solar/Wind Harmer
16.655
3145783HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.072
3145796HORNRTN
Solar/Wind Harmer
-0.022
3147043LAWRENC
Adder
1.769
315693AD1-088 GEN
Solar/Wind Harmer
10.955
962491AG1-098 GEN
Solar/Wind Harmer
14.605
3144293JTRSVLE
Adder
0.564
972277AH1-723 GEN
Adder
98.538
316254AC1-120 GEN1
Solar/Wind Helper
1.567
316006AB2-029 C
Solar/Wind Helper
0.151
316212AC1-099_GEN
Solar/Wind Harmer
0.232
NYPJM->LTFIMP_NY
CLTF
3.231
LGEELTFEXP_LGEE->PJM
CLTF
1.33
WECLTFEXP_WEC->PJM
CLTF
0.642
LAGNLTFEXP_LAGN->PJM
CLTF
8.031
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.091
TVALTFEXP_TVA->PJM
CLTF
4.071
CBM West 1LTFEXP_CBM-W1->PJM
CBM
21.339
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.845
MECLTFEXP_MEC->PJM
CLTF
3.617
SIGELTFEXP_SIGE->PJM
CLTF
0.11
CPLELTFEXP_CPLE->PJM
CLTF
11.449
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.416

Details for 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P4-2: 57302_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57302_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.51 %
Rating:5011.0 MVA
Rating Type:C
MVA to Mitigate:5437.63
MW Contribution:99.54
Bus #Bus NameTypeMW Contribution
3150391LDYSMT3
50/50
38.387
972195AH1-682 GEN
50/50
5.045
315673AE1-157 GEN
Solar/Wind Harmer
22.589
957411AF2-035 GEN
Solar/Wind Harmer
13.49
970317AG2-208 GEN
Solar/Wind Harmer
13.115
3142296MT RD221
Adder
0.824
3142366NRTHEST
Adder
0.828
3150691DARBY 3
Adder
18.207
3150701DARBY 4
Adder
18.165
3150681DARBY 2
Adder
18.143
3150671DARBY 1
Adder
18.122
316075AC2-137 C
Solar/Wind Harmer
0.761
3143526WINTERP
Solar/Wind Harmer
-0.145
966871AG1-558 GEN
Solar/Wind Harmer
0.843
966871AG1-558 GEN
Solar/Wind Harmer
0.288
971223AH1-071 GEN
Solar/Wind Harmer
3.498
3142946ENON
Solar/Wind Harmer
-0.003
944641AF1-129 GEN
Adder
117.349
316240AF1-291 C
Solar/Wind Harmer
0.831
316033AB2-134 GEN
Solar/Wind Harmer
8.807
315697AD1-025 GEN
Solar/Wind Harmer
5.524
316236AE1-162_GEN
Solar/Wind Harmer
0.812
316036AC1-147 C
Solar/Wind Harmer
0.721
3150991CHESPKB
Adder
2.493
3150991CHESPKB
Adder
2.433
970657AG2-426 GEN
Solar/Wind Harmer
8.348
970657AG2-426 GEN
Solar/Wind Harmer
1.746
316316AC1-027 C
Solar/Wind Harmer
0.819
316441AF1-014 GEN
Solar/Wind Harmer
1.799
3142956BIRDNECK
Solar/Wind Harmer
1.432
316185AD1-033 GEN
Solar/Wind Harmer
2.811
3145506HICKORY
Solar/Wind Harmer
-0.106
3145506HICKORY
Solar/Wind Harmer
-0.064
3145506HICKORY
Solar/Wind Harmer
-0.016
316339AD2-160 GEN
Solar/Wind Harmer
1.787
316018AA1-139 ULT2
Solar/Wind Harmer
2.267
316017AA1-139 ULT1
Solar/Wind Harmer
2.142
3137176SLIGO L2192
Solar/Wind Harmer
-0.105
3146456SLIGO L269
Solar/Wind Harmer
3.119
3130086AYDLETT
Solar/Wind Harmer
-0.105
3146386ELIZ CT
Solar/Wind Harmer
-0.026
316431W1029_GEN1
Solar/Wind Harmer
4.685
316433W1029_GEN2
Solar/Wind Harmer
4.685
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3144356SAPONY
Solar/Wind Harmer
0.891
316487AF1-042 GEN
Solar/Wind Harmer
3.345
315742AE1-103 GEN
Solar/Wind Harmer
2.634
958261AF2-120 GEN
Solar/Wind Harmer
9.714
3146376EDENTON
Solar/Wind Harmer
0.744
3146376EDENTON
Solar/Wind Harmer
0.744
972185AH1-677 GEN
Adder
12.419
972187AH1-678 GEN
Adder
6.23
316077AC2-138 C
Solar/Wind Harmer
0.516
3150341NORNECKC1
Adder
2.281
3150341NORNECKC1
Adder
2.263
316468AD1-105 GEN
Solar/Wind Harmer
2.727
970933AG2-581 GEN
Solar/Wind Harmer
22.667
316065AD1-022 GEN
Solar/Wind Harmer
11.908
3145893MURPHYS
Solar/Wind Harmer
0.659
3145893MURPHYS
Solar/Wind Harmer
-0.042
3146173TUNIS
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
316181AB2-040 GEN
Solar/Wind Harmer
3.176
970099AG2-077 GEN
Solar/Wind Harmer
28.311
316426AA2-053 GEN
Solar/Wind Harmer
2.284
3145593CAROLNA
Solar/Wind Harmer
-0.022
3145593CAROLNA
Solar/Wind Harmer
-0.022
966811AG1-552 GEN
Solar/Wind Harmer
2.529
3145593CAROLNA
Solar/Wind Harmer
0.187
3145783HORNRTN
Solar/Wind Harmer
2.652
3145783HORNRTN
Solar/Wind Harmer
2.122
3145783HORNRTN
Solar/Wind Harmer
0.663
3145783HORNRTN
Solar/Wind Harmer
0.265
3145796HORNRTN
Solar/Wind Harmer
-0.067
3150411LDYSMT5
50/50
38.579
3150381LDYSMT2
50/50
36.921
972213AH1-691 GEN
50/50
6.246
972215AH1-692 GEN
50/50
6.246
963051AG1-154 GEN
50/50
4.804
972189AH1-679 GEN
50/50
4.673
316312AB1-027
Solar/Wind Harmer
0.968
316233AE1-074 FULL
Solar/Wind Harmer
0.756
971281AH1-106 GEN
Solar/Wind Harmer
4.569
971283AH1-107 GEN
Solar/Wind Harmer
4.569
971285AH1-108 GEN
Adder
1.886
315976AC1-164 GENA
Solar/Wind Harmer
29.566
316169AC1-164_GENC
Solar/Wind Harmer
25.542
3145933PARMELE
Solar/Wind Harmer
-0.043
3145933PARMELE
Solar/Wind Harmer
-0.022
316274AC1-208 GEN
Solar/Wind Harmer
2.336
3144293JTRSVLE
Adder
0.57
3144293JTRSVLE
Adder
0.48
316447AC1-158 HLD
Solar/Wind Helper
4.863
315651AD1-115 GEN
Solar/Wind Helper
0.986
3152261N ANNA2
50/50
14.959
970497AG2-320 GEN
50/50
27.052
3150401LDYSMT4
50/50
38.459
3150371LDYSMT1
50/50
37.162
315051AA1-145 CT1
50/50
2.085
966881AG1-559 GEN
Solar/Wind Harmer
0.901
3142416OLDCHRC
Solar/Wind Harmer
2.895
970293AG2-193 GEN
Solar/Wind Harmer
3.54
3143096IRON208
Adder
1.049
3143096IRON208
Adder
1.028
3150861SPRUNCD
Adder
1.153
316473AC1-191 GEN
Solar/Wind Harmer
3.016
3142946ENON
Solar/Wind Harmer
-0.009
970133AG2-095 GEN
Solar/Wind Harmer
3.105
316382AG1-145 C
Solar/Wind Harmer
0.829
970129AG2-093 GEN
Solar/Wind Harmer
15.465
315778AD1-151 GEN
Solar/Wind Harmer
23.709
965281AG1-393 GEN
Solar/Wind Harmer
3.42
315839AE2-212 C
Solar/Wind Harmer
0.824
3142433PROV 92
Adder
0.47
3142433PROV 92
Adder
0.47
3150921YORKTN3
Adder
6.081
3144216WINCHST
Adder
0.912
961611AG1-000B GEN
Solar/Wind Harmer
5.72
3151221GRAVEL6
Adder
17.519
3151171GRAVELC
Adder
3.371
315773AC2-141 GEN
Solar/Wind Harmer
11.326
3145336SMITFLD
Solar/Wind Harmer
-0.011
315813AE1-149 C
Solar/Wind Harmer
16.842
3144536CHRHLND
Solar/Wind Harmer
-0.004
970659AG2-427 GEN
Solar/Wind Harmer
2.521
944581AF1-123 GEN
Solar/Wind Harmer
121.674
944601AF1-125 GEN
Solar/Wind Harmer
119.775
3151101ELIZAR3
Adder
22.104
316083AB2-161 GEN
Solar/Wind Harmer
4.341
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3141766HARMONY
Solar/Wind Harmer
2.378
3141843SHACKLE
Adder
1.214
316203AE2-005 GEN
Solar/Wind Harmer
11.255
970661AG2-428 GEN
Solar/Wind Harmer
5.019
316280AD1-041 GEN
Solar/Wind Harmer
2.005
316156AD2-030 GEN
Solar/Wind Harmer
0.708
3141873WAN 176
Solar/Wind Harmer
3.145
3146456SLIGO L269
Solar/Wind Harmer
-0.026
971153AH1-033 GEN
Solar/Wind Harmer
3.22
316320Y1-086
Solar/Wind Harmer
1.532
316435W1029_GEN3
Solar/Wind Harmer
4.685
3146516WINFALL
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
962971AG1-146 GEN
Solar/Wind Harmer
4.8
3145273HOLLAND
Solar/Wind Harmer
-0.019
316484AD2-074 GEN
Solar/Wind Harmer
6.393
970009AG2-005 GEN
Solar/Wind Harmer
3.175
316404AE1-155 C
Solar/Wind Harmer
4.836
3146376EDENTON
Solar/Wind Harmer
-0.025
315614AA2-178 GEN
Solar/Wind Harmer
2.643
3150351NORNECKC2
Adder
2.208
971781AH1-399 GEN
Solar/Wind Harmer
1.509
971157AH1-035 GEN
Solar/Wind Harmer
3.007
315737AD1-076 GEN
Solar/Wind Harmer
4.557
3156081AA2-088 GEN
Solar/Wind Harmer
7.771
316313AB2-026
Solar/Wind Harmer
0.642
316258AE1-075 C
Solar/Wind Harmer
0.578
316405AF2-144 C
Solar/Wind Harmer
0.61
3143336POWHATN
Solar/Wind Harmer
2.401
970917AG2-570 GEN
Solar/Wind Harmer
59.322
3146206CASHIE
Solar/Wind Harmer
-0.024
316365GEN2_N
Solar/Wind Harmer
1.596
3145893MURPHYS
Solar/Wind Harmer
0.165
3145893MURPHYS
Solar/Wind Harmer
-0.024
957521AF2-046 GEN
Solar/Wind Harmer
18.545
961681AG1-008 GEN
Solar/Wind Harmer
18.545
3146173TUNIS
Solar/Wind Harmer
-0.023
3156021HOLLOMANSOL
Solar/Wind Harmer
3.147
316463AE2-346 GEN
Solar/Wind Harmer
0.377
316140AB2-099
Solar/Wind Harmer
0.157
962331AG1-082 GEN
Solar/Wind Harmer
2.909
966621AG1-532 GEN
Solar/Wind Harmer
0.467
3146263WOODLND
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
313506AB2-031 GEN
Solar/Wind Harmer
1.83
316317KELFORD C
Solar/Wind Harmer
1.069
3145823KELFORD
Solar/Wind Harmer
-0.023
3141906WESTMOR
Solar/Wind Harmer
-0.009
3145796HORNRTN
Solar/Wind Harmer
-0.089
3145796HORNRTN
Solar/Wind Harmer
-0.022
3147043LAWRENC
Solar/Wind Harmer
-0.013
316478AD1-087 GEN
Solar/Wind Harmer
1.889
316486AD2-202 GEN
Solar/Wind Harmer
0.553
316210AC1-098 GEN
Solar/Wind Harmer
3.424
3145933PARMELE
Solar/Wind Harmer
-0.022
966801AG1-551 GEN
Solar/Wind Harmer
2.725
3144293JTRSVLE
Adder
0.57
972255AH1-712 GEN
Adder
85.42
3141316ARNOLDS
Adder
0.338
3150331BIRCHWDA
Adder
22.263
316044AC1-158 PL1
Solar/Wind Helper
2.209
316450AC1-158 RIC
Solar/Wind Helper
0.589
3141196NOKESVL
Solar/Wind Helper
1.25
316170AC1-121 GEN2
Solar/Wind Helper
0.444
315975AC1-164 GENB
Solar/Wind Harmer
0.875
316132AB2-190 GEN1
Solar/Wind Harmer
2.777
316369SG1_INVT
Solar/Wind Harmer
4.879
971167AH1-042 GEN
Solar/Wind Harmer
26.236
3142433PROV 92
Adder
0.47
3142433PROV 92
Adder
0.47
972265AH1-717 GEN
Adder
18.71
3151201GRAVEL4
Adder
17.539
3151191GRAVEL3
Adder
17.317
3151211GRAVEL5
Adder
17.317
971445AH1-216 GEN
Solar/Wind Harmer
16.686
3143873LANEXA
Solar/Wind Harmer
-0.016
3143316POE
Solar/Wind Harmer
-0.106
957831AF2-077 GEN
Solar/Wind Harmer
0.808
3138283WHITEMARSH
Solar/Wind Harmer
0.042
316314AB2-024 C
Solar/Wind Harmer
2.295
3151081ELIZAR1
Adder
21.824
3151091ELIZAR2
Adder
21.445
3152611GOSPORTB
Adder
3.031
3152621GOSPORTC
Adder
2.572
3152601GOSPORTA
Adder
2.373
316059AD1-063 C
Solar/Wind Harmer
0.604
315662AE1-191 GEN
Solar/Wind Harmer
3.208
315666AE1-190 GEN
Solar/Wind Harmer
0.802
957601AF2-054 GEN
Solar/Wind Harmer
0.793
3141873WAN 176
Solar/Wind Harmer
-0.005
957871AF2-081 GEN
Solar/Wind Harmer
13.235
315833AF1-017_GEN
Solar/Wind Harmer
5.02
316349AD2-085 GEN
Solar/Wind Harmer
2.351
316311AC2-079 GEN
Solar/Wind Harmer
13.329
319010AE1-072 C
Solar/Wind Harmer
5.339
3146406KITTY HAWK
Solar/Wind Harmer
0.022
316305AF2-043 C
Solar/Wind Harmer
0.795
315835AF2-110_GEN
Solar/Wind Harmer
3.279
3141913WHIT STONE
Solar/Wind Harmer
-0.026
313526AB2-022
Solar/Wind Harmer
0.705
3138133OCRAN
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.026
3146486SUNBURY
Solar/Wind Harmer
-0.026
316321Z2-027
Solar/Wind Harmer
0.702
3146396TANGLEW
Solar/Wind Harmer
0.479
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
962981AG1-147 GEN
Solar/Wind Harmer
11.2
316315AB2-025 C
Solar/Wind Harmer
0.689
941031AE2-094 GEN
Solar/Wind Harmer
47.824
944011AF1-069 GEN
Solar/Wind Harmer
14.985
315814AE2-033 C
Solar/Wind Harmer
23.711
315611Z1-036_GEN2
Solar/Wind Harmer
6.27
970673AG2-436 GEN
Solar/Wind Harmer
52.688
970673AG2-436 GEN
Solar/Wind Harmer
26.677
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
971967AH1-528 GEN
Solar/Wind Harmer
46.561
315816AE2-034 GEN
Solar/Wind Harmer
1.982
3141813NORNECK
Solar/Wind Harmer
-0.024
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.849
315733AD1-074 GEN2
Solar/Wind Harmer
4.849
315735AD1-075 GEN1
Solar/Wind Harmer
2.425
965291AG1-394 GEN
Solar/Wind Harmer
2.115
3146206CASHIE
Solar/Wind Harmer
-0.024
970601AG2-382 GEN
Solar/Wind Harmer
10.379
970085AG2-068 GEN
Solar/Wind Harmer
14.772
970581AG2-369 GEN
Solar/Wind Harmer
12.703
316318V4-068
Solar/Wind Harmer
0.588
3145893MURPHYS
Solar/Wind Harmer
-0.063
3145893MURPHYS
Solar/Wind Harmer
-0.024
3145513AHOSKIE
Solar/Wind Harmer
0.203
961941AG1-037 GEN
Solar/Wind Harmer
0.175
3145513AHOSKIE
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.046
3145683EARLEYS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
3146043SEABORD
Solar/Wind Harmer
-0.023
946281AF1-292 GEN
Solar/Wind Harmer
0.515
315607AA1-063A GEN
Solar/Wind Harmer
2.325
316087AB2-174 GEN
Solar/Wind Harmer
3.258
315652AC1-086 GEN
Solar/Wind Harmer
25.536
3137643SOCKMAN
Solar/Wind Harmer
-0.09
316223AC1-118
Solar/Wind Harmer
0.603
3145796HORNRTN
Solar/Wind Harmer
-0.071
3145796HORNRTN
Solar/Wind Harmer
-0.009
3146033SCOT NK
Solar/Wind Harmer
-0.088
972193AH1-681 GEN
Adder
3.817
972205AH1-687 GEN
Adder
6.664
316164AC1-076 GEN
Solar/Wind Helper
1.975
316411AF1-147_GEN1
Solar/Wind Helper
0.8
316415AF1-147_GEN2
Solar/Wind Helper
0.8
3138216PACIFIC
Solar/Wind Helper
0.039
970831AG2-522 GEN
Solar/Wind Harmer
4.393
3152251N ANNA1
50/50
14.961
972197AH1-683 GEN
50/50
6.005
972219AH1-694 GEN
50/50
4.324
315052AA1-145 CT2
50/50
2.094
966881AG1-559 GEN
Solar/Wind Harmer
0.308
3142416OLDCHRC
Solar/Wind Harmer
-0.074
3142416OLDCHRC
Solar/Wind Harmer
-0.028
3143096IRON208
Adder
1.049
3143526WINTERP
Solar/Wind Harmer
-0.145
3150851SPRUNCC
Adder
1.153
3142543TWELFTH
Solar/Wind Harmer
-0.003
3143226MDLTHAN
Solar/Wind Harmer
-0.028
944631AF1-128 GEN
Adder
118.454
316159AE1-175 C
Solar/Wind Harmer
0.738
970129AG2-093 GEN
Solar/Wind Harmer
6.264
316458AB2-190 GEN2
Solar/Wind Harmer
2.777
315671AE2-027_GEN
Solar/Wind Harmer
20.567
971069AG2-661 GEN
Solar/Wind Harmer
4.33
971647AH1-324 GEN
Solar/Wind Harmer
13.619
971317AH1-138 GEN
Solar/Wind Harmer
3.401
3142433PROV 92
Solar/Wind Harmer
-0.108
3142433PROV 92
Adder
0.47
3142433PROV 92
Adder
0.47
3138126ROCKLANDING
Solar/Wind Harmer
0.083
961611AG1-000B GEN
Solar/Wind Harmer
13.406
3151171GRAVELC
Adder
2.563
316294AC1-161 GEN
Solar/Wind Harmer
8.757
3145336SMITFLD
Solar/Wind Harmer
-0.107
970659AG2-427 GEN
Solar/Wind Harmer
14.226
944591AF1-124 GEN
Solar/Wind Harmer
122.112
316375AC2-012 GEN
Solar/Wind Harmer
9.255
3150981CHESPKA
Adder
2.972
316381AD1-082 GEN
Solar/Wind Harmer
2.453
3141766HARMONY
Solar/Wind Harmer
-0.005
971777AH1-397 GEN
Solar/Wind Harmer
3.139
3141843SHACKLE
Adder
1.214
970661AG2-428 GEN
Solar/Wind Harmer
28.322
316072AD1-144
Solar/Wind Harmer
0.537
939411AE1-173 GEN
Solar/Wind Harmer
132.654
316388AE2-253 GEN
Solar/Wind Harmer
1.787
940641AE2-051 GEN
Solar/Wind Harmer
24.838
3146456SLIGO L269
Solar/Wind Harmer
-0.026
316246AF1-032 C
Solar/Wind Harmer
0.534
316093AE2-104_GEN
Solar/Wind Harmer
7.627
3138133OCRAN
Solar/Wind Harmer
-0.015
3146516WINFALL
Solar/Wind Harmer
-0.083
3146516WINFALL
Solar/Wind Harmer
-0.026
961951AG1-038 GEN
Solar/Wind Harmer
3.345
315800Z1-036_GEN1
Solar/Wind Harmer
6.27
962861AG1-135 GEN
Solar/Wind Harmer
9.433
3130156CHOWAN
Solar/Wind Harmer
-0.025
964211AG1-282 GEN
Solar/Wind Harmer
0.745
3141726DUNNSVL
Solar/Wind Harmer
-0.099
3145663CRESWEL
Solar/Wind Harmer
-0.068
971163AH1-040 GEN
Solar/Wind Harmer
22.964
3150351NORNECKC2
Adder
2.172
3143336POWHATN
Solar/Wind Harmer
2.825
970919AG2-571 GEN
Solar/Wind Harmer
7.509
3146206CASHIE
Solar/Wind Harmer
-0.024
971547AH1-271 GEN
Solar/Wind Harmer
5.931
316023GEN1_S
Solar/Wind Harmer
1.596
970087AG2-069 GEN
Solar/Wind Harmer
22.157
3145893MURPHYS
Solar/Wind Harmer
-0.094
3145893MURPHYS
Solar/Wind Harmer
0.701
316337AD2-073 GEN
Solar/Wind Harmer
0.63
3146173TUNIS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
960081AF2-299 GEN
Solar/Wind Harmer
2.589
3146263WOODLND
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.023
316336AC2-165 C
Solar/Wind Harmer
3.947
316011AB1-132 GEN
Solar/Wind Harmer
4.749
962571AG1-106 GEN
Solar/Wind Harmer
3.263
3145823KELFORD
Solar/Wind Harmer
-0.023
957481AF2-042 GEN
Solar/Wind Harmer
70.778
316174AB2-169 GEN
Solar/Wind Harmer
3.486
316190AA2-174 GEN
Solar/Wind Harmer
0.278
971795AH1-408 GEN
Solar/Wind Harmer
16.865
3145783HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.073
3145796HORNRTN
Solar/Wind Harmer
-0.022
3147043LAWRENC
Adder
1.791
315693AD1-088 GEN
Solar/Wind Harmer
11.089
962491AG1-098 GEN
Solar/Wind Harmer
14.782
316212AC1-099_GEN
Solar/Wind Harmer
1.902
3146293MARTNCO
Solar/Wind Harmer
0.135
3144293JTRSVLE
Adder
0.57
972277AH1-723 GEN
Adder
99.54
316045AC1-158 PL2
Solar/Wind Helper
7.073
316006AB2-029 C
Solar/Wind Helper
0.147
316254AC1-120 GEN1
Solar/Wind Helper
1.333
NYPJM->LTFIMP_NY
CLTF
3.205
LGEELTFEXP_LGEE->PJM
CLTF
1.382
WECLTFEXP_WEC->PJM
CLTF
0.67
LAGNLTFEXP_LAGN->PJM
CLTF
8.217
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.482
TVALTFEXP_TVA->PJM
CLTF
4.164
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.391
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.181
MECLTFEXP_MEC->PJM
CLTF
3.746
SIGELTFEXP_SIGE->PJM
CLTF
0.114
CPLELTFEXP_CPLE->PJM
CLTF
11.613
CBM West 2LTFEXP_CBM-W2->PJM
CBM
42.551

Details for 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P4-2: XT573_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: XT573_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.51 %
Rating:5011.0 MVA
Rating Type:C
MVA to Mitigate:5437.5
MW Contribution:99.54
Bus #Bus NameTypeMW Contribution
3150391LDYSMT3
50/50
38.385
972195AH1-682 GEN
50/50
5.044
315673AE1-157 GEN
Solar/Wind Harmer
22.588
957411AF2-035 GEN
Solar/Wind Harmer
13.489
970317AG2-208 GEN
Solar/Wind Harmer
13.114
3142296MT RD221
Adder
0.823
3142366NRTHEST
Adder
0.828
3150691DARBY 3
Adder
18.206
3150701DARBY 4
Adder
18.164
3150681DARBY 2
Adder
18.143
3150671DARBY 1
Adder
18.121
316075AC2-137 C
Solar/Wind Harmer
0.761
3143526WINTERP
Solar/Wind Harmer
-0.145
966871AG1-558 GEN
Solar/Wind Harmer
0.843
966871AG1-558 GEN
Solar/Wind Harmer
0.288
971223AH1-071 GEN
Solar/Wind Harmer
3.498
3142946ENON
Solar/Wind Harmer
-0.003
944641AF1-129 GEN
Adder
117.344
316240AF1-291 C
Solar/Wind Harmer
0.831
316033AB2-134 GEN
Solar/Wind Harmer
8.807
315697AD1-025 GEN
Solar/Wind Harmer
5.523
316236AE1-162_GEN
Solar/Wind Harmer
0.812
316036AC1-147 C
Solar/Wind Harmer
0.721
3150991CHESPKB
Adder
2.493
3150991CHESPKB
Adder
2.433
970657AG2-426 GEN
Solar/Wind Harmer
8.347
970657AG2-426 GEN
Solar/Wind Harmer
1.746
316316AC1-027 C
Solar/Wind Harmer
0.819
316441AF1-014 GEN
Solar/Wind Harmer
1.799
3142956BIRDNECK
Solar/Wind Harmer
1.432
316185AD1-033 GEN
Solar/Wind Harmer
2.811
3145506HICKORY
Solar/Wind Harmer
-0.106
3145506HICKORY
Solar/Wind Harmer
-0.064
3145506HICKORY
Solar/Wind Harmer
-0.016
316339AD2-160 GEN
Solar/Wind Harmer
1.787
316018AA1-139 ULT2
Solar/Wind Harmer
2.267
316017AA1-139 ULT1
Solar/Wind Harmer
2.142
3137176SLIGO L2192
Solar/Wind Harmer
-0.105
3146456SLIGO L269
Solar/Wind Harmer
3.119
3130086AYDLETT
Solar/Wind Harmer
-0.105
3146386ELIZ CT
Solar/Wind Harmer
-0.026
316431W1029_GEN1
Solar/Wind Harmer
4.684
316433W1029_GEN2
Solar/Wind Harmer
4.684
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3144356SAPONY
Solar/Wind Harmer
0.891
316487AF1-042 GEN
Solar/Wind Harmer
3.345
315742AE1-103 GEN
Solar/Wind Harmer
2.633
958261AF2-120 GEN
Solar/Wind Harmer
9.713
3146376EDENTON
Solar/Wind Harmer
0.744
3146376EDENTON
Solar/Wind Harmer
0.744
972185AH1-677 GEN
Adder
12.418
972187AH1-678 GEN
Adder
6.23
316077AC2-138 C
Solar/Wind Harmer
0.516
3150341NORNECKC1
Adder
2.281
3150341NORNECKC1
Adder
2.263
316468AD1-105 GEN
Solar/Wind Harmer
2.727
970933AG2-581 GEN
Solar/Wind Harmer
22.666
316065AD1-022 GEN
Solar/Wind Harmer
11.907
3145893MURPHYS
Solar/Wind Harmer
0.659
3145893MURPHYS
Solar/Wind Harmer
-0.042
3146173TUNIS
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
316181AB2-040 GEN
Solar/Wind Harmer
3.175
970099AG2-077 GEN
Solar/Wind Harmer
28.31
316426AA2-053 GEN
Solar/Wind Harmer
2.283
3145593CAROLNA
Solar/Wind Harmer
-0.022
3145593CAROLNA
Solar/Wind Harmer
-0.022
966811AG1-552 GEN
Solar/Wind Harmer
2.529
3145593CAROLNA
Solar/Wind Harmer
0.187
3145783HORNRTN
Solar/Wind Harmer
2.652
3145783HORNRTN
Solar/Wind Harmer
2.122
3145783HORNRTN
Solar/Wind Harmer
0.663
3145783HORNRTN
Solar/Wind Harmer
0.265
3145796HORNRTN
Solar/Wind Harmer
-0.067
3145933PARMELE
Solar/Wind Harmer
-0.043
3145933PARMELE
Solar/Wind Harmer
-0.022
316274AC1-208 GEN
Solar/Wind Harmer
2.336
3144293JTRSVLE
Adder
0.57
3144293JTRSVLE
Adder
0.48
316447AC1-158 HLD
Solar/Wind Helper
4.863
315651AD1-115 GEN
Solar/Wind Helper
0.986
3152261N ANNA2
50/50
14.958
970497AG2-320 GEN
50/50
27.051
3150401LDYSMT4
50/50
38.457
3150371LDYSMT1
50/50
37.16
315051AA1-145 CT1
50/50
2.085
966881AG1-559 GEN
Solar/Wind Harmer
0.901
3142416OLDCHRC
Solar/Wind Harmer
2.895
970293AG2-193 GEN
Solar/Wind Harmer
3.54
3143096IRON208
Adder
1.049
3143096IRON208
Adder
1.028
3150861SPRUNCD
Adder
1.152
316473AC1-191 GEN
Solar/Wind Harmer
3.016
3142946ENON
Solar/Wind Harmer
-0.009
970133AG2-095 GEN
Solar/Wind Harmer
3.105
316382AG1-145 C
Solar/Wind Harmer
0.829
970129AG2-093 GEN
Solar/Wind Harmer
15.465
315778AD1-151 GEN
Solar/Wind Harmer
23.708
965281AG1-393 GEN
Solar/Wind Harmer
3.42
315839AE2-212 C
Solar/Wind Harmer
0.824
3142433PROV 92
Adder
0.47
3142433PROV 92
Adder
0.47
3150921YORKTN3
Adder
6.081
3144216WINCHST
Adder
0.912
961611AG1-000B GEN
Solar/Wind Harmer
5.72
3151221GRAVEL6
Adder
17.518
3151171GRAVELC
Adder
3.37
315773AC2-141 GEN
Solar/Wind Harmer
11.326
3145336SMITFLD
Solar/Wind Harmer
-0.011
315813AE1-149 C
Solar/Wind Harmer
16.841
3144536CHRHLND
Solar/Wind Harmer
-0.004
970659AG2-427 GEN
Solar/Wind Harmer
2.521
944581AF1-123 GEN
Solar/Wind Harmer
121.668
944601AF1-125 GEN
Solar/Wind Harmer
119.77
3151101ELIZAR3
Adder
22.103
316083AB2-161 GEN
Solar/Wind Harmer
4.341
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3141766HARMONY
Solar/Wind Harmer
2.378
3141843SHACKLE
Adder
1.214
316203AE2-005 GEN
Solar/Wind Harmer
11.254
970661AG2-428 GEN
Solar/Wind Harmer
5.019
316280AD1-041 GEN
Solar/Wind Harmer
2.005
316156AD2-030 GEN
Solar/Wind Harmer
0.708
3141873WAN 176
Solar/Wind Harmer
3.145
3146456SLIGO L269
Solar/Wind Harmer
-0.026
971153AH1-033 GEN
Solar/Wind Harmer
3.22
316320Y1-086
Solar/Wind Harmer
1.531
316435W1029_GEN3
Solar/Wind Harmer
4.684
3146516WINFALL
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
962971AG1-146 GEN
Solar/Wind Harmer
4.8
3145273HOLLAND
Solar/Wind Harmer
-0.019
316484AD2-074 GEN
Solar/Wind Harmer
6.393
970009AG2-005 GEN
Solar/Wind Harmer
3.174
316404AE1-155 C
Solar/Wind Harmer
4.835
3146376EDENTON
Solar/Wind Harmer
-0.025
315614AA2-178 GEN
Solar/Wind Harmer
2.643
3150351NORNECKC2
Adder
2.208
971781AH1-399 GEN
Solar/Wind Harmer
1.509
971157AH1-035 GEN
Solar/Wind Harmer
3.007
315737AD1-076 GEN
Solar/Wind Harmer
4.557
3156081AA2-088 GEN
Solar/Wind Harmer
7.771
316313AB2-026
Solar/Wind Harmer
0.642
316258AE1-075 C
Solar/Wind Harmer
0.578
316405AF2-144 C
Solar/Wind Harmer
0.61
3143336POWHATN
Solar/Wind Harmer
2.401
970917AG2-570 GEN
Solar/Wind Harmer
59.32
3146206CASHIE
Solar/Wind Harmer
-0.024
316365GEN2_N
Solar/Wind Harmer
1.596
3145893MURPHYS
Solar/Wind Harmer
0.165
3145893MURPHYS
Solar/Wind Harmer
-0.024
957521AF2-046 GEN
Solar/Wind Harmer
18.545
961681AG1-008 GEN
Solar/Wind Harmer
18.545
3146173TUNIS
Solar/Wind Harmer
-0.023
3156021HOLLOMANSOL
Solar/Wind Harmer
3.147
316463AE2-346 GEN
Solar/Wind Harmer
0.377
316140AB2-099
Solar/Wind Harmer
0.157
962331AG1-082 GEN
Solar/Wind Harmer
2.909
966621AG1-532 GEN
Solar/Wind Harmer
0.467
3146263WOODLND
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
313506AB2-031 GEN
Solar/Wind Harmer
1.83
316317KELFORD C
Solar/Wind Harmer
1.069
3145823KELFORD
Solar/Wind Harmer
-0.023
3141906WESTMOR
Solar/Wind Harmer
-0.009
3145796HORNRTN
Solar/Wind Harmer
-0.089
3145796HORNRTN
Solar/Wind Harmer
-0.022
3147043LAWRENC
Solar/Wind Harmer
-0.013
316478AD1-087 GEN
Solar/Wind Harmer
1.889
316486AD2-202 GEN
Solar/Wind Harmer
0.553
316210AC1-098 GEN
Solar/Wind Harmer
3.424
3145933PARMELE
Solar/Wind Harmer
-0.022
966801AG1-551 GEN
Solar/Wind Harmer
2.725
3144293JTRSVLE
Adder
0.57
972255AH1-712 GEN
Adder
85.421
3141316ARNOLDS
Adder
0.338
3150331BIRCHWDA
Adder
22.262
316044AC1-158 PL1
Solar/Wind Helper
2.209
316450AC1-158 RIC
Solar/Wind Helper
0.589
3141196NOKESVL
Solar/Wind Helper
1.25
316170AC1-121 GEN2
Solar/Wind Helper
0.444
3150411LDYSMT5
50/50
38.577
3150381LDYSMT2
50/50
36.92
972213AH1-691 GEN
50/50
6.245
972215AH1-692 GEN
50/50
6.245
963051AG1-154 GEN
50/50
4.804
972189AH1-679 GEN
50/50
4.673
316312AB1-027
Solar/Wind Harmer
0.968
316233AE1-074 FULL
Solar/Wind Harmer
0.756
971281AH1-106 GEN
Solar/Wind Harmer
4.569
971283AH1-107 GEN
Solar/Wind Harmer
4.569
971285AH1-108 GEN
Adder
1.886
315976AC1-164 GENA
Solar/Wind Harmer
29.565
316169AC1-164_GENC
Solar/Wind Harmer
25.541
315975AC1-164 GENB
Solar/Wind Harmer
0.875
316132AB2-190 GEN1
Solar/Wind Harmer
2.777
316369SG1_INVT
Solar/Wind Harmer
4.879
971167AH1-042 GEN
Solar/Wind Harmer
26.235
3142433PROV 92
Adder
0.47
3142433PROV 92
Adder
0.47
972265AH1-717 GEN
Adder
18.709
3151201GRAVEL4
Adder
17.539
3151191GRAVEL3
Adder
17.317
3151211GRAVEL5
Adder
17.317
971445AH1-216 GEN
Solar/Wind Harmer
16.685
3143873LANEXA
Solar/Wind Harmer
-0.016
3143316POE
Solar/Wind Harmer
-0.106
957831AF2-077 GEN
Solar/Wind Harmer
0.807
3138283WHITEMARSH
Solar/Wind Harmer
0.042
316314AB2-024 C
Solar/Wind Harmer
2.295
3151081ELIZAR1
Adder
21.824
3151091ELIZAR2
Adder
21.445
3152611GOSPORTB
Adder
3.031
3152621GOSPORTC
Adder
2.572
3152601GOSPORTA
Adder
2.373
316059AD1-063 C
Solar/Wind Harmer
0.604
315662AE1-191 GEN
Solar/Wind Harmer
3.208
315666AE1-190 GEN
Solar/Wind Harmer
0.802
957601AF2-054 GEN
Solar/Wind Harmer
0.793
3141873WAN 176
Solar/Wind Harmer
-0.005
957871AF2-081 GEN
Solar/Wind Harmer
13.234
315833AF1-017_GEN
Solar/Wind Harmer
5.02
316349AD2-085 GEN
Solar/Wind Harmer
2.35
316311AC2-079 GEN
Solar/Wind Harmer
13.328
319010AE1-072 C
Solar/Wind Harmer
5.338
3146406KITTY HAWK
Solar/Wind Harmer
0.022
316305AF2-043 C
Solar/Wind Harmer
0.795
315835AF2-110_GEN
Solar/Wind Harmer
3.279
3141913WHIT STONE
Solar/Wind Harmer
-0.026
313526AB2-022
Solar/Wind Harmer
0.705
3138133OCRAN
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.026
3146486SUNBURY
Solar/Wind Harmer
-0.026
316321Z2-027
Solar/Wind Harmer
0.702
3146396TANGLEW
Solar/Wind Harmer
0.479
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
962981AG1-147 GEN
Solar/Wind Harmer
11.2
316315AB2-025 C
Solar/Wind Harmer
0.689
941031AE2-094 GEN
Solar/Wind Harmer
47.822
944011AF1-069 GEN
Solar/Wind Harmer
14.984
315814AE2-033 C
Solar/Wind Harmer
23.71
315611Z1-036_GEN2
Solar/Wind Harmer
6.27
970673AG2-436 GEN
Solar/Wind Harmer
52.685
970673AG2-436 GEN
Solar/Wind Harmer
26.676
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
971967AH1-528 GEN
Solar/Wind Harmer
46.56
315816AE2-034 GEN
Solar/Wind Harmer
1.982
3141813NORNECK
Solar/Wind Harmer
-0.024
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.849
315733AD1-074 GEN2
Solar/Wind Harmer
4.849
315735AD1-075 GEN1
Solar/Wind Harmer
2.425
965291AG1-394 GEN
Solar/Wind Harmer
2.115
3146206CASHIE
Solar/Wind Harmer
-0.024
970601AG2-382 GEN
Solar/Wind Harmer
10.378
970085AG2-068 GEN
Solar/Wind Harmer
14.771
970581AG2-369 GEN
Solar/Wind Harmer
12.703
316318V4-068
Solar/Wind Harmer
0.588
3145893MURPHYS
Solar/Wind Harmer
-0.063
3145893MURPHYS
Solar/Wind Harmer
-0.024
3145513AHOSKIE
Solar/Wind Harmer
0.203
961941AG1-037 GEN
Solar/Wind Harmer
0.175
3145513AHOSKIE
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.046
3145683EARLEYS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
3146043SEABORD
Solar/Wind Harmer
-0.023
946281AF1-292 GEN
Solar/Wind Harmer
0.515
315607AA1-063A GEN
Solar/Wind Harmer
2.325
316087AB2-174 GEN
Solar/Wind Harmer
3.258
315652AC1-086 GEN
Solar/Wind Harmer
25.535
3137643SOCKMAN
Solar/Wind Harmer
-0.09
316223AC1-118
Solar/Wind Harmer
0.603
3145796HORNRTN
Solar/Wind Harmer
-0.071
3145796HORNRTN
Solar/Wind Harmer
-0.009
3146033SCOT NK
Solar/Wind Harmer
-0.088
972193AH1-681 GEN
Adder
3.817
972205AH1-687 GEN
Adder
6.664
316164AC1-076 GEN
Solar/Wind Helper
1.975
316411AF1-147_GEN1
Solar/Wind Helper
0.8
316415AF1-147_GEN2
Solar/Wind Helper
0.8
3138216PACIFIC
Solar/Wind Helper
0.039
970831AG2-522 GEN
Solar/Wind Harmer
4.393
3152251N ANNA1
50/50
14.959
972197AH1-683 GEN
50/50
6.005
972219AH1-694 GEN
50/50
4.324
315052AA1-145 CT2
50/50
2.094
966881AG1-559 GEN
Solar/Wind Harmer
0.308
3142416OLDCHRC
Solar/Wind Harmer
-0.074
3142416OLDCHRC
Solar/Wind Harmer
-0.028
3143096IRON208
Adder
1.049
3143526WINTERP
Solar/Wind Harmer
-0.145
3150851SPRUNCC
Adder
1.152
3142543TWELFTH
Solar/Wind Harmer
-0.003
3143226MDLTHAN
Solar/Wind Harmer
-0.028
944631AF1-128 GEN
Adder
118.449
316159AE1-175 C
Solar/Wind Harmer
0.738
970129AG2-093 GEN
Solar/Wind Harmer
6.264
316458AB2-190 GEN2
Solar/Wind Harmer
2.777
315671AE2-027_GEN
Solar/Wind Harmer
20.566
971069AG2-661 GEN
Solar/Wind Harmer
4.33
971647AH1-324 GEN
Solar/Wind Harmer
13.618
971317AH1-138 GEN
Solar/Wind Harmer
3.401
3142433PROV 92
Solar/Wind Harmer
-0.108
3142433PROV 92
Adder
0.47
3142433PROV 92
Adder
0.47
3138126ROCKLANDING
Solar/Wind Harmer
0.083
961611AG1-000B GEN
Solar/Wind Harmer
13.406
3151171GRAVELC
Adder
2.563
316294AC1-161 GEN
Solar/Wind Harmer
8.757
3145336SMITFLD
Solar/Wind Harmer
-0.107
970659AG2-427 GEN
Solar/Wind Harmer
14.225
944591AF1-124 GEN
Solar/Wind Harmer
122.107
316375AC2-012 GEN
Solar/Wind Harmer
9.254
3150981CHESPKA
Adder
2.972
316381AD1-082 GEN
Solar/Wind Harmer
2.453
3141766HARMONY
Solar/Wind Harmer
-0.005
971777AH1-397 GEN
Solar/Wind Harmer
3.139
3141843SHACKLE
Adder
1.214
970661AG2-428 GEN
Solar/Wind Harmer
28.32
316072AD1-144
Solar/Wind Harmer
0.537
939411AE1-173 GEN
Solar/Wind Harmer
132.648
316388AE2-253 GEN
Solar/Wind Harmer
1.787
940641AE2-051 GEN
Solar/Wind Harmer
24.837
3146456SLIGO L269
Solar/Wind Harmer
-0.026
316246AF1-032 C
Solar/Wind Harmer
0.534
316093AE2-104_GEN
Solar/Wind Harmer
7.627
3138133OCRAN
Solar/Wind Harmer
-0.015
3146516WINFALL
Solar/Wind Harmer
-0.083
3146516WINFALL
Solar/Wind Harmer
-0.026
961951AG1-038 GEN
Solar/Wind Harmer
3.345
315800Z1-036_GEN1
Solar/Wind Harmer
6.27
962861AG1-135 GEN
Solar/Wind Harmer
9.433
3130156CHOWAN
Solar/Wind Harmer
-0.025
964211AG1-282 GEN
Solar/Wind Harmer
0.745
3141726DUNNSVL
Solar/Wind Harmer
-0.099
3145663CRESWEL
Solar/Wind Harmer
-0.068
971163AH1-040 GEN
Solar/Wind Harmer
22.963
3150351NORNECKC2
Adder
2.172
3143336POWHATN
Solar/Wind Harmer
2.825
970919AG2-571 GEN
Solar/Wind Harmer
7.509
3146206CASHIE
Solar/Wind Harmer
-0.024
971547AH1-271 GEN
Solar/Wind Harmer
5.93
316023GEN1_S
Solar/Wind Harmer
1.596
970087AG2-069 GEN
Solar/Wind Harmer
22.156
3145893MURPHYS
Solar/Wind Harmer
-0.094
3145893MURPHYS
Solar/Wind Harmer
0.701
316337AD2-073 GEN
Solar/Wind Harmer
0.63
3146173TUNIS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
960081AF2-299 GEN
Solar/Wind Harmer
2.589
3146263WOODLND
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.023
316336AC2-165 C
Solar/Wind Harmer
3.947
316011AB1-132 GEN
Solar/Wind Harmer
4.749
962571AG1-106 GEN
Solar/Wind Harmer
3.263
3145823KELFORD
Solar/Wind Harmer
-0.023
957481AF2-042 GEN
Solar/Wind Harmer
70.776
316174AB2-169 GEN
Solar/Wind Harmer
3.486
316190AA2-174 GEN
Solar/Wind Harmer
0.278
971795AH1-408 GEN
Solar/Wind Harmer
16.865
3145783HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.073
3145796HORNRTN
Solar/Wind Harmer
-0.022
3147043LAWRENC
Adder
1.791
315693AD1-088 GEN
Solar/Wind Harmer
11.089
962491AG1-098 GEN
Solar/Wind Harmer
14.782
316212AC1-099_GEN
Solar/Wind Harmer
1.902
3146293MARTNCO
Solar/Wind Harmer
0.135
3144293JTRSVLE
Adder
0.57
972277AH1-723 GEN
Adder
99.541
316045AC1-158 PL2
Solar/Wind Helper
7.073
316006AB2-029 C
Solar/Wind Helper
0.147
316254AC1-120 GEN1
Solar/Wind Helper
1.332
NYPJM->LTFIMP_NY
CLTF
3.205
LGEELTFEXP_LGEE->PJM
CLTF
1.382
WECLTFEXP_WEC->PJM
CLTF
0.67
LAGNLTFEXP_LAGN->PJM
CLTF
8.217
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.481
TVALTFEXP_TVA->PJM
CLTF
4.164
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.392
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.181
MECLTFEXP_MEC->PJM
CLTF
3.747
SIGELTFEXP_SIGE->PJM
CLTF
0.114
CPLELTFEXP_CPLE->PJM
CLTF
11.613
CBM West 2LTFEXP_CBM-W2->PJM
CBM
42.552

Details for 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 515T573_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.24 %
Rating:5011.0 MVA
Rating Type:C
MVA to Mitigate:5423.67
MW Contribution:99.58
Bus #Bus NameTypeMW Contribution
3150391LDYSMT3
50/50
38.213
972195AH1-682 GEN
50/50
5.022
315673AE1-157 GEN
Solar/Wind Harmer
22.49
957411AF2-035 GEN
Solar/Wind Harmer
13.431
970317AG2-208 GEN
Solar/Wind Harmer
13.058
3142296MT RD221
Adder
0.82
3142366NRTHEST
Adder
0.825
3150691DARBY 3
Adder
18.133
3150701DARBY 4
Adder
18.091
3150681DARBY 2
Adder
18.07
3150671DARBY 1
Adder
18.049
316075AC2-137 C
Solar/Wind Harmer
0.758
3143526WINTERP
Solar/Wind Harmer
-0.145
966871AG1-558 GEN
Solar/Wind Harmer
0.839
966871AG1-558 GEN
Solar/Wind Harmer
0.287
971223AH1-071 GEN
Solar/Wind Harmer
3.483
3142946ENON
Solar/Wind Harmer
-0.003
944641AF1-129 GEN
Adder
116.855
316240AF1-291 C
Solar/Wind Harmer
0.828
316033AB2-134 GEN
Solar/Wind Harmer
8.77
315697AD1-025 GEN
Solar/Wind Harmer
5.5
316236AE1-162_GEN
Solar/Wind Harmer
0.809
316036AC1-147 C
Solar/Wind Harmer
0.718
3150991CHESPKB
Adder
2.482
3150991CHESPKB
Adder
2.423
970657AG2-426 GEN
Solar/Wind Harmer
8.312
970657AG2-426 GEN
Solar/Wind Harmer
1.738
316441AF1-014 GEN
Solar/Wind Harmer
1.792
316316AC1-027 C
Solar/Wind Harmer
0.816
3142956BIRDNECK
Solar/Wind Harmer
1.426
316185AD1-033 GEN
Solar/Wind Harmer
2.799
3145506HICKORY
Solar/Wind Harmer
-0.105
3145506HICKORY
Solar/Wind Harmer
-0.063
3145506HICKORY
Solar/Wind Harmer
-0.016
316339AD2-160 GEN
Solar/Wind Harmer
1.779
316018AA1-139 ULT2
Solar/Wind Harmer
2.258
316017AA1-139 ULT1
Solar/Wind Harmer
2.133
3137176SLIGO L2192
Solar/Wind Harmer
-0.104
3146456SLIGO L269
Solar/Wind Harmer
3.106
3130086AYDLETT
Solar/Wind Harmer
-0.105
3146386ELIZ CT
Solar/Wind Harmer
-0.026
316431W1029_GEN1
Solar/Wind Harmer
4.665
316433W1029_GEN2
Solar/Wind Harmer
4.665
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3144356SAPONY
Solar/Wind Harmer
0.888
316487AF1-042 GEN
Solar/Wind Harmer
3.331
315742AE1-103 GEN
Solar/Wind Harmer
2.623
3146376EDENTON
Solar/Wind Harmer
0.74
3146376EDENTON
Solar/Wind Harmer
0.74
958261AF2-120 GEN
Solar/Wind Harmer
9.671
972185AH1-677 GEN
Adder
12.364
972187AH1-678 GEN
Adder
6.203
316077AC2-138 C
Solar/Wind Harmer
0.514
3150341NORNECKC1
Adder
2.271
3150341NORNECKC1
Adder
2.253
316468AD1-105 GEN
Solar/Wind Harmer
2.715
970933AG2-581 GEN
Solar/Wind Harmer
22.578
316065AD1-022 GEN
Solar/Wind Harmer
11.86
3145893MURPHYS
Solar/Wind Harmer
0.656
3145893MURPHYS
Solar/Wind Harmer
-0.042
3146173TUNIS
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.023
316181AB2-040 GEN
Solar/Wind Harmer
3.164
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
970099AG2-077 GEN
Solar/Wind Harmer
28.221
316426AA2-053 GEN
Solar/Wind Harmer
2.275
3145593CAROLNA
Solar/Wind Harmer
-0.022
3145593CAROLNA
Solar/Wind Harmer
-0.022
966811AG1-552 GEN
Solar/Wind Harmer
2.52
3145593CAROLNA
Solar/Wind Harmer
0.186
3145783HORNRTN
Solar/Wind Harmer
2.643
3145783HORNRTN
Solar/Wind Harmer
2.114
3145783HORNRTN
Solar/Wind Harmer
0.661
3145783HORNRTN
Solar/Wind Harmer
0.264
3145796HORNRTN
Solar/Wind Harmer
-0.066
3145933PARMELE
Solar/Wind Harmer
-0.043
3145933PARMELE
Solar/Wind Harmer
-0.022
316274AC1-208 GEN
Solar/Wind Harmer
2.327
3144293JTRSVLE
Adder
0.57
3144293JTRSVLE
Adder
0.48
316447AC1-158 HLD
Solar/Wind Helper
4.858
315651AD1-115 GEN
Solar/Wind Helper
0.961
3152261N ANNA2
50/50
14.825
970497AG2-320 GEN
50/50
26.932
3150401LDYSMT4
50/50
38.285
3150371LDYSMT1
50/50
36.994
315051AA1-145 CT1
50/50
2.076
966881AG1-559 GEN
Solar/Wind Harmer
0.897
3142416OLDCHRC
Solar/Wind Harmer
2.884
970293AG2-193 GEN
Solar/Wind Harmer
3.526
3143096IRON208
Adder
1.045
3143096IRON208
Adder
1.024
3150861SPRUNCD
Adder
1.148
316473AC1-191 GEN
Solar/Wind Harmer
3.004
3142946ENON
Solar/Wind Harmer
-0.009
970133AG2-095 GEN
Solar/Wind Harmer
3.092
316382AG1-145 C
Solar/Wind Harmer
0.825
970129AG2-093 GEN
Solar/Wind Harmer
15.4
315778AD1-151 GEN
Solar/Wind Harmer
23.609
965281AG1-393 GEN
Solar/Wind Harmer
3.406
315839AE2-212 C
Solar/Wind Harmer
0.82
3142433PROV 92
Adder
0.469
3142433PROV 92
Adder
0.469
3150921YORKTN3
Adder
6.055
3144216WINCHST
Adder
0.908
961611AG1-000B GEN
Solar/Wind Harmer
5.696
3151221GRAVEL6
Adder
17.444
3151171GRAVELC
Adder
3.356
315773AC2-141 GEN
Solar/Wind Harmer
11.277
3145336SMITFLD
Solar/Wind Harmer
-0.011
315813AE1-149 C
Solar/Wind Harmer
16.769
3144536CHRHLND
Solar/Wind Harmer
-0.004
970659AG2-427 GEN
Solar/Wind Harmer
2.51
944581AF1-123 GEN
Solar/Wind Harmer
121.145
944601AF1-125 GEN
Solar/Wind Harmer
119.254
3151101ELIZAR3
Adder
22.008
316083AB2-161 GEN
Solar/Wind Harmer
4.322
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3141766HARMONY
Solar/Wind Harmer
2.368
3141843SHACKLE
Adder
1.209
316203AE2-005 GEN
Solar/Wind Harmer
11.207
970661AG2-428 GEN
Solar/Wind Harmer
4.998
316280AD1-041 GEN
Solar/Wind Harmer
1.996
316156AD2-030 GEN
Solar/Wind Harmer
0.705
3141873WAN 176
Solar/Wind Harmer
3.132
3146456SLIGO L269
Solar/Wind Harmer
-0.026
971153AH1-033 GEN
Solar/Wind Harmer
3.206
316320Y1-086
Solar/Wind Harmer
1.525
316435W1029_GEN3
Solar/Wind Harmer
4.665
3146516WINFALL
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.025
962971AG1-146 GEN
Solar/Wind Harmer
4.779
3145273HOLLAND
Solar/Wind Harmer
-0.019
316484AD2-074 GEN
Solar/Wind Harmer
6.366
970009AG2-005 GEN
Solar/Wind Harmer
3.161
3146376EDENTON
Solar/Wind Harmer
-0.025
316404AE1-155 C
Solar/Wind Harmer
4.814
315614AA2-178 GEN
Solar/Wind Harmer
2.632
3150351NORNECKC2
Adder
2.198
971781AH1-399 GEN
Solar/Wind Harmer
1.502
971157AH1-035 GEN
Solar/Wind Harmer
2.995
315737AD1-076 GEN
Solar/Wind Harmer
4.539
3156081AA2-088 GEN
Solar/Wind Harmer
7.74
316313AB2-026
Solar/Wind Harmer
0.642
316258AE1-075 C
Solar/Wind Harmer
0.578
316405AF2-144 C
Solar/Wind Harmer
0.61
3143336POWHATN
Solar/Wind Harmer
2.401
970917AG2-570 GEN
Solar/Wind Harmer
59.071
3146206CASHIE
Solar/Wind Harmer
-0.024
316365GEN2_N
Solar/Wind Harmer
1.589
3145893MURPHYS
Solar/Wind Harmer
0.164
3145893MURPHYS
Solar/Wind Harmer
-0.023
957521AF2-046 GEN
Solar/Wind Harmer
18.473
961681AG1-008 GEN
Solar/Wind Harmer
18.473
3146173TUNIS
Solar/Wind Harmer
-0.023
3156021HOLLOMANSOL
Solar/Wind Harmer
3.134
316463AE2-346 GEN
Solar/Wind Harmer
0.375
316140AB2-099
Solar/Wind Harmer
0.156
962331AG1-082 GEN
Solar/Wind Harmer
2.898
966621AG1-532 GEN
Solar/Wind Harmer
0.465
3146263WOODLND
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.023
313506AB2-031 GEN
Solar/Wind Harmer
1.823
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
316317KELFORD C
Solar/Wind Harmer
1.065
3145823KELFORD
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.089
3145796HORNRTN
Solar/Wind Harmer
-0.022
3141906WESTMOR
Solar/Wind Harmer
-0.009
3147043LAWRENC
Solar/Wind Harmer
-0.013
316478AD1-087 GEN
Solar/Wind Harmer
1.884
316486AD2-202 GEN
Solar/Wind Harmer
0.552
316210AC1-098 GEN
Solar/Wind Harmer
3.412
3145933PARMELE
Solar/Wind Harmer
-0.022
966801AG1-551 GEN
Solar/Wind Harmer
2.715
3144293JTRSVLE
Adder
0.57
972255AH1-712 GEN
Adder
85.454
3141316ARNOLDS
Adder
0.336
3150331BIRCHWDA
Adder
22.127
316044AC1-158 PL1
Solar/Wind Helper
2.207
316450AC1-158 RIC
Solar/Wind Helper
0.589
3141196NOKESVL
Solar/Wind Helper
1.25
316170AC1-121 GEN2
Solar/Wind Helper
0.431
3150411LDYSMT5
50/50
38.405
3150381LDYSMT2
50/50
36.755
972213AH1-691 GEN
50/50
6.217
972215AH1-692 GEN
50/50
6.217
963051AG1-154 GEN
50/50
4.783
972189AH1-679 GEN
50/50
4.654
316312AB1-027
Solar/Wind Harmer
0.964
316233AE1-074 FULL
Solar/Wind Harmer
0.753
971281AH1-106 GEN
Solar/Wind Harmer
4.55
971283AH1-107 GEN
Solar/Wind Harmer
4.55
971285AH1-108 GEN
Adder
1.878
315976AC1-164 GENA
Solar/Wind Harmer
29.445
316169AC1-164_GENC
Solar/Wind Harmer
25.437
315975AC1-164 GENB
Solar/Wind Harmer
0.871
316132AB2-190 GEN1
Solar/Wind Harmer
2.765
316369SG1_INVT
Solar/Wind Harmer
4.859
971167AH1-042 GEN
Solar/Wind Harmer
26.126
3142433PROV 92
Adder
0.469
3142433PROV 92
Adder
0.469
972265AH1-717 GEN
Adder
18.63
3151201GRAVEL4
Adder
17.465
3151191GRAVEL3
Adder
17.243
3151211GRAVEL5
Adder
17.243
971445AH1-216 GEN
Solar/Wind Harmer
16.614
3143873LANEXA
Solar/Wind Harmer
-0.016
3143316POE
Solar/Wind Harmer
-0.105
957831AF2-077 GEN
Solar/Wind Harmer
0.804
3138283WHITEMARSH
Solar/Wind Harmer
0.041
316314AB2-024 C
Solar/Wind Harmer
2.285
3151081ELIZAR1
Adder
21.73
3151091ELIZAR2
Adder
21.353
3152611GOSPORTB
Adder
3.018
3152621GOSPORTC
Adder
2.561
3152601GOSPORTA
Adder
2.363
316059AD1-063 C
Solar/Wind Harmer
0.601
315662AE1-191 GEN
Solar/Wind Harmer
3.194
315666AE1-190 GEN
Solar/Wind Harmer
0.799
957601AF2-054 GEN
Solar/Wind Harmer
0.789
3141873WAN 176
Solar/Wind Harmer
-0.005
957871AF2-081 GEN
Solar/Wind Harmer
13.177
315833AF1-017_GEN
Solar/Wind Harmer
4.998
316349AD2-085 GEN
Solar/Wind Harmer
2.341
316311AC2-079 GEN
Solar/Wind Harmer
13.272
319010AE1-072 C
Solar/Wind Harmer
5.316
3146406KITTY HAWK
Solar/Wind Harmer
0.022
316305AF2-043 C
Solar/Wind Harmer
0.791
315835AF2-110_GEN
Solar/Wind Harmer
3.265
3141913WHIT STONE
Solar/Wind Harmer
-0.026
313526AB2-022
Solar/Wind Harmer
0.702
3138133OCRAN
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.026
3146486SUNBURY
Solar/Wind Harmer
-0.026
316321Z2-027
Solar/Wind Harmer
0.699
3146396TANGLEW
Solar/Wind Harmer
0.477
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
962981AG1-147 GEN
Solar/Wind Harmer
11.152
316315AB2-025 C
Solar/Wind Harmer
0.686
941031AE2-094 GEN
Solar/Wind Harmer
47.608
944011AF1-069 GEN
Solar/Wind Harmer
14.917
315814AE2-033 C
Solar/Wind Harmer
23.609
315611Z1-036_GEN2
Solar/Wind Harmer
6.244
970673AG2-436 GEN
Solar/Wind Harmer
52.454
970673AG2-436 GEN
Solar/Wind Harmer
26.559
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
971967AH1-528 GEN
Solar/Wind Harmer
46.364
315816AE2-034 GEN
Solar/Wind Harmer
1.974
3141813NORNECK
Solar/Wind Harmer
-0.024
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.83
315733AD1-074 GEN2
Solar/Wind Harmer
4.83
315735AD1-075 GEN1
Solar/Wind Harmer
2.416
965291AG1-394 GEN
Solar/Wind Harmer
2.107
3146206CASHIE
Solar/Wind Harmer
-0.024
970601AG2-382 GEN
Solar/Wind Harmer
10.337
970085AG2-068 GEN
Solar/Wind Harmer
14.709
970581AG2-369 GEN
Solar/Wind Harmer
12.65
316318V4-068
Solar/Wind Harmer
0.586
3145893MURPHYS
Solar/Wind Harmer
-0.063
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145513AHOSKIE
Solar/Wind Harmer
0.202
961941AG1-037 GEN
Solar/Wind Harmer
0.174
3145513AHOSKIE
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.046
3145683EARLEYS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
3146043SEABORD
Solar/Wind Harmer
-0.023
946281AF1-292 GEN
Solar/Wind Harmer
0.514
315607AA1-063A GEN
Solar/Wind Harmer
2.316
316087AB2-174 GEN
Solar/Wind Harmer
3.247
315652AC1-086 GEN
Solar/Wind Harmer
25.438
3137643SOCKMAN
Solar/Wind Harmer
-0.09
3145796HORNRTN
Solar/Wind Harmer
-0.071
3145796HORNRTN
Solar/Wind Harmer
-0.009
316223AC1-118
Solar/Wind Harmer
0.6
3146033SCOT NK
Solar/Wind Harmer
-0.088
972193AH1-681 GEN
Adder
3.818
972205AH1-687 GEN
Adder
6.726
316164AC1-076 GEN
Solar/Wind Helper
1.947
316411AF1-147_GEN1
Solar/Wind Helper
0.8
316415AF1-147_GEN2
Solar/Wind Helper
0.8
3138216PACIFIC
Solar/Wind Helper
0.039
970831AG2-522 GEN
Solar/Wind Harmer
4.38
3152251N ANNA1
50/50
14.826
972197AH1-683 GEN
50/50
5.978
972219AH1-694 GEN
50/50
4.304
315052AA1-145 CT2
50/50
2.085
966881AG1-559 GEN
Solar/Wind Harmer
0.307
3142416OLDCHRC
Solar/Wind Harmer
-0.074
3142416OLDCHRC
Solar/Wind Harmer
-0.028
3143096IRON208
Adder
1.045
3143526WINTERP
Solar/Wind Harmer
-0.145
3150851SPRUNCC
Adder
1.148
3142543TWELFTH
Solar/Wind Harmer
-0.003
3143226MDLTHAN
Solar/Wind Harmer
-0.028
944631AF1-128 GEN
Adder
117.965
316159AE1-175 C
Solar/Wind Harmer
0.735
970129AG2-093 GEN
Solar/Wind Harmer
6.238
316458AB2-190 GEN2
Solar/Wind Harmer
2.765
315671AE2-027_GEN
Solar/Wind Harmer
20.479
971069AG2-661 GEN
Solar/Wind Harmer
4.312
971647AH1-324 GEN
Solar/Wind Harmer
13.561
971317AH1-138 GEN
Solar/Wind Harmer
3.386
3142433PROV 92
Solar/Wind Harmer
-0.108
3142433PROV 92
Adder
0.469
3142433PROV 92
Adder
0.469
3138126ROCKLANDING
Solar/Wind Harmer
0.083
961611AG1-000B GEN
Solar/Wind Harmer
13.349
3151171GRAVELC
Adder
2.552
316294AC1-161 GEN
Solar/Wind Harmer
8.719
3145336SMITFLD
Solar/Wind Harmer
-0.107
970659AG2-427 GEN
Solar/Wind Harmer
14.165
944591AF1-124 GEN
Solar/Wind Harmer
121.581
316375AC2-012 GEN
Solar/Wind Harmer
9.215
3150981CHESPKA
Adder
2.959
316381AD1-082 GEN
Solar/Wind Harmer
2.442
3141766HARMONY
Solar/Wind Harmer
-0.005
971777AH1-397 GEN
Solar/Wind Harmer
3.126
3141843SHACKLE
Adder
1.209
970661AG2-428 GEN
Solar/Wind Harmer
28.2
316072AD1-144
Solar/Wind Harmer
0.535
939411AE1-173 GEN
Solar/Wind Harmer
132.05
316388AE2-253 GEN
Solar/Wind Harmer
1.779
940641AE2-051 GEN
Solar/Wind Harmer
24.723
3146456SLIGO L269
Solar/Wind Harmer
-0.026
316246AF1-032 C
Solar/Wind Harmer
0.531
316093AE2-104_GEN
Solar/Wind Harmer
7.594
3138133OCRAN
Solar/Wind Harmer
-0.015
3146516WINFALL
Solar/Wind Harmer
-0.083
3146516WINFALL
Solar/Wind Harmer
-0.026
961951AG1-038 GEN
Solar/Wind Harmer
3.331
315800Z1-036_GEN1
Solar/Wind Harmer
6.244
962861AG1-135 GEN
Solar/Wind Harmer
9.392
3130156CHOWAN
Solar/Wind Harmer
-0.025
964211AG1-282 GEN
Solar/Wind Harmer
0.742
3141726DUNNSVL
Solar/Wind Harmer
-0.098
3145663CRESWEL
Solar/Wind Harmer
-0.068
971163AH1-040 GEN
Solar/Wind Harmer
22.869
3150351NORNECKC2
Adder
2.162
3143336POWHATN
Solar/Wind Harmer
2.825
970919AG2-571 GEN
Solar/Wind Harmer
7.477
3146206CASHIE
Solar/Wind Harmer
-0.024
971547AH1-271 GEN
Solar/Wind Harmer
5.907
316023GEN1_S
Solar/Wind Harmer
1.589
970087AG2-069 GEN
Solar/Wind Harmer
22.064
3145893MURPHYS
Solar/Wind Harmer
-0.094
3145893MURPHYS
Solar/Wind Harmer
0.698
316337AD2-073 GEN
Solar/Wind Harmer
0.628
3146173TUNIS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
960081AF2-299 GEN
Solar/Wind Harmer
2.58
3146263WOODLND
Solar/Wind Harmer
-0.023
316336AC2-165 C
Solar/Wind Harmer
3.951
3145963POPLR C
Solar/Wind Harmer
-0.023
316011AB1-132 GEN
Solar/Wind Harmer
4.731
962571AG1-106 GEN
Solar/Wind Harmer
3.25
3145823KELFORD
Solar/Wind Harmer
-0.023
957481AF2-042 GEN
Solar/Wind Harmer
70.553
316174AB2-169 GEN
Solar/Wind Harmer
3.473
316190AA2-174 GEN
Solar/Wind Harmer
0.277
971795AH1-408 GEN
Solar/Wind Harmer
16.81
3145783HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.073
3145796HORNRTN
Solar/Wind Harmer
-0.022
3147043LAWRENC
Adder
1.785
315693AD1-088 GEN
Solar/Wind Harmer
11.061
962491AG1-098 GEN
Solar/Wind Harmer
14.747
316212AC1-099_GEN
Solar/Wind Harmer
1.895
3146293MARTNCO
Solar/Wind Harmer
0.134
3144293JTRSVLE
Adder
0.57
972277AH1-723 GEN
Adder
99.579
316045AC1-158 PL2
Solar/Wind Helper
7.066
316006AB2-029 C
Solar/Wind Helper
0.145
316254AC1-120 GEN1
Solar/Wind Helper
1.294
NYPJM->LTFIMP_NY
CLTF
3.205
LGEELTFEXP_LGEE->PJM
CLTF
1.386
WECLTFEXP_WEC->PJM
CLTF
0.672
LAGNLTFEXP_LAGN->PJM
CLTF
8.214
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.425
TVALTFEXP_TVA->PJM
CLTF
4.163
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.47
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.182
MECLTFEXP_MEC->PJM
CLTF
3.753
SIGELTFEXP_SIGE->PJM
CLTF
0.114
CPLELTFEXP_CPLE->PJM
CLTF
11.58
CBM West 2LTFEXP_CBM-W2->PJM
CBM
42.571

Details for 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T573_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.86 %
Rating:5011.0 MVA
Rating Type:C
MVA to Mitigate:5404.77
MW Contribution:99.08
Bus #Bus NameTypeMW Contribution
3150391LDYSMT3
50/50
38.084
972195AH1-682 GEN
50/50
5.005
315673AE1-157 GEN
Solar/Wind Harmer
22.411
957411AF2-035 GEN
Solar/Wind Harmer
13.383
970317AG2-208 GEN
Solar/Wind Harmer
13.012
3142296MT RD221
Adder
0.817
3142366NRTHEST
Adder
0.822
3150691DARBY 3
Adder
18.059
3150701DARBY 4
Adder
18.017
3150681DARBY 2
Adder
17.996
3150671DARBY 1
Adder
17.975
316075AC2-137 C
Solar/Wind Harmer
0.755
3143526WINTERP
Solar/Wind Harmer
-0.144
966871AG1-558 GEN
Solar/Wind Harmer
0.836
966871AG1-558 GEN
Solar/Wind Harmer
0.286
971223AH1-071 GEN
Solar/Wind Harmer
3.468
3142946ENON
Solar/Wind Harmer
-0.003
944641AF1-129 GEN
Adder
116.369
316240AF1-291 C
Solar/Wind Harmer
0.824
316033AB2-134 GEN
Solar/Wind Harmer
8.733
315697AD1-025 GEN
Solar/Wind Harmer
5.477
316236AE1-162_GEN
Solar/Wind Harmer
0.805
3152261N ANNA2
50/50
14.761
970497AG2-320 GEN
50/50
26.842
3150401LDYSMT4
50/50
38.156
3150371LDYSMT1
50/50
36.869
315051AA1-145 CT1
50/50
2.068
966881AG1-559 GEN
Solar/Wind Harmer
0.894
3142416OLDCHRC
Solar/Wind Harmer
2.872
970293AG2-193 GEN
Solar/Wind Harmer
3.512
3143096IRON208
Adder
1.04
3143096IRON208
Adder
1.02
3150861SPRUNCD
Adder
1.143
316473AC1-191 GEN
Solar/Wind Harmer
2.992
3142946ENON
Solar/Wind Harmer
-0.009
970133AG2-095 GEN
Solar/Wind Harmer
3.08
316382AG1-145 C
Solar/Wind Harmer
0.822
970129AG2-093 GEN
Solar/Wind Harmer
15.336
315778AD1-151 GEN
Solar/Wind Harmer
23.511
965281AG1-393 GEN
Solar/Wind Harmer
3.392
315839AE2-212 C
Solar/Wind Harmer
0.817
3142433PROV 92
Adder
0.467
3142433PROV 92
Adder
0.467
3150921YORKTN3
Adder
6.03
3150411LDYSMT5
50/50
38.275
3150381LDYSMT2
50/50
36.631
972213AH1-691 GEN
50/50
6.196
972215AH1-692 GEN
50/50
6.196
963051AG1-154 GEN
50/50
4.767
972189AH1-679 GEN
50/50
4.636
316312AB1-027
Solar/Wind Harmer
0.96
316233AE1-074 FULL
Solar/Wind Harmer
0.75
971281AH1-106 GEN
Solar/Wind Harmer
4.53
971283AH1-107 GEN
Solar/Wind Harmer
4.53
971285AH1-108 GEN
Adder
1.87
315976AC1-164 GENA
Solar/Wind Harmer
29.326
316169AC1-164_GENC
Solar/Wind Harmer
25.335
315975AC1-164 GENB
Solar/Wind Harmer
0.868
316132AB2-190 GEN1
Solar/Wind Harmer
2.754
316369SG1_INVT
Solar/Wind Harmer
4.838
971167AH1-042 GEN
Solar/Wind Harmer
26.02
3142433PROV 92
Adder
0.467
3142433PROV 92
Adder
0.467
972265AH1-717 GEN
Adder
18.552
3151201GRAVEL4
Adder
17.392
3151191GRAVEL3
Adder
17.171
3151211GRAVEL5
Adder
17.171
3143873LANEXA
Solar/Wind Harmer
-0.016
971445AH1-216 GEN
Solar/Wind Harmer
16.544
3143316POE
Solar/Wind Harmer
-0.105
957831AF2-077 GEN
Solar/Wind Harmer
0.801
3138283WHITEMARSH
Solar/Wind Harmer
0.041
316314AB2-024 C
Solar/Wind Harmer
2.276
3151081ELIZAR1
Adder
21.638
3151091ELIZAR2
Adder
21.262
3152611GOSPORTB
Adder
3.005
3152621GOSPORTC
Adder
2.55
3152601GOSPORTA
Adder
2.353
316059AD1-063 C
Solar/Wind Harmer
0.599
315662AE1-191 GEN
Solar/Wind Harmer
3.181
315666AE1-190 GEN
Solar/Wind Harmer
0.795
957601AF2-054 GEN
Solar/Wind Harmer
0.786
3141873WAN 176
Solar/Wind Harmer
-0.005
957871AF2-081 GEN
Solar/Wind Harmer
13.122
315833AF1-017_GEN
Solar/Wind Harmer
4.977
316349AD2-085 GEN
Solar/Wind Harmer
2.331
316311AC2-079 GEN
Solar/Wind Harmer
13.215
319010AE1-072 C
Solar/Wind Harmer
5.293
3146406KITTY HAWK
Solar/Wind Harmer
0.022
316305AF2-043 C
Solar/Wind Harmer
0.788
315835AF2-110_GEN
Solar/Wind Harmer
3.251
3141913WHIT STONE
Solar/Wind Harmer
-0.026
313526AB2-022
Solar/Wind Harmer
0.699
3138133OCRAN
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.026
3146486SUNBURY
Solar/Wind Harmer
-0.026
316321Z2-027
Solar/Wind Harmer
0.696
3146396TANGLEW
Solar/Wind Harmer
0.475
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
962981AG1-147 GEN
Solar/Wind Harmer
11.107
316315AB2-025 C
Solar/Wind Harmer
0.683
941031AE2-094 GEN
Solar/Wind Harmer
47.398
944011AF1-069 GEN
Solar/Wind Harmer
14.851
315814AE2-033 C
Solar/Wind Harmer
23.507
315611Z1-036_GEN2
Solar/Wind Harmer
6.217
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
970673AG2-436 GEN
Solar/Wind Harmer
52.222
970673AG2-436 GEN
Solar/Wind Harmer
26.441
971967AH1-528 GEN
Solar/Wind Harmer
46.156
315816AE2-034 GEN
Solar/Wind Harmer
1.965
3141813NORNECK
Solar/Wind Harmer
-0.024
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.809
315733AD1-074 GEN2
Solar/Wind Harmer
4.809
315735AD1-075 GEN1
Solar/Wind Harmer
2.405
965291AG1-394 GEN
Solar/Wind Harmer
2.097
3146206CASHIE
Solar/Wind Harmer
-0.023
970601AG2-382 GEN
Solar/Wind Harmer
10.292
970085AG2-068 GEN
Solar/Wind Harmer
14.643
970581AG2-369 GEN
Solar/Wind Harmer
12.593
316318V4-068
Solar/Wind Harmer
0.584
3145893MURPHYS
Solar/Wind Harmer
-0.063
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145513AHOSKIE
Solar/Wind Harmer
0.201
961941AG1-037 GEN
Solar/Wind Harmer
0.173
3145513AHOSKIE
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.046
3145683EARLEYS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
3146043SEABORD
Solar/Wind Harmer
-0.023
946281AF1-292 GEN
Solar/Wind Harmer
0.511
315607AA1-063A GEN
Solar/Wind Harmer
2.306
316087AB2-174 GEN
Solar/Wind Harmer
3.232
315652AC1-086 GEN
Solar/Wind Harmer
25.325
3137643SOCKMAN
Solar/Wind Harmer
-0.089
316223AC1-118
Solar/Wind Harmer
0.598
3145796HORNRTN
Solar/Wind Harmer
-0.07
3145796HORNRTN
Solar/Wind Harmer
-0.009
3146033SCOT NK
Solar/Wind Harmer
-0.088
972193AH1-681 GEN
Adder
3.799
972205AH1-687 GEN
Adder
6.668
316164AC1-076 GEN
Solar/Wind Helper
2.414
316411AF1-147_GEN1
Solar/Wind Helper
0.796
316415AF1-147_GEN2
Solar/Wind Helper
0.796
3138216PACIFIC
Solar/Wind Helper
0.039
970831AG2-522 GEN
Solar/Wind Harmer
4.359
3144216WINCHST
Adder
0.904
961611AG1-000B GEN
Solar/Wind Harmer
5.672
3151221GRAVEL6
Adder
17.372
3151171GRAVELC
Adder
3.342
315773AC2-141 GEN
Solar/Wind Harmer
11.23
3145336SMITFLD
Solar/Wind Harmer
-0.011
315813AE1-149 C
Solar/Wind Harmer
16.699
3144536CHRHLND
Solar/Wind Harmer
-0.004
970659AG2-427 GEN
Solar/Wind Harmer
2.5
944581AF1-123 GEN
Solar/Wind Harmer
120.633
944601AF1-125 GEN
Solar/Wind Harmer
118.751
3151101ELIZAR3
Adder
21.915
316083AB2-161 GEN
Solar/Wind Harmer
4.304
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3141766HARMONY
Solar/Wind Harmer
2.358
3141843SHACKLE
Adder
1.204
316203AE2-005 GEN
Solar/Wind Harmer
11.162
970661AG2-428 GEN
Solar/Wind Harmer
4.976
316280AD1-041 GEN
Solar/Wind Harmer
1.988
316156AD2-030 GEN
Solar/Wind Harmer
0.702
3141873WAN 176
Solar/Wind Harmer
3.119
3146456SLIGO L269
Solar/Wind Harmer
-0.026
971153AH1-033 GEN
Solar/Wind Harmer
3.192
316320Y1-086
Solar/Wind Harmer
1.518
316435W1029_GEN3
Solar/Wind Harmer
4.645
3146516WINFALL
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
962971AG1-146 GEN
Solar/Wind Harmer
4.76
3145273HOLLAND
Solar/Wind Harmer
-0.019
316484AD2-074 GEN
Solar/Wind Harmer
6.34
970009AG2-005 GEN
Solar/Wind Harmer
3.148
316404AE1-155 C
Solar/Wind Harmer
4.795
3146376EDENTON
Solar/Wind Harmer
-0.025
315614AA2-178 GEN
Solar/Wind Harmer
2.621
3150351NORNECKC2
Adder
2.19
971781AH1-399 GEN
Solar/Wind Harmer
1.496
971157AH1-035 GEN
Solar/Wind Harmer
2.982
315737AD1-076 GEN
Solar/Wind Harmer
4.519
3156081AA2-088 GEN
Solar/Wind Harmer
7.706
316313AB2-026
Solar/Wind Harmer
0.638
316258AE1-075 C
Solar/Wind Harmer
0.575
316405AF2-144 C
Solar/Wind Harmer
0.606
3143336POWHATN
Solar/Wind Harmer
2.387
3146206CASHIE
Solar/Wind Harmer
-0.023
970917AG2-570 GEN
Solar/Wind Harmer
58.807
316365GEN2_N
Solar/Wind Harmer
1.582
3145893MURPHYS
Solar/Wind Harmer
0.163
3145893MURPHYS
Solar/Wind Harmer
-0.023
957521AF2-046 GEN
Solar/Wind Harmer
18.392
961681AG1-008 GEN
Solar/Wind Harmer
18.392
3146173TUNIS
Solar/Wind Harmer
-0.023
3156021HOLLOMANSOL
Solar/Wind Harmer
3.121
316463AE2-346 GEN
Solar/Wind Harmer
0.374
316140AB2-099
Solar/Wind Harmer
0.156
962331AG1-082 GEN
Solar/Wind Harmer
2.885
966621AG1-532 GEN
Solar/Wind Harmer
0.463
3146263WOODLND
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.023
313506AB2-031 GEN
Solar/Wind Harmer
1.815
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
316317KELFORD C
Solar/Wind Harmer
1.061
3145823KELFORD
Solar/Wind Harmer
-0.022
3141906WESTMOR
Solar/Wind Harmer
-0.009
3145796HORNRTN
Solar/Wind Harmer
-0.088
3145796HORNRTN
Solar/Wind Harmer
-0.022
3147043LAWRENC
Solar/Wind Harmer
-0.013
316478AD1-087 GEN
Solar/Wind Harmer
1.875
316486AD2-202 GEN
Solar/Wind Harmer
0.549
316210AC1-098 GEN
Solar/Wind Harmer
3.396
3145933PARMELE
Solar/Wind Harmer
-0.022
966801AG1-551 GEN
Solar/Wind Harmer
2.702
3144293JTRSVLE
Adder
0.566
972255AH1-712 GEN
Adder
85.026
3141316ARNOLDS
Adder
0.335
3150331BIRCHWDA
Adder
22.053
316044AC1-158 PL1
Solar/Wind Helper
2.142
316450AC1-158 RIC
Solar/Wind Helper
0.571
316170AC1-121 GEN2
Solar/Wind Helper
0.52
3141196NOKESVL
Solar/Wind Helper
1.245
316036AC1-147 C
Solar/Wind Harmer
0.715
3150991CHESPKB
Adder
2.472
3150991CHESPKB
Adder
2.412
970657AG2-426 GEN
Solar/Wind Harmer
8.277
970657AG2-426 GEN
Solar/Wind Harmer
1.731
316441AF1-014 GEN
Solar/Wind Harmer
1.785
316316AC1-027 C
Solar/Wind Harmer
0.812
3142956BIRDNECK
Solar/Wind Harmer
1.42
316185AD1-033 GEN
Solar/Wind Harmer
2.787
3145506HICKORY
Solar/Wind Harmer
-0.105
3145506HICKORY
Solar/Wind Harmer
-0.063
3145506HICKORY
Solar/Wind Harmer
-0.016
316339AD2-160 GEN
Solar/Wind Harmer
1.772
316018AA1-139 ULT2
Solar/Wind Harmer
2.248
316017AA1-139 ULT1
Solar/Wind Harmer
2.124
3137176SLIGO L2192
Solar/Wind Harmer
-0.104
3146456SLIGO L269
Solar/Wind Harmer
3.093
3130086AYDLETT
Solar/Wind Harmer
-0.104
3146386ELIZ CT
Solar/Wind Harmer
-0.026
316431W1029_GEN1
Solar/Wind Harmer
4.645
316433W1029_GEN2
Solar/Wind Harmer
4.645
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3144356SAPONY
Solar/Wind Harmer
0.884
316487AF1-042 GEN
Solar/Wind Harmer
3.317
315742AE1-103 GEN
Solar/Wind Harmer
2.611
958261AF2-120 GEN
Solar/Wind Harmer
9.632
3146376EDENTON
Solar/Wind Harmer
0.737
3146376EDENTON
Solar/Wind Harmer
0.737
972185AH1-677 GEN
Adder
12.31
972187AH1-678 GEN
Adder
6.176
316077AC2-138 C
Solar/Wind Harmer
0.512
3150341NORNECKC1
Adder
2.262
3150341NORNECKC1
Adder
2.244
316468AD1-105 GEN
Solar/Wind Harmer
2.704
970933AG2-581 GEN
Solar/Wind Harmer
22.474
316065AD1-022 GEN
Solar/Wind Harmer
11.808
3145893MURPHYS
Solar/Wind Harmer
0.653
3145893MURPHYS
Solar/Wind Harmer
-0.042
3146173TUNIS
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.023
316181AB2-040 GEN
Solar/Wind Harmer
3.15
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
970099AG2-077 GEN
Solar/Wind Harmer
28.086
316426AA2-053 GEN
Solar/Wind Harmer
2.265
3145593CAROLNA
Solar/Wind Harmer
-0.022
3145593CAROLNA
Solar/Wind Harmer
-0.022
966811AG1-552 GEN
Solar/Wind Harmer
2.509
3145593CAROLNA
Solar/Wind Harmer
0.185
3145783HORNRTN
Solar/Wind Harmer
2.631
3145783HORNRTN
Solar/Wind Harmer
2.105
3145783HORNRTN
Solar/Wind Harmer
0.658
3145783HORNRTN
Solar/Wind Harmer
0.263
3145796HORNRTN
Solar/Wind Harmer
-0.066
3145933PARMELE
Solar/Wind Harmer
-0.043
3145933PARMELE
Solar/Wind Harmer
-0.022
316274AC1-208 GEN
Solar/Wind Harmer
2.317
3144293JTRSVLE
Adder
0.566
3144293JTRSVLE
Adder
0.477
316447AC1-158 HLD
Solar/Wind Helper
4.715
315651AD1-115 GEN
Solar/Wind Helper
1.124
3152251N ANNA1
50/50
14.763
972197AH1-683 GEN
50/50
5.958
972219AH1-694 GEN
50/50
4.29
315052AA1-145 CT2
50/50
2.077
966881AG1-559 GEN
Solar/Wind Harmer
0.306
3142416OLDCHRC
Solar/Wind Harmer
-0.074
3142416OLDCHRC
Solar/Wind Harmer
-0.028
3143096IRON208
Adder
1.04
3143526WINTERP
Solar/Wind Harmer
-0.144
3150851SPRUNCC
Adder
1.143
3142543TWELFTH
Solar/Wind Harmer
-0.003
3143226MDLTHAN
Solar/Wind Harmer
-0.028
944631AF1-128 GEN
Adder
117.48
316159AE1-175 C
Solar/Wind Harmer
0.732
970129AG2-093 GEN
Solar/Wind Harmer
6.212
316458AB2-190 GEN2
Solar/Wind Harmer
2.754
315671AE2-027_GEN
Solar/Wind Harmer
20.394
971069AG2-661 GEN
Solar/Wind Harmer
4.294
971647AH1-324 GEN
Solar/Wind Harmer
13.504
971317AH1-138 GEN
Solar/Wind Harmer
3.372
3142433PROV 92
Solar/Wind Harmer
-0.107
3142433PROV 92
Adder
0.467
3142433PROV 92
Adder
0.467
3138126ROCKLANDING
Solar/Wind Harmer
0.083
961611AG1-000B GEN
Solar/Wind Harmer
13.293
3151171GRAVELC
Adder
2.542
316294AC1-161 GEN
Solar/Wind Harmer
8.683
3145336SMITFLD
Solar/Wind Harmer
-0.106
970659AG2-427 GEN
Solar/Wind Harmer
14.105
944591AF1-124 GEN
Solar/Wind Harmer
121.068
316375AC2-012 GEN
Solar/Wind Harmer
9.176
3150981CHESPKA
Adder
2.946
316381AD1-082 GEN
Solar/Wind Harmer
2.432
3141766HARMONY
Solar/Wind Harmer
-0.005
971777AH1-397 GEN
Solar/Wind Harmer
3.113
3141843SHACKLE
Adder
1.204
970661AG2-428 GEN
Solar/Wind Harmer
28.081
316072AD1-144
Solar/Wind Harmer
0.532
939411AE1-173 GEN
Solar/Wind Harmer
131.481
316388AE2-253 GEN
Solar/Wind Harmer
1.772
940641AE2-051 GEN
Solar/Wind Harmer
24.616
3146456SLIGO L269
Solar/Wind Harmer
-0.026
316246AF1-032 C
Solar/Wind Harmer
0.529
316093AE2-104_GEN
Solar/Wind Harmer
7.562
3138133OCRAN
Solar/Wind Harmer
-0.015
3146516WINFALL
Solar/Wind Harmer
-0.082
3146516WINFALL
Solar/Wind Harmer
-0.025
961951AG1-038 GEN
Solar/Wind Harmer
3.317
315800Z1-036_GEN1
Solar/Wind Harmer
6.217
962861AG1-135 GEN
Solar/Wind Harmer
9.354
3130156CHOWAN
Solar/Wind Harmer
-0.025
964211AG1-282 GEN
Solar/Wind Harmer
0.739
3141726DUNNSVL
Solar/Wind Harmer
-0.098
3145663CRESWEL
Solar/Wind Harmer
-0.068
971163AH1-040 GEN
Solar/Wind Harmer
22.771
3150351NORNECKC2
Adder
2.153
3143336POWHATN
Solar/Wind Harmer
2.808
3146206CASHIE
Solar/Wind Harmer
-0.023
971547AH1-271 GEN
Solar/Wind Harmer
5.881
970919AG2-571 GEN
Solar/Wind Harmer
7.444
316023GEN1_S
Solar/Wind Harmer
1.582
970087AG2-069 GEN
Solar/Wind Harmer
21.965
3145893MURPHYS
Solar/Wind Harmer
-0.093
3145893MURPHYS
Solar/Wind Harmer
0.695
316337AD2-073 GEN
Solar/Wind Harmer
0.625
3146173TUNIS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
960081AF2-299 GEN
Solar/Wind Harmer
2.568
3146263WOODLND
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.023
316336AC2-165 C
Solar/Wind Harmer
3.927
316011AB1-132 GEN
Solar/Wind Harmer
4.71
962571AG1-106 GEN
Solar/Wind Harmer
3.236
3145823KELFORD
Solar/Wind Harmer
-0.022
957481AF2-042 GEN
Solar/Wind Harmer
70.215
316174AB2-169 GEN
Solar/Wind Harmer
3.457
316190AA2-174 GEN
Solar/Wind Harmer
0.275
971795AH1-408 GEN
Solar/Wind Harmer
16.732
3145783HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.073
3145796HORNRTN
Solar/Wind Harmer
-0.022
3147043LAWRENC
Adder
1.777
315693AD1-088 GEN
Solar/Wind Harmer
11.006
962491AG1-098 GEN
Solar/Wind Harmer
14.673
316212AC1-099_GEN
Solar/Wind Harmer
1.887
3146293MARTNCO
Solar/Wind Harmer
0.134
3144293JTRSVLE
Adder
0.566
972277AH1-723 GEN
Adder
99.081
316045AC1-158 PL2
Solar/Wind Helper
6.858
316254AC1-120 GEN1
Solar/Wind Helper
1.559
316006AB2-029 C
Solar/Wind Helper
0.15
NYPJM->LTFIMP_NY
CLTF
3.186
LGEELTFEXP_LGEE->PJM
CLTF
1.378
WECLTFEXP_WEC->PJM
CLTF
0.668
LAGNLTFEXP_LAGN->PJM
CLTF
8.173
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.302
TVALTFEXP_TVA->PJM
CLTF
4.142
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.357
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.11
MECLTFEXP_MEC->PJM
CLTF
3.734
SIGELTFEXP_SIGE->PJM
CLTF
0.114
CPLELTFEXP_CPLE->PJM
CLTF
11.526
CBM West 2LTFEXP_CBM-W2->PJM
CBM
42.356

Details for 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 581_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.67 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:4208.1
MW Contribution:84.96
Bus #Bus NameTypeMW Contribution
3150391LDYSMT3
50/50
28.713
972195AH1-682 GEN
50/50
3.773
3142296MT RD221
50/50
0.663
3142366NRTHEST
50/50
0.658
315673AE1-157 GEN
Solar/Wind Harmer
13.925
957411AF2-035 GEN
Solar/Wind Harmer
8.572
970317AG2-208 GEN
Solar/Wind Harmer
7.941
3150691DARBY 3
Adder
13.639
3150701DARBY 4
Adder
13.607
3150681DARBY 2
Adder
13.591
3150671DARBY 1
Adder
13.575
316075AC2-137 C
Solar/Wind Harmer
0.052
966871AG1-558 GEN
Solar/Wind Harmer
0.215
3142946ENON
Solar/Wind Harmer
0.018
944641AF1-129 GEN
Adder
86.641
316240AF1-291 C
Solar/Wind Harmer
0.001
3143526WINTERP
Solar/Wind Harmer
0.94
316033AB2-134 GEN
Solar/Wind Harmer
0.011
315697AD1-025 GEN
Solar/Wind Harmer
0.202
971223AH1-071 GEN
Solar/Wind Harmer
1.89
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316036AC1-147 C
Solar/Wind Harmer
0.032
3150991CHESPKB
Adder
1.827
3150991CHESPKB
Adder
1.783
970657AG2-426 GEN
Solar/Wind Harmer
6.101
970657AG2-426 GEN
Solar/Wind Harmer
1.279
316316AC1-027 C
Solar/Wind Harmer
0.167
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.005
3145506HICKORY
Solar/Wind Harmer
0.693
3145506HICKORY
Solar/Wind Harmer
0.416
3145506HICKORY
Solar/Wind Harmer
0.104
316339AD2-160 GEN
Solar/Wind Harmer
0.28
316018AA1-139 ULT2
Solar/Wind Harmer
0.004
316017AA1-139 ULT1
Solar/Wind Harmer
0.096
3137176SLIGO L2192
Solar/Wind Harmer
0.686
3146456SLIGO L269
Solar/Wind Harmer
3.048
3130086AYDLETT
Solar/Wind Harmer
0.688
3146386ELIZ CT
Solar/Wind Harmer
0.17
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.168
3146516WINFALL
Solar/Wind Harmer
0.168
3146516WINFALL
Solar/Wind Harmer
0.168
3146626S HERTFORD
Solar/Wind Harmer
0.167
3146626S HERTFORD
Solar/Wind Harmer
0.167
3144356SAPONY
Solar/Wind Harmer
1.381
315742AE1-103 GEN
Solar/Wind Harmer
0.002
3146376EDENTON
Solar/Wind Harmer
0.728
3146376EDENTON
Solar/Wind Harmer
0.728
972185AH1-677 GEN
Adder
8.902
972187AH1-678 GEN
Adder
4.473
958261AF2-120 GEN
Solar/Wind Harmer
5.185
316065AD1-022 GEN
Solar/Wind Harmer
7.188
970933AG2-581 GEN
Solar/Wind Harmer
12.41
3145893MURPHYS
Solar/Wind Harmer
1.035
3145893MURPHYS
Solar/Wind Harmer
0.278
3146173TUNIS
Solar/Wind Harmer
0.153
3146173TUNIS
Solar/Wind Harmer
0.153
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
1.579
3150341NORNECKC1
Adder
1.567
316468AD1-105 GEN
Solar/Wind Harmer
-0.049
3142666NORTHAMPTON
Solar/Wind Harmer
0.149
3142666NORTHAMPTON
Solar/Wind Harmer
0.149
3142666NORTHAMPTON
Solar/Wind Harmer
0.149
3142666NORTHAMPTON
Solar/Wind Harmer
0.09
316181AB2-040 GEN
Solar/Wind Harmer
0.216
316426AA2-053 GEN
Solar/Wind Harmer
0.501
3145593CAROLNA
Solar/Wind Harmer
0.147
3145593CAROLNA
Solar/Wind Harmer
0.147
966811AG1-552 GEN
Solar/Wind Harmer
1.6
3145593CAROLNA
Solar/Wind Harmer
0.184
970099AG2-077 GEN
Solar/Wind Harmer
15.68
3145783HORNRTN
Solar/Wind Harmer
2.61
3145783HORNRTN
Solar/Wind Harmer
2.088
3145783HORNRTN
Solar/Wind Harmer
0.652
3145783HORNRTN
Solar/Wind Harmer
0.261
3145796HORNRTN
Solar/Wind Harmer
0.44
3145933PARMELE
Solar/Wind Harmer
0.288
3145933PARMELE
Solar/Wind Harmer
0.144
316274AC1-208 GEN
Solar/Wind Harmer
0.74
971741AH1-377 GEN
Solar/Wind Harmer
13.893
970301AG2-198 GEN
Solar/Wind Harmer
5.915
3145493TOT1
Solar/Wind Harmer
0.317
3145453TOT5
Solar/Wind Harmer
0.19
3145603CNETO
Solar/Wind Harmer
0.127
939181AE1-148 GEN
Solar/Wind Harmer
6.556
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.01
970323AG2-213 GEN
Solar/Wind Harmer
5.778
971775AH1-396 GEN
Solar/Wind Harmer
0.217
958211AF2-115 GEN
Solar/Wind Harmer
1.62
963191AG1-168 GEN
Solar/Wind Harmer
0.54
3144293JTRSVLE
Adder
0.43
3144293JTRSVLE
Adder
0.362
3147133PAMPLIN
Solar/Wind Harmer
0.135
3147133PAMPLIN
Solar/Wind Harmer
0.108
961601AG1-000A GEN
Solar/Wind Harmer
2.386
316263AC1-034 GEN
Solar/Wind Harmer
5.098
962561AG1-105 GEN
Solar/Wind Harmer
6.266
3146776BUCKING
Solar/Wind Harmer
0.519
3146776BUCKING
Solar/Wind Harmer
0.042
964791AG1-342 GEN
Solar/Wind Harmer
2.488
3146843MT LREL
Solar/Wind Harmer
0.129
3146843MT LREL
Solar/Wind Harmer
0.129
971489AH1-241 GEN
Solar/Wind Harmer
6.355
316222AC1-221 GEN
Solar/Wind Harmer
0.477
226929AD2-058 GEN
Solar/Wind Helper
0.118
3150411LDYSMT5
50/50
28.857
3150381LDYSMT2
50/50
27.617
972213AH1-691 GEN
50/50
4.672
972215AH1-692 GEN
50/50
4.672
963051AG1-154 GEN
50/50
3.594
972189AH1-679 GEN
50/50
3.546
316312AB1-027
Solar/Wind Harmer
0.345
315976AC1-164 GENA
Solar/Wind Harmer
19.303
316169AC1-164_GENC
Solar/Wind Harmer
16.676
315975AC1-164 GENB
Solar/Wind Harmer
0.571
971285AH1-108 GEN
Adder
1.386
316233AE1-074 FULL
Solar/Wind Harmer
0.145
971281AH1-106 GEN
Solar/Wind Harmer
2.508
971283AH1-107 GEN
Solar/Wind Harmer
2.508
316132AB2-190 GEN1
Solar/Wind Harmer
0.968
316369SG1_INVT
Solar/Wind Harmer
0.007
971167AH1-042 GEN
Solar/Wind Harmer
15.837
3142433PROV 92
Adder
0.346
3142433PROV 92
Adder
0.346
972265AH1-717 GEN
Adder
13.77
3151201GRAVEL4
Adder
12.909
3151191GRAVEL3
Adder
12.745
3151211GRAVEL5
Adder
12.745
971445AH1-216 GEN
Solar/Wind Harmer
12.417
3143873LANEXA
Solar/Wind Harmer
0.105
3138283WHITEMARSH
Solar/Wind Harmer
0.041
3143316POE
Solar/Wind Harmer
0.692
316314AB2-024 C
Solar/Wind Harmer
0.001
3151081ELIZAR1
Adder
15.992
3151091ELIZAR2
Adder
15.714
3152611GOSPORTB
Adder
2.221
3152621GOSPORTC
Adder
1.885
3152601GOSPORTA
Adder
1.739
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
5.131
957871AF2-081 GEN
Solar/Wind Harmer
8.594
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.118
316311AC2-079 GEN
Solar/Wind Harmer
4.949
315662AE1-191 GEN
Solar/Wind Harmer
0.006
315666AE1-190 GEN
Solar/Wind Harmer
0.001
319010AE1-072 C
Solar/Wind Harmer
0.867
3146406KITTY HAWK
Solar/Wind Harmer
0.021
316305AF2-043 C
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.034
315835AF2-110_GEN
Solar/Wind Harmer
1.175
313526AB2-022
Solar/Wind Harmer
0.092
3146486SUNBURY
Solar/Wind Harmer
0.17
3146486SUNBURY
Solar/Wind Harmer
0.17
316321Z2-027
Solar/Wind Harmer
0.032
3146396TANGLEW
Solar/Wind Harmer
0.468
3145176PASQUOTANK
Solar/Wind Harmer
0.105
3141913WHIT STONE
Solar/Wind Harmer
0.168
3138133OCRAN
Solar/Wind Harmer
0.05
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3141783LANCAST
Solar/Wind Harmer
0.099
3141783LANCAST
Solar/Wind Harmer
0.066
316315AB2-025 C
Solar/Wind Harmer
0.133
315814AE2-033 C
Solar/Wind Harmer
13.015
3130156CHOWAN
Solar/Wind Harmer
0.164
3130156CHOWAN
Solar/Wind Harmer
0.164
941031AE2-094 GEN
Solar/Wind Harmer
29.871
944011AF1-069 GEN
Solar/Wind Harmer
9.76
962981AG1-147 GEN
Solar/Wind Harmer
6.055
315816AE2-034 GEN
Solar/Wind Harmer
0.688
970327AG2-215 GEN
Solar/Wind Harmer
5.255
970673AG2-436 GEN
Solar/Wind Harmer
34.096
970673AG2-436 GEN
Solar/Wind Harmer
22.731
971967AH1-528 GEN
Solar/Wind Harmer
25.316
3130546PLYMOUTH
Solar/Wind Harmer
0.158
315732AD1-074 GEN1
Solar/Wind Harmer
0.903
315733AD1-074 GEN2
Solar/Wind Harmer
0.903
315735AD1-075 GEN1
Solar/Wind Harmer
0.452
965291AG1-394 GEN
Solar/Wind Harmer
0.694
3146206CASHIE
Solar/Wind Harmer
0.155
970601AG2-382 GEN
Solar/Wind Harmer
5.807
3145893MURPHYS
Solar/Wind Harmer
0.418
3145893MURPHYS
Solar/Wind Harmer
0.155
3145513AHOSKIE
Solar/Wind Harmer
0.319
3145513AHOSKIE
Solar/Wind Harmer
0.153
3145683EARLEYS
Solar/Wind Harmer
0.304
3145683EARLEYS
Solar/Wind Harmer
0.152
3145683EARLEYS
Solar/Wind Harmer
0.152
970085AG2-068 GEN
Solar/Wind Harmer
8.093
970581AG2-369 GEN
Solar/Wind Harmer
6.96
3146043SEABORD
Solar/Wind Harmer
0.151
315607AA1-063A GEN
Solar/Wind Harmer
0.308
3141813NORNECK
Solar/Wind Harmer
0.151
316087AB2-174 GEN
Solar/Wind Harmer
0.004
315652AC1-086 GEN
Solar/Wind Harmer
16.356
3137643SOCKMAN
Solar/Wind Harmer
0.592
3145796HORNRTN
Solar/Wind Harmer
0.469
3145796HORNRTN
Solar/Wind Harmer
0.059
3146033SCOT NK
Solar/Wind Harmer
0.584
972193AH1-681 GEN
Adder
3.258
970831AG2-522 GEN
Solar/Wind Harmer
6.025
316005AA1-067
Solar/Wind Harmer
0.151
3145746EVERETS
Solar/Wind Harmer
0.561
3145746EVERETS
Solar/Wind Harmer
0.141
3145746EVERETS
Solar/Wind Harmer
0.141
3145746EVERETS
Solar/Wind Harmer
0.141
970181AG2-120 GEN
Solar/Wind Harmer
1.754
957861AF2-080 GEN
Solar/Wind Harmer
5.976
316420AA1-050 GEN
Solar/Wind Harmer
0.005
3145573BETHELC
Solar/Wind Harmer
0.137
3145573BETHELC
Solar/Wind Harmer
0.137
316319Z2-044 C
Solar/Wind Harmer
0
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
971443AH1-215 GEN
Solar/Wind Harmer
2.276
3144303KENBRDG
Solar/Wind Harmer
0.108
970683AG2-441 GEN
Solar/Wind Harmer
9.015
970681AG2-440 GEN
Solar/Wind Harmer
7.212
946301AF1-294 GEN
Solar/Wind Harmer
2.664
961791AG1-021 GEN
Solar/Wind Harmer
1.296
315657AE1-056 GEN
Solar/Wind Harmer
4.652
970285AG2-188 GEN
Solar/Wind Harmer
10.359
971845AH1-439 GEN
Solar/Wind Harmer
5.906
316223AC1-118
Solar/Wind Harmer
0.093
316118AC1-105 GEN
Solar/Wind Harmer
0.328
3147173SINAI
Solar/Wind Harmer
0.125
3147243WELCO
Solar/Wind Harmer
0.078
972205AH1-687 GEN
Adder
5.337
971447AH1-217 GEN
Solar/Wind Harmer
3.558
970865AG2-541 GEN
Solar/Wind Harmer
3.939
970497AG2-320 GEN
50/50
20.809
3150401LDYSMT4
50/50
28.767
3150371LDYSMT1
50/50
27.797
315051AA1-145 CT1
50/50
1.582
971645AH1-323 GEN
50/50
17.655
3142416OLDCHRC
Solar/Wind Harmer
1.87
970293AG2-193 GEN
Solar/Wind Harmer
2.014
3143096IRON208
Adder
0.779
3143096IRON208
Adder
0.764
316473AC1-191 GEN
Solar/Wind Harmer
0.628
3142946ENON
Solar/Wind Harmer
0.062
3150861SPRUNCD
Adder
0.847
970133AG2-095 GEN
Solar/Wind Harmer
1.744
316382AG1-145 C
Solar/Wind Harmer
0.001
970129AG2-093 GEN
Solar/Wind Harmer
10.911
315778AD1-151 GEN
Solar/Wind Harmer
14.378
965281AG1-393 GEN
Solar/Wind Harmer
1.909
315839AE2-212 C
Solar/Wind Harmer
0.001
3150921YORKTN3
Adder
4.486
3144216WINCHST
Adder
0.673
961611AG1-000B GEN
Solar/Wind Harmer
4.749
3142433PROV 92
Adder
0.346
3142433PROV 92
Adder
0.346
3151221GRAVEL6
Adder
12.894
3151171GRAVELC
Adder
2.481
315773AC2-141 GEN
Solar/Wind Harmer
6.451
3145336SMITFLD
Solar/Wind Harmer
0.071
315813AE1-149 C
Solar/Wind Harmer
9.37
3144536CHRHLND
Solar/Wind Harmer
0.026
970659AG2-427 GEN
Solar/Wind Harmer
1.847
3151101ELIZAR3
Adder
16.197
316083AB2-161 GEN
Solar/Wind Harmer
0.002
3144873MCLAUGH
Solar/Wind Harmer
0.004
944581AF1-123 GEN
Solar/Wind Harmer
39.252
944601AF1-125 GEN
Solar/Wind Harmer
38.647
970661AG2-428 GEN
Solar/Wind Harmer
3.678
3141766HARMONY
Solar/Wind Harmer
2.312
3141843SHACKLE
Adder
0.885
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316280AD1-041 GEN
Solar/Wind Harmer
0.004
3146456SLIGO L269
Solar/Wind Harmer
0.172
971153AH1-033 GEN
Solar/Wind Harmer
1.991
316156AD2-030 GEN
Solar/Wind Harmer
0.127
3141873WAN 176
Solar/Wind Harmer
3.045
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.168
3146626S HERTFORD
Solar/Wind Harmer
0.167
3145273HOLLAND
Solar/Wind Harmer
0.125
3146376EDENTON
Solar/Wind Harmer
0.164
962971AG1-146 GEN
Solar/Wind Harmer
2.595
315614AA2-178 GEN
Solar/Wind Harmer
0.918
970009AG2-005 GEN
Solar/Wind Harmer
1.196
971157AH1-035 GEN
Solar/Wind Harmer
1.892
315737AD1-076 GEN
Solar/Wind Harmer
2.022
316404AE1-155 C
Solar/Wind Harmer
0.035
3156081AA2-088 GEN
Solar/Wind Harmer
0.004
316313AB2-026
Solar/Wind Harmer
0.098
316258AE1-075 C
Solar/Wind Harmer
0.118
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
2.362
3146206CASHIE
Solar/Wind Harmer
0.155
3145893MURPHYS
Solar/Wind Harmer
0.259
3145893MURPHYS
Solar/Wind Harmer
0.155
957521AF2-046 GEN
Solar/Wind Harmer
11.485
961681AG1-008 GEN
Solar/Wind Harmer
11.485
316365GEN2_N
Solar/Wind Harmer
0.346
3146173TUNIS
Solar/Wind Harmer
0.153
3156021HOLLOMANSOL
Solar/Wind Harmer
0.696
316463AE2-346 GEN
Solar/Wind Harmer
0.131
316140AB2-099
Solar/Wind Harmer
0.055
962331AG1-082 GEN
Solar/Wind Harmer
1.628
970917AG2-570 GEN
Solar/Wind Harmer
13.535
3150351NORNECKC2
Adder
1.529
3146263WOODLND
Solar/Wind Harmer
0.151
971781AH1-399 GEN
Solar/Wind Harmer
0.197
3145963POPLR C
Solar/Wind Harmer
0.15
3142666NORTHAMPTON
Solar/Wind Harmer
0.149
313506AB2-031 GEN
Solar/Wind Harmer
0.461
316317KELFORD C
Solar/Wind Harmer
0.014
3145823KELFORD
Solar/Wind Harmer
0.149
3145796HORNRTN
Solar/Wind Harmer
0.586
3145796HORNRTN
Solar/Wind Harmer
0.146
3147043LAWRENC
Solar/Wind Harmer
0.088
3145933PARMELE
Solar/Wind Harmer
0.144
966801AG1-551 GEN
Solar/Wind Harmer
1.675
316210AC1-098 GEN
Solar/Wind Harmer
1.333
972255AH1-712 GEN
Adder
72.909
316478AD1-087 GEN
Solar/Wind Harmer
0.497
316486AD2-202 GEN
Solar/Wind Harmer
0.146
3145746EVERETS
Solar/Wind Harmer
0.141
3145746EVERETS
Solar/Wind Harmer
0.141
315724AD1-057 GEN
Solar/Wind Harmer
0.524
316327AA2-057 GEN
Solar/Wind Harmer
0.209
970909AG2-566 GEN
Solar/Wind Harmer
1.479
3146073TAR RVR
Solar/Wind Harmer
0.137
3146083TARBORO
Solar/Wind Harmer
0.137
3146233WITAKRS
Solar/Wind Harmer
0.685
3146233WITAKRS
Solar/Wind Harmer
0.093
3138543CONSLDL
Solar/Wind Harmer
0.09
316131AB2-060 GEN
Solar/Wind Harmer
0.427
964241AG1-285 GEN
Solar/Wind Harmer
9.049
315785AD2-033 C
Solar/Wind Harmer
1.102
970257AG2-171 GEN
Solar/Wind Harmer
4.334
959311AF2-222 GEN
Solar/Wind Harmer
12.033
963181AG1-167 GEN
Solar/Wind Harmer
0.54
3144293JTRSVLE
Adder
0.43
3147133PAMPLIN
Solar/Wind Harmer
0.423
971193AH1-056 GEN
Solar/Wind Harmer
8.213
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
961601AG1-000A GEN
Solar/Wind Harmer
9.544
3145543BTLEBRO
Solar/Wind Harmer
0.134
3145543BTLEBRO
Solar/Wind Harmer
0.134
971623AH1-311 GEN
Solar/Wind Harmer
0.268
3146926FARMVIL
Solar/Wind Harmer
0.08
3147666LOUISA
Solar/Wind Harmer
0.299
3146776BUCKING
Solar/Wind Harmer
0.047
3141906WESTMOR
Solar/Wind Harmer
0.052
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
5.333
970737AG2-469 GEN
Solar/Wind Harmer
5.097
970221AG2-151 GEN
Solar/Wind Harmer
6.355
971683AH1-343 GEN
Solar/Wind Harmer
4.317
316283AC2-100 C
Solar/Wind Harmer
0.224
227287AC2-120 GEN
Solar/Wind Helper
0.387
226910AB2-157 C
Solar/Wind Helper
0.015
972197AH1-683 GEN
50/50
4.492
972219AH1-694 GEN
50/50
3.234
315052AA1-145 CT2
50/50
1.589
966881AG1-559 GEN
Solar/Wind Harmer
0.232
3142416OLDCHRC
Solar/Wind Harmer
0.502
3142416OLDCHRC
Solar/Wind Harmer
0.192
3143096IRON208
Adder
0.779
3142543TWELFTH
Solar/Wind Harmer
0.018
944631AF1-128 GEN
Adder
88.024
3150851SPRUNCC
Adder
0.847
316159AE1-175 C
Solar/Wind Harmer
0.157
3143526WINTERP
Solar/Wind Harmer
0.94
970129AG2-093 GEN
Solar/Wind Harmer
5.135
316458AB2-190 GEN2
Solar/Wind Harmer
0.968
971069AG2-661 GEN
Solar/Wind Harmer
3.195
315671AE2-027_GEN
Solar/Wind Harmer
11.489
971647AH1-324 GEN
Solar/Wind Harmer
7.623
971317AH1-138 GEN
Solar/Wind Harmer
1.333
3138126ROCKLANDING
Solar/Wind Harmer
0.082
961611AG1-000B GEN
Solar/Wind Harmer
9.339
3142433PROV 92
Solar/Wind Harmer
0.711
3142433PROV 92
Adder
0.346
3142433PROV 92
Adder
0.346
3151171GRAVELC
Adder
1.887
3143226MDLTHAN
Solar/Wind Harmer
0.177
316294AC1-161 GEN
Solar/Wind Harmer
3.06
3145336SMITFLD
Solar/Wind Harmer
0.705
970659AG2-427 GEN
Solar/Wind Harmer
8.444
316375AC2-012 GEN
Solar/Wind Harmer
0.004
3150981CHESPKA
Adder
2.178
316381AD1-082 GEN
Solar/Wind Harmer
0.182
944591AF1-124 GEN
Solar/Wind Harmer
39.391
970661AG2-428 GEN
Solar/Wind Harmer
17.291
3141766HARMONY
Solar/Wind Harmer
0.035
316072AD1-144
Solar/Wind Harmer
0.063
971777AH1-397 GEN
Solar/Wind Harmer
0.457
3141843SHACKLE
Adder
0.885
316388AE2-253 GEN
Solar/Wind Harmer
0.541
3146456SLIGO L269
Solar/Wind Harmer
0.172
316246AF1-032 C
Solar/Wind Harmer
0.078
316093AE2-104_GEN
Solar/Wind Harmer
2.878
939411AE1-173 GEN
Solar/Wind Harmer
72.518
940641AE2-051 GEN
Solar/Wind Harmer
13.497
3146516WINFALL
Solar/Wind Harmer
0.545
3146516WINFALL
Solar/Wind Harmer
0.168
3138133OCRAN
Solar/Wind Harmer
0.1
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.164
3145663CRESWEL
Solar/Wind Harmer
0.449
971163AH1-040 GEN
Solar/Wind Harmer
12.829
962861AG1-135 GEN
Solar/Wind Harmer
5.046
3143336POWHATN
Solar/Wind Harmer
2.778
3146206CASHIE
Solar/Wind Harmer
0.155
971547AH1-271 GEN
Solar/Wind Harmer
3.318
3145893MURPHYS
Solar/Wind Harmer
0.619
3145893MURPHYS
Solar/Wind Harmer
0.688
316023GEN1_S
Solar/Wind Harmer
0.346
3141726DUNNSVL
Solar/Wind Harmer
0.616
3146173TUNIS
Solar/Wind Harmer
0.153
970919AG2-571 GEN
Solar/Wind Harmer
5.414
3145683EARLEYS
Solar/Wind Harmer
0.152
970087AG2-069 GEN
Solar/Wind Harmer
12.139
3150351NORNECKC2
Adder
1.504
316336AC2-165 C
Solar/Wind Harmer
0.006
3146263WOODLND
Solar/Wind Harmer
0.151
960081AF2-299 GEN
Solar/Wind Harmer
1.445
3145963POPLR C
Solar/Wind Harmer
0.15
3145823KELFORD
Solar/Wind Harmer
0.149
316011AB1-132 GEN
Solar/Wind Harmer
2.703
962571AG1-106 GEN
Solar/Wind Harmer
2.116
316174AB2-169 GEN
Solar/Wind Harmer
0.004
316190AA2-174 GEN
Solar/Wind Harmer
0
971795AH1-408 GEN
Solar/Wind Harmer
9.834
957481AF2-042 GEN
Solar/Wind Harmer
39.2
3145783HORNRTN
Solar/Wind Harmer
0.147
3145796HORNRTN
Solar/Wind Harmer
0.484
3145796HORNRTN
Solar/Wind Harmer
0.146
3147043LAWRENC
Adder
1.322
315693AD1-088 GEN
Solar/Wind Harmer
6.952
962491AG1-098 GEN
Solar/Wind Harmer
8.247
3146293MARTNCO
Solar/Wind Harmer
0.133
316212AC1-099_GEN
Solar/Wind Harmer
0.743
972277AH1-723 GEN
Adder
84.961
3145746EVERETS
Solar/Wind Harmer
0.141
3145746EVERETS
Solar/Wind Harmer
0.141
316337AD2-073 GEN
Solar/Wind Harmer
0.122
316129AC1-054 GEN
Solar/Wind Harmer
0.528
971065AG2-659 GEN
Solar/Wind Harmer
5.969
315722AD1-056 GEN
Solar/Wind Harmer
0.885
316494AC1-189 GEN
Solar/Wind Harmer
0.468
970937AG2-583 GEN
Solar/Wind Harmer
8.39
961671AG1-007 GEN
Solar/Wind Harmer
0.021
3146083TARBORO
Solar/Wind Harmer
0.137
3145493TOT1
Solar/Wind Harmer
0.607
3146233WITAKRS
Solar/Wind Harmer
0.543
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315687AD1-152 GEN
Solar/Wind Harmer
0.004
970685AG2-442 GEN
Solar/Wind Harmer
10.097
963171AG1-166 GEN
Solar/Wind Harmer
0.72
971563AH1-280 GEN
Solar/Wind Harmer
1.44
3144293JTRSVLE
Adder
0.43
3145543BTLEBRO
Solar/Wind Harmer
0.134
3145543BTLEBRO
Solar/Wind Harmer
0.107
316359AB2-059 GEN
Solar/Wind Harmer
0.482
316049AB1-081 GEN
Solar/Wind Harmer
0.768
3142053HEARTS
Solar/Wind Harmer
0.236
3146926FARMVIL
Solar/Wind Harmer
0.08
3147666LOUISA
Solar/Wind Harmer
0.52
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.052
970401AG2-262 GEN
Solar/Wind Harmer
0.76
316192AB2-158 GEN
Solar/Wind Harmer
0.724
972003AH1-546 GEN
Solar/Wind Harmer
5.346
316003AC1-222 GEN
Solar/Wind Harmer
0.003
971377AH1-170 GEN
Solar/Wind Harmer
1.271
3147623JAMES R
Solar/Wind Harmer
0.276
972135AH1-637 GEN
Solar/Wind Harmer
0.962
NYPJM->LTFIMP_NY
CLTF
2.846
LGEELTFEXP_LGEE->PJM
CLTF
1.614
WECLTFEXP_WEC->PJM
CLTF
0.82
LAGNLTFEXP_LAGN->PJM
CLTF
7.584
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.244
TVALTFEXP_TVA->PJM
CLTF
3.839
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.903
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.41
MECLTFEXP_MEC->PJM
CLTF
4.166
SIGELTFEXP_SIGE->PJM
CLTF
0.129
CPLELTFEXP_CPLE->PJM
CLTF
8.902
CBM West 2LTFEXP_CBM-W2->PJM
CBM
42.096

Details for 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 552_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.56 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:4204.63
MW Contribution:84.67
Bus #Bus NameTypeMW Contribution
3150391LDYSMT3
50/50
28.468
972195AH1-682 GEN
50/50
3.741
315673AE1-157 GEN
Solar/Wind Harmer
13.816
957411AF2-035 GEN
Solar/Wind Harmer
8.508
970317AG2-208 GEN
Solar/Wind Harmer
7.883
3142296MT RD221
Adder
0.622
3142366NRTHEST
Adder
0.618
3150691DARBY 3
Adder
13.575
3150701DARBY 4
Adder
13.543
3150681DARBY 2
Adder
13.528
3150671DARBY 1
Adder
13.512
316075AC2-137 C
Solar/Wind Harmer
0.051
966871AG1-558 GEN
Solar/Wind Harmer
0.214
3142946ENON
Solar/Wind Harmer
0.018
944641AF1-129 GEN
Adder
86.296
3143526WINTERP
Solar/Wind Harmer
0.937
316240AF1-291 C
Solar/Wind Harmer
0.001
316033AB2-134 GEN
Solar/Wind Harmer
0.01
315697AD1-025 GEN
Solar/Wind Harmer
0.201
971223AH1-071 GEN
Solar/Wind Harmer
1.886
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316036AC1-147 C
Solar/Wind Harmer
0.032
3150991CHESPKB
Adder
1.821
3150991CHESPKB
Adder
1.777
970657AG2-426 GEN
Solar/Wind Harmer
6.079
970657AG2-426 GEN
Solar/Wind Harmer
1.274
316316AC1-027 C
Solar/Wind Harmer
0.166
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.005
3145506HICKORY
Solar/Wind Harmer
0.691
3145506HICKORY
Solar/Wind Harmer
0.414
3145506HICKORY
Solar/Wind Harmer
0.104
316339AD2-160 GEN
Solar/Wind Harmer
0.279
316018AA1-139 ULT2
Solar/Wind Harmer
0.004
316017AA1-139 ULT1
Solar/Wind Harmer
0.096
3137176SLIGO L2192
Solar/Wind Harmer
0.683
3146456SLIGO L269
Solar/Wind Harmer
3.038
3130086AYDLETT
Solar/Wind Harmer
0.686
3146386ELIZ CT
Solar/Wind Harmer
0.17
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.168
3146516WINFALL
Solar/Wind Harmer
0.168
3146516WINFALL
Solar/Wind Harmer
0.168
3146626S HERTFORD
Solar/Wind Harmer
0.167
3146626S HERTFORD
Solar/Wind Harmer
0.167
3144356SAPONY
Solar/Wind Harmer
1.377
315742AE1-103 GEN
Solar/Wind Harmer
0.002
3146376EDENTON
Solar/Wind Harmer
0.726
3146376EDENTON
Solar/Wind Harmer
0.726
972185AH1-677 GEN
Adder
8.883
972187AH1-678 GEN
Adder
4.463
958261AF2-120 GEN
Solar/Wind Harmer
5.156
316065AD1-022 GEN
Solar/Wind Harmer
7.167
970933AG2-581 GEN
Solar/Wind Harmer
12.385
3145893MURPHYS
Solar/Wind Harmer
1.032
3145893MURPHYS
Solar/Wind Harmer
0.278
3146173TUNIS
Solar/Wind Harmer
0.153
3146173TUNIS
Solar/Wind Harmer
0.153
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
1.57
3150341NORNECKC1
Adder
1.558
316468AD1-105 GEN
Solar/Wind Harmer
-0.049
3142666NORTHAMPTON
Solar/Wind Harmer
0.149
3142666NORTHAMPTON
Solar/Wind Harmer
0.149
3142666NORTHAMPTON
Solar/Wind Harmer
0.149
3142666NORTHAMPTON
Solar/Wind Harmer
0.089
316181AB2-040 GEN
Solar/Wind Harmer
0.216
316426AA2-053 GEN
Solar/Wind Harmer
0.5
3145593CAROLNA
Solar/Wind Harmer
0.147
3145593CAROLNA
Solar/Wind Harmer
0.147
966811AG1-552 GEN
Solar/Wind Harmer
1.596
3145593CAROLNA
Solar/Wind Harmer
0.183
970099AG2-077 GEN
Solar/Wind Harmer
15.655
3145783HORNRTN
Solar/Wind Harmer
2.603
3145783HORNRTN
Solar/Wind Harmer
2.082
3145783HORNRTN
Solar/Wind Harmer
0.651
3145783HORNRTN
Solar/Wind Harmer
0.26
3145796HORNRTN
Solar/Wind Harmer
0.438
3145933PARMELE
Solar/Wind Harmer
0.287
3145933PARMELE
Solar/Wind Harmer
0.143
316274AC1-208 GEN
Solar/Wind Harmer
0.738
971741AH1-377 GEN
Solar/Wind Harmer
13.893
970301AG2-198 GEN
Solar/Wind Harmer
5.917
939181AE1-148 GEN
Solar/Wind Harmer
6.546
3145493TOT1
Solar/Wind Harmer
0.316
3145453TOT5
Solar/Wind Harmer
0.189
3145603CNETO
Solar/Wind Harmer
0.126
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.01
970323AG2-213 GEN
Solar/Wind Harmer
5.776
971775AH1-396 GEN
Solar/Wind Harmer
0.217
958211AF2-115 GEN
Solar/Wind Harmer
1.621
963191AG1-168 GEN
Solar/Wind Harmer
0.54
3144293JTRSVLE
Adder
0.43
3144293JTRSVLE
Adder
0.362
3147133PAMPLIN
Solar/Wind Harmer
0.135
3147133PAMPLIN
Solar/Wind Harmer
0.108
961601AG1-000A GEN
Solar/Wind Harmer
2.38
316263AC1-034 GEN
Solar/Wind Harmer
5.085
962561AG1-105 GEN
Solar/Wind Harmer
6.258
3146776BUCKING
Solar/Wind Harmer
0.521
3146776BUCKING
Solar/Wind Harmer
0.042
964791AG1-342 GEN
Solar/Wind Harmer
2.485
3146843MT LREL
Solar/Wind Harmer
0.129
3146843MT LREL
Solar/Wind Harmer
0.129
971489AH1-241 GEN
Solar/Wind Harmer
6.386
316222AC1-221 GEN
Solar/Wind Harmer
0.476
226929AD2-058 GEN
Solar/Wind Helper
0.118
971531AH1-263 GEN
50/50
38.605
3150411LDYSMT5
50/50
28.611
3150381LDYSMT2
50/50
27.382
972213AH1-691 GEN
50/50
4.632
972215AH1-692 GEN
50/50
4.632
963051AG1-154 GEN
50/50
3.563
972189AH1-679 GEN
50/50
3.525
316312AB1-027
Solar/Wind Harmer
0.343
315976AC1-164 GENA
Solar/Wind Harmer
19.21
316169AC1-164_GENC
Solar/Wind Harmer
16.596
315975AC1-164 GENB
Solar/Wind Harmer
0.568
971285AH1-108 GEN
Adder
1.381
316233AE1-074 FULL
Solar/Wind Harmer
0.144
971281AH1-106 GEN
Solar/Wind Harmer
2.501
971283AH1-107 GEN
Solar/Wind Harmer
2.501
316132AB2-190 GEN1
Solar/Wind Harmer
0.964
316369SG1_INVT
Solar/Wind Harmer
0.007
971167AH1-042 GEN
Solar/Wind Harmer
15.763
3142433PROV 92
Adder
0.344
3142433PROV 92
Adder
0.344
972265AH1-717 GEN
Adder
13.718
3151201GRAVEL4
Adder
12.859
3151191GRAVEL3
Adder
12.697
3151211GRAVEL5
Adder
12.697
971445AH1-216 GEN
Solar/Wind Harmer
12.371
3143873LANEXA
Solar/Wind Harmer
0.105
3138283WHITEMARSH
Solar/Wind Harmer
0.04
3143316POE
Solar/Wind Harmer
0.69
3151081ELIZAR1
Adder
15.936
3151091ELIZAR2
Adder
15.659
316314AB2-024 C
Solar/Wind Harmer
0.001
3152611GOSPORTB
Adder
2.213
3152621GOSPORTC
Adder
1.878
3152601GOSPORTA
Adder
1.733
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
5.106
957871AF2-081 GEN
Solar/Wind Harmer
8.564
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.118
316311AC2-079 GEN
Solar/Wind Harmer
4.932
319010AE1-072 C
Solar/Wind Harmer
0.864
315662AE1-191 GEN
Solar/Wind Harmer
0.006
315666AE1-190 GEN
Solar/Wind Harmer
0.001
3146406KITTY HAWK
Solar/Wind Harmer
0.021
316305AF2-043 C
Solar/Wind Harmer
0.001
315835AF2-110_GEN
Solar/Wind Harmer
1.17
3141873WAN 176
Solar/Wind Harmer
0.034
313526AB2-022
Solar/Wind Harmer
0.092
3146486SUNBURY
Solar/Wind Harmer
0.169
3146486SUNBURY
Solar/Wind Harmer
0.169
316321Z2-027
Solar/Wind Harmer
0.031
3146396TANGLEW
Solar/Wind Harmer
0.466
3145176PASQUOTANK
Solar/Wind Harmer
0.105
3141913WHIT STONE
Solar/Wind Harmer
0.167
3138133OCRAN
Solar/Wind Harmer
0.05
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3141783LANCAST
Solar/Wind Harmer
0.099
3141783LANCAST
Solar/Wind Harmer
0.066
316315AB2-025 C
Solar/Wind Harmer
0.133
315814AE2-033 C
Solar/Wind Harmer
12.978
3130156CHOWAN
Solar/Wind Harmer
0.163
3130156CHOWAN
Solar/Wind Harmer
0.163
941031AE2-094 GEN
Solar/Wind Harmer
29.802
944011AF1-069 GEN
Solar/Wind Harmer
9.738
962981AG1-147 GEN
Solar/Wind Harmer
6.022
315816AE2-034 GEN
Solar/Wind Harmer
0.686
970673AG2-436 GEN
Solar/Wind Harmer
34.019
970673AG2-436 GEN
Solar/Wind Harmer
22.68
970327AG2-215 GEN
Solar/Wind Harmer
5.226
971967AH1-528 GEN
Solar/Wind Harmer
25.262
3130546PLYMOUTH
Solar/Wind Harmer
0.157
315732AD1-074 GEN1
Solar/Wind Harmer
0.9
315733AD1-074 GEN2
Solar/Wind Harmer
0.9
315735AD1-075 GEN1
Solar/Wind Harmer
0.451
965291AG1-394 GEN
Solar/Wind Harmer
0.692
3146206CASHIE
Solar/Wind Harmer
0.155
970601AG2-382 GEN
Solar/Wind Harmer
5.789
3145893MURPHYS
Solar/Wind Harmer
0.416
3145893MURPHYS
Solar/Wind Harmer
0.154
3145513AHOSKIE
Solar/Wind Harmer
0.318
3145513AHOSKIE
Solar/Wind Harmer
0.152
3145683EARLEYS
Solar/Wind Harmer
0.303
3145683EARLEYS
Solar/Wind Harmer
0.151
3145683EARLEYS
Solar/Wind Harmer
0.151
970085AG2-068 GEN
Solar/Wind Harmer
8.075
970581AG2-369 GEN
Solar/Wind Harmer
6.945
3146043SEABORD
Solar/Wind Harmer
0.151
315607AA1-063A GEN
Solar/Wind Harmer
0.307
3141813NORNECK
Solar/Wind Harmer
0.15
316087AB2-174 GEN
Solar/Wind Harmer
0.004
315652AC1-086 GEN
Solar/Wind Harmer
16.312
3137643SOCKMAN
Solar/Wind Harmer
0.591
3145796HORNRTN
Solar/Wind Harmer
0.468
3145796HORNRTN
Solar/Wind Harmer
0.058
3146033SCOT NK
Solar/Wind Harmer
0.582
972193AH1-681 GEN
Adder
3.246
970831AG2-522 GEN
Solar/Wind Harmer
6.013
316005AA1-067
Solar/Wind Harmer
0.151
3145746EVERETS
Solar/Wind Harmer
0.559
3145746EVERETS
Solar/Wind Harmer
0.14
3145746EVERETS
Solar/Wind Harmer
0.14
3145746EVERETS
Solar/Wind Harmer
0.14
970181AG2-120 GEN
Solar/Wind Harmer
1.749
957861AF2-080 GEN
Solar/Wind Harmer
5.96
316420AA1-050 GEN
Solar/Wind Harmer
0.005
3145573BETHELC
Solar/Wind Harmer
0.136
3145573BETHELC
Solar/Wind Harmer
0.136
316319Z2-044 C
Solar/Wind Harmer
0
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
971443AH1-215 GEN
Solar/Wind Harmer
2.275
3144303KENBRDG
Solar/Wind Harmer
0.108
970683AG2-441 GEN
Solar/Wind Harmer
9.014
970681AG2-440 GEN
Solar/Wind Harmer
7.211
946301AF1-294 GEN
Solar/Wind Harmer
2.665
961791AG1-021 GEN
Solar/Wind Harmer
1.296
315657AE1-056 GEN
Solar/Wind Harmer
4.654
970285AG2-188 GEN
Solar/Wind Harmer
10.387
971845AH1-439 GEN
Solar/Wind Harmer
5.923
316223AC1-118
Solar/Wind Harmer
0.092
316118AC1-105 GEN
Solar/Wind Harmer
0.328
972205AH1-687 GEN
Adder
5.363
3147173SINAI
Solar/Wind Harmer
0.125
3147243WELCO
Solar/Wind Harmer
0.078
971447AH1-217 GEN
Solar/Wind Harmer
3.576
970865AG2-541 GEN
Solar/Wind Harmer
3.934
970497AG2-320 GEN
50/50
20.637
3150401LDYSMT4
50/50
28.522
3150371LDYSMT1
50/50
27.56
315051AA1-145 CT1
50/50
1.572
3142416OLDCHRC
Solar/Wind Harmer
1.861
970293AG2-193 GEN
Solar/Wind Harmer
2.005
3143096IRON208
Adder
0.776
3143096IRON208
Adder
0.76
316473AC1-191 GEN
Solar/Wind Harmer
0.625
3142946ENON
Solar/Wind Harmer
0.062
3150861SPRUNCD
Adder
0.844
970133AG2-095 GEN
Solar/Wind Harmer
1.736
316382AG1-145 C
Solar/Wind Harmer
0.001
970129AG2-093 GEN
Solar/Wind Harmer
10.867
315778AD1-151 GEN
Solar/Wind Harmer
14.321
965281AG1-393 GEN
Solar/Wind Harmer
1.902
315839AE2-212 C
Solar/Wind Harmer
0.001
3150921YORKTN3
Adder
4.467
3144216WINCHST
Adder
0.67
961611AG1-000B GEN
Solar/Wind Harmer
4.73
3142433PROV 92
Adder
0.344
3142433PROV 92
Adder
0.344
3151221GRAVEL6
Adder
12.845
3151171GRAVELC
Adder
2.471
315773AC2-141 GEN
Solar/Wind Harmer
6.428
3145336SMITFLD
Solar/Wind Harmer
0.07
315813AE1-149 C
Solar/Wind Harmer
9.336
3144536CHRHLND
Solar/Wind Harmer
0.026
970659AG2-427 GEN
Solar/Wind Harmer
1.84
3151101ELIZAR3
Adder
16.14
316083AB2-161 GEN
Solar/Wind Harmer
0.002
3144873MCLAUGH
Solar/Wind Harmer
0.004
944581AF1-123 GEN
Solar/Wind Harmer
39.115
944601AF1-125 GEN
Solar/Wind Harmer
38.512
970661AG2-428 GEN
Solar/Wind Harmer
3.665
3141766HARMONY
Solar/Wind Harmer
2.301
3141843SHACKLE
Adder
0.88
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3146456SLIGO L269
Solar/Wind Harmer
0.172
971153AH1-033 GEN
Solar/Wind Harmer
1.985
316280AD1-041 GEN
Solar/Wind Harmer
0.004
316156AD2-030 GEN
Solar/Wind Harmer
0.126
3141873WAN 176
Solar/Wind Harmer
3.03
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.168
3146626S HERTFORD
Solar/Wind Harmer
0.167
3145273HOLLAND
Solar/Wind Harmer
0.125
3146376EDENTON
Solar/Wind Harmer
0.163
962971AG1-146 GEN
Solar/Wind Harmer
2.581
315614AA2-178 GEN
Solar/Wind Harmer
0.915
970009AG2-005 GEN
Solar/Wind Harmer
1.189
971157AH1-035 GEN
Solar/Wind Harmer
1.886
315737AD1-076 GEN
Solar/Wind Harmer
2.016
3156081AA2-088 GEN
Solar/Wind Harmer
0.004
316313AB2-026
Solar/Wind Harmer
0.099
316258AE1-075 C
Solar/Wind Harmer
0.118
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
2.362
316404AE1-155 C
Solar/Wind Harmer
0.035
3146206CASHIE
Solar/Wind Harmer
0.155
3145893MURPHYS
Solar/Wind Harmer
0.258
3145893MURPHYS
Solar/Wind Harmer
0.154
957521AF2-046 GEN
Solar/Wind Harmer
11.452
961681AG1-008 GEN
Solar/Wind Harmer
11.452
316365GEN2_N
Solar/Wind Harmer
0.345
3146173TUNIS
Solar/Wind Harmer
0.153
3156021HOLLOMANSOL
Solar/Wind Harmer
0.694
316463AE2-346 GEN
Solar/Wind Harmer
0.131
316140AB2-099
Solar/Wind Harmer
0.054
962331AG1-082 GEN
Solar/Wind Harmer
1.624
970917AG2-570 GEN
Solar/Wind Harmer
13.506
3146263WOODLND
Solar/Wind Harmer
0.15
3150351NORNECKC2
Adder
1.52
3145963POPLR C
Solar/Wind Harmer
0.149
971781AH1-399 GEN
Solar/Wind Harmer
0.196
3142666NORTHAMPTON
Solar/Wind Harmer
0.149
313506AB2-031 GEN
Solar/Wind Harmer
0.46
316317KELFORD C
Solar/Wind Harmer
0.014
3145823KELFORD
Solar/Wind Harmer
0.149
3145796HORNRTN
Solar/Wind Harmer
0.585
3145796HORNRTN
Solar/Wind Harmer
0.146
3147043LAWRENC
Solar/Wind Harmer
0.087
3145933PARMELE
Solar/Wind Harmer
0.143
966801AG1-551 GEN
Solar/Wind Harmer
1.67
316210AC1-098 GEN
Solar/Wind Harmer
1.33
316478AD1-087 GEN
Solar/Wind Harmer
0.496
316486AD2-202 GEN
Solar/Wind Harmer
0.146
972255AH1-712 GEN
Adder
72.658
3145746EVERETS
Solar/Wind Harmer
0.14
3145746EVERETS
Solar/Wind Harmer
0.14
315724AD1-057 GEN
Solar/Wind Harmer
0.523
970909AG2-566 GEN
Solar/Wind Harmer
1.479
316327AA2-057 GEN
Solar/Wind Harmer
0.209
3146073TAR RVR
Solar/Wind Harmer
0.136
3146083TARBORO
Solar/Wind Harmer
0.136
3146233WITAKRS
Solar/Wind Harmer
0.683
3146233WITAKRS
Solar/Wind Harmer
0.093
3138543CONSLDL
Solar/Wind Harmer
0.09
316131AB2-060 GEN
Solar/Wind Harmer
0.427
964241AG1-285 GEN
Solar/Wind Harmer
9.041
315785AD2-033 C
Solar/Wind Harmer
1.101
970257AG2-171 GEN
Solar/Wind Harmer
4.332
959311AF2-222 GEN
Solar/Wind Harmer
12.029
963181AG1-167 GEN
Solar/Wind Harmer
0.54
3144293JTRSVLE
Adder
0.43
3147133PAMPLIN
Solar/Wind Harmer
0.423
971193AH1-056 GEN
Solar/Wind Harmer
8.216
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.081
961601AG1-000A GEN
Solar/Wind Harmer
9.521
3145543BTLEBRO
Solar/Wind Harmer
0.134
3145543BTLEBRO
Solar/Wind Harmer
0.134
971623AH1-311 GEN
Solar/Wind Harmer
0.268
3147666LOUISA
Solar/Wind Harmer
0.307
3146776BUCKING
Solar/Wind Harmer
0.047
3141906WESTMOR
Solar/Wind Harmer
0.051
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
5.326
970221AG2-151 GEN
Solar/Wind Harmer
6.386
970737AG2-469 GEN
Solar/Wind Harmer
5.057
971683AH1-343 GEN
Solar/Wind Harmer
4.312
316283AC2-100 C
Solar/Wind Harmer
0.223
227287AC2-120 GEN
Solar/Wind Helper
0.388
226910AB2-157 C
Solar/Wind Helper
0.015
972197AH1-683 GEN
50/50
4.454
972219AH1-694 GEN
50/50
3.207
315052AA1-145 CT2
50/50
1.579
966881AG1-559 GEN
Solar/Wind Harmer
0.23
3142416OLDCHRC
Solar/Wind Harmer
0.499
3142416OLDCHRC
Solar/Wind Harmer
0.191
3143096IRON208
Adder
0.776
3142543TWELFTH
Solar/Wind Harmer
0.018
944631AF1-128 GEN
Adder
87.636
3150851SPRUNCC
Adder
0.844
316159AE1-175 C
Solar/Wind Harmer
0.156
3143526WINTERP
Solar/Wind Harmer
0.937
970129AG2-093 GEN
Solar/Wind Harmer
5.114
316458AB2-190 GEN2
Solar/Wind Harmer
0.964
971069AG2-661 GEN
Solar/Wind Harmer
3.182
315671AE2-027_GEN
Solar/Wind Harmer
11.444
971647AH1-324 GEN
Solar/Wind Harmer
7.594
971317AH1-138 GEN
Solar/Wind Harmer
1.327
3138126ROCKLANDING
Solar/Wind Harmer
0.082
961611AG1-000B GEN
Solar/Wind Harmer
9.303
3142433PROV 92
Solar/Wind Harmer
0.707
3142433PROV 92
Adder
0.344
3142433PROV 92
Adder
0.344
3143226MDLTHAN
Solar/Wind Harmer
0.177
3151171GRAVELC
Adder
1.879
316294AC1-161 GEN
Solar/Wind Harmer
3.05
3145336SMITFLD
Solar/Wind Harmer
0.702
970659AG2-427 GEN
Solar/Wind Harmer
8.414
316375AC2-012 GEN
Solar/Wind Harmer
0.004
3150981CHESPKA
Adder
2.17
316381AD1-082 GEN
Solar/Wind Harmer
0.181
944591AF1-124 GEN
Solar/Wind Harmer
39.254
970661AG2-428 GEN
Solar/Wind Harmer
17.23
316072AD1-144
Solar/Wind Harmer
0.063
3141766HARMONY
Solar/Wind Harmer
0.035
971777AH1-397 GEN
Solar/Wind Harmer
0.455
3141843SHACKLE
Adder
0.88
316388AE2-253 GEN
Solar/Wind Harmer
0.539
3146456SLIGO L269
Solar/Wind Harmer
0.172
316246AF1-032 C
Solar/Wind Harmer
0.077
316093AE2-104_GEN
Solar/Wind Harmer
2.869
939411AE1-173 GEN
Solar/Wind Harmer
72.314
940641AE2-051 GEN
Solar/Wind Harmer
13.462
3146516WINFALL
Solar/Wind Harmer
0.544
3146516WINFALL
Solar/Wind Harmer
0.168
3138133OCRAN
Solar/Wind Harmer
0.1
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.163
3145663CRESWEL
Solar/Wind Harmer
0.447
971163AH1-040 GEN
Solar/Wind Harmer
12.788
962861AG1-135 GEN
Solar/Wind Harmer
5.018
3143336POWHATN
Solar/Wind Harmer
2.779
3146206CASHIE
Solar/Wind Harmer
0.155
971547AH1-271 GEN
Solar/Wind Harmer
3.308
3145893MURPHYS
Solar/Wind Harmer
0.617
3145893MURPHYS
Solar/Wind Harmer
0.686
316023GEN1_S
Solar/Wind Harmer
0.345
3141726DUNNSVL
Solar/Wind Harmer
0.612
3146173TUNIS
Solar/Wind Harmer
0.153
970919AG2-571 GEN
Solar/Wind Harmer
5.402
3145683EARLEYS
Solar/Wind Harmer
0.151
970087AG2-069 GEN
Solar/Wind Harmer
12.113
316336AC2-165 C
Solar/Wind Harmer
0.006
3146263WOODLND
Solar/Wind Harmer
0.15
960081AF2-299 GEN
Solar/Wind Harmer
1.442
3150351NORNECKC2
Adder
1.495
3145963POPLR C
Solar/Wind Harmer
0.149
3145823KELFORD
Solar/Wind Harmer
0.149
316011AB1-132 GEN
Solar/Wind Harmer
2.696
962571AG1-106 GEN
Solar/Wind Harmer
2.11
316174AB2-169 GEN
Solar/Wind Harmer
0.004
316190AA2-174 GEN
Solar/Wind Harmer
0
971795AH1-408 GEN
Solar/Wind Harmer
9.812
957481AF2-042 GEN
Solar/Wind Harmer
39.137
3145783HORNRTN
Solar/Wind Harmer
0.146
3145796HORNRTN
Solar/Wind Harmer
0.482
3145796HORNRTN
Solar/Wind Harmer
0.146
3147043LAWRENC
Adder
1.319
315693AD1-088 GEN
Solar/Wind Harmer
6.943
962491AG1-098 GEN
Solar/Wind Harmer
8.237
3146293MARTNCO
Solar/Wind Harmer
0.133
316212AC1-099_GEN
Solar/Wind Harmer
0.741
972277AH1-723 GEN
Adder
84.669
3145746EVERETS
Solar/Wind Harmer
0.14
3145746EVERETS
Solar/Wind Harmer
0.14
316129AC1-054 GEN
Solar/Wind Harmer
0.527
316337AD2-073 GEN
Solar/Wind Harmer
0.122
971065AG2-659 GEN
Solar/Wind Harmer
5.957
315722AD1-056 GEN
Solar/Wind Harmer
0.882
316494AC1-189 GEN
Solar/Wind Harmer
0.467
970937AG2-583 GEN
Solar/Wind Harmer
8.414
961671AG1-007 GEN
Solar/Wind Harmer
0.021
3146083TARBORO
Solar/Wind Harmer
0.136
3145493TOT1
Solar/Wind Harmer
0.606
3146233WITAKRS
Solar/Wind Harmer
0.542
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315687AD1-152 GEN
Solar/Wind Harmer
0.004
970685AG2-442 GEN
Solar/Wind Harmer
10.095
963171AG1-166 GEN
Solar/Wind Harmer
0.72
971563AH1-280 GEN
Solar/Wind Harmer
1.44
3144293JTRSVLE
Adder
0.43
3146926FARMVIL
Solar/Wind Harmer
0.081
3145543BTLEBRO
Solar/Wind Harmer
0.134
3145543BTLEBRO
Solar/Wind Harmer
0.107
316359AB2-059 GEN
Solar/Wind Harmer
0.481
316049AB1-081 GEN
Solar/Wind Harmer
0.766
3142053HEARTS
Solar/Wind Harmer
0.236
3147666LOUISA
Solar/Wind Harmer
0.534
316192AB2-158 GEN
Solar/Wind Harmer
0.744
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.052
970401AG2-262 GEN
Solar/Wind Harmer
0.759
972003AH1-546 GEN
Solar/Wind Harmer
5.371
316003AC1-222 GEN
Solar/Wind Harmer
0.003
971377AH1-170 GEN
Solar/Wind Harmer
1.277
3147623JAMES R
Solar/Wind Harmer
0.277
NYPJM->LTFIMP_NY
CLTF
2.848
LGEELTFEXP_LGEE->PJM
CLTF
1.613
WECLTFEXP_WEC->PJM
CLTF
0.819
LAGNLTFEXP_LAGN->PJM
CLTF
7.576
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.212
TVALTFEXP_TVA->PJM
CLTF
3.836
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.893
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.398
MECLTFEXP_MEC->PJM
CLTF
4.164
SIGELTFEXP_SIGE->PJM
CLTF
0.129
CPLELTFEXP_CPLE->PJM
CLTF
8.886
CBM West 2LTFEXP_CBM-W2->PJM
CBM
42.062

Details for 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 545T552_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.2 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4696.32
MW Contribution:86.5
Bus #Bus NameTypeMW Contribution
315052AA1-145 CT2
50/50
1.588
972197AH1-683 GEN
50/50
4.413
972219AH1-694 GEN
50/50
3.177
966881AG1-559 GEN
Solar/Wind Harmer
0.23
3142416OLDCHRC
Solar/Wind Harmer
-0.056
3142416OLDCHRC
Solar/Wind Harmer
-0.022
3143096IRON208
Adder
0.787
3142543TWELFTH
Solar/Wind Harmer
-0.002
944631AF1-128 GEN
Adder
88.83
3150851SPRUNCC
Adder
0.858
3143526WINTERP
Solar/Wind Harmer
-0.107
316159AE1-175 C
Solar/Wind Harmer
0.552
970129AG2-093 GEN
Solar/Wind Harmer
4.679
316458AB2-190 GEN2
Solar/Wind Harmer
2.074
971069AG2-661 GEN
Solar/Wind Harmer
3.233
315671AE2-027_GEN
Solar/Wind Harmer
15.31
971647AH1-324 GEN
Solar/Wind Harmer
10.159
3143226MDLTHAN
Solar/Wind Harmer
-0.02
3138126ROCKLANDING
Solar/Wind Harmer
0.062
961611AG1-000B GEN
Solar/Wind Harmer
9.996
971317AH1-138 GEN
Solar/Wind Harmer
2.531
3151171GRAVELC
Adder
1.91
316294AC1-161 GEN
Solar/Wind Harmer
6.513
3142433PROV 92
Solar/Wind Harmer
-0.08
3142433PROV 92
Adder
0.348
3142433PROV 92
Adder
0.348
3145336SMITFLD
Solar/Wind Harmer
-0.08
970659AG2-427 GEN
Solar/Wind Harmer
10.57
316375AC2-012 GEN
Solar/Wind Harmer
6.881
3150981CHESPKA
Adder
2.209
944591AF1-124 GEN
Solar/Wind Harmer
90.743
316381AD1-082 GEN
Solar/Wind Harmer
1.823
970661AG2-428 GEN
Solar/Wind Harmer
21.05
316072AD1-144
Solar/Wind Harmer
0.4
316388AE2-253 GEN
Solar/Wind Harmer
1.329
3146456SLIGO L269
Solar/Wind Harmer
-0.02
316246AF1-032 C
Solar/Wind Harmer
0.397
3141766HARMONY
Solar/Wind Harmer
-0.004
971777AH1-397 GEN
Solar/Wind Harmer
2.297
3141843SHACKLE
Adder
0.888
316093AE2-104_GEN
Solar/Wind Harmer
5.675
939411AE1-173 GEN
Solar/Wind Harmer
97.222
940641AE2-051 GEN
Solar/Wind Harmer
18.116
3146516WINFALL
Solar/Wind Harmer
-0.062
3146516WINFALL
Solar/Wind Harmer
-0.019
315800Z1-036_GEN1
Solar/Wind Harmer
4.677
3138133OCRAN
Solar/Wind Harmer
-0.011
3130156CHOWAN
Solar/Wind Harmer
-0.019
3145663CRESWEL
Solar/Wind Harmer
-0.051
971163AH1-040 GEN
Solar/Wind Harmer
17.174
3143336POWHATN
Solar/Wind Harmer
2.14
961951AG1-038 GEN
Solar/Wind Harmer
2.365
3146206CASHIE
Solar/Wind Harmer
-0.018
971547AH1-271 GEN
Solar/Wind Harmer
4.446
3145893MURPHYS
Solar/Wind Harmer
-0.07
3145893MURPHYS
Solar/Wind Harmer
0.525
316023GEN1_S
Solar/Wind Harmer
1.191
962861AG1-135 GEN
Solar/Wind Harmer
6.62
3146173TUNIS
Solar/Wind Harmer
-0.017
970919AG2-571 GEN
Solar/Wind Harmer
5.533
316336AC2-165 C
Solar/Wind Harmer
3.03
970087AG2-069 GEN
Solar/Wind Harmer
16.334
3145683EARLEYS
Solar/Wind Harmer
-0.017
3146263WOODLND
Solar/Wind Harmer
-0.017
960081AF2-299 GEN
Solar/Wind Harmer
1.941
964211AG1-282 GEN
Solar/Wind Harmer
0.517
3141726DUNNSVL
Solar/Wind Harmer
-0.068
3145963POPLR C
Solar/Wind Harmer
-0.017
3145823KELFORD
Solar/Wind Harmer
-0.017
316011AB1-132 GEN
Solar/Wind Harmer
3.565
962571AG1-106 GEN
Solar/Wind Harmer
2.449
316174AB2-169 GEN
Solar/Wind Harmer
2.625
316190AA2-174 GEN
Solar/Wind Harmer
0.209
971795AH1-408 GEN
Solar/Wind Harmer
12.691
957481AF2-042 GEN
Solar/Wind Harmer
52.83
3150391LDYSMT3
50/50
28.208
972195AH1-682 GEN
50/50
3.707
957411AF2-035 GEN
Solar/Wind Harmer
10.059
970317AG2-208 GEN
Solar/Wind Harmer
9.78
315673AE1-157 GEN
Solar/Wind Harmer
16.754
3142296MT RD221
Adder
0.629
3142366NRTHEST
Adder
0.626
3150691DARBY 3
Adder
13.746
3150701DARBY 4
Adder
13.714
3150681DARBY 2
Adder
13.698
3150671DARBY 1
Adder
13.682
316075AC2-137 C
Solar/Wind Harmer
0.574
3142946ENON
Solar/Wind Harmer
-0.002
966871AG1-558 GEN
Solar/Wind Harmer
0.63
966871AG1-558 GEN
Solar/Wind Harmer
0.215
944641AF1-129 GEN
Adder
87.651
3143526WINTERP
Solar/Wind Harmer
-0.107
316240AF1-291 C
Solar/Wind Harmer
0.62
316033AB2-134 GEN
Solar/Wind Harmer
6.572
315697AD1-025 GEN
Solar/Wind Harmer
4.122
971223AH1-071 GEN
Solar/Wind Harmer
2.538
316236AE1-162_GEN
Solar/Wind Harmer
0.605
316036AC1-147 C
Solar/Wind Harmer
0.536
3150991CHESPKB
Adder
1.854
3150991CHESPKB
Adder
1.809
970657AG2-426 GEN
Solar/Wind Harmer
6.204
970657AG2-426 GEN
Solar/Wind Harmer
1.297
316316AC1-027 C
Solar/Wind Harmer
0.609
3142956BIRDNECK
Solar/Wind Harmer
1.065
316185AD1-033 GEN
Solar/Wind Harmer
2.09
3145506HICKORY
Solar/Wind Harmer
-0.079
3145506HICKORY
Solar/Wind Harmer
-0.047
3145506HICKORY
Solar/Wind Harmer
-0.012
316339AD2-160 GEN
Solar/Wind Harmer
1.329
316018AA1-139 ULT2
Solar/Wind Harmer
1.686
316017AA1-139 ULT1
Solar/Wind Harmer
1.593
3137176SLIGO L2192
Solar/Wind Harmer
-0.078
3146456SLIGO L269
Solar/Wind Harmer
2.32
3130086AYDLETT
Solar/Wind Harmer
-0.078
316441AF1-014 GEN
Solar/Wind Harmer
1.317
3146386ELIZ CT
Solar/Wind Harmer
-0.019
316431W1029_GEN1
Solar/Wind Harmer
3.49
316433W1029_GEN2
Solar/Wind Harmer
3.49
3146516WINFALL
Solar/Wind Harmer
-0.019
3146516WINFALL
Solar/Wind Harmer
-0.019
3146516WINFALL
Solar/Wind Harmer
-0.019
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3144356SAPONY
Solar/Wind Harmer
0.658
315742AE1-103 GEN
Solar/Wind Harmer
1.965
3146376EDENTON
Solar/Wind Harmer
0.555
3146376EDENTON
Solar/Wind Harmer
0.555
972185AH1-677 GEN
Adder
9.093
972187AH1-678 GEN
Adder
4.569
316487AF1-042 GEN
Solar/Wind Harmer
2.365
316065AD1-022 GEN
Solar/Wind Harmer
8.924
970933AG2-581 GEN
Solar/Wind Harmer
16.701
3145893MURPHYS
Solar/Wind Harmer
0.494
3145893MURPHYS
Solar/Wind Harmer
-0.032
3146173TUNIS
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.017
958261AF2-120 GEN
Solar/Wind Harmer
6.798
316181AB2-040 GEN
Solar/Wind Harmer
2.384
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
316426AA2-053 GEN
Solar/Wind Harmer
1.717
3145593CAROLNA
Solar/Wind Harmer
-0.017
3145593CAROLNA
Solar/Wind Harmer
-0.017
966811AG1-552 GEN
Solar/Wind Harmer
1.903
3145593CAROLNA
Solar/Wind Harmer
0.14
970099AG2-077 GEN
Solar/Wind Harmer
21.132
3145783HORNRTN
Solar/Wind Harmer
1.996
3145783HORNRTN
Solar/Wind Harmer
1.597
3145783HORNRTN
Solar/Wind Harmer
0.499
3145783HORNRTN
Solar/Wind Harmer
0.2
316077AC2-138 C
Solar/Wind Harmer
0.355
3150341NORNECKC1
Adder
1.567
3150341NORNECKC1
Adder
1.555
3145796HORNRTN
Solar/Wind Harmer
-0.05
316468AD1-105 GEN
Solar/Wind Harmer
1.853
3145933PARMELE
Solar/Wind Harmer
-0.033
3145933PARMELE
Solar/Wind Harmer
-0.016
316274AC1-208 GEN
Solar/Wind Harmer
1.764
3144293JTRSVLE
Adder
0.442
3144293JTRSVLE
Adder
0.372
226929AD2-058 GEN
Solar/Wind Helper
0.128
971531AH1-263 GEN
50/50
39.714
972189AH1-679 GEN
50/50
3.545
3150411LDYSMT5
50/50
28.349
3150381LDYSMT2
50/50
27.131
972213AH1-691 GEN
50/50
4.59
972215AH1-692 GEN
50/50
4.59
316312AB1-027
Solar/Wind Harmer
0.736
315976AC1-164 GENA
Solar/Wind Harmer
22.253
316169AC1-164_GENC
Solar/Wind Harmer
19.225
315975AC1-164 GENB
Solar/Wind Harmer
0.658
971285AH1-108 GEN
Adder
1.403
316233AE1-074 FULL
Solar/Wind Harmer
0.556
971281AH1-106 GEN
Solar/Wind Harmer
3.356
971283AH1-107 GEN
Solar/Wind Harmer
3.356
316132AB2-190 GEN1
Solar/Wind Harmer
2.074
316369SG1_INVT
Solar/Wind Harmer
3.641
972265AH1-717 GEN
Adder
13.944
3151201GRAVEL4
Adder
13.072
3151191GRAVEL3
Adder
12.906
3151211GRAVEL5
Adder
12.906
971167AH1-042 GEN
Solar/Wind Harmer
19.411
3142433PROV 92
Adder
0.348
3142433PROV 92
Adder
0.348
971445AH1-216 GEN
Solar/Wind Harmer
12.425
3143316POE
Solar/Wind Harmer
-0.078
3151081ELIZAR1
Adder
16.225
3151091ELIZAR2
Adder
15.943
3152611GOSPORTB
Adder
2.253
3152621GOSPORTC
Adder
1.912
3152601GOSPORTA
Adder
1.764
3143873LANEXA
Solar/Wind Harmer
-0.012
957831AF2-077 GEN
Solar/Wind Harmer
0.596
3138283WHITEMARSH
Solar/Wind Harmer
0.031
316314AB2-024 C
Solar/Wind Harmer
1.685
957871AF2-081 GEN
Solar/Wind Harmer
9.844
315833AF1-017_GEN
Solar/Wind Harmer
3.733
316349AD2-085 GEN
Solar/Wind Harmer
1.748
316311AC2-079 GEN
Solar/Wind Harmer
9.912
319010AE1-072 C
Solar/Wind Harmer
3.972
3146406KITTY HAWK
Solar/Wind Harmer
0.016
316305AF2-043 C
Solar/Wind Harmer
0.591
316059AD1-063 C
Solar/Wind Harmer
0.442
315835AF2-110_GEN
Solar/Wind Harmer
2.44
313526AB2-022
Solar/Wind Harmer
0.525
315662AE1-191 GEN
Solar/Wind Harmer
2.344
315666AE1-190 GEN
Solar/Wind Harmer
0.586
3146486SUNBURY
Solar/Wind Harmer
-0.019
3146486SUNBURY
Solar/Wind Harmer
-0.019
316321Z2-027
Solar/Wind Harmer
0.523
3146396TANGLEW
Solar/Wind Harmer
0.356
3145176PASQUOTANK
Solar/Wind Harmer
-0.012
957601AF2-054 GEN
Solar/Wind Harmer
0.578
3141873WAN 176
Solar/Wind Harmer
-0.004
3141913WHIT STONE
Solar/Wind Harmer
-0.019
315611Z1-036_GEN2
Solar/Wind Harmer
4.677
316315AB2-025 C
Solar/Wind Harmer
0.509
3138133OCRAN
Solar/Wind Harmer
-0.006
315814AE2-033 C
Solar/Wind Harmer
17.521
3130156CHOWAN
Solar/Wind Harmer
-0.019
3130156CHOWAN
Solar/Wind Harmer
-0.019
3141783LANCAST
Solar/Wind Harmer
-0.011
3141783LANCAST
Solar/Wind Harmer
-0.007
941031AE2-094 GEN
Solar/Wind Harmer
34.885
944011AF1-069 GEN
Solar/Wind Harmer
10.931
970673AG2-436 GEN
Solar/Wind Harmer
38.527
970673AG2-436 GEN
Solar/Wind Harmer
19.507
315816AE2-034 GEN
Solar/Wind Harmer
1.482
962981AG1-147 GEN
Solar/Wind Harmer
7.964
971967AH1-528 GEN
Solar/Wind Harmer
34.143
3130546PLYMOUTH
Solar/Wind Harmer
-0.018
315732AD1-074 GEN1
Solar/Wind Harmer
3.633
315733AD1-074 GEN2
Solar/Wind Harmer
3.633
315735AD1-075 GEN1
Solar/Wind Harmer
1.817
965291AG1-394 GEN
Solar/Wind Harmer
1.584
3146206CASHIE
Solar/Wind Harmer
-0.018
970601AG2-382 GEN
Solar/Wind Harmer
7.78
316318V4-068
Solar/Wind Harmer
0.441
3145893MURPHYS
Solar/Wind Harmer
-0.047
3145893MURPHYS
Solar/Wind Harmer
-0.018
3145513AHOSKIE
Solar/Wind Harmer
0.152
961941AG1-037 GEN
Solar/Wind Harmer
0.131
3145513AHOSKIE
Solar/Wind Harmer
-0.017
970085AG2-068 GEN
Solar/Wind Harmer
10.889
970581AG2-369 GEN
Solar/Wind Harmer
9.365
3145683EARLEYS
Solar/Wind Harmer
-0.035
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.017
3146043SEABORD
Solar/Wind Harmer
-0.017
315607AA1-063A GEN
Solar/Wind Harmer
1.746
946281AF1-292 GEN
Solar/Wind Harmer
0.386
316087AB2-174 GEN
Solar/Wind Harmer
2.445
315652AC1-086 GEN
Solar/Wind Harmer
19.168
3137643SOCKMAN
Solar/Wind Harmer
-0.068
3141813NORNECK
Solar/Wind Harmer
-0.017
3145796HORNRTN
Solar/Wind Harmer
-0.053
3145796HORNRTN
Solar/Wind Harmer
-0.007
3146033SCOT NK
Solar/Wind Harmer
-0.067
972193AH1-681 GEN
Adder
3.317
972205AH1-687 GEN
Adder
5.556
970831AG2-522 GEN
Solar/Wind Harmer
4.191
970497AG2-320 GEN
50/50
20.535
971645AH1-323 GEN
50/50
17.746
315051AA1-145 CT1
50/50
1.581
3150401LDYSMT4
50/50
28.261
3150371LDYSMT1
50/50
27.308
966881AG1-559 GEN
Solar/Wind Harmer
0.672
3142416OLDCHRC
Solar/Wind Harmer
2.201
970293AG2-193 GEN
Solar/Wind Harmer
2.672
3143096IRON208
Adder
0.787
3143096IRON208
Adder
0.771
3142946ENON
Solar/Wind Harmer
-0.007
316473AC1-191 GEN
Solar/Wind Harmer
2.254
3150861SPRUNCD
Adder
0.858
970133AG2-095 GEN
Solar/Wind Harmer
2.321
316382AG1-145 C
Solar/Wind Harmer
0.62
970129AG2-093 GEN
Solar/Wind Harmer
11.551
315778AD1-151 GEN
Solar/Wind Harmer
17.699
965281AG1-393 GEN
Solar/Wind Harmer
2.545
315839AE2-212 C
Solar/Wind Harmer
0.613
3150921YORKTN3
Adder
4.533
3144216WINCHST
Adder
0.68
961611AG1-000B GEN
Solar/Wind Harmer
4.265
3151221GRAVEL6
Adder
13.057
3151171GRAVELC
Adder
2.512
315773AC2-141 GEN
Solar/Wind Harmer
8.424
3142433PROV 92
Adder
0.348
3142433PROV 92
Adder
0.348
3145336SMITFLD
Solar/Wind Harmer
-0.008
315813AE1-149 C
Solar/Wind Harmer
12.509
3144536CHRHLND
Solar/Wind Harmer
-0.003
970659AG2-427 GEN
Solar/Wind Harmer
1.873
3151101ELIZAR3
Adder
16.432
944581AF1-123 GEN
Solar/Wind Harmer
90.418
944601AF1-125 GEN
Solar/Wind Harmer
89.007
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316083AB2-161 GEN
Solar/Wind Harmer
3.226
970661AG2-428 GEN
Solar/Wind Harmer
3.73
3146456SLIGO L269
Solar/Wind Harmer
-0.02
971153AH1-033 GEN
Solar/Wind Harmer
2.395
3141766HARMONY
Solar/Wind Harmer
1.741
3141843SHACKLE
Adder
0.888
316203AE2-005 GEN
Solar/Wind Harmer
8.236
316320Y1-086
Solar/Wind Harmer
1.14
316280AD1-041 GEN
Solar/Wind Harmer
1.465
316156AD2-030 GEN
Solar/Wind Harmer
0.516
3141873WAN 176
Solar/Wind Harmer
2.292
316435W1029_GEN3
Solar/Wind Harmer
3.49
3146516WINFALL
Solar/Wind Harmer
-0.019
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3145273HOLLAND
Solar/Wind Harmer
-0.014
3146376EDENTON
Solar/Wind Harmer
-0.019
315614AA2-178 GEN
Solar/Wind Harmer
1.976
962971AG1-146 GEN
Solar/Wind Harmer
3.413
316313AB2-026
Solar/Wind Harmer
0.486
316258AE1-075 C
Solar/Wind Harmer
0.438
316405AF2-144 C
Solar/Wind Harmer
0.462
3143336POWHATN
Solar/Wind Harmer
1.819
971157AH1-035 GEN
Solar/Wind Harmer
2.252
315737AD1-076 GEN
Solar/Wind Harmer
3.414
316484AD2-074 GEN
Solar/Wind Harmer
4.519
970009AG2-005 GEN
Solar/Wind Harmer
2.244
3156081AA2-088 GEN
Solar/Wind Harmer
5.819
3146206CASHIE
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
0.124
3145893MURPHYS
Solar/Wind Harmer
-0.018
316365GEN2_N
Solar/Wind Harmer
1.191
957521AF2-046 GEN
Solar/Wind Harmer
13.906
961681AG1-008 GEN
Solar/Wind Harmer
13.906
3146173TUNIS
Solar/Wind Harmer
-0.017
316404AE1-155 C
Solar/Wind Harmer
3.384
3156021HOLLOMANSOL
Solar/Wind Harmer
2.361
970917AG2-570 GEN
Solar/Wind Harmer
43.708
316463AE2-346 GEN
Solar/Wind Harmer
0.283
316140AB2-099
Solar/Wind Harmer
0.118
962331AG1-082 GEN
Solar/Wind Harmer
2.183
3146263WOODLND
Solar/Wind Harmer
-0.017
966621AG1-532 GEN
Solar/Wind Harmer
0.35
3145963POPLR C
Solar/Wind Harmer
-0.017
313506AB2-031 GEN
Solar/Wind Harmer
1.374
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
316317KELFORD C
Solar/Wind Harmer
0.804
3145823KELFORD
Solar/Wind Harmer
-0.017
3150351NORNECKC2
Adder
1.517
3145796HORNRTN
Solar/Wind Harmer
-0.067
3145796HORNRTN
Solar/Wind Harmer
-0.017
3147043LAWRENC
Solar/Wind Harmer
-0.01
971781AH1-399 GEN
Solar/Wind Harmer
1.025
3145933PARMELE
Solar/Wind Harmer
-0.016
966801AG1-551 GEN
Solar/Wind Harmer
2.058
316210AC1-098 GEN
Solar/Wind Harmer
2.585
316478AD1-087 GEN
Solar/Wind Harmer
1.419
316486AD2-202 GEN
Solar/Wind Harmer
0.416
972255AH1-712 GEN
Adder
74.234
3144293JTRSVLE
Adder
0.442
227287AC2-120 GEN
Solar/Wind Helper
0.418
226910AB2-157 C
Solar/Wind Helper
0.017
3145783HORNRTN
Solar/Wind Harmer
-0.017
3150351NORNECKC2
Adder
1.492
3145796HORNRTN
Solar/Wind Harmer
-0.055
3145796HORNRTN
Solar/Wind Harmer
-0.017
3147043LAWRENC
Adder
1.35
315693AD1-088 GEN
Solar/Wind Harmer
8.336
962491AG1-098 GEN
Solar/Wind Harmer
11.128
3146293MARTNCO
Solar/Wind Harmer
0.102
316212AC1-099_GEN
Solar/Wind Harmer
1.436
972277AH1-723 GEN
Adder
86.505
3144293JTRSVLE
Adder
0.442
NYPJM->LTFIMP_NY
CLTF
2.987
LGEELTFEXP_LGEE->PJM
CLTF
1.72
WECLTFEXP_WEC->PJM
CLTF
0.877
LAGNLTFEXP_LAGN->PJM
CLTF
7.934
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.871
TVALTFEXP_TVA->PJM
CLTF
4.016
CBM West 1LTFEXP_CBM-W1->PJM
CBM
31.014
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.058
MECLTFEXP_MEC->PJM
CLTF
4.425
SIGELTFEXP_SIGE->PJM
CLTF
0.137
CPLELTFEXP_CPLE->PJM
CLTF
9.143
CBM West 2LTFEXP_CBM-W2->PJM
CBM
44.304

Details for 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T594_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 545T594_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.13 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4535.93
MW Contribution:80.59
Bus #Bus NameTypeMW Contribution
972189AH1-679 GEN
50/50
3.41
316312AB1-027
Solar/Wind Harmer
0.719
316233AE1-074 FULL
Solar/Wind Harmer
0.569
971281AH1-106 GEN
Solar/Wind Harmer
3.437
971283AH1-107 GEN
Solar/Wind Harmer
3.437
971285AH1-108 GEN
Adder
1.413
3150411LDYSMT5
Adder
25.004
3150381LDYSMT2
Adder
23.93
972213AH1-691 GEN
Adder
4.048
972215AH1-692 GEN
Adder
4.048
315976AC1-164 GENA
Solar/Wind Harmer
21.931
316169AC1-164_GENC
Solar/Wind Harmer
18.947
315975AC1-164 GENB
Solar/Wind Harmer
0.649
316132AB2-190 GEN1
Solar/Wind Harmer
2.078
316369SG1_INVT
Solar/Wind Harmer
3.654
972265AH1-717 GEN
Adder
14.028
3151201GRAVEL4
Adder
13.151
3151191GRAVEL3
Adder
12.984
3151211GRAVEL5
Adder
12.984
3143316POE
Solar/Wind Harmer
-0.08
971445AH1-216 GEN
Solar/Wind Harmer
12.527
3151081ELIZAR1
Adder
16.427
3151091ELIZAR2
Adder
16.142
3152611GOSPORTB
Adder
2.281
3152621GOSPORTC
Adder
1.936
3152601GOSPORTA
Adder
1.786
971167AH1-042 GEN
Solar/Wind Harmer
19.307
3142433PROV 92
Adder
0.346
3142433PROV 92
Adder
0.346
957871AF2-081 GEN
Solar/Wind Harmer
9.972
315833AF1-017_GEN
Solar/Wind Harmer
3.78
316349AD2-085 GEN
Solar/Wind Harmer
1.77
316311AC2-079 GEN
Solar/Wind Harmer
10.038
319010AE1-072 C
Solar/Wind Harmer
4.024
3146406KITTY HAWK
Solar/Wind Harmer
0.017
316305AF2-043 C
Solar/Wind Harmer
0.599
957831AF2-077 GEN
Solar/Wind Harmer
0.595
3138283WHITEMARSH
Solar/Wind Harmer
0.031
315835AF2-110_GEN
Solar/Wind Harmer
2.472
3143873LANEXA
Solar/Wind Harmer
-0.012
313526AB2-022
Solar/Wind Harmer
0.532
3146486SUNBURY
Solar/Wind Harmer
-0.02
3146486SUNBURY
Solar/Wind Harmer
-0.02
316321Z2-027
Solar/Wind Harmer
0.529
3146396TANGLEW
Solar/Wind Harmer
0.361
3145176PASQUOTANK
Solar/Wind Harmer
-0.012
316314AB2-024 C
Solar/Wind Harmer
1.673
316059AD1-063 C
Solar/Wind Harmer
0.44
315662AE1-191 GEN
Solar/Wind Harmer
2.334
315666AE1-190 GEN
Solar/Wind Harmer
0.583
941031AE2-094 GEN
Solar/Wind Harmer
36.29
944011AF1-069 GEN
Solar/Wind Harmer
11.371
316315AB2-025 C
Solar/Wind Harmer
0.522
315814AE2-033 C
Solar/Wind Harmer
17.949
957601AF2-054 GEN
Solar/Wind Harmer
0.576
3141873WAN 176
Solar/Wind Harmer
-0.004
315611Z1-036_GEN2
Solar/Wind Harmer
4.742
970673AG2-436 GEN
Solar/Wind Harmer
40.043
970673AG2-436 GEN
Solar/Wind Harmer
20.275
3130156CHOWAN
Solar/Wind Harmer
-0.019
3130156CHOWAN
Solar/Wind Harmer
-0.019
3141913WHIT STONE
Solar/Wind Harmer
-0.019
971967AH1-528 GEN
Solar/Wind Harmer
35.457
3138133OCRAN
Solar/Wind Harmer
-0.006
3141783LANCAST
Solar/Wind Harmer
-0.011
3141783LANCAST
Solar/Wind Harmer
-0.007
315816AE2-034 GEN
Solar/Wind Harmer
1.504
3130546PLYMOUTH
Solar/Wind Harmer
-0.018
315732AD1-074 GEN1
Solar/Wind Harmer
3.686
315733AD1-074 GEN2
Solar/Wind Harmer
3.686
315735AD1-075 GEN1
Solar/Wind Harmer
1.844
962981AG1-147 GEN
Solar/Wind Harmer
7.96
965291AG1-394 GEN
Solar/Wind Harmer
1.61
3146206CASHIE
Solar/Wind Harmer
-0.018
970601AG2-382 GEN
Solar/Wind Harmer
7.898
970085AG2-068 GEN
Solar/Wind Harmer
11.282
970581AG2-369 GEN
Solar/Wind Harmer
9.703
316318V4-068
Solar/Wind Harmer
0.448
3145893MURPHYS
Solar/Wind Harmer
-0.048
3145893MURPHYS
Solar/Wind Harmer
-0.018
3145513AHOSKIE
Solar/Wind Harmer
0.155
961941AG1-037 GEN
Solar/Wind Harmer
0.133
3145513AHOSKIE
Solar/Wind Harmer
-0.018
3145683EARLEYS
Solar/Wind Harmer
-0.035
3145683EARLEYS
Solar/Wind Harmer
-0.018
3145683EARLEYS
Solar/Wind Harmer
-0.018
3146043SEABORD
Solar/Wind Harmer
-0.018
946281AF1-292 GEN
Solar/Wind Harmer
0.395
315607AA1-063A GEN
Solar/Wind Harmer
1.777
316087AB2-174 GEN
Solar/Wind Harmer
2.495
315652AC1-086 GEN
Solar/Wind Harmer
19.533
3137643SOCKMAN
Solar/Wind Harmer
-0.069
3145796HORNRTN
Solar/Wind Harmer
-0.054
3145796HORNRTN
Solar/Wind Harmer
-0.007
3146033SCOT NK
Solar/Wind Harmer
-0.068
3141813NORNECK
Solar/Wind Harmer
-0.017
972193AH1-681 GEN
Adder
3.09
972205AH1-687 GEN
Adder
5.621
3152251N ANNA1
50/50
11.182
315052AA1-145 CT2
50/50
1.528
316045AC1-158 PL2
Solar/Wind Harmer
8.338
3142416OLDCHRC
Solar/Wind Harmer
-0.055
3142416OLDCHRC
Solar/Wind Harmer
-0.021
966881AG1-559 GEN
Solar/Wind Harmer
0.218
3143526WINTERP
Solar/Wind Harmer
-0.109
3143226MDLTHAN
Solar/Wind Harmer
-0.021
3150851SPRUNCC
Adder
0.863
3143096IRON208
Adder
0.782
3142543TWELFTH
Solar/Wind Harmer
-0.002
972197AH1-683 GEN
Adder
3.892
972219AH1-694 GEN
Adder
2.802
944631AF1-128 GEN
Adder
88.257
970129AG2-093 GEN
Solar/Wind Harmer
4.687
316458AB2-190 GEN2
Solar/Wind Harmer
2.078
315671AE2-027_GEN
Solar/Wind Harmer
15.394
971069AG2-661 GEN
Solar/Wind Harmer
3.242
316159AE1-175 C
Solar/Wind Harmer
0.549
971647AH1-324 GEN
Solar/Wind Harmer
10.202
316294AC1-161 GEN
Solar/Wind Harmer
6.591
961611AG1-000B GEN
Solar/Wind Harmer
10.047
3151171GRAVELC
Adder
1.922
3138126ROCKLANDING
Solar/Wind Harmer
0.062
3145336SMITFLD
Solar/Wind Harmer
-0.081
971317AH1-138 GEN
Solar/Wind Harmer
2.528
944591AF1-124 GEN
Solar/Wind Harmer
91.948
316375AC2-012 GEN
Solar/Wind Harmer
6.965
3150981CHESPKA
Adder
2.237
970659AG2-427 GEN
Solar/Wind Harmer
10.696
316381AD1-082 GEN
Solar/Wind Harmer
1.844
970661AG2-428 GEN
Solar/Wind Harmer
21.306
939411AE1-173 GEN
Solar/Wind Harmer
100.174
940641AE2-051 GEN
Solar/Wind Harmer
18.774
3142433PROV 92
Solar/Wind Harmer
-0.08
3142433PROV 92
Adder
0.346
3142433PROV 92
Adder
0.346
316072AD1-144
Solar/Wind Harmer
0.404
316388AE2-253 GEN
Solar/Wind Harmer
1.346
3146456SLIGO L269
Solar/Wind Harmer
-0.02
316246AF1-032 C
Solar/Wind Harmer
0.402
316093AE2-104_GEN
Solar/Wind Harmer
5.749
3146516WINFALL
Solar/Wind Harmer
-0.063
3146516WINFALL
Solar/Wind Harmer
-0.019
3141766HARMONY
Solar/Wind Harmer
-0.004
971777AH1-397 GEN
Solar/Wind Harmer
2.287
3141843SHACKLE
Adder
0.884
315800Z1-036_GEN1
Solar/Wind Harmer
4.742
3130156CHOWAN
Solar/Wind Harmer
-0.019
3138133OCRAN
Solar/Wind Harmer
-0.011
3147666LOUISA
Solar/Wind Harmer
-0.074
3143336POWHATN
Solar/Wind Harmer
2.208
3145663CRESWEL
Solar/Wind Harmer
-0.052
971163AH1-040 GEN
Solar/Wind Harmer
17.421
316192AB2-158 GEN
Solar/Wind Harmer
2.18
970919AG2-571 GEN
Solar/Wind Harmer
5.734
3146206CASHIE
Solar/Wind Harmer
-0.018
971547AH1-271 GEN
Solar/Wind Harmer
4.513
970087AG2-069 GEN
Solar/Wind Harmer
16.924
316023GEN1_S
Solar/Wind Harmer
1.216
3145893MURPHYS
Solar/Wind Harmer
-0.072
3145893MURPHYS
Solar/Wind Harmer
0.534
961951AG1-038 GEN
Solar/Wind Harmer
2.365
316336AC2-165 C
Solar/Wind Harmer
3.117
3146173TUNIS
Solar/Wind Harmer
-0.018
3145683EARLEYS
Solar/Wind Harmer
-0.018
962861AG1-135 GEN
Solar/Wind Harmer
6.627
960081AF2-299 GEN
Solar/Wind Harmer
1.982
3146263WOODLND
Solar/Wind Harmer
-0.017
957481AF2-042 GEN
Solar/Wind Harmer
54.551
3145963POPLR C
Solar/Wind Harmer
-0.017
316011AB1-132 GEN
Solar/Wind Harmer
3.633
962571AG1-106 GEN
Solar/Wind Harmer
2.496
3145823KELFORD
Solar/Wind Harmer
-0.017
316190AA2-174 GEN
Solar/Wind Harmer
0.213
316174AB2-169 GEN
Solar/Wind Harmer
2.665
971795AH1-408 GEN
Solar/Wind Harmer
12.961
964211AG1-282 GEN
Solar/Wind Harmer
0.518
3141726DUNNSVL
Solar/Wind Harmer
-0.069
315693AD1-088 GEN
Solar/Wind Harmer
8.593
962491AG1-098 GEN
Solar/Wind Harmer
11.467
3145783HORNRTN
Solar/Wind Harmer
-0.017
3147043LAWRENC
Adder
1.379
3145796HORNRTN
Solar/Wind Harmer
-0.056
3145796HORNRTN
Solar/Wind Harmer
-0.017
3150351NORNECKC2
Adder
1.498
3144293JTRSVLE
Adder
0.452
972277AH1-723 GEN
Adder
80.59
3151751LOISA D
Adder
7.458
316212AC1-099_GEN
Solar/Wind Harmer
0.862
3142296MT RD221
50/50
0.65
3142366NRTHEST
50/50
0.655
3150691DARBY 3
50/50
14.384
3150701DARBY 4
50/50
14.351
316447AC1-158 HLD
Solar/Wind Harmer
5.732
957411AF2-035 GEN
Solar/Wind Harmer
9.538
970317AG2-208 GEN
Solar/Wind Harmer
9.273
3150681DARBY 2
Adder
13.508
3150671DARBY 1
Adder
13.493
3143526WINTERP
Solar/Wind Harmer
-0.109
971223AH1-071 GEN
Solar/Wind Harmer
2.643
315673AE1-157 GEN
Solar/Wind Harmer
15.81
316075AC2-137 C
Solar/Wind Harmer
0.565
3150391LDYSMT3
Adder
24.879
972195AH1-682 GEN
Adder
3.27
3142946ENON
Solar/Wind Harmer
-0.002
944641AF1-129 GEN
Adder
87.852
316240AF1-291 C
Solar/Wind Harmer
0.622
966871AG1-558 GEN
Solar/Wind Harmer
0.616
966871AG1-558 GEN
Solar/Wind Harmer
0.211
316033AB2-134 GEN
Solar/Wind Harmer
6.595
315697AD1-025 GEN
Solar/Wind Harmer
4.136
316236AE1-162_GEN
Solar/Wind Harmer
0.61
316036AC1-147 C
Solar/Wind Harmer
0.543
3150991CHESPKB
Adder
1.876
3150991CHESPKB
Adder
1.831
316316AC1-027 C
Solar/Wind Harmer
0.617
3142956BIRDNECK
Solar/Wind Harmer
1.078
970657AG2-426 GEN
Solar/Wind Harmer
6.278
970657AG2-426 GEN
Solar/Wind Harmer
1.313
316185AD1-033 GEN
Solar/Wind Harmer
2.117
3145506HICKORY
Solar/Wind Harmer
-0.08
3145506HICKORY
Solar/Wind Harmer
-0.048
3145506HICKORY
Solar/Wind Harmer
-0.012
316339AD2-160 GEN
Solar/Wind Harmer
1.346
316018AA1-139 ULT2
Solar/Wind Harmer
1.708
316017AA1-139 ULT1
Solar/Wind Harmer
1.614
3137176SLIGO L2192
Solar/Wind Harmer
-0.079
3146456SLIGO L269
Solar/Wind Harmer
2.351
3130086AYDLETT
Solar/Wind Harmer
-0.079
3146386ELIZ CT
Solar/Wind Harmer
-0.02
316431W1029_GEN1
Solar/Wind Harmer
3.536
316433W1029_GEN2
Solar/Wind Harmer
3.536
3146516WINFALL
Solar/Wind Harmer
-0.019
3146516WINFALL
Solar/Wind Harmer
-0.019
3146516WINFALL
Solar/Wind Harmer
-0.019
316441AF1-014 GEN
Solar/Wind Harmer
1.311
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3144356SAPONY
Solar/Wind Harmer
0.675
315742AE1-103 GEN
Solar/Wind Harmer
1.993
3146376EDENTON
Solar/Wind Harmer
0.563
3146376EDENTON
Solar/Wind Harmer
0.563
972185AH1-677 GEN
Adder
9.446
972187AH1-678 GEN
Adder
4.744
970933AG2-581 GEN
Solar/Wind Harmer
17.317
316065AD1-022 GEN
Solar/Wind Harmer
9.058
3145893MURPHYS
Solar/Wind Harmer
0.502
3145893MURPHYS
Solar/Wind Harmer
-0.032
316487AF1-042 GEN
Solar/Wind Harmer
2.365
3146173TUNIS
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
958261AF2-120 GEN
Solar/Wind Harmer
6.808
970099AG2-077 GEN
Solar/Wind Harmer
21.82
316181AB2-040 GEN
Solar/Wind Harmer
2.432
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
316426AA2-053 GEN
Solar/Wind Harmer
1.749
3145593CAROLNA
Solar/Wind Harmer
-0.017
3145593CAROLNA
Solar/Wind Harmer
-0.017
966811AG1-552 GEN
Solar/Wind Harmer
1.939
3145593CAROLNA
Solar/Wind Harmer
0.143
3145783HORNRTN
Solar/Wind Harmer
2.034
3145783HORNRTN
Solar/Wind Harmer
1.627
3145783HORNRTN
Solar/Wind Harmer
0.508
3145783HORNRTN
Solar/Wind Harmer
0.203
3145796HORNRTN
Solar/Wind Harmer
-0.051
316077AC2-138 C
Solar/Wind Harmer
0.356
3150341NORNECKC1
Adder
1.573
3150341NORNECKC1
Adder
1.56
3144293JTRSVLE
Adder
0.452
3144293JTRSVLE
Adder
0.38
3151731LOISA B
Adder
7.458
3151721LOISA A
Adder
7.419
226929AD2-058 GEN
Solar/Wind Helper
0.114
3152261N ANNA2
50/50
11.181
970497AG2-320 GEN
50/50
19.067
971645AH1-323 GEN
50/50
17.222
315051AA1-145 CT1
50/50
1.521
316044AC1-158 PL1
Solar/Wind Harmer
2.607
316450AC1-158 RIC
Solar/Wind Harmer
0.695
3142416OLDCHRC
Solar/Wind Harmer
2.152
966881AG1-559 GEN
Solar/Wind Harmer
0.637
970293AG2-193 GEN
Solar/Wind Harmer
2.633
3150861SPRUNCD
Adder
0.863
3143096IRON208
Adder
0.782
3143096IRON208
Adder
0.767
3150401LDYSMT4
Adder
24.926
3150371LDYSMT1
Adder
24.085
3142946ENON
Solar/Wind Harmer
-0.007
970133AG2-095 GEN
Solar/Wind Harmer
2.322
970129AG2-093 GEN
Solar/Wind Harmer
11.571
315839AE2-212 C
Solar/Wind Harmer
0.618
316473AC1-191 GEN
Solar/Wind Harmer
2.205
965281AG1-393 GEN
Solar/Wind Harmer
2.562
315778AD1-151 GEN
Solar/Wind Harmer
17.748
316382AG1-145 C
Solar/Wind Harmer
0.617
315773AC2-141 GEN
Solar/Wind Harmer
8.525
961611AG1-000B GEN
Solar/Wind Harmer
4.287
3151221GRAVEL6
Adder
13.136
3151171GRAVELC
Adder
2.527
3144216WINCHST
Adder
0.681
3150921YORKTN3
Adder
4.537
315813AE1-149 C
Solar/Wind Harmer
12.652
3145336SMITFLD
Solar/Wind Harmer
-0.008
3144536CHRHLND
Solar/Wind Harmer
-0.003
944581AF1-123 GEN
Solar/Wind Harmer
91.618
944601AF1-125 GEN
Solar/Wind Harmer
90.188
3151101ELIZAR3
Adder
16.637
970659AG2-427 GEN
Solar/Wind Harmer
1.895
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316083AB2-161 GEN
Solar/Wind Harmer
3.264
970661AG2-428 GEN
Solar/Wind Harmer
3.776
3142433PROV 92
Adder
0.346
3142433PROV 92
Adder
0.346
3146456SLIGO L269
Solar/Wind Harmer
-0.02
971153AH1-033 GEN
Solar/Wind Harmer
2.426
316320Y1-086
Solar/Wind Harmer
1.155
316435W1029_GEN3
Solar/Wind Harmer
3.536
3146516WINFALL
Solar/Wind Harmer
-0.019
3141766HARMONY
Solar/Wind Harmer
1.731
3141843SHACKLE
Adder
0.884
316203AE2-005 GEN
Solar/Wind Harmer
8.198
316280AD1-041 GEN
Solar/Wind Harmer
1.459
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3145273HOLLAND
Solar/Wind Harmer
-0.014
316156AD2-030 GEN
Solar/Wind Harmer
0.514
3141873WAN 176
Solar/Wind Harmer
2.284
3146376EDENTON
Solar/Wind Harmer
-0.019
3147666LOUISA
Solar/Wind Harmer
-0.043
316313AB2-026
Solar/Wind Harmer
0.502
316258AE1-075 C
Solar/Wind Harmer
0.452
316405AF2-144 C
Solar/Wind Harmer
0.477
3143336POWHATN
Solar/Wind Harmer
1.877
315614AA2-178 GEN
Solar/Wind Harmer
2.005
971157AH1-035 GEN
Solar/Wind Harmer
2.285
315737AD1-076 GEN
Solar/Wind Harmer
3.464
3156081AA2-088 GEN
Solar/Wind Harmer
5.913
962971AG1-146 GEN
Solar/Wind Harmer
3.411
970917AG2-570 GEN
Solar/Wind Harmer
45.296
3146206CASHIE
Solar/Wind Harmer
-0.018
316365GEN2_N
Solar/Wind Harmer
1.216
3145893MURPHYS
Solar/Wind Harmer
0.126
3145893MURPHYS
Solar/Wind Harmer
-0.018
316484AD2-074 GEN
Solar/Wind Harmer
4.52
970009AG2-005 GEN
Solar/Wind Harmer
2.244
957521AF2-046 GEN
Solar/Wind Harmer
14.132
961681AG1-008 GEN
Solar/Wind Harmer
14.132
3146173TUNIS
Solar/Wind Harmer
-0.018
3156021HOLLOMANSOL
Solar/Wind Harmer
2.398
316463AE2-346 GEN
Solar/Wind Harmer
0.287
316140AB2-099
Solar/Wind Harmer
0.12
962331AG1-082 GEN
Solar/Wind Harmer
2.219
966621AG1-532 GEN
Solar/Wind Harmer
0.357
316404AE1-155 C
Solar/Wind Harmer
3.389
3146263WOODLND
Solar/Wind Harmer
-0.017
313506AB2-031 GEN
Solar/Wind Harmer
1.402
3145963POPLR C
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
316317KELFORD C
Solar/Wind Harmer
0.818
3145823KELFORD
Solar/Wind Harmer
-0.017
3147043LAWRENC
Solar/Wind Harmer
-0.01
3145796HORNRTN
Solar/Wind Harmer
-0.068
3145796HORNRTN
Solar/Wind Harmer
-0.017
316478AD1-087 GEN
Solar/Wind Harmer
1.462
316486AD2-202 GEN
Solar/Wind Harmer
0.428
3150351NORNECKC2
Adder
1.523
3144293JTRSVLE
Adder
0.452
972255AH1-712 GEN
Adder
69.158
3151761LOISA E
Adder
15.204
227287AC2-120 GEN
Solar/Wind Helper
0.375
226910AB2-157 C
Solar/Wind Helper
0.015
316210AC1-098 GEN
Solar/Wind Harmer
1.553
NYPJM->LTFIMP_NY
CLTF
2.897
LGEELTFEXP_LGEE->PJM
CLTF
1.548
WECLTFEXP_WEC->PJM
CLTF
0.782
LAGNLTFEXP_LAGN->PJM
CLTF
7.571
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.834
TVALTFEXP_TVA->PJM
CLTF
3.832
CBM West 1LTFEXP_CBM-W1->PJM
CBM
27.364
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.323
MECLTFEXP_MEC->PJM
CLTF
4.03
SIGELTFEXP_SIGE->PJM
CLTF
0.124
CPLELTFEXP_CPLE->PJM
CLTF
9.237
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.506

Details for 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: H4T581_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H4T581_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.18 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4419.9
MW Contribution:84.96
Bus #Bus NameTypeMW Contribution
3150391LDYSMT3
50/50
28.713
972195AH1-682 GEN
50/50
3.773
3142296MT RD221
50/50
0.663
3142366NRTHEST
50/50
0.658
315673AE1-157 GEN
Solar/Wind Harmer
16.967
957411AF2-035 GEN
Solar/Wind Harmer
10.157
970317AG2-208 GEN
Solar/Wind Harmer
9.875
3150691DARBY 3
Adder
13.639
3150701DARBY 4
Adder
13.607
3150681DARBY 2
Adder
13.591
3150671DARBY 1
Adder
13.575
316075AC2-137 C
Solar/Wind Harmer
0.57
966871AG1-558 GEN
Solar/Wind Harmer
0.628
966871AG1-558 GEN
Solar/Wind Harmer
0.215
3142946ENON
Solar/Wind Harmer
-0.002
944641AF1-129 GEN
Adder
86.641
316240AF1-291 C
Solar/Wind Harmer
0.613
3143526WINTERP
Solar/Wind Harmer
-0.105
316033AB2-134 GEN
Solar/Wind Harmer
6.495
315697AD1-025 GEN
Solar/Wind Harmer
4.074
971223AH1-071 GEN
Solar/Wind Harmer
2.488
316236AE1-162_GEN
Solar/Wind Harmer
0.597
316036AC1-147 C
Solar/Wind Harmer
0.529
3150991CHESPKB
Adder
1.827
3150991CHESPKB
Adder
1.783
970657AG2-426 GEN
Solar/Wind Harmer
6.116
970657AG2-426 GEN
Solar/Wind Harmer
1.279
316316AC1-027 C
Solar/Wind Harmer
0.6
3142956BIRDNECK
Solar/Wind Harmer
1.049
316185AD1-033 GEN
Solar/Wind Harmer
2.06
3145506HICKORY
Solar/Wind Harmer
-0.078
3145506HICKORY
Solar/Wind Harmer
-0.047
3145506HICKORY
Solar/Wind Harmer
-0.012
316441AF1-014 GEN
Solar/Wind Harmer
1.311
316339AD2-160 GEN
Solar/Wind Harmer
1.309
316018AA1-139 ULT2
Solar/Wind Harmer
1.662
316017AA1-139 ULT1
Solar/Wind Harmer
1.57
3137176SLIGO L2192
Solar/Wind Harmer
-0.077
3146456SLIGO L269
Solar/Wind Harmer
2.286
3130086AYDLETT
Solar/Wind Harmer
-0.077
3146386ELIZ CT
Solar/Wind Harmer
-0.019
316431W1029_GEN1
Solar/Wind Harmer
3.437
316433W1029_GEN2
Solar/Wind Harmer
3.437
3146516WINFALL
Solar/Wind Harmer
-0.019
3146516WINFALL
Solar/Wind Harmer
-0.019
3146516WINFALL
Solar/Wind Harmer
-0.019
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3144356SAPONY
Solar/Wind Harmer
0.647
315742AE1-103 GEN
Solar/Wind Harmer
1.934
3146376EDENTON
Solar/Wind Harmer
0.546
3146376EDENTON
Solar/Wind Harmer
0.546
316487AF1-042 GEN
Solar/Wind Harmer
2.37
972185AH1-677 GEN
Adder
8.902
972187AH1-678 GEN
Adder
4.473
958261AF2-120 GEN
Solar/Wind Harmer
6.827
316065AD1-022 GEN
Solar/Wind Harmer
8.77
970933AG2-581 GEN
Solar/Wind Harmer
16.339
3145893MURPHYS
Solar/Wind Harmer
0.485
3145893MURPHYS
Solar/Wind Harmer
-0.031
3146173TUNIS
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.017
316077AC2-138 C
Solar/Wind Harmer
0.357
3150341NORNECKC1
Adder
1.579
3150341NORNECKC1
Adder
1.567
316468AD1-105 GEN
Solar/Wind Harmer
1.88
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
316181AB2-040 GEN
Solar/Wind Harmer
2.338
316426AA2-053 GEN
Solar/Wind Harmer
1.684
3145593CAROLNA
Solar/Wind Harmer
-0.017
3145593CAROLNA
Solar/Wind Harmer
-0.017
966811AG1-552 GEN
Solar/Wind Harmer
1.865
3145593CAROLNA
Solar/Wind Harmer
0.138
970099AG2-077 GEN
Solar/Wind Harmer
20.646
3145783HORNRTN
Solar/Wind Harmer
1.957
3145783HORNRTN
Solar/Wind Harmer
1.566
3145783HORNRTN
Solar/Wind Harmer
0.489
3145783HORNRTN
Solar/Wind Harmer
0.196
3145796HORNRTN
Solar/Wind Harmer
-0.049
3145933PARMELE
Solar/Wind Harmer
-0.032
3145933PARMELE
Solar/Wind Harmer
-0.016
316274AC1-208 GEN
Solar/Wind Harmer
1.729
3144293JTRSVLE
Adder
0.43
3144293JTRSVLE
Adder
0.362
226929AD2-058 GEN
Solar/Wind Helper
0.118
3150411LDYSMT5
50/50
28.857
3150381LDYSMT2
50/50
27.617
972213AH1-691 GEN
50/50
4.672
972215AH1-692 GEN
50/50
4.672
963051AG1-154 GEN
50/50
3.594
972189AH1-679 GEN
50/50
3.546
316312AB1-027
Solar/Wind Harmer
0.731
315976AC1-164 GENA
Solar/Wind Harmer
22.101
316169AC1-164_GENC
Solar/Wind Harmer
19.093
315975AC1-164 GENB
Solar/Wind Harmer
0.654
971285AH1-108 GEN
Adder
1.386
316233AE1-074 FULL
Solar/Wind Harmer
0.547
971281AH1-106 GEN
Solar/Wind Harmer
3.302
971283AH1-107 GEN
Solar/Wind Harmer
3.302
316132AB2-190 GEN1
Solar/Wind Harmer
2.05
316369SG1_INVT
Solar/Wind Harmer
3.598
971167AH1-042 GEN
Solar/Wind Harmer
19.287
3142433PROV 92
Adder
0.346
3142433PROV 92
Adder
0.346
972265AH1-717 GEN
Adder
13.77
3151201GRAVEL4
Adder
12.909
3151191GRAVEL3
Adder
12.745
3151211GRAVEL5
Adder
12.745
971445AH1-216 GEN
Solar/Wind Harmer
12.262
3143873LANEXA
Solar/Wind Harmer
-0.012
957831AF2-077 GEN
Solar/Wind Harmer
0.591
3138283WHITEMARSH
Solar/Wind Harmer
0.03
3143316POE
Solar/Wind Harmer
-0.077
316314AB2-024 C
Solar/Wind Harmer
1.678
3151081ELIZAR1
Adder
15.992
3151091ELIZAR2
Adder
15.714
3152611GOSPORTB
Adder
2.221
3152621GOSPORTC
Adder
1.885
3152601GOSPORTA
Adder
1.739
316059AD1-063 C
Solar/Wind Harmer
0.44
957871AF2-081 GEN
Solar/Wind Harmer
9.699
315833AF1-017_GEN
Solar/Wind Harmer
3.679
316349AD2-085 GEN
Solar/Wind Harmer
1.723
316311AC2-079 GEN
Solar/Wind Harmer
9.769
315662AE1-191 GEN
Solar/Wind Harmer
2.334
315666AE1-190 GEN
Solar/Wind Harmer
0.584
319010AE1-072 C
Solar/Wind Harmer
3.913
3146406KITTY HAWK
Solar/Wind Harmer
0.016
316305AF2-043 C
Solar/Wind Harmer
0.582
957601AF2-054 GEN
Solar/Wind Harmer
0.576
3141873WAN 176
Solar/Wind Harmer
-0.004
315835AF2-110_GEN
Solar/Wind Harmer
2.404
313526AB2-022
Solar/Wind Harmer
0.517
3146486SUNBURY
Solar/Wind Harmer
-0.019
3146486SUNBURY
Solar/Wind Harmer
-0.019
316321Z2-027
Solar/Wind Harmer
0.515
3146396TANGLEW
Solar/Wind Harmer
0.351
3145176PASQUOTANK
Solar/Wind Harmer
-0.012
3141913WHIT STONE
Solar/Wind Harmer
-0.019
3138133OCRAN
Solar/Wind Harmer
-0.006
315611Z1-036_GEN2
Solar/Wind Harmer
4.604
3141783LANCAST
Solar/Wind Harmer
-0.011
3141783LANCAST
Solar/Wind Harmer
-0.007
316315AB2-025 C
Solar/Wind Harmer
0.5
315814AE2-033 C
Solar/Wind Harmer
17.214
3130156CHOWAN
Solar/Wind Harmer
-0.018
3130156CHOWAN
Solar/Wind Harmer
-0.018
941031AE2-094 GEN
Solar/Wind Harmer
34.167
944011AF1-069 GEN
Solar/Wind Harmer
10.706
962981AG1-147 GEN
Solar/Wind Harmer
7.972
315816AE2-034 GEN
Solar/Wind Harmer
1.458
970673AG2-436 GEN
Solar/Wind Harmer
37.725
970673AG2-436 GEN
Solar/Wind Harmer
19.101
971967AH1-528 GEN
Solar/Wind Harmer
33.421
3130546PLYMOUTH
Solar/Wind Harmer
-0.018
315732AD1-074 GEN1
Solar/Wind Harmer
3.571
315733AD1-074 GEN2
Solar/Wind Harmer
3.571
315735AD1-075 GEN1
Solar/Wind Harmer
1.786
965291AG1-394 GEN
Solar/Wind Harmer
1.556
3146206CASHIE
Solar/Wind Harmer
-0.017
970601AG2-382 GEN
Solar/Wind Harmer
7.645
316318V4-068
Solar/Wind Harmer
0.433
3145893MURPHYS
Solar/Wind Harmer
-0.047
3145893MURPHYS
Solar/Wind Harmer
-0.017
3145513AHOSKIE
Solar/Wind Harmer
0.15
961941AG1-037 GEN
Solar/Wind Harmer
0.129
3145513AHOSKIE
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.034
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.017
970085AG2-068 GEN
Solar/Wind Harmer
10.655
970581AG2-369 GEN
Solar/Wind Harmer
9.164
3146043SEABORD
Solar/Wind Harmer
-0.017
315607AA1-063A GEN
Solar/Wind Harmer
1.713
3141813NORNECK
Solar/Wind Harmer
-0.017
946281AF1-292 GEN
Solar/Wind Harmer
0.379
316087AB2-174 GEN
Solar/Wind Harmer
2.398
315652AC1-086 GEN
Solar/Wind Harmer
18.802
3137643SOCKMAN
Solar/Wind Harmer
-0.066
3145796HORNRTN
Solar/Wind Harmer
-0.052
3145796HORNRTN
Solar/Wind Harmer
-0.007
3146033SCOT NK
Solar/Wind Harmer
-0.065
972193AH1-681 GEN
Adder
3.258
972205AH1-687 GEN
Adder
5.337
970831AG2-522 GEN
Solar/Wind Harmer
4.1
970497AG2-320 GEN
50/50
20.809
3150401LDYSMT4
50/50
28.767
3150371LDYSMT1
50/50
27.797
315051AA1-145 CT1
50/50
1.582
971645AH1-323 GEN
50/50
17.655
966881AG1-559 GEN
Solar/Wind Harmer
0.679
3142416OLDCHRC
Solar/Wind Harmer
2.188
970293AG2-193 GEN
Solar/Wind Harmer
2.652
3143096IRON208
Adder
0.779
3143096IRON208
Adder
0.764
316473AC1-191 GEN
Solar/Wind Harmer
2.249
3142946ENON
Solar/Wind Harmer
-0.007
3150861SPRUNCD
Adder
0.847
970133AG2-095 GEN
Solar/Wind Harmer
2.296
316382AG1-145 C
Solar/Wind Harmer
0.614
970129AG2-093 GEN
Solar/Wind Harmer
11.42
315778AD1-151 GEN
Solar/Wind Harmer
17.494
965281AG1-393 GEN
Solar/Wind Harmer
2.513
315839AE2-212 C
Solar/Wind Harmer
0.605
3150921YORKTN3
Adder
4.486
3144216WINCHST
Adder
0.673
961611AG1-000B GEN
Solar/Wind Harmer
4.213
3142433PROV 92
Adder
0.346
3142433PROV 92
Adder
0.346
3151221GRAVEL6
Adder
12.894
3151171GRAVELC
Adder
2.481
315773AC2-141 GEN
Solar/Wind Harmer
8.304
3145336SMITFLD
Solar/Wind Harmer
-0.008
315813AE1-149 C
Solar/Wind Harmer
12.337
3144536CHRHLND
Solar/Wind Harmer
-0.003
970659AG2-427 GEN
Solar/Wind Harmer
1.847
3151101ELIZAR3
Adder
16.197
316083AB2-161 GEN
Solar/Wind Harmer
3.181
3144873MCLAUGH
Solar/Wind Harmer
-0.001
944581AF1-123 GEN
Solar/Wind Harmer
89.102
944601AF1-125 GEN
Solar/Wind Harmer
87.711
970661AG2-428 GEN
Solar/Wind Harmer
3.678
3141766HARMONY
Solar/Wind Harmer
1.734
3141843SHACKLE
Adder
0.885
316203AE2-005 GEN
Solar/Wind Harmer
8.201
316280AD1-041 GEN
Solar/Wind Harmer
1.459
3146456SLIGO L269
Solar/Wind Harmer
-0.019
971153AH1-033 GEN
Solar/Wind Harmer
2.36
316156AD2-030 GEN
Solar/Wind Harmer
0.514
3141873WAN 176
Solar/Wind Harmer
2.284
316320Y1-086
Solar/Wind Harmer
1.123
316435W1029_GEN3
Solar/Wind Harmer
3.437
3146516WINFALL
Solar/Wind Harmer
-0.019
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3145273HOLLAND
Solar/Wind Harmer
-0.014
3146376EDENTON
Solar/Wind Harmer
-0.018
962971AG1-146 GEN
Solar/Wind Harmer
3.417
315614AA2-178 GEN
Solar/Wind Harmer
1.944
316484AD2-074 GEN
Solar/Wind Harmer
4.529
970009AG2-005 GEN
Solar/Wind Harmer
2.249
971157AH1-035 GEN
Solar/Wind Harmer
2.214
315737AD1-076 GEN
Solar/Wind Harmer
3.356
316404AE1-155 C
Solar/Wind Harmer
3.398
3156081AA2-088 GEN
Solar/Wind Harmer
5.718
316313AB2-026
Solar/Wind Harmer
0.474
316258AE1-075 C
Solar/Wind Harmer
0.426
316405AF2-144 C
Solar/Wind Harmer
0.45
3143336POWHATN
Solar/Wind Harmer
1.771
3146206CASHIE
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
0.121
3145893MURPHYS
Solar/Wind Harmer
-0.017
957521AF2-046 GEN
Solar/Wind Harmer
13.658
961681AG1-008 GEN
Solar/Wind Harmer
13.658
316365GEN2_N
Solar/Wind Harmer
1.169
3146173TUNIS
Solar/Wind Harmer
-0.017
3156021HOLLOMANSOL
Solar/Wind Harmer
2.319
316463AE2-346 GEN
Solar/Wind Harmer
0.278
316140AB2-099
Solar/Wind Harmer
0.116
962331AG1-082 GEN
Solar/Wind Harmer
2.144
970917AG2-570 GEN
Solar/Wind Harmer
42.771
3150351NORNECKC2
Adder
1.529
3146263WOODLND
Solar/Wind Harmer
-0.017
966621AG1-532 GEN
Solar/Wind Harmer
0.343
971781AH1-399 GEN
Solar/Wind Harmer
1.04
3145963POPLR C
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
313506AB2-031 GEN
Solar/Wind Harmer
1.347
316317KELFORD C
Solar/Wind Harmer
0.789
3145823KELFORD
Solar/Wind Harmer
-0.017
3145796HORNRTN
Solar/Wind Harmer
-0.066
3145796HORNRTN
Solar/Wind Harmer
-0.016
3147043LAWRENC
Solar/Wind Harmer
-0.01
3145933PARMELE
Solar/Wind Harmer
-0.016
966801AG1-551 GEN
Solar/Wind Harmer
2.019
316210AC1-098 GEN
Solar/Wind Harmer
2.534
972255AH1-712 GEN
Adder
72.909
316478AD1-087 GEN
Solar/Wind Harmer
1.386
316486AD2-202 GEN
Solar/Wind Harmer
0.406
3144293JTRSVLE
Adder
0.43
227287AC2-120 GEN
Solar/Wind Helper
0.387
226910AB2-157 C
Solar/Wind Helper
0.015
972197AH1-683 GEN
50/50
4.492
972219AH1-694 GEN
50/50
3.234
315052AA1-145 CT2
50/50
1.589
966881AG1-559 GEN
Solar/Wind Harmer
0.232
3142416OLDCHRC
Solar/Wind Harmer
-0.056
3142416OLDCHRC
Solar/Wind Harmer
-0.021
3143096IRON208
Adder
0.779
3142543TWELFTH
Solar/Wind Harmer
-0.002
944631AF1-128 GEN
Adder
88.024
3150851SPRUNCC
Adder
0.847
316159AE1-175 C
Solar/Wind Harmer
0.547
3143526WINTERP
Solar/Wind Harmer
-0.105
970129AG2-093 GEN
Solar/Wind Harmer
4.626
316458AB2-190 GEN2
Solar/Wind Harmer
2.05
971069AG2-661 GEN
Solar/Wind Harmer
3.195
315671AE2-027_GEN
Solar/Wind Harmer
15.127
971647AH1-324 GEN
Solar/Wind Harmer
10.037
971317AH1-138 GEN
Solar/Wind Harmer
2.507
3138126ROCKLANDING
Solar/Wind Harmer
0.061
961611AG1-000B GEN
Solar/Wind Harmer
9.875
3142433PROV 92
Solar/Wind Harmer
-0.08
3142433PROV 92
Adder
0.346
3142433PROV 92
Adder
0.346
3151171GRAVELC
Adder
1.887
3143226MDLTHAN
Solar/Wind Harmer
-0.02
316294AC1-161 GEN
Solar/Wind Harmer
6.42
3145336SMITFLD
Solar/Wind Harmer
-0.079
970659AG2-427 GEN
Solar/Wind Harmer
10.422
316375AC2-012 GEN
Solar/Wind Harmer
6.782
3150981CHESPKA
Adder
2.178
316381AD1-082 GEN
Solar/Wind Harmer
1.797
944591AF1-124 GEN
Solar/Wind Harmer
89.423
970661AG2-428 GEN
Solar/Wind Harmer
20.752
3141766HARMONY
Solar/Wind Harmer
-0.004
316072AD1-144
Solar/Wind Harmer
0.394
971777AH1-397 GEN
Solar/Wind Harmer
2.288
3141843SHACKLE
Adder
0.885
316388AE2-253 GEN
Solar/Wind Harmer
1.309
3146456SLIGO L269
Solar/Wind Harmer
-0.019
316246AF1-032 C
Solar/Wind Harmer
0.391
316093AE2-104_GEN
Solar/Wind Harmer
5.591
939411AE1-173 GEN
Solar/Wind Harmer
95.482
940641AE2-051 GEN
Solar/Wind Harmer
17.771
3146516WINFALL
Solar/Wind Harmer
-0.061
3146516WINFALL
Solar/Wind Harmer
-0.019
3138133OCRAN
Solar/Wind Harmer
-0.011
315800Z1-036_GEN1
Solar/Wind Harmer
4.604
3130156CHOWAN
Solar/Wind Harmer
-0.018
3145663CRESWEL
Solar/Wind Harmer
-0.05
971163AH1-040 GEN
Solar/Wind Harmer
16.891
961951AG1-038 GEN
Solar/Wind Harmer
2.37
962861AG1-135 GEN
Solar/Wind Harmer
6.643
3143336POWHATN
Solar/Wind Harmer
2.084
3146206CASHIE
Solar/Wind Harmer
-0.017
971547AH1-271 GEN
Solar/Wind Harmer
4.369
3145893MURPHYS
Solar/Wind Harmer
-0.069
3145893MURPHYS
Solar/Wind Harmer
0.516
316023GEN1_S
Solar/Wind Harmer
1.169
964211AG1-282 GEN
Solar/Wind Harmer
0.52
3141726DUNNSVL
Solar/Wind Harmer
-0.069
3146173TUNIS
Solar/Wind Harmer
-0.017
970919AG2-571 GEN
Solar/Wind Harmer
5.414
3145683EARLEYS
Solar/Wind Harmer
-0.017
970087AG2-069 GEN
Solar/Wind Harmer
15.983
3150351NORNECKC2
Adder
1.504
316336AC2-165 C
Solar/Wind Harmer
2.945
3146263WOODLND
Solar/Wind Harmer
-0.017
960081AF2-299 GEN
Solar/Wind Harmer
1.903
3145963POPLR C
Solar/Wind Harmer
-0.017
3145823KELFORD
Solar/Wind Harmer
-0.017
316011AB1-132 GEN
Solar/Wind Harmer
3.497
962571AG1-106 GEN
Solar/Wind Harmer
2.402
316174AB2-169 GEN
Solar/Wind Harmer
2.577
316190AA2-174 GEN
Solar/Wind Harmer
0.205
971795AH1-408 GEN
Solar/Wind Harmer
12.43
957481AF2-042 GEN
Solar/Wind Harmer
51.614
3145783HORNRTN
Solar/Wind Harmer
-0.016
3145796HORNRTN
Solar/Wind Harmer
-0.054
3145796HORNRTN
Solar/Wind Harmer
-0.016
3147043LAWRENC
Adder
1.322
315693AD1-088 GEN
Solar/Wind Harmer
8.136
962491AG1-098 GEN
Solar/Wind Harmer
10.858
3146293MARTNCO
Solar/Wind Harmer
0.1
316212AC1-099_GEN
Solar/Wind Harmer
1.408
972277AH1-723 GEN
Adder
84.961
3144293JTRSVLE
Adder
0.43
NYPJM->LTFIMP_NY
CLTF
2.846
LGEELTFEXP_LGEE->PJM
CLTF
1.614
WECLTFEXP_WEC->PJM
CLTF
0.82
LAGNLTFEXP_LAGN->PJM
CLTF
7.584
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.244
TVALTFEXP_TVA->PJM
CLTF
3.839
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.903
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.41
MECLTFEXP_MEC->PJM
CLTF
4.166
SIGELTFEXP_SIGE->PJM
CLTF
0.129
CPLELTFEXP_CPLE->PJM
CLTF
8.902
CBM West 2LTFEXP_CBM-W2->PJM
CBM
42.096

Details for 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: H3T552_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H3T552_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.16 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4419.22
MW Contribution:84.69
Bus #Bus NameTypeMW Contribution
3150391LDYSMT3
50/50
28.476
972195AH1-682 GEN
50/50
3.742
315673AE1-157 GEN
Solar/Wind Harmer
16.839
957411AF2-035 GEN
Solar/Wind Harmer
10.085
970317AG2-208 GEN
Solar/Wind Harmer
9.805
3142296MT RD221
Adder
0.622
3142366NRTHEST
Adder
0.618
3150691DARBY 3
Adder
13.579
3150701DARBY 4
Adder
13.548
3150681DARBY 2
Adder
13.532
3150671DARBY 1
Adder
13.516
316075AC2-137 C
Solar/Wind Harmer
0.567
966871AG1-558 GEN
Solar/Wind Harmer
0.625
966871AG1-558 GEN
Solar/Wind Harmer
0.214
3142946ENON
Solar/Wind Harmer
-0.002
944641AF1-129 GEN
Adder
86.324
3143526WINTERP
Solar/Wind Harmer
-0.105
316240AF1-291 C
Solar/Wind Harmer
0.611
316033AB2-134 GEN
Solar/Wind Harmer
6.472
315697AD1-025 GEN
Solar/Wind Harmer
4.059
971223AH1-071 GEN
Solar/Wind Harmer
2.484
316236AE1-162_GEN
Solar/Wind Harmer
0.595
316036AC1-147 C
Solar/Wind Harmer
0.527
3150991CHESPKB
Adder
1.821
3150991CHESPKB
Adder
1.777
970657AG2-426 GEN
Solar/Wind Harmer
6.097
970657AG2-426 GEN
Solar/Wind Harmer
1.275
316316AC1-027 C
Solar/Wind Harmer
0.598
3142956BIRDNECK
Solar/Wind Harmer
1.046
316185AD1-033 GEN
Solar/Wind Harmer
2.053
3145506HICKORY
Solar/Wind Harmer
-0.077
3145506HICKORY
Solar/Wind Harmer
-0.046
3145506HICKORY
Solar/Wind Harmer
-0.012
316441AF1-014 GEN
Solar/Wind Harmer
1.305
316339AD2-160 GEN
Solar/Wind Harmer
1.305
316018AA1-139 ULT2
Solar/Wind Harmer
1.657
316017AA1-139 ULT1
Solar/Wind Harmer
1.565
3137176SLIGO L2192
Solar/Wind Harmer
-0.076
3146456SLIGO L269
Solar/Wind Harmer
2.279
3130086AYDLETT
Solar/Wind Harmer
-0.077
3146386ELIZ CT
Solar/Wind Harmer
-0.019
316431W1029_GEN1
Solar/Wind Harmer
3.426
316433W1029_GEN2
Solar/Wind Harmer
3.426
3146516WINFALL
Solar/Wind Harmer
-0.019
3146516WINFALL
Solar/Wind Harmer
-0.019
3146516WINFALL
Solar/Wind Harmer
-0.019
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3144356SAPONY
Solar/Wind Harmer
0.645
315742AE1-103 GEN
Solar/Wind Harmer
1.928
3146376EDENTON
Solar/Wind Harmer
0.545
3146376EDENTON
Solar/Wind Harmer
0.545
316487AF1-042 GEN
Solar/Wind Harmer
2.358
972185AH1-677 GEN
Adder
8.886
972187AH1-678 GEN
Adder
4.465
958261AF2-120 GEN
Solar/Wind Harmer
6.791
316065AD1-022 GEN
Solar/Wind Harmer
8.747
970933AG2-581 GEN
Solar/Wind Harmer
16.313
3145893MURPHYS
Solar/Wind Harmer
0.484
3145893MURPHYS
Solar/Wind Harmer
-0.031
3146173TUNIS
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.017
316077AC2-138 C
Solar/Wind Harmer
0.355
3150341NORNECKC1
Adder
1.571
3150341NORNECKC1
Adder
1.558
316468AD1-105 GEN
Solar/Wind Harmer
1.868
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
316181AB2-040 GEN
Solar/Wind Harmer
2.333
316426AA2-053 GEN
Solar/Wind Harmer
1.68
3145593CAROLNA
Solar/Wind Harmer
-0.016
3145593CAROLNA
Solar/Wind Harmer
-0.016
966811AG1-552 GEN
Solar/Wind Harmer
1.861
3145593CAROLNA
Solar/Wind Harmer
0.137
970099AG2-077 GEN
Solar/Wind Harmer
20.62
3145783HORNRTN
Solar/Wind Harmer
1.953
3145783HORNRTN
Solar/Wind Harmer
1.562
3145783HORNRTN
Solar/Wind Harmer
0.488
3145783HORNRTN
Solar/Wind Harmer
0.195
3145796HORNRTN
Solar/Wind Harmer
-0.049
3145933PARMELE
Solar/Wind Harmer
-0.032
3145933PARMELE
Solar/Wind Harmer
-0.016
316274AC1-208 GEN
Solar/Wind Harmer
1.725
3144293JTRSVLE
Adder
0.43
3144293JTRSVLE
Adder
0.362
226929AD2-058 GEN
Solar/Wind Helper
0.118
971531AH1-263 GEN
50/50
38.619
3150411LDYSMT5
50/50
28.618
3150381LDYSMT2
50/50
27.389
972213AH1-691 GEN
50/50
4.633
972215AH1-692 GEN
50/50
4.633
963051AG1-154 GEN
50/50
3.564
972189AH1-679 GEN
50/50
3.526
316312AB1-027
Solar/Wind Harmer
0.728
315976AC1-164 GENA
Solar/Wind Harmer
22.001
316169AC1-164_GENC
Solar/Wind Harmer
19.007
315975AC1-164 GENB
Solar/Wind Harmer
0.651
971285AH1-108 GEN
Adder
1.381
316233AE1-074 FULL
Solar/Wind Harmer
0.545
971281AH1-106 GEN
Solar/Wind Harmer
3.293
971283AH1-107 GEN
Solar/Wind Harmer
3.293
316132AB2-190 GEN1
Solar/Wind Harmer
2.043
316369SG1_INVT
Solar/Wind Harmer
3.585
971167AH1-042 GEN
Solar/Wind Harmer
19.203
3142433PROV 92
Adder
0.344
3142433PROV 92
Adder
0.344
972265AH1-717 GEN
Adder
13.722
3151201GRAVEL4
Adder
12.864
3151191GRAVEL3
Adder
12.701
3151211GRAVEL5
Adder
12.701
971445AH1-216 GEN
Solar/Wind Harmer
12.22
3143873LANEXA
Solar/Wind Harmer
-0.012
957831AF2-077 GEN
Solar/Wind Harmer
0.589
3138283WHITEMARSH
Solar/Wind Harmer
0.03
3143316POE
Solar/Wind Harmer
-0.077
3151081ELIZAR1
Adder
15.941
3151091ELIZAR2
Adder
15.664
316314AB2-024 C
Solar/Wind Harmer
1.67
3152611GOSPORTB
Adder
2.214
3152621GOSPORTC
Adder
1.879
3152601GOSPORTA
Adder
1.733
316059AD1-063 C
Solar/Wind Harmer
0.438
957871AF2-081 GEN
Solar/Wind Harmer
9.669
315833AF1-017_GEN
Solar/Wind Harmer
3.667
316349AD2-085 GEN
Solar/Wind Harmer
1.717
316311AC2-079 GEN
Solar/Wind Harmer
9.738
319010AE1-072 C
Solar/Wind Harmer
3.901
315662AE1-191 GEN
Solar/Wind Harmer
2.324
315666AE1-190 GEN
Solar/Wind Harmer
0.581
3146406KITTY HAWK
Solar/Wind Harmer
0.016
316305AF2-043 C
Solar/Wind Harmer
0.581
315835AF2-110_GEN
Solar/Wind Harmer
2.396
957601AF2-054 GEN
Solar/Wind Harmer
0.573
3141873WAN 176
Solar/Wind Harmer
-0.004
313526AB2-022
Solar/Wind Harmer
0.515
3146486SUNBURY
Solar/Wind Harmer
-0.019
3146486SUNBURY
Solar/Wind Harmer
-0.019
316321Z2-027
Solar/Wind Harmer
0.513
3146396TANGLEW
Solar/Wind Harmer
0.35
3145176PASQUOTANK
Solar/Wind Harmer
-0.012
3141913WHIT STONE
Solar/Wind Harmer
-0.019
3138133OCRAN
Solar/Wind Harmer
-0.006
315611Z1-036_GEN2
Solar/Wind Harmer
4.59
3141783LANCAST
Solar/Wind Harmer
-0.011
3141783LANCAST
Solar/Wind Harmer
-0.007
316315AB2-025 C
Solar/Wind Harmer
0.499
315814AE2-033 C
Solar/Wind Harmer
17.17
3130156CHOWAN
Solar/Wind Harmer
-0.018
3130156CHOWAN
Solar/Wind Harmer
-0.018
941031AE2-094 GEN
Solar/Wind Harmer
34.101
944011AF1-069 GEN
Solar/Wind Harmer
10.685
962981AG1-147 GEN
Solar/Wind Harmer
7.932
315816AE2-034 GEN
Solar/Wind Harmer
1.454
970673AG2-436 GEN
Solar/Wind Harmer
37.654
970673AG2-436 GEN
Solar/Wind Harmer
19.065
971967AH1-528 GEN
Solar/Wind Harmer
33.362
3130546PLYMOUTH
Solar/Wind Harmer
-0.018
315732AD1-074 GEN1
Solar/Wind Harmer
3.561
315733AD1-074 GEN2
Solar/Wind Harmer
3.561
315735AD1-075 GEN1
Solar/Wind Harmer
1.781
965291AG1-394 GEN
Solar/Wind Harmer
1.552
3146206CASHIE
Solar/Wind Harmer
-0.017
970601AG2-382 GEN
Solar/Wind Harmer
7.625
316318V4-068
Solar/Wind Harmer
0.432
3145893MURPHYS
Solar/Wind Harmer
-0.047
3145893MURPHYS
Solar/Wind Harmer
-0.017
3145513AHOSKIE
Solar/Wind Harmer
0.149
961941AG1-037 GEN
Solar/Wind Harmer
0.129
3145513AHOSKIE
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.034
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.017
970085AG2-068 GEN
Solar/Wind Harmer
10.636
970581AG2-369 GEN
Solar/Wind Harmer
9.147
3146043SEABORD
Solar/Wind Harmer
-0.017
315607AA1-063A GEN
Solar/Wind Harmer
1.709
946281AF1-292 GEN
Solar/Wind Harmer
0.378
3141813NORNECK
Solar/Wind Harmer
-0.017
316087AB2-174 GEN
Solar/Wind Harmer
2.392
315652AC1-086 GEN
Solar/Wind Harmer
18.758
3137643SOCKMAN
Solar/Wind Harmer
-0.066
3145796HORNRTN
Solar/Wind Harmer
-0.052
3145796HORNRTN
Solar/Wind Harmer
-0.007
3146033SCOT NK
Solar/Wind Harmer
-0.065
972193AH1-681 GEN
Adder
3.247
972205AH1-687 GEN
Adder
5.365
970831AG2-522 GEN
Solar/Wind Harmer
4.093
970497AG2-320 GEN
50/50
20.643
3150401LDYSMT4
50/50
28.529
3150371LDYSMT1
50/50
27.567
315051AA1-145 CT1
50/50
1.573
966881AG1-559 GEN
Solar/Wind Harmer
0.674
3142416OLDCHRC
Solar/Wind Harmer
2.177
970293AG2-193 GEN
Solar/Wind Harmer
2.641
3143096IRON208
Adder
0.776
3143096IRON208
Adder
0.761
316473AC1-191 GEN
Solar/Wind Harmer
2.237
3142946ENON
Solar/Wind Harmer
-0.007
3150861SPRUNCD
Adder
0.844
970133AG2-095 GEN
Solar/Wind Harmer
2.287
316382AG1-145 C
Solar/Wind Harmer
0.612
970129AG2-093 GEN
Solar/Wind Harmer
11.378
315778AD1-151 GEN
Solar/Wind Harmer
17.43
965281AG1-393 GEN
Solar/Wind Harmer
2.504
315839AE2-212 C
Solar/Wind Harmer
0.603
3150921YORKTN3
Adder
4.468
3144216WINCHST
Adder
0.67
961611AG1-000B GEN
Solar/Wind Harmer
4.198
3142433PROV 92
Adder
0.344
3142433PROV 92
Adder
0.344
3151221GRAVEL6
Adder
12.849
3151171GRAVELC
Adder
2.472
315773AC2-141 GEN
Solar/Wind Harmer
8.277
3145336SMITFLD
Solar/Wind Harmer
-0.008
315813AE1-149 C
Solar/Wind Harmer
12.297
3144536CHRHLND
Solar/Wind Harmer
-0.003
970659AG2-427 GEN
Solar/Wind Harmer
1.841
3151101ELIZAR3
Adder
16.145
316083AB2-161 GEN
Solar/Wind Harmer
3.17
3144873MCLAUGH
Solar/Wind Harmer
-0.001
944581AF1-123 GEN
Solar/Wind Harmer
88.821
944601AF1-125 GEN
Solar/Wind Harmer
87.435
970661AG2-428 GEN
Solar/Wind Harmer
3.666
3141766HARMONY
Solar/Wind Harmer
1.726
3141843SHACKLE
Adder
0.881
316203AE2-005 GEN
Solar/Wind Harmer
8.164
3146456SLIGO L269
Solar/Wind Harmer
-0.019
971153AH1-033 GEN
Solar/Wind Harmer
2.353
316280AD1-041 GEN
Solar/Wind Harmer
1.452
316156AD2-030 GEN
Solar/Wind Harmer
0.511
3141873WAN 176
Solar/Wind Harmer
2.273
316320Y1-086
Solar/Wind Harmer
1.12
316435W1029_GEN3
Solar/Wind Harmer
3.426
3146516WINFALL
Solar/Wind Harmer
-0.019
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3145273HOLLAND
Solar/Wind Harmer
-0.014
3146376EDENTON
Solar/Wind Harmer
-0.018
962971AG1-146 GEN
Solar/Wind Harmer
3.399
315614AA2-178 GEN
Solar/Wind Harmer
1.938
316484AD2-074 GEN
Solar/Wind Harmer
4.506
970009AG2-005 GEN
Solar/Wind Harmer
2.237
971157AH1-035 GEN
Solar/Wind Harmer
2.208
315737AD1-076 GEN
Solar/Wind Harmer
3.347
3156081AA2-088 GEN
Solar/Wind Harmer
5.703
316313AB2-026
Solar/Wind Harmer
0.474
316258AE1-075 C
Solar/Wind Harmer
0.427
316405AF2-144 C
Solar/Wind Harmer
0.45
3143336POWHATN
Solar/Wind Harmer
1.772
316404AE1-155 C
Solar/Wind Harmer
3.381
3146206CASHIE
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
0.121
3145893MURPHYS
Solar/Wind Harmer
-0.017
957521AF2-046 GEN
Solar/Wind Harmer
13.623
961681AG1-008 GEN
Solar/Wind Harmer
13.623
316365GEN2_N
Solar/Wind Harmer
1.166
3146173TUNIS
Solar/Wind Harmer
-0.017
3156021HOLLOMANSOL
Solar/Wind Harmer
2.313
316463AE2-346 GEN
Solar/Wind Harmer
0.277
316140AB2-099
Solar/Wind Harmer
0.115
962331AG1-082 GEN
Solar/Wind Harmer
2.139
970917AG2-570 GEN
Solar/Wind Harmer
42.694
3146263WOODLND
Solar/Wind Harmer
-0.017
966621AG1-532 GEN
Solar/Wind Harmer
0.343
3150351NORNECKC2
Adder
1.52
3145963POPLR C
Solar/Wind Harmer
-0.017
971781AH1-399 GEN
Solar/Wind Harmer
1.034
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
313506AB2-031 GEN
Solar/Wind Harmer
1.344
316317KELFORD C
Solar/Wind Harmer
0.787
3145823KELFORD
Solar/Wind Harmer
-0.017
3145796HORNRTN
Solar/Wind Harmer
-0.065
3145796HORNRTN
Solar/Wind Harmer
-0.016
3147043LAWRENC
Solar/Wind Harmer
-0.01
3145933PARMELE
Solar/Wind Harmer
-0.016
966801AG1-551 GEN
Solar/Wind Harmer
2.014
316210AC1-098 GEN
Solar/Wind Harmer
2.528
316478AD1-087 GEN
Solar/Wind Harmer
1.384
316486AD2-202 GEN
Solar/Wind Harmer
0.405
972255AH1-712 GEN
Adder
72.68
3144293JTRSVLE
Adder
0.43
227287AC2-120 GEN
Solar/Wind Helper
0.388
226910AB2-157 C
Solar/Wind Helper
0.015
972197AH1-683 GEN
50/50
4.455
972219AH1-694 GEN
50/50
3.208
315052AA1-145 CT2
50/50
1.58
966881AG1-559 GEN
Solar/Wind Harmer
0.23
3142416OLDCHRC
Solar/Wind Harmer
-0.056
3142416OLDCHRC
Solar/Wind Harmer
-0.021
3143096IRON208
Adder
0.776
3142543TWELFTH
Solar/Wind Harmer
-0.002
944631AF1-128 GEN
Adder
87.663
3150851SPRUNCC
Adder
0.844
316159AE1-175 C
Solar/Wind Harmer
0.545
3143526WINTERP
Solar/Wind Harmer
-0.105
970129AG2-093 GEN
Solar/Wind Harmer
4.609
316458AB2-190 GEN2
Solar/Wind Harmer
2.043
971069AG2-661 GEN
Solar/Wind Harmer
3.184
315671AE2-027_GEN
Solar/Wind Harmer
15.073
971647AH1-324 GEN
Solar/Wind Harmer
10.001
971317AH1-138 GEN
Solar/Wind Harmer
2.498
3138126ROCKLANDING
Solar/Wind Harmer
0.061
961611AG1-000B GEN
Solar/Wind Harmer
9.84
3142433PROV 92
Solar/Wind Harmer
-0.079
3142433PROV 92
Adder
0.344
3142433PROV 92
Adder
0.344
3143226MDLTHAN
Solar/Wind Harmer
-0.02
3151171GRAVELC
Adder
1.88
316294AC1-161 GEN
Solar/Wind Harmer
6.4
3145336SMITFLD
Solar/Wind Harmer
-0.079
970659AG2-427 GEN
Solar/Wind Harmer
10.389
316375AC2-012 GEN
Solar/Wind Harmer
6.761
3150981CHESPKA
Adder
2.171
316381AD1-082 GEN
Solar/Wind Harmer
1.791
944591AF1-124 GEN
Solar/Wind Harmer
89.141
970661AG2-428 GEN
Solar/Wind Harmer
20.686
316072AD1-144
Solar/Wind Harmer
0.393
3141766HARMONY
Solar/Wind Harmer
-0.004
971777AH1-397 GEN
Solar/Wind Harmer
2.277
3141843SHACKLE
Adder
0.881
316388AE2-253 GEN
Solar/Wind Harmer
1.305
3146456SLIGO L269
Solar/Wind Harmer
-0.019
316246AF1-032 C
Solar/Wind Harmer
0.39
316093AE2-104_GEN
Solar/Wind Harmer
5.574
939411AE1-173 GEN
Solar/Wind Harmer
95.246
940641AE2-051 GEN
Solar/Wind Harmer
17.731
3146516WINFALL
Solar/Wind Harmer
-0.061
3146516WINFALL
Solar/Wind Harmer
-0.019
3138133OCRAN
Solar/Wind Harmer
-0.011
315800Z1-036_GEN1
Solar/Wind Harmer
4.59
3130156CHOWAN
Solar/Wind Harmer
-0.018
3145663CRESWEL
Solar/Wind Harmer
-0.05
971163AH1-040 GEN
Solar/Wind Harmer
16.843
961951AG1-038 GEN
Solar/Wind Harmer
2.358
962861AG1-135 GEN
Solar/Wind Harmer
6.609
3143336POWHATN
Solar/Wind Harmer
2.085
3146206CASHIE
Solar/Wind Harmer
-0.017
971547AH1-271 GEN
Solar/Wind Harmer
4.357
3145893MURPHYS
Solar/Wind Harmer
-0.069
3145893MURPHYS
Solar/Wind Harmer
0.515
316023GEN1_S
Solar/Wind Harmer
1.166
964211AG1-282 GEN
Solar/Wind Harmer
0.518
3141726DUNNSVL
Solar/Wind Harmer
-0.069
3146173TUNIS
Solar/Wind Harmer
-0.017
970919AG2-571 GEN
Solar/Wind Harmer
5.404
3145683EARLEYS
Solar/Wind Harmer
-0.017
970087AG2-069 GEN
Solar/Wind Harmer
15.954
316336AC2-165 C
Solar/Wind Harmer
2.948
3146263WOODLND
Solar/Wind Harmer
-0.017
960081AF2-299 GEN
Solar/Wind Harmer
1.899
3150351NORNECKC2
Adder
1.495
3145963POPLR C
Solar/Wind Harmer
-0.017
3145823KELFORD
Solar/Wind Harmer
-0.017
316011AB1-132 GEN
Solar/Wind Harmer
3.489
962571AG1-106 GEN
Solar/Wind Harmer
2.397
316174AB2-169 GEN
Solar/Wind Harmer
2.57
316190AA2-174 GEN
Solar/Wind Harmer
0.204
971795AH1-408 GEN
Solar/Wind Harmer
12.407
957481AF2-042 GEN
Solar/Wind Harmer
51.549
3145783HORNRTN
Solar/Wind Harmer
-0.016
3145796HORNRTN
Solar/Wind Harmer
-0.054
3145796HORNRTN
Solar/Wind Harmer
-0.016
3147043LAWRENC
Adder
1.319
315693AD1-088 GEN
Solar/Wind Harmer
8.129
962491AG1-098 GEN
Solar/Wind Harmer
10.849
3146293MARTNCO
Solar/Wind Harmer
0.1
316212AC1-099_GEN
Solar/Wind Harmer
1.404
972277AH1-723 GEN
Adder
84.694
3144293JTRSVLE
Adder
0.43
NYPJM->LTFIMP_NY
CLTF
2.849
LGEELTFEXP_LGEE->PJM
CLTF
1.614
WECLTFEXP_WEC->PJM
CLTF
0.82
LAGNLTFEXP_LAGN->PJM
CLTF
7.579
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.219
TVALTFEXP_TVA->PJM
CLTF
3.837
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.903
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.403
MECLTFEXP_MEC->PJM
CLTF
4.165
SIGELTFEXP_SIGE->PJM
CLTF
0.129
CPLELTFEXP_CPLE->PJM
CLTF
8.889
CBM West 2LTFEXP_CBM-W2->PJM
CBM
42.077

Details for 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T552_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T552_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.08 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4415.8
MW Contribution:84.67
Bus #Bus NameTypeMW Contribution
3150391LDYSMT3
50/50
28.468
972195AH1-682 GEN
50/50
3.741
315673AE1-157 GEN
Solar/Wind Harmer
16.835
957411AF2-035 GEN
Solar/Wind Harmer
10.082
970317AG2-208 GEN
Solar/Wind Harmer
9.802
3142296MT RD221
Adder
0.622
3142366NRTHEST
Adder
0.618
3150691DARBY 3
Adder
13.575
3150701DARBY 4
Adder
13.543
3150681DARBY 2
Adder
13.528
3150671DARBY 1
Adder
13.512
316075AC2-137 C
Solar/Wind Harmer
0.567
966871AG1-558 GEN
Solar/Wind Harmer
0.625
966871AG1-558 GEN
Solar/Wind Harmer
0.214
3142946ENON
Solar/Wind Harmer
-0.002
944641AF1-129 GEN
Adder
86.296
3143526WINTERP
Solar/Wind Harmer
-0.105
316240AF1-291 C
Solar/Wind Harmer
0.61
316033AB2-134 GEN
Solar/Wind Harmer
6.469
315697AD1-025 GEN
Solar/Wind Harmer
4.057
971223AH1-071 GEN
Solar/Wind Harmer
2.483
316236AE1-162_GEN
Solar/Wind Harmer
0.595
316036AC1-147 C
Solar/Wind Harmer
0.527
3150991CHESPKB
Adder
1.821
3150991CHESPKB
Adder
1.777
970657AG2-426 GEN
Solar/Wind Harmer
6.095
970657AG2-426 GEN
Solar/Wind Harmer
1.274
316316AC1-027 C
Solar/Wind Harmer
0.598
3142956BIRDNECK
Solar/Wind Harmer
1.046
316185AD1-033 GEN
Solar/Wind Harmer
2.053
3145506HICKORY
Solar/Wind Harmer
-0.077
3145506HICKORY
Solar/Wind Harmer
-0.046
3145506HICKORY
Solar/Wind Harmer
-0.012
316441AF1-014 GEN
Solar/Wind Harmer
1.305
316339AD2-160 GEN
Solar/Wind Harmer
1.305
316018AA1-139 ULT2
Solar/Wind Harmer
1.656
316017AA1-139 ULT1
Solar/Wind Harmer
1.564
3137176SLIGO L2192
Solar/Wind Harmer
-0.076
3146456SLIGO L269
Solar/Wind Harmer
2.278
3130086AYDLETT
Solar/Wind Harmer
-0.077
3146386ELIZ CT
Solar/Wind Harmer
-0.019
316431W1029_GEN1
Solar/Wind Harmer
3.425
316433W1029_GEN2
Solar/Wind Harmer
3.425
3146516WINFALL
Solar/Wind Harmer
-0.019
3146516WINFALL
Solar/Wind Harmer
-0.019
3146516WINFALL
Solar/Wind Harmer
-0.019
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3144356SAPONY
Solar/Wind Harmer
0.645
315742AE1-103 GEN
Solar/Wind Harmer
1.927
3146376EDENTON
Solar/Wind Harmer
0.545
3146376EDENTON
Solar/Wind Harmer
0.545
316487AF1-042 GEN
Solar/Wind Harmer
2.357
972185AH1-677 GEN
Adder
8.883
972187AH1-678 GEN
Adder
4.463
958261AF2-120 GEN
Solar/Wind Harmer
6.788
316065AD1-022 GEN
Solar/Wind Harmer
8.744
970933AG2-581 GEN
Solar/Wind Harmer
16.307
3145893MURPHYS
Solar/Wind Harmer
0.484
3145893MURPHYS
Solar/Wind Harmer
-0.031
3146173TUNIS
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.017
316077AC2-138 C
Solar/Wind Harmer
0.355
3150341NORNECKC1
Adder
1.57
3150341NORNECKC1
Adder
1.558
316468AD1-105 GEN
Solar/Wind Harmer
1.868
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
316181AB2-040 GEN
Solar/Wind Harmer
2.332
316426AA2-053 GEN
Solar/Wind Harmer
1.68
3145593CAROLNA
Solar/Wind Harmer
-0.016
3145593CAROLNA
Solar/Wind Harmer
-0.016
966811AG1-552 GEN
Solar/Wind Harmer
1.861
3145593CAROLNA
Solar/Wind Harmer
0.137
970099AG2-077 GEN
Solar/Wind Harmer
20.612
3145783HORNRTN
Solar/Wind Harmer
1.952
3145783HORNRTN
Solar/Wind Harmer
1.562
3145783HORNRTN
Solar/Wind Harmer
0.488
3145783HORNRTN
Solar/Wind Harmer
0.195
3145796HORNRTN
Solar/Wind Harmer
-0.049
3145933PARMELE
Solar/Wind Harmer
-0.032
3145933PARMELE
Solar/Wind Harmer
-0.016
316274AC1-208 GEN
Solar/Wind Harmer
1.725
3144293JTRSVLE
Adder
0.43
3144293JTRSVLE
Adder
0.362
226929AD2-058 GEN
Solar/Wind Helper
0.118
971531AH1-263 GEN
50/50
38.605
3150411LDYSMT5
50/50
28.611
3150381LDYSMT2
50/50
27.382
972213AH1-691 GEN
50/50
4.632
972215AH1-692 GEN
50/50
4.632
963051AG1-154 GEN
50/50
3.563
972189AH1-679 GEN
50/50
3.525
316312AB1-027
Solar/Wind Harmer
0.728
315976AC1-164 GENA
Solar/Wind Harmer
21.995
316169AC1-164_GENC
Solar/Wind Harmer
19.001
315975AC1-164 GENB
Solar/Wind Harmer
0.651
971285AH1-108 GEN
Adder
1.381
316233AE1-074 FULL
Solar/Wind Harmer
0.545
971281AH1-106 GEN
Solar/Wind Harmer
3.292
971283AH1-107 GEN
Solar/Wind Harmer
3.292
316132AB2-190 GEN1
Solar/Wind Harmer
2.042
316369SG1_INVT
Solar/Wind Harmer
3.584
971167AH1-042 GEN
Solar/Wind Harmer
19.197
3142433PROV 92
Adder
0.344
3142433PROV 92
Adder
0.344
972265AH1-717 GEN
Adder
13.718
3151201GRAVEL4
Adder
12.859
3151191GRAVEL3
Adder
12.697
3151211GRAVEL5
Adder
12.697
971445AH1-216 GEN
Solar/Wind Harmer
12.216
3143873LANEXA
Solar/Wind Harmer
-0.012
957831AF2-077 GEN
Solar/Wind Harmer
0.589
3138283WHITEMARSH
Solar/Wind Harmer
0.03
3143316POE
Solar/Wind Harmer
-0.077
3151081ELIZAR1
Adder
15.936
3151091ELIZAR2
Adder
15.659
316314AB2-024 C
Solar/Wind Harmer
1.67
3152611GOSPORTB
Adder
2.213
3152621GOSPORTC
Adder
1.878
3152601GOSPORTA
Adder
1.733
316059AD1-063 C
Solar/Wind Harmer
0.438
957871AF2-081 GEN
Solar/Wind Harmer
9.666
315833AF1-017_GEN
Solar/Wind Harmer
3.666
316349AD2-085 GEN
Solar/Wind Harmer
1.717
316311AC2-079 GEN
Solar/Wind Harmer
9.735
319010AE1-072 C
Solar/Wind Harmer
3.9
315662AE1-191 GEN
Solar/Wind Harmer
2.323
315666AE1-190 GEN
Solar/Wind Harmer
0.581
3146406KITTY HAWK
Solar/Wind Harmer
0.016
316305AF2-043 C
Solar/Wind Harmer
0.58
315835AF2-110_GEN
Solar/Wind Harmer
2.396
957601AF2-054 GEN
Solar/Wind Harmer
0.573
3141873WAN 176
Solar/Wind Harmer
-0.004
313526AB2-022
Solar/Wind Harmer
0.515
3146486SUNBURY
Solar/Wind Harmer
-0.019
3146486SUNBURY
Solar/Wind Harmer
-0.019
316321Z2-027
Solar/Wind Harmer
0.513
3146396TANGLEW
Solar/Wind Harmer
0.35
3145176PASQUOTANK
Solar/Wind Harmer
-0.012
3141913WHIT STONE
Solar/Wind Harmer
-0.019
3138133OCRAN
Solar/Wind Harmer
-0.006
315611Z1-036_GEN2
Solar/Wind Harmer
4.589
3141783LANCAST
Solar/Wind Harmer
-0.011
3141783LANCAST
Solar/Wind Harmer
-0.007
316315AB2-025 C
Solar/Wind Harmer
0.499
315814AE2-033 C
Solar/Wind Harmer
17.164
3130156CHOWAN
Solar/Wind Harmer
-0.018
3130156CHOWAN
Solar/Wind Harmer
-0.018
941031AE2-094 GEN
Solar/Wind Harmer
34.089
944011AF1-069 GEN
Solar/Wind Harmer
10.681
962981AG1-147 GEN
Solar/Wind Harmer
7.93
315816AE2-034 GEN
Solar/Wind Harmer
1.453
970673AG2-436 GEN
Solar/Wind Harmer
37.641
970673AG2-436 GEN
Solar/Wind Harmer
19.058
971967AH1-528 GEN
Solar/Wind Harmer
33.35
3130546PLYMOUTH
Solar/Wind Harmer
-0.018
315732AD1-074 GEN1
Solar/Wind Harmer
3.56
315733AD1-074 GEN2
Solar/Wind Harmer
3.56
315735AD1-075 GEN1
Solar/Wind Harmer
1.78
965291AG1-394 GEN
Solar/Wind Harmer
1.552
3146206CASHIE
Solar/Wind Harmer
-0.017
970601AG2-382 GEN
Solar/Wind Harmer
7.622
316318V4-068
Solar/Wind Harmer
0.432
3145893MURPHYS
Solar/Wind Harmer
-0.047
3145893MURPHYS
Solar/Wind Harmer
-0.017
3145513AHOSKIE
Solar/Wind Harmer
0.149
961941AG1-037 GEN
Solar/Wind Harmer
0.129
3145513AHOSKIE
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.034
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.017
970085AG2-068 GEN
Solar/Wind Harmer
10.632
970581AG2-369 GEN
Solar/Wind Harmer
9.144
3146043SEABORD
Solar/Wind Harmer
-0.017
315607AA1-063A GEN
Solar/Wind Harmer
1.709
946281AF1-292 GEN
Solar/Wind Harmer
0.378
3141813NORNECK
Solar/Wind Harmer
-0.017
316087AB2-174 GEN
Solar/Wind Harmer
2.392
315652AC1-086 GEN
Solar/Wind Harmer
18.752
3137643SOCKMAN
Solar/Wind Harmer
-0.066
3145796HORNRTN
Solar/Wind Harmer
-0.052
3145796HORNRTN
Solar/Wind Harmer
-0.006
3146033SCOT NK
Solar/Wind Harmer
-0.065
972193AH1-681 GEN
Adder
3.246
972205AH1-687 GEN
Adder
5.363
970831AG2-522 GEN
Solar/Wind Harmer
4.092
970497AG2-320 GEN
50/50
20.637
3150401LDYSMT4
50/50
28.522
3150371LDYSMT1
50/50
27.56
315051AA1-145 CT1
50/50
1.572
966881AG1-559 GEN
Solar/Wind Harmer
0.674
3142416OLDCHRC
Solar/Wind Harmer
2.177
970293AG2-193 GEN
Solar/Wind Harmer
2.64
3143096IRON208
Adder
0.776
3143096IRON208
Adder
0.76
316473AC1-191 GEN
Solar/Wind Harmer
2.237
3142946ENON
Solar/Wind Harmer
-0.007
3150861SPRUNCD
Adder
0.844
970133AG2-095 GEN
Solar/Wind Harmer
2.286
316382AG1-145 C
Solar/Wind Harmer
0.612
970129AG2-093 GEN
Solar/Wind Harmer
11.374
315778AD1-151 GEN
Solar/Wind Harmer
17.424
965281AG1-393 GEN
Solar/Wind Harmer
2.504
315839AE2-212 C
Solar/Wind Harmer
0.602
3150921YORKTN3
Adder
4.467
3144216WINCHST
Adder
0.67
961611AG1-000B GEN
Solar/Wind Harmer
4.197
3142433PROV 92
Adder
0.344
3142433PROV 92
Adder
0.344
3151221GRAVEL6
Adder
12.845
3151171GRAVELC
Adder
2.471
315773AC2-141 GEN
Solar/Wind Harmer
8.274
3145336SMITFLD
Solar/Wind Harmer
-0.008
315813AE1-149 C
Solar/Wind Harmer
12.293
3144536CHRHLND
Solar/Wind Harmer
-0.003
970659AG2-427 GEN
Solar/Wind Harmer
1.84
3151101ELIZAR3
Adder
16.14
316083AB2-161 GEN
Solar/Wind Harmer
3.169
3144873MCLAUGH
Solar/Wind Harmer
-0.001
944581AF1-123 GEN
Solar/Wind Harmer
88.792
944601AF1-125 GEN
Solar/Wind Harmer
87.406
970661AG2-428 GEN
Solar/Wind Harmer
3.665
3141766HARMONY
Solar/Wind Harmer
1.726
3141843SHACKLE
Adder
0.88
316203AE2-005 GEN
Solar/Wind Harmer
8.161
3146456SLIGO L269
Solar/Wind Harmer
-0.019
971153AH1-033 GEN
Solar/Wind Harmer
2.352
316280AD1-041 GEN
Solar/Wind Harmer
1.452
316156AD2-030 GEN
Solar/Wind Harmer
0.511
3141873WAN 176
Solar/Wind Harmer
2.272
316320Y1-086
Solar/Wind Harmer
1.119
316435W1029_GEN3
Solar/Wind Harmer
3.425
3146516WINFALL
Solar/Wind Harmer
-0.019
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3145273HOLLAND
Solar/Wind Harmer
-0.014
3146376EDENTON
Solar/Wind Harmer
-0.018
962971AG1-146 GEN
Solar/Wind Harmer
3.398
315614AA2-178 GEN
Solar/Wind Harmer
1.938
316484AD2-074 GEN
Solar/Wind Harmer
4.504
970009AG2-005 GEN
Solar/Wind Harmer
2.237
971157AH1-035 GEN
Solar/Wind Harmer
2.207
315737AD1-076 GEN
Solar/Wind Harmer
3.346
3156081AA2-088 GEN
Solar/Wind Harmer
5.701
316313AB2-026
Solar/Wind Harmer
0.474
316258AE1-075 C
Solar/Wind Harmer
0.426
316405AF2-144 C
Solar/Wind Harmer
0.45
3143336POWHATN
Solar/Wind Harmer
1.771
316404AE1-155 C
Solar/Wind Harmer
3.379
3146206CASHIE
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
0.121
3145893MURPHYS
Solar/Wind Harmer
-0.017
957521AF2-046 GEN
Solar/Wind Harmer
13.619
961681AG1-008 GEN
Solar/Wind Harmer
13.619
316365GEN2_N
Solar/Wind Harmer
1.166
3146173TUNIS
Solar/Wind Harmer
-0.017
3156021HOLLOMANSOL
Solar/Wind Harmer
2.313
316463AE2-346 GEN
Solar/Wind Harmer
0.277
316140AB2-099
Solar/Wind Harmer
0.115
962331AG1-082 GEN
Solar/Wind Harmer
2.138
970917AG2-570 GEN
Solar/Wind Harmer
42.678
3146263WOODLND
Solar/Wind Harmer
-0.017
966621AG1-532 GEN
Solar/Wind Harmer
0.342
3150351NORNECKC2
Adder
1.52
3145963POPLR C
Solar/Wind Harmer
-0.017
971781AH1-399 GEN
Solar/Wind Harmer
1.033
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
313506AB2-031 GEN
Solar/Wind Harmer
1.344
316317KELFORD C
Solar/Wind Harmer
0.787
3145823KELFORD
Solar/Wind Harmer
-0.017
3145796HORNRTN
Solar/Wind Harmer
-0.065
3145796HORNRTN
Solar/Wind Harmer
-0.016
3147043LAWRENC
Solar/Wind Harmer
-0.01
3145933PARMELE
Solar/Wind Harmer
-0.016
966801AG1-551 GEN
Solar/Wind Harmer
2.013
316210AC1-098 GEN
Solar/Wind Harmer
2.527
316478AD1-087 GEN
Solar/Wind Harmer
1.384
316486AD2-202 GEN
Solar/Wind Harmer
0.405
972255AH1-712 GEN
Adder
72.658
3144293JTRSVLE
Adder
0.43
227287AC2-120 GEN
Solar/Wind Helper
0.388
226910AB2-157 C
Solar/Wind Helper
0.015
972197AH1-683 GEN
50/50
4.454
972219AH1-694 GEN
50/50
3.207
315052AA1-145 CT2
50/50
1.579
966881AG1-559 GEN
Solar/Wind Harmer
0.23
3142416OLDCHRC
Solar/Wind Harmer
-0.056
3142416OLDCHRC
Solar/Wind Harmer
-0.021
3143096IRON208
Adder
0.776
3142543TWELFTH
Solar/Wind Harmer
-0.002
944631AF1-128 GEN
Adder
87.636
3150851SPRUNCC
Adder
0.844
316159AE1-175 C
Solar/Wind Harmer
0.545
3143526WINTERP
Solar/Wind Harmer
-0.105
970129AG2-093 GEN
Solar/Wind Harmer
4.607
316458AB2-190 GEN2
Solar/Wind Harmer
2.042
971069AG2-661 GEN
Solar/Wind Harmer
3.182
315671AE2-027_GEN
Solar/Wind Harmer
15.069
971647AH1-324 GEN
Solar/Wind Harmer
9.998
971317AH1-138 GEN
Solar/Wind Harmer
2.497
3138126ROCKLANDING
Solar/Wind Harmer
0.061
961611AG1-000B GEN
Solar/Wind Harmer
9.836
3142433PROV 92
Solar/Wind Harmer
-0.079
3142433PROV 92
Adder
0.344
3142433PROV 92
Adder
0.344
3143226MDLTHAN
Solar/Wind Harmer
-0.02
3151171GRAVELC
Adder
1.879
316294AC1-161 GEN
Solar/Wind Harmer
6.398
3145336SMITFLD
Solar/Wind Harmer
-0.079
970659AG2-427 GEN
Solar/Wind Harmer
10.386
316375AC2-012 GEN
Solar/Wind Harmer
6.758
3150981CHESPKA
Adder
2.17
316381AD1-082 GEN
Solar/Wind Harmer
1.791
944591AF1-124 GEN
Solar/Wind Harmer
89.112
970661AG2-428 GEN
Solar/Wind Harmer
20.679
316072AD1-144
Solar/Wind Harmer
0.393
3141766HARMONY
Solar/Wind Harmer
-0.004
971777AH1-397 GEN
Solar/Wind Harmer
2.276
3141843SHACKLE
Adder
0.88
316388AE2-253 GEN
Solar/Wind Harmer
1.305
3146456SLIGO L269
Solar/Wind Harmer
-0.019
316246AF1-032 C
Solar/Wind Harmer
0.39
316093AE2-104_GEN
Solar/Wind Harmer
5.572
939411AE1-173 GEN
Solar/Wind Harmer
95.213
940641AE2-051 GEN
Solar/Wind Harmer
17.725
3146516WINFALL
Solar/Wind Harmer
-0.061
3146516WINFALL
Solar/Wind Harmer
-0.019
3138133OCRAN
Solar/Wind Harmer
-0.011
315800Z1-036_GEN1
Solar/Wind Harmer
4.589
3130156CHOWAN
Solar/Wind Harmer
-0.018
3145663CRESWEL
Solar/Wind Harmer
-0.05
971163AH1-040 GEN
Solar/Wind Harmer
16.838
961951AG1-038 GEN
Solar/Wind Harmer
2.357
962861AG1-135 GEN
Solar/Wind Harmer
6.607
3143336POWHATN
Solar/Wind Harmer
2.084
3146206CASHIE
Solar/Wind Harmer
-0.017
971547AH1-271 GEN
Solar/Wind Harmer
4.356
3145893MURPHYS
Solar/Wind Harmer
-0.069
3145893MURPHYS
Solar/Wind Harmer
0.514
316023GEN1_S
Solar/Wind Harmer
1.166
964211AG1-282 GEN
Solar/Wind Harmer
0.517
3141726DUNNSVL
Solar/Wind Harmer
-0.068
3146173TUNIS
Solar/Wind Harmer
-0.017
970919AG2-571 GEN
Solar/Wind Harmer
5.402
3145683EARLEYS
Solar/Wind Harmer
-0.017
970087AG2-069 GEN
Solar/Wind Harmer
15.949
316336AC2-165 C
Solar/Wind Harmer
2.947
3146263WOODLND
Solar/Wind Harmer
-0.017
960081AF2-299 GEN
Solar/Wind Harmer
1.898
3150351NORNECKC2
Adder
1.495
3145963POPLR C
Solar/Wind Harmer
-0.017
3145823KELFORD
Solar/Wind Harmer
-0.017
316011AB1-132 GEN
Solar/Wind Harmer
3.487
962571AG1-106 GEN
Solar/Wind Harmer
2.396
316174AB2-169 GEN
Solar/Wind Harmer
2.569
316190AA2-174 GEN
Solar/Wind Harmer
0.204
971795AH1-408 GEN
Solar/Wind Harmer
12.402
957481AF2-042 GEN
Solar/Wind Harmer
51.531
3145783HORNRTN
Solar/Wind Harmer
-0.016
3145796HORNRTN
Solar/Wind Harmer
-0.054
3145796HORNRTN
Solar/Wind Harmer
-0.016
3147043LAWRENC
Adder
1.319
315693AD1-088 GEN
Solar/Wind Harmer
8.126
962491AG1-098 GEN
Solar/Wind Harmer
10.846
3146293MARTNCO
Solar/Wind Harmer
0.1
316212AC1-099_GEN
Solar/Wind Harmer
1.404
972277AH1-723 GEN
Adder
84.669
3144293JTRSVLE
Adder
0.43
NYPJM->LTFIMP_NY
CLTF
2.848
LGEELTFEXP_LGEE->PJM
CLTF
1.613
WECLTFEXP_WEC->PJM
CLTF
0.819
LAGNLTFEXP_LAGN->PJM
CLTF
7.576
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.212
TVALTFEXP_TVA->PJM
CLTF
3.836
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.893
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.398
MECLTFEXP_MEC->PJM
CLTF
4.164
SIGELTFEXP_SIGE->PJM
CLTF
0.129
CPLELTFEXP_CPLE->PJM
CLTF
8.886
CBM West 2LTFEXP_CBM-W2->PJM
CBM
42.062

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:175.45 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:5650.14
MW Contribution:76.92
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
4.373
3151101ELIZAR3
50/50
30.305
3150861SPRUNCD
50/50
1.461
3151161SURRY 1
50/50
11.304
970917AG2-570 GEN
Solar/Wind Harmer
28.408
315773AC2-141 GEN
Solar/Wind Harmer
11.382
944581AF1-123 GEN
Solar/Wind Harmer
69.733
944601AF1-125 GEN
Solar/Wind Harmer
68.658
3144873MCLAUGH
Solar/Wind Harmer
0.008
3146456SLIGO L269
Solar/Wind Harmer
0.306
971153AH1-033 GEN
Solar/Wind Harmer
3.534
3144536CHRHLND
Solar/Wind Harmer
0.046
316320Y1-086
Solar/Wind Harmer
0.002
970661AG2-428 GEN
Solar/Wind Harmer
6.41
316083AB2-161 GEN
Solar/Wind Harmer
0.004
970659AG2-427 GEN
Solar/Wind Harmer
3.204
315813AE1-149 C
Solar/Wind Harmer
16.153
316435W1029_GEN3
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.3
3145336SMITFLD
Solar/Wind Harmer
0.12
3146626S HERTFORD
Solar/Wind Harmer
0.299
315839AE2-212 C
Solar/Wind Harmer
0.002
3145273HOLLAND
Solar/Wind Harmer
0.223
316313AB2-026
Solar/Wind Harmer
0.186
316258AE1-075 C
Solar/Wind Harmer
0.223
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
4.463
965281AG1-393 GEN
Solar/Wind Harmer
3.139
3151221GRAVEL6
Adder
21.396
3151171GRAVELC
Adder
4.116
3146376EDENTON
Solar/Wind Harmer
0.294
961611AG1-000B GEN
Solar/Wind Harmer
7.797
316365GEN2_N
Solar/Wind Harmer
0.655
315614AA2-178 GEN
Solar/Wind Harmer
1.657
315778AD1-151 GEN
Solar/Wind Harmer
23.065
3156081AA2-088 GEN
Solar/Wind Harmer
0.007
970129AG2-093 GEN
Solar/Wind Harmer
17.309
316478AD1-087 GEN
Solar/Wind Harmer
0.999
316486AD2-202 GEN
Solar/Wind Harmer
0.293
971157AH1-035 GEN
Solar/Wind Harmer
3.43
315737AD1-076 GEN
Solar/Wind Harmer
3.669
3144216WINCHST
Adder
1.072
970133AG2-095 GEN
Solar/Wind Harmer
2.723
3145893MURPHYS
Solar/Wind Harmer
0.474
3145893MURPHYS
Solar/Wind Harmer
0.283
3146206CASHIE
Solar/Wind Harmer
0.283
957521AF2-046 GEN
Solar/Wind Harmer
21.052
961681AG1-008 GEN
Solar/Wind Harmer
21.052
3150921YORKTN3
Adder
7.103
3146173TUNIS
Solar/Wind Harmer
0.281
313506AB2-031 GEN
Solar/Wind Harmer
0.867
3156021HOLLOMANSOL
Solar/Wind Harmer
1.274
316463AE2-346 GEN
Solar/Wind Harmer
0.241
316140AB2-099
Solar/Wind Harmer
0.1
962331AG1-082 GEN
Solar/Wind Harmer
2.99
3142666NORTHAMPTON
Solar/Wind Harmer
0.279
3146263WOODLND
Solar/Wind Harmer
0.278
3147043LAWRENC
Solar/Wind Harmer
0.166
316317KELFORD C
Solar/Wind Harmer
0.027
3145823KELFORD
Solar/Wind Harmer
0.275
3145796HORNRTN
Solar/Wind Harmer
1.1
3145796HORNRTN
Solar/Wind Harmer
0.275
3145963POPLR C
Solar/Wind Harmer
0.274
3143096IRON208
Adder
1.147
3143096IRON208
Adder
1.124
316382AG1-145 C
Solar/Wind Harmer
0.002
316210AC1-098 GEN
Solar/Wind Harmer
2.485
3145933PARMELE
Solar/Wind Harmer
0.265
966801AG1-551 GEN
Solar/Wind Harmer
3.091
3142946ENON
Solar/Wind Harmer
0.089
315724AD1-057 GEN
Solar/Wind Harmer
0.985
3145746EVERETS
Solar/Wind Harmer
0.261
3145746EVERETS
Solar/Wind Harmer
0.261
316327AA2-057 GEN
Solar/Wind Harmer
0.393
970909AG2-566 GEN
Solar/Wind Harmer
2.748
316131AB2-060 GEN
Solar/Wind Harmer
0.81
3146233WITAKRS
Solar/Wind Harmer
1.286
3146233WITAKRS
Solar/Wind Harmer
0.174
3138543CONSLDL
Solar/Wind Harmer
0.169
964241AG1-285 GEN
Solar/Wind Harmer
17.051
3146073TAR RVR
Solar/Wind Harmer
0.255
3146083TARBORO
Solar/Wind Harmer
0.255
970293AG2-193 GEN
Solar/Wind Harmer
2.717
3142433PROV 92
Adder
0.492
3142433PROV 92
Adder
0.492
315785AD2-033 C
Solar/Wind Harmer
2.056
961601AG1-000A GEN
Solar/Wind Harmer
17.946
3145543BTLEBRO
Solar/Wind Harmer
0.252
3145543BTLEBRO
Solar/Wind Harmer
0.252
971623AH1-311 GEN
Solar/Wind Harmer
0.505
970257AG2-171 GEN
Solar/Wind Harmer
8.061
959311AF2-222 GEN
Solar/Wind Harmer
22.323
963181AG1-167 GEN
Solar/Wind Harmer
0.987
3144293JTRSVLE
Adder
0.785
3147133PAMPLIN
Solar/Wind Harmer
0.769
971193AH1-056 GEN
Solar/Wind Harmer
14.916
3141843SHACKLE
Adder
1.244
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316280AD1-041 GEN
Solar/Wind Harmer
0.005
3141766HARMONY
Solar/Wind Harmer
3.224
316156AD2-030 GEN
Solar/Wind Harmer
0.179
3141873WAN 176
Solar/Wind Harmer
4.293
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
10.242
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3142416OLDCHRC
Solar/Wind Harmer
2.323
3146926FARMVIL
Solar/Wind Harmer
0.141
971683AH1-343 GEN
Solar/Wind Harmer
8.112
962971AG1-146 GEN
Solar/Wind Harmer
3.502
316283AC2-100 C
Solar/Wind Harmer
0.428
316473AC1-191 GEN
Solar/Wind Harmer
0.734
970009AG2-005 GEN
Solar/Wind Harmer
1.596
3146776BUCKING
Solar/Wind Harmer
0.076
316404AE1-155 C
Solar/Wind Harmer
0.046
3150351NORNECKC2
Adder
1.933
970221AG2-151 GEN
Solar/Wind Harmer
9.113
971781AH1-399 GEN
Solar/Wind Harmer
0.197
3141906WESTMOR
Solar/Wind Harmer
0.057
270197AD1-017 GEN1
Solar/Wind Harmer
0.888
270018AE2-047 C O1
Solar/Wind Harmer
0.003
3147312GRETNA
Solar/Wind Harmer
0.026
941821AE2-187 GEN
Solar/Wind Harmer
4.176
972255AH1-712 GEN
Adder
66.009
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
970737AG2-469 GEN
Solar/Wind Harmer
5.167
958131AF2-107 GEN
Solar/Wind Harmer
3.333
316044AC1-158 PL1
Solar/Wind Helper
2.198
316450AC1-158 RIC
Solar/Wind Helper
0.586
3147666LOUISA
Solar/Wind Helper
0.715
316170AC1-121 GEN2
Solar/Wind Helper
0.429
3141196NOKESVL
Solar/Wind Helper
1.038
3132273ORANGE
Solar/Wind Helper
0.047
227287AC2-120 GEN
Solar/Wind Helper
0.311
226910AB2-157 C
Solar/Wind Helper
0.013
970119AG2-088 GEN
50/50
49.132
315243AE2-183_GT3
50/50
5.558
3151051BRUNSWICKS1
50/50
9.077
3151021BRUNSWICKG1
50/50
4.373
971451AH1-221 GEN
50/50
13.283
3150981CHESPKA
50/50
4.07
3150851SPRUNCC
50/50
1.461
3152331SURRY 2
50/50
12.331
3143226MDLTHAN
Solar/Wind Harmer
0.368
940641AE2-051 GEN
Solar/Wind Harmer
28.054
939411AE1-173 GEN
Solar/Wind Harmer
145.057
3143526WINTERP
Solar/Wind Harmer
1.742
970919AG2-571 GEN
Solar/Wind Harmer
11.363
970087AG2-069 GEN
Solar/Wind Harmer
25.456
316294AC1-161 GEN
Solar/Wind Harmer
5.4
944591AF1-124 GEN
Solar/Wind Harmer
69.98
316375AC2-012 GEN
Solar/Wind Harmer
0.008
316388AE2-253 GEN
Solar/Wind Harmer
0.96
3146456SLIGO L269
Solar/Wind Harmer
0.306
316246AF1-032 C
Solar/Wind Harmer
0.137
316093AE2-104_GEN
Solar/Wind Harmer
5.099
970661AG2-428 GEN
Solar/Wind Harmer
30.138
316381AD1-082 GEN
Solar/Wind Harmer
0.316
970659AG2-427 GEN
Solar/Wind Harmer
14.649
316072AD1-144
Solar/Wind Harmer
0.109
3146516WINFALL
Solar/Wind Harmer
0.972
3146516WINFALL
Solar/Wind Harmer
0.3
3145336SMITFLD
Solar/Wind Harmer
1.197
957481AF2-042 GEN
Solar/Wind Harmer
79.695
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
5.25
3130156CHOWAN
Solar/Wind Harmer
0.294
3151171GRAVELC
Adder
3.13
961611AG1-000B GEN
Solar/Wind Harmer
15.335
315671AE2-027_GEN
Solar/Wind Harmer
18.679
316023GEN1_S
Solar/Wind Harmer
0.655
971647AH1-324 GEN
Solar/Wind Harmer
12.413
3145663CRESWEL
Solar/Wind Harmer
0.81
971163AH1-040 GEN
Solar/Wind Harmer
23.157
315693AD1-088 GEN
Solar/Wind Harmer
13.873
971069AG2-661 GEN
Solar/Wind Harmer
5.126
962491AG1-098 GEN
Solar/Wind Harmer
16.401
316458AB2-190 GEN2
Solar/Wind Harmer
1.538
970129AG2-093 GEN
Solar/Wind Harmer
8.145
960081AF2-299 GEN
Solar/Wind Harmer
2.73
3138126ROCKLANDING
Solar/Wind Harmer
0.13
3145893MURPHYS
Solar/Wind Harmer
1.134
3145893MURPHYS
Solar/Wind Harmer
1.26
3146206CASHIE
Solar/Wind Harmer
0.283
971547AH1-271 GEN
Solar/Wind Harmer
6.043
3146173TUNIS
Solar/Wind Harmer
0.281
3142543TWELFTH
Solar/Wind Harmer
0.027
3145683EARLEYS
Solar/Wind Harmer
0.279
316011AB1-132 GEN
Solar/Wind Harmer
5.071
962571AG1-106 GEN
Solar/Wind Harmer
3.968
971795AH1-408 GEN
Solar/Wind Harmer
18.591
3146263WOODLND
Solar/Wind Harmer
0.278
316190AA2-174 GEN
Solar/Wind Harmer
0
3147043LAWRENC
Adder
2.5
316336AC2-165 C
Solar/Wind Harmer
0.011
971317AH1-138 GEN
Solar/Wind Harmer
2.057
3145823KELFORD
Solar/Wind Harmer
0.275
3145796HORNRTN
Solar/Wind Harmer
0.907
3145796HORNRTN
Solar/Wind Harmer
0.275
3145783HORNRTN
Solar/Wind Harmer
0.275
3145963POPLR C
Solar/Wind Harmer
0.274
3143096IRON208
Adder
1.147
316174AB2-169 GEN
Solar/Wind Harmer
0.007
316159AE1-175 C
Solar/Wind Harmer
0.235
944631AF1-128 GEN
Adder
128.871
315687AD1-152 GEN
Solar/Wind Harmer
0.009
316212AC1-099_GEN
Solar/Wind Harmer
1.386
316129AC1-054 GEN
Solar/Wind Harmer
1.006
971065AG2-659 GEN
Solar/Wind Harmer
11.378
3146293MARTNCO
Solar/Wind Harmer
0.246
315722AD1-056 GEN
Solar/Wind Harmer
1.662
3145746EVERETS
Solar/Wind Harmer
0.261
3145746EVERETS
Solar/Wind Harmer
0.261
316494AC1-189 GEN
Solar/Wind Harmer
0.872
316237AB2-079_GEN
Solar/Wind Harmer
0.002
3146233WITAKRS
Solar/Wind Harmer
1.019
961671AG1-007 GEN
Solar/Wind Harmer
0.039
3146083TARBORO
Solar/Wind Harmer
0.255
3145493TOT1
Solar/Wind Harmer
1.136
3142433PROV 92
Solar/Wind Harmer
1.012
3142433PROV 92
Adder
0.492
3142433PROV 92
Adder
0.492
316359AB2-059 GEN
Solar/Wind Harmer
0.906
316049AB1-081 GEN
Solar/Wind Harmer
1.444
3145543BTLEBRO
Solar/Wind Harmer
0.252
3145543BTLEBRO
Solar/Wind Harmer
0.202
3142053HEARTS
Solar/Wind Harmer
0.444
970685AG2-442 GEN
Solar/Wind Harmer
18.609
970401AG2-262 GEN
Solar/Wind Harmer
1.452
963171AG1-166 GEN
Solar/Wind Harmer
1.316
971563AH1-280 GEN
Solar/Wind Harmer
2.632
3144293JTRSVLE
Adder
0.785
971777AH1-397 GEN
Solar/Wind Harmer
0.643
3141843SHACKLE
Adder
1.244
3141766HARMONY
Solar/Wind Harmer
0.048
3142416OLDCHRC
Solar/Wind Harmer
0.623
3142416OLDCHRC
Solar/Wind Harmer
0.239
3146926FARMVIL
Solar/Wind Harmer
0.141
3138133OCRAN
Solar/Wind Harmer
0.139
316003AC1-222 GEN
Solar/Wind Harmer
0.006
970937AG2-583 GEN
Solar/Wind Harmer
13.92
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.085
962861AG1-135 GEN
Solar/Wind Harmer
6.647
3141726DUNNSVL
Solar/Wind Harmer
0.786
3150351NORNECKC2
Adder
1.901
972003AH1-546 GEN
Solar/Wind Harmer
8.083
971377AH1-170 GEN
Solar/Wind Harmer
1.823
3147623JAMES R
Solar/Wind Harmer
0.396
316337AD2-073 GEN
Solar/Wind Harmer
0.146
970223AG2-152 GEN
Solar/Wind Harmer
10.672
270016AE1-250 BESS
Solar/Wind Harmer
0.004
3147123OTTER R
Solar/Wind Harmer
0.084
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
3147312GRETNA
Solar/Wind Harmer
0.104
3146802CHATHAM
Solar/Wind Harmer
0.098
941801AE2-185 GEN
Solar/Wind Harmer
4.176
972277AH1-723 GEN
Adder
76.921
270030AE2-140 GEN
Solar/Wind Harmer
12.711
316045AC1-158 PL2
Solar/Wind Helper
7.036
3147666LOUISA
Solar/Wind Helper
1.244
316192AB2-158 GEN
Solar/Wind Helper
2.045
316254AC1-120 GEN1
Solar/Wind Helper
1.287
316006AB2-029 C
Solar/Wind Helper
0.13
316303AF2-085
50/50
6.551
315244AE2-183_ST
50/50
9.609
963041AG1-153 GEN
50/50
8.856
315779AE2-040
50/50
4.414
3151081ELIZAR1
50/50
29.922
3151091ELIZAR2
50/50
29.403
941591AE2-156 GEN
50/50
27.332
3152611GOSPORTB
50/50
4.152
3152621GOSPORTC
50/50
3.523
3152601GOSPORTA
50/50
3.25
971285AH1-108 GEN
50/50
2.391
972263AH1-716 GEN
50/50
170.662
941031AE2-094 GEN
Solar/Wind Harmer
63.788
944011AF1-069 GEN
Solar/Wind Harmer
20.842
970673AG2-436 GEN
Solar/Wind Harmer
72.487
970673AG2-436 GEN
Solar/Wind Harmer
48.325
316233AE1-074 FULL
Solar/Wind Harmer
0.268
971281AH1-106 GEN
Solar/Wind Harmer
4.649
971283AH1-107 GEN
Solar/Wind Harmer
4.649
971967AH1-528 GEN
Solar/Wind Harmer
53.477
970085AG2-068 GEN
Solar/Wind Harmer
16.971
970581AG2-369 GEN
Solar/Wind Harmer
14.595
316315AB2-025 C
Solar/Wind Harmer
0.256
315814AE2-033 C
Solar/Wind Harmer
24.917
3143316POE
Solar/Wind Harmer
1.232
957871AF2-081 GEN
Solar/Wind Harmer
15.244
319010AE1-072 C
Solar/Wind Harmer
1.539
3146406KITTY HAWK
Solar/Wind Harmer
0.038
316305AF2-043 C
Solar/Wind Harmer
0.002
313526AB2-022
Solar/Wind Harmer
0.164
315835AF2-110_GEN
Solar/Wind Harmer
2.081
315833AF1-017_GEN
Solar/Wind Harmer
0.002
316349AD2-085 GEN
Solar/Wind Harmer
0.208
316311AC2-079 GEN
Solar/Wind Harmer
8.702
3146486SUNBURY
Solar/Wind Harmer
0.302
3146486SUNBURY
Solar/Wind Harmer
0.302
316321Z2-027
Solar/Wind Harmer
0.056
3146396TANGLEW
Solar/Wind Harmer
0.833
3145176PASQUOTANK
Solar/Wind Harmer
0.187
971445AH1-216 GEN
Solar/Wind Harmer
21.042
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.294
3130156CHOWAN
Solar/Wind Harmer
0.294
972265AH1-717 GEN
Adder
22.85
3151201GRAVEL4
Adder
21.42
3151191GRAVEL3
Adder
21.149
3151211GRAVEL5
Adder
21.149
316369SG1_INVT
Solar/Wind Harmer
0.011
315816AE2-034 GEN
Solar/Wind Harmer
1.242
316132AB2-190 GEN1
Solar/Wind Harmer
1.538
3130546PLYMOUTH
Solar/Wind Harmer
0.286
965291AG1-394 GEN
Solar/Wind Harmer
1.269
315732AD1-074 GEN1
Solar/Wind Harmer
1.639
315733AD1-074 GEN2
Solar/Wind Harmer
1.639
315735AD1-075 GEN1
Solar/Wind Harmer
0.82
3145893MURPHYS
Solar/Wind Harmer
0.765
3145893MURPHYS
Solar/Wind Harmer
0.283
3146206CASHIE
Solar/Wind Harmer
0.283
970601AG2-382 GEN
Solar/Wind Harmer
10.575
316087AB2-174 GEN
Solar/Wind Harmer
0.008
3146043SEABORD
Solar/Wind Harmer
0.28
970533AG2-339 GEN
50/50
30.786
970531AG2-338 GEN
50/50
12.314
315242AE2-183_GT2
50/50
5.558
315241AE2-183_GT1
50/50
5.524
972185AH1-677 GEN
50/50
20.036
3151041BRUNSWICKG3
50/50
4.373
972187AH1-678 GEN
50/50
10.036
3150991CHESPKB
50/50
3.415
3150991CHESPKB
50/50
3.333
971223AH1-071 GEN
Solar/Wind Harmer
3.931
3143526WINTERP
Solar/Wind Harmer
1.742
970933AG2-581 GEN
Solar/Wind Harmer
25.944
3144356SAPONY
Solar/Wind Harmer
2.645
316185AD1-033 GEN
Solar/Wind Harmer
0.009
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.295
3145506HICKORY
Solar/Wind Harmer
1.229
3145506HICKORY
Solar/Wind Harmer
0.737
3145506HICKORY
Solar/Wind Harmer
0.184
316036AC1-147 C
Solar/Wind Harmer
0.057
316339AD2-160 GEN
Solar/Wind Harmer
0.497
316018AA1-139 ULT2
Solar/Wind Harmer
0.008
316017AA1-139 ULT1
Solar/Wind Harmer
0.171
3137176SLIGO L2192
Solar/Wind Harmer
1.217
3146456SLIGO L269
Solar/Wind Harmer
5.409
3130086AYDLETT
Solar/Wind Harmer
1.221
3146386ELIZ CT
Solar/Wind Harmer
0.303
970657AG2-426 GEN
Solar/Wind Harmer
10.611
970657AG2-426 GEN
Solar/Wind Harmer
2.224
316431W1029_GEN1
Solar/Wind Harmer
0.002
316433W1029_GEN2
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.3
3146516WINFALL
Solar/Wind Harmer
0.3
3146516WINFALL
Solar/Wind Harmer
0.3
316236AE1-162_GEN
Solar/Wind Harmer
0.002
3146626S HERTFORD
Solar/Wind Harmer
0.299
3146626S HERTFORD
Solar/Wind Harmer
0.299
970099AG2-077 GEN
Solar/Wind Harmer
31.878
315742AE1-103 GEN
Solar/Wind Harmer
0.003
3146376EDENTON
Solar/Wind Harmer
1.308
3146376EDENTON
Solar/Wind Harmer
1.308
316240AF1-291 C
Solar/Wind Harmer
0.002
316033AB2-134 GEN
Solar/Wind Harmer
0.017
315697AD1-025 GEN
Solar/Wind Harmer
0.325
944641AF1-129 GEN
Adder
137.21
316065AD1-022 GEN
Solar/Wind Harmer
13.074
3145893MURPHYS
Solar/Wind Harmer
1.897
3145893MURPHYS
Solar/Wind Harmer
0.51
3146173TUNIS
Solar/Wind Harmer
0.281
3146173TUNIS
Solar/Wind Harmer
0.281
316181AB2-040 GEN
Solar/Wind Harmer
0.407
3142666NORTHAMPTON
Solar/Wind Harmer
0.279
3142666NORTHAMPTON
Solar/Wind Harmer
0.279
3142666NORTHAMPTON
Solar/Wind Harmer
0.279
3142666NORTHAMPTON
Solar/Wind Harmer
0.167
316426AA2-053 GEN
Solar/Wind Harmer
0.935
3145593CAROLNA
Solar/Wind Harmer
0.276
3145593CAROLNA
Solar/Wind Harmer
0.276
966811AG1-552 GEN
Solar/Wind Harmer
2.997
3145593CAROLNA
Solar/Wind Harmer
0.344
3145796HORNRTN
Solar/Wind Harmer
0.825
3145783HORNRTN
Solar/Wind Harmer
4.886
3145783HORNRTN
Solar/Wind Harmer
3.909
3145783HORNRTN
Solar/Wind Harmer
1.222
3145783HORNRTN
Solar/Wind Harmer
0.489
316274AC1-208 GEN
Solar/Wind Harmer
1.384
3145933PARMELE
Solar/Wind Harmer
0.531
3145933PARMELE
Solar/Wind Harmer
0.265
3142946ENON
Solar/Wind Harmer
0.026
971741AH1-377 GEN
Solar/Wind Harmer
26.27
939181AE1-148 GEN
Solar/Wind Harmer
12.567
3142366NRTHEST
Adder
0.844
313527AB2-043 GEN
Solar/Wind Harmer
0.003
970301AG2-198 GEN
Solar/Wind Harmer
10.992
3150691DARBY 3
Adder
18.496
3150701DARBY 4
Adder
18.453
3150681DARBY 2
Adder
18.432
3150671DARBY 1
Adder
18.41
3145493TOT1
Solar/Wind Harmer
0.592
3145453TOT5
Solar/Wind Harmer
0.355
3145603CNETO
Solar/Wind Harmer
0.237
961601AG1-000A GEN
Solar/Wind Harmer
4.486
316263AC1-034 GEN
Solar/Wind Harmer
9.586
316075AC2-137 C
Solar/Wind Harmer
0.069
970323AG2-213 GEN
Solar/Wind Harmer
10.747
971775AH1-396 GEN
Solar/Wind Harmer
0.403
316034AC1-036 C
Solar/Wind Harmer
0.018
962561AG1-105 GEN
Solar/Wind Harmer
11.957
964791AG1-342 GEN
Solar/Wind Harmer
4.752
3146843MT LREL
Solar/Wind Harmer
0.247
3146843MT LREL
Solar/Wind Harmer
0.247
958211AF2-115 GEN
Solar/Wind Harmer
2.961
963191AG1-168 GEN
Solar/Wind Harmer
0.987
3144293JTRSVLE
Adder
0.785
3144293JTRSVLE
Adder
0.661
3147133PAMPLIN
Solar/Wind Harmer
0.245
3147133PAMPLIN
Solar/Wind Harmer
0.196
3142296MT RD221
Adder
0.748
316222AC1-221 GEN
Solar/Wind Harmer
0.912
966871AG1-558 GEN
Solar/Wind Harmer
0.251
3146776BUCKING
Solar/Wind Harmer
0.848
3146776BUCKING
Solar/Wind Harmer
0.069
958261AF2-120 GEN
Solar/Wind Harmer
6.796
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
1.997
3150341NORNECKC1
Adder
1.981
942751AE2-291 GEN
Solar/Wind Harmer
9.768
971489AH1-241 GEN
Solar/Wind Harmer
9.113
316468AD1-105 GEN
Solar/Wind Harmer
-0.049
270013AE1-250 PV
Solar/Wind Harmer
0.004
315821AE2-092 GEN
Solar/Wind Harmer
0.008
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
3.248
316447AC1-158 HLD
Solar/Wind Helper
4.837
315651AD1-115 GEN
Solar/Wind Helper
0.937
226929AD2-058 GEN
Solar/Wind Helper
0.091
3145513AHOSKIE
Solar/Wind Harmer
0.586
3145513AHOSKIE
Solar/Wind Harmer
0.28
315607AA1-063A GEN
Solar/Wind Harmer
0.572
3145683EARLEYS
Solar/Wind Harmer
0.558
3145683EARLEYS
Solar/Wind Harmer
0.279
3145683EARLEYS
Solar/Wind Harmer
0.279
315652AC1-086 GEN
Solar/Wind Harmer
30.678
3137643SOCKMAN
Solar/Wind Harmer
1.111
3145796HORNRTN
Solar/Wind Harmer
0.88
3145796HORNRTN
Solar/Wind Harmer
0.11
3146033SCOT NK
Solar/Wind Harmer
1.084
970831AG2-522 GEN
Solar/Wind Harmer
11.448
3138283WHITEMARSH
Solar/Wind Harmer
0.061
316005AA1-067
Solar/Wind Harmer
0.28
3145746EVERETS
Solar/Wind Harmer
1.039
3145746EVERETS
Solar/Wind Harmer
0.261
3145746EVERETS
Solar/Wind Harmer
0.261
3145746EVERETS
Solar/Wind Harmer
0.261
970181AG2-120 GEN
Solar/Wind Harmer
3.25
957861AF2-080 GEN
Solar/Wind Harmer
11.129
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316420AA1-050 GEN
Solar/Wind Harmer
0.008
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.255
3145573BETHELC
Solar/Wind Harmer
0.255
971167AH1-042 GEN
Solar/Wind Harmer
22.645
315976AC1-164 GENA
Solar/Wind Harmer
26.291
316169AC1-164_GENC
Solar/Wind Harmer
22.713
315975AC1-164 GENB
Solar/Wind Harmer
0.778
3142433PROV 92
Adder
0.492
3142433PROV 92
Adder
0.492
971443AH1-215 GEN
Solar/Wind Harmer
4.236
3144303KENBRDG
Solar/Wind Harmer
0.201
970683AG2-441 GEN
Solar/Wind Harmer
16.616
970681AG2-440 GEN
Solar/Wind Harmer
13.292
946301AF1-294 GEN
Solar/Wind Harmer
4.868
961791AG1-021 GEN
Solar/Wind Harmer
2.368
3143873LANEXA
Solar/Wind Harmer
0.148
315657AE1-056 GEN
Solar/Wind Harmer
8.449
316118AC1-105 GEN
Solar/Wind Harmer
0.629
970189AG2-124 GEN
Solar/Wind Harmer
7.213
315662AE1-191 GEN
Solar/Wind Harmer
0.008
315666AE1-190 GEN
Solar/Wind Harmer
0.002
316314AB2-024 C
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.002
3141873WAN 176
Solar/Wind Harmer
0.048
3147173SINAI
Solar/Wind Harmer
0.24
3147243WELCO
Solar/Wind Harmer
0.15
316312AB1-027
Solar/Wind Harmer
0.429
3141913WHIT STONE
Solar/Wind Harmer
0.234
3138133OCRAN
Solar/Wind Harmer
0.069
3141783LANCAST
Solar/Wind Harmer
0.137
3141783LANCAST
Solar/Wind Harmer
0.091
962981AG1-147 GEN
Solar/Wind Harmer
8.172
970285AG2-188 GEN
Solar/Wind Harmer
17.223
971845AH1-439 GEN
Solar/Wind Harmer
9.707
970327AG2-215 GEN
Solar/Wind Harmer
7.016
970865AG2-541 GEN
Solar/Wind Harmer
7.314
316123AC1-075 GEN
Solar/Wind Harmer
0.262
970165AG2-112 GEN
Solar/Wind Harmer
1.554
970163AG2-111 GEN
Solar/Wind Harmer
1.483
3141813NORNECK
Solar/Wind Harmer
0.191
972205AH1-687 GEN
Adder
7.916
971447AH1-217 GEN
Solar/Wind Harmer
4.969
270494AE1-108_GEN
Solar/Wind Harmer
1.845
972189AH1-679 GEN
Adder
2.488
316223AC1-118
Solar/Wind Harmer
0.103
972193AH1-681 GEN
Adder
2.949
316164AC1-076 GEN
Solar/Wind Helper
1.496
316411AF1-147_GEN1
Solar/Wind Helper
0.807
316415AF1-147_GEN2
Solar/Wind Helper
0.807
3138216PACIFIC
Solar/Wind Helper
0.039
NYPJM->LTFIMP_NY
CLTF
3.567
LGEELTFEXP_LGEE->PJM
CLTF
2.341
WECLTFEXP_WEC->PJM
CLTF
1.189
AG2-052LTFEXP_AG2-052->PJM
LTF
0.064
AH1-155LTFEXP_AH1-155->PJM
LTF
0.096
LAGNLTFEXP_LAGN->PJM
CLTF
12.487
CBM South 2LTFEXP_CBM-S2->PJM
CBM
36.918
TVALTFEXP_TVA->PJM
CLTF
6.285
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.504
CBM South 1LTFEXP_CBM-S1->PJM
CBM
21.654
MECLTFEXP_MEC->PJM
CLTF
6.28
SIGELTFEXP_SIGE->PJM
CLTF
0.191
CPLELTFEXP_CPLE->PJM
CLTF
16.793
CBM West 2LTFEXP_CBM-W2->PJM
CBM
66.855

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:154.63 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:6092.43
MW Contribution:78.72
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
6.608
315244AE2-183_ST
50/50
9.677
963041AG1-153 GEN
50/50
8.919
315779AE2-040
50/50
4.458
3151081ELIZAR1
50/50
30.271
3151091ELIZAR2
50/50
29.745
941591AE2-156 GEN
50/50
27.651
3152611GOSPORTB
50/50
4.2
3152621GOSPORTC
50/50
3.565
3152601GOSPORTA
50/50
3.288
971285AH1-108 GEN
50/50
2.43
972263AH1-716 GEN
50/50
172.931
941031AE2-094 GEN
Solar/Wind Harmer
73.475
944011AF1-069 GEN
Solar/Wind Harmer
23.022
970673AG2-436 GEN
Solar/Wind Harmer
80.77
970673AG2-436 GEN
Solar/Wind Harmer
40.896
316233AE1-074 FULL
Solar/Wind Harmer
1.026
971281AH1-106 GEN
Solar/Wind Harmer
6.195
971283AH1-107 GEN
Solar/Wind Harmer
6.195
971967AH1-528 GEN
Solar/Wind Harmer
71.103
970085AG2-068 GEN
Solar/Wind Harmer
22.506
970581AG2-369 GEN
Solar/Wind Harmer
19.356
316315AB2-025 C
Solar/Wind Harmer
0.968
315814AE2-033 C
Solar/Wind Harmer
33.285
3143316POE
Solar/Wind Harmer
-0.139
957871AF2-081 GEN
Solar/Wind Harmer
17.401
319010AE1-072 C
Solar/Wind Harmer
7.024
3146406KITTY HAWK
Solar/Wind Harmer
0.029
316305AF2-043 C
Solar/Wind Harmer
1.044
313526AB2-022
Solar/Wind Harmer
0.93
315833AF1-017_GEN
Solar/Wind Harmer
6.546
316349AD2-085 GEN
Solar/Wind Harmer
3.065
316311AC2-079 GEN
Solar/Wind Harmer
17.383
315835AF2-110_GEN
Solar/Wind Harmer
4.308
3146486SUNBURY
Solar/Wind Harmer
-0.034
3146486SUNBURY
Solar/Wind Harmer
-0.034
316321Z2-027
Solar/Wind Harmer
0.926
3146396TANGLEW
Solar/Wind Harmer
0.632
3145176PASQUOTANK
Solar/Wind Harmer
-0.021
971445AH1-216 GEN
Solar/Wind Harmer
21.053
315611Z1-036_GEN2
Solar/Wind Harmer
8.332
972265AH1-717 GEN
Adder
23.171
3151201GRAVEL4
Adder
21.721
3151191GRAVEL3
Adder
21.446
3151211GRAVEL5
Adder
21.446
3130156CHOWAN
Solar/Wind Harmer
-0.033
3130156CHOWAN
Solar/Wind Harmer
-0.033
316369SG1_INVT
Solar/Wind Harmer
5.9
315816AE2-034 GEN
Solar/Wind Harmer
2.66
316132AB2-190 GEN1
Solar/Wind Harmer
3.31
3130546PLYMOUTH
Solar/Wind Harmer
-0.032
965291AG1-394 GEN
Solar/Wind Harmer
2.878
315732AD1-074 GEN1
Solar/Wind Harmer
6.549
315733AD1-074 GEN2
Solar/Wind Harmer
6.549
315735AD1-075 GEN1
Solar/Wind Harmer
3.275
946281AF1-292 GEN
Solar/Wind Harmer
0.723
316318V4-068
Solar/Wind Harmer
0.802
3145893MURPHYS
Solar/Wind Harmer
-0.086
3145893MURPHYS
Solar/Wind Harmer
-0.032
3146206CASHIE
Solar/Wind Harmer
-0.032
970601AG2-382 GEN
Solar/Wind Harmer
14.071
316087AB2-174 GEN
Solar/Wind Harmer
4.56
3146043SEABORD
Solar/Wind Harmer
-0.032
3145513AHOSKIE
Solar/Wind Harmer
0.277
961941AG1-037 GEN
Solar/Wind Harmer
0.239
3145513AHOSKIE
Solar/Wind Harmer
-0.032
315607AA1-063A GEN
Solar/Wind Harmer
3.21
3145683EARLEYS
Solar/Wind Harmer
-0.063
3145683EARLEYS
Solar/Wind Harmer
-0.032
3145683EARLEYS
Solar/Wind Harmer
-0.032
315652AC1-086 GEN
Solar/Wind Harmer
35.613
3137643SOCKMAN
Solar/Wind Harmer
-0.126
3145796HORNRTN
Solar/Wind Harmer
-0.099
3145796HORNRTN
Solar/Wind Harmer
-0.012
3146033SCOT NK
Solar/Wind Harmer
-0.122
970831AG2-522 GEN
Solar/Wind Harmer
15.209
957831AF2-077 GEN
Solar/Wind Harmer
0.905
3138283WHITEMARSH
Solar/Wind Harmer
0.047
316005AA1-067
Solar/Wind Harmer
0.599
3145746EVERETS
Solar/Wind Harmer
-0.117
3145746EVERETS
Solar/Wind Harmer
-0.03
3145746EVERETS
Solar/Wind Harmer
-0.03
3145746EVERETS
Solar/Wind Harmer
-0.03
970181AG2-120 GEN
Solar/Wind Harmer
3.889
957861AF2-080 GEN
Solar/Wind Harmer
12.812
971167AH1-042 GEN
Solar/Wind Harmer
28.174
316239AB2-077_GEN
Solar/Wind Harmer
0.879
316238AB2-078_GEN
Solar/Wind Harmer
0.879
316420AA1-050 GEN
Solar/Wind Harmer
3.326
315976AC1-164 GENA
Solar/Wind Harmer
30.748
316169AC1-164_GENC
Solar/Wind Harmer
26.564
315975AC1-164 GENB
Solar/Wind Harmer
0.91
3142433PROV 92
Adder
0.503
3142433PROV 92
Adder
0.503
316319Z2-044 C
Solar/Wind Harmer
1.605
3145573BETHELC
Solar/Wind Harmer
-0.029
3145573BETHELC
Solar/Wind Harmer
-0.029
972205AH1-687 GEN
Adder
7.988
972189AH1-679 GEN
Adder
2.712
972193AH1-681 GEN
Adder
3.018
316164AC1-076 GEN
Solar/Wind Helper
1.525
316411AF1-147_GEN1
Solar/Wind Helper
0.816
316415AF1-147_GEN2
Solar/Wind Helper
0.816
3138216PACIFIC
Solar/Wind Helper
0.04
970119AG2-088 GEN
50/50
49.56
315243AE2-183_GT3
50/50
5.597
3151051BRUNSWICKS1
50/50
9.142
3151021BRUNSWICKG1
50/50
4.405
971451AH1-221 GEN
50/50
13.378
3150981CHESPKA
50/50
4.118
3150851SPRUNCC
50/50
1.485
3152331SURRY 2
50/50
12.49
3143226MDLTHAN
Solar/Wind Harmer
-0.042
940641AE2-051 GEN
Solar/Wind Harmer
37.221
939411AE1-173 GEN
Solar/Wind Harmer
192.62
3143526WINTERP
Solar/Wind Harmer
-0.197
970919AG2-571 GEN
Solar/Wind Harmer
11.445
970087AG2-069 GEN
Solar/Wind Harmer
33.76
316294AC1-161 GEN
Solar/Wind Harmer
11.456
944591AF1-124 GEN
Solar/Wind Harmer
160.67
316375AC2-012 GEN
Solar/Wind Harmer
12.086
316388AE2-253 GEN
Solar/Wind Harmer
2.349
3146456SLIGO L269
Solar/Wind Harmer
-0.035
316246AF1-032 C
Solar/Wind Harmer
0.701
970659AG2-427 GEN
Solar/Wind Harmer
18.316
316381AD1-082 GEN
Solar/Wind Harmer
3.162
970661AG2-428 GEN
Solar/Wind Harmer
36.628
316093AE2-104_GEN
Solar/Wind Harmer
10.019
316072AD1-144
Solar/Wind Harmer
0.693
3146516WINFALL
Solar/Wind Harmer
-0.11
3146516WINFALL
Solar/Wind Harmer
-0.034
3145336SMITFLD
Solar/Wind Harmer
-0.136
957481AF2-042 GEN
Solar/Wind Harmer
105.713
315800Z1-036_GEN1
Solar/Wind Harmer
8.332
3151171GRAVELC
Adder
3.174
3143336POWHATN
Solar/Wind Harmer
3.972
3130156CHOWAN
Solar/Wind Harmer
-0.033
961611AG1-000B GEN
Solar/Wind Harmer
16.45
315671AE2-027_GEN
Solar/Wind Harmer
24.982
971647AH1-324 GEN
Solar/Wind Harmer
16.587
316023GEN1_S
Solar/Wind Harmer
2.232
971069AG2-661 GEN
Solar/Wind Harmer
5.205
3145663CRESWEL
Solar/Wind Harmer
-0.092
971163AH1-040 GEN
Solar/Wind Harmer
30.822
316458AB2-190 GEN2
Solar/Wind Harmer
3.31
315693AD1-088 GEN
Solar/Wind Harmer
16.359
970129AG2-093 GEN
Solar/Wind Harmer
7.456
962491AG1-098 GEN
Solar/Wind Harmer
21.758
3138126ROCKLANDING
Solar/Wind Harmer
0.099
960081AF2-299 GEN
Solar/Wind Harmer
3.629
3145893MURPHYS
Solar/Wind Harmer
-0.128
3145893MURPHYS
Solar/Wind Harmer
0.955
3142543TWELFTH
Solar/Wind Harmer
-0.003
3146206CASHIE
Solar/Wind Harmer
-0.032
971547AH1-271 GEN
Solar/Wind Harmer
8.041
3146173TUNIS
Solar/Wind Harmer
-0.032
3145683EARLEYS
Solar/Wind Harmer
-0.032
316011AB1-132 GEN
Solar/Wind Harmer
6.623
962571AG1-106 GEN
Solar/Wind Harmer
4.551
971795AH1-408 GEN
Solar/Wind Harmer
23.72
3146263WOODLND
Solar/Wind Harmer
-0.032
971317AH1-138 GEN
Solar/Wind Harmer
3.934
316190AA2-174 GEN
Solar/Wind Harmer
0.386
3143096IRON208
Adder
1.169
3147043LAWRENC
Adder
2.523
316336AC2-165 C
Solar/Wind Harmer
5.44
3145823KELFORD
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.102
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145783HORNRTN
Solar/Wind Harmer
-0.031
3145963POPLR C
Solar/Wind Harmer
-0.031
316159AE1-175 C
Solar/Wind Harmer
0.836
944631AF1-128 GEN
Adder
131.354
316174AB2-169 GEN
Solar/Wind Harmer
4.773
315687AD1-152 GEN
Solar/Wind Harmer
3.672
316212AC1-099_GEN
Solar/Wind Harmer
2.649
316129AC1-054 GEN
Solar/Wind Harmer
2.658
971065AG2-659 GEN
Solar/Wind Harmer
15.113
3146293MARTNCO
Solar/Wind Harmer
0.186
315722AD1-056 GEN
Solar/Wind Harmer
3.115
3145746EVERETS
Solar/Wind Harmer
-0.03
3145746EVERETS
Solar/Wind Harmer
-0.03
316494AC1-189 GEN
Solar/Wind Harmer
3.151
316237AB2-079_GEN
Solar/Wind Harmer
0.879
3142433PROV 92
Solar/Wind Harmer
-0.116
3142433PROV 92
Adder
0.503
3142433PROV 92
Adder
0.503
3146233WITAKRS
Solar/Wind Harmer
-0.115
961671AG1-007 GEN
Solar/Wind Harmer
0.366
3146083TARBORO
Solar/Wind Harmer
-0.029
3145493TOT1
Solar/Wind Harmer
0.86
3141843SHACKLE
Adder
1.273
3144293JTRSVLE
Adder
0.792
3150351NORNECKC2
Adder
1.971
972277AH1-723 GEN
Adder
78.716
316045AC1-158 PL2
Solar/Wind Helper
7.153
3147666LOUISA
Solar/Wind Helper
1.265
316192AB2-158 GEN
Solar/Wind Helper
2.08
316254AC1-120 GEN1
Solar/Wind Helper
1.311
316006AB2-029 C
Solar/Wind Helper
0.132
970533AG2-339 GEN
50/50
31.002
970531AG2-338 GEN
50/50
12.401
315242AE2-183_GT2
50/50
5.597
315241AE2-183_GT1
50/50
5.563
972185AH1-677 GEN
50/50
20.179
3151041BRUNSWICKG3
50/50
4.405
972187AH1-678 GEN
50/50
10.108
3150991CHESPKB
50/50
3.455
3150991CHESPKB
50/50
3.372
971223AH1-071 GEN
Solar/Wind Harmer
5.22
3143526WINTERP
Solar/Wind Harmer
-0.197
970933AG2-581 GEN
Solar/Wind Harmer
34.405
3144356SAPONY
Solar/Wind Harmer
1.252
316185AD1-033 GEN
Solar/Wind Harmer
3.69
3142956BIRDNECK
Solar/Wind Harmer
1.875
316316AC1-027 C
Solar/Wind Harmer
1.073
316036AC1-147 C
Solar/Wind Harmer
0.942
3145506HICKORY
Solar/Wind Harmer
-0.139
3145506HICKORY
Solar/Wind Harmer
-0.083
3145506HICKORY
Solar/Wind Harmer
-0.021
316339AD2-160 GEN
Solar/Wind Harmer
2.349
316018AA1-139 ULT2
Solar/Wind Harmer
2.981
316017AA1-139 ULT1
Solar/Wind Harmer
2.816
3137176SLIGO L2192
Solar/Wind Harmer
-0.137
3146456SLIGO L269
Solar/Wind Harmer
4.103
3130086AYDLETT
Solar/Wind Harmer
-0.138
970657AG2-426 GEN
Solar/Wind Harmer
10.774
970657AG2-426 GEN
Solar/Wind Harmer
2.253
3146386ELIZ CT
Solar/Wind Harmer
-0.034
316431W1029_GEN1
Solar/Wind Harmer
6.192
316433W1029_GEN2
Solar/Wind Harmer
6.192
3146516WINFALL
Solar/Wind Harmer
-0.034
3146516WINFALL
Solar/Wind Harmer
-0.034
3146516WINFALL
Solar/Wind Harmer
-0.034
316236AE1-162_GEN
Solar/Wind Harmer
1.027
3146626S HERTFORD
Solar/Wind Harmer
-0.034
3146626S HERTFORD
Solar/Wind Harmer
-0.034
970099AG2-077 GEN
Solar/Wind Harmer
42.285
315742AE1-103 GEN
Solar/Wind Harmer
3.51
3146376EDENTON
Solar/Wind Harmer
0.992
3146376EDENTON
Solar/Wind Harmer
0.992
316240AF1-291 C
Solar/Wind Harmer
1
316033AB2-134 GEN
Solar/Wind Harmer
10.649
315697AD1-025 GEN
Solar/Wind Harmer
6.679
944641AF1-129 GEN
Adder
139.506
316065AD1-022 GEN
Solar/Wind Harmer
16.121
3145893MURPHYS
Solar/Wind Harmer
0.898
3145893MURPHYS
Solar/Wind Harmer
-0.058
3146173TUNIS
Solar/Wind Harmer
-0.032
3146173TUNIS
Solar/Wind Harmer
-0.032
316181AB2-040 GEN
Solar/Wind Harmer
4.441
3142666NORTHAMPTON
Solar/Wind Harmer
-0.032
3142666NORTHAMPTON
Solar/Wind Harmer
-0.032
3142666NORTHAMPTON
Solar/Wind Harmer
-0.032
3142666NORTHAMPTON
Solar/Wind Harmer
-0.019
316426AA2-053 GEN
Solar/Wind Harmer
3.174
3145593CAROLNA
Solar/Wind Harmer
-0.031
3145593CAROLNA
Solar/Wind Harmer
-0.031
966811AG1-552 GEN
Solar/Wind Harmer
3.528
3145593CAROLNA
Solar/Wind Harmer
0.26
3145796HORNRTN
Solar/Wind Harmer
-0.093
3145783HORNRTN
Solar/Wind Harmer
3.7
3145783HORNRTN
Solar/Wind Harmer
2.96
3145783HORNRTN
Solar/Wind Harmer
0.925
3145783HORNRTN
Solar/Wind Harmer
0.37
3142946ENON
Solar/Wind Harmer
-0.003
316274AC1-208 GEN
Solar/Wind Harmer
3.264
3145933PARMELE
Solar/Wind Harmer
-0.06
3145933PARMELE
Solar/Wind Harmer
-0.03
971741AH1-377 GEN
Solar/Wind Harmer
34.86
3142366NRTHEST
Adder
0.864
939181AE1-148 GEN
Solar/Wind Harmer
16.686
3150691DARBY 3
Adder
18.921
3150701DARBY 4
Adder
18.877
3150681DARBY 2
Adder
18.855
3150671DARBY 1
Adder
18.833
313527AB2-043 GEN
Solar/Wind Harmer
4.747
970301AG2-198 GEN
Solar/Wind Harmer
14.587
3145493TOT1
Solar/Wind Harmer
0.448
3145453TOT5
Solar/Wind Harmer
0.269
3145603CNETO
Solar/Wind Harmer
0.179
3144293JTRSVLE
Adder
0.792
3144293JTRSVLE
Adder
0.667
3142296MT RD221
Adder
0.77
3150341NORNECKC1
Adder
2.071
3150341NORNECKC1
Adder
2.054
316447AC1-158 HLD
Solar/Wind Helper
4.918
315651AD1-115 GEN
Solar/Wind Helper
0.954
226929AD2-058 GEN
Solar/Wind Helper
0.092
316075AC2-137 C
Solar/Wind Harmer
0.319
3151031BRUNSWICKG2
50/50
4.405
3151101ELIZAR3
50/50
30.659
3150861SPRUNCD
50/50
1.485
3151161SURRY 1
50/50
11.463
970917AG2-570 GEN
Solar/Wind Harmer
90.418
315773AC2-141 GEN
Solar/Wind Harmer
14.817
944581AF1-123 GEN
Solar/Wind Harmer
160.093
944601AF1-125 GEN
Solar/Wind Harmer
157.595
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146456SLIGO L269
Solar/Wind Harmer
-0.035
971153AH1-033 GEN
Solar/Wind Harmer
4.235
3144536CHRHLND
Solar/Wind Harmer
-0.005
315813AE1-149 C
Solar/Wind Harmer
21.552
970659AG2-427 GEN
Solar/Wind Harmer
3.246
316083AB2-161 GEN
Solar/Wind Harmer
5.596
970661AG2-428 GEN
Solar/Wind Harmer
6.491
316320Y1-086
Solar/Wind Harmer
2.02
316435W1029_GEN3
Solar/Wind Harmer
6.192
3146516WINFALL
Solar/Wind Harmer
-0.034
3145336SMITFLD
Solar/Wind Harmer
-0.013
315839AE2-212 C
Solar/Wind Harmer
1.026
3146626S HERTFORD
Solar/Wind Harmer
-0.034
3145273HOLLAND
Solar/Wind Harmer
-0.025
965281AG1-393 GEN
Solar/Wind Harmer
4.197
3151221GRAVEL6
Adder
21.696
3151171GRAVELC
Adder
4.174
316313AB2-026
Solar/Wind Harmer
0.903
316258AE1-075 C
Solar/Wind Harmer
0.813
316405AF2-144 C
Solar/Wind Harmer
0.857
3143336POWHATN
Solar/Wind Harmer
3.376
3146376EDENTON
Solar/Wind Harmer
-0.033
961611AG1-000B GEN
Solar/Wind Harmer
7.019
316365GEN2_N
Solar/Wind Harmer
2.232
315778AD1-151 GEN
Solar/Wind Harmer
28.5
315614AA2-178 GEN
Solar/Wind Harmer
3.547
970129AG2-093 GEN
Solar/Wind Harmer
18.408
3156081AA2-088 GEN
Solar/Wind Harmer
10.555
971157AH1-035 GEN
Solar/Wind Harmer
4.057
3144216WINCHST
Adder
1.088
970133AG2-095 GEN
Solar/Wind Harmer
3.645
316478AD1-087 GEN
Solar/Wind Harmer
2.805
316486AD2-202 GEN
Solar/Wind Harmer
0.821
315737AD1-076 GEN
Solar/Wind Harmer
6.155
966621AG1-532 GEN
Solar/Wind Harmer
0.655
3150921YORKTN3
Adder
7.214
3145893MURPHYS
Solar/Wind Harmer
0.225
3145893MURPHYS
Solar/Wind Harmer
-0.032
3146206CASHIE
Solar/Wind Harmer
-0.032
957521AF2-046 GEN
Solar/Wind Harmer
25.297
961681AG1-008 GEN
Solar/Wind Harmer
25.297
3146173TUNIS
Solar/Wind Harmer
-0.032
3156021HOLLOMANSOL
Solar/Wind Harmer
4.291
313506AB2-031 GEN
Solar/Wind Harmer
2.559
316463AE2-346 GEN
Solar/Wind Harmer
0.515
316140AB2-099
Solar/Wind Harmer
0.215
962331AG1-082 GEN
Solar/Wind Harmer
3.978
3142666NORTHAMPTON
Solar/Wind Harmer
-0.032
3146263WOODLND
Solar/Wind Harmer
-0.032
3143096IRON208
Adder
1.169
3143096IRON208
Adder
1.146
3147043LAWRENC
Solar/Wind Harmer
-0.019
316317KELFORD C
Solar/Wind Harmer
1.473
3145823KELFORD
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.124
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145963POPLR C
Solar/Wind Harmer
-0.031
316382AG1-145 C
Solar/Wind Harmer
0.939
3142946ENON
Solar/Wind Harmer
-0.01
316210AC1-098 GEN
Solar/Wind Harmer
4.769
3145933PARMELE
Solar/Wind Harmer
-0.03
966801AG1-551 GEN
Solar/Wind Harmer
3.764
315724AD1-057 GEN
Solar/Wind Harmer
1.713
3145746EVERETS
Solar/Wind Harmer
-0.03
3145746EVERETS
Solar/Wind Harmer
-0.03
316327AA2-057 GEN
Solar/Wind Harmer
2.98
970293AG2-193 GEN
Solar/Wind Harmer
3.658
970909AG2-566 GEN
Solar/Wind Harmer
2.77
316131AB2-060 GEN
Solar/Wind Harmer
3.147
3142433PROV 92
Adder
0.503
3142433PROV 92
Adder
0.503
3146233WITAKRS
Solar/Wind Harmer
0.608
3146233WITAKRS
Solar/Wind Harmer
-0.02
3138543CONSLDL
Solar/Wind Harmer
-0.019
3146073TAR RVR
Solar/Wind Harmer
-0.029
3146083TARBORO
Solar/Wind Harmer
-0.029
964241AG1-285 GEN
Solar/Wind Harmer
22.639
3141843SHACKLE
Adder
1.273
3144293JTRSVLE
Adder
0.792
3150351NORNECKC2
Adder
2.004
972255AH1-712 GEN
Adder
67.55
316044AC1-158 PL1
Solar/Wind Helper
2.235
316450AC1-158 RIC
Solar/Wind Helper
0.596
3147666LOUISA
Solar/Wind Helper
0.727
316170AC1-121 GEN2
Solar/Wind Helper
0.437
3141196NOKESVL
Solar/Wind Helper
1.052
3132273ORANGE
Solar/Wind Helper
0.048
227287AC2-120 GEN
Solar/Wind Helper
0.315
226910AB2-157 C
Solar/Wind Helper
0.013
NYPJM->LTFIMP_NY
CLTF
3.61
LGEELTFEXP_LGEE->PJM
CLTF
2.36
WECLTFEXP_WEC->PJM
CLTF
1.198
AG2-052LTFEXP_AG2-052->PJM
LTF
0.064
AH1-155LTFEXP_AH1-155->PJM
LTF
0.097
LAGNLTFEXP_LAGN->PJM
CLTF
12.593
CBM South 2LTFEXP_CBM-S2->PJM
CBM
37.232
TVALTFEXP_TVA->PJM
CLTF
6.338
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.824
CBM South 1LTFEXP_CBM-S1->PJM
CBM
21.839
MECLTFEXP_MEC->PJM
CLTF
6.331
SIGELTFEXP_SIGE->PJM
CLTF
0.193
CPLELTFEXP_CPLE->PJM
CLTF
16.935
CBM West 2LTFEXP_CBM-W2->PJM
CBM
67.417

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:152.97 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:6027.13
MW Contribution:75.54
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
6.58
315244AE2-183_ST
50/50
9.618
963041AG1-153 GEN
50/50
8.863
315779AE2-040
50/50
4.423
3151081ELIZAR1
50/50
29.93
3151091ELIZAR2
50/50
29.41
941591AE2-156 GEN
50/50
27.339
3152611GOSPORTB
50/50
4.153
3152621GOSPORTC
50/50
3.524
3152601GOSPORTA
50/50
3.251
971285AH1-108 GEN
50/50
2.407
972263AH1-716 GEN
50/50
170.499
941031AE2-094 GEN
Solar/Wind Harmer
73.029
944011AF1-069 GEN
Solar/Wind Harmer
22.883
970673AG2-436 GEN
Solar/Wind Harmer
80.276
970673AG2-436 GEN
Solar/Wind Harmer
40.646
316233AE1-074 FULL
Solar/Wind Harmer
1.019
971281AH1-106 GEN
Solar/Wind Harmer
6.156
971283AH1-107 GEN
Solar/Wind Harmer
6.156
971967AH1-528 GEN
Solar/Wind Harmer
70.663
970085AG2-068 GEN
Solar/Wind Harmer
22.364
970581AG2-369 GEN
Solar/Wind Harmer
19.233
316315AB2-025 C
Solar/Wind Harmer
0.96
315814AE2-033 C
Solar/Wind Harmer
33.023
3143316POE
Solar/Wind Harmer
-0.138
957871AF2-081 GEN
Solar/Wind Harmer
17.208
319010AE1-072 C
Solar/Wind Harmer
6.946
3146406KITTY HAWK
Solar/Wind Harmer
0.029
316305AF2-043 C
Solar/Wind Harmer
1.032
315833AF1-017_GEN
Solar/Wind Harmer
6.476
316349AD2-085 GEN
Solar/Wind Harmer
3.033
316311AC2-079 GEN
Solar/Wind Harmer
17.198
313526AB2-022
Solar/Wind Harmer
0.919
315835AF2-110_GEN
Solar/Wind Harmer
4.261
3146486SUNBURY
Solar/Wind Harmer
-0.034
3146486SUNBURY
Solar/Wind Harmer
-0.034
316321Z2-027
Solar/Wind Harmer
0.916
3146396TANGLEW
Solar/Wind Harmer
0.625
3145176PASQUOTANK
Solar/Wind Harmer
-0.021
971445AH1-216 GEN
Solar/Wind Harmer
20.803
315611Z1-036_GEN2
Solar/Wind Harmer
8.244
972265AH1-717 GEN
Adder
22.888
3151201GRAVEL4
Adder
21.456
3151191GRAVEL3
Adder
21.184
3151211GRAVEL5
Adder
21.184
3130156CHOWAN
Solar/Wind Harmer
-0.033
3130156CHOWAN
Solar/Wind Harmer
-0.033
316369SG1_INVT
Solar/Wind Harmer
5.828
315816AE2-034 GEN
Solar/Wind Harmer
2.633
316132AB2-190 GEN1
Solar/Wind Harmer
3.27
3130546PLYMOUTH
Solar/Wind Harmer
-0.032
965291AG1-394 GEN
Solar/Wind Harmer
2.85
315732AD1-074 GEN1
Solar/Wind Harmer
6.483
315733AD1-074 GEN2
Solar/Wind Harmer
6.483
315735AD1-075 GEN1
Solar/Wind Harmer
3.242
946281AF1-292 GEN
Solar/Wind Harmer
0.717
316318V4-068
Solar/Wind Harmer
0.794
3145893MURPHYS
Solar/Wind Harmer
-0.086
3145893MURPHYS
Solar/Wind Harmer
-0.032
3146206CASHIE
Solar/Wind Harmer
-0.032
970601AG2-382 GEN
Solar/Wind Harmer
13.932
316087AB2-174 GEN
Solar/Wind Harmer
4.521
3146043SEABORD
Solar/Wind Harmer
-0.031
3145513AHOSKIE
Solar/Wind Harmer
0.275
961941AG1-037 GEN
Solar/Wind Harmer
0.237
3145513AHOSKIE
Solar/Wind Harmer
-0.031
315607AA1-063A GEN
Solar/Wind Harmer
3.181
3145683EARLEYS
Solar/Wind Harmer
-0.062
3145683EARLEYS
Solar/Wind Harmer
-0.031
3145683EARLEYS
Solar/Wind Harmer
-0.031
315652AC1-086 GEN
Solar/Wind Harmer
35.304
3137643SOCKMAN
Solar/Wind Harmer
-0.124
3145796HORNRTN
Solar/Wind Harmer
-0.098
3145796HORNRTN
Solar/Wind Harmer
-0.012
3146033SCOT NK
Solar/Wind Harmer
-0.121
970831AG2-522 GEN
Solar/Wind Harmer
15.086
957831AF2-077 GEN
Solar/Wind Harmer
0.889
3138283WHITEMARSH
Solar/Wind Harmer
0.046
316005AA1-067
Solar/Wind Harmer
0.594
3145746EVERETS
Solar/Wind Harmer
-0.116
3145746EVERETS
Solar/Wind Harmer
-0.029
3145746EVERETS
Solar/Wind Harmer
-0.029
3145746EVERETS
Solar/Wind Harmer
-0.029
970181AG2-120 GEN
Solar/Wind Harmer
3.854
957861AF2-080 GEN
Solar/Wind Harmer
12.697
316239AB2-077_GEN
Solar/Wind Harmer
0.873
316238AB2-078_GEN
Solar/Wind Harmer
0.873
316420AA1-050 GEN
Solar/Wind Harmer
3.296
316319Z2-044 C
Solar/Wind Harmer
1.592
971167AH1-042 GEN
Solar/Wind Harmer
27.693
3145573BETHELC
Solar/Wind Harmer
-0.029
3145573BETHELC
Solar/Wind Harmer
-0.029
315976AC1-164 GENA
Solar/Wind Harmer
30.185
316169AC1-164_GENC
Solar/Wind Harmer
26.077
315975AC1-164 GENB
Solar/Wind Harmer
0.893
3142433PROV 92
Adder
0.494
3142433PROV 92
Adder
0.494
972205AH1-687 GEN
Adder
7.923
972189AH1-679 GEN
Adder
2.542
972193AH1-681 GEN
Adder
2.896
316164AC1-076 GEN
Solar/Wind Helper
1.492
316411AF1-147_GEN1
Solar/Wind Helper
0.805
316415AF1-147_GEN2
Solar/Wind Helper
0.805
3138216PACIFIC
Solar/Wind Helper
0.039
970533AG2-339 GEN
50/50
30.814
970531AG2-338 GEN
50/50
12.326
315242AE2-183_GT2
50/50
5.563
315241AE2-183_GT1
50/50
5.529
972185AH1-677 GEN
50/50
20.054
3151041BRUNSWICKG3
50/50
4.377
972187AH1-678 GEN
50/50
10.045
3150991CHESPKB
50/50
3.416
3150991CHESPKB
50/50
3.334
971223AH1-071 GEN
Solar/Wind Harmer
5.198
3143526WINTERP
Solar/Wind Harmer
-0.196
970933AG2-581 GEN
Solar/Wind Harmer
34.189
3144356SAPONY
Solar/Wind Harmer
1.242
316185AD1-033 GEN
Solar/Wind Harmer
3.648
3142956BIRDNECK
Solar/Wind Harmer
1.854
316316AC1-027 C
Solar/Wind Harmer
1.061
316036AC1-147 C
Solar/Wind Harmer
0.932
3145506HICKORY
Solar/Wind Harmer
-0.137
3145506HICKORY
Solar/Wind Harmer
-0.083
3145506HICKORY
Solar/Wind Harmer
-0.02
316339AD2-160 GEN
Solar/Wind Harmer
2.323
316018AA1-139 ULT2
Solar/Wind Harmer
2.948
316017AA1-139 ULT1
Solar/Wind Harmer
2.785
3137176SLIGO L2192
Solar/Wind Harmer
-0.136
3146456SLIGO L269
Solar/Wind Harmer
4.058
3130086AYDLETT
Solar/Wind Harmer
-0.137
970657AG2-426 GEN
Solar/Wind Harmer
10.662
970657AG2-426 GEN
Solar/Wind Harmer
2.23
3146386ELIZ CT
Solar/Wind Harmer
-0.034
316431W1029_GEN1
Solar/Wind Harmer
6.125
316433W1029_GEN2
Solar/Wind Harmer
6.125
3146516WINFALL
Solar/Wind Harmer
-0.034
3146516WINFALL
Solar/Wind Harmer
-0.034
3146516WINFALL
Solar/Wind Harmer
-0.034
316236AE1-162_GEN
Solar/Wind Harmer
1.015
970099AG2-077 GEN
Solar/Wind Harmer
42.007
3146626S HERTFORD
Solar/Wind Harmer
-0.033
3146626S HERTFORD
Solar/Wind Harmer
-0.033
315742AE1-103 GEN
Solar/Wind Harmer
3.474
3146376EDENTON
Solar/Wind Harmer
0.981
3146376EDENTON
Solar/Wind Harmer
0.981
316240AF1-291 C
Solar/Wind Harmer
0.989
316033AB2-134 GEN
Solar/Wind Harmer
10.519
315697AD1-025 GEN
Solar/Wind Harmer
6.597
944641AF1-129 GEN
Adder
138.008
316065AD1-022 GEN
Solar/Wind Harmer
15.96
3145893MURPHYS
Solar/Wind Harmer
0.889
3145893MURPHYS
Solar/Wind Harmer
-0.057
3146173TUNIS
Solar/Wind Harmer
-0.032
3146173TUNIS
Solar/Wind Harmer
-0.032
316181AB2-040 GEN
Solar/Wind Harmer
4.403
3142666NORTHAMPTON
Solar/Wind Harmer
-0.031
3142666NORTHAMPTON
Solar/Wind Harmer
-0.031
3142666NORTHAMPTON
Solar/Wind Harmer
-0.031
3142666NORTHAMPTON
Solar/Wind Harmer
-0.019
316426AA2-053 GEN
Solar/Wind Harmer
3.146
3145593CAROLNA
Solar/Wind Harmer
-0.031
3145593CAROLNA
Solar/Wind Harmer
-0.031
966811AG1-552 GEN
Solar/Wind Harmer
3.497
3145593CAROLNA
Solar/Wind Harmer
0.258
3145796HORNRTN
Solar/Wind Harmer
-0.092
3145783HORNRTN
Solar/Wind Harmer
3.668
3145783HORNRTN
Solar/Wind Harmer
2.934
3145783HORNRTN
Solar/Wind Harmer
0.917
3145783HORNRTN
Solar/Wind Harmer
0.367
316274AC1-208 GEN
Solar/Wind Harmer
3.236
3142946ENON
Solar/Wind Harmer
-0.003
3145933PARMELE
Solar/Wind Harmer
-0.059
3145933PARMELE
Solar/Wind Harmer
-0.03
971741AH1-377 GEN
Solar/Wind Harmer
34.617
939181AE1-148 GEN
Solar/Wind Harmer
16.559
3142366NRTHEST
Adder
0.852
3150691DARBY 3
Adder
18.657
3150701DARBY 4
Adder
18.614
3150681DARBY 2
Adder
18.592
3150671DARBY 1
Adder
18.57
313527AB2-043 GEN
Solar/Wind Harmer
4.711
970301AG2-198 GEN
Solar/Wind Harmer
14.484
3145493TOT1
Solar/Wind Harmer
0.444
3145453TOT5
Solar/Wind Harmer
0.267
3145603CNETO
Solar/Wind Harmer
0.178
3144293JTRSVLE
Adder
0.786
3144293JTRSVLE
Adder
0.662
3142296MT RD221
Adder
0.76
3150341NORNECKC1
Adder
2.003
3150341NORNECKC1
Adder
1.987
316447AC1-158 HLD
Solar/Wind Helper
4.827
315651AD1-115 GEN
Solar/Wind Helper
0.935
226929AD2-058 GEN
Solar/Wind Helper
0.091
316075AC2-137 C
Solar/Wind Harmer
0.313
970119AG2-088 GEN
50/50
49.347
315243AE2-183_GT3
50/50
5.563
3151051BRUNSWICKS1
50/50
9.085
3151021BRUNSWICKG1
50/50
4.377
971451AH1-221 GEN
50/50
13.295
3150981CHESPKA
50/50
4.072
3150851SPRUNCC
50/50
1.471
3152331SURRY 2
50/50
12.317
3143226MDLTHAN
Solar/Wind Harmer
-0.041
940641AE2-051 GEN
Solar/Wind Harmer
36.965
939411AE1-173 GEN
Solar/Wind Harmer
191.106
3143526WINTERP
Solar/Wind Harmer
-0.196
970919AG2-571 GEN
Solar/Wind Harmer
11.373
970087AG2-069 GEN
Solar/Wind Harmer
33.546
316294AC1-161 GEN
Solar/Wind Harmer
11.322
944591AF1-124 GEN
Solar/Wind Harmer
158.875
316375AC2-012 GEN
Solar/Wind Harmer
11.949
316388AE2-253 GEN
Solar/Wind Harmer
2.323
3146456SLIGO L269
Solar/Wind Harmer
-0.034
316246AF1-032 C
Solar/Wind Harmer
0.693
970659AG2-427 GEN
Solar/Wind Harmer
18.128
316381AD1-082 GEN
Solar/Wind Harmer
3.129
970661AG2-428 GEN
Solar/Wind Harmer
36.248
316093AE2-104_GEN
Solar/Wind Harmer
9.91
316072AD1-144
Solar/Wind Harmer
0.685
3146516WINFALL
Solar/Wind Harmer
-0.109
3146516WINFALL
Solar/Wind Harmer
-0.034
3145336SMITFLD
Solar/Wind Harmer
-0.134
957481AF2-042 GEN
Solar/Wind Harmer
105.016
315800Z1-036_GEN1
Solar/Wind Harmer
8.244
3143336POWHATN
Solar/Wind Harmer
3.951
3151171GRAVELC
Adder
3.136
3130156CHOWAN
Solar/Wind Harmer
-0.033
315671AE2-027_GEN
Solar/Wind Harmer
24.714
961611AG1-000B GEN
Solar/Wind Harmer
16.249
316023GEN1_S
Solar/Wind Harmer
2.214
971647AH1-324 GEN
Solar/Wind Harmer
16.385
3145663CRESWEL
Solar/Wind Harmer
-0.091
971163AH1-040 GEN
Solar/Wind Harmer
30.505
315693AD1-088 GEN
Solar/Wind Harmer
16.249
971069AG2-661 GEN
Solar/Wind Harmer
5.142
316458AB2-190 GEN2
Solar/Wind Harmer
3.27
962491AG1-098 GEN
Solar/Wind Harmer
21.612
970129AG2-093 GEN
Solar/Wind Harmer
7.365
960081AF2-299 GEN
Solar/Wind Harmer
3.599
3138126ROCKLANDING
Solar/Wind Harmer
0.098
3145893MURPHYS
Solar/Wind Harmer
-0.127
3145893MURPHYS
Solar/Wind Harmer
0.946
3146206CASHIE
Solar/Wind Harmer
-0.032
971547AH1-271 GEN
Solar/Wind Harmer
7.961
3142543TWELFTH
Solar/Wind Harmer
-0.003
3146173TUNIS
Solar/Wind Harmer
-0.032
3145683EARLEYS
Solar/Wind Harmer
-0.031
316011AB1-132 GEN
Solar/Wind Harmer
6.566
962571AG1-106 GEN
Solar/Wind Harmer
4.511
971795AH1-408 GEN
Solar/Wind Harmer
23.527
3151031BRUNSWICKG2
50/50
4.377
3151101ELIZAR3
50/50
30.313
3150861SPRUNCD
50/50
1.471
3151161SURRY 1
50/50
11.323
970917AG2-570 GEN
Solar/Wind Harmer
89.846
315773AC2-141 GEN
Solar/Wind Harmer
14.644
944581AF1-123 GEN
Solar/Wind Harmer
158.305
944601AF1-125 GEN
Solar/Wind Harmer
155.834
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146456SLIGO L269
Solar/Wind Harmer
-0.034
971153AH1-033 GEN
Solar/Wind Harmer
4.188
3144536CHRHLND
Solar/Wind Harmer
-0.005
315813AE1-149 C
Solar/Wind Harmer
21.335
970659AG2-427 GEN
Solar/Wind Harmer
3.213
316083AB2-161 GEN
Solar/Wind Harmer
5.538
970661AG2-428 GEN
Solar/Wind Harmer
6.424
316320Y1-086
Solar/Wind Harmer
1.998
316435W1029_GEN3
Solar/Wind Harmer
6.125
3146516WINFALL
Solar/Wind Harmer
-0.034
315839AE2-212 C
Solar/Wind Harmer
1.016
3145336SMITFLD
Solar/Wind Harmer
-0.013
3146626S HERTFORD
Solar/Wind Harmer
-0.033
3145273HOLLAND
Solar/Wind Harmer
-0.025
316313AB2-026
Solar/Wind Harmer
0.898
316258AE1-075 C
Solar/Wind Harmer
0.808
316405AF2-144 C
Solar/Wind Harmer
0.853
3143336POWHATN
Solar/Wind Harmer
3.359
965281AG1-393 GEN
Solar/Wind Harmer
4.153
3151221GRAVEL6
Adder
21.431
3151171GRAVELC
Adder
4.123
3146376EDENTON
Solar/Wind Harmer
-0.033
961611AG1-000B GEN
Solar/Wind Harmer
6.933
316365GEN2_N
Solar/Wind Harmer
2.214
315614AA2-178 GEN
Solar/Wind Harmer
3.511
315778AD1-151 GEN
Solar/Wind Harmer
28.152
970129AG2-093 GEN
Solar/Wind Harmer
18.183
3156081AA2-088 GEN
Solar/Wind Harmer
10.453
316478AD1-087 GEN
Solar/Wind Harmer
2.786
316486AD2-202 GEN
Solar/Wind Harmer
0.816
971157AH1-035 GEN
Solar/Wind Harmer
4.016
315737AD1-076 GEN
Solar/Wind Harmer
6.093
970133AG2-095 GEN
Solar/Wind Harmer
3.601
966621AG1-532 GEN
Solar/Wind Harmer
0.649
3144216WINCHST
Adder
1.073
3145893MURPHYS
Solar/Wind Harmer
0.222
3145893MURPHYS
Solar/Wind Harmer
-0.032
3146206CASHIE
Solar/Wind Harmer
-0.032
957521AF2-046 GEN
Solar/Wind Harmer
25.055
961681AG1-008 GEN
Solar/Wind Harmer
25.055
3150921YORKTN3
Adder
7.106
3146173TUNIS
Solar/Wind Harmer
-0.032
313506AB2-031 GEN
Solar/Wind Harmer
2.537
3156021HOLLOMANSOL
Solar/Wind Harmer
4.249
316463AE2-346 GEN
Solar/Wind Harmer
0.51
316140AB2-099
Solar/Wind Harmer
0.212
962331AG1-082 GEN
Solar/Wind Harmer
3.94
3142666NORTHAMPTON
Solar/Wind Harmer
-0.031
3146263WOODLND
Solar/Wind Harmer
-0.031
3147043LAWRENC
Solar/Wind Harmer
-0.018
3143096IRON208
Adder
1.154
3143096IRON208
Adder
1.131
316317KELFORD C
Solar/Wind Harmer
1.459
3145823KELFORD
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.123
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145963POPLR C
Solar/Wind Harmer
-0.031
316382AG1-145 C
Solar/Wind Harmer
0.924
316210AC1-098 GEN
Solar/Wind Harmer
4.726
3142946ENON
Solar/Wind Harmer
-0.01
3145933PARMELE
Solar/Wind Harmer
-0.03
966801AG1-551 GEN
Solar/Wind Harmer
3.729
315724AD1-057 GEN
Solar/Wind Harmer
1.698
3145746EVERETS
Solar/Wind Harmer
-0.029
3145746EVERETS
Solar/Wind Harmer
-0.029
316327AA2-057 GEN
Solar/Wind Harmer
2.954
970909AG2-566 GEN
Solar/Wind Harmer
2.75
316131AB2-060 GEN
Solar/Wind Harmer
3.123
970293AG2-193 GEN
Solar/Wind Harmer
3.602
3146233WITAKRS
Solar/Wind Harmer
0.603
3146233WITAKRS
Solar/Wind Harmer
-0.019
3138543CONSLDL
Solar/Wind Harmer
-0.019
964241AG1-285 GEN
Solar/Wind Harmer
22.468
3146073TAR RVR
Solar/Wind Harmer
-0.029
3146083TARBORO
Solar/Wind Harmer
-0.029
3142433PROV 92
Adder
0.494
3142433PROV 92
Adder
0.494
3144293JTRSVLE
Adder
0.786
3141843SHACKLE
Adder
1.247
3150351NORNECKC2
Adder
1.939
972255AH1-712 GEN
Adder
64.825
316044AC1-158 PL1
Solar/Wind Helper
2.193
316450AC1-158 RIC
Solar/Wind Helper
0.585
3147666LOUISA
Solar/Wind Helper
0.714
316170AC1-121 GEN2
Solar/Wind Helper
0.428
3141196NOKESVL
Solar/Wind Helper
1.035
3132273ORANGE
Solar/Wind Helper
0.047
227287AC2-120 GEN
Solar/Wind Helper
0.311
226910AB2-157 C
Solar/Wind Helper
0.013
3146263WOODLND
Solar/Wind Harmer
-0.031
316190AA2-174 GEN
Solar/Wind Harmer
0.382
316336AC2-165 C
Solar/Wind Harmer
5.409
3147043LAWRENC
Adder
2.503
971317AH1-138 GEN
Solar/Wind Harmer
3.871
3143096IRON208
Adder
1.154
3145823KELFORD
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.102
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145783HORNRTN
Solar/Wind Harmer
-0.031
3145963POPLR C
Solar/Wind Harmer
-0.031
316159AE1-175 C
Solar/Wind Harmer
0.823
316174AB2-169 GEN
Solar/Wind Harmer
4.727
944631AF1-128 GEN
Adder
129.496
315687AD1-152 GEN
Solar/Wind Harmer
3.646
316212AC1-099_GEN
Solar/Wind Harmer
2.626
316129AC1-054 GEN
Solar/Wind Harmer
2.637
971065AG2-659 GEN
Solar/Wind Harmer
14.993
3146293MARTNCO
Solar/Wind Harmer
0.185
315722AD1-056 GEN
Solar/Wind Harmer
3.088
3145746EVERETS
Solar/Wind Harmer
-0.029
3145746EVERETS
Solar/Wind Harmer
-0.029
316494AC1-189 GEN
Solar/Wind Harmer
3.123
316237AB2-079_GEN
Solar/Wind Harmer
0.873
3146233WITAKRS
Solar/Wind Harmer
-0.114
961671AG1-007 GEN
Solar/Wind Harmer
0.363
3146083TARBORO
Solar/Wind Harmer
-0.029
3145493TOT1
Solar/Wind Harmer
0.852
3142433PROV 92
Solar/Wind Harmer
-0.114
3142433PROV 92
Adder
0.494
3142433PROV 92
Adder
0.494
3144293JTRSVLE
Adder
0.786
3141843SHACKLE
Adder
1.247
3150351NORNECKC2
Adder
1.907
972277AH1-723 GEN
Adder
75.541
316045AC1-158 PL2
Solar/Wind Helper
7.02
3147666LOUISA
Solar/Wind Helper
1.242
316192AB2-158 GEN
Solar/Wind Helper
2.041
316254AC1-120 GEN1
Solar/Wind Helper
1.285
316006AB2-029 C
Solar/Wind Helper
0.129
NYPJM->LTFIMP_NY
CLTF
3.562
LGEELTFEXP_LGEE->PJM
CLTF
2.331
WECLTFEXP_WEC->PJM
CLTF
1.184
AG2-052LTFEXP_AG2-052->PJM
LTF
0.064
AH1-155LTFEXP_AH1-155->PJM
LTF
0.096
LAGNLTFEXP_LAGN->PJM
CLTF
12.464
CBM South 2LTFEXP_CBM-S2->PJM
CBM
36.906
TVALTFEXP_TVA->PJM
CLTF
6.273
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.329
CBM South 1LTFEXP_CBM-S1->PJM
CBM
21.608
MECLTFEXP_MEC->PJM
CLTF
6.26
SIGELTFEXP_SIGE->PJM
CLTF
0.19
CPLELTFEXP_CPLE->PJM
CLTF
16.795
CBM West 2LTFEXP_CBM-W2->PJM
CBM
66.696

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 574T575_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 574T575_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.12 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:5205.6
MW Contribution:69.84
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
5.96
315244AE2-183_ST
50/50
8.724
963041AG1-153 GEN
50/50
8.039
315779AE2-040
50/50
4.026
3151081ELIZAR1
50/50
27.372
3151091ELIZAR2
50/50
26.896
941591AE2-156 GEN
50/50
25.004
3152611GOSPORTB
50/50
3.798
3152621GOSPORTC
50/50
3.223
3152601GOSPORTA
50/50
2.973
971285AH1-108 GEN
50/50
2.203
972263AH1-716 GEN
50/50
156.512
941031AE2-094 GEN
Solar/Wind Harmer
66.256
944011AF1-069 GEN
Solar/Wind Harmer
20.76
970673AG2-436 GEN
Solar/Wind Harmer
72.821
970673AG2-436 GEN
Solar/Wind Harmer
36.871
316233AE1-074 FULL
Solar/Wind Harmer
0.927
971281AH1-106 GEN
Solar/Wind Harmer
5.6
971283AH1-107 GEN
Solar/Wind Harmer
5.6
971967AH1-528 GEN
Solar/Wind Harmer
64.075
970085AG2-068 GEN
Solar/Wind Harmer
20.283
970581AG2-369 GEN
Solar/Wind Harmer
17.443
316315AB2-025 C
Solar/Wind Harmer
0.874
315814AE2-033 C
Solar/Wind Harmer
30.059
3143316POE
Solar/Wind Harmer
-0.126
957871AF2-081 GEN
Solar/Wind Harmer
15.731
319010AE1-072 C
Solar/Wind Harmer
6.35
3146406KITTY HAWK
Solar/Wind Harmer
0.026
316305AF2-043 C
Solar/Wind Harmer
0.944
315833AF1-017_GEN
Solar/Wind Harmer
5.92
316349AD2-085 GEN
Solar/Wind Harmer
2.772
316311AC2-079 GEN
Solar/Wind Harmer
15.721
313526AB2-022
Solar/Wind Harmer
0.84
315835AF2-110_GEN
Solar/Wind Harmer
3.894
3146486SUNBURY
Solar/Wind Harmer
-0.031
3146486SUNBURY
Solar/Wind Harmer
-0.031
316321Z2-027
Solar/Wind Harmer
0.837
3146396TANGLEW
Solar/Wind Harmer
0.571
3145176PASQUOTANK
Solar/Wind Harmer
-0.019
971445AH1-216 GEN
Solar/Wind Harmer
19.056
315611Z1-036_GEN2
Solar/Wind Harmer
7.529
972265AH1-717 GEN
Adder
20.984
3151201GRAVEL4
Adder
19.671
3151191GRAVEL3
Adder
19.422
3151211GRAVEL5
Adder
19.422
3130156CHOWAN
Solar/Wind Harmer
-0.03
3130156CHOWAN
Solar/Wind Harmer
-0.03
316369SG1_INVT
Solar/Wind Harmer
5.347
315816AE2-034 GEN
Solar/Wind Harmer
2.403
316132AB2-190 GEN1
Solar/Wind Harmer
3.001
3130546PLYMOUTH
Solar/Wind Harmer
-0.029
965291AG1-394 GEN
Solar/Wind Harmer
2.597
315732AD1-074 GEN1
Solar/Wind Harmer
5.913
315733AD1-074 GEN2
Solar/Wind Harmer
5.913
315735AD1-075 GEN1
Solar/Wind Harmer
2.957
946281AF1-292 GEN
Solar/Wind Harmer
0.651
316318V4-068
Solar/Wind Harmer
0.724
3145893MURPHYS
Solar/Wind Harmer
-0.078
3145893MURPHYS
Solar/Wind Harmer
-0.029
3146206CASHIE
Solar/Wind Harmer
-0.029
970601AG2-382 GEN
Solar/Wind Harmer
12.703
316087AB2-174 GEN
Solar/Wind Harmer
4.11
3146043SEABORD
Solar/Wind Harmer
-0.029
3145513AHOSKIE
Solar/Wind Harmer
0.25
961941AG1-037 GEN
Solar/Wind Harmer
0.216
3145513AHOSKIE
Solar/Wind Harmer
-0.029
315607AA1-063A GEN
Solar/Wind Harmer
2.895
3145683EARLEYS
Solar/Wind Harmer
-0.057
3145683EARLEYS
Solar/Wind Harmer
-0.029
3145683EARLEYS
Solar/Wind Harmer
-0.029
315652AC1-086 GEN
Solar/Wind Harmer
32.119
3137643SOCKMAN
Solar/Wind Harmer
-0.113
3145796HORNRTN
Solar/Wind Harmer
-0.09
3145796HORNRTN
Solar/Wind Harmer
-0.011
3146033SCOT NK
Solar/Wind Harmer
-0.11
957831AF2-077 GEN
Solar/Wind Harmer
0.824
3138283WHITEMARSH
Solar/Wind Harmer
0.042
970831AG2-522 GEN
Solar/Wind Harmer
13.68
316005AA1-067
Solar/Wind Harmer
0.541
3145746EVERETS
Solar/Wind Harmer
-0.106
3145746EVERETS
Solar/Wind Harmer
-0.027
3151031BRUNSWICKG2
50/50
3.97
3151101ELIZAR3
50/50
27.722
3150861SPRUNCD
50/50
1.346
3151161SURRY 1
50/50
10.381
970917AG2-570 GEN
Solar/Wind Harmer
81.486
315773AC2-141 GEN
Solar/Wind Harmer
13.395
944581AF1-123 GEN
Solar/Wind Harmer
144.734
944601AF1-125 GEN
Solar/Wind Harmer
142.475
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146456SLIGO L269
Solar/Wind Harmer
-0.031
971153AH1-033 GEN
Solar/Wind Harmer
3.829
3144536CHRHLND
Solar/Wind Harmer
-0.005
315813AE1-149 C
Solar/Wind Harmer
19.509
970659AG2-427 GEN
Solar/Wind Harmer
2.937
316083AB2-161 GEN
Solar/Wind Harmer
5.063
970661AG2-428 GEN
Solar/Wind Harmer
5.873
316320Y1-086
Solar/Wind Harmer
1.826
316435W1029_GEN3
Solar/Wind Harmer
5.597
315839AE2-212 C
Solar/Wind Harmer
0.929
3145336SMITFLD
Solar/Wind Harmer
-0.012
3146516WINFALL
Solar/Wind Harmer
-0.031
3146626S HERTFORD
Solar/Wind Harmer
-0.031
3145273HOLLAND
Solar/Wind Harmer
-0.023
965281AG1-393 GEN
Solar/Wind Harmer
3.804
3151221GRAVEL6
Adder
19.649
3151171GRAVELC
Adder
3.78
3146376EDENTON
Solar/Wind Harmer
-0.03
961611AG1-000B GEN
Solar/Wind Harmer
6.358
316365GEN2_N
Solar/Wind Harmer
2.014
316313AB2-026
Solar/Wind Harmer
0.805
316258AE1-075 C
Solar/Wind Harmer
0.725
316405AF2-144 C
Solar/Wind Harmer
0.765
3143336POWHATN
Solar/Wind Harmer
3.012
315778AD1-151 GEN
Solar/Wind Harmer
25.835
315614AA2-178 GEN
Solar/Wind Harmer
3.204
970129AG2-093 GEN
Solar/Wind Harmer
16.692
3144216WINCHST
Adder
0.987
970133AG2-095 GEN
Solar/Wind Harmer
3.307
3156081AA2-088 GEN
Solar/Wind Harmer
9.526
971157AH1-035 GEN
Solar/Wind Harmer
3.664
3150921YORKTN3
Adder
6.541
315737AD1-076 GEN
Solar/Wind Harmer
5.557
316478AD1-087 GEN
Solar/Wind Harmer
2.52
316486AD2-202 GEN
Solar/Wind Harmer
0.738
966621AG1-532 GEN
Solar/Wind Harmer
0.59
3145893MURPHYS
Solar/Wind Harmer
0.203
3145893MURPHYS
Solar/Wind Harmer
-0.029
3146206CASHIE
Solar/Wind Harmer
-0.029
957521AF2-046 GEN
Solar/Wind Harmer
22.828
961681AG1-008 GEN
Solar/Wind Harmer
22.828
3146173TUNIS
Solar/Wind Harmer
-0.029
3156021HOLLOMANSOL
Solar/Wind Harmer
3.873
316463AE2-346 GEN
Solar/Wind Harmer
0.465
316140AB2-099
Solar/Wind Harmer
0.194
962331AG1-082 GEN
Solar/Wind Harmer
3.59
313506AB2-031 GEN
Solar/Wind Harmer
2.306
3142666NORTHAMPTON
Solar/Wind Harmer
-0.028
3146263WOODLND
Solar/Wind Harmer
-0.028
3143096IRON208
Adder
1.062
3143096IRON208
Adder
1.041
316382AG1-145 C
Solar/Wind Harmer
0.853
3147043LAWRENC
Solar/Wind Harmer
-0.017
316317KELFORD C
Solar/Wind Harmer
1.328
3145823KELFORD
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.112
3145796HORNRTN
Solar/Wind Harmer
-0.028
3145963POPLR C
Solar/Wind Harmer
-0.028
3142946ENON
Solar/Wind Harmer
-0.009
316210AC1-098 GEN
Solar/Wind Harmer
4.299
3145933PARMELE
Solar/Wind Harmer
-0.027
966801AG1-551 GEN
Solar/Wind Harmer
3.395
315724AD1-057 GEN
Solar/Wind Harmer
1.544
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
970293AG2-193 GEN
Solar/Wind Harmer
3.331
316327AA2-057 GEN
Solar/Wind Harmer
2.686
3142433PROV 92
Adder
0.458
3142433PROV 92
Adder
0.458
3146233WITAKRS
Solar/Wind Harmer
0.548
3146233WITAKRS
Solar/Wind Harmer
-0.018
3138543CONSLDL
Solar/Wind Harmer
-0.017
316131AB2-060 GEN
Solar/Wind Harmer
2.82
3146073TAR RVR
Solar/Wind Harmer
-0.026
3146083TARBORO
Solar/Wind Harmer
-0.026
970909AG2-566 GEN
Solar/Wind Harmer
2.466
3141843SHACKLE
Adder
1.162
3144293JTRSVLE
Adder
0.705
3150351NORNECKC2
Adder
1.858
972255AH1-712 GEN
Adder
59.932
316044AC1-158 PL1
Solar/Wind Helper
2.745
316450AC1-158 RIC
Solar/Wind Helper
0.732
3147666LOUISA
Solar/Wind Helper
0.987
316170AC1-121 GEN2
Solar/Wind Helper
0.472
3132273ORANGE
Solar/Wind Helper
0.057
3141196NOKESVL
Solar/Wind Helper
0.931
964241AG1-285 GEN
Solar/Wind Harmer
19.851
970119AG2-088 GEN
50/50
44.697
315243AE2-183_GT3
50/50
5.046
3151051BRUNSWICKS1
50/50
8.24
3151021BRUNSWICKG1
50/50
3.97
971451AH1-221 GEN
50/50
12.059
3150981CHESPKA
50/50
3.724
3150851SPRUNCC
50/50
1.346
3152331SURRY 2
50/50
11.301
3143226MDLTHAN
Solar/Wind Harmer
-0.038
940641AE2-051 GEN
Solar/Wind Harmer
33.588
939411AE1-173 GEN
Solar/Wind Harmer
173.894
3143526WINTERP
Solar/Wind Harmer
-0.178
970919AG2-571 GEN
Solar/Wind Harmer
10.315
970087AG2-069 GEN
Solar/Wind Harmer
30.424
316294AC1-161 GEN
Solar/Wind Harmer
10.357
944591AF1-124 GEN
Solar/Wind Harmer
145.255
316375AC2-012 GEN
Solar/Wind Harmer
10.929
316388AE2-253 GEN
Solar/Wind Harmer
2.123
3146456SLIGO L269
Solar/Wind Harmer
-0.031
316246AF1-032 C
Solar/Wind Harmer
0.634
970659AG2-427 GEN
Solar/Wind Harmer
16.575
316381AD1-082 GEN
Solar/Wind Harmer
2.861
970661AG2-428 GEN
Solar/Wind Harmer
33.139
316093AE2-104_GEN
Solar/Wind Harmer
9.058
316072AD1-144
Solar/Wind Harmer
0.627
3145336SMITFLD
Solar/Wind Harmer
-0.123
3146516WINFALL
Solar/Wind Harmer
-0.099
3146516WINFALL
Solar/Wind Harmer
-0.031
315800Z1-036_GEN1
Solar/Wind Harmer
7.529
957481AF2-042 GEN
Solar/Wind Harmer
95.029
3151171GRAVELC
Adder
2.875
3130156CHOWAN
Solar/Wind Harmer
-0.03
315671AE2-027_GEN
Solar/Wind Harmer
22.65
961611AG1-000B GEN
Solar/Wind Harmer
14.902
971647AH1-324 GEN
Solar/Wind Harmer
15.03
316023GEN1_S
Solar/Wind Harmer
2.014
3143336POWHATN
Solar/Wind Harmer
3.544
971069AG2-661 GEN
Solar/Wind Harmer
4.719
3145663CRESWEL
Solar/Wind Harmer
-0.083
971163AH1-040 GEN
Solar/Wind Harmer
27.837
316458AB2-190 GEN2
Solar/Wind Harmer
3.001
970129AG2-093 GEN
Solar/Wind Harmer
6.761
315693AD1-088 GEN
Solar/Wind Harmer
14.68
3138126ROCKLANDING
Solar/Wind Harmer
0.09
3142543TWELFTH
Solar/Wind Harmer
-0.003
962491AG1-098 GEN
Solar/Wind Harmer
19.518
960081AF2-299 GEN
Solar/Wind Harmer
3.271
3145893MURPHYS
Solar/Wind Harmer
-0.116
3145893MURPHYS
Solar/Wind Harmer
0.862
3146206CASHIE
Solar/Wind Harmer
-0.029
971547AH1-271 GEN
Solar/Wind Harmer
7.259
3146173TUNIS
Solar/Wind Harmer
-0.029
3145683EARLEYS
Solar/Wind Harmer
-0.029
971317AH1-138 GEN
Solar/Wind Harmer
3.571
316011AB1-132 GEN
Solar/Wind Harmer
5.973
962571AG1-106 GEN
Solar/Wind Harmer
4.104
3146263WOODLND
Solar/Wind Harmer
-0.028
3143096IRON208
Adder
1.062
971795AH1-408 GEN
Solar/Wind Harmer
21.355
316190AA2-174 GEN
Solar/Wind Harmer
0.348
316159AE1-175 C
Solar/Wind Harmer
0.759
3147043LAWRENC
Adder
2.27
3145823KELFORD
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.092
3145796HORNRTN
Solar/Wind Harmer
-0.028
944631AF1-128 GEN
Adder
119.343
3145963POPLR C
Solar/Wind Harmer
-0.028
3145783HORNRTN
Solar/Wind Harmer
-0.028
316174AB2-169 GEN
Solar/Wind Harmer
4.307
316336AC2-165 C
Solar/Wind Harmer
4.835
316212AC1-099_GEN
Solar/Wind Harmer
2.388
315687AD1-152 GEN
Solar/Wind Harmer
3.298
316129AC1-054 GEN
Solar/Wind Harmer
2.39
971065AG2-659 GEN
Solar/Wind Harmer
13.588
3146293MARTNCO
Solar/Wind Harmer
0.168
315722AD1-056 GEN
Solar/Wind Harmer
2.807
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
3142433PROV 92
Solar/Wind Harmer
-0.105
3142433PROV 92
Adder
0.458
3142433PROV 92
Adder
0.458
316494AC1-189 GEN
Solar/Wind Harmer
2.84
3146233WITAKRS
Solar/Wind Harmer
-0.104
316237AB2-079_GEN
Solar/Wind Harmer
0.788
961671AG1-007 GEN
Solar/Wind Harmer
0.33
3146083TARBORO
Solar/Wind Harmer
-0.026
3145493TOT1
Solar/Wind Harmer
0.775
3141843SHACKLE
Adder
1.162
3144293JTRSVLE
Adder
0.705
3150351NORNECKC2
Adder
1.828
972277AH1-723 GEN
Adder
69.838
316045AC1-158 PL2
Solar/Wind Helper
8.788
3147666LOUISA
Solar/Wind Helper
1.717
316192AB2-158 GEN
Solar/Wind Helper
2.822
316254AC1-120 GEN1
Solar/Wind Helper
1.415
316006AB2-029 C
Solar/Wind Helper
0.131
970533AG2-339 GEN
50/50
27.956
970531AG2-338 GEN
50/50
11.182
315242AE2-183_GT2
50/50
5.046
315241AE2-183_GT1
50/50
5.015
972185AH1-677 GEN
50/50
18.191
3151041BRUNSWICKG3
50/50
3.97
972187AH1-678 GEN
50/50
9.111
3150991CHESPKB
50/50
3.124
3150991CHESPKB
50/50
3.049
971223AH1-071 GEN
Solar/Wind Harmer
4.708
3143526WINTERP
Solar/Wind Harmer
-0.178
970933AG2-581 GEN
Solar/Wind Harmer
30.984
3144356SAPONY
Solar/Wind Harmer
1.13
316185AD1-033 GEN
Solar/Wind Harmer
3.336
3142956BIRDNECK
Solar/Wind Harmer
1.696
316316AC1-027 C
Solar/Wind Harmer
0.97
316036AC1-147 C
Solar/Wind Harmer
0.852
3145506HICKORY
Solar/Wind Harmer
-0.126
3145506HICKORY
Solar/Wind Harmer
-0.075
3145506HICKORY
Solar/Wind Harmer
-0.019
316339AD2-160 GEN
Solar/Wind Harmer
2.123
316018AA1-139 ULT2
Solar/Wind Harmer
2.695
316017AA1-139 ULT1
Solar/Wind Harmer
2.546
3137176SLIGO L2192
Solar/Wind Harmer
-0.124
3146456SLIGO L269
Solar/Wind Harmer
3.71
3130086AYDLETT
Solar/Wind Harmer
-0.125
970657AG2-426 GEN
Solar/Wind Harmer
9.748
970657AG2-426 GEN
Solar/Wind Harmer
2.039
3146386ELIZ CT
Solar/Wind Harmer
-0.031
316431W1029_GEN1
Solar/Wind Harmer
5.597
316433W1029_GEN2
Solar/Wind Harmer
5.597
316236AE1-162_GEN
Solar/Wind Harmer
0.929
3146516WINFALL
Solar/Wind Harmer
-0.031
3146516WINFALL
Solar/Wind Harmer
-0.031
3146516WINFALL
Solar/Wind Harmer
-0.031
3146626S HERTFORD
Solar/Wind Harmer
-0.031
3146626S HERTFORD
Solar/Wind Harmer
-0.031
970099AG2-077 GEN
Solar/Wind Harmer
38.011
315742AE1-103 GEN
Solar/Wind Harmer
3.171
3146376EDENTON
Solar/Wind Harmer
0.896
3146376EDENTON
Solar/Wind Harmer
0.896
316240AF1-291 C
Solar/Wind Harmer
0.906
316033AB2-134 GEN
Solar/Wind Harmer
9.651
315697AD1-025 GEN
Solar/Wind Harmer
6.053
944641AF1-129 GEN
Adder
126.539
316065AD1-022 GEN
Solar/Wind Harmer
14.554
3145893MURPHYS
Solar/Wind Harmer
0.81
3145893MURPHYS
Solar/Wind Harmer
-0.052
3146173TUNIS
Solar/Wind Harmer
-0.029
3146173TUNIS
Solar/Wind Harmer
-0.029
316181AB2-040 GEN
Solar/Wind Harmer
4.002
3142666NORTHAMPTON
Solar/Wind Harmer
-0.028
3142666NORTHAMPTON
Solar/Wind Harmer
-0.028
3142666NORTHAMPTON
Solar/Wind Harmer
-0.028
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
316426AA2-053 GEN
Solar/Wind Harmer
2.861
3145593CAROLNA
Solar/Wind Harmer
-0.028
3145593CAROLNA
Solar/Wind Harmer
-0.028
966811AG1-552 GEN
Solar/Wind Harmer
3.179
3145593CAROLNA
Solar/Wind Harmer
0.235
3145796HORNRTN
Solar/Wind Harmer
-0.084
3145783HORNRTN
Solar/Wind Harmer
3.335
3145783HORNRTN
Solar/Wind Harmer
2.668
3145783HORNRTN
Solar/Wind Harmer
0.834
3145783HORNRTN
Solar/Wind Harmer
0.334
3142946ENON
Solar/Wind Harmer
-0.003
316274AC1-208 GEN
Solar/Wind Harmer
2.942
3145933PARMELE
Solar/Wind Harmer
-0.054
3145933PARMELE
Solar/Wind Harmer
-0.027
3142366NRTHEST
Adder
0.786
3150691DARBY 3
Adder
17.226
3150701DARBY 4
Adder
17.185
3150681DARBY 2
Adder
17.165
3150671DARBY 1
Adder
17.145
971741AH1-377 GEN
Solar/Wind Harmer
31.097
939181AE1-148 GEN
Solar/Wind Harmer
14.98
316075AC2-137 C
Solar/Wind Harmer
0.711
313527AB2-043 GEN
Solar/Wind Harmer
4.254
3145493TOT1
Solar/Wind Harmer
0.404
3145453TOT5
Solar/Wind Harmer
0.242
3145603CNETO
Solar/Wind Harmer
0.162
970301AG2-198 GEN
Solar/Wind Harmer
12.986
3144293JTRSVLE
Adder
0.705
3144293JTRSVLE
Adder
0.594
3142296MT RD221
Adder
0.704
3150341NORNECKC1
Adder
1.92
3150341NORNECKC1
Adder
1.904
316447AC1-158 HLD
Solar/Wind Helper
6.042
315651AD1-115 GEN
Solar/Wind Helper
1.014
966001AG1-469 GEN
Solar/Wind Helper
0.285
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
970181AG2-120 GEN
Solar/Wind Harmer
3.507
971167AH1-042 GEN
Solar/Wind Harmer
25.67
3142433PROV 92
Adder
0.458
3142433PROV 92
Adder
0.458
315976AC1-164 GENA
Solar/Wind Harmer
27.981
316169AC1-164_GENC
Solar/Wind Harmer
24.173
315975AC1-164 GENB
Solar/Wind Harmer
0.828
957861AF2-080 GEN
Solar/Wind Harmer
11.55
316420AA1-050 GEN
Solar/Wind Harmer
2.998
316319Z2-044 C
Solar/Wind Harmer
1.447
316239AB2-077_GEN
Solar/Wind Harmer
0.788
316238AB2-078_GEN
Solar/Wind Harmer
0.788
3145573BETHELC
Solar/Wind Harmer
-0.026
3145573BETHELC
Solar/Wind Harmer
-0.026
972205AH1-687 GEN
Adder
6.895
972189AH1-679 GEN
Adder
2.574
972193AH1-681 GEN
Adder
2.678
316164AC1-076 GEN
Solar/Wind Helper
1.627
NYPJM->LTFIMP_NY
CLTF
3.09
LGEELTFEXP_LGEE->PJM
CLTF
2.105
WECLTFEXP_WEC->PJM
CLTF
1.07
LAGNLTFEXP_LAGN->PJM
CLTF
11.269
CBM South 2LTFEXP_CBM-S2->PJM
CBM
33.419
TVALTFEXP_TVA->PJM
CLTF
5.67
CBM West 1LTFEXP_CBM-W1->PJM
CBM
37.367
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.53
MECLTFEXP_MEC->PJM
CLTF
5.657
SIGELTFEXP_SIGE->PJM
CLTF
0.172
CPLELTFEXP_CPLE->PJM
CLTF
15.222
CBM West 2LTFEXP_CBM-W2->PJM
CBM
60.286

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T581_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 568T581_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:210.08 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:8277.02
MW Contribution:133.53
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
6.43
971285AH1-108 GEN
50/50
2.792
316233AE1-074 FULL
Solar/Wind Harmer
1.077
971281AH1-106 GEN
Solar/Wind Harmer
6.508
971283AH1-107 GEN
Solar/Wind Harmer
6.508
316312AB1-027
Solar/Wind Harmer
1.301
972189AH1-679 GEN
Adder
5.748
316132AB2-190 GEN1
Solar/Wind Harmer
3.853
3143316POE
Solar/Wind Harmer
-0.15
316369SG1_INVT
Solar/Wind Harmer
6.784
315976AC1-164 GENA
Solar/Wind Harmer
40.068
316169AC1-164_GENC
Solar/Wind Harmer
34.615
315975AC1-164 GENB
Solar/Wind Harmer
1.185
972265AH1-717 GEN
Adder
26.11
3151201GRAVEL4
Adder
24.476
3151191GRAVEL3
Adder
24.166
3151211GRAVEL5
Adder
24.166
971445AH1-216 GEN
Solar/Wind Harmer
23.358
3151081ELIZAR1
Adder
30.739
3151091ELIZAR2
Adder
30.205
3152611GOSPORTB
Adder
4.268
3152621GOSPORTC
Adder
3.622
3152601GOSPORTA
Adder
3.342
957871AF2-081 GEN
Solar/Wind Harmer
18.665
315833AF1-017_GEN
Solar/Wind Harmer
7.074
316349AD2-085 GEN
Solar/Wind Harmer
3.313
316311AC2-079 GEN
Solar/Wind Harmer
18.784
319010AE1-072 C
Solar/Wind Harmer
7.531
3146406KITTY HAWK
Solar/Wind Harmer
0.031
316305AF2-043 C
Solar/Wind Harmer
1.121
941031AE2-094 GEN
Solar/Wind Harmer
69.631
944011AF1-069 GEN
Solar/Wind Harmer
21.818
971167AH1-042 GEN
Solar/Wind Harmer
35.733
315835AF2-110_GEN
Solar/Wind Harmer
4.626
3142433PROV 92
Adder
0.64
3142433PROV 92
Adder
0.64
3150411LDYSMT5
Adder
44.306
3150381LDYSMT2
Adder
42.402
972213AH1-691 GEN
Adder
7.173
972215AH1-692 GEN
Adder
7.173
313526AB2-022
Solar/Wind Harmer
0.995
3146486SUNBURY
Solar/Wind Harmer
-0.037
3146486SUNBURY
Solar/Wind Harmer
-0.037
957831AF2-077 GEN
Solar/Wind Harmer
1.106
3138283WHITEMARSH
Solar/Wind Harmer
0.057
316321Z2-027
Solar/Wind Harmer
0.991
3146396TANGLEW
Solar/Wind Harmer
0.676
3145176PASQUOTANK
Solar/Wind Harmer
-0.023
316315AB2-025 C
Solar/Wind Harmer
0.987
3143873LANEXA
Solar/Wind Harmer
-0.022
970673AG2-436 GEN
Solar/Wind Harmer
76.723
970673AG2-436 GEN
Solar/Wind Harmer
38.847
315814AE2-033 C
Solar/Wind Harmer
33.934
316314AB2-024 C
Solar/Wind Harmer
3.103
316059AD1-063 C
Solar/Wind Harmer
0.817
971967AH1-528 GEN
Solar/Wind Harmer
67.827
315662AE1-191 GEN
Solar/Wind Harmer
4.344
315666AE1-190 GEN
Solar/Wind Harmer
1.086
315611Z1-036_GEN2
Solar/Wind Harmer
8.871
957601AF2-054 GEN
Solar/Wind Harmer
1.073
3141873WAN 176
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.035
3130156CHOWAN
Solar/Wind Harmer
-0.035
3141913WHIT STONE
Solar/Wind Harmer
-0.035
3138133OCRAN
Solar/Wind Harmer
-0.011
3141783LANCAST
Solar/Wind Harmer
-0.021
3141783LANCAST
Solar/Wind Harmer
-0.014
315816AE2-034 GEN
Solar/Wind Harmer
2.812
970085AG2-068 GEN
Solar/Wind Harmer
21.516
970581AG2-369 GEN
Solar/Wind Harmer
18.504
962981AG1-147 GEN
Solar/Wind Harmer
15.002
3130546PLYMOUTH
Solar/Wind Harmer
-0.034
315732AD1-074 GEN1
Solar/Wind Harmer
6.893
315733AD1-074 GEN2
Solar/Wind Harmer
6.893
315735AD1-075 GEN1
Solar/Wind Harmer
3.447
965291AG1-394 GEN
Solar/Wind Harmer
3.013
3146206CASHIE
Solar/Wind Harmer
-0.034
970601AG2-382 GEN
Solar/Wind Harmer
14.768
316318V4-068
Solar/Wind Harmer
0.839
3145893MURPHYS
Solar/Wind Harmer
-0.09
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145513AHOSKIE
Solar/Wind Harmer
0.289
961941AG1-037 GEN
Solar/Wind Harmer
0.25
3145513AHOSKIE
Solar/Wind Harmer
-0.033
946281AF1-292 GEN
Solar/Wind Harmer
0.741
3145683EARLEYS
Solar/Wind Harmer
-0.066
3145683EARLEYS
Solar/Wind Harmer
-0.033
3145683EARLEYS
Solar/Wind Harmer
-0.033
3146043SEABORD
Solar/Wind Harmer
-0.033
315607AA1-063A GEN
Solar/Wind Harmer
3.327
316087AB2-174 GEN
Solar/Wind Harmer
4.68
315652AC1-086 GEN
Solar/Wind Harmer
36.606
3137643SOCKMAN
Solar/Wind Harmer
-0.129
3141813NORNECK
Solar/Wind Harmer
-0.032
3145796HORNRTN
Solar/Wind Harmer
-0.102
3145796HORNRTN
Solar/Wind Harmer
-0.013
3146033SCOT NK
Solar/Wind Harmer
-0.127
972205AH1-687 GEN
Adder
10.039
972193AH1-681 GEN
Adder
5.12
3151881LOWMORC
Adder
1.285
3151881LOWMORC
Adder
1.265
3151861LOWMORA
Adder
1.245
316164AC1-076 GEN
Solar/Wind Helper
1.978
316411AF1-147_GEN1
Solar/Wind Helper
1.078
316415AF1-147_GEN2
Solar/Wind Helper
1.078
3138216PACIFIC
Solar/Wind Helper
0.053
237085AD2-009_GEN
Solar/Wind Helper
1.439
238208AF1-136 C
Solar/Wind Helper
0.182
960921AF2-383 GEN
Solar/Wind Helper
0.176
205943AE1-185 GEN
Solar/Wind Helper
0.492
233935AB2-179 C
Solar/Wind Helper
1.23
205932AD2-116_GEN
Solar/Wind Helper
0.492
205956AE1-196_GEN
Solar/Wind Helper
0.492
232436AB1-176 C
Solar/Wind Helper
0.043
233923SMA
Solar/Wind Helper
0.928
233990AG1-397 GEN
Solar/Wind Helper
0.029
234033AF1-007_GEN
Solar/Wind Helper
6.799
232432Z2-076 GEN
Solar/Wind Helper
0.065
959381AF2-229 GEN
Solar/Wind Helper
0.334
238152AF2-075_GEN
Solar/Wind Helper
0.554
964001AG1-254 GEN
Solar/Wind Helper
0.922
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.025
219914AD2-027 C
Solar/Wind Helper
0.111
219272CLEANLIGHT C
Solar/Wind Helper
0.024
219688LUMSOLAR_S C
Solar/Wind Helper
0.038
219607WPEMNERT C
Solar/Wind Helper
0.077
214067T20SOLAR
Solar/Wind Helper
0.011
970831AG2-522 GEN
Solar/Wind Harmer
4.516
3152251N ANNA1
50/50
24.932
970119AG2-088 GEN
50/50
48.227
3150851SPRUNCC
50/50
1.706
3143096IRON208
50/50
1.529
3143226MDLTHAN
Solar/Wind Harmer
-0.041
3143526WINTERP
Solar/Wind Harmer
-0.207
3142543TWELFTH
Solar/Wind Harmer
-0.004
3142416OLDCHRC
Solar/Wind Harmer
-0.1
3142416OLDCHRC
Solar/Wind Harmer
-0.038
940641AE2-051 GEN
Solar/Wind Harmer
35.93
944631AF1-128 GEN
Adder
162.412
315671AE2-027_GEN
Solar/Wind Harmer
28.648
939411AE1-173 GEN
Solar/Wind Harmer
190.668
316294AC1-161 GEN
Solar/Wind Harmer
12.329
970129AG2-093 GEN
Solar/Wind Harmer
8.69
316458AB2-190 GEN2
Solar/Wind Harmer
3.853
971069AG2-661 GEN
Solar/Wind Harmer
6.016
971647AH1-324 GEN
Solar/Wind Harmer
18.957
961611AG1-000B GEN
Solar/Wind Harmer
18.682
3151171GRAVELC
Adder
3.577
316159AE1-175 C
Solar/Wind Harmer
1.013
3145336SMITFLD
Solar/Wind Harmer
-0.15
944591AF1-124 GEN
Solar/Wind Harmer
172.182
966881AG1-559 GEN
Solar/Wind Harmer
0.388
316375AC2-012 GEN
Solar/Wind Harmer
13.033
3150981CHESPKA
Adder
4.185
970659AG2-427 GEN
Solar/Wind Harmer
20.009
3138126ROCKLANDING
Solar/Wind Harmer
0.115
316381AD1-082 GEN
Solar/Wind Harmer
3.451
970661AG2-428 GEN
Solar/Wind Harmer
39.862
971317AH1-138 GEN
Solar/Wind Harmer
4.684
316388AE2-253 GEN
Solar/Wind Harmer
2.52
316072AD1-144
Solar/Wind Harmer
0.755
3146456SLIGO L269
Solar/Wind Harmer
-0.037
316246AF1-032 C
Solar/Wind Harmer
0.752
316093AE2-104_GEN
Solar/Wind Harmer
10.761
3142433PROV 92
Solar/Wind Harmer
-0.147
3142433PROV 92
Adder
0.64
3142433PROV 92
Adder
0.64
972197AH1-683 GEN
Adder
6.897
972219AH1-694 GEN
Adder
4.966
3146516WINFALL
Solar/Wind Harmer
-0.117
3146516WINFALL
Solar/Wind Harmer
-0.036
3147666LOUISA
Solar/Wind Harmer
-0.144
971777AH1-397 GEN
Solar/Wind Harmer
4.252
3141843SHACKLE
Adder
1.644
3141766HARMONY
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
8.871
3130156CHOWAN
Solar/Wind Harmer
-0.035
316192AB2-158 GEN
Solar/Wind Harmer
4.195
3138133OCRAN
Solar/Wind Harmer
-0.021
3143336POWHATN
Solar/Wind Harmer
4.148
3145663CRESWEL
Solar/Wind Harmer
-0.097
971163AH1-040 GEN
Solar/Wind Harmer
32.582
970919AG2-571 GEN
Solar/Wind Harmer
10.938
970087AG2-069 GEN
Solar/Wind Harmer
32.274
961951AG1-038 GEN
Solar/Wind Harmer
4.47
316023GEN1_S
Solar/Wind Harmer
2.287
3146206CASHIE
Solar/Wind Harmer
-0.034
971547AH1-271 GEN
Solar/Wind Harmer
8.439
3145893MURPHYS
Solar/Wind Harmer
-0.134
3145893MURPHYS
Solar/Wind Harmer
0.999
962861AG1-135 GEN
Solar/Wind Harmer
12.565
316336AC2-165 C
Solar/Wind Harmer
5.815
3146173TUNIS
Solar/Wind Harmer
-0.033
960081AF2-299 GEN
Solar/Wind Harmer
3.72
957481AF2-042 GEN
Solar/Wind Harmer
103.301
3145683EARLEYS
Solar/Wind Harmer
-0.033
3146263WOODLND
Solar/Wind Harmer
-0.033
964211AG1-282 GEN
Solar/Wind Harmer
0.987
3141726DUNNSVL
Solar/Wind Harmer
-0.131
3145963POPLR C
Solar/Wind Harmer
-0.032
316011AB1-132 GEN
Solar/Wind Harmer
6.808
962571AG1-106 GEN
Solar/Wind Harmer
4.677
3145823KELFORD
Solar/Wind Harmer
-0.032
315693AD1-088 GEN
Solar/Wind Harmer
16.208
316190AA2-174 GEN
Solar/Wind Harmer
0.398
971795AH1-408 GEN
Solar/Wind Harmer
24.298
962491AG1-098 GEN
Solar/Wind Harmer
21.614
3150351NORNECKC2
Adder
2.867
316174AB2-169 GEN
Solar/Wind Harmer
4.976
3147043LAWRENC
Adder
2.584
3145783HORNRTN
Solar/Wind Harmer
-0.032
3145796HORNRTN
Solar/Wind Harmer
-0.105
3145796HORNRTN
Solar/Wind Harmer
-0.032
316212AC1-099_GEN
Solar/Wind Harmer
2.729
3146293MARTNCO
Solar/Wind Harmer
0.193
3144293JTRSVLE
Adder
0.837
972277AH1-723 GEN
Adder
133.532
3151751LOISA D
Adder
11.364
316045AC1-158 PL2
Solar/Wind Helper
15.147
316006AB2-029 C
Solar/Wind Helper
0.159
316254AC1-120 GEN1
Solar/Wind Helper
1.225
23779801AA1-109
Solar/Wind Helper
0.187
223401AF1-299 GEN
Solar/Wind Helper
0.373
237080AD1-060 GEN
Solar/Wind Helper
0.304
237038AE2-054 C
Solar/Wind Helper
0.241
235062AE1-101 C1
Solar/Wind Helper
1.47
966131AG1-482 GEN
Solar/Wind Helper
0.075
233930AB2-032 GEN
Solar/Wind Helper
0.369
233915AB1-141 GEN
Solar/Wind Helper
0.487
232422X3-066 FULL
Solar/Wind Helper
0.111
233964AF2-378 GEN
Solar/Wind Helper
0.04
232426Y1-080 FULL
Solar/Wind Helper
0.038
233998TM1NIN_3.36
Solar/Wind Helper
0.253
232404W1-003 C
Solar/Wind Helper
0.491
232428Y3-058 C
Solar/Wind Helper
0.327
232434Z2-077 GEN
Solar/Wind Helper
0.123
233954AC2-188 GEN
Solar/Wind Helper
0.225
233950AC2-186 GEN
Solar/Wind Helper
0.112
233972AC1-094 C
Solar/Wind Helper
0.293
238148AE2-230_GEN2
Solar/Wind Helper
0.39
230511AF1-262
Solar/Wind Helper
0.014
230434AG1-499 GEN
Solar/Wind Helper
0.222
228728W1-130C
Solar/Wind Helper
0.052
219258KINSLEYDEP C
Solar/Wind Helper
0.074
219904AC1-010 C
Solar/Wind Helper
0.058
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219907AC1-030 C
Solar/Wind Helper
0.033
219686LUMSOLAR_N C
Solar/Wind Helper
0.038
219304NAMERICA C
Solar/Wind Helper
0.126
971133AH1-012 GEN
50/50
6.819
3142296MT RD221
50/50
1.172
3142366NRTHEST
50/50
1.196
3150691DARBY 3
50/50
26.261
3150701DARBY 4
50/50
26.199
3150681DARBY 2
50/50
26.169
971223AH1-071 GEN
Solar/Wind Harmer
5.08
3143526WINTERP
Solar/Wind Harmer
-0.207
3150671DARBY 1
Adder
24.633
944641AF1-129 GEN
Adder
162.93
316240AF1-291 C
Solar/Wind Harmer
1.156
316075AC2-137 C
Solar/Wind Harmer
1.03
3142946ENON
Solar/Wind Harmer
-0.004
316033AB2-134 GEN
Solar/Wind Harmer
12.245
315697AD1-025 GEN
Solar/Wind Harmer
7.68
316236AE1-162_GEN
Solar/Wind Harmer
1.137
957411AF2-035 GEN
Solar/Wind Harmer
16.975
970317AG2-208 GEN
Solar/Wind Harmer
16.504
316036AC1-147 C
Solar/Wind Harmer
1.016
3150991CHESPKB
Adder
3.511
3150991CHESPKB
Adder
3.427
316316AC1-027 C
Solar/Wind Harmer
1.154
3142956BIRDNECK
Solar/Wind Harmer
2.018
970657AG2-426 GEN
Solar/Wind Harmer
11.745
970657AG2-426 GEN
Solar/Wind Harmer
2.456
316185AD1-033 GEN
Solar/Wind Harmer
3.963
3145506HICKORY
Solar/Wind Harmer
-0.149
3145506HICKORY
Solar/Wind Harmer
-0.09
3145506HICKORY
Solar/Wind Harmer
-0.022
315673AE1-157 GEN
Solar/Wind Harmer
28.094
316339AD2-160 GEN
Solar/Wind Harmer
2.52
966871AG1-558 GEN
Solar/Wind Harmer
1.122
966871AG1-558 GEN
Solar/Wind Harmer
0.384
316018AA1-139 ULT2
Solar/Wind Harmer
3.198
316017AA1-139 ULT1
Solar/Wind Harmer
3.021
3137176SLIGO L2192
Solar/Wind Harmer
-0.147
3146456SLIGO L269
Solar/Wind Harmer
4.4
3130086AYDLETT
Solar/Wind Harmer
-0.148
3150391LDYSMT3
Adder
44.085
972195AH1-682 GEN
Adder
5.793
3146386ELIZ CT
Solar/Wind Harmer
-0.037
3144356SAPONY
Solar/Wind Harmer
1.276
316431W1029_GEN1
Solar/Wind Harmer
6.618
316433W1029_GEN2
Solar/Wind Harmer
6.618
3146516WINFALL
Solar/Wind Harmer
-0.036
3146516WINFALL
Solar/Wind Harmer
-0.036
3146516WINFALL
Solar/Wind Harmer
-0.036
3146626S HERTFORD
Solar/Wind Harmer
-0.036
3146626S HERTFORD
Solar/Wind Harmer
-0.036
972185AH1-677 GEN
Adder
18.085
316441AF1-014 GEN
Solar/Wind Harmer
2.437
972187AH1-678 GEN
Adder
9.074
315742AE1-103 GEN
Solar/Wind Harmer
3.731
3146376EDENTON
Solar/Wind Harmer
1.053
3146376EDENTON
Solar/Wind Harmer
1.053
970933AG2-581 GEN
Solar/Wind Harmer
33.038
316487AF1-042 GEN
Solar/Wind Harmer
4.47
316065AD1-022 GEN
Solar/Wind Harmer
16.937
3145893MURPHYS
Solar/Wind Harmer
0.939
3145893MURPHYS
Solar/Wind Harmer
-0.06
3146173TUNIS
Solar/Wind Harmer
-0.033
3146173TUNIS
Solar/Wind Harmer
-0.033
958261AF2-120 GEN
Solar/Wind Harmer
12.924
970099AG2-077 GEN
Solar/Wind Harmer
41.32
316181AB2-040 GEN
Solar/Wind Harmer
4.56
3142666NORTHAMPTON
Solar/Wind Harmer
-0.033
3142666NORTHAMPTON
Solar/Wind Harmer
-0.033
3142666NORTHAMPTON
Solar/Wind Harmer
-0.033
3142666NORTHAMPTON
Solar/Wind Harmer
-0.019
316426AA2-053 GEN
Solar/Wind Harmer
3.274
316077AC2-138 C
Solar/Wind Harmer
0.682
3150341NORNECKC1
Adder
3.012
3150341NORNECKC1
Adder
2.987
3145593CAROLNA
Solar/Wind Harmer
-0.032
3145593CAROLNA
Solar/Wind Harmer
-0.032
966811AG1-552 GEN
Solar/Wind Harmer
3.63
3145593CAROLNA
Solar/Wind Harmer
0.268
3145783HORNRTN
Solar/Wind Harmer
3.807
3145783HORNRTN
Solar/Wind Harmer
3.046
3145783HORNRTN
Solar/Wind Harmer
0.952
3145783HORNRTN
Solar/Wind Harmer
0.381
3145796HORNRTN
Solar/Wind Harmer
-0.096
316468AD1-105 GEN
Solar/Wind Harmer
3.513
3145933PARMELE
Solar/Wind Harmer
-0.062
3145933PARMELE
Solar/Wind Harmer
-0.031
316274AC1-208 GEN
Solar/Wind Harmer
3.354
3144293JTRSVLE
Adder
0.837
3144293JTRSVLE
Adder
0.705
3151731LOISA B
Adder
11.364
3151721LOISA A
Adder
11.305
316447AC1-158 HLD
Solar/Wind Helper
10.414
315651AD1-115 GEN
Solar/Wind Helper
0.939
226929AD2-058 GEN
Solar/Wind Helper
0.108
23777801MSM_W1-116
Solar/Wind Helper
0.111
237025AB1-124 C
Solar/Wind Helper
0.161
237006AB1-125 GEN
Solar/Wind Helper
0.121
237034AC2-136 C
Solar/Wind Helper
0.211
23777901MDS_W4-102
Solar/Wind Helper
0.157
235020AA1-095 C
Solar/Wind Helper
0.046
237001AB1-127_GEN
Solar/Wind Helper
0.396
237002AB1-128_GEN
Solar/Wind Helper
0.396
235063AE1-101 C2
Solar/Wind Helper
1.47
238175AF1-290_GEN
Solar/Wind Helper
0.127
238169AE2-226 GEN1
Solar/Wind Helper
0.578
238170AE2-226 GEN2
Solar/Wind Helper
0.578
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
205916AD1-020 GEN
Solar/Wind Helper
1.656
233933AB2-153 GEN
Solar/Wind Helper
0.225
233987AB2-037 GEN
Solar/Wind Helper
2.269
233944AB2-135 GEN
Solar/Wind Helper
0.57
232424Y1-079 C
Solar/Wind Helper
0.113
233946AB2-136 GEN
Solar/Wind Helper
0.55
234036AF2-325 C
Solar/Wind Helper
0.041
233901CHERRYDALE C
Solar/Wind Helper
0.225
232408W1-005 C
Solar/Wind Helper
0.491
232410W1-006 C
Solar/Wind Helper
0.491
233939AC1-091 C
Solar/Wind Helper
0.339
233970AC1-092 C
Solar/Wind Helper
0.339
20390526W1-045 C
Solar/Wind Helper
0.327
230433AD2-135 GEN
Solar/Wind Helper
0.016
230407AD2-065 C
Solar/Wind Helper
0.039
219921AF1-264
Solar/Wind Helper
0.049
219615MILLCREEK C
Solar/Wind Helper
0.026
3152261N ANNA2
50/50
24.93
970497AG2-320 GEN
50/50
33.128
3150861SPRUNCD
50/50
1.706
971645AH1-323 GEN
50/50
30.891
3143096IRON208
50/50
1.529
3143096IRON208
50/50
1.499
3142416OLDCHRC
Solar/Wind Harmer
3.892
970293AG2-193 GEN
Solar/Wind Harmer
4.804
315839AE2-212 C
Solar/Wind Harmer
1.153
970133AG2-095 GEN
Solar/Wind Harmer
4.299
3142946ENON
Solar/Wind Harmer
-0.013
965281AG1-393 GEN
Solar/Wind Harmer
4.773
315773AC2-141 GEN
Solar/Wind Harmer
15.945
970129AG2-093 GEN
Solar/Wind Harmer
21.453
315778AD1-151 GEN
Solar/Wind Harmer
32.937
315813AE1-149 C
Solar/Wind Harmer
23.666
961611AG1-000B GEN
Solar/Wind Harmer
7.971
3151221GRAVEL6
Adder
24.448
3151171GRAVELC
Adder
4.704
316382AG1-145 C
Solar/Wind Harmer
1.138
3145336SMITFLD
Solar/Wind Harmer
-0.015
944581AF1-123 GEN
Solar/Wind Harmer
171.564
944601AF1-125 GEN
Solar/Wind Harmer
168.886
966881AG1-559 GEN
Solar/Wind Harmer
1.134
3144536CHRHLND
Solar/Wind Harmer
-0.006
3151101ELIZAR3
Adder
31.133
970659AG2-427 GEN
Solar/Wind Harmer
3.546
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3144216WINCHST
Adder
1.263
316083AB2-161 GEN
Solar/Wind Harmer
6.107
3150921YORKTN3
Adder
8.413
970661AG2-428 GEN
Solar/Wind Harmer
7.064
316473AC1-191 GEN
Solar/Wind Harmer
4.017
3146456SLIGO L269
Solar/Wind Harmer
-0.037
971153AH1-033 GEN
Solar/Wind Harmer
4.542
3142433PROV 92
Adder
0.64
3142433PROV 92
Adder
0.64
3150401LDYSMT4
Adder
44.168
3150371LDYSMT1
Adder
42.678
316320Y1-086
Solar/Wind Harmer
2.162
316435W1029_GEN3
Solar/Wind Harmer
6.618
3146516WINFALL
Solar/Wind Harmer
-0.036
3146626S HERTFORD
Solar/Wind Harmer
-0.036
3147666LOUISA
Solar/Wind Harmer
-0.083
3141843SHACKLE
Adder
1.644
316203AE2-005 GEN
Solar/Wind Harmer
15.244
3141766HARMONY
Solar/Wind Harmer
3.217
3145273HOLLAND
Solar/Wind Harmer
-0.027
316280AD1-041 GEN
Solar/Wind Harmer
2.715
316156AD2-030 GEN
Solar/Wind Harmer
0.958
3141873WAN 176
Solar/Wind Harmer
4.258
3146376EDENTON
Solar/Wind Harmer
-0.035
316313AB2-026
Solar/Wind Harmer
0.943
316258AE1-075 C
Solar/Wind Harmer
0.849
316405AF2-144 C
Solar/Wind Harmer
0.895
3143336POWHATN
Solar/Wind Harmer
3.526
315614AA2-178 GEN
Solar/Wind Harmer
3.75
970917AG2-570 GEN
Solar/Wind Harmer
86.408
962971AG1-146 GEN
Solar/Wind Harmer
6.43
971157AH1-035 GEN
Solar/Wind Harmer
4.274
3156081AA2-088 GEN
Solar/Wind Harmer
11.067
315737AD1-076 GEN
Solar/Wind Harmer
6.478
316484AD2-074 GEN
Solar/Wind Harmer
8.542
970009AG2-005 GEN
Solar/Wind Harmer
4.242
316365GEN2_N
Solar/Wind Harmer
2.287
3146206CASHIE
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.235
3145893MURPHYS
Solar/Wind Harmer
-0.034
957521AF2-046 GEN
Solar/Wind Harmer
26.442
961681AG1-008 GEN
Solar/Wind Harmer
26.442
3146173TUNIS
Solar/Wind Harmer
-0.033
316404AE1-155 C
Solar/Wind Harmer
6.434
3156021HOLLOMANSOL
Solar/Wind Harmer
4.485
316463AE2-346 GEN
Solar/Wind Harmer
0.537
316140AB2-099
Solar/Wind Harmer
0.224
962331AG1-082 GEN
Solar/Wind Harmer
4.15
966621AG1-532 GEN
Solar/Wind Harmer
0.671
3146263WOODLND
Solar/Wind Harmer
-0.033
313506AB2-031 GEN
Solar/Wind Harmer
2.628
3142666NORTHAMPTON
Solar/Wind Harmer
-0.033
3145963POPLR C
Solar/Wind Harmer
-0.032
316317KELFORD C
Solar/Wind Harmer
1.529
3145823KELFORD
Solar/Wind Harmer
-0.032
3150351NORNECKC2
Adder
2.915
3147043LAWRENC
Solar/Wind Harmer
-0.019
3145796HORNRTN
Solar/Wind Harmer
-0.128
3145796HORNRTN
Solar/Wind Harmer
-0.032
316478AD1-087 GEN
Solar/Wind Harmer
2.758
316486AD2-202 GEN
Solar/Wind Harmer
0.808
971781AH1-399 GEN
Solar/Wind Harmer
1.944
316210AC1-098 GEN
Solar/Wind Harmer
4.912
3145933PARMELE
Solar/Wind Harmer
-0.031
966801AG1-551 GEN
Solar/Wind Harmer
3.899
3144293JTRSVLE
Adder
0.837
972255AH1-712 GEN
Adder
114.59
3151761LOISA E
Adder
23.168
972183AH1-676 GEN
Adder
179.308
3141316ARNOLDS
Adder
0.38
3150331BIRCHWDA
Adder
23.913
3151861LOWMORA
Adder
1.295
316044AC1-158 PL1
Solar/Wind Helper
4.732
316450AC1-158 RIC
Solar/Wind Helper
1.262
3141196NOKESVL
Solar/Wind Helper
1.429
227287AC2-120 GEN
Solar/Wind Helper
0.373
226910AB2-157 C
Solar/Wind Helper
0.015
316170AC1-121 GEN2
Solar/Wind Helper
0.408
237030AB1-096 C
Solar/Wind Helper
0.069
223402AF1-300 C
Solar/Wind Helper
0.373
238221AF1-254 C O1
Solar/Wind Helper
0.245
235067AD1-061 GEN
Solar/Wind Helper
0.438
205917AD1-020 ES
Solar/Wind Helper
0.356
233918AB1-142 GEN
Solar/Wind Helper
0.487
233982AB2-133 GEN
Solar/Wind Helper
0.347
233994AC2-023 GEN
Solar/Wind Helper
0.931
233996TM1833_GEN
Solar/Wind Helper
0.253
233997TMININ_4.2
Solar/Wind Helper
0.253
232406W1-004 FULL
Solar/Wind Helper
0.491
233940AF2-379 C
Solar/Wind Helper
0.06
234015AF2-250 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.225
233971AC1-093 C
Solar/Wind Helper
0.346
238147AE2-230_GEN1
Solar/Wind Helper
0.388
238149AF1-291A_GEN
Solar/Wind Helper
0.111
230430AE1-229_GEN
Solar/Wind Helper
3.252
230415AB2-049 C
Solar/Wind Helper
0.029
228729W2-030 C
Solar/Wind Helper
0.106
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.053
219912AD2-042 GEN
Solar/Wind Helper
0.144
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.11
959561AF2-247 GEN
Solar/Wind Helper
0.02
NYPJM->LTFIMP_NY
CLTF
4.79
LGEELTFEXP_LGEE->PJM
CLTF
2.231
WECLTFEXP_WEC->PJM
CLTF
1.099
LAGNLTFEXP_LAGN->PJM
CLTF
12.471
CBM South 2LTFEXP_CBM-S2->PJM
CBM
37.435
TVALTFEXP_TVA->PJM
CLTF
6.314
CBM West 1LTFEXP_CBM-W1->PJM
CBM
37.411
CBM South 1LTFEXP_CBM-S1->PJM
CBM
21.636
MECLTFEXP_MEC->PJM
CLTF
5.976
SIGELTFEXP_SIGE->PJM
CLTF
0.183
CPLELTFEXP_CPLE->PJM
CLTF
16.95
CBM West 2LTFEXP_CBM-W2->PJM
CBM
65.721

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 574T575_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 574T575_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:174.96 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:6893.4
MW Contribution:73.59
Bus #Bus NameTypeMW Contribution
3152251N ANNA1
50/50
31.961
970119AG2-088 GEN
50/50
40.696
315243AE2-183_GT3
50/50
4.555
3151051BRUNSWICKS1
50/50
7.445
3151021BRUNSWICKG1
50/50
3.587
971451AH1-221 GEN
50/50
10.895
3150981CHESPKA
50/50
3.363
3147666LOUISA
Solar/Wind Harmer
-0.188
316192AB2-158 GEN
Solar/Wind Harmer
5.479
3143226MDLTHAN
Solar/Wind Harmer
-0.034
940641AE2-051 GEN
Solar/Wind Harmer
30.211
3143526WINTERP
Solar/Wind Harmer
-0.162
939411AE1-173 GEN
Solar/Wind Harmer
156.554
3143336POWHATN
Solar/Wind Harmer
3.513
970919AG2-571 GEN
Solar/Wind Harmer
9.325
970087AG2-069 GEN
Solar/Wind Harmer
27.507
316294AC1-161 GEN
Solar/Wind Harmer
9.352
944591AF1-124 GEN
Solar/Wind Harmer
131.161
316375AC2-012 GEN
Solar/Wind Harmer
9.869
316388AE2-253 GEN
Solar/Wind Harmer
1.918
3146456SLIGO L269
Solar/Wind Harmer
-0.028
316336AC2-165 C
Solar/Wind Harmer
4.931
316246AF1-032 C
Solar/Wind Harmer
0.572
316381AD1-082 GEN
Solar/Wind Harmer
2.584
970659AG2-427 GEN
Solar/Wind Harmer
14.969
970661AG2-428 GEN
Solar/Wind Harmer
29.933
316093AE2-104_GEN
Solar/Wind Harmer
8.186
957481AF2-042 GEN
Solar/Wind Harmer
87.747
3150851SPRUNCC
Adder
1.15
316072AD1-144
Solar/Wind Harmer
0.567
3146516WINFALL
Solar/Wind Harmer
-0.09
3146516WINFALL
Solar/Wind Harmer
-0.028
3145336SMITFLD
Solar/Wind Harmer
-0.111
315800Z1-036_GEN1
Solar/Wind Harmer
6.81
315693AD1-088 GEN
Solar/Wind Harmer
13.752
3151171GRAVELC
Adder
2.597
962491AG1-098 GEN
Solar/Wind Harmer
18.339
3130156CHOWAN
Solar/Wind Harmer
-0.027
961611AG1-000B GEN
Solar/Wind Harmer
13.464
315671AE2-027_GEN
Solar/Wind Harmer
20.456
971647AH1-324 GEN
Solar/Wind Harmer
13.581
316023GEN1_S
Solar/Wind Harmer
1.828
971069AG2-661 GEN
Solar/Wind Harmer
4.264
3145663CRESWEL
Solar/Wind Harmer
-0.075
971163AH1-040 GEN
Solar/Wind Harmer
25.206
316458AB2-190 GEN2
Solar/Wind Harmer
2.713
970129AG2-093 GEN
Solar/Wind Harmer
6.111
3151751LOISA D
Adder
15.367
960081AF2-299 GEN
Solar/Wind Harmer
2.989
3138126ROCKLANDING
Solar/Wind Harmer
0.081
3142543TWELFTH
Solar/Wind Harmer
-0.003
3145893MURPHYS
Solar/Wind Harmer
-0.105
3145893MURPHYS
Solar/Wind Harmer
0.783
3146206CASHIE
Solar/Wind Harmer
-0.026
971547AH1-271 GEN
Solar/Wind Harmer
6.58
971795AH1-408 GEN
Solar/Wind Harmer
19.653
3146173TUNIS
Solar/Wind Harmer
-0.026
3147043LAWRENC
Adder
2.097
3145683EARLEYS
Solar/Wind Harmer
-0.026
316011AB1-132 GEN
Solar/Wind Harmer
5.429
962571AG1-106 GEN
Solar/Wind Harmer
3.73
3146263WOODLND
Solar/Wind Harmer
-0.026
316190AA2-174 GEN
Solar/Wind Harmer
0.317
3143096IRON208
Adder
0.962
971317AH1-138 GEN
Solar/Wind Harmer
3.222
3145783HORNRTN
Solar/Wind Harmer
-0.026
3145823KELFORD
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.084
3145796HORNRTN
Solar/Wind Harmer
-0.026
316159AE1-175 C
Solar/Wind Harmer
0.686
3145963POPLR C
Solar/Wind Harmer
-0.025
944631AF1-128 GEN
Adder
107.977
315687AD1-152 GEN
Solar/Wind Harmer
3.055
316174AB2-169 GEN
Solar/Wind Harmer
3.908
970937AG2-583 GEN
Solar/Wind Harmer
18.128
316129AC1-054 GEN
Solar/Wind Harmer
2.211
971065AG2-659 GEN
Solar/Wind Harmer
12.582
316212AC1-099_GEN
Solar/Wind Harmer
2.175
970685AG2-442 GEN
Solar/Wind Harmer
21.702
3144293JTRSVLE
Adder
0.703
3142433PROV 92
Adder
0.412
3142433PROV 92
Adder
0.412
3141843SHACKLE
Adder
1.042
3150351NORNECKC2
Adder
1.599
972277AH1-723 GEN
Adder
73.593
316045AC1-158 PL2
Solar/Wind Helper
11.209
3152261N ANNA2
50/50
31.958
3151031BRUNSWICKG2
50/50
3.587
3151101ELIZAR3
50/50
25.035
3147666LOUISA
Solar/Wind Harmer
-0.108
316313AB2-026
Solar/Wind Harmer
0.798
316258AE1-075 C
Solar/Wind Harmer
0.719
316405AF2-144 C
Solar/Wind Harmer
0.758
3143336POWHATN
Solar/Wind Harmer
2.986
970917AG2-570 GEN
Solar/Wind Harmer
73.668
315773AC2-141 GEN
Solar/Wind Harmer
12.096
944581AF1-123 GEN
Solar/Wind Harmer
130.69
944601AF1-125 GEN
Solar/Wind Harmer
128.65
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146456SLIGO L269
Solar/Wind Harmer
-0.028
971153AH1-033 GEN
Solar/Wind Harmer
3.459
3144536CHRHLND
Solar/Wind Harmer
-0.004
315813AE1-149 C
Solar/Wind Harmer
17.615
316083AB2-161 GEN
Solar/Wind Harmer
4.573
970659AG2-427 GEN
Solar/Wind Harmer
2.653
970661AG2-428 GEN
Solar/Wind Harmer
5.305
316320Y1-086
Solar/Wind Harmer
1.65
3150861SPRUNCD
Adder
1.15
316435W1029_GEN3
Solar/Wind Harmer
5.059
3146516WINFALL
Solar/Wind Harmer
-0.028
3145336SMITFLD
Solar/Wind Harmer
-0.011
315839AE2-212 C
Solar/Wind Harmer
0.839
3146626S HERTFORD
Solar/Wind Harmer
-0.028
3145273HOLLAND
Solar/Wind Harmer
-0.021
965281AG1-393 GEN
Solar/Wind Harmer
3.435
3151221GRAVEL6
Adder
17.751
3151171GRAVELC
Adder
3.415
3146376EDENTON
Solar/Wind Harmer
-0.027
961611AG1-000B GEN
Solar/Wind Harmer
5.745
316365GEN2_N
Solar/Wind Harmer
1.828
316478AD1-087 GEN
Solar/Wind Harmer
2.335
316486AD2-202 GEN
Solar/Wind Harmer
0.684
315778AD1-151 GEN
Solar/Wind Harmer
23.348
315614AA2-178 GEN
Solar/Wind Harmer
2.901
970129AG2-093 GEN
Solar/Wind Harmer
15.087
3156081AA2-088 GEN
Solar/Wind Harmer
8.655
3151761LOISA E
Adder
31.328
970133AG2-095 GEN
Solar/Wind Harmer
2.99
966621AG1-532 GEN
Solar/Wind Harmer
0.539
3144216WINCHST
Adder
0.891
971157AH1-035 GEN
Solar/Wind Harmer
3.319
315737AD1-076 GEN
Solar/Wind Harmer
5.035
3150921YORKTN3
Adder
5.907
3145893MURPHYS
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
-0.026
957521AF2-046 GEN
Solar/Wind Harmer
20.741
961681AG1-008 GEN
Solar/Wind Harmer
20.741
3146206CASHIE
Solar/Wind Harmer
-0.026
313506AB2-031 GEN
Solar/Wind Harmer
2.107
3146173TUNIS
Solar/Wind Harmer
-0.026
316463AE2-346 GEN
Solar/Wind Harmer
0.422
316140AB2-099
Solar/Wind Harmer
0.176
962331AG1-082 GEN
Solar/Wind Harmer
3.26
3156021HOLLOMANSOL
Solar/Wind Harmer
3.513
3147043LAWRENC
Solar/Wind Harmer
-0.015
3142666NORTHAMPTON
Solar/Wind Harmer
-0.026
3146263WOODLND
Solar/Wind Harmer
-0.026
970909AG2-566 GEN
Solar/Wind Harmer
2.462
3143096IRON208
Adder
0.962
3143096IRON208
Adder
0.943
316317KELFORD C
Solar/Wind Harmer
1.207
3145823KELFORD
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.102
3145796HORNRTN
Solar/Wind Harmer
-0.026
972183AH1-676 GEN
Adder
243.274
316382AG1-145 C
Solar/Wind Harmer
0.77
3145963POPLR C
Solar/Wind Harmer
-0.025
3142946ENON
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
3.914
316131AB2-060 GEN
Solar/Wind Harmer
2.677
964241AG1-285 GEN
Solar/Wind Harmer
19.386
315785AD2-033 C
Solar/Wind Harmer
5.622
970257AG2-171 GEN
Solar/Wind Harmer
9.302
959311AF2-222 GEN
Solar/Wind Harmer
25.891
3144293JTRSVLE
Adder
0.703
3142433PROV 92
Adder
0.412
3142433PROV 92
Adder
0.412
3141843SHACKLE
Adder
1.042
3150351NORNECKC2
Adder
1.625
972255AH1-712 GEN
Adder
63.154
316044AC1-158 PL1
Solar/Wind Helper
3.502
316450AC1-158 RIC
Solar/Wind Helper
0.934
3141196NOKESVL
Solar/Wind Helper
1.078
227287AC2-120 GEN
Solar/Wind Helper
0.305
226910AB2-157 C
Solar/Wind Helper
0.012
971133AH1-012 GEN
50/50
8.834
970533AG2-339 GEN
50/50
25.186
970531AG2-338 GEN
50/50
10.074
315242AE2-183_GT2
50/50
4.555
315241AE2-183_GT1
50/50
4.527
972185AH1-677 GEN
50/50
16.42
3151041BRUNSWICKG3
50/50
3.587
972187AH1-678 GEN
50/50
8.232
3150991CHESPKB
50/50
2.821
3150991CHESPKB
50/50
2.753
971223AH1-071 GEN
Solar/Wind Harmer
4.287
3143526WINTERP
Solar/Wind Harmer
-0.162
970933AG2-581 GEN
Solar/Wind Harmer
28.21
3144356SAPONY
Solar/Wind Harmer
1.021
316185AD1-033 GEN
Solar/Wind Harmer
3.013
3142956BIRDNECK
Solar/Wind Harmer
1.531
316316AC1-027 C
Solar/Wind Harmer
0.876
316036AC1-147 C
Solar/Wind Harmer
0.769
3145506HICKORY
Solar/Wind Harmer
-0.113
3145506HICKORY
Solar/Wind Harmer
-0.068
3145506HICKORY
Solar/Wind Harmer
-0.017
316339AD2-160 GEN
Solar/Wind Harmer
1.918
316018AA1-139 ULT2
Solar/Wind Harmer
2.435
316017AA1-139 ULT1
Solar/Wind Harmer
2.3
3137176SLIGO L2192
Solar/Wind Harmer
-0.112
3146456SLIGO L269
Solar/Wind Harmer
3.351
3130086AYDLETT
Solar/Wind Harmer
-0.113
970657AG2-426 GEN
Solar/Wind Harmer
8.805
970657AG2-426 GEN
Solar/Wind Harmer
1.841
3146386ELIZ CT
Solar/Wind Harmer
-0.028
970099AG2-077 GEN
Solar/Wind Harmer
35.099
316431W1029_GEN1
Solar/Wind Harmer
5.059
316433W1029_GEN2
Solar/Wind Harmer
5.059
3146516WINFALL
Solar/Wind Harmer
-0.028
3146516WINFALL
Solar/Wind Harmer
-0.028
3146516WINFALL
Solar/Wind Harmer
-0.028
316236AE1-162_GEN
Solar/Wind Harmer
0.839
3146626S HERTFORD
Solar/Wind Harmer
-0.028
3146626S HERTFORD
Solar/Wind Harmer
-0.028
315742AE1-103 GEN
Solar/Wind Harmer
2.873
3146376EDENTON
Solar/Wind Harmer
0.811
3146376EDENTON
Solar/Wind Harmer
0.811
316240AF1-291 C
Solar/Wind Harmer
0.819
316033AB2-134 GEN
Solar/Wind Harmer
8.722
315697AD1-025 GEN
Solar/Wind Harmer
5.47
944641AF1-129 GEN
Adder
114.368
3151731LOISA B
Adder
15.367
3151721LOISA A
Adder
15.287
3145893MURPHYS
Solar/Wind Harmer
0.736
3145893MURPHYS
Solar/Wind Harmer
-0.047
316065AD1-022 GEN
Solar/Wind Harmer
13.191
971741AH1-377 GEN
Solar/Wind Harmer
30.569
316181AB2-040 GEN
Solar/Wind Harmer
3.656
3146173TUNIS
Solar/Wind Harmer
-0.026
3146173TUNIS
Solar/Wind Harmer
-0.026
3142666NORTHAMPTON
Solar/Wind Harmer
-0.026
3142666NORTHAMPTON
Solar/Wind Harmer
-0.026
3142666NORTHAMPTON
Solar/Wind Harmer
-0.026
3142666NORTHAMPTON
Solar/Wind Harmer
-0.015
970301AG2-198 GEN
Solar/Wind Harmer
12.968
316426AA2-053 GEN
Solar/Wind Harmer
2.61
3145593CAROLNA
Solar/Wind Harmer
-0.026
3145593CAROLNA
Solar/Wind Harmer
-0.026
966811AG1-552 GEN
Solar/Wind Harmer
2.903
3145593CAROLNA
Solar/Wind Harmer
0.214
3145783HORNRTN
Solar/Wind Harmer
3.044
3145783HORNRTN
Solar/Wind Harmer
2.436
3145783HORNRTN
Solar/Wind Harmer
0.761
3145783HORNRTN
Solar/Wind Harmer
0.304
3145796HORNRTN
Solar/Wind Harmer
-0.076
3142946ENON
Solar/Wind Harmer
-0.003
939181AE1-148 GEN
Solar/Wind Harmer
13.998
316274AC1-208 GEN
Solar/Wind Harmer
2.681
313527AB2-043 GEN
Solar/Wind Harmer
4.032
316034AC1-036 C
Solar/Wind Harmer
0.46
970323AG2-213 GEN
Solar/Wind Harmer
12.403
971775AH1-396 GEN
Solar/Wind Harmer
1.766
3144293JTRSVLE
Adder
0.703
3144293JTRSVLE
Adder
0.592
3142366NRTHEST
Adder
0.712
3150691DARBY 3
Adder
15.594
3150701DARBY 4
Adder
15.558
3150681DARBY 2
Adder
15.54
3150671DARBY 1
Adder
15.522
3142296MT RD221
Adder
0.637
3150341NORNECKC1
Adder
1.679
3150341NORNECKC1
Adder
1.666
316447AC1-158 HLD
Solar/Wind Helper
7.707
226929AD2-058 GEN
Solar/Wind Helper
0.088
316303AF2-085
50/50
5.426
315244AE2-183_ST
50/50
7.875
963041AG1-153 GEN
50/50
7.263
315779AE2-040
50/50
3.636
3151081ELIZAR1
50/50
24.718
3151091ELIZAR2
50/50
24.289
941591AE2-156 GEN
50/50
22.58
3152611GOSPORTB
50/50
3.43
3152621GOSPORTC
50/50
2.911
3152601GOSPORTA
50/50
2.685
941031AE2-094 GEN
Solar/Wind Harmer
59.691
944011AF1-069 GEN
Solar/Wind Harmer
18.703
316233AE1-074 FULL
Solar/Wind Harmer
0.843
971281AH1-106 GEN
Solar/Wind Harmer
5.091
971283AH1-107 GEN
Solar/Wind Harmer
5.091
970673AG2-436 GEN
Solar/Wind Harmer
65.689
970673AG2-436 GEN
Solar/Wind Harmer
33.26
971967AH1-528 GEN
Solar/Wind Harmer
58.02
970085AG2-068 GEN
Solar/Wind Harmer
18.338
970581AG2-369 GEN
Solar/Wind Harmer
15.771
316315AB2-025 C
Solar/Wind Harmer
0.79
315814AE2-033 C
Solar/Wind Harmer
27.155
3143316POE
Solar/Wind Harmer
-0.114
957871AF2-081 GEN
Solar/Wind Harmer
14.21
319010AE1-072 C
Solar/Wind Harmer
5.736
3146406KITTY HAWK
Solar/Wind Harmer
0.024
316305AF2-043 C
Solar/Wind Harmer
0.853
315833AF1-017_GEN
Solar/Wind Harmer
5.349
316349AD2-085 GEN
Solar/Wind Harmer
2.505
316311AC2-079 GEN
Solar/Wind Harmer
14.204
313526AB2-022
Solar/Wind Harmer
0.759
315835AF2-110_GEN
Solar/Wind Harmer
3.519
3146486SUNBURY
Solar/Wind Harmer
-0.028
3146486SUNBURY
Solar/Wind Harmer
-0.028
316321Z2-027
Solar/Wind Harmer
0.757
3146396TANGLEW
Solar/Wind Harmer
0.516
3145176PASQUOTANK
Solar/Wind Harmer
-0.017
971285AH1-108 GEN
Adder
1.882
971445AH1-216 GEN
Solar/Wind Harmer
17.213
315611Z1-036_GEN2
Solar/Wind Harmer
6.81
972265AH1-717 GEN
Adder
18.958
3151201GRAVEL4
Adder
17.771
3151191GRAVEL3
Adder
17.547
3151211GRAVEL5
Adder
17.547
3130156CHOWAN
Solar/Wind Harmer
-0.027
3130156CHOWAN
Solar/Wind Harmer
-0.027
316369SG1_INVT
Solar/Wind Harmer
4.832
315816AE2-034 GEN
Solar/Wind Harmer
2.176
316132AB2-190 GEN1
Solar/Wind Harmer
2.713
965291AG1-394 GEN
Solar/Wind Harmer
2.36
946281AF1-292 GEN
Solar/Wind Harmer
0.595
3130546PLYMOUTH
Solar/Wind Harmer
-0.026
315732AD1-074 GEN1
Solar/Wind Harmer
5.358
315733AD1-074 GEN2
Solar/Wind Harmer
5.358
315735AD1-075 GEN1
Solar/Wind Harmer
2.68
316318V4-068
Solar/Wind Harmer
0.658
3145893MURPHYS
Solar/Wind Harmer
-0.071
3145893MURPHYS
Solar/Wind Harmer
-0.026
3146206CASHIE
Solar/Wind Harmer
-0.026
970601AG2-382 GEN
Solar/Wind Harmer
11.515
316087AB2-174 GEN
Solar/Wind Harmer
3.755
3146043SEABORD
Solar/Wind Harmer
-0.026
315607AA1-063A GEN
Solar/Wind Harmer
2.638
3145513AHOSKIE
Solar/Wind Harmer
0.227
961941AG1-037 GEN
Solar/Wind Harmer
0.196
3145513AHOSKIE
Solar/Wind Harmer
-0.026
3137643SOCKMAN
Solar/Wind Harmer
-0.103
3145683EARLEYS
Solar/Wind Harmer
-0.052
3145683EARLEYS
Solar/Wind Harmer
-0.026
3145683EARLEYS
Solar/Wind Harmer
-0.026
315652AC1-086 GEN
Solar/Wind Harmer
29.194
3145796HORNRTN
Solar/Wind Harmer
-0.081
3145796HORNRTN
Solar/Wind Harmer
-0.01
970831AG2-522 GEN
Solar/Wind Harmer
12.637
3146033SCOT NK
Solar/Wind Harmer
-0.1
971443AH1-215 GEN
Solar/Wind Harmer
4.884
3144303KENBRDG
Solar/Wind Harmer
-0.02
3147346CASHSCORNER
Solar/Wind Harmer
0.384
3142433PROV 92
Adder
0.412
3142433PROV 92
Adder
0.412
972205AH1-687 GEN
Adder
8.575
972189AH1-679 GEN
Adder
2.228
972193AH1-681 GEN
Adder
2.822
316411AF1-147_GEN1
Solar/Wind Helper
0.847
316415AF1-147_GEN2
Solar/Wind Helper
0.847
3138216PACIFIC
Solar/Wind Helper
0.041
316164AC1-076 GEN
Solar/Wind Helper
1.148
970683AG2-441 GEN
Solar/Wind Harmer
5.411
970681AG2-440 GEN
Solar/Wind Harmer
4.329
NYPJM->LTFIMP_NY
CLTF
3.837
LGEELTFEXP_LGEE->PJM
CLTF
1.676
WECLTFEXP_WEC->PJM
CLTF
0.823
LAGNLTFEXP_LAGN->PJM
CLTF
9.821
CBM South 2LTFEXP_CBM-S2->PJM
CBM
30.397
TVALTFEXP_TVA->PJM
CLTF
4.963
CBM West 1LTFEXP_CBM-W1->PJM
CBM
27.809
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.931
MECLTFEXP_MEC->PJM
CLTF
4.554
SIGELTFEXP_SIGE->PJM
CLTF
0.138
CPLELTFEXP_CPLE->PJM
CLTF
13.878
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.117

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 552_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:172.64 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:5559.88
MW Contribution:87.35
Bus #Bus NameTypeMW Contribution
3152261N ANNA2
50/50
20.32
3150861SPRUNCD
50/50
1.216
3143096IRON208
50/50
1.078
3143096IRON208
50/50
1.056
3150801HOPHCF4
50/50
1.421
971211AH1-065 GEN
50/50
1.714
3151101ELIZAR3
50/50
23.68
3151161SURRY 1
50/50
9.205
3147666LOUISA
Solar/Wind Harmer
0.591
315839AE2-212 C
Solar/Wind Harmer
0.002
315773AC2-141 GEN
Solar/Wind Harmer
8.876
965281AG1-393 GEN
Solar/Wind Harmer
2.585
315813AE1-149 C
Solar/Wind Harmer
12.873
970133AG2-095 GEN
Solar/Wind Harmer
2.314
944581AF1-123 GEN
Solar/Wind Harmer
54.216
944601AF1-125 GEN
Solar/Wind Harmer
53.381
970129AG2-093 GEN
Solar/Wind Harmer
14.547
315778AD1-151 GEN
Solar/Wind Harmer
19.233
3144536CHRHLND
Solar/Wind Harmer
0.036
3144873MCLAUGH
Solar/Wind Harmer
0.006
970659AG2-427 GEN
Solar/Wind Harmer
2.54
3145336SMITFLD
Solar/Wind Harmer
0.096
316083AB2-161 GEN
Solar/Wind Harmer
0.003
961611AG1-000B GEN
Solar/Wind Harmer
6.396
3151221GRAVEL6
Adder
17.422
3151171GRAVELC
Adder
3.352
970661AG2-428 GEN
Solar/Wind Harmer
5.062
970293AG2-193 GEN
Solar/Wind Harmer
2.548
3142946ENON
Solar/Wind Harmer
0.08
3146456SLIGO L269
Solar/Wind Harmer
0.238
971153AH1-033 GEN
Solar/Wind Harmer
2.749
3142416OLDCHRC
Solar/Wind Harmer
2.305
3144216WINCHST
Adder
0.896
3150921YORKTN3
Adder
5.966
316382AG1-145 C
Solar/Wind Harmer
0.002
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.233
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
3146626S HERTFORD
Solar/Wind Harmer
0.231
3145273HOLLAND
Solar/Wind Harmer
0.173
316473AC1-191 GEN
Solar/Wind Harmer
0.778
3141843SHACKLE
Adder
1.16
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316313AB2-026
Solar/Wind Harmer
0.143
316258AE1-075 C
Solar/Wind Harmer
0.171
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.429
3146376EDENTON
Solar/Wind Harmer
0.227
3141766HARMONY
Solar/Wind Harmer
3.024
316280AD1-041 GEN
Solar/Wind Harmer
0.005
316156AD2-030 GEN
Solar/Wind Harmer
0.167
3141873WAN 176
Solar/Wind Harmer
4.011
970917AG2-570 GEN
Solar/Wind Harmer
20.009
315614AA2-178 GEN
Solar/Wind Harmer
1.271
971157AH1-035 GEN
Solar/Wind Harmer
2.623
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
316365GEN2_N
Solar/Wind Harmer
0.489
315737AD1-076 GEN
Solar/Wind Harmer
2.804
3150401LDYSMT4
Adder
29.156
3150371LDYSMT1
Adder
28.172
962971AG1-146 GEN
Solar/Wind Harmer
3.461
3146206CASHIE
Solar/Wind Harmer
0.216
3145893MURPHYS
Solar/Wind Harmer
0.361
3145893MURPHYS
Solar/Wind Harmer
0.215
957521AF2-046 GEN
Solar/Wind Harmer
15.996
961681AG1-008 GEN
Solar/Wind Harmer
15.996
970009AG2-005 GEN
Solar/Wind Harmer
1.599
3146173TUNIS
Solar/Wind Harmer
0.213
3156021HOLLOMANSOL
Solar/Wind Harmer
0.967
316463AE2-346 GEN
Solar/Wind Harmer
0.183
316140AB2-099
Solar/Wind Harmer
0.076
962331AG1-082 GEN
Solar/Wind Harmer
2.268
316404AE1-155 C
Solar/Wind Harmer
0.047
3146263WOODLND
Solar/Wind Harmer
0.21
313506AB2-031 GEN
Solar/Wind Harmer
0.649
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3145963POPLR C
Solar/Wind Harmer
0.208
316317KELFORD C
Solar/Wind Harmer
0.02
3145823KELFORD
Solar/Wind Harmer
0.208
316478AD1-087 GEN
Solar/Wind Harmer
0.721
316486AD2-202 GEN
Solar/Wind Harmer
0.212
3147043LAWRENC
Solar/Wind Harmer
0.124
3145796HORNRTN
Solar/Wind Harmer
0.822
3145796HORNRTN
Solar/Wind Harmer
0.206
3150351NORNECKC2
Adder
2.075
316210AC1-098 GEN
Solar/Wind Harmer
1.861
3145933PARMELE
Solar/Wind Harmer
0.2
966801AG1-551 GEN
Solar/Wind Harmer
2.326
971781AH1-399 GEN
Solar/Wind Harmer
0.26
970909AG2-566 GEN
Solar/Wind Harmer
2.105
3145746EVERETS
Solar/Wind Harmer
0.196
3145746EVERETS
Solar/Wind Harmer
0.196
315724AD1-057 GEN
Solar/Wind Harmer
0.733
316327AA2-057 GEN
Solar/Wind Harmer
0.292
316131AB2-060 GEN
Solar/Wind Harmer
0.604
964241AG1-285 GEN
Solar/Wind Harmer
12.793
315785AD2-033 C
Solar/Wind Harmer
1.556
970257AG2-171 GEN
Solar/Wind Harmer
6.117
959311AF2-222 GEN
Solar/Wind Harmer
16.978
3146233WITAKRS
Solar/Wind Harmer
0.955
3146233WITAKRS
Solar/Wind Harmer
0.129
3146073TAR RVR
Solar/Wind Harmer
0.19
3146083TARBORO
Solar/Wind Harmer
0.19
963181AG1-167 GEN
Solar/Wind Harmer
0.761
3144293JTRSVLE
Adder
0.605
3138543CONSLDL
Solar/Wind Harmer
0.125
3147133PAMPLIN
Solar/Wind Harmer
0.596
971193AH1-056 GEN
Solar/Wind Harmer
11.558
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.113
961601AG1-000A GEN
Solar/Wind Harmer
13.299
3145543BTLEBRO
Solar/Wind Harmer
0.187
3145543BTLEBRO
Solar/Wind Harmer
0.187
971623AH1-311 GEN
Solar/Wind Harmer
0.374
3141906WESTMOR
Solar/Wind Harmer
0.074
3146776BUCKING
Solar/Wind Harmer
0.064
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.491
970737AG2-469 GEN
Solar/Wind Harmer
7.435
971683AH1-343 GEN
Solar/Wind Harmer
5.965
316283AC2-100 C
Solar/Wind Harmer
0.31
970221AG2-151 GEN
Solar/Wind Harmer
8.416
972255AH1-712 GEN
Adder
74.962
3151761LOISA E
Adder
17.688
972183AH1-676 GEN
Adder
136.298
3141316ARNOLDS
Adder
0.29
316044AC1-158 PL1
Solar/Wind Helper
5.216
316450AC1-158 RIC
Solar/Wind Helper
1.391
3141196NOKESVL
Solar/Wind Helper
1.131
971133AH1-012 GEN
50/50
5.491
944641AF1-129 GEN
50/50
122.767
970533AG2-339 GEN
50/50
21.564
970531AG2-338 GEN
50/50
8.626
3142366NRTHEST
50/50
0.836
3150781HOPHCF2
50/50
0.977
3150791HOPHCF3
50/50
0.977
3150761HOPPOLC
50/50
0.62
971213AH1-066 GEN
50/50
0.857
971223AH1-071 GEN
Solar/Wind Harmer
2.834
3143526WINTERP
Solar/Wind Harmer
1.342
316240AF1-291 C
Solar/Wind Harmer
0.002
3150691DARBY 3
Adder
17.296
3150701DARBY 4
Adder
17.255
3150681DARBY 2
Adder
17.235
3150671DARBY 1
Adder
17.215
316036AC1-147 C
Solar/Wind Harmer
0.045
3150991CHESPKB
Adder
2.516
3150991CHESPKB
Adder
2.456
316033AB2-134 GEN
Solar/Wind Harmer
0.014
315697AD1-025 GEN
Solar/Wind Harmer
0.27
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.23
316236AE1-162_GEN
Solar/Wind Harmer
0.002
316185AD1-033 GEN
Solar/Wind Harmer
0.007
970657AG2-426 GEN
Solar/Wind Harmer
8.395
970657AG2-426 GEN
Solar/Wind Harmer
1.76
3142296MT RD221
Adder
0.763
3145506HICKORY
Solar/Wind Harmer
0.957
3145506HICKORY
Solar/Wind Harmer
0.574
3145506HICKORY
Solar/Wind Harmer
0.144
3142946ENON
Solar/Wind Harmer
0.024
316339AD2-160 GEN
Solar/Wind Harmer
0.387
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
316017AA1-139 ULT1
Solar/Wind Harmer
0.133
3137176SLIGO L2192
Solar/Wind Harmer
0.946
3146456SLIGO L269
Solar/Wind Harmer
4.208
3130086AYDLETT
Solar/Wind Harmer
0.95
316075AC2-137 C
Solar/Wind Harmer
0.065
972185AH1-677 GEN
Adder
13.26
3144356SAPONY
Solar/Wind Harmer
1.973
3146386ELIZ CT
Solar/Wind Harmer
0.235
972187AH1-678 GEN
Adder
6.65
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.233
3146516WINFALL
Solar/Wind Harmer
0.233
3146516WINFALL
Solar/Wind Harmer
0.233
3146626S HERTFORD
Solar/Wind Harmer
0.231
3146626S HERTFORD
Solar/Wind Harmer
0.231
966871AG1-558 GEN
Solar/Wind Harmer
0.266
970933AG2-581 GEN
Solar/Wind Harmer
18.37
315742AE1-103 GEN
Solar/Wind Harmer
0.003
3146376EDENTON
Solar/Wind Harmer
1.008
3146376EDENTON
Solar/Wind Harmer
1.008
957411AF2-035 GEN
Solar/Wind Harmer
9.597
970317AG2-208 GEN
Solar/Wind Harmer
8.892
315673AE1-157 GEN
Solar/Wind Harmer
15.364
3150391LDYSMT3
Adder
29.101
972195AH1-682 GEN
Adder
3.824
316065AD1-022 GEN
Solar/Wind Harmer
9.976
3145893MURPHYS
Solar/Wind Harmer
1.442
3145893MURPHYS
Solar/Wind Harmer
0.388
970099AG2-077 GEN
Solar/Wind Harmer
22.899
3146173TUNIS
Solar/Wind Harmer
0.213
3146173TUNIS
Solar/Wind Harmer
0.213
958261AF2-120 GEN
Solar/Wind Harmer
6.97
316181AB2-040 GEN
Solar/Wind Harmer
0.305
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3142666NORTHAMPTON
Solar/Wind Harmer
0.126
316426AA2-053 GEN
Solar/Wind Harmer
0.702
3145593CAROLNA
Solar/Wind Harmer
0.207
3145593CAROLNA
Solar/Wind Harmer
0.207
966811AG1-552 GEN
Solar/Wind Harmer
2.246
3145593CAROLNA
Solar/Wind Harmer
0.258
3145783HORNRTN
Solar/Wind Harmer
3.66
3145783HORNRTN
Solar/Wind Harmer
2.928
3145783HORNRTN
Solar/Wind Harmer
0.915
3145783HORNRTN
Solar/Wind Harmer
0.366
3145796HORNRTN
Solar/Wind Harmer
0.617
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.143
3150341NORNECKC1
Adder
2.126
971741AH1-377 GEN
Solar/Wind Harmer
19.869
3145933PARMELE
Solar/Wind Harmer
0.399
3145933PARMELE
Solar/Wind Harmer
0.2
316274AC1-208 GEN
Solar/Wind Harmer
1.034
316468AD1-105 GEN
Solar/Wind Harmer
-0.064
970301AG2-198 GEN
Solar/Wind Harmer
8.419
939181AE1-148 GEN
Solar/Wind Harmer
9.29
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.014
970323AG2-213 GEN
Solar/Wind Harmer
8.155
971775AH1-396 GEN
Solar/Wind Harmer
0.306
3145493TOT1
Solar/Wind Harmer
0.441
3145453TOT5
Solar/Wind Harmer
0.264
3145603CNETO
Solar/Wind Harmer
0.176
958211AF2-115 GEN
Solar/Wind Harmer
2.282
963191AG1-168 GEN
Solar/Wind Harmer
0.761
3144293JTRSVLE
Adder
0.605
3144293JTRSVLE
Adder
0.51
3147133PAMPLIN
Solar/Wind Harmer
0.19
3147133PAMPLIN
Solar/Wind Harmer
0.152
961601AG1-000A GEN
Solar/Wind Harmer
3.325
316263AC1-034 GEN
Solar/Wind Harmer
7.104
962561AG1-105 GEN
Solar/Wind Harmer
8.835
964791AG1-342 GEN
Solar/Wind Harmer
3.505
3146843MT LREL
Solar/Wind Harmer
0.182
3146843MT LREL
Solar/Wind Harmer
0.182
3146776BUCKING
Solar/Wind Harmer
0.716
3146776BUCKING
Solar/Wind Harmer
0.058
316222AC1-221 GEN
Solar/Wind Harmer
0.661
971489AH1-241 GEN
Solar/Wind Harmer
8.416
315821AE2-092 GEN
Solar/Wind Harmer
0.008
942751AE2-291 GEN
Solar/Wind Harmer
7.289
3151731LOISA B
Adder
8.676
3151721LOISA A
Adder
8.631
316447AC1-158 HLD
Solar/Wind Helper
11.481
316303AF2-085
50/50
4.723
971285AH1-108 GEN
50/50
1.99
970603AG2-384 GEN
50/50
5.178
972263AH1-716 GEN
50/50
139.063
316233AE1-074 FULL
Solar/Wind Harmer
0.207
971281AH1-106 GEN
Solar/Wind Harmer
3.58
971283AH1-107 GEN
Solar/Wind Harmer
3.58
3143316POE
Solar/Wind Harmer
0.964
941031AE2-094 GEN
Solar/Wind Harmer
44.68
944011AF1-069 GEN
Solar/Wind Harmer
14.599
316132AB2-190 GEN1
Solar/Wind Harmer
1.291
3151081ELIZAR1
Adder
22.034
3151091ELIZAR2
Adder
21.652
3152611GOSPORTB
Adder
3.059
3152621GOSPORTC
Adder
2.596
3152601GOSPORTA
Adder
2.395
316369SG1_INVT
Solar/Wind Harmer
0.009
971445AH1-216 GEN
Solar/Wind Harmer
16.89
972265AH1-717 GEN
Adder
18.606
3151201GRAVEL4
Adder
17.442
3151191GRAVEL3
Adder
17.221
3151211GRAVEL5
Adder
17.221
970673AG2-436 GEN
Solar/Wind Harmer
50.858
970673AG2-436 GEN
Solar/Wind Harmer
33.905
957871AF2-081 GEN
Solar/Wind Harmer
11.862
316312AB1-027
Solar/Wind Harmer
0.425
319010AE1-072 C
Solar/Wind Harmer
1.197
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.163
316311AC2-079 GEN
Solar/Wind Harmer
6.823
3146406KITTY HAWK
Solar/Wind Harmer
0.03
316305AF2-043 C
Solar/Wind Harmer
0.002
315835AF2-110_GEN
Solar/Wind Harmer
1.621
316315AB2-025 C
Solar/Wind Harmer
0.191
315976AC1-164 GENA
Solar/Wind Harmer
24.444
316169AC1-164_GENC
Solar/Wind Harmer
21.117
315975AC1-164 GENB
Solar/Wind Harmer
0.723
313526AB2-022
Solar/Wind Harmer
0.128
971967AH1-528 GEN
Solar/Wind Harmer
37.658
315814AE2-033 C
Solar/Wind Harmer
18.587
3146486SUNBURY
Solar/Wind Harmer
0.235
3146486SUNBURY
Solar/Wind Harmer
0.235
316321Z2-027
Solar/Wind Harmer
0.044
3146396TANGLEW
Solar/Wind Harmer
0.646
3145176PASQUOTANK
Solar/Wind Harmer
0.145
972189AH1-679 GEN
Adder
3.913
971167AH1-042 GEN
Solar/Wind Harmer
20.686
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
3138283WHITEMARSH
Solar/Wind Harmer
0.054
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
3143873LANEXA
Solar/Wind Harmer
0.137
316314AB2-024 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
6.729
3130156CHOWAN
Solar/Wind Harmer
0.227
3130156CHOWAN
Solar/Wind Harmer
0.227
316059AD1-063 C
Solar/Wind Harmer
0.001
315662AE1-191 GEN
Solar/Wind Harmer
0.007
315666AE1-190 GEN
Solar/Wind Harmer
0.002
3141873WAN 176
Solar/Wind Harmer
0.045
970085AG2-068 GEN
Solar/Wind Harmer
11.956
970581AG2-369 GEN
Solar/Wind Harmer
10.282
3141913WHIT STONE
Solar/Wind Harmer
0.222
315816AE2-034 GEN
Solar/Wind Harmer
0.953
3138133OCRAN
Solar/Wind Harmer
0.066
3141783LANCAST
Solar/Wind Harmer
0.132
3141783LANCAST
Solar/Wind Harmer
0.088
3130546PLYMOUTH
Solar/Wind Harmer
0.218
315732AD1-074 GEN1
Solar/Wind Harmer
1.252
315733AD1-074 GEN2
Solar/Wind Harmer
1.252
315735AD1-075 GEN1
Solar/Wind Harmer
0.627
965291AG1-394 GEN
Solar/Wind Harmer
0.966
3150411LDYSMT5
Adder
29.247
3150381LDYSMT2
Adder
27.99
972213AH1-691 GEN
Adder
4.735
972215AH1-692 GEN
Adder
4.735
962981AG1-147 GEN
Solar/Wind Harmer
8.075
3146206CASHIE
Solar/Wind Harmer
0.216
970601AG2-382 GEN
Solar/Wind Harmer
8.061
3145893MURPHYS
Solar/Wind Harmer
0.582
3145893MURPHYS
Solar/Wind Harmer
0.215
970327AG2-215 GEN
Solar/Wind Harmer
7.029
3145513AHOSKIE
Solar/Wind Harmer
0.444
3145513AHOSKIE
Solar/Wind Harmer
0.212
3146043SEABORD
Solar/Wind Harmer
0.212
3145683EARLEYS
Solar/Wind Harmer
0.423
3145683EARLEYS
Solar/Wind Harmer
0.211
3145683EARLEYS
Solar/Wind Harmer
0.211
315607AA1-063A GEN
Solar/Wind Harmer
0.431
316087AB2-174 GEN
Solar/Wind Harmer
0.006
315652AC1-086 GEN
Solar/Wind Harmer
22.967
3137643SOCKMAN
Solar/Wind Harmer
0.832
3145796HORNRTN
Solar/Wind Harmer
0.658
3145796HORNRTN
Solar/Wind Harmer
0.082
3141813NORNECK
Solar/Wind Harmer
0.205
3146033SCOT NK
Solar/Wind Harmer
0.815
970831AG2-522 GEN
Solar/Wind Harmer
8.503
316005AA1-067
Solar/Wind Harmer
0.21
3145746EVERETS
Solar/Wind Harmer
0.779
3145746EVERETS
Solar/Wind Harmer
0.196
3145746EVERETS
Solar/Wind Harmer
0.196
3145746EVERETS
Solar/Wind Harmer
0.196
970181AG2-120 GEN
Solar/Wind Harmer
2.436
957861AF2-080 GEN
Solar/Wind Harmer
8.31
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316420AA1-050 GEN
Solar/Wind Harmer
0.006
971443AH1-215 GEN
Solar/Wind Harmer
3.212
3144303KENBRDG
Solar/Wind Harmer
0.153
970683AG2-441 GEN
Solar/Wind Harmer
12.709
970681AG2-440 GEN
Solar/Wind Harmer
10.167
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.19
3145573BETHELC
Solar/Wind Harmer
0.19
946301AF1-294 GEN
Solar/Wind Harmer
3.752
961791AG1-021 GEN
Solar/Wind Harmer
1.825
315657AE1-056 GEN
Solar/Wind Harmer
6.547
316223AC1-118
Solar/Wind Harmer
0.132
970285AG2-188 GEN
Solar/Wind Harmer
14.341
971845AH1-439 GEN
Solar/Wind Harmer
8.154
316118AC1-105 GEN
Solar/Wind Harmer
0.462
3147173SINAI
Solar/Wind Harmer
0.175
3147243WELCO
Solar/Wind Harmer
0.11
972205AH1-687 GEN
Adder
7.204
944491AF1-114 GEN
Solar/Wind Harmer
0.001
970865AG2-541 GEN
Solar/Wind Harmer
5.394
971447AH1-217 GEN
Solar/Wind Harmer
4.654
972193AH1-681 GEN
Adder
3.349
316123AC1-075 GEN
Solar/Wind Harmer
0.195
970165AG2-112 GEN
Solar/Wind Harmer
1.154
970163AG2-111 GEN
Solar/Wind Harmer
1.101
270494AE1-108_GEN
Solar/Wind Harmer
1.672
3147346CASHSCORNER
Solar/Wind Harmer
0.293
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316164AC1-076 GEN
Solar/Wind Helper
1.38
316411AF1-147_GEN1
Solar/Wind Helper
0.79
316415AF1-147_GEN2
Solar/Wind Helper
0.79
3138216PACIFIC
Solar/Wind Helper
0.038
3152251N ANNA1
50/50
20.321
970119AG2-088 GEN
50/50
35.422
3150851SPRUNCC
50/50
1.216
3143096IRON208
50/50
1.078
3152331SURRY 2
50/50
9.99
3150771HOPHCF1
50/50
0.977
3143226MDLTHAN
Solar/Wind Harmer
0.265
3143526WINTERP
Solar/Wind Harmer
1.342
3147666LOUISA
Solar/Wind Harmer
1.028
316192AB2-158 GEN
Solar/Wind Harmer
1.415
940641AE2-051 GEN
Solar/Wind Harmer
19.964
939411AE1-173 GEN
Solar/Wind Harmer
105.426
3142543TWELFTH
Solar/Wind Harmer
0.023
316294AC1-161 GEN
Solar/Wind Harmer
4.211
315671AE2-027_GEN
Solar/Wind Harmer
15.496
944591AF1-124 GEN
Solar/Wind Harmer
54.408
970129AG2-093 GEN
Solar/Wind Harmer
6.846
316458AB2-190 GEN2
Solar/Wind Harmer
1.291
971069AG2-661 GEN
Solar/Wind Harmer
4.274
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
3
970659AG2-427 GEN
Solar/Wind Harmer
11.613
971647AH1-324 GEN
Solar/Wind Harmer
10.242
3145336SMITFLD
Solar/Wind Harmer
0.959
316381AD1-082 GEN
Solar/Wind Harmer
0.25
944631AF1-128 GEN
Adder
114.357
961611AG1-000B GEN
Solar/Wind Harmer
12.579
3151171GRAVELC
Adder
2.549
970661AG2-428 GEN
Solar/Wind Harmer
23.801
316388AE2-253 GEN
Solar/Wind Harmer
0.747
3146456SLIGO L269
Solar/Wind Harmer
0.238
3142416OLDCHRC
Solar/Wind Harmer
0.618
3142416OLDCHRC
Solar/Wind Harmer
0.237
316072AD1-144
Solar/Wind Harmer
0.086
3138126ROCKLANDING
Solar/Wind Harmer
0.109
316246AF1-032 C
Solar/Wind Harmer
0.107
316159AE1-175 C
Solar/Wind Harmer
0.205
316093AE2-104_GEN
Solar/Wind Harmer
3.974
971317AH1-138 GEN
Solar/Wind Harmer
1.762
3146516WINFALL
Solar/Wind Harmer
0.754
3146516WINFALL
Solar/Wind Harmer
0.233
3142433PROV 92
Solar/Wind Harmer
0.928
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
971777AH1-397 GEN
Solar/Wind Harmer
0.6
3141843SHACKLE
Adder
1.16
3143336POWHATN
Solar/Wind Harmer
4.034
3130156CHOWAN
Solar/Wind Harmer
0.227
3141766HARMONY
Solar/Wind Harmer
0.045
970919AG2-571 GEN
Solar/Wind Harmer
8.004
966881AG1-559 GEN
Solar/Wind Harmer
0.26
970087AG2-069 GEN
Solar/Wind Harmer
17.934
3145663CRESWEL
Solar/Wind Harmer
0.622
971163AH1-040 GEN
Solar/Wind Harmer
17.772
3138133OCRAN
Solar/Wind Harmer
0.133
316023GEN1_S
Solar/Wind Harmer
0.489
972197AH1-683 GEN
Adder
4.553
972219AH1-694 GEN
Adder
3.278
316336AC2-165 C
Solar/Wind Harmer
0.008
3146206CASHIE
Solar/Wind Harmer
0.216
971547AH1-271 GEN
Solar/Wind Harmer
4.607
3145893MURPHYS
Solar/Wind Harmer
0.862
3145893MURPHYS
Solar/Wind Harmer
0.958
957481AF2-042 GEN
Solar/Wind Harmer
57.247
3146173TUNIS
Solar/Wind Harmer
0.213
960081AF2-299 GEN
Solar/Wind Harmer
2.041
962861AG1-135 GEN
Solar/Wind Harmer
6.774
3145683EARLEYS
Solar/Wind Harmer
0.211
3146263WOODLND
Solar/Wind Harmer
0.21
315693AD1-088 GEN
Solar/Wind Harmer
10.091
962491AG1-098 GEN
Solar/Wind Harmer
11.959
316011AB1-132 GEN
Solar/Wind Harmer
3.796
962571AG1-106 GEN
Solar/Wind Harmer
2.971
971795AH1-408 GEN
Solar/Wind Harmer
13.893
3145963POPLR C
Solar/Wind Harmer
0.208
316190AA2-174 GEN
Solar/Wind Harmer
0
3145823KELFORD
Solar/Wind Harmer
0.208
3141726DUNNSVL
Solar/Wind Harmer
0.83
316174AB2-169 GEN
Solar/Wind Harmer
0.006
3147043LAWRENC
Adder
1.868
3145783HORNRTN
Solar/Wind Harmer
0.206
3145796HORNRTN
Solar/Wind Harmer
0.678
3145796HORNRTN
Solar/Wind Harmer
0.206
3150351NORNECKC2
Adder
2.04
316212AC1-099_GEN
Solar/Wind Harmer
1.038
3146293MARTNCO
Solar/Wind Harmer
0.185
316129AC1-054 GEN
Solar/Wind Harmer
0.746
971065AG2-659 GEN
Solar/Wind Harmer
8.434
3145746EVERETS
Solar/Wind Harmer
0.196
3145746EVERETS
Solar/Wind Harmer
0.196
315722AD1-056 GEN
Solar/Wind Harmer
1.237
316337AD2-073 GEN
Solar/Wind Harmer
0.169
315687AD1-152 GEN
Solar/Wind Harmer
0.006
316494AC1-189 GEN
Solar/Wind Harmer
0.651
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970937AG2-583 GEN
Solar/Wind Harmer
11.696
970685AG2-442 GEN
Solar/Wind Harmer
14.234
3146233WITAKRS
Solar/Wind Harmer
0.757
961671AG1-007 GEN
Solar/Wind Harmer
0.029
3146083TARBORO
Solar/Wind Harmer
0.19
3145493TOT1
Solar/Wind Harmer
0.845
963171AG1-166 GEN
Solar/Wind Harmer
1.014
971563AH1-280 GEN
Solar/Wind Harmer
2.028
3144293JTRSVLE
Adder
0.605
3146926FARMVIL
Solar/Wind Harmer
0.113
3145543BTLEBRO
Solar/Wind Harmer
0.187
3145543BTLEBRO
Solar/Wind Harmer
0.149
316359AB2-059 GEN
Solar/Wind Harmer
0.672
316049AB1-081 GEN
Solar/Wind Harmer
1.07
3142053HEARTS
Solar/Wind Harmer
0.329
970401AG2-262 GEN
Solar/Wind Harmer
1.071
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.072
972003AH1-546 GEN
Solar/Wind Harmer
7.247
316003AC1-222 GEN
Solar/Wind Harmer
0.004
972135AH1-637 GEN
Solar/Wind Harmer
1.431
971377AH1-170 GEN
Solar/Wind Harmer
1.683
3147623JAMES R
Solar/Wind Harmer
0.366
972277AH1-723 GEN
Adder
87.353
3151751LOISA D
Adder
8.676
970223AG2-152 GEN
Solar/Wind Harmer
7.908
316045AC1-158 PL2
Solar/Wind Helper
16.699
316006AB2-029 C
Solar/Wind Helper
0.14
NYPJM->LTFIMP_NY
CLTF
3.266
LGEELTFEXP_LGEE->PJM
CLTF
1.371
WECLTFEXP_WEC->PJM
CLTF
0.662
LAGNLTFEXP_LAGN->PJM
CLTF
8.398
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.505
TVALTFEXP_TVA->PJM
CLTF
4.252
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.027
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.441
MECLTFEXP_MEC->PJM
CLTF
3.751
SIGELTFEXP_SIGE->PJM
CLTF
0.114
CPLELTFEXP_CPLE->PJM
CLTF
12.136
CBM West 2LTFEXP_CBM-W2->PJM
CBM
43.163

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 581_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:171.66 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:5528.27
MW Contribution:89.32
Bus #Bus NameTypeMW Contribution
3152261N ANNA2
50/50
20.433
3150861SPRUNCD
50/50
1.238
3143096IRON208
50/50
1.099
3143096IRON208
50/50
1.077
3150801HOPHCF4
50/50
1.448
971211AH1-065 GEN
50/50
1.746
3151161SURRY 1
50/50
9.371
3147666LOUISA
Solar/Wind Harmer
0.585
315839AE2-212 C
Solar/Wind Harmer
0.002
315773AC2-141 GEN
Solar/Wind Harmer
9.03
965281AG1-393 GEN
Solar/Wind Harmer
2.631
315813AE1-149 C
Solar/Wind Harmer
13.098
970133AG2-095 GEN
Solar/Wind Harmer
2.358
970129AG2-093 GEN
Solar/Wind Harmer
14.818
944581AF1-123 GEN
Solar/Wind Harmer
55.15
944601AF1-125 GEN
Solar/Wind Harmer
54.301
315778AD1-151 GEN
Solar/Wind Harmer
19.588
3151101ELIZAR3
Adder
22.703
3144536CHRHLND
Solar/Wind Harmer
0.037
3144873MCLAUGH
Solar/Wind Harmer
0.006
970659AG2-427 GEN
Solar/Wind Harmer
2.585
3145336SMITFLD
Solar/Wind Harmer
0.098
961611AG1-000B GEN
Solar/Wind Harmer
6.513
316083AB2-161 GEN
Solar/Wind Harmer
0.003
3151221GRAVEL6
Adder
17.737
3151171GRAVELC
Adder
3.413
970293AG2-193 GEN
Solar/Wind Harmer
2.6
3142946ENON
Solar/Wind Harmer
0.081
970661AG2-428 GEN
Solar/Wind Harmer
5.15
3142416OLDCHRC
Solar/Wind Harmer
2.354
3144216WINCHST
Adder
0.913
3146456SLIGO L269
Solar/Wind Harmer
0.242
971153AH1-033 GEN
Solar/Wind Harmer
2.796
3150921YORKTN3
Adder
6.079
316382AG1-145 C
Solar/Wind Harmer
0.002
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3142433PROV 92
Adder
0.46
3142433PROV 92
Adder
0.46
3146516WINFALL
Solar/Wind Harmer
0.236
316473AC1-191 GEN
Solar/Wind Harmer
0.795
3146626S HERTFORD
Solar/Wind Harmer
0.235
3145273HOLLAND
Solar/Wind Harmer
0.176
3141843SHACKLE
Adder
1.184
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3141766HARMONY
Solar/Wind Harmer
3.085
316280AD1-041 GEN
Solar/Wind Harmer
0.005
3146376EDENTON
Solar/Wind Harmer
0.23
316156AD2-030 GEN
Solar/Wind Harmer
0.17
3141873WAN 176
Solar/Wind Harmer
4.092
316313AB2-026
Solar/Wind Harmer
0.145
316258AE1-075 C
Solar/Wind Harmer
0.173
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.472
970917AG2-570 GEN
Solar/Wind Harmer
20.3
315614AA2-178 GEN
Solar/Wind Harmer
1.293
3150401LDYSMT4
Adder
30.059
3150371LDYSMT1
Adder
29.045
971157AH1-035 GEN
Solar/Wind Harmer
2.667
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
315737AD1-076 GEN
Solar/Wind Harmer
2.851
316365GEN2_N
Solar/Wind Harmer
0.497
962971AG1-146 GEN
Solar/Wind Harmer
3.533
3146206CASHIE
Solar/Wind Harmer
0.219
3145893MURPHYS
Solar/Wind Harmer
0.367
3145893MURPHYS
Solar/Wind Harmer
0.219
971133AH1-012 GEN
50/50
5.467
944641AF1-129 GEN
50/50
125.042
3142366NRTHEST
50/50
0.853
970533AG2-339 GEN
50/50
21.877
970531AG2-338 GEN
50/50
8.751
3150781HOPHCF2
50/50
0.996
3150791HOPHCF3
50/50
0.996
3150761HOPPOLC
50/50
0.631
971213AH1-066 GEN
50/50
0.873
3150691DARBY 3
50/50
18.729
3150701DARBY 4
50/50
18.685
971223AH1-071 GEN
Solar/Wind Harmer
2.875
3143526WINTERP
Solar/Wind Harmer
1.363
316240AF1-291 C
Solar/Wind Harmer
0.002
3150681DARBY 2
Adder
17.588
3150671DARBY 1
Adder
17.568
3142296MT RD221
Adder
0.779
316033AB2-134 GEN
Solar/Wind Harmer
0.014
315697AD1-025 GEN
Solar/Wind Harmer
0.275
316036AC1-147 C
Solar/Wind Harmer
0.045
3150991CHESPKB
Adder
2.56
3150991CHESPKB
Adder
2.499
316236AE1-162_GEN
Solar/Wind Harmer
0.002
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.234
316185AD1-033 GEN
Solar/Wind Harmer
0.007
970657AG2-426 GEN
Solar/Wind Harmer
8.541
970657AG2-426 GEN
Solar/Wind Harmer
1.79
3142946ENON
Solar/Wind Harmer
0.024
3145506HICKORY
Solar/Wind Harmer
0.973
3145506HICKORY
Solar/Wind Harmer
0.584
3145506HICKORY
Solar/Wind Harmer
0.146
316339AD2-160 GEN
Solar/Wind Harmer
0.393
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
316017AA1-139 ULT1
Solar/Wind Harmer
0.135
316075AC2-137 C
Solar/Wind Harmer
0.066
3137176SLIGO L2192
Solar/Wind Harmer
0.963
3146456SLIGO L269
Solar/Wind Harmer
4.28
3130086AYDLETT
Solar/Wind Harmer
0.966
972185AH1-677 GEN
Adder
13.452
3144356SAPONY
Solar/Wind Harmer
2.004
3146386ELIZ CT
Solar/Wind Harmer
0.239
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
972187AH1-678 GEN
Adder
6.746
3146516WINFALL
Solar/Wind Harmer
0.236
3146516WINFALL
Solar/Wind Harmer
0.236
3146516WINFALL
Solar/Wind Harmer
0.236
966871AG1-558 GEN
Solar/Wind Harmer
0.272
3146626S HERTFORD
Solar/Wind Harmer
0.235
3146626S HERTFORD
Solar/Wind Harmer
0.235
316303AF2-085
50/50
4.791
971285AH1-108 GEN
50/50
2.026
970603AG2-384 GEN
50/50
5.274
316233AE1-074 FULL
Solar/Wind Harmer
0.21
971281AH1-106 GEN
Solar/Wind Harmer
3.638
971283AH1-107 GEN
Solar/Wind Harmer
3.638
3143316POE
Solar/Wind Harmer
0.98
941031AE2-094 GEN
Solar/Wind Harmer
45.33
944011AF1-069 GEN
Solar/Wind Harmer
14.811
316132AB2-190 GEN1
Solar/Wind Harmer
1.315
316369SG1_INVT
Solar/Wind Harmer
0.009
3151081ELIZAR1
Adder
22.416
3151091ELIZAR2
Adder
22.027
3152611GOSPORTB
Adder
3.112
3152621GOSPORTC
Adder
2.641
3152601GOSPORTA
Adder
2.437
971445AH1-216 GEN
Solar/Wind Harmer
17.191
972265AH1-717 GEN
Adder
18.943
3151201GRAVEL4
Adder
17.758
3151191GRAVEL3
Adder
17.533
3151211GRAVEL5
Adder
17.533
316312AB1-027
Solar/Wind Harmer
0.435
3152251N ANNA1
50/50
20.435
970119AG2-088 GEN
50/50
35.934
3150851SPRUNCC
50/50
1.238
3143096IRON208
50/50
1.099
3152331SURRY 2
50/50
10.173
3150771HOPHCF1
50/50
0.996
3143226MDLTHAN
Solar/Wind Harmer
0.269
3143526WINTERP
Solar/Wind Harmer
1.363
3147666LOUISA
Solar/Wind Harmer
1.017
940641AE2-051 GEN
Solar/Wind Harmer
20.264
939411AE1-173 GEN
Solar/Wind Harmer
107.071
3142543TWELFTH
Solar/Wind Harmer
0.024
316192AB2-158 GEN
Solar/Wind Harmer
1.397
316294AC1-161 GEN
Solar/Wind Harmer
4.284
315671AE2-027_GEN
Solar/Wind Harmer
15.779
970129AG2-093 GEN
Solar/Wind Harmer
6.973
316458AB2-190 GEN2
Solar/Wind Harmer
1.315
944591AF1-124 GEN
Solar/Wind Harmer
55.346
971069AG2-661 GEN
Solar/Wind Harmer
4.353
944631AF1-128 GEN
Adder
116.602
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
3.052
971647AH1-324 GEN
Solar/Wind Harmer
10.43
970659AG2-427 GEN
Solar/Wind Harmer
11.815
3145336SMITFLD
Solar/Wind Harmer
0.976
961611AG1-000B GEN
Solar/Wind Harmer
12.808
316381AD1-082 GEN
Solar/Wind Harmer
0.254
3151171GRAVELC
Adder
2.595
970661AG2-428 GEN
Solar/Wind Harmer
24.214
3142416OLDCHRC
Solar/Wind Harmer
0.631
3142416OLDCHRC
Solar/Wind Harmer
0.242
316388AE2-253 GEN
Solar/Wind Harmer
0.76
3138126ROCKLANDING
Solar/Wind Harmer
0.111
3146456SLIGO L269
Solar/Wind Harmer
0.242
316072AD1-144
Solar/Wind Harmer
0.088
316159AE1-175 C
Solar/Wind Harmer
0.209
316246AF1-032 C
Solar/Wind Harmer
0.109
971317AH1-138 GEN
Solar/Wind Harmer
1.796
316093AE2-104_GEN
Solar/Wind Harmer
4.042
3142433PROV 92
Solar/Wind Harmer
0.947
3142433PROV 92
Adder
0.46
3142433PROV 92
Adder
0.46
3146516WINFALL
Solar/Wind Harmer
0.766
3146516WINFALL
Solar/Wind Harmer
0.236
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
971777AH1-397 GEN
Solar/Wind Harmer
0.612
3141843SHACKLE
Adder
1.184
3141766HARMONY
Solar/Wind Harmer
0.046
966881AG1-559 GEN
Solar/Wind Harmer
0.267
3130156CHOWAN
Solar/Wind Harmer
0.23
3143336POWHATN
Solar/Wind Harmer
4.084
970919AG2-571 GEN
Solar/Wind Harmer
8.12
970087AG2-069 GEN
Solar/Wind Harmer
18.195
3138133OCRAN
Solar/Wind Harmer
0.136
3145663CRESWEL
Solar/Wind Harmer
0.632
971163AH1-040 GEN
Solar/Wind Harmer
18.07
972197AH1-683 GEN
Adder
4.694
972219AH1-694 GEN
Adder
3.38
316023GEN1_S
Solar/Wind Harmer
0.497
3146206CASHIE
Solar/Wind Harmer
0.219
971547AH1-271 GEN
Solar/Wind Harmer
4.683
316336AC2-165 C
Solar/Wind Harmer
0.009
3145893MURPHYS
Solar/Wind Harmer
0.876
3145893MURPHYS
Solar/Wind Harmer
0.974
957481AF2-042 GEN
Solar/Wind Harmer
58.056
3146173TUNIS
Solar/Wind Harmer
0.217
962861AG1-135 GEN
Solar/Wind Harmer
6.917
960081AF2-299 GEN
Solar/Wind Harmer
2.073
3145683EARLEYS
Solar/Wind Harmer
0.215
3146263WOODLND
Solar/Wind Harmer
0.214
315693AD1-088 GEN
Solar/Wind Harmer
10.231
962491AG1-098 GEN
Solar/Wind Harmer
12.124
316011AB1-132 GEN
Solar/Wind Harmer
3.856
962571AG1-106 GEN
Solar/Wind Harmer
3.018
3141726DUNNSVL
Solar/Wind Harmer
0.847
3145963POPLR C
Solar/Wind Harmer
0.211
971795AH1-408 GEN
Solar/Wind Harmer
14.105
316190AA2-174 GEN
Solar/Wind Harmer
0
3145823KELFORD
Solar/Wind Harmer
0.211
316174AB2-169 GEN
Solar/Wind Harmer
0.006
3147043LAWRENC
Adder
1.896
3145783HORNRTN
Solar/Wind Harmer
0.209
3150351NORNECKC2
Adder
2.084
3145796HORNRTN
Solar/Wind Harmer
0.689
3145796HORNRTN
Solar/Wind Harmer
0.209
316212AC1-099_GEN
Solar/Wind Harmer
1.054
3146293MARTNCO
Solar/Wind Harmer
0.188
316129AC1-054 GEN
Solar/Wind Harmer
0.758
971065AG2-659 GEN
Solar/Wind Harmer
8.56
316337AD2-073 GEN
Solar/Wind Harmer
0.173
3145746EVERETS
Solar/Wind Harmer
0.199
3145746EVERETS
Solar/Wind Harmer
0.199
315722AD1-056 GEN
Solar/Wind Harmer
1.256
315687AD1-152 GEN
Solar/Wind Harmer
0.006
316494AC1-189 GEN
Solar/Wind Harmer
0.661
316237AB2-079_GEN
Solar/Wind Harmer
0.002
3146233WITAKRS
Solar/Wind Harmer
0.769
961671AG1-007 GEN
Solar/Wind Harmer
0.03
3146083TARBORO
Solar/Wind Harmer
0.193
3145493TOT1
Solar/Wind Harmer
0.859
970685AG2-442 GEN
Solar/Wind Harmer
14.419
970937AG2-583 GEN
Solar/Wind Harmer
11.813
963171AG1-166 GEN
Solar/Wind Harmer
1.027
971563AH1-280 GEN
Solar/Wind Harmer
2.054
3144293JTRSVLE
Adder
0.613
3146926FARMVIL
Solar/Wind Harmer
0.114
3145543BTLEBRO
Solar/Wind Harmer
0.19
3145543BTLEBRO
Solar/Wind Harmer
0.152
316359AB2-059 GEN
Solar/Wind Harmer
0.682
316049AB1-081 GEN
Solar/Wind Harmer
1.086
3142053HEARTS
Solar/Wind Harmer
0.334
970401AG2-262 GEN
Solar/Wind Harmer
1.086
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.072
972003AH1-546 GEN
Solar/Wind Harmer
7.307
972135AH1-637 GEN
Solar/Wind Harmer
1.466
316003AC1-222 GEN
Solar/Wind Harmer
0.005
971377AH1-170 GEN
Solar/Wind Harmer
1.697
3147623JAMES R
Solar/Wind Harmer
0.369
972277AH1-723 GEN
Adder
89.316
3151751LOISA D
Adder
8.255
970223AG2-152 GEN
Solar/Wind Harmer
8.023
316045AC1-158 PL2
Solar/Wind Helper
16.818
316006AB2-029 C
Solar/Wind Helper
0.152
316254AC1-120 GEN1
Solar/Wind Helper
1.388
957871AF2-081 GEN
Solar/Wind Harmer
12.066
970673AG2-436 GEN
Solar/Wind Harmer
51.597
970673AG2-436 GEN
Solar/Wind Harmer
34.398
319010AE1-072 C
Solar/Wind Harmer
1.218
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.166
316311AC2-079 GEN
Solar/Wind Harmer
6.941
3146406KITTY HAWK
Solar/Wind Harmer
0.03
316305AF2-043 C
Solar/Wind Harmer
0.002
315976AC1-164 GENA
Solar/Wind Harmer
24.95
316169AC1-164_GENC
Solar/Wind Harmer
21.555
315975AC1-164 GENB
Solar/Wind Harmer
0.738
315835AF2-110_GEN
Solar/Wind Harmer
1.649
316315AB2-025 C
Solar/Wind Harmer
0.194
313526AB2-022
Solar/Wind Harmer
0.13
972189AH1-679 GEN
Adder
4.009
3146486SUNBURY
Solar/Wind Harmer
0.239
3146486SUNBURY
Solar/Wind Harmer
0.239
971967AH1-528 GEN
Solar/Wind Harmer
38.202
315814AE2-033 C
Solar/Wind Harmer
18.884
316321Z2-027
Solar/Wind Harmer
0.044
3146396TANGLEW
Solar/Wind Harmer
0.658
3145176PASQUOTANK
Solar/Wind Harmer
0.148
971167AH1-042 GEN
Solar/Wind Harmer
21.1
3142433PROV 92
Adder
0.46
3142433PROV 92
Adder
0.46
3138283WHITEMARSH
Solar/Wind Harmer
0.055
3143873LANEXA
Solar/Wind Harmer
0.14
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
316314AB2-024 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
6.866
316059AD1-063 C
Solar/Wind Harmer
0.001
315662AE1-191 GEN
Solar/Wind Harmer
0.008
315666AE1-190 GEN
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.23
3130156CHOWAN
Solar/Wind Harmer
0.23
3141873WAN 176
Solar/Wind Harmer
0.046
970085AG2-068 GEN
Solar/Wind Harmer
12.13
970581AG2-369 GEN
Solar/Wind Harmer
10.432
3141913WHIT STONE
Solar/Wind Harmer
0.227
3138133OCRAN
Solar/Wind Harmer
0.068
315816AE2-034 GEN
Solar/Wind Harmer
0.969
3141783LANCAST
Solar/Wind Harmer
0.135
3141783LANCAST
Solar/Wind Harmer
0.09
3150411LDYSMT5
Adder
30.153
3150381LDYSMT2
Adder
28.858
972213AH1-691 GEN
Adder
4.882
972215AH1-692 GEN
Adder
4.882
3130546PLYMOUTH
Solar/Wind Harmer
0.222
315732AD1-074 GEN1
Solar/Wind Harmer
1.273
315733AD1-074 GEN2
Solar/Wind Harmer
1.273
315735AD1-075 GEN1
Solar/Wind Harmer
0.637
965291AG1-394 GEN
Solar/Wind Harmer
0.982
962981AG1-147 GEN
Solar/Wind Harmer
8.243
3146206CASHIE
Solar/Wind Harmer
0.219
970601AG2-382 GEN
Solar/Wind Harmer
8.195
3145893MURPHYS
Solar/Wind Harmer
0.591
3145893MURPHYS
Solar/Wind Harmer
0.219
970327AG2-215 GEN
Solar/Wind Harmer
7.177
3145513AHOSKIE
Solar/Wind Harmer
0.452
3145513AHOSKIE
Solar/Wind Harmer
0.216
3146043SEABORD
Solar/Wind Harmer
0.215
3145683EARLEYS
Solar/Wind Harmer
0.43
3145683EARLEYS
Solar/Wind Harmer
0.215
3145683EARLEYS
Solar/Wind Harmer
0.215
315607AA1-063A GEN
Solar/Wind Harmer
0.438
316087AB2-174 GEN
Solar/Wind Harmer
0.006
315652AC1-086 GEN
Solar/Wind Harmer
23.331
3137643SOCKMAN
Solar/Wind Harmer
0.845
3141813NORNECK
Solar/Wind Harmer
0.209
3145796HORNRTN
Solar/Wind Harmer
0.668
3145796HORNRTN
Solar/Wind Harmer
0.084
3146033SCOT NK
Solar/Wind Harmer
0.828
970831AG2-522 GEN
Solar/Wind Harmer
8.631
316005AA1-067
Solar/Wind Harmer
0.213
3145746EVERETS
Solar/Wind Harmer
0.791
3145746EVERETS
Solar/Wind Harmer
0.199
3145746EVERETS
Solar/Wind Harmer
0.199
3145746EVERETS
Solar/Wind Harmer
0.199
970181AG2-120 GEN
Solar/Wind Harmer
2.475
957861AF2-080 GEN
Solar/Wind Harmer
8.442
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316420AA1-050 GEN
Solar/Wind Harmer
0.006
971443AH1-215 GEN
Solar/Wind Harmer
3.255
3144303KENBRDG
Solar/Wind Harmer
0.155
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.193
3145573BETHELC
Solar/Wind Harmer
0.193
970683AG2-441 GEN
Solar/Wind Harmer
12.874
970681AG2-440 GEN
Solar/Wind Harmer
10.299
946301AF1-294 GEN
Solar/Wind Harmer
3.8
961791AG1-021 GEN
Solar/Wind Harmer
1.849
315657AE1-056 GEN
Solar/Wind Harmer
6.628
316223AC1-118
Solar/Wind Harmer
0.135
970285AG2-188 GEN
Solar/Wind Harmer
14.487
971845AH1-439 GEN
Solar/Wind Harmer
8.236
316118AC1-105 GEN
Solar/Wind Harmer
0.469
3147173SINAI
Solar/Wind Harmer
0.178
3147243WELCO
Solar/Wind Harmer
0.111
972205AH1-687 GEN
Adder
7.261
944491AF1-114 GEN
Solar/Wind Harmer
0.001
970865AG2-541 GEN
Solar/Wind Harmer
5.471
971447AH1-217 GEN
Solar/Wind Harmer
4.69
972193AH1-681 GEN
Adder
3.425
316123AC1-075 GEN
Solar/Wind Harmer
0.197
970165AG2-112 GEN
Solar/Wind Harmer
1.171
970163AG2-111 GEN
Solar/Wind Harmer
1.117
270494AE1-108_GEN
Solar/Wind Harmer
1.686
3147346CASHSCORNER
Solar/Wind Harmer
0.279
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316164AC1-076 GEN
Solar/Wind Helper
2.196
316411AF1-147_GEN1
Solar/Wind Helper
0.801
316415AF1-147_GEN2
Solar/Wind Helper
0.801
3138216PACIFIC
Solar/Wind Helper
0.039
970933AG2-581 GEN
Solar/Wind Harmer
18.633
315742AE1-103 GEN
Solar/Wind Harmer
0.003
957411AF2-035 GEN
Solar/Wind Harmer
9.864
970317AG2-208 GEN
Solar/Wind Harmer
9.139
3146376EDENTON
Solar/Wind Harmer
1.025
3146376EDENTON
Solar/Wind Harmer
1.025
315673AE1-157 GEN
Solar/Wind Harmer
15.809
3150391LDYSMT3
Adder
30.003
972195AH1-682 GEN
Adder
3.943
316065AD1-022 GEN
Solar/Wind Harmer
10.141
3145893MURPHYS
Solar/Wind Harmer
1.466
3145893MURPHYS
Solar/Wind Harmer
0.394
970099AG2-077 GEN
Solar/Wind Harmer
23.222
3146173TUNIS
Solar/Wind Harmer
0.217
3146173TUNIS
Solar/Wind Harmer
0.217
958261AF2-120 GEN
Solar/Wind Harmer
7.118
316181AB2-040 GEN
Solar/Wind Harmer
0.309
3142666NORTHAMPTON
Solar/Wind Harmer
0.212
3142666NORTHAMPTON
Solar/Wind Harmer
0.212
3142666NORTHAMPTON
Solar/Wind Harmer
0.212
3142666NORTHAMPTON
Solar/Wind Harmer
0.128
316426AA2-053 GEN
Solar/Wind Harmer
0.713
3145593CAROLNA
Solar/Wind Harmer
0.21
3145593CAROLNA
Solar/Wind Harmer
0.21
966811AG1-552 GEN
Solar/Wind Harmer
2.282
3145593CAROLNA
Solar/Wind Harmer
0.262
3145783HORNRTN
Solar/Wind Harmer
3.718
3145783HORNRTN
Solar/Wind Harmer
2.974
3145783HORNRTN
Solar/Wind Harmer
0.93
3145783HORNRTN
Solar/Wind Harmer
0.372
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.19
3150341NORNECKC1
Adder
2.172
3145796HORNRTN
Solar/Wind Harmer
0.626
3145933PARMELE
Solar/Wind Harmer
0.406
3145933PARMELE
Solar/Wind Harmer
0.203
971741AH1-377 GEN
Solar/Wind Harmer
20.122
316274AC1-208 GEN
Solar/Wind Harmer
1.051
316468AD1-105 GEN
Solar/Wind Harmer
-0.066
970301AG2-198 GEN
Solar/Wind Harmer
8.524
939181AE1-148 GEN
Solar/Wind Harmer
9.423
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.014
970323AG2-213 GEN
Solar/Wind Harmer
8.264
971775AH1-396 GEN
Solar/Wind Harmer
0.31
3145493TOT1
Solar/Wind Harmer
0.448
3145453TOT5
Solar/Wind Harmer
0.269
3145603CNETO
Solar/Wind Harmer
0.179
958211AF2-115 GEN
Solar/Wind Harmer
2.311
963191AG1-168 GEN
Solar/Wind Harmer
0.77
3144293JTRSVLE
Adder
0.613
3144293JTRSVLE
Adder
0.516
3147133PAMPLIN
Solar/Wind Harmer
0.192
3147133PAMPLIN
Solar/Wind Harmer
0.154
961601AG1-000A GEN
Solar/Wind Harmer
3.377
316263AC1-034 GEN
Solar/Wind Harmer
7.215
962561AG1-105 GEN
Solar/Wind Harmer
8.959
964791AG1-342 GEN
Solar/Wind Harmer
3.555
3146843MT LREL
Solar/Wind Harmer
0.185
3146843MT LREL
Solar/Wind Harmer
0.185
3146776BUCKING
Solar/Wind Harmer
0.723
3146776BUCKING
Solar/Wind Harmer
0.059
316222AC1-221 GEN
Solar/Wind Harmer
0.67
971489AH1-241 GEN
Solar/Wind Harmer
8.483
942751AE2-291 GEN
Solar/Wind Harmer
7.393
315821AE2-092 GEN
Solar/Wind Harmer
0.008
3151731LOISA B
Adder
8.255
3151721LOISA A
Adder
8.212
316447AC1-158 HLD
Solar/Wind Helper
11.564
315651AD1-115 GEN
Solar/Wind Helper
1.026
970009AG2-005 GEN
Solar/Wind Harmer
1.633
957521AF2-046 GEN
Solar/Wind Harmer
16.257
961681AG1-008 GEN
Solar/Wind Harmer
16.257
3146173TUNIS
Solar/Wind Harmer
0.217
3156021HOLLOMANSOL
Solar/Wind Harmer
0.983
316463AE2-346 GEN
Solar/Wind Harmer
0.186
316140AB2-099
Solar/Wind Harmer
0.077
962331AG1-082 GEN
Solar/Wind Harmer
2.305
316404AE1-155 C
Solar/Wind Harmer
0.048
3146263WOODLND
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.659
3142666NORTHAMPTON
Solar/Wind Harmer
0.212
3145963POPLR C
Solar/Wind Harmer
0.211
316317KELFORD C
Solar/Wind Harmer
0.02
3145823KELFORD
Solar/Wind Harmer
0.211
3147043LAWRENC
Solar/Wind Harmer
0.126
316478AD1-087 GEN
Solar/Wind Harmer
0.731
316486AD2-202 GEN
Solar/Wind Harmer
0.215
3150351NORNECKC2
Adder
2.12
3145796HORNRTN
Solar/Wind Harmer
0.835
3145796HORNRTN
Solar/Wind Harmer
0.209
316210AC1-098 GEN
Solar/Wind Harmer
1.891
3145933PARMELE
Solar/Wind Harmer
0.203
966801AG1-551 GEN
Solar/Wind Harmer
2.363
971781AH1-399 GEN
Solar/Wind Harmer
0.266
970909AG2-566 GEN
Solar/Wind Harmer
2.131
3145746EVERETS
Solar/Wind Harmer
0.199
3145746EVERETS
Solar/Wind Harmer
0.199
315724AD1-057 GEN
Solar/Wind Harmer
0.745
316327AA2-057 GEN
Solar/Wind Harmer
0.297
316131AB2-060 GEN
Solar/Wind Harmer
0.613
964241AG1-285 GEN
Solar/Wind Harmer
12.969
315785AD2-033 C
Solar/Wind Harmer
1.576
970257AG2-171 GEN
Solar/Wind Harmer
6.198
959311AF2-222 GEN
Solar/Wind Harmer
17.202
3146233WITAKRS
Solar/Wind Harmer
0.97
3146233WITAKRS
Solar/Wind Harmer
0.131
3146073TAR RVR
Solar/Wind Harmer
0.193
3146083TARBORO
Solar/Wind Harmer
0.193
3138543CONSLDL
Solar/Wind Harmer
0.127
963181AG1-167 GEN
Solar/Wind Harmer
0.77
3144293JTRSVLE
Adder
0.613
3147133PAMPLIN
Solar/Wind Harmer
0.603
971193AH1-056 GEN
Solar/Wind Harmer
11.702
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
961601AG1-000A GEN
Solar/Wind Harmer
13.507
3146926FARMVIL
Solar/Wind Harmer
0.114
3145543BTLEBRO
Solar/Wind Harmer
0.19
3145543BTLEBRO
Solar/Wind Harmer
0.19
971623AH1-311 GEN
Solar/Wind Harmer
0.38
3141906WESTMOR
Solar/Wind Harmer
0.075
3146776BUCKING
Solar/Wind Harmer
0.065
970737AG2-469 GEN
Solar/Wind Harmer
7.61
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.598
971683AH1-343 GEN
Solar/Wind Harmer
6.05
316283AC2-100 C
Solar/Wind Harmer
0.314
970221AG2-151 GEN
Solar/Wind Harmer
8.483
972255AH1-712 GEN
Adder
76.646
3151761LOISA E
Adder
16.829
3141316ARNOLDS
Adder
0.299
972183AH1-676 GEN
Adder
129.168
3150331BIRCHWDA
Adder
19.249
316044AC1-158 PL1
Solar/Wind Helper
5.254
316450AC1-158 RIC
Solar/Wind Helper
1.401
316170AC1-121 GEN2
Solar/Wind Helper
0.463
3141196NOKESVL
Solar/Wind Helper
1.151
NYPJM->LTFIMP_NY
CLTF
3.309
LGEELTFEXP_LGEE->PJM
CLTF
1.392
WECLTFEXP_WEC->PJM
CLTF
0.673
LAGNLTFEXP_LAGN->PJM
CLTF
8.524
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.899
TVALTFEXP_TVA->PJM
CLTF
4.316
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.369
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.657
MECLTFEXP_MEC->PJM
CLTF
3.808
SIGELTFEXP_SIGE->PJM
CLTF
0.116
CPLELTFEXP_CPLE->PJM
CLTF
12.317
CBM West 2LTFEXP_CBM-W2->PJM
CBM
43.813

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T581_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T581_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:150.52 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:5930.65
MW Contribution:89.64
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
4.782
971285AH1-108 GEN
50/50
2.017
970603AG2-384 GEN
50/50
5.251
972263AH1-716 GEN
50/50
141.451
316233AE1-074 FULL
Solar/Wind Harmer
0.79
971281AH1-106 GEN
Solar/Wind Harmer
4.774
971283AH1-107 GEN
Solar/Wind Harmer
4.774
3143316POE
Solar/Wind Harmer
-0.109
941031AE2-094 GEN
Solar/Wind Harmer
51.844
944011AF1-069 GEN
Solar/Wind Harmer
16.245
3151081ELIZAR1
Adder
22.389
3151091ELIZAR2
Adder
22
316132AB2-190 GEN1
Solar/Wind Harmer
2.776
3152611GOSPORTB
Adder
3.108
3152621GOSPORTC
Adder
2.638
3152601GOSPORTA
Adder
2.434
316369SG1_INVT
Solar/Wind Harmer
4.896
971445AH1-216 GEN
Solar/Wind Harmer
16.942
972265AH1-717 GEN
Adder
18.896
3151201GRAVEL4
Adder
17.714
3151191GRAVEL3
Adder
17.489
3151211GRAVEL5
Adder
17.489
957871AF2-081 GEN
Solar/Wind Harmer
13.602
970673AG2-436 GEN
Solar/Wind Harmer
57.084
970673AG2-436 GEN
Solar/Wind Harmer
28.903
319010AE1-072 C
Solar/Wind Harmer
5.488
3146406KITTY HAWK
Solar/Wind Harmer
0.023
315833AF1-017_GEN
Solar/Wind Harmer
5.15
316349AD2-085 GEN
Solar/Wind Harmer
2.412
316311AC2-079 GEN
Solar/Wind Harmer
13.676
316305AF2-043 C
Solar/Wind Harmer
0.817
316312AB1-027
Solar/Wind Harmer
0.914
315835AF2-110_GEN
Solar/Wind Harmer
3.371
315976AC1-164 GENA
Solar/Wind Harmer
28.429
316169AC1-164_GENC
Solar/Wind Harmer
24.56
315975AC1-164 GENB
Solar/Wind Harmer
0.841
313526AB2-022
Solar/Wind Harmer
0.725
316315AB2-025 C
Solar/Wind Harmer
0.725
971967AH1-528 GEN
Solar/Wind Harmer
50.429
3146486SUNBURY
Solar/Wind Harmer
-0.027
3146486SUNBURY
Solar/Wind Harmer
-0.027
315814AE2-033 C
Solar/Wind Harmer
24.939
316321Z2-027
Solar/Wind Harmer
0.722
3146396TANGLEW
Solar/Wind Harmer
0.493
3145176PASQUOTANK
Solar/Wind Harmer
-0.017
971167AH1-042 GEN
Solar/Wind Harmer
25.534
3142433PROV 92
Adder
0.457
3142433PROV 92
Adder
0.457
957831AF2-077 GEN
Solar/Wind Harmer
0.794
3138283WHITEMARSH
Solar/Wind Harmer
0.041
315611Z1-036_GEN2
Solar/Wind Harmer
6.468
3143873LANEXA
Solar/Wind Harmer
-0.015
972189AH1-679 GEN
Adder
3.879
316314AB2-024 C
Solar/Wind Harmer
2.214
3130156CHOWAN
Solar/Wind Harmer
-0.026
3130156CHOWAN
Solar/Wind Harmer
-0.026
316059AD1-063 C
Solar/Wind Harmer
0.583
315662AE1-191 GEN
Solar/Wind Harmer
3.107
315666AE1-190 GEN
Solar/Wind Harmer
0.777
957601AF2-054 GEN
Solar/Wind Harmer
0.768
3141873WAN 176
Solar/Wind Harmer
-0.005
970085AG2-068 GEN
Solar/Wind Harmer
15.97
970581AG2-369 GEN
Solar/Wind Harmer
13.734
315816AE2-034 GEN
Solar/Wind Harmer
2.051
3141913WHIT STONE
Solar/Wind Harmer
-0.025
3138133OCRAN
Solar/Wind Harmer
-0.008
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
3130546PLYMOUTH
Solar/Wind Harmer
-0.025
315732AD1-074 GEN1
Solar/Wind Harmer
5.029
315733AD1-074 GEN2
Solar/Wind Harmer
5.029
315735AD1-075 GEN1
Solar/Wind Harmer
2.515
965291AG1-394 GEN
Solar/Wind Harmer
2.201
3146206CASHIE
Solar/Wind Harmer
-0.025
970601AG2-382 GEN
Solar/Wind Harmer
10.779
316318V4-068
Solar/Wind Harmer
0.613
3145893MURPHYS
Solar/Wind Harmer
-0.066
3145893MURPHYS
Solar/Wind Harmer
-0.025
962981AG1-147 GEN
Solar/Wind Harmer
10.738
3145513AHOSKIE
Solar/Wind Harmer
0.211
961941AG1-037 GEN
Solar/Wind Harmer
0.182
3145513AHOSKIE
Solar/Wind Harmer
-0.024
946281AF1-292 GEN
Solar/Wind Harmer
0.543
3146043SEABORD
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.048
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
315607AA1-063A GEN
Solar/Wind Harmer
2.433
316087AB2-174 GEN
Solar/Wind Harmer
3.429
315652AC1-086 GEN
Solar/Wind Harmer
26.795
3137643SOCKMAN
Solar/Wind Harmer
-0.094
3145796HORNRTN
Solar/Wind Harmer
-0.075
3145796HORNRTN
Solar/Wind Harmer
-0.009
3146033SCOT NK
Solar/Wind Harmer
-0.093
3141813NORNECK
Solar/Wind Harmer
-0.023
3150411LDYSMT5
Adder
26.823
3150381LDYSMT2
Adder
25.67
972213AH1-691 GEN
Adder
4.342
972215AH1-692 GEN
Adder
4.342
972205AH1-687 GEN
Adder
7.266
972193AH1-681 GEN
Adder
3.437
316164AC1-076 GEN
Solar/Wind Helper
2.187
316411AF1-147_GEN1
Solar/Wind Helper
0.802
316415AF1-147_GEN2
Solar/Wind Helper
0.802
3138216PACIFIC
Solar/Wind Helper
0.039
971133AH1-012 GEN
50/50
5.498
944641AF1-129 GEN
50/50
124.495
970533AG2-339 GEN
50/50
21.875
970531AG2-338 GEN
50/50
8.75
3150781HOPHCF2
50/50
0.992
3150791HOPHCF3
50/50
0.992
3150761HOPPOLC
50/50
0.629
971213AH1-066 GEN
50/50
0.87
3142366NRTHEST
50/50
0.848
971223AH1-071 GEN
Solar/Wind Harmer
3.778
3143526WINTERP
Solar/Wind Harmer
-0.152
316240AF1-291 C
Solar/Wind Harmer
0.834
316036AC1-147 C
Solar/Wind Harmer
0.74
3150991CHESPKB
Adder
2.557
3150991CHESPKB
Adder
2.496
316033AB2-134 GEN
Solar/Wind Harmer
8.837
315697AD1-025 GEN
Solar/Wind Harmer
5.542
316316AC1-027 C
Solar/Wind Harmer
0.841
3142956BIRDNECK
Solar/Wind Harmer
1.47
316236AE1-162_GEN
Solar/Wind Harmer
0.825
3150691DARBY 3
Adder
17.538
3150701DARBY 4
Adder
17.497
3150681DARBY 2
Adder
17.476
3150671DARBY 1
Adder
17.456
316185AD1-033 GEN
Solar/Wind Harmer
2.888
970657AG2-426 GEN
Solar/Wind Harmer
8.542
970657AG2-426 GEN
Solar/Wind Harmer
1.786
3145506HICKORY
Solar/Wind Harmer
-0.109
3145506HICKORY
Solar/Wind Harmer
-0.065
3145506HICKORY
Solar/Wind Harmer
-0.016
3142296MT RD221
Adder
0.773
316339AD2-160 GEN
Solar/Wind Harmer
1.836
3142946ENON
Solar/Wind Harmer
-0.003
316018AA1-139 ULT2
Solar/Wind Harmer
2.33
316017AA1-139 ULT1
Solar/Wind Harmer
2.201
3137176SLIGO L2192
Solar/Wind Harmer
-0.107
3146456SLIGO L269
Solar/Wind Harmer
3.207
3130086AYDLETT
Solar/Wind Harmer
-0.108
316075AC2-137 C
Solar/Wind Harmer
0.73
972185AH1-677 GEN
Adder
13.451
3146386ELIZ CT
Solar/Wind Harmer
-0.027
3144356SAPONY
Solar/Wind Harmer
0.938
316431W1029_GEN1
Solar/Wind Harmer
4.824
316433W1029_GEN2
Solar/Wind Harmer
4.824
972187AH1-678 GEN
Adder
6.746
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
970933AG2-581 GEN
Solar/Wind Harmer
24.532
966871AG1-558 GEN
Solar/Wind Harmer
0.787
966871AG1-558 GEN
Solar/Wind Harmer
0.269
315742AE1-103 GEN
Solar/Wind Harmer
2.721
3146376EDENTON
Solar/Wind Harmer
0.768
3146376EDENTON
Solar/Wind Harmer
0.768
316441AF1-014 GEN
Solar/Wind Harmer
1.742
316065AD1-022 GEN
Solar/Wind Harmer
12.361
3145893MURPHYS
Solar/Wind Harmer
0.686
3145893MURPHYS
Solar/Wind Harmer
-0.044
970099AG2-077 GEN
Solar/Wind Harmer
30.574
3146173TUNIS
Solar/Wind Harmer
-0.024
3146173TUNIS
Solar/Wind Harmer
-0.024
316487AF1-042 GEN
Solar/Wind Harmer
3.2
957411AF2-035 GEN
Solar/Wind Harmer
10.838
970317AG2-208 GEN
Solar/Wind Harmer
10.537
316181AB2-040 GEN
Solar/Wind Harmer
3.34
958261AF2-120 GEN
Solar/Wind Harmer
9.253
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
316426AA2-053 GEN
Solar/Wind Harmer
2.396
3145593CAROLNA
Solar/Wind Harmer
-0.024
3145593CAROLNA
Solar/Wind Harmer
-0.024
966811AG1-552 GEN
Solar/Wind Harmer
2.657
3145593CAROLNA
Solar/Wind Harmer
0.196
3145783HORNRTN
Solar/Wind Harmer
2.786
3145783HORNRTN
Solar/Wind Harmer
2.229
3145783HORNRTN
Solar/Wind Harmer
0.697
3145783HORNRTN
Solar/Wind Harmer
0.279
315673AE1-157 GEN
Solar/Wind Harmer
17.6
3145796HORNRTN
Solar/Wind Harmer
-0.07
316077AC2-138 C
Solar/Wind Harmer
0.488
3150341NORNECKC1
Adder
2.157
3150341NORNECKC1
Adder
2.139
3150391LDYSMT3
Adder
26.689
972195AH1-682 GEN
Adder
3.507
3144293JTRSVLE
Adder
0.613
3144293JTRSVLE
Adder
0.516
3151731LOISA B
Adder
8.322
3151721LOISA A
Adder
8.279
316447AC1-158 HLD
Solar/Wind Helper
11.529
315651AD1-115 GEN
Solar/Wind Helper
1.021
971741AH1-377 GEN
Solar/Wind Harmer
12.626
3152261N ANNA2
50/50
20.538
3150861SPRUNCD
50/50
1.233
3143096IRON208
50/50
1.093
3143096IRON208
50/50
1.071
3150801HOPHCF4
50/50
1.442
971211AH1-065 GEN
50/50
1.739
3151101ELIZAR3
50/50
24.061
3151161SURRY 1
50/50
9.348
3147666LOUISA
Solar/Wind Harmer
-0.066
315773AC2-141 GEN
Solar/Wind Harmer
11.614
315839AE2-212 C
Solar/Wind Harmer
0.835
965281AG1-393 GEN
Solar/Wind Harmer
3.451
315813AE1-149 C
Solar/Wind Harmer
17.198
944581AF1-123 GEN
Solar/Wind Harmer
125.059
944601AF1-125 GEN
Solar/Wind Harmer
123.108
970133AG2-095 GEN
Solar/Wind Harmer
3.091
970129AG2-093 GEN
Solar/Wind Harmer
15.452
3144536CHRHLND
Solar/Wind Harmer
-0.004
3144873MCLAUGH
Solar/Wind Harmer
-0.001
315778AD1-151 GEN
Solar/Wind Harmer
23.752
970659AG2-427 GEN
Solar/Wind Harmer
2.578
3145336SMITFLD
Solar/Wind Harmer
-0.011
961611AG1-000B GEN
Solar/Wind Harmer
5.762
316083AB2-161 GEN
Solar/Wind Harmer
4.441
3151221GRAVEL6
Adder
17.693
3151171GRAVELC
Adder
3.404
970661AG2-428 GEN
Solar/Wind Harmer
5.139
3142946ENON
Solar/Wind Harmer
-0.009
970293AG2-193 GEN
Solar/Wind Harmer
3.403
3146456SLIGO L269
Solar/Wind Harmer
-0.027
971153AH1-033 GEN
Solar/Wind Harmer
3.31
3144216WINCHST
Adder
0.911
3150921YORKTN3
Adder
6.062
3142416OLDCHRC
Solar/Wind Harmer
2.734
316382AG1-145 C
Solar/Wind Harmer
0.815
316320Y1-086
Solar/Wind Harmer
1.576
316435W1029_GEN3
Solar/Wind Harmer
4.824
3146516WINFALL
Solar/Wind Harmer
-0.026
3142433PROV 92
Adder
0.457
3142433PROV 92
Adder
0.457
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3145273HOLLAND
Solar/Wind Harmer
-0.02
316473AC1-191 GEN
Solar/Wind Harmer
2.815
3146376EDENTON
Solar/Wind Harmer
-0.026
3141843SHACKLE
Adder
1.176
316203AE2-005 GEN
Solar/Wind Harmer
10.898
3141766HARMONY
Solar/Wind Harmer
2.298
316313AB2-026
Solar/Wind Harmer
0.695
316258AE1-075 C
Solar/Wind Harmer
0.626
316405AF2-144 C
Solar/Wind Harmer
0.66
3143336POWHATN
Solar/Wind Harmer
2.601
316280AD1-041 GEN
Solar/Wind Harmer
1.942
316156AD2-030 GEN
Solar/Wind Harmer
0.685
3141873WAN 176
Solar/Wind Harmer
3.046
970917AG2-570 GEN
Solar/Wind Harmer
64.143
315614AA2-178 GEN
Solar/Wind Harmer
2.735
971157AH1-035 GEN
Solar/Wind Harmer
3.118
3156081AA2-088 GEN
Solar/Wind Harmer
8.083
315737AD1-076 GEN
Solar/Wind Harmer
4.727
316365GEN2_N
Solar/Wind Harmer
1.677
3146206CASHIE
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
0.172
3145893MURPHYS
Solar/Wind Harmer
-0.025
962971AG1-146 GEN
Solar/Wind Harmer
4.602
957521AF2-046 GEN
Solar/Wind Harmer
19.314
961681AG1-008 GEN
Solar/Wind Harmer
19.314
3146173TUNIS
Solar/Wind Harmer
-0.024
3156021HOLLOMANSOL
Solar/Wind Harmer
3.275
316484AD2-074 GEN
Solar/Wind Harmer
6.115
970009AG2-005 GEN
Solar/Wind Harmer
3.036
316463AE2-346 GEN
Solar/Wind Harmer
0.393
316140AB2-099
Solar/Wind Harmer
0.163
962331AG1-082 GEN
Solar/Wind Harmer
3.031
966621AG1-532 GEN
Solar/Wind Harmer
0.492
966881AG1-559 GEN
Solar/Wind Harmer
0.724
3146263WOODLND
Solar/Wind Harmer
-0.024
313506AB2-031 GEN
Solar/Wind Harmer
1.925
316404AE1-155 C
Solar/Wind Harmer
4.606
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3145963POPLR C
Solar/Wind Harmer
-0.024
316317KELFORD C
Solar/Wind Harmer
1.117
3145823KELFORD
Solar/Wind Harmer
-0.024
316478AD1-087 GEN
Solar/Wind Harmer
2.037
316486AD2-202 GEN
Solar/Wind Harmer
0.597
3147043LAWRENC
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.093
3145796HORNRTN
Solar/Wind Harmer
-0.023
3150351NORNECKC2
Adder
2.088
316210AC1-098 GEN
Solar/Wind Harmer
3.591
3150401LDYSMT4
Adder
26.739
3150371LDYSMT1
Adder
25.837
3144293JTRSVLE
Adder
0.613
972255AH1-712 GEN
Adder
76.926
3151761LOISA E
Adder
16.965
972183AH1-676 GEN
Adder
130.241
3141316ARNOLDS
Adder
0.278
316044AC1-158 PL1
Solar/Wind Helper
5.238
316450AC1-158 RIC
Solar/Wind Helper
1.397
316170AC1-121 GEN2
Solar/Wind Helper
0.46
3141196NOKESVL
Solar/Wind Helper
1.151
3152251N ANNA1
50/50
20.54
970119AG2-088 GEN
50/50
35.865
3150851SPRUNCC
50/50
1.233
3143096IRON208
50/50
1.093
3152331SURRY 2
50/50
10.164
3150771HOPHCF1
50/50
0.992
3143226MDLTHAN
Solar/Wind Harmer
-0.03
3143526WINTERP
Solar/Wind Harmer
-0.152
3147666LOUISA
Solar/Wind Harmer
-0.114
940641AE2-051 GEN
Solar/Wind Harmer
26.675
939411AE1-173 GEN
Solar/Wind Harmer
140.912
316192AB2-158 GEN
Solar/Wind Harmer
3.325
3142543TWELFTH
Solar/Wind Harmer
-0.003
316294AC1-161 GEN
Solar/Wind Harmer
8.98
315671AE2-027_GEN
Solar/Wind Harmer
20.692
944591AF1-124 GEN
Solar/Wind Harmer
125.51
970129AG2-093 GEN
Solar/Wind Harmer
6.259
316458AB2-190 GEN2
Solar/Wind Harmer
2.776
316375AC2-012 GEN
Solar/Wind Harmer
9.491
3150981CHESPKA
Adder
3.048
971069AG2-661 GEN
Solar/Wind Harmer
4.338
970659AG2-427 GEN
Solar/Wind Harmer
14.549
3145336SMITFLD
Solar/Wind Harmer
-0.109
971647AH1-324 GEN
Solar/Wind Harmer
13.692
961611AG1-000B GEN
Solar/Wind Harmer
13.505
316381AD1-082 GEN
Solar/Wind Harmer
2.509
944631AF1-128 GEN
Adder
116.045
3151171GRAVELC
Adder
2.589
970661AG2-428 GEN
Solar/Wind Harmer
28.997
316388AE2-253 GEN
Solar/Wind Harmer
1.836
3146456SLIGO L269
Solar/Wind Harmer
-0.027
316072AD1-144
Solar/Wind Harmer
0.549
3138126ROCKLANDING
Solar/Wind Harmer
0.083
316246AF1-032 C
Solar/Wind Harmer
0.548
3142416OLDCHRC
Solar/Wind Harmer
-0.07
3142416OLDCHRC
Solar/Wind Harmer
-0.027
316159AE1-175 C
Solar/Wind Harmer
0.726
316093AE2-104_GEN
Solar/Wind Harmer
7.84
971317AH1-138 GEN
Solar/Wind Harmer
3.367
3146516WINFALL
Solar/Wind Harmer
-0.086
3146516WINFALL
Solar/Wind Harmer
-0.026
3142433PROV 92
Solar/Wind Harmer
-0.105
3142433PROV 92
Adder
0.457
3142433PROV 92
Adder
0.457
315800Z1-036_GEN1
Solar/Wind Harmer
6.468
3130156CHOWAN
Solar/Wind Harmer
-0.026
971777AH1-397 GEN
Solar/Wind Harmer
3.039
3141843SHACKLE
Adder
1.176
3141766HARMONY
Solar/Wind Harmer
-0.005
3143336POWHATN
Solar/Wind Harmer
3.06
970919AG2-571 GEN
Solar/Wind Harmer
8.119
970087AG2-069 GEN
Solar/Wind Harmer
23.954
3145663CRESWEL
Solar/Wind Harmer
-0.071
971163AH1-040 GEN
Solar/Wind Harmer
23.766
3138133OCRAN
Solar/Wind Harmer
-0.015
316023GEN1_S
Solar/Wind Harmer
1.677
3146206CASHIE
Solar/Wind Harmer
-0.025
971547AH1-271 GEN
Solar/Wind Harmer
6.159
316336AC2-165 C
Solar/Wind Harmer
4.278
3145893MURPHYS
Solar/Wind Harmer
-0.098
3145893MURPHYS
Solar/Wind Harmer
0.73
957481AF2-042 GEN
Solar/Wind Harmer
76.436
3146173TUNIS
Solar/Wind Harmer
-0.024
961951AG1-038 GEN
Solar/Wind Harmer
3.2
960081AF2-299 GEN
Solar/Wind Harmer
2.727
3145683EARLEYS
Solar/Wind Harmer
-0.024
966881AG1-559 GEN
Solar/Wind Harmer
0.248
3146263WOODLND
Solar/Wind Harmer
-0.024
962861AG1-135 GEN
Solar/Wind Harmer
8.995
315693AD1-088 GEN
Solar/Wind Harmer
11.973
962491AG1-098 GEN
Solar/Wind Harmer
15.963
316011AB1-132 GEN
Solar/Wind Harmer
4.983
962571AG1-106 GEN
Solar/Wind Harmer
3.424
971795AH1-408 GEN
Solar/Wind Harmer
17.814
3145963POPLR C
Solar/Wind Harmer
-0.024
316190AA2-174 GEN
Solar/Wind Harmer
0.291
3145823KELFORD
Solar/Wind Harmer
-0.024
316174AB2-169 GEN
Solar/Wind Harmer
3.632
3147043LAWRENC
Adder
1.895
964211AG1-282 GEN
Solar/Wind Harmer
0.706
3141726DUNNSVL
Solar/Wind Harmer
-0.093
3145783HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.077
3145796HORNRTN
Solar/Wind Harmer
-0.023
3150351NORNECKC2
Adder
2.053
316212AC1-099_GEN
Solar/Wind Harmer
1.995
972197AH1-683 GEN
Adder
4.175
972219AH1-694 GEN
Adder
3.006
3144293JTRSVLE
Adder
0.613
972277AH1-723 GEN
Adder
89.642
3151751LOISA D
Adder
8.322
316045AC1-158 PL2
Solar/Wind Helper
16.768
316006AB2-029 C
Solar/Wind Helper
0.152
316254AC1-120 GEN1
Solar/Wind Helper
1.381
NYPJM->LTFIMP_NY
CLTF
3.309
LGEELTFEXP_LGEE->PJM
CLTF
1.397
WECLTFEXP_WEC->PJM
CLTF
0.676
LAGNLTFEXP_LAGN->PJM
CLTF
8.538
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.91
TVALTFEXP_TVA->PJM
CLTF
4.323
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.478
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.684
MECLTFEXP_MEC->PJM
CLTF
3.82
SIGELTFEXP_SIGE->PJM
CLTF
0.116
CPLELTFEXP_CPLE->PJM
CLTF
12.318
CBM West 2LTFEXP_CBM-W2->PJM
CBM
43.908

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T552_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T552_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:148.0 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:5831.04
MW Contribution:87.35
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
4.723
971285AH1-108 GEN
50/50
1.99
970603AG2-384 GEN
50/50
5.178
972263AH1-716 GEN
50/50
139.063
316233AE1-074 FULL
Solar/Wind Harmer
0.78
971281AH1-106 GEN
Solar/Wind Harmer
4.714
971283AH1-107 GEN
Solar/Wind Harmer
4.714
3143316POE
Solar/Wind Harmer
-0.108
941031AE2-094 GEN
Solar/Wind Harmer
51.106
944011AF1-069 GEN
Solar/Wind Harmer
16.013
316132AB2-190 GEN1
Solar/Wind Harmer
2.735
3151081ELIZAR1
Adder
22.034
3151091ELIZAR2
Adder
21.652
3152611GOSPORTB
Adder
3.059
3152621GOSPORTC
Adder
2.596
3152601GOSPORTA
Adder
2.395
316369SG1_INVT
Solar/Wind Harmer
4.823
971445AH1-216 GEN
Solar/Wind Harmer
16.679
972265AH1-717 GEN
Adder
18.606
3151201GRAVEL4
Adder
17.442
3151191GRAVEL3
Adder
17.221
3151211GRAVEL5
Adder
17.221
970673AG2-436 GEN
Solar/Wind Harmer
56.272
970673AG2-436 GEN
Solar/Wind Harmer
28.492
957871AF2-081 GEN
Solar/Wind Harmer
13.387
316312AB1-027
Solar/Wind Harmer
0.901
319010AE1-072 C
Solar/Wind Harmer
5.402
315833AF1-017_GEN
Solar/Wind Harmer
5.072
316349AD2-085 GEN
Solar/Wind Harmer
2.375
316311AC2-079 GEN
Solar/Wind Harmer
13.467
3146406KITTY HAWK
Solar/Wind Harmer
0.022
316305AF2-043 C
Solar/Wind Harmer
0.804
315835AF2-110_GEN
Solar/Wind Harmer
3.318
316315AB2-025 C
Solar/Wind Harmer
0.715
315976AC1-164 GENA
Solar/Wind Harmer
27.987
316169AC1-164_GENC
Solar/Wind Harmer
24.178
315975AC1-164 GENB
Solar/Wind Harmer
0.828
313526AB2-022
Solar/Wind Harmer
0.714
971967AH1-528 GEN
Solar/Wind Harmer
49.715
315814AE2-033 C
Solar/Wind Harmer
24.583
3146486SUNBURY
Solar/Wind Harmer
-0.026
3146486SUNBURY
Solar/Wind Harmer
-0.026
316321Z2-027
Solar/Wind Harmer
0.711
3146396TANGLEW
Solar/Wind Harmer
0.485
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
972189AH1-679 GEN
Adder
3.913
971167AH1-042 GEN
Solar/Wind Harmer
25.191
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
957831AF2-077 GEN
Solar/Wind Harmer
0.783
3138283WHITEMARSH
Solar/Wind Harmer
0.04
315611Z1-036_GEN2
Solar/Wind Harmer
6.367
3143873LANEXA
Solar/Wind Harmer
-0.015
316314AB2-024 C
Solar/Wind Harmer
2.185
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
316059AD1-063 C
Solar/Wind Harmer
0.576
315662AE1-191 GEN
Solar/Wind Harmer
3.067
315666AE1-190 GEN
Solar/Wind Harmer
0.767
957601AF2-054 GEN
Solar/Wind Harmer
0.758
3141873WAN 176
Solar/Wind Harmer
-0.005
970085AG2-068 GEN
Solar/Wind Harmer
15.742
970581AG2-369 GEN
Solar/Wind Harmer
13.538
3141913WHIT STONE
Solar/Wind Harmer
-0.025
315816AE2-034 GEN
Solar/Wind Harmer
2.02
3138133OCRAN
Solar/Wind Harmer
-0.007
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.952
315733AD1-074 GEN2
Solar/Wind Harmer
4.952
315735AD1-075 GEN1
Solar/Wind Harmer
2.477
965291AG1-394 GEN
Solar/Wind Harmer
2.168
3150411LDYSMT5
Adder
29.247
3150381LDYSMT2
Adder
27.99
972213AH1-691 GEN
Adder
4.735
972215AH1-692 GEN
Adder
4.735
962981AG1-147 GEN
Solar/Wind Harmer
10.632
3146206CASHIE
Solar/Wind Harmer
-0.024
970601AG2-382 GEN
Solar/Wind Harmer
10.614
316318V4-068
Solar/Wind Harmer
0.603
3145893MURPHYS
Solar/Wind Harmer
-0.065
3145893MURPHYS
Solar/Wind Harmer
-0.024
946281AF1-292 GEN
Solar/Wind Harmer
0.535
3145513AHOSKIE
Solar/Wind Harmer
0.208
961941AG1-037 GEN
Solar/Wind Harmer
0.18
3145513AHOSKIE
Solar/Wind Harmer
-0.024
3146043SEABORD
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.047
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
315607AA1-063A GEN
Solar/Wind Harmer
2.397
316087AB2-174 GEN
Solar/Wind Harmer
3.379
315652AC1-086 GEN
Solar/Wind Harmer
26.401
3137643SOCKMAN
Solar/Wind Harmer
-0.093
3145796HORNRTN
Solar/Wind Harmer
-0.073
3145796HORNRTN
Solar/Wind Harmer
-0.009
3141813NORNECK
Solar/Wind Harmer
-0.023
3146033SCOT NK
Solar/Wind Harmer
-0.091
972205AH1-687 GEN
Adder
7.204
972193AH1-681 GEN
Adder
3.349
316164AC1-076 GEN
Solar/Wind Helper
1.38
316411AF1-147_GEN1
Solar/Wind Helper
0.79
316415AF1-147_GEN2
Solar/Wind Helper
0.79
3138216PACIFIC
Solar/Wind Helper
0.038
3152261N ANNA2
50/50
20.32
3150861SPRUNCD
50/50
1.216
3143096IRON208
50/50
1.078
3143096IRON208
50/50
1.056
3150801HOPHCF4
50/50
1.421
971211AH1-065 GEN
50/50
1.714
3151101ELIZAR3
50/50
23.68
3151161SURRY 1
50/50
9.205
3147666LOUISA
Solar/Wind Harmer
-0.066
315839AE2-212 C
Solar/Wind Harmer
0.823
315773AC2-141 GEN
Solar/Wind Harmer
11.425
965281AG1-393 GEN
Solar/Wind Harmer
3.403
315813AE1-149 C
Solar/Wind Harmer
16.949
970133AG2-095 GEN
Solar/Wind Harmer
3.047
944581AF1-123 GEN
Solar/Wind Harmer
123.071
944601AF1-125 GEN
Solar/Wind Harmer
121.15
970129AG2-093 GEN
Solar/Wind Harmer
15.226
315778AD1-151 GEN
Solar/Wind Harmer
23.4
3144536CHRHLND
Solar/Wind Harmer
-0.004
3144873MCLAUGH
Solar/Wind Harmer
-0.001
970659AG2-427 GEN
Solar/Wind Harmer
2.54
3145336SMITFLD
Solar/Wind Harmer
-0.011
316083AB2-161 GEN
Solar/Wind Harmer
4.375
961611AG1-000B GEN
Solar/Wind Harmer
5.675
3151221GRAVEL6
Adder
17.422
3151171GRAVELC
Adder
3.352
970661AG2-428 GEN
Solar/Wind Harmer
5.062
970293AG2-193 GEN
Solar/Wind Harmer
3.354
3142946ENON
Solar/Wind Harmer
-0.009
3146456SLIGO L269
Solar/Wind Harmer
-0.027
971153AH1-033 GEN
Solar/Wind Harmer
3.257
3142416OLDCHRC
Solar/Wind Harmer
2.696
3144216WINCHST
Adder
0.896
3150921YORKTN3
Adder
5.966
316382AG1-145 C
Solar/Wind Harmer
0.802
316320Y1-086
Solar/Wind Harmer
1.551
316435W1029_GEN3
Solar/Wind Harmer
4.748
3146516WINFALL
Solar/Wind Harmer
-0.026
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3145273HOLLAND
Solar/Wind Harmer
-0.019
316473AC1-191 GEN
Solar/Wind Harmer
2.785
3141843SHACKLE
Adder
1.16
316203AE2-005 GEN
Solar/Wind Harmer
10.757
316313AB2-026
Solar/Wind Harmer
0.688
316258AE1-075 C
Solar/Wind Harmer
0.619
316405AF2-144 C
Solar/Wind Harmer
0.653
3143336POWHATN
Solar/Wind Harmer
2.572
3146376EDENTON
Solar/Wind Harmer
-0.025
3141766HARMONY
Solar/Wind Harmer
2.268
316280AD1-041 GEN
Solar/Wind Harmer
1.917
316156AD2-030 GEN
Solar/Wind Harmer
0.677
3141873WAN 176
Solar/Wind Harmer
3.008
970917AG2-570 GEN
Solar/Wind Harmer
63.229
966881AG1-559 GEN
Solar/Wind Harmer
0.76
315614AA2-178 GEN
Solar/Wind Harmer
2.693
971157AH1-035 GEN
Solar/Wind Harmer
3.07
3156081AA2-088 GEN
Solar/Wind Harmer
7.961
316365GEN2_N
Solar/Wind Harmer
1.652
315737AD1-076 GEN
Solar/Wind Harmer
4.654
3150401LDYSMT4
Adder
29.156
3150371LDYSMT1
Adder
28.172
962971AG1-146 GEN
Solar/Wind Harmer
4.557
3146206CASHIE
Solar/Wind Harmer
-0.024
3145893MURPHYS
Solar/Wind Harmer
0.169
3145893MURPHYS
Solar/Wind Harmer
-0.024
957521AF2-046 GEN
Solar/Wind Harmer
19.023
961681AG1-008 GEN
Solar/Wind Harmer
19.023
316484AD2-074 GEN
Solar/Wind Harmer
6.058
970009AG2-005 GEN
Solar/Wind Harmer
3.008
3146173TUNIS
Solar/Wind Harmer
-0.024
3156021HOLLOMANSOL
Solar/Wind Harmer
3.225
966621AG1-532 GEN
Solar/Wind Harmer
0.485
316463AE2-346 GEN
Solar/Wind Harmer
0.387
316140AB2-099
Solar/Wind Harmer
0.161
962331AG1-082 GEN
Solar/Wind Harmer
2.986
316404AE1-155 C
Solar/Wind Harmer
4.568
3146263WOODLND
Solar/Wind Harmer
-0.024
313506AB2-031 GEN
Solar/Wind Harmer
1.897
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.023
316317KELFORD C
Solar/Wind Harmer
1.1
3145823KELFORD
Solar/Wind Harmer
-0.023
316478AD1-087 GEN
Solar/Wind Harmer
2.009
316486AD2-202 GEN
Solar/Wind Harmer
0.588
3147043LAWRENC
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.092
3145796HORNRTN
Solar/Wind Harmer
-0.023
3150351NORNECKC2
Adder
2.075
316210AC1-098 GEN
Solar/Wind Harmer
3.537
3144293JTRSVLE
Adder
0.605
972255AH1-712 GEN
Adder
74.962
3151761LOISA E
Adder
17.688
972183AH1-676 GEN
Adder
136.298
3141316ARNOLDS
Adder
0.29
316044AC1-158 PL1
Solar/Wind Helper
5.216
316450AC1-158 RIC
Solar/Wind Helper
1.391
3141196NOKESVL
Solar/Wind Helper
1.131
971133AH1-012 GEN
50/50
5.491
944641AF1-129 GEN
50/50
122.767
970533AG2-339 GEN
50/50
21.564
970531AG2-338 GEN
50/50
8.626
3142366NRTHEST
50/50
0.836
3150781HOPHCF2
50/50
0.977
3150791HOPHCF3
50/50
0.977
3150761HOPPOLC
50/50
0.62
971213AH1-066 GEN
50/50
0.857
971223AH1-071 GEN
Solar/Wind Harmer
3.731
3143526WINTERP
Solar/Wind Harmer
-0.15
316240AF1-291 C
Solar/Wind Harmer
0.822
3150691DARBY 3
Adder
17.296
3150701DARBY 4
Adder
17.255
3150681DARBY 2
Adder
17.235
3150671DARBY 1
Adder
17.215
316036AC1-147 C
Solar/Wind Harmer
0.728
3150991CHESPKB
Adder
2.516
3150991CHESPKB
Adder
2.456
316033AB2-134 GEN
Solar/Wind Harmer
8.705
315697AD1-025 GEN
Solar/Wind Harmer
5.46
3142956BIRDNECK
Solar/Wind Harmer
1.447
316316AC1-027 C
Solar/Wind Harmer
0.828
316236AE1-162_GEN
Solar/Wind Harmer
0.812
316185AD1-033 GEN
Solar/Wind Harmer
2.842
970657AG2-426 GEN
Solar/Wind Harmer
8.416
970657AG2-426 GEN
Solar/Wind Harmer
1.76
3142296MT RD221
Adder
0.763
3145506HICKORY
Solar/Wind Harmer
-0.107
3145506HICKORY
Solar/Wind Harmer
-0.064
3145506HICKORY
Solar/Wind Harmer
-0.016
3142946ENON
Solar/Wind Harmer
-0.003
316339AD2-160 GEN
Solar/Wind Harmer
1.807
316018AA1-139 ULT2
Solar/Wind Harmer
2.294
316017AA1-139 ULT1
Solar/Wind Harmer
2.166
3137176SLIGO L2192
Solar/Wind Harmer
-0.106
3146456SLIGO L269
Solar/Wind Harmer
3.156
3130086AYDLETT
Solar/Wind Harmer
-0.106
316075AC2-137 C
Solar/Wind Harmer
0.719
972185AH1-677 GEN
Adder
13.26
3144356SAPONY
Solar/Wind Harmer
0.924
3146386ELIZ CT
Solar/Wind Harmer
-0.026
972187AH1-678 GEN
Adder
6.65
316431W1029_GEN1
Solar/Wind Harmer
4.748
316433W1029_GEN2
Solar/Wind Harmer
4.748
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
966871AG1-558 GEN
Solar/Wind Harmer
0.778
966871AG1-558 GEN
Solar/Wind Harmer
0.266
970933AG2-581 GEN
Solar/Wind Harmer
24.187
315742AE1-103 GEN
Solar/Wind Harmer
2.679
316441AF1-014 GEN
Solar/Wind Harmer
1.72
3146376EDENTON
Solar/Wind Harmer
0.756
3146376EDENTON
Solar/Wind Harmer
0.756
957411AF2-035 GEN
Solar/Wind Harmer
11.373
970317AG2-208 GEN
Solar/Wind Harmer
11.057
315673AE1-157 GEN
Solar/Wind Harmer
18.722
3150391LDYSMT3
Adder
29.101
972195AH1-682 GEN
Adder
3.824
316065AD1-022 GEN
Solar/Wind Harmer
12.172
3145893MURPHYS
Solar/Wind Harmer
0.676
3145893MURPHYS
Solar/Wind Harmer
-0.043
970099AG2-077 GEN
Solar/Wind Harmer
30.15
316487AF1-042 GEN
Solar/Wind Harmer
3.17
3146173TUNIS
Solar/Wind Harmer
-0.024
3146173TUNIS
Solar/Wind Harmer
-0.024
958261AF2-120 GEN
Solar/Wind Harmer
9.177
316181AB2-040 GEN
Solar/Wind Harmer
3.292
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
316426AA2-053 GEN
Solar/Wind Harmer
2.36
3145593CAROLNA
Solar/Wind Harmer
-0.023
3145593CAROLNA
Solar/Wind Harmer
-0.023
966811AG1-552 GEN
Solar/Wind Harmer
2.618
3145593CAROLNA
Solar/Wind Harmer
0.193
3145783HORNRTN
Solar/Wind Harmer
2.745
3145783HORNRTN
Solar/Wind Harmer
2.196
3145783HORNRTN
Solar/Wind Harmer
0.686
3145783HORNRTN
Solar/Wind Harmer
0.275
3145796HORNRTN
Solar/Wind Harmer
-0.069
316077AC2-138 C
Solar/Wind Harmer
0.485
3150341NORNECKC1
Adder
2.143
3150341NORNECKC1
Adder
2.126
3144293JTRSVLE
Adder
0.605
3144293JTRSVLE
Adder
0.51
3151731LOISA B
Adder
8.676
3151721LOISA A
Adder
8.631
316447AC1-158 HLD
Solar/Wind Helper
11.481
971741AH1-377 GEN
Solar/Wind Harmer
12.466
3152251N ANNA1
50/50
20.321
970119AG2-088 GEN
50/50
35.422
3150851SPRUNCC
50/50
1.216
3143096IRON208
50/50
1.078
3152331SURRY 2
50/50
9.99
3150771HOPHCF1
50/50
0.977
3143226MDLTHAN
Solar/Wind Harmer
-0.03
3143526WINTERP
Solar/Wind Harmer
-0.15
3147666LOUISA
Solar/Wind Harmer
-0.115
316192AB2-158 GEN
Solar/Wind Harmer
3.345
940641AE2-051 GEN
Solar/Wind Harmer
26.285
939411AE1-173 GEN
Solar/Wind Harmer
138.811
3142543TWELFTH
Solar/Wind Harmer
-0.003
316294AC1-161 GEN
Solar/Wind Harmer
8.834
315671AE2-027_GEN
Solar/Wind Harmer
20.403
944591AF1-124 GEN
Solar/Wind Harmer
123.514
970129AG2-093 GEN
Solar/Wind Harmer
6.167
316458AB2-190 GEN2
Solar/Wind Harmer
2.735
971069AG2-661 GEN
Solar/Wind Harmer
4.274
316375AC2-012 GEN
Solar/Wind Harmer
9.341
3150981CHESPKA
Adder
3
970659AG2-427 GEN
Solar/Wind Harmer
14.335
971647AH1-324 GEN
Solar/Wind Harmer
13.486
3145336SMITFLD
Solar/Wind Harmer
-0.107
316381AD1-082 GEN
Solar/Wind Harmer
2.472
944631AF1-128 GEN
Adder
114.357
961611AG1-000B GEN
Solar/Wind Harmer
13.3
3151171GRAVELC
Adder
2.549
970661AG2-428 GEN
Solar/Wind Harmer
28.566
316388AE2-253 GEN
Solar/Wind Harmer
1.807
3146456SLIGO L269
Solar/Wind Harmer
-0.027
3142416OLDCHRC
Solar/Wind Harmer
-0.069
3142416OLDCHRC
Solar/Wind Harmer
-0.026
316072AD1-144
Solar/Wind Harmer
0.54
3138126ROCKLANDING
Solar/Wind Harmer
0.082
316246AF1-032 C
Solar/Wind Harmer
0.54
316159AE1-175 C
Solar/Wind Harmer
0.715
316093AE2-104_GEN
Solar/Wind Harmer
7.718
971317AH1-138 GEN
Solar/Wind Harmer
3.315
3146516WINFALL
Solar/Wind Harmer
-0.084
3146516WINFALL
Solar/Wind Harmer
-0.026
3142433PROV 92
Solar/Wind Harmer
-0.104
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
315800Z1-036_GEN1
Solar/Wind Harmer
6.367
971777AH1-397 GEN
Solar/Wind Harmer
3
3141843SHACKLE
Adder
1.16
3143336POWHATN
Solar/Wind Harmer
3.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
3141766HARMONY
Solar/Wind Harmer
-0.005
970919AG2-571 GEN
Solar/Wind Harmer
8.004
966881AG1-559 GEN
Solar/Wind Harmer
0.26
970087AG2-069 GEN
Solar/Wind Harmer
23.613
3145663CRESWEL
Solar/Wind Harmer
-0.07
971163AH1-040 GEN
Solar/Wind Harmer
23.4
3138133OCRAN
Solar/Wind Harmer
-0.015
316023GEN1_S
Solar/Wind Harmer
1.652
972197AH1-683 GEN
Adder
4.553
972219AH1-694 GEN
Adder
3.278
316336AC2-165 C
Solar/Wind Harmer
4.232
3146206CASHIE
Solar/Wind Harmer
-0.024
971547AH1-271 GEN
Solar/Wind Harmer
6.065
3145893MURPHYS
Solar/Wind Harmer
-0.096
3145893MURPHYS
Solar/Wind Harmer
0.719
957481AF2-042 GEN
Solar/Wind Harmer
75.375
961951AG1-038 GEN
Solar/Wind Harmer
3.17
3146173TUNIS
Solar/Wind Harmer
-0.024
960081AF2-299 GEN
Solar/Wind Harmer
2.688
962861AG1-135 GEN
Solar/Wind Harmer
8.919
3145683EARLEYS
Solar/Wind Harmer
-0.024
3146263WOODLND
Solar/Wind Harmer
-0.024
315693AD1-088 GEN
Solar/Wind Harmer
11.811
962491AG1-098 GEN
Solar/Wind Harmer
15.746
316011AB1-132 GEN
Solar/Wind Harmer
4.91
962571AG1-106 GEN
Solar/Wind Harmer
3.374
971795AH1-408 GEN
Solar/Wind Harmer
17.56
3145963POPLR C
Solar/Wind Harmer
-0.023
316190AA2-174 GEN
Solar/Wind Harmer
0.287
3145823KELFORD
Solar/Wind Harmer
-0.023
964211AG1-282 GEN
Solar/Wind Harmer
0.701
3141726DUNNSVL
Solar/Wind Harmer
-0.093
316174AB2-169 GEN
Solar/Wind Harmer
3.577
3147043LAWRENC
Adder
1.868
3145783HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.076
3145796HORNRTN
Solar/Wind Harmer
-0.023
3150351NORNECKC2
Adder
2.04
316212AC1-099_GEN
Solar/Wind Harmer
1.965
3144293JTRSVLE
Adder
0.605
972277AH1-723 GEN
Adder
87.353
3151751LOISA D
Adder
8.676
316045AC1-158 PL2
Solar/Wind Helper
16.699
316006AB2-029 C
Solar/Wind Helper
0.14
NYPJM->LTFIMP_NY
CLTF
3.266
LGEELTFEXP_LGEE->PJM
CLTF
1.371
WECLTFEXP_WEC->PJM
CLTF
0.662
LAGNLTFEXP_LAGN->PJM
CLTF
8.398
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.505
TVALTFEXP_TVA->PJM
CLTF
4.252
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.027
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.441
MECLTFEXP_MEC->PJM
CLTF
3.751
SIGELTFEXP_SIGE->PJM
CLTF
0.114
CPLELTFEXP_CPLE->PJM
CLTF
12.136
CBM West 2LTFEXP_CBM-W2->PJM
CBM
43.163

Details for 8POSSUM-BURCHES 500.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019B_SRT-A


Base Case Flowgate

Area:DVP/PJM
Facility Description:
8POSSUM-BURCHES 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.93 %
Rating:3099.0 MVA
Rating Type:B
MVA to Mitigate:3561.83
MW Contribution:83.44
Bus #Bus NameTypeMW Contribution
970053AG2-049 GEN
50/50
3.273
3150411LDYSMT5
50/50
25.907
3150381LDYSMT2
50/50
24.794
972213AH1-691 GEN
50/50
4.194
972215AH1-692 GEN
50/50
4.194
963051AG1-154 GEN
50/50
3.226
3141426STAFORD
Solar/Wind Harmer
-0.005
944491AF1-114 GEN
Solar/Wind Harmer
5.857
316223AC1-118
Solar/Wind Harmer
0.522
972189AH1-679 GEN
Adder
2.807
3141813NORNECK
Solar/Wind Harmer
-0.019
962981AG1-147 GEN
Solar/Wind Harmer
8.074
3141783LANCAST
Solar/Wind Harmer
-0.011
3141783LANCAST
Solar/Wind Harmer
-0.007
3138133OCRAN
Solar/Wind Harmer
-0.006
3141913WHIT STONE
Solar/Wind Harmer
-0.018
316312AB1-027
Solar/Wind Harmer
0.614
316314AB2-024 C
Solar/Wind Harmer
1.555
316059AD1-063 C
Solar/Wind Harmer
0.411
957601AF2-054 GEN
Solar/Wind Harmer
0.544
3141873WAN 176
Solar/Wind Harmer
-0.004
315662AE1-191 GEN
Solar/Wind Harmer
2.192
315666AE1-190 GEN
Solar/Wind Harmer
0.548
3143873LANEXA
Solar/Wind Harmer
-0.011
3142433PROV 92
Adder
0.313
3142433PROV 92
Adder
0.313
971167AH1-042 GEN
Solar/Wind Harmer
17.397
315976AC1-164 GENA
Solar/Wind Harmer
19.078
316169AC1-164_GENC
Solar/Wind Harmer
16.482
315975AC1-164 GENB
Solar/Wind Harmer
0.564
316164AC1-076 GEN
Solar/Wind Harmer
1.517
957831AF2-077 GEN
Solar/Wind Harmer
0.539
3138283WHITEMARSH
Solar/Wind Harmer
0.028
971285AH1-108 GEN
Adder
1.2
316233AE1-074 FULL
Solar/Wind Harmer
0.48
971281AH1-106 GEN
Solar/Wind Harmer
2.897
971283AH1-107 GEN
Solar/Wind Harmer
2.897
316132AB2-190 GEN1
Solar/Wind Harmer
1.788
316369SG1_INVT
Solar/Wind Harmer
3.146
972265AH1-717 GEN
Adder
12.099
3151201GRAVEL4
Adder
11.342
3151191GRAVEL3
Adder
11.198
3151211GRAVEL5
Adder
11.198
971445AH1-216 GEN
Solar/Wind Harmer
10.79
3143316POE
Solar/Wind Harmer
-0.068
3151081ELIZAR1
Adder
14.117
3151091ELIZAR2
Adder
13.871
3152611GOSPORTB
Adder
1.961
3152621GOSPORTC
Adder
1.664
3152601GOSPORTA
Adder
1.535
315833AF1-017_GEN
Solar/Wind Harmer
3.27
316349AD2-085 GEN
Solar/Wind Harmer
1.531
316311AC2-079 GEN
Solar/Wind Harmer
8.684
957871AF2-081 GEN
Solar/Wind Harmer
8.603
316305AF2-043 C
Solar/Wind Harmer
0.518
319010AE1-072 C
Solar/Wind Harmer
3.475
3146406KITTY HAWK
Solar/Wind Harmer
0.014
315835AF2-110_GEN
Solar/Wind Harmer
2.143
313526AB2-022
Solar/Wind Harmer
0.461
3146486SUNBURY
Solar/Wind Harmer
-0.017
3146486SUNBURY
Solar/Wind Harmer
-0.017
316321Z2-027
Solar/Wind Harmer
0.46
3145176PASQUOTANK
Solar/Wind Harmer
-0.011
3146396TANGLEW
Solar/Wind Harmer
0.314
316315AB2-025 C
Solar/Wind Harmer
0.455
315814AE2-033 C
Solar/Wind Harmer
15.687
315611Z1-036_GEN2
Solar/Wind Harmer
4.161
3147346CASHSCORNER
Solar/Wind Harmer
0.26
941031AE2-094 GEN
Solar/Wind Harmer
31.438
944011AF1-069 GEN
Solar/Wind Harmer
9.851
3130156CHOWAN
Solar/Wind Harmer
-0.017
3130156CHOWAN
Solar/Wind Harmer
-0.017
970673AG2-436 GEN
Solar/Wind Harmer
34.947
970673AG2-436 GEN
Solar/Wind Harmer
17.695
971967AH1-528 GEN
Solar/Wind Harmer
31.136
315816AE2-034 GEN
Solar/Wind Harmer
1.339
3130546PLYMOUTH
Solar/Wind Harmer
-0.016
315732AD1-074 GEN1
Solar/Wind Harmer
3.31
315733AD1-074 GEN2
Solar/Wind Harmer
3.31
315735AD1-075 GEN1
Solar/Wind Harmer
1.656
965291AG1-394 GEN
Solar/Wind Harmer
1.45
3146206CASHIE
Solar/Wind Harmer
-0.016
970601AG2-382 GEN
Solar/Wind Harmer
7.123
316318V4-068
Solar/Wind Harmer
0.405
3145893MURPHYS
Solar/Wind Harmer
-0.044
3145893MURPHYS
Solar/Wind Harmer
-0.016
970085AG2-068 GEN
Solar/Wind Harmer
10.104
970581AG2-369 GEN
Solar/Wind Harmer
8.69
3145513AHOSKIE
Solar/Wind Harmer
0.141
961941AG1-037 GEN
Solar/Wind Harmer
0.121
3145513AHOSKIE
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.032
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.016
3146043SEABORD
Solar/Wind Harmer
-0.016
946281AF1-292 GEN
Solar/Wind Harmer
0.36
315607AA1-063A GEN
Solar/Wind Harmer
1.624
316087AB2-174 GEN
Solar/Wind Harmer
2.286
972193AH1-681 GEN
Adder
3.199
972205AH1-687 GEN
Adder
5.971
3151881LOWMORC
Adder
1.27
3151881LOWMORC
Adder
1.25
3151861LOWMORA
Adder
1.23
233935AB2-179 C
Solar/Wind Helper
1.735
232436AB1-176 C
Solar/Wind Helper
0.06
233923SMA
Solar/Wind Helper
1.302
233990AG1-397 GEN
Solar/Wind Helper
0.041
232432Z2-076 GEN
Solar/Wind Helper
0.091
234033AF1-007_GEN
Solar/Wind Helper
9.531
964001AG1-254 GEN
Solar/Wind Helper
1.261
228754AB1-001 C
Solar/Wind Helper
0.034
227927V4-067C
Solar/Wind Helper
0.013
219914AD2-027 C
Solar/Wind Helper
0.15
219272CLEANLIGHT C
Solar/Wind Helper
0.033
219688LUMSOLAR_S C
Solar/Wind Helper
0.052
219607WPEMNERT C
Solar/Wind Helper
0.104
214067T20SOLAR
Solar/Wind Helper
0.015
20715728PEM_W1-119
Solar/Wind Helper
0.124
20715828PEM_W1-120
Solar/Wind Helper
0.124
207459AE1-142 C O1
Solar/Wind Helper
0.373
219620RIDERU C
Solar/Wind Helper
0.001
20675528CPH_W2-050
Solar/Wind Helper
0.109
218526CNTRALGAS2 C
Solar/Wind Helper
0.203
218524CNTRALGAS1 C
Solar/Wind Helper
0.203
966261AG1-495 GEN
Solar/Wind Helper
0.101
207530AG1-191 GEN
Solar/Wind Helper
0.081
20676328BVR_Y1-020
Solar/Wind Helper
0.033
20674828DL_W4-046
Solar/Wind Helper
0.01
20675928HOL_W4-097
Solar/Wind Helper
0.061
207484AF2-139 C O1
Solar/Wind Helper
0.103
207408W3-077 C
Solar/Wind Helper
0.103
20675728RH_W2-091
Solar/Wind Helper
0.168
20675128HRM_W1-127
Solar/Wind Helper
0.036
960921AF2-383 GEN
Solar/Wind Helper
0.211
209116AE2-175 GEN
Solar/Wind Helper
2.147
205932AD2-116_GEN
Solar/Wind Helper
0.581
205956AE1-196_GEN
Solar/Wind Helper
0.581
205943AE1-185 GEN
Solar/Wind Helper
0.575
961261AF2-417 GEN
Solar/Wind Helper
0.512
959431AF2-234 GEN
Solar/Wind Helper
0.976
964051AG1-259 GEN
Solar/Wind Helper
0.073
964061AG1-260 GEN
Solar/Wind Helper
0.073
959421AF2-233 GEN
Solar/Wind Helper
0.488
972223AH1-696 GEN
50/50
17.601
3150151POSSMC1
50/50
2.228
3141346CRANES
50/50
0.247
3150011OMF A
50/50
0.367
3140676OCCOQUN
50/50
0.487
972197AH1-683 GEN
50/50
4.033
972219AH1-694 GEN
50/50
2.904
957971AF2-091 GEN
Solar/Wind Harmer
1.991
972135AH1-637 GEN
Solar/Wind Harmer
1.978
966881AG1-559 GEN
Solar/Wind Harmer
0.202
316337AD2-073 GEN
Solar/Wind Harmer
0.512
3150351NORNECKC2
Adder
1.667
964211AG1-282 GEN
Solar/Wind Harmer
0.563
3141726DUNNSVL
Solar/Wind Harmer
-0.074
962861AG1-135 GEN
Solar/Wind Harmer
6.97
961951AG1-038 GEN
Solar/Wind Harmer
2.439
3138133OCRAN
Solar/Wind Harmer
-0.011
316045AC1-158 PL2
Solar/Wind Harmer
5.715
3142416OLDCHRC
Solar/Wind Harmer
-0.047
3142416OLDCHRC
Solar/Wind Harmer
-0.018
3141766HARMONY
Solar/Wind Harmer
-0.004
971777AH1-397 GEN
Solar/Wind Harmer
2.137
3141843SHACKLE
Adder
0.827
3142433PROV 92
Solar/Wind Harmer
-0.072
3142433PROV 92
Adder
0.313
3142433PROV 92
Adder
0.313
3143096IRON208
Adder
0.67
944631AF1-128 GEN
Adder
76.064
3142543TWELFTH
Solar/Wind Harmer
-0.002
3150851SPRUNCC
Adder
0.733
3143526WINTERP
Solar/Wind Harmer
-0.092
316159AE1-175 C
Solar/Wind Harmer
0.478
971317AH1-138 GEN
Solar/Wind Harmer
2.221
3147666LOUISA
Solar/Wind Harmer
-0.071
3143226MDLTHAN
Solar/Wind Harmer
-0.018
316192AB2-158 GEN
Solar/Wind Harmer
2.108
970129AG2-093 GEN
Solar/Wind Harmer
4.032
316458AB2-190 GEN2
Solar/Wind Harmer
1.788
315671AE2-027_GEN
Solar/Wind Harmer
13.243
3138126ROCKLANDING
Solar/Wind Harmer
0.054
971069AG2-661 GEN
Solar/Wind Harmer
2.791
971647AH1-324 GEN
Solar/Wind Harmer
8.789
316254AC1-120 GEN1
Solar/Wind Harmer
1.418
961611AG1-000B GEN
Solar/Wind Harmer
8.659
3151171GRAVELC
Adder
1.658
3145336SMITFLD
Solar/Wind Harmer
-0.069
316294AC1-161 GEN
Solar/Wind Harmer
5.624
970659AG2-427 GEN
Solar/Wind Harmer
9.221
316381AD1-082 GEN
Solar/Wind Harmer
1.591
316375AC2-012 GEN
Solar/Wind Harmer
5.987
970661AG2-428 GEN
Solar/Wind Harmer
18.39
3150981CHESPKA
Adder
1.923
944591AF1-124 GEN
Solar/Wind Harmer
78.926
316072AD1-144
Solar/Wind Harmer
0.349
316388AE2-253 GEN
Solar/Wind Harmer
1.161
3146456SLIGO L269
Solar/Wind Harmer
-0.017
316246AF1-032 C
Solar/Wind Harmer
0.348
316093AE2-104_GEN
Solar/Wind Harmer
4.984
939411AE1-173 GEN
Solar/Wind Harmer
85.695
316006AB2-029 C
Solar/Wind Harmer
0.983
971685AH1-345 GEN
Solar/Wind Harmer
1.499
940641AE2-051 GEN
Solar/Wind Harmer
16.029
3150281M RUN A
Adder
20.58
3150221REMNGT2
Adder
19.137
3150211REMNGT1
Adder
19.01
972201AH1-685 GEN
Adder
3.302
3151751LOISA D
Adder
9.812
3146516WINFALL
Solar/Wind Harmer
-0.055
3146516WINFALL
Solar/Wind Harmer
-0.017
315683AE1-153 C
Solar/Wind Harmer
15.812
3143336POWHATN
Solar/Wind Harmer
2.008
315800Z1-036_GEN1
Solar/Wind Harmer
4.161
3130156CHOWAN
Solar/Wind Harmer
-0.017
316336AC2-165 C
Solar/Wind Harmer
2.903
3145663CRESWEL
Solar/Wind Harmer
-0.046
971163AH1-040 GEN
Solar/Wind Harmer
15.508
3146206CASHIE
Solar/Wind Harmer
-0.016
971547AH1-271 GEN
Solar/Wind Harmer
4.071
316023GEN1_S
Solar/Wind Harmer
1.097
3145893MURPHYS
Solar/Wind Harmer
-0.065
3145893MURPHYS
Solar/Wind Harmer
0.482
970919AG2-571 GEN
Solar/Wind Harmer
5.126
3146173TUNIS
Solar/Wind Harmer
-0.016
970087AG2-069 GEN
Solar/Wind Harmer
15.156
970937AG2-583 GEN
Solar/Wind Harmer
11.617
3145683EARLEYS
Solar/Wind Harmer
-0.016
960081AF2-299 GEN
Solar/Wind Harmer
1.81
3146263WOODLND
Solar/Wind Harmer
-0.016
957481AF2-042 GEN
Solar/Wind Harmer
49.991
3145963POPLR C
Solar/Wind Harmer
-0.016
3147043LAWRENC
Adder
1.279
972277AH1-723 GEN
Adder
83.443
3144293JTRSVLE
Adder
0.442
223401AF1-299 GEN
Solar/Wind Helper
0.748
233930AB2-032 GEN
Solar/Wind Helper
0.519
233915AB1-141 GEN
Solar/Wind Helper
0.685
232422X3-066 FULL
Solar/Wind Helper
0.156
233964AF2-378 GEN
Solar/Wind Helper
0.057
232426Y1-080 FULL
Solar/Wind Helper
0.053
232428Y3-058 C
Solar/Wind Helper
0.459
233998TM1NIN_3.36
Solar/Wind Helper
0.355
232404W1-003 C
Solar/Wind Helper
0.689
233954AC2-188 GEN
Solar/Wind Helper
0.315
233950AC2-186 GEN
Solar/Wind Helper
0.158
232434Z2-077 GEN
Solar/Wind Helper
0.172
233972AC1-094 C
Solar/Wind Helper
0.41
230511AF1-262
Solar/Wind Helper
0.019
230434AG1-499 GEN
Solar/Wind Helper
0.303
228728W1-130C
Solar/Wind Helper
0.071
219258KINSLEYDEP C
Solar/Wind Helper
0.101
219904AC1-010 C
Solar/Wind Helper
0.079
219907AC1-030 C
Solar/Wind Helper
0.044
218660EHAMPSOLAR C
Solar/Wind Helper
0.043
219686LUMSOLAR_N C
Solar/Wind Helper
0.052
219304NAMERICA C
Solar/Wind Helper
0.171
20720728JCB_W1-129
Solar/Wind Helper
0.074
207445AB1-138_GEN
Solar/Wind Helper
0.134
963711AG1-223 GEN
Solar/Wind Helper
0.082
20714828MDF_W3-079
Solar/Wind Helper
0.167
219680HOPEWELLV C1
Solar/Wind Helper
0.004
207454AA2-184 E
Solar/Wind Helper
0.395
20715228NPK_W1-113
Solar/Wind Helper
0.1
20742028HF_AC1-207
Solar/Wind Helper
0.179
218428ETC SOLAR C
Solar/Wind Helper
0.006
217213AMBOY SO C
Solar/Wind Helper
0.036
207528AF2-192 GEN
Solar/Wind Helper
0.096
20673628F1S_V4-069
Solar/Wind Helper
0.037
20675428EAM_W2-061
Solar/Wind Helper
0.02
20676428JCR_X2-075
Solar/Wind Helper
0.085
217209CENTRL HS C
Solar/Wind Helper
0.01
217208PARK ELE C
Solar/Wind Helper
0.006
205941AD2-115 GEN
Solar/Wind Helper
0.613
20674328GAR_V4-001
Solar/Wind Helper
0.028
207439AE1-081 C O1
Solar/Wind Helper
0.023
20675828AU_W4-064
Solar/Wind Helper
0.036
207437AD2-070 GEN
Solar/Wind Helper
0.169
207518AF1-320_GEN
Solar/Wind Helper
1.931
20671928W4-073
Solar/Wind Helper
0.11
961301AF2-421 GEN
Solar/Wind Helper
0.512
963151AG1-164 GEN
Solar/Wind Helper
0.512
212266LOR1
Solar/Wind Helper
0.054
961341AF2-425 GEN
Solar/Wind Helper
0.499
212507AE2-042_GEN
Solar/Wind Helper
1.74
946731AF1-337 GEN
Solar/Wind Helper
0.489
209071AE2-133 GEN
Solar/Wind Helper
0.088
966131AG1-482 GEN
Solar/Wind Helper
0.075
971795AH1-408 GEN
Solar/Wind Harmer
10.192
3150091POSSM6B
50/50
1.654
3150071POSSM 5
50/50
101.841
3150181POSSMC2
50/50
2.247
3150181POSSMC2
50/50
2.228
3150181POSSMC2
50/50
2.228
957191AF2-013 GEN
50/50
16.389
3150391LDYSMT3
50/50
25.778
972195AH1-682 GEN
50/50
3.388
315673AE1-157 GEN
Solar/Wind Harmer
14.947
957411AF2-035 GEN
Solar/Wind Harmer
8.848
970317AG2-208 GEN
Solar/Wind Harmer
8.602
316468AD1-105 GEN
Solar/Wind Harmer
2.147
316077AC2-138 C
Solar/Wind Harmer
0.396
3150341NORNECKC1
Adder
1.751
3150341NORNECKC1
Adder
1.737
958261AF2-120 GEN
Solar/Wind Harmer
7.213
316487AF1-042 GEN
Solar/Wind Harmer
2.439
966871AG1-558 GEN
Solar/Wind Harmer
0.555
966871AG1-558 GEN
Solar/Wind Harmer
0.19
3142296MT RD221
Adder
0.518
316447AC1-158 HLD
Solar/Wind Harmer
3.929
316441AF1-014 GEN
Solar/Wind Harmer
1.225
316075AC2-137 C
Solar/Wind Harmer
0.488
3150691DARBY 3
Adder
11.585
3150701DARBY 4
Adder
11.558
3150681DARBY 2
Adder
11.544
3150671DARBY 1
Adder
11.531
3142366NRTHEST
Adder
0.526
3142946ENON
Solar/Wind Harmer
-0.002
3143526WINTERP
Solar/Wind Harmer
-0.092
971223AH1-071 GEN
Solar/Wind Harmer
2.216
944641AF1-129 GEN
Adder
75.175
316240AF1-291 C
Solar/Wind Harmer
0.533
316033AB2-134 GEN
Solar/Wind Harmer
5.679
315697AD1-025 GEN
Solar/Wind Harmer
3.562
315651AD1-115 GEN
Solar/Wind Harmer
7.681
316236AE1-162_GEN
Solar/Wind Harmer
0.525
970657AG2-426 GEN
Solar/Wind Harmer
5.416
970657AG2-426 GEN
Solar/Wind Harmer
1.133
316036AC1-147 C
Solar/Wind Harmer
0.467
3150991CHESPKB
Adder
1.613
3150991CHESPKB
Adder
1.574
316316AC1-027 C
Solar/Wind Harmer
0.53
3142956BIRDNECK
Solar/Wind Harmer
0.927
316185AD1-033 GEN
Solar/Wind Harmer
1.821
3145506HICKORY
Solar/Wind Harmer
-0.069
3145506HICKORY
Solar/Wind Harmer
-0.041
3145506HICKORY
Solar/Wind Harmer
-0.01
316339AD2-160 GEN
Solar/Wind Harmer
1.161
316018AA1-139 ULT2
Solar/Wind Harmer
1.474
316017AA1-139 ULT1
Solar/Wind Harmer
1.392
3137176SLIGO L2192
Solar/Wind Harmer
-0.068
3146456SLIGO L269
Solar/Wind Harmer
2.03
3130086AYDLETT
Solar/Wind Harmer
-0.068
3146386ELIZ CT
Solar/Wind Harmer
-0.017
966001AG1-469 GEN
Solar/Wind Harmer
0.321
316431W1029_GEN1
Solar/Wind Harmer
3.081
316433W1029_GEN2
Solar/Wind Harmer
3.081
3151731LOISA B
Adder
9.812
3151721LOISA A
Adder
9.761
3146516WINFALL
Solar/Wind Harmer
-0.017
3146516WINFALL
Solar/Wind Harmer
-0.017
3146516WINFALL
Solar/Wind Harmer
-0.017
3146626S HERTFORD
Solar/Wind Harmer
-0.017
3146626S HERTFORD
Solar/Wind Harmer
-0.017
3144356SAPONY
Solar/Wind Harmer
0.589
315742AE1-103 GEN
Solar/Wind Harmer
1.756
3146376EDENTON
Solar/Wind Harmer
0.496
3146376EDENTON
Solar/Wind Harmer
0.496
972185AH1-677 GEN
Adder
8.276
972187AH1-678 GEN
Adder
4.177
970933AG2-581 GEN
Solar/Wind Harmer
15.383
316065AD1-022 GEN
Solar/Wind Harmer
8.157
3145893MURPHYS
Solar/Wind Harmer
0.454
3145893MURPHYS
Solar/Wind Harmer
-0.029
3146173TUNIS
Solar/Wind Harmer
-0.016
3146173TUNIS
Solar/Wind Harmer
-0.016
316181AB2-040 GEN
Solar/Wind Harmer
2.231
970099AG2-077 GEN
Solar/Wind Harmer
19.996
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3144293JTRSVLE
Adder
0.442
3144293JTRSVLE
Adder
0.372
226929AD2-058 GEN
Solar/Wind Helper
0.393
208835TUHI V3-051
Solar/Wind Helper
0.036
208835TUHI V3-051
Solar/Wind Helper
0.036
233933AB2-153 GEN
Solar/Wind Helper
0.317
233944AB2-135 GEN
Solar/Wind Helper
0.802
232424Y1-079 C
Solar/Wind Helper
0.158
233987AB2-037 GEN
Solar/Wind Helper
3.185
234036AF2-325 C
Solar/Wind Helper
0.057
233946AB2-136 GEN
Solar/Wind Helper
0.772
233901CHERRYDALE C
Solar/Wind Helper
0.316
232408W1-005 C
Solar/Wind Helper
0.689
232410W1-006 C
Solar/Wind Helper
0.689
233939AC1-091 C
Solar/Wind Helper
0.474
233970AC1-092 C
Solar/Wind Helper
0.474
230433AD2-135 GEN
Solar/Wind Helper
0.022
230407AD2-065 C
Solar/Wind Helper
0.053
219921AF1-264
Solar/Wind Helper
0.067
219615MILLCREEK C
Solar/Wind Helper
0.035
963401AG1-189 GEN
Solar/Wind Helper
0.072
963391AG1-188 GEN
Solar/Wind Helper
0.106
20714928UPF_X1-085
Solar/Wind Helper
0.007
20720628TIN_W1-124
Solar/Wind Helper
0.242
20716928W4-060COL
Solar/Wind Helper
0.065
218440SUMMTASSOC C
Solar/Wind Helper
0.021
20673828FLE_V3-070
Solar/Wind Helper
0.114
207442AE1-156 GEN
Solar/Wind Helper
0.41
20676128MHD_W3-029
Solar/Wind Helper
0.121
20671828STAW2-080
Solar/Wind Helper
0.033
217081WEATEXAS C
Solar/Wind Helper
0.016
217202FBANKSOLAR C
Solar/Wind Helper
0.004
217201HACKENSOLA C
Solar/Wind Helper
0.004
217206BARNGR HS C
Solar/Wind Helper
0.008
217204WCALDSOLAR C
Solar/Wind Helper
0.004
20676228FRD_X1-012
Solar/Wind Helper
0.113
207471AF2-354 C
Solar/Wind Helper
0.208
20674928WA_W3-044
Solar/Wind Helper
0.121
964851AG1-348 GEN
Solar/Wind Helper
0.099
20674128FR_U2-059
Solar/Wind Helper
0.005
966111AG1-480 GEN
Solar/Wind Helper
0.054
211065PSPA IPP
Solar/Wind Helper
0.182
211065PSPA IPP
Solar/Wind Helper
0.182
208972BECR K09
Solar/Wind Helper
0.376
961431AF2-434 GEN
Solar/Wind Helper
0.497
209029WAYMART-WD
Solar/Wind Helper
0.936
209054AE2-059 GEN
Solar/Wind Helper
0.089
946751AF1-339 GEN
Solar/Wind Helper
0.489
209137AF2-361 C
Solar/Wind Helper
1.35
3150101POSSM6S
50/50
2.528
3150081POSSM6A
50/50
1.654
3150151POSSMC1
50/50
2.228
3150151POSSMC1
50/50
2.228
3150331BIRCHWDA
50/50
34.1
3150021OMF B
50/50
0.367
3141316ARNOLDS
50/50
0.47
3150401LDYSMT4
50/50
25.826
3150371LDYSMT1
50/50
24.955
970497AG2-320 GEN
50/50
16.885
966881AG1-559 GEN
Solar/Wind Harmer
0.591
970737AG2-469 GEN
Solar/Wind Harmer
9.802
3141906WESTMOR
Solar/Wind Harmer
-0.008
971781AH1-399 GEN
Solar/Wind Harmer
1.188
3150351NORNECKC2
Adder
1.695
316404AE1-155 C
Solar/Wind Harmer
3.591
316484AD2-074 GEN
Solar/Wind Harmer
4.661
970009AG2-005 GEN
Solar/Wind Harmer
2.314
316473AC1-191 GEN
Solar/Wind Harmer
1.987
962971AG1-146 GEN
Solar/Wind Harmer
3.46
316044AC1-158 PL1
Solar/Wind Harmer
1.787
316450AC1-158 RIC
Solar/Wind Harmer
0.476
3142416OLDCHRC
Solar/Wind Harmer
1.836
3141766HARMONY
Solar/Wind Harmer
1.619
316156AD2-030 GEN
Solar/Wind Harmer
0.486
3141873WAN 176
Solar/Wind Harmer
2.158
316280AD1-041 GEN
Solar/Wind Harmer
1.37
316203AE2-005 GEN
Solar/Wind Harmer
7.663
3141843SHACKLE
Adder
0.827
3142433PROV 92
Adder
0.313
3142433PROV 92
Adder
0.313
970293AG2-193 GEN
Solar/Wind Harmer
2.261
3143096IRON208
Adder
0.67
3143096IRON208
Adder
0.657
3142946ENON
Solar/Wind Harmer
-0.006
3150861SPRUNCD
Adder
0.733
316382AG1-145 C
Solar/Wind Harmer
0.537
3147666LOUISA
Solar/Wind Harmer
-0.041
970133AG2-095 GEN
Solar/Wind Harmer
1.996
970129AG2-093 GEN
Solar/Wind Harmer
9.954
3150921YORKTN3
Adder
3.952
3144216WINCHST
Adder
0.592
315778AD1-151 GEN
Solar/Wind Harmer
15.278
965281AG1-393 GEN
Solar/Wind Harmer
2.203
315839AE2-212 C
Solar/Wind Harmer
0.53
316170AC1-121 GEN2
Solar/Wind Harmer
0.473
961611AG1-000B GEN
Solar/Wind Harmer
3.695
3151221GRAVEL6
Adder
11.329
3151171GRAVELC
Adder
2.18
3145336SMITFLD
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
10.889
315773AC2-141 GEN
Solar/Wind Harmer
7.274
970659AG2-427 GEN
Solar/Wind Harmer
1.634
3144536CHRHLND
Solar/Wind Harmer
-0.003
316083AB2-161 GEN
Solar/Wind Harmer
2.815
3151101ELIZAR3
Adder
14.297
970661AG2-428 GEN
Solar/Wind Harmer
3.259
3144873MCLAUGH
Solar/Wind Harmer
0
3132273ORANGE
Solar/Wind Harmer
-0.003
944581AF1-123 GEN
Solar/Wind Harmer
78.643
944601AF1-125 GEN
Solar/Wind Harmer
77.415
3146456SLIGO L269
Solar/Wind Harmer
-0.017
971153AH1-033 GEN
Solar/Wind Harmer
2.095
316320Y1-086
Solar/Wind Harmer
1.002
3150301M RUN C
Adder
20.568
3150291M RUN B
Adder
20.415
3150231REMNGT3
Adder
20.661
3150241REMNGT4
Adder
19.264
972199AH1-684 GEN
Adder
2.921
972217AH1-693 GEN
Adder
2.54
316435W1029_GEN3
Solar/Wind Harmer
3.081
3151761LOISA E
Adder
20.004
3146516WINFALL
Solar/Wind Harmer
-0.017
972183AH1-676 GEN
Adder
161.171
3146626S HERTFORD
Solar/Wind Harmer
-0.017
316313AB2-026
Solar/Wind Harmer
0.456
316258AE1-075 C
Solar/Wind Harmer
0.411
316405AF2-144 C
Solar/Wind Harmer
0.433
3143336POWHATN
Solar/Wind Harmer
1.707
3145273HOLLAND
Solar/Wind Harmer
-0.013
3146376EDENTON
Solar/Wind Harmer
-0.017
3141196NOKESVL
Solar/Wind Harmer
-0.067
315614AA2-178 GEN
Solar/Wind Harmer
1.785
971157AH1-035 GEN
Solar/Wind Harmer
2.049
3156081AA2-088 GEN
Solar/Wind Harmer
5.315
315737AD1-076 GEN
Solar/Wind Harmer
3.111
3146206CASHIE
Solar/Wind Harmer
-0.016
316365GEN2_N
Solar/Wind Harmer
1.097
3145893MURPHYS
Solar/Wind Harmer
0.113
3145893MURPHYS
Solar/Wind Harmer
-0.016
957521AF2-046 GEN
Solar/Wind Harmer
12.788
961681AG1-008 GEN
Solar/Wind Harmer
12.788
970917AG2-570 GEN
Solar/Wind Harmer
40.495
3146173TUNIS
Solar/Wind Harmer
-0.016
3156021HOLLOMANSOL
Solar/Wind Harmer
2.177
316463AE2-346 GEN
Solar/Wind Harmer
0.261
316140AB2-099
Solar/Wind Harmer
0.109
962331AG1-082 GEN
Solar/Wind Harmer
2.017
966621AG1-532 GEN
Solar/Wind Harmer
0.326
3146263WOODLND
Solar/Wind Harmer
-0.016
313506AB2-031 GEN
Solar/Wind Harmer
1.286
3145963POPLR C
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
972255AH1-712 GEN
Adder
71.607
3144293JTRSVLE
Adder
0.442
3151861LOWMORA
Adder
1.28
227287AC2-120 GEN
Solar/Wind Helper
1.262
226910AB2-157 C
Solar/Wind Helper
0.049
223402AF1-300 C
Solar/Wind Helper
0.748
233918AB1-142 GEN
Solar/Wind Helper
0.685
233982AB2-133 GEN
Solar/Wind Helper
0.488
233994AC2-023 GEN
Solar/Wind Helper
1.306
233996TM1833_GEN
Solar/Wind Helper
0.355
233997TMININ_4.2
Solar/Wind Helper
0.355
233940AF2-379 C
Solar/Wind Helper
0.084
234015AF2-250 C
Solar/Wind Helper
0.051
232406W1-004 FULL
Solar/Wind Helper
0.689
233952AC2-187 GEN
Solar/Wind Helper
0.315
233971AC1-093 C
Solar/Wind Helper
0.485
230430AE1-229_GEN
Solar/Wind Helper
4.448
230415AB2-049 C
Solar/Wind Helper
0.04
228729W2-030 C
Solar/Wind Helper
0.145
219623KINSLEYBEA C
Solar/Wind Helper
0.003
219766PARADISE C
Solar/Wind Helper
0.072
219912AD2-042 GEN
Solar/Wind Helper
0.196
219291REEVESSOUT C
Solar/Wind Helper
0.015
219236SOUTHERNHQ C
Solar/Wind Helper
0.007
219906AC1-017 C
Solar/Wind Helper
0.054
219348LDSOLAR C
Solar/Wind Helper
0.149
959561AF2-247 GEN
Solar/Wind Helper
0.027
20716028EGP_W2-019
Solar/Wind Helper
0.024
20720828JCB_W4-025
Solar/Wind Helper
0.082
20715028HAN_X4-015
Solar/Wind Helper
0.074
219276PARKLANDSO C
Solar/Wind Helper
0.115
20714528FRN_Y2-051
Solar/Wind Helper
0.073
20720528MAN_W1-024
Solar/Wind Helper
0.036
219612MATRIX C
Solar/Wind Helper
0.03
218438BLK ROCK C
Solar/Wind Helper
0.035
219908AB1-139 C
Solar/Wind Helper
0.093
219919AE1-041 FULL
Solar/Wind Helper
0.005
219249CENTRALDIV C
Solar/Wind Helper
0.013
20673728F2S_V4-070
Solar/Wind Helper
0.037
217211CAMDEN ST C
Solar/Wind Helper
0.006
217169METRODIV C
Solar/Wind Helper
0.005
20676728BRNX1-095
Solar/Wind Helper
0.037
207510AF2-138 C
Solar/Wind Helper
0.1
20674628WNG_W3-110
Solar/Wind Helper
0.11
963161AG1-165 GEN
Solar/Wind Helper
0.512
963071AG1-156 GEN
Solar/Wind Helper
1.658
209027LOR2_Q27
Solar/Wind Helper
1.175
961331AF2-424 GEN
Solar/Wind Helper
0.499
961421AF2-433 GEN
Solar/Wind Helper
0.497
957921AF2-086 GEN
Solar/Wind Helper
0.492
946691AF1-333 GEN
Solar/Wind Helper
0.489
946741AF1-338 GEN
Solar/Wind Helper
0.489
209067AE2-060 GEN
Solar/Wind Helper
0.08
NYPJM->LTFIMP_NY
CLTF
5.379
LGEELTFEXP_LGEE->PJM
CLTF
4.06
WECLTFEXP_WEC->PJM
CLTF
2.182
AG2-052LTFEXP_AG2-052->PJM
LTF
0.13
AH1-155LTFEXP_AH1-155->PJM
LTF
0.195
LAGNLTFEXP_LAGN->PJM
CLTF
13.612
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.468
TVALTFEXP_TVA->PJM
CLTF
6.85
CBM West 1LTFEXP_CBM-W1->PJM
CBM
81.121
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.087
MECLTFEXP_MEC->PJM
CLTF
9.963
SIGELTFEXP_SIGE->PJM
CLTF
0.313
CPLELTFEXP_CPLE->PJM
CLTF
10.068
CBM West 2LTFEXP_CBM-W2->PJM
CBM
85.372

Details for 8POSSUM-BURCHES 500.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019F_SRT-SL


Base Case Flowgate

Area:DVP/PJM
Facility Description:
8POSSUM-BURCHES 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019F_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.21 %
Rating:3099.0 MVA
Rating Type:B
MVA to Mitigate:3322.42
MW Contribution:69.27
Bus #Bus NameTypeMW Contribution
970053AG2-049 GEN
50/50
2.783
3150411LDYSMT5
50/50
22.239
3150381LDYSMT2
50/50
21.283
972213AH1-691 GEN
50/50
3.6
972215AH1-692 GEN
50/50
3.6
963051AG1-154 GEN
50/50
2.769
3141426STAFORD
Solar/Wind Harmer
-0.004
944491AF1-114 GEN
Solar/Wind Harmer
5.027
316223AC1-118
Solar/Wind Harmer
0.446
972189AH1-679 GEN
Adder
2.388
3141813NORNECK
Solar/Wind Harmer
-0.016
962981AG1-147 GEN
Solar/Wind Harmer
6.86
3141783LANCAST
Solar/Wind Harmer
-0.009
3141783LANCAST
Solar/Wind Harmer
-0.006
3138133OCRAN
Solar/Wind Harmer
-0.005
3141913WHIT STONE
Solar/Wind Harmer
-0.015
316312AB1-027
Solar/Wind Harmer
0.52
957601AF2-054 GEN
Solar/Wind Harmer
0.461
316059AD1-063 C
Solar/Wind Harmer
0.349
3141873WAN 176
Solar/Wind Harmer
-0.003
316314AB2-024 C
Solar/Wind Harmer
1.318
315662AE1-191 GEN
Solar/Wind Harmer
1.858
315666AE1-190 GEN
Solar/Wind Harmer
0.465
3143873LANEXA
Solar/Wind Harmer
-0.009
3142433PROV 92
Adder
0.265
3142433PROV 92
Adder
0.265
971167AH1-042 GEN
Solar/Wind Harmer
14.738
315976AC1-164 GENA
Solar/Wind Harmer
16.157
316169AC1-164_GENC
Solar/Wind Harmer
13.958
315975AC1-164 GENB
Solar/Wind Harmer
0.478
957831AF2-077 GEN
Solar/Wind Harmer
0.456
3138283WHITEMARSH
Solar/Wind Harmer
0.023
971285AH1-108 GEN
Adder
1.014
316233AE1-074 FULL
Solar/Wind Harmer
0.405
971281AH1-106 GEN
Solar/Wind Harmer
2.447
971283AH1-107 GEN
Solar/Wind Harmer
2.447
316164AC1-076 GEN
Solar/Wind Harmer
1.264
316132AB2-190 GEN1
Solar/Wind Harmer
1.511
316369SG1_INVT
Solar/Wind Harmer
2.658
972265AH1-717 GEN
Adder
10.215
3151201GRAVEL4
Adder
9.576
3151191GRAVEL3
Adder
9.455
3151211GRAVEL5
Adder
9.455
971445AH1-216 GEN
Solar/Wind Harmer
9.107
3143316POE
Solar/Wind Harmer
-0.058
3151081ELIZAR1
Adder
11.906
3151091ELIZAR2
Adder
11.7
3152611GOSPORTB
Adder
1.654
3152621GOSPORTC
Adder
1.404
3152601GOSPORTA
Adder
1.295
315833AF1-017_GEN
Solar/Wind Harmer
2.757
316349AD2-085 GEN
Solar/Wind Harmer
1.291
316311AC2-079 GEN
Solar/Wind Harmer
7.321
957871AF2-081 GEN
Solar/Wind Harmer
7.253
316305AF2-043 C
Solar/Wind Harmer
0.437
319010AE1-072 C
Solar/Wind Harmer
2.929
3146406KITTY HAWK
Solar/Wind Harmer
0.012
315835AF2-110_GEN
Solar/Wind Harmer
1.806
313526AB2-022
Solar/Wind Harmer
0.389
3146486SUNBURY
Solar/Wind Harmer
-0.014
3146486SUNBURY
Solar/Wind Harmer
-0.014
316321Z2-027
Solar/Wind Harmer
0.388
3145176PASQUOTANK
Solar/Wind Harmer
-0.009
3146396TANGLEW
Solar/Wind Harmer
0.264
316315AB2-025 C
Solar/Wind Harmer
0.383
315611Z1-036_GEN2
Solar/Wind Harmer
3.503
315814AE2-033 C
Solar/Wind Harmer
13.2
941031AE2-094 GEN
Solar/Wind Harmer
26.435
944011AF1-069 GEN
Solar/Wind Harmer
8.283
3130156CHOWAN
Solar/Wind Harmer
-0.014
3130156CHOWAN
Solar/Wind Harmer
-0.014
970673AG2-436 GEN
Solar/Wind Harmer
29.368
970673AG2-436 GEN
Solar/Wind Harmer
14.87
971967AH1-528 GEN
Solar/Wind Harmer
26.154
315816AE2-034 GEN
Solar/Wind Harmer
1.125
3147346CASHSCORNER
Solar/Wind Harmer
0.215
3130546PLYMOUTH
Solar/Wind Harmer
-0.014
315732AD1-074 GEN1
Solar/Wind Harmer
2.781
315733AD1-074 GEN2
Solar/Wind Harmer
2.781
315735AD1-075 GEN1
Solar/Wind Harmer
1.391
965291AG1-394 GEN
Solar/Wind Harmer
1.218
3146206CASHIE
Solar/Wind Harmer
-0.014
970601AG2-382 GEN
Solar/Wind Harmer
5.981
316318V4-068
Solar/Wind Harmer
0.34
3145893MURPHYS
Solar/Wind Harmer
-0.037
3145893MURPHYS
Solar/Wind Harmer
-0.014
970085AG2-068 GEN
Solar/Wind Harmer
8.474
970581AG2-369 GEN
Solar/Wind Harmer
7.288
3145513AHOSKIE
Solar/Wind Harmer
0.118
961941AG1-037 GEN
Solar/Wind Harmer
0.102
3145513AHOSKIE
Solar/Wind Harmer
-0.013
3145683EARLEYS
Solar/Wind Harmer
-0.027
3145683EARLEYS
Solar/Wind Harmer
-0.013
3145683EARLEYS
Solar/Wind Harmer
-0.013
3146043SEABORD
Solar/Wind Harmer
-0.013
946281AF1-292 GEN
Solar/Wind Harmer
0.302
315607AA1-063A GEN
Solar/Wind Harmer
1.361
316087AB2-174 GEN
Solar/Wind Harmer
1.916
972193AH1-681 GEN
Adder
2.656
972205AH1-687 GEN
Adder
4.959
233935AB2-179 C
Solar/Wind Helper
1.252
232436AB1-176 C
Solar/Wind Helper
0.043
233923SMA
Solar/Wind Helper
0.931
233990AG1-397 GEN
Solar/Wind Helper
0.03
232432Z2-076 GEN
Solar/Wind Helper
0.065
234033AF1-007_GEN
Solar/Wind Helper
6.814
960921AF2-383 GEN
Solar/Wind Helper
0.173
315652AC1-086 GEN
Solar/Wind Harmer
5.139
3150101POSSM6S
50/50
2.213
3150081POSSM6A
50/50
1.448
3150151POSSMC1
50/50
1.951
3150151POSSMC1
50/50
1.951
3150331BIRCHWDA
50/50
29.482
3150021OMF B
50/50
0.314
3141316ARNOLDS
50/50
0.405
3150401LDYSMT4
50/50
22.17
3150371LDYSMT1
50/50
21.422
970497AG2-320 GEN
50/50
14.485
966881AG1-559 GEN
Solar/Wind Harmer
0.505
970737AG2-469 GEN
Solar/Wind Harmer
8.391
3141906WESTMOR
Solar/Wind Harmer
-0.007
971781AH1-399 GEN
Solar/Wind Harmer
1.014
3150351NORNECKC2
Adder
1.443
316404AE1-155 C
Solar/Wind Harmer
3.054
316484AD2-074 GEN
Solar/Wind Harmer
3.962
970009AG2-005 GEN
Solar/Wind Harmer
1.967
962971AG1-146 GEN
Solar/Wind Harmer
2.94
316473AC1-191 GEN
Solar/Wind Harmer
1.687
316156AD2-030 GEN
Solar/Wind Harmer
0.412
3141873WAN 176
Solar/Wind Harmer
1.83
3142416OLDCHRC
Solar/Wind Harmer
1.556
3141766HARMONY
Solar/Wind Harmer
1.373
316280AD1-041 GEN
Solar/Wind Harmer
1.161
316203AE2-005 GEN
Solar/Wind Harmer
6.497
3141843SHACKLE
Adder
0.701
3142433PROV 92
Adder
0.265
3142433PROV 92
Adder
0.265
970293AG2-193 GEN
Solar/Wind Harmer
1.915
3142946ENON
Solar/Wind Harmer
-0.005
3143096IRON208
Adder
0.567
3143096IRON208
Adder
0.556
316044AC1-158 PL1
Solar/Wind Harmer
1.49
316450AC1-158 RIC
Solar/Wind Harmer
0.397
3150861SPRUNCD
Adder
0.62
316382AG1-145 C
Solar/Wind Harmer
0.454
970133AG2-095 GEN
Solar/Wind Harmer
1.687
970129AG2-093 GEN
Solar/Wind Harmer
8.412
3150921YORKTN3
Adder
3.34
3144216WINCHST
Adder
0.5
315778AD1-151 GEN
Solar/Wind Harmer
12.908
965281AG1-393 GEN
Solar/Wind Harmer
1.861
3147666LOUISA
Solar/Wind Harmer
-0.034
315839AE2-212 C
Solar/Wind Harmer
0.447
961611AG1-000B GEN
Solar/Wind Harmer
3.12
3151221GRAVEL6
Adder
9.565
3151171GRAVELC
Adder
1.84
3145336SMITFLD
Solar/Wind Harmer
-0.006
315813AE1-149 C
Solar/Wind Harmer
9.189
315773AC2-141 GEN
Solar/Wind Harmer
6.136
970659AG2-427 GEN
Solar/Wind Harmer
1.379
3144536CHRHLND
Solar/Wind Harmer
-0.002
316083AB2-161 GEN
Solar/Wind Harmer
2.375
970661AG2-428 GEN
Solar/Wind Harmer
2.749
3151101ELIZAR3
Adder
12.059
3144873MCLAUGH
Solar/Wind Harmer
0
944581AF1-123 GEN
Solar/Wind Harmer
66.324
944601AF1-125 GEN
Solar/Wind Harmer
65.289
316170AC1-121 GEN2
Solar/Wind Harmer
0.391
3146456SLIGO L269
Solar/Wind Harmer
-0.014
971153AH1-033 GEN
Solar/Wind Harmer
1.766
316320Y1-086
Solar/Wind Harmer
0.844
3132273ORANGE
Solar/Wind Harmer
-0.003
316435W1029_GEN3
Solar/Wind Harmer
2.595
3146516WINFALL
Solar/Wind Harmer
-0.014
3146626S HERTFORD
Solar/Wind Harmer
-0.014
3145273HOLLAND
Solar/Wind Harmer
-0.011
316313AB2-026
Solar/Wind Harmer
0.383
316258AE1-075 C
Solar/Wind Harmer
0.345
316405AF2-144 C
Solar/Wind Harmer
0.364
3143336POWHATN
Solar/Wind Harmer
1.431
3151761LOISA E
Adder
16.592
3146376EDENTON
Solar/Wind Harmer
-0.014
972183AH1-676 GEN
Adder
133.629
3150301M RUN C
Adder
16.786
3150291M RUN B
Adder
16.662
315614AA2-178 GEN
Solar/Wind Harmer
1.5
3150231REMNGT3
Adder
16.854
3150241REMNGT4
Adder
15.715
972199AH1-684 GEN
Adder
2.383
972217AH1-693 GEN
Adder
2.072
971157AH1-035 GEN
Solar/Wind Harmer
1.722
3156081AA2-088 GEN
Solar/Wind Harmer
4.464
315737AD1-076 GEN
Solar/Wind Harmer
2.613
3146206CASHIE
Solar/Wind Harmer
-0.014
3145893MURPHYS
Solar/Wind Harmer
0.095
3145893MURPHYS
Solar/Wind Harmer
-0.014
316365GEN2_N
Solar/Wind Harmer
0.92
957521AF2-046 GEN
Solar/Wind Harmer
10.733
961681AG1-008 GEN
Solar/Wind Harmer
10.733
970917AG2-570 GEN
Solar/Wind Harmer
33.966
3146173TUNIS
Solar/Wind Harmer
-0.014
3156021HOLLOMANSOL
Solar/Wind Harmer
1.827
316463AE2-346 GEN
Solar/Wind Harmer
0.219
316140AB2-099
Solar/Wind Harmer
0.091
962331AG1-082 GEN
Solar/Wind Harmer
1.693
966621AG1-532 GEN
Solar/Wind Harmer
0.274
3141196NOKESVL
Solar/Wind Harmer
-0.054
3146263WOODLND
Solar/Wind Harmer
-0.013
313506AB2-031 GEN
Solar/Wind Harmer
1.078
3145963POPLR C
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
316317KELFORD C
Solar/Wind Harmer
0.63
3145823KELFORD
Solar/Wind Harmer
-0.013
972255AH1-712 GEN
Adder
59.443
3144293JTRSVLE
Adder
0.368
227287AC2-120 GEN
Solar/Wind Helper
1.292
226910AB2-157 C
Solar/Wind Helper
0.05
223402AF1-300 C
Solar/Wind Helper
0.708
233982AB2-133 GEN
Solar/Wind Helper
0.35
233918AB1-142 GEN
Solar/Wind Helper
0.492
233994AC2-023 GEN
Solar/Wind Helper
0.934
233996TM1833_GEN
Solar/Wind Helper
0.254
233997TMININ_4.2
Solar/Wind Helper
0.254
233940AF2-379 C
Solar/Wind Helper
0.06
232406W1-004 FULL
Solar/Wind Helper
0.493
234015AF2-250 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.226
233971AC1-093 C
Solar/Wind Helper
0.346
3150091POSSM6B
50/50
1.448
3150071POSSM 5
50/50
89.158
3150181POSSMC2
50/50
1.967
3150181POSSMC2
50/50
1.951
3150181POSSMC2
50/50
1.951
957191AF2-013 GEN
50/50
14.124
3150391LDYSMT3
50/50
22.128
972195AH1-682 GEN
50/50
2.908
315673AE1-157 GEN
Solar/Wind Harmer
12.798
957411AF2-035 GEN
Solar/Wind Harmer
7.564
970317AG2-208 GEN
Solar/Wind Harmer
7.354
316468AD1-105 GEN
Solar/Wind Harmer
1.833
316077AC2-138 C
Solar/Wind Harmer
0.337
3150341NORNECKC1
Adder
1.491
3150341NORNECKC1
Adder
1.479
958261AF2-120 GEN
Solar/Wind Harmer
6.135
316487AF1-042 GEN
Solar/Wind Harmer
2.073
966871AG1-558 GEN
Solar/Wind Harmer
0.471
966871AG1-558 GEN
Solar/Wind Harmer
0.161
3142296MT RD221
Adder
0.439
316441AF1-014 GEN
Solar/Wind Harmer
1.039
316075AC2-137 C
Solar/Wind Harmer
0.413
3150691DARBY 3
Adder
9.809
3150701DARBY 4
Adder
9.787
3150681DARBY 2
Adder
9.775
3150671DARBY 1
Adder
9.764
3142366NRTHEST
Adder
0.445
3142946ENON
Solar/Wind Harmer
-0.002
316447AC1-158 HLD
Solar/Wind Harmer
3.277
3143526WINTERP
Solar/Wind Harmer
-0.078
944641AF1-129 GEN
Adder
63.531
971223AH1-071 GEN
Solar/Wind Harmer
1.869
316240AF1-291 C
Solar/Wind Harmer
0.45
316033AB2-134 GEN
Solar/Wind Harmer
4.797
315697AD1-025 GEN
Solar/Wind Harmer
3.009
316236AE1-162_GEN
Solar/Wind Harmer
0.443
970657AG2-426 GEN
Solar/Wind Harmer
4.568
970657AG2-426 GEN
Solar/Wind Harmer
0.955
316036AC1-147 C
Solar/Wind Harmer
0.394
3150991CHESPKB
Adder
1.36
3150991CHESPKB
Adder
1.328
316316AC1-027 C
Solar/Wind Harmer
0.447
3142956BIRDNECK
Solar/Wind Harmer
0.782
316185AD1-033 GEN
Solar/Wind Harmer
1.536
3145506HICKORY
Solar/Wind Harmer
-0.058
3145506HICKORY
Solar/Wind Harmer
-0.035
3145506HICKORY
Solar/Wind Harmer
-0.009
316339AD2-160 GEN
Solar/Wind Harmer
0.979
316018AA1-139 ULT2
Solar/Wind Harmer
1.243
316017AA1-139 ULT1
Solar/Wind Harmer
1.174
3137176SLIGO L2192
Solar/Wind Harmer
-0.057
3146456SLIGO L269
Solar/Wind Harmer
1.711
3130086AYDLETT
Solar/Wind Harmer
-0.058
315651AD1-115 GEN
Solar/Wind Harmer
6.347
3146386ELIZ CT
Solar/Wind Harmer
-0.014
316431W1029_GEN1
Solar/Wind Harmer
2.595
316433W1029_GEN2
Solar/Wind Harmer
2.595
3146516WINFALL
Solar/Wind Harmer
-0.014
3146516WINFALL
Solar/Wind Harmer
-0.014
3146516WINFALL
Solar/Wind Harmer
-0.014
3146626S HERTFORD
Solar/Wind Harmer
-0.014
3146626S HERTFORD
Solar/Wind Harmer
-0.014
3144356SAPONY
Solar/Wind Harmer
0.495
315742AE1-103 GEN
Solar/Wind Harmer
1.477
966001AG1-469 GEN
Solar/Wind Harmer
0.267
3151731LOISA B
Adder
8.139
3151721LOISA A
Adder
8.097
3146376EDENTON
Solar/Wind Harmer
0.418
3146376EDENTON
Solar/Wind Harmer
0.418
972185AH1-677 GEN
Adder
6.952
972187AH1-678 GEN
Adder
3.508
970933AG2-581 GEN
Solar/Wind Harmer
12.91
316065AD1-022 GEN
Solar/Wind Harmer
6.85
3145893MURPHYS
Solar/Wind Harmer
0.381
3145893MURPHYS
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.014
3146173TUNIS
Solar/Wind Harmer
-0.014
316181AB2-040 GEN
Solar/Wind Harmer
1.87
970099AG2-077 GEN
Solar/Wind Harmer
16.745
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3144293JTRSVLE
Adder
0.368
3144293JTRSVLE
Adder
0.31
226929AD2-058 GEN
Solar/Wind Helper
0.403
208835TUHI V3-051
Solar/Wind Helper
0.031
208835TUHI V3-051
Solar/Wind Helper
0.031
233933AB2-153 GEN
Solar/Wind Helper
0.227
233944AB2-135 GEN
Solar/Wind Helper
0.575
232424Y1-079 C
Solar/Wind Helper
0.113
233987AB2-037 GEN
Solar/Wind Helper
2.278
234036AF2-325 C
Solar/Wind Helper
0.041
233946AB2-136 GEN
Solar/Wind Helper
0.552
233901CHERRYDALE C
Solar/Wind Helper
0.226
232408W1-005 C
Solar/Wind Helper
0.493
232410W1-006 C
Solar/Wind Helper
0.493
233939AC1-091 C
Solar/Wind Helper
0.339
233970AC1-092 C
Solar/Wind Helper
0.339
972223AH1-696 GEN
50/50
15.409
3150151POSSMC1
50/50
1.951
3141346CRANES
50/50
0.214
3150011OMF A
50/50
0.314
3140676OCCOQUN
50/50
0.417
972197AH1-683 GEN
50/50
3.462
972219AH1-694 GEN
50/50
2.493
957971AF2-091 GEN
Solar/Wind Harmer
1.709
972135AH1-637 GEN
Solar/Wind Harmer
1.695
966881AG1-559 GEN
Solar/Wind Harmer
0.173
316337AD2-073 GEN
Solar/Wind Harmer
0.437
3150351NORNECKC2
Adder
1.419
964211AG1-282 GEN
Solar/Wind Harmer
0.479
3141726DUNNSVL
Solar/Wind Harmer
-0.063
962861AG1-135 GEN
Solar/Wind Harmer
5.928
961951AG1-038 GEN
Solar/Wind Harmer
2.073
3138133OCRAN
Solar/Wind Harmer
-0.009
3142416OLDCHRC
Solar/Wind Harmer
-0.04
3142416OLDCHRC
Solar/Wind Harmer
-0.015
3141766HARMONY
Solar/Wind Harmer
-0.003
971777AH1-397 GEN
Solar/Wind Harmer
1.812
3141843SHACKLE
Adder
0.701
3142433PROV 92
Solar/Wind Harmer
-0.061
3142433PROV 92
Adder
0.265
3142433PROV 92
Adder
0.265
3143096IRON208
Adder
0.567
316045AC1-158 PL2
Solar/Wind Harmer
4.767
944631AF1-128 GEN
Adder
64.359
3142543TWELFTH
Solar/Wind Harmer
-0.001
3150851SPRUNCC
Adder
0.62
316159AE1-175 C
Solar/Wind Harmer
0.404
3143526WINTERP
Solar/Wind Harmer
-0.078
971317AH1-138 GEN
Solar/Wind Harmer
1.879
3143226MDLTHAN
Solar/Wind Harmer
-0.015
970129AG2-093 GEN
Solar/Wind Harmer
3.407
316458AB2-190 GEN2
Solar/Wind Harmer
1.511
315671AE2-027_GEN
Solar/Wind Harmer
11.189
3138126ROCKLANDING
Solar/Wind Harmer
0.046
971069AG2-661 GEN
Solar/Wind Harmer
2.358
3147666LOUISA
Solar/Wind Harmer
-0.059
971647AH1-324 GEN
Solar/Wind Harmer
7.424
961611AG1-000B GEN
Solar/Wind Harmer
7.313
316192AB2-158 GEN
Solar/Wind Harmer
1.761
3151171GRAVELC
Adder
1.4
3145336SMITFLD
Solar/Wind Harmer
-0.059
316294AC1-161 GEN
Solar/Wind Harmer
4.745
970659AG2-427 GEN
Solar/Wind Harmer
7.779
316381AD1-082 GEN
Solar/Wind Harmer
1.342
970661AG2-428 GEN
Solar/Wind Harmer
15.511
316375AC2-012 GEN
Solar/Wind Harmer
5.05
3150981CHESPKA
Adder
1.622
944591AF1-124 GEN
Solar/Wind Harmer
66.562
316072AD1-144
Solar/Wind Harmer
0.295
316254AC1-120 GEN1
Solar/Wind Harmer
1.174
316388AE2-253 GEN
Solar/Wind Harmer
0.979
3146456SLIGO L269
Solar/Wind Harmer
-0.014
316246AF1-032 C
Solar/Wind Harmer
0.293
316093AE2-104_GEN
Solar/Wind Harmer
4.2
939411AE1-173 GEN
Solar/Wind Harmer
72.191
940641AE2-051 GEN
Solar/Wind Harmer
13.499
3146516WINFALL
Solar/Wind Harmer
-0.046
3146516WINFALL
Solar/Wind Harmer
-0.014
3143336POWHATN
Solar/Wind Harmer
1.684
315800Z1-036_GEN1
Solar/Wind Harmer
3.503
3151751LOISA D
Adder
8.139
3130156CHOWAN
Solar/Wind Harmer
-0.014
316006AB2-029 C
Solar/Wind Harmer
0.804
971685AH1-345 GEN
Solar/Wind Harmer
1.226
315683AE1-153 C
Solar/Wind Harmer
13.032
316336AC2-165 C
Solar/Wind Harmer
2.431
3150281M RUN A
Adder
16.797
3145663CRESWEL
Solar/Wind Harmer
-0.039
971163AH1-040 GEN
Solar/Wind Harmer
13.037
3150221REMNGT2
Adder
15.611
3150211REMNGT1
Adder
15.507
972201AH1-685 GEN
Adder
2.693
3146206CASHIE
Solar/Wind Harmer
-0.014
971547AH1-271 GEN
Solar/Wind Harmer
3.418
3145893MURPHYS
Solar/Wind Harmer
-0.054
3145893MURPHYS
Solar/Wind Harmer
0.405
316023GEN1_S
Solar/Wind Harmer
0.92
970919AG2-571 GEN
Solar/Wind Harmer
4.3
3146173TUNIS
Solar/Wind Harmer
-0.014
970087AG2-069 GEN
Solar/Wind Harmer
12.711
3145683EARLEYS
Solar/Wind Harmer
-0.013
960081AF2-299 GEN
Solar/Wind Harmer
1.517
970937AG2-583 GEN
Solar/Wind Harmer
9.686
3146263WOODLND
Solar/Wind Harmer
-0.013
957481AF2-042 GEN
Solar/Wind Harmer
41.862
3145963POPLR C
Solar/Wind Harmer
-0.013
3145823KELFORD
Solar/Wind Harmer
-0.013
316011AB1-132 GEN
Solar/Wind Harmer
2.795
3147043LAWRENC
Adder
1.071
972277AH1-723 GEN
Adder
69.269
3144293JTRSVLE
Adder
0.368
223401AF1-299 GEN
Solar/Wind Helper
0.708
233930AB2-032 GEN
Solar/Wind Helper
0.373
233915AB1-141 GEN
Solar/Wind Helper
0.492
232422X3-066 FULL
Solar/Wind Helper
0.112
233964AF2-378 GEN
Solar/Wind Helper
0.041
232426Y1-080 FULL
Solar/Wind Helper
0.038
232428Y3-058 C
Solar/Wind Helper
0.328
233998TM1NIN_3.36
Solar/Wind Helper
0.254
232404W1-003 C
Solar/Wind Helper
0.493
233954AC2-188 GEN
Solar/Wind Helper
0.226
233950AC2-186 GEN
Solar/Wind Helper
0.113
232434Z2-077 GEN
Solar/Wind Helper
0.123
233972AC1-094 C
Solar/Wind Helper
0.293
NYPJM->LTFIMP_NY
CLTF
3.821
LGEELTFEXP_LGEE->PJM
CLTF
3.225
WECLTFEXP_WEC->PJM
CLTF
1.731
AG2-052LTFEXP_AG2-052->PJM
LTF
0.103
AH1-155LTFEXP_AH1-155->PJM
LTF
0.154
LAGNLTFEXP_LAGN->PJM
CLTF
10.958
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.907
TVALTFEXP_TVA->PJM
CLTF
5.516
CBM West 1LTFEXP_CBM-W1->PJM
CBM
64.289
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.158
MECLTFEXP_MEC->PJM
CLTF
7.931
SIGELTFEXP_SIGE->PJM
CLTF
0.249
CPLELTFEXP_CPLE->PJM
CLTF
8.326
CBM West 2LTFEXP_CBM-W2->PJM
CBM
68.371

Details for 8POSSUM-BURCHES 500.0 kV Ckt 1 line l/o AP_P1-2_PE-500-406T_SRT-A


Base Case Flowgate

Area:DVP/PJM
Facility Description:
8POSSUM-BURCHES 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-500-406T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.05 %
Rating:2913.06 MVA
Rating Type:B
MVA to Mitigate:3060.21
MW Contribution:68.71
Bus #Bus NameTypeMW Contribution
3150101POSSM6S
50/50
2.207
3150081POSSM6A
50/50
1.444
3150151POSSMC1
50/50
1.946
3150151POSSMC1
50/50
1.946
3150331BIRCHWDA
50/50
29.368
3150021OMF B
50/50
0.313
3141316ARNOLDS
50/50
0.404
3150401LDYSMT4
50/50
22.067
3150371LDYSMT1
50/50
21.323
970497AG2-320 GEN
50/50
14.416
970737AG2-469 GEN
Solar/Wind Harmer
6.342
3141906WESTMOR
Solar/Wind Harmer
0.059
971781AH1-399 GEN
Solar/Wind Harmer
0.191
3150351NORNECKC2
Adder
1.435
316404AE1-155 C
Solar/Wind Harmer
0.032
970009AG2-005 GEN
Solar/Wind Harmer
1.04
962971AG1-146 GEN
Solar/Wind Harmer
2.22
316473AC1-191 GEN
Solar/Wind Harmer
0.469
316156AD2-030 GEN
Solar/Wind Harmer
0.101
3141873WAN 176
Solar/Wind Harmer
2.426
3141766HARMONY
Solar/Wind Harmer
1.82
3142416OLDCHRC
Solar/Wind Harmer
1.322
316280AD1-041 GEN
Solar/Wind Harmer
0.003
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3141843SHACKLE
Adder
0.697
3142433PROV 92
Adder
0.264
3142433PROV 92
Adder
0.264
970293AG2-193 GEN
Solar/Wind Harmer
1.446
3142946ENON
Solar/Wind Harmer
0.045
3143096IRON208
Adder
0.563
3143096IRON208
Adder
0.552
316044AC1-158 PL1
Solar/Wind Harmer
0.654
316450AC1-158 RIC
Solar/Wind Harmer
0.174
3150861SPRUNCD
Adder
0.616
316382AG1-145 C
Solar/Wind Harmer
0.001
970133AG2-095 GEN
Solar/Wind Harmer
1.273
970129AG2-093 GEN
Solar/Wind Harmer
7.987
3150921YORKTN3
Adder
3.319
3144216WINCHST
Adder
0.497
315778AD1-151 GEN
Solar/Wind Harmer
10.543
965281AG1-393 GEN
Solar/Wind Harmer
1.404
315839AE2-212 C
Solar/Wind Harmer
0.001
3147666LOUISA
Solar/Wind Harmer
0.302
961611AG1-000B GEN
Solar/Wind Harmer
3.495
3151221GRAVEL6
Adder
9.505
3151171GRAVELC
Adder
1.829
3145336SMITFLD
Solar/Wind Harmer
0.052
315813AE1-149 C
Solar/Wind Harmer
6.935
315773AC2-141 GEN
Solar/Wind Harmer
4.737
970659AG2-427 GEN
Solar/Wind Harmer
1.37
3144536CHRHLND
Solar/Wind Harmer
0.019
316083AB2-161 GEN
Solar/Wind Harmer
0.002
970661AG2-428 GEN
Solar/Wind Harmer
2.731
3151101ELIZAR3
Adder
11.981
3144873MCLAUGH
Solar/Wind Harmer
0.003
944581AF1-123 GEN
Solar/Wind Harmer
29.029
944601AF1-125 GEN
Solar/Wind Harmer
28.582
316170AC1-121 GEN2
Solar/Wind Harmer
0.137
3146456SLIGO L269
Solar/Wind Harmer
0.128
971153AH1-033 GEN
Solar/Wind Harmer
1.481
316320Y1-086
Solar/Wind Harmer
0.001
3132273ORANGE
Solar/Wind Harmer
0.025
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.126
3146626S HERTFORD
Solar/Wind Harmer
0.126
3145273HOLLAND
Solar/Wind Harmer
0.094
316313AB2-026
Solar/Wind Harmer
0.079
316258AE1-075 C
Solar/Wind Harmer
0.095
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
1.895
3146376EDENTON
Solar/Wind Harmer
0.124
3151761LOISA E
Adder
16.466
972183AH1-676 GEN
Adder
132.605
315614AA2-178 GEN
Solar/Wind Harmer
0.703
3150301M RUN C
Adder
16.643
3150291M RUN B
Adder
16.52
3150231REMNGT3
Adder
16.71
3150241REMNGT4
Adder
15.58
972199AH1-684 GEN
Adder
2.362
972217AH1-693 GEN
Adder
2.054
971157AH1-035 GEN
Solar/Wind Harmer
1.461
3156081AA2-088 GEN
Solar/Wind Harmer
0.003
315737AD1-076 GEN
Solar/Wind Harmer
1.564
3146206CASHIE
Solar/Wind Harmer
0.121
3145893MURPHYS
Solar/Wind Harmer
0.202
3145893MURPHYS
Solar/Wind Harmer
0.121
316365GEN2_N
Solar/Wind Harmer
0.271
957521AF2-046 GEN
Solar/Wind Harmer
8.962
961681AG1-008 GEN
Solar/Wind Harmer
8.962
970917AG2-570 GEN
Solar/Wind Harmer
10.673
3146173TUNIS
Solar/Wind Harmer
0.12
3156021HOLLOMANSOL
Solar/Wind Harmer
0.544
316463AE2-346 GEN
Solar/Wind Harmer
0.103
316140AB2-099
Solar/Wind Harmer
0.043
962331AG1-082 GEN
Solar/Wind Harmer
1.276
3141196NOKESVL
Solar/Wind Harmer
0.475
3146263WOODLND
Solar/Wind Harmer
0.119
313506AB2-031 GEN
Solar/Wind Harmer
0.366
3145963POPLR C
Solar/Wind Harmer
0.118
3142666NORTHAMPTON
Solar/Wind Harmer
0.118
316317KELFORD C
Solar/Wind Harmer
0.011
3145823KELFORD
Solar/Wind Harmer
0.118
3147043LAWRENC
Solar/Wind Harmer
0.071
3145796HORNRTN
Solar/Wind Harmer
0.468
3145796HORNRTN
Solar/Wind Harmer
0.117
970909AG2-566 GEN
Solar/Wind Harmer
1.246
316478AD1-087 GEN
Solar/Wind Harmer
0.406
316486AD2-202 GEN
Solar/Wind Harmer
0.119
3146926FARMVIL
Solar/Wind Harmer
0.07
316210AC1-098 GEN
Solar/Wind Harmer
1.074
3146776BUCKING
Solar/Wind Harmer
0.042
3145933PARMELE
Solar/Wind Harmer
0.115
966801AG1-551 GEN
Solar/Wind Harmer
1.346
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
972255AH1-712 GEN
Adder
58.961
3147133PAMPLIN
Solar/Wind Harmer
0.361
971193AH1-056 GEN
Solar/Wind Harmer
7.005
963181AG1-167 GEN
Solar/Wind Harmer
0.459
3144293JTRSVLE
Adder
0.366
959311AF2-222 GEN
Solar/Wind Harmer
10.172
970257AG2-171 GEN
Solar/Wind Harmer
3.659
3145746EVERETS
Solar/Wind Harmer
0.114
3145746EVERETS
Solar/Wind Harmer
0.114
315785AD2-033 C
Solar/Wind Harmer
0.929
964241AG1-285 GEN
Solar/Wind Harmer
7.598
315724AD1-057 GEN
Solar/Wind Harmer
0.428
316131AB2-060 GEN
Solar/Wind Harmer
0.358
316327AA2-057 GEN
Solar/Wind Harmer
0.171
970221AG2-151 GEN
Solar/Wind Harmer
6.002
227287AC2-120 GEN
Solar/Wind Helper
1.283
226910AB2-157 C
Solar/Wind Helper
0.05
223402AF1-300 C
Solar/Wind Helper
0.698
233918AB1-142 GEN
Solar/Wind Helper
0.486
233982AB2-133 GEN
Solar/Wind Helper
0.346
233994AC2-023 GEN
Solar/Wind Helper
0.923
233996TM1833_GEN
Solar/Wind Helper
0.251
233997TMININ_4.2
Solar/Wind Helper
0.251
233940AF2-379 C
Solar/Wind Helper
0.06
234015AF2-250 C
Solar/Wind Helper
0.036
232406W1-004 FULL
Solar/Wind Helper
0.487
233952AC2-187 GEN
Solar/Wind Helper
0.223
233971AC1-093 C
Solar/Wind Helper
0.342
970053AG2-049 GEN
50/50
2.771
3150411LDYSMT5
50/50
22.136
3150381LDYSMT2
50/50
21.185
972213AH1-691 GEN
50/50
3.584
972215AH1-692 GEN
50/50
3.584
963051AG1-154 GEN
50/50
2.757
3141426STAFORD
Solar/Wind Harmer
0.039
944491AF1-114 GEN
Solar/Wind Harmer
0
316223AC1-118
Solar/Wind Harmer
0.105
972189AH1-679 GEN
Adder
2.375
3141813NORNECK
Solar/Wind Harmer
0.141
970327AG2-215 GEN
Solar/Wind Harmer
4.571
962981AG1-147 GEN
Solar/Wind Harmer
5.181
3141783LANCAST
Solar/Wind Harmer
0.083
3141783LANCAST
Solar/Wind Harmer
0.055
3138133OCRAN
Solar/Wind Harmer
0.041
3141913WHIT STONE
Solar/Wind Harmer
0.137
3141873WAN 176
Solar/Wind Harmer
0.027
316059AD1-063 C
Solar/Wind Harmer
0.001
316314AB2-024 C
Solar/Wind Harmer
0
316312AB1-027
Solar/Wind Harmer
0.244
315662AE1-191 GEN
Solar/Wind Harmer
0.004
315666AE1-190 GEN
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.04
3143873LANEXA
Solar/Wind Harmer
0.082
3142433PROV 92
Adder
0.264
3142433PROV 92
Adder
0.264
971167AH1-042 GEN
Solar/Wind Harmer
12.03
315976AC1-164 GENA
Solar/Wind Harmer
14.027
316169AC1-164_GENC
Solar/Wind Harmer
12.118
315975AC1-164 GENB
Solar/Wind Harmer
0.415
3138283WHITEMARSH
Solar/Wind Harmer
0.031
971285AH1-108 GEN
Adder
1.008
316233AE1-074 FULL
Solar/Wind Harmer
0.107
971281AH1-106 GEN
Solar/Wind Harmer
1.847
971283AH1-107 GEN
Solar/Wind Harmer
1.847
316164AC1-076 GEN
Solar/Wind Harmer
0.186
316132AB2-190 GEN1
Solar/Wind Harmer
0.709
316369SG1_INVT
Solar/Wind Harmer
0.005
972265AH1-717 GEN
Adder
10.151
3151201GRAVEL4
Adder
9.516
3151191GRAVEL3
Adder
9.395
3151211GRAVEL5
Adder
9.395
971445AH1-216 GEN
Solar/Wind Harmer
9.164
3143316POE
Solar/Wind Harmer
0.514
3151081ELIZAR1
Adder
11.83
3151091ELIZAR2
Adder
11.624
3152611GOSPORTB
Adder
1.643
3152621GOSPORTC
Adder
1.395
3152601GOSPORTA
Adder
1.287
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.088
316311AC2-079 GEN
Solar/Wind Harmer
3.686
957871AF2-081 GEN
Solar/Wind Harmer
6.385
316305AF2-043 C
Solar/Wind Harmer
0.001
319010AE1-072 C
Solar/Wind Harmer
0.645
3146406KITTY HAWK
Solar/Wind Harmer
0.016
315835AF2-110_GEN
Solar/Wind Harmer
0.877
313526AB2-022
Solar/Wind Harmer
0.069
3146486SUNBURY
Solar/Wind Harmer
0.127
3146486SUNBURY
Solar/Wind Harmer
0.127
316321Z2-027
Solar/Wind Harmer
0.024
3146396TANGLEW
Solar/Wind Harmer
0.35
3145176PASQUOTANK
Solar/Wind Harmer
0.079
316315AB2-025 C
Solar/Wind Harmer
0.101
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
315814AE2-033 C
Solar/Wind Harmer
9.914
941031AE2-094 GEN
Solar/Wind Harmer
22.955
944011AF1-069 GEN
Solar/Wind Harmer
7.5
3130156CHOWAN
Solar/Wind Harmer
0.124
3130156CHOWAN
Solar/Wind Harmer
0.124
970673AG2-436 GEN
Solar/Wind Harmer
26.361
970673AG2-436 GEN
Solar/Wind Harmer
17.574
971967AH1-528 GEN
Solar/Wind Harmer
19.675
315816AE2-034 GEN
Solar/Wind Harmer
0.528
3147346CASHSCORNER
Solar/Wind Harmer
0.285
3130546PLYMOUTH
Solar/Wind Harmer
0.122
315732AD1-074 GEN1
Solar/Wind Harmer
0.698
315733AD1-074 GEN2
Solar/Wind Harmer
0.698
315735AD1-075 GEN1
Solar/Wind Harmer
0.35
965291AG1-394 GEN
Solar/Wind Harmer
0.539
3146206CASHIE
Solar/Wind Harmer
0.121
970601AG2-382 GEN
Solar/Wind Harmer
4.511
3145893MURPHYS
Solar/Wind Harmer
0.326
3145893MURPHYS
Solar/Wind Harmer
0.121
970085AG2-068 GEN
Solar/Wind Harmer
6.391
970581AG2-369 GEN
Solar/Wind Harmer
5.496
3145513AHOSKIE
Solar/Wind Harmer
0.25
3145513AHOSKIE
Solar/Wind Harmer
0.12
3145683EARLEYS
Solar/Wind Harmer
0.239
3145683EARLEYS
Solar/Wind Harmer
0.119
3145683EARLEYS
Solar/Wind Harmer
0.119
3146043SEABORD
Solar/Wind Harmer
0.119
315607AA1-063A GEN
Solar/Wind Harmer
0.243
316087AB2-174 GEN
Solar/Wind Harmer
0.003
315652AC1-086 GEN
Solar/Wind Harmer
12.981
3137643SOCKMAN
Solar/Wind Harmer
0.471
3145796HORNRTN
Solar/Wind Harmer
0.374
3145796HORNRTN
Solar/Wind Harmer
0.047
3146033SCOT NK
Solar/Wind Harmer
0.467
970285AG2-188 GEN
Solar/Wind Harmer
9.159
971845AH1-439 GEN
Solar/Wind Harmer
5.245
970831AG2-522 GEN
Solar/Wind Harmer
4.918
972193AH1-681 GEN
Adder
2.634
972205AH1-687 GEN
Adder
4.919
315657AE1-056 GEN
Solar/Wind Harmer
3.968
946301AF1-294 GEN
Solar/Wind Harmer
2.267
961791AG1-021 GEN
Solar/Wind Harmer
1.103
970683AG2-441 GEN
Solar/Wind Harmer
7.642
970681AG2-440 GEN
Solar/Wind Harmer
6.113
3144303KENBRDG
Solar/Wind Harmer
0.091
971443AH1-215 GEN
Solar/Wind Harmer
1.921
316005AA1-067
Solar/Wind Harmer
0.123
3145746EVERETS
Solar/Wind Harmer
0.455
3145746EVERETS
Solar/Wind Harmer
0.114
3145746EVERETS
Solar/Wind Harmer
0.114
3145746EVERETS
Solar/Wind Harmer
0.114
970181AG2-120 GEN
Solar/Wind Harmer
1.422
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
957861AF2-080 GEN
Solar/Wind Harmer
4.883
316420AA1-050 GEN
Solar/Wind Harmer
0.004
233935AB2-179 C
Solar/Wind Helper
1.237
232436AB1-176 C
Solar/Wind Helper
0.043
233923SMA
Solar/Wind Helper
0.92
233990AG1-397 GEN
Solar/Wind Helper
0.259
232432Z2-076 GEN
Solar/Wind Helper
0.064
234033AF1-007_GEN
Solar/Wind Helper
6.733
972223AH1-696 GEN
50/50
15.369
3150151POSSMC1
50/50
1.946
3141346CRANES
50/50
0.214
3150011OMF A
50/50
0.313
3140676OCCOQUN
50/50
0.415
972197AH1-683 GEN
50/50
3.446
972219AH1-694 GEN
50/50
2.481
972135AH1-637 GEN
Solar/Wind Harmer
1.281
966881AG1-559 GEN
Solar/Wind Harmer
0.172
316337AD2-073 GEN
Solar/Wind Harmer
0.125
3150351NORNECKC2
Adder
1.412
3141726DUNNSVL
Solar/Wind Harmer
0.564
962861AG1-135 GEN
Solar/Wind Harmer
4.477
3138133OCRAN
Solar/Wind Harmer
0.082
3141766HARMONY
Solar/Wind Harmer
0.027
3142416OLDCHRC
Solar/Wind Harmer
0.355
3142416OLDCHRC
Solar/Wind Harmer
0.136
971777AH1-397 GEN
Solar/Wind Harmer
0.36
3141843SHACKLE
Adder
0.697
3142433PROV 92
Solar/Wind Harmer
0.542
3142433PROV 92
Adder
0.264
3142433PROV 92
Adder
0.264
3143096IRON208
Adder
0.563
316045AC1-158 PL2
Solar/Wind Harmer
2.091
944631AF1-128 GEN
Adder
63.967
3142543TWELFTH
Solar/Wind Harmer
0.013
3150851SPRUNCC
Adder
0.616
316159AE1-175 C
Solar/Wind Harmer
0.115
3143526WINTERP
Solar/Wind Harmer
0.692
971317AH1-138 GEN
Solar/Wind Harmer
0.993
3143226MDLTHAN
Solar/Wind Harmer
0.132
970129AG2-093 GEN
Solar/Wind Harmer
3.759
316458AB2-190 GEN2
Solar/Wind Harmer
0.709
315671AE2-027_GEN
Solar/Wind Harmer
8.445
3138126ROCKLANDING
Solar/Wind Harmer
0.061
971069AG2-661 GEN
Solar/Wind Harmer
2.343
971647AH1-324 GEN
Solar/Wind Harmer
5.603
3147666LOUISA
Solar/Wind Harmer
0.525
961611AG1-000B GEN
Solar/Wind Harmer
6.873
316192AB2-158 GEN
Solar/Wind Harmer
0.74
3151171GRAVELC
Adder
1.391
3145336SMITFLD
Solar/Wind Harmer
0.52
316294AC1-161 GEN
Solar/Wind Harmer
2.247
970659AG2-427 GEN
Solar/Wind Harmer
6.262
316381AD1-082 GEN
Solar/Wind Harmer
0.135
970661AG2-428 GEN
Solar/Wind Harmer
12.841
316375AC2-012 GEN
Solar/Wind Harmer
0.003
3150981CHESPKA
Adder
1.611
944591AF1-124 GEN
Solar/Wind Harmer
29.132
316072AD1-144
Solar/Wind Harmer
0.047
316254AC1-120 GEN1
Solar/Wind Harmer
0.274
316388AE2-253 GEN
Solar/Wind Harmer
0.402
3146456SLIGO L269
Solar/Wind Harmer
0.128
316246AF1-032 C
Solar/Wind Harmer
0.058
316093AE2-104_GEN
Solar/Wind Harmer
2.148
939411AE1-173 GEN
Solar/Wind Harmer
54.47
940641AE2-051 GEN
Solar/Wind Harmer
10.185
3146516WINFALL
Solar/Wind Harmer
0.409
3146516WINFALL
Solar/Wind Harmer
0.126
3143336POWHATN
Solar/Wind Harmer
2.23
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.124
3151751LOISA D
Adder
8.077
316006AB2-029 C
Solar/Wind Harmer
0.001
971685AH1-345 GEN
Solar/Wind Harmer
0.923
316336AC2-165 C
Solar/Wind Harmer
0.005
315683AE1-153 C
Solar/Wind Harmer
9.818
3145663CRESWEL
Solar/Wind Harmer
0.344
971163AH1-040 GEN
Solar/Wind Harmer
9.834
3150281M RUN A
Adder
16.653
3150221REMNGT2
Adder
15.477
3150211REMNGT1
Adder
15.375
972201AH1-685 GEN
Adder
2.67
3146206CASHIE
Solar/Wind Harmer
0.121
971547AH1-271 GEN
Solar/Wind Harmer
2.578
3145893MURPHYS
Solar/Wind Harmer
0.482
3145893MURPHYS
Solar/Wind Harmer
0.536
316023GEN1_S
Solar/Wind Harmer
0.271
970919AG2-571 GEN
Solar/Wind Harmer
4.269
3146173TUNIS
Solar/Wind Harmer
0.12
970087AG2-069 GEN
Solar/Wind Harmer
9.586
3145683EARLEYS
Solar/Wind Harmer
0.119
960081AF2-299 GEN
Solar/Wind Harmer
1.144
970937AG2-583 GEN
Solar/Wind Harmer
7.301
3146263WOODLND
Solar/Wind Harmer
0.119
957481AF2-042 GEN
Solar/Wind Harmer
31.564
3145963POPLR C
Solar/Wind Harmer
0.118
3145823KELFORD
Solar/Wind Harmer
0.118
316011AB1-132 GEN
Solar/Wind Harmer
2.146
971795AH1-408 GEN
Solar/Wind Harmer
7.87
962571AG1-106 GEN
Solar/Wind Harmer
1.679
316190AA2-174 GEN
Solar/Wind Harmer
0
315693AD1-088 GEN
Solar/Wind Harmer
5.655
316174AB2-169 GEN
Solar/Wind Harmer
0.003
962491AG1-098 GEN
Solar/Wind Harmer
6.721
3147043LAWRENC
Adder
1.063
3145783HORNRTN
Solar/Wind Harmer
0.117
3145796HORNRTN
Solar/Wind Harmer
0.386
3145796HORNRTN
Solar/Wind Harmer
0.117
3146926FARMVIL
Solar/Wind Harmer
0.07
316212AC1-099_GEN
Solar/Wind Harmer
0.599
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.046
3146293MARTNCO
Solar/Wind Harmer
0.107
972003AH1-546 GEN
Solar/Wind Harmer
4.897
972277AH1-723 GEN
Adder
68.708
316129AC1-054 GEN
Solar/Wind Harmer
0.433
963171AG1-166 GEN
Solar/Wind Harmer
0.613
971563AH1-280 GEN
Solar/Wind Harmer
1.225
3144293JTRSVLE
Adder
0.366
971065AG2-659 GEN
Solar/Wind Harmer
4.897
970685AG2-442 GEN
Solar/Wind Harmer
8.558
3145746EVERETS
Solar/Wind Harmer
0.114
3145746EVERETS
Solar/Wind Harmer
0.114
315722AD1-056 GEN
Solar/Wind Harmer
0.721
316237AB2-079_GEN
Solar/Wind Harmer
0.001
316494AC1-189 GEN
Solar/Wind Harmer
0.383
315687AD1-152 GEN
Solar/Wind Harmer
0.004
971377AH1-170 GEN
Solar/Wind Harmer
1.2
3147623JAMES R
Solar/Wind Harmer
0.261
223401AF1-299 GEN
Solar/Wind Helper
0.698
233930AB2-032 GEN
Solar/Wind Helper
0.368
233915AB1-141 GEN
Solar/Wind Helper
0.486
232422X3-066 FULL
Solar/Wind Helper
0.11
233964AF2-378 GEN
Solar/Wind Helper
0.04
232426Y1-080 FULL
Solar/Wind Helper
0.037
232428Y3-058 C
Solar/Wind Helper
0.325
233998TM1NIN_3.36
Solar/Wind Helper
0.251
232404W1-003 C
Solar/Wind Helper
0.487
233954AC2-188 GEN
Solar/Wind Helper
0.223
233950AC2-186 GEN
Solar/Wind Helper
0.111
232434Z2-077 GEN
Solar/Wind Helper
0.122
233972AC1-094 C
Solar/Wind Helper
0.289
3150091POSSM6B
50/50
1.444
3150071POSSM 5
50/50
88.927
3150181POSSMC2
50/50
1.962
3150181POSSMC2
50/50
1.946
3150181POSSMC2
50/50
1.946
957191AF2-013 GEN
50/50
14.065
3150391LDYSMT3
50/50
22.026
972195AH1-682 GEN
50/50
2.894
315673AE1-157 GEN
Solar/Wind Harmer
10.452
957411AF2-035 GEN
Solar/Wind Harmer
6.351
970317AG2-208 GEN
Solar/Wind Harmer
5.884
316468AD1-105 GEN
Solar/Wind Harmer
-0.047
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
1.483
3150341NORNECKC1
Adder
1.471
958261AF2-120 GEN
Solar/Wind Harmer
4.633
966871AG1-558 GEN
Solar/Wind Harmer
0.16
3142296MT RD221
Adder
0.436
316075AC2-137 C
Solar/Wind Harmer
0.037
3150691DARBY 3
Adder
9.75
3150701DARBY 4
Adder
9.728
3150681DARBY 2
Adder
9.716
3150671DARBY 1
Adder
9.705
3142366NRTHEST
Adder
0.443
3142946ENON
Solar/Wind Harmer
0.013
316447AC1-158 HLD
Solar/Wind Harmer
1.437
3143526WINTERP
Solar/Wind Harmer
0.692
944641AF1-129 GEN
Adder
63.136
971223AH1-071 GEN
Solar/Wind Harmer
1.411
316240AF1-291 C
Solar/Wind Harmer
0.001
316033AB2-134 GEN
Solar/Wind Harmer
0.008
315697AD1-025 GEN
Solar/Wind Harmer
0.148
316236AE1-162_GEN
Solar/Wind Harmer
0.001
970657AG2-426 GEN
Solar/Wind Harmer
4.528
970657AG2-426 GEN
Solar/Wind Harmer
0.949
316036AC1-147 C
Solar/Wind Harmer
0.024
3150991CHESPKB
Adder
1.352
3150991CHESPKB
Adder
1.319
316316AC1-027 C
Solar/Wind Harmer
0.124
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.004
3145506HICKORY
Solar/Wind Harmer
0.514
3145506HICKORY
Solar/Wind Harmer
0.308
3145506HICKORY
Solar/Wind Harmer
0.077
316339AD2-160 GEN
Solar/Wind Harmer
0.208
316018AA1-139 ULT2
Solar/Wind Harmer
0.003
316017AA1-139 ULT1
Solar/Wind Harmer
0.072
3137176SLIGO L2192
Solar/Wind Harmer
0.51
3146456SLIGO L269
Solar/Wind Harmer
2.267
3130086AYDLETT
Solar/Wind Harmer
0.512
315651AD1-115 GEN
Solar/Wind Harmer
0.004
3146386ELIZ CT
Solar/Wind Harmer
0.127
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.126
3146516WINFALL
Solar/Wind Harmer
0.126
3146516WINFALL
Solar/Wind Harmer
0.126
3146626S HERTFORD
Solar/Wind Harmer
0.126
3146626S HERTFORD
Solar/Wind Harmer
0.126
3144356SAPONY
Solar/Wind Harmer
1.05
315742AE1-103 GEN
Solar/Wind Harmer
0.001
966001AG1-469 GEN
Solar/Wind Harmer
0.073
3146376EDENTON
Solar/Wind Harmer
0.553
3146376EDENTON
Solar/Wind Harmer
0.553
3151731LOISA B
Adder
8.077
3151721LOISA A
Adder
8.035
972185AH1-677 GEN
Adder
6.905
972187AH1-678 GEN
Adder
3.484
970933AG2-581 GEN
Solar/Wind Harmer
9.737
316065AD1-022 GEN
Solar/Wind Harmer
5.575
3145893MURPHYS
Solar/Wind Harmer
0.807
3145893MURPHYS
Solar/Wind Harmer
0.217
3146173TUNIS
Solar/Wind Harmer
0.12
3146173TUNIS
Solar/Wind Harmer
0.12
316181AB2-040 GEN
Solar/Wind Harmer
0.172
970099AG2-077 GEN
Solar/Wind Harmer
12.626
3142666NORTHAMPTON
Solar/Wind Harmer
0.118
3142666NORTHAMPTON
Solar/Wind Harmer
0.118
3142666NORTHAMPTON
Solar/Wind Harmer
0.118
3142666NORTHAMPTON
Solar/Wind Harmer
0.071
316426AA2-053 GEN
Solar/Wind Harmer
0.398
3145593CAROLNA
Solar/Wind Harmer
0.118
3145593CAROLNA
Solar/Wind Harmer
0.118
966811AG1-552 GEN
Solar/Wind Harmer
1.276
3145593CAROLNA
Solar/Wind Harmer
0.146
3145783HORNRTN
Solar/Wind Harmer
2.085
3145783HORNRTN
Solar/Wind Harmer
1.668
3145783HORNRTN
Solar/Wind Harmer
0.521
3145783HORNRTN
Solar/Wind Harmer
0.209
3145796HORNRTN
Solar/Wind Harmer
0.351
971741AH1-377 GEN
Solar/Wind Harmer
11.611
970301AG2-198 GEN
Solar/Wind Harmer
4.984
3146776BUCKING
Solar/Wind Harmer
0.462
3146776BUCKING
Solar/Wind Harmer
0.037
3145933PARMELE
Solar/Wind Harmer
0.231
3145933PARMELE
Solar/Wind Harmer
0.115
316274AC1-208 GEN
Solar/Wind Harmer
0.598
3147133PAMPLIN
Solar/Wind Harmer
0.115
3147133PAMPLIN
Solar/Wind Harmer
0.092
958211AF2-115 GEN
Solar/Wind Harmer
1.378
963191AG1-168 GEN
Solar/Wind Harmer
0.459
3144293JTRSVLE
Adder
0.366
3144293JTRSVLE
Adder
0.308
316034AC1-036 C
Solar/Wind Harmer
0.008
970323AG2-213 GEN
Solar/Wind Harmer
4.879
971775AH1-396 GEN
Solar/Wind Harmer
0.183
313527AB2-043 GEN
Solar/Wind Harmer
0.001
939181AE1-148 GEN
Solar/Wind Harmer
5.453
971489AH1-241 GEN
Solar/Wind Harmer
6.002
226929AD2-058 GEN
Solar/Wind Helper
0.401
208835TUHI V3-051
Solar/Wind Helper
0.03
208835TUHI V3-051
Solar/Wind Helper
0.03
233933AB2-153 GEN
Solar/Wind Helper
0.225
233944AB2-135 GEN
Solar/Wind Helper
0.569
232424Y1-079 C
Solar/Wind Helper
0.112
233987AB2-037 GEN
Solar/Wind Helper
2.251
234036AF2-325 C
Solar/Wind Helper
0.04
233946AB2-136 GEN
Solar/Wind Helper
0.546
233901CHERRYDALE C
Solar/Wind Helper
0.223
232408W1-005 C
Solar/Wind Helper
0.487
232410W1-006 C
Solar/Wind Helper
0.487
233939AC1-091 C
Solar/Wind Helper
0.335
233970AC1-092 C
Solar/Wind Helper
0.335
NYPJM->LTFIMP_NY
CLTF
3.769
LGEELTFEXP_LGEE->PJM
CLTF
3.18
WECLTFEXP_WEC->PJM
CLTF
1.706
AG2-052LTFEXP_AG2-052->PJM
LTF
0.101
AH1-155LTFEXP_AH1-155->PJM
LTF
0.152
LAGNLTFEXP_LAGN->PJM
CLTF
10.825
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.705
TVALTFEXP_TVA->PJM
CLTF
5.449
CBM West 1LTFEXP_CBM-W1->PJM
CBM
63.366
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.907
MECLTFEXP_MEC->PJM
CLTF
7.822
SIGELTFEXP_SIGE->PJM
CLTF
0.246
CPLELTFEXP_CPLE->PJM
CLTF
8.254
CBM West 2LTFEXP_CBM-W2->PJM
CBM
67.489

Details for 8POSSUM-BURCHES 500.0 kV Ckt 1 line l/o PEPCO_P4_PP41_SRT-A


Base Case Flowgate

Area:DVP/PJM
Facility Description:
8POSSUM-BURCHES 500.0 kV Ckt 1 line
Contingency Name:
PEPCO_P4_PP41_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.72 %
Rating:3099.0 MVA
Rating Type:B
MVA to Mitigate:3214.41
MW Contribution:69.2
Bus #Bus NameTypeMW Contribution
3150101POSSM6S
50/50
2.218
3150081POSSM6A
50/50
1.451
3150151POSSMC1
50/50
1.955
3150151POSSMC1
50/50
1.955
3150331BIRCHWDA
50/50
29.526
3150021OMF B
50/50
0.315
3141316ARNOLDS
50/50
0.406
3150401LDYSMT4
50/50
22.193
3150371LDYSMT1
50/50
21.444
970497AG2-320 GEN
50/50
14.499
966881AG1-559 GEN
Solar/Wind Harmer
0.506
970737AG2-469 GEN
Solar/Wind Harmer
8.399
3141906WESTMOR
Solar/Wind Harmer
-0.007
971781AH1-399 GEN
Solar/Wind Harmer
1.015
3150351NORNECKC2
Adder
1.444
316404AE1-155 C
Solar/Wind Harmer
3.056
316484AD2-074 GEN
Solar/Wind Harmer
3.964
970009AG2-005 GEN
Solar/Wind Harmer
1.968
962971AG1-146 GEN
Solar/Wind Harmer
2.941
316473AC1-191 GEN
Solar/Wind Harmer
1.687
316156AD2-030 GEN
Solar/Wind Harmer
0.412
3141873WAN 176
Solar/Wind Harmer
1.831
3142416OLDCHRC
Solar/Wind Harmer
1.556
3141766HARMONY
Solar/Wind Harmer
1.373
316280AD1-041 GEN
Solar/Wind Harmer
1.162
316203AE2-005 GEN
Solar/Wind Harmer
6.499
3141843SHACKLE
Adder
0.701
3142433PROV 92
Adder
0.265
3142433PROV 92
Adder
0.265
970293AG2-193 GEN
Solar/Wind Harmer
1.915
3142946ENON
Solar/Wind Harmer
-0.005
3143096IRON208
Adder
0.567
3143096IRON208
Adder
0.556
316044AC1-158 PL1
Solar/Wind Harmer
1.49
316450AC1-158 RIC
Solar/Wind Harmer
0.397
3150861SPRUNCD
Adder
0.62
316382AG1-145 C
Solar/Wind Harmer
0.454
970133AG2-095 GEN
Solar/Wind Harmer
1.687
970129AG2-093 GEN
Solar/Wind Harmer
8.413
3150921YORKTN3
Adder
3.34
3144216WINCHST
Adder
0.5
315778AD1-151 GEN
Solar/Wind Harmer
12.909
965281AG1-393 GEN
Solar/Wind Harmer
1.861
3147666LOUISA
Solar/Wind Harmer
-0.034
315839AE2-212 C
Solar/Wind Harmer
0.447
961611AG1-000B GEN
Solar/Wind Harmer
3.12
3151221GRAVEL6
Adder
9.566
3151171GRAVELC
Adder
1.84
3145336SMITFLD
Solar/Wind Harmer
-0.006
315813AE1-149 C
Solar/Wind Harmer
9.19
315773AC2-141 GEN
Solar/Wind Harmer
6.136
970659AG2-427 GEN
Solar/Wind Harmer
1.379
3144536CHRHLND
Solar/Wind Harmer
-0.002
316083AB2-161 GEN
Solar/Wind Harmer
2.375
970661AG2-428 GEN
Solar/Wind Harmer
2.749
3151101ELIZAR3
Adder
12.058
3144873MCLAUGH
Solar/Wind Harmer
0
944581AF1-123 GEN
Solar/Wind Harmer
66.322
944601AF1-125 GEN
Solar/Wind Harmer
65.287
316170AC1-121 GEN2
Solar/Wind Harmer
0.391
3146456SLIGO L269
Solar/Wind Harmer
-0.014
971153AH1-033 GEN
Solar/Wind Harmer
1.766
316320Y1-086
Solar/Wind Harmer
0.844
3132273ORANGE
Solar/Wind Harmer
-0.003
316435W1029_GEN3
Solar/Wind Harmer
2.595
3146516WINFALL
Solar/Wind Harmer
-0.014
3146626S HERTFORD
Solar/Wind Harmer
-0.014
3145273HOLLAND
Solar/Wind Harmer
-0.011
316313AB2-026
Solar/Wind Harmer
0.383
316258AE1-075 C
Solar/Wind Harmer
0.344
316405AF2-144 C
Solar/Wind Harmer
0.363
3143336POWHATN
Solar/Wind Harmer
1.431
3151761LOISA E
Adder
16.586
3146376EDENTON
Solar/Wind Harmer
-0.014
972183AH1-676 GEN
Adder
133.578
3150301M RUN C
Adder
16.781
3150291M RUN B
Adder
16.656
315614AA2-178 GEN
Solar/Wind Harmer
1.5
3150231REMNGT3
Adder
16.848
3150241REMNGT4
Adder
15.709
972199AH1-684 GEN
Adder
2.382
972217AH1-693 GEN
Adder
2.071
971157AH1-035 GEN
Solar/Wind Harmer
1.721
3156081AA2-088 GEN
Solar/Wind Harmer
4.463
315737AD1-076 GEN
Solar/Wind Harmer
2.612
3146206CASHIE
Solar/Wind Harmer
-0.014
3145893MURPHYS
Solar/Wind Harmer
0.095
3145893MURPHYS
Solar/Wind Harmer
-0.014
316365GEN2_N
Solar/Wind Harmer
0.92
957521AF2-046 GEN
Solar/Wind Harmer
10.729
961681AG1-008 GEN
Solar/Wind Harmer
10.729
970917AG2-570 GEN
Solar/Wind Harmer
33.953
3146173TUNIS
Solar/Wind Harmer
-0.014
3156021HOLLOMANSOL
Solar/Wind Harmer
1.826
316463AE2-346 GEN
Solar/Wind Harmer
0.219
316140AB2-099
Solar/Wind Harmer
0.091
962331AG1-082 GEN
Solar/Wind Harmer
1.692
966621AG1-532 GEN
Solar/Wind Harmer
0.274
3141196NOKESVL
Solar/Wind Harmer
-0.054
3146263WOODLND
Solar/Wind Harmer
-0.013
313506AB2-031 GEN
Solar/Wind Harmer
1.077
3145963POPLR C
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
316317KELFORD C
Solar/Wind Harmer
0.629
3145823KELFORD
Solar/Wind Harmer
-0.013
972255AH1-712 GEN
Adder
59.381
3144293JTRSVLE
Adder
0.368
227287AC2-120 GEN
Solar/Wind Helper
1.281
226910AB2-157 C
Solar/Wind Helper
0.05
972223AH1-696 GEN
50/50
15.444
3150151POSSMC1
50/50
1.955
3141346CRANES
50/50
0.215
3150011OMF A
50/50
0.315
3140676OCCOQUN
50/50
0.417
972197AH1-683 GEN
50/50
3.465
972219AH1-694 GEN
50/50
2.495
957971AF2-091 GEN
Solar/Wind Harmer
1.711
972135AH1-637 GEN
Solar/Wind Harmer
1.697
966881AG1-559 GEN
Solar/Wind Harmer
0.173
316337AD2-073 GEN
Solar/Wind Harmer
0.437
3150351NORNECKC2
Adder
1.42
964211AG1-282 GEN
Solar/Wind Harmer
0.479
3141726DUNNSVL
Solar/Wind Harmer
-0.063
962861AG1-135 GEN
Solar/Wind Harmer
5.93
961951AG1-038 GEN
Solar/Wind Harmer
2.074
3138133OCRAN
Solar/Wind Harmer
-0.009
3142416OLDCHRC
Solar/Wind Harmer
-0.04
3142416OLDCHRC
Solar/Wind Harmer
-0.015
3141766HARMONY
Solar/Wind Harmer
-0.003
971777AH1-397 GEN
Solar/Wind Harmer
1.812
3141843SHACKLE
Adder
0.701
3142433PROV 92
Solar/Wind Harmer
-0.061
3142433PROV 92
Adder
0.265
3142433PROV 92
Adder
0.265
3143096IRON208
Adder
0.567
316045AC1-158 PL2
Solar/Wind Harmer
4.768
944631AF1-128 GEN
Adder
64.371
3142543TWELFTH
Solar/Wind Harmer
-0.001
3150851SPRUNCC
Adder
0.62
316159AE1-175 C
Solar/Wind Harmer
0.404
3143526WINTERP
Solar/Wind Harmer
-0.078
971317AH1-138 GEN
Solar/Wind Harmer
1.879
3143226MDLTHAN
Solar/Wind Harmer
-0.015
970129AG2-093 GEN
Solar/Wind Harmer
3.408
316458AB2-190 GEN2
Solar/Wind Harmer
1.511
3138126ROCKLANDING
Solar/Wind Harmer
0.046
315671AE2-027_GEN
Solar/Wind Harmer
11.19
971069AG2-661 GEN
Solar/Wind Harmer
2.358
3147666LOUISA
Solar/Wind Harmer
-0.059
971647AH1-324 GEN
Solar/Wind Harmer
7.424
961611AG1-000B GEN
Solar/Wind Harmer
7.313
316192AB2-158 GEN
Solar/Wind Harmer
1.761
3151171GRAVELC
Adder
1.4
3145336SMITFLD
Solar/Wind Harmer
-0.059
316294AC1-161 GEN
Solar/Wind Harmer
4.745
970659AG2-427 GEN
Solar/Wind Harmer
7.779
316381AD1-082 GEN
Solar/Wind Harmer
1.342
970661AG2-428 GEN
Solar/Wind Harmer
15.511
316375AC2-012 GEN
Solar/Wind Harmer
5.05
3150981CHESPKA
Adder
1.622
944591AF1-124 GEN
Solar/Wind Harmer
66.561
316072AD1-144
Solar/Wind Harmer
0.295
316254AC1-120 GEN1
Solar/Wind Harmer
1.174
316388AE2-253 GEN
Solar/Wind Harmer
0.979
3146456SLIGO L269
Solar/Wind Harmer
-0.014
316246AF1-032 C
Solar/Wind Harmer
0.293
316093AE2-104_GEN
Solar/Wind Harmer
4.2
939411AE1-173 GEN
Solar/Wind Harmer
72.185
940641AE2-051 GEN
Solar/Wind Harmer
13.497
3146516WINFALL
Solar/Wind Harmer
-0.046
3146516WINFALL
Solar/Wind Harmer
-0.014
3143336POWHATN
Solar/Wind Harmer
1.683
315800Z1-036_GEN1
Solar/Wind Harmer
3.502
3151751LOISA D
Adder
8.136
3130156CHOWAN
Solar/Wind Harmer
-0.014
316006AB2-029 C
Solar/Wind Harmer
0.804
971685AH1-345 GEN
Solar/Wind Harmer
1.225
315683AE1-153 C
Solar/Wind Harmer
13.027
316336AC2-165 C
Solar/Wind Harmer
2.43
3150281M RUN A
Adder
16.791
3145663CRESWEL
Solar/Wind Harmer
-0.039
971163AH1-040 GEN
Solar/Wind Harmer
13.033
3150221REMNGT2
Adder
15.606
3150211REMNGT1
Adder
15.502
972201AH1-685 GEN
Adder
2.692
3146206CASHIE
Solar/Wind Harmer
-0.014
971547AH1-271 GEN
Solar/Wind Harmer
3.417
3145893MURPHYS
Solar/Wind Harmer
-0.054
3145893MURPHYS
Solar/Wind Harmer
0.405
316023GEN1_S
Solar/Wind Harmer
0.92
970919AG2-571 GEN
Solar/Wind Harmer
4.298
3146173TUNIS
Solar/Wind Harmer
-0.014
970087AG2-069 GEN
Solar/Wind Harmer
12.706
3145683EARLEYS
Solar/Wind Harmer
-0.013
960081AF2-299 GEN
Solar/Wind Harmer
1.517
970937AG2-583 GEN
Solar/Wind Harmer
9.68
3146263WOODLND
Solar/Wind Harmer
-0.013
957481AF2-042 GEN
Solar/Wind Harmer
41.84
3145963POPLR C
Solar/Wind Harmer
-0.013
316011AB1-132 GEN
Solar/Wind Harmer
2.794
3145823KELFORD
Solar/Wind Harmer
-0.013
3147043LAWRENC
Adder
1.071
972277AH1-723 GEN
Adder
69.197
3144293JTRSVLE
Adder
0.368
223401AF1-299 GEN
Solar/Wind Helper
0.699
233930AB2-032 GEN
Solar/Wind Helper
0.373
233915AB1-141 GEN
Solar/Wind Helper
0.492
232422X3-066 FULL
Solar/Wind Helper
0.112
233964AF2-378 GEN
Solar/Wind Helper
0.041
232426Y1-080 FULL
Solar/Wind Helper
0.038
232428Y3-058 C
Solar/Wind Helper
0.329
233998TM1NIN_3.36
Solar/Wind Helper
0.254
232404W1-003 C
Solar/Wind Helper
0.493
233954AC2-188 GEN
Solar/Wind Helper
0.226
233950AC2-186 GEN
Solar/Wind Helper
0.113
232434Z2-077 GEN
Solar/Wind Helper
0.123
3150091POSSM6B
50/50
1.451
3150071POSSM 5
50/50
89.359
3150181POSSMC2
50/50
1.972
3150181POSSMC2
50/50
1.955
3150181POSSMC2
50/50
1.955
957191AF2-013 GEN
50/50
14.143
3150391LDYSMT3
50/50
22.151
972195AH1-682 GEN
50/50
2.911
315673AE1-157 GEN
Solar/Wind Harmer
12.809
957411AF2-035 GEN
Solar/Wind Harmer
7.57
970317AG2-208 GEN
Solar/Wind Harmer
7.36
316468AD1-105 GEN
Solar/Wind Harmer
1.834
316077AC2-138 C
Solar/Wind Harmer
0.338
3150341NORNECKC1
Adder
1.492
3150341NORNECKC1
Adder
1.48
958261AF2-120 GEN
Solar/Wind Harmer
6.138
316487AF1-042 GEN
Solar/Wind Harmer
2.074
966871AG1-558 GEN
Solar/Wind Harmer
0.471
966871AG1-558 GEN
Solar/Wind Harmer
0.161
3142296MT RD221
Adder
0.439
316441AF1-014 GEN
Solar/Wind Harmer
1.039
316075AC2-137 C
Solar/Wind Harmer
0.413
3150691DARBY 3
Adder
9.812
3150701DARBY 4
Adder
9.789
3150681DARBY 2
Adder
9.777
3150671DARBY 1
Adder
9.766
3142366NRTHEST
Adder
0.445
3142946ENON
Solar/Wind Harmer
-0.002
316447AC1-158 HLD
Solar/Wind Harmer
3.278
3143526WINTERP
Solar/Wind Harmer
-0.078
944641AF1-129 GEN
Adder
63.538
971223AH1-071 GEN
Solar/Wind Harmer
1.869
316240AF1-291 C
Solar/Wind Harmer
0.45
316033AB2-134 GEN
Solar/Wind Harmer
4.798
315697AD1-025 GEN
Solar/Wind Harmer
3.009
316236AE1-162_GEN
Solar/Wind Harmer
0.443
970657AG2-426 GEN
Solar/Wind Harmer
4.568
970657AG2-426 GEN
Solar/Wind Harmer
0.955
316036AC1-147 C
Solar/Wind Harmer
0.394
3150991CHESPKB
Adder
1.36
3150991CHESPKB
Adder
1.328
316316AC1-027 C
Solar/Wind Harmer
0.447
3142956BIRDNECK
Solar/Wind Harmer
0.782
316185AD1-033 GEN
Solar/Wind Harmer
1.536
3145506HICKORY
Solar/Wind Harmer
-0.058
3145506HICKORY
Solar/Wind Harmer
-0.035
3145506HICKORY
Solar/Wind Harmer
-0.009
316339AD2-160 GEN
Solar/Wind Harmer
0.979
316018AA1-139 ULT2
Solar/Wind Harmer
1.243
316017AA1-139 ULT1
Solar/Wind Harmer
1.174
3137176SLIGO L2192
Solar/Wind Harmer
-0.057
3146456SLIGO L269
Solar/Wind Harmer
1.711
3130086AYDLETT
Solar/Wind Harmer
-0.058
315651AD1-115 GEN
Solar/Wind Harmer
6.346
3146386ELIZ CT
Solar/Wind Harmer
-0.014
316431W1029_GEN1
Solar/Wind Harmer
2.595
316433W1029_GEN2
Solar/Wind Harmer
2.595
3146516WINFALL
Solar/Wind Harmer
-0.014
3146516WINFALL
Solar/Wind Harmer
-0.014
3146516WINFALL
Solar/Wind Harmer
-0.014
3146626S HERTFORD
Solar/Wind Harmer
-0.014
3146626S HERTFORD
Solar/Wind Harmer
-0.014
3144356SAPONY
Solar/Wind Harmer
0.495
315742AE1-103 GEN
Solar/Wind Harmer
1.477
966001AG1-469 GEN
Solar/Wind Harmer
0.266
3151731LOISA B
Adder
8.136
3151721LOISA A
Adder
8.094
3146376EDENTON
Solar/Wind Harmer
0.418
3146376EDENTON
Solar/Wind Harmer
0.418
972185AH1-677 GEN
Adder
6.951
972187AH1-678 GEN
Adder
3.507
970933AG2-581 GEN
Solar/Wind Harmer
12.906
316065AD1-022 GEN
Solar/Wind Harmer
6.847
3145893MURPHYS
Solar/Wind Harmer
0.381
3145893MURPHYS
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.014
3146173TUNIS
Solar/Wind Harmer
-0.014
316181AB2-040 GEN
Solar/Wind Harmer
1.869
970099AG2-077 GEN
Solar/Wind Harmer
16.736
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3144293JTRSVLE
Adder
0.368
3144293JTRSVLE
Adder
0.31
226929AD2-058 GEN
Solar/Wind Helper
0.4
208835TUHI V3-051
Solar/Wind Helper
0.031
208835TUHI V3-051
Solar/Wind Helper
0.031
233933AB2-153 GEN
Solar/Wind Helper
0.228
233944AB2-135 GEN
Solar/Wind Helper
0.576
232424Y1-079 C
Solar/Wind Helper
0.114
233987AB2-037 GEN
Solar/Wind Helper
2.282
234036AF2-325 C
Solar/Wind Helper
0.041
233946AB2-136 GEN
Solar/Wind Helper
0.553
233901CHERRYDALE C
Solar/Wind Helper
0.226
232408W1-005 C
Solar/Wind Helper
0.493
232410W1-006 C
Solar/Wind Helper
0.493
233939AC1-091 C
Solar/Wind Helper
0.339
233970AC1-092 C
Solar/Wind Helper
0.339
970053AG2-049 GEN
50/50
2.789
3150411LDYSMT5
50/50
22.262
3150381LDYSMT2
50/50
21.306
972213AH1-691 GEN
50/50
3.604
972215AH1-692 GEN
50/50
3.604
963051AG1-154 GEN
50/50
2.772
3141426STAFORD
Solar/Wind Harmer
-0.004
944491AF1-114 GEN
Solar/Wind Harmer
5.033
316223AC1-118
Solar/Wind Harmer
0.446
972189AH1-679 GEN
Adder
2.389
3141813NORNECK
Solar/Wind Harmer
-0.016
962981AG1-147 GEN
Solar/Wind Harmer
6.863
3141783LANCAST
Solar/Wind Harmer
-0.009
3141783LANCAST
Solar/Wind Harmer
-0.006
3138133OCRAN
Solar/Wind Harmer
-0.005
3141913WHIT STONE
Solar/Wind Harmer
-0.015
957601AF2-054 GEN
Solar/Wind Harmer
0.462
3141873WAN 176
Solar/Wind Harmer
-0.003
316314AB2-024 C
Solar/Wind Harmer
1.319
316312AB1-027
Solar/Wind Harmer
0.52
316059AD1-063 C
Solar/Wind Harmer
0.349
315662AE1-191 GEN
Solar/Wind Harmer
1.859
315666AE1-190 GEN
Solar/Wind Harmer
0.465
3143873LANEXA
Solar/Wind Harmer
-0.009
3142433PROV 92
Adder
0.265
3142433PROV 92
Adder
0.265
971167AH1-042 GEN
Solar/Wind Harmer
14.742
315976AC1-164 GENA
Solar/Wind Harmer
16.161
316169AC1-164_GENC
Solar/Wind Harmer
13.961
315975AC1-164 GENB
Solar/Wind Harmer
0.478
957831AF2-077 GEN
Solar/Wind Harmer
0.456
3138283WHITEMARSH
Solar/Wind Harmer
0.023
971285AH1-108 GEN
Adder
1.015
316233AE1-074 FULL
Solar/Wind Harmer
0.405
971281AH1-106 GEN
Solar/Wind Harmer
2.447
971283AH1-107 GEN
Solar/Wind Harmer
2.447
316164AC1-076 GEN
Solar/Wind Harmer
1.264
316132AB2-190 GEN1
Solar/Wind Harmer
1.511
316369SG1_INVT
Solar/Wind Harmer
2.658
972265AH1-717 GEN
Adder
10.216
3151201GRAVEL4
Adder
9.577
3151191GRAVEL3
Adder
9.455
3151211GRAVEL5
Adder
9.455
971445AH1-216 GEN
Solar/Wind Harmer
9.107
3143316POE
Solar/Wind Harmer
-0.058
3151081ELIZAR1
Adder
11.906
3151091ELIZAR2
Adder
11.699
3152611GOSPORTB
Adder
1.654
3152621GOSPORTC
Adder
1.404
3152601GOSPORTA
Adder
1.295
315833AF1-017_GEN
Solar/Wind Harmer
2.757
316349AD2-085 GEN
Solar/Wind Harmer
1.291
316311AC2-079 GEN
Solar/Wind Harmer
7.321
957871AF2-081 GEN
Solar/Wind Harmer
7.252
316305AF2-043 C
Solar/Wind Harmer
0.436
319010AE1-072 C
Solar/Wind Harmer
2.929
3146406KITTY HAWK
Solar/Wind Harmer
0.012
315835AF2-110_GEN
Solar/Wind Harmer
1.806
313526AB2-022
Solar/Wind Harmer
0.389
3146486SUNBURY
Solar/Wind Harmer
-0.014
3146486SUNBURY
Solar/Wind Harmer
-0.014
316321Z2-027
Solar/Wind Harmer
0.388
3145176PASQUOTANK
Solar/Wind Harmer
-0.009
3146396TANGLEW
Solar/Wind Harmer
0.264
316315AB2-025 C
Solar/Wind Harmer
0.383
315611Z1-036_GEN2
Solar/Wind Harmer
3.502
315814AE2-033 C
Solar/Wind Harmer
13.198
941031AE2-094 GEN
Solar/Wind Harmer
26.429
944011AF1-069 GEN
Solar/Wind Harmer
8.281
3130156CHOWAN
Solar/Wind Harmer
-0.014
3130156CHOWAN
Solar/Wind Harmer
-0.014
970673AG2-436 GEN
Solar/Wind Harmer
29.36
970673AG2-436 GEN
Solar/Wind Harmer
14.866
971967AH1-528 GEN
Solar/Wind Harmer
26.146
315816AE2-034 GEN
Solar/Wind Harmer
1.125
3147346CASHSCORNER
Solar/Wind Harmer
0.215
3130546PLYMOUTH
Solar/Wind Harmer
-0.014
315732AD1-074 GEN1
Solar/Wind Harmer
2.78
315733AD1-074 GEN2
Solar/Wind Harmer
2.78
315735AD1-075 GEN1
Solar/Wind Harmer
1.39
965291AG1-394 GEN
Solar/Wind Harmer
1.217
3146206CASHIE
Solar/Wind Harmer
-0.014
970601AG2-382 GEN
Solar/Wind Harmer
5.979
316318V4-068
Solar/Wind Harmer
0.34
3145893MURPHYS
Solar/Wind Harmer
-0.037
3145893MURPHYS
Solar/Wind Harmer
-0.014
970085AG2-068 GEN
Solar/Wind Harmer
8.471
970581AG2-369 GEN
Solar/Wind Harmer
7.285
3145513AHOSKIE
Solar/Wind Harmer
0.118
961941AG1-037 GEN
Solar/Wind Harmer
0.102
3145513AHOSKIE
Solar/Wind Harmer
-0.013
3145683EARLEYS
Solar/Wind Harmer
-0.027
3145683EARLEYS
Solar/Wind Harmer
-0.013
3145683EARLEYS
Solar/Wind Harmer
-0.013
3146043SEABORD
Solar/Wind Harmer
-0.013
946281AF1-292 GEN
Solar/Wind Harmer
0.302
315607AA1-063A GEN
Solar/Wind Harmer
1.361
316087AB2-174 GEN
Solar/Wind Harmer
1.915
972193AH1-681 GEN
Adder
2.653
972205AH1-687 GEN
Adder
4.954
233935AB2-179 C
Solar/Wind Helper
1.253
232436AB1-176 C
Solar/Wind Helper
0.043
233923SMA
Solar/Wind Helper
0.932
233990AG1-397 GEN
Solar/Wind Helper
0.03
232432Z2-076 GEN
Solar/Wind Helper
0.065
234033AF1-007_GEN
Solar/Wind Helper
6.824
315652AC1-086 GEN
Solar/Wind Harmer
5.136
223402AF1-300 C
Solar/Wind Helper
0.699
233982AB2-133 GEN
Solar/Wind Helper
0.351
233918AB1-142 GEN
Solar/Wind Helper
0.492
233994AC2-023 GEN
Solar/Wind Helper
0.935
233996TM1833_GEN
Solar/Wind Helper
0.254
233997TMININ_4.2
Solar/Wind Helper
0.254
233940AF2-379 C
Solar/Wind Helper
0.06
234015AF2-250 C
Solar/Wind Helper
0.037
232406W1-004 FULL
Solar/Wind Helper
0.493
233952AC2-187 GEN
Solar/Wind Helper
0.226
233971AC1-093 C
Solar/Wind Helper
0.347
233972AC1-094 C
Solar/Wind Helper
0.293
NYPJM->LTFIMP_NY
CLTF
3.816
LGEELTFEXP_LGEE->PJM
CLTF
3.208
WECLTFEXP_WEC->PJM
CLTF
1.721
AG2-052LTFEXP_AG2-052->PJM
LTF
0.102
AH1-155LTFEXP_AH1-155->PJM
LTF
0.153
LAGNLTFEXP_LAGN->PJM
CLTF
10.915
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.861
TVALTFEXP_TVA->PJM
CLTF
5.494
CBM West 1LTFEXP_CBM-W1->PJM
CBM
63.932
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.074
MECLTFEXP_MEC->PJM
CLTF
7.89
SIGELTFEXP_SIGE->PJM
CLTF
0.248
CPLELTFEXP_CPLE->PJM
CLTF
8.313
CBM West 2LTFEXP_CBM-W2->PJM
CBM
68.064

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T581_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 568T581_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:211.93 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:8350.21
MW Contribution:129.9
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
6.236
971285AH1-108 GEN
50/50
2.704
316233AE1-074 FULL
Solar/Wind Harmer
1.044
971281AH1-106 GEN
Solar/Wind Harmer
6.308
971283AH1-107 GEN
Solar/Wind Harmer
6.308
316312AB1-027
Solar/Wind Harmer
1.259
972189AH1-679 GEN
Adder
5.56
316132AB2-190 GEN1
Solar/Wind Harmer
3.73
3143316POE
Solar/Wind Harmer
-0.145
316369SG1_INVT
Solar/Wind Harmer
6.568
315976AC1-164 GENA
Solar/Wind Harmer
38.783
316169AC1-164_GENC
Solar/Wind Harmer
33.504
315975AC1-164 GENB
Solar/Wind Harmer
1.147
972265AH1-717 GEN
Adder
25.277
3151201GRAVEL4
Adder
23.696
3151191GRAVEL3
Adder
23.396
3151211GRAVEL5
Adder
23.396
971445AH1-216 GEN
Solar/Wind Harmer
22.614
3151081ELIZAR1
Adder
29.76
3151091ELIZAR2
Adder
29.243
3152611GOSPORTB
Adder
4.132
3152621GOSPORTC
Adder
3.507
3152601GOSPORTA
Adder
3.235
957871AF2-081 GEN
Solar/Wind Harmer
18.071
315833AF1-017_GEN
Solar/Wind Harmer
6.849
316349AD2-085 GEN
Solar/Wind Harmer
3.207
316311AC2-079 GEN
Solar/Wind Harmer
18.186
319010AE1-072 C
Solar/Wind Harmer
7.291
3146406KITTY HAWK
Solar/Wind Harmer
0.03
316305AF2-043 C
Solar/Wind Harmer
1.085
941031AE2-094 GEN
Solar/Wind Harmer
67.43
944011AF1-069 GEN
Solar/Wind Harmer
21.128
971167AH1-042 GEN
Solar/Wind Harmer
34.583
315835AF2-110_GEN
Solar/Wind Harmer
4.479
3142433PROV 92
Adder
0.62
3142433PROV 92
Adder
0.62
313526AB2-022
Solar/Wind Harmer
0.963
3150411LDYSMT5
Adder
42.755
3150381LDYSMT2
Adder
40.918
972213AH1-691 GEN
Adder
6.922
972215AH1-692 GEN
Adder
6.922
3146486SUNBURY
Solar/Wind Harmer
-0.036
3146486SUNBURY
Solar/Wind Harmer
-0.036
957831AF2-077 GEN
Solar/Wind Harmer
1.07
3138283WHITEMARSH
Solar/Wind Harmer
0.055
316321Z2-027
Solar/Wind Harmer
0.959
3146396TANGLEW
Solar/Wind Harmer
0.654
3145176PASQUOTANK
Solar/Wind Harmer
-0.022
316315AB2-025 C
Solar/Wind Harmer
0.955
970673AG2-436 GEN
Solar/Wind Harmer
74.301
970673AG2-436 GEN
Solar/Wind Harmer
37.621
3143873LANEXA
Solar/Wind Harmer
-0.021
315814AE2-033 C
Solar/Wind Harmer
32.86
316314AB2-024 C
Solar/Wind Harmer
3.002
316059AD1-063 C
Solar/Wind Harmer
0.79
971967AH1-528 GEN
Solar/Wind Harmer
65.706
315662AE1-191 GEN
Solar/Wind Harmer
4.203
315666AE1-190 GEN
Solar/Wind Harmer
1.051
315611Z1-036_GEN2
Solar/Wind Harmer
8.589
957601AF2-054 GEN
Solar/Wind Harmer
1.038
3141873WAN 176
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.034
3130156CHOWAN
Solar/Wind Harmer
-0.034
3141913WHIT STONE
Solar/Wind Harmer
-0.034
3138133OCRAN
Solar/Wind Harmer
-0.01
3141783LANCAST
Solar/Wind Harmer
-0.02
3141783LANCAST
Solar/Wind Harmer
-0.013
315816AE2-034 GEN
Solar/Wind Harmer
2.723
970085AG2-068 GEN
Solar/Wind Harmer
20.836
970581AG2-369 GEN
Solar/Wind Harmer
17.919
962981AG1-147 GEN
Solar/Wind Harmer
14.507
3130546PLYMOUTH
Solar/Wind Harmer
-0.033
315732AD1-074 GEN1
Solar/Wind Harmer
6.673
315733AD1-074 GEN2
Solar/Wind Harmer
6.673
315735AD1-075 GEN1
Solar/Wind Harmer
3.338
965291AG1-394 GEN
Solar/Wind Harmer
2.918
3146206CASHIE
Solar/Wind Harmer
-0.033
970601AG2-382 GEN
Solar/Wind Harmer
14.298
316318V4-068
Solar/Wind Harmer
0.812
3145893MURPHYS
Solar/Wind Harmer
-0.087
3145893MURPHYS
Solar/Wind Harmer
-0.032
3145513AHOSKIE
Solar/Wind Harmer
0.28
961941AG1-037 GEN
Solar/Wind Harmer
0.242
3145513AHOSKIE
Solar/Wind Harmer
-0.032
946281AF1-292 GEN
Solar/Wind Harmer
0.718
3145683EARLEYS
Solar/Wind Harmer
-0.064
3145683EARLEYS
Solar/Wind Harmer
-0.032
3145683EARLEYS
Solar/Wind Harmer
-0.032
3146043SEABORD
Solar/Wind Harmer
-0.032
315607AA1-063A GEN
Solar/Wind Harmer
3.223
316087AB2-174 GEN
Solar/Wind Harmer
4.534
315652AC1-086 GEN
Solar/Wind Harmer
35.448
3137643SOCKMAN
Solar/Wind Harmer
-0.125
3141813NORNECK
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.099
3145796HORNRTN
Solar/Wind Harmer
-0.012
3146033SCOT NK
Solar/Wind Harmer
-0.123
972205AH1-687 GEN
Adder
9.958
972193AH1-681 GEN
Adder
4.981
3151881LOWMORC
Adder
1.266
3151881LOWMORC
Adder
1.246
3151861LOWMORA
Adder
1.226
316411AF1-147_GEN1
Solar/Wind Helper
1.074
316415AF1-147_GEN2
Solar/Wind Helper
1.074
3138216PACIFIC
Solar/Wind Helper
0.052
237085AD2-009_GEN
Solar/Wind Helper
1.439
238208AF1-136 C
Solar/Wind Helper
0.182
960921AF2-383 GEN
Solar/Wind Helper
0.176
205943AE1-185 GEN
Solar/Wind Helper
0.492
233935AB2-179 C
Solar/Wind Helper
1.231
205932AD2-116_GEN
Solar/Wind Helper
0.492
205956AE1-196_GEN
Solar/Wind Helper
0.492
232436AB1-176 C
Solar/Wind Helper
0.043
233923SMA
Solar/Wind Helper
0.929
233990AG1-397 GEN
Solar/Wind Helper
0.029
234033AF1-007_GEN
Solar/Wind Helper
6.804
232432Z2-076 GEN
Solar/Wind Helper
0.065
238152AF2-075_GEN
Solar/Wind Helper
0.557
959381AF2-229 GEN
Solar/Wind Helper
0.335
964001AG1-254 GEN
Solar/Wind Helper
0.923
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.025
219914AD2-027 C
Solar/Wind Helper
0.111
219272CLEANLIGHT C
Solar/Wind Helper
0.024
219688LUMSOLAR_S C
Solar/Wind Helper
0.038
219607WPEMNERT C
Solar/Wind Helper
0.077
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.092
20715828PEM_W1-120
Solar/Wind Helper
0.092
3152251N ANNA1
50/50
24.095
970119AG2-088 GEN
50/50
46.768
3150851SPRUNCC
50/50
1.653
3143096IRON208
50/50
1.481
316045AC1-158 PL2
Solar/Wind Harmer
23.52
3143226MDLTHAN
Solar/Wind Harmer
-0.039
3143526WINTERP
Solar/Wind Harmer
-0.201
3142543TWELFTH
Solar/Wind Harmer
-0.004
3147666LOUISA
Solar/Wind Harmer
-0.149
3142416OLDCHRC
Solar/Wind Harmer
-0.097
3142416OLDCHRC
Solar/Wind Harmer
-0.037
940641AE2-051 GEN
Solar/Wind Harmer
34.79
944631AF1-128 GEN
Adder
157.238
315671AE2-027_GEN
Solar/Wind Harmer
27.738
939411AE1-173 GEN
Solar/Wind Harmer
184.612
316294AC1-161 GEN
Solar/Wind Harmer
11.936
970129AG2-093 GEN
Solar/Wind Harmer
8.413
316458AB2-190 GEN2
Solar/Wind Harmer
3.73
971069AG2-661 GEN
Solar/Wind Harmer
5.824
971647AH1-324 GEN
Solar/Wind Harmer
18.353
961611AG1-000B GEN
Solar/Wind Harmer
18.086
316192AB2-158 GEN
Solar/Wind Harmer
4.354
3151171GRAVELC
Adder
3.463
316159AE1-175 C
Solar/Wind Harmer
0.981
3145336SMITFLD
Solar/Wind Harmer
-0.145
944591AF1-124 GEN
Solar/Wind Harmer
166.698
316375AC2-012 GEN
Solar/Wind Harmer
12.618
3150981CHESPKA
Adder
4.052
970659AG2-427 GEN
Solar/Wind Harmer
19.373
966881AG1-559 GEN
Solar/Wind Harmer
0.375
3138126ROCKLANDING
Solar/Wind Harmer
0.112
316381AD1-082 GEN
Solar/Wind Harmer
3.341
970661AG2-428 GEN
Solar/Wind Harmer
38.595
971317AH1-138 GEN
Solar/Wind Harmer
4.533
316388AE2-253 GEN
Solar/Wind Harmer
2.44
316072AD1-144
Solar/Wind Harmer
0.731
3146456SLIGO L269
Solar/Wind Harmer
-0.036
316246AF1-032 C
Solar/Wind Harmer
0.728
316093AE2-104_GEN
Solar/Wind Harmer
10.418
3142433PROV 92
Solar/Wind Harmer
-0.143
3142433PROV 92
Adder
0.62
3142433PROV 92
Adder
0.62
972197AH1-683 GEN
Adder
6.656
972219AH1-694 GEN
Adder
4.792
3146516WINFALL
Solar/Wind Harmer
-0.114
3146516WINFALL
Solar/Wind Harmer
-0.035
971777AH1-397 GEN
Solar/Wind Harmer
4.114
3141843SHACKLE
Adder
1.591
3141766HARMONY
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
8.589
3130156CHOWAN
Solar/Wind Harmer
-0.034
3143336POWHATN
Solar/Wind Harmer
4.05
3138133OCRAN
Solar/Wind Harmer
-0.02
3145663CRESWEL
Solar/Wind Harmer
-0.094
971163AH1-040 GEN
Solar/Wind Harmer
31.545
970919AG2-571 GEN
Solar/Wind Harmer
10.592
970087AG2-069 GEN
Solar/Wind Harmer
31.254
316023GEN1_S
Solar/Wind Harmer
2.215
961951AG1-038 GEN
Solar/Wind Harmer
4.322
316336AC2-165 C
Solar/Wind Harmer
5.691
3146206CASHIE
Solar/Wind Harmer
-0.033
971547AH1-271 GEN
Solar/Wind Harmer
8.17
3145893MURPHYS
Solar/Wind Harmer
-0.13
3145893MURPHYS
Solar/Wind Harmer
0.967
962861AG1-135 GEN
Solar/Wind Harmer
12.147
3146173TUNIS
Solar/Wind Harmer
-0.032
957481AF2-042 GEN
Solar/Wind Harmer
100.212
960081AF2-299 GEN
Solar/Wind Harmer
3.604
3145683EARLEYS
Solar/Wind Harmer
-0.032
3146263WOODLND
Solar/Wind Harmer
-0.032
964211AG1-282 GEN
Solar/Wind Harmer
0.954
3141726DUNNSVL
Solar/Wind Harmer
-0.126
316011AB1-132 GEN
Solar/Wind Harmer
6.592
962571AG1-106 GEN
Solar/Wind Harmer
4.529
3145963POPLR C
Solar/Wind Harmer
-0.031
315693AD1-088 GEN
Solar/Wind Harmer
15.742
971795AH1-408 GEN
Solar/Wind Harmer
23.556
3145823KELFORD
Solar/Wind Harmer
-0.031
962491AG1-098 GEN
Solar/Wind Harmer
20.998
316190AA2-174 GEN
Solar/Wind Harmer
0.385
316174AB2-169 GEN
Solar/Wind Harmer
4.817
3150351NORNECKC2
Adder
2.771
3147043LAWRENC
Adder
2.506
3145783HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.102
3145796HORNRTN
Solar/Wind Harmer
-0.031
3144293JTRSVLE
Adder
0.817
972277AH1-723 GEN
Adder
129.895
3151751LOISA D
Adder
13.353
23779801AA1-109
Solar/Wind Helper
0.187
223401AF1-299 GEN
Solar/Wind Helper
0.373
237080AD1-060 GEN
Solar/Wind Helper
0.304
237038AE2-054 C
Solar/Wind Helper
0.241
235062AE1-101 C1
Solar/Wind Helper
1.47
966131AG1-482 GEN
Solar/Wind Helper
0.075
233930AB2-032 GEN
Solar/Wind Helper
0.369
233915AB1-141 GEN
Solar/Wind Helper
0.487
232422X3-066 FULL
Solar/Wind Helper
0.111
232426Y1-080 FULL
Solar/Wind Helper
0.038
233964AF2-378 GEN
Solar/Wind Helper
0.04
233998TM1NIN_3.36
Solar/Wind Helper
0.253
232404W1-003 C
Solar/Wind Helper
0.492
232428Y3-058 C
Solar/Wind Helper
0.328
232434Z2-077 GEN
Solar/Wind Helper
0.123
233954AC2-188 GEN
Solar/Wind Helper
0.225
233950AC2-186 GEN
Solar/Wind Helper
0.113
233972AC1-094 C
Solar/Wind Helper
0.293
238148AE2-230_GEN2
Solar/Wind Helper
0.391
230511AF1-262
Solar/Wind Helper
0.014
230434AG1-499 GEN
Solar/Wind Helper
0.222
228728W1-130C
Solar/Wind Helper
0.052
219258KINSLEYDEP C
Solar/Wind Helper
0.074
219904AC1-010 C
Solar/Wind Helper
0.058
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219907AC1-030 C
Solar/Wind Helper
0.033
219686LUMSOLAR_N C
Solar/Wind Helper
0.038
219304NAMERICA C
Solar/Wind Helper
0.126
20720728JCB_W1-129
Solar/Wind Helper
0.055
971133AH1-012 GEN
50/50
6.863
3142296MT RD221
50/50
1.135
3142366NRTHEST
50/50
1.158
3150691DARBY 3
50/50
25.424
3150701DARBY 4
50/50
25.364
3150681DARBY 2
50/50
25.335
316447AC1-158 HLD
Solar/Wind Harmer
16.169
971223AH1-071 GEN
Solar/Wind Harmer
4.926
3143526WINTERP
Solar/Wind Harmer
-0.201
3150671DARBY 1
Adder
23.848
944641AF1-129 GEN
Adder
157.758
316240AF1-291 C
Solar/Wind Harmer
1.119
316075AC2-137 C
Solar/Wind Harmer
0.997
3142946ENON
Solar/Wind Harmer
-0.004
316033AB2-134 GEN
Solar/Wind Harmer
11.856
315697AD1-025 GEN
Solar/Wind Harmer
7.436
316236AE1-162_GEN
Solar/Wind Harmer
1.101
316036AC1-147 C
Solar/Wind Harmer
0.984
3150991CHESPKB
Adder
3.399
3150991CHESPKB
Adder
3.318
957411AF2-035 GEN
Solar/Wind Harmer
16.399
970317AG2-208 GEN
Solar/Wind Harmer
15.944
316316AC1-027 C
Solar/Wind Harmer
1.117
3142956BIRDNECK
Solar/Wind Harmer
1.953
970657AG2-426 GEN
Solar/Wind Harmer
11.372
970657AG2-426 GEN
Solar/Wind Harmer
2.378
316185AD1-033 GEN
Solar/Wind Harmer
3.837
3145506HICKORY
Solar/Wind Harmer
-0.144
3145506HICKORY
Solar/Wind Harmer
-0.087
3145506HICKORY
Solar/Wind Harmer
-0.022
316339AD2-160 GEN
Solar/Wind Harmer
2.44
315673AE1-157 GEN
Solar/Wind Harmer
27.13
316018AA1-139 ULT2
Solar/Wind Harmer
3.096
316017AA1-139 ULT1
Solar/Wind Harmer
2.925
966871AG1-558 GEN
Solar/Wind Harmer
1.086
966871AG1-558 GEN
Solar/Wind Harmer
0.372
3137176SLIGO L2192
Solar/Wind Harmer
-0.143
3146456SLIGO L269
Solar/Wind Harmer
4.26
3130086AYDLETT
Solar/Wind Harmer
-0.143
3146386ELIZ CT
Solar/Wind Harmer
-0.036
3150391LDYSMT3
Adder
42.542
972195AH1-682 GEN
Adder
5.591
3144356SAPONY
Solar/Wind Harmer
1.235
316431W1029_GEN1
Solar/Wind Harmer
6.407
316433W1029_GEN2
Solar/Wind Harmer
6.407
3146516WINFALL
Solar/Wind Harmer
-0.035
3146516WINFALL
Solar/Wind Harmer
-0.035
3146516WINFALL
Solar/Wind Harmer
-0.035
3146626S HERTFORD
Solar/Wind Harmer
-0.035
3146626S HERTFORD
Solar/Wind Harmer
-0.035
972185AH1-677 GEN
Adder
17.515
316441AF1-014 GEN
Solar/Wind Harmer
2.358
972187AH1-678 GEN
Adder
8.788
315742AE1-103 GEN
Solar/Wind Harmer
3.612
3146376EDENTON
Solar/Wind Harmer
1.02
3146376EDENTON
Solar/Wind Harmer
1.02
970933AG2-581 GEN
Solar/Wind Harmer
32.018
316487AF1-042 GEN
Solar/Wind Harmer
4.322
316065AD1-022 GEN
Solar/Wind Harmer
16.398
3145893MURPHYS
Solar/Wind Harmer
0.909
3145893MURPHYS
Solar/Wind Harmer
-0.059
3146173TUNIS
Solar/Wind Harmer
-0.032
3146173TUNIS
Solar/Wind Harmer
-0.032
958261AF2-120 GEN
Solar/Wind Harmer
12.494
970099AG2-077 GEN
Solar/Wind Harmer
40.085
316181AB2-040 GEN
Solar/Wind Harmer
4.418
3142666NORTHAMPTON
Solar/Wind Harmer
-0.031
3142666NORTHAMPTON
Solar/Wind Harmer
-0.031
3142666NORTHAMPTON
Solar/Wind Harmer
-0.031
3142666NORTHAMPTON
Solar/Wind Harmer
-0.019
316426AA2-053 GEN
Solar/Wind Harmer
3.171
3145593CAROLNA
Solar/Wind Harmer
-0.031
3145593CAROLNA
Solar/Wind Harmer
-0.031
966811AG1-552 GEN
Solar/Wind Harmer
3.517
3145593CAROLNA
Solar/Wind Harmer
0.26
316077AC2-138 C
Solar/Wind Harmer
0.659
3150341NORNECKC1
Adder
2.91
3150341NORNECKC1
Adder
2.887
3145783HORNRTN
Solar/Wind Harmer
3.688
3145783HORNRTN
Solar/Wind Harmer
2.95
3145783HORNRTN
Solar/Wind Harmer
0.922
3145783HORNRTN
Solar/Wind Harmer
0.369
3145796HORNRTN
Solar/Wind Harmer
-0.093
316468AD1-105 GEN
Solar/Wind Harmer
3.393
3144293JTRSVLE
Adder
0.817
3144293JTRSVLE
Adder
0.688
3151731LOISA B
Adder
13.353
3151721LOISA A
Adder
13.284
226929AD2-058 GEN
Solar/Wind Helper
0.107
23777801MSM_W1-116
Solar/Wind Helper
0.111
237025AB1-124 C
Solar/Wind Helper
0.161
237006AB1-125 GEN
Solar/Wind Helper
0.121
237034AC2-136 C
Solar/Wind Helper
0.211
23777901MDS_W4-102
Solar/Wind Helper
0.157
235020AA1-095 C
Solar/Wind Helper
0.046
237001AB1-127_GEN
Solar/Wind Helper
0.396
237002AB1-128_GEN
Solar/Wind Helper
0.396
235063AE1-101 C2
Solar/Wind Helper
1.47
238175AF1-290_GEN
Solar/Wind Helper
0.127
238169AE2-226 GEN1
Solar/Wind Helper
0.579
238170AE2-226 GEN2
Solar/Wind Helper
0.579
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
205916AD1-020 GEN
Solar/Wind Helper
1.657
233933AB2-153 GEN
Solar/Wind Helper
0.225
233987AB2-037 GEN
Solar/Wind Helper
2.27
233944AB2-135 GEN
Solar/Wind Helper
0.571
232424Y1-079 C
Solar/Wind Helper
0.113
233946AB2-136 GEN
Solar/Wind Helper
0.551
234036AF2-325 C
Solar/Wind Helper
0.041
233901CHERRYDALE C
Solar/Wind Helper
0.225
232408W1-005 C
Solar/Wind Helper
0.492
232410W1-006 C
Solar/Wind Helper
0.492
233939AC1-091 C
Solar/Wind Helper
0.339
233970AC1-092 C
Solar/Wind Helper
0.339
20390526W1-045 C
Solar/Wind Helper
0.328
230433AD2-135 GEN
Solar/Wind Helper
0.016
230407AD2-065 C
Solar/Wind Helper
0.039
219921AF1-264
Solar/Wind Helper
0.049
219615MILLCREEK C
Solar/Wind Helper
0.026
3152261N ANNA2
50/50
24.093
970497AG2-320 GEN
50/50
31.984
3150861SPRUNCD
50/50
1.653
971645AH1-323 GEN
50/50
29.901
3143096IRON208
50/50
1.481
3143096IRON208
50/50
1.451
316044AC1-158 PL1
Solar/Wind Harmer
7.353
316450AC1-158 RIC
Solar/Wind Harmer
1.961
3147666LOUISA
Solar/Wind Harmer
-0.086
3142416OLDCHRC
Solar/Wind Harmer
3.768
970293AG2-193 GEN
Solar/Wind Harmer
4.65
315839AE2-212 C
Solar/Wind Harmer
1.116
970133AG2-095 GEN
Solar/Wind Harmer
4.162
965281AG1-393 GEN
Solar/Wind Harmer
4.621
3142946ENON
Solar/Wind Harmer
-0.012
315773AC2-141 GEN
Solar/Wind Harmer
15.437
970129AG2-093 GEN
Solar/Wind Harmer
20.77
315778AD1-151 GEN
Solar/Wind Harmer
31.888
315813AE1-149 C
Solar/Wind Harmer
22.914
961611AG1-000B GEN
Solar/Wind Harmer
7.717
3151221GRAVEL6
Adder
23.669
3151171GRAVELC
Adder
4.554
316382AG1-145 C
Solar/Wind Harmer
1.101
3145336SMITFLD
Solar/Wind Harmer
-0.014
944581AF1-123 GEN
Solar/Wind Harmer
166.1
944601AF1-125 GEN
Solar/Wind Harmer
163.508
3144536CHRHLND
Solar/Wind Harmer
-0.006
3151101ELIZAR3
Adder
30.141
970659AG2-427 GEN
Solar/Wind Harmer
3.433
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3144216WINCHST
Adder
1.223
966881AG1-559 GEN
Solar/Wind Harmer
1.096
316083AB2-161 GEN
Solar/Wind Harmer
5.913
3150921YORKTN3
Adder
8.144
970661AG2-428 GEN
Solar/Wind Harmer
6.84
316473AC1-191 GEN
Solar/Wind Harmer
3.887
3146456SLIGO L269
Solar/Wind Harmer
-0.036
971153AH1-033 GEN
Solar/Wind Harmer
4.397
3142433PROV 92
Adder
0.62
3142433PROV 92
Adder
0.62
316320Y1-086
Solar/Wind Harmer
2.093
3150401LDYSMT4
Adder
42.622
3150371LDYSMT1
Adder
41.184
316435W1029_GEN3
Solar/Wind Harmer
6.407
3146516WINFALL
Solar/Wind Harmer
-0.035
3146626S HERTFORD
Solar/Wind Harmer
-0.035
3141843SHACKLE
Adder
1.591
316203AE2-005 GEN
Solar/Wind Harmer
14.749
3145273HOLLAND
Solar/Wind Harmer
-0.026
3141766HARMONY
Solar/Wind Harmer
3.112
316280AD1-041 GEN
Solar/Wind Harmer
2.627
316156AD2-030 GEN
Solar/Wind Harmer
0.927
3141873WAN 176
Solar/Wind Harmer
4.119
3146376EDENTON
Solar/Wind Harmer
-0.034
316313AB2-026
Solar/Wind Harmer
0.92
316258AE1-075 C
Solar/Wind Harmer
0.829
316405AF2-144 C
Solar/Wind Harmer
0.874
3143336POWHATN
Solar/Wind Harmer
3.443
315614AA2-178 GEN
Solar/Wind Harmer
3.63
970917AG2-570 GEN
Solar/Wind Harmer
83.678
962971AG1-146 GEN
Solar/Wind Harmer
6.217
971157AH1-035 GEN
Solar/Wind Harmer
4.137
3156081AA2-088 GEN
Solar/Wind Harmer
10.718
315737AD1-076 GEN
Solar/Wind Harmer
6.272
316365GEN2_N
Solar/Wind Harmer
2.215
316484AD2-074 GEN
Solar/Wind Harmer
8.259
970009AG2-005 GEN
Solar/Wind Harmer
4.101
3146206CASHIE
Solar/Wind Harmer
-0.033
3145893MURPHYS
Solar/Wind Harmer
0.227
3145893MURPHYS
Solar/Wind Harmer
-0.032
957521AF2-046 GEN
Solar/Wind Harmer
25.606
961681AG1-008 GEN
Solar/Wind Harmer
25.606
3146173TUNIS
Solar/Wind Harmer
-0.032
316404AE1-155 C
Solar/Wind Harmer
6.22
3156021HOLLOMANSOL
Solar/Wind Harmer
4.342
316463AE2-346 GEN
Solar/Wind Harmer
0.52
316140AB2-099
Solar/Wind Harmer
0.217
962331AG1-082 GEN
Solar/Wind Harmer
4.019
966621AG1-532 GEN
Solar/Wind Harmer
0.65
3146263WOODLND
Solar/Wind Harmer
-0.032
313506AB2-031 GEN
Solar/Wind Harmer
2.546
3142666NORTHAMPTON
Solar/Wind Harmer
-0.031
3145963POPLR C
Solar/Wind Harmer
-0.031
316317KELFORD C
Solar/Wind Harmer
1.48
3145823KELFORD
Solar/Wind Harmer
-0.031
3150351NORNECKC2
Adder
2.817
3147043LAWRENC
Solar/Wind Harmer
-0.018
3145796HORNRTN
Solar/Wind Harmer
-0.123
3145796HORNRTN
Solar/Wind Harmer
-0.031
316478AD1-087 GEN
Solar/Wind Harmer
2.676
316486AD2-202 GEN
Solar/Wind Harmer
0.784
3144293JTRSVLE
Adder
0.817
972255AH1-712 GEN
Adder
111.469
3151761LOISA E
Adder
27.223
972183AH1-676 GEN
Adder
213.104
3141316ARNOLDS
Adder
0.364
3150331BIRCHWDA
Adder
22.835
3151861LOWMORA
Adder
1.276
3141196NOKESVL
Solar/Wind Helper
1.408
227287AC2-120 GEN
Solar/Wind Helper
0.371
226910AB2-157 C
Solar/Wind Helper
0.015
237030AB1-096 C
Solar/Wind Helper
0.069
223402AF1-300 C
Solar/Wind Helper
0.373
238221AF1-254 C O1
Solar/Wind Helper
0.245
235067AD1-061 GEN
Solar/Wind Helper
0.438
205917AD1-020 ES
Solar/Wind Helper
0.356
233918AB1-142 GEN
Solar/Wind Helper
0.487
233982AB2-133 GEN
Solar/Wind Helper
0.347
233994AC2-023 GEN
Solar/Wind Helper
0.932
233996TM1833_GEN
Solar/Wind Helper
0.253
233997TMININ_4.2
Solar/Wind Helper
0.253
232406W1-004 FULL
Solar/Wind Helper
0.492
233940AF2-379 C
Solar/Wind Helper
0.06
234015AF2-250 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.225
233971AC1-093 C
Solar/Wind Helper
0.346
238147AE2-230_GEN1
Solar/Wind Helper
0.39
238149AF1-291A_GEN
Solar/Wind Helper
0.111
230430AE1-229_GEN
Solar/Wind Helper
3.256
230415AB2-049 C
Solar/Wind Helper
0.029
228729W2-030 C
Solar/Wind Helper
0.107
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.053
219912AD2-042 GEN
Solar/Wind Helper
0.144
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.11
959561AF2-247 GEN
Solar/Wind Helper
0.02
20716028EGP_W2-019
Solar/Wind Helper
0.018
20720828JCB_W4-025
Solar/Wind Helper
0.061
20715028HAN_X4-015
Solar/Wind Helper
0.055
971781AH1-399 GEN
Solar/Wind Harmer
0.994
NYPJM->LTFIMP_NY
CLTF
4.81
LGEELTFEXP_LGEE->PJM
CLTF
2.081
WECLTFEXP_WEC->PJM
CLTF
1.018
LAGNLTFEXP_LAGN->PJM
CLTF
11.897
CBM South 2LTFEXP_CBM-S2->PJM
CBM
36.13
TVALTFEXP_TVA->PJM
CLTF
6.026
CBM West 1LTFEXP_CBM-W1->PJM
CBM
34.397
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.604
MECLTFEXP_MEC->PJM
CLTF
5.595
SIGELTFEXP_SIGE->PJM
CLTF
0.171
CPLELTFEXP_CPLE->PJM
CLTF
16.389
CBM West 2LTFEXP_CBM-W2->PJM
CBM
62.285

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 545T552_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:182.6 %
Rating:3118.0 MVA
Rating Type:C
MVA to Mitigate:5693.43
MW Contribution:86.3
Bus #Bus NameTypeMW Contribution
971531AH1-263 GEN
50/50
59.005
316303AF2-085
50/50
4.624
971285AH1-108 GEN
50/50
1.961
970603AG2-384 GEN
50/50
5.102
316164AC1-076 GEN
Solar/Wind Harmer
2.874
316233AE1-074 FULL
Solar/Wind Harmer
0.766
971281AH1-106 GEN
Solar/Wind Harmer
4.628
971283AH1-107 GEN
Solar/Wind Harmer
4.628
3143316POE
Solar/Wind Harmer
-0.106
316132AB2-190 GEN1
Solar/Wind Harmer
2.695
941031AE2-094 GEN
Solar/Wind Harmer
49.887
944011AF1-069 GEN
Solar/Wind Harmer
15.631
316369SG1_INVT
Solar/Wind Harmer
4.75
3151081ELIZAR1
Adder
21.638
3151091ELIZAR2
Adder
21.263
3152611GOSPORTB
Adder
3.004
3152621GOSPORTC
Adder
2.55
3152601GOSPORTA
Adder
2.352
971445AH1-216 GEN
Solar/Wind Harmer
16.401
316312AB1-027
Solar/Wind Harmer
0.894
972265AH1-717 GEN
Adder
18.309
3151201GRAVEL4
Adder
17.164
3151191GRAVEL3
Adder
16.946
3151211GRAVEL5
Adder
16.946
957871AF2-081 GEN
Solar/Wind Harmer
13.142
315976AC1-164 GENA
Solar/Wind Harmer
27.715
316169AC1-164_GENC
Solar/Wind Harmer
23.943
315975AC1-164 GENB
Solar/Wind Harmer
0.82
315833AF1-017_GEN
Solar/Wind Harmer
4.98
316349AD2-085 GEN
Solar/Wind Harmer
2.332
316311AC2-079 GEN
Solar/Wind Harmer
13.224
319010AE1-072 C
Solar/Wind Harmer
5.302
972189AH1-679 GEN
Adder
3.909
3146406KITTY HAWK
Solar/Wind Harmer
0.022
316305AF2-043 C
Solar/Wind Harmer
0.789
970673AG2-436 GEN
Solar/Wind Harmer
54.922
970673AG2-436 GEN
Solar/Wind Harmer
27.809
315835AF2-110_GEN
Solar/Wind Harmer
3.257
313526AB2-022
Solar/Wind Harmer
0.701
316315AB2-025 C
Solar/Wind Harmer
0.7
971167AH1-042 GEN
Solar/Wind Harmer
24.945
3146486SUNBURY
Solar/Wind Harmer
-0.026
3146486SUNBURY
Solar/Wind Harmer
-0.026
316321Z2-027
Solar/Wind Harmer
0.698
3146396TANGLEW
Solar/Wind Harmer
0.476
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
315814AE2-033 C
Solar/Wind Harmer
24.069
3142433PROV 92
Adder
0.447
3142433PROV 92
Adder
0.447
971967AH1-528 GEN
Solar/Wind Harmer
48.532
957831AF2-077 GEN
Solar/Wind Harmer
0.774
3138283WHITEMARSH
Solar/Wind Harmer
0.04
3143873LANEXA
Solar/Wind Harmer
-0.015
316314AB2-024 C
Solar/Wind Harmer
2.168
316059AD1-063 C
Solar/Wind Harmer
0.572
315611Z1-036_GEN2
Solar/Wind Harmer
6.245
315662AE1-191 GEN
Solar/Wind Harmer
3.043
315666AE1-190 GEN
Solar/Wind Harmer
0.761
957601AF2-054 GEN
Solar/Wind Harmer
0.752
3141873WAN 176
Solar/Wind Harmer
-0.005
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
3150411LDYSMT5
Adder
29.791
3150381LDYSMT2
Adder
28.511
972213AH1-691 GEN
Adder
4.823
972215AH1-692 GEN
Adder
4.823
3141913WHIT STONE
Solar/Wind Harmer
-0.025
3138133OCRAN
Solar/Wind Harmer
-0.007
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
970085AG2-068 GEN
Solar/Wind Harmer
15.354
970581AG2-369 GEN
Solar/Wind Harmer
13.205
315816AE2-034 GEN
Solar/Wind Harmer
1.979
962981AG1-147 GEN
Solar/Wind Harmer
10.594
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.85
315733AD1-074 GEN2
Solar/Wind Harmer
4.85
315735AD1-075 GEN1
Solar/Wind Harmer
2.426
965291AG1-394 GEN
Solar/Wind Harmer
2.123
3146206CASHIE
Solar/Wind Harmer
-0.024
970601AG2-382 GEN
Solar/Wind Harmer
10.393
316318V4-068
Solar/Wind Harmer
0.591
3145893MURPHYS
Solar/Wind Harmer
-0.064
3145893MURPHYS
Solar/Wind Harmer
-0.024
3145513AHOSKIE
Solar/Wind Harmer
0.204
961941AG1-037 GEN
Solar/Wind Harmer
0.176
3145513AHOSKIE
Solar/Wind Harmer
-0.023
946281AF1-292 GEN
Solar/Wind Harmer
0.523
3146043SEABORD
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.046
3152251N ANNA1
50/50
19.45
971507AH1-251 GEN
50/50
16.115
970119AG2-088 GEN
50/50
34.68
3150851SPRUNCC
50/50
1.198
3143096IRON208
50/50
1.065
316045AC1-158 PL2
Solar/Wind Harmer
21.331
3147666LOUISA
Solar/Wind Harmer
-0.117
3143226MDLTHAN
Solar/Wind Harmer
-0.029
316192AB2-158 GEN
Solar/Wind Harmer
3.431
3143526WINTERP
Solar/Wind Harmer
-0.147
940641AE2-051 GEN
Solar/Wind Harmer
25.691
939411AE1-173 GEN
Solar/Wind Harmer
135.819
3142543TWELFTH
Solar/Wind Harmer
-0.003
316294AC1-161 GEN
Solar/Wind Harmer
8.675
315671AE2-027_GEN
Solar/Wind Harmer
20.092
970129AG2-093 GEN
Solar/Wind Harmer
6.077
316458AB2-190 GEN2
Solar/Wind Harmer
2.695
944631AF1-128 GEN
Adder
112.977
971069AG2-661 GEN
Solar/Wind Harmer
4.21
944591AF1-124 GEN
Solar/Wind Harmer
121.264
971647AH1-324 GEN
Solar/Wind Harmer
13.278
961611AG1-000B GEN
Solar/Wind Harmer
13.092
316375AC2-012 GEN
Solar/Wind Harmer
9.174
3150981CHESPKA
Adder
2.946
970659AG2-427 GEN
Solar/Wind Harmer
14.084
3145336SMITFLD
Solar/Wind Harmer
-0.105
3142416OLDCHRC
Solar/Wind Harmer
-0.069
3142416OLDCHRC
Solar/Wind Harmer
-0.026
3151171GRAVELC
Adder
2.508
316381AD1-082 GEN
Solar/Wind Harmer
2.429
970661AG2-428 GEN
Solar/Wind Harmer
28.06
3138126ROCKLANDING
Solar/Wind Harmer
0.081
316388AE2-253 GEN
Solar/Wind Harmer
1.774
316159AE1-175 C
Solar/Wind Harmer
0.706
316072AD1-144
Solar/Wind Harmer
0.531
3146456SLIGO L269
Solar/Wind Harmer
-0.026
316246AF1-032 C
Solar/Wind Harmer
0.53
971317AH1-138 GEN
Solar/Wind Harmer
3.272
316093AE2-104_GEN
Solar/Wind Harmer
7.576
3142433PROV 92
Solar/Wind Harmer
-0.103
3142433PROV 92
Adder
0.447
3142433PROV 92
Adder
0.447
3146516WINFALL
Solar/Wind Harmer
-0.083
3146516WINFALL
Solar/Wind Harmer
-0.026
966881AG1-559 GEN
Solar/Wind Harmer
0.262
971777AH1-397 GEN
Solar/Wind Harmer
2.977
3141843SHACKLE
Adder
1.151
3141766HARMONY
Solar/Wind Harmer
-0.005
315800Z1-036_GEN1
Solar/Wind Harmer
6.245
3143336POWHATN
Solar/Wind Harmer
2.977
3130156CHOWAN
Solar/Wind Harmer
-0.025
972197AH1-683 GEN
Adder
4.637
972219AH1-694 GEN
Adder
3.339
3138133OCRAN
Solar/Wind Harmer
-0.015
970919AG2-571 GEN
Solar/Wind Harmer
7.807
970087AG2-069 GEN
Solar/Wind Harmer
23.032
3145663CRESWEL
Solar/Wind Harmer
-0.068
971163AH1-040 GEN
Solar/Wind Harmer
22.931
316336AC2-165 C
Solar/Wind Harmer
4.171
961951AG1-038 GEN
Solar/Wind Harmer
3.162
316023GEN1_S
Solar/Wind Harmer
1.617
3146206CASHIE
Solar/Wind Harmer
-0.024
971547AH1-271 GEN
Solar/Wind Harmer
5.939
962861AG1-135 GEN
Solar/Wind Harmer
8.906
3145893MURPHYS
Solar/Wind Harmer
-0.094
3145893MURPHYS
Solar/Wind Harmer
0.704
957481AF2-042 GEN
Solar/Wind Harmer
73.619
3146173TUNIS
Solar/Wind Harmer
-0.023
960081AF2-299 GEN
Solar/Wind Harmer
2.629
964211AG1-282 GEN
Solar/Wind Harmer
0.702
3141726DUNNSVL
Solar/Wind Harmer
-0.093
3145683EARLEYS
Solar/Wind Harmer
-0.023
3146263WOODLND
Solar/Wind Harmer
-0.023
315693AD1-088 GEN
Solar/Wind Harmer
11.547
3150351NORNECKC2
Adder
2.044
962491AG1-098 GEN
Solar/Wind Harmer
15.398
316011AB1-132 GEN
Solar/Wind Harmer
4.801
962571AG1-106 GEN
Solar/Wind Harmer
3.298
971795AH1-408 GEN
Solar/Wind Harmer
17.176
3145963POPLR C
Solar/Wind Harmer
-0.023
316190AA2-174 GEN
Solar/Wind Harmer
0.281
3145823KELFORD
Solar/Wind Harmer
-0.023
316174AB2-169 GEN
Solar/Wind Harmer
3.498
3147043LAWRENC
Adder
1.827
3145783HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.074
3145796HORNRTN
Solar/Wind Harmer
-0.023
3144293JTRSVLE
Adder
0.594
3151751LOISA D
Adder
10.119
972277AH1-723 GEN
Adder
86.298
316006AB2-029 C
Solar/Wind Helper
0.108
3152261N ANNA2
50/50
19.448
3150861SPRUNCD
50/50
1.198
3143096IRON208
50/50
1.065
3143096IRON208
50/50
1.043
316044AC1-158 PL1
Solar/Wind Harmer
6.668
316450AC1-158 RIC
Solar/Wind Harmer
1.778
3147666LOUISA
Solar/Wind Harmer
-0.067
315839AE2-212 C
Solar/Wind Harmer
0.81
315773AC2-141 GEN
Solar/Wind Harmer
11.22
965281AG1-393 GEN
Solar/Wind Harmer
3.35
970133AG2-095 GEN
Solar/Wind Harmer
3.004
315813AE1-149 C
Solar/Wind Harmer
16.657
970129AG2-093 GEN
Solar/Wind Harmer
15.004
315778AD1-151 GEN
Solar/Wind Harmer
23.05
944581AF1-123 GEN
Solar/Wind Harmer
120.829
944601AF1-125 GEN
Solar/Wind Harmer
118.944
970293AG2-193 GEN
Solar/Wind Harmer
3.321
3151101ELIZAR3
Adder
21.915
961611AG1-000B GEN
Solar/Wind Harmer
5.586
3144536CHRHLND
Solar/Wind Harmer
-0.004
3142946ENON
Solar/Wind Harmer
-0.009
970659AG2-427 GEN
Solar/Wind Harmer
2.496
3145336SMITFLD
Solar/Wind Harmer
-0.01
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3142416OLDCHRC
Solar/Wind Harmer
2.673
3151221GRAVEL6
Adder
17.144
3151171GRAVELC
Adder
3.298
316083AB2-161 GEN
Solar/Wind Harmer
4.299
970661AG2-428 GEN
Solar/Wind Harmer
4.973
3144216WINCHST
Adder
0.884
3150921YORKTN3
Adder
5.882
316382AG1-145 C
Solar/Wind Harmer
0.792
3146456SLIGO L269
Solar/Wind Harmer
-0.026
971153AH1-033 GEN
Solar/Wind Harmer
3.198
316320Y1-086
Solar/Wind Harmer
1.522
3142433PROV 92
Adder
0.447
3142433PROV 92
Adder
0.447
316473AC1-191 GEN
Solar/Wind Harmer
2.772
316435W1029_GEN3
Solar/Wind Harmer
4.659
3146516WINFALL
Solar/Wind Harmer
-0.026
966881AG1-559 GEN
Solar/Wind Harmer
0.767
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3145273HOLLAND
Solar/Wind Harmer
-0.019
3141843SHACKLE
Adder
1.151
316203AE2-005 GEN
Solar/Wind Harmer
10.672
3141766HARMONY
Solar/Wind Harmer
2.25
316280AD1-041 GEN
Solar/Wind Harmer
1.902
316156AD2-030 GEN
Solar/Wind Harmer
0.672
3141873WAN 176
Solar/Wind Harmer
2.985
316313AB2-026
Solar/Wind Harmer
0.677
316258AE1-075 C
Solar/Wind Harmer
0.609
316405AF2-144 C
Solar/Wind Harmer
0.643
3143336POWHATN
Solar/Wind Harmer
2.53
3146376EDENTON
Solar/Wind Harmer
-0.025
3150401LDYSMT4
Adder
29.698
3150371LDYSMT1
Adder
28.696
970917AG2-570 GEN
Solar/Wind Harmer
61.676
315614AA2-178 GEN
Solar/Wind Harmer
2.639
962971AG1-146 GEN
Solar/Wind Harmer
4.54
971157AH1-035 GEN
Solar/Wind Harmer
3.007
3156081AA2-088 GEN
Solar/Wind Harmer
7.797
316484AD2-074 GEN
Solar/Wind Harmer
6.042
970009AG2-005 GEN
Solar/Wind Harmer
3
315737AD1-076 GEN
Solar/Wind Harmer
4.558
316365GEN2_N
Solar/Wind Harmer
1.617
3146206CASHIE
Solar/Wind Harmer
-0.024
3145893MURPHYS
Solar/Wind Harmer
0.165
3145893MURPHYS
Solar/Wind Harmer
-0.024
316404AE1-155 C
Solar/Wind Harmer
4.564
957521AF2-046 GEN
Solar/Wind Harmer
18.624
961681AG1-008 GEN
Solar/Wind Harmer
18.624
3146173TUNIS
Solar/Wind Harmer
-0.023
3156021HOLLOMANSOL
Solar/Wind Harmer
3.157
316463AE2-346 GEN
Solar/Wind Harmer
0.378
316140AB2-099
Solar/Wind Harmer
0.158
962331AG1-082 GEN
Solar/Wind Harmer
2.922
966621AG1-532 GEN
Solar/Wind Harmer
0.474
3146263WOODLND
Solar/Wind Harmer
-0.023
313506AB2-031 GEN
Solar/Wind Harmer
1.855
3150351NORNECKC2
Adder
2.079
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.023
316317KELFORD C
Solar/Wind Harmer
1.076
3145823KELFORD
Solar/Wind Harmer
-0.023
3147043LAWRENC
Solar/Wind Harmer
-0.013
316478AD1-087 GEN
Solar/Wind Harmer
1.962
316486AD2-202 GEN
Solar/Wind Harmer
0.574
3145796HORNRTN
Solar/Wind Harmer
-0.09
3145796HORNRTN
Solar/Wind Harmer
-0.023
3144293JTRSVLE
Adder
0.594
3151761LOISA E
Adder
20.63
972183AH1-676 GEN
Adder
160.944
972255AH1-712 GEN
Adder
74.056
3141316ARNOLDS
Adder
0.31
3150331BIRCHWDA
Adder
20.259
3141196NOKESVL
Solar/Wind Helper
0.97
971133AH1-012 GEN
50/50
5.464
944641AF1-129 GEN
50/50
120.961
3142366NRTHEST
50/50
0.827
3150691DARBY 3
50/50
18.162
3150701DARBY 4
50/50
18.119
316447AC1-158 HLD
Solar/Wind Harmer
14.664
971223AH1-071 GEN
Solar/Wind Harmer
3.653
3143526WINTERP
Solar/Wind Harmer
-0.147
316240AF1-291 C
Solar/Wind Harmer
0.81
3150681DARBY 2
Adder
17.056
3150671DARBY 1
Adder
17.036
3142296MT RD221
Adder
0.757
316033AB2-134 GEN
Solar/Wind Harmer
8.573
315697AD1-025 GEN
Solar/Wind Harmer
5.377
316036AC1-147 C
Solar/Wind Harmer
0.715
3150991CHESPKB
Adder
2.471
3150991CHESPKB
Adder
2.412
3142946ENON
Solar/Wind Harmer
-0.003
316236AE1-162_GEN
Solar/Wind Harmer
0.799
316316AC1-027 C
Solar/Wind Harmer
0.813
3142956BIRDNECK
Solar/Wind Harmer
1.42
970657AG2-426 GEN
Solar/Wind Harmer
8.268
970657AG2-426 GEN
Solar/Wind Harmer
1.729
316185AD1-033 GEN
Solar/Wind Harmer
2.79
3145506HICKORY
Solar/Wind Harmer
-0.105
3145506HICKORY
Solar/Wind Harmer
-0.063
3145506HICKORY
Solar/Wind Harmer
-0.016
316075AC2-137 C
Solar/Wind Harmer
0.712
316339AD2-160 GEN
Solar/Wind Harmer
1.774
316018AA1-139 ULT2
Solar/Wind Harmer
2.252
316017AA1-139 ULT1
Solar/Wind Harmer
2.127
3137176SLIGO L2192
Solar/Wind Harmer
-0.104
3146456SLIGO L269
Solar/Wind Harmer
3.098
3130086AYDLETT
Solar/Wind Harmer
-0.104
3146386ELIZ CT
Solar/Wind Harmer
-0.026
3144356SAPONY
Solar/Wind Harmer
0.905
972185AH1-677 GEN
Adder
12.941
966871AG1-558 GEN
Solar/Wind Harmer
0.774
966871AG1-558 GEN
Solar/Wind Harmer
0.265
316431W1029_GEN1
Solar/Wind Harmer
4.659
316433W1029_GEN2
Solar/Wind Harmer
4.659
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
972187AH1-678 GEN
Adder
6.489
957411AF2-035 GEN
Solar/Wind Harmer
11.475
970317AG2-208 GEN
Solar/Wind Harmer
11.157
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
316441AF1-014 GEN
Solar/Wind Harmer
1.706
315673AE1-157 GEN
Solar/Wind Harmer
18.955
970933AG2-581 GEN
Solar/Wind Harmer
23.615
315742AE1-103 GEN
Solar/Wind Harmer
2.627
3146376EDENTON
Solar/Wind Harmer
0.741
3146376EDENTON
Solar/Wind Harmer
0.741
3150391LDYSMT3
Adder
29.642
972195AH1-682 GEN
Adder
3.895
316487AF1-042 GEN
Solar/Wind Harmer
3.162
316065AD1-022 GEN
Solar/Wind Harmer
11.919
3145893MURPHYS
Solar/Wind Harmer
0.662
3145893MURPHYS
Solar/Wind Harmer
-0.043
958261AF2-120 GEN
Solar/Wind Harmer
9.168
970099AG2-077 GEN
Solar/Wind Harmer
29.447
3146173TUNIS
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.023
316181AB2-040 GEN
Solar/Wind Harmer
3.22
316077AC2-138 C
Solar/Wind Harmer
0.486
3150341NORNECKC1
Adder
2.147
3150341NORNECKC1
Adder
2.13
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
316426AA2-053 GEN
Solar/Wind Harmer
2.308
3145593CAROLNA
Solar/Wind Harmer
-0.023
3145593CAROLNA
Solar/Wind Harmer
-0.023
966811AG1-552 GEN
Solar/Wind Harmer
2.56
3145593CAROLNA
Solar/Wind Harmer
0.189
3145783HORNRTN
Solar/Wind Harmer
2.684
3145783HORNRTN
Solar/Wind Harmer
2.147
3145783HORNRTN
Solar/Wind Harmer
0.671
3145783HORNRTN
Solar/Wind Harmer
0.268
3145796HORNRTN
Solar/Wind Harmer
-0.067
3144293JTRSVLE
Adder
0.594
3144293JTRSVLE
Adder
0.5
3151731LOISA B
Adder
10.119
3151721LOISA A
Adder
10.067
316468AD1-105 GEN
Solar/Wind Harmer
1.252
3145683EARLEYS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
315607AA1-063A GEN
Solar/Wind Harmer
2.345
316087AB2-174 GEN
Solar/Wind Harmer
3.305
3141813NORNECK
Solar/Wind Harmer
-0.023
315652AC1-086 GEN
Solar/Wind Harmer
25.813
3137643SOCKMAN
Solar/Wind Harmer
-0.091
3145796HORNRTN
Solar/Wind Harmer
-0.072
3145796HORNRTN
Solar/Wind Harmer
-0.009
972205AH1-687 GEN
Adder
7.173
972193AH1-681 GEN
Adder
3.309
316411AF1-147_GEN1
Solar/Wind Helper
0.769
316415AF1-147_GEN2
Solar/Wind Helper
0.769
3138216PACIFIC
Solar/Wind Helper
0.038
NYPJM->LTFIMP_NY
CLTF
3.258
LGEELTFEXP_LGEE->PJM
CLTF
1.156
WECLTFEXP_WEC->PJM
CLTF
0.544
LAGNLTFEXP_LAGN->PJM
CLTF
7.753
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.482
TVALTFEXP_TVA->PJM
CLTF
3.93
CBM West 1LTFEXP_CBM-W1->PJM
CBM
17.526
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.238
MECLTFEXP_MEC->PJM
CLTF
3.227
SIGELTFEXP_SIGE->PJM
CLTF
0.097
CPLELTFEXP_CPLE->PJM
CLTF
11.751
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.921

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 552_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:179.85 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:5791.82
MW Contribution:88.61
Bus #Bus NameTypeMW Contribution
3152261N ANNA2
50/50
19.95
3150861SPRUNCD
50/50
1.216
3143096IRON208
50/50
1.079
3143096IRON208
50/50
1.057
3150801HOPHCF4
50/50
1.421
971211AH1-065 GEN
50/50
1.714
3151161SURRY 1
50/50
9.199
316044AC1-158 PL1
Solar/Wind Harmer
3.047
316450AC1-158 RIC
Solar/Wind Harmer
0.812
3147666LOUISA
Solar/Wind Harmer
0.63
315839AE2-212 C
Solar/Wind Harmer
0.002
315773AC2-141 GEN
Solar/Wind Harmer
8.863
965281AG1-393 GEN
Solar/Wind Harmer
2.583
970133AG2-095 GEN
Solar/Wind Harmer
2.314
315813AE1-149 C
Solar/Wind Harmer
12.857
970129AG2-093 GEN
Solar/Wind Harmer
14.547
944581AF1-123 GEN
Solar/Wind Harmer
54.129
944601AF1-125 GEN
Solar/Wind Harmer
53.295
315778AD1-151 GEN
Solar/Wind Harmer
19.229
3151101ELIZAR3
Adder
22.283
3144536CHRHLND
Solar/Wind Harmer
0.036
3144873MCLAUGH
Solar/Wind Harmer
0.006
970659AG2-427 GEN
Solar/Wind Harmer
2.537
961611AG1-000B GEN
Solar/Wind Harmer
6.393
3145336SMITFLD
Solar/Wind Harmer
0.096
316083AB2-161 GEN
Solar/Wind Harmer
0.003
3151221GRAVEL6
Adder
17.41
3151171GRAVELC
Adder
3.35
970293AG2-193 GEN
Solar/Wind Harmer
2.553
3142946ENON
Solar/Wind Harmer
0.08
970661AG2-428 GEN
Solar/Wind Harmer
5.055
3142416OLDCHRC
Solar/Wind Harmer
2.311
3144216WINCHST
Adder
0.896
3146456SLIGO L269
Solar/Wind Harmer
0.237
971153AH1-033 GEN
Solar/Wind Harmer
2.744
3150921YORKTN3
Adder
5.966
316382AG1-145 C
Solar/Wind Harmer
0.002
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3142433PROV 92
Adder
0.452
3142433PROV 92
Adder
0.452
3146516WINFALL
Solar/Wind Harmer
0.232
316473AC1-191 GEN
Solar/Wind Harmer
0.781
3146626S HERTFORD
Solar/Wind Harmer
0.231
3145273HOLLAND
Solar/Wind Harmer
0.173
316313AB2-026
Solar/Wind Harmer
0.144
316258AE1-075 C
Solar/Wind Harmer
0.172
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.453
3141843SHACKLE
Adder
1.161
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3141766HARMONY
Solar/Wind Harmer
3.026
316280AD1-041 GEN
Solar/Wind Harmer
0.005
3146376EDENTON
Solar/Wind Harmer
0.226
316156AD2-030 GEN
Solar/Wind Harmer
0.167
3141873WAN 176
Solar/Wind Harmer
4.013
970917AG2-570 GEN
Solar/Wind Harmer
19.927
315614AA2-178 GEN
Solar/Wind Harmer
1.269
3150401LDYSMT4
Adder
29.389
3150371LDYSMT1
Adder
28.398
971157AH1-035 GEN
Solar/Wind Harmer
2.618
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
316365GEN2_N
Solar/Wind Harmer
0.488
315737AD1-076 GEN
Solar/Wind Harmer
2.798
962971AG1-146 GEN
Solar/Wind Harmer
3.462
3146206CASHIE
Solar/Wind Harmer
0.215
3145893MURPHYS
Solar/Wind Harmer
0.36
3145893MURPHYS
Solar/Wind Harmer
0.215
957521AF2-046 GEN
Solar/Wind Harmer
15.963
961681AG1-008 GEN
Solar/Wind Harmer
15.963
970009AG2-005 GEN
Solar/Wind Harmer
1.6
3146173TUNIS
Solar/Wind Harmer
0.213
3156021HOLLOMANSOL
Solar/Wind Harmer
0.965
316463AE2-346 GEN
Solar/Wind Harmer
0.182
316140AB2-099
Solar/Wind Harmer
0.076
962331AG1-082 GEN
Solar/Wind Harmer
2.263
316404AE1-155 C
Solar/Wind Harmer
0.047
3146263WOODLND
Solar/Wind Harmer
0.21
313506AB2-031 GEN
Solar/Wind Harmer
0.648
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3145963POPLR C
Solar/Wind Harmer
0.207
316317KELFORD C
Solar/Wind Harmer
0.02
3145823KELFORD
Solar/Wind Harmer
0.207
316478AD1-087 GEN
Solar/Wind Harmer
0.72
316486AD2-202 GEN
Solar/Wind Harmer
0.211
3147043LAWRENC
Solar/Wind Harmer
0.124
3145796HORNRTN
Solar/Wind Harmer
0.82
3145796HORNRTN
Solar/Wind Harmer
0.205
3150351NORNECKC2
Adder
2.075
316210AC1-098 GEN
Solar/Wind Harmer
1.857
3145933PARMELE
Solar/Wind Harmer
0.199
966801AG1-551 GEN
Solar/Wind Harmer
2.319
970909AG2-566 GEN
Solar/Wind Harmer
2.12
971781AH1-399 GEN
Solar/Wind Harmer
0.26
3145746EVERETS
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.195
315724AD1-057 GEN
Solar/Wind Harmer
0.731
316327AA2-057 GEN
Solar/Wind Harmer
0.292
316131AB2-060 GEN
Solar/Wind Harmer
0.605
964241AG1-285 GEN
Solar/Wind Harmer
12.823
315785AD2-033 C
Solar/Wind Harmer
1.561
970257AG2-171 GEN
Solar/Wind Harmer
6.143
959311AF2-222 GEN
Solar/Wind Harmer
17.057
963181AG1-167 GEN
Solar/Wind Harmer
0.766
3144293JTRSVLE
Adder
0.609
3147133PAMPLIN
Solar/Wind Harmer
0.6
971193AH1-056 GEN
Solar/Wind Harmer
11.648
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.114
3146233WITAKRS
Solar/Wind Harmer
0.953
3146233WITAKRS
Solar/Wind Harmer
0.129
3146073TAR RVR
Solar/Wind Harmer
0.189
3146083TARBORO
Solar/Wind Harmer
0.189
3138543CONSLDL
Solar/Wind Harmer
0.125
3132273ORANGE
Solar/Wind Harmer
0.038
961601AG1-000A GEN
Solar/Wind Harmer
13.257
3145543BTLEBRO
Solar/Wind Harmer
0.186
3145543BTLEBRO
Solar/Wind Harmer
0.186
971623AH1-311 GEN
Solar/Wind Harmer
0.373
3141906WESTMOR
Solar/Wind Harmer
0.074
3146776BUCKING
Solar/Wind Harmer
0.066
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.481
970737AG2-469 GEN
Solar/Wind Harmer
7.427
316170AC1-121 GEN2
Solar/Wind Harmer
0.183
3151761LOISA E
Adder
22.218
972183AH1-676 GEN
Adder
173.787
970221AG2-151 GEN
Solar/Wind Harmer
8.67
971683AH1-343 GEN
Solar/Wind Harmer
5.958
316283AC2-100 C
Solar/Wind Harmer
0.309
972255AH1-712 GEN
Adder
76.037
3141316ARNOLDS
Adder
0.289
3141196NOKESVL
Solar/Wind Helper
1.164
3152251N ANNA1
50/50
19.951
971507AH1-251 GEN
50/50
16.627
970119AG2-088 GEN
50/50
35.342
3150851SPRUNCC
50/50
1.216
3143096IRON208
50/50
1.079
3152331SURRY 2
50/50
9.986
3150771HOPHCF1
50/50
0.977
316045AC1-158 PL2
Solar/Wind Harmer
9.742
3147666LOUISA
Solar/Wind Harmer
1.096
316192AB2-158 GEN
Solar/Wind Harmer
1.516
3143226MDLTHAN
Solar/Wind Harmer
0.265
3143526WINTERP
Solar/Wind Harmer
1.34
940641AE2-051 GEN
Solar/Wind Harmer
19.885
939411AE1-173 GEN
Solar/Wind Harmer
105.071
3142543TWELFTH
Solar/Wind Harmer
0.023
316294AC1-161 GEN
Solar/Wind Harmer
4.205
315671AE2-027_GEN
Solar/Wind Harmer
15.49
970129AG2-093 GEN
Solar/Wind Harmer
6.846
316458AB2-190 GEN2
Solar/Wind Harmer
1.291
944591AF1-124 GEN
Solar/Wind Harmer
54.321
971069AG2-661 GEN
Solar/Wind Harmer
4.273
944631AF1-128 GEN
Adder
114.478
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
2.995
971647AH1-324 GEN
Solar/Wind Harmer
10.238
970659AG2-427 GEN
Solar/Wind Harmer
11.598
961611AG1-000B GEN
Solar/Wind Harmer
12.573
3145336SMITFLD
Solar/Wind Harmer
0.958
316381AD1-082 GEN
Solar/Wind Harmer
0.25
3151171GRAVELC
Adder
2.547
970661AG2-428 GEN
Solar/Wind Harmer
23.769
3142416OLDCHRC
Solar/Wind Harmer
0.62
3142416OLDCHRC
Solar/Wind Harmer
0.237
316388AE2-253 GEN
Solar/Wind Harmer
0.746
3138126ROCKLANDING
Solar/Wind Harmer
0.109
3146456SLIGO L269
Solar/Wind Harmer
0.237
316072AD1-144
Solar/Wind Harmer
0.086
316159AE1-175 C
Solar/Wind Harmer
0.205
316246AF1-032 C
Solar/Wind Harmer
0.107
971317AH1-138 GEN
Solar/Wind Harmer
1.763
316093AE2-104_GEN
Solar/Wind Harmer
3.967
3142433PROV 92
Solar/Wind Harmer
0.929
3142433PROV 92
Adder
0.452
3142433PROV 92
Adder
0.452
3146516WINFALL
Solar/Wind Harmer
0.752
3146516WINFALL
Solar/Wind Harmer
0.232
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
4.063
971777AH1-397 GEN
Solar/Wind Harmer
0.6
3141843SHACKLE
Adder
1.161
3141766HARMONY
Solar/Wind Harmer
0.045
3130156CHOWAN
Solar/Wind Harmer
0.226
966881AG1-559 GEN
Solar/Wind Harmer
0.262
970919AG2-571 GEN
Solar/Wind Harmer
7.971
970087AG2-069 GEN
Solar/Wind Harmer
17.86
3138133OCRAN
Solar/Wind Harmer
0.133
3145663CRESWEL
Solar/Wind Harmer
0.62
971163AH1-040 GEN
Solar/Wind Harmer
17.736
972197AH1-683 GEN
Adder
4.589
972219AH1-694 GEN
Adder
3.304
316336AC2-165 C
Solar/Wind Harmer
0.009
316023GEN1_S
Solar/Wind Harmer
0.488
3146206CASHIE
Solar/Wind Harmer
0.215
971547AH1-271 GEN
Solar/Wind Harmer
4.597
3145893MURPHYS
Solar/Wind Harmer
0.86
3145893MURPHYS
Solar/Wind Harmer
0.956
957481AF2-042 GEN
Solar/Wind Harmer
57.154
3146173TUNIS
Solar/Wind Harmer
0.213
960081AF2-299 GEN
Solar/Wind Harmer
2.037
962861AG1-135 GEN
Solar/Wind Harmer
6.776
3145683EARLEYS
Solar/Wind Harmer
0.211
315693AD1-088 GEN
Solar/Wind Harmer
10.092
3146263WOODLND
Solar/Wind Harmer
0.21
962491AG1-098 GEN
Solar/Wind Harmer
11.964
316011AB1-132 GEN
Solar/Wind Harmer
3.787
962571AG1-106 GEN
Solar/Wind Harmer
2.963
971795AH1-408 GEN
Solar/Wind Harmer
13.875
3145963POPLR C
Solar/Wind Harmer
0.207
3141726DUNNSVL
Solar/Wind Harmer
0.83
316190AA2-174 GEN
Solar/Wind Harmer
0
3145823KELFORD
Solar/Wind Harmer
0.207
3147043LAWRENC
Adder
1.866
316174AB2-169 GEN
Solar/Wind Harmer
0.005
3145783HORNRTN
Solar/Wind Harmer
0.205
3145796HORNRTN
Solar/Wind Harmer
0.677
3145796HORNRTN
Solar/Wind Harmer
0.205
3150351NORNECKC2
Adder
2.041
316212AC1-099_GEN
Solar/Wind Harmer
1.035
3146293MARTNCO
Solar/Wind Harmer
0.185
316129AC1-054 GEN
Solar/Wind Harmer
0.746
971065AG2-659 GEN
Solar/Wind Harmer
8.425
3145746EVERETS
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.195
315722AD1-056 GEN
Solar/Wind Harmer
1.233
316337AD2-073 GEN
Solar/Wind Harmer
0.169
970937AG2-583 GEN
Solar/Wind Harmer
11.922
315687AD1-152 GEN
Solar/Wind Harmer
0.006
316494AC1-189 GEN
Solar/Wind Harmer
0.649
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970685AG2-442 GEN
Solar/Wind Harmer
14.314
963171AG1-166 GEN
Solar/Wind Harmer
1.021
971563AH1-280 GEN
Solar/Wind Harmer
2.042
3144293JTRSVLE
Adder
0.609
3146926FARMVIL
Solar/Wind Harmer
0.114
3146233WITAKRS
Solar/Wind Harmer
0.755
961671AG1-007 GEN
Solar/Wind Harmer
0.029
3146083TARBORO
Solar/Wind Harmer
0.189
3145493TOT1
Solar/Wind Harmer
0.843
3145543BTLEBRO
Solar/Wind Harmer
0.186
3145543BTLEBRO
Solar/Wind Harmer
0.149
316359AB2-059 GEN
Solar/Wind Harmer
0.669
316049AB1-081 GEN
Solar/Wind Harmer
1.066
3142053HEARTS
Solar/Wind Harmer
0.328
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.073
970401AG2-262 GEN
Solar/Wind Harmer
1.071
972003AH1-546 GEN
Solar/Wind Harmer
7.446
316254AC1-120 GEN1
Solar/Wind Harmer
0.366
316003AC1-222 GEN
Solar/Wind Harmer
0.004
3151751LOISA D
Adder
10.898
972135AH1-637 GEN
Solar/Wind Harmer
1.429
971377AH1-170 GEN
Solar/Wind Harmer
1.734
3147623JAMES R
Solar/Wind Harmer
0.377
972277AH1-723 GEN
Adder
88.606
971531AH1-263 GEN
50/50
60.398
316303AF2-085
50/50
4.712
971285AH1-108 GEN
50/50
1.991
970603AG2-384 GEN
50/50
5.178
316164AC1-076 GEN
Solar/Wind Harmer
0.448
316233AE1-074 FULL
Solar/Wind Harmer
0.206
971281AH1-106 GEN
Solar/Wind Harmer
3.576
971283AH1-107 GEN
Solar/Wind Harmer
3.576
3143316POE
Solar/Wind Harmer
0.962
941031AE2-094 GEN
Solar/Wind Harmer
44.489
944011AF1-069 GEN
Solar/Wind Harmer
14.536
316132AB2-190 GEN1
Solar/Wind Harmer
1.291
316369SG1_INVT
Solar/Wind Harmer
0.009
3151081ELIZAR1
Adder
22.001
3151091ELIZAR2
Adder
21.619
3152611GOSPORTB
Adder
3.055
3152621GOSPORTC
Adder
2.593
3152601GOSPORTA
Adder
2.392
971445AH1-216 GEN
Solar/Wind Harmer
16.874
972265AH1-717 GEN
Adder
18.594
3151201GRAVEL4
Adder
17.43
3151191GRAVEL3
Adder
17.21
3151211GRAVEL5
Adder
17.21
316312AB1-027
Solar/Wind Harmer
0.427
957871AF2-081 GEN
Solar/Wind Harmer
11.843
970673AG2-436 GEN
Solar/Wind Harmer
50.646
970673AG2-436 GEN
Solar/Wind Harmer
33.764
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.163
319010AE1-072 C
Solar/Wind Harmer
1.195
316311AC2-079 GEN
Solar/Wind Harmer
6.813
3146406KITTY HAWK
Solar/Wind Harmer
0.03
316305AF2-043 C
Solar/Wind Harmer
0.002
315976AC1-164 GENA
Solar/Wind Harmer
24.491
316169AC1-164_GENC
Solar/Wind Harmer
21.158
315975AC1-164 GENB
Solar/Wind Harmer
0.725
315835AF2-110_GEN
Solar/Wind Harmer
1.619
316315AB2-025 C
Solar/Wind Harmer
0.19
313526AB2-022
Solar/Wind Harmer
0.127
972189AH1-679 GEN
Adder
3.932
3146486SUNBURY
Solar/Wind Harmer
0.234
3146486SUNBURY
Solar/Wind Harmer
0.234
971967AH1-528 GEN
Solar/Wind Harmer
37.517
315814AE2-033 C
Solar/Wind Harmer
18.537
316321Z2-027
Solar/Wind Harmer
0.044
3146396TANGLEW
Solar/Wind Harmer
0.645
3145176PASQUOTANK
Solar/Wind Harmer
0.145
971167AH1-042 GEN
Solar/Wind Harmer
20.705
3142433PROV 92
Adder
0.452
3142433PROV 92
Adder
0.452
3138283WHITEMARSH
Solar/Wind Harmer
0.054
3143873LANEXA
Solar/Wind Harmer
0.138
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
316314AB2-024 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
6.735
316059AD1-063 C
Solar/Wind Harmer
0.001
315662AE1-191 GEN
Solar/Wind Harmer
0.007
315666AE1-190 GEN
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.226
3130156CHOWAN
Solar/Wind Harmer
0.226
3141873WAN 176
Solar/Wind Harmer
0.045
970085AG2-068 GEN
Solar/Wind Harmer
11.907
970581AG2-369 GEN
Solar/Wind Harmer
10.24
3141913WHIT STONE
Solar/Wind Harmer
0.222
3138133OCRAN
Solar/Wind Harmer
0.066
315816AE2-034 GEN
Solar/Wind Harmer
0.951
3141783LANCAST
Solar/Wind Harmer
0.132
3141783LANCAST
Solar/Wind Harmer
0.088
3150411LDYSMT5
Adder
29.481
3150381LDYSMT2
Adder
28.214
972213AH1-691 GEN
Adder
4.773
972215AH1-692 GEN
Adder
4.773
3130546PLYMOUTH
Solar/Wind Harmer
0.218
315732AD1-074 GEN1
Solar/Wind Harmer
1.25
315733AD1-074 GEN2
Solar/Wind Harmer
1.25
315735AD1-075 GEN1
Solar/Wind Harmer
0.626
965291AG1-394 GEN
Solar/Wind Harmer
0.964
962981AG1-147 GEN
Solar/Wind Harmer
8.079
3146206CASHIE
Solar/Wind Harmer
0.215
970601AG2-382 GEN
Solar/Wind Harmer
8.044
3145893MURPHYS
Solar/Wind Harmer
0.581
3145893MURPHYS
Solar/Wind Harmer
0.215
970327AG2-215 GEN
Solar/Wind Harmer
7.032
3145513AHOSKIE
Solar/Wind Harmer
0.443
3145513AHOSKIE
Solar/Wind Harmer
0.212
3146043SEABORD
Solar/Wind Harmer
0.211
3145683EARLEYS
Solar/Wind Harmer
0.422
3145683EARLEYS
Solar/Wind Harmer
0.211
3145683EARLEYS
Solar/Wind Harmer
0.211
315607AA1-063A GEN
Solar/Wind Harmer
0.431
316087AB2-174 GEN
Solar/Wind Harmer
0.006
315652AC1-086 GEN
Solar/Wind Harmer
22.91
3137643SOCKMAN
Solar/Wind Harmer
0.831
3145796HORNRTN
Solar/Wind Harmer
0.656
3145796HORNRTN
Solar/Wind Harmer
0.082
3141813NORNECK
Solar/Wind Harmer
0.205
3146033SCOT NK
Solar/Wind Harmer
0.813
970831AG2-522 GEN
Solar/Wind Harmer
8.493
316005AA1-067
Solar/Wind Harmer
0.209
3145746EVERETS
Solar/Wind Harmer
0.776
3145746EVERETS
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.195
970181AG2-120 GEN
Solar/Wind Harmer
2.429
957861AF2-080 GEN
Solar/Wind Harmer
8.286
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
3.225
3144303KENBRDG
Solar/Wind Harmer
0.153
970683AG2-441 GEN
Solar/Wind Harmer
12.781
970681AG2-440 GEN
Solar/Wind Harmer
10.225
946301AF1-294 GEN
Solar/Wind Harmer
3.778
961791AG1-021 GEN
Solar/Wind Harmer
1.838
315657AE1-056 GEN
Solar/Wind Harmer
6.598
316420AA1-050 GEN
Solar/Wind Harmer
0.006
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.189
3145573BETHELC
Solar/Wind Harmer
0.189
970285AG2-188 GEN
Solar/Wind Harmer
14.603
316223AC1-118
Solar/Wind Harmer
0.132
971845AH1-439 GEN
Solar/Wind Harmer
8.313
316118AC1-105 GEN
Solar/Wind Harmer
0.462
3147173SINAI
Solar/Wind Harmer
0.175
3147243WELCO
Solar/Wind Harmer
0.11
972205AH1-687 GEN
Adder
7.416
3147346CASHSCORNER
Solar/Wind Harmer
0.37
944491AF1-114 GEN
Solar/Wind Harmer
0.001
971447AH1-217 GEN
Solar/Wind Harmer
4.798
970865AG2-541 GEN
Solar/Wind Harmer
5.388
972193AH1-681 GEN
Adder
3.397
270494AE1-108_GEN
Solar/Wind Harmer
1.716
316123AC1-075 GEN
Solar/Wind Harmer
0.194
970165AG2-112 GEN
Solar/Wind Harmer
1.153
970163AG2-111 GEN
Solar/Wind Harmer
1.1
3138266HYDRAULIC
Solar/Wind Harmer
0.006
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316411AF1-147_GEN1
Solar/Wind Helper
0.82
316415AF1-147_GEN2
Solar/Wind Helper
0.82
3138216PACIFIC
Solar/Wind Helper
0.04
971133AH1-012 GEN
50/50
5.665
944641AF1-129 GEN
50/50
122.768
3142366NRTHEST
50/50
0.838
970533AG2-339 GEN
50/50
21.472
970531AG2-338 GEN
50/50
8.589
3150781HOPHCF2
50/50
0.977
3150791HOPHCF3
50/50
0.977
3150761HOPPOLC
50/50
0.62
971213AH1-066 GEN
50/50
0.857
3150691DARBY 3
50/50
18.39
316447AC1-158 HLD
Solar/Wind Harmer
6.696
971223AH1-071 GEN
Solar/Wind Harmer
2.827
3143526WINTERP
Solar/Wind Harmer
1.34
316240AF1-291 C
Solar/Wind Harmer
0.002
3150701DARBY 4
Adder
17.29
3150681DARBY 2
Adder
17.27
3150671DARBY 1
Adder
17.25
3142296MT RD221
Adder
0.765
316033AB2-134 GEN
Solar/Wind Harmer
0.014
315697AD1-025 GEN
Solar/Wind Harmer
0.27
316036AC1-147 C
Solar/Wind Harmer
0.045
3150991CHESPKB
Adder
2.513
3150991CHESPKB
Adder
2.452
316236AE1-162_GEN
Solar/Wind Harmer
0.002
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.23
316185AD1-033 GEN
Solar/Wind Harmer
0.007
970657AG2-426 GEN
Solar/Wind Harmer
8.383
970657AG2-426 GEN
Solar/Wind Harmer
1.758
3142946ENON
Solar/Wind Harmer
0.024
3145506HICKORY
Solar/Wind Harmer
0.955
3145506HICKORY
Solar/Wind Harmer
0.573
3145506HICKORY
Solar/Wind Harmer
0.143
316339AD2-160 GEN
Solar/Wind Harmer
0.386
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
316017AA1-139 ULT1
Solar/Wind Harmer
0.133
316075AC2-137 C
Solar/Wind Harmer
0.065
3137176SLIGO L2192
Solar/Wind Harmer
0.945
3146456SLIGO L269
Solar/Wind Harmer
4.201
3130086AYDLETT
Solar/Wind Harmer
0.948
972185AH1-677 GEN
Adder
13.205
3144356SAPONY
Solar/Wind Harmer
1.967
3146386ELIZ CT
Solar/Wind Harmer
0.235
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
972187AH1-678 GEN
Adder
6.623
3146516WINFALL
Solar/Wind Harmer
0.232
3146516WINFALL
Solar/Wind Harmer
0.232
3146516WINFALL
Solar/Wind Harmer
0.232
966871AG1-558 GEN
Solar/Wind Harmer
0.267
3146626S HERTFORD
Solar/Wind Harmer
0.231
3146626S HERTFORD
Solar/Wind Harmer
0.231
970933AG2-581 GEN
Solar/Wind Harmer
18.312
315742AE1-103 GEN
Solar/Wind Harmer
0.003
957411AF2-035 GEN
Solar/Wind Harmer
9.66
970317AG2-208 GEN
Solar/Wind Harmer
8.949
3146376EDENTON
Solar/Wind Harmer
1.006
3146376EDENTON
Solar/Wind Harmer
1.006
315673AE1-157 GEN
Solar/Wind Harmer
15.472
3150391LDYSMT3
Adder
29.334
972195AH1-682 GEN
Adder
3.855
316065AD1-022 GEN
Solar/Wind Harmer
9.955
3145893MURPHYS
Solar/Wind Harmer
1.439
3145893MURPHYS
Solar/Wind Harmer
0.387
970099AG2-077 GEN
Solar/Wind Harmer
22.861
3146173TUNIS
Solar/Wind Harmer
0.213
3146173TUNIS
Solar/Wind Harmer
0.213
958261AF2-120 GEN
Solar/Wind Harmer
6.972
316181AB2-040 GEN
Solar/Wind Harmer
0.304
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3142666NORTHAMPTON
Solar/Wind Harmer
0.125
316426AA2-053 GEN
Solar/Wind Harmer
0.701
3145593CAROLNA
Solar/Wind Harmer
0.207
3145593CAROLNA
Solar/Wind Harmer
0.207
966811AG1-552 GEN
Solar/Wind Harmer
2.242
3145593CAROLNA
Solar/Wind Harmer
0.257
3145783HORNRTN
Solar/Wind Harmer
3.653
3145783HORNRTN
Solar/Wind Harmer
2.922
3145783HORNRTN
Solar/Wind Harmer
0.913
3145783HORNRTN
Solar/Wind Harmer
0.365
3145796HORNRTN
Solar/Wind Harmer
0.615
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.144
3150341NORNECKC1
Adder
2.127
971741AH1-377 GEN
Solar/Wind Harmer
19.978
3145933PARMELE
Solar/Wind Harmer
0.398
3145933PARMELE
Solar/Wind Harmer
0.199
316274AC1-208 GEN
Solar/Wind Harmer
1.032
970301AG2-198 GEN
Solar/Wind Harmer
8.48
316468AD1-105 GEN
Solar/Wind Harmer
-0.064
939181AE1-148 GEN
Solar/Wind Harmer
9.287
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.014
970323AG2-213 GEN
Solar/Wind Harmer
8.19
971775AH1-396 GEN
Solar/Wind Harmer
0.307
958211AF2-115 GEN
Solar/Wind Harmer
2.298
963191AG1-168 GEN
Solar/Wind Harmer
0.766
3144293JTRSVLE
Adder
0.609
3144293JTRSVLE
Adder
0.513
3147133PAMPLIN
Solar/Wind Harmer
0.191
3147133PAMPLIN
Solar/Wind Harmer
0.153
3145493TOT1
Solar/Wind Harmer
0.439
3145453TOT5
Solar/Wind Harmer
0.264
3145603CNETO
Solar/Wind Harmer
0.176
961601AG1-000A GEN
Solar/Wind Harmer
3.314
316263AC1-034 GEN
Solar/Wind Harmer
7.082
962561AG1-105 GEN
Solar/Wind Harmer
8.835
3146776BUCKING
Solar/Wind Harmer
0.73
3146776BUCKING
Solar/Wind Harmer
0.059
964791AG1-342 GEN
Solar/Wind Harmer
3.505
3146843MT LREL
Solar/Wind Harmer
0.182
3146843MT LREL
Solar/Wind Harmer
0.182
966001AG1-469 GEN
Solar/Wind Harmer
0.098
3151731LOISA B
Adder
10.898
3151721LOISA A
Adder
10.842
971489AH1-241 GEN
Solar/Wind Harmer
8.67
316222AC1-221 GEN
Solar/Wind Harmer
0.658
315821AE2-092 GEN
Solar/Wind Harmer
0.008
942751AE2-291 GEN
Solar/Wind Harmer
7.283
315651AD1-115 GEN
Solar/Wind Harmer
0.004
NYPJM->LTFIMP_NY
CLTF
3.433
LGEELTFEXP_LGEE->PJM
CLTF
1.291
WECLTFEXP_WEC->PJM
CLTF
0.616
LAGNLTFEXP_LAGN->PJM
CLTF
8.202
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.311
TVALTFEXP_TVA->PJM
CLTF
4.157
CBM West 1LTFEXP_CBM-W1->PJM
CBM
20.192
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.068
MECLTFEXP_MEC->PJM
CLTF
3.555
SIGELTFEXP_SIGE->PJM
CLTF
0.108
CPLELTFEXP_CPLE->PJM
CLTF
12.074
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.739

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 574T575_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 574T575_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:179.37 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:7067.14
MW Contribution:72.11
Bus #Bus NameTypeMW Contribution
3152251N ANNA1
50/50
30.744
970119AG2-088 GEN
50/50
39.456
3151791S ANNAG2
50/50
0.958
3151781S ANNAS1
50/50
0.492
315243AE2-183_GT3
50/50
4.407
3151051BRUNSWICKS1
50/50
7.204
3151021BRUNSWICKG1
50/50
3.471
971451AH1-221 GEN
50/50
10.542
3151741LOISA C
50/50
0.984
3151751LOISA D
50/50
17.992
316045AC1-158 PL2
Solar/Wind Harmer
27.219
3147666LOUISA
Solar/Wind Harmer
-0.19
316192AB2-158 GEN
Solar/Wind Harmer
5.545
3143226MDLTHAN
Solar/Wind Harmer
-0.033
940641AE2-051 GEN
Solar/Wind Harmer
29.235
3143526WINTERP
Solar/Wind Harmer
-0.157
939411AE1-173 GEN
Solar/Wind Harmer
151.543
3143336POWHATN
Solar/Wind Harmer
3.431
970919AG2-571 GEN
Solar/Wind Harmer
9.022
970087AG2-069 GEN
Solar/Wind Harmer
26.614
316294AC1-161 GEN
Solar/Wind Harmer
9.062
944591AF1-124 GEN
Solar/Wind Harmer
127.089
316336AC2-165 C
Solar/Wind Harmer
4.826
316375AC2-012 GEN
Solar/Wind Harmer
9.564
3150981CHESPKA
Adder
3.071
316388AE2-253 GEN
Solar/Wind Harmer
1.858
3146456SLIGO L269
Solar/Wind Harmer
-0.027
316246AF1-032 C
Solar/Wind Harmer
0.555
970659AG2-427 GEN
Solar/Wind Harmer
14.512
316381AD1-082 GEN
Solar/Wind Harmer
2.505
970661AG2-428 GEN
Solar/Wind Harmer
29.016
316093AE2-104_GEN
Solar/Wind Harmer
7.933
3150851SPRUNCC
Adder
1.117
957481AF2-042 GEN
Solar/Wind Harmer
85.059
316072AD1-144
Solar/Wind Harmer
0.549
3145336SMITFLD
Solar/Wind Harmer
-0.107
3146516WINFALL
Solar/Wind Harmer
-0.087
3146516WINFALL
Solar/Wind Harmer
-0.027
315800Z1-036_GEN1
Solar/Wind Harmer
6.597
315693AD1-088 GEN
Solar/Wind Harmer
13.348
962491AG1-098 GEN
Solar/Wind Harmer
17.806
3151171GRAVELC
Adder
2.519
3130156CHOWAN
Solar/Wind Harmer
-0.026
315671AE2-027_GEN
Solar/Wind Harmer
19.85
961611AG1-000B GEN
Solar/Wind Harmer
13.059
971647AH1-324 GEN
Solar/Wind Harmer
13.175
316023GEN1_S
Solar/Wind Harmer
1.771
971069AG2-661 GEN
Solar/Wind Harmer
4.138
3145663CRESWEL
Solar/Wind Harmer
-0.073
971163AH1-040 GEN
Solar/Wind Harmer
24.415
316458AB2-190 GEN2
Solar/Wind Harmer
2.633
970129AG2-093 GEN
Solar/Wind Harmer
5.931
960081AF2-299 GEN
Solar/Wind Harmer
2.896
3138126ROCKLANDING
Solar/Wind Harmer
0.079
3142543TWELFTH
Solar/Wind Harmer
-0.002
3145893MURPHYS
Solar/Wind Harmer
-0.102
3145893MURPHYS
Solar/Wind Harmer
0.759
3146206CASHIE
Solar/Wind Harmer
-0.025
971547AH1-271 GEN
Solar/Wind Harmer
6.373
971795AH1-408 GEN
Solar/Wind Harmer
19.052
3146173TUNIS
Solar/Wind Harmer
-0.025
3147043LAWRENC
Adder
2.033
3145683EARLEYS
Solar/Wind Harmer
-0.025
316011AB1-132 GEN
Solar/Wind Harmer
5.258
962571AG1-106 GEN
Solar/Wind Harmer
3.612
3146263WOODLND
Solar/Wind Harmer
-0.025
3143096IRON208
Adder
0.935
316190AA2-174 GEN
Solar/Wind Harmer
0.307
971317AH1-138 GEN
Solar/Wind Harmer
3.127
970937AG2-583 GEN
Solar/Wind Harmer
17.864
3145783HORNRTN
Solar/Wind Harmer
-0.025
316159AE1-175 C
Solar/Wind Harmer
0.666
3145823KELFORD
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.081
3145796HORNRTN
Solar/Wind Harmer
-0.025
944631AF1-128 GEN
Adder
104.9
3145963POPLR C
Solar/Wind Harmer
-0.025
315687AD1-152 GEN
Solar/Wind Harmer
2.961
316174AB2-169 GEN
Solar/Wind Harmer
3.783
316129AC1-054 GEN
Solar/Wind Harmer
2.143
971065AG2-659 GEN
Solar/Wind Harmer
12.198
3146926FARMVIL
Solar/Wind Harmer
-0.014
963171AG1-166 GEN
Solar/Wind Harmer
3.025
971563AH1-280 GEN
Solar/Wind Harmer
3.025
3144293JTRSVLE
Adder
0.686
970685AG2-442 GEN
Solar/Wind Harmer
21.155
3142433PROV 92
Adder
0.401
3142433PROV 92
Adder
0.401
3141843SHACKLE
Adder
1.013
3150351NORNECKC2
Adder
1.557
972277AH1-723 GEN
Adder
72.107
3152261N ANNA2
50/50
30.741
3151771S ANNAG1
50/50
0.958
3151801S ANNAS2
50/50
0.492
3151031BRUNSWICKG2
50/50
3.471
3151761LOISA E
50/50
36.68
972183AH1-676 GEN
50/50
287.058
316044AC1-158 PL1
Solar/Wind Harmer
8.509
316450AC1-158 RIC
Solar/Wind Harmer
2.269
3147666LOUISA
Solar/Wind Harmer
-0.109
316313AB2-026
Solar/Wind Harmer
0.78
316258AE1-075 C
Solar/Wind Harmer
0.702
316405AF2-144 C
Solar/Wind Harmer
0.741
3143336POWHATN
Solar/Wind Harmer
2.916
970917AG2-570 GEN
Solar/Wind Harmer
71.277
315773AC2-141 GEN
Solar/Wind Harmer
11.72
944581AF1-123 GEN
Solar/Wind Harmer
126.633
944601AF1-125 GEN
Solar/Wind Harmer
124.656
3151101ELIZAR3
Adder
22.862
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146456SLIGO L269
Solar/Wind Harmer
-0.027
971153AH1-033 GEN
Solar/Wind Harmer
3.351
3144536CHRHLND
Solar/Wind Harmer
-0.004
315813AE1-149 C
Solar/Wind Harmer
17.079
970659AG2-427 GEN
Solar/Wind Harmer
2.572
316083AB2-161 GEN
Solar/Wind Harmer
4.433
970661AG2-428 GEN
Solar/Wind Harmer
5.142
316320Y1-086
Solar/Wind Harmer
1.598
3132273ORANGE
Solar/Wind Harmer
-0.005
3150861SPRUNCD
Adder
1.117
316435W1029_GEN3
Solar/Wind Harmer
4.902
315839AE2-212 C
Solar/Wind Harmer
0.814
3146516WINFALL
Solar/Wind Harmer
-0.027
3145336SMITFLD
Solar/Wind Harmer
-0.011
3146626S HERTFORD
Solar/Wind Harmer
-0.027
3145273HOLLAND
Solar/Wind Harmer
-0.02
965281AG1-393 GEN
Solar/Wind Harmer
3.333
3151221GRAVEL6
Adder
17.215
3151171GRAVELC
Adder
3.312
3146376EDENTON
Solar/Wind Harmer
-0.026
961611AG1-000B GEN
Solar/Wind Harmer
5.572
316365GEN2_N
Solar/Wind Harmer
1.771
315778AD1-151 GEN
Solar/Wind Harmer
22.655
316478AD1-087 GEN
Solar/Wind Harmer
2.264
316486AD2-202 GEN
Solar/Wind Harmer
0.663
315614AA2-178 GEN
Solar/Wind Harmer
2.81
970129AG2-093 GEN
Solar/Wind Harmer
14.642
3156081AA2-088 GEN
Solar/Wind Harmer
8.385
970133AG2-095 GEN
Solar/Wind Harmer
2.902
3144216WINCHST
Adder
0.865
966621AG1-532 GEN
Solar/Wind Harmer
0.522
971157AH1-035 GEN
Solar/Wind Harmer
3.215
315737AD1-076 GEN
Solar/Wind Harmer
4.877
3150921YORKTN3
Adder
5.73
3145893MURPHYS
Solar/Wind Harmer
0.178
3145893MURPHYS
Solar/Wind Harmer
-0.025
957521AF2-046 GEN
Solar/Wind Harmer
20.091
961681AG1-008 GEN
Solar/Wind Harmer
20.091
3146206CASHIE
Solar/Wind Harmer
-0.025
313506AB2-031 GEN
Solar/Wind Harmer
2.041
3146173TUNIS
Solar/Wind Harmer
-0.025
970909AG2-566 GEN
Solar/Wind Harmer
2.403
316463AE2-346 GEN
Solar/Wind Harmer
0.409
316140AB2-099
Solar/Wind Harmer
0.17
962331AG1-082 GEN
Solar/Wind Harmer
3.158
3156021HOLLOMANSOL
Solar/Wind Harmer
3.402
3147043LAWRENC
Solar/Wind Harmer
-0.015
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3146263WOODLND
Solar/Wind Harmer
-0.025
3143096IRON208
Adder
0.935
3143096IRON208
Adder
0.916
316382AG1-145 C
Solar/Wind Harmer
0.748
316317KELFORD C
Solar/Wind Harmer
1.169
3145823KELFORD
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.099
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145963POPLR C
Solar/Wind Harmer
-0.025
3142946ENON
Solar/Wind Harmer
-0.008
3146926FARMVIL
Solar/Wind Harmer
-0.014
942461AE2-259 GEN
Solar/Wind Harmer
3.644
3147133PAMPLIN
Solar/Wind Harmer
-0.076
971193AH1-056 GEN
Solar/Wind Harmer
15.132
963181AG1-167 GEN
Solar/Wind Harmer
2.268
3144293JTRSVLE
Adder
0.686
3142433PROV 92
Adder
0.401
3142433PROV 92
Adder
0.401
3141843SHACKLE
Adder
1.013
3150351NORNECKC2
Adder
1.583
972255AH1-712 GEN
Adder
61.879
3141196NOKESVL
Solar/Wind Helper
1.074
959311AF2-222 GEN
Solar/Wind Harmer
12.268
971133AH1-012 GEN
50/50
8.748
970533AG2-339 GEN
50/50
24.369
970531AG2-338 GEN
50/50
9.748
315242AE2-183_GT2
50/50
4.407
315241AE2-183_GT1
50/50
4.38
972185AH1-677 GEN
50/50
15.889
3151041BRUNSWICKG3
50/50
3.471
972187AH1-678 GEN
50/50
7.965
3151731LOISA B
50/50
17.992
3151721LOISA A
50/50
17.899
316447AC1-158 HLD
Solar/Wind Harmer
18.712
971223AH1-071 GEN
Solar/Wind Harmer
4.156
3143526WINTERP
Solar/Wind Harmer
-0.157
970933AG2-581 GEN
Solar/Wind Harmer
27.317
3144356SAPONY
Solar/Wind Harmer
0.989
966001AG1-469 GEN
Solar/Wind Harmer
0.532
316185AD1-033 GEN
Solar/Wind Harmer
2.919
3142956BIRDNECK
Solar/Wind Harmer
1.484
316316AC1-027 C
Solar/Wind Harmer
0.849
316036AC1-147 C
Solar/Wind Harmer
0.746
3150991CHESPKB
Adder
2.576
3150991CHESPKB
Adder
2.515
3145506HICKORY
Solar/Wind Harmer
-0.11
3145506HICKORY
Solar/Wind Harmer
-0.066
3145506HICKORY
Solar/Wind Harmer
-0.016
316339AD2-160 GEN
Solar/Wind Harmer
1.858
316018AA1-139 ULT2
Solar/Wind Harmer
2.359
316017AA1-139 ULT1
Solar/Wind Harmer
2.228
3137176SLIGO L2192
Solar/Wind Harmer
-0.109
3146456SLIGO L269
Solar/Wind Harmer
3.247
3130086AYDLETT
Solar/Wind Harmer
-0.109
970657AG2-426 GEN
Solar/Wind Harmer
8.535
970657AG2-426 GEN
Solar/Wind Harmer
1.785
3146386ELIZ CT
Solar/Wind Harmer
-0.027
970099AG2-077 GEN
Solar/Wind Harmer
34.024
316431W1029_GEN1
Solar/Wind Harmer
4.902
316433W1029_GEN2
Solar/Wind Harmer
4.902
316236AE1-162_GEN
Solar/Wind Harmer
0.814
3146516WINFALL
Solar/Wind Harmer
-0.027
3146516WINFALL
Solar/Wind Harmer
-0.027
3146516WINFALL
Solar/Wind Harmer
-0.027
3146626S HERTFORD
Solar/Wind Harmer
-0.027
3146626S HERTFORD
Solar/Wind Harmer
-0.027
315742AE1-103 GEN
Solar/Wind Harmer
2.783
3146376EDENTON
Solar/Wind Harmer
0.785
3146376EDENTON
Solar/Wind Harmer
0.785
316240AF1-291 C
Solar/Wind Harmer
0.795
316033AB2-134 GEN
Solar/Wind Harmer
8.462
315697AD1-025 GEN
Solar/Wind Harmer
5.307
944641AF1-129 GEN
Adder
111.019
971741AH1-377 GEN
Solar/Wind Harmer
29.798
3145893MURPHYS
Solar/Wind Harmer
0.713
3145893MURPHYS
Solar/Wind Harmer
-0.046
316065AD1-022 GEN
Solar/Wind Harmer
12.776
316181AB2-040 GEN
Solar/Wind Harmer
3.542
3146173TUNIS
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.025
970301AG2-198 GEN
Solar/Wind Harmer
12.658
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.015
316426AA2-053 GEN
Solar/Wind Harmer
2.529
3145593CAROLNA
Solar/Wind Harmer
-0.025
3145593CAROLNA
Solar/Wind Harmer
-0.025
966811AG1-552 GEN
Solar/Wind Harmer
2.813
3145593CAROLNA
Solar/Wind Harmer
0.208
3145783HORNRTN
Solar/Wind Harmer
2.949
3145783HORNRTN
Solar/Wind Harmer
2.359
3145783HORNRTN
Solar/Wind Harmer
0.737
3145783HORNRTN
Solar/Wind Harmer
0.295
3145796HORNRTN
Solar/Wind Harmer
-0.074
3142946ENON
Solar/Wind Harmer
-0.002
3147133PAMPLIN
Solar/Wind Harmer
-0.024
3147133PAMPLIN
Solar/Wind Harmer
-0.019
958211AF2-115 GEN
Solar/Wind Harmer
3.781
963191AG1-168 GEN
Solar/Wind Harmer
2.268
3144293JTRSVLE
Adder
0.686
3144293JTRSVLE
Adder
0.577
3142366NRTHEST
Adder
0.692
3150691DARBY 3
Adder
15.167
3150701DARBY 4
Adder
15.132
3150681DARBY 2
Adder
15.114
3150671DARBY 1
Adder
15.096
3142296MT RD221
Adder
0.621
3150341NORNECKC1
Adder
1.636
3150341NORNECKC1
Adder
1.623
226929AD2-058 GEN
Solar/Wind Helper
0.087
316303AF2-085
50/50
5.261
315244AE2-183_ST
50/50
7.62
963041AG1-153 GEN
50/50
7.028
315779AE2-040
50/50
3.522
316164AC1-076 GEN
Solar/Wind Harmer
2.938
941031AE2-094 GEN
Solar/Wind Harmer
57.754
944011AF1-069 GEN
Solar/Wind Harmer
18.096
316233AE1-074 FULL
Solar/Wind Harmer
0.818
971281AH1-106 GEN
Solar/Wind Harmer
4.94
971283AH1-107 GEN
Solar/Wind Harmer
4.94
970673AG2-436 GEN
Solar/Wind Harmer
63.56
970673AG2-436 GEN
Solar/Wind Harmer
32.182
971967AH1-528 GEN
Solar/Wind Harmer
56.158
970085AG2-068 GEN
Solar/Wind Harmer
17.743
970581AG2-369 GEN
Solar/Wind Harmer
15.259
316315AB2-025 C
Solar/Wind Harmer
0.765
315814AE2-033 C
Solar/Wind Harmer
26.3
3143316POE
Solar/Wind Harmer
-0.11
3151081ELIZAR1
Adder
22.573
3151091ELIZAR2
Adder
22.181
3152611GOSPORTB
Adder
3.132
3152621GOSPORTC
Adder
2.658
3152601GOSPORTA
Adder
2.452
957871AF2-081 GEN
Solar/Wind Harmer
13.769
319010AE1-072 C
Solar/Wind Harmer
5.558
3147346CASHSCORNER
Solar/Wind Harmer
0.425
3146406KITTY HAWK
Solar/Wind Harmer
0.023
316305AF2-043 C
Solar/Wind Harmer
0.826
315833AF1-017_GEN
Solar/Wind Harmer
5.184
316349AD2-085 GEN
Solar/Wind Harmer
2.427
316311AC2-079 GEN
Solar/Wind Harmer
13.767
315835AF2-110_GEN
Solar/Wind Harmer
3.41
313526AB2-022
Solar/Wind Harmer
0.736
971285AH1-108 GEN
Adder
1.828
3146486SUNBURY
Solar/Wind Harmer
-0.027
3146486SUNBURY
Solar/Wind Harmer
-0.027
316321Z2-027
Solar/Wind Harmer
0.733
3146396TANGLEW
Solar/Wind Harmer
0.5
3145176PASQUOTANK
Solar/Wind Harmer
-0.017
971445AH1-216 GEN
Solar/Wind Harmer
16.689
315611Z1-036_GEN2
Solar/Wind Harmer
6.597
972265AH1-717 GEN
Adder
18.385
3151201GRAVEL4
Adder
17.235
3151191GRAVEL3
Adder
17.017
3151211GRAVEL5
Adder
17.017
3130156CHOWAN
Solar/Wind Harmer
-0.026
3130156CHOWAN
Solar/Wind Harmer
-0.026
316369SG1_INVT
Solar/Wind Harmer
4.688
315816AE2-034 GEN
Solar/Wind Harmer
2.107
316132AB2-190 GEN1
Solar/Wind Harmer
2.633
965291AG1-394 GEN
Solar/Wind Harmer
2.286
946281AF1-292 GEN
Solar/Wind Harmer
0.577
3130546PLYMOUTH
Solar/Wind Harmer
-0.026
315732AD1-074 GEN1
Solar/Wind Harmer
5.189
315733AD1-074 GEN2
Solar/Wind Harmer
5.189
315735AD1-075 GEN1
Solar/Wind Harmer
2.595
316318V4-068
Solar/Wind Harmer
0.637
3145893MURPHYS
Solar/Wind Harmer
-0.069
3145893MURPHYS
Solar/Wind Harmer
-0.025
316087AB2-174 GEN
Solar/Wind Harmer
3.638
3146206CASHIE
Solar/Wind Harmer
-0.025
970601AG2-382 GEN
Solar/Wind Harmer
11.153
3146043SEABORD
Solar/Wind Harmer
-0.025
315607AA1-063A GEN
Solar/Wind Harmer
2.556
3145513AHOSKIE
Solar/Wind Harmer
0.22
961941AG1-037 GEN
Solar/Wind Harmer
0.19
3145513AHOSKIE
Solar/Wind Harmer
-0.025
3137643SOCKMAN
Solar/Wind Harmer
-0.1
3145683EARLEYS
Solar/Wind Harmer
-0.05
3145683EARLEYS
Solar/Wind Harmer
-0.025
3145683EARLEYS
Solar/Wind Harmer
-0.025
315652AC1-086 GEN
Solar/Wind Harmer
28.271
3145796HORNRTN
Solar/Wind Harmer
-0.079
3145796HORNRTN
Solar/Wind Harmer
-0.01
970831AG2-522 GEN
Solar/Wind Harmer
12.25
3146033SCOT NK
Solar/Wind Harmer
-0.097
315657AE1-056 GEN
Solar/Wind Harmer
9.079
946301AF1-294 GEN
Solar/Wind Harmer
6.2
961791AG1-021 GEN
Solar/Wind Harmer
3.025
970683AG2-441 GEN
Solar/Wind Harmer
18.888
970681AG2-440 GEN
Solar/Wind Harmer
15.111
3142433PROV 92
Adder
0.401
3142433PROV 92
Adder
0.401
972205AH1-687 GEN
Adder
8.511
972189AH1-679 GEN
Adder
2.2
972193AH1-681 GEN
Adder
2.765
316411AF1-147_GEN1
Solar/Wind Helper
0.849
316415AF1-147_GEN2
Solar/Wind Helper
0.849
3138216PACIFIC
Solar/Wind Helper
0.042
NYPJM->LTFIMP_NY
CLTF
3.877
LGEELTFEXP_LGEE->PJM
CLTF
1.536
WECLTFEXP_WEC->PJM
CLTF
0.747
LAGNLTFEXP_LAGN->PJM
CLTF
9.308
CBM South 2LTFEXP_CBM-S2->PJM
CBM
29.279
TVALTFEXP_TVA->PJM
CLTF
4.707
CBM West 1LTFEXP_CBM-W1->PJM
CBM
24.945
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.004
MECLTFEXP_MEC->PJM
CLTF
4.2
SIGELTFEXP_SIGE->PJM
CLTF
0.127
CPLELTFEXP_CPLE->PJM
CLTF
13.402
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.993

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 581_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:175.06 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:5637.7
MW Contribution:86.87
Bus #Bus NameTypeMW Contribution
3152261N ANNA2
50/50
19.717
3150861SPRUNCD
50/50
1.197
3143096IRON208
50/50
1.062
3143096IRON208
50/50
1.041
3150801HOPHCF4
50/50
1.399
971211AH1-065 GEN
50/50
1.687
3151161SURRY 1
50/50
9.055
316044AC1-158 PL1
Solar/Wind Harmer
3.023
316450AC1-158 RIC
Solar/Wind Harmer
0.806
3147666LOUISA
Solar/Wind Harmer
0.614
315839AE2-212 C
Solar/Wind Harmer
0.002
315773AC2-141 GEN
Solar/Wind Harmer
8.726
965281AG1-393 GEN
Solar/Wind Harmer
2.543
315813AE1-149 C
Solar/Wind Harmer
12.658
970133AG2-095 GEN
Solar/Wind Harmer
2.278
970129AG2-093 GEN
Solar/Wind Harmer
14.319
944581AF1-123 GEN
Solar/Wind Harmer
53.293
944601AF1-125 GEN
Solar/Wind Harmer
52.472
315778AD1-151 GEN
Solar/Wind Harmer
18.928
3151101ELIZAR3
Adder
21.938
3144536CHRHLND
Solar/Wind Harmer
0.035
3144873MCLAUGH
Solar/Wind Harmer
0.006
970659AG2-427 GEN
Solar/Wind Harmer
2.498
3145336SMITFLD
Solar/Wind Harmer
0.094
961611AG1-000B GEN
Solar/Wind Harmer
6.293
316083AB2-161 GEN
Solar/Wind Harmer
0.003
3151221GRAVEL6
Adder
17.139
3151171GRAVELC
Adder
3.297
970293AG2-193 GEN
Solar/Wind Harmer
2.512
970661AG2-428 GEN
Solar/Wind Harmer
4.977
3142946ENON
Solar/Wind Harmer
0.079
3142416OLDCHRC
Solar/Wind Harmer
2.274
3144216WINCHST
Adder
0.882
3146456SLIGO L269
Solar/Wind Harmer
0.234
971153AH1-033 GEN
Solar/Wind Harmer
2.702
3150921YORKTN3
Adder
5.872
316382AG1-145 C
Solar/Wind Harmer
0.002
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3142433PROV 92
Adder
0.445
3142433PROV 92
Adder
0.445
3146516WINFALL
Solar/Wind Harmer
0.229
316473AC1-191 GEN
Solar/Wind Harmer
0.768
3146626S HERTFORD
Solar/Wind Harmer
0.227
3145273HOLLAND
Solar/Wind Harmer
0.17
316313AB2-026
Solar/Wind Harmer
0.142
316258AE1-075 C
Solar/Wind Harmer
0.17
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.394
3141843SHACKLE
Adder
1.143
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3141766HARMONY
Solar/Wind Harmer
2.978
316280AD1-041 GEN
Solar/Wind Harmer
0.005
3146376EDENTON
Solar/Wind Harmer
0.223
316156AD2-030 GEN
Solar/Wind Harmer
0.165
3141873WAN 176
Solar/Wind Harmer
3.95
970917AG2-570 GEN
Solar/Wind Harmer
19.626
315614AA2-178 GEN
Solar/Wind Harmer
1.249
3150401LDYSMT4
Adder
28.893
3150371LDYSMT1
Adder
27.918
971157AH1-035 GEN
Solar/Wind Harmer
2.577
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
316365GEN2_N
Solar/Wind Harmer
0.481
315737AD1-076 GEN
Solar/Wind Harmer
2.755
962971AG1-146 GEN
Solar/Wind Harmer
3.408
3146206CASHIE
Solar/Wind Harmer
0.212
3145893MURPHYS
Solar/Wind Harmer
0.354
3145893MURPHYS
Solar/Wind Harmer
0.212
957521AF2-046 GEN
Solar/Wind Harmer
15.715
961681AG1-008 GEN
Solar/Wind Harmer
15.715
970009AG2-005 GEN
Solar/Wind Harmer
1.575
3146173TUNIS
Solar/Wind Harmer
0.21
3156021HOLLOMANSOL
Solar/Wind Harmer
0.95
316463AE2-346 GEN
Solar/Wind Harmer
0.179
316140AB2-099
Solar/Wind Harmer
0.075
962331AG1-082 GEN
Solar/Wind Harmer
2.227
316404AE1-155 C
Solar/Wind Harmer
0.047
3146263WOODLND
Solar/Wind Harmer
0.207
313506AB2-031 GEN
Solar/Wind Harmer
0.638
3142666NORTHAMPTON
Solar/Wind Harmer
0.205
3145963POPLR C
Solar/Wind Harmer
0.204
316317KELFORD C
Solar/Wind Harmer
0.02
3145823KELFORD
Solar/Wind Harmer
0.204
316478AD1-087 GEN
Solar/Wind Harmer
0.708
316486AD2-202 GEN
Solar/Wind Harmer
0.208
3147043LAWRENC
Solar/Wind Harmer
0.122
3145796HORNRTN
Solar/Wind Harmer
0.807
3145796HORNRTN
Solar/Wind Harmer
0.202
3150351NORNECKC2
Adder
2.043
316210AC1-098 GEN
Solar/Wind Harmer
1.828
3145933PARMELE
Solar/Wind Harmer
0.196
966801AG1-551 GEN
Solar/Wind Harmer
2.283
970909AG2-566 GEN
Solar/Wind Harmer
2.083
971781AH1-399 GEN
Solar/Wind Harmer
0.256
3145746EVERETS
Solar/Wind Harmer
0.192
3145746EVERETS
Solar/Wind Harmer
0.192
315724AD1-057 GEN
Solar/Wind Harmer
0.72
316327AA2-057 GEN
Solar/Wind Harmer
0.287
316131AB2-060 GEN
Solar/Wind Harmer
0.595
964241AG1-285 GEN
Solar/Wind Harmer
12.61
315785AD2-033 C
Solar/Wind Harmer
1.535
970257AG2-171 GEN
Solar/Wind Harmer
6.039
959311AF2-222 GEN
Solar/Wind Harmer
16.767
963181AG1-167 GEN
Solar/Wind Harmer
0.752
3144293JTRSVLE
Adder
0.599
3147133PAMPLIN
Solar/Wind Harmer
0.59
971193AH1-056 GEN
Solar/Wind Harmer
11.443
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146233WITAKRS
Solar/Wind Harmer
0.938
3146233WITAKRS
Solar/Wind Harmer
0.127
3146926FARMVIL
Solar/Wind Harmer
0.112
3146073TAR RVR
Solar/Wind Harmer
0.186
3146083TARBORO
Solar/Wind Harmer
0.186
3138543CONSLDL
Solar/Wind Harmer
0.123
961601AG1-000A GEN
Solar/Wind Harmer
13.049
3145543BTLEBRO
Solar/Wind Harmer
0.183
3145543BTLEBRO
Solar/Wind Harmer
0.183
971623AH1-311 GEN
Solar/Wind Harmer
0.367
3141906WESTMOR
Solar/Wind Harmer
0.072
3146776BUCKING
Solar/Wind Harmer
0.064
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.36
970737AG2-469 GEN
Solar/Wind Harmer
7.314
971683AH1-343 GEN
Solar/Wind Harmer
5.86
3151761LOISA E
Adder
21.054
970221AG2-151 GEN
Solar/Wind Harmer
8.48
3132273ORANGE
Solar/Wind Harmer
0.031
316283AC2-100 C
Solar/Wind Harmer
0.304
972183AH1-676 GEN
Adder
164.313
972255AH1-712 GEN
Adder
74.545
316170AC1-121 GEN2
Solar/Wind Harmer
0.13
3141316ARNOLDS
Adder
0.285
3141196NOKESVL
Solar/Wind Helper
1.139
3152251N ANNA1
50/50
19.719
970119AG2-088 GEN
50/50
34.806
3150851SPRUNCC
50/50
1.197
3143096IRON208
50/50
1.062
3152331SURRY 2
50/50
9.829
3150771HOPHCF1
50/50
0.962
316045AC1-158 PL2
Solar/Wind Harmer
9.665
3147666LOUISA
Solar/Wind Harmer
1.067
3143226MDLTHAN
Solar/Wind Harmer
0.261
316192AB2-158 GEN
Solar/Wind Harmer
1.475
3143526WINTERP
Solar/Wind Harmer
1.319
940641AE2-051 GEN
Solar/Wind Harmer
19.587
939411AE1-173 GEN
Solar/Wind Harmer
103.486
3142543TWELFTH
Solar/Wind Harmer
0.023
316294AC1-161 GEN
Solar/Wind Harmer
4.14
315671AE2-027_GEN
Solar/Wind Harmer
15.248
970129AG2-093 GEN
Solar/Wind Harmer
6.738
316458AB2-190 GEN2
Solar/Wind Harmer
1.271
944591AF1-124 GEN
Solar/Wind Harmer
53.482
971069AG2-661 GEN
Solar/Wind Harmer
4.206
944631AF1-128 GEN
Adder
112.66
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
2.949
971647AH1-324 GEN
Solar/Wind Harmer
10.078
971133AH1-012 GEN
50/50
5.548
944641AF1-129 GEN
50/50
120.841
970533AG2-339 GEN
50/50
21.15
970531AG2-338 GEN
50/50
8.46
3142366NRTHEST
50/50
0.824
3150781HOPHCF2
50/50
0.962
3150791HOPHCF3
50/50
0.962
3150761HOPPOLC
50/50
0.61
971213AH1-066 GEN
50/50
0.844
3150691DARBY 3
50/50
18.094
3150701DARBY 4
50/50
18.052
316447AC1-158 HLD
Solar/Wind Harmer
6.644
971223AH1-071 GEN
Solar/Wind Harmer
2.784
3143526WINTERP
Solar/Wind Harmer
1.319
316240AF1-291 C
Solar/Wind Harmer
0.002
3150681DARBY 2
Adder
16.992
3150671DARBY 1
Adder
16.973
3142296MT RD221
Adder
0.753
316033AB2-134 GEN
Solar/Wind Harmer
0.014
315697AD1-025 GEN
Solar/Wind Harmer
0.266
316036AC1-147 C
Solar/Wind Harmer
0.044
3150991CHESPKB
Adder
2.474
3150991CHESPKB
Adder
2.414
316236AE1-162_GEN
Solar/Wind Harmer
0.002
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.226
316185AD1-033 GEN
Solar/Wind Harmer
0.007
970657AG2-426 GEN
Solar/Wind Harmer
8.254
970657AG2-426 GEN
Solar/Wind Harmer
1.73
3145506HICKORY
Solar/Wind Harmer
0.94
3145506HICKORY
Solar/Wind Harmer
0.564
3145506HICKORY
Solar/Wind Harmer
0.141
3142946ENON
Solar/Wind Harmer
0.023
316339AD2-160 GEN
Solar/Wind Harmer
0.38
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
316017AA1-139 ULT1
Solar/Wind Harmer
0.131
3137176SLIGO L2192
Solar/Wind Harmer
0.93
316075AC2-137 C
Solar/Wind Harmer
0.064
3146456SLIGO L269
Solar/Wind Harmer
4.136
3130086AYDLETT
Solar/Wind Harmer
0.933
972185AH1-677 GEN
Adder
13.007
3144356SAPONY
Solar/Wind Harmer
1.937
3146386ELIZ CT
Solar/Wind Harmer
0.231
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
972187AH1-678 GEN
Adder
6.523
3146516WINFALL
Solar/Wind Harmer
0.229
3146516WINFALL
Solar/Wind Harmer
0.229
3146516WINFALL
Solar/Wind Harmer
0.229
966871AG1-558 GEN
Solar/Wind Harmer
0.263
3146626S HERTFORD
Solar/Wind Harmer
0.227
3146626S HERTFORD
Solar/Wind Harmer
0.227
970933AG2-581 GEN
Solar/Wind Harmer
18.033
315742AE1-103 GEN
Solar/Wind Harmer
0.003
3146376EDENTON
Solar/Wind Harmer
0.99
3146376EDENTON
Solar/Wind Harmer
0.99
957411AF2-035 GEN
Solar/Wind Harmer
9.498
970317AG2-208 GEN
Solar/Wind Harmer
8.8
315673AE1-157 GEN
Solar/Wind Harmer
15.213
3150391LDYSMT3
Adder
28.839
972195AH1-682 GEN
Adder
3.79
316065AD1-022 GEN
Solar/Wind Harmer
9.8
3145893MURPHYS
Solar/Wind Harmer
1.417
3145893MURPHYS
Solar/Wind Harmer
0.381
970099AG2-077 GEN
Solar/Wind Harmer
22.503
3146173TUNIS
Solar/Wind Harmer
0.21
3146173TUNIS
Solar/Wind Harmer
0.21
958261AF2-120 GEN
Solar/Wind Harmer
6.863
316181AB2-040 GEN
Solar/Wind Harmer
0.299
3142666NORTHAMPTON
Solar/Wind Harmer
0.205
3142666NORTHAMPTON
Solar/Wind Harmer
0.205
3142666NORTHAMPTON
Solar/Wind Harmer
0.205
3142666NORTHAMPTON
Solar/Wind Harmer
0.123
316426AA2-053 GEN
Solar/Wind Harmer
0.69
3145593CAROLNA
Solar/Wind Harmer
0.203
3145593CAROLNA
Solar/Wind Harmer
0.203
966811AG1-552 GEN
Solar/Wind Harmer
2.207
3145593CAROLNA
Solar/Wind Harmer
0.253
3145783HORNRTN
Solar/Wind Harmer
3.596
3145783HORNRTN
Solar/Wind Harmer
2.876
3145783HORNRTN
Solar/Wind Harmer
0.899
3145783HORNRTN
Solar/Wind Harmer
0.36
3145796HORNRTN
Solar/Wind Harmer
0.606
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.11
3150341NORNECKC1
Adder
2.093
971741AH1-377 GEN
Solar/Wind Harmer
19.637
3145933PARMELE
Solar/Wind Harmer
0.392
3145933PARMELE
Solar/Wind Harmer
0.196
316274AC1-208 GEN
Solar/Wind Harmer
1.016
970301AG2-198 GEN
Solar/Wind Harmer
8.333
316468AD1-105 GEN
Solar/Wind Harmer
-0.063
939181AE1-148 GEN
Solar/Wind Harmer
9.137
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.014
970323AG2-213 GEN
Solar/Wind Harmer
8.051
971775AH1-396 GEN
Solar/Wind Harmer
0.302
958211AF2-115 GEN
Solar/Wind Harmer
2.257
963191AG1-168 GEN
Solar/Wind Harmer
0.752
3144293JTRSVLE
Adder
0.599
3144293JTRSVLE
Adder
0.504
3147133PAMPLIN
Solar/Wind Harmer
0.188
3147133PAMPLIN
Solar/Wind Harmer
0.15
3145493TOT1
Solar/Wind Harmer
0.432
3145453TOT5
Solar/Wind Harmer
0.259
3145603CNETO
Solar/Wind Harmer
0.173
961601AG1-000A GEN
Solar/Wind Harmer
3.262
316263AC1-034 GEN
Solar/Wind Harmer
6.97
962561AG1-105 GEN
Solar/Wind Harmer
8.691
964791AG1-342 GEN
Solar/Wind Harmer
3.448
3146843MT LREL
Solar/Wind Harmer
0.179
3146843MT LREL
Solar/Wind Harmer
0.179
3146776BUCKING
Solar/Wind Harmer
0.716
3146776BUCKING
Solar/Wind Harmer
0.058
3151731LOISA B
Adder
10.327
3151721LOISA A
Adder
10.274
971489AH1-241 GEN
Solar/Wind Harmer
8.48
316222AC1-221 GEN
Solar/Wind Harmer
0.648
966001AG1-469 GEN
Solar/Wind Harmer
0.09
315821AE2-092 GEN
Solar/Wind Harmer
0.008
942751AE2-291 GEN
Solar/Wind Harmer
7.158
316303AF2-085
50/50
4.641
971285AH1-108 GEN
50/50
1.959
970603AG2-384 GEN
50/50
5.097
316233AE1-074 FULL
Solar/Wind Harmer
0.203
971281AH1-106 GEN
Solar/Wind Harmer
3.521
971283AH1-107 GEN
Solar/Wind Harmer
3.521
3143316POE
Solar/Wind Harmer
0.947
941031AE2-094 GEN
Solar/Wind Harmer
43.824
944011AF1-069 GEN
Solar/Wind Harmer
14.319
316132AB2-190 GEN1
Solar/Wind Harmer
1.271
316369SG1_INVT
Solar/Wind Harmer
0.009
3151081ELIZAR1
Adder
21.661
3151091ELIZAR2
Adder
21.285
3152611GOSPORTB
Adder
3.008
3152621GOSPORTC
Adder
2.552
3152601GOSPORTA
Adder
2.355
971445AH1-216 GEN
Solar/Wind Harmer
16.611
972265AH1-717 GEN
Adder
18.304
3151201GRAVEL4
Adder
17.158
3151191GRAVEL3
Adder
16.941
3151211GRAVEL5
Adder
16.941
316312AB1-027
Solar/Wind Harmer
0.42
957871AF2-081 GEN
Solar/Wind Harmer
11.66
316164AC1-076 GEN
Solar/Wind Harmer
0.329
970673AG2-436 GEN
Solar/Wind Harmer
49.886
970673AG2-436 GEN
Solar/Wind Harmer
33.257
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.16
319010AE1-072 C
Solar/Wind Harmer
1.177
316311AC2-079 GEN
Solar/Wind Harmer
6.708
3146406KITTY HAWK
Solar/Wind Harmer
0.029
316305AF2-043 C
Solar/Wind Harmer
0.002
315976AC1-164 GENA
Solar/Wind Harmer
24.098
316169AC1-164_GENC
Solar/Wind Harmer
20.818
315975AC1-164 GENB
Solar/Wind Harmer
0.713
315835AF2-110_GEN
Solar/Wind Harmer
1.594
316315AB2-025 C
Solar/Wind Harmer
0.187
313526AB2-022
Solar/Wind Harmer
0.125
971967AH1-528 GEN
Solar/Wind Harmer
36.95
3146486SUNBURY
Solar/Wind Harmer
0.231
3146486SUNBURY
Solar/Wind Harmer
0.231
972189AH1-679 GEN
Adder
3.867
315814AE2-033 C
Solar/Wind Harmer
18.254
316321Z2-027
Solar/Wind Harmer
0.043
3146396TANGLEW
Solar/Wind Harmer
0.635
3145176PASQUOTANK
Solar/Wind Harmer
0.143
971167AH1-042 GEN
Solar/Wind Harmer
20.377
3142433PROV 92
Adder
0.445
3142433PROV 92
Adder
0.445
3138283WHITEMARSH
Solar/Wind Harmer
0.053
3143873LANEXA
Solar/Wind Harmer
0.135
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
316314AB2-024 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
6.628
316059AD1-063 C
Solar/Wind Harmer
0.001
315662AE1-191 GEN
Solar/Wind Harmer
0.007
315666AE1-190 GEN
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.223
3130156CHOWAN
Solar/Wind Harmer
0.223
3141873WAN 176
Solar/Wind Harmer
0.044
970085AG2-068 GEN
Solar/Wind Harmer
11.727
970581AG2-369 GEN
Solar/Wind Harmer
10.085
3141913WHIT STONE
Solar/Wind Harmer
0.219
3138133OCRAN
Solar/Wind Harmer
0.065
315816AE2-034 GEN
Solar/Wind Harmer
0.937
3141783LANCAST
Solar/Wind Harmer
0.13
3141783LANCAST
Solar/Wind Harmer
0.087
3150411LDYSMT5
Adder
28.983
3150381LDYSMT2
Adder
27.738
972213AH1-691 GEN
Adder
4.692
972215AH1-692 GEN
Adder
4.692
3130546PLYMOUTH
Solar/Wind Harmer
0.215
315732AD1-074 GEN1
Solar/Wind Harmer
1.23
315733AD1-074 GEN2
Solar/Wind Harmer
1.23
315735AD1-075 GEN1
Solar/Wind Harmer
0.616
965291AG1-394 GEN
Solar/Wind Harmer
0.949
962981AG1-147 GEN
Solar/Wind Harmer
7.952
3146206CASHIE
Solar/Wind Harmer
0.212
970601AG2-382 GEN
Solar/Wind Harmer
7.919
3145893MURPHYS
Solar/Wind Harmer
0.572
3145893MURPHYS
Solar/Wind Harmer
0.212
970327AG2-215 GEN
Solar/Wind Harmer
6.922
3145513AHOSKIE
Solar/Wind Harmer
0.437
3145513AHOSKIE
Solar/Wind Harmer
0.209
3146043SEABORD
Solar/Wind Harmer
0.208
3145683EARLEYS
Solar/Wind Harmer
0.416
3145683EARLEYS
Solar/Wind Harmer
0.208
3145683EARLEYS
Solar/Wind Harmer
0.208
315607AA1-063A GEN
Solar/Wind Harmer
0.424
316087AB2-174 GEN
Solar/Wind Harmer
0.006
315652AC1-086 GEN
Solar/Wind Harmer
22.553
3137643SOCKMAN
Solar/Wind Harmer
0.818
3145796HORNRTN
Solar/Wind Harmer
0.646
3145796HORNRTN
Solar/Wind Harmer
0.081
3141813NORNECK
Solar/Wind Harmer
0.201
3146033SCOT NK
Solar/Wind Harmer
0.8
970831AG2-522 GEN
Solar/Wind Harmer
8.358
316005AA1-067
Solar/Wind Harmer
0.206
3145746EVERETS
Solar/Wind Harmer
0.764
3145746EVERETS
Solar/Wind Harmer
0.192
3145746EVERETS
Solar/Wind Harmer
0.192
3145746EVERETS
Solar/Wind Harmer
0.192
970181AG2-120 GEN
Solar/Wind Harmer
2.391
957861AF2-080 GEN
Solar/Wind Harmer
8.156
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
3.171
3144303KENBRDG
Solar/Wind Harmer
0.151
970683AG2-441 GEN
Solar/Wind Harmer
12.561
970681AG2-440 GEN
Solar/Wind Harmer
10.049
946301AF1-294 GEN
Solar/Wind Harmer
3.712
961791AG1-021 GEN
Solar/Wind Harmer
1.806
315657AE1-056 GEN
Solar/Wind Harmer
6.482
316420AA1-050 GEN
Solar/Wind Harmer
0.006
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.186
3145573BETHELC
Solar/Wind Harmer
0.186
970285AG2-188 GEN
Solar/Wind Harmer
14.319
316223AC1-118
Solar/Wind Harmer
0.13
971845AH1-439 GEN
Solar/Wind Harmer
8.149
316118AC1-105 GEN
Solar/Wind Harmer
0.454
3147173SINAI
Solar/Wind Harmer
0.172
3147243WELCO
Solar/Wind Harmer
0.108
972205AH1-687 GEN
Adder
7.256
944491AF1-114 GEN
Solar/Wind Harmer
0.001
971447AH1-217 GEN
Solar/Wind Harmer
4.692
970865AG2-541 GEN
Solar/Wind Harmer
5.299
3147346CASHSCORNER
Solar/Wind Harmer
0.35
972193AH1-681 GEN
Adder
3.331
316123AC1-075 GEN
Solar/Wind Harmer
0.191
970165AG2-112 GEN
Solar/Wind Harmer
1.134
970163AG2-111 GEN
Solar/Wind Harmer
1.081
270494AE1-108_GEN
Solar/Wind Harmer
1.679
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316411AF1-147_GEN1
Solar/Wind Helper
0.804
316415AF1-147_GEN2
Solar/Wind Helper
0.804
3138216PACIFIC
Solar/Wind Helper
0.039
970659AG2-427 GEN
Solar/Wind Harmer
11.419
3145336SMITFLD
Solar/Wind Harmer
0.943
961611AG1-000B GEN
Solar/Wind Harmer
12.376
316381AD1-082 GEN
Solar/Wind Harmer
0.246
3151171GRAVELC
Adder
2.508
970661AG2-428 GEN
Solar/Wind Harmer
23.401
3142416OLDCHRC
Solar/Wind Harmer
0.61
3142416OLDCHRC
Solar/Wind Harmer
0.234
316388AE2-253 GEN
Solar/Wind Harmer
0.734
3138126ROCKLANDING
Solar/Wind Harmer
0.107
3146456SLIGO L269
Solar/Wind Harmer
0.234
316072AD1-144
Solar/Wind Harmer
0.085
316159AE1-175 C
Solar/Wind Harmer
0.201
316246AF1-032 C
Solar/Wind Harmer
0.105
971317AH1-138 GEN
Solar/Wind Harmer
1.735
316093AE2-104_GEN
Solar/Wind Harmer
3.906
3142433PROV 92
Solar/Wind Harmer
0.914
3142433PROV 92
Adder
0.445
3142433PROV 92
Adder
0.445
3146516WINFALL
Solar/Wind Harmer
0.741
3146516WINFALL
Solar/Wind Harmer
0.229
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.993
971777AH1-397 GEN
Solar/Wind Harmer
0.591
3141843SHACKLE
Adder
1.143
3141766HARMONY
Solar/Wind Harmer
0.045
3130156CHOWAN
Solar/Wind Harmer
0.223
966881AG1-559 GEN
Solar/Wind Harmer
0.257
970919AG2-571 GEN
Solar/Wind Harmer
7.85
970087AG2-069 GEN
Solar/Wind Harmer
17.59
3138133OCRAN
Solar/Wind Harmer
0.131
3145663CRESWEL
Solar/Wind Harmer
0.611
971163AH1-040 GEN
Solar/Wind Harmer
17.461
972197AH1-683 GEN
Adder
4.512
972219AH1-694 GEN
Adder
3.248
316336AC2-165 C
Solar/Wind Harmer
0.008
316023GEN1_S
Solar/Wind Harmer
0.481
3146206CASHIE
Solar/Wind Harmer
0.212
971547AH1-271 GEN
Solar/Wind Harmer
4.525
3145893MURPHYS
Solar/Wind Harmer
0.847
3145893MURPHYS
Solar/Wind Harmer
0.941
957481AF2-042 GEN
Solar/Wind Harmer
56.258
3146173TUNIS
Solar/Wind Harmer
0.21
960081AF2-299 GEN
Solar/Wind Harmer
2.005
962861AG1-135 GEN
Solar/Wind Harmer
6.67
3145683EARLEYS
Solar/Wind Harmer
0.208
315693AD1-088 GEN
Solar/Wind Harmer
9.93
3146263WOODLND
Solar/Wind Harmer
0.207
962491AG1-098 GEN
Solar/Wind Harmer
11.772
316011AB1-132 GEN
Solar/Wind Harmer
3.728
962571AG1-106 GEN
Solar/Wind Harmer
2.917
971795AH1-408 GEN
Solar/Wind Harmer
13.656
3145963POPLR C
Solar/Wind Harmer
0.204
3141726DUNNSVL
Solar/Wind Harmer
0.817
316190AA2-174 GEN
Solar/Wind Harmer
0
3145823KELFORD
Solar/Wind Harmer
0.204
3147043LAWRENC
Adder
1.836
316174AB2-169 GEN
Solar/Wind Harmer
0.005
3145783HORNRTN
Solar/Wind Harmer
0.202
3145796HORNRTN
Solar/Wind Harmer
0.666
3145796HORNRTN
Solar/Wind Harmer
0.202
3150351NORNECKC2
Adder
2.009
316212AC1-099_GEN
Solar/Wind Harmer
1.019
3146293MARTNCO
Solar/Wind Harmer
0.182
316129AC1-054 GEN
Solar/Wind Harmer
0.734
971065AG2-659 GEN
Solar/Wind Harmer
8.291
3145746EVERETS
Solar/Wind Harmer
0.192
3145746EVERETS
Solar/Wind Harmer
0.192
315722AD1-056 GEN
Solar/Wind Harmer
1.214
316337AD2-073 GEN
Solar/Wind Harmer
0.167
315687AD1-152 GEN
Solar/Wind Harmer
0.006
970937AG2-583 GEN
Solar/Wind Harmer
11.689
316494AC1-189 GEN
Solar/Wind Harmer
0.639
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970685AG2-442 GEN
Solar/Wind Harmer
14.068
963171AG1-166 GEN
Solar/Wind Harmer
1.003
971563AH1-280 GEN
Solar/Wind Harmer
2.007
3144293JTRSVLE
Adder
0.599
3146233WITAKRS
Solar/Wind Harmer
0.743
3146926FARMVIL
Solar/Wind Harmer
0.112
961671AG1-007 GEN
Solar/Wind Harmer
0.029
3146083TARBORO
Solar/Wind Harmer
0.186
3145493TOT1
Solar/Wind Harmer
0.829
3145543BTLEBRO
Solar/Wind Harmer
0.183
3145543BTLEBRO
Solar/Wind Harmer
0.147
316359AB2-059 GEN
Solar/Wind Harmer
0.659
316049AB1-081 GEN
Solar/Wind Harmer
1.05
3142053HEARTS
Solar/Wind Harmer
0.323
970401AG2-262 GEN
Solar/Wind Harmer
1.053
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.072
972003AH1-546 GEN
Solar/Wind Harmer
7.289
316003AC1-222 GEN
Solar/Wind Harmer
0.004
972135AH1-637 GEN
Solar/Wind Harmer
1.408
3151751LOISA D
Adder
10.327
971377AH1-170 GEN
Solar/Wind Harmer
1.696
3147623JAMES R
Solar/Wind Harmer
0.368
972277AH1-723 GEN
Adder
86.868
316254AC1-120 GEN1
Solar/Wind Harmer
0.26
NYPJM->LTFIMP_NY
CLTF
3.369
LGEELTFEXP_LGEE->PJM
CLTF
1.264
WECLTFEXP_WEC->PJM
CLTF
0.603
LAGNLTFEXP_LAGN->PJM
CLTF
8.056
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.878
TVALTFEXP_TVA->PJM
CLTF
4.082
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.76
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.813
MECLTFEXP_MEC->PJM
CLTF
3.485
SIGELTFEXP_SIGE->PJM
CLTF
0.106
CPLELTFEXP_CPLE->PJM
CLTF
11.88
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.966

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T552_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T552_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:154.28 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:6078.79
MW Contribution:88.61
Bus #Bus NameTypeMW Contribution
971531AH1-263 GEN
50/50
60.398
316303AF2-085
50/50
4.712
971285AH1-108 GEN
50/50
1.991
970603AG2-384 GEN
50/50
5.178
316164AC1-076 GEN
Solar/Wind Harmer
3.019
316233AE1-074 FULL
Solar/Wind Harmer
0.779
971281AH1-106 GEN
Solar/Wind Harmer
4.708
971283AH1-107 GEN
Solar/Wind Harmer
4.708
3143316POE
Solar/Wind Harmer
-0.107
941031AE2-094 GEN
Solar/Wind Harmer
50.888
944011AF1-069 GEN
Solar/Wind Harmer
15.945
316132AB2-190 GEN1
Solar/Wind Harmer
2.735
316369SG1_INVT
Solar/Wind Harmer
4.821
3151081ELIZAR1
Adder
22.001
3151091ELIZAR2
Adder
21.619
3152611GOSPORTB
Adder
3.055
3152621GOSPORTC
Adder
2.593
3152601GOSPORTA
Adder
2.392
971445AH1-216 GEN
Solar/Wind Harmer
16.663
972265AH1-717 GEN
Adder
18.594
3151201GRAVEL4
Adder
17.43
3151191GRAVEL3
Adder
17.21
3151211GRAVEL5
Adder
17.21
316312AB1-027
Solar/Wind Harmer
0.904
957871AF2-081 GEN
Solar/Wind Harmer
13.366
970673AG2-436 GEN
Solar/Wind Harmer
56.037
970673AG2-436 GEN
Solar/Wind Harmer
28.373
315833AF1-017_GEN
Solar/Wind Harmer
5.064
316349AD2-085 GEN
Solar/Wind Harmer
2.371
319010AE1-072 C
Solar/Wind Harmer
5.393
316311AC2-079 GEN
Solar/Wind Harmer
13.447
3146406KITTY HAWK
Solar/Wind Harmer
0.022
316305AF2-043 C
Solar/Wind Harmer
0.803
315976AC1-164 GENA
Solar/Wind Harmer
28.04
316169AC1-164_GENC
Solar/Wind Harmer
24.224
315975AC1-164 GENB
Solar/Wind Harmer
0.83
315835AF2-110_GEN
Solar/Wind Harmer
3.313
316315AB2-025 C
Solar/Wind Harmer
0.713
313526AB2-022
Solar/Wind Harmer
0.713
972189AH1-679 GEN
Adder
3.932
3146486SUNBURY
Solar/Wind Harmer
-0.026
3146486SUNBURY
Solar/Wind Harmer
-0.026
971967AH1-528 GEN
Solar/Wind Harmer
49.529
315814AE2-033 C
Solar/Wind Harmer
24.517
316321Z2-027
Solar/Wind Harmer
0.71
3146396TANGLEW
Solar/Wind Harmer
0.484
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
971167AH1-042 GEN
Solar/Wind Harmer
25.215
3142433PROV 92
Adder
0.452
3142433PROV 92
Adder
0.452
957831AF2-077 GEN
Solar/Wind Harmer
0.783
3138283WHITEMARSH
Solar/Wind Harmer
0.04
3143873LANEXA
Solar/Wind Harmer
-0.015
315611Z1-036_GEN2
Solar/Wind Harmer
6.355
316314AB2-024 C
Solar/Wind Harmer
2.187
316059AD1-063 C
Solar/Wind Harmer
0.576
315662AE1-191 GEN
Solar/Wind Harmer
3.069
315666AE1-190 GEN
Solar/Wind Harmer
0.767
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
957601AF2-054 GEN
Solar/Wind Harmer
0.759
3141873WAN 176
Solar/Wind Harmer
-0.005
970085AG2-068 GEN
Solar/Wind Harmer
15.677
970581AG2-369 GEN
Solar/Wind Harmer
13.482
3141913WHIT STONE
Solar/Wind Harmer
-0.025
3138133OCRAN
Solar/Wind Harmer
-0.007
315816AE2-034 GEN
Solar/Wind Harmer
2.016
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
3150411LDYSMT5
Adder
29.481
3150381LDYSMT2
Adder
28.214
972213AH1-691 GEN
Adder
4.773
972215AH1-692 GEN
Adder
4.773
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.942
315733AD1-074 GEN2
Solar/Wind Harmer
4.942
315735AD1-075 GEN1
Solar/Wind Harmer
2.472
965291AG1-394 GEN
Solar/Wind Harmer
2.164
962981AG1-147 GEN
Solar/Wind Harmer
10.637
3146206CASHIE
Solar/Wind Harmer
-0.024
970601AG2-382 GEN
Solar/Wind Harmer
10.591
316318V4-068
Solar/Wind Harmer
0.602
3145893MURPHYS
Solar/Wind Harmer
-0.065
3145893MURPHYS
Solar/Wind Harmer
-0.024
946281AF1-292 GEN
Solar/Wind Harmer
0.534
3145513AHOSKIE
Solar/Wind Harmer
0.208
961941AG1-037 GEN
Solar/Wind Harmer
0.179
3145513AHOSKIE
Solar/Wind Harmer
-0.024
3146043SEABORD
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.047
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
315607AA1-063A GEN
Solar/Wind Harmer
2.392
316087AB2-174 GEN
Solar/Wind Harmer
3.373
315652AC1-086 GEN
Solar/Wind Harmer
26.336
3137643SOCKMAN
Solar/Wind Harmer
-0.093
3145796HORNRTN
Solar/Wind Harmer
-0.073
3145796HORNRTN
Solar/Wind Harmer
-0.009
3141813NORNECK
Solar/Wind Harmer
-0.023
3146033SCOT NK
Solar/Wind Harmer
-0.091
972205AH1-687 GEN
Adder
7.416
972193AH1-681 GEN
Adder
3.397
316411AF1-147_GEN1
Solar/Wind Helper
0.82
316415AF1-147_GEN2
Solar/Wind Helper
0.82
3138216PACIFIC
Solar/Wind Helper
0.04
3152251N ANNA1
50/50
19.951
971507AH1-251 GEN
50/50
16.627
970119AG2-088 GEN
50/50
35.342
3150851SPRUNCC
50/50
1.216
3143096IRON208
50/50
1.079
3152331SURRY 2
50/50
9.986
3150771HOPHCF1
50/50
0.977
316045AC1-158 PL2
Solar/Wind Harmer
22.057
3147666LOUISA
Solar/Wind Harmer
-0.123
316192AB2-158 GEN
Solar/Wind Harmer
3.585
3143226MDLTHAN
Solar/Wind Harmer
-0.03
3143526WINTERP
Solar/Wind Harmer
-0.15
940641AE2-051 GEN
Solar/Wind Harmer
26.182
939411AE1-173 GEN
Solar/Wind Harmer
138.344
3142543TWELFTH
Solar/Wind Harmer
-0.003
316294AC1-161 GEN
Solar/Wind Harmer
8.821
315671AE2-027_GEN
Solar/Wind Harmer
20.395
970129AG2-093 GEN
Solar/Wind Harmer
6.167
316458AB2-190 GEN2
Solar/Wind Harmer
2.735
944591AF1-124 GEN
Solar/Wind Harmer
123.316
971069AG2-661 GEN
Solar/Wind Harmer
4.273
944631AF1-128 GEN
Adder
114.478
316375AC2-012 GEN
Solar/Wind Harmer
9.327
3150981CHESPKA
Adder
2.995
971647AH1-324 GEN
Solar/Wind Harmer
13.48
970659AG2-427 GEN
Solar/Wind Harmer
14.317
961611AG1-000B GEN
Solar/Wind Harmer
13.293
3145336SMITFLD
Solar/Wind Harmer
-0.107
316381AD1-082 GEN
Solar/Wind Harmer
2.469
3151171GRAVELC
Adder
2.547
970661AG2-428 GEN
Solar/Wind Harmer
28.527
3142416OLDCHRC
Solar/Wind Harmer
-0.069
3142416OLDCHRC
Solar/Wind Harmer
-0.027
316388AE2-253 GEN
Solar/Wind Harmer
1.804
3138126ROCKLANDING
Solar/Wind Harmer
0.082
3146456SLIGO L269
Solar/Wind Harmer
-0.027
316072AD1-144
Solar/Wind Harmer
0.54
316159AE1-175 C
Solar/Wind Harmer
0.715
316246AF1-032 C
Solar/Wind Harmer
0.539
971317AH1-138 GEN
Solar/Wind Harmer
3.316
316093AE2-104_GEN
Solar/Wind Harmer
7.706
3142433PROV 92
Solar/Wind Harmer
-0.104
3142433PROV 92
Adder
0.452
3142433PROV 92
Adder
0.452
3146516WINFALL
Solar/Wind Harmer
-0.084
3146516WINFALL
Solar/Wind Harmer
-0.026
315800Z1-036_GEN1
Solar/Wind Harmer
6.355
3143336POWHATN
Solar/Wind Harmer
3.047
971777AH1-397 GEN
Solar/Wind Harmer
3.003
3141843SHACKLE
Adder
1.161
3141766HARMONY
Solar/Wind Harmer
-0.005
3130156CHOWAN
Solar/Wind Harmer
-0.025
966881AG1-559 GEN
Solar/Wind Harmer
0.262
970919AG2-571 GEN
Solar/Wind Harmer
7.971
970087AG2-069 GEN
Solar/Wind Harmer
23.516
3138133OCRAN
Solar/Wind Harmer
-0.015
3145663CRESWEL
Solar/Wind Harmer
-0.069
971163AH1-040 GEN
Solar/Wind Harmer
23.353
972197AH1-683 GEN
Adder
4.589
972219AH1-694 GEN
Adder
3.304
316336AC2-165 C
Solar/Wind Harmer
4.275
316023GEN1_S
Solar/Wind Harmer
1.648
3146206CASHIE
Solar/Wind Harmer
-0.024
971547AH1-271 GEN
Solar/Wind Harmer
6.052
3145893MURPHYS
Solar/Wind Harmer
-0.096
3145893MURPHYS
Solar/Wind Harmer
0.717
957481AF2-042 GEN
Solar/Wind Harmer
75.252
961951AG1-038 GEN
Solar/Wind Harmer
3.171
3146173TUNIS
Solar/Wind Harmer
-0.024
960081AF2-299 GEN
Solar/Wind Harmer
2.682
962861AG1-135 GEN
Solar/Wind Harmer
8.922
3145683EARLEYS
Solar/Wind Harmer
-0.024
315693AD1-088 GEN
Solar/Wind Harmer
11.811
3146263WOODLND
Solar/Wind Harmer
-0.024
962491AG1-098 GEN
Solar/Wind Harmer
15.753
316011AB1-132 GEN
Solar/Wind Harmer
4.898
962571AG1-106 GEN
Solar/Wind Harmer
3.365
971795AH1-408 GEN
Solar/Wind Harmer
17.538
3145963POPLR C
Solar/Wind Harmer
-0.023
964211AG1-282 GEN
Solar/Wind Harmer
0.701
3141726DUNNSVL
Solar/Wind Harmer
-0.093
316190AA2-174 GEN
Solar/Wind Harmer
0.286
3145823KELFORD
Solar/Wind Harmer
-0.023
3147043LAWRENC
Adder
1.866
316174AB2-169 GEN
Solar/Wind Harmer
3.568
3145783HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.076
3145796HORNRTN
Solar/Wind Harmer
-0.023
3150351NORNECKC2
Adder
2.041
3144293JTRSVLE
Adder
0.609
3151751LOISA D
Adder
10.898
972277AH1-723 GEN
Adder
88.606
971133AH1-012 GEN
50/50
5.665
944641AF1-129 GEN
50/50
122.768
3142366NRTHEST
50/50
0.838
970533AG2-339 GEN
50/50
21.472
970531AG2-338 GEN
50/50
8.589
3150781HOPHCF2
50/50
0.977
3150791HOPHCF3
50/50
0.977
3150761HOPPOLC
50/50
0.62
971213AH1-066 GEN
50/50
0.857
3150691DARBY 3
50/50
18.39
316447AC1-158 HLD
Solar/Wind Harmer
15.163
971223AH1-071 GEN
Solar/Wind Harmer
3.723
3143526WINTERP
Solar/Wind Harmer
-0.15
316240AF1-291 C
Solar/Wind Harmer
0.822
3150701DARBY 4
Adder
17.29
3150681DARBY 2
Adder
17.27
3150671DARBY 1
Adder
17.25
3142296MT RD221
Adder
0.765
316033AB2-134 GEN
Solar/Wind Harmer
8.703
315697AD1-025 GEN
Solar/Wind Harmer
5.458
316036AC1-147 C
Solar/Wind Harmer
0.727
3150991CHESPKB
Adder
2.513
3150991CHESPKB
Adder
2.452
316236AE1-162_GEN
Solar/Wind Harmer
0.812
3142956BIRDNECK
Solar/Wind Harmer
1.444
316316AC1-027 C
Solar/Wind Harmer
0.826
316185AD1-033 GEN
Solar/Wind Harmer
2.837
970657AG2-426 GEN
Solar/Wind Harmer
8.405
970657AG2-426 GEN
Solar/Wind Harmer
1.758
3142946ENON
Solar/Wind Harmer
-0.003
3145506HICKORY
Solar/Wind Harmer
-0.107
3145506HICKORY
Solar/Wind Harmer
-0.064
3145506HICKORY
Solar/Wind Harmer
-0.016
316339AD2-160 GEN
Solar/Wind Harmer
1.804
316018AA1-139 ULT2
Solar/Wind Harmer
2.29
316017AA1-139 ULT1
Solar/Wind Harmer
2.163
316075AC2-137 C
Solar/Wind Harmer
0.72
3137176SLIGO L2192
Solar/Wind Harmer
-0.106
3146456SLIGO L269
Solar/Wind Harmer
3.151
3130086AYDLETT
Solar/Wind Harmer
-0.106
972185AH1-677 GEN
Adder
13.205
3144356SAPONY
Solar/Wind Harmer
0.922
3146386ELIZ CT
Solar/Wind Harmer
-0.026
316431W1029_GEN1
Solar/Wind Harmer
4.74
316433W1029_GEN2
Solar/Wind Harmer
4.74
972187AH1-678 GEN
Adder
6.623
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
966871AG1-558 GEN
Solar/Wind Harmer
0.781
966871AG1-558 GEN
Solar/Wind Harmer
0.267
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
970933AG2-581 GEN
Solar/Wind Harmer
24.111
315742AE1-103 GEN
Solar/Wind Harmer
2.675
316441AF1-014 GEN
Solar/Wind Harmer
1.721
957411AF2-035 GEN
Solar/Wind Harmer
11.447
970317AG2-208 GEN
Solar/Wind Harmer
11.129
3146376EDENTON
Solar/Wind Harmer
0.755
3146376EDENTON
Solar/Wind Harmer
0.755
315673AE1-157 GEN
Solar/Wind Harmer
18.853
3150391LDYSMT3
Adder
29.334
972195AH1-682 GEN
Adder
3.855
316065AD1-022 GEN
Solar/Wind Harmer
12.145
3145893MURPHYS
Solar/Wind Harmer
0.674
3145893MURPHYS
Solar/Wind Harmer
-0.043
970099AG2-077 GEN
Solar/Wind Harmer
30.101
316487AF1-042 GEN
Solar/Wind Harmer
3.171
3146173TUNIS
Solar/Wind Harmer
-0.024
3146173TUNIS
Solar/Wind Harmer
-0.024
958261AF2-120 GEN
Solar/Wind Harmer
9.18
316181AB2-040 GEN
Solar/Wind Harmer
3.285
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
316426AA2-053 GEN
Solar/Wind Harmer
2.355
3145593CAROLNA
Solar/Wind Harmer
-0.023
3145593CAROLNA
Solar/Wind Harmer
-0.023
966811AG1-552 GEN
Solar/Wind Harmer
2.613
3145593CAROLNA
Solar/Wind Harmer
0.193
3145783HORNRTN
Solar/Wind Harmer
2.74
3145783HORNRTN
Solar/Wind Harmer
2.192
3145783HORNRTN
Solar/Wind Harmer
0.685
3145783HORNRTN
Solar/Wind Harmer
0.274
3145796HORNRTN
Solar/Wind Harmer
-0.069
316077AC2-138 C
Solar/Wind Harmer
0.485
3150341NORNECKC1
Adder
2.144
3150341NORNECKC1
Adder
2.127
3144293JTRSVLE
Adder
0.609
3144293JTRSVLE
Adder
0.513
3151731LOISA B
Adder
10.898
3151721LOISA A
Adder
10.842
971741AH1-377 GEN
Solar/Wind Harmer
1.355
3152261N ANNA2
50/50
19.95
3150861SPRUNCD
50/50
1.216
3143096IRON208
50/50
1.079
3143096IRON208
50/50
1.057
3150801HOPHCF4
50/50
1.421
971211AH1-065 GEN
50/50
1.714
3151161SURRY 1
50/50
9.199
316044AC1-158 PL1
Solar/Wind Harmer
6.895
316450AC1-158 RIC
Solar/Wind Harmer
1.839
3147666LOUISA
Solar/Wind Harmer
-0.07
315839AE2-212 C
Solar/Wind Harmer
0.822
315773AC2-141 GEN
Solar/Wind Harmer
11.408
965281AG1-393 GEN
Solar/Wind Harmer
3.401
970133AG2-095 GEN
Solar/Wind Harmer
3.047
315813AE1-149 C
Solar/Wind Harmer
16.929
970129AG2-093 GEN
Solar/Wind Harmer
15.225
944581AF1-123 GEN
Solar/Wind Harmer
122.873
944601AF1-125 GEN
Solar/Wind Harmer
120.955
315778AD1-151 GEN
Solar/Wind Harmer
23.395
3151101ELIZAR3
Adder
22.283
3144536CHRHLND
Solar/Wind Harmer
-0.004
3144873MCLAUGH
Solar/Wind Harmer
-0.001
970659AG2-427 GEN
Solar/Wind Harmer
2.537
961611AG1-000B GEN
Solar/Wind Harmer
5.672
3145336SMITFLD
Solar/Wind Harmer
-0.011
316083AB2-161 GEN
Solar/Wind Harmer
4.37
3151221GRAVEL6
Adder
17.41
3151171GRAVELC
Adder
3.35
970293AG2-193 GEN
Solar/Wind Harmer
3.361
3142946ENON
Solar/Wind Harmer
-0.009
970661AG2-428 GEN
Solar/Wind Harmer
5.055
3142416OLDCHRC
Solar/Wind Harmer
2.704
3144216WINCHST
Adder
0.896
3146456SLIGO L269
Solar/Wind Harmer
-0.027
971153AH1-033 GEN
Solar/Wind Harmer
3.252
3150921YORKTN3
Adder
5.966
316382AG1-145 C
Solar/Wind Harmer
0.803
316320Y1-086
Solar/Wind Harmer
1.548
316435W1029_GEN3
Solar/Wind Harmer
4.74
3142433PROV 92
Adder
0.452
3142433PROV 92
Adder
0.452
3146516WINFALL
Solar/Wind Harmer
-0.026
316473AC1-191 GEN
Solar/Wind Harmer
2.794
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3145273HOLLAND
Solar/Wind Harmer
-0.019
316313AB2-026
Solar/Wind Harmer
0.692
316258AE1-075 C
Solar/Wind Harmer
0.623
316405AF2-144 C
Solar/Wind Harmer
0.658
3143336POWHATN
Solar/Wind Harmer
2.59
3141843SHACKLE
Adder
1.161
316203AE2-005 GEN
Solar/Wind Harmer
10.766
3141766HARMONY
Solar/Wind Harmer
2.27
316280AD1-041 GEN
Solar/Wind Harmer
1.918
966881AG1-559 GEN
Solar/Wind Harmer
0.765
3146376EDENTON
Solar/Wind Harmer
-0.025
316156AD2-030 GEN
Solar/Wind Harmer
0.677
3141873WAN 176
Solar/Wind Harmer
3.01
970917AG2-570 GEN
Solar/Wind Harmer
62.97
315614AA2-178 GEN
Solar/Wind Harmer
2.688
3150401LDYSMT4
Adder
29.389
3150371LDYSMT1
Adder
28.398
971157AH1-035 GEN
Solar/Wind Harmer
3.064
3156081AA2-088 GEN
Solar/Wind Harmer
7.946
316365GEN2_N
Solar/Wind Harmer
1.648
315737AD1-076 GEN
Solar/Wind Harmer
4.644
962971AG1-146 GEN
Solar/Wind Harmer
4.559
3146206CASHIE
Solar/Wind Harmer
-0.024
3145893MURPHYS
Solar/Wind Harmer
0.169
3145893MURPHYS
Solar/Wind Harmer
-0.024
957521AF2-046 GEN
Solar/Wind Harmer
18.984
961681AG1-008 GEN
Solar/Wind Harmer
18.984
316484AD2-074 GEN
Solar/Wind Harmer
6.061
970009AG2-005 GEN
Solar/Wind Harmer
3.009
3146173TUNIS
Solar/Wind Harmer
-0.024
3156021HOLLOMANSOL
Solar/Wind Harmer
3.218
966621AG1-532 GEN
Solar/Wind Harmer
0.484
316463AE2-346 GEN
Solar/Wind Harmer
0.386
316140AB2-099
Solar/Wind Harmer
0.161
962331AG1-082 GEN
Solar/Wind Harmer
2.979
316404AE1-155 C
Solar/Wind Harmer
4.57
3146263WOODLND
Solar/Wind Harmer
-0.024
313506AB2-031 GEN
Solar/Wind Harmer
1.893
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.023
316317KELFORD C
Solar/Wind Harmer
1.098
3145823KELFORD
Solar/Wind Harmer
-0.023
316478AD1-087 GEN
Solar/Wind Harmer
2.006
316486AD2-202 GEN
Solar/Wind Harmer
0.588
3147043LAWRENC
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.092
3145796HORNRTN
Solar/Wind Harmer
-0.023
3150351NORNECKC2
Adder
2.075
3144293JTRSVLE
Adder
0.609
3151761LOISA E
Adder
22.218
972183AH1-676 GEN
Adder
173.787
972255AH1-712 GEN
Adder
76.037
3141316ARNOLDS
Adder
0.289
3141196NOKESVL
Solar/Wind Helper
1.164
NYPJM->LTFIMP_NY
CLTF
3.433
LGEELTFEXP_LGEE->PJM
CLTF
1.291
WECLTFEXP_WEC->PJM
CLTF
0.616
LAGNLTFEXP_LAGN->PJM
CLTF
8.202
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.311
TVALTFEXP_TVA->PJM
CLTF
4.157
CBM West 1LTFEXP_CBM-W1->PJM
CBM
20.192
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.068
MECLTFEXP_MEC->PJM
CLTF
3.555
SIGELTFEXP_SIGE->PJM
CLTF
0.108
CPLELTFEXP_CPLE->PJM
CLTF
12.074
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.739

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H3T552_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H3T552_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:154.01 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:6067.89
MW Contribution:88.53
Bus #Bus NameTypeMW Contribution
971531AH1-263 GEN
50/50
60.354
316303AF2-085
50/50
4.709
971285AH1-108 GEN
50/50
1.989
970603AG2-384 GEN
50/50
5.174
316164AC1-076 GEN
Solar/Wind Harmer
3.016
316233AE1-074 FULL
Solar/Wind Harmer
0.779
971281AH1-106 GEN
Solar/Wind Harmer
4.705
971283AH1-107 GEN
Solar/Wind Harmer
4.705
3143316POE
Solar/Wind Harmer
-0.107
941031AE2-094 GEN
Solar/Wind Harmer
50.85
944011AF1-069 GEN
Solar/Wind Harmer
15.933
316132AB2-190 GEN1
Solar/Wind Harmer
2.733
316369SG1_INVT
Solar/Wind Harmer
4.818
3151081ELIZAR1
Adder
21.985
3151091ELIZAR2
Adder
21.603
3152611GOSPORTB
Adder
3.052
3152621GOSPORTC
Adder
2.591
3152601GOSPORTA
Adder
2.39
971445AH1-216 GEN
Solar/Wind Harmer
16.65
972265AH1-717 GEN
Adder
18.58
3151201GRAVEL4
Adder
17.417
3151191GRAVEL3
Adder
17.197
3151211GRAVEL5
Adder
17.197
316312AB1-027
Solar/Wind Harmer
0.903
957871AF2-081 GEN
Solar/Wind Harmer
13.355
970673AG2-436 GEN
Solar/Wind Harmer
55.995
970673AG2-436 GEN
Solar/Wind Harmer
28.352
315833AF1-017_GEN
Solar/Wind Harmer
5.061
316349AD2-085 GEN
Solar/Wind Harmer
2.37
319010AE1-072 C
Solar/Wind Harmer
5.389
316311AC2-079 GEN
Solar/Wind Harmer
13.437
3146406KITTY HAWK
Solar/Wind Harmer
0.022
316305AF2-043 C
Solar/Wind Harmer
0.802
315976AC1-164 GENA
Solar/Wind Harmer
28.019
316169AC1-164_GENC
Solar/Wind Harmer
24.206
315975AC1-164 GENB
Solar/Wind Harmer
0.829
315835AF2-110_GEN
Solar/Wind Harmer
3.311
316315AB2-025 C
Solar/Wind Harmer
0.712
313526AB2-022
Solar/Wind Harmer
0.712
972189AH1-679 GEN
Adder
3.929
3146486SUNBURY
Solar/Wind Harmer
-0.026
3146486SUNBURY
Solar/Wind Harmer
-0.026
971967AH1-528 GEN
Solar/Wind Harmer
49.492
315814AE2-033 C
Solar/Wind Harmer
24.499
316321Z2-027
Solar/Wind Harmer
0.709
3146396TANGLEW
Solar/Wind Harmer
0.484
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
971167AH1-042 GEN
Solar/Wind Harmer
25.196
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
957831AF2-077 GEN
Solar/Wind Harmer
0.782
3138283WHITEMARSH
Solar/Wind Harmer
0.04
3152251N ANNA1
50/50
19.938
971507AH1-251 GEN
50/50
16.616
970119AG2-088 GEN
50/50
35.315
3150851SPRUNCC
50/50
1.216
3143096IRON208
50/50
1.078
3152331SURRY 2
50/50
9.978
3150771HOPHCF1
50/50
0.977
316045AC1-158 PL2
Solar/Wind Harmer
22.043
3147666LOUISA
Solar/Wind Harmer
-0.123
316192AB2-158 GEN
Solar/Wind Harmer
3.583
3143226MDLTHAN
Solar/Wind Harmer
-0.03
3143526WINTERP
Solar/Wind Harmer
-0.15
940641AE2-051 GEN
Solar/Wind Harmer
26.162
939411AE1-173 GEN
Solar/Wind Harmer
138.24
3142543TWELFTH
Solar/Wind Harmer
-0.003
316294AC1-161 GEN
Solar/Wind Harmer
8.814
315671AE2-027_GEN
Solar/Wind Harmer
20.38
970129AG2-093 GEN
Solar/Wind Harmer
6.163
316458AB2-190 GEN2
Solar/Wind Harmer
2.733
944591AF1-124 GEN
Solar/Wind Harmer
123.223
971069AG2-661 GEN
Solar/Wind Harmer
4.27
944631AF1-128 GEN
Adder
114.392
316375AC2-012 GEN
Solar/Wind Harmer
9.32
3150981CHESPKA
Adder
2.993
971647AH1-324 GEN
Solar/Wind Harmer
13.47
970659AG2-427 GEN
Solar/Wind Harmer
14.306
961611AG1-000B GEN
Solar/Wind Harmer
13.283
3145336SMITFLD
Solar/Wind Harmer
-0.107
316381AD1-082 GEN
Solar/Wind Harmer
2.467
3143873LANEXA
Solar/Wind Harmer
-0.015
315611Z1-036_GEN2
Solar/Wind Harmer
6.351
316314AB2-024 C
Solar/Wind Harmer
2.185
316059AD1-063 C
Solar/Wind Harmer
0.576
315662AE1-191 GEN
Solar/Wind Harmer
3.067
315666AE1-190 GEN
Solar/Wind Harmer
0.767
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
957601AF2-054 GEN
Solar/Wind Harmer
0.758
3141873WAN 176
Solar/Wind Harmer
-0.005
970085AG2-068 GEN
Solar/Wind Harmer
15.665
970581AG2-369 GEN
Solar/Wind Harmer
13.472
3141913WHIT STONE
Solar/Wind Harmer
-0.025
3138133OCRAN
Solar/Wind Harmer
-0.007
315816AE2-034 GEN
Solar/Wind Harmer
2.014
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
3150411LDYSMT5
Adder
29.459
3150381LDYSMT2
Adder
28.193
972213AH1-691 GEN
Adder
4.769
972215AH1-692 GEN
Adder
4.769
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.938
315733AD1-074 GEN2
Solar/Wind Harmer
4.938
315735AD1-075 GEN1
Solar/Wind Harmer
2.47
965291AG1-394 GEN
Solar/Wind Harmer
2.162
962981AG1-147 GEN
Solar/Wind Harmer
10.629
3146206CASHIE
Solar/Wind Harmer
-0.024
970601AG2-382 GEN
Solar/Wind Harmer
10.583
316318V4-068
Solar/Wind Harmer
0.602
3145893MURPHYS
Solar/Wind Harmer
-0.065
3145893MURPHYS
Solar/Wind Harmer
-0.024
946281AF1-292 GEN
Solar/Wind Harmer
0.534
3145513AHOSKIE
Solar/Wind Harmer
0.208
961941AG1-037 GEN
Solar/Wind Harmer
0.179
3145513AHOSKIE
Solar/Wind Harmer
-0.024
3146043SEABORD
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.047
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
315607AA1-063A GEN
Solar/Wind Harmer
2.391
316087AB2-174 GEN
Solar/Wind Harmer
3.37
315652AC1-086 GEN
Solar/Wind Harmer
26.316
3137643SOCKMAN
Solar/Wind Harmer
-0.093
3145796HORNRTN
Solar/Wind Harmer
-0.073
3145796HORNRTN
Solar/Wind Harmer
-0.009
3141813NORNECK
Solar/Wind Harmer
-0.023
3146033SCOT NK
Solar/Wind Harmer
-0.091
972205AH1-687 GEN
Adder
7.409
972193AH1-681 GEN
Adder
3.394
316411AF1-147_GEN1
Solar/Wind Helper
0.818
316415AF1-147_GEN2
Solar/Wind Helper
0.818
3138216PACIFIC
Solar/Wind Helper
0.04
971133AH1-012 GEN
50/50
5.661
944641AF1-129 GEN
50/50
122.675
3142366NRTHEST
50/50
0.837
970533AG2-339 GEN
50/50
21.455
970531AG2-338 GEN
50/50
8.582
3150781HOPHCF2
50/50
0.977
3150791HOPHCF3
50/50
0.977
3150761HOPPOLC
50/50
0.619
971213AH1-066 GEN
50/50
0.857
3150691DARBY 3
50/50
18.376
316447AC1-158 HLD
Solar/Wind Harmer
15.154
971223AH1-071 GEN
Solar/Wind Harmer
3.72
3143526WINTERP
Solar/Wind Harmer
-0.15
316240AF1-291 C
Solar/Wind Harmer
0.821
3150701DARBY 4
Adder
17.277
3150681DARBY 2
Adder
17.257
3150671DARBY 1
Adder
17.237
3142296MT RD221
Adder
0.765
316033AB2-134 GEN
Solar/Wind Harmer
8.696
315697AD1-025 GEN
Solar/Wind Harmer
5.454
316036AC1-147 C
Solar/Wind Harmer
0.727
3150991CHESPKB
Adder
2.511
3150991CHESPKB
Adder
2.451
316236AE1-162_GEN
Solar/Wind Harmer
0.811
3142956BIRDNECK
Solar/Wind Harmer
1.443
316316AC1-027 C
Solar/Wind Harmer
0.826
316185AD1-033 GEN
Solar/Wind Harmer
2.835
970657AG2-426 GEN
Solar/Wind Harmer
8.398
970657AG2-426 GEN
Solar/Wind Harmer
1.756
3142946ENON
Solar/Wind Harmer
-0.003
3145506HICKORY
Solar/Wind Harmer
-0.107
3145506HICKORY
Solar/Wind Harmer
-0.064
3145506HICKORY
Solar/Wind Harmer
-0.016
316339AD2-160 GEN
Solar/Wind Harmer
1.803
316018AA1-139 ULT2
Solar/Wind Harmer
2.288
316017AA1-139 ULT1
Solar/Wind Harmer
2.161
316075AC2-137 C
Solar/Wind Harmer
0.72
3137176SLIGO L2192
Solar/Wind Harmer
-0.105
3146456SLIGO L269
Solar/Wind Harmer
3.148
3130086AYDLETT
Solar/Wind Harmer
-0.106
972185AH1-677 GEN
Adder
13.195
3144356SAPONY
Solar/Wind Harmer
0.921
3146386ELIZ CT
Solar/Wind Harmer
-0.026
316431W1029_GEN1
Solar/Wind Harmer
4.736
316433W1029_GEN2
Solar/Wind Harmer
4.736
972187AH1-678 GEN
Adder
6.618
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
966871AG1-558 GEN
Solar/Wind Harmer
0.78
966871AG1-558 GEN
Solar/Wind Harmer
0.267
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
970933AG2-581 GEN
Solar/Wind Harmer
24.093
315742AE1-103 GEN
Solar/Wind Harmer
2.673
316441AF1-014 GEN
Solar/Wind Harmer
1.72
957411AF2-035 GEN
Solar/Wind Harmer
11.438
970317AG2-208 GEN
Solar/Wind Harmer
11.12
3146376EDENTON
Solar/Wind Harmer
0.754
3146376EDENTON
Solar/Wind Harmer
0.754
315673AE1-157 GEN
Solar/Wind Harmer
18.839
3150391LDYSMT3
Adder
29.312
972195AH1-682 GEN
Adder
3.852
316065AD1-022 GEN
Solar/Wind Harmer
12.136
3145893MURPHYS
Solar/Wind Harmer
0.674
3145893MURPHYS
Solar/Wind Harmer
-0.043
970099AG2-077 GEN
Solar/Wind Harmer
30.078
316487AF1-042 GEN
Solar/Wind Harmer
3.169
3146173TUNIS
Solar/Wind Harmer
-0.024
3146173TUNIS
Solar/Wind Harmer
-0.024
958261AF2-120 GEN
Solar/Wind Harmer
9.173
316181AB2-040 GEN
Solar/Wind Harmer
3.283
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
316426AA2-053 GEN
Solar/Wind Harmer
2.354
3145593CAROLNA
Solar/Wind Harmer
-0.023
3145593CAROLNA
Solar/Wind Harmer
-0.023
966811AG1-552 GEN
Solar/Wind Harmer
2.611
3145593CAROLNA
Solar/Wind Harmer
0.193
3145783HORNRTN
Solar/Wind Harmer
2.737
3145783HORNRTN
Solar/Wind Harmer
2.19
3145783HORNRTN
Solar/Wind Harmer
0.684
3145783HORNRTN
Solar/Wind Harmer
0.274
3145796HORNRTN
Solar/Wind Harmer
-0.069
316077AC2-138 C
Solar/Wind Harmer
0.485
3150341NORNECKC1
Adder
2.142
3150341NORNECKC1
Adder
2.125
3144293JTRSVLE
Adder
0.609
3144293JTRSVLE
Adder
0.513
3151731LOISA B
Adder
10.888
3151721LOISA A
Adder
10.832
971741AH1-377 GEN
Solar/Wind Harmer
1.353
3151171GRAVELC
Adder
2.545
970661AG2-428 GEN
Solar/Wind Harmer
28.505
3142416OLDCHRC
Solar/Wind Harmer
-0.069
3142416OLDCHRC
Solar/Wind Harmer
-0.026
316388AE2-253 GEN
Solar/Wind Harmer
1.803
3138126ROCKLANDING
Solar/Wind Harmer
0.082
3146456SLIGO L269
Solar/Wind Harmer
-0.027
316072AD1-144
Solar/Wind Harmer
0.539
316159AE1-175 C
Solar/Wind Harmer
0.714
316246AF1-032 C
Solar/Wind Harmer
0.538
971317AH1-138 GEN
Solar/Wind Harmer
3.313
316093AE2-104_GEN
Solar/Wind Harmer
7.7
3142433PROV 92
Solar/Wind Harmer
-0.104
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
3146516WINFALL
Solar/Wind Harmer
-0.084
3146516WINFALL
Solar/Wind Harmer
-0.026
315800Z1-036_GEN1
Solar/Wind Harmer
6.351
3143336POWHATN
Solar/Wind Harmer
3.045
971777AH1-397 GEN
Solar/Wind Harmer
3
3141843SHACKLE
Adder
1.16
3141766HARMONY
Solar/Wind Harmer
-0.005
3130156CHOWAN
Solar/Wind Harmer
-0.025
966881AG1-559 GEN
Solar/Wind Harmer
0.261
970919AG2-571 GEN
Solar/Wind Harmer
7.965
970087AG2-069 GEN
Solar/Wind Harmer
23.498
3138133OCRAN
Solar/Wind Harmer
-0.015
3145663CRESWEL
Solar/Wind Harmer
-0.069
971163AH1-040 GEN
Solar/Wind Harmer
23.335
972197AH1-683 GEN
Adder
4.586
972219AH1-694 GEN
Adder
3.302
316336AC2-165 C
Solar/Wind Harmer
4.272
316023GEN1_S
Solar/Wind Harmer
1.647
3146206CASHIE
Solar/Wind Harmer
-0.024
971547AH1-271 GEN
Solar/Wind Harmer
6.047
3145893MURPHYS
Solar/Wind Harmer
-0.096
3145893MURPHYS
Solar/Wind Harmer
0.717
957481AF2-042 GEN
Solar/Wind Harmer
75.195
961951AG1-038 GEN
Solar/Wind Harmer
3.169
3146173TUNIS
Solar/Wind Harmer
-0.024
960081AF2-299 GEN
Solar/Wind Harmer
2.68
962861AG1-135 GEN
Solar/Wind Harmer
8.916
3145683EARLEYS
Solar/Wind Harmer
-0.024
315693AD1-088 GEN
Solar/Wind Harmer
11.802
3146263WOODLND
Solar/Wind Harmer
-0.023
962491AG1-098 GEN
Solar/Wind Harmer
15.74
316011AB1-132 GEN
Solar/Wind Harmer
4.894
962571AG1-106 GEN
Solar/Wind Harmer
3.363
971795AH1-408 GEN
Solar/Wind Harmer
17.524
3145963POPLR C
Solar/Wind Harmer
-0.023
964211AG1-282 GEN
Solar/Wind Harmer
0.701
3141726DUNNSVL
Solar/Wind Harmer
-0.093
316190AA2-174 GEN
Solar/Wind Harmer
0.286
3145823KELFORD
Solar/Wind Harmer
-0.023
3147043LAWRENC
Adder
1.864
316174AB2-169 GEN
Solar/Wind Harmer
3.565
3145783HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.076
3145796HORNRTN
Solar/Wind Harmer
-0.023
3150351NORNECKC2
Adder
2.039
3144293JTRSVLE
Adder
0.609
3151751LOISA D
Adder
10.888
972277AH1-723 GEN
Adder
88.526
3152261N ANNA2
50/50
19.936
3150861SPRUNCD
50/50
1.216
3143096IRON208
50/50
1.078
3143096IRON208
50/50
1.057
3150801HOPHCF4
50/50
1.42
971211AH1-065 GEN
50/50
1.713
3151161SURRY 1
50/50
9.192
316044AC1-158 PL1
Solar/Wind Harmer
6.891
316450AC1-158 RIC
Solar/Wind Harmer
1.837
3147666LOUISA
Solar/Wind Harmer
-0.07
315839AE2-212 C
Solar/Wind Harmer
0.822
315773AC2-141 GEN
Solar/Wind Harmer
11.4
965281AG1-393 GEN
Solar/Wind Harmer
3.399
970133AG2-095 GEN
Solar/Wind Harmer
3.045
315813AE1-149 C
Solar/Wind Harmer
16.916
970129AG2-093 GEN
Solar/Wind Harmer
15.214
944581AF1-123 GEN
Solar/Wind Harmer
122.781
944601AF1-125 GEN
Solar/Wind Harmer
120.864
315778AD1-151 GEN
Solar/Wind Harmer
23.378
3151101ELIZAR3
Adder
22.266
3144536CHRHLND
Solar/Wind Harmer
-0.004
3144873MCLAUGH
Solar/Wind Harmer
-0.001
970659AG2-427 GEN
Solar/Wind Harmer
2.535
961611AG1-000B GEN
Solar/Wind Harmer
5.668
3145336SMITFLD
Solar/Wind Harmer
-0.011
316083AB2-161 GEN
Solar/Wind Harmer
4.366
3151221GRAVEL6
Adder
17.397
3151171GRAVELC
Adder
3.347
970293AG2-193 GEN
Solar/Wind Harmer
3.359
3142946ENON
Solar/Wind Harmer
-0.009
970661AG2-428 GEN
Solar/Wind Harmer
5.052
3142416OLDCHRC
Solar/Wind Harmer
2.702
3144216WINCHST
Adder
0.896
3146456SLIGO L269
Solar/Wind Harmer
-0.027
971153AH1-033 GEN
Solar/Wind Harmer
3.25
3150921YORKTN3
Adder
5.961
316382AG1-145 C
Solar/Wind Harmer
0.802
316320Y1-086
Solar/Wind Harmer
1.547
316435W1029_GEN3
Solar/Wind Harmer
4.736
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
3146516WINFALL
Solar/Wind Harmer
-0.026
316473AC1-191 GEN
Solar/Wind Harmer
2.792
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3145273HOLLAND
Solar/Wind Harmer
-0.019
316313AB2-026
Solar/Wind Harmer
0.692
316258AE1-075 C
Solar/Wind Harmer
0.623
316405AF2-144 C
Solar/Wind Harmer
0.657
3143336POWHATN
Solar/Wind Harmer
2.588
3141843SHACKLE
Adder
1.16
316203AE2-005 GEN
Solar/Wind Harmer
10.758
3141766HARMONY
Solar/Wind Harmer
2.268
316280AD1-041 GEN
Solar/Wind Harmer
1.917
966881AG1-559 GEN
Solar/Wind Harmer
0.764
3146376EDENTON
Solar/Wind Harmer
-0.025
316156AD2-030 GEN
Solar/Wind Harmer
0.677
3141873WAN 176
Solar/Wind Harmer
3.008
970917AG2-570 GEN
Solar/Wind Harmer
62.922
315614AA2-178 GEN
Solar/Wind Harmer
2.686
3150401LDYSMT4
Adder
29.367
3150371LDYSMT1
Adder
28.377
971157AH1-035 GEN
Solar/Wind Harmer
3.061
3156081AA2-088 GEN
Solar/Wind Harmer
7.94
316365GEN2_N
Solar/Wind Harmer
1.647
315737AD1-076 GEN
Solar/Wind Harmer
4.641
962971AG1-146 GEN
Solar/Wind Harmer
4.555
3146206CASHIE
Solar/Wind Harmer
-0.024
3145893MURPHYS
Solar/Wind Harmer
0.169
3145893MURPHYS
Solar/Wind Harmer
-0.024
957521AF2-046 GEN
Solar/Wind Harmer
18.97
961681AG1-008 GEN
Solar/Wind Harmer
18.97
316484AD2-074 GEN
Solar/Wind Harmer
6.056
970009AG2-005 GEN
Solar/Wind Harmer
3.007
3146173TUNIS
Solar/Wind Harmer
-0.024
3156021HOLLOMANSOL
Solar/Wind Harmer
3.215
966621AG1-532 GEN
Solar/Wind Harmer
0.483
316463AE2-346 GEN
Solar/Wind Harmer
0.385
316140AB2-099
Solar/Wind Harmer
0.161
962331AG1-082 GEN
Solar/Wind Harmer
2.977
316404AE1-155 C
Solar/Wind Harmer
4.567
3146263WOODLND
Solar/Wind Harmer
-0.023
313506AB2-031 GEN
Solar/Wind Harmer
1.892
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.023
316317KELFORD C
Solar/Wind Harmer
1.097
3145823KELFORD
Solar/Wind Harmer
-0.023
3147043LAWRENC
Solar/Wind Harmer
-0.014
316478AD1-087 GEN
Solar/Wind Harmer
2.005
316486AD2-202 GEN
Solar/Wind Harmer
0.587
3145796HORNRTN
Solar/Wind Harmer
-0.092
3145796HORNRTN
Solar/Wind Harmer
-0.023
3150351NORNECKC2
Adder
2.074
3144293JTRSVLE
Adder
0.609
3151761LOISA E
Adder
22.198
972183AH1-676 GEN
Adder
173.63
972255AH1-712 GEN
Adder
75.968
3141316ARNOLDS
Adder
0.289
3141196NOKESVL
Solar/Wind Helper
1.139
NYPJM->LTFIMP_NY
CLTF
3.429
LGEELTFEXP_LGEE->PJM
CLTF
1.289
WECLTFEXP_WEC->PJM
CLTF
0.615
LAGNLTFEXP_LAGN->PJM
CLTF
8.194
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.289
TVALTFEXP_TVA->PJM
CLTF
4.152
CBM West 1LTFEXP_CBM-W1->PJM
CBM
20.16
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.053
MECLTFEXP_MEC->PJM
CLTF
3.551
SIGELTFEXP_SIGE->PJM
CLTF
0.108
CPLELTFEXP_CPLE->PJM
CLTF
12.064
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.692

Details for AE1-157 TAP-6LDYSMITH CT 230.0 kV Ckt 1 line l/o DVP_P4-2: 574T575_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AE1-157 TAP-6LDYSMITH CT 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 574T575_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:143.48 %
Rating:1809.0 MVA
Rating Type:C
MVA to Mitigate:2595.59
MW Contribution:51.66
Bus #Bus NameTypeMW Contribution
315051AA1-145 CT1
50/50
2.898
971645AH1-323 GEN
50/50
17.376
966881AG1-559 GEN
Solar/Wind Harmer
2.184
3142416OLDCHRC
Solar/Wind Harmer
1.914
316473AC1-191 GEN
Solar/Wind Harmer
2.025
970293AG2-193 GEN
Solar/Wind Harmer
2.132
3143096IRON208
Adder
0.606
3143096IRON208
Adder
0.594
3150861SPRUNCD
Adder
0.643
3142946ENON
Solar/Wind Harmer
-0.005
970133AG2-095 GEN
Solar/Wind Harmer
1.669
965281AG1-393 GEN
Solar/Wind Harmer
1.802
970129AG2-093 GEN
Solar/Wind Harmer
8.1
315839AE2-212 C
Solar/Wind Harmer
0.433
315778AD1-151 GEN
Solar/Wind Harmer
12.182
3142296MT RD221
50/50
0.631
3142366NRTHEST
50/50
0.558
3150691DARBY 3
50/50
12.032
3150701DARBY 4
50/50
12.004
3150681DARBY 2
50/50
11.99
315673AE1-157 GEN
Solar/Wind Harmer
62.078
957411AF2-035 GEN
Solar/Wind Harmer
32.692
970317AG2-208 GEN
Solar/Wind Harmer
31.784
966871AG1-558 GEN
Solar/Wind Harmer
0.566
966871AG1-558 GEN
Solar/Wind Harmer
0.194
3150671DARBY 1
Adder
11.286
316075AC2-137 C
Solar/Wind Harmer
0.441
3142946ENON
Solar/Wind Harmer
-0.002
944641AF1-129 GEN
Adder
65.069
316240AF1-291 C
Solar/Wind Harmer
0.455
3143526WINTERP
Solar/Wind Harmer
-0.074
316033AB2-134 GEN
Solar/Wind Harmer
4.473
315697AD1-025 GEN
Solar/Wind Harmer
2.805
970657AG2-426 GEN
Solar/Wind Harmer
4.011
970657AG2-426 GEN
Solar/Wind Harmer
0.839
316236AE1-162_GEN
Solar/Wind Harmer
0.382
971223AH1-071 GEN
Solar/Wind Harmer
1.579
316441AF1-014 GEN
Solar/Wind Harmer
0.848
316036AC1-147 C
Solar/Wind Harmer
0.324
3150991CHESPKB
Adder
1.119
3150991CHESPKB
Adder
1.092
316316AC1-027 C
Solar/Wind Harmer
0.366
3142956BIRDNECK
Solar/Wind Harmer
0.64
316185AD1-033 GEN
Solar/Wind Harmer
1.254
3145506HICKORY
Solar/Wind Harmer
-0.047
3145506HICKORY
Solar/Wind Harmer
-0.028
3145506HICKORY
Solar/Wind Harmer
-0.007
316339AD2-160 GEN
Solar/Wind Harmer
0.796
316018AA1-139 ULT2
Solar/Wind Harmer
1.01
316017AA1-139 ULT1
Solar/Wind Harmer
0.954
3137176SLIGO L2192
Solar/Wind Harmer
-0.047
3146456SLIGO L269
Solar/Wind Harmer
1.39
3130086AYDLETT
Solar/Wind Harmer
-0.047
3146386ELIZ CT
Solar/Wind Harmer
-0.012
316431W1029_GEN1
Solar/Wind Harmer
2.086
316433W1029_GEN2
Solar/Wind Harmer
2.086
316468AD1-105 GEN
Solar/Wind Harmer
1.28
3146516WINFALL
Solar/Wind Harmer
-0.011
3146516WINFALL
Solar/Wind Harmer
-0.011
3146516WINFALL
Solar/Wind Harmer
-0.011
3146626S HERTFORD
Solar/Wind Harmer
-0.011
3146626S HERTFORD
Solar/Wind Harmer
-0.011
3144356SAPONY
Solar/Wind Harmer
0.397
315742AE1-103 GEN
Solar/Wind Harmer
1.177
3146376EDENTON
Solar/Wind Harmer
0.33
3146376EDENTON
Solar/Wind Harmer
0.33
316065AD1-022 GEN
Solar/Wind Harmer
5.248
3145893MURPHYS
Solar/Wind Harmer
0.29
3145893MURPHYS
Solar/Wind Harmer
-0.019
3146173TUNIS
Solar/Wind Harmer
-0.01
3146173TUNIS
Solar/Wind Harmer
-0.01
316487AF1-042 GEN
Solar/Wind Harmer
1.34
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
972189AH1-679 GEN
50/50
6.496
316312AB1-027
Solar/Wind Harmer
0.64
971285AH1-108 GEN
Adder
1.052
315976AC1-164 GENA
Solar/Wind Harmer
15.998
316169AC1-164_GENC
Solar/Wind Harmer
13.821
315975AC1-164 GENB
Solar/Wind Harmer
0.473
316132AB2-190 GEN1
Solar/Wind Harmer
1.45
316233AE1-074 FULL
Solar/Wind Harmer
0.383
971281AH1-106 GEN
Solar/Wind Harmer
2.311
971283AH1-107 GEN
Solar/Wind Harmer
2.311
971167AH1-042 GEN
Solar/Wind Harmer
13.55
3142433PROV 92
Adder
0.24
3142433PROV 92
Adder
0.24
316369SG1_INVT
Solar/Wind Harmer
2.478
3143873LANEXA
Solar/Wind Harmer
-0.008
3143316POE
Solar/Wind Harmer
-0.052
972265AH1-717 GEN
Adder
9.04
3151201GRAVEL4
Adder
8.475
3151191GRAVEL3
Adder
8.367
3151211GRAVEL5
Adder
8.367
316314AB2-024 C
Solar/Wind Harmer
1.098
971445AH1-216 GEN
Solar/Wind Harmer
7.863
316059AD1-063 C
Solar/Wind Harmer
0.284
957831AF2-077 GEN
Solar/Wind Harmer
0.376
3138283WHITEMARSH
Solar/Wind Harmer
0.019
315662AE1-191 GEN
Solar/Wind Harmer
1.493
315666AE1-190 GEN
Solar/Wind Harmer
0.373
315833AF1-017_GEN
Solar/Wind Harmer
2.326
316349AD2-085 GEN
Solar/Wind Harmer
1.089
316311AC2-079 GEN
Solar/Wind Harmer
6.173
957601AF2-054 GEN
Solar/Wind Harmer
0.363
3141873WAN 176
Solar/Wind Harmer
-0.002
3152611GOSPORTB
Adder
1.36
3152621GOSPORTC
Adder
1.154
3152601GOSPORTA
Adder
1.065
3151081ELIZAR1
Adder
9.78
3151091ELIZAR2
Adder
9.61
315835AF2-110_GEN
Solar/Wind Harmer
1.479
957871AF2-081 GEN
Solar/Wind Harmer
5.897
316305AF2-043 C
Solar/Wind Harmer
0.355
319010AE1-072 C
Solar/Wind Harmer
2.378
3146406KITTY HAWK
Solar/Wind Harmer
0.01
313526AB2-022
Solar/Wind Harmer
0.314
3146486SUNBURY
Solar/Wind Harmer
-0.012
3146486SUNBURY
Solar/Wind Harmer
-0.012
3141913WHIT STONE
Solar/Wind Harmer
-0.012
316321Z2-027
Solar/Wind Harmer
0.312
3146396TANGLEW
Solar/Wind Harmer
0.213
3145176PASQUOTANK
Solar/Wind Harmer
-0.007
3138133OCRAN
Solar/Wind Harmer
-0.003
316315AB2-025 C
Solar/Wind Harmer
0.307
315814AE2-033 C
Solar/Wind Harmer
10.558
315611Z1-036_GEN2
Solar/Wind Harmer
2.785
3141783LANCAST
Solar/Wind Harmer
-0.007
3141783LANCAST
Solar/Wind Harmer
-0.004
3130156CHOWAN
Solar/Wind Harmer
-0.011
3130156CHOWAN
Solar/Wind Harmer
-0.011
315816AE2-034 GEN
Solar/Wind Harmer
0.877
3130546PLYMOUTH
Solar/Wind Harmer
-0.011
315732AD1-074 GEN1
Solar/Wind Harmer
2.139
315733AD1-074 GEN2
Solar/Wind Harmer
2.139
315735AD1-075 GEN1
Solar/Wind Harmer
1.07
962981AG1-147 GEN
Solar/Wind Harmer
4.609
965291AG1-394 GEN
Solar/Wind Harmer
0.933
3146206CASHIE
Solar/Wind Harmer
-0.01
970601AG2-382 GEN
Solar/Wind Harmer
4.572
316318V4-068
Solar/Wind Harmer
0.259
3145893MURPHYS
Solar/Wind Harmer
-0.028
3145893MURPHYS
Solar/Wind Harmer
-0.01
3145513AHOSKIE
Solar/Wind Harmer
0.089
961941AG1-037 GEN
Solar/Wind Harmer
0.077
3145513AHOSKIE
Solar/Wind Harmer
-0.01
3145683EARLEYS
Solar/Wind Harmer
-0.02
3145683EARLEYS
Solar/Wind Harmer
-0.01
3145683EARLEYS
Solar/Wind Harmer
-0.01
3146043SEABORD
Solar/Wind Harmer
-0.01
315607AA1-063A GEN
Solar/Wind Harmer
1.016
946281AF1-292 GEN
Solar/Wind Harmer
0.225
316087AB2-174 GEN
Solar/Wind Harmer
1.418
315652AC1-086 GEN
Solar/Wind Harmer
11.162
941031AE2-094 GEN
Solar/Wind Harmer
18.558
944011AF1-069 GEN
Solar/Wind Harmer
5.815
3137643SOCKMAN
Solar/Wind Harmer
-0.039
970673AG2-436 GEN
Solar/Wind Harmer
20.5
970673AG2-436 GEN
Solar/Wind Harmer
10.38
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.004
972193AH1-681 GEN
Adder
1.981
3146033SCOT NK
Solar/Wind Harmer
-0.038
971967AH1-528 GEN
Solar/Wind Harmer
18.168
970085AG2-068 GEN
Solar/Wind Harmer
5.8
970581AG2-369 GEN
Solar/Wind Harmer
4.988
316005AA1-067
Solar/Wind Harmer
0.188
3145746EVERETS
Solar/Wind Harmer
-0.037
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
970181AG2-120 GEN
Solar/Wind Harmer
1.217
957861AF2-080 GEN
Solar/Wind Harmer
3.974
970831AG2-522 GEN
Solar/Wind Harmer
4.54
972205AH1-687 GEN
Adder
2.844
3141426STAFORD
Solar/Wind Helper
0.043
316420AA1-050 GEN
Solar/Wind Harmer
0.204
3142433PROV 92
Adder
0.24
3142433PROV 92
Adder
0.24
316382AG1-145 C
Solar/Wind Harmer
0.41
961611AG1-000B GEN
Solar/Wind Harmer
2.819
315813AE1-149 C
Solar/Wind Harmer
8.328
3151221GRAVEL6
Adder
8.465
3151171GRAVELC
Adder
1.629
970659AG2-427 GEN
Solar/Wind Harmer
1.221
316083AB2-161 GEN
Solar/Wind Harmer
2.095
3144216WINCHST
Adder
0.432
3150921YORKTN3
Adder
2.87
970661AG2-428 GEN
Solar/Wind Harmer
2.394
3145336SMITFLD
Solar/Wind Harmer
-0.005
3141843SHACKLE
Adder
0.572
316203AE2-005 GEN
Solar/Wind Harmer
5.302
3141766HARMONY
Solar/Wind Harmer
1.119
316280AD1-041 GEN
Solar/Wind Harmer
0.933
3144536CHRHLND
Solar/Wind Harmer
-0.002
316156AD2-030 GEN
Solar/Wind Harmer
0.324
3141873WAN 176
Solar/Wind Harmer
1.439
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
9.905
315773AC2-141 GEN
Solar/Wind Harmer
4.984
944581AF1-123 GEN
Solar/Wind Harmer
53.957
944601AF1-125 GEN
Solar/Wind Harmer
53.115
3146456SLIGO L269
Solar/Wind Harmer
-0.012
971153AH1-033 GEN
Solar/Wind Harmer
1.434
316320Y1-086
Solar/Wind Harmer
0.682
316435W1029_GEN3
Solar/Wind Harmer
2.086
971781AH1-399 GEN
Solar/Wind Harmer
0.708
3146516WINFALL
Solar/Wind Harmer
-0.011
3145273HOLLAND
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.011
3146376EDENTON
Solar/Wind Harmer
-0.011
315614AA2-178 GEN
Solar/Wind Harmer
1.169
971157AH1-035 GEN
Solar/Wind Harmer
1.327
315737AD1-076 GEN
Solar/Wind Harmer
2.01
316313AB2-026
Solar/Wind Harmer
0.285
316258AE1-075 C
Solar/Wind Harmer
0.257
316405AF2-144 C
Solar/Wind Harmer
0.271
3143336POWHATN
Solar/Wind Harmer
1.067
3156081AA2-088 GEN
Solar/Wind Harmer
3.431
962971AG1-146 GEN
Solar/Wind Harmer
1.975
3146206CASHIE
Solar/Wind Harmer
-0.01
316365GEN2_N
Solar/Wind Harmer
0.702
3145893MURPHYS
Solar/Wind Harmer
0.073
3145893MURPHYS
Solar/Wind Harmer
-0.01
957521AF2-046 GEN
Solar/Wind Harmer
8.162
961681AG1-008 GEN
Solar/Wind Harmer
8.162
3146173TUNIS
Solar/Wind Harmer
-0.01
3156021HOLLOMANSOL
Solar/Wind Harmer
1.383
316463AE2-346 GEN
Solar/Wind Harmer
0.165
316140AB2-099
Solar/Wind Harmer
0.069
962331AG1-082 GEN
Solar/Wind Harmer
1.277
316484AD2-074 GEN
Solar/Wind Harmer
2.562
970009AG2-005 GEN
Solar/Wind Harmer
1.272
3146263WOODLND
Solar/Wind Harmer
-0.01
966621AG1-532 GEN
Solar/Wind Harmer
0.204
3145963POPLR C
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
316317KELFORD C
Solar/Wind Harmer
0.468
3145823KELFORD
Solar/Wind Harmer
-0.01
313506AB2-031 GEN
Solar/Wind Harmer
0.796
3145796HORNRTN
Solar/Wind Harmer
-0.039
3145796HORNRTN
Solar/Wind Harmer
-0.01
972255AH1-712 GEN
Adder
44.332
316404AE1-155 C
Solar/Wind Harmer
1.851
3147043LAWRENC
Solar/Wind Harmer
-0.006
3145933PARMELE
Solar/Wind Harmer
-0.009
966801AG1-551 GEN
Solar/Wind Harmer
1.188
316210AC1-098 GEN
Solar/Wind Harmer
1.487
970917AG2-570 GEN
Solar/Wind Harmer
23.277
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
315724AD1-057 GEN
Solar/Wind Harmer
0.528
316327AA2-057 GEN
Solar/Wind Harmer
0.917
3150351NORNECKC2
Adder
0.772
3144293JTRSVLE
Adder
0.236
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
316181AB2-040 GEN
Solar/Wind Harmer
1.381
316426AA2-053 GEN
Solar/Wind Harmer
0.993
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.098
3145593CAROLNA
Solar/Wind Harmer
0.081
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145783HORNRTN
Solar/Wind Harmer
1.151
3145783HORNRTN
Solar/Wind Harmer
0.921
3145783HORNRTN
Solar/Wind Harmer
0.288
3145783HORNRTN
Solar/Wind Harmer
0.115
972185AH1-677 GEN
Adder
4.839
958261AF2-120 GEN
Solar/Wind Harmer
3.718
972187AH1-678 GEN
Adder
2.432
3145933PARMELE
Solar/Wind Harmer
-0.019
3145933PARMELE
Solar/Wind Harmer
-0.009
970933AG2-581 GEN
Solar/Wind Harmer
8.889
316274AC1-208 GEN
Solar/Wind Harmer
1.012
970099AG2-077 GEN
Solar/Wind Harmer
11.254
3150341NORNECKC1
Adder
0.797
3150341NORNECKC1
Adder
0.791
3144293JTRSVLE
Adder
0.236
3144293JTRSVLE
Adder
0.199
226929AD2-058 GEN
Solar/Wind Helper
0.044
315052AA1-145 CT2
50/50
2.911
966881AG1-559 GEN
Solar/Wind Harmer
0.747
3142416OLDCHRC
Solar/Wind Harmer
-0.049
3142416OLDCHRC
Solar/Wind Harmer
-0.019
3143096IRON208
Adder
0.606
3142543TWELFTH
Solar/Wind Harmer
-0.002
3150851SPRUNCC
Adder
0.643
944631AF1-128 GEN
Adder
65.707
315671AE2-027_GEN
Solar/Wind Harmer
10.943
970129AG2-093 GEN
Solar/Wind Harmer
3.281
316458AB2-190 GEN2
Solar/Wind Harmer
1.45
3143526WINTERP
Solar/Wind Harmer
-0.074
971069AG2-661 GEN
Solar/Wind Harmer
2.225
3142433PROV 92
Solar/Wind Harmer
-0.055
3142433PROV 92
Adder
0.24
3142433PROV 92
Adder
0.24
971647AH1-324 GEN
Solar/Wind Harmer
6.815
316159AE1-175 C
Solar/Wind Harmer
0.365
961611AG1-000B GEN
Solar/Wind Harmer
6.606
3151171GRAVELC
Adder
1.239
970659AG2-427 GEN
Solar/Wind Harmer
6.892
316381AD1-082 GEN
Solar/Wind Harmer
1.184
971317AH1-138 GEN
Solar/Wind Harmer
1.611
3138126ROCKLANDING
Solar/Wind Harmer
0.039
970661AG2-428 GEN
Solar/Wind Harmer
13.512
3145336SMITFLD
Solar/Wind Harmer
-0.05
3143226MDLTHAN
Solar/Wind Harmer
-0.013
971777AH1-397 GEN
Solar/Wind Harmer
1.479
3141843SHACKLE
Adder
0.572
3141766HARMONY
Solar/Wind Harmer
-0.002
316072AD1-144
Solar/Wind Harmer
0.244
316375AC2-012 GEN
Solar/Wind Harmer
4.153
3150981CHESPKA
Adder
1.334
316294AC1-161 GEN
Solar/Wind Harmer
3.853
944591AF1-124 GEN
Solar/Wind Harmer
54.151
316093AE2-104_GEN
Solar/Wind Harmer
3.44
316388AE2-253 GEN
Solar/Wind Harmer
0.796
316246AF1-032 C
Solar/Wind Harmer
0.239
3146456SLIGO L269
Solar/Wind Harmer
-0.012
3146516WINFALL
Solar/Wind Harmer
-0.037
3146516WINFALL
Solar/Wind Harmer
-0.011
3138133OCRAN
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
2.785
3130156CHOWAN
Solar/Wind Harmer
-0.011
939411AE1-173 GEN
Solar/Wind Harmer
54.187
3145663CRESWEL
Solar/Wind Harmer
-0.03
971163AH1-040 GEN
Solar/Wind Harmer
10.157
3143336POWHATN
Solar/Wind Harmer
1.255
940641AE2-051 GEN
Solar/Wind Harmer
9.841
3146206CASHIE
Solar/Wind Harmer
-0.01
971547AH1-271 GEN
Solar/Wind Harmer
2.612
316023GEN1_S
Solar/Wind Harmer
0.702
3145893MURPHYS
Solar/Wind Harmer
-0.041
3145893MURPHYS
Solar/Wind Harmer
0.309
3146173TUNIS
Solar/Wind Harmer
-0.01
961951AG1-038 GEN
Solar/Wind Harmer
1.34
3145683EARLEYS
Solar/Wind Harmer
-0.01
3146263WOODLND
Solar/Wind Harmer
-0.01
316336AC2-165 C
Solar/Wind Harmer
1.744
960081AF2-299 GEN
Solar/Wind Harmer
1.128
3145963POPLR C
Solar/Wind Harmer
-0.01
316011AB1-132 GEN
Solar/Wind Harmer
2.076
962571AG1-106 GEN
Solar/Wind Harmer
1.426
3145823KELFORD
Solar/Wind Harmer
-0.01
316174AB2-169 GEN
Solar/Wind Harmer
1.527
316190AA2-174 GEN
Solar/Wind Harmer
0.121
962861AG1-135 GEN
Solar/Wind Harmer
3.656
3145796HORNRTN
Solar/Wind Harmer
-0.032
3145796HORNRTN
Solar/Wind Harmer
-0.01
972277AH1-723 GEN
Adder
51.66
971795AH1-408 GEN
Solar/Wind Harmer
7.284
3145783HORNRTN
Solar/Wind Harmer
-0.01
3147043LAWRENC
Adder
0.77
3146293MARTNCO
Solar/Wind Harmer
0.059
316212AC1-099_GEN
Solar/Wind Harmer
0.826
970919AG2-571 GEN
Solar/Wind Harmer
2.946
970087AG2-069 GEN
Solar/Wind Harmer
8.699
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
315722AD1-056 GEN
Solar/Wind Harmer
0.96
964211AG1-282 GEN
Solar/Wind Harmer
0.275
3141726DUNNSVL
Solar/Wind Harmer
-0.036
316494AC1-189 GEN
Solar/Wind Harmer
0.977
316129AC1-054 GEN
Solar/Wind Harmer
0.79
957481AF2-042 GEN
Solar/Wind Harmer
28.134
3150351NORNECKC2
Adder
0.759
3144293JTRSVLE
Adder
0.236
NYPJM->LTFIMP_NY
CLTF
1.538
LGEELTFEXP_LGEE->PJM
CLTF
0.748
WECLTFEXP_WEC->PJM
CLTF
0.372
LAGNLTFEXP_LAGN->PJM
CLTF
3.852
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.958
TVALTFEXP_TVA->PJM
CLTF
1.953
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.851
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.75
MECLTFEXP_MEC->PJM
CLTF
1.962
SIGELTFEXP_SIGE->PJM
CLTF
0.06
CPLELTFEXP_CPLE->PJM
CLTF
4.899
CBM West 2LTFEXP_CBM-W2->PJM
CBM
20.775

Details for AE1-157 TAP-6LDYSMITH CT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AE1-157 TAP-6LDYSMITH CT 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:137.7 %
Rating:1478.62 MVA
Rating Type:B
MVA to Mitigate:2036.01
MW Contribution:48.21
Bus #Bus NameTypeMW Contribution
972189AH1-679 GEN
50/50
6.54
316312AB1-027
Solar/Wind Harmer
0.289
3142296MT RD221
50/50
0.608
3142366NRTHEST
50/50
0.528
3150691DARBY 3
50/50
11.375
3150701DARBY 4
50/50
11.349
3150681DARBY 2
50/50
11.335
315673AE1-157 GEN
Solar/Wind Harmer
52.424
957411AF2-035 GEN
Solar/Wind Harmer
28.305
970317AG2-208 GEN
Solar/Wind Harmer
26.223
966871AG1-558 GEN
Solar/Wind Harmer
0.187
3150671DARBY 1
Adder
10.67
316075AC2-137 C
Solar/Wind Harmer
0.038
3142946ENON
Solar/Wind Harmer
0.013
944641AF1-129 GEN
Adder
59.87
316240AF1-291 C
Solar/Wind Harmer
0.001
3143526WINTERP
Solar/Wind Harmer
0.585
316033AB2-134 GEN
Solar/Wind Harmer
0.007
315697AD1-025 GEN
Solar/Wind Harmer
0.126
316468AD1-105 GEN
Solar/Wind Harmer
-0.033
970657AG2-426 GEN
Solar/Wind Harmer
3.569
970657AG2-426 GEN
Solar/Wind Harmer
0.748
316236AE1-162_GEN
Solar/Wind Harmer
0.001
971223AH1-071 GEN
Solar/Wind Harmer
1.027
316036AC1-147 C
Solar/Wind Harmer
0.017
3150991CHESPKB
Adder
0.985
3150991CHESPKB
Adder
0.962
316316AC1-027 C
Solar/Wind Harmer
0.09
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.003
3145506HICKORY
Solar/Wind Harmer
0.37
3145506HICKORY
Solar/Wind Harmer
0.222
3145506HICKORY
Solar/Wind Harmer
0.056
316339AD2-160 GEN
Solar/Wind Harmer
0.15
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.051
3137176SLIGO L2192
Solar/Wind Harmer
0.366
3146456SLIGO L269
Solar/Wind Harmer
1.627
3130086AYDLETT
Solar/Wind Harmer
0.367
3146386ELIZ CT
Solar/Wind Harmer
0.091
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.089
3146516WINFALL
Solar/Wind Harmer
0.089
3146516WINFALL
Solar/Wind Harmer
0.089
3146626S HERTFORD
Solar/Wind Harmer
0.089
3146626S HERTFORD
Solar/Wind Harmer
0.089
3144356SAPONY
Solar/Wind Harmer
0.735
315742AE1-103 GEN
Solar/Wind Harmer
0.001
3146376EDENTON
Solar/Wind Harmer
0.385
3146376EDENTON
Solar/Wind Harmer
0.385
316065AD1-022 GEN
Solar/Wind Harmer
3.744
958261AF2-120 GEN
Solar/Wind Harmer
2.666
3145893MURPHYS
Solar/Wind Harmer
0.538
3145893MURPHYS
Solar/Wind Harmer
0.145
3146173TUNIS
Solar/Wind Harmer
0.079
3146173TUNIS
Solar/Wind Harmer
0.079
3142666NORTHAMPTON
Solar/Wind Harmer
0.076
3142666NORTHAMPTON
Solar/Wind Harmer
0.076
3142666NORTHAMPTON
Solar/Wind Harmer
0.076
3142666NORTHAMPTON
Solar/Wind Harmer
0.046
316181AB2-040 GEN
Solar/Wind Harmer
0.11
316426AA2-053 GEN
Solar/Wind Harmer
0.255
3145796HORNRTN
Solar/Wind Harmer
0.224
3145593CAROLNA
Solar/Wind Harmer
0.075
3145593CAROLNA
Solar/Wind Harmer
0.075
966811AG1-552 GEN
Solar/Wind Harmer
0.811
3145593CAROLNA
Solar/Wind Harmer
0.093
3145783HORNRTN
Solar/Wind Harmer
1.321
3145783HORNRTN
Solar/Wind Harmer
1.057
3145783HORNRTN
Solar/Wind Harmer
0.33
3145783HORNRTN
Solar/Wind Harmer
0.132
3145933PARMELE
Solar/Wind Harmer
0.146
3145933PARMELE
Solar/Wind Harmer
0.073
316077AC2-138 C
Solar/Wind Harmer
0
3150341NORNECKC1
Adder
0.759
3150341NORNECKC1
Adder
0.753
316274AC1-208 GEN
Solar/Wind Harmer
0.373
972185AH1-677 GEN
Adder
3.992
972187AH1-678 GEN
Adder
2.007
970933AG2-581 GEN
Solar/Wind Harmer
5.576
3145493TOT1
Solar/Wind Harmer
0.158
3145453TOT5
Solar/Wind Harmer
0.095
3145603CNETO
Solar/Wind Harmer
0.063
961601AG1-000A GEN
Solar/Wind Harmer
1.182
316263AC1-034 GEN
Solar/Wind Harmer
2.524
970099AG2-077 GEN
Solar/Wind Harmer
7.081
939181AE1-148 GEN
Solar/Wind Harmer
3.089
313527AB2-043 GEN
Solar/Wind Harmer
0.001
971741AH1-377 GEN
Solar/Wind Harmer
6.257
316034AC1-036 C
Solar/Wind Harmer
0.005
970323AG2-213 GEN
Solar/Wind Harmer
2.676
971775AH1-396 GEN
Solar/Wind Harmer
0.1
970301AG2-198 GEN
Solar/Wind Harmer
2.661
958211AF2-115 GEN
Solar/Wind Harmer
0.743
963191AG1-168 GEN
Solar/Wind Harmer
0.248
3144293JTRSVLE
Adder
0.197
3144293JTRSVLE
Adder
0.166
3147133PAMPLIN
Solar/Wind Harmer
0.062
3147133PAMPLIN
Solar/Wind Harmer
0.049
962561AG1-105 GEN
Solar/Wind Harmer
2.907
964791AG1-342 GEN
Solar/Wind Harmer
1.152
3146843MT LREL
Solar/Wind Harmer
0.06
3146843MT LREL
Solar/Wind Harmer
0.06
3146776BUCKING
Solar/Wind Harmer
0.231
3146776BUCKING
Solar/Wind Harmer
0.019
971285AH1-108 GEN
Adder
0.966
315976AC1-164 GENA
Solar/Wind Harmer
13.07
316169AC1-164_GENC
Solar/Wind Harmer
11.292
315975AC1-164 GENB
Solar/Wind Harmer
0.387
971167AH1-042 GEN
Solar/Wind Harmer
10.363
316132AB2-190 GEN1
Solar/Wind Harmer
0.626
3142433PROV 92
Adder
0.224
3142433PROV 92
Adder
0.224
316233AE1-074 FULL
Solar/Wind Harmer
0.09
971281AH1-106 GEN
Solar/Wind Harmer
1.562
971283AH1-107 GEN
Solar/Wind Harmer
1.562
316369SG1_INVT
Solar/Wind Harmer
0.004
3143873LANEXA
Solar/Wind Harmer
0.066
316314AB2-024 C
Solar/Wind Harmer
0
3143316POE
Solar/Wind Harmer
0.414
972265AH1-717 GEN
Adder
8.131
3151201GRAVEL4
Adder
7.623
3151191GRAVEL3
Adder
7.526
3151211GRAVEL5
Adder
7.526
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
3.086
315662AE1-191 GEN
Solar/Wind Harmer
0.003
315666AE1-190 GEN
Solar/Wind Harmer
0.001
3138283WHITEMARSH
Solar/Wind Harmer
0.024
971445AH1-216 GEN
Solar/Wind Harmer
7.113
3141873WAN 176
Solar/Wind Harmer
0.02
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.066
316311AC2-079 GEN
Solar/Wind Harmer
2.768
3141913WHIT STONE
Solar/Wind Harmer
0.096
3138133OCRAN
Solar/Wind Harmer
0.028
3152611GOSPORTB
Adder
1.198
3152621GOSPORTC
Adder
1.017
3152601GOSPORTA
Adder
0.938
3151081ELIZAR1
Adder
8.608
3151091ELIZAR2
Adder
8.459
3141783LANCAST
Solar/Wind Harmer
0.056
3141783LANCAST
Solar/Wind Harmer
0.037
315835AF2-110_GEN
Solar/Wind Harmer
0.636
316305AF2-043 C
Solar/Wind Harmer
0.001
957871AF2-081 GEN
Solar/Wind Harmer
4.589
319010AE1-072 C
Solar/Wind Harmer
0.463
3146406KITTY HAWK
Solar/Wind Harmer
0.011
313526AB2-022
Solar/Wind Harmer
0.049
3146486SUNBURY
Solar/Wind Harmer
0.091
3146486SUNBURY
Solar/Wind Harmer
0.091
316321Z2-027
Solar/Wind Harmer
0.017
3146396TANGLEW
Solar/Wind Harmer
0.249
3145176PASQUOTANK
Solar/Wind Harmer
0.056
962981AG1-147 GEN
Solar/Wind Harmer
3.282
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
316315AB2-025 C
Solar/Wind Harmer
0.071
315814AE2-033 C
Solar/Wind Harmer
6.916
3130156CHOWAN
Solar/Wind Harmer
0.086
3130156CHOWAN
Solar/Wind Harmer
0.086
970327AG2-215 GEN
Solar/Wind Harmer
2.794
315816AE2-034 GEN
Solar/Wind Harmer
0.361
3130546PLYMOUTH
Solar/Wind Harmer
0.082
315732AD1-074 GEN1
Solar/Wind Harmer
0.471
315733AD1-074 GEN2
Solar/Wind Harmer
0.471
315735AD1-075 GEN1
Solar/Wind Harmer
0.236
965291AG1-394 GEN
Solar/Wind Harmer
0.361
3146206CASHIE
Solar/Wind Harmer
0.081
970601AG2-382 GEN
Solar/Wind Harmer
3.02
972193AH1-681 GEN
Adder
1.848
3145893MURPHYS
Solar/Wind Harmer
0.217
3145893MURPHYS
Solar/Wind Harmer
0.08
3145513AHOSKIE
Solar/Wind Harmer
0.165
3145513AHOSKIE
Solar/Wind Harmer
0.079
3145683EARLEYS
Solar/Wind Harmer
0.157
3145683EARLEYS
Solar/Wind Harmer
0.078
3145683EARLEYS
Solar/Wind Harmer
0.078
3146043SEABORD
Solar/Wind Harmer
0.078
315607AA1-063A GEN
Solar/Wind Harmer
0.158
315652AC1-086 GEN
Solar/Wind Harmer
8.376
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.3
3145796HORNRTN
Solar/Wind Harmer
0.239
3145796HORNRTN
Solar/Wind Harmer
0.03
3146033SCOT NK
Solar/Wind Harmer
0.297
941031AE2-094 GEN
Solar/Wind Harmer
13.369
944011AF1-069 GEN
Solar/Wind Harmer
4.368
3141813NORNECK
Solar/Wind Harmer
0.072
970673AG2-436 GEN
Solar/Wind Harmer
15.278
970673AG2-436 GEN
Solar/Wind Harmer
10.185
316005AA1-067
Solar/Wind Harmer
0.076
3145746EVERETS
Solar/Wind Harmer
0.283
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
970181AG2-120 GEN
Solar/Wind Harmer
0.885
971967AH1-528 GEN
Solar/Wind Harmer
11.354
957861AF2-080 GEN
Solar/Wind Harmer
2.998
316420AA1-050 GEN
Solar/Wind Harmer
0.002
970831AG2-522 GEN
Solar/Wind Harmer
2.933
970085AG2-068 GEN
Solar/Wind Harmer
3.642
970581AG2-369 GEN
Solar/Wind Harmer
3.132
3145573BETHELC
Solar/Wind Harmer
0.068
3145573BETHELC
Solar/Wind Harmer
0.068
316319Z2-044 C
Solar/Wind Harmer
0
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
971443AH1-215 GEN
Solar/Wind Harmer
1.054
3144303KENBRDG
Solar/Wind Harmer
0.05
970683AG2-441 GEN
Solar/Wind Harmer
4.154
970681AG2-440 GEN
Solar/Wind Harmer
3.323
946301AF1-294 GEN
Solar/Wind Harmer
1.222
961791AG1-021 GEN
Solar/Wind Harmer
0.594
315657AE1-056 GEN
Solar/Wind Harmer
2.127
316118AC1-105 GEN
Solar/Wind Harmer
0.152
970285AG2-188 GEN
Solar/Wind Harmer
4.613
971845AH1-439 GEN
Solar/Wind Harmer
2.627
3147173SINAI
Solar/Wind Harmer
0.057
3147243WELCO
Solar/Wind Harmer
0.036
3141426STAFORD
Solar/Wind Helper
0.036
315051AA1-145 CT1
50/50
2.918
971645AH1-323 GEN
50/50
16.828
316473AC1-191 GEN
Solar/Wind Harmer
0.547
3142416OLDCHRC
Solar/Wind Harmer
1.565
970293AG2-193 GEN
Solar/Wind Harmer
1.528
3143096IRON208
Adder
0.565
3143096IRON208
Adder
0.554
3150861SPRUNCD
Adder
0.59
3142946ENON
Solar/Wind Harmer
0.043
970133AG2-095 GEN
Solar/Wind Harmer
1.165
970129AG2-093 GEN
Solar/Wind Harmer
7.076
965281AG1-393 GEN
Solar/Wind Harmer
1.247
315839AE2-212 C
Solar/Wind Harmer
0.001
3142433PROV 92
Adder
0.224
3142433PROV 92
Adder
0.224
315778AD1-151 GEN
Solar/Wind Harmer
9.121
316382AG1-145 C
Solar/Wind Harmer
0.001
961611AG1-000B GEN
Solar/Wind Harmer
2.869
315813AE1-149 C
Solar/Wind Harmer
5.675
3151221GRAVEL6
Adder
7.614
3151171GRAVELC
Adder
1.465
3141766HARMONY
Solar/Wind Harmer
1.389
3141843SHACKLE
Adder
0.532
316203AE2-005 GEN
Solar/Wind Harmer
0
3144216WINCHST
Adder
0.39
3150921YORKTN3
Adder
2.595
970659AG2-427 GEN
Solar/Wind Harmer
1.091
316083AB2-161 GEN
Solar/Wind Harmer
0.001
316280AD1-041 GEN
Solar/Wind Harmer
0.002
971781AH1-399 GEN
Solar/Wind Harmer
0.134
970661AG2-428 GEN
Solar/Wind Harmer
2.133
3145336SMITFLD
Solar/Wind Harmer
0.04
316156AD2-030 GEN
Solar/Wind Harmer
0.074
3141873WAN 176
Solar/Wind Harmer
1.782
3144536CHRHLND
Solar/Wind Harmer
0.014
3144873MCLAUGH
Solar/Wind Harmer
0.002
3151101ELIZAR3
Adder
8.719
315773AC2-141 GEN
Solar/Wind Harmer
3.396
944581AF1-123 GEN
Solar/Wind Harmer
20.859
944601AF1-125 GEN
Solar/Wind Harmer
20.537
3146456SLIGO L269
Solar/Wind Harmer
0.092
971153AH1-033 GEN
Solar/Wind Harmer
1.063
316320Y1-086
Solar/Wind Harmer
0
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.089
3145273HOLLAND
Solar/Wind Harmer
0.067
3146626S HERTFORD
Solar/Wind Harmer
0.089
962971AG1-146 GEN
Solar/Wind Harmer
1.407
3146376EDENTON
Solar/Wind Harmer
0.086
970009AG2-005 GEN
Solar/Wind Harmer
0.636
315614AA2-178 GEN
Solar/Wind Harmer
0.482
971157AH1-035 GEN
Solar/Wind Harmer
0.988
315737AD1-076 GEN
Solar/Wind Harmer
1.055
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3146206CASHIE
Solar/Wind Harmer
0.081
972255AH1-712 GEN
Adder
41.371
316404AE1-155 C
Solar/Wind Harmer
0.018
3145893MURPHYS
Solar/Wind Harmer
0.134
3145893MURPHYS
Solar/Wind Harmer
0.08
957521AF2-046 GEN
Solar/Wind Harmer
5.958
961681AG1-008 GEN
Solar/Wind Harmer
5.958
316365GEN2_N
Solar/Wind Harmer
0.179
316313AB2-026
Solar/Wind Harmer
0.05
316258AE1-075 C
Solar/Wind Harmer
0.06
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
1.205
3146173TUNIS
Solar/Wind Harmer
0.079
3156021HOLLOMANSOL
Solar/Wind Harmer
0.36
316463AE2-346 GEN
Solar/Wind Harmer
0.068
316140AB2-099
Solar/Wind Harmer
0.028
962331AG1-082 GEN
Solar/Wind Harmer
0.841
3146263WOODLND
Solar/Wind Harmer
0.077
3145963POPLR C
Solar/Wind Harmer
0.077
3142666NORTHAMPTON
Solar/Wind Harmer
0.076
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.076
313506AB2-031 GEN
Solar/Wind Harmer
0.234
3145796HORNRTN
Solar/Wind Harmer
0.299
3145796HORNRTN
Solar/Wind Harmer
0.075
3145933PARMELE
Solar/Wind Harmer
0.073
966801AG1-551 GEN
Solar/Wind Harmer
0.851
3147043LAWRENC
Solar/Wind Harmer
0.044
316210AC1-098 GEN
Solar/Wind Harmer
0.674
3150351NORNECKC2
Adder
0.735
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
315724AD1-057 GEN
Solar/Wind Harmer
0.263
316327AA2-057 GEN
Solar/Wind Harmer
0.105
970917AG2-570 GEN
Solar/Wind Harmer
6.089
3146073TAR RVR
Solar/Wind Harmer
0.068
3146083TARBORO
Solar/Wind Harmer
0.068
3146233WITAKRS
Solar/Wind Harmer
0.341
3146233WITAKRS
Solar/Wind Harmer
0.046
3138543CONSLDL
Solar/Wind Harmer
0.045
961601AG1-000A GEN
Solar/Wind Harmer
4.729
3145543BTLEBRO
Solar/Wind Harmer
0.066
3145543BTLEBRO
Solar/Wind Harmer
0.066
971623AH1-311 GEN
Solar/Wind Harmer
0.133
316478AD1-087 GEN
Solar/Wind Harmer
0.225
316486AD2-202 GEN
Solar/Wind Harmer
0.066
316131AB2-060 GEN
Solar/Wind Harmer
0.2
964241AG1-285 GEN
Solar/Wind Harmer
4.22
315785AD2-033 C
Solar/Wind Harmer
0.511
970257AG2-171 GEN
Solar/Wind Harmer
2.007
959311AF2-222 GEN
Solar/Wind Harmer
5.564
970909AG2-566 GEN
Solar/Wind Harmer
0.665
963181AG1-167 GEN
Solar/Wind Harmer
0.248
3144293JTRSVLE
Adder
0.197
3147133PAMPLIN
Solar/Wind Harmer
0.193
971193AH1-056 GEN
Solar/Wind Harmer
3.754
942461AE2-259 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.036
3146776BUCKING
Solar/Wind Harmer
0.021
316248AF1-058 C
Solar/Wind Harmer
0
960061AF2-297 GEN
Solar/Wind Harmer
2.45
315052AA1-145 CT2
50/50
2.93
966881AG1-559 GEN
Solar/Wind Harmer
0.767
3142416OLDCHRC
Solar/Wind Harmer
0.42
3142416OLDCHRC
Solar/Wind Harmer
0.161
3143096IRON208
Adder
0.565
3142543TWELFTH
Solar/Wind Harmer
0.013
944631AF1-128 GEN
Adder
61.065
3150851SPRUNCC
Adder
0.59
315671AE2-027_GEN
Solar/Wind Harmer
7.592
970129AG2-093 GEN
Solar/Wind Harmer
3.33
316458AB2-190 GEN2
Solar/Wind Harmer
0.626
3142433PROV 92
Solar/Wind Harmer
0.461
3142433PROV 92
Adder
0.224
3142433PROV 92
Adder
0.224
971069AG2-661 GEN
Solar/Wind Harmer
2.027
3143526WINTERP
Solar/Wind Harmer
0.585
316159AE1-175 C
Solar/Wind Harmer
0.096
971647AH1-324 GEN
Solar/Wind Harmer
4.69
961611AG1-000B GEN
Solar/Wind Harmer
5.643
3151171GRAVELC
Adder
1.114
971317AH1-138 GEN
Solar/Wind Harmer
0.779
3141766HARMONY
Solar/Wind Harmer
0.021
971777AH1-397 GEN
Solar/Wind Harmer
0.275
3141843SHACKLE
Adder
0.532
3138126ROCKLANDING
Solar/Wind Harmer
0.047
970659AG2-427 GEN
Solar/Wind Harmer
4.989
316381AD1-082 GEN
Solar/Wind Harmer
0.107
970661AG2-428 GEN
Solar/Wind Harmer
10.027
3145336SMITFLD
Solar/Wind Harmer
0.402
3143226MDLTHAN
Solar/Wind Harmer
0.096
316072AD1-144
Solar/Wind Harmer
0.034
3138133OCRAN
Solar/Wind Harmer
0.057
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
1.175
316294AC1-161 GEN
Solar/Wind Harmer
1.611
316093AE2-104_GEN
Solar/Wind Harmer
1.559
944591AF1-124 GEN
Solar/Wind Harmer
20.933
316388AE2-253 GEN
Solar/Wind Harmer
0.289
316246AF1-032 C
Solar/Wind Harmer
0.042
3146456SLIGO L269
Solar/Wind Harmer
0.092
3146516WINFALL
Solar/Wind Harmer
0.29
3146516WINFALL
Solar/Wind Harmer
0.089
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.086
3145663CRESWEL
Solar/Wind Harmer
0.235
971163AH1-040 GEN
Solar/Wind Harmer
6.732
962861AG1-135 GEN
Solar/Wind Harmer
2.618
939411AE1-173 GEN
Solar/Wind Harmer
34.828
3146206CASHIE
Solar/Wind Harmer
0.081
971547AH1-271 GEN
Solar/Wind Harmer
1.726
972277AH1-723 GEN
Adder
48.21
3145893MURPHYS
Solar/Wind Harmer
0.321
3145893MURPHYS
Solar/Wind Harmer
0.357
316023GEN1_S
Solar/Wind Harmer
0.179
3143336POWHATN
Solar/Wind Harmer
1.418
3146173TUNIS
Solar/Wind Harmer
0.079
3145683EARLEYS
Solar/Wind Harmer
0.078
940641AE2-051 GEN
Solar/Wind Harmer
6.235
3146263WOODLND
Solar/Wind Harmer
0.077
3141726DUNNSVL
Solar/Wind Harmer
0.309
3145963POPLR C
Solar/Wind Harmer
0.077
960081AF2-299 GEN
Solar/Wind Harmer
0.737
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3145823KELFORD
Solar/Wind Harmer
0.076
316011AB1-132 GEN
Solar/Wind Harmer
1.384
962571AG1-106 GEN
Solar/Wind Harmer
1.083
316336AC2-165 C
Solar/Wind Harmer
0.003
316190AA2-174 GEN
Solar/Wind Harmer
0
3145796HORNRTN
Solar/Wind Harmer
0.247
3145796HORNRTN
Solar/Wind Harmer
0.075
3145783HORNRTN
Solar/Wind Harmer
0.074
971795AH1-408 GEN
Solar/Wind Harmer
4.936
3146293MARTNCO
Solar/Wind Harmer
0.068
3147043LAWRENC
Adder
0.658
316212AC1-099_GEN
Solar/Wind Harmer
0.376
3150351NORNECKC2
Adder
0.723
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
315722AD1-056 GEN
Solar/Wind Harmer
0.444
316494AC1-189 GEN
Solar/Wind Harmer
0.235
970919AG2-571 GEN
Solar/Wind Harmer
2.436
970087AG2-069 GEN
Solar/Wind Harmer
5.462
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.068
3145493TOT1
Solar/Wind Harmer
0.303
316129AC1-054 GEN
Solar/Wind Harmer
0.256
3146233WITAKRS
Solar/Wind Harmer
0.27
971065AG2-659 GEN
Solar/Wind Harmer
2.88
316359AB2-059 GEN
Solar/Wind Harmer
0.239
316049AB1-081 GEN
Solar/Wind Harmer
0.38
3145543BTLEBRO
Solar/Wind Harmer
0.066
3145543BTLEBRO
Solar/Wind Harmer
0.053
3142053HEARTS
Solar/Wind Harmer
0.117
957481AF2-042 GEN
Solar/Wind Harmer
17.703
315693AD1-088 GEN
Solar/Wind Harmer
3.143
962491AG1-098 GEN
Solar/Wind Harmer
3.727
970937AG2-583 GEN
Solar/Wind Harmer
3.946
316237AB2-079_GEN
Solar/Wind Harmer
0.001
970685AG2-442 GEN
Solar/Wind Harmer
4.652
963171AG1-166 GEN
Solar/Wind Harmer
0.33
971563AH1-280 GEN
Solar/Wind Harmer
0.661
3144293JTRSVLE
Adder
0.197
315687AD1-152 GEN
Solar/Wind Harmer
0.002
3146926FARMVIL
Solar/Wind Harmer
0.036
970401AG2-262 GEN
Solar/Wind Harmer
0.352
316337AD2-073 GEN
Solar/Wind Harmer
0.051
316322AB2-045
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
0.023
NYPJM->LTFIMP_NY
CLTF
1.306
LGEELTFEXP_LGEE->PJM
CLTF
0.633
WECLTFEXP_WEC->PJM
CLTF
0.314
LAGNLTFEXP_LAGN->PJM
CLTF
3.259
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.253
TVALTFEXP_TVA->PJM
CLTF
1.654
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.836
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.715
MECLTFEXP_MEC->PJM
CLTF
1.658
SIGELTFEXP_SIGE->PJM
CLTF
0.051
CPLELTFEXP_CPLE->PJM
CLTF
4.134
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.574

Details for AE1-157 TAP-6LDYSMITH CT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AE1-157 TAP-6LDYSMITH CT 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.09 %
Rating:1809.0 MVA
Rating Type:C
MVA to Mitigate:2172.49
MW Contribution:43.25
Bus #Bus NameTypeMW Contribution
315052AA1-145 CT2
50/50
3.022
966881AG1-559 GEN
Solar/Wind Harmer
0.775
3142416OLDCHRC
Solar/Wind Harmer
-0.05
3142416OLDCHRC
Solar/Wind Harmer
-0.019
3143096IRON208
Adder
0.592
3142543TWELFTH
Solar/Wind Harmer
-0.002
3150851SPRUNCC
Adder
0.623
944631AF1-128 GEN
Adder
63.31
315671AE2-027_GEN
Solar/Wind Harmer
10.43
970129AG2-093 GEN
Solar/Wind Harmer
3.098
316458AB2-190 GEN2
Solar/Wind Harmer
1.368
3143526WINTERP
Solar/Wind Harmer
-0.069
3142433PROV 92
Solar/Wind Harmer
-0.053
3142433PROV 92
Adder
0.231
3142433PROV 92
Adder
0.231
971069AG2-661 GEN
Solar/Wind Harmer
2.086
971647AH1-324 GEN
Solar/Wind Harmer
6.322
316159AE1-175 C
Solar/Wind Harmer
0.337
961611AG1-000B GEN
Solar/Wind Harmer
6.091
3151171GRAVELC
Adder
1.133
971777AH1-397 GEN
Solar/Wind Harmer
1.405
3141843SHACKLE
Adder
0.543
3141766HARMONY
Solar/Wind Harmer
-0.002
970659AG2-427 GEN
Solar/Wind Harmer
6.325
316381AD1-082 GEN
Solar/Wind Harmer
1.084
971317AH1-138 GEN
Solar/Wind Harmer
1.473
3138126ROCKLANDING
Solar/Wind Harmer
0.036
970661AG2-428 GEN
Solar/Wind Harmer
12.312
3143226MDLTHAN
Solar/Wind Harmer
-0.011
3145336SMITFLD
Solar/Wind Harmer
-0.046
3138133OCRAN
Solar/Wind Harmer
-0.006
316072AD1-144
Solar/Wind Harmer
0.217
316375AC2-012 GEN
Solar/Wind Harmer
3.67
3150981CHESPKA
Adder
1.178
316093AE2-104_GEN
Solar/Wind Harmer
3.051
944591AF1-124 GEN
Solar/Wind Harmer
47.558
316246AF1-032 C
Solar/Wind Harmer
0.211
316388AE2-253 GEN
Solar/Wind Harmer
0.701
316294AC1-161 GEN
Solar/Wind Harmer
3.361
3146456SLIGO L269
Solar/Wind Harmer
-0.01
3146516WINFALL
Solar/Wind Harmer
-0.033
3146516WINFALL
Solar/Wind Harmer
-0.01
315800Z1-036_GEN1
Solar/Wind Harmer
2.45
961951AG1-038 GEN
Solar/Wind Harmer
1.29
3130156CHOWAN
Solar/Wind Harmer
-0.01
3145663CRESWEL
Solar/Wind Harmer
-0.026
971163AH1-040 GEN
Solar/Wind Harmer
8.915
962861AG1-135 GEN
Solar/Wind Harmer
3.534
3143336POWHATN
Solar/Wind Harmer
1.113
939411AE1-173 GEN
Solar/Wind Harmer
46.267
316023GEN1_S
Solar/Wind Harmer
0.618
3146206CASHIE
Solar/Wind Harmer
-0.009
971547AH1-271 GEN
Solar/Wind Harmer
2.289
3145893MURPHYS
Solar/Wind Harmer
-0.036
3145893MURPHYS
Solar/Wind Harmer
0.27
3146173TUNIS
Solar/Wind Harmer
-0.009
964211AG1-282 GEN
Solar/Wind Harmer
0.269
3141726DUNNSVL
Solar/Wind Harmer
-0.036
3145683EARLEYS
Solar/Wind Harmer
-0.009
940641AE2-051 GEN
Solar/Wind Harmer
8.306
316336AC2-165 C
Solar/Wind Harmer
1.534
3146263WOODLND
Solar/Wind Harmer
-0.009
960081AF2-299 GEN
Solar/Wind Harmer
0.987
3145963POPLR C
Solar/Wind Harmer
-0.009
316011AB1-132 GEN
Solar/Wind Harmer
1.817
962571AG1-106 GEN
Solar/Wind Harmer
1.248
3145823KELFORD
Solar/Wind Harmer
-0.009
316174AB2-169 GEN
Solar/Wind Harmer
1.333
316190AA2-174 GEN
Solar/Wind Harmer
0.105
3145796HORNRTN
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.008
971795AH1-408 GEN
Solar/Wind Harmer
6.339
3145783HORNRTN
Solar/Wind Harmer
-0.008
3150351NORNECKC2
Adder
0.745
3147043LAWRENC
Adder
0.669
3146293MARTNCO
Solar/Wind Harmer
0.051
316212AC1-099_GEN
Solar/Wind Harmer
0.719
972277AH1-723 GEN
Adder
43.254
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
315722AD1-056 GEN
Solar/Wind Harmer
0.834
316494AC1-189 GEN
Solar/Wind Harmer
0.848
970919AG2-571 GEN
Solar/Wind Harmer
2.47
970087AG2-069 GEN
Solar/Wind Harmer
7.293
316129AC1-054 GEN
Solar/Wind Harmer
0.678
961671AG1-007 GEN
Solar/Wind Harmer
0.098
3146083TARBORO
Solar/Wind Harmer
-0.008
3145493TOT1
Solar/Wind Harmer
0.229
3146233WITAKRS
Solar/Wind Harmer
-0.03
971065AG2-659 GEN
Solar/Wind Harmer
3.835
3144293JTRSVLE
Adder
0.199
957481AF2-042 GEN
Solar/Wind Harmer
19.562
3142296MT RD221
50/50
0.652
3142366NRTHEST
50/50
0.558
3150691DARBY 3
50/50
11.988
3150701DARBY 4
50/50
11.96
3150681DARBY 2
50/50
11.946
315673AE1-157 GEN
Solar/Wind Harmer
64.401
957411AF2-035 GEN
Solar/Wind Harmer
33.919
970317AG2-208 GEN
Solar/Wind Harmer
32.977
966871AG1-558 GEN
Solar/Wind Harmer
0.588
966871AG1-558 GEN
Solar/Wind Harmer
0.201
3150671DARBY 1
Adder
11.244
316075AC2-137 C
Solar/Wind Harmer
0.43
944641AF1-129 GEN
Adder
62.735
3142946ENON
Solar/Wind Harmer
-0.002
316240AF1-291 C
Solar/Wind Harmer
0.437
3143526WINTERP
Solar/Wind Harmer
-0.069
316033AB2-134 GEN
Solar/Wind Harmer
4.174
315697AD1-025 GEN
Solar/Wind Harmer
2.618
316468AD1-105 GEN
Solar/Wind Harmer
1.403
316441AF1-014 GEN
Solar/Wind Harmer
0.805
970657AG2-426 GEN
Solar/Wind Harmer
3.667
970657AG2-426 GEN
Solar/Wind Harmer
0.767
971223AH1-071 GEN
Solar/Wind Harmer
1.433
316236AE1-162_GEN
Solar/Wind Harmer
0.345
316036AC1-147 C
Solar/Wind Harmer
0.286
3150991CHESPKB
Adder
0.989
3150991CHESPKB
Adder
0.965
316316AC1-027 C
Solar/Wind Harmer
0.323
3142956BIRDNECK
Solar/Wind Harmer
0.565
316185AD1-033 GEN
Solar/Wind Harmer
1.104
3145506HICKORY
Solar/Wind Harmer
-0.042
3145506HICKORY
Solar/Wind Harmer
-0.025
3145506HICKORY
Solar/Wind Harmer
-0.006
316339AD2-160 GEN
Solar/Wind Harmer
0.701
316018AA1-139 ULT2
Solar/Wind Harmer
0.89
316017AA1-139 ULT1
Solar/Wind Harmer
0.84
3137176SLIGO L2192
Solar/Wind Harmer
-0.041
3146456SLIGO L269
Solar/Wind Harmer
1.224
3130086AYDLETT
Solar/Wind Harmer
-0.041
3146386ELIZ CT
Solar/Wind Harmer
-0.01
316431W1029_GEN1
Solar/Wind Harmer
1.837
316433W1029_GEN2
Solar/Wind Harmer
1.837
3144356SAPONY
Solar/Wind Harmer
0.353
3146516WINFALL
Solar/Wind Harmer
-0.01
3146516WINFALL
Solar/Wind Harmer
-0.01
3146516WINFALL
Solar/Wind Harmer
-0.01
3146626S HERTFORD
Solar/Wind Harmer
-0.01
3146626S HERTFORD
Solar/Wind Harmer
-0.01
315742AE1-103 GEN
Solar/Wind Harmer
1.039
316487AF1-042 GEN
Solar/Wind Harmer
1.29
3146376EDENTON
Solar/Wind Harmer
0.29
3146376EDENTON
Solar/Wind Harmer
0.29
958261AF2-120 GEN
Solar/Wind Harmer
3.6
316065AD1-022 GEN
Solar/Wind Harmer
4.599
3145893MURPHYS
Solar/Wind Harmer
0.254
3145893MURPHYS
Solar/Wind Harmer
-0.016
3146173TUNIS
Solar/Wind Harmer
-0.009
3146173TUNIS
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
316181AB2-040 GEN
Solar/Wind Harmer
1.206
316426AA2-053 GEN
Solar/Wind Harmer
0.866
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.957
3145593CAROLNA
Solar/Wind Harmer
0.071
3145783HORNRTN
Solar/Wind Harmer
1.003
3145783HORNRTN
Solar/Wind Harmer
0.802
3145783HORNRTN
Solar/Wind Harmer
0.251
3145783HORNRTN
Solar/Wind Harmer
0.1
316077AC2-138 C
Solar/Wind Harmer
0.177
3150341NORNECKC1
Adder
0.782
3150341NORNECKC1
Adder
0.776
3145933PARMELE
Solar/Wind Harmer
-0.016
3145933PARMELE
Solar/Wind Harmer
-0.008
316274AC1-208 GEN
Solar/Wind Harmer
0.88
972185AH1-677 GEN
Adder
4.053
972187AH1-678 GEN
Adder
2.037
970933AG2-581 GEN
Solar/Wind Harmer
7.449
3145493TOT1
Solar/Wind Harmer
0.12
3145453TOT5
Solar/Wind Harmer
0.072
3145603CNETO
Solar/Wind Harmer
0.048
3144293JTRSVLE
Adder
0.199
3144293JTRSVLE
Adder
0.168
970099AG2-077 GEN
Solar/Wind Harmer
7.825
972189AH1-679 GEN
50/50
6.745
316312AB1-027
Solar/Wind Harmer
0.646
971285AH1-108 GEN
Adder
1.02
315976AC1-164 GENA
Solar/Wind Harmer
15.264
316169AC1-164_GENC
Solar/Wind Harmer
13.187
315975AC1-164 GENB
Solar/Wind Harmer
0.452
971167AH1-042 GEN
Solar/Wind Harmer
13.036
316132AB2-190 GEN1
Solar/Wind Harmer
1.368
316233AE1-074 FULL
Solar/Wind Harmer
0.36
971281AH1-106 GEN
Solar/Wind Harmer
2.178
971283AH1-107 GEN
Solar/Wind Harmer
2.178
3142433PROV 92
Adder
0.231
3142433PROV 92
Adder
0.231
316369SG1_INVT
Solar/Wind Harmer
2.313
3143873LANEXA
Solar/Wind Harmer
-0.007
316314AB2-024 C
Solar/Wind Harmer
1.044
3143316POE
Solar/Wind Harmer
-0.048
972265AH1-717 GEN
Adder
8.267
3151201GRAVEL4
Adder
7.75
3151191GRAVEL3
Adder
7.652
3151211GRAVEL5
Adder
7.652
316059AD1-063 C
Solar/Wind Harmer
0.27
315662AE1-191 GEN
Solar/Wind Harmer
1.416
315666AE1-190 GEN
Solar/Wind Harmer
0.354
957831AF2-077 GEN
Solar/Wind Harmer
0.348
3138283WHITEMARSH
Solar/Wind Harmer
0.018
971445AH1-216 GEN
Solar/Wind Harmer
7.11
957601AF2-054 GEN
Solar/Wind Harmer
0.343
3141873WAN 176
Solar/Wind Harmer
-0.002
3141913WHIT STONE
Solar/Wind Harmer
-0.011
315833AF1-017_GEN
Solar/Wind Harmer
2.09
316349AD2-085 GEN
Solar/Wind Harmer
0.979
316311AC2-079 GEN
Solar/Wind Harmer
5.546
3138133OCRAN
Solar/Wind Harmer
-0.003
3141783LANCAST
Solar/Wind Harmer
-0.006
3141783LANCAST
Solar/Wind Harmer
-0.004
3152611GOSPORTB
Adder
1.202
3152621GOSPORTC
Adder
1.02
3152601GOSPORTA
Adder
0.941
3151081ELIZAR1
Adder
8.634
3151091ELIZAR2
Adder
8.484
315835AF2-110_GEN
Solar/Wind Harmer
1.312
316305AF2-043 C
Solar/Wind Harmer
0.314
957871AF2-081 GEN
Solar/Wind Harmer
5.192
319010AE1-072 C
Solar/Wind Harmer
2.094
3146406KITTY HAWK
Solar/Wind Harmer
0.009
313526AB2-022
Solar/Wind Harmer
0.276
3146486SUNBURY
Solar/Wind Harmer
-0.01
3146486SUNBURY
Solar/Wind Harmer
-0.01
316321Z2-027
Solar/Wind Harmer
0.275
3145176PASQUOTANK
Solar/Wind Harmer
-0.006
3146396TANGLEW
Solar/Wind Harmer
0.188
316315AB2-025 C
Solar/Wind Harmer
0.273
962981AG1-147 GEN
Solar/Wind Harmer
4.42
315814AE2-033 C
Solar/Wind Harmer
9.389
315611Z1-036_GEN2
Solar/Wind Harmer
2.45
3130156CHOWAN
Solar/Wind Harmer
-0.01
3130156CHOWAN
Solar/Wind Harmer
-0.01
315816AE2-034 GEN
Solar/Wind Harmer
0.769
3130546PLYMOUTH
Solar/Wind Harmer
-0.009
315732AD1-074 GEN1
Solar/Wind Harmer
1.875
315733AD1-074 GEN2
Solar/Wind Harmer
1.875
315735AD1-075 GEN1
Solar/Wind Harmer
0.938
965291AG1-394 GEN
Solar/Wind Harmer
0.819
3146206CASHIE
Solar/Wind Harmer
-0.009
970601AG2-382 GEN
Solar/Wind Harmer
4.006
316318V4-068
Solar/Wind Harmer
0.227
3145893MURPHYS
Solar/Wind Harmer
-0.024
3145893MURPHYS
Solar/Wind Harmer
-0.009
3145513AHOSKIE
Solar/Wind Harmer
0.078
961941AG1-037 GEN
Solar/Wind Harmer
0.067
3145513AHOSKIE
Solar/Wind Harmer
-0.009
3145683EARLEYS
Solar/Wind Harmer
-0.018
3145683EARLEYS
Solar/Wind Harmer
-0.009
3145683EARLEYS
Solar/Wind Harmer
-0.009
3146043SEABORD
Solar/Wind Harmer
-0.009
315607AA1-063A GEN
Solar/Wind Harmer
0.888
946281AF1-292 GEN
Solar/Wind Harmer
0.197
316087AB2-174 GEN
Solar/Wind Harmer
1.239
315652AC1-086 GEN
Solar/Wind Harmer
9.768
3137643SOCKMAN
Solar/Wind Harmer
-0.034
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.034
3141813NORNECK
Solar/Wind Harmer
-0.008
941031AE2-094 GEN
Solar/Wind Harmer
15.534
944011AF1-069 GEN
Solar/Wind Harmer
4.867
970673AG2-436 GEN
Solar/Wind Harmer
17.166
970673AG2-436 GEN
Solar/Wind Harmer
8.692
972193AH1-681 GEN
Adder
1.658
971967AH1-528 GEN
Solar/Wind Harmer
15.218
316005AA1-067
Solar/Wind Harmer
0.163
3145746EVERETS
Solar/Wind Harmer
-0.032
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
970181AG2-120 GEN
Solar/Wind Harmer
1.057
957861AF2-080 GEN
Solar/Wind Harmer
3.447
970831AG2-522 GEN
Solar/Wind Harmer
3.906
316420AA1-050 GEN
Solar/Wind Harmer
0.89
970085AG2-068 GEN
Solar/Wind Harmer
4.862
970581AG2-369 GEN
Solar/Wind Harmer
4.181
3145573BETHELC
Solar/Wind Harmer
-0.008
3145573BETHELC
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.426
3141426STAFORD
Solar/Wind Helper
0.035
315051AA1-145 CT1
50/50
3.009
971645AH1-323 GEN
50/50
18.069
966881AG1-559 GEN
Solar/Wind Harmer
2.266
316473AC1-191 GEN
Solar/Wind Harmer
2.105
3142416OLDCHRC
Solar/Wind Harmer
1.933
970293AG2-193 GEN
Solar/Wind Harmer
2.103
3143096IRON208
Adder
0.592
3143096IRON208
Adder
0.58
3150861SPRUNCD
Adder
0.623
3142946ENON
Solar/Wind Harmer
-0.005
970133AG2-095 GEN
Solar/Wind Harmer
1.592
965281AG1-393 GEN
Solar/Wind Harmer
1.712
315839AE2-212 C
Solar/Wind Harmer
0.411
970129AG2-093 GEN
Solar/Wind Harmer
7.649
3142433PROV 92
Adder
0.231
3142433PROV 92
Adder
0.231
315778AD1-151 GEN
Solar/Wind Harmer
11.42
971781AH1-399 GEN
Solar/Wind Harmer
0.776
316382AG1-145 C
Solar/Wind Harmer
0.379
315813AE1-149 C
Solar/Wind Harmer
7.713
961611AG1-000B GEN
Solar/Wind Harmer
2.599
3151221GRAVEL6
Adder
7.741
3151171GRAVELC
Adder
1.489
3141843SHACKLE
Adder
0.543
316203AE2-005 GEN
Solar/Wind Harmer
5.036
3141766HARMONY
Solar/Wind Harmer
1.062
970659AG2-427 GEN
Solar/Wind Harmer
1.121
316083AB2-161 GEN
Solar/Wind Harmer
1.919
316280AD1-041 GEN
Solar/Wind Harmer
0.885
3144216WINCHST
Adder
0.393
3150921YORKTN3
Adder
2.606
970661AG2-428 GEN
Solar/Wind Harmer
2.182
316156AD2-030 GEN
Solar/Wind Harmer
0.306
3141873WAN 176
Solar/Wind Harmer
1.362
3145336SMITFLD
Solar/Wind Harmer
-0.005
3144536CHRHLND
Solar/Wind Harmer
-0.002
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
8.744
944581AF1-123 GEN
Solar/Wind Harmer
47.387
944601AF1-125 GEN
Solar/Wind Harmer
46.647
315773AC2-141 GEN
Solar/Wind Harmer
4.348
3146456SLIGO L269
Solar/Wind Harmer
-0.01
971153AH1-033 GEN
Solar/Wind Harmer
1.263
316320Y1-086
Solar/Wind Harmer
0.6
316435W1029_GEN3
Solar/Wind Harmer
1.837
3145273HOLLAND
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.01
962971AG1-146 GEN
Solar/Wind Harmer
1.894
3146626S HERTFORD
Solar/Wind Harmer
-0.01
316484AD2-074 GEN
Solar/Wind Harmer
2.465
970009AG2-005 GEN
Solar/Wind Harmer
1.224
3146376EDENTON
Solar/Wind Harmer
-0.01
315614AA2-178 GEN
Solar/Wind Harmer
1.026
316313AB2-026
Solar/Wind Harmer
0.253
316258AE1-075 C
Solar/Wind Harmer
0.228
316405AF2-144 C
Solar/Wind Harmer
0.24
3143336POWHATN
Solar/Wind Harmer
0.946
971157AH1-035 GEN
Solar/Wind Harmer
1.164
316404AE1-155 C
Solar/Wind Harmer
1.792
3156081AA2-088 GEN
Solar/Wind Harmer
3.013
315737AD1-076 GEN
Solar/Wind Harmer
1.762
316365GEN2_N
Solar/Wind Harmer
0.618
3146206CASHIE
Solar/Wind Harmer
-0.009
3145893MURPHYS
Solar/Wind Harmer
0.064
3145893MURPHYS
Solar/Wind Harmer
-0.009
957521AF2-046 GEN
Solar/Wind Harmer
7.153
961681AG1-008 GEN
Solar/Wind Harmer
7.153
3146173TUNIS
Solar/Wind Harmer
-0.009
3156021HOLLOMANSOL
Solar/Wind Harmer
1.211
316463AE2-346 GEN
Solar/Wind Harmer
0.145
316140AB2-099
Solar/Wind Harmer
0.06
962331AG1-082 GEN
Solar/Wind Harmer
1.118
3146263WOODLND
Solar/Wind Harmer
-0.009
966621AG1-532 GEN
Solar/Wind Harmer
0.178
3145963POPLR C
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
316317KELFORD C
Solar/Wind Harmer
0.408
3145823KELFORD
Solar/Wind Harmer
-0.009
313506AB2-031 GEN
Solar/Wind Harmer
0.695
3145796HORNRTN
Solar/Wind Harmer
-0.034
3145796HORNRTN
Solar/Wind Harmer
-0.008
3150351NORNECKC2
Adder
0.757
3147043LAWRENC
Solar/Wind Harmer
-0.005
3145933PARMELE
Solar/Wind Harmer
-0.008
966801AG1-551 GEN
Solar/Wind Harmer
1.034
316210AC1-098 GEN
Solar/Wind Harmer
1.294
972255AH1-712 GEN
Adder
37.118
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
315724AD1-057 GEN
Solar/Wind Harmer
0.459
316327AA2-057 GEN
Solar/Wind Harmer
0.796
970917AG2-570 GEN
Solar/Wind Harmer
19.512
3146073TAR RVR
Solar/Wind Harmer
-0.008
3146083TARBORO
Solar/Wind Harmer
-0.008
3146233WITAKRS
Solar/Wind Harmer
0.161
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3144293JTRSVLE
Adder
0.199
NYPJM->LTFIMP_NY
CLTF
1.288
LGEELTFEXP_LGEE->PJM
CLTF
0.601
WECLTFEXP_WEC->PJM
CLTF
0.297
LAGNLTFEXP_LAGN->PJM
CLTF
3.178
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.209
TVALTFEXP_TVA->PJM
CLTF
1.611
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.206
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.551
MECLTFEXP_MEC->PJM
CLTF
1.584
SIGELTFEXP_SIGE->PJM
CLTF
0.049
CPLELTFEXP_CPLE->PJM
CLTF
4.142
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.001

Details for AE1-157 TAP-6LDYSMITH CT 230.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AE1-157 TAP-6LDYSMITH CT 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 557T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.2 %
Rating:1809.0 MVA
Rating Type:C
MVA to Mitigate:2156.3
MW Contribution:53.78
Bus #Bus NameTypeMW Contribution
315052AA1-145 CT2
50/50
2.956
966881AG1-559 GEN
Solar/Wind Harmer
0.768
3142416OLDCHRC
Solar/Wind Harmer
-0.046
3142416OLDCHRC
Solar/Wind Harmer
-0.018
3142543TWELFTH
Solar/Wind Harmer
-0.001
3143096IRON208
Adder
0.549
3150851SPRUNCC
Adder
0.581
944631AF1-128 GEN
Adder
58.155
315671AE2-027_GEN
Solar/Wind Harmer
9.626
3143526WINTERP
Solar/Wind Harmer
-0.065
970129AG2-093 GEN
Solar/Wind Harmer
2.835
316458AB2-190 GEN2
Solar/Wind Harmer
1.251
3142433PROV 92
Solar/Wind Harmer
-0.048
3142433PROV 92
Adder
0.21
3142433PROV 92
Adder
0.21
971069AG2-661 GEN
Solar/Wind Harmer
1.902
971647AH1-324 GEN
Solar/Wind Harmer
5.736
316159AE1-175 C
Solar/Wind Harmer
0.302
961611AG1-000B GEN
Solar/Wind Harmer
5.51
970659AG2-427 GEN
Solar/Wind Harmer
5.753
3151171GRAVELC
Adder
1.021
316381AD1-082 GEN
Solar/Wind Harmer
0.985
971777AH1-397 GEN
Solar/Wind Harmer
1.257
3141843SHACKLE
Adder
0.486
3143226MDLTHAN
Solar/Wind Harmer
-0.011
3141766HARMONY
Solar/Wind Harmer
-0.002
970661AG2-428 GEN
Solar/Wind Harmer
11.16
971317AH1-138 GEN
Solar/Wind Harmer
1.309
3138126ROCKLANDING
Solar/Wind Harmer
0.032
3145336SMITFLD
Solar/Wind Harmer
-0.041
972277AH1-723 GEN
Adder
53.776
3138133OCRAN
Solar/Wind Harmer
-0.006
316072AD1-144
Solar/Wind Harmer
0.194
316375AC2-012 GEN
Solar/Wind Harmer
3.263
3150981CHESPKA
Adder
1.048
316093AE2-104_GEN
Solar/Wind Harmer
2.727
316246AF1-032 C
Solar/Wind Harmer
0.188
944591AF1-124 GEN
Solar/Wind Harmer
42.182
316388AE2-253 GEN
Solar/Wind Harmer
0.623
3146456SLIGO L269
Solar/Wind Harmer
-0.009
316294AC1-161 GEN
Solar/Wind Harmer
2.962
3146516WINFALL
Solar/Wind Harmer
-0.029
3146516WINFALL
Solar/Wind Harmer
-0.009
3143336POWHATN
Solar/Wind Harmer
1.053
315800Z1-036_GEN1
Solar/Wind Harmer
2.188
3130156CHOWAN
Solar/Wind Harmer
-0.009
961951AG1-038 GEN
Solar/Wind Harmer
1.133
3145663CRESWEL
Solar/Wind Harmer
-0.024
971163AH1-040 GEN
Solar/Wind Harmer
7.992
316336AC2-165 C
Solar/Wind Harmer
1.46
316023GEN1_S
Solar/Wind Harmer
0.562
962861AG1-135 GEN
Solar/Wind Harmer
3.092
3146206CASHIE
Solar/Wind Harmer
-0.008
971547AH1-271 GEN
Solar/Wind Harmer
2.059
939411AE1-173 GEN
Solar/Wind Harmer
41.157
3145893MURPHYS
Solar/Wind Harmer
-0.033
3145893MURPHYS
Solar/Wind Harmer
0.244
3146173TUNIS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
960081AF2-299 GEN
Solar/Wind Harmer
0.899
3146263WOODLND
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.651
962571AG1-106 GEN
Solar/Wind Harmer
1.134
940641AE2-051 GEN
Solar/Wind Harmer
7.394
3145963POPLR C
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
316174AB2-169 GEN
Solar/Wind Harmer
1.203
316190AA2-174 GEN
Solar/Wind Harmer
0.096
964211AG1-282 GEN
Solar/Wind Harmer
0.234
3141726DUNNSVL
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.008
971795AH1-408 GEN
Solar/Wind Harmer
5.789
3145783HORNRTN
Solar/Wind Harmer
-0.008
3147043LAWRENC
Adder
0.611
3146293MARTNCO
Solar/Wind Harmer
0.046
316212AC1-099_GEN
Solar/Wind Harmer
0.653
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.76
3150351NORNECKC2
Adder
0.644
970937AG2-583 GEN
Solar/Wind Harmer
5.173
316494AC1-189 GEN
Solar/Wind Harmer
0.771
316129AC1-054 GEN
Solar/Wind Harmer
0.621
961671AG1-007 GEN
Solar/Wind Harmer
0.089
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.209
3146233WITAKRS
Solar/Wind Harmer
-0.028
970919AG2-571 GEN
Solar/Wind Harmer
2.225
971065AG2-659 GEN
Solar/Wind Harmer
3.511
970087AG2-069 GEN
Solar/Wind Harmer
6.571
316359AB2-059 GEN
Solar/Wind Harmer
0.928
316049AB1-081 GEN
Solar/Wind Harmer
0.743
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
3142053HEARTS
Solar/Wind Harmer
0.081
3144293JTRSVLE
Adder
0.187
957481AF2-042 GEN
Solar/Wind Harmer
6.85
3142296MT RD221
50/50
0.619
3142366NRTHEST
50/50
0.524
3150691DARBY 3
50/50
11.194
3150701DARBY 4
50/50
11.168
3150681DARBY 2
50/50
11.155
315673AE1-157 GEN
Solar/Wind Harmer
63.975
957411AF2-035 GEN
Solar/Wind Harmer
33.623
970317AG2-208 GEN
Solar/Wind Harmer
32.689
966871AG1-558 GEN
Solar/Wind Harmer
0.556
966871AG1-558 GEN
Solar/Wind Harmer
0.19
3150671DARBY 1
Adder
10.5
316075AC2-137 C
Solar/Wind Harmer
0.395
944641AF1-129 GEN
Adder
58.186
3142946ENON
Solar/Wind Harmer
-0.001
316240AF1-291 C
Solar/Wind Harmer
0.405
3143526WINTERP
Solar/Wind Harmer
-0.065
316033AB2-134 GEN
Solar/Wind Harmer
3.798
315697AD1-025 GEN
Solar/Wind Harmer
2.382
316468AD1-105 GEN
Solar/Wind Harmer
1.303
316441AF1-014 GEN
Solar/Wind Harmer
0.72
971223AH1-071 GEN
Solar/Wind Harmer
1.333
970657AG2-426 GEN
Solar/Wind Harmer
3.33
970657AG2-426 GEN
Solar/Wind Harmer
0.696
316236AE1-162_GEN
Solar/Wind Harmer
0.309
316036AC1-147 C
Solar/Wind Harmer
0.254
3150991CHESPKB
Adder
0.879
3150991CHESPKB
Adder
0.858
316316AC1-027 C
Solar/Wind Harmer
0.287
3142956BIRDNECK
Solar/Wind Harmer
0.502
316185AD1-033 GEN
Solar/Wind Harmer
0.981
3145506HICKORY
Solar/Wind Harmer
-0.037
3145506HICKORY
Solar/Wind Harmer
-0.022
3145506HICKORY
Solar/Wind Harmer
-0.006
316339AD2-160 GEN
Solar/Wind Harmer
0.623
316018AA1-139 ULT2
Solar/Wind Harmer
0.791
316017AA1-139 ULT1
Solar/Wind Harmer
0.747
3137176SLIGO L2192
Solar/Wind Harmer
-0.036
3144356SAPONY
Solar/Wind Harmer
0.321
3146456SLIGO L269
Solar/Wind Harmer
1.088
3130086AYDLETT
Solar/Wind Harmer
-0.037
3146386ELIZ CT
Solar/Wind Harmer
-0.009
316431W1029_GEN1
Solar/Wind Harmer
1.638
316433W1029_GEN2
Solar/Wind Harmer
1.638
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
315742AE1-103 GEN
Solar/Wind Harmer
0.933
3146376EDENTON
Solar/Wind Harmer
0.259
3146376EDENTON
Solar/Wind Harmer
0.259
316487AF1-042 GEN
Solar/Wind Harmer
1.133
316065AD1-022 GEN
Solar/Wind Harmer
4.136
3145893MURPHYS
Solar/Wind Harmer
0.23
3145893MURPHYS
Solar/Wind Harmer
-0.015
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
958261AF2-120 GEN
Solar/Wind Harmer
3.146
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
316181AB2-040 GEN
Solar/Wind Harmer
1.098
316426AA2-053 GEN
Solar/Wind Harmer
0.786
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.87
3145593CAROLNA
Solar/Wind Harmer
0.064
3145783HORNRTN
Solar/Wind Harmer
0.911
3145783HORNRTN
Solar/Wind Harmer
0.729
3145783HORNRTN
Solar/Wind Harmer
0.228
3145783HORNRTN
Solar/Wind Harmer
0.091
3145933PARMELE
Solar/Wind Harmer
-0.015
3145933PARMELE
Solar/Wind Harmer
-0.007
316274AC1-208 GEN
Solar/Wind Harmer
0.801
972185AH1-677 GEN
Adder
3.637
316077AC2-138 C
Solar/Wind Harmer
0.153
3150341NORNECKC1
Adder
0.676
3150341NORNECKC1
Adder
0.671
972187AH1-678 GEN
Adder
1.83
970933AG2-581 GEN
Solar/Wind Harmer
6.716
3145493TOT1
Solar/Wind Harmer
0.109
3145453TOT5
Solar/Wind Harmer
0.065
3145603CNETO
Solar/Wind Harmer
0.044
961601AG1-000A GEN
Solar/Wind Harmer
2.709
316263AC1-034 GEN
Solar/Wind Harmer
3.226
3144293JTRSVLE
Adder
0.187
3144293JTRSVLE
Adder
0.157
970099AG2-077 GEN
Solar/Wind Harmer
2.74
972189AH1-679 GEN
50/50
6.597
316312AB1-027
Solar/Wind Harmer
0.605
971285AH1-108 GEN
Adder
0.951
315976AC1-164 GENA
Solar/Wind Harmer
13.809
316169AC1-164_GENC
Solar/Wind Harmer
11.929
315975AC1-164 GENB
Solar/Wind Harmer
0.409
316233AE1-074 FULL
Solar/Wind Harmer
0.336
971281AH1-106 GEN
Solar/Wind Harmer
2.031
971283AH1-107 GEN
Solar/Wind Harmer
2.031
316132AB2-190 GEN1
Solar/Wind Harmer
1.251
971167AH1-042 GEN
Solar/Wind Harmer
11.862
3142433PROV 92
Adder
0.21
3142433PROV 92
Adder
0.21
316369SG1_INVT
Solar/Wind Harmer
2.104
3143873LANEXA
Solar/Wind Harmer
-0.007
3143316POE
Solar/Wind Harmer
-0.044
316314AB2-024 C
Solar/Wind Harmer
0.933
972265AH1-717 GEN
Adder
7.449
3151201GRAVEL4
Adder
6.983
3151191GRAVEL3
Adder
6.894
3151211GRAVEL5
Adder
6.894
316059AD1-063 C
Solar/Wind Harmer
0.241
315662AE1-191 GEN
Solar/Wind Harmer
1.264
315666AE1-190 GEN
Solar/Wind Harmer
0.316
971445AH1-216 GEN
Solar/Wind Harmer
6.379
957831AF2-077 GEN
Solar/Wind Harmer
0.309
3138283WHITEMARSH
Solar/Wind Harmer
0.016
957601AF2-054 GEN
Solar/Wind Harmer
0.306
3141873WAN 176
Solar/Wind Harmer
-0.002
972193AH1-681 GEN
Adder
2.062
315833AF1-017_GEN
Solar/Wind Harmer
1.881
316349AD2-085 GEN
Solar/Wind Harmer
0.881
316311AC2-079 GEN
Solar/Wind Harmer
4.991
3141913WHIT STONE
Solar/Wind Harmer
-0.01
3138133OCRAN
Solar/Wind Harmer
-0.003
3152611GOSPORTB
Adder
1.069
3152621GOSPORTC
Adder
0.907
3152601GOSPORTA
Adder
0.837
3141783LANCAST
Solar/Wind Harmer
-0.006
3141783LANCAST
Solar/Wind Harmer
-0.004
3151081ELIZAR1
Adder
7.676
3151091ELIZAR2
Adder
7.542
315835AF2-110_GEN
Solar/Wind Harmer
1.172
316305AF2-043 C
Solar/Wind Harmer
0.279
957871AF2-081 GEN
Solar/Wind Harmer
4.617
316315AB2-025 C
Solar/Wind Harmer
0.249
319010AE1-072 C
Solar/Wind Harmer
1.863
3146406KITTY HAWK
Solar/Wind Harmer
0.008
315814AE2-033 C
Solar/Wind Harmer
8.538
3146486SUNBURY
Solar/Wind Harmer
-0.009
3146486SUNBURY
Solar/Wind Harmer
-0.009
313526AB2-022
Solar/Wind Harmer
0.246
316321Z2-027
Solar/Wind Harmer
0.245
3146396TANGLEW
Solar/Wind Harmer
0.167
3145176PASQUOTANK
Solar/Wind Harmer
-0.006
962981AG1-147 GEN
Solar/Wind Harmer
3.893
315611Z1-036_GEN2
Solar/Wind Harmer
2.188
3130156CHOWAN
Solar/Wind Harmer
-0.009
3130156CHOWAN
Solar/Wind Harmer
-0.009
315816AE2-034 GEN
Solar/Wind Harmer
0.69
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315732AD1-074 GEN1
Solar/Wind Harmer
1.685
315733AD1-074 GEN2
Solar/Wind Harmer
1.685
315735AD1-075 GEN1
Solar/Wind Harmer
0.843
965291AG1-394 GEN
Solar/Wind Harmer
0.739
3146206CASHIE
Solar/Wind Harmer
-0.008
970601AG2-382 GEN
Solar/Wind Harmer
3.604
316318V4-068
Solar/Wind Harmer
0.205
3145893MURPHYS
Solar/Wind Harmer
-0.022
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145513AHOSKIE
Solar/Wind Harmer
0.07
961941AG1-037 GEN
Solar/Wind Harmer
0.061
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3146043SEABORD
Solar/Wind Harmer
-0.008
946281AF1-292 GEN
Solar/Wind Harmer
0.179
315607AA1-063A GEN
Solar/Wind Harmer
0.804
316087AB2-174 GEN
Solar/Wind Harmer
1.128
315652AC1-086 GEN
Solar/Wind Harmer
8.876
3137643SOCKMAN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.03
941031AE2-094 GEN
Solar/Wind Harmer
13.907
944011AF1-069 GEN
Solar/Wind Harmer
4.358
970673AG2-436 GEN
Solar/Wind Harmer
15.392
970673AG2-436 GEN
Solar/Wind Harmer
7.793
316005AA1-067
Solar/Wind Harmer
0.148
3145746EVERETS
Solar/Wind Harmer
-0.029
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
970181AG2-120 GEN
Solar/Wind Harmer
0.96
971967AH1-528 GEN
Solar/Wind Harmer
13.674
3141813NORNECK
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
3.136
970831AG2-522 GEN
Solar/Wind Harmer
3.571
316420AA1-050 GEN
Solar/Wind Harmer
0.811
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
316319Z2-044 C
Solar/Wind Harmer
0.388
970085AG2-068 GEN
Solar/Wind Harmer
4.38
970581AG2-369 GEN
Solar/Wind Harmer
3.767
3141426STAFORD
Solar/Wind Helper
0.036
315051AA1-145 CT1
50/50
2.943
971645AH1-323 GEN
50/50
17.196
966881AG1-559 GEN
Solar/Wind Harmer
2.246
316473AC1-191 GEN
Solar/Wind Harmer
1.99
3142416OLDCHRC
Solar/Wind Harmer
1.811
970293AG2-193 GEN
Solar/Wind Harmer
1.949
3143096IRON208
Adder
0.549
3143096IRON208
Adder
0.538
3150861SPRUNCD
Adder
0.581
3142946ENON
Solar/Wind Harmer
-0.004
970133AG2-095 GEN
Solar/Wind Harmer
1.463
965281AG1-393 GEN
Solar/Wind Harmer
1.579
315839AE2-212 C
Solar/Wind Harmer
0.379
970129AG2-093 GEN
Solar/Wind Harmer
6.999
3142433PROV 92
Adder
0.21
3142433PROV 92
Adder
0.21
315778AD1-151 GEN
Solar/Wind Harmer
10.413
971781AH1-399 GEN
Solar/Wind Harmer
0.721
315813AE1-149 C
Solar/Wind Harmer
7.049
316382AG1-145 C
Solar/Wind Harmer
0.339
961611AG1-000B GEN
Solar/Wind Harmer
2.351
970659AG2-427 GEN
Solar/Wind Harmer
1.02
3151221GRAVEL6
Adder
6.975
3151171GRAVELC
Adder
1.342
316083AB2-161 GEN
Solar/Wind Harmer
1.744
3141843SHACKLE
Adder
0.486
316203AE2-005 GEN
Solar/Wind Harmer
4.504
3141766HARMONY
Solar/Wind Harmer
0.948
970661AG2-428 GEN
Solar/Wind Harmer
1.978
316280AD1-041 GEN
Solar/Wind Harmer
0.79
3144216WINCHST
Adder
0.35
3150921YORKTN3
Adder
2.317
3145336SMITFLD
Solar/Wind Harmer
-0.004
316156AD2-030 GEN
Solar/Wind Harmer
0.273
3141873WAN 176
Solar/Wind Harmer
1.213
972255AH1-712 GEN
Adder
46.148
3144536CHRHLND
Solar/Wind Harmer
-0.001
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
7.774
944581AF1-123 GEN
Solar/Wind Harmer
42.031
944601AF1-125 GEN
Solar/Wind Harmer
41.375
3146456SLIGO L269
Solar/Wind Harmer
-0.009
971153AH1-033 GEN
Solar/Wind Harmer
1.123
315773AC2-141 GEN
Solar/Wind Harmer
3.831
316320Y1-086
Solar/Wind Harmer
0.535
3145273HOLLAND
Solar/Wind Harmer
-0.007
316435W1029_GEN3
Solar/Wind Harmer
1.638
3146516WINFALL
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
962971AG1-146 GEN
Solar/Wind Harmer
1.669
316313AB2-026
Solar/Wind Harmer
0.239
316258AE1-075 C
Solar/Wind Harmer
0.215
316405AF2-144 C
Solar/Wind Harmer
0.227
3143336POWHATN
Solar/Wind Harmer
0.895
3146376EDENTON
Solar/Wind Harmer
-0.009
316484AD2-074 GEN
Solar/Wind Harmer
2.165
970009AG2-005 GEN
Solar/Wind Harmer
1.075
315614AA2-178 GEN
Solar/Wind Harmer
0.92
3156081AA2-088 GEN
Solar/Wind Harmer
2.717
971157AH1-035 GEN
Solar/Wind Harmer
1.045
315737AD1-076 GEN
Solar/Wind Harmer
1.583
316365GEN2_N
Solar/Wind Harmer
0.562
3146206CASHIE
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.057
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.456
961681AG1-008 GEN
Solar/Wind Harmer
6.456
3146173TUNIS
Solar/Wind Harmer
-0.008
316404AE1-155 C
Solar/Wind Harmer
1.566
3156021HOLLOMANSOL
Solar/Wind Harmer
1.092
316463AE2-346 GEN
Solar/Wind Harmer
0.131
316140AB2-099
Solar/Wind Harmer
0.054
962331AG1-082 GEN
Solar/Wind Harmer
1.009
966621AG1-532 GEN
Solar/Wind Harmer
0.162
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145963POPLR C
Solar/Wind Harmer
-0.008
313506AB2-031 GEN
Solar/Wind Harmer
0.633
316317KELFORD C
Solar/Wind Harmer
0.369
3145823KELFORD
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.005
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.936
316210AC1-098 GEN
Solar/Wind Harmer
1.176
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.418
3150351NORNECKC2
Adder
0.654
316327AA2-057 GEN
Solar/Wind Harmer
0.725
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
0.147
3146233WITAKRS
Solar/Wind Harmer
-0.005
970917AG2-570 GEN
Solar/Wind Harmer
17.575
3138543CONSLDL
Solar/Wind Harmer
-0.005
961601AG1-000A GEN
Solar/Wind Harmer
2.743
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3144293JTRSVLE
Adder
0.187
NYPJM->LTFIMP_NY
CLTF
1.285
LGEELTFEXP_LGEE->PJM
CLTF
0.641
WECLTFEXP_WEC->PJM
CLTF
0.318
LAGNLTFEXP_LAGN->PJM
CLTF
3.178
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.749
TVALTFEXP_TVA->PJM
CLTF
1.616
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.025
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.605
MECLTFEXP_MEC->PJM
CLTF
1.66
SIGELTFEXP_SIGE->PJM
CLTF
0.051
CPLELTFEXP_CPLE->PJM
CLTF
3.862
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.32

Details for AE1-157 TAP-6LDYSMITH CT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AE1-157 TAP-6LDYSMITH CT 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.26 %
Rating:1809.0 MVA
Rating Type:C
MVA to Mitigate:2121.27
MW Contribution:45.58
Bus #Bus NameTypeMW Contribution
972189AH1-679 GEN
50/50
6.193
316312AB1-027
Solar/Wind Harmer
0.576
971285AH1-108 GEN
Adder
0.913
315976AC1-164 GENA
Solar/Wind Harmer
14.017
316169AC1-164_GENC
Solar/Wind Harmer
12.109
315975AC1-164 GENB
Solar/Wind Harmer
0.415
316132AB2-190 GEN1
Solar/Wind Harmer
1.249
971167AH1-042 GEN
Solar/Wind Harmer
11.747
3142433PROV 92
Adder
0.208
3142433PROV 92
Adder
0.208
316233AE1-074 FULL
Solar/Wind Harmer
0.323
971281AH1-106 GEN
Solar/Wind Harmer
1.949
971283AH1-107 GEN
Solar/Wind Harmer
1.949
316369SG1_INVT
Solar/Wind Harmer
2.122
3143873LANEXA
Solar/Wind Harmer
-0.007
3143316POE
Solar/Wind Harmer
-0.044
972265AH1-717 GEN
Adder
7.661
3151201GRAVEL4
Adder
7.182
3151191GRAVEL3
Adder
7.091
3151211GRAVEL5
Adder
7.091
316314AB2-024 C
Solar/Wind Harmer
0.944
316059AD1-063 C
Solar/Wind Harmer
0.244
971445AH1-216 GEN
Solar/Wind Harmer
6.622
957831AF2-077 GEN
Solar/Wind Harmer
0.319
3138283WHITEMARSH
Solar/Wind Harmer
0.016
315662AE1-191 GEN
Solar/Wind Harmer
1.276
315666AE1-190 GEN
Solar/Wind Harmer
0.319
957601AF2-054 GEN
Solar/Wind Harmer
0.309
3141873WAN 176
Solar/Wind Harmer
-0.002
315833AF1-017_GEN
Solar/Wind Harmer
1.944
316349AD2-085 GEN
Solar/Wind Harmer
0.911
316311AC2-079 GEN
Solar/Wind Harmer
5.16
3152611GOSPORTB
Adder
1.131
3152621GOSPORTC
Adder
0.96
3152601GOSPORTA
Adder
0.885
3151081ELIZAR1
Adder
8.127
3151091ELIZAR2
Adder
7.986
3141913WHIT STONE
Solar/Wind Harmer
-0.01
315835AF2-110_GEN
Solar/Wind Harmer
1.229
316305AF2-043 C
Solar/Wind Harmer
0.295
957871AF2-081 GEN
Solar/Wind Harmer
4.891
319010AE1-072 C
Solar/Wind Harmer
1.972
3146406KITTY HAWK
Solar/Wind Harmer
0.008
3138133OCRAN
Solar/Wind Harmer
-0.003
313526AB2-022
Solar/Wind Harmer
0.26
3146486SUNBURY
Solar/Wind Harmer
-0.01
3146486SUNBURY
Solar/Wind Harmer
-0.01
316321Z2-027
Solar/Wind Harmer
0.259
3146396TANGLEW
Solar/Wind Harmer
0.177
3145176PASQUOTANK
Solar/Wind Harmer
-0.006
3141783LANCAST
Solar/Wind Harmer
-0.006
3141783LANCAST
Solar/Wind Harmer
-0.004
316315AB2-025 C
Solar/Wind Harmer
0.252
315611Z1-036_GEN2
Solar/Wind Harmer
2.304
315814AE2-033 C
Solar/Wind Harmer
8.664
3130156CHOWAN
Solar/Wind Harmer
-0.009
3130156CHOWAN
Solar/Wind Harmer
-0.009
315816AE2-034 GEN
Solar/Wind Harmer
0.723
962981AG1-147 GEN
Solar/Wind Harmer
3.871
3130546PLYMOUTH
Solar/Wind Harmer
-0.009
315732AD1-074 GEN1
Solar/Wind Harmer
1.762
315733AD1-074 GEN2
Solar/Wind Harmer
1.762
315735AD1-075 GEN1
Solar/Wind Harmer
0.881
965291AG1-394 GEN
Solar/Wind Harmer
0.767
3146206CASHIE
Solar/Wind Harmer
-0.009
970601AG2-382 GEN
Solar/Wind Harmer
3.761
972193AH1-681 GEN
Adder
1.748
316318V4-068
Solar/Wind Harmer
0.213
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.009
3145513AHOSKIE
Solar/Wind Harmer
0.073
961941AG1-037 GEN
Solar/Wind Harmer
0.063
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3146043SEABORD
Solar/Wind Harmer
-0.008
315607AA1-063A GEN
Solar/Wind Harmer
0.831
946281AF1-292 GEN
Solar/Wind Harmer
0.183
315652AC1-086 GEN
Solar/Wind Harmer
9.12
316087AB2-174 GEN
Solar/Wind Harmer
1.156
3137643SOCKMAN
Solar/Wind Harmer
-0.032
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.031
941031AE2-094 GEN
Solar/Wind Harmer
14.54
944011AF1-069 GEN
Solar/Wind Harmer
4.556
970673AG2-436 GEN
Solar/Wind Harmer
16.073
970673AG2-436 GEN
Solar/Wind Harmer
8.138
971967AH1-528 GEN
Solar/Wind Harmer
14.253
316005AA1-067
Solar/Wind Harmer
0.153
3145746EVERETS
Solar/Wind Harmer
-0.03
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
970181AG2-120 GEN
Solar/Wind Harmer
0.993
957861AF2-080 GEN
Solar/Wind Harmer
3.238
970831AG2-522 GEN
Solar/Wind Harmer
3.663
316420AA1-050 GEN
Solar/Wind Harmer
0.836
970085AG2-068 GEN
Solar/Wind Harmer
4.559
970581AG2-369 GEN
Solar/Wind Harmer
3.92
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
316319Z2-044 C
Solar/Wind Harmer
0.4
3141426STAFORD
Solar/Wind Helper
0.041
315052AA1-145 CT2
50/50
2.775
966881AG1-559 GEN
Solar/Wind Harmer
0.727
3142416OLDCHRC
Solar/Wind Harmer
-0.044
3142416OLDCHRC
Solar/Wind Harmer
-0.017
3143096IRON208
Adder
0.532
3142543TWELFTH
Solar/Wind Harmer
-0.001
3150851SPRUNCC
Adder
0.558
944631AF1-128 GEN
Adder
57.426
315671AE2-027_GEN
Solar/Wind Harmer
9.427
970129AG2-093 GEN
Solar/Wind Harmer
2.827
316458AB2-190 GEN2
Solar/Wind Harmer
1.249
971069AG2-661 GEN
Solar/Wind Harmer
1.91
3142433PROV 92
Solar/Wind Harmer
-0.048
3142433PROV 92
Adder
0.208
3142433PROV 92
Adder
0.208
3143526WINTERP
Solar/Wind Harmer
-0.062
316159AE1-175 C
Solar/Wind Harmer
0.313
971647AH1-324 GEN
Solar/Wind Harmer
5.818
961611AG1-000B GEN
Solar/Wind Harmer
5.622
3151171GRAVELC
Adder
1.05
971317AH1-138 GEN
Solar/Wind Harmer
1.371
970659AG2-427 GEN
Solar/Wind Harmer
5.815
3138126ROCKLANDING
Solar/Wind Harmer
0.033
316381AD1-082 GEN
Solar/Wind Harmer
0.998
971777AH1-397 GEN
Solar/Wind Harmer
1.267
3141843SHACKLE
Adder
0.49
3141766HARMONY
Solar/Wind Harmer
-0.002
970661AG2-428 GEN
Solar/Wind Harmer
11.365
3145336SMITFLD
Solar/Wind Harmer
-0.042
3143226MDLTHAN
Solar/Wind Harmer
-0.01
316072AD1-144
Solar/Wind Harmer
0.204
316375AC2-012 GEN
Solar/Wind Harmer
3.453
3150981CHESPKA
Adder
1.109
316294AC1-161 GEN
Solar/Wind Harmer
3.192
316093AE2-104_GEN
Solar/Wind Harmer
2.859
944591AF1-124 GEN
Solar/Wind Harmer
44.876
316388AE2-253 GEN
Solar/Wind Harmer
0.66
316246AF1-032 C
Solar/Wind Harmer
0.198
3146456SLIGO L269
Solar/Wind Harmer
-0.01
3138133OCRAN
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.031
3146516WINFALL
Solar/Wind Harmer
-0.009
315800Z1-036_GEN1
Solar/Wind Harmer
2.304
3130156CHOWAN
Solar/Wind Harmer
-0.009
3145663CRESWEL
Solar/Wind Harmer
-0.025
971163AH1-040 GEN
Solar/Wind Harmer
8.378
939411AE1-173 GEN
Solar/Wind Harmer
43.471
3146206CASHIE
Solar/Wind Harmer
-0.009
971547AH1-271 GEN
Solar/Wind Harmer
2.149
972277AH1-723 GEN
Adder
45.58
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.253
3143336POWHATN
Solar/Wind Harmer
1.013
316023GEN1_S
Solar/Wind Harmer
0.574
961951AG1-038 GEN
Solar/Wind Harmer
1.121
3146173TUNIS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
940641AE2-051 GEN
Solar/Wind Harmer
7.795
3146263WOODLND
Solar/Wind Harmer
-0.008
3145963POPLR C
Solar/Wind Harmer
-0.008
960081AF2-299 GEN
Solar/Wind Harmer
0.92
3145823KELFORD
Solar/Wind Harmer
-0.008
316174AB2-169 GEN
Solar/Wind Harmer
1.252
962861AG1-135 GEN
Solar/Wind Harmer
3.042
316011AB1-132 GEN
Solar/Wind Harmer
1.696
962571AG1-106 GEN
Solar/Wind Harmer
1.165
316336AC2-165 C
Solar/Wind Harmer
1.403
316190AA2-174 GEN
Solar/Wind Harmer
0.099
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
3145783HORNRTN
Solar/Wind Harmer
-0.008
971795AH1-408 GEN
Solar/Wind Harmer
5.915
3146293MARTNCO
Solar/Wind Harmer
0.048
3147043LAWRENC
Adder
0.624
316212AC1-099_GEN
Solar/Wind Harmer
0.674
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
964211AG1-282 GEN
Solar/Wind Harmer
0.227
3141726DUNNSVL
Solar/Wind Harmer
-0.03
315722AD1-056 GEN
Solar/Wind Harmer
0.781
316494AC1-189 GEN
Solar/Wind Harmer
0.796
970919AG2-571 GEN
Solar/Wind Harmer
2.316
970087AG2-069 GEN
Solar/Wind Harmer
6.838
316129AC1-054 GEN
Solar/Wind Harmer
0.636
961671AG1-007 GEN
Solar/Wind Harmer
0.092
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.215
3146233WITAKRS
Solar/Wind Harmer
-0.029
971065AG2-659 GEN
Solar/Wind Harmer
3.598
3150351NORNECKC2
Adder
0.621
3144293JTRSVLE
Adder
0.188
957481AF2-042 GEN
Solar/Wind Harmer
18.463
3142296MT RD221
50/50
0.574
3142366NRTHEST
50/50
0.497
3150691DARBY 3
50/50
10.715
3150701DARBY 4
50/50
10.691
3150681DARBY 2
50/50
10.678
315673AE1-157 GEN
Solar/Wind Harmer
60.58
957411AF2-035 GEN
Solar/Wind Harmer
31.802
970317AG2-208 GEN
Solar/Wind Harmer
30.918
966871AG1-558 GEN
Solar/Wind Harmer
0.511
966871AG1-558 GEN
Solar/Wind Harmer
0.175
3150671DARBY 1
Adder
10.051
316075AC2-137 C
Solar/Wind Harmer
0.39
3142946ENON
Solar/Wind Harmer
-0.001
944641AF1-129 GEN
Adder
56.507
316240AF1-291 C
Solar/Wind Harmer
0.394
3143526WINTERP
Solar/Wind Harmer
-0.062
316033AB2-134 GEN
Solar/Wind Harmer
3.83
315697AD1-025 GEN
Solar/Wind Harmer
2.402
970657AG2-426 GEN
Solar/Wind Harmer
3.379
970657AG2-426 GEN
Solar/Wind Harmer
0.707
316441AF1-014 GEN
Solar/Wind Harmer
0.726
316236AE1-162_GEN
Solar/Wind Harmer
0.321
971223AH1-071 GEN
Solar/Wind Harmer
1.286
316468AD1-105 GEN
Solar/Wind Harmer
1.117
316036AC1-147 C
Solar/Wind Harmer
0.269
3150991CHESPKB
Adder
0.93
3150991CHESPKB
Adder
0.908
316316AC1-027 C
Solar/Wind Harmer
0.304
3142956BIRDNECK
Solar/Wind Harmer
0.532
316185AD1-033 GEN
Solar/Wind Harmer
1.04
3145506HICKORY
Solar/Wind Harmer
-0.039
3145506HICKORY
Solar/Wind Harmer
-0.023
3145506HICKORY
Solar/Wind Harmer
-0.006
316339AD2-160 GEN
Solar/Wind Harmer
0.66
316018AA1-139 ULT2
Solar/Wind Harmer
0.838
316017AA1-139 ULT1
Solar/Wind Harmer
0.791
3137176SLIGO L2192
Solar/Wind Harmer
-0.039
3146456SLIGO L269
Solar/Wind Harmer
1.153
3130086AYDLETT
Solar/Wind Harmer
-0.039
3146386ELIZ CT
Solar/Wind Harmer
-0.01
316431W1029_GEN1
Solar/Wind Harmer
1.728
316433W1029_GEN2
Solar/Wind Harmer
1.728
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3144356SAPONY
Solar/Wind Harmer
0.326
315742AE1-103 GEN
Solar/Wind Harmer
0.974
3146376EDENTON
Solar/Wind Harmer
0.273
3146376EDENTON
Solar/Wind Harmer
0.273
316065AD1-022 GEN
Solar/Wind Harmer
4.319
3145893MURPHYS
Solar/Wind Harmer
0.238
3145893MURPHYS
Solar/Wind Harmer
-0.015
316487AF1-042 GEN
Solar/Wind Harmer
1.121
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
316181AB2-040 GEN
Solar/Wind Harmer
1.126
316426AA2-053 GEN
Solar/Wind Harmer
0.811
958261AF2-120 GEN
Solar/Wind Harmer
3.088
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.895
3145593CAROLNA
Solar/Wind Harmer
0.066
3145783HORNRTN
Solar/Wind Harmer
0.938
3145783HORNRTN
Solar/Wind Harmer
0.751
3145783HORNRTN
Solar/Wind Harmer
0.235
3145783HORNRTN
Solar/Wind Harmer
0.094
3145933PARMELE
Solar/Wind Harmer
-0.015
3145933PARMELE
Solar/Wind Harmer
-0.008
316274AC1-208 GEN
Solar/Wind Harmer
0.825
972185AH1-677 GEN
Adder
3.795
972187AH1-678 GEN
Adder
1.908
970933AG2-581 GEN
Solar/Wind Harmer
6.981
3145493TOT1
Solar/Wind Harmer
0.112
3145453TOT5
Solar/Wind Harmer
0.067
3145603CNETO
Solar/Wind Harmer
0.045
3150341NORNECKC1
Adder
0.652
3150341NORNECKC1
Adder
0.647
3144293JTRSVLE
Adder
0.188
3144293JTRSVLE
Adder
0.158
970099AG2-077 GEN
Solar/Wind Harmer
7.385
315051AA1-145 CT1
50/50
2.763
971645AH1-323 GEN
50/50
15.887
966881AG1-559 GEN
Solar/Wind Harmer
2.125
3142416OLDCHRC
Solar/Wind Harmer
1.724
316473AC1-191 GEN
Solar/Wind Harmer
1.83
970293AG2-193 GEN
Solar/Wind Harmer
1.893
3143096IRON208
Adder
0.532
3143096IRON208
Adder
0.522
3150861SPRUNCD
Adder
0.558
3142946ENON
Solar/Wind Harmer
-0.004
970133AG2-095 GEN
Solar/Wind Harmer
1.445
970129AG2-093 GEN
Solar/Wind Harmer
6.978
965281AG1-393 GEN
Solar/Wind Harmer
1.549
315839AE2-212 C
Solar/Wind Harmer
0.372
315778AD1-151 GEN
Solar/Wind Harmer
10.456
3142433PROV 92
Adder
0.208
3142433PROV 92
Adder
0.208
316382AG1-145 C
Solar/Wind Harmer
0.352
961611AG1-000B GEN
Solar/Wind Harmer
2.399
315813AE1-149 C
Solar/Wind Harmer
7.056
3151221GRAVEL6
Adder
7.174
3151171GRAVELC
Adder
1.38
970659AG2-427 GEN
Solar/Wind Harmer
1.031
3144216WINCHST
Adder
0.366
3150921YORKTN3
Adder
2.434
316083AB2-161 GEN
Solar/Wind Harmer
1.766
3141843SHACKLE
Adder
0.49
3141766HARMONY
Solar/Wind Harmer
0.959
316203AE2-005 GEN
Solar/Wind Harmer
4.541
970661AG2-428 GEN
Solar/Wind Harmer
2.014
3145336SMITFLD
Solar/Wind Harmer
-0.004
316280AD1-041 GEN
Solar/Wind Harmer
0.798
316156AD2-030 GEN
Solar/Wind Harmer
0.276
3141873WAN 176
Solar/Wind Harmer
1.226
3144536CHRHLND
Solar/Wind Harmer
-0.002
971781AH1-399 GEN
Solar/Wind Harmer
0.618
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
8.231
315773AC2-141 GEN
Solar/Wind Harmer
4.129
944581AF1-123 GEN
Solar/Wind Harmer
44.715
944601AF1-125 GEN
Solar/Wind Harmer
44.017
3146456SLIGO L269
Solar/Wind Harmer
-0.01
971153AH1-033 GEN
Solar/Wind Harmer
1.19
316320Y1-086
Solar/Wind Harmer
0.565
316435W1029_GEN3
Solar/Wind Harmer
1.728
3146516WINFALL
Solar/Wind Harmer
-0.009
3145273HOLLAND
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3146376EDENTON
Solar/Wind Harmer
-0.009
315614AA2-178 GEN
Solar/Wind Harmer
0.964
962971AG1-146 GEN
Solar/Wind Harmer
1.659
971157AH1-035 GEN
Solar/Wind Harmer
1.093
315737AD1-076 GEN
Solar/Wind Harmer
1.656
3156081AA2-088 GEN
Solar/Wind Harmer
2.822
3146206CASHIE
Solar/Wind Harmer
-0.009
972255AH1-712 GEN
Adder
39.114
3145893MURPHYS
Solar/Wind Harmer
0.06
3145893MURPHYS
Solar/Wind Harmer
-0.009
316313AB2-026
Solar/Wind Harmer
0.23
316258AE1-075 C
Solar/Wind Harmer
0.207
316405AF2-144 C
Solar/Wind Harmer
0.219
3143336POWHATN
Solar/Wind Harmer
0.861
316365GEN2_N
Solar/Wind Harmer
0.574
957521AF2-046 GEN
Solar/Wind Harmer
6.704
961681AG1-008 GEN
Solar/Wind Harmer
6.704
316484AD2-074 GEN
Solar/Wind Harmer
2.143
970009AG2-005 GEN
Solar/Wind Harmer
1.064
3146173TUNIS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1.136
316463AE2-346 GEN
Solar/Wind Harmer
0.136
316140AB2-099
Solar/Wind Harmer
0.057
962331AG1-082 GEN
Solar/Wind Harmer
1.048
3146263WOODLND
Solar/Wind Harmer
-0.008
3145963POPLR C
Solar/Wind Harmer
-0.008
966621AG1-532 GEN
Solar/Wind Harmer
0.166
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
316317KELFORD C
Solar/Wind Harmer
0.383
3145823KELFORD
Solar/Wind Harmer
-0.008
313506AB2-031 GEN
Solar/Wind Harmer
0.649
316404AE1-155 C
Solar/Wind Harmer
1.537
3145796HORNRTN
Solar/Wind Harmer
-0.032
3145796HORNRTN
Solar/Wind Harmer
-0.008
3145933PARMELE
Solar/Wind Harmer
-0.008
966801AG1-551 GEN
Solar/Wind Harmer
0.971
3147043LAWRENC
Solar/Wind Harmer
-0.005
316210AC1-098 GEN
Solar/Wind Harmer
1.213
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
315724AD1-057 GEN
Solar/Wind Harmer
0.43
316327AA2-057 GEN
Solar/Wind Harmer
0.746
970917AG2-570 GEN
Solar/Wind Harmer
18.293
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
0.151
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3150351NORNECKC2
Adder
0.631
3144293JTRSVLE
Adder
0.188
NYPJM->LTFIMP_NY
CLTF
1.242
LGEELTFEXP_LGEE->PJM
CLTF
0.605
WECLTFEXP_WEC->PJM
CLTF
0.3
LAGNLTFEXP_LAGN->PJM
CLTF
3.104
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.794
TVALTFEXP_TVA->PJM
CLTF
1.575
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.367
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.444
MECLTFEXP_MEC->PJM
CLTF
1.583
SIGELTFEXP_SIGE->PJM
CLTF
0.049
CPLELTFEXP_CPLE->PJM
CLTF
3.926
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.752
CONTINGENCY 'DVP_P1-2: LN 553_SRT-S'
 OPEN BRANCH FROM BUS 314908 TO BUS 314910 CKT 1                /*8ELMONT      500.0 - 8CUNINGHAM   500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
END
CONTINGENCY 'DVP_P1-2: LN 574_SRT-S'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3966 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 3572 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'PEPCO_P1_5070_SRT-A'
 OPEN BRANCH FROM BUS 200019 TO BUS 314922 CKT 1   /*BURCHES      500.0 - 8POSSUM      500.0
END
CONTINGENCY 'DVP_P4-2: H2T560_SRT-A'
 OPEN BRANCH FROM BUS 200019 TO BUS 314922 CKT 1   /*BURCHES      500.0 - 8POSSUM      500.0
 OPEN BRANCH FROM BUS 313908 TO BUS 314922 CKT 1   /*6POS PT TAP2 230.0 - 8POSSUM      500.0
END
CONTINGENCY 'DVP_P4-2: H1T560_SRT-A'
 OPEN BRANCH FROM BUS 200019 TO BUS 314922 CKT 1   /*BURCHES      500.0 - 8POSSUM      500.0
 OPEN BRANCH FROM BUS 313058 TO BUS 314922 CKT 1   /*6POSS PT TAP 230.0 - 8POSSUM      500.0
END
CONTINGENCY 'DVP_P4-2: 560T571_SRT-S'
 OPEN BRANCH FROM BUS 200019 TO BUS 314922 CKT 1                /*BURCHES      500.0 - 8POSSUM      500.0
 OPEN BRANCH FROM BUS 313383 TO BUS 314922 CKT 1                /*8OCCOQUN     500.0 - 8POSSUM      500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
END
CONTINGENCY 'AP_P2-3_PE-500-019F_SRT-SL'
 DISCONNECT BRANCH FROM BUS 200003 TO BUS 235105 CKT 1          /*BRIGHTON     500.0 - 01DOUBS      500.0
 DISCONNECT BRANCH FROM BUS 235105 TO BUS 235459 CKT 2          /*01DOUBS      500.0 - 01DOUBS      230.0
 DISCONNECT BRANCH FROM BUS 235105 TO BUS 235459 CKT 4          /*01DOUBS      500.0 - 01DOUBS      230.0
 REMOVE SWSHUNT FROM BUS 235105 BLOCK 1 STEP 1                  /*01DOUBS      500.0
 SET POSTCONTRATING 4357 BRANCH FROM BUS 235105 TO BUS 313403 CKT 1 /*01DOUBS      500.0 - 8ASPEN       500.0
 SET POSTCONTRATING 4357 BRANCH FROM BUS 235105 TO BUS 314939 CKT 1 /*01DOUBS      500.0 - 8GOOSE CREEK 500.0
 SET PRECONTRATING 4178 BRANCH FROM BUS 235105 TO BUS 313403 CKT 1 /*01DOUBS      500.0 - 8ASPEN       500.0
 SET PRECONTRATING 4178 BRANCH FROM BUS 235105 TO BUS 314939 CKT 1 /*01DOUBS      500.0 - 8GOOSE CREEK 500.0
END
CONTINGENCY 'AP_P2-3_PE-500-019B_SRT-A'
 DISCONNECT BRANCH FROM BUS 235105 TO BUS 200003 CKT 1   /*01DOUBS      500.0 - BRIGHTON     500.0
 DISCONNECT BRANCH FROM BUS 270095 TO BUS 235105 CKT 1   /*CHAN         500.0 - 01DOUBS      500.0
END
CONTINGENCY 'DVP_P7-1: LN 514-2098_SRT-S'
 OPEN BRANCH FROM BUS 235105 TO BUS 314939 CKT 1                /*01DOUBS      500.0 - 8GOOSE CREEK 500.0
 OPEN BRANCH FROM BUS 313010 TO BUS 313021 CKT 1                /*6BREEZYKNOLL 230.0 - 6DRYMILLS    230.0
 OPEN BRANCH FROM BUS 313010 TO BUS 313021 CKT 2                /*6BREEZYKNOLL 230.0 - 6DRYMILLS    230.0
 OPEN BRANCH FROM BUS 313010 TO BUS 314005 CKT 1                /*6BREEZYKNOLL 230.0 - 6HAMLTON     230.0
 OPEN BRANCH FROM BUS 313021 TO BUS 314072 CKT 1                /*6DRYMILLS    230.0 - 6PL VIEW     230.0
 OPEN BUS 313010                                                /*6BREEZYKNOLL 230.0
 OPEN BUS 313021                                                /*6DRYMILLS    230.0
 OPEN BUS 314005                                                /*6HAMLTON     230.0
 SET POSTCONTRATING 1315 BRANCH FROM BUS 314004 TO BUS 314072 CKT 1 /*6ASHBURN     230.0 - 6PL VIEW     230.0
 SET PRECONTRATING 1219 BRANCH FROM BUS 314004 TO BUS 314072 CKT 1 /*6ASHBURN     230.0 - 6PL VIEW     230.0
END
CONTINGENCY 'DVP_P4-2: 574T575_SRT-S'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 OPEN BRANCH FROM BUS 314911 TO BUS 314918 CKT 1                /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
 SET POSTCONTRATING 3966 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
 SET PRECONTRATING 3572 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: H1T574_SRT-S'
 OPEN BRANCH FROM BUS 314218 TO BUS 314908 CKT 1                /*6ELMONT      230.0 - 8ELMONT      500.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT      500.0 - 8CUNINGHAM   500.0
 SET POSTCONTRATING 3966 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT      500.0 - 8CUNINGHAM   500.0
 SET PRECONTRATING 3572 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: 557T574_SRT-S'
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3966 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 3572 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: H2T574_SRT-S'
 OPEN BRANCH FROM BUS 314196 TO BUS 314911 CKT 2                /*6LADYSMITH   230.0 - 8LADYSMITH   500.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3966 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 3572 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: 568T581_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1                /*8CHANCE      500.0 - 8LADYSMITH   500.0
 OPEN BRANCH FROM BUS 314911 TO BUS 314922 CKT 1                /*8LADYSMITH   500.0 - 8POSSUM      500.0
 SET POSTCONTRATING 2913 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P1-2: LN 9344_SRT-A'
 OPEN BRANCH FROM BUS 313393 TO BUS 313905 CKT 1   /*8MARS        500.0 - 8WSHNGSTAR   500.0
END
CONTINGENCY 'DVP_P1-2: LN 594_SRT-S'
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 573_SRT-S'
 OPEN BRANCH FROM BUS 314918 TO BUS 314934 CKT 1                /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
END
CONTINGENCY 'DVP_P4-2: 545T594_SRT-S'
 OPEN BRANCH FROM BUS 314900 TO BUS 314916 CKT 1                /*8BRISTER     500.0 - 8MORRSVL     500.0
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET POSTCONTRATING 3966 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET PRECONTRATING 3572 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
END
CONTINGENCY 'DVP_P4-2: H1T594_SRT-S'
 OPEN BRANCH FROM BUS 314063 TO BUS 314916 CKT 1                /*6MORRSVL     230.0 - 8MORRSVL     500.0
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 OPEN BUS 314897                                                /*8MORRS_1     500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314916 TO BUS 314929 CKT 1 /*8MORRSVL     500.0 - 8FRONT ROYAL 500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314916 TO BUS 314929 CKT 1 /*8MORRSVL     500.0 - 8FRONT ROYAL 500.0
END
CONTINGENCY 'DVP_P4-2: SPOTS H1T594_SRT-S'
 OPEN BRANCH FROM BUS 314755 TO BUS 314934 CKT 1                /*3SPOTSYL     115.0 - 8SPOTSYL     500.0
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P4-2: 515T594_SRT-S'
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 OPEN BRANCH FROM BUS 314934 TO BUS 314944 CKT 1                /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 OPEN BUS 314944                                                /*8SPOTSYL EC  500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P4-2: H1T573_SRT-S'
 OPEN BRANCH FROM BUS 314755 TO BUS 314934 CKT 1                /*3SPOTSYL     115.0 - 8SPOTSYL     500.0
 OPEN BRANCH FROM BUS 314918 TO BUS 314934 CKT 1                /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
END
CONTINGENCY 'DVP_P4-1: FLUVANN GT22_SRT-S'
 OPEN BRANCH FROM BUS 314910 TO BUS 314943 CKT 1                /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
 OPEN BRANCH FROM BUS 314943 TO BUS 315217 CKT 1                /*8FLUVANNAWES 500.0 - 1CUNINGB      18.0
 OPEN BRANCH FROM BUS 314943 TO BUS 315218 CKT 1                /*8FLUVANNAWES 500.0 - 1CUNINGC      18.0
 OPEN BUS 314943                                                /*8FLUVANNAWES 500.0
 OPEN BUS 315217                                                /*1CUNINGB      18.0
 OPEN BUS 315218                                                /*1CUNINGC      18.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314907 TO BUS 314910 CKT 1 /*8DOOMS       500.0 - 8CUNINGHAM   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT      500.0 - 8CUNINGHAM   500.0
 SET PRECONTRATING 2598 BRANCH FROM BUS 314907 TO BUS 314910 CKT 1 /*8DOOMS       500.0 - 8CUNINGHAM   500.0
 SET PRECONTRATING 2598 BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT      500.0 - 8CUNINGHAM   500.0
END
CONTINGENCY 'DVP_P1-2: LN 542_SRT-S'
 OPEN BRANCH FROM BUS 314910 TO BUS 314943 CKT 1                /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
 OPEN BRANCH FROM BUS 314943 TO BUS 315217 CKT 1                /*8FLUVANNAWES 500.0 - 1CUNINGB      18.0
 OPEN BRANCH FROM BUS 314943 TO BUS 315218 CKT 1                /*8FLUVANNAWES 500.0 - 1CUNINGC      18.0
 OPEN BUS 314943                                                /*8FLUVANNAWES 500.0
 OPEN BUS 315217                                                /*1CUNINGB      18.0
 OPEN BUS 315218                                                /*1CUNINGC      18.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314907 TO BUS 314910 CKT 1 /*8DOOMS       500.0 - 8CUNINGHAM   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT      500.0 - 8CUNINGHAM   500.0
 SET PRECONTRATING 2598 BRANCH FROM BUS 314907 TO BUS 314910 CKT 1 /*8DOOMS       500.0 - 8CUNINGHAM   500.0
 SET PRECONTRATING 2598 BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT      500.0 - 8CUNINGHAM   500.0
END
CONTINGENCY 'DVP_P2-2: ELMONT B1_SRT-S'
 OPEN BRANCH FROM BUS 314218 TO BUS 314908 CKT 1                /*6ELMONT      230.0 - 8ELMONT      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P2-2: LADYSMITH B2_SRT-S'
 OPEN BRANCH FROM BUS 314196 TO BUS 314911 CKT 2                /*6LADYSMITH   230.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2913 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
END
CONTINGENCY 'DVP_P1-2: LN 576_SRT-S'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P4-2: H4T581_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1                /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2913 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: H1T581_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314196 TO BUS 314911 CKT 1                /*6LADYSMITH   230.0 - 8LADYSMITH   500.0
 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1                /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2913 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P4-2: 57602_SRT-S'
 OPEN BRANCH FROM BUS 314232 TO BUS 314918 CKT 1                /*6NO ANNA     230.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P4-2: WT576_SRT-S'
 OPEN BRANCH FROM BUS 314232 TO BUS 314918 CKT 2                /*6NO ANNA     230.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P7-1: LN 2090-256_SRT-S'
 OPEN BRANCH FROM BUS 313837 TO BUS 314138 CKT 1                /*6SUMMIT      230.0 - 6MINE RD     230.0
 OPEN BRANCH FROM BUS 313837 TO BUS 314197 CKT 1                /*6SUMMIT      230.0 - 6LDYSMITH CT 230.0
 OPEN BRANCH FROM BUS 314137 TO BUS 314138 CKT 1                /*6FREDBRG     230.0 - 6MINE RD     230.0
 OPEN BRANCH FROM BUS 314150 TO BUS 314212 CKT 1                /*6STJOHN      230.0 - 6FOUR RIVERS 230.0
 OPEN BRANCH FROM BUS 314197 TO BUS 315672 CKT 1                /*6LDYSMITH CT 230.0 - AE1-157 TAP  230.0
 OPEN BUS 313837                                                /*6SUMMIT      230.0
 OPEN BUS 314138                                                /*6MINE RD     230.0
 OPEN BUS 314149                                                /*3STJOHND     115.0
 OPEN BUS 314150                                                /*6STJOHN      230.0
 OPEN BUS 314154                                                /*3STJOHNS     115.0
 OPEN BUS 315672                                                /*AE1-157 TAP  230.0
 OPEN BUS 315673                                                /*AE1-157 GEN    0.6
 OPEN BUS 315803                                                /*AE1-157 MAIN 230.0
 OPEN BUS 315804                                                /*AE1-157 COL1  34.5
 OPEN BUS 315805                                                /*AE1-157 COL2  34.5
 SET POSTCONTRATING 657 BRANCH FROM BUS 313027 TO BUS 314212 CKT 1 /*6FOUR RIVER1 230.0 - 6FOUR RIVERS 230.0
 SET POSTCONTRATING 876 BRANCH FROM BUS 314212 TO BUS 315610 CKT 1 /*6FOUR RIVERS 230.0 - AA1-145 MAIN 230.0
 SET PRECONTRATING 598 BRANCH FROM BUS 313027 TO BUS 314212 CKT 1 /*6FOUR RIVER1 230.0 - 6FOUR RIVERS 230.0
 SET PRECONTRATING 813 BRANCH FROM BUS 314212 TO BUS 315610 CKT 1 /*6FOUR RIVERS 230.0 - AA1-145 MAIN 230.0
END
CONTINGENCY 'DVP_P7-1: LN 2076-2145_SRT-A-2'
 OPEN BRANCH FROM BUS 313810 TO BUS 944490 CKT 1   /*6DAHLGREN    230.0 - AF1-114 TP   230.0
 OPEN BRANCH FROM BUS 313810 TO BUS 957190 CKT 1   /*6DAHLGREN    230.0 - AF2-013 TP   230.0
END
CONTINGENCY 'DVP_P4-2: 57302_SRT-S'
 OPEN BRANCH FROM BUS 314232 TO BUS 314918 CKT 1                /*6NO ANNA     230.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314918 TO BUS 314934 CKT 1                /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P4-2: XT573_SRT-S'
 OPEN BRANCH FROM BUS 314232 TO BUS 314918 CKT 2                /*6NO ANNA     230.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314918 TO BUS 314934 CKT 1                /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P4-2: 515T573_SRT-S'
 OPEN BRANCH FROM BUS 314918 TO BUS 314934 CKT 1   /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 OPEN BRANCH FROM BUS 314934 TO BUS 314944 CKT 1   /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 OPEN BUS 314944                                   /*8SPOTSYL EC  500.0
END
CONTINGENCY 'DVP_P1-2: LN 581_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1                /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2913 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P1-2: LN 552_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1                /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P4-2: 545T552_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1                /*8BRISTER     500.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314916 CKT 1                /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314916 TO BUS 314934 CKT 1 /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314916 TO BUS 314934 CKT 1 /*8MORRSVL     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P4-2: H3T552_SRT-S'
 OPEN BRANCH FROM BUS 314130 TO BUS 314900 CKT 2                /*6BRISTER     230.0 - 8BRISTER     500.0
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1                /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P4-2: H1T552_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1                /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'AP_P1-2_PE-500-406T_SRT-A'
 DISCONNECT BRANCH FROM BUS 200003 TO BUS 235105 CKT 1   /*BRIGHTON     500.0 - 01DOUBS      500.0
END
CONTINGENCY 'PEPCO_P4_PP41_SRT-A'
 OPEN BRANCH FROM BUS 200003 TO BUS 224058 CKT 1   /*BRIGHTON     500.0 - BRG 3T 230   230.0
 OPEN BRANCH FROM BUS 200003 TO BUS 235105 CKT 1   /*BRIGHTON     500.0 - 01DOUBS      500.0
END
314749 to 314772 ckt 1
314290 to 223938 ckt 1
314218 to 314222 ckt 1
314212 to 314150 ckt 1
314222 to 314212 ckt 1
314759 to 314734 ckt 1
314197 to 313837 ckt 1
314138 to 314137 ckt 1
314772 to 314759 ckt 1
314150 to 315672 ckt 1
313837 to 314138 ckt 1
313911 to 314290 ckt 1
314933 to 972284 ckt 1
314905 to 314900 ckt 1
314910 to 314908 ckt 1
314908 to 314218 ckt 2
314908 to 314911 ckt 1
314911 to 314905 ckt 1
314911 to 314922 ckt 1
314914 to 314918 ckt 1
314918 to 314934 ckt 1
314922 to 200019 ckt 1
314934 to 314916 ckt 1
315672 to 314197 ckt 1

Winter Peak Analysis

The New Service Request AH1-723 was evaluated as a 776.0 MW (712.0 MW Capacity) injection in the Dominion area.

AH1-723 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 776.0 MW (776.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

(No impacts were found for this analysis)

Light Load Analysis

The New Service Request AH1-723 was evaluated as a 776.0 MW injection

AH1-723 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 776.0 MW (776.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

(No impacts were found for this analysis)

Short Circuit Analysis

Short Circuit analysis is not performed as part of the Phase I System Impact Study. Short Circuit analysis will commence in the Phase II System Impact Study.

Stability Analysis

Stability analysis is not performed as part of the Phase I System Impact Study. Stability analysis will commence in the Phase II System Impact Study.

Reactive Power Analysis

Reactive Power analysis is not performed as part of the Phase I System Impact Study. Reactive Power analysis will commence in the Phase II System Impact Study.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-038Lexington-Low Moor 230kVUnder Construction
AA1-050Tarboro-Everetts 230kVIn Service
AA1-063ACarolina–Seaboard 115kVIn Service
AA1-067Everetts 34.5kVIn Service
AA1-095Halfway-Marlowe 34.5kVIn Service
AA1-139Hickory-Shawboro 230kVIn Service
AA1-145Four Rivers 230kVIn Service
AA2-053Carolina-Jackson 115kVIn Service
AA2-057Hornertown-Whitakers 115kVIn Service
AA2-174Carolina-Jackson 115kVIn Service
AA2-178Mackeys 230kVIn Service
AA2-184Atlantic-Red Bank 34kVIn Service
AB1-001Absecon 12 kVIn Service
AB1-027Old Church 34.5 KVIn Service
AB1-081Anaconda-Mayo Dunbar 115kVIn Service
AB1-096Carroll-Mt. Airy 34.5kVIn Service
AB1-124Carroll-Monocacy 34.5kVPartially in Service - Under Construction
AB1-125Carroll-Monocacy 34.5kVIn Service
AB1-127St. Thomas-Guilford 34.5kVIn Service
AB1-128St. Thomas-Mercersburg 34.5kVIn Service
AB1-132Thelma 230kVIn Service
AB1-138Navy 34.5kVIn Service
AB1-139Metuchen 26kVIn Service
AB1-141Church-Wye Mills 138 kV IIn Service
AB1-142Church-Wye Mills 138 kV IIIn Service
AB1-176Price 25kV IIEngineering & Procurement
AB2-022Elizabeth City 34.5kVIn Service
AB2-024Correctional 34.5kVIn Service
AB2-025Sapony 34.5kVIn Service
AB2-026Powhatan 34.5kVIn Service
AB2-029Remington 34.5kVIn Service
AB2-031Brink-Trego 115kVIn Service
AB2-032Church-Wye Mills 138 kVIn Service
AB2-037Keeney-Steele 230kVUnder Construction
AB2-040Brink 115kVIn Service
AB2-043Chase City 115kVIn Service
AB2-045Buckingham 34.5kVIn Service
AB2-049Gloucester Township 12kVIn Service
AB2-059Benson-Dunbar 115kVIn Service
AB2-060Chase City-Lunenburg 115kVIn Service
AB2-077Buggs Island-Chase City 115kVIn Service
AB2-078Buggs Island-Chase City 115kVIn Service
AB2-079Buggs Island-Chase City 115kVIn Service
AB2-099Ahoskie 34.5kVIn Service
AB2-133Chestertown 69kVUnder Construction
AB2-134Hopewell-Surry 230kVIn Service
AB2-135Church-Kent 69kVIn Service
AB2-136Cambridge-West Cambridge 69kVUnder Construction
AB2-153Church-Wye Mills 138 kVIn Service
AB2-157Prince George's County 12kVIn Service
AB2-158Louisa-South Anna 230kVIn Service
AB2-161Waverly #2 DP 115kVIn Service
AB2-169Pantago-Five Points 115kVIn Service
AB2-174Emporia-Trego 115kVIn Service
AB2-179Townsend 138kVIn Service
AB2-190Hopewell-Surry 230kVIn Service
AC1-010Gloucester 26kVUnder Construction
AC1-017Levittown 13 kVIn Service
AC1-027Pendleton 34.5kVIn Service
AC1-030Cinnaminson 13kVIn Service
AC1-034Heartsease DP - Mayo Dunbar 115kVSuspended
AC1-036Twittys Creek 34.5kVIn Service
AC1-042Altavista-Mt. Airy 69kVIn Service
AC1-054Kerr Dam–Eatons Ferry 115 kVIn Service
AC1-075Perth-Hickory Grove 115kVIn Service
AC1-076Locust Grove-Paytes 115kVIn Service
AC1-086Thelma 230kVSuspended
AC1-091Cedar Creek 138kV IEngineering & Procurement
AC1-092Cedar Creek 138kV IIEngineering & Procurement
AC1-093Cedar Creek 138kV IIIEngineering & Procurement
AC1-094Cedar Creek 138kV IVEngineering & Procurement
AC1-098Dawson-South Justice 115kVPartially in Service - Under Construction
AC1-099Dawson-South Justice 115kVPartially in Service - Under Construction
AC1-105Halifax-Mt. Laurel 115kVIn Service
AC1-118Westmoreland 34.5kVIn Service
AC1-120Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-121Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-122Smith Mountain-Candler's Mountain 138kVIn Service
AC1-145Gretna DP 69 kVIn Service
AC1-147Grassfield 34.5kVIn Service
AC1-158Spotsylvania 500kVIn Service
AC1-161Septa 500kVIn Service
AC1-164Chickahominy 230kVPartially in Service - Under Construction
AC1-189Chinquapin-Everetts 230kVUnder Construction
AC1-191Elmont 115kVEngineering & Procurement
AC1-208Cox-Whitakers 115kVUnder Construction
AC1-221Halifax-Person 230kVIn Service
AC1-222Crystal Hill-Halifax 115kVIn Service
AC2-012Grassfield-Great Bridge 115kVIn Service
AC2-023Hebron 69kVEngineering & Procurement
AC2-079Ivor-Oak Ridge 115kVSuspended
AC2-100Halifax-Person 230kVIn Service
AC2-120Ripley 69kVIn Service
AC2-136East Hagerstown 12kVUnder Construction
AC2-137Elko 34.5kVIn Service
AC2-138Northern Neck 34.5kVIn Service
AC2-141Septa 500kVEngineering & Procurement
AC2-165Bremo-Powhatan 230kVSuspended
AC2-186Harrington 25kVUnder Construction
AC2-187Harrington 69kVUnder Construction
AC2-188Harrington 69 kVUnder Construction
AD1-017Smith Mountain-Bearskin 138 kVIn Service
AD1-020Hunterstown-Lincoln 115 kVIn Service
AD1-022Cashie-Trowbridge 230 kVEngineering & Procurement
AD1-025Hopewell-Surry 230 kVUnder Construction
AD1-033Fentress-Landstown 230 kVIn Service
AD1-041Harmony Village-Shackleford 115 kVIn Service
AD1-056Hornertown-Hathaway 230 kVSuspended
AD1-057Hornertown-Hathaway 230 kVSuspended
AD1-060Mercersburg-Milnor 34.5 kVIn Service
AD1-061McConnelsburg-Mercersburg 34 kVIn Service
AD1-063Harmony Village 34.5 kVIn Service
AD1-074Trowbridge 230 kVEngineering & Procurement
AD1-075Trowbridge 230 kVEngineering & Procurement
AD1-076Trowbridge 230 kVEngineering & Procurement
AD1-082Bakers Pond-Ivor 115kVIn Service
AD1-087Clover-Sedge Hill 230 kVIn Service
AD1-088Briery-Clover 230 kVSuspended
AD1-105Kings Dominion DP 115 kVUnder Construction
AD1-115Mountain Run-Mitchell 115 kVEngineering & Procurement
AD1-144Kings Fork 34.5 kVIn Service
AD1-151Hopewell-Surry 230 kVSuspended
AD1-152Clover-Sedge Hill 230 kVIn Service
AD1-155Meadow Brook-Strasburg 138 kVIn Service
AD2-009McConnellsburg 138 kVIn Service
AD2-027Camden Switch 26 kVIn Service
AD2-030Wan 34.5 kVIn Service
AD2-033Chase City-Lunenburg 115 kVUnder Construction
AD2-042Camden Switch 26 kV IIIn Service
AD2-058St. Barnabas 13 kVIn Service
AD2-065Atco 12 kVIn Service
AD2-070Gilbert-Morris Park 34.5kVIn Service
AD2-073Sanders DP 230 kVIn Service
AD2-074Garner DP-Lancaster 115 kVEngineering & Procurement
AD2-085Myrtle-Windsor DP 115kVEngineering & Procurement
AD2-115Lyons-Moselem 69kVIn Service
AD2-116Hokes-Grantley 69 kVIn Service
AD2-135Williamstown 12kVPartially in Service - Under Construction
AD2-160Hickory-Moyock 230kVIn Service
AD2-202Clover-Sedge Hill 230kVIn Service
AE1-041Edison 4kVIn Service
AE1-056Red House-South Creek 115 kVWithdrawn
AE1-071Shade Gap-Roxbury 115 kVIn Service
AE1-072Shawboro-Sligo 230 kVUnder Construction
AE1-074Winterpock 34.5 kVUnder Construction
AE1-075Powhatan 34.5 kVIn Service
AE1-081Landing 12.47 kVIn Service
AE1-100Axton 138 kVIn Service
AE1-101McConnellsburg-Texas Eastern 138 kVIn Service
AE1-103Holland-Union Camp 115 kVUnder Construction
AE1-108Bremo-Scottsville 138 kVEngineering & Procurement
AE1-142Manitou-Pleasant Plains 34.5 kVIn Service
AE1-148Kerr Dam-Ridge Rd 115 kVActive
AE1-149Disputanta-Poe 115 kVSuspended
AE1-153Remington-Gordonsville 230 kVSuspended
AE1-155Garner-Northern Neck 115 kVIn Service
AE1-156Quakertown Solar II 34.5 kVPartially in Service - Under Construction
AE1-157Ladysmith CT-St. Johns 230 kVSuspended
AE1-162Smithfield 34.5 kVIn Service
AE1-173Carson-Suffolk 500 kVUnder Construction
AE1-175Light Foot 34.5 kVIn Service
AE1-185Hokes-Jackson 69 kVIn Service
AE1-190Harmony Village-Shackleford 115 kVPartially in Service - Under Construction
AE1-191Harmony Village-Shackleford 115 kVPartially in Service - Under Construction
AE1-196Hokes-Jackson 69 kV IIIn Service
AE1-229Deepwater-Upper Pittsgrove 138 kVSuspended
AE1-250Smith Mountain-E. Danville 138 kVEngineering & Procurement
AE2-005Harmony Village-Shackleford 115 kVUnder Construction
AE2-019New Road 230 kVUnder Construction
AE2-027Harrowgate-Locks 115kVUnder Construction
AE2-029Grottoes-Merck 115kVUnder Construction
AE2-033Clubhouse-Sapony 230 kVSuspended
AE2-034Mackeys 230 kVPartially in Service - Under Construction
AE2-040Sapony 34.5 kVPartially in Service - Under Construction
AE2-041Harmony Village 230 kVEngineering & Procurement
AE2-042Milton 69 kVIn Service
AE2-047Ridgeway-Solite 69 kVEngineering & Procurement
AE2-051Carson-Septa 500 kVEngineering & Procurement
AE2-054Warfordsburg 34 kVIn Service
AE2-059Derry Tap-Derry Bus 69 kVIn Service
AE2-060Mifflintown Bus-Mifflintown Tap 69 kVIn Service
AE2-092Kidds Store-Sherwood 115 kVEngineering & Procurement
AE2-094Carson-Rogers Road 500 kVEngineering & Procurement
AE2-104Suffolk 115 kVSuspended
AE2-133Penns Tap-Richfield Tie 69 kVIn Service
AE2-140Axton-Danville 138 kVSuspended
AE2-156Yadkin 115 kVActive
AE2-166Stockton 138 kVSuspended
AE2-175Jackson-Long Pond 69 kVPartially in Service - Under Construction
AE2-183Rogers Road 500 kVIn Service
AE2-185Gladys DP-Stonemill Switching Station 69 kVActive
AE2-187Shockoe DP-Chatham 69 kVActive
AE2-212Harrowgate 34 kVEngineering & Procurement
AE2-226Millville-Old Chapel 138 kVEngineering & Procurement
AE2-230Bartonsville-Meadow Brook 138 kVIn Service
AE2-253Hickory-Moyock 230 kVIn Service
AE2-259Curdsville-Willis Mtn 115 kVEngineering & Procurement
AE2-283Gladys-Stone Mill 69 kVActive
AE2-291Grit DP-Perth 115 kVActive
AE2-346Ahoskie 34.5 kVIn Service
AF1-007Indian River 230 kV ISuspended
AF1-014Harmony Village-Shackleford 115 kVUnder Construction
AF1-017Myrtle-Windsor 115 kVEngineering & Procurement
AF1-018Harmony Village 230 kVEngineering & Procurement
AF1-028Endless Caverns 115 kVUnder Construction
AF1-032Suffolk 34.5 kVIn Service
AF1-042Garner DP-Lancaster 115 kVEngineering & Procurement
AF1-049Berry Hill 138 kVUnder Construction
AF1-058Welco 34.5 kVIn Service
AF1-069Carson-Rogers Rd 500 kVEngineering & Procurement
AF1-075Harrisburg-Endless Caverns 230 kVSuspended
AF1-114Oak Grove-Dahlgren 230 kVEngineering & Procurement
AF1-123Harper 230 kVActive
AF1-124Harper 230 kVActive
AF1-125Harper 230 kVActive
AF1-128Chesterfield 230 kVActive
AF1-129Chesterfield 230 kVEngineering & Procurement
AF1-136Warfordsburg-Purcell Junction 34.5 kVEngineering & Procurement
AF1-147Poland Rd-Runway DP 230kVUnder Construction
AF1-254Milnor-Huyetts 34.5 kVUnder Construction
AF1-262Upper Pittsgrove 12 kVIn Service
AF1-264Runnemede 13 kVIn Service
AF1-290Feagans Mill-Millville 138 kVIn Service
AF1-291Tyler 34.5 kVEngineering & Procurement
AF1-291ABartonsville-Meadow Brook 138 kVIn Service
AF1-292Fields 34.5kVEngineering & Procurement
AF1-294Jetersville-Ponton 115 kVActive
AF1-299Otter Point 34.5 kV IIn Service
AF1-300Otter Point 34.5 kV IIIn Service
AF1-320Merrill Creek 115 kVEngineering & Procurement
AF1-333Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-337Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-338Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-339Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF2-013Arnold's Corner-Dahlgren 230 kVEngineering & Procurement
AF2-035St. Johns 115 kVActive
AF2-042Clover-Rawlings 500 kVActive
AF2-043Suffolk 34.5 kVIn Service
AF2-046Tunis-Mapleton 115 kVActive
AF2-054Wan 34.5 kVIn Service
AF2-075Bartonsville-Meadow Brook 138 kV IIIIn Service
AF2-077White Marsh 34.5 kVIn Service
AF2-080Chinquapin-Everetts 230 kVActive
AF2-081Moyock 230 kVActive
AF2-085Midlothian 34.5 kVIn Service
AF2-086Scott Tap-Bowmans Mill Tap 69 kVEngineering & Procurement
AF2-091Oak Grove-Dahlgren 230 kVEngineering & Procurement
AF2-107Clifford 138 kVEngineering & Procurement
AF2-110Suffolk 115 kVSuspended
AF2-115Jetersville-Ponton 115 kVActive
AF2-120Garner-Northern Neck 115 kVActive
AF2-138Flanders-West Wharton 34.5 kVIn Service
AF2-139Gilbert-Warren Glen 34.5 kVIn Service
AF2-144Powhatan 34.5 kVIn Service
AF2-192Frenchtown Solar-West Flemington 34.5 kVSuspended
AF2-222Madisonville DP-Twitty's Creek 115 kVActive
AF2-229Roxbury 23 kVEngineering & Procurement
AF2-233Penns-Richfield Tie #1 69 kVEngineering & Procurement
AF2-234Sunbury Yard #1-Richfield Tie #2 69 kVEngineering & Procurement
AF2-247Bustleton 13.2 kVIn Service
AF2-250Edgewood 12 kV IIIIn Service
AF2-297Sedge Hill 115 kVActive
AF2-299Fields 34.5 kVActive
AF2-325Jacktown 12 kVEngineering & Procurement
AF2-354Washington 34.5 kV IIEngineering & Procurement
AF2-361Mifflintown Tap 69 kVEngineering & Procurement
AF2-378Cambridge 12 kVEngineering & Procurement
AF2-379Princess Anne 25 kVUnder Construction
AF2-383Tolna 115 kVWithdrawn
AF2-417West Damascus Tap-West Damascus 69 kVEngineering & Procurement
AF2-421East Hazelton-Weatherly Tap 69Engineering & Procurement
AF2-424Reed-Reed Tap #1 69 kVEngineering & Procurement
AF2-425Reed-Reed Tap#1 69 kVEngineering & Procurement
AF2-433Columbia-Geisinger Tap #1 69 kVEngineering & Procurement
AF2-434Columbia-Geisinger Tap #1 69 kVEngineering & Procurement
AG1-007Tar River 12.5 kVEngineering & Procurement
AG1-008Tunis-Mapleton 115 kVActive
AG1-021Jetersville-Ponton 115 kVActive
AG1-037Ahoskie 34.5 kVEngineering & Procurement
AG1-038Garner DP-Lancaster 115 kVEngineering & Procurement
AG1-082Ahoskie 34.5 kVActive
AG1-098Briery-Clover 230 kVActive
AG1-105Mount Laurel-Barnes Junction 115 kVActive
AG1-106Thelma 230 kVActive
AG1-124Gladstone 138 kVActive
AG1-135Garner-Lancaster 115 kVActive
AG1-145Lightfoot 34.5 kVIn Service
AG1-146Garner DP-Lancaster 115 kVActive
AG1-147Garner DP-Lancaster 115 kVActive
AG1-153Heritage 500 kVActive
AG1-154Ladysmith CT 230 kVActive
AG1-156Jack Frost-Lake Harmony 69 kVEngineering & Procurement
AG1-164East Hazelton-Weatherly Tap 69 kVEngineering & Procurement
AG1-165East Hazelton-Weatherly Tap 69 kVEngineering & Procurement
AG1-166Lone Pine 115 kVActive
AG1-167Lone Pine 115 kVActive
AG1-168Lone Pine 115 kVActive
AG1-188Manitou-Oyster Creek 34.5 kVEngineering & Procurement
AG1-189Oyster Creek-Bamber Lake 34.5Engineering & Procurement
AG1-191Chester-Pohatcong Mountain 34.5 kVPartially in Service - Under Construction
AG1-210Northern Neck 34.5 kVEngineering & Procurement
AG1-221Poland Rd-Runway DP 230 kVUnder Construction
AG1-223Larrabee-Allaire 34.5 kVUnder Construction
AG1-254Salem-Woodstown 69 kVEngineering & Procurement
AG1-259Sunbury-Dalmatia 69 kVEngineering & Procurement
AG1-260Sunbury-Dalmatia 69 kVEngineering & Procurement
AG1-282Dunnsville 34.5 kVEngineering & Procurement
AG1-285Chase City-Central 115 kVActive
AG1-342Dryburg 115 kVActive
AG1-348Pequest River-Washington 34.5 kVIn Service
AG1-393Sapony 34.5 kVActive
AG1-394Boykins 34.5 kVActive
AG1-397Walston 12 kVWithdrawn
AG1-469Gordonsville 34.5 kVEngineering & Procurement
AG1-480Shawnee 34.5 kVEngineering & Procurement
AG1-482Hamilton 115 kVWithdrawn
AG1-495Gilbert-Rocktown 34.5 kVEngineering & Procurement
AG1-499Lambs 12.47 kVUnder Construction
AG1-532Fields 34.5 kVEngineering & Procurement
AG1-536Garner-Northern Neck 115 kVActive
AG1-551Parmele 34.5 kVActive
AG1-552Carolina 34.5 kVActive
AG1-558Buckner 34.5 kVEngineering & Procurement
AG1-559Caroline Pines 22 kVEngineering & Procurement
AG2-005Garner DP-Lancaster 115 kVActive
AG2-010Peninsula-Whealton 115 kVActive
AG2-049Van Dorn 34.5 kVActive
AG2-068Heritage - Wake 500 kVActive
AG2-069Heritage - Wake 500 kVActive
AG2-077Clover-Rawlings 500 kVActive
AG2-086Mt. Jackson DP-Mt. Jackson 115 kVActive
AG2-088Midlothian 230 kVActive
AG2-093Colonial Trail-Hopewell 230 kVActive
AG2-095Hopewell 34.5 kV (Circuit 313)Active
AG2-111Perth 34.5 kV Substation (Circuit 408)Active
AG2-112Perth 34.5 kV Substation (Circuit 404)Active
AG2-120Everetts 34.5 kVActive
AG2-124Shackleford-Harmony 115 kVActive
AG2-151Trices Lake - James River Tap 115 kVActive
AG2-152Banister-Bear Skin 138 kVActive
AG2-171Lunenburg-Nutbush 115 kVActive
AG2-188Farmville - Buckingham 230 kVActive
AG2-193Turner 34.5 kVActive
AG2-198Briery - Finneywood 230 kVActive
AG2-208Greenwood DP - St. Johns DP 115 kVActive
AG2-213Gary D.P Tap - Gary D.P 115 kVActive
AG2-215Garner DP-Lancaster 115 kVActive
AG2-262Dryburg 115 kVActive
AG2-304Liberty 230 kVActive
AG2-320Ladysmith 230 kVActive
AG2-338Rogers Road - Carson 500 kVActive
AG2-339Rogers Road - Carson 500 kVActive
AG2-366Garner Delivery Point - Lancaster 115 kVActive
AG2-369Heritage - Wake 500 kVActive
AG2-382Cashie 230 kVActive
AG2-384Chesterfield 230 kVActive
AG2-426Wakefield - Waverly 115 kVActive
AG2-427Waverly 115 kVActive
AG2-428Wakefield 115 kVActive
AG2-436Carson - Rogers Road 500 kVActive
AG2-440Twittys Creek - Madisonville 115 kVActive
AG2-441Twittys Creek - Madisonville 115 kVActive
AG2-442Twittys Creek - Madisonville 115 kVActive
AG2-469Westmoreland – Oak Grove 230 kVActive
AG2-522Five Forks DP 115 kVActive
AG2-541Perth - Crystal Hill 115 kVActive
AG2-566Briery - Finneywood 230 kVActive
AG2-570Heritage - Wake 500 kVActive
AG2-571Heritage - Wake 500 kVActive
AG2-581Rawlings-Clover 500 kVActive
AG2-583Bremo - Cartersville 230 kVActive
AG2-659Kerr Dam – Hawtree 115 kVActive
AG2-661Hopewell - Colonial Trail 230 kVActive
AH1-012Louisa - North Anna 230 kVActive
AH1-033Sligo 34.5 kVActive
AH1-035Plymouth 34.5 kVActive
AH1-040Mackeys - Creswell 115 kVActive
AH1-042Providence Forge-Turner 115kVActive
AH1-056Red House DP 115kVActive
AH1-065Hopewell 34.5kVActive
AH1-066Hopewell 34.5kVActive
AH1-071Midlothian 34.5 kVActive
AH1-086Morrisville 230kVActive
AH1-087Morrisville 230kVActive
AH1-088Morrisville 230kVActive
AH1-089Morrisville 230kVActive
AH1-106Winterpock 34.5kVActive
AH1-107Winterpock 34.5kVActive
AH1-108Spruance NUG 230 kVActive
AH1-138Penniman 34.5 kVActive
AH1-157Penniman - Waller 230 kVActive
AH1-164Oak Level - Tank Hill 138 kVActive
AH1-170Columbia DP 115kVActive
AH1-215Central VA-Twitty 115 kVActive
AH1-216Smithfield-Surry 230 kVActive
AH1-217Kidds Store - Fork Union 115 kV IIActive
AH1-221Heritage 500 kVActive
AH1-223Poland Rd-Runway DP 230 kVActive
AH1-241Cobbs Creek - James River Industrial 115kVActive
AH1-251Todds Tavern- Spotsylvania/Goldsdale 115kVActive
AH1-263Chancellor 115 kVActive
AH1-271Cashie 230 kVActive
AH1-280Jetersville-Ponton 115 kVActive
AH1-311Heartsease DP - Mayo Dunbar 115kVActive
AH1-323Elmont 230 kVActive
AH1-324Colonial Trail – Surry 230 kVActive
AH1-343Crystal Hill DP- Perth 115kVActive
AH1-345Remington 324 34.5 kVActive
AH1-377Clover- Farmville 230kVActive
AH1-387Meadowbrook-Greenland Gap 500kVActive
AH1-396Gary 24.94 kVActive
AH1-397Shacklesford 34.5 kVActive
AH1-399North Doswell 12.5 kVActive
AH1-408Freeman DP – Lawrenceville 115 kVActive
AH1-439Buckingham- Farmville 230kVActive
AH1-528Rawlings - Unity 500 kVActive
AH1-546Bremo - Buckingham 230 kVActive
AH1-637Oak Grove 34.5 kVActive
AH1-676Gordonsville 230 kVActive
AH1-677Rogers Road 500 kVActive
AH1-678Heritage 500 kVActive
AH1-679Four Rivers 230 kVActive
AH1-681Cunningham 500 kVActive
AH1-682Ladysmith CT 230 kVActive
AH1-683Ladysmith CT 230 kVActive
AH1-684Remington CT 230 kVActive
AH1-685Remington CT 230 kVActive
AH1-687Bear Garden 230kVActive
AH1-691Ladysmith CT 230 kVActive
AH1-692Ladysmith CT 230 kVActive
AH1-693Remington CT 230 kVActive
AH1-694Ladysmith CT 230 kVActive
AH1-696Possum Point 230kVActive
AH1-712Cunningham 500 kVActive
AH1-713Mt. Storm 500kVActive
AH1-716Surry-Skiffes Creek 500kVActive
AH1-717Surry 230kVActive
AH1-729Ocean Court 230 kVActive
V4-067Cates Road Egg Harbor Township 12kVDeactivated
V4-068Murphy's 34.5kVIn Service
W1-003Oak HallIn Service
W1-004Oak HallIn Service
W1-005Oak HallIn Service
W1-006Oak HallIn Service
W1-130Vine Road 12kVIn Service
W2-030Egg Harbor TownshipIn Service
W3-077Broadway-Stewartsville 34.5kVIn Service
X3-066Church Hill 69kVIn Service
Y1-079Wye Mills 69kVIn Service
Y1-080Dorchester 12kVIn Service
Y1-086Morgans CornerIn Service
Y3-058Rockawalkin 69kVIn Service
Z1-036WinFall-Chowan 230kVIn Service
Z2-027Pasquotank 34.5kVIn Service
Z2-044Whitakers 34.5kVIn Service
Z2-076Worcester South 25kVIn Service
Z2-077Worcester North 25kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with potential Affected System impacts. PJM initiates coordination with each Affected System Operator by providing a list of New Service Requests in the Cycle with potential impacts to their respective system. If the Affected System Operator indicates an Affected System Study is required, PJM will notify the Project Developer or Eligible Customer of the need for an Affected System Study. See below if any Affected System Operator requires a study for this project:

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Phase I analysis results, this project may have a cost responsibility for the following System Reinforcements:

AH1-723 System Reinforcements:
TORTEP IDTitleAllocated Cost ($USD)
Dominionn9248.0 / TC1-PH2-DOM-042Construct new 41.13 mile line between North Anna and Midlothian with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN" at 145 degrees C. Station upgrades at North Anna and Midlothian to accommodate new line.$60,017,895
Dominionn9249.0 / TC1-PH2-DOM-043Construct new 37.26 mile line between Midlothian and Carson with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C. Station upgrades at Midlothian and Carson to accommodate new line.$34,511,925
Dominion(Pending) / TC2-PH1-DOM-0075Wreck and rebuild 18.75 miles of 500 kV Line 594 between Spotsylvania and Morrisville with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN"$14,640,609
PEPCO(Pending) / (Pending)Additional Aspen to Dickerson H 230 kV line$12,775,261
Dominion(Pending) / TC2-PH1-DOM-0071Wreck and rebuild 14.02 miles of 500 kV Line 573 between Spotsylvania and North Anna with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN".$12,065,519
Dominion(Pending) / TC2-PH1-DOM-2097Build a new 11.95 mile line from Aspen 230 kV to Dickerson 230 kV with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor at 250 degrees C.$4,908,903
Dominion(Pending) / TC2-PH1-DOM-2005Wreck and rebuild 5.74 mi of 230 kV Line 230 between Four Rivers and Hanover with (2) 768.2 ACSS/TW (20/7) "Maumee" conductor @ 250 Deg. C$4,049,226
PEPCO(Pending) / (Pending)TC2 Upgrade for BURCHES 500.0 kV to 8POSSUM 500.0 kV ckt 1$1,115,503
Dominion(Pending) / TC2-PH1-DOM-0072Replace 2-2500 ACAR 84/7 line lead on Line 573 at North Anna 500 kV$116,833
Dominion(Pending) / TC2-PH1-DOM-0073Replace Wave Trap 573WT at Spotsylvania 500 KV$116,833
Dominion(Pending) / TC2-PH1-DOM-0076Replace Wave Trap 594WT at Morrisville 500 KV$95,021
Dominion(Pending) / TC2-PH1-DOM-0077Replace Wave Trap 594WT at Spotsylvania 500 KV$95,021
Dominion(Pending) / TC2-PH1-DOM-0078Replace 3-1590 AAC 61 line lead on Line 594 at Morrisville 500 kV$95,021
Dominion(Pending) / TC2-PH1-DOM-2004Replace 2-1590 AAC 61 line lead on line 2032 at Four Rivers 230 kV.$92,821
Dominion(Pending)No overload on Dominion equipment for 8POSSUM - BURCHES (TC2)$0
Grand Total:$144,696,391

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: b4000.354
Type
Short Circuit
TO
Dominion
RTEP ID / TO ID
b4000.354
Title
Ladysmith substation breakers replacement: 574T575 and 568T581
Description
Expand Ladysmith substation to a add redundant circuit breakers to the middle breakers on both 500kV strings (574T575 and 568T581). The equipment including switches 57518, 57515, H115 will be replaced with 5000A equipment.
Cost Information
Time Estimate
Nov 14 2029

Contingent

Note: Although AH1-723 may not presently have cost responsibility for this upgrade, AH1-723 may need this upgrade in-service to be deliverable to the PJM system. If AH1-723 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P4-2: 568T581_SRT-S
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P2-2: LADYSMITH B2_SRT-S
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P4-2: H1T581_SRT-S
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P4-2: H4T581_SRT-S
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P4-2: 568T581_SRT-S

System Reinforcement: n9248.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9248.0 / TC1-PH2-DOM-042
Title
Construct new 41.13 mile line between North Anna and Midlothian with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN" at 145 degrees C. Station upgrades at North Anna and Midlothian to accommodate new line.
Description
Construct new 41.13 mile line between North Anna and Midlothian with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN" at 145 degrees C. Station upgrades at North Anna and Midlothian to accommodate new line.
Total Cost ($USD)
$345,766,000
Allocated Cost ($USD)
$60,017,895
Time Estimate
48 to 60 Months

Contributor

FacilityContingency
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P1-2: LN 576_SRT-S
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 lineDVP_P1-2: LN 557_SRT-S
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P4-2: WT576_SRT-S
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P4-2: 57602_SRT-S
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 lineDVP_P4-2: 557T574_SRT-S
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-088
49.1 MW3.2%$10,967,705
AG2-338
12.3 MW0.8%$2,748,846
AG2-339
30.8 MW2.0%$6,872,339
AG2-428
79.4 MW5.1%$17,734,681
AG2-436
235.2 MW15.2%$52,507,120
AG2-570
114.4 MW7.4%$25,532,306
AG2-571
22.2 MW1.4%$4,965,737
AH1-528
104.3 MW6.7%$23,286,172
AH1-681
10.3 MW0.7%$2,301,272
AH1-712
230.7 MW14.9%$51,504,150
AH1-716
391.2 MW25.3%$87,327,776
AH1-723
268.9 MW17.4%$60,017,895

System Reinforcement: n9249.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9249.0 / TC1-PH2-DOM-043
Title
Construct new 37.26 mile line between Midlothian and Carson with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C. Station upgrades at Midlothian and Carson to accommodate new line.
Description
Construct new 37.26 mile line between Midlothian and Carson with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C. Station upgrades at Midlothian and Carson to accommodate new line. New Rating = 4356/4356/5009 MVA
Total Cost ($USD)
$231,012,000
Allocated Cost ($USD)
$34,511,925
Time Estimate
48 to 60 Months

Contributor

FacilityContingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
11.5 MW0.9%$2,162,271
AG2-069
17.3 MW1.4%$3,243,406
AG2-077
42.8 MW3.5%$8,054,092
AG2-369
13.6 MW1.1%$2,549,532
AG2-436
223.5 MW18.2%$42,020,468
AG2-440
6.8 MW0.6%$1,283,978
AG2-441
8.5 MW0.7%$1,605,066
AG2-442
14.7 MW1.2%$2,762,902
AG2-570
29.3 MW2.4%$5,515,652
AG2-571
11.7 MW1.0%$2,206,261
AG2-581
34.4 MW2.8%$6,460,118
AH1-528
98.4 MW8.0%$18,504,880
AH1-681
7.0 MW0.6%$1,323,268
AH1-712
157.5 MW12.8%$29,616,268
AH1-716
368.1 MW30.0%$69,191,915
AH1-723
183.6 MW14.9%$34,511,925

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0075
Title
Wreck and rebuild 18.75 miles of 500 kV Line 594 between Spotsylvania and Morrisville with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN"
Description
Wreck and rebuild 18.75 miles of 500 kV Line 594 between Spotsylvania and Morrisville with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN"
Total Cost ($USD)
$110,625,000
Allocated Cost ($USD)
$14,640,609
Time Estimate
18 to 60 Months

Contributor

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P2-2: MORRISVILLE B1_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P4-2: 545T552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 581_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P4-2: H1T552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P4-2: H3T552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 550_SRT-A
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-088
34.7 MW5.3%$5,883,523
AG2-428
33.0 MW5.1%$5,604,107
AG2-436
82.7 MW12.7%$14,035,461
AG2-570
61.7 MW9.5%$10,463,443
AG2-571
7.8 MW1.2%$1,324,471
AH1-263
59.0 MW9.0%$10,010,303
AH1-528
48.5 MW7.4%$8,233,540
AH1-676
160.9 MW24.7%$27,304,435
AH1-681
3.3 MW0.5%$561,378
AH1-712
74.1 MW11.4%$12,563,732
AH1-723
86.3 MW13.2%$14,640,609

System Reinforcement
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
(Pending) / (Pending)
Title
Additional Aspen to Dickerson H 230 kV line
Description
PEPCO’s substation cost to accommodate an additional circuit at Dickerson H to be approximately $7.86 million. The cost for the remaining 7.25 miles of 230 kV transmission line is estimated at $78.62 million.
Total Cost ($USD)
$86,480,000
Allocated Cost ($USD)
$12,775,261
Time Estimate
24 to 48 Months

Contributor

FacilityContingency
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-304
29.6 MW5.1%$4,408,470
AG2-436
55.1 MW9.5%$8,218,034
AG2-570
42.2 MW7.3%$6,292,831
AG2-571
5.3 MW0.9%$796,553
AH1-528
16.3 MW2.8%$2,428,713
AH1-676
184.1 MW31.7%$27,439,654
AH1-681
3.3 MW0.6%$489,797
AH1-712
73.5 MW12.7%$10,963,043
AH1-723
85.7 MW14.8%$12,775,261
AH1-727
70.4 MW12.1%$10,496,797
AH1-729
14.6 MW2.5%$2,170,846

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0071
Title
Wreck and rebuild 14.02 miles of 500 kV Line 573 between Spotsylvania and North Anna with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN".
Description
Wreck and rebuild 14.02 miles of 500 kV Line 573 between Spotsylvania and North Anna with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN".
Total Cost ($USD)
$82,718,000
Allocated Cost ($USD)
$12,065,519
Time Estimate
18 to 48 Months

Contributor

FacilityContingency
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 552_SRT-S
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 581_SRT-S
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-088
35.4 MW5.9%$4,892,618
AG2-436
84.8 MW14.2%$11,707,917
AH1-528
37.7 MW6.3%$5,201,462
AH1-676
136.3 MW22.8%$18,825,984
AH1-681
3.3 MW0.6%$462,576
AH1-712
75.0 MW12.5%$10,354,029
AH1-716
139.1 MW23.2%$19,207,896
AH1-723
87.4 MW14.6%$12,065,519

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2097
Title
Build a new 11.95 mile line from Aspen 230 kV to Dickerson 230 kV with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor at 250 degrees C.
Description
Build a new 11.95 mile line from Aspen 230 kV to Dickerson 230 kV with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor at 250 degrees C.
Total Cost ($USD)
$33,230,000
Allocated Cost ($USD)
$4,908,903
Time Estimate
48 to 60 Months

Contributor

FacilityContingency
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 lineAP_P2-3_PE-500-019B_SRT-A
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 lineAP_P2-3_PE-500-019F_SRT-SL
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 lineAP_P1-2_PE-500-406T_SRT-A
DICKH230-6EDFERRY 230.0 kV Ckt 1 lineAP_P2-3_PE-500-019F_SRT-SL
DICKH230-6EDFERRY 230.0 kV Ckt 1 lineAP_P2-3_PE-500-019B_SRT-A
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 linePEPCO_P1_5070_SRT-A
DICKH230-6EDFERRY 230.0 kV Ckt 1 linePEPCO_P1_5070_SRT-A
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-304
29.6 MW5.1%$1,693,958
AG2-436
55.1 MW9.5%$3,157,785
AG2-570
42.2 MW7.3%$2,418,025
AG2-571
5.3 MW0.9%$306,076
AH1-528
16.3 MW2.8%$933,235
AH1-676
184.1 MW31.7%$10,543,706
AH1-681
3.3 MW0.6%$188,205
AH1-712
73.5 MW12.7%$4,212,557
AH1-723
85.7 MW14.8%$4,908,903
AH1-727
70.4 MW12.1%$4,033,401
AH1-729
14.6 MW2.5%$834,149

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2005
Title
Wreck and rebuild 5.74 mi of 230 kV Line 230 between Four Rivers and Hanover with (2) 768.2 ACSS/TW (20/7) "Maumee" conductor @ 250 Deg. C
Description
Wreck and rebuild 5.74 mi of 230 kV Line 230 between Four Rivers and Hanover with (2) 768.2 ACSS/TW (20/7) "Maumee" conductor @ 250 Deg. C
Total Cost ($USD)
$21,812,000
Allocated Cost ($USD)
$4,049,226
Time Estimate
36 to 42 Months

Contributor

FacilityContingency
6FOUR RIVERS-6HANOVER 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-208
44.2 MW14.7%$3,211,365
AG2-428
16.9 MW5.6%$1,225,332
AG2-436
33.3 MW11.1%$2,420,004
AG2-570
25.2 MW8.4%$1,830,551
AG2-571
3.2 MW1.1%$231,698
AH1-042
14.3 MW4.8%$1,038,099
AH1-323
18.0 MW6.0%$1,306,488
AH1-528
19.6 MW6.5%$1,424,771
AH1-679
19.9 MW6.6%$1,444,315
AH1-681
2.1 MW0.7%$155,264
AH1-712
47.8 MW15.9%$3,474,886
AH1-723
55.7 MW18.6%$4,049,226

System Reinforcement
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
(Pending) / (Pending)
Title
TC2 Upgrade for BURCHES 500.0 kV to 8POSSUM 500.0 kV ckt 1
Description
Replaces the terminal equipment at Burches Hill 500 kV station (breakers, switches, and stranded bus) that upgrades the ratings.
Total Cost ($USD)
$6,000,000
Allocated Cost ($USD)
$1,115,503
Time Estimate
48 to 60 Months

Contributor

FacilityContingency
BURCHES-8POSSUM 500.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-436
52.6 MW11.7%$703,728
AG2-570
40.5 MW9.0%$541,355
AG2-571
5.1 MW1.1%$68,527
AH1-528
31.1 MW6.9%$416,240
AH1-676
161.2 MW35.9%$2,154,606
AH1-681
3.2 MW0.7%$42,766
AH1-712
71.6 MW16.0%$957,274
AH1-723
83.4 MW18.6%$1,115,503

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0072
Title
Replace 2-2500 ACAR 84/7 line lead on Line 573 at North Anna 500 kV
Description
Replace 2-2500 ACAR 84/7 line lead on Line 573 at North Anna 500 kV
Total Cost ($USD)
$600,000
Allocated Cost ($USD)
$116,833
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 581_SRT-S
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-088
35.9 MW7.8%$47,005
AG2-436
86.0 MW18.7%$112,489
AH1-528
38.2 MW8.3%$49,971
AH1-676
129.2 MW28.2%$168,963
AH1-681
3.4 MW0.7%$4,480
AH1-712
76.6 MW16.7%$100,259
AH1-723
89.3 MW19.5%$116,833

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0073
Title
Replace Wave Trap 573WT at Spotsylvania 500 KV
Description
Replace Wave Trap 573WT at Spotsylvania 500 KV
Total Cost ($USD)
$600,000
Allocated Cost ($USD)
$116,833
Time Estimate
16 to 18 Months

Contributor

FacilityContingency
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 581_SRT-S
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-088
35.9 MW7.8%$47,005
AG2-436
86.0 MW18.7%$112,489
AH1-528
38.2 MW8.3%$49,971
AH1-676
129.2 MW28.2%$168,963
AH1-681
3.4 MW0.7%$4,480
AH1-712
76.6 MW16.7%$100,259
AH1-723
89.3 MW19.5%$116,833

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0076
Title
Replace Wave Trap 594WT at Morrisville 500 KV
Description
Replace Wave Trap 594WT at Morrisville 500 KV
Total Cost ($USD)
$600,000
Allocated Cost ($USD)
$95,021
Time Estimate
16 to 18 Months

Contributor

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 581_SRT-S
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-088
35.3 MW6.3%$37,901
AG2-436
84.4 MW15.1%$90,521
AH1-263
60.4 MW10.8%$64,771
AH1-528
37.5 MW6.7%$40,233
AH1-676
173.8 MW31.1%$186,369
AH1-681
3.4 MW0.6%$3,643
AH1-712
76.0 MW13.6%$81,542
AH1-723
88.6 MW15.8%$95,021

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0077
Title
Replace Wave Trap 594WT at Spotsylvania 500 KV
Description
Replace Wave Trap 594WT at Spotsylvania 500 KV
Total Cost ($USD)
$600,000
Allocated Cost ($USD)
$95,021
Time Estimate
16 to 18 Months

Contributor

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 581_SRT-S
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-088
35.3 MW6.3%$37,901
AG2-436
84.4 MW15.1%$90,521
AH1-263
60.4 MW10.8%$64,771
AH1-528
37.5 MW6.7%$40,233
AH1-676
173.8 MW31.1%$186,369
AH1-681
3.4 MW0.6%$3,643
AH1-712
76.0 MW13.6%$81,542
AH1-723
88.6 MW15.8%$95,021

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0078
Title
Replace 3-1590 AAC 61 line lead on Line 594 at Morrisville 500 kV
Description
Replace 3-1590 AAC 61 line lead on Line 594 at Morrisville 500 kV
Total Cost ($USD)
$600,000
Allocated Cost ($USD)
$95,021
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 581_SRT-S
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-088
35.3 MW6.3%$37,901
AG2-436
84.4 MW15.1%$90,521
AH1-263
60.4 MW10.8%$64,771
AH1-528
37.5 MW6.7%$40,233
AH1-676
173.8 MW31.1%$186,369
AH1-681
3.4 MW0.6%$3,643
AH1-712
76.0 MW13.6%$81,542
AH1-723
88.6 MW15.8%$95,021

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2004
Title
Replace 2-1590 AAC 61 line lead on line 2032 at Four Rivers 230 kV.
Description
Replace 2-1590 AAC 61 line lead on line 2032 at Four Rivers 230 kV.
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$92,821
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6FOUR RIVERS-6HANOVER 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-208
44.2 MW14.7%$73,615
AG2-428
16.9 MW5.6%$28,088
AG2-436
33.3 MW11.1%$55,474
AG2-570
25.2 MW8.4%$41,962
AG2-571
3.2 MW1.1%$5,311
AH1-042
14.3 MW4.8%$23,797
AH1-323
18.0 MW6.0%$29,949
AH1-528
19.6 MW6.5%$32,660
AH1-679
19.9 MW6.6%$33,108
AH1-681
2.1 MW0.7%$3,559
AH1-712
47.8 MW15.9%$79,655
AH1-723
55.7 MW18.6%$92,821

System Reinforcement: b3800.300
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.300
Title
Wreck/Rebuild 230kV Line #2135 segment Hollymeade Junction – Cash’s Corner using double-circuit capable 230 kV poles. (The second 230kV circuit will be wired but not have terminal ends.)
Description
Wreck/Rebuild 230kV Line #2135 segment Hollymeade Junction – Cash’s Corner using double-circuit capable 230 kV poles. (The second 230kV circuit will be wired but not have terminal ends.)
Cost Information
Time Estimate
Jun 30 2028

Contingent

Note: Although AH1-723 may not presently have cost responsibility for this upgrade, AH1-723 may need this upgrade in-service to be deliverable to the PJM system. If AH1-723 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6CASHSCORNER-6HOLLYMD 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.302
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.302
Title
Upgrade Cash's Corner switches 213576 and 213579 and line leads to 4000A continuous current rating of 230kV Line #2135.
Description
Upgrade Cash's Corner switches 213576 and 213579 and line leads to 4000A continuous current rating of 230kV Line #2135.
Cost Information
Time Estimate
Jun 30 2028

Contingent

Note: Although AH1-723 may not presently have cost responsibility for this upgrade, AH1-723 may need this upgrade in-service to be deliverable to the PJM system. If AH1-723 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6CASHSCORNER-6HOLLYMD 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AH1-723 may not presently have cost responsibility for this upgrade, AH1-723 may need this upgrade in-service to be deliverable to the PJM system. If AH1-723 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
6LDYSMITH CT-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6SUMMIT-6LDYSMITH CT 230.0 kV Ckt 1 line(Any)
6ELMONT-6HANOVER 230.0 kV Ckt 1 line(Any)
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
8ELMONT-8CUNINGHAM 500.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
6FREDBRG-6MINE RD 230.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6SUMMIT-6MINE RD 230.0 kV Ckt 1 line(Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.355
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.355
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AH1-723 may not presently have cost responsibility for this upgrade, AH1-723 may need this upgrade in-service to be deliverable to the PJM system. If AH1-723 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6SUMMIT-6MINE RD 230.0 kV Ckt 1 line(Any)
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
6LDYSMITH CT-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6SUMMIT-6LDYSMITH CT 230.0 kV Ckt 1 line(Any)
6ELMONT-6HANOVER 230.0 kV Ckt 1 line(Any)
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
6FREDBRG-6MINE RD 230.0 kV Ckt 1 line(Any)
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8ELMONT-8CUNINGHAM 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029

Contingent

Note: Although AH1-723 may not presently have cost responsibility for this upgrade, AH1-723 may need this upgrade in-service to be deliverable to the PJM system. If AH1-723 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6SUMMIT-6MINE RD 230.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
6LDYSMITH CT-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
6ELMONT-6HANOVER 230.0 kV Ckt 1 line(Any)
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
6SUMMIT-6LDYSMITH CT 230.0 kV Ckt 1 line(Any)
6FREDBRG-6MINE RD 230.0 kV Ckt 1 line(Any)
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8ELMONT-8CUNINGHAM 500.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029

Contingent

Note: Although AH1-723 may not presently have cost responsibility for this upgrade, AH1-723 may need this upgrade in-service to be deliverable to the PJM system. If AH1-723 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6SUMMIT-6MINE RD 230.0 kV Ckt 1 line(Any)
6LDYSMITH CT-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
6SUMMIT-6LDYSMITH CT 230.0 kV Ckt 1 line(Any)
6ELMONT-6HANOVER 230.0 kV Ckt 1 line(Any)
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
6FREDBRG-6MINE RD 230.0 kV Ckt 1 line(Any)
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8ELMONT-8CUNINGHAM 500.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.343
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.343
Title
Uprate bus at Brambleton to support 500kV Line #558 (Aspen to Brambleton) uprate.
Description
Uprate bus at Brambleton to support 500kV Line #558 (Aspen to Brambleton) uprate.
Cost Information
Time Estimate
Nov 28 2025

Contingent

Note: Although AH1-723 may not presently have cost responsibility for this upgrade, AH1-723 may need this upgrade in-service to be deliverable to the PJM system. If AH1-723 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8BRAMBLETON-AH1-727 TP 500.0 kV Ckt 1 line(Any)

System Reinforcement: n9139.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9139.0 / TC1-PH1-DOM-073
Title
Wreck and rebuild 37.41 miles of 500kV line 563 between Midlothian and Carson with (3) 1351.5 ACSR (45/7) "Dipper" and associated substation work.
Description
Wreck and rebuild 37.41 miles of 500kV transmission line 563 between Midlothian and Carson with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C and associated substation work to achieve new rating of 4356/4356/5009 MVA. Remove wave traps.
Total Cost ($USD)
$245,455,768
Allocated Cost ($USD)
$0
Time Estimate
69 to 70 Months

Contingent

Note: Based on PJM cost allocation criteria, AH1-723 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-723 could receive cost allocation. Although AH1-723 may not presently have cost responsibility for this upgrade, AH1-723 may need this upgrade in-service to be deliverable to the PJM system. If AH1-723 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S

System Reinforcement: n9191.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9191.0 / TC1-PH1-DOM-090
Title
Rebuild 41.13 miles of line 576 between North Anna and Midlothian with triple bundled (3) 1351.5 ACSR (45/7) "Dipper" conductor and associated substation work.
Description
Rebuild 41.13 miles of line 576 between North Anna and Midlothian with triple bundled (3) 1351.5 ACSR (45/7) "Dipper" conductor at 110 degrees C and associated substation work to achieve new rating of 4356/4356/5009 MVA.
Total Cost ($USD)
$256,706,175
Allocated Cost ($USD)
$0
Time Estimate
74 to 75 Months

Contingent

Note: Based on PJM cost allocation criteria, AH1-723 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-723 could receive cost allocation. Although AH1-723 may not presently have cost responsibility for this upgrade, AH1-723 may need this upgrade in-service to be deliverable to the PJM system. If AH1-723 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P1-2: LN 576_SRT-S
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P4-2: WT576_SRT-S
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P4-2: 57602_SRT-S
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.353
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.353
Title
Upgrade 500kV terminal equipment at Elmont substation.
Description
Upgrade 500kV terminal equipment at Elmont substation.
Cost Information
Time Estimate
Jun 01 2028

Contingent

Note: Although AH1-723 may not presently have cost responsibility for this upgrade, AH1-723 may need this upgrade in-service to be deliverable to the PJM system. If AH1-723 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P2-2: ELMONT B1_SRT-S
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P4-2: H1T553_SRT-S

System Reinforcement: b4000.325
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.325
Title
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Description
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Cost Information
Time Estimate
Feb 24 2029

Contingent

Note: Although AH1-723 may not presently have cost responsibility for this upgrade, AH1-723 may need this upgrade in-service to be deliverable to the PJM system. If AH1-723 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6SUMMIT-6MINE RD 230.0 kV Ckt 1 line(Any)
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
6LDYSMITH CT-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
6SUMMIT-6LDYSMITH CT 230.0 kV Ckt 1 line(Any)
6ELMONT-6HANOVER 230.0 kV Ckt 1 line(Any)
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
6FREDBRG-6MINE RD 230.0 kV Ckt 1 line(Any)
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8ELMONT-8CUNINGHAM 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.326
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.326
Title
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Description
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Cost Information
Time Estimate
Feb 24 2029

Contingent

Note: Although AH1-723 may not presently have cost responsibility for this upgrade, AH1-723 may need this upgrade in-service to be deliverable to the PJM system. If AH1-723 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
6LDYSMITH CT-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
6SUMMIT-6LDYSMITH CT 230.0 kV Ckt 1 line(Any)
6ELMONT-6HANOVER 230.0 kV Ckt 1 line(Any)
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
8ELMONT-8CUNINGHAM 500.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
6FREDBRG-6MINE RD 230.0 kV Ckt 1 line(Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6SUMMIT-6MINE RD 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.327
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.327
Title
Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.
Description
Upgrade/install equipment at Ladysmith substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230kV strings of breaker and a half scheme.
Cost Information
Time Estimate
Feb 24 2029

Contingent

Note: Although AH1-723 may not presently have cost responsibility for this upgrade, AH1-723 may need this upgrade in-service to be deliverable to the PJM system. If AH1-723 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6SUMMIT-6MINE RD 230.0 kV Ckt 1 line(Any)
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
6LDYSMITH CT-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6SUMMIT-6LDYSMITH CT 230.0 kV Ckt 1 line(Any)
6ELMONT-6HANOVER 230.0 kV Ckt 1 line(Any)
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
8ELMONT-8CUNINGHAM 500.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
6FREDBRG-6MINE RD 230.0 kV Ckt 1 line(Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Contingent

Note: Although AH1-723 may not presently have cost responsibility for this upgrade, AH1-723 may need this upgrade in-service to be deliverable to the PJM system. If AH1-723 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
6LDYSMITH CT-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
6SUMMIT-6LDYSMITH CT 230.0 kV Ckt 1 line(Any)
6ELMONT-6HANOVER 230.0 kV Ckt 1 line(Any)
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
8ELMONT-8CUNINGHAM 500.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
6FREDBRG-6MINE RD 230.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6SUMMIT-6MINE RD 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

Contingent

Note: Although AH1-723 may not presently have cost responsibility for this upgrade, AH1-723 may need this upgrade in-service to be deliverable to the PJM system. If AH1-723 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
6LDYSMITH CT-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
6SUMMIT-6LDYSMITH CT 230.0 kV Ckt 1 line(Any)
6ELMONT-6HANOVER 230.0 kV Ckt 1 line(Any)
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
8ELMONT-8CUNINGHAM 500.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
6FREDBRG-6MINE RD 230.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6SUMMIT-6MINE RD 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Contingent

Note: Although AH1-723 may not presently have cost responsibility for this upgrade, AH1-723 may need this upgrade in-service to be deliverable to the PJM system. If AH1-723 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6LDYSMITH CT-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
6SUMMIT-6LDYSMITH CT 230.0 kV Ckt 1 line(Any)
6ELMONT-6HANOVER 230.0 kV Ckt 1 line(Any)
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
6FREDBRG-6MINE RD 230.0 kV Ckt 1 line(Any)
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8ELMONT-8CUNINGHAM 500.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
6SUMMIT-6MINE RD 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Contingent

Note: Although AH1-723 may not presently have cost responsibility for this upgrade, AH1-723 may need this upgrade in-service to be deliverable to the PJM system. If AH1-723 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
6LDYSMITH CT-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
6SUMMIT-6LDYSMITH CT 230.0 kV Ckt 1 line(Any)
6ELMONT-6HANOVER 230.0 kV Ckt 1 line(Any)
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
8ELMONT-8CUNINGHAM 500.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
6FREDBRG-6MINE RD 230.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6SUMMIT-6MINE RD 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Kraken to accommodate the new 500kV line from North Anna to Kraken.
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AH1-723 may not presently have cost responsibility for this upgrade, AH1-723 may need this upgrade in-service to be deliverable to the PJM system. If AH1-723 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
6LDYSMITH CT-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6SUMMIT-6LDYSMITH CT 230.0 kV Ckt 1 line(Any)
6ELMONT-6HANOVER 230.0 kV Ckt 1 line(Any)
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
8ELMONT-8CUNINGHAM 500.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
6FREDBRG-6MINE RD 230.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6SUMMIT-6MINE RD 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Kraken substation into Yeat substation
Description
Cut-in 500kV line from Kraken substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AH1-723 may not presently have cost responsibility for this upgrade, AH1-723 may need this upgrade in-service to be deliverable to the PJM system. If AH1-723 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6SUMMIT-6MINE RD 230.0 kV Ckt 1 line(Any)
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
6LDYSMITH CT-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
6SUMMIT-6LDYSMITH CT 230.0 kV Ckt 1 line(Any)
6ELMONT-6HANOVER 230.0 kV Ckt 1 line(Any)
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
6FREDBRG-6MINE RD 230.0 kV Ckt 1 line(Any)
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8ELMONT-8CUNINGHAM 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Contingent

Note: Although AH1-723 may not presently have cost responsibility for this upgrade, AH1-723 may need this upgrade in-service to be deliverable to the PJM system. If AH1-723 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6SUMMIT-6MINE RD 230.0 kV Ckt 1 line(Any)
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
6LDYSMITH CT-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
6SUMMIT-6LDYSMITH CT 230.0 kV Ckt 1 line(Any)
6ELMONT-6HANOVER 230.0 kV Ckt 1 line(Any)
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
6FREDBRG-6MINE RD 230.0 kV Ckt 1 line(Any)
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8ELMONT-8CUNINGHAM 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Contingent

Note: Although AH1-723 may not presently have cost responsibility for this upgrade, AH1-723 may need this upgrade in-service to be deliverable to the PJM system. If AH1-723 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
6LDYSMITH CT-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
6SUMMIT-6LDYSMITH CT 230.0 kV Ckt 1 line(Any)
6ELMONT-6HANOVER 230.0 kV Ckt 1 line(Any)
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
6FREDBRG-6MINE RD 230.0 kV Ckt 1 line(Any)
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8ELMONT-8CUNINGHAM 500.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6SUMMIT-6MINE RD 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.356
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AH1-723 may not presently have cost responsibility for this upgrade, AH1-723 may need this upgrade in-service to be deliverable to the PJM system. If AH1-723 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
6LDYSMITH CT-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
6SUMMIT-6LDYSMITH CT 230.0 kV Ckt 1 line(Any)
6ELMONT-6HANOVER 230.0 kV Ckt 1 line(Any)
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
8ELMONT-8CUNINGHAM 500.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
6FREDBRG-6MINE RD 230.0 kV Ckt 1 line(Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6SUMMIT-6MINE RD 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending)
Title
No overload on Dominion equipment for 8POSSUM - BURCHES (TC2)
Description
Dominion End Ratings Winter: 5414/5581/6107 Light Load: 5227/5388/5941 Summer: 4257/4388/5046
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
BURCHES-8POSSUM 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.242
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.242
Title
Upgrading switches 20366M and 20369M and line leads to 4000A continuous current rating of 230kV Line #203 at Edwards Ferry substation
Description
Upgrading switches 20366M and 20369M and line leads to 4000A continuous current rating of 230kV Line #203 at Edwards Ferry substation
Cost Information
Time Estimate
Sep 13 2030

Contingent

Note: Although AH1-723 may not presently have cost responsibility for this upgrade, AH1-723 may need this upgrade in-service to be deliverable to the PJM system. If AH1-723 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.244
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b3800.244
Title
Rebuild 7.26 miles of existing 230 kV circuit from Dickerson Station H to Ed's Ferry area to accommodate the new 500 kV circuit between Doubs and Aspen. (The 230kV portion of the project)
Description
Rebuild 7.26 miles of existing 230 kV circuit from Dickerson Station H to Ed's Ferry area to accommodate the new 500 kV circuit between Doubs and Aspen. (The 230kV portion of the project)
Cost Information
Time Estimate
Dec 31 2030

Contingent

Note: Although AH1-723 may not presently have cost responsibility for this upgrade, AH1-723 may need this upgrade in-service to be deliverable to the PJM system. If AH1-723 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
          AE2-094 500 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-338, AG2-339
        
          AG2-570 500 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-570, AG2-571
        
          Cunningham 500 kV (Dominion): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AH1-681, AH1-712, AH1-723
        
          AG2-068 500 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-068, AG2-069, AG2-369
        
          AG2-440 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-440, AG2-441, AG2-442
        

Attachments

AH1-723 One Line Diagram

AH1-723 One Line Diagram.pdf
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.