AG2-104 Phase II System Impact Study Report

v1.00 released 2026-06-03 18:10

Marysville-Flatlick 765 kV

126.85 MW Capacity / 200.0 MW Energy

Introduction

This Phase II System Impact Study (SIS) Report has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 310 for New Service Requests (projects) in Transition Cycle 2 (TC2). The Project Developer/Eligible Customer (developer) is Oak Run Solar Project, LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is AEP Ohio Transmission Company, Inc..

Preface

The Phase II System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle summary format and (ii) an individual project-level basis. The Phase II System Impact Study Results (for both the summary and individual reports) will be publicly available on PJM’s website. Project Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.5, PJM takes the following actions during the Phase II System Impact Study:

  1. PJM will retool load flow results from the Phase I System Impact Study (summer peak, winter peak and light load) based on decisions made by Project Developers or Eligible Customers during Decision Point I.
  2. PJM will conduct any required voltage analyses.
  3. PJM will perform short circuit and stability analyses as required.
  4. PJM will coordinate with the Affected System to confirm which projects in the PJM Cycle will require Affected System studies. If the Affected System Operator indicates that an Affected System study is required, PJM will:
    1. Notify the Project Developer or Eligible Customer of the need for an Affected System study and the requirement to execute an Affected System study agreement with the impacted Affected System Operator, and;
    2. Include the results of the Affected System Operator’s Affected System Study in the Phase II System Impact Study results, if applicable and available.
  5. The Phase II System Impact Study Results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.

The Transmission Owner takes the following actions during the Phase II System Impact Study:

  1. Verify Interconnection Facilities and Network Upgrades required to accommodate the New Service Request.
  2. Perform a Facilities Study. The Facilities Study in Phase II System Impact Study phase will be for the physical Interconnection Facilities. The Facilities Study requirements are outlined in Attachment C of this manual. The study will be conducted pursuant to Tariff, Part VII, Subpart D, section 307(A)(7) and Tariff, Part VIII, Subpart C, section 404(A)(7).

Decision Point II Requirements

At the close of Phase II System Impact Study, PJM will initiate Decision Point II (DP2). During DP2, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.A. Additional information on these elements is available in PJM Manual 14H sections 4.6, 6, and 7.

Allowable project modifications at Decision Point II are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

Adverse Test Eligibility

This New Service Request does not meet the Adverse Study Impact Criteria and has the option to either move forward in the Cycle process or withdraw at DP2 with Readiness Deposit #1 forfeited. See adverse study impact calculation below.

This section details whether a Project Developer or Eligible Customer qualifies for the Adverse Study Impact clause outlined in the PJM OATT, Part VII, Subpart D, section 311.B and Manual 14H, section 6.2.2. In order to qualify for an Adverse Study Impact at Decision Point II, the Network Upgrade cost from Phase I to Phase II must:

  1. Increase overall by 25% or more
  2. Increases by more than $10,000 per MW (Includes Costs identified in Affected System studies)

If a New Service Request meets the criteria above and chooses to withdraw the request, PJM will refund the cumulative Readiness Deposit amounts paid at the Application Phase and at Decision Point I (RD1 and RD2, respectively).

The below calculations show the computation of this New Service Request's Adverse Study Impact

DP2 Adverse Eligibility = DP2 Adverse Cost Alloc DP1 Adverse Cost Alloc > 1.25 AND ( DP2 Adverse Cost Alloc - DP1 Adverse Cost Alloc ) Project Size > $10,000 per MW
DP2 Adverse Eligibility = $1,416,513 $62,232,419 = 0.02 AND ( $1,416,513 - $62,232,419 ) 200.0 = $-304,080 per MW

General

The Project Developer has proposed a Solar generating facility located in the AEP Ohio Transmission Company, Inc. zone — Madison County, Ohio. The installed facilities will have a total capability of 200.0 MW with 126.85 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AG2-104
Project Name:
Marysville-Flatlick 765 kV
Project Developer Name:
Oak Run Solar Project, LLC
State:
Ohio
County:
Madison
Transmission Owner:
AEP Ohio Transmission Company, Inc.
MFO:
200.0
MWE:
200.0
MWC:
126.85
Fuel Type:
Solar
Basecase Study Year:
2028

Physical Interconnection Facility Study

Report Available

The transmission owner has completed the Physical Interconnection Facilities Study. This report is available for download.

Point of Interconnection

AG2-104 will interconnect on the American Electric Power  transmission system by tapping the Marysville-Flatlick 765 kV Line.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In Phase II SIS, the interconnected Transmission Owner has performed a facilities study for both the Transmission Owner Interconnection Facilities (TOIF) and Physical Interconnection Network Upgrades. The System Reliability Network Upgrade shown in the table are planning level cost estimates which are subject to change as a result of a facility study performed by the TO during Phase III System Impact Study.

Based on the Phase II SIS results, the AG2-104 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit #3 are also shown below.

Cost Summary
DescriptionCost Allocated to AG2-104Cost Subject to Readiness*Cost Subject to Adverse
Transmission Owner Interconnection Facilities (TOIF)$0$0$0
Other Scope$369,787$0$0
Option To Build Oversight$0$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0$0
Network Upgrades$92,761$92,761$92,761
System Reliability Network Upgrades
Steady State Thermal & Voltage$1,323,752$1,323,752$1,323,752
Transient Stability$0$0$0
Short Circuit$0$0$0
Transmission Owner Analysis
SubRegional$0$0$0
Distribution$0$0$0
Affected System Reinforcements
AFS - PJM Violations$0$0$0
AFS - Non-PJM Violations$0$0$0
Total$1,786,300$1,416,513$1,416,513

* Contributes to calculation for Readiness Deposit #3 (RD3). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Note 4: Please see the ‘Affected Systems Studies’ section of this Phase II SIS report for details on your project’s need for an Affected Systems Study. If your project requires an Affected Systems Study, the Affected Systems impacts may not be available from the Affected System Operator at the time of the PJM Phase II SIS. Therefore, the cost in this section would not reflect any required upgrades by the Affected System until the study is completed. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 311 (Decision Point II) A.1.b and PJM Manual 14H, section 6.2, Readiness Deposit #3 (RD3) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point II (DP2), the Project Developer or Eligible Customer is required to submit Readiness Deposit #3, which is calculated as 20% of cost allocation for required Phase II Network Upgrades minus Readiness Deposit #1 & Readiness Deposit #2.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Note 4: Readiness Deposit #3 can be zero, but may not be a negative number.

Readiness Deposit #3 Due for Project AG2-104

Readiness Deposit #3 has been calculated for the project based on the Phase II System Impact Study results and is shown in the table below. This Readiness Deposit #3 must be provided at Decision Point II through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit #3 Due for AG2-104
Project ID: AG2-104
20% of cost allocation for Phase II Network Upgrades:(A) $283,303
Sum of Readiness Deposit #1 & Readiness Deposit #2 Received:(B) $6,223,242
Readiness Deposit #3 (RD3) due at DP2:(A) - (B) = $0
Note: Failure to provide an acceptable form of Readiness Deposit #3 by the end of Decision Point II will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Build Option
Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Review and revision of breaker control settings associated with the customer line, as necessary due to the addition of new sources at the customer station.

$44,758$12,003$28,387$7,613$92,761$92,761
Other
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Installation of auxiliary load submeters for AG2-104, consisting of one (1) auxiliary load submeter at 230 kV and two (2) auxiliary load submeters at 34.5 kV, including the meter, IR1101 router, and Ethernet switch provided by AEP, submeter plate EDG-37, and router and Ethernet switch CIDs provided by AEP. Installation of the auxiliary submeters, procured by AEP and installed by the Project Developer, along with the associated fiber optic cabling.

$259,744$43,359$58,500$8,184$369,787$369,787
Developer Build Option

(No Developer Build Option for this project.)

Build Option Price Comparison
Build OptionTotal CostAllocated Cost
Transmission Owner Build Option$462,548$462,548
Developer Build Option(No Developer Build Option)

Based on the scope of work for the Interconnection Facilities, it is expected to take 15 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

Note that the TO findings were made from a conceptual review of this project. A more detailed review of the connection facilities and their cost will be identified in a future study phase. Further note that the cost estimate data provided should be considered high level estimates since it was produced without a detailed engineering review. The Project Developer will be responsible for the actual cost of construction. TO herein reserves the right to return to any issues in this document and, upon appropriate justification, request additional monies to complete any reinforcements to the transmission systems.

Remote Terminal Work: During Phase II of the PJM interconnection process, TO’s System Protection Engineering Department will review transmission line protection as well as anti-islanding required to accommodate the new generation and interconnection substation. System Protection Engineering will determine the minimal acceptable protection requirements to reliably interconnect the proposed generating facility with the transmission system. The review is based on maintaining system reliability by reviewing TO’s protection requirements with the known transmission system configuration which includes generating facilities in the area. This review may determine that transmission line protection and communication upgrades are required at remote substations.

Transmission Owner Analysis

No Transmission Owner impacts identified.

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. AEP interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AG2-104 was evaluated as a 200.0 MW (126.85 MW Capacity) injection in the AEP area.

AG2-104 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 200.0 MW (200.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS
BreakerAC215.61 %1180.0B2544.23
13.94
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS
BreakerAC215.61 %1180.0B2544.23
13.94
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
SingleAC215.61 %1180.0B2544.23
13.94
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
SingleAC215.59 %1180.0B2543.97
13.94
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
BreakerAC111.73 %4142.0B4627.93
37.2
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
AEP_P4_#706_05GAVIN 765_C1_SRT-A
BreakerAC107.42 %4142.0B4449.39
53.8
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
AP_P2-3_MP-500-020_SRT-SL
BreakerAC106.82 %4142.0B4424.53
37.58
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
AP_P2-3_MP-500-021_SRT-SL
BreakerAC106.7 %4142.0B4419.47
37.52
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
BreakerAC106.67 %4142.0B4418.17
37.5
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC104.85 %4142.0B4342.78
27.65
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
AEP_P1-2_#706_SRT-A
SingleAC104.04 %4142.0B4309.27
39.68
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
ATSI_P7-1_TE-345-030_SRT-A
TowerAC100.26 %4142.0B4152.93
37.73
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
ATSI_P7-1_TE-345-031_SRT-A
TowerAC100.15 %4142.0B4148.28
37.73
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AEP_P4_#ADKINS AG1125_SRT-A_SENS
BreakerAC104.63 %4571.0B4782.69
68.34
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AEP_P1-2_#AG1-125-ADKINS_SRT-A_SENS
SingleAC101.48 %4571.0B4638.62
50.41
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AEP_P4_#ADKINS AG1125_SRT-A_SENS
BreakerAC105.09 %4571.0B4803.57
68.34
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AEP_P1-2_#AG1-125-ADKINS_SRT-A_SENS
SingleAC101.94 %4571.0B4659.48
50.41

Details for [AG2-104] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:215.61 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2544.23
MW Contribution:
13.94
IPD Plant:AG2-104
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970149AG2-104 GEN
PJM_IPD
13.94

Details for [AG2-104] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:215.61 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2544.23
MW Contribution:
13.94
IPD Plant:AG2-104
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970149AG2-104 GEN
PJM_IPD
13.94

Details for [AG2-104] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-237805-237806_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:215.61 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2544.23
MW Contribution:
13.94
IPD Plant:AG2-104
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970149AG2-104 GEN
PJM_IPD
13.94

Details for [AG2-104] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-242508-237805_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:215.59 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2543.97
MW Contribution:
13.94
IPD Plant:AG2-104
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970149AG2-104 GEN
PJM_IPD
13.94

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o AEP_P4_#2942_05KAMMER 765_PP_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.73 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4627.93
MW Contribution:
37.2
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:125.68 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5205.7
MW Contribution:
36.73
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
13.634
270120AB2-067 GEN2
50/50
13.634
270160DARBY CT5
50/50
0.817
270161DARBY CT6
50/50
0.806
270466AD2-091
50/50
8.337
25326109MON D
50/50
1.882
25326509SID D
50/50
1.875
270349AD2-093_GEN
Solar/Wind Harmer
6.551
270471AD2-092_GEN
Solar/Wind Harmer
6.551
946101AF1-275 GEN
Solar/Wind Harmer
2.638
270054AF2-122 C O1
Solar/Wind Harmer
5.579
253383AE2-342_GEN
Solar/Wind Harmer
1.432
942861AE2-305 GEN
Solar/Wind Harmer
12.319
938701AE1-092 GEN
Solar/Wind Harmer
29.745
270462AD2-086
Solar/Wind Harmer
9.973
270269AC2-059
Solar/Wind Harmer
12.923
253378AE2-206_GEN
Solar/Wind Harmer
4.933
25322209TAIT E
Adder
12.972
25322209TAIT E
Adder
12.68
253415AE1-040 GEN
Solar/Wind Harmer
1.495
253370AE2-315 SEC1
Adder
2.649
253349AC2-067 GEN
Solar/Wind Harmer
2.665
253400AC2-068 GEN
Solar/Wind Harmer
1.072
970349AG2-230 GEN
Solar/Wind Harmer
19.467
945421AF1-207 GEN
Solar/Wind Harmer
18.162
957841AF2-078 GEN
Solar/Wind Harmer
7.818
970291AG2-192 GEN
Solar/Wind Harmer
1.681
970291AG2-192 GEN
Solar/Wind Harmer
0.541
944541AF1-119 GEN
Solar/Wind Harmer
5.407
960971AF2-388 GEN
Solar/Wind Harmer
14.115
270535AF1-215 GEN1
Solar/Wind Harmer
5.84
270536AF1-215 GEN2
Solar/Wind Harmer
5.84
270180AB1-006 GEN1
Solar/Wind Harmer
9.254
24697605MDL-3G C
Solar/Wind Harmer
4.743
24755605MDL-5G
Solar/Wind Harmer
3.102
24697905MDL-4G C
Solar/Wind Harmer
2.953
270181AB1-006 GEN2
Solar/Wind Harmer
0.92
942221AE2-234 GEN
Solar/Wind Harmer
4.491
965681AG1-436 GEN
Solar/Wind Harmer
16.003
965791AG1-447 GEN
Solar/Wind Harmer
8.187
270031AE2-169
Solar/Wind Harmer
10.386
270599AE1-208 GEN
Solar/Wind Harmer
10.386
24387305FR-4G C
Solar/Wind Harmer
6.468
966841AG1-555 GEN
Solar/Wind Harmer
3.198
274770LINCOLN ;1U
Adder
7.887
274771LINCOLN ;2U
Adder
7.887
24725505WLD G2 C
Solar/Wind Harmer
5.055
24699105WLD G1 C
Solar/Wind Harmer
4.996
270201AC2-176 GEN
Solar/Wind Harmer
6.526
247621Y3-024
Adder
0.306
964611AG1-324 GEN
Solar/Wind Harmer
0.664
270246TR4_N_V150
Solar/Wind Harmer
1.078
270247TR4_N_V136
Solar/Wind Harmer
1.078
970883AG2-550 GEN
Solar/Wind Harmer
12.676
970885AG2-551 GEN
Solar/Wind Harmer
2.948
270383AD1-128 GEN
Solar/Wind Harmer
7.709
274805UNIV PK N;1U
Adder
6.337
274808UNIV PK N;4U
Adder
6.295
274888KELLY CRK;1U
Solar/Wind Harmer
7.437
247620Y3-023
Adder
0.579
274674JOLIET 9 ;6U
Adder
19.323
274696ROCKY RD ;4P
Adder
14.179
274695ROCKY RD ;2P
Adder
13.852
274693ROCKY RD ;1P
Adder
13.715
274697ROCKY RD ;3P
Adder
3.763
274683WAUKEGAN ;8U
Adder
26.185
274683WAUKEGAN ;8U
Adder
22.073
25194408D.CRK1
Adder
9.285
25194508D.CRK3
Adder
1.736
972235AH1-702 GEN1
Adder
3.095
972236AH1-702 GEN2
Adder
2.691
274764LEE CO EC;5U
Adder
11.387
274765LEE CO EC;6U
Adder
11.387
274762LEE CO EC;3U
Adder
11.36
274763LEE CO EC;4U
Adder
11.253
254304AE2-114 C
Solar/Wind Helper
0.277
254305AE2-115 C
Solar/Wind Helper
0.277
241967AE2-285_GEN
Solar/Wind Helper
0.8
241801AE1-079 GEN
Solar/Wind Helper
0.313
962101AG1-054 GEN
Solar/Wind Helper
0.804
237043AE2-125 C
Solar/Wind Helper
0.204
946071AF1-272 GEN
Solar/Wind Helper
2.92
203835AF1-098 GEN
Solar/Wind Helper
2.083
946381AF1-302 GEN
Solar/Wind Helper
0.24
20083426SW_E13_K22
Solar/Wind Helper
0.059
20088826HIGHLAND
Solar/Wind Helper
0.947
203818AF1-086 GEN
Solar/Wind Helper
1.799
23585401KL_K28_T16
Solar/Wind Helper
1.286
203853AF1-134 C O1
Solar/Wind Helper
0.505
203804AE2-113_GEN
Solar/Wind Helper
1.868
23751201ROTHROCK
Solar/Wind Helper
0.744
203961AE2-224 GEN
Solar/Wind Helper
2.516
940863AE2-074 GEN
Solar/Wind Helper
0.487
203954AE2-126 C
Solar/Wind Helper
0.496
235054AD2-180 GEN
Solar/Wind Helper
1.697
203946AE2-131 C
Solar/Wind Helper
0.495
238117U2-030
Solar/Wind Helper
0.287
235531U2-073 GEN
Solar/Wind Helper
2.713
270156DARBY CT1
50/50
0.834
270157DARBY CT2
50/50
0.831
270159DARBY CT4
50/50
0.82
270158DARBY CT3
50/50
0.818
270036AE2-216 BAT
50/50
9.171
270459AD2-067 GEN
Solar/Wind Harmer
14.991
961821AG1-024 GEN
Solar/Wind Harmer
15.221
241955AC1-078 GEN
Solar/Wind Harmer
12.28
945631AF1-228 GEN
Solar/Wind Harmer
7.537
241973AD2-163_GEN1
Solar/Wind Harmer
3.183
241974AD2-163_GEN2
Solar/Wind Harmer
3.183
943861AF1-054 GEN
Solar/Wind Harmer
6.081
943851AF1-053 GEN
Solar/Wind Harmer
2.938
253338AC1-165 GEN
Solar/Wind Harmer
1.644
253343AC1-166 GEN
Solar/Wind Harmer
1.644
270223U2-072_GEN1
Solar/Wind Harmer
2.95
270224U2-072_GEN2
Solar/Wind Harmer
2.95
270227U2-072_GEN3
Solar/Wind Harmer
2.95
270228U2-072_GEN4
Solar/Wind Harmer
2.95
270231U2-072_GEN5
Solar/Wind Harmer
2.95
270578AF1-285 GEN2
Solar/Wind Harmer
0.695
270432AC2-029 GEN
Solar/Wind Harmer
10.129
270302AB2-170 GEN
Solar/Wind Harmer
12.005
241972AD1-140 GEN
Solar/Wind Harmer
6.404
253372AE2-315 SEC3
Adder
2.506
253372AE2-315 SEC3
Adder
2.506
270071AF1-092 GEN
Solar/Wind Harmer
19.771
25306009OHH W.
Adder
3.787
270340AC2-060 GEN
Solar/Wind Harmer
3.955
270263AC1-001 GEN
Solar/Wind Harmer
1.363
24729505KEY G4
Adder
8.445
970289AG2-191 GEN
Solar/Wind Harmer
2.456
958711AF2-162 GEN
Solar/Wind Harmer
1.306
959141AF2-205 GEN
Solar/Wind Harmer
7.803
958391AF2-133 GEN
Solar/Wind Harmer
11.7
959331AF2-224 GEN
Solar/Wind Harmer
12.88
946581AF1-322 GEN
Solar/Wind Harmer
13.166
24691005MDL-2G C
Solar/Wind Harmer
4.758
253406AD2-031_GEN
Solar/Wind Harmer
1.637
945581AF1-223 GEN
Solar/Wind Harmer
5.812
960681AF2-359 GEN
Solar/Wind Harmer
4.837
963791AG1-232 GEN
Solar/Wind Harmer
17.234
24386405FR-21G C
Solar/Wind Harmer
5.476
24387005FR-3G C
Solar/Wind Harmer
5.037
274775LINCOLN ;6U
Adder
7.887
274776LINCOLN ;7U
Adder
7.887
274777LINCOLN ;8U
Adder
7.887
961761AG1-017 GEN
Solar/Wind Harmer
0.543
270526AF1-158 GEN
Solar/Wind Harmer
5.757
964611AG1-324 GEN
Solar/Wind Harmer
4.95
253433AC1-085 GEN1
Solar/Wind Harmer
6.743
253432AC1-085 GEN2
Solar/Wind Harmer
0.339
247536S-71 GEN
Solar/Wind Harmer
5.133
247521TR3_G114
Solar/Wind Harmer
4.26
270191TR4_S_V150
Solar/Wind Harmer
3.801
965051AG1-369 GEN
Solar/Wind Harmer
6.329
270543AE2-219 C
Solar/Wind Harmer
12.676
970031AG2-029 GEN
Solar/Wind Harmer
31.677
971771AH1-392 GEN
Solar/Wind Harmer
11.401
971029AG2-637 GEN
Solar/Wind Harmer
18.999
965041AG1-368 GEN
Solar/Wind Harmer
12.63
963841AG1-237 GEN
Solar/Wind Harmer
13.795
972037AH1-567 GEN1
Adder
0.231
972228AH1-698 GEN2
Adder
4.668
972227AH1-698 GEN1
Adder
3.287
274827FISK ;RP
Adder
9.775
274800UNIV PARK;3U
Adder
7.343
274801UNIV PARK;4U
Adder
7.343
274687WILL CNTY;4U
Adder
35.099
274687WILL CNTY;4U
Adder
35.099
274675JOLIET 29;7U
Adder
38.521
274675JOLIET 29;7U
Adder
37.145
274728ELWOOD EC;5P
Adder
20.631
274731ELWOOD EC;2P
Adder
20.631
274733ELWOOD EC;3P
Adder
20.631
274735ELWOOD EC;4P
Adder
20.631
274744AC1-111 GEN8
Adder
6.986
274746AC1-111 G10
Adder
6.986
25196408WSDLE3
Adder
10.858
274823ROCKFORD ;21
Adder
23.942
972267AH1-718 GEN
Adder
5.066
25196108MFTGT2
Adder
1.847
25196108MFTGT2
Adder
1.715
241985AE1-237 GEN
Solar/Wind Helper
0.312
241982AE2-343 S C
Solar/Wind Helper
0.28
241997AF1-093 GEN
Solar/Wind Helper
0.316
23652301WDPWR_K20
Solar/Wind Helper
0.162
23750501ELLIOTTS
Solar/Wind Helper
0.704
203846AF2-130 C
Solar/Wind Helper
0.505
20089126CSLMN_L13
Solar/Wind Helper
0.622
20089226LOOKOUT
Solar/Wind Helper
0.62
20088926STNY CRK
Solar/Wind Helper
0.862
20094526CT_V3-030
Solar/Wind Helper
0.502
203955AF1-039 C O1
Solar/Wind Helper
0.386
203940AF1-140 C
Solar/Wind Helper
0.417
20088626ARWF_N39
Solar/Wind Helper
1.259
20334926Z1-069 C
Solar/Wind Helper
1.425
23750701CROSSCHOOL
Solar/Wind Helper
1.2
238118U2-030_1
Solar/Wind Helper
0.287
200917MEHOOPANY_G
Solar/Wind Helper
2.134
270166AC1-044 GEN3
50/50
13.634
962761AG1-125 GEN
Solar/Wind Harmer
60.25
970149AG2-104 GEN
Solar/Wind Harmer
37.205
970155AG2-107 GEN
Solar/Wind Harmer
26.272
270520AE2-214 GEN
Solar/Wind Harmer
10.552
270286AF1-227 GEN2
Solar/Wind Harmer
3.521
253333AC1-068 GEN
Solar/Wind Harmer
1.586
270391AF1-285 GEN3
Solar/Wind Harmer
1.806
270578AF1-285 GEN2
Solar/Wind Harmer
1.806
270317AD1-130_GEN
Solar/Wind Harmer
4.589
270485AE1-090_GEN
Solar/Wind Harmer
0.867
270273AD2-016 GEN
Solar/Wind Harmer
3.685
25326309TAIT D
Adder
1.458
253370AE2-315 SEC1
Adder
2.649
253371AE2-315 SEC2
Adder
2.506
253398AE2-221_GEN2
Solar/Wind Harmer
5.86
965651AG1-433 GEN
Solar/Wind Harmer
7.057
940581AE2-045 GEN
Solar/Wind Harmer
13.168
971605AH1-302 GEN
Solar/Wind Harmer
11.259
971995AH1-542 GEN
Solar/Wind Harmer
14.188
964861AG1-349 GEN
Solar/Wind Harmer
10.135
971917AH1-482 GEN
Solar/Wind Harmer
11.693
958381AF2-132 GEN
Solar/Wind Harmer
11.693
958861AF2-177 GEN
Solar/Wind Harmer
14.078
965011AG1-365 GEN
Solar/Wind Harmer
12.88
270055AF2-134 C O1
Solar/Wind Harmer
3.893
24791305MDL-5G
Solar/Wind Harmer
3.102
270594AE1-207 GEN
Solar/Wind Harmer
17.476
270032AE2-172
Solar/Wind Harmer
5.985
970373AG2-245 GEN
Solar/Wind Harmer
27.014
945371AF1-202 GEN
Solar/Wind Harmer
8.941
276903AD2-071 C
Solar/Wind Harmer
12.774
24385905FR-11G C
Solar/Wind Harmer
10.583
24386605FR-22G C
Solar/Wind Harmer
5.476
270024AE2-089 GEN
Solar/Wind Harmer
5.963
972207SS24-0001
Solar/Wind Harmer
28.043
274773LINCOLN ;4U
Adder
7.887
274774LINCOLN ;5U
Adder
7.887
253316AC1-085 GEN3
Solar/Wind Harmer
10.624
946171AF1-282 GEN
Solar/Wind Harmer
12.689
970825AG2-519 GEN
Solar/Wind Harmer
2.659
270005AE1-210 C O1
Solar/Wind Harmer
6.921
274723RIVER EC ;12
Adder
22.667
274751CRETE EC ;1U
Adder
6.184
274754CRETE EC ;4U
Adder
6.184
270216AD2-079_GEN
Solar/Wind Harmer
0.764
274812UNIV PK N;8U
Adder
6.323
24639705ELKHART HY
Adder
0.193
274802UNIV PARK;5U
Adder
7.347
274676JOLIET 29;8U
Adder
38.521
274732ELWOOD EC;7P
Adder
20.631
274674JOLIET 9 ;6U
Adder
19.323
274745AC1-111 GEN9
Adder
6.986
274682WAUKEGAN ;7U
Adder
22.344
274828WAUKEGAN ;BP
Adder
13.726
274822ROCKFORD ;11
Adder
24.117
24728605AND G2
Adder
4.712
25194608D.CRK4
Adder
2.018
274761LEE CO EC;2U
Adder
11.36
274766LEE CO EC;7U
Adder
11.226
25196808ZIMRHP
Adder
91.918
25196008MFTGT1
Adder
1.676
970091AG2-072 GEN
Adder
52.601
254303AC2-168 GEN
Solar/Wind Helper
0.2
241966AE1-183 GEN
Solar/Wind Helper
0.316
961971AG1-040 GEN
Solar/Wind Helper
0.526
203830AF1-094 GEN
Solar/Wind Helper
0.526
203979AG1-198 GEN
Solar/Wind Helper
0.315
203947AF1-006 C
Solar/Wind Helper
0.571
20084626FORWARD
Solar/Wind Helper
0.376
20089026BF_G21_K23
Solar/Wind Helper
0.492
964201AG1-281 GEN
Solar/Wind Helper
0.505
238185AF2-356 C
Solar/Wind Helper
2.211
20091526CHSTN_FL
Solar/Wind Helper
0.61
20090526Q36
Solar/Wind Helper
1.071
203952AE2-129 C
Solar/Wind Helper
0.495
203855AF2-088 C
Solar/Wind Helper
0.16
238126S14_GEN_1
Solar/Wind Helper
0.672
238120AE2-309 GEN
Solar/Wind Helper
0.423
23751101LEADS_P59
Solar/Wind Helper
1.861
270051AF1-062 GEN
50/50
17.906
270475AD2-096_GEN
50/50
10.496
962771AG1-126 GEN
Solar/Wind Harmer
60.25
970153AG2-106 GEN
Solar/Wind Harmer
26.272
961921AG1-034 GEN
Solar/Wind Harmer
22.831
270284AF1-227 GEN1
Solar/Wind Harmer
9.52
270287AF1-227 GEN3
Solar/Wind Harmer
3.521
942051AE2-217 GEN
Solar/Wind Harmer
28.777
270518AE2-148 GEN
Solar/Wind Harmer
18.58
253325AC1-069 GEN
Solar/Wind Harmer
1.586
942871AE2-306 GEN
Solar/Wind Harmer
1.355
270391AF1-285 GEN3
Solar/Wind Harmer
0.695
960801AF2-371 GEN
Solar/Wind Harmer
3.703
964871AG1-351 GEN
Solar/Wind Harmer
2.557
276820AF1-078_GEN
Solar/Wind Harmer
2.191
960071AF2-298 GEN
Solar/Wind Harmer
2.003
253303V4-073 C
Solar/Wind Harmer
0.153
253370AE2-315 SEC1
Adder
2.649
253371AE2-315 SEC2
Adder
2.506
944531AF1-118 GEN
Solar/Wind Harmer
45.692
270043AE2-236 GEN
Solar/Wind Harmer
7.15
247642Z2-115 C
Solar/Wind Harmer
0.083
971347AH1-153 GEN
Solar/Wind Harmer
6.489
965461AG1-414 GEN
Solar/Wind Harmer
2.931
970289AG2-191 GEN
Solar/Wind Harmer
0.992
253394AE2-221_GEN
Solar/Wind Harmer
5.86
964401AG1-302 GEN
Solar/Wind Harmer
11.693
965021AG1-366 GEN
Solar/Wind Harmer
2.995
24690905MDL-1G C
Solar/Wind Harmer
10.33
970781AG2-491 GEN
Solar/Wind Harmer
12.867
24386205FR-12G C
Solar/Wind Harmer
5.457
274772LINCOLN ;3U
Adder
7.887
24441505OLIV SLR
Solar/Wind Harmer
0.17
962031AG1-047 GEN
Solar/Wind Harmer
3.839
957741AF2-068 GEN
Solar/Wind Harmer
19.045
253317AC1-085 GEN4
Solar/Wind Harmer
10.624
946181AF1-283 GEN
Solar/Wind Harmer
16.496
946031AF1-268 GEN
Solar/Wind Harmer
10.518
970825AG2-519 GEN
Solar/Wind Harmer
7.139
270004AE1-209 GEN
Solar/Wind Harmer
6.921
270063AE2-323 C
Solar/Wind Harmer
2.782
274724RIVER EC ;11
Adder
22.402
972231SS25-0005
Solar/Wind Harmer
12.006
972181SS23-001
Solar/Wind Harmer
7.504
274752CRETE EC ;2U
Adder
6.184
274753CRETE EC ;3U
Adder
6.184
247643Z2-116 C
Solar/Wind Harmer
0.088
276164X3-005 C
Solar/Wind Harmer
0.887
274814UNIV PK N;0U
Adder
6.378
274807UNIV PK N;3U
Adder
6.364
274811UNIV PK N;7U
Adder
6.323
274803UNIV PARK;6U
Adder
7.347
274826FISK ;BP
Adder
13.792
972259AH1-714 GEN
Adder
24.031
972038AH1-567 GEN2
Adder
0.46
274676JOLIET 29;8U
Adder
37.145
274729ELWOOD EC;1P
Adder
20.631
274730ELWOOD EC;6P
Adder
20.631
274734ELWOOD EC;8P
Adder
20.631
274736ELWOOD EC;9P
Adder
20.631
274682WAUKEGAN ;7U
Adder
22.344
25196608WSDLE5
Adder
10.548
24728505AND G1
Adder
4.712
25194608D.CRK4
Adder
2.018
274760LEE CO EC;1U
Adder
11.36
274767LEE CO EC;8U
Adder
11.226
25196008MFTGT1
Adder
1.623
235058AG1-386 C
Solar/Wind Helper
0.581
237048AF1-022 C
Solar/Wind Helper
0.208
237046AF1-021 C
Solar/Wind Helper
0.376
962511AG1-100 GEN
Solar/Wind Helper
0.525
20092526R32
Solar/Wind Helper
1.228
202652Y1-033 WT C
Solar/Wind Helper
0.585
964991AG1-363 GEN
Solar/Wind Helper
3.784
20303426NA_O38_P22
Solar/Wind Helper
1.032
23562501BACKB
Solar/Wind Helper
0.906
203993AD2-133_GEN1
Solar/Wind Helper
1.071
203854AF2-039 C
Solar/Wind Helper
0.332
20398826ARMNA MT
Solar/Wind Helper
1.535
238127S14_GEN_2
Solar/Wind Helper
0.672
941421AE2-139 GEN
Solar/Wind Helper
2.297
274887GEN-1.85
Solar/Wind Harmer
0.443
276843GEN-1.7
Solar/Wind Harmer
0.048
CPLELTFEXP_CPLE->PJM
CLTF
2.158
CBM West 2LTFEXP_CBM-W2->PJM
CBM
133.077
NYPJM->LTFIMP_NY
CLTF
5.256
LGEELTFEXP_LGEE->PJM
CLTF
7.735
WECLTFEXP_WEC->PJM
CLTF
4.687
AG2-052LTFEXP_AG2-052->PJM
LTF
0.294
AH1-155LTFEXP_AH1-155->PJM
LTF
0.441
LAGNLTFEXP_LAGN->PJM
CLTF
17.312
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.667
TVALTFEXP_TVA->PJM
CLTF
8.311
CBM West 1LTFEXP_CBM-W1->PJM
CBM
156.431
CBM South 1LTFEXP_CBM-S1->PJM
CBM
33.206
MECLTFEXP_MEC->PJM
CLTF
19.244
SIGELTFEXP_SIGE->PJM
CLTF
0.591

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o AEP_P4_#706_05GAVIN 765_C1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#706_05GAVIN 765_C1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.42 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4449.39
MW Contribution:
53.8
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
3.319
270459AD2-067 GEN
Solar/Wind Harmer
19.807
961821AG1-024 GEN
Solar/Wind Harmer
20.11
241955AC1-078 GEN
Solar/Wind Harmer
15.492
241973AD2-163_GEN1
Solar/Wind Harmer
4.025
241974AD2-163_GEN2
Solar/Wind Harmer
4.025
270223U2-072_GEN1
Solar/Wind Harmer
3.956
270224U2-072_GEN2
Solar/Wind Harmer
3.956
270227U2-072_GEN3
Solar/Wind Harmer
3.956
270228U2-072_GEN4
Solar/Wind Harmer
3.956
270231U2-072_GEN5
Solar/Wind Harmer
3.956
270578AF1-285 GEN2
Solar/Wind Harmer
0.932
945631AF1-228 GEN
Solar/Wind Harmer
9.329
943861AF1-054 GEN
Solar/Wind Harmer
7.538
943851AF1-053 GEN
Solar/Wind Harmer
3.643
270302AB2-170 GEN
Solar/Wind Harmer
16.105
253338AC1-165 GEN
Solar/Wind Harmer
1.946
253343AC1-166 GEN
Solar/Wind Harmer
1.946
241972AD1-140 GEN
Solar/Wind Harmer
7.47
270432AC2-029 GEN
Solar/Wind Harmer
11.406
957201AF2-014 GEN
Solar/Wind Harmer
7.338
270435AC2-044 GEN
Solar/Wind Harmer
3.236
959331AF2-224 GEN
Solar/Wind Harmer
16.062
247521TR3_G114
Solar/Wind Harmer
5.362
270191TR4_S_V150
Solar/Wind Harmer
4.784
965051AG1-369 GEN
Solar/Wind Harmer
7.966
270071AF1-092 GEN
Solar/Wind Harmer
23.849
965041AG1-368 GEN
Solar/Wind Harmer
15.857
270007AE1-245 C
Solar/Wind Harmer
8.496
970031AG2-029 GEN
Solar/Wind Harmer
38.958
970179AG2-119 GEN
Solar/Wind Harmer
12.462
971771AH1-392 GEN
Solar/Wind Harmer
13.875
963791AG1-232 GEN
Solar/Wind Harmer
20.803
960681AF2-359 GEN
Solar/Wind Harmer
5.817
270526AF1-158 GEN
Solar/Wind Harmer
6.973
24729505KEY G4
Adder
9.953
944161AF1-084 GEN
Solar/Wind Harmer
3.358
270404AC1-167 GEN
Solar/Wind Harmer
1.639
958391AF2-133 GEN
Solar/Wind Harmer
13.726
959141AF2-205 GEN
Solar/Wind Harmer
9.136
958711AF2-162 GEN
Solar/Wind Harmer
1.519
274775LINCOLN ;6U
Adder
9.27
274776LINCOLN ;7U
Adder
9.27
274777LINCOLN ;8U
Adder
9.27
946581AF1-322 GEN
Solar/Wind Harmer
15.185
24691005MDL-2G C
Solar/Wind Harmer
5.488
970289AG2-191 GEN
Solar/Wind Harmer
2.804
972037AH1-567 GEN1
Adder
0.27
966831AG1-554 GEN
Solar/Wind Harmer
1.764
274827FISK ;RP
Adder
11.436
960591AF2-350 GEN
Solar/Wind Harmer
14.735
274800UNIV PARK;3U
Adder
8.587
274801UNIV PARK;4U
Adder
8.587
972228AH1-698 GEN2
Adder
5.454
972227AH1-698 GEN1
Adder
3.84
274687WILL CNTY;4U
Adder
40.93
274687WILL CNTY;4U
Adder
40.93
274675JOLIET 29;7U
Adder
44.89
274675JOLIET 29;7U
Adder
43.287
274728ELWOOD EC;5P
Adder
24.024
274731ELWOOD EC;2P
Adder
24.024
274733ELWOOD EC;3P
Adder
24.024
274735ELWOOD EC;4P
Adder
24.024
274744AC1-111 GEN8
Adder
8.105
274746AC1-111 G10
Adder
8.105
253372AE2-315 SEC3
Adder
2.747
253372AE2-315 SEC3
Adder
2.747
25306009OHH W.
Adder
4.15
274823ROCKFORD ;21
Adder
27.402
972267AH1-718 GEN
Adder
5.748
25196408WSDLE3
Adder
10.931
25196108MFTGT2
Adder
1.832
25196108MFTGT2
Adder
1.701
23750501ELLIOTTS
Solar/Wind Helper
0.6
23652301WDPWR_K20
Solar/Wind Helper
0.129
23750701CROSSCHOOL
Solar/Wind Helper
1.119
270166AC1-044 GEN3
50/50
17.244
24721705FLATG2
50/50
3.319
24721805FLATG3
50/50
3.319
962761AG1-125 GEN
Solar/Wind Harmer
87.132
970149AG2-104 GEN
Solar/Wind Harmer
53.804
970155AG2-107 GEN
Solar/Wind Harmer
37.994
270286AF1-227 GEN2
Solar/Wind Harmer
4.722
270520AE2-214 GEN
Solar/Wind Harmer
13.554
270391AF1-285 GEN3
Solar/Wind Harmer
2.423
270578AF1-285 GEN2
Solar/Wind Harmer
2.423
270317AD1-130_GEN
Solar/Wind Harmer
6.157
270485AE1-090_GEN
Solar/Wind Harmer
1.163
253333AC1-068 GEN
Solar/Wind Harmer
1.877
971995AH1-542 GEN
Solar/Wind Harmer
19.672
246936BC-WTG1
Solar/Wind Harmer
6.329
270489AE1-102 GEN1
Solar/Wind Harmer
2.103
965421AG1-410 GEN
Solar/Wind Harmer
48.507
965011AG1-365 GEN
Solar/Wind Harmer
16.062
270216AD2-079_GEN
Solar/Wind Harmer
0.934
24639705ELKHART HY
Adder
0.237
270258AD1-119 GEN
Solar/Wind Harmer
3.118
957891AF2-083 GEN
Solar/Wind Harmer
22.99
945111AF1-176 GEN
Solar/Wind Harmer
27.342
970373AG2-245 GEN
Solar/Wind Harmer
32.081
270449AD2-020 GEN
Solar/Wind Harmer
4.272
943021AE2-325 GEN
Solar/Wind Harmer
5.553
270055AF2-134 C O1
Solar/Wind Harmer
4.602
958381AF2-132 GEN
Solar/Wind Harmer
13.753
964861AG1-349 GEN
Solar/Wind Harmer
11.914
971917AH1-482 GEN
Solar/Wind Harmer
13.746
24441205WTRV SLR C
Solar/Wind Harmer
0.203
940581AE2-045 GEN
Solar/Wind Harmer
15.382
971605AH1-302 GEN
Solar/Wind Harmer
13.152
965651AG1-433 GEN
Solar/Wind Harmer
8.204
270297AD1-101 GEN
Solar/Wind Harmer
3.045
972207SS24-0001
Solar/Wind Harmer
32.96
274773LINCOLN ;4U
Adder
9.27
274774LINCOLN ;5U
Adder
9.27
958861AF2-177 GEN
Solar/Wind Harmer
16.291
274751CRETE EC ;1U
Adder
7.284
274754CRETE EC ;4U
Adder
7.284
270273AD2-016 GEN
Solar/Wind Harmer
3.959
274723RIVER EC ;12
Adder
26.668
24791305MDL-5G
Solar/Wind Harmer
3.578
270024AE2-089 GEN
Solar/Wind Harmer
6.948
274812UNIV PK N;8U
Adder
7.423
25326309TAIT D
Adder
1.618
274802UNIV PARK;5U
Adder
8.599
274676JOLIET 29;8U
Adder
44.89
274674JOLIET 9 ;6U
Adder
22.504
274732ELWOOD EC;7P
Adder
24.024
274745AC1-111 GEN9
Adder
8.105
253370AE2-315 SEC1
Adder
2.904
253371AE2-315 SEC2
Adder
2.747
274682WAUKEGAN ;7U
Adder
25.826
270119AB2-067 GEN1
50/50
17.244
270120AB2-067 GEN2
50/50
17.244
270349AD2-093_GEN
Solar/Wind Harmer
8.784
270471AD2-092_GEN
Solar/Wind Harmer
8.784
270054AF2-122 C O1
Solar/Wind Harmer
7.347
946101AF1-275 GEN
Solar/Wind Harmer
3.388
253383AE2-342_GEN
Solar/Wind Harmer
1.816
942861AE2-305 GEN
Solar/Wind Harmer
15.272
270462AD2-086
Solar/Wind Harmer
13.378
938701AE1-092 GEN
Solar/Wind Harmer
39.554
253378AE2-206_GEN
Solar/Wind Harmer
6.061
25326509SID D
Adder
2.143
246937BC-WTG2
Solar/Wind Harmer
6.329
270246TR4_N_V150
Solar/Wind Harmer
1.357
270247TR4_N_V136
Solar/Wind Harmer
1.357
247607V1-011 GEN
Solar/Wind Harmer
6.22
970349AG2-230 GEN
Solar/Wind Harmer
23.598
942801AE2-298 GEN
Solar/Wind Harmer
2.373
241960AC2-195 GEN
Solar/Wind Harmer
4.323
247620Y3-023
Adder
0.71
965681AG1-436 GEN
Solar/Wind Harmer
19.243
965791AG1-447 GEN
Solar/Wind Harmer
9.845
961051AF2-396 GEN
Solar/Wind Harmer
24.247
961051AF2-396 GEN
Solar/Wind Harmer
11.278
270535AF1-215 GEN1
Solar/Wind Harmer
6.903
270536AF1-215 GEN2
Solar/Wind Harmer
6.903
25326109MON D
Adder
1.994
942221AE2-234 GEN
Solar/Wind Harmer
5.285
944541AF1-119 GEN
Solar/Wind Harmer
6.286
960971AF2-388 GEN
Solar/Wind Harmer
16.409
945421AF1-207 GEN
Solar/Wind Harmer
21.073
957841AF2-078 GEN
Solar/Wind Harmer
9.072
944231AF1-091 GEN
Solar/Wind Harmer
26.952
274770LINCOLN ;1U
Adder
9.27
274771LINCOLN ;2U
Adder
9.27
270269AC2-059
Solar/Wind Harmer
13.884
270180AB1-006 GEN1
Solar/Wind Harmer
10.673
24697605MDL-3G C
Solar/Wind Harmer
5.47
24755605MDL-5G
Solar/Wind Harmer
3.578
24697905MDL-4G C
Solar/Wind Harmer
3.405
270181AB1-006 GEN2
Solar/Wind Harmer
1.061
274805UNIV PK N;1U
Adder
7.439
274808UNIV PK N;4U
Adder
7.391
25322209TAIT E
Adder
14.396
25322209TAIT E
Adder
14.072
970291AG2-192 GEN
Solar/Wind Harmer
1.918
970291AG2-192 GEN
Solar/Wind Harmer
0.618
274888KELLY CRK;1U
Solar/Wind Harmer
8.695
276776AD2-060 GEN
Solar/Wind Harmer
0.617
958011AF2-095 GEN
Solar/Wind Harmer
21.218
970941AG2-585 GEN
Solar/Wind Harmer
8.104
274674JOLIET 9 ;6U
Adder
22.504
253370AE2-315 SEC1
Adder
2.904
247621Y3-024
Adder
0.348
274696ROCKY RD ;4P
Adder
16.391
274695ROCKY RD ;2P
Adder
16.014
274693ROCKY RD ;1P
Adder
15.856
274697ROCKY RD ;3P
Adder
4.35
274683WAUKEGAN ;8U
Adder
30.253
274683WAUKEGAN ;8U
Adder
25.502
972235AH1-702 GEN1
Adder
3.539
972236AH1-702 GEN2
Adder
3.077
274764LEE CO EC;5U
Adder
12.96
274765LEE CO EC;6U
Adder
12.96
274762LEE CO EC;3U
Adder
12.93
274763LEE CO EC;4U
Adder
12.808
25194408D.CRK1
Adder
9.313
25194508D.CRK3
Adder
1.741
972159AH1-661 GEN
Adder
1.225
23751201ROTHROCK
Solar/Wind Helper
0.691
23585401KL_K28_T16
Solar/Wind Helper
1.178
237043AE2-125 C
Solar/Wind Helper
0.16
235054AD2-180 GEN
Solar/Wind Helper
1.576
238117U2-030
Solar/Wind Helper
0.267
235531U2-073 GEN
Solar/Wind Helper
2.548
24721905FLATG4
50/50
3.319
24722005FLATG5
50/50
3.319
270051AF1-062 GEN
50/50
23.559
270475AD2-096_GEN
50/50
14.072
962771AG1-126 GEN
Solar/Wind Harmer
87.132
970153AG2-106 GEN
Solar/Wind Harmer
37.994
961921AG1-034 GEN
Solar/Wind Harmer
30.165
270284AF1-227 GEN1
Solar/Wind Harmer
12.766
270287AF1-227 GEN3
Solar/Wind Harmer
4.722
942871AE2-306 GEN
Solar/Wind Harmer
1.817
270391AF1-285 GEN3
Solar/Wind Harmer
0.932
942051AE2-217 GEN
Solar/Wind Harmer
35.999
270518AE2-148 GEN
Solar/Wind Harmer
22.44
253325AC1-069 GEN
Solar/Wind Harmer
1.877
960801AF2-371 GEN
Solar/Wind Harmer
4.344
964871AG1-351 GEN
Solar/Wind Harmer
2.999
276820AF1-078_GEN
Solar/Wind Harmer
2.693
246938BC-WTG3
Solar/Wind Harmer
6.438
270491AE1-102 GEN2
Solar/Wind Harmer
2.103
965021AG1-366 GEN
Solar/Wind Harmer
3.735
270043AE2-236 GEN
Solar/Wind Harmer
8.753
24695305TIMB G C
Solar/Wind Harmer
5.277
958091AF2-103 GEN
Solar/Wind Harmer
0.254
971347AH1-153 GEN
Solar/Wind Harmer
7.866
270063AE2-323 C
Solar/Wind Harmer
3.423
944531AF1-118 GEN
Solar/Wind Harmer
54.114
247643Z2-116 C
Solar/Wind Harmer
0.107
958581AF2-149 GEN
Solar/Wind Harmer
6.587
971199AH1-059 GEN
Solar/Wind Harmer
3.233
24441505OLIV SLR
Solar/Wind Harmer
0.205
270505AE1-170 C O1
Solar/Wind Harmer
22.99
945111AF1-176 GEN
Solar/Wind Harmer
8.665
964401AG1-302 GEN
Solar/Wind Harmer
13.753
270044AE2-322 C
Solar/Wind Harmer
1.989
270588AE1-091_GEN
Solar/Wind Harmer
16.602
274772LINCOLN ;3U
Adder
9.27
972231SS25-0005
Solar/Wind Harmer
14.143
972181SS23-001
Solar/Wind Harmer
8.839
274752CRETE EC ;2U
Adder
7.284
274753CRETE EC ;3U
Adder
7.284
274724RIVER EC ;11
Adder
26.355
247642Z2-115 C
Solar/Wind Harmer
0.095
24690905MDL-1G C
Solar/Wind Harmer
11.914
970781AG2-491 GEN
Solar/Wind Harmer
14.841
276164X3-005 C
Solar/Wind Harmer
1.042
274814UNIV PK N;0U
Adder
7.488
274807UNIV PK N;3U
Adder
7.472
274811UNIV PK N;7U
Adder
7.423
965461AG1-414 GEN
Solar/Wind Harmer
3.346
970289AG2-191 GEN
Solar/Wind Harmer
1.133
274803UNIV PARK;6U
Adder
8.599
274826FISK ;BP
Adder
16.137
274887GEN-1.85
Solar/Wind Harmer
7.851
276772AC2-154 GEN
Solar/Wind Harmer
4.112
276843GEN-1.7
Solar/Wind Harmer
0.845
276806AD2-047 C O1
Solar/Wind Harmer
15.763
972038AH1-567 GEN2
Adder
0.538
972259AH1-714 GEN
Adder
28.051
274676JOLIET 29;8U
Adder
43.287
274730ELWOOD EC;6P
Adder
24.024
274734ELWOOD EC;8P
Adder
24.024
274736ELWOOD EC;9P
Adder
24.024
274729ELWOOD EC;1P
Adder
24.024
253370AE2-315 SEC1
Adder
2.904
253371AE2-315 SEC2
Adder
2.747
274682WAUKEGAN ;7U
Adder
25.826
274760LEE CO EC;1U
Adder
12.93
274767LEE CO EC;8U
Adder
12.777
24728505AND G1
Adder
5.071
25196608WSDLE5
Adder
10.619
25194608D.CRK4
Adder
2.025
25196008MFTGT1
Adder
1.61
23906502RICHG2&3
Adder
1.439
23906402RICHG1
Adder
1.437
237048AF1-022 C
Solar/Wind Helper
0.174
237046AF1-021 C
Solar/Wind Helper
0.304
964991AG1-363 GEN
Solar/Wind Helper
3.522
23562501BACKB
Solar/Wind Helper
0.847
235058AG1-386 C
Solar/Wind Helper
0.4
238127S14_GEN_2
Solar/Wind Helper
0.635
202652Y1-033 WT C
Solar/Wind Helper
0.501
970707AG2-453 GEN
Solar/Wind Harmer
31.58
238118U2-030_1
Solar/Wind Helper
0.267
203955AF1-039 C O1
Solar/Wind Helper
0.331
274828WAUKEGAN ;BP
Adder
15.858
274822ROCKFORD ;11
Adder
27.602
274761LEE CO EC;2U
Adder
12.93
274766LEE CO EC;7U
Adder
12.777
24728605AND G2
Adder
5.071
25194608D.CRK4
Adder
2.025
25196008MFTGT1
Adder
1.662
23906502RICHG2&3
Adder
1.439
25196808ZIMRHP
Adder
90.149
970091AG2-072 GEN
Adder
55.681
238185AF2-356 C
Solar/Wind Helper
2.037
23751101LEADS_P59
Solar/Wind Helper
1.839
238120AE2-309 GEN
Solar/Wind Helper
0.401
238126S14_GEN_1
Solar/Wind Helper
0.635
CBM West 2LTFEXP_CBM-W2->PJM
CBM
124.415
NYPJM->LTFIMP_NY
CLTF
4.821
LGEELTFEXP_LGEE->PJM
CLTF
7.242
WECLTFEXP_WEC->PJM
CLTF
5.355
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.468
AG2-052LTFEXP_AG2-052->PJM
LTF
0.342
AH1-155LTFEXP_AH1-155->PJM
LTF
0.513
LAGNLTFEXP_LAGN->PJM
CLTF
14.301
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.305
TVALTFEXP_TVA->PJM
CLTF
6.29
CBM West 1LTFEXP_CBM-W1->PJM
CBM
183.968
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.5
MECLTFEXP_MEC->PJM
CLTF
20.741
SIGELTFEXP_SIGE->PJM
CLTF
0.579

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o AP_P2-3_MP-500-020_SRT-SL


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-3_MP-500-020_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.82 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4424.53
MW Contribution:
37.58
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-3_MP-500-020_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.3 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5024.36
MW Contribution:
37.07
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
13.704
270120AB2-067 GEN2
50/50
13.704
270160DARBY CT5
50/50
0.827
270161DARBY CT6
50/50
0.815
270466AD2-091
50/50
8.446
25326109MON D
50/50
1.908
25326509SID D
50/50
1.901
270349AD2-093_GEN
Solar/Wind Harmer
6.619
270471AD2-092_GEN
Solar/Wind Harmer
6.619
946101AF1-275 GEN
Solar/Wind Harmer
2.667
270054AF2-122 C O1
Solar/Wind Harmer
5.642
253383AE2-342_GEN
Solar/Wind Harmer
1.448
942861AE2-305 GEN
Solar/Wind Harmer
12.466
938701AE1-092 GEN
Solar/Wind Harmer
30.136
270462AD2-086
Solar/Wind Harmer
10.102
270269AC2-059
Solar/Wind Harmer
13.102
253378AE2-206_GEN
Solar/Wind Harmer
5
25322209TAIT E
Adder
13.154
25322209TAIT E
Adder
12.859
253415AE1-040 GEN
Solar/Wind Harmer
1.516
253370AE2-315 SEC1
Adder
2.687
253349AC2-067 GEN
Solar/Wind Harmer
2.703
253400AC2-068 GEN
Solar/Wind Harmer
1.087
970349AG2-230 GEN
Solar/Wind Harmer
19.743
945421AF1-207 GEN
Solar/Wind Harmer
18.42
957841AF2-078 GEN
Solar/Wind Harmer
7.93
970291AG2-192 GEN
Solar/Wind Harmer
1.705
970291AG2-192 GEN
Solar/Wind Harmer
0.549
944541AF1-119 GEN
Solar/Wind Harmer
5.484
960971AF2-388 GEN
Solar/Wind Harmer
14.317
270535AF1-215 GEN1
Solar/Wind Harmer
5.924
270536AF1-215 GEN2
Solar/Wind Harmer
5.924
270180AB1-006 GEN1
Solar/Wind Harmer
9.386
24697605MDL-3G C
Solar/Wind Harmer
4.811
24755605MDL-5G
Solar/Wind Harmer
3.146
24697905MDL-4G C
Solar/Wind Harmer
2.995
270181AB1-006 GEN2
Solar/Wind Harmer
0.933
942221AE2-234 GEN
Solar/Wind Harmer
4.556
965681AG1-436 GEN
Solar/Wind Harmer
16.232
965791AG1-447 GEN
Solar/Wind Harmer
8.305
270031AE2-169
Solar/Wind Harmer
10.536
270599AE1-208 GEN
Solar/Wind Harmer
10.536
24387305FR-4G C
Solar/Wind Harmer
6.561
966841AG1-555 GEN
Solar/Wind Harmer
3.244
274770LINCOLN ;1U
Adder
8.001
274771LINCOLN ;2U
Adder
8.001
24725505WLD G2 C
Solar/Wind Harmer
5.129
24699105WLD G1 C
Solar/Wind Harmer
5.069
270201AC2-176 GEN
Solar/Wind Harmer
6.621
247621Y3-024
Adder
0.311
964611AG1-324 GEN
Solar/Wind Harmer
0.674
270246TR4_N_V150
Solar/Wind Harmer
1.093
270247TR4_N_V136
Solar/Wind Harmer
1.093
970883AG2-550 GEN
Solar/Wind Harmer
12.861
970885AG2-551 GEN
Solar/Wind Harmer
2.991
270383AD1-128 GEN
Solar/Wind Harmer
7.821
274805UNIV PK N;1U
Adder
6.429
274808UNIV PK N;4U
Adder
6.386
247620Y3-023
Adder
0.588
274674JOLIET 9 ;6U
Adder
19.605
274695ROCKY RD ;2P
Adder
14.055
274693ROCKY RD ;1P
Adder
13.917
274697ROCKY RD ;3P
Adder
3.818
274696ROCKY RD ;4P
Adder
14.387
274683WAUKEGAN ;8U
Adder
26.57
274683WAUKEGAN ;8U
Adder
22.397
25194408D.CRK1
Adder
9.426
25194508D.CRK3
Adder
1.762
972235AH1-702 GEN1
Adder
3.14
972236AH1-702 GEN2
Adder
2.731
274764LEE CO EC;5U
Adder
11.556
274765LEE CO EC;6U
Adder
11.556
274762LEE CO EC;3U
Adder
11.529
274763LEE CO EC;4U
Adder
11.421
254304AE2-114 C
Solar/Wind Helper
0.274
254305AE2-115 C
Solar/Wind Helper
0.274
241967AE2-285_GEN
Solar/Wind Helper
0.791
241801AE1-079 GEN
Solar/Wind Helper
0.309
962101AG1-054 GEN
Solar/Wind Helper
0.794
237043AE2-125 C
Solar/Wind Helper
0.201
946071AF1-272 GEN
Solar/Wind Helper
2.885
203835AF1-098 GEN
Solar/Wind Helper
2.054
946381AF1-302 GEN
Solar/Wind Helper
0.237
20083426SW_E13_K22
Solar/Wind Helper
0.058
20088826HIGHLAND
Solar/Wind Helper
0.936
203818AF1-086 GEN
Solar/Wind Helper
1.776
23585401KL_K28_T16
Solar/Wind Helper
1.272
203853AF1-134 C O1
Solar/Wind Helper
0.498
23751201ROTHROCK
Solar/Wind Helper
0.736
203804AE2-113_GEN
Solar/Wind Helper
1.843
203961AE2-224 GEN
Solar/Wind Helper
2.485
940863AE2-074 GEN
Solar/Wind Helper
0.48
235054AD2-180 GEN
Solar/Wind Helper
1.679
203954AE2-126 C
Solar/Wind Helper
0.49
203946AE2-131 C
Solar/Wind Helper
0.489
238117U2-030
Solar/Wind Helper
0.284
235531U2-073 GEN
Solar/Wind Helper
2.681
270156DARBY CT1
50/50
0.843
270157DARBY CT2
50/50
0.841
270159DARBY CT4
50/50
0.83
270158DARBY CT3
50/50
0.828
270036AE2-216 BAT
50/50
9.29
270459AD2-067 GEN
Solar/Wind Harmer
15.153
961821AG1-024 GEN
Solar/Wind Harmer
15.385
241955AC1-078 GEN
Solar/Wind Harmer
12.422
945631AF1-228 GEN
Solar/Wind Harmer
7.626
241973AD2-163_GEN1
Solar/Wind Harmer
3.221
241974AD2-163_GEN2
Solar/Wind Harmer
3.221
943861AF1-054 GEN
Solar/Wind Harmer
6.153
943851AF1-053 GEN
Solar/Wind Harmer
2.973
253338AC1-165 GEN
Solar/Wind Harmer
1.665
253343AC1-166 GEN
Solar/Wind Harmer
1.665
270223U2-072_GEN1
Solar/Wind Harmer
2.986
270224U2-072_GEN2
Solar/Wind Harmer
2.986
270227U2-072_GEN3
Solar/Wind Harmer
2.986
270228U2-072_GEN4
Solar/Wind Harmer
2.986
270231U2-072_GEN5
Solar/Wind Harmer
2.986
270578AF1-285 GEN2
Solar/Wind Harmer
0.703
270432AC2-029 GEN
Solar/Wind Harmer
10.263
270302AB2-170 GEN
Solar/Wind Harmer
12.161
241972AD1-140 GEN
Solar/Wind Harmer
6.488
253372AE2-315 SEC3
Adder
2.541
253372AE2-315 SEC3
Adder
2.541
270071AF1-092 GEN
Solar/Wind Harmer
20.047
25306009OHH W.
Adder
3.841
270340AC2-060 GEN
Solar/Wind Harmer
4.012
270263AC1-001 GEN
Solar/Wind Harmer
1.383
24729505KEY G4
Adder
8.564
970289AG2-191 GEN
Solar/Wind Harmer
2.491
958711AF2-162 GEN
Solar/Wind Harmer
1.325
959141AF2-205 GEN
Solar/Wind Harmer
7.914
958391AF2-133 GEN
Solar/Wind Harmer
11.867
959331AF2-224 GEN
Solar/Wind Harmer
13.064
946581AF1-322 GEN
Solar/Wind Harmer
13.354
24691005MDL-2G C
Solar/Wind Harmer
4.826
253406AD2-031_GEN
Solar/Wind Harmer
1.661
945581AF1-223 GEN
Solar/Wind Harmer
5.896
960681AF2-359 GEN
Solar/Wind Harmer
4.907
963791AG1-232 GEN
Solar/Wind Harmer
17.483
24386405FR-21G C
Solar/Wind Harmer
5.555
24387005FR-3G C
Solar/Wind Harmer
5.109
274775LINCOLN ;6U
Adder
8.001
274776LINCOLN ;7U
Adder
8.001
274777LINCOLN ;8U
Adder
8.001
961761AG1-017 GEN
Solar/Wind Harmer
0.551
270526AF1-158 GEN
Solar/Wind Harmer
5.84
253433AC1-085 GEN1
Solar/Wind Harmer
6.842
253432AC1-085 GEN2
Solar/Wind Harmer
0.344
964611AG1-324 GEN
Solar/Wind Harmer
5.022
247536S-71 GEN
Solar/Wind Harmer
5.208
247521TR3_G114
Solar/Wind Harmer
4.322
270191TR4_S_V150
Solar/Wind Harmer
3.856
965051AG1-369 GEN
Solar/Wind Harmer
6.421
270543AE2-219 C
Solar/Wind Harmer
12.861
970031AG2-029 GEN
Solar/Wind Harmer
32.137
971771AH1-392 GEN
Solar/Wind Harmer
11.566
971029AG2-637 GEN
Solar/Wind Harmer
19.276
965041AG1-368 GEN
Solar/Wind Harmer
12.814
963841AG1-237 GEN
Solar/Wind Harmer
13.995
972037AH1-567 GEN1
Adder
0.234
972228AH1-698 GEN2
Adder
4.735
972227AH1-698 GEN1
Adder
3.334
274827FISK ;RP
Adder
9.917
274800UNIV PARK;3U
Adder
7.45
274801UNIV PARK;4U
Adder
7.45
274687WILL CNTY;4U
Adder
35.61
274687WILL CNTY;4U
Adder
35.61
274675JOLIET 29;7U
Adder
39.082
274675JOLIET 29;7U
Adder
37.686
274728ELWOOD EC;5P
Adder
20.931
274731ELWOOD EC;2P
Adder
20.931
274733ELWOOD EC;3P
Adder
20.931
274735ELWOOD EC;4P
Adder
20.931
274744AC1-111 GEN8
Adder
7.088
274746AC1-111 G10
Adder
7.088
25196408WSDLE3
Adder
11.023
270166AC1-044 GEN3
50/50
13.704
962761AG1-125 GEN
Solar/Wind Harmer
60.856
970149AG2-104 GEN
Solar/Wind Harmer
37.579
970155AG2-107 GEN
Solar/Wind Harmer
26.536
270520AE2-214 GEN
Solar/Wind Harmer
10.667
270286AF1-227 GEN2
Solar/Wind Harmer
3.56
253333AC1-068 GEN
Solar/Wind Harmer
1.605
270391AF1-285 GEN3
Solar/Wind Harmer
1.829
270578AF1-285 GEN2
Solar/Wind Harmer
1.829
270317AD1-130_GEN
Solar/Wind Harmer
4.649
270485AE1-090_GEN
Solar/Wind Harmer
0.878
270273AD2-016 GEN
Solar/Wind Harmer
3.736
25326309TAIT D
Adder
1.478
253370AE2-315 SEC1
Adder
2.687
253371AE2-315 SEC2
Adder
2.541
253398AE2-221_GEN2
Solar/Wind Harmer
5.944
965651AG1-433 GEN
Solar/Wind Harmer
7.158
940581AE2-045 GEN
Solar/Wind Harmer
13.356
971605AH1-302 GEN
Solar/Wind Harmer
11.42
971995AH1-542 GEN
Solar/Wind Harmer
14.398
964861AG1-349 GEN
Solar/Wind Harmer
10.279
971917AH1-482 GEN
Solar/Wind Harmer
11.86
958381AF2-132 GEN
Solar/Wind Harmer
11.86
958861AF2-177 GEN
Solar/Wind Harmer
14.28
965011AG1-365 GEN
Solar/Wind Harmer
13.064
270055AF2-134 C O1
Solar/Wind Harmer
3.949
270594AE1-207 GEN
Solar/Wind Harmer
17.727
270032AE2-172
Solar/Wind Harmer
6.071
24791305MDL-5G
Solar/Wind Harmer
3.146
970373AG2-245 GEN
Solar/Wind Harmer
27.399
945371AF1-202 GEN
Solar/Wind Harmer
9.07
276903AD2-071 C
Solar/Wind Harmer
12.959
24385905FR-11G C
Solar/Wind Harmer
10.735
24386605FR-22G C
Solar/Wind Harmer
5.555
270024AE2-089 GEN
Solar/Wind Harmer
6.05
972207SS24-0001
Solar/Wind Harmer
28.446
274773LINCOLN ;4U
Adder
8.001
274774LINCOLN ;5U
Adder
8.001
253316AC1-085 GEN3
Solar/Wind Harmer
10.78
946171AF1-282 GEN
Solar/Wind Harmer
12.876
970825AG2-519 GEN
Solar/Wind Harmer
2.698
270005AE1-210 C O1
Solar/Wind Harmer
7.022
274723RIVER EC ;12
Adder
22.995
274751CRETE EC ;1U
Adder
6.273
274754CRETE EC ;4U
Adder
6.273
270216AD2-079_GEN
Solar/Wind Harmer
0.776
274812UNIV PK N;8U
Adder
6.415
24639705ELKHART HY
Adder
0.196
274802UNIV PARK;5U
Adder
7.454
274676JOLIET 29;8U
Adder
39.082
274732ELWOOD EC;7P
Adder
20.931
274674JOLIET 9 ;6U
Adder
19.605
274745AC1-111 GEN9
Adder
7.088
274682WAUKEGAN ;7U
Adder
22.672
274828WAUKEGAN ;BP
Adder
13.928
274822ROCKFORD ;11
Adder
24.475
24728605AND G2
Adder
4.783
25194608D.CRK4
Adder
2.049
274761LEE CO EC;2U
Adder
11.529
274766LEE CO EC;7U
Adder
11.394
25196808ZIMRHP
Adder
93.328
25196008MFTGT1
Adder
1.701
970091AG2-072 GEN
Adder
53.422
254303AC2-168 GEN
Solar/Wind Helper
0.198
241966AE1-183 GEN
Solar/Wind Helper
0.312
961971AG1-040 GEN
Solar/Wind Helper
0.519
203830AF1-094 GEN
Solar/Wind Helper
0.518
203979AG1-198 GEN
Solar/Wind Helper
0.311
203947AF1-006 C
Solar/Wind Helper
0.563
20084626FORWARD
Solar/Wind Helper
0.372
20089026BF_G21_K23
Solar/Wind Helper
0.487
238185AF2-356 C
Solar/Wind Helper
2.187
964201AG1-281 GEN
Solar/Wind Helper
0.499
20091526CHSTN_FL
Solar/Wind Helper
0.602
20090526Q36
Solar/Wind Helper
1.057
203952AE2-129 C
Solar/Wind Helper
0.489
203855AF2-088 C
Solar/Wind Helper
0.158
238126S14_GEN_1
Solar/Wind Helper
0.664
238120AE2-309 GEN
Solar/Wind Helper
0.418
23751101LEADS_P59
Solar/Wind Helper
1.838
965421AG1-410 GEN
Solar/Wind Harmer
8.043
274823ROCKFORD ;21
Adder
24.297
972267AH1-718 GEN
Adder
5.142
25196108MFTGT2
Adder
1.876
25196108MFTGT2
Adder
1.742
241985AE1-237 GEN
Solar/Wind Helper
0.309
241982AE2-343 S C
Solar/Wind Helper
0.277
241997AF1-093 GEN
Solar/Wind Helper
0.312
23652301WDPWR_K20
Solar/Wind Helper
0.16
23750501ELLIOTTS
Solar/Wind Helper
0.697
203846AF2-130 C
Solar/Wind Helper
0.499
20089126CSLMN_L13
Solar/Wind Helper
0.615
20089226LOOKOUT
Solar/Wind Helper
0.613
20088926STNY CRK
Solar/Wind Helper
0.851
203955AF1-039 C O1
Solar/Wind Helper
0.382
20094526CT_V3-030
Solar/Wind Helper
0.495
203940AF1-140 C
Solar/Wind Helper
0.412
20088626ARWF_N39
Solar/Wind Helper
1.243
20334926Z1-069 C
Solar/Wind Helper
1.406
23750701CROSSCHOOL
Solar/Wind Helper
1.187
238118U2-030_1
Solar/Wind Helper
0.284
200917MEHOOPANY_G
Solar/Wind Helper
2.104
270051AF1-062 GEN
50/50
18.085
270475AD2-096_GEN
50/50
10.605
962771AG1-126 GEN
Solar/Wind Harmer
60.856
970153AG2-106 GEN
Solar/Wind Harmer
26.536
961921AG1-034 GEN
Solar/Wind Harmer
23.077
270284AF1-227 GEN1
Solar/Wind Harmer
9.626
270287AF1-227 GEN3
Solar/Wind Harmer
3.56
942051AE2-217 GEN
Solar/Wind Harmer
29.118
270518AE2-148 GEN
Solar/Wind Harmer
18.808
253325AC1-069 GEN
Solar/Wind Harmer
1.605
942871AE2-306 GEN
Solar/Wind Harmer
1.372
270391AF1-285 GEN3
Solar/Wind Harmer
0.703
960801AF2-371 GEN
Solar/Wind Harmer
3.753
964871AG1-351 GEN
Solar/Wind Harmer
2.591
276820AF1-078_GEN
Solar/Wind Harmer
2.221
960071AF2-298 GEN
Solar/Wind Harmer
2.031
253303V4-073 C
Solar/Wind Harmer
0.155
253370AE2-315 SEC1
Adder
2.687
253371AE2-315 SEC2
Adder
2.541
944531AF1-118 GEN
Solar/Wind Harmer
46.338
270043AE2-236 GEN
Solar/Wind Harmer
7.251
247642Z2-115 C
Solar/Wind Harmer
0.084
971347AH1-153 GEN
Solar/Wind Harmer
6.581
965461AG1-414 GEN
Solar/Wind Harmer
2.973
970289AG2-191 GEN
Solar/Wind Harmer
1.006
253394AE2-221_GEN
Solar/Wind Harmer
5.944
964401AG1-302 GEN
Solar/Wind Harmer
11.86
965021AG1-366 GEN
Solar/Wind Harmer
3.038
24690905MDL-1G C
Solar/Wind Harmer
10.477
970781AG2-491 GEN
Solar/Wind Harmer
13.051
24386205FR-12G C
Solar/Wind Harmer
5.536
274772LINCOLN ;3U
Adder
8.001
24441505OLIV SLR
Solar/Wind Harmer
0.172
962031AG1-047 GEN
Solar/Wind Harmer
3.895
957741AF2-068 GEN
Solar/Wind Harmer
19.322
253317AC1-085 GEN4
Solar/Wind Harmer
10.78
946181AF1-283 GEN
Solar/Wind Harmer
16.739
946031AF1-268 GEN
Solar/Wind Harmer
10.671
970825AG2-519 GEN
Solar/Wind Harmer
7.243
270004AE1-209 GEN
Solar/Wind Harmer
7.022
270063AE2-323 C
Solar/Wind Harmer
2.823
274724RIVER EC ;11
Adder
22.726
972231SS25-0005
Solar/Wind Harmer
12.18
972181SS23-001
Solar/Wind Harmer
7.613
274752CRETE EC ;2U
Adder
6.273
274753CRETE EC ;3U
Adder
6.273
247643Z2-116 C
Solar/Wind Harmer
0.089
276164X3-005 C
Solar/Wind Harmer
0.9
274814UNIV PK N;0U
Adder
6.471
274807UNIV PK N;3U
Adder
6.457
274811UNIV PK N;7U
Adder
6.415
274803UNIV PARK;6U
Adder
7.454
274826FISK ;BP
Adder
13.992
972259AH1-714 GEN
Adder
24.38
972038AH1-567 GEN2
Adder
0.466
274676JOLIET 29;8U
Adder
37.686
274729ELWOOD EC;1P
Adder
20.931
274730ELWOOD EC;6P
Adder
20.931
274734ELWOOD EC;8P
Adder
20.931
274736ELWOOD EC;9P
Adder
20.931
274682WAUKEGAN ;7U
Adder
22.672
25196608WSDLE5
Adder
10.708
24728505AND G1
Adder
4.783
25194608D.CRK4
Adder
2.049
274760LEE CO EC;1U
Adder
11.529
274767LEE CO EC;8U
Adder
11.394
25196008MFTGT1
Adder
1.648
235058AG1-386 C
Solar/Wind Helper
0.575
237048AF1-022 C
Solar/Wind Helper
0.206
237046AF1-021 C
Solar/Wind Helper
0.372
962511AG1-100 GEN
Solar/Wind Helper
0.518
202652Y1-033 WT C
Solar/Wind Helper
0.578
20092526R32
Solar/Wind Helper
1.213
964991AG1-363 GEN
Solar/Wind Helper
3.745
20303426NA_O38_P22
Solar/Wind Helper
1.019
23562501BACKB
Solar/Wind Helper
0.896
203993AD2-133_GEN1
Solar/Wind Helper
1.057
203854AF2-039 C
Solar/Wind Helper
0.328
20398826ARMNA MT
Solar/Wind Helper
1.514
238127S14_GEN_2
Solar/Wind Helper
0.664
941421AE2-139 GEN
Solar/Wind Helper
2.265
965431AG1-411 GEN
Solar/Wind Harmer
0
CPLELTFEXP_CPLE->PJM
CLTF
2.322
CBM West 2LTFEXP_CBM-W2->PJM
CBM
135.459
NYPJM->LTFIMP_NY
CLTF
5.177
LGEELTFEXP_LGEE->PJM
CLTF
7.861
WECLTFEXP_WEC->PJM
CLTF
4.757
AG2-052LTFEXP_AG2-052->PJM
LTF
0.298
AH1-155LTFEXP_AH1-155->PJM
LTF
0.447
LAGNLTFEXP_LAGN->PJM
CLTF
17.663
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.14
TVALTFEXP_TVA->PJM
CLTF
8.485
CBM West 1LTFEXP_CBM-W1->PJM
CBM
159.09
CBM South 1LTFEXP_CBM-S1->PJM
CBM
33.869
MECLTFEXP_MEC->PJM
CLTF
19.548
SIGELTFEXP_SIGE->PJM
CLTF
0.601

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o AP_P2-3_MP-500-021_SRT-SL


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-3_MP-500-021_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.7 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4419.47
MW Contribution:
37.52
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-3_MP-500-021_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.09 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5015.35
MW Contribution:
36.99
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
13.695
270120AB2-067 GEN2
50/50
13.695
270160DARBY CT5
50/50
0.825
270161DARBY CT6
50/50
0.814
270466AD2-091
50/50
8.429
25326109MON D
50/50
1.904
25326509SID D
50/50
1.897
270349AD2-093_GEN
Solar/Wind Harmer
6.609
270471AD2-092_GEN
Solar/Wind Harmer
6.609
946101AF1-275 GEN
Solar/Wind Harmer
2.662
270054AF2-122 C O1
Solar/Wind Harmer
5.631
253383AE2-342_GEN
Solar/Wind Harmer
1.446
942861AE2-305 GEN
Solar/Wind Harmer
12.443
938701AE1-092 GEN
Solar/Wind Harmer
30.075
270462AD2-086
Solar/Wind Harmer
10.083
270269AC2-059
Solar/Wind Harmer
13.072
253378AE2-206_GEN
Solar/Wind Harmer
4.99
25322209TAIT E
Adder
13.127
25322209TAIT E
Adder
12.832
253415AE1-040 GEN
Solar/Wind Harmer
1.513
253370AE2-315 SEC1
Adder
2.681
253349AC2-067 GEN
Solar/Wind Harmer
2.698
253400AC2-068 GEN
Solar/Wind Harmer
1.085
970349AG2-230 GEN
Solar/Wind Harmer
19.704
945421AF1-207 GEN
Solar/Wind Harmer
18.384
957841AF2-078 GEN
Solar/Wind Harmer
7.914
970291AG2-192 GEN
Solar/Wind Harmer
1.701
970291AG2-192 GEN
Solar/Wind Harmer
0.548
944541AF1-119 GEN
Solar/Wind Harmer
5.473
960971AF2-388 GEN
Solar/Wind Harmer
14.288
270535AF1-215 GEN1
Solar/Wind Harmer
5.912
270536AF1-215 GEN2
Solar/Wind Harmer
5.912
270180AB1-006 GEN1
Solar/Wind Harmer
9.367
24697605MDL-3G C
Solar/Wind Harmer
4.801
24755605MDL-5G
Solar/Wind Harmer
3.14
24697905MDL-4G C
Solar/Wind Harmer
2.989
270181AB1-006 GEN2
Solar/Wind Harmer
0.931
942221AE2-234 GEN
Solar/Wind Harmer
4.547
965681AG1-436 GEN
Solar/Wind Harmer
16.2
965791AG1-447 GEN
Solar/Wind Harmer
8.288
270031AE2-169
Solar/Wind Harmer
10.515
270599AE1-208 GEN
Solar/Wind Harmer
10.515
24387305FR-4G C
Solar/Wind Harmer
6.548
966841AG1-555 GEN
Solar/Wind Harmer
3.237
270051AF1-062 GEN
50/50
18.055
270475AD2-096_GEN
50/50
10.588
962771AG1-126 GEN
Solar/Wind Harmer
60.765
970153AG2-106 GEN
Solar/Wind Harmer
26.496
961921AG1-034 GEN
Solar/Wind Harmer
23.036
270284AF1-227 GEN1
Solar/Wind Harmer
9.61
270287AF1-227 GEN3
Solar/Wind Harmer
3.554
942051AE2-217 GEN
Solar/Wind Harmer
29.065
270518AE2-148 GEN
Solar/Wind Harmer
18.772
253325AC1-069 GEN
Solar/Wind Harmer
1.602
942871AE2-306 GEN
Solar/Wind Harmer
1.369
270391AF1-285 GEN3
Solar/Wind Harmer
0.702
960801AF2-371 GEN
Solar/Wind Harmer
3.744
964871AG1-351 GEN
Solar/Wind Harmer
2.585
276820AF1-078_GEN
Solar/Wind Harmer
2.217
960071AF2-298 GEN
Solar/Wind Harmer
2.027
253303V4-073 C
Solar/Wind Harmer
0.155
253370AE2-315 SEC1
Adder
2.681
253371AE2-315 SEC2
Adder
2.536
944531AF1-118 GEN
Solar/Wind Harmer
46.245
270043AE2-236 GEN
Solar/Wind Harmer
7.237
247642Z2-115 C
Solar/Wind Harmer
0.084
971347AH1-153 GEN
Solar/Wind Harmer
6.568
965461AG1-414 GEN
Solar/Wind Harmer
2.967
970289AG2-191 GEN
Solar/Wind Harmer
1.004
253394AE2-221_GEN
Solar/Wind Harmer
5.932
964401AG1-302 GEN
Solar/Wind Harmer
11.837
965021AG1-366 GEN
Solar/Wind Harmer
3.032
24690905MDL-1G C
Solar/Wind Harmer
10.457
970781AG2-491 GEN
Solar/Wind Harmer
13.025
24386205FR-12G C
Solar/Wind Harmer
5.525
274772LINCOLN ;3U
Adder
7.985
24441505OLIV SLR
Solar/Wind Harmer
0.172
962031AG1-047 GEN
Solar/Wind Harmer
3.887
957741AF2-068 GEN
Solar/Wind Harmer
19.282
253317AC1-085 GEN4
Solar/Wind Harmer
10.757
946181AF1-283 GEN
Solar/Wind Harmer
16.703
946031AF1-268 GEN
Solar/Wind Harmer
10.649
970825AG2-519 GEN
Solar/Wind Harmer
7.228
270004AE1-209 GEN
Solar/Wind Harmer
7.007
270063AE2-323 C
Solar/Wind Harmer
2.817
274724RIVER EC ;11
Adder
22.681
972231SS25-0005
Solar/Wind Harmer
12.156
972181SS23-001
Solar/Wind Harmer
7.597
274752CRETE EC ;2U
Adder
6.261
274753CRETE EC ;3U
Adder
6.261
247643Z2-116 C
Solar/Wind Harmer
0.089
276164X3-005 C
Solar/Wind Harmer
0.899
274814UNIV PK N;0U
Adder
6.458
274807UNIV PK N;3U
Adder
6.444
274811UNIV PK N;7U
Adder
6.402
274803UNIV PARK;6U
Adder
7.439
274826FISK ;BP
Adder
13.965
972259AH1-714 GEN
Adder
24.332
972038AH1-567 GEN2
Adder
0.465
274676JOLIET 29;8U
Adder
37.611
274729ELWOOD EC;1P
Adder
20.89
274730ELWOOD EC;6P
Adder
20.89
274734ELWOOD EC;8P
Adder
20.89
274736ELWOOD EC;9P
Adder
20.89
274682WAUKEGAN ;7U
Adder
22.627
25196608WSDLE5
Adder
10.684
24728505AND G1
Adder
4.773
25194608D.CRK4
Adder
2.045
274760LEE CO EC;1U
Adder
11.506
274767LEE CO EC;8U
Adder
11.371
25196008MFTGT1
Adder
1.644
235058AG1-386 C
Solar/Wind Helper
0.575
237048AF1-022 C
Solar/Wind Helper
0.205
237046AF1-021 C
Solar/Wind Helper
0.372
962511AG1-100 GEN
Solar/Wind Helper
0.518
202652Y1-033 WT C
Solar/Wind Helper
0.577
20092526R32
Solar/Wind Helper
1.211
964991AG1-363 GEN
Solar/Wind Helper
3.733
20303426NA_O38_P22
Solar/Wind Helper
1.018
23562501BACKB
Solar/Wind Helper
0.894
203993AD2-133_GEN1
Solar/Wind Helper
1.056
203854AF2-039 C
Solar/Wind Helper
0.327
20398826ARMNA MT
Solar/Wind Helper
1.512
238127S14_GEN_2
Solar/Wind Helper
0.662
941421AE2-139 GEN
Solar/Wind Helper
2.261
274887GEN-1.85
Solar/Wind Harmer
0.448
276843GEN-1.7
Solar/Wind Harmer
0.048
270156DARBY CT1
50/50
0.842
270157DARBY CT2
50/50
0.84
270159DARBY CT4
50/50
0.828
270158DARBY CT3
50/50
0.826
270036AE2-216 BAT
50/50
9.272
270459AD2-067 GEN
Solar/Wind Harmer
15.126
961821AG1-024 GEN
Solar/Wind Harmer
15.357
241955AC1-078 GEN
Solar/Wind Harmer
12.399
945631AF1-228 GEN
Solar/Wind Harmer
7.612
241973AD2-163_GEN1
Solar/Wind Harmer
3.215
241974AD2-163_GEN2
Solar/Wind Harmer
3.215
943861AF1-054 GEN
Solar/Wind Harmer
6.142
943851AF1-053 GEN
Solar/Wind Harmer
2.968
253338AC1-165 GEN
Solar/Wind Harmer
1.661
253343AC1-166 GEN
Solar/Wind Harmer
1.661
270223U2-072_GEN1
Solar/Wind Harmer
2.981
270224U2-072_GEN2
Solar/Wind Harmer
2.981
270227U2-072_GEN3
Solar/Wind Harmer
2.981
270228U2-072_GEN4
Solar/Wind Harmer
2.981
270231U2-072_GEN5
Solar/Wind Harmer
2.981
270578AF1-285 GEN2
Solar/Wind Harmer
0.702
270432AC2-029 GEN
Solar/Wind Harmer
10.241
270302AB2-170 GEN
Solar/Wind Harmer
12.138
241972AD1-140 GEN
Solar/Wind Harmer
6.475
253372AE2-315 SEC3
Adder
2.536
253372AE2-315 SEC3
Adder
2.536
270071AF1-092 GEN
Solar/Wind Harmer
20.008
25306009OHH W.
Adder
3.833
270340AC2-060 GEN
Solar/Wind Harmer
4.004
270263AC1-001 GEN
Solar/Wind Harmer
1.38
24729505KEY G4
Adder
8.547
970289AG2-191 GEN
Solar/Wind Harmer
2.486
958711AF2-162 GEN
Solar/Wind Harmer
1.322
959141AF2-205 GEN
Solar/Wind Harmer
7.898
958391AF2-133 GEN
Solar/Wind Harmer
11.843
959331AF2-224 GEN
Solar/Wind Harmer
13.038
946581AF1-322 GEN
Solar/Wind Harmer
13.327
24691005MDL-2G C
Solar/Wind Harmer
4.816
253406AD2-031_GEN
Solar/Wind Harmer
1.657
945581AF1-223 GEN
Solar/Wind Harmer
5.884
960681AF2-359 GEN
Solar/Wind Harmer
4.897
963791AG1-232 GEN
Solar/Wind Harmer
17.447
24386405FR-21G C
Solar/Wind Harmer
5.544
24387005FR-3G C
Solar/Wind Harmer
5.099
274775LINCOLN ;6U
Adder
7.985
274776LINCOLN ;7U
Adder
7.985
274777LINCOLN ;8U
Adder
7.985
961761AG1-017 GEN
Solar/Wind Harmer
0.55
270526AF1-158 GEN
Solar/Wind Harmer
5.829
964611AG1-324 GEN
Solar/Wind Harmer
5.011
253433AC1-085 GEN1
Solar/Wind Harmer
6.828
253432AC1-085 GEN2
Solar/Wind Harmer
0.344
247536S-71 GEN
Solar/Wind Harmer
5.197
247521TR3_G114
Solar/Wind Harmer
4.313
270191TR4_S_V150
Solar/Wind Harmer
3.848
965051AG1-369 GEN
Solar/Wind Harmer
6.408
270543AE2-219 C
Solar/Wind Harmer
12.834
970031AG2-029 GEN
Solar/Wind Harmer
32.072
971771AH1-392 GEN
Solar/Wind Harmer
11.543
971029AG2-637 GEN
Solar/Wind Harmer
19.236
965041AG1-368 GEN
Solar/Wind Harmer
12.788
963841AG1-237 GEN
Solar/Wind Harmer
13.967
972228AH1-698 GEN2
Adder
4.726
972227AH1-698 GEN1
Adder
3.328
972037AH1-567 GEN1
Adder
0.234
274827FISK ;RP
Adder
9.897
274800UNIV PARK;3U
Adder
7.435
274801UNIV PARK;4U
Adder
7.435
274687WILL CNTY;4U
Adder
35.54
274687WILL CNTY;4U
Adder
35.54
274675JOLIET 29;7U
Adder
39.004
274675JOLIET 29;7U
Adder
37.611
274728ELWOOD EC;5P
Adder
20.89
274731ELWOOD EC;2P
Adder
20.89
274733ELWOOD EC;3P
Adder
20.89
274735ELWOOD EC;4P
Adder
20.89
274744AC1-111 GEN8
Adder
7.074
274746AC1-111 G10
Adder
7.074
25196408WSDLE3
Adder
10.998
274823ROCKFORD ;21
Adder
24.249
972267AH1-718 GEN
Adder
5.132
25196108MFTGT2
Adder
1.871
25196108MFTGT2
Adder
1.738
241985AE1-237 GEN
Solar/Wind Helper
0.309
241982AE2-343 S C
Solar/Wind Helper
0.277
241997AF1-093 GEN
Solar/Wind Helper
0.312
23652301WDPWR_K20
Solar/Wind Helper
0.16
23750501ELLIOTTS
Solar/Wind Helper
0.695
203846AF2-130 C
Solar/Wind Helper
0.499
20089126CSLMN_L13
Solar/Wind Helper
0.614
20089226LOOKOUT
Solar/Wind Helper
0.612
20088926STNY CRK
Solar/Wind Helper
0.85
20094526CT_V3-030
Solar/Wind Helper
0.495
203955AF1-039 C O1
Solar/Wind Helper
0.381
203940AF1-140 C
Solar/Wind Helper
0.411
20088626ARWF_N39
Solar/Wind Helper
1.241
20334926Z1-069 C
Solar/Wind Helper
1.404
23750701CROSSCHOOL
Solar/Wind Helper
1.183
238118U2-030_1
Solar/Wind Helper
0.283
274770LINCOLN ;1U
Adder
7.985
274771LINCOLN ;2U
Adder
7.985
24725505WLD G2 C
Solar/Wind Harmer
5.118
24699105WLD G1 C
Solar/Wind Harmer
5.058
270201AC2-176 GEN
Solar/Wind Harmer
6.607
247621Y3-024
Adder
0.31
964611AG1-324 GEN
Solar/Wind Harmer
0.672
270246TR4_N_V150
Solar/Wind Harmer
1.091
270247TR4_N_V136
Solar/Wind Harmer
1.091
970883AG2-550 GEN
Solar/Wind Harmer
12.834
970885AG2-551 GEN
Solar/Wind Harmer
2.985
270383AD1-128 GEN
Solar/Wind Harmer
7.805
274805UNIV PK N;1U
Adder
6.416
274808UNIV PK N;4U
Adder
6.374
274888KELLY CRK;1U
Solar/Wind Harmer
7.53
247620Y3-023
Adder
0.587
274674JOLIET 9 ;6U
Adder
19.566
274695ROCKY RD ;2P
Adder
14.027
274693ROCKY RD ;1P
Adder
13.889
274697ROCKY RD ;3P
Adder
3.811
274696ROCKY RD ;4P
Adder
14.358
274683WAUKEGAN ;8U
Adder
26.517
274683WAUKEGAN ;8U
Adder
22.353
25194408D.CRK1
Adder
9.405
25194508D.CRK3
Adder
1.758
972235AH1-702 GEN1
Adder
3.134
972236AH1-702 GEN2
Adder
2.725
274764LEE CO EC;5U
Adder
11.533
274765LEE CO EC;6U
Adder
11.533
274762LEE CO EC;3U
Adder
11.506
274763LEE CO EC;4U
Adder
11.398
254304AE2-114 C
Solar/Wind Helper
0.274
254305AE2-115 C
Solar/Wind Helper
0.274
241967AE2-285_GEN
Solar/Wind Helper
0.791
241801AE1-079 GEN
Solar/Wind Helper
0.309
962101AG1-054 GEN
Solar/Wind Helper
0.794
237043AE2-125 C
Solar/Wind Helper
0.201
946071AF1-272 GEN
Solar/Wind Helper
2.881
203835AF1-098 GEN
Solar/Wind Helper
2.053
946381AF1-302 GEN
Solar/Wind Helper
0.237
20083426SW_E13_K22
Solar/Wind Helper
0.058
20088826HIGHLAND
Solar/Wind Helper
0.934
203818AF1-086 GEN
Solar/Wind Helper
1.773
23585401KL_K28_T16
Solar/Wind Helper
1.269
203853AF1-134 C O1
Solar/Wind Helper
0.498
203804AE2-113_GEN
Solar/Wind Helper
1.841
23751201ROTHROCK
Solar/Wind Helper
0.734
203961AE2-224 GEN
Solar/Wind Helper
2.481
940863AE2-074 GEN
Solar/Wind Helper
0.48
203954AE2-126 C
Solar/Wind Helper
0.489
235054AD2-180 GEN
Solar/Wind Helper
1.674
203946AE2-131 C
Solar/Wind Helper
0.488
238117U2-030
Solar/Wind Helper
0.283
235531U2-073 GEN
Solar/Wind Helper
2.674
270166AC1-044 GEN3
50/50
13.695
962761AG1-125 GEN
Solar/Wind Harmer
60.765
970149AG2-104 GEN
Solar/Wind Harmer
37.522
970155AG2-107 GEN
Solar/Wind Harmer
26.496
270520AE2-214 GEN
Solar/Wind Harmer
10.649
270286AF1-227 GEN2
Solar/Wind Harmer
3.554
253333AC1-068 GEN
Solar/Wind Harmer
1.602
270391AF1-285 GEN3
Solar/Wind Harmer
1.826
270578AF1-285 GEN2
Solar/Wind Harmer
1.826
270317AD1-130_GEN
Solar/Wind Harmer
4.64
270485AE1-090_GEN
Solar/Wind Harmer
0.877
270273AD2-016 GEN
Solar/Wind Harmer
3.727
25326309TAIT D
Adder
1.475
253370AE2-315 SEC1
Adder
2.681
253371AE2-315 SEC2
Adder
2.536
253398AE2-221_GEN2
Solar/Wind Harmer
5.932
965651AG1-433 GEN
Solar/Wind Harmer
7.144
940581AE2-045 GEN
Solar/Wind Harmer
13.329
971605AH1-302 GEN
Solar/Wind Harmer
11.397
971995AH1-542 GEN
Solar/Wind Harmer
14.364
964861AG1-349 GEN
Solar/Wind Harmer
10.259
971917AH1-482 GEN
Solar/Wind Harmer
11.837
958381AF2-132 GEN
Solar/Wind Harmer
11.837
958861AF2-177 GEN
Solar/Wind Harmer
14.251
965011AG1-365 GEN
Solar/Wind Harmer
13.038
270055AF2-134 C O1
Solar/Wind Harmer
3.941
270594AE1-207 GEN
Solar/Wind Harmer
17.691
270032AE2-172
Solar/Wind Harmer
6.059
24791305MDL-5G
Solar/Wind Harmer
3.14
970373AG2-245 GEN
Solar/Wind Harmer
27.345
945371AF1-202 GEN
Solar/Wind Harmer
9.051
276903AD2-071 C
Solar/Wind Harmer
12.933
24385905FR-11G C
Solar/Wind Harmer
10.714
24386605FR-22G C
Solar/Wind Harmer
5.544
270024AE2-089 GEN
Solar/Wind Harmer
6.037
972207SS24-0001
Solar/Wind Harmer
28.39
274773LINCOLN ;4U
Adder
7.985
274774LINCOLN ;5U
Adder
7.985
253316AC1-085 GEN3
Solar/Wind Harmer
10.757
946171AF1-282 GEN
Solar/Wind Harmer
12.848
970825AG2-519 GEN
Solar/Wind Harmer
2.692
270005AE1-210 C O1
Solar/Wind Harmer
7.007
274723RIVER EC ;12
Adder
22.949
274751CRETE EC ;1U
Adder
6.261
274754CRETE EC ;4U
Adder
6.261
270216AD2-079_GEN
Solar/Wind Harmer
0.774
274812UNIV PK N;8U
Adder
6.402
24639705ELKHART HY
Adder
0.196
274802UNIV PARK;5U
Adder
7.439
274676JOLIET 29;8U
Adder
39.004
274732ELWOOD EC;7P
Adder
20.89
274674JOLIET 9 ;6U
Adder
19.566
274745AC1-111 GEN9
Adder
7.074
274682WAUKEGAN ;7U
Adder
22.627
274828WAUKEGAN ;BP
Adder
13.9
274822ROCKFORD ;11
Adder
24.426
24728605AND G2
Adder
4.773
25194608D.CRK4
Adder
2.045
274761LEE CO EC;2U
Adder
11.506
274766LEE CO EC;7U
Adder
11.371
25196808ZIMRHP
Adder
93.121
25196008MFTGT1
Adder
1.698
970091AG2-072 GEN
Adder
53.308
254303AC2-168 GEN
Solar/Wind Helper
0.198
241966AE1-183 GEN
Solar/Wind Helper
0.312
961971AG1-040 GEN
Solar/Wind Helper
0.519
203830AF1-094 GEN
Solar/Wind Helper
0.518
203979AG1-198 GEN
Solar/Wind Helper
0.311
203947AF1-006 C
Solar/Wind Helper
0.563
20084626FORWARD
Solar/Wind Helper
0.371
20089026BF_G21_K23
Solar/Wind Helper
0.486
238185AF2-356 C
Solar/Wind Helper
2.181
964201AG1-281 GEN
Solar/Wind Helper
0.498
20091526CHSTN_FL
Solar/Wind Helper
0.601
20090526Q36
Solar/Wind Helper
1.056
203952AE2-129 C
Solar/Wind Helper
0.488
203855AF2-088 C
Solar/Wind Helper
0.158
238126S14_GEN_1
Solar/Wind Helper
0.662
238120AE2-309 GEN
Solar/Wind Helper
0.417
23751101LEADS_P59
Solar/Wind Helper
1.833
CPLELTFEXP_CPLE->PJM
CLTF
2.32
CBM West 2LTFEXP_CBM-W2->PJM
CBM
135.179
NYPJM->LTFIMP_NY
CLTF
5.166
LGEELTFEXP_LGEE->PJM
CLTF
7.844
WECLTFEXP_WEC->PJM
CLTF
4.747
AG2-052LTFEXP_AG2-052->PJM
LTF
0.298
AH1-155LTFEXP_AH1-155->PJM
LTF
0.446
LAGNLTFEXP_LAGN->PJM
CLTF
17.626
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.12
TVALTFEXP_TVA->PJM
CLTF
8.468
CBM West 1LTFEXP_CBM-W1->PJM
CBM
158.733
CBM South 1LTFEXP_CBM-S1->PJM
CBM
33.797
MECLTFEXP_MEC->PJM
CLTF
19.508
SIGELTFEXP_SIGE->PJM
CLTF
0.599

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o AEP_P4_#37_05MOUNTN 765_B1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.67 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4418.17
MW Contribution:
37.5
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.0 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5011.7
MW Contribution:
36.96
Bus #Bus NameTypeMW Contribution
270051AF1-062 GEN
50/50
18.043
270475AD2-096_GEN
50/50
10.581
962771AG1-126 GEN
Solar/Wind Harmer
60.725
970153AG2-106 GEN
Solar/Wind Harmer
26.479
961921AG1-034 GEN
Solar/Wind Harmer
23.018
270284AF1-227 GEN1
Solar/Wind Harmer
9.603
270287AF1-227 GEN3
Solar/Wind Harmer
3.552
942051AE2-217 GEN
Solar/Wind Harmer
29.041
270518AE2-148 GEN
Solar/Wind Harmer
18.756
253325AC1-069 GEN
Solar/Wind Harmer
1.601
942871AE2-306 GEN
Solar/Wind Harmer
1.368
270391AF1-285 GEN3
Solar/Wind Harmer
0.702
960801AF2-371 GEN
Solar/Wind Harmer
3.74
964871AG1-351 GEN
Solar/Wind Harmer
2.583
276820AF1-078_GEN
Solar/Wind Harmer
2.215
960071AF2-298 GEN
Solar/Wind Harmer
2.025
253303V4-073 C
Solar/Wind Harmer
0.155
253370AE2-315 SEC1
Adder
2.679
253371AE2-315 SEC2
Adder
2.534
270156DARBY CT1
50/50
0.841
270157DARBY CT2
50/50
0.839
270159DARBY CT4
50/50
0.828
270158DARBY CT3
50/50
0.826
270036AE2-216 BAT
50/50
9.265
270459AD2-067 GEN
Solar/Wind Harmer
15.114
961821AG1-024 GEN
Solar/Wind Harmer
15.345
241955AC1-078 GEN
Solar/Wind Harmer
12.389
945631AF1-228 GEN
Solar/Wind Harmer
7.606
241973AD2-163_GEN1
Solar/Wind Harmer
3.212
241974AD2-163_GEN2
Solar/Wind Harmer
3.212
943861AF1-054 GEN
Solar/Wind Harmer
6.137
943851AF1-053 GEN
Solar/Wind Harmer
2.966
253338AC1-165 GEN
Solar/Wind Harmer
1.66
253343AC1-166 GEN
Solar/Wind Harmer
1.66
270223U2-072_GEN1
Solar/Wind Harmer
2.978
270224U2-072_GEN2
Solar/Wind Harmer
2.978
270227U2-072_GEN3
Solar/Wind Harmer
2.978
270228U2-072_GEN4
Solar/Wind Harmer
2.978
270231U2-072_GEN5
Solar/Wind Harmer
2.978
270578AF1-285 GEN2
Solar/Wind Harmer
0.702
270432AC2-029 GEN
Solar/Wind Harmer
10.231
270302AB2-170 GEN
Solar/Wind Harmer
12.128
241972AD1-140 GEN
Solar/Wind Harmer
6.47
253372AE2-315 SEC3
Adder
2.534
253372AE2-315 SEC3
Adder
2.534
270071AF1-092 GEN
Solar/Wind Harmer
19.99
25306009OHH W.
Adder
3.829
270340AC2-060 GEN
Solar/Wind Harmer
4
270263AC1-001 GEN
Solar/Wind Harmer
1.378
24729505KEY G4
Adder
8.54
970289AG2-191 GEN
Solar/Wind Harmer
2.484
958711AF2-162 GEN
Solar/Wind Harmer
1.321
959141AF2-205 GEN
Solar/Wind Harmer
7.891
958391AF2-133 GEN
Solar/Wind Harmer
11.833
959331AF2-224 GEN
Solar/Wind Harmer
13.026
946581AF1-322 GEN
Solar/Wind Harmer
13.316
24691005MDL-2G C
Solar/Wind Harmer
4.812
253406AD2-031_GEN
Solar/Wind Harmer
1.656
945581AF1-223 GEN
Solar/Wind Harmer
5.879
960681AF2-359 GEN
Solar/Wind Harmer
4.892
963791AG1-232 GEN
Solar/Wind Harmer
17.431
24386405FR-21G C
Solar/Wind Harmer
5.54
24387005FR-3G C
Solar/Wind Harmer
5.095
274775LINCOLN ;6U
Adder
7.978
274776LINCOLN ;7U
Adder
7.978
274777LINCOLN ;8U
Adder
7.978
961761AG1-017 GEN
Solar/Wind Harmer
0.55
270526AF1-158 GEN
Solar/Wind Harmer
5.824
270119AB2-067 GEN1
50/50
13.691
270120AB2-067 GEN2
50/50
13.691
270160DARBY CT5
50/50
0.825
270161DARBY CT6
50/50
0.813
270466AD2-091
50/50
8.422
25326109MON D
50/50
1.903
25326509SID D
50/50
1.895
270349AD2-093_GEN
Solar/Wind Harmer
6.604
270471AD2-092_GEN
Solar/Wind Harmer
6.604
946101AF1-275 GEN
Solar/Wind Harmer
2.66
270054AF2-122 C O1
Solar/Wind Harmer
5.626
253383AE2-342_GEN
Solar/Wind Harmer
1.445
942861AE2-305 GEN
Solar/Wind Harmer
12.433
938701AE1-092 GEN
Solar/Wind Harmer
30.048
270462AD2-086
Solar/Wind Harmer
10.074
270269AC2-059
Solar/Wind Harmer
13.059
253378AE2-206_GEN
Solar/Wind Harmer
4.985
944531AF1-118 GEN
Solar/Wind Harmer
46.204
270043AE2-236 GEN
Solar/Wind Harmer
7.23
247642Z2-115 C
Solar/Wind Harmer
0.084
971347AH1-153 GEN
Solar/Wind Harmer
6.562
965461AG1-414 GEN
Solar/Wind Harmer
2.965
970289AG2-191 GEN
Solar/Wind Harmer
1.003
253394AE2-221_GEN
Solar/Wind Harmer
5.926
964401AG1-302 GEN
Solar/Wind Harmer
11.826
965021AG1-366 GEN
Solar/Wind Harmer
3.029
24690905MDL-1G C
Solar/Wind Harmer
10.447
970781AG2-491 GEN
Solar/Wind Harmer
13.014
24386205FR-12G C
Solar/Wind Harmer
5.52
274772LINCOLN ;3U
Adder
7.978
24441505OLIV SLR
Solar/Wind Harmer
0.172
962031AG1-047 GEN
Solar/Wind Harmer
3.883
957741AF2-068 GEN
Solar/Wind Harmer
19.265
253317AC1-085 GEN4
Solar/Wind Harmer
10.746
946181AF1-283 GEN
Solar/Wind Harmer
16.687
946031AF1-268 GEN
Solar/Wind Harmer
10.639
970825AG2-519 GEN
Solar/Wind Harmer
7.221
270004AE1-209 GEN
Solar/Wind Harmer
7.001
270063AE2-323 C
Solar/Wind Harmer
2.815
274724RIVER EC ;11
Adder
22.661
972231SS25-0005
Solar/Wind Harmer
12.145
972181SS23-001
Solar/Wind Harmer
7.591
274752CRETE EC ;2U
Adder
6.255
274753CRETE EC ;3U
Adder
6.255
247643Z2-116 C
Solar/Wind Harmer
0.089
276164X3-005 C
Solar/Wind Harmer
0.898
274814UNIV PK N;0U
Adder
6.452
274807UNIV PK N;3U
Adder
6.438
274811UNIV PK N;7U
Adder
6.396
274803UNIV PARK;6U
Adder
7.433
274826FISK ;BP
Adder
13.952
972259AH1-714 GEN
Adder
24.311
972038AH1-567 GEN2
Adder
0.465
274676JOLIET 29;8U
Adder
37.578
274729ELWOOD EC;1P
Adder
20.872
274730ELWOOD EC;6P
Adder
20.872
274734ELWOOD EC;8P
Adder
20.872
274736ELWOOD EC;9P
Adder
20.872
274682WAUKEGAN ;7U
Adder
22.607
25196608WSDLE5
Adder
10.674
24728505AND G1
Adder
4.768
25194608D.CRK4
Adder
2.043
274760LEE CO EC;1U
Adder
11.496
274767LEE CO EC;8U
Adder
11.361
25196008MFTGT1
Adder
1.643
235058AG1-386 C
Solar/Wind Helper
0.575
237048AF1-022 C
Solar/Wind Helper
0.205
237046AF1-021 C
Solar/Wind Helper
0.372
962511AG1-100 GEN
Solar/Wind Helper
0.518
202652Y1-033 WT C
Solar/Wind Helper
0.576
20092526R32
Solar/Wind Helper
1.21
964991AG1-363 GEN
Solar/Wind Helper
3.728
20303426NA_O38_P22
Solar/Wind Helper
1.017
23562501BACKB
Solar/Wind Helper
0.893
203993AD2-133_GEN1
Solar/Wind Helper
1.055
203854AF2-039 C
Solar/Wind Helper
0.327
20398826ARMNA MT
Solar/Wind Helper
1.511
238127S14_GEN_2
Solar/Wind Helper
0.662
941421AE2-139 GEN
Solar/Wind Helper
2.259
274887GEN-1.85
Solar/Wind Harmer
0.448
276843GEN-1.7
Solar/Wind Harmer
0.048
964611AG1-324 GEN
Solar/Wind Harmer
5.007
253433AC1-085 GEN1
Solar/Wind Harmer
6.821
253432AC1-085 GEN2
Solar/Wind Harmer
0.343
247536S-71 GEN
Solar/Wind Harmer
5.193
247521TR3_G114
Solar/Wind Harmer
4.309
270191TR4_S_V150
Solar/Wind Harmer
3.845
965051AG1-369 GEN
Solar/Wind Harmer
6.402
270543AE2-219 C
Solar/Wind Harmer
12.822
970031AG2-029 GEN
Solar/Wind Harmer
32.043
971771AH1-392 GEN
Solar/Wind Harmer
11.533
971029AG2-637 GEN
Solar/Wind Harmer
19.218
965041AG1-368 GEN
Solar/Wind Harmer
12.776
963841AG1-237 GEN
Solar/Wind Harmer
13.955
972228AH1-698 GEN2
Adder
4.722
972227AH1-698 GEN1
Adder
3.325
972037AH1-567 GEN1
Adder
0.233
274827FISK ;RP
Adder
9.888
274800UNIV PARK;3U
Adder
7.429
274801UNIV PARK;4U
Adder
7.429
274687WILL CNTY;4U
Adder
35.509
274687WILL CNTY;4U
Adder
35.509
274675JOLIET 29;7U
Adder
38.97
274675JOLIET 29;7U
Adder
37.578
274728ELWOOD EC;5P
Adder
20.872
274731ELWOOD EC;2P
Adder
20.872
274733ELWOOD EC;3P
Adder
20.872
274735ELWOOD EC;4P
Adder
20.872
274744AC1-111 GEN8
Adder
7.068
274746AC1-111 G10
Adder
7.068
25196408WSDLE3
Adder
10.988
274823ROCKFORD ;21
Adder
24.227
972267AH1-718 GEN
Adder
5.127
25196108MFTGT2
Adder
1.87
25196108MFTGT2
Adder
1.736
241985AE1-237 GEN
Solar/Wind Helper
0.309
241982AE2-343 S C
Solar/Wind Helper
0.277
241997AF1-093 GEN
Solar/Wind Helper
0.312
23652301WDPWR_K20
Solar/Wind Helper
0.16
23750501ELLIOTTS
Solar/Wind Helper
0.695
203846AF2-130 C
Solar/Wind Helper
0.498
20089126CSLMN_L13
Solar/Wind Helper
0.613
20089226LOOKOUT
Solar/Wind Helper
0.611
20088926STNY CRK
Solar/Wind Helper
0.849
20094526CT_V3-030
Solar/Wind Helper
0.494
203955AF1-039 C O1
Solar/Wind Helper
0.38
203940AF1-140 C
Solar/Wind Helper
0.411
20088626ARWF_N39
Solar/Wind Helper
1.24
20334926Z1-069 C
Solar/Wind Helper
1.403
23750701CROSSCHOOL
Solar/Wind Helper
1.182
238118U2-030_1
Solar/Wind Helper
0.283
25322209TAIT E
Adder
13.115
25322209TAIT E
Adder
12.82
253415AE1-040 GEN
Solar/Wind Harmer
1.511
253370AE2-315 SEC1
Adder
2.679
253349AC2-067 GEN
Solar/Wind Harmer
2.695
253400AC2-068 GEN
Solar/Wind Harmer
1.084
970349AG2-230 GEN
Solar/Wind Harmer
19.687
945421AF1-207 GEN
Solar/Wind Harmer
18.368
957841AF2-078 GEN
Solar/Wind Harmer
7.907
970291AG2-192 GEN
Solar/Wind Harmer
1.7
970291AG2-192 GEN
Solar/Wind Harmer
0.547
944541AF1-119 GEN
Solar/Wind Harmer
5.469
960971AF2-388 GEN
Solar/Wind Harmer
14.275
270535AF1-215 GEN1
Solar/Wind Harmer
5.907
270536AF1-215 GEN2
Solar/Wind Harmer
5.907
270180AB1-006 GEN1
Solar/Wind Harmer
9.359
24697605MDL-3G C
Solar/Wind Harmer
4.797
24755605MDL-5G
Solar/Wind Harmer
3.137
24697905MDL-4G C
Solar/Wind Harmer
2.986
270181AB1-006 GEN2
Solar/Wind Harmer
0.931
942221AE2-234 GEN
Solar/Wind Harmer
4.543
965681AG1-436 GEN
Solar/Wind Harmer
16.186
965791AG1-447 GEN
Solar/Wind Harmer
8.281
270031AE2-169
Solar/Wind Harmer
10.505
270599AE1-208 GEN
Solar/Wind Harmer
10.505
24387305FR-4G C
Solar/Wind Harmer
6.542
966841AG1-555 GEN
Solar/Wind Harmer
3.234
274770LINCOLN ;1U
Adder
7.978
274771LINCOLN ;2U
Adder
7.978
24725505WLD G2 C
Solar/Wind Harmer
5.114
24699105WLD G1 C
Solar/Wind Harmer
5.054
270201AC2-176 GEN
Solar/Wind Harmer
6.601
247621Y3-024
Adder
0.31
964611AG1-324 GEN
Solar/Wind Harmer
0.672
270246TR4_N_V150
Solar/Wind Harmer
1.09
270247TR4_N_V136
Solar/Wind Harmer
1.09
970883AG2-550 GEN
Solar/Wind Harmer
12.822
970885AG2-551 GEN
Solar/Wind Harmer
2.982
270383AD1-128 GEN
Solar/Wind Harmer
7.798
274805UNIV PK N;1U
Adder
6.41
274808UNIV PK N;4U
Adder
6.368
274888KELLY CRK;1U
Solar/Wind Harmer
7.524
247620Y3-023
Adder
0.586
274674JOLIET 9 ;6U
Adder
19.549
274695ROCKY RD ;2P
Adder
14.015
274693ROCKY RD ;1P
Adder
13.877
274697ROCKY RD ;3P
Adder
3.807
274696ROCKY RD ;4P
Adder
14.346
274683WAUKEGAN ;8U
Adder
26.494
274683WAUKEGAN ;8U
Adder
22.333
25194408D.CRK1
Adder
9.396
25194508D.CRK3
Adder
1.757
972235AH1-702 GEN1
Adder
3.131
972236AH1-702 GEN2
Adder
2.723
274764LEE CO EC;5U
Adder
11.523
274765LEE CO EC;6U
Adder
11.523
274762LEE CO EC;3U
Adder
11.496
274763LEE CO EC;4U
Adder
11.388
254304AE2-114 C
Solar/Wind Helper
0.274
254305AE2-115 C
Solar/Wind Helper
0.274
241967AE2-285_GEN
Solar/Wind Helper
0.791
241801AE1-079 GEN
Solar/Wind Helper
0.309
962101AG1-054 GEN
Solar/Wind Helper
0.794
237043AE2-125 C
Solar/Wind Helper
0.201
946071AF1-272 GEN
Solar/Wind Helper
2.879
203835AF1-098 GEN
Solar/Wind Helper
2.053
946381AF1-302 GEN
Solar/Wind Helper
0.237
20083426SW_E13_K22
Solar/Wind Helper
0.058
20088826HIGHLAND
Solar/Wind Helper
0.934
203818AF1-086 GEN
Solar/Wind Helper
1.772
23585401KL_K28_T16
Solar/Wind Helper
1.267
203853AF1-134 C O1
Solar/Wind Helper
0.497
203804AE2-113_GEN
Solar/Wind Helper
1.84
23751201ROTHROCK
Solar/Wind Helper
0.733
203961AE2-224 GEN
Solar/Wind Helper
2.479
940863AE2-074 GEN
Solar/Wind Helper
0.479
203954AE2-126 C
Solar/Wind Helper
0.489
235054AD2-180 GEN
Solar/Wind Helper
1.672
203946AE2-131 C
Solar/Wind Helper
0.488
238117U2-030
Solar/Wind Helper
0.283
235531U2-073 GEN
Solar/Wind Helper
2.67
270166AC1-044 GEN3
50/50
13.691
962761AG1-125 GEN
Solar/Wind Harmer
60.725
970149AG2-104 GEN
Solar/Wind Harmer
37.498
970155AG2-107 GEN
Solar/Wind Harmer
26.479
270520AE2-214 GEN
Solar/Wind Harmer
10.641
270286AF1-227 GEN2
Solar/Wind Harmer
3.552
253333AC1-068 GEN
Solar/Wind Harmer
1.601
270391AF1-285 GEN3
Solar/Wind Harmer
1.824
270578AF1-285 GEN2
Solar/Wind Harmer
1.824
270317AD1-130_GEN
Solar/Wind Harmer
4.636
270485AE1-090_GEN
Solar/Wind Harmer
0.876
270273AD2-016 GEN
Solar/Wind Harmer
3.724
25326309TAIT D
Adder
1.474
253370AE2-315 SEC1
Adder
2.679
253371AE2-315 SEC2
Adder
2.534
253398AE2-221_GEN2
Solar/Wind Harmer
5.926
965651AG1-433 GEN
Solar/Wind Harmer
7.138
940581AE2-045 GEN
Solar/Wind Harmer
13.318
971605AH1-302 GEN
Solar/Wind Harmer
11.387
971995AH1-542 GEN
Solar/Wind Harmer
14.349
964861AG1-349 GEN
Solar/Wind Harmer
10.25
971917AH1-482 GEN
Solar/Wind Harmer
11.826
958381AF2-132 GEN
Solar/Wind Harmer
11.826
958861AF2-177 GEN
Solar/Wind Harmer
14.238
965011AG1-365 GEN
Solar/Wind Harmer
13.026
270055AF2-134 C O1
Solar/Wind Harmer
3.938
24791305MDL-5G
Solar/Wind Harmer
3.137
270594AE1-207 GEN
Solar/Wind Harmer
17.675
270032AE2-172
Solar/Wind Harmer
6.053
970373AG2-245 GEN
Solar/Wind Harmer
27.321
945371AF1-202 GEN
Solar/Wind Harmer
9.043
276903AD2-071 C
Solar/Wind Harmer
12.921
24385905FR-11G C
Solar/Wind Harmer
10.705
24386605FR-22G C
Solar/Wind Harmer
5.54
270024AE2-089 GEN
Solar/Wind Harmer
6.032
972207SS24-0001
Solar/Wind Harmer
28.366
274773LINCOLN ;4U
Adder
7.978
274774LINCOLN ;5U
Adder
7.978
253316AC1-085 GEN3
Solar/Wind Harmer
10.746
946171AF1-282 GEN
Solar/Wind Harmer
12.836
970825AG2-519 GEN
Solar/Wind Harmer
2.69
270005AE1-210 C O1
Solar/Wind Harmer
7.001
274723RIVER EC ;12
Adder
22.929
274751CRETE EC ;1U
Adder
6.255
274754CRETE EC ;4U
Adder
6.255
270216AD2-079_GEN
Solar/Wind Harmer
0.773
274812UNIV PK N;8U
Adder
6.396
24639705ELKHART HY
Adder
0.196
274802UNIV PARK;5U
Adder
7.433
274676JOLIET 29;8U
Adder
38.97
274732ELWOOD EC;7P
Adder
20.872
274674JOLIET 9 ;6U
Adder
19.549
274745AC1-111 GEN9
Adder
7.068
274682WAUKEGAN ;7U
Adder
22.607
274828WAUKEGAN ;BP
Adder
13.888
274822ROCKFORD ;11
Adder
24.404
24728605AND G2
Adder
4.768
25194608D.CRK4
Adder
2.043
274761LEE CO EC;2U
Adder
11.496
274766LEE CO EC;7U
Adder
11.361
25196808ZIMRHP
Adder
93.029
25196008MFTGT1
Adder
1.696
970091AG2-072 GEN
Adder
53.258
254303AC2-168 GEN
Solar/Wind Helper
0.198
241966AE1-183 GEN
Solar/Wind Helper
0.312
961971AG1-040 GEN
Solar/Wind Helper
0.519
203830AF1-094 GEN
Solar/Wind Helper
0.518
203979AG1-198 GEN
Solar/Wind Helper
0.311
203947AF1-006 C
Solar/Wind Helper
0.563
20084626FORWARD
Solar/Wind Helper
0.371
20089026BF_G21_K23
Solar/Wind Helper
0.485
964201AG1-281 GEN
Solar/Wind Helper
0.498
238185AF2-356 C
Solar/Wind Helper
2.178
20091526CHSTN_FL
Solar/Wind Helper
0.601
20090526Q36
Solar/Wind Helper
1.055
203952AE2-129 C
Solar/Wind Helper
0.488
203855AF2-088 C
Solar/Wind Helper
0.158
238126S14_GEN_1
Solar/Wind Helper
0.662
238120AE2-309 GEN
Solar/Wind Helper
0.416
23751101LEADS_P59
Solar/Wind Helper
1.832
CPLELTFEXP_CPLE->PJM
CLTF
2.319
CBM West 2LTFEXP_CBM-W2->PJM
CBM
135.056
NYPJM->LTFIMP_NY
CLTF
5.162
LGEELTFEXP_LGEE->PJM
CLTF
7.836
WECLTFEXP_WEC->PJM
CLTF
4.743
AG2-052LTFEXP_AG2-052->PJM
LTF
0.297
AH1-155LTFEXP_AH1-155->PJM
LTF
0.446
LAGNLTFEXP_LAGN->PJM
CLTF
17.61
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.111
TVALTFEXP_TVA->PJM
CLTF
8.46
CBM West 1LTFEXP_CBM-W1->PJM
CBM
158.575
CBM South 1LTFEXP_CBM-S1->PJM
CBM
33.765
MECLTFEXP_MEC->PJM
CLTF
19.491
SIGELTFEXP_SIGE->PJM
CLTF
0.599

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o AP_P1-3_MP-765-501T_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.85 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4342.78
MW Contribution:
27.65
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.43 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4946.71
MW Contribution:
27.25
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
13.691
270120AB2-067 GEN2
50/50
13.691
270160DARBY CT5
50/50
0.825
270161DARBY CT6
50/50
0.813
270466AD2-091
50/50
8.422
25326109MON D
50/50
1.903
25326509SID D
50/50
1.895
270349AD2-093_GEN
Solar/Wind Harmer
0.002
270471AD2-092_GEN
Solar/Wind Harmer
0.002
270054AF2-122 C O1
Solar/Wind Harmer
0
942861AE2-305 GEN
Solar/Wind Harmer
8.674
938701AE1-092 GEN
Solar/Wind Harmer
16.303
971655AH1-328 GEN
Solar/Wind Harmer
3.602
270462AD2-086
Solar/Wind Harmer
0.001
270269AC2-059
Solar/Wind Harmer
0
970329AG2-216 GEN
Solar/Wind Harmer
4.181
25322209TAIT E
Adder
13.115
25322209TAIT E
Adder
12.82
253370AE2-315 SEC1
Adder
2.679
970349AG2-230 GEN
Solar/Wind Harmer
13.735
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0.001
970291AG2-192 GEN
Solar/Wind Harmer
1.186
970291AG2-192 GEN
Solar/Wind Harmer
0.547
944541AF1-119 GEN
Solar/Wind Harmer
0.609
960971AF2-388 GEN
Solar/Wind Harmer
5.346
270156DARBY CT1
50/50
0.841
270157DARBY CT2
50/50
0.839
270159DARBY CT4
50/50
0.828
270158DARBY CT3
50/50
0.826
270036AE2-216 BAT
50/50
9.265
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
7.494
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
945631AF1-228 GEN
Solar/Wind Harmer
0
943861AF1-054 GEN
Solar/Wind Harmer
4.282
943851AF1-053 GEN
Solar/Wind Harmer
2.966
270578AF1-285 GEN2
Solar/Wind Harmer
0.702
270432AC2-029 GEN
Solar/Wind Harmer
4.521
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.422
270051AF1-062 GEN
50/50
18.043
270475AD2-096_GEN
50/50
10.581
962771AG1-126 GEN
Solar/Wind Harmer
51.21
970153AG2-106 GEN
Solar/Wind Harmer
32.701
961921AG1-034 GEN
Solar/Wind Harmer
11.241
270284AF1-227 GEN1
Solar/Wind Harmer
0
942051AE2-217 GEN
Solar/Wind Harmer
20.261
270518AE2-148 GEN
Solar/Wind Harmer
0.888
253325AC1-069 GEN
Solar/Wind Harmer
0.012
270391AF1-285 GEN3
Solar/Wind Harmer
0.702
253370AE2-315 SEC1
Adder
2.679
253371AE2-315 SEC2
Adder
2.534
970191AG2-125 GEN
Solar/Wind Harmer
2.379
944531AF1-118 GEN
Solar/Wind Harmer
41.277
270043AE2-236 GEN
Solar/Wind Harmer
5.885
247642Z2-115 C
Solar/Wind Harmer
0.004
971347AH1-153 GEN
Solar/Wind Harmer
4.578
970289AG2-191 GEN
Solar/Wind Harmer
1.003
253394AE2-221_GEN
Solar/Wind Harmer
0.001
964401AG1-302 GEN
Solar/Wind Harmer
0.001
965021AG1-366 GEN
Solar/Wind Harmer
3.029
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
9.079
24386205FR-12G C
Solar/Wind Harmer
0
274772LINCOLN ;3U
Adder
10.86
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
13.441
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
11.642
946031AF1-268 GEN
Solar/Wind Harmer
8.511
970825AG2-519 GEN
Solar/Wind Harmer
6.737
270004AE1-209 GEN
Solar/Wind Harmer
1.936
270063AE2-323 C
Solar/Wind Harmer
0.001
274724RIVER EC ;11
Adder
22.661
274752CRETE EC ;2U
Adder
10.545
274753CRETE EC ;3U
Adder
10.545
274814UNIV PK N;0U
Adder
6.452
274807UNIV PK N;3U
Adder
6.438
274811UNIV PK N;7U
Adder
6.396
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
971613AH1-306 GEN
Solar/Wind Harmer
4.358
942221AE2-234 GEN
Solar/Wind Harmer
3.637
965681AG1-436 GEN
Solar/Wind Harmer
11.293
965791AG1-447 GEN
Solar/Wind Harmer
8.281
270031AE2-169
Solar/Wind Harmer
4.946
270599AE1-208 GEN
Solar/Wind Harmer
8.243
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
1.019
274770LINCOLN ;1U
Adder
10.86
274771LINCOLN ;2U
Adder
10.86
24725505WLD G2 C
Solar/Wind Harmer
0
241972AD1-140 GEN
Solar/Wind Harmer
1.102
253372AE2-315 SEC3
Adder
2.534
253372AE2-315 SEC3
Adder
2.534
270071AF1-092 GEN
Solar/Wind Harmer
17.821
25306009OHH W.
Adder
3.829
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.92
24729505KEY G4
Adder
8.54
970289AG2-191 GEN
Solar/Wind Harmer
1.733
971611AH1-305 GEN
Solar/Wind Harmer
5.423
959141AF2-205 GEN
Solar/Wind Harmer
0.001
958391AF2-133 GEN
Solar/Wind Harmer
0.001
959331AF2-224 GEN
Solar/Wind Harmer
6.362
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.671
945581AF1-223 GEN
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
963791AG1-232 GEN
Solar/Wind Harmer
12.161
971609AH1-304 GEN
Solar/Wind Harmer
1.469
24386405FR-21G C
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
10.86
274776LINCOLN ;7U
Adder
10.86
274777LINCOLN ;8U
Adder
10.86
270526AF1-158 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
3.493
247536S-71 GEN
Solar/Wind Harmer
0.358
247521TR3_G114
Solar/Wind Harmer
0.324
965051AG1-369 GEN
Solar/Wind Harmer
4.466
270543AE2-219 C
Solar/Wind Harmer
6.262
970031AG2-029 GEN
Solar/Wind Harmer
4.844
971771AH1-392 GEN
Solar/Wind Harmer
8.94
971029AG2-637 GEN
Solar/Wind Harmer
13.408
965041AG1-368 GEN
Solar/Wind Harmer
8.914
963841AG1-237 GEN
Solar/Wind Harmer
3.86
960591AF2-350 GEN
Solar/Wind Harmer
8.895
972228AH1-698 GEN2
Adder
4.722
972227AH1-698 GEN1
Adder
3.325
972037AH1-567 GEN1
Adder
0.233
274827FISK ;RP
Adder
9.888
274800UNIV PARK;3U
Adder
7.429
274801UNIV PARK;4U
Adder
7.429
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.124
274687WILL CNTY;4U
Adder
35.509
274687WILL CNTY;4U
Adder
35.509
274675JOLIET 29;7U
Adder
38.97
274675JOLIET 29;7U
Adder
37.578
274728ELWOOD EC;5P
Adder
20.872
274731ELWOOD EC;2P
Adder
20.872
274733ELWOOD EC;3P
Adder
20.872
274735ELWOOD EC;4P
Adder
20.872
970833AG2-524 GEN
Solar/Wind Harmer
9.741
970833AG2-524 GEN
Solar/Wind Harmer
6.494
274744AC1-111 GEN8
Adder
7.068
274746AC1-111 G10
Adder
7.068
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.922
270356AE2-297 GEN
Solar/Wind Harmer
0
970169AG2-114 GEN
Solar/Wind Harmer
8.736
971675AH1-338 GEN
Solar/Wind Harmer
3.397
276861AD2-134 GEN
Solar/Wind Harmer
0.155
276863AD2-134 GEN
Solar/Wind Harmer
0.155
971411AH1-196 GEN
Solar/Wind Harmer
13.063
25196408WSDLE3
Adder
10.988
971171AH1-044 GEN
Solar/Wind Harmer
17.379
926823AC1-168 GEN
Solar/Wind Harmer
1.477
270007AE1-245 C
Solar/Wind Harmer
0
274823ROCKFORD ;21
Adder
24.227
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
9.098
274856ECOGROVE ;U1
Solar/Wind Harmer
0.202
971681AH1-341 GEN
Solar/Wind Harmer
13.904
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.287
274887GEN-1.85
Solar/Wind Harmer
0.231
276843GEN-1.7
Solar/Wind Harmer
0.288
276806AD2-047 C O1
Solar/Wind Harmer
5.041
970707AG2-453 GEN
Solar/Wind Harmer
29.056
274803UNIV PARK;6U
Adder
7.433
274826FISK ;BP
Adder
13.952
939351AE1-166 GEN
Solar/Wind Harmer
0
972259AH1-714 GEN
Adder
24.311
972038AH1-567 GEN2
Adder
0.465
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.319
270491AE1-102 GEN2
Solar/Wind Harmer
1.154
274676JOLIET 29;8U
Adder
37.578
274729ELWOOD EC;1P
Adder
20.872
274730ELWOOD EC;6P
Adder
20.872
274734ELWOOD EC;8P
Adder
20.872
274736ELWOOD EC;9P
Adder
20.872
270505AE1-170 C O1
Solar/Wind Harmer
9.267
943121AE2-341 GEN
Solar/Wind Harmer
14.798
943591AF1-030 GEN
Solar/Wind Harmer
9.841
945111AF1-176 GEN
Solar/Wind Harmer
7.15
24695305TIMB G C
Solar/Wind Harmer
0.747
274862TOP CROP ;2U
Solar/Wind Harmer
1.188
274682WAUKEGAN ;7U
Adder
22.607
276868AE1-113 GEN
Solar/Wind Harmer
1.751
274879MINONK ;1U
Solar/Wind Harmer
0.365
946671AF1-331 GEN
Solar/Wind Harmer
0.929
274855GSG-6 ;RU
Solar/Wind Harmer
0.318
274850MENDOTA H;RU
Solar/Wind Harmer
0.101
25196608WSDLE5
Adder
10.674
959091AF2-200 GEN
Solar/Wind Harmer
17.379
970571AG2-364 GEN
Solar/Wind Harmer
17.368
24728505AND G1
Adder
4.768
25194608D.CRK4
Adder
2.043
252519AF1-045_GEN
Solar/Wind Harmer
4.521
965091AG1-374 GEN
Solar/Wind Harmer
25.867
959611AF2-252 GEN
Solar/Wind Harmer
2.874
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
11.496
274767LEE CO EC;8U
Adder
11.361
970193AG2-126 GEN
Solar/Wind Harmer
12.901
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.287
252507AC2-088 GEN
Solar/Wind Harmer
0.384
971993AH1-541 GEN
Solar/Wind Harmer
3.929
24699105WLD G1 C
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
247621Y3-024
Adder
0.31
964611AG1-324 GEN
Solar/Wind Harmer
0.672
270246TR4_N_V150
Solar/Wind Harmer
0.057
270247TR4_N_V136
Solar/Wind Harmer
0.057
970883AG2-550 GEN
Solar/Wind Harmer
8.946
970885AG2-551 GEN
Solar/Wind Harmer
2.982
270383AD1-128 GEN
Solar/Wind Harmer
0
274805UNIV PK N;1U
Adder
6.41
274808UNIV PK N;4U
Adder
6.368
274888KELLY CRK;1U
Solar/Wind Harmer
0.519
276776AD2-060 GEN
Solar/Wind Harmer
0.949
958011AF2-095 GEN
Solar/Wind Harmer
12.809
970941AG2-585 GEN
Solar/Wind Harmer
4.892
276897AD1-100 C
Solar/Wind Harmer
22.228
247620Y3-023
Adder
0.586
926881AC1-175 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.358
274674JOLIET 9 ;6U
Adder
19.549
276893AG1-478 C
Solar/Wind Harmer
0.591
970241AG2-163 GEN
Solar/Wind Harmer
5.155
958481AF2-142 GEN
Solar/Wind Harmer
13.2
961051AF2-396 GEN
Solar/Wind Harmer
17.567
961051AF2-396 GEN
Solar/Wind Harmer
11.711
274695ROCKY RD ;2P
Adder
14.015
274693ROCKY RD ;1P
Adder
13.877
274697ROCKY RD ;3P
Adder
3.807
274696ROCKY RD ;4P
Adder
14.346
274683WAUKEGAN ;8U
Adder
26.494
274683WAUKEGAN ;8U
Adder
22.333
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
13.148
962691AG1-118 GEN
Solar/Wind Harmer
26.273
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
25183208HLCRTG
Solar/Wind Harmer
0.001
971341AH1-150 GEN
Solar/Wind Harmer
17.379
971343AH1-151 GEN
Solar/Wind Harmer
17.379
247607V1-011 GEN
Solar/Wind Harmer
0
25194408D.CRK1
Adder
9.396
25194508D.CRK3
Adder
1.757
972235AH1-702 GEN1
Adder
3.131
972236AH1-702 GEN2
Adder
2.723
942111AE2-223 GEN
Solar/Wind Harmer
2.816
938861AE1-114 GEN
Solar/Wind Harmer
4.893
960611AF2-352 GEN
Solar/Wind Harmer
2.874
276645AC1-214 GEN1
Solar/Wind Harmer
0.338
274764LEE CO EC;5U
Adder
11.523
274765LEE CO EC;6U
Adder
11.523
274762LEE CO EC;3U
Adder
11.496
274763LEE CO EC;4U
Adder
11.388
945391AF1-204 GEN
Solar/Wind Harmer
9.138
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.387
252509AD1-136 GEN
Solar/Wind Harmer
0.043
276615X2-022 GEN
Solar/Wind Harmer
0.088
276838X2-022 GEN2
Solar/Wind Harmer
0.476
970623AG2-406 GEN
Solar/Wind Harmer
1.547
962581AG1-107 GEN
Solar/Wind Harmer
0.001
971587AH1-292 GEN
Solar/Wind Harmer
6.129
276916AD2-100_GEN
Solar/Wind Harmer
17.538
276911AD2-131_GEN
Solar/Wind Harmer
1.155
254304AE2-114 C
Solar/Wind Helper
0.274
254305AE2-115 C
Solar/Wind Helper
0.274
241967AE2-285_GEN
Solar/Wind Helper
0.791
241801AE1-079 GEN
Solar/Wind Helper
0.309
962101AG1-054 GEN
Solar/Wind Helper
0.794
237043AE2-125 C
Solar/Wind Helper
0.201
946071AF1-272 GEN
Solar/Wind Helper
2.879
203835AF1-098 GEN
Solar/Wind Helper
2.053
946381AF1-302 GEN
Solar/Wind Helper
0.237
20083426SW_E13_K22
Solar/Wind Helper
0.058
20088826HIGHLAND
Solar/Wind Helper
0.934
203818AF1-086 GEN
Solar/Wind Helper
1.772
23585401KL_K28_T16
Solar/Wind Helper
1.267
203853AF1-134 C O1
Solar/Wind Helper
0.497
203804AE2-113_GEN
Solar/Wind Helper
1.84
23751201ROTHROCK
Solar/Wind Helper
0.733
203961AE2-224 GEN
Solar/Wind Helper
2.479
940863AE2-074 GEN
Solar/Wind Helper
0.479
203954AE2-126 C
Solar/Wind Helper
0.489
235054AD2-180 GEN
Solar/Wind Helper
1.672
203946AE2-131 C
Solar/Wind Helper
0.488
238117U2-030
Solar/Wind Helper
0.283
235531U2-073 GEN
Solar/Wind Helper
2.67
276741O09 GEN1
Solar/Wind Harmer
0.303
972267AH1-718 GEN
Adder
5.127
276668AB2-070 GEN1
Solar/Wind Harmer
0.334
276848AB2-070 GEN3
Solar/Wind Harmer
0.333
276849AB2-070 GEN2
Solar/Wind Harmer
0.334
25196108MFTGT2
Adder
1.87
25196108MFTGT2
Adder
1.736
946321AF1-296 GEN
Solar/Wind Harmer
4.758
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
241985AE1-237 GEN
Solar/Wind Helper
0.309
241982AE2-343 S C
Solar/Wind Helper
0.277
241997AF1-093 GEN
Solar/Wind Helper
0.312
23652301WDPWR_K20
Solar/Wind Helper
0.16
23750501ELLIOTTS
Solar/Wind Helper
0.695
203846AF2-130 C
Solar/Wind Helper
0.498
20089126CSLMN_L13
Solar/Wind Helper
0.613
20089226LOOKOUT
Solar/Wind Helper
0.611
20088926STNY CRK
Solar/Wind Helper
0.849
20094526CT_V3-030
Solar/Wind Helper
0.494
203955AF1-039 C O1
Solar/Wind Helper
0.38
203940AF1-140 C
Solar/Wind Helper
0.411
20088626ARWF_N39
Solar/Wind Helper
1.24
20334926Z1-069 C
Solar/Wind Helper
1.403
23750701CROSSCHOOL
Solar/Wind Helper
1.182
238118U2-030_1
Solar/Wind Helper
0.283
270166AC1-044 GEN3
50/50
13.691
962761AG1-125 GEN
Solar/Wind Harmer
51.21
970149AG2-104 GEN
Solar/Wind Harmer
27.654
970155AG2-107 GEN
Solar/Wind Harmer
32.701
270520AE2-214 GEN
Solar/Wind Harmer
0.001
253333AC1-068 GEN
Solar/Wind Harmer
0.012
270317AD1-130_GEN
Solar/Wind Harmer
-0.001
270273AD2-016 GEN
Solar/Wind Harmer
1.001
25326309TAIT D
Adder
1.474
253370AE2-315 SEC1
Adder
2.679
253371AE2-315 SEC2
Adder
2.534
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
2.673
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
11.387
971995AH1-542 GEN
Solar/Wind Harmer
3.337
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.826
958381AF2-132 GEN
Solar/Wind Harmer
0.001
958861AF2-177 GEN
Solar/Wind Harmer
3.938
965011AG1-365 GEN
Solar/Wind Harmer
9.088
270055AF2-134 C O1
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
10.169
270032AE2-172
Solar/Wind Harmer
6.053
970373AG2-245 GEN
Solar/Wind Harmer
19.061
945371AF1-202 GEN
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
10.066
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
274773LINCOLN ;4U
Adder
10.86
274774LINCOLN ;5U
Adder
10.86
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
8.955
970825AG2-519 GEN
Solar/Wind Harmer
3.175
270005AE1-210 C O1
Solar/Wind Harmer
1.936
274723RIVER EC ;12
Adder
22.929
274751CRETE EC ;1U
Adder
10.545
274754CRETE EC ;4U
Adder
10.545
274812UNIV PK N;8U
Adder
6.396
24639705ELKHART HY
Adder
0.196
965421AG1-410 GEN
Solar/Wind Harmer
26.684
274802UNIV PARK;5U
Adder
7.433
941551AE2-152 GEN
Solar/Wind Harmer
0.001
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
6.512
246936BC-WTG1
Solar/Wind Harmer
0.358
270489AE1-102 GEN1
Solar/Wind Harmer
1.154
274676JOLIET 29;8U
Adder
38.97
274732ELWOOD EC;7P
Adder
20.872
274674JOLIET 9 ;6U
Adder
19.549
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
20.916
957891AF2-083 GEN
Solar/Wind Harmer
14.717
274745AC1-111 GEN9
Adder
7.068
945111AF1-176 GEN
Solar/Wind Harmer
15.739
939401AE1-172 GEN
Solar/Wind Harmer
6.59
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.43
274861TOP CROP ;1U
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
22.607
274828WAUKEGAN ;BP
Adder
13.888
276805AD2-038 GEN
Solar/Wind Harmer
0
970773AG2-487 GEN
Solar/Wind Harmer
1.548
270449AD2-020 GEN
Solar/Wind Harmer
-0.001
943021AE2-325 GEN
Solar/Wind Harmer
4.573
971997AH1-543 GEN
Solar/Wind Harmer
4.591
276882AE2-255 GEN
Solar/Wind Harmer
1.021
962781AG1-127 GEN
Solar/Wind Harmer
8.326
274872LEEDK;1U
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
26.068
959081AF2-199 GEN
Solar/Wind Harmer
8.689
971067AG2-660 GEN
Solar/Wind Harmer
2.896
970569AG2-363 GEN
Solar/Wind Harmer
26.052
274822ROCKFORD ;11
Adder
24.404
24728605AND G2
Adder
4.768
25194608D.CRK4
Adder
2.043
252516AE2-318_GEN
Solar/Wind Harmer
9.707
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
12.131
970819AG2-516 GEN
Solar/Wind Harmer
10.388
252510AF1-249 C
Solar/Wind Harmer
0.065
276646AC1-214 GEN2
Solar/Wind Harmer
0.338
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
11.496
274766LEE CO EC;7U
Adder
11.361
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.303
25196808ZIMRHP
Adder
93.029
25196008MFTGT1
Adder
1.696
276621W2-048 GEN
Solar/Wind Harmer
0.423
965911AG1-460 GEN
Solar/Wind Harmer
1.674
970091AG2-072 GEN
Adder
16.07
254303AC2-168 GEN
Solar/Wind Helper
0.198
241966AE1-183 GEN
Solar/Wind Helper
0.312
961971AG1-040 GEN
Solar/Wind Helper
0.519
203830AF1-094 GEN
Solar/Wind Helper
0.518
203979AG1-198 GEN
Solar/Wind Helper
0.311
203947AF1-006 C
Solar/Wind Helper
0.563
20084626FORWARD
Solar/Wind Helper
0.371
20089026BF_G21_K23
Solar/Wind Helper
0.485
964201AG1-281 GEN
Solar/Wind Helper
0.498
238185AF2-356 C
Solar/Wind Helper
2.178
20091526CHSTN_FL
Solar/Wind Helper
0.601
20090526Q36
Solar/Wind Helper
1.055
203952AE2-129 C
Solar/Wind Helper
0.488
203855AF2-088 C
Solar/Wind Helper
0.158
238126S14_GEN_1
Solar/Wind Helper
0.662
238120AE2-309 GEN
Solar/Wind Helper
0.416
23751101LEADS_P59
Solar/Wind Helper
1.832
25196008MFTGT1
Adder
1.643
965931AG1-462 GEN
Solar/Wind Harmer
21.621
971087AG2-675 GEN
Solar/Wind Harmer
4.522
957381AF2-032 GEN
Solar/Wind Harmer
1.898
942481AE2-261 GEN
Solar/Wind Harmer
25.023
270367AC2-061_GEN
Solar/Wind Harmer
-0.001
235058AG1-386 C
Solar/Wind Helper
0.575
237048AF1-022 C
Solar/Wind Helper
0.205
237046AF1-021 C
Solar/Wind Helper
0.372
962511AG1-100 GEN
Solar/Wind Helper
0.518
202652Y1-033 WT C
Solar/Wind Helper
0.576
20092526R32
Solar/Wind Helper
1.21
964991AG1-363 GEN
Solar/Wind Helper
3.728
20303426NA_O38_P22
Solar/Wind Helper
1.017
23562501BACKB
Solar/Wind Helper
0.893
203993AD2-133_GEN1
Solar/Wind Helper
1.055
203854AF2-039 C
Solar/Wind Helper
0.327
20398826ARMNA MT
Solar/Wind Helper
1.511
238127S14_GEN_2
Solar/Wind Helper
0.662
941421AE2-139 GEN
Solar/Wind Helper
2.259
958171AF2-111 GEN
Solar/Wind Harmer
13.887
CPLELTFEXP_CPLE->PJM
CLTF
2.319
CBM West 2LTFEXP_CBM-W2->PJM
CBM
135.056
NYPJM->LTFIMP_NY
CLTF
5.162
LGEELTFEXP_LGEE->PJM
CLTF
7.836
WECLTFEXP_WEC->PJM
CLTF
4.743
AG2-052LTFEXP_AG2-052->PJM
LTF
0.297
AH1-155LTFEXP_AH1-155->PJM
LTF
0.446
LAGNLTFEXP_LAGN->PJM
CLTF
17.61
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.111
TVALTFEXP_TVA->PJM
CLTF
8.46
CBM West 1LTFEXP_CBM-W1->PJM
CBM
158.575
CBM South 1LTFEXP_CBM-S1->PJM
CBM
33.765
MECLTFEXP_MEC->PJM
CLTF
19.491
SIGELTFEXP_SIGE->PJM
CLTF
0.599

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o AEP_P1-2_#706_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#706_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.04 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4309.27
MW Contribution:
39.68
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#706_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:92.06 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:3813.12
MW Contribution:
37.9
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
17.244
270120AB2-067 GEN2
50/50
17.244
270349AD2-093_GEN
Solar/Wind Harmer
0.002
270471AD2-092_GEN
Solar/Wind Harmer
0.002
270054AF2-122 C O1
Solar/Wind Harmer
0
942861AE2-305 GEN
Solar/Wind Harmer
10.655
270462AD2-086
Solar/Wind Harmer
0.002
938701AE1-092 GEN
Solar/Wind Harmer
21.46
971655AH1-328 GEN
Solar/Wind Harmer
4.742
970329AG2-216 GEN
Solar/Wind Harmer
5.083
25326509SID D
Adder
2.143
246937BC-WTG2
Solar/Wind Harmer
0.455
270246TR4_N_V150
Solar/Wind Harmer
0.071
270247TR4_N_V136
Solar/Wind Harmer
0.071
247607V1-011 GEN
Solar/Wind Harmer
0
970349AG2-230 GEN
Solar/Wind Harmer
16.464
247620Y3-023
Adder
0.71
965681AG1-436 GEN
Solar/Wind Harmer
13.426
965791AG1-447 GEN
Solar/Wind Harmer
9.845
970623AG2-406 GEN
Solar/Wind Harmer
1.96
961051AF2-396 GEN
Solar/Wind Harmer
21.315
961051AF2-396 GEN
Solar/Wind Harmer
14.21
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
25326109MON D
Adder
1.994
942221AE2-234 GEN
Solar/Wind Harmer
4.232
944541AF1-119 GEN
Solar/Wind Harmer
0.7
960971AF2-388 GEN
Solar/Wind Harmer
6.145
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0.001
970621AG2-405 GEN
Solar/Wind Harmer
1.914
944231AF1-091 GEN
Solar/Wind Harmer
24.097
274770LINCOLN ;1U
Adder
12.619
274771LINCOLN ;2U
Adder
12.619
270269AC2-059
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274805UNIV PK N;1U
Adder
7.439
274808UNIV PK N;4U
Adder
7.391
25322209TAIT E
Adder
14.396
25322209TAIT E
Adder
14.072
970291AG2-192 GEN
Solar/Wind Harmer
1.338
970291AG2-192 GEN
Solar/Wind Harmer
0.618
274888KELLY CRK;1U
Solar/Wind Harmer
0.6
276776AD2-060 GEN
Solar/Wind Harmer
1.097
958011AF2-095 GEN
Solar/Wind Harmer
14.803
970941AG2-585 GEN
Solar/Wind Harmer
5.654
276897AD1-100 C
Solar/Wind Harmer
25.624
971613AH1-306 GEN
Solar/Wind Harmer
4.9
274674JOLIET 9 ;6U
Adder
22.504
276893AG1-478 C
Solar/Wind Harmer
0.68
270031AE2-169
Solar/Wind Harmer
5.58
270599AE1-208 GEN
Solar/Wind Harmer
9.3
253370AE2-315 SEC1
Adder
2.904
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
1.147
270201AC2-176 GEN
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
15.103
247621Y3-024
Adder
0.348
964611AG1-324 GEN
Solar/Wind Harmer
0.754
274696ROCKY RD ;4P
Adder
16.391
274695ROCKY RD ;2P
Adder
16.014
274693ROCKY RD ;1P
Adder
15.856
274697ROCKY RD ;3P
Adder
4.35
274683WAUKEGAN ;8U
Adder
30.253
274683WAUKEGAN ;8U
Adder
25.502
958491AF2-143 GEN
Solar/Wind Harmer
14.984
962691AG1-118 GEN
Solar/Wind Harmer
29.945
276901AD2-066 C O1
Solar/Wind Harmer
-0.001
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
9.92
970885AG2-551 GEN
Solar/Wind Harmer
3.307
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
19.677
971343AH1-151 GEN
Solar/Wind Harmer
19.677
972235AH1-702 GEN1
Adder
3.539
972236AH1-702 GEN2
Adder
3.077
270383AD1-128 GEN
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
5.694
938861AE1-114 GEN
Solar/Wind Harmer
5.51
274764LEE CO EC;5U
Adder
12.96
274765LEE CO EC;6U
Adder
12.96
274762LEE CO EC;3U
Adder
12.93
274763LEE CO EC;4U
Adder
12.808
926881AC1-175 GEN
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
3.143
276645AC1-214 GEN1
Solar/Wind Harmer
0.379
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.554
960611AF2-352 GEN
Solar/Wind Harmer
3.19
945391AF1-204 GEN
Solar/Wind Harmer
9.764
276615X2-022 GEN
Solar/Wind Harmer
0.095
276838X2-022 GEN2
Solar/Wind Harmer
0.516
25194408D.CRK1
Adder
9.313
25194508D.CRK3
Adder
1.741
972159AH1-661 GEN
Adder
1.225
23751201ROTHROCK
Solar/Wind Helper
0.691
23585401KL_K28_T16
Solar/Wind Helper
1.178
237043AE2-125 C
Solar/Wind Helper
0.16
235054AD2-180 GEN
Solar/Wind Helper
1.576
238117U2-030
Solar/Wind Helper
0.267
235531U2-073 GEN
Solar/Wind Helper
2.548
24721605FLATG1
50/50
3.319
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
9.821
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
270578AF1-285 GEN2
Solar/Wind Harmer
0.932
945631AF1-228 GEN
Solar/Wind Harmer
-0.001
943861AF1-054 GEN
Solar/Wind Harmer
5.259
943851AF1-053 GEN
Solar/Wind Harmer
3.643
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.888
241972AD1-140 GEN
Solar/Wind Harmer
1.272
270432AC2-029 GEN
Solar/Wind Harmer
5.04
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.43
959331AF2-224 GEN
Solar/Wind Harmer
7.844
247521TR3_G114
Solar/Wind Harmer
0.403
965051AG1-369 GEN
Solar/Wind Harmer
5.558
270071AF1-092 GEN
Solar/Wind Harmer
21.261
965041AG1-368 GEN
Solar/Wind Harmer
11.063
270007AE1-245 C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
5.889
970179AG2-119 GEN
Solar/Wind Harmer
9.709
971771AH1-392 GEN
Solar/Wind Harmer
10.756
963791AG1-232 GEN
Solar/Wind Harmer
14.514
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270526AF1-158 GEN
Solar/Wind Harmer
0.001
24729505KEY G4
Adder
9.953
958391AF2-133 GEN
Solar/Wind Harmer
0.002
959141AF2-205 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
6.264
274775LINCOLN ;6U
Adder
12.619
274776LINCOLN ;7U
Adder
12.619
274777LINCOLN ;8U
Adder
12.619
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
1.956
972037AH1-567 GEN1
Adder
0.27
274827FISK ;RP
Adder
11.436
960591AF2-350 GEN
Solar/Wind Harmer
10.28
274800UNIV PARK;3U
Adder
8.587
274801UNIV PARK;4U
Adder
8.587
972228AH1-698 GEN2
Adder
5.454
972227AH1-698 GEN1
Adder
3.84
945581AF1-223 GEN
Solar/Wind Harmer
0.001
274687WILL CNTY;4U
Adder
40.93
274687WILL CNTY;4U
Adder
40.93
274675JOLIET 29;7U
Adder
44.89
274675JOLIET 29;7U
Adder
43.287
274728ELWOOD EC;5P
Adder
24.024
274731ELWOOD EC;2P
Adder
24.024
274733ELWOOD EC;3P
Adder
24.024
274735ELWOOD EC;4P
Adder
24.024
970833AG2-524 GEN
Solar/Wind Harmer
11.198
970833AG2-524 GEN
Solar/Wind Harmer
7.465
270377AD1-106 GEN
Solar/Wind Harmer
3.864
971609AH1-304 GEN
Solar/Wind Harmer
1.657
971549AH1-272 GEN
Solar/Wind Harmer
20.903
274744AC1-111 GEN8
Adder
8.105
274746AC1-111 G10
Adder
8.105
253372AE2-315 SEC3
Adder
2.747
253372AE2-315 SEC3
Adder
2.747
24386405FR-21G C
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
3.923
25306009OHH W.
Adder
4.15
247536S-71 GEN
Solar/Wind Harmer
0.4
970073AG2-061 GEN
Solar/Wind Harmer
3.33
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
4.303
270543AE2-219 C
Solar/Wind Harmer
6.944
971675AH1-338 GEN
Solar/Wind Harmer
3.854
971411AH1-196 GEN
Solar/Wind Harmer
14.823
276861AD2-134 GEN
Solar/Wind Harmer
0.176
276863AD2-134 GEN
Solar/Wind Harmer
0.176
970169AG2-114 GEN
Solar/Wind Harmer
9.859
971171AH1-044 GEN
Solar/Wind Harmer
19.677
971029AG2-637 GEN
Solar/Wind Harmer
14.756
274823ROCKFORD ;21
Adder
27.402
926823AC1-168 GEN
Solar/Wind Harmer
1.667
274856ECOGROVE ;U1
Solar/Wind Harmer
0.228
971681AH1-341 GEN
Solar/Wind Harmer
15.659
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
10.156
972267AH1-718 GEN
Adder
5.748
276741O09 GEN1
Solar/Wind Harmer
0.34
274877BISHOP HL;1U
Solar/Wind Harmer
0.321
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
5.283
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270356AE2-297 GEN
Solar/Wind Harmer
-0.001
276668AB2-070 GEN1
Solar/Wind Harmer
0.365
276848AB2-070 GEN3
Solar/Wind Harmer
0.363
276849AB2-070 GEN2
Solar/Wind Harmer
0.365
270263AC1-001 GEN
Solar/Wind Harmer
0.924
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.684
25196408WSDLE3
Adder
10.931
25196108MFTGT2
Adder
1.832
25196108MFTGT2
Adder
1.701
23750501ELLIOTTS
Solar/Wind Helper
0.6
23652301WDPWR_K20
Solar/Wind Helper
0.129
23750701CROSSCHOOL
Solar/Wind Helper
1.119
238118U2-030_1
Solar/Wind Helper
0.267
203955AF1-039 C O1
Solar/Wind Helper
0.331
270166AC1-044 GEN3
50/50
17.244
24721705FLATG2
50/50
3.319
24721805FLATG3
50/50
3.319
962761AG1-125 GEN
Solar/Wind Harmer
73.48
970149AG2-104 GEN
Solar/Wind Harmer
39.681
970155AG2-107 GEN
Solar/Wind Harmer
46.922
270520AE2-214 GEN
Solar/Wind Harmer
0.001
270317AD1-130_GEN
Solar/Wind Harmer
-0.001
253333AC1-068 GEN
Solar/Wind Harmer
0.014
971995AH1-542 GEN
Solar/Wind Harmer
4.575
246936BC-WTG1
Solar/Wind Harmer
0.455
270489AE1-102 GEN1
Solar/Wind Harmer
1.468
965421AG1-410 GEN
Solar/Wind Harmer
33.842
965011AG1-365 GEN
Solar/Wind Harmer
11.206
24639705ELKHART HY
Adder
0.237
957891AF2-083 GEN
Solar/Wind Harmer
17.821
945111AF1-176 GEN
Solar/Wind Harmer
19.076
970373AG2-245 GEN
Solar/Wind Harmer
22.382
270449AD2-020 GEN
Solar/Wind Harmer
-0.001
943021AE2-325 GEN
Solar/Wind Harmer
5.553
270055AF2-134 C O1
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.002
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
13.746
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
13.152
965651AG1-433 GEN
Solar/Wind Harmer
3.072
274773LINCOLN ;4U
Adder
12.619
274774LINCOLN ;5U
Adder
12.619
958861AF2-177 GEN
Solar/Wind Harmer
4.506
274751CRETE EC ;1U
Adder
12.279
274754CRETE EC ;4U
Adder
12.279
270273AD2-016 GEN
Solar/Wind Harmer
1.064
274723RIVER EC ;12
Adder
26.668
270024AE2-089 GEN
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
7.423
25326309TAIT D
Adder
1.618
274802UNIV PARK;5U
Adder
8.599
945371AF1-202 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
44.89
270594AE1-207 GEN
Solar/Wind Harmer
11.433
270032AE2-172
Solar/Wind Harmer
6.805
274674JOLIET 9 ;6U
Adder
22.504
274732ELWOOD EC;7P
Adder
24.024
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
241813AF1-122_GEN
Solar/Wind Harmer
4.544
971201AH1-060 GEN
Solar/Wind Harmer
2.029
274745AC1-111 GEN9
Adder
8.105
253370AE2-315 SEC1
Adder
2.904
253371AE2-315 SEC2
Adder
2.747
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.636
274861TOP CROP ;1U
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
11.216
939401AE1-172 GEN
Solar/Wind Harmer
7.51
274682WAUKEGAN ;7U
Adder
25.826
274828WAUKEGAN ;BP
Adder
15.858
276805AD2-038 GEN
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
9.482
276882AE2-255 GEN
Solar/Wind Harmer
1.162
274872LEEDK;1U
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
5.217
970825AG2-519 GEN
Solar/Wind Harmer
3.528
270005AE1-210 C O1
Solar/Wind Harmer
2.149
957471AF2-041 GEN
Solar/Wind Harmer
29.515
959081AF2-199 GEN
Solar/Wind Harmer
9.838
971067AG2-660 GEN
Solar/Wind Harmer
3.279
274822ROCKFORD ;11
Adder
27.602
970569AG2-363 GEN
Solar/Wind Harmer
29.408
970819AG2-516 GEN
Solar/Wind Harmer
11.727
963741AG1-226 GEN
Solar/Wind Harmer
23.101
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
12.93
274766LEE CO EC;7U
Adder
12.777
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
7.109
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
13.541
276646AC1-214 GEN2
Solar/Wind Harmer
0.379
276708O09 GEN2
Solar/Wind Harmer
0.34
274848CAMPGROVE;RU
Solar/Wind Harmer
0
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
970773AG2-487 GEN
Solar/Wind Harmer
1.647
24728605AND G2
Adder
5.071
276621W2-048 GEN
Solar/Wind Harmer
0.459
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
9.029
25194608D.CRK4
Adder
2.025
25196008MFTGT1
Adder
1.662
23906502RICHG2&3
Adder
1.439
25196808ZIMRHP
Adder
90.149
970091AG2-072 GEN
Adder
20.654
238185AF2-356 C
Solar/Wind Helper
2.037
23751101LEADS_P59
Solar/Wind Helper
1.839
238120AE2-309 GEN
Solar/Wind Helper
0.401
238126S14_GEN_1
Solar/Wind Helper
0.635
965911AG1-460 GEN
Solar/Wind Harmer
1.103
24721905FLATG4
50/50
3.319
24722005FLATG5
50/50
3.319
270051AF1-062 GEN
50/50
23.559
270475AD2-096_GEN
50/50
14.072
962771AG1-126 GEN
Solar/Wind Harmer
73.48
970153AG2-106 GEN
Solar/Wind Harmer
46.922
961921AG1-034 GEN
Solar/Wind Harmer
14.732
270284AF1-227 GEN1
Solar/Wind Harmer
0
270391AF1-285 GEN3
Solar/Wind Harmer
0.932
942051AE2-217 GEN
Solar/Wind Harmer
25.116
270518AE2-148 GEN
Solar/Wind Harmer
1.063
253325AC1-069 GEN
Solar/Wind Harmer
0.014
246938BC-WTG3
Solar/Wind Harmer
0.406
270491AE1-102 GEN2
Solar/Wind Harmer
1.468
965021AG1-366 GEN
Solar/Wind Harmer
3.735
270043AE2-236 GEN
Solar/Wind Harmer
7.125
24695305TIMB G C
Solar/Wind Harmer
0.934
971347AH1-153 GEN
Solar/Wind Harmer
5.488
270063AE2-323 C
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
48.343
971199AH1-059 GEN
Solar/Wind Harmer
2.255
270505AE1-170 C O1
Solar/Wind Harmer
11.228
945111AF1-176 GEN
Solar/Wind Harmer
8.665
964401AG1-302 GEN
Solar/Wind Harmer
0.002
270588AE1-091_GEN
Solar/Wind Harmer
8.236
274772LINCOLN ;3U
Adder
12.619
274752CRETE EC ;2U
Adder
12.279
274753CRETE EC ;3U
Adder
12.279
274724RIVER EC ;11
Adder
26.355
247642Z2-115 C
Solar/Wind Harmer
0.004
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
10.354
274814UNIV PK N;0U
Adder
7.488
274807UNIV PK N;3U
Adder
7.472
274811UNIV PK N;7U
Adder
7.423
970289AG2-191 GEN
Solar/Wind Harmer
1.133
274803UNIV PARK;6U
Adder
8.599
274826FISK ;BP
Adder
16.137
274887GEN-1.85
Solar/Wind Harmer
0.267
276843GEN-1.7
Solar/Wind Harmer
0.332
276806AD2-047 C O1
Solar/Wind Harmer
5.825
972038AH1-567 GEN2
Adder
0.538
970707AG2-453 GEN
Solar/Wind Harmer
33.528
972259AH1-714 GEN
Adder
28.051
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
43.287
274730ELWOOD EC;6P
Adder
24.024
274734ELWOOD EC;8P
Adder
24.024
274736ELWOOD EC;9P
Adder
24.024
274729ELWOOD EC;1P
Adder
24.024
970065AG2-057 GEN
Solar/Wind Harmer
1.014
943121AE2-341 GEN
Solar/Wind Harmer
16.972
943591AF1-030 GEN
Solar/Wind Harmer
11.286
253370AE2-315 SEC1
Adder
2.904
253371AE2-315 SEC2
Adder
2.747
24386205FR-12G C
Solar/Wind Harmer
0
970191AG2-125 GEN
Solar/Wind Harmer
2.597
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
15.132
274862TOP CROP ;2U
Solar/Wind Harmer
1.359
274682WAUKEGAN ;7U
Adder
25.826
276868AE1-113 GEN
Solar/Wind Harmer
1.991
274879MINONK ;1U
Solar/Wind Harmer
0.415
946031AF1-268 GEN
Solar/Wind Harmer
9.47
970825AG2-519 GEN
Solar/Wind Harmer
7.486
270004AE1-209 GEN
Solar/Wind Harmer
2.149
946671AF1-331 GEN
Solar/Wind Harmer
1.054
274855GSG-6 ;RU
Solar/Wind Harmer
0.361
274850MENDOTA H;RU
Solar/Wind Harmer
0.115
959091AF2-200 GEN
Solar/Wind Harmer
19.677
970571AG2-364 GEN
Solar/Wind Harmer
19.606
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
12.93
274767LEE CO EC;8U
Adder
12.777
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.321
965091AG1-374 GEN
Solar/Wind Harmer
28.713
959611AF2-252 GEN
Solar/Wind Harmer
3.19
253394AE2-221_GEN
Solar/Wind Harmer
0.001
965931AG1-462 GEN
Solar/Wind Harmer
23.963
971087AG2-675 GEN
Solar/Wind Harmer
5.012
971993AH1-541 GEN
Solar/Wind Harmer
4.285
24728505AND G1
Adder
5.071
970193AG2-126 GEN
Solar/Wind Harmer
13.784
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
11.737
270541AE2-072 C
Solar/Wind Harmer
0.001
957381AF2-032 GEN
Solar/Wind Harmer
2.038
25196608WSDLE5
Adder
10.619
25194608D.CRK4
Adder
2.025
25196008MFTGT1
Adder
1.61
23906502RICHG2&3
Adder
1.439
23906402RICHG1
Adder
1.437
237048AF1-022 C
Solar/Wind Helper
0.174
237046AF1-021 C
Solar/Wind Helper
0.304
964991AG1-363 GEN
Solar/Wind Helper
3.522
23562501BACKB
Solar/Wind Helper
0.847
235058AG1-386 C
Solar/Wind Helper
0.4
238127S14_GEN_2
Solar/Wind Helper
0.635
202652Y1-033 WT C
Solar/Wind Helper
0.501
942481AE2-261 GEN
Solar/Wind Harmer
16.491
CBM West 2LTFEXP_CBM-W2->PJM
CBM
124.415
NYPJM->LTFIMP_NY
CLTF
4.821
LGEELTFEXP_LGEE->PJM
CLTF
7.242
WECLTFEXP_WEC->PJM
CLTF
5.355
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.468
AG2-052LTFEXP_AG2-052->PJM
LTF
0.342
AH1-155LTFEXP_AH1-155->PJM
LTF
0.513
LAGNLTFEXP_LAGN->PJM
CLTF
14.301
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.305
TVALTFEXP_TVA->PJM
CLTF
6.29
CBM West 1LTFEXP_CBM-W1->PJM
CBM
183.968
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.5
MECLTFEXP_MEC->PJM
CLTF
20.741
SIGELTFEXP_SIGE->PJM
CLTF
0.579

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o ATSI_P7-1_TE-345-030_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
ATSI_P7-1_TE-345-030_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:100.26 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4152.93
MW Contribution:
37.73
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
ATSI_P7-1_TE-345-030_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:96.51 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:3997.33
MW Contribution:
32.62
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
15.769
270120AB2-067 GEN2
50/50
15.769
270160DARBY CT5
50/50
0.838
270161DARBY CT6
50/50
0.827
270466AD2-091
50/50
9.303
25326509SID D
50/50
1.962
270349AD2-093_GEN
Solar/Wind Harmer
6.996
270156DARBY CT1
50/50
0.855
270157DARBY CT2
50/50
0.853
270159DARBY CT4
50/50
0.841
270158DARBY CT3
50/50
0.839
270036AE2-216 BAT
50/50
10.234
270459AD2-067 GEN
Solar/Wind Harmer
16.44
961821AG1-024 GEN
Solar/Wind Harmer
16.692
241955AC1-078 GEN
Solar/Wind Harmer
12.841
241973AD2-163_GEN1
Solar/Wind Harmer
3.356
241974AD2-163_GEN2
Solar/Wind Harmer
3.356
945631AF1-228 GEN
Solar/Wind Harmer
7.764
270223U2-072_GEN1
Solar/Wind Harmer
3.264
270471AD2-092_GEN
Solar/Wind Harmer
6.996
270054AF2-122 C O1
Solar/Wind Harmer
6.002
946101AF1-275 GEN
Solar/Wind Harmer
2.774
253383AE2-342_GEN
Solar/Wind Harmer
1.515
942861AE2-305 GEN
Solar/Wind Harmer
12.851
270462AD2-086
Solar/Wind Harmer
11.128
938701AE1-092 GEN
Solar/Wind Harmer
32.666
253378AE2-206_GEN
Solar/Wind Harmer
5.191
246937BC-WTG2
Solar/Wind Harmer
5.449
270246TR4_N_V150
Solar/Wind Harmer
1.17
270247TR4_N_V136
Solar/Wind Harmer
1.17
247607V1-011 GEN
Solar/Wind Harmer
5.389
942801AE2-298 GEN
Solar/Wind Harmer
2.059
970349AG2-230 GEN
Solar/Wind Harmer
20.346
247620Y3-023
Adder
0.617
965681AG1-436 GEN
Solar/Wind Harmer
16.676
965791AG1-447 GEN
Solar/Wind Harmer
8.532
25326109MON D
Adder
1.754
961051AF2-396 GEN
Solar/Wind Harmer
21.131
961051AF2-396 GEN
Solar/Wind Harmer
9.828
270535AF1-215 GEN1
Solar/Wind Harmer
5.996
270536AF1-215 GEN2
Solar/Wind Harmer
5.996
270269AC2-059
Solar/Wind Harmer
12.313
944231AF1-091 GEN
Solar/Wind Harmer
23.698
942221AE2-234 GEN
Solar/Wind Harmer
4.606
944541AF1-119 GEN
Solar/Wind Harmer
5.48
960971AF2-388 GEN
Solar/Wind Harmer
14.305
945421AF1-207 GEN
Solar/Wind Harmer
18.355
957841AF2-078 GEN
Solar/Wind Harmer
7.901
25322209TAIT E
Adder
12.734
25322209TAIT E
Adder
12.447
274770LINCOLN ;1U
Adder
8.061
274771LINCOLN ;2U
Adder
8.061
270180AB1-006 GEN1
Solar/Wind Harmer
9.319
24697605MDL-3G C
Solar/Wind Harmer
4.776
24755605MDL-5G
Solar/Wind Harmer
3.124
24697905MDL-4G C
Solar/Wind Harmer
2.973
270181AB1-006 GEN2
Solar/Wind Harmer
0.927
270051AF1-062 GEN
50/50
19.36
270475AD2-096_GEN
50/50
11.209
961921AG1-034 GEN
Solar/Wind Harmer
25.037
962771AG1-126 GEN
Solar/Wind Harmer
61.099
970153AG2-106 GEN
Solar/Wind Harmer
26.642
270284AF1-227 GEN1
Solar/Wind Harmer
10.292
270287AF1-227 GEN3
Solar/Wind Harmer
3.807
942051AE2-217 GEN
Solar/Wind Harmer
30.068
942871AE2-306 GEN
Solar/Wind Harmer
1.499
270391AF1-285 GEN3
Solar/Wind Harmer
0.769
270518AE2-148 GEN
Solar/Wind Harmer
18.916
253325AC1-069 GEN
Solar/Wind Harmer
1.593
960801AF2-371 GEN
Solar/Wind Harmer
3.709
964871AG1-351 GEN
Solar/Wind Harmer
2.561
276820AF1-078_GEN
Solar/Wind Harmer
2.306
246938BC-WTG3
Solar/Wind Harmer
5.543
270491AE1-102 GEN2
Solar/Wind Harmer
1.811
965021AG1-366 GEN
Solar/Wind Harmer
3.212
270043AE2-236 GEN
Solar/Wind Harmer
7.533
24695305TIMB G C
Solar/Wind Harmer
4.562
958091AF2-103 GEN
Solar/Wind Harmer
0.22
971347AH1-153 GEN
Solar/Wind Harmer
6.782
270063AE2-323 C
Solar/Wind Harmer
2.966
247643Z2-116 C
Solar/Wind Harmer
0.093
944531AF1-118 GEN
Solar/Wind Harmer
46.834
270505AE1-170 C O1
Solar/Wind Harmer
20.011
945111AF1-176 GEN
Solar/Wind Harmer
7.543
24441505OLIV SLR
Solar/Wind Harmer
0.178
270044AE2-322 C
Solar/Wind Harmer
1.744
964401AG1-302 GEN
Solar/Wind Harmer
11.955
270588AE1-091_GEN
Solar/Wind Harmer
14.355
960071AF2-298 GEN
Solar/Wind Harmer
1.969
274772LINCOLN ;3U
Adder
8.061
247642Z2-115 C
Solar/Wind Harmer
0.083
972231SS25-0005
Solar/Wind Harmer
12.318
972181SS23-001
Solar/Wind Harmer
7.699
274752CRETE EC ;2U
Adder
6.344
274753CRETE EC ;3U
Adder
6.344
274724RIVER EC ;11
Adder
22.955
24690905MDL-1G C
Solar/Wind Harmer
10.402
970781AG2-491 GEN
Solar/Wind Harmer
12.958
276164X3-005 C
Solar/Wind Harmer
0.908
274814UNIV PK N;0U
Adder
6.527
274807UNIV PK N;3U
Adder
6.513
274811UNIV PK N;7U
Adder
6.471
965461AG1-414 GEN
Solar/Wind Harmer
2.929
970289AG2-191 GEN
Solar/Wind Harmer
0.991
253303V4-073 C
Solar/Wind Harmer
0.149
253370AE2-315 SEC1
Adder
2.58
253371AE2-315 SEC2
Adder
2.44
274803UNIV PARK;6U
Adder
7.502
274826FISK ;BP
Adder
14.078
274887GEN-1.85
Solar/Wind Harmer
6.849
276772AC2-154 GEN
Solar/Wind Harmer
3.588
276843GEN-1.7
Solar/Wind Harmer
0.737
276806AD2-047 C O1
Solar/Wind Harmer
13.753
972038AH1-567 GEN2
Adder
0.469
972259AH1-714 GEN
Adder
24.478
274676JOLIET 29;8U
Adder
37.812
274729ELWOOD EC;1P
Adder
20.991
274730ELWOOD EC;6P
Adder
20.991
274734ELWOOD EC;8P
Adder
20.991
274736ELWOOD EC;9P
Adder
20.991
274682WAUKEGAN ;7U
Adder
22.632
274760LEE CO EC;1U
Adder
11.403
274767LEE CO EC;8U
Adder
11.269
24728505AND G1
Adder
4.559
25196608WSDLE5
Adder
9.804
23906502RICHG2&3
Adder
1.375
23906402RICHG1
Adder
1.374
25194608D.CRK4
Adder
1.872
25196008MFTGT1
Adder
1.498
235058AG1-386 C
Solar/Wind Helper
0.454
237048AF1-022 C
Solar/Wind Helper
0.176
237046AF1-021 C
Solar/Wind Helper
0.314
202652Y1-033 WT C
Solar/Wind Helper
0.507
270224U2-072_GEN2
Solar/Wind Harmer
3.264
270227U2-072_GEN3
Solar/Wind Harmer
3.264
270228U2-072_GEN4
Solar/Wind Harmer
3.264
270231U2-072_GEN5
Solar/Wind Harmer
3.264
270578AF1-285 GEN2
Solar/Wind Harmer
0.769
943861AF1-054 GEN
Solar/Wind Harmer
6.343
943851AF1-053 GEN
Solar/Wind Harmer
3.065
270302AB2-170 GEN
Solar/Wind Harmer
13.397
253338AC1-165 GEN
Solar/Wind Harmer
1.652
253343AC1-166 GEN
Solar/Wind Harmer
1.652
241972AD1-140 GEN
Solar/Wind Harmer
6.448
270432AC2-029 GEN
Solar/Wind Harmer
9.905
957201AF2-014 GEN
Solar/Wind Harmer
6.318
270435AC2-044 GEN
Solar/Wind Harmer
2.786
959331AF2-224 GEN
Solar/Wind Harmer
13.812
247521TR3_G114
Solar/Wind Harmer
4.624
270191TR4_S_V150
Solar/Wind Harmer
4.126
965051AG1-369 GEN
Solar/Wind Harmer
6.87
965041AG1-368 GEN
Solar/Wind Harmer
13.691
270071AF1-092 GEN
Solar/Wind Harmer
20.508
270007AE1-245 C
Solar/Wind Harmer
7.361
970031AG2-029 GEN
Solar/Wind Harmer
33.755
971771AH1-392 GEN
Solar/Wind Harmer
12.042
963791AG1-232 GEN
Solar/Wind Harmer
18.061
270526AF1-158 GEN
Solar/Wind Harmer
6.052
960681AF2-359 GEN
Solar/Wind Harmer
5.041
24729505KEY G4
Adder
8.63
270404AC1-167 GEN
Solar/Wind Harmer
1.437
944161AF1-084 GEN
Solar/Wind Harmer
2.932
958391AF2-133 GEN
Solar/Wind Harmer
11.935
959141AF2-205 GEN
Solar/Wind Harmer
7.947
958711AF2-162 GEN
Solar/Wind Harmer
1.324
274775LINCOLN ;6U
Adder
8.061
274776LINCOLN ;7U
Adder
8.061
274777LINCOLN ;8U
Adder
8.061
946581AF1-322 GEN
Solar/Wind Harmer
13.258
24691005MDL-2G C
Solar/Wind Harmer
4.791
970289AG2-191 GEN
Solar/Wind Harmer
2.454
971549AH1-272 GEN
Solar/Wind Harmer
23.856
945581AF1-223 GEN
Solar/Wind Harmer
5.843
253372AE2-315 SEC3
Adder
2.44
253372AE2-315 SEC3
Adder
2.44
972037AH1-567 GEN1
Adder
0.235
274827FISK ;RP
Adder
9.977
960591AF2-350 GEN
Solar/Wind Harmer
12.856
274800UNIV PARK;3U
Adder
7.493
274801UNIV PARK;4U
Adder
7.493
972228AH1-698 GEN2
Adder
4.758
972227AH1-698 GEN1
Adder
3.351
25306009OHH W.
Adder
3.692
274687WILL CNTY;4U
Adder
35.747
274687WILL CNTY;4U
Adder
35.747
274675JOLIET 29;7U
Adder
39.213
274675JOLIET 29;7U
Adder
37.813
274728ELWOOD EC;5P
Adder
20.991
274731ELWOOD EC;2P
Adder
20.991
274733ELWOOD EC;3P
Adder
20.991
274735ELWOOD EC;4P
Adder
20.991
274744AC1-111 GEN8
Adder
7.091
274746AC1-111 G10
Adder
7.091
274823ROCKFORD ;21
Adder
24.111
972267AH1-718 GEN
Adder
5.076
25196408WSDLE3
Adder
10.092
25196108MFTGT2
Adder
1.705
25196108MFTGT2
Adder
1.583
241985AE1-237 GEN
Solar/Wind Helper
0.248
241982AE2-343 S C
Solar/Wind Helper
0.222
241997AF1-093 GEN
Solar/Wind Helper
0.252
23652301WDPWR_K20
Solar/Wind Helper
0.135
23750501ELLIOTTS
Solar/Wind Helper
0.602
203846AF2-130 C
Solar/Wind Helper
0.426
203955AF1-039 C O1
Solar/Wind Helper
0.334
20089126CSLMN_L13
Solar/Wind Helper
0.536
20089226LOOKOUT
Solar/Wind Helper
0.534
20088926STNY CRK
Solar/Wind Helper
0.738
274805UNIV PK N;1U
Adder
6.485
274808UNIV PK N;4U
Adder
6.442
970291AG2-192 GEN
Solar/Wind Harmer
1.679
970291AG2-192 GEN
Solar/Wind Harmer
0.541
253370AE2-315 SEC1
Adder
2.58
274888KELLY CRK;1U
Solar/Wind Harmer
7.586
276776AD2-060 GEN
Solar/Wind Harmer
0.538
958011AF2-095 GEN
Solar/Wind Harmer
18.512
970941AG2-585 GEN
Solar/Wind Harmer
7.071
253349AC2-067 GEN
Solar/Wind Harmer
2.612
253400AC2-068 GEN
Solar/Wind Harmer
1.051
274674JOLIET 9 ;6U
Adder
19.662
247621Y3-024
Adder
0.307
274696ROCKY RD ;4P
Adder
14.362
274695ROCKY RD ;2P
Adder
14.031
274693ROCKY RD ;1P
Adder
13.893
274697ROCKY RD ;3P
Adder
3.812
274683WAUKEGAN ;8U
Adder
26.517
274683WAUKEGAN ;8U
Adder
22.352
972235AH1-702 GEN1
Adder
3.115
972236AH1-702 GEN2
Adder
2.709
274764LEE CO EC;5U
Adder
11.43
274765LEE CO EC;6U
Adder
11.43
274762LEE CO EC;3U
Adder
11.403
274763LEE CO EC;4U
Adder
11.296
25194408D.CRK1
Adder
8.612
25194508D.CRK3
Adder
1.61
254304AE2-114 C
Solar/Wind Helper
0.219
254305AE2-115 C
Solar/Wind Helper
0.219
241967AE2-285_GEN
Solar/Wind Helper
0.634
241801AE1-079 GEN
Solar/Wind Helper
0.248
962101AG1-054 GEN
Solar/Wind Helper
0.64
237043AE2-125 C
Solar/Wind Helper
0.169
946071AF1-272 GEN
Solar/Wind Helper
2.473
23585401KL_K28_T16
Solar/Wind Helper
1.134
23751201ROTHROCK
Solar/Wind Helper
0.663
20083426SW_E13_K22
Solar/Wind Helper
0.05
203835AF1-098 GEN
Solar/Wind Helper
1.767
946381AF1-302 GEN
Solar/Wind Helper
0.204
23562501BACKB
Solar/Wind Helper
0.81
962511AG1-100 GEN
Solar/Wind Helper
0.445
964991AG1-363 GEN
Solar/Wind Helper
3.324
270166AC1-044 GEN3
50/50
15.769
962761AG1-125 GEN
Solar/Wind Harmer
61.099
970149AG2-104 GEN
Solar/Wind Harmer
37.729
970155AG2-107 GEN
Solar/Wind Harmer
26.642
270520AE2-214 GEN
Solar/Wind Harmer
11.097
270286AF1-227 GEN2
Solar/Wind Harmer
3.807
270391AF1-285 GEN3
Solar/Wind Harmer
1.999
270578AF1-285 GEN2
Solar/Wind Harmer
1.999
270317AD1-130_GEN
Solar/Wind Harmer
5.121
270485AE1-090_GEN
Solar/Wind Harmer
0.968
253333AC1-068 GEN
Solar/Wind Harmer
1.593
971995AH1-542 GEN
Solar/Wind Harmer
16.172
246936BC-WTG1
Solar/Wind Harmer
5.449
270489AE1-102 GEN1
Solar/Wind Harmer
1.811
965421AG1-410 GEN
Solar/Wind Harmer
41.76
965011AG1-365 GEN
Solar/Wind Harmer
13.812
270216AD2-079_GEN
Solar/Wind Harmer
0.811
270258AD1-119 GEN
Solar/Wind Harmer
2.722
24639705ELKHART HY
Adder
0.206
945111AF1-176 GEN
Solar/Wind Harmer
23.801
957891AF2-083 GEN
Solar/Wind Harmer
20.009
270449AD2-020 GEN
Solar/Wind Harmer
3.725
943021AE2-325 GEN
Solar/Wind Harmer
4.842
970373AG2-245 GEN
Solar/Wind Harmer
27.846
270055AF2-134 C O1
Solar/Wind Harmer
3.997
270273AD2-016 GEN
Solar/Wind Harmer
3.511
24441205WTRV SLR C
Solar/Wind Harmer
0.178
958381AF2-132 GEN
Solar/Wind Harmer
11.955
964861AG1-349 GEN
Solar/Wind Harmer
10.357
270297AD1-101 GEN
Solar/Wind Harmer
2.676
971917AH1-482 GEN
Solar/Wind Harmer
11.949
940581AE2-045 GEN
Solar/Wind Harmer
13.384
971605AH1-302 GEN
Solar/Wind Harmer
11.444
965651AG1-433 GEN
Solar/Wind Harmer
7.153
25326309TAIT D
Adder
1.431
958861AF2-177 GEN
Solar/Wind Harmer
14.228
972207SS24-0001
Solar/Wind Harmer
28.659
274773LINCOLN ;4U
Adder
8.061
274774LINCOLN ;5U
Adder
8.061
270024AE2-089 GEN
Solar/Wind Harmer
6.086
274751CRETE EC ;1U
Adder
6.344
274754CRETE EC ;4U
Adder
6.344
274723RIVER EC ;12
Adder
23.228
24791305MDL-5G
Solar/Wind Harmer
3.124
274812UNIV PK N;8U
Adder
6.471
945371AF1-202 GEN
Solar/Wind Harmer
8.988
253370AE2-315 SEC1
Adder
2.58
253371AE2-315 SEC2
Adder
2.44
274802UNIV PARK;5U
Adder
7.502
274676JOLIET 29;8U
Adder
39.213
274732ELWOOD EC;7P
Adder
20.991
274674JOLIET 9 ;6U
Adder
19.662
274745AC1-111 GEN9
Adder
7.091
274682WAUKEGAN ;7U
Adder
22.632
274828WAUKEGAN ;BP
Adder
13.9
274822ROCKFORD ;11
Adder
24.287
274761LEE CO EC;2U
Adder
11.403
274766LEE CO EC;7U
Adder
11.269
24728605AND G2
Adder
4.559
23906502RICHG2&3
Adder
1.375
25194608D.CRK4
Adder
1.872
25196008MFTGT1
Adder
1.547
25196808ZIMRHP
Adder
84.175
23920202STRYCT
Adder
1.48
970091AG2-072 GEN
Adder
42.348
254303AC2-168 GEN
Solar/Wind Helper
0.157
241966AE1-183 GEN
Solar/Wind Helper
0.252
238185AF2-356 C
Solar/Wind Helper
1.95
961971AG1-040 GEN
Solar/Wind Helper
0.445
203830AF1-094 GEN
Solar/Wind Helper
0.445
203979AG1-198 GEN
Solar/Wind Helper
0.267
20089026BF_G21_K23
Solar/Wind Helper
0.424
203947AF1-006 C
Solar/Wind Helper
0.484
20084626FORWARD
Solar/Wind Helper
0.322
270594AE1-207 GEN
Solar/Wind Harmer
5.091
270032AE2-172
Solar/Wind Harmer
1.743
CPLELTFEXP_CPLE->PJM
CLTF
0.317
CBM West 2LTFEXP_CBM-W2->PJM
CBM
119.936
NYPJM->LTFIMP_NY
CLTF
4.743
LGEELTFEXP_LGEE->PJM
CLTF
6.936
WECLTFEXP_WEC->PJM
CLTF
4.716
AG2-052LTFEXP_AG2-052->PJM
LTF
0.299
AH1-155LTFEXP_AH1-155->PJM
LTF
0.449
LAGNLTFEXP_LAGN->PJM
CLTF
14.706
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.029
TVALTFEXP_TVA->PJM
CLTF
6.774
CBM West 1LTFEXP_CBM-W1->PJM
CBM
168.69
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.689
MECLTFEXP_MEC->PJM
CLTF
18.731
SIGELTFEXP_SIGE->PJM
CLTF
0.544

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o ATSI_P7-1_TE-345-031_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
ATSI_P7-1_TE-345-031_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:100.15 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4148.28
MW Contribution:
37.73
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
ATSI_P7-1_TE-345-031_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:96.38 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:3992.14
MW Contribution:
32.62
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
15.77
270120AB2-067 GEN2
50/50
15.77
270160DARBY CT5
50/50
0.838
270161DARBY CT6
50/50
0.827
270466AD2-091
50/50
9.305
25326509SID D
50/50
1.962
270349AD2-093_GEN
Solar/Wind Harmer
6.997
270471AD2-092_GEN
Solar/Wind Harmer
6.997
270054AF2-122 C O1
Solar/Wind Harmer
6.003
946101AF1-275 GEN
Solar/Wind Harmer
2.775
253383AE2-342_GEN
Solar/Wind Harmer
1.515
942861AE2-305 GEN
Solar/Wind Harmer
12.854
270462AD2-086
Solar/Wind Harmer
11.13
938701AE1-092 GEN
Solar/Wind Harmer
32.673
253378AE2-206_GEN
Solar/Wind Harmer
5.193
246937BC-WTG2
Solar/Wind Harmer
5.451
270246TR4_N_V150
Solar/Wind Harmer
1.17
270247TR4_N_V136
Solar/Wind Harmer
1.17
247607V1-011 GEN
Solar/Wind Harmer
5.39
942801AE2-298 GEN
Solar/Wind Harmer
2.06
970349AG2-230 GEN
Solar/Wind Harmer
20.351
247620Y3-023
Adder
0.617
965681AG1-436 GEN
Solar/Wind Harmer
16.68
965791AG1-447 GEN
Solar/Wind Harmer
8.534
25326109MON D
Adder
1.754
961051AF2-396 GEN
Solar/Wind Harmer
21.136
961051AF2-396 GEN
Solar/Wind Harmer
9.831
270535AF1-215 GEN1
Solar/Wind Harmer
5.998
270536AF1-215 GEN2
Solar/Wind Harmer
5.998
270269AC2-059
Solar/Wind Harmer
12.316
944231AF1-091 GEN
Solar/Wind Harmer
23.704
942221AE2-234 GEN
Solar/Wind Harmer
4.607
944541AF1-119 GEN
Solar/Wind Harmer
5.481
960971AF2-388 GEN
Solar/Wind Harmer
14.309
945421AF1-207 GEN
Solar/Wind Harmer
18.359
957841AF2-078 GEN
Solar/Wind Harmer
7.903
25322209TAIT E
Adder
12.737
25322209TAIT E
Adder
12.451
274770LINCOLN ;1U
Adder
8.063
274771LINCOLN ;2U
Adder
8.063
270180AB1-006 GEN1
Solar/Wind Harmer
9.321
24697605MDL-3G C
Solar/Wind Harmer
4.778
24755605MDL-5G
Solar/Wind Harmer
3.125
24697905MDL-4G C
Solar/Wind Harmer
2.974
270181AB1-006 GEN2
Solar/Wind Harmer
0.927
274805UNIV PK N;1U
Adder
6.486
274808UNIV PK N;4U
Adder
6.444
970291AG2-192 GEN
Solar/Wind Harmer
1.68
970291AG2-192 GEN
Solar/Wind Harmer
0.541
253370AE2-315 SEC1
Adder
2.581
274888KELLY CRK;1U
Solar/Wind Harmer
7.588
276776AD2-060 GEN
Solar/Wind Harmer
0.538
958011AF2-095 GEN
Solar/Wind Harmer
18.517
970941AG2-585 GEN
Solar/Wind Harmer
7.072
253349AC2-067 GEN
Solar/Wind Harmer
2.613
253400AC2-068 GEN
Solar/Wind Harmer
1.051
274674JOLIET 9 ;6U
Adder
19.667
247621Y3-024
Adder
0.307
274696ROCKY RD ;4P
Adder
14.366
274695ROCKY RD ;2P
Adder
14.034
274693ROCKY RD ;1P
Adder
13.896
274697ROCKY RD ;3P
Adder
3.812
274683WAUKEGAN ;8U
Adder
26.524
274683WAUKEGAN ;8U
Adder
22.358
972235AH1-702 GEN1
Adder
3.116
972236AH1-702 GEN2
Adder
2.709
274764LEE CO EC;5U
Adder
11.433
274765LEE CO EC;6U
Adder
11.433
274762LEE CO EC;3U
Adder
11.406
270156DARBY CT1
50/50
0.855
270157DARBY CT2
50/50
0.853
270159DARBY CT4
50/50
0.841
270158DARBY CT3
50/50
0.839
270036AE2-216 BAT
50/50
10.236
270459AD2-067 GEN
Solar/Wind Harmer
16.443
961821AG1-024 GEN
Solar/Wind Harmer
16.694
241955AC1-078 GEN
Solar/Wind Harmer
12.844
241973AD2-163_GEN1
Solar/Wind Harmer
3.356
241974AD2-163_GEN2
Solar/Wind Harmer
3.356
945631AF1-228 GEN
Solar/Wind Harmer
7.765
270223U2-072_GEN1
Solar/Wind Harmer
3.264
270224U2-072_GEN2
Solar/Wind Harmer
3.264
270227U2-072_GEN3
Solar/Wind Harmer
3.264
270228U2-072_GEN4
Solar/Wind Harmer
3.264
270231U2-072_GEN5
Solar/Wind Harmer
3.264
270578AF1-285 GEN2
Solar/Wind Harmer
0.769
943861AF1-054 GEN
Solar/Wind Harmer
6.345
943851AF1-053 GEN
Solar/Wind Harmer
3.066
270302AB2-170 GEN
Solar/Wind Harmer
13.399
253338AC1-165 GEN
Solar/Wind Harmer
1.653
253343AC1-166 GEN
Solar/Wind Harmer
1.653
241972AD1-140 GEN
Solar/Wind Harmer
6.45
270432AC2-029 GEN
Solar/Wind Harmer
9.907
957201AF2-014 GEN
Solar/Wind Harmer
6.32
270435AC2-044 GEN
Solar/Wind Harmer
2.787
959331AF2-224 GEN
Solar/Wind Harmer
13.815
247521TR3_G114
Solar/Wind Harmer
4.625
270191TR4_S_V150
Solar/Wind Harmer
4.127
965051AG1-369 GEN
Solar/Wind Harmer
6.871
965041AG1-368 GEN
Solar/Wind Harmer
13.694
270071AF1-092 GEN
Solar/Wind Harmer
20.513
270007AE1-245 C
Solar/Wind Harmer
7.363
970031AG2-029 GEN
Solar/Wind Harmer
33.763
971771AH1-392 GEN
Solar/Wind Harmer
12.045
963791AG1-232 GEN
Solar/Wind Harmer
18.065
270526AF1-158 GEN
Solar/Wind Harmer
6.053
960681AF2-359 GEN
Solar/Wind Harmer
5.042
24729505KEY G4
Adder
8.632
270404AC1-167 GEN
Solar/Wind Harmer
1.438
944161AF1-084 GEN
Solar/Wind Harmer
2.932
958391AF2-133 GEN
Solar/Wind Harmer
11.938
959141AF2-205 GEN
Solar/Wind Harmer
7.949
958711AF2-162 GEN
Solar/Wind Harmer
1.324
274775LINCOLN ;6U
Adder
8.063
274776LINCOLN ;7U
Adder
8.063
274777LINCOLN ;8U
Adder
8.063
946581AF1-322 GEN
Solar/Wind Harmer
13.262
24691005MDL-2G C
Solar/Wind Harmer
4.793
970289AG2-191 GEN
Solar/Wind Harmer
2.455
971549AH1-272 GEN
Solar/Wind Harmer
23.862
945581AF1-223 GEN
Solar/Wind Harmer
5.844
253372AE2-315 SEC3
Adder
2.441
253372AE2-315 SEC3
Adder
2.441
972037AH1-567 GEN1
Adder
0.236
274827FISK ;RP
Adder
9.979
960591AF2-350 GEN
Solar/Wind Harmer
12.859
274800UNIV PARK;3U
Adder
7.495
274801UNIV PARK;4U
Adder
7.495
972228AH1-698 GEN2
Adder
4.76
972227AH1-698 GEN1
Adder
3.351
25306009OHH W.
Adder
3.693
274687WILL CNTY;4U
Adder
35.756
274687WILL CNTY;4U
Adder
35.756
274675JOLIET 29;7U
Adder
39.223
274675JOLIET 29;7U
Adder
37.822
274728ELWOOD EC;5P
Adder
20.997
274731ELWOOD EC;2P
Adder
20.997
274733ELWOOD EC;3P
Adder
20.997
274735ELWOOD EC;4P
Adder
20.997
274744AC1-111 GEN8
Adder
7.092
274746AC1-111 G10
Adder
7.092
274823ROCKFORD ;21
Adder
24.117
972267AH1-718 GEN
Adder
5.077
25196408WSDLE3
Adder
10.095
25196108MFTGT2
Adder
1.705
25196108MFTGT2
Adder
1.584
241985AE1-237 GEN
Solar/Wind Helper
0.247
241982AE2-343 S C
Solar/Wind Helper
0.222
241997AF1-093 GEN
Solar/Wind Helper
0.252
23652301WDPWR_K20
Solar/Wind Helper
0.134
274763LEE CO EC;4U
Adder
11.299
25194408D.CRK1
Adder
8.615
25194508D.CRK3
Adder
1.611
254304AE2-114 C
Solar/Wind Helper
0.219
254305AE2-115 C
Solar/Wind Helper
0.219
241967AE2-285_GEN
Solar/Wind Helper
0.634
241801AE1-079 GEN
Solar/Wind Helper
0.248
962101AG1-054 GEN
Solar/Wind Helper
0.64
237043AE2-125 C
Solar/Wind Helper
0.169
946071AF1-272 GEN
Solar/Wind Helper
2.472
23585401KL_K28_T16
Solar/Wind Helper
1.134
23751201ROTHROCK
Solar/Wind Helper
0.662
20083426SW_E13_K22
Solar/Wind Helper
0.05
203835AF1-098 GEN
Solar/Wind Helper
1.766
946381AF1-302 GEN
Solar/Wind Helper
0.204
270051AF1-062 GEN
50/50
19.363
270475AD2-096_GEN
50/50
11.21
961921AG1-034 GEN
Solar/Wind Harmer
25.042
962771AG1-126 GEN
Solar/Wind Harmer
61.109
970153AG2-106 GEN
Solar/Wind Harmer
26.647
270284AF1-227 GEN1
Solar/Wind Harmer
10.294
270287AF1-227 GEN3
Solar/Wind Harmer
3.807
942051AE2-217 GEN
Solar/Wind Harmer
30.074
942871AE2-306 GEN
Solar/Wind Harmer
1.499
270391AF1-285 GEN3
Solar/Wind Harmer
0.769
270518AE2-148 GEN
Solar/Wind Harmer
18.92
253325AC1-069 GEN
Solar/Wind Harmer
1.594
960801AF2-371 GEN
Solar/Wind Harmer
3.709
964871AG1-351 GEN
Solar/Wind Harmer
2.561
276820AF1-078_GEN
Solar/Wind Harmer
2.307
246938BC-WTG3
Solar/Wind Harmer
5.545
270491AE1-102 GEN2
Solar/Wind Harmer
1.811
965021AG1-366 GEN
Solar/Wind Harmer
3.213
270043AE2-236 GEN
Solar/Wind Harmer
7.535
24695305TIMB G C
Solar/Wind Harmer
4.564
958091AF2-103 GEN
Solar/Wind Harmer
0.22
971347AH1-153 GEN
Solar/Wind Harmer
6.784
270063AE2-323 C
Solar/Wind Harmer
2.967
247643Z2-116 C
Solar/Wind Harmer
0.093
944531AF1-118 GEN
Solar/Wind Harmer
46.845
270505AE1-170 C O1
Solar/Wind Harmer
20.016
945111AF1-176 GEN
Solar/Wind Harmer
7.545
24441505OLIV SLR
Solar/Wind Harmer
0.178
270044AE2-322 C
Solar/Wind Harmer
1.744
964401AG1-302 GEN
Solar/Wind Harmer
11.958
270588AE1-091_GEN
Solar/Wind Harmer
14.359
960071AF2-298 GEN
Solar/Wind Harmer
1.969
274772LINCOLN ;3U
Adder
8.063
247642Z2-115 C
Solar/Wind Harmer
0.083
972231SS25-0005
Solar/Wind Harmer
12.321
972181SS23-001
Solar/Wind Harmer
7.701
274752CRETE EC ;2U
Adder
6.346
274753CRETE EC ;3U
Adder
6.346
274724RIVER EC ;11
Adder
22.961
24690905MDL-1G C
Solar/Wind Harmer
10.405
970781AG2-491 GEN
Solar/Wind Harmer
12.961
276164X3-005 C
Solar/Wind Harmer
0.908
274814UNIV PK N;0U
Adder
6.529
274807UNIV PK N;3U
Adder
6.515
274811UNIV PK N;7U
Adder
6.472
965461AG1-414 GEN
Solar/Wind Harmer
2.93
970289AG2-191 GEN
Solar/Wind Harmer
0.992
253303V4-073 C
Solar/Wind Harmer
0.149
253370AE2-315 SEC1
Adder
2.581
253371AE2-315 SEC2
Adder
2.441
274803UNIV PARK;6U
Adder
7.503
274826FISK ;BP
Adder
14.081
274887GEN-1.85
Solar/Wind Harmer
6.851
276772AC2-154 GEN
Solar/Wind Harmer
3.589
276843GEN-1.7
Solar/Wind Harmer
0.737
276806AD2-047 C O1
Solar/Wind Harmer
13.756
972038AH1-567 GEN2
Adder
0.469
972259AH1-714 GEN
Adder
24.485
274676JOLIET 29;8U
Adder
37.822
274729ELWOOD EC;1P
Adder
20.997
274730ELWOOD EC;6P
Adder
20.997
274734ELWOOD EC;8P
Adder
20.997
274736ELWOOD EC;9P
Adder
20.997
274682WAUKEGAN ;7U
Adder
22.638
274760LEE CO EC;1U
Adder
11.406
274767LEE CO EC;8U
Adder
11.272
24728505AND G1
Adder
4.56
25196608WSDLE5
Adder
9.806
23906502RICHG2&3
Adder
1.375
23906402RICHG1
Adder
1.375
25194608D.CRK4
Adder
1.873
25196008MFTGT1
Adder
1.498
235058AG1-386 C
Solar/Wind Helper
0.454
237048AF1-022 C
Solar/Wind Helper
0.176
237046AF1-021 C
Solar/Wind Helper
0.314
202652Y1-033 WT C
Solar/Wind Helper
0.506
23562501BACKB
Solar/Wind Helper
0.809
962511AG1-100 GEN
Solar/Wind Helper
0.444
964991AG1-363 GEN
Solar/Wind Helper
3.323
23750501ELLIOTTS
Solar/Wind Helper
0.601
203846AF2-130 C
Solar/Wind Helper
0.426
203955AF1-039 C O1
Solar/Wind Helper
0.334
20089126CSLMN_L13
Solar/Wind Helper
0.536
20089226LOOKOUT
Solar/Wind Helper
0.534
20088926STNY CRK
Solar/Wind Helper
0.738
270166AC1-044 GEN3
50/50
15.77
962761AG1-125 GEN
Solar/Wind Harmer
61.109
970149AG2-104 GEN
Solar/Wind Harmer
37.735
970155AG2-107 GEN
Solar/Wind Harmer
26.647
270520AE2-214 GEN
Solar/Wind Harmer
11.099
270286AF1-227 GEN2
Solar/Wind Harmer
3.807
270391AF1-285 GEN3
Solar/Wind Harmer
1.999
270578AF1-285 GEN2
Solar/Wind Harmer
1.999
270317AD1-130_GEN
Solar/Wind Harmer
5.122
270485AE1-090_GEN
Solar/Wind Harmer
0.968
253333AC1-068 GEN
Solar/Wind Harmer
1.594
971995AH1-542 GEN
Solar/Wind Harmer
16.176
246936BC-WTG1
Solar/Wind Harmer
5.451
270489AE1-102 GEN1
Solar/Wind Harmer
1.811
965421AG1-410 GEN
Solar/Wind Harmer
41.769
965011AG1-365 GEN
Solar/Wind Harmer
13.815
270216AD2-079_GEN
Solar/Wind Harmer
0.811
270258AD1-119 GEN
Solar/Wind Harmer
2.723
24639705ELKHART HY
Adder
0.206
945111AF1-176 GEN
Solar/Wind Harmer
23.807
957891AF2-083 GEN
Solar/Wind Harmer
20.013
270449AD2-020 GEN
Solar/Wind Harmer
3.726
943021AE2-325 GEN
Solar/Wind Harmer
4.844
970373AG2-245 GEN
Solar/Wind Harmer
27.853
270055AF2-134 C O1
Solar/Wind Harmer
3.998
270273AD2-016 GEN
Solar/Wind Harmer
3.512
24441205WTRV SLR C
Solar/Wind Harmer
0.178
958381AF2-132 GEN
Solar/Wind Harmer
11.958
964861AG1-349 GEN
Solar/Wind Harmer
10.359
971917AH1-482 GEN
Solar/Wind Harmer
11.952
270297AD1-101 GEN
Solar/Wind Harmer
2.676
940581AE2-045 GEN
Solar/Wind Harmer
13.387
971605AH1-302 GEN
Solar/Wind Harmer
11.446
965651AG1-433 GEN
Solar/Wind Harmer
7.154
25326309TAIT D
Adder
1.432
958861AF2-177 GEN
Solar/Wind Harmer
14.232
972207SS24-0001
Solar/Wind Harmer
28.666
274773LINCOLN ;4U
Adder
8.063
274774LINCOLN ;5U
Adder
8.063
270024AE2-089 GEN
Solar/Wind Harmer
6.087
274751CRETE EC ;1U
Adder
6.346
274754CRETE EC ;4U
Adder
6.346
274723RIVER EC ;12
Adder
23.234
24791305MDL-5G
Solar/Wind Harmer
3.125
274812UNIV PK N;8U
Adder
6.472
945371AF1-202 GEN
Solar/Wind Harmer
8.99
253370AE2-315 SEC1
Adder
2.581
253371AE2-315 SEC2
Adder
2.441
274802UNIV PARK;5U
Adder
7.503
274676JOLIET 29;8U
Adder
39.223
274732ELWOOD EC;7P
Adder
20.997
274674JOLIET 9 ;6U
Adder
19.667
274745AC1-111 GEN9
Adder
7.092
274682WAUKEGAN ;7U
Adder
22.638
274828WAUKEGAN ;BP
Adder
13.903
274822ROCKFORD ;11
Adder
24.293
274761LEE CO EC;2U
Adder
11.406
274766LEE CO EC;7U
Adder
11.272
24728605AND G2
Adder
4.56
23906502RICHG2&3
Adder
1.375
25194608D.CRK4
Adder
1.873
25196008MFTGT1
Adder
1.547
25196808ZIMRHP
Adder
84.199
23920202STRYCT
Adder
1.481
970091AG2-072 GEN
Adder
42.361
254303AC2-168 GEN
Solar/Wind Helper
0.157
241966AE1-183 GEN
Solar/Wind Helper
0.252
238185AF2-356 C
Solar/Wind Helper
1.949
961971AG1-040 GEN
Solar/Wind Helper
0.445
203830AF1-094 GEN
Solar/Wind Helper
0.445
203979AG1-198 GEN
Solar/Wind Helper
0.267
20089026BF_G21_K23
Solar/Wind Helper
0.424
203947AF1-006 C
Solar/Wind Helper
0.484
20084626FORWARD
Solar/Wind Helper
0.322
270594AE1-207 GEN
Solar/Wind Harmer
5.092
270032AE2-172
Solar/Wind Harmer
1.744
CPLELTFEXP_CPLE->PJM
CLTF
0.32
CBM West 2LTFEXP_CBM-W2->PJM
CBM
119.979
NYPJM->LTFIMP_NY
CLTF
4.741
LGEELTFEXP_LGEE->PJM
CLTF
6.938
WECLTFEXP_WEC->PJM
CLTF
4.717
AG2-052LTFEXP_AG2-052->PJM
LTF
0.299
AH1-155LTFEXP_AH1-155->PJM
LTF
0.449
LAGNLTFEXP_LAGN->PJM
CLTF
14.713
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.039
TVALTFEXP_TVA->PJM
CLTF
6.778
CBM West 1LTFEXP_CBM-W1->PJM
CBM
168.737
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.702
MECLTFEXP_MEC->PJM
CLTF
18.736
SIGELTFEXP_SIGE->PJM
CLTF
0.544

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AEP_P4_#ADKINS AG1125_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#ADKINS AG1125_SRT-A_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.63 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:4782.69
MW Contribution:
68.34
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
270102X2-052 ST
50/50
2.435
270100X2-052 CT1
50/50
2.25
270101X2-052 CT2
50/50
2.25
24643105BUCHANAN
50/50
0.019
247620Y3-023
50/50
0.727
270349AD2-093_GEN
Solar/Wind Harmer
6.24
270471AD2-092_GEN
Solar/Wind Harmer
6.24
970349AG2-230 GEN
Solar/Wind Harmer
23.509
965681AG1-436 GEN
Solar/Wind Harmer
18.941
965791AG1-447 GEN
Solar/Wind Harmer
9.691
961051AF2-396 GEN
Solar/Wind Harmer
23.569
961051AF2-396 GEN
Solar/Wind Harmer
10.962
24344105CKG2
50/50
12.076
270143AC1-141 CT2_
50/50
3.606
24639705ELKHART HY
50/50
0.243
970521AG2-332 GEN
50/50
17.34
270535AF1-215 GEN1
Solar/Wind Harmer
6.708
270536AF1-215 GEN2
Solar/Wind Harmer
6.708
274770LINCOLN ;1U
Adder
9.097
274771LINCOLN ;2U
Adder
9.097
274805UNIV PK N;1U
Adder
7.248
274808UNIV PK N;4U
Adder
7.201
945421AF1-207 GEN
Solar/Wind Harmer
20.2
957841AF2-078 GEN
Solar/Wind Harmer
8.696
274888KELLY CRK;1U
Solar/Wind Harmer
8.462
276776AD2-060 GEN
Solar/Wind Harmer
0.6
958011AF2-095 GEN
Solar/Wind Harmer
20.65
970941AG2-585 GEN
Solar/Wind Harmer
7.887
276897AD1-100 C
Solar/Wind Harmer
66.349
274674JOLIET 9 ;6U
Adder
21.855
276893AG1-478 C
Solar/Wind Harmer
0.622
270180AB1-006 GEN1
Solar/Wind Harmer
10.164
24697605MDL-3G C
Solar/Wind Harmer
5.21
24755605MDL-5G
Solar/Wind Harmer
3.407
24697905MDL-4G C
Solar/Wind Harmer
3.243
270181AB1-006 GEN2
Solar/Wind Harmer
1.011
958481AF2-142 GEN
Solar/Wind Harmer
20.916
274696ROCKY RD ;4P
Adder
15.857
274695ROCKY RD ;2P
Adder
15.492
274693ROCKY RD ;1P
Adder
15.339
274697ROCKY RD ;3P
Adder
4.208
274683WAUKEGAN ;8U
Adder
29.25
274683WAUKEGAN ;8U
Adder
24.656
962691AG1-118 GEN
Solar/Wind Harmer
41.457
958491AF2-143 GEN
Solar/Wind Harmer
20.688
960751AF2-366 GEN
Solar/Wind Harmer
3.956
276901AD2-066 C O1
Solar/Wind Harmer
4.828
972235AH1-702 GEN1
Adder
3.399
972236AH1-702 GEN2
Adder
2.955
274764LEE CO EC;5U
Adder
12.402
274765LEE CO EC;6U
Adder
12.402
274762LEE CO EC;3U
Adder
12.373
274763LEE CO EC;4U
Adder
12.256
247621Y3-024
Adder
0.274
270054AF2-122 C O1
Solar/Wind Helper
1.203
24387305FR-4G C
Solar/Wind Harmer
6.907
24344005CKG1
50/50
9.721
270144AC1-141 ST1_
50/50
3.196
24641605TWIN BRNCH
50/50
0.026
24653605MOTTVILLE
50/50
0.006
270071AF1-092 GEN
Solar/Wind Harmer
22.781
960681AF2-359 GEN
Solar/Wind Harmer
5.725
971771AH1-392 GEN
Solar/Wind Harmer
13.577
270526AF1-158 GEN
Solar/Wind Harmer
6.833
970031AG2-029 GEN
Solar/Wind Harmer
36.912
944161AF1-084 GEN
Solar/Wind Harmer
3.26
274775LINCOLN ;6U
Adder
9.097
274776LINCOLN ;7U
Adder
9.097
274777LINCOLN ;8U
Adder
9.097
958391AF2-133 GEN
Solar/Wind Harmer
13.265
959331AF2-224 GEN
Solar/Wind Harmer
14.62
959141AF2-205 GEN
Solar/Wind Harmer
8.817
972037AH1-567 GEN1
Adder
0.263
274827FISK ;RP
Adder
11.133
960591AF2-350 GEN
Solar/Wind Harmer
14.34
274800UNIV PARK;3U
Adder
8.357
274801UNIV PARK;4U
Adder
8.357
972228AH1-698 GEN2
Adder
5.307
972227AH1-698 GEN1
Adder
3.737
274687WILL CNTY;4U
Adder
39.781
274687WILL CNTY;4U
Adder
39.781
274675JOLIET 29;7U
Adder
43.621
274675JOLIET 29;7U
Adder
42.063
274728ELWOOD EC;5P
Adder
23.325
274731ELWOOD EC;2P
Adder
23.324
274733ELWOOD EC;3P
Adder
23.324
274735ELWOOD EC;4P
Adder
23.324
276893AG1-478 C
Solar/Wind Harmer
0.78
970833AG2-524 GEN
Solar/Wind Harmer
12.364
970833AG2-524 GEN
Solar/Wind Harmer
5.751
946581AF1-322 GEN
Solar/Wind Harmer
14.461
24691005MDL-2G C
Solar/Wind Harmer
5.226
274744AC1-111 GEN8
Adder
7.861
274746AC1-111 G10
Adder
7.861
24729505KEY G4
Adder
9.035
270223U2-072_GEN1
Solar/Wind Harmer
2.747
270224U2-072_GEN2
Solar/Wind Harmer
2.747
270227U2-072_GEN3
Solar/Wind Harmer
2.747
270228U2-072_GEN4
Solar/Wind Harmer
2.747
270231U2-072_GEN5
Solar/Wind Harmer
2.747
270578AF1-285 GEN2
Solar/Wind Harmer
0.647
970073AG2-061 GEN
Solar/Wind Harmer
3.208
971549AH1-272 GEN
Solar/Wind Harmer
25.443
965041AG1-368 GEN
Solar/Wind Harmer
13.732
274863CRW1-WTG
Solar/Wind Harmer
7.627
274864CRW2-WTG
Solar/Wind Harmer
7.627
971411AH1-196 GEN
Solar/Wind Harmer
20.459
971675AH1-338 GEN
Solar/Wind Harmer
24.548
276861AD2-134 GEN
Solar/Wind Harmer
2.434
276863AD2-134 GEN
Solar/Wind Harmer
2.434
274823ROCKFORD ;21
Adder
26.328
972267AH1-718 GEN
Adder
5.487
24386405FR-21G C
Solar/Wind Harmer
5.848
24387005FR-3G C
Solar/Wind Harmer
5.379
270475AD2-096_GEN
50/50
9.997
270142AC1-141 CT1_
50/50
3.606
24642205MAYFLWER
50/50
0.055
944961AF1-161 GEN
50/50
4.308
962601AG1-109 GEN
50/50
4.308
962771AG1-126 GEN
Solar/Wind Harmer
110.681
970153AG2-106 GEN
Solar/Wind Harmer
48.262
270284AF1-227 GEN1
Solar/Wind Harmer
8.999
270287AF1-227 GEN3
Solar/Wind Harmer
3.328
971347AH1-153 GEN
Solar/Wind Harmer
7.836
270043AE2-236 GEN
Solar/Wind Harmer
8.379
24441505OLIV SLR
Solar/Wind Harmer
0.201
247643Z2-116 C
Solar/Wind Harmer
0.105
270505AE1-170 C O1
Solar/Wind Harmer
22.409
945111AF1-176 GEN
Solar/Wind Harmer
8.423
270063AE2-323 C
Solar/Wind Harmer
3.264
964401AG1-302 GEN
Solar/Wind Harmer
13.317
274772LINCOLN ;3U
Adder
9.097
965021AG1-366 GEN
Solar/Wind Harmer
3.4
972231SS25-0005
Solar/Wind Harmer
13.792
972181SS23-001
Solar/Wind Harmer
8.62
274752CRETE EC ;2U
Adder
7.103
274753CRETE EC ;3U
Adder
7.103
274724RIVER EC ;11
Adder
25.717
276164X3-005 C
Solar/Wind Harmer
1.016
274814UNIV PK N;0U
Adder
7.296
274807UNIV PK N;3U
Adder
7.28
274811UNIV PK N;7U
Adder
7.232
274803UNIV PARK;6U
Adder
8.371
274826FISK ;BP
Adder
15.709
970707AG2-453 GEN
Solar/Wind Harmer
40.157
274887GEN-1.85
Solar/Wind Harmer
7.64
276772AC2-154 GEN
Solar/Wind Harmer
4.002
276843GEN-1.7
Solar/Wind Harmer
0.822
276806AD2-047 C O1
Solar/Wind Harmer
15.341
972038AH1-567 GEN2
Adder
0.523
972259AH1-714 GEN
Adder
27.313
939351AE1-166 GEN
Solar/Wind Harmer
8.47
274676JOLIET 29;8U
Adder
42.062
274730ELWOOD EC;6P
Adder
23.325
274734ELWOOD EC;8P
Adder
23.325
274736ELWOOD EC;9P
Adder
23.325
274729ELWOOD EC;1P
Adder
23.324
944531AF1-118 GEN
Solar/Wind Harmer
49.583
24690905MDL-1G C
Solar/Wind Harmer
11.346
970781AG2-491 GEN
Solar/Wind Harmer
14.133
943121AE2-341 GEN
Solar/Wind Harmer
21.118
943591AF1-030 GEN
Solar/Wind Harmer
14.078
274862TOP CROP ;2U
Solar/Wind Harmer
7.05
942871AE2-306 GEN
Solar/Wind Harmer
1.262
270391AF1-285 GEN3
Solar/Wind Harmer
0.647
274682WAUKEGAN ;7U
Adder
24.977
276868AE1-113 GEN
Solar/Wind Harmer
13.887
274879MINONK ;1U
Solar/Wind Harmer
9.259
276799AD1-013 GEN
Solar/Wind Harmer
3.014
946671AF1-331 GEN
Solar/Wind Harmer
0.571
274855GSG-6 ;RU
Solar/Wind Harmer
5.034
274850MENDOTA H;RU
Solar/Wind Harmer
3.5
276602WESTBROOK C
Solar/Wind Harmer
2.898
274760LEE CO EC;1U
Adder
12.373
274767LEE CO EC;8U
Adder
12.227
24728505AND G1
Adder
4.035
23906402RICHG1
Adder
1.058
23906502RICHG2&3
Adder
1.056
24386205FR-12G C
Solar/Wind Harmer
5.827
24307105BERRINSP G
50/50
0.032
962761AG1-125 GEN
Solar/Wind Harmer
110.681
970149AG2-104 GEN
Solar/Wind Harmer
68.345
970155AG2-107 GEN
Solar/Wind Harmer
48.262
270286AF1-227 GEN2
Solar/Wind Harmer
3.328
270216AD2-079_GEN
Solar/Wind Harmer
0.91
957891AF2-083 GEN
Solar/Wind Harmer
22.392
970373AG2-245 GEN
Solar/Wind Harmer
31.282
945111AF1-176 GEN
Solar/Wind Harmer
26.576
270449AD2-020 GEN
Solar/Wind Harmer
4.153
943021AE2-325 GEN
Solar/Wind Harmer
5.398
270055AF2-134 C O1
Solar/Wind Harmer
4.472
958381AF2-132 GEN
Solar/Wind Harmer
13.317
972207SS24-0001
Solar/Wind Harmer
32.343
274773LINCOLN ;4U
Adder
9.097
274774LINCOLN ;5U
Adder
9.097
964861AG1-349 GEN
Solar/Wind Harmer
11.531
971917AH1-482 GEN
Solar/Wind Harmer
13.304
965011AG1-365 GEN
Solar/Wind Harmer
14.62
24441205WTRV SLR C
Solar/Wind Harmer
0.197
274751CRETE EC ;1U
Adder
7.103
274754CRETE EC ;4U
Adder
7.103
940581AE2-045 GEN
Solar/Wind Harmer
14.817
971605AH1-302 GEN
Solar/Wind Harmer
12.669
274723RIVER EC ;12
Adder
26.022
274812UNIV PK N;8U
Adder
7.232
274802UNIV PARK;5U
Adder
8.371
941551AE2-152 GEN
Solar/Wind Harmer
6.478
274676JOLIET 29;8U
Adder
43.62
274674JOLIET 9 ;6U
Adder
21.855
274732ELWOOD EC;7P
Adder
23.325
274871GR RIDGE ;2U
Solar/Wind Harmer
10.884
274847GR RIDGE ;BU
Solar/Wind Harmer
7.156
24791305MDL-5G
Solar/Wind Harmer
3.407
274745AC1-111 GEN9
Adder
7.861
276694AA1-018 GEN2
Solar/Wind Harmer
8.798
276691AA1-018 GEN1
Solar/Wind Harmer
1.052
274861TOP CROP ;1U
Solar/Wind Harmer
8.443
270391AF1-285 GEN3
Solar/Wind Harmer
1.682
270578AF1-285 GEN2
Solar/Wind Harmer
1.682
274682WAUKEGAN ;7U
Adder
24.977
274828WAUKEGAN ;BP
Adder
15.332
939401AE1-172 GEN
Solar/Wind Harmer
19.294
276805AD2-038 GEN
Solar/Wind Harmer
7.072
962781AG1-127 GEN
Solar/Wind Harmer
13.111
274872LEEDK;1U
Solar/Wind Harmer
11.294
276882AE2-255 GEN
Solar/Wind Harmer
4.629
971997AH1-543 GEN
Solar/Wind Harmer
21.574
274822ROCKFORD ;11
Adder
26.521
274761LEE CO EC;2U
Adder
12.373
274766LEE CO EC;7U
Adder
12.227
24728605AND G2
Adder
4.035
970091AG2-072 GEN
Adder
69.079
23906502RICHG2&3
Adder
1.056
24385905FR-11G C
Solar/Wind Harmer
11.302
24386605FR-22G C
Solar/Wind Harmer
5.848
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.539
NYPJM->LTFIMP_NY
CLTF
2.802
LGEELTFEXP_LGEE->PJM
CLTF
4.631
WECLTFEXP_WEC->PJM
CLTF
5.141
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.467
AG2-052LTFEXP_AG2-052->PJM
LTF
0.327
AH1-155LTFEXP_AH1-155->PJM
LTF
0.491
LAGNLTFEXP_LAGN->PJM
CLTF
11.508
TVALTFEXP_TVA->PJM
CLTF
4.677
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.087
CBM West 1LTFEXP_CBM-W1->PJM
CBM
165.647
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.96
MECLTFEXP_MEC->PJM
CLTF
19.157
SIGELTFEXP_SIGE->PJM
CLTF
0.435

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AEP_P1-2_#AG1-125-ADKINS_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#AG1-125-ADKINS_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.48 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:4638.62
MW Contribution:
50.41
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
270102X2-052 ST
50/50
2.435
270100X2-052 CT1
50/50
2.25
270101X2-052 CT2
50/50
2.25
24643105BUCHANAN
50/50
0.019
247620Y3-023
50/50
0.727
270349AD2-093_GEN
Solar/Wind Harmer
0.002
270471AD2-092_GEN
Solar/Wind Harmer
0.002
970349AG2-230 GEN
Solar/Wind Harmer
16.401
965681AG1-436 GEN
Solar/Wind Harmer
13.215
965791AG1-447 GEN
Solar/Wind Harmer
9.691
961051AF2-396 GEN
Solar/Wind Harmer
20.719
961051AF2-396 GEN
Solar/Wind Harmer
13.812
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
274770LINCOLN ;1U
Adder
12.383
274771LINCOLN ;2U
Adder
12.383
274805UNIV PK N;1U
Adder
7.248
274808UNIV PK N;4U
Adder
7.201
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0.001
274888KELLY CRK;1U
Solar/Wind Harmer
0.583
24344005CKG1
50/50
9.721
270144AC1-141 ST1_
50/50
3.196
24641605TWIN BRNCH
50/50
0.026
24653605MOTTVILLE
50/50
0.006
270071AF1-092 GEN
Solar/Wind Harmer
20.308
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971771AH1-392 GEN
Solar/Wind Harmer
10.525
270526AF1-158 GEN
Solar/Wind Harmer
0.001
970031AG2-029 GEN
Solar/Wind Harmer
5.58
274775LINCOLN ;6U
Adder
12.383
274776LINCOLN ;7U
Adder
12.383
274777LINCOLN ;8U
Adder
12.383
958391AF2-133 GEN
Solar/Wind Harmer
0.002
959331AF2-224 GEN
Solar/Wind Harmer
7.14
959141AF2-205 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
6.034
972037AH1-567 GEN1
Adder
0.263
274827FISK ;RP
Adder
11.133
960591AF2-350 GEN
Solar/Wind Harmer
10.005
274800UNIV PARK;3U
Adder
8.357
274801UNIV PARK;4U
Adder
8.357
972228AH1-698 GEN2
Adder
5.307
972227AH1-698 GEN1
Adder
3.737
274687WILL CNTY;4U
Adder
39.781
274687WILL CNTY;4U
Adder
39.781
274675JOLIET 29;7U
Adder
43.621
274675JOLIET 29;7U
Adder
42.063
274728ELWOOD EC;5P
Adder
23.325
274731ELWOOD EC;2P
Adder
23.324
274733ELWOOD EC;3P
Adder
23.324
274735ELWOOD EC;4P
Adder
23.324
970833AG2-524 GEN
Solar/Wind Harmer
10.869
970833AG2-524 GEN
Solar/Wind Harmer
7.246
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274744AC1-111 GEN8
Adder
7.861
274746AC1-111 G10
Adder
7.861
24729505KEY G4
Adder
9.035
270578AF1-285 GEN2
Solar/Wind Harmer
0.647
970073AG2-061 GEN
Solar/Wind Harmer
3.208
971549AH1-272 GEN
Solar/Wind Harmer
19.814
965041AG1-368 GEN
Solar/Wind Harmer
9.581
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971411AH1-196 GEN
Solar/Wind Harmer
14.274
971675AH1-338 GEN
Solar/Wind Harmer
3.711
276861AD2-134 GEN
Solar/Wind Harmer
0.169
276863AD2-134 GEN
Solar/Wind Harmer
0.169
24386405FR-21G C
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
18.917
274823ROCKFORD ;21
Adder
26.328
970169AG2-114 GEN
Solar/Wind Harmer
9.398
247521TR3_G114
Solar/Wind Harmer
0.34
965051AG1-369 GEN
Solar/Wind Harmer
4.689
963791AG1-232 GEN
Solar/Wind Harmer
12.673
926823AC1-168 GEN
Solar/Wind Harmer
1.594
274856ECOGROVE ;U1
Solar/Wind Harmer
0.219
971681AH1-341 GEN
Solar/Wind Harmer
14.998
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.303
963841AG1-237 GEN
Solar/Wind Harmer
3.99
972267AH1-718 GEN
Adder
5.487
276741O09 GEN1
Solar/Wind Harmer
0.324
274877BISHOP HL;1U
Solar/Wind Harmer
0.305
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
9.573
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.153
970289AG2-191 GEN
Solar/Wind Harmer
1.719
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
5.01
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270007AE1-245 C
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
1.403
276668AB2-070 GEN1
Solar/Wind Harmer
0.336
276848AB2-070 GEN3
Solar/Wind Harmer
0.334
276849AB2-070 GEN2
Solar/Wind Harmer
0.336
276776AD2-060 GEN
Solar/Wind Harmer
1.067
958011AF2-095 GEN
Solar/Wind Harmer
14.407
970941AG2-585 GEN
Solar/Wind Harmer
5.503
276897AD1-100 C
Solar/Wind Harmer
24.912
274674JOLIET 9 ;6U
Adder
21.855
276893AG1-478 C
Solar/Wind Harmer
0.66
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
14.593
274696ROCKY RD ;4P
Adder
15.857
274695ROCKY RD ;2P
Adder
15.492
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
3.17
944221AF1-090 GEN
Solar/Wind Harmer
4.619
247536S-71 GEN
Solar/Wind Harmer
0.309
270543AE2-219 C
Solar/Wind Harmer
5.183
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
10.57
270356AE2-297 GEN
Solar/Wind Harmer
0
24344105CKG2
50/50
12.076
270143AC1-141 CT2_
50/50
3.606
24639705ELKHART HY
50/50
0.243
970521AG2-332 GEN
50/50
17.34
24307105BERRINSP G
50/50
0.032
962761AG1-125 GEN
Solar/Wind Harmer
93.339
970149AG2-104 GEN
Solar/Wind Harmer
50.405
970155AG2-107 GEN
Solar/Wind Harmer
59.604
957891AF2-083 GEN
Solar/Wind Harmer
17.358
970373AG2-245 GEN
Solar/Wind Harmer
21.825
945111AF1-176 GEN
Solar/Wind Harmer
18.541
270449AD2-020 GEN
Solar/Wind Harmer
-0.001
943021AE2-325 GEN
Solar/Wind Harmer
5.398
270055AF2-134 C O1
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.002
274773LINCOLN ;4U
Adder
12.383
274774LINCOLN ;5U
Adder
12.383
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
13.304
965011AG1-365 GEN
Solar/Wind Harmer
10.2
274751CRETE EC ;1U
Adder
11.974
274754CRETE EC ;4U
Adder
11.974
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
12.669
274723RIVER EC ;12
Adder
26.022
274812UNIV PK N;8U
Adder
7.232
274802UNIV PARK;5U
Adder
8.371
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
43.62
274674JOLIET 9 ;6U
Adder
21.855
274732ELWOOD EC;7P
Adder
23.325
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
7.861
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.581
274861TOP CROP ;1U
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
24.977
274828WAUKEGAN ;BP
Adder
15.332
939401AE1-172 GEN
Solar/Wind Harmer
7.225
276805AD2-038 GEN
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
9.154
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
1.118
971997AH1-543 GEN
Solar/Wind Harmer
5.017
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
28.375
959081AF2-199 GEN
Solar/Wind Harmer
9.458
971067AG2-660 GEN
Solar/Wind Harmer
3.153
274822ROCKFORD ;11
Adder
26.521
970819AG2-516 GEN
Solar/Wind Harmer
11.253
970569AG2-363 GEN
Solar/Wind Harmer
28.125
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
12.373
274766LEE CO EC;7U
Adder
12.227
270317AD1-130_GEN
Solar/Wind Harmer
-0.001
965651AG1-433 GEN
Solar/Wind Harmer
2.714
965421AG1-410 GEN
Solar/Wind Harmer
27.632
276646AC1-214 GEN2
Solar/Wind Harmer
0.36
276708O09 GEN2
Solar/Wind Harmer
0.324
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
12.763
274848CAMPGROVE;RU
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.367
270489AE1-102 GEN1
Solar/Wind Harmer
1.184
958861AF2-177 GEN
Solar/Wind Harmer
3.944
963741AG1-226 GEN
Solar/Wind Harmer
21.176
270594AE1-207 GEN
Solar/Wind Harmer
9.873
270032AE2-172
Solar/Wind Harmer
5.877
945371AF1-202 GEN
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
9.571
276621W2-048 GEN
Solar/Wind Harmer
0.421
965911AG1-460 GEN
Solar/Wind Harmer
1.629
270005AE1-210 C O1
Solar/Wind Harmer
1.763
970825AG2-519 GEN
Solar/Wind Harmer
2.883
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.555
24728605AND G2
Adder
4.035
970773AG2-487 GEN
Solar/Wind Harmer
1.216
970091AG2-072 GEN
Adder
69.079
23906502RICHG2&3
Adder
1.056
270475AD2-096_GEN
50/50
9.997
270142AC1-141 CT1_
50/50
3.606
24642205MAYFLWER
50/50
0.055
944961AF1-161 GEN
50/50
4.308
962601AG1-109 GEN
50/50
4.308
962771AG1-126 GEN
Solar/Wind Harmer
93.339
970153AG2-106 GEN
Solar/Wind Harmer
59.604
270284AF1-227 GEN1
Solar/Wind Harmer
0
971347AH1-153 GEN
Solar/Wind Harmer
5.467
270043AE2-236 GEN
Solar/Wind Harmer
6.82
270505AE1-170 C O1
Solar/Wind Harmer
10.944
945111AF1-176 GEN
Solar/Wind Harmer
8.423
270063AE2-323 C
Solar/Wind Harmer
0.001
964401AG1-302 GEN
Solar/Wind Harmer
0.002
274772LINCOLN ;3U
Adder
12.383
965021AG1-366 GEN
Solar/Wind Harmer
3.4
274752CRETE EC ;2U
Adder
11.974
274753CRETE EC ;3U
Adder
11.974
274724RIVER EC ;11
Adder
25.717
274814UNIV PK N;0U
Adder
7.296
274807UNIV PK N;3U
Adder
7.28
274811UNIV PK N;7U
Adder
7.232
274803UNIV PARK;6U
Adder
8.371
274826FISK ;BP
Adder
15.709
970707AG2-453 GEN
Solar/Wind Harmer
32.686
274887GEN-1.85
Solar/Wind Harmer
0.26
276843GEN-1.7
Solar/Wind Harmer
0.323
276806AD2-047 C O1
Solar/Wind Harmer
5.669
972038AH1-567 GEN2
Adder
0.523
972259AH1-714 GEN
Adder
27.313
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
42.062
274730ELWOOD EC;6P
Adder
23.325
274734ELWOOD EC;8P
Adder
23.325
274736ELWOOD EC;9P
Adder
23.325
274729ELWOOD EC;1P
Adder
23.324
944531AF1-118 GEN
Solar/Wind Harmer
44.295
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
9.86
943121AE2-341 GEN
Solar/Wind Harmer
16.469
943591AF1-030 GEN
Solar/Wind Harmer
10.952
274862TOP CROP ;2U
Solar/Wind Harmer
1.313
270391AF1-285 GEN3
Solar/Wind Harmer
0.647
274682WAUKEGAN ;7U
Adder
24.977
276868AE1-113 GEN
Solar/Wind Harmer
1.916
274879MINONK ;1U
Solar/Wind Harmer
0.4
946671AF1-331 GEN
Solar/Wind Harmer
1.015
274855GSG-6 ;RU
Solar/Wind Harmer
0.347
274850MENDOTA H;RU
Solar/Wind Harmer
0.11
24386205FR-12G C
Solar/Wind Harmer
0
959091AF2-200 GEN
Solar/Wind Harmer
18.917
970571AG2-364 GEN
Solar/Wind Harmer
18.75
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
12.373
274767LEE CO EC;8U
Adder
12.227
247642Z2-115 C
Solar/Wind Harmer
0.004
24695305TIMB G C
Solar/Wind Harmer
0.78
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.305
246938BC-WTG3
Solar/Wind Harmer
0.328
270491AE1-102 GEN2
Solar/Wind Harmer
1.184
970289AG2-191 GEN
Solar/Wind Harmer
0.995
965091AG1-374 GEN
Solar/Wind Harmer
26.927
959611AF2-252 GEN
Solar/Wind Harmer
2.992
965931AG1-462 GEN
Solar/Wind Harmer
22.694
971087AG2-675 GEN
Solar/Wind Harmer
4.746
971993AH1-541 GEN
Solar/Wind Harmer
3.947
274693ROCKY RD ;1P
Adder
15.339
274697ROCKY RD ;3P
Adder
4.208
274683WAUKEGAN ;8U
Adder
29.25
274683WAUKEGAN ;8U
Adder
24.656
962691AG1-118 GEN
Solar/Wind Harmer
28.923
958491AF2-143 GEN
Solar/Wind Harmer
14.434
276901AD2-066 C O1
Solar/Wind Harmer
-0.001
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
1.076
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
18.917
971343AH1-151 GEN
Solar/Wind Harmer
18.917
972235AH1-702 GEN1
Adder
3.399
972236AH1-702 GEN2
Adder
2.955
270246TR4_N_V150
Solar/Wind Harmer
0.06
270247TR4_N_V136
Solar/Wind Harmer
0.06
938861AE1-114 GEN
Solar/Wind Harmer
5.277
274764LEE CO EC;5U
Adder
12.402
274765LEE CO EC;6U
Adder
12.402
274762LEE CO EC;3U
Adder
12.373
274763LEE CO EC;4U
Adder
12.256
944231AF1-091 GEN
Solar/Wind Harmer
21.381
270462AD2-086
Solar/Wind Harmer
0.001
944541AF1-119 GEN
Solar/Wind Harmer
0.618
960971AF2-388 GEN
Solar/Wind Harmer
5.429
942221AE2-234 GEN
Solar/Wind Harmer
3.695
276645AC1-214 GEN1
Solar/Wind Harmer
0.36
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.481
942111AE2-223 GEN
Solar/Wind Harmer
2.963
246937BC-WTG2
Solar/Wind Harmer
0.367
970291AG2-192 GEN
Solar/Wind Harmer
1.176
970291AG2-192 GEN
Solar/Wind Harmer
0.543
960611AF2-352 GEN
Solar/Wind Harmer
2.992
970241AG2-163 GEN
Solar/Wind Harmer
5.219
971613AH1-306 GEN
Solar/Wind Harmer
4.231
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.574
270031AE2-169
Solar/Wind Harmer
4.725
270599AE1-208 GEN
Solar/Wind Harmer
7.874
276615X2-022 GEN
Solar/Wind Harmer
0.087
276838X2-022 GEN2
Solar/Wind Harmer
0.473
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.61
276916AD2-100_GEN
Solar/Wind Harmer
16.976
276911AD2-131_GEN
Solar/Wind Harmer
1.118
945391AF1-204 GEN
Solar/Wind Harmer
8.566
247621Y3-024
Adder
0.274
926881AC1-175 GEN
Solar/Wind Harmer
0
970621AG2-405 GEN
Solar/Wind Harmer
1.383
270383AD1-128 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
7.404
970885AG2-551 GEN
Solar/Wind Harmer
2.468
971587AH1-292 GEN
Solar/Wind Harmer
5.199
270054AF2-122 C O1
Solar/Wind Helper
1.203
957381AF2-032 GEN
Solar/Wind Harmer
1.851
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
12.219
942481AE2-261 GEN
Solar/Wind Harmer
24.353
270004AE1-209 GEN
Solar/Wind Harmer
1.763
970825AG2-519 GEN
Solar/Wind Harmer
6.118
946031AF1-268 GEN
Solar/Wind Harmer
7.675
970193AG2-126 GEN
Solar/Wind Harmer
12.093
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
24728505AND G1
Adder
4.035
23906402RICHG1
Adder
1.058
23906502RICHG2&3
Adder
1.056
270541AE2-072 C
Solar/Wind Harmer
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.539
NYPJM->LTFIMP_NY
CLTF
2.802
LGEELTFEXP_LGEE->PJM
CLTF
4.631
WECLTFEXP_WEC->PJM
CLTF
5.141
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.467
AG2-052LTFEXP_AG2-052->PJM
LTF
0.327
AH1-155LTFEXP_AH1-155->PJM
LTF
0.491
LAGNLTFEXP_LAGN->PJM
CLTF
11.508
TVALTFEXP_TVA->PJM
CLTF
4.677
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.087
CBM West 1LTFEXP_CBM-W1->PJM
CBM
165.647
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.96
MECLTFEXP_MEC->PJM
CLTF
19.157
SIGELTFEXP_SIGE->PJM
CLTF
0.435

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AEP_P4_#ADKINS AG1125_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#ADKINS AG1125_SRT-A_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.09 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:4803.57
MW Contribution:
68.34
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
270102X2-052 ST
50/50
2.435
270100X2-052 CT1
50/50
2.25
270101X2-052 CT2
50/50
2.25
24643105BUCHANAN
50/50
0.019
247620Y3-023
50/50
0.727
270349AD2-093_GEN
Solar/Wind Harmer
6.24
270471AD2-092_GEN
Solar/Wind Harmer
6.24
970349AG2-230 GEN
Solar/Wind Harmer
23.509
965681AG1-436 GEN
Solar/Wind Harmer
18.941
965791AG1-447 GEN
Solar/Wind Harmer
9.691
961051AF2-396 GEN
Solar/Wind Harmer
23.569
961051AF2-396 GEN
Solar/Wind Harmer
10.962
270535AF1-215 GEN1
Solar/Wind Harmer
6.708
270536AF1-215 GEN2
Solar/Wind Harmer
6.708
274770LINCOLN ;1U
Adder
9.097
274771LINCOLN ;2U
Adder
9.097
274805UNIV PK N;1U
Adder
7.248
274808UNIV PK N;4U
Adder
7.201
945421AF1-207 GEN
Solar/Wind Harmer
20.2
957841AF2-078 GEN
Solar/Wind Harmer
8.696
274888KELLY CRK;1U
Solar/Wind Harmer
8.462
276776AD2-060 GEN
Solar/Wind Harmer
0.6
958011AF2-095 GEN
Solar/Wind Harmer
20.65
970941AG2-585 GEN
Solar/Wind Harmer
7.887
276897AD1-100 C
Solar/Wind Harmer
66.349
274674JOLIET 9 ;6U
Adder
21.855
276893AG1-478 C
Solar/Wind Harmer
0.622
270180AB1-006 GEN1
Solar/Wind Harmer
10.164
24697605MDL-3G C
Solar/Wind Harmer
5.21
24755605MDL-5G
Solar/Wind Harmer
3.407
24697905MDL-4G C
Solar/Wind Harmer
3.243
270181AB1-006 GEN2
Solar/Wind Harmer
1.011
958481AF2-142 GEN
Solar/Wind Harmer
20.916
274696ROCKY RD ;4P
Adder
15.857
274695ROCKY RD ;2P
Adder
15.492
274693ROCKY RD ;1P
Adder
15.339
274697ROCKY RD ;3P
Adder
4.208
274683WAUKEGAN ;8U
Adder
29.25
274683WAUKEGAN ;8U
Adder
24.656
962691AG1-118 GEN
Solar/Wind Harmer
41.457
958491AF2-143 GEN
Solar/Wind Harmer
20.688
960751AF2-366 GEN
Solar/Wind Harmer
3.956
276901AD2-066 C O1
Solar/Wind Harmer
4.828
972235AH1-702 GEN1
Adder
3.399
972236AH1-702 GEN2
Adder
2.955
274764LEE CO EC;5U
Adder
12.402
274765LEE CO EC;6U
Adder
12.402
274762LEE CO EC;3U
Adder
12.373
274763LEE CO EC;4U
Adder
12.256
247621Y3-024
Adder
0.274
270054AF2-122 C O1
Solar/Wind Helper
1.203
24387305FR-4G C
Solar/Wind Harmer
6.907
24344105CKG2
50/50
12.076
270143AC1-141 CT2_
50/50
3.606
24639705ELKHART HY
50/50
0.243
970521AG2-332 GEN
50/50
17.34
24307105BERRINSP G
50/50
0.032
962761AG1-125 GEN
Solar/Wind Harmer
110.681
970149AG2-104 GEN
Solar/Wind Harmer
68.345
970155AG2-107 GEN
Solar/Wind Harmer
48.262
270286AF1-227 GEN2
Solar/Wind Harmer
3.328
270216AD2-079_GEN
Solar/Wind Harmer
0.91
957891AF2-083 GEN
Solar/Wind Harmer
22.392
970373AG2-245 GEN
Solar/Wind Harmer
31.282
945111AF1-176 GEN
Solar/Wind Harmer
26.576
270449AD2-020 GEN
Solar/Wind Harmer
4.153
943021AE2-325 GEN
Solar/Wind Harmer
5.398
270055AF2-134 C O1
Solar/Wind Harmer
4.472
958381AF2-132 GEN
Solar/Wind Harmer
13.317
972207SS24-0001
Solar/Wind Harmer
32.343
274773LINCOLN ;4U
Adder
9.097
274774LINCOLN ;5U
Adder
9.097
964861AG1-349 GEN
Solar/Wind Harmer
11.531
971917AH1-482 GEN
Solar/Wind Harmer
13.304
965011AG1-365 GEN
Solar/Wind Harmer
14.62
24441205WTRV SLR C
Solar/Wind Harmer
0.197
274751CRETE EC ;1U
Adder
7.103
274754CRETE EC ;4U
Adder
7.103
940581AE2-045 GEN
Solar/Wind Harmer
14.817
971605AH1-302 GEN
Solar/Wind Harmer
12.669
274723RIVER EC ;12
Adder
26.022
274812UNIV PK N;8U
Adder
7.232
274802UNIV PARK;5U
Adder
8.371
941551AE2-152 GEN
Solar/Wind Harmer
6.478
274676JOLIET 29;8U
Adder
43.62
274674JOLIET 9 ;6U
Adder
21.855
274732ELWOOD EC;7P
Adder
23.325
274871GR RIDGE ;2U
Solar/Wind Harmer
10.884
274847GR RIDGE ;BU
Solar/Wind Harmer
7.156
24791305MDL-5G
Solar/Wind Harmer
3.407
274745AC1-111 GEN9
Adder
7.861
276694AA1-018 GEN2
Solar/Wind Harmer
8.798
276691AA1-018 GEN1
Solar/Wind Harmer
1.052
274861TOP CROP ;1U
Solar/Wind Harmer
8.443
270391AF1-285 GEN3
Solar/Wind Harmer
1.682
270578AF1-285 GEN2
Solar/Wind Harmer
1.682
274682WAUKEGAN ;7U
Adder
24.977
274828WAUKEGAN ;BP
Adder
15.332
939401AE1-172 GEN
Solar/Wind Harmer
19.294
276805AD2-038 GEN
Solar/Wind Harmer
7.072
962781AG1-127 GEN
Solar/Wind Harmer
13.111
274872LEEDK;1U
Solar/Wind Harmer
11.294
276882AE2-255 GEN
Solar/Wind Harmer
4.629
971997AH1-543 GEN
Solar/Wind Harmer
21.574
274822ROCKFORD ;11
Adder
26.521
274761LEE CO EC;2U
Adder
12.373
274766LEE CO EC;7U
Adder
12.227
24728605AND G2
Adder
4.035
970091AG2-072 GEN
Adder
69.079
23906502RICHG2&3
Adder
1.056
24385905FR-11G C
Solar/Wind Harmer
11.302
24386605FR-22G C
Solar/Wind Harmer
5.848
24344005CKG1
50/50
9.721
270144AC1-141 ST1_
50/50
3.196
24641605TWIN BRNCH
50/50
0.026
24653605MOTTVILLE
50/50
0.006
270071AF1-092 GEN
Solar/Wind Harmer
22.781
960681AF2-359 GEN
Solar/Wind Harmer
5.725
971771AH1-392 GEN
Solar/Wind Harmer
13.577
270526AF1-158 GEN
Solar/Wind Harmer
6.833
970031AG2-029 GEN
Solar/Wind Harmer
36.912
944161AF1-084 GEN
Solar/Wind Harmer
3.26
274775LINCOLN ;6U
Adder
9.097
274776LINCOLN ;7U
Adder
9.097
274777LINCOLN ;8U
Adder
9.097
958391AF2-133 GEN
Solar/Wind Harmer
13.265
959331AF2-224 GEN
Solar/Wind Harmer
14.62
959141AF2-205 GEN
Solar/Wind Harmer
8.817
972037AH1-567 GEN1
Adder
0.263
274827FISK ;RP
Adder
11.133
960591AF2-350 GEN
Solar/Wind Harmer
14.34
274800UNIV PARK;3U
Adder
8.357
274801UNIV PARK;4U
Adder
8.357
972228AH1-698 GEN2
Adder
5.307
972227AH1-698 GEN1
Adder
3.737
274687WILL CNTY;4U
Adder
39.781
274687WILL CNTY;4U
Adder
39.781
274675JOLIET 29;7U
Adder
43.621
274675JOLIET 29;7U
Adder
42.063
274728ELWOOD EC;5P
Adder
23.325
274731ELWOOD EC;2P
Adder
23.324
274733ELWOOD EC;3P
Adder
23.324
274735ELWOOD EC;4P
Adder
23.324
276893AG1-478 C
Solar/Wind Harmer
0.78
970833AG2-524 GEN
Solar/Wind Harmer
12.364
970833AG2-524 GEN
Solar/Wind Harmer
5.751
946581AF1-322 GEN
Solar/Wind Harmer
14.461
24691005MDL-2G C
Solar/Wind Harmer
5.226
274744AC1-111 GEN8
Adder
7.861
274746AC1-111 G10
Adder
7.861
24729505KEY G4
Adder
9.035
270223U2-072_GEN1
Solar/Wind Harmer
2.747
270224U2-072_GEN2
Solar/Wind Harmer
2.747
270227U2-072_GEN3
Solar/Wind Harmer
2.747
270228U2-072_GEN4
Solar/Wind Harmer
2.747
270231U2-072_GEN5
Solar/Wind Harmer
2.747
270578AF1-285 GEN2
Solar/Wind Harmer
0.647
970073AG2-061 GEN
Solar/Wind Harmer
3.208
971549AH1-272 GEN
Solar/Wind Harmer
25.443
965041AG1-368 GEN
Solar/Wind Harmer
13.732
274863CRW1-WTG
Solar/Wind Harmer
7.627
274864CRW2-WTG
Solar/Wind Harmer
7.627
971411AH1-196 GEN
Solar/Wind Harmer
20.459
971675AH1-338 GEN
Solar/Wind Harmer
24.548
276861AD2-134 GEN
Solar/Wind Harmer
2.434
276863AD2-134 GEN
Solar/Wind Harmer
2.434
274823ROCKFORD ;21
Adder
26.328
972267AH1-718 GEN
Adder
5.487
24386405FR-21G C
Solar/Wind Harmer
5.848
24387005FR-3G C
Solar/Wind Harmer
5.379
270475AD2-096_GEN
50/50
9.997
270142AC1-141 CT1_
50/50
3.606
24642205MAYFLWER
50/50
0.055
944961AF1-161 GEN
50/50
4.308
962601AG1-109 GEN
50/50
4.308
962771AG1-126 GEN
Solar/Wind Harmer
110.681
970153AG2-106 GEN
Solar/Wind Harmer
48.262
270284AF1-227 GEN1
Solar/Wind Harmer
8.999
270287AF1-227 GEN3
Solar/Wind Harmer
3.328
971347AH1-153 GEN
Solar/Wind Harmer
7.836
270043AE2-236 GEN
Solar/Wind Harmer
8.379
24441505OLIV SLR
Solar/Wind Harmer
0.201
247643Z2-116 C
Solar/Wind Harmer
0.105
270505AE1-170 C O1
Solar/Wind Harmer
22.409
945111AF1-176 GEN
Solar/Wind Harmer
8.423
270063AE2-323 C
Solar/Wind Harmer
3.264
964401AG1-302 GEN
Solar/Wind Harmer
13.317
274772LINCOLN ;3U
Adder
9.097
965021AG1-366 GEN
Solar/Wind Harmer
3.4
972231SS25-0005
Solar/Wind Harmer
13.792
972181SS23-001
Solar/Wind Harmer
8.62
274752CRETE EC ;2U
Adder
7.103
274753CRETE EC ;3U
Adder
7.103
274724RIVER EC ;11
Adder
25.717
276164X3-005 C
Solar/Wind Harmer
1.016
274814UNIV PK N;0U
Adder
7.296
274807UNIV PK N;3U
Adder
7.28
274811UNIV PK N;7U
Adder
7.232
274803UNIV PARK;6U
Adder
8.371
274826FISK ;BP
Adder
15.709
970707AG2-453 GEN
Solar/Wind Harmer
40.157
274887GEN-1.85
Solar/Wind Harmer
7.64
276772AC2-154 GEN
Solar/Wind Harmer
4.002
276843GEN-1.7
Solar/Wind Harmer
0.822
276806AD2-047 C O1
Solar/Wind Harmer
15.341
972038AH1-567 GEN2
Adder
0.523
972259AH1-714 GEN
Adder
27.313
939351AE1-166 GEN
Solar/Wind Harmer
8.47
274676JOLIET 29;8U
Adder
42.062
274730ELWOOD EC;6P
Adder
23.325
274734ELWOOD EC;8P
Adder
23.325
274736ELWOOD EC;9P
Adder
23.325
274729ELWOOD EC;1P
Adder
23.324
944531AF1-118 GEN
Solar/Wind Harmer
49.583
24690905MDL-1G C
Solar/Wind Harmer
11.346
970781AG2-491 GEN
Solar/Wind Harmer
14.133
943121AE2-341 GEN
Solar/Wind Harmer
21.118
943591AF1-030 GEN
Solar/Wind Harmer
14.078
274862TOP CROP ;2U
Solar/Wind Harmer
7.05
942871AE2-306 GEN
Solar/Wind Harmer
1.262
270391AF1-285 GEN3
Solar/Wind Harmer
0.647
274682WAUKEGAN ;7U
Adder
24.977
276868AE1-113 GEN
Solar/Wind Harmer
13.887
274879MINONK ;1U
Solar/Wind Harmer
9.259
276799AD1-013 GEN
Solar/Wind Harmer
3.014
946671AF1-331 GEN
Solar/Wind Harmer
0.571
274855GSG-6 ;RU
Solar/Wind Harmer
5.034
274850MENDOTA H;RU
Solar/Wind Harmer
3.5
276602WESTBROOK C
Solar/Wind Harmer
2.898
274760LEE CO EC;1U
Adder
12.373
274767LEE CO EC;8U
Adder
12.227
24728505AND G1
Adder
4.035
23906402RICHG1
Adder
1.058
23906502RICHG2&3
Adder
1.056
24386205FR-12G C
Solar/Wind Harmer
5.827
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.539
NYPJM->LTFIMP_NY
CLTF
2.802
LGEELTFEXP_LGEE->PJM
CLTF
4.631
WECLTFEXP_WEC->PJM
CLTF
5.141
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.467
AG2-052LTFEXP_AG2-052->PJM
LTF
0.327
AH1-155LTFEXP_AH1-155->PJM
LTF
0.491
LAGNLTFEXP_LAGN->PJM
CLTF
11.508
TVALTFEXP_TVA->PJM
CLTF
4.677
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.087
CBM West 1LTFEXP_CBM-W1->PJM
CBM
165.647
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.96
MECLTFEXP_MEC->PJM
CLTF
19.157
SIGELTFEXP_SIGE->PJM
CLTF
0.435

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AEP_P1-2_#AG1-125-ADKINS_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#AG1-125-ADKINS_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.94 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:4659.48
MW Contribution:
50.41
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
270102X2-052 ST
50/50
2.435
270100X2-052 CT1
50/50
2.25
270101X2-052 CT2
50/50
2.25
24643105BUCHANAN
50/50
0.019
247620Y3-023
50/50
0.727
270349AD2-093_GEN
Solar/Wind Harmer
0.002
270471AD2-092_GEN
Solar/Wind Harmer
0.002
970349AG2-230 GEN
Solar/Wind Harmer
16.401
965681AG1-436 GEN
Solar/Wind Harmer
13.215
965791AG1-447 GEN
Solar/Wind Harmer
9.691
961051AF2-396 GEN
Solar/Wind Harmer
20.719
961051AF2-396 GEN
Solar/Wind Harmer
13.812
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
274770LINCOLN ;1U
Adder
12.383
274771LINCOLN ;2U
Adder
12.383
274805UNIV PK N;1U
Adder
7.248
274808UNIV PK N;4U
Adder
7.201
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0.001
274888KELLY CRK;1U
Solar/Wind Harmer
0.583
276776AD2-060 GEN
Solar/Wind Harmer
1.067
958011AF2-095 GEN
Solar/Wind Harmer
14.407
970941AG2-585 GEN
Solar/Wind Harmer
5.503
276897AD1-100 C
Solar/Wind Harmer
24.912
274674JOLIET 9 ;6U
Adder
21.855
276893AG1-478 C
Solar/Wind Harmer
0.66
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
14.593
274696ROCKY RD ;4P
Adder
15.857
274695ROCKY RD ;2P
Adder
15.492
274693ROCKY RD ;1P
Adder
15.339
274697ROCKY RD ;3P
Adder
4.208
274683WAUKEGAN ;8U
Adder
29.25
274683WAUKEGAN ;8U
Adder
24.656
962691AG1-118 GEN
Solar/Wind Harmer
28.923
958491AF2-143 GEN
Solar/Wind Harmer
14.434
276901AD2-066 C O1
Solar/Wind Harmer
-0.001
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
1.076
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
18.917
971343AH1-151 GEN
Solar/Wind Harmer
18.917
972235AH1-702 GEN1
Adder
3.399
972236AH1-702 GEN2
Adder
2.955
270246TR4_N_V150
Solar/Wind Harmer
0.06
270247TR4_N_V136
Solar/Wind Harmer
0.06
938861AE1-114 GEN
Solar/Wind Harmer
5.277
274764LEE CO EC;5U
Adder
12.402
274765LEE CO EC;6U
Adder
12.402
274762LEE CO EC;3U
Adder
12.373
274763LEE CO EC;4U
Adder
12.256
944231AF1-091 GEN
Solar/Wind Harmer
21.381
270462AD2-086
Solar/Wind Harmer
0.001
944541AF1-119 GEN
Solar/Wind Harmer
0.618
960971AF2-388 GEN
Solar/Wind Harmer
5.429
942221AE2-234 GEN
Solar/Wind Harmer
3.695
276645AC1-214 GEN1
Solar/Wind Harmer
0.36
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.481
942111AE2-223 GEN
Solar/Wind Harmer
2.963
246937BC-WTG2
Solar/Wind Harmer
0.367
970291AG2-192 GEN
Solar/Wind Harmer
1.176
970291AG2-192 GEN
Solar/Wind Harmer
0.543
960611AF2-352 GEN
Solar/Wind Harmer
2.992
970241AG2-163 GEN
Solar/Wind Harmer
5.219
971613AH1-306 GEN
Solar/Wind Harmer
4.231
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.574
270031AE2-169
Solar/Wind Harmer
4.725
270599AE1-208 GEN
Solar/Wind Harmer
7.874
276615X2-022 GEN
Solar/Wind Harmer
0.087
276838X2-022 GEN2
Solar/Wind Harmer
0.473
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.61
276916AD2-100_GEN
Solar/Wind Harmer
16.976
276911AD2-131_GEN
Solar/Wind Harmer
1.118
945391AF1-204 GEN
Solar/Wind Harmer
8.566
247621Y3-024
Adder
0.274
926881AC1-175 GEN
Solar/Wind Harmer
0
970621AG2-405 GEN
Solar/Wind Harmer
1.383
270383AD1-128 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
7.404
970885AG2-551 GEN
Solar/Wind Harmer
2.468
971587AH1-292 GEN
Solar/Wind Harmer
5.199
270054AF2-122 C O1
Solar/Wind Helper
1.203
24344005CKG1
50/50
9.721
270144AC1-141 ST1_
50/50
3.196
24641605TWIN BRNCH
50/50
0.026
24653605MOTTVILLE
50/50
0.006
270071AF1-092 GEN
Solar/Wind Harmer
20.308
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971771AH1-392 GEN
Solar/Wind Harmer
10.525
270526AF1-158 GEN
Solar/Wind Harmer
0.001
970031AG2-029 GEN
Solar/Wind Harmer
5.58
274775LINCOLN ;6U
Adder
12.383
274776LINCOLN ;7U
Adder
12.383
274777LINCOLN ;8U
Adder
12.383
958391AF2-133 GEN
Solar/Wind Harmer
0.002
959331AF2-224 GEN
Solar/Wind Harmer
7.14
959141AF2-205 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
6.034
972037AH1-567 GEN1
Adder
0.263
274827FISK ;RP
Adder
11.133
960591AF2-350 GEN
Solar/Wind Harmer
10.005
274800UNIV PARK;3U
Adder
8.357
274801UNIV PARK;4U
Adder
8.357
972228AH1-698 GEN2
Adder
5.307
972227AH1-698 GEN1
Adder
3.737
274687WILL CNTY;4U
Adder
39.781
274687WILL CNTY;4U
Adder
39.781
274675JOLIET 29;7U
Adder
43.621
274675JOLIET 29;7U
Adder
42.063
274728ELWOOD EC;5P
Adder
23.325
274731ELWOOD EC;2P
Adder
23.324
274733ELWOOD EC;3P
Adder
23.324
274735ELWOOD EC;4P
Adder
23.324
970833AG2-524 GEN
Solar/Wind Harmer
10.869
970833AG2-524 GEN
Solar/Wind Harmer
7.246
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274744AC1-111 GEN8
Adder
7.861
274746AC1-111 G10
Adder
7.861
24729505KEY G4
Adder
9.035
270578AF1-285 GEN2
Solar/Wind Harmer
0.647
970073AG2-061 GEN
Solar/Wind Harmer
3.208
971549AH1-272 GEN
Solar/Wind Harmer
19.814
965041AG1-368 GEN
Solar/Wind Harmer
9.581
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971411AH1-196 GEN
Solar/Wind Harmer
14.274
971675AH1-338 GEN
Solar/Wind Harmer
3.711
276861AD2-134 GEN
Solar/Wind Harmer
0.169
276863AD2-134 GEN
Solar/Wind Harmer
0.169
24386405FR-21G C
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
18.917
274823ROCKFORD ;21
Adder
26.328
970169AG2-114 GEN
Solar/Wind Harmer
9.398
247521TR3_G114
Solar/Wind Harmer
0.34
965051AG1-369 GEN
Solar/Wind Harmer
4.689
963791AG1-232 GEN
Solar/Wind Harmer
12.673
926823AC1-168 GEN
Solar/Wind Harmer
1.594
274856ECOGROVE ;U1
Solar/Wind Harmer
0.219
971681AH1-341 GEN
Solar/Wind Harmer
14.998
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.303
963841AG1-237 GEN
Solar/Wind Harmer
3.99
972267AH1-718 GEN
Adder
5.487
276741O09 GEN1
Solar/Wind Harmer
0.324
274877BISHOP HL;1U
Solar/Wind Harmer
0.305
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
9.573
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.153
970289AG2-191 GEN
Solar/Wind Harmer
1.719
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
5.01
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270007AE1-245 C
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
1.403
276668AB2-070 GEN1
Solar/Wind Harmer
0.336
276848AB2-070 GEN3
Solar/Wind Harmer
0.334
276849AB2-070 GEN2
Solar/Wind Harmer
0.336
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
3.17
944221AF1-090 GEN
Solar/Wind Harmer
4.619
247536S-71 GEN
Solar/Wind Harmer
0.309
270543AE2-219 C
Solar/Wind Harmer
5.183
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
10.57
270356AE2-297 GEN
Solar/Wind Harmer
0
24344105CKG2
50/50
12.076
270143AC1-141 CT2_
50/50
3.606
24639705ELKHART HY
50/50
0.243
970521AG2-332 GEN
50/50
17.34
24307105BERRINSP G
50/50
0.032
962761AG1-125 GEN
Solar/Wind Harmer
93.339
970149AG2-104 GEN
Solar/Wind Harmer
50.405
970155AG2-107 GEN
Solar/Wind Harmer
59.604
957891AF2-083 GEN
Solar/Wind Harmer
17.358
970373AG2-245 GEN
Solar/Wind Harmer
21.825
945111AF1-176 GEN
Solar/Wind Harmer
18.541
270449AD2-020 GEN
Solar/Wind Harmer
-0.001
943021AE2-325 GEN
Solar/Wind Harmer
5.398
270055AF2-134 C O1
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.002
274773LINCOLN ;4U
Adder
12.383
274774LINCOLN ;5U
Adder
12.383
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
13.304
965011AG1-365 GEN
Solar/Wind Harmer
10.2
274751CRETE EC ;1U
Adder
11.974
274754CRETE EC ;4U
Adder
11.974
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
12.669
274723RIVER EC ;12
Adder
26.022
274812UNIV PK N;8U
Adder
7.232
274802UNIV PARK;5U
Adder
8.371
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
43.62
274674JOLIET 9 ;6U
Adder
21.855
274732ELWOOD EC;7P
Adder
23.325
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
7.861
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.581
274861TOP CROP ;1U
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
24.977
274828WAUKEGAN ;BP
Adder
15.332
939401AE1-172 GEN
Solar/Wind Harmer
7.225
276805AD2-038 GEN
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
9.154
274872LEEDK;1U
Solar/Wind Harmer
0
270475AD2-096_GEN
50/50
9.997
270142AC1-141 CT1_
50/50
3.606
24642205MAYFLWER
50/50
0.055
944961AF1-161 GEN
50/50
4.308
962601AG1-109 GEN
50/50
4.308
962771AG1-126 GEN
Solar/Wind Harmer
93.339
970153AG2-106 GEN
Solar/Wind Harmer
59.604
270284AF1-227 GEN1
Solar/Wind Harmer
0
971347AH1-153 GEN
Solar/Wind Harmer
5.467
270043AE2-236 GEN
Solar/Wind Harmer
6.82
270505AE1-170 C O1
Solar/Wind Harmer
10.944
945111AF1-176 GEN
Solar/Wind Harmer
8.423
270063AE2-323 C
Solar/Wind Harmer
0.001
964401AG1-302 GEN
Solar/Wind Harmer
0.002
274772LINCOLN ;3U
Adder
12.383
965021AG1-366 GEN
Solar/Wind Harmer
3.4
274752CRETE EC ;2U
Adder
11.974
274753CRETE EC ;3U
Adder
11.974
274724RIVER EC ;11
Adder
25.717
274814UNIV PK N;0U
Adder
7.296
274807UNIV PK N;3U
Adder
7.28
274811UNIV PK N;7U
Adder
7.232
274803UNIV PARK;6U
Adder
8.371
274826FISK ;BP
Adder
15.709
970707AG2-453 GEN
Solar/Wind Harmer
32.686
274887GEN-1.85
Solar/Wind Harmer
0.26
276843GEN-1.7
Solar/Wind Harmer
0.323
276806AD2-047 C O1
Solar/Wind Harmer
5.669
972038AH1-567 GEN2
Adder
0.523
972259AH1-714 GEN
Adder
27.313
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
42.062
274730ELWOOD EC;6P
Adder
23.325
274734ELWOOD EC;8P
Adder
23.325
274736ELWOOD EC;9P
Adder
23.325
274729ELWOOD EC;1P
Adder
23.324
944531AF1-118 GEN
Solar/Wind Harmer
44.295
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
9.86
943121AE2-341 GEN
Solar/Wind Harmer
16.469
943591AF1-030 GEN
Solar/Wind Harmer
10.952
274862TOP CROP ;2U
Solar/Wind Harmer
1.313
270391AF1-285 GEN3
Solar/Wind Harmer
0.647
274682WAUKEGAN ;7U
Adder
24.977
276868AE1-113 GEN
Solar/Wind Harmer
1.916
274879MINONK ;1U
Solar/Wind Harmer
0.4
946671AF1-331 GEN
Solar/Wind Harmer
1.015
274855GSG-6 ;RU
Solar/Wind Harmer
0.347
274850MENDOTA H;RU
Solar/Wind Harmer
0.11
24386205FR-12G C
Solar/Wind Harmer
0
959091AF2-200 GEN
Solar/Wind Harmer
18.917
970571AG2-364 GEN
Solar/Wind Harmer
18.75
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
12.373
274767LEE CO EC;8U
Adder
12.227
247642Z2-115 C
Solar/Wind Harmer
0.004
24695305TIMB G C
Solar/Wind Harmer
0.78
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.305
246938BC-WTG3
Solar/Wind Harmer
0.328
270491AE1-102 GEN2
Solar/Wind Harmer
1.184
970289AG2-191 GEN
Solar/Wind Harmer
0.995
965091AG1-374 GEN
Solar/Wind Harmer
26.927
959611AF2-252 GEN
Solar/Wind Harmer
2.992
965931AG1-462 GEN
Solar/Wind Harmer
22.694
971087AG2-675 GEN
Solar/Wind Harmer
4.746
971993AH1-541 GEN
Solar/Wind Harmer
3.947
957381AF2-032 GEN
Solar/Wind Harmer
1.851
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
12.219
942481AE2-261 GEN
Solar/Wind Harmer
24.353
270004AE1-209 GEN
Solar/Wind Harmer
1.763
970825AG2-519 GEN
Solar/Wind Harmer
6.118
946031AF1-268 GEN
Solar/Wind Harmer
7.675
970193AG2-126 GEN
Solar/Wind Harmer
12.093
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
24728505AND G1
Adder
4.035
23906402RICHG1
Adder
1.058
23906502RICHG2&3
Adder
1.056
270541AE2-072 C
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
1.118
971997AH1-543 GEN
Solar/Wind Harmer
5.017
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
28.375
959081AF2-199 GEN
Solar/Wind Harmer
9.458
971067AG2-660 GEN
Solar/Wind Harmer
3.153
274822ROCKFORD ;11
Adder
26.521
970819AG2-516 GEN
Solar/Wind Harmer
11.253
970569AG2-363 GEN
Solar/Wind Harmer
28.125
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
12.373
274766LEE CO EC;7U
Adder
12.227
270317AD1-130_GEN
Solar/Wind Harmer
-0.001
965651AG1-433 GEN
Solar/Wind Harmer
2.714
965421AG1-410 GEN
Solar/Wind Harmer
27.632
276646AC1-214 GEN2
Solar/Wind Harmer
0.36
276708O09 GEN2
Solar/Wind Harmer
0.324
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
12.763
274848CAMPGROVE;RU
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.367
270489AE1-102 GEN1
Solar/Wind Harmer
1.184
958861AF2-177 GEN
Solar/Wind Harmer
3.944
963741AG1-226 GEN
Solar/Wind Harmer
21.176
270594AE1-207 GEN
Solar/Wind Harmer
9.873
270032AE2-172
Solar/Wind Harmer
5.877
945371AF1-202 GEN
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
9.571
276621W2-048 GEN
Solar/Wind Harmer
0.421
965911AG1-460 GEN
Solar/Wind Harmer
1.629
270005AE1-210 C O1
Solar/Wind Harmer
1.763
970825AG2-519 GEN
Solar/Wind Harmer
2.883
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.555
24728605AND G2
Adder
4.035
970773AG2-487 GEN
Solar/Wind Harmer
1.216
970091AG2-072 GEN
Adder
69.079
23906502RICHG2&3
Adder
1.056
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.539
NYPJM->LTFIMP_NY
CLTF
2.802
LGEELTFEXP_LGEE->PJM
CLTF
4.631
WECLTFEXP_WEC->PJM
CLTF
5.141
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.467
AG2-052LTFEXP_AG2-052->PJM
LTF
0.327
AH1-155LTFEXP_AH1-155->PJM
LTF
0.491
LAGNLTFEXP_LAGN->PJM
CLTF
11.508
TVALTFEXP_TVA->PJM
CLTF
4.677
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.087
CBM West 1LTFEXP_CBM-W1->PJM
CBM
165.647
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.96
MECLTFEXP_MEC->PJM
CLTF
19.157
SIGELTFEXP_SIGE->PJM
CLTF
0.435
CONTINGENCY 'AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 237805 TO BUS 237806 CKT 1   /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
 REMOVE SWSHUNT FROM BUS 237806 BLOCK 1 STEP 2           /*01ROCKYPOINT 765.0
END
CONTINGENCY 'AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 237805 TO BUS 237806 CKT 1   /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
 REMOVE SWSHUNT FROM BUS 237806 BLOCK 1 STEP 1           /*01ROCKYPOINT 765.0
END
CONTINGENCY 'AP_P1-2_PE-765-237805-237806_SRT-A_SENS'
 DISCONNECT BRANCH FROM BUS 237805 TO BUS 237806 CKT 1   /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
END
CONTINGENCY 'AP_P1-2_PE-765-242508-237805_SRT-A_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1   /*05AMOS       765.0 - 01WELTON_SPR 765.0
END
CONTINGENCY 'AEP_P4_#2942_05KAMMER 765_PP_SRT-A'
 OPEN BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242516 TO BUS 242920 CKT 1   /*05MOUNTN     765.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 OPEN BRANCH FROM BUS 242925 TO BUS 243188 CKT 1   /*05KAMMER     765.0 - 05MLG1        26.0
 REMOVE UNIT 1 FROM BUS 243188                     /*05MLG1        26.0
END
CONTINGENCY 'AEP_P4_#706_05GAVIN 765_C1_SRT-A'
 OPEN BRANCH FROM BUS 242922 TO BUS 290622 CKT 1    /*05FLTLCK     765.0 - 05GAVIN_RF   765.0
 OPEN BRANCH FROM BUS 242923 TO BUS 290622 CKT Z1   /*05GAVIN      765.0 - 05GAVIN_RF   765.0
END
CONTINGENCY 'AP_P2-3_MP-500-020_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 1          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 2          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5          /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1          /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1          /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                          /*05BELMON     765.0
 SET POSTCONTRATING 2492 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
 SET PRECONTRATING 1986 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AP_P2-3_MP-500-021_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 3          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5          /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1          /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1          /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                          /*05BELMON     765.0
 SET POSTCONTRATING 2492 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
 SET PRECONTRATING 1986 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AEP_P4_#37_05MOUNTN 765_B1_SRT-A'
 OPEN BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242516 TO BUS 242920 CKT 1   /*05MOUNTN     765.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
END
CONTINGENCY 'AP_P1-3_MP-765-501T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1   /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                   /*05BELMON     765.0
END
CONTINGENCY 'AEP_P1-2_#706_SRT-A'
 OPEN BRANCH FROM BUS 242922 TO BUS 290622 CKT 1    /*05FLTLCK     765.0 - 05GAVIN_RF   765.0
 OPEN BRANCH FROM BUS 242923 TO BUS 290622 CKT Z1   /*05GAVIN      765.0 - 05GAVIN_RF   765.0
END
CONTINGENCY 'ATSI_P7-1_TE-345-030_SRT-A'
 DISCONNECT BRANCH FROM BUS 239289 TO BUS 238569 CKT 1   /*02HAYES      345.0 - 02BEAVER     345.0
 DISCONNECT BRANCH FROM BUS 241877 TO BUS 238569 CKT 1   /*AC2-103 TAP  345.0 - 02BEAVER     345.0
END
CONTINGENCY 'ATSI_P7-1_TE-345-031_SRT-A'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 241877 CKT 1   /*02DAV-BE     345.0 - AC2-103 TAP  345.0
 DISCONNECT BRANCH FROM BUS 239289 TO BUS 238569 CKT 1   /*02HAYES      345.0 - 02BEAVER     345.0
END
CONTINGENCY 'AEP_P4_#ADKINS AG1125_SRT-A_SENS'
 OPEN BRANCH FROM BUS 962760 TO BUS 248125 CKT 1   /*AG1-125 TP   765.0 - 05ADKINS     765.0
END
CONTINGENCY 'AEP_P1-2_#AG1-125-ADKINS_SRT-A_SENS'
 OPEN BRANCH FROM BUS 962760 TO BUS 248125 CKT 1   /*AG1-125 TP   765.0 - 05ADKINS     765.0
END
290614 to 242515 ckt 1
290623 to 242925 ckt Z1
242928 to 290620 ckt Z1
290620 to 242926 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AEP_P4_#8975_05KAMMER 765_MM2_SRT-A
BreakerAC123.53 %3792.0B4684.3
22.21
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT7A_SRT-SL
BreakerAC123.51 %3792.0B4683.54
22.21
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT10A_SRT-SL
BreakerAC123.51 %3792.0B4683.44
22.29
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AP_P1-2_MP-500-028_SRT-A
SingleAC122.65 %3792.0B4650.99
16.38
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-502T_SRT-A
SingleAC122.64 %3792.0B4650.57
16.38
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AEP_P4_#8975_05KAMMER 765_MM2_SRT-A
BreakerAC139.19 %3792.0B5278.17
21.61
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT7A_SRT-SL
BreakerAC139.17 %3792.0B5277.43
21.61
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT10A_SRT-SL
BreakerAC138.98 %3792.0B5270.18
21.79
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-502T_SRT-A
SingleAC138.45 %3792.0B5250.02
15.94
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P1-2_MP-500-028_SRT-A
SingleAC138.41 %3792.0B5248.4
15.94
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-024_SRT-A
BreakerAC134.25 %3729.0B5006.21
25.33
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-025_SRT-A
BreakerAC133.4 %3729.0B4974.31
25.23
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-015_SRT-A
BreakerAC133.01 %3729.0B4959.97
25.21
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-014_SRT-A
BreakerAC133.01 %3729.0B4959.97
25.21
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P1-2_MP-500-007A_SRT-A
SingleAC131.87 %3729.0B4917.49
18.57
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-012_SRT-A
BreakerAC130.69 %3729.0B4873.53
25.23
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P1-2_MP-500-008A_SRT-SL
SingleAC124.24 %3729.0B4632.89
17.93
GD2AEP/AP
05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer
AEP_P4_#8975_05KAMMER 765_MM2_SRT-A
BreakerAC101.35 %4000.0B4053.82
23.73
GD2AEP/AP
05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer
AP_P2-3_WP-500-DRT10A_SRT-SL
BreakerAC101.34 %4000.0B4053.72
23.74
GD2AEP/AP
05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer
AP_P2-3_WP-500-DRT7A_SRT-SL
BreakerAC101.32 %4000.0B4052.99
23.73
GD2AEP/AP
05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer
AP_P1-2_MP-500-028_SRT-A
SingleAC100.79 %4000.0B4031.79
17.5
GD2AEP/AP
05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer
AP_P1-3_MP-765-502T_SRT-A
SingleAC100.79 %4000.0B4031.62
17.5
GD2AEP
05GAVIN-05MOUNTN 765.0 kV Ckt 1 line
AEP_P4_#8075_05MARYSV 765_A2_SRT-A
BreakerAC121.81 %4571.0B5567.74
72.73
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P4_#9728_05MALIS 138_L1_SRT-A
BreakerAC116.82 %1409.0B1646.06
12.9
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P4_#9730_05MALIS 138_P1_SRT-A
BreakerAC110.97 %1409.0B1563.59
12.87
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P4_#9729_05MALIS 138_M1_SRT-A
BreakerAC110.88 %1409.0B1562.23
12.87
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P4_#7222_05MALIS 765_D_SRT-A
BreakerAC105.36 %1409.0B1484.58
12.81
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
BusAC105.35 %1409.0B1484.33
12.81
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-024_SRT-A
BreakerAC135.56 %3792.0B5140.38
25.33
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-025_SRT-A
BreakerAC134.72 %3792.0B5108.61
25.23
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-014_SRT-A
BreakerAC134.34 %3792.0B5094.21
25.21
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-015_SRT-A
BreakerAC134.34 %3792.0B5094.21
25.21
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P1-2_MP-500-007A_SRT-A
SingleAC133.22 %3792.0B5051.83
18.57
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-012_SRT-A
BreakerAC132.01 %3792.0B5005.84
25.23
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P1-2_MP-500-008A_SRT-SL
SingleAC125.57 %3792.0B4761.71
17.93
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
BreakerAC133.37 %4142.0B5524.29
54.32
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
AP_P2-3_MP-500-020_SRT-SL
BreakerAC130.4 %4142.0B5401.24
54.51
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
AP_P2-3_MP-500-021_SRT-SL
BreakerAC130.35 %4142.0B5399.06
54.49
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
BreakerAC130.33 %4142.0B5398.09
54.48
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC127.9 %4142.0B5297.56
40.18
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
AEP_P4_#8085_05MARYSV 345_H_SRT-A
BreakerAC113.34 %4142.0B4694.66
61.68
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
AEP_P2-2_#8072_05MARYSV 765_2_SRT-A
BusAC112.49 %4142.0B4659.23
61.9
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
AEP_P1-2_#706_SRT-A
SingleAC108.0 %4142.0B4473.55
59.15
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
AEP_P7-1_#10944___SRT-A
TowerAC106.37 %4142.0B4405.9
50.08
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
ATSI_P7-1_TE-345-027A_SRT-A
TowerAC106.18 %4142.0B4397.83
50.44
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
AP_P2-2_WP-500-DRT14_SRT-SL
BusAC102.92 %4142.0B4263.07
49.91
GD2AEP
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
AEP_P4_#711_05MARYSV 765_A1_SRT-A
BreakerAC107.43 %3097.0B3327.22
48.32
GD2AEP
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
AEP_P4_#7222_05MALIS 765_D_SRT-A
BreakerAC107.32 %3097.0B3323.76
48.15
GD2AEP
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
BusAC107.32 %3097.0B3323.61
48.15
GD2AEP
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
AEP_P4_#9729_05MALIS 138_M1_SRT-A
BreakerAC107.26 %3097.0B3321.91
48.14
GD2AEP
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
AEP_P4_#9730_05MALIS 138_P1_SRT-A
BreakerAC107.26 %3097.0B3321.72
48.14
GD2AEP
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
AEP_P4_#9728_05MALIS 138_L1_SRT-A
BreakerAC107.23 %3097.0B3320.78
48.13
GD2AEP
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
AEP_P1-2_#711_6224_SRT-A
SingleAC101.73 %3097.0B3150.57
35.64
GD2AEP
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
AEP_P1-3_#7222_05MALIS 765_1_SRT-A
SingleAC101.63 %3097.0B3147.5
35.51
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
BreakerAC131.42 %4571.0B6007.36
59.0
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AP_P2-3_MP-500-020_SRT-SL
BreakerAC128.84 %4571.0B5889.34
59.16
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AP_P2-3_MP-500-021_SRT-SL
BreakerAC128.81 %4571.0B5888.09
59.15
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
BreakerAC128.8 %4571.0B5887.55
59.15
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC126.31 %4571.0B5773.71
43.62
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AEP_P4_#8085_05MARYSV 345_H_SRT-A
BreakerAC118.38 %4571.0B5411.14
69.03
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AEP_P2-2_#8072_05MARYSV 765_2_SRT-A
BusAC117.25 %4571.0B5359.3
69.35
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AEP_P1-3_#8072_05MARYSV 765_2_SRT-A
SingleAC111.01 %4571.0B5074.41
51.15
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Base Case
SingleAC110.62 %4047.0A4476.89
40.3
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AEP_P7-1_#10944___SRT-A
TowerAC109.61 %4571.0B5010.18
54.78
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
ATSI_P7-1_TE-345-027A_SRT-A
TowerAC108.08 %4571.0B4940.32
55.1
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AP_P2-2_WP-500-DRT14_SRT-SL
BusAC105.37 %4571.0B4816.67
54.59
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
BreakerAC131.44 %4571.0B6007.99
59.0
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AP_P2-3_MP-500-020_SRT-SL
BreakerAC128.87 %4571.0B5890.54
59.16
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AP_P2-3_MP-500-021_SRT-SL
BreakerAC128.84 %4571.0B5889.29
59.15
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
BreakerAC128.83 %4571.0B5888.74
59.15
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC126.34 %4571.0B5774.92
43.62
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AEP_P4_#8085_05MARYSV 345_H_SRT-A
BreakerAC118.61 %4571.0B5421.49
69.03
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AEP_P2-2_#8072_05MARYSV 765_2_SRT-A
BusAC117.48 %4571.0B5369.79
69.35
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AEP_P1-3_#8072_05MARYSV 765_2_SRT-A
SingleAC111.24 %4571.0B5084.88
51.15
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Base Case
SingleAC110.76 %4047.0A4482.29
40.3
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AEP_P7-1_#10944___SRT-A
TowerAC109.68 %4571.0B5013.66
54.78
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
ATSI_P7-1_TE-345-027A_SRT-A
TowerAC108.18 %4571.0B4944.72
55.1
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AP_P2-2_WP-500-DRT14_SRT-SL
BusAC105.46 %4571.0B4820.76
54.59
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#8075_05MARYSV 765_A2_SRT-A
BreakerAC119.32 %5523.0B6590.12
41.58
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#8980_05KAMMER 765_QQ2_SRT-A
BreakerAC117.27 %5523.0B6477.04
33.69
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P1-2_#17217_SRT-A
SingleAC116.4 %5523.0B6428.58
24.84
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#17219_05GUERNSEY 765_A_SRT-A
BreakerAC112.72 %5523.0B6225.55
33.97
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#7445_05MARYSV 765_B_SRT-A
BreakerAC111.96 %5523.0B6183.32
56.64
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Base Case
SingleAC109.18 %4558.0A4976.63
14.75
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
BreakerAC108.41 %5523.0B5987.66
23.47
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
BusAC107.46 %5523.0B5935.05
31.56
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC106.76 %5523.0B5896.19
17.31
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P7-1_#10944___SRT-A
TowerAC105.86 %5523.0B5846.6
20.26
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P7-1_#10856___SRT-A
TowerAC101.88 %5523.0B5626.94
20.51

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AEP_P4_#8975_05KAMMER 765_MM2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8975_05KAMMER 765_MM2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:123.53 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4684.3
MW Contribution:
22.21
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270459AD2-067 GEN
Solar/Wind Harmer
8.564
961821AG1-024 GEN
Solar/Wind Harmer
8.695
270291AC1-194 GEN
Solar/Wind Harmer
5.184
270432AC2-029 GEN
Solar/Wind Harmer
7.128
270263AC1-001 GEN
Solar/Wind Harmer
1.061
241955AC1-078 GEN
Solar/Wind Harmer
7.548
940611AE2-048 GEN
Solar/Wind Harmer
22.264
941391AE2-136 GEN
Solar/Wind Harmer
11.537
945631AF1-228 GEN
Solar/Wind Harmer
4.727
241973AD2-163_GEN1
Solar/Wind Harmer
1.986
241974AD2-163_GEN2
Solar/Wind Harmer
1.986
253338AC1-165 GEN
Solar/Wind Harmer
1.085
253343AC1-166 GEN
Solar/Wind Harmer
1.085
23559001PLEAS1
50/50
11.898
23562401OGROV2
50/50
2.273
24318805MLG1
50/50
6.603
24721905FLATG4
Adder
24.08
962771AG1-126 GEN
Solar/Wind Harmer
35.963
970153AG2-106 GEN
Solar/Wind Harmer
15.681
943861AF1-054 GEN
Solar/Wind Harmer
3.855
943851AF1-053 GEN
Solar/Wind Harmer
1.863
971985AH1-537 GEN
Solar/Wind Harmer
17.842
270340AC2-060 GEN
Solar/Wind Harmer
3.013
241972AD1-140 GEN
Solar/Wind Harmer
4.405
253406AD2-031_GEN
Solar/Wind Harmer
1.251
253433AC1-085 GEN1
Solar/Wind Harmer
5.175
253432AC1-085 GEN2
Solar/Wind Harmer
0.26
253372AE2-315 SEC3
Adder
1.842
253372AE2-315 SEC3
Adder
1.842
270223U2-072_GEN1
Solar/Wind Harmer
1.918
270224U2-072_GEN2
Solar/Wind Harmer
1.918
270227U2-072_GEN3
Solar/Wind Harmer
1.918
270228U2-072_GEN4
Solar/Wind Harmer
1.918
270231U2-072_GEN5
Solar/Wind Harmer
1.918
270578AF1-285 GEN2
Solar/Wind Harmer
0.452
25306009OHH W.
Adder
2.794
25196408WSDLE3
Adder
8.492
25196308WSDLE2
Adder
8.418
25196208WSDLE1
Adder
8.397
25196708WSDLE6
Adder
8.376
25196508WSDLE4
Adder
8.165
270302AB2-170 GEN
Solar/Wind Harmer
8.028
25196108MFTGT2
Adder
1.458
25196108MFTGT2
Adder
1.354
971029AG2-637 GEN
Solar/Wind Harmer
14.154
972163AH1-664 GEN
Solar/Wind Harmer
9.428
972165AH1-665 GEN
Solar/Wind Harmer
7.543
270543AE2-219 C
Solar/Wind Harmer
9.417
24729505KEY G4
Adder
6.101
247536S-71 GEN
Solar/Wind Harmer
3.803
958711AF2-162 GEN
Solar/Wind Harmer
0.951
945581AF1-223 GEN
Solar/Wind Harmer
4.258
961761AG1-017 GEN
Solar/Wind Harmer
0.401
964611AG1-324 GEN
Solar/Wind Harmer
3.657
270356AE2-297 GEN
Solar/Wind Harmer
4.321
270071AF1-092 GEN
Solar/Wind Harmer
14.041
970289AG2-191 GEN
Solar/Wind Harmer
1.776
963791AG1-232 GEN
Solar/Wind Harmer
12.58
959331AF2-224 GEN
Solar/Wind Harmer
9.303
247521TR3_G114
Solar/Wind Harmer
3.113
270191TR4_S_V150
Solar/Wind Harmer
2.777
965051AG1-369 GEN
Solar/Wind Harmer
4.624
965041AG1-368 GEN
Solar/Wind Harmer
9.252
957201AF2-014 GEN
Solar/Wind Harmer
4.187
270435AC2-044 GEN
Solar/Wind Harmer
1.847
274775LINCOLN ;6U
Adder
7.689
274776LINCOLN ;7U
Adder
7.689
274777LINCOLN ;8U
Adder
7.689
972037AH1-567 GEN1
Adder
0.166
972228AH1-698 GEN2
Adder
3.362
972227AH1-698 GEN1
Adder
2.368
274827FISK ;RP
Adder
7.042
274800UNIV PARK;3U
Adder
5.291
274801UNIV PARK;4U
Adder
5.291
274687WILL CNTY;4U
Adder
25.315
274687WILL CNTY;4U
Adder
25.315
274728ELWOOD EC;5P
Adder
14.887
274731ELWOOD EC;2P
Adder
14.887
274733ELWOOD EC;3P
Adder
14.887
274735ELWOOD EC;4P
Adder
14.887
274675JOLIET 29;7U
Adder
27.787
274675JOLIET 29;7U
Adder
26.795
274744AC1-111 GEN8
Adder
5.047
274746AC1-111 G10
Adder
5.047
23750701CROSSCHOOL
Solar/Wind Helper
1.372
238118U2-030_1
Solar/Wind Helper
0.32
23750501ELLIOTTS
Solar/Wind Helper
0.64
238169AE2-226 GEN1
Solar/Wind Helper
0.606
238170AE2-226 GEN2
Solar/Wind Helper
0.606
23779801AA1-109
Solar/Wind Helper
0.168
237025AB1-124 C
Solar/Wind Helper
0.143
237030AB1-096 C
Solar/Wind Helper
0.058
3138216PACIFIC
Solar/Wind Helper
0.038
23684101S70BUS1
50/50
0.295
24318905MLG2
50/50
4.819
270349AD2-093_GEN
Solar/Wind Harmer
3.759
270471AD2-092_GEN
Solar/Wind Harmer
3.759
270054AF2-122 C O1
Solar/Wind Harmer
3.36
927014AC1-188 GEN
Solar/Wind Harmer
1.627
946101AF1-275 GEN
Solar/Wind Harmer
1.548
971073AG2-665 GEN
Solar/Wind Harmer
8.168
970879AG2-548 GEN
Solar/Wind Harmer
1.187
270269AC2-059
Solar/Wind Harmer
9.486
253383AE2-342_GEN
Solar/Wind Harmer
0.888
942861AE2-305 GEN
Solar/Wind Harmer
7.811
24723005RIVRG1
Adder
18.772
24723105RIVRG2
Adder
18.772
253415AE1-040 GEN
Solar/Wind Harmer
1.12
962581AG1-107 GEN
Solar/Wind Harmer
4.922
961491AF2-440 GEN
Solar/Wind Harmer
2.045
25326109MON D
Adder
1.28
253370AE2-315 SEC1
Adder
1.947
25322209TAIT E
Adder
9.472
25322209TAIT E
Adder
9.26
938701AE1-092 GEN
Solar/Wind Harmer
20.019
25183208HLCRTG
Solar/Wind Harmer
5.858
972159AH1-661 GEN
Adder
0.966
252509AD1-136 GEN
Solar/Wind Harmer
0.247
253349AC2-067 GEN
Solar/Wind Harmer
1.965
253400AC2-068 GEN
Solar/Wind Harmer
0.79
253378AE2-206_GEN
Solar/Wind Harmer
3.461
25194408D.CRK1
Adder
7.279
25194508D.CRK3
Adder
1.361
270462AD2-086
Solar/Wind Harmer
6.668
25326509SID D
Adder
1.261
24728805RICHG1
Adder
3.564
24728905RICHG2
Adder
3.564
970883AG2-550 GEN
Solar/Wind Harmer
9.417
970885AG2-551 GEN
Solar/Wind Harmer
2.19
270383AD1-128 GEN
Solar/Wind Harmer
5.743
926881AC1-175 GEN
Solar/Wind Harmer
5.249
944541AF1-119 GEN
Solar/Wind Harmer
3.934
960971AF2-388 GEN
Solar/Wind Harmer
10.271
247621Y3-024
Adder
0.226
270201AC2-176 GEN
Solar/Wind Harmer
4.819
964611AG1-324 GEN
Solar/Wind Harmer
0.491
270031AE2-169
Solar/Wind Harmer
7.629
270599AE1-208 GEN
Solar/Wind Harmer
7.629
942221AE2-234 GEN
Solar/Wind Harmer
3.273
970291AG2-192 GEN
Solar/Wind Harmer
1.215
970291AG2-192 GEN
Solar/Wind Harmer
0.391
24725505WLD G2 C
Solar/Wind Harmer
3.711
24699105WLD G1 C
Solar/Wind Harmer
3.668
270246TR4_N_V150
Solar/Wind Harmer
0.788
270247TR4_N_V136
Solar/Wind Harmer
0.788
970349AG2-230 GEN
Solar/Wind Harmer
13.877
246937BC-WTG2
Solar/Wind Harmer
3.612
247620Y3-023
Adder
0.422
274770LINCOLN ;1U
Adder
7.689
274771LINCOLN ;2U
Adder
7.689
274805UNIV PK N;1U
Adder
4.563
274808UNIV PK N;4U
Adder
4.533
274674JOLIET 9 ;6U
Adder
13.943
274696ROCKY RD ;4P
Adder
10.261
274695ROCKY RD ;2P
Adder
10.024
274693ROCKY RD ;1P
Adder
9.926
274697ROCKY RD ;3P
Adder
2.723
23751201ROTHROCK
Solar/Wind Helper
0.855
23585401KL_K28_T16
Solar/Wind Helper
1.451
316097T157 G90
Solar/Wind Helper
1.331
235054AD2-180 GEN
Solar/Wind Helper
1.948
238117U2-030
Solar/Wind Helper
0.32
235531U2-073 GEN
Solar/Wind Helper
3.079
238147AE2-230_GEN1
Solar/Wind Helper
0.432
238148AE2-230_GEN2
Solar/Wind Helper
0.432
238149AF1-291A_GEN
Solar/Wind Helper
0.123
237061AD1-155 GEN
Solar/Wind Helper
1.53
235020AA1-095 C
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.238
237080AD1-060 GEN
Solar/Wind Helper
0.297
235062AE1-101 C1
Solar/Wind Helper
1.447
237006AB1-125 GEN
Solar/Wind Helper
0.107
316411AF1-147_GEN1
Solar/Wind Helper
0.762
945421AF1-207 GEN
Solar/Wind Harmer
9.897
23559101PLEAS2
50/50
11.898
23684201S70BUS2
50/50
0.3
23562301OGROV1
50/50
2.293
962761AG1-125 GEN
Solar/Wind Harmer
35.963
970149AG2-104 GEN
Solar/Wind Harmer
22.207
970155AG2-107 GEN
Solar/Wind Harmer
15.681
960001AF2-291 GEN
Solar/Wind Harmer
3.191
270510AE1-227 GEN1
Solar/Wind Harmer
2.61
270331AC1-082 GEN3
Solar/Wind Harmer
0.495
270520AE2-214 GEN
Solar/Wind Harmer
6.192
971073AG2-665 GEN
Solar/Wind Harmer
1.187
270273AD2-016 GEN
Solar/Wind Harmer
2.704
972203AH1-686 GEN
Adder
2.339
270286AF1-227 GEN2
Solar/Wind Harmer
2.112
24686505CER G6
Adder
8.358
253333AC1-068 GEN
Solar/Wind Harmer
1.046
24723205RIVRG3
Adder
18.772
972269AH1-719 GEN
Adder
2.288
253398AE2-221_GEN2
Solar/Wind Harmer
4.42
253316AC1-085 GEN3
Solar/Wind Harmer
8.153
946171AF1-282 GEN
Solar/Wind Harmer
9.738
253370AE2-315 SEC1
Adder
1.947
253371AE2-315 SEC2
Adder
1.842
270391AF1-285 GEN3
Solar/Wind Harmer
1.175
270578AF1-285 GEN2
Solar/Wind Harmer
1.175
25326309TAIT D
Adder
1.064
252516AE2-318_GEN
Solar/Wind Harmer
9.663
252510AF1-249 C
Solar/Wind Harmer
0.402
25194608D.CRK4
Adder
1.582
25196808ZIMRHP
Adder
72.791
270317AD1-130_GEN
Solar/Wind Harmer
3.069
270485AE1-090_GEN
Solar/Wind Harmer
0.58
270222AC2-111 GEN
Solar/Wind Harmer
4.248
944031AF1-071 GEN
Solar/Wind Harmer
0.956
25196008MFTGT1
Adder
1.323
945681AF1-233 GEN
Solar/Wind Harmer
17.8
971995AH1-542 GEN
Solar/Wind Harmer
10.357
942081AE2-220 GEN
Solar/Wind Harmer
6.014
270209AC1-174_GEN
Solar/Wind Harmer
3.827
270437AC2-090 C
Solar/Wind Harmer
5.249
270239V3-007_GEN1
Solar/Wind Harmer
1.618
965651AG1-433 GEN
Solar/Wind Harmer
5.136
958861AF2-177 GEN
Solar/Wind Harmer
10.268
945371AF1-202 GEN
Solar/Wind Harmer
6.551
270005AE1-210 C O1
Solar/Wind Harmer
5.125
970825AG2-519 GEN
Solar/Wind Harmer
1.966
270024AE2-089 GEN
Solar/Wind Harmer
4.385
270594AE1-207 GEN
Solar/Wind Harmer
12.702
270032AE2-172
Solar/Wind Harmer
4.35
970091AG2-072 GEN
Adder
71.643
276903AD2-071 C
Solar/Wind Harmer
9.334
965011AG1-365 GEN
Solar/Wind Harmer
9.303
965421AG1-410 GEN
Solar/Wind Harmer
27.72
246936BC-WTG1
Solar/Wind Harmer
3.612
270489AE1-102 GEN1
Solar/Wind Harmer
1.2
24728605AND G2
Adder
3.541
24639705ELKHART HY
Adder
0.141
274773LINCOLN ;4U
Adder
7.689
274774LINCOLN ;5U
Adder
7.689
274751CRETE EC ;1U
Adder
7.503
274754CRETE EC ;4U
Adder
7.503
274723RIVER EC ;12
Adder
16.309
274812UNIV PK N;8U
Adder
4.553
274802UNIV PARK;5U
Adder
5.293
274732ELWOOD EC;7P
Adder
14.887
274676JOLIET 29;8U
Adder
27.787
274674JOLIET 9 ;6U
Adder
13.943
274745AC1-111 GEN9
Adder
5.047
274682WAUKEGAN ;7U
Adder
1.991
23751101LEADS_P59
Solar/Wind Helper
2.413
23583801GRNGAP
Solar/Wind Helper
4.978
316095T157 G97
Solar/Wind Helper
1.331
238185AF2-356 C
Solar/Wind Helper
2.499
238120AE2-309 GEN
Solar/Wind Helper
0.489
238109AE1-109 GEN2
Solar/Wind Helper
0.103
238126S14_GEN_1
Solar/Wind Helper
0.769
23546401DTGZ2-030
Solar/Wind Helper
0.078
237085AD2-009_GEN
Solar/Wind Helper
1.438
235067AD1-061 GEN
Solar/Wind Helper
0.388
237038AE2-054 C
Solar/Wind Helper
0.237
237002AB1-128_GEN
Solar/Wind Helper
0.386
23777801MSM_W1-116
Solar/Wind Helper
0.1
270512AE1-227 GEN2
Solar/Wind Harmer
2.215
270330AC1-082 GEN2
Solar/Wind Harmer
0.494
270329AC1-082 GEN1
Solar/Wind Harmer
0.494
971191AH1-055 GEN
Solar/Wind Harmer
19.337
957541AF2-048 GEN
Solar/Wind Harmer
1.627
961921AG1-034 GEN
Solar/Wind Harmer
13.042
970879AG2-548 GEN
Solar/Wind Harmer
8.168
960801AF2-371 GEN
Solar/Wind Harmer
2.586
964871AG1-351 GEN
Solar/Wind Harmer
1.786
270284AF1-227 GEN1
Solar/Wind Harmer
5.709
270287AF1-227 GEN3
Solar/Wind Harmer
2.112
942051AE2-217 GEN
Solar/Wind Harmer
18.072
24686405CER G5
Adder
8.292
253325AC1-069 GEN
Solar/Wind Harmer
1.046
270518AE2-148 GEN
Solar/Wind Harmer
12.072
270367AC2-061_GEN
Solar/Wind Harmer
3.102
253394AE2-221_GEN
Solar/Wind Harmer
4.42
253317AC1-085 GEN4
Solar/Wind Harmer
8.153
946181AF1-283 GEN
Solar/Wind Harmer
12.659
253303V4-073 C
Solar/Wind Harmer
0.113
253370AE2-315 SEC1
Adder
1.947
253371AE2-315 SEC2
Adder
1.842
942871AE2-306 GEN
Solar/Wind Harmer
0.881
270391AF1-285 GEN3
Solar/Wind Harmer
0.452
270186AC1-089 GEN
Solar/Wind Harmer
5.927
960071AF2-298 GEN
Solar/Wind Harmer
1.467
252507AC2-088 GEN
Solar/Wind Harmer
1.731
252519AF1-045_GEN
Solar/Wind Harmer
3.517
276820AF1-078_GEN
Solar/Wind Harmer
1.537
252524AE2-267 GEN
Solar/Wind Harmer
1.516
25196608WSDLE5
Adder
8.25
25194608D.CRK4
Adder
1.582
25196008MFTGT1
Adder
1.281
972167AH1-666 GEN
Solar/Wind Harmer
7.557
958171AF2-111 GEN
Solar/Wind Harmer
23.611
944531AF1-118 GEN
Solar/Wind Harmer
32.926
24379505HDWTR1G C
Solar/Wind Harmer
7.436
270240V3-007_GEN2
Solar/Wind Harmer
5.818
270004AE1-209 GEN
Solar/Wind Harmer
5.125
962031AG1-047 GEN
Solar/Wind Harmer
2.835
957741AF2-068 GEN
Solar/Wind Harmer
14.065
946031AF1-268 GEN
Solar/Wind Harmer
7.782
970825AG2-519 GEN
Solar/Wind Harmer
5.279
965461AG1-414 GEN
Solar/Wind Harmer
2.119
970289AG2-191 GEN
Solar/Wind Harmer
0.717
247642Z2-115 C
Solar/Wind Harmer
0.06
270043AE2-236 GEN
Solar/Wind Harmer
5.125
965021AG1-366 GEN
Solar/Wind Harmer
2.164
971347AH1-153 GEN
Solar/Wind Harmer
4.626
246938BC-WTG3
Solar/Wind Harmer
3.674
270491AE1-102 GEN2
Solar/Wind Harmer
1.2
24728705AND G3
Adder
7.406
24728505AND G1
Adder
3.541
24695305TIMB G C
Solar/Wind Harmer
3.079
274772LINCOLN ;3U
Adder
7.689
274752CRETE EC ;2U
Adder
7.503
274753CRETE EC ;3U
Adder
7.503
274724RIVER EC ;11
Adder
16.119
274814UNIV PK N;0U
Adder
4.593
274807UNIV PK N;3U
Adder
4.583
274811UNIV PK N;7U
Adder
4.553
274803UNIV PARK;6U
Adder
5.293
274826FISK ;BP
Adder
9.937
972038AH1-567 GEN2
Adder
0.331
972259AH1-714 GEN
Adder
17.31
274729ELWOOD EC;1P
Adder
14.887
274730ELWOOD EC;6P
Adder
14.887
274734ELWOOD EC;8P
Adder
14.887
274736ELWOOD EC;9P
Adder
14.887
274676JOLIET 29;8U
Adder
26.795
274682WAUKEGAN ;7U
Adder
16.174
23562501BACKB
Solar/Wind Helper
1.049
964991AG1-363 GEN
Solar/Wind Helper
4.289
238108AE1-109 GEN1
Solar/Wind Helper
0.103
238110AE1-109 GEN3
Solar/Wind Helper
0.103
238127S14_GEN_2
Solar/Wind Helper
0.769
237048AF1-022 C
Solar/Wind Helper
0.176
238152AF2-075_GEN
Solar/Wind Helper
0.617
238175AF1-290_GEN
Solar/Wind Helper
0.135
23777901MDS_W4-102
Solar/Wind Helper
0.153
235063AE1-101 C2
Solar/Wind Helper
1.447
237001AB1-127_GEN
Solar/Wind Helper
0.384
316415AF1-147_GEN2
Solar/Wind Helper
0.762
CPLELTFEXP_CPLE->PJM
CLTF
1.222
CBM West 2LTFEXP_CBM-W2->PJM
CBM
104.659
NYPJM->LTFIMP_NY
CLTF
4.529
LGEELTFEXP_LGEE->PJM
CLTF
6.23
WECLTFEXP_WEC->PJM
CLTF
3.411
AG2-052LTFEXP_AG2-052->PJM
LTF
0.213
AH1-155LTFEXP_AH1-155->PJM
LTF
0.319
LAGNLTFEXP_LAGN->PJM
CLTF
14.046
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.869
TVALTFEXP_TVA->PJM
CLTF
6.974
CBM West 1LTFEXP_CBM-W1->PJM
CBM
125.509
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.61
MECLTFEXP_MEC->PJM
CLTF
14.364
SIGELTFEXP_SIGE->PJM
CLTF
0.464

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT7A_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT7A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:123.51 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4683.54
MW Contribution:
22.21
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23559001PLEAS1
50/50
11.898
23562401OGROV2
50/50
2.273
24318805MLG1
50/50
6.603
24721905FLATG4
Adder
24.08
962771AG1-126 GEN
Solar/Wind Harmer
35.963
970153AG2-106 GEN
Solar/Wind Harmer
15.681
270512AE1-227 GEN2
Solar/Wind Harmer
2.215
270330AC1-082 GEN2
Solar/Wind Harmer
0.494
270329AC1-082 GEN1
Solar/Wind Harmer
0.494
971191AH1-055 GEN
Solar/Wind Harmer
19.337
957541AF2-048 GEN
Solar/Wind Harmer
1.627
961921AG1-034 GEN
Solar/Wind Harmer
13.042
970879AG2-548 GEN
Solar/Wind Harmer
8.168
960801AF2-371 GEN
Solar/Wind Harmer
2.586
964871AG1-351 GEN
Solar/Wind Harmer
1.786
270284AF1-227 GEN1
Solar/Wind Harmer
5.709
270287AF1-227 GEN3
Solar/Wind Harmer
2.112
942051AE2-217 GEN
Solar/Wind Harmer
18.072
24686405CER G5
Adder
8.292
253325AC1-069 GEN
Solar/Wind Harmer
1.046
270518AE2-148 GEN
Solar/Wind Harmer
12.072
270367AC2-061_GEN
Solar/Wind Harmer
3.102
253394AE2-221_GEN
Solar/Wind Harmer
4.42
270459AD2-067 GEN
Solar/Wind Harmer
8.564
961821AG1-024 GEN
Solar/Wind Harmer
8.695
270291AC1-194 GEN
Solar/Wind Harmer
5.184
270432AC2-029 GEN
Solar/Wind Harmer
7.128
270263AC1-001 GEN
Solar/Wind Harmer
1.061
241955AC1-078 GEN
Solar/Wind Harmer
7.548
940611AE2-048 GEN
Solar/Wind Harmer
22.264
941391AE2-136 GEN
Solar/Wind Harmer
11.537
945631AF1-228 GEN
Solar/Wind Harmer
4.727
241973AD2-163_GEN1
Solar/Wind Harmer
1.986
241974AD2-163_GEN2
Solar/Wind Harmer
1.986
253338AC1-165 GEN
Solar/Wind Harmer
1.085
253343AC1-166 GEN
Solar/Wind Harmer
1.085
943861AF1-054 GEN
Solar/Wind Harmer
3.855
943851AF1-053 GEN
Solar/Wind Harmer
1.863
971985AH1-537 GEN
Solar/Wind Harmer
17.842
270340AC2-060 GEN
Solar/Wind Harmer
3.013
241972AD1-140 GEN
Solar/Wind Harmer
4.405
253406AD2-031_GEN
Solar/Wind Harmer
1.251
253433AC1-085 GEN1
Solar/Wind Harmer
5.175
253432AC1-085 GEN2
Solar/Wind Harmer
0.26
253372AE2-315 SEC3
Adder
1.842
253372AE2-315 SEC3
Adder
1.842
270223U2-072_GEN1
Solar/Wind Harmer
1.918
270224U2-072_GEN2
Solar/Wind Harmer
1.918
270227U2-072_GEN3
Solar/Wind Harmer
1.918
270228U2-072_GEN4
Solar/Wind Harmer
1.918
270231U2-072_GEN5
Solar/Wind Harmer
1.918
270578AF1-285 GEN2
Solar/Wind Harmer
0.452
25306009OHH W.
Adder
2.794
25196408WSDLE3
Adder
8.492
25196308WSDLE2
Adder
8.418
25196208WSDLE1
Adder
8.397
25196708WSDLE6
Adder
8.376
25196508WSDLE4
Adder
8.165
270302AB2-170 GEN
Solar/Wind Harmer
8.028
25196108MFTGT2
Adder
1.458
25196108MFTGT2
Adder
1.354
971029AG2-637 GEN
Solar/Wind Harmer
14.154
972163AH1-664 GEN
Solar/Wind Harmer
9.428
972165AH1-665 GEN
Solar/Wind Harmer
7.543
270543AE2-219 C
Solar/Wind Harmer
9.417
24729505KEY G4
Adder
6.101
247536S-71 GEN
Solar/Wind Harmer
3.803
958711AF2-162 GEN
Solar/Wind Harmer
0.951
945581AF1-223 GEN
Solar/Wind Harmer
4.258
961761AG1-017 GEN
Solar/Wind Harmer
0.401
964611AG1-324 GEN
Solar/Wind Harmer
3.657
270356AE2-297 GEN
Solar/Wind Harmer
4.321
270071AF1-092 GEN
Solar/Wind Harmer
14.041
970289AG2-191 GEN
Solar/Wind Harmer
1.776
963791AG1-232 GEN
Solar/Wind Harmer
12.58
959331AF2-224 GEN
Solar/Wind Harmer
9.303
247521TR3_G114
Solar/Wind Harmer
3.113
270191TR4_S_V150
Solar/Wind Harmer
2.777
965051AG1-369 GEN
Solar/Wind Harmer
4.624
965041AG1-368 GEN
Solar/Wind Harmer
9.252
957201AF2-014 GEN
Solar/Wind Harmer
4.187
270435AC2-044 GEN
Solar/Wind Harmer
1.847
274775LINCOLN ;6U
Adder
7.689
274776LINCOLN ;7U
Adder
7.689
274777LINCOLN ;8U
Adder
7.689
972037AH1-567 GEN1
Adder
0.166
972228AH1-698 GEN2
Adder
3.362
972227AH1-698 GEN1
Adder
2.368
274827FISK ;RP
Adder
7.042
274800UNIV PARK;3U
Adder
5.291
274801UNIV PARK;4U
Adder
5.291
274687WILL CNTY;4U
Adder
25.315
274687WILL CNTY;4U
Adder
25.315
274728ELWOOD EC;5P
Adder
14.887
274731ELWOOD EC;2P
Adder
14.887
274733ELWOOD EC;3P
Adder
14.887
274735ELWOOD EC;4P
Adder
14.887
274675JOLIET 29;7U
Adder
27.787
274675JOLIET 29;7U
Adder
26.795
274744AC1-111 GEN8
Adder
5.047
274746AC1-111 G10
Adder
5.047
23684101S70BUS1
50/50
0.295
24318905MLG2
50/50
4.819
270349AD2-093_GEN
Solar/Wind Harmer
3.759
270471AD2-092_GEN
Solar/Wind Harmer
3.759
270054AF2-122 C O1
Solar/Wind Harmer
3.36
927014AC1-188 GEN
Solar/Wind Harmer
1.627
946101AF1-275 GEN
Solar/Wind Harmer
1.548
971073AG2-665 GEN
Solar/Wind Harmer
8.168
970879AG2-548 GEN
Solar/Wind Harmer
1.187
270269AC2-059
Solar/Wind Harmer
9.486
253383AE2-342_GEN
Solar/Wind Harmer
0.888
942861AE2-305 GEN
Solar/Wind Harmer
7.811
24723005RIVRG1
Adder
18.772
24723105RIVRG2
Adder
18.772
253415AE1-040 GEN
Solar/Wind Harmer
1.12
962581AG1-107 GEN
Solar/Wind Harmer
4.922
961491AF2-440 GEN
Solar/Wind Harmer
2.045
25326109MON D
Adder
1.28
253370AE2-315 SEC1
Adder
1.947
25322209TAIT E
Adder
9.472
25322209TAIT E
Adder
9.26
938701AE1-092 GEN
Solar/Wind Harmer
20.019
25183208HLCRTG
Solar/Wind Harmer
5.858
972159AH1-661 GEN
Adder
0.966
252509AD1-136 GEN
Solar/Wind Harmer
0.247
253349AC2-067 GEN
Solar/Wind Harmer
1.965
253400AC2-068 GEN
Solar/Wind Harmer
0.79
253378AE2-206_GEN
Solar/Wind Harmer
3.461
25194408D.CRK1
Adder
7.279
25194508D.CRK3
Adder
1.361
270462AD2-086
Solar/Wind Harmer
6.668
25326509SID D
Adder
1.261
24728805RICHG1
Adder
3.564
24728905RICHG2
Adder
3.564
970883AG2-550 GEN
Solar/Wind Harmer
9.417
970885AG2-551 GEN
Solar/Wind Harmer
2.19
270383AD1-128 GEN
Solar/Wind Harmer
5.743
926881AC1-175 GEN
Solar/Wind Harmer
5.249
944541AF1-119 GEN
Solar/Wind Harmer
3.934
960971AF2-388 GEN
Solar/Wind Harmer
10.271
247621Y3-024
Adder
0.226
270201AC2-176 GEN
Solar/Wind Harmer
4.819
964611AG1-324 GEN
Solar/Wind Harmer
0.491
270031AE2-169
Solar/Wind Harmer
7.629
270599AE1-208 GEN
Solar/Wind Harmer
7.629
942221AE2-234 GEN
Solar/Wind Harmer
3.273
970291AG2-192 GEN
Solar/Wind Harmer
1.215
970291AG2-192 GEN
Solar/Wind Harmer
0.391
24725505WLD G2 C
Solar/Wind Harmer
3.711
24699105WLD G1 C
Solar/Wind Harmer
3.668
270246TR4_N_V150
Solar/Wind Harmer
0.788
270247TR4_N_V136
Solar/Wind Harmer
0.788
970349AG2-230 GEN
Solar/Wind Harmer
13.877
246937BC-WTG2
Solar/Wind Harmer
3.612
247620Y3-023
Adder
0.422
274770LINCOLN ;1U
Adder
7.689
274771LINCOLN ;2U
Adder
7.689
274805UNIV PK N;1U
Adder
4.563
274808UNIV PK N;4U
Adder
4.533
274674JOLIET 9 ;6U
Adder
13.943
274696ROCKY RD ;4P
Adder
10.261
274695ROCKY RD ;2P
Adder
10.024
274693ROCKY RD ;1P
Adder
9.926
274697ROCKY RD ;3P
Adder
2.723
23751201ROTHROCK
Solar/Wind Helper
0.855
23585401KL_K28_T16
Solar/Wind Helper
1.451
316097T157 G90
Solar/Wind Helper
1.331
235054AD2-180 GEN
Solar/Wind Helper
1.948
238117U2-030
Solar/Wind Helper
0.32
235531U2-073 GEN
Solar/Wind Helper
3.079
238147AE2-230_GEN1
Solar/Wind Helper
0.432
238148AE2-230_GEN2
Solar/Wind Helper
0.432
238149AF1-291A_GEN
Solar/Wind Helper
0.123
237061AD1-155 GEN
Solar/Wind Helper
1.53
235020AA1-095 C
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.238
237080AD1-060 GEN
Solar/Wind Helper
0.297
235062AE1-101 C1
Solar/Wind Helper
1.447
237006AB1-125 GEN
Solar/Wind Helper
0.107
316411AF1-147_GEN1
Solar/Wind Helper
0.762
945421AF1-207 GEN
Solar/Wind Harmer
9.897
253317AC1-085 GEN4
Solar/Wind Harmer
8.153
946181AF1-283 GEN
Solar/Wind Harmer
12.659
253303V4-073 C
Solar/Wind Harmer
0.113
253370AE2-315 SEC1
Adder
1.947
253371AE2-315 SEC2
Adder
1.842
942871AE2-306 GEN
Solar/Wind Harmer
0.881
270391AF1-285 GEN3
Solar/Wind Harmer
0.452
270186AC1-089 GEN
Solar/Wind Harmer
5.927
960071AF2-298 GEN
Solar/Wind Harmer
1.467
252507AC2-088 GEN
Solar/Wind Harmer
1.731
252519AF1-045_GEN
Solar/Wind Harmer
3.517
276820AF1-078_GEN
Solar/Wind Harmer
1.537
252524AE2-267 GEN
Solar/Wind Harmer
1.516
25196608WSDLE5
Adder
8.25
25194608D.CRK4
Adder
1.582
25196008MFTGT1
Adder
1.281
972167AH1-666 GEN
Solar/Wind Harmer
7.557
958171AF2-111 GEN
Solar/Wind Harmer
23.611
944531AF1-118 GEN
Solar/Wind Harmer
32.926
24379505HDWTR1G C
Solar/Wind Harmer
7.436
270240V3-007_GEN2
Solar/Wind Harmer
5.818
270004AE1-209 GEN
Solar/Wind Harmer
5.125
962031AG1-047 GEN
Solar/Wind Harmer
2.835
957741AF2-068 GEN
Solar/Wind Harmer
14.065
946031AF1-268 GEN
Solar/Wind Harmer
7.782
970825AG2-519 GEN
Solar/Wind Harmer
5.279
965461AG1-414 GEN
Solar/Wind Harmer
2.119
970289AG2-191 GEN
Solar/Wind Harmer
0.717
247642Z2-115 C
Solar/Wind Harmer
0.06
270043AE2-236 GEN
Solar/Wind Harmer
5.125
965021AG1-366 GEN
Solar/Wind Harmer
2.164
971347AH1-153 GEN
Solar/Wind Harmer
4.626
246938BC-WTG3
Solar/Wind Harmer
3.674
270491AE1-102 GEN2
Solar/Wind Harmer
1.2
24728705AND G3
Adder
7.406
24728505AND G1
Adder
3.541
24695305TIMB G C
Solar/Wind Harmer
3.079
274772LINCOLN ;3U
Adder
7.689
274752CRETE EC ;2U
Adder
7.503
23750701CROSSCHOOL
Solar/Wind Helper
1.372
238118U2-030_1
Solar/Wind Helper
0.32
23750501ELLIOTTS
Solar/Wind Helper
0.64
238169AE2-226 GEN1
Solar/Wind Helper
0.606
238170AE2-226 GEN2
Solar/Wind Helper
0.606
23779801AA1-109
Solar/Wind Helper
0.168
237025AB1-124 C
Solar/Wind Helper
0.143
237030AB1-096 C
Solar/Wind Helper
0.058
3138216PACIFIC
Solar/Wind Helper
0.038
274753CRETE EC ;3U
Adder
7.503
274724RIVER EC ;11
Adder
16.119
274814UNIV PK N;0U
Adder
4.593
274807UNIV PK N;3U
Adder
4.583
274811UNIV PK N;7U
Adder
4.553
274803UNIV PARK;6U
Adder
5.293
274826FISK ;BP
Adder
9.937
972038AH1-567 GEN2
Adder
0.331
972259AH1-714 GEN
Adder
17.31
274729ELWOOD EC;1P
Adder
14.887
274730ELWOOD EC;6P
Adder
14.887
274734ELWOOD EC;8P
Adder
14.887
274736ELWOOD EC;9P
Adder
14.887
274676JOLIET 29;8U
Adder
26.795
274682WAUKEGAN ;7U
Adder
16.174
23562501BACKB
Solar/Wind Helper
1.049
964991AG1-363 GEN
Solar/Wind Helper
4.289
238108AE1-109 GEN1
Solar/Wind Helper
0.103
238110AE1-109 GEN3
Solar/Wind Helper
0.103
238127S14_GEN_2
Solar/Wind Helper
0.769
237048AF1-022 C
Solar/Wind Helper
0.176
238152AF2-075_GEN
Solar/Wind Helper
0.617
238175AF1-290_GEN
Solar/Wind Helper
0.135
23777901MDS_W4-102
Solar/Wind Helper
0.153
235063AE1-101 C2
Solar/Wind Helper
1.447
237001AB1-127_GEN
Solar/Wind Helper
0.384
316415AF1-147_GEN2
Solar/Wind Helper
0.762
23559101PLEAS2
50/50
11.898
23684201S70BUS2
50/50
0.3
23562301OGROV1
50/50
2.293
962761AG1-125 GEN
Solar/Wind Harmer
35.963
970149AG2-104 GEN
Solar/Wind Harmer
22.207
970155AG2-107 GEN
Solar/Wind Harmer
15.681
960001AF2-291 GEN
Solar/Wind Harmer
3.191
270510AE1-227 GEN1
Solar/Wind Harmer
2.61
270331AC1-082 GEN3
Solar/Wind Harmer
0.495
270520AE2-214 GEN
Solar/Wind Harmer
6.192
971073AG2-665 GEN
Solar/Wind Harmer
1.187
270273AD2-016 GEN
Solar/Wind Harmer
2.704
972203AH1-686 GEN
Adder
2.339
270286AF1-227 GEN2
Solar/Wind Harmer
2.112
24686505CER G6
Adder
8.358
253333AC1-068 GEN
Solar/Wind Harmer
1.046
24723205RIVRG3
Adder
18.772
972269AH1-719 GEN
Adder
2.288
253398AE2-221_GEN2
Solar/Wind Harmer
4.42
253316AC1-085 GEN3
Solar/Wind Harmer
8.153
946171AF1-282 GEN
Solar/Wind Harmer
9.738
253370AE2-315 SEC1
Adder
1.947
253371AE2-315 SEC2
Adder
1.842
270391AF1-285 GEN3
Solar/Wind Harmer
1.175
270578AF1-285 GEN2
Solar/Wind Harmer
1.175
25326309TAIT D
Adder
1.064
252516AE2-318_GEN
Solar/Wind Harmer
9.663
252510AF1-249 C
Solar/Wind Harmer
0.402
25194608D.CRK4
Adder
1.582
25196808ZIMRHP
Adder
72.791
270317AD1-130_GEN
Solar/Wind Harmer
3.069
270485AE1-090_GEN
Solar/Wind Harmer
0.58
270222AC2-111 GEN
Solar/Wind Harmer
4.248
944031AF1-071 GEN
Solar/Wind Harmer
0.956
25196008MFTGT1
Adder
1.323
945681AF1-233 GEN
Solar/Wind Harmer
17.8
971995AH1-542 GEN
Solar/Wind Harmer
10.357
942081AE2-220 GEN
Solar/Wind Harmer
6.014
270209AC1-174_GEN
Solar/Wind Harmer
3.827
270437AC2-090 C
Solar/Wind Harmer
5.249
270239V3-007_GEN1
Solar/Wind Harmer
1.618
965651AG1-433 GEN
Solar/Wind Harmer
5.136
958861AF2-177 GEN
Solar/Wind Harmer
10.268
945371AF1-202 GEN
Solar/Wind Harmer
6.551
270005AE1-210 C O1
Solar/Wind Harmer
5.125
970825AG2-519 GEN
Solar/Wind Harmer
1.966
270024AE2-089 GEN
Solar/Wind Harmer
4.385
270594AE1-207 GEN
Solar/Wind Harmer
12.702
270032AE2-172
Solar/Wind Harmer
4.35
970091AG2-072 GEN
Adder
71.643
276903AD2-071 C
Solar/Wind Harmer
9.334
965011AG1-365 GEN
Solar/Wind Harmer
9.303
965421AG1-410 GEN
Solar/Wind Harmer
27.72
246936BC-WTG1
Solar/Wind Harmer
3.612
270489AE1-102 GEN1
Solar/Wind Harmer
1.2
24728605AND G2
Adder
3.541
24639705ELKHART HY
Adder
0.141
274773LINCOLN ;4U
Adder
7.689
274774LINCOLN ;5U
Adder
7.689
274751CRETE EC ;1U
Adder
7.503
274754CRETE EC ;4U
Adder
7.503
274723RIVER EC ;12
Adder
16.309
274812UNIV PK N;8U
Adder
4.553
274802UNIV PARK;5U
Adder
5.293
274732ELWOOD EC;7P
Adder
14.887
274676JOLIET 29;8U
Adder
27.787
274674JOLIET 9 ;6U
Adder
13.943
274745AC1-111 GEN9
Adder
5.047
274682WAUKEGAN ;7U
Adder
1.991
23751101LEADS_P59
Solar/Wind Helper
2.413
23583801GRNGAP
Solar/Wind Helper
4.978
316095T157 G97
Solar/Wind Helper
1.331
238185AF2-356 C
Solar/Wind Helper
2.499
238120AE2-309 GEN
Solar/Wind Helper
0.489
238109AE1-109 GEN2
Solar/Wind Helper
0.103
238126S14_GEN_1
Solar/Wind Helper
0.769
23546401DTGZ2-030
Solar/Wind Helper
0.078
237085AD2-009_GEN
Solar/Wind Helper
1.438
235067AD1-061 GEN
Solar/Wind Helper
0.388
237038AE2-054 C
Solar/Wind Helper
0.237
237002AB1-128_GEN
Solar/Wind Helper
0.386
23777801MSM_W1-116
Solar/Wind Helper
0.1
CPLELTFEXP_CPLE->PJM
CLTF
1.222
CBM West 2LTFEXP_CBM-W2->PJM
CBM
104.659
NYPJM->LTFIMP_NY
CLTF
4.529
LGEELTFEXP_LGEE->PJM
CLTF
6.23
WECLTFEXP_WEC->PJM
CLTF
3.411
AG2-052LTFEXP_AG2-052->PJM
LTF
0.213
AH1-155LTFEXP_AH1-155->PJM
LTF
0.319
LAGNLTFEXP_LAGN->PJM
CLTF
14.046
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.869
TVALTFEXP_TVA->PJM
CLTF
6.974
CBM West 1LTFEXP_CBM-W1->PJM
CBM
125.509
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.61
MECLTFEXP_MEC->PJM
CLTF
14.364
SIGELTFEXP_SIGE->PJM
CLTF
0.464

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT10A_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT10A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:123.51 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4683.44
MW Contribution:
22.29
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23684101S70BUS1
50/50
0.296
24318905MLG2
50/50
4.853
270349AD2-093_GEN
Solar/Wind Harmer
3.775
270471AD2-092_GEN
Solar/Wind Harmer
3.775
270054AF2-122 C O1
Solar/Wind Harmer
3.376
927014AC1-188 GEN
Solar/Wind Harmer
1.634
946101AF1-275 GEN
Solar/Wind Harmer
1.555
971073AG2-665 GEN
Solar/Wind Harmer
8.201
970879AG2-548 GEN
Solar/Wind Harmer
1.192
270269AC2-059
Solar/Wind Harmer
9.525
253383AE2-342_GEN
Solar/Wind Harmer
0.892
942861AE2-305 GEN
Solar/Wind Harmer
7.845
24723005RIVRG1
Adder
18.832
24723105RIVRG2
Adder
18.832
253415AE1-040 GEN
Solar/Wind Harmer
1.125
962581AG1-107 GEN
Solar/Wind Harmer
4.941
961491AF2-440 GEN
Solar/Wind Harmer
2.053
25326109MON D
Adder
1.285
253370AE2-315 SEC1
Adder
1.955
25322209TAIT E
Adder
9.512
25322209TAIT E
Adder
9.298
972159AH1-661 GEN
Adder
0.971
938701AE1-092 GEN
Solar/Wind Harmer
20.114
25183208HLCRTG
Solar/Wind Harmer
5.882
252509AD1-136 GEN
Solar/Wind Harmer
0.248
253349AC2-067 GEN
Solar/Wind Harmer
1.973
270459AD2-067 GEN
Solar/Wind Harmer
8.603
961821AG1-024 GEN
Solar/Wind Harmer
8.735
270291AC1-194 GEN
Solar/Wind Harmer
5.205
270432AC2-029 GEN
Solar/Wind Harmer
7.158
270263AC1-001 GEN
Solar/Wind Harmer
1.066
241955AC1-078 GEN
Solar/Wind Harmer
7.581
940611AE2-048 GEN
Solar/Wind Harmer
22.381
941391AE2-136 GEN
Solar/Wind Harmer
11.597
945631AF1-228 GEN
Solar/Wind Harmer
4.748
241973AD2-163_GEN1
Solar/Wind Harmer
1.995
241974AD2-163_GEN2
Solar/Wind Harmer
1.995
253338AC1-165 GEN
Solar/Wind Harmer
1.089
253343AC1-166 GEN
Solar/Wind Harmer
1.089
943861AF1-054 GEN
Solar/Wind Harmer
3.872
943851AF1-053 GEN
Solar/Wind Harmer
1.871
971985AH1-537 GEN
Solar/Wind Harmer
17.911
270340AC2-060 GEN
Solar/Wind Harmer
3.025
241972AD1-140 GEN
Solar/Wind Harmer
4.424
253406AD2-031_GEN
Solar/Wind Harmer
1.256
253433AC1-085 GEN1
Solar/Wind Harmer
5.195
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
253372AE2-315 SEC3
Adder
1.85
253372AE2-315 SEC3
Adder
1.85
270223U2-072_GEN1
Solar/Wind Harmer
1.927
270224U2-072_GEN2
Solar/Wind Harmer
1.927
270227U2-072_GEN3
Solar/Wind Harmer
1.927
270228U2-072_GEN4
Solar/Wind Harmer
1.927
270231U2-072_GEN5
Solar/Wind Harmer
1.927
270578AF1-285 GEN2
Solar/Wind Harmer
0.454
25306009OHH W.
Adder
2.806
25196408WSDLE3
Adder
8.526
25196308WSDLE2
Adder
8.452
25196208WSDLE1
Adder
8.431
25196708WSDLE6
Adder
8.409
25196508WSDLE4
Adder
8.198
270302AB2-170 GEN
Solar/Wind Harmer
8.066
25196108MFTGT2
Adder
1.464
25196108MFTGT2
Adder
1.359
971029AG2-637 GEN
Solar/Wind Harmer
14.212
253400AC2-068 GEN
Solar/Wind Harmer
0.793
253378AE2-206_GEN
Solar/Wind Harmer
3.476
25194408D.CRK1
Adder
7.308
25194508D.CRK3
Adder
1.366
270462AD2-086
Solar/Wind Harmer
6.699
25326509SID D
Adder
1.267
24728805RICHG1
Adder
3.578
24728905RICHG2
Adder
3.578
970883AG2-550 GEN
Solar/Wind Harmer
9.456
970885AG2-551 GEN
Solar/Wind Harmer
2.199
270383AD1-128 GEN
Solar/Wind Harmer
5.766
926881AC1-175 GEN
Solar/Wind Harmer
5.27
944541AF1-119 GEN
Solar/Wind Harmer
3.951
960971AF2-388 GEN
Solar/Wind Harmer
10.314
247621Y3-024
Adder
0.227
270201AC2-176 GEN
Solar/Wind Harmer
4.839
964611AG1-324 GEN
Solar/Wind Harmer
0.493
270031AE2-169
Solar/Wind Harmer
7.66
270599AE1-208 GEN
Solar/Wind Harmer
7.66
942221AE2-234 GEN
Solar/Wind Harmer
3.287
970291AG2-192 GEN
Solar/Wind Harmer
1.22
970291AG2-192 GEN
Solar/Wind Harmer
0.393
24725505WLD G2 C
Solar/Wind Harmer
3.726
24699105WLD G1 C
Solar/Wind Harmer
3.683
270246TR4_N_V150
Solar/Wind Harmer
0.791
270247TR4_N_V136
Solar/Wind Harmer
0.791
970349AG2-230 GEN
Solar/Wind Harmer
13.937
246937BC-WTG2
Solar/Wind Harmer
3.628
247620Y3-023
Adder
0.424
274770LINCOLN ;1U
Adder
7.721
274771LINCOLN ;2U
Adder
7.721
274805UNIV PK N;1U
Adder
4.582
274808UNIV PK N;4U
Adder
4.552
274674JOLIET 9 ;6U
Adder
14
274696ROCKY RD ;4P
Adder
10.303
274695ROCKY RD ;2P
Adder
10.065
274693ROCKY RD ;1P
Adder
9.966
274697ROCKY RD ;3P
Adder
2.734
316097T157 G90
Solar/Wind Helper
1.343
23751201ROTHROCK
Solar/Wind Helper
0.827
23585401KL_K28_T16
Solar/Wind Helper
1.409
235054AD2-180 GEN
Solar/Wind Helper
1.901
235531U2-073 GEN
Solar/Wind Helper
3.003
238117U2-030
Solar/Wind Helper
0.311
238147AE2-230_GEN1
Solar/Wind Helper
0.435
238148AE2-230_GEN2
Solar/Wind Helper
0.435
238149AF1-291A_GEN
Solar/Wind Helper
0.124
237061AD1-155 GEN
Solar/Wind Helper
1.542
235020AA1-095 C
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.239
237080AD1-060 GEN
Solar/Wind Helper
0.298
235062AE1-101 C1
Solar/Wind Helper
1.453
237006AB1-125 GEN
Solar/Wind Helper
0.108
316411AF1-147_GEN1
Solar/Wind Helper
0.768
972163AH1-664 GEN
Solar/Wind Harmer
9.464
972165AH1-665 GEN
Solar/Wind Harmer
7.571
270543AE2-219 C
Solar/Wind Harmer
9.456
24729505KEY G4
Adder
6.127
247536S-71 GEN
Solar/Wind Harmer
3.819
958711AF2-162 GEN
Solar/Wind Harmer
0.955
945581AF1-223 GEN
Solar/Wind Harmer
4.276
961761AG1-017 GEN
Solar/Wind Harmer
0.403
964611AG1-324 GEN
Solar/Wind Harmer
3.672
270356AE2-297 GEN
Solar/Wind Harmer
4.339
270071AF1-092 GEN
Solar/Wind Harmer
14.1
970289AG2-191 GEN
Solar/Wind Harmer
1.783
963791AG1-232 GEN
Solar/Wind Harmer
12.634
959331AF2-224 GEN
Solar/Wind Harmer
9.345
247521TR3_G114
Solar/Wind Harmer
3.127
270191TR4_S_V150
Solar/Wind Harmer
2.79
965051AG1-369 GEN
Solar/Wind Harmer
4.645
965041AG1-368 GEN
Solar/Wind Harmer
9.293
957201AF2-014 GEN
Solar/Wind Harmer
4.207
270435AC2-044 GEN
Solar/Wind Harmer
1.855
274775LINCOLN ;6U
Adder
7.721
274776LINCOLN ;7U
Adder
7.721
274777LINCOLN ;8U
Adder
7.721
972037AH1-567 GEN1
Adder
0.167
972228AH1-698 GEN2
Adder
3.376
972227AH1-698 GEN1
Adder
2.377
274827FISK ;RP
Adder
7.071
274800UNIV PARK;3U
Adder
5.313
274801UNIV PARK;4U
Adder
5.313
274687WILL CNTY;4U
Adder
25.419
274687WILL CNTY;4U
Adder
25.419
274728ELWOOD EC;5P
Adder
14.948
274731ELWOOD EC;2P
Adder
14.948
274733ELWOOD EC;3P
Adder
14.948
274735ELWOOD EC;4P
Adder
14.948
274675JOLIET 29;7U
Adder
27.901
274675JOLIET 29;7U
Adder
26.905
274744AC1-111 GEN8
Adder
5.067
274746AC1-111 G10
Adder
5.067
23750701CROSSCHOOL
Solar/Wind Helper
1.353
238118U2-030_1
Solar/Wind Helper
0.311
238169AE2-226 GEN1
Solar/Wind Helper
0.61
238170AE2-226 GEN2
Solar/Wind Helper
0.61
23750501ELLIOTTS
Solar/Wind Helper
0.612
23779801AA1-109
Solar/Wind Helper
0.169
3138216PACIFIC
Solar/Wind Helper
0.038
237025AB1-124 C
Solar/Wind Helper
0.144
237030AB1-096 C
Solar/Wind Helper
0.059
970031AG2-029 GEN
Solar/Wind Harmer
4.035
23559001PLEAS1
50/50
11.912
23562401OGROV2
50/50
2.283
24318805MLG1
50/50
6.628
24721905FLATG4
Adder
24.155
962771AG1-126 GEN
Solar/Wind Harmer
36.099
970153AG2-106 GEN
Solar/Wind Harmer
15.741
270512AE1-227 GEN2
Solar/Wind Harmer
2.229
270330AC1-082 GEN2
Solar/Wind Harmer
0.495
270329AC1-082 GEN1
Solar/Wind Harmer
0.495
971191AH1-055 GEN
Solar/Wind Harmer
19.41
957541AF2-048 GEN
Solar/Wind Harmer
1.634
961921AG1-034 GEN
Solar/Wind Harmer
13.102
970879AG2-548 GEN
Solar/Wind Harmer
8.201
960801AF2-371 GEN
Solar/Wind Harmer
2.597
964871AG1-351 GEN
Solar/Wind Harmer
1.793
270284AF1-227 GEN1
Solar/Wind Harmer
5.734
270287AF1-227 GEN3
Solar/Wind Harmer
2.121
942051AE2-217 GEN
Solar/Wind Harmer
18.15
24686405CER G5
Adder
8.32
253325AC1-069 GEN
Solar/Wind Harmer
1.051
270518AE2-148 GEN
Solar/Wind Harmer
12.124
270367AC2-061_GEN
Solar/Wind Harmer
3.114
253394AE2-221_GEN
Solar/Wind Harmer
4.438
253317AC1-085 GEN4
Solar/Wind Harmer
8.185
946181AF1-283 GEN
Solar/Wind Harmer
12.71
253303V4-073 C
Solar/Wind Harmer
0.113
253370AE2-315 SEC1
Adder
1.955
253371AE2-315 SEC2
Adder
1.85
942871AE2-306 GEN
Solar/Wind Harmer
0.885
270391AF1-285 GEN3
Solar/Wind Harmer
0.454
270186AC1-089 GEN
Solar/Wind Harmer
5.95
960071AF2-298 GEN
Solar/Wind Harmer
1.473
252507AC2-088 GEN
Solar/Wind Harmer
1.738
252519AF1-045_GEN
Solar/Wind Harmer
3.531
276820AF1-078_GEN
Solar/Wind Harmer
1.544
252524AE2-267 GEN
Solar/Wind Harmer
1.522
25196608WSDLE5
Adder
8.282
25194608D.CRK4
Adder
1.589
25196008MFTGT1
Adder
1.286
972167AH1-666 GEN
Solar/Wind Harmer
7.586
958171AF2-111 GEN
Solar/Wind Harmer
23.702
944531AF1-118 GEN
Solar/Wind Harmer
33.064
24379505HDWTR1G C
Solar/Wind Harmer
7.466
270240V3-007_GEN2
Solar/Wind Harmer
5.841
270004AE1-209 GEN
Solar/Wind Harmer
5.146
962031AG1-047 GEN
Solar/Wind Harmer
2.847
957741AF2-068 GEN
Solar/Wind Harmer
14.123
946031AF1-268 GEN
Solar/Wind Harmer
7.814
970825AG2-519 GEN
Solar/Wind Harmer
5.3
965461AG1-414 GEN
Solar/Wind Harmer
2.128
970289AG2-191 GEN
Solar/Wind Harmer
0.72
247642Z2-115 C
Solar/Wind Harmer
0.06
270043AE2-236 GEN
Solar/Wind Harmer
5.148
965021AG1-366 GEN
Solar/Wind Harmer
2.173
971347AH1-153 GEN
Solar/Wind Harmer
4.646
246938BC-WTG3
Solar/Wind Harmer
3.691
270491AE1-102 GEN2
Solar/Wind Harmer
1.206
24728705AND G3
Adder
7.436
24728505AND G1
Adder
3.555
24695305TIMB G C
Solar/Wind Harmer
3.093
958581AF2-149 GEN
Solar/Wind Harmer
3.962
971199AH1-059 GEN
Solar/Wind Harmer
1.944
274772LINCOLN ;3U
Adder
7.721
274752CRETE EC ;2U
Adder
7.534
274753CRETE EC ;3U
Adder
7.534
274724RIVER EC ;11
Adder
16.186
274814UNIV PK N;0U
Adder
4.612
274807UNIV PK N;3U
Adder
4.602
274811UNIV PK N;7U
Adder
4.572
274803UNIV PARK;6U
Adder
5.315
274826FISK ;BP
Adder
9.978
972038AH1-567 GEN2
Adder
0.333
972259AH1-714 GEN
Adder
17.382
274729ELWOOD EC;1P
Adder
14.948
274730ELWOOD EC;6P
Adder
14.948
274734ELWOOD EC;8P
Adder
14.948
274736ELWOOD EC;9P
Adder
14.948
274676JOLIET 29;8U
Adder
26.905
274682WAUKEGAN ;7U
Adder
16.24
964991AG1-363 GEN
Solar/Wind Helper
4.317
23562501BACKB
Solar/Wind Helper
1.016
238108AE1-109 GEN1
Solar/Wind Helper
0.102
238110AE1-109 GEN3
Solar/Wind Helper
0.102
238127S14_GEN_2
Solar/Wind Helper
0.755
238152AF2-075_GEN
Solar/Wind Helper
0.621
238175AF1-290_GEN
Solar/Wind Helper
0.135
23777901MDS_W4-102
Solar/Wind Helper
0.154
235063AE1-101 C2
Solar/Wind Helper
1.453
237001AB1-127_GEN
Solar/Wind Helper
0.386
316415AF1-147_GEN2
Solar/Wind Helper
0.768
237048AF1-022 C
Solar/Wind Helper
0.156
23559101PLEAS2
50/50
11.912
23684201S70BUS2
50/50
0.302
23562301OGROV1
50/50
2.303
962761AG1-125 GEN
Solar/Wind Harmer
36.099
970149AG2-104 GEN
Solar/Wind Harmer
22.291
970155AG2-107 GEN
Solar/Wind Harmer
15.741
270510AE1-227 GEN1
Solar/Wind Harmer
2.626
960001AF2-291 GEN
Solar/Wind Harmer
3.203
270331AC1-082 GEN3
Solar/Wind Harmer
0.497
270520AE2-214 GEN
Solar/Wind Harmer
6.219
971073AG2-665 GEN
Solar/Wind Harmer
1.192
270273AD2-016 GEN
Solar/Wind Harmer
2.715
972203AH1-686 GEN
Adder
2.346
270286AF1-227 GEN2
Solar/Wind Harmer
2.121
24686505CER G6
Adder
8.386
253333AC1-068 GEN
Solar/Wind Harmer
1.051
24723205RIVRG3
Adder
18.832
972269AH1-719 GEN
Adder
2.301
253398AE2-221_GEN2
Solar/Wind Harmer
4.438
253316AC1-085 GEN3
Solar/Wind Harmer
8.185
946171AF1-282 GEN
Solar/Wind Harmer
9.777
253370AE2-315 SEC1
Adder
1.955
253371AE2-315 SEC2
Adder
1.85
270391AF1-285 GEN3
Solar/Wind Harmer
1.18
270578AF1-285 GEN2
Solar/Wind Harmer
1.18
25326309TAIT D
Adder
1.069
252516AE2-318_GEN
Solar/Wind Harmer
9.702
252510AF1-249 C
Solar/Wind Harmer
0.403
25194608D.CRK4
Adder
1.589
270317AD1-130_GEN
Solar/Wind Harmer
3.084
270485AE1-090_GEN
Solar/Wind Harmer
0.583
25196808ZIMRHP
Adder
73.077
270222AC2-111 GEN
Solar/Wind Harmer
4.266
944031AF1-071 GEN
Solar/Wind Harmer
0.96
25196008MFTGT1
Adder
1.328
945681AF1-233 GEN
Solar/Wind Harmer
17.868
971995AH1-542 GEN
Solar/Wind Harmer
10.409
942081AE2-220 GEN
Solar/Wind Harmer
6.039
270209AC1-174_GEN
Solar/Wind Harmer
3.843
270437AC2-090 C
Solar/Wind Harmer
5.27
270239V3-007_GEN1
Solar/Wind Harmer
1.625
965651AG1-433 GEN
Solar/Wind Harmer
5.157
958861AF2-177 GEN
Solar/Wind Harmer
10.311
945371AF1-202 GEN
Solar/Wind Harmer
6.578
270005AE1-210 C O1
Solar/Wind Harmer
5.146
970825AG2-519 GEN
Solar/Wind Harmer
1.974
270024AE2-089 GEN
Solar/Wind Harmer
4.403
270594AE1-207 GEN
Solar/Wind Harmer
12.754
270032AE2-172
Solar/Wind Harmer
4.368
970091AG2-072 GEN
Adder
71.916
276903AD2-071 C
Solar/Wind Harmer
9.372
965011AG1-365 GEN
Solar/Wind Harmer
9.345
965421AG1-410 GEN
Solar/Wind Harmer
27.848
246936BC-WTG1
Solar/Wind Harmer
3.628
270489AE1-102 GEN1
Solar/Wind Harmer
1.206
24728605AND G2
Adder
3.555
24639705ELKHART HY
Adder
0.141
274773LINCOLN ;4U
Adder
7.721
274774LINCOLN ;5U
Adder
7.721
274751CRETE EC ;1U
Adder
7.534
274754CRETE EC ;4U
Adder
7.534
274723RIVER EC ;12
Adder
16.377
274812UNIV PK N;8U
Adder
4.572
274802UNIV PARK;5U
Adder
5.315
274732ELWOOD EC;7P
Adder
14.948
274676JOLIET 29;8U
Adder
27.901
274674JOLIET 9 ;6U
Adder
14
274745AC1-111 GEN9
Adder
5.067
274682WAUKEGAN ;7U
Adder
1.999
23751101LEADS_P59
Solar/Wind Helper
2.36
23583801GRNGAP
Solar/Wind Helper
5.023
316095T157 G97
Solar/Wind Helper
1.343
238185AF2-356 C
Solar/Wind Helper
2.448
238109AE1-109 GEN2
Solar/Wind Helper
0.102
238120AE2-309 GEN
Solar/Wind Helper
0.48
238126S14_GEN_1
Solar/Wind Helper
0.755
23546401DTGZ2-030
Solar/Wind Helper
0.078
237085AD2-009_GEN
Solar/Wind Helper
1.443
235067AD1-061 GEN
Solar/Wind Helper
0.39
237038AE2-054 C
Solar/Wind Helper
0.238
237002AB1-128_GEN
Solar/Wind Helper
0.387
23777801MSM_W1-116
Solar/Wind Helper
0.1
CPLELTFEXP_CPLE->PJM
CLTF
1.203
CBM West 2LTFEXP_CBM-W2->PJM
CBM
105.012
NYPJM->LTFIMP_NY
CLTF
4.537
LGEELTFEXP_LGEE->PJM
CLTF
6.253
WECLTFEXP_WEC->PJM
CLTF
3.425
AG2-052LTFEXP_AG2-052->PJM
LTF
0.214
AH1-155LTFEXP_AH1-155->PJM
LTF
0.32
LAGNLTFEXP_LAGN->PJM
CLTF
14.087
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.851
TVALTFEXP_TVA->PJM
CLTF
6.994
CBM West 1LTFEXP_CBM-W1->PJM
CBM
126.067
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.694
MECLTFEXP_MEC->PJM
CLTF
14.418
SIGELTFEXP_SIGE->PJM
CLTF
0.465

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-028_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:122.65 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4650.99
MW Contribution:
16.38
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23684101S70BUS1
50/50
0.295
24318905MLG2
50/50
4.819
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0
971073AG2-665 GEN
Solar/Wind Harmer
5.224
970879AG2-548 GEN
Solar/Wind Harmer
1.187
270269AC2-059
Solar/Wind Harmer
0.001
942861AE2-305 GEN
Solar/Wind Harmer
5.449
24723005RIVRG1
Adder
18.772
24723105RIVRG2
Adder
18.772
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25326109MON D
Adder
1.28
253370AE2-315 SEC1
Adder
1.947
25322209TAIT E
Adder
9.472
25322209TAIT E
Adder
9.26
938701AE1-092 GEN
Solar/Wind Harmer
10.862
971655AH1-328 GEN
Solar/Wind Harmer
2.4
25183208HLCRTG
Solar/Wind Harmer
0
972159AH1-661 GEN
Adder
0.966
252509AD1-136 GEN
Solar/Wind Harmer
0.034
970329AG2-216 GEN
Solar/Wind Harmer
2.902
25194408D.CRK1
Adder
7.279
25194508D.CRK3
Adder
1.361
270462AD2-086
Solar/Wind Harmer
0
25326509SID D
Adder
1.261
24728805RICHG1
Adder
3.564
24728905RICHG2
Adder
3.564
970883AG2-550 GEN
Solar/Wind Harmer
6.57
970885AG2-551 GEN
Solar/Wind Harmer
2.19
270383AD1-128 GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.438
960971AF2-388 GEN
Solar/Wind Harmer
3.846
247621Y3-024
Adder
0.226
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.491
270031AE2-169
Solar/Wind Harmer
3.592
270599AE1-208 GEN
Solar/Wind Harmer
5.986
942221AE2-234 GEN
Solar/Wind Harmer
2.621
971613AH1-306 GEN
Solar/Wind Harmer
3.132
970291AG2-192 GEN
Solar/Wind Harmer
0.848
970291AG2-192 GEN
Solar/Wind Harmer
0.391
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270246TR4_N_V150
Solar/Wind Harmer
0.041
270247TR4_N_V136
Solar/Wind Harmer
0.041
970349AG2-230 GEN
Solar/Wind Harmer
9.682
246937BC-WTG2
Solar/Wind Harmer
0.26
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.726
965681AG1-436 GEN
Solar/Wind Harmer
8.006
965791AG1-447 GEN
Solar/Wind Harmer
5.871
247607V1-011 GEN
Solar/Wind Harmer
0
247620Y3-023
Adder
0.422
972043AH1-570 GEN
Solar/Wind Harmer
1.663
972045AH1-571 GEN
Solar/Wind Harmer
1.333
970241AG2-163 GEN
Solar/Wind Harmer
3.722
961051AF2-396 GEN
Solar/Wind Harmer
12.733
961051AF2-396 GEN
Solar/Wind Harmer
8.489
274770LINCOLN ;1U
Adder
7.689
274771LINCOLN ;2U
Adder
7.689
971587AH1-292 GEN
Solar/Wind Harmer
4.656
970623AG2-406 GEN
Solar/Wind Harmer
1.161
274805UNIV PK N;1U
Adder
4.563
274808UNIV PK N;4U
Adder
4.533
274888KELLY CRK;1U
Solar/Wind Harmer
0.369
276776AD2-060 GEN
Solar/Wind Harmer
0.676
958011AF2-095 GEN
Solar/Wind Harmer
9.122
970941AG2-585 GEN
Solar/Wind Harmer
3.484
945391AF1-204 GEN
Solar/Wind Harmer
6.73
276897AD1-100 C
Solar/Wind Harmer
15.831
274674JOLIET 9 ;6U
Adder
13.943
276893AG1-478 C
Solar/Wind Harmer
0.421
971125AH1-004 GEN
Solar/Wind Harmer
2.523
970107AG2-081 GEN
Solar/Wind Harmer
1.892
23559101PLEAS2
50/50
11.898
23684201S70BUS2
50/50
0.3
23562301OGROV1
50/50
2.293
962761AG1-125 GEN
Solar/Wind Harmer
30.328
970149AG2-104 GEN
Solar/Wind Harmer
16.378
970155AG2-107 GEN
Solar/Wind Harmer
19.366
960001AF2-291 GEN
Solar/Wind Harmer
0
270510AE1-227 GEN1
Solar/Wind Harmer
1.881
270520AE2-214 GEN
Solar/Wind Harmer
0
971073AG2-665 GEN
Solar/Wind Harmer
1.187
270273AD2-016 GEN
Solar/Wind Harmer
0.726
972203AH1-686 GEN
Adder
2.339
24686505CER G6
Adder
8.358
253333AC1-068 GEN
Solar/Wind Harmer
0.008
24723205RIVRG3
Adder
18.772
972269AH1-719 GEN
Adder
2.288
253398AE2-221_GEN2
Solar/Wind Harmer
0
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.794
253370AE2-315 SEC1
Adder
1.947
253371AE2-315 SEC2
Adder
1.842
25326309TAIT D
Adder
1.064
252516AE2-318_GEN
Solar/Wind Harmer
7.551
252510AF1-249 C
Solar/Wind Harmer
0.051
25194608D.CRK4
Adder
1.582
25196808ZIMRHP
Adder
72.791
270317AD1-130_GEN
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.323
945681AF1-233 GEN
Solar/Wind Harmer
12.419
971995AH1-542 GEN
Solar/Wind Harmer
2.409
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.811
965651AG1-433 GEN
Solar/Wind Harmer
1.923
958861AF2-177 GEN
Solar/Wind Harmer
2.84
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.418
970773AG2-487 GEN
Solar/Wind Harmer
1.155
970825AG2-519 GEN
Solar/Wind Harmer
2.32
270024AE2-089 GEN
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
7.308
270032AE2-172
Solar/Wind Harmer
4.35
970091AG2-072 GEN
Adder
71.643
276903AD2-071 C
Solar/Wind Harmer
7.272
965011AG1-365 GEN
Solar/Wind Harmer
6.491
965421AG1-410 GEN
Solar/Wind Harmer
19.339
246936BC-WTG1
Solar/Wind Harmer
0.26
270489AE1-102 GEN1
Solar/Wind Harmer
0.837
24728605AND G2
Adder
3.541
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
8.034
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.351
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
13.48
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24639705ELKHART HY
Adder
0.141
963741AG1-226 GEN
Solar/Wind Harmer
15.1
957891AF2-083 GEN
Solar/Wind Harmer
10.629
945111AF1-176 GEN
Solar/Wind Harmer
11.377
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.32
274773LINCOLN ;4U
Adder
7.689
274774LINCOLN ;5U
Adder
7.689
274751CRETE EC ;1U
Adder
7.503
274754CRETE EC ;4U
Adder
7.503
274723RIVER EC ;12
Adder
16.309
274812UNIV PK N;8U
Adder
4.553
274802UNIV PARK;5U
Adder
5.293
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
14.887
274676JOLIET 29;8U
Adder
27.787
274674JOLIET 9 ;6U
Adder
13.943
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
4.718
944971AF1-162 GEN
Solar/Wind Harmer
6.303
274745AC1-111 GEN9
Adder
5.047
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.023
274861TOP CROP ;1U
Solar/Wind Harmer
0
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.246
270291AC1-194 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
3.15
270263AC1-001 GEN
Solar/Wind Harmer
0.709
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
940611AE2-048 GEN
Solar/Wind Harmer
17.38
941391AE2-136 GEN
Solar/Wind Harmer
9.79
945631AF1-228 GEN
Solar/Wind Harmer
0.001
943861AF1-054 GEN
Solar/Wind Harmer
2.69
276805AD2-038 GEN
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
1.991
971997AH1-543 GEN
Solar/Wind Harmer
3.293
958481AF2-142 GEN
Solar/Wind Harmer
9.443
943851AF1-053 GEN
Solar/Wind Harmer
1.863
971985AH1-537 GEN
Solar/Wind Harmer
2.075
270340AC2-060 GEN
Solar/Wind Harmer
0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.749
253406AD2-031_GEN
Solar/Wind Harmer
0.507
253372AE2-315 SEC3
Adder
1.842
253372AE2-315 SEC3
Adder
1.842
270578AF1-285 GEN2
Solar/Wind Harmer
0.452
25306009OHH W.
Adder
2.794
25196408WSDLE3
Adder
8.492
25196308WSDLE2
Adder
8.418
25196208WSDLE1
Adder
8.397
25196708WSDLE6
Adder
8.376
25196508WSDLE4
Adder
8.165
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.941
25196108MFTGT2
Adder
1.458
25196108MFTGT2
Adder
1.354
971029AG2-637 GEN
Solar/Wind Harmer
9.875
972163AH1-664 GEN
Solar/Wind Harmer
7.323
972165AH1-665 GEN
Solar/Wind Harmer
5.865
270543AE2-219 C
Solar/Wind Harmer
4.599
24729505KEY G4
Adder
6.101
247536S-71 GEN
Solar/Wind Harmer
0.262
945581AF1-223 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
2.551
270356AE2-297 GEN
Solar/Wind Harmer
0
270071AF1-092 GEN
Solar/Wind Harmer
12.517
971609AH1-304 GEN
Solar/Wind Harmer
1.067
970289AG2-191 GEN
Solar/Wind Harmer
1.239
963791AG1-232 GEN
Solar/Wind Harmer
8.777
959331AF2-224 GEN
Solar/Wind Harmer
4.543
247521TR3_G114
Solar/Wind Harmer
0.234
965051AG1-369 GEN
Solar/Wind Harmer
3.226
965041AG1-368 GEN
Solar/Wind Harmer
6.455
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.816
970031AG2-029 GEN
Solar/Wind Harmer
3.483
971611AH1-305 GEN
Solar/Wind Harmer
3.826
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
339216AC1-074 GEN
Solar/Wind Harmer
0.171
24386405FR-21G C
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0
971771AH1-392 GEN
Solar/Wind Harmer
6.4
270526AF1-158 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.771
274775LINCOLN ;6U
Adder
7.689
274776LINCOLN ;7U
Adder
7.689
274777LINCOLN ;8U
Adder
7.689
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.166
960591AF2-350 GEN
Solar/Wind Harmer
6.334
972228AH1-698 GEN2
Adder
3.362
972227AH1-698 GEN1
Adder
2.368
274827FISK ;RP
Adder
7.042
274800UNIV PARK;3U
Adder
5.291
274801UNIV PARK;4U
Adder
5.291
970179AG2-119 GEN
Solar/Wind Harmer
5.652
274687WILL CNTY;4U
Adder
25.315
274687WILL CNTY;4U
Adder
25.315
274728ELWOOD EC;5P
Adder
14.887
274731ELWOOD EC;2P
Adder
14.887
274733ELWOOD EC;3P
Adder
14.887
274735ELWOOD EC;4P
Adder
14.887
274675JOLIET 29;7U
Adder
27.787
274675JOLIET 29;7U
Adder
26.795
970833AG2-524 GEN
Solar/Wind Harmer
6.949
970833AG2-524 GEN
Solar/Wind Harmer
4.633
957241AF2-018 GEN
Solar/Wind Harmer
0
270053AF1-130 C
Solar/Wind Harmer
14.066
274744AC1-111 GEN8
Adder
5.047
274746AC1-111 G10
Adder
5.047
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970169AG2-114 GEN
Solar/Wind Harmer
6.285
970073AG2-061 GEN
Solar/Wind Harmer
2.094
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.578
926823AC1-168 GEN
Solar/Wind Harmer
1.063
274854TWINGROVE;U2
Solar/Wind Harmer
0
971675AH1-338 GEN
Solar/Wind Harmer
2.438
276861AD2-134 GEN
Solar/Wind Harmer
0.111
276863AD2-134 GEN
Solar/Wind Harmer
0.111
971411AH1-196 GEN
Solar/Wind Harmer
9.373
23750701CROSSCHOOL
Solar/Wind Helper
1.372
238118U2-030_1
Solar/Wind Helper
0.32
23750501ELLIOTTS
Solar/Wind Helper
0.64
238169AE2-226 GEN1
Solar/Wind Helper
0.606
944231AF1-091 GEN
Solar/Wind Harmer
14.516
276901AD2-066 C O1
Solar/Wind Harmer
0
274696ROCKY RD ;4P
Adder
10.261
274695ROCKY RD ;2P
Adder
10.024
274693ROCKY RD ;1P
Adder
9.926
274697ROCKY RD ;3P
Adder
2.723
958491AF2-143 GEN
Solar/Wind Harmer
9.422
962691AG1-118 GEN
Solar/Wind Harmer
18.812
942111AE2-223 GEN
Solar/Wind Harmer
2.036
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.083
970621AG2-405 GEN
Solar/Wind Harmer
1.144
23751201ROTHROCK
Solar/Wind Helper
0.855
23585401KL_K28_T16
Solar/Wind Helper
1.451
316097T157 G90
Solar/Wind Helper
1.331
235054AD2-180 GEN
Solar/Wind Helper
1.948
238117U2-030
Solar/Wind Helper
0.32
235531U2-073 GEN
Solar/Wind Helper
3.079
238147AE2-230_GEN1
Solar/Wind Helper
0.432
238148AE2-230_GEN2
Solar/Wind Helper
0.432
238149AF1-291A_GEN
Solar/Wind Helper
0.123
237061AD1-155 GEN
Solar/Wind Helper
1.53
235020AA1-095 C
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.238
237080AD1-060 GEN
Solar/Wind Helper
0.297
235062AE1-101 C1
Solar/Wind Helper
1.447
237006AB1-125 GEN
Solar/Wind Helper
0.107
316411AF1-147_GEN1
Solar/Wind Helper
0.762
971341AH1-150 GEN
Solar/Wind Harmer
3.185
971343AH1-151 GEN
Solar/Wind Harmer
3.185
238170AE2-226 GEN2
Solar/Wind Helper
0.606
23779801AA1-109
Solar/Wind Helper
0.168
237025AB1-124 C
Solar/Wind Helper
0.143
237030AB1-096 C
Solar/Wind Helper
0.058
3138216PACIFIC
Solar/Wind Helper
0.038
971171AH1-044 GEN
Solar/Wind Harmer
3.185
276882AE2-255 GEN
Solar/Wind Harmer
0.732
962781AG1-127 GEN
Solar/Wind Harmer
5.964
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
8.771
274872LEEDK;1U
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
18.746
23751101LEADS_P59
Solar/Wind Helper
2.413
23583801GRNGAP
Solar/Wind Helper
4.978
316095T157 G97
Solar/Wind Helper
1.331
238185AF2-356 C
Solar/Wind Helper
2.499
238120AE2-309 GEN
Solar/Wind Helper
0.489
238109AE1-109 GEN2
Solar/Wind Helper
0.103
238126S14_GEN_1
Solar/Wind Helper
0.769
23546401DTGZ2-030
Solar/Wind Helper
0.078
237085AD2-009_GEN
Solar/Wind Helper
1.438
235067AD1-061 GEN
Solar/Wind Helper
0.388
237038AE2-054 C
Solar/Wind Helper
0.237
237002AB1-128_GEN
Solar/Wind Helper
0.386
23777801MSM_W1-116
Solar/Wind Helper
0.1
957471AF2-041 GEN
Solar/Wind Harmer
4.778
959081AF2-199 GEN
Solar/Wind Harmer
1.593
971067AG2-660 GEN
Solar/Wind Harmer
0.531
23559001PLEAS1
50/50
11.898
23562401OGROV2
50/50
2.273
24318805MLG1
50/50
6.603
24721905FLATG4
Adder
24.08
962771AG1-126 GEN
Solar/Wind Harmer
30.328
970153AG2-106 GEN
Solar/Wind Harmer
19.366
270512AE1-227 GEN2
Solar/Wind Harmer
1.881
971191AH1-055 GEN
Solar/Wind Harmer
18.543
961921AG1-034 GEN
Solar/Wind Harmer
6.37
970879AG2-548 GEN
Solar/Wind Harmer
5.224
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
942051AE2-217 GEN
Solar/Wind Harmer
12.608
24686405CER G5
Adder
8.292
253325AC1-069 GEN
Solar/Wind Harmer
0.008
270518AE2-148 GEN
Solar/Wind Harmer
0.572
270367AC2-061_GEN
Solar/Wind Harmer
0
253394AE2-221_GEN
Solar/Wind Harmer
0
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.832
253370AE2-315 SEC1
Adder
1.947
253371AE2-315 SEC2
Adder
1.842
270391AF1-285 GEN3
Solar/Wind Harmer
0.452
270186AC1-089 GEN
Solar/Wind Harmer
0
252507AC2-088 GEN
Solar/Wind Harmer
0.304
252519AF1-045_GEN
Solar/Wind Harmer
3.517
970191AG2-125 GEN
Solar/Wind Harmer
1.734
25196608WSDLE5
Adder
8.25
25194608D.CRK4
Adder
1.582
25196008MFTGT1
Adder
1.281
972167AH1-666 GEN
Solar/Wind Harmer
5.273
958171AF2-111 GEN
Solar/Wind Harmer
16.473
944531AF1-118 GEN
Solar/Wind Harmer
29.414
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.418
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.813
946031AF1-268 GEN
Solar/Wind Harmer
6.225
970825AG2-519 GEN
Solar/Wind Harmer
4.924
970289AG2-191 GEN
Solar/Wind Harmer
0.717
247642Z2-115 C
Solar/Wind Harmer
0.003
270043AE2-236 GEN
Solar/Wind Harmer
4.172
965021AG1-366 GEN
Solar/Wind Harmer
2.164
971347AH1-153 GEN
Solar/Wind Harmer
3.227
246938BC-WTG3
Solar/Wind Harmer
0.232
270491AE1-102 GEN2
Solar/Wind Harmer
0.837
24728705AND G3
Adder
7.406
24728505AND G1
Adder
3.541
24695305TIMB G C
Solar/Wind Harmer
0.545
971199AH1-059 GEN
Solar/Wind Harmer
1.349
24690905MDL-1G C
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.424
270063AE2-323 C
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
5.168
270505AE1-170 C O1
Solar/Wind Harmer
6.695
274772LINCOLN ;3U
Adder
7.689
274752CRETE EC ;2U
Adder
7.503
274753CRETE EC ;3U
Adder
7.503
274724RIVER EC ;11
Adder
16.119
274814UNIV PK N;0U
Adder
4.593
274807UNIV PK N;3U
Adder
4.583
274811UNIV PK N;7U
Adder
4.553
274803UNIV PARK;6U
Adder
5.293
274887GEN-1.85
Solar/Wind Harmer
0.165
276843GEN-1.7
Solar/Wind Harmer
0.205
276806AD2-047 C O1
Solar/Wind Harmer
3.589
970193AG2-126 GEN
Solar/Wind Harmer
9.501
274826FISK ;BP
Adder
9.937
972038AH1-567 GEN2
Adder
0.331
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
20.679
972259AH1-714 GEN
Adder
17.31
274729ELWOOD EC;1P
Adder
14.887
274730ELWOOD EC;6P
Adder
14.887
274734ELWOOD EC;8P
Adder
14.887
274736ELWOOD EC;9P
Adder
14.887
274676JOLIET 29;8U
Adder
26.795
943121AE2-341 GEN
Solar/Wind Harmer
10.564
943591AF1-030 GEN
Solar/Wind Harmer
7.025
274862TOP CROP ;2U
Solar/Wind Harmer
0.85
274682WAUKEGAN ;7U
Adder
16.174
276868AE1-113 GEN
Solar/Wind Harmer
1.255
274879MINONK ;1U
Solar/Wind Harmer
0.262
946671AF1-331 GEN
Solar/Wind Harmer
0.667
965091AG1-374 GEN
Solar/Wind Harmer
18.751
959611AF2-252 GEN
Solar/Wind Harmer
2.083
274855GSG-6 ;RU
Solar/Wind Harmer
0.228
274850MENDOTA H;RU
Solar/Wind Harmer
0.073
970571AG2-364 GEN
Solar/Wind Harmer
12.497
270588AE1-091_GEN
Solar/Wind Harmer
4.882
23562501BACKB
Solar/Wind Helper
1.049
964991AG1-363 GEN
Solar/Wind Helper
4.289
238108AE1-109 GEN1
Solar/Wind Helper
0.103
238110AE1-109 GEN3
Solar/Wind Helper
0.103
238127S14_GEN_2
Solar/Wind Helper
0.769
237048AF1-022 C
Solar/Wind Helper
0.176
238152AF2-075_GEN
Solar/Wind Helper
0.617
238175AF1-290_GEN
Solar/Wind Helper
0.135
23777901MDS_W4-102
Solar/Wind Helper
0.153
235063AE1-101 C2
Solar/Wind Helper
1.447
237001AB1-127_GEN
Solar/Wind Helper
0.384
316415AF1-147_GEN2
Solar/Wind Helper
0.762
959091AF2-200 GEN
Solar/Wind Harmer
3.185
CPLELTFEXP_CPLE->PJM
CLTF
1.222
CBM West 2LTFEXP_CBM-W2->PJM
CBM
104.659
NYPJM->LTFIMP_NY
CLTF
4.529
LGEELTFEXP_LGEE->PJM
CLTF
6.23
WECLTFEXP_WEC->PJM
CLTF
3.411
AG2-052LTFEXP_AG2-052->PJM
LTF
0.213
AH1-155LTFEXP_AH1-155->PJM
LTF
0.319
LAGNLTFEXP_LAGN->PJM
CLTF
14.046
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.869
TVALTFEXP_TVA->PJM
CLTF
6.974
CBM West 1LTFEXP_CBM-W1->PJM
CBM
125.509
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.61
MECLTFEXP_MEC->PJM
CLTF
14.364
SIGELTFEXP_SIGE->PJM
CLTF
0.464

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-502T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-502T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:122.64 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4650.57
MW Contribution:
16.38
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.246
270291AC1-194 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
3.15
270263AC1-001 GEN
Solar/Wind Harmer
0.709
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
940611AE2-048 GEN
Solar/Wind Harmer
17.38
941391AE2-136 GEN
Solar/Wind Harmer
9.79
945631AF1-228 GEN
Solar/Wind Harmer
0.001
943861AF1-054 GEN
Solar/Wind Harmer
2.69
943851AF1-053 GEN
Solar/Wind Harmer
1.863
971985AH1-537 GEN
Solar/Wind Harmer
2.075
270340AC2-060 GEN
Solar/Wind Harmer
0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.749
253406AD2-031_GEN
Solar/Wind Harmer
0.507
253372AE2-315 SEC3
Adder
1.842
253372AE2-315 SEC3
Adder
1.842
270578AF1-285 GEN2
Solar/Wind Harmer
0.452
25306009OHH W.
Adder
2.794
25196408WSDLE3
Adder
8.492
25196308WSDLE2
Adder
8.418
25196208WSDLE1
Adder
8.397
25196708WSDLE6
Adder
8.376
25196508WSDLE4
Adder
8.165
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.941
25196108MFTGT2
Adder
1.458
25196108MFTGT2
Adder
1.354
971029AG2-637 GEN
Solar/Wind Harmer
9.875
972163AH1-664 GEN
Solar/Wind Harmer
7.323
972165AH1-665 GEN
Solar/Wind Harmer
5.865
270543AE2-219 C
Solar/Wind Harmer
4.599
24729505KEY G4
Adder
6.101
247536S-71 GEN
Solar/Wind Harmer
0.262
945581AF1-223 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
2.551
270356AE2-297 GEN
Solar/Wind Harmer
0
270071AF1-092 GEN
Solar/Wind Harmer
12.517
971609AH1-304 GEN
Solar/Wind Harmer
1.067
970289AG2-191 GEN
Solar/Wind Harmer
1.239
963791AG1-232 GEN
Solar/Wind Harmer
8.777
959331AF2-224 GEN
Solar/Wind Harmer
4.543
247521TR3_G114
Solar/Wind Harmer
0.234
965051AG1-369 GEN
Solar/Wind Harmer
3.226
965041AG1-368 GEN
Solar/Wind Harmer
6.455
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.816
970031AG2-029 GEN
Solar/Wind Harmer
3.483
971611AH1-305 GEN
Solar/Wind Harmer
3.826
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
339216AC1-074 GEN
Solar/Wind Harmer
0.171
24386405FR-21G C
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0
971771AH1-392 GEN
Solar/Wind Harmer
6.4
270526AF1-158 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.771
274775LINCOLN ;6U
Adder
7.689
274776LINCOLN ;7U
Adder
7.689
274777LINCOLN ;8U
Adder
7.689
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.166
960591AF2-350 GEN
Solar/Wind Harmer
6.334
972228AH1-698 GEN2
Adder
3.362
972227AH1-698 GEN1
Adder
2.368
274827FISK ;RP
Adder
7.042
274800UNIV PARK;3U
Adder
5.291
274801UNIV PARK;4U
Adder
5.291
970179AG2-119 GEN
Solar/Wind Harmer
5.652
274687WILL CNTY;4U
Adder
25.315
274687WILL CNTY;4U
Adder
25.315
274728ELWOOD EC;5P
Adder
14.887
274731ELWOOD EC;2P
Adder
14.887
274733ELWOOD EC;3P
Adder
14.887
274735ELWOOD EC;4P
Adder
14.887
274675JOLIET 29;7U
Adder
27.787
274675JOLIET 29;7U
Adder
26.795
970833AG2-524 GEN
Solar/Wind Harmer
6.949
970833AG2-524 GEN
Solar/Wind Harmer
4.633
957241AF2-018 GEN
Solar/Wind Harmer
0
270053AF1-130 C
Solar/Wind Harmer
14.066
274744AC1-111 GEN8
Adder
5.047
274746AC1-111 G10
Adder
5.047
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970169AG2-114 GEN
Solar/Wind Harmer
6.285
970073AG2-061 GEN
Solar/Wind Harmer
2.094
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.578
926823AC1-168 GEN
Solar/Wind Harmer
1.063
274854TWINGROVE;U2
Solar/Wind Harmer
0
971675AH1-338 GEN
Solar/Wind Harmer
2.438
276861AD2-134 GEN
Solar/Wind Harmer
0.111
276863AD2-134 GEN
Solar/Wind Harmer
0.111
971411AH1-196 GEN
Solar/Wind Harmer
9.373
23750701CROSSCHOOL
Solar/Wind Helper
1.372
23684101S70BUS1
50/50
0.295
24318905MLG2
50/50
4.819
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0
971073AG2-665 GEN
Solar/Wind Harmer
5.224
970879AG2-548 GEN
Solar/Wind Harmer
1.187
270269AC2-059
Solar/Wind Harmer
0.001
942861AE2-305 GEN
Solar/Wind Harmer
5.449
24723005RIVRG1
Adder
18.772
24723105RIVRG2
Adder
18.772
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25326109MON D
Adder
1.28
253370AE2-315 SEC1
Adder
1.947
25322209TAIT E
Adder
9.472
25322209TAIT E
Adder
9.26
938701AE1-092 GEN
Solar/Wind Harmer
10.862
971655AH1-328 GEN
Solar/Wind Harmer
2.4
25183208HLCRTG
Solar/Wind Harmer
0
972159AH1-661 GEN
Adder
0.966
252509AD1-136 GEN
Solar/Wind Harmer
0.034
970329AG2-216 GEN
Solar/Wind Harmer
2.902
25194408D.CRK1
Adder
7.279
25194508D.CRK3
Adder
1.361
270462AD2-086
Solar/Wind Harmer
0
25326509SID D
Adder
1.261
24728805RICHG1
Adder
3.564
24728905RICHG2
Adder
3.564
970883AG2-550 GEN
Solar/Wind Harmer
6.57
970885AG2-551 GEN
Solar/Wind Harmer
2.19
270383AD1-128 GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.438
960971AF2-388 GEN
Solar/Wind Harmer
3.846
247621Y3-024
Adder
0.226
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.491
270031AE2-169
Solar/Wind Harmer
3.592
270599AE1-208 GEN
Solar/Wind Harmer
5.986
942221AE2-234 GEN
Solar/Wind Harmer
2.621
971613AH1-306 GEN
Solar/Wind Harmer
3.132
970291AG2-192 GEN
Solar/Wind Harmer
0.848
970291AG2-192 GEN
Solar/Wind Harmer
0.391
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270246TR4_N_V150
Solar/Wind Harmer
0.041
270247TR4_N_V136
Solar/Wind Harmer
0.041
970349AG2-230 GEN
Solar/Wind Harmer
9.682
246937BC-WTG2
Solar/Wind Harmer
0.26
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.726
965681AG1-436 GEN
Solar/Wind Harmer
8.006
965791AG1-447 GEN
Solar/Wind Harmer
5.871
247607V1-011 GEN
Solar/Wind Harmer
0
247620Y3-023
Adder
0.422
972043AH1-570 GEN
Solar/Wind Harmer
1.663
972045AH1-571 GEN
Solar/Wind Harmer
1.333
970241AG2-163 GEN
Solar/Wind Harmer
3.722
961051AF2-396 GEN
Solar/Wind Harmer
12.733
961051AF2-396 GEN
Solar/Wind Harmer
8.489
274770LINCOLN ;1U
Adder
7.689
274771LINCOLN ;2U
Adder
7.689
971587AH1-292 GEN
Solar/Wind Harmer
4.656
970623AG2-406 GEN
Solar/Wind Harmer
1.161
274805UNIV PK N;1U
Adder
4.563
274808UNIV PK N;4U
Adder
4.533
274888KELLY CRK;1U
Solar/Wind Harmer
0.369
276776AD2-060 GEN
Solar/Wind Harmer
0.676
958011AF2-095 GEN
Solar/Wind Harmer
9.122
970941AG2-585 GEN
Solar/Wind Harmer
3.484
945391AF1-204 GEN
Solar/Wind Harmer
6.73
276897AD1-100 C
Solar/Wind Harmer
15.831
274674JOLIET 9 ;6U
Adder
13.943
276893AG1-478 C
Solar/Wind Harmer
0.421
971125AH1-004 GEN
Solar/Wind Harmer
2.523
970107AG2-081 GEN
Solar/Wind Harmer
1.892
958481AF2-142 GEN
Solar/Wind Harmer
9.443
944231AF1-091 GEN
Solar/Wind Harmer
14.516
276901AD2-066 C O1
Solar/Wind Harmer
0
274696ROCKY RD ;4P
Adder
10.261
274695ROCKY RD ;2P
Adder
10.024
274693ROCKY RD ;1P
Adder
9.926
274697ROCKY RD ;3P
Adder
2.723
958491AF2-143 GEN
Solar/Wind Harmer
9.422
962691AG1-118 GEN
Solar/Wind Harmer
18.812
942111AE2-223 GEN
Solar/Wind Harmer
2.036
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.083
970621AG2-405 GEN
Solar/Wind Harmer
1.144
23751201ROTHROCK
Solar/Wind Helper
0.855
23585401KL_K28_T16
Solar/Wind Helper
1.451
316097T157 G90
Solar/Wind Helper
1.331
235054AD2-180 GEN
Solar/Wind Helper
1.948
238117U2-030
Solar/Wind Helper
0.32
235531U2-073 GEN
Solar/Wind Helper
3.079
238147AE2-230_GEN1
Solar/Wind Helper
0.432
238148AE2-230_GEN2
Solar/Wind Helper
0.432
238149AF1-291A_GEN
Solar/Wind Helper
0.123
237061AD1-155 GEN
Solar/Wind Helper
1.53
235020AA1-095 C
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.238
237080AD1-060 GEN
Solar/Wind Helper
0.297
235062AE1-101 C1
Solar/Wind Helper
1.447
237006AB1-125 GEN
Solar/Wind Helper
0.107
316411AF1-147_GEN1
Solar/Wind Helper
0.762
971341AH1-150 GEN
Solar/Wind Harmer
3.185
971343AH1-151 GEN
Solar/Wind Harmer
3.185
23559001PLEAS1
50/50
11.898
23562401OGROV2
50/50
2.273
24318805MLG1
50/50
6.603
24721905FLATG4
Adder
24.08
962771AG1-126 GEN
Solar/Wind Harmer
30.328
970153AG2-106 GEN
Solar/Wind Harmer
19.366
270512AE1-227 GEN2
Solar/Wind Harmer
1.881
971191AH1-055 GEN
Solar/Wind Harmer
18.543
961921AG1-034 GEN
Solar/Wind Harmer
6.37
970879AG2-548 GEN
Solar/Wind Harmer
5.224
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
942051AE2-217 GEN
Solar/Wind Harmer
12.608
24686405CER G5
Adder
8.292
253325AC1-069 GEN
Solar/Wind Harmer
0.008
270518AE2-148 GEN
Solar/Wind Harmer
0.572
270367AC2-061_GEN
Solar/Wind Harmer
0
253394AE2-221_GEN
Solar/Wind Harmer
0
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.832
253370AE2-315 SEC1
Adder
1.947
253371AE2-315 SEC2
Adder
1.842
270391AF1-285 GEN3
Solar/Wind Harmer
0.452
270186AC1-089 GEN
Solar/Wind Harmer
0
252507AC2-088 GEN
Solar/Wind Harmer
0.304
252519AF1-045_GEN
Solar/Wind Harmer
3.517
970191AG2-125 GEN
Solar/Wind Harmer
1.734
25196608WSDLE5
Adder
8.25
25194608D.CRK4
Adder
1.582
25196008MFTGT1
Adder
1.281
972167AH1-666 GEN
Solar/Wind Harmer
5.273
958171AF2-111 GEN
Solar/Wind Harmer
16.473
944531AF1-118 GEN
Solar/Wind Harmer
29.414
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.418
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.813
946031AF1-268 GEN
Solar/Wind Harmer
6.225
970825AG2-519 GEN
Solar/Wind Harmer
4.924
970289AG2-191 GEN
Solar/Wind Harmer
0.717
247642Z2-115 C
Solar/Wind Harmer
0.003
270043AE2-236 GEN
Solar/Wind Harmer
4.172
965021AG1-366 GEN
Solar/Wind Harmer
2.164
971347AH1-153 GEN
Solar/Wind Harmer
3.227
246938BC-WTG3
Solar/Wind Harmer
0.232
270491AE1-102 GEN2
Solar/Wind Harmer
0.837
24728705AND G3
Adder
7.406
24728505AND G1
Adder
3.541
24695305TIMB G C
Solar/Wind Harmer
0.545
971199AH1-059 GEN
Solar/Wind Harmer
1.349
24690905MDL-1G C
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.424
270063AE2-323 C
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
5.168
270505AE1-170 C O1
Solar/Wind Harmer
6.695
274772LINCOLN ;3U
Adder
7.689
274752CRETE EC ;2U
Adder
7.503
274753CRETE EC ;3U
Adder
7.503
274724RIVER EC ;11
Adder
16.119
274814UNIV PK N;0U
Adder
4.593
274807UNIV PK N;3U
Adder
4.583
274811UNIV PK N;7U
Adder
4.553
274803UNIV PARK;6U
Adder
5.293
274887GEN-1.85
Solar/Wind Harmer
0.165
276843GEN-1.7
Solar/Wind Harmer
0.205
276806AD2-047 C O1
Solar/Wind Harmer
3.589
970193AG2-126 GEN
Solar/Wind Harmer
9.501
274826FISK ;BP
Adder
9.937
972038AH1-567 GEN2
Adder
0.331
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
20.679
972259AH1-714 GEN
Adder
17.31
274729ELWOOD EC;1P
Adder
14.887
274730ELWOOD EC;6P
Adder
14.887
274734ELWOOD EC;8P
Adder
14.887
274736ELWOOD EC;9P
Adder
14.887
274676JOLIET 29;8U
Adder
26.795
943121AE2-341 GEN
Solar/Wind Harmer
10.564
943591AF1-030 GEN
Solar/Wind Harmer
7.025
274862TOP CROP ;2U
Solar/Wind Harmer
0.85
274682WAUKEGAN ;7U
Adder
16.174
276868AE1-113 GEN
Solar/Wind Harmer
1.255
274879MINONK ;1U
Solar/Wind Harmer
0.262
946671AF1-331 GEN
Solar/Wind Harmer
0.667
965091AG1-374 GEN
Solar/Wind Harmer
18.751
959611AF2-252 GEN
Solar/Wind Harmer
2.083
274855GSG-6 ;RU
Solar/Wind Harmer
0.228
274850MENDOTA H;RU
Solar/Wind Harmer
0.073
970571AG2-364 GEN
Solar/Wind Harmer
12.497
270588AE1-091_GEN
Solar/Wind Harmer
4.882
23562501BACKB
Solar/Wind Helper
1.049
964991AG1-363 GEN
Solar/Wind Helper
4.289
238108AE1-109 GEN1
Solar/Wind Helper
0.103
238110AE1-109 GEN3
Solar/Wind Helper
0.103
238127S14_GEN_2
Solar/Wind Helper
0.769
237048AF1-022 C
Solar/Wind Helper
0.176
238152AF2-075_GEN
Solar/Wind Helper
0.617
238175AF1-290_GEN
Solar/Wind Helper
0.135
23777901MDS_W4-102
Solar/Wind Helper
0.153
235063AE1-101 C2
Solar/Wind Helper
1.447
237001AB1-127_GEN
Solar/Wind Helper
0.384
316415AF1-147_GEN2
Solar/Wind Helper
0.762
959091AF2-200 GEN
Solar/Wind Harmer
3.185
23559101PLEAS2
50/50
11.898
23684201S70BUS2
50/50
0.3
23562301OGROV1
50/50
2.293
962761AG1-125 GEN
Solar/Wind Harmer
30.328
970149AG2-104 GEN
Solar/Wind Harmer
16.378
970155AG2-107 GEN
Solar/Wind Harmer
19.366
960001AF2-291 GEN
Solar/Wind Harmer
0
270510AE1-227 GEN1
Solar/Wind Harmer
1.881
270520AE2-214 GEN
Solar/Wind Harmer
0
971073AG2-665 GEN
Solar/Wind Harmer
1.187
270273AD2-016 GEN
Solar/Wind Harmer
0.726
972203AH1-686 GEN
Adder
2.339
24686505CER G6
Adder
8.358
253333AC1-068 GEN
Solar/Wind Harmer
0.008
24723205RIVRG3
Adder
18.772
972269AH1-719 GEN
Adder
2.288
253398AE2-221_GEN2
Solar/Wind Harmer
0
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.794
253370AE2-315 SEC1
Adder
1.947
253371AE2-315 SEC2
Adder
1.842
25326309TAIT D
Adder
1.064
252516AE2-318_GEN
Solar/Wind Harmer
7.551
252510AF1-249 C
Solar/Wind Harmer
0.051
25194608D.CRK4
Adder
1.582
25196808ZIMRHP
Adder
72.791
270317AD1-130_GEN
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.323
945681AF1-233 GEN
Solar/Wind Harmer
12.419
971995AH1-542 GEN
Solar/Wind Harmer
2.409
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.811
965651AG1-433 GEN
Solar/Wind Harmer
1.923
958861AF2-177 GEN
Solar/Wind Harmer
2.84
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.418
970773AG2-487 GEN
Solar/Wind Harmer
1.155
970825AG2-519 GEN
Solar/Wind Harmer
2.32
270024AE2-089 GEN
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
7.308
270032AE2-172
Solar/Wind Harmer
4.35
970091AG2-072 GEN
Adder
71.643
276903AD2-071 C
Solar/Wind Harmer
7.272
965011AG1-365 GEN
Solar/Wind Harmer
6.491
965421AG1-410 GEN
Solar/Wind Harmer
19.339
246936BC-WTG1
Solar/Wind Harmer
0.26
270489AE1-102 GEN1
Solar/Wind Harmer
0.837
24728605AND G2
Adder
3.541
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
8.034
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.351
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
13.48
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24639705ELKHART HY
Adder
0.141
963741AG1-226 GEN
Solar/Wind Harmer
15.1
957891AF2-083 GEN
Solar/Wind Harmer
10.629
945111AF1-176 GEN
Solar/Wind Harmer
11.377
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.32
274773LINCOLN ;4U
Adder
7.689
274774LINCOLN ;5U
Adder
7.689
274751CRETE EC ;1U
Adder
7.503
274754CRETE EC ;4U
Adder
7.503
274723RIVER EC ;12
Adder
16.309
274812UNIV PK N;8U
Adder
4.553
274802UNIV PARK;5U
Adder
5.293
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
14.887
274676JOLIET 29;8U
Adder
27.787
274674JOLIET 9 ;6U
Adder
13.943
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
4.718
944971AF1-162 GEN
Solar/Wind Harmer
6.303
274745AC1-111 GEN9
Adder
5.047
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.023
274861TOP CROP ;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
1.991
971997AH1-543 GEN
Solar/Wind Harmer
3.293
276882AE2-255 GEN
Solar/Wind Harmer
0.732
962781AG1-127 GEN
Solar/Wind Harmer
5.964
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
8.771
274872LEEDK;1U
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
18.746
23751101LEADS_P59
Solar/Wind Helper
2.413
23583801GRNGAP
Solar/Wind Helper
4.978
316095T157 G97
Solar/Wind Helper
1.331
238118U2-030_1
Solar/Wind Helper
0.32
23750501ELLIOTTS
Solar/Wind Helper
0.64
238169AE2-226 GEN1
Solar/Wind Helper
0.606
238170AE2-226 GEN2
Solar/Wind Helper
0.606
23779801AA1-109
Solar/Wind Helper
0.168
237025AB1-124 C
Solar/Wind Helper
0.143
237030AB1-096 C
Solar/Wind Helper
0.058
3138216PACIFIC
Solar/Wind Helper
0.038
971171AH1-044 GEN
Solar/Wind Harmer
3.185
238185AF2-356 C
Solar/Wind Helper
2.499
238120AE2-309 GEN
Solar/Wind Helper
0.489
238109AE1-109 GEN2
Solar/Wind Helper
0.103
238126S14_GEN_1
Solar/Wind Helper
0.769
23546401DTGZ2-030
Solar/Wind Helper
0.078
237085AD2-009_GEN
Solar/Wind Helper
1.438
235067AD1-061 GEN
Solar/Wind Helper
0.388
237038AE2-054 C
Solar/Wind Helper
0.237
237002AB1-128_GEN
Solar/Wind Helper
0.386
23777801MSM_W1-116
Solar/Wind Helper
0.1
957471AF2-041 GEN
Solar/Wind Harmer
4.778
959081AF2-199 GEN
Solar/Wind Harmer
1.593
971067AG2-660 GEN
Solar/Wind Harmer
0.531
CPLELTFEXP_CPLE->PJM
CLTF
1.222
CBM West 2LTFEXP_CBM-W2->PJM
CBM
104.659
NYPJM->LTFIMP_NY
CLTF
4.529
LGEELTFEXP_LGEE->PJM
CLTF
6.23
WECLTFEXP_WEC->PJM
CLTF
3.411
AG2-052LTFEXP_AG2-052->PJM
LTF
0.213
AH1-155LTFEXP_AH1-155->PJM
LTF
0.319
LAGNLTFEXP_LAGN->PJM
CLTF
14.046
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.869
TVALTFEXP_TVA->PJM
CLTF
6.974
CBM West 1LTFEXP_CBM-W1->PJM
CBM
125.509
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.61
MECLTFEXP_MEC->PJM
CLTF
14.364
SIGELTFEXP_SIGE->PJM
CLTF
0.464

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AEP_P4_#8975_05KAMMER 765_MM2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8975_05KAMMER 765_MM2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:139.19 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5278.17
MW Contribution:
21.61
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
50/50
1217.29
23684101S70BUS1
50/50
0.309
24318905MLG2
50/50
4.655
927014AC1-188 GEN
Solar/Wind Harmer
1.603
270349AD2-093_GEN
Solar/Wind Harmer
3.664
270471AD2-092_GEN
Solar/Wind Harmer
3.664
270054AF2-122 C O1
Solar/Wind Harmer
3.288
971073AG2-665 GEN
Solar/Wind Harmer
8.039
970879AG2-548 GEN
Solar/Wind Harmer
1.168
946101AF1-275 GEN
Solar/Wind Harmer
1.513
270269AC2-059
Solar/Wind Harmer
9.305
24723005RIVRG1
Adder
18.491
24723105RIVRG2
Adder
18.491
253383AE2-342_GEN
Solar/Wind Harmer
0.868
942861AE2-305 GEN
Solar/Wind Harmer
7.636
253415AE1-040 GEN
Solar/Wind Harmer
1.098
962581AG1-107 GEN
Solar/Wind Harmer
4.832
961491AF2-440 GEN
Solar/Wind Harmer
2.008
972159AH1-661 GEN
Adder
0.953
25326109MON D
Adder
1.253
253370AE2-315 SEC1
Adder
1.908
25322209TAIT E
Adder
9.279
25322209TAIT E
Adder
9.07
25183208HLCRTG
Solar/Wind Harmer
5.747
252509AD1-136 GEN
Solar/Wind Harmer
0.243
253349AC2-067 GEN
Solar/Wind Harmer
1.925
253400AC2-068 GEN
Solar/Wind Harmer
0.774
938701AE1-092 GEN
Solar/Wind Harmer
19.541
25194408D.CRK1
Adder
7.139
25194508D.CRK3
Adder
1.335
253378AE2-206_GEN
Solar/Wind Harmer
3.383
25326509SID D
Adder
1.233
270462AD2-086
Solar/Wind Harmer
6.502
24728805RICHG1
Adder
3.492
940611AE2-048 GEN
Solar/Wind Harmer
22.073
941391AE2-136 GEN
Solar/Wind Harmer
11.438
270291AC1-194 GEN
Solar/Wind Harmer
5.101
270459AD2-067 GEN
Solar/Wind Harmer
8.368
961821AG1-024 GEN
Solar/Wind Harmer
8.496
270432AC2-029 GEN
Solar/Wind Harmer
6.989
270263AC1-001 GEN
Solar/Wind Harmer
1.042
241955AC1-078 GEN
Solar/Wind Harmer
7.382
945631AF1-228 GEN
Solar/Wind Harmer
4.627
971985AH1-537 GEN
Solar/Wind Harmer
17.539
253338AC1-165 GEN
Solar/Wind Harmer
1.063
253343AC1-166 GEN
Solar/Wind Harmer
1.063
241973AD2-163_GEN1
Solar/Wind Harmer
1.941
241974AD2-163_GEN2
Solar/Wind Harmer
1.941
943861AF1-054 GEN
Solar/Wind Harmer
3.769
943851AF1-053 GEN
Solar/Wind Harmer
1.821
270340AC2-060 GEN
Solar/Wind Harmer
2.956
241972AD1-140 GEN
Solar/Wind Harmer
4.312
253406AD2-031_GEN
Solar/Wind Harmer
1.227
253433AC1-085 GEN1
Solar/Wind Harmer
5.075
253432AC1-085 GEN2
Solar/Wind Harmer
0.255
253372AE2-315 SEC3
Adder
1.805
253372AE2-315 SEC3
Adder
1.805
25306009OHH W.
Adder
2.738
270223U2-072_GEN1
Solar/Wind Harmer
1.87
270224U2-072_GEN2
Solar/Wind Harmer
1.87
270227U2-072_GEN3
Solar/Wind Harmer
1.87
270228U2-072_GEN4
Solar/Wind Harmer
1.87
270231U2-072_GEN5
Solar/Wind Harmer
1.87
270578AF1-285 GEN2
Solar/Wind Harmer
0.441
25196408WSDLE3
Adder
8.328
25196308WSDLE2
Adder
8.256
25196208WSDLE1
Adder
8.235
25196708WSDLE6
Adder
8.215
25196508WSDLE4
Adder
8.008
270302AB2-170 GEN
Solar/Wind Harmer
7.829
25196108MFTGT2
Adder
1.43
25196108MFTGT2
Adder
1.328
972163AH1-664 GEN
Solar/Wind Harmer
9.262
972165AH1-665 GEN
Solar/Wind Harmer
7.409
971029AG2-637 GEN
Solar/Wind Harmer
13.858
270543AE2-219 C
Solar/Wind Harmer
9.219
247536S-71 GEN
Solar/Wind Harmer
3.723
24729505KEY G4
Adder
5.966
958711AF2-162 GEN
Solar/Wind Harmer
0.93
945581AF1-223 GEN
Solar/Wind Harmer
4.167
270356AE2-297 GEN
Solar/Wind Harmer
4.233
961761AG1-017 GEN
Solar/Wind Harmer
0.393
964611AG1-324 GEN
Solar/Wind Harmer
3.579
270071AF1-092 GEN
Solar/Wind Harmer
13.725
970289AG2-191 GEN
Solar/Wind Harmer
1.738
24728905RICHG2
Adder
3.492
970883AG2-550 GEN
Solar/Wind Harmer
9.219
970885AG2-551 GEN
Solar/Wind Harmer
2.144
270383AD1-128 GEN
Solar/Wind Harmer
5.623
926881AC1-175 GEN
Solar/Wind Harmer
5.139
944541AF1-119 GEN
Solar/Wind Harmer
3.848
960971AF2-388 GEN
Solar/Wind Harmer
10.047
247621Y3-024
Adder
0.222
270201AC2-176 GEN
Solar/Wind Harmer
4.716
964611AG1-324 GEN
Solar/Wind Harmer
0.48
270031AE2-169
Solar/Wind Harmer
7.466
270599AE1-208 GEN
Solar/Wind Harmer
7.466
942221AE2-234 GEN
Solar/Wind Harmer
3.201
970291AG2-192 GEN
Solar/Wind Harmer
1.189
970291AG2-192 GEN
Solar/Wind Harmer
0.383
24725505WLD G2 C
Solar/Wind Harmer
3.633
24699105WLD G1 C
Solar/Wind Harmer
3.591
270246TR4_N_V150
Solar/Wind Harmer
0.769
270247TR4_N_V136
Solar/Wind Harmer
0.769
970349AG2-230 GEN
Solar/Wind Harmer
13.564
945421AF1-207 GEN
Solar/Wind Harmer
12.67
957841AF2-078 GEN
Solar/Wind Harmer
5.454
247620Y3-023
Adder
0.413
274770LINCOLN ;1U
Adder
7.522
963791AG1-232 GEN
Solar/Wind Harmer
12.295
959331AF2-224 GEN
Solar/Wind Harmer
9.086
247521TR3_G114
Solar/Wind Harmer
3.039
270191TR4_S_V150
Solar/Wind Harmer
2.712
965051AG1-369 GEN
Solar/Wind Harmer
4.516
965041AG1-368 GEN
Solar/Wind Harmer
9.035
339216AC1-074 GEN
Solar/Wind Harmer
1.512
274775LINCOLN ;6U
Adder
7.522
274776LINCOLN ;7U
Adder
7.522
274777LINCOLN ;8U
Adder
7.522
972037AH1-567 GEN1
Adder
0.163
972228AH1-698 GEN2
Adder
3.29
972227AH1-698 GEN1
Adder
2.316
274827FISK ;RP
Adder
6.89
274800UNIV PARK;3U
Adder
5.177
274801UNIV PARK;4U
Adder
5.177
274687WILL CNTY;4U
Adder
24.769
274687WILL CNTY;4U
Adder
24.769
274728ELWOOD EC;5P
Adder
14.566
274731ELWOOD EC;2P
Adder
14.566
274733ELWOOD EC;3P
Adder
14.566
274735ELWOOD EC;4P
Adder
14.566
23750701CROSSCHOOL
Solar/Wind Helper
1.155
238169AE2-226 GEN1
Solar/Wind Helper
0.584
238170AE2-226 GEN2
Solar/Wind Helper
0.584
23779801AA1-109
Solar/Wind Helper
0.162
238118U2-030_1
Solar/Wind Helper
0.26
23559001PLEAS1
50/50
11.247
23562401OGROV2
50/50
2.416
24318805MLG1
50/50
6.319
24721905FLATG4
Adder
23.461
962771AG1-126 GEN
Solar/Wind Harmer
35.004
970153AG2-106 GEN
Solar/Wind Harmer
15.264
270512AE1-227 GEN2
Solar/Wind Harmer
2.247
270330AC1-082 GEN2
Solar/Wind Harmer
0.49
270329AC1-082 GEN1
Solar/Wind Harmer
0.49
971191AH1-055 GEN
Solar/Wind Harmer
19.037
957541AF2-048 GEN
Solar/Wind Harmer
1.603
970879AG2-548 GEN
Solar/Wind Harmer
8.039
961921AG1-034 GEN
Solar/Wind Harmer
12.743
960801AF2-371 GEN
Solar/Wind Harmer
2.536
964871AG1-351 GEN
Solar/Wind Harmer
1.751
24686405CER G5
Adder
8.185
270284AF1-227 GEN1
Solar/Wind Harmer
5.566
270287AF1-227 GEN3
Solar/Wind Harmer
2.059
942051AE2-217 GEN
Solar/Wind Harmer
17.671
253325AC1-069 GEN
Solar/Wind Harmer
1.025
270518AE2-148 GEN
Solar/Wind Harmer
11.818
270367AC2-061_GEN
Solar/Wind Harmer
3.046
253394AE2-221_GEN
Solar/Wind Harmer
4.334
253317AC1-085 GEN4
Solar/Wind Harmer
7.996
946181AF1-283 GEN
Solar/Wind Harmer
12.416
270186AC1-089 GEN
Solar/Wind Harmer
5.821
253303V4-073 C
Solar/Wind Harmer
0.11
253370AE2-315 SEC1
Adder
1.908
253371AE2-315 SEC2
Adder
1.805
960071AF2-298 GEN
Solar/Wind Harmer
1.437
252507AC2-088 GEN
Solar/Wind Harmer
1.699
252519AF1-045_GEN
Solar/Wind Harmer
3.45
942871AE2-306 GEN
Solar/Wind Harmer
0.859
270391AF1-285 GEN3
Solar/Wind Harmer
0.441
252524AE2-267 GEN
Solar/Wind Harmer
1.486
25196608WSDLE5
Adder
8.09
25194608D.CRK4
Adder
1.552
276820AF1-078_GEN
Solar/Wind Harmer
1.503
25196008MFTGT1
Adder
1.256
972167AH1-666 GEN
Solar/Wind Harmer
7.423
958171AF2-111 GEN
Solar/Wind Harmer
23.182
24379505HDWTR1G C
Solar/Wind Harmer
7.281
270240V3-007_GEN2
Solar/Wind Harmer
5.697
944531AF1-118 GEN
Solar/Wind Harmer
32.194
270004AE1-209 GEN
Solar/Wind Harmer
5.017
946031AF1-268 GEN
Solar/Wind Harmer
7.618
962031AG1-047 GEN
Solar/Wind Harmer
2.774
957741AF2-068 GEN
Solar/Wind Harmer
13.765
970825AG2-519 GEN
Solar/Wind Harmer
5.167
965461AG1-414 GEN
Solar/Wind Harmer
2.074
970289AG2-191 GEN
Solar/Wind Harmer
0.702
247642Z2-115 C
Solar/Wind Harmer
0.058
270043AE2-236 GEN
Solar/Wind Harmer
5.008
965021AG1-366 GEN
Solar/Wind Harmer
2.113
24728705AND G3
Adder
7.256
24728505AND G1
Adder
3.47
971347AH1-153 GEN
Solar/Wind Harmer
4.521
339243AC2-075 GEN1
Solar/Wind Harmer
0.41
274772LINCOLN ;3U
Adder
7.522
274752CRETE EC ;2U
Adder
7.339
274753CRETE EC ;3U
Adder
7.339
274724RIVER EC ;11
Adder
15.767
274814UNIV PK N;0U
Adder
4.493
274807UNIV PK N;3U
Adder
4.483
274811UNIV PK N;7U
Adder
4.454
274803UNIV PARK;6U
Adder
5.179
274826FISK ;BP
Adder
9.721
972038AH1-567 GEN2
Adder
0.324
972259AH1-714 GEN
Adder
16.936
274729ELWOOD EC;1P
Adder
14.566
274730ELWOOD EC;6P
Adder
14.566
274734ELWOOD EC;8P
Adder
14.566
274736ELWOOD EC;9P
Adder
0.016
964991AG1-363 GEN
Solar/Wind Helper
4.131
238152AF2-075_GEN
Solar/Wind Helper
0.595
238175AF1-290_GEN
Solar/Wind Helper
0.13
238108AE1-109 GEN1
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
23777901MDS_W4-102
Solar/Wind Helper
0.147
235063AE1-101 C2
Solar/Wind Helper
1.383
237001AB1-127_GEN
Solar/Wind Helper
0.369
238127S14_GEN_2
Solar/Wind Helper
0.641
274771LINCOLN ;2U
Adder
7.522
274805UNIV PK N;1U
Adder
4.464
274808UNIV PK N;4U
Adder
4.435
316097T157 G90
Solar/Wind Helper
1.299
238147AE2-230_GEN1
Solar/Wind Helper
0.416
238148AE2-230_GEN2
Solar/Wind Helper
0.416
238149AF1-291A_GEN
Solar/Wind Helper
0.119
237061AD1-155 GEN
Solar/Wind Helper
1.477
235020AA1-095 C
Solar/Wind Helper
0.044
238221AF1-254 C O1
Solar/Wind Helper
0.228
237080AD1-060 GEN
Solar/Wind Helper
0.284
235062AE1-101 C1
Solar/Wind Helper
1.383
235531U2-073 GEN
Solar/Wind Helper
2.544
238117U2-030
Solar/Wind Helper
0.26
23559101PLEAS2
50/50
11.247
23684201S70BUS2
50/50
0.315
23562301OGROV1
50/50
2.436
962761AG1-125 GEN
Solar/Wind Harmer
35.004
970149AG2-104 GEN
Solar/Wind Harmer
21.615
970155AG2-107 GEN
Solar/Wind Harmer
15.264
270510AE1-227 GEN1
Solar/Wind Harmer
2.647
960001AF2-291 GEN
Solar/Wind Harmer
3.156
270331AC1-082 GEN3
Solar/Wind Harmer
0.491
971073AG2-665 GEN
Solar/Wind Harmer
1.168
270520AE2-214 GEN
Solar/Wind Harmer
6.054
972203AH1-686 GEN
Adder
2.3
270273AD2-016 GEN
Solar/Wind Harmer
2.653
24686505CER G6
Adder
8.25
972269AH1-719 GEN
Adder
2.27
270286AF1-227 GEN2
Solar/Wind Harmer
2.059
24723205RIVRG3
Adder
18.491
253333AC1-068 GEN
Solar/Wind Harmer
1.025
253398AE2-221_GEN2
Solar/Wind Harmer
4.334
253316AC1-085 GEN3
Solar/Wind Harmer
7.996
946171AF1-282 GEN
Solar/Wind Harmer
9.551
253370AE2-315 SEC1
Adder
1.908
253371AE2-315 SEC2
Adder
1.805
25326309TAIT D
Adder
1.043
252516AE2-318_GEN
Solar/Wind Harmer
9.479
270391AF1-285 GEN3
Solar/Wind Harmer
1.145
270578AF1-285 GEN2
Solar/Wind Harmer
1.145
252510AF1-249 C
Solar/Wind Harmer
0.394
25194608D.CRK4
Adder
1.552
25196808ZIMRHP
Adder
71.417
270317AD1-130_GEN
Solar/Wind Harmer
2.993
270485AE1-090_GEN
Solar/Wind Harmer
0.565
270222AC2-111 GEN
Solar/Wind Harmer
4.163
944031AF1-071 GEN
Solar/Wind Harmer
0.937
25196008MFTGT1
Adder
1.297
945681AF1-233 GEN
Solar/Wind Harmer
17.484
942081AE2-220 GEN
Solar/Wind Harmer
5.889
270209AC1-174_GEN
Solar/Wind Harmer
3.747
270437AC2-090 C
Solar/Wind Harmer
5.139
270239V3-007_GEN1
Solar/Wind Harmer
1.584
965651AG1-433 GEN
Solar/Wind Harmer
5.023
958861AF2-177 GEN
Solar/Wind Harmer
10.045
945371AF1-202 GEN
Solar/Wind Harmer
6.41
971995AH1-542 GEN
Solar/Wind Harmer
10.104
270005AE1-210 C O1
Solar/Wind Harmer
5.017
970825AG2-519 GEN
Solar/Wind Harmer
1.925
970091AG2-072 GEN
Adder
70.262
270594AE1-207 GEN
Solar/Wind Harmer
12.433
270032AE2-172
Solar/Wind Harmer
4.258
270024AE2-089 GEN
Solar/Wind Harmer
4.289
276903AD2-071 C
Solar/Wind Harmer
9.138
965011AG1-365 GEN
Solar/Wind Harmer
9.086
24728605AND G2
Adder
3.47
339221AD2-048_GEN
Solar/Wind Harmer
1.388
965421AG1-410 GEN
Solar/Wind Harmer
27.057
24639705ELKHART HY
Adder
0.138
274773LINCOLN ;4U
Adder
7.522
274774LINCOLN ;5U
Adder
7.522
274751CRETE EC ;1U
Adder
7.339
274754CRETE EC ;4U
Adder
7.339
274723RIVER EC ;12
Adder
15.953
274812UNIV PK N;8U
Adder
4.454
274802UNIV PARK;5U
Adder
5.179
274732ELWOOD EC;7P
Adder
14.566
23583801GRNGAP
Solar/Wind Helper
4.857
316095T157 G97
Solar/Wind Helper
1.299
23546401DTGZ2-030
Solar/Wind Helper
0.075
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238185AF2-356 C
Solar/Wind Helper
2.003
237038AE2-054 C
Solar/Wind Helper
0.227
235067AD1-061 GEN
Solar/Wind Helper
0.371
237085AD2-009_GEN
Solar/Wind Helper
1.37
238120AE2-309 GEN
Solar/Wind Helper
0.408
237002AB1-128_GEN
Solar/Wind Helper
0.369
238126S14_GEN_1
Solar/Wind Helper
0.641
23777801MSM_W1-116
Solar/Wind Helper
0.096
940581AE2-045 GEN
Solar/Wind Harmer
5.47
971605AH1-302 GEN
Solar/Wind Harmer
4.677
CPLELTFEXP_CPLE->PJM
CLTF
1.296
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.919
NYPJM->LTFIMP_NY
CLTF
4.411
LGEELTFEXP_LGEE->PJM
CLTF
6.118
WECLTFEXP_WEC->PJM
CLTF
3.339
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312
LAGNLTFEXP_LAGN->PJM
CLTF
13.85
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.952
TVALTFEXP_TVA->PJM
CLTF
6.885
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.746
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.223
MECLTFEXP_MEC->PJM
CLTF
14.081
SIGELTFEXP_SIGE->PJM
CLTF
0.455

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT7A_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT7A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:139.17 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5277.43
MW Contribution:
21.61
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
50/50
1217.29
23684101S70BUS1
50/50
0.309
24318905MLG2
50/50
4.655
927014AC1-188 GEN
Solar/Wind Harmer
1.603
270349AD2-093_GEN
Solar/Wind Harmer
3.664
270471AD2-092_GEN
Solar/Wind Harmer
3.664
270054AF2-122 C O1
Solar/Wind Harmer
3.288
971073AG2-665 GEN
Solar/Wind Harmer
8.039
970879AG2-548 GEN
Solar/Wind Harmer
1.168
946101AF1-275 GEN
Solar/Wind Harmer
1.513
270269AC2-059
Solar/Wind Harmer
9.305
24723005RIVRG1
Adder
18.491
24723105RIVRG2
Adder
18.491
253383AE2-342_GEN
Solar/Wind Harmer
0.868
942861AE2-305 GEN
Solar/Wind Harmer
7.636
253415AE1-040 GEN
Solar/Wind Harmer
1.098
962581AG1-107 GEN
Solar/Wind Harmer
4.832
961491AF2-440 GEN
Solar/Wind Harmer
2.008
972159AH1-661 GEN
Adder
0.953
25326109MON D
Adder
1.253
253370AE2-315 SEC1
Adder
1.908
25322209TAIT E
Adder
9.279
25322209TAIT E
Adder
9.07
25183208HLCRTG
Solar/Wind Harmer
5.747
252509AD1-136 GEN
Solar/Wind Harmer
0.243
253349AC2-067 GEN
Solar/Wind Harmer
1.925
253400AC2-068 GEN
Solar/Wind Harmer
0.774
938701AE1-092 GEN
Solar/Wind Harmer
19.541
25194408D.CRK1
Adder
7.139
25194508D.CRK3
Adder
1.335
253378AE2-206_GEN
Solar/Wind Harmer
3.383
25326509SID D
Adder
1.233
270462AD2-086
Solar/Wind Harmer
6.502
24728805RICHG1
Adder
3.492
24728905RICHG2
Adder
3.492
970883AG2-550 GEN
Solar/Wind Harmer
9.219
970885AG2-551 GEN
Solar/Wind Harmer
2.144
270383AD1-128 GEN
Solar/Wind Harmer
5.623
926881AC1-175 GEN
Solar/Wind Harmer
5.139
944541AF1-119 GEN
Solar/Wind Harmer
3.848
960971AF2-388 GEN
Solar/Wind Harmer
10.047
247621Y3-024
Adder
0.222
270201AC2-176 GEN
Solar/Wind Harmer
4.716
964611AG1-324 GEN
Solar/Wind Harmer
0.48
270031AE2-169
Solar/Wind Harmer
7.466
270599AE1-208 GEN
Solar/Wind Harmer
7.466
942221AE2-234 GEN
Solar/Wind Harmer
3.201
970291AG2-192 GEN
Solar/Wind Harmer
1.189
970291AG2-192 GEN
Solar/Wind Harmer
0.383
24725505WLD G2 C
Solar/Wind Harmer
3.633
24699105WLD G1 C
Solar/Wind Harmer
3.591
270246TR4_N_V150
Solar/Wind Harmer
0.769
270247TR4_N_V136
Solar/Wind Harmer
0.769
970349AG2-230 GEN
Solar/Wind Harmer
13.564
945421AF1-207 GEN
Solar/Wind Harmer
12.67
957841AF2-078 GEN
Solar/Wind Harmer
5.454
247620Y3-023
Adder
0.413
274770LINCOLN ;1U
Adder
7.522
274771LINCOLN ;2U
Adder
7.522
274805UNIV PK N;1U
Adder
4.464
274808UNIV PK N;4U
Adder
4.435
316097T157 G90
Solar/Wind Helper
1.299
238147AE2-230_GEN1
Solar/Wind Helper
0.416
238148AE2-230_GEN2
Solar/Wind Helper
0.416
238149AF1-291A_GEN
Solar/Wind Helper
0.119
237061AD1-155 GEN
Solar/Wind Helper
1.477
235020AA1-095 C
Solar/Wind Helper
0.044
238221AF1-254 C O1
Solar/Wind Helper
0.228
237080AD1-060 GEN
Solar/Wind Helper
0.284
940611AE2-048 GEN
Solar/Wind Harmer
22.073
941391AE2-136 GEN
Solar/Wind Harmer
11.438
270291AC1-194 GEN
Solar/Wind Harmer
5.101
270459AD2-067 GEN
Solar/Wind Harmer
8.368
961821AG1-024 GEN
Solar/Wind Harmer
8.496
270432AC2-029 GEN
Solar/Wind Harmer
6.989
270263AC1-001 GEN
Solar/Wind Harmer
1.042
241955AC1-078 GEN
Solar/Wind Harmer
7.382
945631AF1-228 GEN
Solar/Wind Harmer
4.627
971985AH1-537 GEN
Solar/Wind Harmer
17.539
253338AC1-165 GEN
Solar/Wind Harmer
1.063
253343AC1-166 GEN
Solar/Wind Harmer
1.063
241973AD2-163_GEN1
Solar/Wind Harmer
1.941
241974AD2-163_GEN2
Solar/Wind Harmer
1.941
943861AF1-054 GEN
Solar/Wind Harmer
3.769
943851AF1-053 GEN
Solar/Wind Harmer
1.821
270340AC2-060 GEN
Solar/Wind Harmer
2.956
241972AD1-140 GEN
Solar/Wind Harmer
4.312
253406AD2-031_GEN
Solar/Wind Harmer
1.227
253433AC1-085 GEN1
Solar/Wind Harmer
5.075
253432AC1-085 GEN2
Solar/Wind Harmer
0.255
253372AE2-315 SEC3
Adder
1.805
253372AE2-315 SEC3
Adder
1.805
25306009OHH W.
Adder
2.738
270223U2-072_GEN1
Solar/Wind Harmer
1.87
270224U2-072_GEN2
Solar/Wind Harmer
1.87
270227U2-072_GEN3
Solar/Wind Harmer
1.87
270228U2-072_GEN4
Solar/Wind Harmer
1.87
270231U2-072_GEN5
Solar/Wind Harmer
1.87
270578AF1-285 GEN2
Solar/Wind Harmer
0.441
25196408WSDLE3
Adder
8.328
25196308WSDLE2
Adder
8.256
25196208WSDLE1
Adder
8.235
25196708WSDLE6
Adder
8.215
25196508WSDLE4
Adder
8.008
270302AB2-170 GEN
Solar/Wind Harmer
7.829
25196108MFTGT2
Adder
1.43
25196108MFTGT2
Adder
1.328
972163AH1-664 GEN
Solar/Wind Harmer
9.262
972165AH1-665 GEN
Solar/Wind Harmer
7.409
971029AG2-637 GEN
Solar/Wind Harmer
13.858
270543AE2-219 C
Solar/Wind Harmer
9.219
247536S-71 GEN
Solar/Wind Harmer
3.723
24729505KEY G4
Adder
5.966
958711AF2-162 GEN
Solar/Wind Harmer
0.93
945581AF1-223 GEN
Solar/Wind Harmer
4.167
270356AE2-297 GEN
Solar/Wind Harmer
4.233
961761AG1-017 GEN
Solar/Wind Harmer
0.393
964611AG1-324 GEN
Solar/Wind Harmer
3.579
270071AF1-092 GEN
Solar/Wind Harmer
13.725
970289AG2-191 GEN
Solar/Wind Harmer
1.738
963791AG1-232 GEN
Solar/Wind Harmer
12.295
959331AF2-224 GEN
Solar/Wind Harmer
9.086
247521TR3_G114
Solar/Wind Harmer
3.039
270191TR4_S_V150
Solar/Wind Harmer
2.712
965051AG1-369 GEN
Solar/Wind Harmer
4.516
965041AG1-368 GEN
Solar/Wind Harmer
9.035
339216AC1-074 GEN
Solar/Wind Harmer
1.512
274775LINCOLN ;6U
Adder
7.522
274776LINCOLN ;7U
Adder
7.522
274777LINCOLN ;8U
Adder
7.522
972037AH1-567 GEN1
Adder
0.163
972228AH1-698 GEN2
Adder
3.29
972227AH1-698 GEN1
Adder
2.316
274827FISK ;RP
Adder
6.89
274800UNIV PARK;3U
Adder
5.177
274801UNIV PARK;4U
Adder
5.177
274687WILL CNTY;4U
Adder
24.769
274687WILL CNTY;4U
Adder
24.769
274728ELWOOD EC;5P
Adder
14.566
274731ELWOOD EC;2P
Adder
14.566
274733ELWOOD EC;3P
Adder
14.566
274735ELWOOD EC;4P
Adder
14.566
23750701CROSSCHOOL
Solar/Wind Helper
1.155
238169AE2-226 GEN1
Solar/Wind Helper
0.584
238170AE2-226 GEN2
Solar/Wind Helper
0.584
235062AE1-101 C1
Solar/Wind Helper
1.383
235531U2-073 GEN
Solar/Wind Helper
2.544
238117U2-030
Solar/Wind Helper
0.26
23779801AA1-109
Solar/Wind Helper
0.162
238118U2-030_1
Solar/Wind Helper
0.26
23559101PLEAS2
50/50
11.247
23684201S70BUS2
50/50
0.315
23562301OGROV1
50/50
2.436
962761AG1-125 GEN
Solar/Wind Harmer
35.004
970149AG2-104 GEN
Solar/Wind Harmer
21.615
970155AG2-107 GEN
Solar/Wind Harmer
15.264
270510AE1-227 GEN1
Solar/Wind Harmer
2.647
960001AF2-291 GEN
Solar/Wind Harmer
3.156
270331AC1-082 GEN3
Solar/Wind Harmer
0.491
971073AG2-665 GEN
Solar/Wind Harmer
1.168
270520AE2-214 GEN
Solar/Wind Harmer
6.054
972203AH1-686 GEN
Adder
2.3
270273AD2-016 GEN
Solar/Wind Harmer
2.653
24686505CER G6
Adder
8.25
972269AH1-719 GEN
Adder
2.27
270286AF1-227 GEN2
Solar/Wind Harmer
2.059
24723205RIVRG3
Adder
18.491
253333AC1-068 GEN
Solar/Wind Harmer
1.025
253398AE2-221_GEN2
Solar/Wind Harmer
4.334
253316AC1-085 GEN3
Solar/Wind Harmer
7.996
946171AF1-282 GEN
Solar/Wind Harmer
9.551
253370AE2-315 SEC1
Adder
1.908
253371AE2-315 SEC2
Adder
1.805
25326309TAIT D
Adder
1.043
252516AE2-318_GEN
Solar/Wind Harmer
9.479
270391AF1-285 GEN3
Solar/Wind Harmer
1.145
270578AF1-285 GEN2
Solar/Wind Harmer
1.145
252510AF1-249 C
Solar/Wind Harmer
0.394
25194608D.CRK4
Adder
1.552
25196808ZIMRHP
Adder
71.417
270317AD1-130_GEN
Solar/Wind Harmer
2.993
270485AE1-090_GEN
Solar/Wind Harmer
0.565
270222AC2-111 GEN
Solar/Wind Harmer
4.163
944031AF1-071 GEN
Solar/Wind Harmer
0.937
25196008MFTGT1
Adder
1.297
945681AF1-233 GEN
Solar/Wind Harmer
17.484
942081AE2-220 GEN
Solar/Wind Harmer
5.889
270209AC1-174_GEN
Solar/Wind Harmer
3.747
270437AC2-090 C
Solar/Wind Harmer
5.139
270239V3-007_GEN1
Solar/Wind Harmer
1.584
965651AG1-433 GEN
Solar/Wind Harmer
5.023
958861AF2-177 GEN
Solar/Wind Harmer
10.045
945371AF1-202 GEN
Solar/Wind Harmer
6.41
971995AH1-542 GEN
Solar/Wind Harmer
10.104
270005AE1-210 C O1
Solar/Wind Harmer
5.017
970825AG2-519 GEN
Solar/Wind Harmer
1.925
970091AG2-072 GEN
Adder
70.262
270594AE1-207 GEN
Solar/Wind Harmer
12.433
270032AE2-172
Solar/Wind Harmer
4.258
270024AE2-089 GEN
Solar/Wind Harmer
4.289
276903AD2-071 C
Solar/Wind Harmer
9.138
965011AG1-365 GEN
Solar/Wind Harmer
9.086
24728605AND G2
Adder
3.47
339221AD2-048_GEN
Solar/Wind Harmer
1.388
965421AG1-410 GEN
Solar/Wind Harmer
27.057
24639705ELKHART HY
Adder
0.138
274773LINCOLN ;4U
Adder
7.522
274774LINCOLN ;5U
Adder
7.522
274751CRETE EC ;1U
Adder
7.339
274754CRETE EC ;4U
Adder
7.339
274723RIVER EC ;12
Adder
15.953
274812UNIV PK N;8U
Adder
4.454
274802UNIV PARK;5U
Adder
5.179
274732ELWOOD EC;7P
Adder
14.566
23583801GRNGAP
Solar/Wind Helper
4.857
316095T157 G97
Solar/Wind Helper
1.299
23546401DTGZ2-030
Solar/Wind Helper
0.075
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238185AF2-356 C
Solar/Wind Helper
2.003
237038AE2-054 C
Solar/Wind Helper
0.227
235067AD1-061 GEN
Solar/Wind Helper
0.371
237085AD2-009_GEN
Solar/Wind Helper
1.37
238120AE2-309 GEN
Solar/Wind Helper
0.408
237002AB1-128_GEN
Solar/Wind Helper
0.369
238126S14_GEN_1
Solar/Wind Helper
0.641
23777801MSM_W1-116
Solar/Wind Helper
0.096
940581AE2-045 GEN
Solar/Wind Harmer
5.47
971605AH1-302 GEN
Solar/Wind Harmer
4.677
23559001PLEAS1
50/50
11.247
23562401OGROV2
50/50
2.416
24318805MLG1
50/50
6.319
24721905FLATG4
Adder
23.461
962771AG1-126 GEN
Solar/Wind Harmer
35.004
970153AG2-106 GEN
Solar/Wind Harmer
15.264
270512AE1-227 GEN2
Solar/Wind Harmer
2.247
270330AC1-082 GEN2
Solar/Wind Harmer
0.49
270329AC1-082 GEN1
Solar/Wind Harmer
0.49
971191AH1-055 GEN
Solar/Wind Harmer
19.037
957541AF2-048 GEN
Solar/Wind Harmer
1.603
970879AG2-548 GEN
Solar/Wind Harmer
8.039
961921AG1-034 GEN
Solar/Wind Harmer
12.743
960801AF2-371 GEN
Solar/Wind Harmer
2.536
964871AG1-351 GEN
Solar/Wind Harmer
1.751
24686405CER G5
Adder
8.185
270284AF1-227 GEN1
Solar/Wind Harmer
5.566
270287AF1-227 GEN3
Solar/Wind Harmer
2.059
942051AE2-217 GEN
Solar/Wind Harmer
17.671
253325AC1-069 GEN
Solar/Wind Harmer
1.025
270518AE2-148 GEN
Solar/Wind Harmer
11.818
270367AC2-061_GEN
Solar/Wind Harmer
3.046
253394AE2-221_GEN
Solar/Wind Harmer
4.334
253317AC1-085 GEN4
Solar/Wind Harmer
7.996
946181AF1-283 GEN
Solar/Wind Harmer
12.416
270186AC1-089 GEN
Solar/Wind Harmer
5.821
253303V4-073 C
Solar/Wind Harmer
0.11
253370AE2-315 SEC1
Adder
1.908
253371AE2-315 SEC2
Adder
1.805
960071AF2-298 GEN
Solar/Wind Harmer
1.437
252507AC2-088 GEN
Solar/Wind Harmer
1.699
252519AF1-045_GEN
Solar/Wind Harmer
3.45
942871AE2-306 GEN
Solar/Wind Harmer
0.859
270391AF1-285 GEN3
Solar/Wind Harmer
0.441
252524AE2-267 GEN
Solar/Wind Harmer
1.486
25196608WSDLE5
Adder
8.09
25194608D.CRK4
Adder
1.552
276820AF1-078_GEN
Solar/Wind Harmer
1.503
25196008MFTGT1
Adder
1.256
972167AH1-666 GEN
Solar/Wind Harmer
7.423
958171AF2-111 GEN
Solar/Wind Harmer
23.182
24379505HDWTR1G C
Solar/Wind Harmer
7.281
270240V3-007_GEN2
Solar/Wind Harmer
5.697
944531AF1-118 GEN
Solar/Wind Harmer
32.194
270004AE1-209 GEN
Solar/Wind Harmer
5.017
946031AF1-268 GEN
Solar/Wind Harmer
7.618
962031AG1-047 GEN
Solar/Wind Harmer
2.774
957741AF2-068 GEN
Solar/Wind Harmer
13.765
970825AG2-519 GEN
Solar/Wind Harmer
5.167
965461AG1-414 GEN
Solar/Wind Harmer
2.074
970289AG2-191 GEN
Solar/Wind Harmer
0.702
247642Z2-115 C
Solar/Wind Harmer
0.058
270043AE2-236 GEN
Solar/Wind Harmer
5.008
965021AG1-366 GEN
Solar/Wind Harmer
2.113
24728705AND G3
Adder
7.256
24728505AND G1
Adder
3.47
971347AH1-153 GEN
Solar/Wind Harmer
4.521
339243AC2-075 GEN1
Solar/Wind Harmer
0.41
274772LINCOLN ;3U
Adder
7.522
274752CRETE EC ;2U
Adder
7.339
274753CRETE EC ;3U
Adder
7.339
274724RIVER EC ;11
Adder
15.767
274814UNIV PK N;0U
Adder
4.493
274807UNIV PK N;3U
Adder
4.483
274811UNIV PK N;7U
Adder
4.454
274803UNIV PARK;6U
Adder
5.179
274826FISK ;BP
Adder
9.721
972038AH1-567 GEN2
Adder
0.324
972259AH1-714 GEN
Adder
16.936
274729ELWOOD EC;1P
Adder
14.566
274730ELWOOD EC;6P
Adder
14.566
274734ELWOOD EC;8P
Adder
14.566
274736ELWOOD EC;9P
Adder
0.016
964991AG1-363 GEN
Solar/Wind Helper
4.131
238152AF2-075_GEN
Solar/Wind Helper
0.595
238175AF1-290_GEN
Solar/Wind Helper
0.13
238108AE1-109 GEN1
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
23777901MDS_W4-102
Solar/Wind Helper
0.147
235063AE1-101 C2
Solar/Wind Helper
1.383
237001AB1-127_GEN
Solar/Wind Helper
0.369
238127S14_GEN_2
Solar/Wind Helper
0.641
CPLELTFEXP_CPLE->PJM
CLTF
1.296
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.919
NYPJM->LTFIMP_NY
CLTF
4.411
LGEELTFEXP_LGEE->PJM
CLTF
6.118
WECLTFEXP_WEC->PJM
CLTF
3.339
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312
LAGNLTFEXP_LAGN->PJM
CLTF
13.85
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.952
TVALTFEXP_TVA->PJM
CLTF
6.885
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.746
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.223
MECLTFEXP_MEC->PJM
CLTF
14.081
SIGELTFEXP_SIGE->PJM
CLTF
0.455

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT10A_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT10A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:138.98 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5270.18
MW Contribution:
21.79
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
50/50
1216.009
23684101S70BUS1
50/50
0.312
23534401HANNIB
50/50
0.148
24318905MLG2
50/50
4.725
927014AC1-188 GEN
Solar/Wind Harmer
1.616
270349AD2-093_GEN
Solar/Wind Harmer
3.698
270471AD2-092_GEN
Solar/Wind Harmer
3.698
270054AF2-122 C O1
Solar/Wind Harmer
3.319
971073AG2-665 GEN
Solar/Wind Harmer
8.107
970879AG2-548 GEN
Solar/Wind Harmer
1.178
946101AF1-275 GEN
Solar/Wind Harmer
1.527
270269AC2-059
Solar/Wind Harmer
9.386
253383AE2-342_GEN
Solar/Wind Harmer
0.876
24723005RIVRG1
Adder
18.614
24723105RIVRG2
Adder
18.614
942861AE2-305 GEN
Solar/Wind Harmer
7.705
253415AE1-040 GEN
Solar/Wind Harmer
1.108
962581AG1-107 GEN
Solar/Wind Harmer
4.871
961491AF2-440 GEN
Solar/Wind Harmer
2.024
972159AH1-661 GEN
Adder
0.964
25326109MON D
Adder
1.264
253370AE2-315 SEC1
Adder
1.924
25322209TAIT E
Adder
9.36
25322209TAIT E
Adder
9.149
25183208HLCRTG
Solar/Wind Harmer
5.795
252509AD1-136 GEN
Solar/Wind Harmer
0.245
938701AE1-092 GEN
Solar/Wind Harmer
19.736
253349AC2-067 GEN
Solar/Wind Harmer
1.941
253400AC2-068 GEN
Solar/Wind Harmer
0.781
25194408D.CRK1
Adder
7.198
25194508D.CRK3
Adder
1.346
253378AE2-206_GEN
Solar/Wind Harmer
3.414
25326509SID D
Adder
1.244
270462AD2-086
Solar/Wind Harmer
6.566
24728805RICHG1
Adder
3.521
24728905RICHG2
Adder
3.521
970883AG2-550 GEN
Solar/Wind Harmer
9.298
970885AG2-551 GEN
Solar/Wind Harmer
2.162
270383AD1-128 GEN
Solar/Wind Harmer
5.671
926881AC1-175 GEN
Solar/Wind Harmer
5.183
944541AF1-119 GEN
Solar/Wind Harmer
3.882
960971AF2-388 GEN
Solar/Wind Harmer
10.135
247621Y3-024
Adder
0.223
270201AC2-176 GEN
Solar/Wind Harmer
4.757
964611AG1-324 GEN
Solar/Wind Harmer
0.484
270031AE2-169
Solar/Wind Harmer
7.53
270599AE1-208 GEN
Solar/Wind Harmer
7.53
942221AE2-234 GEN
Solar/Wind Harmer
3.23
970291AG2-192 GEN
Solar/Wind Harmer
1.199
970291AG2-192 GEN
Solar/Wind Harmer
0.386
24725505WLD G2 C
Solar/Wind Harmer
3.664
24699105WLD G1 C
Solar/Wind Harmer
3.622
270246TR4_N_V150
Solar/Wind Harmer
0.776
270247TR4_N_V136
Solar/Wind Harmer
0.776
970349AG2-230 GEN
Solar/Wind Harmer
13.685
246937BC-WTG2
Solar/Wind Harmer
3.559
247620Y3-023
Adder
0.416
274770LINCOLN ;1U
Adder
7.587
274771LINCOLN ;2U
Adder
7.587
274805UNIV PK N;1U
Adder
4.503
274808UNIV PK N;4U
Adder
4.473
316097T157 G90
Solar/Wind Helper
1.324
238147AE2-230_GEN1
Solar/Wind Helper
0.423
238148AE2-230_GEN2
Solar/Wind Helper
0.423
238149AF1-291A_GEN
Solar/Wind Helper
0.121
237061AD1-155 GEN
Solar/Wind Helper
1.5
235020AA1-095 C
Solar/Wind Helper
0.044
238221AF1-254 C O1
Solar/Wind Helper
0.231
237080AD1-060 GEN
Solar/Wind Helper
0.287
235062AE1-101 C1
Solar/Wind Helper
1.395
237006AB1-125 GEN
Solar/Wind Helper
0.106
316411AF1-147_GEN1
Solar/Wind Helper
0.753
945421AF1-207 GEN
Solar/Wind Harmer
3.67
940611AE2-048 GEN
Solar/Wind Harmer
22.313
941391AE2-136 GEN
Solar/Wind Harmer
11.562
270291AC1-194 GEN
Solar/Wind Harmer
5.145
270459AD2-067 GEN
Solar/Wind Harmer
8.448
961821AG1-024 GEN
Solar/Wind Harmer
8.577
270432AC2-029 GEN
Solar/Wind Harmer
7.05
270263AC1-001 GEN
Solar/Wind Harmer
1.051
241955AC1-078 GEN
Solar/Wind Harmer
7.45
945631AF1-228 GEN
Solar/Wind Harmer
4.669
971985AH1-537 GEN
Solar/Wind Harmer
17.679
253338AC1-165 GEN
Solar/Wind Harmer
1.072
253343AC1-166 GEN
Solar/Wind Harmer
1.072
241973AD2-163_GEN1
Solar/Wind Harmer
1.959
241974AD2-163_GEN2
Solar/Wind Harmer
1.959
943861AF1-054 GEN
Solar/Wind Harmer
3.803
943851AF1-053 GEN
Solar/Wind Harmer
1.838
270340AC2-060 GEN
Solar/Wind Harmer
2.981
241972AD1-140 GEN
Solar/Wind Harmer
4.35
253406AD2-031_GEN
Solar/Wind Harmer
1.237
253433AC1-085 GEN1
Solar/Wind Harmer
5.118
253432AC1-085 GEN2
Solar/Wind Harmer
0.258
253372AE2-315 SEC3
Adder
1.82
253372AE2-315 SEC3
Adder
1.82
25306009OHH W.
Adder
2.761
270223U2-072_GEN1
Solar/Wind Harmer
1.888
270224U2-072_GEN2
Solar/Wind Harmer
1.888
270227U2-072_GEN3
Solar/Wind Harmer
1.888
270228U2-072_GEN4
Solar/Wind Harmer
1.888
270231U2-072_GEN5
Solar/Wind Harmer
1.888
270578AF1-285 GEN2
Solar/Wind Harmer
0.445
25196408WSDLE3
Adder
8.398
25196308WSDLE2
Adder
8.325
25196208WSDLE1
Adder
8.304
25196708WSDLE6
Adder
8.283
25196508WSDLE4
Adder
8.074
270302AB2-170 GEN
Solar/Wind Harmer
7.906
25196108MFTGT2
Adder
1.442
25196108MFTGT2
Adder
1.339
972163AH1-664 GEN
Solar/Wind Harmer
9.335
972165AH1-665 GEN
Solar/Wind Harmer
7.468
971029AG2-637 GEN
Solar/Wind Harmer
13.978
270543AE2-219 C
Solar/Wind Harmer
9.298
247536S-71 GEN
Solar/Wind Harmer
3.755
24729505KEY G4
Adder
6.019
958711AF2-162 GEN
Solar/Wind Harmer
0.938
945581AF1-223 GEN
Solar/Wind Harmer
4.203
270356AE2-297 GEN
Solar/Wind Harmer
4.269
961761AG1-017 GEN
Solar/Wind Harmer
0.396
964611AG1-324 GEN
Solar/Wind Harmer
3.61
270071AF1-092 GEN
Solar/Wind Harmer
13.847
970289AG2-191 GEN
Solar/Wind Harmer
1.753
963791AG1-232 GEN
Solar/Wind Harmer
12.407
959331AF2-224 GEN
Solar/Wind Harmer
9.171
247521TR3_G114
Solar/Wind Harmer
3.068
270191TR4_S_V150
Solar/Wind Harmer
2.738
965051AG1-369 GEN
Solar/Wind Harmer
4.559
965041AG1-368 GEN
Solar/Wind Harmer
9.12
339216AC1-074 GEN
Solar/Wind Harmer
1.524
957201AF2-014 GEN
Solar/Wind Harmer
4.127
270435AC2-044 GEN
Solar/Wind Harmer
1.82
274775LINCOLN ;6U
Adder
7.587
274776LINCOLN ;7U
Adder
7.587
274777LINCOLN ;8U
Adder
7.587
972037AH1-567 GEN1
Adder
0.164
972228AH1-698 GEN2
Adder
3.318
972227AH1-698 GEN1
Adder
2.336
274827FISK ;RP
Adder
6.949
274800UNIV PARK;3U
Adder
5.222
274801UNIV PARK;4U
Adder
5.222
274687WILL CNTY;4U
Adder
24.982
274687WILL CNTY;4U
Adder
24.982
941621AE2-160 GEN
Adder
2.939
274728ELWOOD EC;5P
Adder
14.692
274731ELWOOD EC;2P
Adder
14.692
274733ELWOOD EC;3P
Adder
14.692
274735ELWOOD EC;4P
Adder
11.662
238169AE2-226 GEN1
Solar/Wind Helper
0.593
238170AE2-226 GEN2
Solar/Wind Helper
0.593
23750701CROSSCHOOL
Solar/Wind Helper
1.115
23779801AA1-109
Solar/Wind Helper
0.164
3138216PACIFIC
Solar/Wind Helper
0.037
237030AB1-096 C
Solar/Wind Helper
0.057
237025AB1-124 C
Solar/Wind Helper
0.141
23559101PLEAS2
50/50
11.275
23684201S70BUS2
50/50
0.318
23562301OGROV1
50/50
2.457
962761AG1-125 GEN
Solar/Wind Harmer
35.283
970149AG2-104 GEN
Solar/Wind Harmer
21.787
970155AG2-107 GEN
Solar/Wind Harmer
15.385
270510AE1-227 GEN1
Solar/Wind Harmer
2.681
960001AF2-291 GEN
Solar/Wind Harmer
3.18
270331AC1-082 GEN3
Solar/Wind Harmer
0.495
971073AG2-665 GEN
Solar/Wind Harmer
1.178
270520AE2-214 GEN
Solar/Wind Harmer
6.11
270273AD2-016 GEN
Solar/Wind Harmer
2.676
972203AH1-686 GEN
Adder
2.316
972269AH1-719 GEN
Adder
2.296
24686505CER G6
Adder
8.307
270286AF1-227 GEN2
Solar/Wind Harmer
2.078
24723205RIVRG3
Adder
18.614
253333AC1-068 GEN
Solar/Wind Harmer
1.034
253398AE2-221_GEN2
Solar/Wind Harmer
4.371
253316AC1-085 GEN3
Solar/Wind Harmer
8.063
946171AF1-282 GEN
Solar/Wind Harmer
9.631
253370AE2-315 SEC1
Adder
1.924
253371AE2-315 SEC2
Adder
1.82
25326309TAIT D
Adder
1.052
270391AF1-285 GEN3
Solar/Wind Harmer
1.157
270578AF1-285 GEN2
Solar/Wind Harmer
1.157
252516AE2-318_GEN
Solar/Wind Harmer
9.558
252510AF1-249 C
Solar/Wind Harmer
0.397
25194608D.CRK4
Adder
1.565
25196808ZIMRHP
Adder
72.004
270317AD1-130_GEN
Solar/Wind Harmer
3.023
270485AE1-090_GEN
Solar/Wind Harmer
0.571
270222AC2-111 GEN
Solar/Wind Harmer
4.198
944031AF1-071 GEN
Solar/Wind Harmer
0.945
25196008MFTGT1
Adder
1.308
945681AF1-233 GEN
Solar/Wind Harmer
17.624
942081AE2-220 GEN
Solar/Wind Harmer
5.939
270209AC1-174_GEN
Solar/Wind Harmer
3.779
270437AC2-090 C
Solar/Wind Harmer
5.183
270239V3-007_GEN1
Solar/Wind Harmer
1.598
971995AH1-542 GEN
Solar/Wind Harmer
10.211
965651AG1-433 GEN
Solar/Wind Harmer
5.067
958861AF2-177 GEN
Solar/Wind Harmer
10.133
945371AF1-202 GEN
Solar/Wind Harmer
6.466
270005AE1-210 C O1
Solar/Wind Harmer
5.06
970825AG2-519 GEN
Solar/Wind Harmer
1.941
970091AG2-072 GEN
Adder
70.821
270594AE1-207 GEN
Solar/Wind Harmer
12.54
270032AE2-172
Solar/Wind Harmer
4.294
270024AE2-089 GEN
Solar/Wind Harmer
4.327
276903AD2-071 C
Solar/Wind Harmer
9.216
965011AG1-365 GEN
Solar/Wind Harmer
9.171
24728605AND G2
Adder
3.499
339221AD2-048_GEN
Solar/Wind Harmer
1.399
965421AG1-410 GEN
Solar/Wind Harmer
27.321
246936BC-WTG1
Solar/Wind Harmer
3.559
270489AE1-102 GEN1
Solar/Wind Harmer
1.183
24639705ELKHART HY
Adder
0.139
274773LINCOLN ;4U
Adder
7.587
274774LINCOLN ;5U
Adder
7.587
274751CRETE EC ;1U
Adder
7.403
274754CRETE EC ;4U
Adder
7.403
274723RIVER EC ;12
Adder
16.092
274812UNIV PK N;8U
Adder
4.493
274802UNIV PARK;5U
Adder
5.223
274732ELWOOD EC;7P
Adder
14.692
23583801GRNGAP
Solar/Wind Helper
4.95
316095T157 G97
Solar/Wind Helper
1.324
23546401DTGZ2-030
Solar/Wind Helper
0.076
238109AE1-109 GEN2
Solar/Wind Helper
0.087
237038AE2-054 C
Solar/Wind Helper
0.229
235067AD1-061 GEN
Solar/Wind Helper
0.374
237085AD2-009_GEN
Solar/Wind Helper
1.38
237002AB1-128_GEN
Solar/Wind Helper
0.373
23777801MSM_W1-116
Solar/Wind Helper
0.098
23559001PLEAS1
50/50
11.275
23562401OGROV2
50/50
2.436
24318805MLG1
50/50
6.371
24721905FLATG4
Adder
23.616
962771AG1-126 GEN
Solar/Wind Harmer
35.283
970153AG2-106 GEN
Solar/Wind Harmer
15.385
270512AE1-227 GEN2
Solar/Wind Harmer
2.276
270330AC1-082 GEN2
Solar/Wind Harmer
0.494
270329AC1-082 GEN1
Solar/Wind Harmer
0.494
971191AH1-055 GEN
Solar/Wind Harmer
19.185
957541AF2-048 GEN
Solar/Wind Harmer
1.616
970879AG2-548 GEN
Solar/Wind Harmer
8.107
961921AG1-034 GEN
Solar/Wind Harmer
12.865
960801AF2-371 GEN
Solar/Wind Harmer
2.559
964871AG1-351 GEN
Solar/Wind Harmer
1.767
24686405CER G5
Adder
8.242
270284AF1-227 GEN1
Solar/Wind Harmer
5.618
270287AF1-227 GEN3
Solar/Wind Harmer
2.078
942051AE2-217 GEN
Solar/Wind Harmer
17.832
253325AC1-069 GEN
Solar/Wind Harmer
1.034
270518AE2-148 GEN
Solar/Wind Harmer
11.924
270367AC2-061_GEN
Solar/Wind Harmer
3.071
253394AE2-221_GEN
Solar/Wind Harmer
4.371
253317AC1-085 GEN4
Solar/Wind Harmer
8.063
946181AF1-283 GEN
Solar/Wind Harmer
12.52
270186AC1-089 GEN
Solar/Wind Harmer
5.868
253303V4-073 C
Solar/Wind Harmer
0.111
253370AE2-315 SEC1
Adder
1.924
253371AE2-315 SEC2
Adder
1.82
960071AF2-298 GEN
Solar/Wind Harmer
1.449
252507AC2-088 GEN
Solar/Wind Harmer
1.712
942871AE2-306 GEN
Solar/Wind Harmer
0.867
270391AF1-285 GEN3
Solar/Wind Harmer
0.445
252519AF1-045_GEN
Solar/Wind Harmer
3.479
252524AE2-267 GEN
Solar/Wind Harmer
1.499
25196608WSDLE5
Adder
8.158
25194608D.CRK4
Adder
1.565
276820AF1-078_GEN
Solar/Wind Harmer
1.517
25196008MFTGT1
Adder
1.267
972167AH1-666 GEN
Solar/Wind Harmer
7.482
958171AF2-111 GEN
Solar/Wind Harmer
23.368
24379505HDWTR1G C
Solar/Wind Harmer
7.343
270240V3-007_GEN2
Solar/Wind Harmer
5.745
944531AF1-118 GEN
Solar/Wind Harmer
32.478
270004AE1-209 GEN
Solar/Wind Harmer
5.06
946031AF1-268 GEN
Solar/Wind Harmer
7.684
962031AG1-047 GEN
Solar/Wind Harmer
2.799
957741AF2-068 GEN
Solar/Wind Harmer
13.884
970825AG2-519 GEN
Solar/Wind Harmer
5.212
965461AG1-414 GEN
Solar/Wind Harmer
2.092
970289AG2-191 GEN
Solar/Wind Harmer
0.708
247642Z2-115 C
Solar/Wind Harmer
0.059
270043AE2-236 GEN
Solar/Wind Harmer
5.054
965021AG1-366 GEN
Solar/Wind Harmer
2.133
971347AH1-153 GEN
Solar/Wind Harmer
4.562
24728705AND G3
Adder
7.317
24728505AND G1
Adder
3.499
958581AF2-149 GEN
Solar/Wind Harmer
3.901
971199AH1-059 GEN
Solar/Wind Harmer
1.914
339243AC2-075 GEN1
Solar/Wind Harmer
0.413
246938BC-WTG3
Solar/Wind Harmer
3.621
270491AE1-102 GEN2
Solar/Wind Harmer
1.183
274772LINCOLN ;3U
Adder
7.587
274752CRETE EC ;2U
Adder
7.403
274753CRETE EC ;3U
Adder
7.403
274724RIVER EC ;11
Adder
15.904
274814UNIV PK N;0U
Adder
4.532
274807UNIV PK N;3U
Adder
4.522
274811UNIV PK N;7U
Adder
4.493
274803UNIV PARK;6U
Adder
5.223
274826FISK ;BP
Adder
9.806
972038AH1-567 GEN2
Adder
0.327
972259AH1-714 GEN
Adder
17.082
274729ELWOOD EC;1P
Adder
14.692
274730ELWOOD EC;6P
Adder
14.692
274734ELWOOD EC;8P
Adder
14.692
964991AG1-363 GEN
Solar/Wind Helper
4.19
238152AF2-075_GEN
Solar/Wind Helper
0.604
238175AF1-290_GEN
Solar/Wind Helper
0.131
23777901MDS_W4-102
Solar/Wind Helper
0.149
238108AE1-109 GEN1
Solar/Wind Helper
0.087
238110AE1-109 GEN3
Solar/Wind Helper
0.087
237001AB1-127_GEN
Solar/Wind Helper
0.372
235063AE1-101 C2
Solar/Wind Helper
1.395
316415AF1-147_GEN2
Solar/Wind Helper
0.753
CPLELTFEXP_CPLE->PJM
CLTF
1.258
CBM West 2LTFEXP_CBM-W2->PJM
CBM
103.644
NYPJM->LTFIMP_NY
CLTF
4.427
LGEELTFEXP_LGEE->PJM
CLTF
6.165
WECLTFEXP_WEC->PJM
CLTF
3.367
AG2-052LTFEXP_AG2-052->PJM
LTF
0.21
AH1-155LTFEXP_AH1-155->PJM
LTF
0.315
LAGNLTFEXP_LAGN->PJM
CLTF
13.935
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.915
TVALTFEXP_TVA->PJM
CLTF
6.925
CBM West 1LTFEXP_CBM-W1->PJM
CBM
123.892
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.394
MECLTFEXP_MEC->PJM
CLTF
14.194
SIGELTFEXP_SIGE->PJM
CLTF
0.459

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-502T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-502T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:138.45 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5250.02
MW Contribution:
15.94
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
940611AE2-048 GEN
Solar/Wind Harmer
17.232
941391AE2-136 GEN
Solar/Wind Harmer
9.707
270291AC1-194 GEN
Solar/Wind Harmer
0
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.149
270432AC2-029 GEN
Solar/Wind Harmer
3.088
270263AC1-001 GEN
Solar/Wind Harmer
0.696
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
945631AF1-228 GEN
Solar/Wind Harmer
0.001
971985AH1-537 GEN
Solar/Wind Harmer
2.039
943861AF1-054 GEN
Solar/Wind Harmer
2.63
943851AF1-053 GEN
Solar/Wind Harmer
1.821
270340AC2-060 GEN
Solar/Wind Harmer
0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.733
253406AD2-031_GEN
Solar/Wind Harmer
0.497
253372AE2-315 SEC3
Adder
1.805
253372AE2-315 SEC3
Adder
1.805
25306009OHH W.
Adder
2.738
270578AF1-285 GEN2
Solar/Wind Harmer
0.441
25196408WSDLE3
Adder
8.328
25196308WSDLE2
Adder
8.256
25196208WSDLE1
Adder
8.235
25196708WSDLE6
Adder
8.215
25196508WSDLE4
Adder
8.008
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.918
25196108MFTGT2
Adder
1.43
25196108MFTGT2
Adder
1.328
972163AH1-664 GEN
Solar/Wind Harmer
7.194
972165AH1-665 GEN
Solar/Wind Harmer
5.762
971029AG2-637 GEN
Solar/Wind Harmer
9.669
270543AE2-219 C
Solar/Wind Harmer
4.502
247536S-71 GEN
Solar/Wind Harmer
0.257
24729505KEY G4
Adder
5.966
945581AF1-223 GEN
Solar/Wind Harmer
0
270356AE2-297 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
2.497
971609AH1-304 GEN
Solar/Wind Harmer
1.044
270071AF1-092 GEN
Solar/Wind Harmer
12.235
970289AG2-191 GEN
Solar/Wind Harmer
1.213
963791AG1-232 GEN
Solar/Wind Harmer
8.578
959331AF2-224 GEN
Solar/Wind Harmer
4.437
247521TR3_G114
Solar/Wind Harmer
0.229
965051AG1-369 GEN
Solar/Wind Harmer
3.151
965041AG1-368 GEN
Solar/Wind Harmer
6.303
339216AC1-074 GEN
Solar/Wind Harmer
0.168
971611AH1-305 GEN
Solar/Wind Harmer
3.744
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.796
958391AF2-133 GEN
Solar/Wind Harmer
0.001
970031AG2-029 GEN
Solar/Wind Harmer
3.403
24386405FR-21G C
Solar/Wind Harmer
0
957241AF2-018 GEN
Solar/Wind Harmer
0
270053AF1-130 C
Solar/Wind Harmer
13.997
960681AF2-359 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.713
971771AH1-392 GEN
Solar/Wind Harmer
6.254
270526AF1-158 GEN
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
7.522
274776LINCOLN ;7U
Adder
7.522
274777LINCOLN ;8U
Adder
7.522
972037AH1-567 GEN1
Adder
0.163
960591AF2-350 GEN
Solar/Wind Harmer
6.197
972228AH1-698 GEN2
Adder
3.29
972227AH1-698 GEN1
Adder
2.316
274827FISK ;RP
Adder
6.89
274800UNIV PARK;3U
Adder
5.177
274801UNIV PARK;4U
Adder
5.177
270399AC1-101 GEN
Solar/Wind Harmer
1.959
270400AC1-102 GEN
Solar/Wind Harmer
1.959
274687WILL CNTY;4U
Adder
24.769
274687WILL CNTY;4U
Adder
24.769
274728ELWOOD EC;5P
Adder
14.566
274731ELWOOD EC;2P
Adder
14.566
274733ELWOOD EC;3P
Adder
14.566
274735ELWOOD EC;4P
Adder
14.566
970833AG2-524 GEN
Solar/Wind Harmer
6.799
970833AG2-524 GEN
Solar/Wind Harmer
4.533
970179AG2-119 GEN
Solar/Wind Harmer
5.512
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970169AG2-114 GEN
Solar/Wind Harmer
6.152
970073AG2-061 GEN
Solar/Wind Harmer
2.049
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.441
274854TWINGROVE;U2
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
1.04
276861AD2-134 GEN
Solar/Wind Harmer
0.109
276863AD2-134 GEN
Solar/Wind Harmer
0.109
971675AH1-338 GEN
Solar/Wind Harmer
2.386
971411AH1-196 GEN
Solar/Wind Harmer
9.174
23750701CROSSCHOOL
Solar/Wind Helper
1.155
238169AE2-226 GEN1
Solar/Wind Helper
0.584
238170AE2-226 GEN2
Solar/Wind Helper
0.584
23779801AA1-109
Solar/Wind Helper
0.162
238118U2-030_1
Solar/Wind Helper
0.26
971171AH1-044 GEN
Solar/Wind Harmer
2.06
970935AG2-582 GEN
50/50
1217.29
23684101S70BUS1
50/50
0.309
24318905MLG2
50/50
4.655
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0
971073AG2-665 GEN
Solar/Wind Harmer
5.141
970879AG2-548 GEN
Solar/Wind Harmer
1.168
270269AC2-059
Solar/Wind Harmer
0.001
24723005RIVRG1
Adder
18.491
24723105RIVRG2
Adder
18.491
942861AE2-305 GEN
Solar/Wind Harmer
5.328
962581AG1-107 GEN
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
0.953
25326109MON D
Adder
1.253
253370AE2-315 SEC1
Adder
1.908
25322209TAIT E
Adder
9.279
25322209TAIT E
Adder
9.07
25183208HLCRTG
Solar/Wind Harmer
0
252509AD1-136 GEN
Solar/Wind Harmer
0.033
938701AE1-092 GEN
Solar/Wind Harmer
10.602
971655AH1-328 GEN
Solar/Wind Harmer
2.343
25194408D.CRK1
Adder
7.139
25194508D.CRK3
Adder
1.335
970329AG2-216 GEN
Solar/Wind Harmer
2.837
25326509SID D
Adder
1.233
270462AD2-086
Solar/Wind Harmer
0
24728805RICHG1
Adder
3.492
24728905RICHG2
Adder
3.492
970883AG2-550 GEN
Solar/Wind Harmer
6.432
970885AG2-551 GEN
Solar/Wind Harmer
2.144
270383AD1-128 GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.428
960971AF2-388 GEN
Solar/Wind Harmer
3.762
247621Y3-024
Adder
0.222
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.48
270031AE2-169
Solar/Wind Harmer
3.515
270599AE1-208 GEN
Solar/Wind Harmer
5.858
971613AH1-306 GEN
Solar/Wind Harmer
3.066
942221AE2-234 GEN
Solar/Wind Harmer
2.563
970291AG2-192 GEN
Solar/Wind Harmer
0.83
970291AG2-192 GEN
Solar/Wind Harmer
0.383
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270246TR4_N_V150
Solar/Wind Harmer
0.04
270247TR4_N_V136
Solar/Wind Harmer
0.04
970349AG2-230 GEN
Solar/Wind Harmer
9.463
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.253
24697605MDL-3G C
Solar/Wind Harmer
0
972043AH1-570 GEN
Solar/Wind Harmer
1.634
972045AH1-571 GEN
Solar/Wind Harmer
1.309
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.711
965681AG1-436 GEN
Solar/Wind Harmer
7.827
965791AG1-447 GEN
Solar/Wind Harmer
5.74
247620Y3-023
Adder
0.413
247607V1-011 GEN
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
3.645
971587AH1-292 GEN
Solar/Wind Harmer
4.565
961051AF2-396 GEN
Solar/Wind Harmer
12.441
961051AF2-396 GEN
Solar/Wind Harmer
8.294
274770LINCOLN ;1U
Adder
7.522
274771LINCOLN ;2U
Adder
7.522
945391AF1-204 GEN
Solar/Wind Harmer
6.594
274805UNIV PK N;1U
Adder
4.464
274808UNIV PK N;4U
Adder
4.435
971125AH1-004 GEN
Solar/Wind Harmer
2.48
970107AG2-081 GEN
Solar/Wind Harmer
1.86
274888KELLY CRK;1U
Solar/Wind Harmer
0.361
276776AD2-060 GEN
Solar/Wind Harmer
0.661
958011AF2-095 GEN
Solar/Wind Harmer
8.924
970941AG2-585 GEN
Solar/Wind Harmer
3.408
276897AD1-100 C
Solar/Wind Harmer
15.489
970623AG2-406 GEN
Solar/Wind Harmer
1.134
276893AG1-478 C
Solar/Wind Harmer
0.412
958481AF2-142 GEN
Solar/Wind Harmer
9.241
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.221
944231AF1-091 GEN
Solar/Wind Harmer
14.169
962691AG1-118 GEN
Solar/Wind Harmer
18.411
942111AE2-223 GEN
Solar/Wind Harmer
1.994
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.04
316097T157 G90
Solar/Wind Helper
1.299
238147AE2-230_GEN1
Solar/Wind Helper
0.416
238148AE2-230_GEN2
Solar/Wind Helper
0.416
238149AF1-291A_GEN
Solar/Wind Helper
0.119
237061AD1-155 GEN
Solar/Wind Helper
1.477
235020AA1-095 C
Solar/Wind Helper
0.044
238221AF1-254 C O1
Solar/Wind Helper
0.228
237080AD1-060 GEN
Solar/Wind Helper
0.284
235062AE1-101 C1
Solar/Wind Helper
1.383
235531U2-073 GEN
Solar/Wind Helper
2.544
238117U2-030
Solar/Wind Helper
0.26
971341AH1-150 GEN
Solar/Wind Harmer
2.06
971343AH1-151 GEN
Solar/Wind Harmer
2.06
23559101PLEAS2
50/50
11.247
23684201S70BUS2
50/50
0.315
23562301OGROV1
50/50
2.436
962761AG1-125 GEN
Solar/Wind Harmer
29.52
970149AG2-104 GEN
Solar/Wind Harmer
15.941
970155AG2-107 GEN
Solar/Wind Harmer
18.85
270510AE1-227 GEN1
Solar/Wind Harmer
1.908
960001AF2-291 GEN
Solar/Wind Harmer
0
971073AG2-665 GEN
Solar/Wind Harmer
1.168
270520AE2-214 GEN
Solar/Wind Harmer
0
972203AH1-686 GEN
Adder
2.3
270273AD2-016 GEN
Solar/Wind Harmer
0.712
24686505CER G6
Adder
8.25
972269AH1-719 GEN
Adder
2.27
24723205RIVRG3
Adder
18.491
253333AC1-068 GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.663
253370AE2-315 SEC1
Adder
1.908
253371AE2-315 SEC2
Adder
1.805
25326309TAIT D
Adder
1.043
252516AE2-318_GEN
Solar/Wind Harmer
7.407
252510AF1-249 C
Solar/Wind Harmer
0.05
25194608D.CRK4
Adder
1.552
25196808ZIMRHP
Adder
71.417
270317AD1-130_GEN
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.297
945681AF1-233 GEN
Solar/Wind Harmer
12.198
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.711
965651AG1-433 GEN
Solar/Wind Harmer
1.881
958861AF2-177 GEN
Solar/Wind Harmer
2.778
945371AF1-202 GEN
Solar/Wind Harmer
0
971995AH1-542 GEN
Solar/Wind Harmer
2.35
270005AE1-210 C O1
Solar/Wind Harmer
1.388
970773AG2-487 GEN
Solar/Wind Harmer
1.132
970825AG2-519 GEN
Solar/Wind Harmer
2.272
970091AG2-072 GEN
Adder
70.262
270594AE1-207 GEN
Solar/Wind Harmer
7.153
270032AE2-172
Solar/Wind Harmer
4.258
270024AE2-089 GEN
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
7.119
965011AG1-365 GEN
Solar/Wind Harmer
6.339
24728605AND G2
Adder
3.47
965421AG1-410 GEN
Solar/Wind Harmer
18.877
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
7.861
246936BC-WTG1
Solar/Wind Harmer
0.253
270489AE1-102 GEN1
Solar/Wind Harmer
0.817
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.17
270055AF2-134 C O1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
13.183
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
944971AF1-162 GEN
Solar/Wind Harmer
6.272
24639705ELKHART HY
Adder
0.138
963741AG1-226 GEN
Solar/Wind Harmer
14.786
957891AF2-083 GEN
Solar/Wind Harmer
10.385
945111AF1-176 GEN
Solar/Wind Harmer
11.117
274773LINCOLN ;4U
Adder
7.522
274774LINCOLN ;5U
Adder
7.522
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.244
274751CRETE EC ;1U
Adder
7.339
274754CRETE EC ;4U
Adder
7.339
274723RIVER EC ;12
Adder
15.953
274812UNIV PK N;8U
Adder
4.454
274802UNIV PARK;5U
Adder
5.179
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
14.566
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
4.617
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.001
274861TOP CROP ;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.223
276882AE2-255 GEN
Solar/Wind Harmer
0.717
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
8.588
962781AG1-127 GEN
Solar/Wind Harmer
5.837
274872LEEDK;1U
Solar/Wind Harmer
0
971403AH1-188 GEN
Solar/Wind Harmer
8.564
970569AG2-363 GEN
Solar/Wind Harmer
18.35
23583801GRNGAP
Solar/Wind Helper
4.857
316095T157 G97
Solar/Wind Helper
1.299
23546401DTGZ2-030
Solar/Wind Helper
0.075
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238185AF2-356 C
Solar/Wind Helper
2.003
237038AE2-054 C
Solar/Wind Helper
0.227
235067AD1-061 GEN
Solar/Wind Helper
0.371
237085AD2-009_GEN
Solar/Wind Helper
1.37
238120AE2-309 GEN
Solar/Wind Helper
0.408
237002AB1-128_GEN
Solar/Wind Helper
0.369
238126S14_GEN_1
Solar/Wind Helper
0.641
23777801MSM_W1-116
Solar/Wind Helper
0.096
957471AF2-041 GEN
Solar/Wind Harmer
3.09
959081AF2-199 GEN
Solar/Wind Harmer
1.03
971067AG2-660 GEN
Solar/Wind Harmer
0.343
23559001PLEAS1
50/50
11.247
23562401OGROV2
50/50
2.416
24318805MLG1
50/50
6.319
24721905FLATG4
Adder
23.461
962771AG1-126 GEN
Solar/Wind Harmer
29.52
970153AG2-106 GEN
Solar/Wind Harmer
18.85
270512AE1-227 GEN2
Solar/Wind Harmer
1.908
971191AH1-055 GEN
Solar/Wind Harmer
18.254
970879AG2-548 GEN
Solar/Wind Harmer
5.141
961921AG1-034 GEN
Solar/Wind Harmer
6.223
24686405CER G5
Adder
8.185
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
942051AE2-217 GEN
Solar/Wind Harmer
12.329
253325AC1-069 GEN
Solar/Wind Harmer
0.008
270518AE2-148 GEN
Solar/Wind Harmer
0.56
270367AC2-061_GEN
Solar/Wind Harmer
0
253394AE2-221_GEN
Solar/Wind Harmer
0
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.662
270186AC1-089 GEN
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.908
253371AE2-315 SEC2
Adder
1.805
252507AC2-088 GEN
Solar/Wind Harmer
0.298
252519AF1-045_GEN
Solar/Wind Harmer
3.45
270391AF1-285 GEN3
Solar/Wind Harmer
0.441
970191AG2-125 GEN
Solar/Wind Harmer
1.699
25196608WSDLE5
Adder
8.09
25194608D.CRK4
Adder
1.552
25196008MFTGT1
Adder
1.256
972167AH1-666 GEN
Solar/Wind Harmer
5.179
958171AF2-111 GEN
Solar/Wind Harmer
16.173
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
28.761
270004AE1-209 GEN
Solar/Wind Harmer
1.388
946031AF1-268 GEN
Solar/Wind Harmer
6.094
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.603
970825AG2-519 GEN
Solar/Wind Harmer
4.82
970289AG2-191 GEN
Solar/Wind Harmer
0.702
247642Z2-115 C
Solar/Wind Harmer
0.003
270043AE2-236 GEN
Solar/Wind Harmer
4.076
965021AG1-366 GEN
Solar/Wind Harmer
2.113
24728705AND G3
Adder
7.256
24728505AND G1
Adder
3.47
971347AH1-153 GEN
Solar/Wind Harmer
3.154
971199AH1-059 GEN
Solar/Wind Harmer
1.321
24690905MDL-1G C
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.226
970781AG2-491 GEN
Solar/Wind Harmer
6.287
270491AE1-102 GEN2
Solar/Wind Harmer
0.817
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24695305TIMB G C
Solar/Wind Harmer
0.532
270063AE2-323 C
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
5.05
270505AE1-170 C O1
Solar/Wind Harmer
6.542
274772LINCOLN ;3U
Adder
7.522
274752CRETE EC ;2U
Adder
7.339
274753CRETE EC ;3U
Adder
7.339
274724RIVER EC ;11
Adder
15.767
970193AG2-126 GEN
Solar/Wind Harmer
9.309
274814UNIV PK N;0U
Adder
4.493
274807UNIV PK N;3U
Adder
4.483
274811UNIV PK N;7U
Adder
4.454
274803UNIV PARK;6U
Adder
5.179
274887GEN-1.85
Solar/Wind Harmer
0.161
276843GEN-1.7
Solar/Wind Harmer
0.2
276806AD2-047 C O1
Solar/Wind Harmer
3.512
939351AE1-166 GEN
Solar/Wind Harmer
0
274826FISK ;BP
Adder
9.721
972038AH1-567 GEN2
Adder
0.324
970707AG2-453 GEN
Solar/Wind Harmer
20.232
972259AH1-714 GEN
Adder
16.936
274729ELWOOD EC;1P
Adder
14.566
274730ELWOOD EC;6P
Adder
14.566
274734ELWOOD EC;8P
Adder
14.566
274736ELWOOD EC;9P
Adder
0.016
943121AE2-341 GEN
Solar/Wind Harmer
10.337
943591AF1-030 GEN
Solar/Wind Harmer
6.874
274862TOP CROP ;2U
Solar/Wind Harmer
0.832
276868AE1-113 GEN
Solar/Wind Harmer
1.228
274879MINONK ;1U
Solar/Wind Harmer
0.256
965091AG1-374 GEN
Solar/Wind Harmer
18.362
959611AF2-252 GEN
Solar/Wind Harmer
2.04
946671AF1-331 GEN
Solar/Wind Harmer
0.653
274855GSG-6 ;RU
Solar/Wind Harmer
0.223
274850MENDOTA H;RU
Solar/Wind Harmer
0.071
970571AG2-364 GEN
Solar/Wind Harmer
12.233
964991AG1-363 GEN
Solar/Wind Helper
4.131
238152AF2-075_GEN
Solar/Wind Helper
0.595
238175AF1-290_GEN
Solar/Wind Helper
0.13
238108AE1-109 GEN1
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
23777901MDS_W4-102
Solar/Wind Helper
0.147
235063AE1-101 C2
Solar/Wind Helper
1.383
237001AB1-127_GEN
Solar/Wind Helper
0.369
238127S14_GEN_2
Solar/Wind Helper
0.641
959091AF2-200 GEN
Solar/Wind Harmer
2.06
CPLELTFEXP_CPLE->PJM
CLTF
1.296
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.919
NYPJM->LTFIMP_NY
CLTF
4.411
LGEELTFEXP_LGEE->PJM
CLTF
6.118
WECLTFEXP_WEC->PJM
CLTF
3.339
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312
LAGNLTFEXP_LAGN->PJM
CLTF
13.85
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.952
TVALTFEXP_TVA->PJM
CLTF
6.885
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.746
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.223
MECLTFEXP_MEC->PJM
CLTF
14.081
SIGELTFEXP_SIGE->PJM
CLTF
0.455

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-028_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:138.41 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5248.4
MW Contribution:
15.94
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
940611AE2-048 GEN
Solar/Wind Harmer
17.232
941391AE2-136 GEN
Solar/Wind Harmer
9.707
270291AC1-194 GEN
Solar/Wind Harmer
0
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.149
270432AC2-029 GEN
Solar/Wind Harmer
3.088
270263AC1-001 GEN
Solar/Wind Harmer
0.696
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
945631AF1-228 GEN
Solar/Wind Harmer
0.001
971985AH1-537 GEN
Solar/Wind Harmer
2.039
943861AF1-054 GEN
Solar/Wind Harmer
2.63
943851AF1-053 GEN
Solar/Wind Harmer
1.821
270340AC2-060 GEN
Solar/Wind Harmer
0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.733
253406AD2-031_GEN
Solar/Wind Harmer
0.497
253372AE2-315 SEC3
Adder
1.805
253372AE2-315 SEC3
Adder
1.805
25306009OHH W.
Adder
2.738
270578AF1-285 GEN2
Solar/Wind Harmer
0.441
25196408WSDLE3
Adder
8.328
25196308WSDLE2
Adder
8.256
25196208WSDLE1
Adder
8.235
25196708WSDLE6
Adder
8.215
25196508WSDLE4
Adder
8.008
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.918
25196108MFTGT2
Adder
1.43
25196108MFTGT2
Adder
1.328
972163AH1-664 GEN
Solar/Wind Harmer
7.194
972165AH1-665 GEN
Solar/Wind Harmer
5.762
971029AG2-637 GEN
Solar/Wind Harmer
9.669
270543AE2-219 C
Solar/Wind Harmer
4.502
247536S-71 GEN
Solar/Wind Harmer
0.257
24729505KEY G4
Adder
5.966
945581AF1-223 GEN
Solar/Wind Harmer
0
270356AE2-297 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
2.497
971609AH1-304 GEN
Solar/Wind Harmer
1.044
270071AF1-092 GEN
Solar/Wind Harmer
12.235
970289AG2-191 GEN
Solar/Wind Harmer
1.213
963791AG1-232 GEN
Solar/Wind Harmer
8.578
959331AF2-224 GEN
Solar/Wind Harmer
4.437
247521TR3_G114
Solar/Wind Harmer
0.229
965051AG1-369 GEN
Solar/Wind Harmer
3.151
965041AG1-368 GEN
Solar/Wind Harmer
6.303
339216AC1-074 GEN
Solar/Wind Harmer
0.168
971611AH1-305 GEN
Solar/Wind Harmer
3.744
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.796
958391AF2-133 GEN
Solar/Wind Harmer
0.001
970031AG2-029 GEN
Solar/Wind Harmer
3.403
24386405FR-21G C
Solar/Wind Harmer
0
957241AF2-018 GEN
Solar/Wind Harmer
0
270053AF1-130 C
Solar/Wind Harmer
13.997
960681AF2-359 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.713
971771AH1-392 GEN
Solar/Wind Harmer
6.254
270526AF1-158 GEN
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
7.522
274776LINCOLN ;7U
Adder
7.522
274777LINCOLN ;8U
Adder
7.522
972037AH1-567 GEN1
Adder
0.163
960591AF2-350 GEN
Solar/Wind Harmer
6.197
972228AH1-698 GEN2
Adder
3.29
972227AH1-698 GEN1
Adder
2.316
274827FISK ;RP
Adder
6.89
274800UNIV PARK;3U
Adder
5.177
274801UNIV PARK;4U
Adder
5.177
270399AC1-101 GEN
Solar/Wind Harmer
1.959
270400AC1-102 GEN
Solar/Wind Harmer
1.959
274687WILL CNTY;4U
Adder
24.769
274687WILL CNTY;4U
Adder
24.769
274728ELWOOD EC;5P
Adder
14.566
274731ELWOOD EC;2P
Adder
14.566
274733ELWOOD EC;3P
Adder
14.566
274735ELWOOD EC;4P
Adder
14.566
970833AG2-524 GEN
Solar/Wind Harmer
6.799
970833AG2-524 GEN
Solar/Wind Harmer
4.533
970179AG2-119 GEN
Solar/Wind Harmer
5.512
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970169AG2-114 GEN
Solar/Wind Harmer
6.152
970073AG2-061 GEN
Solar/Wind Harmer
2.049
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.441
274854TWINGROVE;U2
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
1.04
276861AD2-134 GEN
Solar/Wind Harmer
0.109
276863AD2-134 GEN
Solar/Wind Harmer
0.109
971675AH1-338 GEN
Solar/Wind Harmer
2.386
971411AH1-196 GEN
Solar/Wind Harmer
9.174
23750701CROSSCHOOL
Solar/Wind Helper
1.155
238169AE2-226 GEN1
Solar/Wind Helper
0.584
238170AE2-226 GEN2
Solar/Wind Helper
0.584
23779801AA1-109
Solar/Wind Helper
0.162
238118U2-030_1
Solar/Wind Helper
0.26
971171AH1-044 GEN
Solar/Wind Harmer
2.06
970935AG2-582 GEN
50/50
1217.29
23684101S70BUS1
50/50
0.309
24318905MLG2
50/50
4.655
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0
971073AG2-665 GEN
Solar/Wind Harmer
5.141
970879AG2-548 GEN
Solar/Wind Harmer
1.168
270269AC2-059
Solar/Wind Harmer
0.001
24723005RIVRG1
Adder
18.491
24723105RIVRG2
Adder
18.491
942861AE2-305 GEN
Solar/Wind Harmer
5.328
962581AG1-107 GEN
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
0.953
25326109MON D
Adder
1.253
253370AE2-315 SEC1
Adder
1.908
25322209TAIT E
Adder
9.279
25322209TAIT E
Adder
9.07
25183208HLCRTG
Solar/Wind Harmer
0
252509AD1-136 GEN
Solar/Wind Harmer
0.033
938701AE1-092 GEN
Solar/Wind Harmer
10.602
971655AH1-328 GEN
Solar/Wind Harmer
2.343
25194408D.CRK1
Adder
7.139
25194508D.CRK3
Adder
1.335
970329AG2-216 GEN
Solar/Wind Harmer
2.837
25326509SID D
Adder
1.233
270462AD2-086
Solar/Wind Harmer
0
24728805RICHG1
Adder
3.492
24728905RICHG2
Adder
3.492
970883AG2-550 GEN
Solar/Wind Harmer
6.432
970885AG2-551 GEN
Solar/Wind Harmer
2.144
270383AD1-128 GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.428
960971AF2-388 GEN
Solar/Wind Harmer
3.762
247621Y3-024
Adder
0.222
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.48
270031AE2-169
Solar/Wind Harmer
3.515
270599AE1-208 GEN
Solar/Wind Harmer
5.858
971613AH1-306 GEN
Solar/Wind Harmer
3.066
942221AE2-234 GEN
Solar/Wind Harmer
2.563
970291AG2-192 GEN
Solar/Wind Harmer
0.83
970291AG2-192 GEN
Solar/Wind Harmer
0.383
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270246TR4_N_V150
Solar/Wind Harmer
0.04
270247TR4_N_V136
Solar/Wind Harmer
0.04
970349AG2-230 GEN
Solar/Wind Harmer
9.463
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.253
24697605MDL-3G C
Solar/Wind Harmer
0
972043AH1-570 GEN
Solar/Wind Harmer
1.634
972045AH1-571 GEN
Solar/Wind Harmer
1.309
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.711
965681AG1-436 GEN
Solar/Wind Harmer
7.827
965791AG1-447 GEN
Solar/Wind Harmer
5.74
247620Y3-023
Adder
0.413
247607V1-011 GEN
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
3.645
971587AH1-292 GEN
Solar/Wind Harmer
4.565
961051AF2-396 GEN
Solar/Wind Harmer
12.441
961051AF2-396 GEN
Solar/Wind Harmer
8.294
274770LINCOLN ;1U
Adder
7.522
274771LINCOLN ;2U
Adder
7.522
945391AF1-204 GEN
Solar/Wind Harmer
6.594
274805UNIV PK N;1U
Adder
4.464
274808UNIV PK N;4U
Adder
4.435
971125AH1-004 GEN
Solar/Wind Harmer
2.48
970107AG2-081 GEN
Solar/Wind Harmer
1.86
274888KELLY CRK;1U
Solar/Wind Harmer
0.361
276776AD2-060 GEN
Solar/Wind Harmer
0.661
958011AF2-095 GEN
Solar/Wind Harmer
8.924
970941AG2-585 GEN
Solar/Wind Harmer
3.408
276897AD1-100 C
Solar/Wind Harmer
15.489
970623AG2-406 GEN
Solar/Wind Harmer
1.134
276893AG1-478 C
Solar/Wind Harmer
0.412
958481AF2-142 GEN
Solar/Wind Harmer
9.241
23559101PLEAS2
50/50
11.247
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.221
944231AF1-091 GEN
Solar/Wind Harmer
14.169
962691AG1-118 GEN
Solar/Wind Harmer
18.411
942111AE2-223 GEN
Solar/Wind Harmer
1.994
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.04
316097T157 G90
Solar/Wind Helper
1.299
238147AE2-230_GEN1
Solar/Wind Helper
0.416
238148AE2-230_GEN2
Solar/Wind Helper
0.416
238149AF1-291A_GEN
Solar/Wind Helper
0.119
237061AD1-155 GEN
Solar/Wind Helper
1.477
235020AA1-095 C
Solar/Wind Helper
0.044
238221AF1-254 C O1
Solar/Wind Helper
0.228
237080AD1-060 GEN
Solar/Wind Helper
0.284
235062AE1-101 C1
Solar/Wind Helper
1.383
235531U2-073 GEN
Solar/Wind Helper
2.544
238117U2-030
Solar/Wind Helper
0.26
971341AH1-150 GEN
Solar/Wind Harmer
2.06
971343AH1-151 GEN
Solar/Wind Harmer
2.06
23559001PLEAS1
50/50
11.247
23562401OGROV2
50/50
2.416
24318805MLG1
50/50
6.319
24721905FLATG4
Adder
23.461
962771AG1-126 GEN
Solar/Wind Harmer
29.52
970153AG2-106 GEN
Solar/Wind Harmer
18.85
270512AE1-227 GEN2
Solar/Wind Harmer
1.908
971191AH1-055 GEN
Solar/Wind Harmer
18.254
23684201S70BUS2
50/50
0.315
23562301OGROV1
50/50
2.436
962761AG1-125 GEN
Solar/Wind Harmer
29.52
970149AG2-104 GEN
Solar/Wind Harmer
15.941
970155AG2-107 GEN
Solar/Wind Harmer
18.85
270510AE1-227 GEN1
Solar/Wind Harmer
1.908
960001AF2-291 GEN
Solar/Wind Harmer
0
971073AG2-665 GEN
Solar/Wind Harmer
1.168
270520AE2-214 GEN
Solar/Wind Harmer
0
972203AH1-686 GEN
Adder
2.3
270273AD2-016 GEN
Solar/Wind Harmer
0.712
24686505CER G6
Adder
8.25
972269AH1-719 GEN
Adder
2.27
24723205RIVRG3
Adder
18.491
253333AC1-068 GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.663
253370AE2-315 SEC1
Adder
1.908
253371AE2-315 SEC2
Adder
1.805
25326309TAIT D
Adder
1.043
252516AE2-318_GEN
Solar/Wind Harmer
7.407
252510AF1-249 C
Solar/Wind Harmer
0.05
25194608D.CRK4
Adder
1.552
25196808ZIMRHP
Adder
71.417
270317AD1-130_GEN
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.297
945681AF1-233 GEN
Solar/Wind Harmer
12.198
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.711
965651AG1-433 GEN
Solar/Wind Harmer
1.881
958861AF2-177 GEN
Solar/Wind Harmer
2.778
945371AF1-202 GEN
Solar/Wind Harmer
0
971995AH1-542 GEN
Solar/Wind Harmer
2.35
270005AE1-210 C O1
Solar/Wind Harmer
1.388
970773AG2-487 GEN
Solar/Wind Harmer
1.132
970825AG2-519 GEN
Solar/Wind Harmer
2.272
970091AG2-072 GEN
Adder
70.262
270594AE1-207 GEN
Solar/Wind Harmer
7.153
270032AE2-172
Solar/Wind Harmer
4.258
270024AE2-089 GEN
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
7.119
965011AG1-365 GEN
Solar/Wind Harmer
6.339
24728605AND G2
Adder
3.47
965421AG1-410 GEN
Solar/Wind Harmer
18.877
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
7.861
246936BC-WTG1
Solar/Wind Harmer
0.253
270489AE1-102 GEN1
Solar/Wind Harmer
0.817
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.17
270055AF2-134 C O1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
13.183
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
944971AF1-162 GEN
Solar/Wind Harmer
6.272
24639705ELKHART HY
Adder
0.138
963741AG1-226 GEN
Solar/Wind Harmer
14.786
957891AF2-083 GEN
Solar/Wind Harmer
10.385
945111AF1-176 GEN
Solar/Wind Harmer
11.117
274773LINCOLN ;4U
Adder
7.522
274774LINCOLN ;5U
Adder
7.522
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.244
274751CRETE EC ;1U
Adder
7.339
274754CRETE EC ;4U
Adder
7.339
274723RIVER EC ;12
Adder
15.953
274812UNIV PK N;8U
Adder
4.454
274802UNIV PARK;5U
Adder
5.179
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
14.566
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
4.617
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.001
274861TOP CROP ;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.223
276882AE2-255 GEN
Solar/Wind Harmer
0.717
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
8.588
962781AG1-127 GEN
Solar/Wind Harmer
5.837
274872LEEDK;1U
Solar/Wind Harmer
0
971403AH1-188 GEN
Solar/Wind Harmer
8.564
970569AG2-363 GEN
Solar/Wind Harmer
18.35
23583801GRNGAP
Solar/Wind Helper
4.857
316095T157 G97
Solar/Wind Helper
1.299
23546401DTGZ2-030
Solar/Wind Helper
0.075
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238185AF2-356 C
Solar/Wind Helper
2.003
237038AE2-054 C
Solar/Wind Helper
0.227
235067AD1-061 GEN
Solar/Wind Helper
0.371
237085AD2-009_GEN
Solar/Wind Helper
1.37
238120AE2-309 GEN
Solar/Wind Helper
0.408
237002AB1-128_GEN
Solar/Wind Helper
0.369
238126S14_GEN_1
Solar/Wind Helper
0.641
23777801MSM_W1-116
Solar/Wind Helper
0.096
957471AF2-041 GEN
Solar/Wind Harmer
3.09
959081AF2-199 GEN
Solar/Wind Harmer
1.03
971067AG2-660 GEN
Solar/Wind Harmer
0.343
970879AG2-548 GEN
Solar/Wind Harmer
5.141
961921AG1-034 GEN
Solar/Wind Harmer
6.223
24686405CER G5
Adder
8.185
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
942051AE2-217 GEN
Solar/Wind Harmer
12.329
253325AC1-069 GEN
Solar/Wind Harmer
0.008
270518AE2-148 GEN
Solar/Wind Harmer
0.56
270367AC2-061_GEN
Solar/Wind Harmer
0
253394AE2-221_GEN
Solar/Wind Harmer
0
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.662
270186AC1-089 GEN
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.908
253371AE2-315 SEC2
Adder
1.805
252507AC2-088 GEN
Solar/Wind Harmer
0.298
252519AF1-045_GEN
Solar/Wind Harmer
3.45
270391AF1-285 GEN3
Solar/Wind Harmer
0.441
970191AG2-125 GEN
Solar/Wind Harmer
1.699
25196608WSDLE5
Adder
8.09
25194608D.CRK4
Adder
1.552
25196008MFTGT1
Adder
1.256
972167AH1-666 GEN
Solar/Wind Harmer
5.179
958171AF2-111 GEN
Solar/Wind Harmer
16.173
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
28.761
270004AE1-209 GEN
Solar/Wind Harmer
1.388
946031AF1-268 GEN
Solar/Wind Harmer
6.094
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.603
970825AG2-519 GEN
Solar/Wind Harmer
4.82
970289AG2-191 GEN
Solar/Wind Harmer
0.702
247642Z2-115 C
Solar/Wind Harmer
0.003
270043AE2-236 GEN
Solar/Wind Harmer
4.076
965021AG1-366 GEN
Solar/Wind Harmer
2.113
24728705AND G3
Adder
7.256
24728505AND G1
Adder
3.47
971347AH1-153 GEN
Solar/Wind Harmer
3.154
971199AH1-059 GEN
Solar/Wind Harmer
1.321
24690905MDL-1G C
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.226
970781AG2-491 GEN
Solar/Wind Harmer
6.287
270491AE1-102 GEN2
Solar/Wind Harmer
0.817
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24695305TIMB G C
Solar/Wind Harmer
0.532
270063AE2-323 C
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
5.05
270505AE1-170 C O1
Solar/Wind Harmer
6.542
274772LINCOLN ;3U
Adder
7.522
274752CRETE EC ;2U
Adder
7.339
274753CRETE EC ;3U
Adder
7.339
274724RIVER EC ;11
Adder
15.767
970193AG2-126 GEN
Solar/Wind Harmer
9.309
274814UNIV PK N;0U
Adder
4.493
274807UNIV PK N;3U
Adder
4.483
274811UNIV PK N;7U
Adder
4.454
274803UNIV PARK;6U
Adder
5.179
274887GEN-1.85
Solar/Wind Harmer
0.161
276843GEN-1.7
Solar/Wind Harmer
0.2
276806AD2-047 C O1
Solar/Wind Harmer
3.512
939351AE1-166 GEN
Solar/Wind Harmer
0
274826FISK ;BP
Adder
9.721
972038AH1-567 GEN2
Adder
0.324
970707AG2-453 GEN
Solar/Wind Harmer
20.232
972259AH1-714 GEN
Adder
16.936
274729ELWOOD EC;1P
Adder
14.566
274730ELWOOD EC;6P
Adder
14.566
274734ELWOOD EC;8P
Adder
14.566
274736ELWOOD EC;9P
Adder
0.016
943121AE2-341 GEN
Solar/Wind Harmer
10.337
943591AF1-030 GEN
Solar/Wind Harmer
6.874
274862TOP CROP ;2U
Solar/Wind Harmer
0.832
276868AE1-113 GEN
Solar/Wind Harmer
1.228
274879MINONK ;1U
Solar/Wind Harmer
0.256
965091AG1-374 GEN
Solar/Wind Harmer
18.362
959611AF2-252 GEN
Solar/Wind Harmer
2.04
946671AF1-331 GEN
Solar/Wind Harmer
0.653
274855GSG-6 ;RU
Solar/Wind Harmer
0.223
274850MENDOTA H;RU
Solar/Wind Harmer
0.071
970571AG2-364 GEN
Solar/Wind Harmer
12.233
964991AG1-363 GEN
Solar/Wind Helper
4.131
238152AF2-075_GEN
Solar/Wind Helper
0.595
238175AF1-290_GEN
Solar/Wind Helper
0.13
238108AE1-109 GEN1
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
23777901MDS_W4-102
Solar/Wind Helper
0.147
235063AE1-101 C2
Solar/Wind Helper
1.383
237001AB1-127_GEN
Solar/Wind Helper
0.369
238127S14_GEN_2
Solar/Wind Helper
0.641
959091AF2-200 GEN
Solar/Wind Harmer
2.06
CPLELTFEXP_CPLE->PJM
CLTF
1.296
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.919
NYPJM->LTFIMP_NY
CLTF
4.411
LGEELTFEXP_LGEE->PJM
CLTF
6.118
WECLTFEXP_WEC->PJM
CLTF
3.339
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312
LAGNLTFEXP_LAGN->PJM
CLTF
13.85
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.952
TVALTFEXP_TVA->PJM
CLTF
6.885
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.746
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.223
MECLTFEXP_MEC->PJM
CLTF
14.081
SIGELTFEXP_SIGE->PJM
CLTF
0.455

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-024_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.25 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:5006.21
MW Contribution:
25.33
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270459AD2-067 GEN
Solar/Wind Harmer
10.212
961821AG1-024 GEN
Solar/Wind Harmer
10.368
972239AH1-704 GEN
Adder
2.66
241955AC1-078 GEN
Solar/Wind Harmer
8.781
241973AD2-163_GEN1
Solar/Wind Harmer
2.319
241974AD2-163_GEN2
Solar/Wind Harmer
2.319
943861AF1-054 GEN
Solar/Wind Harmer
4.476
943851AF1-053 GEN
Solar/Wind Harmer
2.163
945631AF1-228 GEN
Solar/Wind Harmer
5.449
270223U2-072_GEN1
Solar/Wind Harmer
2.274
270224U2-072_GEN2
Solar/Wind Harmer
2.274
270227U2-072_GEN3
Solar/Wind Harmer
2.274
270228U2-072_GEN4
Solar/Wind Harmer
2.274
270231U2-072_GEN5
Solar/Wind Harmer
2.274
270578AF1-285 GEN2
Solar/Wind Harmer
0.536
270432AC2-029 GEN
Solar/Wind Harmer
8.025
253338AC1-165 GEN
Solar/Wind Harmer
1.235
253343AC1-166 GEN
Solar/Wind Harmer
1.235
270302AB2-170 GEN
Solar/Wind Harmer
9.522
940611AE2-048 GEN
Solar/Wind Harmer
24.76
941391AE2-136 GEN
Solar/Wind Harmer
12.83
270263AC1-001 GEN
Solar/Wind Harmer
1.17
241972AD1-140 GEN
Solar/Wind Harmer
5.01
270291AC1-194 GEN
Solar/Wind Harmer
5.61
270340AC2-060 GEN
Solar/Wind Harmer
3.331
970179AG2-119 GEN
Solar/Wind Harmer
8.806
253372AE2-315 SEC3
Adder
2.062
253372AE2-315 SEC3
Adder
2.062
25306009OHH W.
Adder
3.128
253406AD2-031_GEN
Solar/Wind Harmer
1.383
957201AF2-014 GEN
Solar/Wind Harmer
4.888
270435AC2-044 GEN
Solar/Wind Harmer
2.156
253433AC1-085 GEN1
Solar/Wind Harmer
5.708
253432AC1-085 GEN2
Solar/Wind Harmer
0.287
247521TR3_G114
Solar/Wind Harmer
3.604
270191TR4_S_V150
Solar/Wind Harmer
3.216
965051AG1-369 GEN
Solar/Wind Harmer
5.355
959331AF2-224 GEN
Solar/Wind Harmer
10.725
270377AD1-106 GEN
Solar/Wind Harmer
5.62
270007AE1-245 C
Solar/Wind Harmer
5.779
965041AG1-368 GEN
Solar/Wind Harmer
10.701
24729505KEY G4
Adder
6.914
966831AG1-554 GEN
Solar/Wind Harmer
1.275
971567AH1-282 GEN
Solar/Wind Harmer
5.316
270071AF1-092 GEN
Solar/Wind Harmer
15.971
963791AG1-232 GEN
Solar/Wind Harmer
14.371
971985AH1-537 GEN
Solar/Wind Harmer
18.964
24318805MLG1
50/50
10.127
23559001PLEAS1
50/50
6.362
270051AF1-062 GEN
50/50
11.798
270475AD2-096_GEN
50/50
7.137
962771AG1-126 GEN
Solar/Wind Harmer
41.016
970153AG2-106 GEN
Solar/Wind Harmer
17.885
961921AG1-034 GEN
Solar/Wind Harmer
15.551
270284AF1-227 GEN1
Solar/Wind Harmer
6.768
270287AF1-227 GEN3
Solar/Wind Harmer
2.504
24721905FLATG4
Adder
24.045
942051AE2-217 GEN
Solar/Wind Harmer
20.995
960801AF2-371 GEN
Solar/Wind Harmer
2.937
964871AG1-351 GEN
Solar/Wind Harmer
2.028
942871AE2-306 GEN
Solar/Wind Harmer
1.045
270391AF1-285 GEN3
Solar/Wind Harmer
0.536
270518AE2-148 GEN
Solar/Wind Harmer
13.818
253325AC1-069 GEN
Solar/Wind Harmer
1.191
276820AF1-078_GEN
Solar/Wind Harmer
1.776
958581AF2-149 GEN
Solar/Wind Harmer
4.712
971199AH1-059 GEN
Solar/Wind Harmer
2.312
970879AG2-548 GEN
Solar/Wind Harmer
8.771
960071AF2-298 GEN
Solar/Wind Harmer
1.647
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.18
253371AE2-315 SEC2
Adder
2.062
970065AG2-057 GEN
Solar/Wind Harmer
0.921
957541AF2-048 GEN
Solar/Wind Harmer
1.717
253394AE2-221_GEN
Solar/Wind Harmer
4.9
246938BC-WTG3
Solar/Wind Harmer
4.289
270491AE1-102 GEN2
Solar/Wind Harmer
1.401
971191AH1-055 GEN
Solar/Wind Harmer
20.077
253317AC1-085 GEN4
Solar/Wind Harmer
8.992
946181AF1-283 GEN
Solar/Wind Harmer
13.963
965021AG1-366 GEN
Solar/Wind Harmer
2.494
958091AF2-103 GEN
Solar/Wind Harmer
0.173
24695305TIMB G C
Solar/Wind Harmer
3.573
270588AE1-091_GEN
Solar/Wind Harmer
11.753
944531AF1-118 GEN
Solar/Wind Harmer
37.358
270043AE2-236 GEN
Solar/Wind Harmer
5.865
252519AF1-045_GEN
Solar/Wind Harmer
3.859
270367AC2-061_GEN
Solar/Wind Harmer
3.367
252524AE2-267 GEN
Solar/Wind Harmer
1.667
25196608WSDLE5
Adder
9.072
25194608D.CRK4
Adder
1.739
252507AC2-088 GEN
Solar/Wind Harmer
1.892
270044AE2-322 C
Solar/Wind Harmer
1.388
270063AE2-323 C
Solar/Wind Harmer
2.32
962031AG1-047 GEN
Solar/Wind Harmer
3.189
957741AF2-068 GEN
Solar/Wind Harmer
15.82
971347AH1-153 GEN
Solar/Wind Harmer
5.266
270512AE1-227 GEN2
Solar/Wind Harmer
2.212
270186AC1-089 GEN
Solar/Wind Harmer
6.425
946031AF1-268 GEN
Solar/Wind Harmer
8.725
270004AE1-209 GEN
Solar/Wind Harmer
5.743
24379505HDWTR1G C
Solar/Wind Harmer
8.305
270240V3-007_GEN2
Solar/Wind Harmer
6.498
270330AC1-082 GEN2
Solar/Wind Harmer
0.5
270329AC1-082 GEN1
Solar/Wind Harmer
0.5
970825AG2-519 GEN
Solar/Wind Harmer
5.915
247643Z2-116 C
Solar/Wind Harmer
0.073
25196008MFTGT1
Adder
1.404
274752CRETE EC ;2U
Adder
8.473
274753CRETE EC ;3U
Adder
8.473
274772LINCOLN ;3U
Adder
8.673
274724RIVER EC ;11
Adder
18.196
274814UNIV PK N;0U
Adder
5.182
274807UNIV PK N;3U
Adder
5.171
274811UNIV PK N;7U
Adder
5.137
274803UNIV PARK;6U
Adder
5.968
24728705AND G3
Adder
8.209
24728505AND G1
Adder
3.925
274826FISK ;BP
Adder
11.201
972038AH1-567 GEN2
Adder
0.373
972259AH1-714 GEN
Adder
19.5
274676JOLIET 29;8U
Adder
30.174
274729ELWOOD EC;1P
Adder
16.762
274730ELWOOD EC;6P
Adder
16.762
274734ELWOOD EC;8P
Adder
16.762
274736ELWOOD EC;9P
Adder
16.762
274682WAUKEGAN ;7U
Adder
18.178
964991AG1-363 GEN
Solar/Wind Helper
5.171
238108AE1-109 GEN1
Solar/Wind Helper
0.115
238110AE1-109 GEN3
Solar/Wind Helper
0.115
238127S14_GEN_2
Solar/Wind Helper
0.836
238175AF1-290_GEN
Solar/Wind Helper
0.158
238152AF2-075_GEN
Solar/Wind Helper
0.715
23777901MDS_W4-102
Solar/Wind Helper
0.179
23562501BACKB
Solar/Wind Helper
1.023
235063AE1-101 C2
Solar/Wind Helper
1.678
237001AB1-127_GEN
Solar/Wind Helper
0.446
237048AF1-022 C
Solar/Wind Helper
0.186
316415AF1-147_GEN2
Solar/Wind Helper
0.898
205916AD1-020 GEN
Solar/Wind Helper
1.732
270119AB2-067 GEN1
50/50
7.109
270120AB2-067 GEN2
50/50
7.109
24318905MLG2
50/50
7.027
270349AD2-093_GEN
Solar/Wind Harmer
4.455
270471AD2-092_GEN
Solar/Wind Harmer
4.455
270054AF2-122 C O1
Solar/Wind Harmer
3.972
946101AF1-275 GEN
Solar/Wind Harmer
1.811
253383AE2-342_GEN
Solar/Wind Harmer
1.04
942861AE2-305 GEN
Solar/Wind Harmer
9.069
938701AE1-092 GEN
Solar/Wind Harmer
23.766
270462AD2-086
Solar/Wind Harmer
7.908
270269AC2-059
Solar/Wind Harmer
10.571
253378AE2-206_GEN
Solar/Wind Harmer
3.997
972159AH1-661 GEN
Adder
1.106
253415AE1-040 GEN
Solar/Wind Harmer
1.242
25326509SID D
Adder
1.451
241960AC2-195 GEN
Solar/Wind Harmer
3.055
971073AG2-665 GEN
Solar/Wind Harmer
8.771
970879AG2-548 GEN
Solar/Wind Harmer
1.275
25326109MON D
Adder
1.442
25322209TAIT E
Adder
10.635
25322209TAIT E
Adder
10.396
253370AE2-315 SEC1
Adder
2.18
927014AC1-188 GEN
Solar/Wind Harmer
1.717
253349AC2-067 GEN
Solar/Wind Harmer
2.203
253400AC2-068 GEN
Solar/Wind Harmer
0.886
246937BC-WTG2
Solar/Wind Harmer
4.216
270246TR4_N_V150
Solar/Wind Harmer
0.912
270247TR4_N_V136
Solar/Wind Harmer
0.912
942801AE2-298 GEN
Solar/Wind Harmer
1.621
247607V1-011 GEN
Solar/Wind Harmer
4.231
962581AG1-107 GEN
Solar/Wind Harmer
5.356
961491AF2-440 GEN
Solar/Wind Harmer
2.226
25183208HLCRTG
Solar/Wind Harmer
6.427
944541AF1-119 GEN
Solar/Wind Harmer
4.444
960971AF2-388 GEN
Solar/Wind Harmer
11.601
942221AE2-234 GEN
Solar/Wind Harmer
3.71
25194408D.CRK1
Adder
8
25194508D.CRK3
Adder
1.496
252509AD1-136 GEN
Solar/Wind Harmer
0.27
970883AG2-550 GEN
Solar/Wind Harmer
10.561
970885AG2-551 GEN
Solar/Wind Harmer
2.456
247621Y3-024
Adder
0.255
270201AC2-176 GEN
Solar/Wind Harmer
5.42
964611AG1-324 GEN
Solar/Wind Harmer
0.551
208835TUHI V3-051
Solar/Wind Helper
0.022
205932AD2-116_GEN
Solar/Wind Helper
0.514
233918AB1-142 GEN
Solar/Wind Helper
0.508
233944AB2-135 GEN
Solar/Wind Helper
0.596
233996TM1833_GEN
Solar/Wind Helper
0.207
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232426Y1-080 FULL
Solar/Wind Helper
0.039
232404W1-003 C
Solar/Wind Helper
0.513
232408W1-005 C
Solar/Wind Helper
0.513
316447AC1-158 HLD
Solar/Wind Helper
2.876
316044AC1-158 PL1
Solar/Wind Helper
1.307
228729W2-030 C
Solar/Wind Helper
0.112
219766PARADISE C
Solar/Wind Helper
0.055
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.116
203975AE1-071-GEN
Solar/Wind Helper
2.526
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.065
20714528FRN_Y2-051
Solar/Wind Helper
0.058
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
218440SUMMTASSOC C
Solar/Wind Helper
0.017
218428ETC SOLAR C
Solar/Wind Helper
0.005
219908AB1-139 C
Solar/Wind Helper
0.075
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673628F1S_V4-069
Solar/Wind Helper
0.03
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207530AG1-191 GEN
Solar/Wind Helper
0.067
207439AE1-081 C O1
Solar/Wind Helper
0.019
20676328BVR_Y1-020
Solar/Wind Helper
0.027
207484AF2-139 C O1
Solar/Wind Helper
0.085
20674928WA_W3-044
Solar/Wind Helper
0.099
20674628WNG_W3-110
Solar/Wind Helper
0.09
20676228FRD_X1-012
Solar/Wind Helper
0.093
20675728RH_W2-091
Solar/Wind Helper
0.082
207518AF1-320_GEN
Solar/Wind Helper
1.586
20675828AU_W4-064
Solar/Wind Helper
0.03
211065PSPA IPP
Solar/Wind Helper
0.153
202652Y1-033 WT C
Solar/Wind Helper
0.504
961301AF2-421 GEN
Solar/Wind Helper
0.443
963151AG1-164 GEN
Solar/Wind Helper
0.443
961341AF2-425 GEN
Solar/Wind Helper
0.442
212507AE2-042_GEN
Solar/Wind Helper
1.561
270166AC1-044 GEN3
50/50
7.109
23559101PLEAS2
50/50
6.362
962761AG1-125 GEN
Solar/Wind Harmer
41.016
970149AG2-104 GEN
Solar/Wind Harmer
25.328
970155AG2-107 GEN
Solar/Wind Harmer
17.885
270286AF1-227 GEN2
Solar/Wind Harmer
2.504
270520AE2-214 GEN
Solar/Wind Harmer
7.243
270391AF1-285 GEN3
Solar/Wind Harmer
1.393
270578AF1-285 GEN2
Solar/Wind Harmer
1.393
253333AC1-068 GEN
Solar/Wind Harmer
1.191
270317AD1-130_GEN
Solar/Wind Harmer
3.64
270485AE1-090_GEN
Solar/Wind Harmer
0.688
270273AD2-016 GEN
Solar/Wind Harmer
3.013
971995AH1-542 GEN
Solar/Wind Harmer
12.463
972269AH1-719 GEN
Adder
2.545
971073AG2-665 GEN
Solar/Wind Harmer
1.275
25326309TAIT D
Adder
1.195
253370AE2-315 SEC1
Adder
2.18
253371AE2-315 SEC2
Adder
2.062
241813AF1-122_GEN
Solar/Wind Harmer
5.897
971201AH1-060 GEN
Solar/Wind Harmer
1.843
253398AE2-221_GEN2
Solar/Wind Harmer
4.9
246936BC-WTG1
Solar/Wind Harmer
4.216
270489AE1-102 GEN1
Solar/Wind Harmer
1.401
965421AG1-410 GEN
Solar/Wind Harmer
32.318
960001AF2-291 GEN
Solar/Wind Harmer
3.25
253316AC1-085 GEN3
Solar/Wind Harmer
8.992
946171AF1-282 GEN
Solar/Wind Harmer
10.741
965011AG1-365 GEN
Solar/Wind Harmer
10.725
270258AD1-119 GEN
Solar/Wind Harmer
2.156
965651AG1-433 GEN
Solar/Wind Harmer
5.801
252516AE2-318_GEN
Solar/Wind Harmer
10.604
970349AG2-230 GEN
Solar/Wind Harmer
15.797
270031AE2-169
Solar/Wind Harmer
8.576
270599AE1-208 GEN
Solar/Wind Harmer
8.576
270383AD1-128 GEN
Solar/Wind Harmer
6.419
926881AC1-175 GEN
Solar/Wind Harmer
5.862
247620Y3-023
Adder
0.483
944231AF1-091 GEN
Solar/Wind Harmer
18.887
24728805RICHG1
Adder
3.96
24728905RICHG2
Adder
3.96
274770LINCOLN ;1U
Adder
8.673
274771LINCOLN ;2U
Adder
8.673
274805UNIV PK N;1U
Adder
5.149
274808UNIV PK N;4U
Adder
5.115
274674JOLIET 9 ;6U
Adder
15.699
274696ROCKY RD ;4P
Adder
11.533
274695ROCKY RD ;2P
Adder
11.267
274693ROCKY RD ;1P
Adder
11.156
274697ROCKY RD ;3P
Adder
3.061
274683WAUKEGAN ;8U
Adder
21.305
274683WAUKEGAN ;8U
Adder
9.68
316097T157 G90
Solar/Wind Helper
1.515
235054AD2-180 GEN
Solar/Wind Helper
2.054
23585401KL_K28_T16
Solar/Wind Helper
1.5
235531U2-073 GEN
Solar/Wind Helper
3.347
238117U2-030
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.501
238148AE2-230_GEN2
Solar/Wind Helper
0.501
238149AF1-291A_GEN
Solar/Wind Helper
0.143
23751201ROTHROCK
Solar/Wind Helper
0.836
235020AA1-095 C
Solar/Wind Helper
0.054
237061AD1-155 GEN
Solar/Wind Helper
1.772
238221AF1-254 C O1
Solar/Wind Helper
0.278
237080AD1-060 GEN
Solar/Wind Helper
0.346
235062AE1-101 C1
Solar/Wind Helper
1.678
316411AF1-147_GEN1
Solar/Wind Helper
0.898
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.371
223402AF1-300 C
Solar/Wind Helper
0.371
316006AB2-029 C
Solar/Wind Helper
0.119
233930AB2-032 GEN
Solar/Wind Helper
0.385
232424Y1-079 C
Solar/Wind Helper
0.118
233982AB2-133 GEN
Solar/Wind Helper
0.363
232436AB1-176 C
Solar/Wind Helper
0.045
233946AB2-136 GEN
Solar/Wind Helper
0.575
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.972
232428Y3-058 C
Solar/Wind Helper
0.342
232410W1-006 C
Solar/Wind Helper
0.513
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.235
233954AC2-188 GEN
Solar/Wind Helper
0.235
230511AF1-262
Solar/Wind Helper
0.015
316045AC1-158 PL2
Solar/Wind Helper
4.182
316450AC1-158 RIC
Solar/Wind Helper
0.348
230433AD2-135 GEN
Solar/Wind Helper
0.017
228754AB1-001 C
Solar/Wind Helper
0.026
219904AC1-010 C
Solar/Wind Helper
0.061
219912AD2-042 GEN
Solar/Wind Helper
0.151
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219906AC1-017 C
Solar/Wind Helper
0.042
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.133
214067T20SOLAR
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.064
207459AE1-142 C O1
Solar/Wind Helper
0.293
20714828MDF_W3-079
Solar/Wind Helper
0.132
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.028
20675428EAM_W2-061
Solar/Wind Helper
0.016
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.023
20675928HOL_W4-097
Solar/Wind Helper
0.051
207471AF2-354 C
Solar/Wind Helper
0.17
20674828DL_W4-046
Solar/Wind Helper
0.008
961431AF2-434 GEN
Solar/Wind Helper
0.441
958711AF2-162 GEN
Solar/Wind Harmer
1.074
25196408WSDLE3
Adder
9.339
25196308WSDLE2
Adder
9.258
25196208WSDLE1
Adder
9.235
25196708WSDLE6
Adder
9.211
25196508WSDLE4
Adder
8.979
945581AF1-223 GEN
Solar/Wind Harmer
4.795
971029AG2-637 GEN
Solar/Wind Harmer
15.851
970031AG2-029 GEN
Solar/Wind Harmer
26.415
270404AC1-167 GEN
Solar/Wind Harmer
1.144
270543AE2-219 C
Solar/Wind Harmer
10.561
247536S-71 GEN
Solar/Wind Harmer
4.271
961761AG1-017 GEN
Solar/Wind Harmer
0.451
964611AG1-324 GEN
Solar/Wind Harmer
4.11
25196108MFTGT2
Adder
1.598
25196108MFTGT2
Adder
1.484
274775LINCOLN ;6U
Adder
8.673
274776LINCOLN ;7U
Adder
8.673
274777LINCOLN ;8U
Adder
8.673
972037AH1-567 GEN1
Adder
0.187
274827FISK ;RP
Adder
7.938
274800UNIV PARK;3U
Adder
5.964
274801UNIV PARK;4U
Adder
5.964
972228AH1-698 GEN2
Adder
3.789
972227AH1-698 GEN1
Adder
2.668
274687WILL CNTY;4U
Adder
28.512
274687WILL CNTY;4U
Adder
28.512
274675JOLIET 29;7U
Adder
31.291
274675JOLIET 29;7U
Adder
30.174
274728ELWOOD EC;5P
Adder
16.762
274731ELWOOD EC;2P
Adder
16.762
274733ELWOOD EC;3P
Adder
16.762
274735ELWOOD EC;4P
Adder
16.762
274744AC1-111 GEN8
Adder
5.677
274746AC1-111 G10
Adder
5.677
23750701CROSSCHOOL
Solar/Wind Helper
1.517
238118U2-030_1
Solar/Wind Helper
0.345
238169AE2-226 GEN1
Solar/Wind Helper
0.708
238170AE2-226 GEN2
Solar/Wind Helper
0.708
23779801AA1-109
Solar/Wind Helper
0.195
3138216PACIFIC
Solar/Wind Helper
0.045
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.166
23750501ELLIOTTS
Solar/Wind Helper
0.647
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.372
959381AF2-229 GEN
Solar/Wind Helper
0.36
20390526W1-045 C
Solar/Wind Helper
0.354
3141426STAFORD
Solar/Wind Helper
0.053
205943AE1-185 GEN
Solar/Wind Helper
0.515
205956AE1-196_GEN
Solar/Wind Helper
0.514
233915AB1-141 GEN
Solar/Wind Helper
0.508
233940AF2-379 C
Solar/Wind Helper
0.063
233901CHERRYDALE C
Solar/Wind Helper
0.235
232432Z2-076 GEN
Solar/Wind Helper
0.068
315651AD1-115 GEN
Solar/Wind Helper
0.795
230434AG1-499 GEN
Solar/Wind Helper
0.232
228728W1-130C
Solar/Wind Helper
0.055
230407AD2-065 C
Solar/Wind Helper
0.041
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.078
219615MILLCREEK C
Solar/Wind Helper
0.027
20715028HAN_X4-015
Solar/Wind Helper
0.058
20720728JCB_W1-129
Solar/Wind Helper
0.058
207445AB1-138_GEN
Solar/Wind Helper
0.106
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.192
316164AC1-076 GEN
Solar/Wind Helper
1.108
20675528CPH_W2-050
Solar/Wind Helper
0.114
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.097
20676428JCR_X2-075
Solar/Wind Helper
0.069
964851AG1-348 GEN
Solar/Wind Helper
0.064
207408W3-077 C
Solar/Wind Helper
0.085
20675128HRM_W1-127
Solar/Wind Helper
0.03
203955AF1-039 C O1
Solar/Wind Helper
0.332
209027LOR2_Q27
Solar/Wind Helper
1.036
212266LOR1
Solar/Wind Helper
0.302
209054AE2-059 GEN
Solar/Wind Helper
0.08
958861AF2-177 GEN
Solar/Wind Harmer
11.586
270024AE2-089 GEN
Solar/Wind Harmer
4.961
252510AF1-249 C
Solar/Wind Harmer
0.441
25194608D.CRK4
Adder
1.739
945371AF1-202 GEN
Solar/Wind Harmer
7.376
270297AD1-101 GEN
Solar/Wind Harmer
2.147
270222AC2-111 GEN
Solar/Wind Harmer
4.718
944031AF1-071 GEN
Solar/Wind Harmer
1.062
270510AE1-227 GEN1
Solar/Wind Harmer
2.605
270005AE1-210 C O1
Solar/Wind Harmer
5.743
942081AE2-220 GEN
Solar/Wind Harmer
6.717
270209AC1-174_GEN
Solar/Wind Harmer
4.274
270437AC2-090 C
Solar/Wind Harmer
5.862
270239V3-007_GEN1
Solar/Wind Harmer
1.807
270331AC1-082 GEN3
Solar/Wind Harmer
0.501
25196808ZIMRHP
Adder
79.685
970825AG2-519 GEN
Solar/Wind Harmer
2.203
24639705ELKHART HY
Adder
0.161
270216AD2-079_GEN
Solar/Wind Harmer
0.634
25196008MFTGT1
Adder
1.45
274751CRETE EC ;1U
Adder
8.473
274754CRETE EC ;4U
Adder
8.473
274773LINCOLN ;4U
Adder
8.673
274774LINCOLN ;5U
Adder
8.673
274723RIVER EC ;12
Adder
18.412
274812UNIV PK N;8U
Adder
5.137
274802UNIV PARK;5U
Adder
5.968
24728605AND G2
Adder
3.925
274676JOLIET 29;8U
Adder
31.291
274732ELWOOD EC;7P
Adder
16.762
274674JOLIET 9 ;6U
Adder
15.699
972203AH1-686 GEN
Adder
2.344
274745AC1-111 GEN9
Adder
5.677
970091AG2-072 GEN
Adder
77.647
274682WAUKEGAN ;7U
Adder
18.178
316095T157 G97
Solar/Wind Helper
1.515
23583801GRNGAP
Solar/Wind Helper
5.644
238185AF2-356 C
Solar/Wind Helper
2.686
238109AE1-109 GEN2
Solar/Wind Helper
0.115
238120AE2-309 GEN
Solar/Wind Helper
0.534
238126S14_GEN_1
Solar/Wind Helper
0.836
23546401DTGZ2-030
Solar/Wind Helper
0.09
237085AD2-009_GEN
Solar/Wind Helper
1.667
237038AE2-054 C
Solar/Wind Helper
0.275
235067AD1-061 GEN
Solar/Wind Helper
0.451
237002AB1-128_GEN
Solar/Wind Helper
0.448
23751101LEADS_P59
Solar/Wind Helper
2.15
23777801MSM_W1-116
Solar/Wind Helper
0.116
3141196NOKESVL
Solar/Wind Helper
1.039
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.022
233935AB2-179 C
Solar/Wind Helper
1.283
233987AB2-037 GEN
Solar/Wind Helper
2.369
233933AB2-153 GEN
Solar/Wind Helper
0.235
232422X3-066 FULL
Solar/Wind Helper
0.115
232417X3-008 C
Solar/Wind Helper
0.235
233964AF2-378 GEN
Solar/Wind Helper
0.042
233923SMA
Solar/Wind Helper
0.76
233997TMININ_4.2
Solar/Wind Helper
0.207
232406W1-004 FULL
Solar/Wind Helper
0.513
232434Z2-077 GEN
Solar/Wind Helper
0.128
233950AC2-186 GEN
Solar/Wind Helper
0.118
230415AB2-049 C
Solar/Wind Helper
0.031
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
219291REEVESSOUT C
Solar/Wind Helper
0.012
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.313
219612MATRIX C
Solar/Wind Helper
0.024
205941AD2-115 GEN
Solar/Wind Helper
0.501
20716928W4-060COL
Solar/Wind Helper
0.052
219249CENTRALDIV C
Solar/Wind Helper
0.01
217213AMBOY SO C
Solar/Wind Helper
0.029
207442AE1-156 GEN
Solar/Wind Helper
0.329
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
207511W3-106 GEN
Solar/Wind Helper
0.027
20671928W4-073
Solar/Wind Helper
0.091
20674128FR_U2-059
Solar/Wind Helper
0.004
209116AE2-175 GEN
Solar/Wind Helper
1.799
211065PSPA IPP
Solar/Wind Helper
0.153
963161AG1-165 GEN
Solar/Wind Helper
0.443
961331AF2-424 GEN
Solar/Wind Helper
0.442
961421AF2-433 GEN
Solar/Wind Helper
0.441
957921AF2-086 GEN
Solar/Wind Helper
0.436
270594AE1-207 GEN
Solar/Wind Harmer
13.371
270032AE2-172
Solar/Wind Harmer
4.579
CPLELTFEXP_CPLE->PJM
CLTF
0.593
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.743
NYPJM->LTFIMP_NY
CLTF
4.85
LGEELTFEXP_LGEE->PJM
CLTF
6.747
WECLTFEXP_WEC->PJM
CLTF
3.823
AG2-052LTFEXP_AG2-052->PJM
LTF
0.239
AH1-155LTFEXP_AH1-155->PJM
LTF
0.359
LAGNLTFEXP_LAGN->PJM
CLTF
14.823
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.742
TVALTFEXP_TVA->PJM
CLTF
7.286
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.944
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.079
MECLTFEXP_MEC->PJM
CLTF
15.894
SIGELTFEXP_SIGE->PJM
CLTF
0.505

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-025_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-025_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.4 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4974.31
MW Contribution:
25.23
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
7.082
270120AB2-067 GEN2
50/50
7.082
24318905MLG2
50/50
7.035
270349AD2-093_GEN
Solar/Wind Harmer
4.445
270471AD2-092_GEN
Solar/Wind Harmer
4.445
270054AF2-122 C O1
Solar/Wind Harmer
3.971
946101AF1-275 GEN
Solar/Wind Harmer
1.808
253383AE2-342_GEN
Solar/Wind Harmer
1.038
942861AE2-305 GEN
Solar/Wind Harmer
9.053
938701AE1-092 GEN
Solar/Wind Harmer
23.731
270462AD2-086
Solar/Wind Harmer
7.892
270269AC2-059
Solar/Wind Harmer
10.554
972159AH1-661 GEN
Adder
1.111
253378AE2-206_GEN
Solar/Wind Harmer
3.988
253415AE1-040 GEN
Solar/Wind Harmer
1.24
25326509SID D
Adder
1.448
241960AC2-195 GEN
Solar/Wind Harmer
3.053
971073AG2-665 GEN
Solar/Wind Harmer
8.757
970879AG2-548 GEN
Solar/Wind Harmer
1.273
25326109MON D
Adder
1.438
25322209TAIT E
Adder
10.61
25322209TAIT E
Adder
10.371
253370AE2-315 SEC1
Adder
2.175
927014AC1-188 GEN
Solar/Wind Harmer
1.713
253349AC2-067 GEN
Solar/Wind Harmer
2.197
253400AC2-068 GEN
Solar/Wind Harmer
0.884
246937BC-WTG2
Solar/Wind Harmer
4.206
270246TR4_N_V150
Solar/Wind Harmer
0.91
270247TR4_N_V136
Solar/Wind Harmer
0.91
942801AE2-298 GEN
Solar/Wind Harmer
1.617
247607V1-011 GEN
Solar/Wind Harmer
4.221
962581AG1-107 GEN
Solar/Wind Harmer
5.341
961491AF2-440 GEN
Solar/Wind Harmer
2.22
25183208HLCRTG
Solar/Wind Harmer
6.41
944541AF1-119 GEN
Solar/Wind Harmer
4.431
960971AF2-388 GEN
Solar/Wind Harmer
11.568
942221AE2-234 GEN
Solar/Wind Harmer
3.699
25194408D.CRK1
Adder
7.978
25194508D.CRK3
Adder
1.491
252509AD1-136 GEN
Solar/Wind Harmer
0.27
970883AG2-550 GEN
Solar/Wind Harmer
10.531
970885AG2-551 GEN
Solar/Wind Harmer
2.449
247621Y3-024
Adder
0.254
270201AC2-176 GEN
Solar/Wind Harmer
5.405
964611AG1-324 GEN
Solar/Wind Harmer
0.55
970349AG2-230 GEN
Solar/Wind Harmer
15.75
270031AE2-169
Solar/Wind Harmer
8.551
270599AE1-208 GEN
Solar/Wind Harmer
8.551
972239AH1-704 GEN
Adder
2.673
270459AD2-067 GEN
Solar/Wind Harmer
10.203
961821AG1-024 GEN
Solar/Wind Harmer
10.359
241955AC1-078 GEN
Solar/Wind Harmer
8.768
241973AD2-163_GEN1
Solar/Wind Harmer
2.315
241974AD2-163_GEN2
Solar/Wind Harmer
2.315
945631AF1-228 GEN
Solar/Wind Harmer
5.44
943861AF1-054 GEN
Solar/Wind Harmer
4.468
943851AF1-053 GEN
Solar/Wind Harmer
2.159
270223U2-072_GEN1
Solar/Wind Harmer
2.27
270224U2-072_GEN2
Solar/Wind Harmer
2.27
270227U2-072_GEN3
Solar/Wind Harmer
2.27
270228U2-072_GEN4
Solar/Wind Harmer
2.27
270231U2-072_GEN5
Solar/Wind Harmer
2.27
270578AF1-285 GEN2
Solar/Wind Harmer
0.535
270432AC2-029 GEN
Solar/Wind Harmer
8.013
253338AC1-165 GEN
Solar/Wind Harmer
1.233
253343AC1-166 GEN
Solar/Wind Harmer
1.233
270302AB2-170 GEN
Solar/Wind Harmer
9.503
940611AE2-048 GEN
Solar/Wind Harmer
24.928
941391AE2-136 GEN
Solar/Wind Harmer
12.917
270263AC1-001 GEN
Solar/Wind Harmer
1.168
241972AD1-140 GEN
Solar/Wind Harmer
4.999
270291AC1-194 GEN
Solar/Wind Harmer
5.603
970179AG2-119 GEN
Solar/Wind Harmer
8.8
270340AC2-060 GEN
Solar/Wind Harmer
3.323
253372AE2-315 SEC3
Adder
2.057
253372AE2-315 SEC3
Adder
2.057
25306009OHH W.
Adder
3.121
253406AD2-031_GEN
Solar/Wind Harmer
1.379
957201AF2-014 GEN
Solar/Wind Harmer
4.877
270435AC2-044 GEN
Solar/Wind Harmer
2.151
270377AD1-106 GEN
Solar/Wind Harmer
5.62
253433AC1-085 GEN1
Solar/Wind Harmer
5.693
253432AC1-085 GEN2
Solar/Wind Harmer
0.287
247521TR3_G114
Solar/Wind Harmer
3.595
270191TR4_S_V150
Solar/Wind Harmer
3.208
965051AG1-369 GEN
Solar/Wind Harmer
5.342
959331AF2-224 GEN
Solar/Wind Harmer
10.696
270007AE1-245 C
Solar/Wind Harmer
5.766
965041AG1-368 GEN
Solar/Wind Harmer
10.674
971567AH1-282 GEN
Solar/Wind Harmer
5.319
966831AG1-554 GEN
Solar/Wind Harmer
1.274
24729505KEY G4
Adder
6.894
270071AF1-092 GEN
Solar/Wind Harmer
15.924
963791AG1-232 GEN
Solar/Wind Harmer
14.332
971985AH1-537 GEN
Solar/Wind Harmer
18.912
958711AF2-162 GEN
Solar/Wind Harmer
1.071
25196408WSDLE3
Adder
9.314
25196308WSDLE2
Adder
9.233
25196208WSDLE1
Adder
9.209
25196708WSDLE6
Adder
9.186
25196508WSDLE4
Adder
8.955
945581AF1-223 GEN
Solar/Wind Harmer
4.781
270404AC1-167 GEN
Solar/Wind Harmer
1.141
971029AG2-637 GEN
Solar/Wind Harmer
15.807
970031AG2-029 GEN
Solar/Wind Harmer
26.342
270543AE2-219 C
Solar/Wind Harmer
10.531
247536S-71 GEN
Solar/Wind Harmer
4.259
961761AG1-017 GEN
Solar/Wind Harmer
0.45
964611AG1-324 GEN
Solar/Wind Harmer
4.099
25196108MFTGT2
Adder
1.593
24318805MLG1
50/50
10.084
23559001PLEAS1
50/50
6.18
270051AF1-062 GEN
50/50
11.783
270475AD2-096_GEN
50/50
7.121
962771AG1-126 GEN
Solar/Wind Harmer
40.857
970153AG2-106 GEN
Solar/Wind Harmer
17.815
961921AG1-034 GEN
Solar/Wind Harmer
15.539
270284AF1-227 GEN1
Solar/Wind Harmer
6.753
270287AF1-227 GEN3
Solar/Wind Harmer
2.498
24721905FLATG4
Adder
23.892
942051AE2-217 GEN
Solar/Wind Harmer
20.96
960801AF2-371 GEN
Solar/Wind Harmer
2.935
964871AG1-351 GEN
Solar/Wind Harmer
2.026
942871AE2-306 GEN
Solar/Wind Harmer
1.043
270391AF1-285 GEN3
Solar/Wind Harmer
0.535
270518AE2-148 GEN
Solar/Wind Harmer
13.795
253325AC1-069 GEN
Solar/Wind Harmer
1.189
276820AF1-078_GEN
Solar/Wind Harmer
1.772
958581AF2-149 GEN
Solar/Wind Harmer
4.716
971199AH1-059 GEN
Solar/Wind Harmer
2.315
970879AG2-548 GEN
Solar/Wind Harmer
8.757
960071AF2-298 GEN
Solar/Wind Harmer
1.643
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
970065AG2-057 GEN
Solar/Wind Harmer
0.921
957541AF2-048 GEN
Solar/Wind Harmer
1.713
270512AE1-227 GEN2
Solar/Wind Harmer
2.273
253394AE2-221_GEN
Solar/Wind Harmer
4.888
246938BC-WTG3
Solar/Wind Harmer
4.279
270491AE1-102 GEN2
Solar/Wind Harmer
1.398
971191AH1-055 GEN
Solar/Wind Harmer
20.022
253317AC1-085 GEN4
Solar/Wind Harmer
8.97
946181AF1-283 GEN
Solar/Wind Harmer
13.928
965021AG1-366 GEN
Solar/Wind Harmer
2.488
958091AF2-103 GEN
Solar/Wind Harmer
0.172
24695305TIMB G C
Solar/Wind Harmer
3.564
270588AE1-091_GEN
Solar/Wind Harmer
11.739
944531AF1-118 GEN
Solar/Wind Harmer
37.25
270043AE2-236 GEN
Solar/Wind Harmer
5.848
252519AF1-045_GEN
Solar/Wind Harmer
3.849
270367AC2-061_GEN
Solar/Wind Harmer
3.358
252524AE2-267 GEN
Solar/Wind Harmer
1.662
25196608WSDLE5
Adder
9.047
25194608D.CRK4
Adder
1.734
270044AE2-322 C
Solar/Wind Harmer
1.385
252507AC2-088 GEN
Solar/Wind Harmer
1.887
270063AE2-323 C
Solar/Wind Harmer
2.313
962031AG1-047 GEN
Solar/Wind Harmer
3.18
957741AF2-068 GEN
Solar/Wind Harmer
15.775
971347AH1-153 GEN
Solar/Wind Harmer
5.25
270186AC1-089 GEN
Solar/Wind Harmer
6.407
946031AF1-268 GEN
Solar/Wind Harmer
8.7
270004AE1-209 GEN
Solar/Wind Harmer
5.726
270330AC1-082 GEN2
Solar/Wind Harmer
0.498
270329AC1-082 GEN1
Solar/Wind Harmer
0.498
24379505HDWTR1G C
Solar/Wind Harmer
8.281
270240V3-007_GEN2
Solar/Wind Harmer
6.479
970825AG2-519 GEN
Solar/Wind Harmer
5.897
247643Z2-116 C
Solar/Wind Harmer
0.073
25196008MFTGT1
Adder
1.4
274752CRETE EC ;2U
Adder
8.448
274753CRETE EC ;3U
Adder
8.448
274772LINCOLN ;3U
Adder
8.646
274724RIVER EC ;11
Adder
18.141
274814UNIV PK N;0U
Adder
5.166
274807UNIV PK N;3U
Adder
5.155
274811UNIV PK N;7U
Adder
5.122
274803UNIV PARK;6U
Adder
5.949
24728705AND G3
Adder
8.184
24728505AND G1
Adder
3.913
274826FISK ;BP
Adder
11.167
972038AH1-567 GEN2
Adder
0.372
972259AH1-714 GEN
Adder
19.441
274676JOLIET 29;8U
Adder
30.081
274729ELWOOD EC;1P
Adder
16.71
274730ELWOOD EC;6P
Adder
16.71
274734ELWOOD EC;8P
Adder
16.71
274736ELWOOD EC;9P
Adder
16.71
274682WAUKEGAN ;7U
Adder
18.122
270383AD1-128 GEN
Solar/Wind Harmer
6.401
926881AC1-175 GEN
Solar/Wind Harmer
5.845
247620Y3-023
Adder
0.482
944231AF1-091 GEN
Solar/Wind Harmer
18.84
24728805RICHG1
Adder
3.949
24728905RICHG2
Adder
3.949
274770LINCOLN ;1U
Adder
8.646
274771LINCOLN ;2U
Adder
8.646
274805UNIV PK N;1U
Adder
5.133
274808UNIV PK N;4U
Adder
5.099
274674JOLIET 9 ;6U
Adder
15.65
274696ROCKY RD ;4P
Adder
11.497
274695ROCKY RD ;2P
Adder
11.232
274693ROCKY RD ;1P
Adder
11.121
274697ROCKY RD ;3P
Adder
3.051
274683WAUKEGAN ;8U
Adder
21.239
274683WAUKEGAN ;8U
Adder
9.65
316097T157 G90
Solar/Wind Helper
1.512
235054AD2-180 GEN
Solar/Wind Helper
2.044
23585401KL_K28_T16
Solar/Wind Helper
1.493
235531U2-073 GEN
Solar/Wind Helper
3.333
238117U2-030
Solar/Wind Helper
0.344
238147AE2-230_GEN1
Solar/Wind Helper
0.5
238148AE2-230_GEN2
Solar/Wind Helper
0.5
238149AF1-291A_GEN
Solar/Wind Helper
0.143
235020AA1-095 C
Solar/Wind Helper
0.053
23751201ROTHROCK
Solar/Wind Helper
0.83
237061AD1-155 GEN
Solar/Wind Helper
1.768
238221AF1-254 C O1
Solar/Wind Helper
0.277
237080AD1-060 GEN
Solar/Wind Helper
0.345
235062AE1-101 C1
Solar/Wind Helper
1.674
316411AF1-147_GEN1
Solar/Wind Helper
0.896
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.37
223402AF1-300 C
Solar/Wind Helper
0.37
316006AB2-029 C
Solar/Wind Helper
0.119
233930AB2-032 GEN
Solar/Wind Helper
0.384
232424Y1-079 C
Solar/Wind Helper
0.117
232436AB1-176 C
Solar/Wind Helper
0.045
233982AB2-133 GEN
Solar/Wind Helper
0.362
233946AB2-136 GEN
Solar/Wind Helper
0.574
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.969
232428Y3-058 C
Solar/Wind Helper
0.341
234015AF2-250 C
Solar/Wind Helper
0.038
232410W1-006 C
Solar/Wind Helper
0.511
233952AC2-187 GEN
Solar/Wind Helper
0.234
233954AC2-188 GEN
Solar/Wind Helper
0.234
316045AC1-158 PL2
Solar/Wind Helper
4.174
316450AC1-158 RIC
Solar/Wind Helper
0.348
230511AF1-262
Solar/Wind Helper
0.015
230433AD2-135 GEN
Solar/Wind Helper
0.017
228754AB1-001 C
Solar/Wind Helper
0.026
219904AC1-010 C
Solar/Wind Helper
0.061
219912AD2-042 GEN
Solar/Wind Helper
0.151
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219906AC1-017 C
Solar/Wind Helper
0.042
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.132
214067T20SOLAR
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.064
207459AE1-142 C O1
Solar/Wind Helper
0.292
20714828MDF_W3-079
Solar/Wind Helper
0.131
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
20675428EAM_W2-061
Solar/Wind Helper
0.016
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.023
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.17
20674828DL_W4-046
Solar/Wind Helper
0.008
25196108MFTGT2
Adder
1.48
274775LINCOLN ;6U
Adder
8.646
274776LINCOLN ;7U
Adder
8.646
274777LINCOLN ;8U
Adder
8.646
972037AH1-567 GEN1
Adder
0.187
274827FISK ;RP
Adder
7.914
274800UNIV PARK;3U
Adder
5.946
274801UNIV PARK;4U
Adder
5.946
972228AH1-698 GEN2
Adder
3.777
972227AH1-698 GEN1
Adder
2.66
274687WILL CNTY;4U
Adder
28.425
274687WILL CNTY;4U
Adder
28.425
274675JOLIET 29;7U
Adder
31.195
274675JOLIET 29;7U
Adder
30.081
274728ELWOOD EC;5P
Adder
16.71
274731ELWOOD EC;2P
Adder
16.71
274733ELWOOD EC;3P
Adder
16.71
274735ELWOOD EC;4P
Adder
16.71
274744AC1-111 GEN8
Adder
5.66
274746AC1-111 G10
Adder
5.66
23750701CROSSCHOOL
Solar/Wind Helper
1.512
238118U2-030_1
Solar/Wind Helper
0.344
238169AE2-226 GEN1
Solar/Wind Helper
0.707
238170AE2-226 GEN2
Solar/Wind Helper
0.707
23779801AA1-109
Solar/Wind Helper
0.195
3138216PACIFIC
Solar/Wind Helper
0.045
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.166
23750501ELLIOTTS
Solar/Wind Helper
0.644
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.371
959381AF2-229 GEN
Solar/Wind Helper
0.359
20390526W1-045 C
Solar/Wind Helper
0.353
3141426STAFORD
Solar/Wind Helper
0.053
205943AE1-185 GEN
Solar/Wind Helper
0.513
205956AE1-196_GEN
Solar/Wind Helper
0.513
233915AB1-141 GEN
Solar/Wind Helper
0.507
233940AF2-379 C
Solar/Wind Helper
0.063
233901CHERRYDALE C
Solar/Wind Helper
0.234
232432Z2-076 GEN
Solar/Wind Helper
0.068
315651AD1-115 GEN
Solar/Wind Helper
0.793
230434AG1-499 GEN
Solar/Wind Helper
0.232
228728W1-130C
Solar/Wind Helper
0.054
230407AD2-065 C
Solar/Wind Helper
0.041
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219615MILLCREEK C
Solar/Wind Helper
0.027
20715028HAN_X4-015
Solar/Wind Helper
0.058
20720728JCB_W1-129
Solar/Wind Helper
0.058
207445AB1-138_GEN
Solar/Wind Helper
0.105
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.191
316164AC1-076 GEN
Solar/Wind Helper
1.106
20675528CPH_W2-050
Solar/Wind Helper
0.114
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.097
20676428JCR_X2-075
Solar/Wind Helper
0.068
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.085
20675128HRM_W1-127
Solar/Wind Helper
0.03
209027LOR2_Q27
Solar/Wind Helper
1.033
212266LOR1
Solar/Wind Helper
0.301
203955AF1-039 C O1
Solar/Wind Helper
0.331
964991AG1-363 GEN
Solar/Wind Helper
5.16
238108AE1-109 GEN1
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238127S14_GEN_2
Solar/Wind Helper
0.833
238175AF1-290_GEN
Solar/Wind Helper
0.158
238152AF2-075_GEN
Solar/Wind Helper
0.714
23777901MDS_W4-102
Solar/Wind Helper
0.179
23562501BACKB
Solar/Wind Helper
1.015
235063AE1-101 C2
Solar/Wind Helper
1.674
237001AB1-127_GEN
Solar/Wind Helper
0.445
237048AF1-022 C
Solar/Wind Helper
0.185
316415AF1-147_GEN2
Solar/Wind Helper
0.896
205916AD1-020 GEN
Solar/Wind Helper
1.727
208835TUHI V3-051
Solar/Wind Helper
0.022
205932AD2-116_GEN
Solar/Wind Helper
0.513
233918AB1-142 GEN
Solar/Wind Helper
0.507
233944AB2-135 GEN
Solar/Wind Helper
0.595
233996TM1833_GEN
Solar/Wind Helper
0.207
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232426Y1-080 FULL
Solar/Wind Helper
0.039
232404W1-003 C
Solar/Wind Helper
0.511
232408W1-005 C
Solar/Wind Helper
0.511
316447AC1-158 HLD
Solar/Wind Helper
2.87
316044AC1-158 PL1
Solar/Wind Helper
1.304
228729W2-030 C
Solar/Wind Helper
0.111
219766PARADISE C
Solar/Wind Helper
0.055
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.115
203975AE1-071-GEN
Solar/Wind Helper
2.519
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714528FRN_Y2-051
Solar/Wind Helper
0.057
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
218440SUMMTASSOC C
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207530AG1-191 GEN
Solar/Wind Helper
0.067
207439AE1-081 C O1
Solar/Wind Helper
0.019
20676328BVR_Y1-020
Solar/Wind Helper
0.027
207484AF2-139 C O1
Solar/Wind Helper
0.085
20674928WA_W3-044
Solar/Wind Helper
0.099
20674628WNG_W3-110
Solar/Wind Helper
0.09
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
207518AF1-320_GEN
Solar/Wind Helper
1.582
20675828AU_W4-064
Solar/Wind Helper
0.03
211065PSPA IPP
Solar/Wind Helper
0.153
961301AF2-421 GEN
Solar/Wind Helper
0.442
963151AG1-164 GEN
Solar/Wind Helper
0.442
202652Y1-033 WT C
Solar/Wind Helper
0.501
270166AC1-044 GEN3
50/50
7.082
23559101PLEAS2
50/50
6.18
962761AG1-125 GEN
Solar/Wind Harmer
40.857
970149AG2-104 GEN
Solar/Wind Harmer
25.229
970155AG2-107 GEN
Solar/Wind Harmer
17.815
270520AE2-214 GEN
Solar/Wind Harmer
7.233
270286AF1-227 GEN2
Solar/Wind Harmer
2.498
270391AF1-285 GEN3
Solar/Wind Harmer
1.39
270578AF1-285 GEN2
Solar/Wind Harmer
1.39
253333AC1-068 GEN
Solar/Wind Harmer
1.189
270317AD1-130_GEN
Solar/Wind Harmer
3.633
270485AE1-090_GEN
Solar/Wind Harmer
0.686
971995AH1-542 GEN
Solar/Wind Harmer
12.451
270273AD2-016 GEN
Solar/Wind Harmer
3.008
972269AH1-719 GEN
Adder
2.564
971073AG2-665 GEN
Solar/Wind Harmer
1.273
25326309TAIT D
Adder
1.192
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
241813AF1-122_GEN
Solar/Wind Harmer
5.894
971201AH1-060 GEN
Solar/Wind Harmer
1.842
270510AE1-227 GEN1
Solar/Wind Harmer
2.678
253398AE2-221_GEN2
Solar/Wind Harmer
4.888
246936BC-WTG1
Solar/Wind Harmer
4.206
270489AE1-102 GEN1
Solar/Wind Harmer
1.398
965421AG1-410 GEN
Solar/Wind Harmer
32.241
960001AF2-291 GEN
Solar/Wind Harmer
3.242
253316AC1-085 GEN3
Solar/Wind Harmer
8.97
946171AF1-282 GEN
Solar/Wind Harmer
10.714
965011AG1-365 GEN
Solar/Wind Harmer
10.696
961341AF2-425 GEN
Solar/Wind Helper
0.441
270258AD1-119 GEN
Solar/Wind Harmer
2.151
965651AG1-433 GEN
Solar/Wind Harmer
5.784
252516AE2-318_GEN
Solar/Wind Harmer
10.575
958861AF2-177 GEN
Solar/Wind Harmer
11.552
270024AE2-089 GEN
Solar/Wind Harmer
4.947
252510AF1-249 C
Solar/Wind Harmer
0.44
25194608D.CRK4
Adder
1.734
270297AD1-101 GEN
Solar/Wind Harmer
2.142
945371AF1-202 GEN
Solar/Wind Harmer
7.355
270222AC2-111 GEN
Solar/Wind Harmer
4.705
944031AF1-071 GEN
Solar/Wind Harmer
1.059
270005AE1-210 C O1
Solar/Wind Harmer
5.726
25196808ZIMRHP
Adder
79.465
270331AC1-082 GEN3
Solar/Wind Harmer
0.499
942081AE2-220 GEN
Solar/Wind Harmer
6.698
270209AC1-174_GEN
Solar/Wind Harmer
4.262
270437AC2-090 C
Solar/Wind Harmer
5.845
270239V3-007_GEN1
Solar/Wind Harmer
1.802
970825AG2-519 GEN
Solar/Wind Harmer
2.196
24639705ELKHART HY
Adder
0.161
270216AD2-079_GEN
Solar/Wind Harmer
0.632
25196008MFTGT1
Adder
1.445
274751CRETE EC ;1U
Adder
8.448
274754CRETE EC ;4U
Adder
8.448
274773LINCOLN ;4U
Adder
8.646
274774LINCOLN ;5U
Adder
8.646
274723RIVER EC ;12
Adder
18.356
274812UNIV PK N;8U
Adder
5.122
274802UNIV PARK;5U
Adder
5.949
24728605AND G2
Adder
3.913
274676JOLIET 29;8U
Adder
31.195
274732ELWOOD EC;7P
Adder
16.71
274674JOLIET 9 ;6U
Adder
15.65
972203AH1-686 GEN
Adder
2.333
274745AC1-111 GEN9
Adder
5.66
970091AG2-072 GEN
Adder
77.376
274682WAUKEGAN ;7U
Adder
18.122
316095T157 G97
Solar/Wind Helper
1.512
23583801GRNGAP
Solar/Wind Helper
5.632
238185AF2-356 C
Solar/Wind Helper
2.674
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238120AE2-309 GEN
Solar/Wind Helper
0.532
238126S14_GEN_1
Solar/Wind Helper
0.833
23546401DTGZ2-030
Solar/Wind Helper
0.09
237085AD2-009_GEN
Solar/Wind Helper
1.663
237038AE2-054 C
Solar/Wind Helper
0.275
235067AD1-061 GEN
Solar/Wind Helper
0.45
237002AB1-128_GEN
Solar/Wind Helper
0.447
23751101LEADS_P59
Solar/Wind Helper
2.129
23777801MSM_W1-116
Solar/Wind Helper
0.115
3141196NOKESVL
Solar/Wind Helper
1.037
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.349
208835TUHI V3-051
Solar/Wind Helper
0.022
233935AB2-179 C
Solar/Wind Helper
1.279
233987AB2-037 GEN
Solar/Wind Helper
2.363
233933AB2-153 GEN
Solar/Wind Helper
0.235
232422X3-066 FULL
Solar/Wind Helper
0.115
232417X3-008 C
Solar/Wind Helper
0.234
233964AF2-378 GEN
Solar/Wind Helper
0.042
233923SMA
Solar/Wind Helper
0.758
233997TMININ_4.2
Solar/Wind Helper
0.207
232406W1-004 FULL
Solar/Wind Helper
0.511
232434Z2-077 GEN
Solar/Wind Helper
0.128
233950AC2-186 GEN
Solar/Wind Helper
0.117
230415AB2-049 C
Solar/Wind Helper
0.031
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
219291REEVESSOUT C
Solar/Wind Helper
0.012
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.312
219612MATRIX C
Solar/Wind Helper
0.024
205941AD2-115 GEN
Solar/Wind Helper
0.499
20716928W4-060COL
Solar/Wind Helper
0.052
219249CENTRALDIV C
Solar/Wind Helper
0.01
217213AMBOY SO C
Solar/Wind Helper
0.029
207442AE1-156 GEN
Solar/Wind Helper
0.328
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
207511W3-106 GEN
Solar/Wind Helper
0.027
20671928W4-073
Solar/Wind Helper
0.09
20674128FR_U2-059
Solar/Wind Helper
0.004
209116AE2-175 GEN
Solar/Wind Helper
1.794
211065PSPA IPP
Solar/Wind Helper
0.153
963161AG1-165 GEN
Solar/Wind Helper
0.442
961331AF2-424 GEN
Solar/Wind Helper
0.441
270594AE1-207 GEN
Solar/Wind Harmer
13.331
270032AE2-172
Solar/Wind Harmer
4.566
CPLELTFEXP_CPLE->PJM
CLTF
0.578
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.337
NYPJM->LTFIMP_NY
CLTF
4.834
LGEELTFEXP_LGEE->PJM
CLTF
6.725
WECLTFEXP_WEC->PJM
CLTF
3.811
AG2-052LTFEXP_AG2-052->PJM
LTF
0.239
AH1-155LTFEXP_AH1-155->PJM
LTF
0.358
LAGNLTFEXP_LAGN->PJM
CLTF
14.764
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.682
TVALTFEXP_TVA->PJM
CLTF
7.257
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.545
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.966
MECLTFEXP_MEC->PJM
CLTF
15.842
SIGELTFEXP_SIGE->PJM
CLTF
0.503

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-015_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-015_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.01 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4959.97
MW Contribution:
25.21
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972239AH1-704 GEN
Adder
2.68
270459AD2-067 GEN
Solar/Wind Harmer
10.209
961821AG1-024 GEN
Solar/Wind Harmer
10.365
241955AC1-078 GEN
Solar/Wind Harmer
8.772
241973AD2-163_GEN1
Solar/Wind Harmer
2.316
241974AD2-163_GEN2
Solar/Wind Harmer
2.316
945631AF1-228 GEN
Solar/Wind Harmer
5.442
943861AF1-054 GEN
Solar/Wind Harmer
4.469
943851AF1-053 GEN
Solar/Wind Harmer
2.16
270223U2-072_GEN1
Solar/Wind Harmer
2.27
270224U2-072_GEN2
Solar/Wind Harmer
2.27
270227U2-072_GEN3
Solar/Wind Harmer
2.27
270228U2-072_GEN4
Solar/Wind Harmer
2.27
270231U2-072_GEN5
Solar/Wind Harmer
2.27
270578AF1-285 GEN2
Solar/Wind Harmer
0.535
24318805MLG1
50/50
10.069
23559001PLEAS1
50/50
6.109
270051AF1-062 GEN
50/50
11.788
270475AD2-096_GEN
50/50
7.121
962771AG1-126 GEN
Solar/Wind Harmer
40.825
970153AG2-106 GEN
Solar/Wind Harmer
17.802
961921AG1-034 GEN
Solar/Wind Harmer
15.548
270284AF1-227 GEN1
Solar/Wind Harmer
6.753
270287AF1-227 GEN3
Solar/Wind Harmer
2.498
24721905FLATG4
Adder
23.852
942051AE2-217 GEN
Solar/Wind Harmer
20.967
960801AF2-371 GEN
Solar/Wind Harmer
2.937
964871AG1-351 GEN
Solar/Wind Harmer
2.028
942871AE2-306 GEN
Solar/Wind Harmer
1.043
270391AF1-285 GEN3
Solar/Wind Harmer
0.535
270518AE2-148 GEN
Solar/Wind Harmer
13.799
253325AC1-069 GEN
Solar/Wind Harmer
1.189
276820AF1-078_GEN
Solar/Wind Harmer
1.772
958581AF2-149 GEN
Solar/Wind Harmer
4.723
971199AH1-059 GEN
Solar/Wind Harmer
2.318
270512AE1-227 GEN2
Solar/Wind Harmer
2.305
970879AG2-548 GEN
Solar/Wind Harmer
8.762
270119AB2-067 GEN1
50/50
7.073
270120AB2-067 GEN2
50/50
7.073
24318905MLG2
50/50
7.043
23684101S70BUS1
50/50
0.165
270349AD2-093_GEN
Solar/Wind Harmer
4.444
270471AD2-092_GEN
Solar/Wind Harmer
4.444
270054AF2-122 C O1
Solar/Wind Harmer
3.974
946101AF1-275 GEN
Solar/Wind Harmer
1.809
253383AE2-342_GEN
Solar/Wind Harmer
1.038
942861AE2-305 GEN
Solar/Wind Harmer
9.054
938701AE1-092 GEN
Solar/Wind Harmer
23.739
270462AD2-086
Solar/Wind Harmer
7.893
270269AC2-059
Solar/Wind Harmer
10.558
972159AH1-661 GEN
Adder
1.114
253378AE2-206_GEN
Solar/Wind Harmer
3.989
253415AE1-040 GEN
Solar/Wind Harmer
1.24
25326509SID D
Adder
1.448
241960AC2-195 GEN
Solar/Wind Harmer
3.054
971073AG2-665 GEN
Solar/Wind Harmer
8.762
970879AG2-548 GEN
Solar/Wind Harmer
1.274
25326109MON D
Adder
1.438
25322209TAIT E
Adder
10.61
25322209TAIT E
Adder
10.372
253370AE2-315 SEC1
Adder
2.175
927014AC1-188 GEN
Solar/Wind Harmer
1.714
253349AC2-067 GEN
Solar/Wind Harmer
2.197
253400AC2-068 GEN
Solar/Wind Harmer
0.884
246937BC-WTG2
Solar/Wind Harmer
4.206
270246TR4_N_V150
Solar/Wind Harmer
0.91
270247TR4_N_V136
Solar/Wind Harmer
0.91
942801AE2-298 GEN
Solar/Wind Harmer
1.617
247607V1-011 GEN
Solar/Wind Harmer
4.221
962581AG1-107 GEN
Solar/Wind Harmer
5.341
961491AF2-440 GEN
Solar/Wind Harmer
2.22
25183208HLCRTG
Solar/Wind Harmer
6.409
944541AF1-119 GEN
Solar/Wind Harmer
4.43
960971AF2-388 GEN
Solar/Wind Harmer
11.565
942221AE2-234 GEN
Solar/Wind Harmer
3.699
25194408D.CRK1
Adder
7.977
25194508D.CRK3
Adder
1.491
252509AD1-136 GEN
Solar/Wind Harmer
0.27
970883AG2-550 GEN
Solar/Wind Harmer
10.53
970885AG2-551 GEN
Solar/Wind Harmer
2.449
247621Y3-024
Adder
0.254
270201AC2-176 GEN
Solar/Wind Harmer
5.404
964611AG1-324 GEN
Solar/Wind Harmer
0.55
970349AG2-230 GEN
Solar/Wind Harmer
15.746
270031AE2-169
Solar/Wind Harmer
8.55
270599AE1-208 GEN
Solar/Wind Harmer
8.55
270383AD1-128 GEN
Solar/Wind Harmer
6.399
926881AC1-175 GEN
Solar/Wind Harmer
5.844
247620Y3-023
Adder
0.482
944231AF1-091 GEN
Solar/Wind Harmer
18.838
24728805RICHG1
Adder
3.948
24728905RICHG2
Adder
3.948
274770LINCOLN ;1U
Adder
8.644
274771LINCOLN ;2U
Adder
8.644
274805UNIV PK N;1U
Adder
5.131
274808UNIV PK N;4U
Adder
5.098
274674JOLIET 9 ;6U
Adder
15.646
274696ROCKY RD ;4P
Adder
11.494
274695ROCKY RD ;2P
Adder
11.229
274693ROCKY RD ;1P
Adder
11.118
274697ROCKY RD ;3P
Adder
3.05
274683WAUKEGAN ;8U
Adder
21.233
274683WAUKEGAN ;8U
Adder
9.373
316097T157 G90
Solar/Wind Helper
1.512
235054AD2-180 GEN
Solar/Wind Helper
2.035
23585401KL_K28_T16
Solar/Wind Helper
1.485
235531U2-073 GEN
Solar/Wind Helper
3.323
238117U2-030
Solar/Wind Helper
0.343
238147AE2-230_GEN1
Solar/Wind Helper
0.499
238148AE2-230_GEN2
Solar/Wind Helper
0.499
238149AF1-291A_GEN
Solar/Wind Helper
0.143
235020AA1-095 C
Solar/Wind Helper
0.053
237061AD1-155 GEN
Solar/Wind Helper
1.768
23751201ROTHROCK
Solar/Wind Helper
0.823
238221AF1-254 C O1
Solar/Wind Helper
0.277
237080AD1-060 GEN
Solar/Wind Helper
0.345
235062AE1-101 C1
Solar/Wind Helper
1.673
316411AF1-147_GEN1
Solar/Wind Helper
0.896
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.37
223402AF1-300 C
Solar/Wind Helper
0.37
316006AB2-029 C
Solar/Wind Helper
0.119
233982AB2-133 GEN
Solar/Wind Helper
0.362
233930AB2-032 GEN
Solar/Wind Helper
0.384
232424Y1-079 C
Solar/Wind Helper
0.117
232436AB1-176 C
Solar/Wind Helper
0.045
233946AB2-136 GEN
Solar/Wind Helper
0.573
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.969
232410W1-006 C
Solar/Wind Helper
0.511
232428Y3-058 C
Solar/Wind Helper
0.341
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.234
233954AC2-188 GEN
Solar/Wind Helper
0.234
316045AC1-158 PL2
Solar/Wind Helper
4.174
316450AC1-158 RIC
Solar/Wind Helper
0.348
230511AF1-262
Solar/Wind Helper
0.015
230433AD2-135 GEN
Solar/Wind Helper
0.017
228754AB1-001 C
Solar/Wind Helper
0.026
219904AC1-010 C
Solar/Wind Helper
0.061
219912AD2-042 GEN
Solar/Wind Helper
0.151
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219906AC1-017 C
Solar/Wind Helper
0.042
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.132
214067T20SOLAR
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.064
207459AE1-142 C O1
Solar/Wind Helper
0.292
20714828MDF_W3-079
Solar/Wind Helper
0.131
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
20675428EAM_W2-061
Solar/Wind Helper
0.016
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
270432AC2-029 GEN
Solar/Wind Harmer
8.017
253338AC1-165 GEN
Solar/Wind Harmer
1.233
253343AC1-166 GEN
Solar/Wind Harmer
1.233
940611AE2-048 GEN
Solar/Wind Harmer
25.038
941391AE2-136 GEN
Solar/Wind Harmer
12.974
270302AB2-170 GEN
Solar/Wind Harmer
9.503
270263AC1-001 GEN
Solar/Wind Harmer
1.169
241972AD1-140 GEN
Solar/Wind Harmer
5
270291AC1-194 GEN
Solar/Wind Harmer
5.607
970179AG2-119 GEN
Solar/Wind Harmer
8.805
270340AC2-060 GEN
Solar/Wind Harmer
3.324
253372AE2-315 SEC3
Adder
2.057
253372AE2-315 SEC3
Adder
2.057
25306009OHH W.
Adder
3.121
253406AD2-031_GEN
Solar/Wind Harmer
1.379
957201AF2-014 GEN
Solar/Wind Harmer
4.876
270435AC2-044 GEN
Solar/Wind Harmer
2.15
270377AD1-106 GEN
Solar/Wind Harmer
5.625
253433AC1-085 GEN1
Solar/Wind Harmer
5.693
253432AC1-085 GEN2
Solar/Wind Harmer
0.287
247521TR3_G114
Solar/Wind Harmer
3.595
270191TR4_S_V150
Solar/Wind Harmer
3.208
965051AG1-369 GEN
Solar/Wind Harmer
5.341
959331AF2-224 GEN
Solar/Wind Harmer
10.694
270007AE1-245 C
Solar/Wind Harmer
5.766
965041AG1-368 GEN
Solar/Wind Harmer
10.672
971567AH1-282 GEN
Solar/Wind Harmer
5.325
966831AG1-554 GEN
Solar/Wind Harmer
1.274
24729505KEY G4
Adder
6.892
963791AG1-232 GEN
Solar/Wind Harmer
14.329
270071AF1-092 GEN
Solar/Wind Harmer
15.92
971985AH1-537 GEN
Solar/Wind Harmer
18.912
958711AF2-162 GEN
Solar/Wind Harmer
1.07
25196408WSDLE3
Adder
9.313
25196308WSDLE2
Adder
9.232
25196208WSDLE1
Adder
9.209
25196708WSDLE6
Adder
9.186
25196508WSDLE4
Adder
8.954
945581AF1-223 GEN
Solar/Wind Harmer
4.78
270404AC1-167 GEN
Solar/Wind Harmer
1.141
971029AG2-637 GEN
Solar/Wind Harmer
15.805
970031AG2-029 GEN
Solar/Wind Harmer
26.336
270543AE2-219 C
Solar/Wind Harmer
10.53
247536S-71 GEN
Solar/Wind Harmer
4.259
961761AG1-017 GEN
Solar/Wind Harmer
0.45
964611AG1-324 GEN
Solar/Wind Harmer
4.098
25196108MFTGT2
Adder
1.593
25196108MFTGT2
Adder
1.479
274775LINCOLN ;6U
Adder
8.644
274776LINCOLN ;7U
Adder
8.644
274777LINCOLN ;8U
Adder
8.644
972037AH1-567 GEN1
Adder
0.187
274827FISK ;RP
Adder
7.912
274800UNIV PARK;3U
Adder
5.944
274801UNIV PARK;4U
Adder
5.944
972228AH1-698 GEN2
Adder
3.776
972227AH1-698 GEN1
Adder
2.659
274687WILL CNTY;4U
Adder
28.416
274687WILL CNTY;4U
Adder
28.416
274675JOLIET 29;7U
Adder
31.186
274675JOLIET 29;7U
Adder
30.072
274728ELWOOD EC;5P
Adder
16.705
274731ELWOOD EC;2P
Adder
16.705
274733ELWOOD EC;3P
Adder
16.705
274735ELWOOD EC;4P
Adder
16.705
274744AC1-111 GEN8
Adder
5.658
274746AC1-111 G10
Adder
5.658
23750701CROSSCHOOL
Solar/Wind Helper
1.507
238118U2-030_1
Solar/Wind Helper
0.343
238169AE2-226 GEN1
Solar/Wind Helper
0.707
238170AE2-226 GEN2
Solar/Wind Helper
0.707
23779801AA1-109
Solar/Wind Helper
0.195
3138216PACIFIC
Solar/Wind Helper
0.045
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.166
23750501ELLIOTTS
Solar/Wind Helper
0.64
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.371
959381AF2-229 GEN
Solar/Wind Helper
0.359
20390526W1-045 C
Solar/Wind Helper
0.353
3141426STAFORD
Solar/Wind Helper
0.053
205943AE1-185 GEN
Solar/Wind Helper
0.513
205956AE1-196_GEN
Solar/Wind Helper
0.513
233915AB1-141 GEN
Solar/Wind Helper
0.506
233901CHERRYDALE C
Solar/Wind Helper
0.234
233940AF2-379 C
Solar/Wind Helper
0.063
232432Z2-076 GEN
Solar/Wind Helper
0.068
315651AD1-115 GEN
Solar/Wind Helper
0.793
230434AG1-499 GEN
Solar/Wind Helper
0.232
228728W1-130C
Solar/Wind Helper
0.054
230407AD2-065 C
Solar/Wind Helper
0.041
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219615MILLCREEK C
Solar/Wind Helper
0.027
20715028HAN_X4-015
Solar/Wind Helper
0.058
20720728JCB_W1-129
Solar/Wind Helper
0.058
207445AB1-138_GEN
Solar/Wind Helper
0.105
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.191
316164AC1-076 GEN
Solar/Wind Helper
1.106
20675528CPH_W2-050
Solar/Wind Helper
0.114
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.097
20676428JCR_X2-075
Solar/Wind Helper
0.068
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.085
20675128HRM_W1-127
Solar/Wind Helper
0.03
209027LOR2_Q27
Solar/Wind Helper
1.033
212266LOR1
Solar/Wind Helper
0.301
960071AF2-298 GEN
Solar/Wind Harmer
1.643
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
970065AG2-057 GEN
Solar/Wind Harmer
0.922
957541AF2-048 GEN
Solar/Wind Harmer
1.714
253394AE2-221_GEN
Solar/Wind Harmer
4.888
246938BC-WTG3
Solar/Wind Harmer
4.278
270491AE1-102 GEN2
Solar/Wind Harmer
1.398
971191AH1-055 GEN
Solar/Wind Harmer
20.024
253317AC1-085 GEN4
Solar/Wind Harmer
8.97
946181AF1-283 GEN
Solar/Wind Harmer
13.928
965021AG1-366 GEN
Solar/Wind Harmer
2.487
958091AF2-103 GEN
Solar/Wind Harmer
0.172
270588AE1-091_GEN
Solar/Wind Harmer
11.743
24695305TIMB G C
Solar/Wind Harmer
3.563
944531AF1-118 GEN
Solar/Wind Harmer
37.241
270043AE2-236 GEN
Solar/Wind Harmer
5.847
252519AF1-045_GEN
Solar/Wind Harmer
3.849
270367AC2-061_GEN
Solar/Wind Harmer
3.358
252524AE2-267 GEN
Solar/Wind Harmer
1.662
25196608WSDLE5
Adder
9.047
25194608D.CRK4
Adder
1.734
270044AE2-322 C
Solar/Wind Harmer
1.385
252507AC2-088 GEN
Solar/Wind Harmer
1.887
270063AE2-323 C
Solar/Wind Harmer
2.313
962031AG1-047 GEN
Solar/Wind Harmer
3.179
957741AF2-068 GEN
Solar/Wind Harmer
15.772
971347AH1-153 GEN
Solar/Wind Harmer
5.249
270186AC1-089 GEN
Solar/Wind Harmer
6.407
946031AF1-268 GEN
Solar/Wind Harmer
8.698
270330AC1-082 GEN2
Solar/Wind Harmer
0.498
270329AC1-082 GEN1
Solar/Wind Harmer
0.498
270004AE1-209 GEN
Solar/Wind Harmer
5.725
24379505HDWTR1G C
Solar/Wind Harmer
8.279
270240V3-007_GEN2
Solar/Wind Harmer
6.478
970825AG2-519 GEN
Solar/Wind Harmer
5.896
247643Z2-116 C
Solar/Wind Harmer
0.073
25196008MFTGT1
Adder
1.4
274752CRETE EC ;2U
Adder
8.445
274753CRETE EC ;3U
Adder
8.445
274772LINCOLN ;3U
Adder
8.644
274724RIVER EC ;11
Adder
18.136
274814UNIV PK N;0U
Adder
5.165
274807UNIV PK N;3U
Adder
5.154
274811UNIV PK N;7U
Adder
5.12
274803UNIV PARK;6U
Adder
5.948
24728705AND G3
Adder
8.182
24728505AND G1
Adder
3.912
274826FISK ;BP
Adder
11.164
972038AH1-567 GEN2
Adder
0.372
972259AH1-714 GEN
Adder
19.435
274676JOLIET 29;8U
Adder
30.072
274729ELWOOD EC;1P
Adder
16.705
274730ELWOOD EC;6P
Adder
16.705
274734ELWOOD EC;8P
Adder
16.705
274736ELWOOD EC;9P
Adder
16.705
274682WAUKEGAN ;7U
Adder
18.116
964991AG1-363 GEN
Solar/Wind Helper
5.159
238108AE1-109 GEN1
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238127S14_GEN_2
Solar/Wind Helper
0.83
238175AF1-290_GEN
Solar/Wind Helper
0.158
238152AF2-075_GEN
Solar/Wind Helper
0.714
23777901MDS_W4-102
Solar/Wind Helper
0.179
23562501BACKB
Solar/Wind Helper
1.006
235063AE1-101 C2
Solar/Wind Helper
1.673
237001AB1-127_GEN
Solar/Wind Helper
0.445
316415AF1-147_GEN2
Solar/Wind Helper
0.896
237048AF1-022 C
Solar/Wind Helper
0.184
205916AD1-020 GEN
Solar/Wind Helper
1.727
208835TUHI V3-051
Solar/Wind Helper
0.022
205932AD2-116_GEN
Solar/Wind Helper
0.513
233918AB1-142 GEN
Solar/Wind Helper
0.506
233944AB2-135 GEN
Solar/Wind Helper
0.595
232426Y1-080 FULL
Solar/Wind Helper
0.039
233996TM1833_GEN
Solar/Wind Helper
0.207
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232404W1-003 C
Solar/Wind Helper
0.511
232408W1-005 C
Solar/Wind Helper
0.511
316447AC1-158 HLD
Solar/Wind Helper
2.87
316044AC1-158 PL1
Solar/Wind Helper
1.304
228729W2-030 C
Solar/Wind Helper
0.111
219766PARADISE C
Solar/Wind Helper
0.055
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.115
203975AE1-071-GEN
Solar/Wind Helper
2.518
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714528FRN_Y2-051
Solar/Wind Helper
0.057
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
218440SUMMTASSOC C
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207530AG1-191 GEN
Solar/Wind Helper
0.067
20676328BVR_Y1-020
Solar/Wind Helper
0.027
207439AE1-081 C O1
Solar/Wind Helper
0.019
207484AF2-139 C O1
Solar/Wind Helper
0.085
20674928WA_W3-044
Solar/Wind Helper
0.099
20674628WNG_W3-110
Solar/Wind Helper
0.09
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
207518AF1-320_GEN
Solar/Wind Helper
1.581
20675828AU_W4-064
Solar/Wind Helper
0.03
211065PSPA IPP
Solar/Wind Helper
0.153
961301AF2-421 GEN
Solar/Wind Helper
0.442
963151AG1-164 GEN
Solar/Wind Helper
0.442
961341AF2-425 GEN
Solar/Wind Helper
0.44
270166AC1-044 GEN3
50/50
7.073
23559101PLEAS2
50/50
6.109
23684201S70BUS2
50/50
0.168
962761AG1-125 GEN
Solar/Wind Harmer
40.825
970149AG2-104 GEN
Solar/Wind Harmer
25.209
970155AG2-107 GEN
Solar/Wind Harmer
17.802
270520AE2-214 GEN
Solar/Wind Harmer
7.236
270286AF1-227 GEN2
Solar/Wind Harmer
2.498
270391AF1-285 GEN3
Solar/Wind Harmer
1.39
270578AF1-285 GEN2
Solar/Wind Harmer
1.39
253333AC1-068 GEN
Solar/Wind Harmer
1.189
270317AD1-130_GEN
Solar/Wind Harmer
3.633
270485AE1-090_GEN
Solar/Wind Harmer
0.686
971995AH1-542 GEN
Solar/Wind Harmer
12.457
270273AD2-016 GEN
Solar/Wind Harmer
3.01
972269AH1-719 GEN
Adder
2.576
270510AE1-227 GEN1
Solar/Wind Harmer
2.716
971073AG2-665 GEN
Solar/Wind Harmer
1.274
25326309TAIT D
Adder
1.192
241813AF1-122_GEN
Solar/Wind Harmer
5.898
971201AH1-060 GEN
Solar/Wind Harmer
1.843
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
253398AE2-221_GEN2
Solar/Wind Harmer
4.888
246936BC-WTG1
Solar/Wind Harmer
4.206
270489AE1-102 GEN1
Solar/Wind Harmer
1.398
965421AG1-410 GEN
Solar/Wind Harmer
32.239
960001AF2-291 GEN
Solar/Wind Harmer
3.243
253316AC1-085 GEN3
Solar/Wind Harmer
8.97
946171AF1-282 GEN
Solar/Wind Harmer
10.714
965011AG1-365 GEN
Solar/Wind Harmer
10.694
270258AD1-119 GEN
Solar/Wind Harmer
2.151
965651AG1-433 GEN
Solar/Wind Harmer
5.783
252516AE2-318_GEN
Solar/Wind Harmer
10.575
958861AF2-177 GEN
Solar/Wind Harmer
11.549
252510AF1-249 C
Solar/Wind Harmer
0.44
270024AE2-089 GEN
Solar/Wind Harmer
4.946
25194608D.CRK4
Adder
1.734
270297AD1-101 GEN
Solar/Wind Harmer
2.142
945371AF1-202 GEN
Solar/Wind Harmer
7.353
270222AC2-111 GEN
Solar/Wind Harmer
4.705
944031AF1-071 GEN
Solar/Wind Harmer
1.059
270331AC1-082 GEN3
Solar/Wind Harmer
0.499
270005AE1-210 C O1
Solar/Wind Harmer
5.725
25196808ZIMRHP
Adder
79.46
942081AE2-220 GEN
Solar/Wind Harmer
6.696
270209AC1-174_GEN
Solar/Wind Harmer
4.261
270437AC2-090 C
Solar/Wind Harmer
5.844
270239V3-007_GEN1
Solar/Wind Harmer
1.802
970825AG2-519 GEN
Solar/Wind Harmer
2.196
24639705ELKHART HY
Adder
0.16
270216AD2-079_GEN
Solar/Wind Harmer
0.632
25196008MFTGT1
Adder
1.445
274751CRETE EC ;1U
Adder
8.445
274754CRETE EC ;4U
Adder
8.445
274773LINCOLN ;4U
Adder
8.644
274774LINCOLN ;5U
Adder
8.644
274723RIVER EC ;12
Adder
18.35
274812UNIV PK N;8U
Adder
5.12
274802UNIV PARK;5U
Adder
5.948
24728605AND G2
Adder
3.912
274676JOLIET 29;8U
Adder
31.186
274732ELWOOD EC;7P
Adder
16.705
274674JOLIET 9 ;6U
Adder
15.646
972203AH1-686 GEN
Adder
2.33
274745AC1-111 GEN9
Adder
5.658
970091AG2-072 GEN
Adder
77.346
274682WAUKEGAN ;7U
Adder
18.116
316095T157 G97
Solar/Wind Helper
1.512
23583801GRNGAP
Solar/Wind Helper
5.632
238185AF2-356 C
Solar/Wind Helper
2.664
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238120AE2-309 GEN
Solar/Wind Helper
0.53
238126S14_GEN_1
Solar/Wind Helper
0.83
23546401DTGZ2-030
Solar/Wind Helper
0.09
237085AD2-009_GEN
Solar/Wind Helper
1.662
237038AE2-054 C
Solar/Wind Helper
0.275
235067AD1-061 GEN
Solar/Wind Helper
0.449
237002AB1-128_GEN
Solar/Wind Helper
0.447
23777801MSM_W1-116
Solar/Wind Helper
0.115
23751101LEADS_P59
Solar/Wind Helper
2.095
3141196NOKESVL
Solar/Wind Helper
1.037
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.349
208835TUHI V3-051
Solar/Wind Helper
0.022
233935AB2-179 C
Solar/Wind Helper
1.279
233987AB2-037 GEN
Solar/Wind Helper
2.362
233933AB2-153 GEN
Solar/Wind Helper
0.234
232422X3-066 FULL
Solar/Wind Helper
0.115
232417X3-008 C
Solar/Wind Helper
0.234
233964AF2-378 GEN
Solar/Wind Helper
0.042
233923SMA
Solar/Wind Helper
0.758
233997TMININ_4.2
Solar/Wind Helper
0.207
232406W1-004 FULL
Solar/Wind Helper
0.511
232434Z2-077 GEN
Solar/Wind Helper
0.128
233950AC2-186 GEN
Solar/Wind Helper
0.117
230415AB2-049 C
Solar/Wind Helper
0.031
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
219291REEVESSOUT C
Solar/Wind Helper
0.012
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.312
219612MATRIX C
Solar/Wind Helper
0.024
205941AD2-115 GEN
Solar/Wind Helper
0.499
20716928W4-060COL
Solar/Wind Helper
0.052
219249CENTRALDIV C
Solar/Wind Helper
0.01
217213AMBOY SO C
Solar/Wind Helper
0.029
207442AE1-156 GEN
Solar/Wind Helper
0.328
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
207511W3-106 GEN
Solar/Wind Helper
0.027
20671928W4-073
Solar/Wind Helper
0.09
20674128FR_U2-059
Solar/Wind Helper
0.004
209116AE2-175 GEN
Solar/Wind Helper
1.794
211065PSPA IPP
Solar/Wind Helper
0.153
963161AG1-165 GEN
Solar/Wind Helper
0.442
961331AF2-424 GEN
Solar/Wind Helper
0.44
270594AE1-207 GEN
Solar/Wind Harmer
13.328
270032AE2-172
Solar/Wind Harmer
4.564
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.023
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.17
20674828DL_W4-046
Solar/Wind Helper
0.008
CPLELTFEXP_CPLE->PJM
CLTF
0.575
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.294
NYPJM->LTFIMP_NY
CLTF
4.833
LGEELTFEXP_LGEE->PJM
CLTF
6.723
WECLTFEXP_WEC->PJM
CLTF
3.81
AG2-052LTFEXP_AG2-052->PJM
LTF
0.239
AH1-155LTFEXP_AH1-155->PJM
LTF
0.358
LAGNLTFEXP_LAGN->PJM
CLTF
14.758
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.672
TVALTFEXP_TVA->PJM
CLTF
7.253
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.516
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.953
MECLTFEXP_MEC->PJM
CLTF
15.837
SIGELTFEXP_SIGE->PJM
CLTF
0.503

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-014_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.01 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4959.97
MW Contribution:
25.21
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972239AH1-704 GEN
Adder
2.68
270459AD2-067 GEN
Solar/Wind Harmer
10.209
961821AG1-024 GEN
Solar/Wind Harmer
10.365
241955AC1-078 GEN
Solar/Wind Harmer
8.772
241973AD2-163_GEN1
Solar/Wind Harmer
2.316
241974AD2-163_GEN2
Solar/Wind Harmer
2.316
945631AF1-228 GEN
Solar/Wind Harmer
5.442
943861AF1-054 GEN
Solar/Wind Harmer
4.469
943851AF1-053 GEN
Solar/Wind Harmer
2.16
270223U2-072_GEN1
Solar/Wind Harmer
2.27
270224U2-072_GEN2
Solar/Wind Harmer
2.27
270227U2-072_GEN3
Solar/Wind Harmer
2.27
270228U2-072_GEN4
Solar/Wind Harmer
2.27
270231U2-072_GEN5
Solar/Wind Harmer
2.27
270578AF1-285 GEN2
Solar/Wind Harmer
0.535
270432AC2-029 GEN
Solar/Wind Harmer
8.017
253338AC1-165 GEN
Solar/Wind Harmer
1.233
253343AC1-166 GEN
Solar/Wind Harmer
1.233
940611AE2-048 GEN
Solar/Wind Harmer
25.038
941391AE2-136 GEN
Solar/Wind Harmer
12.974
270302AB2-170 GEN
Solar/Wind Harmer
9.503
270263AC1-001 GEN
Solar/Wind Harmer
1.169
241972AD1-140 GEN
Solar/Wind Harmer
5
270291AC1-194 GEN
Solar/Wind Harmer
5.607
970179AG2-119 GEN
Solar/Wind Harmer
8.805
270340AC2-060 GEN
Solar/Wind Harmer
3.324
253372AE2-315 SEC3
Adder
2.057
253372AE2-315 SEC3
Adder
2.057
25306009OHH W.
Adder
3.121
253406AD2-031_GEN
Solar/Wind Harmer
1.379
957201AF2-014 GEN
Solar/Wind Harmer
4.876
270435AC2-044 GEN
Solar/Wind Harmer
2.15
270377AD1-106 GEN
Solar/Wind Harmer
5.625
253433AC1-085 GEN1
Solar/Wind Harmer
5.693
253432AC1-085 GEN2
Solar/Wind Harmer
0.287
247521TR3_G114
Solar/Wind Harmer
3.595
270191TR4_S_V150
Solar/Wind Harmer
3.208
965051AG1-369 GEN
Solar/Wind Harmer
5.341
959331AF2-224 GEN
Solar/Wind Harmer
10.694
270007AE1-245 C
Solar/Wind Harmer
5.766
965041AG1-368 GEN
Solar/Wind Harmer
10.672
971567AH1-282 GEN
Solar/Wind Harmer
5.325
966831AG1-554 GEN
Solar/Wind Harmer
1.274
24729505KEY G4
Adder
6.892
963791AG1-232 GEN
Solar/Wind Harmer
14.329
270071AF1-092 GEN
Solar/Wind Harmer
15.92
971985AH1-537 GEN
Solar/Wind Harmer
18.912
958711AF2-162 GEN
Solar/Wind Harmer
1.07
25196408WSDLE3
Adder
9.313
25196308WSDLE2
Adder
9.232
25196208WSDLE1
Adder
9.209
25196708WSDLE6
Adder
9.186
25196508WSDLE4
Adder
8.954
945581AF1-223 GEN
Solar/Wind Harmer
4.78
270404AC1-167 GEN
Solar/Wind Harmer
1.141
971029AG2-637 GEN
Solar/Wind Harmer
15.805
270119AB2-067 GEN1
50/50
7.073
270120AB2-067 GEN2
50/50
7.073
24318905MLG2
50/50
7.043
23684101S70BUS1
50/50
0.165
270349AD2-093_GEN
Solar/Wind Harmer
4.444
270471AD2-092_GEN
Solar/Wind Harmer
4.444
270054AF2-122 C O1
Solar/Wind Harmer
3.974
946101AF1-275 GEN
Solar/Wind Harmer
1.809
253383AE2-342_GEN
Solar/Wind Harmer
1.038
942861AE2-305 GEN
Solar/Wind Harmer
9.054
938701AE1-092 GEN
Solar/Wind Harmer
23.739
270462AD2-086
Solar/Wind Harmer
7.893
270269AC2-059
Solar/Wind Harmer
10.558
972159AH1-661 GEN
Adder
1.114
253378AE2-206_GEN
Solar/Wind Harmer
3.989
253415AE1-040 GEN
Solar/Wind Harmer
1.24
25326509SID D
Adder
1.448
241960AC2-195 GEN
Solar/Wind Harmer
3.054
971073AG2-665 GEN
Solar/Wind Harmer
8.762
970879AG2-548 GEN
Solar/Wind Harmer
1.274
25326109MON D
Adder
1.438
25322209TAIT E
Adder
10.61
25322209TAIT E
Adder
10.372
253370AE2-315 SEC1
Adder
2.175
927014AC1-188 GEN
Solar/Wind Harmer
1.714
253349AC2-067 GEN
Solar/Wind Harmer
2.197
253400AC2-068 GEN
Solar/Wind Harmer
0.884
246937BC-WTG2
Solar/Wind Harmer
4.206
270246TR4_N_V150
Solar/Wind Harmer
0.91
270247TR4_N_V136
Solar/Wind Harmer
0.91
942801AE2-298 GEN
Solar/Wind Harmer
1.617
247607V1-011 GEN
Solar/Wind Harmer
4.221
962581AG1-107 GEN
Solar/Wind Harmer
5.341
961491AF2-440 GEN
Solar/Wind Harmer
2.22
25183208HLCRTG
Solar/Wind Harmer
6.409
944541AF1-119 GEN
Solar/Wind Harmer
4.43
960971AF2-388 GEN
Solar/Wind Harmer
11.565
942221AE2-234 GEN
Solar/Wind Harmer
3.699
25194408D.CRK1
Adder
7.977
25194508D.CRK3
Adder
1.491
252509AD1-136 GEN
Solar/Wind Harmer
0.27
970883AG2-550 GEN
Solar/Wind Harmer
10.53
970885AG2-551 GEN
Solar/Wind Harmer
2.449
247621Y3-024
Adder
0.254
270201AC2-176 GEN
Solar/Wind Harmer
5.404
964611AG1-324 GEN
Solar/Wind Harmer
0.55
970349AG2-230 GEN
Solar/Wind Harmer
15.746
270031AE2-169
Solar/Wind Harmer
8.55
270599AE1-208 GEN
Solar/Wind Harmer
8.55
270383AD1-128 GEN
Solar/Wind Harmer
6.399
926881AC1-175 GEN
Solar/Wind Harmer
5.844
247620Y3-023
Adder
0.482
944231AF1-091 GEN
Solar/Wind Harmer
18.838
24728805RICHG1
Adder
3.948
24728905RICHG2
Adder
3.948
274770LINCOLN ;1U
Adder
8.644
274771LINCOLN ;2U
Adder
8.644
274805UNIV PK N;1U
Adder
5.131
274808UNIV PK N;4U
Adder
5.098
274674JOLIET 9 ;6U
Adder
15.646
274696ROCKY RD ;4P
Adder
11.494
274695ROCKY RD ;2P
Adder
11.229
274693ROCKY RD ;1P
Adder
11.118
274697ROCKY RD ;3P
Adder
3.05
274683WAUKEGAN ;8U
Adder
21.233
274683WAUKEGAN ;8U
Adder
9.373
316097T157 G90
Solar/Wind Helper
1.512
235054AD2-180 GEN
Solar/Wind Helper
2.035
23585401KL_K28_T16
Solar/Wind Helper
1.485
235531U2-073 GEN
Solar/Wind Helper
3.323
238117U2-030
Solar/Wind Helper
0.343
238147AE2-230_GEN1
Solar/Wind Helper
0.499
238148AE2-230_GEN2
Solar/Wind Helper
0.499
238149AF1-291A_GEN
Solar/Wind Helper
0.143
235020AA1-095 C
Solar/Wind Helper
0.053
237061AD1-155 GEN
Solar/Wind Helper
1.768
23751201ROTHROCK
Solar/Wind Helper
0.823
238221AF1-254 C O1
Solar/Wind Helper
0.277
237080AD1-060 GEN
Solar/Wind Helper
0.345
235062AE1-101 C1
Solar/Wind Helper
1.673
316411AF1-147_GEN1
Solar/Wind Helper
0.896
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.37
223402AF1-300 C
Solar/Wind Helper
0.37
316006AB2-029 C
Solar/Wind Helper
0.119
233982AB2-133 GEN
Solar/Wind Helper
0.362
233930AB2-032 GEN
Solar/Wind Helper
0.384
232424Y1-079 C
Solar/Wind Helper
0.117
232436AB1-176 C
Solar/Wind Helper
0.045
233946AB2-136 GEN
Solar/Wind Helper
0.573
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.969
232410W1-006 C
Solar/Wind Helper
0.511
232428Y3-058 C
Solar/Wind Helper
0.341
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.234
233954AC2-188 GEN
Solar/Wind Helper
0.234
316045AC1-158 PL2
Solar/Wind Helper
4.174
316450AC1-158 RIC
Solar/Wind Helper
0.348
230511AF1-262
Solar/Wind Helper
0.015
230433AD2-135 GEN
Solar/Wind Helper
0.017
228754AB1-001 C
Solar/Wind Helper
0.026
219904AC1-010 C
Solar/Wind Helper
0.061
219912AD2-042 GEN
Solar/Wind Helper
0.151
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219906AC1-017 C
Solar/Wind Helper
0.042
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.132
214067T20SOLAR
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.064
207459AE1-142 C O1
Solar/Wind Helper
0.292
20714828MDF_W3-079
Solar/Wind Helper
0.131
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
20675428EAM_W2-061
Solar/Wind Helper
0.016
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.023
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.17
20674828DL_W4-046
Solar/Wind Helper
0.008
24318805MLG1
50/50
10.069
23559001PLEAS1
50/50
6.109
270051AF1-062 GEN
50/50
11.788
270475AD2-096_GEN
50/50
7.121
962771AG1-126 GEN
Solar/Wind Harmer
40.825
970153AG2-106 GEN
Solar/Wind Harmer
17.802
961921AG1-034 GEN
Solar/Wind Harmer
15.548
270284AF1-227 GEN1
Solar/Wind Harmer
6.753
270287AF1-227 GEN3
Solar/Wind Harmer
2.498
24721905FLATG4
Adder
23.852
942051AE2-217 GEN
Solar/Wind Harmer
20.967
960801AF2-371 GEN
Solar/Wind Harmer
2.937
964871AG1-351 GEN
Solar/Wind Harmer
2.028
942871AE2-306 GEN
Solar/Wind Harmer
1.043
270391AF1-285 GEN3
Solar/Wind Harmer
0.535
270518AE2-148 GEN
Solar/Wind Harmer
13.799
253325AC1-069 GEN
Solar/Wind Harmer
1.189
276820AF1-078_GEN
Solar/Wind Harmer
1.772
958581AF2-149 GEN
Solar/Wind Harmer
4.723
971199AH1-059 GEN
Solar/Wind Harmer
2.318
270512AE1-227 GEN2
Solar/Wind Harmer
2.305
970879AG2-548 GEN
Solar/Wind Harmer
8.762
960071AF2-298 GEN
Solar/Wind Harmer
1.643
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
970065AG2-057 GEN
Solar/Wind Harmer
0.922
957541AF2-048 GEN
Solar/Wind Harmer
1.714
253394AE2-221_GEN
Solar/Wind Harmer
4.888
246938BC-WTG3
Solar/Wind Harmer
4.278
270491AE1-102 GEN2
Solar/Wind Harmer
1.398
971191AH1-055 GEN
Solar/Wind Harmer
20.024
253317AC1-085 GEN4
Solar/Wind Harmer
8.97
946181AF1-283 GEN
Solar/Wind Harmer
13.928
965021AG1-366 GEN
Solar/Wind Harmer
2.487
958091AF2-103 GEN
Solar/Wind Harmer
0.172
270588AE1-091_GEN
Solar/Wind Harmer
11.743
24695305TIMB G C
Solar/Wind Harmer
3.563
944531AF1-118 GEN
Solar/Wind Harmer
37.241
270043AE2-236 GEN
Solar/Wind Harmer
5.847
252519AF1-045_GEN
Solar/Wind Harmer
3.849
270367AC2-061_GEN
Solar/Wind Harmer
3.358
252524AE2-267 GEN
Solar/Wind Harmer
1.662
25196608WSDLE5
Adder
9.047
25194608D.CRK4
Adder
1.734
270044AE2-322 C
Solar/Wind Harmer
1.385
252507AC2-088 GEN
Solar/Wind Harmer
1.887
270063AE2-323 C
Solar/Wind Harmer
2.313
962031AG1-047 GEN
Solar/Wind Harmer
3.179
957741AF2-068 GEN
Solar/Wind Harmer
15.772
971347AH1-153 GEN
Solar/Wind Harmer
5.249
270186AC1-089 GEN
Solar/Wind Harmer
6.407
946031AF1-268 GEN
Solar/Wind Harmer
8.698
270330AC1-082 GEN2
Solar/Wind Harmer
0.498
270329AC1-082 GEN1
Solar/Wind Harmer
0.498
270004AE1-209 GEN
Solar/Wind Harmer
5.725
24379505HDWTR1G C
Solar/Wind Harmer
8.279
270240V3-007_GEN2
Solar/Wind Harmer
6.478
970825AG2-519 GEN
Solar/Wind Harmer
5.896
247643Z2-116 C
Solar/Wind Harmer
0.073
25196008MFTGT1
Adder
1.4
274752CRETE EC ;2U
Adder
8.445
274753CRETE EC ;3U
Adder
8.445
274772LINCOLN ;3U
Adder
8.644
274724RIVER EC ;11
Adder
18.136
274814UNIV PK N;0U
Adder
5.165
274807UNIV PK N;3U
Adder
5.154
274811UNIV PK N;7U
Adder
5.12
274803UNIV PARK;6U
Adder
5.948
24728705AND G3
Adder
8.182
24728505AND G1
Adder
3.912
274826FISK ;BP
Adder
11.164
972038AH1-567 GEN2
Adder
0.372
972259AH1-714 GEN
Adder
19.435
274676JOLIET 29;8U
Adder
30.072
274729ELWOOD EC;1P
Adder
16.705
274730ELWOOD EC;6P
Adder
16.705
274734ELWOOD EC;8P
Adder
16.705
274736ELWOOD EC;9P
Adder
16.705
274682WAUKEGAN ;7U
Adder
18.116
964991AG1-363 GEN
Solar/Wind Helper
5.159
238108AE1-109 GEN1
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238127S14_GEN_2
Solar/Wind Helper
0.83
238175AF1-290_GEN
Solar/Wind Helper
0.158
238152AF2-075_GEN
Solar/Wind Helper
0.714
23777901MDS_W4-102
Solar/Wind Helper
0.179
23562501BACKB
Solar/Wind Helper
1.006
235063AE1-101 C2
Solar/Wind Helper
1.673
237001AB1-127_GEN
Solar/Wind Helper
0.445
316415AF1-147_GEN2
Solar/Wind Helper
0.896
237048AF1-022 C
Solar/Wind Helper
0.184
205916AD1-020 GEN
Solar/Wind Helper
1.727
208835TUHI V3-051
Solar/Wind Helper
0.022
205932AD2-116_GEN
Solar/Wind Helper
0.513
233918AB1-142 GEN
Solar/Wind Helper
0.506
233944AB2-135 GEN
Solar/Wind Helper
0.595
232426Y1-080 FULL
Solar/Wind Helper
0.039
233996TM1833_GEN
Solar/Wind Helper
0.207
270166AC1-044 GEN3
50/50
7.073
23559101PLEAS2
50/50
6.109
23684201S70BUS2
50/50
0.168
962761AG1-125 GEN
Solar/Wind Harmer
40.825
970149AG2-104 GEN
Solar/Wind Harmer
25.209
970155AG2-107 GEN
Solar/Wind Harmer
17.802
270520AE2-214 GEN
Solar/Wind Harmer
7.236
270286AF1-227 GEN2
Solar/Wind Harmer
2.498
270391AF1-285 GEN3
Solar/Wind Harmer
1.39
270578AF1-285 GEN2
Solar/Wind Harmer
1.39
253333AC1-068 GEN
Solar/Wind Harmer
1.189
270317AD1-130_GEN
Solar/Wind Harmer
3.633
270485AE1-090_GEN
Solar/Wind Harmer
0.686
971995AH1-542 GEN
Solar/Wind Harmer
12.457
270273AD2-016 GEN
Solar/Wind Harmer
3.01
972269AH1-719 GEN
Adder
2.576
270510AE1-227 GEN1
Solar/Wind Harmer
2.716
971073AG2-665 GEN
Solar/Wind Harmer
1.274
25326309TAIT D
Adder
1.192
241813AF1-122_GEN
Solar/Wind Harmer
5.898
971201AH1-060 GEN
Solar/Wind Harmer
1.843
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
253398AE2-221_GEN2
Solar/Wind Harmer
4.888
246936BC-WTG1
Solar/Wind Harmer
4.206
270489AE1-102 GEN1
Solar/Wind Harmer
1.398
965421AG1-410 GEN
Solar/Wind Harmer
32.239
960001AF2-291 GEN
Solar/Wind Harmer
3.243
253316AC1-085 GEN3
Solar/Wind Harmer
8.97
946171AF1-282 GEN
Solar/Wind Harmer
10.714
965011AG1-365 GEN
Solar/Wind Harmer
10.694
270258AD1-119 GEN
Solar/Wind Harmer
2.151
965651AG1-433 GEN
Solar/Wind Harmer
5.783
252516AE2-318_GEN
Solar/Wind Harmer
10.575
958861AF2-177 GEN
Solar/Wind Harmer
11.549
252510AF1-249 C
Solar/Wind Harmer
0.44
270024AE2-089 GEN
Solar/Wind Harmer
4.946
25194608D.CRK4
Adder
1.734
270297AD1-101 GEN
Solar/Wind Harmer
2.142
945371AF1-202 GEN
Solar/Wind Harmer
7.353
270222AC2-111 GEN
Solar/Wind Harmer
4.705
944031AF1-071 GEN
Solar/Wind Harmer
1.059
270331AC1-082 GEN3
Solar/Wind Harmer
0.499
270005AE1-210 C O1
Solar/Wind Harmer
5.725
25196808ZIMRHP
Adder
79.46
942081AE2-220 GEN
Solar/Wind Harmer
6.696
270209AC1-174_GEN
Solar/Wind Harmer
4.261
270437AC2-090 C
Solar/Wind Harmer
5.844
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232404W1-003 C
Solar/Wind Helper
0.511
232408W1-005 C
Solar/Wind Helper
0.511
316447AC1-158 HLD
Solar/Wind Helper
2.87
316044AC1-158 PL1
Solar/Wind Helper
1.304
228729W2-030 C
Solar/Wind Helper
0.111
219766PARADISE C
Solar/Wind Helper
0.055
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.115
203975AE1-071-GEN
Solar/Wind Helper
2.518
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714528FRN_Y2-051
Solar/Wind Helper
0.057
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
218440SUMMTASSOC C
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207530AG1-191 GEN
Solar/Wind Helper
0.067
20676328BVR_Y1-020
Solar/Wind Helper
0.027
207439AE1-081 C O1
Solar/Wind Helper
0.019
207484AF2-139 C O1
Solar/Wind Helper
0.085
20674928WA_W3-044
Solar/Wind Helper
0.099
20674628WNG_W3-110
Solar/Wind Helper
0.09
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
207518AF1-320_GEN
Solar/Wind Helper
1.581
20675828AU_W4-064
Solar/Wind Helper
0.03
970031AG2-029 GEN
Solar/Wind Harmer
26.336
270543AE2-219 C
Solar/Wind Harmer
10.53
247536S-71 GEN
Solar/Wind Harmer
4.259
961761AG1-017 GEN
Solar/Wind Harmer
0.45
964611AG1-324 GEN
Solar/Wind Harmer
4.098
25196108MFTGT2
Adder
1.593
25196108MFTGT2
Adder
1.479
274775LINCOLN ;6U
Adder
8.644
274776LINCOLN ;7U
Adder
8.644
274777LINCOLN ;8U
Adder
8.644
972037AH1-567 GEN1
Adder
0.187
274827FISK ;RP
Adder
7.912
274800UNIV PARK;3U
Adder
5.944
274801UNIV PARK;4U
Adder
5.944
972228AH1-698 GEN2
Adder
3.776
972227AH1-698 GEN1
Adder
2.659
274687WILL CNTY;4U
Adder
28.416
274687WILL CNTY;4U
Adder
28.416
274675JOLIET 29;7U
Adder
31.186
274675JOLIET 29;7U
Adder
30.072
274728ELWOOD EC;5P
Adder
16.705
274731ELWOOD EC;2P
Adder
16.705
274733ELWOOD EC;3P
Adder
16.705
274735ELWOOD EC;4P
Adder
16.705
274744AC1-111 GEN8
Adder
5.658
274746AC1-111 G10
Adder
5.658
23750701CROSSCHOOL
Solar/Wind Helper
1.507
238118U2-030_1
Solar/Wind Helper
0.343
238169AE2-226 GEN1
Solar/Wind Helper
0.707
238170AE2-226 GEN2
Solar/Wind Helper
0.707
23779801AA1-109
Solar/Wind Helper
0.195
3138216PACIFIC
Solar/Wind Helper
0.045
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.166
23750501ELLIOTTS
Solar/Wind Helper
0.64
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.371
959381AF2-229 GEN
Solar/Wind Helper
0.359
20390526W1-045 C
Solar/Wind Helper
0.353
3141426STAFORD
Solar/Wind Helper
0.053
205943AE1-185 GEN
Solar/Wind Helper
0.513
205956AE1-196_GEN
Solar/Wind Helper
0.513
233915AB1-141 GEN
Solar/Wind Helper
0.506
233901CHERRYDALE C
Solar/Wind Helper
0.234
233940AF2-379 C
Solar/Wind Helper
0.063
232432Z2-076 GEN
Solar/Wind Helper
0.068
315651AD1-115 GEN
Solar/Wind Helper
0.793
230434AG1-499 GEN
Solar/Wind Helper
0.232
228728W1-130C
Solar/Wind Helper
0.054
230407AD2-065 C
Solar/Wind Helper
0.041
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219615MILLCREEK C
Solar/Wind Helper
0.027
20715028HAN_X4-015
Solar/Wind Helper
0.058
20720728JCB_W1-129
Solar/Wind Helper
0.058
207445AB1-138_GEN
Solar/Wind Helper
0.105
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.191
316164AC1-076 GEN
Solar/Wind Helper
1.106
20675528CPH_W2-050
Solar/Wind Helper
0.114
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.097
20676428JCR_X2-075
Solar/Wind Helper
0.068
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.085
20675128HRM_W1-127
Solar/Wind Helper
0.03
209027LOR2_Q27
Solar/Wind Helper
1.033
212266LOR1
Solar/Wind Helper
0.301
211065PSPA IPP
Solar/Wind Helper
0.153
961301AF2-421 GEN
Solar/Wind Helper
0.442
963151AG1-164 GEN
Solar/Wind Helper
0.442
961341AF2-425 GEN
Solar/Wind Helper
0.44
270239V3-007_GEN1
Solar/Wind Harmer
1.802
970825AG2-519 GEN
Solar/Wind Harmer
2.196
24639705ELKHART HY
Adder
0.16
270216AD2-079_GEN
Solar/Wind Harmer
0.632
25196008MFTGT1
Adder
1.445
274751CRETE EC ;1U
Adder
8.445
274754CRETE EC ;4U
Adder
8.445
274773LINCOLN ;4U
Adder
8.644
274774LINCOLN ;5U
Adder
8.644
274723RIVER EC ;12
Adder
18.35
274812UNIV PK N;8U
Adder
5.12
274802UNIV PARK;5U
Adder
5.948
24728605AND G2
Adder
3.912
274676JOLIET 29;8U
Adder
31.186
274732ELWOOD EC;7P
Adder
16.705
274674JOLIET 9 ;6U
Adder
15.646
972203AH1-686 GEN
Adder
2.33
274745AC1-111 GEN9
Adder
5.658
970091AG2-072 GEN
Adder
77.346
274682WAUKEGAN ;7U
Adder
18.116
316095T157 G97
Solar/Wind Helper
1.512
23583801GRNGAP
Solar/Wind Helper
5.632
238185AF2-356 C
Solar/Wind Helper
2.664
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238120AE2-309 GEN
Solar/Wind Helper
0.53
238126S14_GEN_1
Solar/Wind Helper
0.83
23546401DTGZ2-030
Solar/Wind Helper
0.09
237085AD2-009_GEN
Solar/Wind Helper
1.662
237038AE2-054 C
Solar/Wind Helper
0.275
235067AD1-061 GEN
Solar/Wind Helper
0.449
237002AB1-128_GEN
Solar/Wind Helper
0.447
23777801MSM_W1-116
Solar/Wind Helper
0.115
23751101LEADS_P59
Solar/Wind Helper
2.095
3141196NOKESVL
Solar/Wind Helper
1.037
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.349
208835TUHI V3-051
Solar/Wind Helper
0.022
233935AB2-179 C
Solar/Wind Helper
1.279
233987AB2-037 GEN
Solar/Wind Helper
2.362
233933AB2-153 GEN
Solar/Wind Helper
0.234
232422X3-066 FULL
Solar/Wind Helper
0.115
232417X3-008 C
Solar/Wind Helper
0.234
233964AF2-378 GEN
Solar/Wind Helper
0.042
233923SMA
Solar/Wind Helper
0.758
233997TMININ_4.2
Solar/Wind Helper
0.207
232406W1-004 FULL
Solar/Wind Helper
0.511
232434Z2-077 GEN
Solar/Wind Helper
0.128
233950AC2-186 GEN
Solar/Wind Helper
0.117
230415AB2-049 C
Solar/Wind Helper
0.031
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
219291REEVESSOUT C
Solar/Wind Helper
0.012
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.312
219612MATRIX C
Solar/Wind Helper
0.024
205941AD2-115 GEN
Solar/Wind Helper
0.499
20716928W4-060COL
Solar/Wind Helper
0.052
219249CENTRALDIV C
Solar/Wind Helper
0.01
217213AMBOY SO C
Solar/Wind Helper
0.029
207442AE1-156 GEN
Solar/Wind Helper
0.328
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
207511W3-106 GEN
Solar/Wind Helper
0.027
20671928W4-073
Solar/Wind Helper
0.09
20674128FR_U2-059
Solar/Wind Helper
0.004
209116AE2-175 GEN
Solar/Wind Helper
1.794
211065PSPA IPP
Solar/Wind Helper
0.153
963161AG1-165 GEN
Solar/Wind Helper
0.442
961331AF2-424 GEN
Solar/Wind Helper
0.44
270594AE1-207 GEN
Solar/Wind Harmer
13.328
270032AE2-172
Solar/Wind Harmer
4.564
CPLELTFEXP_CPLE->PJM
CLTF
0.575
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.294
NYPJM->LTFIMP_NY
CLTF
4.833
LGEELTFEXP_LGEE->PJM
CLTF
6.723
WECLTFEXP_WEC->PJM
CLTF
3.81
AG2-052LTFEXP_AG2-052->PJM
LTF
0.239
AH1-155LTFEXP_AH1-155->PJM
LTF
0.358
LAGNLTFEXP_LAGN->PJM
CLTF
14.758
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.672
TVALTFEXP_TVA->PJM
CLTF
7.253
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.516
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.953
MECLTFEXP_MEC->PJM
CLTF
15.837
SIGELTFEXP_SIGE->PJM
CLTF
0.503

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-007A_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-007A_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:131.87 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4917.49
MW Contribution:
18.57
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
7.069
270120AB2-067 GEN2
50/50
7.069
24318905MLG2
50/50
7.039
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0
942861AE2-305 GEN
Solar/Wind Harmer
6.31
938701AE1-092 GEN
Solar/Wind Harmer
12.867
971655AH1-328 GEN
Solar/Wind Harmer
2.843
270462AD2-086
Solar/Wind Harmer
0
270269AC2-059
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
1.113
970329AG2-216 GEN
Solar/Wind Harmer
3.341
25326509SID D
Adder
1.446
971073AG2-665 GEN
Solar/Wind Harmer
5.597
970879AG2-548 GEN
Solar/Wind Harmer
1.272
25326109MON D
Adder
1.437
25322209TAIT E
Adder
10.598
25322209TAIT E
Adder
10.36
253370AE2-315 SEC1
Adder
2.172
246937BC-WTG2
Solar/Wind Harmer
0.302
270246TR4_N_V150
Solar/Wind Harmer
0.048
270247TR4_N_V136
Solar/Wind Harmer
0.048
247607V1-011 GEN
Solar/Wind Harmer
0
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25183208HLCRTG
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.351
944541AF1-119 GEN
Solar/Wind Harmer
0.492
960971AF2-388 GEN
Solar/Wind Harmer
4.326
942221AE2-234 GEN
Solar/Wind Harmer
2.958
25194408D.CRK1
Adder
7.968
25194508D.CRK3
Adder
1.49
970621AG2-405 GEN
Solar/Wind Harmer
1.345
252509AD1-136 GEN
Solar/Wind Harmer
0.037
970883AG2-550 GEN
Solar/Wind Harmer
7.338
970885AG2-551 GEN
Solar/Wind Harmer
2.446
247621Y3-024
Adder
0.253
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.549
970349AG2-230 GEN
Solar/Wind Harmer
10.973
270031AE2-169
Solar/Wind Harmer
4.021
270599AE1-208 GEN
Solar/Wind Harmer
6.701
270383AD1-128 GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
247620Y3-023
Adder
0.481
944231AF1-091 GEN
Solar/Wind Harmer
16.825
24728805RICHG1
Adder
3.944
24728905RICHG2
Adder
3.944
971613AH1-306 GEN
Solar/Wind Harmer
3.493
970291AG2-192 GEN
Solar/Wind Harmer
0.945
970291AG2-192 GEN
Solar/Wind Harmer
0.436
961051AF2-396 GEN
Solar/Wind Harmer
14.52
961051AF2-396 GEN
Solar/Wind Harmer
9.68
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
9.052
965791AG1-447 GEN
Solar/Wind Harmer
6.638
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
8.634
274771LINCOLN ;2U
Adder
8.634
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.807
274805UNIV PK N;1U
Adder
5.126
274808UNIV PK N;4U
Adder
5.092
274888KELLY CRK;1U
Solar/Wind Harmer
0.414
276776AD2-060 GEN
Solar/Wind Harmer
0.758
958011AF2-095 GEN
Solar/Wind Harmer
10.234
970941AG2-585 GEN
Solar/Wind Harmer
3.909
276897AD1-100 C
Solar/Wind Harmer
17.749
274674JOLIET 9 ;6U
Adder
15.628
276893AG1-478 C
Solar/Wind Harmer
0.472
970241AG2-163 GEN
Solar/Wind Harmer
4.124
958481AF2-142 GEN
Solar/Wind Harmer
10.569
274696ROCKY RD ;4P
Adder
11.481
274695ROCKY RD ;2P
Adder
11.216
274693ROCKY RD ;1P
Adder
11.106
274697ROCKY RD ;3P
Adder
3.047
958491AF2-143 GEN
Solar/Wind Harmer
10.536
276901AD2-066 C O1
Solar/Wind Harmer
0
274683WAUKEGAN ;8U
Adder
21.209
274683WAUKEGAN ;8U
Adder
9.636
962691AG1-118 GEN
Solar/Wind Harmer
21.036
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
7.415
942111AE2-223 GEN
Solar/Wind Harmer
2.266
316097T157 G90
Solar/Wind Helper
1.51
235054AD2-180 GEN
Solar/Wind Helper
2.04
23585401KL_K28_T16
Solar/Wind Helper
1.489
235531U2-073 GEN
Solar/Wind Helper
3.327
238117U2-030
Solar/Wind Helper
0.343
238147AE2-230_GEN1
Solar/Wind Helper
0.499
238148AE2-230_GEN2
Solar/Wind Helper
0.499
238149AF1-291A_GEN
Solar/Wind Helper
0.143
235020AA1-095 C
Solar/Wind Helper
0.053
23751201ROTHROCK
Solar/Wind Helper
0.828
237061AD1-155 GEN
Solar/Wind Helper
1.767
238221AF1-254 C O1
Solar/Wind Helper
0.277
237080AD1-060 GEN
Solar/Wind Helper
0.344
235062AE1-101 C1
Solar/Wind Helper
1.672
316411AF1-147_GEN1
Solar/Wind Helper
0.895
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.37
223402AF1-300 C
Solar/Wind Helper
0.37
316006AB2-029 C
Solar/Wind Helper
0.118
233982AB2-133 GEN
Solar/Wind Helper
0.362
233930AB2-032 GEN
Solar/Wind Helper
0.383
232424Y1-079 C
Solar/Wind Helper
0.117
232436AB1-176 C
Solar/Wind Helper
0.045
233946AB2-136 GEN
Solar/Wind Helper
0.573
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.968
232410W1-006 C
Solar/Wind Helper
0.511
232428Y3-058 C
Solar/Wind Helper
0.341
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.234
233954AC2-188 GEN
Solar/Wind Helper
0.234
316045AC1-158 PL2
Solar/Wind Helper
4.17
316450AC1-158 RIC
Solar/Wind Helper
0.348
230511AF1-262
Solar/Wind Helper
0.015
230433AD2-135 GEN
Solar/Wind Helper
0.017
228754AB1-001 C
Solar/Wind Helper
0.026
219904AC1-010 C
Solar/Wind Helper
0.061
219912AD2-042 GEN
Solar/Wind Helper
0.151
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219906AC1-017 C
Solar/Wind Helper
0.042
219607WPEMNERT C
Solar/Wind Helper
0.081
972239AH1-704 GEN
Adder
2.678
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
5.057
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
945631AF1-228 GEN
Solar/Wind Harmer
0.001
943861AF1-054 GEN
Solar/Wind Harmer
3.115
943851AF1-053 GEN
Solar/Wind Harmer
2.157
270578AF1-285 GEN2
Solar/Wind Harmer
0.534
270432AC2-029 GEN
Solar/Wind Harmer
3.538
940611AE2-048 GEN
Solar/Wind Harmer
19.52
941391AE2-136 GEN
Solar/Wind Harmer
10.996
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.113
270263AC1-001 GEN
Solar/Wind Harmer
0.78
241972AD1-140 GEN
Solar/Wind Harmer
0.849
270291AC1-194 GEN
Solar/Wind Harmer
0
970179AG2-119 GEN
Solar/Wind Harmer
6.854
270340AC2-060 GEN
Solar/Wind Harmer
0.001
253372AE2-315 SEC3
Adder
2.055
253372AE2-315 SEC3
Adder
2.055
25306009OHH W.
Adder
3.117
253406AD2-031_GEN
Solar/Wind Harmer
0.559
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.949
270377AD1-106 GEN
Solar/Wind Harmer
2.842
247521TR3_G114
Solar/Wind Harmer
0.27
965051AG1-369 GEN
Solar/Wind Harmer
3.723
959331AF2-224 GEN
Solar/Wind Harmer
5.217
270007AE1-245 C
Solar/Wind Harmer
0
965041AG1-368 GEN
Solar/Wind Harmer
7.438
971567AH1-282 GEN
Solar/Wind Harmer
5.69
24729505KEY G4
Adder
6.885
963791AG1-232 GEN
Solar/Wind Harmer
9.987
270071AF1-092 GEN
Solar/Wind Harmer
14.177
971985AH1-537 GEN
Solar/Wind Harmer
2.196
25196408WSDLE3
Adder
9.302
25196308WSDLE2
Adder
9.221
25196208WSDLE1
Adder
9.198
25196708WSDLE6
Adder
9.175
25196508WSDLE4
Adder
8.944
945581AF1-223 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
11.014
970031AG2-029 GEN
Solar/Wind Harmer
3.977
270543AE2-219 C
Solar/Wind Harmer
5.137
247536S-71 GEN
Solar/Wind Harmer
0.293
964611AG1-324 GEN
Solar/Wind Harmer
2.856
971609AH1-304 GEN
Solar/Wind Harmer
1.194
970289AG2-191 GEN
Solar/Wind Harmer
1.382
971771AH1-392 GEN
Solar/Wind Harmer
7.271
270526AF1-158 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
25196108MFTGT2
Adder
1.591
25196108MFTGT2
Adder
1.478
270356AE2-297 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
959141AF2-205 GEN
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
4.281
971549AH1-272 GEN
Solar/Wind Harmer
14.794
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.634
274776LINCOLN ;7U
Adder
8.634
274777LINCOLN ;8U
Adder
8.634
24386405FR-21G C
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.186
960591AF2-350 GEN
Solar/Wind Harmer
7.107
274827FISK ;RP
Adder
7.903
274800UNIV PARK;3U
Adder
5.937
274801UNIV PARK;4U
Adder
5.937
972228AH1-698 GEN2
Adder
3.772
972227AH1-698 GEN1
Adder
2.656
963841AG1-237 GEN
Solar/Wind Harmer
3.075
972163AH1-664 GEN
Solar/Wind Harmer
7.896
972165AH1-665 GEN
Solar/Wind Harmer
6.324
274687WILL CNTY;4U
Adder
28.385
274687WILL CNTY;4U
Adder
28.385
274675JOLIET 29;7U
Adder
31.151
274675JOLIET 29;7U
Adder
30.039
274728ELWOOD EC;5P
Adder
16.687
274731ELWOOD EC;2P
Adder
16.687
274733ELWOOD EC;3P
Adder
16.687
274735ELWOOD EC;4P
Adder
16.687
970833AG2-524 GEN
Solar/Wind Harmer
7.786
970833AG2-524 GEN
Solar/Wind Harmer
5.191
274744AC1-111 GEN8
Adder
5.652
274746AC1-111 G10
Adder
5.652
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.341
970169AG2-114 GEN
Solar/Wind Harmer
7.011
945641AF1-229 GEN
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
2.723
276861AD2-134 GEN
Solar/Wind Harmer
0.124
276863AD2-134 GEN
Solar/Wind Harmer
0.124
971411AH1-196 GEN
Solar/Wind Harmer
10.47
926823AC1-168 GEN
Solar/Wind Harmer
1.186
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.32
23750701CROSSCHOOL
Solar/Wind Helper
1.509
238118U2-030_1
Solar/Wind Helper
0.343
238169AE2-226 GEN1
Solar/Wind Helper
0.706
238170AE2-226 GEN2
Solar/Wind Helper
0.706
23779801AA1-109
Solar/Wind Helper
0.194
3138216PACIFIC
Solar/Wind Helper
0.045
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.165
23750501ELLIOTTS
Solar/Wind Helper
0.642
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.371
959381AF2-229 GEN
Solar/Wind Helper
0.359
20390526W1-045 C
Solar/Wind Helper
0.353
3141426STAFORD
Solar/Wind Helper
0.053
205943AE1-185 GEN
Solar/Wind Helper
0.513
205956AE1-196_GEN
Solar/Wind Helper
0.512
233915AB1-141 GEN
Solar/Wind Helper
0.506
233901CHERRYDALE C
Solar/Wind Helper
0.234
233940AF2-379 C
Solar/Wind Helper
0.062
232432Z2-076 GEN
Solar/Wind Helper
0.067
315651AD1-115 GEN
Solar/Wind Helper
0.793
230434AG1-499 GEN
Solar/Wind Helper
0.232
228728W1-130C
Solar/Wind Helper
0.054
230407AD2-065 C
Solar/Wind Helper
0.041
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219615MILLCREEK C
Solar/Wind Helper
0.027
20715028HAN_X4-015
Solar/Wind Helper
0.057
20720728JCB_W1-129
Solar/Wind Helper
0.057
207445AB1-138_GEN
Solar/Wind Helper
0.105
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.191
316164AC1-076 GEN
Solar/Wind Helper
1.105
20675528CPH_W2-050
Solar/Wind Helper
0.114
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.096
20676428JCR_X2-075
Solar/Wind Helper
0.068
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.085
20675128HRM_W1-127
Solar/Wind Helper
0.03
209027LOR2_Q27
Solar/Wind Helper
1.031
212266LOR1
Solar/Wind Helper
0.3
203955AF1-039 C O1
Solar/Wind Helper
0.33
971171AH1-044 GEN
Solar/Wind Harmer
9.057
219304NAMERICA C
Solar/Wind Helper
0.132
214067T20SOLAR
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.064
207459AE1-142 C O1
Solar/Wind Helper
0.292
20714828MDF_W3-079
Solar/Wind Helper
0.131
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
20675428EAM_W2-061
Solar/Wind Helper
0.016
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.023
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.169
20674828DL_W4-046
Solar/Wind Helper
0.008
971341AH1-150 GEN
Solar/Wind Harmer
9.057
971343AH1-151 GEN
Solar/Wind Harmer
9.057
24318805MLG1
50/50
10.065
23559001PLEAS1
50/50
6.097
270051AF1-062 GEN
50/50
11.777
270475AD2-096_GEN
50/50
7.114
962771AG1-126 GEN
Solar/Wind Harmer
34.394
970153AG2-106 GEN
Solar/Wind Harmer
21.963
961921AG1-034 GEN
Solar/Wind Harmer
7.586
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
24721905FLATG4
Adder
23.821
942051AE2-217 GEN
Solar/Wind Harmer
14.613
270391AF1-285 GEN3
Solar/Wind Harmer
0.534
270518AE2-148 GEN
Solar/Wind Harmer
0.653
253325AC1-069 GEN
Solar/Wind Harmer
0.009
971199AH1-059 GEN
Solar/Wind Harmer
1.615
270512AE1-227 GEN2
Solar/Wind Harmer
1.954
970879AG2-548 GEN
Solar/Wind Harmer
5.597
970065AG2-057 GEN
Solar/Wind Harmer
0.757
253370AE2-315 SEC1
Adder
2.172
253371AE2-315 SEC2
Adder
2.055
970191AG2-125 GEN
Solar/Wind Harmer
1.937
253394AE2-221_GEN
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.27
270491AE1-102 GEN2
Solar/Wind Harmer
0.974
971191AH1-055 GEN
Solar/Wind Harmer
19.175
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.706
965021AG1-366 GEN
Solar/Wind Harmer
2.484
270588AE1-091_GEN
Solar/Wind Harmer
5.82
24695305TIMB G C
Solar/Wind Harmer
0.63
944531AF1-118 GEN
Solar/Wind Harmer
33.233
270043AE2-236 GEN
Solar/Wind Harmer
4.754
252519AF1-045_GEN
Solar/Wind Harmer
3.844
270367AC2-061_GEN
Solar/Wind Harmer
0
25196608WSDLE5
Adder
9.036
25194608D.CRK4
Adder
1.732
252507AC2-088 GEN
Solar/Wind Harmer
0.33
270063AE2-323 C
Solar/Wind Harmer
0
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.991
971347AH1-153 GEN
Solar/Wind Harmer
3.658
270186AC1-089 GEN
Solar/Wind Harmer
0
946031AF1-268 GEN
Solar/Wind Harmer
6.95
270004AE1-209 GEN
Solar/Wind Harmer
1.582
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
5.494
970289AG2-191 GEN
Solar/Wind Harmer
0.8
945111AF1-176 GEN
Solar/Wind Harmer
5.891
247642Z2-115 C
Solar/Wind Harmer
0.003
270505AE1-170 C O1
Solar/Wind Harmer
7.629
25196008MFTGT1
Adder
1.398
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
7.162
958171AF2-111 GEN
Solar/Wind Harmer
17.857
274752CRETE EC ;2U
Adder
8.436
274753CRETE EC ;3U
Adder
8.436
274772LINCOLN ;3U
Adder
8.634
274724RIVER EC ;11
Adder
18.116
24386205FR-12G C
Solar/Wind Harmer
0
274814UNIV PK N;0U
Adder
5.159
274807UNIV PK N;3U
Adder
5.148
274811UNIV PK N;7U
Adder
5.114
972167AH1-666 GEN
Solar/Wind Harmer
5.69
274803UNIV PARK;6U
Adder
5.941
24728705AND G3
Adder
8.173
24728505AND G1
Adder
3.908
274887GEN-1.85
Solar/Wind Harmer
0.185
276843GEN-1.7
Solar/Wind Harmer
0.23
276806AD2-047 C O1
Solar/Wind Harmer
4.027
274826FISK ;BP
Adder
11.151
972038AH1-567 GEN2
Adder
0.372
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
23.191
972259AH1-714 GEN
Adder
19.413
274676JOLIET 29;8U
Adder
30.039
274729ELWOOD EC;1P
Adder
16.687
274730ELWOOD EC;6P
Adder
16.687
274734ELWOOD EC;8P
Adder
16.687
274736ELWOOD EC;9P
Adder
16.687
943121AE2-341 GEN
Solar/Wind Harmer
11.83
943591AF1-030 GEN
Solar/Wind Harmer
7.867
270541AE2-072 C
Solar/Wind Harmer
0
274862TOP CROP ;2U
Solar/Wind Harmer
0.951
274682WAUKEGAN ;7U
Adder
18.096
276868AE1-113 GEN
Solar/Wind Harmer
1.403
274879MINONK ;1U
Solar/Wind Harmer
0.293
946671AF1-331 GEN
Solar/Wind Harmer
0.745
274855GSG-6 ;RU
Solar/Wind Harmer
0.255
274850MENDOTA H;RU
Solar/Wind Harmer
0.081
970193AG2-126 GEN
Solar/Wind Harmer
10.468
970571AG2-364 GEN
Solar/Wind Harmer
13.944
964991AG1-363 GEN
Solar/Wind Helper
5.155
238108AE1-109 GEN1
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238127S14_GEN_2
Solar/Wind Helper
0.831
238175AF1-290_GEN
Solar/Wind Helper
0.158
238152AF2-075_GEN
Solar/Wind Helper
0.713
23777901MDS_W4-102
Solar/Wind Helper
0.178
23562501BACKB
Solar/Wind Helper
1.012
235063AE1-101 C2
Solar/Wind Helper
1.672
237001AB1-127_GEN
Solar/Wind Helper
0.445
237048AF1-022 C
Solar/Wind Helper
0.184
316415AF1-147_GEN2
Solar/Wind Helper
0.895
205916AD1-020 GEN
Solar/Wind Helper
1.725
208835TUHI V3-051
Solar/Wind Helper
0.022
205932AD2-116_GEN
Solar/Wind Helper
0.512
233918AB1-142 GEN
Solar/Wind Helper
0.506
233944AB2-135 GEN
Solar/Wind Helper
0.594
232426Y1-080 FULL
Solar/Wind Helper
0.039
233996TM1833_GEN
Solar/Wind Helper
0.207
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232404W1-003 C
Solar/Wind Helper
0.511
232408W1-005 C
Solar/Wind Helper
0.511
316447AC1-158 HLD
Solar/Wind Helper
2.868
316044AC1-158 PL1
Solar/Wind Helper
1.303
228729W2-030 C
Solar/Wind Helper
0.111
219766PARADISE C
Solar/Wind Helper
0.055
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.115
203975AE1-071-GEN
Solar/Wind Helper
2.516
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714528FRN_Y2-051
Solar/Wind Helper
0.057
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
218440SUMMTASSOC C
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207530AG1-191 GEN
Solar/Wind Helper
0.067
207439AE1-081 C O1
Solar/Wind Helper
0.019
20676328BVR_Y1-020
Solar/Wind Helper
0.027
207484AF2-139 C O1
Solar/Wind Helper
0.085
20674928WA_W3-044
Solar/Wind Helper
0.099
20674628WNG_W3-110
Solar/Wind Helper
0.09
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
207518AF1-320_GEN
Solar/Wind Helper
1.58
20675828AU_W4-064
Solar/Wind Helper
0.03
211065PSPA IPP
Solar/Wind Helper
0.152
961301AF2-421 GEN
Solar/Wind Helper
0.441
963151AG1-164 GEN
Solar/Wind Helper
0.441
202652Y1-033 WT C
Solar/Wind Helper
0.5
959091AF2-200 GEN
Solar/Wind Harmer
9.057
270166AC1-044 GEN3
50/50
7.069
23559101PLEAS2
50/50
6.097
962761AG1-125 GEN
Solar/Wind Harmer
34.394
970149AG2-104 GEN
Solar/Wind Harmer
18.573
970155AG2-107 GEN
Solar/Wind Harmer
21.963
270520AE2-214 GEN
Solar/Wind Harmer
0
253333AC1-068 GEN
Solar/Wind Harmer
0.009
270317AD1-130_GEN
Solar/Wind Harmer
0
971995AH1-542 GEN
Solar/Wind Harmer
2.894
270273AD2-016 GEN
Solar/Wind Harmer
0.807
972269AH1-719 GEN
Adder
2.573
270510AE1-227 GEN1
Solar/Wind Harmer
1.954
971073AG2-665 GEN
Solar/Wind Harmer
1.272
25326309TAIT D
Adder
1.191
241813AF1-122_GEN
Solar/Wind Harmer
3.39
971201AH1-060 GEN
Solar/Wind Harmer
1.514
253370AE2-315 SEC1
Adder
2.172
253371AE2-315 SEC2
Adder
2.055
253398AE2-221_GEN2
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.302
270489AE1-102 GEN1
Solar/Wind Harmer
0.974
965421AG1-410 GEN
Solar/Wind Harmer
22.47
960001AF2-291 GEN
Solar/Wind Harmer
0
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.466
965011AG1-365 GEN
Solar/Wind Harmer
7.453
965651AG1-433 GEN
Solar/Wind Harmer
2.163
252516AE2-318_GEN
Solar/Wind Harmer
8.253
958861AF2-177 GEN
Solar/Wind Harmer
3.191
270024AE2-089 GEN
Solar/Wind Harmer
0.001
252510AF1-249 C
Solar/Wind Harmer
0.056
25194608D.CRK4
Adder
1.732
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.582
25196808ZIMRHP
Adder
79.365
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.351
970825AG2-519 GEN
Solar/Wind Harmer
2.589
24639705ELKHART HY
Adder
0.16
270594AE1-207 GEN
Solar/Wind Harmer
8.151
270032AE2-172
Solar/Wind Harmer
4.852
945111AF1-176 GEN
Solar/Wind Harmer
12.968
957891AF2-083 GEN
Solar/Wind Harmer
12.11
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.787
276903AD2-071 C
Solar/Wind Harmer
8.095
25196008MFTGT1
Adder
1.443
970773AG2-487 GEN
Solar/Wind Harmer
1.277
970373AG2-245 GEN
Solar/Wind Harmer
15.17
270055AF2-134 C O1
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.365
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.989
274751CRETE EC ;1U
Adder
8.436
274754CRETE EC ;4U
Adder
8.436
274773LINCOLN ;4U
Adder
8.634
274774LINCOLN ;5U
Adder
8.634
274723RIVER EC ;12
Adder
18.33
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
5.114
274802UNIV PARK;5U
Adder
5.941
24728605AND G2
Adder
3.908
945681AF1-233 GEN
Solar/Wind Harmer
13.398
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
31.151
274732ELWOOD EC;7P
Adder
16.687
274674JOLIET 9 ;6U
Adder
15.628
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
16.733
274745AC1-111 GEN9
Adder
5.652
972203AH1-686 GEN
Adder
2.327
939401AE1-172 GEN
Solar/Wind Harmer
5.275
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.145
274861TOP CROP ;1U
Solar/Wind Harmer
0
970091AG2-072 GEN
Adder
77.252
274682WAUKEGAN ;7U
Adder
18.096
276805AD2-038 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.818
971997AH1-543 GEN
Solar/Wind Harmer
3.68
962781AG1-127 GEN
Solar/Wind Harmer
6.668
274872LEEDK;1U
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
20.915
939741AE1-205 GEN
Solar/Wind Harmer
9.761
316095T157 G97
Solar/Wind Helper
1.51
23583801GRNGAP
Solar/Wind Helper
5.626
238185AF2-356 C
Solar/Wind Helper
2.669
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238120AE2-309 GEN
Solar/Wind Helper
0.531
238126S14_GEN_1
Solar/Wind Helper
0.831
23546401DTGZ2-030
Solar/Wind Helper
0.09
237085AD2-009_GEN
Solar/Wind Helper
1.661
237038AE2-054 C
Solar/Wind Helper
0.274
235067AD1-061 GEN
Solar/Wind Helper
0.449
237002AB1-128_GEN
Solar/Wind Helper
0.446
23751101LEADS_P59
Solar/Wind Helper
2.119
23777801MSM_W1-116
Solar/Wind Helper
0.115
3141196NOKESVL
Solar/Wind Helper
1.036
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.349
208835TUHI V3-051
Solar/Wind Helper
0.022
233935AB2-179 C
Solar/Wind Helper
1.278
233987AB2-037 GEN
Solar/Wind Helper
2.36
233933AB2-153 GEN
Solar/Wind Helper
0.234
232422X3-066 FULL
Solar/Wind Helper
0.115
232417X3-008 C
Solar/Wind Helper
0.234
233964AF2-378 GEN
Solar/Wind Helper
0.042
233923SMA
Solar/Wind Helper
0.757
233997TMININ_4.2
Solar/Wind Helper
0.207
232406W1-004 FULL
Solar/Wind Helper
0.511
232434Z2-077 GEN
Solar/Wind Helper
0.128
233950AC2-186 GEN
Solar/Wind Helper
0.117
230415AB2-049 C
Solar/Wind Helper
0.031
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
219291REEVESSOUT C
Solar/Wind Helper
0.012
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.312
219612MATRIX C
Solar/Wind Helper
0.024
205941AD2-115 GEN
Solar/Wind Helper
0.499
20716928W4-060COL
Solar/Wind Helper
0.052
219249CENTRALDIV C
Solar/Wind Helper
0.01
217213AMBOY SO C
Solar/Wind Helper
0.029
207442AE1-156 GEN
Solar/Wind Helper
0.328
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
207511W3-106 GEN
Solar/Wind Helper
0.027
20671928W4-073
Solar/Wind Helper
0.09
20674128FR_U2-059
Solar/Wind Helper
0.004
209116AE2-175 GEN
Solar/Wind Helper
1.792
211065PSPA IPP
Solar/Wind Helper
0.152
963161AG1-165 GEN
Solar/Wind Helper
0.441
957471AF2-041 GEN
Solar/Wind Harmer
13.586
959081AF2-199 GEN
Solar/Wind Harmer
4.529
971067AG2-660 GEN
Solar/Wind Harmer
1.51
CPLELTFEXP_CPLE->PJM
CLTF
0.571
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.151
NYPJM->LTFIMP_NY
CLTF
4.827
LGEELTFEXP_LGEE->PJM
CLTF
6.715
WECLTFEXP_WEC->PJM
CLTF
3.806
AG2-052LTFEXP_AG2-052->PJM
LTF
0.238
AH1-155LTFEXP_AH1-155->PJM
LTF
0.358
LAGNLTFEXP_LAGN->PJM
CLTF
14.738
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.655
TVALTFEXP_TVA->PJM
CLTF
7.243
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.362
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.914
MECLTFEXP_MEC->PJM
CLTF
15.818
SIGELTFEXP_SIGE->PJM
CLTF
0.502

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-012_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-012_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:130.69 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4873.53
MW Contribution:
25.23
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
7.05
270120AB2-067 GEN2
50/50
7.05
24318905MLG2
50/50
7.451
270054AF2-122 C O1
Solar/Wind Harmer
4.054
270349AD2-093_GEN
Solar/Wind Harmer
4.513
270471AD2-092_GEN
Solar/Wind Harmer
4.513
946101AF1-275 GEN
Solar/Wind Harmer
1.838
253383AE2-342_GEN
Solar/Wind Harmer
1.057
938701AE1-092 GEN
Solar/Wind Harmer
24.428
24318805MLG1
50/50
10
23559001PLEAS1
50/50
5.445
270051AF1-062 GEN
50/50
11.971
962771AG1-126 GEN
Solar/Wind Harmer
40.867
970153AG2-106 GEN
Solar/Wind Harmer
17.82
961921AG1-034 GEN
Solar/Wind Harmer
15.881
270284AF1-227 GEN1
Solar/Wind Harmer
6.884
270287AF1-227 GEN3
Solar/Wind Harmer
2.547
942051AE2-217 GEN
Solar/Wind Harmer
21.323
942871AE2-306 GEN
Solar/Wind Harmer
1.07
270391AF1-285 GEN3
Solar/Wind Harmer
0.549
960801AF2-371 GEN
Solar/Wind Harmer
2.983
964871AG1-351 GEN
Solar/Wind Harmer
2.06
270512AE1-227 GEN2
Solar/Wind Harmer
2.449
270518AE2-148 GEN
Solar/Wind Harmer
13.997
958581AF2-149 GEN
Solar/Wind Harmer
4.955
971199AH1-059 GEN
Solar/Wind Harmer
2.432
24721905FLATG4
Adder
23.444
253325AC1-069 GEN
Solar/Wind Harmer
1.205
970065AG2-057 GEN
Solar/Wind Harmer
0.972
276820AF1-078_GEN
Solar/Wind Harmer
1.81
270588AE1-091_GEN
Solar/Wind Harmer
12.281
961961AG1-039 GEN
Solar/Wind Harmer
3.18
246938BC-WTG3
Solar/Wind Harmer
4.404
270491AE1-102 GEN2
Solar/Wind Harmer
1.439
970879AG2-548 GEN
Solar/Wind Harmer
8.835
958091AF2-103 GEN
Solar/Wind Harmer
0.178
960071AF2-298 GEN
Solar/Wind Harmer
1.664
253303V4-073 C
Solar/Wind Harmer
0.127
253370AE2-315 SEC1
Adder
2.2
253371AE2-315 SEC2
Adder
2.081
24695305TIMB G C
Solar/Wind Harmer
3.661
965021AG1-366 GEN
Solar/Wind Harmer
2.544
270044AE2-322 C
Solar/Wind Harmer
1.431
253394AE2-221_GEN
Solar/Wind Harmer
4.932
957541AF2-048 GEN
Solar/Wind Harmer
1.72
270043AE2-236 GEN
Solar/Wind Harmer
5.961
944531AF1-118 GEN
Solar/Wind Harmer
37.819
253317AC1-085 GEN4
Solar/Wind Harmer
9.041
946181AF1-283 GEN
Solar/Wind Harmer
14.038
270063AE2-323 C
Solar/Wind Harmer
2.363
270541AE2-072 C
Solar/Wind Harmer
4.86
971191AH1-055 GEN
Solar/Wind Harmer
20.005
971347AH1-153 GEN
Solar/Wind Harmer
5.342
247643Z2-116 C
Solar/Wind Harmer
0.074
962031AG1-047 GEN
Solar/Wind Harmer
3.224
957741AF2-068 GEN
Solar/Wind Harmer
15.993
945111AF1-176 GEN
Solar/Wind Harmer
6.028
270505AE1-170 C O1
Solar/Wind Harmer
15.984
252519AF1-045_GEN
Solar/Wind Harmer
3.876
252524AE2-267 GEN
Solar/Wind Harmer
1.675
25196608WSDLE5
Adder
9.116
25194608D.CRK4
Adder
1.747
270367AC2-061_GEN
Solar/Wind Harmer
3.375
23906502RICHG2&3
Adder
1.268
23906402RICHG1
Adder
1.268
25196008MFTGT1
Adder
1.409
274752CRETE EC ;2U
Adder
8.571
274753CRETE EC ;3U
Adder
8.571
274724RIVER EC ;11
Adder
18.401
274772LINCOLN ;3U
Adder
8.764
274814UNIV PK N;0U
Adder
5.24
274807UNIV PK N;3U
Adder
5.228
274811UNIV PK N;7U
Adder
5.194
274803UNIV PARK;6U
Adder
6.031
274826FISK ;BP
Adder
11.319
972038AH1-567 GEN2
Adder
0.377
972259AH1-714 GEN
Adder
19.698
274676JOLIET 29;8U
Adder
30.477
274729ELWOOD EC;1P
Adder
16.929
274730ELWOOD EC;6P
Adder
16.929
274734ELWOOD EC;8P
Adder
16.929
274736ELWOOD EC;9P
Adder
16.929
964991AG1-363 GEN
Solar/Wind Helper
5.569
238108AE1-109 GEN1
Solar/Wind Helper
0.122
238110AE1-109 GEN3
Solar/Wind Helper
0.122
238152AF2-075_GEN
Solar/Wind Helper
0.794
238175AF1-290_GEN
Solar/Wind Helper
0.173
238127S14_GEN_2
Solar/Wind Helper
0.87
23777901MDS_W4-102
Solar/Wind Helper
0.192
942861AE2-305 GEN
Solar/Wind Harmer
9.201
270462AD2-086
Solar/Wind Harmer
8.12
972159AH1-661 GEN
Adder
1.163
241960AC2-195 GEN
Solar/Wind Harmer
3.204
270269AC2-059
Solar/Wind Harmer
10.672
253378AE2-206_GEN
Solar/Wind Harmer
4.074
25326509SID D
Adder
1.478
253415AE1-040 GEN
Solar/Wind Harmer
1.252
25326109MON D
Adder
1.457
246937BC-WTG2
Solar/Wind Harmer
4.329
971073AG2-665 GEN
Solar/Wind Harmer
8.835
970879AG2-548 GEN
Solar/Wind Harmer
1.284
25322209TAIT E
Adder
10.744
25322209TAIT E
Adder
10.502
942801AE2-298 GEN
Solar/Wind Harmer
1.666
247607V1-011 GEN
Solar/Wind Harmer
4.348
253370AE2-315 SEC1
Adder
2.2
270246TR4_N_V150
Solar/Wind Harmer
0.933
270247TR4_N_V136
Solar/Wind Harmer
0.933
247522W1-056 GEN
Solar/Wind Harmer
2.469
253349AC2-067 GEN
Solar/Wind Harmer
2.225
253400AC2-068 GEN
Solar/Wind Harmer
0.895
927014AC1-188 GEN
Solar/Wind Harmer
1.72
944231AF1-091 GEN
Solar/Wind Harmer
19.433
942221AE2-234 GEN
Solar/Wind Harmer
3.759
944541AF1-119 GEN
Solar/Wind Harmer
4.494
960971AF2-388 GEN
Solar/Wind Harmer
11.731
247620Y3-023
Adder
0.492
970349AG2-230 GEN
Solar/Wind Harmer
16.027
247621Y3-024
Adder
0.257
25183208HLCRTG
Solar/Wind Harmer
6.454
970883AG2-550 GEN
Solar/Wind Harmer
10.668
970885AG2-551 GEN
Solar/Wind Harmer
2.481
962581AG1-107 GEN
Solar/Wind Harmer
5.371
961491AF2-440 GEN
Solar/Wind Harmer
2.232
270201AC2-176 GEN
Solar/Wind Harmer
5.48
961051AF2-396 GEN
Solar/Wind Harmer
16.91
961051AF2-396 GEN
Solar/Wind Harmer
7.865
964611AG1-324 GEN
Solar/Wind Harmer
0.557
270031AE2-169
Solar/Wind Harmer
8.665
270599AE1-208 GEN
Solar/Wind Harmer
8.665
25194408D.CRK1
Adder
8.037
25194508D.CRK3
Adder
1.503
24728805RICHG1
Adder
3.989
24728905RICHG2
Adder
3.989
970935AG2-582 GEN
Adder
238.716
274770LINCOLN ;1U
Adder
8.764
274771LINCOLN ;2U
Adder
8.764
274805UNIV PK N;1U
Adder
5.205
274808UNIV PK N;4U
Adder
5.171
274674JOLIET 9 ;6U
Adder
0.246
316097T157 G90
Solar/Wind Helper
1.71
238147AE2-230_GEN1
Solar/Wind Helper
0.556
238148AE2-230_GEN2
Solar/Wind Helper
0.556
238149AF1-291A_GEN
Solar/Wind Helper
0.159
237061AD1-155 GEN
Solar/Wind Helper
1.974
235054AD2-180 GEN
Solar/Wind Helper
2.118
235531U2-073 GEN
Solar/Wind Helper
3.481
23585401KL_K28_T16
Solar/Wind Helper
1.534
972239AH1-704 GEN
50/50
3.095
270459AD2-067 GEN
Solar/Wind Harmer
10.428
961821AG1-024 GEN
Solar/Wind Harmer
10.588
241955AC1-078 GEN
Solar/Wind Harmer
8.918
241973AD2-163_GEN1
Solar/Wind Harmer
2.358
241974AD2-163_GEN2
Solar/Wind Harmer
2.358
940611AE2-048 GEN
Solar/Wind Harmer
26.008
941391AE2-136 GEN
Solar/Wind Harmer
13.477
270223U2-072_GEN1
Solar/Wind Harmer
2.33
270224U2-072_GEN2
Solar/Wind Harmer
2.33
270227U2-072_GEN3
Solar/Wind Harmer
2.33
270228U2-072_GEN4
Solar/Wind Harmer
2.33
270231U2-072_GEN5
Solar/Wind Harmer
2.33
270578AF1-285 GEN2
Solar/Wind Harmer
0.549
943861AF1-054 GEN
Solar/Wind Harmer
4.542
943851AF1-053 GEN
Solar/Wind Harmer
2.195
945631AF1-228 GEN
Solar/Wind Harmer
5.525
270302AB2-170 GEN
Solar/Wind Harmer
9.776
270432AC2-029 GEN
Solar/Wind Harmer
8.117
970179AG2-119 GEN
Solar/Wind Harmer
9.237
253338AC1-165 GEN
Solar/Wind Harmer
1.249
253343AC1-166 GEN
Solar/Wind Harmer
1.249
241972AD1-140 GEN
Solar/Wind Harmer
5.07
270263AC1-001 GEN
Solar/Wind Harmer
1.18
971567AH1-282 GEN
Solar/Wind Harmer
5.635
235020AA1-095 C
Solar/Wind Helper
0.058
238117U2-030
Solar/Wind Helper
0.357
238221AF1-254 C O1
Solar/Wind Helper
0.297
237080AD1-060 GEN
Solar/Wind Helper
0.369
235062AE1-101 C1
Solar/Wind Helper
1.786
316411AF1-147_GEN1
Solar/Wind Helper
0.984
23751201ROTHROCK
Solar/Wind Helper
0.821
237006AB1-125 GEN
Solar/Wind Helper
0.132
316006AB2-029 C
Solar/Wind Helper
0.131
223401AF1-299 GEN
Solar/Wind Helper
0.389
223402AF1-300 C
Solar/Wind Helper
0.389
316045AC1-158 PL2
Solar/Wind Helper
4.643
316450AC1-158 RIC
Solar/Wind Helper
0.387
3132123MT JACKSON
Solar/Wind Helper
0.767
233930AB2-032 GEN
Solar/Wind Helper
0.389
233982AB2-133 GEN
Solar/Wind Helper
0.367
232424Y1-079 C
Solar/Wind Helper
0.119
232436AB1-176 C
Solar/Wind Helper
0.045
233946AB2-136 GEN
Solar/Wind Helper
0.581
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.982
232410W1-006 C
Solar/Wind Helper
0.518
232428Y3-058 C
Solar/Wind Helper
0.346
234015AF2-250 C
Solar/Wind Helper
0.039
233952AC2-187 GEN
Solar/Wind Helper
0.238
233954AC2-188 GEN
Solar/Wind Helper
0.238
966001AG1-469 GEN
Solar/Wind Helper
0.256
230511AF1-262
Solar/Wind Helper
0.015
230433AD2-135 GEN
Solar/Wind Helper
0.017
228754AB1-001 C
Solar/Wind Helper
0.026
219904AC1-010 C
Solar/Wind Helper
0.061
219912AD2-042 GEN
Solar/Wind Helper
0.152
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219906AC1-017 C
Solar/Wind Helper
0.042
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.133
214067T20SOLAR
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.064
207459AE1-142 C O1
Solar/Wind Helper
0.293
20714828MDF_W3-079
Solar/Wind Helper
0.132
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
20675428EAM_W2-061
Solar/Wind Helper
0.016
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.023
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.169
20674828DL_W4-046
Solar/Wind Helper
0.008
270377AD1-106 GEN
Solar/Wind Harmer
5.917
966831AG1-554 GEN
Solar/Wind Harmer
1.337
270291AC1-194 GEN
Solar/Wind Harmer
5.669
270340AC2-060 GEN
Solar/Wind Harmer
3.354
957201AF2-014 GEN
Solar/Wind Harmer
5.019
270435AC2-044 GEN
Solar/Wind Harmer
2.213
270007AE1-245 C
Solar/Wind Harmer
5.939
253372AE2-315 SEC3
Adder
2.081
253372AE2-315 SEC3
Adder
2.081
247521TR3_G114
Solar/Wind Harmer
3.687
270191TR4_S_V150
Solar/Wind Harmer
3.29
965051AG1-369 GEN
Solar/Wind Harmer
5.479
25306009OHH W.
Adder
3.158
965041AG1-368 GEN
Solar/Wind Harmer
10.944
959331AF2-224 GEN
Solar/Wind Harmer
10.939
253406AD2-031_GEN
Solar/Wind Harmer
1.391
270404AC1-167 GEN
Solar/Wind Harmer
1.18
963791AG1-232 GEN
Solar/Wind Harmer
14.614
253433AC1-085 GEN1
Solar/Wind Harmer
5.738
253432AC1-085 GEN2
Solar/Wind Harmer
0.289
270071AF1-092 GEN
Solar/Wind Harmer
16.191
24729505KEY G4
Adder
6.997
945641AF1-229 GEN
Solar/Wind Harmer
3.912
970031AG2-029 GEN
Solar/Wind Harmer
26.913
958711AF2-162 GEN
Solar/Wind Harmer
1.086
945581AF1-223 GEN
Solar/Wind Harmer
4.845
971029AG2-637 GEN
Solar/Wind Harmer
16.005
270499AE1-146 GEN
Solar/Wind Harmer
2.679
270543AE2-219 C
Solar/Wind Harmer
10.668
247536S-71 GEN
Solar/Wind Harmer
4.316
961761AG1-017 GEN
Solar/Wind Harmer
0.456
964611AG1-324 GEN
Solar/Wind Harmer
4.154
971771AH1-392 GEN
Solar/Wind Harmer
9.58
944161AF1-084 GEN
Solar/Wind Harmer
2.352
25196408WSDLE3
Adder
9.385
25196308WSDLE2
Adder
9.303
25196208WSDLE1
Adder
9.28
25196708WSDLE6
Adder
9.256
25196508WSDLE4
Adder
9.023
25196108MFTGT2
Adder
1.604
25196108MFTGT2
Adder
1.489
274775LINCOLN ;6U
Adder
8.764
274776LINCOLN ;7U
Adder
8.764
274777LINCOLN ;8U
Adder
8.764
972037AH1-567 GEN1
Adder
0.189
274827FISK ;RP
Adder
8.022
274800UNIV PARK;3U
Adder
6.026
274801UNIV PARK;4U
Adder
6.026
972228AH1-698 GEN2
Adder
3.828
972227AH1-698 GEN1
Adder
2.695
274687WILL CNTY;4U
Adder
28.802
274687WILL CNTY;4U
Adder
28.802
274675JOLIET 29;7U
Adder
31.606
274675JOLIET 29;7U
Adder
30.477
274728ELWOOD EC;5P
Adder
16.929
274731ELWOOD EC;2P
Adder
16.929
274733ELWOOD EC;3P
Adder
16.929
274735ELWOOD EC;4P
Adder
16.929
23750701CROSSCHOOL
Solar/Wind Helper
1.591
238169AE2-226 GEN1
Solar/Wind Helper
0.777
238170AE2-226 GEN2
Solar/Wind Helper
0.777
238118U2-030_1
Solar/Wind Helper
0.357
3138216PACIFIC
Solar/Wind Helper
0.049
23779801AA1-109
Solar/Wind Helper
0.208
237030AB1-096 C
Solar/Wind Helper
0.071
237025AB1-124 C
Solar/Wind Helper
0.176
226929AD2-058 GEN
Solar/Wind Helper
0.108
3141426STAFORD
Solar/Wind Helper
0.058
315651AD1-115 GEN
Solar/Wind Helper
0.883
316164AC1-076 GEN
Solar/Wind Helper
1.232
23750501ELLIOTTS
Solar/Wind Helper
0.631
205917AD1-020 ES
Solar/Wind Helper
0.381
959381AF2-229 GEN
Solar/Wind Helper
0.368
20390526W1-045 C
Solar/Wind Helper
0.361
205943AE1-185 GEN
Solar/Wind Helper
0.521
205956AE1-196_GEN
Solar/Wind Helper
0.521
233915AB1-141 GEN
Solar/Wind Helper
0.514
233901CHERRYDALE C
Solar/Wind Helper
0.238
233940AF2-379 C
Solar/Wind Helper
0.063
232432Z2-076 GEN
Solar/Wind Helper
0.068
230434AG1-499 GEN
Solar/Wind Helper
0.234
228728W1-130C
Solar/Wind Helper
0.055
230407AD2-065 C
Solar/Wind Helper
0.041
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.078
219615MILLCREEK C
Solar/Wind Helper
0.027
20715028HAN_X4-015
Solar/Wind Helper
0.058
20720728JCB_W1-129
Solar/Wind Helper
0.058
207445AB1-138_GEN
Solar/Wind Helper
0.106
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.192
20675528CPH_W2-050
Solar/Wind Helper
0.114
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.097
20676428JCR_X2-075
Solar/Wind Helper
0.068
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.084
20675128HRM_W1-127
Solar/Wind Helper
0.03
235063AE1-101 C2
Solar/Wind Helper
1.786
237001AB1-127_GEN
Solar/Wind Helper
0.476
316415AF1-147_GEN2
Solar/Wind Helper
0.984
23562501BACKB
Solar/Wind Helper
1
316447AC1-158 HLD
Solar/Wind Helper
3.193
316044AC1-158 PL1
Solar/Wind Helper
1.451
237048AF1-022 C
Solar/Wind Helper
0.18
205916AD1-020 GEN
Solar/Wind Helper
1.77
208835TUHI V3-051
Solar/Wind Helper
0.022
205932AD2-116_GEN
Solar/Wind Helper
0.521
233918AB1-142 GEN
Solar/Wind Helper
0.514
233944AB2-135 GEN
Solar/Wind Helper
0.603
232426Y1-080 FULL
Solar/Wind Helper
0.04
3147666LOUISA
Solar/Wind Helper
0.962
233996TM1833_GEN
Solar/Wind Helper
0.21
233998TM1NIN_3.36
Solar/Wind Helper
0.21
232404W1-003 C
Solar/Wind Helper
0.518
232408W1-005 C
Solar/Wind Helper
0.518
316192AB2-158 GEN
Solar/Wind Helper
1.618
228729W2-030 C
Solar/Wind Helper
0.112
219766PARADISE C
Solar/Wind Helper
0.055
203975AE1-071-GEN
Solar/Wind Helper
2.543
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.116
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.065
20714528FRN_Y2-051
Solar/Wind Helper
0.058
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
218440SUMMTASSOC C
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207530AG1-191 GEN
Solar/Wind Helper
0.066
207439AE1-081 C O1
Solar/Wind Helper
0.019
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20674628WNG_W3-110
Solar/Wind Helper
0.09
207484AF2-139 C O1
Solar/Wind Helper
0.084
20674928WA_W3-044
Solar/Wind Helper
0.099
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
207518AF1-320_GEN
Solar/Wind Helper
1.573
20675828AU_W4-064
Solar/Wind Helper
0.03
211065PSPA IPP
Solar/Wind Helper
0.151
270166AC1-044 GEN3
50/50
7.05
23559101PLEAS2
50/50
5.445
270122AB2-093 CT
50/50
4.1
962761AG1-125 GEN
Solar/Wind Harmer
40.867
970149AG2-104 GEN
Solar/Wind Harmer
25.235
970155AG2-107 GEN
Solar/Wind Harmer
17.82
270286AF1-227 GEN2
Solar/Wind Harmer
2.547
270520AE2-214 GEN
Solar/Wind Harmer
7.352
270391AF1-285 GEN3
Solar/Wind Harmer
1.427
270578AF1-285 GEN2
Solar/Wind Harmer
1.427
971995AH1-542 GEN
Solar/Wind Harmer
12.942
972269AH1-719 GEN
Adder
2.693
270317AD1-130_GEN
Solar/Wind Harmer
3.738
270485AE1-090_GEN
Solar/Wind Harmer
0.706
270510AE1-227 GEN1
Solar/Wind Harmer
2.885
253333AC1-068 GEN
Solar/Wind Harmer
1.205
241813AF1-122_GEN
Solar/Wind Harmer
6.22
971201AH1-060 GEN
Solar/Wind Harmer
1.944
270273AD2-016 GEN
Solar/Wind Harmer
3.042
241847AF2-150_GEN
Solar/Wind Harmer
4.61
246936BC-WTG1
Solar/Wind Harmer
4.329
270489AE1-102 GEN1
Solar/Wind Harmer
1.439
965421AG1-410 GEN
Solar/Wind Harmer
33.164
971073AG2-665 GEN
Solar/Wind Harmer
1.284
25326309TAIT D
Adder
1.207
253370AE2-315 SEC1
Adder
2.2
253371AE2-315 SEC2
Adder
2.081
270297AD1-101 GEN
Solar/Wind Harmer
2.226
965011AG1-365 GEN
Solar/Wind Harmer
10.939
270258AD1-119 GEN
Solar/Wind Harmer
2.219
253398AE2-221_GEN2
Solar/Wind Harmer
4.932
253316AC1-085 GEN3
Solar/Wind Harmer
9.041
946171AF1-282 GEN
Solar/Wind Harmer
10.799
965651AG1-433 GEN
Solar/Wind Harmer
5.866
270024AE2-089 GEN
Solar/Wind Harmer
5.027
958861AF2-177 GEN
Solar/Wind Harmer
11.712
960001AF2-291 GEN
Solar/Wind Harmer
3.236
24639705ELKHART HY
Adder
0.164
945371AF1-202 GEN
Solar/Wind Harmer
7.453
270216AD2-079_GEN
Solar/Wind Harmer
0.645
945111AF1-176 GEN
Solar/Wind Harmer
19.021
957891AF2-083 GEN
Solar/Wind Harmer
15.982
252516AE2-318_GEN
Solar/Wind Harmer
10.65
270449AD2-020 GEN
Solar/Wind Harmer
2.984
943021AE2-325 GEN
Solar/Wind Harmer
3.878
270222AC2-111 GEN
Solar/Wind Harmer
4.753
944031AF1-071 GEN
Solar/Wind Harmer
1.069
24441205WTRV SLR C
Solar/Wind Harmer
0.143
252510AF1-249 C
Solar/Wind Harmer
0.443
25194608D.CRK4
Adder
1.747
25196808ZIMRHP
Adder
79.955
23906502RICHG2&3
Adder
1.268
25196008MFTGT1
Adder
1.455
274751CRETE EC ;1U
Adder
8.571
274754CRETE EC ;4U
Adder
8.571
274723RIVER EC ;12
Adder
18.619
274773LINCOLN ;4U
Adder
8.764
274774LINCOLN ;5U
Adder
8.764
274812UNIV PK N;8U
Adder
5.194
274802UNIV PARK;5U
Adder
6.031
23920202STRYCT
Adder
1.44
274676JOLIET 29;8U
Adder
31.606
274732ELWOOD EC;7P
Adder
16.929
274674JOLIET 9 ;6U
Adder
15.855
23583801GRNGAP
Solar/Wind Helper
6.383
316095T157 G97
Solar/Wind Helper
1.71
238109AE1-109 GEN2
Solar/Wind Helper
0.122
238185AF2-356 C
Solar/Wind Helper
2.787
23546401DTGZ2-030
Solar/Wind Helper
0.1
238120AE2-309 GEN
Solar/Wind Helper
0.557
238126S14_GEN_1
Solar/Wind Helper
0.87
237038AE2-054 C
Solar/Wind Helper
0.294
235067AD1-061 GEN
Solar/Wind Helper
0.481
237085AD2-009_GEN
Solar/Wind Helper
1.776
237002AB1-128_GEN
Solar/Wind Helper
0.477
3141196NOKESVL
Solar/Wind Helper
1.144
23777801MSM_W1-116
Solar/Wind Helper
0.123
226910AB2-157 C
Solar/Wind Helper
0.016
227287AC2-120 GEN
Solar/Wind Helper
0.377
23751101LEADS_P59
Solar/Wind Helper
1.984
3132273ORANGE
Solar/Wind Helper
0.049
208835TUHI V3-051
Solar/Wind Helper
0.022
233935AB2-179 C
Solar/Wind Helper
1.297
233987AB2-037 GEN
Solar/Wind Helper
2.395
233933AB2-153 GEN
Solar/Wind Helper
0.238
232422X3-066 FULL
Solar/Wind Helper
0.117
232417X3-008 C
Solar/Wind Helper
0.238
233964AF2-378 GEN
Solar/Wind Helper
0.043
3147666LOUISA
Solar/Wind Helper
0.553
233923SMA
Solar/Wind Helper
0.769
233997TMININ_4.2
Solar/Wind Helper
0.21
232406W1-004 FULL
Solar/Wind Helper
0.518
232434Z2-077 GEN
Solar/Wind Helper
0.13
233950AC2-186 GEN
Solar/Wind Helper
0.119
230415AB2-049 C
Solar/Wind Helper
0.031
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.117
219291REEVESSOUT C
Solar/Wind Helper
0.012
218660EHAMPSOLAR C
Solar/Wind Helper
0.034
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.313
966881AG1-559 GEN
Solar/Wind Helper
0.313
219612MATRIX C
Solar/Wind Helper
0.024
20716928W4-060COL
Solar/Wind Helper
0.052
205941AD2-115 GEN
Solar/Wind Helper
0.499
219249CENTRALDIV C
Solar/Wind Helper
0.01
217213AMBOY SO C
Solar/Wind Helper
0.029
207442AE1-156 GEN
Solar/Wind Helper
0.328
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.138
207511W3-106 GEN
Solar/Wind Helper
0.027
20671928W4-073
Solar/Wind Helper
0.09
20674128FR_U2-059
Solar/Wind Helper
0.004
209116AE2-175 GEN
Solar/Wind Helper
1.777
211065PSPA IPP
Solar/Wind Helper
0.151
960841AF2-375 GEN
Solar/Wind Harmer
0.624
CBM West 2LTFEXP_CBM-W2->PJM
CBM
111.457
NYPJM->LTFIMP_NY
CLTF
4.574
LGEELTFEXP_LGEE->PJM
CLTF
6.731
WECLTFEXP_WEC->PJM
CLTF
3.853
AG2-052LTFEXP_AG2-052->PJM
LTF
0.242
AH1-155LTFEXP_AH1-155->PJM
LTF
0.363
LAGNLTFEXP_LAGN->PJM
CLTF
14.456
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.226
TVALTFEXP_TVA->PJM
CLTF
7.078
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.111
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.423
MECLTFEXP_MEC->PJM
CLTF
15.924
SIGELTFEXP_SIGE->PJM
CLTF
0.504

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-008A_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.24 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4632.89
MW Contribution:
17.93
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972239AH1-704 GEN
50/50
2.774
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.899
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
945631AF1-228 GEN
Solar/Wind Harmer
0.001
943861AF1-054 GEN
Solar/Wind Harmer
3.014
943851AF1-053 GEN
Solar/Wind Harmer
2.087
270578AF1-285 GEN2
Solar/Wind Harmer
0.517
270432AC2-029 GEN
Solar/Wind Harmer
3.42
940611AE2-048 GEN
Solar/Wind Harmer
18.925
941391AE2-136 GEN
Solar/Wind Harmer
10.66
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.077
270263AC1-001 GEN
Solar/Wind Harmer
0.753
241972AD1-140 GEN
Solar/Wind Harmer
0.821
970179AG2-119 GEN
Solar/Wind Harmer
6.643
270291AC1-194 GEN
Solar/Wind Harmer
0
270340AC2-060 GEN
Solar/Wind Harmer
0.001
253372AE2-315 SEC3
Adder
1.985
253372AE2-315 SEC3
Adder
1.985
25306009OHH W.
Adder
3.011
253406AD2-031_GEN
Solar/Wind Harmer
0.539
270377AD1-106 GEN
Solar/Wind Harmer
2.755
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.918
247521TR3_G114
Solar/Wind Harmer
0.261
965051AG1-369 GEN
Solar/Wind Harmer
3.6
971567AH1-282 GEN
Solar/Wind Harmer
5.517
959331AF2-224 GEN
Solar/Wind Harmer
5.044
270007AE1-245 C
Solar/Wind Harmer
0
965041AG1-368 GEN
Solar/Wind Harmer
7.193
24729505KEY G4
Adder
6.652
963791AG1-232 GEN
Solar/Wind Harmer
9.652
270071AF1-092 GEN
Solar/Wind Harmer
13.7
971985AH1-537 GEN
Solar/Wind Harmer
2.117
25196408WSDLE3
Adder
8.98
25196308WSDLE2
Adder
8.902
25196208WSDLE1
Adder
8.879
25196708WSDLE6
Adder
8.857
25196508WSDLE4
Adder
8.634
970031AG2-029 GEN
Solar/Wind Harmer
3.844
945581AF1-223 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
10.639
270543AE2-219 C
Solar/Wind Harmer
4.962
247536S-71 GEN
Solar/Wind Harmer
0.283
964611AG1-324 GEN
Solar/Wind Harmer
2.759
971609AH1-304 GEN
Solar/Wind Harmer
1.153
971771AH1-392 GEN
Solar/Wind Harmer
7.027
970289AG2-191 GEN
Solar/Wind Harmer
1.334
270526AF1-158 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.536
25196108MFTGT2
Adder
1.426
270356AE2-297 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
959141AF2-205 GEN
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
4.135
971549AH1-272 GEN
Solar/Wind Harmer
14.305
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.341
274776LINCOLN ;7U
Adder
8.341
274777LINCOLN ;8U
Adder
8.341
24386405FR-21G C
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.18
960591AF2-350 GEN
Solar/Wind Harmer
6.866
274827FISK ;RP
Adder
7.635
274800UNIV PARK;3U
Adder
5.736
274801UNIV PARK;4U
Adder
5.736
972228AH1-698 GEN2
Adder
3.644
972227AH1-698 GEN1
Adder
2.566
24318805MLG1
50/50
9.823
23559001PLEAS1
50/50
5.39
270051AF1-062 GEN
50/50
11.411
962771AG1-126 GEN
Solar/Wind Harmer
33.201
970153AG2-106 GEN
Solar/Wind Harmer
21.201
961921AG1-034 GEN
Solar/Wind Harmer
7.349
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
942051AE2-217 GEN
Solar/Wind Harmer
14.139
24721905FLATG4
Adder
22.814
270391AF1-285 GEN3
Solar/Wind Harmer
0.517
270518AE2-148 GEN
Solar/Wind Harmer
0.631
253325AC1-069 GEN
Solar/Wind Harmer
0.009
971199AH1-059 GEN
Solar/Wind Harmer
1.566
270512AE1-227 GEN2
Solar/Wind Harmer
1.899
970879AG2-548 GEN
Solar/Wind Harmer
5.401
970065AG2-057 GEN
Solar/Wind Harmer
0.734
253370AE2-315 SEC1
Adder
2.099
253371AE2-315 SEC2
Adder
1.985
970191AG2-125 GEN
Solar/Wind Harmer
1.872
253394AE2-221_GEN
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.261
270491AE1-102 GEN2
Solar/Wind Harmer
0.942
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.372
270588AE1-091_GEN
Solar/Wind Harmer
5.637
965021AG1-366 GEN
Solar/Wind Harmer
2.402
971191AH1-055 GEN
Solar/Wind Harmer
18.47
24695305TIMB G C
Solar/Wind Harmer
0.609
944531AF1-118 GEN
Solar/Wind Harmer
32.112
270043AE2-236 GEN
Solar/Wind Harmer
4.595
252519AF1-045_GEN
Solar/Wind Harmer
3.711
270367AC2-061_GEN
Solar/Wind Harmer
0
25196608WSDLE5
Adder
8.723
25194608D.CRK4
Adder
1.672
270063AE2-323 C
Solar/Wind Harmer
0
252507AC2-088 GEN
Solar/Wind Harmer
0.319
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.618
971347AH1-153 GEN
Solar/Wind Harmer
3.535
270186AC1-089 GEN
Solar/Wind Harmer
0
946031AF1-268 GEN
Solar/Wind Harmer
6.713
270004AE1-209 GEN
Solar/Wind Harmer
1.528
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
5.307
945111AF1-176 GEN
Solar/Wind Harmer
5.694
970289AG2-191 GEN
Solar/Wind Harmer
0.773
270505AE1-170 C O1
Solar/Wind Harmer
7.374
247642Z2-115 C
Solar/Wind Harmer
0.003
25196008MFTGT1
Adder
1.349
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.916
274752CRETE EC ;2U
Adder
8.15
274753CRETE EC ;3U
Adder
8.15
274772LINCOLN ;3U
Adder
8.341
274724RIVER EC ;11
Adder
17.501
958171AF2-111 GEN
Solar/Wind Harmer
17.234
274814UNIV PK N;0U
Adder
4.984
274807UNIV PK N;3U
Adder
4.973
274811UNIV PK N;7U
Adder
4.941
24386205FR-12G C
Solar/Wind Harmer
0
274803UNIV PARK;6U
Adder
5.739
274887GEN-1.85
Solar/Wind Harmer
0.178
276843GEN-1.7
Solar/Wind Harmer
0.222
276806AD2-047 C O1
Solar/Wind Harmer
3.89
274826FISK ;BP
Adder
10.773
972038AH1-567 GEN2
Adder
0.359
972167AH1-666 GEN
Solar/Wind Harmer
5.491
24728705AND G3
Adder
7.891
24728505AND G1
Adder
3.773
939351AE1-166 GEN
Solar/Wind Harmer
0
972259AH1-714 GEN
Adder
18.754
970707AG2-453 GEN
Solar/Wind Harmer
22.403
274676JOLIET 29;8U
Adder
29.018
274729ELWOOD EC;1P
Adder
16.119
274730ELWOOD EC;6P
Adder
16.119
274734ELWOOD EC;8P
Adder
16.119
274736ELWOOD EC;9P
Adder
16.119
270541AE2-072 C
Solar/Wind Harmer
0
943121AE2-341 GEN
Solar/Wind Harmer
11.428
943591AF1-030 GEN
Solar/Wind Harmer
7.6
274862TOP CROP ;2U
Solar/Wind Harmer
0.919
276868AE1-113 GEN
Solar/Wind Harmer
1.355
274879MINONK ;1U
Solar/Wind Harmer
0.283
946671AF1-331 GEN
Solar/Wind Harmer
0.719
963841AG1-237 GEN
Solar/Wind Harmer
2.97
274687WILL CNTY;4U
Adder
27.42
274687WILL CNTY;4U
Adder
27.42
972163AH1-664 GEN
Solar/Wind Harmer
7.619
972165AH1-665 GEN
Solar/Wind Harmer
6.102
274675JOLIET 29;7U
Adder
30.093
274675JOLIET 29;7U
Adder
29.018
274728ELWOOD EC;5P
Adder
16.119
274731ELWOOD EC;2P
Adder
16.119
274733ELWOOD EC;3P
Adder
16.119
274735ELWOOD EC;4P
Adder
16.119
970833AG2-524 GEN
Solar/Wind Harmer
7.521
970833AG2-524 GEN
Solar/Wind Harmer
5.014
945641AF1-229 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.262
970169AG2-114 GEN
Solar/Wind Harmer
6.772
971675AH1-338 GEN
Solar/Wind Harmer
2.63
276861AD2-134 GEN
Solar/Wind Harmer
0.12
276863AD2-134 GEN
Solar/Wind Harmer
0.12
971411AH1-196 GEN
Solar/Wind Harmer
10.113
926823AC1-168 GEN
Solar/Wind Harmer
1.145
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.07
23750701CROSSCHOOL
Solar/Wind Helper
1.401
238169AE2-226 GEN1
Solar/Wind Helper
0.681
238170AE2-226 GEN2
Solar/Wind Helper
0.681
238118U2-030_1
Solar/Wind Helper
0.315
23779801AA1-109
Solar/Wind Helper
0.188
3138216PACIFIC
Solar/Wind Helper
0.043
270119AB2-067 GEN1
50/50
6.887
270120AB2-067 GEN2
50/50
6.887
24318905MLG2
50/50
6.869
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0
942861AE2-305 GEN
Solar/Wind Harmer
6.105
938701AE1-092 GEN
Solar/Wind Harmer
12.459
971655AH1-328 GEN
Solar/Wind Harmer
2.753
270462AD2-086
Solar/Wind Harmer
0
270269AC2-059
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
1.079
970329AG2-216 GEN
Solar/Wind Harmer
3.232
970935AG2-582 GEN
Adder
241.832
25326509SID D
Adder
1.398
25326109MON D
Adder
1.388
971073AG2-665 GEN
Solar/Wind Harmer
5.401
970879AG2-548 GEN
Solar/Wind Harmer
1.228
25322209TAIT E
Adder
10.24
25322209TAIT E
Adder
10.01
253370AE2-315 SEC1
Adder
2.099
246937BC-WTG2
Solar/Wind Harmer
0.292
270246TR4_N_V150
Solar/Wind Harmer
0.046
270247TR4_N_V136
Solar/Wind Harmer
0.046
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.306
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25183208HLCRTG
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.476
960971AF2-388 GEN
Solar/Wind Harmer
4.179
942221AE2-234 GEN
Solar/Wind Harmer
2.858
970621AG2-405 GEN
Solar/Wind Harmer
1.302
25194408D.CRK1
Adder
7.692
25194508D.CRK3
Adder
1.438
970883AG2-550 GEN
Solar/Wind Harmer
7.088
970885AG2-551 GEN
Solar/Wind Harmer
2.363
237030AB1-096 C
Solar/Wind Helper
0.065
237025AB1-124 C
Solar/Wind Helper
0.16
226929AD2-058 GEN
Solar/Wind Helper
0.096
205917AD1-020 ES
Solar/Wind Helper
0.358
959381AF2-229 GEN
Solar/Wind Helper
0.346
20390526W1-045 C
Solar/Wind Helper
0.339
23750501ELLIOTTS
Solar/Wind Helper
0.573
3141426STAFORD
Solar/Wind Helper
0.051
205943AE1-185 GEN
Solar/Wind Helper
0.494
205956AE1-196_GEN
Solar/Wind Helper
0.494
233915AB1-141 GEN
Solar/Wind Helper
0.488
233901CHERRYDALE C
Solar/Wind Helper
0.226
233940AF2-379 C
Solar/Wind Helper
0.06
232432Z2-076 GEN
Solar/Wind Helper
0.065
315651AD1-115 GEN
Solar/Wind Helper
0.766
230434AG1-499 GEN
Solar/Wind Helper
0.223
228728W1-130C
Solar/Wind Helper
0.052
230407AD2-065 C
Solar/Wind Helper
0.039
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.075
219615MILLCREEK C
Solar/Wind Helper
0.026
20715028HAN_X4-015
Solar/Wind Helper
0.055
20720728JCB_W1-129
Solar/Wind Helper
0.055
207445AB1-138_GEN
Solar/Wind Helper
0.101
316164AC1-076 GEN
Solar/Wind Helper
1.068
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.184
971171AH1-044 GEN
Solar/Wind Harmer
8.748
247621Y3-024
Adder
0.245
252509AD1-136 GEN
Solar/Wind Harmer
0.035
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.531
970349AG2-230 GEN
Solar/Wind Harmer
10.604
270031AE2-169
Solar/Wind Harmer
3.884
270599AE1-208 GEN
Solar/Wind Harmer
6.473
270383AD1-128 GEN
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
16.273
247620Y3-023
Adder
0.465
926881AC1-175 GEN
Solar/Wind Harmer
0
971613AH1-306 GEN
Solar/Wind Harmer
3.374
24728805RICHG1
Adder
3.809
24728905RICHG2
Adder
3.809
970291AG2-192 GEN
Solar/Wind Harmer
0.913
970291AG2-192 GEN
Solar/Wind Harmer
0.421
961051AF2-396 GEN
Solar/Wind Harmer
14.035
961051AF2-396 GEN
Solar/Wind Harmer
9.356
965681AG1-436 GEN
Solar/Wind Harmer
8.747
965791AG1-447 GEN
Solar/Wind Harmer
6.414
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
8.341
274771LINCOLN ;2U
Adder
8.341
274805UNIV PK N;1U
Adder
4.952
274808UNIV PK N;4U
Adder
4.919
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.78
274888KELLY CRK;1U
Solar/Wind Harmer
0.4
276776AD2-060 GEN
Solar/Wind Harmer
0.732
958011AF2-095 GEN
Solar/Wind Harmer
9.886
970941AG2-585 GEN
Solar/Wind Harmer
3.776
276897AD1-100 C
Solar/Wind Harmer
17.145
276893AG1-478 C
Solar/Wind Harmer
0.456
970241AG2-163 GEN
Solar/Wind Harmer
3.982
958481AF2-142 GEN
Solar/Wind Harmer
10.21
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
10.177
962691AG1-118 GEN
Solar/Wind Harmer
20.32
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
7.158
942111AE2-223 GEN
Solar/Wind Harmer
2.188
316097T157 G90
Solar/Wind Helper
1.459
238147AE2-230_GEN1
Solar/Wind Helper
0.481
238148AE2-230_GEN2
Solar/Wind Helper
0.481
238149AF1-291A_GEN
Solar/Wind Helper
0.137
235020AA1-095 C
Solar/Wind Helper
0.051
235531U2-073 GEN
Solar/Wind Helper
3.071
235054AD2-180 GEN
Solar/Wind Helper
1.845
237061AD1-155 GEN
Solar/Wind Helper
1.703
238117U2-030
Solar/Wind Helper
0.315
238221AF1-254 C O1
Solar/Wind Helper
0.267
237080AD1-060 GEN
Solar/Wind Helper
0.332
23585401KL_K28_T16
Solar/Wind Helper
1.332
235062AE1-101 C1
Solar/Wind Helper
1.608
316411AF1-147_GEN1
Solar/Wind Helper
0.865
237006AB1-125 GEN
Solar/Wind Helper
0.12
223401AF1-299 GEN
Solar/Wind Helper
0.357
223402AF1-300 C
Solar/Wind Helper
0.357
316006AB2-029 C
Solar/Wind Helper
0.114
23751201ROTHROCK
Solar/Wind Helper
0.696
233982AB2-133 GEN
Solar/Wind Helper
0.349
233930AB2-032 GEN
Solar/Wind Helper
0.37
232424Y1-079 C
Solar/Wind Helper
0.113
232436AB1-176 C
Solar/Wind Helper
0.043
233946AB2-136 GEN
Solar/Wind Helper
0.553
234036AF2-325 C
Solar/Wind Helper
0.041
233994AC2-023 GEN
Solar/Wind Helper
0.934
232410W1-006 C
Solar/Wind Helper
0.493
232428Y3-058 C
Solar/Wind Helper
0.329
234015AF2-250 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.226
233954AC2-188 GEN
Solar/Wind Helper
0.226
316045AC1-158 PL2
Solar/Wind Helper
4.03
316450AC1-158 RIC
Solar/Wind Helper
0.336
230511AF1-262
Solar/Wind Helper
0.014
230433AD2-135 GEN
Solar/Wind Helper
0.017
228754AB1-001 C
Solar/Wind Helper
0.025
219904AC1-010 C
Solar/Wind Helper
0.059
219912AD2-042 GEN
Solar/Wind Helper
0.146
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219906AC1-017 C
Solar/Wind Helper
0.041
219607WPEMNERT C
Solar/Wind Helper
0.078
219304NAMERICA C
Solar/Wind Helper
0.127
214067T20SOLAR
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.061
207459AE1-142 C O1
Solar/Wind Helper
0.282
20714828MDF_W3-079
Solar/Wind Helper
0.127
20742028HF_AC1-207
Solar/Wind Helper
0.137
218438BLK ROCK C
Solar/Wind Helper
0.026
971341AH1-150 GEN
Solar/Wind Harmer
8.748
971343AH1-151 GEN
Solar/Wind Harmer
8.748
274855GSG-6 ;RU
Solar/Wind Harmer
0.246
274850MENDOTA H;RU
Solar/Wind Harmer
0.078
970193AG2-126 GEN
Solar/Wind Harmer
10.106
970571AG2-364 GEN
Solar/Wind Harmer
13.468
964991AG1-363 GEN
Solar/Wind Helper
4.979
238108AE1-109 GEN1
Solar/Wind Helper
0.107
238110AE1-109 GEN3
Solar/Wind Helper
0.107
238175AF1-290_GEN
Solar/Wind Helper
0.152
238152AF2-075_GEN
Solar/Wind Helper
0.687
23777901MDS_W4-102
Solar/Wind Helper
0.172
238127S14_GEN_2
Solar/Wind Helper
0.769
235063AE1-101 C2
Solar/Wind Helper
1.608
237001AB1-127_GEN
Solar/Wind Helper
0.428
316415AF1-147_GEN2
Solar/Wind Helper
0.865
237048AF1-022 C
Solar/Wind Helper
0.164
23562501BACKB
Solar/Wind Helper
0.845
205916AD1-020 GEN
Solar/Wind Helper
1.664
208835TUHI V3-051
Solar/Wind Helper
0.021
205932AD2-116_GEN
Solar/Wind Helper
0.494
233918AB1-142 GEN
Solar/Wind Helper
0.488
233944AB2-135 GEN
Solar/Wind Helper
0.573
232426Y1-080 FULL
Solar/Wind Helper
0.038
233996TM1833_GEN
Solar/Wind Helper
0.199
233998TM1NIN_3.36
Solar/Wind Helper
0.199
232404W1-003 C
Solar/Wind Helper
0.493
232408W1-005 C
Solar/Wind Helper
0.493
316447AC1-158 HLD
Solar/Wind Helper
2.771
316044AC1-158 PL1
Solar/Wind Helper
1.259
228729W2-030 C
Solar/Wind Helper
0.107
219766PARADISE C
Solar/Wind Helper
0.053
219907AC1-030 C
Solar/Wind Helper
0.033
219686LUMSOLAR_N C
Solar/Wind Helper
0.039
219348LDSOLAR C
Solar/Wind Helper
0.111
203975AE1-071-GEN
Solar/Wind Helper
2.421
20716028EGP_W2-019
Solar/Wind Helper
0.018
20715828PEM_W1-120
Solar/Wind Helper
0.093
219276PARKLANDSO C
Solar/Wind Helper
0.087
963711AG1-223 GEN
Solar/Wind Helper
0.062
20714528FRN_Y2-051
Solar/Wind Helper
0.055
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.076
20720528MAN_W1-024
Solar/Wind Helper
0.027
959091AF2-200 GEN
Solar/Wind Harmer
8.748
270166AC1-044 GEN3
50/50
6.887
23559101PLEAS2
50/50
5.39
270122AB2-093 CT
50/50
3.675
962761AG1-125 GEN
Solar/Wind Harmer
33.201
970149AG2-104 GEN
Solar/Wind Harmer
17.929
970155AG2-107 GEN
Solar/Wind Harmer
21.201
270520AE2-214 GEN
Solar/Wind Harmer
0
253333AC1-068 GEN
Solar/Wind Harmer
0.009
270317AD1-130_GEN
Solar/Wind Harmer
0
971995AH1-542 GEN
Solar/Wind Harmer
2.804
270273AD2-016 GEN
Solar/Wind Harmer
0.78
972269AH1-719 GEN
Adder
2.495
270510AE1-227 GEN1
Solar/Wind Harmer
1.899
971073AG2-665 GEN
Solar/Wind Harmer
1.228
241813AF1-122_GEN
Solar/Wind Harmer
3.287
971201AH1-060 GEN
Solar/Wind Harmer
1.467
25326309TAIT D
Adder
1.151
253370AE2-315 SEC1
Adder
2.099
253371AE2-315 SEC2
Adder
1.985
253398AE2-221_GEN2
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.292
270489AE1-102 GEN1
Solar/Wind Harmer
0.942
965421AG1-410 GEN
Solar/Wind Harmer
21.735
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.209
965011AG1-365 GEN
Solar/Wind Harmer
7.206
960001AF2-291 GEN
Solar/Wind Harmer
0
965651AG1-433 GEN
Solar/Wind Harmer
2.09
958861AF2-177 GEN
Solar/Wind Harmer
3.083
252516AE2-318_GEN
Solar/Wind Harmer
7.967
270024AE2-089 GEN
Solar/Wind Harmer
0.001
252510AF1-249 C
Solar/Wind Harmer
0.054
25194608D.CRK4
Adder
1.672
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.528
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.168
24639705ELKHART HY
Adder
0.155
25196808ZIMRHP
Adder
76.605
970825AG2-519 GEN
Solar/Wind Harmer
2.501
270594AE1-207 GEN
Solar/Wind Harmer
7.872
270032AE2-172
Solar/Wind Harmer
4.686
945111AF1-176 GEN
Solar/Wind Harmer
12.534
957891AF2-083 GEN
Solar/Wind Harmer
11.704
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.661
276903AD2-071 C
Solar/Wind Harmer
7.818
25196008MFTGT1
Adder
1.393
970773AG2-487 GEN
Solar/Wind Harmer
1.233
970373AG2-245 GEN
Solar/Wind Harmer
14.656
270055AF2-134 C O1
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.046
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.682
274751CRETE EC ;1U
Adder
8.15
274754CRETE EC ;4U
Adder
8.15
274773LINCOLN ;4U
Adder
8.341
274774LINCOLN ;5U
Adder
8.341
274723RIVER EC ;12
Adder
17.708
274812UNIV PK N;8U
Adder
4.941
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
274802UNIV PARK;5U
Adder
5.739
24728605AND G2
Adder
3.773
945681AF1-233 GEN
Solar/Wind Harmer
12.929
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
30.093
274732ELWOOD EC;7P
Adder
16.119
274674JOLIET 9 ;6U
Adder
4.855
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
16.157
939401AE1-172 GEN
Solar/Wind Harmer
5.095
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.106
274861TOP CROP ;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.791
971997AH1-543 GEN
Solar/Wind Harmer
3.554
962781AG1-127 GEN
Solar/Wind Harmer
6.441
274872LEEDK;1U
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
20.202
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.427
316095T157 G97
Solar/Wind Helper
1.459
23583801GRNGAP
Solar/Wind Helper
5.433
238109AE1-109 GEN2
Solar/Wind Helper
0.107
238185AF2-356 C
Solar/Wind Helper
2.442
238120AE2-309 GEN
Solar/Wind Helper
0.491
23546401DTGZ2-030
Solar/Wind Helper
0.086
238126S14_GEN_1
Solar/Wind Helper
0.769
237038AE2-054 C
Solar/Wind Helper
0.264
235067AD1-061 GEN
Solar/Wind Helper
0.432
237085AD2-009_GEN
Solar/Wind Helper
1.596
237002AB1-128_GEN
Solar/Wind Helper
0.43
23777801MSM_W1-116
Solar/Wind Helper
0.111
3141196NOKESVL
Solar/Wind Helper
1.002
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.337
208835TUHI V3-051
Solar/Wind Helper
0.021
233935AB2-179 C
Solar/Wind Helper
1.233
233987AB2-037 GEN
Solar/Wind Helper
2.277
233933AB2-153 GEN
Solar/Wind Helper
0.226
232422X3-066 FULL
Solar/Wind Helper
0.111
232417X3-008 C
Solar/Wind Helper
0.226
233964AF2-378 GEN
Solar/Wind Helper
0.041
233923SMA
Solar/Wind Helper
0.731
233997TMININ_4.2
Solar/Wind Helper
0.199
232406W1-004 FULL
Solar/Wind Helper
0.493
233950AC2-186 GEN
Solar/Wind Helper
0.113
232434Z2-077 GEN
Solar/Wind Helper
0.123
230415AB2-049 C
Solar/Wind Helper
0.029
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.05
219914AD2-027 C
Solar/Wind Helper
0.111
219291REEVESSOUT C
Solar/Wind Helper
0.011
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.039
959561AF2-247 GEN
Solar/Wind Helper
0.02
20715728PEM_W1-119
Solar/Wind Helper
0.093
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.301
219612MATRIX C
Solar/Wind Helper
0.023
205941AD2-115 GEN
Solar/Wind Helper
0.481
20716928W4-060COL
Solar/Wind Helper
0.05
957471AF2-041 GEN
Solar/Wind Harmer
13.123
959081AF2-199 GEN
Solar/Wind Harmer
4.374
971067AG2-660 GEN
Solar/Wind Harmer
1.458
CPLELTFEXP_CPLE->PJM
CLTF
0.539
CBM West 2LTFEXP_CBM-W2->PJM
CBM
108.215
NYPJM->LTFIMP_NY
CLTF
4.644
LGEELTFEXP_LGEE->PJM
CLTF
6.478
WECLTFEXP_WEC->PJM
CLTF
3.676
AG2-052LTFEXP_AG2-052->PJM
LTF
0.23
AH1-155LTFEXP_AH1-155->PJM
LTF
0.345
LAGNLTFEXP_LAGN->PJM
CLTF
14.214
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.353
TVALTFEXP_TVA->PJM
CLTF
6.984
CBM West 1LTFEXP_CBM-W1->PJM
CBM
137.595
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.883
MECLTFEXP_MEC->PJM
CLTF
15.273
SIGELTFEXP_SIGE->PJM
CLTF
0.485

Details for 05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer l/o AEP_P4_#8975_05KAMMER 765_MM2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer
Contingency Name:
AEP_P4_#8975_05KAMMER 765_MM2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.35 %
Rating:4000.0 MVA
Rating Type:B
MVA to Mitigate:4053.82
MW Contribution:
23.73
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
5.522
24289405MTG1
50/50
6.078
243186AF1-051 GEN
50/50
6.83
962761AG1-125 GEN
Solar/Wind Harmer
38.42
970149AG2-104 GEN
Solar/Wind Harmer
23.725
970155AG2-107 GEN
Solar/Wind Harmer
16.753
972203AH1-686 GEN
Adder
2.528
24723205RIVRG3
Adder
20.281
24686505CER G6
Adder
8.903
960001AF2-291 GEN
Solar/Wind Harmer
3.193
270331AC1-082 GEN3
Solar/Wind Harmer
0.502
270286AF1-227 GEN2
Solar/Wind Harmer
2.151
270520AE2-214 GEN
Solar/Wind Harmer
6.107
270273AD2-016 GEN
Solar/Wind Harmer
2.677
971073AG2-665 GEN
Solar/Wind Harmer
1.164
253333AC1-068 GEN
Solar/Wind Harmer
1.043
253316AC1-085 GEN3
Solar/Wind Harmer
8.322
946171AF1-282 GEN
Solar/Wind Harmer
9.94
253398AE2-221_GEN2
Solar/Wind Harmer
4.505
252516AE2-318_GEN
Solar/Wind Harmer
9.922
252510AF1-249 C
Solar/Wind Harmer
0.413
971985AH1-537 GEN
Solar/Wind Harmer
18.214
270263AC1-001 GEN
Solar/Wind Harmer
1.051
943861AF1-054 GEN
Solar/Wind Harmer
3.868
943851AF1-053 GEN
Solar/Wind Harmer
1.869
270340AC2-060 GEN
Solar/Wind Harmer
3.034
270432AC2-029 GEN
Solar/Wind Harmer
7.024
241955AC1-078 GEN
Solar/Wind Harmer
7.462
241973AD2-163_GEN1
Solar/Wind Harmer
1.984
241974AD2-163_GEN2
Solar/Wind Harmer
1.984
253338AC1-165 GEN
Solar/Wind Harmer
1.081
253343AC1-166 GEN
Solar/Wind Harmer
1.081
945631AF1-228 GEN
Solar/Wind Harmer
4.679
253406AD2-031_GEN
Solar/Wind Harmer
1.273
241972AD1-140 GEN
Solar/Wind Harmer
4.45
253433AC1-085 GEN1
Solar/Wind Harmer
5.282
253432AC1-085 GEN2
Solar/Wind Harmer
0.266
270459AD2-067 GEN
Solar/Wind Harmer
8.295
961821AG1-024 GEN
Solar/Wind Harmer
8.422
253372AE2-315 SEC3
Adder
1.876
253372AE2-315 SEC3
Adder
1.876
25196408WSDLE3
Adder
8.732
25196308WSDLE2
Adder
8.656
25196208WSDLE1
Adder
8.634
25196708WSDLE6
Adder
8.613
25196508WSDLE4
Adder
8.396
25306009OHH W.
Adder
2.85
270223U2-072_GEN1
Solar/Wind Harmer
1.952
270224U2-072_GEN2
Solar/Wind Harmer
1.952
270227U2-072_GEN3
Solar/Wind Harmer
1.952
270228U2-072_GEN4
Solar/Wind Harmer
1.952
270231U2-072_GEN5
Solar/Wind Harmer
1.952
270578AF1-285 GEN2
Solar/Wind Harmer
0.46
270291AC1-194 GEN
Solar/Wind Harmer
5.023
25196108MFTGT2
Adder
1.507
25196108MFTGT2
Adder
1.399
24729505KEY G4
Adder
6.352
958711AF2-162 GEN
Solar/Wind Harmer
0.989
945581AF1-223 GEN
Solar/Wind Harmer
4.431
971029AG2-637 GEN
Solar/Wind Harmer
14.654
270071AF1-092 GEN
Solar/Wind Harmer
14.639
270543AE2-219 C
Solar/Wind Harmer
9.759
270302AB2-170 GEN
Solar/Wind Harmer
8.168
247536S-71 GEN
Solar/Wind Harmer
3.945
972163AH1-664 GEN
Solar/Wind Harmer
9.749
972165AH1-665 GEN
Solar/Wind Harmer
7.799
970289AG2-191 GEN
Solar/Wind Harmer
1.852
964611AG1-324 GEN
Solar/Wind Harmer
3.798
270356AE2-297 GEN
Solar/Wind Harmer
4.491
961761AG1-017 GEN
Solar/Wind Harmer
0.417
957241AF2-018 GEN
Solar/Wind Harmer
4.296
270053AF1-130 C
Solar/Wind Harmer
17.164
963791AG1-232 GEN
Solar/Wind Harmer
13.051
946581AF1-322 GEN
Solar/Wind Harmer
9.871
270119AB2-067 GEN1
50/50
5.522
270120AB2-067 GEN2
50/50
5.522
243186AF1-051 GEN
50/50
6.83
24318905MLG2
50/50
4.385
24723005RIVRG1
Adder
20.281
24723105RIVRG2
Adder
20.281
270349AD2-093_GEN
Solar/Wind Harmer
3.829
270471AD2-092_GEN
Solar/Wind Harmer
3.829
927014AC1-188 GEN
Solar/Wind Harmer
1.622
946101AF1-275 GEN
Solar/Wind Harmer
1.527
253383AE2-342_GEN
Solar/Wind Harmer
0.892
270269AC2-059
Solar/Wind Harmer
9.392
942861AE2-305 GEN
Solar/Wind Harmer
7.837
253415AE1-040 GEN
Solar/Wind Harmer
1.128
962581AG1-107 GEN
Solar/Wind Harmer
5.045
961491AF2-440 GEN
Solar/Wind Harmer
2.097
971073AG2-665 GEN
Solar/Wind Harmer
8.007
970879AG2-548 GEN
Solar/Wind Harmer
1.164
252509AD1-136 GEN
Solar/Wind Harmer
0.254
25183208HLCRTG
Solar/Wind Harmer
6.007
253370AE2-315 SEC1
Adder
1.983
25194408D.CRK1
Adder
7.485
25194508D.CRK3
Adder
1.399
25326109MON D
Adder
1.301
25322209TAIT E
Adder
9.645
25322209TAIT E
Adder
9.428
253349AC2-067 GEN
Solar/Wind Harmer
2.007
253400AC2-068 GEN
Solar/Wind Harmer
0.807
270054AF2-122 C O1
Solar/Wind Harmer
3.197
944541AF1-119 GEN
Solar/Wind Harmer
4.095
960971AF2-388 GEN
Solar/Wind Harmer
10.691
253378AE2-206_GEN
Solar/Wind Harmer
3.513
926881AC1-175 GEN
Solar/Wind Harmer
5.454
270383AD1-128 GEN
Solar/Wind Harmer
5.961
24728805RICHG1
Adder
3.69
24728905RICHG2
Adder
3.69
970883AG2-550 GEN
Solar/Wind Harmer
9.759
970885AG2-551 GEN
Solar/Wind Harmer
2.269
270462AD2-086
Solar/Wind Harmer
6.784
970291AG2-192 GEN
Solar/Wind Harmer
1.267
25326509SID D
Adder
1.282
970291AG2-192 GEN
Solar/Wind Harmer
0.408
247621Y3-024
Adder
0.235
270031AE2-169
Solar/Wind Harmer
7.939
270599AE1-208 GEN
Solar/Wind Harmer
7.939
964611AG1-324 GEN
Solar/Wind Harmer
0.51
270201AC2-176 GEN
Solar/Wind Harmer
5.005
24691005MDL-2G C
Solar/Wind Harmer
3.567
959331AF2-224 GEN
Solar/Wind Harmer
9.647
959141AF2-205 GEN
Solar/Wind Harmer
5.832
958391AF2-133 GEN
Solar/Wind Harmer
8.746
274775LINCOLN ;6U
Adder
8.061
274776LINCOLN ;7U
Adder
8.061
274777LINCOLN ;8U
Adder
8.061
972228AH1-698 GEN2
Adder
3.526
972227AH1-698 GEN1
Adder
2.483
972037AH1-567 GEN1
Adder
0.174
274827FISK ;RP
Adder
7.384
274800UNIV PARK;3U
Adder
5.548
274801UNIV PARK;4U
Adder
5.548
274687WILL CNTY;4U
Adder
26.551
274687WILL CNTY;4U
Adder
26.551
274728ELWOOD EC;5P
Adder
15.615
274731ELWOOD EC;2P
Adder
15.615
274733ELWOOD EC;3P
Adder
15.615
274735ELWOOD EC;4P
Adder
15.615
274675JOLIET 29;7U
Adder
29.146
274675JOLIET 29;7U
Adder
28.105
274744AC1-111 GEN8
Adder
5.296
274746AC1-111 G10
Adder
5.296
23750701CROSSCHOOL
Solar/Wind Helper
1.294
24725505WLD G2 C
Solar/Wind Harmer
3.868
24699105WLD G1 C
Solar/Wind Harmer
3.822
942221AE2-234 GEN
Solar/Wind Harmer
3.403
970349AG2-230 GEN
Solar/Wind Harmer
14.508
945421AF1-207 GEN
Solar/Wind Harmer
13.563
957841AF2-078 GEN
Solar/Wind Harmer
5.839
270180AB1-006 GEN1
Solar/Wind Harmer
6.938
24697605MDL-3G C
Solar/Wind Harmer
3.556
24755605MDL-5G
Solar/Wind Harmer
2.326
24697905MDL-4G C
Solar/Wind Harmer
2.214
270181AB1-006 GEN2
Solar/Wind Harmer
0.69
247620Y3-023
Adder
0.44
274770LINCOLN ;1U
Adder
8.061
274771LINCOLN ;2U
Adder
8.061
274805UNIV PK N;1U
Adder
4.783
274808UNIV PK N;4U
Adder
4.751
274674JOLIET 9 ;6U
Adder
14.625
274696ROCKY RD ;4P
Adder
10.771
274695ROCKY RD ;2P
Adder
10.523
274693ROCKY RD ;1P
Adder
10.419
274697ROCKY RD ;3P
Adder
2.859
23751201ROTHROCK
Solar/Wind Helper
0.867
23585401KL_K28_T16
Solar/Wind Helper
1.41
235054AD2-180 GEN
Solar/Wind Helper
1.875
238117U2-030
Solar/Wind Helper
0.306
235531U2-073 GEN
Solar/Wind Helper
2.924
316097T157 G90
Solar/Wind Helper
1.19
238118U2-030_1
Solar/Wind Helper
0.306
23750501ELLIOTTS
Solar/Wind Helper
0.628
253370AE2-315 SEC1
Adder
1.983
253371AE2-315 SEC2
Adder
1.876
25194608D.CRK4
Adder
1.627
25326309TAIT D
Adder
1.084
270391AF1-285 GEN3
Solar/Wind Harmer
1.195
270578AF1-285 GEN2
Solar/Wind Harmer
1.195
25196808ZIMRHP
Adder
74.904
970091AG2-072 GEN
Adder
75.485
25196008MFTGT1
Adder
1.367
270222AC2-111 GEN
Solar/Wind Harmer
4.385
944031AF1-071 GEN
Solar/Wind Harmer
0.987
965651AG1-433 GEN
Solar/Wind Harmer
5.345
958861AF2-177 GEN
Solar/Wind Harmer
10.687
942081AE2-220 GEN
Solar/Wind Harmer
6.249
270209AC1-174_GEN
Solar/Wind Harmer
3.977
270437AC2-090 C
Solar/Wind Harmer
5.454
270239V3-007_GEN1
Solar/Wind Harmer
1.681
945371AF1-202 GEN
Solar/Wind Harmer
6.817
945681AF1-233 GEN
Solar/Wind Harmer
18.397
270317AD1-130_GEN
Solar/Wind Harmer
3.123
270485AE1-090_GEN
Solar/Wind Harmer
0.59
270005AE1-210 C O1
Solar/Wind Harmer
5.332
270594AE1-207 GEN
Solar/Wind Harmer
13.238
270032AE2-172
Solar/Wind Harmer
4.533
970825AG2-519 GEN
Solar/Wind Harmer
2.045
276903AD2-071 C
Solar/Wind Harmer
9.73
270024AE2-089 GEN
Solar/Wind Harmer
4.552
944971AF1-162 GEN
Solar/Wind Harmer
6.766
940581AE2-045 GEN
Solar/Wind Harmer
9.84
24791305MDL-5G
Solar/Wind Harmer
2.326
965011AG1-365 GEN
Solar/Wind Harmer
9.647
971605AH1-302 GEN
Solar/Wind Harmer
8.413
964861AG1-349 GEN
Solar/Wind Harmer
7.578
971917AH1-482 GEN
Solar/Wind Harmer
8.743
24728605AND G2
Adder
3.696
24639705ELKHART HY
Adder
0.147
274773LINCOLN ;4U
Adder
8.061
274774LINCOLN ;5U
Adder
8.061
274751CRETE EC ;1U
Adder
7.861
274754CRETE EC ;4U
Adder
7.861
274723RIVER EC ;12
Adder
17.091
274812UNIV PK N;8U
Adder
4.772
274802UNIV PARK;5U
Adder
5.55
274732ELWOOD EC;7P
Adder
15.615
274676JOLIET 29;8U
Adder
29.146
274674JOLIET 9 ;6U
Adder
14.625
274745AC1-111 GEN9
Adder
5.296
23751101LEADS_P59
Solar/Wind Helper
2.597
238185AF2-356 C
Solar/Wind Helper
2.387
23583801GRNGAP
Solar/Wind Helper
4.45
238120AE2-309 GEN
Solar/Wind Helper
0.461
316095T157 G97
Solar/Wind Helper
1.19
238126S14_GEN_1
Solar/Wind Helper
0.726
238109AE1-109 GEN2
Solar/Wind Helper
0.096
958381AF2-132 GEN
Solar/Wind Harmer
6.61
24318805MLG1
50/50
7.624
24289405MTG1
50/50
6.078
24721905FLATG4
Adder
26.83
962771AG1-126 GEN
Solar/Wind Harmer
38.42
970153AG2-106 GEN
Solar/Wind Harmer
16.753
24686405CER G5
Adder
8.833
270330AC1-082 GEN2
Solar/Wind Harmer
0.501
270329AC1-082 GEN1
Solar/Wind Harmer
0.501
971191AH1-055 GEN
Solar/Wind Harmer
19.621
270284AF1-227 GEN1
Solar/Wind Harmer
5.814
270287AF1-227 GEN3
Solar/Wind Harmer
2.151
957541AF2-048 GEN
Solar/Wind Harmer
1.622
270367AC2-061_GEN
Solar/Wind Harmer
3.183
970879AG2-548 GEN
Solar/Wind Harmer
8.007
942051AE2-217 GEN
Solar/Wind Harmer
18.009
253325AC1-069 GEN
Solar/Wind Harmer
1.043
270186AC1-089 GEN
Solar/Wind Harmer
6.09
270518AE2-148 GEN
Solar/Wind Harmer
12.029
253317AC1-085 GEN4
Solar/Wind Harmer
8.322
946181AF1-283 GEN
Solar/Wind Harmer
12.922
252507AC2-088 GEN
Solar/Wind Harmer
1.779
253394AE2-221_GEN
Solar/Wind Harmer
4.505
252519AF1-045_GEN
Solar/Wind Harmer
3.611
961921AG1-034 GEN
Solar/Wind Harmer
12.632
253303V4-073 C
Solar/Wind Harmer
0.115
253370AE2-315 SEC1
Adder
1.983
253371AE2-315 SEC2
Adder
1.876
25194608D.CRK4
Adder
1.627
252524AE2-267 GEN
Solar/Wind Harmer
1.558
25196608WSDLE5
Adder
8.482
942871AE2-306 GEN
Solar/Wind Harmer
0.896
270391AF1-285 GEN3
Solar/Wind Harmer
0.46
960071AF2-298 GEN
Solar/Wind Harmer
1.495
960801AF2-371 GEN
Solar/Wind Harmer
2.503
964871AG1-351 GEN
Solar/Wind Harmer
1.728
25196008MFTGT1
Adder
1.324
944531AF1-118 GEN
Solar/Wind Harmer
34.283
276820AF1-078_GEN
Solar/Wind Harmer
1.561
24379505HDWTR1G C
Solar/Wind Harmer
7.727
270240V3-007_GEN2
Solar/Wind Harmer
6.045
972167AH1-666 GEN
Solar/Wind Harmer
7.81
270004AE1-209 GEN
Solar/Wind Harmer
5.332
946031AF1-268 GEN
Solar/Wind Harmer
8.091
965461AG1-414 GEN
Solar/Wind Harmer
2.21
970289AG2-191 GEN
Solar/Wind Harmer
0.748
247642Z2-115 C
Solar/Wind Harmer
0.062
970825AG2-519 GEN
Solar/Wind Harmer
5.491
958171AF2-111 GEN
Solar/Wind Harmer
24.35
962031AG1-047 GEN
Solar/Wind Harmer
2.944
957741AF2-068 GEN
Solar/Wind Harmer
14.606
270043AE2-236 GEN
Solar/Wind Harmer
5.338
971347AH1-153 GEN
Solar/Wind Harmer
4.836
24690905MDL-1G C
Solar/Wind Harmer
7.745
970781AG2-491 GEN
Solar/Wind Harmer
9.647
965021AG1-366 GEN
Solar/Wind Harmer
2.244
24728705AND G3
Adder
7.73
24728505AND G1
Adder
3.696
274772LINCOLN ;3U
Adder
8.061
274752CRETE EC ;2U
Adder
7.861
274753CRETE EC ;3U
Adder
7.861
274724RIVER EC ;11
Adder
16.891
274814UNIV PK N;0U
Adder
4.814
274807UNIV PK N;3U
Adder
4.804
274811UNIV PK N;7U
Adder
4.772
274803UNIV PARK;6U
Adder
5.55
274826FISK ;BP
Adder
10.419
972038AH1-567 GEN2
Adder
0.347
972259AH1-714 GEN
Adder
18.154
274729ELWOOD EC;1P
Adder
15.615
274730ELWOOD EC;6P
Adder
15.615
274734ELWOOD EC;8P
Adder
15.615
274736ELWOOD EC;9P
Adder
15.615
274676JOLIET 29;8U
Adder
28.105
274682WAUKEGAN ;7U
Adder
3.428
23562501BACKB
Solar/Wind Helper
1.069
237048AF1-022 C
Solar/Wind Helper
0.182
964991AG1-363 GEN
Solar/Wind Helper
3.896
238127S14_GEN_2
Solar/Wind Helper
0.726
238108AE1-109 GEN1
Solar/Wind Helper
0.096
238110AE1-109 GEN3
Solar/Wind Helper
0.096
238175AF1-290_GEN
Solar/Wind Helper
0.12
CPLELTFEXP_CPLE->PJM
CLTF
2.151
CBM West 2LTFEXP_CBM-W2->PJM
CBM
111.961
NYPJM->LTFIMP_NY
CLTF
4.02
LGEELTFEXP_LGEE->PJM
CLTF
6.53
WECLTFEXP_WEC->PJM
CLTF
3.585
AG2-052LTFEXP_AG2-052->PJM
LTF
0.223
AH1-155LTFEXP_AH1-155->PJM
LTF
0.334
LAGNLTFEXP_LAGN->PJM
CLTF
15.27
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.297
TVALTFEXP_TVA->PJM
CLTF
7.601
CBM West 1LTFEXP_CBM-W1->PJM
CBM
131.169
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.834
MECLTFEXP_MEC->PJM
CLTF
15.181
SIGELTFEXP_SIGE->PJM
CLTF
0.488

Details for 05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer l/o AP_P2-3_WP-500-DRT10A_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer
Contingency Name:
AP_P2-3_WP-500-DRT10A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.34 %
Rating:4000.0 MVA
Rating Type:B
MVA to Mitigate:4053.72
MW Contribution:
23.74
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
5.526
24289405MTG1
50/50
6.082
243186AF1-051 GEN
50/50
6.835
962761AG1-125 GEN
Solar/Wind Harmer
38.451
970149AG2-104 GEN
Solar/Wind Harmer
23.744
970155AG2-107 GEN
Solar/Wind Harmer
16.767
972203AH1-686 GEN
Adder
2.53
24723205RIVRG3
Adder
20.295
24686505CER G6
Adder
8.909
960001AF2-291 GEN
Solar/Wind Harmer
3.196
270331AC1-082 GEN3
Solar/Wind Harmer
0.503
270286AF1-227 GEN2
Solar/Wind Harmer
2.153
270520AE2-214 GEN
Solar/Wind Harmer
6.113
270273AD2-016 GEN
Solar/Wind Harmer
2.68
971073AG2-665 GEN
Solar/Wind Harmer
1.165
253333AC1-068 GEN
Solar/Wind Harmer
1.044
253316AC1-085 GEN3
Solar/Wind Harmer
8.329
946171AF1-282 GEN
Solar/Wind Harmer
9.949
253398AE2-221_GEN2
Solar/Wind Harmer
4.509
252516AE2-318_GEN
Solar/Wind Harmer
9.931
252510AF1-249 C
Solar/Wind Harmer
0.413
253370AE2-315 SEC1
Adder
1.985
253371AE2-315 SEC2
Adder
1.878
25194608D.CRK4
Adder
1.629
25326309TAIT D
Adder
1.085
270391AF1-285 GEN3
Solar/Wind Harmer
1.197
270578AF1-285 GEN2
Solar/Wind Harmer
1.197
25196808ZIMRHP
Adder
74.969
970091AG2-072 GEN
Adder
75.547
25196008MFTGT1
Adder
1.368
270222AC2-111 GEN
Solar/Wind Harmer
4.389
944031AF1-071 GEN
Solar/Wind Harmer
0.987
965651AG1-433 GEN
Solar/Wind Harmer
5.35
958861AF2-177 GEN
Solar/Wind Harmer
10.697
945371AF1-202 GEN
Solar/Wind Harmer
6.823
942081AE2-220 GEN
Solar/Wind Harmer
6.255
270209AC1-174_GEN
Solar/Wind Harmer
3.98
270437AC2-090 C
Solar/Wind Harmer
5.459
270239V3-007_GEN1
Solar/Wind Harmer
1.683
945681AF1-233 GEN
Solar/Wind Harmer
18.412
270317AD1-130_GEN
Solar/Wind Harmer
3.126
270485AE1-090_GEN
Solar/Wind Harmer
0.591
270005AE1-210 C O1
Solar/Wind Harmer
5.336
270594AE1-207 GEN
Solar/Wind Harmer
13.25
270032AE2-172
Solar/Wind Harmer
4.538
970825AG2-519 GEN
Solar/Wind Harmer
2.047
276903AD2-071 C
Solar/Wind Harmer
9.739
270024AE2-089 GEN
Solar/Wind Harmer
4.556
944971AF1-162 GEN
Solar/Wind Harmer
6.77
965011AG1-365 GEN
Solar/Wind Harmer
9.657
940581AE2-045 GEN
Solar/Wind Harmer
9.849
24791305MDL-5G
Solar/Wind Harmer
2.328
971605AH1-302 GEN
Solar/Wind Harmer
8.421
24728605AND G2
Adder
3.699
24639705ELKHART HY
Adder
0.147
274773LINCOLN ;4U
Adder
8.068
274774LINCOLN ;5U
Adder
8.068
274751CRETE EC ;1U
Adder
7.868
274754CRETE EC ;4U
Adder
7.868
274723RIVER EC ;12
Adder
17.106
274812UNIV PK N;8U
Adder
4.777
274802UNIV PARK;5U
Adder
5.555
274732ELWOOD EC;7P
Adder
15.629
274676JOLIET 29;8U
Adder
29.172
274674JOLIET 9 ;6U
Adder
14.638
274745AC1-111 GEN9
Adder
5.301
23751101LEADS_P59
Solar/Wind Helper
2.585
238185AF2-356 C
Solar/Wind Helper
2.375
23583801GRNGAP
Solar/Wind Helper
4.46
316095T157 G97
Solar/Wind Helper
1.193
238120AE2-309 GEN
Solar/Wind Helper
0.459
238126S14_GEN_1
Solar/Wind Helper
0.723
238109AE1-109 GEN2
Solar/Wind Helper
0.095
964861AG1-349 GEN
Solar/Wind Harmer
1.402
971917AH1-482 GEN
Solar/Wind Harmer
1.617
971985AH1-537 GEN
Solar/Wind Harmer
18.229
270263AC1-001 GEN
Solar/Wind Harmer
1.052
943861AF1-054 GEN
Solar/Wind Harmer
3.872
943851AF1-053 GEN
Solar/Wind Harmer
1.871
270432AC2-029 GEN
Solar/Wind Harmer
7.031
270340AC2-060 GEN
Solar/Wind Harmer
3.037
241955AC1-078 GEN
Solar/Wind Harmer
7.469
241973AD2-163_GEN1
Solar/Wind Harmer
1.986
241974AD2-163_GEN2
Solar/Wind Harmer
1.986
253338AC1-165 GEN
Solar/Wind Harmer
1.082
253343AC1-166 GEN
Solar/Wind Harmer
1.082
945631AF1-228 GEN
Solar/Wind Harmer
4.683
253406AD2-031_GEN
Solar/Wind Harmer
1.274
241972AD1-140 GEN
Solar/Wind Harmer
4.454
253433AC1-085 GEN1
Solar/Wind Harmer
5.287
253432AC1-085 GEN2
Solar/Wind Harmer
0.266
270459AD2-067 GEN
Solar/Wind Harmer
8.304
961821AG1-024 GEN
Solar/Wind Harmer
8.431
253372AE2-315 SEC3
Adder
1.878
253372AE2-315 SEC3
Adder
1.878
25196408WSDLE3
Adder
8.74
25196308WSDLE2
Adder
8.664
25196208WSDLE1
Adder
8.642
25196708WSDLE6
Adder
8.62
25196508WSDLE4
Adder
8.403
25306009OHH W.
Adder
2.853
270223U2-072_GEN1
Solar/Wind Harmer
1.954
270224U2-072_GEN2
Solar/Wind Harmer
1.954
270227U2-072_GEN3
Solar/Wind Harmer
1.954
270228U2-072_GEN4
Solar/Wind Harmer
1.954
270231U2-072_GEN5
Solar/Wind Harmer
1.954
270578AF1-285 GEN2
Solar/Wind Harmer
0.46
270291AC1-194 GEN
Solar/Wind Harmer
5.028
25196108MFTGT2
Adder
1.508
25196108MFTGT2
Adder
1.4
24729505KEY G4
Adder
6.358
958711AF2-162 GEN
Solar/Wind Harmer
0.99
945581AF1-223 GEN
Solar/Wind Harmer
4.435
971029AG2-637 GEN
Solar/Wind Harmer
14.667
270071AF1-092 GEN
Solar/Wind Harmer
14.653
270543AE2-219 C
Solar/Wind Harmer
9.768
270302AB2-170 GEN
Solar/Wind Harmer
8.176
247536S-71 GEN
Solar/Wind Harmer
3.949
972163AH1-664 GEN
Solar/Wind Harmer
9.757
972165AH1-665 GEN
Solar/Wind Harmer
7.806
970289AG2-191 GEN
Solar/Wind Harmer
1.853
964611AG1-324 GEN
Solar/Wind Harmer
3.802
270356AE2-297 GEN
Solar/Wind Harmer
4.495
961761AG1-017 GEN
Solar/Wind Harmer
0.417
957241AF2-018 GEN
Solar/Wind Harmer
4.299
270053AF1-130 C
Solar/Wind Harmer
17.176
963791AG1-232 GEN
Solar/Wind Harmer
13.064
959331AF2-224 GEN
Solar/Wind Harmer
9.657
946581AF1-322 GEN
Solar/Wind Harmer
9.879
24691005MDL-2G C
Solar/Wind Harmer
3.57
959141AF2-205 GEN
Solar/Wind Harmer
5.837
958391AF2-133 GEN
Solar/Wind Harmer
8.754
274775LINCOLN ;6U
Adder
8.068
274776LINCOLN ;7U
Adder
8.068
274777LINCOLN ;8U
Adder
8.068
972228AH1-698 GEN2
Adder
3.529
972227AH1-698 GEN1
Adder
2.485
972037AH1-567 GEN1
Adder
0.174
274827FISK ;RP
Adder
7.39
274800UNIV PARK;3U
Adder
5.553
274801UNIV PARK;4U
Adder
5.553
274687WILL CNTY;4U
Adder
26.575
274687WILL CNTY;4U
Adder
26.575
274728ELWOOD EC;5P
Adder
15.629
274731ELWOOD EC;2P
Adder
15.629
274733ELWOOD EC;3P
Adder
15.629
274735ELWOOD EC;4P
Adder
15.629
274675JOLIET 29;7U
Adder
29.172
274675JOLIET 29;7U
Adder
28.13
274744AC1-111 GEN8
Adder
5.301
274746AC1-111 G10
Adder
5.301
23750701CROSSCHOOL
Solar/Wind Helper
1.289
238118U2-030_1
Solar/Wind Helper
0.304
23750501ELLIOTTS
Solar/Wind Helper
0.621
270119AB2-067 GEN1
50/50
5.526
270120AB2-067 GEN2
50/50
5.526
243186AF1-051 GEN
50/50
6.835
24318905MLG2
50/50
4.392
24723005RIVRG1
Adder
20.295
24723105RIVRG2
Adder
20.295
270349AD2-093_GEN
Solar/Wind Harmer
3.833
270471AD2-092_GEN
Solar/Wind Harmer
3.833
927014AC1-188 GEN
Solar/Wind Harmer
1.623
946101AF1-275 GEN
Solar/Wind Harmer
1.528
253383AE2-342_GEN
Solar/Wind Harmer
0.893
270269AC2-059
Solar/Wind Harmer
9.401
942861AE2-305 GEN
Solar/Wind Harmer
7.844
253415AE1-040 GEN
Solar/Wind Harmer
1.129
962581AG1-107 GEN
Solar/Wind Harmer
5.049
961491AF2-440 GEN
Solar/Wind Harmer
2.098
971073AG2-665 GEN
Solar/Wind Harmer
8.014
970879AG2-548 GEN
Solar/Wind Harmer
1.165
252509AD1-136 GEN
Solar/Wind Harmer
0.254
25183208HLCRTG
Solar/Wind Harmer
6.012
253370AE2-315 SEC1
Adder
1.985
25194408D.CRK1
Adder
7.492
25194508D.CRK3
Adder
1.401
25326109MON D
Adder
1.302
25322209TAIT E
Adder
9.654
25322209TAIT E
Adder
9.437
253349AC2-067 GEN
Solar/Wind Harmer
2.009
253400AC2-068 GEN
Solar/Wind Harmer
0.808
270054AF2-122 C O1
Solar/Wind Harmer
3.201
944541AF1-119 GEN
Solar/Wind Harmer
4.099
960971AF2-388 GEN
Solar/Wind Harmer
10.701
253378AE2-206_GEN
Solar/Wind Harmer
3.516
926881AC1-175 GEN
Solar/Wind Harmer
5.459
270383AD1-128 GEN
Solar/Wind Harmer
5.966
24728805RICHG1
Adder
3.693
24728905RICHG2
Adder
3.693
970883AG2-550 GEN
Solar/Wind Harmer
9.768
970885AG2-551 GEN
Solar/Wind Harmer
2.272
270462AD2-086
Solar/Wind Harmer
6.791
25326509SID D
Adder
1.283
970291AG2-192 GEN
Solar/Wind Harmer
1.268
970291AG2-192 GEN
Solar/Wind Harmer
0.408
247621Y3-024
Adder
0.235
270031AE2-169
Solar/Wind Harmer
7.946
270599AE1-208 GEN
Solar/Wind Harmer
7.946
964611AG1-324 GEN
Solar/Wind Harmer
0.51
270201AC2-176 GEN
Solar/Wind Harmer
5.009
24725505WLD G2 C
Solar/Wind Harmer
3.871
24699105WLD G1 C
Solar/Wind Harmer
3.826
942221AE2-234 GEN
Solar/Wind Harmer
3.406
970349AG2-230 GEN
Solar/Wind Harmer
14.521
945421AF1-207 GEN
Solar/Wind Harmer
13.575
957841AF2-078 GEN
Solar/Wind Harmer
5.844
270180AB1-006 GEN1
Solar/Wind Harmer
6.944
24697605MDL-3G C
Solar/Wind Harmer
3.559
24755605MDL-5G
Solar/Wind Harmer
2.328
24697905MDL-4G C
Solar/Wind Harmer
2.216
270181AB1-006 GEN2
Solar/Wind Harmer
0.69
938701AE1-092 GEN
Solar/Wind Harmer
19.934
247620Y3-023
Adder
0.441
274770LINCOLN ;1U
Adder
8.068
274771LINCOLN ;2U
Adder
8.068
274805UNIV PK N;1U
Adder
4.787
274808UNIV PK N;4U
Adder
4.756
274674JOLIET 9 ;6U
Adder
14.638
274695ROCKY RD ;2P
Adder
10.532
274693ROCKY RD ;1P
Adder
10.429
274697ROCKY RD ;3P
Adder
2.861
274696ROCKY RD ;4P
Adder
10.781
23751201ROTHROCK
Solar/Wind Helper
0.861
23585401KL_K28_T16
Solar/Wind Helper
1.4
235054AD2-180 GEN
Solar/Wind Helper
1.865
238117U2-030
Solar/Wind Helper
0.304
316097T157 G90
Solar/Wind Helper
1.193
235531U2-073 GEN
Solar/Wind Helper
2.906
24318805MLG1
50/50
7.629
24289405MTG1
50/50
6.082
24721905FLATG4
Adder
26.847
962771AG1-126 GEN
Solar/Wind Harmer
38.451
970153AG2-106 GEN
Solar/Wind Harmer
16.767
24686405CER G5
Adder
8.839
270330AC1-082 GEN2
Solar/Wind Harmer
0.501
270329AC1-082 GEN1
Solar/Wind Harmer
0.501
971191AH1-055 GEN
Solar/Wind Harmer
19.637
270284AF1-227 GEN1
Solar/Wind Harmer
5.82
270287AF1-227 GEN3
Solar/Wind Harmer
2.153
957541AF2-048 GEN
Solar/Wind Harmer
1.623
270367AC2-061_GEN
Solar/Wind Harmer
3.185
970879AG2-548 GEN
Solar/Wind Harmer
8.014
942051AE2-217 GEN
Solar/Wind Harmer
18.027
253325AC1-069 GEN
Solar/Wind Harmer
1.044
270186AC1-089 GEN
Solar/Wind Harmer
6.095
270518AE2-148 GEN
Solar/Wind Harmer
12.041
253317AC1-085 GEN4
Solar/Wind Harmer
8.329
946181AF1-283 GEN
Solar/Wind Harmer
12.933
252507AC2-088 GEN
Solar/Wind Harmer
1.781
253394AE2-221_GEN
Solar/Wind Harmer
4.509
252519AF1-045_GEN
Solar/Wind Harmer
3.614
961921AG1-034 GEN
Solar/Wind Harmer
12.646
253303V4-073 C
Solar/Wind Harmer
0.115
253370AE2-315 SEC1
Adder
1.985
253371AE2-315 SEC2
Adder
1.878
25194608D.CRK4
Adder
1.629
252524AE2-267 GEN
Solar/Wind Harmer
1.56
25196608WSDLE5
Adder
8.49
942871AE2-306 GEN
Solar/Wind Harmer
0.897
270391AF1-285 GEN3
Solar/Wind Harmer
0.46
960071AF2-298 GEN
Solar/Wind Harmer
1.496
960801AF2-371 GEN
Solar/Wind Harmer
2.506
964871AG1-351 GEN
Solar/Wind Harmer
1.73
25196008MFTGT1
Adder
1.325
944531AF1-118 GEN
Solar/Wind Harmer
34.314
276820AF1-078_GEN
Solar/Wind Harmer
1.562
24379505HDWTR1G C
Solar/Wind Harmer
7.734
270240V3-007_GEN2
Solar/Wind Harmer
6.051
972167AH1-666 GEN
Solar/Wind Harmer
7.816
270004AE1-209 GEN
Solar/Wind Harmer
5.336
946031AF1-268 GEN
Solar/Wind Harmer
8.098
965461AG1-414 GEN
Solar/Wind Harmer
2.212
970289AG2-191 GEN
Solar/Wind Harmer
0.749
247642Z2-115 C
Solar/Wind Harmer
0.062
970825AG2-519 GEN
Solar/Wind Harmer
5.495
958171AF2-111 GEN
Solar/Wind Harmer
24.37
962031AG1-047 GEN
Solar/Wind Harmer
2.947
957741AF2-068 GEN
Solar/Wind Harmer
14.62
270043AE2-236 GEN
Solar/Wind Harmer
5.343
971347AH1-153 GEN
Solar/Wind Harmer
4.84
965021AG1-366 GEN
Solar/Wind Harmer
2.246
24690905MDL-1G C
Solar/Wind Harmer
7.751
970781AG2-491 GEN
Solar/Wind Harmer
9.656
24728705AND G3
Adder
7.736
24728505AND G1
Adder
3.699
274772LINCOLN ;3U
Adder
8.068
274752CRETE EC ;2U
Adder
7.868
274753CRETE EC ;3U
Adder
7.868
274724RIVER EC ;11
Adder
16.907
274814UNIV PK N;0U
Adder
4.818
274807UNIV PK N;3U
Adder
4.808
274811UNIV PK N;7U
Adder
4.777
274803UNIV PARK;6U
Adder
5.555
274826FISK ;BP
Adder
10.428
972038AH1-567 GEN2
Adder
0.348
972259AH1-714 GEN
Adder
18.171
274729ELWOOD EC;1P
Adder
15.629
274730ELWOOD EC;6P
Adder
15.629
274734ELWOOD EC;8P
Adder
15.629
274736ELWOOD EC;9P
Adder
15.629
274676JOLIET 29;8U
Adder
28.13
274682WAUKEGAN ;7U
Adder
3.431
23562501BACKB
Solar/Wind Helper
1.061
964991AG1-363 GEN
Solar/Wind Helper
3.902
237048AF1-022 C
Solar/Wind Helper
0.177
238127S14_GEN_2
Solar/Wind Helper
0.723
238108AE1-109 GEN1
Solar/Wind Helper
0.095
238110AE1-109 GEN3
Solar/Wind Helper
0.095
238175AF1-290_GEN
Solar/Wind Helper
0.12
CPLELTFEXP_CPLE->PJM
CLTF
2.146
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.043
NYPJM->LTFIMP_NY
CLTF
4.022
LGEELTFEXP_LGEE->PJM
CLTF
6.535
WECLTFEXP_WEC->PJM
CLTF
3.588
AG2-052LTFEXP_AG2-052->PJM
LTF
0.223
AH1-155LTFEXP_AH1-155->PJM
LTF
0.334
LAGNLTFEXP_LAGN->PJM
CLTF
15.279
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.293
TVALTFEXP_TVA->PJM
CLTF
7.605
CBM West 1LTFEXP_CBM-W1->PJM
CBM
131.297
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.853
MECLTFEXP_MEC->PJM
CLTF
15.194
SIGELTFEXP_SIGE->PJM
CLTF
0.488

Details for 05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer l/o AP_P2-3_WP-500-DRT7A_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer
Contingency Name:
AP_P2-3_WP-500-DRT7A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.32 %
Rating:4000.0 MVA
Rating Type:B
MVA to Mitigate:4052.99
MW Contribution:
23.73
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
5.522
24289405MTG1
50/50
6.078
243186AF1-051 GEN
50/50
6.83
962761AG1-125 GEN
Solar/Wind Harmer
38.42
970149AG2-104 GEN
Solar/Wind Harmer
23.725
970155AG2-107 GEN
Solar/Wind Harmer
16.753
972203AH1-686 GEN
Adder
2.528
24723205RIVRG3
Adder
20.281
24686505CER G6
Adder
8.903
960001AF2-291 GEN
Solar/Wind Harmer
3.193
270331AC1-082 GEN3
Solar/Wind Harmer
0.502
270286AF1-227 GEN2
Solar/Wind Harmer
2.151
270520AE2-214 GEN
Solar/Wind Harmer
6.107
270273AD2-016 GEN
Solar/Wind Harmer
2.677
971073AG2-665 GEN
Solar/Wind Harmer
1.164
253333AC1-068 GEN
Solar/Wind Harmer
1.043
253316AC1-085 GEN3
Solar/Wind Harmer
8.322
946171AF1-282 GEN
Solar/Wind Harmer
9.94
253398AE2-221_GEN2
Solar/Wind Harmer
4.505
252516AE2-318_GEN
Solar/Wind Harmer
9.922
971985AH1-537 GEN
Solar/Wind Harmer
18.214
270263AC1-001 GEN
Solar/Wind Harmer
1.051
943861AF1-054 GEN
Solar/Wind Harmer
3.868
943851AF1-053 GEN
Solar/Wind Harmer
1.869
270340AC2-060 GEN
Solar/Wind Harmer
3.034
270432AC2-029 GEN
Solar/Wind Harmer
7.024
241955AC1-078 GEN
Solar/Wind Harmer
7.462
241973AD2-163_GEN1
Solar/Wind Harmer
1.984
241974AD2-163_GEN2
Solar/Wind Harmer
1.984
253338AC1-165 GEN
Solar/Wind Harmer
1.081
253343AC1-166 GEN
Solar/Wind Harmer
1.081
945631AF1-228 GEN
Solar/Wind Harmer
4.679
253406AD2-031_GEN
Solar/Wind Harmer
1.273
241972AD1-140 GEN
Solar/Wind Harmer
4.45
253433AC1-085 GEN1
Solar/Wind Harmer
5.282
253432AC1-085 GEN2
Solar/Wind Harmer
0.266
270459AD2-067 GEN
Solar/Wind Harmer
8.295
961821AG1-024 GEN
Solar/Wind Harmer
8.422
253372AE2-315 SEC3
Adder
1.876
253372AE2-315 SEC3
Adder
1.876
25196408WSDLE3
Adder
8.732
25196308WSDLE2
Adder
8.656
25196208WSDLE1
Adder
8.634
25196708WSDLE6
Adder
8.613
25196508WSDLE4
Adder
8.396
25306009OHH W.
Adder
2.85
270223U2-072_GEN1
Solar/Wind Harmer
1.952
270224U2-072_GEN2
Solar/Wind Harmer
1.952
270227U2-072_GEN3
Solar/Wind Harmer
1.952
270228U2-072_GEN4
Solar/Wind Harmer
1.952
270231U2-072_GEN5
Solar/Wind Harmer
1.952
270578AF1-285 GEN2
Solar/Wind Harmer
0.46
270291AC1-194 GEN
Solar/Wind Harmer
5.023
25196108MFTGT2
Adder
1.507
25196108MFTGT2
Adder
1.399
24729505KEY G4
Adder
6.352
958711AF2-162 GEN
Solar/Wind Harmer
0.989
945581AF1-223 GEN
Solar/Wind Harmer
4.431
971029AG2-637 GEN
Solar/Wind Harmer
14.654
270071AF1-092 GEN
Solar/Wind Harmer
14.639
270543AE2-219 C
Solar/Wind Harmer
9.759
270302AB2-170 GEN
Solar/Wind Harmer
8.168
247536S-71 GEN
Solar/Wind Harmer
3.945
972163AH1-664 GEN
Solar/Wind Harmer
9.749
972165AH1-665 GEN
Solar/Wind Harmer
7.799
970289AG2-191 GEN
Solar/Wind Harmer
1.852
964611AG1-324 GEN
Solar/Wind Harmer
3.798
270356AE2-297 GEN
Solar/Wind Harmer
4.491
961761AG1-017 GEN
Solar/Wind Harmer
0.417
957241AF2-018 GEN
Solar/Wind Harmer
4.296
270053AF1-130 C
Solar/Wind Harmer
17.164
963791AG1-232 GEN
Solar/Wind Harmer
13.051
270119AB2-067 GEN1
50/50
5.522
270120AB2-067 GEN2
50/50
5.522
243186AF1-051 GEN
50/50
6.83
24318905MLG2
50/50
4.385
24723005RIVRG1
Adder
20.281
24723105RIVRG2
Adder
20.281
270349AD2-093_GEN
Solar/Wind Harmer
3.829
270471AD2-092_GEN
Solar/Wind Harmer
3.829
927014AC1-188 GEN
Solar/Wind Harmer
1.622
946101AF1-275 GEN
Solar/Wind Harmer
1.527
253383AE2-342_GEN
Solar/Wind Harmer
0.892
946581AF1-322 GEN
Solar/Wind Harmer
9.871
24691005MDL-2G C
Solar/Wind Harmer
3.567
959331AF2-224 GEN
Solar/Wind Harmer
9.647
959141AF2-205 GEN
Solar/Wind Harmer
5.832
958391AF2-133 GEN
Solar/Wind Harmer
8.746
274775LINCOLN ;6U
Adder
8.061
274776LINCOLN ;7U
Adder
8.061
274777LINCOLN ;8U
Adder
8.061
972228AH1-698 GEN2
Adder
3.526
972227AH1-698 GEN1
Adder
2.483
972037AH1-567 GEN1
Adder
0.174
274827FISK ;RP
Adder
7.384
274800UNIV PARK;3U
Adder
5.548
274801UNIV PARK;4U
Adder
5.548
274687WILL CNTY;4U
Adder
26.551
274687WILL CNTY;4U
Adder
26.551
274728ELWOOD EC;5P
Adder
15.615
274731ELWOOD EC;2P
Adder
15.615
274733ELWOOD EC;3P
Adder
15.615
274735ELWOOD EC;4P
Adder
15.615
274675JOLIET 29;7U
Adder
29.146
274675JOLIET 29;7U
Adder
28.105
274744AC1-111 GEN8
Adder
5.296
274746AC1-111 G10
Adder
5.296
23750701CROSSCHOOL
Solar/Wind Helper
1.294
238118U2-030_1
Solar/Wind Helper
0.306
23750501ELLIOTTS
Solar/Wind Helper
0.628
270269AC2-059
Solar/Wind Harmer
9.392
942861AE2-305 GEN
Solar/Wind Harmer
7.837
253415AE1-040 GEN
Solar/Wind Harmer
1.128
962581AG1-107 GEN
Solar/Wind Harmer
5.045
961491AF2-440 GEN
Solar/Wind Harmer
2.097
971073AG2-665 GEN
Solar/Wind Harmer
8.007
970879AG2-548 GEN
Solar/Wind Harmer
1.164
252509AD1-136 GEN
Solar/Wind Harmer
0.254
25183208HLCRTG
Solar/Wind Harmer
6.007
253370AE2-315 SEC1
Adder
1.983
25194408D.CRK1
Adder
7.485
25194508D.CRK3
Adder
1.399
25326109MON D
Adder
1.301
25322209TAIT E
Adder
9.645
25322209TAIT E
Adder
9.428
253349AC2-067 GEN
Solar/Wind Harmer
2.007
253400AC2-068 GEN
Solar/Wind Harmer
0.807
270054AF2-122 C O1
Solar/Wind Harmer
3.197
944541AF1-119 GEN
Solar/Wind Harmer
4.095
960971AF2-388 GEN
Solar/Wind Harmer
10.691
253378AE2-206_GEN
Solar/Wind Harmer
3.513
926881AC1-175 GEN
Solar/Wind Harmer
5.454
270383AD1-128 GEN
Solar/Wind Harmer
5.961
24728805RICHG1
Adder
3.69
24728905RICHG2
Adder
3.69
970883AG2-550 GEN
Solar/Wind Harmer
9.759
970885AG2-551 GEN
Solar/Wind Harmer
2.269
270462AD2-086
Solar/Wind Harmer
6.784
970291AG2-192 GEN
Solar/Wind Harmer
1.267
25326509SID D
Adder
1.282
970291AG2-192 GEN
Solar/Wind Harmer
0.408
247621Y3-024
Adder
0.235
270031AE2-169
Solar/Wind Harmer
7.939
270599AE1-208 GEN
Solar/Wind Harmer
7.939
964611AG1-324 GEN
Solar/Wind Harmer
0.51
270201AC2-176 GEN
Solar/Wind Harmer
5.005
24725505WLD G2 C
Solar/Wind Harmer
3.868
24699105WLD G1 C
Solar/Wind Harmer
3.822
942221AE2-234 GEN
Solar/Wind Harmer
3.403
970349AG2-230 GEN
Solar/Wind Harmer
14.508
945421AF1-207 GEN
Solar/Wind Harmer
13.563
957841AF2-078 GEN
Solar/Wind Harmer
5.839
270180AB1-006 GEN1
Solar/Wind Harmer
6.938
24697605MDL-3G C
Solar/Wind Harmer
3.556
24755605MDL-5G
Solar/Wind Harmer
2.326
24697905MDL-4G C
Solar/Wind Harmer
2.214
270181AB1-006 GEN2
Solar/Wind Harmer
0.69
247620Y3-023
Adder
0.44
274770LINCOLN ;1U
Adder
8.061
274771LINCOLN ;2U
Adder
8.061
274805UNIV PK N;1U
Adder
4.783
274808UNIV PK N;4U
Adder
4.751
274674JOLIET 9 ;6U
Adder
14.625
274696ROCKY RD ;4P
Adder
10.771
274695ROCKY RD ;2P
Adder
10.523
274693ROCKY RD ;1P
Adder
10.419
274697ROCKY RD ;3P
Adder
2.859
23751201ROTHROCK
Solar/Wind Helper
0.867
23585401KL_K28_T16
Solar/Wind Helper
1.41
235054AD2-180 GEN
Solar/Wind Helper
1.875
238117U2-030
Solar/Wind Helper
0.306
235531U2-073 GEN
Solar/Wind Helper
2.924
316097T157 G90
Solar/Wind Helper
1.19
252510AF1-249 C
Solar/Wind Harmer
0.413
253370AE2-315 SEC1
Adder
1.983
253371AE2-315 SEC2
Adder
1.876
25194608D.CRK4
Adder
1.627
25326309TAIT D
Adder
1.084
270391AF1-285 GEN3
Solar/Wind Harmer
1.195
270578AF1-285 GEN2
Solar/Wind Harmer
1.195
25196808ZIMRHP
Adder
74.904
970091AG2-072 GEN
Adder
75.485
25196008MFTGT1
Adder
1.367
270222AC2-111 GEN
Solar/Wind Harmer
4.385
944031AF1-071 GEN
Solar/Wind Harmer
0.987
965651AG1-433 GEN
Solar/Wind Harmer
5.345
958861AF2-177 GEN
Solar/Wind Harmer
10.687
942081AE2-220 GEN
Solar/Wind Harmer
6.249
270209AC1-174_GEN
Solar/Wind Harmer
3.977
270437AC2-090 C
Solar/Wind Harmer
5.454
270239V3-007_GEN1
Solar/Wind Harmer
1.681
945371AF1-202 GEN
Solar/Wind Harmer
6.817
945681AF1-233 GEN
Solar/Wind Harmer
18.397
270317AD1-130_GEN
Solar/Wind Harmer
3.123
270485AE1-090_GEN
Solar/Wind Harmer
0.59
270005AE1-210 C O1
Solar/Wind Harmer
5.332
270594AE1-207 GEN
Solar/Wind Harmer
13.238
270032AE2-172
Solar/Wind Harmer
4.533
970825AG2-519 GEN
Solar/Wind Harmer
2.045
276903AD2-071 C
Solar/Wind Harmer
9.73
270024AE2-089 GEN
Solar/Wind Harmer
4.552
944971AF1-162 GEN
Solar/Wind Harmer
6.766
940581AE2-045 GEN
Solar/Wind Harmer
9.84
24791305MDL-5G
Solar/Wind Harmer
2.326
965011AG1-365 GEN
Solar/Wind Harmer
9.647
971605AH1-302 GEN
Solar/Wind Harmer
8.413
964861AG1-349 GEN
Solar/Wind Harmer
7.578
971917AH1-482 GEN
Solar/Wind Harmer
8.743
24728605AND G2
Adder
3.696
24639705ELKHART HY
Adder
0.147
274773LINCOLN ;4U
Adder
8.061
274774LINCOLN ;5U
Adder
8.061
274751CRETE EC ;1U
Adder
7.861
274754CRETE EC ;4U
Adder
7.861
274723RIVER EC ;12
Adder
17.091
274812UNIV PK N;8U
Adder
4.772
274802UNIV PARK;5U
Adder
5.55
274732ELWOOD EC;7P
Adder
15.615
274676JOLIET 29;8U
Adder
29.146
274674JOLIET 9 ;6U
Adder
14.625
274745AC1-111 GEN9
Adder
5.296
23751101LEADS_P59
Solar/Wind Helper
2.597
238185AF2-356 C
Solar/Wind Helper
2.387
23583801GRNGAP
Solar/Wind Helper
4.45
238120AE2-309 GEN
Solar/Wind Helper
0.461
316095T157 G97
Solar/Wind Helper
1.19
238126S14_GEN_1
Solar/Wind Helper
0.726
238109AE1-109 GEN2
Solar/Wind Helper
0.096
958381AF2-132 GEN
Solar/Wind Harmer
6.61
24318805MLG1
50/50
7.624
24289405MTG1
50/50
6.078
24721905FLATG4
Adder
26.83
962771AG1-126 GEN
Solar/Wind Harmer
38.42
970153AG2-106 GEN
Solar/Wind Harmer
16.753
24686405CER G5
Adder
8.833
270330AC1-082 GEN2
Solar/Wind Harmer
0.501
270329AC1-082 GEN1
Solar/Wind Harmer
0.501
971191AH1-055 GEN
Solar/Wind Harmer
19.621
270284AF1-227 GEN1
Solar/Wind Harmer
5.814
270287AF1-227 GEN3
Solar/Wind Harmer
2.151
957541AF2-048 GEN
Solar/Wind Harmer
1.622
270367AC2-061_GEN
Solar/Wind Harmer
3.183
970879AG2-548 GEN
Solar/Wind Harmer
8.007
942051AE2-217 GEN
Solar/Wind Harmer
18.009
253325AC1-069 GEN
Solar/Wind Harmer
1.043
270186AC1-089 GEN
Solar/Wind Harmer
6.09
270518AE2-148 GEN
Solar/Wind Harmer
12.029
253317AC1-085 GEN4
Solar/Wind Harmer
8.322
946181AF1-283 GEN
Solar/Wind Harmer
12.922
252507AC2-088 GEN
Solar/Wind Harmer
1.779
253394AE2-221_GEN
Solar/Wind Harmer
4.505
252519AF1-045_GEN
Solar/Wind Harmer
3.611
961921AG1-034 GEN
Solar/Wind Harmer
12.632
253303V4-073 C
Solar/Wind Harmer
0.115
253370AE2-315 SEC1
Adder
1.983
253371AE2-315 SEC2
Adder
1.876
25194608D.CRK4
Adder
1.627
252524AE2-267 GEN
Solar/Wind Harmer
1.558
25196608WSDLE5
Adder
8.482
942871AE2-306 GEN
Solar/Wind Harmer
0.896
270391AF1-285 GEN3
Solar/Wind Harmer
0.46
960071AF2-298 GEN
Solar/Wind Harmer
1.495
960801AF2-371 GEN
Solar/Wind Harmer
2.503
964871AG1-351 GEN
Solar/Wind Harmer
1.728
25196008MFTGT1
Adder
1.324
944531AF1-118 GEN
Solar/Wind Harmer
34.283
276820AF1-078_GEN
Solar/Wind Harmer
1.561
24379505HDWTR1G C
Solar/Wind Harmer
7.727
270240V3-007_GEN2
Solar/Wind Harmer
6.045
972167AH1-666 GEN
Solar/Wind Harmer
7.81
270004AE1-209 GEN
Solar/Wind Harmer
5.332
946031AF1-268 GEN
Solar/Wind Harmer
8.091
965461AG1-414 GEN
Solar/Wind Harmer
2.21
970289AG2-191 GEN
Solar/Wind Harmer
0.748
247642Z2-115 C
Solar/Wind Harmer
0.062
970825AG2-519 GEN
Solar/Wind Harmer
5.491
958171AF2-111 GEN
Solar/Wind Harmer
24.35
962031AG1-047 GEN
Solar/Wind Harmer
2.944
957741AF2-068 GEN
Solar/Wind Harmer
14.606
270043AE2-236 GEN
Solar/Wind Harmer
5.338
971347AH1-153 GEN
Solar/Wind Harmer
4.836
24690905MDL-1G C
Solar/Wind Harmer
7.745
970781AG2-491 GEN
Solar/Wind Harmer
9.647
965021AG1-366 GEN
Solar/Wind Harmer
2.244
24728705AND G3
Adder
7.73
24728505AND G1
Adder
3.696
274772LINCOLN ;3U
Adder
8.061
274752CRETE EC ;2U
Adder
7.861
274753CRETE EC ;3U
Adder
7.861
274724RIVER EC ;11
Adder
16.891
274814UNIV PK N;0U
Adder
4.814
274807UNIV PK N;3U
Adder
4.804
274811UNIV PK N;7U
Adder
4.772
274803UNIV PARK;6U
Adder
5.55
274826FISK ;BP
Adder
10.419
972038AH1-567 GEN2
Adder
0.347
972259AH1-714 GEN
Adder
18.154
274729ELWOOD EC;1P
Adder
15.615
274730ELWOOD EC;6P
Adder
15.615
274734ELWOOD EC;8P
Adder
15.615
274736ELWOOD EC;9P
Adder
15.615
274676JOLIET 29;8U
Adder
28.105
274682WAUKEGAN ;7U
Adder
3.428
23562501BACKB
Solar/Wind Helper
1.069
237048AF1-022 C
Solar/Wind Helper
0.182
964991AG1-363 GEN
Solar/Wind Helper
3.896
238127S14_GEN_2
Solar/Wind Helper
0.726
238108AE1-109 GEN1
Solar/Wind Helper
0.096
238110AE1-109 GEN3
Solar/Wind Helper
0.096
238175AF1-290_GEN
Solar/Wind Helper
0.12
CPLELTFEXP_CPLE->PJM
CLTF
2.151
CBM West 2LTFEXP_CBM-W2->PJM
CBM
111.961
NYPJM->LTFIMP_NY
CLTF
4.02
LGEELTFEXP_LGEE->PJM
CLTF
6.53
WECLTFEXP_WEC->PJM
CLTF
3.585
AG2-052LTFEXP_AG2-052->PJM
LTF
0.223
AH1-155LTFEXP_AH1-155->PJM
LTF
0.334
LAGNLTFEXP_LAGN->PJM
CLTF
15.27
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.297
TVALTFEXP_TVA->PJM
CLTF
7.601
CBM West 1LTFEXP_CBM-W1->PJM
CBM
131.169
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.834
MECLTFEXP_MEC->PJM
CLTF
15.181
SIGELTFEXP_SIGE->PJM
CLTF
0.488

Details for 05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer l/o AP_P1-2_MP-500-028_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer
Contingency Name:
AP_P1-2_MP-500-028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.79 %
Rating:4000.0 MVA
Rating Type:B
MVA to Mitigate:4031.79
MW Contribution:
17.5
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
971985AH1-537 GEN
Solar/Wind Harmer
2.118
270263AC1-001 GEN
Solar/Wind Harmer
0.702
943861AF1-054 GEN
Solar/Wind Harmer
2.699
943851AF1-053 GEN
Solar/Wind Harmer
1.869
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270432AC2-029 GEN
Solar/Wind Harmer
3.104
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
945631AF1-228 GEN
Solar/Wind Harmer
0.001
253406AD2-031_GEN
Solar/Wind Harmer
0.516
241972AD1-140 GEN
Solar/Wind Harmer
0.757
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.113
253372AE2-315 SEC3
Adder
1.876
253372AE2-315 SEC3
Adder
1.876
25196408WSDLE3
Adder
8.732
25196308WSDLE2
Adder
8.656
25196208WSDLE1
Adder
8.634
25196708WSDLE6
Adder
8.613
25196508WSDLE4
Adder
8.396
25306009OHH W.
Adder
2.85
270578AF1-285 GEN2
Solar/Wind Harmer
0.46
270291AC1-194 GEN
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.507
25196108MFTGT2
Adder
1.399
24729505KEY G4
Adder
6.352
945581AF1-223 GEN
Solar/Wind Harmer
0
270166AC1-044 GEN3
50/50
5.522
24289405MTG1
50/50
6.078
243186AF1-051 GEN
50/50
6.83
962761AG1-125 GEN
Solar/Wind Harmer
32.401
970149AG2-104 GEN
Solar/Wind Harmer
17.497
970155AG2-107 GEN
Solar/Wind Harmer
20.69
972203AH1-686 GEN
Adder
2.528
24723205RIVRG3
Adder
20.281
24686505CER G6
Adder
8.903
960001AF2-291 GEN
Solar/Wind Harmer
0
270520AE2-214 GEN
Solar/Wind Harmer
0
270273AD2-016 GEN
Solar/Wind Harmer
0.719
971073AG2-665 GEN
Solar/Wind Harmer
1.164
253333AC1-068 GEN
Solar/Wind Harmer
0.008
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.935
24318805MLG1
50/50
7.624
24289405MTG1
50/50
6.078
24721905FLATG4
Adder
26.83
962771AG1-126 GEN
Solar/Wind Harmer
32.401
970153AG2-106 GEN
Solar/Wind Harmer
20.69
24686405CER G5
Adder
8.833
971191AH1-055 GEN
Solar/Wind Harmer
18.814
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
270367AC2-061_GEN
Solar/Wind Harmer
0
970879AG2-548 GEN
Solar/Wind Harmer
5.121
942051AE2-217 GEN
Solar/Wind Harmer
12.564
253325AC1-069 GEN
Solar/Wind Harmer
0.008
270186AC1-089 GEN
Solar/Wind Harmer
0
270518AE2-148 GEN
Solar/Wind Harmer
0.57
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.015
252507AC2-088 GEN
Solar/Wind Harmer
0.312
253394AE2-221_GEN
Solar/Wind Harmer
0
252519AF1-045_GEN
Solar/Wind Harmer
3.611
961921AG1-034 GEN
Solar/Wind Harmer
6.169
253370AE2-315 SEC1
Adder
1.983
253371AE2-315 SEC2
Adder
1.876
25194608D.CRK4
Adder
1.627
25196608WSDLE5
Adder
8.482
270391AF1-285 GEN3
Solar/Wind Harmer
0.46
970191AG2-125 GEN
Solar/Wind Harmer
1.771
25196008MFTGT1
Adder
1.324
944531AF1-118 GEN
Solar/Wind Harmer
30.627
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
972167AH1-666 GEN
Solar/Wind Harmer
5.449
270004AE1-209 GEN
Solar/Wind Harmer
1.475
946031AF1-268 GEN
Solar/Wind Harmer
6.472
970289AG2-191 GEN
Solar/Wind Harmer
0.748
247642Z2-115 C
Solar/Wind Harmer
0.003
970825AG2-519 GEN
Solar/Wind Harmer
5.122
958171AF2-111 GEN
Solar/Wind Harmer
16.988
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.19
270043AE2-236 GEN
Solar/Wind Harmer
4.345
971347AH1-153 GEN
Solar/Wind Harmer
3.374
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.73
965021AG1-366 GEN
Solar/Wind Harmer
2.244
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24728705AND G3
Adder
7.73
24728505AND G1
Adder
3.696
24386205FR-12G C
Solar/Wind Harmer
0
270063AE2-323 C
Solar/Wind Harmer
0
274772LINCOLN ;3U
Adder
8.061
274752CRETE EC ;2U
Adder
7.861
274753CRETE EC ;3U
Adder
7.861
274724RIVER EC ;11
Adder
16.891
270505AE1-170 C O1
Solar/Wind Harmer
6.985
945111AF1-176 GEN
Solar/Wind Harmer
5.391
274814UNIV PK N;0U
Adder
4.814
274807UNIV PK N;3U
Adder
4.804
274811UNIV PK N;7U
Adder
4.772
970193AG2-126 GEN
Solar/Wind Harmer
9.971
274887GEN-1.85
Solar/Wind Harmer
0.173
276843GEN-1.7
Solar/Wind Harmer
0.215
270119AB2-067 GEN1
50/50
5.522
270120AB2-067 GEN2
50/50
5.522
243186AF1-051 GEN
50/50
6.83
24318905MLG2
50/50
4.385
24723005RIVRG1
Adder
20.281
24723105RIVRG2
Adder
20.281
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
270269AC2-059
Solar/Wind Harmer
0.001
942861AE2-305 GEN
Solar/Wind Harmer
5.467
962581AG1-107 GEN
Solar/Wind Harmer
0.001
971073AG2-665 GEN
Solar/Wind Harmer
5.121
970879AG2-548 GEN
Solar/Wind Harmer
1.164
252509AD1-136 GEN
Solar/Wind Harmer
0.035
25183208HLCRTG
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.983
25194408D.CRK1
Adder
7.485
25194508D.CRK3
Adder
1.399
25326109MON D
Adder
1.301
25322209TAIT E
Adder
9.645
25322209TAIT E
Adder
9.428
270054AF2-122 C O1
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.456
960971AF2-388 GEN
Solar/Wind Harmer
4.003
970329AG2-216 GEN
Solar/Wind Harmer
2.946
926881AC1-175 GEN
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
24728805RICHG1
Adder
3.69
24728905RICHG2
Adder
3.69
970883AG2-550 GEN
Solar/Wind Harmer
6.808
970885AG2-551 GEN
Solar/Wind Harmer
2.269
270462AD2-086
Solar/Wind Harmer
0
971613AH1-306 GEN
Solar/Wind Harmer
3.264
970291AG2-192 GEN
Solar/Wind Harmer
0.884
25326509SID D
Adder
1.282
970291AG2-192 GEN
Solar/Wind Harmer
0.408
247621Y3-024
Adder
0.235
270031AE2-169
Solar/Wind Harmer
3.738
270599AE1-208 GEN
Solar/Wind Harmer
6.229
964611AG1-324 GEN
Solar/Wind Harmer
0.51
270201AC2-176 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
2.725
970349AG2-230 GEN
Solar/Wind Harmer
10.122
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
938701AE1-092 GEN
Solar/Wind Harmer
10.804
971655AH1-328 GEN
Solar/Wind Harmer
2.387
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.761
965681AG1-436 GEN
Solar/Wind Harmer
8.373
965791AG1-447 GEN
Solar/Wind Harmer
6.14
970241AG2-163 GEN
Solar/Wind Harmer
3.903
971587AH1-292 GEN
Solar/Wind Harmer
4.898
270246TR4_N_V150
Solar/Wind Harmer
0.043
270247TR4_N_V136
Solar/Wind Harmer
0.043
247620Y3-023
Adder
0.44
274770LINCOLN ;1U
Adder
8.061
274771LINCOLN ;2U
Adder
8.061
972043AH1-570 GEN
Solar/Wind Harmer
1.73
972045AH1-571 GEN
Solar/Wind Harmer
1.386
274805UNIV PK N;1U
Adder
4.783
274808UNIV PK N;4U
Adder
4.751
945391AF1-204 GEN
Solar/Wind Harmer
7.062
274888KELLY CRK;1U
Solar/Wind Harmer
0.387
276776AD2-060 GEN
Solar/Wind Harmer
0.708
958011AF2-095 GEN
Solar/Wind Harmer
9.564
970941AG2-585 GEN
Solar/Wind Harmer
3.653
276897AD1-100 C
Solar/Wind Harmer
16.602
961051AF2-396 GEN
Solar/Wind Harmer
13.281
961051AF2-396 GEN
Solar/Wind Harmer
8.854
274674JOLIET 9 ;6U
Adder
14.625
276893AG1-478 C
Solar/Wind Harmer
0.442
246937BC-WTG2
Solar/Wind Harmer
0.267
958481AF2-142 GEN
Solar/Wind Harmer
9.909
276901AD2-066 C O1
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
10.224
270071AF1-092 GEN
Solar/Wind Harmer
13.05
270543AE2-219 C
Solar/Wind Harmer
4.766
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.957
247536S-71 GEN
Solar/Wind Harmer
0.272
972163AH1-664 GEN
Solar/Wind Harmer
7.573
972165AH1-665 GEN
Solar/Wind Harmer
6.065
970289AG2-191 GEN
Solar/Wind Harmer
1.292
971609AH1-304 GEN
Solar/Wind Harmer
1.11
964611AG1-324 GEN
Solar/Wind Harmer
2.65
270356AE2-297 GEN
Solar/Wind Harmer
0
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
270053AF1-130 C
Solar/Wind Harmer
15.098
963791AG1-232 GEN
Solar/Wind Harmer
9.106
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
959331AF2-224 GEN
Solar/Wind Harmer
4.711
971611AH1-305 GEN
Solar/Wind Harmer
4.007
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.905
960681AF2-359 GEN
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
3.625
270526AF1-158 GEN
Solar/Wind Harmer
0
971771AH1-392 GEN
Solar/Wind Harmer
6.682
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
247521TR3_G114
Solar/Wind Harmer
0.242
965051AG1-369 GEN
Solar/Wind Harmer
3.331
965041AG1-368 GEN
Solar/Wind Harmer
6.672
270399AC1-101 GEN
Solar/Wind Harmer
2.112
270400AC1-102 GEN
Solar/Wind Harmer
2.112
339216AC1-074 GEN
Solar/Wind Harmer
0.178
274775LINCOLN ;6U
Adder
8.061
274776LINCOLN ;7U
Adder
8.061
274777LINCOLN ;8U
Adder
8.061
960591AF2-350 GEN
Solar/Wind Harmer
6.642
972228AH1-698 GEN2
Adder
3.526
972227AH1-698 GEN1
Adder
2.483
972037AH1-567 GEN1
Adder
0.174
274827FISK ;RP
Adder
7.384
274800UNIV PARK;3U
Adder
5.548
274801UNIV PARK;4U
Adder
5.548
274687WILL CNTY;4U
Adder
26.551
274687WILL CNTY;4U
Adder
26.551
274728ELWOOD EC;5P
Adder
15.615
274731ELWOOD EC;2P
Adder
15.615
274733ELWOOD EC;3P
Adder
15.615
274735ELWOOD EC;4P
Adder
15.615
274675JOLIET 29;7U
Adder
29.146
274675JOLIET 29;7U
Adder
28.105
970833AG2-524 GEN
Solar/Wind Harmer
7.29
970833AG2-524 GEN
Solar/Wind Harmer
4.86
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.839
274744AC1-111 GEN8
Adder
5.296
274746AC1-111 G10
Adder
5.296
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970169AG2-114 GEN
Solar/Wind Harmer
6.598
970073AG2-061 GEN
Solar/Wind Harmer
2.198
270007AE1-245 C
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.91
274854TWINGROVE;U2
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
1.116
276861AD2-134 GEN
Solar/Wind Harmer
0.117
276863AD2-134 GEN
Solar/Wind Harmer
0.117
971675AH1-338 GEN
Solar/Wind Harmer
2.56
971411AH1-196 GEN
Solar/Wind Harmer
9.845
23750701CROSSCHOOL
Solar/Wind Helper
1.294
238118U2-030_1
Solar/Wind Helper
0.306
23750501ELLIOTTS
Solar/Wind Helper
0.628
971171AH1-044 GEN
Solar/Wind Harmer
11.056
274696ROCKY RD ;4P
Adder
10.771
274695ROCKY RD ;2P
Adder
10.523
274693ROCKY RD ;1P
Adder
10.419
274697ROCKY RD ;3P
Adder
2.859
958491AF2-143 GEN
Solar/Wind Harmer
9.89
962691AG1-118 GEN
Solar/Wind Harmer
19.752
247607V1-011 GEN
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
2.139
971125AH1-004 GEN
Solar/Wind Harmer
2.63
970107AG2-081 GEN
Solar/Wind Harmer
1.973
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.189
23751201ROTHROCK
Solar/Wind Helper
0.867
23585401KL_K28_T16
Solar/Wind Helper
1.41
235054AD2-180 GEN
Solar/Wind Helper
1.875
238117U2-030
Solar/Wind Helper
0.306
235531U2-073 GEN
Solar/Wind Helper
2.924
316097T157 G90
Solar/Wind Helper
1.19
971341AH1-150 GEN
Solar/Wind Harmer
11.056
971343AH1-151 GEN
Solar/Wind Harmer
11.056
276806AD2-047 C O1
Solar/Wind Harmer
3.764
274803UNIV PARK;6U
Adder
5.55
939351AE1-166 GEN
Solar/Wind Harmer
0
274826FISK ;BP
Adder
10.419
972038AH1-567 GEN2
Adder
0.347
970707AG2-453 GEN
Solar/Wind Harmer
21.689
972259AH1-714 GEN
Adder
18.154
24695305TIMB G C
Solar/Wind Harmer
0.562
274729ELWOOD EC;1P
Adder
15.615
274730ELWOOD EC;6P
Adder
15.615
274734ELWOOD EC;8P
Adder
15.615
274736ELWOOD EC;9P
Adder
15.615
274676JOLIET 29;8U
Adder
28.105
246938BC-WTG3
Solar/Wind Harmer
0.239
270491AE1-102 GEN2
Solar/Wind Harmer
0.861
943121AE2-341 GEN
Solar/Wind Harmer
11.086
943591AF1-030 GEN
Solar/Wind Harmer
7.372
274862TOP CROP ;2U
Solar/Wind Harmer
0.892
274682WAUKEGAN ;7U
Adder
3.428
276868AE1-113 GEN
Solar/Wind Harmer
1.318
274879MINONK ;1U
Solar/Wind Harmer
0.275
965091AG1-374 GEN
Solar/Wind Harmer
19.702
959611AF2-252 GEN
Solar/Wind Harmer
2.189
946671AF1-331 GEN
Solar/Wind Harmer
0.7
274855GSG-6 ;RU
Solar/Wind Harmer
0.24
274850MENDOTA H;RU
Solar/Wind Harmer
0.076
970571AG2-364 GEN
Solar/Wind Harmer
13.127
23562501BACKB
Solar/Wind Helper
1.069
237048AF1-022 C
Solar/Wind Helper
0.182
964991AG1-363 GEN
Solar/Wind Helper
3.896
238127S14_GEN_2
Solar/Wind Helper
0.726
238108AE1-109 GEN1
Solar/Wind Helper
0.096
238110AE1-109 GEN3
Solar/Wind Helper
0.096
238175AF1-290_GEN
Solar/Wind Helper
0.12
959091AF2-200 GEN
Solar/Wind Harmer
11.056
253398AE2-221_GEN2
Solar/Wind Harmer
0
252516AE2-318_GEN
Solar/Wind Harmer
7.753
252510AF1-249 C
Solar/Wind Harmer
0.052
253370AE2-315 SEC1
Adder
1.983
253371AE2-315 SEC2
Adder
1.876
25194608D.CRK4
Adder
1.627
25326309TAIT D
Adder
1.084
25196808ZIMRHP
Adder
74.904
970091AG2-072 GEN
Adder
75.485
25196008MFTGT1
Adder
1.367
965651AG1-433 GEN
Solar/Wind Harmer
2.002
958861AF2-177 GEN
Solar/Wind Harmer
2.956
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5
945371AF1-202 GEN
Solar/Wind Harmer
0
945681AF1-233 GEN
Solar/Wind Harmer
12.835
270317AD1-130_GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.475
270594AE1-207 GEN
Solar/Wind Harmer
7.616
270032AE2-172
Solar/Wind Harmer
4.533
970825AG2-519 GEN
Solar/Wind Harmer
2.414
970773AG2-487 GEN
Solar/Wind Harmer
1.2
276903AD2-071 C
Solar/Wind Harmer
7.58
270024AE2-089 GEN
Solar/Wind Harmer
0.001
944971AF1-162 GEN
Solar/Wind Harmer
6.766
940581AE2-045 GEN
Solar/Wind Harmer
0
965011AG1-365 GEN
Solar/Wind Harmer
6.731
971605AH1-302 GEN
Solar/Wind Harmer
8.413
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.743
958381AF2-132 GEN
Solar/Wind Harmer
0.001
24728605AND G2
Adder
3.696
270055AF2-134 C O1
Solar/Wind Harmer
0
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
14.104
963741AG1-226 GEN
Solar/Wind Harmer
15.834
24639705ELKHART HY
Adder
0.147
274773LINCOLN ;4U
Adder
8.061
274774LINCOLN ;5U
Adder
8.061
274751CRETE EC ;1U
Adder
7.861
274754CRETE EC ;4U
Adder
7.861
274723RIVER EC ;12
Adder
17.091
957891AF2-083 GEN
Solar/Wind Harmer
11.089
945111AF1-176 GEN
Solar/Wind Harmer
11.868
274812UNIV PK N;8U
Adder
4.772
274802UNIV PARK;5U
Adder
5.55
941551AE2-152 GEN
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.463
965421AG1-410 GEN
Solar/Wind Harmer
19.9
274732ELWOOD EC;7P
Adder
15.615
274676JOLIET 29;8U
Adder
29.146
274674JOLIET 9 ;6U
Adder
14.625
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.267
270489AE1-102 GEN1
Solar/Wind Harmer
0.861
939401AE1-172 GEN
Solar/Wind Harmer
4.951
274745AC1-111 GEN9
Adder
5.296
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.073
274861TOP CROP ;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.457
276882AE2-255 GEN
Solar/Wind Harmer
0.769
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.213
962781AG1-127 GEN
Solar/Wind Harmer
6.263
274872LEEDK;1U
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
19.691
971403AH1-188 GEN
Solar/Wind Harmer
9.18
23751101LEADS_P59
Solar/Wind Helper
2.597
238185AF2-356 C
Solar/Wind Helper
2.387
23583801GRNGAP
Solar/Wind Helper
4.45
238120AE2-309 GEN
Solar/Wind Helper
0.461
316095T157 G97
Solar/Wind Helper
1.19
238126S14_GEN_1
Solar/Wind Helper
0.726
238109AE1-109 GEN2
Solar/Wind Helper
0.096
957471AF2-041 GEN
Solar/Wind Harmer
16.585
959081AF2-199 GEN
Solar/Wind Harmer
5.528
971067AG2-660 GEN
Solar/Wind Harmer
1.843
CPLELTFEXP_CPLE->PJM
CLTF
2.151
CBM West 2LTFEXP_CBM-W2->PJM
CBM
111.961
NYPJM->LTFIMP_NY
CLTF
4.02
LGEELTFEXP_LGEE->PJM
CLTF
6.53
WECLTFEXP_WEC->PJM
CLTF
3.585
AG2-052LTFEXP_AG2-052->PJM
LTF
0.223
AH1-155LTFEXP_AH1-155->PJM
LTF
0.334
LAGNLTFEXP_LAGN->PJM
CLTF
15.27
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.297
TVALTFEXP_TVA->PJM
CLTF
7.601
CBM West 1LTFEXP_CBM-W1->PJM
CBM
131.169
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.834
MECLTFEXP_MEC->PJM
CLTF
15.181
SIGELTFEXP_SIGE->PJM
CLTF
0.488

Details for 05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer l/o AP_P1-3_MP-765-502T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer
Contingency Name:
AP_P1-3_MP-765-502T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.79 %
Rating:4000.0 MVA
Rating Type:B
MVA to Mitigate:4031.62
MW Contribution:
17.5
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
971985AH1-537 GEN
Solar/Wind Harmer
2.118
270263AC1-001 GEN
Solar/Wind Harmer
0.702
943861AF1-054 GEN
Solar/Wind Harmer
2.699
943851AF1-053 GEN
Solar/Wind Harmer
1.869
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270432AC2-029 GEN
Solar/Wind Harmer
3.104
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
945631AF1-228 GEN
Solar/Wind Harmer
0.001
253406AD2-031_GEN
Solar/Wind Harmer
0.516
241972AD1-140 GEN
Solar/Wind Harmer
0.757
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.113
253372AE2-315 SEC3
Adder
1.876
253372AE2-315 SEC3
Adder
1.876
25196408WSDLE3
Adder
8.732
25196308WSDLE2
Adder
8.656
25196208WSDLE1
Adder
8.634
25196708WSDLE6
Adder
8.613
25196508WSDLE4
Adder
8.396
25306009OHH W.
Adder
2.85
270578AF1-285 GEN2
Solar/Wind Harmer
0.46
270291AC1-194 GEN
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.507
25196108MFTGT2
Adder
1.399
24729505KEY G4
Adder
6.352
945581AF1-223 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
10.224
270071AF1-092 GEN
Solar/Wind Harmer
13.05
270543AE2-219 C
Solar/Wind Harmer
4.766
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.957
247536S-71 GEN
Solar/Wind Harmer
0.272
972163AH1-664 GEN
Solar/Wind Harmer
7.573
972165AH1-665 GEN
Solar/Wind Harmer
6.065
970289AG2-191 GEN
Solar/Wind Harmer
1.292
971609AH1-304 GEN
Solar/Wind Harmer
1.11
964611AG1-324 GEN
Solar/Wind Harmer
2.65
270356AE2-297 GEN
Solar/Wind Harmer
0
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
270053AF1-130 C
Solar/Wind Harmer
15.098
963791AG1-232 GEN
Solar/Wind Harmer
9.106
270119AB2-067 GEN1
50/50
5.522
270120AB2-067 GEN2
50/50
5.522
243186AF1-051 GEN
50/50
6.83
24318905MLG2
50/50
4.385
24723005RIVRG1
Adder
20.281
24723105RIVRG2
Adder
20.281
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
270269AC2-059
Solar/Wind Harmer
0.001
942861AE2-305 GEN
Solar/Wind Harmer
5.467
962581AG1-107 GEN
Solar/Wind Harmer
0.001
971073AG2-665 GEN
Solar/Wind Harmer
5.121
970879AG2-548 GEN
Solar/Wind Harmer
1.164
252509AD1-136 GEN
Solar/Wind Harmer
0.035
25183208HLCRTG
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.983
25194408D.CRK1
Adder
7.485
25194508D.CRK3
Adder
1.399
25326109MON D
Adder
1.301
25322209TAIT E
Adder
9.645
25322209TAIT E
Adder
9.428
270054AF2-122 C O1
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.456
960971AF2-388 GEN
Solar/Wind Harmer
4.003
970329AG2-216 GEN
Solar/Wind Harmer
2.946
926881AC1-175 GEN
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
24728805RICHG1
Adder
3.69
24728905RICHG2
Adder
3.69
970883AG2-550 GEN
Solar/Wind Harmer
6.808
970885AG2-551 GEN
Solar/Wind Harmer
2.269
270462AD2-086
Solar/Wind Harmer
0
971613AH1-306 GEN
Solar/Wind Harmer
3.264
970291AG2-192 GEN
Solar/Wind Harmer
0.884
25326509SID D
Adder
1.282
970291AG2-192 GEN
Solar/Wind Harmer
0.408
247621Y3-024
Adder
0.235
270031AE2-169
Solar/Wind Harmer
3.738
270599AE1-208 GEN
Solar/Wind Harmer
6.229
964611AG1-324 GEN
Solar/Wind Harmer
0.51
270201AC2-176 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
2.725
970349AG2-230 GEN
Solar/Wind Harmer
10.122
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
938701AE1-092 GEN
Solar/Wind Harmer
10.804
971655AH1-328 GEN
Solar/Wind Harmer
2.387
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
270166AC1-044 GEN3
50/50
5.522
24289405MTG1
50/50
6.078
243186AF1-051 GEN
50/50
6.83
962761AG1-125 GEN
Solar/Wind Harmer
32.401
970149AG2-104 GEN
Solar/Wind Harmer
17.497
970155AG2-107 GEN
Solar/Wind Harmer
20.69
972203AH1-686 GEN
Adder
2.528
24723205RIVRG3
Adder
20.281
24686505CER G6
Adder
8.903
960001AF2-291 GEN
Solar/Wind Harmer
0
270520AE2-214 GEN
Solar/Wind Harmer
0
270273AD2-016 GEN
Solar/Wind Harmer
0.719
971073AG2-665 GEN
Solar/Wind Harmer
1.164
253333AC1-068 GEN
Solar/Wind Harmer
0.008
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.935
253398AE2-221_GEN2
Solar/Wind Harmer
0
252516AE2-318_GEN
Solar/Wind Harmer
7.753
252510AF1-249 C
Solar/Wind Harmer
0.052
253370AE2-315 SEC1
Adder
1.983
253371AE2-315 SEC2
Adder
1.876
25194608D.CRK4
Adder
1.627
25326309TAIT D
Adder
1.084
25196808ZIMRHP
Adder
74.904
970091AG2-072 GEN
Adder
75.485
25196008MFTGT1
Adder
1.367
965651AG1-433 GEN
Solar/Wind Harmer
2.002
958861AF2-177 GEN
Solar/Wind Harmer
2.956
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5
945371AF1-202 GEN
Solar/Wind Harmer
0
945681AF1-233 GEN
Solar/Wind Harmer
12.835
270317AD1-130_GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.475
270594AE1-207 GEN
Solar/Wind Harmer
7.616
270032AE2-172
Solar/Wind Harmer
4.533
970825AG2-519 GEN
Solar/Wind Harmer
2.414
24318805MLG1
50/50
7.624
24289405MTG1
50/50
6.078
24721905FLATG4
Adder
26.83
962771AG1-126 GEN
Solar/Wind Harmer
32.401
970153AG2-106 GEN
Solar/Wind Harmer
20.69
24686405CER G5
Adder
8.833
971191AH1-055 GEN
Solar/Wind Harmer
18.814
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
270367AC2-061_GEN
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.761
965681AG1-436 GEN
Solar/Wind Harmer
8.373
965791AG1-447 GEN
Solar/Wind Harmer
6.14
970241AG2-163 GEN
Solar/Wind Harmer
3.903
971587AH1-292 GEN
Solar/Wind Harmer
4.898
270246TR4_N_V150
Solar/Wind Harmer
0.043
270247TR4_N_V136
Solar/Wind Harmer
0.043
247620Y3-023
Adder
0.44
274770LINCOLN ;1U
Adder
8.061
274771LINCOLN ;2U
Adder
8.061
972043AH1-570 GEN
Solar/Wind Harmer
1.73
972045AH1-571 GEN
Solar/Wind Harmer
1.386
274805UNIV PK N;1U
Adder
4.783
274808UNIV PK N;4U
Adder
4.751
945391AF1-204 GEN
Solar/Wind Harmer
7.062
274888KELLY CRK;1U
Solar/Wind Harmer
0.387
276776AD2-060 GEN
Solar/Wind Harmer
0.708
958011AF2-095 GEN
Solar/Wind Harmer
9.564
970941AG2-585 GEN
Solar/Wind Harmer
3.653
276897AD1-100 C
Solar/Wind Harmer
16.602
961051AF2-396 GEN
Solar/Wind Harmer
13.281
961051AF2-396 GEN
Solar/Wind Harmer
8.854
274674JOLIET 9 ;6U
Adder
14.625
276893AG1-478 C
Solar/Wind Harmer
0.442
246937BC-WTG2
Solar/Wind Harmer
0.267
958481AF2-142 GEN
Solar/Wind Harmer
9.909
276901AD2-066 C O1
Solar/Wind Harmer
0
274696ROCKY RD ;4P
Adder
10.771
274695ROCKY RD ;2P
Adder
10.523
274693ROCKY RD ;1P
Adder
10.419
274697ROCKY RD ;3P
Adder
2.859
958491AF2-143 GEN
Solar/Wind Harmer
9.89
962691AG1-118 GEN
Solar/Wind Harmer
19.752
247607V1-011 GEN
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
2.139
971125AH1-004 GEN
Solar/Wind Harmer
2.63
970107AG2-081 GEN
Solar/Wind Harmer
1.973
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.189
23751201ROTHROCK
Solar/Wind Helper
0.867
23585401KL_K28_T16
Solar/Wind Helper
1.41
235054AD2-180 GEN
Solar/Wind Helper
1.875
238117U2-030
Solar/Wind Helper
0.306
235531U2-073 GEN
Solar/Wind Helper
2.924
316097T157 G90
Solar/Wind Helper
1.19
971341AH1-150 GEN
Solar/Wind Harmer
11.056
971343AH1-151 GEN
Solar/Wind Harmer
11.056
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
959331AF2-224 GEN
Solar/Wind Harmer
4.711
971611AH1-305 GEN
Solar/Wind Harmer
4.007
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.905
960681AF2-359 GEN
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
3.625
270526AF1-158 GEN
Solar/Wind Harmer
0
971771AH1-392 GEN
Solar/Wind Harmer
6.682
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
247521TR3_G114
Solar/Wind Harmer
0.242
965051AG1-369 GEN
Solar/Wind Harmer
3.331
965041AG1-368 GEN
Solar/Wind Harmer
6.672
270399AC1-101 GEN
Solar/Wind Harmer
2.112
270400AC1-102 GEN
Solar/Wind Harmer
2.112
339216AC1-074 GEN
Solar/Wind Harmer
0.178
274775LINCOLN ;6U
Adder
8.061
274776LINCOLN ;7U
Adder
8.061
274777LINCOLN ;8U
Adder
8.061
960591AF2-350 GEN
Solar/Wind Harmer
6.642
972228AH1-698 GEN2
Adder
3.526
972227AH1-698 GEN1
Adder
2.483
972037AH1-567 GEN1
Adder
0.174
274827FISK ;RP
Adder
7.384
274800UNIV PARK;3U
Adder
5.548
274801UNIV PARK;4U
Adder
5.548
274687WILL CNTY;4U
Adder
26.551
274687WILL CNTY;4U
Adder
26.551
274728ELWOOD EC;5P
Adder
15.615
274731ELWOOD EC;2P
Adder
15.615
274733ELWOOD EC;3P
Adder
15.615
274735ELWOOD EC;4P
Adder
15.615
274675JOLIET 29;7U
Adder
29.146
274675JOLIET 29;7U
Adder
28.105
970833AG2-524 GEN
Solar/Wind Harmer
7.29
970833AG2-524 GEN
Solar/Wind Harmer
4.86
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.839
274744AC1-111 GEN8
Adder
5.296
274746AC1-111 G10
Adder
5.296
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970169AG2-114 GEN
Solar/Wind Harmer
6.598
970073AG2-061 GEN
Solar/Wind Harmer
2.198
270007AE1-245 C
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.91
274854TWINGROVE;U2
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
1.116
276861AD2-134 GEN
Solar/Wind Harmer
0.117
276863AD2-134 GEN
Solar/Wind Harmer
0.117
971675AH1-338 GEN
Solar/Wind Harmer
2.56
971411AH1-196 GEN
Solar/Wind Harmer
9.845
23750701CROSSCHOOL
Solar/Wind Helper
1.294
238118U2-030_1
Solar/Wind Helper
0.306
23750501ELLIOTTS
Solar/Wind Helper
0.628
971171AH1-044 GEN
Solar/Wind Harmer
11.056
970773AG2-487 GEN
Solar/Wind Harmer
1.2
276903AD2-071 C
Solar/Wind Harmer
7.58
270024AE2-089 GEN
Solar/Wind Harmer
0.001
944971AF1-162 GEN
Solar/Wind Harmer
6.766
940581AE2-045 GEN
Solar/Wind Harmer
0
965011AG1-365 GEN
Solar/Wind Harmer
6.731
971605AH1-302 GEN
Solar/Wind Harmer
8.413
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.743
958381AF2-132 GEN
Solar/Wind Harmer
0.001
24728605AND G2
Adder
3.696
270055AF2-134 C O1
Solar/Wind Harmer
0
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
14.104
963741AG1-226 GEN
Solar/Wind Harmer
15.834
24639705ELKHART HY
Adder
0.147
274773LINCOLN ;4U
Adder
8.061
274774LINCOLN ;5U
Adder
8.061
274751CRETE EC ;1U
Adder
7.861
274754CRETE EC ;4U
Adder
7.861
274723RIVER EC ;12
Adder
17.091
957891AF2-083 GEN
Solar/Wind Harmer
11.089
945111AF1-176 GEN
Solar/Wind Harmer
11.868
274812UNIV PK N;8U
Adder
4.772
274802UNIV PARK;5U
Adder
5.55
941551AE2-152 GEN
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.463
965421AG1-410 GEN
Solar/Wind Harmer
19.9
274732ELWOOD EC;7P
Adder
15.615
274676JOLIET 29;8U
Adder
29.146
274674JOLIET 9 ;6U
Adder
14.625
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.267
270489AE1-102 GEN1
Solar/Wind Harmer
0.861
939401AE1-172 GEN
Solar/Wind Harmer
4.951
274745AC1-111 GEN9
Adder
5.296
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.073
274861TOP CROP ;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.457
276882AE2-255 GEN
Solar/Wind Harmer
0.769
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.213
962781AG1-127 GEN
Solar/Wind Harmer
6.263
274872LEEDK;1U
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
19.691
971403AH1-188 GEN
Solar/Wind Harmer
9.18
23751101LEADS_P59
Solar/Wind Helper
2.597
238185AF2-356 C
Solar/Wind Helper
2.387
23583801GRNGAP
Solar/Wind Helper
4.45
238120AE2-309 GEN
Solar/Wind Helper
0.461
316095T157 G97
Solar/Wind Helper
1.19
238126S14_GEN_1
Solar/Wind Helper
0.726
238109AE1-109 GEN2
Solar/Wind Helper
0.096
957471AF2-041 GEN
Solar/Wind Harmer
16.585
959081AF2-199 GEN
Solar/Wind Harmer
5.528
971067AG2-660 GEN
Solar/Wind Harmer
1.843
970879AG2-548 GEN
Solar/Wind Harmer
5.121
942051AE2-217 GEN
Solar/Wind Harmer
12.564
253325AC1-069 GEN
Solar/Wind Harmer
0.008
270186AC1-089 GEN
Solar/Wind Harmer
0
270518AE2-148 GEN
Solar/Wind Harmer
0.57
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.015
252507AC2-088 GEN
Solar/Wind Harmer
0.312
253394AE2-221_GEN
Solar/Wind Harmer
0
252519AF1-045_GEN
Solar/Wind Harmer
3.611
961921AG1-034 GEN
Solar/Wind Harmer
6.169
253370AE2-315 SEC1
Adder
1.983
253371AE2-315 SEC2
Adder
1.876
25194608D.CRK4
Adder
1.627
25196608WSDLE5
Adder
8.482
270391AF1-285 GEN3
Solar/Wind Harmer
0.46
970191AG2-125 GEN
Solar/Wind Harmer
1.771
25196008MFTGT1
Adder
1.324
944531AF1-118 GEN
Solar/Wind Harmer
30.627
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
972167AH1-666 GEN
Solar/Wind Harmer
5.449
270004AE1-209 GEN
Solar/Wind Harmer
1.475
946031AF1-268 GEN
Solar/Wind Harmer
6.472
970289AG2-191 GEN
Solar/Wind Harmer
0.748
247642Z2-115 C
Solar/Wind Harmer
0.003
970825AG2-519 GEN
Solar/Wind Harmer
5.122
958171AF2-111 GEN
Solar/Wind Harmer
16.988
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.19
270043AE2-236 GEN
Solar/Wind Harmer
4.345
971347AH1-153 GEN
Solar/Wind Harmer
3.374
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.73
965021AG1-366 GEN
Solar/Wind Harmer
2.244
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24728705AND G3
Adder
7.73
24728505AND G1
Adder
3.696
24386205FR-12G C
Solar/Wind Harmer
0
270063AE2-323 C
Solar/Wind Harmer
0
274772LINCOLN ;3U
Adder
8.061
274752CRETE EC ;2U
Adder
7.861
274753CRETE EC ;3U
Adder
7.861
274724RIVER EC ;11
Adder
16.891
270505AE1-170 C O1
Solar/Wind Harmer
6.985
945111AF1-176 GEN
Solar/Wind Harmer
5.391
274814UNIV PK N;0U
Adder
4.814
274807UNIV PK N;3U
Adder
4.804
274811UNIV PK N;7U
Adder
4.772
970193AG2-126 GEN
Solar/Wind Harmer
9.971
274887GEN-1.85
Solar/Wind Harmer
0.173
276843GEN-1.7
Solar/Wind Harmer
0.215
276806AD2-047 C O1
Solar/Wind Harmer
3.764
274803UNIV PARK;6U
Adder
5.55
939351AE1-166 GEN
Solar/Wind Harmer
0
274826FISK ;BP
Adder
10.419
972038AH1-567 GEN2
Adder
0.347
970707AG2-453 GEN
Solar/Wind Harmer
21.689
972259AH1-714 GEN
Adder
18.154
24695305TIMB G C
Solar/Wind Harmer
0.562
274729ELWOOD EC;1P
Adder
15.615
274730ELWOOD EC;6P
Adder
15.615
274734ELWOOD EC;8P
Adder
15.615
274736ELWOOD EC;9P
Adder
15.615
274676JOLIET 29;8U
Adder
28.105
246938BC-WTG3
Solar/Wind Harmer
0.239
270491AE1-102 GEN2
Solar/Wind Harmer
0.861
943121AE2-341 GEN
Solar/Wind Harmer
11.086
943591AF1-030 GEN
Solar/Wind Harmer
7.372
274862TOP CROP ;2U
Solar/Wind Harmer
0.892
274682WAUKEGAN ;7U
Adder
3.428
276868AE1-113 GEN
Solar/Wind Harmer
1.318
274879MINONK ;1U
Solar/Wind Harmer
0.275
965091AG1-374 GEN
Solar/Wind Harmer
19.702
959611AF2-252 GEN
Solar/Wind Harmer
2.189
946671AF1-331 GEN
Solar/Wind Harmer
0.7
274855GSG-6 ;RU
Solar/Wind Harmer
0.24
274850MENDOTA H;RU
Solar/Wind Harmer
0.076
970571AG2-364 GEN
Solar/Wind Harmer
13.127
23562501BACKB
Solar/Wind Helper
1.069
237048AF1-022 C
Solar/Wind Helper
0.182
964991AG1-363 GEN
Solar/Wind Helper
3.896
238127S14_GEN_2
Solar/Wind Helper
0.726
238108AE1-109 GEN1
Solar/Wind Helper
0.096
238110AE1-109 GEN3
Solar/Wind Helper
0.096
238175AF1-290_GEN
Solar/Wind Helper
0.12
959091AF2-200 GEN
Solar/Wind Harmer
11.056
CPLELTFEXP_CPLE->PJM
CLTF
2.151
CBM West 2LTFEXP_CBM-W2->PJM
CBM
111.961
NYPJM->LTFIMP_NY
CLTF
4.02
LGEELTFEXP_LGEE->PJM
CLTF
6.53
WECLTFEXP_WEC->PJM
CLTF
3.585
AG2-052LTFEXP_AG2-052->PJM
LTF
0.223
AH1-155LTFEXP_AH1-155->PJM
LTF
0.334
LAGNLTFEXP_LAGN->PJM
CLTF
15.27
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.297
TVALTFEXP_TVA->PJM
CLTF
7.601
CBM West 1LTFEXP_CBM-W1->PJM
CBM
131.169
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.834
MECLTFEXP_MEC->PJM
CLTF
15.181
SIGELTFEXP_SIGE->PJM
CLTF
0.488

Details for 05GAVIN-05MOUNTN 765.0 kV Ckt 1 line l/o AEP_P4_#8075_05MARYSV 765_A2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05GAVIN-05MOUNTN 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8075_05MARYSV 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.81 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5567.74
MW Contribution:
72.73
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
5.637
960681AF2-359 GEN
Solar/Wind Harmer
4.171
274775LINCOLN ;6U
Adder
6.828
274776LINCOLN ;7U
Adder
6.828
274777LINCOLN ;8U
Adder
6.828
971771AH1-392 GEN
Solar/Wind Harmer
9.865
270526AF1-158 GEN
Solar/Wind Harmer
4.968
270071AF1-092 GEN
Solar/Wind Harmer
16.393
274827FISK ;RP
Adder
8.382
972228AH1-698 GEN2
Adder
4.001
972227AH1-698 GEN1
Adder
2.817
960591AF2-350 GEN
Solar/Wind Harmer
10.8
972037AH1-567 GEN1
Adder
0.198
274800UNIV PARK;3U
Adder
6.294
274801UNIV PARK;4U
Adder
6.294
274687WILL CNTY;4U
Adder
30.059
274687WILL CNTY;4U
Adder
30.059
274675JOLIET 29;7U
Adder
32.988
274675JOLIET 29;7U
Adder
31.81
274728ELWOOD EC;5P
Adder
17.641
274731ELWOOD EC;2P
Adder
17.641
274733ELWOOD EC;3P
Adder
17.641
274735ELWOOD EC;4P
Adder
17.641
970833AG2-524 GEN
Solar/Wind Harmer
9.369
243186AF1-051 GEN
50/50
25.323
24721705FLATG2
50/50
83.72
270102X2-052 ST
50/50
1.77
270100X2-052 CT1
50/50
1.635
270101X2-052 CT2
50/50
1.635
970349AG2-230 GEN
Solar/Wind Harmer
17.451
965681AG1-436 GEN
Solar/Wind Harmer
13.797
965791AG1-447 GEN
Solar/Wind Harmer
7.059
274770LINCOLN ;1U
Adder
6.828
274771LINCOLN ;2U
Adder
6.828
274805UNIV PK N;1U
Adder
5.43
274808UNIV PK N;4U
Adder
5.395
274888KELLY CRK;1U
Solar/Wind Harmer
6.373
276776AD2-060 GEN
Solar/Wind Harmer
0.452
958011AF2-095 GEN
Solar/Wind Harmer
15.552
970941AG2-585 GEN
Solar/Wind Harmer
5.94
276897AD1-100 C
Solar/Wind Harmer
50.05
274674JOLIET 9 ;6U
Adder
16.537
276893AG1-478 C
Solar/Wind Harmer
0.47
961051AF2-396 GEN
Solar/Wind Harmer
16.977
961051AF2-396 GEN
Solar/Wind Harmer
7.896
247620Y3-023
Adder
0.491
274696ROCKY RD ;4P
Adder
12.099
274695ROCKY RD ;2P
Adder
11.82
274693ROCKY RD ;1P
Adder
11.704
274697ROCKY RD ;3P
Adder
3.211
274683WAUKEGAN ;8U
Adder
22.325
274683WAUKEGAN ;8U
Adder
18.819
958481AF2-142 GEN
Solar/Wind Harmer
15.887
962691AG1-118 GEN
Solar/Wind Harmer
31.712
270535AF1-215 GEN1
Solar/Wind Harmer
4.788
270536AF1-215 GEN2
Solar/Wind Harmer
4.788
960751AF2-366 GEN
Solar/Wind Harmer
3.028
958491AF2-143 GEN
Solar/Wind Harmer
15.765
276901AD2-066 C O1
Solar/Wind Harmer
3.683
971341AH1-150 GEN
Solar/Wind Harmer
20.86
971343AH1-151 GEN
Solar/Wind Harmer
20.86
276872AE1-163_GEN1
Solar/Wind Harmer
6.982
276876AE1-163_GEN2
Solar/Wind Harmer
6.982
972235AH1-702 GEN1
Adder
2.619
972236AH1-702 GEN2
Adder
2.278
274764LEE CO EC;5U
Adder
9.6
274765LEE CO EC;6U
Adder
9.6
274762LEE CO EC;3U
Adder
9.577
274763LEE CO EC;4U
Adder
9.487
970833AG2-524 GEN
Solar/Wind Harmer
4.358
276893AG1-478 C
Solar/Wind Harmer
0.59
274744AC1-111 GEN8
Adder
5.979
274746AC1-111 G10
Adder
5.979
944161AF1-084 GEN
Solar/Wind Harmer
2.343
970073AG2-061 GEN
Solar/Wind Harmer
2.444
971675AH1-338 GEN
Solar/Wind Harmer
18.853
971411AH1-196 GEN
Solar/Wind Harmer
15.71
276861AD2-134 GEN
Solar/Wind Harmer
1.87
276863AD2-134 GEN
Solar/Wind Harmer
1.87
971171AH1-044 GEN
Solar/Wind Harmer
20.86
970031AG2-029 GEN
Solar/Wind Harmer
26.06
274823ROCKFORD ;21
Adder
20.279
274863CRW1-WTG
Solar/Wind Harmer
5.807
274864CRW2-WTG
Solar/Wind Harmer
5.807
276889AE2-281 GEN
Solar/Wind Harmer
1.995
24729505KEY G4
Adder
6.732
958391AF2-133 GEN
Solar/Wind Harmer
9.403
274856ECOGROVE ;U1
Solar/Wind Harmer
3.494
276611AD2-172 GEN
Solar/Wind Harmer
2.65
276612AE2-035 GEN
Solar/Wind Harmer
2.65
926823AC1-168 GEN
Solar/Wind Harmer
4.437
971681AH1-341 GEN
Solar/Wind Harmer
15.482
972267AH1-718 GEN
Adder
4.26
24318705GVG2
50/50
23.473
24722005FLATG5
50/50
5.637
24721905FLATG4
50/50
102.97
962771AG1-126 GEN
Solar/Wind Harmer
117.776
970153AG2-106 GEN
Solar/Wind Harmer
51.356
971347AH1-153 GEN
Solar/Wind Harmer
5.817
270043AE2-236 GEN
Solar/Wind Harmer
6.077
274772LINCOLN ;3U
Adder
6.828
24441505OLIV SLR
Solar/Wind Harmer
0.146
247643Z2-116 C
Solar/Wind Harmer
0.076
274724RIVER EC ;11
Adder
19.254
970707AG2-453 GEN
Solar/Wind Harmer
30.421
276164X3-005 C
Solar/Wind Harmer
0.762
972231SS25-0005
Solar/Wind Harmer
10.288
972181SS23-001
Solar/Wind Harmer
6.43
274752CRETE EC ;2U
Adder
5.299
274753CRETE EC ;3U
Adder
5.299
972259AH1-714 GEN
Adder
20.646
274814UNIV PK N;0U
Adder
5.466
274807UNIV PK N;3U
Adder
5.454
274811UNIV PK N;7U
Adder
5.418
274826FISK ;BP
Adder
11.827
274887GEN-1.85
Solar/Wind Harmer
5.754
276772AC2-154 GEN
Solar/Wind Harmer
3.014
276843GEN-1.7
Solar/Wind Harmer
0.619
276806AD2-047 C O1
Solar/Wind Harmer
11.553
274803UNIV PARK;6U
Adder
6.296
972038AH1-567 GEN2
Adder
0.394
270505AE1-170 C O1
Solar/Wind Harmer
16.193
939351AE1-166 GEN
Solar/Wind Harmer
6.39
274676JOLIET 29;8U
Adder
31.81
945111AF1-176 GEN
Solar/Wind Harmer
6.071
274729ELWOOD EC;1P
Adder
17.641
274730ELWOOD EC;6P
Adder
17.641
274734ELWOOD EC;8P
Adder
17.641
274736ELWOOD EC;9P
Adder
17.641
943121AE2-341 GEN
Solar/Wind Harmer
16.071
943591AF1-030 GEN
Solar/Wind Harmer
10.714
274682WAUKEGAN ;7U
Adder
19.056
274862TOP CROP ;2U
Solar/Wind Harmer
5.355
944531AF1-118 GEN
Solar/Wind Harmer
36.997
270063AE2-323 C
Solar/Wind Harmer
2.319
276868AE1-113 GEN
Solar/Wind Harmer
10.604
274879MINONK ;1U
Solar/Wind Harmer
7.07
276799AD1-013 GEN
Solar/Wind Harmer
2.315
946671AF1-331 GEN
Solar/Wind Harmer
0.439
274855GSG-6 ;RU
Solar/Wind Harmer
3.866
274850MENDOTA H;RU
Solar/Wind Harmer
2.688
276602WESTBROOK C
Solar/Wind Harmer
2.226
964401AG1-302 GEN
Solar/Wind Harmer
9.462
959091AF2-200 GEN
Solar/Wind Harmer
20.86
274760LEE CO EC;1U
Adder
9.577
274767LEE CO EC;8U
Adder
9.465
970571AG2-364 GEN
Solar/Wind Harmer
13.727
243186AF1-051 GEN
50/50
25.323
24318705GVG2
50/50
23.473
24721805FLATG3
50/50
5.637
24344105CKG2
50/50
8.984
962761AG1-125 GEN
Solar/Wind Harmer
117.776
970149AG2-104 GEN
Solar/Wind Harmer
72.727
970155AG2-107 GEN
Solar/Wind Harmer
51.356
972207SS24-0001
Solar/Wind Harmer
24.277
274773LINCOLN ;4U
Adder
6.828
274774LINCOLN ;5U
Adder
6.828
270216AD2-079_GEN
Solar/Wind Harmer
0.659
274723RIVER EC ;12
Adder
19.477
274751CRETE EC ;1U
Adder
5.299
274754CRETE EC ;4U
Adder
5.299
274812UNIV PK N;8U
Adder
5.418
274802UNIV PARK;5U
Adder
6.296
957891AF2-083 GEN
Solar/Wind Harmer
16.172
941551AE2-152 GEN
Solar/Wind Harmer
4.886
24639705ELKHART HY
Adder
0.165
274676JOLIET 29;8U
Adder
32.988
274674JOLIET 9 ;6U
Adder
16.537
945111AF1-176 GEN
Solar/Wind Harmer
19.155
274732ELWOOD EC;7P
Adder
17.641
274871GR RIDGE ;2U
Solar/Wind Harmer
8.25
274847GR RIDGE ;BU
Solar/Wind Harmer
5.425
274745AC1-111 GEN9
Adder
5.979
970373AG2-245 GEN
Solar/Wind Harmer
22.427
270449AD2-020 GEN
Solar/Wind Harmer
2.991
943021AE2-325 GEN
Solar/Wind Harmer
3.887
274682WAUKEGAN ;7U
Adder
19.056
274828WAUKEGAN ;BP
Adder
11.703
276694AA1-018 GEN2
Solar/Wind Harmer
6.683
276691AA1-018 GEN1
Solar/Wind Harmer
0.799
274861TOP CROP ;1U
Solar/Wind Harmer
6.413
270055AF2-134 C O1
Solar/Wind Harmer
3.192
962781AG1-127 GEN
Solar/Wind Harmer
10.037
274872LEEDK;1U
Solar/Wind Harmer
8.651
939401AE1-172 GEN
Solar/Wind Harmer
14.65
276805AD2-038 GEN
Solar/Wind Harmer
5.39
276882AE2-255 GEN
Solar/Wind Harmer
3.535
971997AH1-543 GEN
Solar/Wind Harmer
16.49
24441205WTRV SLR C
Solar/Wind Harmer
0.141
958381AF2-132 GEN
Solar/Wind Harmer
9.462
957471AF2-041 GEN
Solar/Wind Harmer
31.291
959081AF2-199 GEN
Solar/Wind Harmer
10.43
971067AG2-660 GEN
Solar/Wind Harmer
2.426
964861AG1-349 GEN
Solar/Wind Harmer
8.19
971917AH1-482 GEN
Solar/Wind Harmer
9.449
274822ROCKFORD ;11
Adder
20.427
970819AG2-516 GEN
Solar/Wind Harmer
12.445
274761LEE CO EC;2U
Adder
9.577
274766LEE CO EC;7U
Adder
9.465
970569AG2-363 GEN
Solar/Wind Harmer
20.591
CPLELTFEXP_CPLE->PJM
CLTF
3.107
CBM West 2LTFEXP_CBM-W2->PJM
CBM
100.587
NYPJM->LTFIMP_NY
CLTF
3.437
LGEELTFEXP_LGEE->PJM
CLTF
4.047
WECLTFEXP_WEC->PJM
CLTF
3.968
AG2-052LTFEXP_AG2-052->PJM
LTF
0.242
AH1-155LTFEXP_AH1-155->PJM
LTF
0.364
LAGNLTFEXP_LAGN->PJM
CLTF
13.978
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.324
TVALTFEXP_TVA->PJM
CLTF
6.618
CBM West 1LTFEXP_CBM-W1->PJM
CBM
120.794
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.36
MECLTFEXP_MEC->PJM
CLTF
15.734
SIGELTFEXP_SIGE->PJM
CLTF
0.372

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P4_#9728_05MALIS 138_L1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9728_05MALIS 138_L1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.82 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1646.06
MW Contribution:
12.9
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270036AE2-216 BAT
50/50
5.971
270223U2-072_GEN1
Solar/Wind Harmer
1.974
270224U2-072_GEN2
Solar/Wind Harmer
1.974
270227U2-072_GEN3
Solar/Wind Harmer
1.974
270228U2-072_GEN4
Solar/Wind Harmer
1.974
270231U2-072_GEN5
Solar/Wind Harmer
1.974
270578AF1-285 GEN2
Solar/Wind Harmer
0.465
241973AD2-163_GEN1
Solar/Wind Harmer
1.951
241974AD2-163_GEN2
Solar/Wind Harmer
1.951
270302AB2-170 GEN
Solar/Wind Harmer
7.816
970179AG2-119 GEN
Solar/Wind Harmer
6.791
241955AC1-078 GEN
Solar/Wind Harmer
4.994
957201AF2-014 GEN
Solar/Wind Harmer
2.726
270435AC2-044 GEN
Solar/Wind Harmer
1.202
241972AD1-140 GEN
Solar/Wind Harmer
2.573
270007AE1-245 C
Solar/Wind Harmer
3.051
247521TR3_G114
Solar/Wind Harmer
1.861
270191TR4_S_V150
Solar/Wind Harmer
1.66
965051AG1-369 GEN
Solar/Wind Harmer
2.764
965041AG1-368 GEN
Solar/Wind Harmer
5.371
945631AF1-228 GEN
Solar/Wind Harmer
2.514
959331AF2-224 GEN
Solar/Wind Harmer
5.3
270404AC1-167 GEN
Solar/Wind Harmer
0.571
943861AF1-054 GEN
Solar/Wind Harmer
1.939
943851AF1-053 GEN
Solar/Wind Harmer
0.937
963791AG1-232 GEN
Solar/Wind Harmer
6.712
253338AC1-165 GEN
Solar/Wind Harmer
0.524
253343AC1-166 GEN
Solar/Wind Harmer
0.524
970031AG2-029 GEN
Solar/Wind Harmer
12.056
270071AF1-092 GEN
Solar/Wind Harmer
7.206
24729505KEY G4
Adder
3.077
25306009OHH W.
Adder
1.341
253372AE2-315 SEC3
Adder
0.879
253372AE2-315 SEC3
Adder
0.879
958711AF2-162 GEN
Solar/Wind Harmer
0.469
971771AH1-392 GEN
Solar/Wind Harmer
4.103
945581AF1-223 GEN
Solar/Wind Harmer
2.057
944161AF1-084 GEN
Solar/Wind Harmer
0.999
270526AF1-158 GEN
Solar/Wind Harmer
2.05
961761AG1-017 GEN
Solar/Wind Harmer
0.193
964611AG1-324 GEN
Solar/Wind Harmer
1.75
247536S-71 GEN
Solar/Wind Harmer
1.815
960681AF2-359 GEN
Solar/Wind Harmer
1.694
270543AE2-219 C
Solar/Wind Harmer
4.458
971029AG2-637 GEN
Solar/Wind Harmer
6.646
971549AH1-272 GEN
Solar/Wind Harmer
8.101
274775LINCOLN ;6U
Adder
2.707
274776LINCOLN ;7U
Adder
2.707
274777LINCOLN ;8U
Adder
2.707
970289AG2-191 GEN
Solar/Wind Harmer
0.824
972037AH1-567 GEN1
Adder
0.079
274827FISK ;RP
Adder
3.358
960591AF2-350 GEN
Solar/Wind Harmer
4.325
274800UNIV PARK;3U
Adder
2.522
274801UNIV PARK;4U
Adder
2.522
972228AH1-698 GEN2
Adder
1.601
270466AD2-091
50/50
5.428
270349AD2-093_GEN
Solar/Wind Harmer
4.875
270471AD2-092_GEN
Solar/Wind Harmer
4.875
938701AE1-092 GEN
Solar/Wind Harmer
21.99
270462AD2-086
Solar/Wind Harmer
6.492
946101AF1-275 GEN
Solar/Wind Harmer
1.347
241960AC2-195 GEN
Solar/Wind Harmer
2.356
253378AE2-206_GEN
Solar/Wind Harmer
2.404
25326509SID D
Adder
0.839
246937BC-WTG2
Solar/Wind Harmer
2.351
942801AE2-298 GEN
Solar/Wind Harmer
0.86
247607V1-011 GEN
Solar/Wind Harmer
2.234
270246TR4_N_V150
Solar/Wind Harmer
0.471
270247TR4_N_V136
Solar/Wind Harmer
0.471
942861AE2-305 GEN
Solar/Wind Harmer
3.928
25326109MON D
Adder
0.654
944231AF1-091 GEN
Solar/Wind Harmer
8.795
25322209TAIT E
Adder
4.684
25322209TAIT E
Adder
4.578
942221AE2-234 GEN
Solar/Wind Harmer
1.652
253349AC2-067 GEN
Solar/Wind Harmer
0.96
253400AC2-068 GEN
Solar/Wind Harmer
0.386
247620Y3-023
Adder
0.214
253370AE2-315 SEC1
Adder
0.929
944541AF1-119 GEN
Solar/Wind Harmer
1.941
960971AF2-388 GEN
Solar/Wind Harmer
5.068
970349AG2-230 GEN
Solar/Wind Harmer
6.915
961051AF2-396 GEN
Solar/Wind Harmer
7.218
961051AF2-396 GEN
Solar/Wind Harmer
3.357
247621Y3-024
Adder
0.109
270201AC2-176 GEN
Solar/Wind Harmer
2.319
253383AE2-342_GEN
Solar/Wind Harmer
0.398
964611AG1-324 GEN
Solar/Wind Harmer
0.235
270286AF1-227 GEN2
Solar/Wind Harmer
2.53
971995AH1-542 GEN
Solar/Wind Harmer
11.797
270391AF1-285 GEN3
Solar/Wind Harmer
1.209
270578AF1-285 GEN2
Solar/Wind Harmer
1.209
270317AD1-130_GEN
Solar/Wind Harmer
2.988
270485AE1-090_GEN
Solar/Wind Harmer
0.565
270520AE2-214 GEN
Solar/Wind Harmer
5.389
241813AF1-122_GEN
Solar/Wind Harmer
4.164
971201AH1-060 GEN
Solar/Wind Harmer
1.301
962761AG1-125 GEN
Solar/Wind Harmer
20.895
970149AG2-104 GEN
Solar/Wind Harmer
12.903
970155AG2-107 GEN
Solar/Wind Harmer
9.111
246936BC-WTG1
Solar/Wind Harmer
2.351
270489AE1-102 GEN1
Solar/Wind Harmer
0.781
965421AG1-410 GEN
Solar/Wind Harmer
17.827
270297AD1-101 GEN
Solar/Wind Harmer
1.129
270258AD1-119 GEN
Solar/Wind Harmer
1.095
965011AG1-365 GEN
Solar/Wind Harmer
5.3
253333AC1-068 GEN
Solar/Wind Harmer
0.505
25326309TAIT D
Adder
0.527
270024AE2-089 GEN
Solar/Wind Harmer
2.197
253370AE2-315 SEC1
Adder
0.929
253371AE2-315 SEC2
Adder
0.879
965651AG1-433 GEN
Solar/Wind Harmer
2.534
24639705ELKHART HY
Adder
0.071
270216AD2-079_GEN
Solar/Wind Harmer
0.279
958861AF2-177 GEN
Solar/Wind Harmer
5.03
945111AF1-176 GEN
Solar/Wind Harmer
8.149
957891AF2-083 GEN
Solar/Wind Harmer
6.834
945371AF1-202 GEN
Solar/Wind Harmer
3.165
270449AD2-020 GEN
Solar/Wind Harmer
1.271
943021AE2-325 GEN
Solar/Wind Harmer
1.652
24441205WTRV SLR C
Solar/Wind Harmer
0.06
970373AG2-245 GEN
Solar/Wind Harmer
9.221
270005AE1-210 C O1
Solar/Wind Harmer
2.395
970825AG2-519 GEN
Solar/Wind Harmer
0.919
274751CRETE EC ;1U
Adder
2.136
274754CRETE EC ;4U
Adder
2.136
972207SS24-0001
Solar/Wind Harmer
9.624
274773LINCOLN ;4U
Adder
2.707
274774LINCOLN ;5U
Adder
2.707
274723RIVER EC ;12
Adder
7.823
270055AF2-134 C O1
Solar/Wind Harmer
1.317
274812UNIV PK N;8U
Adder
2.178
270594AE1-207 GEN
Solar/Wind Harmer
5.904
270032AE2-172
Solar/Wind Harmer
2.022
274802UNIV PARK;5U
Adder
2.524
958381AF2-132 GEN
Solar/Wind Harmer
3.921
274676JOLIET 29;8U
Adder
13.196
270475AD2-096_GEN
50/50
7.81
270284AF1-227 GEN1
Solar/Wind Harmer
6.84
270287AF1-227 GEN3
Solar/Wind Harmer
2.53
942871AE2-306 GEN
Solar/Wind Harmer
0.907
270391AF1-285 GEN3
Solar/Wind Harmer
0.465
942051AE2-217 GEN
Solar/Wind Harmer
13.98
970065AG2-057 GEN
Solar/Wind Harmer
0.651
276820AF1-078_GEN
Solar/Wind Harmer
1.068
962771AG1-126 GEN
Solar/Wind Harmer
20.895
970153AG2-106 GEN
Solar/Wind Harmer
9.111
246938BC-WTG3
Solar/Wind Harmer
2.392
270491AE1-102 GEN2
Solar/Wind Harmer
0.781
958091AF2-103 GEN
Solar/Wind Harmer
0.091
24695305TIMB G C
Solar/Wind Harmer
1.831
965021AG1-366 GEN
Solar/Wind Harmer
1.232
270044AE2-322 C
Solar/Wind Harmer
0.692
270518AE2-148 GEN
Solar/Wind Harmer
6.261
270588AE1-091_GEN
Solar/Wind Harmer
5.505
270043AE2-236 GEN
Solar/Wind Harmer
2.704
253325AC1-069 GEN
Solar/Wind Harmer
0.505
960071AF2-298 GEN
Solar/Wind Harmer
0.73
270063AE2-323 C
Solar/Wind Harmer
1.052
944531AF1-118 GEN
Solar/Wind Harmer
16.732
270541AE2-072 C
Solar/Wind Harmer
2.158
253303V4-073 C
Solar/Wind Harmer
0.054
253370AE2-315 SEC1
Adder
0.929
253371AE2-315 SEC2
Adder
0.879
971347AH1-153 GEN
Solar/Wind Harmer
2.305
247643Z2-116 C
Solar/Wind Harmer
0.032
945111AF1-176 GEN
Solar/Wind Harmer
2.583
270505AE1-170 C O1
Solar/Wind Harmer
6.831
962031AG1-047 GEN
Solar/Wind Harmer
1.364
957741AF2-068 GEN
Solar/Wind Harmer
6.767
24441505OLIV SLR
Solar/Wind Harmer
0.06
965681AG1-436 GEN
Solar/Wind Harmer
5.605
965791AG1-447 GEN
Solar/Wind Harmer
2.868
270031AE2-169
Solar/Wind Harmer
3.645
270599AE1-208 GEN
Solar/Wind Harmer
3.645
970883AG2-550 GEN
Solar/Wind Harmer
4.458
970885AG2-551 GEN
Solar/Wind Harmer
1.037
274770LINCOLN ;1U
Adder
2.707
274771LINCOLN ;2U
Adder
2.707
270535AF1-215 GEN1
Solar/Wind Harmer
1.976
270536AF1-215 GEN2
Solar/Wind Harmer
1.976
274805UNIV PK N;1U
Adder
2.183
274808UNIV PK N;4U
Adder
2.168
970291AG2-192 GEN
Solar/Wind Harmer
0.564
970291AG2-192 GEN
Solar/Wind Harmer
0.182
270383AD1-128 GEN
Solar/Wind Harmer
2.644
274888KELLY CRK;1U
Solar/Wind Harmer
2.552
276776AD2-060 GEN
Solar/Wind Harmer
0.181
958011AF2-095 GEN
Solar/Wind Harmer
6.228
970941AG2-585 GEN
Solar/Wind Harmer
2.379
270054AF2-122 C O1
Solar/Wind Helper
0.827
972227AH1-698 GEN1
Adder
1.127
274687WILL CNTY;4U
Adder
12.029
274687WILL CNTY;4U
Adder
12.029
274675JOLIET 29;7U
Adder
13.196
274675JOLIET 29;7U
Adder
12.725
946031AF1-268 GEN
Solar/Wind Harmer
3.655
270004AE1-209 GEN
Solar/Wind Harmer
2.395
970825AG2-519 GEN
Solar/Wind Harmer
2.467
972231SS25-0005
Solar/Wind Harmer
4.147
972181SS23-001
Solar/Wind Harmer
2.592
274752CRETE EC ;2U
Adder
2.136
274753CRETE EC ;3U
Adder
2.136
274772LINCOLN ;3U
Adder
2.707
274724RIVER EC ;11
Adder
7.731
276164X3-005 C
Solar/Wind Harmer
0.306
274814UNIV PK N;0U
Adder
2.197
274807UNIV PK N;3U
Adder
2.192
274811UNIV PK N;7U
Adder
2.178
965461AG1-414 GEN
Solar/Wind Harmer
0.984
970289AG2-191 GEN
Solar/Wind Harmer
0.333
247642Z2-115 C
Solar/Wind Harmer
0.028
274803UNIV PARK;6U
Adder
2.524
274826FISK ;BP
Adder
4.738
274887GEN-1.85
Solar/Wind Harmer
2.304
276772AC2-154 GEN
Solar/Wind Harmer
1.207
276843GEN-1.7
Solar/Wind Harmer
0.248
276806AD2-047 C O1
Solar/Wind Harmer
4.627
972038AH1-567 GEN2
Adder
0.158
964401AG1-302 GEN
Solar/Wind Harmer
3.921
972259AH1-714 GEN
Adder
8.237
274676JOLIET 29;8U
Adder
12.724
970707AG2-453 GEN
Solar/Wind Harmer
11.087
CPLELTFEXP_CPLE->PJM
CLTF
0.338
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.726
NYPJM->LTFIMP_NY
CLTF
1.312
LGEELTFEXP_LGEE->PJM
CLTF
2.29
WECLTFEXP_WEC->PJM
CLTF
1.588
AG2-052LTFEXP_AG2-052->PJM
LTF
0.1
AH1-155LTFEXP_AH1-155->PJM
LTF
0.15
LAGNLTFEXP_LAGN->PJM
CLTF
5.1
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.32
TVALTFEXP_TVA->PJM
CLTF
2.365
CBM West 1LTFEXP_CBM-W1->PJM
CBM
56.311
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.538
MECLTFEXP_MEC->PJM
CLTF
6.315
SIGELTFEXP_SIGE->PJM
CLTF
0.181

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P4_#9730_05MALIS 138_P1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9730_05MALIS 138_P1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.97 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1563.59
MW Contribution:
12.87
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270036AE2-216 BAT
50/50
5.957
270223U2-072_GEN1
Solar/Wind Harmer
1.969
270224U2-072_GEN2
Solar/Wind Harmer
1.969
270227U2-072_GEN3
Solar/Wind Harmer
1.969
270228U2-072_GEN4
Solar/Wind Harmer
1.969
270231U2-072_GEN5
Solar/Wind Harmer
1.969
270578AF1-285 GEN2
Solar/Wind Harmer
0.464
241973AD2-163_GEN1
Solar/Wind Harmer
1.945
241974AD2-163_GEN2
Solar/Wind Harmer
1.945
270302AB2-170 GEN
Solar/Wind Harmer
7.798
970179AG2-119 GEN
Solar/Wind Harmer
6.776
241955AC1-078 GEN
Solar/Wind Harmer
4.984
957201AF2-014 GEN
Solar/Wind Harmer
2.72
270435AC2-044 GEN
Solar/Wind Harmer
1.199
241972AD1-140 GEN
Solar/Wind Harmer
2.566
270007AE1-245 C
Solar/Wind Harmer
3.044
247521TR3_G114
Solar/Wind Harmer
1.857
270191TR4_S_V150
Solar/Wind Harmer
1.657
965051AG1-369 GEN
Solar/Wind Harmer
2.758
965041AG1-368 GEN
Solar/Wind Harmer
5.359
945631AF1-228 GEN
Solar/Wind Harmer
2.509
959331AF2-224 GEN
Solar/Wind Harmer
5.288
270404AC1-167 GEN
Solar/Wind Harmer
0.569
943861AF1-054 GEN
Solar/Wind Harmer
1.926
943851AF1-053 GEN
Solar/Wind Harmer
0.931
963791AG1-232 GEN
Solar/Wind Harmer
6.697
253338AC1-165 GEN
Solar/Wind Harmer
0.523
253343AC1-166 GEN
Solar/Wind Harmer
0.523
970031AG2-029 GEN
Solar/Wind Harmer
12.029
270071AF1-092 GEN
Solar/Wind Harmer
7.19
24729505KEY G4
Adder
3.07
25306009OHH W.
Adder
1.338
958711AF2-162 GEN
Solar/Wind Harmer
0.468
253372AE2-315 SEC3
Adder
0.877
253372AE2-315 SEC3
Adder
0.877
971771AH1-392 GEN
Solar/Wind Harmer
4.095
945581AF1-223 GEN
Solar/Wind Harmer
2.053
944161AF1-084 GEN
Solar/Wind Harmer
0.997
270526AF1-158 GEN
Solar/Wind Harmer
2.045
961761AG1-017 GEN
Solar/Wind Harmer
0.193
964611AG1-324 GEN
Solar/Wind Harmer
1.747
247536S-71 GEN
Solar/Wind Harmer
1.811
960681AF2-359 GEN
Solar/Wind Harmer
1.691
270543AE2-219 C
Solar/Wind Harmer
4.448
971029AG2-637 GEN
Solar/Wind Harmer
6.632
971549AH1-272 GEN
Solar/Wind Harmer
8.084
274775LINCOLN ;6U
Adder
2.701
274776LINCOLN ;7U
Adder
2.701
274777LINCOLN ;8U
Adder
2.701
970289AG2-191 GEN
Solar/Wind Harmer
0.823
972037AH1-567 GEN1
Adder
0.079
274827FISK ;RP
Adder
3.351
960591AF2-350 GEN
Solar/Wind Harmer
4.316
274800UNIV PARK;3U
Adder
2.516
274801UNIV PARK;4U
Adder
2.516
972228AH1-698 GEN2
Adder
1.597
972227AH1-698 GEN1
Adder
1.125
270466AD2-091
50/50
5.415
270349AD2-093_GEN
Solar/Wind Harmer
4.863
270471AD2-092_GEN
Solar/Wind Harmer
4.863
938701AE1-092 GEN
Solar/Wind Harmer
21.934
270462AD2-086
Solar/Wind Harmer
6.477
946101AF1-275 GEN
Solar/Wind Harmer
1.343
241960AC2-195 GEN
Solar/Wind Harmer
2.35
253378AE2-206_GEN
Solar/Wind Harmer
2.398
25326509SID D
Adder
0.837
246937BC-WTG2
Solar/Wind Harmer
2.346
942801AE2-298 GEN
Solar/Wind Harmer
0.858
247607V1-011 GEN
Solar/Wind Harmer
2.229
270246TR4_N_V150
Solar/Wind Harmer
0.47
270247TR4_N_V136
Solar/Wind Harmer
0.47
942861AE2-305 GEN
Solar/Wind Harmer
3.903
25326109MON D
Adder
0.652
944231AF1-091 GEN
Solar/Wind Harmer
8.776
25322209TAIT E
Adder
4.673
25322209TAIT E
Adder
4.568
942221AE2-234 GEN
Solar/Wind Harmer
1.648
253349AC2-067 GEN
Solar/Wind Harmer
0.958
253400AC2-068 GEN
Solar/Wind Harmer
0.385
247620Y3-023
Adder
0.214
944541AF1-119 GEN
Solar/Wind Harmer
1.937
960971AF2-388 GEN
Solar/Wind Harmer
5.057
253370AE2-315 SEC1
Adder
0.927
970349AG2-230 GEN
Solar/Wind Harmer
6.9
961051AF2-396 GEN
Solar/Wind Harmer
7.203
961051AF2-396 GEN
Solar/Wind Harmer
3.35
247621Y3-024
Adder
0.109
270201AC2-176 GEN
Solar/Wind Harmer
2.314
964611AG1-324 GEN
Solar/Wind Harmer
0.234
965681AG1-436 GEN
Solar/Wind Harmer
5.593
965791AG1-447 GEN
Solar/Wind Harmer
2.861
253383AE2-342_GEN
Solar/Wind Harmer
0.395
270031AE2-169
Solar/Wind Harmer
3.637
270599AE1-208 GEN
Solar/Wind Harmer
3.637
970883AG2-550 GEN
Solar/Wind Harmer
4.448
970885AG2-551 GEN
Solar/Wind Harmer
1.034
274770LINCOLN ;1U
Adder
2.701
274771LINCOLN ;2U
Adder
2.701
270535AF1-215 GEN1
Solar/Wind Harmer
1.972
270536AF1-215 GEN2
Solar/Wind Harmer
1.972
274805UNIV PK N;1U
Adder
2.178
270286AF1-227 GEN2
Solar/Wind Harmer
2.524
971995AH1-542 GEN
Solar/Wind Harmer
11.77
270391AF1-285 GEN3
Solar/Wind Harmer
1.206
270578AF1-285 GEN2
Solar/Wind Harmer
1.206
270317AD1-130_GEN
Solar/Wind Harmer
2.981
270485AE1-090_GEN
Solar/Wind Harmer
0.563
270520AE2-214 GEN
Solar/Wind Harmer
5.374
241813AF1-122_GEN
Solar/Wind Harmer
4.155
971201AH1-060 GEN
Solar/Wind Harmer
1.298
962761AG1-125 GEN
Solar/Wind Harmer
20.847
970149AG2-104 GEN
Solar/Wind Harmer
12.873
970155AG2-107 GEN
Solar/Wind Harmer
9.09
246936BC-WTG1
Solar/Wind Harmer
2.346
270489AE1-102 GEN1
Solar/Wind Harmer
0.78
965421AG1-410 GEN
Solar/Wind Harmer
17.787
270297AD1-101 GEN
Solar/Wind Harmer
1.127
270258AD1-119 GEN
Solar/Wind Harmer
1.093
965011AG1-365 GEN
Solar/Wind Harmer
5.288
253333AC1-068 GEN
Solar/Wind Harmer
0.504
25326309TAIT D
Adder
0.526
270024AE2-089 GEN
Solar/Wind Harmer
2.192
965651AG1-433 GEN
Solar/Wind Harmer
2.529
253370AE2-315 SEC1
Adder
0.927
253371AE2-315 SEC2
Adder
0.877
24639705ELKHART HY
Adder
0.071
270216AD2-079_GEN
Solar/Wind Harmer
0.278
958861AF2-177 GEN
Solar/Wind Harmer
5.02
945111AF1-176 GEN
Solar/Wind Harmer
8.131
957891AF2-083 GEN
Solar/Wind Harmer
6.82
945371AF1-202 GEN
Solar/Wind Harmer
3.158
270449AD2-020 GEN
Solar/Wind Harmer
1.268
943021AE2-325 GEN
Solar/Wind Harmer
1.648
24441205WTRV SLR C
Solar/Wind Harmer
0.06
970373AG2-245 GEN
Solar/Wind Harmer
9.201
270005AE1-210 C O1
Solar/Wind Harmer
2.39
970825AG2-519 GEN
Solar/Wind Harmer
0.917
274751CRETE EC ;1U
Adder
2.131
274754CRETE EC ;4U
Adder
2.131
972207SS24-0001
Solar/Wind Harmer
9.604
274773LINCOLN ;4U
Adder
2.701
274774LINCOLN ;5U
Adder
2.701
274723RIVER EC ;12
Adder
7.806
270055AF2-134 C O1
Solar/Wind Harmer
1.315
274812UNIV PK N;8U
Adder
2.173
270594AE1-207 GEN
Solar/Wind Harmer
5.891
270032AE2-172
Solar/Wind Harmer
2.018
274802UNIV PARK;5U
Adder
2.519
958381AF2-132 GEN
Solar/Wind Harmer
3.912
270475AD2-096_GEN
50/50
7.792
270284AF1-227 GEN1
Solar/Wind Harmer
6.824
270287AF1-227 GEN3
Solar/Wind Harmer
2.524
942871AE2-306 GEN
Solar/Wind Harmer
0.905
270391AF1-285 GEN3
Solar/Wind Harmer
0.464
942051AE2-217 GEN
Solar/Wind Harmer
13.942
970065AG2-057 GEN
Solar/Wind Harmer
0.649
276820AF1-078_GEN
Solar/Wind Harmer
1.065
962771AG1-126 GEN
Solar/Wind Harmer
20.847
970153AG2-106 GEN
Solar/Wind Harmer
9.09
246938BC-WTG3
Solar/Wind Harmer
2.386
270491AE1-102 GEN2
Solar/Wind Harmer
0.78
958091AF2-103 GEN
Solar/Wind Harmer
0.091
24695305TIMB G C
Solar/Wind Harmer
1.827
965021AG1-366 GEN
Solar/Wind Harmer
1.23
270044AE2-322 C
Solar/Wind Harmer
0.691
270518AE2-148 GEN
Solar/Wind Harmer
6.249
270588AE1-091_GEN
Solar/Wind Harmer
5.494
270043AE2-236 GEN
Solar/Wind Harmer
2.698
253325AC1-069 GEN
Solar/Wind Harmer
0.504
960071AF2-298 GEN
Solar/Wind Harmer
0.728
270063AE2-323 C
Solar/Wind Harmer
1.049
944531AF1-118 GEN
Solar/Wind Harmer
16.696
270541AE2-072 C
Solar/Wind Harmer
2.153
253303V4-073 C
Solar/Wind Harmer
0.054
253370AE2-315 SEC1
Adder
0.927
253371AE2-315 SEC2
Adder
0.877
971347AH1-153 GEN
Solar/Wind Harmer
2.3
247643Z2-116 C
Solar/Wind Harmer
0.032
945111AF1-176 GEN
Solar/Wind Harmer
2.577
270505AE1-170 C O1
Solar/Wind Harmer
6.816
962031AG1-047 GEN
Solar/Wind Harmer
1.361
957741AF2-068 GEN
Solar/Wind Harmer
6.753
24441505OLIV SLR
Solar/Wind Harmer
0.06
946031AF1-268 GEN
Solar/Wind Harmer
3.647
270004AE1-209 GEN
Solar/Wind Harmer
2.39
970825AG2-519 GEN
Solar/Wind Harmer
2.462
972231SS25-0005
Solar/Wind Harmer
4.138
972181SS23-001
Solar/Wind Harmer
2.586
274752CRETE EC ;2U
Adder
2.131
274753CRETE EC ;3U
Adder
2.131
274772LINCOLN ;3U
Adder
2.701
274724RIVER EC ;11
Adder
7.714
276164X3-005 C
Solar/Wind Harmer
0.305
274814UNIV PK N;0U
Adder
2.192
274807UNIV PK N;3U
Adder
2.187
274811UNIV PK N;7U
Adder
2.173
965461AG1-414 GEN
Solar/Wind Harmer
0.982
970289AG2-191 GEN
Solar/Wind Harmer
0.332
247642Z2-115 C
Solar/Wind Harmer
0.028
274803UNIV PARK;6U
Adder
2.519
274808UNIV PK N;4U
Adder
2.164
970291AG2-192 GEN
Solar/Wind Harmer
0.563
970291AG2-192 GEN
Solar/Wind Harmer
0.181
270383AD1-128 GEN
Solar/Wind Harmer
2.638
274888KELLY CRK;1U
Solar/Wind Harmer
2.547
276776AD2-060 GEN
Solar/Wind Harmer
0.181
958011AF2-095 GEN
Solar/Wind Harmer
6.215
970941AG2-585 GEN
Solar/Wind Harmer
2.374
270054AF2-122 C O1
Solar/Wind Helper
0.821
274826FISK ;BP
Adder
4.728
274887GEN-1.85
Solar/Wind Harmer
2.299
276772AC2-154 GEN
Solar/Wind Harmer
1.204
276843GEN-1.7
Solar/Wind Harmer
0.247
276806AD2-047 C O1
Solar/Wind Harmer
4.617
972038AH1-567 GEN2
Adder
0.157
964401AG1-302 GEN
Solar/Wind Harmer
3.912
972259AH1-714 GEN
Adder
8.22
970707AG2-453 GEN
Solar/Wind Harmer
11.064
CPLELTFEXP_CPLE->PJM
CLTF
0.338
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.643
NYPJM->LTFIMP_NY
CLTF
1.31
LGEELTFEXP_LGEE->PJM
CLTF
2.285
WECLTFEXP_WEC->PJM
CLTF
1.584
AG2-052LTFEXP_AG2-052->PJM
LTF
0.1
AH1-155LTFEXP_AH1-155->PJM
LTF
0.15
LAGNLTFEXP_LAGN->PJM
CLTF
5.09
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.316
TVALTFEXP_TVA->PJM
CLTF
2.361
CBM West 1LTFEXP_CBM-W1->PJM
CBM
56.192
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.519
MECLTFEXP_MEC->PJM
CLTF
6.302
SIGELTFEXP_SIGE->PJM
CLTF
0.181

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P4_#9729_05MALIS 138_M1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9729_05MALIS 138_M1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.88 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1562.23
MW Contribution:
12.87
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270036AE2-216 BAT
50/50
5.954
270223U2-072_GEN1
Solar/Wind Harmer
1.968
270224U2-072_GEN2
Solar/Wind Harmer
1.968
270227U2-072_GEN3
Solar/Wind Harmer
1.968
270228U2-072_GEN4
Solar/Wind Harmer
1.968
270231U2-072_GEN5
Solar/Wind Harmer
1.968
270578AF1-285 GEN2
Solar/Wind Harmer
0.464
241973AD2-163_GEN1
Solar/Wind Harmer
1.944
241974AD2-163_GEN2
Solar/Wind Harmer
1.944
270302AB2-170 GEN
Solar/Wind Harmer
7.794
970179AG2-119 GEN
Solar/Wind Harmer
6.772
241955AC1-078 GEN
Solar/Wind Harmer
4.982
957201AF2-014 GEN
Solar/Wind Harmer
2.718
270435AC2-044 GEN
Solar/Wind Harmer
1.199
241972AD1-140 GEN
Solar/Wind Harmer
2.564
270007AE1-245 C
Solar/Wind Harmer
3.043
247521TR3_G114
Solar/Wind Harmer
1.856
270191TR4_S_V150
Solar/Wind Harmer
1.656
965051AG1-369 GEN
Solar/Wind Harmer
2.757
965041AG1-368 GEN
Solar/Wind Harmer
5.357
945631AF1-228 GEN
Solar/Wind Harmer
2.508
959331AF2-224 GEN
Solar/Wind Harmer
5.285
270404AC1-167 GEN
Solar/Wind Harmer
0.569
943861AF1-054 GEN
Solar/Wind Harmer
1.923
943851AF1-053 GEN
Solar/Wind Harmer
0.929
963791AG1-232 GEN
Solar/Wind Harmer
6.694
253338AC1-165 GEN
Solar/Wind Harmer
0.523
253343AC1-166 GEN
Solar/Wind Harmer
0.523
970031AG2-029 GEN
Solar/Wind Harmer
12.023
270071AF1-092 GEN
Solar/Wind Harmer
7.187
24729505KEY G4
Adder
3.068
25306009OHH W.
Adder
1.337
958711AF2-162 GEN
Solar/Wind Harmer
0.468
253372AE2-315 SEC3
Adder
0.876
253372AE2-315 SEC3
Adder
0.876
971771AH1-392 GEN
Solar/Wind Harmer
4.093
945581AF1-223 GEN
Solar/Wind Harmer
2.052
944161AF1-084 GEN
Solar/Wind Harmer
0.996
270526AF1-158 GEN
Solar/Wind Harmer
2.044
961761AG1-017 GEN
Solar/Wind Harmer
0.193
964611AG1-324 GEN
Solar/Wind Harmer
1.746
247536S-71 GEN
Solar/Wind Harmer
1.81
960681AF2-359 GEN
Solar/Wind Harmer
1.69
270543AE2-219 C
Solar/Wind Harmer
4.446
971029AG2-637 GEN
Solar/Wind Harmer
6.628
971549AH1-272 GEN
Solar/Wind Harmer
8.08
274775LINCOLN ;6U
Adder
2.7
274776LINCOLN ;7U
Adder
2.7
274777LINCOLN ;8U
Adder
2.7
970289AG2-191 GEN
Solar/Wind Harmer
0.822
972037AH1-567 GEN1
Adder
0.079
274827FISK ;RP
Adder
3.349
274800UNIV PARK;3U
Adder
2.515
274801UNIV PARK;4U
Adder
2.515
960591AF2-350 GEN
Solar/Wind Harmer
4.314
972228AH1-698 GEN2
Adder
1.596
972227AH1-698 GEN1
Adder
1.124
270475AD2-096_GEN
50/50
7.787
270466AD2-091
50/50
5.413
270349AD2-093_GEN
Solar/Wind Harmer
4.86
270471AD2-092_GEN
Solar/Wind Harmer
4.86
938701AE1-092 GEN
Solar/Wind Harmer
21.921
270462AD2-086
Solar/Wind Harmer
6.473
946101AF1-275 GEN
Solar/Wind Harmer
1.343
241960AC2-195 GEN
Solar/Wind Harmer
2.349
253378AE2-206_GEN
Solar/Wind Harmer
2.397
25326509SID D
Adder
0.837
246937BC-WTG2
Solar/Wind Harmer
2.344
942801AE2-298 GEN
Solar/Wind Harmer
0.858
247607V1-011 GEN
Solar/Wind Harmer
2.227
270246TR4_N_V150
Solar/Wind Harmer
0.469
270247TR4_N_V136
Solar/Wind Harmer
0.469
942861AE2-305 GEN
Solar/Wind Harmer
3.897
25326109MON D
Adder
0.652
944231AF1-091 GEN
Solar/Wind Harmer
8.771
25322209TAIT E
Adder
4.67
25322209TAIT E
Adder
4.565
942221AE2-234 GEN
Solar/Wind Harmer
1.648
253349AC2-067 GEN
Solar/Wind Harmer
0.957
253400AC2-068 GEN
Solar/Wind Harmer
0.385
247620Y3-023
Adder
0.214
944541AF1-119 GEN
Solar/Wind Harmer
1.936
960971AF2-388 GEN
Solar/Wind Harmer
5.055
253370AE2-315 SEC1
Adder
0.926
970349AG2-230 GEN
Solar/Wind Harmer
6.897
961051AF2-396 GEN
Solar/Wind Harmer
7.199
961051AF2-396 GEN
Solar/Wind Harmer
3.348
247621Y3-024
Adder
0.109
270201AC2-176 GEN
Solar/Wind Harmer
2.313
964611AG1-324 GEN
Solar/Wind Harmer
0.234
965681AG1-436 GEN
Solar/Wind Harmer
5.59
965791AG1-447 GEN
Solar/Wind Harmer
2.86
270031AE2-169
Solar/Wind Harmer
3.636
270599AE1-208 GEN
Solar/Wind Harmer
3.636
253383AE2-342_GEN
Solar/Wind Harmer
0.394
970883AG2-550 GEN
Solar/Wind Harmer
4.446
970885AG2-551 GEN
Solar/Wind Harmer
1.034
274770LINCOLN ;1U
Adder
2.7
274771LINCOLN ;2U
Adder
2.7
270535AF1-215 GEN1
Solar/Wind Harmer
1.971
270536AF1-215 GEN2
Solar/Wind Harmer
1.971
274805UNIV PK N;1U
Adder
2.177
274808UNIV PK N;4U
Adder
2.163
970291AG2-192 GEN
Solar/Wind Harmer
0.562
970291AG2-192 GEN
Solar/Wind Harmer
0.181
270383AD1-128 GEN
Solar/Wind Harmer
2.637
274888KELLY CRK;1U
Solar/Wind Harmer
2.545
276776AD2-060 GEN
Solar/Wind Harmer
0.181
958011AF2-095 GEN
Solar/Wind Harmer
6.212
970941AG2-585 GEN
Solar/Wind Harmer
2.372
270054AF2-122 C O1
Solar/Wind Helper
0.82
270286AF1-227 GEN2
Solar/Wind Harmer
2.523
971995AH1-542 GEN
Solar/Wind Harmer
11.763
270391AF1-285 GEN3
Solar/Wind Harmer
1.205
270578AF1-285 GEN2
Solar/Wind Harmer
1.205
270317AD1-130_GEN
Solar/Wind Harmer
2.98
270485AE1-090_GEN
Solar/Wind Harmer
0.563
270520AE2-214 GEN
Solar/Wind Harmer
5.371
241813AF1-122_GEN
Solar/Wind Harmer
4.152
971201AH1-060 GEN
Solar/Wind Harmer
1.298
962761AG1-125 GEN
Solar/Wind Harmer
20.836
970149AG2-104 GEN
Solar/Wind Harmer
12.866
970155AG2-107 GEN
Solar/Wind Harmer
9.086
246936BC-WTG1
Solar/Wind Harmer
2.344
270489AE1-102 GEN1
Solar/Wind Harmer
0.779
965421AG1-410 GEN
Solar/Wind Harmer
17.778
270297AD1-101 GEN
Solar/Wind Harmer
1.126
270258AD1-119 GEN
Solar/Wind Harmer
1.092
965011AG1-365 GEN
Solar/Wind Harmer
5.285
253333AC1-068 GEN
Solar/Wind Harmer
0.504
25326309TAIT D
Adder
0.525
270024AE2-089 GEN
Solar/Wind Harmer
2.191
965651AG1-433 GEN
Solar/Wind Harmer
2.527
253370AE2-315 SEC1
Adder
0.926
253371AE2-315 SEC2
Adder
0.876
24639705ELKHART HY
Adder
0.071
270216AD2-079_GEN
Solar/Wind Harmer
0.278
958861AF2-177 GEN
Solar/Wind Harmer
5.017
945111AF1-176 GEN
Solar/Wind Harmer
8.127
957891AF2-083 GEN
Solar/Wind Harmer
6.816
945371AF1-202 GEN
Solar/Wind Harmer
3.157
270449AD2-020 GEN
Solar/Wind Harmer
1.268
943021AE2-325 GEN
Solar/Wind Harmer
1.648
24441205WTRV SLR C
Solar/Wind Harmer
0.06
970373AG2-245 GEN
Solar/Wind Harmer
9.197
270005AE1-210 C O1
Solar/Wind Harmer
2.388
970825AG2-519 GEN
Solar/Wind Harmer
0.916
274751CRETE EC ;1U
Adder
2.13
274754CRETE EC ;4U
Adder
2.13
972207SS24-0001
Solar/Wind Harmer
9.599
274773LINCOLN ;4U
Adder
2.7
274774LINCOLN ;5U
Adder
2.7
274723RIVER EC ;12
Adder
7.802
270055AF2-134 C O1
Solar/Wind Harmer
1.314
274812UNIV PK N;8U
Adder
2.172
270594AE1-207 GEN
Solar/Wind Harmer
5.888
270032AE2-172
Solar/Wind Harmer
2.017
274802UNIV PARK;5U
Adder
2.518
958381AF2-132 GEN
Solar/Wind Harmer
3.91
270284AF1-227 GEN1
Solar/Wind Harmer
6.82
270287AF1-227 GEN3
Solar/Wind Harmer
2.523
942871AE2-306 GEN
Solar/Wind Harmer
0.904
270391AF1-285 GEN3
Solar/Wind Harmer
0.464
942051AE2-217 GEN
Solar/Wind Harmer
13.933
970065AG2-057 GEN
Solar/Wind Harmer
0.649
276820AF1-078_GEN
Solar/Wind Harmer
1.065
962771AG1-126 GEN
Solar/Wind Harmer
20.836
970153AG2-106 GEN
Solar/Wind Harmer
9.086
246938BC-WTG3
Solar/Wind Harmer
2.385
270491AE1-102 GEN2
Solar/Wind Harmer
0.779
958091AF2-103 GEN
Solar/Wind Harmer
0.091
24695305TIMB G C
Solar/Wind Harmer
1.826
965021AG1-366 GEN
Solar/Wind Harmer
1.229
270044AE2-322 C
Solar/Wind Harmer
0.691
270518AE2-148 GEN
Solar/Wind Harmer
6.247
270588AE1-091_GEN
Solar/Wind Harmer
5.492
270043AE2-236 GEN
Solar/Wind Harmer
2.697
253325AC1-069 GEN
Solar/Wind Harmer
0.504
960071AF2-298 GEN
Solar/Wind Harmer
0.728
270063AE2-323 C
Solar/Wind Harmer
1.049
944531AF1-118 GEN
Solar/Wind Harmer
16.688
270541AE2-072 C
Solar/Wind Harmer
2.152
253303V4-073 C
Solar/Wind Harmer
0.054
253370AE2-315 SEC1
Adder
0.926
253371AE2-315 SEC2
Adder
0.876
971347AH1-153 GEN
Solar/Wind Harmer
2.299
247643Z2-116 C
Solar/Wind Harmer
0.032
945111AF1-176 GEN
Solar/Wind Harmer
2.576
270505AE1-170 C O1
Solar/Wind Harmer
6.813
962031AG1-047 GEN
Solar/Wind Harmer
1.36
957741AF2-068 GEN
Solar/Wind Harmer
6.749
24441505OLIV SLR
Solar/Wind Harmer
0.06
946031AF1-268 GEN
Solar/Wind Harmer
3.645
270004AE1-209 GEN
Solar/Wind Harmer
2.388
970825AG2-519 GEN
Solar/Wind Harmer
2.461
972231SS25-0005
Solar/Wind Harmer
4.136
972181SS23-001
Solar/Wind Harmer
2.585
274752CRETE EC ;2U
Adder
2.13
274753CRETE EC ;3U
Adder
2.13
274772LINCOLN ;3U
Adder
2.7
274724RIVER EC ;11
Adder
7.711
276164X3-005 C
Solar/Wind Harmer
0.305
274814UNIV PK N;0U
Adder
2.191
274807UNIV PK N;3U
Adder
2.186
274811UNIV PK N;7U
Adder
2.172
965461AG1-414 GEN
Solar/Wind Harmer
0.981
970289AG2-191 GEN
Solar/Wind Harmer
0.332
274803UNIV PARK;6U
Adder
2.518
247642Z2-115 C
Solar/Wind Harmer
0.028
274826FISK ;BP
Adder
4.726
972038AH1-567 GEN2
Adder
0.157
274887GEN-1.85
Solar/Wind Harmer
2.298
276772AC2-154 GEN
Solar/Wind Harmer
1.204
276843GEN-1.7
Solar/Wind Harmer
0.247
276806AD2-047 C O1
Solar/Wind Harmer
4.615
964401AG1-302 GEN
Solar/Wind Harmer
3.91
972259AH1-714 GEN
Adder
8.216
970707AG2-453 GEN
Solar/Wind Harmer
11.058
CPLELTFEXP_CPLE->PJM
CLTF
0.338
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.624
NYPJM->LTFIMP_NY
CLTF
1.309
LGEELTFEXP_LGEE->PJM
CLTF
2.284
WECLTFEXP_WEC->PJM
CLTF
1.583
AG2-052LTFEXP_AG2-052->PJM
LTF
0.1
AH1-155LTFEXP_AH1-155->PJM
LTF
0.15
LAGNLTFEXP_LAGN->PJM
CLTF
5.087
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.315
TVALTFEXP_TVA->PJM
CLTF
2.36
CBM West 1LTFEXP_CBM-W1->PJM
CBM
56.165
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.515
MECLTFEXP_MEC->PJM
CLTF
6.298
SIGELTFEXP_SIGE->PJM
CLTF
0.181

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P4_#7222_05MALIS 765_D_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7222_05MALIS 765_D_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.36 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1484.58
MW Contribution:
12.81
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270036AE2-216 BAT
50/50
5.928
270223U2-072_GEN1
Solar/Wind Harmer
1.959
270224U2-072_GEN2
Solar/Wind Harmer
1.959
270227U2-072_GEN3
Solar/Wind Harmer
1.959
270228U2-072_GEN4
Solar/Wind Harmer
1.959
270231U2-072_GEN5
Solar/Wind Harmer
1.959
270578AF1-285 GEN2
Solar/Wind Harmer
0.462
241973AD2-163_GEN1
Solar/Wind Harmer
1.933
241974AD2-163_GEN2
Solar/Wind Harmer
1.933
270302AB2-170 GEN
Solar/Wind Harmer
7.76
970179AG2-119 GEN
Solar/Wind Harmer
6.743
241955AC1-078 GEN
Solar/Wind Harmer
4.963
957201AF2-014 GEN
Solar/Wind Harmer
2.707
270435AC2-044 GEN
Solar/Wind Harmer
1.194
241972AD1-140 GEN
Solar/Wind Harmer
2.551
270007AE1-245 C
Solar/Wind Harmer
3.03
247521TR3_G114
Solar/Wind Harmer
1.848
270191TR4_S_V150
Solar/Wind Harmer
1.649
965051AG1-369 GEN
Solar/Wind Harmer
2.745
965041AG1-368 GEN
Solar/Wind Harmer
5.334
945631AF1-228 GEN
Solar/Wind Harmer
2.5
959331AF2-224 GEN
Solar/Wind Harmer
5.263
270404AC1-167 GEN
Solar/Wind Harmer
0.567
963791AG1-232 GEN
Solar/Wind Harmer
6.667
943861AF1-054 GEN
Solar/Wind Harmer
1.9
943851AF1-053 GEN
Solar/Wind Harmer
0.918
253338AC1-165 GEN
Solar/Wind Harmer
0.521
253343AC1-166 GEN
Solar/Wind Harmer
0.521
970031AG2-029 GEN
Solar/Wind Harmer
11.974
270071AF1-092 GEN
Solar/Wind Harmer
7.157
24729505KEY G4
Adder
3.056
25306009OHH W.
Adder
1.331
958711AF2-162 GEN
Solar/Wind Harmer
0.466
253372AE2-315 SEC3
Adder
0.873
253372AE2-315 SEC3
Adder
0.873
971771AH1-392 GEN
Solar/Wind Harmer
4.076
945581AF1-223 GEN
Solar/Wind Harmer
2.044
944161AF1-084 GEN
Solar/Wind Harmer
0.992
270526AF1-158 GEN
Solar/Wind Harmer
2.036
961761AG1-017 GEN
Solar/Wind Harmer
0.192
964611AG1-324 GEN
Solar/Wind Harmer
1.739
247536S-71 GEN
Solar/Wind Harmer
1.803
960681AF2-359 GEN
Solar/Wind Harmer
1.683
270543AE2-219 C
Solar/Wind Harmer
4.428
971029AG2-637 GEN
Solar/Wind Harmer
6.602
971549AH1-272 GEN
Solar/Wind Harmer
8.047
274775LINCOLN ;6U
Adder
2.689
274776LINCOLN ;7U
Adder
2.689
274777LINCOLN ;8U
Adder
2.689
970289AG2-191 GEN
Solar/Wind Harmer
0.819
972037AH1-567 GEN1
Adder
0.079
270286AF1-227 GEN2
Solar/Wind Harmer
2.512
971995AH1-542 GEN
Solar/Wind Harmer
11.711
270391AF1-285 GEN3
Solar/Wind Harmer
1.2
270578AF1-285 GEN2
Solar/Wind Harmer
1.2
270317AD1-130_GEN
Solar/Wind Harmer
2.967
270485AE1-090_GEN
Solar/Wind Harmer
0.56
270520AE2-214 GEN
Solar/Wind Harmer
5.342
241813AF1-122_GEN
Solar/Wind Harmer
4.135
971201AH1-060 GEN
Solar/Wind Harmer
1.292
962761AG1-125 GEN
Solar/Wind Harmer
20.746
970149AG2-104 GEN
Solar/Wind Harmer
12.811
970155AG2-107 GEN
Solar/Wind Harmer
9.046
246936BC-WTG1
Solar/Wind Harmer
2.335
270489AE1-102 GEN1
Solar/Wind Harmer
0.776
965421AG1-410 GEN
Solar/Wind Harmer
17.703
270297AD1-101 GEN
Solar/Wind Harmer
1.121
270258AD1-119 GEN
Solar/Wind Harmer
1.088
965011AG1-365 GEN
Solar/Wind Harmer
5.263
253333AC1-068 GEN
Solar/Wind Harmer
0.503
25326309TAIT D
Adder
0.523
270024AE2-089 GEN
Solar/Wind Harmer
2.182
965651AG1-433 GEN
Solar/Wind Harmer
2.517
253370AE2-315 SEC1
Adder
0.922
253371AE2-315 SEC2
Adder
0.873
24639705ELKHART HY
Adder
0.071
270216AD2-079_GEN
Solar/Wind Harmer
0.277
958861AF2-177 GEN
Solar/Wind Harmer
4.997
945111AF1-176 GEN
Solar/Wind Harmer
8.094
957891AF2-083 GEN
Solar/Wind Harmer
6.788
945371AF1-202 GEN
Solar/Wind Harmer
3.144
270449AD2-020 GEN
Solar/Wind Harmer
1.263
943021AE2-325 GEN
Solar/Wind Harmer
1.641
24441205WTRV SLR C
Solar/Wind Harmer
0.06
970373AG2-245 GEN
Solar/Wind Harmer
9.16
270005AE1-210 C O1
Solar/Wind Harmer
2.379
970825AG2-519 GEN
Solar/Wind Harmer
0.913
274751CRETE EC ;1U
Adder
2.121
274754CRETE EC ;4U
Adder
2.121
972207SS24-0001
Solar/Wind Harmer
9.56
274773LINCOLN ;4U
Adder
2.689
274774LINCOLN ;5U
Adder
2.689
274723RIVER EC ;12
Adder
7.77
270055AF2-134 C O1
Solar/Wind Harmer
1.309
274812UNIV PK N;8U
Adder
2.163
270594AE1-207 GEN
Solar/Wind Harmer
5.865
270032AE2-172
Solar/Wind Harmer
2.008
274802UNIV PARK;5U
Adder
2.508
270475AD2-096_GEN
50/50
7.753
270284AF1-227 GEN1
Solar/Wind Harmer
6.79
270287AF1-227 GEN3
Solar/Wind Harmer
2.512
942871AE2-306 GEN
Solar/Wind Harmer
0.9
270391AF1-285 GEN3
Solar/Wind Harmer
0.462
942051AE2-217 GEN
Solar/Wind Harmer
13.86
970065AG2-057 GEN
Solar/Wind Harmer
0.646
276820AF1-078_GEN
Solar/Wind Harmer
1.059
962771AG1-126 GEN
Solar/Wind Harmer
20.746
270466AD2-091
50/50
5.389
270349AD2-093_GEN
Solar/Wind Harmer
4.839
270471AD2-092_GEN
Solar/Wind Harmer
4.839
938701AE1-092 GEN
Solar/Wind Harmer
21.815
270462AD2-086
Solar/Wind Harmer
6.445
946101AF1-275 GEN
Solar/Wind Harmer
1.336
241960AC2-195 GEN
Solar/Wind Harmer
2.339
253378AE2-206_GEN
Solar/Wind Harmer
2.385
25326509SID D
Adder
0.833
246937BC-WTG2
Solar/Wind Harmer
2.335
942801AE2-298 GEN
Solar/Wind Harmer
0.854
247607V1-011 GEN
Solar/Wind Harmer
2.218
270246TR4_N_V150
Solar/Wind Harmer
0.468
270247TR4_N_V136
Solar/Wind Harmer
0.468
942861AE2-305 GEN
Solar/Wind Harmer
3.849
25326109MON D
Adder
0.649
944231AF1-091 GEN
Solar/Wind Harmer
8.735
25322209TAIT E
Adder
4.65
25322209TAIT E
Adder
4.546
942221AE2-234 GEN
Solar/Wind Harmer
1.641
253349AC2-067 GEN
Solar/Wind Harmer
0.953
253400AC2-068 GEN
Solar/Wind Harmer
0.383
247620Y3-023
Adder
0.213
944541AF1-119 GEN
Solar/Wind Harmer
1.928
960971AF2-388 GEN
Solar/Wind Harmer
5.034
253370AE2-315 SEC1
Adder
0.922
970349AG2-230 GEN
Solar/Wind Harmer
6.869
961051AF2-396 GEN
Solar/Wind Harmer
7.17
961051AF2-396 GEN
Solar/Wind Harmer
3.335
247621Y3-024
Adder
0.108
270201AC2-176 GEN
Solar/Wind Harmer
2.303
964611AG1-324 GEN
Solar/Wind Harmer
0.233
965681AG1-436 GEN
Solar/Wind Harmer
5.567
965791AG1-447 GEN
Solar/Wind Harmer
2.848
270031AE2-169
Solar/Wind Harmer
3.621
270599AE1-208 GEN
Solar/Wind Harmer
3.621
970883AG2-550 GEN
Solar/Wind Harmer
4.428
970885AG2-551 GEN
Solar/Wind Harmer
1.03
253383AE2-342_GEN
Solar/Wind Harmer
0.387
274770LINCOLN ;1U
Adder
2.689
274771LINCOLN ;2U
Adder
2.689
270535AF1-215 GEN1
Solar/Wind Harmer
1.963
270536AF1-215 GEN2
Solar/Wind Harmer
1.963
274805UNIV PK N;1U
Adder
2.168
274808UNIV PK N;4U
Adder
2.154
970291AG2-192 GEN
Solar/Wind Harmer
0.56
970291AG2-192 GEN
Solar/Wind Harmer
0.18
270383AD1-128 GEN
Solar/Wind Harmer
2.627
270054AF2-122 C O1
Solar/Wind Helper
0.81
970153AG2-106 GEN
Solar/Wind Harmer
9.046
246938BC-WTG3
Solar/Wind Harmer
2.375
270491AE1-102 GEN2
Solar/Wind Harmer
0.776
958091AF2-103 GEN
Solar/Wind Harmer
0.091
24695305TIMB G C
Solar/Wind Harmer
1.818
965021AG1-366 GEN
Solar/Wind Harmer
1.224
270044AE2-322 C
Solar/Wind Harmer
0.688
270518AE2-148 GEN
Solar/Wind Harmer
6.224
270588AE1-091_GEN
Solar/Wind Harmer
5.471
270043AE2-236 GEN
Solar/Wind Harmer
2.686
253325AC1-069 GEN
Solar/Wind Harmer
0.503
960071AF2-298 GEN
Solar/Wind Harmer
0.725
270063AE2-323 C
Solar/Wind Harmer
1.045
944531AF1-118 GEN
Solar/Wind Harmer
16.62
270541AE2-072 C
Solar/Wind Harmer
2.143
253303V4-073 C
Solar/Wind Harmer
0.053
253370AE2-315 SEC1
Adder
0.922
253371AE2-315 SEC2
Adder
0.873
971347AH1-153 GEN
Solar/Wind Harmer
2.29
247643Z2-116 C
Solar/Wind Harmer
0.032
945111AF1-176 GEN
Solar/Wind Harmer
2.565
270505AE1-170 C O1
Solar/Wind Harmer
6.785
962031AG1-047 GEN
Solar/Wind Harmer
1.355
957741AF2-068 GEN
Solar/Wind Harmer
6.722
24441505OLIV SLR
Solar/Wind Harmer
0.06
946031AF1-268 GEN
Solar/Wind Harmer
3.631
270004AE1-209 GEN
Solar/Wind Harmer
2.379
970825AG2-519 GEN
Solar/Wind Harmer
2.451
972231SS25-0005
Solar/Wind Harmer
4.119
972181SS23-001
Solar/Wind Harmer
2.574
274752CRETE EC ;2U
Adder
2.121
274753CRETE EC ;3U
Adder
2.121
274772LINCOLN ;3U
Adder
2.689
274724RIVER EC ;11
Adder
7.679
276164X3-005 C
Solar/Wind Harmer
0.304
274814UNIV PK N;0U
Adder
2.182
274807UNIV PK N;3U
Adder
2.178
274811UNIV PK N;7U
Adder
2.163
965461AG1-414 GEN
Solar/Wind Harmer
0.977
970289AG2-191 GEN
Solar/Wind Harmer
0.331
247642Z2-115 C
Solar/Wind Harmer
0.028
274803UNIV PARK;6U
Adder
2.508
CPLELTFEXP_CPLE->PJM
CLTF
0.337
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.469
NYPJM->LTFIMP_NY
CLTF
1.304
LGEELTFEXP_LGEE->PJM
CLTF
2.276
WECLTFEXP_WEC->PJM
CLTF
1.577
AG2-052LTFEXP_AG2-052->PJM
LTF
0.1
AH1-155LTFEXP_AH1-155->PJM
LTF
0.149
LAGNLTFEXP_LAGN->PJM
CLTF
5.068
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.308
TVALTFEXP_TVA->PJM
CLTF
2.351
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.942
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.48
MECLTFEXP_MEC->PJM
CLTF
6.274
SIGELTFEXP_SIGE->PJM
CLTF
0.18

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P2-2_#7222_05MALIS 765_1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:105.35 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1484.33
MW Contribution:
12.81
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270466AD2-091
50/50
5.389
270349AD2-093_GEN
Solar/Wind Harmer
4.839
270471AD2-092_GEN
Solar/Wind Harmer
4.839
938701AE1-092 GEN
Solar/Wind Harmer
21.815
270462AD2-086
Solar/Wind Harmer
6.445
946101AF1-275 GEN
Solar/Wind Harmer
1.336
241960AC2-195 GEN
Solar/Wind Harmer
2.339
253378AE2-206_GEN
Solar/Wind Harmer
2.385
25326509SID D
Adder
0.833
246937BC-WTG2
Solar/Wind Harmer
2.335
942801AE2-298 GEN
Solar/Wind Harmer
0.854
247607V1-011 GEN
Solar/Wind Harmer
2.218
270246TR4_N_V150
Solar/Wind Harmer
0.468
270247TR4_N_V136
Solar/Wind Harmer
0.468
942861AE2-305 GEN
Solar/Wind Harmer
3.849
25326109MON D
Adder
0.649
944231AF1-091 GEN
Solar/Wind Harmer
8.735
25322209TAIT E
Adder
4.65
25322209TAIT E
Adder
4.546
942221AE2-234 GEN
Solar/Wind Harmer
1.641
253349AC2-067 GEN
Solar/Wind Harmer
0.953
253400AC2-068 GEN
Solar/Wind Harmer
0.383
247620Y3-023
Adder
0.213
944541AF1-119 GEN
Solar/Wind Harmer
1.928
960971AF2-388 GEN
Solar/Wind Harmer
5.034
253370AE2-315 SEC1
Adder
0.922
970349AG2-230 GEN
Solar/Wind Harmer
6.869
961051AF2-396 GEN
Solar/Wind Harmer
7.17
961051AF2-396 GEN
Solar/Wind Harmer
3.335
247621Y3-024
Adder
0.108
270201AC2-176 GEN
Solar/Wind Harmer
2.303
964611AG1-324 GEN
Solar/Wind Harmer
0.233
965681AG1-436 GEN
Solar/Wind Harmer
5.567
965791AG1-447 GEN
Solar/Wind Harmer
2.848
270031AE2-169
Solar/Wind Harmer
3.621
270599AE1-208 GEN
Solar/Wind Harmer
3.621
970883AG2-550 GEN
Solar/Wind Harmer
4.428
970885AG2-551 GEN
Solar/Wind Harmer
1.03
253383AE2-342_GEN
Solar/Wind Harmer
0.387
274770LINCOLN ;1U
Adder
2.689
274771LINCOLN ;2U
Adder
2.689
270535AF1-215 GEN1
Solar/Wind Harmer
1.963
270536AF1-215 GEN2
Solar/Wind Harmer
1.963
274805UNIV PK N;1U
Adder
2.168
274808UNIV PK N;4U
Adder
2.154
970291AG2-192 GEN
Solar/Wind Harmer
0.56
970291AG2-192 GEN
Solar/Wind Harmer
0.18
270383AD1-128 GEN
Solar/Wind Harmer
2.627
270054AF2-122 C O1
Solar/Wind Helper
0.81
270036AE2-216 BAT
50/50
5.928
270223U2-072_GEN1
Solar/Wind Harmer
1.959
270224U2-072_GEN2
Solar/Wind Harmer
1.959
270227U2-072_GEN3
Solar/Wind Harmer
1.959
270228U2-072_GEN4
Solar/Wind Harmer
1.959
270231U2-072_GEN5
Solar/Wind Harmer
1.959
270578AF1-285 GEN2
Solar/Wind Harmer
0.462
241973AD2-163_GEN1
Solar/Wind Harmer
1.933
241974AD2-163_GEN2
Solar/Wind Harmer
1.933
270302AB2-170 GEN
Solar/Wind Harmer
7.76
970179AG2-119 GEN
Solar/Wind Harmer
6.743
241955AC1-078 GEN
Solar/Wind Harmer
4.963
957201AF2-014 GEN
Solar/Wind Harmer
2.707
270435AC2-044 GEN
Solar/Wind Harmer
1.194
241972AD1-140 GEN
Solar/Wind Harmer
2.551
270007AE1-245 C
Solar/Wind Harmer
3.03
247521TR3_G114
Solar/Wind Harmer
1.848
270191TR4_S_V150
Solar/Wind Harmer
1.649
965051AG1-369 GEN
Solar/Wind Harmer
2.745
965041AG1-368 GEN
Solar/Wind Harmer
5.334
945631AF1-228 GEN
Solar/Wind Harmer
2.5
959331AF2-224 GEN
Solar/Wind Harmer
5.263
270404AC1-167 GEN
Solar/Wind Harmer
0.567
963791AG1-232 GEN
Solar/Wind Harmer
6.667
943861AF1-054 GEN
Solar/Wind Harmer
1.9
943851AF1-053 GEN
Solar/Wind Harmer
0.918
253338AC1-165 GEN
Solar/Wind Harmer
0.521
253343AC1-166 GEN
Solar/Wind Harmer
0.521
970031AG2-029 GEN
Solar/Wind Harmer
11.974
270071AF1-092 GEN
Solar/Wind Harmer
7.157
24729505KEY G4
Adder
3.056
25306009OHH W.
Adder
1.331
958711AF2-162 GEN
Solar/Wind Harmer
0.466
253372AE2-315 SEC3
Adder
0.873
253372AE2-315 SEC3
Adder
0.873
971771AH1-392 GEN
Solar/Wind Harmer
4.076
945581AF1-223 GEN
Solar/Wind Harmer
2.044
944161AF1-084 GEN
Solar/Wind Harmer
0.992
270526AF1-158 GEN
Solar/Wind Harmer
2.036
961761AG1-017 GEN
Solar/Wind Harmer
0.192
964611AG1-324 GEN
Solar/Wind Harmer
1.739
247536S-71 GEN
Solar/Wind Harmer
1.803
960681AF2-359 GEN
Solar/Wind Harmer
1.683
270543AE2-219 C
Solar/Wind Harmer
4.428
971029AG2-637 GEN
Solar/Wind Harmer
6.602
971549AH1-272 GEN
Solar/Wind Harmer
8.047
274775LINCOLN ;6U
Adder
2.689
274776LINCOLN ;7U
Adder
2.689
274777LINCOLN ;8U
Adder
2.689
970289AG2-191 GEN
Solar/Wind Harmer
0.819
972037AH1-567 GEN1
Adder
0.079
270475AD2-096_GEN
50/50
7.753
270284AF1-227 GEN1
Solar/Wind Harmer
6.79
270287AF1-227 GEN3
Solar/Wind Harmer
2.512
942871AE2-306 GEN
Solar/Wind Harmer
0.9
270391AF1-285 GEN3
Solar/Wind Harmer
0.462
942051AE2-217 GEN
Solar/Wind Harmer
13.86
970065AG2-057 GEN
Solar/Wind Harmer
0.646
276820AF1-078_GEN
Solar/Wind Harmer
1.059
962771AG1-126 GEN
Solar/Wind Harmer
20.746
970153AG2-106 GEN
Solar/Wind Harmer
9.046
246938BC-WTG3
Solar/Wind Harmer
2.375
270491AE1-102 GEN2
Solar/Wind Harmer
0.776
958091AF2-103 GEN
Solar/Wind Harmer
0.091
24695305TIMB G C
Solar/Wind Harmer
1.818
965021AG1-366 GEN
Solar/Wind Harmer
1.224
270044AE2-322 C
Solar/Wind Harmer
0.688
270518AE2-148 GEN
Solar/Wind Harmer
6.224
270588AE1-091_GEN
Solar/Wind Harmer
5.471
270043AE2-236 GEN
Solar/Wind Harmer
2.686
253325AC1-069 GEN
Solar/Wind Harmer
0.503
960071AF2-298 GEN
Solar/Wind Harmer
0.725
270063AE2-323 C
Solar/Wind Harmer
1.045
944531AF1-118 GEN
Solar/Wind Harmer
16.62
270541AE2-072 C
Solar/Wind Harmer
2.143
253303V4-073 C
Solar/Wind Harmer
0.053
253370AE2-315 SEC1
Adder
0.922
253371AE2-315 SEC2
Adder
0.873
971347AH1-153 GEN
Solar/Wind Harmer
2.29
247643Z2-116 C
Solar/Wind Harmer
0.032
945111AF1-176 GEN
Solar/Wind Harmer
2.565
270505AE1-170 C O1
Solar/Wind Harmer
6.785
962031AG1-047 GEN
Solar/Wind Harmer
1.355
957741AF2-068 GEN
Solar/Wind Harmer
6.722
24441505OLIV SLR
Solar/Wind Harmer
0.06
946031AF1-268 GEN
Solar/Wind Harmer
3.631
270004AE1-209 GEN
Solar/Wind Harmer
2.379
970825AG2-519 GEN
Solar/Wind Harmer
2.451
972231SS25-0005
Solar/Wind Harmer
4.119
972181SS23-001
Solar/Wind Harmer
2.574
274752CRETE EC ;2U
Adder
2.121
274753CRETE EC ;3U
Adder
2.121
274772LINCOLN ;3U
Adder
2.689
274724RIVER EC ;11
Adder
7.679
276164X3-005 C
Solar/Wind Harmer
0.304
274814UNIV PK N;0U
Adder
2.182
274807UNIV PK N;3U
Adder
2.178
274811UNIV PK N;7U
Adder
2.163
965461AG1-414 GEN
Solar/Wind Harmer
0.977
970289AG2-191 GEN
Solar/Wind Harmer
0.331
247642Z2-115 C
Solar/Wind Harmer
0.028
274803UNIV PARK;6U
Adder
2.508
270286AF1-227 GEN2
Solar/Wind Harmer
2.512
971995AH1-542 GEN
Solar/Wind Harmer
11.711
270391AF1-285 GEN3
Solar/Wind Harmer
1.2
270578AF1-285 GEN2
Solar/Wind Harmer
1.2
270317AD1-130_GEN
Solar/Wind Harmer
2.967
270485AE1-090_GEN
Solar/Wind Harmer
0.56
270520AE2-214 GEN
Solar/Wind Harmer
5.342
241813AF1-122_GEN
Solar/Wind Harmer
4.135
971201AH1-060 GEN
Solar/Wind Harmer
1.292
962761AG1-125 GEN
Solar/Wind Harmer
20.746
970149AG2-104 GEN
Solar/Wind Harmer
12.811
970155AG2-107 GEN
Solar/Wind Harmer
9.046
246936BC-WTG1
Solar/Wind Harmer
2.335
270489AE1-102 GEN1
Solar/Wind Harmer
0.776
965421AG1-410 GEN
Solar/Wind Harmer
17.703
270297AD1-101 GEN
Solar/Wind Harmer
1.121
270258AD1-119 GEN
Solar/Wind Harmer
1.088
965011AG1-365 GEN
Solar/Wind Harmer
5.263
253333AC1-068 GEN
Solar/Wind Harmer
0.503
25326309TAIT D
Adder
0.523
270024AE2-089 GEN
Solar/Wind Harmer
2.182
965651AG1-433 GEN
Solar/Wind Harmer
2.517
253370AE2-315 SEC1
Adder
0.922
253371AE2-315 SEC2
Adder
0.873
24639705ELKHART HY
Adder
0.071
270216AD2-079_GEN
Solar/Wind Harmer
0.277
958861AF2-177 GEN
Solar/Wind Harmer
4.997
945111AF1-176 GEN
Solar/Wind Harmer
8.094
957891AF2-083 GEN
Solar/Wind Harmer
6.788
945371AF1-202 GEN
Solar/Wind Harmer
3.144
270449AD2-020 GEN
Solar/Wind Harmer
1.263
943021AE2-325 GEN
Solar/Wind Harmer
1.641
24441205WTRV SLR C
Solar/Wind Harmer
0.06
970373AG2-245 GEN
Solar/Wind Harmer
9.16
270005AE1-210 C O1
Solar/Wind Harmer
2.379
970825AG2-519 GEN
Solar/Wind Harmer
0.913
274751CRETE EC ;1U
Adder
2.121
274754CRETE EC ;4U
Adder
2.121
972207SS24-0001
Solar/Wind Harmer
9.56
274773LINCOLN ;4U
Adder
2.689
274774LINCOLN ;5U
Adder
2.689
274723RIVER EC ;12
Adder
7.77
270055AF2-134 C O1
Solar/Wind Harmer
1.309
274812UNIV PK N;8U
Adder
2.163
270594AE1-207 GEN
Solar/Wind Harmer
5.865
270032AE2-172
Solar/Wind Harmer
2.008
274802UNIV PARK;5U
Adder
2.508
CPLELTFEXP_CPLE->PJM
CLTF
0.337
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.469
NYPJM->LTFIMP_NY
CLTF
1.304
LGEELTFEXP_LGEE->PJM
CLTF
2.276
WECLTFEXP_WEC->PJM
CLTF
1.577
AG2-052LTFEXP_AG2-052->PJM
LTF
0.1
AH1-155LTFEXP_AH1-155->PJM
LTF
0.149
LAGNLTFEXP_LAGN->PJM
CLTF
5.068
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.308
TVALTFEXP_TVA->PJM
CLTF
2.351
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.942
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.48
MECLTFEXP_MEC->PJM
CLTF
6.274
SIGELTFEXP_SIGE->PJM
CLTF
0.18

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-024_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:135.56 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5140.38
MW Contribution:
25.33
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
7.109
270120AB2-067 GEN2
50/50
7.109
24318905MLG2
50/50
7.027
270349AD2-093_GEN
Solar/Wind Harmer
4.455
270471AD2-092_GEN
Solar/Wind Harmer
4.455
270054AF2-122 C O1
Solar/Wind Harmer
3.972
946101AF1-275 GEN
Solar/Wind Harmer
1.811
253383AE2-342_GEN
Solar/Wind Harmer
1.04
942861AE2-305 GEN
Solar/Wind Harmer
9.069
938701AE1-092 GEN
Solar/Wind Harmer
23.766
270462AD2-086
Solar/Wind Harmer
7.908
270269AC2-059
Solar/Wind Harmer
10.571
253378AE2-206_GEN
Solar/Wind Harmer
3.997
972159AH1-661 GEN
Adder
1.106
253415AE1-040 GEN
Solar/Wind Harmer
1.242
25326509SID D
Adder
1.451
241960AC2-195 GEN
Solar/Wind Harmer
3.055
971073AG2-665 GEN
Solar/Wind Harmer
8.771
970879AG2-548 GEN
Solar/Wind Harmer
1.275
25326109MON D
Adder
1.442
25322209TAIT E
Adder
10.635
25322209TAIT E
Adder
10.396
253370AE2-315 SEC1
Adder
2.18
927014AC1-188 GEN
Solar/Wind Harmer
1.717
253349AC2-067 GEN
Solar/Wind Harmer
2.203
253400AC2-068 GEN
Solar/Wind Harmer
0.886
246937BC-WTG2
Solar/Wind Harmer
4.216
270246TR4_N_V150
Solar/Wind Harmer
0.912
270247TR4_N_V136
Solar/Wind Harmer
0.912
942801AE2-298 GEN
Solar/Wind Harmer
1.621
247607V1-011 GEN
Solar/Wind Harmer
4.231
270459AD2-067 GEN
Solar/Wind Harmer
10.212
961821AG1-024 GEN
Solar/Wind Harmer
10.368
972239AH1-704 GEN
Adder
2.66
241955AC1-078 GEN
Solar/Wind Harmer
8.781
241973AD2-163_GEN1
Solar/Wind Harmer
2.319
241974AD2-163_GEN2
Solar/Wind Harmer
2.319
943861AF1-054 GEN
Solar/Wind Harmer
4.476
943851AF1-053 GEN
Solar/Wind Harmer
2.163
945631AF1-228 GEN
Solar/Wind Harmer
5.449
270223U2-072_GEN1
Solar/Wind Harmer
2.274
270224U2-072_GEN2
Solar/Wind Harmer
2.274
270227U2-072_GEN3
Solar/Wind Harmer
2.274
270228U2-072_GEN4
Solar/Wind Harmer
2.274
270231U2-072_GEN5
Solar/Wind Harmer
2.274
270578AF1-285 GEN2
Solar/Wind Harmer
0.536
270432AC2-029 GEN
Solar/Wind Harmer
8.025
253338AC1-165 GEN
Solar/Wind Harmer
1.235
253343AC1-166 GEN
Solar/Wind Harmer
1.235
270302AB2-170 GEN
Solar/Wind Harmer
9.522
940611AE2-048 GEN
Solar/Wind Harmer
24.76
941391AE2-136 GEN
Solar/Wind Harmer
12.83
270263AC1-001 GEN
Solar/Wind Harmer
1.17
241972AD1-140 GEN
Solar/Wind Harmer
5.01
270291AC1-194 GEN
Solar/Wind Harmer
5.61
270340AC2-060 GEN
Solar/Wind Harmer
3.331
970179AG2-119 GEN
Solar/Wind Harmer
8.806
253372AE2-315 SEC3
Adder
2.062
253372AE2-315 SEC3
Adder
2.062
25306009OHH W.
Adder
3.128
253406AD2-031_GEN
Solar/Wind Harmer
1.383
957201AF2-014 GEN
Solar/Wind Harmer
4.888
270435AC2-044 GEN
Solar/Wind Harmer
2.156
253433AC1-085 GEN1
Solar/Wind Harmer
5.708
253432AC1-085 GEN2
Solar/Wind Harmer
0.287
247521TR3_G114
Solar/Wind Harmer
3.604
270191TR4_S_V150
Solar/Wind Harmer
3.216
962581AG1-107 GEN
Solar/Wind Harmer
5.356
961491AF2-440 GEN
Solar/Wind Harmer
2.226
25183208HLCRTG
Solar/Wind Harmer
6.427
944541AF1-119 GEN
Solar/Wind Harmer
4.444
960971AF2-388 GEN
Solar/Wind Harmer
11.601
942221AE2-234 GEN
Solar/Wind Harmer
3.71
25194408D.CRK1
Adder
8
25194508D.CRK3
Adder
1.496
252509AD1-136 GEN
Solar/Wind Harmer
0.27
970883AG2-550 GEN
Solar/Wind Harmer
10.561
970885AG2-551 GEN
Solar/Wind Harmer
2.456
247621Y3-024
Adder
0.255
270201AC2-176 GEN
Solar/Wind Harmer
5.42
964611AG1-324 GEN
Solar/Wind Harmer
0.551
970349AG2-230 GEN
Solar/Wind Harmer
15.797
270031AE2-169
Solar/Wind Harmer
8.576
270599AE1-208 GEN
Solar/Wind Harmer
8.576
270383AD1-128 GEN
Solar/Wind Harmer
6.419
926881AC1-175 GEN
Solar/Wind Harmer
5.862
247620Y3-023
Adder
0.483
944231AF1-091 GEN
Solar/Wind Harmer
18.887
24728805RICHG1
Adder
3.96
24728905RICHG2
Adder
3.96
274770LINCOLN ;1U
Adder
8.673
274771LINCOLN ;2U
Adder
8.673
274805UNIV PK N;1U
Adder
5.149
274808UNIV PK N;4U
Adder
5.115
274674JOLIET 9 ;6U
Adder
15.699
274696ROCKY RD ;4P
Adder
11.533
274695ROCKY RD ;2P
Adder
11.267
274693ROCKY RD ;1P
Adder
11.156
274697ROCKY RD ;3P
Adder
3.061
274683WAUKEGAN ;8U
Adder
21.305
274683WAUKEGAN ;8U
Adder
9.68
316097T157 G90
Solar/Wind Helper
1.515
235054AD2-180 GEN
Solar/Wind Helper
2.054
23585401KL_K28_T16
Solar/Wind Helper
1.5
235531U2-073 GEN
Solar/Wind Helper
3.347
238117U2-030
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.501
238148AE2-230_GEN2
Solar/Wind Helper
0.501
238149AF1-291A_GEN
Solar/Wind Helper
0.143
23751201ROTHROCK
Solar/Wind Helper
0.836
235020AA1-095 C
Solar/Wind Helper
0.054
237061AD1-155 GEN
Solar/Wind Helper
1.772
238221AF1-254 C O1
Solar/Wind Helper
0.278
237080AD1-060 GEN
Solar/Wind Helper
0.346
235062AE1-101 C1
Solar/Wind Helper
1.678
316411AF1-147_GEN1
Solar/Wind Helper
0.898
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.371
223402AF1-300 C
Solar/Wind Helper
0.371
316006AB2-029 C
Solar/Wind Helper
0.119
233930AB2-032 GEN
Solar/Wind Helper
0.385
232424Y1-079 C
Solar/Wind Helper
0.118
233982AB2-133 GEN
Solar/Wind Helper
0.363
232436AB1-176 C
Solar/Wind Helper
0.045
233946AB2-136 GEN
Solar/Wind Helper
0.575
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.972
232428Y3-058 C
Solar/Wind Helper
0.342
232410W1-006 C
Solar/Wind Helper
0.513
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.235
233954AC2-188 GEN
Solar/Wind Helper
0.235
230511AF1-262
Solar/Wind Helper
0.015
316045AC1-158 PL2
Solar/Wind Helper
4.182
316450AC1-158 RIC
Solar/Wind Helper
0.348
230433AD2-135 GEN
Solar/Wind Helper
0.017
228754AB1-001 C
Solar/Wind Helper
0.026
219904AC1-010 C
Solar/Wind Helper
0.061
219912AD2-042 GEN
Solar/Wind Helper
0.151
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219906AC1-017 C
Solar/Wind Helper
0.042
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.133
214067T20SOLAR
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.064
207459AE1-142 C O1
Solar/Wind Helper
0.293
20714828MDF_W3-079
Solar/Wind Helper
0.132
20742028HF_AC1-207
Solar/Wind Helper
0.142
965051AG1-369 GEN
Solar/Wind Harmer
5.355
959331AF2-224 GEN
Solar/Wind Harmer
10.725
270377AD1-106 GEN
Solar/Wind Harmer
5.62
270007AE1-245 C
Solar/Wind Harmer
5.779
965041AG1-368 GEN
Solar/Wind Harmer
10.701
24729505KEY G4
Adder
6.914
966831AG1-554 GEN
Solar/Wind Harmer
1.275
971567AH1-282 GEN
Solar/Wind Harmer
5.316
270071AF1-092 GEN
Solar/Wind Harmer
15.971
963791AG1-232 GEN
Solar/Wind Harmer
14.371
971985AH1-537 GEN
Solar/Wind Harmer
18.964
958711AF2-162 GEN
Solar/Wind Harmer
1.074
25196408WSDLE3
Adder
9.339
25196308WSDLE2
Adder
9.258
25196208WSDLE1
Adder
9.235
25196708WSDLE6
Adder
9.211
25196508WSDLE4
Adder
8.979
945581AF1-223 GEN
Solar/Wind Harmer
4.795
971029AG2-637 GEN
Solar/Wind Harmer
15.851
970031AG2-029 GEN
Solar/Wind Harmer
26.415
270404AC1-167 GEN
Solar/Wind Harmer
1.144
270543AE2-219 C
Solar/Wind Harmer
10.561
247536S-71 GEN
Solar/Wind Harmer
4.271
961761AG1-017 GEN
Solar/Wind Harmer
0.451
964611AG1-324 GEN
Solar/Wind Harmer
4.11
25196108MFTGT2
Adder
1.598
25196108MFTGT2
Adder
1.484
274775LINCOLN ;6U
Adder
8.673
274776LINCOLN ;7U
Adder
8.673
274777LINCOLN ;8U
Adder
8.673
972037AH1-567 GEN1
Adder
0.187
274827FISK ;RP
Adder
7.938
274800UNIV PARK;3U
Adder
5.964
274801UNIV PARK;4U
Adder
5.964
972228AH1-698 GEN2
Adder
3.789
972227AH1-698 GEN1
Adder
2.668
274687WILL CNTY;4U
Adder
28.512
274687WILL CNTY;4U
Adder
28.512
274675JOLIET 29;7U
Adder
31.291
274675JOLIET 29;7U
Adder
30.174
274728ELWOOD EC;5P
Adder
16.762
274731ELWOOD EC;2P
Adder
16.762
274733ELWOOD EC;3P
Adder
16.762
274735ELWOOD EC;4P
Adder
16.762
274744AC1-111 GEN8
Adder
5.677
274746AC1-111 G10
Adder
5.677
23750701CROSSCHOOL
Solar/Wind Helper
1.517
238118U2-030_1
Solar/Wind Helper
0.345
238169AE2-226 GEN1
Solar/Wind Helper
0.708
238170AE2-226 GEN2
Solar/Wind Helper
0.708
23779801AA1-109
Solar/Wind Helper
0.195
3138216PACIFIC
Solar/Wind Helper
0.045
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.166
23750501ELLIOTTS
Solar/Wind Helper
0.647
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.372
959381AF2-229 GEN
Solar/Wind Helper
0.36
20390526W1-045 C
Solar/Wind Helper
0.354
3141426STAFORD
Solar/Wind Helper
0.053
205943AE1-185 GEN
Solar/Wind Helper
0.515
205956AE1-196_GEN
Solar/Wind Helper
0.514
233915AB1-141 GEN
Solar/Wind Helper
0.508
233940AF2-379 C
Solar/Wind Helper
0.063
233901CHERRYDALE C
Solar/Wind Helper
0.235
232432Z2-076 GEN
Solar/Wind Helper
0.068
315651AD1-115 GEN
Solar/Wind Helper
0.795
230434AG1-499 GEN
Solar/Wind Helper
0.232
228728W1-130C
Solar/Wind Helper
0.055
230407AD2-065 C
Solar/Wind Helper
0.041
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.078
219615MILLCREEK C
Solar/Wind Helper
0.027
20715028HAN_X4-015
Solar/Wind Helper
0.058
20720728JCB_W1-129
Solar/Wind Helper
0.058
207445AB1-138_GEN
Solar/Wind Helper
0.106
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.192
316164AC1-076 GEN
Solar/Wind Helper
1.108
20675528CPH_W2-050
Solar/Wind Helper
0.114
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.097
20676428JCR_X2-075
Solar/Wind Helper
0.069
964851AG1-348 GEN
Solar/Wind Helper
0.064
207408W3-077 C
Solar/Wind Helper
0.085
20675128HRM_W1-127
Solar/Wind Helper
0.03
203955AF1-039 C O1
Solar/Wind Helper
0.332
209027LOR2_Q27
Solar/Wind Helper
1.036
212266LOR1
Solar/Wind Helper
0.302
209054AE2-059 GEN
Solar/Wind Helper
0.08
270166AC1-044 GEN3
50/50
7.109
23559101PLEAS2
50/50
6.362
962761AG1-125 GEN
Solar/Wind Harmer
41.016
970149AG2-104 GEN
Solar/Wind Harmer
25.328
970155AG2-107 GEN
Solar/Wind Harmer
17.885
270286AF1-227 GEN2
Solar/Wind Harmer
2.504
270520AE2-214 GEN
Solar/Wind Harmer
7.243
270391AF1-285 GEN3
Solar/Wind Harmer
1.393
270578AF1-285 GEN2
Solar/Wind Harmer
1.393
253333AC1-068 GEN
Solar/Wind Harmer
1.191
270317AD1-130_GEN
Solar/Wind Harmer
3.64
270485AE1-090_GEN
Solar/Wind Harmer
0.688
270273AD2-016 GEN
Solar/Wind Harmer
3.013
971995AH1-542 GEN
Solar/Wind Harmer
12.463
972269AH1-719 GEN
Adder
2.545
971073AG2-665 GEN
Solar/Wind Harmer
1.275
25326309TAIT D
Adder
1.195
253370AE2-315 SEC1
Adder
2.18
253371AE2-315 SEC2
Adder
2.062
241813AF1-122_GEN
Solar/Wind Harmer
5.897
971201AH1-060 GEN
Solar/Wind Harmer
1.843
253398AE2-221_GEN2
Solar/Wind Harmer
4.9
246936BC-WTG1
Solar/Wind Harmer
4.216
270489AE1-102 GEN1
Solar/Wind Harmer
1.401
965421AG1-410 GEN
Solar/Wind Harmer
32.318
960001AF2-291 GEN
Solar/Wind Harmer
3.25
253316AC1-085 GEN3
Solar/Wind Harmer
8.992
946171AF1-282 GEN
Solar/Wind Harmer
10.741
965011AG1-365 GEN
Solar/Wind Harmer
10.725
270258AD1-119 GEN
Solar/Wind Harmer
2.156
965651AG1-433 GEN
Solar/Wind Harmer
5.801
252516AE2-318_GEN
Solar/Wind Harmer
10.604
958861AF2-177 GEN
Solar/Wind Harmer
11.586
270024AE2-089 GEN
Solar/Wind Harmer
4.961
252510AF1-249 C
Solar/Wind Harmer
0.441
25194608D.CRK4
Adder
1.739
945371AF1-202 GEN
Solar/Wind Harmer
7.376
270297AD1-101 GEN
Solar/Wind Harmer
2.147
270222AC2-111 GEN
Solar/Wind Harmer
4.718
944031AF1-071 GEN
Solar/Wind Harmer
1.062
270510AE1-227 GEN1
Solar/Wind Harmer
2.605
270005AE1-210 C O1
Solar/Wind Harmer
5.743
942081AE2-220 GEN
Solar/Wind Harmer
6.717
270209AC1-174_GEN
Solar/Wind Harmer
4.274
270437AC2-090 C
Solar/Wind Harmer
5.862
270239V3-007_GEN1
Solar/Wind Harmer
1.807
270331AC1-082 GEN3
Solar/Wind Harmer
0.501
25196808ZIMRHP
Adder
79.685
970825AG2-519 GEN
Solar/Wind Harmer
2.203
24639705ELKHART HY
Adder
0.161
270216AD2-079_GEN
Solar/Wind Harmer
0.634
25196008MFTGT1
Adder
1.45
274751CRETE EC ;1U
Adder
8.473
274754CRETE EC ;4U
Adder
8.473
274773LINCOLN ;4U
Adder
8.673
274774LINCOLN ;5U
Adder
8.673
274723RIVER EC ;12
Adder
18.412
274812UNIV PK N;8U
Adder
5.137
274802UNIV PARK;5U
Adder
5.968
24728605AND G2
Adder
3.925
274676JOLIET 29;8U
Adder
31.291
274732ELWOOD EC;7P
Adder
16.762
274674JOLIET 9 ;6U
Adder
15.699
972203AH1-686 GEN
Adder
2.344
274745AC1-111 GEN9
Adder
5.677
970091AG2-072 GEN
Adder
77.647
274682WAUKEGAN ;7U
Adder
18.178
316095T157 G97
Solar/Wind Helper
1.515
23583801GRNGAP
Solar/Wind Helper
5.644
238185AF2-356 C
Solar/Wind Helper
2.686
238109AE1-109 GEN2
Solar/Wind Helper
0.115
238120AE2-309 GEN
Solar/Wind Helper
0.534
238126S14_GEN_1
Solar/Wind Helper
0.836
23546401DTGZ2-030
Solar/Wind Helper
0.09
237085AD2-009_GEN
Solar/Wind Helper
1.667
237038AE2-054 C
Solar/Wind Helper
0.275
235067AD1-061 GEN
Solar/Wind Helper
0.451
237002AB1-128_GEN
Solar/Wind Helper
0.448
23751101LEADS_P59
Solar/Wind Helper
2.15
23777801MSM_W1-116
Solar/Wind Helper
0.116
3141196NOKESVL
Solar/Wind Helper
1.039
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.022
233935AB2-179 C
Solar/Wind Helper
1.283
233987AB2-037 GEN
Solar/Wind Helper
2.369
233933AB2-153 GEN
Solar/Wind Helper
0.235
232422X3-066 FULL
Solar/Wind Helper
0.115
232417X3-008 C
Solar/Wind Helper
0.235
233964AF2-378 GEN
Solar/Wind Helper
0.042
233923SMA
Solar/Wind Helper
0.76
233997TMININ_4.2
Solar/Wind Helper
0.207
232406W1-004 FULL
Solar/Wind Helper
0.513
232434Z2-077 GEN
Solar/Wind Helper
0.128
233950AC2-186 GEN
Solar/Wind Helper
0.118
230415AB2-049 C
Solar/Wind Helper
0.031
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
219291REEVESSOUT C
Solar/Wind Helper
0.012
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.313
219612MATRIX C
Solar/Wind Helper
0.024
205941AD2-115 GEN
Solar/Wind Helper
0.501
20716928W4-060COL
Solar/Wind Helper
0.052
219249CENTRALDIV C
Solar/Wind Helper
0.01
217213AMBOY SO C
Solar/Wind Helper
0.029
207442AE1-156 GEN
Solar/Wind Helper
0.329
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
207511W3-106 GEN
Solar/Wind Helper
0.027
20671928W4-073
Solar/Wind Helper
0.091
20674128FR_U2-059
Solar/Wind Helper
0.004
209116AE2-175 GEN
Solar/Wind Helper
1.799
211065PSPA IPP
Solar/Wind Helper
0.153
963161AG1-165 GEN
Solar/Wind Helper
0.443
961331AF2-424 GEN
Solar/Wind Helper
0.442
961421AF2-433 GEN
Solar/Wind Helper
0.441
957921AF2-086 GEN
Solar/Wind Helper
0.436
270594AE1-207 GEN
Solar/Wind Harmer
13.371
270032AE2-172
Solar/Wind Harmer
4.579
218438BLK ROCK C
Solar/Wind Helper
0.028
20675428EAM_W2-061
Solar/Wind Helper
0.016
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.023
20675928HOL_W4-097
Solar/Wind Helper
0.051
207471AF2-354 C
Solar/Wind Helper
0.17
20674828DL_W4-046
Solar/Wind Helper
0.008
961431AF2-434 GEN
Solar/Wind Helper
0.441
24318805MLG1
50/50
10.127
23559001PLEAS1
50/50
6.362
270051AF1-062 GEN
50/50
11.798
270475AD2-096_GEN
50/50
7.137
962771AG1-126 GEN
Solar/Wind Harmer
41.016
970153AG2-106 GEN
Solar/Wind Harmer
17.885
961921AG1-034 GEN
Solar/Wind Harmer
15.551
270284AF1-227 GEN1
Solar/Wind Harmer
6.768
270287AF1-227 GEN3
Solar/Wind Harmer
2.504
24721905FLATG4
Adder
24.045
942051AE2-217 GEN
Solar/Wind Harmer
20.995
960801AF2-371 GEN
Solar/Wind Harmer
2.937
964871AG1-351 GEN
Solar/Wind Harmer
2.028
942871AE2-306 GEN
Solar/Wind Harmer
1.045
270391AF1-285 GEN3
Solar/Wind Harmer
0.536
270518AE2-148 GEN
Solar/Wind Harmer
13.818
253325AC1-069 GEN
Solar/Wind Harmer
1.191
276820AF1-078_GEN
Solar/Wind Harmer
1.776
958581AF2-149 GEN
Solar/Wind Harmer
4.712
971199AH1-059 GEN
Solar/Wind Harmer
2.312
970879AG2-548 GEN
Solar/Wind Harmer
8.771
960071AF2-298 GEN
Solar/Wind Harmer
1.647
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.18
253371AE2-315 SEC2
Adder
2.062
970065AG2-057 GEN
Solar/Wind Harmer
0.921
957541AF2-048 GEN
Solar/Wind Harmer
1.717
253394AE2-221_GEN
Solar/Wind Harmer
4.9
246938BC-WTG3
Solar/Wind Harmer
4.289
270491AE1-102 GEN2
Solar/Wind Harmer
1.401
971191AH1-055 GEN
Solar/Wind Harmer
20.077
253317AC1-085 GEN4
Solar/Wind Harmer
8.992
946181AF1-283 GEN
Solar/Wind Harmer
13.963
965021AG1-366 GEN
Solar/Wind Harmer
2.494
958091AF2-103 GEN
Solar/Wind Harmer
0.173
24695305TIMB G C
Solar/Wind Harmer
3.573
270588AE1-091_GEN
Solar/Wind Harmer
11.753
944531AF1-118 GEN
Solar/Wind Harmer
37.358
270043AE2-236 GEN
Solar/Wind Harmer
5.865
252519AF1-045_GEN
Solar/Wind Harmer
3.859
270367AC2-061_GEN
Solar/Wind Harmer
3.367
252524AE2-267 GEN
Solar/Wind Harmer
1.667
25196608WSDLE5
Adder
9.072
25194608D.CRK4
Adder
1.739
252507AC2-088 GEN
Solar/Wind Harmer
1.892
270044AE2-322 C
Solar/Wind Harmer
1.388
270063AE2-323 C
Solar/Wind Harmer
2.32
962031AG1-047 GEN
Solar/Wind Harmer
3.189
957741AF2-068 GEN
Solar/Wind Harmer
15.82
971347AH1-153 GEN
Solar/Wind Harmer
5.266
270512AE1-227 GEN2
Solar/Wind Harmer
2.212
270186AC1-089 GEN
Solar/Wind Harmer
6.425
946031AF1-268 GEN
Solar/Wind Harmer
8.725
270004AE1-209 GEN
Solar/Wind Harmer
5.743
24379505HDWTR1G C
Solar/Wind Harmer
8.305
270240V3-007_GEN2
Solar/Wind Harmer
6.498
270330AC1-082 GEN2
Solar/Wind Harmer
0.5
270329AC1-082 GEN1
Solar/Wind Harmer
0.5
970825AG2-519 GEN
Solar/Wind Harmer
5.915
247643Z2-116 C
Solar/Wind Harmer
0.073
25196008MFTGT1
Adder
1.404
274752CRETE EC ;2U
Adder
8.473
274753CRETE EC ;3U
Adder
8.473
274772LINCOLN ;3U
Adder
8.673
274724RIVER EC ;11
Adder
18.196
274814UNIV PK N;0U
Adder
5.182
274807UNIV PK N;3U
Adder
5.171
274811UNIV PK N;7U
Adder
5.137
274803UNIV PARK;6U
Adder
5.968
24728705AND G3
Adder
8.209
24728505AND G1
Adder
3.925
274826FISK ;BP
Adder
11.201
972038AH1-567 GEN2
Adder
0.373
972259AH1-714 GEN
Adder
19.5
274676JOLIET 29;8U
Adder
30.174
274729ELWOOD EC;1P
Adder
16.762
274730ELWOOD EC;6P
Adder
16.762
274734ELWOOD EC;8P
Adder
16.762
274736ELWOOD EC;9P
Adder
16.762
274682WAUKEGAN ;7U
Adder
18.178
964991AG1-363 GEN
Solar/Wind Helper
5.171
238108AE1-109 GEN1
Solar/Wind Helper
0.115
238110AE1-109 GEN3
Solar/Wind Helper
0.115
238127S14_GEN_2
Solar/Wind Helper
0.836
238175AF1-290_GEN
Solar/Wind Helper
0.158
238152AF2-075_GEN
Solar/Wind Helper
0.715
23777901MDS_W4-102
Solar/Wind Helper
0.179
23562501BACKB
Solar/Wind Helper
1.023
235063AE1-101 C2
Solar/Wind Helper
1.678
237001AB1-127_GEN
Solar/Wind Helper
0.446
237048AF1-022 C
Solar/Wind Helper
0.186
316415AF1-147_GEN2
Solar/Wind Helper
0.898
205916AD1-020 GEN
Solar/Wind Helper
1.732
208835TUHI V3-051
Solar/Wind Helper
0.022
205932AD2-116_GEN
Solar/Wind Helper
0.514
233918AB1-142 GEN
Solar/Wind Helper
0.508
233944AB2-135 GEN
Solar/Wind Helper
0.596
233996TM1833_GEN
Solar/Wind Helper
0.207
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232426Y1-080 FULL
Solar/Wind Helper
0.039
232404W1-003 C
Solar/Wind Helper
0.513
232408W1-005 C
Solar/Wind Helper
0.513
316447AC1-158 HLD
Solar/Wind Helper
2.876
316044AC1-158 PL1
Solar/Wind Helper
1.307
228729W2-030 C
Solar/Wind Helper
0.112
219766PARADISE C
Solar/Wind Helper
0.055
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.116
203975AE1-071-GEN
Solar/Wind Helper
2.526
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.065
20714528FRN_Y2-051
Solar/Wind Helper
0.058
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
218440SUMMTASSOC C
Solar/Wind Helper
0.017
218428ETC SOLAR C
Solar/Wind Helper
0.005
219908AB1-139 C
Solar/Wind Helper
0.075
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673628F1S_V4-069
Solar/Wind Helper
0.03
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207530AG1-191 GEN
Solar/Wind Helper
0.067
207439AE1-081 C O1
Solar/Wind Helper
0.019
20676328BVR_Y1-020
Solar/Wind Helper
0.027
207484AF2-139 C O1
Solar/Wind Helper
0.085
20674928WA_W3-044
Solar/Wind Helper
0.099
20674628WNG_W3-110
Solar/Wind Helper
0.09
20676228FRD_X1-012
Solar/Wind Helper
0.093
20675728RH_W2-091
Solar/Wind Helper
0.082
207518AF1-320_GEN
Solar/Wind Helper
1.586
20675828AU_W4-064
Solar/Wind Helper
0.03
211065PSPA IPP
Solar/Wind Helper
0.153
202652Y1-033 WT C
Solar/Wind Helper
0.504
961301AF2-421 GEN
Solar/Wind Helper
0.443
963151AG1-164 GEN
Solar/Wind Helper
0.443
961341AF2-425 GEN
Solar/Wind Helper
0.442
212507AE2-042_GEN
Solar/Wind Helper
1.561
CPLELTFEXP_CPLE->PJM
CLTF
0.593
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.743
NYPJM->LTFIMP_NY
CLTF
4.85
LGEELTFEXP_LGEE->PJM
CLTF
6.747
WECLTFEXP_WEC->PJM
CLTF
3.823
AG2-052LTFEXP_AG2-052->PJM
LTF
0.239
AH1-155LTFEXP_AH1-155->PJM
LTF
0.359
LAGNLTFEXP_LAGN->PJM
CLTF
14.823
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.742
TVALTFEXP_TVA->PJM
CLTF
7.286
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.944
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.079
MECLTFEXP_MEC->PJM
CLTF
15.894
SIGELTFEXP_SIGE->PJM
CLTF
0.505

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-025_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-025_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.72 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5108.61
MW Contribution:
25.23
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972239AH1-704 GEN
Adder
2.673
270459AD2-067 GEN
Solar/Wind Harmer
10.203
961821AG1-024 GEN
Solar/Wind Harmer
10.359
241955AC1-078 GEN
Solar/Wind Harmer
8.768
241973AD2-163_GEN1
Solar/Wind Harmer
2.315
241974AD2-163_GEN2
Solar/Wind Harmer
2.315
945631AF1-228 GEN
Solar/Wind Harmer
5.44
943861AF1-054 GEN
Solar/Wind Harmer
4.468
943851AF1-053 GEN
Solar/Wind Harmer
2.159
270223U2-072_GEN1
Solar/Wind Harmer
2.27
270224U2-072_GEN2
Solar/Wind Harmer
2.27
270227U2-072_GEN3
Solar/Wind Harmer
2.27
270228U2-072_GEN4
Solar/Wind Harmer
2.27
270231U2-072_GEN5
Solar/Wind Harmer
2.27
270578AF1-285 GEN2
Solar/Wind Harmer
0.535
270432AC2-029 GEN
Solar/Wind Harmer
8.013
253338AC1-165 GEN
Solar/Wind Harmer
1.233
253343AC1-166 GEN
Solar/Wind Harmer
1.233
270302AB2-170 GEN
Solar/Wind Harmer
9.503
940611AE2-048 GEN
Solar/Wind Harmer
24.928
941391AE2-136 GEN
Solar/Wind Harmer
12.917
270263AC1-001 GEN
Solar/Wind Harmer
1.168
241972AD1-140 GEN
Solar/Wind Harmer
4.999
270291AC1-194 GEN
Solar/Wind Harmer
5.603
970179AG2-119 GEN
Solar/Wind Harmer
8.8
270340AC2-060 GEN
Solar/Wind Harmer
3.323
253372AE2-315 SEC3
Adder
2.057
253372AE2-315 SEC3
Adder
2.057
25306009OHH W.
Adder
3.121
253406AD2-031_GEN
Solar/Wind Harmer
1.379
957201AF2-014 GEN
Solar/Wind Harmer
4.877
270435AC2-044 GEN
Solar/Wind Harmer
2.151
270377AD1-106 GEN
Solar/Wind Harmer
5.62
253433AC1-085 GEN1
Solar/Wind Harmer
5.693
253432AC1-085 GEN2
Solar/Wind Harmer
0.287
247521TR3_G114
Solar/Wind Harmer
3.595
270191TR4_S_V150
Solar/Wind Harmer
3.208
965051AG1-369 GEN
Solar/Wind Harmer
5.342
959331AF2-224 GEN
Solar/Wind Harmer
10.696
270007AE1-245 C
Solar/Wind Harmer
5.766
965041AG1-368 GEN
Solar/Wind Harmer
10.674
971567AH1-282 GEN
Solar/Wind Harmer
5.319
966831AG1-554 GEN
Solar/Wind Harmer
1.274
24729505KEY G4
Adder
6.894
270071AF1-092 GEN
Solar/Wind Harmer
15.924
963791AG1-232 GEN
Solar/Wind Harmer
14.332
971985AH1-537 GEN
Solar/Wind Harmer
18.912
958711AF2-162 GEN
Solar/Wind Harmer
1.071
25196408WSDLE3
Adder
9.314
25196308WSDLE2
Adder
9.233
25196208WSDLE1
Adder
9.209
25196708WSDLE6
Adder
9.186
25196508WSDLE4
Adder
8.955
945581AF1-223 GEN
Solar/Wind Harmer
4.781
270404AC1-167 GEN
Solar/Wind Harmer
1.141
270166AC1-044 GEN3
50/50
7.082
23559101PLEAS2
50/50
6.18
962761AG1-125 GEN
Solar/Wind Harmer
40.857
970149AG2-104 GEN
Solar/Wind Harmer
25.229
970155AG2-107 GEN
Solar/Wind Harmer
17.815
270520AE2-214 GEN
Solar/Wind Harmer
7.233
270286AF1-227 GEN2
Solar/Wind Harmer
2.498
270391AF1-285 GEN3
Solar/Wind Harmer
1.39
270578AF1-285 GEN2
Solar/Wind Harmer
1.39
253333AC1-068 GEN
Solar/Wind Harmer
1.189
270317AD1-130_GEN
Solar/Wind Harmer
3.633
270485AE1-090_GEN
Solar/Wind Harmer
0.686
971995AH1-542 GEN
Solar/Wind Harmer
12.451
270273AD2-016 GEN
Solar/Wind Harmer
3.008
972269AH1-719 GEN
Adder
2.564
971073AG2-665 GEN
Solar/Wind Harmer
1.273
25326309TAIT D
Adder
1.192
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
241813AF1-122_GEN
Solar/Wind Harmer
5.894
971201AH1-060 GEN
Solar/Wind Harmer
1.842
270510AE1-227 GEN1
Solar/Wind Harmer
2.678
253398AE2-221_GEN2
Solar/Wind Harmer
4.888
246936BC-WTG1
Solar/Wind Harmer
4.206
270489AE1-102 GEN1
Solar/Wind Harmer
1.398
965421AG1-410 GEN
Solar/Wind Harmer
32.241
960001AF2-291 GEN
Solar/Wind Harmer
3.242
253316AC1-085 GEN3
Solar/Wind Harmer
8.97
946171AF1-282 GEN
Solar/Wind Harmer
10.714
965011AG1-365 GEN
Solar/Wind Harmer
10.696
270258AD1-119 GEN
Solar/Wind Harmer
2.151
965651AG1-433 GEN
Solar/Wind Harmer
5.784
252516AE2-318_GEN
Solar/Wind Harmer
10.575
958861AF2-177 GEN
Solar/Wind Harmer
11.552
270119AB2-067 GEN1
50/50
7.082
270120AB2-067 GEN2
50/50
7.082
24318905MLG2
50/50
7.035
270349AD2-093_GEN
Solar/Wind Harmer
4.445
270471AD2-092_GEN
Solar/Wind Harmer
4.445
270054AF2-122 C O1
Solar/Wind Harmer
3.971
946101AF1-275 GEN
Solar/Wind Harmer
1.808
253383AE2-342_GEN
Solar/Wind Harmer
1.038
942861AE2-305 GEN
Solar/Wind Harmer
9.053
938701AE1-092 GEN
Solar/Wind Harmer
23.731
270462AD2-086
Solar/Wind Harmer
7.892
270269AC2-059
Solar/Wind Harmer
10.554
972159AH1-661 GEN
Adder
1.111
253378AE2-206_GEN
Solar/Wind Harmer
3.988
253415AE1-040 GEN
Solar/Wind Harmer
1.24
25326509SID D
Adder
1.448
241960AC2-195 GEN
Solar/Wind Harmer
3.053
971073AG2-665 GEN
Solar/Wind Harmer
8.757
970879AG2-548 GEN
Solar/Wind Harmer
1.273
25326109MON D
Adder
1.438
25322209TAIT E
Adder
10.61
25322209TAIT E
Adder
10.371
253370AE2-315 SEC1
Adder
2.175
927014AC1-188 GEN
Solar/Wind Harmer
1.713
253349AC2-067 GEN
Solar/Wind Harmer
2.197
253400AC2-068 GEN
Solar/Wind Harmer
0.884
246937BC-WTG2
Solar/Wind Harmer
4.206
270246TR4_N_V150
Solar/Wind Harmer
0.91
270247TR4_N_V136
Solar/Wind Harmer
0.91
942801AE2-298 GEN
Solar/Wind Harmer
1.617
247607V1-011 GEN
Solar/Wind Harmer
4.221
962581AG1-107 GEN
Solar/Wind Harmer
5.341
961491AF2-440 GEN
Solar/Wind Harmer
2.22
25183208HLCRTG
Solar/Wind Harmer
6.41
944541AF1-119 GEN
Solar/Wind Harmer
4.431
960971AF2-388 GEN
Solar/Wind Harmer
11.568
942221AE2-234 GEN
Solar/Wind Harmer
3.699
25194408D.CRK1
Adder
7.978
25194508D.CRK3
Adder
1.491
252509AD1-136 GEN
Solar/Wind Harmer
0.27
970883AG2-550 GEN
Solar/Wind Harmer
10.531
970885AG2-551 GEN
Solar/Wind Harmer
2.449
247621Y3-024
Adder
0.254
270201AC2-176 GEN
Solar/Wind Harmer
5.405
964611AG1-324 GEN
Solar/Wind Harmer
0.55
970349AG2-230 GEN
Solar/Wind Harmer
15.75
270031AE2-169
Solar/Wind Harmer
8.551
270599AE1-208 GEN
Solar/Wind Harmer
8.551
270383AD1-128 GEN
Solar/Wind Harmer
6.401
926881AC1-175 GEN
Solar/Wind Harmer
5.845
247620Y3-023
Adder
0.482
944231AF1-091 GEN
Solar/Wind Harmer
18.84
24728805RICHG1
Adder
3.949
24728905RICHG2
Adder
3.949
274770LINCOLN ;1U
Adder
8.646
274771LINCOLN ;2U
Adder
8.646
274805UNIV PK N;1U
Adder
5.133
274808UNIV PK N;4U
Adder
5.099
274674JOLIET 9 ;6U
Adder
15.65
274696ROCKY RD ;4P
Adder
11.497
274695ROCKY RD ;2P
Adder
11.232
274693ROCKY RD ;1P
Adder
11.121
274697ROCKY RD ;3P
Adder
3.051
274683WAUKEGAN ;8U
Adder
21.239
274683WAUKEGAN ;8U
Adder
9.65
316097T157 G90
Solar/Wind Helper
1.512
235054AD2-180 GEN
Solar/Wind Helper
2.044
23585401KL_K28_T16
Solar/Wind Helper
1.493
235531U2-073 GEN
Solar/Wind Helper
3.333
971029AG2-637 GEN
Solar/Wind Harmer
15.807
970031AG2-029 GEN
Solar/Wind Harmer
26.342
270543AE2-219 C
Solar/Wind Harmer
10.531
247536S-71 GEN
Solar/Wind Harmer
4.259
961761AG1-017 GEN
Solar/Wind Harmer
0.45
964611AG1-324 GEN
Solar/Wind Harmer
4.099
25196108MFTGT2
Adder
1.593
25196108MFTGT2
Adder
1.48
274775LINCOLN ;6U
Adder
8.646
274776LINCOLN ;7U
Adder
8.646
274777LINCOLN ;8U
Adder
8.646
972037AH1-567 GEN1
Adder
0.187
274827FISK ;RP
Adder
7.914
274800UNIV PARK;3U
Adder
5.946
270024AE2-089 GEN
Solar/Wind Harmer
4.947
252510AF1-249 C
Solar/Wind Harmer
0.44
25194608D.CRK4
Adder
1.734
270297AD1-101 GEN
Solar/Wind Harmer
2.142
945371AF1-202 GEN
Solar/Wind Harmer
7.355
270222AC2-111 GEN
Solar/Wind Harmer
4.705
944031AF1-071 GEN
Solar/Wind Harmer
1.059
270005AE1-210 C O1
Solar/Wind Harmer
5.726
25196808ZIMRHP
Adder
79.465
270331AC1-082 GEN3
Solar/Wind Harmer
0.499
942081AE2-220 GEN
Solar/Wind Harmer
6.698
270209AC1-174_GEN
Solar/Wind Harmer
4.262
270437AC2-090 C
Solar/Wind Harmer
5.845
270239V3-007_GEN1
Solar/Wind Harmer
1.802
970825AG2-519 GEN
Solar/Wind Harmer
2.196
24639705ELKHART HY
Adder
0.161
270216AD2-079_GEN
Solar/Wind Harmer
0.632
25196008MFTGT1
Adder
1.445
274751CRETE EC ;1U
Adder
8.448
238117U2-030
Solar/Wind Helper
0.344
238147AE2-230_GEN1
Solar/Wind Helper
0.5
238148AE2-230_GEN2
Solar/Wind Helper
0.5
238149AF1-291A_GEN
Solar/Wind Helper
0.143
235020AA1-095 C
Solar/Wind Helper
0.053
23751201ROTHROCK
Solar/Wind Helper
0.83
237061AD1-155 GEN
Solar/Wind Helper
1.768
238221AF1-254 C O1
Solar/Wind Helper
0.277
237080AD1-060 GEN
Solar/Wind Helper
0.345
235062AE1-101 C1
Solar/Wind Helper
1.674
316411AF1-147_GEN1
Solar/Wind Helper
0.896
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.37
223402AF1-300 C
Solar/Wind Helper
0.37
316006AB2-029 C
Solar/Wind Helper
0.119
233930AB2-032 GEN
Solar/Wind Helper
0.384
232424Y1-079 C
Solar/Wind Helper
0.117
232436AB1-176 C
Solar/Wind Helper
0.045
233982AB2-133 GEN
Solar/Wind Helper
0.362
233946AB2-136 GEN
Solar/Wind Helper
0.574
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.969
232428Y3-058 C
Solar/Wind Helper
0.341
234015AF2-250 C
Solar/Wind Helper
0.038
232410W1-006 C
Solar/Wind Helper
0.511
233952AC2-187 GEN
Solar/Wind Helper
0.234
233954AC2-188 GEN
Solar/Wind Helper
0.234
316045AC1-158 PL2
Solar/Wind Helper
4.174
316450AC1-158 RIC
Solar/Wind Helper
0.348
230511AF1-262
Solar/Wind Helper
0.015
230433AD2-135 GEN
Solar/Wind Helper
0.017
228754AB1-001 C
Solar/Wind Helper
0.026
219904AC1-010 C
Solar/Wind Helper
0.061
219912AD2-042 GEN
Solar/Wind Helper
0.151
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219906AC1-017 C
Solar/Wind Helper
0.042
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.132
214067T20SOLAR
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.064
207459AE1-142 C O1
Solar/Wind Helper
0.292
20714828MDF_W3-079
Solar/Wind Helper
0.131
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
20675428EAM_W2-061
Solar/Wind Helper
0.016
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.023
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.17
20674828DL_W4-046
Solar/Wind Helper
0.008
274801UNIV PARK;4U
Adder
5.946
972228AH1-698 GEN2
Adder
3.777
972227AH1-698 GEN1
Adder
2.66
274687WILL CNTY;4U
Adder
28.425
274687WILL CNTY;4U
Adder
28.425
274675JOLIET 29;7U
Adder
31.195
274675JOLIET 29;7U
Adder
30.081
274728ELWOOD EC;5P
Adder
16.71
274731ELWOOD EC;2P
Adder
16.71
274733ELWOOD EC;3P
Adder
16.71
274735ELWOOD EC;4P
Adder
16.71
274744AC1-111 GEN8
Adder
5.66
274746AC1-111 G10
Adder
5.66
23750701CROSSCHOOL
Solar/Wind Helper
1.512
238118U2-030_1
Solar/Wind Helper
0.344
238169AE2-226 GEN1
Solar/Wind Helper
0.707
238170AE2-226 GEN2
Solar/Wind Helper
0.707
23779801AA1-109
Solar/Wind Helper
0.195
3138216PACIFIC
Solar/Wind Helper
0.045
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.166
23750501ELLIOTTS
Solar/Wind Helper
0.644
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.371
959381AF2-229 GEN
Solar/Wind Helper
0.359
20390526W1-045 C
Solar/Wind Helper
0.353
3141426STAFORD
Solar/Wind Helper
0.053
205943AE1-185 GEN
Solar/Wind Helper
0.513
205956AE1-196_GEN
Solar/Wind Helper
0.513
233915AB1-141 GEN
Solar/Wind Helper
0.507
233940AF2-379 C
Solar/Wind Helper
0.063
233901CHERRYDALE C
Solar/Wind Helper
0.234
232432Z2-076 GEN
Solar/Wind Helper
0.068
315651AD1-115 GEN
Solar/Wind Helper
0.793
230434AG1-499 GEN
Solar/Wind Helper
0.232
228728W1-130C
Solar/Wind Helper
0.054
230407AD2-065 C
Solar/Wind Helper
0.041
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219615MILLCREEK C
Solar/Wind Helper
0.027
20715028HAN_X4-015
Solar/Wind Helper
0.058
20720728JCB_W1-129
Solar/Wind Helper
0.058
207445AB1-138_GEN
Solar/Wind Helper
0.105
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.191
316164AC1-076 GEN
Solar/Wind Helper
1.106
20675528CPH_W2-050
Solar/Wind Helper
0.114
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.097
20676428JCR_X2-075
Solar/Wind Helper
0.068
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.085
20675128HRM_W1-127
Solar/Wind Helper
0.03
209027LOR2_Q27
Solar/Wind Helper
1.033
212266LOR1
Solar/Wind Helper
0.301
203955AF1-039 C O1
Solar/Wind Helper
0.331
24318805MLG1
50/50
10.084
23559001PLEAS1
50/50
6.18
270051AF1-062 GEN
50/50
11.783
270475AD2-096_GEN
50/50
7.121
962771AG1-126 GEN
Solar/Wind Harmer
40.857
970153AG2-106 GEN
Solar/Wind Harmer
17.815
961921AG1-034 GEN
Solar/Wind Harmer
15.539
270284AF1-227 GEN1
Solar/Wind Harmer
6.753
270287AF1-227 GEN3
Solar/Wind Harmer
2.498
24721905FLATG4
Adder
23.892
942051AE2-217 GEN
Solar/Wind Harmer
20.96
960801AF2-371 GEN
Solar/Wind Harmer
2.935
964871AG1-351 GEN
Solar/Wind Harmer
2.026
942871AE2-306 GEN
Solar/Wind Harmer
1.043
270391AF1-285 GEN3
Solar/Wind Harmer
0.535
270518AE2-148 GEN
Solar/Wind Harmer
13.795
253325AC1-069 GEN
Solar/Wind Harmer
1.189
276820AF1-078_GEN
Solar/Wind Harmer
1.772
958581AF2-149 GEN
Solar/Wind Harmer
4.716
971199AH1-059 GEN
Solar/Wind Harmer
2.315
970879AG2-548 GEN
Solar/Wind Harmer
8.757
960071AF2-298 GEN
Solar/Wind Harmer
1.643
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
970065AG2-057 GEN
Solar/Wind Harmer
0.921
957541AF2-048 GEN
Solar/Wind Harmer
1.713
270512AE1-227 GEN2
Solar/Wind Harmer
2.273
253394AE2-221_GEN
Solar/Wind Harmer
4.888
246938BC-WTG3
Solar/Wind Harmer
4.279
270491AE1-102 GEN2
Solar/Wind Harmer
1.398
971191AH1-055 GEN
Solar/Wind Harmer
20.022
253317AC1-085 GEN4
Solar/Wind Harmer
8.97
946181AF1-283 GEN
Solar/Wind Harmer
13.928
965021AG1-366 GEN
Solar/Wind Harmer
2.488
958091AF2-103 GEN
Solar/Wind Harmer
0.172
24695305TIMB G C
Solar/Wind Harmer
3.564
270588AE1-091_GEN
Solar/Wind Harmer
11.739
944531AF1-118 GEN
Solar/Wind Harmer
37.25
270043AE2-236 GEN
Solar/Wind Harmer
5.848
252519AF1-045_GEN
Solar/Wind Harmer
3.849
270367AC2-061_GEN
Solar/Wind Harmer
3.358
252524AE2-267 GEN
Solar/Wind Harmer
1.662
25196608WSDLE5
Adder
9.047
25194608D.CRK4
Adder
1.734
270044AE2-322 C
Solar/Wind Harmer
1.385
252507AC2-088 GEN
Solar/Wind Harmer
1.887
270063AE2-323 C
Solar/Wind Harmer
2.313
962031AG1-047 GEN
Solar/Wind Harmer
3.18
957741AF2-068 GEN
Solar/Wind Harmer
15.775
971347AH1-153 GEN
Solar/Wind Harmer
5.25
270186AC1-089 GEN
Solar/Wind Harmer
6.407
946031AF1-268 GEN
Solar/Wind Harmer
8.7
270004AE1-209 GEN
Solar/Wind Harmer
5.726
270330AC1-082 GEN2
Solar/Wind Harmer
0.498
270329AC1-082 GEN1
Solar/Wind Harmer
0.498
24379505HDWTR1G C
Solar/Wind Harmer
8.281
270240V3-007_GEN2
Solar/Wind Harmer
6.479
970825AG2-519 GEN
Solar/Wind Harmer
5.897
247643Z2-116 C
Solar/Wind Harmer
0.073
25196008MFTGT1
Adder
1.4
274752CRETE EC ;2U
Adder
8.448
274753CRETE EC ;3U
Adder
8.448
274772LINCOLN ;3U
Adder
8.646
274724RIVER EC ;11
Adder
18.141
274814UNIV PK N;0U
Adder
5.166
274807UNIV PK N;3U
Adder
5.155
274811UNIV PK N;7U
Adder
5.122
274803UNIV PARK;6U
Adder
5.949
24728705AND G3
Adder
8.184
24728505AND G1
Adder
3.913
274826FISK ;BP
Adder
11.167
972038AH1-567 GEN2
Adder
0.372
972259AH1-714 GEN
Adder
19.441
274676JOLIET 29;8U
Adder
30.081
274729ELWOOD EC;1P
Adder
16.71
274730ELWOOD EC;6P
Adder
16.71
274734ELWOOD EC;8P
Adder
16.71
274736ELWOOD EC;9P
Adder
16.71
274682WAUKEGAN ;7U
Adder
18.122
964991AG1-363 GEN
Solar/Wind Helper
5.16
238108AE1-109 GEN1
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238127S14_GEN_2
Solar/Wind Helper
0.833
238175AF1-290_GEN
Solar/Wind Helper
0.158
238152AF2-075_GEN
Solar/Wind Helper
0.714
23777901MDS_W4-102
Solar/Wind Helper
0.179
23562501BACKB
Solar/Wind Helper
1.015
235063AE1-101 C2
Solar/Wind Helper
1.674
237001AB1-127_GEN
Solar/Wind Helper
0.445
237048AF1-022 C
Solar/Wind Helper
0.185
316415AF1-147_GEN2
Solar/Wind Helper
0.896
205916AD1-020 GEN
Solar/Wind Helper
1.727
208835TUHI V3-051
Solar/Wind Helper
0.022
205932AD2-116_GEN
Solar/Wind Helper
0.513
233918AB1-142 GEN
Solar/Wind Helper
0.507
233944AB2-135 GEN
Solar/Wind Helper
0.595
233996TM1833_GEN
Solar/Wind Helper
0.207
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232426Y1-080 FULL
Solar/Wind Helper
0.039
232404W1-003 C
Solar/Wind Helper
0.511
232408W1-005 C
Solar/Wind Helper
0.511
316447AC1-158 HLD
Solar/Wind Helper
2.87
316044AC1-158 PL1
Solar/Wind Helper
1.304
228729W2-030 C
Solar/Wind Helper
0.111
219766PARADISE C
Solar/Wind Helper
0.055
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.115
203975AE1-071-GEN
Solar/Wind Helper
2.519
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714528FRN_Y2-051
Solar/Wind Helper
0.057
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
218440SUMMTASSOC C
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207530AG1-191 GEN
Solar/Wind Helper
0.067
207439AE1-081 C O1
Solar/Wind Helper
0.019
20676328BVR_Y1-020
Solar/Wind Helper
0.027
207484AF2-139 C O1
Solar/Wind Helper
0.085
20674928WA_W3-044
Solar/Wind Helper
0.099
20674628WNG_W3-110
Solar/Wind Helper
0.09
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
207518AF1-320_GEN
Solar/Wind Helper
1.582
20675828AU_W4-064
Solar/Wind Helper
0.03
211065PSPA IPP
Solar/Wind Helper
0.153
961301AF2-421 GEN
Solar/Wind Helper
0.442
963151AG1-164 GEN
Solar/Wind Helper
0.442
202652Y1-033 WT C
Solar/Wind Helper
0.501
961341AF2-425 GEN
Solar/Wind Helper
0.441
274754CRETE EC ;4U
Adder
8.448
274773LINCOLN ;4U
Adder
8.646
274774LINCOLN ;5U
Adder
8.646
274723RIVER EC ;12
Adder
18.356
274812UNIV PK N;8U
Adder
5.122
274802UNIV PARK;5U
Adder
5.949
24728605AND G2
Adder
3.913
274676JOLIET 29;8U
Adder
31.195
274732ELWOOD EC;7P
Adder
16.71
274674JOLIET 9 ;6U
Adder
15.65
972203AH1-686 GEN
Adder
2.333
274745AC1-111 GEN9
Adder
5.66
970091AG2-072 GEN
Adder
77.376
274682WAUKEGAN ;7U
Adder
18.122
316095T157 G97
Solar/Wind Helper
1.512
23583801GRNGAP
Solar/Wind Helper
5.632
238185AF2-356 C
Solar/Wind Helper
2.674
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238120AE2-309 GEN
Solar/Wind Helper
0.532
238126S14_GEN_1
Solar/Wind Helper
0.833
23546401DTGZ2-030
Solar/Wind Helper
0.09
237085AD2-009_GEN
Solar/Wind Helper
1.663
237038AE2-054 C
Solar/Wind Helper
0.275
235067AD1-061 GEN
Solar/Wind Helper
0.45
237002AB1-128_GEN
Solar/Wind Helper
0.447
23751101LEADS_P59
Solar/Wind Helper
2.129
23777801MSM_W1-116
Solar/Wind Helper
0.115
3141196NOKESVL
Solar/Wind Helper
1.037
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.349
208835TUHI V3-051
Solar/Wind Helper
0.022
233935AB2-179 C
Solar/Wind Helper
1.279
233987AB2-037 GEN
Solar/Wind Helper
2.363
233933AB2-153 GEN
Solar/Wind Helper
0.235
232422X3-066 FULL
Solar/Wind Helper
0.115
232417X3-008 C
Solar/Wind Helper
0.234
233964AF2-378 GEN
Solar/Wind Helper
0.042
233923SMA
Solar/Wind Helper
0.758
233997TMININ_4.2
Solar/Wind Helper
0.207
232406W1-004 FULL
Solar/Wind Helper
0.511
232434Z2-077 GEN
Solar/Wind Helper
0.128
233950AC2-186 GEN
Solar/Wind Helper
0.117
230415AB2-049 C
Solar/Wind Helper
0.031
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
219291REEVESSOUT C
Solar/Wind Helper
0.012
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.312
219612MATRIX C
Solar/Wind Helper
0.024
205941AD2-115 GEN
Solar/Wind Helper
0.499
20716928W4-060COL
Solar/Wind Helper
0.052
219249CENTRALDIV C
Solar/Wind Helper
0.01
217213AMBOY SO C
Solar/Wind Helper
0.029
207442AE1-156 GEN
Solar/Wind Helper
0.328
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
207511W3-106 GEN
Solar/Wind Helper
0.027
20671928W4-073
Solar/Wind Helper
0.09
20674128FR_U2-059
Solar/Wind Helper
0.004
209116AE2-175 GEN
Solar/Wind Helper
1.794
211065PSPA IPP
Solar/Wind Helper
0.153
963161AG1-165 GEN
Solar/Wind Helper
0.442
961331AF2-424 GEN
Solar/Wind Helper
0.441
270594AE1-207 GEN
Solar/Wind Harmer
13.331
270032AE2-172
Solar/Wind Harmer
4.566
CPLELTFEXP_CPLE->PJM
CLTF
0.578
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.337
NYPJM->LTFIMP_NY
CLTF
4.834
LGEELTFEXP_LGEE->PJM
CLTF
6.725
WECLTFEXP_WEC->PJM
CLTF
3.811
AG2-052LTFEXP_AG2-052->PJM
LTF
0.239
AH1-155LTFEXP_AH1-155->PJM
LTF
0.358
LAGNLTFEXP_LAGN->PJM
CLTF
14.764
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.682
TVALTFEXP_TVA->PJM
CLTF
7.257
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.545
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.966
MECLTFEXP_MEC->PJM
CLTF
15.842
SIGELTFEXP_SIGE->PJM
CLTF
0.503

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-014_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.34 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5094.21
MW Contribution:
25.21
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
7.073
270120AB2-067 GEN2
50/50
7.073
24318905MLG2
50/50
7.043
23684101S70BUS1
50/50
0.165
270349AD2-093_GEN
Solar/Wind Harmer
4.444
270471AD2-092_GEN
Solar/Wind Harmer
4.444
270054AF2-122 C O1
Solar/Wind Harmer
3.974
946101AF1-275 GEN
Solar/Wind Harmer
1.809
253383AE2-342_GEN
Solar/Wind Harmer
1.038
942861AE2-305 GEN
Solar/Wind Harmer
9.054
938701AE1-092 GEN
Solar/Wind Harmer
23.739
270462AD2-086
Solar/Wind Harmer
7.893
270269AC2-059
Solar/Wind Harmer
10.558
972159AH1-661 GEN
Adder
1.114
253378AE2-206_GEN
Solar/Wind Harmer
3.989
253415AE1-040 GEN
Solar/Wind Harmer
1.24
25326509SID D
Adder
1.448
241960AC2-195 GEN
Solar/Wind Harmer
3.054
971073AG2-665 GEN
Solar/Wind Harmer
8.762
970879AG2-548 GEN
Solar/Wind Harmer
1.274
25326109MON D
Adder
1.438
25322209TAIT E
Adder
10.61
25322209TAIT E
Adder
10.372
253370AE2-315 SEC1
Adder
2.175
927014AC1-188 GEN
Solar/Wind Harmer
1.714
253349AC2-067 GEN
Solar/Wind Harmer
2.197
253400AC2-068 GEN
Solar/Wind Harmer
0.884
246937BC-WTG2
Solar/Wind Harmer
4.206
270246TR4_N_V150
Solar/Wind Harmer
0.91
972239AH1-704 GEN
Adder
2.68
270459AD2-067 GEN
Solar/Wind Harmer
10.209
961821AG1-024 GEN
Solar/Wind Harmer
10.365
241955AC1-078 GEN
Solar/Wind Harmer
8.772
241973AD2-163_GEN1
Solar/Wind Harmer
2.316
241974AD2-163_GEN2
Solar/Wind Harmer
2.316
945631AF1-228 GEN
Solar/Wind Harmer
5.442
943861AF1-054 GEN
Solar/Wind Harmer
4.469
943851AF1-053 GEN
Solar/Wind Harmer
2.16
270223U2-072_GEN1
Solar/Wind Harmer
2.27
270224U2-072_GEN2
Solar/Wind Harmer
2.27
270227U2-072_GEN3
Solar/Wind Harmer
2.27
270228U2-072_GEN4
Solar/Wind Harmer
2.27
270231U2-072_GEN5
Solar/Wind Harmer
2.27
270578AF1-285 GEN2
Solar/Wind Harmer
0.535
270432AC2-029 GEN
Solar/Wind Harmer
8.017
253338AC1-165 GEN
Solar/Wind Harmer
1.233
253343AC1-166 GEN
Solar/Wind Harmer
1.233
940611AE2-048 GEN
Solar/Wind Harmer
25.038
941391AE2-136 GEN
Solar/Wind Harmer
12.974
270302AB2-170 GEN
Solar/Wind Harmer
9.503
270263AC1-001 GEN
Solar/Wind Harmer
1.169
241972AD1-140 GEN
Solar/Wind Harmer
5
270291AC1-194 GEN
Solar/Wind Harmer
5.607
970179AG2-119 GEN
Solar/Wind Harmer
8.805
270340AC2-060 GEN
Solar/Wind Harmer
3.324
253372AE2-315 SEC3
Adder
2.057
253372AE2-315 SEC3
Adder
2.057
25306009OHH W.
Adder
3.121
253406AD2-031_GEN
Solar/Wind Harmer
1.379
957201AF2-014 GEN
Solar/Wind Harmer
4.876
270166AC1-044 GEN3
50/50
7.073
23559101PLEAS2
50/50
6.109
23684201S70BUS2
50/50
0.168
962761AG1-125 GEN
Solar/Wind Harmer
40.825
970149AG2-104 GEN
Solar/Wind Harmer
25.209
970155AG2-107 GEN
Solar/Wind Harmer
17.802
270520AE2-214 GEN
Solar/Wind Harmer
7.236
270286AF1-227 GEN2
Solar/Wind Harmer
2.498
270391AF1-285 GEN3
Solar/Wind Harmer
1.39
270578AF1-285 GEN2
Solar/Wind Harmer
1.39
253333AC1-068 GEN
Solar/Wind Harmer
1.189
270317AD1-130_GEN
Solar/Wind Harmer
3.633
270485AE1-090_GEN
Solar/Wind Harmer
0.686
971995AH1-542 GEN
Solar/Wind Harmer
12.457
270273AD2-016 GEN
Solar/Wind Harmer
3.01
972269AH1-719 GEN
Adder
2.576
270510AE1-227 GEN1
Solar/Wind Harmer
2.716
971073AG2-665 GEN
Solar/Wind Harmer
1.274
25326309TAIT D
Adder
1.192
241813AF1-122_GEN
Solar/Wind Harmer
5.898
971201AH1-060 GEN
Solar/Wind Harmer
1.843
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
253398AE2-221_GEN2
Solar/Wind Harmer
4.888
246936BC-WTG1
Solar/Wind Harmer
4.206
270489AE1-102 GEN1
Solar/Wind Harmer
1.398
24318805MLG1
50/50
10.069
23559001PLEAS1
50/50
6.109
270051AF1-062 GEN
50/50
11.788
270475AD2-096_GEN
50/50
7.121
962771AG1-126 GEN
Solar/Wind Harmer
40.825
970153AG2-106 GEN
Solar/Wind Harmer
17.802
961921AG1-034 GEN
Solar/Wind Harmer
15.548
270284AF1-227 GEN1
Solar/Wind Harmer
6.753
270287AF1-227 GEN3
Solar/Wind Harmer
2.498
24721905FLATG4
Adder
23.852
942051AE2-217 GEN
Solar/Wind Harmer
20.967
960801AF2-371 GEN
Solar/Wind Harmer
2.937
964871AG1-351 GEN
Solar/Wind Harmer
2.028
942871AE2-306 GEN
Solar/Wind Harmer
1.043
270391AF1-285 GEN3
Solar/Wind Harmer
0.535
270518AE2-148 GEN
Solar/Wind Harmer
13.799
253325AC1-069 GEN
Solar/Wind Harmer
1.189
276820AF1-078_GEN
Solar/Wind Harmer
1.772
958581AF2-149 GEN
Solar/Wind Harmer
4.723
971199AH1-059 GEN
Solar/Wind Harmer
2.318
270512AE1-227 GEN2
Solar/Wind Harmer
2.305
970879AG2-548 GEN
Solar/Wind Harmer
8.762
960071AF2-298 GEN
Solar/Wind Harmer
1.643
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
970065AG2-057 GEN
Solar/Wind Harmer
0.922
957541AF2-048 GEN
Solar/Wind Harmer
1.714
253394AE2-221_GEN
Solar/Wind Harmer
4.888
246938BC-WTG3
Solar/Wind Harmer
4.278
270491AE1-102 GEN2
Solar/Wind Harmer
1.398
971191AH1-055 GEN
Solar/Wind Harmer
20.024
253317AC1-085 GEN4
Solar/Wind Harmer
8.97
946181AF1-283 GEN
Solar/Wind Harmer
13.928
965021AG1-366 GEN
Solar/Wind Harmer
2.487
958091AF2-103 GEN
Solar/Wind Harmer
0.172
270588AE1-091_GEN
Solar/Wind Harmer
11.743
24695305TIMB G C
Solar/Wind Harmer
3.563
944531AF1-118 GEN
Solar/Wind Harmer
37.241
270043AE2-236 GEN
Solar/Wind Harmer
5.847
252519AF1-045_GEN
Solar/Wind Harmer
3.849
270367AC2-061_GEN
Solar/Wind Harmer
3.358
252524AE2-267 GEN
Solar/Wind Harmer
1.662
25196608WSDLE5
Adder
9.047
25194608D.CRK4
Adder
1.734
270044AE2-322 C
Solar/Wind Harmer
1.385
270435AC2-044 GEN
Solar/Wind Harmer
2.15
270377AD1-106 GEN
Solar/Wind Harmer
5.625
253433AC1-085 GEN1
Solar/Wind Harmer
5.693
253432AC1-085 GEN2
Solar/Wind Harmer
0.287
247521TR3_G114
Solar/Wind Harmer
3.595
270191TR4_S_V150
Solar/Wind Harmer
3.208
965051AG1-369 GEN
Solar/Wind Harmer
5.341
959331AF2-224 GEN
Solar/Wind Harmer
10.694
270007AE1-245 C
Solar/Wind Harmer
5.766
965041AG1-368 GEN
Solar/Wind Harmer
10.672
971567AH1-282 GEN
Solar/Wind Harmer
5.325
966831AG1-554 GEN
Solar/Wind Harmer
1.274
24729505KEY G4
Adder
6.892
963791AG1-232 GEN
Solar/Wind Harmer
14.329
270071AF1-092 GEN
Solar/Wind Harmer
15.92
971985AH1-537 GEN
Solar/Wind Harmer
18.912
958711AF2-162 GEN
Solar/Wind Harmer
1.07
25196408WSDLE3
Adder
9.313
25196308WSDLE2
Adder
9.232
25196208WSDLE1
Adder
9.209
25196708WSDLE6
Adder
9.186
25196508WSDLE4
Adder
8.954
945581AF1-223 GEN
Solar/Wind Harmer
4.78
270404AC1-167 GEN
Solar/Wind Harmer
1.141
971029AG2-637 GEN
Solar/Wind Harmer
15.805
970031AG2-029 GEN
Solar/Wind Harmer
26.336
270543AE2-219 C
Solar/Wind Harmer
10.53
247536S-71 GEN
Solar/Wind Harmer
4.259
961761AG1-017 GEN
Solar/Wind Harmer
0.45
964611AG1-324 GEN
Solar/Wind Harmer
4.098
25196108MFTGT2
Adder
1.593
25196108MFTGT2
Adder
1.479
274775LINCOLN ;6U
Adder
8.644
274776LINCOLN ;7U
Adder
8.644
274777LINCOLN ;8U
Adder
8.644
972037AH1-567 GEN1
Adder
0.187
274827FISK ;RP
Adder
7.912
274800UNIV PARK;3U
Adder
5.944
274801UNIV PARK;4U
Adder
5.944
270247TR4_N_V136
Solar/Wind Harmer
0.91
942801AE2-298 GEN
Solar/Wind Harmer
1.617
247607V1-011 GEN
Solar/Wind Harmer
4.221
962581AG1-107 GEN
Solar/Wind Harmer
5.341
961491AF2-440 GEN
Solar/Wind Harmer
2.22
25183208HLCRTG
Solar/Wind Harmer
6.409
944541AF1-119 GEN
Solar/Wind Harmer
4.43
960971AF2-388 GEN
Solar/Wind Harmer
11.565
942221AE2-234 GEN
Solar/Wind Harmer
3.699
25194408D.CRK1
Adder
7.977
25194508D.CRK3
Adder
1.491
252509AD1-136 GEN
Solar/Wind Harmer
0.27
970883AG2-550 GEN
Solar/Wind Harmer
10.53
970885AG2-551 GEN
Solar/Wind Harmer
2.449
247621Y3-024
Adder
0.254
270201AC2-176 GEN
Solar/Wind Harmer
5.404
964611AG1-324 GEN
Solar/Wind Harmer
0.55
970349AG2-230 GEN
Solar/Wind Harmer
15.746
270031AE2-169
Solar/Wind Harmer
8.55
270599AE1-208 GEN
Solar/Wind Harmer
8.55
270383AD1-128 GEN
Solar/Wind Harmer
6.399
926881AC1-175 GEN
Solar/Wind Harmer
5.844
247620Y3-023
Adder
0.482
944231AF1-091 GEN
Solar/Wind Harmer
18.838
24728805RICHG1
Adder
3.948
24728905RICHG2
Adder
3.948
274770LINCOLN ;1U
Adder
8.644
274771LINCOLN ;2U
Adder
8.644
274805UNIV PK N;1U
Adder
5.131
274808UNIV PK N;4U
Adder
5.098
274674JOLIET 9 ;6U
Adder
15.646
274696ROCKY RD ;4P
Adder
11.494
274695ROCKY RD ;2P
Adder
11.229
274693ROCKY RD ;1P
Adder
11.118
274697ROCKY RD ;3P
Adder
3.05
274683WAUKEGAN ;8U
Adder
21.233
274683WAUKEGAN ;8U
Adder
9.373
316097T157 G90
Solar/Wind Helper
1.512
235054AD2-180 GEN
Solar/Wind Helper
2.035
23585401KL_K28_T16
Solar/Wind Helper
1.485
235531U2-073 GEN
Solar/Wind Helper
3.323
238117U2-030
Solar/Wind Helper
0.343
238147AE2-230_GEN1
Solar/Wind Helper
0.499
238148AE2-230_GEN2
Solar/Wind Helper
0.499
238149AF1-291A_GEN
Solar/Wind Helper
0.143
235020AA1-095 C
Solar/Wind Helper
0.053
237061AD1-155 GEN
Solar/Wind Helper
1.768
23751201ROTHROCK
Solar/Wind Helper
0.823
238221AF1-254 C O1
Solar/Wind Helper
0.277
237080AD1-060 GEN
Solar/Wind Helper
0.345
235062AE1-101 C1
Solar/Wind Helper
1.673
316411AF1-147_GEN1
Solar/Wind Helper
0.896
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.37
223402AF1-300 C
Solar/Wind Helper
0.37
316006AB2-029 C
Solar/Wind Helper
0.119
233982AB2-133 GEN
Solar/Wind Helper
0.362
972228AH1-698 GEN2
Adder
3.776
972227AH1-698 GEN1
Adder
2.659
274687WILL CNTY;4U
Adder
28.416
274687WILL CNTY;4U
Adder
28.416
274675JOLIET 29;7U
Adder
31.186
274675JOLIET 29;7U
Adder
30.072
274728ELWOOD EC;5P
Adder
16.705
274731ELWOOD EC;2P
Adder
16.705
274733ELWOOD EC;3P
Adder
16.705
274735ELWOOD EC;4P
Adder
16.705
274744AC1-111 GEN8
Adder
5.658
274746AC1-111 G10
Adder
5.658
23750701CROSSCHOOL
Solar/Wind Helper
1.507
238118U2-030_1
Solar/Wind Helper
0.343
238169AE2-226 GEN1
Solar/Wind Helper
0.707
238170AE2-226 GEN2
Solar/Wind Helper
0.707
23779801AA1-109
Solar/Wind Helper
0.195
3138216PACIFIC
Solar/Wind Helper
0.045
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.166
23750501ELLIOTTS
Solar/Wind Helper
0.64
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.371
959381AF2-229 GEN
Solar/Wind Helper
0.359
20390526W1-045 C
Solar/Wind Helper
0.353
3141426STAFORD
Solar/Wind Helper
0.053
205943AE1-185 GEN
Solar/Wind Helper
0.513
205956AE1-196_GEN
Solar/Wind Helper
0.513
233915AB1-141 GEN
Solar/Wind Helper
0.506
233901CHERRYDALE C
Solar/Wind Helper
0.234
233940AF2-379 C
Solar/Wind Helper
0.063
232432Z2-076 GEN
Solar/Wind Helper
0.068
315651AD1-115 GEN
Solar/Wind Helper
0.793
230434AG1-499 GEN
Solar/Wind Helper
0.232
228728W1-130C
Solar/Wind Helper
0.054
230407AD2-065 C
Solar/Wind Helper
0.041
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219615MILLCREEK C
Solar/Wind Helper
0.027
20715028HAN_X4-015
Solar/Wind Helper
0.058
20720728JCB_W1-129
Solar/Wind Helper
0.058
207445AB1-138_GEN
Solar/Wind Helper
0.105
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.191
316164AC1-076 GEN
Solar/Wind Helper
1.106
20675528CPH_W2-050
Solar/Wind Helper
0.114
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.097
20676428JCR_X2-075
Solar/Wind Helper
0.068
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.085
20675128HRM_W1-127
Solar/Wind Helper
0.03
209027LOR2_Q27
Solar/Wind Helper
1.033
212266LOR1
Solar/Wind Helper
0.301
233930AB2-032 GEN
Solar/Wind Helper
0.384
232424Y1-079 C
Solar/Wind Helper
0.117
232436AB1-176 C
Solar/Wind Helper
0.045
233946AB2-136 GEN
Solar/Wind Helper
0.573
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.969
232410W1-006 C
Solar/Wind Helper
0.511
232428Y3-058 C
Solar/Wind Helper
0.341
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.234
233954AC2-188 GEN
Solar/Wind Helper
0.234
316045AC1-158 PL2
Solar/Wind Helper
4.174
316450AC1-158 RIC
Solar/Wind Helper
0.348
230511AF1-262
Solar/Wind Helper
0.015
230433AD2-135 GEN
Solar/Wind Helper
0.017
228754AB1-001 C
Solar/Wind Helper
0.026
219904AC1-010 C
Solar/Wind Helper
0.061
219912AD2-042 GEN
Solar/Wind Helper
0.151
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219906AC1-017 C
Solar/Wind Helper
0.042
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.132
214067T20SOLAR
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.064
207459AE1-142 C O1
Solar/Wind Helper
0.292
20714828MDF_W3-079
Solar/Wind Helper
0.131
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
20675428EAM_W2-061
Solar/Wind Helper
0.016
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.023
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.17
20674828DL_W4-046
Solar/Wind Helper
0.008
252507AC2-088 GEN
Solar/Wind Harmer
1.887
270063AE2-323 C
Solar/Wind Harmer
2.313
962031AG1-047 GEN
Solar/Wind Harmer
3.179
957741AF2-068 GEN
Solar/Wind Harmer
15.772
971347AH1-153 GEN
Solar/Wind Harmer
5.249
270186AC1-089 GEN
Solar/Wind Harmer
6.407
946031AF1-268 GEN
Solar/Wind Harmer
8.698
270330AC1-082 GEN2
Solar/Wind Harmer
0.498
270329AC1-082 GEN1
Solar/Wind Harmer
0.498
270004AE1-209 GEN
Solar/Wind Harmer
5.725
24379505HDWTR1G C
Solar/Wind Harmer
8.279
270240V3-007_GEN2
Solar/Wind Harmer
6.478
970825AG2-519 GEN
Solar/Wind Harmer
5.896
247643Z2-116 C
Solar/Wind Harmer
0.073
25196008MFTGT1
Adder
1.4
274752CRETE EC ;2U
Adder
8.445
274753CRETE EC ;3U
Adder
8.445
274772LINCOLN ;3U
Adder
8.644
274724RIVER EC ;11
Adder
18.136
274814UNIV PK N;0U
Adder
5.165
274807UNIV PK N;3U
Adder
5.154
274811UNIV PK N;7U
Adder
5.12
274803UNIV PARK;6U
Adder
5.948
24728705AND G3
Adder
8.182
24728505AND G1
Adder
3.912
274826FISK ;BP
Adder
11.164
972038AH1-567 GEN2
Adder
0.372
972259AH1-714 GEN
Adder
19.435
274676JOLIET 29;8U
Adder
30.072
274729ELWOOD EC;1P
Adder
16.705
274730ELWOOD EC;6P
Adder
16.705
274734ELWOOD EC;8P
Adder
16.705
274736ELWOOD EC;9P
Adder
16.705
274682WAUKEGAN ;7U
Adder
18.116
964991AG1-363 GEN
Solar/Wind Helper
5.159
238108AE1-109 GEN1
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238127S14_GEN_2
Solar/Wind Helper
0.83
238175AF1-290_GEN
Solar/Wind Helper
0.158
238152AF2-075_GEN
Solar/Wind Helper
0.714
23777901MDS_W4-102
Solar/Wind Helper
0.179
23562501BACKB
Solar/Wind Helper
1.006
235063AE1-101 C2
Solar/Wind Helper
1.673
237001AB1-127_GEN
Solar/Wind Helper
0.445
316415AF1-147_GEN2
Solar/Wind Helper
0.896
237048AF1-022 C
Solar/Wind Helper
0.184
205916AD1-020 GEN
Solar/Wind Helper
1.727
208835TUHI V3-051
Solar/Wind Helper
0.022
205932AD2-116_GEN
Solar/Wind Helper
0.513
233918AB1-142 GEN
Solar/Wind Helper
0.506
233944AB2-135 GEN
Solar/Wind Helper
0.595
232426Y1-080 FULL
Solar/Wind Helper
0.039
233996TM1833_GEN
Solar/Wind Helper
0.207
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232404W1-003 C
Solar/Wind Helper
0.511
232408W1-005 C
Solar/Wind Helper
0.511
316447AC1-158 HLD
Solar/Wind Helper
2.87
316044AC1-158 PL1
Solar/Wind Helper
1.304
228729W2-030 C
Solar/Wind Helper
0.111
219766PARADISE C
Solar/Wind Helper
0.055
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.115
203975AE1-071-GEN
Solar/Wind Helper
2.518
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714528FRN_Y2-051
Solar/Wind Helper
0.057
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
218440SUMMTASSOC C
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207530AG1-191 GEN
Solar/Wind Helper
0.067
20676328BVR_Y1-020
Solar/Wind Helper
0.027
207439AE1-081 C O1
Solar/Wind Helper
0.019
207484AF2-139 C O1
Solar/Wind Helper
0.085
20674928WA_W3-044
Solar/Wind Helper
0.099
20674628WNG_W3-110
Solar/Wind Helper
0.09
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
207518AF1-320_GEN
Solar/Wind Helper
1.581
20675828AU_W4-064
Solar/Wind Helper
0.03
211065PSPA IPP
Solar/Wind Helper
0.153
961301AF2-421 GEN
Solar/Wind Helper
0.442
963151AG1-164 GEN
Solar/Wind Helper
0.442
961341AF2-425 GEN
Solar/Wind Helper
0.44
965421AG1-410 GEN
Solar/Wind Harmer
32.239
960001AF2-291 GEN
Solar/Wind Harmer
3.243
253316AC1-085 GEN3
Solar/Wind Harmer
8.97
946171AF1-282 GEN
Solar/Wind Harmer
10.714
965011AG1-365 GEN
Solar/Wind Harmer
10.694
270258AD1-119 GEN
Solar/Wind Harmer
2.151
965651AG1-433 GEN
Solar/Wind Harmer
5.783
252516AE2-318_GEN
Solar/Wind Harmer
10.575
958861AF2-177 GEN
Solar/Wind Harmer
11.549
252510AF1-249 C
Solar/Wind Harmer
0.44
270024AE2-089 GEN
Solar/Wind Harmer
4.946
25194608D.CRK4
Adder
1.734
270297AD1-101 GEN
Solar/Wind Harmer
2.142
945371AF1-202 GEN
Solar/Wind Harmer
7.353
270222AC2-111 GEN
Solar/Wind Harmer
4.705
944031AF1-071 GEN
Solar/Wind Harmer
1.059
270331AC1-082 GEN3
Solar/Wind Harmer
0.499
270005AE1-210 C O1
Solar/Wind Harmer
5.725
25196808ZIMRHP
Adder
79.46
942081AE2-220 GEN
Solar/Wind Harmer
6.696
270209AC1-174_GEN
Solar/Wind Harmer
4.261
270437AC2-090 C
Solar/Wind Harmer
5.844
270239V3-007_GEN1
Solar/Wind Harmer
1.802
970825AG2-519 GEN
Solar/Wind Harmer
2.196
24639705ELKHART HY
Adder
0.16
270216AD2-079_GEN
Solar/Wind Harmer
0.632
25196008MFTGT1
Adder
1.445
274751CRETE EC ;1U
Adder
8.445
274754CRETE EC ;4U
Adder
8.445
274773LINCOLN ;4U
Adder
8.644
274774LINCOLN ;5U
Adder
8.644
274723RIVER EC ;12
Adder
18.35
274812UNIV PK N;8U
Adder
5.12
274802UNIV PARK;5U
Adder
5.948
24728605AND G2
Adder
3.912
274676JOLIET 29;8U
Adder
31.186
274732ELWOOD EC;7P
Adder
16.705
274674JOLIET 9 ;6U
Adder
15.646
972203AH1-686 GEN
Adder
2.33
274745AC1-111 GEN9
Adder
5.658
970091AG2-072 GEN
Adder
77.346
274682WAUKEGAN ;7U
Adder
18.116
316095T157 G97
Solar/Wind Helper
1.512
23583801GRNGAP
Solar/Wind Helper
5.632
238185AF2-356 C
Solar/Wind Helper
2.664
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238120AE2-309 GEN
Solar/Wind Helper
0.53
238126S14_GEN_1
Solar/Wind Helper
0.83
23546401DTGZ2-030
Solar/Wind Helper
0.09
237085AD2-009_GEN
Solar/Wind Helper
1.662
237038AE2-054 C
Solar/Wind Helper
0.275
235067AD1-061 GEN
Solar/Wind Helper
0.449
237002AB1-128_GEN
Solar/Wind Helper
0.447
23777801MSM_W1-116
Solar/Wind Helper
0.115
23751101LEADS_P59
Solar/Wind Helper
2.095
3141196NOKESVL
Solar/Wind Helper
1.037
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.349
208835TUHI V3-051
Solar/Wind Helper
0.022
233935AB2-179 C
Solar/Wind Helper
1.279
233987AB2-037 GEN
Solar/Wind Helper
2.362
233933AB2-153 GEN
Solar/Wind Helper
0.234
232422X3-066 FULL
Solar/Wind Helper
0.115
232417X3-008 C
Solar/Wind Helper
0.234
233964AF2-378 GEN
Solar/Wind Helper
0.042
233923SMA
Solar/Wind Helper
0.758
233997TMININ_4.2
Solar/Wind Helper
0.207
232406W1-004 FULL
Solar/Wind Helper
0.511
232434Z2-077 GEN
Solar/Wind Helper
0.128
233950AC2-186 GEN
Solar/Wind Helper
0.117
230415AB2-049 C
Solar/Wind Helper
0.031
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
219291REEVESSOUT C
Solar/Wind Helper
0.012
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.312
219612MATRIX C
Solar/Wind Helper
0.024
205941AD2-115 GEN
Solar/Wind Helper
0.499
20716928W4-060COL
Solar/Wind Helper
0.052
219249CENTRALDIV C
Solar/Wind Helper
0.01
217213AMBOY SO C
Solar/Wind Helper
0.029
207442AE1-156 GEN
Solar/Wind Helper
0.328
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
207511W3-106 GEN
Solar/Wind Helper
0.027
20671928W4-073
Solar/Wind Helper
0.09
20674128FR_U2-059
Solar/Wind Helper
0.004
209116AE2-175 GEN
Solar/Wind Helper
1.794
211065PSPA IPP
Solar/Wind Helper
0.153
963161AG1-165 GEN
Solar/Wind Helper
0.442
961331AF2-424 GEN
Solar/Wind Helper
0.44
270594AE1-207 GEN
Solar/Wind Harmer
13.328
270032AE2-172
Solar/Wind Harmer
4.564
CPLELTFEXP_CPLE->PJM
CLTF
0.575
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.294
NYPJM->LTFIMP_NY
CLTF
4.833
LGEELTFEXP_LGEE->PJM
CLTF
6.723
WECLTFEXP_WEC->PJM
CLTF
3.81
AG2-052LTFEXP_AG2-052->PJM
LTF
0.239
AH1-155LTFEXP_AH1-155->PJM
LTF
0.358
LAGNLTFEXP_LAGN->PJM
CLTF
14.758
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.672
TVALTFEXP_TVA->PJM
CLTF
7.253
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.516
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.953
MECLTFEXP_MEC->PJM
CLTF
15.837
SIGELTFEXP_SIGE->PJM
CLTF
0.503

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-015_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-015_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.34 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5094.21
MW Contribution:
25.21
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972239AH1-704 GEN
Adder
2.68
270459AD2-067 GEN
Solar/Wind Harmer
10.209
961821AG1-024 GEN
Solar/Wind Harmer
10.365
241955AC1-078 GEN
Solar/Wind Harmer
8.772
241973AD2-163_GEN1
Solar/Wind Harmer
2.316
241974AD2-163_GEN2
Solar/Wind Harmer
2.316
945631AF1-228 GEN
Solar/Wind Harmer
5.442
943861AF1-054 GEN
Solar/Wind Harmer
4.469
943851AF1-053 GEN
Solar/Wind Harmer
2.16
270223U2-072_GEN1
Solar/Wind Harmer
2.27
270224U2-072_GEN2
Solar/Wind Harmer
2.27
270227U2-072_GEN3
Solar/Wind Harmer
2.27
270228U2-072_GEN4
Solar/Wind Harmer
2.27
270231U2-072_GEN5
Solar/Wind Harmer
2.27
270578AF1-285 GEN2
Solar/Wind Harmer
0.535
270432AC2-029 GEN
Solar/Wind Harmer
8.017
253338AC1-165 GEN
Solar/Wind Harmer
1.233
253343AC1-166 GEN
Solar/Wind Harmer
1.233
940611AE2-048 GEN
Solar/Wind Harmer
25.038
941391AE2-136 GEN
Solar/Wind Harmer
12.974
270302AB2-170 GEN
Solar/Wind Harmer
9.503
270263AC1-001 GEN
Solar/Wind Harmer
1.169
241972AD1-140 GEN
Solar/Wind Harmer
5
270291AC1-194 GEN
Solar/Wind Harmer
5.607
970179AG2-119 GEN
Solar/Wind Harmer
8.805
270340AC2-060 GEN
Solar/Wind Harmer
3.324
253372AE2-315 SEC3
Adder
2.057
253372AE2-315 SEC3
Adder
2.057
25306009OHH W.
Adder
3.121
253406AD2-031_GEN
Solar/Wind Harmer
1.379
957201AF2-014 GEN
Solar/Wind Harmer
4.876
270435AC2-044 GEN
Solar/Wind Harmer
2.15
270377AD1-106 GEN
Solar/Wind Harmer
5.625
253433AC1-085 GEN1
Solar/Wind Harmer
5.693
253432AC1-085 GEN2
Solar/Wind Harmer
0.287
247521TR3_G114
Solar/Wind Harmer
3.595
270191TR4_S_V150
Solar/Wind Harmer
3.208
965051AG1-369 GEN
Solar/Wind Harmer
5.341
959331AF2-224 GEN
Solar/Wind Harmer
10.694
270007AE1-245 C
Solar/Wind Harmer
5.766
965041AG1-368 GEN
Solar/Wind Harmer
10.672
971567AH1-282 GEN
Solar/Wind Harmer
5.325
966831AG1-554 GEN
Solar/Wind Harmer
1.274
24729505KEY G4
Adder
6.892
963791AG1-232 GEN
Solar/Wind Harmer
14.329
270071AF1-092 GEN
Solar/Wind Harmer
15.92
971985AH1-537 GEN
Solar/Wind Harmer
18.912
958711AF2-162 GEN
Solar/Wind Harmer
1.07
25196408WSDLE3
Adder
9.313
25196308WSDLE2
Adder
9.232
25196208WSDLE1
Adder
9.209
25196708WSDLE6
Adder
9.186
25196508WSDLE4
Adder
8.954
945581AF1-223 GEN
Solar/Wind Harmer
4.78
270404AC1-167 GEN
Solar/Wind Harmer
1.141
971029AG2-637 GEN
Solar/Wind Harmer
15.805
970031AG2-029 GEN
Solar/Wind Harmer
26.336
270543AE2-219 C
Solar/Wind Harmer
10.53
247536S-71 GEN
Solar/Wind Harmer
4.259
961761AG1-017 GEN
Solar/Wind Harmer
0.45
964611AG1-324 GEN
Solar/Wind Harmer
4.098
25196108MFTGT2
Adder
1.593
25196108MFTGT2
Adder
1.479
274775LINCOLN ;6U
Adder
8.644
274776LINCOLN ;7U
Adder
8.644
274777LINCOLN ;8U
Adder
8.644
972037AH1-567 GEN1
Adder
0.187
274827FISK ;RP
Adder
7.912
274800UNIV PARK;3U
Adder
5.944
274801UNIV PARK;4U
Adder
5.944
972228AH1-698 GEN2
Adder
3.776
972227AH1-698 GEN1
Adder
2.659
274687WILL CNTY;4U
Adder
28.416
274687WILL CNTY;4U
Adder
28.416
274675JOLIET 29;7U
Adder
31.186
274675JOLIET 29;7U
Adder
30.072
274728ELWOOD EC;5P
Adder
16.705
274731ELWOOD EC;2P
Adder
16.705
274733ELWOOD EC;3P
Adder
16.705
274735ELWOOD EC;4P
Adder
16.705
274744AC1-111 GEN8
Adder
5.658
274746AC1-111 G10
Adder
5.658
23750701CROSSCHOOL
Solar/Wind Helper
1.507
238118U2-030_1
Solar/Wind Helper
0.343
238169AE2-226 GEN1
Solar/Wind Helper
0.707
238170AE2-226 GEN2
Solar/Wind Helper
0.707
23779801AA1-109
Solar/Wind Helper
0.195
3138216PACIFIC
Solar/Wind Helper
0.045
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.166
23750501ELLIOTTS
Solar/Wind Helper
0.64
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.371
959381AF2-229 GEN
Solar/Wind Helper
0.359
20390526W1-045 C
Solar/Wind Helper
0.353
3141426STAFORD
Solar/Wind Helper
0.053
205943AE1-185 GEN
Solar/Wind Helper
0.513
205956AE1-196_GEN
Solar/Wind Helper
0.513
233915AB1-141 GEN
Solar/Wind Helper
0.506
233901CHERRYDALE C
Solar/Wind Helper
0.234
233940AF2-379 C
Solar/Wind Helper
0.063
232432Z2-076 GEN
Solar/Wind Helper
0.068
315651AD1-115 GEN
Solar/Wind Helper
0.793
230434AG1-499 GEN
Solar/Wind Helper
0.232
228728W1-130C
Solar/Wind Helper
0.054
230407AD2-065 C
Solar/Wind Helper
0.041
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219615MILLCREEK C
Solar/Wind Helper
0.027
20715028HAN_X4-015
Solar/Wind Helper
0.058
20720728JCB_W1-129
Solar/Wind Helper
0.058
207445AB1-138_GEN
Solar/Wind Helper
0.105
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.191
316164AC1-076 GEN
Solar/Wind Helper
1.106
20675528CPH_W2-050
Solar/Wind Helper
0.114
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.097
20676428JCR_X2-075
Solar/Wind Helper
0.068
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.085
20675128HRM_W1-127
Solar/Wind Helper
0.03
209027LOR2_Q27
Solar/Wind Helper
1.033
212266LOR1
Solar/Wind Helper
0.301
270119AB2-067 GEN1
50/50
7.073
270120AB2-067 GEN2
50/50
7.073
24318905MLG2
50/50
7.043
23684101S70BUS1
50/50
0.165
270349AD2-093_GEN
Solar/Wind Harmer
4.444
270471AD2-092_GEN
Solar/Wind Harmer
4.444
270054AF2-122 C O1
Solar/Wind Harmer
3.974
946101AF1-275 GEN
Solar/Wind Harmer
1.809
253383AE2-342_GEN
Solar/Wind Harmer
1.038
942861AE2-305 GEN
Solar/Wind Harmer
9.054
938701AE1-092 GEN
Solar/Wind Harmer
23.739
270462AD2-086
Solar/Wind Harmer
7.893
270269AC2-059
Solar/Wind Harmer
10.558
972159AH1-661 GEN
Adder
1.114
253378AE2-206_GEN
Solar/Wind Harmer
3.989
253415AE1-040 GEN
Solar/Wind Harmer
1.24
25326509SID D
Adder
1.448
241960AC2-195 GEN
Solar/Wind Harmer
3.054
971073AG2-665 GEN
Solar/Wind Harmer
8.762
970879AG2-548 GEN
Solar/Wind Harmer
1.274
25326109MON D
Adder
1.438
25322209TAIT E
Adder
10.61
25322209TAIT E
Adder
10.372
253370AE2-315 SEC1
Adder
2.175
927014AC1-188 GEN
Solar/Wind Harmer
1.714
253349AC2-067 GEN
Solar/Wind Harmer
2.197
253400AC2-068 GEN
Solar/Wind Harmer
0.884
246937BC-WTG2
Solar/Wind Harmer
4.206
270246TR4_N_V150
Solar/Wind Harmer
0.91
270247TR4_N_V136
Solar/Wind Harmer
0.91
942801AE2-298 GEN
Solar/Wind Harmer
1.617
247607V1-011 GEN
Solar/Wind Harmer
4.221
962581AG1-107 GEN
Solar/Wind Harmer
5.341
961491AF2-440 GEN
Solar/Wind Harmer
2.22
25183208HLCRTG
Solar/Wind Harmer
6.409
944541AF1-119 GEN
Solar/Wind Harmer
4.43
960971AF2-388 GEN
Solar/Wind Harmer
11.565
24318805MLG1
50/50
10.069
23559001PLEAS1
50/50
6.109
270051AF1-062 GEN
50/50
11.788
270475AD2-096_GEN
50/50
7.121
962771AG1-126 GEN
Solar/Wind Harmer
40.825
970153AG2-106 GEN
Solar/Wind Harmer
17.802
961921AG1-034 GEN
Solar/Wind Harmer
15.548
270284AF1-227 GEN1
Solar/Wind Harmer
6.753
270287AF1-227 GEN3
Solar/Wind Harmer
2.498
24721905FLATG4
Adder
23.852
942051AE2-217 GEN
Solar/Wind Harmer
20.967
960801AF2-371 GEN
Solar/Wind Harmer
2.937
964871AG1-351 GEN
Solar/Wind Harmer
2.028
942871AE2-306 GEN
Solar/Wind Harmer
1.043
270391AF1-285 GEN3
Solar/Wind Harmer
0.535
270518AE2-148 GEN
Solar/Wind Harmer
13.799
253325AC1-069 GEN
Solar/Wind Harmer
1.189
276820AF1-078_GEN
Solar/Wind Harmer
1.772
958581AF2-149 GEN
Solar/Wind Harmer
4.723
971199AH1-059 GEN
Solar/Wind Harmer
2.318
270512AE1-227 GEN2
Solar/Wind Harmer
2.305
970879AG2-548 GEN
Solar/Wind Harmer
8.762
960071AF2-298 GEN
Solar/Wind Harmer
1.643
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
970065AG2-057 GEN
Solar/Wind Harmer
0.922
957541AF2-048 GEN
Solar/Wind Harmer
1.714
253394AE2-221_GEN
Solar/Wind Harmer
4.888
246938BC-WTG3
Solar/Wind Harmer
4.278
270491AE1-102 GEN2
Solar/Wind Harmer
1.398
971191AH1-055 GEN
Solar/Wind Harmer
20.024
253317AC1-085 GEN4
Solar/Wind Harmer
8.97
946181AF1-283 GEN
Solar/Wind Harmer
13.928
965021AG1-366 GEN
Solar/Wind Harmer
2.487
958091AF2-103 GEN
Solar/Wind Harmer
0.172
270588AE1-091_GEN
Solar/Wind Harmer
11.743
24695305TIMB G C
Solar/Wind Harmer
3.563
944531AF1-118 GEN
Solar/Wind Harmer
37.241
270043AE2-236 GEN
Solar/Wind Harmer
5.847
252519AF1-045_GEN
Solar/Wind Harmer
3.849
270367AC2-061_GEN
Solar/Wind Harmer
3.358
252524AE2-267 GEN
Solar/Wind Harmer
1.662
25196608WSDLE5
Adder
9.047
25194608D.CRK4
Adder
1.734
270044AE2-322 C
Solar/Wind Harmer
1.385
252507AC2-088 GEN
Solar/Wind Harmer
1.887
270063AE2-323 C
Solar/Wind Harmer
2.313
962031AG1-047 GEN
Solar/Wind Harmer
3.179
957741AF2-068 GEN
Solar/Wind Harmer
15.772
971347AH1-153 GEN
Solar/Wind Harmer
5.249
270186AC1-089 GEN
Solar/Wind Harmer
6.407
946031AF1-268 GEN
Solar/Wind Harmer
8.698
270330AC1-082 GEN2
Solar/Wind Harmer
0.498
270329AC1-082 GEN1
Solar/Wind Harmer
0.498
270004AE1-209 GEN
Solar/Wind Harmer
5.725
24379505HDWTR1G C
Solar/Wind Harmer
8.279
270240V3-007_GEN2
Solar/Wind Harmer
6.478
970825AG2-519 GEN
Solar/Wind Harmer
5.896
247643Z2-116 C
Solar/Wind Harmer
0.073
25196008MFTGT1
Adder
1.4
274752CRETE EC ;2U
Adder
8.445
274753CRETE EC ;3U
Adder
8.445
274772LINCOLN ;3U
Adder
8.644
274724RIVER EC ;11
Adder
18.136
274814UNIV PK N;0U
Adder
5.165
274807UNIV PK N;3U
Adder
5.154
274811UNIV PK N;7U
Adder
5.12
274803UNIV PARK;6U
Adder
5.948
24728705AND G3
Adder
8.182
24728505AND G1
Adder
3.912
274826FISK ;BP
Adder
11.164
972038AH1-567 GEN2
Adder
0.372
972259AH1-714 GEN
Adder
19.435
274676JOLIET 29;8U
Adder
30.072
274729ELWOOD EC;1P
Adder
16.705
274730ELWOOD EC;6P
Adder
16.705
274734ELWOOD EC;8P
Adder
16.705
274736ELWOOD EC;9P
Adder
16.705
274682WAUKEGAN ;7U
Adder
18.116
964991AG1-363 GEN
Solar/Wind Helper
5.159
238108AE1-109 GEN1
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238127S14_GEN_2
Solar/Wind Helper
0.83
238175AF1-290_GEN
Solar/Wind Helper
0.158
238152AF2-075_GEN
Solar/Wind Helper
0.714
23777901MDS_W4-102
Solar/Wind Helper
0.179
23562501BACKB
Solar/Wind Helper
1.006
235063AE1-101 C2
Solar/Wind Helper
1.673
237001AB1-127_GEN
Solar/Wind Helper
0.445
316415AF1-147_GEN2
Solar/Wind Helper
0.896
237048AF1-022 C
Solar/Wind Helper
0.184
205916AD1-020 GEN
Solar/Wind Helper
1.727
208835TUHI V3-051
Solar/Wind Helper
0.022
205932AD2-116_GEN
Solar/Wind Helper
0.513
233918AB1-142 GEN
Solar/Wind Helper
0.506
233944AB2-135 GEN
Solar/Wind Helper
0.595
232426Y1-080 FULL
Solar/Wind Helper
0.039
233996TM1833_GEN
Solar/Wind Helper
0.207
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232404W1-003 C
Solar/Wind Helper
0.511
232408W1-005 C
Solar/Wind Helper
0.511
316447AC1-158 HLD
Solar/Wind Helper
2.87
316044AC1-158 PL1
Solar/Wind Helper
1.304
228729W2-030 C
Solar/Wind Helper
0.111
219766PARADISE C
Solar/Wind Helper
0.055
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.115
203975AE1-071-GEN
Solar/Wind Helper
2.518
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714528FRN_Y2-051
Solar/Wind Helper
0.057
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
218440SUMMTASSOC C
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207530AG1-191 GEN
Solar/Wind Helper
0.067
20676328BVR_Y1-020
Solar/Wind Helper
0.027
207439AE1-081 C O1
Solar/Wind Helper
0.019
207484AF2-139 C O1
Solar/Wind Helper
0.085
20674928WA_W3-044
Solar/Wind Helper
0.099
20674628WNG_W3-110
Solar/Wind Helper
0.09
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
207518AF1-320_GEN
Solar/Wind Helper
1.581
20675828AU_W4-064
Solar/Wind Helper
0.03
211065PSPA IPP
Solar/Wind Helper
0.153
961301AF2-421 GEN
Solar/Wind Helper
0.442
963151AG1-164 GEN
Solar/Wind Helper
0.442
961341AF2-425 GEN
Solar/Wind Helper
0.44
942221AE2-234 GEN
Solar/Wind Harmer
3.699
25194408D.CRK1
Adder
7.977
25194508D.CRK3
Adder
1.491
252509AD1-136 GEN
Solar/Wind Harmer
0.27
970883AG2-550 GEN
Solar/Wind Harmer
10.53
970885AG2-551 GEN
Solar/Wind Harmer
2.449
247621Y3-024
Adder
0.254
270201AC2-176 GEN
Solar/Wind Harmer
5.404
964611AG1-324 GEN
Solar/Wind Harmer
0.55
970349AG2-230 GEN
Solar/Wind Harmer
15.746
270031AE2-169
Solar/Wind Harmer
8.55
270599AE1-208 GEN
Solar/Wind Harmer
8.55
270383AD1-128 GEN
Solar/Wind Harmer
6.399
926881AC1-175 GEN
Solar/Wind Harmer
5.844
247620Y3-023
Adder
0.482
944231AF1-091 GEN
Solar/Wind Harmer
18.838
24728805RICHG1
Adder
3.948
24728905RICHG2
Adder
3.948
274770LINCOLN ;1U
Adder
8.644
274771LINCOLN ;2U
Adder
8.644
274805UNIV PK N;1U
Adder
5.131
274808UNIV PK N;4U
Adder
5.098
274674JOLIET 9 ;6U
Adder
15.646
274696ROCKY RD ;4P
Adder
11.494
274695ROCKY RD ;2P
Adder
11.229
274693ROCKY RD ;1P
Adder
11.118
274697ROCKY RD ;3P
Adder
3.05
274683WAUKEGAN ;8U
Adder
21.233
274683WAUKEGAN ;8U
Adder
9.373
316097T157 G90
Solar/Wind Helper
1.512
235054AD2-180 GEN
Solar/Wind Helper
2.035
23585401KL_K28_T16
Solar/Wind Helper
1.485
235531U2-073 GEN
Solar/Wind Helper
3.323
238117U2-030
Solar/Wind Helper
0.343
270166AC1-044 GEN3
50/50
7.073
23559101PLEAS2
50/50
6.109
23684201S70BUS2
50/50
0.168
962761AG1-125 GEN
Solar/Wind Harmer
40.825
970149AG2-104 GEN
Solar/Wind Harmer
25.209
970155AG2-107 GEN
Solar/Wind Harmer
17.802
270520AE2-214 GEN
Solar/Wind Harmer
7.236
270286AF1-227 GEN2
Solar/Wind Harmer
2.498
270391AF1-285 GEN3
Solar/Wind Harmer
1.39
270578AF1-285 GEN2
Solar/Wind Harmer
1.39
253333AC1-068 GEN
Solar/Wind Harmer
1.189
270317AD1-130_GEN
Solar/Wind Harmer
3.633
270485AE1-090_GEN
Solar/Wind Harmer
0.686
971995AH1-542 GEN
Solar/Wind Harmer
12.457
270273AD2-016 GEN
Solar/Wind Harmer
3.01
972269AH1-719 GEN
Adder
2.576
270510AE1-227 GEN1
Solar/Wind Harmer
2.716
971073AG2-665 GEN
Solar/Wind Harmer
1.274
25326309TAIT D
Adder
1.192
241813AF1-122_GEN
Solar/Wind Harmer
5.898
971201AH1-060 GEN
Solar/Wind Harmer
1.843
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
253398AE2-221_GEN2
Solar/Wind Harmer
4.888
246936BC-WTG1
Solar/Wind Harmer
4.206
270489AE1-102 GEN1
Solar/Wind Harmer
1.398
965421AG1-410 GEN
Solar/Wind Harmer
32.239
960001AF2-291 GEN
Solar/Wind Harmer
3.243
253316AC1-085 GEN3
Solar/Wind Harmer
8.97
946171AF1-282 GEN
Solar/Wind Harmer
10.714
965011AG1-365 GEN
Solar/Wind Harmer
10.694
270258AD1-119 GEN
Solar/Wind Harmer
2.151
965651AG1-433 GEN
Solar/Wind Harmer
5.783
252516AE2-318_GEN
Solar/Wind Harmer
10.575
958861AF2-177 GEN
Solar/Wind Harmer
11.549
252510AF1-249 C
Solar/Wind Harmer
0.44
270024AE2-089 GEN
Solar/Wind Harmer
4.946
25194608D.CRK4
Adder
1.734
270297AD1-101 GEN
Solar/Wind Harmer
2.142
945371AF1-202 GEN
Solar/Wind Harmer
7.353
270222AC2-111 GEN
Solar/Wind Harmer
4.705
944031AF1-071 GEN
Solar/Wind Harmer
1.059
270331AC1-082 GEN3
Solar/Wind Harmer
0.499
270005AE1-210 C O1
Solar/Wind Harmer
5.725
25196808ZIMRHP
Adder
79.46
942081AE2-220 GEN
Solar/Wind Harmer
6.696
270209AC1-174_GEN
Solar/Wind Harmer
4.261
270437AC2-090 C
Solar/Wind Harmer
5.844
270239V3-007_GEN1
Solar/Wind Harmer
1.802
970825AG2-519 GEN
Solar/Wind Harmer
2.196
24639705ELKHART HY
Adder
0.16
270216AD2-079_GEN
Solar/Wind Harmer
0.632
25196008MFTGT1
Adder
1.445
274751CRETE EC ;1U
Adder
8.445
274754CRETE EC ;4U
Adder
8.445
274773LINCOLN ;4U
Adder
8.644
274774LINCOLN ;5U
Adder
8.644
274723RIVER EC ;12
Adder
18.35
274812UNIV PK N;8U
Adder
5.12
274802UNIV PARK;5U
Adder
5.948
24728605AND G2
Adder
3.912
274676JOLIET 29;8U
Adder
31.186
274732ELWOOD EC;7P
Adder
16.705
274674JOLIET 9 ;6U
Adder
15.646
972203AH1-686 GEN
Adder
2.33
274745AC1-111 GEN9
Adder
5.658
970091AG2-072 GEN
Adder
77.346
274682WAUKEGAN ;7U
Adder
18.116
316095T157 G97
Solar/Wind Helper
1.512
23583801GRNGAP
Solar/Wind Helper
5.632
238185AF2-356 C
Solar/Wind Helper
2.664
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238120AE2-309 GEN
Solar/Wind Helper
0.53
238126S14_GEN_1
Solar/Wind Helper
0.83
23546401DTGZ2-030
Solar/Wind Helper
0.09
237085AD2-009_GEN
Solar/Wind Helper
1.662
237038AE2-054 C
Solar/Wind Helper
0.275
235067AD1-061 GEN
Solar/Wind Helper
0.449
237002AB1-128_GEN
Solar/Wind Helper
0.447
23777801MSM_W1-116
Solar/Wind Helper
0.115
23751101LEADS_P59
Solar/Wind Helper
2.095
3141196NOKESVL
Solar/Wind Helper
1.037
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.349
208835TUHI V3-051
Solar/Wind Helper
0.022
233935AB2-179 C
Solar/Wind Helper
1.279
233987AB2-037 GEN
Solar/Wind Helper
2.362
233933AB2-153 GEN
Solar/Wind Helper
0.234
232422X3-066 FULL
Solar/Wind Helper
0.115
232417X3-008 C
Solar/Wind Helper
0.234
233964AF2-378 GEN
Solar/Wind Helper
0.042
233923SMA
Solar/Wind Helper
0.758
233997TMININ_4.2
Solar/Wind Helper
0.207
232406W1-004 FULL
Solar/Wind Helper
0.511
232434Z2-077 GEN
Solar/Wind Helper
0.128
233950AC2-186 GEN
Solar/Wind Helper
0.117
230415AB2-049 C
Solar/Wind Helper
0.031
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
219291REEVESSOUT C
Solar/Wind Helper
0.012
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.312
219612MATRIX C
Solar/Wind Helper
0.024
205941AD2-115 GEN
Solar/Wind Helper
0.499
20716928W4-060COL
Solar/Wind Helper
0.052
219249CENTRALDIV C
Solar/Wind Helper
0.01
217213AMBOY SO C
Solar/Wind Helper
0.029
207442AE1-156 GEN
Solar/Wind Helper
0.328
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
207511W3-106 GEN
Solar/Wind Helper
0.027
20671928W4-073
Solar/Wind Helper
0.09
20674128FR_U2-059
Solar/Wind Helper
0.004
209116AE2-175 GEN
Solar/Wind Helper
1.794
211065PSPA IPP
Solar/Wind Helper
0.153
963161AG1-165 GEN
Solar/Wind Helper
0.442
238147AE2-230_GEN1
Solar/Wind Helper
0.499
238148AE2-230_GEN2
Solar/Wind Helper
0.499
238149AF1-291A_GEN
Solar/Wind Helper
0.143
235020AA1-095 C
Solar/Wind Helper
0.053
237061AD1-155 GEN
Solar/Wind Helper
1.768
23751201ROTHROCK
Solar/Wind Helper
0.823
238221AF1-254 C O1
Solar/Wind Helper
0.277
237080AD1-060 GEN
Solar/Wind Helper
0.345
235062AE1-101 C1
Solar/Wind Helper
1.673
316411AF1-147_GEN1
Solar/Wind Helper
0.896
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.37
223402AF1-300 C
Solar/Wind Helper
0.37
316006AB2-029 C
Solar/Wind Helper
0.119
233982AB2-133 GEN
Solar/Wind Helper
0.362
233930AB2-032 GEN
Solar/Wind Helper
0.384
232424Y1-079 C
Solar/Wind Helper
0.117
232436AB1-176 C
Solar/Wind Helper
0.045
233946AB2-136 GEN
Solar/Wind Helper
0.573
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.969
232410W1-006 C
Solar/Wind Helper
0.511
232428Y3-058 C
Solar/Wind Helper
0.341
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.234
233954AC2-188 GEN
Solar/Wind Helper
0.234
316045AC1-158 PL2
Solar/Wind Helper
4.174
316450AC1-158 RIC
Solar/Wind Helper
0.348
230511AF1-262
Solar/Wind Helper
0.015
230433AD2-135 GEN
Solar/Wind Helper
0.017
228754AB1-001 C
Solar/Wind Helper
0.026
219904AC1-010 C
Solar/Wind Helper
0.061
219912AD2-042 GEN
Solar/Wind Helper
0.151
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219906AC1-017 C
Solar/Wind Helper
0.042
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.132
214067T20SOLAR
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.064
207459AE1-142 C O1
Solar/Wind Helper
0.292
20714828MDF_W3-079
Solar/Wind Helper
0.131
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
20675428EAM_W2-061
Solar/Wind Helper
0.016
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.023
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.17
20674828DL_W4-046
Solar/Wind Helper
0.008
961331AF2-424 GEN
Solar/Wind Helper
0.44
270594AE1-207 GEN
Solar/Wind Harmer
13.328
270032AE2-172
Solar/Wind Harmer
4.564
CPLELTFEXP_CPLE->PJM
CLTF
0.575
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.294
NYPJM->LTFIMP_NY
CLTF
4.833
LGEELTFEXP_LGEE->PJM
CLTF
6.723
WECLTFEXP_WEC->PJM
CLTF
3.81
AG2-052LTFEXP_AG2-052->PJM
LTF
0.239
AH1-155LTFEXP_AH1-155->PJM
LTF
0.358
LAGNLTFEXP_LAGN->PJM
CLTF
14.758
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.672
TVALTFEXP_TVA->PJM
CLTF
7.253
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.516
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.953
MECLTFEXP_MEC->PJM
CLTF
15.837
SIGELTFEXP_SIGE->PJM
CLTF
0.503

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P1-2_MP-500-007A_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P1-2_MP-500-007A_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:133.22 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5051.83
MW Contribution:
18.57
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972239AH1-704 GEN
Adder
2.678
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
5.057
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
945631AF1-228 GEN
Solar/Wind Harmer
0.001
943861AF1-054 GEN
Solar/Wind Harmer
3.115
270119AB2-067 GEN1
50/50
7.069
270120AB2-067 GEN2
50/50
7.069
24318905MLG2
50/50
7.039
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0
942861AE2-305 GEN
Solar/Wind Harmer
6.31
938701AE1-092 GEN
Solar/Wind Harmer
12.867
971655AH1-328 GEN
Solar/Wind Harmer
2.843
270462AD2-086
Solar/Wind Harmer
0
270269AC2-059
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
1.113
970329AG2-216 GEN
Solar/Wind Harmer
3.341
25326509SID D
Adder
1.446
971073AG2-665 GEN
Solar/Wind Harmer
5.597
970879AG2-548 GEN
Solar/Wind Harmer
1.272
25326109MON D
Adder
1.437
25322209TAIT E
Adder
10.598
25322209TAIT E
Adder
10.36
253370AE2-315 SEC1
Adder
2.172
246937BC-WTG2
Solar/Wind Harmer
0.302
270246TR4_N_V150
Solar/Wind Harmer
0.048
270247TR4_N_V136
Solar/Wind Harmer
0.048
247607V1-011 GEN
Solar/Wind Harmer
0
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25183208HLCRTG
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.351
944541AF1-119 GEN
Solar/Wind Harmer
0.492
960971AF2-388 GEN
Solar/Wind Harmer
4.326
942221AE2-234 GEN
Solar/Wind Harmer
2.958
25194408D.CRK1
Adder
7.968
25194508D.CRK3
Adder
1.49
970621AG2-405 GEN
Solar/Wind Harmer
1.345
252509AD1-136 GEN
Solar/Wind Harmer
0.037
970883AG2-550 GEN
Solar/Wind Harmer
7.338
970885AG2-551 GEN
Solar/Wind Harmer
2.446
247621Y3-024
Adder
0.253
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.549
970349AG2-230 GEN
Solar/Wind Harmer
10.973
270031AE2-169
Solar/Wind Harmer
4.021
270599AE1-208 GEN
Solar/Wind Harmer
6.701
270383AD1-128 GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
247620Y3-023
Adder
0.481
944231AF1-091 GEN
Solar/Wind Harmer
16.825
24728805RICHG1
Adder
3.944
24728905RICHG2
Adder
3.944
971613AH1-306 GEN
Solar/Wind Harmer
3.493
970291AG2-192 GEN
Solar/Wind Harmer
0.945
970291AG2-192 GEN
Solar/Wind Harmer
0.436
961051AF2-396 GEN
Solar/Wind Harmer
14.52
961051AF2-396 GEN
Solar/Wind Harmer
9.68
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
9.052
965791AG1-447 GEN
Solar/Wind Harmer
6.638
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
8.634
274771LINCOLN ;2U
Adder
8.634
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.807
274805UNIV PK N;1U
Adder
5.126
274808UNIV PK N;4U
Adder
5.092
274888KELLY CRK;1U
Solar/Wind Harmer
0.414
276776AD2-060 GEN
Solar/Wind Harmer
0.758
958011AF2-095 GEN
Solar/Wind Harmer
10.234
970941AG2-585 GEN
Solar/Wind Harmer
3.909
276897AD1-100 C
Solar/Wind Harmer
17.749
274674JOLIET 9 ;6U
Adder
15.628
276893AG1-478 C
Solar/Wind Harmer
0.472
970241AG2-163 GEN
Solar/Wind Harmer
4.124
958481AF2-142 GEN
Solar/Wind Harmer
10.569
274696ROCKY RD ;4P
Adder
11.481
274695ROCKY RD ;2P
Adder
11.216
274693ROCKY RD ;1P
Adder
11.106
274697ROCKY RD ;3P
Adder
3.047
958491AF2-143 GEN
Solar/Wind Harmer
10.536
276901AD2-066 C O1
Solar/Wind Harmer
0
274683WAUKEGAN ;8U
Adder
21.209
943851AF1-053 GEN
Solar/Wind Harmer
2.157
270578AF1-285 GEN2
Solar/Wind Harmer
0.534
270432AC2-029 GEN
Solar/Wind Harmer
3.538
940611AE2-048 GEN
Solar/Wind Harmer
19.52
941391AE2-136 GEN
Solar/Wind Harmer
10.996
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.113
270263AC1-001 GEN
Solar/Wind Harmer
0.78
241972AD1-140 GEN
Solar/Wind Harmer
0.849
270291AC1-194 GEN
Solar/Wind Harmer
0
970179AG2-119 GEN
Solar/Wind Harmer
6.854
270340AC2-060 GEN
Solar/Wind Harmer
0.001
253372AE2-315 SEC3
Adder
2.055
253372AE2-315 SEC3
Adder
2.055
25306009OHH W.
Adder
3.117
253406AD2-031_GEN
Solar/Wind Harmer
0.559
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.949
270377AD1-106 GEN
Solar/Wind Harmer
2.842
247521TR3_G114
Solar/Wind Harmer
0.27
965051AG1-369 GEN
Solar/Wind Harmer
3.723
959331AF2-224 GEN
Solar/Wind Harmer
5.217
270007AE1-245 C
Solar/Wind Harmer
0
965041AG1-368 GEN
Solar/Wind Harmer
7.438
971567AH1-282 GEN
Solar/Wind Harmer
5.69
24729505KEY G4
Adder
6.885
963791AG1-232 GEN
Solar/Wind Harmer
9.987
270071AF1-092 GEN
Solar/Wind Harmer
14.177
971985AH1-537 GEN
Solar/Wind Harmer
2.196
25196408WSDLE3
Adder
9.302
25196308WSDLE2
Adder
9.221
25196208WSDLE1
Adder
9.198
25196708WSDLE6
Adder
9.175
25196508WSDLE4
Adder
8.944
945581AF1-223 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
11.014
970031AG2-029 GEN
Solar/Wind Harmer
3.977
270543AE2-219 C
Solar/Wind Harmer
5.137
247536S-71 GEN
Solar/Wind Harmer
0.293
964611AG1-324 GEN
Solar/Wind Harmer
2.856
971609AH1-304 GEN
Solar/Wind Harmer
1.194
970289AG2-191 GEN
Solar/Wind Harmer
1.382
971771AH1-392 GEN
Solar/Wind Harmer
7.271
270526AF1-158 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
25196108MFTGT2
Adder
1.591
25196108MFTGT2
Adder
1.478
270356AE2-297 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
959141AF2-205 GEN
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
4.281
971549AH1-272 GEN
Solar/Wind Harmer
14.794
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.634
274776LINCOLN ;7U
Adder
8.634
274777LINCOLN ;8U
Adder
8.634
24386405FR-21G C
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.186
960591AF2-350 GEN
Solar/Wind Harmer
7.107
274827FISK ;RP
Adder
7.903
274800UNIV PARK;3U
Adder
5.937
274801UNIV PARK;4U
Adder
5.937
972228AH1-698 GEN2
Adder
3.772
972227AH1-698 GEN1
Adder
2.656
963841AG1-237 GEN
Solar/Wind Harmer
3.075
972163AH1-664 GEN
Solar/Wind Harmer
7.896
972165AH1-665 GEN
Solar/Wind Harmer
6.324
274687WILL CNTY;4U
Adder
28.385
274687WILL CNTY;4U
Adder
28.385
274675JOLIET 29;7U
Adder
31.151
274675JOLIET 29;7U
Adder
30.039
274728ELWOOD EC;5P
Adder
16.687
274731ELWOOD EC;2P
Adder
16.687
274733ELWOOD EC;3P
Adder
16.687
274735ELWOOD EC;4P
Adder
16.687
970833AG2-524 GEN
Solar/Wind Harmer
7.786
970833AG2-524 GEN
Solar/Wind Harmer
5.191
274744AC1-111 GEN8
Adder
5.652
274746AC1-111 G10
Adder
5.652
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.341
970169AG2-114 GEN
Solar/Wind Harmer
7.011
945641AF1-229 GEN
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
2.723
276861AD2-134 GEN
Solar/Wind Harmer
0.124
276863AD2-134 GEN
Solar/Wind Harmer
0.124
971411AH1-196 GEN
Solar/Wind Harmer
10.47
926823AC1-168 GEN
Solar/Wind Harmer
1.186
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.32
23750701CROSSCHOOL
Solar/Wind Helper
1.509
238118U2-030_1
Solar/Wind Helper
0.343
238169AE2-226 GEN1
Solar/Wind Helper
0.706
238170AE2-226 GEN2
Solar/Wind Helper
0.706
23779801AA1-109
Solar/Wind Helper
0.194
3138216PACIFIC
Solar/Wind Helper
0.045
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.165
23750501ELLIOTTS
Solar/Wind Helper
0.642
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.371
959381AF2-229 GEN
Solar/Wind Helper
0.359
20390526W1-045 C
Solar/Wind Helper
0.353
3141426STAFORD
Solar/Wind Helper
0.053
205943AE1-185 GEN
Solar/Wind Helper
0.513
270166AC1-044 GEN3
50/50
7.069
23559101PLEAS2
50/50
6.097
962761AG1-125 GEN
Solar/Wind Harmer
34.394
970149AG2-104 GEN
Solar/Wind Harmer
18.573
970155AG2-107 GEN
Solar/Wind Harmer
21.963
270520AE2-214 GEN
Solar/Wind Harmer
0
253333AC1-068 GEN
Solar/Wind Harmer
0.009
270317AD1-130_GEN
Solar/Wind Harmer
0
971995AH1-542 GEN
Solar/Wind Harmer
2.894
270273AD2-016 GEN
Solar/Wind Harmer
0.807
972269AH1-719 GEN
Adder
2.573
270510AE1-227 GEN1
Solar/Wind Harmer
1.954
971073AG2-665 GEN
Solar/Wind Harmer
1.272
25326309TAIT D
Adder
1.191
241813AF1-122_GEN
Solar/Wind Harmer
3.39
971201AH1-060 GEN
Solar/Wind Harmer
1.514
253370AE2-315 SEC1
Adder
2.172
253371AE2-315 SEC2
Adder
2.055
253398AE2-221_GEN2
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.302
270489AE1-102 GEN1
Solar/Wind Harmer
0.974
965421AG1-410 GEN
Solar/Wind Harmer
22.47
960001AF2-291 GEN
Solar/Wind Harmer
0
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.466
965011AG1-365 GEN
Solar/Wind Harmer
7.453
965651AG1-433 GEN
Solar/Wind Harmer
2.163
252516AE2-318_GEN
Solar/Wind Harmer
8.253
958861AF2-177 GEN
Solar/Wind Harmer
3.191
270024AE2-089 GEN
Solar/Wind Harmer
0.001
252510AF1-249 C
Solar/Wind Harmer
0.056
25194608D.CRK4
Adder
1.732
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.582
25196808ZIMRHP
Adder
79.365
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.351
970825AG2-519 GEN
Solar/Wind Harmer
2.589
24639705ELKHART HY
Adder
0.16
270594AE1-207 GEN
Solar/Wind Harmer
8.151
270032AE2-172
Solar/Wind Harmer
4.852
945111AF1-176 GEN
Solar/Wind Harmer
12.968
957891AF2-083 GEN
Solar/Wind Harmer
12.11
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.787
276903AD2-071 C
Solar/Wind Harmer
8.095
25196008MFTGT1
Adder
1.443
970773AG2-487 GEN
Solar/Wind Harmer
1.277
970373AG2-245 GEN
Solar/Wind Harmer
15.17
270055AF2-134 C O1
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.365
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.989
274751CRETE EC ;1U
Adder
8.436
274754CRETE EC ;4U
Adder
8.436
274773LINCOLN ;4U
Adder
8.634
274774LINCOLN ;5U
Adder
8.634
274723RIVER EC ;12
Adder
18.33
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
5.114
274802UNIV PARK;5U
Adder
5.941
24728605AND G2
Adder
3.908
945681AF1-233 GEN
Solar/Wind Harmer
13.398
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
31.151
274732ELWOOD EC;7P
Adder
16.687
274674JOLIET 9 ;6U
Adder
15.628
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
16.733
274745AC1-111 GEN9
Adder
5.652
972203AH1-686 GEN
Adder
2.327
939401AE1-172 GEN
Solar/Wind Harmer
5.275
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.145
274861TOP CROP ;1U
Solar/Wind Harmer
0
970091AG2-072 GEN
Adder
77.252
274682WAUKEGAN ;7U
Adder
18.096
276805AD2-038 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.818
971997AH1-543 GEN
Solar/Wind Harmer
3.68
962781AG1-127 GEN
Solar/Wind Harmer
6.668
274872LEEDK;1U
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
20.915
939741AE1-205 GEN
Solar/Wind Harmer
9.761
316095T157 G97
Solar/Wind Helper
1.51
23583801GRNGAP
Solar/Wind Helper
5.626
238185AF2-356 C
Solar/Wind Helper
2.669
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238120AE2-309 GEN
Solar/Wind Helper
0.531
238126S14_GEN_1
Solar/Wind Helper
0.831
23546401DTGZ2-030
Solar/Wind Helper
0.09
237085AD2-009_GEN
Solar/Wind Helper
1.661
237038AE2-054 C
Solar/Wind Helper
0.274
235067AD1-061 GEN
Solar/Wind Helper
0.449
237002AB1-128_GEN
Solar/Wind Helper
0.446
23751101LEADS_P59
Solar/Wind Helper
2.119
23777801MSM_W1-116
Solar/Wind Helper
0.115
3141196NOKESVL
Solar/Wind Helper
1.036
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.349
24318805MLG1
50/50
10.065
23559001PLEAS1
50/50
6.097
270051AF1-062 GEN
50/50
11.777
270475AD2-096_GEN
50/50
7.114
962771AG1-126 GEN
Solar/Wind Harmer
34.394
970153AG2-106 GEN
Solar/Wind Harmer
21.963
961921AG1-034 GEN
Solar/Wind Harmer
7.586
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
24721905FLATG4
Adder
23.821
942051AE2-217 GEN
Solar/Wind Harmer
14.613
270391AF1-285 GEN3
Solar/Wind Harmer
0.534
270518AE2-148 GEN
Solar/Wind Harmer
0.653
253325AC1-069 GEN
Solar/Wind Harmer
0.009
971199AH1-059 GEN
Solar/Wind Harmer
1.615
270512AE1-227 GEN2
Solar/Wind Harmer
1.954
970879AG2-548 GEN
Solar/Wind Harmer
5.597
970065AG2-057 GEN
Solar/Wind Harmer
0.757
253370AE2-315 SEC1
Adder
2.172
253371AE2-315 SEC2
Adder
2.055
970191AG2-125 GEN
Solar/Wind Harmer
1.937
253394AE2-221_GEN
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.27
270491AE1-102 GEN2
Solar/Wind Harmer
0.974
971191AH1-055 GEN
Solar/Wind Harmer
19.175
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.706
965021AG1-366 GEN
Solar/Wind Harmer
2.484
270588AE1-091_GEN
Solar/Wind Harmer
5.82
24695305TIMB G C
Solar/Wind Harmer
0.63
944531AF1-118 GEN
Solar/Wind Harmer
33.233
270043AE2-236 GEN
Solar/Wind Harmer
4.754
252519AF1-045_GEN
Solar/Wind Harmer
3.844
270367AC2-061_GEN
Solar/Wind Harmer
0
25196608WSDLE5
Adder
9.036
25194608D.CRK4
Adder
1.732
252507AC2-088 GEN
Solar/Wind Harmer
0.33
270063AE2-323 C
Solar/Wind Harmer
0
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.991
971347AH1-153 GEN
Solar/Wind Harmer
3.658
270186AC1-089 GEN
Solar/Wind Harmer
0
946031AF1-268 GEN
Solar/Wind Harmer
6.95
270004AE1-209 GEN
Solar/Wind Harmer
1.582
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
5.494
970289AG2-191 GEN
Solar/Wind Harmer
0.8
945111AF1-176 GEN
Solar/Wind Harmer
5.891
247642Z2-115 C
Solar/Wind Harmer
0.003
270505AE1-170 C O1
Solar/Wind Harmer
7.629
25196008MFTGT1
Adder
1.398
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
7.162
958171AF2-111 GEN
Solar/Wind Harmer
17.857
274752CRETE EC ;2U
Adder
8.436
274753CRETE EC ;3U
Adder
8.436
274772LINCOLN ;3U
Adder
8.634
274724RIVER EC ;11
Adder
18.116
24386205FR-12G C
Solar/Wind Harmer
0
274814UNIV PK N;0U
Adder
5.159
274807UNIV PK N;3U
Adder
5.148
274811UNIV PK N;7U
Adder
5.114
972167AH1-666 GEN
Solar/Wind Harmer
5.69
274803UNIV PARK;6U
Adder
5.941
24728705AND G3
Adder
8.173
24728505AND G1
Adder
3.908
274887GEN-1.85
Solar/Wind Harmer
0.185
276843GEN-1.7
Solar/Wind Harmer
0.23
276806AD2-047 C O1
Solar/Wind Harmer
4.027
274826FISK ;BP
Adder
11.151
972038AH1-567 GEN2
Adder
0.372
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
23.191
972259AH1-714 GEN
Adder
19.413
274676JOLIET 29;8U
Adder
30.039
274729ELWOOD EC;1P
Adder
16.687
274730ELWOOD EC;6P
Adder
16.687
274734ELWOOD EC;8P
Adder
16.687
274736ELWOOD EC;9P
Adder
16.687
943121AE2-341 GEN
Solar/Wind Harmer
11.83
943591AF1-030 GEN
Solar/Wind Harmer
7.867
270541AE2-072 C
Solar/Wind Harmer
0
274862TOP CROP ;2U
Solar/Wind Harmer
0.951
274682WAUKEGAN ;7U
Adder
18.096
276868AE1-113 GEN
Solar/Wind Harmer
1.403
274879MINONK ;1U
Solar/Wind Harmer
0.293
946671AF1-331 GEN
Solar/Wind Harmer
0.745
274855GSG-6 ;RU
Solar/Wind Harmer
0.255
274850MENDOTA H;RU
Solar/Wind Harmer
0.081
970193AG2-126 GEN
Solar/Wind Harmer
10.468
970571AG2-364 GEN
Solar/Wind Harmer
13.944
964991AG1-363 GEN
Solar/Wind Helper
5.155
238108AE1-109 GEN1
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238127S14_GEN_2
Solar/Wind Helper
0.831
238175AF1-290_GEN
Solar/Wind Helper
0.158
238152AF2-075_GEN
Solar/Wind Helper
0.713
23777901MDS_W4-102
Solar/Wind Helper
0.178
23562501BACKB
Solar/Wind Helper
1.012
235063AE1-101 C2
Solar/Wind Helper
1.672
237001AB1-127_GEN
Solar/Wind Helper
0.445
237048AF1-022 C
Solar/Wind Helper
0.184
316415AF1-147_GEN2
Solar/Wind Helper
0.895
205916AD1-020 GEN
Solar/Wind Helper
1.725
208835TUHI V3-051
Solar/Wind Helper
0.022
205932AD2-116_GEN
Solar/Wind Helper
0.512
233918AB1-142 GEN
Solar/Wind Helper
0.506
233944AB2-135 GEN
Solar/Wind Helper
0.594
232426Y1-080 FULL
Solar/Wind Helper
0.039
233996TM1833_GEN
Solar/Wind Helper
0.207
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232404W1-003 C
Solar/Wind Helper
0.511
232408W1-005 C
Solar/Wind Helper
0.511
316447AC1-158 HLD
Solar/Wind Helper
2.868
316044AC1-158 PL1
Solar/Wind Helper
1.303
228729W2-030 C
Solar/Wind Helper
0.111
219766PARADISE C
Solar/Wind Helper
0.055
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.115
205956AE1-196_GEN
Solar/Wind Helper
0.512
233915AB1-141 GEN
Solar/Wind Helper
0.506
233901CHERRYDALE C
Solar/Wind Helper
0.234
233940AF2-379 C
Solar/Wind Helper
0.062
232432Z2-076 GEN
Solar/Wind Helper
0.067
315651AD1-115 GEN
Solar/Wind Helper
0.793
230434AG1-499 GEN
Solar/Wind Helper
0.232
228728W1-130C
Solar/Wind Helper
0.054
230407AD2-065 C
Solar/Wind Helper
0.041
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219615MILLCREEK C
Solar/Wind Helper
0.027
20715028HAN_X4-015
Solar/Wind Helper
0.057
20720728JCB_W1-129
Solar/Wind Helper
0.057
207445AB1-138_GEN
Solar/Wind Helper
0.105
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.191
316164AC1-076 GEN
Solar/Wind Helper
1.105
20675528CPH_W2-050
Solar/Wind Helper
0.114
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.096
20676428JCR_X2-075
Solar/Wind Helper
0.068
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.085
20675128HRM_W1-127
Solar/Wind Helper
0.03
209027LOR2_Q27
Solar/Wind Helper
1.031
212266LOR1
Solar/Wind Helper
0.3
203955AF1-039 C O1
Solar/Wind Helper
0.33
971171AH1-044 GEN
Solar/Wind Harmer
9.057
203975AE1-071-GEN
Solar/Wind Helper
2.516
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714528FRN_Y2-051
Solar/Wind Helper
0.057
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
218440SUMMTASSOC C
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207530AG1-191 GEN
Solar/Wind Helper
0.067
207439AE1-081 C O1
Solar/Wind Helper
0.019
20676328BVR_Y1-020
Solar/Wind Helper
0.027
207484AF2-139 C O1
Solar/Wind Helper
0.085
20674928WA_W3-044
Solar/Wind Helper
0.099
20674628WNG_W3-110
Solar/Wind Helper
0.09
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
207518AF1-320_GEN
Solar/Wind Helper
1.58
20675828AU_W4-064
Solar/Wind Helper
0.03
211065PSPA IPP
Solar/Wind Helper
0.152
961301AF2-421 GEN
Solar/Wind Helper
0.441
963151AG1-164 GEN
Solar/Wind Helper
0.441
202652Y1-033 WT C
Solar/Wind Helper
0.5
959091AF2-200 GEN
Solar/Wind Harmer
9.057
274683WAUKEGAN ;8U
Adder
9.636
962691AG1-118 GEN
Solar/Wind Harmer
21.036
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
7.415
942111AE2-223 GEN
Solar/Wind Harmer
2.266
316097T157 G90
Solar/Wind Helper
1.51
235054AD2-180 GEN
Solar/Wind Helper
2.04
23585401KL_K28_T16
Solar/Wind Helper
1.489
235531U2-073 GEN
Solar/Wind Helper
3.327
238117U2-030
Solar/Wind Helper
0.343
238147AE2-230_GEN1
Solar/Wind Helper
0.499
238148AE2-230_GEN2
Solar/Wind Helper
0.499
238149AF1-291A_GEN
Solar/Wind Helper
0.143
235020AA1-095 C
Solar/Wind Helper
0.053
23751201ROTHROCK
Solar/Wind Helper
0.828
237061AD1-155 GEN
Solar/Wind Helper
1.767
238221AF1-254 C O1
Solar/Wind Helper
0.277
237080AD1-060 GEN
Solar/Wind Helper
0.344
235062AE1-101 C1
Solar/Wind Helper
1.672
316411AF1-147_GEN1
Solar/Wind Helper
0.895
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.37
223402AF1-300 C
Solar/Wind Helper
0.37
316006AB2-029 C
Solar/Wind Helper
0.118
233982AB2-133 GEN
Solar/Wind Helper
0.362
233930AB2-032 GEN
Solar/Wind Helper
0.383
232424Y1-079 C
Solar/Wind Helper
0.117
232436AB1-176 C
Solar/Wind Helper
0.045
233946AB2-136 GEN
Solar/Wind Helper
0.573
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.968
232410W1-006 C
Solar/Wind Helper
0.511
232428Y3-058 C
Solar/Wind Helper
0.341
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.234
233954AC2-188 GEN
Solar/Wind Helper
0.234
316045AC1-158 PL2
Solar/Wind Helper
4.17
316450AC1-158 RIC
Solar/Wind Helper
0.348
230511AF1-262
Solar/Wind Helper
0.015
230433AD2-135 GEN
Solar/Wind Helper
0.017
228754AB1-001 C
Solar/Wind Helper
0.026
219904AC1-010 C
Solar/Wind Helper
0.061
219912AD2-042 GEN
Solar/Wind Helper
0.151
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219906AC1-017 C
Solar/Wind Helper
0.042
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.132
214067T20SOLAR
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.064
207459AE1-142 C O1
Solar/Wind Helper
0.292
20714828MDF_W3-079
Solar/Wind Helper
0.131
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
20675428EAM_W2-061
Solar/Wind Helper
0.016
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.023
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.169
20674828DL_W4-046
Solar/Wind Helper
0.008
971341AH1-150 GEN
Solar/Wind Harmer
9.057
971343AH1-151 GEN
Solar/Wind Harmer
9.057
208835TUHI V3-051
Solar/Wind Helper
0.022
233935AB2-179 C
Solar/Wind Helper
1.278
233987AB2-037 GEN
Solar/Wind Helper
2.36
233933AB2-153 GEN
Solar/Wind Helper
0.234
232422X3-066 FULL
Solar/Wind Helper
0.115
232417X3-008 C
Solar/Wind Helper
0.234
233964AF2-378 GEN
Solar/Wind Helper
0.042
233923SMA
Solar/Wind Helper
0.757
233997TMININ_4.2
Solar/Wind Helper
0.207
232406W1-004 FULL
Solar/Wind Helper
0.511
232434Z2-077 GEN
Solar/Wind Helper
0.128
233950AC2-186 GEN
Solar/Wind Helper
0.117
230415AB2-049 C
Solar/Wind Helper
0.031
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
219291REEVESSOUT C
Solar/Wind Helper
0.012
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.312
219612MATRIX C
Solar/Wind Helper
0.024
205941AD2-115 GEN
Solar/Wind Helper
0.499
20716928W4-060COL
Solar/Wind Helper
0.052
219249CENTRALDIV C
Solar/Wind Helper
0.01
217213AMBOY SO C
Solar/Wind Helper
0.029
207442AE1-156 GEN
Solar/Wind Helper
0.328
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
207511W3-106 GEN
Solar/Wind Helper
0.027
20671928W4-073
Solar/Wind Helper
0.09
20674128FR_U2-059
Solar/Wind Helper
0.004
209116AE2-175 GEN
Solar/Wind Helper
1.792
211065PSPA IPP
Solar/Wind Helper
0.152
963161AG1-165 GEN
Solar/Wind Helper
0.441
957471AF2-041 GEN
Solar/Wind Harmer
13.586
959081AF2-199 GEN
Solar/Wind Harmer
4.529
971067AG2-660 GEN
Solar/Wind Harmer
1.51
CPLELTFEXP_CPLE->PJM
CLTF
0.571
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.151
NYPJM->LTFIMP_NY
CLTF
4.827
LGEELTFEXP_LGEE->PJM
CLTF
6.715
WECLTFEXP_WEC->PJM
CLTF
3.806
AG2-052LTFEXP_AG2-052->PJM
LTF
0.238
AH1-155LTFEXP_AH1-155->PJM
LTF
0.358
LAGNLTFEXP_LAGN->PJM
CLTF
14.738
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.655
TVALTFEXP_TVA->PJM
CLTF
7.243
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.362
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.914
MECLTFEXP_MEC->PJM
CLTF
15.818
SIGELTFEXP_SIGE->PJM
CLTF
0.502

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-012_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-012_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.01 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5005.84
MW Contribution:
25.23
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24318805MLG1
50/50
10
23559001PLEAS1
50/50
5.445
270051AF1-062 GEN
50/50
11.971
962771AG1-126 GEN
Solar/Wind Harmer
40.867
970153AG2-106 GEN
Solar/Wind Harmer
17.82
961921AG1-034 GEN
Solar/Wind Harmer
15.881
270284AF1-227 GEN1
Solar/Wind Harmer
6.884
270287AF1-227 GEN3
Solar/Wind Harmer
2.547
942051AE2-217 GEN
Solar/Wind Harmer
21.323
942871AE2-306 GEN
Solar/Wind Harmer
1.07
270391AF1-285 GEN3
Solar/Wind Harmer
0.549
960801AF2-371 GEN
Solar/Wind Harmer
2.983
964871AG1-351 GEN
Solar/Wind Harmer
2.06
270512AE1-227 GEN2
Solar/Wind Harmer
2.449
270119AB2-067 GEN1
50/50
7.05
270120AB2-067 GEN2
50/50
7.05
24318905MLG2
50/50
7.451
270054AF2-122 C O1
Solar/Wind Harmer
4.054
270349AD2-093_GEN
Solar/Wind Harmer
4.513
270471AD2-092_GEN
Solar/Wind Harmer
4.513
946101AF1-275 GEN
Solar/Wind Harmer
1.838
253383AE2-342_GEN
Solar/Wind Harmer
1.057
938701AE1-092 GEN
Solar/Wind Harmer
24.428
942861AE2-305 GEN
Solar/Wind Harmer
9.201
270462AD2-086
Solar/Wind Harmer
8.12
972159AH1-661 GEN
Adder
1.163
241960AC2-195 GEN
Solar/Wind Harmer
3.204
270269AC2-059
Solar/Wind Harmer
10.672
253378AE2-206_GEN
Solar/Wind Harmer
4.074
25326509SID D
Adder
1.478
253415AE1-040 GEN
Solar/Wind Harmer
1.252
25326109MON D
Adder
1.457
246937BC-WTG2
Solar/Wind Harmer
4.329
971073AG2-665 GEN
Solar/Wind Harmer
8.835
970879AG2-548 GEN
Solar/Wind Harmer
1.284
25322209TAIT E
Adder
10.744
25322209TAIT E
Adder
10.502
942801AE2-298 GEN
Solar/Wind Harmer
1.666
247607V1-011 GEN
Solar/Wind Harmer
4.348
253370AE2-315 SEC1
Adder
2.2
270246TR4_N_V150
Solar/Wind Harmer
0.933
270247TR4_N_V136
Solar/Wind Harmer
0.933
247522W1-056 GEN
Solar/Wind Harmer
2.469
253349AC2-067 GEN
Solar/Wind Harmer
2.225
253400AC2-068 GEN
Solar/Wind Harmer
0.895
927014AC1-188 GEN
Solar/Wind Harmer
1.72
944231AF1-091 GEN
Solar/Wind Harmer
19.433
942221AE2-234 GEN
Solar/Wind Harmer
3.759
944541AF1-119 GEN
Solar/Wind Harmer
4.494
960971AF2-388 GEN
Solar/Wind Harmer
11.731
247620Y3-023
Adder
0.492
970349AG2-230 GEN
Solar/Wind Harmer
16.027
247621Y3-024
Adder
0.257
25183208HLCRTG
Solar/Wind Harmer
6.454
970883AG2-550 GEN
Solar/Wind Harmer
10.668
970885AG2-551 GEN
Solar/Wind Harmer
2.481
962581AG1-107 GEN
Solar/Wind Harmer
5.371
961491AF2-440 GEN
Solar/Wind Harmer
2.232
270201AC2-176 GEN
Solar/Wind Harmer
5.48
961051AF2-396 GEN
Solar/Wind Harmer
16.91
961051AF2-396 GEN
Solar/Wind Harmer
7.865
964611AG1-324 GEN
Solar/Wind Harmer
0.557
270031AE2-169
Solar/Wind Harmer
8.665
270599AE1-208 GEN
Solar/Wind Harmer
8.665
25194408D.CRK1
Adder
8.037
25194508D.CRK3
Adder
1.503
24728805RICHG1
Adder
3.989
24728905RICHG2
Adder
3.989
970935AG2-582 GEN
Adder
238.716
274770LINCOLN ;1U
Adder
8.764
274771LINCOLN ;2U
Adder
8.764
274805UNIV PK N;1U
Adder
5.205
274808UNIV PK N;4U
Adder
5.171
274674JOLIET 9 ;6U
Adder
0.246
316097T157 G90
Solar/Wind Helper
1.71
238147AE2-230_GEN1
Solar/Wind Helper
0.556
238148AE2-230_GEN2
Solar/Wind Helper
0.556
238149AF1-291A_GEN
Solar/Wind Helper
0.159
237061AD1-155 GEN
Solar/Wind Helper
1.974
235054AD2-180 GEN
Solar/Wind Helper
2.118
235531U2-073 GEN
Solar/Wind Helper
3.481
23585401KL_K28_T16
Solar/Wind Helper
1.534
235020AA1-095 C
Solar/Wind Helper
0.058
238117U2-030
Solar/Wind Helper
0.357
238221AF1-254 C O1
Solar/Wind Helper
0.297
237080AD1-060 GEN
Solar/Wind Helper
0.369
235062AE1-101 C1
Solar/Wind Helper
1.786
316411AF1-147_GEN1
Solar/Wind Helper
0.984
23751201ROTHROCK
Solar/Wind Helper
0.821
237006AB1-125 GEN
Solar/Wind Helper
0.132
316006AB2-029 C
Solar/Wind Helper
0.131
223401AF1-299 GEN
Solar/Wind Helper
0.389
223402AF1-300 C
Solar/Wind Helper
0.389
316045AC1-158 PL2
Solar/Wind Helper
4.643
316450AC1-158 RIC
Solar/Wind Helper
0.387
3132123MT JACKSON
Solar/Wind Helper
0.767
233930AB2-032 GEN
Solar/Wind Helper
0.389
233982AB2-133 GEN
Solar/Wind Helper
0.367
232424Y1-079 C
Solar/Wind Helper
0.119
232436AB1-176 C
Solar/Wind Helper
0.045
233946AB2-136 GEN
Solar/Wind Helper
0.581
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.982
232410W1-006 C
Solar/Wind Helper
0.518
232428Y3-058 C
Solar/Wind Helper
0.346
234015AF2-250 C
Solar/Wind Helper
0.039
233952AC2-187 GEN
Solar/Wind Helper
0.238
233954AC2-188 GEN
Solar/Wind Helper
0.238
966001AG1-469 GEN
Solar/Wind Helper
0.256
230511AF1-262
Solar/Wind Helper
0.015
230433AD2-135 GEN
Solar/Wind Helper
0.017
228754AB1-001 C
Solar/Wind Helper
0.026
219904AC1-010 C
Solar/Wind Helper
0.061
219912AD2-042 GEN
Solar/Wind Helper
0.152
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219906AC1-017 C
Solar/Wind Helper
0.042
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.133
214067T20SOLAR
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.064
207459AE1-142 C O1
Solar/Wind Helper
0.293
20714828MDF_W3-079
Solar/Wind Helper
0.132
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
20675428EAM_W2-061
Solar/Wind Helper
0.016
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.023
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.169
20674828DL_W4-046
Solar/Wind Helper
0.008
972239AH1-704 GEN
50/50
3.095
270459AD2-067 GEN
Solar/Wind Harmer
10.428
961821AG1-024 GEN
Solar/Wind Harmer
10.588
241955AC1-078 GEN
Solar/Wind Harmer
8.918
241973AD2-163_GEN1
Solar/Wind Harmer
2.358
241974AD2-163_GEN2
Solar/Wind Harmer
2.358
940611AE2-048 GEN
Solar/Wind Harmer
26.008
941391AE2-136 GEN
Solar/Wind Harmer
13.477
270223U2-072_GEN1
Solar/Wind Harmer
2.33
270224U2-072_GEN2
Solar/Wind Harmer
2.33
270227U2-072_GEN3
Solar/Wind Harmer
2.33
270228U2-072_GEN4
Solar/Wind Harmer
2.33
270231U2-072_GEN5
Solar/Wind Harmer
2.33
270578AF1-285 GEN2
Solar/Wind Harmer
0.549
943861AF1-054 GEN
Solar/Wind Harmer
4.542
943851AF1-053 GEN
Solar/Wind Harmer
2.195
945631AF1-228 GEN
Solar/Wind Harmer
5.525
270302AB2-170 GEN
Solar/Wind Harmer
9.776
270432AC2-029 GEN
Solar/Wind Harmer
8.117
970179AG2-119 GEN
Solar/Wind Harmer
9.237
253338AC1-165 GEN
Solar/Wind Harmer
1.249
253343AC1-166 GEN
Solar/Wind Harmer
1.249
241972AD1-140 GEN
Solar/Wind Harmer
5.07
270263AC1-001 GEN
Solar/Wind Harmer
1.18
971567AH1-282 GEN
Solar/Wind Harmer
5.635
270377AD1-106 GEN
Solar/Wind Harmer
5.917
966831AG1-554 GEN
Solar/Wind Harmer
1.337
270291AC1-194 GEN
Solar/Wind Harmer
5.669
270340AC2-060 GEN
Solar/Wind Harmer
3.354
957201AF2-014 GEN
Solar/Wind Harmer
5.019
270435AC2-044 GEN
Solar/Wind Harmer
2.213
270007AE1-245 C
Solar/Wind Harmer
5.939
253372AE2-315 SEC3
Adder
2.081
253372AE2-315 SEC3
Adder
2.081
247521TR3_G114
Solar/Wind Harmer
3.687
270191TR4_S_V150
Solar/Wind Harmer
3.29
965051AG1-369 GEN
Solar/Wind Harmer
5.479
25306009OHH W.
Adder
3.158
965041AG1-368 GEN
Solar/Wind Harmer
10.944
959331AF2-224 GEN
Solar/Wind Harmer
10.939
253406AD2-031_GEN
Solar/Wind Harmer
1.391
270404AC1-167 GEN
Solar/Wind Harmer
1.18
963791AG1-232 GEN
Solar/Wind Harmer
14.614
253433AC1-085 GEN1
Solar/Wind Harmer
5.738
253432AC1-085 GEN2
Solar/Wind Harmer
0.289
270071AF1-092 GEN
Solar/Wind Harmer
16.191
24729505KEY G4
Adder
6.997
945641AF1-229 GEN
Solar/Wind Harmer
3.912
970031AG2-029 GEN
Solar/Wind Harmer
26.913
958711AF2-162 GEN
Solar/Wind Harmer
1.086
945581AF1-223 GEN
Solar/Wind Harmer
4.845
971029AG2-637 GEN
Solar/Wind Harmer
16.005
270499AE1-146 GEN
Solar/Wind Harmer
2.679
270543AE2-219 C
Solar/Wind Harmer
10.668
247536S-71 GEN
Solar/Wind Harmer
4.316
961761AG1-017 GEN
Solar/Wind Harmer
0.456
964611AG1-324 GEN
Solar/Wind Harmer
4.154
971771AH1-392 GEN
Solar/Wind Harmer
9.58
944161AF1-084 GEN
Solar/Wind Harmer
2.352
25196408WSDLE3
Adder
9.385
25196308WSDLE2
Adder
9.303
25196208WSDLE1
Adder
9.28
25196708WSDLE6
Adder
9.256
25196508WSDLE4
Adder
9.023
25196108MFTGT2
Adder
1.604
25196108MFTGT2
Adder
1.489
274775LINCOLN ;6U
Adder
8.764
274776LINCOLN ;7U
Adder
8.764
274777LINCOLN ;8U
Adder
8.764
972037AH1-567 GEN1
Adder
0.189
274827FISK ;RP
Adder
8.022
274800UNIV PARK;3U
Adder
6.026
274801UNIV PARK;4U
Adder
6.026
972228AH1-698 GEN2
Adder
3.828
972227AH1-698 GEN1
Adder
2.695
274687WILL CNTY;4U
Adder
28.802
274687WILL CNTY;4U
Adder
28.802
274675JOLIET 29;7U
Adder
31.606
274675JOLIET 29;7U
Adder
30.477
274728ELWOOD EC;5P
Adder
16.929
274731ELWOOD EC;2P
Adder
16.929
274733ELWOOD EC;3P
Adder
16.929
274735ELWOOD EC;4P
Adder
16.929
23750701CROSSCHOOL
Solar/Wind Helper
1.591
238169AE2-226 GEN1
Solar/Wind Helper
0.777
238170AE2-226 GEN2
Solar/Wind Helper
0.777
238118U2-030_1
Solar/Wind Helper
0.357
3138216PACIFIC
Solar/Wind Helper
0.049
23779801AA1-109
Solar/Wind Helper
0.208
237030AB1-096 C
Solar/Wind Helper
0.071
237025AB1-124 C
Solar/Wind Helper
0.176
226929AD2-058 GEN
Solar/Wind Helper
0.108
3141426STAFORD
Solar/Wind Helper
0.058
315651AD1-115 GEN
Solar/Wind Helper
0.883
316164AC1-076 GEN
Solar/Wind Helper
1.232
23750501ELLIOTTS
Solar/Wind Helper
0.631
205917AD1-020 ES
Solar/Wind Helper
0.381
959381AF2-229 GEN
Solar/Wind Helper
0.368
20390526W1-045 C
Solar/Wind Helper
0.361
205943AE1-185 GEN
Solar/Wind Helper
0.521
205956AE1-196_GEN
Solar/Wind Helper
0.521
233915AB1-141 GEN
Solar/Wind Helper
0.514
233901CHERRYDALE C
Solar/Wind Helper
0.238
233940AF2-379 C
Solar/Wind Helper
0.063
232432Z2-076 GEN
Solar/Wind Helper
0.068
230434AG1-499 GEN
Solar/Wind Helper
0.234
228728W1-130C
Solar/Wind Helper
0.055
230407AD2-065 C
Solar/Wind Helper
0.041
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.078
219615MILLCREEK C
Solar/Wind Helper
0.027
20715028HAN_X4-015
Solar/Wind Helper
0.058
20720728JCB_W1-129
Solar/Wind Helper
0.058
207445AB1-138_GEN
Solar/Wind Helper
0.106
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.192
20675528CPH_W2-050
Solar/Wind Helper
0.114
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.097
20676428JCR_X2-075
Solar/Wind Helper
0.068
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.084
20675128HRM_W1-127
Solar/Wind Helper
0.03
270518AE2-148 GEN
Solar/Wind Harmer
13.997
958581AF2-149 GEN
Solar/Wind Harmer
4.955
971199AH1-059 GEN
Solar/Wind Harmer
2.432
24721905FLATG4
Adder
23.444
253325AC1-069 GEN
Solar/Wind Harmer
1.205
970065AG2-057 GEN
Solar/Wind Harmer
0.972
276820AF1-078_GEN
Solar/Wind Harmer
1.81
270588AE1-091_GEN
Solar/Wind Harmer
12.281
961961AG1-039 GEN
Solar/Wind Harmer
3.18
246938BC-WTG3
Solar/Wind Harmer
4.404
270491AE1-102 GEN2
Solar/Wind Harmer
1.439
970879AG2-548 GEN
Solar/Wind Harmer
8.835
958091AF2-103 GEN
Solar/Wind Harmer
0.178
960071AF2-298 GEN
Solar/Wind Harmer
1.664
253303V4-073 C
Solar/Wind Harmer
0.127
253370AE2-315 SEC1
Adder
2.2
253371AE2-315 SEC2
Adder
2.081
24695305TIMB G C
Solar/Wind Harmer
3.661
965021AG1-366 GEN
Solar/Wind Harmer
2.544
270044AE2-322 C
Solar/Wind Harmer
1.431
253394AE2-221_GEN
Solar/Wind Harmer
4.932
957541AF2-048 GEN
Solar/Wind Harmer
1.72
270043AE2-236 GEN
Solar/Wind Harmer
5.961
944531AF1-118 GEN
Solar/Wind Harmer
37.819
253317AC1-085 GEN4
Solar/Wind Harmer
9.041
946181AF1-283 GEN
Solar/Wind Harmer
14.038
270063AE2-323 C
Solar/Wind Harmer
2.363
270541AE2-072 C
Solar/Wind Harmer
4.86
971191AH1-055 GEN
Solar/Wind Harmer
20.005
971347AH1-153 GEN
Solar/Wind Harmer
5.342
247643Z2-116 C
Solar/Wind Harmer
0.074
962031AG1-047 GEN
Solar/Wind Harmer
3.224
957741AF2-068 GEN
Solar/Wind Harmer
15.993
945111AF1-176 GEN
Solar/Wind Harmer
6.028
270505AE1-170 C O1
Solar/Wind Harmer
15.984
252519AF1-045_GEN
Solar/Wind Harmer
3.876
252524AE2-267 GEN
Solar/Wind Harmer
1.675
25196608WSDLE5
Adder
9.116
25194608D.CRK4
Adder
1.747
270367AC2-061_GEN
Solar/Wind Harmer
3.375
23906502RICHG2&3
Adder
1.268
23906402RICHG1
Adder
1.268
25196008MFTGT1
Adder
1.409
274752CRETE EC ;2U
Adder
8.571
274753CRETE EC ;3U
Adder
8.571
274724RIVER EC ;11
Adder
18.401
274772LINCOLN ;3U
Adder
8.764
274814UNIV PK N;0U
Adder
5.24
274807UNIV PK N;3U
Adder
5.228
274811UNIV PK N;7U
Adder
5.194
274803UNIV PARK;6U
Adder
6.031
274826FISK ;BP
Adder
11.319
972038AH1-567 GEN2
Adder
0.377
972259AH1-714 GEN
Adder
19.698
274676JOLIET 29;8U
Adder
30.477
274729ELWOOD EC;1P
Adder
16.929
274730ELWOOD EC;6P
Adder
16.929
274734ELWOOD EC;8P
Adder
16.929
274736ELWOOD EC;9P
Adder
16.929
964991AG1-363 GEN
Solar/Wind Helper
5.569
238108AE1-109 GEN1
Solar/Wind Helper
0.122
238110AE1-109 GEN3
Solar/Wind Helper
0.122
238152AF2-075_GEN
Solar/Wind Helper
0.794
238175AF1-290_GEN
Solar/Wind Helper
0.173
238127S14_GEN_2
Solar/Wind Helper
0.87
23777901MDS_W4-102
Solar/Wind Helper
0.192
235063AE1-101 C2
Solar/Wind Helper
1.786
237001AB1-127_GEN
Solar/Wind Helper
0.476
316415AF1-147_GEN2
Solar/Wind Helper
0.984
23562501BACKB
Solar/Wind Helper
1
316447AC1-158 HLD
Solar/Wind Helper
3.193
316044AC1-158 PL1
Solar/Wind Helper
1.451
237048AF1-022 C
Solar/Wind Helper
0.18
205916AD1-020 GEN
Solar/Wind Helper
1.77
208835TUHI V3-051
Solar/Wind Helper
0.022
205932AD2-116_GEN
Solar/Wind Helper
0.521
233918AB1-142 GEN
Solar/Wind Helper
0.514
233944AB2-135 GEN
Solar/Wind Helper
0.603
232426Y1-080 FULL
Solar/Wind Helper
0.04
3147666LOUISA
Solar/Wind Helper
0.962
233996TM1833_GEN
Solar/Wind Helper
0.21
233998TM1NIN_3.36
Solar/Wind Helper
0.21
232404W1-003 C
Solar/Wind Helper
0.518
232408W1-005 C
Solar/Wind Helper
0.518
316192AB2-158 GEN
Solar/Wind Helper
1.618
228729W2-030 C
Solar/Wind Helper
0.112
219766PARADISE C
Solar/Wind Helper
0.055
203975AE1-071-GEN
Solar/Wind Helper
2.543
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.116
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.065
20714528FRN_Y2-051
Solar/Wind Helper
0.058
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
218440SUMMTASSOC C
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207530AG1-191 GEN
Solar/Wind Helper
0.066
207439AE1-081 C O1
Solar/Wind Helper
0.019
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20674628WNG_W3-110
Solar/Wind Helper
0.09
207484AF2-139 C O1
Solar/Wind Helper
0.084
20674928WA_W3-044
Solar/Wind Helper
0.099
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
207518AF1-320_GEN
Solar/Wind Helper
1.573
20675828AU_W4-064
Solar/Wind Helper
0.03
211065PSPA IPP
Solar/Wind Helper
0.151
270166AC1-044 GEN3
50/50
7.05
23559101PLEAS2
50/50
5.445
270122AB2-093 CT
50/50
4.1
962761AG1-125 GEN
Solar/Wind Harmer
40.867
970149AG2-104 GEN
Solar/Wind Harmer
25.235
970155AG2-107 GEN
Solar/Wind Harmer
17.82
270286AF1-227 GEN2
Solar/Wind Harmer
2.547
270520AE2-214 GEN
Solar/Wind Harmer
7.352
270391AF1-285 GEN3
Solar/Wind Harmer
1.427
270578AF1-285 GEN2
Solar/Wind Harmer
1.427
971995AH1-542 GEN
Solar/Wind Harmer
12.942
972269AH1-719 GEN
Adder
2.693
270317AD1-130_GEN
Solar/Wind Harmer
3.738
270485AE1-090_GEN
Solar/Wind Harmer
0.706
270510AE1-227 GEN1
Solar/Wind Harmer
2.885
253333AC1-068 GEN
Solar/Wind Harmer
1.205
241813AF1-122_GEN
Solar/Wind Harmer
6.22
971201AH1-060 GEN
Solar/Wind Harmer
1.944
270273AD2-016 GEN
Solar/Wind Harmer
3.042
241847AF2-150_GEN
Solar/Wind Harmer
4.61
246936BC-WTG1
Solar/Wind Harmer
4.329
270489AE1-102 GEN1
Solar/Wind Harmer
1.439
965421AG1-410 GEN
Solar/Wind Harmer
33.164
971073AG2-665 GEN
Solar/Wind Harmer
1.284
25326309TAIT D
Adder
1.207
253370AE2-315 SEC1
Adder
2.2
253371AE2-315 SEC2
Adder
2.081
270297AD1-101 GEN
Solar/Wind Harmer
2.226
965011AG1-365 GEN
Solar/Wind Harmer
10.939
270258AD1-119 GEN
Solar/Wind Harmer
2.219
253398AE2-221_GEN2
Solar/Wind Harmer
4.932
253316AC1-085 GEN3
Solar/Wind Harmer
9.041
946171AF1-282 GEN
Solar/Wind Harmer
10.799
965651AG1-433 GEN
Solar/Wind Harmer
5.866
270024AE2-089 GEN
Solar/Wind Harmer
5.027
958861AF2-177 GEN
Solar/Wind Harmer
11.712
960001AF2-291 GEN
Solar/Wind Harmer
3.236
24639705ELKHART HY
Adder
0.164
945371AF1-202 GEN
Solar/Wind Harmer
7.453
270216AD2-079_GEN
Solar/Wind Harmer
0.645
945111AF1-176 GEN
Solar/Wind Harmer
19.021
957891AF2-083 GEN
Solar/Wind Harmer
15.982
252516AE2-318_GEN
Solar/Wind Harmer
10.65
270449AD2-020 GEN
Solar/Wind Harmer
2.984
943021AE2-325 GEN
Solar/Wind Harmer
3.878
270222AC2-111 GEN
Solar/Wind Harmer
4.753
944031AF1-071 GEN
Solar/Wind Harmer
1.069
24441205WTRV SLR C
Solar/Wind Harmer
0.143
252510AF1-249 C
Solar/Wind Harmer
0.443
25194608D.CRK4
Adder
1.747
25196808ZIMRHP
Adder
79.955
23906502RICHG2&3
Adder
1.268
25196008MFTGT1
Adder
1.455
274751CRETE EC ;1U
Adder
8.571
274754CRETE EC ;4U
Adder
8.571
274723RIVER EC ;12
Adder
18.619
274773LINCOLN ;4U
Adder
8.764
274774LINCOLN ;5U
Adder
8.764
274812UNIV PK N;8U
Adder
5.194
274802UNIV PARK;5U
Adder
6.031
23920202STRYCT
Adder
1.44
274676JOLIET 29;8U
Adder
31.606
274732ELWOOD EC;7P
Adder
16.929
274674JOLIET 9 ;6U
Adder
15.855
23583801GRNGAP
Solar/Wind Helper
6.383
316095T157 G97
Solar/Wind Helper
1.71
238109AE1-109 GEN2
Solar/Wind Helper
0.122
238185AF2-356 C
Solar/Wind Helper
2.787
23546401DTGZ2-030
Solar/Wind Helper
0.1
238120AE2-309 GEN
Solar/Wind Helper
0.557
238126S14_GEN_1
Solar/Wind Helper
0.87
237038AE2-054 C
Solar/Wind Helper
0.294
235067AD1-061 GEN
Solar/Wind Helper
0.481
237085AD2-009_GEN
Solar/Wind Helper
1.776
237002AB1-128_GEN
Solar/Wind Helper
0.477
3141196NOKESVL
Solar/Wind Helper
1.144
23777801MSM_W1-116
Solar/Wind Helper
0.123
226910AB2-157 C
Solar/Wind Helper
0.016
227287AC2-120 GEN
Solar/Wind Helper
0.377
23751101LEADS_P59
Solar/Wind Helper
1.984
3132273ORANGE
Solar/Wind Helper
0.049
208835TUHI V3-051
Solar/Wind Helper
0.022
233935AB2-179 C
Solar/Wind Helper
1.297
233987AB2-037 GEN
Solar/Wind Helper
2.395
233933AB2-153 GEN
Solar/Wind Helper
0.238
232422X3-066 FULL
Solar/Wind Helper
0.117
232417X3-008 C
Solar/Wind Helper
0.238
233964AF2-378 GEN
Solar/Wind Helper
0.043
3147666LOUISA
Solar/Wind Helper
0.553
233923SMA
Solar/Wind Helper
0.769
233997TMININ_4.2
Solar/Wind Helper
0.21
232406W1-004 FULL
Solar/Wind Helper
0.518
232434Z2-077 GEN
Solar/Wind Helper
0.13
233950AC2-186 GEN
Solar/Wind Helper
0.119
230415AB2-049 C
Solar/Wind Helper
0.031
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.117
219291REEVESSOUT C
Solar/Wind Helper
0.012
218660EHAMPSOLAR C
Solar/Wind Helper
0.034
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.313
966881AG1-559 GEN
Solar/Wind Helper
0.313
219612MATRIX C
Solar/Wind Helper
0.024
20716928W4-060COL
Solar/Wind Helper
0.052
205941AD2-115 GEN
Solar/Wind Helper
0.499
219249CENTRALDIV C
Solar/Wind Helper
0.01
217213AMBOY SO C
Solar/Wind Helper
0.029
207442AE1-156 GEN
Solar/Wind Helper
0.328
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.138
207511W3-106 GEN
Solar/Wind Helper
0.027
20671928W4-073
Solar/Wind Helper
0.09
20674128FR_U2-059
Solar/Wind Helper
0.004
209116AE2-175 GEN
Solar/Wind Helper
1.777
211065PSPA IPP
Solar/Wind Helper
0.151
960841AF2-375 GEN
Solar/Wind Harmer
0.624
CBM West 2LTFEXP_CBM-W2->PJM
CBM
111.457
NYPJM->LTFIMP_NY
CLTF
4.574
LGEELTFEXP_LGEE->PJM
CLTF
6.731
WECLTFEXP_WEC->PJM
CLTF
3.853
AG2-052LTFEXP_AG2-052->PJM
LTF
0.242
AH1-155LTFEXP_AH1-155->PJM
LTF
0.363
LAGNLTFEXP_LAGN->PJM
CLTF
14.456
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.226
TVALTFEXP_TVA->PJM
CLTF
7.078
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.111
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.423
MECLTFEXP_MEC->PJM
CLTF
15.924
SIGELTFEXP_SIGE->PJM
CLTF
0.504

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P1-2_MP-500-008A_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:125.57 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4761.71
MW Contribution:
17.93
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
6.887
270120AB2-067 GEN2
50/50
6.887
24318905MLG2
50/50
6.869
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0
942861AE2-305 GEN
Solar/Wind Harmer
6.105
938701AE1-092 GEN
Solar/Wind Harmer
12.459
971655AH1-328 GEN
Solar/Wind Harmer
2.753
270462AD2-086
Solar/Wind Harmer
0
270269AC2-059
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
1.079
970329AG2-216 GEN
Solar/Wind Harmer
3.232
970935AG2-582 GEN
Adder
241.832
25326509SID D
Adder
1.398
25326109MON D
Adder
1.388
971073AG2-665 GEN
Solar/Wind Harmer
5.401
970879AG2-548 GEN
Solar/Wind Harmer
1.228
25322209TAIT E
Adder
10.24
25322209TAIT E
Adder
10.01
253370AE2-315 SEC1
Adder
2.099
246937BC-WTG2
Solar/Wind Harmer
0.292
270246TR4_N_V150
Solar/Wind Harmer
0.046
270247TR4_N_V136
Solar/Wind Harmer
0.046
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.306
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25183208HLCRTG
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.476
960971AF2-388 GEN
Solar/Wind Harmer
4.179
942221AE2-234 GEN
Solar/Wind Harmer
2.858
970621AG2-405 GEN
Solar/Wind Harmer
1.302
25194408D.CRK1
Adder
7.692
25194508D.CRK3
Adder
1.438
970883AG2-550 GEN
Solar/Wind Harmer
7.088
970885AG2-551 GEN
Solar/Wind Harmer
2.363
247621Y3-024
Adder
0.245
252509AD1-136 GEN
Solar/Wind Harmer
0.035
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.531
970349AG2-230 GEN
Solar/Wind Harmer
10.604
270031AE2-169
Solar/Wind Harmer
3.884
270599AE1-208 GEN
Solar/Wind Harmer
6.473
270383AD1-128 GEN
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
16.273
247620Y3-023
Adder
0.465
926881AC1-175 GEN
Solar/Wind Harmer
0
971613AH1-306 GEN
Solar/Wind Harmer
3.374
24728805RICHG1
Adder
3.809
24728905RICHG2
Adder
3.809
970291AG2-192 GEN
Solar/Wind Harmer
0.913
970291AG2-192 GEN
Solar/Wind Harmer
0.421
961051AF2-396 GEN
Solar/Wind Harmer
14.035
961051AF2-396 GEN
Solar/Wind Harmer
9.356
965681AG1-436 GEN
Solar/Wind Harmer
8.747
965791AG1-447 GEN
Solar/Wind Harmer
6.414
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
8.341
274771LINCOLN ;2U
Adder
8.341
274805UNIV PK N;1U
Adder
4.952
274808UNIV PK N;4U
Adder
4.919
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.78
274888KELLY CRK;1U
Solar/Wind Harmer
0.4
276776AD2-060 GEN
Solar/Wind Harmer
0.732
958011AF2-095 GEN
Solar/Wind Harmer
9.886
970941AG2-585 GEN
Solar/Wind Harmer
3.776
276897AD1-100 C
Solar/Wind Harmer
17.145
276893AG1-478 C
Solar/Wind Harmer
0.456
970241AG2-163 GEN
Solar/Wind Harmer
3.982
958481AF2-142 GEN
Solar/Wind Harmer
10.21
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
10.177
962691AG1-118 GEN
Solar/Wind Harmer
20.32
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
7.158
942111AE2-223 GEN
Solar/Wind Harmer
2.188
316097T157 G90
Solar/Wind Helper
1.459
238147AE2-230_GEN1
Solar/Wind Helper
0.481
238148AE2-230_GEN2
Solar/Wind Helper
0.481
238149AF1-291A_GEN
Solar/Wind Helper
0.137
235020AA1-095 C
Solar/Wind Helper
0.051
235531U2-073 GEN
Solar/Wind Helper
3.071
235054AD2-180 GEN
Solar/Wind Helper
1.845
237061AD1-155 GEN
Solar/Wind Helper
1.703
238117U2-030
Solar/Wind Helper
0.315
238221AF1-254 C O1
Solar/Wind Helper
0.267
237080AD1-060 GEN
Solar/Wind Helper
0.332
23585401KL_K28_T16
Solar/Wind Helper
1.332
235062AE1-101 C1
Solar/Wind Helper
1.608
316411AF1-147_GEN1
Solar/Wind Helper
0.865
237006AB1-125 GEN
Solar/Wind Helper
0.12
223401AF1-299 GEN
Solar/Wind Helper
0.357
223402AF1-300 C
Solar/Wind Helper
0.357
316006AB2-029 C
Solar/Wind Helper
0.114
23751201ROTHROCK
Solar/Wind Helper
0.696
233982AB2-133 GEN
Solar/Wind Helper
0.349
233930AB2-032 GEN
Solar/Wind Helper
0.37
232424Y1-079 C
Solar/Wind Helper
0.113
232436AB1-176 C
Solar/Wind Helper
0.043
233946AB2-136 GEN
Solar/Wind Helper
0.553
234036AF2-325 C
Solar/Wind Helper
0.041
233994AC2-023 GEN
Solar/Wind Helper
0.934
232410W1-006 C
Solar/Wind Helper
0.493
232428Y3-058 C
Solar/Wind Helper
0.329
234015AF2-250 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.226
233954AC2-188 GEN
Solar/Wind Helper
0.226
316045AC1-158 PL2
Solar/Wind Helper
4.03
316450AC1-158 RIC
Solar/Wind Helper
0.336
230511AF1-262
Solar/Wind Helper
0.014
230433AD2-135 GEN
Solar/Wind Helper
0.017
228754AB1-001 C
Solar/Wind Helper
0.025
219904AC1-010 C
Solar/Wind Helper
0.059
219912AD2-042 GEN
Solar/Wind Helper
0.146
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219906AC1-017 C
Solar/Wind Helper
0.041
219607WPEMNERT C
Solar/Wind Helper
0.078
219304NAMERICA C
Solar/Wind Helper
0.127
214067T20SOLAR
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.061
207459AE1-142 C O1
Solar/Wind Helper
0.282
20714828MDF_W3-079
Solar/Wind Helper
0.127
20742028HF_AC1-207
Solar/Wind Helper
0.137
218438BLK ROCK C
Solar/Wind Helper
0.026
971341AH1-150 GEN
Solar/Wind Harmer
8.748
971343AH1-151 GEN
Solar/Wind Harmer
8.748
972239AH1-704 GEN
50/50
2.774
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.899
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
945631AF1-228 GEN
Solar/Wind Harmer
0.001
943861AF1-054 GEN
Solar/Wind Harmer
3.014
943851AF1-053 GEN
Solar/Wind Harmer
2.087
270578AF1-285 GEN2
Solar/Wind Harmer
0.517
270432AC2-029 GEN
Solar/Wind Harmer
3.42
940611AE2-048 GEN
Solar/Wind Harmer
18.925
941391AE2-136 GEN
Solar/Wind Harmer
10.66
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.077
270263AC1-001 GEN
Solar/Wind Harmer
0.753
241972AD1-140 GEN
Solar/Wind Harmer
0.821
970179AG2-119 GEN
Solar/Wind Harmer
6.643
270291AC1-194 GEN
Solar/Wind Harmer
0
270340AC2-060 GEN
Solar/Wind Harmer
0.001
253372AE2-315 SEC3
Adder
1.985
253372AE2-315 SEC3
Adder
1.985
25306009OHH W.
Adder
3.011
253406AD2-031_GEN
Solar/Wind Harmer
0.539
270377AD1-106 GEN
Solar/Wind Harmer
2.755
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.918
247521TR3_G114
Solar/Wind Harmer
0.261
965051AG1-369 GEN
Solar/Wind Harmer
3.6
971567AH1-282 GEN
Solar/Wind Harmer
5.517
959331AF2-224 GEN
Solar/Wind Harmer
5.044
270007AE1-245 C
Solar/Wind Harmer
0
965041AG1-368 GEN
Solar/Wind Harmer
7.193
24729505KEY G4
Adder
6.652
963791AG1-232 GEN
Solar/Wind Harmer
9.652
270071AF1-092 GEN
Solar/Wind Harmer
13.7
971985AH1-537 GEN
Solar/Wind Harmer
2.117
25196408WSDLE3
Adder
8.98
25196308WSDLE2
Adder
8.902
25196208WSDLE1
Adder
8.879
25196708WSDLE6
Adder
8.857
25196508WSDLE4
Adder
8.634
970031AG2-029 GEN
Solar/Wind Harmer
3.844
945581AF1-223 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
10.639
270543AE2-219 C
Solar/Wind Harmer
4.962
247536S-71 GEN
Solar/Wind Harmer
0.283
964611AG1-324 GEN
Solar/Wind Harmer
2.759
971609AH1-304 GEN
Solar/Wind Harmer
1.153
971771AH1-392 GEN
Solar/Wind Harmer
7.027
970289AG2-191 GEN
Solar/Wind Harmer
1.334
270526AF1-158 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.536
25196108MFTGT2
Adder
1.426
270356AE2-297 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
959141AF2-205 GEN
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
4.135
971549AH1-272 GEN
Solar/Wind Harmer
14.305
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.341
274776LINCOLN ;7U
Adder
8.341
274777LINCOLN ;8U
Adder
8.341
24386405FR-21G C
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.18
960591AF2-350 GEN
Solar/Wind Harmer
6.866
274827FISK ;RP
Adder
7.635
274800UNIV PARK;3U
Adder
5.736
274801UNIV PARK;4U
Adder
5.736
972228AH1-698 GEN2
Adder
3.644
972227AH1-698 GEN1
Adder
2.566
963841AG1-237 GEN
Solar/Wind Harmer
2.97
274687WILL CNTY;4U
Adder
27.42
274687WILL CNTY;4U
Adder
27.42
972163AH1-664 GEN
Solar/Wind Harmer
7.619
972165AH1-665 GEN
Solar/Wind Harmer
6.102
274675JOLIET 29;7U
Adder
30.093
274675JOLIET 29;7U
Adder
29.018
274728ELWOOD EC;5P
Adder
16.119
274731ELWOOD EC;2P
Adder
16.119
274733ELWOOD EC;3P
Adder
16.119
274735ELWOOD EC;4P
Adder
16.119
970833AG2-524 GEN
Solar/Wind Harmer
7.521
970833AG2-524 GEN
Solar/Wind Harmer
5.014
945641AF1-229 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.262
970169AG2-114 GEN
Solar/Wind Harmer
6.772
971675AH1-338 GEN
Solar/Wind Harmer
2.63
276861AD2-134 GEN
Solar/Wind Harmer
0.12
276863AD2-134 GEN
Solar/Wind Harmer
0.12
971411AH1-196 GEN
Solar/Wind Harmer
10.113
926823AC1-168 GEN
Solar/Wind Harmer
1.145
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.07
23750701CROSSCHOOL
Solar/Wind Helper
1.401
238169AE2-226 GEN1
Solar/Wind Helper
0.681
238170AE2-226 GEN2
Solar/Wind Helper
0.681
238118U2-030_1
Solar/Wind Helper
0.315
23779801AA1-109
Solar/Wind Helper
0.188
3138216PACIFIC
Solar/Wind Helper
0.043
237030AB1-096 C
Solar/Wind Helper
0.065
237025AB1-124 C
Solar/Wind Helper
0.16
226929AD2-058 GEN
Solar/Wind Helper
0.096
205917AD1-020 ES
Solar/Wind Helper
0.358
959381AF2-229 GEN
Solar/Wind Helper
0.346
20390526W1-045 C
Solar/Wind Helper
0.339
23750501ELLIOTTS
Solar/Wind Helper
0.573
3141426STAFORD
Solar/Wind Helper
0.051
205943AE1-185 GEN
Solar/Wind Helper
0.494
205956AE1-196_GEN
Solar/Wind Helper
0.494
233915AB1-141 GEN
Solar/Wind Helper
0.488
233901CHERRYDALE C
Solar/Wind Helper
0.226
233940AF2-379 C
Solar/Wind Helper
0.06
232432Z2-076 GEN
Solar/Wind Helper
0.065
315651AD1-115 GEN
Solar/Wind Helper
0.766
230434AG1-499 GEN
Solar/Wind Helper
0.223
228728W1-130C
Solar/Wind Helper
0.052
230407AD2-065 C
Solar/Wind Helper
0.039
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.075
219615MILLCREEK C
Solar/Wind Helper
0.026
20715028HAN_X4-015
Solar/Wind Helper
0.055
20720728JCB_W1-129
Solar/Wind Helper
0.055
207445AB1-138_GEN
Solar/Wind Helper
0.101
316164AC1-076 GEN
Solar/Wind Helper
1.068
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.184
971171AH1-044 GEN
Solar/Wind Harmer
8.748
270166AC1-044 GEN3
50/50
6.887
23559101PLEAS2
50/50
5.39
270122AB2-093 CT
50/50
3.675
962761AG1-125 GEN
Solar/Wind Harmer
33.201
970149AG2-104 GEN
Solar/Wind Harmer
17.929
970155AG2-107 GEN
Solar/Wind Harmer
21.201
270520AE2-214 GEN
Solar/Wind Harmer
0
253333AC1-068 GEN
Solar/Wind Harmer
0.009
270317AD1-130_GEN
Solar/Wind Harmer
0
971995AH1-542 GEN
Solar/Wind Harmer
2.804
270273AD2-016 GEN
Solar/Wind Harmer
0.78
972269AH1-719 GEN
Adder
2.495
270510AE1-227 GEN1
Solar/Wind Harmer
1.899
971073AG2-665 GEN
Solar/Wind Harmer
1.228
241813AF1-122_GEN
Solar/Wind Harmer
3.287
971201AH1-060 GEN
Solar/Wind Harmer
1.467
25326309TAIT D
Adder
1.151
253370AE2-315 SEC1
Adder
2.099
253371AE2-315 SEC2
Adder
1.985
253398AE2-221_GEN2
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.292
270489AE1-102 GEN1
Solar/Wind Harmer
0.942
965421AG1-410 GEN
Solar/Wind Harmer
21.735
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.209
965011AG1-365 GEN
Solar/Wind Harmer
7.206
960001AF2-291 GEN
Solar/Wind Harmer
0
965651AG1-433 GEN
Solar/Wind Harmer
2.09
958861AF2-177 GEN
Solar/Wind Harmer
3.083
252516AE2-318_GEN
Solar/Wind Harmer
7.967
270024AE2-089 GEN
Solar/Wind Harmer
0.001
252510AF1-249 C
Solar/Wind Harmer
0.054
25194608D.CRK4
Adder
1.672
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.528
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.168
24639705ELKHART HY
Adder
0.155
25196808ZIMRHP
Adder
76.605
970825AG2-519 GEN
Solar/Wind Harmer
2.501
270594AE1-207 GEN
Solar/Wind Harmer
7.872
270032AE2-172
Solar/Wind Harmer
4.686
945111AF1-176 GEN
Solar/Wind Harmer
12.534
957891AF2-083 GEN
Solar/Wind Harmer
11.704
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.661
276903AD2-071 C
Solar/Wind Harmer
7.818
25196008MFTGT1
Adder
1.393
970773AG2-487 GEN
Solar/Wind Harmer
1.233
970373AG2-245 GEN
Solar/Wind Harmer
14.656
270055AF2-134 C O1
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.046
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.682
274751CRETE EC ;1U
Adder
8.15
274754CRETE EC ;4U
Adder
8.15
274773LINCOLN ;4U
Adder
8.341
274774LINCOLN ;5U
Adder
8.341
274723RIVER EC ;12
Adder
17.708
274812UNIV PK N;8U
Adder
4.941
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
274802UNIV PARK;5U
Adder
5.739
24728605AND G2
Adder
3.773
945681AF1-233 GEN
Solar/Wind Harmer
12.929
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
30.093
274732ELWOOD EC;7P
Adder
16.119
274674JOLIET 9 ;6U
Adder
4.855
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
16.157
939401AE1-172 GEN
Solar/Wind Harmer
5.095
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.106
274861TOP CROP ;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.791
971997AH1-543 GEN
Solar/Wind Harmer
3.554
962781AG1-127 GEN
Solar/Wind Harmer
6.441
274872LEEDK;1U
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
20.202
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.427
316095T157 G97
Solar/Wind Helper
1.459
23583801GRNGAP
Solar/Wind Helper
5.433
238109AE1-109 GEN2
Solar/Wind Helper
0.107
238185AF2-356 C
Solar/Wind Helper
2.442
238120AE2-309 GEN
Solar/Wind Helper
0.491
23546401DTGZ2-030
Solar/Wind Helper
0.086
238126S14_GEN_1
Solar/Wind Helper
0.769
237038AE2-054 C
Solar/Wind Helper
0.264
235067AD1-061 GEN
Solar/Wind Helper
0.432
237085AD2-009_GEN
Solar/Wind Helper
1.596
237002AB1-128_GEN
Solar/Wind Helper
0.43
23777801MSM_W1-116
Solar/Wind Helper
0.111
3141196NOKESVL
Solar/Wind Helper
1.002
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.337
208835TUHI V3-051
Solar/Wind Helper
0.021
233935AB2-179 C
Solar/Wind Helper
1.233
233987AB2-037 GEN
Solar/Wind Helper
2.277
233933AB2-153 GEN
Solar/Wind Helper
0.226
232422X3-066 FULL
Solar/Wind Helper
0.111
232417X3-008 C
Solar/Wind Helper
0.226
233964AF2-378 GEN
Solar/Wind Helper
0.041
233923SMA
Solar/Wind Helper
0.731
233997TMININ_4.2
Solar/Wind Helper
0.199
232406W1-004 FULL
Solar/Wind Helper
0.493
233950AC2-186 GEN
Solar/Wind Helper
0.113
232434Z2-077 GEN
Solar/Wind Helper
0.123
230415AB2-049 C
Solar/Wind Helper
0.029
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.05
219914AD2-027 C
Solar/Wind Helper
0.111
219291REEVESSOUT C
Solar/Wind Helper
0.011
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.039
959561AF2-247 GEN
Solar/Wind Helper
0.02
20715728PEM_W1-119
Solar/Wind Helper
0.093
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.301
219612MATRIX C
Solar/Wind Helper
0.023
205941AD2-115 GEN
Solar/Wind Helper
0.481
20716928W4-060COL
Solar/Wind Helper
0.05
957471AF2-041 GEN
Solar/Wind Harmer
13.123
959081AF2-199 GEN
Solar/Wind Harmer
4.374
971067AG2-660 GEN
Solar/Wind Harmer
1.458
24318805MLG1
50/50
9.823
23559001PLEAS1
50/50
5.39
270051AF1-062 GEN
50/50
11.411
962771AG1-126 GEN
Solar/Wind Harmer
33.201
970153AG2-106 GEN
Solar/Wind Harmer
21.201
961921AG1-034 GEN
Solar/Wind Harmer
7.349
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
942051AE2-217 GEN
Solar/Wind Harmer
14.139
24721905FLATG4
Adder
22.814
270391AF1-285 GEN3
Solar/Wind Harmer
0.517
270518AE2-148 GEN
Solar/Wind Harmer
0.631
253325AC1-069 GEN
Solar/Wind Harmer
0.009
971199AH1-059 GEN
Solar/Wind Harmer
1.566
270512AE1-227 GEN2
Solar/Wind Harmer
1.899
970879AG2-548 GEN
Solar/Wind Harmer
5.401
970065AG2-057 GEN
Solar/Wind Harmer
0.734
253370AE2-315 SEC1
Adder
2.099
253371AE2-315 SEC2
Adder
1.985
970191AG2-125 GEN
Solar/Wind Harmer
1.872
253394AE2-221_GEN
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.261
270491AE1-102 GEN2
Solar/Wind Harmer
0.942
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.372
270588AE1-091_GEN
Solar/Wind Harmer
5.637
965021AG1-366 GEN
Solar/Wind Harmer
2.402
971191AH1-055 GEN
Solar/Wind Harmer
18.47
24695305TIMB G C
Solar/Wind Harmer
0.609
944531AF1-118 GEN
Solar/Wind Harmer
32.112
270043AE2-236 GEN
Solar/Wind Harmer
4.595
252519AF1-045_GEN
Solar/Wind Harmer
3.711
270367AC2-061_GEN
Solar/Wind Harmer
0
25196608WSDLE5
Adder
8.723
25194608D.CRK4
Adder
1.672
270063AE2-323 C
Solar/Wind Harmer
0
252507AC2-088 GEN
Solar/Wind Harmer
0.319
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.618
971347AH1-153 GEN
Solar/Wind Harmer
3.535
270186AC1-089 GEN
Solar/Wind Harmer
0
946031AF1-268 GEN
Solar/Wind Harmer
6.713
270004AE1-209 GEN
Solar/Wind Harmer
1.528
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
5.307
945111AF1-176 GEN
Solar/Wind Harmer
5.694
970289AG2-191 GEN
Solar/Wind Harmer
0.773
270505AE1-170 C O1
Solar/Wind Harmer
7.374
247642Z2-115 C
Solar/Wind Harmer
0.003
25196008MFTGT1
Adder
1.349
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.916
274752CRETE EC ;2U
Adder
8.15
274753CRETE EC ;3U
Adder
8.15
274772LINCOLN ;3U
Adder
8.341
274724RIVER EC ;11
Adder
17.501
958171AF2-111 GEN
Solar/Wind Harmer
17.234
274814UNIV PK N;0U
Adder
4.984
274807UNIV PK N;3U
Adder
4.973
274811UNIV PK N;7U
Adder
4.941
24386205FR-12G C
Solar/Wind Harmer
0
274803UNIV PARK;6U
Adder
5.739
274887GEN-1.85
Solar/Wind Harmer
0.178
276843GEN-1.7
Solar/Wind Harmer
0.222
276806AD2-047 C O1
Solar/Wind Harmer
3.89
274826FISK ;BP
Adder
10.773
972038AH1-567 GEN2
Adder
0.359
972167AH1-666 GEN
Solar/Wind Harmer
5.491
24728705AND G3
Adder
7.891
24728505AND G1
Adder
3.773
939351AE1-166 GEN
Solar/Wind Harmer
0
972259AH1-714 GEN
Adder
18.754
970707AG2-453 GEN
Solar/Wind Harmer
22.403
274676JOLIET 29;8U
Adder
29.018
274729ELWOOD EC;1P
Adder
16.119
274730ELWOOD EC;6P
Adder
16.119
274734ELWOOD EC;8P
Adder
16.119
274736ELWOOD EC;9P
Adder
16.119
270541AE2-072 C
Solar/Wind Harmer
0
943121AE2-341 GEN
Solar/Wind Harmer
11.428
943591AF1-030 GEN
Solar/Wind Harmer
7.6
274862TOP CROP ;2U
Solar/Wind Harmer
0.919
276868AE1-113 GEN
Solar/Wind Harmer
1.355
274879MINONK ;1U
Solar/Wind Harmer
0.283
946671AF1-331 GEN
Solar/Wind Harmer
0.719
274855GSG-6 ;RU
Solar/Wind Harmer
0.246
274850MENDOTA H;RU
Solar/Wind Harmer
0.078
970193AG2-126 GEN
Solar/Wind Harmer
10.106
970571AG2-364 GEN
Solar/Wind Harmer
13.468
964991AG1-363 GEN
Solar/Wind Helper
4.979
238108AE1-109 GEN1
Solar/Wind Helper
0.107
238110AE1-109 GEN3
Solar/Wind Helper
0.107
238175AF1-290_GEN
Solar/Wind Helper
0.152
238152AF2-075_GEN
Solar/Wind Helper
0.687
23777901MDS_W4-102
Solar/Wind Helper
0.172
238127S14_GEN_2
Solar/Wind Helper
0.769
235063AE1-101 C2
Solar/Wind Helper
1.608
237001AB1-127_GEN
Solar/Wind Helper
0.428
316415AF1-147_GEN2
Solar/Wind Helper
0.865
237048AF1-022 C
Solar/Wind Helper
0.164
23562501BACKB
Solar/Wind Helper
0.845
205916AD1-020 GEN
Solar/Wind Helper
1.664
208835TUHI V3-051
Solar/Wind Helper
0.021
205932AD2-116_GEN
Solar/Wind Helper
0.494
233918AB1-142 GEN
Solar/Wind Helper
0.488
233944AB2-135 GEN
Solar/Wind Helper
0.573
232426Y1-080 FULL
Solar/Wind Helper
0.038
233996TM1833_GEN
Solar/Wind Helper
0.199
233998TM1NIN_3.36
Solar/Wind Helper
0.199
232404W1-003 C
Solar/Wind Helper
0.493
232408W1-005 C
Solar/Wind Helper
0.493
316447AC1-158 HLD
Solar/Wind Helper
2.771
316044AC1-158 PL1
Solar/Wind Helper
1.259
228729W2-030 C
Solar/Wind Helper
0.107
219766PARADISE C
Solar/Wind Helper
0.053
219907AC1-030 C
Solar/Wind Helper
0.033
219686LUMSOLAR_N C
Solar/Wind Helper
0.039
219348LDSOLAR C
Solar/Wind Helper
0.111
203975AE1-071-GEN
Solar/Wind Helper
2.421
20716028EGP_W2-019
Solar/Wind Helper
0.018
20715828PEM_W1-120
Solar/Wind Helper
0.093
219276PARKLANDSO C
Solar/Wind Helper
0.087
963711AG1-223 GEN
Solar/Wind Helper
0.062
20714528FRN_Y2-051
Solar/Wind Helper
0.055
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.076
20720528MAN_W1-024
Solar/Wind Helper
0.027
959091AF2-200 GEN
Solar/Wind Harmer
8.748
CPLELTFEXP_CPLE->PJM
CLTF
0.539
CBM West 2LTFEXP_CBM-W2->PJM
CBM
108.215
NYPJM->LTFIMP_NY
CLTF
4.644
LGEELTFEXP_LGEE->PJM
CLTF
6.478
WECLTFEXP_WEC->PJM
CLTF
3.676
AG2-052LTFEXP_AG2-052->PJM
LTF
0.23
AH1-155LTFEXP_AH1-155->PJM
LTF
0.345
LAGNLTFEXP_LAGN->PJM
CLTF
14.214
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.353
TVALTFEXP_TVA->PJM
CLTF
6.984
CBM West 1LTFEXP_CBM-W1->PJM
CBM
137.595
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.883
MECLTFEXP_MEC->PJM
CLTF
15.273
SIGELTFEXP_SIGE->PJM
CLTF
0.485

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o AEP_P4_#2942_05KAMMER 765_PP_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.37 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5524.29
MW Contribution:
54.32
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721705FLATG2
50/50
25.504
270102X2-052 ST
50/50
2.028
270100X2-052 CT1
50/50
1.873
270101X2-052 CT2
50/50
1.873
970349AG2-230 GEN
Solar/Wind Harmer
19.746
965681AG1-436 GEN
Solar/Wind Harmer
15.822
965791AG1-447 GEN
Solar/Wind Harmer
8.095
274770LINCOLN ;1U
Adder
7.814
274771LINCOLN ;2U
Adder
7.814
274805UNIV PK N;1U
Adder
6.246
274808UNIV PK N;4U
Adder
6.205
247620Y3-023
Adder
0.572
274888KELLY CRK;1U
Solar/Wind Harmer
7.33
276776AD2-060 GEN
Solar/Wind Harmer
0.52
958011AF2-095 GEN
Solar/Wind Harmer
17.887
970941AG2-585 GEN
Solar/Wind Harmer
6.832
276897AD1-100 C
Solar/Wind Harmer
57.601
274674JOLIET 9 ;6U
Adder
19.033
961051AF2-396 GEN
Solar/Wind Harmer
19.608
961051AF2-396 GEN
Solar/Wind Harmer
9.12
276893AG1-478 C
Solar/Wind Harmer
0.541
270535AF1-215 GEN1
Solar/Wind Harmer
5.582
270536AF1-215 GEN2
Solar/Wind Harmer
5.582
274695ROCKY RD ;2P
Adder
13.622
274693ROCKY RD ;1P
Adder
13.488
274697ROCKY RD ;3P
Adder
3.701
274696ROCKY RD ;4P
Adder
13.944
958481AF2-142 GEN
Solar/Wind Harmer
18.341
274683WAUKEGAN ;8U
Adder
25.738
274683WAUKEGAN ;8U
Adder
21.696
962691AG1-118 GEN
Solar/Wind Harmer
36.571
960751AF2-366 GEN
Solar/Wind Harmer
3.493
958491AF2-143 GEN
Solar/Wind Harmer
18.23
276901AD2-066 C O1
Solar/Wind Harmer
4.26
971341AH1-150 GEN
Solar/Wind Harmer
24.114
971343AH1-151 GEN
Solar/Wind Harmer
24.114
276872AE1-163_GEN1
Solar/Wind Harmer
8.092
276876AE1-163_GEN2
Solar/Wind Harmer
8.092
944541AF1-119 GEN
Solar/Wind Harmer
5.043
960971AF2-388 GEN
Solar/Wind Harmer
13.167
972235AH1-702 GEN1
Adder
3.029
972236AH1-702 GEN2
Adder
2.634
274764LEE CO EC;5U
Adder
11.122
274765LEE CO EC;6U
Adder
11.122
274762LEE CO EC;3U
Adder
11.096
274763LEE CO EC;4U
Adder
10.991
247621Y3-024
Adder
0.255
24728805RICHG1
Adder
3.445
24728905RICHG2
Adder
3.445
24723005RIVRG1
Adder
16.246
24723105RIVRG2
Adder
16.246
24721605FLATG1
50/50
1.717
270071AF1-092 GEN
Solar/Wind Harmer
19.285
960681AF2-359 GEN
Solar/Wind Harmer
4.783
274775LINCOLN ;6U
Adder
7.814
274776LINCOLN ;7U
Adder
7.814
274777LINCOLN ;8U
Adder
7.814
971771AH1-392 GEN
Solar/Wind Harmer
11.343
270526AF1-158 GEN
Solar/Wind Harmer
5.709
24729505KEY G4
Adder
8.088
274827FISK ;RP
Adder
9.638
972228AH1-698 GEN2
Adder
4.601
972037AH1-567 GEN1
Adder
0.227
960591AF2-350 GEN
Solar/Wind Harmer
12.422
972227AH1-698 GEN1
Adder
3.24
274800UNIV PARK;3U
Adder
7.239
274801UNIV PARK;4U
Adder
7.239
970031AG2-029 GEN
Solar/Wind Harmer
30.971
274687WILL CNTY;4U
Adder
34.585
274687WILL CNTY;4U
Adder
34.585
274675JOLIET 29;7U
Adder
37.956
274675JOLIET 29;7U
Adder
36.6
274728ELWOOD EC;5P
Adder
20.31
274731ELWOOD EC;2P
Adder
20.31
274733ELWOOD EC;3P
Adder
20.31
274735ELWOOD EC;4P
Adder
20.31
970833AG2-524 GEN
Solar/Wind Harmer
10.785
970833AG2-524 GEN
Solar/Wind Harmer
5.016
276893AG1-478 C
Solar/Wind Harmer
0.679
274744AC1-111 GEN8
Adder
6.882
24722005FLATG5
50/50
1.717
24721905FLATG4
50/50
31.369
962771AG1-126 GEN
Solar/Wind Harmer
87.974
970153AG2-106 GEN
Solar/Wind Harmer
38.361
971347AH1-153 GEN
Solar/Wind Harmer
6.582
270043AE2-236 GEN
Solar/Wind Harmer
7.12
944531AF1-118 GEN
Solar/Wind Harmer
44.172
274772LINCOLN ;3U
Adder
7.814
24441505OLIV SLR
Solar/Wind Harmer
0.168
247643Z2-116 C
Solar/Wind Harmer
0.088
274724RIVER EC ;11
Adder
22.122
276164X3-005 C
Solar/Wind Harmer
0.876
972231SS25-0005
Solar/Wind Harmer
11.835
972181SS23-001
Solar/Wind Harmer
7.397
274752CRETE EC ;2U
Adder
6.095
274753CRETE EC ;3U
Adder
6.095
970707AG2-453 GEN
Solar/Wind Harmer
34.907
274814UNIV PK N;0U
Adder
6.287
274807UNIV PK N;3U
Adder
6.273
274811UNIV PK N;7U
Adder
6.232
270063AE2-323 C
Solar/Wind Harmer
2.735
270505AE1-170 C O1
Solar/Wind Harmer
18.66
972259AH1-714 GEN
Adder
23.722
274826FISK ;BP
Adder
13.6
274803UNIV PARK;6U
Adder
7.242
274887GEN-1.85
Solar/Wind Harmer
6.618
276772AC2-154 GEN
Solar/Wind Harmer
3.467
276843GEN-1.7
Solar/Wind Harmer
0.712
276806AD2-047 C O1
Solar/Wind Harmer
13.288
972038AH1-567 GEN2
Adder
0.453
945111AF1-176 GEN
Solar/Wind Harmer
7.015
939351AE1-166 GEN
Solar/Wind Harmer
7.354
274676JOLIET 29;8U
Adder
36.6
274729ELWOOD EC;1P
Adder
20.31
274730ELWOOD EC;6P
Adder
20.31
274734ELWOOD EC;8P
Adder
20.31
274736ELWOOD EC;9P
Adder
20.31
943121AE2-341 GEN
Solar/Wind Harmer
18.489
943591AF1-030 GEN
Solar/Wind Harmer
12.326
965021AG1-366 GEN
Solar/Wind Harmer
2.854
274862TOP CROP ;2U
Solar/Wind Harmer
6.183
274682WAUKEGAN ;7U
Adder
21.966
964401AG1-302 GEN
Solar/Wind Harmer
11.078
276868AE1-113 GEN
Solar/Wind Harmer
12.267
274879MINONK ;1U
Solar/Wind Harmer
8.179
276799AD1-013 GEN
Solar/Wind Harmer
2.674
946671AF1-331 GEN
Solar/Wind Harmer
0.507
274855GSG-6 ;RU
Solar/Wind Harmer
4.466
274850MENDOTA H;RU
Solar/Wind Harmer
3.105
276602WESTBROOK C
Solar/Wind Harmer
2.571
959091AF2-200 GEN
Solar/Wind Harmer
24.114
274760LEE CO EC;1U
Adder
11.096
274767LEE CO EC;8U
Adder
10.965
24728705AND G3
Adder
8.25
24728505AND G1
Adder
3.945
24721805FLATG3
50/50
1.717
24344105CKG2
50/50
10.062
962761AG1-125 GEN
Solar/Wind Harmer
87.974
970149AG2-104 GEN
Solar/Wind Harmer
54.324
970155AG2-107 GEN
Solar/Wind Harmer
38.361
972207SS24-0001
Solar/Wind Harmer
27.781
274773LINCOLN ;4U
Adder
7.814
274774LINCOLN ;5U
Adder
7.814
270216AD2-079_GEN
Solar/Wind Harmer
0.76
274723RIVER EC ;12
Adder
22.38
24639705ELKHART HY
Adder
0.192
274751CRETE EC ;1U
Adder
6.095
274754CRETE EC ;4U
Adder
6.095
274812UNIV PK N;8U
Adder
6.232
957891AF2-083 GEN
Solar/Wind Harmer
18.652
274802UNIV PARK;5U
Adder
7.242
945111AF1-176 GEN
Solar/Wind Harmer
22.135
941551AE2-152 GEN
Solar/Wind Harmer
5.624
970373AG2-245 GEN
Solar/Wind Harmer
26.033
274676JOLIET 29;8U
Adder
37.955
274674JOLIET 9 ;6U
Adder
19.033
274732ELWOOD EC;7P
Adder
20.31
274871GR RIDGE ;2U
Solar/Wind Harmer
9.497
274847GR RIDGE ;BU
Solar/Wind Harmer
6.245
270449AD2-020 GEN
Solar/Wind Harmer
3.453
943021AE2-325 GEN
Solar/Wind Harmer
4.487
274745AC1-111 GEN9
Adder
6.882
270055AF2-134 C O1
Solar/Wind Harmer
3.721
965011AG1-365 GEN
Solar/Wind Harmer
12.272
276694AA1-018 GEN2
Solar/Wind Harmer
7.715
276691AA1-018 GEN1
Solar/Wind Harmer
0.922
274861TOP CROP ;1U
Solar/Wind Harmer
7.405
274682WAUKEGAN ;7U
Adder
21.966
274828WAUKEGAN ;BP
Adder
13.492
958381AF2-132 GEN
Solar/Wind Harmer
11.078
964861AG1-349 GEN
Solar/Wind Harmer
9.594
971917AH1-482 GEN
Solar/Wind Harmer
11.068
939401AE1-172 GEN
Solar/Wind Harmer
16.971
962781AG1-127 GEN
Solar/Wind Harmer
11.578
274872LEEDK;1U
Solar/Wind Harmer
9.982
276805AD2-038 GEN
Solar/Wind Harmer
6.232
276882AE2-255 GEN
Solar/Wind Harmer
4.089
971997AH1-543 GEN
Solar/Wind Harmer
19.082
274746AC1-111 G10
Adder
6.882
959331AF2-224 GEN
Solar/Wind Harmer
12.272
944161AF1-084 GEN
Solar/Wind Harmer
2.708
958391AF2-133 GEN
Solar/Wind Harmer
11.034
970073AG2-061 GEN
Solar/Wind Harmer
2.826
959141AF2-205 GEN
Solar/Wind Harmer
7.334
971675AH1-338 GEN
Solar/Wind Harmer
21.777
971411AH1-196 GEN
Solar/Wind Harmer
18.145
276861AD2-134 GEN
Solar/Wind Harmer
2.16
276863AD2-134 GEN
Solar/Wind Harmer
2.16
274863CRW1-WTG
Solar/Wind Harmer
6.746
274864CRW2-WTG
Solar/Wind Harmer
6.746
971171AH1-044 GEN
Solar/Wind Harmer
24.114
276889AE2-281 GEN
Solar/Wind Harmer
2.312
958711AF2-162 GEN
Solar/Wind Harmer
1.219
274823ROCKFORD ;21
Adder
23.447
972267AH1-718 GEN
Adder
4.941
24441205WTRV SLR C
Solar/Wind Harmer
0.163
940581AE2-045 GEN
Solar/Wind Harmer
12.324
971605AH1-302 GEN
Solar/Wind Harmer
10.538
957471AF2-041 GEN
Solar/Wind Harmer
36.171
959081AF2-199 GEN
Solar/Wind Harmer
12.057
971067AG2-660 GEN
Solar/Wind Harmer
2.804
965651AG1-433 GEN
Solar/Wind Harmer
6.583
274822ROCKFORD ;11
Adder
23.618
274761LEE CO EC;2U
Adder
11.096
274766LEE CO EC;7U
Adder
10.965
24728605AND G2
Adder
3.945
970091AG2-072 GEN
Adder
77.847
972203AH1-686 GEN
Adder
2.041
24723205RIVRG3
Adder
16.246
970819AG2-516 GEN
Solar/Wind Harmer
4.983
CPLELTFEXP_CPLE->PJM
CLTF
3.171
CBM West 2LTFEXP_CBM-W2->PJM
CBM
122.514
NYPJM->LTFIMP_NY
CLTF
3.95
LGEELTFEXP_LGEE->PJM
CLTF
5.945
WECLTFEXP_WEC->PJM
CLTF
4.589
AG2-052LTFEXP_AG2-052->PJM
LTF
0.283
AH1-155LTFEXP_AH1-155->PJM
LTF
0.425
LAGNLTFEXP_LAGN->PJM
CLTF
16.557
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.009
TVALTFEXP_TVA->PJM
CLTF
7.882
CBM West 1LTFEXP_CBM-W1->PJM
CBM
147.549
CBM South 1LTFEXP_CBM-S1->PJM
CBM
30.124
MECLTFEXP_MEC->PJM
CLTF
18.481
SIGELTFEXP_SIGE->PJM
CLTF
0.494

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o AP_P2-3_MP-500-020_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-020_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:130.4 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5401.24
MW Contribution:
54.51
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721705FLATG2
50/50
25.668
270102X2-052 ST
50/50
2.042
270100X2-052 CT1
50/50
1.887
270101X2-052 CT2
50/50
1.887
970349AG2-230 GEN
Solar/Wind Harmer
19.884
965681AG1-436 GEN
Solar/Wind Harmer
15.937
965791AG1-447 GEN
Solar/Wind Harmer
8.154
274770LINCOLN ;1U
Adder
7.871
274771LINCOLN ;2U
Adder
7.871
274805UNIV PK N;1U
Adder
6.292
274808UNIV PK N;4U
Adder
6.251
247620Y3-023
Adder
0.576
274888KELLY CRK;1U
Solar/Wind Harmer
7.384
276776AD2-060 GEN
Solar/Wind Harmer
0.524
958011AF2-095 GEN
Solar/Wind Harmer
18.019
970941AG2-585 GEN
Solar/Wind Harmer
6.882
276897AD1-100 C
Solar/Wind Harmer
58.027
274674JOLIET 9 ;6U
Adder
19.174
961051AF2-396 GEN
Solar/Wind Harmer
19.754
961051AF2-396 GEN
Solar/Wind Harmer
9.188
276893AG1-478 C
Solar/Wind Harmer
0.545
24721605FLATG1
50/50
1.728
270071AF1-092 GEN
Solar/Wind Harmer
19.423
960681AF2-359 GEN
Solar/Wind Harmer
4.817
274775LINCOLN ;6U
Adder
7.871
274776LINCOLN ;7U
Adder
7.871
274777LINCOLN ;8U
Adder
7.871
971771AH1-392 GEN
Solar/Wind Harmer
11.426
270526AF1-158 GEN
Solar/Wind Harmer
5.751
24729505KEY G4
Adder
8.148
274827FISK ;RP
Adder
9.709
972037AH1-567 GEN1
Adder
0.229
960591AF2-350 GEN
Solar/Wind Harmer
12.513
972228AH1-698 GEN2
Adder
4.635
972227AH1-698 GEN1
Adder
3.264
274800UNIV PARK;3U
Adder
7.293
274801UNIV PARK;4U
Adder
7.293
970031AG2-029 GEN
Solar/Wind Harmer
31.201
274687WILL CNTY;4U
Adder
34.841
274687WILL CNTY;4U
Adder
34.841
274675JOLIET 29;7U
Adder
38.237
274675JOLIET 29;7U
Adder
36.871
274728ELWOOD EC;5P
Adder
20.461
274731ELWOOD EC;2P
Adder
20.461
274733ELWOOD EC;3P
Adder
20.461
274735ELWOOD EC;4P
Adder
20.461
970833AG2-524 GEN
Solar/Wind Harmer
10.865
970833AG2-524 GEN
Solar/Wind Harmer
5.054
276893AG1-478 C
Solar/Wind Harmer
0.684
274744AC1-111 GEN8
Adder
6.933
274746AC1-111 G10
Adder
6.933
959331AF2-224 GEN
Solar/Wind Harmer
12.364
944161AF1-084 GEN
Solar/Wind Harmer
2.728
958391AF2-133 GEN
Solar/Wind Harmer
11.118
970073AG2-061 GEN
Solar/Wind Harmer
2.848
959141AF2-205 GEN
Solar/Wind Harmer
7.39
971675AH1-338 GEN
Solar/Wind Harmer
21.942
971411AH1-196 GEN
Solar/Wind Harmer
18.283
24722005FLATG5
50/50
1.728
24721905FLATG4
50/50
31.57
962771AG1-126 GEN
Solar/Wind Harmer
88.275
970153AG2-106 GEN
Solar/Wind Harmer
38.492
971347AH1-153 GEN
Solar/Wind Harmer
6.628
270043AE2-236 GEN
Solar/Wind Harmer
7.171
944531AF1-118 GEN
Solar/Wind Harmer
44.495
274772LINCOLN ;3U
Adder
7.871
24441505OLIV SLR
Solar/Wind Harmer
0.17
247643Z2-116 C
Solar/Wind Harmer
0.088
274724RIVER EC ;11
Adder
22.284
276164X3-005 C
Solar/Wind Harmer
0.882
972231SS25-0005
Solar/Wind Harmer
11.922
972181SS23-001
Solar/Wind Harmer
7.451
274752CRETE EC ;2U
Adder
6.14
274753CRETE EC ;3U
Adder
6.14
970707AG2-453 GEN
Solar/Wind Harmer
35.163
274814UNIV PK N;0U
Adder
6.333
274807UNIV PK N;3U
Adder
6.32
274811UNIV PK N;7U
Adder
6.278
270063AE2-323 C
Solar/Wind Harmer
2.756
270505AE1-170 C O1
Solar/Wind Harmer
18.797
972259AH1-714 GEN
Adder
23.897
274826FISK ;BP
Adder
13.7
274803UNIV PARK;6U
Adder
7.295
274887GEN-1.85
Solar/Wind Harmer
6.667
276772AC2-154 GEN
Solar/Wind Harmer
3.492
276843GEN-1.7
Solar/Wind Harmer
0.717
276806AD2-047 C O1
Solar/Wind Harmer
13.386
972038AH1-567 GEN2
Adder
0.456
945111AF1-176 GEN
Solar/Wind Harmer
7.067
939351AE1-166 GEN
Solar/Wind Harmer
7.408
274676JOLIET 29;8U
Adder
36.871
274729ELWOOD EC;1P
Adder
20.461
274730ELWOOD EC;6P
Adder
20.461
274734ELWOOD EC;8P
Adder
20.461
274736ELWOOD EC;9P
Adder
20.461
943121AE2-341 GEN
Solar/Wind Harmer
18.626
943591AF1-030 GEN
Solar/Wind Harmer
12.418
965021AG1-366 GEN
Solar/Wind Harmer
2.875
274862TOP CROP ;2U
Solar/Wind Harmer
6.229
274682WAUKEGAN ;7U
Adder
22.131
964401AG1-302 GEN
Solar/Wind Harmer
11.162
276868AE1-113 GEN
Solar/Wind Harmer
12.36
274879MINONK ;1U
Solar/Wind Harmer
8.24
276799AD1-013 GEN
Solar/Wind Harmer
2.694
946671AF1-331 GEN
Solar/Wind Harmer
0.51
274855GSG-6 ;RU
Solar/Wind Harmer
4.5
274850MENDOTA H;RU
Solar/Wind Harmer
3.129
276602WESTBROOK C
Solar/Wind Harmer
2.591
959091AF2-200 GEN
Solar/Wind Harmer
24.297
274760LEE CO EC;1U
Adder
11.181
274767LEE CO EC;8U
Adder
11.049
24728705AND G3
Adder
8.324
24728505AND G1
Adder
3.98
270535AF1-215 GEN1
Solar/Wind Harmer
5.623
270536AF1-215 GEN2
Solar/Wind Harmer
5.623
274696ROCKY RD ;4P
Adder
14.048
274695ROCKY RD ;2P
Adder
13.724
274693ROCKY RD ;1P
Adder
13.589
274697ROCKY RD ;3P
Adder
3.728
958481AF2-142 GEN
Solar/Wind Harmer
18.479
276861AD2-134 GEN
Solar/Wind Harmer
2.176
276863AD2-134 GEN
Solar/Wind Harmer
2.176
274863CRW1-WTG
Solar/Wind Harmer
6.797
274864CRW2-WTG
Solar/Wind Harmer
6.797
971171AH1-044 GEN
Solar/Wind Harmer
24.297
276889AE2-281 GEN
Solar/Wind Harmer
2.33
958711AF2-162 GEN
Solar/Wind Harmer
1.228
274823ROCKFORD ;21
Adder
23.625
972267AH1-718 GEN
Adder
4.979
274683WAUKEGAN ;8U
Adder
25.931
274683WAUKEGAN ;8U
Adder
21.859
962691AG1-118 GEN
Solar/Wind Harmer
36.846
960751AF2-366 GEN
Solar/Wind Harmer
3.519
958491AF2-143 GEN
Solar/Wind Harmer
18.367
276901AD2-066 C O1
Solar/Wind Harmer
4.293
971341AH1-150 GEN
Solar/Wind Harmer
24.297
971343AH1-151 GEN
Solar/Wind Harmer
24.297
276872AE1-163_GEN1
Solar/Wind Harmer
8.153
276876AE1-163_GEN2
Solar/Wind Harmer
8.153
944541AF1-119 GEN
Solar/Wind Harmer
5.082
960971AF2-388 GEN
Solar/Wind Harmer
13.267
972235AH1-702 GEN1
Adder
3.052
972236AH1-702 GEN2
Adder
2.654
274764LEE CO EC;5U
Adder
11.207
274765LEE CO EC;6U
Adder
11.207
274762LEE CO EC;3U
Adder
11.181
274763LEE CO EC;4U
Adder
11.076
247621Y3-024
Adder
0.257
24728805RICHG1
Adder
3.48
24728905RICHG2
Adder
3.48
24723005RIVRG1
Adder
16.421
24723105RIVRG2
Adder
16.421
24721805FLATG3
50/50
1.728
24344105CKG2
50/50
10.131
962761AG1-125 GEN
Solar/Wind Harmer
88.275
970149AG2-104 GEN
Solar/Wind Harmer
54.51
970155AG2-107 GEN
Solar/Wind Harmer
38.492
972207SS24-0001
Solar/Wind Harmer
27.984
274773LINCOLN ;4U
Adder
7.871
274774LINCOLN ;5U
Adder
7.871
270216AD2-079_GEN
Solar/Wind Harmer
0.766
274723RIVER EC ;12
Adder
22.545
24639705ELKHART HY
Adder
0.193
274751CRETE EC ;1U
Adder
6.14
274754CRETE EC ;4U
Adder
6.14
274812UNIV PK N;8U
Adder
6.278
957891AF2-083 GEN
Solar/Wind Harmer
18.789
274802UNIV PARK;5U
Adder
7.295
945111AF1-176 GEN
Solar/Wind Harmer
22.299
941551AE2-152 GEN
Solar/Wind Harmer
5.665
970373AG2-245 GEN
Solar/Wind Harmer
26.226
274676JOLIET 29;8U
Adder
38.237
274674JOLIET 9 ;6U
Adder
19.174
274732ELWOOD EC;7P
Adder
20.461
274871GR RIDGE ;2U
Solar/Wind Harmer
9.567
274847GR RIDGE ;BU
Solar/Wind Harmer
6.291
270449AD2-020 GEN
Solar/Wind Harmer
3.479
943021AE2-325 GEN
Solar/Wind Harmer
4.521
274745AC1-111 GEN9
Adder
6.933
270055AF2-134 C O1
Solar/Wind Harmer
3.749
965011AG1-365 GEN
Solar/Wind Harmer
12.364
276694AA1-018 GEN2
Solar/Wind Harmer
7.773
276691AA1-018 GEN1
Solar/Wind Harmer
0.929
274861TOP CROP ;1U
Solar/Wind Harmer
7.461
274682WAUKEGAN ;7U
Adder
22.131
958381AF2-132 GEN
Solar/Wind Harmer
11.162
274828WAUKEGAN ;BP
Adder
13.593
964861AG1-349 GEN
Solar/Wind Harmer
9.666
971917AH1-482 GEN
Solar/Wind Harmer
11.152
939401AE1-172 GEN
Solar/Wind Harmer
17.099
962781AG1-127 GEN
Solar/Wind Harmer
11.665
274872LEEDK;1U
Solar/Wind Harmer
10.057
276805AD2-038 GEN
Solar/Wind Harmer
6.279
276882AE2-255 GEN
Solar/Wind Harmer
4.12
971997AH1-543 GEN
Solar/Wind Harmer
19.226
24441205WTRV SLR C
Solar/Wind Harmer
0.164
940581AE2-045 GEN
Solar/Wind Harmer
12.418
971605AH1-302 GEN
Solar/Wind Harmer
10.618
957471AF2-041 GEN
Solar/Wind Harmer
36.445
959081AF2-199 GEN
Solar/Wind Harmer
12.148
971067AG2-660 GEN
Solar/Wind Harmer
2.825
965651AG1-433 GEN
Solar/Wind Harmer
6.634
274822ROCKFORD ;11
Adder
23.797
274761LEE CO EC;2U
Adder
11.181
274766LEE CO EC;7U
Adder
11.049
24728605AND G2
Adder
3.98
970091AG2-072 GEN
Adder
78.555
972203AH1-686 GEN
Adder
2.063
24723205RIVRG3
Adder
16.421
970819AG2-516 GEN
Solar/Wind Harmer
5.021
CPLELTFEXP_CPLE->PJM
CLTF
3.258
CBM West 2LTFEXP_CBM-W2->PJM
CBM
123.727
NYPJM->LTFIMP_NY
CLTF
3.908
LGEELTFEXP_LGEE->PJM
CLTF
6.008
WECLTFEXP_WEC->PJM
CLTF
4.624
AG2-052LTFEXP_AG2-052->PJM
LTF
0.285
AH1-155LTFEXP_AH1-155->PJM
LTF
0.428
LAGNLTFEXP_LAGN->PJM
CLTF
16.737
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.259
TVALTFEXP_TVA->PJM
CLTF
7.972
CBM West 1LTFEXP_CBM-W1->PJM
CBM
148.883
CBM South 1LTFEXP_CBM-S1->PJM
CBM
30.463
MECLTFEXP_MEC->PJM
CLTF
18.634
SIGELTFEXP_SIGE->PJM
CLTF
0.499

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o AP_P2-3_MP-500-021_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-021_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:130.35 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5399.06
MW Contribution:
54.49
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
1.727
270071AF1-092 GEN
Solar/Wind Harmer
19.407
960681AF2-359 GEN
Solar/Wind Harmer
4.813
274775LINCOLN ;6U
Adder
7.864
274776LINCOLN ;7U
Adder
7.864
274777LINCOLN ;8U
Adder
7.864
971771AH1-392 GEN
Solar/Wind Harmer
11.417
270526AF1-158 GEN
Solar/Wind Harmer
5.746
24729505KEY G4
Adder
8.141
274827FISK ;RP
Adder
9.701
972037AH1-567 GEN1
Adder
0.229
960591AF2-350 GEN
Solar/Wind Harmer
12.503
972228AH1-698 GEN2
Adder
4.631
972227AH1-698 GEN1
Adder
3.261
274800UNIV PARK;3U
Adder
7.287
274801UNIV PARK;4U
Adder
7.287
970031AG2-029 GEN
Solar/Wind Harmer
31.175
274687WILL CNTY;4U
Adder
34.812
274687WILL CNTY;4U
Adder
34.812
274675JOLIET 29;7U
Adder
38.205
24722005FLATG5
50/50
1.727
24721905FLATG4
50/50
31.545
962771AG1-126 GEN
Solar/Wind Harmer
88.239
970153AG2-106 GEN
Solar/Wind Harmer
38.476
971347AH1-153 GEN
Solar/Wind Harmer
6.623
270043AE2-236 GEN
Solar/Wind Harmer
7.165
944531AF1-118 GEN
Solar/Wind Harmer
44.457
274772LINCOLN ;3U
Adder
7.864
24441505OLIV SLR
Solar/Wind Harmer
0.169
247643Z2-116 C
Solar/Wind Harmer
0.088
274724RIVER EC ;11
Adder
22.266
276164X3-005 C
Solar/Wind Harmer
0.882
972231SS25-0005
Solar/Wind Harmer
11.912
972181SS23-001
Solar/Wind Harmer
7.445
274752CRETE EC ;2U
Adder
6.135
274753CRETE EC ;3U
Adder
6.135
970707AG2-453 GEN
Solar/Wind Harmer
35.134
270063AE2-323 C
Solar/Wind Harmer
2.753
274814UNIV PK N;0U
Adder
6.328
274807UNIV PK N;3U
Adder
6.314
274811UNIV PK N;7U
Adder
6.273
270505AE1-170 C O1
Solar/Wind Harmer
18.782
972259AH1-714 GEN
Adder
23.878
274826FISK ;BP
Adder
13.689
274803UNIV PARK;6U
Adder
7.289
274887GEN-1.85
Solar/Wind Harmer
6.661
276772AC2-154 GEN
Solar/Wind Harmer
3.489
276843GEN-1.7
Solar/Wind Harmer
0.717
276806AD2-047 C O1
Solar/Wind Harmer
13.375
972038AH1-567 GEN2
Adder
0.456
945111AF1-176 GEN
Solar/Wind Harmer
7.061
939351AE1-166 GEN
Solar/Wind Harmer
7.402
274676JOLIET 29;8U
Adder
36.84
274729ELWOOD EC;1P
Adder
20.444
274730ELWOOD EC;6P
Adder
20.444
24721805FLATG3
50/50
1.727
24344105CKG2
50/50
10.123
962761AG1-125 GEN
Solar/Wind Harmer
88.239
970149AG2-104 GEN
Solar/Wind Harmer
54.487
970155AG2-107 GEN
Solar/Wind Harmer
38.476
972207SS24-0001
Solar/Wind Harmer
27.961
274773LINCOLN ;4U
Adder
7.864
274774LINCOLN ;5U
Adder
7.864
270216AD2-079_GEN
Solar/Wind Harmer
0.765
274723RIVER EC ;12
Adder
22.526
24639705ELKHART HY
Adder
0.193
274751CRETE EC ;1U
Adder
6.135
274754CRETE EC ;4U
Adder
6.135
274812UNIV PK N;8U
Adder
6.273
957891AF2-083 GEN
Solar/Wind Harmer
18.774
274802UNIV PARK;5U
Adder
7.289
945111AF1-176 GEN
Solar/Wind Harmer
22.281
941551AE2-152 GEN
Solar/Wind Harmer
5.66
970373AG2-245 GEN
Solar/Wind Harmer
26.204
274676JOLIET 29;8U
Adder
38.205
274674JOLIET 9 ;6U
Adder
19.158
274732ELWOOD EC;7P
Adder
20.444
274871GR RIDGE ;2U
Solar/Wind Harmer
9.559
274847GR RIDGE ;BU
Solar/Wind Harmer
6.286
270449AD2-020 GEN
Solar/Wind Harmer
3.476
943021AE2-325 GEN
Solar/Wind Harmer
4.517
274745AC1-111 GEN9
Adder
6.927
270055AF2-134 C O1
Solar/Wind Harmer
3.746
965011AG1-365 GEN
Solar/Wind Harmer
12.354
276694AA1-018 GEN2
Solar/Wind Harmer
7.767
276691AA1-018 GEN1
Solar/Wind Harmer
0.928
274861TOP CROP ;1U
Solar/Wind Harmer
7.454
274682WAUKEGAN ;7U
Adder
22.112
274828WAUKEGAN ;BP
Adder
13.581
958381AF2-132 GEN
Solar/Wind Harmer
11.152
964861AG1-349 GEN
Solar/Wind Harmer
9.658
971917AH1-482 GEN
Solar/Wind Harmer
11.142
939401AE1-172 GEN
Solar/Wind Harmer
17.084
962781AG1-127 GEN
Solar/Wind Harmer
11.655
274872LEEDK;1U
Solar/Wind Harmer
10.049
276805AD2-038 GEN
Solar/Wind Harmer
6.274
276882AE2-255 GEN
Solar/Wind Harmer
4.117
971997AH1-543 GEN
Solar/Wind Harmer
19.21
24441205WTRV SLR C
Solar/Wind Harmer
0.164
940581AE2-045 GEN
Solar/Wind Harmer
12.407
971605AH1-302 GEN
Solar/Wind Harmer
10.609
957471AF2-041 GEN
Solar/Wind Harmer
36.414
959081AF2-199 GEN
Solar/Wind Harmer
12.138
971067AG2-660 GEN
Solar/Wind Harmer
2.823
965651AG1-433 GEN
Solar/Wind Harmer
6.628
274822ROCKFORD ;11
Adder
23.777
274761LEE CO EC;2U
Adder
11.171
274766LEE CO EC;7U
Adder
11.04
24728605AND G2
Adder
3.976
970091AG2-072 GEN
Adder
78.473
972203AH1-686 GEN
Adder
2.06
24723205RIVRG3
Adder
16.4
970819AG2-516 GEN
Solar/Wind Harmer
5.017
24721705FLATG2
50/50
25.648
270102X2-052 ST
50/50
2.041
270100X2-052 CT1
50/50
1.885
270101X2-052 CT2
50/50
1.885
970349AG2-230 GEN
Solar/Wind Harmer
19.868
965681AG1-436 GEN
Solar/Wind Harmer
15.923
965791AG1-447 GEN
Solar/Wind Harmer
8.147
274770LINCOLN ;1U
Adder
7.864
274771LINCOLN ;2U
Adder
7.864
274805UNIV PK N;1U
Adder
6.287
274808UNIV PK N;4U
Adder
6.246
247620Y3-023
Adder
0.576
274888KELLY CRK;1U
Solar/Wind Harmer
7.378
276776AD2-060 GEN
Solar/Wind Harmer
0.523
958011AF2-095 GEN
Solar/Wind Harmer
18.005
970941AG2-585 GEN
Solar/Wind Harmer
6.877
276897AD1-100 C
Solar/Wind Harmer
57.979
274674JOLIET 9 ;6U
Adder
19.158
961051AF2-396 GEN
Solar/Wind Harmer
19.737
961051AF2-396 GEN
Solar/Wind Harmer
9.18
276893AG1-478 C
Solar/Wind Harmer
0.545
270535AF1-215 GEN1
Solar/Wind Harmer
5.619
270536AF1-215 GEN2
Solar/Wind Harmer
5.619
274696ROCKY RD ;4P
Adder
14.036
274695ROCKY RD ;2P
Adder
13.713
274693ROCKY RD ;1P
Adder
13.578
274697ROCKY RD ;3P
Adder
3.725
958481AF2-142 GEN
Solar/Wind Harmer
18.463
274683WAUKEGAN ;8U
Adder
25.91
274683WAUKEGAN ;8U
Adder
21.841
962691AG1-118 GEN
Solar/Wind Harmer
36.815
960751AF2-366 GEN
Solar/Wind Harmer
3.516
958491AF2-143 GEN
Solar/Wind Harmer
18.352
276901AD2-066 C O1
Solar/Wind Harmer
4.289
971341AH1-150 GEN
Solar/Wind Harmer
24.276
971343AH1-151 GEN
Solar/Wind Harmer
24.276
276872AE1-163_GEN1
Solar/Wind Harmer
8.146
276876AE1-163_GEN2
Solar/Wind Harmer
8.146
944541AF1-119 GEN
Solar/Wind Harmer
5.078
960971AF2-388 GEN
Solar/Wind Harmer
13.256
972235AH1-702 GEN1
Adder
3.05
972236AH1-702 GEN2
Adder
2.652
274764LEE CO EC;5U
Adder
11.198
274765LEE CO EC;6U
Adder
11.198
274762LEE CO EC;3U
Adder
11.171
274763LEE CO EC;4U
Adder
11.066
247621Y3-024
Adder
0.257
24728805RICHG1
Adder
3.476
24728905RICHG2
Adder
3.476
24723005RIVRG1
Adder
16.4
24723105RIVRG2
Adder
16.4
274675JOLIET 29;7U
Adder
36.841
274728ELWOOD EC;5P
Adder
20.444
274731ELWOOD EC;2P
Adder
20.444
274733ELWOOD EC;3P
Adder
20.444
274735ELWOOD EC;4P
Adder
20.444
970833AG2-524 GEN
Solar/Wind Harmer
10.856
970833AG2-524 GEN
Solar/Wind Harmer
5.05
276893AG1-478 C
Solar/Wind Harmer
0.684
274744AC1-111 GEN8
Adder
6.927
274746AC1-111 G10
Adder
6.927
959331AF2-224 GEN
Solar/Wind Harmer
12.354
944161AF1-084 GEN
Solar/Wind Harmer
2.725
958391AF2-133 GEN
Solar/Wind Harmer
11.108
970073AG2-061 GEN
Solar/Wind Harmer
2.845
959141AF2-205 GEN
Solar/Wind Harmer
7.383
971675AH1-338 GEN
Solar/Wind Harmer
21.924
971411AH1-196 GEN
Solar/Wind Harmer
18.267
276861AD2-134 GEN
Solar/Wind Harmer
2.174
276863AD2-134 GEN
Solar/Wind Harmer
2.174
274863CRW1-WTG
Solar/Wind Harmer
6.791
274864CRW2-WTG
Solar/Wind Harmer
6.791
971171AH1-044 GEN
Solar/Wind Harmer
24.276
276889AE2-281 GEN
Solar/Wind Harmer
2.328
958711AF2-162 GEN
Solar/Wind Harmer
1.227
274823ROCKFORD ;21
Adder
23.605
972267AH1-718 GEN
Adder
4.975
274734ELWOOD EC;8P
Adder
20.444
274736ELWOOD EC;9P
Adder
20.444
943121AE2-341 GEN
Solar/Wind Harmer
18.611
943591AF1-030 GEN
Solar/Wind Harmer
12.407
965021AG1-366 GEN
Solar/Wind Harmer
2.873
274862TOP CROP ;2U
Solar/Wind Harmer
6.224
274682WAUKEGAN ;7U
Adder
22.112
964401AG1-302 GEN
Solar/Wind Harmer
11.152
276868AE1-113 GEN
Solar/Wind Harmer
12.35
274879MINONK ;1U
Solar/Wind Harmer
8.233
276799AD1-013 GEN
Solar/Wind Harmer
2.692
946671AF1-331 GEN
Solar/Wind Harmer
0.51
274855GSG-6 ;RU
Solar/Wind Harmer
4.496
274850MENDOTA H;RU
Solar/Wind Harmer
3.126
276602WESTBROOK C
Solar/Wind Harmer
2.588
959091AF2-200 GEN
Solar/Wind Harmer
24.276
274760LEE CO EC;1U
Adder
11.171
274767LEE CO EC;8U
Adder
11.04
24728705AND G3
Adder
8.316
24728505AND G1
Adder
3.976
CPLELTFEXP_CPLE->PJM
CLTF
3.256
CBM West 2LTFEXP_CBM-W2->PJM
CBM
123.605
NYPJM->LTFIMP_NY
CLTF
3.903
LGEELTFEXP_LGEE->PJM
CLTF
6.001
WECLTFEXP_WEC->PJM
CLTF
4.62
AG2-052LTFEXP_AG2-052->PJM
LTF
0.285
AH1-155LTFEXP_AH1-155->PJM
LTF
0.428
LAGNLTFEXP_LAGN->PJM
CLTF
16.72
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.247
TVALTFEXP_TVA->PJM
CLTF
7.964
CBM West 1LTFEXP_CBM-W1->PJM
CBM
148.737
CBM South 1LTFEXP_CBM-S1->PJM
CBM
30.431
MECLTFEXP_MEC->PJM
CLTF
18.617
SIGELTFEXP_SIGE->PJM
CLTF
0.499

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o AEP_P4_#37_05MOUNTN 765_B1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:130.33 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5398.09
MW Contribution:
54.48
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721805FLATG3
50/50
1.726
24344105CKG2
50/50
10.12
962761AG1-125 GEN
Solar/Wind Harmer
88.223
970149AG2-104 GEN
Solar/Wind Harmer
54.478
970155AG2-107 GEN
Solar/Wind Harmer
38.469
972207SS24-0001
Solar/Wind Harmer
27.951
274773LINCOLN ;4U
Adder
7.861
274774LINCOLN ;5U
Adder
7.861
270216AD2-079_GEN
Solar/Wind Harmer
0.765
274723RIVER EC ;12
Adder
22.518
24639705ELKHART HY
Adder
0.193
274751CRETE EC ;1U
Adder
6.133
274754CRETE EC ;4U
Adder
6.133
274812UNIV PK N;8U
Adder
6.271
957891AF2-083 GEN
Solar/Wind Harmer
18.767
274802UNIV PARK;5U
Adder
7.287
945111AF1-176 GEN
Solar/Wind Harmer
22.272
941551AE2-152 GEN
Solar/Wind Harmer
5.658
970373AG2-245 GEN
Solar/Wind Harmer
26.195
274676JOLIET 29;8U
Adder
38.191
274674JOLIET 9 ;6U
Adder
19.151
274732ELWOOD EC;7P
Adder
20.437
274871GR RIDGE ;2U
Solar/Wind Harmer
9.556
274847GR RIDGE ;BU
Solar/Wind Harmer
6.283
270449AD2-020 GEN
Solar/Wind Harmer
3.475
943021AE2-325 GEN
Solar/Wind Harmer
4.515
274745AC1-111 GEN9
Adder
6.924
270055AF2-134 C O1
Solar/Wind Harmer
3.744
965011AG1-365 GEN
Solar/Wind Harmer
12.349
276694AA1-018 GEN2
Solar/Wind Harmer
7.764
276691AA1-018 GEN1
Solar/Wind Harmer
0.928
274861TOP CROP ;1U
Solar/Wind Harmer
7.452
274682WAUKEGAN ;7U
Adder
22.104
958381AF2-132 GEN
Solar/Wind Harmer
11.148
274828WAUKEGAN ;BP
Adder
13.576
964861AG1-349 GEN
Solar/Wind Harmer
9.654
971917AH1-482 GEN
Solar/Wind Harmer
11.138
939401AE1-172 GEN
Solar/Wind Harmer
17.078
962781AG1-127 GEN
Solar/Wind Harmer
11.651
274872LEEDK;1U
Solar/Wind Harmer
10.045
276805AD2-038 GEN
Solar/Wind Harmer
6.272
276882AE2-255 GEN
Solar/Wind Harmer
4.115
971997AH1-543 GEN
Solar/Wind Harmer
19.203
24441205WTRV SLR C
Solar/Wind Harmer
0.164
940581AE2-045 GEN
Solar/Wind Harmer
12.403
971605AH1-302 GEN
Solar/Wind Harmer
10.605
957471AF2-041 GEN
Solar/Wind Harmer
36.401
959081AF2-199 GEN
Solar/Wind Harmer
12.134
971067AG2-660 GEN
Solar/Wind Harmer
2.822
965651AG1-433 GEN
Solar/Wind Harmer
6.625
274822ROCKFORD ;11
Adder
23.769
274761LEE CO EC;2U
Adder
11.167
274766LEE CO EC;7U
Adder
11.036
24728605AND G2
Adder
3.974
970091AG2-072 GEN
Adder
78.436
972203AH1-686 GEN
Adder
2.059
24723205RIVRG3
Adder
16.391
970819AG2-516 GEN
Solar/Wind Harmer
5.015
24722005FLATG5
50/50
1.726
24721905FLATG4
50/50
31.534
962771AG1-126 GEN
Solar/Wind Harmer
88.223
970153AG2-106 GEN
Solar/Wind Harmer
38.469
971347AH1-153 GEN
Solar/Wind Harmer
6.62
270043AE2-236 GEN
Solar/Wind Harmer
7.162
944531AF1-118 GEN
Solar/Wind Harmer
44.44
274772LINCOLN ;3U
Adder
7.861
247643Z2-116 C
Solar/Wind Harmer
0.088
24441505OLIV SLR
Solar/Wind Harmer
0.169
274724RIVER EC ;11
Adder
22.258
276164X3-005 C
Solar/Wind Harmer
0.881
972231SS25-0005
Solar/Wind Harmer
11.907
972181SS23-001
Solar/Wind Harmer
7.442
274752CRETE EC ;2U
Adder
6.133
274753CRETE EC ;3U
Adder
6.133
970707AG2-453 GEN
Solar/Wind Harmer
35.122
274814UNIV PK N;0U
Adder
6.326
24721605FLATG1
50/50
1.726
270071AF1-092 GEN
Solar/Wind Harmer
19.4
960681AF2-359 GEN
Solar/Wind Harmer
4.812
274775LINCOLN ;6U
Adder
7.861
274776LINCOLN ;7U
Adder
7.861
274777LINCOLN ;8U
Adder
7.861
971771AH1-392 GEN
Solar/Wind Harmer
11.412
270526AF1-158 GEN
Solar/Wind Harmer
5.744
24729505KEY G4
Adder
8.138
274827FISK ;RP
Adder
9.698
972037AH1-567 GEN1
Adder
0.229
960591AF2-350 GEN
Solar/Wind Harmer
12.499
972228AH1-698 GEN2
Adder
4.629
972227AH1-698 GEN1
Adder
3.26
274800UNIV PARK;3U
Adder
7.284
274801UNIV PARK;4U
Adder
7.284
970031AG2-029 GEN
Solar/Wind Harmer
31.163
274687WILL CNTY;4U
Adder
34.799
274687WILL CNTY;4U
Adder
34.799
274675JOLIET 29;7U
Adder
38.191
274675JOLIET 29;7U
Adder
36.827
274728ELWOOD EC;5P
Adder
20.437
274731ELWOOD EC;2P
Adder
20.436
274733ELWOOD EC;3P
Adder
20.436
274735ELWOOD EC;4P
Adder
20.436
970833AG2-524 GEN
Solar/Wind Harmer
10.852
970833AG2-524 GEN
Solar/Wind Harmer
5.048
276893AG1-478 C
Solar/Wind Harmer
0.684
274744AC1-111 GEN8
Adder
6.924
274746AC1-111 G10
Adder
6.924
959331AF2-224 GEN
Solar/Wind Harmer
12.349
944161AF1-084 GEN
Solar/Wind Harmer
2.724
958391AF2-133 GEN
Solar/Wind Harmer
11.104
970073AG2-061 GEN
Solar/Wind Harmer
2.844
959141AF2-205 GEN
Solar/Wind Harmer
7.381
971675AH1-338 GEN
Solar/Wind Harmer
21.916
971411AH1-196 GEN
Solar/Wind Harmer
18.261
276861AD2-134 GEN
Solar/Wind Harmer
2.174
276863AD2-134 GEN
Solar/Wind Harmer
2.174
274863CRW1-WTG
Solar/Wind Harmer
6.788
274864CRW2-WTG
Solar/Wind Harmer
6.788
971171AH1-044 GEN
Solar/Wind Harmer
24.267
276889AE2-281 GEN
Solar/Wind Harmer
2.327
958711AF2-162 GEN
Solar/Wind Harmer
1.226
274823ROCKFORD ;21
Adder
23.596
972267AH1-718 GEN
Adder
4.973
24721705FLATG2
50/50
25.639
270102X2-052 ST
50/50
2.04
270100X2-052 CT1
50/50
1.885
270101X2-052 CT2
50/50
1.885
970349AG2-230 GEN
Solar/Wind Harmer
19.861
965681AG1-436 GEN
Solar/Wind Harmer
15.918
965791AG1-447 GEN
Solar/Wind Harmer
8.144
274770LINCOLN ;1U
Adder
7.861
274771LINCOLN ;2U
Adder
7.861
274805UNIV PK N;1U
Adder
6.285
274808UNIV PK N;4U
Adder
6.243
247620Y3-023
Adder
0.576
274888KELLY CRK;1U
Solar/Wind Harmer
7.375
276776AD2-060 GEN
Solar/Wind Harmer
0.523
958011AF2-095 GEN
Solar/Wind Harmer
17.998
970941AG2-585 GEN
Solar/Wind Harmer
6.874
276897AD1-100 C
Solar/Wind Harmer
57.958
274674JOLIET 9 ;6U
Adder
19.151
961051AF2-396 GEN
Solar/Wind Harmer
19.73
961051AF2-396 GEN
Solar/Wind Harmer
9.177
276893AG1-478 C
Solar/Wind Harmer
0.545
270535AF1-215 GEN1
Solar/Wind Harmer
5.616
270536AF1-215 GEN2
Solar/Wind Harmer
5.616
274696ROCKY RD ;4P
Adder
14.031
274695ROCKY RD ;2P
Adder
13.708
274693ROCKY RD ;1P
Adder
13.573
274697ROCKY RD ;3P
Adder
3.724
958481AF2-142 GEN
Solar/Wind Harmer
18.457
274683WAUKEGAN ;8U
Adder
25.9
274683WAUKEGAN ;8U
Adder
21.833
962691AG1-118 GEN
Solar/Wind Harmer
36.802
960751AF2-366 GEN
Solar/Wind Harmer
3.515
958491AF2-143 GEN
Solar/Wind Harmer
18.345
276901AD2-066 C O1
Solar/Wind Harmer
4.287
971341AH1-150 GEN
Solar/Wind Harmer
24.267
971343AH1-151 GEN
Solar/Wind Harmer
24.267
276872AE1-163_GEN1
Solar/Wind Harmer
8.143
276876AE1-163_GEN2
Solar/Wind Harmer
8.143
944541AF1-119 GEN
Solar/Wind Harmer
5.076
960971AF2-388 GEN
Solar/Wind Harmer
13.25
972235AH1-702 GEN1
Adder
3.049
972236AH1-702 GEN2
Adder
2.651
274764LEE CO EC;5U
Adder
11.194
274765LEE CO EC;6U
Adder
11.194
274762LEE CO EC;3U
Adder
11.167
274763LEE CO EC;4U
Adder
11.062
247621Y3-024
Adder
0.257
24728805RICHG1
Adder
3.474
24728905RICHG2
Adder
3.474
24723005RIVRG1
Adder
16.391
24723105RIVRG2
Adder
16.391
274807UNIV PK N;3U
Adder
6.312
274811UNIV PK N;7U
Adder
6.271
270063AE2-323 C
Solar/Wind Harmer
2.752
270505AE1-170 C O1
Solar/Wind Harmer
18.775
972259AH1-714 GEN
Adder
23.869
274826FISK ;BP
Adder
13.684
274803UNIV PARK;6U
Adder
7.287
274887GEN-1.85
Solar/Wind Harmer
6.659
276772AC2-154 GEN
Solar/Wind Harmer
3.488
276843GEN-1.7
Solar/Wind Harmer
0.716
276806AD2-047 C O1
Solar/Wind Harmer
13.371
972038AH1-567 GEN2
Adder
0.456
945111AF1-176 GEN
Solar/Wind Harmer
7.059
939351AE1-166 GEN
Solar/Wind Harmer
7.399
274676JOLIET 29;8U
Adder
36.827
274729ELWOOD EC;1P
Adder
20.436
274730ELWOOD EC;6P
Adder
20.437
274734ELWOOD EC;8P
Adder
20.437
274736ELWOOD EC;9P
Adder
20.437
943121AE2-341 GEN
Solar/Wind Harmer
18.604
943591AF1-030 GEN
Solar/Wind Harmer
12.403
965021AG1-366 GEN
Solar/Wind Harmer
2.872
274862TOP CROP ;2U
Solar/Wind Harmer
6.222
274682WAUKEGAN ;7U
Adder
22.104
964401AG1-302 GEN
Solar/Wind Harmer
11.148
276868AE1-113 GEN
Solar/Wind Harmer
12.345
274879MINONK ;1U
Solar/Wind Harmer
8.23
276799AD1-013 GEN
Solar/Wind Harmer
2.691
946671AF1-331 GEN
Solar/Wind Harmer
0.51
274855GSG-6 ;RU
Solar/Wind Harmer
4.495
274850MENDOTA H;RU
Solar/Wind Harmer
3.125
276602WESTBROOK C
Solar/Wind Harmer
2.587
959091AF2-200 GEN
Solar/Wind Harmer
24.267
274760LEE CO EC;1U
Adder
11.167
274767LEE CO EC;8U
Adder
11.036
24728705AND G3
Adder
8.312
24728505AND G1
Adder
3.974
CPLELTFEXP_CPLE->PJM
CLTF
3.255
CBM West 2LTFEXP_CBM-W2->PJM
CBM
123.551
NYPJM->LTFIMP_NY
CLTF
3.901
LGEELTFEXP_LGEE->PJM
CLTF
5.998
WECLTFEXP_WEC->PJM
CLTF
4.618
AG2-052LTFEXP_AG2-052->PJM
LTF
0.285
AH1-155LTFEXP_AH1-155->PJM
LTF
0.428
LAGNLTFEXP_LAGN->PJM
CLTF
16.713
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.242
TVALTFEXP_TVA->PJM
CLTF
7.96
CBM West 1LTFEXP_CBM-W1->PJM
CBM
148.673
CBM South 1LTFEXP_CBM-S1->PJM
CBM
30.416
MECLTFEXP_MEC->PJM
CLTF
18.61
SIGELTFEXP_SIGE->PJM
CLTF
0.498

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o AP_P1-3_MP-765-501T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:127.9 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5297.56
MW Contribution:
40.18
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
1.726
270071AF1-092 GEN
Solar/Wind Harmer
17.295
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
274775LINCOLN ;6U
Adder
10.701
274776LINCOLN ;7U
Adder
10.701
274777LINCOLN ;8U
Adder
10.701
971771AH1-392 GEN
Solar/Wind Harmer
8.847
270526AF1-158 GEN
Solar/Wind Harmer
0.001
24729505KEY G4
Adder
8.138
274827FISK ;RP
Adder
9.698
972037AH1-567 GEN1
Adder
0.229
960591AF2-350 GEN
Solar/Wind Harmer
8.72
972228AH1-698 GEN2
Adder
4.629
972227AH1-698 GEN1
Adder
3.26
274800UNIV PARK;3U
Adder
7.284
274801UNIV PARK;4U
Adder
7.284
970031AG2-029 GEN
Solar/Wind Harmer
4.711
274687WILL CNTY;4U
Adder
34.799
274687WILL CNTY;4U
Adder
34.799
274675JOLIET 29;7U
Adder
38.191
274675JOLIET 29;7U
Adder
36.827
274728ELWOOD EC;5P
Adder
20.437
274731ELWOOD EC;2P
Adder
20.436
274733ELWOOD EC;3P
Adder
20.436
274735ELWOOD EC;4P
Adder
20.436
970833AG2-524 GEN
Solar/Wind Harmer
9.54
970833AG2-524 GEN
Solar/Wind Harmer
6.36
274744AC1-111 GEN8
Adder
6.924
274746AC1-111 G10
Adder
6.924
959331AF2-224 GEN
Solar/Wind Harmer
6.031
958391AF2-133 GEN
Solar/Wind Harmer
0.001
970073AG2-061 GEN
Solar/Wind Harmer
2.844
959141AF2-205 GEN
Solar/Wind Harmer
0
971675AH1-338 GEN
Solar/Wind Harmer
3.313
971411AH1-196 GEN
Solar/Wind Harmer
12.74
276861AD2-134 GEN
Solar/Wind Harmer
0.151
276863AD2-134 GEN
Solar/Wind Harmer
0.151
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
5.051
971171AH1-044 GEN
Solar/Wind Harmer
16.931
274823ROCKFORD ;21
Adder
23.596
970169AG2-114 GEN
Solar/Wind Harmer
8.419
274856ECOGROVE ;U1
Solar/Wind Harmer
0.197
926823AC1-168 GEN
Solar/Wind Harmer
1.43
971681AH1-341 GEN
Solar/Wind Harmer
13.512
972267AH1-718 GEN
Adder
4.973
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
276741O09 GEN1
Solar/Wind Harmer
0.294
274877BISHOP HL;1U
Solar/Wind Harmer
0.277
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
8.684
946321AF1-296 GEN
Solar/Wind Harmer
4.596
274854TWINGROVE;U2
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
11.059
24386405FR-21G C
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
3.499
965041AG1-368 GEN
Solar/Wind Harmer
8.029
970289AG2-191 GEN
Solar/Wind Harmer
1.518
276668AB2-070 GEN1
Solar/Wind Harmer
0.314
276848AB2-070 GEN3
Solar/Wind Harmer
0.312
276849AB2-070 GEN2
Solar/Wind Harmer
0.314
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
1.297
971549AH1-272 GEN
Solar/Wind Harmer
16.346
247521TR3_G114
Solar/Wind Harmer
0.284
965051AG1-369 GEN
Solar/Wind Harmer
3.91
944221AF1-090 GEN
Solar/Wind Harmer
4.487
964611AG1-324 GEN
Solar/Wind Harmer
2.967
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.934
247536S-71 GEN
Solar/Wind Harmer
0.293
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
4.979
270007AE1-245 C
Solar/Wind Harmer
0
270356AE2-297 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Harmer
0.462
971029AG2-637 GEN
Solar/Wind Harmer
10.316
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.938
24722005FLATG5
50/50
1.726
24721905FLATG4
50/50
31.534
962771AG1-126 GEN
Solar/Wind Harmer
74.4
970153AG2-106 GEN
Solar/Wind Harmer
47.51
971347AH1-153 GEN
Solar/Wind Harmer
4.619
270043AE2-236 GEN
Solar/Wind Harmer
5.83
944531AF1-118 GEN
Solar/Wind Harmer
39.701
274772LINCOLN ;3U
Adder
10.701
274724RIVER EC ;11
Adder
22.258
274752CRETE EC ;2U
Adder
10.338
274753CRETE EC ;3U
Adder
10.338
970707AG2-453 GEN
Solar/Wind Harmer
28.587
274814UNIV PK N;0U
Adder
6.326
274807UNIV PK N;3U
Adder
6.312
274811UNIV PK N;7U
Adder
6.271
270063AE2-323 C
Solar/Wind Harmer
0
270505AE1-170 C O1
Solar/Wind Harmer
9.169
972259AH1-714 GEN
Adder
23.869
274826FISK ;BP
Adder
13.684
274803UNIV PARK;6U
Adder
7.287
274887GEN-1.85
Solar/Wind Harmer
0.227
276843GEN-1.7
Solar/Wind Harmer
0.282
276806AD2-047 C O1
Solar/Wind Harmer
4.941
972038AH1-567 GEN2
Adder
0.456
945111AF1-176 GEN
Solar/Wind Harmer
7.059
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
36.827
274729ELWOOD EC;1P
Adder
20.436
274730ELWOOD EC;6P
Adder
20.437
274734ELWOOD EC;8P
Adder
20.437
274736ELWOOD EC;9P
Adder
20.437
943121AE2-341 GEN
Solar/Wind Harmer
14.508
943591AF1-030 GEN
Solar/Wind Harmer
9.648
965021AG1-366 GEN
Solar/Wind Harmer
2.872
274862TOP CROP ;2U
Solar/Wind Harmer
1.159
274682WAUKEGAN ;7U
Adder
22.104
964401AG1-302 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.703
274879MINONK ;1U
Solar/Wind Harmer
0.355
946671AF1-331 GEN
Solar/Wind Harmer
0.906
274855GSG-6 ;RU
Solar/Wind Harmer
0.31
274850MENDOTA H;RU
Solar/Wind Harmer
0.099
959091AF2-200 GEN
Solar/Wind Harmer
16.931
970571AG2-364 GEN
Solar/Wind Harmer
16.823
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
11.167
274767LEE CO EC;8U
Adder
11.036
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
8.328
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.277
965091AG1-374 GEN
Solar/Wind Harmer
24.6
959611AF2-252 GEN
Solar/Wind Harmer
2.733
24386205FR-12G C
Solar/Wind Harmer
0
965931AG1-462 GEN
Solar/Wind Harmer
20.87
971087AG2-675 GEN
Solar/Wind Harmer
4.365
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.879
971993AH1-541 GEN
Solar/Wind Harmer
3.686
957381AF2-032 GEN
Solar/Wind Harmer
1.767
942481AE2-261 GEN
Solar/Wind Harmer
23.27
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
270004AE1-209 GEN
Solar/Wind Harmer
1.678
970825AG2-519 GEN
Solar/Wind Harmer
5.778
24695305TIMB G C
Solar/Wind Harmer
0.648
946031AF1-268 GEN
Solar/Wind Harmer
7.259
970193AG2-126 GEN
Solar/Wind Harmer
11.441
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
11.403
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.266
270491AE1-102 GEN2
Solar/Wind Harmer
0.958
24728705AND G3
Adder
8.312
24728505AND G1
Adder
3.974
270391AF1-285 GEN3
Solar/Wind Harmer
0.462
24721705FLATG2
50/50
25.639
270102X2-052 ST
50/50
2.04
270100X2-052 CT1
50/50
1.885
270101X2-052 CT2
50/50
1.885
970349AG2-230 GEN
Solar/Wind Harmer
13.856
965681AG1-436 GEN
Solar/Wind Harmer
11.105
965791AG1-447 GEN
Solar/Wind Harmer
8.144
274770LINCOLN ;1U
Adder
10.701
274771LINCOLN ;2U
Adder
10.701
274805UNIV PK N;1U
Adder
6.285
274808UNIV PK N;4U
Adder
6.243
247620Y3-023
Adder
0.576
274888KELLY CRK;1U
Solar/Wind Harmer
0.509
276776AD2-060 GEN
Solar/Wind Harmer
0.93
958011AF2-095 GEN
Solar/Wind Harmer
12.557
970941AG2-585 GEN
Solar/Wind Harmer
4.796
276897AD1-100 C
Solar/Wind Harmer
21.761
274674JOLIET 9 ;6U
Adder
19.151
961051AF2-396 GEN
Solar/Wind Harmer
17.344
961051AF2-396 GEN
Solar/Wind Harmer
11.563
276893AG1-478 C
Solar/Wind Harmer
0.578
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274696ROCKY RD ;4P
Adder
14.031
274695ROCKY RD ;2P
Adder
13.708
274693ROCKY RD ;1P
Adder
13.573
274697ROCKY RD ;3P
Adder
3.724
958481AF2-142 GEN
Solar/Wind Harmer
12.877
274683WAUKEGAN ;8U
Adder
25.9
274683WAUKEGAN ;8U
Adder
21.833
962691AG1-118 GEN
Solar/Wind Harmer
25.676
958491AF2-143 GEN
Solar/Wind Harmer
12.799
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
16.931
971343AH1-151 GEN
Solar/Wind Harmer
16.931
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.565
960971AF2-388 GEN
Solar/Wind Harmer
4.962
972235AH1-702 GEN1
Adder
3.049
972236AH1-702 GEN2
Adder
2.651
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
938861AE1-114 GEN
Solar/Wind Harmer
4.755
274764LEE CO EC;5U
Adder
11.194
274765LEE CO EC;6U
Adder
11.194
274762LEE CO EC;3U
Adder
11.167
274763LEE CO EC;4U
Adder
11.062
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.343
276645AC1-214 GEN1
Solar/Wind Harmer
0.326
942111AE2-223 GEN
Solar/Wind Harmer
2.688
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
942221AE2-234 GEN
Solar/Wind Harmer
3.3
960611AF2-352 GEN
Solar/Wind Harmer
2.733
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.927
970291AG2-192 GEN
Solar/Wind Harmer
1.039
970291AG2-192 GEN
Solar/Wind Harmer
0.479
970241AG2-163 GEN
Solar/Wind Harmer
4.651
270031AE2-169
Solar/Wind Harmer
4.369
270599AE1-208 GEN
Solar/Wind Harmer
7.282
276615X2-022 GEN
Solar/Wind Harmer
0.082
276838X2-022 GEN2
Solar/Wind Harmer
0.445
971613AH1-306 GEN
Solar/Wind Harmer
3.795
270246TR4_N_V150
Solar/Wind Harmer
0.05
270247TR4_N_V136
Solar/Wind Harmer
0.05
276916AD2-100_GEN
Solar/Wind Harmer
16.28
276911AD2-131_GEN
Solar/Wind Harmer
1.072
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
17.757
945391AF1-204 GEN
Solar/Wind Harmer
8.104
964611AG1-324 GEN
Solar/Wind Harmer
0.571
270201AC2-176 GEN
Solar/Wind Harmer
0
247621Y3-024
Adder
0.257
926881AC1-175 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.297
971587AH1-292 GEN
Solar/Wind Harmer
5.361
270383AD1-128 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
7.112
970885AG2-551 GEN
Solar/Wind Harmer
2.371
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.29
270462AD2-086
Solar/Wind Harmer
0
24728805RICHG1
Adder
3.474
24728905RICHG2
Adder
3.474
24723005RIVRG1
Adder
16.391
24723105RIVRG2
Adder
16.391
24721805FLATG3
50/50
1.726
24344105CKG2
50/50
10.12
962761AG1-125 GEN
Solar/Wind Harmer
74.4
970149AG2-104 GEN
Solar/Wind Harmer
40.177
970155AG2-107 GEN
Solar/Wind Harmer
47.51
274773LINCOLN ;4U
Adder
10.701
274774LINCOLN ;5U
Adder
10.701
274723RIVER EC ;12
Adder
22.518
24639705ELKHART HY
Adder
0.193
274751CRETE EC ;1U
Adder
10.338
274754CRETE EC ;4U
Adder
10.338
274812UNIV PK N;8U
Adder
6.271
957891AF2-083 GEN
Solar/Wind Harmer
14.548
274802UNIV PARK;5U
Adder
7.287
945111AF1-176 GEN
Solar/Wind Harmer
15.539
941551AE2-152 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
18.275
274676JOLIET 29;8U
Adder
38.191
274674JOLIET 9 ;6U
Adder
19.151
274732ELWOOD EC;7P
Adder
20.437
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
4.515
274745AC1-111 GEN9
Adder
6.924
270055AF2-134 C O1
Solar/Wind Harmer
0
965011AG1-365 GEN
Solar/Wind Harmer
8.615
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.395
274861TOP CROP ;1U
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
22.104
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274828WAUKEGAN ;BP
Adder
13.576
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.138
939401AE1-172 GEN
Solar/Wind Harmer
6.395
962781AG1-127 GEN
Solar/Wind Harmer
8.134
274872LEEDK;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.993
971997AH1-543 GEN
Solar/Wind Harmer
4.466
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
10.605
957471AF2-041 GEN
Solar/Wind Harmer
25.396
959081AF2-199 GEN
Solar/Wind Harmer
8.465
971067AG2-660 GEN
Solar/Wind Harmer
2.822
965651AG1-433 GEN
Solar/Wind Harmer
2.481
274822ROCKFORD ;11
Adder
23.769
970819AG2-516 GEN
Solar/Wind Harmer
10.109
970569AG2-363 GEN
Solar/Wind Harmer
25.234
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
11.167
274766LEE CO EC;7U
Adder
11.036
958861AF2-177 GEN
Solar/Wind Harmer
3.623
276708O09 GEN2
Solar/Wind Harmer
0.294
276646AC1-214 GEN2
Solar/Wind Harmer
0.326
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
11.579
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
18.871
276621W2-048 GEN
Solar/Wind Harmer
0.396
270594AE1-207 GEN
Solar/Wind Harmer
8.855
270032AE2-172
Solar/Wind Harmer
5.271
270024AE2-089 GEN
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
8.696
965911AG1-460 GEN
Solar/Wind Harmer
1.557
270005AE1-210 C O1
Solar/Wind Harmer
1.678
970825AG2-519 GEN
Solar/Wind Harmer
2.723
965421AG1-410 GEN
Solar/Wind Harmer
22.474
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.436
246936BC-WTG1
Solar/Wind Harmer
0.297
270489AE1-102 GEN1
Solar/Wind Harmer
0.958
24728605AND G2
Adder
3.974
970091AG2-072 GEN
Adder
78.436
970773AG2-487 GEN
Solar/Wind Harmer
1.228
270317AD1-130_GEN
Solar/Wind Harmer
0
972203AH1-686 GEN
Adder
2.059
24723205RIVRG3
Adder
16.391
CPLELTFEXP_CPLE->PJM
CLTF
3.255
CBM West 2LTFEXP_CBM-W2->PJM
CBM
123.551
NYPJM->LTFIMP_NY
CLTF
3.901
LGEELTFEXP_LGEE->PJM
CLTF
5.998
WECLTFEXP_WEC->PJM
CLTF
4.618
AG2-052LTFEXP_AG2-052->PJM
LTF
0.285
AH1-155LTFEXP_AH1-155->PJM
LTF
0.428
LAGNLTFEXP_LAGN->PJM
CLTF
16.713
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.242
TVALTFEXP_TVA->PJM
CLTF
7.96
CBM West 1LTFEXP_CBM-W1->PJM
CBM
148.673
CBM South 1LTFEXP_CBM-S1->PJM
CBM
30.416
MECLTFEXP_MEC->PJM
CLTF
18.61
SIGELTFEXP_SIGE->PJM
CLTF
0.498

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o AEP_P4_#8085_05MARYSV 345_H_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8085_05MARYSV 345_H_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.34 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4694.66
MW Contribution:
61.68
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
1.321
960681AF2-359 GEN
Solar/Wind Harmer
4.212
274775LINCOLN ;6U
Adder
6.874
274776LINCOLN ;7U
Adder
6.874
274777LINCOLN ;8U
Adder
6.874
971771AH1-392 GEN
Solar/Wind Harmer
9.965
270526AF1-158 GEN
Solar/Wind Harmer
5.017
24721705FLATG2
50/50
19.618
270102X2-052 ST
50/50
1.789
270100X2-052 CT1
50/50
1.653
270101X2-052 CT2
50/50
1.653
970349AG2-230 GEN
Solar/Wind Harmer
17.731
965681AG1-436 GEN
Solar/Wind Harmer
13.935
965791AG1-447 GEN
Solar/Wind Harmer
7.129
274770LINCOLN ;1U
Adder
6.874
274771LINCOLN ;2U
Adder
6.874
274805UNIV PK N;1U
Adder
5.456
24722005FLATG5
50/50
1.321
24721905FLATG4
50/50
24.129
962771AG1-126 GEN
Solar/Wind Harmer
99.887
970153AG2-106 GEN
Solar/Wind Harmer
43.555
971347AH1-153 GEN
Solar/Wind Harmer
5.91
270043AE2-236 GEN
Solar/Wind Harmer
6.144
274772LINCOLN ;3U
Adder
6.874
270071AF1-092 GEN
Solar/Wind Harmer
16.573
274827FISK ;RP
Adder
8.415
972228AH1-698 GEN2
Adder
4.017
972227AH1-698 GEN1
Adder
2.828
972037AH1-567 GEN1
Adder
0.198
960591AF2-350 GEN
Solar/Wind Harmer
10.843
274800UNIV PARK;3U
Adder
6.319
274801UNIV PARK;4U
Adder
6.319
274687WILL CNTY;4U
Adder
30.15
274687WILL CNTY;4U
Adder
30.15
274675JOLIET 29;7U
Adder
33.083
274675JOLIET 29;7U
Adder
31.902
274728ELWOOD EC;5P
Adder
17.689
274731ELWOOD EC;2P
Adder
17.689
274733ELWOOD EC;3P
Adder
17.689
274735ELWOOD EC;4P
Adder
17.689
970833AG2-524 GEN
Solar/Wind Harmer
9.394
970833AG2-524 GEN
Solar/Wind Harmer
4.369
276893AG1-478 C
Solar/Wind Harmer
0.592
274744AC1-111 GEN8
Adder
5.988
274746AC1-111 G10
Adder
5.988
944161AF1-084 GEN
Solar/Wind Harmer
2.361
24729505KEY G4
Adder
6.826
970073AG2-061 GEN
Solar/Wind Harmer
2.442
970031AG2-029 GEN
Solar/Wind Harmer
26.139
971675AH1-338 GEN
Solar/Wind Harmer
18.803
971411AH1-196 GEN
Solar/Wind Harmer
15.668
276861AD2-134 GEN
Solar/Wind Harmer
1.865
276863AD2-134 GEN
Solar/Wind Harmer
1.865
958391AF2-133 GEN
Solar/Wind Harmer
9.431
971171AH1-044 GEN
Solar/Wind Harmer
20.788
274863CRW1-WTG
Solar/Wind Harmer
5.799
274864CRW2-WTG
Solar/Wind Harmer
5.799
276889AE2-281 GEN
Solar/Wind Harmer
1.989
274823ROCKFORD ;21
Adder
20.198
959141AF2-205 GEN
Solar/Wind Harmer
6.254
274856ECOGROVE ;U1
Solar/Wind Harmer
3.476
276611AD2-172 GEN
Solar/Wind Harmer
2.637
276612AE2-035 GEN
Solar/Wind Harmer
2.637
926823AC1-168 GEN
Solar/Wind Harmer
4.419
972267AH1-718 GEN
Adder
4.228
274808UNIV PK N;4U
Adder
5.42
274888KELLY CRK;1U
Solar/Wind Harmer
6.399
276776AD2-060 GEN
Solar/Wind Harmer
0.454
958011AF2-095 GEN
Solar/Wind Harmer
15.614
970941AG2-585 GEN
Solar/Wind Harmer
5.964
276897AD1-100 C
Solar/Wind Harmer
50.231
961051AF2-396 GEN
Solar/Wind Harmer
17.118
961051AF2-396 GEN
Solar/Wind Harmer
7.962
274674JOLIET 9 ;6U
Adder
16.582
276893AG1-478 C
Solar/Wind Harmer
0.471
247620Y3-023
Adder
0.494
274695ROCKY RD ;2P
Adder
11.821
274693ROCKY RD ;1P
Adder
11.705
274697ROCKY RD ;3P
Adder
3.211
274696ROCKY RD ;4P
Adder
12.1
270535AF1-215 GEN1
Solar/Wind Harmer
4.813
270536AF1-215 GEN2
Solar/Wind Harmer
4.813
958481AF2-142 GEN
Solar/Wind Harmer
15.893
274683WAUKEGAN ;8U
Adder
22.318
274683WAUKEGAN ;8U
Adder
18.813
962691AG1-118 GEN
Solar/Wind Harmer
31.685
960751AF2-366 GEN
Solar/Wind Harmer
3.025
958491AF2-143 GEN
Solar/Wind Harmer
15.75
276901AD2-066 C O1
Solar/Wind Harmer
3.679
971341AH1-150 GEN
Solar/Wind Harmer
20.788
971343AH1-151 GEN
Solar/Wind Harmer
20.788
276872AE1-163_GEN1
Solar/Wind Harmer
6.962
276876AE1-163_GEN2
Solar/Wind Harmer
6.962
972235AH1-702 GEN1
Adder
2.608
972236AH1-702 GEN2
Adder
2.268
274764LEE CO EC;5U
Adder
9.541
24441505OLIV SLR
Solar/Wind Harmer
0.148
247643Z2-116 C
Solar/Wind Harmer
0.077
274724RIVER EC ;11
Adder
19.358
970707AG2-453 GEN
Solar/Wind Harmer
30.551
276164X3-005 C
Solar/Wind Harmer
0.766
972231SS25-0005
Solar/Wind Harmer
10.343
972181SS23-001
Solar/Wind Harmer
6.464
274752CRETE EC ;2U
Adder
5.327
274753CRETE EC ;3U
Adder
5.327
270505AE1-170 C O1
Solar/Wind Harmer
16.341
274814UNIV PK N;0U
Adder
5.491
274807UNIV PK N;3U
Adder
5.48
274811UNIV PK N;7U
Adder
5.444
972259AH1-714 GEN
Adder
20.728
274826FISK ;BP
Adder
11.874
274803UNIV PARK;6U
Adder
6.322
274887GEN-1.85
Solar/Wind Harmer
5.777
276772AC2-154 GEN
Solar/Wind Harmer
3.026
276843GEN-1.7
Solar/Wind Harmer
0.622
276806AD2-047 C O1
Solar/Wind Harmer
11.6
972038AH1-567 GEN2
Adder
0.396
945111AF1-176 GEN
Solar/Wind Harmer
6.122
939351AE1-166 GEN
Solar/Wind Harmer
6.413
274676JOLIET 29;8U
Adder
31.901
274729ELWOOD EC;1P
Adder
17.689
274730ELWOOD EC;6P
Adder
17.689
274734ELWOOD EC;8P
Adder
17.689
274736ELWOOD EC;9P
Adder
17.689
943121AE2-341 GEN
Solar/Wind Harmer
16.099
943591AF1-030 GEN
Solar/Wind Harmer
10.733
944531AF1-118 GEN
Solar/Wind Harmer
37.545
270063AE2-323 C
Solar/Wind Harmer
2.331
274682WAUKEGAN ;7U
Adder
19.052
274862TOP CROP ;2U
Solar/Wind Harmer
5.357
964401AG1-302 GEN
Solar/Wind Harmer
9.498
276868AE1-113 GEN
Solar/Wind Harmer
10.588
274879MINONK ;1U
Solar/Wind Harmer
7.059
276799AD1-013 GEN
Solar/Wind Harmer
2.309
946671AF1-331 GEN
Solar/Wind Harmer
0.437
274855GSG-6 ;RU
Solar/Wind Harmer
3.856
274850MENDOTA H;RU
Solar/Wind Harmer
2.681
276602WESTBROOK C
Solar/Wind Harmer
2.22
959091AF2-200 GEN
Solar/Wind Harmer
20.788
274760LEE CO EC;1U
Adder
9.518
274767LEE CO EC;8U
Adder
9.406
970571AG2-364 GEN
Solar/Wind Harmer
17.349
274765LEE CO EC;6U
Adder
9.541
274762LEE CO EC;3U
Adder
9.518
274763LEE CO EC;4U
Adder
9.429
270054AF2-122 C O1
Solar/Wind Helper
1.534
24344105CKG2
50/50
9.16
24721805FLATG3
50/50
1.321
962761AG1-125 GEN
Solar/Wind Harmer
99.887
970149AG2-104 GEN
Solar/Wind Harmer
61.68
970155AG2-107 GEN
Solar/Wind Harmer
43.555
972207SS24-0001
Solar/Wind Harmer
24.439
274773LINCOLN ;4U
Adder
6.874
274774LINCOLN ;5U
Adder
6.874
270216AD2-079_GEN
Solar/Wind Harmer
0.665
274723RIVER EC ;12
Adder
19.582
274751CRETE EC ;1U
Adder
5.327
274754CRETE EC ;4U
Adder
5.327
957891AF2-083 GEN
Solar/Wind Harmer
16.317
274812UNIV PK N;8U
Adder
5.444
24639705ELKHART HY
Adder
0.166
274802UNIV PARK;5U
Adder
6.322
945111AF1-176 GEN
Solar/Wind Harmer
19.317
941551AE2-152 GEN
Solar/Wind Harmer
4.904
274676JOLIET 29;8U
Adder
33.083
274674JOLIET 9 ;6U
Adder
16.582
274732ELWOOD EC;7P
Adder
17.689
270449AD2-020 GEN
Solar/Wind Harmer
3.015
943021AE2-325 GEN
Solar/Wind Harmer
3.918
274871GR RIDGE ;2U
Solar/Wind Harmer
8.271
274847GR RIDGE ;BU
Solar/Wind Harmer
5.438
970373AG2-245 GEN
Solar/Wind Harmer
22.572
274745AC1-111 GEN9
Adder
5.988
270055AF2-134 C O1
Solar/Wind Harmer
3.209
274682WAUKEGAN ;7U
Adder
19.052
276694AA1-018 GEN2
Solar/Wind Harmer
6.686
276691AA1-018 GEN1
Solar/Wind Harmer
0.799
274828WAUKEGAN ;BP
Adder
11.699
274861TOP CROP ;1U
Solar/Wind Harmer
6.416
962781AG1-127 GEN
Solar/Wind Harmer
10.025
24441205WTRV SLR C
Solar/Wind Harmer
0.142
274872LEEDK;1U
Solar/Wind Harmer
8.639
939401AE1-172 GEN
Solar/Wind Harmer
14.653
276805AD2-038 GEN
Solar/Wind Harmer
5.384
958381AF2-132 GEN
Solar/Wind Harmer
9.498
276882AE2-255 GEN
Solar/Wind Harmer
3.53
971997AH1-543 GEN
Solar/Wind Harmer
16.465
964861AG1-349 GEN
Solar/Wind Harmer
8.219
971917AH1-482 GEN
Solar/Wind Harmer
9.483
957471AF2-041 GEN
Solar/Wind Harmer
31.182
959081AF2-199 GEN
Solar/Wind Harmer
10.394
971067AG2-660 GEN
Solar/Wind Harmer
2.417
274822ROCKFORD ;11
Adder
20.346
970819AG2-516 GEN
Solar/Wind Harmer
12.386
274761LEE CO EC;2U
Adder
9.518
274766LEE CO EC;7U
Adder
9.406
970569AG2-363 GEN
Solar/Wind Harmer
26.024
CPLELTFEXP_CPLE->PJM
CLTF
1.839
CBM West 2LTFEXP_CBM-W2->PJM
CBM
91.434
NYPJM->LTFIMP_NY
CLTF
2.631
LGEELTFEXP_LGEE->PJM
CLTF
3.807
WECLTFEXP_WEC->PJM
CLTF
3.948
AG2-052LTFEXP_AG2-052->PJM
LTF
0.243
AH1-155LTFEXP_AH1-155->PJM
LTF
0.365
LAGNLTFEXP_LAGN->PJM
CLTF
11.984
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.904
TVALTFEXP_TVA->PJM
CLTF
5.443
CBM West 1LTFEXP_CBM-W1->PJM
CBM
119.029
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.507
MECLTFEXP_MEC->PJM
CLTF
15.271
SIGELTFEXP_SIGE->PJM
CLTF
0.352

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o AEP_P2-2_#8072_05MARYSV 765_2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#8072_05MARYSV 765_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:112.49 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4659.23
MW Contribution:
61.9
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
1.329
960681AF2-359 GEN
Solar/Wind Harmer
4.162
274775LINCOLN ;6U
Adder
6.799
274776LINCOLN ;7U
Adder
6.799
274777LINCOLN ;8U
Adder
6.799
971771AH1-392 GEN
Solar/Wind Harmer
9.834
270526AF1-158 GEN
Solar/Wind Harmer
4.953
270071AF1-092 GEN
Solar/Wind Harmer
16.309
274827FISK ;RP
Adder
8.32
972228AH1-698 GEN2
Adder
3.972
972227AH1-698 GEN1
Adder
2.797
960591AF2-350 GEN
Solar/Wind Harmer
10.721
972037AH1-567 GEN1
Adder
0.196
274800UNIV PARK;3U
Adder
6.248
274801UNIV PARK;4U
Adder
6.248
274687WILL CNTY;4U
Adder
29.812
274687WILL CNTY;4U
Adder
29.812
274675JOLIET 29;7U
Adder
32.713
274675JOLIET 29;7U
Adder
31.545
274728ELWOOD EC;5P
Adder
17.491
274731ELWOOD EC;2P
Adder
17.491
274733ELWOOD EC;3P
Adder
17.491
274735ELWOOD EC;4P
Adder
17.491
970833AG2-524 GEN
Solar/Wind Harmer
9.289
970833AG2-524 GEN
Solar/Wind Harmer
4.321
276893AG1-478 C
Solar/Wind Harmer
0.585
274744AC1-111 GEN8
Adder
5.922
274746AC1-111 G10
Adder
5.922
944161AF1-084 GEN
Solar/Wind Harmer
2.328
970073AG2-061 GEN
Solar/Wind Harmer
2.414
24729505KEY G4
Adder
6.715
971675AH1-338 GEN
Solar/Wind Harmer
18.594
24721705FLATG2
50/50
19.739
270102X2-052 ST
50/50
1.768
270100X2-052 CT1
50/50
1.633
270101X2-052 CT2
50/50
1.633
970349AG2-230 GEN
Solar/Wind Harmer
17.533
965681AG1-436 GEN
Solar/Wind Harmer
13.768
965791AG1-447 GEN
Solar/Wind Harmer
7.044
274770LINCOLN ;1U
Adder
6.799
274771LINCOLN ;2U
Adder
6.799
274805UNIV PK N;1U
Adder
5.393
274808UNIV PK N;4U
Adder
5.358
274888KELLY CRK;1U
Solar/Wind Harmer
6.327
276776AD2-060 GEN
Solar/Wind Harmer
0.449
958011AF2-095 GEN
Solar/Wind Harmer
15.439
970941AG2-585 GEN
Solar/Wind Harmer
5.897
276897AD1-100 C
Solar/Wind Harmer
49.671
274674JOLIET 9 ;6U
Adder
16.397
276893AG1-478 C
Solar/Wind Harmer
0.466
961051AF2-396 GEN
Solar/Wind Harmer
16.875
961051AF2-396 GEN
Solar/Wind Harmer
7.849
247620Y3-023
Adder
0.486
274696ROCKY RD ;4P
Adder
11.966
274695ROCKY RD ;2P
Adder
11.69
274693ROCKY RD ;1P
Adder
11.575
274697ROCKY RD ;3P
Adder
3.176
270535AF1-215 GEN1
Solar/Wind Harmer
4.754
270536AF1-215 GEN2
Solar/Wind Harmer
4.754
958481AF2-142 GEN
Solar/Wind Harmer
15.714
274683WAUKEGAN ;8U
Adder
22.069
274683WAUKEGAN ;8U
Adder
18.603
962691AG1-118 GEN
Solar/Wind Harmer
31.334
960751AF2-366 GEN
Solar/Wind Harmer
2.991
958491AF2-143 GEN
Solar/Wind Harmer
15.572
276901AD2-066 C O1
Solar/Wind Harmer
3.638
971341AH1-150 GEN
Solar/Wind Harmer
20.556
971343AH1-151 GEN
Solar/Wind Harmer
20.556
276872AE1-163_GEN1
Solar/Wind Harmer
6.883
276876AE1-163_GEN2
Solar/Wind Harmer
6.883
972235AH1-702 GEN1
Adder
2.579
972236AH1-702 GEN2
Adder
2.243
274764LEE CO EC;5U
Adder
9.434
274765LEE CO EC;6U
Adder
9.434
274762LEE CO EC;3U
Adder
9.412
274763LEE CO EC;4U
Adder
9.323
270054AF2-122 C O1
Solar/Wind Helper
1.497
971411AH1-196 GEN
Solar/Wind Harmer
15.493
276861AD2-134 GEN
Solar/Wind Harmer
1.844
276863AD2-134 GEN
Solar/Wind Harmer
1.844
971171AH1-044 GEN
Solar/Wind Harmer
20.556
274863CRW1-WTG
Solar/Wind Harmer
5.734
274864CRW2-WTG
Solar/Wind Harmer
5.734
958391AF2-133 GEN
Solar/Wind Harmer
9.315
970031AG2-029 GEN
Solar/Wind Harmer
25.643
276889AE2-281 GEN
Solar/Wind Harmer
1.967
274823ROCKFORD ;21
Adder
19.973
959141AF2-205 GEN
Solar/Wind Harmer
6.177
274856ECOGROVE ;U1
Solar/Wind Harmer
3.438
276611AD2-172 GEN
Solar/Wind Harmer
2.608
276612AE2-035 GEN
Solar/Wind Harmer
2.608
926823AC1-168 GEN
Solar/Wind Harmer
4.369
972267AH1-718 GEN
Adder
4.181
24344105CKG2
50/50
9.067
24721805FLATG3
50/50
1.329
962761AG1-125 GEN
Solar/Wind Harmer
100.25
970149AG2-104 GEN
Solar/Wind Harmer
61.904
970155AG2-107 GEN
Solar/Wind Harmer
43.713
972207SS24-0001
Solar/Wind Harmer
24.173
274773LINCOLN ;4U
Adder
6.799
274774LINCOLN ;5U
Adder
6.799
270216AD2-079_GEN
Solar/Wind Harmer
0.655
274723RIVER EC ;12
Adder
19.359
274751CRETE EC ;1U
Adder
5.265
274754CRETE EC ;4U
Adder
5.265
274812UNIV PK N;8U
Adder
5.382
957891AF2-083 GEN
Solar/Wind Harmer
16.09
274802UNIV PARK;5U
Adder
6.25
941551AE2-152 GEN
Solar/Wind Harmer
4.849
24639705ELKHART HY
Adder
0.164
945111AF1-176 GEN
Solar/Wind Harmer
19.042
274676JOLIET 29;8U
Adder
32.713
274674JOLIET 9 ;6U
Adder
16.397
274732ELWOOD EC;7P
Adder
17.491
274871GR RIDGE ;2U
Solar/Wind Harmer
8.179
274847GR RIDGE ;BU
Solar/Wind Harmer
5.378
970373AG2-245 GEN
Solar/Wind Harmer
22.298
270449AD2-020 GEN
Solar/Wind Harmer
2.973
943021AE2-325 GEN
Solar/Wind Harmer
3.863
274745AC1-111 GEN9
Adder
5.922
274682WAUKEGAN ;7U
Adder
18.84
270055AF2-134 C O1
Solar/Wind Harmer
3.169
276694AA1-018 GEN2
Solar/Wind Harmer
6.61
276691AA1-018 GEN1
Solar/Wind Harmer
0.79
274828WAUKEGAN ;BP
Adder
11.568
274861TOP CROP ;1U
Solar/Wind Harmer
6.343
962781AG1-127 GEN
Solar/Wind Harmer
9.914
274872LEEDK;1U
Solar/Wind Harmer
8.543
939401AE1-172 GEN
Solar/Wind Harmer
14.488
276805AD2-038 GEN
Solar/Wind Harmer
5.324
24441205WTRV SLR C
Solar/Wind Harmer
0.14
276882AE2-255 GEN
Solar/Wind Harmer
3.49
971997AH1-543 GEN
Solar/Wind Harmer
16.281
958381AF2-132 GEN
Solar/Wind Harmer
9.381
964861AG1-349 GEN
Solar/Wind Harmer
8.119
971917AH1-482 GEN
Solar/Wind Harmer
9.367
957471AF2-041 GEN
Solar/Wind Harmer
30.834
959081AF2-199 GEN
Solar/Wind Harmer
10.278
971067AG2-660 GEN
Solar/Wind Harmer
2.39
274822ROCKFORD ;11
Adder
20.119
970819AG2-516 GEN
Solar/Wind Harmer
12.248
274761LEE CO EC;2U
Adder
9.412
274766LEE CO EC;7U
Adder
9.301
970569AG2-363 GEN
Solar/Wind Harmer
25.73
24722005FLATG5
50/50
1.329
24721905FLATG4
50/50
24.278
962771AG1-126 GEN
Solar/Wind Harmer
100.25
970153AG2-106 GEN
Solar/Wind Harmer
43.713
971347AH1-153 GEN
Solar/Wind Harmer
5.844
270043AE2-236 GEN
Solar/Wind Harmer
6.039
274772LINCOLN ;3U
Adder
6.799
24441505OLIV SLR
Solar/Wind Harmer
0.146
247643Z2-116 C
Solar/Wind Harmer
0.076
274724RIVER EC ;11
Adder
19.137
970707AG2-453 GEN
Solar/Wind Harmer
30.216
276164X3-005 C
Solar/Wind Harmer
0.757
972231SS25-0005
Solar/Wind Harmer
10.223
972181SS23-001
Solar/Wind Harmer
6.39
274752CRETE EC ;2U
Adder
5.265
274753CRETE EC ;3U
Adder
5.265
274814UNIV PK N;0U
Adder
5.429
274807UNIV PK N;3U
Adder
5.417
274811UNIV PK N;7U
Adder
5.382
972259AH1-714 GEN
Adder
20.498
270505AE1-170 C O1
Solar/Wind Harmer
16.115
274826FISK ;BP
Adder
11.74
274887GEN-1.85
Solar/Wind Harmer
5.712
276772AC2-154 GEN
Solar/Wind Harmer
2.992
276843GEN-1.7
Solar/Wind Harmer
0.615
276806AD2-047 C O1
Solar/Wind Harmer
11.469
274803UNIV PARK;6U
Adder
6.25
972038AH1-567 GEN2
Adder
0.391
939351AE1-166 GEN
Solar/Wind Harmer
6.341
945111AF1-176 GEN
Solar/Wind Harmer
6.035
274676JOLIET 29;8U
Adder
31.544
274729ELWOOD EC;1P
Adder
17.491
274730ELWOOD EC;6P
Adder
17.491
274734ELWOOD EC;8P
Adder
17.491
274736ELWOOD EC;9P
Adder
17.491
943121AE2-341 GEN
Solar/Wind Harmer
15.921
943591AF1-030 GEN
Solar/Wind Harmer
10.614
944531AF1-118 GEN
Solar/Wind Harmer
36.947
274682WAUKEGAN ;7U
Adder
18.84
274862TOP CROP ;2U
Solar/Wind Harmer
5.296
270063AE2-323 C
Solar/Wind Harmer
2.288
276868AE1-113 GEN
Solar/Wind Harmer
10.469
274879MINONK ;1U
Solar/Wind Harmer
6.98
964401AG1-302 GEN
Solar/Wind Harmer
9.381
276799AD1-013 GEN
Solar/Wind Harmer
2.283
946671AF1-331 GEN
Solar/Wind Harmer
0.433
274855GSG-6 ;RU
Solar/Wind Harmer
3.813
274850MENDOTA H;RU
Solar/Wind Harmer
2.651
276602WESTBROOK C
Solar/Wind Harmer
2.195
959091AF2-200 GEN
Solar/Wind Harmer
20.556
274760LEE CO EC;1U
Adder
9.412
274767LEE CO EC;8U
Adder
9.301
970571AG2-364 GEN
Solar/Wind Harmer
17.153
CPLELTFEXP_CPLE->PJM
CLTF
1.857
CBM West 2LTFEXP_CBM-W2->PJM
CBM
90.382
NYPJM->LTFIMP_NY
CLTF
2.602
LGEELTFEXP_LGEE->PJM
CLTF
3.741
WECLTFEXP_WEC->PJM
CLTF
3.904
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
AH1-155LTFEXP_AH1-155->PJM
LTF
0.36
LAGNLTFEXP_LAGN->PJM
CLTF
11.871
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.921
TVALTFEXP_TVA->PJM
CLTF
5.394
CBM West 1LTFEXP_CBM-W1->PJM
CBM
117.032
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.292
MECLTFEXP_MEC->PJM
CLTF
15.099
SIGELTFEXP_SIGE->PJM
CLTF
0.346

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o AEP_P1-2_#706_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#706_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.0 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4473.55
MW Contribution:
59.15
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721705FLATG2
50/50
69.962
24721605FLATG1
50/50
4.711
270144AC1-141 ST1_
50/50
3.051
24641605TWIN BRNCH
50/50
0.025
24344005CKG1
50/50
9.268
24653605MOTTVILLE
50/50
0.005
959331AF2-224 GEN
Solar/Wind Harmer
7.224
270578AF1-285 GEN2
Solar/Wind Harmer
0.682
270071AF1-092 GEN
Solar/Wind Harmer
19.599
970031AG2-029 GEN
Solar/Wind Harmer
5.461
971771AH1-392 GEN
Solar/Wind Harmer
10.022
270526AF1-158 GEN
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
24729505KEY G4
Adder
9.105
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.376
965041AG1-368 GEN
Solar/Wind Harmer
9.736
274775LINCOLN ;6U
Adder
11.612
274776LINCOLN ;7U
Adder
11.612
274777LINCOLN ;8U
Adder
11.612
247521TR3_G114
Solar/Wind Harmer
0.347
965051AG1-369 GEN
Solar/Wind Harmer
4.782
963791AG1-232 GEN
Solar/Wind Harmer
12.72
972037AH1-567 GEN1
Adder
0.247
274827FISK ;RP
Adder
10.469
960591AF2-350 GEN
Solar/Wind Harmer
9.405
274800UNIV PARK;3U
Adder
7.859
274801UNIV PARK;4U
Adder
7.859
972228AH1-698 GEN2
Adder
4.989
972227AH1-698 GEN1
Adder
3.513
957201AF2-014 GEN
Solar/Wind Harmer
0.001
247620Y3-023
50/50
0.701
270102X2-052 ST
50/50
2.277
270100X2-052 CT1
50/50
2.104
270101X2-052 CT2
50/50
2.104
24643105BUCHANAN
50/50
0.018
270349AD2-093_GEN
Solar/Wind Harmer
0.002
270471AD2-092_GEN
Solar/Wind Harmer
0.002
970349AG2-230 GEN
Solar/Wind Harmer
15.664
961051AF2-396 GEN
Solar/Wind Harmer
19.838
961051AF2-396 GEN
Solar/Wind Harmer
13.225
965681AG1-436 GEN
Solar/Wind Harmer
12.356
965791AG1-447 GEN
Solar/Wind Harmer
9.061
270462AD2-086
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
11.612
274771LINCOLN ;2U
Adder
11.612
270246TR4_N_V150
Solar/Wind Harmer
0.061
270247TR4_N_V136
Solar/Wind Harmer
0.061
274805UNIV PK N;1U
Adder
6.81
274808UNIV PK N;4U
Adder
6.766
274888KELLY CRK;1U
Solar/Wind Harmer
0.548
276776AD2-060 GEN
Solar/Wind Harmer
1.003
958011AF2-095 GEN
Solar/Wind Harmer
13.543
970941AG2-585 GEN
Solar/Wind Harmer
5.173
246937BC-WTG2
Solar/Wind Harmer
0.378
276897AD1-100 C
Solar/Wind Harmer
23.396
944231AF1-091 GEN
Solar/Wind Harmer
21.57
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
274674JOLIET 9 ;6U
Adder
20.564
276893AG1-478 C
Solar/Wind Harmer
0.621
944541AF1-119 GEN
Solar/Wind Harmer
0.62
960971AF2-388 GEN
Solar/Wind Harmer
5.451
958481AF2-142 GEN
Solar/Wind Harmer
13.721
274695ROCKY RD ;2P
Adder
14.592
274693ROCKY RD ;1P
Adder
14.449
274697ROCKY RD ;3P
Adder
3.964
274696ROCKY RD ;4P
Adder
14.936
942221AE2-234 GEN
Solar/Wind Harmer
3.664
274683WAUKEGAN ;8U
Adder
27.547
274683WAUKEGAN ;8U
Adder
23.221
962691AG1-118 GEN
Solar/Wind Harmer
27.25
958491AF2-143 GEN
Solar/Wind Harmer
13.572
276901AD2-066 C O1
Solar/Wind Harmer
0
247607V1-011 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
17.823
971343AH1-151 GEN
Solar/Wind Harmer
17.823
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
3.202
972236AH1-702 GEN2
Adder
2.785
970623AG2-406 GEN
Solar/Wind Harmer
1.615
938861AE1-114 GEN
Solar/Wind Harmer
4.972
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0.001
274764LEE CO EC;5U
Adder
11.687
24721805FLATG3
50/50
4.711
24344105CKG2
50/50
11.483
274765LEE CO EC;6U
Adder
11.687
274762LEE CO EC;3U
Adder
11.659
274763LEE CO EC;4U
Adder
11.55
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.395
276645AC1-214 GEN1
Solar/Wind Harmer
0.339
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
2.774
270031AE2-169
Solar/Wind Harmer
4.65
270599AE1-208 GEN
Solar/Wind Harmer
7.749
960611AF2-352 GEN
Solar/Wind Harmer
2.8
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.946
970291AG2-192 GEN
Solar/Wind Harmer
1.081
970291AG2-192 GEN
Solar/Wind Harmer
0.499
971613AH1-306 GEN
Solar/Wind Harmer
3.949
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.604
970241AG2-163 GEN
Solar/Wind Harmer
4.646
970621AG2-405 GEN
Solar/Wind Harmer
1.449
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
247621Y3-024
Adder
0.272
276615X2-022 GEN
Solar/Wind Harmer
0.081
276838X2-022 GEN2
Solar/Wind Harmer
0.442
926881AC1-175 GEN
Solar/Wind Harmer
0
276916AD2-100_GEN
Solar/Wind Harmer
15.862
276911AD2-131_GEN
Solar/Wind Harmer
1.045
970883AG2-550 GEN
Solar/Wind Harmer
7.401
970885AG2-551 GEN
Solar/Wind Harmer
2.467
270383AD1-128 GEN
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
7.788
971587AH1-292 GEN
Solar/Wind Harmer
4.757
24728805RICHG1
Adder
3.35
24728905RICHG2
Adder
3.35
970329AG2-216 GEN
Solar/Wind Harmer
2.663
25326509SID D
Adder
1.142
270435AC2-044 GEN
Solar/Wind Harmer
1.188
274687WILL CNTY;4U
Adder
37.422
274687WILL CNTY;4U
Adder
37.422
274675JOLIET 29;7U
Adder
41.04
274675JOLIET 29;7U
Adder
39.575
274728ELWOOD EC;5P
Adder
21.94
274731ELWOOD EC;2P
Adder
21.939
274733ELWOOD EC;3P
Adder
21.939
274735ELWOOD EC;4P
Adder
21.939
970833AG2-524 GEN
Solar/Wind Harmer
10.228
970833AG2-524 GEN
Solar/Wind Harmer
6.819
971549AH1-272 GEN
Solar/Wind Harmer
19.166
274744AC1-111 GEN8
Adder
7.404
274746AC1-111 G10
Adder
7.404
958391AF2-133 GEN
Solar/Wind Harmer
0.001
970073AG2-061 GEN
Solar/Wind Harmer
3.016
959141AF2-205 GEN
Solar/Wind Harmer
0.001
971411AH1-196 GEN
Solar/Wind Harmer
13.448
971675AH1-338 GEN
Solar/Wind Harmer
3.496
276861AD2-134 GEN
Solar/Wind Harmer
0.16
276863AD2-134 GEN
Solar/Wind Harmer
0.16
971611AH1-305 GEN
Solar/Wind Harmer
5.334
270007AE1-245 C
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
17.823
274823ROCKFORD ;21
Adder
24.808
274856ECOGROVE ;U1
Solar/Wind Harmer
0.206
945581AF1-223 GEN
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
1.499
970169AG2-114 GEN
Solar/Wind Harmer
8.815
971681AH1-341 GEN
Solar/Wind Harmer
14.132
972267AH1-718 GEN
Adder
5.171
276741O09 GEN1
Solar/Wind Harmer
0.306
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.287
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
8.961
971609AH1-304 GEN
Solar/Wind Harmer
1.381
946321AF1-296 GEN
Solar/Wind Harmer
4.723
274854TWINGROVE;U2
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
1.58
963841AG1-237 GEN
Solar/Wind Harmer
3.532
964611AG1-324 GEN
Solar/Wind Harmer
3.142
276668AB2-070 GEN1
Solar/Wind Harmer
0.314
276848AB2-070 GEN3
Solar/Wind Harmer
0.312
276849AB2-070 GEN2
Solar/Wind Harmer
0.314
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
0.308
270543AE2-219 C
Solar/Wind Harmer
5.181
944221AF1-090 GEN
Solar/Wind Harmer
4.314
971029AG2-637 GEN
Solar/Wind Harmer
10.609
270356AE2-297 GEN
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
270143AC1-141 CT2_
50/50
3.456
24639705ELKHART HY
50/50
0.234
970521AG2-332 GEN
50/50
16.675
24307105BERRINSP G
50/50
0.03
962761AG1-125 GEN
Solar/Wind Harmer
109.537
970149AG2-104 GEN
Solar/Wind Harmer
59.152
970155AG2-107 GEN
Solar/Wind Harmer
69.947
965011AG1-365 GEN
Solar/Wind Harmer
10.32
957891AF2-083 GEN
Solar/Wind Harmer
16.606
945111AF1-176 GEN
Solar/Wind Harmer
17.763
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
5.166
270317AD1-130_GEN
Solar/Wind Harmer
-0.001
274773LINCOLN ;4U
Adder
11.612
274774LINCOLN ;5U
Adder
11.612
274723RIVER EC ;12
Adder
24.471
274751CRETE EC ;1U
Adder
11.245
274754CRETE EC ;4U
Adder
11.245
965421AG1-410 GEN
Solar/Wind Harmer
28.412
970373AG2-245 GEN
Solar/Wind Harmer
19.884
274812UNIV PK N;8U
Adder
6.795
274802UNIV PARK;5U
Adder
7.869
246936BC-WTG1
Solar/Wind Harmer
0.378
270489AE1-102 GEN1
Solar/Wind Harmer
1.219
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
41.04
270055AF2-134 C O1
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
20.564
274732ELWOOD EC;7P
Adder
21.94
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
965651AG1-433 GEN
Solar/Wind Harmer
2.726
274745AC1-111 GEN9
Adder
7.404
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.902
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.486
274861TOP CROP ;1U
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
23.522
958861AF2-177 GEN
Solar/Wind Harmer
3.956
274828WAUKEGAN ;BP
Adder
14.44
962781AG1-127 GEN
Solar/Wind Harmer
8.625
939401AE1-172 GEN
Solar/Wind Harmer
6.778
276805AD2-038 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
1.051
971997AH1-543 GEN
Solar/Wind Harmer
4.72
24722005FLATG5
50/50
4.711
24721905FLATG4
50/50
86.05
270475AD2-096_GEN
50/50
10.483
270142AC1-141 CT1_
50/50
3.456
24642205MAYFLWER
50/50
0.053
944961AF1-161 GEN
50/50
4.124
962601AG1-109 GEN
50/50
4.124
962771AG1-126 GEN
Solar/Wind Harmer
109.537
970153AG2-106 GEN
Solar/Wind Harmer
69.947
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
270043AE2-236 GEN
Solar/Wind Harmer
6.765
971347AH1-153 GEN
Solar/Wind Harmer
5.221
965021AG1-366 GEN
Solar/Wind Harmer
3.44
270391AF1-285 GEN3
Solar/Wind Harmer
0.682
270063AE2-323 C
Solar/Wind Harmer
0.001
270505AE1-170 C O1
Solar/Wind Harmer
10.472
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
11.201
957471AF2-041 GEN
Solar/Wind Harmer
26.735
959081AF2-199 GEN
Solar/Wind Harmer
8.912
971067AG2-660 GEN
Solar/Wind Harmer
2.971
274822ROCKFORD ;11
Adder
24.99
970819AG2-516 GEN
Solar/Wind Harmer
10.604
945371AF1-202 GEN
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
26.447
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
11.659
274766LEE CO EC;7U
Adder
11.522
276708O09 GEN2
Solar/Wind Harmer
0.306
276646AC1-214 GEN2
Solar/Wind Harmer
0.339
270024AE2-089 GEN
Solar/Wind Harmer
0.001
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
11.948
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
9.214
270032AE2-172
Solar/Wind Harmer
5.485
270005AE1-210 C O1
Solar/Wind Harmer
1.752
276903AD2-071 C
Solar/Wind Harmer
8.936
970825AG2-519 GEN
Solar/Wind Harmer
2.836
963741AG1-226 GEN
Solar/Wind Harmer
18.848
276621W2-048 GEN
Solar/Wind Harmer
0.393
965911AG1-460 GEN
Solar/Wind Harmer
1.522
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.54
24728605AND G2
Adder
3.831
970773AG2-487 GEN
Solar/Wind Harmer
1.192
23906502RICHG2&3
Adder
1.11
944531AF1-118 GEN
Solar/Wind Harmer
44.69
945111AF1-176 GEN
Solar/Wind Harmer
8.069
274772LINCOLN ;3U
Adder
11.612
274724RIVER EC ;11
Adder
24.187
274752CRETE EC ;2U
Adder
11.245
274753CRETE EC ;3U
Adder
11.245
274814UNIV PK N;0U
Adder
6.855
274807UNIV PK N;3U
Adder
6.84
274811UNIV PK N;7U
Adder
6.795
970707AG2-453 GEN
Solar/Wind Harmer
30.807
24695305TIMB G C
Solar/Wind Harmer
0.797
274803UNIV PARK;6U
Adder
7.869
274826FISK ;BP
Adder
14.772
274887GEN-1.85
Solar/Wind Harmer
0.244
276843GEN-1.7
Solar/Wind Harmer
0.304
276806AD2-047 C O1
Solar/Wind Harmer
5.33
972038AH1-567 GEN2
Adder
0.492
972259AH1-714 GEN
Adder
25.709
246938BC-WTG3
Solar/Wind Harmer
0.338
270491AE1-102 GEN2
Solar/Wind Harmer
1.219
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
39.574
274729ELWOOD EC;1P
Adder
21.939
274730ELWOOD EC;6P
Adder
21.94
274734ELWOOD EC;8P
Adder
21.94
274736ELWOOD EC;9P
Adder
21.94
943121AE2-341 GEN
Solar/Wind Harmer
15.518
943591AF1-030 GEN
Solar/Wind Harmer
10.32
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
1.234
274682WAUKEGAN ;7U
Adder
23.522
276868AE1-113 GEN
Solar/Wind Harmer
1.802
274879MINONK ;1U
Solar/Wind Harmer
0.376
946671AF1-331 GEN
Solar/Wind Harmer
0.957
274855GSG-6 ;RU
Solar/Wind Harmer
0.327
274850MENDOTA H;RU
Solar/Wind Harmer
0.104
959091AF2-200 GEN
Solar/Wind Harmer
17.823
970571AG2-364 GEN
Solar/Wind Harmer
17.631
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
11.659
274767LEE CO EC;8U
Adder
11.522
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
8.625
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.287
965091AG1-374 GEN
Solar/Wind Harmer
25.202
959611AF2-252 GEN
Solar/Wind Harmer
2.8
247642Z2-115 C
Solar/Wind Harmer
0.003
965931AG1-462 GEN
Solar/Wind Harmer
21.395
971087AG2-675 GEN
Solar/Wind Harmer
4.475
24386205FR-12G C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.915
270004AE1-209 GEN
Solar/Wind Harmer
1.752
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
12.121
970825AG2-519 GEN
Solar/Wind Harmer
6.019
971993AH1-541 GEN
Solar/Wind Harmer
3.688
946031AF1-268 GEN
Solar/Wind Harmer
7.583
957381AF2-032 GEN
Solar/Wind Harmer
1.73
942481AE2-261 GEN
Solar/Wind Harmer
22.758
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970193AG2-126 GEN
Solar/Wind Harmer
10.995
24728705AND G3
Adder
8.012
24728505AND G1
Adder
3.831
270541AE2-072 C
Solar/Wind Harmer
0
23906402RICHG1
Adder
1.111
23906502RICHG2&3
Adder
1.11
CBM West 2LTFEXP_CBM-W2->PJM
CBM
98.889
NYPJM->LTFIMP_NY
CLTF
3.074
LGEELTFEXP_LGEE->PJM
CLTF
4.556
WECLTFEXP_WEC->PJM
CLTF
4.845
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.158
AG2-052LTFEXP_AG2-052->PJM
LTF
0.305
AH1-155LTFEXP_AH1-155->PJM
LTF
0.457
LAGNLTFEXP_LAGN->PJM
CLTF
11.488
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.981
TVALTFEXP_TVA->PJM
CLTF
4.815
CBM West 1LTFEXP_CBM-W1->PJM
CBM
159.375
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.313
MECLTFEXP_MEC->PJM
CLTF
18.13
SIGELTFEXP_SIGE->PJM
CLTF
0.416

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o AEP_P7-1_#10944___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10944___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:106.37 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4405.9
MW Contribution:
50.08
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270102X2-052 ST
50/50
1.753
270100X2-052 CT1
50/50
1.619
270101X2-052 CT2
50/50
1.619
274770LINCOLN ;1U
50/50
7.111
274771LINCOLN ;2U
50/50
7.111
24643105BUCHANAN
50/50
0.014
247620Y3-023
50/50
0.527
970349AG2-230 GEN
Solar/Wind Harmer
17.18
965681AG1-436 GEN
Solar/Wind Harmer
13.66
965791AG1-447 GEN
Solar/Wind Harmer
6.989
961051AF2-396 GEN
Solar/Wind Harmer
17.026
961051AF2-396 GEN
Solar/Wind Harmer
7.919
274805UNIV PK N;1U
Adder
5.349
270144AC1-141 ST1_
50/50
2.309
24641605TWIN BRNCH
50/50
0.019
24344005CKG1
50/50
7.016
274775LINCOLN ;6U
50/50
7.111
274776LINCOLN ;7U
50/50
7.111
274777LINCOLN ;8U
50/50
7.111
24653605MOTTVILLE
50/50
0.004
270071AF1-092 GEN
Solar/Wind Harmer
16.698
971771AH1-392 GEN
Solar/Wind Harmer
9.838
960681AF2-359 GEN
Solar/Wind Harmer
4.129
270526AF1-158 GEN
Solar/Wind Harmer
4.941
970031AG2-029 GEN
Solar/Wind Harmer
26.92
24729505KEY G4
Adder
6.95
959331AF2-224 GEN
Solar/Wind Harmer
10.708
944161AF1-084 GEN
Solar/Wind Harmer
2.351
274827FISK ;RP
Adder
8.245
972037AH1-567 GEN1
Adder
0.194
960591AF2-350 GEN
Solar/Wind Harmer
10.623
972228AH1-698 GEN2
Adder
3.934
972227AH1-698 GEN1
Adder
2.77
274800UNIV PARK;3U
Adder
6.192
274801UNIV PARK;4U
Adder
6.192
274687WILL CNTY;4U
Adder
29.548
274687WILL CNTY;4U
Adder
29.548
274675JOLIET 29;7U
Adder
32.421
274675JOLIET 29;7U
Adder
31.263
274728ELWOOD EC;5P
Adder
17.342
274731ELWOOD EC;2P
Adder
17.342
274733ELWOOD EC;3P
Adder
17.342
274735ELWOOD EC;4P
Adder
17.342
276893AG1-478 C
Solar/Wind Harmer
0.58
970833AG2-524 GEN
Solar/Wind Harmer
9.206
970833AG2-524 GEN
Solar/Wind Harmer
4.282
274744AC1-111 GEN8
Adder
5.869
274746AC1-111 G10
Adder
5.869
970073AG2-061 GEN
Solar/Wind Harmer
2.402
958391AF2-133 GEN
Solar/Wind Harmer
9.368
959141AF2-205 GEN
Solar/Wind Harmer
6.219
971675AH1-338 GEN
Solar/Wind Harmer
18.487
971411AH1-196 GEN
Solar/Wind Harmer
15.404
276861AD2-134 GEN
Solar/Wind Harmer
1.833
276863AD2-134 GEN
Solar/Wind Harmer
1.833
958711AF2-162 GEN
Solar/Wind Harmer
1.038
274863CRW1-WTG
Solar/Wind Harmer
5.719
274864CRW2-WTG
Solar/Wind Harmer
5.719
971171AH1-044 GEN
Solar/Wind Harmer
20.451
274823ROCKFORD ;21
Adder
19.877
972267AH1-718 GEN
Adder
4.172
276889AE2-281 GEN
Solar/Wind Harmer
1.564
270142AC1-141 CT1_
50/50
2.615
24642205MAYFLWER
50/50
0.04
274772LINCOLN ;3U
50/50
7.111
962771AG1-126 GEN
Solar/Wind Harmer
81.095
970153AG2-106 GEN
Solar/Wind Harmer
35.361
971347AH1-153 GEN
Solar/Wind Harmer
5.727
270043AE2-236 GEN
Solar/Wind Harmer
6.212
247643Z2-116 C
Solar/Wind Harmer
0.076
24441505OLIV SLR
Solar/Wind Harmer
0.146
944531AF1-118 GEN
Solar/Wind Harmer
38.072
270063AE2-323 C
Solar/Wind Harmer
2.379
270505AE1-170 C O1
Solar/Wind Harmer
16.205
945111AF1-176 GEN
Solar/Wind Harmer
6.092
274724RIVER EC ;11
Adder
18.964
965021AG1-366 GEN
Solar/Wind Harmer
2.49
972231SS25-0005
Solar/Wind Harmer
10.145
972181SS23-001
Solar/Wind Harmer
6.341
274752CRETE EC ;2U
Adder
5.225
274753CRETE EC ;3U
Adder
5.225
276164X3-005 C
Solar/Wind Harmer
0.75
970707AG2-453 GEN
Solar/Wind Harmer
29.859
274814UNIV PK N;0U
Adder
5.384
274807UNIV PK N;3U
Adder
5.372
274811UNIV PK N;7U
Adder
5.337
972259AH1-714 GEN
Adder
20.284
274826FISK ;BP
Adder
11.634
274803UNIV PARK;6U
Adder
6.195
274887GEN-1.85
Solar/Wind Harmer
5.66
276772AC2-154 GEN
Solar/Wind Harmer
2.965
276843GEN-1.7
Solar/Wind Harmer
0.609
276806AD2-047 C O1
Solar/Wind Harmer
11.364
972038AH1-567 GEN2
Adder
0.388
939351AE1-166 GEN
Solar/Wind Harmer
6.283
274676JOLIET 29;8U
Adder
31.263
274729ELWOOD EC;1P
Adder
17.342
274730ELWOOD EC;6P
Adder
17.342
274734ELWOOD EC;8P
Adder
17.342
274736ELWOOD EC;9P
Adder
17.342
943121AE2-341 GEN
Solar/Wind Harmer
15.771
943591AF1-030 GEN
Solar/Wind Harmer
10.514
274862TOP CROP ;2U
Solar/Wind Harmer
5.264
274682WAUKEGAN ;7U
Adder
18.701
964401AG1-302 GEN
Solar/Wind Harmer
9.422
276868AE1-113 GEN
Solar/Wind Harmer
10.419
274879MINONK ;1U
Solar/Wind Harmer
6.946
24344105CKG2
50/50
8.783
270143AC1-141 CT2_
50/50
2.615
24639705ELKHART HY
50/50
0.177
970521AG2-332 GEN
50/50
12.574
274773LINCOLN ;4U
50/50
7.111
274774LINCOLN ;5U
50/50
7.111
962761AG1-125 GEN
Solar/Wind Harmer
81.095
970149AG2-104 GEN
Solar/Wind Harmer
50.076
970155AG2-107 GEN
Solar/Wind Harmer
35.361
270216AD2-079_GEN
Solar/Wind Harmer
0.66
972207SS24-0001
Solar/Wind Harmer
23.828
957891AF2-083 GEN
Solar/Wind Harmer
16.194
945111AF1-176 GEN
Solar/Wind Harmer
19.221
274723RIVER EC ;12
Adder
19.185
965011AG1-365 GEN
Solar/Wind Harmer
10.708
270449AD2-020 GEN
Solar/Wind Harmer
2.998
943021AE2-325 GEN
Solar/Wind Harmer
3.897
274751CRETE EC ;1U
Adder
5.225
274754CRETE EC ;4U
Adder
5.225
274812UNIV PK N;8U
Adder
5.337
274802UNIV PARK;5U
Adder
6.195
970373AG2-245 GEN
Solar/Wind Harmer
22.283
941551AE2-152 GEN
Solar/Wind Harmer
4.804
274676JOLIET 29;8U
Adder
32.421
274674JOLIET 9 ;6U
Adder
16.253
274732ELWOOD EC;7P
Adder
17.342
274871GR RIDGE ;2U
Solar/Wind Harmer
8.105
274847GR RIDGE ;BU
Solar/Wind Harmer
5.33
24441205WTRV SLR C
Solar/Wind Harmer
0.141
270055AF2-134 C O1
Solar/Wind Harmer
3.175
274745AC1-111 GEN9
Adder
5.869
276694AA1-018 GEN2
Solar/Wind Harmer
6.569
276691AA1-018 GEN1
Solar/Wind Harmer
0.785
274861TOP CROP ;1U
Solar/Wind Harmer
6.305
274682WAUKEGAN ;7U
Adder
18.701
274828WAUKEGAN ;BP
Adder
11.484
958381AF2-132 GEN
Solar/Wind Harmer
9.422
964861AG1-349 GEN
Solar/Wind Harmer
8.156
971917AH1-482 GEN
Solar/Wind Harmer
9.41
962781AG1-127 GEN
Solar/Wind Harmer
9.845
939401AE1-172 GEN
Solar/Wind Harmer
14.42
274872LEEDK;1U
Solar/Wind Harmer
8.485
276805AD2-038 GEN
Solar/Wind Harmer
5.297
276882AE2-255 GEN
Solar/Wind Harmer
3.473
971997AH1-543 GEN
Solar/Wind Harmer
16.202
965651AG1-433 GEN
Solar/Wind Harmer
5.607
940581AE2-045 GEN
Solar/Wind Harmer
10.433
971605AH1-302 GEN
Solar/Wind Harmer
8.92
957471AF2-041 GEN
Solar/Wind Harmer
30.677
959081AF2-199 GEN
Solar/Wind Harmer
10.226
971067AG2-660 GEN
Solar/Wind Harmer
2.378
274822ROCKFORD ;11
Adder
20.022
274761LEE CO EC;2U
Adder
9.383
274766LEE CO EC;7U
Adder
9.273
274808UNIV PK N;4U
Adder
5.314
274888KELLY CRK;1U
Solar/Wind Harmer
6.269
276776AD2-060 GEN
Solar/Wind Harmer
0.445
958011AF2-095 GEN
Solar/Wind Harmer
15.297
970941AG2-585 GEN
Solar/Wind Harmer
5.843
276897AD1-100 C
Solar/Wind Harmer
49.21
274674JOLIET 9 ;6U
Adder
16.253
276893AG1-478 C
Solar/Wind Harmer
0.462
270535AF1-215 GEN1
Solar/Wind Harmer
4.763
270536AF1-215 GEN2
Solar/Wind Harmer
4.763
270349AD2-093_GEN
Solar/Wind Harmer
3.782
270471AD2-092_GEN
Solar/Wind Harmer
3.782
274696ROCKY RD ;4P
Adder
11.873
274695ROCKY RD ;2P
Adder
11.599
274693ROCKY RD ;1P
Adder
11.485
274697ROCKY RD ;3P
Adder
3.151
958481AF2-142 GEN
Solar/Wind Harmer
15.617
274683WAUKEGAN ;8U
Adder
21.908
274683WAUKEGAN ;8U
Adder
18.468
962691AG1-118 GEN
Solar/Wind Harmer
31.108
960751AF2-366 GEN
Solar/Wind Harmer
2.97
958491AF2-143 GEN
Solar/Wind Harmer
15.495
276901AD2-066 C O1
Solar/Wind Harmer
3.62
944541AF1-119 GEN
Solar/Wind Harmer
4.295
960971AF2-388 GEN
Solar/Wind Harmer
11.213
971341AH1-150 GEN
Solar/Wind Harmer
20.451
971343AH1-151 GEN
Solar/Wind Harmer
20.451
972235AH1-702 GEN1
Adder
2.567
972236AH1-702 GEN2
Adder
2.232
274764LEE CO EC;5U
Adder
9.405
274765LEE CO EC;6U
Adder
9.405
274762LEE CO EC;3U
Adder
9.383
274763LEE CO EC;4U
Adder
9.295
247621Y3-024
Adder
0.211
270054AF2-122 C O1
Solar/Wind Helper
1.259
276872AE1-163_GEN1
Solar/Wind Harmer
5.473
276876AE1-163_GEN2
Solar/Wind Harmer
5.473
276799AD1-013 GEN
Solar/Wind Harmer
2.27
946671AF1-331 GEN
Solar/Wind Harmer
0.43
274855GSG-6 ;RU
Solar/Wind Harmer
3.791
274850MENDOTA H;RU
Solar/Wind Harmer
2.636
276602WESTBROOK C
Solar/Wind Harmer
2.183
959091AF2-200 GEN
Solar/Wind Harmer
20.451
274760LEE CO EC;1U
Adder
9.383
274767LEE CO EC;8U
Adder
9.273
24721905FLATG4
Adder
19.591
CPLELTFEXP_CPLE->PJM
CLTF
1.822
CBM West 2LTFEXP_CBM-W2->PJM
CBM
95.28
NYPJM->LTFIMP_NY
CLTF
2.91
LGEELTFEXP_LGEE->PJM
CLTF
4.438
WECLTFEXP_WEC->PJM
CLTF
3.887
AG2-052LTFEXP_AG2-052->PJM
LTF
0.241
AH1-155LTFEXP_AH1-155->PJM
LTF
0.361
LAGNLTFEXP_LAGN->PJM
CLTF
12.46
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.11
TVALTFEXP_TVA->PJM
CLTF
5.754
CBM West 1LTFEXP_CBM-W1->PJM
CBM
124.135
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.087
MECLTFEXP_MEC->PJM
CLTF
15.27
SIGELTFEXP_SIGE->PJM
CLTF
0.384

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-027A_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-027A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:106.18 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4397.83
MW Contribution:
50.44
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270102X2-052 ST
50/50
1.83
270100X2-052 CT1
50/50
1.691
270101X2-052 CT2
50/50
1.691
247620Y3-023
50/50
0.556
24643105BUCHANAN
50/50
0.014
274770LINCOLN ;1U
50/50
7.357
274771LINCOLN ;2U
50/50
7.357
970349AG2-230 GEN
Solar/Wind Harmer
17.91
965681AG1-436 GEN
Solar/Wind Harmer
14.253
270144AC1-141 ST1_
50/50
2.433
24641605TWIN BRNCH
50/50
0.02
24344005CKG1
50/50
7.405
24653605MOTTVILLE
50/50
0.004
274775LINCOLN ;6U
50/50
7.357
274776LINCOLN ;7U
50/50
7.357
274777LINCOLN ;8U
50/50
7.357
270071AF1-092 GEN
Solar/Wind Harmer
17.36
971771AH1-392 GEN
Solar/Wind Harmer
10.331
270526AF1-158 GEN
Solar/Wind Harmer
5.178
960681AF2-359 GEN
Solar/Wind Harmer
4.309
970031AG2-029 GEN
Solar/Wind Harmer
28.41
959331AF2-224 GEN
Solar/Wind Harmer
11.337
944161AF1-084 GEN
Solar/Wind Harmer
2.492
965791AG1-447 GEN
Solar/Wind Harmer
7.292
961051AF2-396 GEN
Solar/Wind Harmer
18.009
961051AF2-396 GEN
Solar/Wind Harmer
8.376
270349AD2-093_GEN
Solar/Wind Harmer
4.039
270471AD2-092_GEN
Solar/Wind Harmer
4.039
274805UNIV PK N;1U
Adder
5.542
274808UNIV PK N;4U
Adder
5.506
274888KELLY CRK;1U
Solar/Wind Harmer
6.487
276776AD2-060 GEN
Solar/Wind Harmer
0.46
958011AF2-095 GEN
Solar/Wind Harmer
15.829
970941AG2-585 GEN
Solar/Wind Harmer
6.046
276897AD1-100 C
Solar/Wind Harmer
50.878
274674JOLIET 9 ;6U
Adder
16.804
276893AG1-478 C
Solar/Wind Harmer
0.478
270535AF1-215 GEN1
Solar/Wind Harmer
4.943
270536AF1-215 GEN2
Solar/Wind Harmer
4.943
274695ROCKY RD ;2P
Adder
11.976
274693ROCKY RD ;1P
Adder
11.858
274697ROCKY RD ;3P
Adder
3.253
274696ROCKY RD ;4P
Adder
12.259
958481AF2-142 GEN
Solar/Wind Harmer
16.133
274683WAUKEGAN ;8U
Adder
22.619
274683WAUKEGAN ;8U
Adder
19.067
962691AG1-118 GEN
Solar/Wind Harmer
32.105
960751AF2-366 GEN
Solar/Wind Harmer
3.065
958491AF2-143 GEN
Solar/Wind Harmer
15.995
276901AD2-066 C O1
Solar/Wind Harmer
3.736
944541AF1-119 GEN
Solar/Wind Harmer
4.432
960971AF2-388 GEN
Solar/Wind Harmer
11.571
972235AH1-702 GEN1
Adder
2.646
972236AH1-702 GEN2
Adder
2.301
274764LEE CO EC;5U
Adder
9.686
274765LEE CO EC;6U
Adder
9.686
274762LEE CO EC;3U
Adder
9.664
274763LEE CO EC;4U
Adder
9.573
247621Y3-024
Adder
0.218
971341AH1-150 GEN
Solar/Wind Harmer
18.283
971343AH1-151 GEN
Solar/Wind Harmer
18.283
24729505KEY G4
Adder
7.189
972037AH1-567 GEN1
Adder
0.201
274827FISK ;RP
Adder
8.534
960591AF2-350 GEN
Solar/Wind Harmer
10.992
274800UNIV PARK;3U
Adder
6.408
274801UNIV PARK;4U
Adder
6.408
972228AH1-698 GEN2
Adder
4.07
972227AH1-698 GEN1
Adder
2.866
274687WILL CNTY;4U
Adder
30.56
274687WILL CNTY;4U
Adder
30.56
274675JOLIET 29;7U
Adder
33.526
274675JOLIET 29;7U
Adder
32.329
274728ELWOOD EC;5P
Adder
17.93
274731ELWOOD EC;2P
Adder
17.93
274733ELWOOD EC;3P
Adder
17.93
274735ELWOOD EC;4P
Adder
17.93
276893AG1-478 C
Solar/Wind Harmer
0.6
970833AG2-524 GEN
Solar/Wind Harmer
9.514
970833AG2-524 GEN
Solar/Wind Harmer
4.425
274744AC1-111 GEN8
Adder
6.063
274746AC1-111 G10
Adder
6.063
958391AF2-133 GEN
Solar/Wind Harmer
9.699
970073AG2-061 GEN
Solar/Wind Harmer
2.48
971549AH1-272 GEN
Solar/Wind Harmer
19.702
959141AF2-205 GEN
Solar/Wind Harmer
6.434
965041AG1-368 GEN
Solar/Wind Harmer
10.597
971675AH1-338 GEN
Solar/Wind Harmer
19.065
971411AH1-196 GEN
Solar/Wind Harmer
15.888
276861AD2-134 GEN
Solar/Wind Harmer
1.891
276863AD2-134 GEN
Solar/Wind Harmer
1.891
958711AF2-162 GEN
Solar/Wind Harmer
1.071
274863CRW1-WTG
Solar/Wind Harmer
5.896
274864CRW2-WTG
Solar/Wind Harmer
5.896
274823ROCKFORD ;21
Adder
20.49
972267AH1-718 GEN
Adder
4.295
971171AH1-044 GEN
Solar/Wind Harmer
18.283
24344105CKG2
50/50
9.143
270143AC1-141 CT2_
50/50
2.756
24639705ELKHART HY
50/50
0.186
970521AG2-332 GEN
50/50
13.256
24307105BERRINSP G
50/50
0.024
274773LINCOLN ;4U
50/50
7.357
274774LINCOLN ;5U
50/50
7.357
962761AG1-125 GEN
Solar/Wind Harmer
81.685
970149AG2-104 GEN
Solar/Wind Harmer
50.44
970155AG2-107 GEN
Solar/Wind Harmer
35.618
270216AD2-079_GEN
Solar/Wind Harmer
0.695
957891AF2-083 GEN
Solar/Wind Harmer
17.095
945111AF1-176 GEN
Solar/Wind Harmer
20.303
965011AG1-365 GEN
Solar/Wind Harmer
11.337
270449AD2-020 GEN
Solar/Wind Harmer
3.174
943021AE2-325 GEN
Solar/Wind Harmer
4.125
972207SS24-0001
Solar/Wind Harmer
24.651
24441205WTRV SLR C
Solar/Wind Harmer
0.151
274723RIVER EC ;12
Adder
19.886
274751CRETE EC ;1U
Adder
5.419
274754CRETE EC ;4U
Adder
5.419
274812UNIV PK N;8U
Adder
5.53
970373AG2-245 GEN
Solar/Wind Harmer
23.162
274802UNIV PARK;5U
Adder
6.413
941551AE2-152 GEN
Solar/Wind Harmer
4.967
274676JOLIET 29;8U
Adder
33.526
274674JOLIET 9 ;6U
Adder
16.804
274732ELWOOD EC;7P
Adder
17.93
270055AF2-134 C O1
Solar/Wind Harmer
3.295
274871GR RIDGE ;2U
Solar/Wind Harmer
8.376
274847GR RIDGE ;BU
Solar/Wind Harmer
5.508
274745AC1-111 GEN9
Adder
6.063
958381AF2-132 GEN
Solar/Wind Harmer
9.763
276694AA1-018 GEN2
Solar/Wind Harmer
6.786
276691AA1-018 GEN1
Solar/Wind Harmer
0.811
274861TOP CROP ;1U
Solar/Wind Harmer
6.513
964861AG1-349 GEN
Solar/Wind Harmer
8.45
971917AH1-482 GEN
Solar/Wind Harmer
9.749
274682WAUKEGAN ;7U
Adder
19.309
274828WAUKEGAN ;BP
Adder
11.857
962781AG1-127 GEN
Solar/Wind Harmer
10.159
939401AE1-172 GEN
Solar/Wind Harmer
14.878
274872LEEDK;1U
Solar/Wind Harmer
8.755
276805AD2-038 GEN
Solar/Wind Harmer
5.468
276882AE2-255 GEN
Solar/Wind Harmer
3.584
971997AH1-543 GEN
Solar/Wind Harmer
16.713
965651AG1-433 GEN
Solar/Wind Harmer
5.786
940581AE2-045 GEN
Solar/Wind Harmer
10.785
971605AH1-302 GEN
Solar/Wind Harmer
9.222
274822ROCKFORD ;11
Adder
20.64
274761LEE CO EC;2U
Adder
9.664
274766LEE CO EC;7U
Adder
9.55
957471AF2-041 GEN
Solar/Wind Harmer
27.425
959081AF2-199 GEN
Solar/Wind Harmer
9.142
971067AG2-660 GEN
Solar/Wind Harmer
2.126
270142AC1-141 CT1_
50/50
2.756
24642205MAYFLWER
50/50
0.042
944961AF1-161 GEN
50/50
3.292
962601AG1-109 GEN
50/50
3.292
274772LINCOLN ;3U
50/50
7.357
962771AG1-126 GEN
Solar/Wind Harmer
81.685
970153AG2-106 GEN
Solar/Wind Harmer
35.618
971347AH1-153 GEN
Solar/Wind Harmer
5.97
270043AE2-236 GEN
Solar/Wind Harmer
6.503
247643Z2-116 C
Solar/Wind Harmer
0.08
270063AE2-323 C
Solar/Wind Harmer
2.51
270505AE1-170 C O1
Solar/Wind Harmer
17.111
24441505OLIV SLR
Solar/Wind Harmer
0.152
945111AF1-176 GEN
Solar/Wind Harmer
6.435
965021AG1-366 GEN
Solar/Wind Harmer
2.637
944531AF1-118 GEN
Solar/Wind Harmer
39.408
274724RIVER EC ;11
Adder
19.656
972231SS25-0005
Solar/Wind Harmer
10.523
972181SS23-001
Solar/Wind Harmer
6.577
274752CRETE EC ;2U
Adder
5.419
274753CRETE EC ;3U
Adder
5.419
276164X3-005 C
Solar/Wind Harmer
0.777
274814UNIV PK N;0U
Adder
5.578
274807UNIV PK N;3U
Adder
5.566
274811UNIV PK N;7U
Adder
5.53
970707AG2-453 GEN
Solar/Wind Harmer
30.87
274803UNIV PARK;6U
Adder
6.413
274826FISK ;BP
Adder
12.041
972259AH1-714 GEN
Adder
20.975
274887GEN-1.85
Solar/Wind Harmer
5.856
276772AC2-154 GEN
Solar/Wind Harmer
3.068
276843GEN-1.7
Solar/Wind Harmer
0.63
276806AD2-047 C O1
Solar/Wind Harmer
11.759
972038AH1-567 GEN2
Adder
0.401
939351AE1-166 GEN
Solar/Wind Harmer
6.495
274676JOLIET 29;8U
Adder
32.328
274730ELWOOD EC;6P
Adder
17.93
274734ELWOOD EC;8P
Adder
17.93
274736ELWOOD EC;9P
Adder
17.93
274729ELWOOD EC;1P
Adder
17.93
943121AE2-341 GEN
Solar/Wind Harmer
16.292
943591AF1-030 GEN
Solar/Wind Harmer
10.861
964401AG1-302 GEN
Solar/Wind Harmer
9.763
274862TOP CROP ;2U
Solar/Wind Harmer
5.438
274682WAUKEGAN ;7U
Adder
19.309
276868AE1-113 GEN
Solar/Wind Harmer
10.751
274879MINONK ;1U
Solar/Wind Harmer
7.168
276799AD1-013 GEN
Solar/Wind Harmer
2.341
946671AF1-331 GEN
Solar/Wind Harmer
0.444
274855GSG-6 ;RU
Solar/Wind Harmer
3.91
274850MENDOTA H;RU
Solar/Wind Harmer
2.718
276602WESTBROOK C
Solar/Wind Harmer
2.251
274760LEE CO EC;1U
Adder
9.664
274767LEE CO EC;8U
Adder
9.55
24721905FLATG4
Adder
18.411
959091AF2-200 GEN
Solar/Wind Harmer
18.283
CPLELTFEXP_CPLE->PJM
CLTF
1.45
CBM West 2LTFEXP_CBM-W2->PJM
CBM
94.882
NYPJM->LTFIMP_NY
CLTF
2.96
LGEELTFEXP_LGEE->PJM
CLTF
4.361
WECLTFEXP_WEC->PJM
CLTF
4.006
AG2-052LTFEXP_AG2-052->PJM
LTF
0.249
AH1-155LTFEXP_AH1-155->PJM
LTF
0.374
LAGNLTFEXP_LAGN->PJM
CLTF
12.208
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.04
TVALTFEXP_TVA->PJM
CLTF
5.56
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.803
CBM South 1LTFEXP_CBM-S1->PJM
CBM
21.413
MECLTFEXP_MEC->PJM
CLTF
15.587
SIGELTFEXP_SIGE->PJM
CLTF
0.383

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o AP_P2-2_WP-500-DRT14_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-500-DRT14_SRT-SL
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:102.92 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4263.07
MW Contribution:
49.91
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270144AC1-141 ST1_
50/50
2.278
24641605TWIN BRNCH
50/50
0.019
24344005CKG1
50/50
6.924
24653605MOTTVILLE
50/50
0.004
274775LINCOLN ;6U
50/50
6.961
270142AC1-141 CT1_
50/50
2.58
270475AD2-096_GEN
50/50
6.246
24642205MAYFLWER
50/50
0.039
274772LINCOLN ;3U
50/50
6.961
962771AG1-126 GEN
Solar/Wind Harmer
80.818
970153AG2-106 GEN
Solar/Wind Harmer
35.24
971347AH1-153 GEN
Solar/Wind Harmer
5.64
270043AE2-236 GEN
Solar/Wind Harmer
6.139
247643Z2-116 C
Solar/Wind Harmer
0.075
24441505OLIV SLR
Solar/Wind Harmer
0.143
270063AE2-323 C
Solar/Wind Harmer
2.352
944531AF1-118 GEN
Solar/Wind Harmer
37.376
270505AE1-170 C O1
Solar/Wind Harmer
15.995
965021AG1-366 GEN
Solar/Wind Harmer
2.475
945111AF1-176 GEN
Solar/Wind Harmer
6.013
274724RIVER EC ;11
Adder
18.57
972231SS25-0005
Solar/Wind Harmer
9.936
972181SS23-001
Solar/Wind Harmer
6.21
274752CRETE EC ;2U
Adder
5.117
274753CRETE EC ;3U
Adder
5.117
276164X3-005 C
Solar/Wind Harmer
0.734
274814UNIV PK N;0U
Adder
5.27
274807UNIV PK N;3U
Adder
5.258
274811UNIV PK N;7U
Adder
5.224
970707AG2-453 GEN
Solar/Wind Harmer
29.202
972259AH1-714 GEN
Adder
19.836
274803UNIV PARK;6U
Adder
6.061
274826FISK ;BP
Adder
11.381
274887GEN-1.85
Solar/Wind Harmer
5.536
276772AC2-154 GEN
Solar/Wind Harmer
2.9
276843GEN-1.7
Solar/Wind Harmer
0.596
276806AD2-047 C O1
Solar/Wind Harmer
11.116
972038AH1-567 GEN2
Adder
0.379
939351AE1-166 GEN
Solar/Wind Harmer
6.142
274676JOLIET 29;8U
Adder
30.563
274729ELWOOD EC;1P
Adder
16.951
274730ELWOOD EC;6P
Adder
16.951
270102X2-052 ST
50/50
1.723
270100X2-052 CT1
50/50
1.592
270101X2-052 CT2
50/50
1.592
247620Y3-023
50/50
0.521
24643105BUCHANAN
50/50
0.014
274770LINCOLN ;1U
50/50
6.961
274771LINCOLN ;2U
50/50
6.961
970349AG2-230 GEN
Solar/Wind Harmer
16.919
270349AD2-093_GEN
Solar/Wind Harmer
3.899
270471AD2-092_GEN
Solar/Wind Harmer
3.899
965681AG1-436 GEN
Solar/Wind Harmer
13.424
965791AG1-447 GEN
Solar/Wind Harmer
6.868
961051AF2-396 GEN
Solar/Wind Harmer
16.811
961051AF2-396 GEN
Solar/Wind Harmer
7.819
274805UNIV PK N;1U
Adder
5.235
274808UNIV PK N;4U
Adder
5.201
274888KELLY CRK;1U
Solar/Wind Harmer
6.132
276776AD2-060 GEN
Solar/Wind Harmer
0.435
958011AF2-095 GEN
Solar/Wind Harmer
14.963
970941AG2-585 GEN
Solar/Wind Harmer
5.715
276897AD1-100 C
Solar/Wind Harmer
48.109
274674JOLIET 9 ;6U
Adder
15.887
276893AG1-478 C
Solar/Wind Harmer
0.452
270535AF1-215 GEN1
Solar/Wind Harmer
4.659
270536AF1-215 GEN2
Solar/Wind Harmer
4.659
274696ROCKY RD ;4P
Adder
11.592
274695ROCKY RD ;2P
Adder
11.325
274693ROCKY RD ;1P
Adder
11.213
274697ROCKY RD ;3P
Adder
3.076
958481AF2-142 GEN
Solar/Wind Harmer
15.249
274683WAUKEGAN ;8U
Adder
21.387
274683WAUKEGAN ;8U
Adder
18.028
962691AG1-118 GEN
Solar/Wind Harmer
30.359
960751AF2-366 GEN
Solar/Wind Harmer
2.898
958491AF2-143 GEN
Solar/Wind Harmer
15.119
276901AD2-066 C O1
Solar/Wind Harmer
3.532
944541AF1-119 GEN
Solar/Wind Harmer
4.198
960971AF2-388 GEN
Solar/Wind Harmer
10.959
971341AH1-150 GEN
Solar/Wind Harmer
19.937
971343AH1-151 GEN
Solar/Wind Harmer
19.937
972235AH1-702 GEN1
Adder
2.502
972236AH1-702 GEN2
Adder
2.176
274764LEE CO EC;5U
Adder
9.158
274765LEE CO EC;6U
Adder
9.158
274762LEE CO EC;3U
Adder
9.137
274763LEE CO EC;4U
Adder
9.051
276872AE1-163_GEN1
Solar/Wind Harmer
1.054
276876AE1-163_GEN2
Solar/Wind Harmer
1.054
274776LINCOLN ;7U
50/50
6.961
274777LINCOLN ;8U
50/50
6.961
270071AF1-092 GEN
Solar/Wind Harmer
16.436
971771AH1-392 GEN
Solar/Wind Harmer
9.695
960681AF2-359 GEN
Solar/Wind Harmer
4.058
270526AF1-158 GEN
Solar/Wind Harmer
4.864
970031AG2-029 GEN
Solar/Wind Harmer
26.621
959331AF2-224 GEN
Solar/Wind Harmer
10.64
944161AF1-084 GEN
Solar/Wind Harmer
2.322
24729505KEY G4
Adder
6.815
972037AH1-567 GEN1
Adder
0.19
274827FISK ;RP
Adder
8.066
960591AF2-350 GEN
Solar/Wind Harmer
10.391
274800UNIV PARK;3U
Adder
6.057
274801UNIV PARK;4U
Adder
6.057
972228AH1-698 GEN2
Adder
3.847
972227AH1-698 GEN1
Adder
2.709
274687WILL CNTY;4U
Adder
28.89
274687WILL CNTY;4U
Adder
28.89
274675JOLIET 29;7U
Adder
31.695
274675JOLIET 29;7U
Adder
30.563
274728ELWOOD EC;5P
Adder
16.951
274731ELWOOD EC;2P
Adder
16.951
274733ELWOOD EC;3P
Adder
16.951
274735ELWOOD EC;4P
Adder
16.951
276893AG1-478 C
Solar/Wind Harmer
0.567
970833AG2-524 GEN
Solar/Wind Harmer
8.997
970833AG2-524 GEN
Solar/Wind Harmer
4.184
274744AC1-111 GEN8
Adder
5.734
274746AC1-111 G10
Adder
5.734
958391AF2-133 GEN
Solar/Wind Harmer
9.145
970073AG2-061 GEN
Solar/Wind Harmer
2.344
959141AF2-205 GEN
Solar/Wind Harmer
6.067
958711AF2-162 GEN
Solar/Wind Harmer
1.014
971675AH1-338 GEN
Solar/Wind Harmer
18.028
971411AH1-196 GEN
Solar/Wind Harmer
15.022
276861AD2-134 GEN
Solar/Wind Harmer
1.788
276863AD2-134 GEN
Solar/Wind Harmer
1.788
274863CRW1-WTG
Solar/Wind Harmer
5.574
274864CRW2-WTG
Solar/Wind Harmer
5.574
971171AH1-044 GEN
Solar/Wind Harmer
19.937
274823ROCKFORD ;21
Adder
19.373
972267AH1-718 GEN
Adder
4.06
276889AE2-281 GEN
Solar/Wind Harmer
0.301
274734ELWOOD EC;8P
Adder
16.951
274736ELWOOD EC;9P
Adder
16.951
943121AE2-341 GEN
Solar/Wind Harmer
15.408
943591AF1-030 GEN
Solar/Wind Harmer
10.272
274862TOP CROP ;2U
Solar/Wind Harmer
5.14
274682WAUKEGAN ;7U
Adder
18.257
964401AG1-302 GEN
Solar/Wind Harmer
9.204
276868AE1-113 GEN
Solar/Wind Harmer
10.164
274879MINONK ;1U
Solar/Wind Harmer
6.776
276799AD1-013 GEN
Solar/Wind Harmer
2.213
946671AF1-331 GEN
Solar/Wind Harmer
0.419
274855GSG-6 ;RU
Solar/Wind Harmer
3.697
274850MENDOTA H;RU
Solar/Wind Harmer
2.57
276602WESTBROOK C
Solar/Wind Harmer
2.128
270284AF1-227 GEN1
Solar/Wind Harmer
5.652
270287AF1-227 GEN3
Solar/Wind Harmer
2.091
959091AF2-200 GEN
Solar/Wind Harmer
19.937
274760LEE CO EC;1U
Adder
9.137
274767LEE CO EC;8U
Adder
9.029
24721905FLATG4
Adder
18.074
24344105CKG2
50/50
8.654
270143AC1-141 CT2_
50/50
2.58
24639705ELKHART HY
50/50
0.174
970521AG2-332 GEN
50/50
12.412
274773LINCOLN ;4U
50/50
6.961
274774LINCOLN ;5U
50/50
6.961
962761AG1-125 GEN
Solar/Wind Harmer
80.818
970149AG2-104 GEN
Solar/Wind Harmer
49.905
970155AG2-107 GEN
Solar/Wind Harmer
35.24
270216AD2-079_GEN
Solar/Wind Harmer
0.651
957891AF2-083 GEN
Solar/Wind Harmer
15.983
965011AG1-365 GEN
Solar/Wind Harmer
10.64
945111AF1-176 GEN
Solar/Wind Harmer
18.974
972207SS24-0001
Solar/Wind Harmer
23.325
270449AD2-020 GEN
Solar/Wind Harmer
2.961
943021AE2-325 GEN
Solar/Wind Harmer
3.848
274723RIVER EC ;12
Adder
18.787
274751CRETE EC ;1U
Adder
5.117
274754CRETE EC ;4U
Adder
5.117
274812UNIV PK N;8U
Adder
5.224
274802UNIV PARK;5U
Adder
6.061
970373AG2-245 GEN
Solar/Wind Harmer
21.824
24441205WTRV SLR C
Solar/Wind Harmer
0.14
941551AE2-152 GEN
Solar/Wind Harmer
4.697
274676JOLIET 29;8U
Adder
31.695
274674JOLIET 9 ;6U
Adder
15.887
274732ELWOOD EC;7P
Adder
16.951
274871GR RIDGE ;2U
Solar/Wind Harmer
7.921
274847GR RIDGE ;BU
Solar/Wind Harmer
5.208
270055AF2-134 C O1
Solar/Wind Harmer
3.106
274745AC1-111 GEN9
Adder
5.734
276694AA1-018 GEN2
Solar/Wind Harmer
6.415
276691AA1-018 GEN1
Solar/Wind Harmer
0.767
274861TOP CROP ;1U
Solar/Wind Harmer
6.156
274682WAUKEGAN ;7U
Adder
18.257
274828WAUKEGAN ;BP
Adder
11.211
958381AF2-132 GEN
Solar/Wind Harmer
9.204
964861AG1-349 GEN
Solar/Wind Harmer
7.967
971917AH1-482 GEN
Solar/Wind Harmer
9.191
962781AG1-127 GEN
Solar/Wind Harmer
9.606
939401AE1-172 GEN
Solar/Wind Harmer
14.067
274872LEEDK;1U
Solar/Wind Harmer
8.279
276805AD2-038 GEN
Solar/Wind Harmer
5.169
276882AE2-255 GEN
Solar/Wind Harmer
3.388
971997AH1-543 GEN
Solar/Wind Harmer
15.801
965651AG1-433 GEN
Solar/Wind Harmer
5.48
270286AF1-227 GEN2
Solar/Wind Harmer
2.091
940581AE2-045 GEN
Solar/Wind Harmer
10.172
971605AH1-302 GEN
Solar/Wind Harmer
8.697
957471AF2-041 GEN
Solar/Wind Harmer
29.905
959081AF2-199 GEN
Solar/Wind Harmer
9.968
971067AG2-660 GEN
Solar/Wind Harmer
2.318
274822ROCKFORD ;11
Adder
19.515
274761LEE CO EC;2U
Adder
9.137
274766LEE CO EC;7U
Adder
9.029
CPLELTFEXP_CPLE->PJM
CLTF
1.379
CBM West 2LTFEXP_CBM-W2->PJM
CBM
89.572
NYPJM->LTFIMP_NY
CLTF
2.723
LGEELTFEXP_LGEE->PJM
CLTF
4.091
WECLTFEXP_WEC->PJM
CLTF
3.788
AG2-052LTFEXP_AG2-052->PJM
LTF
0.235
AH1-155LTFEXP_AH1-155->PJM
LTF
0.353
LAGNLTFEXP_LAGN->PJM
CLTF
11.534
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.685
TVALTFEXP_TVA->PJM
CLTF
5.252
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.463
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.201
MECLTFEXP_MEC->PJM
CLTF
14.731
SIGELTFEXP_SIGE->PJM
CLTF
0.36

Details for 05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#711_05MARYSV 765_A1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
Contingency Name:
AEP_P4_#711_05MARYSV 765_A1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.43 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3327.22
MW Contribution:
48.32
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721805FLATG3
50/50
1.063
962761AG1-125 GEN
Solar/Wind Harmer
78.258
970149AG2-104 GEN
Solar/Wind Harmer
48.324
970155AG2-107 GEN
Solar/Wind Harmer
34.124
972207SS24-0001
Solar/Wind Harmer
12.083
274773LINCOLN ;4U
Adder
3.399
274774LINCOLN ;5U
Adder
3.399
274723RIVER EC ;12
Adder
9.496
941551AE2-152 GEN
Solar/Wind Harmer
2.391
274802UNIV PARK;5U
Adder
3.071
274812UNIV PK N;8U
Adder
2.636
274751CRETE EC ;1U
Adder
2.57
274754CRETE EC ;4U
Adder
2.57
274676JOLIET 29;8U
Adder
16.11
274871GR RIDGE ;2U
Solar/Wind Harmer
4.032
274847GR RIDGE ;BU
Solar/Wind Harmer
2.651
274674JOLIET 9 ;6U
Adder
8.073
274732ELWOOD EC;7P
Adder
8.606
274745AC1-111 GEN9
Adder
2.922
274682WAUKEGAN ;7U
Adder
9.263
274828WAUKEGAN ;BP
Adder
5.686
276694AA1-018 GEN2
Solar/Wind Harmer
3.235
276691AA1-018 GEN1
Solar/Wind Harmer
0.387
962781AG1-127 GEN
Solar/Wind Harmer
4.873
274861TOP CROP ;1U
Solar/Wind Harmer
3.103
274872LEEDK;1U
Solar/Wind Harmer
4.197
939401AE1-172 GEN
Solar/Wind Harmer
7.067
276805AD2-038 GEN
Solar/Wind Harmer
2.599
970373AG2-245 GEN
Solar/Wind Harmer
10.616
971997AH1-543 GEN
Solar/Wind Harmer
7.954
276882AE2-255 GEN
Solar/Wind Harmer
1.704
957471AF2-041 GEN
Solar/Wind Harmer
15.098
959081AF2-199 GEN
Solar/Wind Harmer
5.033
971067AG2-660 GEN
Solar/Wind Harmer
1.17
274822ROCKFORD ;11
Adder
9.846
970819AG2-516 GEN
Solar/Wind Harmer
5.988
270055AF2-134 C O1
Solar/Wind Harmer
1.501
274858EASY ROAD;U2
Solar/Wind Harmer
2.364
274761LEE CO EC;2U
Adder
4.59
274766LEE CO EC;7U
Adder
4.536
970569AG2-363 GEN
Solar/Wind Harmer
14.794
270216AD2-079_GEN
Solar/Wind Harmer
0.298
957891AF2-083 GEN
Solar/Wind Harmer
7.311
958381AF2-132 GEN
Solar/Wind Harmer
4.417
276708O09 GEN2
Solar/Wind Harmer
1.739
964861AG1-349 GEN
Solar/Wind Harmer
3.821
971917AH1-482 GEN
Solar/Wind Harmer
4.408
276646AC1-214 GEN2
Solar/Wind Harmer
0.646
945111AF1-176 GEN
Solar/Wind Harmer
8.554
274848CAMPGROVE;RU
Solar/Wind Harmer
3.088
24639705ELKHART HY
Adder
0.072
270286AF1-227 GEN2
Solar/Wind Helper
2.335
270391AF1-285 GEN3
Solar/Wind Helper
1.033
270578AF1-285 GEN2
Solar/Wind Helper
1.033
270317AD1-130_GEN
Solar/Wind Helper
5.921
270485AE1-090_GEN
Solar/Wind Helper
0.466
270520AE2-214 GEN
Solar/Wind Helper
3.134
253333AC1-068 GEN
Solar/Wind Helper
0.859
960841AF2-375 GEN
Solar/Wind Helper
1.147
270273AD2-016 GEN
Solar/Wind Helper
1.662
270297AD1-101 GEN
Solar/Wind Helper
0.209
958961AF2-187 GEN
Solar/Wind Helper
1.121
241840AF1-064_GEN
Solar/Wind Helper
0.476
241807AE2-176_GEN
Solar/Wind Helper
0.698
24721705FLATG2
50/50
15.792
970349AG2-230 GEN
Solar/Wind Harmer
8.806
274770LINCOLN ;1U
Adder
3.399
274771LINCOLN ;2U
Adder
3.399
965681AG1-436 GEN
Solar/Wind Harmer
6.664
965791AG1-447 GEN
Solar/Wind Harmer
3.409
274888KELLY CRK;1U
Solar/Wind Harmer
3.114
276776AD2-060 GEN
Solar/Wind Harmer
0.221
958011AF2-095 GEN
Solar/Wind Harmer
7.599
970941AG2-585 GEN
Solar/Wind Harmer
2.903
276897AD1-100 C
Solar/Wind Harmer
24.489
274805UNIV PK N;1U
Adder
2.642
274808UNIV PK N;4U
Adder
2.625
274674JOLIET 9 ;6U
Adder
8.073
276893AG1-478 C
Solar/Wind Harmer
0.229
274696ROCKY RD ;4P
Adder
5.889
274695ROCKY RD ;2P
Adder
5.753
274693ROCKY RD ;1P
Adder
5.697
274697ROCKY RD ;3P
Adder
1.563
274683WAUKEGAN ;8U
Adder
10.848
274683WAUKEGAN ;8U
Adder
9.145
962691AG1-118 GEN
Solar/Wind Harmer
15.409
958481AF2-142 GEN
Solar/Wind Harmer
7.69
960751AF2-366 GEN
Solar/Wind Harmer
1.47
958491AF2-143 GEN
Solar/Wind Harmer
7.602
276901AD2-066 C O1
Solar/Wind Harmer
1.777
971341AH1-150 GEN
Solar/Wind Harmer
10.065
971343AH1-151 GEN
Solar/Wind Harmer
10.065
972235AH1-702 GEN1
Adder
1.262
972236AH1-702 GEN2
Adder
1.097
276872AE1-163_GEN1
Solar/Wind Harmer
3.349
276876AE1-163_GEN2
Solar/Wind Harmer
3.349
24721605FLATG1
50/50
1.063
274775LINCOLN ;6U
Adder
3.399
274776LINCOLN ;7U
Adder
3.399
274777LINCOLN ;8U
Adder
3.399
960681AF2-359 GEN
Solar/Wind Harmer
2.014
972228AH1-698 GEN2
Adder
1.958
972227AH1-698 GEN1
Adder
1.378
960591AF2-350 GEN
Solar/Wind Harmer
5.277
274827FISK ;RP
Adder
4.092
274800UNIV PARK;3U
Adder
3.073
274801UNIV PARK;4U
Adder
3.073
972037AH1-567 GEN1
Adder
0.096
274687WILL CNTY;4U
Adder
14.674
274687WILL CNTY;4U
Adder
14.674
274675JOLIET 29;7U
Adder
16.11
274675JOLIET 29;7U
Adder
15.535
970833AG2-524 GEN
Solar/Wind Harmer
4.579
970833AG2-524 GEN
Solar/Wind Harmer
2.13
274728ELWOOD EC;5P
Adder
8.606
274731ELWOOD EC;2P
Adder
8.606
274733ELWOOD EC;3P
Adder
8.606
274735ELWOOD EC;4P
Adder
8.606
276893AG1-478 C
Solar/Wind Harmer
0.288
274744AC1-111 GEN8
Adder
2.922
274746AC1-111 G10
Adder
2.922
270526AF1-158 GEN
Solar/Wind Harmer
2.34
971771AH1-392 GEN
Solar/Wind Harmer
4.588
970073AG2-061 GEN
Solar/Wind Harmer
1.179
971675AH1-338 GEN
Solar/Wind Harmer
9.118
276861AD2-134 GEN
Solar/Wind Harmer
0.904
276863AD2-134 GEN
Solar/Wind Harmer
0.904
971411AH1-196 GEN
Solar/Wind Harmer
7.595
971171AH1-044 GEN
Solar/Wind Harmer
10.065
274823ROCKFORD ;21
Adder
9.774
274863CRW1-WTG
Solar/Wind Harmer
2.783
274864CRW2-WTG
Solar/Wind Harmer
2.783
276889AE2-281 GEN
Solar/Wind Harmer
0.957
274856ECOGROVE ;U1
Solar/Wind Harmer
1.68
276611AD2-172 GEN
Solar/Wind Harmer
1.274
276612AE2-035 GEN
Solar/Wind Harmer
1.274
971681AH1-341 GEN
Solar/Wind Harmer
7.429
926823AC1-168 GEN
Solar/Wind Harmer
2.122
970169AG2-114 GEN
Solar/Wind Harmer
4.901
972267AH1-718 GEN
Adder
2.035
276741O09 GEN1
Solar/Wind Harmer
1.739
958391AF2-133 GEN
Solar/Wind Harmer
4.373
274877BISHOP HL;1U
Solar/Wind Harmer
1.621
959141AF2-205 GEN
Solar/Wind Harmer
2.893
270223U2-072_GEN1
Solar/Wind Helper
1.526
270224U2-072_GEN2
Solar/Wind Helper
1.526
270227U2-072_GEN3
Solar/Wind Helper
1.526
270228U2-072_GEN4
Solar/Wind Helper
1.526
270231U2-072_GEN5
Solar/Wind Helper
1.526
241973AD2-163_GEN1
Solar/Wind Helper
2.406
241974AD2-163_GEN2
Solar/Wind Helper
2.406
241955AC1-078 GEN
Solar/Wind Helper
2.39
945631AF1-228 GEN
Solar/Wind Helper
1.862
966831AG1-554 GEN
Solar/Wind Helper
0.86
253338AC1-165 GEN
Solar/Wind Helper
0.829
253343AC1-166 GEN
Solar/Wind Helper
0.829
241972AD1-140 GEN
Solar/Wind Helper
3.091
945641AF1-229 GEN
Solar/Wind Helper
1.095
270499AE1-146 GEN
Solar/Wind Helper
1.885
270263AC1-001 GEN
Solar/Wind Helper
0.54
270340AC2-060 GEN
Solar/Wind Helper
0.967
270535AF1-215 GEN1
Solar/Wind Harmer
2.252
270536AF1-215 GEN2
Solar/Wind Harmer
2.252
938861AE1-114 GEN
Solar/Wind Harmer
4.059
274764LEE CO EC;5U
Adder
4.601
274765LEE CO EC;6U
Adder
4.601
274762LEE CO EC;3U
Adder
4.59
274763LEE CO EC;4U
Adder
4.547
276158O29GEN2
Solar/Wind Harmer
2.436
276157O29GEN1
Solar/Wind Harmer
1.852
276645AC1-214 GEN1
Solar/Wind Harmer
0.646
247620Y3-023
Adder
0.208
270349AD2-093_GEN
Solar/Wind Helper
4.68
270471AD2-092_GEN
Solar/Wind Helper
4.68
270462AD2-086
Solar/Wind Helper
5.356
253383AE2-342_GEN
Solar/Wind Helper
1.111
946101AF1-275 GEN
Solar/Wind Helper
0.784
241960AC2-195 GEN
Solar/Wind Helper
1.835
270054AF2-122 C O1
Solar/Wind Helper
1.457
253378AE2-206_GEN
Solar/Wind Helper
1.313
247522W1-056 GEN
Solar/Wind Helper
1.156
253415AE1-040 GEN
Solar/Wind Helper
0.455
961051AF2-396 GEN
Solar/Wind Harmer
7.374
961051AF2-396 GEN
Solar/Wind Harmer
3.43
24722005FLATG5
50/50
1.063
24721905FLATG4
50/50
19.423
962771AG1-126 GEN
Solar/Wind Harmer
78.258
970153AG2-106 GEN
Solar/Wind Harmer
34.124
971347AH1-153 GEN
Solar/Wind Harmer
2.935
274772LINCOLN ;3U
Adder
3.399
970707AG2-453 GEN
Solar/Wind Harmer
15.013
972259AH1-714 GEN
Adder
10.14
276164X3-005 C
Solar/Wind Harmer
0.372
274724RIVER EC ;11
Adder
9.39
274887GEN-1.85
Solar/Wind Harmer
2.812
276772AC2-154 GEN
Solar/Wind Harmer
1.473
276843GEN-1.7
Solar/Wind Harmer
0.303
276806AD2-047 C O1
Solar/Wind Harmer
5.646
274826FISK ;BP
Adder
5.774
939351AE1-166 GEN
Solar/Wind Harmer
3.126
972038AH1-567 GEN2
Adder
0.192
274803UNIV PARK;6U
Adder
3.071
274814UNIV PK N;0U
Adder
2.659
274807UNIV PK N;3U
Adder
2.653
274811UNIV PK N;7U
Adder
2.636
972231SS25-0005
Solar/Wind Harmer
4.99
972181SS23-001
Solar/Wind Harmer
3.119
274752CRETE EC ;2U
Adder
2.57
274753CRETE EC ;3U
Adder
2.57
274676JOLIET 29;8U
Adder
15.535
943121AE2-341 GEN
Solar/Wind Harmer
7.867
943591AF1-030 GEN
Solar/Wind Harmer
5.245
274729ELWOOD EC;1P
Adder
8.606
274730ELWOOD EC;6P
Adder
8.606
274734ELWOOD EC;8P
Adder
8.606
274736ELWOOD EC;9P
Adder
8.606
24441505OLIV SLR
Solar/Wind Harmer
0.069
274682WAUKEGAN ;7U
Adder
9.263
274862TOP CROP ;2U
Solar/Wind Harmer
2.591
276799AD1-013 GEN
Solar/Wind Harmer
1.12
946671AF1-331 GEN
Solar/Wind Harmer
0.212
274855GSG-6 ;RU
Solar/Wind Harmer
1.87
274850MENDOTA H;RU
Solar/Wind Harmer
1.3
276602WESTBROOK C
Solar/Wind Harmer
1.076
276868AE1-113 GEN
Solar/Wind Harmer
5.111
274879MINONK ;1U
Solar/Wind Harmer
3.407
959091AF2-200 GEN
Solar/Wind Harmer
10.065
247643Z2-116 C
Solar/Wind Harmer
0.034
274857EASY ROAD;U1
Solar/Wind Harmer
2.364
274760LEE CO EC;1U
Adder
4.59
274767LEE CO EC;8U
Adder
4.536
970571AG2-364 GEN
Solar/Wind Harmer
9.862
276603SUBLETTE C
Solar/Wind Harmer
0.517
270505AE1-170 C O1
Solar/Wind Harmer
7.344
964401AG1-302 GEN
Solar/Wind Harmer
4.417
274851PROVIDENC;RU
Solar/Wind Harmer
1.375
274849CRESCENT ;1U
Solar/Wind Harmer
0.892
276782AC1-033 GEN
Solar/Wind Harmer
1.916
274878BISHOP HL;2U
Solar/Wind Harmer
1.621
945111AF1-176 GEN
Solar/Wind Harmer
2.711
270284AF1-227 GEN1
Solar/Wind Helper
6.367
270287AF1-227 GEN3
Solar/Wind Helper
2.335
942871AE2-306 GEN
Solar/Wind Helper
0.775
276820AF1-078_GEN
Solar/Wind Helper
0.613
270518AE2-148 GEN
Solar/Wind Helper
10.61
960801AF2-371 GEN
Solar/Wind Helper
0.85
964871AG1-351 GEN
Solar/Wind Helper
0.587
253325AC1-069 GEN
Solar/Wind Helper
0.859
270541AE2-072 C
Solar/Wind Helper
1.112
960071AF2-298 GEN
Solar/Wind Helper
0.32
CPLELTFEXP_CPLE->PJM
CLTF
1.546
CBM West 2LTFEXP_CBM-W2->PJM
CBM
39.631
NYPJM->LTFIMP_NY
CLTF
0.933
LGEELTFEXP_LGEE->PJM
CLTF
0.885
WECLTFEXP_WEC->PJM
CLTF
1.909
AG2-052LTFEXP_AG2-052->PJM
LTF
0.114
AH1-155LTFEXP_AH1-155->PJM
LTF
0.17
LAGNLTFEXP_LAGN->PJM
CLTF
5.571
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.313
TVALTFEXP_TVA->PJM
CLTF
2.485
CBM West 1LTFEXP_CBM-W1->PJM
CBM
43.606
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.522
MECLTFEXP_MEC->PJM
CLTF
7.183
SIGELTFEXP_SIGE->PJM
CLTF
0.119

Details for 05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#7222_05MALIS 765_D_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
Contingency Name:
AEP_P4_#7222_05MALIS 765_D_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.32 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3323.76
MW Contribution:
48.15
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
1.059
274775LINCOLN ;6U
Adder
3.349
274776LINCOLN ;7U
Adder
3.349
274777LINCOLN ;8U
Adder
3.349
960681AF2-359 GEN
Solar/Wind Harmer
1.984
972228AH1-698 GEN2
Adder
1.928
972227AH1-698 GEN1
Adder
1.358
960591AF2-350 GEN
Solar/Wind Harmer
5.197
274827FISK ;RP
Adder
4.03
274800UNIV PARK;3U
Adder
3.027
274801UNIV PARK;4U
Adder
3.027
972037AH1-567 GEN1
Adder
0.095
274687WILL CNTY;4U
Adder
14.452
274687WILL CNTY;4U
Adder
14.452
274675JOLIET 29;7U
Adder
15.866
274675JOLIET 29;7U
Adder
15.3
970833AG2-524 GEN
Solar/Wind Harmer
4.51
970833AG2-524 GEN
Solar/Wind Harmer
2.098
274728ELWOOD EC;5P
Adder
8.475
274731ELWOOD EC;2P
Adder
8.475
274733ELWOOD EC;3P
Adder
8.475
274735ELWOOD EC;4P
Adder
8.475
276893AG1-478 C
Solar/Wind Harmer
0.283
274744AC1-111 GEN8
Adder
2.877
274746AC1-111 G10
Adder
2.877
270526AF1-158 GEN
Solar/Wind Harmer
2.303
971771AH1-392 GEN
Solar/Wind Harmer
4.514
970073AG2-061 GEN
Solar/Wind Harmer
1.16
971675AH1-338 GEN
Solar/Wind Harmer
8.977
276861AD2-134 GEN
Solar/Wind Harmer
0.89
276863AD2-134 GEN
Solar/Wind Harmer
0.89
971411AH1-196 GEN
Solar/Wind Harmer
7.478
971171AH1-044 GEN
Solar/Wind Harmer
9.909
274823ROCKFORD ;21
Adder
9.622
276889AE2-281 GEN
Solar/Wind Harmer
0.942
274863CRW1-WTG
Solar/Wind Harmer
2.739
274864CRW2-WTG
Solar/Wind Harmer
2.739
274856ECOGROVE ;U1
Solar/Wind Harmer
1.654
276611AD2-172 GEN
Solar/Wind Harmer
1.254
24721705FLATG2
50/50
15.73
970349AG2-230 GEN
Solar/Wind Harmer
8.682
274770LINCOLN ;1U
Adder
3.349
274771LINCOLN ;2U
Adder
3.349
965681AG1-436 GEN
Solar/Wind Harmer
6.562
965791AG1-447 GEN
Solar/Wind Harmer
3.357
274888KELLY CRK;1U
Solar/Wind Harmer
3.067
276776AD2-060 GEN
Solar/Wind Harmer
0.218
958011AF2-095 GEN
Solar/Wind Harmer
7.484
970941AG2-585 GEN
Solar/Wind Harmer
2.859
276897AD1-100 C
Solar/Wind Harmer
24.118
274805UNIV PK N;1U
Adder
2.602
274808UNIV PK N;4U
Adder
2.585
274674JOLIET 9 ;6U
Adder
7.951
276893AG1-478 C
Solar/Wind Harmer
0.226
274695ROCKY RD ;2P
Adder
5.665
274693ROCKY RD ;1P
Adder
5.61
274697ROCKY RD ;3P
Adder
1.539
274696ROCKY RD ;4P
Adder
5.799
274683WAUKEGAN ;8U
Adder
10.682
274683WAUKEGAN ;8U
Adder
9.005
962691AG1-118 GEN
Solar/Wind Harmer
15.173
958481AF2-142 GEN
Solar/Wind Harmer
7.571
960751AF2-366 GEN
Solar/Wind Harmer
1.448
958491AF2-143 GEN
Solar/Wind Harmer
7.484
276901AD2-066 C O1
Solar/Wind Harmer
1.749
971341AH1-150 GEN
Solar/Wind Harmer
9.909
971343AH1-151 GEN
Solar/Wind Harmer
9.909
972235AH1-702 GEN1
Adder
1.242
972236AH1-702 GEN2
Adder
1.08
276872AE1-163_GEN1
Solar/Wind Harmer
3.296
276876AE1-163_GEN2
Solar/Wind Harmer
3.296
270535AF1-215 GEN1
Solar/Wind Harmer
2.215
270536AF1-215 GEN2
Solar/Wind Harmer
2.215
938861AE1-114 GEN
Solar/Wind Harmer
3.995
274764LEE CO EC;5U
Adder
4.528
274765LEE CO EC;6U
Adder
4.528
274762LEE CO EC;3U
Adder
4.518
274763LEE CO EC;4U
Adder
4.475
276158O29GEN2
Solar/Wind Harmer
2.397
276157O29GEN1
Solar/Wind Harmer
1.823
276645AC1-214 GEN1
Solar/Wind Harmer
0.636
247620Y3-023
Adder
0.204
270349AD2-093_GEN
Solar/Wind Helper
4.705
270471AD2-092_GEN
Solar/Wind Helper
4.705
270462AD2-086
Solar/Wind Helper
5.394
253383AE2-342_GEN
Solar/Wind Helper
1.128
946101AF1-275 GEN
Solar/Wind Helper
0.8
24721805FLATG3
50/50
1.059
962761AG1-125 GEN
Solar/Wind Harmer
77.975
970149AG2-104 GEN
Solar/Wind Harmer
48.149
970155AG2-107 GEN
Solar/Wind Harmer
34.001
972207SS24-0001
Solar/Wind Harmer
11.906
274773LINCOLN ;4U
Adder
3.349
274774LINCOLN ;5U
Adder
3.349
274723RIVER EC ;12
Adder
9.352
941551AE2-152 GEN
Solar/Wind Harmer
2.355
274802UNIV PARK;5U
Adder
3.024
274812UNIV PK N;8U
Adder
2.596
274751CRETE EC ;1U
Adder
2.531
274754CRETE EC ;4U
Adder
2.531
276612AE2-035 GEN
Solar/Wind Harmer
1.254
971681AH1-341 GEN
Solar/Wind Harmer
7.312
926823AC1-168 GEN
Solar/Wind Harmer
2.088
970169AG2-114 GEN
Solar/Wind Harmer
4.823
972267AH1-718 GEN
Adder
2.003
276741O09 GEN1
Solar/Wind Harmer
1.712
958391AF2-133 GEN
Solar/Wind Harmer
4.3
274877BISHOP HL;1U
Solar/Wind Harmer
1.595
959141AF2-205 GEN
Solar/Wind Harmer
2.844
270223U2-072_GEN1
Solar/Wind Helper
1.536
270224U2-072_GEN2
Solar/Wind Helper
1.536
270227U2-072_GEN3
Solar/Wind Helper
1.536
270228U2-072_GEN4
Solar/Wind Helper
1.536
270231U2-072_GEN5
Solar/Wind Helper
1.536
241973AD2-163_GEN1
Solar/Wind Helper
2.441
241974AD2-163_GEN2
Solar/Wind Helper
2.441
241955AC1-078 GEN
Solar/Wind Helper
2.436
945631AF1-228 GEN
Solar/Wind Helper
1.902
966831AG1-554 GEN
Solar/Wind Helper
0.869
253338AC1-165 GEN
Solar/Wind Helper
0.848
253343AC1-166 GEN
Solar/Wind Helper
0.848
241972AD1-140 GEN
Solar/Wind Helper
3.153
945641AF1-229 GEN
Solar/Wind Helper
1.107
270499AE1-146 GEN
Solar/Wind Helper
1.906
270263AC1-001 GEN
Solar/Wind Helper
0.555
270340AC2-060 GEN
Solar/Wind Helper
0.994
274676JOLIET 29;8U
Adder
15.866
274871GR RIDGE ;2U
Solar/Wind Harmer
3.971
274847GR RIDGE ;BU
Solar/Wind Harmer
2.611
274674JOLIET 9 ;6U
Adder
7.951
274732ELWOOD EC;7P
Adder
8.475
274745AC1-111 GEN9
Adder
2.877
274682WAUKEGAN ;7U
Adder
9.121
274828WAUKEGAN ;BP
Adder
5.599
276694AA1-018 GEN2
Solar/Wind Harmer
3.185
276691AA1-018 GEN1
Solar/Wind Harmer
0.381
962781AG1-127 GEN
Solar/Wind Harmer
4.798
274861TOP CROP ;1U
Solar/Wind Harmer
3.055
274872LEEDK;1U
Solar/Wind Harmer
4.133
939401AE1-172 GEN
Solar/Wind Harmer
6.957
276805AD2-038 GEN
Solar/Wind Harmer
2.558
970373AG2-245 GEN
Solar/Wind Harmer
10.446
971997AH1-543 GEN
Solar/Wind Harmer
7.83
276882AE2-255 GEN
Solar/Wind Harmer
1.677
957471AF2-041 GEN
Solar/Wind Harmer
14.863
959081AF2-199 GEN
Solar/Wind Harmer
4.954
971067AG2-660 GEN
Solar/Wind Harmer
1.152
274822ROCKFORD ;11
Adder
9.693
970819AG2-516 GEN
Solar/Wind Harmer
5.894
270055AF2-134 C O1
Solar/Wind Harmer
1.477
274858EASY ROAD;U2
Solar/Wind Harmer
2.326
274761LEE CO EC;2U
Adder
4.518
274766LEE CO EC;7U
Adder
4.465
970569AG2-363 GEN
Solar/Wind Harmer
14.559
270216AD2-079_GEN
Solar/Wind Harmer
0.293
957891AF2-083 GEN
Solar/Wind Harmer
7.188
958381AF2-132 GEN
Solar/Wind Harmer
4.344
276708O09 GEN2
Solar/Wind Harmer
1.712
964861AG1-349 GEN
Solar/Wind Harmer
3.757
971917AH1-482 GEN
Solar/Wind Harmer
4.335
276646AC1-214 GEN2
Solar/Wind Harmer
0.636
945111AF1-176 GEN
Solar/Wind Harmer
8.408
274848CAMPGROVE;RU
Solar/Wind Harmer
3.038
24639705ELKHART HY
Adder
0.071
270286AF1-227 GEN2
Solar/Wind Helper
2.348
270391AF1-285 GEN3
Solar/Wind Helper
1.04
270578AF1-285 GEN2
Solar/Wind Helper
1.04
270317AD1-130_GEN
Solar/Wind Helper
5.963
270485AE1-090_GEN
Solar/Wind Helper
0.469
270520AE2-214 GEN
Solar/Wind Helper
3.2
253333AC1-068 GEN
Solar/Wind Helper
0.879
960841AF2-375 GEN
Solar/Wind Helper
1.159
270273AD2-016 GEN
Solar/Wind Helper
1.703
270297AD1-101 GEN
Solar/Wind Helper
0.213
958961AF2-187 GEN
Solar/Wind Helper
1.122
241840AF1-064_GEN
Solar/Wind Helper
0.483
241807AE2-176_GEN
Solar/Wind Helper
0.703
24722005FLATG5
50/50
1.059
24721905FLATG4
50/50
19.347
962771AG1-126 GEN
Solar/Wind Harmer
77.975
970153AG2-106 GEN
Solar/Wind Harmer
34.001
971347AH1-153 GEN
Solar/Wind Harmer
2.894
274772LINCOLN ;3U
Adder
3.349
970707AG2-453 GEN
Solar/Wind Harmer
14.79
972259AH1-714 GEN
Adder
9.988
276164X3-005 C
Solar/Wind Harmer
0.367
274724RIVER EC ;11
Adder
9.248
274887GEN-1.85
Solar/Wind Harmer
2.769
276772AC2-154 GEN
Solar/Wind Harmer
1.45
276843GEN-1.7
Solar/Wind Harmer
0.298
276806AD2-047 C O1
Solar/Wind Harmer
5.56
274826FISK ;BP
Adder
5.687
939351AE1-166 GEN
Solar/Wind Harmer
3.079
972038AH1-567 GEN2
Adder
0.189
274803UNIV PARK;6U
Adder
3.024
274814UNIV PK N;0U
Adder
2.619
274807UNIV PK N;3U
Adder
2.613
274811UNIV PK N;7U
Adder
2.596
972231SS25-0005
Solar/Wind Harmer
4.914
972181SS23-001
Solar/Wind Harmer
3.071
274752CRETE EC ;2U
Adder
2.531
274753CRETE EC ;3U
Adder
2.531
274676JOLIET 29;8U
Adder
15.299
943121AE2-341 GEN
Solar/Wind Harmer
7.748
943591AF1-030 GEN
Solar/Wind Harmer
5.165
274729ELWOOD EC;1P
Adder
8.475
274730ELWOOD EC;6P
Adder
8.475
274734ELWOOD EC;8P
Adder
8.475
274736ELWOOD EC;9P
Adder
8.475
24441505OLIV SLR
Solar/Wind Harmer
0.068
274682WAUKEGAN ;7U
Adder
9.121
274862TOP CROP ;2U
Solar/Wind Harmer
2.551
276799AD1-013 GEN
Solar/Wind Harmer
1.102
946671AF1-331 GEN
Solar/Wind Harmer
0.209
274855GSG-6 ;RU
Solar/Wind Harmer
1.841
274850MENDOTA H;RU
Solar/Wind Harmer
1.28
276602WESTBROOK C
Solar/Wind Harmer
1.06
276868AE1-113 GEN
Solar/Wind Harmer
5.031
274879MINONK ;1U
Solar/Wind Harmer
3.354
959091AF2-200 GEN
Solar/Wind Harmer
9.909
247643Z2-116 C
Solar/Wind Harmer
0.034
274857EASY ROAD;U1
Solar/Wind Harmer
2.326
274760LEE CO EC;1U
Adder
4.518
274767LEE CO EC;8U
Adder
4.465
970571AG2-364 GEN
Solar/Wind Harmer
9.706
276603SUBLETTE C
Solar/Wind Harmer
0.508
270505AE1-170 C O1
Solar/Wind Harmer
7.222
964401AG1-302 GEN
Solar/Wind Harmer
4.344
274851PROVIDENC;RU
Solar/Wind Harmer
1.352
274849CRESCENT ;1U
Solar/Wind Harmer
0.878
276782AC1-033 GEN
Solar/Wind Harmer
1.885
274878BISHOP HL;2U
Solar/Wind Harmer
1.595
945111AF1-176 GEN
Solar/Wind Harmer
2.665
270284AF1-227 GEN1
Solar/Wind Helper
6.403
270287AF1-227 GEN3
Solar/Wind Helper
2.348
942871AE2-306 GEN
Solar/Wind Helper
0.78
276820AF1-078_GEN
Solar/Wind Helper
0.621
270518AE2-148 GEN
Solar/Wind Helper
10.844
960801AF2-371 GEN
Solar/Wind Helper
0.869
964871AG1-351 GEN
Solar/Wind Helper
0.6
253325AC1-069 GEN
Solar/Wind Helper
0.879
270541AE2-072 C
Solar/Wind Helper
1.128
960071AF2-298 GEN
Solar/Wind Helper
0.328
241960AC2-195 GEN
Solar/Wind Helper
1.855
270054AF2-122 C O1
Solar/Wind Helper
1.473
253378AE2-206_GEN
Solar/Wind Helper
1.329
247522W1-056 GEN
Solar/Wind Helper
1.168
253415AE1-040 GEN
Solar/Wind Helper
0.468
253349AC2-067 GEN
Solar/Wind Helper
0.175
253400AC2-068 GEN
Solar/Wind Helper
0.07
961051AF2-396 GEN
Solar/Wind Harmer
7.248
961051AF2-396 GEN
Solar/Wind Harmer
3.371
CPLELTFEXP_CPLE->PJM
CLTF
1.537
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.767
NYPJM->LTFIMP_NY
CLTF
0.905
LGEELTFEXP_LGEE->PJM
CLTF
0.829
WECLTFEXP_WEC->PJM
CLTF
1.879
AG2-052LTFEXP_AG2-052->PJM
LTF
0.112
AH1-155LTFEXP_AH1-155->PJM
LTF
0.168
LAGNLTFEXP_LAGN->PJM
CLTF
5.461
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.255
TVALTFEXP_TVA->PJM
CLTF
2.432
CBM West 1LTFEXP_CBM-W1->PJM
CBM
42.534
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.305
MECLTFEXP_MEC->PJM
CLTF
7.06
SIGELTFEXP_SIGE->PJM
CLTF
0.115

Details for 05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer l/o AEP_P2-2_#7222_05MALIS 765_1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
Contingency Name:
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:107.32 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3323.61
MW Contribution:
48.15
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721705FLATG2
50/50
15.73
970349AG2-230 GEN
Solar/Wind Harmer
8.682
274770LINCOLN ;1U
Adder
3.349
274771LINCOLN ;2U
Adder
3.349
965681AG1-436 GEN
Solar/Wind Harmer
6.562
965791AG1-447 GEN
Solar/Wind Harmer
3.357
274888KELLY CRK;1U
Solar/Wind Harmer
3.067
276776AD2-060 GEN
Solar/Wind Harmer
0.218
958011AF2-095 GEN
Solar/Wind Harmer
7.484
970941AG2-585 GEN
Solar/Wind Harmer
2.859
276897AD1-100 C
Solar/Wind Harmer
24.118
274805UNIV PK N;1U
Adder
2.602
274808UNIV PK N;4U
Adder
2.585
274674JOLIET 9 ;6U
Adder
7.951
276893AG1-478 C
Solar/Wind Harmer
0.226
274695ROCKY RD ;2P
Adder
5.665
274693ROCKY RD ;1P
Adder
5.61
274697ROCKY RD ;3P
Adder
1.539
274696ROCKY RD ;4P
Adder
5.799
274683WAUKEGAN ;8U
Adder
10.682
274683WAUKEGAN ;8U
Adder
9.005
962691AG1-118 GEN
Solar/Wind Harmer
15.173
958481AF2-142 GEN
Solar/Wind Harmer
7.571
960751AF2-366 GEN
Solar/Wind Harmer
1.448
958491AF2-143 GEN
Solar/Wind Harmer
7.484
276901AD2-066 C O1
Solar/Wind Harmer
1.749
971341AH1-150 GEN
Solar/Wind Harmer
9.909
971343AH1-151 GEN
Solar/Wind Harmer
9.909
972235AH1-702 GEN1
Adder
1.242
972236AH1-702 GEN2
Adder
1.08
276872AE1-163_GEN1
Solar/Wind Harmer
3.296
276876AE1-163_GEN2
Solar/Wind Harmer
3.296
270535AF1-215 GEN1
Solar/Wind Harmer
2.215
270536AF1-215 GEN2
Solar/Wind Harmer
2.215
938861AE1-114 GEN
Solar/Wind Harmer
3.995
274764LEE CO EC;5U
Adder
4.528
274765LEE CO EC;6U
Adder
4.528
274762LEE CO EC;3U
Adder
4.518
274763LEE CO EC;4U
Adder
4.475
276158O29GEN2
Solar/Wind Harmer
2.397
276157O29GEN1
Solar/Wind Harmer
1.823
276645AC1-214 GEN1
Solar/Wind Harmer
0.636
247620Y3-023
Adder
0.204
270349AD2-093_GEN
Solar/Wind Helper
4.705
270471AD2-092_GEN
Solar/Wind Helper
4.705
270462AD2-086
Solar/Wind Helper
5.394
253383AE2-342_GEN
Solar/Wind Helper
1.128
946101AF1-275 GEN
Solar/Wind Helper
0.8
241960AC2-195 GEN
Solar/Wind Helper
1.855
270054AF2-122 C O1
Solar/Wind Helper
1.473
253378AE2-206_GEN
Solar/Wind Helper
1.329
24721605FLATG1
50/50
1.059
274775LINCOLN ;6U
Adder
3.349
274776LINCOLN ;7U
Adder
3.349
274777LINCOLN ;8U
Adder
3.349
960681AF2-359 GEN
Solar/Wind Harmer
1.984
972228AH1-698 GEN2
Adder
1.928
972227AH1-698 GEN1
Adder
1.358
960591AF2-350 GEN
Solar/Wind Harmer
5.197
274827FISK ;RP
Adder
4.03
274800UNIV PARK;3U
Adder
3.027
274801UNIV PARK;4U
Adder
3.027
972037AH1-567 GEN1
Adder
0.095
274687WILL CNTY;4U
Adder
14.452
274687WILL CNTY;4U
Adder
14.452
274675JOLIET 29;7U
Adder
15.866
274675JOLIET 29;7U
Adder
15.3
970833AG2-524 GEN
Solar/Wind Harmer
4.51
970833AG2-524 GEN
Solar/Wind Harmer
2.098
274728ELWOOD EC;5P
Adder
8.475
274731ELWOOD EC;2P
Adder
8.475
274733ELWOOD EC;3P
Adder
8.475
274735ELWOOD EC;4P
Adder
8.475
276893AG1-478 C
Solar/Wind Harmer
0.283
274744AC1-111 GEN8
Adder
2.877
274746AC1-111 G10
Adder
2.877
270526AF1-158 GEN
Solar/Wind Harmer
2.303
971771AH1-392 GEN
Solar/Wind Harmer
4.514
970073AG2-061 GEN
Solar/Wind Harmer
1.16
971675AH1-338 GEN
Solar/Wind Harmer
8.977
276861AD2-134 GEN
Solar/Wind Harmer
0.89
276863AD2-134 GEN
Solar/Wind Harmer
0.89
971411AH1-196 GEN
Solar/Wind Harmer
7.478
971171AH1-044 GEN
Solar/Wind Harmer
9.909
274823ROCKFORD ;21
Adder
9.622
276889AE2-281 GEN
Solar/Wind Harmer
0.942
274863CRW1-WTG
Solar/Wind Harmer
2.739
274864CRW2-WTG
Solar/Wind Harmer
2.739
274856ECOGROVE ;U1
Solar/Wind Harmer
1.654
276611AD2-172 GEN
Solar/Wind Harmer
1.254
276612AE2-035 GEN
Solar/Wind Harmer
1.254
971681AH1-341 GEN
Solar/Wind Harmer
7.312
926823AC1-168 GEN
Solar/Wind Harmer
2.088
970169AG2-114 GEN
Solar/Wind Harmer
4.823
972267AH1-718 GEN
Adder
2.003
276741O09 GEN1
Solar/Wind Harmer
1.712
958391AF2-133 GEN
Solar/Wind Harmer
4.3
274877BISHOP HL;1U
Solar/Wind Harmer
1.595
959141AF2-205 GEN
Solar/Wind Harmer
2.844
270223U2-072_GEN1
Solar/Wind Helper
1.536
270224U2-072_GEN2
Solar/Wind Helper
1.536
270227U2-072_GEN3
Solar/Wind Helper
1.536
270228U2-072_GEN4
Solar/Wind Helper
1.536
270231U2-072_GEN5
Solar/Wind Helper
1.536
241973AD2-163_GEN1
Solar/Wind Helper
2.441
241974AD2-163_GEN2
Solar/Wind Helper
2.441
241955AC1-078 GEN
Solar/Wind Helper
2.436
945631AF1-228 GEN
Solar/Wind Helper
1.902
966831AG1-554 GEN
Solar/Wind Helper
0.869
253338AC1-165 GEN
Solar/Wind Helper
0.848
253343AC1-166 GEN
Solar/Wind Helper
0.848
241972AD1-140 GEN
Solar/Wind Helper
3.153
945641AF1-229 GEN
Solar/Wind Helper
1.107
270499AE1-146 GEN
Solar/Wind Helper
1.906
270263AC1-001 GEN
Solar/Wind Helper
0.555
270340AC2-060 GEN
Solar/Wind Helper
0.994
24721805FLATG3
50/50
1.059
962761AG1-125 GEN
Solar/Wind Harmer
77.975
970149AG2-104 GEN
Solar/Wind Harmer
48.149
970155AG2-107 GEN
Solar/Wind Harmer
34.001
972207SS24-0001
Solar/Wind Harmer
11.906
274773LINCOLN ;4U
Adder
3.349
274774LINCOLN ;5U
Adder
3.349
274723RIVER EC ;12
Adder
9.352
941551AE2-152 GEN
Solar/Wind Harmer
2.355
274802UNIV PARK;5U
Adder
3.024
274812UNIV PK N;8U
Adder
2.596
274751CRETE EC ;1U
Adder
2.531
274754CRETE EC ;4U
Adder
2.531
274676JOLIET 29;8U
Adder
15.866
274871GR RIDGE ;2U
Solar/Wind Harmer
3.971
274847GR RIDGE ;BU
Solar/Wind Harmer
2.611
274674JOLIET 9 ;6U
Adder
7.951
274732ELWOOD EC;7P
Adder
8.475
274745AC1-111 GEN9
Adder
2.877
274682WAUKEGAN ;7U
Adder
9.121
274828WAUKEGAN ;BP
Adder
5.599
276694AA1-018 GEN2
Solar/Wind Harmer
3.185
276691AA1-018 GEN1
Solar/Wind Harmer
0.381
962781AG1-127 GEN
Solar/Wind Harmer
4.798
274861TOP CROP ;1U
Solar/Wind Harmer
3.055
274872LEEDK;1U
Solar/Wind Harmer
4.133
939401AE1-172 GEN
Solar/Wind Harmer
6.957
276805AD2-038 GEN
Solar/Wind Harmer
2.558
970373AG2-245 GEN
Solar/Wind Harmer
10.446
971997AH1-543 GEN
Solar/Wind Harmer
7.83
276882AE2-255 GEN
Solar/Wind Harmer
1.677
957471AF2-041 GEN
Solar/Wind Harmer
14.863
959081AF2-199 GEN
Solar/Wind Harmer
4.954
971067AG2-660 GEN
Solar/Wind Harmer
1.152
274822ROCKFORD ;11
Adder
9.693
970819AG2-516 GEN
Solar/Wind Harmer
5.894
270055AF2-134 C O1
Solar/Wind Harmer
1.477
274858EASY ROAD;U2
Solar/Wind Harmer
2.326
274761LEE CO EC;2U
Adder
4.518
274766LEE CO EC;7U
Adder
4.465
970569AG2-363 GEN
Solar/Wind Harmer
14.559
270216AD2-079_GEN
Solar/Wind Harmer
0.293
957891AF2-083 GEN
Solar/Wind Harmer
7.188
958381AF2-132 GEN
Solar/Wind Harmer
4.344
276708O09 GEN2
Solar/Wind Harmer
1.712
964861AG1-349 GEN
Solar/Wind Harmer
3.757
971917AH1-482 GEN
Solar/Wind Harmer
4.335
276646AC1-214 GEN2
Solar/Wind Harmer
0.636
945111AF1-176 GEN
Solar/Wind Harmer
8.408
274848CAMPGROVE;RU
Solar/Wind Harmer
3.038
24639705ELKHART HY
Adder
0.071
270286AF1-227 GEN2
Solar/Wind Helper
2.348
270391AF1-285 GEN3
Solar/Wind Helper
1.04
270578AF1-285 GEN2
Solar/Wind Helper
1.04
270317AD1-130_GEN
Solar/Wind Helper
5.963
270485AE1-090_GEN
Solar/Wind Helper
0.469
270520AE2-214 GEN
Solar/Wind Helper
3.2
253333AC1-068 GEN
Solar/Wind Helper
0.879
960841AF2-375 GEN
Solar/Wind Helper
1.159
270273AD2-016 GEN
Solar/Wind Helper
1.703
270297AD1-101 GEN
Solar/Wind Helper
0.213
958961AF2-187 GEN
Solar/Wind Helper
1.122
241840AF1-064_GEN
Solar/Wind Helper
0.483
241807AE2-176_GEN
Solar/Wind Helper
0.703
247522W1-056 GEN
Solar/Wind Helper
1.168
253415AE1-040 GEN
Solar/Wind Helper
0.468
253349AC2-067 GEN
Solar/Wind Helper
0.175
253400AC2-068 GEN
Solar/Wind Helper
0.07
961051AF2-396 GEN
Solar/Wind Harmer
7.248
961051AF2-396 GEN
Solar/Wind Harmer
3.371
24722005FLATG5
50/50
1.059
24721905FLATG4
50/50
19.347
962771AG1-126 GEN
Solar/Wind Harmer
77.975
970153AG2-106 GEN
Solar/Wind Harmer
34.001
971347AH1-153 GEN
Solar/Wind Harmer
2.894
274772LINCOLN ;3U
Adder
3.349
970707AG2-453 GEN
Solar/Wind Harmer
14.79
972259AH1-714 GEN
Adder
9.988
276164X3-005 C
Solar/Wind Harmer
0.367
274724RIVER EC ;11
Adder
9.248
274887GEN-1.85
Solar/Wind Harmer
2.769
276772AC2-154 GEN
Solar/Wind Harmer
1.45
276843GEN-1.7
Solar/Wind Harmer
0.298
276806AD2-047 C O1
Solar/Wind Harmer
5.56
274826FISK ;BP
Adder
5.687
939351AE1-166 GEN
Solar/Wind Harmer
3.079
972038AH1-567 GEN2
Adder
0.189
274803UNIV PARK;6U
Adder
3.024
274814UNIV PK N;0U
Adder
2.619
274807UNIV PK N;3U
Adder
2.613
274811UNIV PK N;7U
Adder
2.596
972231SS25-0005
Solar/Wind Harmer
4.914
972181SS23-001
Solar/Wind Harmer
3.071
274752CRETE EC ;2U
Adder
2.531
274753CRETE EC ;3U
Adder
2.531
274676JOLIET 29;8U
Adder
15.299
943121AE2-341 GEN
Solar/Wind Harmer
7.748
943591AF1-030 GEN
Solar/Wind Harmer
5.165
274729ELWOOD EC;1P
Adder
8.475
274730ELWOOD EC;6P
Adder
8.475
274734ELWOOD EC;8P
Adder
8.475
274736ELWOOD EC;9P
Adder
8.475
24441505OLIV SLR
Solar/Wind Harmer
0.068
274682WAUKEGAN ;7U
Adder
9.121
274862TOP CROP ;2U
Solar/Wind Harmer
2.551
276799AD1-013 GEN
Solar/Wind Harmer
1.102
946671AF1-331 GEN
Solar/Wind Harmer
0.209
274855GSG-6 ;RU
Solar/Wind Harmer
1.841
274850MENDOTA H;RU
Solar/Wind Harmer
1.28
276602WESTBROOK C
Solar/Wind Harmer
1.06
276868AE1-113 GEN
Solar/Wind Harmer
5.031
274879MINONK ;1U
Solar/Wind Harmer
3.354
959091AF2-200 GEN
Solar/Wind Harmer
9.909
247643Z2-116 C
Solar/Wind Harmer
0.034
274857EASY ROAD;U1
Solar/Wind Harmer
2.326
274760LEE CO EC;1U
Adder
4.518
274767LEE CO EC;8U
Adder
4.465
970571AG2-364 GEN
Solar/Wind Harmer
9.706
276603SUBLETTE C
Solar/Wind Harmer
0.508
270505AE1-170 C O1
Solar/Wind Harmer
7.222
964401AG1-302 GEN
Solar/Wind Harmer
4.344
274851PROVIDENC;RU
Solar/Wind Harmer
1.352
274849CRESCENT ;1U
Solar/Wind Harmer
0.878
276782AC1-033 GEN
Solar/Wind Harmer
1.885
274878BISHOP HL;2U
Solar/Wind Harmer
1.595
945111AF1-176 GEN
Solar/Wind Harmer
2.665
270284AF1-227 GEN1
Solar/Wind Helper
6.403
270287AF1-227 GEN3
Solar/Wind Helper
2.348
942871AE2-306 GEN
Solar/Wind Helper
0.78
276820AF1-078_GEN
Solar/Wind Helper
0.621
270518AE2-148 GEN
Solar/Wind Helper
10.844
960801AF2-371 GEN
Solar/Wind Helper
0.869
964871AG1-351 GEN
Solar/Wind Helper
0.6
253325AC1-069 GEN
Solar/Wind Helper
0.879
270541AE2-072 C
Solar/Wind Helper
1.128
960071AF2-298 GEN
Solar/Wind Helper
0.328
CPLELTFEXP_CPLE->PJM
CLTF
1.537
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.767
NYPJM->LTFIMP_NY
CLTF
0.905
LGEELTFEXP_LGEE->PJM
CLTF
0.829
WECLTFEXP_WEC->PJM
CLTF
1.879
AG2-052LTFEXP_AG2-052->PJM
LTF
0.112
AH1-155LTFEXP_AH1-155->PJM
LTF
0.168
LAGNLTFEXP_LAGN->PJM
CLTF
5.461
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.255
TVALTFEXP_TVA->PJM
CLTF
2.432
CBM West 1LTFEXP_CBM-W1->PJM
CBM
42.534
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.305
MECLTFEXP_MEC->PJM
CLTF
7.06
SIGELTFEXP_SIGE->PJM
CLTF
0.115

Details for 05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#9729_05MALIS 138_M1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
Contingency Name:
AEP_P4_#9729_05MALIS 138_M1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.26 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3321.91
MW Contribution:
48.14
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721705FLATG2
50/50
15.728
970349AG2-230 GEN
Solar/Wind Harmer
8.677
274770LINCOLN ;1U
Adder
3.347
274771LINCOLN ;2U
Adder
3.347
965681AG1-436 GEN
Solar/Wind Harmer
6.558
965791AG1-447 GEN
Solar/Wind Harmer
3.355
274888KELLY CRK;1U
Solar/Wind Harmer
3.065
276776AD2-060 GEN
Solar/Wind Harmer
0.217
958011AF2-095 GEN
Solar/Wind Harmer
7.48
970941AG2-585 GEN
Solar/Wind Harmer
2.857
276897AD1-100 C
Solar/Wind Harmer
24.104
274805UNIV PK N;1U
Adder
2.6
274808UNIV PK N;4U
Adder
2.583
274674JOLIET 9 ;6U
Adder
7.946
276893AG1-478 C
Solar/Wind Harmer
0.226
274696ROCKY RD ;4P
Adder
5.796
274695ROCKY RD ;2P
Adder
5.662
274693ROCKY RD ;1P
Adder
5.606
274697ROCKY RD ;3P
Adder
1.538
274683WAUKEGAN ;8U
Adder
10.676
274683WAUKEGAN ;8U
Adder
8.999
962691AG1-118 GEN
Solar/Wind Harmer
15.164
958481AF2-142 GEN
Solar/Wind Harmer
7.567
24721805FLATG3
50/50
1.059
962761AG1-125 GEN
Solar/Wind Harmer
77.959
970149AG2-104 GEN
Solar/Wind Harmer
48.14
970155AG2-107 GEN
Solar/Wind Harmer
33.994
972207SS24-0001
Solar/Wind Harmer
11.9
274773LINCOLN ;4U
Adder
3.347
274774LINCOLN ;5U
Adder
3.347
274723RIVER EC ;12
Adder
9.347
941551AE2-152 GEN
Solar/Wind Harmer
2.353
274802UNIV PARK;5U
Adder
3.023
274812UNIV PK N;8U
Adder
2.595
274751CRETE EC ;1U
Adder
2.529
274754CRETE EC ;4U
Adder
2.529
274676JOLIET 29;8U
Adder
15.857
274871GR RIDGE ;2U
Solar/Wind Harmer
3.969
274847GR RIDGE ;BU
Solar/Wind Harmer
2.61
24721605FLATG1
50/50
1.059
274775LINCOLN ;6U
Adder
3.347
274776LINCOLN ;7U
Adder
3.347
274777LINCOLN ;8U
Adder
3.347
960681AF2-359 GEN
Solar/Wind Harmer
1.983
972228AH1-698 GEN2
Adder
1.927
972227AH1-698 GEN1
Adder
1.357
960591AF2-350 GEN
Solar/Wind Harmer
5.195
274827FISK ;RP
Adder
4.028
274800UNIV PARK;3U
Adder
3.025
274801UNIV PARK;4U
Adder
3.025
972037AH1-567 GEN1
Adder
0.095
274687WILL CNTY;4U
Adder
14.443
274687WILL CNTY;4U
Adder
14.443
274675JOLIET 29;7U
Adder
15.857
274675JOLIET 29;7U
Adder
15.291
970833AG2-524 GEN
Solar/Wind Harmer
4.507
970833AG2-524 GEN
Solar/Wind Harmer
2.096
274728ELWOOD EC;5P
Adder
8.47
274731ELWOOD EC;2P
Adder
8.47
274733ELWOOD EC;3P
Adder
8.47
274735ELWOOD EC;4P
Adder
8.47
276893AG1-478 C
Solar/Wind Harmer
0.283
274744AC1-111 GEN8
Adder
2.876
274746AC1-111 G10
Adder
2.876
270526AF1-158 GEN
Solar/Wind Harmer
2.302
971771AH1-392 GEN
Solar/Wind Harmer
4.511
970073AG2-061 GEN
Solar/Wind Harmer
1.16
971675AH1-338 GEN
Solar/Wind Harmer
8.972
276861AD2-134 GEN
Solar/Wind Harmer
0.89
276863AD2-134 GEN
Solar/Wind Harmer
0.89
971411AH1-196 GEN
Solar/Wind Harmer
7.473
971171AH1-044 GEN
Solar/Wind Harmer
9.903
274823ROCKFORD ;21
Adder
9.617
276889AE2-281 GEN
Solar/Wind Harmer
0.941
274863CRW1-WTG
Solar/Wind Harmer
2.738
274864CRW2-WTG
Solar/Wind Harmer
2.738
274856ECOGROVE ;U1
Solar/Wind Harmer
1.653
276611AD2-172 GEN
Solar/Wind Harmer
1.254
276612AE2-035 GEN
Solar/Wind Harmer
1.254
971681AH1-341 GEN
Solar/Wind Harmer
7.308
926823AC1-168 GEN
Solar/Wind Harmer
2.087
970169AG2-114 GEN
Solar/Wind Harmer
4.82
972267AH1-718 GEN
Adder
2.001
276741O09 GEN1
Solar/Wind Harmer
1.711
958391AF2-133 GEN
Solar/Wind Harmer
4.297
274877BISHOP HL;1U
Solar/Wind Harmer
1.594
959141AF2-205 GEN
Solar/Wind Harmer
2.842
270223U2-072_GEN1
Solar/Wind Helper
1.536
270224U2-072_GEN2
Solar/Wind Helper
1.536
270227U2-072_GEN3
Solar/Wind Helper
1.536
270228U2-072_GEN4
Solar/Wind Helper
1.536
270231U2-072_GEN5
Solar/Wind Helper
1.536
241973AD2-163_GEN1
Solar/Wind Helper
2.443
241974AD2-163_GEN2
Solar/Wind Helper
2.443
241955AC1-078 GEN
Solar/Wind Helper
2.437
945631AF1-228 GEN
Solar/Wind Helper
1.903
966831AG1-554 GEN
Solar/Wind Helper
0.87
253338AC1-165 GEN
Solar/Wind Helper
0.848
253343AC1-166 GEN
Solar/Wind Helper
0.848
241972AD1-140 GEN
Solar/Wind Helper
3.155
945641AF1-229 GEN
Solar/Wind Helper
1.107
270499AE1-146 GEN
Solar/Wind Helper
1.907
270263AC1-001 GEN
Solar/Wind Helper
0.555
270340AC2-060 GEN
Solar/Wind Helper
0.994
960751AF2-366 GEN
Solar/Wind Harmer
1.447
958491AF2-143 GEN
Solar/Wind Harmer
7.479
276901AD2-066 C O1
Solar/Wind Harmer
1.748
971341AH1-150 GEN
Solar/Wind Harmer
9.903
971343AH1-151 GEN
Solar/Wind Harmer
9.903
972235AH1-702 GEN1
Adder
1.241
972236AH1-702 GEN2
Adder
1.079
276872AE1-163_GEN1
Solar/Wind Harmer
3.294
276876AE1-163_GEN2
Solar/Wind Harmer
3.294
270535AF1-215 GEN1
Solar/Wind Harmer
2.214
270536AF1-215 GEN2
Solar/Wind Harmer
2.214
938861AE1-114 GEN
Solar/Wind Harmer
3.993
274764LEE CO EC;5U
Adder
4.526
274765LEE CO EC;6U
Adder
4.526
274762LEE CO EC;3U
Adder
4.515
274763LEE CO EC;4U
Adder
4.473
276158O29GEN2
Solar/Wind Harmer
2.396
276157O29GEN1
Solar/Wind Harmer
1.821
276645AC1-214 GEN1
Solar/Wind Harmer
0.636
247620Y3-023
Adder
0.204
270349AD2-093_GEN
Solar/Wind Helper
4.707
270471AD2-092_GEN
Solar/Wind Helper
4.707
270462AD2-086
Solar/Wind Helper
5.396
253383AE2-342_GEN
Solar/Wind Helper
1.129
946101AF1-275 GEN
Solar/Wind Helper
0.801
241960AC2-195 GEN
Solar/Wind Helper
1.856
270054AF2-122 C O1
Solar/Wind Helper
1.472
24722005FLATG5
50/50
1.059
24721905FLATG4
50/50
19.344
962771AG1-126 GEN
Solar/Wind Harmer
77.959
970153AG2-106 GEN
Solar/Wind Harmer
33.994
971347AH1-153 GEN
Solar/Wind Harmer
2.892
274772LINCOLN ;3U
Adder
3.347
970707AG2-453 GEN
Solar/Wind Harmer
14.782
972259AH1-714 GEN
Adder
9.982
276164X3-005 C
Solar/Wind Harmer
0.367
274724RIVER EC ;11
Adder
9.243
274887GEN-1.85
Solar/Wind Harmer
2.768
276772AC2-154 GEN
Solar/Wind Harmer
1.45
276843GEN-1.7
Solar/Wind Harmer
0.298
276806AD2-047 C O1
Solar/Wind Harmer
5.557
274826FISK ;BP
Adder
5.683
939351AE1-166 GEN
Solar/Wind Harmer
3.077
972038AH1-567 GEN2
Adder
0.189
274803UNIV PARK;6U
Adder
3.023
274814UNIV PK N;0U
Adder
2.617
274807UNIV PK N;3U
Adder
2.612
274811UNIV PK N;7U
Adder
2.595
972231SS25-0005
Solar/Wind Harmer
4.911
972181SS23-001
Solar/Wind Harmer
3.069
274752CRETE EC ;2U
Adder
2.529
274753CRETE EC ;3U
Adder
2.529
274676JOLIET 29;8U
Adder
15.29
943121AE2-341 GEN
Solar/Wind Harmer
7.744
943591AF1-030 GEN
Solar/Wind Harmer
5.163
274729ELWOOD EC;1P
Adder
8.47
274730ELWOOD EC;6P
Adder
8.47
274734ELWOOD EC;8P
Adder
8.47
274736ELWOOD EC;9P
Adder
8.47
24441505OLIV SLR
Solar/Wind Harmer
0.068
274682WAUKEGAN ;7U
Adder
9.116
274862TOP CROP ;2U
Solar/Wind Harmer
2.55
276799AD1-013 GEN
Solar/Wind Harmer
1.102
946671AF1-331 GEN
Solar/Wind Harmer
0.209
274855GSG-6 ;RU
Solar/Wind Harmer
1.84
274850MENDOTA H;RU
Solar/Wind Harmer
1.279
276602WESTBROOK C
Solar/Wind Harmer
1.059
276868AE1-113 GEN
Solar/Wind Harmer
5.028
274879MINONK ;1U
Solar/Wind Harmer
3.352
959091AF2-200 GEN
Solar/Wind Harmer
9.903
247643Z2-116 C
Solar/Wind Harmer
0.034
274857EASY ROAD;U1
Solar/Wind Harmer
2.325
274760LEE CO EC;1U
Adder
4.515
274767LEE CO EC;8U
Adder
4.462
970571AG2-364 GEN
Solar/Wind Harmer
9.7
276603SUBLETTE C
Solar/Wind Harmer
0.508
270505AE1-170 C O1
Solar/Wind Harmer
7.217
964401AG1-302 GEN
Solar/Wind Harmer
4.341
274851PROVIDENC;RU
Solar/Wind Harmer
1.352
274849CRESCENT ;1U
Solar/Wind Harmer
0.877
276782AC1-033 GEN
Solar/Wind Harmer
1.884
274878BISHOP HL;2U
Solar/Wind Harmer
1.594
945111AF1-176 GEN
Solar/Wind Harmer
2.663
270284AF1-227 GEN1
Solar/Wind Helper
6.406
270287AF1-227 GEN3
Solar/Wind Helper
2.349
942871AE2-306 GEN
Solar/Wind Helper
0.78
276820AF1-078_GEN
Solar/Wind Helper
0.621
270518AE2-148 GEN
Solar/Wind Helper
10.848
960801AF2-371 GEN
Solar/Wind Helper
0.869
964871AG1-351 GEN
Solar/Wind Helper
0.6
253325AC1-069 GEN
Solar/Wind Helper
0.879
270541AE2-072 C
Solar/Wind Helper
1.129
253378AE2-206_GEN
Solar/Wind Helper
1.33
247522W1-056 GEN
Solar/Wind Helper
1.168
253415AE1-040 GEN
Solar/Wind Helper
0.468
253349AC2-067 GEN
Solar/Wind Helper
0.175
253400AC2-068 GEN
Solar/Wind Helper
0.07
961051AF2-396 GEN
Solar/Wind Harmer
7.243
961051AF2-396 GEN
Solar/Wind Harmer
3.369
274674JOLIET 9 ;6U
Adder
7.946
274732ELWOOD EC;7P
Adder
8.47
274745AC1-111 GEN9
Adder
2.876
274682WAUKEGAN ;7U
Adder
9.116
274828WAUKEGAN ;BP
Adder
5.596
276694AA1-018 GEN2
Solar/Wind Harmer
3.183
276691AA1-018 GEN1
Solar/Wind Harmer
0.38
962781AG1-127 GEN
Solar/Wind Harmer
4.796
274861TOP CROP ;1U
Solar/Wind Harmer
3.054
274872LEEDK;1U
Solar/Wind Harmer
4.131
939401AE1-172 GEN
Solar/Wind Harmer
6.953
276805AD2-038 GEN
Solar/Wind Harmer
2.557
971997AH1-543 GEN
Solar/Wind Harmer
7.825
970373AG2-245 GEN
Solar/Wind Harmer
10.44
276882AE2-255 GEN
Solar/Wind Harmer
1.676
957471AF2-041 GEN
Solar/Wind Harmer
14.855
959081AF2-199 GEN
Solar/Wind Harmer
4.952
971067AG2-660 GEN
Solar/Wind Harmer
1.152
274822ROCKFORD ;11
Adder
9.687
970819AG2-516 GEN
Solar/Wind Harmer
5.891
270055AF2-134 C O1
Solar/Wind Harmer
1.476
274858EASY ROAD;U2
Solar/Wind Harmer
2.325
274761LEE CO EC;2U
Adder
4.515
274766LEE CO EC;7U
Adder
4.462
970569AG2-363 GEN
Solar/Wind Harmer
14.55
270216AD2-079_GEN
Solar/Wind Harmer
0.292
957891AF2-083 GEN
Solar/Wind Harmer
7.184
958381AF2-132 GEN
Solar/Wind Harmer
4.341
276708O09 GEN2
Solar/Wind Harmer
1.711
964861AG1-349 GEN
Solar/Wind Harmer
3.755
971917AH1-482 GEN
Solar/Wind Harmer
4.332
276646AC1-214 GEN2
Solar/Wind Harmer
0.636
945111AF1-176 GEN
Solar/Wind Harmer
8.403
274848CAMPGROVE;RU
Solar/Wind Harmer
3.037
24639705ELKHART HY
Adder
0.071
270286AF1-227 GEN2
Solar/Wind Helper
2.349
270391AF1-285 GEN3
Solar/Wind Helper
1.04
270578AF1-285 GEN2
Solar/Wind Helper
1.04
270317AD1-130_GEN
Solar/Wind Helper
5.965
270485AE1-090_GEN
Solar/Wind Helper
0.469
270520AE2-214 GEN
Solar/Wind Helper
3.202
253333AC1-068 GEN
Solar/Wind Helper
0.879
960841AF2-375 GEN
Solar/Wind Helper
1.16
270273AD2-016 GEN
Solar/Wind Helper
1.703
270297AD1-101 GEN
Solar/Wind Helper
0.213
958961AF2-187 GEN
Solar/Wind Helper
1.122
241840AF1-064_GEN
Solar/Wind Helper
0.483
241807AE2-176_GEN
Solar/Wind Helper
0.703
960071AF2-298 GEN
Solar/Wind Helper
0.328
CPLELTFEXP_CPLE->PJM
CLTF
1.537
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.741
NYPJM->LTFIMP_NY
CLTF
0.904
LGEELTFEXP_LGEE->PJM
CLTF
0.828
WECLTFEXP_WEC->PJM
CLTF
1.878
AG2-052LTFEXP_AG2-052->PJM
LTF
0.112
AH1-155LTFEXP_AH1-155->PJM
LTF
0.168
LAGNLTFEXP_LAGN->PJM
CLTF
5.458
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.254
TVALTFEXP_TVA->PJM
CLTF
2.431
CBM West 1LTFEXP_CBM-W1->PJM
CBM
42.496
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.299
MECLTFEXP_MEC->PJM
CLTF
7.056
SIGELTFEXP_SIGE->PJM
CLTF
0.115

Details for 05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#9730_05MALIS 138_P1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
Contingency Name:
AEP_P4_#9730_05MALIS 138_P1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.26 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3321.72
MW Contribution:
48.14
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
1.059
274775LINCOLN ;6U
Adder
3.347
274776LINCOLN ;7U
Adder
3.347
274777LINCOLN ;8U
Adder
3.347
960681AF2-359 GEN
Solar/Wind Harmer
1.982
972228AH1-698 GEN2
Adder
1.927
972227AH1-698 GEN1
Adder
1.357
960591AF2-350 GEN
Solar/Wind Harmer
5.194
274827FISK ;RP
Adder
4.028
274800UNIV PARK;3U
Adder
3.025
274801UNIV PARK;4U
Adder
3.025
972037AH1-567 GEN1
Adder
0.095
274687WILL CNTY;4U
Adder
14.442
274687WILL CNTY;4U
Adder
14.442
274675JOLIET 29;7U
Adder
15.856
274675JOLIET 29;7U
Adder
15.29
970833AG2-524 GEN
Solar/Wind Harmer
4.507
970833AG2-524 GEN
Solar/Wind Harmer
2.096
274728ELWOOD EC;5P
Adder
8.469
274731ELWOOD EC;2P
Adder
8.469
274733ELWOOD EC;3P
Adder
8.469
274735ELWOOD EC;4P
Adder
8.469
276893AG1-478 C
Solar/Wind Harmer
0.283
274744AC1-111 GEN8
Adder
2.876
24721705FLATG2
50/50
15.727
970349AG2-230 GEN
Solar/Wind Harmer
8.676
274770LINCOLN ;1U
Adder
3.347
274771LINCOLN ;2U
Adder
3.347
965681AG1-436 GEN
Solar/Wind Harmer
6.558
965791AG1-447 GEN
Solar/Wind Harmer
3.355
274888KELLY CRK;1U
Solar/Wind Harmer
3.065
276776AD2-060 GEN
Solar/Wind Harmer
0.217
958011AF2-095 GEN
Solar/Wind Harmer
7.48
970941AG2-585 GEN
Solar/Wind Harmer
2.857
276897AD1-100 C
Solar/Wind Harmer
24.103
274805UNIV PK N;1U
Adder
2.6
274808UNIV PK N;4U
Adder
2.583
274674JOLIET 9 ;6U
Adder
7.946
276893AG1-478 C
Solar/Wind Harmer
0.226
274695ROCKY RD ;2P
Adder
5.662
274693ROCKY RD ;1P
Adder
5.606
274697ROCKY RD ;3P
Adder
1.538
274696ROCKY RD ;4P
Adder
5.795
274683WAUKEGAN ;8U
Adder
10.675
274683WAUKEGAN ;8U
Adder
8.999
962691AG1-118 GEN
Solar/Wind Harmer
15.163
958481AF2-142 GEN
Solar/Wind Harmer
7.566
960751AF2-366 GEN
Solar/Wind Harmer
1.447
958491AF2-143 GEN
Solar/Wind Harmer
7.479
276901AD2-066 C O1
Solar/Wind Harmer
1.748
971341AH1-150 GEN
Solar/Wind Harmer
9.902
971343AH1-151 GEN
Solar/Wind Harmer
9.902
972235AH1-702 GEN1
Adder
1.241
972236AH1-702 GEN2
Adder
1.079
276872AE1-163_GEN1
Solar/Wind Harmer
3.294
276876AE1-163_GEN2
Solar/Wind Harmer
3.294
270535AF1-215 GEN1
Solar/Wind Harmer
2.213
270536AF1-215 GEN2
Solar/Wind Harmer
2.213
938861AE1-114 GEN
Solar/Wind Harmer
3.992
274764LEE CO EC;5U
Adder
4.526
274765LEE CO EC;6U
Adder
4.526
274762LEE CO EC;3U
Adder
4.515
274763LEE CO EC;4U
Adder
4.472
276158O29GEN2
Solar/Wind Harmer
2.396
276157O29GEN1
Solar/Wind Harmer
1.821
276645AC1-214 GEN1
Solar/Wind Harmer
0.636
274746AC1-111 G10
Adder
2.876
270526AF1-158 GEN
Solar/Wind Harmer
2.302
971771AH1-392 GEN
Solar/Wind Harmer
4.511
970073AG2-061 GEN
Solar/Wind Harmer
1.16
971675AH1-338 GEN
Solar/Wind Harmer
8.971
276861AD2-134 GEN
Solar/Wind Harmer
0.89
276863AD2-134 GEN
Solar/Wind Harmer
0.89
971411AH1-196 GEN
Solar/Wind Harmer
7.473
971171AH1-044 GEN
Solar/Wind Harmer
9.902
274823ROCKFORD ;21
Adder
9.616
276889AE2-281 GEN
Solar/Wind Harmer
0.941
274863CRW1-WTG
Solar/Wind Harmer
2.737
274864CRW2-WTG
Solar/Wind Harmer
2.737
274856ECOGROVE ;U1
Solar/Wind Harmer
1.653
276611AD2-172 GEN
Solar/Wind Harmer
1.254
276612AE2-035 GEN
Solar/Wind Harmer
1.254
971681AH1-341 GEN
Solar/Wind Harmer
7.307
926823AC1-168 GEN
Solar/Wind Harmer
2.087
970169AG2-114 GEN
Solar/Wind Harmer
4.819
972267AH1-718 GEN
Adder
2.001
276741O09 GEN1
Solar/Wind Harmer
1.71
958391AF2-133 GEN
Solar/Wind Harmer
4.297
274877BISHOP HL;1U
Solar/Wind Harmer
1.594
959141AF2-205 GEN
Solar/Wind Harmer
2.842
270223U2-072_GEN1
Solar/Wind Helper
1.536
270224U2-072_GEN2
Solar/Wind Helper
1.536
270227U2-072_GEN3
Solar/Wind Helper
1.536
270228U2-072_GEN4
Solar/Wind Helper
1.536
270231U2-072_GEN5
Solar/Wind Helper
1.536
241973AD2-163_GEN1
Solar/Wind Helper
2.443
241974AD2-163_GEN2
Solar/Wind Helper
2.443
241955AC1-078 GEN
Solar/Wind Helper
2.437
945631AF1-228 GEN
Solar/Wind Helper
1.903
966831AG1-554 GEN
Solar/Wind Helper
0.87
253338AC1-165 GEN
Solar/Wind Helper
0.848
253343AC1-166 GEN
Solar/Wind Helper
0.848
241972AD1-140 GEN
Solar/Wind Helper
3.156
945641AF1-229 GEN
Solar/Wind Helper
1.107
270499AE1-146 GEN
Solar/Wind Helper
1.907
270263AC1-001 GEN
Solar/Wind Helper
0.555
270340AC2-060 GEN
Solar/Wind Helper
0.994
24721805FLATG3
50/50
1.059
962761AG1-125 GEN
Solar/Wind Harmer
77.957
970149AG2-104 GEN
Solar/Wind Harmer
48.139
970155AG2-107 GEN
Solar/Wind Harmer
33.993
972207SS24-0001
Solar/Wind Harmer
11.899
274773LINCOLN ;4U
Adder
3.347
274774LINCOLN ;5U
Adder
3.347
274723RIVER EC ;12
Adder
9.346
941551AE2-152 GEN
Solar/Wind Harmer
2.353
274802UNIV PARK;5U
Adder
3.023
274812UNIV PK N;8U
Adder
2.594
274751CRETE EC ;1U
Adder
2.529
274754CRETE EC ;4U
Adder
2.529
274676JOLIET 29;8U
Adder
15.856
274871GR RIDGE ;2U
Solar/Wind Harmer
3.969
274847GR RIDGE ;BU
Solar/Wind Harmer
2.61
274674JOLIET 9 ;6U
Adder
7.946
274732ELWOOD EC;7P
Adder
8.469
274745AC1-111 GEN9
Adder
2.876
274682WAUKEGAN ;7U
Adder
9.115
274828WAUKEGAN ;BP
Adder
5.596
276694AA1-018 GEN2
Solar/Wind Harmer
3.183
276691AA1-018 GEN1
Solar/Wind Harmer
0.38
962781AG1-127 GEN
Solar/Wind Harmer
4.795
274861TOP CROP ;1U
Solar/Wind Harmer
3.053
274872LEEDK;1U
Solar/Wind Harmer
4.13
939401AE1-172 GEN
Solar/Wind Harmer
6.952
276805AD2-038 GEN
Solar/Wind Harmer
2.557
970373AG2-245 GEN
Solar/Wind Harmer
10.439
971997AH1-543 GEN
Solar/Wind Harmer
7.825
276882AE2-255 GEN
Solar/Wind Harmer
1.676
957471AF2-041 GEN
Solar/Wind Harmer
14.854
959081AF2-199 GEN
Solar/Wind Harmer
4.951
971067AG2-660 GEN
Solar/Wind Harmer
1.151
274822ROCKFORD ;11
Adder
9.686
970819AG2-516 GEN
Solar/Wind Harmer
5.891
270055AF2-134 C O1
Solar/Wind Harmer
1.476
274858EASY ROAD;U2
Solar/Wind Harmer
2.325
274761LEE CO EC;2U
Adder
4.515
274766LEE CO EC;7U
Adder
4.462
970569AG2-363 GEN
Solar/Wind Harmer
14.549
270216AD2-079_GEN
Solar/Wind Harmer
0.292
957891AF2-083 GEN
Solar/Wind Harmer
7.183
958381AF2-132 GEN
Solar/Wind Harmer
4.341
276708O09 GEN2
Solar/Wind Harmer
1.71
964861AG1-349 GEN
Solar/Wind Harmer
3.754
971917AH1-482 GEN
Solar/Wind Harmer
4.332
276646AC1-214 GEN2
Solar/Wind Harmer
0.636
945111AF1-176 GEN
Solar/Wind Harmer
8.402
274848CAMPGROVE;RU
Solar/Wind Harmer
3.036
24639705ELKHART HY
Adder
0.071
270286AF1-227 GEN2
Solar/Wind Helper
2.349
270391AF1-285 GEN3
Solar/Wind Helper
1.04
247620Y3-023
Adder
0.204
270349AD2-093_GEN
Solar/Wind Helper
4.707
270471AD2-092_GEN
Solar/Wind Helper
4.707
270462AD2-086
Solar/Wind Helper
5.396
253383AE2-342_GEN
Solar/Wind Helper
1.129
946101AF1-275 GEN
Solar/Wind Helper
0.801
241960AC2-195 GEN
Solar/Wind Helper
1.856
270054AF2-122 C O1
Solar/Wind Helper
1.471
253378AE2-206_GEN
Solar/Wind Helper
1.33
247522W1-056 GEN
Solar/Wind Helper
1.168
253415AE1-040 GEN
Solar/Wind Helper
0.468
253349AC2-067 GEN
Solar/Wind Helper
0.175
253400AC2-068 GEN
Solar/Wind Helper
0.07
961051AF2-396 GEN
Solar/Wind Harmer
7.242
961051AF2-396 GEN
Solar/Wind Harmer
3.368
24722005FLATG5
50/50
1.059
24721905FLATG4
50/50
19.344
962771AG1-126 GEN
Solar/Wind Harmer
77.957
970153AG2-106 GEN
Solar/Wind Harmer
33.993
971347AH1-153 GEN
Solar/Wind Harmer
2.892
274772LINCOLN ;3U
Adder
3.347
970707AG2-453 GEN
Solar/Wind Harmer
14.781
972259AH1-714 GEN
Adder
9.981
276164X3-005 C
Solar/Wind Harmer
0.367
274724RIVER EC ;11
Adder
9.242
274887GEN-1.85
Solar/Wind Harmer
2.767
276772AC2-154 GEN
Solar/Wind Harmer
1.45
276843GEN-1.7
Solar/Wind Harmer
0.298
276806AD2-047 C O1
Solar/Wind Harmer
5.557
274826FISK ;BP
Adder
5.683
939351AE1-166 GEN
Solar/Wind Harmer
3.077
972038AH1-567 GEN2
Adder
0.189
274803UNIV PARK;6U
Adder
3.023
274814UNIV PK N;0U
Adder
2.617
274807UNIV PK N;3U
Adder
2.611
274811UNIV PK N;7U
Adder
2.594
972231SS25-0005
Solar/Wind Harmer
4.91
972181SS23-001
Solar/Wind Harmer
3.069
274752CRETE EC ;2U
Adder
2.529
274753CRETE EC ;3U
Adder
2.529
274676JOLIET 29;8U
Adder
15.289
943121AE2-341 GEN
Solar/Wind Harmer
7.743
943591AF1-030 GEN
Solar/Wind Harmer
5.162
274729ELWOOD EC;1P
Adder
8.469
274730ELWOOD EC;6P
Adder
8.469
274734ELWOOD EC;8P
Adder
8.469
274736ELWOOD EC;9P
Adder
8.469
24441505OLIV SLR
Solar/Wind Harmer
0.068
274682WAUKEGAN ;7U
Adder
9.115
274862TOP CROP ;2U
Solar/Wind Harmer
2.549
276799AD1-013 GEN
Solar/Wind Harmer
1.102
946671AF1-331 GEN
Solar/Wind Harmer
0.209
274855GSG-6 ;RU
Solar/Wind Harmer
1.84
274850MENDOTA H;RU
Solar/Wind Harmer
1.279
276602WESTBROOK C
Solar/Wind Harmer
1.059
276868AE1-113 GEN
Solar/Wind Harmer
5.028
274879MINONK ;1U
Solar/Wind Harmer
3.352
959091AF2-200 GEN
Solar/Wind Harmer
9.902
247643Z2-116 C
Solar/Wind Harmer
0.034
274857EASY ROAD;U1
Solar/Wind Harmer
2.325
274760LEE CO EC;1U
Adder
4.515
274767LEE CO EC;8U
Adder
4.462
970571AG2-364 GEN
Solar/Wind Harmer
9.7
276603SUBLETTE C
Solar/Wind Harmer
0.508
270505AE1-170 C O1
Solar/Wind Harmer
7.217
964401AG1-302 GEN
Solar/Wind Harmer
4.341
274851PROVIDENC;RU
Solar/Wind Harmer
1.352
274849CRESCENT ;1U
Solar/Wind Harmer
0.877
276782AC1-033 GEN
Solar/Wind Harmer
1.884
274878BISHOP HL;2U
Solar/Wind Harmer
1.594
945111AF1-176 GEN
Solar/Wind Harmer
2.663
270284AF1-227 GEN1
Solar/Wind Helper
6.406
270287AF1-227 GEN3
Solar/Wind Helper
2.349
942871AE2-306 GEN
Solar/Wind Helper
0.78
276820AF1-078_GEN
Solar/Wind Helper
0.621
270518AE2-148 GEN
Solar/Wind Helper
10.849
960801AF2-371 GEN
Solar/Wind Helper
0.869
964871AG1-351 GEN
Solar/Wind Helper
0.6
253325AC1-069 GEN
Solar/Wind Helper
0.879
270541AE2-072 C
Solar/Wind Helper
1.129
960071AF2-298 GEN
Solar/Wind Helper
0.328
270578AF1-285 GEN2
Solar/Wind Helper
1.04
270317AD1-130_GEN
Solar/Wind Helper
5.966
270485AE1-090_GEN
Solar/Wind Helper
0.469
270520AE2-214 GEN
Solar/Wind Helper
3.203
253333AC1-068 GEN
Solar/Wind Helper
0.879
960841AF2-375 GEN
Solar/Wind Helper
1.16
270273AD2-016 GEN
Solar/Wind Helper
1.703
270297AD1-101 GEN
Solar/Wind Helper
0.213
958961AF2-187 GEN
Solar/Wind Helper
1.122
241840AF1-064_GEN
Solar/Wind Helper
0.483
241807AE2-176_GEN
Solar/Wind Helper
0.703
CPLELTFEXP_CPLE->PJM
CLTF
1.537
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.738
NYPJM->LTFIMP_NY
CLTF
0.904
LGEELTFEXP_LGEE->PJM
CLTF
0.828
WECLTFEXP_WEC->PJM
CLTF
1.878
AG2-052LTFEXP_AG2-052->PJM
LTF
0.112
AH1-155LTFEXP_AH1-155->PJM
LTF
0.168
LAGNLTFEXP_LAGN->PJM
CLTF
5.458
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.253
TVALTFEXP_TVA->PJM
CLTF
2.431
CBM West 1LTFEXP_CBM-W1->PJM
CBM
42.492
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.298
MECLTFEXP_MEC->PJM
CLTF
7.055
SIGELTFEXP_SIGE->PJM
CLTF
0.115

Details for 05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#9728_05MALIS 138_L1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
Contingency Name:
AEP_P4_#9728_05MALIS 138_L1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.23 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3320.78
MW Contribution:
48.13
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
1.059
274775LINCOLN ;6U
Adder
3.346
274776LINCOLN ;7U
Adder
3.346
274777LINCOLN ;8U
Adder
3.346
960681AF2-359 GEN
Solar/Wind Harmer
1.982
972228AH1-698 GEN2
Adder
1.926
972227AH1-698 GEN1
Adder
1.356
960591AF2-350 GEN
Solar/Wind Harmer
5.193
274827FISK ;RP
Adder
4.026
274800UNIV PARK;3U
Adder
3.024
274801UNIV PARK;4U
Adder
3.024
972037AH1-567 GEN1
Adder
0.095
274675JOLIET 29;7U
Adder
15.851
274675JOLIET 29;7U
Adder
15.285
274687WILL CNTY;4U
Adder
14.438
274687WILL CNTY;4U
Adder
14.438
970833AG2-524 GEN
Solar/Wind Harmer
4.506
970833AG2-524 GEN
Solar/Wind Harmer
2.096
274728ELWOOD EC;5P
Adder
8.467
274731ELWOOD EC;2P
Adder
8.467
274733ELWOOD EC;3P
Adder
8.467
274735ELWOOD EC;4P
Adder
8.467
276893AG1-478 C
Solar/Wind Harmer
0.283
274744AC1-111 GEN8
Adder
2.875
274746AC1-111 G10
Adder
2.875
270526AF1-158 GEN
Solar/Wind Harmer
2.301
971771AH1-392 GEN
Solar/Wind Harmer
4.509
970073AG2-061 GEN
Solar/Wind Harmer
1.159
971675AH1-338 GEN
Solar/Wind Harmer
8.968
276861AD2-134 GEN
Solar/Wind Harmer
0.889
276863AD2-134 GEN
Solar/Wind Harmer
0.889
971411AH1-196 GEN
Solar/Wind Harmer
7.471
971171AH1-044 GEN
Solar/Wind Harmer
9.899
274823ROCKFORD ;21
Adder
9.613
276889AE2-281 GEN
Solar/Wind Harmer
0.941
274863CRW1-WTG
Solar/Wind Harmer
2.737
274864CRW2-WTG
Solar/Wind Harmer
2.737
274856ECOGROVE ;U1
Solar/Wind Harmer
1.652
276611AD2-172 GEN
Solar/Wind Harmer
1.253
276612AE2-035 GEN
Solar/Wind Harmer
1.253
971681AH1-341 GEN
Solar/Wind Harmer
7.305
926823AC1-168 GEN
Solar/Wind Harmer
2.086
970169AG2-114 GEN
Solar/Wind Harmer
4.818
24721705FLATG2
50/50
15.726
970349AG2-230 GEN
Solar/Wind Harmer
8.674
274770LINCOLN ;1U
Adder
3.346
274771LINCOLN ;2U
Adder
3.346
965681AG1-436 GEN
Solar/Wind Harmer
6.556
965791AG1-447 GEN
Solar/Wind Harmer
3.354
274888KELLY CRK;1U
Solar/Wind Harmer
3.064
276776AD2-060 GEN
Solar/Wind Harmer
0.217
958011AF2-095 GEN
Solar/Wind Harmer
7.477
970941AG2-585 GEN
Solar/Wind Harmer
2.856
276897AD1-100 C
Solar/Wind Harmer
24.095
274805UNIV PK N;1U
Adder
2.599
274808UNIV PK N;4U
Adder
2.582
274674JOLIET 9 ;6U
Adder
7.943
276893AG1-478 C
Solar/Wind Harmer
0.226
274696ROCKY RD ;4P
Adder
5.794
274695ROCKY RD ;2P
Adder
5.66
274693ROCKY RD ;1P
Adder
5.604
274697ROCKY RD ;3P
Adder
1.538
274683WAUKEGAN ;8U
Adder
10.672
274683WAUKEGAN ;8U
Adder
8.996
962691AG1-118 GEN
Solar/Wind Harmer
15.159
958481AF2-142 GEN
Solar/Wind Harmer
7.564
960751AF2-366 GEN
Solar/Wind Harmer
1.446
958491AF2-143 GEN
Solar/Wind Harmer
7.477
276901AD2-066 C O1
Solar/Wind Harmer
1.747
971341AH1-150 GEN
Solar/Wind Harmer
9.899
971343AH1-151 GEN
Solar/Wind Harmer
9.899
972235AH1-702 GEN1
Adder
1.241
972236AH1-702 GEN2
Adder
1.079
276872AE1-163_GEN1
Solar/Wind Harmer
3.293
276876AE1-163_GEN2
Solar/Wind Harmer
3.293
270535AF1-215 GEN1
Solar/Wind Harmer
2.213
270536AF1-215 GEN2
Solar/Wind Harmer
2.213
938861AE1-114 GEN
Solar/Wind Harmer
3.991
274764LEE CO EC;5U
Adder
4.524
274765LEE CO EC;6U
Adder
4.524
274762LEE CO EC;3U
Adder
4.514
274763LEE CO EC;4U
Adder
4.471
276158O29GEN2
Solar/Wind Harmer
2.395
276157O29GEN1
Solar/Wind Harmer
1.821
276645AC1-214 GEN1
Solar/Wind Harmer
0.635
247620Y3-023
Adder
0.204
270349AD2-093_GEN
Solar/Wind Helper
4.708
270471AD2-092_GEN
Solar/Wind Helper
4.708
270462AD2-086
Solar/Wind Helper
5.397
253383AE2-342_GEN
Solar/Wind Helper
1.129
946101AF1-275 GEN
Solar/Wind Helper
0.801
241960AC2-195 GEN
Solar/Wind Helper
1.856
270054AF2-122 C O1
Solar/Wind Helper
1.47
253378AE2-206_GEN
Solar/Wind Helper
1.33
247522W1-056 GEN
Solar/Wind Helper
1.169
253415AE1-040 GEN
Solar/Wind Helper
0.468
253349AC2-067 GEN
Solar/Wind Helper
0.175
253400AC2-068 GEN
Solar/Wind Helper
0.071
961051AF2-396 GEN
Solar/Wind Harmer
7.24
961051AF2-396 GEN
Solar/Wind Harmer
3.367
972267AH1-718 GEN
Adder
2.001
276741O09 GEN1
Solar/Wind Harmer
1.71
958391AF2-133 GEN
Solar/Wind Harmer
4.295
274877BISHOP HL;1U
Solar/Wind Harmer
1.594
959141AF2-205 GEN
Solar/Wind Harmer
2.841
270223U2-072_GEN1
Solar/Wind Helper
1.537
270224U2-072_GEN2
Solar/Wind Helper
1.537
270227U2-072_GEN3
Solar/Wind Helper
1.537
270228U2-072_GEN4
Solar/Wind Helper
1.537
270231U2-072_GEN5
Solar/Wind Helper
1.537
241973AD2-163_GEN1
Solar/Wind Helper
2.444
241974AD2-163_GEN2
Solar/Wind Helper
2.444
241955AC1-078 GEN
Solar/Wind Helper
2.438
945631AF1-228 GEN
Solar/Wind Helper
1.903
966831AG1-554 GEN
Solar/Wind Helper
0.87
253338AC1-165 GEN
Solar/Wind Helper
0.849
253343AC1-166 GEN
Solar/Wind Helper
0.849
241972AD1-140 GEN
Solar/Wind Helper
3.157
945641AF1-229 GEN
Solar/Wind Helper
1.107
270499AE1-146 GEN
Solar/Wind Helper
1.908
270263AC1-001 GEN
Solar/Wind Helper
0.554
270340AC2-060 GEN
Solar/Wind Helper
0.995
24722005FLATG5
50/50
1.059
24721905FLATG4
50/50
19.342
962771AG1-126 GEN
Solar/Wind Harmer
77.949
970153AG2-106 GEN
Solar/Wind Harmer
33.99
971347AH1-153 GEN
Solar/Wind Harmer
2.891
274772LINCOLN ;3U
Adder
3.346
970707AG2-453 GEN
Solar/Wind Harmer
14.776
972259AH1-714 GEN
Adder
9.978
276164X3-005 C
Solar/Wind Harmer
0.367
274724RIVER EC ;11
Adder
9.24
274887GEN-1.85
Solar/Wind Harmer
2.766
276772AC2-154 GEN
Solar/Wind Harmer
1.449
276843GEN-1.7
Solar/Wind Harmer
0.298
276806AD2-047 C O1
Solar/Wind Harmer
5.555
274826FISK ;BP
Adder
5.681
939351AE1-166 GEN
Solar/Wind Harmer
3.076
972038AH1-567 GEN2
Adder
0.189
274803UNIV PARK;6U
Adder
3.022
274814UNIV PK N;0U
Adder
2.616
274807UNIV PK N;3U
Adder
2.611
274811UNIV PK N;7U
Adder
2.594
972231SS25-0005
Solar/Wind Harmer
4.909
972181SS23-001
Solar/Wind Harmer
3.068
274752CRETE EC ;2U
Adder
2.528
274753CRETE EC ;3U
Adder
2.528
274676JOLIET 29;8U
Adder
15.285
943121AE2-341 GEN
Solar/Wind Harmer
7.741
943591AF1-030 GEN
Solar/Wind Harmer
5.161
274729ELWOOD EC;1P
Adder
8.467
274730ELWOOD EC;6P
Adder
8.467
274734ELWOOD EC;8P
Adder
8.467
274736ELWOOD EC;9P
Adder
8.467
24441505OLIV SLR
Solar/Wind Harmer
0.068
274682WAUKEGAN ;7U
Adder
9.113
274862TOP CROP ;2U
Solar/Wind Harmer
2.549
276799AD1-013 GEN
Solar/Wind Harmer
1.101
946671AF1-331 GEN
Solar/Wind Harmer
0.209
274855GSG-6 ;RU
Solar/Wind Harmer
1.839
274850MENDOTA H;RU
Solar/Wind Harmer
1.279
276602WESTBROOK C
Solar/Wind Harmer
1.059
276868AE1-113 GEN
Solar/Wind Harmer
5.026
274879MINONK ;1U
Solar/Wind Harmer
3.351
959091AF2-200 GEN
Solar/Wind Harmer
9.899
247643Z2-116 C
Solar/Wind Harmer
0.034
274857EASY ROAD;U1
Solar/Wind Harmer
2.324
274760LEE CO EC;1U
Adder
4.514
274767LEE CO EC;8U
Adder
4.46
970571AG2-364 GEN
Solar/Wind Harmer
9.697
276603SUBLETTE C
Solar/Wind Harmer
0.508
270505AE1-170 C O1
Solar/Wind Harmer
7.214
964401AG1-302 GEN
Solar/Wind Harmer
4.34
274851PROVIDENC;RU
Solar/Wind Harmer
1.351
274849CRESCENT ;1U
Solar/Wind Harmer
0.877
276782AC1-033 GEN
Solar/Wind Harmer
1.884
274878BISHOP HL;2U
Solar/Wind Harmer
1.594
945111AF1-176 GEN
Solar/Wind Harmer
2.662
270284AF1-227 GEN1
Solar/Wind Helper
6.407
270287AF1-227 GEN3
Solar/Wind Helper
2.35
942871AE2-306 GEN
Solar/Wind Helper
0.78
276820AF1-078_GEN
Solar/Wind Helper
0.621
270518AE2-148 GEN
Solar/Wind Helper
10.851
960801AF2-371 GEN
Solar/Wind Helper
0.869
964871AG1-351 GEN
Solar/Wind Helper
0.6
253325AC1-069 GEN
Solar/Wind Helper
0.879
270541AE2-072 C
Solar/Wind Helper
1.129
960071AF2-298 GEN
Solar/Wind Helper
0.328
24721805FLATG3
50/50
1.059
962761AG1-125 GEN
Solar/Wind Harmer
77.949
970149AG2-104 GEN
Solar/Wind Harmer
48.134
970155AG2-107 GEN
Solar/Wind Harmer
33.99
972207SS24-0001
Solar/Wind Harmer
11.895
274773LINCOLN ;4U
Adder
3.346
274774LINCOLN ;5U
Adder
3.346
274723RIVER EC ;12
Adder
9.343
941551AE2-152 GEN
Solar/Wind Harmer
2.352
274802UNIV PARK;5U
Adder
3.022
274812UNIV PK N;8U
Adder
2.594
274751CRETE EC ;1U
Adder
2.528
274754CRETE EC ;4U
Adder
2.528
274676JOLIET 29;8U
Adder
15.851
274871GR RIDGE ;2U
Solar/Wind Harmer
3.967
274847GR RIDGE ;BU
Solar/Wind Harmer
2.609
274674JOLIET 9 ;6U
Adder
7.943
274732ELWOOD EC;7P
Adder
8.467
274745AC1-111 GEN9
Adder
2.875
274682WAUKEGAN ;7U
Adder
9.113
274828WAUKEGAN ;BP
Adder
5.594
276694AA1-018 GEN2
Solar/Wind Harmer
3.182
276691AA1-018 GEN1
Solar/Wind Harmer
0.38
962781AG1-127 GEN
Solar/Wind Harmer
4.794
274861TOP CROP ;1U
Solar/Wind Harmer
3.053
274872LEEDK;1U
Solar/Wind Harmer
4.129
939401AE1-172 GEN
Solar/Wind Harmer
6.95
276805AD2-038 GEN
Solar/Wind Harmer
2.556
970373AG2-245 GEN
Solar/Wind Harmer
10.436
971997AH1-543 GEN
Solar/Wind Harmer
7.823
276882AE2-255 GEN
Solar/Wind Harmer
1.676
957471AF2-041 GEN
Solar/Wind Harmer
14.849
959081AF2-199 GEN
Solar/Wind Harmer
4.95
971067AG2-660 GEN
Solar/Wind Harmer
1.151
274822ROCKFORD ;11
Adder
9.684
970819AG2-516 GEN
Solar/Wind Harmer
5.889
270055AF2-134 C O1
Solar/Wind Harmer
1.475
274858EASY ROAD;U2
Solar/Wind Harmer
2.324
274761LEE CO EC;2U
Adder
4.514
274766LEE CO EC;7U
Adder
4.46
970569AG2-363 GEN
Solar/Wind Harmer
14.545
270216AD2-079_GEN
Solar/Wind Harmer
0.292
957891AF2-083 GEN
Solar/Wind Harmer
7.181
958381AF2-132 GEN
Solar/Wind Harmer
4.34
276708O09 GEN2
Solar/Wind Harmer
1.71
964861AG1-349 GEN
Solar/Wind Harmer
3.753
971917AH1-482 GEN
Solar/Wind Harmer
4.33
276646AC1-214 GEN2
Solar/Wind Harmer
0.635
945111AF1-176 GEN
Solar/Wind Harmer
8.399
274848CAMPGROVE;RU
Solar/Wind Harmer
3.035
24639705ELKHART HY
Adder
0.071
270286AF1-227 GEN2
Solar/Wind Helper
2.35
270391AF1-285 GEN3
Solar/Wind Helper
1.04
270578AF1-285 GEN2
Solar/Wind Helper
1.04
270317AD1-130_GEN
Solar/Wind Helper
5.967
270485AE1-090_GEN
Solar/Wind Helper
0.469
270520AE2-214 GEN
Solar/Wind Helper
3.204
253333AC1-068 GEN
Solar/Wind Helper
0.879
960841AF2-375 GEN
Solar/Wind Helper
1.16
270273AD2-016 GEN
Solar/Wind Helper
1.703
270297AD1-101 GEN
Solar/Wind Helper
0.213
958961AF2-187 GEN
Solar/Wind Helper
1.122
241840AF1-064_GEN
Solar/Wind Helper
0.483
241807AE2-176_GEN
Solar/Wind Helper
0.704
CPLELTFEXP_CPLE->PJM
CLTF
1.537
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.723
NYPJM->LTFIMP_NY
CLTF
0.904
LGEELTFEXP_LGEE->PJM
CLTF
0.827
WECLTFEXP_WEC->PJM
CLTF
1.878
AG2-052LTFEXP_AG2-052->PJM
LTF
0.112
AH1-155LTFEXP_AH1-155->PJM
LTF
0.167
LAGNLTFEXP_LAGN->PJM
CLTF
5.456
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.253
TVALTFEXP_TVA->PJM
CLTF
2.43
CBM West 1LTFEXP_CBM-W1->PJM
CBM
42.472
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.295
MECLTFEXP_MEC->PJM
CLTF
7.053
SIGELTFEXP_SIGE->PJM
CLTF
0.115

Details for 05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer l/o AEP_P1-2_#711_6224_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
Contingency Name:
AEP_P1-2_#711_6224_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.73 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3150.57
MW Contribution:
35.64
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721705FLATG2
50/50
15.792
243186AF1-051 GEN
50/50
3.141
970349AG2-230 GEN
Solar/Wind Harmer
6.143
274770LINCOLN ;1U
Adder
4.626
274771LINCOLN ;2U
Adder
4.626
965681AG1-436 GEN
Solar/Wind Harmer
4.649
965791AG1-447 GEN
Solar/Wind Harmer
3.409
274888KELLY CRK;1U
Solar/Wind Harmer
0.215
276776AD2-060 GEN
Solar/Wind Harmer
0.393
958011AF2-095 GEN
Solar/Wind Harmer
5.302
970941AG2-585 GEN
Solar/Wind Harmer
2.025
276897AD1-100 C
Solar/Wind Harmer
9.195
274805UNIV PK N;1U
Adder
2.642
274808UNIV PK N;4U
Adder
2.625
274674JOLIET 9 ;6U
Adder
8.073
276893AG1-478 C
Solar/Wind Harmer
0.243
274696ROCKY RD ;4P
Adder
5.889
274695ROCKY RD ;2P
Adder
5.753
274693ROCKY RD ;1P
Adder
5.697
274697ROCKY RD ;3P
Adder
1.563
274683WAUKEGAN ;8U
Adder
10.848
274683WAUKEGAN ;8U
Adder
9.145
962691AG1-118 GEN
Solar/Wind Harmer
10.751
958481AF2-142 GEN
Solar/Wind Harmer
5.365
958491AF2-143 GEN
Solar/Wind Harmer
5.304
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
7.022
971343AH1-151 GEN
Solar/Wind Harmer
7.022
972235AH1-702 GEN1
Adder
1.262
972236AH1-702 GEN2
Adder
1.097
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
938861AE1-114 GEN
Solar/Wind Harmer
1.957
274764LEE CO EC;5U
Adder
4.601
274765LEE CO EC;6U
Adder
4.601
274762LEE CO EC;3U
Adder
4.59
274763LEE CO EC;4U
Adder
4.547
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.548
276645AC1-214 GEN1
Solar/Wind Harmer
0.132
961051AF2-396 GEN
Solar/Wind Harmer
6.669
961051AF2-396 GEN
Solar/Wind Harmer
4.446
942111AE2-223 GEN
Solar/Wind Harmer
1.065
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
1.072
247620Y3-023
Adder
0.208
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.342
270349AD2-093_GEN
Solar/Wind Helper
4.68
270471AD2-092_GEN
Solar/Wind Helper
4.68
270462AD2-086
Solar/Wind Helper
5.356
253383AE2-342_GEN
Solar/Wind Helper
1.111
946101AF1-275 GEN
Solar/Wind Helper
0.784
241960AC2-195 GEN
Solar/Wind Helper
1.835
270054AF2-122 C O1
Solar/Wind Helper
1.457
253378AE2-206_GEN
Solar/Wind Helper
1.313
24721605FLATG1
50/50
1.063
274775LINCOLN ;6U
Adder
4.626
274776LINCOLN ;7U
Adder
4.626
274777LINCOLN ;8U
Adder
4.626
960681AF2-359 GEN
Solar/Wind Harmer
0
972228AH1-698 GEN2
Adder
1.958
972227AH1-698 GEN1
Adder
1.378
960591AF2-350 GEN
Solar/Wind Harmer
3.682
274827FISK ;RP
Adder
4.092
274800UNIV PARK;3U
Adder
3.073
274801UNIV PARK;4U
Adder
3.073
972037AH1-567 GEN1
Adder
0.096
274687WILL CNTY;4U
Adder
14.674
274687WILL CNTY;4U
Adder
14.674
274675JOLIET 29;7U
Adder
16.11
274675JOLIET 29;7U
Adder
15.535
970833AG2-524 GEN
Solar/Wind Harmer
4.026
970833AG2-524 GEN
Solar/Wind Harmer
2.684
274728ELWOOD EC;5P
Adder
8.606
274731ELWOOD EC;2P
Adder
8.606
274733ELWOOD EC;3P
Adder
8.606
274735ELWOOD EC;4P
Adder
8.606
274744AC1-111 GEN8
Adder
2.922
274746AC1-111 G10
Adder
2.922
270526AF1-158 GEN
Solar/Wind Harmer
0
971771AH1-392 GEN
Solar/Wind Harmer
3.557
970073AG2-061 GEN
Solar/Wind Harmer
1.179
971675AH1-338 GEN
Solar/Wind Harmer
1.378
276861AD2-134 GEN
Solar/Wind Harmer
0.063
276863AD2-134 GEN
Solar/Wind Harmer
0.063
971411AH1-196 GEN
Solar/Wind Harmer
5.299
971171AH1-044 GEN
Solar/Wind Harmer
7.022
274823ROCKFORD ;21
Adder
9.774
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
274856ECOGROVE ;U1
Solar/Wind Harmer
0.081
971681AH1-341 GEN
Solar/Wind Harmer
5.563
926823AC1-168 GEN
Solar/Wind Harmer
0.585
970169AG2-114 GEN
Solar/Wind Harmer
3.42
972267AH1-718 GEN
Adder
2.035
276741O09 GEN1
Solar/Wind Harmer
0.12
958391AF2-133 GEN
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.112
959141AF2-205 GEN
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
1.857
971611AH1-305 GEN
Solar/Wind Harmer
1.968
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.442
270071AF1-092 GEN
Solar/Wind Harmer
6.245
274854TWINGROVE;U2
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.118
276848AB2-070 GEN3
Solar/Wind Harmer
0.118
276849AB2-070 GEN2
Solar/Wind Harmer
0.118
270223U2-072_GEN1
Solar/Wind Helper
1.526
270224U2-072_GEN2
Solar/Wind Helper
1.526
270227U2-072_GEN3
Solar/Wind Helper
1.526
270228U2-072_GEN4
Solar/Wind Helper
1.526
270231U2-072_GEN5
Solar/Wind Helper
1.526
241973AD2-163_GEN1
Solar/Wind Helper
2.406
241974AD2-163_GEN2
Solar/Wind Helper
2.406
241955AC1-078 GEN
Solar/Wind Helper
2.39
945631AF1-228 GEN
Solar/Wind Helper
1.862
966831AG1-554 GEN
Solar/Wind Helper
0.86
253338AC1-165 GEN
Solar/Wind Helper
0.829
253343AC1-166 GEN
Solar/Wind Helper
0.829
241972AD1-140 GEN
Solar/Wind Helper
3.091
945641AF1-229 GEN
Solar/Wind Helper
1.095
270499AE1-146 GEN
Solar/Wind Helper
1.885
270263AC1-001 GEN
Solar/Wind Helper
0.54
270340AC2-060 GEN
Solar/Wind Helper
0.967
24721805FLATG3
50/50
1.063
24344105CKG2
50/50
4.719
243186AF1-051 GEN
50/50
3.141
24318705GVG2
50/50
2.911
962761AG1-125 GEN
Solar/Wind Harmer
65.996
970149AG2-104 GEN
Solar/Wind Harmer
35.639
970155AG2-107 GEN
Solar/Wind Harmer
42.143
274773LINCOLN ;4U
Adder
4.626
274774LINCOLN ;5U
Adder
4.626
274723RIVER EC ;12
Adder
9.496
941551AE2-152 GEN
Solar/Wind Harmer
0
274802UNIV PARK;5U
Adder
3.071
274812UNIV PK N;8U
Adder
2.636
274751CRETE EC ;1U
Adder
4.332
274754CRETE EC ;4U
Adder
4.332
274676JOLIET 29;8U
Adder
16.11
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
8.073
274732ELWOOD EC;7P
Adder
8.606
274745AC1-111 GEN9
Adder
2.922
274682WAUKEGAN ;7U
Adder
9.263
274828WAUKEGAN ;BP
Adder
5.686
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.581
962781AG1-127 GEN
Solar/Wind Harmer
3.402
274861TOP CROP ;1U
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
2.646
276805AD2-038 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
7.407
971997AH1-543 GEN
Solar/Wind Harmer
1.85
276882AE2-255 GEN
Solar/Wind Harmer
0.411
957471AF2-041 GEN
Solar/Wind Harmer
10.533
959081AF2-199 GEN
Solar/Wind Harmer
3.511
971067AG2-660 GEN
Solar/Wind Harmer
1.17
274822ROCKFORD ;11
Adder
9.846
970819AG2-516 GEN
Solar/Wind Harmer
4.178
270055AF2-134 C O1
Solar/Wind Harmer
0
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
4.59
274766LEE CO EC;7U
Adder
4.536
970569AG2-363 GEN
Solar/Wind Harmer
10.321
957891AF2-083 GEN
Solar/Wind Harmer
5.667
958381AF2-132 GEN
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.12
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.408
276646AC1-214 GEN2
Solar/Wind Harmer
0.132
945111AF1-176 GEN
Solar/Wind Harmer
5.968
274848CAMPGROVE;RU
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
1.738
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
4.132
24639705ELKHART HY
Adder
0.072
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
4.59
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
270286AF1-227 GEN2
Solar/Wind Helper
2.335
270391AF1-285 GEN3
Solar/Wind Helper
1.033
270578AF1-285 GEN2
Solar/Wind Helper
1.033
270317AD1-130_GEN
Solar/Wind Helper
5.921
270485AE1-090_GEN
Solar/Wind Helper
0.466
270520AE2-214 GEN
Solar/Wind Helper
3.134
253333AC1-068 GEN
Solar/Wind Helper
0.859
960841AF2-375 GEN
Solar/Wind Helper
1.147
270273AD2-016 GEN
Solar/Wind Helper
1.662
270297AD1-101 GEN
Solar/Wind Helper
0.209
958961AF2-187 GEN
Solar/Wind Helper
1.121
241840AF1-064_GEN
Solar/Wind Helper
0.476
241807AE2-176_GEN
Solar/Wind Helper
0.698
24722005FLATG5
50/50
1.063
24721905FLATG4
50/50
19.423
24318705GVG2
50/50
2.911
962771AG1-126 GEN
Solar/Wind Harmer
65.996
970153AG2-106 GEN
Solar/Wind Harmer
42.143
971347AH1-153 GEN
Solar/Wind Harmer
2.048
274772LINCOLN ;3U
Adder
4.626
970707AG2-453 GEN
Solar/Wind Harmer
12.22
972259AH1-714 GEN
Adder
10.14
274724RIVER EC ;11
Adder
9.39
274887GEN-1.85
Solar/Wind Harmer
0.096
276843GEN-1.7
Solar/Wind Harmer
0.119
276806AD2-047 C O1
Solar/Wind Harmer
2.086
274826FISK ;BP
Adder
5.774
939351AE1-166 GEN
Solar/Wind Harmer
0
972038AH1-567 GEN2
Adder
0.192
274803UNIV PARK;6U
Adder
3.071
274814UNIV PK N;0U
Adder
2.659
274807UNIV PK N;3U
Adder
2.653
274811UNIV PK N;7U
Adder
2.636
274752CRETE EC ;2U
Adder
4.332
274753CRETE EC ;3U
Adder
4.332
274676JOLIET 29;8U
Adder
15.535
943121AE2-341 GEN
Solar/Wind Harmer
6.135
943591AF1-030 GEN
Solar/Wind Harmer
4.08
274729ELWOOD EC;1P
Adder
8.606
274730ELWOOD EC;6P
Adder
8.606
274734ELWOOD EC;8P
Adder
8.606
274736ELWOOD EC;9P
Adder
8.606
274682WAUKEGAN ;7U
Adder
9.263
274862TOP CROP ;2U
Solar/Wind Harmer
0.483
946671AF1-331 GEN
Solar/Wind Harmer
0.377
274855GSG-6 ;RU
Solar/Wind Harmer
0.129
274850MENDOTA H;RU
Solar/Wind Harmer
0.041
276868AE1-113 GEN
Solar/Wind Harmer
0.705
274879MINONK ;1U
Solar/Wind Harmer
0.147
959091AF2-200 GEN
Solar/Wind Harmer
7.022
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
4.59
274767LEE CO EC;8U
Adder
4.536
970571AG2-364 GEN
Solar/Wind Harmer
6.881
270505AE1-170 C O1
Solar/Wind Harmer
3.587
964401AG1-302 GEN
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.112
945111AF1-176 GEN
Solar/Wind Harmer
2.711
965931AG1-462 GEN
Solar/Wind Harmer
8.411
971087AG2-675 GEN
Solar/Wind Harmer
1.759
965091AG1-374 GEN
Solar/Wind Harmer
9.651
959611AF2-252 GEN
Solar/Wind Harmer
1.072
270043AE2-236 GEN
Solar/Wind Harmer
2.049
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.153
944531AF1-118 GEN
Solar/Wind Harmer
13.848
24386205FR-12G C
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
1.393
270284AF1-227 GEN1
Solar/Wind Helper
6.367
270287AF1-227 GEN3
Solar/Wind Helper
2.335
942871AE2-306 GEN
Solar/Wind Helper
0.775
276820AF1-078_GEN
Solar/Wind Helper
0.613
270518AE2-148 GEN
Solar/Wind Helper
10.61
960801AF2-371 GEN
Solar/Wind Helper
0.85
964871AG1-351 GEN
Solar/Wind Helper
0.587
253325AC1-069 GEN
Solar/Wind Helper
0.859
270541AE2-072 C
Solar/Wind Helper
1.112
960071AF2-298 GEN
Solar/Wind Helper
0.32
247522W1-056 GEN
Solar/Wind Helper
1.156
253415AE1-040 GEN
Solar/Wind Helper
0.455
CPLELTFEXP_CPLE->PJM
CLTF
1.546
CBM West 2LTFEXP_CBM-W2->PJM
CBM
39.631
NYPJM->LTFIMP_NY
CLTF
0.933
LGEELTFEXP_LGEE->PJM
CLTF
0.885
WECLTFEXP_WEC->PJM
CLTF
1.909
AG2-052LTFEXP_AG2-052->PJM
LTF
0.114
AH1-155LTFEXP_AH1-155->PJM
LTF
0.17
LAGNLTFEXP_LAGN->PJM
CLTF
5.571
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.313
TVALTFEXP_TVA->PJM
CLTF
2.485
CBM West 1LTFEXP_CBM-W1->PJM
CBM
43.606
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.522
MECLTFEXP_MEC->PJM
CLTF
7.183
SIGELTFEXP_SIGE->PJM
CLTF
0.119

Details for 05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer l/o AEP_P1-3_#7222_05MALIS 765_1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
Contingency Name:
AEP_P1-3_#7222_05MALIS 765_1_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.63 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3147.5
MW Contribution:
35.51
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721705FLATG2
50/50
15.73
243186AF1-051 GEN
50/50
3.128
970349AG2-230 GEN
Solar/Wind Harmer
6.057
274770LINCOLN ;1U
Adder
4.558
274771LINCOLN ;2U
Adder
4.558
965681AG1-436 GEN
Solar/Wind Harmer
4.578
965791AG1-447 GEN
Solar/Wind Harmer
3.357
274888KELLY CRK;1U
Solar/Wind Harmer
0.211
276776AD2-060 GEN
Solar/Wind Harmer
0.387
958011AF2-095 GEN
Solar/Wind Harmer
5.222
970941AG2-585 GEN
Solar/Wind Harmer
1.994
276897AD1-100 C
Solar/Wind Harmer
9.056
274805UNIV PK N;1U
Adder
2.602
274808UNIV PK N;4U
Adder
2.585
274674JOLIET 9 ;6U
Adder
7.951
276893AG1-478 C
Solar/Wind Harmer
0.24
274695ROCKY RD ;2P
Adder
5.665
274693ROCKY RD ;1P
Adder
5.61
274697ROCKY RD ;3P
Adder
1.539
274696ROCKY RD ;4P
Adder
5.799
274683WAUKEGAN ;8U
Adder
10.682
274683WAUKEGAN ;8U
Adder
9.005
962691AG1-118 GEN
Solar/Wind Harmer
10.586
958481AF2-142 GEN
Solar/Wind Harmer
5.282
958491AF2-143 GEN
Solar/Wind Harmer
5.221
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
6.913
971343AH1-151 GEN
Solar/Wind Harmer
6.913
972235AH1-702 GEN1
Adder
1.242
972236AH1-702 GEN2
Adder
1.08
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
938861AE1-114 GEN
Solar/Wind Harmer
1.927
274764LEE CO EC;5U
Adder
4.528
274765LEE CO EC;6U
Adder
4.528
274762LEE CO EC;3U
Adder
4.518
274763LEE CO EC;4U
Adder
4.475
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.539
276645AC1-214 GEN1
Solar/Wind Harmer
0.13
961051AF2-396 GEN
Solar/Wind Harmer
6.555
961051AF2-396 GEN
Solar/Wind Harmer
4.37
942111AE2-223 GEN
Solar/Wind Harmer
1.048
960611AF2-352 GEN
Solar/Wind Harmer
1.054
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
247620Y3-023
Adder
0.204
270349AD2-093_GEN
Solar/Wind Helper
4.705
270471AD2-092_GEN
Solar/Wind Helper
4.705
270462AD2-086
Solar/Wind Helper
5.394
253383AE2-342_GEN
Solar/Wind Helper
1.128
946101AF1-275 GEN
Solar/Wind Helper
0.8
241960AC2-195 GEN
Solar/Wind Helper
1.855
270054AF2-122 C O1
Solar/Wind Helper
1.473
253378AE2-206_GEN
Solar/Wind Helper
1.329
247522W1-056 GEN
Solar/Wind Helper
1.168
24721605FLATG1
50/50
1.059
274775LINCOLN ;6U
Adder
4.558
274776LINCOLN ;7U
Adder
4.558
274777LINCOLN ;8U
Adder
4.558
960681AF2-359 GEN
Solar/Wind Harmer
0
972228AH1-698 GEN2
Adder
1.928
972227AH1-698 GEN1
Adder
1.358
960591AF2-350 GEN
Solar/Wind Harmer
3.626
274827FISK ;RP
Adder
4.03
274800UNIV PARK;3U
Adder
3.027
274801UNIV PARK;4U
Adder
3.027
972037AH1-567 GEN1
Adder
0.095
274687WILL CNTY;4U
Adder
14.452
274687WILL CNTY;4U
Adder
14.452
274675JOLIET 29;7U
Adder
15.866
274675JOLIET 29;7U
Adder
15.3
970833AG2-524 GEN
Solar/Wind Harmer
3.965
970833AG2-524 GEN
Solar/Wind Harmer
2.643
274728ELWOOD EC;5P
Adder
8.475
274731ELWOOD EC;2P
Adder
8.475
274733ELWOOD EC;3P
Adder
8.475
274735ELWOOD EC;4P
Adder
8.475
274744AC1-111 GEN8
Adder
2.877
274746AC1-111 G10
Adder
2.877
270526AF1-158 GEN
Solar/Wind Harmer
0
971771AH1-392 GEN
Solar/Wind Harmer
3.499
970073AG2-061 GEN
Solar/Wind Harmer
1.16
971675AH1-338 GEN
Solar/Wind Harmer
1.357
276861AD2-134 GEN
Solar/Wind Harmer
0.062
276863AD2-134 GEN
Solar/Wind Harmer
0.062
971411AH1-196 GEN
Solar/Wind Harmer
5.217
971171AH1-044 GEN
Solar/Wind Harmer
6.913
274823ROCKFORD ;21
Adder
9.622
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
274856ECOGROVE ;U1
Solar/Wind Harmer
0.08
971681AH1-341 GEN
Solar/Wind Harmer
5.476
926823AC1-168 GEN
Solar/Wind Harmer
0.576
970169AG2-114 GEN
Solar/Wind Harmer
3.365
972267AH1-718 GEN
Adder
2.003
276741O09 GEN1
Solar/Wind Harmer
0.118
958391AF2-133 GEN
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.11
959141AF2-205 GEN
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
1.827
971611AH1-305 GEN
Solar/Wind Harmer
1.935
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.385
270071AF1-092 GEN
Solar/Wind Harmer
6.128
274854TWINGROVE;U2
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0
270223U2-072_GEN1
Solar/Wind Helper
1.536
270224U2-072_GEN2
Solar/Wind Helper
1.536
270227U2-072_GEN3
Solar/Wind Helper
1.536
270228U2-072_GEN4
Solar/Wind Helper
1.536
270231U2-072_GEN5
Solar/Wind Helper
1.536
241973AD2-163_GEN1
Solar/Wind Helper
2.441
241974AD2-163_GEN2
Solar/Wind Helper
2.441
241955AC1-078 GEN
Solar/Wind Helper
2.436
945631AF1-228 GEN
Solar/Wind Helper
1.902
966831AG1-554 GEN
Solar/Wind Helper
0.869
253338AC1-165 GEN
Solar/Wind Helper
0.848
253343AC1-166 GEN
Solar/Wind Helper
0.848
241972AD1-140 GEN
Solar/Wind Helper
3.153
945641AF1-229 GEN
Solar/Wind Helper
1.107
270499AE1-146 GEN
Solar/Wind Helper
1.906
270263AC1-001 GEN
Solar/Wind Helper
0.555
270340AC2-060 GEN
Solar/Wind Helper
0.994
24721805FLATG3
50/50
1.059
24344105CKG2
50/50
4.657
243186AF1-051 GEN
50/50
3.128
24318705GVG2
50/50
2.899
962761AG1-125 GEN
Solar/Wind Harmer
65.757
970149AG2-104 GEN
Solar/Wind Harmer
35.51
970155AG2-107 GEN
Solar/Wind Harmer
41.991
274773LINCOLN ;4U
Adder
4.558
274774LINCOLN ;5U
Adder
4.558
274723RIVER EC ;12
Adder
9.352
941551AE2-152 GEN
Solar/Wind Harmer
0
274802UNIV PARK;5U
Adder
3.024
274812UNIV PK N;8U
Adder
2.596
274751CRETE EC ;1U
Adder
4.266
274754CRETE EC ;4U
Adder
4.266
274676JOLIET 29;8U
Adder
15.866
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
7.951
274732ELWOOD EC;7P
Adder
8.475
274745AC1-111 GEN9
Adder
2.877
274682WAUKEGAN ;7U
Adder
9.121
274828WAUKEGAN ;BP
Adder
5.599
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.572
962781AG1-127 GEN
Solar/Wind Harmer
3.35
274861TOP CROP ;1U
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
2.605
276805AD2-038 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
7.288
971997AH1-543 GEN
Solar/Wind Harmer
1.821
276882AE2-255 GEN
Solar/Wind Harmer
0.405
957471AF2-041 GEN
Solar/Wind Harmer
10.37
959081AF2-199 GEN
Solar/Wind Harmer
3.457
971067AG2-660 GEN
Solar/Wind Harmer
1.152
274822ROCKFORD ;11
Adder
9.693
970819AG2-516 GEN
Solar/Wind Harmer
4.112
270055AF2-134 C O1
Solar/Wind Harmer
0
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
4.518
274766LEE CO EC;7U
Adder
4.465
970569AG2-363 GEN
Solar/Wind Harmer
10.157
957891AF2-083 GEN
Solar/Wind Harmer
5.572
958381AF2-132 GEN
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.118
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.335
276646AC1-214 GEN2
Solar/Wind Harmer
0.13
945111AF1-176 GEN
Solar/Wind Harmer
5.866
274848CAMPGROVE;RU
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
1.708
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
4.062
24639705ELKHART HY
Adder
0.071
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
4.513
270286AF1-227 GEN2
Solar/Wind Helper
2.348
270391AF1-285 GEN3
Solar/Wind Helper
1.04
270578AF1-285 GEN2
Solar/Wind Helper
1.04
270317AD1-130_GEN
Solar/Wind Helper
5.963
270485AE1-090_GEN
Solar/Wind Helper
0.469
270520AE2-214 GEN
Solar/Wind Helper
3.2
253415AE1-040 GEN
Solar/Wind Helper
0.468
253349AC2-067 GEN
Solar/Wind Helper
0.175
253400AC2-068 GEN
Solar/Wind Helper
0.07
253333AC1-068 GEN
Solar/Wind Helper
0.879
960841AF2-375 GEN
Solar/Wind Helper
1.159
270273AD2-016 GEN
Solar/Wind Helper
1.703
270297AD1-101 GEN
Solar/Wind Helper
0.213
958961AF2-187 GEN
Solar/Wind Helper
1.122
241840AF1-064_GEN
Solar/Wind Helper
0.483
241807AE2-176_GEN
Solar/Wind Helper
0.703
24722005FLATG5
50/50
1.059
24721905FLATG4
50/50
19.347
24318705GVG2
50/50
2.899
962771AG1-126 GEN
Solar/Wind Harmer
65.757
970153AG2-106 GEN
Solar/Wind Harmer
41.991
971347AH1-153 GEN
Solar/Wind Harmer
2.019
274772LINCOLN ;3U
Adder
4.558
970707AG2-453 GEN
Solar/Wind Harmer
12.038
972259AH1-714 GEN
Adder
9.988
274724RIVER EC ;11
Adder
9.248
274887GEN-1.85
Solar/Wind Harmer
0.094
276843GEN-1.7
Solar/Wind Harmer
0.117
276806AD2-047 C O1
Solar/Wind Harmer
2.055
274826FISK ;BP
Adder
5.687
939351AE1-166 GEN
Solar/Wind Harmer
0
972038AH1-567 GEN2
Adder
0.189
274803UNIV PARK;6U
Adder
3.024
274814UNIV PK N;0U
Adder
2.619
274807UNIV PK N;3U
Adder
2.613
274811UNIV PK N;7U
Adder
2.596
274752CRETE EC ;2U
Adder
4.266
274753CRETE EC ;3U
Adder
4.266
274676JOLIET 29;8U
Adder
15.299
943121AE2-341 GEN
Solar/Wind Harmer
6.042
943591AF1-030 GEN
Solar/Wind Harmer
4.018
274729ELWOOD EC;1P
Adder
8.475
274730ELWOOD EC;6P
Adder
8.475
274734ELWOOD EC;8P
Adder
8.475
274736ELWOOD EC;9P
Adder
8.475
274682WAUKEGAN ;7U
Adder
9.121
274862TOP CROP ;2U
Solar/Wind Harmer
0.475
946671AF1-331 GEN
Solar/Wind Harmer
0.371
274855GSG-6 ;RU
Solar/Wind Harmer
0.127
274850MENDOTA H;RU
Solar/Wind Harmer
0.04
276868AE1-113 GEN
Solar/Wind Harmer
0.694
274879MINONK ;1U
Solar/Wind Harmer
0.145
959091AF2-200 GEN
Solar/Wind Harmer
6.913
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
4.518
274767LEE CO EC;8U
Adder
4.465
970571AG2-364 GEN
Solar/Wind Harmer
6.772
270505AE1-170 C O1
Solar/Wind Harmer
3.527
964401AG1-302 GEN
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.11
945111AF1-176 GEN
Solar/Wind Harmer
2.665
965931AG1-462 GEN
Solar/Wind Harmer
8.275
971087AG2-675 GEN
Solar/Wind Harmer
1.731
965091AG1-374 GEN
Solar/Wind Harmer
9.488
959611AF2-252 GEN
Solar/Wind Harmer
1.054
270043AE2-236 GEN
Solar/Wind Harmer
2.01
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.097
944531AF1-118 GEN
Solar/Wind Harmer
13.569
270284AF1-227 GEN1
Solar/Wind Helper
6.403
270287AF1-227 GEN3
Solar/Wind Helper
2.348
942871AE2-306 GEN
Solar/Wind Helper
0.78
276820AF1-078_GEN
Solar/Wind Helper
0.621
270518AE2-148 GEN
Solar/Wind Helper
10.844
960801AF2-371 GEN
Solar/Wind Helper
0.869
964871AG1-351 GEN
Solar/Wind Helper
0.6
253325AC1-069 GEN
Solar/Wind Helper
0.879
270541AE2-072 C
Solar/Wind Helper
1.128
960071AF2-298 GEN
Solar/Wind Helper
0.328
CPLELTFEXP_CPLE->PJM
CLTF
1.537
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.767
NYPJM->LTFIMP_NY
CLTF
0.905
LGEELTFEXP_LGEE->PJM
CLTF
0.829
WECLTFEXP_WEC->PJM
CLTF
1.879
AG2-052LTFEXP_AG2-052->PJM
LTF
0.112
AH1-155LTFEXP_AH1-155->PJM
LTF
0.168
LAGNLTFEXP_LAGN->PJM
CLTF
5.461
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.255
TVALTFEXP_TVA->PJM
CLTF
2.432
CBM West 1LTFEXP_CBM-W1->PJM
CBM
42.534
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.305
MECLTFEXP_MEC->PJM
CLTF
7.06
SIGELTFEXP_SIGE->PJM
CLTF
0.115

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AEP_P4_#2942_05KAMMER 765_PP_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.42 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:6007.36
MW Contribution:
59.0
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721705FLATG2
50/50
26.627
270102X2-052 ST
50/50
2.048
270100X2-052 CT1
50/50
1.893
270101X2-052 CT2
50/50
1.893
970349AG2-230 GEN
Solar/Wind Harmer
20.036
965681AG1-436 GEN
Solar/Wind Harmer
15.977
965791AG1-447 GEN
Solar/Wind Harmer
8.175
274770LINCOLN ;1U
Adder
7.887
274771LINCOLN ;2U
Adder
7.887
274805UNIV PK N;1U
Adder
6.295
274808UNIV PK N;4U
Adder
6.253
274888KELLY CRK;1U
Solar/Wind Harmer
7.385
276776AD2-060 GEN
Solar/Wind Harmer
0.524
958011AF2-095 GEN
Solar/Wind Harmer
18.022
970941AG2-585 GEN
Solar/Wind Harmer
6.883
247620Y3-023
Adder
0.576
276897AD1-100 C
Solar/Wind Harmer
58.016
961051AF2-396 GEN
Solar/Wind Harmer
19.768
961051AF2-396 GEN
Solar/Wind Harmer
9.195
274674JOLIET 9 ;6U
Adder
19.168
276893AG1-478 C
Solar/Wind Harmer
0.545
270535AF1-215 GEN1
Solar/Wind Harmer
5.606
270536AF1-215 GEN2
Solar/Wind Harmer
5.606
274696ROCKY RD ;4P
Adder
14.03
274695ROCKY RD ;2P
Adder
13.707
274693ROCKY RD ;1P
Adder
13.572
274697ROCKY RD ;3P
Adder
3.724
958481AF2-142 GEN
Solar/Wind Harmer
18.447
274683WAUKEGAN ;8U
Adder
25.894
274683WAUKEGAN ;8U
Adder
21.827
962691AG1-118 GEN
Solar/Wind Harmer
36.785
960751AF2-366 GEN
Solar/Wind Harmer
3.513
958491AF2-143 GEN
Solar/Wind Harmer
18.322
276901AD2-066 C O1
Solar/Wind Harmer
4.281
971341AH1-150 GEN
Solar/Wind Harmer
24.227
971343AH1-151 GEN
Solar/Wind Harmer
24.227
276872AE1-163_GEN1
Solar/Wind Harmer
8.124
276876AE1-163_GEN2
Solar/Wind Harmer
8.124
972235AH1-702 GEN1
Adder
3.043
24721605FLATG1
50/50
1.793
270071AF1-092 GEN
Solar/Wind Harmer
19.366
960681AF2-359 GEN
Solar/Wind Harmer
4.83
971771AH1-392 GEN
Solar/Wind Harmer
11.452
274775LINCOLN ;6U
Adder
7.887
274776LINCOLN ;7U
Adder
7.887
274777LINCOLN ;8U
Adder
7.887
270526AF1-158 GEN
Solar/Wind Harmer
5.763
274827FISK ;RP
Adder
9.712
972037AH1-567 GEN1
Adder
0.229
972228AH1-698 GEN2
Adder
4.636
960591AF2-350 GEN
Solar/Wind Harmer
12.515
972227AH1-698 GEN1
Adder
3.264
274800UNIV PARK;3U
Adder
7.294
274801UNIV PARK;4U
Adder
7.294
274687WILL CNTY;4U
Adder
34.836
274687WILL CNTY;4U
Adder
34.836
274675JOLIET 29;7U
Adder
38.23
274675JOLIET 29;7U
Adder
36.864
274728ELWOOD EC;5P
Adder
20.452
274731ELWOOD EC;2P
Adder
20.452
274733ELWOOD EC;3P
Adder
20.452
274735ELWOOD EC;4P
Adder
20.452
970833AG2-524 GEN
Solar/Wind Harmer
10.861
970833AG2-524 GEN
Solar/Wind Harmer
5.051
276893AG1-478 C
Solar/Wind Harmer
0.684
970031AG2-029 GEN
Solar/Wind Harmer
31.055
24729505KEY G4
Adder
8.043
274744AC1-111 GEN8
Adder
6.929
274746AC1-111 G10
Adder
6.929
944161AF1-084 GEN
Solar/Wind Harmer
2.729
970073AG2-061 GEN
Solar/Wind Harmer
2.841
959331AF2-224 GEN
Solar/Wind Harmer
12.193
958391AF2-133 GEN
Solar/Wind Harmer
11.058
971675AH1-338 GEN
Solar/Wind Harmer
21.888
971411AH1-196 GEN
Solar/Wind Harmer
18.238
276861AD2-134 GEN
Solar/Wind Harmer
2.171
276863AD2-134 GEN
Solar/Wind Harmer
2.171
959141AF2-205 GEN
Solar/Wind Harmer
7.345
274863CRW1-WTG
Solar/Wind Harmer
6.769
274864CRW2-WTG
Solar/Wind Harmer
6.769
971171AH1-044 GEN
Solar/Wind Harmer
24.227
276889AE2-281 GEN
Solar/Wind Harmer
2.321
274823ROCKFORD ;21
Adder
23.553
274856ECOGROVE ;U1
Solar/Wind Harmer
4.06
276611AD2-172 GEN
Solar/Wind Harmer
3.079
276612AE2-035 GEN
Solar/Wind Harmer
3.079
926823AC1-168 GEN
Solar/Wind Harmer
5.168
972267AH1-718 GEN
Adder
4.956
24722005FLATG5
50/50
1.793
24721905FLATG4
50/50
32.75
962771AG1-126 GEN
Solar/Wind Harmer
95.55
970153AG2-106 GEN
Solar/Wind Harmer
41.664
971347AH1-153 GEN
Solar/Wind Harmer
6.679
270043AE2-236 GEN
Solar/Wind Harmer
7.167
274772LINCOLN ;3U
Adder
7.887
24441505OLIV SLR
Solar/Wind Harmer
0.17
247643Z2-116 C
Solar/Wind Harmer
0.088
274724RIVER EC ;11
Adder
22.304
944531AF1-118 GEN
Solar/Wind Harmer
44.033
276164X3-005 C
Solar/Wind Harmer
0.883
970707AG2-453 GEN
Solar/Wind Harmer
35.193
972231SS25-0005
Solar/Wind Harmer
11.928
972181SS23-001
Solar/Wind Harmer
7.455
274752CRETE EC ;2U
Adder
6.143
274753CRETE EC ;3U
Adder
6.143
270505AE1-170 C O1
Solar/Wind Harmer
18.826
274814UNIV PK N;0U
Adder
6.336
274807UNIV PK N;3U
Adder
6.322
274811UNIV PK N;7U
Adder
6.281
972259AH1-714 GEN
Adder
23.907
274826FISK ;BP
Adder
13.704
274803UNIV PARK;6U
Adder
7.297
274887GEN-1.85
Solar/Wind Harmer
6.668
276772AC2-154 GEN
Solar/Wind Harmer
3.493
276843GEN-1.7
Solar/Wind Harmer
0.717
276806AD2-047 C O1
Solar/Wind Harmer
13.389
972038AH1-567 GEN2
Adder
0.457
945111AF1-176 GEN
Solar/Wind Harmer
7.073
270063AE2-323 C
Solar/Wind Harmer
2.747
939351AE1-166 GEN
Solar/Wind Harmer
7.407
274676JOLIET 29;8U
Adder
36.864
274729ELWOOD EC;1P
Adder
20.452
274730ELWOOD EC;6P
Adder
20.452
274734ELWOOD EC;8P
Adder
20.452
274736ELWOOD EC;9P
Adder
20.452
943121AE2-341 GEN
Solar/Wind Harmer
18.618
943591AF1-030 GEN
Solar/Wind Harmer
12.412
274682WAUKEGAN ;7U
Adder
22.1
274862TOP CROP ;2U
Solar/Wind Harmer
6.218
964401AG1-302 GEN
Solar/Wind Harmer
11.111
965021AG1-366 GEN
Solar/Wind Harmer
2.835
276868AE1-113 GEN
Solar/Wind Harmer
12.326
274879MINONK ;1U
Solar/Wind Harmer
8.218
276799AD1-013 GEN
Solar/Wind Harmer
2.687
946671AF1-331 GEN
Solar/Wind Harmer
0.509
274855GSG-6 ;RU
Solar/Wind Harmer
4.489
274850MENDOTA H;RU
Solar/Wind Harmer
3.121
276602WESTBROOK C
Solar/Wind Harmer
2.584
959091AF2-200 GEN
Solar/Wind Harmer
24.227
274760LEE CO EC;1U
Adder
11.136
274767LEE CO EC;8U
Adder
11.004
24728705AND G3
Adder
7.909
24728505AND G1
Adder
3.782
970571AG2-364 GEN
Solar/Wind Harmer
0.461
24721805FLATG3
50/50
1.793
24344105CKG2
50/50
10.243
962761AG1-125 GEN
Solar/Wind Harmer
95.55
970149AG2-104 GEN
Solar/Wind Harmer
59.002
970155AG2-107 GEN
Solar/Wind Harmer
41.664
972207SS24-0001
Solar/Wind Harmer
28.042
274773LINCOLN ;4U
Adder
7.887
274774LINCOLN ;5U
Adder
7.887
270216AD2-079_GEN
Solar/Wind Harmer
0.767
274723RIVER EC ;12
Adder
22.564
24639705ELKHART HY
Adder
0.193
274751CRETE EC ;1U
Adder
6.143
274754CRETE EC ;4U
Adder
6.143
957891AF2-083 GEN
Solar/Wind Harmer
18.814
274812UNIV PK N;8U
Adder
6.281
274802UNIV PARK;5U
Adder
7.297
945111AF1-176 GEN
Solar/Wind Harmer
22.317
941551AE2-152 GEN
Solar/Wind Harmer
5.664
970373AG2-245 GEN
Solar/Wind Harmer
26.184
274676JOLIET 29;8U
Adder
38.229
274674JOLIET 9 ;6U
Adder
19.168
274732ELWOOD EC;7P
Adder
20.452
274871GR RIDGE ;2U
Solar/Wind Harmer
9.563
274847GR RIDGE ;BU
Solar/Wind Harmer
6.288
270449AD2-020 GEN
Solar/Wind Harmer
3.481
943021AE2-325 GEN
Solar/Wind Harmer
4.524
274745AC1-111 GEN9
Adder
6.929
270055AF2-134 C O1
Solar/Wind Harmer
3.737
276694AA1-018 GEN2
Solar/Wind Harmer
7.76
276691AA1-018 GEN1
Solar/Wind Harmer
0.928
274682WAUKEGAN ;7U
Adder
22.1
274861TOP CROP ;1U
Solar/Wind Harmer
7.448
274828WAUKEGAN ;BP
Adder
13.573
958381AF2-132 GEN
Solar/Wind Harmer
11.111
962781AG1-127 GEN
Solar/Wind Harmer
11.644
964861AG1-349 GEN
Solar/Wind Harmer
9.62
971917AH1-482 GEN
Solar/Wind Harmer
11.099
939401AE1-172 GEN
Solar/Wind Harmer
17.049
274872LEEDK;1U
Solar/Wind Harmer
10.038
276805AD2-038 GEN
Solar/Wind Harmer
6.264
965011AG1-365 GEN
Solar/Wind Harmer
12.193
24441205WTRV SLR C
Solar/Wind Harmer
0.164
276882AE2-255 GEN
Solar/Wind Harmer
4.109
971997AH1-543 GEN
Solar/Wind Harmer
19.171
957471AF2-041 GEN
Solar/Wind Harmer
36.34
959081AF2-199 GEN
Solar/Wind Harmer
12.113
971067AG2-660 GEN
Solar/Wind Harmer
2.817
940581AE2-045 GEN
Solar/Wind Harmer
12.334
971605AH1-302 GEN
Solar/Wind Harmer
10.546
274822ROCKFORD ;11
Adder
23.726
970819AG2-516 GEN
Solar/Wind Harmer
14.459
274761LEE CO EC;2U
Adder
11.136
274766LEE CO EC;7U
Adder
11.004
24728605AND G2
Adder
3.782
970091AG2-072 GEN
Adder
75.433
972203AH1-686 GEN
Adder
1.981
970569AG2-363 GEN
Solar/Wind Harmer
0.692
972236AH1-702 GEN2
Adder
2.646
274764LEE CO EC;5U
Adder
11.162
274765LEE CO EC;6U
Adder
11.162
274762LEE CO EC;3U
Adder
11.136
274763LEE CO EC;4U
Adder
11.031
247621Y3-024
Adder
0.244
270054AF2-122 C O1
Solar/Wind Helper
1.556
CPLELTFEXP_CPLE->PJM
CLTF
3.164
CBM West 2LTFEXP_CBM-W2->PJM
CBM
119.495
NYPJM->LTFIMP_NY
CLTF
3.803
LGEELTFEXP_LGEE->PJM
CLTF
5.486
WECLTFEXP_WEC->PJM
CLTF
4.609
AG2-052LTFEXP_AG2-052->PJM
LTF
0.284
AH1-155LTFEXP_AH1-155->PJM
LTF
0.426
LAGNLTFEXP_LAGN->PJM
CLTF
16.173
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.821
TVALTFEXP_TVA->PJM
CLTF
7.643
CBM West 1LTFEXP_CBM-W1->PJM
CBM
145.936
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.934
MECLTFEXP_MEC->PJM
CLTF
18.402
SIGELTFEXP_SIGE->PJM
CLTF
0.471

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AP_P2-3_MP-500-020_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-3_MP-500-020_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:128.84 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5889.34
MW Contribution:
59.16
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721805FLATG3
50/50
1.803
24344105CKG2
50/50
10.303
962761AG1-125 GEN
Solar/Wind Harmer
95.812
970149AG2-104 GEN
Solar/Wind Harmer
59.164
970155AG2-107 GEN
Solar/Wind Harmer
41.779
972207SS24-0001
Solar/Wind Harmer
28.22
274773LINCOLN ;4U
Adder
7.937
274774LINCOLN ;5U
Adder
7.937
270216AD2-079_GEN
Solar/Wind Harmer
0.772
274723RIVER EC ;12
Adder
22.708
24639705ELKHART HY
Adder
0.194
274751CRETE EC ;1U
Adder
6.183
274754CRETE EC ;4U
Adder
6.183
957891AF2-083 GEN
Solar/Wind Harmer
18.934
274812UNIV PK N;8U
Adder
6.321
274802UNIV PARK;5U
Adder
7.344
945111AF1-176 GEN
Solar/Wind Harmer
22.461
941551AE2-152 GEN
Solar/Wind Harmer
5.701
970373AG2-245 GEN
Solar/Wind Harmer
26.353
274676JOLIET 29;8U
Adder
38.476
274674JOLIET 9 ;6U
Adder
19.291
274732ELWOOD EC;7P
Adder
20.585
274871GR RIDGE ;2U
Solar/Wind Harmer
9.625
274847GR RIDGE ;BU
Solar/Wind Harmer
6.329
270449AD2-020 GEN
Solar/Wind Harmer
3.504
943021AE2-325 GEN
Solar/Wind Harmer
4.553
274745AC1-111 GEN9
Adder
6.974
270055AF2-134 C O1
Solar/Wind Harmer
3.762
276694AA1-018 GEN2
Solar/Wind Harmer
7.811
276691AA1-018 GEN1
Solar/Wind Harmer
0.934
274682WAUKEGAN ;7U
Adder
22.245
274861TOP CROP ;1U
Solar/Wind Harmer
7.496
274828WAUKEGAN ;BP
Adder
13.662
958381AF2-132 GEN
Solar/Wind Harmer
11.184
962781AG1-127 GEN
Solar/Wind Harmer
11.72
964861AG1-349 GEN
Solar/Wind Harmer
9.683
24721705FLATG2
50/50
26.77
270102X2-052 ST
50/50
2.061
270100X2-052 CT1
50/50
1.905
270101X2-052 CT2
50/50
1.905
970349AG2-230 GEN
Solar/Wind Harmer
20.157
965681AG1-436 GEN
Solar/Wind Harmer
16.078
965791AG1-447 GEN
Solar/Wind Harmer
8.226
274770LINCOLN ;1U
Adder
7.937
274771LINCOLN ;2U
Adder
7.937
274805UNIV PK N;1U
Adder
6.335
274808UNIV PK N;4U
Adder
6.293
274888KELLY CRK;1U
Solar/Wind Harmer
7.433
276776AD2-060 GEN
Solar/Wind Harmer
0.527
958011AF2-095 GEN
Solar/Wind Harmer
18.138
970941AG2-585 GEN
Solar/Wind Harmer
6.928
247620Y3-023
Adder
0.58
276897AD1-100 C
Solar/Wind Harmer
58.39
961051AF2-396 GEN
Solar/Wind Harmer
19.896
961051AF2-396 GEN
Solar/Wind Harmer
9.254
274674JOLIET 9 ;6U
Adder
19.291
276893AG1-478 C
Solar/Wind Harmer
0.549
270535AF1-215 GEN1
Solar/Wind Harmer
5.643
270536AF1-215 GEN2
Solar/Wind Harmer
5.643
274695ROCKY RD ;2P
Adder
13.796
274693ROCKY RD ;1P
Adder
13.661
274697ROCKY RD ;3P
Adder
3.748
274696ROCKY RD ;4P
Adder
14.122
958481AF2-142 GEN
Solar/Wind Harmer
18.568
274683WAUKEGAN ;8U
Adder
26.063
274683WAUKEGAN ;8U
Adder
21.97
962691AG1-118 GEN
Solar/Wind Harmer
37.026
960751AF2-366 GEN
Solar/Wind Harmer
3.536
24721605FLATG1
50/50
1.803
270071AF1-092 GEN
Solar/Wind Harmer
19.487
960681AF2-359 GEN
Solar/Wind Harmer
4.86
971771AH1-392 GEN
Solar/Wind Harmer
11.525
274775LINCOLN ;6U
Adder
7.937
274776LINCOLN ;7U
Adder
7.937
274777LINCOLN ;8U
Adder
7.937
270526AF1-158 GEN
Solar/Wind Harmer
5.8
274827FISK ;RP
Adder
9.774
972037AH1-567 GEN1
Adder
0.231
960591AF2-350 GEN
Solar/Wind Harmer
12.596
972228AH1-698 GEN2
Adder
4.665
972227AH1-698 GEN1
Adder
3.285
274800UNIV PARK;3U
Adder
7.341
274801UNIV PARK;4U
Adder
7.341
274687WILL CNTY;4U
Adder
35.06
274687WILL CNTY;4U
Adder
35.06
274675JOLIET 29;7U
Adder
38.476
274675JOLIET 29;7U
Adder
37.102
274728ELWOOD EC;5P
Adder
20.585
274731ELWOOD EC;2P
Adder
20.584
274733ELWOOD EC;3P
Adder
20.584
274735ELWOOD EC;4P
Adder
20.584
970833AG2-524 GEN
Solar/Wind Harmer
10.931
970833AG2-524 GEN
Solar/Wind Harmer
5.084
276893AG1-478 C
Solar/Wind Harmer
0.688
970031AG2-029 GEN
Solar/Wind Harmer
31.256
24729505KEY G4
Adder
8.096
274744AC1-111 GEN8
Adder
6.974
274746AC1-111 G10
Adder
6.974
944161AF1-084 GEN
Solar/Wind Harmer
2.746
970073AG2-061 GEN
Solar/Wind Harmer
2.859
959331AF2-224 GEN
Solar/Wind Harmer
12.273
958391AF2-133 GEN
Solar/Wind Harmer
11.131
958491AF2-143 GEN
Solar/Wind Harmer
18.442
276901AD2-066 C O1
Solar/Wind Harmer
4.309
971341AH1-150 GEN
Solar/Wind Harmer
24.388
971343AH1-151 GEN
Solar/Wind Harmer
24.388
276872AE1-163_GEN1
Solar/Wind Harmer
8.178
276876AE1-163_GEN2
Solar/Wind Harmer
8.178
972235AH1-702 GEN1
Adder
3.063
972236AH1-702 GEN2
Adder
2.663
274764LEE CO EC;5U
Adder
11.237
274765LEE CO EC;6U
Adder
11.237
274762LEE CO EC;3U
Adder
11.21
274763LEE CO EC;4U
Adder
11.105
247621Y3-024
Adder
0.245
270054AF2-122 C O1
Solar/Wind Helper
1.545
971675AH1-338 GEN
Solar/Wind Harmer
22.032
971411AH1-196 GEN
Solar/Wind Harmer
18.358
276861AD2-134 GEN
Solar/Wind Harmer
2.185
276863AD2-134 GEN
Solar/Wind Harmer
2.185
959141AF2-205 GEN
Solar/Wind Harmer
7.394
274863CRW1-WTG
Solar/Wind Harmer
6.814
274864CRW2-WTG
Solar/Wind Harmer
6.814
971171AH1-044 GEN
Solar/Wind Harmer
24.388
276889AE2-281 GEN
Solar/Wind Harmer
2.337
274823ROCKFORD ;21
Adder
23.71
274856ECOGROVE ;U1
Solar/Wind Harmer
4.087
276611AD2-172 GEN
Solar/Wind Harmer
3.1
276612AE2-035 GEN
Solar/Wind Harmer
3.1
926823AC1-168 GEN
Solar/Wind Harmer
5.202
972267AH1-718 GEN
Adder
4.989
24722005FLATG5
50/50
1.803
24721905FLATG4
50/50
32.925
962771AG1-126 GEN
Solar/Wind Harmer
95.812
970153AG2-106 GEN
Solar/Wind Harmer
41.779
971347AH1-153 GEN
Solar/Wind Harmer
6.719
270043AE2-236 GEN
Solar/Wind Harmer
7.211
274772LINCOLN ;3U
Adder
7.937
24441505OLIV SLR
Solar/Wind Harmer
0.171
247643Z2-116 C
Solar/Wind Harmer
0.089
274724RIVER EC ;11
Adder
22.446
944531AF1-118 GEN
Solar/Wind Harmer
44.315
276164X3-005 C
Solar/Wind Harmer
0.889
970707AG2-453 GEN
Solar/Wind Harmer
35.418
972231SS25-0005
Solar/Wind Harmer
12.005
972181SS23-001
Solar/Wind Harmer
7.503
274752CRETE EC ;2U
Adder
6.183
274753CRETE EC ;3U
Adder
6.183
270505AE1-170 C O1
Solar/Wind Harmer
18.946
274814UNIV PK N;0U
Adder
6.376
274807UNIV PK N;3U
Adder
6.363
274811UNIV PK N;7U
Adder
6.321
972259AH1-714 GEN
Adder
24.06
274826FISK ;BP
Adder
13.792
274803UNIV PARK;6U
Adder
7.344
274887GEN-1.85
Solar/Wind Harmer
6.711
276772AC2-154 GEN
Solar/Wind Harmer
3.515
276843GEN-1.7
Solar/Wind Harmer
0.722
276806AD2-047 C O1
Solar/Wind Harmer
13.475
972038AH1-567 GEN2
Adder
0.459
945111AF1-176 GEN
Solar/Wind Harmer
7.118
270063AE2-323 C
Solar/Wind Harmer
2.765
939351AE1-166 GEN
Solar/Wind Harmer
7.454
274676JOLIET 29;8U
Adder
37.102
274729ELWOOD EC;1P
Adder
20.584
274730ELWOOD EC;6P
Adder
20.585
274734ELWOOD EC;8P
Adder
20.585
274736ELWOOD EC;9P
Adder
20.585
943121AE2-341 GEN
Solar/Wind Harmer
18.739
943591AF1-030 GEN
Solar/Wind Harmer
12.493
274682WAUKEGAN ;7U
Adder
22.245
274862TOP CROP ;2U
Solar/Wind Harmer
6.259
964401AG1-302 GEN
Solar/Wind Harmer
11.184
965021AG1-366 GEN
Solar/Wind Harmer
2.854
276868AE1-113 GEN
Solar/Wind Harmer
12.408
274879MINONK ;1U
Solar/Wind Harmer
8.272
276799AD1-013 GEN
Solar/Wind Harmer
2.705
946671AF1-331 GEN
Solar/Wind Harmer
0.513
274855GSG-6 ;RU
Solar/Wind Harmer
4.519
274850MENDOTA H;RU
Solar/Wind Harmer
3.142
276602WESTBROOK C
Solar/Wind Harmer
2.601
959091AF2-200 GEN
Solar/Wind Harmer
24.388
274760LEE CO EC;1U
Adder
11.21
274767LEE CO EC;8U
Adder
11.078
24728705AND G3
Adder
7.974
24728505AND G1
Adder
3.813
970571AG2-364 GEN
Solar/Wind Harmer
0.465
971917AH1-482 GEN
Solar/Wind Harmer
11.172
939401AE1-172 GEN
Solar/Wind Harmer
17.161
274872LEEDK;1U
Solar/Wind Harmer
10.104
276805AD2-038 GEN
Solar/Wind Harmer
6.305
965011AG1-365 GEN
Solar/Wind Harmer
12.273
24441205WTRV SLR C
Solar/Wind Harmer
0.165
276882AE2-255 GEN
Solar/Wind Harmer
4.136
971997AH1-543 GEN
Solar/Wind Harmer
19.298
957471AF2-041 GEN
Solar/Wind Harmer
36.581
959081AF2-199 GEN
Solar/Wind Harmer
12.194
971067AG2-660 GEN
Solar/Wind Harmer
2.836
940581AE2-045 GEN
Solar/Wind Harmer
12.416
971605AH1-302 GEN
Solar/Wind Harmer
10.616
274822ROCKFORD ;11
Adder
23.883
970819AG2-516 GEN
Solar/Wind Harmer
14.555
274761LEE CO EC;2U
Adder
11.21
274766LEE CO EC;7U
Adder
11.078
24728605AND G2
Adder
3.813
970091AG2-072 GEN
Adder
76.053
972203AH1-686 GEN
Adder
2
970569AG2-363 GEN
Solar/Wind Harmer
0.697
CPLELTFEXP_CPLE->PJM
CLTF
3.244
CBM West 2LTFEXP_CBM-W2->PJM
CBM
120.566
NYPJM->LTFIMP_NY
CLTF
3.761
LGEELTFEXP_LGEE->PJM
CLTF
5.541
WECLTFEXP_WEC->PJM
CLTF
4.639
AG2-052LTFEXP_AG2-052->PJM
LTF
0.286
AH1-155LTFEXP_AH1-155->PJM
LTF
0.429
LAGNLTFEXP_LAGN->PJM
CLTF
16.333
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.048
TVALTFEXP_TVA->PJM
CLTF
7.723
CBM West 1LTFEXP_CBM-W1->PJM
CBM
147.108
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.235
MECLTFEXP_MEC->PJM
CLTF
18.537
SIGELTFEXP_SIGE->PJM
CLTF
0.475

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AP_P2-3_MP-500-021_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-3_MP-500-021_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:128.81 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5888.09
MW Contribution:
59.15
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721705FLATG2
50/50
26.758
270102X2-052 ST
50/50
2.06
270100X2-052 CT1
50/50
1.904
270101X2-052 CT2
50/50
1.904
970349AG2-230 GEN
Solar/Wind Harmer
20.147
965681AG1-436 GEN
Solar/Wind Harmer
16.07
965791AG1-447 GEN
Solar/Wind Harmer
8.222
274770LINCOLN ;1U
Adder
7.933
274771LINCOLN ;2U
Adder
7.933
274805UNIV PK N;1U
Adder
6.332
274808UNIV PK N;4U
Adder
6.29
274888KELLY CRK;1U
Solar/Wind Harmer
7.429
276776AD2-060 GEN
Solar/Wind Harmer
0.527
958011AF2-095 GEN
Solar/Wind Harmer
18.129
970941AG2-585 GEN
Solar/Wind Harmer
6.924
247620Y3-023
Adder
0.579
276897AD1-100 C
Solar/Wind Harmer
58.361
961051AF2-396 GEN
Solar/Wind Harmer
19.886
961051AF2-396 GEN
Solar/Wind Harmer
9.249
274674JOLIET 9 ;6U
Adder
19.282
276893AG1-478 C
Solar/Wind Harmer
0.548
270535AF1-215 GEN1
Solar/Wind Harmer
5.64
270536AF1-215 GEN2
Solar/Wind Harmer
5.64
274695ROCKY RD ;2P
Adder
13.79
274693ROCKY RD ;1P
Adder
13.654
274697ROCKY RD ;3P
Adder
3.746
274696ROCKY RD ;4P
Adder
14.115
958481AF2-142 GEN
Solar/Wind Harmer
18.559
274683WAUKEGAN ;8U
Adder
26.05
274683WAUKEGAN ;8U
Adder
21.959
962691AG1-118 GEN
Solar/Wind Harmer
37.008
960751AF2-366 GEN
Solar/Wind Harmer
3.534
958491AF2-143 GEN
Solar/Wind Harmer
18.433
276901AD2-066 C O1
Solar/Wind Harmer
4.307
971341AH1-150 GEN
Solar/Wind Harmer
24.375
971343AH1-151 GEN
Solar/Wind Harmer
24.375
276872AE1-163_GEN1
Solar/Wind Harmer
8.174
276876AE1-163_GEN2
Solar/Wind Harmer
8.174
972235AH1-702 GEN1
Adder
3.062
972236AH1-702 GEN2
Adder
2.662
274764LEE CO EC;5U
Adder
11.231
274765LEE CO EC;6U
Adder
11.231
274762LEE CO EC;3U
Adder
11.205
274763LEE CO EC;4U
Adder
11.099
247621Y3-024
Adder
0.245
270054AF2-122 C O1
Solar/Wind Helper
1.546
24721605FLATG1
50/50
1.802
270071AF1-092 GEN
Solar/Wind Harmer
19.478
960681AF2-359 GEN
Solar/Wind Harmer
4.858
971771AH1-392 GEN
Solar/Wind Harmer
11.519
274775LINCOLN ;6U
Adder
7.933
274776LINCOLN ;7U
Adder
7.933
274777LINCOLN ;8U
Adder
7.933
270526AF1-158 GEN
Solar/Wind Harmer
5.797
274827FISK ;RP
Adder
9.769
972037AH1-567 GEN1
Adder
0.23
960591AF2-350 GEN
Solar/Wind Harmer
12.59
972228AH1-698 GEN2
Adder
4.663
972227AH1-698 GEN1
Adder
3.283
274800UNIV PARK;3U
Adder
7.337
274801UNIV PARK;4U
Adder
7.337
274687WILL CNTY;4U
Adder
35.043
274687WILL CNTY;4U
Adder
35.043
274675JOLIET 29;7U
Adder
38.457
274675JOLIET 29;7U
Adder
37.084
274728ELWOOD EC;5P
Adder
20.574
274731ELWOOD EC;2P
Adder
20.574
274733ELWOOD EC;3P
Adder
20.574
274735ELWOOD EC;4P
Adder
20.574
970833AG2-524 GEN
Solar/Wind Harmer
10.925
970833AG2-524 GEN
Solar/Wind Harmer
5.082
276893AG1-478 C
Solar/Wind Harmer
0.688
970031AG2-029 GEN
Solar/Wind Harmer
31.241
24729505KEY G4
Adder
8.091
274744AC1-111 GEN8
Adder
6.97
274746AC1-111 G10
Adder
6.97
944161AF1-084 GEN
Solar/Wind Harmer
2.745
970073AG2-061 GEN
Solar/Wind Harmer
2.858
959331AF2-224 GEN
Solar/Wind Harmer
12.267
958391AF2-133 GEN
Solar/Wind Harmer
11.125
971675AH1-338 GEN
Solar/Wind Harmer
22.021
971411AH1-196 GEN
Solar/Wind Harmer
18.349
276861AD2-134 GEN
Solar/Wind Harmer
2.184
276863AD2-134 GEN
Solar/Wind Harmer
2.184
959141AF2-205 GEN
Solar/Wind Harmer
7.39
274863CRW1-WTG
Solar/Wind Harmer
6.811
274864CRW2-WTG
Solar/Wind Harmer
6.811
971171AH1-044 GEN
Solar/Wind Harmer
24.375
276889AE2-281 GEN
Solar/Wind Harmer
2.336
274823ROCKFORD ;21
Adder
23.698
274856ECOGROVE ;U1
Solar/Wind Harmer
4.085
276611AD2-172 GEN
Solar/Wind Harmer
3.098
276612AE2-035 GEN
Solar/Wind Harmer
3.098
926823AC1-168 GEN
Solar/Wind Harmer
5.2
972267AH1-718 GEN
Adder
4.987
24722005FLATG5
50/50
1.802
24721905FLATG4
50/50
32.911
962771AG1-126 GEN
Solar/Wind Harmer
95.791
970153AG2-106 GEN
Solar/Wind Harmer
41.769
971347AH1-153 GEN
Solar/Wind Harmer
6.716
270043AE2-236 GEN
Solar/Wind Harmer
7.208
274772LINCOLN ;3U
Adder
7.933
24441505OLIV SLR
Solar/Wind Harmer
0.171
247643Z2-116 C
Solar/Wind Harmer
0.089
274724RIVER EC ;11
Adder
22.435
944531AF1-118 GEN
Solar/Wind Harmer
44.293
276164X3-005 C
Solar/Wind Harmer
0.888
970707AG2-453 GEN
Solar/Wind Harmer
35.401
972231SS25-0005
Solar/Wind Harmer
11.999
972181SS23-001
Solar/Wind Harmer
7.499
274752CRETE EC ;2U
Adder
6.18
274753CRETE EC ;3U
Adder
6.18
270505AE1-170 C O1
Solar/Wind Harmer
18.937
274814UNIV PK N;0U
Adder
6.373
274807UNIV PK N;3U
Adder
6.359
274811UNIV PK N;7U
Adder
6.318
972259AH1-714 GEN
Adder
24.048
274826FISK ;BP
Adder
13.785
274803UNIV PARK;6U
Adder
7.34
274887GEN-1.85
Solar/Wind Harmer
6.707
276772AC2-154 GEN
Solar/Wind Harmer
3.513
276843GEN-1.7
Solar/Wind Harmer
0.722
276806AD2-047 C O1
Solar/Wind Harmer
13.468
972038AH1-567 GEN2
Adder
0.459
945111AF1-176 GEN
Solar/Wind Harmer
7.115
270063AE2-323 C
Solar/Wind Harmer
2.764
939351AE1-166 GEN
Solar/Wind Harmer
7.451
274676JOLIET 29;8U
Adder
37.084
274729ELWOOD EC;1P
Adder
20.574
274730ELWOOD EC;6P
Adder
20.574
274734ELWOOD EC;8P
Adder
20.574
274736ELWOOD EC;9P
Adder
20.574
943121AE2-341 GEN
Solar/Wind Harmer
18.73
943591AF1-030 GEN
Solar/Wind Harmer
12.486
274682WAUKEGAN ;7U
Adder
22.234
274862TOP CROP ;2U
Solar/Wind Harmer
6.256
964401AG1-302 GEN
Solar/Wind Harmer
11.178
965021AG1-366 GEN
Solar/Wind Harmer
2.853
276868AE1-113 GEN
Solar/Wind Harmer
12.401
274879MINONK ;1U
Solar/Wind Harmer
8.268
276799AD1-013 GEN
Solar/Wind Harmer
2.704
946671AF1-331 GEN
Solar/Wind Harmer
0.512
274855GSG-6 ;RU
Solar/Wind Harmer
4.516
274850MENDOTA H;RU
Solar/Wind Harmer
3.14
276602WESTBROOK C
Solar/Wind Harmer
2.6
959091AF2-200 GEN
Solar/Wind Harmer
24.375
274760LEE CO EC;1U
Adder
11.205
274767LEE CO EC;8U
Adder
11.073
24728705AND G3
Adder
7.969
24728505AND G1
Adder
3.81
970571AG2-364 GEN
Solar/Wind Harmer
0.464
24721805FLATG3
50/50
1.802
24344105CKG2
50/50
10.299
962761AG1-125 GEN
Solar/Wind Harmer
95.791
970149AG2-104 GEN
Solar/Wind Harmer
59.151
970155AG2-107 GEN
Solar/Wind Harmer
41.769
972207SS24-0001
Solar/Wind Harmer
28.206
274773LINCOLN ;4U
Adder
7.933
274774LINCOLN ;5U
Adder
7.933
270216AD2-079_GEN
Solar/Wind Harmer
0.771
274723RIVER EC ;12
Adder
22.697
24639705ELKHART HY
Adder
0.194
274751CRETE EC ;1U
Adder
6.18
274754CRETE EC ;4U
Adder
6.18
957891AF2-083 GEN
Solar/Wind Harmer
18.925
274812UNIV PK N;8U
Adder
6.318
274802UNIV PARK;5U
Adder
7.34
945111AF1-176 GEN
Solar/Wind Harmer
22.45
941551AE2-152 GEN
Solar/Wind Harmer
5.698
970373AG2-245 GEN
Solar/Wind Harmer
26.34
274676JOLIET 29;8U
Adder
38.457
274674JOLIET 9 ;6U
Adder
19.282
274732ELWOOD EC;7P
Adder
20.574
274871GR RIDGE ;2U
Solar/Wind Harmer
9.62
274847GR RIDGE ;BU
Solar/Wind Harmer
6.326
270449AD2-020 GEN
Solar/Wind Harmer
3.502
943021AE2-325 GEN
Solar/Wind Harmer
4.551
274745AC1-111 GEN9
Adder
6.97
270055AF2-134 C O1
Solar/Wind Harmer
3.76
276694AA1-018 GEN2
Solar/Wind Harmer
7.807
276691AA1-018 GEN1
Solar/Wind Harmer
0.933
274682WAUKEGAN ;7U
Adder
22.234
274861TOP CROP ;1U
Solar/Wind Harmer
7.493
274828WAUKEGAN ;BP
Adder
13.655
958381AF2-132 GEN
Solar/Wind Harmer
11.178
962781AG1-127 GEN
Solar/Wind Harmer
11.715
964861AG1-349 GEN
Solar/Wind Harmer
9.678
971917AH1-482 GEN
Solar/Wind Harmer
11.166
939401AE1-172 GEN
Solar/Wind Harmer
17.153
274872LEEDK;1U
Solar/Wind Harmer
10.099
276805AD2-038 GEN
Solar/Wind Harmer
6.302
965011AG1-365 GEN
Solar/Wind Harmer
12.267
24441205WTRV SLR C
Solar/Wind Harmer
0.165
276882AE2-255 GEN
Solar/Wind Harmer
4.134
971997AH1-543 GEN
Solar/Wind Harmer
19.288
957471AF2-041 GEN
Solar/Wind Harmer
36.563
959081AF2-199 GEN
Solar/Wind Harmer
12.188
971067AG2-660 GEN
Solar/Wind Harmer
2.834
940581AE2-045 GEN
Solar/Wind Harmer
12.41
971605AH1-302 GEN
Solar/Wind Harmer
10.611
274822ROCKFORD ;11
Adder
23.871
970819AG2-516 GEN
Solar/Wind Harmer
14.548
274761LEE CO EC;2U
Adder
11.205
274766LEE CO EC;7U
Adder
11.073
24728605AND G2
Adder
3.81
970091AG2-072 GEN
Adder
76.004
972203AH1-686 GEN
Adder
1.999
970569AG2-363 GEN
Solar/Wind Harmer
0.696
CPLELTFEXP_CPLE->PJM
CLTF
3.243
CBM West 2LTFEXP_CBM-W2->PJM
CBM
120.494
NYPJM->LTFIMP_NY
CLTF
3.758
LGEELTFEXP_LGEE->PJM
CLTF
5.537
WECLTFEXP_WEC->PJM
CLTF
4.637
AG2-052LTFEXP_AG2-052->PJM
LTF
0.286
AH1-155LTFEXP_AH1-155->PJM
LTF
0.429
LAGNLTFEXP_LAGN->PJM
CLTF
16.323
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.041
TVALTFEXP_TVA->PJM
CLTF
7.718
CBM West 1LTFEXP_CBM-W1->PJM
CBM
147.021
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.216
MECLTFEXP_MEC->PJM
CLTF
18.527
SIGELTFEXP_SIGE->PJM
CLTF
0.475

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AEP_P4_#37_05MOUNTN 765_B1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:128.8 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5887.55
MW Contribution:
59.15
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721705FLATG2
50/50
26.753
270102X2-052 ST
50/50
2.06
270100X2-052 CT1
50/50
1.903
270101X2-052 CT2
50/50
1.903
970349AG2-230 GEN
Solar/Wind Harmer
20.143
965681AG1-436 GEN
Solar/Wind Harmer
16.067
965791AG1-447 GEN
Solar/Wind Harmer
8.22
274770LINCOLN ;1U
Adder
7.932
274771LINCOLN ;2U
Adder
7.932
274805UNIV PK N;1U
Adder
6.33
274808UNIV PK N;4U
Adder
6.289
274888KELLY CRK;1U
Solar/Wind Harmer
7.428
276776AD2-060 GEN
Solar/Wind Harmer
0.527
958011AF2-095 GEN
Solar/Wind Harmer
18.125
970941AG2-585 GEN
Solar/Wind Harmer
6.923
247620Y3-023
Adder
0.579
276897AD1-100 C
Solar/Wind Harmer
58.349
961051AF2-396 GEN
Solar/Wind Harmer
19.882
961051AF2-396 GEN
Solar/Wind Harmer
9.247
274674JOLIET 9 ;6U
Adder
19.278
276893AG1-478 C
Solar/Wind Harmer
0.548
24721605FLATG1
50/50
1.801
270071AF1-092 GEN
Solar/Wind Harmer
19.474
960681AF2-359 GEN
Solar/Wind Harmer
4.857
971771AH1-392 GEN
Solar/Wind Harmer
11.517
274775LINCOLN ;6U
Adder
7.932
274776LINCOLN ;7U
Adder
7.932
274777LINCOLN ;8U
Adder
7.932
270526AF1-158 GEN
Solar/Wind Harmer
5.796
274827FISK ;RP
Adder
9.767
972037AH1-567 GEN1
Adder
0.23
960591AF2-350 GEN
Solar/Wind Harmer
12.587
972228AH1-698 GEN2
Adder
4.662
972227AH1-698 GEN1
Adder
3.283
274800UNIV PARK;3U
Adder
7.336
274801UNIV PARK;4U
Adder
7.336
274687WILL CNTY;4U
Adder
35.036
274687WILL CNTY;4U
Adder
35.036
274675JOLIET 29;7U
Adder
38.449
24722005FLATG5
50/50
1.801
24721905FLATG4
50/50
32.904
962771AG1-126 GEN
Solar/Wind Harmer
95.781
970153AG2-106 GEN
Solar/Wind Harmer
41.765
971347AH1-153 GEN
Solar/Wind Harmer
6.714
270043AE2-236 GEN
Solar/Wind Harmer
7.206
274772LINCOLN ;3U
Adder
7.932
24441505OLIV SLR
Solar/Wind Harmer
0.171
247643Z2-116 C
Solar/Wind Harmer
0.089
274724RIVER EC ;11
Adder
22.43
944531AF1-118 GEN
Solar/Wind Harmer
44.283
276164X3-005 C
Solar/Wind Harmer
0.888
970707AG2-453 GEN
Solar/Wind Harmer
35.393
972231SS25-0005
Solar/Wind Harmer
11.996
972181SS23-001
Solar/Wind Harmer
7.498
274752CRETE EC ;2U
Adder
6.178
274753CRETE EC ;3U
Adder
6.178
270505AE1-170 C O1
Solar/Wind Harmer
18.933
274814UNIV PK N;0U
Adder
6.372
274807UNIV PK N;3U
Adder
6.358
274675JOLIET 29;7U
Adder
37.076
274728ELWOOD EC;5P
Adder
20.57
274731ELWOOD EC;2P
Adder
20.57
274733ELWOOD EC;3P
Adder
20.57
274735ELWOOD EC;4P
Adder
20.57
970833AG2-524 GEN
Solar/Wind Harmer
10.923
970833AG2-524 GEN
Solar/Wind Harmer
5.081
276893AG1-478 C
Solar/Wind Harmer
0.688
970031AG2-029 GEN
Solar/Wind Harmer
31.234
24729505KEY G4
Adder
8.09
274744AC1-111 GEN8
Adder
6.969
274746AC1-111 G10
Adder
6.969
944161AF1-084 GEN
Solar/Wind Harmer
2.745
970073AG2-061 GEN
Solar/Wind Harmer
2.857
959331AF2-224 GEN
Solar/Wind Harmer
12.264
958391AF2-133 GEN
Solar/Wind Harmer
11.123
971675AH1-338 GEN
Solar/Wind Harmer
22.016
971411AH1-196 GEN
Solar/Wind Harmer
18.345
276861AD2-134 GEN
Solar/Wind Harmer
2.183
276863AD2-134 GEN
Solar/Wind Harmer
2.183
959141AF2-205 GEN
Solar/Wind Harmer
7.389
274863CRW1-WTG
Solar/Wind Harmer
6.809
274864CRW2-WTG
Solar/Wind Harmer
6.809
971171AH1-044 GEN
Solar/Wind Harmer
24.37
276889AE2-281 GEN
Solar/Wind Harmer
2.335
274823ROCKFORD ;21
Adder
23.693
274856ECOGROVE ;U1
Solar/Wind Harmer
4.084
276611AD2-172 GEN
Solar/Wind Harmer
3.098
276612AE2-035 GEN
Solar/Wind Harmer
3.098
926823AC1-168 GEN
Solar/Wind Harmer
5.199
972267AH1-718 GEN
Adder
4.986
270535AF1-215 GEN1
Solar/Wind Harmer
5.639
270536AF1-215 GEN2
Solar/Wind Harmer
5.639
274696ROCKY RD ;4P
Adder
14.112
274695ROCKY RD ;2P
Adder
13.787
274693ROCKY RD ;1P
Adder
13.651
274697ROCKY RD ;3P
Adder
3.745
958481AF2-142 GEN
Solar/Wind Harmer
18.555
274683WAUKEGAN ;8U
Adder
26.045
274683WAUKEGAN ;8U
Adder
21.955
962691AG1-118 GEN
Solar/Wind Harmer
37
960751AF2-366 GEN
Solar/Wind Harmer
3.533
958491AF2-143 GEN
Solar/Wind Harmer
18.429
276901AD2-066 C O1
Solar/Wind Harmer
4.306
971341AH1-150 GEN
Solar/Wind Harmer
24.37
971343AH1-151 GEN
Solar/Wind Harmer
24.37
276872AE1-163_GEN1
Solar/Wind Harmer
8.172
276876AE1-163_GEN2
Solar/Wind Harmer
8.172
972235AH1-702 GEN1
Adder
3.061
972236AH1-702 GEN2
Adder
2.662
274764LEE CO EC;5U
Adder
11.229
274765LEE CO EC;6U
Adder
11.229
274762LEE CO EC;3U
Adder
11.202
274763LEE CO EC;4U
Adder
11.097
247621Y3-024
Adder
0.245
270054AF2-122 C O1
Solar/Wind Helper
1.547
274811UNIV PK N;7U
Adder
6.317
972259AH1-714 GEN
Adder
24.043
274826FISK ;BP
Adder
13.782
274803UNIV PARK;6U
Adder
7.339
274887GEN-1.85
Solar/Wind Harmer
6.706
276772AC2-154 GEN
Solar/Wind Harmer
3.513
276843GEN-1.7
Solar/Wind Harmer
0.722
276806AD2-047 C O1
Solar/Wind Harmer
13.465
972038AH1-567 GEN2
Adder
0.459
945111AF1-176 GEN
Solar/Wind Harmer
7.113
270063AE2-323 C
Solar/Wind Harmer
2.763
939351AE1-166 GEN
Solar/Wind Harmer
7.449
274676JOLIET 29;8U
Adder
37.076
274729ELWOOD EC;1P
Adder
20.57
274730ELWOOD EC;6P
Adder
20.57
274734ELWOOD EC;8P
Adder
20.57
274736ELWOOD EC;9P
Adder
20.57
943121AE2-341 GEN
Solar/Wind Harmer
18.726
943591AF1-030 GEN
Solar/Wind Harmer
12.484
274682WAUKEGAN ;7U
Adder
22.229
274862TOP CROP ;2U
Solar/Wind Harmer
6.254
964401AG1-302 GEN
Solar/Wind Harmer
11.176
965021AG1-366 GEN
Solar/Wind Harmer
2.852
276868AE1-113 GEN
Solar/Wind Harmer
12.399
274879MINONK ;1U
Solar/Wind Harmer
8.266
276799AD1-013 GEN
Solar/Wind Harmer
2.703
946671AF1-331 GEN
Solar/Wind Harmer
0.512
274855GSG-6 ;RU
Solar/Wind Harmer
4.515
274850MENDOTA H;RU
Solar/Wind Harmer
3.139
276602WESTBROOK C
Solar/Wind Harmer
2.599
959091AF2-200 GEN
Solar/Wind Harmer
24.37
274760LEE CO EC;1U
Adder
11.202
274767LEE CO EC;8U
Adder
11.07
24728705AND G3
Adder
7.966
24728505AND G1
Adder
3.809
970571AG2-364 GEN
Solar/Wind Harmer
0.464
24721805FLATG3
50/50
1.801
24344105CKG2
50/50
10.297
962761AG1-125 GEN
Solar/Wind Harmer
95.781
970149AG2-104 GEN
Solar/Wind Harmer
59.145
970155AG2-107 GEN
Solar/Wind Harmer
41.765
972207SS24-0001
Solar/Wind Harmer
28.2
274773LINCOLN ;4U
Adder
7.932
274774LINCOLN ;5U
Adder
7.932
270216AD2-079_GEN
Solar/Wind Harmer
0.771
274723RIVER EC ;12
Adder
22.692
24639705ELKHART HY
Adder
0.194
274751CRETE EC ;1U
Adder
6.178
274754CRETE EC ;4U
Adder
6.178
957891AF2-083 GEN
Solar/Wind Harmer
18.921
274812UNIV PK N;8U
Adder
6.317
274802UNIV PARK;5U
Adder
7.339
945111AF1-176 GEN
Solar/Wind Harmer
22.445
941551AE2-152 GEN
Solar/Wind Harmer
5.697
970373AG2-245 GEN
Solar/Wind Harmer
26.334
274676JOLIET 29;8U
Adder
38.449
274674JOLIET 9 ;6U
Adder
19.278
274732ELWOOD EC;7P
Adder
20.57
274871GR RIDGE ;2U
Solar/Wind Harmer
9.618
274847GR RIDGE ;BU
Solar/Wind Harmer
6.324
270449AD2-020 GEN
Solar/Wind Harmer
3.501
943021AE2-325 GEN
Solar/Wind Harmer
4.55
274745AC1-111 GEN9
Adder
6.969
270055AF2-134 C O1
Solar/Wind Harmer
3.759
276694AA1-018 GEN2
Solar/Wind Harmer
7.805
276691AA1-018 GEN1
Solar/Wind Harmer
0.933
274682WAUKEGAN ;7U
Adder
22.229
274861TOP CROP ;1U
Solar/Wind Harmer
7.491
274828WAUKEGAN ;BP
Adder
13.652
958381AF2-132 GEN
Solar/Wind Harmer
11.176
962781AG1-127 GEN
Solar/Wind Harmer
11.712
964861AG1-349 GEN
Solar/Wind Harmer
9.676
971917AH1-482 GEN
Solar/Wind Harmer
11.164
939401AE1-172 GEN
Solar/Wind Harmer
17.149
274872LEEDK;1U
Solar/Wind Harmer
10.097
276805AD2-038 GEN
Solar/Wind Harmer
6.3
965011AG1-365 GEN
Solar/Wind Harmer
12.264
24441205WTRV SLR C
Solar/Wind Harmer
0.165
276882AE2-255 GEN
Solar/Wind Harmer
4.133
971997AH1-543 GEN
Solar/Wind Harmer
19.284
957471AF2-041 GEN
Solar/Wind Harmer
36.555
959081AF2-199 GEN
Solar/Wind Harmer
12.185
971067AG2-660 GEN
Solar/Wind Harmer
2.834
940581AE2-045 GEN
Solar/Wind Harmer
12.407
971605AH1-302 GEN
Solar/Wind Harmer
10.609
274822ROCKFORD ;11
Adder
23.866
970819AG2-516 GEN
Solar/Wind Harmer
14.545
274761LEE CO EC;2U
Adder
11.202
274766LEE CO EC;7U
Adder
11.07
24728605AND G2
Adder
3.809
970091AG2-072 GEN
Adder
75.982
972203AH1-686 GEN
Adder
1.998
970569AG2-363 GEN
Solar/Wind Harmer
0.696
CPLELTFEXP_CPLE->PJM
CLTF
3.243
CBM West 2LTFEXP_CBM-W2->PJM
CBM
120.462
NYPJM->LTFIMP_NY
CLTF
3.757
LGEELTFEXP_LGEE->PJM
CLTF
5.535
WECLTFEXP_WEC->PJM
CLTF
4.636
AG2-052LTFEXP_AG2-052->PJM
LTF
0.286
AH1-155LTFEXP_AH1-155->PJM
LTF
0.429
LAGNLTFEXP_LAGN->PJM
CLTF
16.319
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.038
TVALTFEXP_TVA->PJM
CLTF
7.716
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.983
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.207
MECLTFEXP_MEC->PJM
CLTF
18.523
SIGELTFEXP_SIGE->PJM
CLTF
0.475

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AP_P1-3_MP-765-501T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:126.31 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5773.71
MW Contribution:
43.62
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
1.801
270071AF1-092 GEN
Solar/Wind Harmer
17.36
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971771AH1-392 GEN
Solar/Wind Harmer
8.928
274775LINCOLN ;6U
Adder
10.797
274776LINCOLN ;7U
Adder
10.797
274777LINCOLN ;8U
Adder
10.797
270526AF1-158 GEN
Solar/Wind Harmer
0.001
274827FISK ;RP
Adder
9.767
972037AH1-567 GEN1
Adder
0.23
960591AF2-350 GEN
Solar/Wind Harmer
8.782
972228AH1-698 GEN2
Adder
4.662
972227AH1-698 GEN1
Adder
3.283
274800UNIV PARK;3U
Adder
7.336
274801UNIV PARK;4U
Adder
7.336
274687WILL CNTY;4U
Adder
35.036
274687WILL CNTY;4U
Adder
35.036
274675JOLIET 29;7U
Adder
38.449
274675JOLIET 29;7U
Adder
37.076
274728ELWOOD EC;5P
Adder
20.57
274731ELWOOD EC;2P
Adder
20.57
274733ELWOOD EC;3P
Adder
20.57
274735ELWOOD EC;4P
Adder
20.57
970833AG2-524 GEN
Solar/Wind Harmer
9.602
970833AG2-524 GEN
Solar/Wind Harmer
6.401
970031AG2-029 GEN
Solar/Wind Harmer
4.721
24729505KEY G4
Adder
8.09
274744AC1-111 GEN8
Adder
6.969
274746AC1-111 G10
Adder
6.969
970073AG2-061 GEN
Solar/Wind Harmer
2.857
959331AF2-224 GEN
Solar/Wind Harmer
5.989
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
3.328
971411AH1-196 GEN
Solar/Wind Harmer
12.799
276861AD2-134 GEN
Solar/Wind Harmer
0.152
276863AD2-134 GEN
Solar/Wind Harmer
0.152
959141AF2-205 GEN
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
17.002
971611AH1-305 GEN
Solar/Wind Harmer
5.053
274823ROCKFORD ;21
Adder
23.693
274856ECOGROVE ;U1
Solar/Wind Harmer
0.197
926823AC1-168 GEN
Solar/Wind Harmer
1.434
970169AG2-114 GEN
Solar/Wind Harmer
8.435
971681AH1-341 GEN
Solar/Wind Harmer
13.557
972267AH1-718 GEN
Adder
4.986
276741O09 GEN1
Solar/Wind Harmer
0.295
274877BISHOP HL;1U
Solar/Wind Harmer
0.277
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
24722005FLATG5
50/50
1.801
24721905FLATG4
50/50
32.904
962771AG1-126 GEN
Solar/Wind Harmer
80.774
970153AG2-106 GEN
Solar/Wind Harmer
51.58
971347AH1-153 GEN
Solar/Wind Harmer
4.684
270043AE2-236 GEN
Solar/Wind Harmer
5.865
274772LINCOLN ;3U
Adder
10.797
274724RIVER EC ;11
Adder
22.43
944531AF1-118 GEN
Solar/Wind Harmer
39.561
970707AG2-453 GEN
Solar/Wind Harmer
28.808
274752CRETE EC ;2U
Adder
10.415
274753CRETE EC ;3U
Adder
10.415
270505AE1-170 C O1
Solar/Wind Harmer
9.246
274814UNIV PK N;0U
Adder
6.372
274807UNIV PK N;3U
Adder
6.358
274811UNIV PK N;7U
Adder
6.317
972259AH1-714 GEN
Adder
24.043
274826FISK ;BP
Adder
13.782
274803UNIV PARK;6U
Adder
7.339
274887GEN-1.85
Solar/Wind Harmer
0.228
276843GEN-1.7
Solar/Wind Harmer
0.284
276806AD2-047 C O1
Solar/Wind Harmer
4.976
972038AH1-567 GEN2
Adder
0.459
945111AF1-176 GEN
Solar/Wind Harmer
7.113
270063AE2-323 C
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
37.076
274729ELWOOD EC;1P
Adder
20.57
274730ELWOOD EC;6P
Adder
20.57
274734ELWOOD EC;8P
Adder
20.57
274736ELWOOD EC;9P
Adder
20.57
943121AE2-341 GEN
Solar/Wind Harmer
14.603
943591AF1-030 GEN
Solar/Wind Harmer
9.711
274682WAUKEGAN ;7U
Adder
22.229
274862TOP CROP ;2U
Solar/Wind Harmer
1.165
964401AG1-302 GEN
Solar/Wind Harmer
0.001
965021AG1-366 GEN
Solar/Wind Harmer
2.852
276868AE1-113 GEN
Solar/Wind Harmer
1.71
274879MINONK ;1U
Solar/Wind Harmer
0.357
946671AF1-331 GEN
Solar/Wind Harmer
0.91
274855GSG-6 ;RU
Solar/Wind Harmer
0.311
274850MENDOTA H;RU
Solar/Wind Harmer
0.099
959091AF2-200 GEN
Solar/Wind Harmer
17.002
970571AG2-364 GEN
Solar/Wind Harmer
16.871
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
11.202
274767LEE CO EC;8U
Adder
11.07
276782AC1-033 GEN
Solar/Wind Harmer
0
24721705FLATG2
50/50
26.753
270102X2-052 ST
50/50
2.06
270100X2-052 CT1
50/50
1.903
270101X2-052 CT2
50/50
1.903
970349AG2-230 GEN
Solar/Wind Harmer
14.053
965681AG1-436 GEN
Solar/Wind Harmer
11.209
965791AG1-447 GEN
Solar/Wind Harmer
8.22
274770LINCOLN ;1U
Adder
10.797
274771LINCOLN ;2U
Adder
10.797
274805UNIV PK N;1U
Adder
6.33
274808UNIV PK N;4U
Adder
6.289
274888KELLY CRK;1U
Solar/Wind Harmer
0.512
276776AD2-060 GEN
Solar/Wind Harmer
0.937
958011AF2-095 GEN
Solar/Wind Harmer
12.646
970941AG2-585 GEN
Solar/Wind Harmer
4.83
247620Y3-023
Adder
0.579
276897AD1-100 C
Solar/Wind Harmer
21.908
961051AF2-396 GEN
Solar/Wind Harmer
17.478
961051AF2-396 GEN
Solar/Wind Harmer
11.652
274674JOLIET 9 ;6U
Adder
19.278
276893AG1-478 C
Solar/Wind Harmer
0.582
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274696ROCKY RD ;4P
Adder
14.112
274695ROCKY RD ;2P
Adder
13.787
274693ROCKY RD ;1P
Adder
13.651
274697ROCKY RD ;3P
Adder
3.745
958481AF2-142 GEN
Solar/Wind Harmer
12.945
274683WAUKEGAN ;8U
Adder
26.045
274683WAUKEGAN ;8U
Adder
21.955
962691AG1-118 GEN
Solar/Wind Harmer
25.814
958491AF2-143 GEN
Solar/Wind Harmer
12.858
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
17.002
971343AH1-151 GEN
Solar/Wind Harmer
17.002
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
3.061
24721805FLATG3
50/50
1.801
24344105CKG2
50/50
10.297
962761AG1-125 GEN
Solar/Wind Harmer
80.774
970149AG2-104 GEN
Solar/Wind Harmer
43.619
970155AG2-107 GEN
Solar/Wind Harmer
51.58
274773LINCOLN ;4U
Adder
10.797
274774LINCOLN ;5U
Adder
10.797
274723RIVER EC ;12
Adder
22.692
24639705ELKHART HY
Adder
0.194
274751CRETE EC ;1U
Adder
10.415
274754CRETE EC ;4U
Adder
10.415
957891AF2-083 GEN
Solar/Wind Harmer
14.667
274812UNIV PK N;8U
Adder
6.317
274802UNIV PARK;5U
Adder
7.339
945111AF1-176 GEN
Solar/Wind Harmer
15.659
941551AE2-152 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
18.373
274676JOLIET 29;8U
Adder
38.449
274674JOLIET 9 ;6U
Adder
19.278
274732ELWOOD EC;7P
Adder
20.57
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
4.55
274745AC1-111 GEN9
Adder
6.969
270055AF2-134 C O1
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.402
274682WAUKEGAN ;7U
Adder
22.229
274861TOP CROP ;1U
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
13.652
958381AF2-132 GEN
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
8.177
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.164
939401AE1-172 GEN
Solar/Wind Harmer
6.422
972236AH1-702 GEN2
Adder
2.662
938861AE1-114 GEN
Solar/Wind Harmer
4.771
274764LEE CO EC;5U
Adder
11.229
274765LEE CO EC;6U
Adder
11.229
274762LEE CO EC;3U
Adder
11.202
274763LEE CO EC;4U
Adder
11.097
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.557
960971AF2-388 GEN
Solar/Wind Harmer
4.897
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.346
276645AC1-214 GEN1
Solar/Wind Harmer
0.327
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
2.686
960611AF2-352 GEN
Solar/Wind Harmer
2.728
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.921
942221AE2-234 GEN
Solar/Wind Harmer
3.241
970241AG2-163 GEN
Solar/Wind Harmer
4.6
276615X2-022 GEN
Solar/Wind Harmer
0.081
276838X2-022 GEN2
Solar/Wind Harmer
0.442
970291AG2-192 GEN
Solar/Wind Harmer
1.017
970291AG2-192 GEN
Solar/Wind Harmer
0.469
270031AE2-169
Solar/Wind Harmer
4.257
270599AE1-208 GEN
Solar/Wind Harmer
7.096
971613AH1-306 GEN
Solar/Wind Harmer
3.702
276916AD2-100_GEN
Solar/Wind Harmer
16.116
276911AD2-131_GEN
Solar/Wind Harmer
1.062
270246TR4_N_V150
Solar/Wind Harmer
0.049
270247TR4_N_V136
Solar/Wind Harmer
0.049
944231AF1-091 GEN
Solar/Wind Harmer
17.5
945391AF1-204 GEN
Solar/Wind Harmer
7.946
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.549
270201AC2-176 GEN
Solar/Wind Harmer
0
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
971587AH1-292 GEN
Solar/Wind Harmer
5.222
247621Y3-024
Adder
0.245
926881AC1-175 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.284
270383AD1-128 GEN
Solar/Wind Harmer
0
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.232
970883AG2-550 GEN
Solar/Wind Harmer
6.689
970885AG2-551 GEN
Solar/Wind Harmer
2.23
270054AF2-122 C O1
Solar/Wind Helper
1.547
274872LEEDK;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
965011AG1-365 GEN
Solar/Wind Harmer
8.556
276882AE2-255 GEN
Solar/Wind Harmer
0.998
971997AH1-543 GEN
Solar/Wind Harmer
4.485
957471AF2-041 GEN
Solar/Wind Harmer
25.504
959081AF2-199 GEN
Solar/Wind Harmer
8.501
971067AG2-660 GEN
Solar/Wind Harmer
2.834
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
10.609
274822ROCKFORD ;11
Adder
23.866
970819AG2-516 GEN
Solar/Wind Harmer
10.148
970569AG2-363 GEN
Solar/Wind Harmer
25.306
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
11.202
274766LEE CO EC;7U
Adder
11.07
965651AG1-433 GEN
Solar/Wind Harmer
2.449
276708O09 GEN2
Solar/Wind Harmer
0.295
276646AC1-214 GEN2
Solar/Wind Harmer
0.327
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
11.569
958861AF2-177 GEN
Solar/Wind Harmer
3.567
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
18.662
276621W2-048 GEN
Solar/Wind Harmer
0.393
270594AE1-207 GEN
Solar/Wind Harmer
8.639
270032AE2-172
Solar/Wind Harmer
5.142
965911AG1-460 GEN
Solar/Wind Harmer
1.542
270024AE2-089 GEN
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
8.459
270005AE1-210 C O1
Solar/Wind Harmer
1.624
970825AG2-519 GEN
Solar/Wind Harmer
2.629
965421AG1-410 GEN
Solar/Wind Harmer
21.55
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.196
246936BC-WTG1
Solar/Wind Harmer
0.284
270489AE1-102 GEN1
Solar/Wind Harmer
0.915
24728605AND G2
Adder
3.809
970091AG2-072 GEN
Adder
75.982
970773AG2-487 GEN
Solar/Wind Harmer
1.155
972203AH1-686 GEN
Adder
1.998
959341AF2-225 GEN
Solar/Wind Harmer
8.677
946321AF1-296 GEN
Solar/Wind Harmer
4.601
274854TWINGROVE;U2
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
10.858
945581AF1-223 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
3.469
276668AB2-070 GEN1
Solar/Wind Harmer
0.312
276848AB2-070 GEN3
Solar/Wind Harmer
0.31
276849AB2-070 GEN2
Solar/Wind Harmer
0.312
971549AH1-272 GEN
Solar/Wind Harmer
16.367
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
965041AG1-368 GEN
Solar/Wind Harmer
7.859
970289AG2-191 GEN
Solar/Wind Harmer
1.486
971609AH1-304 GEN
Solar/Wind Harmer
1.264
247521TR3_G114
Solar/Wind Harmer
0.275
965051AG1-369 GEN
Solar/Wind Harmer
3.795
944221AF1-090 GEN
Solar/Wind Harmer
4.432
964611AG1-324 GEN
Solar/Wind Harmer
2.855
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.891
247536S-71 GEN
Solar/Wind Harmer
0.278
270007AE1-245 C
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
4.682
270356AE2-297 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
9.586
270578AF1-285 GEN2
Solar/Wind Harmer
0.405
274878BISHOP HL;2U
Solar/Wind Harmer
0.277
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
8.302
965931AG1-462 GEN
Solar/Wind Harmer
20.885
971087AG2-675 GEN
Solar/Wind Harmer
4.368
965091AG1-374 GEN
Solar/Wind Harmer
24.551
959611AF2-252 GEN
Solar/Wind Harmer
2.728
24386205FR-12G C
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
3.663
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.86
957381AF2-032 GEN
Solar/Wind Harmer
1.75
942481AE2-261 GEN
Solar/Wind Harmer
23.05
270004AE1-209 GEN
Solar/Wind Harmer
1.624
970193AG2-126 GEN
Solar/Wind Harmer
11.218
24695305TIMB G C
Solar/Wind Harmer
0.627
970825AG2-519 GEN
Solar/Wind Harmer
5.579
946031AF1-268 GEN
Solar/Wind Harmer
6.994
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.967
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.253
270491AE1-102 GEN2
Solar/Wind Harmer
0.915
24728705AND G3
Adder
7.966
24728505AND G1
Adder
3.809
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
270391AF1-285 GEN3
Solar/Wind Harmer
0.405
CPLELTFEXP_CPLE->PJM
CLTF
3.243
CBM West 2LTFEXP_CBM-W2->PJM
CBM
120.462
NYPJM->LTFIMP_NY
CLTF
3.757
LGEELTFEXP_LGEE->PJM
CLTF
5.535
WECLTFEXP_WEC->PJM
CLTF
4.636
AG2-052LTFEXP_AG2-052->PJM
LTF
0.286
AH1-155LTFEXP_AH1-155->PJM
LTF
0.429
LAGNLTFEXP_LAGN->PJM
CLTF
16.319
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.038
TVALTFEXP_TVA->PJM
CLTF
7.716
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.983
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.207
MECLTFEXP_MEC->PJM
CLTF
18.523
SIGELTFEXP_SIGE->PJM
CLTF
0.475

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AEP_P4_#8085_05MARYSV 345_H_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#8085_05MARYSV 345_H_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.38 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5411.14
MW Contribution:
69.03
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
1.47
960681AF2-359 GEN
Solar/Wind Harmer
4.306
274775LINCOLN ;6U
Adder
7.038
274776LINCOLN ;7U
Adder
7.038
274777LINCOLN ;8U
Adder
7.038
971771AH1-392 GEN
Solar/Wind Harmer
10.162
270526AF1-158 GEN
Solar/Wind Harmer
5.119
270071AF1-092 GEN
Solar/Wind Harmer
16.74
274827FISK ;RP
Adder
8.593
972228AH1-698 GEN2
Adder
4.102
972227AH1-698 GEN1
Adder
2.888
960591AF2-350 GEN
Solar/Wind Harmer
11.072
972037AH1-567 GEN1
Adder
0.203
274800UNIV PARK;3U
Adder
6.452
274801UNIV PARK;4U
Adder
6.452
274687WILL CNTY;4U
Adder
30.779
274687WILL CNTY;4U
Adder
30.779
274675JOLIET 29;7U
Adder
33.773
274675JOLIET 29;7U
Adder
32.567
274728ELWOOD EC;5P
Adder
18.053
274731ELWOOD EC;2P
Adder
18.053
274733ELWOOD EC;3P
Adder
18.053
274735ELWOOD EC;4P
Adder
18.053
970833AG2-524 GEN
Solar/Wind Harmer
9.588
970833AG2-524 GEN
Solar/Wind Harmer
4.46
276893AG1-478 C
Solar/Wind Harmer
0.604
274744AC1-111 GEN8
Adder
6.112
274746AC1-111 G10
Adder
6.112
944161AF1-084 GEN
Solar/Wind Harmer
2.398
970073AG2-061 GEN
Solar/Wind Harmer
2.486
971675AH1-338 GEN
Solar/Wind Harmer
19.15
971411AH1-196 GEN
Solar/Wind Harmer
15.957
276861AD2-134 GEN
Solar/Wind Harmer
1.899
276863AD2-134 GEN
Solar/Wind Harmer
1.899
971171AH1-044 GEN
Solar/Wind Harmer
21.162
274863CRW1-WTG
Solar/Wind Harmer
5.893
274864CRW2-WTG
Solar/Wind Harmer
5.893
274823ROCKFORD ;21
Adder
20.558
276889AE2-281 GEN
Solar/Wind Harmer
2.023
958391AF2-133 GEN
Solar/Wind Harmer
9.55
24729505KEY G4
Adder
6.806
274856ECOGROVE ;U1
Solar/Wind Harmer
3.537
276611AD2-172 GEN
Solar/Wind Harmer
2.683
276612AE2-035 GEN
Solar/Wind Harmer
2.683
970031AG2-029 GEN
Solar/Wind Harmer
26.201
959141AF2-205 GEN
Solar/Wind Harmer
6.328
926823AC1-168 GEN
Solar/Wind Harmer
4.489
972267AH1-718 GEN
Adder
4.296
241955AC1-078 GEN
Solar/Wind Helper
2.364
241973AD2-163_GEN1
Solar/Wind Helper
1.917
241974AD2-163_GEN2
Solar/Wind Helper
1.917
945631AF1-228 GEN
Solar/Wind Helper
1.875
24344105CKG2
50/50
9.476
24721805FLATG3
50/50
1.47
962761AG1-125 GEN
Solar/Wind Harmer
111.791
970149AG2-104 GEN
Solar/Wind Harmer
69.031
970155AG2-107 GEN
Solar/Wind Harmer
48.746
972207SS24-0001
Solar/Wind Harmer
25.024
274773LINCOLN ;4U
Adder
7.038
274774LINCOLN ;5U
Adder
7.038
270216AD2-079_GEN
Solar/Wind Harmer
0.676
274723RIVER EC ;12
Adder
20.004
274751CRETE EC ;1U
Adder
5.439
274754CRETE EC ;4U
Adder
5.439
274812UNIV PK N;8U
Adder
5.558
274802UNIV PARK;5U
Adder
6.455
957891AF2-083 GEN
Solar/Wind Harmer
16.598
941551AE2-152 GEN
Solar/Wind Harmer
5.007
24639705ELKHART HY
Adder
0.169
274676JOLIET 29;8U
Adder
33.772
945111AF1-176 GEN
Solar/Wind Harmer
19.629
274674JOLIET 9 ;6U
Adder
16.926
274732ELWOOD EC;7P
Adder
18.053
274871GR RIDGE ;2U
Solar/Wind Harmer
8.442
274847GR RIDGE ;BU
Solar/Wind Harmer
5.551
274745AC1-111 GEN9
Adder
6.112
970373AG2-245 GEN
Solar/Wind Harmer
22.961
270449AD2-020 GEN
Solar/Wind Harmer
3.064
943021AE2-325 GEN
Solar/Wind Harmer
3.981
274682WAUKEGAN ;7U
Adder
19.427
274828WAUKEGAN ;BP
Adder
11.928
276694AA1-018 GEN2
Solar/Wind Harmer
6.813
276691AA1-018 GEN1
Solar/Wind Harmer
0.814
274861TOP CROP ;1U
Solar/Wind Harmer
6.537
270055AF2-134 C O1
Solar/Wind Harmer
3.258
962781AG1-127 GEN
Solar/Wind Harmer
10.218
274872LEEDK;1U
Solar/Wind Harmer
8.804
939401AE1-172 GEN
Solar/Wind Harmer
14.911
276805AD2-038 GEN
Solar/Wind Harmer
5.482
24441205WTRV SLR C
Solar/Wind Harmer
0.144
276882AE2-255 GEN
Solar/Wind Harmer
3.593
971997AH1-543 GEN
Solar/Wind Harmer
16.759
958381AF2-132 GEN
Solar/Wind Harmer
9.627
964861AG1-349 GEN
Solar/Wind Harmer
8.33
971917AH1-482 GEN
Solar/Wind Harmer
9.611
957471AF2-041 GEN
Solar/Wind Harmer
31.743
959081AF2-199 GEN
Solar/Wind Harmer
10.581
971067AG2-660 GEN
Solar/Wind Harmer
2.461
24721705FLATG2
50/50
21.838
270102X2-052 ST
50/50
1.83
270100X2-052 CT1
50/50
1.69
270101X2-052 CT2
50/50
1.69
970349AG2-230 GEN
Solar/Wind Harmer
18.249
965681AG1-436 GEN
Solar/Wind Harmer
14.245
965791AG1-447 GEN
Solar/Wind Harmer
7.288
274770LINCOLN ;1U
Adder
7.038
274771LINCOLN ;2U
Adder
7.038
274805UNIV PK N;1U
Adder
5.57
274808UNIV PK N;4U
Adder
5.534
274888KELLY CRK;1U
Solar/Wind Harmer
6.534
276776AD2-060 GEN
Solar/Wind Harmer
0.463
958011AF2-095 GEN
Solar/Wind Harmer
15.944
970941AG2-585 GEN
Solar/Wind Harmer
6.09
276897AD1-100 C
Solar/Wind Harmer
51.281
274674JOLIET 9 ;6U
Adder
16.926
276893AG1-478 C
Solar/Wind Harmer
0.481
961051AF2-396 GEN
Solar/Wind Harmer
17.393
961051AF2-396 GEN
Solar/Wind Harmer
8.09
247620Y3-023
Adder
0.5
274695ROCKY RD ;2P
Adder
12.056
274693ROCKY RD ;1P
Adder
11.937
274697ROCKY RD ;3P
Adder
3.275
274696ROCKY RD ;4P
Adder
12.34
274683WAUKEGAN ;8U
Adder
22.755
274683WAUKEGAN ;8U
Adder
19.182
958481AF2-142 GEN
Solar/Wind Harmer
16.196
270535AF1-215 GEN1
Solar/Wind Harmer
4.888
270536AF1-215 GEN2
Solar/Wind Harmer
4.888
962691AG1-118 GEN
Solar/Wind Harmer
32.301
960751AF2-366 GEN
Solar/Wind Harmer
3.083
958491AF2-143 GEN
Solar/Wind Harmer
16.036
276901AD2-066 C O1
Solar/Wind Harmer
3.746
971341AH1-150 GEN
Solar/Wind Harmer
21.162
971343AH1-151 GEN
Solar/Wind Harmer
21.162
276872AE1-163_GEN1
Solar/Wind Harmer
7.079
276876AE1-163_GEN2
Solar/Wind Harmer
7.079
972235AH1-702 GEN1
Adder
2.654
972236AH1-702 GEN2
Adder
2.308
274764LEE CO EC;5U
Adder
9.7
274765LEE CO EC;6U
Adder
9.7
274762LEE CO EC;3U
Adder
9.677
274763LEE CO EC;4U
Adder
9.586
270054AF2-122 C O1
Solar/Wind Helper
2.149
270349AD2-093_GEN
Solar/Wind Helper
2.07
270471AD2-092_GEN
Solar/Wind Helper
2.07
946101AF1-275 GEN
Solar/Wind Helper
0.83
253383AE2-342_GEN
Solar/Wind Helper
0.865
241960AC2-195 GEN
Solar/Wind Helper
1.459
274822ROCKFORD ;11
Adder
20.709
970819AG2-516 GEN
Solar/Wind Harmer
12.603
274761LEE CO EC;2U
Adder
9.677
274766LEE CO EC;7U
Adder
9.563
270520AE2-214 GEN
Solar/Wind Helper
3.319
270286AF1-227 GEN2
Solar/Wind Helper
0.968
970569AG2-363 GEN
Solar/Wind Harmer
26.441
24722005FLATG5
50/50
1.47
24721905FLATG4
50/50
26.859
962771AG1-126 GEN
Solar/Wind Harmer
111.791
970153AG2-106 GEN
Solar/Wind Harmer
48.746
971347AH1-153 GEN
Solar/Wind Harmer
6.083
274772LINCOLN ;3U
Adder
7.038
270043AE2-236 GEN
Solar/Wind Harmer
6.211
24441505OLIV SLR
Solar/Wind Harmer
0.151
247643Z2-116 C
Solar/Wind Harmer
0.078
274724RIVER EC ;11
Adder
19.776
970707AG2-453 GEN
Solar/Wind Harmer
31.235
276164X3-005 C
Solar/Wind Harmer
0.783
972231SS25-0005
Solar/Wind Harmer
10.56
972181SS23-001
Solar/Wind Harmer
6.6
274752CRETE EC ;2U
Adder
5.439
274753CRETE EC ;3U
Adder
5.439
972259AH1-714 GEN
Adder
21.177
274814UNIV PK N;0U
Adder
5.607
274807UNIV PK N;3U
Adder
5.595
274811UNIV PK N;7U
Adder
5.558
270505AE1-170 C O1
Solar/Wind Harmer
16.629
274826FISK ;BP
Adder
12.125
274887GEN-1.85
Solar/Wind Harmer
5.899
276772AC2-154 GEN
Solar/Wind Harmer
3.09
276843GEN-1.7
Solar/Wind Harmer
0.635
276806AD2-047 C O1
Solar/Wind Harmer
11.845
274803UNIV PARK;6U
Adder
6.455
972038AH1-567 GEN2
Adder
0.404
939351AE1-166 GEN
Solar/Wind Harmer
6.547
274676JOLIET 29;8U
Adder
32.566
945111AF1-176 GEN
Solar/Wind Harmer
6.221
274729ELWOOD EC;1P
Adder
18.053
274730ELWOOD EC;6P
Adder
18.053
274734ELWOOD EC;8P
Adder
18.053
274736ELWOOD EC;9P
Adder
18.053
943121AE2-341 GEN
Solar/Wind Harmer
16.435
943591AF1-030 GEN
Solar/Wind Harmer
10.957
274682WAUKEGAN ;7U
Adder
19.427
274862TOP CROP ;2U
Solar/Wind Harmer
5.458
944531AF1-118 GEN
Solar/Wind Harmer
37.571
270063AE2-323 C
Solar/Wind Harmer
2.345
276868AE1-113 GEN
Solar/Wind Harmer
10.778
274879MINONK ;1U
Solar/Wind Harmer
7.185
276799AD1-013 GEN
Solar/Wind Harmer
2.351
946671AF1-331 GEN
Solar/Wind Harmer
0.446
274855GSG-6 ;RU
Solar/Wind Harmer
3.927
274850MENDOTA H;RU
Solar/Wind Harmer
2.73
276602WESTBROOK C
Solar/Wind Harmer
2.261
964401AG1-302 GEN
Solar/Wind Harmer
9.627
959091AF2-200 GEN
Solar/Wind Harmer
21.162
274760LEE CO EC;1U
Adder
9.677
274767LEE CO EC;8U
Adder
9.563
270284AF1-227 GEN1
Solar/Wind Helper
2.64
270287AF1-227 GEN3
Solar/Wind Helper
0.968
960801AF2-371 GEN
Solar/Wind Helper
0.993
964871AG1-351 GEN
Solar/Wind Helper
0.685
970571AG2-364 GEN
Solar/Wind Harmer
17.627
CPLELTFEXP_CPLE->PJM
CLTF
1.972
CBM West 2LTFEXP_CBM-W2->PJM
CBM
89.423
NYPJM->LTFIMP_NY
CLTF
2.495
LGEELTFEXP_LGEE->PJM
CLTF
3.316
WECLTFEXP_WEC->PJM
CLTF
4.018
AG2-052LTFEXP_AG2-052->PJM
LTF
0.247
AH1-155LTFEXP_AH1-155->PJM
LTF
0.37
LAGNLTFEXP_LAGN->PJM
CLTF
11.793
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.114
TVALTFEXP_TVA->PJM
CLTF
5.294
CBM West 1LTFEXP_CBM-W1->PJM
CBM
117.272
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.566
MECLTFEXP_MEC->PJM
CLTF
15.378
SIGELTFEXP_SIGE->PJM
CLTF
0.329

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AEP_P2-2_#8072_05MARYSV 765_2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P2-2_#8072_05MARYSV 765_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:117.25 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5359.3
MW Contribution:
69.35
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
1.482
960681AF2-359 GEN
Solar/Wind Harmer
4.234
274775LINCOLN ;6U
Adder
6.931
274776LINCOLN ;7U
Adder
6.931
274777LINCOLN ;8U
Adder
6.931
270526AF1-158 GEN
Solar/Wind Harmer
5.027
971771AH1-392 GEN
Solar/Wind Harmer
9.974
270071AF1-092 GEN
Solar/Wind Harmer
16.362
274827FISK ;RP
Adder
8.458
972228AH1-698 GEN2
Adder
4.038
972227AH1-698 GEN1
Adder
2.843
960591AF2-350 GEN
Solar/Wind Harmer
10.898
972037AH1-567 GEN1
Adder
0.199
274800UNIV PARK;3U
Adder
6.351
274801UNIV PARK;4U
Adder
6.351
274687WILL CNTY;4U
Adder
30.296
274687WILL CNTY;4U
Adder
30.296
274675JOLIET 29;7U
Adder
33.244
274675JOLIET 29;7U
Adder
32.057
970833AG2-524 GEN
Solar/Wind Harmer
9.439
970833AG2-524 GEN
Solar/Wind Harmer
4.39
274728ELWOOD EC;5P
Adder
17.77
274731ELWOOD EC;2P
Adder
17.77
274733ELWOOD EC;3P
Adder
17.77
274735ELWOOD EC;4P
Adder
17.77
276893AG1-478 C
Solar/Wind Harmer
0.594
274744AC1-111 GEN8
Adder
6.017
274746AC1-111 G10
Adder
6.017
944161AF1-084 GEN
Solar/Wind Harmer
2.35
970073AG2-061 GEN
Solar/Wind Harmer
2.447
971675AH1-338 GEN
Solar/Wind Harmer
18.851
971411AH1-196 GEN
Solar/Wind Harmer
15.708
276861AD2-134 GEN
Solar/Wind Harmer
1.869
276863AD2-134 GEN
Solar/Wind Harmer
1.869
971171AH1-044 GEN
Solar/Wind Harmer
20.831
274863CRW1-WTG
Solar/Wind Harmer
5.799
274864CRW2-WTG
Solar/Wind Harmer
5.799
274823ROCKFORD ;21
Adder
20.237
276889AE2-281 GEN
Solar/Wind Harmer
1.991
958391AF2-133 GEN
Solar/Wind Harmer
9.384
274856ECOGROVE ;U1
Solar/Wind Harmer
3.481
276611AD2-172 GEN
Solar/Wind Harmer
2.641
276612AE2-035 GEN
Solar/Wind Harmer
2.641
959141AF2-205 GEN
Solar/Wind Harmer
6.218
926823AC1-168 GEN
Solar/Wind Harmer
4.418
971681AH1-341 GEN
Solar/Wind Harmer
15.409
24729505KEY G4
Adder
6.649
972267AH1-718 GEN
Adder
4.228
241955AC1-078 GEN
Solar/Wind Helper
2.298
241973AD2-163_GEN1
Solar/Wind Helper
1.862
241974AD2-163_GEN2
Solar/Wind Helper
1.862
945631AF1-228 GEN
Solar/Wind Helper
1.837
24721705FLATG2
50/50
22.01
270102X2-052 ST
50/50
1.799
270100X2-052 CT1
50/50
1.662
270101X2-052 CT2
50/50
1.662
970349AG2-230 GEN
Solar/Wind Harmer
17.966
965681AG1-436 GEN
Solar/Wind Harmer
14.006
965791AG1-447 GEN
Solar/Wind Harmer
7.166
274770LINCOLN ;1U
Adder
6.931
274771LINCOLN ;2U
Adder
6.931
274805UNIV PK N;1U
Adder
5.481
274808UNIV PK N;4U
Adder
5.445
274888KELLY CRK;1U
Solar/Wind Harmer
6.431
276776AD2-060 GEN
Solar/Wind Harmer
0.456
958011AF2-095 GEN
Solar/Wind Harmer
15.693
970941AG2-585 GEN
Solar/Wind Harmer
5.994
276897AD1-100 C
Solar/Wind Harmer
50.481
274674JOLIET 9 ;6U
Adder
16.661
276893AG1-478 C
Solar/Wind Harmer
0.474
961051AF2-396 GEN
Solar/Wind Harmer
17.047
961051AF2-396 GEN
Solar/Wind Harmer
7.929
274695ROCKY RD ;2P
Adder
11.868
274693ROCKY RD ;1P
Adder
11.751
274697ROCKY RD ;3P
Adder
3.224
274696ROCKY RD ;4P
Adder
12.148
274683WAUKEGAN ;8U
Adder
22.4
274683WAUKEGAN ;8U
Adder
18.882
958481AF2-142 GEN
Solar/Wind Harmer
15.94
247620Y3-023
Adder
0.489
962691AG1-118 GEN
Solar/Wind Harmer
31.798
270535AF1-215 GEN1
Solar/Wind Harmer
4.804
270536AF1-215 GEN2
Solar/Wind Harmer
4.804
960751AF2-366 GEN
Solar/Wind Harmer
3.035
958491AF2-143 GEN
Solar/Wind Harmer
15.782
276901AD2-066 C O1
Solar/Wind Harmer
3.686
971341AH1-150 GEN
Solar/Wind Harmer
20.831
971343AH1-151 GEN
Solar/Wind Harmer
20.831
276872AE1-163_GEN1
Solar/Wind Harmer
6.967
276876AE1-163_GEN2
Solar/Wind Harmer
6.967
972235AH1-702 GEN1
Adder
2.613
972236AH1-702 GEN2
Adder
2.272
274764LEE CO EC;5U
Adder
9.547
274765LEE CO EC;6U
Adder
9.547
274762LEE CO EC;3U
Adder
9.525
274763LEE CO EC;4U
Adder
9.435
270054AF2-122 C O1
Solar/Wind Helper
2.097
946101AF1-275 GEN
Solar/Wind Helper
0.802
270349AD2-093_GEN
Solar/Wind Helper
1.818
270471AD2-092_GEN
Solar/Wind Helper
1.818
253383AE2-342_GEN
Solar/Wind Helper
0.854
241960AC2-195 GEN
Solar/Wind Helper
1.419
938861AE1-114 GEN
Solar/Wind Harmer
2.265
24721805FLATG3
50/50
1.482
24344105CKG2
50/50
9.343
962761AG1-125 GEN
Solar/Wind Harmer
112.309
970149AG2-104 GEN
Solar/Wind Harmer
69.351
970155AG2-107 GEN
Solar/Wind Harmer
48.972
972207SS24-0001
Solar/Wind Harmer
24.644
274773LINCOLN ;4U
Adder
6.931
274774LINCOLN ;5U
Adder
6.931
274723RIVER EC ;12
Adder
19.685
270216AD2-079_GEN
Solar/Wind Harmer
0.663
274751CRETE EC ;1U
Adder
5.351
274754CRETE EC ;4U
Adder
5.351
274812UNIV PK N;8U
Adder
5.469
274802UNIV PARK;5U
Adder
6.353
941551AE2-152 GEN
Solar/Wind Harmer
4.928
957891AF2-083 GEN
Solar/Wind Harmer
16.274
274676JOLIET 29;8U
Adder
33.244
274674JOLIET 9 ;6U
Adder
16.661
274732ELWOOD EC;7P
Adder
17.77
274871GR RIDGE ;2U
Solar/Wind Harmer
8.31
274847GR RIDGE ;BU
Solar/Wind Harmer
5.464
945111AF1-176 GEN
Solar/Wind Harmer
19.236
24639705ELKHART HY
Adder
0.165
274745AC1-111 GEN9
Adder
6.017
970373AG2-245 GEN
Solar/Wind Harmer
22.569
270449AD2-020 GEN
Solar/Wind Harmer
3.003
943021AE2-325 GEN
Solar/Wind Harmer
3.902
274682WAUKEGAN ;7U
Adder
19.124
274828WAUKEGAN ;BP
Adder
11.742
276694AA1-018 GEN2
Solar/Wind Harmer
6.705
276691AA1-018 GEN1
Solar/Wind Harmer
0.801
274861TOP CROP ;1U
Solar/Wind Harmer
6.434
270055AF2-134 C O1
Solar/Wind Harmer
3.202
962781AG1-127 GEN
Solar/Wind Harmer
10.059
274872LEEDK;1U
Solar/Wind Harmer
8.667
939401AE1-172 GEN
Solar/Wind Harmer
14.675
276805AD2-038 GEN
Solar/Wind Harmer
5.395
276882AE2-255 GEN
Solar/Wind Harmer
3.536
971997AH1-543 GEN
Solar/Wind Harmer
16.495
24441205WTRV SLR C
Solar/Wind Harmer
0.141
958381AF2-132 GEN
Solar/Wind Harmer
9.461
957471AF2-041 GEN
Solar/Wind Harmer
31.247
959081AF2-199 GEN
Solar/Wind Harmer
10.416
971067AG2-660 GEN
Solar/Wind Harmer
2.422
964861AG1-349 GEN
Solar/Wind Harmer
8.186
971917AH1-482 GEN
Solar/Wind Harmer
9.444
274822ROCKFORD ;11
Adder
20.385
970819AG2-516 GEN
Solar/Wind Harmer
12.405
970569AG2-363 GEN
Solar/Wind Harmer
30.826
274761LEE CO EC;2U
Adder
9.525
274766LEE CO EC;7U
Adder
9.413
270520AE2-214 GEN
Solar/Wind Helper
3.207
270286AF1-227 GEN2
Solar/Wind Helper
0.87
24722005FLATG5
50/50
1.482
24721905FLATG4
50/50
27.071
962771AG1-126 GEN
Solar/Wind Harmer
112.309
970153AG2-106 GEN
Solar/Wind Harmer
48.972
971347AH1-153 GEN
Solar/Wind Harmer
5.989
274772LINCOLN ;3U
Adder
6.931
24441505OLIV SLR
Solar/Wind Harmer
0.148
270043AE2-236 GEN
Solar/Wind Harmer
6.061
247643Z2-116 C
Solar/Wind Harmer
0.076
274724RIVER EC ;11
Adder
19.46
970707AG2-453 GEN
Solar/Wind Harmer
30.756
276164X3-005 C
Solar/Wind Harmer
0.77
972231SS25-0005
Solar/Wind Harmer
10.389
972181SS23-001
Solar/Wind Harmer
6.493
274752CRETE EC ;2U
Adder
5.351
274753CRETE EC ;3U
Adder
5.351
972259AH1-714 GEN
Adder
20.849
274814UNIV PK N;0U
Adder
5.517
274807UNIV PK N;3U
Adder
5.505
274811UNIV PK N;7U
Adder
5.469
274826FISK ;BP
Adder
11.934
274887GEN-1.85
Solar/Wind Harmer
5.806
276772AC2-154 GEN
Solar/Wind Harmer
3.041
276843GEN-1.7
Solar/Wind Harmer
0.625
276806AD2-047 C O1
Solar/Wind Harmer
11.659
274803UNIV PARK;6U
Adder
6.353
972038AH1-567 GEN2
Adder
0.398
270505AE1-170 C O1
Solar/Wind Harmer
16.306
939351AE1-166 GEN
Solar/Wind Harmer
6.445
274676JOLIET 29;8U
Adder
32.056
274729ELWOOD EC;1P
Adder
17.77
274730ELWOOD EC;6P
Adder
17.77
274734ELWOOD EC;8P
Adder
17.77
274736ELWOOD EC;9P
Adder
17.77
943121AE2-341 GEN
Solar/Wind Harmer
16.181
943591AF1-030 GEN
Solar/Wind Harmer
10.787
945111AF1-176 GEN
Solar/Wind Harmer
6.096
274682WAUKEGAN ;7U
Adder
19.124
274862TOP CROP ;2U
Solar/Wind Harmer
5.372
944531AF1-118 GEN
Solar/Wind Harmer
36.716
276868AE1-113 GEN
Solar/Wind Harmer
10.607
274879MINONK ;1U
Solar/Wind Harmer
7.072
276799AD1-013 GEN
Solar/Wind Harmer
2.315
946671AF1-331 GEN
Solar/Wind Harmer
0.439
274855GSG-6 ;RU
Solar/Wind Harmer
3.866
274850MENDOTA H;RU
Solar/Wind Harmer
2.688
276602WESTBROOK C
Solar/Wind Harmer
2.225
964401AG1-302 GEN
Solar/Wind Harmer
9.461
959091AF2-200 GEN
Solar/Wind Harmer
20.831
270063AE2-323 C
Solar/Wind Harmer
2.285
970571AG2-364 GEN
Solar/Wind Harmer
20.55
274760LEE CO EC;1U
Adder
9.525
274767LEE CO EC;8U
Adder
9.413
270284AF1-227 GEN1
Solar/Wind Helper
2.373
270287AF1-227 GEN3
Solar/Wind Helper
0.87
960801AF2-371 GEN
Solar/Wind Helper
0.964
964871AG1-351 GEN
Solar/Wind Helper
0.665
CPLELTFEXP_CPLE->PJM
CLTF
1.997
CBM West 2LTFEXP_CBM-W2->PJM
CBM
87.92
NYPJM->LTFIMP_NY
CLTF
2.454
LGEELTFEXP_LGEE->PJM
CLTF
3.221
WECLTFEXP_WEC->PJM
CLTF
3.955
AG2-052LTFEXP_AG2-052->PJM
LTF
0.242
AH1-155LTFEXP_AH1-155->PJM
LTF
0.363
LAGNLTFEXP_LAGN->PJM
CLTF
11.631
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.139
TVALTFEXP_TVA->PJM
CLTF
5.225
CBM West 1LTFEXP_CBM-W1->PJM
CBM
114.418
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.259
MECLTFEXP_MEC->PJM
CLTF
15.133
SIGELTFEXP_SIGE->PJM
CLTF
0.321

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AEP_P1-3_#8072_05MARYSV 765_2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-3_#8072_05MARYSV 765_2_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.01 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5074.41
MW Contribution:
51.15
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721705FLATG2
50/50
22.01
270102X2-052 ST
50/50
1.799
270100X2-052 CT1
50/50
1.662
270101X2-052 CT2
50/50
1.662
970349AG2-230 GEN
Solar/Wind Harmer
12.534
965681AG1-436 GEN
Solar/Wind Harmer
9.772
965791AG1-447 GEN
Solar/Wind Harmer
7.166
274770LINCOLN ;1U
Adder
9.435
274771LINCOLN ;2U
Adder
9.435
274805UNIV PK N;1U
Adder
5.481
274808UNIV PK N;4U
Adder
5.445
274888KELLY CRK;1U
Solar/Wind Harmer
0.443
276776AD2-060 GEN
Solar/Wind Harmer
0.811
958011AF2-095 GEN
Solar/Wind Harmer
10.949
970941AG2-585 GEN
Solar/Wind Harmer
4.182
276897AD1-100 C
Solar/Wind Harmer
18.954
274674JOLIET 9 ;6U
Adder
16.661
276893AG1-478 C
Solar/Wind Harmer
0.502
961051AF2-396 GEN
Solar/Wind Harmer
14.985
961051AF2-396 GEN
Solar/Wind Harmer
9.99
274695ROCKY RD ;2P
Adder
11.868
274693ROCKY RD ;1P
Adder
11.751
274697ROCKY RD ;3P
Adder
3.224
274696ROCKY RD ;4P
Adder
12.148
274683WAUKEGAN ;8U
Adder
22.4
274683WAUKEGAN ;8U
Adder
18.882
958481AF2-142 GEN
Solar/Wind Harmer
11.121
247620Y3-023
Adder
0.489
962691AG1-118 GEN
Solar/Wind Harmer
22.185
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
11.011
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
14.533
971343AH1-151 GEN
Solar/Wind Harmer
14.533
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
2.613
972236AH1-702 GEN2
Adder
2.272
938861AE1-114 GEN
Solar/Wind Harmer
4.06
274764LEE CO EC;5U
Adder
9.547
274765LEE CO EC;6U
Adder
9.547
274762LEE CO EC;3U
Adder
9.525
274763LEE CO EC;4U
Adder
9.435
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.14
276645AC1-214 GEN1
Solar/Wind Harmer
0.276
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
2.249
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.272
944541AF1-119 GEN
Solar/Wind Harmer
0.446
960971AF2-388 GEN
Solar/Wind Harmer
3.922
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.752
276615X2-022 GEN
Solar/Wind Harmer
0.066
276838X2-022 GEN2
Solar/Wind Harmer
0.36
970241AG2-163 GEN
Solar/Wind Harmer
3.681
276916AD2-100_GEN
Solar/Wind Harmer
12.928
276911AD2-131_GEN
Solar/Wind Harmer
0.852
942221AE2-234 GEN
Solar/Wind Harmer
2.468
970291AG2-192 GEN
Solar/Wind Harmer
0.785
970291AG2-192 GEN
Solar/Wind Harmer
0.362
270054AF2-122 C O1
Solar/Wind Helper
2.097
946101AF1-275 GEN
Solar/Wind Helper
0.802
270349AD2-093_GEN
Solar/Wind Helper
1.818
270471AD2-092_GEN
Solar/Wind Helper
1.818
253383AE2-342_GEN
Solar/Wind Helper
0.854
241960AC2-195 GEN
Solar/Wind Helper
1.419
24721605FLATG1
50/50
1.482
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
274775LINCOLN ;6U
Adder
9.435
274776LINCOLN ;7U
Adder
9.435
274777LINCOLN ;8U
Adder
9.435
270526AF1-158 GEN
Solar/Wind Harmer
0
971771AH1-392 GEN
Solar/Wind Harmer
7.732
270071AF1-092 GEN
Solar/Wind Harmer
14.586
274827FISK ;RP
Adder
8.458
972228AH1-698 GEN2
Adder
4.038
972227AH1-698 GEN1
Adder
2.843
960591AF2-350 GEN
Solar/Wind Harmer
7.603
972037AH1-567 GEN1
Adder
0.199
274800UNIV PARK;3U
Adder
6.351
274801UNIV PARK;4U
Adder
6.351
274687WILL CNTY;4U
Adder
30.296
274687WILL CNTY;4U
Adder
30.296
274675JOLIET 29;7U
Adder
33.244
274675JOLIET 29;7U
Adder
32.057
970833AG2-524 GEN
Solar/Wind Harmer
8.297
970833AG2-524 GEN
Solar/Wind Harmer
5.531
274728ELWOOD EC;5P
Adder
17.77
274731ELWOOD EC;2P
Adder
17.77
274733ELWOOD EC;3P
Adder
17.77
274735ELWOOD EC;4P
Adder
17.77
274744AC1-111 GEN8
Adder
6.017
274746AC1-111 G10
Adder
6.017
970073AG2-061 GEN
Solar/Wind Harmer
2.447
971675AH1-338 GEN
Solar/Wind Harmer
2.85
971411AH1-196 GEN
Solar/Wind Harmer
10.959
276861AD2-134 GEN
Solar/Wind Harmer
0.13
276863AD2-134 GEN
Solar/Wind Harmer
0.13
971171AH1-044 GEN
Solar/Wind Harmer
14.533
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
274823ROCKFORD ;21
Adder
20.237
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274856ECOGROVE ;U1
Solar/Wind Harmer
0.168
959141AF2-205 GEN
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
1.219
971681AH1-341 GEN
Solar/Wind Harmer
11.539
24729505KEY G4
Adder
6.649
970169AG2-114 GEN
Solar/Wind Harmer
7.15
971611AH1-305 GEN
Solar/Wind Harmer
4.239
970031AG2-029 GEN
Solar/Wind Harmer
3.854
972267AH1-718 GEN
Adder
4.228
276741O09 GEN1
Solar/Wind Harmer
0.25
274877BISHOP HL;1U
Solar/Wind Harmer
0.234
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.266
946321AF1-296 GEN
Solar/Wind Harmer
3.872
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
971549AH1-272 GEN
Solar/Wind Harmer
13.514
276668AB2-070 GEN1
Solar/Wind Harmer
0.255
276848AB2-070 GEN3
Solar/Wind Harmer
0.254
276849AB2-070 GEN2
Solar/Wind Harmer
0.255
963841AG1-237 GEN
Solar/Wind Harmer
2.803
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
24721805FLATG3
50/50
1.482
24344105CKG2
50/50
9.343
962761AG1-125 GEN
Solar/Wind Harmer
94.712
970149AG2-104 GEN
Solar/Wind Harmer
51.146
970155AG2-107 GEN
Solar/Wind Harmer
60.48
274773LINCOLN ;4U
Adder
9.435
274774LINCOLN ;5U
Adder
9.435
274723RIVER EC ;12
Adder
19.685
274751CRETE EC ;1U
Adder
9.02
274754CRETE EC ;4U
Adder
9.02
274812UNIV PK N;8U
Adder
5.469
274802UNIV PARK;5U
Adder
6.353
941551AE2-152 GEN
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
12.616
274676JOLIET 29;8U
Adder
33.244
274674JOLIET 9 ;6U
Adder
16.661
274732ELWOOD EC;7P
Adder
17.77
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
13.42
24639705ELKHART HY
Adder
0.165
274745AC1-111 GEN9
Adder
6.017
970373AG2-245 GEN
Solar/Wind Harmer
15.746
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.902
274682WAUKEGAN ;7U
Adder
19.124
274828WAUKEGAN ;BP
Adder
11.742
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.205
274861TOP CROP ;1U
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
7.023
274872LEEDK;1U
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
5.495
276805AD2-038 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.854
971997AH1-543 GEN
Solar/Wind Harmer
3.836
958381AF2-132 GEN
Solar/Wind Harmer
0.001
957471AF2-041 GEN
Solar/Wind Harmer
21.8
959081AF2-199 GEN
Solar/Wind Harmer
7.267
971067AG2-660 GEN
Solar/Wind Harmer
2.422
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.444
274822ROCKFORD ;11
Adder
20.385
970819AG2-516 GEN
Solar/Wind Harmer
8.655
970569AG2-363 GEN
Solar/Wind Harmer
21.506
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
9.525
274766LEE CO EC;7U
Adder
9.413
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.899
959331AF2-224 GEN
Solar/Wind Harmer
4.399
945581AF1-223 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
1.148
241955AC1-078 GEN
Solar/Wind Helper
2.298
241973AD2-163_GEN1
Solar/Wind Helper
1.862
241974AD2-163_GEN2
Solar/Wind Helper
1.862
945631AF1-228 GEN
Solar/Wind Helper
1.837
276708O09 GEN2
Solar/Wind Harmer
0.25
276646AC1-214 GEN2
Solar/Wind Harmer
0.276
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.688
965651AG1-433 GEN
Solar/Wind Harmer
1.961
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
2.83
276621W2-048 GEN
Solar/Wind Harmer
0.32
963741AG1-226 GEN
Solar/Wind Harmer
14.933
965011AG1-365 GEN
Solar/Wind Harmer
6.284
945371AF1-202 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
1.24
270520AE2-214 GEN
Solar/Wind Helper
3.207
270286AF1-227 GEN2
Solar/Wind Helper
0.87
24722005FLATG5
50/50
1.482
24721905FLATG4
50/50
27.071
962771AG1-126 GEN
Solar/Wind Harmer
94.712
970153AG2-106 GEN
Solar/Wind Harmer
60.48
971347AH1-153 GEN
Solar/Wind Harmer
4.178
274772LINCOLN ;3U
Adder
9.435
270043AE2-236 GEN
Solar/Wind Harmer
4.934
274724RIVER EC ;11
Adder
19.46
970707AG2-453 GEN
Solar/Wind Harmer
25.034
274752CRETE EC ;2U
Adder
9.02
274753CRETE EC ;3U
Adder
9.02
972259AH1-714 GEN
Adder
20.849
274814UNIV PK N;0U
Adder
5.517
274807UNIV PK N;3U
Adder
5.505
274811UNIV PK N;7U
Adder
5.469
274826FISK ;BP
Adder
11.934
274887GEN-1.85
Solar/Wind Harmer
0.198
276843GEN-1.7
Solar/Wind Harmer
0.246
276806AD2-047 C O1
Solar/Wind Harmer
4.309
274803UNIV PARK;6U
Adder
6.353
972038AH1-567 GEN2
Adder
0.398
270505AE1-170 C O1
Solar/Wind Harmer
7.964
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
32.056
274729ELWOOD EC;1P
Adder
17.77
274730ELWOOD EC;6P
Adder
17.77
274734ELWOOD EC;8P
Adder
17.77
274736ELWOOD EC;9P
Adder
17.77
943121AE2-341 GEN
Solar/Wind Harmer
12.618
943591AF1-030 GEN
Solar/Wind Harmer
8.391
945111AF1-176 GEN
Solar/Wind Harmer
6.096
274682WAUKEGAN ;7U
Adder
19.124
274862TOP CROP ;2U
Solar/Wind Harmer
1
944531AF1-118 GEN
Solar/Wind Harmer
32.801
276868AE1-113 GEN
Solar/Wind Harmer
1.463
274879MINONK ;1U
Solar/Wind Harmer
0.305
946671AF1-331 GEN
Solar/Wind Harmer
0.78
274855GSG-6 ;RU
Solar/Wind Harmer
0.267
274850MENDOTA H;RU
Solar/Wind Harmer
0.085
964401AG1-302 GEN
Solar/Wind Harmer
0.001
959091AF2-200 GEN
Solar/Wind Harmer
14.533
270063AE2-323 C
Solar/Wind Harmer
0
970571AG2-364 GEN
Solar/Wind Harmer
14.338
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
9.525
274767LEE CO EC;8U
Adder
9.413
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.234
965931AG1-462 GEN
Solar/Wind Harmer
17.553
971087AG2-675 GEN
Solar/Wind Harmer
3.671
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.861
965091AG1-374 GEN
Solar/Wind Harmer
20.448
959611AF2-252 GEN
Solar/Wind Harmer
2.272
24386205FR-12G C
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
2.994
965021AG1-366 GEN
Solar/Wind Harmer
2.095
957381AF2-032 GEN
Solar/Wind Harmer
1.409
942481AE2-261 GEN
Solar/Wind Harmer
18.543
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.665
270284AF1-227 GEN1
Solar/Wind Helper
2.373
270287AF1-227 GEN3
Solar/Wind Helper
0.87
960801AF2-371 GEN
Solar/Wind Helper
0.964
964871AG1-351 GEN
Solar/Wind Helper
0.665
CPLELTFEXP_CPLE->PJM
CLTF
1.997
CBM West 2LTFEXP_CBM-W2->PJM
CBM
87.92
NYPJM->LTFIMP_NY
CLTF
2.454
LGEELTFEXP_LGEE->PJM
CLTF
3.221
WECLTFEXP_WEC->PJM
CLTF
3.955
AG2-052LTFEXP_AG2-052->PJM
LTF
0.242
AH1-155LTFEXP_AH1-155->PJM
LTF
0.363
LAGNLTFEXP_LAGN->PJM
CLTF
11.631
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.139
TVALTFEXP_TVA->PJM
CLTF
5.225
CBM West 1LTFEXP_CBM-W1->PJM
CBM
114.418
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.259
MECLTFEXP_MEC->PJM
CLTF
15.133
SIGELTFEXP_SIGE->PJM
CLTF
0.321

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.62 %
Rating:4047.0 MVA
Rating Type:A
MVA to Mitigate:4476.89
MW Contribution:
40.3
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270102X2-052 ST
50/50
1.749
270100X2-052 CT1
50/50
1.616
270101X2-052 CT2
50/50
1.616
24643105BUCHANAN
50/50
0.014
247620Y3-023
50/50
0.526
274770LINCOLN ;1U
50/50
9.616
274771LINCOLN ;2U
50/50
9.616
970349AG2-230 GEN
Solar/Wind Harmer
12.041
965681AG1-436 GEN
Solar/Wind Harmer
9.504
965791AG1-447 GEN
Solar/Wind Harmer
6.97
961051AF2-396 GEN
Solar/Wind Harmer
14.959
961051AF2-396 GEN
Solar/Wind Harmer
9.973
274805UNIV PK N;1U
Adder
5.303
274808UNIV PK N;4U
Adder
5.268
274888KELLY CRK;1U
Solar/Wind Harmer
0.428
276776AD2-060 GEN
Solar/Wind Harmer
0.783
958011AF2-095 GEN
Solar/Wind Harmer
10.572
970941AG2-585 GEN
Solar/Wind Harmer
4.038
276897AD1-100 C
Solar/Wind Harmer
18.287
274674JOLIET 9 ;6U
Adder
16.082
276893AG1-478 C
Solar/Wind Harmer
0.485
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274695ROCKY RD ;2P
Adder
11.454
274693ROCKY RD ;1P
Adder
11.341
274697ROCKY RD ;3P
Adder
3.111
274696ROCKY RD ;4P
Adder
11.724
958481AF2-142 GEN
Solar/Wind Harmer
10.754
274683WAUKEGAN ;8U
Adder
21.627
274683WAUKEGAN ;8U
Adder
18.23
962691AG1-118 GEN
Solar/Wind Harmer
21.414
958491AF2-143 GEN
Solar/Wind Harmer
10.655
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
14.045
971343AH1-151 GEN
Solar/Wind Harmer
14.045
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
2.526
972236AH1-702 GEN2
Adder
2.196
938861AE1-114 GEN
Solar/Wind Harmer
3.928
944541AF1-119 GEN
Solar/Wind Harmer
0.462
960971AF2-388 GEN
Solar/Wind Harmer
4.056
274764LEE CO EC;5U
Adder
9.237
274765LEE CO EC;6U
Adder
9.237
274762LEE CO EC;3U
Adder
9.215
274763LEE CO EC;4U
Adder
9.128
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.104
276645AC1-214 GEN1
Solar/Wind Harmer
0.268
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
2.191
942221AE2-234 GEN
Solar/Wind Harmer
2.684
960611AF2-352 GEN
Solar/Wind Harmer
2.217
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.745
944231AF1-091 GEN
Solar/Wind Harmer
15.08
270246TR4_N_V150
Solar/Wind Harmer
0.042
270247TR4_N_V136
Solar/Wind Harmer
0.042
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
970241AG2-163 GEN
Solar/Wind Harmer
3.669
970291AG2-192 GEN
Solar/Wind Harmer
0.817
970291AG2-192 GEN
Solar/Wind Harmer
0.377
276615X2-022 GEN
Solar/Wind Harmer
0.065
276838X2-022 GEN2
Solar/Wind Harmer
0.353
270031AE2-169
Solar/Wind Harmer
3.44
270599AE1-208 GEN
Solar/Wind Harmer
5.734
971613AH1-306 GEN
Solar/Wind Harmer
2.966
276916AD2-100_GEN
Solar/Wind Harmer
12.749
276911AD2-131_GEN
Solar/Wind Harmer
0.84
246937BC-WTG2
Solar/Wind Harmer
0.244
270054AF2-122 C O1
Solar/Wind Helper
1.656
270144AC1-141 ST1_
50/50
2.311
24641605TWIN BRNCH
50/50
0.019
24344005CKG1
50/50
7.028
24653605MOTTVILLE
50/50
0.004
274775LINCOLN ;6U
50/50
9.616
274776LINCOLN ;7U
50/50
9.616
274777LINCOLN ;8U
50/50
9.616
270071AF1-092 GEN
Solar/Wind Harmer
14.768
971771AH1-392 GEN
Solar/Wind Harmer
7.622
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270526AF1-158 GEN
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
4.047
959331AF2-224 GEN
Solar/Wind Harmer
5.169
274827FISK ;RP
Adder
8.169
972037AH1-567 GEN1
Adder
0.193
960591AF2-350 GEN
Solar/Wind Harmer
7.341
274800UNIV PARK;3U
Adder
6.134
274801UNIV PARK;4U
Adder
6.134
972228AH1-698 GEN2
Adder
3.896
972227AH1-698 GEN1
Adder
2.744
24729505KEY G4
Adder
6.793
274687WILL CNTY;4U
Adder
29.249
274687WILL CNTY;4U
Adder
29.249
274675JOLIET 29;7U
Adder
32.088
274675JOLIET 29;7U
Adder
30.942
274728ELWOOD EC;5P
Adder
17.157
274731ELWOOD EC;2P
Adder
17.157
274733ELWOOD EC;3P
Adder
17.157
274735ELWOOD EC;4P
Adder
17.157
970833AG2-524 GEN
Solar/Wind Harmer
8.005
970833AG2-524 GEN
Solar/Wind Harmer
5.336
274744AC1-111 GEN8
Adder
5.803
274746AC1-111 G10
Adder
5.803
970073AG2-061 GEN
Solar/Wind Harmer
2.368
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
2.753
971411AH1-196 GEN
Solar/Wind Harmer
10.588
276861AD2-134 GEN
Solar/Wind Harmer
0.126
276863AD2-134 GEN
Solar/Wind Harmer
0.126
959141AF2-205 GEN
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
14.045
274823ROCKFORD ;21
Adder
19.56
971611AH1-305 GEN
Solar/Wind Harmer
4.163
274856ECOGROVE ;U1
Solar/Wind Harmer
0.163
926823AC1-168 GEN
Solar/Wind Harmer
1.181
970169AG2-114 GEN
Solar/Wind Harmer
6.939
971681AH1-341 GEN
Solar/Wind Harmer
11.162
972267AH1-718 GEN
Adder
4.093
276741O09 GEN1
Solar/Wind Harmer
0.242
971549AH1-272 GEN
Solar/Wind Harmer
14.066
274877BISHOP HL;1U
Solar/Wind Harmer
0.227
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
9.126
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.079
965041AG1-368 GEN
Solar/Wind Harmer
6.739
946321AF1-296 GEN
Solar/Wind Harmer
3.754
274854TWINGROVE;U2
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
247521TR3_G114
Solar/Wind Harmer
0.235
965051AG1-369 GEN
Solar/Wind Harmer
3.245
963841AG1-237 GEN
Solar/Wind Harmer
2.784
276668AB2-070 GEN1
Solar/Wind Harmer
0.25
276848AB2-070 GEN3
Solar/Wind Harmer
0.249
276849AB2-070 GEN2
Solar/Wind Harmer
0.25
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
1.194
971609AH1-304 GEN
Solar/Wind Harmer
1.022
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.766
24344105CKG2
50/50
8.859
270143AC1-141 CT2_
50/50
2.617
24639705ELKHART HY
50/50
0.176
970521AG2-332 GEN
50/50
12.55
274773LINCOLN ;4U
50/50
9.616
274774LINCOLN ;5U
50/50
9.616
962761AG1-125 GEN
Solar/Wind Harmer
74.627
970149AG2-104 GEN
Solar/Wind Harmer
40.3
970155AG2-107 GEN
Solar/Wind Harmer
47.655
957891AF2-083 GEN
Solar/Wind Harmer
12.55
945111AF1-176 GEN
Solar/Wind Harmer
13.401
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.895
274723RIVER EC ;12
Adder
19.037
274751CRETE EC ;1U
Adder
8.738
274754CRETE EC ;4U
Adder
8.738
965011AG1-365 GEN
Solar/Wind Harmer
7.385
274812UNIV PK N;8U
Adder
5.291
274802UNIV PARK;5U
Adder
6.138
970373AG2-245 GEN
Solar/Wind Harmer
15.385
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
32.088
274674JOLIET 9 ;6U
Adder
16.082
274732ELWOOD EC;7P
Adder
17.157
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
5.803
270055AF2-134 C O1
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.165
274682WAUKEGAN ;7U
Adder
18.463
274861TOP CROP ;1U
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
11.336
958381AF2-132 GEN
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
6.78
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.257
274872LEEDK;1U
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
5.318
276805AD2-038 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.826
971997AH1-543 GEN
Solar/Wind Harmer
3.71
957471AF2-041 GEN
Solar/Wind Harmer
21.068
959081AF2-199 GEN
Solar/Wind Harmer
7.023
971067AG2-660 GEN
Solar/Wind Harmer
2.341
274822ROCKFORD ;11
Adder
19.703
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.741
970819AG2-516 GEN
Solar/Wind Harmer
8.368
970569AG2-363 GEN
Solar/Wind Harmer
20.843
965651AG1-433 GEN
Solar/Wind Harmer
2.028
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
9.215
274766LEE CO EC;7U
Adder
9.107
276708O09 GEN2
Solar/Wind Harmer
0.242
276646AC1-214 GEN2
Solar/Wind Harmer
0.268
958861AF2-177 GEN
Solar/Wind Harmer
2.941
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.439
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
14.886
276621W2-048 GEN
Solar/Wind Harmer
0.314
270024AE2-089 GEN
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
6.922
270032AE2-172
Solar/Wind Harmer
4.12
965421AG1-410 GEN
Solar/Wind Harmer
18.52
965911AG1-460 GEN
Solar/Wind Harmer
1.222
246936BC-WTG1
Solar/Wind Harmer
0.244
270489AE1-102 GEN1
Solar/Wind Harmer
0.786
276903AD2-071 C
Solar/Wind Harmer
6.725
270142AC1-141 CT1_
50/50
2.617
24642205MAYFLWER
50/50
0.04
274772LINCOLN ;3U
50/50
9.616
944961AF1-161 GEN
50/50
3.109
962601AG1-109 GEN
50/50
3.109
962771AG1-126 GEN
Solar/Wind Harmer
74.627
970153AG2-106 GEN
Solar/Wind Harmer
47.655
971347AH1-153 GEN
Solar/Wind Harmer
4.014
270043AE2-236 GEN
Solar/Wind Harmer
5.048
270505AE1-170 C O1
Solar/Wind Harmer
7.914
270063AE2-323 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
6.088
944531AF1-118 GEN
Solar/Wind Harmer
33.371
274724RIVER EC ;11
Adder
18.817
274752CRETE EC ;2U
Adder
8.738
274753CRETE EC ;3U
Adder
8.738
965021AG1-366 GEN
Solar/Wind Harmer
2.462
970707AG2-453 GEN
Solar/Wind Harmer
24.09
274814UNIV PK N;0U
Adder
5.338
274807UNIV PK N;3U
Adder
5.326
274811UNIV PK N;7U
Adder
5.291
972259AH1-714 GEN
Adder
20.093
274826FISK ;BP
Adder
11.527
274803UNIV PARK;6U
Adder
6.138
274887GEN-1.85
Solar/Wind Harmer
0.191
276843GEN-1.7
Solar/Wind Harmer
0.237
276806AD2-047 C O1
Solar/Wind Harmer
4.16
972038AH1-567 GEN2
Adder
0.384
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
30.942
274729ELWOOD EC;1P
Adder
17.157
274730ELWOOD EC;6P
Adder
17.157
274734ELWOOD EC;8P
Adder
17.157
274736ELWOOD EC;9P
Adder
17.157
943121AE2-341 GEN
Solar/Wind Harmer
12.163
943591AF1-030 GEN
Solar/Wind Harmer
8.088
274682WAUKEGAN ;7U
Adder
18.463
274862TOP CROP ;2U
Solar/Wind Harmer
0.968
964401AG1-302 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.416
274879MINONK ;1U
Solar/Wind Harmer
0.295
946671AF1-331 GEN
Solar/Wind Harmer
0.753
274855GSG-6 ;RU
Solar/Wind Harmer
0.257
274850MENDOTA H;RU
Solar/Wind Harmer
0.082
959091AF2-200 GEN
Solar/Wind Harmer
14.045
970571AG2-364 GEN
Solar/Wind Harmer
13.895
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
9.215
274767LEE CO EC;8U
Adder
9.107
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.227
24690905MDL-1G C
Solar/Wind Harmer
0
24721905FLATG4
Adder
19.661
970781AG2-491 GEN
Solar/Wind Harmer
6.766
965931AG1-462 GEN
Solar/Wind Harmer
17.022
971087AG2-675 GEN
Solar/Wind Harmer
3.56
965091AG1-374 GEN
Solar/Wind Harmer
19.952
959611AF2-252 GEN
Solar/Wind Harmer
2.217
24386205FR-12G C
Solar/Wind Harmer
0
247642Z2-115 C
Solar/Wind Harmer
0.003
971993AH1-541 GEN
Solar/Wind Harmer
2.938
24695305TIMB G C
Solar/Wind Harmer
0.537
970289AG2-191 GEN
Solar/Wind Harmer
0.691
957381AF2-032 GEN
Solar/Wind Harmer
1.388
942481AE2-261 GEN
Solar/Wind Harmer
18.271
246938BC-WTG3
Solar/Wind Harmer
0.218
270491AE1-102 GEN2
Solar/Wind Harmer
0.786
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
CPLELTFEXP_CPLE->PJM
CLTF
1.444
CBM West 2LTFEXP_CBM-W2->PJM
CBM
87.349
NYPJM->LTFIMP_NY
CLTF
2.583
LGEELTFEXP_LGEE->PJM
CLTF
3.675
WECLTFEXP_WEC->PJM
CLTF
3.823
AG2-052LTFEXP_AG2-052->PJM
LTF
0.237
AH1-155LTFEXP_AH1-155->PJM
LTF
0.356
LAGNLTFEXP_LAGN->PJM
CLTF
11.281
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.712
TVALTFEXP_TVA->PJM
CLTF
5.082
CBM West 1LTFEXP_CBM-W1->PJM
CBM
120.334
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.267
MECLTFEXP_MEC->PJM
CLTF
14.733
SIGELTFEXP_SIGE->PJM
CLTF
0.34

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AEP_P7-1_#10944___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P7-1_#10944___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:109.61 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5010.18
MW Contribution:
54.78
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270102X2-052 ST
50/50
1.778
270100X2-052 CT1
50/50
1.643
270101X2-052 CT2
50/50
1.643
274770LINCOLN ;1U
50/50
7.217
274771LINCOLN ;2U
50/50
7.217
24643105BUCHANAN
50/50
0.014
247620Y3-023
50/50
0.532
970349AG2-230 GEN
Solar/Wind Harmer
17.514
965681AG1-436 GEN
Solar/Wind Harmer
13.857
965791AG1-447 GEN
Solar/Wind Harmer
7.089
961051AF2-396 GEN
Solar/Wind Harmer
17.218
961051AF2-396 GEN
Solar/Wind Harmer
8.008
274805UNIV PK N;1U
Adder
5.418
270144AC1-141 ST1_
50/50
2.339
24641605TWIN BRNCH
50/50
0.019
24344005CKG1
50/50
7.115
274775LINCOLN ;6U
50/50
7.217
274776LINCOLN ;7U
50/50
7.217
274777LINCOLN ;8U
50/50
7.217
24653605MOTTVILLE
50/50
0.004
270071AF1-092 GEN
Solar/Wind Harmer
16.823
960681AF2-359 GEN
Solar/Wind Harmer
4.189
971771AH1-392 GEN
Solar/Wind Harmer
9.969
270526AF1-158 GEN
Solar/Wind Harmer
5.008
274808UNIV PK N;4U
Adder
5.383
274888KELLY CRK;1U
Solar/Wind Harmer
6.35
958011AF2-095 GEN
Solar/Wind Harmer
15.495
970941AG2-585 GEN
Solar/Wind Harmer
5.918
276776AD2-060 GEN
Solar/Wind Harmer
0.45
276897AD1-100 C
Solar/Wind Harmer
49.833
274674JOLIET 9 ;6U
Adder
16.457
276893AG1-478 C
Solar/Wind Harmer
0.468
270535AF1-215 GEN1
Solar/Wind Harmer
4.807
270536AF1-215 GEN2
Solar/Wind Harmer
4.807
274696ROCKY RD ;4P
Adder
12.013
274695ROCKY RD ;2P
Adder
11.736
274693ROCKY RD ;1P
Adder
11.621
274697ROCKY RD ;3P
Adder
3.188
958481AF2-142 GEN
Solar/Wind Harmer
15.793
274683WAUKEGAN ;8U
Adder
22.163
274683WAUKEGAN ;8U
Adder
18.683
962691AG1-118 GEN
Solar/Wind Harmer
31.466
960751AF2-366 GEN
Solar/Wind Harmer
3.004
958491AF2-143 GEN
Solar/Wind Harmer
15.659
276901AD2-066 C O1
Solar/Wind Harmer
3.658
971341AH1-150 GEN
Solar/Wind Harmer
20.665
971343AH1-151 GEN
Solar/Wind Harmer
20.665
276872AE1-163_GEN1
Solar/Wind Harmer
6.927
276876AE1-163_GEN2
Solar/Wind Harmer
6.927
972235AH1-702 GEN1
Adder
2.593
972236AH1-702 GEN2
Adder
2.255
274764LEE CO EC;5U
Adder
9.494
274765LEE CO EC;6U
Adder
9.494
274762LEE CO EC;3U
Adder
9.471
274763LEE CO EC;4U
Adder
9.382
270054AF2-122 C O1
Solar/Wind Helper
1.794
970031AG2-029 GEN
Solar/Wind Harmer
27.046
274827FISK ;RP
Adder
8.352
972037AH1-567 GEN1
Adder
0.197
960591AF2-350 GEN
Solar/Wind Harmer
10.76
972228AH1-698 GEN2
Adder
3.985
972227AH1-698 GEN1
Adder
2.806
274800UNIV PARK;3U
Adder
6.272
274801UNIV PARK;4U
Adder
6.272
944161AF1-084 GEN
Solar/Wind Harmer
2.376
274687WILL CNTY;4U
Adder
29.923
274687WILL CNTY;4U
Adder
29.923
274675JOLIET 29;7U
Adder
32.832
274675JOLIET 29;7U
Adder
31.659
274728ELWOOD EC;5P
Adder
17.558
274731ELWOOD EC;2P
Adder
17.558
274733ELWOOD EC;3P
Adder
17.558
274735ELWOOD EC;4P
Adder
17.558
24729505KEY G4
Adder
6.928
276893AG1-478 C
Solar/Wind Harmer
0.587
970833AG2-524 GEN
Solar/Wind Harmer
9.321
970833AG2-524 GEN
Solar/Wind Harmer
4.335
959331AF2-224 GEN
Solar/Wind Harmer
10.633
274744AC1-111 GEN8
Adder
5.942
274746AC1-111 G10
Adder
5.942
970073AG2-061 GEN
Solar/Wind Harmer
2.428
958391AF2-133 GEN
Solar/Wind Harmer
9.434
971675AH1-338 GEN
Solar/Wind Harmer
18.686
971411AH1-196 GEN
Solar/Wind Harmer
15.57
276861AD2-134 GEN
Solar/Wind Harmer
1.853
276863AD2-134 GEN
Solar/Wind Harmer
1.853
959141AF2-205 GEN
Solar/Wind Harmer
6.259
274863CRW1-WTG
Solar/Wind Harmer
5.77
274864CRW2-WTG
Solar/Wind Harmer
5.77
971171AH1-044 GEN
Solar/Wind Harmer
20.665
276889AE2-281 GEN
Solar/Wind Harmer
1.979
274823ROCKFORD ;21
Adder
20.081
274856ECOGROVE ;U1
Solar/Wind Harmer
3.458
276611AD2-172 GEN
Solar/Wind Harmer
2.623
276612AE2-035 GEN
Solar/Wind Harmer
2.623
926823AC1-168 GEN
Solar/Wind Harmer
4.398
972267AH1-718 GEN
Adder
4.209
270142AC1-141 CT1_
50/50
2.649
274772LINCOLN ;3U
50/50
7.217
24642205MAYFLWER
50/50
0.04
962771AG1-126 GEN
Solar/Wind Harmer
88.715
970153AG2-106 GEN
Solar/Wind Harmer
38.684
971347AH1-153 GEN
Solar/Wind Harmer
5.838
270043AE2-236 GEN
Solar/Wind Harmer
6.27
247643Z2-116 C
Solar/Wind Harmer
0.077
24441505OLIV SLR
Solar/Wind Harmer
0.148
270505AE1-170 C O1
Solar/Wind Harmer
16.403
270063AE2-323 C
Solar/Wind Harmer
2.395
945111AF1-176 GEN
Solar/Wind Harmer
6.161
944531AF1-118 GEN
Solar/Wind Harmer
38.053
274724RIVER EC ;11
Adder
19.218
972231SS25-0005
Solar/Wind Harmer
10.278
972181SS23-001
Solar/Wind Harmer
6.423
274752CRETE EC ;2U
Adder
5.293
274753CRETE EC ;3U
Adder
5.293
276164X3-005 C
Solar/Wind Harmer
0.76
970707AG2-453 GEN
Solar/Wind Harmer
30.269
274814UNIV PK N;0U
Adder
5.454
274807UNIV PK N;3U
Adder
5.442
274811UNIV PK N;7U
Adder
5.406
972259AH1-714 GEN
Adder
20.552
274826FISK ;BP
Adder
11.785
274803UNIV PARK;6U
Adder
6.275
274887GEN-1.85
Solar/Wind Harmer
5.733
276843GEN-1.7
Solar/Wind Harmer
0.617
276772AC2-154 GEN
Solar/Wind Harmer
3.003
276806AD2-047 C O1
Solar/Wind Harmer
11.511
972038AH1-567 GEN2
Adder
0.393
939351AE1-166 GEN
Solar/Wind Harmer
6.362
274676JOLIET 29;8U
Adder
31.659
274729ELWOOD EC;1P
Adder
17.558
274730ELWOOD EC;6P
Adder
17.558
274734ELWOOD EC;8P
Adder
17.558
274736ELWOOD EC;9P
Adder
17.558
943121AE2-341 GEN
Solar/Wind Harmer
15.97
943591AF1-030 GEN
Solar/Wind Harmer
10.647
965021AG1-366 GEN
Solar/Wind Harmer
2.473
24721905FLATG4
Adder
21.345
274682WAUKEGAN ;7U
Adder
18.92
274862TOP CROP ;2U
Solar/Wind Harmer
5.323
964401AG1-302 GEN
Solar/Wind Harmer
9.495
276868AE1-113 GEN
Solar/Wind Harmer
10.527
274879MINONK ;1U
Solar/Wind Harmer
7.019
276799AD1-013 GEN
Solar/Wind Harmer
2.294
946671AF1-331 GEN
Solar/Wind Harmer
0.435
274855GSG-6 ;RU
Solar/Wind Harmer
3.832
274850MENDOTA H;RU
Solar/Wind Harmer
2.664
276602WESTBROOK C
Solar/Wind Harmer
2.206
959091AF2-200 GEN
Solar/Wind Harmer
20.665
274760LEE CO EC;1U
Adder
9.471
274767LEE CO EC;8U
Adder
9.36
970571AG2-364 GEN
Solar/Wind Harmer
0.393
24344105CKG2
50/50
8.986
270143AC1-141 CT2_
50/50
2.649
274773LINCOLN ;4U
50/50
7.217
274774LINCOLN ;5U
50/50
7.217
24639705ELKHART HY
50/50
0.178
970521AG2-332 GEN
50/50
12.701
962761AG1-125 GEN
Solar/Wind Harmer
88.715
970149AG2-104 GEN
Solar/Wind Harmer
54.782
970155AG2-107 GEN
Solar/Wind Harmer
38.684
270216AD2-079_GEN
Solar/Wind Harmer
0.668
972207SS24-0001
Solar/Wind Harmer
24.182
957891AF2-083 GEN
Solar/Wind Harmer
16.388
945111AF1-176 GEN
Solar/Wind Harmer
19.439
274723RIVER EC ;12
Adder
19.442
274751CRETE EC ;1U
Adder
5.293
274754CRETE EC ;4U
Adder
5.293
270449AD2-020 GEN
Solar/Wind Harmer
3.032
943021AE2-325 GEN
Solar/Wind Harmer
3.94
274812UNIV PK N;8U
Adder
5.406
274802UNIV PARK;5U
Adder
6.275
941551AE2-152 GEN
Solar/Wind Harmer
4.865
970373AG2-245 GEN
Solar/Wind Harmer
22.518
274676JOLIET 29;8U
Adder
32.831
274674JOLIET 9 ;6U
Adder
16.457
274732ELWOOD EC;7P
Adder
17.558
274871GR RIDGE ;2U
Solar/Wind Harmer
8.206
274847GR RIDGE ;BU
Solar/Wind Harmer
5.396
965011AG1-365 GEN
Solar/Wind Harmer
10.633
274745AC1-111 GEN9
Adder
5.942
24441205WTRV SLR C
Solar/Wind Harmer
0.143
270055AF2-134 C O1
Solar/Wind Harmer
3.204
276694AA1-018 GEN2
Solar/Wind Harmer
6.643
276691AA1-018 GEN1
Solar/Wind Harmer
0.794
274682WAUKEGAN ;7U
Adder
18.92
274861TOP CROP ;1U
Solar/Wind Harmer
6.376
274828WAUKEGAN ;BP
Adder
11.618
962781AG1-127 GEN
Solar/Wind Harmer
9.957
958381AF2-132 GEN
Solar/Wind Harmer
9.495
964861AG1-349 GEN
Solar/Wind Harmer
8.218
971917AH1-482 GEN
Solar/Wind Harmer
9.482
274872LEEDK;1U
Solar/Wind Harmer
8.581
939401AE1-172 GEN
Solar/Wind Harmer
14.566
276805AD2-038 GEN
Solar/Wind Harmer
5.353
276882AE2-255 GEN
Solar/Wind Harmer
3.509
971997AH1-543 GEN
Solar/Wind Harmer
16.368
957471AF2-041 GEN
Solar/Wind Harmer
30.997
959081AF2-199 GEN
Solar/Wind Harmer
10.332
971067AG2-660 GEN
Solar/Wind Harmer
2.403
274822ROCKFORD ;11
Adder
20.228
940581AE2-045 GEN
Solar/Wind Harmer
10.493
971605AH1-302 GEN
Solar/Wind Harmer
8.972
970819AG2-516 GEN
Solar/Wind Harmer
12.318
274761LEE CO EC;2U
Adder
9.471
274766LEE CO EC;7U
Adder
9.36
970569AG2-363 GEN
Solar/Wind Harmer
0.589
CPLELTFEXP_CPLE->PJM
CLTF
1.92
CBM West 2LTFEXP_CBM-W2->PJM
CBM
93.511
NYPJM->LTFIMP_NY
CLTF
2.816
LGEELTFEXP_LGEE->PJM
CLTF
4.052
WECLTFEXP_WEC->PJM
CLTF
3.927
AG2-052LTFEXP_AG2-052->PJM
LTF
0.243
AH1-155LTFEXP_AH1-155->PJM
LTF
0.364
LAGNLTFEXP_LAGN->PJM
CLTF
12.285
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.262
TVALTFEXP_TVA->PJM
CLTF
5.629
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.974
CBM South 1LTFEXP_CBM-S1->PJM
CBM
21.323
MECLTFEXP_MEC->PJM
CLTF
15.302
SIGELTFEXP_SIGE->PJM
CLTF
0.365

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o ATSI_P7-1_TE-345-027A_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
ATSI_P7-1_TE-345-027A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:108.08 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:4940.32
MW Contribution:
55.1
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270144AC1-141 ST1_
50/50
2.451
24344005CKG1
50/50
7.462
24641605TWIN BRNCH
50/50
0.02
24653605MOTTVILLE
50/50
0.004
274775LINCOLN ;6U
50/50
7.418
274776LINCOLN ;7U
50/50
7.418
274777LINCOLN ;8U
50/50
7.418
270071AF1-092 GEN
Solar/Wind Harmer
17.395
971771AH1-392 GEN
Solar/Wind Harmer
10.406
270526AF1-158 GEN
Solar/Wind Harmer
5.216
960681AF2-359 GEN
Solar/Wind Harmer
4.343
970031AG2-029 GEN
Solar/Wind Harmer
28.389
944161AF1-084 GEN
Solar/Wind Harmer
2.504
959331AF2-224 GEN
Solar/Wind Harmer
11.213
972037AH1-567 GEN1
Adder
0.203
274827FISK ;RP
Adder
8.588
960591AF2-350 GEN
Solar/Wind Harmer
11.061
274800UNIV PARK;3U
Adder
6.448
274801UNIV PARK;4U
Adder
6.448
972228AH1-698 GEN2
Adder
4.095
972227AH1-698 GEN1
Adder
2.884
274687WILL CNTY;4U
Adder
30.745
274687WILL CNTY;4U
Adder
30.745
274675JOLIET 29;7U
Adder
33.728
274675JOLIET 29;7U
Adder
32.523
24729505KEY G4
Adder
7.126
274728ELWOOD EC;5P
Adder
18.034
274731ELWOOD EC;2P
Adder
18.034
274733ELWOOD EC;3P
Adder
18.034
274735ELWOOD EC;4P
Adder
18.034
276893AG1-478 C
Solar/Wind Harmer
0.603
970833AG2-524 GEN
Solar/Wind Harmer
9.569
970833AG2-524 GEN
Solar/Wind Harmer
4.451
274744AC1-111 GEN8
Adder
6.097
274746AC1-111 G10
Adder
6.097
970073AG2-061 GEN
Solar/Wind Harmer
2.489
958391AF2-133 GEN
Solar/Wind Harmer
9.701
959141AF2-205 GEN
Solar/Wind Harmer
6.431
971675AH1-338 GEN
Solar/Wind Harmer
19.139
971411AH1-196 GEN
Solar/Wind Harmer
15.949
276861AD2-134 GEN
Solar/Wind Harmer
1.898
24344105CKG2
50/50
9.299
270143AC1-141 CT2_
50/50
2.775
24639705ELKHART HY
50/50
0.187
970521AG2-332 GEN
50/50
13.311
24307105BERRINSP G
50/50
0.024
274773LINCOLN ;4U
50/50
7.418
274774LINCOLN ;5U
50/50
7.418
962761AG1-125 GEN
Solar/Wind Harmer
89.226
970149AG2-104 GEN
Solar/Wind Harmer
55.097
970155AG2-107 GEN
Solar/Wind Harmer
38.907
270216AD2-079_GEN
Solar/Wind Harmer
0.699
957891AF2-083 GEN
Solar/Wind Harmer
17.194
270102X2-052 ST
50/50
1.845
270100X2-052 CT1
50/50
1.705
270101X2-052 CT2
50/50
1.705
24643105BUCHANAN
50/50
0.015
247620Y3-023
50/50
0.558
274770LINCOLN ;1U
50/50
7.418
274771LINCOLN ;2U
50/50
7.418
970349AG2-230 GEN
Solar/Wind Harmer
18.149
965681AG1-436 GEN
Solar/Wind Harmer
14.368
965791AG1-447 GEN
Solar/Wind Harmer
7.351
961051AF2-396 GEN
Solar/Wind Harmer
18.101
961051AF2-396 GEN
Solar/Wind Harmer
8.419
274805UNIV PK N;1U
Adder
5.578
274808UNIV PK N;4U
Adder
5.541
274888KELLY CRK;1U
Solar/Wind Harmer
6.527
276776AD2-060 GEN
Solar/Wind Harmer
0.463
958011AF2-095 GEN
Solar/Wind Harmer
15.928
970941AG2-585 GEN
Solar/Wind Harmer
6.084
276897AD1-100 C
Solar/Wind Harmer
51.184
274674JOLIET 9 ;6U
Adder
16.903
276893AG1-478 C
Solar/Wind Harmer
0.481
270535AF1-215 GEN1
Solar/Wind Harmer
4.956
270536AF1-215 GEN2
Solar/Wind Harmer
4.956
274695ROCKY RD ;2P
Adder
12.037
274693ROCKY RD ;1P
Adder
11.918
274697ROCKY RD ;3P
Adder
3.27
274696ROCKY RD ;4P
Adder
12.321
958481AF2-142 GEN
Solar/Wind Harmer
16.205
274683WAUKEGAN ;8U
Adder
22.729
274683WAUKEGAN ;8U
Adder
19.16
962691AG1-118 GEN
Solar/Wind Harmer
32.255
960751AF2-366 GEN
Solar/Wind Harmer
3.079
958491AF2-143 GEN
Solar/Wind Harmer
16.055
276901AD2-066 C O1
Solar/Wind Harmer
3.749
971341AH1-150 GEN
Solar/Wind Harmer
21.158
971343AH1-151 GEN
Solar/Wind Harmer
21.158
276872AE1-163_GEN1
Solar/Wind Harmer
7.094
276876AE1-163_GEN2
Solar/Wind Harmer
7.094
972235AH1-702 GEN1
Adder
2.655
972236AH1-702 GEN2
Adder
2.308
274764LEE CO EC;5U
Adder
9.709
274765LEE CO EC;6U
Adder
9.709
274762LEE CO EC;3U
Adder
9.686
274763LEE CO EC;4U
Adder
9.595
270054AF2-122 C O1
Solar/Wind Helper
1.626
276863AD2-134 GEN
Solar/Wind Harmer
1.898
971549AH1-272 GEN
Solar/Wind Harmer
19.629
274863CRW1-WTG
Solar/Wind Harmer
5.908
274864CRW2-WTG
Solar/Wind Harmer
5.908
971171AH1-044 GEN
Solar/Wind Harmer
21.158
276889AE2-281 GEN
Solar/Wind Harmer
2.027
274823ROCKFORD ;21
Adder
20.558
972267AH1-718 GEN
Adder
4.302
945111AF1-176 GEN
Solar/Wind Harmer
20.409
270449AD2-020 GEN
Solar/Wind Harmer
3.19
943021AE2-325 GEN
Solar/Wind Harmer
4.145
972207SS24-0001
Solar/Wind Harmer
24.857
270142AC1-141 CT1_
50/50
2.775
24642205MAYFLWER
50/50
0.042
944961AF1-161 GEN
50/50
3.309
962601AG1-109 GEN
50/50
3.309
274772LINCOLN ;3U
50/50
7.418
962771AG1-126 GEN
Solar/Wind Harmer
89.226
970153AG2-106 GEN
Solar/Wind Harmer
38.907
971347AH1-153 GEN
Solar/Wind Harmer
6.05
270043AE2-236 GEN
Solar/Wind Harmer
6.529
247643Z2-116 C
Solar/Wind Harmer
0.08
24441505OLIV SLR
Solar/Wind Harmer
0.154
270505AE1-170 C O1
Solar/Wind Harmer
17.214
945111AF1-176 GEN
Solar/Wind Harmer
6.468
270063AE2-323 C
Solar/Wind Harmer
2.513
965021AG1-366 GEN
Solar/Wind Harmer
2.608
944531AF1-118 GEN
Solar/Wind Harmer
39.173
274724RIVER EC ;11
Adder
19.791
972231SS25-0005
Solar/Wind Harmer
10.591
972181SS23-001
Solar/Wind Harmer
6.619
274752CRETE EC ;2U
Adder
5.455
274753CRETE EC ;3U
Adder
5.455
276164X3-005 C
Solar/Wind Harmer
0.782
274814UNIV PK N;0U
Adder
5.614
274807UNIV PK N;3U
Adder
5.602
274811UNIV PK N;7U
Adder
5.565
970707AG2-453 GEN
Solar/Wind Harmer
31.089
274803UNIV PARK;6U
Adder
6.454
274826FISK ;BP
Adder
12.118
972259AH1-714 GEN
Adder
21.114
274887GEN-1.85
Solar/Wind Harmer
5.893
276772AC2-154 GEN
Solar/Wind Harmer
3.087
276843GEN-1.7
Solar/Wind Harmer
0.634
276806AD2-047 C O1
Solar/Wind Harmer
11.833
972038AH1-567 GEN2
Adder
0.404
939351AE1-166 GEN
Solar/Wind Harmer
6.535
274676JOLIET 29;8U
Adder
32.523
24441205WTRV SLR C
Solar/Wind Harmer
0.151
965011AG1-365 GEN
Solar/Wind Harmer
11.213
274723RIVER EC ;12
Adder
20.022
274751CRETE EC ;1U
Adder
5.455
274754CRETE EC ;4U
Adder
5.455
274812UNIV PK N;8U
Adder
5.565
970373AG2-245 GEN
Solar/Wind Harmer
23.253
274802UNIV PARK;5U
Adder
6.454
941551AE2-152 GEN
Solar/Wind Harmer
4.997
274676JOLIET 29;8U
Adder
33.727
274674JOLIET 9 ;6U
Adder
16.903
274732ELWOOD EC;7P
Adder
18.034
274871GR RIDGE ;2U
Solar/Wind Harmer
8.425
274847GR RIDGE ;BU
Solar/Wind Harmer
5.54
270055AF2-134 C O1
Solar/Wind Harmer
3.304
274745AC1-111 GEN9
Adder
6.097
276694AA1-018 GEN2
Solar/Wind Harmer
6.817
276691AA1-018 GEN1
Solar/Wind Harmer
0.815
274861TOP CROP ;1U
Solar/Wind Harmer
6.542
274682WAUKEGAN ;7U
Adder
19.404
274828WAUKEGAN ;BP
Adder
11.914
958381AF2-132 GEN
Solar/Wind Harmer
9.773
964861AG1-349 GEN
Solar/Wind Harmer
8.457
971917AH1-482 GEN
Solar/Wind Harmer
9.757
962781AG1-127 GEN
Solar/Wind Harmer
10.205
274872LEEDK;1U
Solar/Wind Harmer
8.794
939401AE1-172 GEN
Solar/Wind Harmer
14.927
276805AD2-038 GEN
Solar/Wind Harmer
5.489
276882AE2-255 GEN
Solar/Wind Harmer
3.596
971997AH1-543 GEN
Solar/Wind Harmer
16.77
957471AF2-041 GEN
Solar/Wind Harmer
31.738
959081AF2-199 GEN
Solar/Wind Harmer
10.579
971067AG2-660 GEN
Solar/Wind Harmer
2.46
940581AE2-045 GEN
Solar/Wind Harmer
10.772
971605AH1-302 GEN
Solar/Wind Harmer
9.211
274822ROCKFORD ;11
Adder
20.708
274761LEE CO EC;2U
Adder
9.686
274766LEE CO EC;7U
Adder
9.572
970819AG2-516 GEN
Solar/Wind Harmer
7.613
274729ELWOOD EC;1P
Adder
18.034
274730ELWOOD EC;6P
Adder
18.034
274734ELWOOD EC;8P
Adder
18.034
274736ELWOOD EC;9P
Adder
18.034
943121AE2-341 GEN
Solar/Wind Harmer
16.387
943591AF1-030 GEN
Solar/Wind Harmer
10.925
274862TOP CROP ;2U
Solar/Wind Harmer
5.462
274682WAUKEGAN ;7U
Adder
19.404
964401AG1-302 GEN
Solar/Wind Harmer
9.773
276868AE1-113 GEN
Solar/Wind Harmer
10.789
274879MINONK ;1U
Solar/Wind Harmer
7.193
276799AD1-013 GEN
Solar/Wind Harmer
2.35
946671AF1-331 GEN
Solar/Wind Harmer
0.445
274855GSG-6 ;RU
Solar/Wind Harmer
3.925
274850MENDOTA H;RU
Solar/Wind Harmer
2.729
276602WESTBROOK C
Solar/Wind Harmer
2.259
959091AF2-200 GEN
Solar/Wind Harmer
21.158
274760LEE CO EC;1U
Adder
9.686
274767LEE CO EC;8U
Adder
9.572
24721905FLATG4
Adder
19.928
CPLELTFEXP_CPLE->PJM
CLTF
1.484
CBM West 2LTFEXP_CBM-W2->PJM
CBM
91.994
NYPJM->LTFIMP_NY
CLTF
2.82
LGEELTFEXP_LGEE->PJM
CLTF
3.91
WECLTFEXP_WEC->PJM
CLTF
4.019
AG2-052LTFEXP_AG2-052->PJM
LTF
0.25
AH1-155LTFEXP_AH1-155->PJM
LTF
0.374
LAGNLTFEXP_LAGN->PJM
CLTF
11.862
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.972
TVALTFEXP_TVA->PJM
CLTF
5.346
CBM West 1LTFEXP_CBM-W1->PJM
CBM
131.53
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.31
MECLTFEXP_MEC->PJM
CLTF
15.493
SIGELTFEXP_SIGE->PJM
CLTF
0.36

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AP_P2-2_WP-500-DRT14_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-2_WP-500-DRT14_SRT-SL
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:105.37 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:4816.67
MW Contribution:
54.59
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270102X2-052 ST
50/50
1.745
270100X2-052 CT1
50/50
1.613
270101X2-052 CT2
50/50
1.613
24643105BUCHANAN
50/50
0.014
247620Y3-023
50/50
0.525
274770LINCOLN ;1U
50/50
7.048
274771LINCOLN ;2U
50/50
7.048
970349AG2-230 GEN
Solar/Wind Harmer
17.222
965681AG1-436 GEN
Solar/Wind Harmer
13.592
965791AG1-447 GEN
Solar/Wind Harmer
6.954
961051AF2-396 GEN
Solar/Wind Harmer
16.979
961051AF2-396 GEN
Solar/Wind Harmer
7.897
274805UNIV PK N;1U
Adder
5.29
274808UNIV PK N;4U
Adder
5.256
274888KELLY CRK;1U
Solar/Wind Harmer
6.195
276776AD2-060 GEN
Solar/Wind Harmer
0.439
958011AF2-095 GEN
Solar/Wind Harmer
15.117
970941AG2-585 GEN
Solar/Wind Harmer
5.774
276897AD1-100 C
Solar/Wind Harmer
48.591
274674JOLIET 9 ;6U
Adder
16.044
276893AG1-478 C
Solar/Wind Harmer
0.456
270535AF1-215 GEN1
Solar/Wind Harmer
4.689
270536AF1-215 GEN2
Solar/Wind Harmer
4.689
274696ROCKY RD ;4P
Adder
11.696
274695ROCKY RD ;2P
Adder
11.426
274693ROCKY RD ;1P
Adder
11.314
274697ROCKY RD ;3P
Adder
3.104
958481AF2-142 GEN
Solar/Wind Harmer
15.378
274683WAUKEGAN ;8U
Adder
21.575
274683WAUKEGAN ;8U
Adder
18.187
962691AG1-118 GEN
Solar/Wind Harmer
30.62
960751AF2-366 GEN
Solar/Wind Harmer
2.923
958491AF2-143 GEN
Solar/Wind Harmer
15.235
276901AD2-066 C O1
Solar/Wind Harmer
3.558
971341AH1-150 GEN
Solar/Wind Harmer
20.083
971343AH1-151 GEN
Solar/Wind Harmer
20.083
276872AE1-163_GEN1
Solar/Wind Harmer
6.731
276876AE1-163_GEN2
Solar/Wind Harmer
6.731
972235AH1-702 GEN1
Adder
2.52
972236AH1-702 GEN2
Adder
2.191
274764LEE CO EC;5U
Adder
9.214
274765LEE CO EC;6U
Adder
9.214
274762LEE CO EC;3U
Adder
9.192
274763LEE CO EC;4U
Adder
9.106
270054AF2-122 C O1
Solar/Wind Helper
1.659
270144AC1-141 ST1_
50/50
2.306
24641605TWIN BRNCH
50/50
0.019
24344005CKG1
50/50
7.012
24653605MOTTVILLE
50/50
0.004
274775LINCOLN ;6U
50/50
7.048
274776LINCOLN ;7U
50/50
7.048
274777LINCOLN ;8U
50/50
7.048
270071AF1-092 GEN
Solar/Wind Harmer
16.529
971771AH1-392 GEN
Solar/Wind Harmer
9.811
960681AF2-359 GEN
Solar/Wind Harmer
4.109
270526AF1-158 GEN
Solar/Wind Harmer
4.922
970031AG2-029 GEN
Solar/Wind Harmer
26.714
944161AF1-084 GEN
Solar/Wind Harmer
2.344
959331AF2-224 GEN
Solar/Wind Harmer
10.561
274827FISK ;RP
Adder
8.15
972037AH1-567 GEN1
Adder
0.192
960591AF2-350 GEN
Solar/Wind Harmer
10.498
274800UNIV PARK;3U
Adder
6.119
274801UNIV PARK;4U
Adder
6.119
972228AH1-698 GEN2
Adder
3.887
972227AH1-698 GEN1
Adder
2.737
24729505KEY G4
Adder
6.777
274687WILL CNTY;4U
Adder
29.18
274687WILL CNTY;4U
Adder
29.18
274675JOLIET 29;7U
Adder
32.013
274675JOLIET 29;7U
Adder
30.87
274728ELWOOD EC;5P
Adder
17.117
274731ELWOOD EC;2P
Adder
17.117
274733ELWOOD EC;3P
Adder
17.117
274735ELWOOD EC;4P
Adder
17.117
276893AG1-478 C
Solar/Wind Harmer
0.572
970833AG2-524 GEN
Solar/Wind Harmer
9.085
970833AG2-524 GEN
Solar/Wind Harmer
4.225
274744AC1-111 GEN8
Adder
5.789
274746AC1-111 G10
Adder
5.789
970073AG2-061 GEN
Solar/Wind Harmer
2.362
958391AF2-133 GEN
Solar/Wind Harmer
9.182
971675AH1-338 GEN
Solar/Wind Harmer
18.167
971411AH1-196 GEN
Solar/Wind Harmer
15.139
276861AD2-134 GEN
Solar/Wind Harmer
1.802
276863AD2-134 GEN
Solar/Wind Harmer
1.802
959141AF2-205 GEN
Solar/Wind Harmer
6.088
274863CRW1-WTG
Solar/Wind Harmer
5.607
274864CRW2-WTG
Solar/Wind Harmer
5.607
971171AH1-044 GEN
Solar/Wind Harmer
20.083
276889AE2-281 GEN
Solar/Wind Harmer
1.923
274823ROCKFORD ;21
Adder
19.512
274856ECOGROVE ;U1
Solar/Wind Harmer
3.358
276611AD2-172 GEN
Solar/Wind Harmer
2.547
276612AE2-035 GEN
Solar/Wind Harmer
2.547
926823AC1-168 GEN
Solar/Wind Harmer
4.27
972267AH1-718 GEN
Adder
4.083
270142AC1-141 CT1_
50/50
2.611
24642205MAYFLWER
50/50
0.04
274772LINCOLN ;3U
50/50
7.048
944961AF1-161 GEN
50/50
3.102
962601AG1-109 GEN
50/50
3.102
962771AG1-126 GEN
Solar/Wind Harmer
88.413
970153AG2-106 GEN
Solar/Wind Harmer
38.552
971347AH1-153 GEN
Solar/Wind Harmer
5.741
270043AE2-236 GEN
Solar/Wind Harmer
6.188
247643Z2-116 C
Solar/Wind Harmer
0.076
24441505OLIV SLR
Solar/Wind Harmer
0.145
270505AE1-170 C O1
Solar/Wind Harmer
16.169
270063AE2-323 C
Solar/Wind Harmer
2.365
945111AF1-176 GEN
Solar/Wind Harmer
6.074
944531AF1-118 GEN
Solar/Wind Harmer
37.269
274724RIVER EC ;11
Adder
18.774
972231SS25-0005
Solar/Wind Harmer
10.042
972181SS23-001
Solar/Wind Harmer
6.276
274752CRETE EC ;2U
Adder
5.172
274753CRETE EC ;3U
Adder
5.172
276164X3-005 C
Solar/Wind Harmer
0.742
965021AG1-366 GEN
Solar/Wind Harmer
2.456
970707AG2-453 GEN
Solar/Wind Harmer
29.527
274814UNIV PK N;0U
Adder
5.325
274807UNIV PK N;3U
Adder
5.314
274811UNIV PK N;7U
Adder
5.279
972259AH1-714 GEN
Adder
20.047
274826FISK ;BP
Adder
11.5
274803UNIV PARK;6U
Adder
6.124
274887GEN-1.85
Solar/Wind Harmer
5.593
276772AC2-154 GEN
Solar/Wind Harmer
2.93
276843GEN-1.7
Solar/Wind Harmer
0.602
276806AD2-047 C O1
Solar/Wind Harmer
11.231
972038AH1-567 GEN2
Adder
0.383
939351AE1-166 GEN
Solar/Wind Harmer
6.203
274676JOLIET 29;8U
Adder
30.869
274729ELWOOD EC;1P
Adder
17.117
274730ELWOOD EC;6P
Adder
17.117
274734ELWOOD EC;8P
Adder
17.117
274736ELWOOD EC;9P
Adder
17.117
943121AE2-341 GEN
Solar/Wind Harmer
15.56
943591AF1-030 GEN
Solar/Wind Harmer
10.373
274682WAUKEGAN ;7U
Adder
18.419
274862TOP CROP ;2U
Solar/Wind Harmer
5.183
964401AG1-302 GEN
Solar/Wind Harmer
9.249
276868AE1-113 GEN
Solar/Wind Harmer
10.239
274879MINONK ;1U
Solar/Wind Harmer
6.826
276799AD1-013 GEN
Solar/Wind Harmer
2.231
946671AF1-331 GEN
Solar/Wind Harmer
0.423
274855GSG-6 ;RU
Solar/Wind Harmer
3.726
274850MENDOTA H;RU
Solar/Wind Harmer
2.59
276602WESTBROOK C
Solar/Wind Harmer
2.145
959091AF2-200 GEN
Solar/Wind Harmer
20.083
274760LEE CO EC;1U
Adder
9.192
274767LEE CO EC;8U
Adder
9.084
24721905FLATG4
Adder
19.611
970571AG2-364 GEN
Solar/Wind Harmer
0.381
24344105CKG2
50/50
8.841
270143AC1-141 CT2_
50/50
2.611
24639705ELKHART HY
50/50
0.176
970521AG2-332 GEN
50/50
12.521
274773LINCOLN ;4U
50/50
7.048
274774LINCOLN ;5U
50/50
7.048
962761AG1-125 GEN
Solar/Wind Harmer
88.413
970149AG2-104 GEN
Solar/Wind Harmer
54.595
970155AG2-107 GEN
Solar/Wind Harmer
38.552
270216AD2-079_GEN
Solar/Wind Harmer
0.658
957891AF2-083 GEN
Solar/Wind Harmer
16.152
945111AF1-176 GEN
Solar/Wind Harmer
19.165
972207SS24-0001
Solar/Wind Harmer
23.616
270449AD2-020 GEN
Solar/Wind Harmer
2.99
943021AE2-325 GEN
Solar/Wind Harmer
3.886
274723RIVER EC ;12
Adder
18.993
274751CRETE EC ;1U
Adder
5.172
274754CRETE EC ;4U
Adder
5.172
965011AG1-365 GEN
Solar/Wind Harmer
10.561
274812UNIV PK N;8U
Adder
5.279
274802UNIV PARK;5U
Adder
6.124
970373AG2-245 GEN
Solar/Wind Harmer
22.001
24441205WTRV SLR C
Solar/Wind Harmer
0.141
941551AE2-152 GEN
Solar/Wind Harmer
4.744
274676JOLIET 29;8U
Adder
32.013
274674JOLIET 9 ;6U
Adder
16.044
274732ELWOOD EC;7P
Adder
17.117
274871GR RIDGE ;2U
Solar/Wind Harmer
7.998
274847GR RIDGE ;BU
Solar/Wind Harmer
5.259
274745AC1-111 GEN9
Adder
5.789
270055AF2-134 C O1
Solar/Wind Harmer
3.126
276694AA1-018 GEN2
Solar/Wind Harmer
6.469
276691AA1-018 GEN1
Solar/Wind Harmer
0.773
274682WAUKEGAN ;7U
Adder
18.419
274861TOP CROP ;1U
Solar/Wind Harmer
6.208
274828WAUKEGAN ;BP
Adder
11.309
958381AF2-132 GEN
Solar/Wind Harmer
9.249
962781AG1-127 GEN
Solar/Wind Harmer
9.688
964861AG1-349 GEN
Solar/Wind Harmer
8.004
971917AH1-482 GEN
Solar/Wind Harmer
9.235
274872LEEDK;1U
Solar/Wind Harmer
8.348
939401AE1-172 GEN
Solar/Wind Harmer
14.167
276805AD2-038 GEN
Solar/Wind Harmer
5.208
276882AE2-255 GEN
Solar/Wind Harmer
3.413
971997AH1-543 GEN
Solar/Wind Harmer
15.916
957471AF2-041 GEN
Solar/Wind Harmer
30.124
959081AF2-199 GEN
Solar/Wind Harmer
10.041
971067AG2-660 GEN
Solar/Wind Harmer
2.335
274822ROCKFORD ;11
Adder
19.655
940581AE2-045 GEN
Solar/Wind Harmer
10.198
971605AH1-302 GEN
Solar/Wind Harmer
8.72
970819AG2-516 GEN
Solar/Wind Harmer
11.965
274761LEE CO EC;2U
Adder
9.192
274766LEE CO EC;7U
Adder
9.084
970569AG2-363 GEN
Solar/Wind Harmer
0.572
CPLELTFEXP_CPLE->PJM
CLTF
1.417
CBM West 2LTFEXP_CBM-W2->PJM
CBM
87.018
NYPJM->LTFIMP_NY
CLTF
2.599
LGEELTFEXP_LGEE->PJM
CLTF
3.658
WECLTFEXP_WEC->PJM
CLTF
3.814
AG2-052LTFEXP_AG2-052->PJM
LTF
0.236
AH1-155LTFEXP_AH1-155->PJM
LTF
0.355
LAGNLTFEXP_LAGN->PJM
CLTF
11.231
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.638
TVALTFEXP_TVA->PJM
CLTF
5.057
CBM West 1LTFEXP_CBM-W1->PJM
CBM
119.975
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.173
MECLTFEXP_MEC->PJM
CLTF
14.692
SIGELTFEXP_SIGE->PJM
CLTF
0.339

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AEP_P4_#2942_05KAMMER 765_PP_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.44 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:6007.99
MW Contribution:
59.0
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
1.793
270071AF1-092 GEN
Solar/Wind Harmer
19.366
960681AF2-359 GEN
Solar/Wind Harmer
4.83
971771AH1-392 GEN
Solar/Wind Harmer
11.452
24722005FLATG5
50/50
1.793
24721905FLATG4
50/50
32.75
962771AG1-126 GEN
Solar/Wind Harmer
95.55
970153AG2-106 GEN
Solar/Wind Harmer
41.664
971347AH1-153 GEN
Solar/Wind Harmer
6.679
270043AE2-236 GEN
Solar/Wind Harmer
7.167
274772LINCOLN ;3U
Adder
7.887
24441505OLIV SLR
Solar/Wind Harmer
0.17
247643Z2-116 C
Solar/Wind Harmer
0.088
274724RIVER EC ;11
Adder
22.304
944531AF1-118 GEN
Solar/Wind Harmer
44.033
276164X3-005 C
Solar/Wind Harmer
0.883
274775LINCOLN ;6U
Adder
7.887
274776LINCOLN ;7U
Adder
7.887
274777LINCOLN ;8U
Adder
7.887
270526AF1-158 GEN
Solar/Wind Harmer
5.763
274827FISK ;RP
Adder
9.712
972037AH1-567 GEN1
Adder
0.229
972228AH1-698 GEN2
Adder
4.636
960591AF2-350 GEN
Solar/Wind Harmer
12.515
972227AH1-698 GEN1
Adder
3.264
274800UNIV PARK;3U
Adder
7.294
274801UNIV PARK;4U
Adder
7.294
274687WILL CNTY;4U
Adder
34.836
274687WILL CNTY;4U
Adder
34.836
274675JOLIET 29;7U
Adder
38.23
274675JOLIET 29;7U
Adder
36.864
274728ELWOOD EC;5P
Adder
20.452
274731ELWOOD EC;2P
Adder
20.452
274733ELWOOD EC;3P
Adder
20.452
274735ELWOOD EC;4P
Adder
20.452
970833AG2-524 GEN
Solar/Wind Harmer
10.861
970833AG2-524 GEN
Solar/Wind Harmer
5.051
276893AG1-478 C
Solar/Wind Harmer
0.684
24721805FLATG3
50/50
1.793
24344105CKG2
50/50
10.243
962761AG1-125 GEN
Solar/Wind Harmer
95.55
970149AG2-104 GEN
Solar/Wind Harmer
59.002
970155AG2-107 GEN
Solar/Wind Harmer
41.664
972207SS24-0001
Solar/Wind Harmer
28.042
274773LINCOLN ;4U
Adder
7.887
274774LINCOLN ;5U
Adder
7.887
270216AD2-079_GEN
Solar/Wind Harmer
0.767
274723RIVER EC ;12
Adder
22.564
24639705ELKHART HY
Adder
0.193
274751CRETE EC ;1U
Adder
6.143
274754CRETE EC ;4U
Adder
6.143
957891AF2-083 GEN
Solar/Wind Harmer
18.814
274812UNIV PK N;8U
Adder
6.281
274802UNIV PARK;5U
Adder
7.297
945111AF1-176 GEN
Solar/Wind Harmer
22.317
941551AE2-152 GEN
Solar/Wind Harmer
5.664
970373AG2-245 GEN
Solar/Wind Harmer
26.184
274676JOLIET 29;8U
Adder
38.229
274674JOLIET 9 ;6U
Adder
19.168
274732ELWOOD EC;7P
Adder
20.452
274871GR RIDGE ;2U
Solar/Wind Harmer
9.563
274847GR RIDGE ;BU
Solar/Wind Harmer
6.288
270449AD2-020 GEN
Solar/Wind Harmer
3.481
943021AE2-325 GEN
Solar/Wind Harmer
4.524
274745AC1-111 GEN9
Adder
6.929
270055AF2-134 C O1
Solar/Wind Harmer
3.737
276694AA1-018 GEN2
Solar/Wind Harmer
7.76
276691AA1-018 GEN1
Solar/Wind Harmer
0.928
274682WAUKEGAN ;7U
Adder
22.1
274861TOP CROP ;1U
Solar/Wind Harmer
7.448
274828WAUKEGAN ;BP
Adder
13.573
958381AF2-132 GEN
Solar/Wind Harmer
11.111
962781AG1-127 GEN
Solar/Wind Harmer
11.644
964861AG1-349 GEN
Solar/Wind Harmer
9.62
971917AH1-482 GEN
Solar/Wind Harmer
11.099
939401AE1-172 GEN
Solar/Wind Harmer
17.049
274872LEEDK;1U
Solar/Wind Harmer
10.038
276805AD2-038 GEN
Solar/Wind Harmer
6.264
965011AG1-365 GEN
Solar/Wind Harmer
12.193
24441205WTRV SLR C
Solar/Wind Harmer
0.164
276882AE2-255 GEN
Solar/Wind Harmer
4.109
971997AH1-543 GEN
Solar/Wind Harmer
19.171
957471AF2-041 GEN
Solar/Wind Harmer
36.34
959081AF2-199 GEN
Solar/Wind Harmer
12.113
971067AG2-660 GEN
Solar/Wind Harmer
2.817
940581AE2-045 GEN
Solar/Wind Harmer
12.334
971605AH1-302 GEN
Solar/Wind Harmer
10.546
274822ROCKFORD ;11
Adder
23.726
970819AG2-516 GEN
Solar/Wind Harmer
14.459
274761LEE CO EC;2U
Adder
11.136
274766LEE CO EC;7U
Adder
11.004
24728605AND G2
Adder
3.782
970091AG2-072 GEN
Adder
75.433
972203AH1-686 GEN
Adder
1.981
970569AG2-363 GEN
Solar/Wind Harmer
0.692
970707AG2-453 GEN
Solar/Wind Harmer
35.193
972231SS25-0005
Solar/Wind Harmer
11.928
972181SS23-001
Solar/Wind Harmer
7.455
274752CRETE EC ;2U
Adder
6.143
274753CRETE EC ;3U
Adder
6.143
270505AE1-170 C O1
Solar/Wind Harmer
18.826
274814UNIV PK N;0U
Adder
6.336
274807UNIV PK N;3U
Adder
6.322
274811UNIV PK N;7U
Adder
6.281
972259AH1-714 GEN
Adder
23.907
274826FISK ;BP
Adder
13.704
274803UNIV PARK;6U
Adder
7.297
274887GEN-1.85
Solar/Wind Harmer
6.668
276772AC2-154 GEN
Solar/Wind Harmer
3.493
276843GEN-1.7
Solar/Wind Harmer
0.717
276806AD2-047 C O1
Solar/Wind Harmer
13.389
972038AH1-567 GEN2
Adder
0.457
945111AF1-176 GEN
Solar/Wind Harmer
7.073
270063AE2-323 C
Solar/Wind Harmer
2.747
939351AE1-166 GEN
Solar/Wind Harmer
7.407
274676JOLIET 29;8U
Adder
36.864
274729ELWOOD EC;1P
Adder
20.452
274730ELWOOD EC;6P
Adder
20.452
274734ELWOOD EC;8P
Adder
20.452
274736ELWOOD EC;9P
Adder
20.452
943121AE2-341 GEN
Solar/Wind Harmer
18.618
943591AF1-030 GEN
Solar/Wind Harmer
12.412
274682WAUKEGAN ;7U
Adder
22.1
274862TOP CROP ;2U
Solar/Wind Harmer
6.218
964401AG1-302 GEN
Solar/Wind Harmer
11.111
965021AG1-366 GEN
Solar/Wind Harmer
2.835
276868AE1-113 GEN
Solar/Wind Harmer
12.326
274879MINONK ;1U
Solar/Wind Harmer
8.218
276799AD1-013 GEN
Solar/Wind Harmer
2.687
946671AF1-331 GEN
Solar/Wind Harmer
0.509
274855GSG-6 ;RU
Solar/Wind Harmer
4.489
274850MENDOTA H;RU
Solar/Wind Harmer
3.121
276602WESTBROOK C
Solar/Wind Harmer
2.584
959091AF2-200 GEN
Solar/Wind Harmer
24.227
274760LEE CO EC;1U
Adder
11.136
274767LEE CO EC;8U
Adder
11.004
24728705AND G3
Adder
7.909
24728505AND G1
Adder
3.782
970571AG2-364 GEN
Solar/Wind Harmer
0.461
970031AG2-029 GEN
Solar/Wind Harmer
31.055
24729505KEY G4
Adder
8.043
274744AC1-111 GEN8
Adder
6.929
274746AC1-111 G10
Adder
6.929
944161AF1-084 GEN
Solar/Wind Harmer
2.729
970073AG2-061 GEN
Solar/Wind Harmer
2.841
959331AF2-224 GEN
Solar/Wind Harmer
12.193
958391AF2-133 GEN
Solar/Wind Harmer
11.058
971675AH1-338 GEN
Solar/Wind Harmer
21.888
971411AH1-196 GEN
Solar/Wind Harmer
18.238
276861AD2-134 GEN
Solar/Wind Harmer
2.171
276863AD2-134 GEN
Solar/Wind Harmer
2.171
959141AF2-205 GEN
Solar/Wind Harmer
7.345
274863CRW1-WTG
Solar/Wind Harmer
6.769
274864CRW2-WTG
Solar/Wind Harmer
6.769
971171AH1-044 GEN
Solar/Wind Harmer
24.227
276889AE2-281 GEN
Solar/Wind Harmer
2.321
274823ROCKFORD ;21
Adder
23.553
274856ECOGROVE ;U1
Solar/Wind Harmer
4.06
276611AD2-172 GEN
Solar/Wind Harmer
3.079
276612AE2-035 GEN
Solar/Wind Harmer
3.079
926823AC1-168 GEN
Solar/Wind Harmer
5.168
972267AH1-718 GEN
Adder
4.956
24721705FLATG2
50/50
26.627
270102X2-052 ST
50/50
2.048
270100X2-052 CT1
50/50
1.893
270101X2-052 CT2
50/50
1.893
970349AG2-230 GEN
Solar/Wind Harmer
20.036
965681AG1-436 GEN
Solar/Wind Harmer
15.977
965791AG1-447 GEN
Solar/Wind Harmer
8.175
274770LINCOLN ;1U
Adder
7.887
274771LINCOLN ;2U
Adder
7.887
274805UNIV PK N;1U
Adder
6.295
274808UNIV PK N;4U
Adder
6.253
274888KELLY CRK;1U
Solar/Wind Harmer
7.385
276776AD2-060 GEN
Solar/Wind Harmer
0.524
958011AF2-095 GEN
Solar/Wind Harmer
18.022
970941AG2-585 GEN
Solar/Wind Harmer
6.883
247620Y3-023
Adder
0.576
276897AD1-100 C
Solar/Wind Harmer
58.016
961051AF2-396 GEN
Solar/Wind Harmer
19.768
961051AF2-396 GEN
Solar/Wind Harmer
9.195
274674JOLIET 9 ;6U
Adder
19.168
276893AG1-478 C
Solar/Wind Harmer
0.545
270535AF1-215 GEN1
Solar/Wind Harmer
5.606
270536AF1-215 GEN2
Solar/Wind Harmer
5.606
274696ROCKY RD ;4P
Adder
14.03
274695ROCKY RD ;2P
Adder
13.707
274693ROCKY RD ;1P
Adder
13.572
274697ROCKY RD ;3P
Adder
3.724
958481AF2-142 GEN
Solar/Wind Harmer
18.447
274683WAUKEGAN ;8U
Adder
25.894
274683WAUKEGAN ;8U
Adder
21.827
962691AG1-118 GEN
Solar/Wind Harmer
36.785
960751AF2-366 GEN
Solar/Wind Harmer
3.513
958491AF2-143 GEN
Solar/Wind Harmer
18.322
276901AD2-066 C O1
Solar/Wind Harmer
4.281
971341AH1-150 GEN
Solar/Wind Harmer
24.227
971343AH1-151 GEN
Solar/Wind Harmer
24.227
276872AE1-163_GEN1
Solar/Wind Harmer
8.124
276876AE1-163_GEN2
Solar/Wind Harmer
8.124
972235AH1-702 GEN1
Adder
3.043
972236AH1-702 GEN2
Adder
2.646
274764LEE CO EC;5U
Adder
11.162
274765LEE CO EC;6U
Adder
11.162
274762LEE CO EC;3U
Adder
11.136
274763LEE CO EC;4U
Adder
11.031
247621Y3-024
Adder
0.244
270054AF2-122 C O1
Solar/Wind Helper
1.556
CPLELTFEXP_CPLE->PJM
CLTF
3.164
CBM West 2LTFEXP_CBM-W2->PJM
CBM
119.495
NYPJM->LTFIMP_NY
CLTF
3.803
LGEELTFEXP_LGEE->PJM
CLTF
5.486
WECLTFEXP_WEC->PJM
CLTF
4.609
AG2-052LTFEXP_AG2-052->PJM
LTF
0.284
AH1-155LTFEXP_AH1-155->PJM
LTF
0.426
LAGNLTFEXP_LAGN->PJM
CLTF
16.173
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.821
TVALTFEXP_TVA->PJM
CLTF
7.643
CBM West 1LTFEXP_CBM-W1->PJM
CBM
145.936
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.934
MECLTFEXP_MEC->PJM
CLTF
18.402
SIGELTFEXP_SIGE->PJM
CLTF
0.471

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AP_P2-3_MP-500-020_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-020_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:128.87 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5890.54
MW Contribution:
59.16
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721805FLATG3
50/50
1.803
24344105CKG2
50/50
10.303
962761AG1-125 GEN
Solar/Wind Harmer
95.812
970149AG2-104 GEN
Solar/Wind Harmer
59.164
970155AG2-107 GEN
Solar/Wind Harmer
41.779
972207SS24-0001
Solar/Wind Harmer
28.22
274773LINCOLN ;4U
Adder
7.937
274774LINCOLN ;5U
Adder
7.937
270216AD2-079_GEN
Solar/Wind Harmer
0.772
274723RIVER EC ;12
Adder
22.708
24639705ELKHART HY
Adder
0.194
274751CRETE EC ;1U
Adder
6.183
274754CRETE EC ;4U
Adder
6.183
957891AF2-083 GEN
Solar/Wind Harmer
18.934
274812UNIV PK N;8U
Adder
6.321
274802UNIV PARK;5U
Adder
7.344
945111AF1-176 GEN
Solar/Wind Harmer
22.461
941551AE2-152 GEN
Solar/Wind Harmer
5.701
970373AG2-245 GEN
Solar/Wind Harmer
26.353
274676JOLIET 29;8U
Adder
38.476
274674JOLIET 9 ;6U
Adder
19.291
274732ELWOOD EC;7P
Adder
20.585
274871GR RIDGE ;2U
Solar/Wind Harmer
9.625
274847GR RIDGE ;BU
Solar/Wind Harmer
6.329
24721605FLATG1
50/50
1.803
270071AF1-092 GEN
Solar/Wind Harmer
19.487
960681AF2-359 GEN
Solar/Wind Harmer
4.86
971771AH1-392 GEN
Solar/Wind Harmer
11.525
274775LINCOLN ;6U
Adder
7.937
274776LINCOLN ;7U
Adder
7.937
274777LINCOLN ;8U
Adder
7.937
270526AF1-158 GEN
Solar/Wind Harmer
5.8
274827FISK ;RP
Adder
9.774
972037AH1-567 GEN1
Adder
0.231
960591AF2-350 GEN
Solar/Wind Harmer
12.596
972228AH1-698 GEN2
Adder
4.665
972227AH1-698 GEN1
Adder
3.285
274800UNIV PARK;3U
Adder
7.341
274801UNIV PARK;4U
Adder
7.341
274687WILL CNTY;4U
Adder
35.06
274687WILL CNTY;4U
Adder
35.06
274675JOLIET 29;7U
Adder
38.476
274675JOLIET 29;7U
Adder
37.102
274728ELWOOD EC;5P
Adder
20.585
274731ELWOOD EC;2P
Adder
20.584
274733ELWOOD EC;3P
Adder
20.584
274735ELWOOD EC;4P
Adder
20.584
970833AG2-524 GEN
Solar/Wind Harmer
10.931
970833AG2-524 GEN
Solar/Wind Harmer
5.084
276893AG1-478 C
Solar/Wind Harmer
0.688
970031AG2-029 GEN
Solar/Wind Harmer
31.256
24729505KEY G4
Adder
8.096
274744AC1-111 GEN8
Adder
6.974
274746AC1-111 G10
Adder
6.974
944161AF1-084 GEN
Solar/Wind Harmer
2.746
970073AG2-061 GEN
Solar/Wind Harmer
2.859
959331AF2-224 GEN
Solar/Wind Harmer
12.273
958391AF2-133 GEN
Solar/Wind Harmer
11.131
971675AH1-338 GEN
Solar/Wind Harmer
22.032
971411AH1-196 GEN
Solar/Wind Harmer
18.358
276861AD2-134 GEN
Solar/Wind Harmer
2.185
276863AD2-134 GEN
Solar/Wind Harmer
2.185
959141AF2-205 GEN
Solar/Wind Harmer
7.394
274863CRW1-WTG
Solar/Wind Harmer
6.814
274864CRW2-WTG
Solar/Wind Harmer
6.814
971171AH1-044 GEN
Solar/Wind Harmer
24.388
276889AE2-281 GEN
Solar/Wind Harmer
2.337
274823ROCKFORD ;21
Adder
23.71
274856ECOGROVE ;U1
Solar/Wind Harmer
4.087
276611AD2-172 GEN
Solar/Wind Harmer
3.1
276612AE2-035 GEN
Solar/Wind Harmer
3.1
926823AC1-168 GEN
Solar/Wind Harmer
5.202
972267AH1-718 GEN
Adder
4.989
24721705FLATG2
50/50
26.77
270102X2-052 ST
50/50
2.061
270100X2-052 CT1
50/50
1.905
270101X2-052 CT2
50/50
1.905
970349AG2-230 GEN
Solar/Wind Harmer
20.157
965681AG1-436 GEN
Solar/Wind Harmer
16.078
965791AG1-447 GEN
Solar/Wind Harmer
8.226
274770LINCOLN ;1U
Adder
7.937
274771LINCOLN ;2U
Adder
7.937
274805UNIV PK N;1U
Adder
6.335
274808UNIV PK N;4U
Adder
6.293
274888KELLY CRK;1U
Solar/Wind Harmer
7.433
276776AD2-060 GEN
Solar/Wind Harmer
0.527
958011AF2-095 GEN
Solar/Wind Harmer
18.138
970941AG2-585 GEN
Solar/Wind Harmer
6.928
247620Y3-023
Adder
0.58
276897AD1-100 C
Solar/Wind Harmer
58.39
961051AF2-396 GEN
Solar/Wind Harmer
19.896
961051AF2-396 GEN
Solar/Wind Harmer
9.254
274674JOLIET 9 ;6U
Adder
19.291
276893AG1-478 C
Solar/Wind Harmer
0.549
270535AF1-215 GEN1
Solar/Wind Harmer
5.643
270536AF1-215 GEN2
Solar/Wind Harmer
5.643
274695ROCKY RD ;2P
Adder
13.796
274693ROCKY RD ;1P
Adder
13.661
274697ROCKY RD ;3P
Adder
3.748
274696ROCKY RD ;4P
Adder
14.122
958481AF2-142 GEN
Solar/Wind Harmer
18.568
274683WAUKEGAN ;8U
Adder
26.063
274683WAUKEGAN ;8U
Adder
21.97
962691AG1-118 GEN
Solar/Wind Harmer
37.026
960751AF2-366 GEN
Solar/Wind Harmer
3.536
958491AF2-143 GEN
Solar/Wind Harmer
18.442
276901AD2-066 C O1
Solar/Wind Harmer
4.309
971341AH1-150 GEN
Solar/Wind Harmer
24.388
971343AH1-151 GEN
Solar/Wind Harmer
24.388
276872AE1-163_GEN1
Solar/Wind Harmer
8.178
276876AE1-163_GEN2
Solar/Wind Harmer
8.178
972235AH1-702 GEN1
Adder
3.063
972236AH1-702 GEN2
Adder
2.663
274764LEE CO EC;5U
Adder
11.237
274765LEE CO EC;6U
Adder
11.237
274762LEE CO EC;3U
Adder
11.21
274763LEE CO EC;4U
Adder
11.105
247621Y3-024
Adder
0.245
270054AF2-122 C O1
Solar/Wind Helper
1.545
270449AD2-020 GEN
Solar/Wind Harmer
3.504
943021AE2-325 GEN
Solar/Wind Harmer
4.553
274745AC1-111 GEN9
Adder
6.974
270055AF2-134 C O1
Solar/Wind Harmer
3.762
276694AA1-018 GEN2
Solar/Wind Harmer
7.811
276691AA1-018 GEN1
Solar/Wind Harmer
0.934
274682WAUKEGAN ;7U
Adder
22.245
274861TOP CROP ;1U
Solar/Wind Harmer
7.496
274828WAUKEGAN ;BP
Adder
13.662
958381AF2-132 GEN
Solar/Wind Harmer
11.184
962781AG1-127 GEN
Solar/Wind Harmer
11.72
964861AG1-349 GEN
Solar/Wind Harmer
9.683
971917AH1-482 GEN
Solar/Wind Harmer
11.172
939401AE1-172 GEN
Solar/Wind Harmer
17.161
274872LEEDK;1U
Solar/Wind Harmer
10.104
276805AD2-038 GEN
Solar/Wind Harmer
6.305
965011AG1-365 GEN
Solar/Wind Harmer
12.273
24441205WTRV SLR C
Solar/Wind Harmer
0.165
276882AE2-255 GEN
Solar/Wind Harmer
4.136
971997AH1-543 GEN
Solar/Wind Harmer
19.298
957471AF2-041 GEN
Solar/Wind Harmer
36.581
959081AF2-199 GEN
Solar/Wind Harmer
12.194
971067AG2-660 GEN
Solar/Wind Harmer
2.836
940581AE2-045 GEN
Solar/Wind Harmer
12.416
971605AH1-302 GEN
Solar/Wind Harmer
10.616
274822ROCKFORD ;11
Adder
23.883
970819AG2-516 GEN
Solar/Wind Harmer
14.555
274761LEE CO EC;2U
Adder
11.21
274766LEE CO EC;7U
Adder
11.078
24728605AND G2
Adder
3.813
970091AG2-072 GEN
Adder
76.053
972203AH1-686 GEN
Adder
2
970569AG2-363 GEN
Solar/Wind Harmer
0.697
24722005FLATG5
50/50
1.803
24721905FLATG4
50/50
32.925
962771AG1-126 GEN
Solar/Wind Harmer
95.812
970153AG2-106 GEN
Solar/Wind Harmer
41.779
971347AH1-153 GEN
Solar/Wind Harmer
6.719
270043AE2-236 GEN
Solar/Wind Harmer
7.211
274772LINCOLN ;3U
Adder
7.937
24441505OLIV SLR
Solar/Wind Harmer
0.171
247643Z2-116 C
Solar/Wind Harmer
0.089
274724RIVER EC ;11
Adder
22.446
944531AF1-118 GEN
Solar/Wind Harmer
44.315
276164X3-005 C
Solar/Wind Harmer
0.889
970707AG2-453 GEN
Solar/Wind Harmer
35.418
972231SS25-0005
Solar/Wind Harmer
12.005
972181SS23-001
Solar/Wind Harmer
7.503
274752CRETE EC ;2U
Adder
6.183
274753CRETE EC ;3U
Adder
6.183
270505AE1-170 C O1
Solar/Wind Harmer
18.946
274814UNIV PK N;0U
Adder
6.376
274807UNIV PK N;3U
Adder
6.363
274811UNIV PK N;7U
Adder
6.321
972259AH1-714 GEN
Adder
24.06
274826FISK ;BP
Adder
13.792
274803UNIV PARK;6U
Adder
7.344
274887GEN-1.85
Solar/Wind Harmer
6.711
276772AC2-154 GEN
Solar/Wind Harmer
3.515
276843GEN-1.7
Solar/Wind Harmer
0.722
276806AD2-047 C O1
Solar/Wind Harmer
13.475
972038AH1-567 GEN2
Adder
0.459
945111AF1-176 GEN
Solar/Wind Harmer
7.118
270063AE2-323 C
Solar/Wind Harmer
2.765
939351AE1-166 GEN
Solar/Wind Harmer
7.454
274676JOLIET 29;8U
Adder
37.102
274729ELWOOD EC;1P
Adder
20.584
274730ELWOOD EC;6P
Adder
20.585
274734ELWOOD EC;8P
Adder
20.585
274736ELWOOD EC;9P
Adder
20.585
943121AE2-341 GEN
Solar/Wind Harmer
18.739
943591AF1-030 GEN
Solar/Wind Harmer
12.493
274682WAUKEGAN ;7U
Adder
22.245
274862TOP CROP ;2U
Solar/Wind Harmer
6.259
964401AG1-302 GEN
Solar/Wind Harmer
11.184
965021AG1-366 GEN
Solar/Wind Harmer
2.854
276868AE1-113 GEN
Solar/Wind Harmer
12.408
274879MINONK ;1U
Solar/Wind Harmer
8.272
276799AD1-013 GEN
Solar/Wind Harmer
2.705
946671AF1-331 GEN
Solar/Wind Harmer
0.513
274855GSG-6 ;RU
Solar/Wind Harmer
4.519
274850MENDOTA H;RU
Solar/Wind Harmer
3.142
276602WESTBROOK C
Solar/Wind Harmer
2.601
959091AF2-200 GEN
Solar/Wind Harmer
24.388
274760LEE CO EC;1U
Adder
11.21
274767LEE CO EC;8U
Adder
11.078
24728705AND G3
Adder
7.974
24728505AND G1
Adder
3.813
970571AG2-364 GEN
Solar/Wind Harmer
0.465
CPLELTFEXP_CPLE->PJM
CLTF
3.244
CBM West 2LTFEXP_CBM-W2->PJM
CBM
120.566
NYPJM->LTFIMP_NY
CLTF
3.761
LGEELTFEXP_LGEE->PJM
CLTF
5.541
WECLTFEXP_WEC->PJM
CLTF
4.639
AG2-052LTFEXP_AG2-052->PJM
LTF
0.286
AH1-155LTFEXP_AH1-155->PJM
LTF
0.429
LAGNLTFEXP_LAGN->PJM
CLTF
16.333
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.048
TVALTFEXP_TVA->PJM
CLTF
7.723
CBM West 1LTFEXP_CBM-W1->PJM
CBM
147.108
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.235
MECLTFEXP_MEC->PJM
CLTF
18.537
SIGELTFEXP_SIGE->PJM
CLTF
0.475

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AP_P2-3_MP-500-021_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-021_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:128.84 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5889.29
MW Contribution:
59.15
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
1.802
270071AF1-092 GEN
Solar/Wind Harmer
19.478
960681AF2-359 GEN
Solar/Wind Harmer
4.858
971771AH1-392 GEN
Solar/Wind Harmer
11.519
274775LINCOLN ;6U
Adder
7.933
274776LINCOLN ;7U
Adder
7.933
274777LINCOLN ;8U
Adder
7.933
270526AF1-158 GEN
Solar/Wind Harmer
5.797
274827FISK ;RP
Adder
9.769
972037AH1-567 GEN1
Adder
0.23
960591AF2-350 GEN
Solar/Wind Harmer
12.59
972228AH1-698 GEN2
Adder
4.663
972227AH1-698 GEN1
Adder
3.283
274800UNIV PARK;3U
Adder
7.337
274801UNIV PARK;4U
Adder
7.337
274687WILL CNTY;4U
Adder
35.043
274687WILL CNTY;4U
Adder
35.043
274675JOLIET 29;7U
Adder
38.457
274675JOLIET 29;7U
Adder
37.084
274728ELWOOD EC;5P
Adder
20.574
274731ELWOOD EC;2P
Adder
20.574
274733ELWOOD EC;3P
Adder
20.574
274735ELWOOD EC;4P
Adder
20.574
970833AG2-524 GEN
Solar/Wind Harmer
10.925
970833AG2-524 GEN
Solar/Wind Harmer
5.082
276893AG1-478 C
Solar/Wind Harmer
0.688
970031AG2-029 GEN
Solar/Wind Harmer
31.241
24729505KEY G4
Adder
8.091
274744AC1-111 GEN8
Adder
6.97
274746AC1-111 G10
Adder
6.97
944161AF1-084 GEN
Solar/Wind Harmer
2.745
970073AG2-061 GEN
Solar/Wind Harmer
2.858
959331AF2-224 GEN
Solar/Wind Harmer
12.267
958391AF2-133 GEN
Solar/Wind Harmer
11.125
971675AH1-338 GEN
Solar/Wind Harmer
22.021
971411AH1-196 GEN
Solar/Wind Harmer
18.349
276861AD2-134 GEN
Solar/Wind Harmer
2.184
276863AD2-134 GEN
Solar/Wind Harmer
2.184
959141AF2-205 GEN
Solar/Wind Harmer
7.39
274863CRW1-WTG
Solar/Wind Harmer
6.811
274864CRW2-WTG
Solar/Wind Harmer
6.811
971171AH1-044 GEN
Solar/Wind Harmer
24.375
276889AE2-281 GEN
Solar/Wind Harmer
2.336
274823ROCKFORD ;21
Adder
23.698
274856ECOGROVE ;U1
Solar/Wind Harmer
4.085
276611AD2-172 GEN
Solar/Wind Harmer
3.098
276612AE2-035 GEN
Solar/Wind Harmer
3.098
926823AC1-168 GEN
Solar/Wind Harmer
5.2
972267AH1-718 GEN
Adder
4.987
24721705FLATG2
50/50
26.758
270102X2-052 ST
50/50
2.06
270100X2-052 CT1
50/50
1.904
270101X2-052 CT2
50/50
1.904
970349AG2-230 GEN
Solar/Wind Harmer
20.147
965681AG1-436 GEN
Solar/Wind Harmer
16.07
965791AG1-447 GEN
Solar/Wind Harmer
8.222
274770LINCOLN ;1U
Adder
7.933
274771LINCOLN ;2U
Adder
7.933
274805UNIV PK N;1U
Adder
6.332
274808UNIV PK N;4U
Adder
6.29
274888KELLY CRK;1U
Solar/Wind Harmer
7.429
276776AD2-060 GEN
Solar/Wind Harmer
0.527
958011AF2-095 GEN
Solar/Wind Harmer
18.129
970941AG2-585 GEN
Solar/Wind Harmer
6.924
247620Y3-023
Adder
0.579
276897AD1-100 C
Solar/Wind Harmer
58.361
961051AF2-396 GEN
Solar/Wind Harmer
19.886
961051AF2-396 GEN
Solar/Wind Harmer
9.249
274674JOLIET 9 ;6U
Adder
19.282
276893AG1-478 C
Solar/Wind Harmer
0.548
24721805FLATG3
50/50
1.802
24344105CKG2
50/50
10.299
962761AG1-125 GEN
Solar/Wind Harmer
95.791
970149AG2-104 GEN
Solar/Wind Harmer
59.151
970155AG2-107 GEN
Solar/Wind Harmer
41.769
972207SS24-0001
Solar/Wind Harmer
28.206
274773LINCOLN ;4U
Adder
7.933
274774LINCOLN ;5U
Adder
7.933
270216AD2-079_GEN
Solar/Wind Harmer
0.771
274723RIVER EC ;12
Adder
22.697
24639705ELKHART HY
Adder
0.194
274751CRETE EC ;1U
Adder
6.18
274754CRETE EC ;4U
Adder
6.18
957891AF2-083 GEN
Solar/Wind Harmer
18.925
274812UNIV PK N;8U
Adder
6.318
274802UNIV PARK;5U
Adder
7.34
945111AF1-176 GEN
Solar/Wind Harmer
22.45
941551AE2-152 GEN
Solar/Wind Harmer
5.698
970373AG2-245 GEN
Solar/Wind Harmer
26.34
274676JOLIET 29;8U
Adder
38.457
274674JOLIET 9 ;6U
Adder
19.282
274732ELWOOD EC;7P
Adder
20.574
274871GR RIDGE ;2U
Solar/Wind Harmer
9.62
274847GR RIDGE ;BU
Solar/Wind Harmer
6.326
270449AD2-020 GEN
Solar/Wind Harmer
3.502
943021AE2-325 GEN
Solar/Wind Harmer
4.551
274745AC1-111 GEN9
Adder
6.97
270055AF2-134 C O1
Solar/Wind Harmer
3.76
276694AA1-018 GEN2
Solar/Wind Harmer
7.807
276691AA1-018 GEN1
Solar/Wind Harmer
0.933
274682WAUKEGAN ;7U
Adder
22.234
274861TOP CROP ;1U
Solar/Wind Harmer
7.493
274828WAUKEGAN ;BP
Adder
13.655
958381AF2-132 GEN
Solar/Wind Harmer
11.178
962781AG1-127 GEN
Solar/Wind Harmer
11.715
964861AG1-349 GEN
Solar/Wind Harmer
9.678
971917AH1-482 GEN
Solar/Wind Harmer
11.166
939401AE1-172 GEN
Solar/Wind Harmer
17.153
274872LEEDK;1U
Solar/Wind Harmer
10.099
276805AD2-038 GEN
Solar/Wind Harmer
6.302
965011AG1-365 GEN
Solar/Wind Harmer
12.267
24441205WTRV SLR C
Solar/Wind Harmer
0.165
276882AE2-255 GEN
Solar/Wind Harmer
4.134
971997AH1-543 GEN
Solar/Wind Harmer
19.288
957471AF2-041 GEN
Solar/Wind Harmer
36.563
959081AF2-199 GEN
Solar/Wind Harmer
12.188
971067AG2-660 GEN
Solar/Wind Harmer
2.834
940581AE2-045 GEN
Solar/Wind Harmer
12.41
971605AH1-302 GEN
Solar/Wind Harmer
10.611
274822ROCKFORD ;11
Adder
23.871
970819AG2-516 GEN
Solar/Wind Harmer
14.548
274761LEE CO EC;2U
Adder
11.205
274766LEE CO EC;7U
Adder
11.073
24728605AND G2
Adder
3.81
970091AG2-072 GEN
Adder
76.004
972203AH1-686 GEN
Adder
1.999
970569AG2-363 GEN
Solar/Wind Harmer
0.696
270535AF1-215 GEN1
Solar/Wind Harmer
5.64
270536AF1-215 GEN2
Solar/Wind Harmer
5.64
274695ROCKY RD ;2P
Adder
13.79
274693ROCKY RD ;1P
Adder
13.654
274697ROCKY RD ;3P
Adder
3.746
274696ROCKY RD ;4P
Adder
14.115
958481AF2-142 GEN
Solar/Wind Harmer
18.559
274683WAUKEGAN ;8U
Adder
26.05
274683WAUKEGAN ;8U
Adder
21.959
962691AG1-118 GEN
Solar/Wind Harmer
37.008
960751AF2-366 GEN
Solar/Wind Harmer
3.534
958491AF2-143 GEN
Solar/Wind Harmer
18.433
276901AD2-066 C O1
Solar/Wind Harmer
4.307
971341AH1-150 GEN
Solar/Wind Harmer
24.375
971343AH1-151 GEN
Solar/Wind Harmer
24.375
276872AE1-163_GEN1
Solar/Wind Harmer
8.174
276876AE1-163_GEN2
Solar/Wind Harmer
8.174
972235AH1-702 GEN1
Adder
3.062
972236AH1-702 GEN2
Adder
2.662
274764LEE CO EC;5U
Adder
11.231
274765LEE CO EC;6U
Adder
11.231
274762LEE CO EC;3U
Adder
11.205
274763LEE CO EC;4U
Adder
11.099
247621Y3-024
Adder
0.245
270054AF2-122 C O1
Solar/Wind Helper
1.546
24722005FLATG5
50/50
1.802
24721905FLATG4
50/50
32.911
962771AG1-126 GEN
Solar/Wind Harmer
95.791
970153AG2-106 GEN
Solar/Wind Harmer
41.769
971347AH1-153 GEN
Solar/Wind Harmer
6.716
270043AE2-236 GEN
Solar/Wind Harmer
7.208
274772LINCOLN ;3U
Adder
7.933
24441505OLIV SLR
Solar/Wind Harmer
0.171
247643Z2-116 C
Solar/Wind Harmer
0.089
274724RIVER EC ;11
Adder
22.435
944531AF1-118 GEN
Solar/Wind Harmer
44.293
276164X3-005 C
Solar/Wind Harmer
0.888
970707AG2-453 GEN
Solar/Wind Harmer
35.401
972231SS25-0005
Solar/Wind Harmer
11.999
972181SS23-001
Solar/Wind Harmer
7.499
274752CRETE EC ;2U
Adder
6.18
274753CRETE EC ;3U
Adder
6.18
270505AE1-170 C O1
Solar/Wind Harmer
18.937
274814UNIV PK N;0U
Adder
6.373
274807UNIV PK N;3U
Adder
6.359
274811UNIV PK N;7U
Adder
6.318
972259AH1-714 GEN
Adder
24.048
274826FISK ;BP
Adder
13.785
274803UNIV PARK;6U
Adder
7.34
274887GEN-1.85
Solar/Wind Harmer
6.707
276772AC2-154 GEN
Solar/Wind Harmer
3.513
276843GEN-1.7
Solar/Wind Harmer
0.722
276806AD2-047 C O1
Solar/Wind Harmer
13.468
972038AH1-567 GEN2
Adder
0.459
945111AF1-176 GEN
Solar/Wind Harmer
7.115
270063AE2-323 C
Solar/Wind Harmer
2.764
939351AE1-166 GEN
Solar/Wind Harmer
7.451
274676JOLIET 29;8U
Adder
37.084
274729ELWOOD EC;1P
Adder
20.574
274730ELWOOD EC;6P
Adder
20.574
274734ELWOOD EC;8P
Adder
20.574
274736ELWOOD EC;9P
Adder
20.574
943121AE2-341 GEN
Solar/Wind Harmer
18.73
943591AF1-030 GEN
Solar/Wind Harmer
12.486
274682WAUKEGAN ;7U
Adder
22.234
274862TOP CROP ;2U
Solar/Wind Harmer
6.256
964401AG1-302 GEN
Solar/Wind Harmer
11.178
965021AG1-366 GEN
Solar/Wind Harmer
2.853
276868AE1-113 GEN
Solar/Wind Harmer
12.401
274879MINONK ;1U
Solar/Wind Harmer
8.268
276799AD1-013 GEN
Solar/Wind Harmer
2.704
946671AF1-331 GEN
Solar/Wind Harmer
0.512
274855GSG-6 ;RU
Solar/Wind Harmer
4.516
274850MENDOTA H;RU
Solar/Wind Harmer
3.14
276602WESTBROOK C
Solar/Wind Harmer
2.6
959091AF2-200 GEN
Solar/Wind Harmer
24.375
274760LEE CO EC;1U
Adder
11.205
274767LEE CO EC;8U
Adder
11.073
24728705AND G3
Adder
7.969
24728505AND G1
Adder
3.81
970571AG2-364 GEN
Solar/Wind Harmer
0.464
CPLELTFEXP_CPLE->PJM
CLTF
3.243
CBM West 2LTFEXP_CBM-W2->PJM
CBM
120.494
NYPJM->LTFIMP_NY
CLTF
3.758
LGEELTFEXP_LGEE->PJM
CLTF
5.537
WECLTFEXP_WEC->PJM
CLTF
4.637
AG2-052LTFEXP_AG2-052->PJM
LTF
0.286
AH1-155LTFEXP_AH1-155->PJM
LTF
0.429
LAGNLTFEXP_LAGN->PJM
CLTF
16.323
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.041
TVALTFEXP_TVA->PJM
CLTF
7.718
CBM West 1LTFEXP_CBM-W1->PJM
CBM
147.021
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.216
MECLTFEXP_MEC->PJM
CLTF
18.527
SIGELTFEXP_SIGE->PJM
CLTF
0.475

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AEP_P4_#37_05MOUNTN 765_B1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:128.83 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5888.74
MW Contribution:
59.15
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721705FLATG2
50/50
26.753
270102X2-052 ST
50/50
2.06
270100X2-052 CT1
50/50
1.903
270101X2-052 CT2
50/50
1.903
970349AG2-230 GEN
Solar/Wind Harmer
20.143
965681AG1-436 GEN
Solar/Wind Harmer
16.067
965791AG1-447 GEN
Solar/Wind Harmer
8.22
274770LINCOLN ;1U
Adder
7.932
274771LINCOLN ;2U
Adder
7.932
274805UNIV PK N;1U
Adder
6.33
274808UNIV PK N;4U
Adder
6.289
274888KELLY CRK;1U
Solar/Wind Harmer
7.428
276776AD2-060 GEN
Solar/Wind Harmer
0.527
958011AF2-095 GEN
Solar/Wind Harmer
18.125
970941AG2-585 GEN
Solar/Wind Harmer
6.923
247620Y3-023
Adder
0.579
276897AD1-100 C
Solar/Wind Harmer
58.349
961051AF2-396 GEN
Solar/Wind Harmer
19.882
961051AF2-396 GEN
Solar/Wind Harmer
9.247
274674JOLIET 9 ;6U
Adder
19.278
276893AG1-478 C
Solar/Wind Harmer
0.548
270535AF1-215 GEN1
Solar/Wind Harmer
5.639
270536AF1-215 GEN2
Solar/Wind Harmer
5.639
274696ROCKY RD ;4P
Adder
14.112
274695ROCKY RD ;2P
Adder
13.787
274693ROCKY RD ;1P
Adder
13.651
274697ROCKY RD ;3P
Adder
3.745
958481AF2-142 GEN
Solar/Wind Harmer
18.555
274683WAUKEGAN ;8U
Adder
26.045
274683WAUKEGAN ;8U
Adder
21.955
962691AG1-118 GEN
Solar/Wind Harmer
37
960751AF2-366 GEN
Solar/Wind Harmer
3.533
958491AF2-143 GEN
Solar/Wind Harmer
18.429
276901AD2-066 C O1
Solar/Wind Harmer
4.306
971341AH1-150 GEN
Solar/Wind Harmer
24.37
971343AH1-151 GEN
Solar/Wind Harmer
24.37
24721605FLATG1
50/50
1.801
270071AF1-092 GEN
Solar/Wind Harmer
19.474
960681AF2-359 GEN
Solar/Wind Harmer
4.857
971771AH1-392 GEN
Solar/Wind Harmer
11.517
274775LINCOLN ;6U
Adder
7.932
274776LINCOLN ;7U
Adder
7.932
274777LINCOLN ;8U
Adder
7.932
270526AF1-158 GEN
Solar/Wind Harmer
5.796
274827FISK ;RP
Adder
9.767
972037AH1-567 GEN1
Adder
0.23
960591AF2-350 GEN
Solar/Wind Harmer
12.587
972228AH1-698 GEN2
Adder
4.662
972227AH1-698 GEN1
Adder
3.283
274800UNIV PARK;3U
Adder
7.336
274801UNIV PARK;4U
Adder
7.336
274687WILL CNTY;4U
Adder
35.036
274687WILL CNTY;4U
Adder
35.036
274675JOLIET 29;7U
Adder
38.449
274675JOLIET 29;7U
Adder
37.076
274728ELWOOD EC;5P
Adder
20.57
274731ELWOOD EC;2P
Adder
20.57
274733ELWOOD EC;3P
Adder
20.57
274735ELWOOD EC;4P
Adder
20.57
970833AG2-524 GEN
Solar/Wind Harmer
10.923
970833AG2-524 GEN
Solar/Wind Harmer
5.081
276893AG1-478 C
Solar/Wind Harmer
0.688
970031AG2-029 GEN
Solar/Wind Harmer
31.234
24729505KEY G4
Adder
8.09
274744AC1-111 GEN8
Adder
6.969
274746AC1-111 G10
Adder
6.969
944161AF1-084 GEN
Solar/Wind Harmer
2.745
970073AG2-061 GEN
Solar/Wind Harmer
2.857
959331AF2-224 GEN
Solar/Wind Harmer
12.264
958391AF2-133 GEN
Solar/Wind Harmer
11.123
971675AH1-338 GEN
Solar/Wind Harmer
22.016
971411AH1-196 GEN
Solar/Wind Harmer
18.345
276861AD2-134 GEN
Solar/Wind Harmer
2.183
276863AD2-134 GEN
Solar/Wind Harmer
2.183
959141AF2-205 GEN
Solar/Wind Harmer
7.389
274863CRW1-WTG
Solar/Wind Harmer
6.809
274864CRW2-WTG
Solar/Wind Harmer
6.809
971171AH1-044 GEN
Solar/Wind Harmer
24.37
276889AE2-281 GEN
Solar/Wind Harmer
2.335
274823ROCKFORD ;21
Adder
23.693
274856ECOGROVE ;U1
Solar/Wind Harmer
4.084
276611AD2-172 GEN
Solar/Wind Harmer
3.098
276612AE2-035 GEN
Solar/Wind Harmer
3.098
926823AC1-168 GEN
Solar/Wind Harmer
5.199
972267AH1-718 GEN
Adder
4.986
24722005FLATG5
50/50
1.801
24721905FLATG4
50/50
32.904
962771AG1-126 GEN
Solar/Wind Harmer
95.781
970153AG2-106 GEN
Solar/Wind Harmer
41.765
971347AH1-153 GEN
Solar/Wind Harmer
6.714
270043AE2-236 GEN
Solar/Wind Harmer
7.206
274772LINCOLN ;3U
Adder
7.932
24441505OLIV SLR
Solar/Wind Harmer
0.171
247643Z2-116 C
Solar/Wind Harmer
0.089
274724RIVER EC ;11
Adder
22.43
944531AF1-118 GEN
Solar/Wind Harmer
44.283
276164X3-005 C
Solar/Wind Harmer
0.888
970707AG2-453 GEN
Solar/Wind Harmer
35.393
972231SS25-0005
Solar/Wind Harmer
11.996
972181SS23-001
Solar/Wind Harmer
7.498
274752CRETE EC ;2U
Adder
6.178
274753CRETE EC ;3U
Adder
6.178
270505AE1-170 C O1
Solar/Wind Harmer
18.933
274814UNIV PK N;0U
Adder
6.372
274807UNIV PK N;3U
Adder
6.358
274811UNIV PK N;7U
Adder
6.317
972259AH1-714 GEN
Adder
24.043
274826FISK ;BP
Adder
13.782
274803UNIV PARK;6U
Adder
7.339
274887GEN-1.85
Solar/Wind Harmer
6.706
276772AC2-154 GEN
Solar/Wind Harmer
3.513
276843GEN-1.7
Solar/Wind Harmer
0.722
276806AD2-047 C O1
Solar/Wind Harmer
13.465
972038AH1-567 GEN2
Adder
0.459
945111AF1-176 GEN
Solar/Wind Harmer
7.113
270063AE2-323 C
Solar/Wind Harmer
2.763
939351AE1-166 GEN
Solar/Wind Harmer
7.449
274676JOLIET 29;8U
Adder
37.076
274729ELWOOD EC;1P
Adder
20.57
274730ELWOOD EC;6P
Adder
20.57
274734ELWOOD EC;8P
Adder
20.57
274736ELWOOD EC;9P
Adder
20.57
943121AE2-341 GEN
Solar/Wind Harmer
18.726
943591AF1-030 GEN
Solar/Wind Harmer
12.484
274682WAUKEGAN ;7U
Adder
22.229
274862TOP CROP ;2U
Solar/Wind Harmer
6.254
964401AG1-302 GEN
Solar/Wind Harmer
11.176
965021AG1-366 GEN
Solar/Wind Harmer
2.852
276868AE1-113 GEN
Solar/Wind Harmer
12.399
274879MINONK ;1U
Solar/Wind Harmer
8.266
276799AD1-013 GEN
Solar/Wind Harmer
2.703
946671AF1-331 GEN
Solar/Wind Harmer
0.512
274855GSG-6 ;RU
Solar/Wind Harmer
4.515
274850MENDOTA H;RU
Solar/Wind Harmer
3.139
276602WESTBROOK C
Solar/Wind Harmer
2.599
959091AF2-200 GEN
Solar/Wind Harmer
24.37
274760LEE CO EC;1U
Adder
11.202
274767LEE CO EC;8U
Adder
11.07
24728705AND G3
Adder
7.966
24728505AND G1
Adder
3.809
970571AG2-364 GEN
Solar/Wind Harmer
0.464
24721805FLATG3
50/50
1.801
24344105CKG2
50/50
10.297
962761AG1-125 GEN
Solar/Wind Harmer
95.781
970149AG2-104 GEN
Solar/Wind Harmer
59.145
970155AG2-107 GEN
Solar/Wind Harmer
41.765
972207SS24-0001
Solar/Wind Harmer
28.2
274773LINCOLN ;4U
Adder
7.932
274774LINCOLN ;5U
Adder
7.932
270216AD2-079_GEN
Solar/Wind Harmer
0.771
274723RIVER EC ;12
Adder
22.692
24639705ELKHART HY
Adder
0.194
274751CRETE EC ;1U
Adder
6.178
274754CRETE EC ;4U
Adder
6.178
957891AF2-083 GEN
Solar/Wind Harmer
18.921
274812UNIV PK N;8U
Adder
6.317
274802UNIV PARK;5U
Adder
7.339
945111AF1-176 GEN
Solar/Wind Harmer
22.445
941551AE2-152 GEN
Solar/Wind Harmer
5.697
970373AG2-245 GEN
Solar/Wind Harmer
26.334
276872AE1-163_GEN1
Solar/Wind Harmer
8.172
276876AE1-163_GEN2
Solar/Wind Harmer
8.172
972235AH1-702 GEN1
Adder
3.061
972236AH1-702 GEN2
Adder
2.662
274764LEE CO EC;5U
Adder
11.229
274765LEE CO EC;6U
Adder
11.229
274762LEE CO EC;3U
Adder
11.202
274763LEE CO EC;4U
Adder
11.097
247621Y3-024
Adder
0.245
270054AF2-122 C O1
Solar/Wind Helper
1.547
274676JOLIET 29;8U
Adder
38.449
274674JOLIET 9 ;6U
Adder
19.278
274732ELWOOD EC;7P
Adder
20.57
274871GR RIDGE ;2U
Solar/Wind Harmer
9.618
274847GR RIDGE ;BU
Solar/Wind Harmer
6.324
270449AD2-020 GEN
Solar/Wind Harmer
3.501
943021AE2-325 GEN
Solar/Wind Harmer
4.55
274745AC1-111 GEN9
Adder
6.969
270055AF2-134 C O1
Solar/Wind Harmer
3.759
276694AA1-018 GEN2
Solar/Wind Harmer
7.805
276691AA1-018 GEN1
Solar/Wind Harmer
0.933
274682WAUKEGAN ;7U
Adder
22.229
274861TOP CROP ;1U
Solar/Wind Harmer
7.491
274828WAUKEGAN ;BP
Adder
13.652
958381AF2-132 GEN
Solar/Wind Harmer
11.176
962781AG1-127 GEN
Solar/Wind Harmer
11.712
964861AG1-349 GEN
Solar/Wind Harmer
9.676
971917AH1-482 GEN
Solar/Wind Harmer
11.164
939401AE1-172 GEN
Solar/Wind Harmer
17.149
274872LEEDK;1U
Solar/Wind Harmer
10.097
276805AD2-038 GEN
Solar/Wind Harmer
6.3
965011AG1-365 GEN
Solar/Wind Harmer
12.264
24441205WTRV SLR C
Solar/Wind Harmer
0.165
276882AE2-255 GEN
Solar/Wind Harmer
4.133
971997AH1-543 GEN
Solar/Wind Harmer
19.284
957471AF2-041 GEN
Solar/Wind Harmer
36.555
959081AF2-199 GEN
Solar/Wind Harmer
12.185
971067AG2-660 GEN
Solar/Wind Harmer
2.834
940581AE2-045 GEN
Solar/Wind Harmer
12.407
971605AH1-302 GEN
Solar/Wind Harmer
10.609
274822ROCKFORD ;11
Adder
23.866
970819AG2-516 GEN
Solar/Wind Harmer
14.545
274761LEE CO EC;2U
Adder
11.202
274766LEE CO EC;7U
Adder
11.07
24728605AND G2
Adder
3.809
970091AG2-072 GEN
Adder
75.982
972203AH1-686 GEN
Adder
1.998
970569AG2-363 GEN
Solar/Wind Harmer
0.696
CPLELTFEXP_CPLE->PJM
CLTF
3.243
CBM West 2LTFEXP_CBM-W2->PJM
CBM
120.462
NYPJM->LTFIMP_NY
CLTF
3.757
LGEELTFEXP_LGEE->PJM
CLTF
5.535
WECLTFEXP_WEC->PJM
CLTF
4.636
AG2-052LTFEXP_AG2-052->PJM
LTF
0.286
AH1-155LTFEXP_AH1-155->PJM
LTF
0.429
LAGNLTFEXP_LAGN->PJM
CLTF
16.319
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.038
TVALTFEXP_TVA->PJM
CLTF
7.716
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.983
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.207
MECLTFEXP_MEC->PJM
CLTF
18.523
SIGELTFEXP_SIGE->PJM
CLTF
0.475

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AP_P1-3_MP-765-501T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:126.34 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5774.92
MW Contribution:
43.62
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
1.801
270071AF1-092 GEN
Solar/Wind Harmer
17.36
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971771AH1-392 GEN
Solar/Wind Harmer
8.928
274775LINCOLN ;6U
Adder
10.797
274776LINCOLN ;7U
Adder
10.797
274777LINCOLN ;8U
Adder
10.797
270526AF1-158 GEN
Solar/Wind Harmer
0.001
274827FISK ;RP
Adder
9.767
972037AH1-567 GEN1
Adder
0.23
960591AF2-350 GEN
Solar/Wind Harmer
8.782
972228AH1-698 GEN2
Adder
4.662
972227AH1-698 GEN1
Adder
3.283
274800UNIV PARK;3U
Adder
7.336
274801UNIV PARK;4U
Adder
7.336
274687WILL CNTY;4U
Adder
35.036
274687WILL CNTY;4U
Adder
35.036
274675JOLIET 29;7U
Adder
38.449
274675JOLIET 29;7U
Adder
37.076
274728ELWOOD EC;5P
Adder
20.57
274731ELWOOD EC;2P
Adder
20.57
274733ELWOOD EC;3P
Adder
20.57
274735ELWOOD EC;4P
Adder
20.57
970833AG2-524 GEN
Solar/Wind Harmer
9.602
970833AG2-524 GEN
Solar/Wind Harmer
6.401
970031AG2-029 GEN
Solar/Wind Harmer
4.721
24729505KEY G4
Adder
8.09
274744AC1-111 GEN8
Adder
6.969
274746AC1-111 G10
Adder
6.969
970073AG2-061 GEN
Solar/Wind Harmer
2.857
959331AF2-224 GEN
Solar/Wind Harmer
5.989
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
3.328
971411AH1-196 GEN
Solar/Wind Harmer
12.799
276861AD2-134 GEN
Solar/Wind Harmer
0.152
276863AD2-134 GEN
Solar/Wind Harmer
0.152
959141AF2-205 GEN
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
17.002
971611AH1-305 GEN
Solar/Wind Harmer
5.053
274823ROCKFORD ;21
Adder
23.693
274856ECOGROVE ;U1
Solar/Wind Harmer
0.197
926823AC1-168 GEN
Solar/Wind Harmer
1.434
970169AG2-114 GEN
Solar/Wind Harmer
8.435
971681AH1-341 GEN
Solar/Wind Harmer
13.557
972267AH1-718 GEN
Adder
4.986
276741O09 GEN1
Solar/Wind Harmer
0.295
24722005FLATG5
50/50
1.801
24721905FLATG4
50/50
32.904
962771AG1-126 GEN
Solar/Wind Harmer
80.774
970153AG2-106 GEN
Solar/Wind Harmer
51.58
971347AH1-153 GEN
Solar/Wind Harmer
4.684
270043AE2-236 GEN
Solar/Wind Harmer
5.865
274772LINCOLN ;3U
Adder
10.797
274724RIVER EC ;11
Adder
22.43
944531AF1-118 GEN
Solar/Wind Harmer
39.561
970707AG2-453 GEN
Solar/Wind Harmer
28.808
274752CRETE EC ;2U
Adder
10.415
274753CRETE EC ;3U
Adder
10.415
270505AE1-170 C O1
Solar/Wind Harmer
9.246
274814UNIV PK N;0U
Adder
6.372
274807UNIV PK N;3U
Adder
6.358
274811UNIV PK N;7U
Adder
6.317
972259AH1-714 GEN
Adder
24.043
274826FISK ;BP
Adder
13.782
274803UNIV PARK;6U
Adder
7.339
274887GEN-1.85
Solar/Wind Harmer
0.228
276843GEN-1.7
Solar/Wind Harmer
0.284
276806AD2-047 C O1
Solar/Wind Harmer
4.976
972038AH1-567 GEN2
Adder
0.459
945111AF1-176 GEN
Solar/Wind Harmer
7.113
270063AE2-323 C
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
37.076
274729ELWOOD EC;1P
Adder
20.57
274730ELWOOD EC;6P
Adder
20.57
274734ELWOOD EC;8P
Adder
20.57
274736ELWOOD EC;9P
Adder
20.57
943121AE2-341 GEN
Solar/Wind Harmer
14.603
943591AF1-030 GEN
Solar/Wind Harmer
9.711
274682WAUKEGAN ;7U
Adder
22.229
274862TOP CROP ;2U
Solar/Wind Harmer
1.165
964401AG1-302 GEN
Solar/Wind Harmer
0.001
965021AG1-366 GEN
Solar/Wind Harmer
2.852
276868AE1-113 GEN
Solar/Wind Harmer
1.71
274879MINONK ;1U
Solar/Wind Harmer
0.357
946671AF1-331 GEN
Solar/Wind Harmer
0.91
274855GSG-6 ;RU
Solar/Wind Harmer
0.311
274850MENDOTA H;RU
Solar/Wind Harmer
0.099
959091AF2-200 GEN
Solar/Wind Harmer
17.002
970571AG2-364 GEN
Solar/Wind Harmer
16.871
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
11.202
274767LEE CO EC;8U
Adder
11.07
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.277
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
8.302
965931AG1-462 GEN
Solar/Wind Harmer
20.885
971087AG2-675 GEN
Solar/Wind Harmer
4.368
965091AG1-374 GEN
Solar/Wind Harmer
24.551
959611AF2-252 GEN
Solar/Wind Harmer
2.728
274877BISHOP HL;1U
Solar/Wind Harmer
0.277
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
8.677
946321AF1-296 GEN
Solar/Wind Harmer
4.601
274854TWINGROVE;U2
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
10.858
945581AF1-223 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
3.469
276668AB2-070 GEN1
Solar/Wind Harmer
0.312
276848AB2-070 GEN3
Solar/Wind Harmer
0.31
276849AB2-070 GEN2
Solar/Wind Harmer
0.312
971549AH1-272 GEN
Solar/Wind Harmer
16.367
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
965041AG1-368 GEN
Solar/Wind Harmer
7.859
970289AG2-191 GEN
Solar/Wind Harmer
1.486
971609AH1-304 GEN
Solar/Wind Harmer
1.264
247521TR3_G114
Solar/Wind Harmer
0.275
965051AG1-369 GEN
Solar/Wind Harmer
3.795
944221AF1-090 GEN
Solar/Wind Harmer
4.432
964611AG1-324 GEN
Solar/Wind Harmer
2.855
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.891
247536S-71 GEN
Solar/Wind Harmer
0.278
270007AE1-245 C
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
4.682
270356AE2-297 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
9.586
270578AF1-285 GEN2
Solar/Wind Harmer
0.405
24386205FR-12G C
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
3.663
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.86
957381AF2-032 GEN
Solar/Wind Harmer
1.75
942481AE2-261 GEN
Solar/Wind Harmer
23.05
270004AE1-209 GEN
Solar/Wind Harmer
1.624
970193AG2-126 GEN
Solar/Wind Harmer
11.218
24695305TIMB G C
Solar/Wind Harmer
0.627
970825AG2-519 GEN
Solar/Wind Harmer
5.579
946031AF1-268 GEN
Solar/Wind Harmer
6.994
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.967
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.253
270491AE1-102 GEN2
Solar/Wind Harmer
0.915
24728705AND G3
Adder
7.966
24728505AND G1
Adder
3.809
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
270391AF1-285 GEN3
Solar/Wind Harmer
0.405
24721705FLATG2
50/50
26.753
270102X2-052 ST
50/50
2.06
270100X2-052 CT1
50/50
1.903
270101X2-052 CT2
50/50
1.903
970349AG2-230 GEN
Solar/Wind Harmer
14.053
965681AG1-436 GEN
Solar/Wind Harmer
11.209
965791AG1-447 GEN
Solar/Wind Harmer
8.22
274770LINCOLN ;1U
Adder
10.797
274771LINCOLN ;2U
Adder
10.797
274805UNIV PK N;1U
Adder
6.33
274808UNIV PK N;4U
Adder
6.289
274888KELLY CRK;1U
Solar/Wind Harmer
0.512
276776AD2-060 GEN
Solar/Wind Harmer
0.937
958011AF2-095 GEN
Solar/Wind Harmer
12.646
970941AG2-585 GEN
Solar/Wind Harmer
4.83
247620Y3-023
Adder
0.579
276897AD1-100 C
Solar/Wind Harmer
21.908
961051AF2-396 GEN
Solar/Wind Harmer
17.478
961051AF2-396 GEN
Solar/Wind Harmer
11.652
274674JOLIET 9 ;6U
Adder
19.278
276893AG1-478 C
Solar/Wind Harmer
0.582
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274696ROCKY RD ;4P
Adder
14.112
274695ROCKY RD ;2P
Adder
13.787
274693ROCKY RD ;1P
Adder
13.651
274697ROCKY RD ;3P
Adder
3.745
958481AF2-142 GEN
Solar/Wind Harmer
12.945
274683WAUKEGAN ;8U
Adder
26.045
274683WAUKEGAN ;8U
Adder
21.955
962691AG1-118 GEN
Solar/Wind Harmer
25.814
958491AF2-143 GEN
Solar/Wind Harmer
12.858
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
17.002
971343AH1-151 GEN
Solar/Wind Harmer
17.002
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
3.061
972236AH1-702 GEN2
Adder
2.662
938861AE1-114 GEN
Solar/Wind Harmer
4.771
274764LEE CO EC;5U
Adder
11.229
274765LEE CO EC;6U
Adder
11.229
274762LEE CO EC;3U
Adder
11.202
274763LEE CO EC;4U
Adder
11.097
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.557
960971AF2-388 GEN
Solar/Wind Harmer
4.897
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.346
276645AC1-214 GEN1
Solar/Wind Harmer
0.327
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
2.686
960611AF2-352 GEN
Solar/Wind Harmer
2.728
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.921
942221AE2-234 GEN
Solar/Wind Harmer
3.241
970241AG2-163 GEN
Solar/Wind Harmer
4.6
276615X2-022 GEN
Solar/Wind Harmer
0.081
276838X2-022 GEN2
Solar/Wind Harmer
0.442
970291AG2-192 GEN
Solar/Wind Harmer
1.017
970291AG2-192 GEN
Solar/Wind Harmer
0.469
270031AE2-169
Solar/Wind Harmer
4.257
270599AE1-208 GEN
Solar/Wind Harmer
7.096
971613AH1-306 GEN
Solar/Wind Harmer
3.702
276916AD2-100_GEN
Solar/Wind Harmer
16.116
276911AD2-131_GEN
Solar/Wind Harmer
1.062
270246TR4_N_V150
Solar/Wind Harmer
0.049
270247TR4_N_V136
Solar/Wind Harmer
0.049
944231AF1-091 GEN
Solar/Wind Harmer
17.5
945391AF1-204 GEN
Solar/Wind Harmer
7.946
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.549
270201AC2-176 GEN
Solar/Wind Harmer
0
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
971587AH1-292 GEN
Solar/Wind Harmer
5.222
247621Y3-024
Adder
0.245
926881AC1-175 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.284
270383AD1-128 GEN
Solar/Wind Harmer
0
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.232
970883AG2-550 GEN
Solar/Wind Harmer
6.689
970885AG2-551 GEN
Solar/Wind Harmer
2.23
270054AF2-122 C O1
Solar/Wind Helper
1.547
24721805FLATG3
50/50
1.801
24344105CKG2
50/50
10.297
962761AG1-125 GEN
Solar/Wind Harmer
80.774
970149AG2-104 GEN
Solar/Wind Harmer
43.619
970155AG2-107 GEN
Solar/Wind Harmer
51.58
274773LINCOLN ;4U
Adder
10.797
274774LINCOLN ;5U
Adder
10.797
274723RIVER EC ;12
Adder
22.692
24639705ELKHART HY
Adder
0.194
274751CRETE EC ;1U
Adder
10.415
274754CRETE EC ;4U
Adder
10.415
957891AF2-083 GEN
Solar/Wind Harmer
14.667
274812UNIV PK N;8U
Adder
6.317
274802UNIV PARK;5U
Adder
7.339
945111AF1-176 GEN
Solar/Wind Harmer
15.659
941551AE2-152 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
18.373
274676JOLIET 29;8U
Adder
38.449
274674JOLIET 9 ;6U
Adder
19.278
274732ELWOOD EC;7P
Adder
20.57
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
4.55
274745AC1-111 GEN9
Adder
6.969
270055AF2-134 C O1
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.402
274682WAUKEGAN ;7U
Adder
22.229
274861TOP CROP ;1U
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
13.652
958381AF2-132 GEN
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
8.177
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.164
939401AE1-172 GEN
Solar/Wind Harmer
6.422
274872LEEDK;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
965011AG1-365 GEN
Solar/Wind Harmer
8.556
276882AE2-255 GEN
Solar/Wind Harmer
0.998
971997AH1-543 GEN
Solar/Wind Harmer
4.485
957471AF2-041 GEN
Solar/Wind Harmer
25.504
959081AF2-199 GEN
Solar/Wind Harmer
8.501
971067AG2-660 GEN
Solar/Wind Harmer
2.834
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
10.609
274822ROCKFORD ;11
Adder
23.866
970819AG2-516 GEN
Solar/Wind Harmer
10.148
970569AG2-363 GEN
Solar/Wind Harmer
25.306
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
11.202
274766LEE CO EC;7U
Adder
11.07
965651AG1-433 GEN
Solar/Wind Harmer
2.449
276708O09 GEN2
Solar/Wind Harmer
0.295
276646AC1-214 GEN2
Solar/Wind Harmer
0.327
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
11.569
958861AF2-177 GEN
Solar/Wind Harmer
3.567
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
18.662
276621W2-048 GEN
Solar/Wind Harmer
0.393
270594AE1-207 GEN
Solar/Wind Harmer
8.639
270032AE2-172
Solar/Wind Harmer
5.142
965911AG1-460 GEN
Solar/Wind Harmer
1.542
270024AE2-089 GEN
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
8.459
270005AE1-210 C O1
Solar/Wind Harmer
1.624
970825AG2-519 GEN
Solar/Wind Harmer
2.629
965421AG1-410 GEN
Solar/Wind Harmer
21.55
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.196
246936BC-WTG1
Solar/Wind Harmer
0.284
270489AE1-102 GEN1
Solar/Wind Harmer
0.915
24728605AND G2
Adder
3.809
970091AG2-072 GEN
Adder
75.982
970773AG2-487 GEN
Solar/Wind Harmer
1.155
972203AH1-686 GEN
Adder
1.998
CPLELTFEXP_CPLE->PJM
CLTF
3.243
CBM West 2LTFEXP_CBM-W2->PJM
CBM
120.462
NYPJM->LTFIMP_NY
CLTF
3.757
LGEELTFEXP_LGEE->PJM
CLTF
5.535
WECLTFEXP_WEC->PJM
CLTF
4.636
AG2-052LTFEXP_AG2-052->PJM
LTF
0.286
AH1-155LTFEXP_AH1-155->PJM
LTF
0.429
LAGNLTFEXP_LAGN->PJM
CLTF
16.319
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.038
TVALTFEXP_TVA->PJM
CLTF
7.716
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.983
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.207
MECLTFEXP_MEC->PJM
CLTF
18.523
SIGELTFEXP_SIGE->PJM
CLTF
0.475

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AEP_P4_#8085_05MARYSV 345_H_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8085_05MARYSV 345_H_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.61 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5421.49
MW Contribution:
69.03
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721705FLATG2
50/50
21.838
270102X2-052 ST
50/50
1.83
270100X2-052 CT1
50/50
1.69
270101X2-052 CT2
50/50
1.69
970349AG2-230 GEN
Solar/Wind Harmer
18.249
965681AG1-436 GEN
Solar/Wind Harmer
14.245
965791AG1-447 GEN
Solar/Wind Harmer
7.288
274770LINCOLN ;1U
Adder
7.038
274771LINCOLN ;2U
Adder
7.038
274805UNIV PK N;1U
Adder
5.57
274808UNIV PK N;4U
Adder
5.534
274888KELLY CRK;1U
Solar/Wind Harmer
6.534
276776AD2-060 GEN
Solar/Wind Harmer
0.463
958011AF2-095 GEN
Solar/Wind Harmer
15.944
970941AG2-585 GEN
Solar/Wind Harmer
6.09
276897AD1-100 C
Solar/Wind Harmer
51.281
274674JOLIET 9 ;6U
Adder
16.926
276893AG1-478 C
Solar/Wind Harmer
0.481
961051AF2-396 GEN
Solar/Wind Harmer
17.393
24721605FLATG1
50/50
1.47
960681AF2-359 GEN
Solar/Wind Harmer
4.306
274775LINCOLN ;6U
Adder
7.038
274776LINCOLN ;7U
Adder
7.038
274777LINCOLN ;8U
Adder
7.038
971771AH1-392 GEN
Solar/Wind Harmer
10.162
270526AF1-158 GEN
Solar/Wind Harmer
5.119
270071AF1-092 GEN
Solar/Wind Harmer
16.74
274827FISK ;RP
Adder
8.593
972228AH1-698 GEN2
Adder
4.102
972227AH1-698 GEN1
Adder
2.888
960591AF2-350 GEN
Solar/Wind Harmer
11.072
972037AH1-567 GEN1
Adder
0.203
274800UNIV PARK;3U
Adder
6.452
274801UNIV PARK;4U
Adder
6.452
274687WILL CNTY;4U
Adder
30.779
274687WILL CNTY;4U
Adder
30.779
274675JOLIET 29;7U
Adder
33.773
274675JOLIET 29;7U
Adder
32.567
274728ELWOOD EC;5P
Adder
18.053
274731ELWOOD EC;2P
Adder
18.053
274733ELWOOD EC;3P
Adder
18.053
274735ELWOOD EC;4P
Adder
18.053
970833AG2-524 GEN
Solar/Wind Harmer
9.588
970833AG2-524 GEN
Solar/Wind Harmer
4.46
276893AG1-478 C
Solar/Wind Harmer
0.604
274744AC1-111 GEN8
Adder
6.112
274746AC1-111 G10
Adder
6.112
944161AF1-084 GEN
Solar/Wind Harmer
2.398
970073AG2-061 GEN
Solar/Wind Harmer
2.486
971675AH1-338 GEN
Solar/Wind Harmer
19.15
971411AH1-196 GEN
Solar/Wind Harmer
15.957
276861AD2-134 GEN
Solar/Wind Harmer
1.899
276863AD2-134 GEN
Solar/Wind Harmer
1.899
971171AH1-044 GEN
Solar/Wind Harmer
21.162
274863CRW1-WTG
Solar/Wind Harmer
5.893
274864CRW2-WTG
Solar/Wind Harmer
5.893
274823ROCKFORD ;21
Adder
20.558
276889AE2-281 GEN
Solar/Wind Harmer
2.023
958391AF2-133 GEN
Solar/Wind Harmer
9.55
24729505KEY G4
Adder
6.806
274856ECOGROVE ;U1
Solar/Wind Harmer
3.537
276611AD2-172 GEN
Solar/Wind Harmer
2.683
276612AE2-035 GEN
Solar/Wind Harmer
2.683
970031AG2-029 GEN
Solar/Wind Harmer
26.201
959141AF2-205 GEN
Solar/Wind Harmer
6.328
926823AC1-168 GEN
Solar/Wind Harmer
4.489
972267AH1-718 GEN
Adder
4.296
241955AC1-078 GEN
Solar/Wind Helper
2.364
241973AD2-163_GEN1
Solar/Wind Helper
1.917
241974AD2-163_GEN2
Solar/Wind Helper
1.917
945631AF1-228 GEN
Solar/Wind Helper
1.875
961051AF2-396 GEN
Solar/Wind Harmer
8.09
247620Y3-023
Adder
0.5
274695ROCKY RD ;2P
Adder
12.056
274693ROCKY RD ;1P
Adder
11.937
274697ROCKY RD ;3P
Adder
3.275
274696ROCKY RD ;4P
Adder
12.34
274683WAUKEGAN ;8U
Adder
22.755
274683WAUKEGAN ;8U
Adder
19.182
958481AF2-142 GEN
Solar/Wind Harmer
16.196
270535AF1-215 GEN1
Solar/Wind Harmer
4.888
270536AF1-215 GEN2
Solar/Wind Harmer
4.888
962691AG1-118 GEN
Solar/Wind Harmer
32.301
960751AF2-366 GEN
Solar/Wind Harmer
3.083
958491AF2-143 GEN
Solar/Wind Harmer
16.036
276901AD2-066 C O1
Solar/Wind Harmer
3.746
971341AH1-150 GEN
Solar/Wind Harmer
21.162
971343AH1-151 GEN
Solar/Wind Harmer
21.162
276872AE1-163_GEN1
Solar/Wind Harmer
7.079
276876AE1-163_GEN2
Solar/Wind Harmer
7.079
972235AH1-702 GEN1
Adder
2.654
972236AH1-702 GEN2
Adder
2.308
274764LEE CO EC;5U
Adder
9.7
274765LEE CO EC;6U
Adder
9.7
274762LEE CO EC;3U
Adder
9.677
274763LEE CO EC;4U
Adder
9.586
270054AF2-122 C O1
Solar/Wind Helper
2.149
270349AD2-093_GEN
Solar/Wind Helper
2.07
270471AD2-092_GEN
Solar/Wind Helper
2.07
946101AF1-275 GEN
Solar/Wind Helper
0.83
253383AE2-342_GEN
Solar/Wind Helper
0.865
241960AC2-195 GEN
Solar/Wind Helper
1.459
24722005FLATG5
50/50
1.47
24721905FLATG4
50/50
26.859
962771AG1-126 GEN
Solar/Wind Harmer
111.791
970153AG2-106 GEN
Solar/Wind Harmer
48.746
971347AH1-153 GEN
Solar/Wind Harmer
6.083
274772LINCOLN ;3U
Adder
7.038
270043AE2-236 GEN
Solar/Wind Harmer
6.211
24441505OLIV SLR
Solar/Wind Harmer
0.151
247643Z2-116 C
Solar/Wind Harmer
0.078
274724RIVER EC ;11
Adder
19.776
970707AG2-453 GEN
Solar/Wind Harmer
31.235
276164X3-005 C
Solar/Wind Harmer
0.783
972231SS25-0005
Solar/Wind Harmer
10.56
972181SS23-001
Solar/Wind Harmer
6.6
274752CRETE EC ;2U
Adder
5.439
274753CRETE EC ;3U
Adder
5.439
972259AH1-714 GEN
Adder
21.177
274814UNIV PK N;0U
Adder
5.607
274807UNIV PK N;3U
Adder
5.595
274811UNIV PK N;7U
Adder
5.558
270505AE1-170 C O1
Solar/Wind Harmer
16.629
274826FISK ;BP
Adder
12.125
274887GEN-1.85
Solar/Wind Harmer
5.899
276772AC2-154 GEN
Solar/Wind Harmer
3.09
276843GEN-1.7
Solar/Wind Harmer
0.635
276806AD2-047 C O1
Solar/Wind Harmer
11.845
274803UNIV PARK;6U
Adder
6.455
972038AH1-567 GEN2
Adder
0.404
939351AE1-166 GEN
Solar/Wind Harmer
6.547
274676JOLIET 29;8U
Adder
32.566
945111AF1-176 GEN
Solar/Wind Harmer
6.221
274729ELWOOD EC;1P
Adder
18.053
274730ELWOOD EC;6P
Adder
18.053
274734ELWOOD EC;8P
Adder
18.053
274736ELWOOD EC;9P
Adder
18.053
943121AE2-341 GEN
Solar/Wind Harmer
16.435
943591AF1-030 GEN
Solar/Wind Harmer
10.957
274682WAUKEGAN ;7U
Adder
19.427
274862TOP CROP ;2U
Solar/Wind Harmer
5.458
944531AF1-118 GEN
Solar/Wind Harmer
37.571
270063AE2-323 C
Solar/Wind Harmer
2.345
276868AE1-113 GEN
Solar/Wind Harmer
10.778
274879MINONK ;1U
Solar/Wind Harmer
7.185
276799AD1-013 GEN
Solar/Wind Harmer
2.351
946671AF1-331 GEN
Solar/Wind Harmer
0.446
274855GSG-6 ;RU
Solar/Wind Harmer
3.927
274850MENDOTA H;RU
Solar/Wind Harmer
2.73
276602WESTBROOK C
Solar/Wind Harmer
2.261
964401AG1-302 GEN
Solar/Wind Harmer
9.627
959091AF2-200 GEN
Solar/Wind Harmer
21.162
274760LEE CO EC;1U
Adder
9.677
274767LEE CO EC;8U
Adder
9.563
270284AF1-227 GEN1
Solar/Wind Helper
2.64
270287AF1-227 GEN3
Solar/Wind Helper
0.968
960801AF2-371 GEN
Solar/Wind Helper
0.993
964871AG1-351 GEN
Solar/Wind Helper
0.685
970571AG2-364 GEN
Solar/Wind Harmer
17.627
24344105CKG2
50/50
9.476
24721805FLATG3
50/50
1.47
962761AG1-125 GEN
Solar/Wind Harmer
111.791
970149AG2-104 GEN
Solar/Wind Harmer
69.031
970155AG2-107 GEN
Solar/Wind Harmer
48.746
972207SS24-0001
Solar/Wind Harmer
25.024
274773LINCOLN ;4U
Adder
7.038
274774LINCOLN ;5U
Adder
7.038
270216AD2-079_GEN
Solar/Wind Harmer
0.676
274723RIVER EC ;12
Adder
20.004
274751CRETE EC ;1U
Adder
5.439
274754CRETE EC ;4U
Adder
5.439
274812UNIV PK N;8U
Adder
5.558
274802UNIV PARK;5U
Adder
6.455
957891AF2-083 GEN
Solar/Wind Harmer
16.598
941551AE2-152 GEN
Solar/Wind Harmer
5.007
24639705ELKHART HY
Adder
0.169
274676JOLIET 29;8U
Adder
33.772
945111AF1-176 GEN
Solar/Wind Harmer
19.629
274674JOLIET 9 ;6U
Adder
16.926
274732ELWOOD EC;7P
Adder
18.053
274871GR RIDGE ;2U
Solar/Wind Harmer
8.442
274847GR RIDGE ;BU
Solar/Wind Harmer
5.551
274745AC1-111 GEN9
Adder
6.112
970373AG2-245 GEN
Solar/Wind Harmer
22.961
270449AD2-020 GEN
Solar/Wind Harmer
3.064
943021AE2-325 GEN
Solar/Wind Harmer
3.981
274682WAUKEGAN ;7U
Adder
19.427
274828WAUKEGAN ;BP
Adder
11.928
276694AA1-018 GEN2
Solar/Wind Harmer
6.813
276691AA1-018 GEN1
Solar/Wind Harmer
0.814
274861TOP CROP ;1U
Solar/Wind Harmer
6.537
270055AF2-134 C O1
Solar/Wind Harmer
3.258
962781AG1-127 GEN
Solar/Wind Harmer
10.218
274872LEEDK;1U
Solar/Wind Harmer
8.804
939401AE1-172 GEN
Solar/Wind Harmer
14.911
276805AD2-038 GEN
Solar/Wind Harmer
5.482
24441205WTRV SLR C
Solar/Wind Harmer
0.144
276882AE2-255 GEN
Solar/Wind Harmer
3.593
971997AH1-543 GEN
Solar/Wind Harmer
16.759
958381AF2-132 GEN
Solar/Wind Harmer
9.627
964861AG1-349 GEN
Solar/Wind Harmer
8.33
971917AH1-482 GEN
Solar/Wind Harmer
9.611
957471AF2-041 GEN
Solar/Wind Harmer
31.743
959081AF2-199 GEN
Solar/Wind Harmer
10.581
971067AG2-660 GEN
Solar/Wind Harmer
2.461
274822ROCKFORD ;11
Adder
20.709
970819AG2-516 GEN
Solar/Wind Harmer
12.603
274761LEE CO EC;2U
Adder
9.677
274766LEE CO EC;7U
Adder
9.563
270520AE2-214 GEN
Solar/Wind Helper
3.319
270286AF1-227 GEN2
Solar/Wind Helper
0.968
970569AG2-363 GEN
Solar/Wind Harmer
26.441
CPLELTFEXP_CPLE->PJM
CLTF
1.972
CBM West 2LTFEXP_CBM-W2->PJM
CBM
89.423
NYPJM->LTFIMP_NY
CLTF
2.495
LGEELTFEXP_LGEE->PJM
CLTF
3.316
WECLTFEXP_WEC->PJM
CLTF
4.018
AG2-052LTFEXP_AG2-052->PJM
LTF
0.247
AH1-155LTFEXP_AH1-155->PJM
LTF
0.37
LAGNLTFEXP_LAGN->PJM
CLTF
11.793
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.114
TVALTFEXP_TVA->PJM
CLTF
5.294
CBM West 1LTFEXP_CBM-W1->PJM
CBM
117.272
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.566
MECLTFEXP_MEC->PJM
CLTF
15.378
SIGELTFEXP_SIGE->PJM
CLTF
0.329

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AEP_P2-2_#8072_05MARYSV 765_2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#8072_05MARYSV 765_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:117.48 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5369.79
MW Contribution:
69.35
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
1.482
960681AF2-359 GEN
Solar/Wind Harmer
4.234
274775LINCOLN ;6U
Adder
6.931
274776LINCOLN ;7U
Adder
6.931
274777LINCOLN ;8U
Adder
6.931
270526AF1-158 GEN
Solar/Wind Harmer
5.027
971771AH1-392 GEN
Solar/Wind Harmer
9.974
270071AF1-092 GEN
Solar/Wind Harmer
16.362
274827FISK ;RP
Adder
8.458
972228AH1-698 GEN2
Adder
4.038
972227AH1-698 GEN1
Adder
2.843
960591AF2-350 GEN
Solar/Wind Harmer
10.898
972037AH1-567 GEN1
Adder
0.199
274800UNIV PARK;3U
Adder
6.351
274801UNIV PARK;4U
Adder
6.351
274687WILL CNTY;4U
Adder
30.296
274687WILL CNTY;4U
Adder
30.296
274675JOLIET 29;7U
Adder
33.244
274675JOLIET 29;7U
Adder
32.057
970833AG2-524 GEN
Solar/Wind Harmer
9.439
970833AG2-524 GEN
Solar/Wind Harmer
4.39
274728ELWOOD EC;5P
Adder
17.77
274731ELWOOD EC;2P
Adder
17.77
274733ELWOOD EC;3P
Adder
17.77
274735ELWOOD EC;4P
Adder
17.77
276893AG1-478 C
Solar/Wind Harmer
0.594
274744AC1-111 GEN8
Adder
6.017
274746AC1-111 G10
Adder
6.017
944161AF1-084 GEN
Solar/Wind Harmer
2.35
970073AG2-061 GEN
Solar/Wind Harmer
2.447
971675AH1-338 GEN
Solar/Wind Harmer
18.851
971411AH1-196 GEN
Solar/Wind Harmer
15.708
276861AD2-134 GEN
Solar/Wind Harmer
1.869
276863AD2-134 GEN
Solar/Wind Harmer
1.869
971171AH1-044 GEN
Solar/Wind Harmer
20.831
274863CRW1-WTG
Solar/Wind Harmer
5.799
274864CRW2-WTG
Solar/Wind Harmer
5.799
274823ROCKFORD ;21
Adder
20.237
276889AE2-281 GEN
Solar/Wind Harmer
1.991
958391AF2-133 GEN
Solar/Wind Harmer
9.384
274856ECOGROVE ;U1
Solar/Wind Harmer
3.481
276611AD2-172 GEN
Solar/Wind Harmer
2.641
276612AE2-035 GEN
Solar/Wind Harmer
2.641
959141AF2-205 GEN
Solar/Wind Harmer
6.218
926823AC1-168 GEN
Solar/Wind Harmer
4.418
971681AH1-341 GEN
Solar/Wind Harmer
15.409
24729505KEY G4
Adder
6.649
972267AH1-718 GEN
Adder
4.228
241955AC1-078 GEN
Solar/Wind Helper
2.298
241973AD2-163_GEN1
Solar/Wind Helper
1.862
241974AD2-163_GEN2
Solar/Wind Helper
1.862
945631AF1-228 GEN
Solar/Wind Helper
1.837
24721805FLATG3
50/50
1.482
24344105CKG2
50/50
9.343
962761AG1-125 GEN
Solar/Wind Harmer
112.309
970149AG2-104 GEN
Solar/Wind Harmer
69.351
970155AG2-107 GEN
Solar/Wind Harmer
48.972
972207SS24-0001
Solar/Wind Harmer
24.644
274773LINCOLN ;4U
Adder
6.931
274774LINCOLN ;5U
Adder
6.931
274723RIVER EC ;12
Adder
19.685
270216AD2-079_GEN
Solar/Wind Harmer
0.663
274751CRETE EC ;1U
Adder
5.351
274754CRETE EC ;4U
Adder
5.351
274812UNIV PK N;8U
Adder
5.469
274802UNIV PARK;5U
Adder
6.353
941551AE2-152 GEN
Solar/Wind Harmer
4.928
957891AF2-083 GEN
Solar/Wind Harmer
16.274
274676JOLIET 29;8U
Adder
33.244
274674JOLIET 9 ;6U
Adder
16.661
274732ELWOOD EC;7P
Adder
17.77
274871GR RIDGE ;2U
Solar/Wind Harmer
8.31
274847GR RIDGE ;BU
Solar/Wind Harmer
5.464
945111AF1-176 GEN
Solar/Wind Harmer
19.236
24639705ELKHART HY
Adder
0.165
274745AC1-111 GEN9
Adder
6.017
970373AG2-245 GEN
Solar/Wind Harmer
22.569
270449AD2-020 GEN
Solar/Wind Harmer
3.003
943021AE2-325 GEN
Solar/Wind Harmer
3.902
274682WAUKEGAN ;7U
Adder
19.124
274828WAUKEGAN ;BP
Adder
11.742
276694AA1-018 GEN2
Solar/Wind Harmer
6.705
276691AA1-018 GEN1
Solar/Wind Harmer
0.801
274861TOP CROP ;1U
Solar/Wind Harmer
6.434
270055AF2-134 C O1
Solar/Wind Harmer
3.202
962781AG1-127 GEN
Solar/Wind Harmer
10.059
274872LEEDK;1U
Solar/Wind Harmer
8.667
939401AE1-172 GEN
Solar/Wind Harmer
14.675
24721705FLATG2
50/50
22.01
270102X2-052 ST
50/50
1.799
270100X2-052 CT1
50/50
1.662
270101X2-052 CT2
50/50
1.662
970349AG2-230 GEN
Solar/Wind Harmer
17.966
965681AG1-436 GEN
Solar/Wind Harmer
14.006
965791AG1-447 GEN
Solar/Wind Harmer
7.166
274770LINCOLN ;1U
Adder
6.931
274771LINCOLN ;2U
Adder
6.931
274805UNIV PK N;1U
Adder
5.481
274808UNIV PK N;4U
Adder
5.445
274888KELLY CRK;1U
Solar/Wind Harmer
6.431
276776AD2-060 GEN
Solar/Wind Harmer
0.456
958011AF2-095 GEN
Solar/Wind Harmer
15.693
970941AG2-585 GEN
Solar/Wind Harmer
5.994
276897AD1-100 C
Solar/Wind Harmer
50.481
274674JOLIET 9 ;6U
Adder
16.661
276893AG1-478 C
Solar/Wind Harmer
0.474
961051AF2-396 GEN
Solar/Wind Harmer
17.047
961051AF2-396 GEN
Solar/Wind Harmer
7.929
274695ROCKY RD ;2P
Adder
11.868
274693ROCKY RD ;1P
Adder
11.751
274697ROCKY RD ;3P
Adder
3.224
274696ROCKY RD ;4P
Adder
12.148
274683WAUKEGAN ;8U
Adder
22.4
274683WAUKEGAN ;8U
Adder
18.882
958481AF2-142 GEN
Solar/Wind Harmer
15.94
247620Y3-023
Adder
0.489
962691AG1-118 GEN
Solar/Wind Harmer
31.798
270535AF1-215 GEN1
Solar/Wind Harmer
4.804
270536AF1-215 GEN2
Solar/Wind Harmer
4.804
960751AF2-366 GEN
Solar/Wind Harmer
3.035
958491AF2-143 GEN
Solar/Wind Harmer
15.782
276901AD2-066 C O1
Solar/Wind Harmer
3.686
971341AH1-150 GEN
Solar/Wind Harmer
20.831
971343AH1-151 GEN
Solar/Wind Harmer
20.831
276872AE1-163_GEN1
Solar/Wind Harmer
6.967
276876AE1-163_GEN2
Solar/Wind Harmer
6.967
972235AH1-702 GEN1
Adder
2.613
972236AH1-702 GEN2
Adder
2.272
274764LEE CO EC;5U
Adder
9.547
24722005FLATG5
50/50
1.482
24721905FLATG4
50/50
27.071
962771AG1-126 GEN
Solar/Wind Harmer
112.309
970153AG2-106 GEN
Solar/Wind Harmer
48.972
971347AH1-153 GEN
Solar/Wind Harmer
5.989
274772LINCOLN ;3U
Adder
6.931
24441505OLIV SLR
Solar/Wind Harmer
0.148
270043AE2-236 GEN
Solar/Wind Harmer
6.061
247643Z2-116 C
Solar/Wind Harmer
0.076
274724RIVER EC ;11
Adder
19.46
970707AG2-453 GEN
Solar/Wind Harmer
30.756
276164X3-005 C
Solar/Wind Harmer
0.77
972231SS25-0005
Solar/Wind Harmer
10.389
972181SS23-001
Solar/Wind Harmer
6.493
274752CRETE EC ;2U
Adder
5.351
274753CRETE EC ;3U
Adder
5.351
972259AH1-714 GEN
Adder
20.849
274814UNIV PK N;0U
Adder
5.517
274807UNIV PK N;3U
Adder
5.505
274811UNIV PK N;7U
Adder
5.469
274826FISK ;BP
Adder
11.934
274887GEN-1.85
Solar/Wind Harmer
5.806
276772AC2-154 GEN
Solar/Wind Harmer
3.041
276843GEN-1.7
Solar/Wind Harmer
0.625
276806AD2-047 C O1
Solar/Wind Harmer
11.659
274803UNIV PARK;6U
Adder
6.353
972038AH1-567 GEN2
Adder
0.398
270505AE1-170 C O1
Solar/Wind Harmer
16.306
939351AE1-166 GEN
Solar/Wind Harmer
6.445
274676JOLIET 29;8U
Adder
32.056
274729ELWOOD EC;1P
Adder
17.77
274730ELWOOD EC;6P
Adder
17.77
274734ELWOOD EC;8P
Adder
17.77
274736ELWOOD EC;9P
Adder
17.77
943121AE2-341 GEN
Solar/Wind Harmer
16.181
943591AF1-030 GEN
Solar/Wind Harmer
10.787
945111AF1-176 GEN
Solar/Wind Harmer
6.096
274682WAUKEGAN ;7U
Adder
19.124
274862TOP CROP ;2U
Solar/Wind Harmer
5.372
944531AF1-118 GEN
Solar/Wind Harmer
36.716
276868AE1-113 GEN
Solar/Wind Harmer
10.607
274879MINONK ;1U
Solar/Wind Harmer
7.072
276799AD1-013 GEN
Solar/Wind Harmer
2.315
946671AF1-331 GEN
Solar/Wind Harmer
0.439
274855GSG-6 ;RU
Solar/Wind Harmer
3.866
274850MENDOTA H;RU
Solar/Wind Harmer
2.688
276602WESTBROOK C
Solar/Wind Harmer
2.225
964401AG1-302 GEN
Solar/Wind Harmer
9.461
959091AF2-200 GEN
Solar/Wind Harmer
20.831
270063AE2-323 C
Solar/Wind Harmer
2.285
970571AG2-364 GEN
Solar/Wind Harmer
20.55
274760LEE CO EC;1U
Adder
9.525
274767LEE CO EC;8U
Adder
9.413
270284AF1-227 GEN1
Solar/Wind Helper
2.373
270287AF1-227 GEN3
Solar/Wind Helper
0.87
960801AF2-371 GEN
Solar/Wind Helper
0.964
964871AG1-351 GEN
Solar/Wind Helper
0.665
274765LEE CO EC;6U
Adder
9.547
274762LEE CO EC;3U
Adder
9.525
274763LEE CO EC;4U
Adder
9.435
270054AF2-122 C O1
Solar/Wind Helper
2.097
946101AF1-275 GEN
Solar/Wind Helper
0.802
270349AD2-093_GEN
Solar/Wind Helper
1.818
270471AD2-092_GEN
Solar/Wind Helper
1.818
253383AE2-342_GEN
Solar/Wind Helper
0.854
241960AC2-195 GEN
Solar/Wind Helper
1.419
938861AE1-114 GEN
Solar/Wind Harmer
2.265
276805AD2-038 GEN
Solar/Wind Harmer
5.395
276882AE2-255 GEN
Solar/Wind Harmer
3.536
971997AH1-543 GEN
Solar/Wind Harmer
16.495
24441205WTRV SLR C
Solar/Wind Harmer
0.141
958381AF2-132 GEN
Solar/Wind Harmer
9.461
957471AF2-041 GEN
Solar/Wind Harmer
31.247
959081AF2-199 GEN
Solar/Wind Harmer
10.416
971067AG2-660 GEN
Solar/Wind Harmer
2.422
964861AG1-349 GEN
Solar/Wind Harmer
8.186
971917AH1-482 GEN
Solar/Wind Harmer
9.444
274822ROCKFORD ;11
Adder
20.385
970819AG2-516 GEN
Solar/Wind Harmer
12.405
970569AG2-363 GEN
Solar/Wind Harmer
30.826
274761LEE CO EC;2U
Adder
9.525
274766LEE CO EC;7U
Adder
9.413
270520AE2-214 GEN
Solar/Wind Helper
3.207
270286AF1-227 GEN2
Solar/Wind Helper
0.87
CPLELTFEXP_CPLE->PJM
CLTF
1.997
CBM West 2LTFEXP_CBM-W2->PJM
CBM
87.92
NYPJM->LTFIMP_NY
CLTF
2.454
LGEELTFEXP_LGEE->PJM
CLTF
3.221
WECLTFEXP_WEC->PJM
CLTF
3.955
AG2-052LTFEXP_AG2-052->PJM
LTF
0.242
AH1-155LTFEXP_AH1-155->PJM
LTF
0.363
LAGNLTFEXP_LAGN->PJM
CLTF
11.631
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.139
TVALTFEXP_TVA->PJM
CLTF
5.225
CBM West 1LTFEXP_CBM-W1->PJM
CBM
114.418
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.259
MECLTFEXP_MEC->PJM
CLTF
15.133
SIGELTFEXP_SIGE->PJM
CLTF
0.321

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AEP_P1-3_#8072_05MARYSV 765_2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-3_#8072_05MARYSV 765_2_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.24 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5084.88
MW Contribution:
51.15
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721705FLATG2
50/50
22.01
270102X2-052 ST
50/50
1.799
270100X2-052 CT1
50/50
1.662
270101X2-052 CT2
50/50
1.662
970349AG2-230 GEN
Solar/Wind Harmer
12.534
965681AG1-436 GEN
Solar/Wind Harmer
9.772
965791AG1-447 GEN
Solar/Wind Harmer
7.166
274770LINCOLN ;1U
Adder
9.435
274771LINCOLN ;2U
Adder
9.435
274805UNIV PK N;1U
Adder
5.481
274808UNIV PK N;4U
Adder
5.445
274888KELLY CRK;1U
Solar/Wind Harmer
0.443
276776AD2-060 GEN
Solar/Wind Harmer
0.811
958011AF2-095 GEN
Solar/Wind Harmer
10.949
970941AG2-585 GEN
Solar/Wind Harmer
4.182
276897AD1-100 C
Solar/Wind Harmer
18.954
274674JOLIET 9 ;6U
Adder
16.661
276893AG1-478 C
Solar/Wind Harmer
0.502
961051AF2-396 GEN
Solar/Wind Harmer
14.985
961051AF2-396 GEN
Solar/Wind Harmer
9.99
274695ROCKY RD ;2P
Adder
11.868
274693ROCKY RD ;1P
Adder
11.751
274697ROCKY RD ;3P
Adder
3.224
274696ROCKY RD ;4P
Adder
12.148
274683WAUKEGAN ;8U
Adder
22.4
274683WAUKEGAN ;8U
Adder
18.882
958481AF2-142 GEN
Solar/Wind Harmer
11.121
247620Y3-023
Adder
0.489
962691AG1-118 GEN
Solar/Wind Harmer
22.185
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
11.011
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
14.533
971343AH1-151 GEN
Solar/Wind Harmer
14.533
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
2.613
972236AH1-702 GEN2
Adder
2.272
938861AE1-114 GEN
Solar/Wind Harmer
4.06
274764LEE CO EC;5U
Adder
9.547
274765LEE CO EC;6U
Adder
9.547
274762LEE CO EC;3U
Adder
9.525
274763LEE CO EC;4U
Adder
9.435
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.14
276645AC1-214 GEN1
Solar/Wind Harmer
0.276
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
2.249
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.272
944541AF1-119 GEN
Solar/Wind Harmer
0.446
960971AF2-388 GEN
Solar/Wind Harmer
3.922
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.752
276615X2-022 GEN
Solar/Wind Harmer
0.066
276838X2-022 GEN2
Solar/Wind Harmer
0.36
970241AG2-163 GEN
Solar/Wind Harmer
3.681
276916AD2-100_GEN
Solar/Wind Harmer
12.928
276911AD2-131_GEN
Solar/Wind Harmer
0.852
942221AE2-234 GEN
Solar/Wind Harmer
2.468
970291AG2-192 GEN
Solar/Wind Harmer
0.785
970291AG2-192 GEN
Solar/Wind Harmer
0.362
270054AF2-122 C O1
Solar/Wind Helper
2.097
946101AF1-275 GEN
Solar/Wind Helper
0.802
270349AD2-093_GEN
Solar/Wind Helper
1.818
270471AD2-092_GEN
Solar/Wind Helper
1.818
253383AE2-342_GEN
Solar/Wind Helper
0.854
241960AC2-195 GEN
Solar/Wind Helper
1.419
24721605FLATG1
50/50
1.482
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
274775LINCOLN ;6U
Adder
9.435
274776LINCOLN ;7U
Adder
9.435
274777LINCOLN ;8U
Adder
9.435
270526AF1-158 GEN
Solar/Wind Harmer
0
971771AH1-392 GEN
Solar/Wind Harmer
7.732
270071AF1-092 GEN
Solar/Wind Harmer
14.586
274827FISK ;RP
Adder
8.458
972228AH1-698 GEN2
Adder
4.038
972227AH1-698 GEN1
Adder
2.843
960591AF2-350 GEN
Solar/Wind Harmer
7.603
972037AH1-567 GEN1
Adder
0.199
274800UNIV PARK;3U
Adder
6.351
274801UNIV PARK;4U
Adder
6.351
274687WILL CNTY;4U
Adder
30.296
274687WILL CNTY;4U
Adder
30.296
274675JOLIET 29;7U
Adder
33.244
274675JOLIET 29;7U
Adder
32.057
970833AG2-524 GEN
Solar/Wind Harmer
8.297
970833AG2-524 GEN
Solar/Wind Harmer
5.531
274728ELWOOD EC;5P
Adder
17.77
274731ELWOOD EC;2P
Adder
17.77
274733ELWOOD EC;3P
Adder
17.77
274735ELWOOD EC;4P
Adder
17.77
274744AC1-111 GEN8
Adder
6.017
274746AC1-111 G10
Adder
6.017
970073AG2-061 GEN
Solar/Wind Harmer
2.447
971675AH1-338 GEN
Solar/Wind Harmer
2.85
971411AH1-196 GEN
Solar/Wind Harmer
10.959
276861AD2-134 GEN
Solar/Wind Harmer
0.13
276863AD2-134 GEN
Solar/Wind Harmer
0.13
971171AH1-044 GEN
Solar/Wind Harmer
14.533
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
274823ROCKFORD ;21
Adder
20.237
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274856ECOGROVE ;U1
Solar/Wind Harmer
0.168
959141AF2-205 GEN
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
1.219
971681AH1-341 GEN
Solar/Wind Harmer
11.539
24729505KEY G4
Adder
6.649
970169AG2-114 GEN
Solar/Wind Harmer
7.15
971611AH1-305 GEN
Solar/Wind Harmer
4.239
970031AG2-029 GEN
Solar/Wind Harmer
3.854
972267AH1-718 GEN
Adder
4.228
276741O09 GEN1
Solar/Wind Harmer
0.25
274877BISHOP HL;1U
Solar/Wind Harmer
0.234
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.266
946321AF1-296 GEN
Solar/Wind Harmer
3.872
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
971549AH1-272 GEN
Solar/Wind Harmer
13.514
276668AB2-070 GEN1
Solar/Wind Harmer
0.255
276848AB2-070 GEN3
Solar/Wind Harmer
0.254
276849AB2-070 GEN2
Solar/Wind Harmer
0.255
963841AG1-237 GEN
Solar/Wind Harmer
2.803
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
959331AF2-224 GEN
Solar/Wind Harmer
4.399
945581AF1-223 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
1.148
241955AC1-078 GEN
Solar/Wind Helper
2.298
241973AD2-163_GEN1
Solar/Wind Helper
1.862
241974AD2-163_GEN2
Solar/Wind Helper
1.862
945631AF1-228 GEN
Solar/Wind Helper
1.837
24721805FLATG3
50/50
1.482
24344105CKG2
50/50
9.343
962761AG1-125 GEN
Solar/Wind Harmer
94.712
970149AG2-104 GEN
Solar/Wind Harmer
51.146
970155AG2-107 GEN
Solar/Wind Harmer
60.48
274773LINCOLN ;4U
Adder
9.435
274774LINCOLN ;5U
Adder
9.435
274723RIVER EC ;12
Adder
19.685
274751CRETE EC ;1U
Adder
9.02
274754CRETE EC ;4U
Adder
9.02
274812UNIV PK N;8U
Adder
5.469
274802UNIV PARK;5U
Adder
6.353
941551AE2-152 GEN
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
12.616
274676JOLIET 29;8U
Adder
33.244
274674JOLIET 9 ;6U
Adder
16.661
274732ELWOOD EC;7P
Adder
17.77
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
13.42
24639705ELKHART HY
Adder
0.165
274745AC1-111 GEN9
Adder
6.017
970373AG2-245 GEN
Solar/Wind Harmer
15.746
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.902
274682WAUKEGAN ;7U
Adder
19.124
274828WAUKEGAN ;BP
Adder
11.742
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.205
274861TOP CROP ;1U
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
7.023
274872LEEDK;1U
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
5.495
276805AD2-038 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.854
971997AH1-543 GEN
Solar/Wind Harmer
3.836
958381AF2-132 GEN
Solar/Wind Harmer
0.001
957471AF2-041 GEN
Solar/Wind Harmer
21.8
959081AF2-199 GEN
Solar/Wind Harmer
7.267
971067AG2-660 GEN
Solar/Wind Harmer
2.422
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.444
274822ROCKFORD ;11
Adder
20.385
970819AG2-516 GEN
Solar/Wind Harmer
8.655
970569AG2-363 GEN
Solar/Wind Harmer
21.506
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
9.525
274766LEE CO EC;7U
Adder
9.413
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.899
276708O09 GEN2
Solar/Wind Harmer
0.25
276646AC1-214 GEN2
Solar/Wind Harmer
0.276
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.688
965651AG1-433 GEN
Solar/Wind Harmer
1.961
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
2.83
276621W2-048 GEN
Solar/Wind Harmer
0.32
963741AG1-226 GEN
Solar/Wind Harmer
14.933
965011AG1-365 GEN
Solar/Wind Harmer
6.284
945371AF1-202 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
1.24
270520AE2-214 GEN
Solar/Wind Helper
3.207
270286AF1-227 GEN2
Solar/Wind Helper
0.87
24722005FLATG5
50/50
1.482
24721905FLATG4
50/50
27.071
962771AG1-126 GEN
Solar/Wind Harmer
94.712
970153AG2-106 GEN
Solar/Wind Harmer
60.48
971347AH1-153 GEN
Solar/Wind Harmer
4.178
274772LINCOLN ;3U
Adder
9.435
270043AE2-236 GEN
Solar/Wind Harmer
4.934
274724RIVER EC ;11
Adder
19.46
970707AG2-453 GEN
Solar/Wind Harmer
25.034
274752CRETE EC ;2U
Adder
9.02
274753CRETE EC ;3U
Adder
9.02
972259AH1-714 GEN
Adder
20.849
274814UNIV PK N;0U
Adder
5.517
274807UNIV PK N;3U
Adder
5.505
274811UNIV PK N;7U
Adder
5.469
274826FISK ;BP
Adder
11.934
274887GEN-1.85
Solar/Wind Harmer
0.198
276843GEN-1.7
Solar/Wind Harmer
0.246
276806AD2-047 C O1
Solar/Wind Harmer
4.309
274803UNIV PARK;6U
Adder
6.353
972038AH1-567 GEN2
Adder
0.398
270505AE1-170 C O1
Solar/Wind Harmer
7.964
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
32.056
274729ELWOOD EC;1P
Adder
17.77
274730ELWOOD EC;6P
Adder
17.77
274734ELWOOD EC;8P
Adder
17.77
274736ELWOOD EC;9P
Adder
17.77
943121AE2-341 GEN
Solar/Wind Harmer
12.618
943591AF1-030 GEN
Solar/Wind Harmer
8.391
945111AF1-176 GEN
Solar/Wind Harmer
6.096
274682WAUKEGAN ;7U
Adder
19.124
274862TOP CROP ;2U
Solar/Wind Harmer
1
944531AF1-118 GEN
Solar/Wind Harmer
32.801
276868AE1-113 GEN
Solar/Wind Harmer
1.463
274879MINONK ;1U
Solar/Wind Harmer
0.305
946671AF1-331 GEN
Solar/Wind Harmer
0.78
274855GSG-6 ;RU
Solar/Wind Harmer
0.267
274850MENDOTA H;RU
Solar/Wind Harmer
0.085
964401AG1-302 GEN
Solar/Wind Harmer
0.001
959091AF2-200 GEN
Solar/Wind Harmer
14.533
270063AE2-323 C
Solar/Wind Harmer
0
970571AG2-364 GEN
Solar/Wind Harmer
14.338
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
9.525
274767LEE CO EC;8U
Adder
9.413
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.234
965931AG1-462 GEN
Solar/Wind Harmer
17.553
971087AG2-675 GEN
Solar/Wind Harmer
3.671
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.861
965091AG1-374 GEN
Solar/Wind Harmer
20.448
959611AF2-252 GEN
Solar/Wind Harmer
2.272
24386205FR-12G C
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
2.994
965021AG1-366 GEN
Solar/Wind Harmer
2.095
957381AF2-032 GEN
Solar/Wind Harmer
1.409
942481AE2-261 GEN
Solar/Wind Harmer
18.543
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.665
270284AF1-227 GEN1
Solar/Wind Helper
2.373
270287AF1-227 GEN3
Solar/Wind Helper
0.87
960801AF2-371 GEN
Solar/Wind Helper
0.964
964871AG1-351 GEN
Solar/Wind Helper
0.665
CPLELTFEXP_CPLE->PJM
CLTF
1.997
CBM West 2LTFEXP_CBM-W2->PJM
CBM
87.92
NYPJM->LTFIMP_NY
CLTF
2.454
LGEELTFEXP_LGEE->PJM
CLTF
3.221
WECLTFEXP_WEC->PJM
CLTF
3.955
AG2-052LTFEXP_AG2-052->PJM
LTF
0.242
AH1-155LTFEXP_AH1-155->PJM
LTF
0.363
LAGNLTFEXP_LAGN->PJM
CLTF
11.631
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.139
TVALTFEXP_TVA->PJM
CLTF
5.225
CBM West 1LTFEXP_CBM-W1->PJM
CBM
114.418
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.259
MECLTFEXP_MEC->PJM
CLTF
15.133
SIGELTFEXP_SIGE->PJM
CLTF
0.321

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.76 %
Rating:4047.0 MVA
Rating Type:A
MVA to Mitigate:4482.29
MW Contribution:
40.3
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270102X2-052 ST
50/50
1.749
270100X2-052 CT1
50/50
1.616
270101X2-052 CT2
50/50
1.616
24643105BUCHANAN
50/50
0.014
247620Y3-023
50/50
0.526
274770LINCOLN ;1U
50/50
9.616
274771LINCOLN ;2U
50/50
9.616
970349AG2-230 GEN
Solar/Wind Harmer
12.041
965681AG1-436 GEN
Solar/Wind Harmer
9.504
965791AG1-447 GEN
Solar/Wind Harmer
6.97
961051AF2-396 GEN
Solar/Wind Harmer
14.959
961051AF2-396 GEN
Solar/Wind Harmer
9.973
274805UNIV PK N;1U
Adder
5.303
274808UNIV PK N;4U
Adder
5.268
274888KELLY CRK;1U
Solar/Wind Harmer
0.428
276776AD2-060 GEN
Solar/Wind Harmer
0.783
958011AF2-095 GEN
Solar/Wind Harmer
10.572
970941AG2-585 GEN
Solar/Wind Harmer
4.038
276897AD1-100 C
Solar/Wind Harmer
18.287
274674JOLIET 9 ;6U
Adder
16.082
276893AG1-478 C
Solar/Wind Harmer
0.485
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274695ROCKY RD ;2P
Adder
11.454
274693ROCKY RD ;1P
Adder
11.341
274697ROCKY RD ;3P
Adder
3.111
274696ROCKY RD ;4P
Adder
11.724
958481AF2-142 GEN
Solar/Wind Harmer
10.754
274683WAUKEGAN ;8U
Adder
21.627
274683WAUKEGAN ;8U
Adder
18.23
962691AG1-118 GEN
Solar/Wind Harmer
21.414
958491AF2-143 GEN
Solar/Wind Harmer
10.655
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
14.045
971343AH1-151 GEN
Solar/Wind Harmer
14.045
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
2.526
972236AH1-702 GEN2
Adder
2.196
938861AE1-114 GEN
Solar/Wind Harmer
3.928
944541AF1-119 GEN
Solar/Wind Harmer
0.462
960971AF2-388 GEN
Solar/Wind Harmer
4.056
274764LEE CO EC;5U
Adder
9.237
274765LEE CO EC;6U
Adder
9.237
274762LEE CO EC;3U
Adder
9.215
274763LEE CO EC;4U
Adder
9.128
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.104
276645AC1-214 GEN1
Solar/Wind Harmer
0.268
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
2.191
942221AE2-234 GEN
Solar/Wind Harmer
2.684
960611AF2-352 GEN
Solar/Wind Harmer
2.217
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.745
944231AF1-091 GEN
Solar/Wind Harmer
15.08
270246TR4_N_V150
Solar/Wind Harmer
0.042
270247TR4_N_V136
Solar/Wind Harmer
0.042
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
970241AG2-163 GEN
Solar/Wind Harmer
3.669
970291AG2-192 GEN
Solar/Wind Harmer
0.817
970291AG2-192 GEN
Solar/Wind Harmer
0.377
276615X2-022 GEN
Solar/Wind Harmer
0.065
276838X2-022 GEN2
Solar/Wind Harmer
0.353
270031AE2-169
Solar/Wind Harmer
3.44
270599AE1-208 GEN
Solar/Wind Harmer
5.734
971613AH1-306 GEN
Solar/Wind Harmer
2.966
276916AD2-100_GEN
Solar/Wind Harmer
12.749
276911AD2-131_GEN
Solar/Wind Harmer
0.84
246937BC-WTG2
Solar/Wind Harmer
0.244
270054AF2-122 C O1
Solar/Wind Helper
1.656
270142AC1-141 CT1_
50/50
2.617
24642205MAYFLWER
50/50
0.04
274772LINCOLN ;3U
50/50
9.616
944961AF1-161 GEN
50/50
3.109
962601AG1-109 GEN
50/50
3.109
962771AG1-126 GEN
Solar/Wind Harmer
74.627
970153AG2-106 GEN
Solar/Wind Harmer
47.655
971347AH1-153 GEN
Solar/Wind Harmer
4.014
270043AE2-236 GEN
Solar/Wind Harmer
5.048
270505AE1-170 C O1
Solar/Wind Harmer
7.914
270144AC1-141 ST1_
50/50
2.311
24641605TWIN BRNCH
50/50
0.019
24344005CKG1
50/50
7.028
24653605MOTTVILLE
50/50
0.004
274775LINCOLN ;6U
50/50
9.616
274776LINCOLN ;7U
50/50
9.616
274777LINCOLN ;8U
50/50
9.616
270071AF1-092 GEN
Solar/Wind Harmer
14.768
971771AH1-392 GEN
Solar/Wind Harmer
7.622
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270526AF1-158 GEN
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
4.047
959331AF2-224 GEN
Solar/Wind Harmer
5.169
274827FISK ;RP
Adder
8.169
972037AH1-567 GEN1
Adder
0.193
960591AF2-350 GEN
Solar/Wind Harmer
7.341
274800UNIV PARK;3U
Adder
6.134
274801UNIV PARK;4U
Adder
6.134
972228AH1-698 GEN2
Adder
3.896
972227AH1-698 GEN1
Adder
2.744
24729505KEY G4
Adder
6.793
274687WILL CNTY;4U
Adder
29.249
274687WILL CNTY;4U
Adder
29.249
274675JOLIET 29;7U
Adder
32.088
274675JOLIET 29;7U
Adder
30.942
274728ELWOOD EC;5P
Adder
17.157
274731ELWOOD EC;2P
Adder
17.157
274733ELWOOD EC;3P
Adder
17.157
274735ELWOOD EC;4P
Adder
17.157
970833AG2-524 GEN
Solar/Wind Harmer
8.005
970833AG2-524 GEN
Solar/Wind Harmer
5.336
274744AC1-111 GEN8
Adder
5.803
274746AC1-111 G10
Adder
5.803
970073AG2-061 GEN
Solar/Wind Harmer
2.368
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
2.753
971411AH1-196 GEN
Solar/Wind Harmer
10.588
276861AD2-134 GEN
Solar/Wind Harmer
0.126
276863AD2-134 GEN
Solar/Wind Harmer
0.126
959141AF2-205 GEN
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
14.045
274823ROCKFORD ;21
Adder
19.56
971611AH1-305 GEN
Solar/Wind Harmer
4.163
274856ECOGROVE ;U1
Solar/Wind Harmer
0.163
926823AC1-168 GEN
Solar/Wind Harmer
1.181
970169AG2-114 GEN
Solar/Wind Harmer
6.939
971681AH1-341 GEN
Solar/Wind Harmer
11.162
972267AH1-718 GEN
Adder
4.093
276741O09 GEN1
Solar/Wind Harmer
0.242
971549AH1-272 GEN
Solar/Wind Harmer
14.066
274877BISHOP HL;1U
Solar/Wind Harmer
0.227
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
9.126
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.079
965041AG1-368 GEN
Solar/Wind Harmer
6.739
946321AF1-296 GEN
Solar/Wind Harmer
3.754
274854TWINGROVE;U2
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
247521TR3_G114
Solar/Wind Harmer
0.235
965051AG1-369 GEN
Solar/Wind Harmer
3.245
963841AG1-237 GEN
Solar/Wind Harmer
2.784
276668AB2-070 GEN1
Solar/Wind Harmer
0.25
276848AB2-070 GEN3
Solar/Wind Harmer
0.249
276849AB2-070 GEN2
Solar/Wind Harmer
0.25
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
1.194
971609AH1-304 GEN
Solar/Wind Harmer
1.022
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.766
24344105CKG2
50/50
8.859
270143AC1-141 CT2_
50/50
2.617
24639705ELKHART HY
50/50
0.176
970521AG2-332 GEN
50/50
12.55
274773LINCOLN ;4U
50/50
9.616
274774LINCOLN ;5U
50/50
9.616
962761AG1-125 GEN
Solar/Wind Harmer
74.627
970149AG2-104 GEN
Solar/Wind Harmer
40.3
970155AG2-107 GEN
Solar/Wind Harmer
47.655
957891AF2-083 GEN
Solar/Wind Harmer
12.55
945111AF1-176 GEN
Solar/Wind Harmer
13.401
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.895
274723RIVER EC ;12
Adder
19.037
274751CRETE EC ;1U
Adder
8.738
274754CRETE EC ;4U
Adder
8.738
965011AG1-365 GEN
Solar/Wind Harmer
7.385
274812UNIV PK N;8U
Adder
5.291
274802UNIV PARK;5U
Adder
6.138
970373AG2-245 GEN
Solar/Wind Harmer
15.385
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
32.088
274674JOLIET 9 ;6U
Adder
16.082
274732ELWOOD EC;7P
Adder
17.157
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
5.803
270055AF2-134 C O1
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.165
274682WAUKEGAN ;7U
Adder
18.463
274861TOP CROP ;1U
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
11.336
958381AF2-132 GEN
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
6.78
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.257
274872LEEDK;1U
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
5.318
276805AD2-038 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.826
971997AH1-543 GEN
Solar/Wind Harmer
3.71
957471AF2-041 GEN
Solar/Wind Harmer
21.068
959081AF2-199 GEN
Solar/Wind Harmer
7.023
971067AG2-660 GEN
Solar/Wind Harmer
2.341
274822ROCKFORD ;11
Adder
19.703
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.741
970819AG2-516 GEN
Solar/Wind Harmer
8.368
970569AG2-363 GEN
Solar/Wind Harmer
20.843
965651AG1-433 GEN
Solar/Wind Harmer
2.028
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
9.215
274766LEE CO EC;7U
Adder
9.107
276708O09 GEN2
Solar/Wind Harmer
0.242
276646AC1-214 GEN2
Solar/Wind Harmer
0.268
958861AF2-177 GEN
Solar/Wind Harmer
2.941
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.439
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
14.886
276621W2-048 GEN
Solar/Wind Harmer
0.314
270024AE2-089 GEN
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
6.922
270032AE2-172
Solar/Wind Harmer
4.12
965421AG1-410 GEN
Solar/Wind Harmer
18.52
965911AG1-460 GEN
Solar/Wind Harmer
1.222
246936BC-WTG1
Solar/Wind Harmer
0.244
270489AE1-102 GEN1
Solar/Wind Harmer
0.786
276903AD2-071 C
Solar/Wind Harmer
6.725
270063AE2-323 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
6.088
944531AF1-118 GEN
Solar/Wind Harmer
33.371
274724RIVER EC ;11
Adder
18.817
274752CRETE EC ;2U
Adder
8.738
274753CRETE EC ;3U
Adder
8.738
965021AG1-366 GEN
Solar/Wind Harmer
2.462
970707AG2-453 GEN
Solar/Wind Harmer
24.09
274814UNIV PK N;0U
Adder
5.338
274807UNIV PK N;3U
Adder
5.326
274811UNIV PK N;7U
Adder
5.291
972259AH1-714 GEN
Adder
20.093
274826FISK ;BP
Adder
11.527
274803UNIV PARK;6U
Adder
6.138
274887GEN-1.85
Solar/Wind Harmer
0.191
276843GEN-1.7
Solar/Wind Harmer
0.237
276806AD2-047 C O1
Solar/Wind Harmer
4.16
972038AH1-567 GEN2
Adder
0.384
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
30.942
274729ELWOOD EC;1P
Adder
17.157
274730ELWOOD EC;6P
Adder
17.157
274734ELWOOD EC;8P
Adder
17.157
274736ELWOOD EC;9P
Adder
17.157
943121AE2-341 GEN
Solar/Wind Harmer
12.163
943591AF1-030 GEN
Solar/Wind Harmer
8.088
274682WAUKEGAN ;7U
Adder
18.463
274862TOP CROP ;2U
Solar/Wind Harmer
0.968
964401AG1-302 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.416
274879MINONK ;1U
Solar/Wind Harmer
0.295
946671AF1-331 GEN
Solar/Wind Harmer
0.753
274855GSG-6 ;RU
Solar/Wind Harmer
0.257
274850MENDOTA H;RU
Solar/Wind Harmer
0.082
959091AF2-200 GEN
Solar/Wind Harmer
14.045
970571AG2-364 GEN
Solar/Wind Harmer
13.895
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
9.215
274767LEE CO EC;8U
Adder
9.107
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.227
24690905MDL-1G C
Solar/Wind Harmer
0
24721905FLATG4
Adder
19.661
970781AG2-491 GEN
Solar/Wind Harmer
6.766
965931AG1-462 GEN
Solar/Wind Harmer
17.022
971087AG2-675 GEN
Solar/Wind Harmer
3.56
965091AG1-374 GEN
Solar/Wind Harmer
19.952
959611AF2-252 GEN
Solar/Wind Harmer
2.217
24386205FR-12G C
Solar/Wind Harmer
0
247642Z2-115 C
Solar/Wind Harmer
0.003
971993AH1-541 GEN
Solar/Wind Harmer
2.938
24695305TIMB G C
Solar/Wind Harmer
0.537
970289AG2-191 GEN
Solar/Wind Harmer
0.691
957381AF2-032 GEN
Solar/Wind Harmer
1.388
942481AE2-261 GEN
Solar/Wind Harmer
18.271
246938BC-WTG3
Solar/Wind Harmer
0.218
270491AE1-102 GEN2
Solar/Wind Harmer
0.786
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
CPLELTFEXP_CPLE->PJM
CLTF
1.444
CBM West 2LTFEXP_CBM-W2->PJM
CBM
87.349
NYPJM->LTFIMP_NY
CLTF
2.583
LGEELTFEXP_LGEE->PJM
CLTF
3.675
WECLTFEXP_WEC->PJM
CLTF
3.823
AG2-052LTFEXP_AG2-052->PJM
LTF
0.237
AH1-155LTFEXP_AH1-155->PJM
LTF
0.356
LAGNLTFEXP_LAGN->PJM
CLTF
11.281
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.712
TVALTFEXP_TVA->PJM
CLTF
5.082
CBM West 1LTFEXP_CBM-W1->PJM
CBM
120.334
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.267
MECLTFEXP_MEC->PJM
CLTF
14.733
SIGELTFEXP_SIGE->PJM
CLTF
0.34

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AEP_P7-1_#10944___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10944___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:109.68 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5013.66
MW Contribution:
54.78
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270144AC1-141 ST1_
50/50
2.339
24641605TWIN BRNCH
50/50
0.019
24344005CKG1
50/50
7.115
274775LINCOLN ;6U
50/50
7.217
274776LINCOLN ;7U
50/50
7.217
274777LINCOLN ;8U
50/50
7.217
24653605MOTTVILLE
50/50
0.004
270071AF1-092 GEN
Solar/Wind Harmer
16.823
270102X2-052 ST
50/50
1.778
270100X2-052 CT1
50/50
1.643
270101X2-052 CT2
50/50
1.643
274770LINCOLN ;1U
50/50
7.217
274771LINCOLN ;2U
50/50
7.217
24643105BUCHANAN
50/50
0.014
247620Y3-023
50/50
0.532
970349AG2-230 GEN
Solar/Wind Harmer
17.514
965681AG1-436 GEN
Solar/Wind Harmer
13.857
965791AG1-447 GEN
Solar/Wind Harmer
7.089
961051AF2-396 GEN
Solar/Wind Harmer
17.218
961051AF2-396 GEN
Solar/Wind Harmer
8.008
274805UNIV PK N;1U
Adder
5.418
274808UNIV PK N;4U
Adder
5.383
274888KELLY CRK;1U
Solar/Wind Harmer
6.35
958011AF2-095 GEN
Solar/Wind Harmer
15.495
970941AG2-585 GEN
Solar/Wind Harmer
5.918
276776AD2-060 GEN
Solar/Wind Harmer
0.45
276897AD1-100 C
Solar/Wind Harmer
49.833
274674JOLIET 9 ;6U
Adder
16.457
276893AG1-478 C
Solar/Wind Harmer
0.468
270535AF1-215 GEN1
Solar/Wind Harmer
4.807
270536AF1-215 GEN2
Solar/Wind Harmer
4.807
274696ROCKY RD ;4P
Adder
12.013
274695ROCKY RD ;2P
Adder
11.736
274693ROCKY RD ;1P
Adder
11.621
274697ROCKY RD ;3P
Adder
3.188
958481AF2-142 GEN
Solar/Wind Harmer
15.793
274683WAUKEGAN ;8U
Adder
22.163
274683WAUKEGAN ;8U
Adder
18.683
962691AG1-118 GEN
Solar/Wind Harmer
31.466
960751AF2-366 GEN
Solar/Wind Harmer
3.004
958491AF2-143 GEN
Solar/Wind Harmer
15.659
276901AD2-066 C O1
Solar/Wind Harmer
3.658
971341AH1-150 GEN
Solar/Wind Harmer
20.665
971343AH1-151 GEN
Solar/Wind Harmer
20.665
276872AE1-163_GEN1
Solar/Wind Harmer
6.927
276876AE1-163_GEN2
Solar/Wind Harmer
6.927
972235AH1-702 GEN1
Adder
2.593
972236AH1-702 GEN2
Adder
2.255
274764LEE CO EC;5U
Adder
9.494
274765LEE CO EC;6U
Adder
9.494
274762LEE CO EC;3U
Adder
9.471
274763LEE CO EC;4U
Adder
9.382
270054AF2-122 C O1
Solar/Wind Helper
1.794
270142AC1-141 CT1_
50/50
2.649
274772LINCOLN ;3U
50/50
7.217
24642205MAYFLWER
50/50
0.04
962771AG1-126 GEN
Solar/Wind Harmer
88.715
970153AG2-106 GEN
Solar/Wind Harmer
38.684
971347AH1-153 GEN
Solar/Wind Harmer
5.838
270043AE2-236 GEN
Solar/Wind Harmer
6.27
247643Z2-116 C
Solar/Wind Harmer
0.077
24441505OLIV SLR
Solar/Wind Harmer
0.148
270505AE1-170 C O1
Solar/Wind Harmer
16.403
270063AE2-323 C
Solar/Wind Harmer
2.395
945111AF1-176 GEN
Solar/Wind Harmer
6.161
944531AF1-118 GEN
Solar/Wind Harmer
38.053
274724RIVER EC ;11
Adder
19.218
972231SS25-0005
Solar/Wind Harmer
10.278
972181SS23-001
Solar/Wind Harmer
6.423
274752CRETE EC ;2U
Adder
5.293
274753CRETE EC ;3U
Adder
5.293
276164X3-005 C
Solar/Wind Harmer
0.76
970707AG2-453 GEN
Solar/Wind Harmer
30.269
274814UNIV PK N;0U
Adder
5.454
274807UNIV PK N;3U
Adder
5.442
274811UNIV PK N;7U
Adder
5.406
972259AH1-714 GEN
Adder
20.552
274826FISK ;BP
Adder
11.785
274803UNIV PARK;6U
Adder
6.275
274887GEN-1.85
Solar/Wind Harmer
5.733
276843GEN-1.7
Solar/Wind Harmer
0.617
276772AC2-154 GEN
Solar/Wind Harmer
3.003
276806AD2-047 C O1
Solar/Wind Harmer
11.511
972038AH1-567 GEN2
Adder
0.393
939351AE1-166 GEN
Solar/Wind Harmer
6.362
274676JOLIET 29;8U
Adder
31.659
274729ELWOOD EC;1P
Adder
17.558
274730ELWOOD EC;6P
Adder
17.558
274734ELWOOD EC;8P
Adder
17.558
274736ELWOOD EC;9P
Adder
17.558
943121AE2-341 GEN
Solar/Wind Harmer
15.97
943591AF1-030 GEN
Solar/Wind Harmer
10.647
965021AG1-366 GEN
Solar/Wind Harmer
2.473
24721905FLATG4
Adder
21.345
274682WAUKEGAN ;7U
Adder
18.92
274862TOP CROP ;2U
Solar/Wind Harmer
5.323
964401AG1-302 GEN
Solar/Wind Harmer
9.495
276868AE1-113 GEN
Solar/Wind Harmer
10.527
274879MINONK ;1U
Solar/Wind Harmer
7.019
276799AD1-013 GEN
Solar/Wind Harmer
2.294
946671AF1-331 GEN
Solar/Wind Harmer
0.435
274855GSG-6 ;RU
Solar/Wind Harmer
3.832
274850MENDOTA H;RU
Solar/Wind Harmer
2.664
276602WESTBROOK C
Solar/Wind Harmer
2.206
959091AF2-200 GEN
Solar/Wind Harmer
20.665
274760LEE CO EC;1U
Adder
9.471
274767LEE CO EC;8U
Adder
9.36
970571AG2-364 GEN
Solar/Wind Harmer
0.393
960681AF2-359 GEN
Solar/Wind Harmer
4.189
971771AH1-392 GEN
Solar/Wind Harmer
9.969
270526AF1-158 GEN
Solar/Wind Harmer
5.008
970031AG2-029 GEN
Solar/Wind Harmer
27.046
274827FISK ;RP
Adder
8.352
972037AH1-567 GEN1
Adder
0.197
960591AF2-350 GEN
Solar/Wind Harmer
10.76
972228AH1-698 GEN2
Adder
3.985
972227AH1-698 GEN1
Adder
2.806
274800UNIV PARK;3U
Adder
6.272
274801UNIV PARK;4U
Adder
6.272
944161AF1-084 GEN
Solar/Wind Harmer
2.376
274687WILL CNTY;4U
Adder
29.923
274687WILL CNTY;4U
Adder
29.923
274675JOLIET 29;7U
Adder
32.832
274675JOLIET 29;7U
Adder
31.659
274728ELWOOD EC;5P
Adder
17.558
274731ELWOOD EC;2P
Adder
17.558
274733ELWOOD EC;3P
Adder
17.558
274735ELWOOD EC;4P
Adder
17.558
24729505KEY G4
Adder
6.928
276893AG1-478 C
Solar/Wind Harmer
0.587
970833AG2-524 GEN
Solar/Wind Harmer
9.321
970833AG2-524 GEN
Solar/Wind Harmer
4.335
959331AF2-224 GEN
Solar/Wind Harmer
10.633
274744AC1-111 GEN8
Adder
5.942
274746AC1-111 G10
Adder
5.942
970073AG2-061 GEN
Solar/Wind Harmer
2.428
958391AF2-133 GEN
Solar/Wind Harmer
9.434
971675AH1-338 GEN
Solar/Wind Harmer
18.686
971411AH1-196 GEN
Solar/Wind Harmer
15.57
276861AD2-134 GEN
Solar/Wind Harmer
1.853
276863AD2-134 GEN
Solar/Wind Harmer
1.853
959141AF2-205 GEN
Solar/Wind Harmer
6.259
274863CRW1-WTG
Solar/Wind Harmer
5.77
274864CRW2-WTG
Solar/Wind Harmer
5.77
971171AH1-044 GEN
Solar/Wind Harmer
20.665
276889AE2-281 GEN
Solar/Wind Harmer
1.979
274823ROCKFORD ;21
Adder
20.081
274856ECOGROVE ;U1
Solar/Wind Harmer
3.458
276611AD2-172 GEN
Solar/Wind Harmer
2.623
276612AE2-035 GEN
Solar/Wind Harmer
2.623
926823AC1-168 GEN
Solar/Wind Harmer
4.398
972267AH1-718 GEN
Adder
4.209
24344105CKG2
50/50
8.986
270143AC1-141 CT2_
50/50
2.649
274773LINCOLN ;4U
50/50
7.217
274774LINCOLN ;5U
50/50
7.217
24639705ELKHART HY
50/50
0.178
970521AG2-332 GEN
50/50
12.701
962761AG1-125 GEN
Solar/Wind Harmer
88.715
970149AG2-104 GEN
Solar/Wind Harmer
54.782
970155AG2-107 GEN
Solar/Wind Harmer
38.684
270216AD2-079_GEN
Solar/Wind Harmer
0.668
972207SS24-0001
Solar/Wind Harmer
24.182
957891AF2-083 GEN
Solar/Wind Harmer
16.388
945111AF1-176 GEN
Solar/Wind Harmer
19.439
274723RIVER EC ;12
Adder
19.442
274751CRETE EC ;1U
Adder
5.293
274754CRETE EC ;4U
Adder
5.293
270449AD2-020 GEN
Solar/Wind Harmer
3.032
943021AE2-325 GEN
Solar/Wind Harmer
3.94
274812UNIV PK N;8U
Adder
5.406
274802UNIV PARK;5U
Adder
6.275
941551AE2-152 GEN
Solar/Wind Harmer
4.865
970373AG2-245 GEN
Solar/Wind Harmer
22.518
274676JOLIET 29;8U
Adder
32.831
274674JOLIET 9 ;6U
Adder
16.457
274732ELWOOD EC;7P
Adder
17.558
274871GR RIDGE ;2U
Solar/Wind Harmer
8.206
274847GR RIDGE ;BU
Solar/Wind Harmer
5.396
965011AG1-365 GEN
Solar/Wind Harmer
10.633
274745AC1-111 GEN9
Adder
5.942
24441205WTRV SLR C
Solar/Wind Harmer
0.143
270055AF2-134 C O1
Solar/Wind Harmer
3.204
276694AA1-018 GEN2
Solar/Wind Harmer
6.643
276691AA1-018 GEN1
Solar/Wind Harmer
0.794
274682WAUKEGAN ;7U
Adder
18.92
274861TOP CROP ;1U
Solar/Wind Harmer
6.376
274828WAUKEGAN ;BP
Adder
11.618
962781AG1-127 GEN
Solar/Wind Harmer
9.957
958381AF2-132 GEN
Solar/Wind Harmer
9.495
964861AG1-349 GEN
Solar/Wind Harmer
8.218
971917AH1-482 GEN
Solar/Wind Harmer
9.482
274872LEEDK;1U
Solar/Wind Harmer
8.581
939401AE1-172 GEN
Solar/Wind Harmer
14.566
276805AD2-038 GEN
Solar/Wind Harmer
5.353
276882AE2-255 GEN
Solar/Wind Harmer
3.509
971997AH1-543 GEN
Solar/Wind Harmer
16.368
957471AF2-041 GEN
Solar/Wind Harmer
30.997
959081AF2-199 GEN
Solar/Wind Harmer
10.332
971067AG2-660 GEN
Solar/Wind Harmer
2.403
274822ROCKFORD ;11
Adder
20.228
940581AE2-045 GEN
Solar/Wind Harmer
10.493
971605AH1-302 GEN
Solar/Wind Harmer
8.972
970819AG2-516 GEN
Solar/Wind Harmer
12.318
274761LEE CO EC;2U
Adder
9.471
274766LEE CO EC;7U
Adder
9.36
970569AG2-363 GEN
Solar/Wind Harmer
0.589
CPLELTFEXP_CPLE->PJM
CLTF
1.92
CBM West 2LTFEXP_CBM-W2->PJM
CBM
93.511
NYPJM->LTFIMP_NY
CLTF
2.816
LGEELTFEXP_LGEE->PJM
CLTF
4.052
WECLTFEXP_WEC->PJM
CLTF
3.927
AG2-052LTFEXP_AG2-052->PJM
LTF
0.243
AH1-155LTFEXP_AH1-155->PJM
LTF
0.364
LAGNLTFEXP_LAGN->PJM
CLTF
12.285
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.262
TVALTFEXP_TVA->PJM
CLTF
5.629
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.974
CBM South 1LTFEXP_CBM-S1->PJM
CBM
21.323
MECLTFEXP_MEC->PJM
CLTF
15.302
SIGELTFEXP_SIGE->PJM
CLTF
0.365

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-027A_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-027A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:108.18 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:4944.72
MW Contribution:
55.1
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270102X2-052 ST
50/50
1.845
270100X2-052 CT1
50/50
1.705
270101X2-052 CT2
50/50
1.705
24643105BUCHANAN
50/50
0.015
247620Y3-023
50/50
0.558
274770LINCOLN ;1U
50/50
7.418
274771LINCOLN ;2U
50/50
7.418
970349AG2-230 GEN
Solar/Wind Harmer
18.149
965681AG1-436 GEN
Solar/Wind Harmer
14.368
965791AG1-447 GEN
Solar/Wind Harmer
7.351
961051AF2-396 GEN
Solar/Wind Harmer
18.101
961051AF2-396 GEN
Solar/Wind Harmer
8.419
274805UNIV PK N;1U
Adder
5.578
274808UNIV PK N;4U
Adder
5.541
274888KELLY CRK;1U
Solar/Wind Harmer
6.527
276776AD2-060 GEN
Solar/Wind Harmer
0.463
958011AF2-095 GEN
Solar/Wind Harmer
15.928
970941AG2-585 GEN
Solar/Wind Harmer
6.084
276897AD1-100 C
Solar/Wind Harmer
51.184
274674JOLIET 9 ;6U
Adder
16.903
276893AG1-478 C
Solar/Wind Harmer
0.481
270535AF1-215 GEN1
Solar/Wind Harmer
4.956
270536AF1-215 GEN2
Solar/Wind Harmer
4.956
274695ROCKY RD ;2P
Adder
12.037
274693ROCKY RD ;1P
Adder
11.918
274697ROCKY RD ;3P
Adder
3.27
274696ROCKY RD ;4P
Adder
12.321
958481AF2-142 GEN
Solar/Wind Harmer
16.205
274683WAUKEGAN ;8U
Adder
22.729
274683WAUKEGAN ;8U
Adder
19.16
962691AG1-118 GEN
Solar/Wind Harmer
32.255
960751AF2-366 GEN
Solar/Wind Harmer
3.079
958491AF2-143 GEN
Solar/Wind Harmer
16.055
276901AD2-066 C O1
Solar/Wind Harmer
3.749
971341AH1-150 GEN
Solar/Wind Harmer
21.158
971343AH1-151 GEN
Solar/Wind Harmer
21.158
276872AE1-163_GEN1
Solar/Wind Harmer
7.094
276876AE1-163_GEN2
Solar/Wind Harmer
7.094
972235AH1-702 GEN1
Adder
2.655
972236AH1-702 GEN2
Adder
2.308
274764LEE CO EC;5U
Adder
9.709
274765LEE CO EC;6U
Adder
9.709
274762LEE CO EC;3U
Adder
9.686
274763LEE CO EC;4U
Adder
9.595
270054AF2-122 C O1
Solar/Wind Helper
1.626
270142AC1-141 CT1_
50/50
2.775
24642205MAYFLWER
50/50
0.042
944961AF1-161 GEN
50/50
3.309
962601AG1-109 GEN
50/50
3.309
274772LINCOLN ;3U
50/50
7.418
962771AG1-126 GEN
Solar/Wind Harmer
89.226
970153AG2-106 GEN
Solar/Wind Harmer
38.907
971347AH1-153 GEN
Solar/Wind Harmer
6.05
270043AE2-236 GEN
Solar/Wind Harmer
6.529
247643Z2-116 C
Solar/Wind Harmer
0.08
24441505OLIV SLR
Solar/Wind Harmer
0.154
270505AE1-170 C O1
Solar/Wind Harmer
17.214
945111AF1-176 GEN
Solar/Wind Harmer
6.468
270063AE2-323 C
Solar/Wind Harmer
2.513
965021AG1-366 GEN
Solar/Wind Harmer
2.608
944531AF1-118 GEN
Solar/Wind Harmer
39.173
274724RIVER EC ;11
Adder
19.791
972231SS25-0005
Solar/Wind Harmer
10.591
972181SS23-001
Solar/Wind Harmer
6.619
274752CRETE EC ;2U
Adder
5.455
274753CRETE EC ;3U
Adder
5.455
276164X3-005 C
Solar/Wind Harmer
0.782
274814UNIV PK N;0U
Adder
5.614
274807UNIV PK N;3U
Adder
5.602
274811UNIV PK N;7U
Adder
5.565
970707AG2-453 GEN
Solar/Wind Harmer
31.089
274803UNIV PARK;6U
Adder
6.454
274826FISK ;BP
Adder
12.118
972259AH1-714 GEN
Adder
21.114
274887GEN-1.85
Solar/Wind Harmer
5.893
276772AC2-154 GEN
Solar/Wind Harmer
3.087
276843GEN-1.7
Solar/Wind Harmer
0.634
276806AD2-047 C O1
Solar/Wind Harmer
11.833
972038AH1-567 GEN2
Adder
0.404
939351AE1-166 GEN
Solar/Wind Harmer
6.535
274676JOLIET 29;8U
Adder
32.523
274729ELWOOD EC;1P
Adder
18.034
274730ELWOOD EC;6P
Adder
18.034
274734ELWOOD EC;8P
Adder
18.034
274736ELWOOD EC;9P
Adder
18.034
943121AE2-341 GEN
Solar/Wind Harmer
16.387
943591AF1-030 GEN
Solar/Wind Harmer
10.925
274862TOP CROP ;2U
Solar/Wind Harmer
5.462
274682WAUKEGAN ;7U
Adder
19.404
964401AG1-302 GEN
Solar/Wind Harmer
9.773
276868AE1-113 GEN
Solar/Wind Harmer
10.789
274879MINONK ;1U
Solar/Wind Harmer
7.193
276799AD1-013 GEN
Solar/Wind Harmer
2.35
946671AF1-331 GEN
Solar/Wind Harmer
0.445
274855GSG-6 ;RU
Solar/Wind Harmer
3.925
274850MENDOTA H;RU
Solar/Wind Harmer
2.729
276602WESTBROOK C
Solar/Wind Harmer
2.259
959091AF2-200 GEN
Solar/Wind Harmer
21.158
274760LEE CO EC;1U
Adder
9.686
274767LEE CO EC;8U
Adder
9.572
24721905FLATG4
Adder
19.928
270144AC1-141 ST1_
50/50
2.451
24344005CKG1
50/50
7.462
24641605TWIN BRNCH
50/50
0.02
24653605MOTTVILLE
50/50
0.004
274775LINCOLN ;6U
50/50
7.418
274776LINCOLN ;7U
50/50
7.418
274777LINCOLN ;8U
50/50
7.418
270071AF1-092 GEN
Solar/Wind Harmer
17.395
971771AH1-392 GEN
Solar/Wind Harmer
10.406
270526AF1-158 GEN
Solar/Wind Harmer
5.216
960681AF2-359 GEN
Solar/Wind Harmer
4.343
970031AG2-029 GEN
Solar/Wind Harmer
28.389
944161AF1-084 GEN
Solar/Wind Harmer
2.504
959331AF2-224 GEN
Solar/Wind Harmer
11.213
972037AH1-567 GEN1
Adder
0.203
274827FISK ;RP
Adder
8.588
960591AF2-350 GEN
Solar/Wind Harmer
11.061
274800UNIV PARK;3U
Adder
6.448
274801UNIV PARK;4U
Adder
6.448
972228AH1-698 GEN2
Adder
4.095
972227AH1-698 GEN1
Adder
2.884
274687WILL CNTY;4U
Adder
30.745
274687WILL CNTY;4U
Adder
30.745
274675JOLIET 29;7U
Adder
33.728
274675JOLIET 29;7U
Adder
32.523
24729505KEY G4
Adder
7.126
274728ELWOOD EC;5P
Adder
18.034
274731ELWOOD EC;2P
Adder
18.034
274733ELWOOD EC;3P
Adder
18.034
274735ELWOOD EC;4P
Adder
18.034
276893AG1-478 C
Solar/Wind Harmer
0.603
970833AG2-524 GEN
Solar/Wind Harmer
9.569
970833AG2-524 GEN
Solar/Wind Harmer
4.451
274744AC1-111 GEN8
Adder
6.097
274746AC1-111 G10
Adder
6.097
970073AG2-061 GEN
Solar/Wind Harmer
2.489
958391AF2-133 GEN
Solar/Wind Harmer
9.701
959141AF2-205 GEN
Solar/Wind Harmer
6.431
971675AH1-338 GEN
Solar/Wind Harmer
19.139
971411AH1-196 GEN
Solar/Wind Harmer
15.949
276861AD2-134 GEN
Solar/Wind Harmer
1.898
276863AD2-134 GEN
Solar/Wind Harmer
1.898
971549AH1-272 GEN
Solar/Wind Harmer
19.629
274863CRW1-WTG
Solar/Wind Harmer
5.908
274864CRW2-WTG
Solar/Wind Harmer
5.908
971171AH1-044 GEN
Solar/Wind Harmer
21.158
276889AE2-281 GEN
Solar/Wind Harmer
2.027
274823ROCKFORD ;21
Adder
20.558
972267AH1-718 GEN
Adder
4.302
24344105CKG2
50/50
9.299
270143AC1-141 CT2_
50/50
2.775
24639705ELKHART HY
50/50
0.187
970521AG2-332 GEN
50/50
13.311
24307105BERRINSP G
50/50
0.024
274773LINCOLN ;4U
50/50
7.418
274774LINCOLN ;5U
50/50
7.418
962761AG1-125 GEN
Solar/Wind Harmer
89.226
970149AG2-104 GEN
Solar/Wind Harmer
55.097
970155AG2-107 GEN
Solar/Wind Harmer
38.907
270216AD2-079_GEN
Solar/Wind Harmer
0.699
957891AF2-083 GEN
Solar/Wind Harmer
17.194
945111AF1-176 GEN
Solar/Wind Harmer
20.409
270449AD2-020 GEN
Solar/Wind Harmer
3.19
943021AE2-325 GEN
Solar/Wind Harmer
4.145
972207SS24-0001
Solar/Wind Harmer
24.857
24441205WTRV SLR C
Solar/Wind Harmer
0.151
965011AG1-365 GEN
Solar/Wind Harmer
11.213
274723RIVER EC ;12
Adder
20.022
274751CRETE EC ;1U
Adder
5.455
274754CRETE EC ;4U
Adder
5.455
274812UNIV PK N;8U
Adder
5.565
970373AG2-245 GEN
Solar/Wind Harmer
23.253
274802UNIV PARK;5U
Adder
6.454
941551AE2-152 GEN
Solar/Wind Harmer
4.997
274676JOLIET 29;8U
Adder
33.727
274674JOLIET 9 ;6U
Adder
16.903
274732ELWOOD EC;7P
Adder
18.034
274871GR RIDGE ;2U
Solar/Wind Harmer
8.425
274847GR RIDGE ;BU
Solar/Wind Harmer
5.54
270055AF2-134 C O1
Solar/Wind Harmer
3.304
274745AC1-111 GEN9
Adder
6.097
276694AA1-018 GEN2
Solar/Wind Harmer
6.817
276691AA1-018 GEN1
Solar/Wind Harmer
0.815
274861TOP CROP ;1U
Solar/Wind Harmer
6.542
274682WAUKEGAN ;7U
Adder
19.404
274828WAUKEGAN ;BP
Adder
11.914
958381AF2-132 GEN
Solar/Wind Harmer
9.773
964861AG1-349 GEN
Solar/Wind Harmer
8.457
971917AH1-482 GEN
Solar/Wind Harmer
9.757
962781AG1-127 GEN
Solar/Wind Harmer
10.205
274872LEEDK;1U
Solar/Wind Harmer
8.794
939401AE1-172 GEN
Solar/Wind Harmer
14.927
276805AD2-038 GEN
Solar/Wind Harmer
5.489
276882AE2-255 GEN
Solar/Wind Harmer
3.596
971997AH1-543 GEN
Solar/Wind Harmer
16.77
957471AF2-041 GEN
Solar/Wind Harmer
31.738
959081AF2-199 GEN
Solar/Wind Harmer
10.579
971067AG2-660 GEN
Solar/Wind Harmer
2.46
940581AE2-045 GEN
Solar/Wind Harmer
10.772
971605AH1-302 GEN
Solar/Wind Harmer
9.211
274822ROCKFORD ;11
Adder
20.708
274761LEE CO EC;2U
Adder
9.686
274766LEE CO EC;7U
Adder
9.572
970819AG2-516 GEN
Solar/Wind Harmer
7.613
CPLELTFEXP_CPLE->PJM
CLTF
1.484
CBM West 2LTFEXP_CBM-W2->PJM
CBM
91.994
NYPJM->LTFIMP_NY
CLTF
2.82
LGEELTFEXP_LGEE->PJM
CLTF
3.91
WECLTFEXP_WEC->PJM
CLTF
4.019
AG2-052LTFEXP_AG2-052->PJM
LTF
0.25
AH1-155LTFEXP_AH1-155->PJM
LTF
0.374
LAGNLTFEXP_LAGN->PJM
CLTF
11.862
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.972
TVALTFEXP_TVA->PJM
CLTF
5.346
CBM West 1LTFEXP_CBM-W1->PJM
CBM
131.53
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.31
MECLTFEXP_MEC->PJM
CLTF
15.493
SIGELTFEXP_SIGE->PJM
CLTF
0.36

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AP_P2-2_WP-500-DRT14_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-500-DRT14_SRT-SL
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:105.46 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:4820.76
MW Contribution:
54.59
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270102X2-052 ST
50/50
1.745
270100X2-052 CT1
50/50
1.613
270101X2-052 CT2
50/50
1.613
24643105BUCHANAN
50/50
0.014
247620Y3-023
50/50
0.525
274770LINCOLN ;1U
50/50
7.048
274771LINCOLN ;2U
50/50
7.048
970349AG2-230 GEN
Solar/Wind Harmer
17.222
965681AG1-436 GEN
Solar/Wind Harmer
13.592
965791AG1-447 GEN
Solar/Wind Harmer
6.954
961051AF2-396 GEN
Solar/Wind Harmer
16.979
961051AF2-396 GEN
Solar/Wind Harmer
7.897
274805UNIV PK N;1U
Adder
5.29
274808UNIV PK N;4U
Adder
5.256
274888KELLY CRK;1U
Solar/Wind Harmer
6.195
276776AD2-060 GEN
Solar/Wind Harmer
0.439
958011AF2-095 GEN
Solar/Wind Harmer
15.117
970941AG2-585 GEN
Solar/Wind Harmer
5.774
276897AD1-100 C
Solar/Wind Harmer
48.591
274674JOLIET 9 ;6U
Adder
16.044
276893AG1-478 C
Solar/Wind Harmer
0.456
270535AF1-215 GEN1
Solar/Wind Harmer
4.689
270536AF1-215 GEN2
Solar/Wind Harmer
4.689
274696ROCKY RD ;4P
Adder
11.696
274695ROCKY RD ;2P
Adder
11.426
274693ROCKY RD ;1P
Adder
11.314
274697ROCKY RD ;3P
Adder
3.104
958481AF2-142 GEN
Solar/Wind Harmer
15.378
274683WAUKEGAN ;8U
Adder
21.575
274683WAUKEGAN ;8U
Adder
18.187
962691AG1-118 GEN
Solar/Wind Harmer
30.62
960751AF2-366 GEN
Solar/Wind Harmer
2.923
958491AF2-143 GEN
Solar/Wind Harmer
15.235
276901AD2-066 C O1
Solar/Wind Harmer
3.558
971341AH1-150 GEN
Solar/Wind Harmer
20.083
971343AH1-151 GEN
Solar/Wind Harmer
20.083
276872AE1-163_GEN1
Solar/Wind Harmer
6.731
276876AE1-163_GEN2
Solar/Wind Harmer
6.731
972235AH1-702 GEN1
Adder
2.52
972236AH1-702 GEN2
Adder
2.191
274764LEE CO EC;5U
Adder
9.214
274765LEE CO EC;6U
Adder
9.214
274762LEE CO EC;3U
Adder
9.192
274763LEE CO EC;4U
Adder
9.106
270054AF2-122 C O1
Solar/Wind Helper
1.659
270144AC1-141 ST1_
50/50
2.306
24641605TWIN BRNCH
50/50
0.019
24344005CKG1
50/50
7.012
24653605MOTTVILLE
50/50
0.004
274775LINCOLN ;6U
50/50
7.048
274776LINCOLN ;7U
50/50
7.048
274777LINCOLN ;8U
50/50
7.048
270071AF1-092 GEN
Solar/Wind Harmer
16.529
971771AH1-392 GEN
Solar/Wind Harmer
9.811
960681AF2-359 GEN
Solar/Wind Harmer
4.109
270526AF1-158 GEN
Solar/Wind Harmer
4.922
970031AG2-029 GEN
Solar/Wind Harmer
26.714
944161AF1-084 GEN
Solar/Wind Harmer
2.344
959331AF2-224 GEN
Solar/Wind Harmer
10.561
274827FISK ;RP
Adder
8.15
972037AH1-567 GEN1
Adder
0.192
960591AF2-350 GEN
Solar/Wind Harmer
10.498
274800UNIV PARK;3U
Adder
6.119
274801UNIV PARK;4U
Adder
6.119
972228AH1-698 GEN2
Adder
3.887
972227AH1-698 GEN1
Adder
2.737
24729505KEY G4
Adder
6.777
274687WILL CNTY;4U
Adder
29.18
274687WILL CNTY;4U
Adder
29.18
274675JOLIET 29;7U
Adder
32.013
274675JOLIET 29;7U
Adder
30.87
274728ELWOOD EC;5P
Adder
17.117
274731ELWOOD EC;2P
Adder
17.117
274733ELWOOD EC;3P
Adder
17.117
274735ELWOOD EC;4P
Adder
17.117
276893AG1-478 C
Solar/Wind Harmer
0.572
970833AG2-524 GEN
Solar/Wind Harmer
9.085
970833AG2-524 GEN
Solar/Wind Harmer
4.225
274744AC1-111 GEN8
Adder
5.789
274746AC1-111 G10
Adder
5.789
970073AG2-061 GEN
Solar/Wind Harmer
2.362
958391AF2-133 GEN
Solar/Wind Harmer
9.182
971675AH1-338 GEN
Solar/Wind Harmer
18.167
971411AH1-196 GEN
Solar/Wind Harmer
15.139
276861AD2-134 GEN
Solar/Wind Harmer
1.802
276863AD2-134 GEN
Solar/Wind Harmer
1.802
959141AF2-205 GEN
Solar/Wind Harmer
6.088
274863CRW1-WTG
Solar/Wind Harmer
5.607
274864CRW2-WTG
Solar/Wind Harmer
5.607
971171AH1-044 GEN
Solar/Wind Harmer
20.083
276889AE2-281 GEN
Solar/Wind Harmer
1.923
274823ROCKFORD ;21
Adder
19.512
274856ECOGROVE ;U1
Solar/Wind Harmer
3.358
276611AD2-172 GEN
Solar/Wind Harmer
2.547
276612AE2-035 GEN
Solar/Wind Harmer
2.547
926823AC1-168 GEN
Solar/Wind Harmer
4.27
972267AH1-718 GEN
Adder
4.083
270142AC1-141 CT1_
50/50
2.611
24642205MAYFLWER
50/50
0.04
274772LINCOLN ;3U
50/50
7.048
944961AF1-161 GEN
50/50
3.102
962601AG1-109 GEN
50/50
3.102
962771AG1-126 GEN
Solar/Wind Harmer
88.413
970153AG2-106 GEN
Solar/Wind Harmer
38.552
971347AH1-153 GEN
Solar/Wind Harmer
5.741
270043AE2-236 GEN
Solar/Wind Harmer
6.188
247643Z2-116 C
Solar/Wind Harmer
0.076
24441505OLIV SLR
Solar/Wind Harmer
0.145
270505AE1-170 C O1
Solar/Wind Harmer
16.169
270063AE2-323 C
Solar/Wind Harmer
2.365
945111AF1-176 GEN
Solar/Wind Harmer
6.074
944531AF1-118 GEN
Solar/Wind Harmer
37.269
274724RIVER EC ;11
Adder
18.774
972231SS25-0005
Solar/Wind Harmer
10.042
972181SS23-001
Solar/Wind Harmer
6.276
274752CRETE EC ;2U
Adder
5.172
274753CRETE EC ;3U
Adder
5.172
276164X3-005 C
Solar/Wind Harmer
0.742
965021AG1-366 GEN
Solar/Wind Harmer
2.456
970707AG2-453 GEN
Solar/Wind Harmer
29.527
274814UNIV PK N;0U
Adder
5.325
274807UNIV PK N;3U
Adder
5.314
274811UNIV PK N;7U
Adder
5.279
972259AH1-714 GEN
Adder
20.047
274826FISK ;BP
Adder
11.5
274803UNIV PARK;6U
Adder
6.124
274887GEN-1.85
Solar/Wind Harmer
5.593
276772AC2-154 GEN
Solar/Wind Harmer
2.93
276843GEN-1.7
Solar/Wind Harmer
0.602
276806AD2-047 C O1
Solar/Wind Harmer
11.231
972038AH1-567 GEN2
Adder
0.383
939351AE1-166 GEN
Solar/Wind Harmer
6.203
274676JOLIET 29;8U
Adder
30.869
274729ELWOOD EC;1P
Adder
17.117
274730ELWOOD EC;6P
Adder
17.117
274734ELWOOD EC;8P
Adder
17.117
274736ELWOOD EC;9P
Adder
17.117
943121AE2-341 GEN
Solar/Wind Harmer
15.56
943591AF1-030 GEN
Solar/Wind Harmer
10.373
274682WAUKEGAN ;7U
Adder
18.419
274862TOP CROP ;2U
Solar/Wind Harmer
5.183
964401AG1-302 GEN
Solar/Wind Harmer
9.249
276868AE1-113 GEN
Solar/Wind Harmer
10.239
274879MINONK ;1U
Solar/Wind Harmer
6.826
276799AD1-013 GEN
Solar/Wind Harmer
2.231
946671AF1-331 GEN
Solar/Wind Harmer
0.423
274855GSG-6 ;RU
Solar/Wind Harmer
3.726
274850MENDOTA H;RU
Solar/Wind Harmer
2.59
276602WESTBROOK C
Solar/Wind Harmer
2.145
959091AF2-200 GEN
Solar/Wind Harmer
20.083
274760LEE CO EC;1U
Adder
9.192
274767LEE CO EC;8U
Adder
9.084
24721905FLATG4
Adder
19.611
970571AG2-364 GEN
Solar/Wind Harmer
0.381
24344105CKG2
50/50
8.841
270143AC1-141 CT2_
50/50
2.611
24639705ELKHART HY
50/50
0.176
970521AG2-332 GEN
50/50
12.521
274773LINCOLN ;4U
50/50
7.048
274774LINCOLN ;5U
50/50
7.048
962761AG1-125 GEN
Solar/Wind Harmer
88.413
970149AG2-104 GEN
Solar/Wind Harmer
54.595
970155AG2-107 GEN
Solar/Wind Harmer
38.552
270216AD2-079_GEN
Solar/Wind Harmer
0.658
957891AF2-083 GEN
Solar/Wind Harmer
16.152
945111AF1-176 GEN
Solar/Wind Harmer
19.165
972207SS24-0001
Solar/Wind Harmer
23.616
270449AD2-020 GEN
Solar/Wind Harmer
2.99
943021AE2-325 GEN
Solar/Wind Harmer
3.886
274723RIVER EC ;12
Adder
18.993
274751CRETE EC ;1U
Adder
5.172
274754CRETE EC ;4U
Adder
5.172
965011AG1-365 GEN
Solar/Wind Harmer
10.561
274812UNIV PK N;8U
Adder
5.279
274802UNIV PARK;5U
Adder
6.124
970373AG2-245 GEN
Solar/Wind Harmer
22.001
24441205WTRV SLR C
Solar/Wind Harmer
0.141
941551AE2-152 GEN
Solar/Wind Harmer
4.744
274676JOLIET 29;8U
Adder
32.013
274674JOLIET 9 ;6U
Adder
16.044
274732ELWOOD EC;7P
Adder
17.117
274871GR RIDGE ;2U
Solar/Wind Harmer
7.998
274847GR RIDGE ;BU
Solar/Wind Harmer
5.259
274745AC1-111 GEN9
Adder
5.789
270055AF2-134 C O1
Solar/Wind Harmer
3.126
276694AA1-018 GEN2
Solar/Wind Harmer
6.469
276691AA1-018 GEN1
Solar/Wind Harmer
0.773
274682WAUKEGAN ;7U
Adder
18.419
274861TOP CROP ;1U
Solar/Wind Harmer
6.208
274828WAUKEGAN ;BP
Adder
11.309
958381AF2-132 GEN
Solar/Wind Harmer
9.249
962781AG1-127 GEN
Solar/Wind Harmer
9.688
964861AG1-349 GEN
Solar/Wind Harmer
8.004
971917AH1-482 GEN
Solar/Wind Harmer
9.235
274872LEEDK;1U
Solar/Wind Harmer
8.348
939401AE1-172 GEN
Solar/Wind Harmer
14.167
276805AD2-038 GEN
Solar/Wind Harmer
5.208
276882AE2-255 GEN
Solar/Wind Harmer
3.413
971997AH1-543 GEN
Solar/Wind Harmer
15.916
957471AF2-041 GEN
Solar/Wind Harmer
30.124
959081AF2-199 GEN
Solar/Wind Harmer
10.041
971067AG2-660 GEN
Solar/Wind Harmer
2.335
274822ROCKFORD ;11
Adder
19.655
940581AE2-045 GEN
Solar/Wind Harmer
10.198
971605AH1-302 GEN
Solar/Wind Harmer
8.72
970819AG2-516 GEN
Solar/Wind Harmer
11.965
274761LEE CO EC;2U
Adder
9.192
274766LEE CO EC;7U
Adder
9.084
970569AG2-363 GEN
Solar/Wind Harmer
0.572
CPLELTFEXP_CPLE->PJM
CLTF
1.417
CBM West 2LTFEXP_CBM-W2->PJM
CBM
87.018
NYPJM->LTFIMP_NY
CLTF
2.599
LGEELTFEXP_LGEE->PJM
CLTF
3.658
WECLTFEXP_WEC->PJM
CLTF
3.814
AG2-052LTFEXP_AG2-052->PJM
LTF
0.236
AH1-155LTFEXP_AH1-155->PJM
LTF
0.355
LAGNLTFEXP_LAGN->PJM
CLTF
11.231
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.638
TVALTFEXP_TVA->PJM
CLTF
5.057
CBM West 1LTFEXP_CBM-W1->PJM
CBM
119.975
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.173
MECLTFEXP_MEC->PJM
CLTF
14.692
SIGELTFEXP_SIGE->PJM
CLTF
0.339

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#8075_05MARYSV 765_A2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8075_05MARYSV 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.32 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6590.12
MW Contribution:
41.58
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
243186AF1-051 GEN
50/50
13.022
24721705FLATG2
50/50
43.628
24723005RIVRG1
Adder
35.405
24723105RIVRG2
Adder
35.405
970913AG2-568 GEN
Solar/Wind Harmer
10.639
24728205BUCHG1
Adder
6.758
971225AH1-072 GEN
Solar/Wind Harmer
2.946
971227AH1-073 GEN
Solar/Wind Harmer
2.946
270214AC2-123 GEN
Solar/Wind Harmer
3.099
971277AH1-098 GEN
Solar/Wind Harmer
5.287
927014AC1-188 GEN
Solar/Wind Harmer
1.995
24387305FR-4G C
Solar/Wind Harmer
6.235
966841AG1-555 GEN
Solar/Wind Harmer
3.081
945391AF1-204 GEN
Solar/Wind Harmer
17.098
970241AG2-163 GEN
Solar/Wind Harmer
30.673
270180AB1-006 GEN1
Solar/Wind Harmer
8.812
24697605MDL-3G C
Solar/Wind Harmer
4.516
24755605MDL-5G
Solar/Wind Harmer
2.954
24697905MDL-4G C
Solar/Wind Harmer
2.811
270181AB1-006 GEN2
Solar/Wind Harmer
0.876
945421AF1-207 GEN
Solar/Wind Harmer
17.195
957841AF2-078 GEN
Solar/Wind Harmer
7.402
270583AD2-179 GEN
Solar/Wind Harmer
12.237
274770LINCOLN ;1U
Adder
7.555
274771LINCOLN ;2U
Adder
7.555
274880W4-005 GEN4
Solar/Wind Harmer
3.683
276174W4-005 GEN2
Solar/Wind Harmer
3.683
276916AD2-100_GEN
Solar/Wind Harmer
25.572
276911AD2-131_GEN
Solar/Wind Harmer
5.168
276615X2-022 GEN
Solar/Wind Harmer
2.385
276838X2-022 GEN2
Solar/Wind Harmer
0.283
960611AF2-352 GEN
Solar/Wind Harmer
2.831
942111AE2-223 GEN
Solar/Wind Harmer
9.977
276897AD1-100 C
Solar/Wind Harmer
56.428
962691AG1-118 GEN
Solar/Wind Harmer
36.394
274696ROCKY RD ;4P
Adder
13.825
274695ROCKY RD ;2P
Adder
13.506
274693ROCKY RD ;1P
Adder
13.373
274697ROCKY RD ;3P
Adder
3.669
274674JOLIET 9 ;6U
Adder
18.672
274683WAUKEGAN ;8U
Adder
25.548
274683WAUKEGAN ;8U
Adder
21.536
972235AH1-702 GEN1
Adder
3.053
972236AH1-702 GEN2
Adder
2.655
274764LEE CO EC;5U
Adder
11.292
274765LEE CO EC;6U
Adder
11.292
274762LEE CO EC;3U
Adder
11.266
274763LEE CO EC;4U
Adder
11.16
237043AE2-125 C
Solar/Wind Helper
0.181
23585401KL_K28_T16
Solar/Wind Helper
1.305
23751201ROTHROCK
Solar/Wind Helper
0.749
254304AE2-114 C
Solar/Wind Helper
0.216
254305AE2-115 C
Solar/Wind Helper
0.216
962101AG1-054 GEN
Solar/Wind Helper
0.644
235054AD2-180 GEN
Solar/Wind Helper
1.728
241967AE2-285_GEN
Solar/Wind Helper
0.629
241801AE1-079 GEN
Solar/Wind Helper
0.246
238117U2-030
Solar/Wind Helper
0.291
20083426SW_E13_K22
Solar/Wind Helper
0.055
235531U2-073 GEN
Solar/Wind Helper
2.761
24721605FLATG1
50/50
2.938
957241AF2-018 GEN
Solar/Wind Harmer
7.557
270053AF1-130 C
Solar/Wind Harmer
30.195
270399AC1-101 GEN
Solar/Wind Harmer
7.142
270400AC1-102 GEN
Solar/Wind Harmer
7.142
941621AE2-160 GEN
Adder
5.016
970281AG2-184 GEN
Solar/Wind Harmer
31.268
971313AH1-133 GEN
Solar/Wind Harmer
8.781
962211AG1-066 GEN
Solar/Wind Harmer
3.415
24734705WLF1G3
Adder
7.988
24734805WLF1G4
Adder
7.988
24734905WLF1G5
Adder
7.988
971061AG2-657 GEN
Solar/Wind Harmer
12.335
24735105WLF2G1
Adder
7.848
966391AG1-508 GEN
Solar/Wind Harmer
4.607
971985AH1-537 GEN
Solar/Wind Harmer
23.357
971331AH1-145 GEN
Solar/Wind Harmer
11.822
971329AH1-144 GEN
Solar/Wind Harmer
7.552
270444AC2-157 GEN1
Solar/Wind Harmer
7.062
270445AC2-157 GEN2
Solar/Wind Harmer
7.062
971981AH1-535 GEN
Solar/Wind Harmer
12.497
24386405FR-21G C
Solar/Wind Harmer
5.279
24387005FR-3G C
Solar/Wind Harmer
4.855
963841AG1-237 GEN
Solar/Wind Harmer
13.411
946581AF1-322 GEN
Solar/Wind Harmer
12.536
24691005MDL-2G C
Solar/Wind Harmer
4.53
274775LINCOLN ;6U
Adder
7.555
274776LINCOLN ;7U
Adder
7.555
274777LINCOLN ;8U
Adder
7.555
944221AF1-090 GEN
Solar/Wind Harmer
13.317
276668AB2-070 GEN1
Solar/Wind Harmer
2.697
276848AB2-070 GEN3
Solar/Wind Harmer
2.697
276849AB2-070 GEN2
Solar/Wind Harmer
2.697
276763AC1-053 GEN1
Solar/Wind Harmer
4.814
276764AC1-053 GEN2
Solar/Wind Harmer
4.814
274853TWINGROVE;U1
Solar/Wind Harmer
8.769
274854TWINGROVE;U2
Solar/Wind Harmer
8.585
276726Z2-087_GEN
Solar/Wind Harmer
9.623
959341AF2-225 GEN
Solar/Wind Harmer
18.256
274863CRW1-WTG
Solar/Wind Harmer
6.788
274864CRW2-WTG
Solar/Wind Harmer
6.788
970169AG2-114 GEN
Solar/Wind Harmer
12.163
959141AF2-205 GEN
Solar/Wind Harmer
7.348
970833AG2-524 GEN
Solar/Wind Harmer
10.601
970833AG2-524 GEN
Solar/Wind Harmer
4.931
274744AC1-111 GEN8
Adder
6.785
274746AC1-111 G10
Adder
6.785
958391AF2-133 GEN
Solar/Wind Harmer
11.004
972228AH1-698 GEN2
Adder
4.493
972227AH1-698 GEN1
Adder
3.164
274728ELWOOD EC;5P
Adder
19.933
274731ELWOOD EC;2P
Adder
19.933
274733ELWOOD EC;3P
Adder
19.933
274735ELWOOD EC;4P
Adder
19.933
274675JOLIET 29;7U
Adder
37.198
274675JOLIET 29;7U
Adder
35.87
274687WILL CNTY;4U
Adder
33.865
274687WILL CNTY;4U
Adder
33.865
274823ROCKFORD ;21
Adder
23.605
274800UNIV PARK;3U
Adder
7.06
274801UNIV PARK;4U
Adder
7.06
274827FISK ;RP
Adder
9.392
972267AH1-718 GEN
Adder
5.041
23750501ELLIOTTS
Solar/Wind Helper
0.679
23652301WDPWR_K20
Solar/Wind Helper
0.146
241997AF1-093 GEN
Solar/Wind Helper
0.252
241985AE1-237 GEN
Solar/Wind Helper
0.246
241982AE2-343 S C
Solar/Wind Helper
0.221
23750701CROSSCHOOL
Solar/Wind Helper
1.209
203955AF1-039 C O1
Solar/Wind Helper
0.373
238118U2-030_1
Solar/Wind Helper
0.291
20089126CSLMN_L13
Solar/Wind Helper
0.591
20089226LOOKOUT
Solar/Wind Helper
0.59
20088926STNY CRK
Solar/Wind Helper
0.806
203940AF1-140 C
Solar/Wind Helper
0.388
20094526CT_V3-030
Solar/Wind Helper
0.462
20088626ARWF_N39
Solar/Wind Helper
1.182
203846AF2-130 C
Solar/Wind Helper
0.443
20334926Z1-069 C
Solar/Wind Helper
1.308
926823AC1-168 GEN
Solar/Wind Harmer
0.606
946071AF1-272 GEN
Solar/Wind Helper
2.663
20088826HIGHLAND
Solar/Wind Helper
0.88
203818AF1-086 GEN
Solar/Wind Helper
1.65
203961AE2-224 GEN
Solar/Wind Helper
2.354
946381AF1-302 GEN
Solar/Wind Helper
0.217
203853AF1-134 C O1
Solar/Wind Helper
0.466
203946AE2-131 C
Solar/Wind Helper
0.461
203804AE2-113_GEN
Solar/Wind Helper
1.698
940863AE2-074 GEN
Solar/Wind Helper
0.444
203954AE2-126 C
Solar/Wind Helper
0.458
203835AF1-098 GEN
Solar/Wind Helper
1.78
24289405MTG1
50/50
11.749
24318705GVG2
50/50
12.071
24722005FLATG5
50/50
2.938
24721905FLATG4
50/50
53.66
962771AG1-126 GEN
Solar/Wind Harmer
67.342
970153AG2-106 GEN
Solar/Wind Harmer
29.364
24686405CER G5
Adder
15.004
270330AC1-082 GEN2
Solar/Wind Harmer
0.789
270329AC1-082 GEN1
Solar/Wind Harmer
0.789
960911AF2-382 GEN
Solar/Wind Harmer
11.34
972103AH1-617 GEN
Solar/Wind Harmer
29.779
971461AH1-227 GEN
Solar/Wind Harmer
7.556
971191AH1-055 GEN
Solar/Wind Harmer
27.281
270346AE1-212 GEN
Solar/Wind Harmer
12.339
943031AE2-326 GEN
Solar/Wind Harmer
4.878
957541AF2-048 GEN
Solar/Wind Harmer
1.995
24386205FR-12G C
Solar/Wind Harmer
5.26
970193AG2-126 GEN
Solar/Wind Harmer
18.403
24690905MDL-1G C
Solar/Wind Harmer
9.836
970781AG2-491 GEN
Solar/Wind Harmer
12.252
958121AF2-106 GEN
Solar/Wind Harmer
5.546
274772LINCOLN ;3U
Adder
7.555
276785W4-005 GEN1
Solar/Wind Harmer
3.683
971993AH1-541 GEN
Solar/Wind Harmer
11.253
942481AE2-261 GEN
Solar/Wind Harmer
36.404
957381AF2-032 GEN
Solar/Wind Harmer
2.435
965091AG1-374 GEN
Solar/Wind Harmer
36.515
959611AF2-252 GEN
Solar/Wind Harmer
2.831
970707AG2-453 GEN
Solar/Wind Harmer
34.064
939351AE1-166 GEN
Solar/Wind Harmer
7.204
972259AH1-714 GEN
Adder
23.175
943121AE2-341 GEN
Solar/Wind Harmer
18.219
943591AF1-030 GEN
Solar/Wind Harmer
12.146
972273AH1-721 GEN
Adder
101.006
274729ELWOOD EC;1P
Adder
19.933
274730ELWOOD EC;6P
Adder
19.933
274734ELWOOD EC;8P
Adder
19.933
274736ELWOOD EC;9P
Adder
19.933
274682WAUKEGAN ;7U
Adder
21.789
274676JOLIET 29;8U
Adder
35.87
972038AH1-567 GEN2
Adder
0.442
274760LEE CO EC;1U
Adder
11.266
274767LEE CO EC;8U
Adder
11.133
274826FISK ;BP
Adder
13.253
237048AF1-022 C
Solar/Wind Helper
0.199
237046AF1-021 C
Solar/Wind Helper
0.345
235058AG1-386 C
Solar/Wind Helper
0.46
23562501BACKB
Solar/Wind Helper
0.911
202652Y1-033 WT C
Solar/Wind Helper
0.565
964991AG1-363 GEN
Solar/Wind Helper
3.718
238127S14_GEN_2
Solar/Wind Helper
0.686
20092526R32
Solar/Wind Helper
1.14
20303426NA_O38_P22
Solar/Wind Helper
0.969
203993AD2-133_GEN1
Solar/Wind Helper
1
203854AF2-039 C
Solar/Wind Helper
0.309
238108AE1-109 GEN1
Solar/Wind Helper
0.086
238110AE1-109 GEN3
Solar/Wind Helper
0.086
20398826ARMNA MT
Solar/Wind Helper
1.443
962511AG1-100 GEN
Solar/Wind Helper
0.445
941421AE2-139 GEN
Solar/Wind Helper
2.224
24289405MTG1
50/50
11.749
243186AF1-051 GEN
50/50
13.022
24318705GVG2
50/50
12.071
24721805FLATG3
50/50
2.938
962761AG1-125 GEN
Solar/Wind Harmer
67.342
970149AG2-104 GEN
Solar/Wind Harmer
41.584
970155AG2-107 GEN
Solar/Wind Harmer
29.364
24723205RIVRG3
Adder
35.405
972203AH1-686 GEN
Adder
4.304
24686505CER G6
Adder
15.123
944971AF1-162 GEN
Solar/Wind Harmer
11.902
971403AH1-188 GEN
Solar/Wind Harmer
23.698
270331AC1-082 GEN3
Solar/Wind Harmer
0.791
960001AF2-291 GEN
Solar/Wind Harmer
4.817
24728305BUCHG2
Adder
6.758
971687AH1-348 GEN
Solar/Wind Harmer
1.473
24735205WLF2G2
Adder
7.848
970091AG2-072 GEN
Adder
102.767
24385905FR-11G C
Solar/Wind Harmer
10.201
24386605FR-22G C
Solar/Wind Harmer
5.279
963741AG1-226 GEN
Solar/Wind Harmer
55.212
24791305MDL-5G
Solar/Wind Harmer
2.954
972207SS24-0001
Solar/Wind Harmer
26.861
274773LINCOLN ;4U
Adder
7.555
274774LINCOLN ;5U
Adder
7.555
276686W4-005 GEN3
Solar/Wind Harmer
3.683
276621W2-048 GEN
Solar/Wind Harmer
7.596
940581AE2-045 GEN
Solar/Wind Harmer
12.418
971605AH1-302 GEN
Solar/Wind Harmer
10.618
965911AG1-460 GEN
Solar/Wind Harmer
1.699
276655WTG1_EQ
Solar/Wind Harmer
10.623
276656WTG2_EQ
Solar/Wind Harmer
1.406
939741AE1-205 GEN
Solar/Wind Harmer
24.341
939401AE1-172 GEN
Solar/Wind Harmer
16.947
941551AE2-152 GEN
Solar/Wind Harmer
5.509
274871GR RIDGE ;2U
Solar/Wind Harmer
9.337
274847GR RIDGE ;BU
Solar/Wind Harmer
6.14
274745AC1-111 GEN9
Adder
6.785
971997AH1-543 GEN
Solar/Wind Harmer
19.104
274674JOLIET 9 ;6U
Adder
18.672
274732ELWOOD EC;7P
Adder
19.933
274682WAUKEGAN ;7U
Adder
21.789
274676JOLIET 29;8U
Adder
37.198
274828WAUKEGAN ;BP
Adder
13.392
274822ROCKFORD ;11
Adder
23.778
274761LEE CO EC;2U
Adder
11.266
274766LEE CO EC;7U
Adder
11.133
274802UNIV PARK;5U
Adder
6.986
238185AF2-356 C
Solar/Wind Helper
2.23
254303AC2-168 GEN
Solar/Wind Helper
0.156
241966AE1-183 GEN
Solar/Wind Helper
0.252
20089026BF_G21_K23
Solar/Wind Helper
0.468
20084626FORWARD
Solar/Wind Helper
0.35
238120AE2-309 GEN
Solar/Wind Helper
0.432
238126S14_GEN_1
Solar/Wind Helper
0.686
964201AG1-281 GEN
Solar/Wind Helper
0.472
23751101LEADS_P59
Solar/Wind Helper
1.885
20091526CHSTN_FL
Solar/Wind Helper
0.569
20090526Q36
Solar/Wind Helper
1
203952AE2-129 C
Solar/Wind Helper
0.461
203855AF2-088 C
Solar/Wind Helper
0.149
238109AE1-109 GEN2
Solar/Wind Helper
0.086
203830AF1-094 GEN
Solar/Wind Helper
0.449
203979AG1-198 GEN
Solar/Wind Helper
0.27
961971AG1-040 GEN
Solar/Wind Helper
0.447
203947AF1-006 C
Solar/Wind Helper
0.483
CPLELTFEXP_CPLE->PJM
CLTF
6.948
CBM West 2LTFEXP_CBM-W2->PJM
CBM
158.57
NYPJM->LTFIMP_NY
CLTF
5.358
LGEELTFEXP_LGEE->PJM
CLTF
8.414
WECLTFEXP_WEC->PJM
CLTF
4.631
AG2-052LTFEXP_AG2-052->PJM
LTF
0.281
AH1-155LTFEXP_AH1-155->PJM
LTF
0.421
LAGNLTFEXP_LAGN->PJM
CLTF
23.214
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.518
TVALTFEXP_TVA->PJM
CLTF
11.786
CBM West 1LTFEXP_CBM-W1->PJM
CBM
149.868
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.575
MECLTFEXP_MEC->PJM
CLTF
20.238
SIGELTFEXP_SIGE->PJM
CLTF
0.64

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#8980_05KAMMER 765_QQ2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8980_05KAMMER 765_QQ2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.27 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6477.04
MW Contribution:
33.69
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
2.758
957241AF2-018 GEN
Solar/Wind Harmer
7.699
270053AF1-130 C
Solar/Wind Harmer
30.765
270399AC1-101 GEN
Solar/Wind Harmer
7.281
270400AC1-102 GEN
Solar/Wind Harmer
7.281
970281AG2-184 GEN
Solar/Wind Harmer
32.719
971985AH1-537 GEN
Solar/Wind Harmer
27.788
941621AE2-160 GEN
Adder
5.034
962211AG1-066 GEN
Solar/Wind Harmer
3.649
971313AH1-133 GEN
Solar/Wind Harmer
8.798
972163AH1-664 GEN
Solar/Wind Harmer
14.536
972165AH1-665 GEN
Solar/Wind Harmer
11.629
339216AC1-074 GEN
Solar/Wind Harmer
2.394
25196108MFTGT2
Adder
2.183
25196108MFTGT2
Adder
2.027
3429211JKCT 2G
Adder
16.597
25196408WSDLE3
Adder
12.519
25196308WSDLE2
Adder
12.41
25196208WSDLE1
Adder
12.379
25196708WSDLE6
Adder
12.348
25196508WSDLE4
Adder
12.037
24734705WLF1G3
Adder
8.159
24734805WLF1G4
Adder
8.159
24734905WLF1G5
Adder
8.159
253433AC1-085 GEN1
Solar/Wind Harmer
7.506
253432AC1-085 GEN2
Solar/Wind Harmer
0.378
270340AC2-060 GEN
Solar/Wind Harmer
4.256
253406AD2-031_GEN
Solar/Wind Harmer
1.796
270263AC1-001 GEN
Solar/Wind Harmer
1.464
270444AC2-157 GEN1
Solar/Wind Harmer
7.815
270445AC2-157 GEN2
Solar/Wind Harmer
7.815
270291AC1-194 GEN
Solar/Wind Harmer
7.123
243186AF1-051 GEN
50/50
12.477
24721705FLATG2
50/50
40.954
24723005RIVRG1
Adder
35.892
24723105RIVRG2
Adder
35.892
927014AC1-188 GEN
Solar/Wind Harmer
2.477
970913AG2-568 GEN
Solar/Wind Harmer
10.623
971225AH1-072 GEN
Solar/Wind Harmer
3.04
971227AH1-073 GEN
Solar/Wind Harmer
3.04
24728205BUCHG1
Adder
6.8
962581AG1-107 GEN
Solar/Wind Harmer
7.389
961491AF2-440 GEN
Solar/Wind Harmer
3.071
971073AG2-665 GEN
Solar/Wind Harmer
11.654
970879AG2-548 GEN
Solar/Wind Harmer
1.694
252509AD1-136 GEN
Solar/Wind Harmer
0.369
972043AH1-570 GEN
Solar/Wind Harmer
3.585
972045AH1-571 GEN
Solar/Wind Harmer
2.868
25183208HLCRTG
Solar/Wind Harmer
8.652
971125AH1-004 GEN
Solar/Wind Harmer
5.691
970107AG2-081 GEN
Solar/Wind Harmer
4.268
25194408D.CRK1
Adder
10.747
25194508D.CRK3
Adder
2.009
942891AE2-308 GEN
Solar/Wind Harmer
14.201
253415AE1-040 GEN
Solar/Wind Harmer
1.57
964571AG1-320 GEN
Solar/Wind Harmer
11.341
270269AC2-059
Solar/Wind Harmer
12.798
24728805RICHG1
Adder
5.185
24728905RICHG2
Adder
5.185
945391AF1-204 GEN
Solar/Wind Harmer
18.959
926881AC1-175 GEN
Solar/Wind Harmer
7.589
253370AE2-315 SEC1
Adder
2.718
270383AD1-128 GEN
Solar/Wind Harmer
8.27
339231AF1-038_GEN
Solar/Wind Harmer
2.457
24725505WLD G2 C
Solar/Wind Harmer
5.381
24699105WLD G1 C
Solar/Wind Harmer
5.319
339236AF1-050_GEN
Solar/Wind Harmer
2.451
970241AG2-163 GEN
Solar/Wind Harmer
33.734
970291AG2-192 GEN
Solar/Wind Harmer
1.753
970291AG2-192 GEN
Solar/Wind Harmer
0.565
253349AC2-067 GEN
Solar/Wind Harmer
2.741
253400AC2-068 GEN
Solar/Wind Harmer
1.102
25322209TAIT E
Adder
13.112
25322209TAIT E
Adder
12.817
24387305FR-4G C
Solar/Wind Harmer
6.822
966841AG1-555 GEN
Solar/Wind Harmer
3.372
970883AG2-550 GEN
Solar/Wind Harmer
13.404
970885AG2-551 GEN
Solar/Wind Harmer
3.117
270180AB1-006 GEN1
Solar/Wind Harmer
9.612
24697605MDL-3G C
Solar/Wind Harmer
4.927
24755605MDL-5G
Solar/Wind Harmer
3.222
24697905MDL-4G C
Solar/Wind Harmer
3.067
270181AB1-006 GEN2
Solar/Wind Harmer
0.956
971485AH1-239 GEN
Solar/Wind Harmer
10.681
964781AG1-341 GEN
Solar/Wind Harmer
14.151
966021AG1-471 GEN
Solar/Wind Harmer
7.208
270031AE2-169
Solar/Wind Harmer
10.876
270599AE1-208 GEN
Solar/Wind Harmer
10.876
945421AF1-207 GEN
Solar/Wind Harmer
18.73
957841AF2-078 GEN
Solar/Wind Harmer
8.063
25326109MON D
Adder
1.753
964611AG1-324 GEN
Solar/Wind Harmer
0.697
247621Y3-024
Adder
0.321
270201AC2-176 GEN
Solar/Wind Harmer
6.831
274770LINCOLN ;1U
Adder
11.001
274771LINCOLN ;2U
Adder
11.001
274696ROCKY RD ;4P
Adder
14.841
274695ROCKY RD ;2P
Adder
14.499
274693ROCKY RD ;1P
Adder
14.356
274764LEE CO EC;5U
Adder
12.144
274765LEE CO EC;6U
Adder
12.144
274762LEE CO EC;3U
Adder
12.115
274763LEE CO EC;4U
Adder
12.001
274697ROCKY RD ;3P
Adder
3.939
972235AH1-702 GEN1
Adder
3.282
972236AH1-702 GEN2
Adder
2.854
274674JOLIET 9 ;6U
Adder
20.046
274683WAUKEGAN ;8U
Adder
27.432
23585401KL_K28_T16
Solar/Wind Helper
1.54
24735105WLF2G1
Adder
8.041
270356AE2-297 GEN
Solar/Wind Harmer
6.333
971061AG2-657 GEN
Solar/Wind Harmer
12.288
253372AE2-315 SEC3
Adder
2.57
253372AE2-315 SEC3
Adder
2.57
25306009OHH W.
Adder
3.905
970289AG2-191 GEN
Solar/Wind Harmer
2.562
963841AG1-237 GEN
Solar/Wind Harmer
14.713
971029AG2-637 GEN
Solar/Wind Harmer
20.191
24386405FR-21G C
Solar/Wind Harmer
5.776
24387005FR-3G C
Solar/Wind Harmer
5.313
270543AE2-219 C
Solar/Wind Harmer
13.404
946581AF1-322 GEN
Solar/Wind Harmer
13.675
24691005MDL-2G C
Solar/Wind Harmer
4.942
945581AF1-223 GEN
Solar/Wind Harmer
6.056
247536S-71 GEN
Solar/Wind Harmer
5.402
964611AG1-324 GEN
Solar/Wind Harmer
5.196
270432AC2-029 GEN
Solar/Wind Harmer
9.322
944221AF1-090 GEN
Solar/Wind Harmer
14.552
961761AG1-017 GEN
Solar/Wind Harmer
0.569
24729505KEY G4
Adder
8.55
274775LINCOLN ;6U
Adder
11.001
274776LINCOLN ;7U
Adder
11.001
274777LINCOLN ;8U
Adder
11.001
274744AC1-111 GEN8
Adder
7.28
274746AC1-111 G10
Adder
7.28
972267AH1-718 GEN
Adder
5.423
274728ELWOOD EC;5P
Adder
21.404
274731ELWOOD EC;2P
Adder
21.404
274733ELWOOD EC;3P
Adder
21.404
274735ELWOOD EC;4P
Adder
21.404
274823ROCKFORD ;21
Adder
25.367
972228AH1-698 GEN2
Adder
4.822
972227AH1-698 GEN1
Adder
3.396
23750501ELLIOTTS
Solar/Wind Helper
0.793
23652301WDPWR_K20
Solar/Wind Helper
0.169
23750701CROSSCHOOL
Solar/Wind Helper
1.437
238118U2-030_1
Solar/Wind Helper
0.345
203955AF1-039 C O1
Solar/Wind Helper
0.435
20089126CSLMN_L13
Solar/Wind Helper
0.688
20089226LOOKOUT
Solar/Wind Helper
0.686
241997AF1-093 GEN
Solar/Wind Helper
0.282
241985AE1-237 GEN
Solar/Wind Helper
0.274
241982AE2-343 S C
Solar/Wind Helper
0.246
20088926STNY CRK
Solar/Wind Helper
0.934
203940AF1-140 C
Solar/Wind Helper
0.45
20094526CT_V3-030
Solar/Wind Helper
0.534
20088626ARWF_N39
Solar/Wind Helper
1.372
203846AF2-130 C
Solar/Wind Helper
0.501
20334926Z1-069 C
Solar/Wind Helper
1.501
200917MEHOOPANY_G
Solar/Wind Helper
2.447
209067AE2-060 GEN
Solar/Wind Helper
0.092
959431AF2-234 GEN
Solar/Wind Helper
1.007
964051AG1-259 GEN
Solar/Wind Helper
0.075
964061AG1-260 GEN
Solar/Wind Helper
0.075
959421AF2-233 GEN
Solar/Wind Helper
0.504
209054AE2-059 GEN
Solar/Wind Helper
0.091
209027LOR2_Q27
Solar/Wind Helper
1.174
212266LOR1
Solar/Wind Helper
0.342
209029WAYMART-WD
Solar/Wind Helper
0.944
961261AF2-417 GEN
Solar/Wind Helper
0.499
20675128HRM_W1-127
Solar/Wind Helper
0.033
207408W3-077 C
Solar/Wind Helper
0.093
964851AG1-348 GEN
Solar/Wind Helper
0.069
20676428JCR_X2-075
Solar/Wind Helper
0.074
20676128MHD_W3-029
Solar/Wind Helper
0.104
20673828FLE_V3-070
Solar/Wind Helper
0.094
218526CNTRALGAS2 C
Solar/Wind Helper
0.174
20675528CPH_W2-050
Solar/Wind Helper
0.123
20720628TIN_W1-124
Solar/Wind Helper
0.205
219620RIDERU C
Solar/Wind Helper
0.001
207445AB1-138_GEN
Solar/Wind Helper
0.112
20715028HAN_X4-015
Solar/Wind Helper
0.061
20720728JCB_W1-129
Solar/Wind Helper
0.061
959381AF2-229 GEN
Solar/Wind Helper
0.367
20390526W1-045 C
Solar/Wind Helper
0.36
219615MILLCREEK C
Solar/Wind Helper
0.028
219258KINSLEYDEP C
Solar/Wind Helper
0.081
227927V4-067C
Solar/Wind Helper
0.011
230407AD2-065 C
Solar/Wind Helper
0.043
228728W1-130C
Solar/Wind Helper
0.057
230434AG1-499 GEN
Solar/Wind Helper
0.244
233901CHERRYDALE C
Solar/Wind Helper
0.242
233940AF2-379 C
Solar/Wind Helper
0.065
232432Z2-076 GEN
Solar/Wind Helper
0.07
205956AE1-196_GEN
Solar/Wind Helper
0.528
205943AE1-185 GEN
Solar/Wind Helper
0.528
233915AB1-141 GEN
Solar/Wind Helper
0.523
205917AD1-020 ES
Solar/Wind Helper
0.371
237025AB1-124 C
Solar/Wind Helper
0.147
237030AB1-096 C
Solar/Wind Helper
0.06
23779801AA1-109
Solar/Wind Helper
0.169
238169AE2-226 GEN1
Solar/Wind Helper
0.559
238170AE2-226 GEN2
Solar/Wind Helper
0.559
24289405MTG1
50/50
11.336
24318705GVG2
50/50
11.565
24722005FLATG5
50/50
2.758
24721905FLATG4
50/50
50.371
24686405CER G5
Adder
15.429
270330AC1-082 GEN2
Solar/Wind Harmer
0.842
270329AC1-082 GEN1
Solar/Wind Harmer
0.842
962771AG1-126 GEN
Solar/Wind Harmer
54.553
970153AG2-106 GEN
Solar/Wind Harmer
23.787
971191AH1-055 GEN
Solar/Wind Harmer
31.162
957541AF2-048 GEN
Solar/Wind Harmer
2.477
972103AH1-617 GEN
Solar/Wind Harmer
31.161
960911AF2-382 GEN
Solar/Wind Harmer
11.466
971461AH1-227 GEN
Solar/Wind Harmer
7.797
270367AC2-061_GEN
Solar/Wind Harmer
4.689
270186AC1-089 GEN
Solar/Wind Harmer
9.011
970879AG2-548 GEN
Solar/Wind Harmer
11.654
972167AH1-666 GEN
Solar/Wind Harmer
11.619
252507AC2-088 GEN
Solar/Wind Harmer
2.586
958171AF2-111 GEN
Solar/Wind Harmer
35.846
339243AC2-075 GEN1
Solar/Wind Harmer
0.648
252519AF1-045_GEN
Solar/Wind Harmer
5.2
25196008MFTGT1
Adder
1.918
25194608D.CRK4
Adder
2.336
252524AE2-267 GEN
Solar/Wind Harmer
2.234
25196608WSDLE5
Adder
12.162
3429391JKCT 9G
Adder
11.809
970093AG2-073 GEN
Solar/Wind Harmer
7.507
253317AC1-085 GEN4
Solar/Wind Harmer
11.825
946181AF1-283 GEN
Solar/Wind Harmer
18.362
253394AE2-221_GEN
Solar/Wind Harmer
6.325
970455AG2-298 GEN
Solar/Wind Harmer
4.865
970653AG2-424 GEN
Solar/Wind Harmer
0.96
339206AE1-143 GEN
Solar/Wind Harmer
2.932
972273AH1-721 GEN
Adder
114.179
24728705AND G3
Adder
10.976
24728505AND G1
Adder
5.248
970193AG2-126 GEN
Solar/Wind Harmer
20.406
24379505HDWTR1G C
Solar/Wind Harmer
10.752
270240V3-007_GEN2
Solar/Wind Harmer
8.412
253303V4-073 C
Solar/Wind Harmer
0.157
253370AE2-315 SEC1
Adder
2.718
253371AE2-315 SEC2
Adder
2.57
270346AE1-212 GEN
Solar/Wind Harmer
12.206
247642Z2-115 C
Solar/Wind Harmer
0.086
965461AG1-414 GEN
Solar/Wind Harmer
3.058
970289AG2-191 GEN
Solar/Wind Harmer
1.035
270004AE1-209 GEN
Solar/Wind Harmer
7.368
970825AG2-519 GEN
Solar/Wind Harmer
7.583
946031AF1-268 GEN
Solar/Wind Harmer
11.153
24386205FR-12G C
Solar/Wind Harmer
5.756
960071AF2-298 GEN
Solar/Wind Harmer
2.031
339255AE2-071 GEN
Solar/Wind Harmer
1.57
339250AF1-203 GEN
Solar/Wind Harmer
0.808
24690905MDL-1G C
Solar/Wind Harmer
10.73
970781AG2-491 GEN
Solar/Wind Harmer
13.365
962031AG1-047 GEN
Solar/Wind Harmer
4.019
274772LINCOLN ;3U
Adder
11.001
972259AH1-714 GEN
Adder
24.853
274760LEE CO EC;1U
Adder
12.115
274767LEE CO EC;8U
Adder
11.973
274729ELWOOD EC;1P
Adder
21.404
274730ELWOOD EC;6P
Adder
21.404
274734ELWOOD EC;8P
Adder
21.404
274736ELWOOD EC;9P
Adder
21.404
274682WAUKEGAN ;7U
Adder
7.239
237048AF1-022 C
Solar/Wind Helper
0.231
237046AF1-021 C
Solar/Wind Helper
0.4
235058AG1-386 C
Solar/Wind Helper
0.518
23562501BACKB
Solar/Wind Helper
1.078
964991AG1-363 GEN
Solar/Wind Helper
4.441
202652Y1-033 WT C
Solar/Wind Helper
0.66
238127S14_GEN_2
Solar/Wind Helper
0.816
20092526R32
Solar/Wind Helper
1.32
238108AE1-109 GEN1
Solar/Wind Helper
0.103
238110AE1-109 GEN3
Solar/Wind Helper
0.103
20303426NA_O38_P22
Solar/Wind Helper
1.125
203993AD2-133_GEN1
Solar/Wind Helper
1.157
203854AF2-039 C
Solar/Wind Helper
0.357
20398826ARMNA MT
Solar/Wind Helper
1.668
941421AE2-139 GEN
Solar/Wind Helper
2.591
209137AF2-361 C
Solar/Wind Helper
1.545
946731AF1-337 GEN
Solar/Wind Helper
0.504
212507AE2-042_GEN
Solar/Wind Helper
1.784
961341AF2-425 GEN
Solar/Wind Helper
0.502
961301AF2-421 GEN
Solar/Wind Helper
0.5
963151AG1-164 GEN
Solar/Wind Helper
0.5
211065PSPA IPP
Solar/Wind Helper
0.169
207518AF1-320_GEN
Solar/Wind Helper
1.73
20675728RH_W2-091
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.033
203975AE1-071-GEN
Solar/Wind Helper
2.698
207484AF2-139 C O1
Solar/Wind Helper
0.093
20674928WA_W3-044
Solar/Wind Helper
0.108
20676228FRD_X1-012
Solar/Wind Helper
0.101
20674628WNG_W3-110
Solar/Wind Helper
0.098
20676328BVR_Y1-020
Solar/Wind Helper
0.03
207439AE1-081 C O1
Solar/Wind Helper
0.02
207530AG1-191 GEN
Solar/Wind Helper
0.073
20676728BRNX1-095
Solar/Wind Helper
0.032
217208PARK ELE C
Solar/Wind Helper
0.005
217209CENTRL HS C
Solar/Wind Helper
0.009
20671828STAW2-080
Solar/Wind Helper
0.029
20673628F1S_V4-069
Solar/Wind Helper
0.032
962511AG1-100 GEN
Solar/Wind Helper
0.492
219908AB1-139 C
Solar/Wind Helper
0.08
219919AE1-041 FULL
Solar/Wind Helper
0.004
218428ETC SOLAR C
Solar/Wind Helper
0.005
218524CNTRALGAS1 C
Solar/Wind Helper
0.174
218440SUMMTASSOC C
Solar/Wind Helper
0.018
20715228NPK_W1-113
Solar/Wind Helper
0.084
20720528MAN_W1-024
Solar/Wind Helper
0.031
219680HOPEWELLV C1
Solar/Wind Helper
0.003
963711AG1-223 GEN
Solar/Wind Helper
0.069
20714528FRN_Y2-051
Solar/Wind Helper
0.061
219276PARKLANDSO C
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.103
20716028EGP_W2-019
Solar/Wind Helper
0.02
219348LDSOLAR C
Solar/Wind Helper
0.122
219686LUMSOLAR_N C
Solar/Wind Helper
0.042
219907AC1-030 C
Solar/Wind Helper
0.036
219766PARADISE C
Solar/Wind Helper
0.058
228729W2-030 C
Solar/Wind Helper
0.117
233996TM1833_GEN
Solar/Wind Helper
0.214
233998TM1NIN_3.36
Solar/Wind Helper
0.214
232404W1-003 C
Solar/Wind Helper
0.528
232408W1-005 C
Solar/Wind Helper
0.528
232426Y1-080 FULL
Solar/Wind Helper
0.04
205932AD2-116_GEN
Solar/Wind Helper
0.528
233944AB2-135 GEN
Solar/Wind Helper
0.614
233918AB1-142 GEN
Solar/Wind Helper
0.523
235063AE1-101 C2
Solar/Wind Helper
1.478
205916AD1-020 GEN
Solar/Wind Helper
1.727
237001AB1-127_GEN
Solar/Wind Helper
0.391
23777901MDS_W4-102
Solar/Wind Helper
0.152
208835TUHI V3-051
Solar/Wind Helper
0.022
238175AF1-290_GEN
Solar/Wind Helper
0.127
957741AF2-068 GEN
Solar/Wind Harmer
8.281
237043AE2-125 C
Solar/Wind Helper
0.209
23751201ROTHROCK
Solar/Wind Helper
0.884
235054AD2-180 GEN
Solar/Wind Helper
2.046
238117U2-030
Solar/Wind Helper
0.345
235531U2-073 GEN
Solar/Wind Helper
3.281
962101AG1-054 GEN
Solar/Wind Helper
0.72
254304AE2-114 C
Solar/Wind Helper
0.241
254305AE2-115 C
Solar/Wind Helper
0.241
20083426SW_E13_K22
Solar/Wind Helper
0.064
241967AE2-285_GEN
Solar/Wind Helper
0.7
241801AE1-079 GEN
Solar/Wind Helper
0.274
946071AF1-272 GEN
Solar/Wind Helper
3.071
20088826HIGHLAND
Solar/Wind Helper
1.019
203961AE2-224 GEN
Solar/Wind Helper
2.731
203818AF1-086 GEN
Solar/Wind Helper
1.901
203853AF1-134 C O1
Solar/Wind Helper
0.537
946381AF1-302 GEN
Solar/Wind Helper
0.248
203946AE2-131 C
Solar/Wind Helper
0.533
203954AE2-126 C
Solar/Wind Helper
0.526
940863AE2-074 GEN
Solar/Wind Helper
0.508
203804AE2-113_GEN
Solar/Wind Helper
1.942
946751AF1-339 GEN
Solar/Wind Helper
0.504
961431AF2-434 GEN
Solar/Wind Helper
0.502
316097T157 G90
Solar/Wind Helper
1.163
203835AF1-098 GEN
Solar/Wind Helper
1.976
20674828DL_W4-046
Solar/Wind Helper
0.009
20675928HOL_W4-097
Solar/Wind Helper
0.055
207471AF2-354 C
Solar/Wind Helper
0.185
20674328GAR_V4-001
Solar/Wind Helper
0.025
217204WCALDSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217081WEATEXAS C
Solar/Wind Helper
0.014
20675428EAM_W2-061
Solar/Wind Helper
0.017
218438BLK ROCK C
Solar/Wind Helper
0.029
20742028HF_AC1-207
Solar/Wind Helper
0.152
20714828MDF_W3-079
Solar/Wind Helper
0.14
207459AE1-142 C O1
Solar/Wind Helper
0.312
20720828JCB_W4-025
Solar/Wind Helper
0.068
214067T20SOLAR
Solar/Wind Helper
0.012
219607WPEMNERT C
Solar/Wind Helper
0.085
219304NAMERICA C
Solar/Wind Helper
0.14
219906AC1-017 C
Solar/Wind Helper
0.045
219272CLEANLIGHT C
Solar/Wind Helper
0.027
219912AD2-042 GEN
Solar/Wind Helper
0.159
219904AC1-010 C
Solar/Wind Helper
0.064
228754AB1-001 C
Solar/Wind Helper
0.028
230433AD2-135 GEN
Solar/Wind Helper
0.018
230511AF1-262
Solar/Wind Helper
0.016
233952AC2-187 GEN
Solar/Wind Helper
0.242
233954AC2-188 GEN
Solar/Wind Helper
0.242
232410W1-006 C
Solar/Wind Helper
0.528
234015AF2-250 C
Solar/Wind Helper
0.04
233946AB2-136 GEN
Solar/Wind Helper
0.592
233994AC2-023 GEN
Solar/Wind Helper
1.001
232428Y3-058 C
Solar/Wind Helper
0.352
234036AF2-325 C
Solar/Wind Helper
0.044
232424Y1-079 C
Solar/Wind Helper
0.121
232436AB1-176 C
Solar/Wind Helper
0.046
233982AB2-133 GEN
Solar/Wind Helper
0.374
233930AB2-032 GEN
Solar/Wind Helper
0.396
235062AE1-101 C1
Solar/Wind Helper
1.478
237080AD1-060 GEN
Solar/Wind Helper
0.299
235020AA1-095 C
Solar/Wind Helper
0.045
238221AF1-254 C O1
Solar/Wind Helper
0.238
237006AB1-125 GEN
Solar/Wind Helper
0.11
223401AF1-299 GEN
Solar/Wind Helper
0.341
223402AF1-300 C
Solar/Wind Helper
0.341
24289405MTG1
50/50
11.336
243186AF1-051 GEN
50/50
12.477
24318705GVG2
50/50
11.565
24721805FLATG3
50/50
2.758
972203AH1-686 GEN
Adder
4.409
24723205RIVRG3
Adder
35.892
24686505CER G6
Adder
15.551
270331AC1-082 GEN3
Solar/Wind Harmer
0.844
944971AF1-162 GEN
Solar/Wind Harmer
12.126
960001AF2-291 GEN
Solar/Wind Harmer
5.223
971403AH1-188 GEN
Solar/Wind Harmer
23.963
962761AG1-125 GEN
Solar/Wind Harmer
54.553
970149AG2-104 GEN
Solar/Wind Harmer
33.686
970155AG2-107 GEN
Solar/Wind Harmer
23.787
971687AH1-348 GEN
Solar/Wind Harmer
1.522
24728305BUCHG2
Adder
6.8
970091AG2-072 GEN
Adder
113.084
971073AG2-665 GEN
Solar/Wind Harmer
1.694
945681AF1-233 GEN
Solar/Wind Harmer
27.387
339221AD2-048_GEN
Solar/Wind Harmer
2.202
25196808ZIMRHP
Adder
108.598
252516AE2-318_GEN
Solar/Wind Harmer
14.288
252510AF1-249 C
Solar/Wind Harmer
0.594
25196008MFTGT1
Adder
1.98
943111AE2-339 GEN
Solar/Wind Harmer
1.257
25194608D.CRK4
Adder
2.336
3429241JKCT 3G
Adder
16.815
3429421JKCT 10G
Adder
11.809
253316AC1-085 GEN3
Solar/Wind Harmer
11.825
946171AF1-282 GEN
Solar/Wind Harmer
14.124
339211AE2-254 GEN
Solar/Wind Harmer
2.115
24735205WLF2G2
Adder
8.041
253398AE2-221_GEN2
Solar/Wind Harmer
6.325
270222AC2-111 GEN
Solar/Wind Harmer
6.156
944031AF1-071 GEN
Solar/Wind Harmer
1.385
970653AG2-424 GEN
Solar/Wind Harmer
6.638
270273AD2-016 GEN
Solar/Wind Harmer
3.648
24728605AND G2
Adder
5.248
339241AF1-083 GEN
Solar/Wind Harmer
2.268
942081AE2-220 GEN
Solar/Wind Harmer
8.696
270209AC1-174_GEN
Solar/Wind Harmer
5.534
270437AC2-090 C
Solar/Wind Harmer
7.589
270239V3-007_GEN1
Solar/Wind Harmer
2.34
253370AE2-315 SEC1
Adder
2.718
253371AE2-315 SEC2
Adder
2.57
276903AD2-071 C
Solar/Wind Harmer
13.523
963741AG1-226 GEN
Solar/Wind Harmer
60.722
964901AG1-354 GEN
Solar/Wind Harmer
20.24
270594AE1-207 GEN
Solar/Wind Harmer
18.313
270032AE2-172
Solar/Wind Harmer
6.271
270005AE1-210 C O1
Solar/Wind Harmer
7.368
970825AG2-519 GEN
Solar/Wind Harmer
2.824
25326309TAIT D
Adder
1.473
24385905FR-11G C
Solar/Wind Harmer
11.163
24386605FR-22G C
Solar/Wind Harmer
5.776
24791305MDL-5G
Solar/Wind Harmer
3.222
945371AF1-202 GEN
Solar/Wind Harmer
9.316
958861AF2-177 GEN
Solar/Wind Harmer
14.534
274773LINCOLN ;4U
Adder
11.001
274774LINCOLN ;5U
Adder
11.001
274745AC1-111 GEN9
Adder
7.28
274761LEE CO EC;2U
Adder
12.115
274766LEE CO EC;7U
Adder
11.973
274732ELWOOD EC;7P
Adder
21.404
274822ROCKFORD ;11
Adder
25.553
274674JOLIET 9 ;6U
Adder
20.046
238185AF2-356 C
Solar/Wind Helper
2.64
20089026BF_G21_K23
Solar/Wind Helper
0.545
238120AE2-309 GEN
Solar/Wind Helper
0.514
238126S14_GEN_1
Solar/Wind Helper
0.816
254303AC2-168 GEN
Solar/Wind Helper
0.175
241966AE1-183 GEN
Solar/Wind Helper
0.282
23751101LEADS_P59
Solar/Wind Helper
2.242
20084626FORWARD
Solar/Wind Helper
0.405
964201AG1-281 GEN
Solar/Wind Helper
0.548
20091526CHSTN_FL
Solar/Wind Helper
0.659
238109AE1-109 GEN2
Solar/Wind Helper
0.103
20090526Q36
Solar/Wind Helper
1.157
203952AE2-129 C
Solar/Wind Helper
0.533
203855AF2-088 C
Solar/Wind Helper
0.172
209071AE2-133 GEN
Solar/Wind Helper
0.092
946691AF1-333 GEN
Solar/Wind Helper
0.504
946741AF1-338 GEN
Solar/Wind Helper
0.504
961421AF2-433 GEN
Solar/Wind Helper
0.502
957921AF2-086 GEN
Solar/Wind Helper
0.497
961331AF2-424 GEN
Solar/Wind Helper
0.502
208972BECR K09
Solar/Wind Helper
0.375
963161AG1-165 GEN
Solar/Wind Helper
0.5
316095T157 G97
Solar/Wind Helper
1.163
203830AF1-094 GEN
Solar/Wind Helper
0.499
203979AG1-198 GEN
Solar/Wind Helper
0.3
23583801GRNGAP
Solar/Wind Helper
4.315
211065PSPA IPP
Solar/Wind Helper
0.169
209116AE2-175 GEN
Solar/Wind Helper
1.985
961971AG1-040 GEN
Solar/Wind Helper
0.495
20671928W4-073
Solar/Wind Helper
0.099
20674128FR_U2-059
Solar/Wind Helper
0.004
207437AD2-070 GEN
Solar/Wind Helper
0.152
207511W3-106 GEN
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.089
217169METRODIV C
Solar/Wind Helper
0.004
217211CAMDEN ST C
Solar/Wind Helper
0.005
207442AE1-156 GEN
Solar/Wind Helper
0.354
20673728F2S_V4-070
Solar/Wind Helper
0.032
219249CENTRALDIV C
Solar/Wind Helper
0.011
217213AMBOY SO C
Solar/Wind Helper
0.031
205941AD2-115 GEN
Solar/Wind Helper
0.536
20716928W4-060COL
Solar/Wind Helper
0.056
219612MATRIX C
Solar/Wind Helper
0.026
207454AA2-184 E
Solar/Wind Helper
0.335
219918AC2-009 C
Solar/Wind Helper
0.001
20714928UPF_X1-085
Solar/Wind Helper
0.006
20715728PEM_W1-119
Solar/Wind Helper
0.103
959561AF2-247 GEN
Solar/Wind Helper
0.022
219688LUMSOLAR_S C
Solar/Wind Helper
0.042
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
218660EHAMPSOLAR C
Solar/Wind Helper
0.035
219291REEVESSOUT C
Solar/Wind Helper
0.012
219914AD2-027 C
Solar/Wind Helper
0.122
203947AF1-006 C
Solar/Wind Helper
0.532
219921AF1-264
Solar/Wind Helper
0.054
219623KINSLEYBEA C
Solar/Wind Helper
0.002
230415AB2-049 C
Solar/Wind Helper
0.032
233923SMA
Solar/Wind Helper
0.783
233997TMININ_4.2
Solar/Wind Helper
0.214
232406W1-004 FULL
Solar/Wind Helper
0.528
233950AC2-186 GEN
Solar/Wind Helper
0.121
232434Z2-077 GEN
Solar/Wind Helper
0.132
233964AF2-378 GEN
Solar/Wind Helper
0.043
237085AD2-009_GEN
Solar/Wind Helper
1.463
232417X3-008 C
Solar/Wind Helper
0.242
233987AB2-037 GEN
Solar/Wind Helper
2.439
232422X3-066 FULL
Solar/Wind Helper
0.119
233933AB2-153 GEN
Solar/Wind Helper
0.242
233935AB2-179 C
Solar/Wind Helper
1.32
235067AD1-061 GEN
Solar/Wind Helper
0.394
237038AE2-054 C
Solar/Wind Helper
0.24
237002AB1-128_GEN
Solar/Wind Helper
0.392
208835TUHI V3-051
Solar/Wind Helper
0.022
23777801MSM_W1-116
Solar/Wind Helper
0.101
CPLELTFEXP_CPLE->PJM
CLTF
6.482
CBM West 2LTFEXP_CBM-W2->PJM
CBM
172.282
NYPJM->LTFIMP_NY
CLTF
6.32
LGEELTFEXP_LGEE->PJM
CLTF
9.798
WECLTFEXP_WEC->PJM
CLTF
4.977
AG2-052LTFEXP_AG2-052->PJM
LTF
0.304
AH1-155LTFEXP_AH1-155->PJM
LTF
0.457
LAGNLTFEXP_LAGN->PJM
CLTF
24.73
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.035
TVALTFEXP_TVA->PJM
CLTF
12.563
CBM West 1LTFEXP_CBM-W1->PJM
CBM
169.306
CBM South 1LTFEXP_CBM-S1->PJM
CBM
48.33
MECLTFEXP_MEC->PJM
CLTF
21.831
SIGELTFEXP_SIGE->PJM
CLTF
0.725

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P1-2_#17217_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#17217_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.4 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6428.58
MW Contribution:
24.84
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
2.758
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
270053AF1-130 C
Solar/Wind Harmer
27.062
270399AC1-101 GEN
Solar/Wind Harmer
3.79
270400AC1-102 GEN
Solar/Wind Harmer
3.79
970281AG2-184 GEN
Solar/Wind Harmer
22.827
971985AH1-537 GEN
Solar/Wind Harmer
3.231
941621AE2-160 GEN
Adder
5.034
971313AH1-133 GEN
Solar/Wind Harmer
5.062
972163AH1-664 GEN
Solar/Wind Harmer
11.291
972165AH1-665 GEN
Solar/Wind Harmer
9.043
339216AC1-074 GEN
Solar/Wind Harmer
0.266
25196108MFTGT2
Adder
2.183
25196108MFTGT2
Adder
2.027
3429211JKCT 2G
Adder
16.597
25196408WSDLE3
Adder
12.519
25196308WSDLE2
Adder
12.41
25196208WSDLE1
Adder
12.379
25196708WSDLE6
Adder
12.348
25196508WSDLE4
Adder
12.037
24734705WLF1G3
Adder
8.159
24734805WLF1G4
Adder
8.159
24734905WLF1G5
Adder
8.159
270340AC2-060 GEN
Solar/Wind Harmer
0.001
253406AD2-031_GEN
Solar/Wind Harmer
0.728
270263AC1-001 GEN
Solar/Wind Harmer
0.978
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
270291AC1-194 GEN
Solar/Wind Harmer
0
24735105WLF2G1
Adder
8.041
270356AE2-297 GEN
Solar/Wind Harmer
0.001
971061AG2-657 GEN
Solar/Wind Harmer
6.001
253372AE2-315 SEC3
Adder
2.57
253372AE2-315 SEC3
Adder
2.57
25306009OHH W.
Adder
3.905
970289AG2-191 GEN
Solar/Wind Harmer
1.788
963841AG1-237 GEN
Solar/Wind Harmer
4.07
971029AG2-637 GEN
Solar/Wind Harmer
14.087
24386405FR-21G C
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
6.546
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0.001
247536S-71 GEN
Solar/Wind Harmer
0.372
971609AH1-304 GEN
Solar/Wind Harmer
1.521
964611AG1-324 GEN
Solar/Wind Harmer
3.625
270432AC2-029 GEN
Solar/Wind Harmer
4.119
944221AF1-090 GEN
Solar/Wind Harmer
5.449
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.363
276848AB2-070 GEN3
Solar/Wind Harmer
0.362
276849AB2-070 GEN2
Solar/Wind Harmer
0.363
971611AH1-305 GEN
Solar/Wind Harmer
5.499
959141AF2-205 GEN
Solar/Wind Harmer
0.001
274854TWINGROVE;U2
Solar/Wind Harmer
0
24729505KEY G4
Adder
8.55
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
9.649
966391AG1-508 GEN
Solar/Wind Harmer
1.42
970169AG2-114 GEN
Solar/Wind Harmer
9.156
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
241972AD1-140 GEN
Solar/Wind Harmer
0.996
274877BISHOP HL;1U
Solar/Wind Harmer
0.304
926823AC1-168 GEN
Solar/Wind Harmer
1.55
274775LINCOLN ;6U
Adder
11.001
274776LINCOLN ;7U
Adder
11.001
274777LINCOLN ;8U
Adder
11.001
970073AG2-061 GEN
Solar/Wind Harmer
3.032
276741O09 GEN1
Solar/Wind Harmer
0.321
970833AG2-524 GEN
Solar/Wind Harmer
10.003
970833AG2-524 GEN
Solar/Wind Harmer
6.669
274744AC1-111 GEN8
Adder
7.28
274746AC1-111 G10
Adder
7.28
276861AD2-134 GEN
Solar/Wind Harmer
0.162
276863AD2-134 GEN
Solar/Wind Harmer
0.162
971675AH1-338 GEN
Solar/Wind Harmer
3.544
971171AH1-044 GEN
Solar/Wind Harmer
18.173
971681AH1-341 GEN
Solar/Wind Harmer
14.63
972267AH1-718 GEN
Adder
5.423
946321AF1-296 GEN
Solar/Wind Harmer
5.088
274728ELWOOD EC;5P
Adder
21.404
274731ELWOOD EC;2P
Adder
21.404
274733ELWOOD EC;3P
Adder
21.404
274735ELWOOD EC;4P
Adder
21.404
274856ECOGROVE ;U1
Solar/Wind Harmer
0.212
274823ROCKFORD ;21
Adder
25.367
971411AH1-196 GEN
Solar/Wind Harmer
13.626
972228AH1-698 GEN2
Adder
4.822
972227AH1-698 GEN1
Adder
3.396
960591AF2-350 GEN
Solar/Wind Harmer
9.078
23750501ELLIOTTS
Solar/Wind Helper
0.793
23652301WDPWR_K20
Solar/Wind Helper
0.169
23750701CROSSCHOOL
Solar/Wind Helper
1.437
238118U2-030_1
Solar/Wind Helper
0.345
203955AF1-039 C O1
Solar/Wind Helper
0.435
20089126CSLMN_L13
Solar/Wind Helper
0.688
20089226LOOKOUT
Solar/Wind Helper
0.686
241997AF1-093 GEN
Solar/Wind Helper
0.282
241985AE1-237 GEN
Solar/Wind Helper
0.274
241982AE2-343 S C
Solar/Wind Helper
0.246
20088926STNY CRK
Solar/Wind Helper
0.934
203940AF1-140 C
Solar/Wind Helper
0.45
20094526CT_V3-030
Solar/Wind Helper
0.534
20088626ARWF_N39
Solar/Wind Helper
1.372
203846AF2-130 C
Solar/Wind Helper
0.501
20334926Z1-069 C
Solar/Wind Helper
1.501
200917MEHOOPANY_G
Solar/Wind Helper
2.447
209067AE2-060 GEN
Solar/Wind Helper
0.092
959431AF2-234 GEN
Solar/Wind Helper
1.007
964051AG1-259 GEN
Solar/Wind Helper
0.075
964061AG1-260 GEN
Solar/Wind Helper
0.075
959421AF2-233 GEN
Solar/Wind Helper
0.504
209054AE2-059 GEN
Solar/Wind Helper
0.091
209027LOR2_Q27
Solar/Wind Helper
1.174
212266LOR1
Solar/Wind Helper
0.342
209029WAYMART-WD
Solar/Wind Helper
0.944
961261AF2-417 GEN
Solar/Wind Helper
0.499
20675128HRM_W1-127
Solar/Wind Helper
0.033
207408W3-077 C
Solar/Wind Helper
0.093
964851AG1-348 GEN
Solar/Wind Helper
0.069
243186AF1-051 GEN
50/50
12.477
24721705FLATG2
50/50
40.954
24723005RIVRG1
Adder
35.892
24723105RIVRG2
Adder
35.892
970913AG2-568 GEN
Solar/Wind Harmer
8.731
971225AH1-072 GEN
Solar/Wind Harmer
2.121
971227AH1-073 GEN
Solar/Wind Harmer
2.121
24728205BUCHG1
Adder
6.8
962581AG1-107 GEN
Solar/Wind Harmer
0.002
971073AG2-665 GEN
Solar/Wind Harmer
7.453
970879AG2-548 GEN
Solar/Wind Harmer
1.694
252509AD1-136 GEN
Solar/Wind Harmer
0.05
972043AH1-570 GEN
Solar/Wind Harmer
2.601
972045AH1-571 GEN
Solar/Wind Harmer
2.084
25183208HLCRTG
Solar/Wind Harmer
0.001
971125AH1-004 GEN
Solar/Wind Harmer
3.97
970107AG2-081 GEN
Solar/Wind Harmer
2.978
25194408D.CRK1
Adder
10.747
25194508D.CRK3
Adder
2.009
942891AE2-308 GEN
Solar/Wind Harmer
9.908
971587AH1-292 GEN
Solar/Wind Harmer
7.164
964571AG1-320 GEN
Solar/Wind Harmer
8.813
270269AC2-059
Solar/Wind Harmer
0.001
24728805RICHG1
Adder
5.185
24728905RICHG2
Adder
5.185
945391AF1-204 GEN
Solar/Wind Harmer
10.085
926881AC1-175 GEN
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
2.718
270383AD1-128 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
5.492
970291AG2-192 GEN
Solar/Wind Harmer
1.223
970291AG2-192 GEN
Solar/Wind Harmer
0.565
971613AH1-306 GEN
Solar/Wind Harmer
4.515
25322209TAIT E
Adder
13.112
25322209TAIT E
Adder
12.817
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
1.061
970883AG2-550 GEN
Solar/Wind Harmer
9.352
970885AG2-551 GEN
Solar/Wind Harmer
3.117
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
971485AH1-239 GEN
Solar/Wind Harmer
7.452
964781AG1-341 GEN
Solar/Wind Harmer
9.873
966021AG1-471 GEN
Solar/Wind Harmer
5.029
270031AE2-169
Solar/Wind Harmer
5.121
270599AE1-208 GEN
Solar/Wind Harmer
8.535
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0.001
25326109MON D
Adder
1.753
964611AG1-324 GEN
Solar/Wind Harmer
0.697
247621Y3-024
Adder
0.321
270201AC2-176 GEN
Solar/Wind Harmer
0
276916AD2-100_GEN
Solar/Wind Harmer
19.462
276911AD2-131_GEN
Solar/Wind Harmer
1.282
944541AF1-119 GEN
Solar/Wind Harmer
0.618
960971AF2-388 GEN
Solar/Wind Harmer
5.431
276615X2-022 GEN
Solar/Wind Harmer
0.096
276838X2-022 GEN2
Solar/Wind Harmer
0.521
960611AF2-352 GEN
Solar/Wind Harmer
3.067
942111AE2-223 GEN
Solar/Wind Harmer
2.987
276645AC1-214 GEN1
Solar/Wind Harmer
0.358
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
276901AD2-066 C O1
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
22.743
274770LINCOLN ;1U
Adder
11.001
274771LINCOLN ;2U
Adder
11.001
958491AF2-143 GEN
Solar/Wind Harmer
13.642
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.467
958481AF2-142 GEN
Solar/Wind Harmer
13.633
962691AG1-118 GEN
Solar/Wind Harmer
27.261
971341AH1-150 GEN
Solar/Wind Harmer
18.173
971343AH1-151 GEN
Solar/Wind Harmer
18.173
938861AE1-114 GEN
Solar/Wind Harmer
5.149
274696ROCKY RD ;4P
Adder
14.841
274695ROCKY RD ;2P
Adder
14.499
274693ROCKY RD ;1P
Adder
14.356
274764LEE CO EC;5U
Adder
12.144
274765LEE CO EC;6U
Adder
12.144
274762LEE CO EC;3U
Adder
12.115
274763LEE CO EC;4U
Adder
12.001
274697ROCKY RD ;3P
Adder
3.939
972235AH1-702 GEN1
Adder
3.282
972236AH1-702 GEN2
Adder
2.854
276893AG1-478 C
Solar/Wind Harmer
0.606
274674JOLIET 9 ;6U
Adder
20.046
942221AE2-234 GEN
Solar/Wind Harmer
3.648
274683WAUKEGAN ;8U
Adder
27.432
971277AH1-098 GEN
Solar/Wind Harmer
3.633
274888KELLY CRK;1U
Solar/Wind Harmer
0.529
276776AD2-060 GEN
Solar/Wind Harmer
0.968
958011AF2-095 GEN
Solar/Wind Harmer
13.073
970941AG2-585 GEN
Solar/Wind Harmer
4.993
23585401KL_K28_T16
Solar/Wind Helper
1.54
237043AE2-125 C
Solar/Wind Helper
0.209
23751201ROTHROCK
Solar/Wind Helper
0.884
235054AD2-180 GEN
Solar/Wind Helper
2.046
238117U2-030
Solar/Wind Helper
0.345
235531U2-073 GEN
Solar/Wind Helper
3.281
962101AG1-054 GEN
Solar/Wind Helper
0.72
254304AE2-114 C
Solar/Wind Helper
0.241
254305AE2-115 C
Solar/Wind Helper
0.241
20083426SW_E13_K22
Solar/Wind Helper
0.064
241967AE2-285_GEN
Solar/Wind Helper
0.7
241801AE1-079 GEN
Solar/Wind Helper
0.274
946071AF1-272 GEN
Solar/Wind Helper
3.071
20088826HIGHLAND
Solar/Wind Helper
1.019
203961AE2-224 GEN
Solar/Wind Helper
2.731
203818AF1-086 GEN
Solar/Wind Helper
1.901
203853AF1-134 C O1
Solar/Wind Helper
0.537
946381AF1-302 GEN
Solar/Wind Helper
0.248
203946AE2-131 C
Solar/Wind Helper
0.533
203954AE2-126 C
Solar/Wind Helper
0.526
940863AE2-074 GEN
Solar/Wind Helper
0.508
203804AE2-113_GEN
Solar/Wind Helper
1.942
946751AF1-339 GEN
Solar/Wind Helper
0.504
961431AF2-434 GEN
Solar/Wind Helper
0.502
316097T157 G90
Solar/Wind Helper
1.163
203835AF1-098 GEN
Solar/Wind Helper
1.976
20674828DL_W4-046
Solar/Wind Helper
0.009
20675928HOL_W4-097
Solar/Wind Helper
0.055
207471AF2-354 C
Solar/Wind Helper
0.185
20674328GAR_V4-001
Solar/Wind Helper
0.025
217204WCALDSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217081WEATEXAS C
Solar/Wind Helper
0.014
20675428EAM_W2-061
Solar/Wind Helper
0.017
218438BLK ROCK C
Solar/Wind Helper
0.029
20742028HF_AC1-207
Solar/Wind Helper
0.152
20714828MDF_W3-079
Solar/Wind Helper
0.14
207459AE1-142 C O1
Solar/Wind Helper
0.312
20720828JCB_W4-025
Solar/Wind Helper
0.068
214067T20SOLAR
Solar/Wind Helper
0.012
219607WPEMNERT C
Solar/Wind Helper
0.085
219304NAMERICA C
Solar/Wind Helper
0.14
219906AC1-017 C
Solar/Wind Helper
0.045
219272CLEANLIGHT C
Solar/Wind Helper
0.027
219912AD2-042 GEN
Solar/Wind Helper
0.159
219904AC1-010 C
Solar/Wind Helper
0.064
228754AB1-001 C
Solar/Wind Helper
0.028
230433AD2-135 GEN
Solar/Wind Helper
0.018
230511AF1-262
Solar/Wind Helper
0.016
233952AC2-187 GEN
Solar/Wind Helper
0.242
233954AC2-188 GEN
Solar/Wind Helper
0.242
232410W1-006 C
Solar/Wind Helper
0.528
234015AF2-250 C
Solar/Wind Helper
0.04
233946AB2-136 GEN
Solar/Wind Helper
0.592
233994AC2-023 GEN
Solar/Wind Helper
1.001
232428Y3-058 C
Solar/Wind Helper
0.352
234036AF2-325 C
Solar/Wind Helper
0.044
232424Y1-079 C
Solar/Wind Helper
0.121
232436AB1-176 C
Solar/Wind Helper
0.046
233982AB2-133 GEN
Solar/Wind Helper
0.374
233930AB2-032 GEN
Solar/Wind Helper
0.396
235062AE1-101 C1
Solar/Wind Helper
1.478
237080AD1-060 GEN
Solar/Wind Helper
0.299
235020AA1-095 C
Solar/Wind Helper
0.045
238221AF1-254 C O1
Solar/Wind Helper
0.238
237006AB1-125 GEN
Solar/Wind Helper
0.11
223401AF1-299 GEN
Solar/Wind Helper
0.341
223402AF1-300 C
Solar/Wind Helper
0.341
24289405MTG1
50/50
11.336
24318705GVG2
50/50
11.565
24722005FLATG5
50/50
2.758
24721905FLATG4
50/50
50.371
24686405CER G5
Adder
15.429
962771AG1-126 GEN
Solar/Wind Harmer
46.005
970153AG2-106 GEN
Solar/Wind Harmer
29.378
971191AH1-055 GEN
Solar/Wind Harmer
29.882
972103AH1-617 GEN
Solar/Wind Harmer
21.74
960911AF2-382 GEN
Solar/Wind Harmer
7.999
971461AH1-227 GEN
Solar/Wind Harmer
5.44
270367AC2-061_GEN
Solar/Wind Harmer
0
270186AC1-089 GEN
Solar/Wind Harmer
0
970879AG2-548 GEN
Solar/Wind Harmer
7.453
972167AH1-666 GEN
Solar/Wind Harmer
8.106
252507AC2-088 GEN
Solar/Wind Harmer
0.453
958171AF2-111 GEN
Solar/Wind Harmer
25.009
252519AF1-045_GEN
Solar/Wind Harmer
5.2
25196008MFTGT1
Adder
1.918
25194608D.CRK4
Adder
2.336
25196608WSDLE5
Adder
12.162
3429391JKCT 9G
Adder
11.809
970093AG2-073 GEN
Solar/Wind Harmer
8.38
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
12.81
253394AE2-221_GEN
Solar/Wind Harmer
0.001
970455AG2-298 GEN
Solar/Wind Harmer
3.77
970653AG2-424 GEN
Solar/Wind Harmer
0.96
972273AH1-721 GEN
Adder
114.179
24728705AND G3
Adder
10.976
24728505AND G1
Adder
5.248
970193AG2-126 GEN
Solar/Wind Harmer
14.237
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
2.718
253371AE2-315 SEC2
Adder
2.57
270346AE1-212 GEN
Solar/Wind Harmer
8.358
247642Z2-115 C
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
1.035
270004AE1-209 GEN
Solar/Wind Harmer
2.038
970191AG2-125 GEN
Solar/Wind Harmer
2.419
970825AG2-519 GEN
Solar/Wind Harmer
7.074
946031AF1-268 GEN
Solar/Wind Harmer
8.922
24386205FR-12G C
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
9.325
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
13.91
942481AE2-261 GEN
Solar/Wind Harmer
27.692
957381AF2-032 GEN
Solar/Wind Harmer
2.099
971993AH1-541 GEN
Solar/Wind Harmer
4.271
943031AE2-326 GEN
Solar/Wind Harmer
4.803
965091AG1-374 GEN
Solar/Wind Harmer
27.602
959611AF2-252 GEN
Solar/Wind Harmer
3.067
944531AF1-118 GEN
Solar/Wind Harmer
41.107
964401AG1-302 GEN
Solar/Wind Harmer
0.001
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.304
970571AG2-364 GEN
Solar/Wind Harmer
18.217
253325AC1-069 GEN
Solar/Wind Harmer
0.01
276868AE1-113 GEN
Solar/Wind Harmer
1.82
274879MINONK ;1U
Solar/Wind Harmer
0.38
939351AE1-166 GEN
Solar/Wind Harmer
0
274772LINCOLN ;3U
Adder
11.001
970707AG2-453 GEN
Solar/Wind Harmer
29.702
943121AE2-341 GEN
Solar/Wind Harmer
15.239
943591AF1-030 GEN
Solar/Wind Harmer
10.134
274862TOP CROP ;2U
Solar/Wind Harmer
1.227
972259AH1-714 GEN
Adder
24.853
274855GSG-6 ;RU
Solar/Wind Harmer
0.332
274850MENDOTA H;RU
Solar/Wind Harmer
0.106
946671AF1-331 GEN
Solar/Wind Harmer
0.969
959091AF2-200 GEN
Solar/Wind Harmer
18.173
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
12.115
274767LEE CO EC;8U
Adder
11.973
965931AG1-462 GEN
Solar/Wind Harmer
23.167
274729ELWOOD EC;1P
Adder
21.404
274730ELWOOD EC;6P
Adder
21.404
274734ELWOOD EC;8P
Adder
21.404
274736ELWOOD EC;9P
Adder
21.404
971087AG2-675 GEN
Solar/Wind Harmer
4.845
274682WAUKEGAN ;7U
Adder
7.239
274887GEN-1.85
Solar/Wind Harmer
0.236
276843GEN-1.7
Solar/Wind Harmer
0.294
276806AD2-047 C O1
Solar/Wind Harmer
5.144
237048AF1-022 C
Solar/Wind Helper
0.231
237046AF1-021 C
Solar/Wind Helper
0.4
235058AG1-386 C
Solar/Wind Helper
0.518
23562501BACKB
Solar/Wind Helper
1.078
964991AG1-363 GEN
Solar/Wind Helper
4.441
202652Y1-033 WT C
Solar/Wind Helper
0.66
238127S14_GEN_2
Solar/Wind Helper
0.816
20092526R32
Solar/Wind Helper
1.32
238108AE1-109 GEN1
Solar/Wind Helper
0.103
238110AE1-109 GEN3
Solar/Wind Helper
0.103
20303426NA_O38_P22
Solar/Wind Helper
1.125
203993AD2-133_GEN1
Solar/Wind Helper
1.157
203854AF2-039 C
Solar/Wind Helper
0.357
20398826ARMNA MT
Solar/Wind Helper
1.668
941421AE2-139 GEN
Solar/Wind Helper
2.591
209137AF2-361 C
Solar/Wind Helper
1.545
946731AF1-337 GEN
Solar/Wind Helper
0.504
212507AE2-042_GEN
Solar/Wind Helper
1.784
961341AF2-425 GEN
Solar/Wind Helper
0.502
961301AF2-421 GEN
Solar/Wind Helper
0.5
963151AG1-164 GEN
Solar/Wind Helper
0.5
211065PSPA IPP
Solar/Wind Helper
0.169
24289405MTG1
50/50
11.336
243186AF1-051 GEN
50/50
12.477
24318705GVG2
50/50
11.565
24721805FLATG3
50/50
2.758
972203AH1-686 GEN
Adder
4.409
24723205RIVRG3
Adder
35.892
24686505CER G6
Adder
15.551
944971AF1-162 GEN
Solar/Wind Harmer
12.126
960001AF2-291 GEN
Solar/Wind Harmer
0
971403AH1-188 GEN
Solar/Wind Harmer
16.719
962761AG1-125 GEN
Solar/Wind Harmer
46.005
970149AG2-104 GEN
Solar/Wind Harmer
24.844
970155AG2-107 GEN
Solar/Wind Harmer
29.378
971687AH1-348 GEN
Solar/Wind Harmer
1.062
24728305BUCHG2
Adder
6.8
970091AG2-072 GEN
Adder
113.084
971073AG2-665 GEN
Solar/Wind Harmer
1.694
945681AF1-233 GEN
Solar/Wind Harmer
19.107
25196808ZIMRHP
Adder
108.598
252516AE2-318_GEN
Solar/Wind Harmer
11.165
252510AF1-249 C
Solar/Wind Harmer
0.075
25196008MFTGT1
Adder
1.98
25194608D.CRK4
Adder
2.336
3429241JKCT 3G
Adder
16.815
3429421JKCT 10G
Adder
11.809
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
9.854
24735205WLF2G2
Adder
8.041
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
970653AG2-424 GEN
Solar/Wind Harmer
4.631
970773AG2-487 GEN
Solar/Wind Harmer
1.693
270273AD2-016 GEN
Solar/Wind Harmer
0.98
24728605AND G2
Adder
5.248
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
6.957
253370AE2-315 SEC1
Adder
2.718
253371AE2-315 SEC2
Adder
2.57
276903AD2-071 C
Solar/Wind Harmer
10.535
963741AG1-226 GEN
Solar/Wind Harmer
22.28
964901AG1-354 GEN
Solar/Wind Harmer
14.121
270594AE1-207 GEN
Solar/Wind Harmer
10.536
270032AE2-172
Solar/Wind Harmer
6.271
270005AE1-210 C O1
Solar/Wind Harmer
2.038
970825AG2-519 GEN
Solar/Wind Harmer
3.334
25326309TAIT D
Adder
1.473
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
4.02
965911AG1-460 GEN
Solar/Wind Harmer
1.852
965651AG1-433 GEN
Solar/Wind Harmer
2.715
276621W2-048 GEN
Solar/Wind Harmer
0.463
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
11.546
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
12.866
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.925
958381AF2-132 GEN
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
6.831
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.358
270055AF2-134 C O1
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
27.326
971997AH1-543 GEN
Solar/Wind Harmer
4.779
253333AC1-068 GEN
Solar/Wind Harmer
0.01
276882AE2-255 GEN
Solar/Wind Harmer
1.062
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274773LINCOLN ;4U
Adder
11.001
274774LINCOLN ;5U
Adder
11.001
276805AD2-038 GEN
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.321
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0.001
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.477
274861TOP CROP ;1U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
7.28
274872LEEDK;1U
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
27.26
959081AF2-199 GEN
Solar/Wind Harmer
9.087
962781AG1-127 GEN
Solar/Wind Harmer
8.648
971067AG2-660 GEN
Solar/Wind Harmer
3.029
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
12.115
274766LEE CO EC;7U
Adder
11.973
274732ELWOOD EC;7P
Adder
21.404
274822ROCKFORD ;11
Adder
25.553
274674JOLIET 9 ;6U
Adder
20.046
970819AG2-516 GEN
Solar/Wind Harmer
10.9
238185AF2-356 C
Solar/Wind Helper
2.64
20089026BF_G21_K23
Solar/Wind Helper
0.545
238120AE2-309 GEN
Solar/Wind Helper
0.514
238126S14_GEN_1
Solar/Wind Helper
0.816
254303AC2-168 GEN
Solar/Wind Helper
0.175
241966AE1-183 GEN
Solar/Wind Helper
0.282
23751101LEADS_P59
Solar/Wind Helper
2.242
20084626FORWARD
Solar/Wind Helper
0.405
964201AG1-281 GEN
Solar/Wind Helper
0.548
20091526CHSTN_FL
Solar/Wind Helper
0.659
238109AE1-109 GEN2
Solar/Wind Helper
0.103
20090526Q36
Solar/Wind Helper
1.157
203952AE2-129 C
Solar/Wind Helper
0.533
203855AF2-088 C
Solar/Wind Helper
0.172
209071AE2-133 GEN
Solar/Wind Helper
0.092
946691AF1-333 GEN
Solar/Wind Helper
0.504
946741AF1-338 GEN
Solar/Wind Helper
0.504
961421AF2-433 GEN
Solar/Wind Helper
0.502
957921AF2-086 GEN
Solar/Wind Helper
0.497
20676428JCR_X2-075
Solar/Wind Helper
0.074
20676128MHD_W3-029
Solar/Wind Helper
0.104
20673828FLE_V3-070
Solar/Wind Helper
0.094
218526CNTRALGAS2 C
Solar/Wind Helper
0.174
20675528CPH_W2-050
Solar/Wind Helper
0.123
20720628TIN_W1-124
Solar/Wind Helper
0.205
219620RIDERU C
Solar/Wind Helper
0.001
207445AB1-138_GEN
Solar/Wind Helper
0.112
20715028HAN_X4-015
Solar/Wind Helper
0.061
20720728JCB_W1-129
Solar/Wind Helper
0.061
959381AF2-229 GEN
Solar/Wind Helper
0.367
20390526W1-045 C
Solar/Wind Helper
0.36
219615MILLCREEK C
Solar/Wind Helper
0.028
219258KINSLEYDEP C
Solar/Wind Helper
0.081
227927V4-067C
Solar/Wind Helper
0.011
230407AD2-065 C
Solar/Wind Helper
0.043
228728W1-130C
Solar/Wind Helper
0.057
230434AG1-499 GEN
Solar/Wind Helper
0.244
233901CHERRYDALE C
Solar/Wind Helper
0.242
233940AF2-379 C
Solar/Wind Helper
0.065
232432Z2-076 GEN
Solar/Wind Helper
0.07
205956AE1-196_GEN
Solar/Wind Helper
0.528
205943AE1-185 GEN
Solar/Wind Helper
0.528
233915AB1-141 GEN
Solar/Wind Helper
0.523
205917AD1-020 ES
Solar/Wind Helper
0.371
237025AB1-124 C
Solar/Wind Helper
0.147
237030AB1-096 C
Solar/Wind Helper
0.06
23779801AA1-109
Solar/Wind Helper
0.169
238169AE2-226 GEN1
Solar/Wind Helper
0.559
238170AE2-226 GEN2
Solar/Wind Helper
0.559
961331AF2-424 GEN
Solar/Wind Helper
0.502
208972BECR K09
Solar/Wind Helper
0.375
963161AG1-165 GEN
Solar/Wind Helper
0.5
316095T157 G97
Solar/Wind Helper
1.163
203830AF1-094 GEN
Solar/Wind Helper
0.499
203979AG1-198 GEN
Solar/Wind Helper
0.3
23583801GRNGAP
Solar/Wind Helper
4.315
211065PSPA IPP
Solar/Wind Helper
0.169
209116AE2-175 GEN
Solar/Wind Helper
1.985
961971AG1-040 GEN
Solar/Wind Helper
0.495
20671928W4-073
Solar/Wind Helper
0.099
20674128FR_U2-059
Solar/Wind Helper
0.004
207437AD2-070 GEN
Solar/Wind Helper
0.152
207511W3-106 GEN
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.089
217169METRODIV C
Solar/Wind Helper
0.004
217211CAMDEN ST C
Solar/Wind Helper
0.005
207442AE1-156 GEN
Solar/Wind Helper
0.354
20673728F2S_V4-070
Solar/Wind Helper
0.032
219249CENTRALDIV C
Solar/Wind Helper
0.011
217213AMBOY SO C
Solar/Wind Helper
0.031
205941AD2-115 GEN
Solar/Wind Helper
0.536
20716928W4-060COL
Solar/Wind Helper
0.056
219612MATRIX C
Solar/Wind Helper
0.026
207454AA2-184 E
Solar/Wind Helper
0.335
219918AC2-009 C
Solar/Wind Helper
0.001
20714928UPF_X1-085
Solar/Wind Helper
0.006
20715728PEM_W1-119
Solar/Wind Helper
0.103
959561AF2-247 GEN
Solar/Wind Helper
0.022
219688LUMSOLAR_S C
Solar/Wind Helper
0.042
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
218660EHAMPSOLAR C
Solar/Wind Helper
0.035
219291REEVESSOUT C
Solar/Wind Helper
0.012
219914AD2-027 C
Solar/Wind Helper
0.122
203947AF1-006 C
Solar/Wind Helper
0.532
219921AF1-264
Solar/Wind Helper
0.054
219623KINSLEYBEA C
Solar/Wind Helper
0.002
230415AB2-049 C
Solar/Wind Helper
0.032
233923SMA
Solar/Wind Helper
0.783
233997TMININ_4.2
Solar/Wind Helper
0.214
232406W1-004 FULL
Solar/Wind Helper
0.528
233950AC2-186 GEN
Solar/Wind Helper
0.121
232434Z2-077 GEN
Solar/Wind Helper
0.132
233964AF2-378 GEN
Solar/Wind Helper
0.043
237085AD2-009_GEN
Solar/Wind Helper
1.463
232417X3-008 C
Solar/Wind Helper
0.242
233987AB2-037 GEN
Solar/Wind Helper
2.439
232422X3-066 FULL
Solar/Wind Helper
0.119
233933AB2-153 GEN
Solar/Wind Helper
0.242
233935AB2-179 C
Solar/Wind Helper
1.32
235067AD1-061 GEN
Solar/Wind Helper
0.394
237038AE2-054 C
Solar/Wind Helper
0.24
237002AB1-128_GEN
Solar/Wind Helper
0.392
208835TUHI V3-051
Solar/Wind Helper
0.022
23777801MSM_W1-116
Solar/Wind Helper
0.101
970373AG2-245 GEN
Solar/Wind Harmer
16.807
207518AF1-320_GEN
Solar/Wind Helper
1.73
20675728RH_W2-091
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.033
203975AE1-071-GEN
Solar/Wind Helper
2.698
207484AF2-139 C O1
Solar/Wind Helper
0.093
20674928WA_W3-044
Solar/Wind Helper
0.108
20676228FRD_X1-012
Solar/Wind Helper
0.101
20674628WNG_W3-110
Solar/Wind Helper
0.098
20676328BVR_Y1-020
Solar/Wind Helper
0.03
207439AE1-081 C O1
Solar/Wind Helper
0.02
207530AG1-191 GEN
Solar/Wind Helper
0.073
20676728BRNX1-095
Solar/Wind Helper
0.032
217208PARK ELE C
Solar/Wind Helper
0.005
217209CENTRL HS C
Solar/Wind Helper
0.009
20671828STAW2-080
Solar/Wind Helper
0.029
20673628F1S_V4-069
Solar/Wind Helper
0.032
962511AG1-100 GEN
Solar/Wind Helper
0.492
219908AB1-139 C
Solar/Wind Helper
0.08
219919AE1-041 FULL
Solar/Wind Helper
0.004
218428ETC SOLAR C
Solar/Wind Helper
0.005
218524CNTRALGAS1 C
Solar/Wind Helper
0.174
218440SUMMTASSOC C
Solar/Wind Helper
0.018
20715228NPK_W1-113
Solar/Wind Helper
0.084
20720528MAN_W1-024
Solar/Wind Helper
0.031
219680HOPEWELLV C1
Solar/Wind Helper
0.003
963711AG1-223 GEN
Solar/Wind Helper
0.069
20714528FRN_Y2-051
Solar/Wind Helper
0.061
219276PARKLANDSO C
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.103
20716028EGP_W2-019
Solar/Wind Helper
0.02
219348LDSOLAR C
Solar/Wind Helper
0.122
219686LUMSOLAR_N C
Solar/Wind Helper
0.042
219907AC1-030 C
Solar/Wind Helper
0.036
219766PARADISE C
Solar/Wind Helper
0.058
228729W2-030 C
Solar/Wind Helper
0.117
233996TM1833_GEN
Solar/Wind Helper
0.214
233998TM1NIN_3.36
Solar/Wind Helper
0.214
232404W1-003 C
Solar/Wind Helper
0.528
232408W1-005 C
Solar/Wind Helper
0.528
232426Y1-080 FULL
Solar/Wind Helper
0.04
205932AD2-116_GEN
Solar/Wind Helper
0.528
233944AB2-135 GEN
Solar/Wind Helper
0.614
233918AB1-142 GEN
Solar/Wind Helper
0.523
235063AE1-101 C2
Solar/Wind Helper
1.478
205916AD1-020 GEN
Solar/Wind Helper
1.727
237001AB1-127_GEN
Solar/Wind Helper
0.391
23777901MDS_W4-102
Solar/Wind Helper
0.152
208835TUHI V3-051
Solar/Wind Helper
0.022
238175AF1-290_GEN
Solar/Wind Helper
0.127
CPLELTFEXP_CPLE->PJM
CLTF
6.482
CBM West 2LTFEXP_CBM-W2->PJM
CBM
172.282
NYPJM->LTFIMP_NY
CLTF
6.32
LGEELTFEXP_LGEE->PJM
CLTF
9.798
WECLTFEXP_WEC->PJM
CLTF
4.977
AG2-052LTFEXP_AG2-052->PJM
LTF
0.304
AH1-155LTFEXP_AH1-155->PJM
LTF
0.457
LAGNLTFEXP_LAGN->PJM
CLTF
24.73
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.035
TVALTFEXP_TVA->PJM
CLTF
12.563
CBM West 1LTFEXP_CBM-W1->PJM
CBM
169.306
CBM South 1LTFEXP_CBM-S1->PJM
CBM
48.33
MECLTFEXP_MEC->PJM
CLTF
21.831
SIGELTFEXP_SIGE->PJM
CLTF
0.725

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#17219_05GUERNSEY 765_A_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#17219_05GUERNSEY 765_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.72 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6225.55
MW Contribution:
33.97
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
2.774
957241AF2-018 GEN
Solar/Wind Harmer
7.761
270053AF1-130 C
Solar/Wind Harmer
31.012
270399AC1-101 GEN
Solar/Wind Harmer
7.341
270400AC1-102 GEN
Solar/Wind Harmer
7.341
970281AG2-184 GEN
Solar/Wind Harmer
33.013
971985AH1-537 GEN
Solar/Wind Harmer
28.037
941621AE2-160 GEN
Adder
5.08
962211AG1-066 GEN
Solar/Wind Harmer
3.683
971313AH1-133 GEN
Solar/Wind Harmer
8.881
972163AH1-664 GEN
Solar/Wind Harmer
14.676
972165AH1-665 GEN
Solar/Wind Harmer
11.741
24289405MTG1
50/50
11.396
24318705GVG2
50/50
11.631
24722005FLATG5
50/50
2.774
24721905FLATG4
50/50
50.672
24686405CER G5
Adder
15.544
270330AC1-082 GEN2
Solar/Wind Harmer
0.849
270329AC1-082 GEN1
Solar/Wind Harmer
0.849
962771AG1-126 GEN
Solar/Wind Harmer
55.006
970153AG2-106 GEN
Solar/Wind Harmer
23.985
971191AH1-055 GEN
Solar/Wind Harmer
31.424
957541AF2-048 GEN
Solar/Wind Harmer
2.499
972103AH1-617 GEN
Solar/Wind Harmer
31.441
960911AF2-382 GEN
Solar/Wind Harmer
11.571
971461AH1-227 GEN
Solar/Wind Harmer
7.869
270367AC2-061_GEN
Solar/Wind Harmer
4.734
270186AC1-089 GEN
Solar/Wind Harmer
9.096
970879AG2-548 GEN
Solar/Wind Harmer
11.766
972167AH1-666 GEN
Solar/Wind Harmer
11.731
252507AC2-088 GEN
Solar/Wind Harmer
2.611
958171AF2-111 GEN
Solar/Wind Harmer
36.196
339243AC2-075 GEN1
Solar/Wind Harmer
0.655
252519AF1-045_GEN
Solar/Wind Harmer
5.251
25196008MFTGT1
Adder
1.936
25194608D.CRK4
Adder
2.359
252524AE2-267 GEN
Solar/Wind Harmer
2.256
25196608WSDLE5
Adder
12.281
3429391JKCT 9G
Adder
11.925
970093AG2-073 GEN
Solar/Wind Harmer
7.582
253317AC1-085 GEN4
Solar/Wind Harmer
11.942
946181AF1-283 GEN
Solar/Wind Harmer
18.543
253394AE2-221_GEN
Solar/Wind Harmer
6.388
970455AG2-298 GEN
Solar/Wind Harmer
4.914
970653AG2-424 GEN
Solar/Wind Harmer
0.97
339206AE1-143 GEN
Solar/Wind Harmer
2.962
972273AH1-721 GEN
Adder
115.342
24728705AND G3
Adder
11.088
24728505AND G1
Adder
5.301
970193AG2-126 GEN
Solar/Wind Harmer
20.616
24379505HDWTR1G C
Solar/Wind Harmer
10.862
270240V3-007_GEN2
Solar/Wind Harmer
8.498
253303V4-073 C
Solar/Wind Harmer
0.159
253370AE2-315 SEC1
Adder
2.746
253371AE2-315 SEC2
Adder
2.597
270346AE1-212 GEN
Solar/Wind Harmer
12.332
247642Z2-115 C
Solar/Wind Harmer
0.087
965461AG1-414 GEN
Solar/Wind Harmer
3.09
970289AG2-191 GEN
Solar/Wind Harmer
1.046
270004AE1-209 GEN
Solar/Wind Harmer
7.445
970825AG2-519 GEN
Solar/Wind Harmer
7.662
946031AF1-268 GEN
Solar/Wind Harmer
11.269
24386205FR-12G C
Solar/Wind Harmer
5.816
960071AF2-298 GEN
Solar/Wind Harmer
2.052
339255AE2-071 GEN
Solar/Wind Harmer
1.586
339250AF1-203 GEN
Solar/Wind Harmer
0.817
339216AC1-074 GEN
Solar/Wind Harmer
2.418
25196108MFTGT2
Adder
2.204
243186AF1-051 GEN
50/50
12.548
24721705FLATG2
50/50
41.198
24723005RIVRG1
Adder
36.155
24723105RIVRG2
Adder
36.155
927014AC1-188 GEN
Solar/Wind Harmer
2.499
25196108MFTGT2
Adder
2.047
3429211JKCT 2G
Adder
16.761
25196408WSDLE3
Adder
12.643
25196308WSDLE2
Adder
12.533
25196208WSDLE1
Adder
12.501
25196708WSDLE6
Adder
12.47
25196508WSDLE4
Adder
12.156
24734705WLF1G3
Adder
8.239
24734805WLF1G4
Adder
8.239
24734905WLF1G5
Adder
8.239
253433AC1-085 GEN1
Solar/Wind Harmer
7.58
253432AC1-085 GEN2
Solar/Wind Harmer
0.381
270340AC2-060 GEN
Solar/Wind Harmer
4.299
253406AD2-031_GEN
Solar/Wind Harmer
1.814
270263AC1-001 GEN
Solar/Wind Harmer
1.479
270444AC2-157 GEN1
Solar/Wind Harmer
7.893
270445AC2-157 GEN2
Solar/Wind Harmer
7.893
270291AC1-194 GEN
Solar/Wind Harmer
7.194
24735105WLF2G1
Adder
8.122
270356AE2-297 GEN
Solar/Wind Harmer
6.397
971061AG2-657 GEN
Solar/Wind Harmer
12.414
253372AE2-315 SEC3
Adder
2.597
253372AE2-315 SEC3
Adder
2.597
25306009OHH W.
Adder
3.946
970289AG2-191 GEN
Solar/Wind Harmer
2.589
963841AG1-237 GEN
Solar/Wind Harmer
14.866
971029AG2-637 GEN
Solar/Wind Harmer
20.401
24386405FR-21G C
Solar/Wind Harmer
5.837
24387005FR-3G C
Solar/Wind Harmer
5.368
270543AE2-219 C
Solar/Wind Harmer
13.544
946581AF1-322 GEN
Solar/Wind Harmer
13.818
24691005MDL-2G C
Solar/Wind Harmer
4.994
945581AF1-223 GEN
Solar/Wind Harmer
6.119
247536S-71 GEN
Solar/Wind Harmer
5.458
964611AG1-324 GEN
Solar/Wind Harmer
5.25
270432AC2-029 GEN
Solar/Wind Harmer
9.42
944221AF1-090 GEN
Solar/Wind Harmer
14.705
961761AG1-017 GEN
Solar/Wind Harmer
0.575
24729505KEY G4
Adder
8.64
274775LINCOLN ;6U
Adder
11.119
274776LINCOLN ;7U
Adder
11.119
274777LINCOLN ;8U
Adder
11.119
274744AC1-111 GEN8
Adder
7.358
274746AC1-111 G10
Adder
7.358
972267AH1-718 GEN
Adder
5.481
274731ELWOOD EC;2P
Adder
21.634
274733ELWOOD EC;3P
Adder
21.634
274735ELWOOD EC;4P
Adder
21.634
274728ELWOOD EC;5P
Adder
21.634
274823ROCKFORD ;21
Adder
25.64
972228AH1-698 GEN2
Adder
4.874
972227AH1-698 GEN1
Adder
3.432
23750501ELLIOTTS
Solar/Wind Helper
0.784
23652301WDPWR_K20
Solar/Wind Helper
0.167
23750701CROSSCHOOL
Solar/Wind Helper
1.42
238118U2-030_1
Solar/Wind Helper
0.341
203955AF1-039 C O1
Solar/Wind Helper
0.43
20089126CSLMN_L13
Solar/Wind Helper
0.68
20089226LOOKOUT
Solar/Wind Helper
0.678
241997AF1-093 GEN
Solar/Wind Helper
0.278
241985AE1-237 GEN
Solar/Wind Helper
0.27
241982AE2-343 S C
Solar/Wind Helper
0.243
20088926STNY CRK
Solar/Wind Helper
0.922
203940AF1-140 C
Solar/Wind Helper
0.444
20094526CT_V3-030
Solar/Wind Helper
0.527
20088626ARWF_N39
Solar/Wind Helper
1.354
203846AF2-130 C
Solar/Wind Helper
0.494
20334926Z1-069 C
Solar/Wind Helper
1.481
200917MEHOOPANY_G
Solar/Wind Helper
2.413
209067AE2-060 GEN
Solar/Wind Helper
0.091
959431AF2-234 GEN
Solar/Wind Helper
0.993
964051AG1-259 GEN
Solar/Wind Helper
0.074
964061AG1-260 GEN
Solar/Wind Helper
0.074
959421AF2-233 GEN
Solar/Wind Helper
0.497
209054AE2-059 GEN
Solar/Wind Helper
0.09
209027LOR2_Q27
Solar/Wind Helper
1.157
212266LOR1
Solar/Wind Helper
0.337
209029WAYMART-WD
Solar/Wind Helper
0.93
961261AF2-417 GEN
Solar/Wind Helper
0.492
20675128HRM_W1-127
Solar/Wind Helper
0.032
207408W3-077 C
Solar/Wind Helper
0.091
964851AG1-348 GEN
Solar/Wind Helper
0.068
20676428JCR_X2-075
Solar/Wind Helper
0.073
20676128MHD_W3-029
Solar/Wind Helper
0.103
20673828FLE_V3-070
Solar/Wind Helper
0.093
218526CNTRALGAS2 C
Solar/Wind Helper
0.172
20675528CPH_W2-050
Solar/Wind Helper
0.121
20720628TIN_W1-124
Solar/Wind Helper
0.202
219620RIDERU C
Solar/Wind Helper
0.001
207445AB1-138_GEN
Solar/Wind Helper
0.111
20715028HAN_X4-015
Solar/Wind Helper
0.06
20720728JCB_W1-129
Solar/Wind Helper
0.06
959381AF2-229 GEN
Solar/Wind Helper
0.361
20390526W1-045 C
Solar/Wind Helper
0.355
219615MILLCREEK C
Solar/Wind Helper
0.028
219258KINSLEYDEP C
Solar/Wind Helper
0.08
227927V4-067C
Solar/Wind Helper
0.011
230407AD2-065 C
Solar/Wind Helper
0.042
228728W1-130C
Solar/Wind Helper
0.056
230434AG1-499 GEN
Solar/Wind Helper
0.24
232432Z2-076 GEN
Solar/Wind Helper
0.069
233901CHERRYDALE C
Solar/Wind Helper
0.239
233940AF2-379 C
Solar/Wind Helper
0.064
205956AE1-196_GEN
Solar/Wind Helper
0.52
205943AE1-185 GEN
Solar/Wind Helper
0.52
233915AB1-141 GEN
Solar/Wind Helper
0.515
205917AD1-020 ES
Solar/Wind Helper
0.366
237025AB1-124 C
Solar/Wind Helper
0.145
237030AB1-096 C
Solar/Wind Helper
0.059
23779801AA1-109
Solar/Wind Helper
0.167
238169AE2-226 GEN1
Solar/Wind Helper
0.55
238170AE2-226 GEN2
Solar/Wind Helper
0.55
970913AG2-568 GEN
Solar/Wind Harmer
10.718
971225AH1-072 GEN
Solar/Wind Harmer
3.068
971227AH1-073 GEN
Solar/Wind Harmer
3.068
24728205BUCHG1
Adder
6.863
962581AG1-107 GEN
Solar/Wind Harmer
7.459
961491AF2-440 GEN
Solar/Wind Harmer
3.1
971073AG2-665 GEN
Solar/Wind Harmer
11.766
970879AG2-548 GEN
Solar/Wind Harmer
1.71
252509AD1-136 GEN
Solar/Wind Harmer
0.373
972043AH1-570 GEN
Solar/Wind Harmer
3.62
972045AH1-571 GEN
Solar/Wind Harmer
2.896
25183208HLCRTG
Solar/Wind Harmer
8.737
971125AH1-004 GEN
Solar/Wind Harmer
5.746
970107AG2-081 GEN
Solar/Wind Harmer
4.31
25194408D.CRK1
Adder
10.853
25194508D.CRK3
Adder
2.029
942891AE2-308 GEN
Solar/Wind Harmer
14.341
253415AE1-040 GEN
Solar/Wind Harmer
1.586
964571AG1-320 GEN
Solar/Wind Harmer
11.455
270269AC2-059
Solar/Wind Harmer
12.928
24728805RICHG1
Adder
5.238
24728905RICHG2
Adder
5.238
945391AF1-204 GEN
Solar/Wind Harmer
19.154
926881AC1-175 GEN
Solar/Wind Harmer
7.667
253370AE2-315 SEC1
Adder
2.746
270383AD1-128 GEN
Solar/Wind Harmer
8.356
339231AF1-038_GEN
Solar/Wind Harmer
2.483
24725505WLD G2 C
Solar/Wind Harmer
5.437
24699105WLD G1 C
Solar/Wind Harmer
5.374
339236AF1-050_GEN
Solar/Wind Harmer
2.477
970241AG2-163 GEN
Solar/Wind Harmer
34.084
970291AG2-192 GEN
Solar/Wind Harmer
1.771
970291AG2-192 GEN
Solar/Wind Harmer
0.57
253349AC2-067 GEN
Solar/Wind Harmer
2.769
253400AC2-068 GEN
Solar/Wind Harmer
1.114
25322209TAIT E
Adder
13.248
25322209TAIT E
Adder
12.95
24387305FR-4G C
Solar/Wind Harmer
6.894
966841AG1-555 GEN
Solar/Wind Harmer
3.407
970883AG2-550 GEN
Solar/Wind Harmer
13.544
970885AG2-551 GEN
Solar/Wind Harmer
3.15
270180AB1-006 GEN1
Solar/Wind Harmer
9.713
24697605MDL-3G C
Solar/Wind Harmer
4.978
24755605MDL-5G
Solar/Wind Harmer
3.256
24697905MDL-4G C
Solar/Wind Harmer
3.099
270181AB1-006 GEN2
Solar/Wind Harmer
0.966
971485AH1-239 GEN
Solar/Wind Harmer
10.793
964781AG1-341 GEN
Solar/Wind Harmer
14.3
966021AG1-471 GEN
Solar/Wind Harmer
7.284
270031AE2-169
Solar/Wind Harmer
10.99
270599AE1-208 GEN
Solar/Wind Harmer
10.99
945421AF1-207 GEN
Solar/Wind Harmer
18.926
957841AF2-078 GEN
Solar/Wind Harmer
8.147
25326109MON D
Adder
1.772
964611AG1-324 GEN
Solar/Wind Harmer
0.704
247621Y3-024
Adder
0.324
270201AC2-176 GEN
Solar/Wind Harmer
6.903
274770LINCOLN ;1U
Adder
11.119
274771LINCOLN ;2U
Adder
11.119
274696ROCKY RD ;4P
Adder
15.001
274695ROCKY RD ;2P
Adder
14.655
274693ROCKY RD ;1P
Adder
14.51
274764LEE CO EC;5U
Adder
12.274
274765LEE CO EC;6U
Adder
12.274
274762LEE CO EC;3U
Adder
12.246
274763LEE CO EC;4U
Adder
12.13
274697ROCKY RD ;3P
Adder
3.981
274674JOLIET 9 ;6U
Adder
20.261
972235AH1-702 GEN1
Adder
3.317
972236AH1-702 GEN2
Adder
2.884
23585401KL_K28_T16
Solar/Wind Helper
1.522
237043AE2-125 C
Solar/Wind Helper
0.207
23751201ROTHROCK
Solar/Wind Helper
0.874
235054AD2-180 GEN
Solar/Wind Helper
2.021
238117U2-030
Solar/Wind Helper
0.341
235531U2-073 GEN
Solar/Wind Helper
3.241
962101AG1-054 GEN
Solar/Wind Helper
0.711
254304AE2-114 C
Solar/Wind Helper
0.238
254305AE2-115 C
Solar/Wind Helper
0.238
20083426SW_E13_K22
Solar/Wind Helper
0.063
241967AE2-285_GEN
Solar/Wind Helper
0.691
241801AE1-079 GEN
Solar/Wind Helper
0.27
946071AF1-272 GEN
Solar/Wind Helper
3.032
20088826HIGHLAND
Solar/Wind Helper
1.005
203961AE2-224 GEN
Solar/Wind Helper
2.695
203818AF1-086 GEN
Solar/Wind Helper
1.876
203853AF1-134 C O1
Solar/Wind Helper
0.53
946381AF1-302 GEN
Solar/Wind Helper
0.245
203946AE2-131 C
Solar/Wind Helper
0.526
203954AE2-126 C
Solar/Wind Helper
0.519
940863AE2-074 GEN
Solar/Wind Helper
0.501
203804AE2-113_GEN
Solar/Wind Helper
1.916
946751AF1-339 GEN
Solar/Wind Helper
0.496
961431AF2-434 GEN
Solar/Wind Helper
0.495
316097T157 G90
Solar/Wind Helper
1.146
203835AF1-098 GEN
Solar/Wind Helper
1.948
207471AF2-354 C
Solar/Wind Helper
0.183
20674828DL_W4-046
Solar/Wind Helper
0.009
20675928HOL_W4-097
Solar/Wind Helper
0.054
20674328GAR_V4-001
Solar/Wind Helper
0.024
217204WCALDSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217081WEATEXAS C
Solar/Wind Helper
0.014
20675428EAM_W2-061
Solar/Wind Helper
0.017
218438BLK ROCK C
Solar/Wind Helper
0.029
20742028HF_AC1-207
Solar/Wind Helper
0.15
20714828MDF_W3-079
Solar/Wind Helper
0.138
207459AE1-142 C O1
Solar/Wind Helper
0.307
20720828JCB_W4-025
Solar/Wind Helper
0.067
214067T20SOLAR
Solar/Wind Helper
0.012
219607WPEMNERT C
Solar/Wind Helper
0.084
219304NAMERICA C
Solar/Wind Helper
0.138
219906AC1-017 C
Solar/Wind Helper
0.044
219272CLEANLIGHT C
Solar/Wind Helper
0.027
219912AD2-042 GEN
Solar/Wind Helper
0.157
219904AC1-010 C
Solar/Wind Helper
0.063
228754AB1-001 C
Solar/Wind Helper
0.027
230433AD2-135 GEN
Solar/Wind Helper
0.018
230511AF1-262
Solar/Wind Helper
0.015
233952AC2-187 GEN
Solar/Wind Helper
0.239
233954AC2-188 GEN
Solar/Wind Helper
0.239
233994AC2-023 GEN
Solar/Wind Helper
0.986
232410W1-006 C
Solar/Wind Helper
0.52
232428Y3-058 C
Solar/Wind Helper
0.347
234015AF2-250 C
Solar/Wind Helper
0.039
233946AB2-136 GEN
Solar/Wind Helper
0.583
234036AF2-325 C
Solar/Wind Helper
0.043
232424Y1-079 C
Solar/Wind Helper
0.119
233982AB2-133 GEN
Solar/Wind Helper
0.368
24289405MTG1
50/50
11.396
243186AF1-051 GEN
50/50
12.548
24318705GVG2
50/50
11.631
24721805FLATG3
50/50
2.774
972203AH1-686 GEN
Adder
4.442
24723205RIVRG3
Adder
36.155
24686505CER G6
Adder
15.668
270331AC1-082 GEN3
Solar/Wind Harmer
0.851
944971AF1-162 GEN
Solar/Wind Harmer
12.224
960001AF2-291 GEN
Solar/Wind Harmer
5.265
971403AH1-188 GEN
Solar/Wind Harmer
24.159
962761AG1-125 GEN
Solar/Wind Harmer
55.006
970149AG2-104 GEN
Solar/Wind Harmer
33.966
970155AG2-107 GEN
Solar/Wind Harmer
23.985
971687AH1-348 GEN
Solar/Wind Harmer
1.536
24728305BUCHG2
Adder
6.863
970091AG2-072 GEN
Adder
114.157
971073AG2-665 GEN
Solar/Wind Harmer
1.71
945681AF1-233 GEN
Solar/Wind Harmer
27.651
339221AD2-048_GEN
Solar/Wind Harmer
2.223
25196808ZIMRHP
Adder
109.659
252516AE2-318_GEN
Solar/Wind Harmer
14.428
252510AF1-249 C
Solar/Wind Harmer
0.6
25196008MFTGT1
Adder
1.999
943111AE2-339 GEN
Solar/Wind Harmer
1.269
25194608D.CRK4
Adder
2.359
3429241JKCT 3G
Adder
16.981
3429421JKCT 10G
Adder
11.925
253316AC1-085 GEN3
Solar/Wind Harmer
11.942
946171AF1-282 GEN
Solar/Wind Harmer
14.264
339211AE2-254 GEN
Solar/Wind Harmer
2.136
24735205WLF2G2
Adder
8.122
253398AE2-221_GEN2
Solar/Wind Harmer
6.388
270222AC2-111 GEN
Solar/Wind Harmer
6.219
944031AF1-071 GEN
Solar/Wind Harmer
1.399
970653AG2-424 GEN
Solar/Wind Harmer
6.706
270273AD2-016 GEN
Solar/Wind Harmer
3.685
24728605AND G2
Adder
5.301
339241AF1-083 GEN
Solar/Wind Harmer
2.292
942081AE2-220 GEN
Solar/Wind Harmer
8.785
270209AC1-174_GEN
Solar/Wind Harmer
5.591
270437AC2-090 C
Solar/Wind Harmer
7.667
270239V3-007_GEN1
Solar/Wind Harmer
2.364
253370AE2-315 SEC1
Adder
2.746
253371AE2-315 SEC2
Adder
2.597
276903AD2-071 C
Solar/Wind Harmer
13.662
963741AG1-226 GEN
Solar/Wind Harmer
61.351
964901AG1-354 GEN
Solar/Wind Harmer
20.45
270594AE1-207 GEN
Solar/Wind Harmer
18.503
270032AE2-172
Solar/Wind Harmer
6.337
270005AE1-210 C O1
Solar/Wind Harmer
7.445
970825AG2-519 GEN
Solar/Wind Harmer
2.854
25326309TAIT D
Adder
1.488
24385905FR-11G C
Solar/Wind Harmer
11.279
24386605FR-22G C
Solar/Wind Harmer
5.837
24791305MDL-5G
Solar/Wind Harmer
3.256
945371AF1-202 GEN
Solar/Wind Harmer
9.414
958861AF2-177 GEN
Solar/Wind Harmer
14.687
274773LINCOLN ;4U
Adder
11.119
274774LINCOLN ;5U
Adder
11.119
274745AC1-111 GEN9
Adder
7.358
274761LEE CO EC;2U
Adder
12.246
274766LEE CO EC;7U
Adder
12.101
274732ELWOOD EC;7P
Adder
21.634
274822ROCKFORD ;11
Adder
25.827
274674JOLIET 9 ;6U
Adder
20.261
274682WAUKEGAN ;7U
Adder
11.397
238185AF2-356 C
Solar/Wind Helper
2.609
20089026BF_G21_K23
Solar/Wind Helper
0.538
238120AE2-309 GEN
Solar/Wind Helper
0.508
238126S14_GEN_1
Solar/Wind Helper
0.805
254303AC2-168 GEN
Solar/Wind Helper
0.172
241966AE1-183 GEN
Solar/Wind Helper
0.278
23751101LEADS_P59
Solar/Wind Helper
2.213
20084626FORWARD
Solar/Wind Helper
0.4
964201AG1-281 GEN
Solar/Wind Helper
0.541
20091526CHSTN_FL
Solar/Wind Helper
0.651
238109AE1-109 GEN2
Solar/Wind Helper
0.102
20090526Q36
Solar/Wind Helper
1.142
203952AE2-129 C
Solar/Wind Helper
0.526
203855AF2-088 C
Solar/Wind Helper
0.169
209071AE2-133 GEN
Solar/Wind Helper
0.09
946691AF1-333 GEN
Solar/Wind Helper
0.496
946741AF1-338 GEN
Solar/Wind Helper
0.496
961421AF2-433 GEN
Solar/Wind Helper
0.495
957921AF2-086 GEN
Solar/Wind Helper
0.49
961331AF2-424 GEN
Solar/Wind Helper
0.495
208972BECR K09
Solar/Wind Helper
0.37
963161AG1-165 GEN
Solar/Wind Helper
0.492
203830AF1-094 GEN
Solar/Wind Helper
0.492
203979AG1-198 GEN
Solar/Wind Helper
0.295
316095T157 G97
Solar/Wind Helper
1.146
23583801GRNGAP
Solar/Wind Helper
4.253
211065PSPA IPP
Solar/Wind Helper
0.167
209116AE2-175 GEN
Solar/Wind Helper
1.956
961971AG1-040 GEN
Solar/Wind Helper
0.488
20674128FR_U2-059
Solar/Wind Helper
0.004
20671928W4-073
Solar/Wind Helper
0.097
207437AD2-070 GEN
Solar/Wind Helper
0.149
207511W3-106 GEN
Solar/Wind Helper
0.029
207510AF2-138 C
Solar/Wind Helper
0.088
217169METRODIV C
Solar/Wind Helper
0.004
217211CAMDEN ST C
Solar/Wind Helper
0.005
207442AE1-156 GEN
Solar/Wind Helper
0.349
20673728F2S_V4-070
Solar/Wind Helper
0.032
217213AMBOY SO C
Solar/Wind Helper
0.031
219249CENTRALDIV C
Solar/Wind Helper
0.011
205941AD2-115 GEN
Solar/Wind Helper
0.528
20716928W4-060COL
Solar/Wind Helper
0.055
219612MATRIX C
Solar/Wind Helper
0.025
207454AA2-184 E
Solar/Wind Helper
0.33
219918AC2-009 C
Solar/Wind Helper
0.001
20714928UPF_X1-085
Solar/Wind Helper
0.005
20715728PEM_W1-119
Solar/Wind Helper
0.101
959561AF2-247 GEN
Solar/Wind Helper
0.022
219688LUMSOLAR_S C
Solar/Wind Helper
0.042
218660EHAMPSOLAR C
Solar/Wind Helper
0.035
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219291REEVESSOUT C
Solar/Wind Helper
0.012
219914AD2-027 C
Solar/Wind Helper
0.12
219921AF1-264
Solar/Wind Helper
0.054
203947AF1-006 C
Solar/Wind Helper
0.524
219623KINSLEYBEA C
Solar/Wind Helper
0.002
230415AB2-049 C
Solar/Wind Helper
0.032
233950AC2-186 GEN
Solar/Wind Helper
0.119
232434Z2-077 GEN
Solar/Wind Helper
0.13
233923SMA
Solar/Wind Helper
0.772
233997TMININ_4.2
Solar/Wind Helper
0.21
232406W1-004 FULL
Solar/Wind Helper
0.52
232417X3-008 C
Solar/Wind Helper
0.239
233964AF2-378 GEN
Solar/Wind Helper
0.043
237085AD2-009_GEN
Solar/Wind Helper
1.442
233987AB2-037 GEN
Solar/Wind Helper
2.403
233933AB2-153 GEN
Solar/Wind Helper
0.238
232422X3-066 FULL
Solar/Wind Helper
0.117
233935AB2-179 C
Solar/Wind Helper
1.3
235067AD1-061 GEN
Solar/Wind Helper
0.388
237038AE2-054 C
Solar/Wind Helper
0.237
237002AB1-128_GEN
Solar/Wind Helper
0.386
208835TUHI V3-051
Solar/Wind Helper
0.021
23777801MSM_W1-116
Solar/Wind Helper
0.099
233930AB2-032 GEN
Solar/Wind Helper
0.39
232436AB1-176 C
Solar/Wind Helper
0.046
235062AE1-101 C1
Solar/Wind Helper
1.456
237080AD1-060 GEN
Solar/Wind Helper
0.295
235020AA1-095 C
Solar/Wind Helper
0.045
238221AF1-254 C O1
Solar/Wind Helper
0.235
237006AB1-125 GEN
Solar/Wind Helper
0.109
223401AF1-299 GEN
Solar/Wind Helper
0.336
223402AF1-300 C
Solar/Wind Helper
0.336
24690905MDL-1G C
Solar/Wind Harmer
10.842
970781AG2-491 GEN
Solar/Wind Harmer
13.505
962031AG1-047 GEN
Solar/Wind Harmer
4.061
274772LINCOLN ;3U
Adder
11.119
972259AH1-714 GEN
Adder
25.12
274760LEE CO EC;1U
Adder
12.246
274767LEE CO EC;8U
Adder
12.101
274729ELWOOD EC;1P
Adder
21.634
274730ELWOOD EC;6P
Adder
21.634
274734ELWOOD EC;8P
Adder
21.634
274736ELWOOD EC;9P
Adder
21.634
274682WAUKEGAN ;7U
Adder
23.647
237048AF1-022 C
Solar/Wind Helper
0.229
237046AF1-021 C
Solar/Wind Helper
0.396
235058AG1-386 C
Solar/Wind Helper
0.512
23562501BACKB
Solar/Wind Helper
1.065
964991AG1-363 GEN
Solar/Wind Helper
4.388
202652Y1-033 WT C
Solar/Wind Helper
0.652
238127S14_GEN_2
Solar/Wind Helper
0.805
20092526R32
Solar/Wind Helper
1.303
238108AE1-109 GEN1
Solar/Wind Helper
0.102
238110AE1-109 GEN3
Solar/Wind Helper
0.102
20303426NA_O38_P22
Solar/Wind Helper
1.11
203993AD2-133_GEN1
Solar/Wind Helper
1.142
203854AF2-039 C
Solar/Wind Helper
0.352
20398826ARMNA MT
Solar/Wind Helper
1.645
941421AE2-139 GEN
Solar/Wind Helper
2.555
209137AF2-361 C
Solar/Wind Helper
1.523
946731AF1-337 GEN
Solar/Wind Helper
0.496
212507AE2-042_GEN
Solar/Wind Helper
1.759
961341AF2-425 GEN
Solar/Wind Helper
0.495
961301AF2-421 GEN
Solar/Wind Helper
0.492
963151AG1-164 GEN
Solar/Wind Helper
0.492
211065PSPA IPP
Solar/Wind Helper
0.167
207518AF1-320_GEN
Solar/Wind Helper
1.705
20675728RH_W2-091
Solar/Wind Helper
0.089
20675828AU_W4-064
Solar/Wind Helper
0.032
203975AE1-071-GEN
Solar/Wind Helper
2.659
207484AF2-139 C O1
Solar/Wind Helper
0.091
20674928WA_W3-044
Solar/Wind Helper
0.107
20676228FRD_X1-012
Solar/Wind Helper
0.1
20674628WNG_W3-110
Solar/Wind Helper
0.097
20676328BVR_Y1-020
Solar/Wind Helper
0.029
207530AG1-191 GEN
Solar/Wind Helper
0.072
207439AE1-081 C O1
Solar/Wind Helper
0.02
20676728BRNX1-095
Solar/Wind Helper
0.032
217208PARK ELE C
Solar/Wind Helper
0.005
217209CENTRL HS C
Solar/Wind Helper
0.009
20671828STAW2-080
Solar/Wind Helper
0.029
20673628F1S_V4-069
Solar/Wind Helper
0.032
962511AG1-100 GEN
Solar/Wind Helper
0.485
219908AB1-139 C
Solar/Wind Helper
0.079
219919AE1-041 FULL
Solar/Wind Helper
0.004
218428ETC SOLAR C
Solar/Wind Helper
0.005
218524CNTRALGAS1 C
Solar/Wind Helper
0.172
218440SUMMTASSOC C
Solar/Wind Helper
0.018
20715228NPK_W1-113
Solar/Wind Helper
0.083
20720528MAN_W1-024
Solar/Wind Helper
0.03
219680HOPEWELLV C1
Solar/Wind Helper
0.003
963711AG1-223 GEN
Solar/Wind Helper
0.068
20714528FRN_Y2-051
Solar/Wind Helper
0.06
219276PARKLANDSO C
Solar/Wind Helper
0.095
20715828PEM_W1-120
Solar/Wind Helper
0.101
20716028EGP_W2-019
Solar/Wind Helper
0.02
219348LDSOLAR C
Solar/Wind Helper
0.12
219686LUMSOLAR_N C
Solar/Wind Helper
0.042
219907AC1-030 C
Solar/Wind Helper
0.036
219766PARADISE C
Solar/Wind Helper
0.057
228729W2-030 C
Solar/Wind Helper
0.116
233996TM1833_GEN
Solar/Wind Helper
0.21
233998TM1NIN_3.36
Solar/Wind Helper
0.21
232404W1-003 C
Solar/Wind Helper
0.52
232408W1-005 C
Solar/Wind Helper
0.52
232426Y1-080 FULL
Solar/Wind Helper
0.04
205932AD2-116_GEN
Solar/Wind Helper
0.52
233944AB2-135 GEN
Solar/Wind Helper
0.605
233918AB1-142 GEN
Solar/Wind Helper
0.515
235063AE1-101 C2
Solar/Wind Helper
1.456
205916AD1-020 GEN
Solar/Wind Helper
1.701
237001AB1-127_GEN
Solar/Wind Helper
0.386
23777901MDS_W4-102
Solar/Wind Helper
0.149
208835TUHI V3-051
Solar/Wind Helper
0.021
238175AF1-290_GEN
Solar/Wind Helper
0.125
957741AF2-068 GEN
Solar/Wind Harmer
8.369
CPLELTFEXP_CPLE->PJM
CLTF
6.636
CBM West 2LTFEXP_CBM-W2->PJM
CBM
174.171
NYPJM->LTFIMP_NY
CLTF
6.23
LGEELTFEXP_LGEE->PJM
CLTF
9.895
WECLTFEXP_WEC->PJM
CLTF
5.031
AG2-052LTFEXP_AG2-052->PJM
LTF
0.308
AH1-155LTFEXP_AH1-155->PJM
LTF
0.462
LAGNLTFEXP_LAGN->PJM
CLTF
25.015
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.459
TVALTFEXP_TVA->PJM
CLTF
12.705
CBM West 1LTFEXP_CBM-W1->PJM
CBM
171.353
CBM South 1LTFEXP_CBM-S1->PJM
CBM
48.863
MECLTFEXP_MEC->PJM
CLTF
22.066
SIGELTFEXP_SIGE->PJM
CLTF
0.733

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7445_05MARYSV 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.96 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6183.32
MW Contribution:
56.64
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
3.326
957241AF2-018 GEN
Solar/Wind Harmer
8.033
270053AF1-130 C
Solar/Wind Harmer
32.096
270399AC1-101 GEN
Solar/Wind Harmer
7.582
270400AC1-102 GEN
Solar/Wind Harmer
7.582
941621AE2-160 GEN
Adder
5.453
971313AH1-133 GEN
Solar/Wind Harmer
9.358
970281AG2-184 GEN
Solar/Wind Harmer
32.451
971061AG2-657 GEN
Solar/Wind Harmer
13.518
24734705WLF1G3
Adder
8.32
24734805WLF1G4
Adder
8.32
24734905WLF1G5
Adder
8.32
962211AG1-066 GEN
Solar/Wind Harmer
3.487
966391AG1-508 GEN
Solar/Wind Harmer
4.969
24735105WLF2G1
Adder
8.13
971331AH1-145 GEN
Solar/Wind Harmer
12.844
971329AH1-144 GEN
Solar/Wind Harmer
8.204
971985AH1-537 GEN
Solar/Wind Harmer
23.127
971981AH1-535 GEN
Solar/Wind Harmer
12.746
270069AE2-166 C O1
Solar/Wind Harmer
10.572
3429211JKCT 2G
Adder
12.98
972163AH1-664 GEN
Solar/Wind Harmer
10.818
24289405MTG1
50/50
12.684
24721805FLATG3
50/50
3.326
243186AF1-051 GEN
50/50
14.291
24318705GVG2
50/50
13.247
962761AG1-125 GEN
Solar/Wind Harmer
91.718
970149AG2-104 GEN
Solar/Wind Harmer
56.636
970155AG2-107 GEN
Solar/Wind Harmer
39.993
24723205RIVRG3
Adder
37.759
972203AH1-686 GEN
Adder
4.539
24686505CER G6
Adder
16.11
944971AF1-162 GEN
Solar/Wind Harmer
12.651
971403AH1-188 GEN
Solar/Wind Harmer
25.286
270331AC1-082 GEN3
Solar/Wind Harmer
0.847
960001AF2-291 GEN
Solar/Wind Harmer
5.171
24728305BUCHG2
Adder
7.18
971687AH1-348 GEN
Solar/Wind Harmer
1.537
24735205WLF2G2
Adder
8.13
270336AE1-100 GEN
Solar/Wind Harmer
2.029
970091AG2-072 GEN
Adder
90.254
943811AF1-049 GEN
Solar/Wind Harmer
4.254
339211AE2-254 GEN
Solar/Wind Harmer
1.701
339241AF1-083 GEN
Solar/Wind Harmer
1.857
971073AG2-665 GEN
Solar/Wind Harmer
1.298
964901AG1-354 GEN
Solar/Wind Harmer
16.708
3429241JKCT 3G
Adder
13.15
970653AG2-424 GEN
Solar/Wind Harmer
5.33
3429421JKCT 10G
Adder
9.153
972165AH1-665 GEN
Solar/Wind Harmer
8.654
339216AC1-074 GEN
Solar/Wind Harmer
1.805
270444AC2-157 GEN1
Solar/Wind Harmer
5.93
270445AC2-157 GEN2
Solar/Wind Harmer
5.93
270291AC1-194 GEN
Solar/Wind Harmer
5.169
25196108MFTGT2
Adder
1.544
25196108MFTGT2
Adder
1.434
944221AF1-090 GEN
Solar/Wind Harmer
10.637
25196408WSDLE3
Adder
8.509
25196308WSDLE2
Adder
8.435
25196208WSDLE1
Adder
8.414
25196708WSDLE6
Adder
8.393
25196508WSDLE4
Adder
8.182
963841AG1-237 GEN
Solar/Wind Harmer
10.358
276763AC1-053 GEN1
Solar/Wind Harmer
3.74
276764AC1-053 GEN2
Solar/Wind Harmer
3.74
276668AB2-070 GEN1
Solar/Wind Harmer
2.091
276848AB2-070 GEN3
Solar/Wind Harmer
2.091
276849AB2-070 GEN2
Solar/Wind Harmer
2.091
270356AE2-297 GEN
Solar/Wind Harmer
4.331
24386405FR-21G C
Solar/Wind Harmer
4.038
24387005FR-3G C
Solar/Wind Harmer
3.714
274853TWINGROVE;U1
Solar/Wind Harmer
6.662
274854TWINGROVE;U2
Solar/Wind Harmer
6.522
946581AF1-322 GEN
Solar/Wind Harmer
9.458
24691005MDL-2G C
Solar/Wind Harmer
3.418
270197AD1-017 GEN1
Solar/Wind Harmer
1.417
276726Z2-087_GEN
Solar/Wind Harmer
7.262
959341AF2-225 GEN
Solar/Wind Harmer
13.777
972267AH1-718 GEN
Adder
3.77
274823ROCKFORD ;21
Adder
17.467
274744AC1-111 GEN8
Adder
4.935
274746AC1-111 G10
Adder
4.935
274728ELWOOD EC;5P
Adder
14.442
274731ELWOOD EC;2P
Adder
14.442
274733ELWOOD EC;3P
Adder
14.442
274735ELWOOD EC;4P
Adder
14.442
274675JOLIET 29;7U
Adder
26.921
274675JOLIET 29;7U
Adder
15.118
23750501ELLIOTTS
Solar/Wind Helper
0.617
23652301WDPWR_K20
Solar/Wind Helper
0.134
241997AF1-093 GEN
Solar/Wind Helper
0.235
241985AE1-237 GEN
Solar/Wind Helper
0.229
24721705FLATG2
50/50
49.394
243186AF1-051 GEN
50/50
14.291
24723005RIVRG1
Adder
37.759
24723105RIVRG2
Adder
37.759
970913AG2-568 GEN
Solar/Wind Harmer
11.514
24728205BUCHG1
Adder
7.18
971225AH1-072 GEN
Solar/Wind Harmer
3.076
971227AH1-073 GEN
Solar/Wind Harmer
3.076
270214AC2-123 GEN
Solar/Wind Harmer
3.345
971277AH1-098 GEN
Solar/Wind Harmer
5.707
270583AD2-179 GEN
Solar/Wind Harmer
13.318
927014AC1-188 GEN
Solar/Wind Harmer
2.104
966021AG1-471 GEN
Solar/Wind Harmer
6.141
339231AF1-038_GEN
Solar/Wind Harmer
2.061
971485AH1-239 GEN
Solar/Wind Harmer
9.077
942891AE2-308 GEN
Solar/Wind Harmer
11.161
971073AG2-665 GEN
Solar/Wind Harmer
8.927
970879AG2-548 GEN
Solar/Wind Harmer
1.298
339236AF1-050_GEN
Solar/Wind Harmer
2.021
964781AG1-341 GEN
Solar/Wind Harmer
11.789
964571AG1-320 GEN
Solar/Wind Harmer
8.983
972043AH1-570 GEN
Solar/Wind Harmer
2.731
972045AH1-571 GEN
Solar/Wind Harmer
2.185
971125AH1-004 GEN
Solar/Wind Harmer
4.363
970107AG2-081 GEN
Solar/Wind Harmer
3.272
962581AG1-107 GEN
Solar/Wind Harmer
5.294
961491AF2-440 GEN
Solar/Wind Harmer
2.2
252509AD1-136 GEN
Solar/Wind Harmer
0.26
945391AF1-204 GEN
Solar/Wind Harmer
13.723
25183208HLCRTG
Solar/Wind Harmer
5.886
25194408D.CRK1
Adder
7.34
25194508D.CRK3
Adder
1.372
276916AD2-100_GEN
Solar/Wind Harmer
20.233
276911AD2-131_GEN
Solar/Wind Harmer
4.089
970241AG2-163 GEN
Solar/Wind Harmer
23.902
276615X2-022 GEN
Solar/Wind Harmer
1.861
276838X2-022 GEN2
Solar/Wind Harmer
0.221
274880W4-005 GEN4
Solar/Wind Harmer
2.856
276174W4-005 GEN2
Solar/Wind Harmer
2.856
24387305FR-4G C
Solar/Wind Harmer
4.769
966841AG1-555 GEN
Solar/Wind Harmer
2.357
960611AF2-352 GEN
Solar/Wind Harmer
2.15
270180AB1-006 GEN1
Solar/Wind Harmer
6.648
24697605MDL-3G C
Solar/Wind Harmer
3.407
24755605MDL-5G
Solar/Wind Harmer
2.228
24697905MDL-4G C
Solar/Wind Harmer
2.121
270181AB1-006 GEN2
Solar/Wind Harmer
0.661
942111AE2-223 GEN
Solar/Wind Harmer
7.529
24728805RICHG1
Adder
3.447
24728905RICHG2
Adder
3.447
274764LEE CO EC;5U
Adder
8.413
274765LEE CO EC;6U
Adder
8.413
274762LEE CO EC;3U
Adder
8.393
274763LEE CO EC;4U
Adder
8.314
972235AH1-702 GEN1
Adder
2.262
972236AH1-702 GEN2
Adder
1.967
274683WAUKEGAN ;8U
Adder
18.687
274683WAUKEGAN ;8U
Adder
15.753
274696ROCKY RD ;4P
Adder
10.103
274695ROCKY RD ;2P
Adder
9.87
274693ROCKY RD ;1P
Adder
9.773
274697ROCKY RD ;3P
Adder
2.681
274674JOLIET 9 ;6U
Adder
13.524
237043AE2-125 C
Solar/Wind Helper
0.166
254304AE2-114 C
Solar/Wind Helper
0.201
254305AE2-115 C
Solar/Wind Helper
0.201
962101AG1-054 GEN
Solar/Wind Helper
0.598
241967AE2-285_GEN
Solar/Wind Helper
0.586
241801AE1-079 GEN
Solar/Wind Helper
0.229
23585401KL_K28_T16
Solar/Wind Helper
1.176
23751201ROTHROCK
Solar/Wind Helper
0.671
235054AD2-180 GEN
Solar/Wind Helper
1.553
238117U2-030
Solar/Wind Helper
0.261
946071AF1-272 GEN
Solar/Wind Helper
2.433
20083426SW_E13_K22
Solar/Wind Helper
0.05
945421AF1-207 GEN
Solar/Wind Harmer
3.217
943111AE2-339 GEN
Solar/Wind Harmer
0.965
339221AD2-048_GEN
Solar/Wind Harmer
1.667
945681AF1-233 GEN
Solar/Wind Harmer
20.299
25196008MFTGT1
Adder
1.401
25196808ZIMRHP
Adder
75.86
252516AE2-318_GEN
Solar/Wind Harmer
9.778
252510AF1-249 C
Solar/Wind Harmer
0.407
270173AC1-122 GEN
Solar/Wind Harmer
1.632
25194608D.CRK4
Adder
1.596
965911AG1-460 GEN
Solar/Wind Harmer
1.34
24728605AND G2
Adder
3.684
963741AG1-226 GEN
Solar/Wind Harmer
43.023
276621W2-048 GEN
Solar/Wind Harmer
5.925
276686W4-005 GEN3
Solar/Wind Harmer
2.856
24385905FR-11G C
Solar/Wind Harmer
7.803
24386605FR-22G C
Solar/Wind Harmer
4.038
24791305MDL-5G
Solar/Wind Harmer
2.228
270574AD1-017 GEN2
Solar/Wind Harmer
4.722
276655WTG1_EQ
Solar/Wind Harmer
8.017
276656WTG2_EQ
Solar/Wind Harmer
1.061
939741AE1-205 GEN
Solar/Wind Harmer
18.37
274761LEE CO EC;2U
Adder
8.393
274766LEE CO EC;7U
Adder
8.294
274822ROCKFORD ;11
Adder
17.595
274828WAUKEGAN ;BP
Adder
9.796
274682WAUKEGAN ;7U
Adder
15.93
274745AC1-111 GEN9
Adder
4.935
274732ELWOOD EC;7P
Adder
14.442
274674JOLIET 9 ;6U
Adder
13.524
274676JOLIET 29;8U
Adder
26.921
254303AC2-168 GEN
Solar/Wind Helper
0.145
241966AE1-183 GEN
Solar/Wind Helper
0.235
238185AF2-356 C
Solar/Wind Helper
2.008
20089026BF_G21_K23
Solar/Wind Helper
0.425
24289405MTG1
50/50
12.684
24722005FLATG5
50/50
3.326
24721905FLATG4
50/50
60.751
24318705GVG2
50/50
13.247
962771AG1-126 GEN
Solar/Wind Harmer
91.718
970153AG2-106 GEN
Solar/Wind Harmer
39.993
24686405CER G5
Adder
15.983
270330AC1-082 GEN2
Solar/Wind Harmer
0.845
270329AC1-082 GEN1
Solar/Wind Harmer
0.845
960911AF2-382 GEN
Solar/Wind Harmer
12.012
972103AH1-617 GEN
Solar/Wind Harmer
30.905
971461AH1-227 GEN
Solar/Wind Harmer
7.89
971191AH1-055 GEN
Solar/Wind Harmer
28.586
270346AE1-212 GEN
Solar/Wind Harmer
13.435
943031AE2-326 GEN
Solar/Wind Harmer
5.264
958121AF2-106 GEN
Solar/Wind Harmer
6.036
957541AF2-048 GEN
Solar/Wind Harmer
2.104
972273AH1-721 GEN
Adder
96.087
270030AE2-140 GEN
Solar/Wind Harmer
23
970093AG2-073 GEN
Solar/Wind Harmer
5.967
339206AE1-143 GEN
Solar/Wind Harmer
2.39
970879AG2-548 GEN
Solar/Wind Harmer
8.927
339255AE2-071 GEN
Solar/Wind Harmer
1.308
339250AF1-203 GEN
Solar/Wind Harmer
0.673
970653AG2-424 GEN
Solar/Wind Harmer
0.771
970455AG2-298 GEN
Solar/Wind Harmer
3.861
3429391JKCT 9G
Adder
9.153
270186AC1-089 GEN
Solar/Wind Harmer
6.641
339243AC2-075 GEN1
Solar/Wind Harmer
0.489
270367AC2-061_GEN
Solar/Wind Harmer
3.424
972167AH1-666 GEN
Solar/Wind Harmer
8.599
958171AF2-111 GEN
Solar/Wind Harmer
25.759
270018AE2-047 C O1
Solar/Wind Harmer
1.267
252507AC2-088 GEN
Solar/Wind Harmer
1.823
25196008MFTGT1
Adder
1.357
970193AG2-126 GEN
Solar/Wind Harmer
14.771
252519AF1-045_GEN
Solar/Wind Harmer
3.559
25194608D.CRK4
Adder
1.596
252524AE2-267 GEN
Solar/Wind Harmer
1.519
25196608WSDLE5
Adder
8.266
942481AE2-261 GEN
Solar/Wind Harmer
28.724
24728705AND G3
Adder
7.705
24728505AND G1
Adder
3.684
957381AF2-032 GEN
Solar/Wind Harmer
1.919
962751AG1-124 GEN
Solar/Wind Harmer
8.593
276785W4-005 GEN1
Solar/Wind Harmer
2.856
971993AH1-541 GEN
Solar/Wind Harmer
8.726
241982AE2-343 S C
Solar/Wind Helper
0.206
203955AF1-039 C O1
Solar/Wind Helper
0.338
23750701CROSSCHOOL
Solar/Wind Helper
1.086
20089126CSLMN_L13
Solar/Wind Helper
0.537
20089226LOOKOUT
Solar/Wind Helper
0.536
238118U2-030_1
Solar/Wind Helper
0.261
24386205FR-12G C
Solar/Wind Harmer
4.023
965091AG1-374 GEN
Solar/Wind Harmer
27.739
959611AF2-252 GEN
Solar/Wind Harmer
2.15
24690905MDL-1G C
Solar/Wind Harmer
7.42
970781AG2-491 GEN
Solar/Wind Harmer
9.243
274760LEE CO EC;1U
Adder
8.393
274767LEE CO EC;8U
Adder
8.294
274682WAUKEGAN ;7U
Adder
15.93
274729ELWOOD EC;1P
Adder
14.442
274730ELWOOD EC;6P
Adder
14.442
274734ELWOOD EC;8P
Adder
14.442
274736ELWOOD EC;9P
Adder
14.442
237048AF1-022 C
Solar/Wind Helper
0.181
237046AF1-021 C
Solar/Wind Helper
0.315
235058AG1-386 C
Solar/Wind Helper
0.425
202652Y1-033 WT C
Solar/Wind Helper
0.512
23562501BACKB
Solar/Wind Helper
0.816
964991AG1-363 GEN
Solar/Wind Helper
3.339
CPLELTFEXP_CPLE->PJM
CLTF
7.6
CBM West 2LTFEXP_CBM-W2->PJM
CBM
138.522
NYPJM->LTFIMP_NY
CLTF
4.806
LGEELTFEXP_LGEE->PJM
CLTF
7.592
WECLTFEXP_WEC->PJM
CLTF
3.434
AG2-052LTFEXP_AG2-052->PJM
LTF
0.205
AH1-155LTFEXP_AH1-155->PJM
LTF
0.307
LAGNLTFEXP_LAGN->PJM
CLTF
21.182
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.819
TVALTFEXP_TVA->PJM
CLTF
11.07
CBM West 1LTFEXP_CBM-W1->PJM
CBM
111.112
CBM South 1LTFEXP_CBM-S1->PJM
CBM
41.561
MECLTFEXP_MEC->PJM
CLTF
15.956
SIGELTFEXP_SIGE->PJM
CLTF
0.556

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:109.18 %
Rating:4558.0 MVA
Rating Type:A
MVA to Mitigate:4976.63
MW Contribution:
14.75
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
243186AF1-051 GEN
50/50
11.683
24721705FLATG2
50/50
36.759
24723005RIVRG1
Adder
32.69
24723105RIVRG2
Adder
32.69
970913AG2-568 GEN
Solar/Wind Harmer
8.105
24728205BUCHG1
Adder
6.196
971225AH1-072 GEN
Solar/Wind Harmer
1.885
971227AH1-073 GEN
Solar/Wind Harmer
1.885
971277AH1-098 GEN
Solar/Wind Harmer
3.388
971073AG2-665 GEN
Solar/Wind Harmer
5.846
970879AG2-548 GEN
Solar/Wind Harmer
1.329
270583AD2-179 GEN
Solar/Wind Harmer
7.872
962581AG1-107 GEN
Solar/Wind Harmer
0.001
942891AE2-308 GEN
Solar/Wind Harmer
7.677
972043AH1-570 GEN
Solar/Wind Harmer
1.99
972045AH1-571 GEN
Solar/Wind Harmer
1.594
971125AH1-004 GEN
Solar/Wind Harmer
3.042
970107AG2-081 GEN
Solar/Wind Harmer
2.281
966021AG1-471 GEN
Solar/Wind Harmer
4.034
252509AD1-136 GEN
Solar/Wind Harmer
0.037
971485AH1-239 GEN
Solar/Wind Harmer
5.968
964571AG1-320 GEN
Solar/Wind Harmer
6.787
964781AG1-341 GEN
Solar/Wind Harmer
7.81
25183208HLCRTG
Solar/Wind Harmer
0
971587AH1-292 GEN
Solar/Wind Harmer
5.311
25194408D.CRK1
Adder
7.827
25194508D.CRK3
Adder
1.463
24721605FLATG1
50/50
2.475
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
270053AF1-130 C
Solar/Wind Harmer
24.531
270399AC1-101 GEN
Solar/Wind Harmer
3.431
270400AC1-102 GEN
Solar/Wind Harmer
3.431
941621AE2-160 GEN
Adder
4.685
970281AG2-184 GEN
Solar/Wind Harmer
20.069
971313AH1-133 GEN
Solar/Wind Harmer
4.633
971061AG2-657 GEN
Solar/Wind Harmer
5.63
24734705WLF1G3
Adder
7.275
24734805WLF1G4
Adder
7.275
24734905WLF1G5
Adder
7.275
971985AH1-537 GEN
Solar/Wind Harmer
2.606
24735105WLF2G1
Adder
7.131
966391AG1-508 GEN
Solar/Wind Harmer
1.323
971331AH1-145 GEN
Solar/Wind Harmer
10.902
971329AH1-144 GEN
Solar/Wind Harmer
4.007
971981AH1-535 GEN
Solar/Wind Harmer
5.247
972163AH1-664 GEN
Solar/Wind Harmer
8.578
972165AH1-665 GEN
Solar/Wind Harmer
6.87
3429211JKCT 2G
Adder
12.836
339216AC1-074 GEN
Solar/Wind Harmer
0.202
270291AC1-194 GEN
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
7.253
24728805RICHG1
Adder
3.656
24728905RICHG2
Adder
3.656
970241AG2-163 GEN
Solar/Wind Harmer
3.886
276916AD2-100_GEN
Solar/Wind Harmer
13.944
276911AD2-131_GEN
Solar/Wind Harmer
0.919
926881AC1-175 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
0.068
276838X2-022 GEN2
Solar/Wind Harmer
0.37
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.743
270383AD1-128 GEN
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.844
970291AG2-192 GEN
Solar/Wind Harmer
0.389
971613AH1-306 GEN
Solar/Wind Harmer
3.113
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
270269AC2-059
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.145
253370AE2-315 SEC1
Adder
1.843
970883AG2-550 GEN
Solar/Wind Harmer
6.406
970885AG2-551 GEN
Solar/Wind Harmer
2.135
942111AE2-223 GEN
Solar/Wind Harmer
2.08
270031AE2-169
Solar/Wind Harmer
3.483
270599AE1-208 GEN
Solar/Wind Harmer
5.804
276645AC1-214 GEN1
Solar/Wind Harmer
0.248
964611AG1-324 GEN
Solar/Wind Harmer
0.475
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.019
247621Y3-024
Adder
0.218
270201AC2-176 GEN
Solar/Wind Harmer
0
25322209TAIT E
Adder
8.794
25322209TAIT E
Adder
8.596
274764LEE CO EC;5U
Adder
8.405
274765LEE CO EC;6U
Adder
8.405
274762LEE CO EC;3U
Adder
8.386
274763LEE CO EC;4U
Adder
8.307
938861AE1-114 GEN
Solar/Wind Harmer
3.56
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
2.263
972236AH1-702 GEN2
Adder
1.968
971341AH1-150 GEN
Solar/Wind Harmer
12.516
971343AH1-151 GEN
Solar/Wind Harmer
12.516
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.353
962691AG1-118 GEN
Solar/Wind Harmer
18.68
274683WAUKEGAN ;8U
Adder
18.772
274683WAUKEGAN ;8U
Adder
15.824
274696ROCKY RD ;4P
Adder
10.15
274695ROCKY RD ;2P
Adder
9.916
274693ROCKY RD ;1P
Adder
9.818
274697ROCKY RD ;3P
Adder
2.694
958481AF2-142 GEN
Solar/Wind Harmer
9.318
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
15.453
276893AG1-478 C
Solar/Wind Harmer
0.412
274674JOLIET 9 ;6U
Adder
13.632
944541AF1-119 GEN
Solar/Wind Harmer
0.412
960971AF2-388 GEN
Solar/Wind Harmer
3.621
274888KELLY CRK;1U
Solar/Wind Harmer
0.359
276776AD2-060 GEN
Solar/Wind Harmer
0.657
958011AF2-095 GEN
Solar/Wind Harmer
8.864
970941AG2-585 GEN
Solar/Wind Harmer
3.385
23585401KL_K28_T16
Solar/Wind Helper
1.157
237043AE2-125 C
Solar/Wind Helper
0.157
23751201ROTHROCK
Solar/Wind Helper
0.666
235054AD2-180 GEN
Solar/Wind Helper
1.531
25196108MFTGT2
Adder
1.606
25196108MFTGT2
Adder
1.492
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
25196408WSDLE3
Adder
9.098
25196308WSDLE2
Adder
9.019
25196208WSDLE1
Adder
8.997
25196708WSDLE6
Adder
8.974
25196508WSDLE4
Adder
8.748
253406AD2-031_GEN
Solar/Wind Harmer
0.516
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.692
270069AE2-166 C O1
Solar/Wind Harmer
6.22
270356AE2-297 GEN
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
3.926
963841AG1-237 GEN
Solar/Wind Harmer
2.866
24386405FR-21G C
Solar/Wind Harmer
0
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.257
276848AB2-070 GEN3
Solar/Wind Harmer
0.256
276849AB2-070 GEN2
Solar/Wind Harmer
0.257
970289AG2-191 GEN
Solar/Wind Harmer
1.233
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
9.69
274854TWINGROVE;U2
Solar/Wind Harmer
0
25306009OHH W.
Adder
2.654
253372AE2-315 SEC3
Adder
1.743
253372AE2-315 SEC3
Adder
1.743
270543AE2-219 C
Solar/Wind Harmer
4.484
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.721
247536S-71 GEN
Solar/Wind Harmer
0.254
971611AH1-305 GEN
Solar/Wind Harmer
3.778
946321AF1-296 GEN
Solar/Wind Harmer
3.554
274877BISHOP HL;1U
Solar/Wind Harmer
0.211
971609AH1-304 GEN
Solar/Wind Harmer
1.034
964611AG1-324 GEN
Solar/Wind Harmer
2.468
970169AG2-114 GEN
Solar/Wind Harmer
6.325
276741O09 GEN1
Solar/Wind Harmer
0.223
959141AF2-205 GEN
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
3.763
926823AC1-168 GEN
Solar/Wind Harmer
1.07
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
10.116
274856ECOGROVE ;U1
Solar/Wind Harmer
0.147
274823ROCKFORD ;21
Adder
17.485
971171AH1-044 GEN
Solar/Wind Harmer
12.516
276861AD2-134 GEN
Solar/Wind Harmer
0.111
276863AD2-134 GEN
Solar/Wind Harmer
0.111
971675AH1-338 GEN
Solar/Wind Harmer
2.437
971411AH1-196 GEN
Solar/Wind Harmer
9.369
970073AG2-061 GEN
Solar/Wind Harmer
2.078
274744AC1-111 GEN8
Adder
4.965
274746AC1-111 G10
Adder
4.965
970833AG2-524 GEN
Solar/Wind Harmer
6.809
970833AG2-524 GEN
Solar/Wind Harmer
4.54
274728ELWOOD EC;5P
Adder
14.558
274731ELWOOD EC;2P
Adder
14.558
274733ELWOOD EC;3P
Adder
14.558
274735ELWOOD EC;4P
Adder
14.558
274675JOLIET 29;7U
Adder
27.142
960591AF2-350 GEN
Solar/Wind Harmer
6.155
23750501ELLIOTTS
Solar/Wind Helper
0.598
23652301WDPWR_K20
Solar/Wind Helper
0.127
24289405MTG1
50/50
10.896
243186AF1-051 GEN
50/50
11.683
24318705GVG2
50/50
10.829
24721805FLATG3
50/50
2.475
24723205RIVRG3
Adder
32.69
972203AH1-686 GEN
Adder
3.965
24686505CER G6
Adder
14.074
944971AF1-162 GEN
Solar/Wind Harmer
10.992
971403AH1-188 GEN
Solar/Wind Harmer
15.251
960001AF2-291 GEN
Solar/Wind Harmer
0
24728305BUCHG2
Adder
6.196
971687AH1-348 GEN
Solar/Wind Harmer
0.943
24735205WLF2G2
Adder
7.131
971073AG2-665 GEN
Solar/Wind Harmer
1.329
970091AG2-072 GEN
Adder
86.562
945681AF1-233 GEN
Solar/Wind Harmer
14.491
3429241JKCT 3G
Adder
13.004
3429421JKCT 10G
Adder
9.095
970653AG2-424 GEN
Solar/Wind Harmer
3.596
964901AG1-354 GEN
Solar/Wind Harmer
11.126
25196808ZIMRHP
Adder
79.991
25196008MFTGT1
Adder
1.457
252516AE2-318_GEN
Solar/Wind Harmer
8.161
252510AF1-249 C
Solar/Wind Harmer
0.055
25194608D.CRK4
Adder
1.702
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.045
962761AG1-125 GEN
Solar/Wind Harmer
27.311
970149AG2-104 GEN
Solar/Wind Harmer
14.748
970155AG2-107 GEN
Solar/Wind Harmer
17.44
253398AE2-221_GEN2
Solar/Wind Harmer
0
24728605AND G2
Adder
3.745
970773AG2-487 GEN
Solar/Wind Harmer
1.199
963741AG1-226 GEN
Solar/Wind Harmer
15.765
965911AG1-460 GEN
Solar/Wind Harmer
1.325
943811AF1-049 GEN
Solar/Wind Harmer
0
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.832
276621W2-048 GEN
Solar/Wind Harmer
0.329
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.31
270594AE1-207 GEN
Solar/Wind Harmer
7.264
270032AE2-172
Solar/Wind Harmer
4.324
270273AD2-016 GEN
Solar/Wind Harmer
0.662
270005AE1-210 C O1
Solar/Wind Harmer
1.4
970825AG2-519 GEN
Solar/Wind Harmer
2.292
253370AE2-315 SEC1
Adder
1.843
253371AE2-315 SEC2
Adder
1.743
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
8.961
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
7.933
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.248
276708O09 GEN2
Solar/Wind Harmer
0.223
970569AG2-363 GEN
Solar/Wind Harmer
18.869
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.386
274766LEE CO EC;7U
Adder
8.287
25326309TAIT D
Adder
0.988
945371AF1-202 GEN
Solar/Wind Harmer
0
970819AG2-516 GEN
Solar/Wind Harmer
7.523
939401AE1-172 GEN
Solar/Wind Harmer
4.684
274822ROCKFORD ;11
Adder
17.613
957471AF2-041 GEN
Solar/Wind Harmer
18.774
959081AF2-199 GEN
Solar/Wind Harmer
6.258
971067AG2-660 GEN
Solar/Wind Harmer
2.086
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.135
971997AH1-543 GEN
Solar/Wind Harmer
3.283
958381AF2-132 GEN
Solar/Wind Harmer
0.001
276882AE2-255 GEN
Solar/Wind Harmer
0.729
276805AD2-038 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
5.929
274828WAUKEGAN ;BP
Adder
9.84
274682WAUKEGAN ;7U
Adder
16.004
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
2.692
276691AA1-018 GEN1
Solar/Wind Harmer
1.009
274745AC1-111 GEN9
Adder
4.965
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
14.558
274674JOLIET 9 ;6U
Adder
13.632
965651AG1-433 GEN
Solar/Wind Harmer
1.811
274676JOLIET 29;8U
Adder
9.572
238185AF2-356 C
Solar/Wind Helper
1.975
970373AG2-245 GEN
Solar/Wind Harmer
5.443
24289405MTG1
50/50
10.896
24318705GVG2
50/50
10.829
24722005FLATG5
50/50
2.475
24721905FLATG4
50/50
45.211
24686405CER G5
Adder
13.963
971191AH1-055 GEN
Solar/Wind Harmer
25.524
960911AF2-382 GEN
Solar/Wind Harmer
7.256
972103AH1-617 GEN
Solar/Wind Harmer
19.113
971461AH1-227 GEN
Solar/Wind Harmer
4.836
270346AE1-212 GEN
Solar/Wind Harmer
7.826
943031AE2-326 GEN
Solar/Wind Harmer
4.478
970879AG2-548 GEN
Solar/Wind Harmer
5.846
958121AF2-106 GEN
Solar/Wind Harmer
0
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
970093AG2-073 GEN
Solar/Wind Harmer
6.527
972167AH1-666 GEN
Solar/Wind Harmer
6.143
972273AH1-721 GEN
Adder
91.222
3429391JKCT 9G
Adder
9.095
970455AG2-298 GEN
Solar/Wind Harmer
2.913
958171AF2-111 GEN
Solar/Wind Harmer
18.695
252507AC2-088 GEN
Solar/Wind Harmer
0.336
970653AG2-424 GEN
Solar/Wind Harmer
0.745
25196008MFTGT1
Adder
1.411
252519AF1-045_GEN
Solar/Wind Harmer
3.801
25194608D.CRK4
Adder
1.702
25196608WSDLE5
Adder
8.838
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.158
962771AG1-126 GEN
Solar/Wind Harmer
27.311
970153AG2-106 GEN
Solar/Wind Harmer
17.44
253394AE2-221_GEN
Solar/Wind Harmer
0
970193AG2-126 GEN
Solar/Wind Harmer
10.239
24728705AND G3
Adder
7.833
24728505AND G1
Adder
3.745
270030AE2-140 GEN
Solar/Wind Harmer
13.518
942481AE2-261 GEN
Solar/Wind Harmer
19.808
957381AF2-032 GEN
Solar/Wind Harmer
1.5
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
3.022
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.714
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.48
270004AE1-209 GEN
Solar/Wind Harmer
1.4
970825AG2-519 GEN
Solar/Wind Harmer
4.865
965091AG1-374 GEN
Solar/Wind Harmer
19.301
946031AF1-268 GEN
Solar/Wind Harmer
6.123
959611AF2-252 GEN
Solar/Wind Harmer
2.145
253370AE2-315 SEC1
Adder
1.843
253371AE2-315 SEC2
Adder
1.743
970191AG2-125 GEN
Solar/Wind Harmer
1.638
965931AG1-462 GEN
Solar/Wind Harmer
16.203
971087AG2-675 GEN
Solar/Wind Harmer
3.389
274878BISHOP HL;2U
Solar/Wind Harmer
0.211
276782AC1-033 GEN
Solar/Wind Harmer
0
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.45
970571AG2-364 GEN
Solar/Wind Harmer
12.579
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
8.386
274767LEE CO EC;8U
Adder
8.287
959091AF2-200 GEN
Solar/Wind Harmer
12.516
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274855GSG-6 ;RU
Solar/Wind Harmer
0.228
274850MENDOTA H;RU
Solar/Wind Harmer
0.073
946671AF1-331 GEN
Solar/Wind Harmer
0.666
276868AE1-113 GEN
Solar/Wind Harmer
1.25
274879MINONK ;1U
Solar/Wind Harmer
0.261
274682WAUKEGAN ;7U
Adder
16.004
274862TOP CROP ;2U
Solar/Wind Harmer
0.839
943121AE2-341 GEN
Solar/Wind Harmer
10.39
943591AF1-030 GEN
Solar/Wind Harmer
6.91
939351AE1-166 GEN
Solar/Wind Harmer
0
274729ELWOOD EC;1P
Adder
14.558
274730ELWOOD EC;6P
Adder
14.558
274734ELWOOD EC;8P
Adder
14.558
274736ELWOOD EC;9P
Adder
14.558
970707AG2-453 GEN
Solar/Wind Harmer
20.15
274887GEN-1.85
Solar/Wind Harmer
0.16
276843GEN-1.7
Solar/Wind Harmer
0.199
276806AD2-047 C O1
Solar/Wind Harmer
3.488
237048AF1-022 C
Solar/Wind Helper
0.175
237046AF1-021 C
Solar/Wind Helper
0.301
235058AG1-386 C
Solar/Wind Helper
0.387
23562501BACKB
Solar/Wind Helper
0.811
CPLELTFEXP_CPLE->PJM
CLTF
6.32
CBM West 2LTFEXP_CBM-W2->PJM
CBM
132.098
NYPJM->LTFIMP_NY
CLTF
4.626
LGEELTFEXP_LGEE->PJM
CLTF
7.468
WECLTFEXP_WEC->PJM
CLTF
3.435
AG2-052LTFEXP_AG2-052->PJM
LTF
0.207
AH1-155LTFEXP_AH1-155->PJM
LTF
0.311
LAGNLTFEXP_LAGN->PJM
CLTF
19.698
CBM South 2LTFEXP_CBM-S2->PJM
CBM
23
TVALTFEXP_TVA->PJM
CLTF
10.208
CBM West 1LTFEXP_CBM-W1->PJM
CBM
115.748
CBM South 1LTFEXP_CBM-S1->PJM
CBM
38.783
MECLTFEXP_MEC->PJM
CLTF
15.666
SIGELTFEXP_SIGE->PJM
CLTF
0.545

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.41 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5987.66
MW Contribution:
23.47
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
2.717
957241AF2-018 GEN
Solar/Wind Harmer
8.236
270053AF1-130 C
Solar/Wind Harmer
32.909
270399AC1-101 GEN
Solar/Wind Harmer
7.81
24289405MTG1
50/50
11.78
243186AF1-051 GEN
50/50
12.754
24318705GVG2
50/50
11.822
24721805FLATG3
50/50
2.717
24723205RIVRG3
Adder
37.533
972203AH1-686 GEN
Adder
4.531
24686505CER G6
Adder
16.156
944971AF1-162 GEN
Solar/Wind Harmer
12.972
971403AH1-188 GEN
Solar/Wind Harmer
26.012
270331AC1-082 GEN3
Solar/Wind Harmer
0.864
960001AF2-291 GEN
Solar/Wind Harmer
5.313
24728305BUCHG2
Adder
7.739
971687AH1-348 GEN
Solar/Wind Harmer
1.658
24735205WLF2G2
Adder
8.97
270336AE1-100 GEN
Solar/Wind Harmer
2.369
971073AG2-665 GEN
Solar/Wind Harmer
1.558
970091AG2-072 GEN
Adder
102.646
339211AE2-254 GEN
Solar/Wind Harmer
1.998
3429241JKCT 3G
Adder
15.659
270173AC1-122 GEN
Solar/Wind Harmer
2.206
3429421JKCT 10G
Adder
10.948
945681AF1-233 GEN
Solar/Wind Harmer
24.773
943111AE2-339 GEN
Solar/Wind Harmer
1.158
339221AD2-048_GEN
Solar/Wind Harmer
2.01
943811AF1-049 GEN
Solar/Wind Harmer
4.941
339241AF1-083 GEN
Solar/Wind Harmer
2.163
964901AG1-354 GEN
Solar/Wind Harmer
19.398
970653AG2-424 GEN
Solar/Wind Harmer
6.236
25196808ZIMRHP
Adder
95.39
25196008MFTGT1
Adder
1.739
252516AE2-318_GEN
Solar/Wind Harmer
12.45
252510AF1-249 C
Solar/Wind Harmer
0.517
25194608D.CRK4
Adder
2.03
253316AC1-085 GEN3
Solar/Wind Harmer
10.112
946171AF1-282 GEN
Solar/Wind Harmer
12.079
24728605AND G2
Adder
4.51
253398AE2-221_GEN2
Solar/Wind Harmer
5.329
962761AG1-125 GEN
Solar/Wind Harmer
38.013
970149AG2-104 GEN
Solar/Wind Harmer
23.473
970155AG2-107 GEN
Solar/Wind Harmer
16.575
270574AD1-017 GEN2
Solar/Wind Harmer
5.994
316217AC1-145 GEN
Solar/Wind Harmer
2.791
316197AC1-042 GEN
Solar/Wind Harmer
2.116
3147312GRETNA
Solar/Wind Harmer
-0.003
270222AC2-111 GEN
Solar/Wind Harmer
5.217
944031AF1-071 GEN
Solar/Wind Harmer
1.174
963741AG1-226 GEN
Solar/Wind Harmer
51.846
965911AG1-460 GEN
Solar/Wind Harmer
1.606
276621W2-048 GEN
Solar/Wind Harmer
7.12
942081AE2-220 GEN
Solar/Wind Harmer
7.281
270209AC1-174_GEN
Solar/Wind Harmer
4.633
270437AC2-090 C
Solar/Wind Harmer
6.354
270239V3-007_GEN1
Solar/Wind Harmer
1.959
276686W4-005 GEN3
Solar/Wind Harmer
3.438
24385905FR-11G C
Solar/Wind Harmer
9.442
24386605FR-22G C
Solar/Wind Harmer
4.886
276903AD2-071 C
Solar/Wind Harmer
11.325
253370AE2-315 SEC1
Adder
2.225
253371AE2-315 SEC2
Adder
2.104
274761LEE CO EC;2U
Adder
10.206
274766LEE CO EC;7U
Adder
10.085
274822ROCKFORD ;11
Adder
21.436
25326309TAIT D
Adder
1.195
274828WAUKEGAN ;BP
Adder
11.976
274682WAUKEGAN ;7U
Adder
19.478
274745AC1-111 GEN9
Adder
6.042
274732ELWOOD EC;7P
Adder
17.715
274674JOLIET 9 ;6U
Adder
16.589
274676JOLIET 29;8U
Adder
11.649
238185AF2-356 C
Solar/Wind Helper
2.199
238120AE2-309 GEN
Solar/Wind Helper
0.436
238126S14_GEN_1
Solar/Wind Helper
0.692
23583801GRNGAP
Solar/Wind Helper
4.116
316095T157 G97
Solar/Wind Helper
1.102
238109AE1-109 GEN2
Solar/Wind Helper
0.089
20089026BF_G21_K23
Solar/Wind Helper
0.441
20084626FORWARD
Solar/Wind Helper
0.325
964201AG1-281 GEN
Solar/Wind Helper
0.442
270594AE1-207 GEN
Solar/Wind Harmer
12.561
270032AE2-172
Solar/Wind Harmer
4.302
270400AC1-102 GEN
Solar/Wind Harmer
7.81
971313AH1-133 GEN
Solar/Wind Harmer
10.201
941621AE2-160 GEN
Adder
5.641
966391AG1-508 GEN
Solar/Wind Harmer
5.744
970281AG2-184 GEN
Solar/Wind Harmer
34.819
971331AH1-145 GEN
Solar/Wind Harmer
15.307
971329AH1-144 GEN
Solar/Wind Harmer
9.777
24734705WLF1G3
Adder
9.154
24734805WLF1G4
Adder
9.154
24734905WLF1G5
Adder
9.154
962211AG1-066 GEN
Solar/Wind Harmer
3.81
24735105WLF2G1
Adder
8.97
971061AG2-657 GEN
Solar/Wind Harmer
14.005
971985AH1-537 GEN
Solar/Wind Harmer
26.103
243186AF1-051 GEN
50/50
12.754
24721705FLATG2
50/50
40.355
24723005RIVRG1
Adder
37.533
24723105RIVRG2
Adder
37.533
970913AG2-568 GEN
Solar/Wind Harmer
11.956
24728205BUCHG1
Adder
7.739
270214AC2-123 GEN
Solar/Wind Harmer
3.869
971225AH1-072 GEN
Solar/Wind Harmer
3.319
971227AH1-073 GEN
Solar/Wind Harmer
3.319
971277AH1-098 GEN
Solar/Wind Harmer
6.62
270583AD2-179 GEN
Solar/Wind Harmer
16.289
927014AC1-188 GEN
Solar/Wind Harmer
2.364
971073AG2-665 GEN
Solar/Wind Harmer
10.717
970879AG2-548 GEN
Solar/Wind Harmer
1.558
942891AE2-308 GEN
Solar/Wind Harmer
13.25
339231AF1-038_GEN
Solar/Wind Harmer
2.384
972043AH1-570 GEN
Solar/Wind Harmer
3.285
972045AH1-571 GEN
Solar/Wind Harmer
2.628
971125AH1-004 GEN
Solar/Wind Harmer
5.238
970107AG2-081 GEN
Solar/Wind Harmer
3.929
966021AG1-471 GEN
Solar/Wind Harmer
7.071
971485AH1-239 GEN
Solar/Wind Harmer
10.457
962581AG1-107 GEN
Solar/Wind Harmer
6.569
961491AF2-440 GEN
Solar/Wind Harmer
2.73
339236AF1-050_GEN
Solar/Wind Harmer
2.347
964781AG1-341 GEN
Solar/Wind Harmer
13.643
964571AG1-320 GEN
Solar/Wind Harmer
10.544
252509AD1-136 GEN
Solar/Wind Harmer
0.325
25183208HLCRTG
Solar/Wind Harmer
7.535
25194408D.CRK1
Adder
9.34
25194508D.CRK3
Adder
1.746
945391AF1-204 GEN
Solar/Wind Harmer
16.433
942671AE2-283 GEN
Solar/Wind Harmer
5.701
24728805RICHG1
Adder
4.399
24728905RICHG2
Adder
4.399
253415AE1-040 GEN
Solar/Wind Harmer
1.308
276916AD2-100_GEN
Solar/Wind Harmer
24.22
276911AD2-131_GEN
Solar/Wind Harmer
4.895
970241AG2-163 GEN
Solar/Wind Harmer
28.803
276615X2-022 GEN
Solar/Wind Harmer
2.236
276838X2-022 GEN2
Solar/Wind Harmer
0.266
926881AC1-175 GEN
Solar/Wind Harmer
6.354
274880W4-005 GEN4
Solar/Wind Harmer
3.438
276174W4-005 GEN2
Solar/Wind Harmer
3.438
24387305FR-4G C
Solar/Wind Harmer
5.77
966841AG1-555 GEN
Solar/Wind Harmer
2.852
24725505WLD G2 C
Solar/Wind Harmer
4.513
24699105WLD G1 C
Solar/Wind Harmer
4.461
270383AD1-128 GEN
Solar/Wind Harmer
6.909
970291AG2-192 GEN
Solar/Wind Harmer
1.461
970291AG2-192 GEN
Solar/Wind Harmer
0.47
253370AE2-315 SEC1
Adder
2.225
274764LEE CO EC;5U
Adder
10.23
274765LEE CO EC;6U
Adder
10.23
274762LEE CO EC;3U
Adder
10.206
274763LEE CO EC;4U
Adder
10.109
247621Y3-024
Adder
0.264
972235AH1-702 GEN1
Adder
2.754
972236AH1-702 GEN2
Adder
2.395
25322209TAIT E
Adder
10.639
25322209TAIT E
Adder
10.4
274683WAUKEGAN ;8U
Adder
22.847
274683WAUKEGAN ;8U
Adder
19.259
274696ROCKY RD ;4P
Adder
12.353
274695ROCKY RD ;2P
Adder
12.068
274693ROCKY RD ;1P
Adder
11.949
274697ROCKY RD ;3P
Adder
3.278
274674JOLIET 9 ;6U
Adder
16.589
23585401KL_K28_T16
Solar/Wind Helper
1.275
235054AD2-180 GEN
Solar/Wind Helper
1.707
238117U2-030
Solar/Wind Helper
0.29
971981AH1-535 GEN
Solar/Wind Harmer
14.155
270069AE2-166 C O1
Solar/Wind Harmer
12.483
3429211JKCT 2G
Adder
15.456
972163AH1-664 GEN
Solar/Wind Harmer
13.172
972165AH1-665 GEN
Solar/Wind Harmer
10.538
339216AC1-074 GEN
Solar/Wind Harmer
2.182
270291AC1-194 GEN
Solar/Wind Harmer
6.437
25196108MFTGT2
Adder
1.918
25196108MFTGT2
Adder
1.781
270444AC2-157 GEN1
Solar/Wind Harmer
6.941
270445AC2-157 GEN2
Solar/Wind Harmer
6.941
25196408WSDLE3
Adder
10.861
25196308WSDLE2
Adder
10.766
25196208WSDLE1
Adder
10.739
25196708WSDLE6
Adder
10.712
25196508WSDLE4
Adder
10.442
253433AC1-085 GEN1
Solar/Wind Harmer
6.419
253432AC1-085 GEN2
Solar/Wind Harmer
0.323
253406AD2-031_GEN
Solar/Wind Harmer
1.524
270340AC2-060 GEN
Solar/Wind Harmer
3.588
270263AC1-001 GEN
Solar/Wind Harmer
1.236
270197AD1-017 GEN1
Solar/Wind Harmer
1.798
270356AE2-297 GEN
Solar/Wind Harmer
5.395
944221AF1-090 GEN
Solar/Wind Harmer
12.7
963841AG1-237 GEN
Solar/Wind Harmer
12.506
276763AC1-053 GEN1
Solar/Wind Harmer
4.5
276764AC1-053 GEN2
Solar/Wind Harmer
4.5
276668AB2-070 GEN1
Solar/Wind Harmer
2.517
276848AB2-070 GEN3
Solar/Wind Harmer
2.517
276849AB2-070 GEN2
Solar/Wind Harmer
2.517
24386405FR-21G C
Solar/Wind Harmer
4.886
24387005FR-3G C
Solar/Wind Harmer
4.493
970289AG2-191 GEN
Solar/Wind Harmer
2.135
25306009OHH W.
Adder
3.203
253372AE2-315 SEC3
Adder
2.104
253372AE2-315 SEC3
Adder
2.104
972267AH1-718 GEN
Adder
4.579
274823ROCKFORD ;21
Adder
21.28
274744AC1-111 GEN8
Adder
6.042
274746AC1-111 G10
Adder
6.042
274728ELWOOD EC;5P
Adder
17.715
274731ELWOOD EC;2P
Adder
17.715
274733ELWOOD EC;3P
Adder
17.715
274735ELWOOD EC;4P
Adder
17.715
274675JOLIET 29;7U
Adder
33.032
23750501ELLIOTTS
Solar/Wind Helper
0.639
23750701CROSSCHOOL
Solar/Wind Helper
1.205
238118U2-030_1
Solar/Wind Helper
0.29
23652301WDPWR_K20
Solar/Wind Helper
0.134
203955AF1-039 C O1
Solar/Wind Helper
0.355
20089126CSLMN_L13
Solar/Wind Helper
0.558
20089226LOOKOUT
Solar/Wind Helper
0.556
20088926STNY CRK
Solar/Wind Helper
0.752
203940AF1-140 C
Solar/Wind Helper
0.362
235531U2-073 GEN
Solar/Wind Helper
2.776
23751201ROTHROCK
Solar/Wind Helper
0.715
237043AE2-125 C
Solar/Wind Helper
0.165
316097T157 G90
Solar/Wind Helper
1.102
20083426SW_E13_K22
Solar/Wind Helper
0.052
20088826HIGHLAND
Solar/Wind Helper
0.818
946071AF1-272 GEN
Solar/Wind Helper
2.445
203961AE2-224 GEN
Solar/Wind Helper
2.204
24289405MTG1
50/50
11.78
24318705GVG2
50/50
11.822
24722005FLATG5
50/50
2.717
24721905FLATG4
50/50
49.634
24686405CER G5
Adder
16.028
270330AC1-082 GEN2
Solar/Wind Harmer
0.862
270329AC1-082 GEN1
Solar/Wind Harmer
0.862
960911AF2-382 GEN
Solar/Wind Harmer
12.889
943031AE2-326 GEN
Solar/Wind Harmer
6.089
971461AH1-227 GEN
Solar/Wind Harmer
8.512
972103AH1-617 GEN
Solar/Wind Harmer
33.161
971191AH1-055 GEN
Solar/Wind Harmer
30.574
270346AE1-212 GEN
Solar/Wind Harmer
14.67
958121AF2-106 GEN
Solar/Wind Harmer
7.386
957541AF2-048 GEN
Solar/Wind Harmer
2.364
970879AG2-548 GEN
Solar/Wind Harmer
10.717
972273AH1-721 GEN
Adder
111.17
270030AE2-140 GEN
Solar/Wind Harmer
26.764
970093AG2-073 GEN
Solar/Wind Harmer
7.05
270186AC1-089 GEN
Solar/Wind Harmer
8.102
270367AC2-061_GEN
Solar/Wind Harmer
4.197
3429391JKCT 9G
Adder
10.948
972167AH1-666 GEN
Solar/Wind Harmer
10.503
962751AG1-124 GEN
Solar/Wind Harmer
11.766
339206AE1-143 GEN
Solar/Wind Harmer
2.789
339243AC2-075 GEN1
Solar/Wind Harmer
0.591
970455AG2-298 GEN
Solar/Wind Harmer
4.537
970653AG2-424 GEN
Solar/Wind Harmer
0.902
339255AE2-071 GEN
Solar/Wind Harmer
1.514
339250AF1-203 GEN
Solar/Wind Harmer
0.779
958171AF2-111 GEN
Solar/Wind Harmer
32.027
252507AC2-088 GEN
Solar/Wind Harmer
2.278
25196008MFTGT1
Adder
1.685
252519AF1-045_GEN
Solar/Wind Harmer
4.531
25194608D.CRK4
Adder
2.03
252524AE2-267 GEN
Solar/Wind Harmer
1.938
25196608WSDLE5
Adder
10.55
270018AE2-047 C O1
Solar/Wind Harmer
1.501
253317AC1-085 GEN4
Solar/Wind Harmer
10.112
946181AF1-283 GEN
Solar/Wind Harmer
15.702
970193AG2-126 GEN
Solar/Wind Harmer
17.687
24728705AND G3
Adder
9.433
24728505AND G1
Adder
4.51
253394AE2-221_GEN
Solar/Wind Harmer
5.329
962771AG1-126 GEN
Solar/Wind Harmer
38.013
970153AG2-106 GEN
Solar/Wind Harmer
16.575
3147312GRETNA
Solar/Wind Harmer
-0.014
3146802CHATHAM
Solar/Wind Harmer
-0.013
941801AE2-185 GEN
Solar/Wind Harmer
6.453
942481AE2-261 GEN
Solar/Wind Harmer
34.409
957381AF2-032 GEN
Solar/Wind Harmer
2.3
24379505HDWTR1G C
Solar/Wind Harmer
9.002
270240V3-007_GEN2
Solar/Wind Harmer
7.043
276785W4-005 GEN1
Solar/Wind Harmer
3.438
971993AH1-541 GEN
Solar/Wind Harmer
10.504
24386205FR-12G C
Solar/Wind Harmer
4.868
247642Z2-115 C
Solar/Wind Harmer
0.072
965461AG1-414 GEN
Solar/Wind Harmer
2.547
970289AG2-191 GEN
Solar/Wind Harmer
0.862
253370AE2-315 SEC1
Adder
2.225
253371AE2-315 SEC2
Adder
2.104
274760LEE CO EC;1U
Adder
10.206
274767LEE CO EC;8U
Adder
10.085
274682WAUKEGAN ;7U
Adder
19.478
274729ELWOOD EC;1P
Adder
17.715
274730ELWOOD EC;6P
Adder
17.715
274734ELWOOD EC;8P
Adder
17.715
274736ELWOOD EC;9P
Adder
17.715
237048AF1-022 C
Solar/Wind Helper
0.185
237046AF1-021 C
Solar/Wind Helper
0.318
964991AG1-363 GEN
Solar/Wind Helper
3.731
238127S14_GEN_2
Solar/Wind Helper
0.692
23562501BACKB
Solar/Wind Helper
0.87
202652Y1-033 WT C
Solar/Wind Helper
0.538
238108AE1-109 GEN1
Solar/Wind Helper
0.089
238110AE1-109 GEN3
Solar/Wind Helper
0.089
20092526R32
Solar/Wind Helper
1.061
235058AG1-386 C
Solar/Wind Helper
0.381
CPLELTFEXP_CPLE->PJM
CLTF
7.73
CBM West 2LTFEXP_CBM-W2->PJM
CBM
161.379
NYPJM->LTFIMP_NY
CLTF
5.307
LGEELTFEXP_LGEE->PJM
CLTF
8.953
WECLTFEXP_WEC->PJM
CLTF
4.181
AG2-052LTFEXP_AG2-052->PJM
LTF
0.252
AH1-155LTFEXP_AH1-155->PJM
LTF
0.378
LAGNLTFEXP_LAGN->PJM
CLTF
24.264
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.864
TVALTFEXP_TVA->PJM
CLTF
12.601
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.837
CBM South 1LTFEXP_CBM-S1->PJM
CBM
47.616
MECLTFEXP_MEC->PJM
CLTF
19.089
SIGELTFEXP_SIGE->PJM
CLTF
0.657

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P2-2_#7222_05MALIS 765_1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:107.46 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5935.05
MW Contribution:
31.56
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
243186AF1-051 GEN
50/50
12.373
24721705FLATG2
50/50
40.36
24723005RIVRG1
Adder
34.305
24723105RIVRG2
Adder
34.305
970913AG2-568 GEN
Solar/Wind Harmer
10.293
24728205BUCHG1
Adder
6.531
971225AH1-072 GEN
Solar/Wind Harmer
2.862
971227AH1-073 GEN
Solar/Wind Harmer
2.862
927014AC1-188 GEN
Solar/Wind Harmer
2.06
270214AC2-123 GEN
Solar/Wind Harmer
2.985
971277AH1-098 GEN
Solar/Wind Harmer
5.094
942891AE2-308 GEN
Solar/Wind Harmer
11.926
964571AG1-320 GEN
Solar/Wind Harmer
9.728
339231AF1-038_GEN
Solar/Wind Harmer
2.148
972043AH1-570 GEN
Solar/Wind Harmer
2.957
972045AH1-571 GEN
Solar/Wind Harmer
2.366
971125AH1-004 GEN
Solar/Wind Harmer
4.718
970107AG2-081 GEN
Solar/Wind Harmer
3.539
270583AD2-179 GEN
Solar/Wind Harmer
11.79
966021AG1-471 GEN
Solar/Wind Harmer
6.353
339236AF1-050_GEN
Solar/Wind Harmer
2.134
971485AH1-239 GEN
Solar/Wind Harmer
9.407
964781AG1-341 GEN
Solar/Wind Harmer
12.396
945391AF1-204 GEN
Solar/Wind Harmer
16.22
962581AG1-107 GEN
Solar/Wind Harmer
5.847
961491AF2-440 GEN
Solar/Wind Harmer
2.43
970241AG2-163 GEN
Solar/Wind Harmer
28.851
24387305FR-4G C
Solar/Wind Harmer
5.833
966841AG1-555 GEN
Solar/Wind Harmer
2.883
252509AD1-136 GEN
Solar/Wind Harmer
0.293
276916AD2-100_GEN
Solar/Wind Harmer
24.022
276911AD2-131_GEN
Solar/Wind Harmer
4.855
270180AB1-006 GEN1
Solar/Wind Harmer
8.215
24697605MDL-3G C
Solar/Wind Harmer
4.21
24755605MDL-5G
Solar/Wind Harmer
2.754
24697905MDL-4G C
Solar/Wind Harmer
2.621
270181AB1-006 GEN2
Solar/Wind Harmer
0.817
276615X2-022 GEN
Solar/Wind Harmer
2.233
276838X2-022 GEN2
Solar/Wind Harmer
0.265
945421AF1-207 GEN
Solar/Wind Harmer
16.001
957841AF2-078 GEN
Solar/Wind Harmer
6.888
274880W4-005 GEN4
Solar/Wind Harmer
3.443
276174W4-005 GEN2
Solar/Wind Harmer
3.443
971073AG2-665 GEN
Solar/Wind Harmer
9.054
960611AF2-352 GEN
Solar/Wind Harmer
2.632
970879AG2-548 GEN
Solar/Wind Harmer
1.316
970291AG2-192 GEN
Solar/Wind Harmer
1.47
970291AG2-192 GEN
Solar/Wind Harmer
0.473
24725505WLD G2 C
Solar/Wind Harmer
4.494
24699105WLD G1 C
Solar/Wind Harmer
4.441
942111AE2-223 GEN
Solar/Wind Harmer
9.262
25194408D.CRK1
Adder
8.477
25194508D.CRK3
Adder
1.585
274764LEE CO EC;5U
Adder
10.431
274765LEE CO EC;6U
Adder
10.431
274762LEE CO EC;3U
Adder
10.407
274763LEE CO EC;4U
Adder
10.309
24721605FLATG1
50/50
2.718
957241AF2-018 GEN
Solar/Wind Harmer
7.332
270053AF1-130 C
Solar/Wind Harmer
29.298
270399AC1-101 GEN
Solar/Wind Harmer
6.93
270400AC1-102 GEN
Solar/Wind Harmer
6.93
941621AE2-160 GEN
Adder
4.867
970281AG2-184 GEN
Solar/Wind Harmer
30.484
971313AH1-133 GEN
Solar/Wind Harmer
8.48
962211AG1-066 GEN
Solar/Wind Harmer
3.344
24734705WLF1G3
Adder
7.73
24734805WLF1G4
Adder
7.73
24734905WLF1G5
Adder
7.73
971061AG2-657 GEN
Solar/Wind Harmer
11.954
971985AH1-537 GEN
Solar/Wind Harmer
23.681
24735105WLF2G1
Adder
7.594
966391AG1-508 GEN
Solar/Wind Harmer
4.439
971331AH1-145 GEN
Solar/Wind Harmer
11.397
971329AH1-144 GEN
Solar/Wind Harmer
7.28
971981AH1-535 GEN
Solar/Wind Harmer
12.094
270444AC2-157 GEN1
Solar/Wind Harmer
6.747
270445AC2-157 GEN2
Solar/Wind Harmer
6.747
3429211JKCT 2G
Adder
13.893
972163AH1-664 GEN
Solar/Wind Harmer
11.763
972165AH1-665 GEN
Solar/Wind Harmer
9.41
339216AC1-074 GEN
Solar/Wind Harmer
1.968
963841AG1-237 GEN
Solar/Wind Harmer
12.582
25196108MFTGT2
Adder
1.764
25196108MFTGT2
Adder
1.638
24386405FR-21G C
Solar/Wind Harmer
4.939
24387005FR-3G C
Solar/Wind Harmer
4.542
944221AF1-090 GEN
Solar/Wind Harmer
12.541
946581AF1-322 GEN
Solar/Wind Harmer
11.687
24691005MDL-2G C
Solar/Wind Harmer
4.223
276763AC1-053 GEN1
Solar/Wind Harmer
4.503
276764AC1-053 GEN2
Solar/Wind Harmer
4.503
276668AB2-070 GEN1
Solar/Wind Harmer
2.521
276848AB2-070 GEN3
Solar/Wind Harmer
2.521
276849AB2-070 GEN2
Solar/Wind Harmer
2.521
270356AE2-297 GEN
Solar/Wind Harmer
5.225
274853TWINGROVE;U1
Solar/Wind Harmer
8.154
274854TWINGROVE;U2
Solar/Wind Harmer
7.983
970289AG2-191 GEN
Solar/Wind Harmer
2.148
276726Z2-087_GEN
Solar/Wind Harmer
8.934
959341AF2-225 GEN
Solar/Wind Harmer
16.948
972267AH1-718 GEN
Adder
4.661
274823ROCKFORD ;21
Adder
21.773
25196408WSDLE3
Adder
9.858
25196308WSDLE2
Adder
9.772
25196208WSDLE1
Adder
9.747
25196708WSDLE6
Adder
9.723
25196508WSDLE4
Adder
9.478
274744AC1-111 GEN8
Adder
6.235
274746AC1-111 G10
Adder
6.235
274775LINCOLN ;6U
Adder
9.41
274776LINCOLN ;7U
Adder
9.41
274777LINCOLN ;8U
Adder
9.41
274728ELWOOD EC;5P
Adder
18.315
274731ELWOOD EC;2P
Adder
18.315
274733ELWOOD EC;3P
Adder
18.315
274735ELWOOD EC;4P
Adder
18.315
23750501ELLIOTTS
Solar/Wind Helper
0.664
23652301WDPWR_K20
Solar/Wind Helper
0.142
23750701CROSSCHOOL
Solar/Wind Helper
1.189
203955AF1-039 C O1
Solar/Wind Helper
0.363
238118U2-030_1
Solar/Wind Helper
0.286
241997AF1-093 GEN
Solar/Wind Helper
0.24
241985AE1-237 GEN
Solar/Wind Helper
0.233
241982AE2-343 S C
Solar/Wind Helper
0.209
20089126CSLMN_L13
Solar/Wind Helper
0.575
20089226LOOKOUT
Solar/Wind Helper
0.573
20088926STNY CRK
Solar/Wind Helper
0.78
203940AF1-140 C
Solar/Wind Helper
0.376
20094526CT_V3-030
Solar/Wind Helper
0.446
20088626ARWF_N39
Solar/Wind Helper
1.144
203846AF2-130 C
Solar/Wind Helper
0.423
959141AF2-205 GEN
Solar/Wind Harmer
1.763
972235AH1-702 GEN1
Adder
2.817
972236AH1-702 GEN2
Adder
2.45
274696ROCKY RD ;4P
Adder
12.719
274695ROCKY RD ;2P
Adder
12.425
274693ROCKY RD ;1P
Adder
12.303
274697ROCKY RD ;3P
Adder
3.375
274683WAUKEGAN ;8U
Adder
23.51
274683WAUKEGAN ;8U
Adder
19.818
274770LINCOLN ;1U
Adder
9.41
274771LINCOLN ;2U
Adder
9.41
274674JOLIET 9 ;6U
Adder
16.682
237043AE2-125 C
Solar/Wind Helper
0.176
23585401KL_K28_T16
Solar/Wind Helper
1.282
23751201ROTHROCK
Solar/Wind Helper
0.737
235054AD2-180 GEN
Solar/Wind Helper
1.698
238117U2-030
Solar/Wind Helper
0.286
962101AG1-054 GEN
Solar/Wind Helper
0.612
254304AE2-114 C
Solar/Wind Helper
0.205
254305AE2-115 C
Solar/Wind Helper
0.205
241967AE2-285_GEN
Solar/Wind Helper
0.597
241801AE1-079 GEN
Solar/Wind Helper
0.233
235531U2-073 GEN
Solar/Wind Helper
2.712
20083426SW_E13_K22
Solar/Wind Helper
0.053
946071AF1-272 GEN
Solar/Wind Helper
2.571
20088826HIGHLAND
Solar/Wind Helper
0.851
203961AE2-224 GEN
Solar/Wind Helper
2.277
203818AF1-086 GEN
Solar/Wind Helper
1.591
203853AF1-134 C O1
Solar/Wind Helper
0.449
946381AF1-302 GEN
Solar/Wind Helper
0.208
203946AE2-131 C
Solar/Wind Helper
0.445
24289405MTG1
50/50
11.32
243186AF1-051 GEN
50/50
12.373
24318705GVG2
50/50
11.469
24721805FLATG3
50/50
2.718
24723205RIVRG3
Adder
34.305
972203AH1-686 GEN
Adder
4.176
24686505CER G6
Adder
14.723
944971AF1-162 GEN
Solar/Wind Harmer
11.548
971403AH1-188 GEN
Solar/Wind Harmer
22.954
270331AC1-082 GEN3
Solar/Wind Harmer
0.78
960001AF2-291 GEN
Solar/Wind Harmer
4.782
962761AG1-125 GEN
Solar/Wind Harmer
51.105
970149AG2-104 GEN
Solar/Wind Harmer
31.557
970155AG2-107 GEN
Solar/Wind Harmer
22.284
24728305BUCHG2
Adder
6.531
971687AH1-348 GEN
Solar/Wind Harmer
1.432
24735205WLF2G2
Adder
7.594
970091AG2-072 GEN
Adder
98.735
339211AE2-254 GEN
Solar/Wind Harmer
1.806
3429241JKCT 3G
Adder
14.075
970653AG2-424 GEN
Solar/Wind Harmer
5.716
339241AF1-083 GEN
Solar/Wind Harmer
1.965
3429421JKCT 10G
Adder
9.84
339221AD2-048_GEN
Solar/Wind Harmer
1.812
943111AE2-339 GEN
Solar/Wind Harmer
1.043
964901AG1-354 GEN
Solar/Wind Harmer
17.632
945681AF1-233 GEN
Solar/Wind Harmer
22.112
963741AG1-226 GEN
Solar/Wind Harmer
51.931
25196008MFTGT1
Adder
1.6
24385905FR-11G C
Solar/Wind Harmer
9.545
24386605FR-22G C
Solar/Wind Harmer
4.939
24728605AND G2
Adder
4.399
24289405MTG1
50/50
11.32
24318705GVG2
50/50
11.469
24722005FLATG5
50/50
2.718
24721905FLATG4
50/50
49.64
24686405CER G5
Adder
14.607
270330AC1-082 GEN2
Solar/Wind Harmer
0.779
270329AC1-082 GEN1
Solar/Wind Harmer
0.779
962771AG1-126 GEN
Solar/Wind Harmer
51.105
970153AG2-106 GEN
Solar/Wind Harmer
22.284
971191AH1-055 GEN
Solar/Wind Harmer
27.435
960911AF2-382 GEN
Solar/Wind Harmer
10.97
972103AH1-617 GEN
Solar/Wind Harmer
29.032
971461AH1-227 GEN
Solar/Wind Harmer
7.34
203954AE2-126 C
Solar/Wind Helper
0.44
203804AE2-113_GEN
Solar/Wind Helper
1.631
940863AE2-074 GEN
Solar/Wind Helper
0.426
270346AE1-212 GEN
Solar/Wind Harmer
11.918
957541AF2-048 GEN
Solar/Wind Harmer
2.06
943031AE2-326 GEN
Solar/Wind Harmer
4.698
972273AH1-721 GEN
Adder
99.65
970093AG2-073 GEN
Solar/Wind Harmer
6.342
970455AG2-298 GEN
Solar/Wind Harmer
4.162
339206AE1-143 GEN
Solar/Wind Harmer
2.532
970653AG2-424 GEN
Solar/Wind Harmer
0.827
270186AC1-089 GEN
Solar/Wind Harmer
7.225
3429391JKCT 9G
Adder
9.84
270367AC2-061_GEN
Solar/Wind Harmer
3.742
958121AF2-106 GEN
Solar/Wind Harmer
5.343
339243AC2-075 GEN1
Solar/Wind Harmer
0.533
972167AH1-666 GEN
Solar/Wind Harmer
9.374
339255AE2-071 GEN
Solar/Wind Harmer
1.375
339250AF1-203 GEN
Solar/Wind Harmer
0.708
970193AG2-126 GEN
Solar/Wind Harmer
17.459
25196008MFTGT1
Adder
1.55
24386205FR-12G C
Solar/Wind Harmer
4.921
24728705AND G3
Adder
9.201
24728505AND G1
Adder
4.399
252507AC2-088 GEN
Solar/Wind Harmer
2.051
942481AE2-261 GEN
Solar/Wind Harmer
34.173
957381AF2-032 GEN
Solar/Wind Harmer
2.285
24690905MDL-1G C
Solar/Wind Harmer
9.169
970781AG2-491 GEN
Solar/Wind Harmer
11.422
958171AF2-111 GEN
Solar/Wind Harmer
28.524
276785W4-005 GEN1
Solar/Wind Harmer
3.443
971993AH1-541 GEN
Solar/Wind Harmer
10.521
247642Z2-115 C
Solar/Wind Harmer
0.073
965091AG1-374 GEN
Solar/Wind Harmer
33.954
970879AG2-548 GEN
Solar/Wind Harmer
9.054
959611AF2-252 GEN
Solar/Wind Harmer
2.632
965461AG1-414 GEN
Solar/Wind Harmer
2.564
970289AG2-191 GEN
Solar/Wind Harmer
0.868
25194608D.CRK4
Adder
1.843
274760LEE CO EC;1U
Adder
10.407
274767LEE CO EC;8U
Adder
10.284
25196608WSDLE5
Adder
9.576
274682WAUKEGAN ;7U
Adder
20.049
274772LINCOLN ;3U
Adder
9.41
972259AH1-714 GEN
Adder
21.265
274729ELWOOD EC;1P
Adder
18.315
274730ELWOOD EC;6P
Adder
18.315
274734ELWOOD EC;8P
Adder
18.315
274736ELWOOD EC;9P
Adder
18.315
237048AF1-022 C
Solar/Wind Helper
0.194
237046AF1-021 C
Solar/Wind Helper
0.336
235058AG1-386 C
Solar/Wind Helper
0.44
23562501BACKB
Solar/Wind Helper
0.897
964991AG1-363 GEN
Solar/Wind Helper
3.654
202652Y1-033 WT C
Solar/Wind Helper
0.551
238127S14_GEN_2
Solar/Wind Helper
0.674
20092526R32
Solar/Wind Helper
1.103
20303426NA_O38_P22
Solar/Wind Helper
0.938
203993AD2-133_GEN1
Solar/Wind Helper
0.966
238108AE1-109 GEN1
Solar/Wind Helper
0.084
238110AE1-109 GEN3
Solar/Wind Helper
0.084
203854AF2-039 C
Solar/Wind Helper
0.298
965911AG1-460 GEN
Solar/Wind Harmer
1.595
24791305MDL-5G
Solar/Wind Harmer
2.754
276621W2-048 GEN
Solar/Wind Harmer
7.111
276686W4-005 GEN3
Solar/Wind Harmer
3.443
25196808ZIMRHP
Adder
86.01
971073AG2-665 GEN
Solar/Wind Harmer
1.316
276903AD2-071 C
Solar/Wind Harmer
11.309
940581AE2-045 GEN
Solar/Wind Harmer
11.524
971605AH1-302 GEN
Solar/Wind Harmer
9.854
276655WTG1_EQ
Solar/Wind Harmer
9.862
276656WTG2_EQ
Solar/Wind Harmer
1.306
939741AE1-205 GEN
Solar/Wind Harmer
22.597
270594AE1-207 GEN
Solar/Wind Harmer
15.305
270032AE2-172
Solar/Wind Harmer
5.241
25194608D.CRK4
Adder
1.843
274761LEE CO EC;2U
Adder
10.407
274766LEE CO EC;7U
Adder
10.284
274822ROCKFORD ;11
Adder
21.932
274828WAUKEGAN ;BP
Adder
12.324
274745AC1-111 GEN9
Adder
6.235
274682WAUKEGAN ;7U
Adder
20.049
274773LINCOLN ;4U
Adder
9.41
274774LINCOLN ;5U
Adder
9.41
274732ELWOOD EC;7P
Adder
18.315
274674JOLIET 9 ;6U
Adder
17.154
238185AF2-356 C
Solar/Wind Helper
2.191
254303AC2-168 GEN
Solar/Wind Helper
0.149
241966AE1-183 GEN
Solar/Wind Helper
0.24
20089026BF_G21_K23
Solar/Wind Helper
0.455
238120AE2-309 GEN
Solar/Wind Helper
0.424
238126S14_GEN_1
Solar/Wind Helper
0.674
23751101LEADS_P59
Solar/Wind Helper
1.865
20084626FORWARD
Solar/Wind Helper
0.338
964201AG1-281 GEN
Solar/Wind Helper
0.457
20091526CHSTN_FL
Solar/Wind Helper
0.55
20090526Q36
Solar/Wind Helper
0.966
238109AE1-109 GEN2
Solar/Wind Helper
0.084
203952AE2-129 C
Solar/Wind Helper
0.445
203855AF2-088 C
Solar/Wind Helper
0.143
CPLELTFEXP_CPLE->PJM
CLTF
6.634
CBM West 2LTFEXP_CBM-W2->PJM
CBM
151.558
NYPJM->LTFIMP_NY
CLTF
5.206
LGEELTFEXP_LGEE->PJM
CLTF
8.318
WECLTFEXP_WEC->PJM
CLTF
4.274
AG2-052LTFEXP_AG2-052->PJM
LTF
0.26
AH1-155LTFEXP_AH1-155->PJM
LTF
0.389
LAGNLTFEXP_LAGN->PJM
CLTF
22.209
CBM South 2LTFEXP_CBM-S2->PJM
CBM
24.481
TVALTFEXP_TVA->PJM
CLTF
11.344
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.358
CBM South 1LTFEXP_CBM-S1->PJM
CBM
43.12
MECLTFEXP_MEC->PJM
CLTF
18.91
SIGELTFEXP_SIGE->PJM
CLTF
0.622

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.76 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5896.19
MW Contribution:
17.31
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
243186AF1-051 GEN
50/50
12.754
24721705FLATG2
50/50
40.355
24723005RIVRG1
Adder
37.533
24723105RIVRG2
Adder
37.533
970913AG2-568 GEN
Solar/Wind Harmer
9.827
24728205BUCHG1
Adder
7.739
971225AH1-072 GEN
Solar/Wind Harmer
2.315
971227AH1-073 GEN
Solar/Wind Harmer
2.315
971277AH1-098 GEN
Solar/Wind Harmer
4.618
270583AD2-179 GEN
Solar/Wind Harmer
11.364
971073AG2-665 GEN
Solar/Wind Harmer
6.854
970879AG2-548 GEN
Solar/Wind Harmer
1.558
942891AE2-308 GEN
Solar/Wind Harmer
9.244
972043AH1-570 GEN
Solar/Wind Harmer
2.384
972045AH1-571 GEN
Solar/Wind Harmer
1.91
971125AH1-004 GEN
Solar/Wind Harmer
3.655
970107AG2-081 GEN
Solar/Wind Harmer
2.741
966021AG1-471 GEN
Solar/Wind Harmer
4.933
971485AH1-239 GEN
Solar/Wind Harmer
7.296
962581AG1-107 GEN
Solar/Wind Harmer
0.002
964781AG1-341 GEN
Solar/Wind Harmer
9.518
964571AG1-320 GEN
Solar/Wind Harmer
8.194
252509AD1-136 GEN
Solar/Wind Harmer
0.044
25183208HLCRTG
Solar/Wind Harmer
0.001
971587AH1-292 GEN
Solar/Wind Harmer
6.363
25194408D.CRK1
Adder
9.34
25194508D.CRK3
Adder
1.746
945391AF1-204 GEN
Solar/Wind Harmer
8.741
942671AE2-283 GEN
Solar/Wind Harmer
3.812
24728805RICHG1
Adder
4.399
24721605FLATG1
50/50
2.717
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
270053AF1-130 C
Solar/Wind Harmer
28.948
270399AC1-101 GEN
Solar/Wind Harmer
4.065
270400AC1-102 GEN
Solar/Wind Harmer
4.065
971313AH1-133 GEN
Solar/Wind Harmer
5.869
941621AE2-160 GEN
Adder
5.641
966391AG1-508 GEN
Solar/Wind Harmer
1.796
970281AG2-184 GEN
Solar/Wind Harmer
24.292
971331AH1-145 GEN
Solar/Wind Harmer
15.307
971329AH1-144 GEN
Solar/Wind Harmer
5.625
24734705WLF1G3
Adder
9.154
24734805WLF1G4
Adder
9.154
24734905WLF1G5
Adder
9.154
24735105WLF2G1
Adder
8.97
971061AG2-657 GEN
Solar/Wind Harmer
6.84
971985AH1-537 GEN
Solar/Wind Harmer
3.035
971981AH1-535 GEN
Solar/Wind Harmer
6.584
270069AE2-166 C O1
Solar/Wind Harmer
8.709
3429211JKCT 2G
Adder
15.456
972163AH1-664 GEN
Solar/Wind Harmer
10.231
972165AH1-665 GEN
Solar/Wind Harmer
8.194
339216AC1-074 GEN
Solar/Wind Harmer
0.242
270291AC1-194 GEN
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.918
25196108MFTGT2
Adder
1.781
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
25196408WSDLE3
Adder
10.861
25196308WSDLE2
Adder
10.766
25196208WSDLE1
Adder
10.739
25196708WSDLE6
Adder
10.712
25196508WSDLE4
Adder
10.442
253406AD2-031_GEN
Solar/Wind Harmer
0.618
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.825
270197AD1-017 GEN1
Solar/Wind Harmer
1.008
270356AE2-297 GEN
Solar/Wind Harmer
0.001
944221AF1-090 GEN
Solar/Wind Harmer
4.756
963841AG1-237 GEN
Solar/Wind Harmer
3.459
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.312
276848AB2-070 GEN3
Solar/Wind Harmer
0.31
276849AB2-070 GEN2
Solar/Wind Harmer
0.312
24386405FR-21G C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
1.489
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
11.702
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
8.158
25306009OHH W.
Adder
3.203
253372AE2-315 SEC3
Adder
2.104
253372AE2-315 SEC3
Adder
2.104
270543AE2-219 C
Solar/Wind Harmer
5.421
946321AF1-296 GEN
Solar/Wind Harmer
4.325
274877BISHOP HL;1U
Solar/Wind Harmer
0.257
24289405MTG1
50/50
11.78
243186AF1-051 GEN
50/50
12.754
24318705GVG2
50/50
11.822
24721805FLATG3
50/50
2.717
24723205RIVRG3
Adder
37.533
972203AH1-686 GEN
Adder
4.531
24686505CER G6
Adder
16.156
944971AF1-162 GEN
Solar/Wind Harmer
12.972
971403AH1-188 GEN
Solar/Wind Harmer
18.148
960001AF2-291 GEN
Solar/Wind Harmer
0
24728305BUCHG2
Adder
7.739
971687AH1-348 GEN
Solar/Wind Harmer
1.157
24735205WLF2G2
Adder
8.97
971073AG2-665 GEN
Solar/Wind Harmer
1.558
970091AG2-072 GEN
Adder
102.646
3429241JKCT 3G
Adder
15.659
3429421JKCT 10G
Adder
10.948
945681AF1-233 GEN
Solar/Wind Harmer
17.283
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
964901AG1-354 GEN
Solar/Wind Harmer
13.534
970653AG2-424 GEN
Solar/Wind Harmer
4.351
25196808ZIMRHP
Adder
95.39
25196008MFTGT1
Adder
1.739
252516AE2-318_GEN
Solar/Wind Harmer
9.728
252510AF1-249 C
Solar/Wind Harmer
0.065
25194608D.CRK4
Adder
2.03
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
8.427
24728605AND G2
Adder
4.51
253398AE2-221_GEN2
Solar/Wind Harmer
0
962761AG1-125 GEN
Solar/Wind Harmer
32.057
970149AG2-104 GEN
Solar/Wind Harmer
17.311
970155AG2-107 GEN
Solar/Wind Harmer
20.471
3147312GRETNA
Solar/Wind Harmer
0.031
970773AG2-487 GEN
Solar/Wind Harmer
1.442
963741AG1-226 GEN
Solar/Wind Harmer
19.023
965911AG1-460 GEN
Solar/Wind Harmer
1.606
276621W2-048 GEN
Solar/Wind Harmer
0.398
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.825
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
8.823
24728905RICHG2
Adder
4.399
276916AD2-100_GEN
Solar/Wind Harmer
16.897
276911AD2-131_GEN
Solar/Wind Harmer
1.113
970241AG2-163 GEN
Solar/Wind Harmer
4.689
276615X2-022 GEN
Solar/Wind Harmer
0.083
276838X2-022 GEN2
Solar/Wind Harmer
0.448
926881AC1-175 GEN
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.897
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
1.019
970291AG2-192 GEN
Solar/Wind Harmer
0.47
971613AH1-306 GEN
Solar/Wind Harmer
3.76
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.602
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270269AC2-059
Solar/Wind Harmer
0.001
942111AE2-223 GEN
Solar/Wind Harmer
2.525
253370AE2-315 SEC1
Adder
2.225
970883AG2-550 GEN
Solar/Wind Harmer
7.744
970885AG2-551 GEN
Solar/Wind Harmer
2.581
276645AC1-214 GEN1
Solar/Wind Harmer
0.302
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.239
270031AE2-169
Solar/Wind Harmer
4.216
270599AE1-208 GEN
Solar/Wind Harmer
7.027
964611AG1-324 GEN
Solar/Wind Harmer
0.575
274764LEE CO EC;5U
Adder
10.23
274765LEE CO EC;6U
Adder
10.23
274762LEE CO EC;3U
Adder
10.206
274763LEE CO EC;4U
Adder
10.109
938861AE1-114 GEN
Solar/Wind Harmer
4.333
247621Y3-024
Adder
0.264
270201AC2-176 GEN
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
2.754
972236AH1-702 GEN2
Adder
2.395
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
15.232
971343AH1-151 GEN
Solar/Wind Harmer
15.232
25322209TAIT E
Adder
10.639
25322209TAIT E
Adder
10.4
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
11.378
962691AG1-118 GEN
Solar/Wind Harmer
22.733
274683WAUKEGAN ;8U
Adder
22.847
274683WAUKEGAN ;8U
Adder
19.259
274696ROCKY RD ;4P
Adder
12.353
274695ROCKY RD ;2P
Adder
12.068
274693ROCKY RD ;1P
Adder
11.949
274697ROCKY RD ;3P
Adder
3.278
958481AF2-142 GEN
Solar/Wind Harmer
11.337
276897AD1-100 C
Solar/Wind Harmer
18.8
276893AG1-478 C
Solar/Wind Harmer
0.501
274674JOLIET 9 ;6U
Adder
16.589
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274888KELLY CRK;1U
Solar/Wind Harmer
0.437
276776AD2-060 GEN
Solar/Wind Harmer
0.799
958011AF2-095 GEN
Solar/Wind Harmer
10.787
23585401KL_K28_T16
Solar/Wind Helper
1.275
235054AD2-180 GEN
Solar/Wind Helper
1.707
238117U2-030
Solar/Wind Helper
0.29
235531U2-073 GEN
Solar/Wind Helper
2.776
23751201ROTHROCK
Solar/Wind Helper
0.715
237043AE2-125 C
Solar/Wind Helper
0.165
316097T157 G90
Solar/Wind Helper
1.102
20083426SW_E13_K22
Solar/Wind Helper
0.052
20088826HIGHLAND
Solar/Wind Helper
0.818
946071AF1-272 GEN
Solar/Wind Helper
2.445
203961AE2-224 GEN
Solar/Wind Helper
2.204
970941AG2-585 GEN
Solar/Wind Harmer
2.017
247536S-71 GEN
Solar/Wind Harmer
0.307
971611AH1-305 GEN
Solar/Wind Harmer
4.575
970169AG2-114 GEN
Solar/Wind Harmer
7.684
276741O09 GEN1
Solar/Wind Harmer
0.271
972267AH1-718 GEN
Adder
4.579
971609AH1-304 GEN
Solar/Wind Harmer
1.252
964611AG1-324 GEN
Solar/Wind Harmer
2.987
926823AC1-168 GEN
Solar/Wind Harmer
1.302
959141AF2-205 GEN
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971681AH1-341 GEN
Solar/Wind Harmer
12.311
274856ECOGROVE ;U1
Solar/Wind Harmer
0.178
274823ROCKFORD ;21
Adder
21.28
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971171AH1-044 GEN
Solar/Wind Harmer
15.232
945581AF1-223 GEN
Solar/Wind Harmer
0
276861AD2-134 GEN
Solar/Wind Harmer
0.136
276863AD2-134 GEN
Solar/Wind Harmer
0.136
971675AH1-338 GEN
Solar/Wind Harmer
2.966
971411AH1-196 GEN
Solar/Wind Harmer
11.402
970073AG2-061 GEN
Solar/Wind Harmer
2.528
274744AC1-111 GEN8
Adder
6.042
274746AC1-111 G10
Adder
6.042
970833AG2-524 GEN
Solar/Wind Harmer
8.285
970833AG2-524 GEN
Solar/Wind Harmer
5.523
274728ELWOOD EC;5P
Adder
17.715
274731ELWOOD EC;2P
Adder
17.715
274733ELWOOD EC;3P
Adder
17.715
274735ELWOOD EC;4P
Adder
17.715
274675JOLIET 29;7U
Adder
33.032
960591AF2-350 GEN
Solar/Wind Harmer
7.491
23750501ELLIOTTS
Solar/Wind Helper
0.639
23750701CROSSCHOOL
Solar/Wind Helper
1.205
238118U2-030_1
Solar/Wind Helper
0.29
23652301WDPWR_K20
Solar/Wind Helper
0.134
203955AF1-039 C O1
Solar/Wind Helper
0.355
20089126CSLMN_L13
Solar/Wind Helper
0.558
20089226LOOKOUT
Solar/Wind Helper
0.556
20088926STNY CRK
Solar/Wind Helper
0.752
203940AF1-140 C
Solar/Wind Helper
0.362
24289405MTG1
50/50
11.78
24318705GVG2
50/50
11.822
24722005FLATG5
50/50
2.717
24721905FLATG4
50/50
49.634
24686405CER G5
Adder
16.028
960911AF2-382 GEN
Solar/Wind Harmer
8.992
943031AE2-326 GEN
Solar/Wind Harmer
6.089
971461AH1-227 GEN
Solar/Wind Harmer
5.939
972103AH1-617 GEN
Solar/Wind Harmer
23.135
971191AH1-055 GEN
Solar/Wind Harmer
29.317
270346AE1-212 GEN
Solar/Wind Harmer
10.045
958121AF2-106 GEN
Solar/Wind Harmer
0.001
970879AG2-548 GEN
Solar/Wind Harmer
6.854
972273AH1-721 GEN
Adder
111.17
270030AE2-140 GEN
Solar/Wind Harmer
18.672
970093AG2-073 GEN
Solar/Wind Harmer
7.87
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
3429391JKCT 9G
Adder
10.948
972167AH1-666 GEN
Solar/Wind Harmer
7.327
962751AG1-124 GEN
Solar/Wind Harmer
8.058
970455AG2-298 GEN
Solar/Wind Harmer
3.516
970653AG2-424 GEN
Solar/Wind Harmer
0.902
958171AF2-111 GEN
Solar/Wind Harmer
22.344
252507AC2-088 GEN
Solar/Wind Harmer
0.399
25196008MFTGT1
Adder
1.685
252519AF1-045_GEN
Solar/Wind Harmer
4.531
25194608D.CRK4
Adder
2.03
25196608WSDLE5
Adder
10.55
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
10.955
970193AG2-126 GEN
Solar/Wind Harmer
12.34
24728705AND G3
Adder
9.433
24728505AND G1
Adder
4.51
253394AE2-221_GEN
Solar/Wind Harmer
0
962771AG1-126 GEN
Solar/Wind Harmer
32.057
970153AG2-106 GEN
Solar/Wind Harmer
20.471
3147312GRETNA
Solar/Wind Harmer
0.122
3146802CHATHAM
Solar/Wind Harmer
0.115
941801AE2-185 GEN
Solar/Wind Harmer
4.901
942481AE2-261 GEN
Solar/Wind Harmer
24.006
957381AF2-032 GEN
Solar/Wind Harmer
1.818
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
3.664
24386205FR-12G C
Solar/Wind Harmer
0
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.862
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
7.832
270004AE1-209 GEN
Solar/Wind Harmer
1.692
965091AG1-374 GEN
Solar/Wind Harmer
23.422
959611AF2-252 GEN
Solar/Wind Harmer
2.602
970825AG2-519 GEN
Solar/Wind Harmer
5.878
946031AF1-268 GEN
Solar/Wind Harmer
7.4
253370AE2-315 SEC1
Adder
2.225
253371AE2-315 SEC2
Adder
2.104
965931AG1-462 GEN
Solar/Wind Harmer
19.72
971087AG2-675 GEN
Solar/Wind Harmer
4.124
3147123OTTER R
Solar/Wind Harmer
0.087
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.257
970191AG2-125 GEN
Solar/Wind Harmer
1.979
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
10.206
274767LEE CO EC;8U
Adder
10.085
970571AG2-364 GEN
Solar/Wind Harmer
15.299
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
11.443
959091AF2-200 GEN
Solar/Wind Harmer
15.232
274855GSG-6 ;RU
Solar/Wind Harmer
0.277
274850MENDOTA H;RU
Solar/Wind Harmer
0.088
946671AF1-331 GEN
Solar/Wind Harmer
0.811
276868AE1-113 GEN
Solar/Wind Harmer
1.52
274879MINONK ;1U
Solar/Wind Harmer
0.317
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
19.478
274862TOP CROP ;2U
Solar/Wind Harmer
1.021
943121AE2-341 GEN
Solar/Wind Harmer
12.644
943591AF1-030 GEN
Solar/Wind Harmer
8.409
939351AE1-166 GEN
Solar/Wind Harmer
0
274729ELWOOD EC;1P
Adder
17.715
274730ELWOOD EC;6P
Adder
17.715
274734ELWOOD EC;8P
Adder
17.715
274736ELWOOD EC;9P
Adder
17.715
970707AG2-453 GEN
Solar/Wind Harmer
24.521
274887GEN-1.85
Solar/Wind Harmer
0.195
276843GEN-1.7
Solar/Wind Harmer
0.242
276806AD2-047 C O1
Solar/Wind Harmer
4.245
237048AF1-022 C
Solar/Wind Helper
0.185
237046AF1-021 C
Solar/Wind Helper
0.318
964991AG1-363 GEN
Solar/Wind Helper
3.731
238127S14_GEN_2
Solar/Wind Helper
0.692
23562501BACKB
Solar/Wind Helper
0.87
202652Y1-033 WT C
Solar/Wind Helper
0.538
238108AE1-109 GEN1
Solar/Wind Helper
0.089
238110AE1-109 GEN3
Solar/Wind Helper
0.089
20092526R32
Solar/Wind Helper
1.061
235058AG1-386 C
Solar/Wind Helper
0.381
270594AE1-207 GEN
Solar/Wind Harmer
8.772
270032AE2-172
Solar/Wind Harmer
5.222
270005AE1-210 C O1
Solar/Wind Harmer
1.692
970825AG2-519 GEN
Solar/Wind Harmer
2.77
270273AD2-016 GEN
Solar/Wind Harmer
0.795
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
10.877
253370AE2-315 SEC1
Adder
2.225
253371AE2-315 SEC2
Adder
2.104
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.302
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
9.607
276708O09 GEN2
Solar/Wind Harmer
0.271
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
10.206
274766LEE CO EC;7U
Adder
10.085
970569AG2-363 GEN
Solar/Wind Harmer
22.948
970819AG2-516 GEN
Solar/Wind Harmer
9.157
274822ROCKFORD ;11
Adder
21.436
957471AF2-041 GEN
Solar/Wind Harmer
22.848
959081AF2-199 GEN
Solar/Wind Harmer
7.616
971067AG2-660 GEN
Solar/Wind Harmer
2.539
945371AF1-202 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
5.694
971997AH1-543 GEN
Solar/Wind Harmer
3.993
25326309TAIT D
Adder
1.195
276882AE2-255 GEN
Solar/Wind Harmer
0.887
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.865
274872LEEDK;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
7.216
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274828WAUKEGAN ;BP
Adder
11.976
274682WAUKEGAN ;7U
Adder
19.478
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.228
274745AC1-111 GEN9
Adder
6.042
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
3.264
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
17.715
274674JOLIET 9 ;6U
Adder
16.589
274676JOLIET 29;8U
Adder
11.649
270055AF2-134 C O1
Solar/Wind Harmer
0
238185AF2-356 C
Solar/Wind Helper
2.199
238120AE2-309 GEN
Solar/Wind Helper
0.436
238126S14_GEN_1
Solar/Wind Helper
0.692
23583801GRNGAP
Solar/Wind Helper
4.116
316095T157 G97
Solar/Wind Helper
1.102
238109AE1-109 GEN2
Solar/Wind Helper
0.089
20089026BF_G21_K23
Solar/Wind Helper
0.441
20084626FORWARD
Solar/Wind Helper
0.325
964201AG1-281 GEN
Solar/Wind Helper
0.442
CPLELTFEXP_CPLE->PJM
CLTF
7.73
CBM West 2LTFEXP_CBM-W2->PJM
CBM
161.379
NYPJM->LTFIMP_NY
CLTF
5.307
LGEELTFEXP_LGEE->PJM
CLTF
8.953
WECLTFEXP_WEC->PJM
CLTF
4.181
AG2-052LTFEXP_AG2-052->PJM
LTF
0.252
AH1-155LTFEXP_AH1-155->PJM
LTF
0.378
LAGNLTFEXP_LAGN->PJM
CLTF
24.264
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.864
TVALTFEXP_TVA->PJM
CLTF
12.601
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.837
CBM South 1LTFEXP_CBM-S1->PJM
CBM
47.616
MECLTFEXP_MEC->PJM
CLTF
19.089
SIGELTFEXP_SIGE->PJM
CLTF
0.657

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P7-1_#10944___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10944___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:105.86 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5846.6
MW Contribution:
20.26
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
243186AF1-051 GEN
50/50
12.616
24721705FLATG2
50/50
39.51
24723005RIVRG1
Adder
36.981
24723105RIVRG2
Adder
36.981
970913AG2-568 GEN
Solar/Wind Harmer
11.393
24728205BUCHG1
Adder
6.959
927014AC1-188 GEN
Solar/Wind Harmer
2.439
971225AH1-072 GEN
Solar/Wind Harmer
3.033
971227AH1-073 GEN
Solar/Wind Harmer
3.033
270214AC2-123 GEN
Solar/Wind Harmer
3.2
971277AH1-098 GEN
Solar/Wind Harmer
5.471
971073AG2-665 GEN
Solar/Wind Harmer
10.456
970879AG2-548 GEN
Solar/Wind Harmer
1.52
270583AD2-179 GEN
Solar/Wind Harmer
12.855
962581AG1-107 GEN
Solar/Wind Harmer
6.12
961491AF2-440 GEN
Solar/Wind Harmer
2.543
942891AE2-308 GEN
Solar/Wind Harmer
12.112
972043AH1-570 GEN
Solar/Wind Harmer
3.018
972045AH1-571 GEN
Solar/Wind Harmer
2.414
971125AH1-004 GEN
Solar/Wind Harmer
4.793
970107AG2-081 GEN
Solar/Wind Harmer
3.595
339231AF1-038_GEN
Solar/Wind Harmer
2.155
966021AG1-471 GEN
Solar/Wind Harmer
6.374
971485AH1-239 GEN
Solar/Wind Harmer
9.429
252509AD1-136 GEN
Solar/Wind Harmer
0.301
339236AF1-050_GEN
Solar/Wind Harmer
2.122
964571AG1-320 GEN
Solar/Wind Harmer
9.57
964781AG1-341 GEN
Solar/Wind Harmer
12.309
25183208HLCRTG
Solar/Wind Harmer
6.902
25194408D.CRK1
Adder
8.538
25194508D.CRK3
Adder
1.596
945391AF1-204 GEN
Solar/Wind Harmer
14.618
24728805RICHG1
Adder
3.92
24728905RICHG2
Adder
3.92
253415AE1-040 GEN
Solar/Wind Harmer
1.157
276916AD2-100_GEN
Solar/Wind Harmer
21.377
276911AD2-131_GEN
Solar/Wind Harmer
4.32
970241AG2-163 GEN
Solar/Wind Harmer
25.444
926881AC1-175 GEN
Solar/Wind Harmer
5.627
276615X2-022 GEN
Solar/Wind Harmer
1.968
276838X2-022 GEN2
Solar/Wind Harmer
0.234
24725505WLD G2 C
Solar/Wind Harmer
3.981
24699105WLD G1 C
Solar/Wind Harmer
3.935
274880W4-005 GEN4
Solar/Wind Harmer
3.022
276174W4-005 GEN2
Solar/Wind Harmer
3.022
270383AD1-128 GEN
Solar/Wind Harmer
6.1
24387305FR-4G C
Solar/Wind Harmer
5.075
966841AG1-555 GEN
Solar/Wind Harmer
2.508
970291AG2-192 GEN
Solar/Wind Harmer
1.283
970291AG2-192 GEN
Solar/Wind Harmer
0.413
270180AB1-006 GEN1
Solar/Wind Harmer
7.075
253370AE2-315 SEC1
Adder
1.937
247621Y3-024
Adder
0.23
274764LEE CO EC;5U
Adder
8.891
274765LEE CO EC;6U
Adder
8.891
274762LEE CO EC;3U
Adder
8.871
274763LEE CO EC;4U
Adder
8.787
972235AH1-702 GEN1
Adder
2.391
972236AH1-702 GEN2
Adder
2.08
25322209TAIT E
Adder
9.19
25322209TAIT E
Adder
8.984
274683WAUKEGAN ;8U
Adder
19.789
274683WAUKEGAN ;8U
Adder
16.681
274696ROCKY RD ;4P
Adder
10.699
274695ROCKY RD ;2P
Adder
10.452
274693ROCKY RD ;1P
Adder
10.349
274697ROCKY RD ;3P
Adder
2.839
274674JOLIET 9 ;6U
Adder
14.342
237043AE2-125 C
Solar/Wind Helper
0.175
254304AE2-114 C
Solar/Wind Helper
0.213
254305AE2-115 C
Solar/Wind Helper
0.213
962101AG1-054 GEN
Solar/Wind Helper
0.63
241967AE2-285_GEN
Solar/Wind Helper
0.617
241801AE1-079 GEN
Solar/Wind Helper
0.241
23585401KL_K28_T16
Solar/Wind Helper
1.231
23751201ROTHROCK
Solar/Wind Helper
0.704
235054AD2-180 GEN
Solar/Wind Helper
1.627
946071AF1-272 GEN
Solar/Wind Helper
2.555
238117U2-030
Solar/Wind Helper
0.274
20083426SW_E13_K22
Solar/Wind Helper
0.053
20088826HIGHLAND
Solar/Wind Helper
0.842
235531U2-073 GEN
Solar/Wind Helper
2.597
203818AF1-086 GEN
Solar/Wind Helper
1.582
203961AE2-224 GEN
Solar/Wind Helper
2.25
946381AF1-302 GEN
Solar/Wind Helper
0.208
203853AF1-134 C O1
Solar/Wind Helper
0.446
203946AE2-131 C
Solar/Wind Helper
0.441
203804AE2-113_GEN
Solar/Wind Helper
1.63
24721605FLATG1
50/50
2.66
957241AF2-018 GEN
Solar/Wind Harmer
7.904
270053AF1-130 C
Solar/Wind Harmer
31.582
270399AC1-101 GEN
Solar/Wind Harmer
7.458
270400AC1-102 GEN
Solar/Wind Harmer
7.458
941621AE2-160 GEN
Adder
5.547
970281AG2-184 GEN
Solar/Wind Harmer
32.31
971313AH1-133 GEN
Solar/Wind Harmer
9.046
971061AG2-657 GEN
Solar/Wind Harmer
13.699
971985AH1-537 GEN
Solar/Wind Harmer
26.806
962211AG1-066 GEN
Solar/Wind Harmer
3.513
24734705WLF1G3
Adder
8.136
24734805WLF1G4
Adder
8.136
24734905WLF1G5
Adder
8.136
24735105WLF2G1
Adder
7.967
966391AG1-508 GEN
Solar/Wind Harmer
4.767
971331AH1-145 GEN
Solar/Wind Harmer
12.423
971329AH1-144 GEN
Solar/Wind Harmer
7.935
971981AH1-535 GEN
Solar/Wind Harmer
12.575
972163AH1-664 GEN
Solar/Wind Harmer
12.156
972165AH1-665 GEN
Solar/Wind Harmer
9.725
3429211JKCT 2G
Adder
14.123
270291AC1-194 GEN
Solar/Wind Harmer
6.12
339216AC1-074 GEN
Solar/Wind Harmer
2.003
25196108MFTGT2
Adder
1.756
25196108MFTGT2
Adder
1.631
25196408WSDLE3
Adder
9.915
25196308WSDLE2
Adder
9.829
25196208WSDLE1
Adder
9.804
25196708WSDLE6
Adder
9.779
25196508WSDLE4
Adder
9.533
270444AC2-157 GEN1
Solar/Wind Harmer
6.262
270445AC2-157 GEN2
Solar/Wind Harmer
6.262
270069AE2-166 C O1
Solar/Wind Harmer
10.085
253433AC1-085 GEN1
Solar/Wind Harmer
5.787
253432AC1-085 GEN2
Solar/Wind Harmer
0.291
253406AD2-031_GEN
Solar/Wind Harmer
1.368
270340AC2-060 GEN
Solar/Wind Harmer
3.206
270263AC1-001 GEN
Solar/Wind Harmer
1.104
270356AE2-297 GEN
Solar/Wind Harmer
4.818
944221AF1-090 GEN
Solar/Wind Harmer
11.234
963841AG1-237 GEN
Solar/Wind Harmer
11.024
276763AC1-053 GEN1
Solar/Wind Harmer
3.957
276764AC1-053 GEN2
Solar/Wind Harmer
3.957
276668AB2-070 GEN1
Solar/Wind Harmer
2.213
276848AB2-070 GEN3
Solar/Wind Harmer
2.213
276849AB2-070 GEN2
Solar/Wind Harmer
2.213
24386405FR-21G C
Solar/Wind Harmer
4.297
24387005FR-3G C
Solar/Wind Harmer
3.952
970289AG2-191 GEN
Solar/Wind Harmer
1.875
25306009OHH W.
Adder
2.793
253372AE2-315 SEC3
Adder
1.832
253372AE2-315 SEC3
Adder
1.832
972267AH1-718 GEN
Adder
3.983
274823ROCKFORD ;21
Adder
18.472
274744AC1-111 GEN8
Adder
5.228
274746AC1-111 G10
Adder
5.228
274728ELWOOD EC;5P
Adder
15.317
274731ELWOOD EC;2P
Adder
15.317
274733ELWOOD EC;3P
Adder
15.317
274735ELWOOD EC;4P
Adder
15.317
274675JOLIET 29;7U
Adder
28.551
23750501ELLIOTTS
Solar/Wind Helper
0.647
23652301WDPWR_K20
Solar/Wind Helper
0.14
241997AF1-093 GEN
Solar/Wind Helper
0.247
241985AE1-237 GEN
Solar/Wind Helper
0.241
241982AE2-343 S C
Solar/Wind Helper
0.216
203955AF1-039 C O1
Solar/Wind Helper
0.355
23750701CROSSCHOOL
Solar/Wind Helper
1.137
20089126CSLMN_L13
Solar/Wind Helper
0.564
20089226LOOKOUT
Solar/Wind Helper
0.562
238118U2-030_1
Solar/Wind Helper
0.274
20088926STNY CRK
Solar/Wind Helper
0.77
203940AF1-140 C
Solar/Wind Helper
0.371
20094526CT_V3-030
Solar/Wind Helper
0.443
203846AF2-130 C
Solar/Wind Helper
0.428
20088626ARWF_N39
Solar/Wind Helper
1.129
946581AF1-322 GEN
Solar/Wind Harmer
3.68
24289405MTG1
50/50
11.749
24318705GVG2
50/50
11.694
24722005FLATG5
50/50
2.66
24721905FLATG4
50/50
48.595
270330AC1-082 GEN2
Solar/Wind Harmer
0.934
270329AC1-082 GEN1
Solar/Wind Harmer
0.934
24686405CER G5
Adder
16.065
971191AH1-055 GEN
Solar/Wind Harmer
33.049
960911AF2-382 GEN
Solar/Wind Harmer
11.685
957541AF2-048 GEN
Solar/Wind Harmer
2.439
972103AH1-617 GEN
Solar/Wind Harmer
30.771
971461AH1-227 GEN
Solar/Wind Harmer
7.779
270346AE1-212 GEN
Solar/Wind Harmer
13.204
943031AE2-326 GEN
Solar/Wind Harmer
5.037
970879AG2-548 GEN
Solar/Wind Harmer
10.456
958121AF2-106 GEN
Solar/Wind Harmer
5.826
270186AC1-089 GEN
Solar/Wind Harmer
7.579
270367AC2-061_GEN
Solar/Wind Harmer
3.93
970093AG2-073 GEN
Solar/Wind Harmer
6.439
972167AH1-666 GEN
Solar/Wind Harmer
9.688
972273AH1-721 GEN
Adder
100.618
3429391JKCT 9G
Adder
9.999
339243AC2-075 GEN1
Solar/Wind Harmer
0.542
339206AE1-143 GEN
Solar/Wind Harmer
2.528
970455AG2-298 GEN
Solar/Wind Harmer
4.124
252507AC2-088 GEN
Solar/Wind Harmer
2.108
958171AF2-111 GEN
Solar/Wind Harmer
29.368
970653AG2-424 GEN
Solar/Wind Harmer
0.818
339255AE2-071 GEN
Solar/Wind Harmer
1.366
339250AF1-203 GEN
Solar/Wind Harmer
0.703
25196008MFTGT1
Adder
1.543
252519AF1-045_GEN
Solar/Wind Harmer
4.153
25194608D.CRK4
Adder
1.856
252524AE2-267 GEN
Solar/Wind Harmer
1.77
25196608WSDLE5
Adder
9.632
270030AE2-140 GEN
Solar/Wind Harmer
21.915
253317AC1-085 GEN4
Solar/Wind Harmer
9.117
946181AF1-283 GEN
Solar/Wind Harmer
14.157
970193AG2-126 GEN
Solar/Wind Harmer
15.734
24728705AND G3
Adder
8.411
24728505AND G1
Adder
4.021
253394AE2-221_GEN
Solar/Wind Harmer
4.748
942481AE2-261 GEN
Solar/Wind Harmer
30.351
957381AF2-032 GEN
Solar/Wind Harmer
2.028
962771AG1-126 GEN
Solar/Wind Harmer
32.808
970153AG2-106 GEN
Solar/Wind Harmer
14.306
24379505HDWTR1G C
Solar/Wind Harmer
7.972
270240V3-007_GEN2
Solar/Wind Harmer
6.237
276785W4-005 GEN1
Solar/Wind Harmer
3.022
971993AH1-541 GEN
Solar/Wind Harmer
9.233
24386205FR-12G C
Solar/Wind Harmer
4.281
247642Z2-115 C
Solar/Wind Harmer
0.063
965461AG1-414 GEN
Solar/Wind Harmer
2.238
970289AG2-191 GEN
Solar/Wind Harmer
0.757
270004AE1-209 GEN
Solar/Wind Harmer
5.379
24690905MDL-1G C
Solar/Wind Harmer
7.897
253370AE2-315 SEC1
Adder
1.937
253371AE2-315 SEC2
Adder
1.832
274760LEE CO EC;1U
Adder
8.871
274767LEE CO EC;8U
Adder
8.766
274682WAUKEGAN ;7U
Adder
16.869
274729ELWOOD EC;1P
Adder
15.317
274730ELWOOD EC;6P
Adder
15.317
274734ELWOOD EC;8P
Adder
15.317
274736ELWOOD EC;9P
Adder
15.317
237048AF1-022 C
Solar/Wind Helper
0.19
235058AG1-386 C
Solar/Wind Helper
0.455
237046AF1-021 C
Solar/Wind Helper
0.331
202652Y1-033 WT C
Solar/Wind Helper
0.537
23562501BACKB
Solar/Wind Helper
0.856
964991AG1-363 GEN
Solar/Wind Helper
3.486
20092526R32
Solar/Wind Helper
1.091
238127S14_GEN_2
Solar/Wind Helper
0.645
20303426NA_O38_P22
Solar/Wind Helper
0.926
203993AD2-133_GEN1
Solar/Wind Helper
0.956
24289405MTG1
50/50
11.749
243186AF1-051 GEN
50/50
12.616
24318705GVG2
50/50
11.694
24721805FLATG3
50/50
2.66
960001AF2-291 GEN
Solar/Wind Harmer
6.049
24723205RIVRG3
Adder
36.981
270331AC1-082 GEN3
Solar/Wind Harmer
0.937
24686505CER G6
Adder
16.193
972203AH1-686 GEN
Adder
4.427
944971AF1-162 GEN
Solar/Wind Harmer
12.449
971403AH1-188 GEN
Solar/Wind Harmer
24.722
24728305BUCHG2
Adder
6.959
971687AH1-348 GEN
Solar/Wind Harmer
1.517
24735205WLF2G2
Adder
7.967
971073AG2-665 GEN
Solar/Wind Harmer
1.52
970091AG2-072 GEN
Adder
94.28
945681AF1-233 GEN
Solar/Wind Harmer
22.855
3429241JKCT 3G
Adder
14.309
339221AD2-048_GEN
Solar/Wind Harmer
1.847
339211AE2-254 GEN
Solar/Wind Harmer
1.818
3429421JKCT 10G
Adder
9.999
943111AE2-339 GEN
Solar/Wind Harmer
1.059
339241AF1-083 GEN
Solar/Wind Harmer
1.958
970653AG2-424 GEN
Solar/Wind Harmer
5.656
964901AG1-354 GEN
Solar/Wind Harmer
17.533
25196808ZIMRHP
Adder
87.559
25196008MFTGT1
Adder
1.593
252516AE2-318_GEN
Solar/Wind Harmer
11.412
252510AF1-249 C
Solar/Wind Harmer
0.473
25194608D.CRK4
Adder
1.856
270336AE1-100 GEN
Solar/Wind Harmer
1.934
253316AC1-085 GEN3
Solar/Wind Harmer
9.117
946171AF1-282 GEN
Solar/Wind Harmer
10.89
943811AF1-049 GEN
Solar/Wind Harmer
4.052
24728605AND G2
Adder
4.021
253398AE2-221_GEN2
Solar/Wind Harmer
4.748
270222AC2-111 GEN
Solar/Wind Harmer
4.662
944031AF1-071 GEN
Solar/Wind Harmer
1.049
963741AG1-226 GEN
Solar/Wind Harmer
45.799
965911AG1-460 GEN
Solar/Wind Harmer
1.416
962761AG1-125 GEN
Solar/Wind Harmer
32.808
970149AG2-104 GEN
Solar/Wind Harmer
20.259
970155AG2-107 GEN
Solar/Wind Harmer
14.306
942081AE2-220 GEN
Solar/Wind Harmer
6.447
270209AC1-174_GEN
Solar/Wind Harmer
4.103
270437AC2-090 C
Solar/Wind Harmer
5.627
270239V3-007_GEN1
Solar/Wind Harmer
1.735
276621W2-048 GEN
Solar/Wind Harmer
6.266
276686W4-005 GEN3
Solar/Wind Harmer
3.022
24385905FR-11G C
Solar/Wind Harmer
8.303
24386605FR-22G C
Solar/Wind Harmer
4.297
276903AD2-071 C
Solar/Wind Harmer
9.98
270594AE1-207 GEN
Solar/Wind Harmer
13.398
270032AE2-172
Solar/Wind Harmer
4.588
270005AE1-210 C O1
Solar/Wind Harmer
5.379
253370AE2-315 SEC1
Adder
1.937
253371AE2-315 SEC2
Adder
1.832
274761LEE CO EC;2U
Adder
8.871
274766LEE CO EC;7U
Adder
8.766
274822ROCKFORD ;11
Adder
18.607
25326309TAIT D
Adder
1.032
274828WAUKEGAN ;BP
Adder
10.373
274682WAUKEGAN ;7U
Adder
16.869
274745AC1-111 GEN9
Adder
5.228
274732ELWOOD EC;7P
Adder
15.317
274674JOLIET 9 ;6U
Adder
14.342
274676JOLIET 29;8U
Adder
10.069
254303AC2-168 GEN
Solar/Wind Helper
0.154
241966AE1-183 GEN
Solar/Wind Helper
0.247
238185AF2-356 C
Solar/Wind Helper
2.102
20089026BF_G21_K23
Solar/Wind Helper
0.446
20084626FORWARD
Solar/Wind Helper
0.335
964201AG1-281 GEN
Solar/Wind Helper
0.452
238126S14_GEN_1
Solar/Wind Helper
0.645
20091526CHSTN_FL
Solar/Wind Helper
0.544
238120AE2-309 GEN
Solar/Wind Helper
0.406
20090526Q36
Solar/Wind Helper
0.956
203952AE2-129 C
Solar/Wind Helper
0.441
CPLELTFEXP_CPLE->PJM
CLTF
7.221
CBM West 2LTFEXP_CBM-W2->PJM
CBM
143.77
NYPJM->LTFIMP_NY
CLTF
5.068
LGEELTFEXP_LGEE->PJM
CLTF
8.183
WECLTFEXP_WEC->PJM
CLTF
3.631
AG2-052LTFEXP_AG2-052->PJM
LTF
0.218
AH1-155LTFEXP_AH1-155->PJM
LTF
0.328
LAGNLTFEXP_LAGN->PJM
CLTF
21.601
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.934
TVALTFEXP_TVA->PJM
CLTF
11.244
CBM West 1LTFEXP_CBM-W1->PJM
CBM
120.748
CBM South 1LTFEXP_CBM-S1->PJM
CBM
42.677
MECLTFEXP_MEC->PJM
CLTF
16.745
SIGELTFEXP_SIGE->PJM
CLTF
0.592

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P7-1_#10856___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10856___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:101.88 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5626.94
MW Contribution:
20.51
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
2.675
957241AF2-018 GEN
Solar/Wind Harmer
7.959
270053AF1-130 C
Solar/Wind Harmer
31.802
270399AC1-101 GEN
Solar/Wind Harmer
7.511
270400AC1-102 GEN
Solar/Wind Harmer
7.511
941621AE2-160 GEN
Adder
5.587
970281AG2-184 GEN
Solar/Wind Harmer
32.57
971313AH1-133 GEN
Solar/Wind Harmer
9.12
971061AG2-657 GEN
Solar/Wind Harmer
13.811
971985AH1-537 GEN
Solar/Wind Harmer
27.028
962211AG1-066 GEN
Solar/Wind Harmer
3.543
24734705WLF1G3
Adder
8.207
24734805WLF1G4
Adder
8.207
24734905WLF1G5
Adder
8.207
24735105WLF2G1
Adder
8.038
966391AG1-508 GEN
Solar/Wind Harmer
4.81
971331AH1-145 GEN
Solar/Wind Harmer
12.539
971329AH1-144 GEN
Solar/Wind Harmer
8.009
24289405MTG1
50/50
11.803
243186AF1-051 GEN
50/50
12.678
24318705GVG2
50/50
11.752
24721805FLATG3
50/50
2.675
960001AF2-291 GEN
Solar/Wind Harmer
6.087
24723205RIVRG3
Adder
37.214
270331AC1-082 GEN3
Solar/Wind Harmer
0.942
24686505CER G6
Adder
16.296
972203AH1-686 GEN
Adder
4.456
944971AF1-162 GEN
Solar/Wind Harmer
12.535
971403AH1-188 GEN
Solar/Wind Harmer
24.896
24728305BUCHG2
Adder
7.015
971687AH1-348 GEN
Solar/Wind Harmer
1.53
24735205WLF2G2
Adder
8.038
971073AG2-665 GEN
Solar/Wind Harmer
1.534
970091AG2-072 GEN
Adder
95.233
945681AF1-233 GEN
Solar/Wind Harmer
23.089
3429241JKCT 3G
Adder
14.456
339221AD2-048_GEN
Solar/Wind Harmer
1.866
339211AE2-254 GEN
Solar/Wind Harmer
1.837
3429421JKCT 10G
Adder
10.103
943111AE2-339 GEN
Solar/Wind Harmer
1.07
339241AF1-083 GEN
Solar/Wind Harmer
1.979
970653AG2-424 GEN
Solar/Wind Harmer
5.716
964901AG1-354 GEN
Solar/Wind Harmer
17.72
25196808ZIMRHP
Adder
88.501
25196008MFTGT1
Adder
1.61
252516AE2-318_GEN
Solar/Wind Harmer
11.536
252510AF1-249 C
Solar/Wind Harmer
0.479
25194608D.CRK4
Adder
1.876
270336AE1-100 GEN
Solar/Wind Harmer
1.956
253316AC1-085 GEN3
Solar/Wind Harmer
9.221
946171AF1-282 GEN
Solar/Wind Harmer
11.014
943811AF1-049 GEN
Solar/Wind Harmer
4.099
24728605AND G2
Adder
4.069
253398AE2-221_GEN2
Solar/Wind Harmer
4.804
270222AC2-111 GEN
Solar/Wind Harmer
4.717
944031AF1-071 GEN
Solar/Wind Harmer
1.061
963741AG1-226 GEN
Solar/Wind Harmer
46.357
965911AG1-460 GEN
Solar/Wind Harmer
1.434
962761AG1-125 GEN
Solar/Wind Harmer
33.21
970149AG2-104 GEN
Solar/Wind Harmer
20.507
970155AG2-107 GEN
Solar/Wind Harmer
14.481
942081AE2-220 GEN
Solar/Wind Harmer
6.527
270209AC1-174_GEN
Solar/Wind Harmer
4.153
270437AC2-090 C
Solar/Wind Harmer
5.696
270239V3-007_GEN1
Solar/Wind Harmer
1.756
276621W2-048 GEN
Solar/Wind Harmer
6.343
276686W4-005 GEN3
Solar/Wind Harmer
3.059
24385905FR-11G C
Solar/Wind Harmer
8.406
24386605FR-22G C
Solar/Wind Harmer
4.35
276903AD2-071 C
Solar/Wind Harmer
10.104
270594AE1-207 GEN
Solar/Wind Harmer
13.567
270032AE2-172
Solar/Wind Harmer
4.646
270005AE1-210 C O1
Solar/Wind Harmer
5.447
253370AE2-315 SEC1
Adder
1.962
253371AE2-315 SEC2
Adder
1.855
243186AF1-051 GEN
50/50
12.678
24721705FLATG2
50/50
39.728
24723005RIVRG1
Adder
37.214
24723105RIVRG2
Adder
37.214
970913AG2-568 GEN
Solar/Wind Harmer
11.477
24728205BUCHG1
Adder
7.015
927014AC1-188 GEN
Solar/Wind Harmer
2.459
971225AH1-072 GEN
Solar/Wind Harmer
3.058
971227AH1-073 GEN
Solar/Wind Harmer
3.058
270214AC2-123 GEN
Solar/Wind Harmer
3.229
971277AH1-098 GEN
Solar/Wind Harmer
5.52
971073AG2-665 GEN
Solar/Wind Harmer
10.556
970879AG2-548 GEN
Solar/Wind Harmer
1.534
270583AD2-179 GEN
Solar/Wind Harmer
12.98
962581AG1-107 GEN
Solar/Wind Harmer
6.183
961491AF2-440 GEN
Solar/Wind Harmer
2.569
942891AE2-308 GEN
Solar/Wind Harmer
12.236
972043AH1-570 GEN
Solar/Wind Harmer
3.049
972045AH1-571 GEN
Solar/Wind Harmer
2.439
971125AH1-004 GEN
Solar/Wind Harmer
4.843
970107AG2-081 GEN
Solar/Wind Harmer
3.632
339231AF1-038_GEN
Solar/Wind Harmer
2.178
966021AG1-471 GEN
Solar/Wind Harmer
6.442
971485AH1-239 GEN
Solar/Wind Harmer
9.528
252509AD1-136 GEN
Solar/Wind Harmer
0.304
339236AF1-050_GEN
Solar/Wind Harmer
2.145
964571AG1-320 GEN
Solar/Wind Harmer
9.672
964781AG1-341 GEN
Solar/Wind Harmer
12.441
25183208HLCRTG
Solar/Wind Harmer
6.977
25194408D.CRK1
Adder
8.632
25194508D.CRK3
Adder
1.614
945391AF1-204 GEN
Solar/Wind Harmer
14.791
24728805RICHG1
Adder
3.967
24728905RICHG2
Adder
3.967
253415AE1-040 GEN
Solar/Wind Harmer
1.171
276916AD2-100_GEN
Solar/Wind Harmer
21.637
276911AD2-131_GEN
Solar/Wind Harmer
4.373
970241AG2-163 GEN
Solar/Wind Harmer
25.754
926881AC1-175 GEN
Solar/Wind Harmer
5.696
276615X2-022 GEN
Solar/Wind Harmer
1.992
276838X2-022 GEN2
Solar/Wind Harmer
0.237
24725505WLD G2 C
Solar/Wind Harmer
4.03
24699105WLD G1 C
Solar/Wind Harmer
3.983
274880W4-005 GEN4
Solar/Wind Harmer
3.059
276174W4-005 GEN2
Solar/Wind Harmer
3.059
270383AD1-128 GEN
Solar/Wind Harmer
6.175
24387305FR-4G C
Solar/Wind Harmer
5.138
966841AG1-555 GEN
Solar/Wind Harmer
2.539
970291AG2-192 GEN
Solar/Wind Harmer
1.299
970291AG2-192 GEN
Solar/Wind Harmer
0.418
270180AB1-006 GEN1
Solar/Wind Harmer
7.164
253370AE2-315 SEC1
Adder
1.962
247621Y3-024
Adder
0.233
274764LEE CO EC;5U
Adder
9.007
971981AH1-535 GEN
Solar/Wind Harmer
12.699
972163AH1-664 GEN
Solar/Wind Harmer
12.28
972165AH1-665 GEN
Solar/Wind Harmer
9.824
3429211JKCT 2G
Adder
14.268
270291AC1-194 GEN
Solar/Wind Harmer
6.183
339216AC1-074 GEN
Solar/Wind Harmer
2.024
25196108MFTGT2
Adder
1.775
25196108MFTGT2
Adder
1.648
25196408WSDLE3
Adder
10.024
25196308WSDLE2
Adder
9.937
25196208WSDLE1
Adder
9.912
25196708WSDLE6
Adder
9.887
25196508WSDLE4
Adder
9.638
270444AC2-157 GEN1
Solar/Wind Harmer
6.331
270445AC2-157 GEN2
Solar/Wind Harmer
6.331
270069AE2-166 C O1
Solar/Wind Harmer
10.196
253433AC1-085 GEN1
Solar/Wind Harmer
5.853
253432AC1-085 GEN2
Solar/Wind Harmer
0.295
253406AD2-031_GEN
Solar/Wind Harmer
1.384
270340AC2-060 GEN
Solar/Wind Harmer
3.244
270263AC1-001 GEN
Solar/Wind Harmer
1.117
270356AE2-297 GEN
Solar/Wind Harmer
4.876
944221AF1-090 GEN
Solar/Wind Harmer
11.369
963841AG1-237 GEN
Solar/Wind Harmer
11.16
276763AC1-053 GEN1
Solar/Wind Harmer
4.006
276764AC1-053 GEN2
Solar/Wind Harmer
4.006
276668AB2-070 GEN1
Solar/Wind Harmer
2.24
276848AB2-070 GEN3
Solar/Wind Harmer
2.24
276849AB2-070 GEN2
Solar/Wind Harmer
2.24
24386405FR-21G C
Solar/Wind Harmer
4.35
24289405MTG1
50/50
11.803
24318705GVG2
50/50
11.752
24722005FLATG5
50/50
2.675
24721905FLATG4
50/50
48.862
270330AC1-082 GEN2
Solar/Wind Harmer
0.94
270329AC1-082 GEN1
Solar/Wind Harmer
0.94
24686405CER G5
Adder
16.168
971191AH1-055 GEN
Solar/Wind Harmer
33.281
960911AF2-382 GEN
Solar/Wind Harmer
11.778
957541AF2-048 GEN
Solar/Wind Harmer
2.459
972103AH1-617 GEN
Solar/Wind Harmer
31.019
971461AH1-227 GEN
Solar/Wind Harmer
7.843
270346AE1-212 GEN
Solar/Wind Harmer
13.316
943031AE2-326 GEN
Solar/Wind Harmer
5.082
970879AG2-548 GEN
Solar/Wind Harmer
10.556
958121AF2-106 GEN
Solar/Wind Harmer
5.883
270186AC1-089 GEN
Solar/Wind Harmer
7.655
270367AC2-061_GEN
Solar/Wind Harmer
3.969
970093AG2-073 GEN
Solar/Wind Harmer
6.505
972167AH1-666 GEN
Solar/Wind Harmer
9.788
972273AH1-721 GEN
Adder
101.651
3429391JKCT 9G
Adder
10.103
339243AC2-075 GEN1
Solar/Wind Harmer
0.548
339206AE1-143 GEN
Solar/Wind Harmer
2.555
970455AG2-298 GEN
Solar/Wind Harmer
4.167
252507AC2-088 GEN
Solar/Wind Harmer
2.13
958171AF2-111 GEN
Solar/Wind Harmer
29.678
970653AG2-424 GEN
Solar/Wind Harmer
0.827
339255AE2-071 GEN
Solar/Wind Harmer
1.381
339250AF1-203 GEN
Solar/Wind Harmer
0.711
25196008MFTGT1
Adder
1.56
252519AF1-045_GEN
Solar/Wind Harmer
4.199
25194608D.CRK4
Adder
1.876
252524AE2-267 GEN
Solar/Wind Harmer
1.789
25196608WSDLE5
Adder
9.738
270030AE2-140 GEN
Solar/Wind Harmer
22.165
253317AC1-085 GEN4
Solar/Wind Harmer
9.221
946181AF1-283 GEN
Solar/Wind Harmer
14.318
970193AG2-126 GEN
Solar/Wind Harmer
15.92
24728705AND G3
Adder
8.51
24728505AND G1
Adder
4.069
253394AE2-221_GEN
Solar/Wind Harmer
4.804
942481AE2-261 GEN
Solar/Wind Harmer
30.722
957381AF2-032 GEN
Solar/Wind Harmer
2.053
962771AG1-126 GEN
Solar/Wind Harmer
33.21
970153AG2-106 GEN
Solar/Wind Harmer
14.481
24379505HDWTR1G C
Solar/Wind Harmer
8.07
270240V3-007_GEN2
Solar/Wind Harmer
6.314
276785W4-005 GEN1
Solar/Wind Harmer
3.059
971993AH1-541 GEN
Solar/Wind Harmer
9.348
24386205FR-12G C
Solar/Wind Harmer
4.335
247642Z2-115 C
Solar/Wind Harmer
0.064
274765LEE CO EC;6U
Adder
9.007
274762LEE CO EC;3U
Adder
8.986
274763LEE CO EC;4U
Adder
8.901
972235AH1-702 GEN1
Adder
2.423
972236AH1-702 GEN2
Adder
2.107
25322209TAIT E
Adder
9.312
25322209TAIT E
Adder
9.102
274683WAUKEGAN ;8U
Adder
20.05
274683WAUKEGAN ;8U
Adder
16.901
274696ROCKY RD ;4P
Adder
10.84
274695ROCKY RD ;2P
Adder
10.59
274693ROCKY RD ;1P
Adder
10.485
274697ROCKY RD ;3P
Adder
2.877
274674JOLIET 9 ;6U
Adder
14.533
237043AE2-125 C
Solar/Wind Helper
0.172
254304AE2-114 C
Solar/Wind Helper
0.21
254305AE2-115 C
Solar/Wind Helper
0.21
962101AG1-054 GEN
Solar/Wind Helper
0.622
241967AE2-285_GEN
Solar/Wind Helper
0.609
241801AE1-079 GEN
Solar/Wind Helper
0.238
23585401KL_K28_T16
Solar/Wind Helper
1.215
23751201ROTHROCK
Solar/Wind Helper
0.695
235054AD2-180 GEN
Solar/Wind Helper
1.606
946071AF1-272 GEN
Solar/Wind Helper
2.52
238117U2-030
Solar/Wind Helper
0.27
20083426SW_E13_K22
Solar/Wind Helper
0.052
20088826HIGHLAND
Solar/Wind Helper
0.83
235531U2-073 GEN
Solar/Wind Helper
2.561
203818AF1-086 GEN
Solar/Wind Helper
1.56
203961AE2-224 GEN
Solar/Wind Helper
2.218
946381AF1-302 GEN
Solar/Wind Helper
0.205
24387005FR-3G C
Solar/Wind Harmer
4.001
970289AG2-191 GEN
Solar/Wind Harmer
1.899
25306009OHH W.
Adder
2.828
253372AE2-315 SEC3
Adder
1.855
253372AE2-315 SEC3
Adder
1.855
972267AH1-718 GEN
Adder
4.035
274823ROCKFORD ;21
Adder
18.714
274744AC1-111 GEN8
Adder
5.298
274746AC1-111 G10
Adder
5.298
274728ELWOOD EC;5P
Adder
15.521
274731ELWOOD EC;2P
Adder
15.521
274733ELWOOD EC;3P
Adder
15.521
274735ELWOOD EC;4P
Adder
15.521
274675JOLIET 29;7U
Adder
28.931
23750501ELLIOTTS
Solar/Wind Helper
0.639
23652301WDPWR_K20
Solar/Wind Helper
0.139
241997AF1-093 GEN
Solar/Wind Helper
0.244
241985AE1-237 GEN
Solar/Wind Helper
0.238
241982AE2-343 S C
Solar/Wind Helper
0.214
203955AF1-039 C O1
Solar/Wind Helper
0.35
23750701CROSSCHOOL
Solar/Wind Helper
1.122
20089126CSLMN_L13
Solar/Wind Helper
0.556
20089226LOOKOUT
Solar/Wind Helper
0.555
238118U2-030_1
Solar/Wind Helper
0.27
20088926STNY CRK
Solar/Wind Helper
0.759
203940AF1-140 C
Solar/Wind Helper
0.366
20094526CT_V3-030
Solar/Wind Helper
0.437
203846AF2-130 C
Solar/Wind Helper
0.422
20088626ARWF_N39
Solar/Wind Helper
1.113
946581AF1-322 GEN
Solar/Wind Harmer
3.726
274761LEE CO EC;2U
Adder
8.986
274766LEE CO EC;7U
Adder
8.88
274822ROCKFORD ;11
Adder
18.851
25326309TAIT D
Adder
1.046
274828WAUKEGAN ;BP
Adder
10.51
274682WAUKEGAN ;7U
Adder
17.092
274745AC1-111 GEN9
Adder
5.298
274732ELWOOD EC;7P
Adder
15.521
274674JOLIET 9 ;6U
Adder
14.533
274676JOLIET 29;8U
Adder
10.203
254303AC2-168 GEN
Solar/Wind Helper
0.152
241966AE1-183 GEN
Solar/Wind Helper
0.244
238185AF2-356 C
Solar/Wind Helper
2.074
20089026BF_G21_K23
Solar/Wind Helper
0.44
20084626FORWARD
Solar/Wind Helper
0.33
964201AG1-281 GEN
Solar/Wind Helper
0.445
238126S14_GEN_1
Solar/Wind Helper
0.636
20091526CHSTN_FL
Solar/Wind Helper
0.536
238120AE2-309 GEN
Solar/Wind Helper
0.4
965461AG1-414 GEN
Solar/Wind Harmer
2.266
970289AG2-191 GEN
Solar/Wind Harmer
0.767
270004AE1-209 GEN
Solar/Wind Harmer
5.447
24690905MDL-1G C
Solar/Wind Harmer
7.997
253370AE2-315 SEC1
Adder
1.962
253371AE2-315 SEC2
Adder
1.855
274760LEE CO EC;1U
Adder
8.986
274767LEE CO EC;8U
Adder
8.88
274682WAUKEGAN ;7U
Adder
17.092
274729ELWOOD EC;1P
Adder
15.521
274730ELWOOD EC;6P
Adder
15.521
274734ELWOOD EC;8P
Adder
15.521
274736ELWOOD EC;9P
Adder
15.521
237048AF1-022 C
Solar/Wind Helper
0.188
235058AG1-386 C
Solar/Wind Helper
0.45
237046AF1-021 C
Solar/Wind Helper
0.327
202652Y1-033 WT C
Solar/Wind Helper
0.53
23562501BACKB
Solar/Wind Helper
0.844
964991AG1-363 GEN
Solar/Wind Helper
3.438
20092526R32
Solar/Wind Helper
1.076
238127S14_GEN_2
Solar/Wind Helper
0.636
20303426NA_O38_P22
Solar/Wind Helper
0.913
CPLELTFEXP_CPLE->PJM
CLTF
7.358
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.448
NYPJM->LTFIMP_NY
CLTF
4.988
LGEELTFEXP_LGEE->PJM
CLTF
8.269
WECLTFEXP_WEC->PJM
CLTF
3.678
AG2-052LTFEXP_AG2-052->PJM
LTF
0.221
AH1-155LTFEXP_AH1-155->PJM
LTF
0.332
LAGNLTFEXP_LAGN->PJM
CLTF
21.853
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.311
TVALTFEXP_TVA->PJM
CLTF
11.37
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.565
CBM South 1LTFEXP_CBM-S1->PJM
CBM
43.151
MECLTFEXP_MEC->PJM
CLTF
16.954
SIGELTFEXP_SIGE->PJM
CLTF
0.599
CONTINGENCY 'AEP_P4_#8975_05KAMMER 765_MM2_SRT-A'
 OPEN BRANCH FROM BUS 235111 TO BUS 235117 CKT 1   /*01 502 J     500.0 - 01KAMMER     500.0
 OPEN BRANCH FROM BUS 235117 TO BUS 242925 CKT 1   /*01KAMMER     500.0 - 05KAMMER     765.0
END
CONTINGENCY 'AP_P2-3_WP-500-DRT7A_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235111 TO BUS 235117 CKT 1          /*01 502 J     500.0 - 01KAMMER     500.0
 SET POSTCONTRATING 4289 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3546 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3753 BRANCH FROM BUS 235111 TO BUS 235098 CKT 1 /*01 502 J     500.0 - WOODSIDE     500.0
END
CONTINGENCY 'AP_P2-3_WP-500-DRT10A_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235111 TO BUS 235117 CKT 1          /*01 502 J     500.0 - 01KAMMER     500.0
 OPEN BRANCH FROM BUS 235111 TO BUS 235113 CKT 2                /*01 502 J     500.0 - 01 502JCT    138.0
 SET POSTCONTRATING 4289 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3546 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3753 BRANCH FROM BUS 235111 TO BUS 235098 CKT 1 /*01 502 J     500.0 - WOODSIDE     500.0
END
CONTINGENCY 'AP_P1-2_MP-500-028_SRT-A'
 DISCONNECT BRANCH FROM BUS 235111 TO BUS 235117 CKT 1   /*01 502 J     500.0 - 01KAMMER     500.0
 DISCONNECT BRANCH FROM BUS 235117 TO BUS 242925 CKT 1   /*01KAMMER     500.0 - 05KAMMER     765.0
END
CONTINGENCY 'AP_P1-3_MP-765-502T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235117 TO BUS 242925 CKT 1   /*01KAMMER     500.0 - 05KAMMER     765.0
END
CONTINGENCY 'AP_P2-3_MP-500-024_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 1   /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 2   /*01BELMNT     500.0 - 01BELMNT     138.0
END
CONTINGENCY 'AP_P2-3_MP-500-025_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 3   /*01BELMNT     500.0 - 01BELMNT     138.0
END
CONTINGENCY 'AP_P2-3_MP-500-015_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235100 CKT 2   /*01FLINTRUN   500.0 - 01FLINTRN    138.0
END
CONTINGENCY 'AP_P2-3_MP-500-014_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235100 CKT 1   /*01FLINTRUN   500.0 - 01FLINTRN    138.0
END
CONTINGENCY 'AP_P1-2_MP-500-007A_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AP_P2-3_MP-500-012_SRT-A'
 DISCONNECT BRANCH FROM BUS 235107 TO BUS 235235 CKT 1   /*01HARRSN     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235107 TO BUS 235703 CKT 1   /*01HARRSN     500.0 - 01WYLIE R    500.0
END
CONTINGENCY 'AP_P1-2_MP-500-008A_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235107 CKT 1          /*01FLINTRUN   500.0 - 01HARRSN     500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235107 TO BUS 235703 CKT 1 /*01HARRSN     500.0 - 01WYLIE R    500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235107 TO BUS 235703 CKT 1 /*01HARRSN     500.0 - 01WYLIE R    500.0
END
CONTINGENCY 'AEP_P4_#8075_05MARYSV 765_A2_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 242939 CKT 2    /*05MARYSV     765.0 - 05MARYSV     345.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
END
CONTINGENCY 'AEP_P4_#9728_05MALIS 138_L1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243526 TO BUS 243537 CKT 2    /*05HYATT      138.0 - 05MALIS      138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P4_#9730_05MALIS 138_P1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243553 CKT 1    /*05MALIS      138.0 - 05POLARS     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P4_#9729_05MALIS 138_M1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243526 TO BUS 243537 CKT 1    /*05HYATT      138.0 - 05MALIS      138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P4_#7222_05MALIS 765_D_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P2-2_#7222_05MALIS 765_1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P4_#2942_05KAMMER 765_PP_SRT-A'
 OPEN BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242516 TO BUS 242920 CKT 1   /*05MOUNTN     765.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 OPEN BRANCH FROM BUS 242925 TO BUS 243188 CKT 1   /*05KAMMER     765.0 - 05MLG1        26.0
 REMOVE UNIT 1 FROM BUS 243188                     /*05MLG1        26.0
END
CONTINGENCY 'AP_P2-3_MP-500-020_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 1          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 2          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5          /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1          /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1          /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                          /*05BELMON     765.0
 SET POSTCONTRATING 2492 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
 SET PRECONTRATING 1986 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AP_P2-3_MP-500-021_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 3          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5          /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1          /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1          /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                          /*05BELMON     765.0
 SET POSTCONTRATING 2492 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
 SET PRECONTRATING 1986 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AEP_P4_#37_05MOUNTN 765_B1_SRT-A'
 OPEN BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242516 TO BUS 242920 CKT 1   /*05MOUNTN     765.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
END
CONTINGENCY 'AP_P1-3_MP-765-501T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1   /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                   /*05BELMON     765.0
END
CONTINGENCY 'AEP_P4_#8085_05MARYSV 345_H_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 242939 CKT 2   /*05MARYSV     765.0 - 05MARYSV     345.0
 OPEN BRANCH FROM BUS 242939 TO BUS 242945 CKT 1   /*05MARYSV     345.0 - 05SW LIM     345.0
END
CONTINGENCY 'AEP_P2-2_#8072_05MARYSV 765_2_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 242939 CKT 2   /*05MARYSV     765.0 - 05MARYSV     345.0
END
CONTINGENCY 'AEP_P1-2_#706_SRT-A'
 OPEN BRANCH FROM BUS 242922 TO BUS 290622 CKT 1    /*05FLTLCK     765.0 - 05GAVIN_RF   765.0
 OPEN BRANCH FROM BUS 242923 TO BUS 290622 CKT Z1   /*05GAVIN      765.0 - 05GAVIN_RF   765.0
END
CONTINGENCY 'AEP_P7-1_#10944___SRT-A'
 OPEN BRANCH FROM BUS 242528 TO BUS 242940 CKT 1   /*05SPORN      345.0 - 05MUSKNG     345.0
 OPEN BRANCH FROM BUS 242940 TO BUS 242947 CKT 1   /*05MUSKNG     345.0 - 05WATERFORD  345.0
END
CONTINGENCY 'ATSI_P7-1_TE-345-027A_SRT-A'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 239289 CKT 1   /*02DAV-BE     345.0 - 02HAYES      345.0
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 241877 CKT 1   /*02DAV-BE     345.0 - AC2-103 TAP  345.0
END
CONTINGENCY 'AP_P2-2_WP-500-DRT14_SRT-SL'
 OPEN BRANCH FROM BUS 235109 TO BUS 235081 CKT 1                /*AB1-106 POI  500.0 - T-174  1     500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235108 TO BUS 235109 CKT 1 /*01HATFLD     500.0 - AB1-106 POI  500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235116 TO BUS 235109 CKT 1 /*01YUKON      500.0 - AB1-106 POI  500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235108 TO BUS 235109 CKT 1 /*01HATFLD     500.0 - AB1-106 POI  500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235116 TO BUS 235109 CKT 1 /*01YUKON      500.0 - AB1-106 POI  500.0
END
CONTINGENCY 'AEP_P4_#711_05MARYSV 765_A1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
END
CONTINGENCY 'AEP_P1-2_#711_6224_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
END
CONTINGENCY 'AEP_P1-3_#7222_05MALIS 765_1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P1-3_#8072_05MARYSV 765_2_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 242939 CKT 2   /*05MARYSV     765.0 - 05MARYSV     345.0
END
CONTINGENCY 'AEP_P4_#8980_05KAMMER 765_QQ2_SRT-A'
 OPEN BRANCH FROM BUS 242925 TO BUS 290623 CKT Z1   /*05KAMMER     765.0 - 05KAMMER_RG  765.0
 OPEN BRANCH FROM BUS 246526 TO BUS 290623 CKT 1    /*05GUERNSEY   765.0 - 05KAMMER_RG  765.0
END
CONTINGENCY 'AEP_P1-2_#17217_SRT-A'
 OPEN BRANCH FROM BUS 242925 TO BUS 290623 CKT Z1   /*05KAMMER     765.0 - 05KAMMER_RG  765.0
 OPEN BRANCH FROM BUS 246526 TO BUS 290623 CKT 1    /*05GUERNSEY   765.0 - 05KAMMER_RG  765.0
END
CONTINGENCY 'AEP_P4_#17219_05GUERNSEY 765_A_SRT-A'
 OPEN BRANCH FROM BUS 242925 TO BUS 290623 CKT Z1   /*05KAMMER     765.0 - 05KAMMER_RG  765.0
 OPEN BRANCH FROM BUS 246526 TO BUS 246751 CKT 1    /*05GUERNSEY   765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 246526 TO BUS 290623 CKT 1    /*05GUERNSEY   765.0 - 05KAMMER_RG  765.0
END
CONTINGENCY 'AEP_P4_#7445_05MARYSV 765_B_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290621 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RF 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 962760 TO BUS 290621 CKT 1    /*AG1-125 TP   765.0 - 05MARYSVL_RF 765.0
END
CONTINGENCY 'AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'AEP_P1-2_#7422_16_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'AEP_P7-1_#10856___SRT-A'
 OPEN BRANCH FROM BUS 242528 TO BUS 242940 CKT 1   /*05SPORN      345.0 - 05MUSKNG     345.0
 OPEN BRANCH FROM BUS 242528 TO BUS 242947 CKT 1   /*05SPORN      345.0 - 05WATERFORD  345.0
END
235102 to 235235 ckt 1
235235 to 235107 ckt 1
235117 to 235111 ckt 1
242920 to 235102 ckt 5
242923 to 242516 ckt 1
243458 to 246752 ckt 1
242925 to 235117 ckt 1
242926 to 246751 ckt 1
242928 to 242939 ckt 2
242928 to 290620 ckt Z1
290620 to 242926 ckt 1
242516 to 242920 ckt 1

Winter Peak Analysis

The New Service Request AG2-104 was evaluated as a 200.0 MW (126.85 MW Capacity) injection in the AEP area.

AG2-104 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 200.0 MW (200.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
SingleAC179.88 %1180.0B2122.64
14.41
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237805-SB3_SRT-W_SENS
BreakerAC179.88 %1180.0B2122.64
14.41
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237805-SB4_SRT-W_SENS
BreakerAC179.88 %1180.0B2122.64
14.41
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
SingleAC179.88 %1180.0B2122.63
14.41

Details for [AG2-104] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-242508-237805_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:179.88 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2122.64
MW Contribution:
14.41
IPD Plant:AG2-104
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970149AG2-104 GEN
PJM_IPD
14.414

Details for [AG2-104] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237805-SB3_SRT-W_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB3_SRT-W_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:179.88 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2122.64
MW Contribution:
14.41
IPD Plant:AG2-104
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970149AG2-104 GEN
PJM_IPD
14.414

Details for [AG2-104] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237805-SB4_SRT-W_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB4_SRT-W_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:179.88 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2122.64
MW Contribution:
14.41
IPD Plant:AG2-104
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970149AG2-104 GEN
PJM_IPD
14.414

Details for [AG2-104] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-237805-237806_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:179.88 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:2122.63
MW Contribution:
14.41
IPD Plant:AG2-104
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970149AG2-104 GEN
PJM_IPD
14.414
CONTINGENCY 'AP_P1-2_PE-765-242508-237805_SRT-A_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1   /*05AMOS       765.0 - 01WELTON_SPR 765.0
END
CONTINGENCY 'AP_P2-3_PE-765-237805-SB3_SRT-W_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1   /*05AMOS       765.0 - 01WELTON_SPR 765.0
 REDUCE BUS 237805 SHUNT BY 50 PERCENT                   /*01WELTON_SPR 765.0
END
CONTINGENCY 'AP_P2-3_PE-765-237805-SB4_SRT-W_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1   /*05AMOS       765.0 - 01WELTON_SPR 765.0
 REDUCE BUS 237805 SHUNT BY 50 PERCENT                   /*01WELTON_SPR 765.0
END
CONTINGENCY 'AP_P1-2_PE-765-237805-237806_SRT-A_SENS'
 DISCONNECT BRANCH FROM BUS 237805 TO BUS 237806 CKT 1   /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
END
290614 to 242515 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Light Load Analysis

The New Service Request AG2-104 was evaluated as a 200.0 MW injection

AG2-104 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 200.0 MW (200.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P1-3_#7222_05MALIS 765_1_SRT-A
SingleAC101.52 %1409.0B1430.39
7.68
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P4_#9728_05MALIS 138_L1_SRT-A
BreakerAC101.22 %1409.0B1426.24
7.74
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P4_#9730_05MALIS 138_P1_SRT-A
BreakerAC100.94 %1409.0B1422.27
7.72
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
BusAC100.44 %1409.0B1415.21
7.68

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P1-3_#7222_05MALIS 765_1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-3_#7222_05MALIS 765_1_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.52 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1430.39
MW Contribution:
7.68
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
241955AC1-078 GEN
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Harmer
0
270317AD1-130_GEN
Solar/Wind Harmer
0
241813AF1-122_GEN
Solar/Wind Harmer
2.79
270471AD2-092_GEN
Solar/Wind Harmer
0
270349AD2-093_GEN
Solar/Wind Harmer
0
270520AE2-214 GEN
Solar/Wind Harmer
0
270284AF1-227 GEN1
Solar/Wind Harmer
0
270054AF2-122 C O1
Solar/Wind Helper
2.127
270466AD2-091
50/50
5.156
270036AE2-216 BAT
50/50
5.672
270475AD2-096_GEN
50/50
7.52
270051AF1-062 GEN
50/50
Charging
37.356
270578AF1-285 GEN2
Solar/Wind Harmer
1.107
270391AF1-285 GEN3
Solar/Wind Harmer
1.107
270462AD2-086
Solar/Wind Harmer
0
938701AE1-092 GEN
Solar/Wind Harmer
13.409
960851AF2-376 GEN
50/50
2.934
960861AF2-377 GEN
50/50
2.966
962761AG1-125 GEN
Solar/Wind Harmer
12.052
962771AG1-126 GEN
Solar/Wind Harmer
12.052
963581AG1-207 GEN
50/50
4.627
970065AG2-057 GEN
Solar/Wind Harmer
0.436
970149AG2-104 GEN
Solar/Wind Harmer
7.682
970153AG2-106 GEN
Solar/Wind Harmer
8.217
970155AG2-107 GEN
Solar/Wind Harmer
8.217
970179AG2-119 GEN
Solar/Wind Harmer
4.106
970583AG2-370 GEN
50/50
2.869
971201AH1-060 GEN
Solar/Wind Harmer
0.872
270223U2-072_GEN1
Solar/Wind Harmer
2.379
270224U2-072_GEN2
Solar/Wind Harmer
2.379
270227U2-072_GEN3
Solar/Wind Harmer
2.379
270228U2-072_GEN4
Solar/Wind Harmer
2.379
270231U2-072_GEN5
Solar/Wind Harmer
2.379
942051AE2-217 GEN
Solar/Wind Harmer
8.404
965431AG1-411 GEN
50/50
6.397
CBM West 1LTFEXP_CBM-W1->PJM
CBM
50.386
CBM West 2LTFEXP_CBM-W2->PJM
CBM
34.843
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.803
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.418
NYPJM->LTFIMP_NY
CLTF
1.562
LGEELTFEXP_LGEE->PJM
CLTF
2.018
WECLTFEXP_WEC->PJM
CLTF
1.421
CPLELTFEXP_CPLE->PJM
CLTF
0.007
TVALTFEXP_TVA->PJM
CLTF
1.896
MECLTFEXP_MEC->PJM
CLTF
5.573
LAGNLTFEXP_LAGN->PJM
CLTF
4.254
SIGELTFEXP_SIGE->PJM
CLTF
0.159
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
12.239
AG2-052LTFEXP_AG2-052->PJM
LTF
0.088
AH1-155LTFEXP_AH1-155->PJM
LTF
0.132

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P4_#9728_05MALIS 138_L1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9728_05MALIS 138_L1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.22 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1426.24
MW Contribution:
7.74
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
241955AC1-078 GEN
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Harmer
0
270317AD1-130_GEN
Solar/Wind Harmer
0
241813AF1-122_GEN
Solar/Wind Harmer
2.809
270471AD2-092_GEN
Solar/Wind Harmer
0
270349AD2-093_GEN
Solar/Wind Harmer
0
270520AE2-214 GEN
Solar/Wind Harmer
0
270284AF1-227 GEN1
Solar/Wind Harmer
0
270054AF2-122 C O1
Solar/Wind Helper
2.169
270466AD2-091
50/50
5.194
270036AE2-216 BAT
50/50
5.713
270475AD2-096_GEN
50/50
7.576
270051AF1-062 GEN
50/50
Charging
37.736
270578AF1-285 GEN2
Solar/Wind Harmer
1.116
270391AF1-285 GEN3
Solar/Wind Harmer
1.116
270462AD2-086
Solar/Wind Harmer
0
938701AE1-092 GEN
Solar/Wind Harmer
13.517
962761AG1-125 GEN
Solar/Wind Harmer
9.839
962771AG1-126 GEN
Solar/Wind Harmer
9.839
970065AG2-057 GEN
Solar/Wind Harmer
0.439
970149AG2-104 GEN
Solar/Wind Harmer
7.737
970153AG2-106 GEN
Solar/Wind Harmer
6.708
970155AG2-107 GEN
Solar/Wind Harmer
6.708
970179AG2-119 GEN
Solar/Wind Harmer
4.135
971201AH1-060 GEN
Solar/Wind Harmer
0.878
971995AH1-542 GEN
Solar/Wind Harmer
5.582
971995AH1-542 GEN
Solar/Wind Harmer
7.612
270223U2-072_GEN1
Solar/Wind Harmer
2.396
270224U2-072_GEN2
Solar/Wind Harmer
2.396
270227U2-072_GEN3
Solar/Wind Harmer
2.396
270228U2-072_GEN4
Solar/Wind Harmer
2.396
270231U2-072_GEN5
Solar/Wind Harmer
2.396
942051AE2-217 GEN
Solar/Wind Harmer
8.477
CBM West 1LTFEXP_CBM-W1->PJM
CBM
50.719
CBM West 2LTFEXP_CBM-W2->PJM
CBM
35.061
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.85
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.423
NYPJM->LTFIMP_NY
CLTF
1.572
LGEELTFEXP_LGEE->PJM
CLTF
2.031
WECLTFEXP_WEC->PJM
CLTF
1.43
CPLELTFEXP_CPLE->PJM
CLTF
0.006
TVALTFEXP_TVA->PJM
CLTF
1.907
MECLTFEXP_MEC->PJM
CLTF
5.61
LAGNLTFEXP_LAGN->PJM
CLTF
4.28
SIGELTFEXP_SIGE->PJM
CLTF
0.16
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
12.34
AG2-052LTFEXP_AG2-052->PJM
LTF
0.089
AH1-155LTFEXP_AH1-155->PJM
LTF
0.133

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P4_#9730_05MALIS 138_P1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9730_05MALIS 138_P1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.94 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1422.27
MW Contribution:
7.72
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
241955AC1-078 GEN
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Harmer
0
270317AD1-130_GEN
Solar/Wind Harmer
0
241813AF1-122_GEN
Solar/Wind Harmer
2.803
270471AD2-092_GEN
Solar/Wind Harmer
0
270349AD2-093_GEN
Solar/Wind Harmer
0
270520AE2-214 GEN
Solar/Wind Harmer
0
270284AF1-227 GEN1
Solar/Wind Harmer
0
270054AF2-122 C O1
Solar/Wind Helper
2.156
270466AD2-091
50/50
5.182
270036AE2-216 BAT
50/50
5.7
270475AD2-096_GEN
50/50
7.558
270051AF1-062 GEN
50/50
Charging
37.614
270578AF1-285 GEN2
Solar/Wind Harmer
1.113
270391AF1-285 GEN3
Solar/Wind Harmer
1.113
270462AD2-086
Solar/Wind Harmer
0
938701AE1-092 GEN
Solar/Wind Harmer
13.482
962761AG1-125 GEN
Solar/Wind Harmer
9.816
962771AG1-126 GEN
Solar/Wind Harmer
9.816
970065AG2-057 GEN
Solar/Wind Harmer
0.438
970149AG2-104 GEN
Solar/Wind Harmer
7.719
970153AG2-106 GEN
Solar/Wind Harmer
6.693
970155AG2-107 GEN
Solar/Wind Harmer
6.693
970179AG2-119 GEN
Solar/Wind Harmer
4.126
971201AH1-060 GEN
Solar/Wind Harmer
0.876
971995AH1-542 GEN
Solar/Wind Harmer
5.569
971995AH1-542 GEN
Solar/Wind Harmer
7.594
270223U2-072_GEN1
Solar/Wind Harmer
2.391
270224U2-072_GEN2
Solar/Wind Harmer
2.391
270227U2-072_GEN3
Solar/Wind Harmer
2.391
270228U2-072_GEN4
Solar/Wind Harmer
2.391
270231U2-072_GEN5
Solar/Wind Harmer
2.391
942051AE2-217 GEN
Solar/Wind Harmer
8.454
CBM West 1LTFEXP_CBM-W1->PJM
CBM
50.613
CBM West 2LTFEXP_CBM-W2->PJM
CBM
34.991
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.835
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.421
NYPJM->LTFIMP_NY
CLTF
1.568
LGEELTFEXP_LGEE->PJM
CLTF
2.027
WECLTFEXP_WEC->PJM
CLTF
1.427
CPLELTFEXP_CPLE->PJM
CLTF
0.007
TVALTFEXP_TVA->PJM
CLTF
1.904
MECLTFEXP_MEC->PJM
CLTF
5.598
LAGNLTFEXP_LAGN->PJM
CLTF
4.272
SIGELTFEXP_SIGE->PJM
CLTF
0.159
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
12.308
AG2-052LTFEXP_AG2-052->PJM
LTF
0.089
AH1-155LTFEXP_AH1-155->PJM
LTF
0.133

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P2-2_#7222_05MALIS 765_1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:100.44 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1415.21
MW Contribution:
7.68
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
241955AC1-078 GEN
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Harmer
0
270317AD1-130_GEN
Solar/Wind Harmer
0
241813AF1-122_GEN
Solar/Wind Harmer
2.79
270471AD2-092_GEN
Solar/Wind Harmer
0
270349AD2-093_GEN
Solar/Wind Harmer
0
270520AE2-214 GEN
Solar/Wind Harmer
0
270284AF1-227 GEN1
Solar/Wind Harmer
0
270054AF2-122 C O1
Solar/Wind Helper
2.127
270466AD2-091
50/50
5.156
270036AE2-216 BAT
50/50
5.672
270475AD2-096_GEN
50/50
7.52
270051AF1-062 GEN
50/50
Charging
37.356
270578AF1-285 GEN2
Solar/Wind Harmer
1.107
270391AF1-285 GEN3
Solar/Wind Harmer
1.107
270462AD2-086
Solar/Wind Harmer
0
938701AE1-092 GEN
Solar/Wind Harmer
13.409
962761AG1-125 GEN
Solar/Wind Harmer
9.768
962771AG1-126 GEN
Solar/Wind Harmer
9.768
970065AG2-057 GEN
Solar/Wind Harmer
0.436
970149AG2-104 GEN
Solar/Wind Harmer
7.682
970153AG2-106 GEN
Solar/Wind Harmer
6.66
970155AG2-107 GEN
Solar/Wind Harmer
6.66
970179AG2-119 GEN
Solar/Wind Harmer
4.106
971201AH1-060 GEN
Solar/Wind Harmer
0.872
971995AH1-542 GEN
Solar/Wind Harmer
5.541
971995AH1-542 GEN
Solar/Wind Harmer
7.556
270223U2-072_GEN1
Solar/Wind Harmer
2.379
270224U2-072_GEN2
Solar/Wind Harmer
2.379
270227U2-072_GEN3
Solar/Wind Harmer
2.379
270228U2-072_GEN4
Solar/Wind Harmer
2.379
270231U2-072_GEN5
Solar/Wind Harmer
2.379
942051AE2-217 GEN
Solar/Wind Harmer
8.404
CBM West 1LTFEXP_CBM-W1->PJM
CBM
50.386
CBM West 2LTFEXP_CBM-W2->PJM
CBM
34.843
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.803
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.418
NYPJM->LTFIMP_NY
CLTF
1.562
LGEELTFEXP_LGEE->PJM
CLTF
2.018
WECLTFEXP_WEC->PJM
CLTF
1.421
CPLELTFEXP_CPLE->PJM
CLTF
0.007
TVALTFEXP_TVA->PJM
CLTF
1.896
MECLTFEXP_MEC->PJM
CLTF
5.573
LAGNLTFEXP_LAGN->PJM
CLTF
4.254
SIGELTFEXP_SIGE->PJM
CLTF
0.159
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
12.239
AG2-052LTFEXP_AG2-052->PJM
LTF
0.088
AH1-155LTFEXP_AH1-155->PJM
LTF
0.132
CONTINGENCY 'AEP_P1-3_#7222_05MALIS 765_1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P4_#9728_05MALIS 138_L1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243526 TO BUS 243537 CKT 2    /*05HYATT      138.0 - 05MALIS      138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P4_#9730_05MALIS 138_P1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243553 CKT 1    /*05MALIS      138.0 - 05POLARS     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P2-2_#7222_05MALIS 765_1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
243458 to 246752 ckt 1

Short Circuit Analysis

Analysis Complete - No Issues

Based on PJM’s TC2 Phase II Short Circuit Analysis, this project did not contribute >1% fault duty to any previously identified overdutied breakers, nor did it cause any new overdutied breakers.

Please note that in TC2 Phase III, PJM will perform additional analysis including the evaluation of impacts from topology upgrades which may have potential effects on breaker duties not seen in the Phase II analysis.

Stability Analysis

Analysis Complete - No Issues

Executive Summary

 

New Service Requests AG2-029, AG2-104 and AG2-370 in PJM Transition Cycle 2, Cluster 39 are listed in Table 1 below. This report will cover the dynamic analysis of Cluster 39 projects.

 

This analysis is effectively a screening study to determine whether the addition of the Cluster 39 projects will meet the dynamics requirements of the NERC, AEP and PJM reliability standards.

 

The load flow scenario for the analysis was based on the RTEP 2028 Summer Peak, modified to include applicable projects. Cluster 39 projects have been dispatched online at maximum power output, with 1.0 voltage at the terminal bus.

 

Transition Cycle 2 Cluster 39 will be tested for compliance with NERC, PJM and other applicable criteria. The contingencies will be studied with a 20 second simulation time. Contingencies to be studied include:

       a.       Steady-state operation (Category P0);

       b.       Three-phase faults with normal clearing time (and with unsuccessful high-speed reclosing) (Category P1);

       c.       Single-phase bus faults with normal clearing time (Category P2);

       d.       Single-phase faults with stuck breaker (Category P4);

       e.       Single-phase faults placed at 80% of the line with delayed (Zone 2) clearing at line end remote from the fault due to primary communications/relay failure (Category P5);

       f.       Three-phase faults with loss of multiple-circuit tower line; (and with unsuccessful high-speed reclosing) (Category P7).

 

High Speed Reclosing (HSR) facilities were found in the vicinity of TC2 Cluster 39 projects.

 

Prior outage scenarios will not be considered for this study.

 

For all simulations, the queue project under study along with the rest of the PJM system were required to maintain synchronism and with all states returning to an acceptable new condition following the disturbance.

 

For all the fault contingencies tested on the 2028 Summer Peak Load case:

       a)       Cluster 39 projects were able to ride through the faults (except for faults where protective action trips a generator(s)),

       b)       The system with Cluster 39 projects included is transiently stable and post-contingency oscillations were positively damped with a damping margin of at least 3% for interarea modes and 4% for local modes.

       c)       Following fault clearing, all bus voltages recovered to a minimum of 0.7 per unit after 2.5 seconds (except where protective action isolates that bus).

       d)       No transmission element tripped, other than those either directly connected or designed to trip because of that fault.

 

AG2-029 exhibited slow reactive power recovery within the 20-second simulation window for several contingencies. While this issue did not cause instability in the system, the plant controller model was tuned to achieve a faster reactive power output and mitigate the observed slow recovery. Specifically, the plant controller model REPCA1 was updated by updating Kp, Ki, and Kc to 0.2, 2, and 0.15, respectively, and these modifications are pending the developer’s confirmation.

 

AG2-104 exhibited slow reactive power recovery within the 20-second simulation window for several contingencies. While this issue did not cause instability in the system, the plant controller model was tuned to achieve a faster reactive power output and mitigate the observed slow recovery. Specifically, plant controller model PLNTBU1 was updated by updating Kc to 0.15, and this modification has been approved by the developer.

 

It was observed that various units tripped during P1.38 contingency due to the fault at Logtown 138. After further investigation, the trippings were attributed to T-131 wind units as listed below connecting to Logtown which was confirmed by creating a bench case with all Cluster 39 projects offline and observing the similar tripping instances.

       a)       TR3_G114 with ID: ‘W1’ (PSS/E Bus# 270191),

       b)       TR4_S_V150 with ID: ‘W1’ (PSS/E Bus# 270246),

       c)       TR4_N_V150 with ID: ‘W3’ (PSS/E Bus# 270247),

       d)       TR4_N_V136 with ID: ‘W2’ (PSS/E Bus# 247521).

 

After G-netting the above units, the simulation results were found to be stable. Therefore, it was concluded Cluster 39 projects do not attribute to the generator tripping instances.

 

In a number of contingencies, AG1-368 showed slow reactive power dynamics without imposing any instability issues.

 

Flatlick Generators as well as AE1-021 exhibited slow damping dynamics in P4.29-P4.34, P4.38, P4.42, and P4.46. The slow dynamics did not cause any instability issues. Additionally, the simulations were run for 40 seconds, and the system was found to be stable.

 

The IPCMD and IQCMD states in the REGCA1 model of AG2-029 showed erratic behavior for some contingencies in which AG2-029 has been disconnected as part of the contingency event. Since the machines are disconnected and no active or reactive power is injected into the system, this behavior is likely fictitious and a limitation of the software. This does not cause instability in the system.

 

The IPCMD and IQCMD states in the REGCA1 model of AG2-104 showed erratic behavior for some contingencies in which AG2-104 has been disconnected as part of the contingency event. Since the machines are disconnected and no active or reactive power is injected into the system, this behavior is likely fictitious and a limitation of the software. This does not cause instability in the system.

 

The IPCMD and IQCMD states in the REGCA1 model of AG2-370 showed erratic behavior for some contingencies in which AG2-370 has been disconnected as part of the contingency event. Since the machines are disconnected and no active or reactive power is injected into the system, this behavior is likely fictitious and a limitation of the software. This does not cause instability in the system.

 

No mitigations were found to be required.

 

Table 1: Transition Cycle 2 Cluster 39 Projects

 

 

 

 

Project

Fuel Type

Transmission Owner

MFO (MW)

Point of Interconnection

AG2-029 

Solar 

AEP 

250 

Dunton Lake – Forest G Hiple 345 kV 

AG2-104 

Solar 

AEP 

200 

Marysville – Flatlick 765 kV 

AG2-370 

Battery 

AEP 

50 

Tillman substation 138 kV 

 

 

Reactive Power Analysis

Analysis Complete - No Issues

The reactive power capability of AG2-104 meets the 0.95 leading and lagging PF requirement at the high side of the main transformer.

Steady-State Voltage Analysis

Not Required

A steady state voltage analysis is evaluated on a project-by-project basis and depends on specific project parameters. For this project, a steady state voltage analysis is not required per PJM's Manual 14H, Section 4.5.2.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-018Powerton-Goodings GroveIn Service
AB1-006Meadow Lake 345kVIn Service
AB2-067Kammer-Vassell 765kVIn Service
AB2-070Mt. Pulaski-BrokawIn Service
AB2-170East Lima-Marysville 345kVIn Service
AC1-001Delano 138kVIn Service
AC1-033Kewanee 138 kVIn Service
AC1-044Kammer-Vassell 765kVIn Service
AC1-053Lanesville-BrokawIn Service
AC1-068Atlanta 69kV IIn Service
AC1-069Atlanta 69kV IIIn Service
AC1-078Beatty-London 138kVIn Service
AC1-085Stuart-Clinton 345kVIn Service
AC1-111Aurora 138kVIn Service
AC1-141Cook-East Elkhart 345kVIn Service
AC1-165Atlanta 69kV IIIIn Service
AC1-166Atlanta 69kV IVIn Service
AC1-167Platter Creek 69kVUnder Construction
AC1-168Kewanee-StreatorSuspended
AC1-174Losantville 345kVIn Service
AC1-175Losantville 345kVIn Service
AC1-214Crescent RidgeIn Service
AC2-029Circleville 138kVSuspended
AC2-044Maddox Creek 345kVSuspended
AC2-059Biers Run-Circleville 138kVIn Service
AC2-060Buckskin 69kVIn Service
AC2-061Hillsboro-Clinton 138kVIn Service
AC2-067Camden-Crystal I 69kVEngineering & Procurement
AC2-068Camden-Crystal II 69kVEngineering & Procurement
AC2-088S. Bethel-Brown 69kVIn Service
AC2-090Losantville 345kVIn Service
AC2-154Davis Creek 138kVEngineering & Procurement
AC2-157Sullivan 345 kVPartially in Service - Under Construction
AC2-168Clinton 23kVIn Service
AC2-176Jay 138 kVIn Service
AC2-195Galion-Roberts South 138 kVPartially in Service - Under Construction
AD1-013Twombly Road 138kVEngineering & Procurement
AD1-100Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVUnder Construction
AD1-101Continental 69 kVIn Service
AD1-106North Waldo-Wild Creek 138 kVWithdrawn
AD1-119Payne 69 kVIn Service
AD1-128Modoc-Delaware 138 kVIn Service
AD1-130Hardin Switch 345 kVIn Service
AD1-136South Bethel-Brown 69 kVIn Service
AD1-140Greene-Clark 138 kVEngineering & Procurement
AD2-016Biers Run-Circleville 138 kVIn Service
AD2-020Valley 138 kVEngineering & Procurement
AD2-031Martinsville-Wilmington 69 kVIn Service
AD2-038Powerton-Nevada 345 kVUnder Construction
AD2-047Davis Creek 138 kVSuspended
AD2-060Davis Creek 138kVEngineering & Procurement
AD2-066Mazon-Crescent Ridge 138 kVUnder Construction
AD2-067Centerburg 138kVEngineering & Procurement
AD2-071Strawton-Deer Creek 138 kVSuspended
AD2-079Capitol Ave 34.5kVIn Service
AD2-086Hardin Switch 345 kVIn Service
AD2-091Hardin Tap 345kVSuspended
AD2-092Marysville 345kVWithdrawn
AD2-093Marysville 345kVPartially in Service - Under Construction
AD2-096Marysville 345kVSuspended
AD2-100Kincaid-Pana 345 kVSuspended
AD2-131Kincaid-Pana 345kVSuspended
AD2-133Eagle Valley 115kVIn Service
AD2-134Shady OaksPartially in Service - Under Construction
AD2-163Broadview-Tangy 138 kVIn Service
AD2-180Elk Garden-Parr Run 138kVIn Service
AE1-040Greenfield 69 kVIn Service
AE1-079Maysville-Sharon 69 kVUnder Construction
AE1-090Hardin Switch 345 kVIn Service
AE1-091West Newton-Lynn 138 kVSuspended
AE1-092Blue Jacket-Kirby 138 kVEngineering & Procurement
AE1-102Maddox Creek 345 kVSuspended
AE1-113Mole Creek 345 kVUnder Construction
AE1-114Maryland-Lancaster 138 kVEngineering & Procurement
AE1-163Powerton-Nevada 345 kVUnder Construction
AE1-166Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE1-170Kenzie Creek-Colby 138 kVSuspended
AE1-172Loretto-Wilton CenterWithdrawn
AE1-183Maysville-McDowell 69 kVUnder Construction
AE1-205McLean 345 kVEngineering & Procurement
AE1-207Mississinewa-Gaston 138 kVSuspended
AE1-208Delaware-Van Buren 138 kVSuspended
AE1-209Desoto 345 kVSuspended
AE1-210Desoto 345 kVSuspended
AE1-237Andover (Maysville) 69kV IUnder Construction
AE1-245Haviland 138 kVPartially in Service - Under Construction
AE2-045Olive-Reynolds 345 kVEngineering & Procurement
AE2-072East Leipsic-Richland 138 kVIn Service
AE2-074Potter 46 kVUnder Construction
AE2-089Pennville-Adams 138 kVSuspended
AE2-113Farmers Valley-Ridgeway 115 kVUnder Construction
AE2-114Midland 23 kV IIn Service
AE2-115Midland 23 kV IIIn Service
AE2-125Stahlstown-Ligonier 25 kVIn Service
AE2-126Dubois-Curwensville 34.5 kVIn Service
AE2-129Philipsburg-Clarence 34.5 kVIn Service
AE2-131Philipsburg-Karthaus 34.5Under Construction
AE2-139East Towanda-Grover 230 kVEngineering & Procurement
AE2-148Beatty-Greene 345 kVIn Service
AE2-152Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE2-169Delaware-Van Buren 138 kVSuspended
AE2-172Mississinewa-Gaston 138 kVSuspended
AE2-206East Sidney-Quincy 138 kVIn Service
AE2-214Cole 345 kVUnder Construction
AE2-216Hardin Switch 345 kVSuspended
AE2-217East Springfield-London 138 kVEngineering & Procurement
AE2-219Bluff Point-Randolph 138 kVSuspended
AE2-220Losantville 345 kVEngineering & Procurement
AE2-221Clinton-Stuart 345 kVUnder Construction
AE2-223McLean 345 kVEngineering & Procurement
AE2-224Bear Rock-Johnstown 230 kVIn Service
AE2-234Liberty Center-Buckeye Tap 69 kVEngineering & Procurement
AE2-236Columbia-Northeast 138 kVSuspended
AE2-255Molecreek 345 kVUnder Construction
AE2-261Kincaid-Pana 345 kVEngineering & Procurement
AE2-285Maysville 69 kVUnder Construction
AE2-297Madison-Tanners Creek 138 kVIn Service
AE2-298Cavett Switch - West Van Wert 69 kVWithdrawn
AE2-305Givens-Mechanicsburg 138 kVWithdrawn
AE2-306Gunn Road 345 kVUnder Construction
AE2-309Carlos Junction-Lonaconing 34.5 kVIn Service
AE2-315Yankee Tap 69 kVIn Service
AE2-318Ford-Cedarville 138 kVSuspended
AE2-322Platter Creek 69kVUnder Construction
AE2-323Twin Branch-Guardian 138 kVPartially in Service - Under Construction
AE2-325Valley 138 kVWithdrawn
AE2-341Sandwich-Plano 138 kVEngineering & Procurement
AE2-342Woodstock 69 kVSuspended
AE2-343Andover (Maysville) 69 kV IIUnder Construction
AF1-006Fairview East 34.5 kVIn Service
AF1-021Bethelboro-Connellsville #1 25 kVIn Service
AF1-022Lake Lynn-Uniontown 25 kVIn Service
AF1-030Sandwich-Plano 138 kVEngineering & Procurement
AF1-039Listonburg-Highpoint 24.9 kVIn Service
AF1-045Cedarville-Ford 138 kVSuspended
AF1-053Givens-Mechanicsburg 138 kVWithdrawn
AF1-054Givens-Mechanicsburg 138 kVWithdrawn
AF1-062Jug Street 138 kVEngineering & Procurement
AF1-078East Sidney-Quincy 138 kVIn Service
AF1-084Hartford-Almena 69 kVUnder Construction
AF1-086Madera-Westover South 115 kVPartially in Service - Under Construction
AF1-090Kincaid-PanaEngineering & Procurement
AF1-091Varner - Sowers 138 kVEngineering & Procurement
AF1-092Huntington Jct. 138 kVWithdrawn
AF1-093Henderson-Stoneboro 69 kVUnder Construction
AF1-094Union City-Cambridge Springs 34.5 kVEngineering & Procurement
AF1-098Four Mile Jct-Corry East 115 kVSuspended
AF1-118Sorenson-Desoto 345 kVWithdrawn
AF1-119Keystone-Desoto 345 kVEngineering & Procurement
AF1-122Cardington-Liberty 69 kVSuspended
AF1-134Philipsburg-Madera 34.5 kVUnder Construction
AF1-140Claysburg 23 kVEngineering & Procurement
AF1-158Edison-Gravel Pit 138 kVIn Service
AF1-161Valley 138 kVEngineering & Procurement
AF1-176Corey 138 kVEngineering & Procurement
AF1-202Keystone-Desoto 345 kVUnder Construction
AF1-204Eugene 345 kVEngineering & Procurement
AF1-207Reynolds-Olive #1 345 kVEngineering & Procurement
AF1-215Olive-Reynolds 345 kVIn Service
AF1-223Keystone-Desoto 345 kVUnder Construction
AF1-227Marysville – Gunn Road 345 kVIn Service
AF1-228Beatty-Greene 345 kVUnder Construction
AF1-249Nickel 12.47 kVIn Service
AF1-268Desoto-Jay 138 kVEngineering & Procurement
AF1-272Lucerne 115 kVEngineering & Procurement
AF1-275Cole 345 kVUnder Construction
AF1-282Stuart-Clinton 345 kVEngineering & Procurement
AF1-283Stuart-Clinton 345 kVEngineering & Procurement
AF1-285Gunn Road 345 kVUnder Construction
AF1-296Garden Plain 138 kVEngineering & Procurement
AF1-302Brookville-Squab Hollow 138 kVUnder Construction
AF1-322Meadow Lake 345 kVUnder Construction
AF1-331Twombley RoadEngineering & Procurement
AF2-014Maddox Creek 345 kVUnder Construction
AF2-032Kincaid 345 kVWithdrawn
AF2-039Shawville-Clearfield 34.5 kVUnder Construction
AF2-041Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-068Jay 138 kVEngineering & Procurement
AF2-078Reynolds-Olive #1 345 kVEngineering & Procurement
AF2-083Kenzie Creek-Stone Lake 69 kVUnder Construction
AF2-088Shawville-Clearfield 34.5 kV IIUnder Construction
AF2-095Davis Creek 138 kVEngineering & Procurement
AF2-103Haviland 138 kVIn Service
AF2-111North Clark-Spurlock 345 kVEngineering & Procurement
AF2-122Kirk 138 kVPartially in Service - Under Construction
AF2-130Cobalt Corners 34.5 kVIn Service
AF2-132Reynolds-Olive #1 345 kVUnder Construction
AF2-133Reynolds-Olive #2 345 kVUnder Construction
AF2-134Olive-Reynolds #2 345 kVIn Service
AF2-142Nevada 345 kVEngineering & Procurement
AF2-143Powerton-Nevada 345 kVEngineering & Procurement
AF2-149Sharp Road 69 kVEngineering & Procurement
AF2-162Keystone-Desoto 345 kVEngineering & Procurement
AF2-177Sorenson-DeSoto #2 345 kVEngineering & Procurement
AF2-199Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-200Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-205Olive-Reynolds #2 345 kVEngineering & Procurement
AF2-224Allen 345 kVEngineering & Procurement
AF2-225McLean 345 kVEngineering & Procurement
AF2-252Blue Mound 345 kVEngineering & Procurement
AF2-298Crown-New Lebanon 69 kVEngineering & Procurement
AF2-350Kensington 138 kVEngineering & Procurement
AF2-352Blue Mound 345 kVEngineering & Procurement
AF2-356Albright-Mt. Zion 138 kVPartially in Service - Under Construction
AF2-359Olive-University Park 345 kVEngineering & Procurement
AF2-366Crego Rd 138 kVEngineering & Procurement
AF2-371Harrison-Good Hope 138 kVEngineering & Procurement
AF2-388Keystone-Desoto 345 kVEngineering & Procurement
AF2-396Stinger 138 kVEngineering & Procurement
AG1-017Jay 138 kVIn Service
AG1-024Centerburg 138 kVEngineering & Procurement
AG1-034Centerburg 138 kVEngineering & Procurement
AG1-040Morgan Street-Mount Hope 34.5 kVEngineering & Procurement
AG1-047Jay 138 kVEngineering & Procurement
AG1-054Potter-Harlan 69 kVEngineering & Procurement
AG1-100Venango-Saegertown 34.5 kVEngineering & Procurement
AG1-107Hillsboro-Middleboro 138 kVUnder Construction
AG1-109Valley 138 kVEngineering & Procurement
AG1-118Sugar Grove-Waterman 138kVEngineering & Procurement
AG1-125Marysville-Flatlick 765 kVEngineering & Procurement
AG1-126Marysville-Flatlick 765 kVEngineering & Procurement
AG1-127Crego Rd 138 kVEngineering & Procurement
AG1-198Union City 34.5 kVIn Service
AG1-226Dequine-Eugene 345 kVEngineering & Procurement
AG1-232Magley 138 kVEngineering & Procurement
AG1-237Dequine-Eugene 345 kVEngineering & Procurement
AG1-281Claysburg-HCR Tap 46 kVEngineering & Procurement
AG1-302Olive-Reynolds #1 345 kVUnder Construction
AG1-324Jay-Desoto 138 kVEngineering & Procurement
AG1-349Olive-Reynolds #2 345 kVEngineering & Procurement
AG1-351Harrison-Good Hope 138 kVEngineering & Procurement
AG1-363Black Oak-Hatfield 500 kVEngineering & Procurement
AG1-365Allen 345 kVEngineering & Procurement
AG1-366Allen 345 kVEngineering & Procurement
AG1-368Tillman 138 kVEngineering & Procurement
AG1-369Logtown 138 kVEngineering & Procurement
AG1-374Blue Mound 345 kVEngineering & Procurement
AG1-386Smith-Francis Junction 25 kVIn Service
AG1-410Maddox Creek-RP Mone 345 kVEngineering & Procurement
AG1-411Maddox Creek-RP Mone 345 kVEngineering & Procurement
AG1-414Mississinewa 138 kVEngineering & Procurement
AG1-433Keystone-DeSoto 345 kVEngineering & Procurement
AG1-436Olive-University Park 345 kVEngineering & Procurement
AG1-447Olive-University Park 345 kVEngineering & Procurement
AG1-460Kincaid-Pana 345 kVEngineering & Procurement
AG1-462Cordova 345 kVEngineering & Procurement
AG1-478Wilmington 34.5 kVEngineering & Procurement
AG1-554South Kenton 138 kVEngineering & Procurement
AG1-555Dequine 345 kVEngineering & Procurement
AG2-029Forest G. Hipple-Dunton Lake 345 kVActive
AG2-057Cardington-Liberty 69 kV IIActive
AG2-061Dana 345 kVActive
AG2-072Rockport 765 kVActive
AG2-106Marysville-Flatlick 765 kVActive
AG2-107Marysville-Flatlick 765 kVActive
AG2-114Dresden-Pontiac Midpoint 345 kVActive
AG2-119Galion-Roberts South 138 kV IIActive
AG2-125Camden-Crystal 69 kVActive
AG2-126Eugene 345 kVActive
AG2-163Dequine-Eugene 345 kVActive
AG2-191Mississinewa 138 kVActive
AG2-192Mississinewa 138 kVActive
AG2-216East Sidney-Quincy 138 kVActive
AG2-230Dumont 345 kVActive
AG2-245Olive - Reynolds #1 345 kVActive
AG2-332East Elkhart - Elcona Tap 138 kVActive
AG2-363Powerton 345 kVActive
AG2-364Powerton 345 kVActive
AG2-401Losantville 345 kVActive
AG2-405Continental 69 kVActive
AG2-406Payne 69 kVActive
AG2-453Lasalle - Plano 345 kVActive
AG2-487Madison - Tanners Creek 138 kVActive
AG2-491Meadow Lake 345 kVActive
AG2-516Pecatonica 138kVActive
AG2-519Royerton - Desoto 138 kVActive
AG2-524LaSalle Station - Mazon 138 kVActive
AG2-550Bluff Point - Randolph 138 kVActive
AG2-551Bluff Point - Randolph 138 kVActive
AG2-585Kensignton 138kVActive
AG2-637Randolph - Hodgin 138 kVActive
AG2-660Nelson-Electric Junction 345 kVActive
AG2-675Cordova 345 kVActive
AH1-044Nelson - Electric Junction 345 kVActive
AH1-059Sharp Road 69 kVActive
AH1-060Cardington-Liberty 69 kV IIIActive
AH1-150Nelson-Electric Junction 345 kVActive
AH1-151Nelson-Electric Junction 345 kVActive
AH1-153Dumont 345 kVActive
AH1-196Silver Lake - Cherry Valley 345 kVActive
AH1-272Argenta - Twin Branch 345 kVActive
AH1-292Sullivan 345 kVActive
AH1-302Olive - Reynolds 345 kVActive
AH1-304Delaware-Van Buren 138 kVActive
AH1-305Olive - Reynolds 345 kVActive
AH1-306Mississinewa-Gaston 138 kVActive
AH1-327Hardin Switch 345 kVActive
AH1-328Blue Jacket - Kirby 138 kVActive
AH1-338New Sub S2354 138kVActive
AH1-341ESS-H445 3B 138kvActive
AH1-392Gravel Pit-Kankakee 138 kVActive
AH1-482Olive - Reynolds #2 345 kVActive
AH1-541Chestnut 345 kVActive
AH1-542Crissinger-Delaware Business Park 138kVActive
AH1-543Mulberry - Tazewell 345 kVActive
AH1-567University Park 138 kVActive
AH1-661Cannelville 12.47 kVActive
AH1-698Braidwood 345 kVActive
AH1-702Byron 345 kVActive
AH1-714Lasalle 345 kVActive
AH1-718Nelson 345 kVActive
U2-030Four Mile Ridge Wind 138kVIn Service
U2-072East Lima-Marysville 345kVIn Service
U2-073Frostburg 138kV IIIn Service
V1-011Haviland 138kVIn Service
V3-007Desoto-Tanners Creek #1 345kVIn Service
V4-073Yankee 12.5kVIn Service
W2-048Brokaw-LanesvilleIn Service
X2-022Brokaw-LanesvilleIn Service
X2-052Dumont-Olive 345kVIn Service
X3-005Wildwood 12kVIn Service
Y1-033Penn Mar-Rock Wood 115kVIn Service
Y3-023Country Side 12kVIn Service
Y3-024Bluff Point 12kVIn Service
Z2-087Pontiac MidPoint-Brokaw 345kVIn Service
Z2-115Deer Creek 12.47kVIn Service
Z2-116Twin Branch 12.47kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, per Tariff Part VII.G.336 & Manual 14H, Section 13, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In accordance with PJM Tariff Part VII, Subpart D, section 310.A and as outlined in PJM Manual 14H, Sections 4.5 and 13, in Phase II of the Cycle, PJM provides the Affected System Operator any updates on the PJM projects that require an Affected Systems Study based on their response at DP1. New Service Requests that require an Affected Systems Study are required to enter into an Affected Systems Study Agreement with the Affected System Operator, as applicable, prior to the close of DP2 or they will be withdrawn from the Cycle.

If the Project Developer already entered into the necessary agreement and the results are available, PJM will supply them in the Phase II SIS report. See below for the status of any required Affected Systems Study. A status of “Pending” means that the study is not yet completed by the Affected System Operator. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Phase II System Impact Study analysis results, this project is contingent on and may have cost responsibility for the following System Reinforcements:

AG2-104 System Reinforcements:
TORTEP IDTitleCategoryAllocated Cost ($USD)Facilities Study
AEPn9767.005KAMMER_RG 765.0 kV to 05KAMMER 765.0 kV ckt Z1 - Replace WavetrapsCost Allocated$660,025N/A
AEPn9786.005MARYSVL_RM 765.0 kV to 05MALIS 765.0 kV ckt 1 - Replace Wave TrapsCost Allocated$485,654N/A
AEPn9766.005MARYSV 765.0 kV to 05MARYSVL_RM 765.0 kV ckt Z1 - Replace WavetrapCost Allocated$178,073N/A
APSb4000.11Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)Contingent$0N/A
AEPb4000.1Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)Contingent$0N/A
APSb4000.2Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)Contingent$0N/A
APSb4000.3Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)Contingent$0N/A
APSb4000.4Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)Contingent$0N/A
APSb4000.5Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substationContingent$0N/A
APSb4000.6Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)Contingent$0N/A
APSb4000.7Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)Contingent$0N/A
APSb4000.8Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)Contingent$0N/A
APSb4000.9Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)Contingent$0N/A
APSb4000.10Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yardContingent$0N/A
AEPb4068.1b4068: Greentown 765 kV - Teddy 765kV - Marysville 765 kV - Greenfield Line - AEP Proposal 570Contingent$0N/A
AEPb3919.1Reconfigure Maliszewski 765 kV station and establish 345 kV breaker yardContingent$0N/A
AEPb4000.251Replace the wave trap and upgrade the relay at Cloverdale 765kV substationContingent$0N/A
AEPb4000.252Replace the wave trap and upgrade the relay at Joshua Falls 765kV substationContingent$0N/A
Grand Total:$1,323,752

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: n9767.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9767.0 / AEP-TC2-19068
Title
05KAMMER_RG 765.0 kV to 05KAMMER 765.0 kV ckt Z1 - Replace Wavetraps
Description
Replace the existing 3000A wave trap at Kammer 765 station towards Guernsey with a 5000A wave trap. Additionally, replace the 3000A circuit breaker QQ1 with a 5000A circuit breaker. Disconnect switches and a relays will be upgraded as well.
Total Cost ($USD)
$4,500,000
Discounted Total Cost ($USD)
$4,500,000
Allocated Cost ($USD)
$660,025
Time Estimate
48 to 54 Months

Contributor

FacilityContingency
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
Rating SetRating TypeRating Value
(All)A5523.0 MVA
(All)B5523.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-07252.6 MW20.7%$933,153
AG2-104 New AG1-125 swyd (Marysville - Flatlick 765 kV) (AEP): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-104, AG2-106, AG2-107
37.2 MW14.7%$660,025
AG2-106 New AG1-125 swyd (Marysville - Flatlick 765 kV) (AEP): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-104, AG2-106, AG2-107
32.7 MW12.9%$580,123
AG2-107 New AG1-125 swyd (Marysville - Flatlick 765 kV) (AEP): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-104, AG2-106, AG2-107
32.7 MW12.9%$580,123
AG2-363 Powerton ;B 345 kV (ComEd): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-363, AG2-364
26.1 MW10.3%$462,168
AG2-364 Powerton ;B 345 kV (ComEd): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-363, AG2-364
17.4 MW6.8%$308,112
AG2-660 Nelson-Electric Junction 345kV - ComEd: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-660, AH1-044, AH1-150, AH1-151
2.9 MW1.1%$51,376
AH1-044 Nelson-Electric Junction 345kV - ComEd: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-660, AH1-044, AH1-150, AH1-151
17.4 MW6.9%$308,307
AH1-150 Nelson-Electric Junction 345kV - ComEd: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-660, AH1-044, AH1-150, AH1-151
17.4 MW6.9%$308,307
AH1-151 Nelson-Electric Junction 345kV - ComEd: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-660, AH1-044, AH1-150, AH1-151
17.4 MW6.9%$308,307

System Reinforcement: n9786.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9786.0 / AEP-TC2-19161
Title
05MARYSVL_RM 765.0 kV to 05MALIS 765.0 kV ckt 1 - Replace Wave Traps
Description
Replace wave tap at Maliszewski towards Marysville
Total Cost ($USD)
$3,000,000
Discounted Total Cost ($USD)
$3,000,000
Allocated Cost ($USD)
$485,654
Time Estimate
24 to 36 Months

Contributor

FacilityContingency
05MALIS-05MARYSVL_RM 765.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A5496.0 MVA
(All)B5523.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-07275.4 MW20.7%$620,901
AG2-104 New AG1-125 swyd (Marysville - Flatlick 765 kV) (AEP): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-104, AG2-106, AG2-107
59.0 MW16.2%$485,654
AG2-106 New AG1-125 swyd (Marysville - Flatlick 765 kV) (AEP): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-104, AG2-106, AG2-107
51.6 MW14.2%$424,563
AG2-107 New AG1-125 swyd (Marysville - Flatlick 765 kV) (AEP): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-104, AG2-106, AG2-107
51.6 MW14.2%$424,563
AG2-363 Powerton ;B 345 kV (ComEd): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-363, AG2-364
30.8 MW8.5%$253,734
AG2-364 Powerton ;B 345 kV (ComEd): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-363, AG2-364
20.6 MW5.6%$169,150
AG2-660 Nelson-Electric Junction 345kV - ComEd: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-660, AH1-044, AH1-150, AH1-151
2.8 MW0.8%$23,187
AH1-044 Nelson-Electric Junction 345kV - ComEd: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-660, AH1-044, AH1-150, AH1-151
24.2 MW6.6%$199,416
AH1-150 Nelson-Electric Junction 345kV - ComEd: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-660, AH1-044, AH1-150, AH1-151
24.2 MW6.6%$199,416
AH1-151 Nelson-Electric Junction 345kV - ComEd: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-660, AH1-044, AH1-150, AH1-151
24.2 MW6.6%$199,416

System Reinforcement: n9766.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9766.0 / AEP-TC2_19067
Title
05MARYSV 765.0 kV to 05MARYSVL_RM 765.0 kV ckt Z1 - Replace Wavetrap
Description
Replace 4000A Wavetrap towards Maliszewski with 5000A equivalent
Total Cost ($USD)
$1,100,000
Discounted Total Cost ($USD)
$1,100,000
Allocated Cost ($USD)
$178,073
Time Estimate
36 to 48 Months

Contributor

FacilityContingency
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line(Any)
Rating SetRating TypeRating Value
(All)A5523.0 MVA
(All)B5523.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-07275.4 MW20.7%$227,664
AG2-104 New AG1-125 swyd (Marysville - Flatlick 765 kV) (AEP): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-104, AG2-106, AG2-107
59.0 MW16.2%$178,073
AG2-106 New AG1-125 swyd (Marysville - Flatlick 765 kV) (AEP): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-104, AG2-106, AG2-107
51.6 MW14.2%$155,673
AG2-107 New AG1-125 swyd (Marysville - Flatlick 765 kV) (AEP): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-104, AG2-106, AG2-107
51.6 MW14.2%$155,673
AG2-363 Powerton ;B 345 kV (ComEd): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-363, AG2-364
30.8 MW8.5%$93,036
AG2-364 Powerton ;B 345 kV (ComEd): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-363, AG2-364
20.6 MW5.6%$62,022
AG2-660 Nelson-Electric Junction 345kV - ComEd: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-660, AH1-044, AH1-150, AH1-151
2.8 MW0.8%$8,502
AH1-044 Nelson-Electric Junction 345kV - ComEd: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-660, AH1-044, AH1-150, AH1-151
24.2 MW6.6%$73,119
AH1-150 Nelson-Electric Junction 345kV - ComEd: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-660, AH1-044, AH1-150, AH1-151
24.2 MW6.6%$73,119
AH1-151 Nelson-Electric Junction 345kV - ComEd: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-660, AH1-044, AH1-150, AH1-151
24.2 MW6.6%$73,119

System Reinforcement: b4000.11
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.11
Title
Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)
Description
Expand Black Oak Substation to accommodate the connection of the 502 Jct-Woodside 500 kV line and loop the 502 Jct-Woodside 500 kV line into the Black Oak substation by constructing ~0.85 miles of new 500 kV line into and out of Black Oak 500 kV substation
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-104 may not presently have cost responsibility for this upgrade, AG2-104 may need this upgrade in-service to be deliverable to the PJM system. If AG2-104 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.1
Title
Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-104 may not presently have cost responsibility for this upgrade, AG2-104 may need this upgrade in-service to be deliverable to the PJM system. If AG2-104 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.2
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.2
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-104 may not presently have cost responsibility for this upgrade, AG2-104 may need this upgrade in-service to be deliverable to the PJM system. If AG2-104 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.3
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.3
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-104 may not presently have cost responsibility for this upgrade, AG2-104 may need this upgrade in-service to be deliverable to the PJM system. If AG2-104 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.4
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.4
Title
Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-104 may not presently have cost responsibility for this upgrade, AG2-104 may need this upgrade in-service to be deliverable to the PJM system. If AG2-104 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.5
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.5
Title
Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substation
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-104 may not presently have cost responsibility for this upgrade, AG2-104 may need this upgrade in-service to be deliverable to the PJM system. If AG2-104 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.6
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.6
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-104 may not presently have cost responsibility for this upgrade, AG2-104 may need this upgrade in-service to be deliverable to the PJM system. If AG2-104 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.7
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.7
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-104 may not presently have cost responsibility for this upgrade, AG2-104 may need this upgrade in-service to be deliverable to the PJM system. If AG2-104 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.8
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.8
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-104 may not presently have cost responsibility for this upgrade, AG2-104 may need this upgrade in-service to be deliverable to the PJM system. If AG2-104 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.9
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.9
Title
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)
Description
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard. Loop in the Doubs-Goose Creek 500 kV line, the Doubs-Aspen 500 kV line, and the Woodside-Goose Creek 500 kV line. Install two 765/500 kV transformer at Rocky Point substation. 765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-104 may not presently have cost responsibility for this upgrade, AG2-104 may need this upgrade in-service to be deliverable to the PJM system. If AG2-104 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.10
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.10
Title
Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yard
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-104 may not presently have cost responsibility for this upgrade, AG2-104 may need this upgrade in-service to be deliverable to the PJM system. If AG2-104 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4068.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4068.1 / AEP-TC2-18693
Title
b4068: Greentown 765 kV - Teddy 765kV - Marysville 765 kV - Greenfield Line - AEP Proposal 570
Description
b4068.1 through b4068.49: Affected Transmission Owners: AEP / Dayton / ATSI The objective of this project is to construct multiple transmission lines to address Ohio area violations. The total distance covered by the lines is approximately 359.54 miles. The first transmission line ranges from the existing Greentown Substation in Howard County, Indiana to the new Teddy Substation in Clark County, Ohio, the line then branches north towards the existing Marysville Substation in Union County, Ohio, and east to the existing Beatty Substation in Franklin County, Ohio, and then extends to the existing Cole Substation in Franklin County, Ohio. The second transmission line extends from the existing Adkins Substation in Pickaway County, Ohio, to the new West Millersport Substation in Fairfield County, Ohio, then continues to the existing Conesville Substation in Coshocton County, Ohio before finally extending to the existing Guernsey Substation in Guernsey County, Ohio. There is a total of five transmission lines that extend between unnamed substations (Hayden - Cole 345 kV, Hyatt - Maliszewski 345 kV [double circuit], Roberts - Kenny 138 kV, Wilson - 5th Avenue 138 kV, West Millersport-Kirk 345 kV). This project will traverse 4 counties (Howard, Grant, Blackford, Jay) in Indiana, and 13 counties (Darke, Shelby, Champaign, Clark, Madison, Franklin, Delaware, Pickaway, Fairfield, Licking, Muskingum, Coshocton, Guernsey) in Ohio. This proposal has a total of 38 components, including 16 substation upgrade components, two greenfield substation components, eight greenfield transmission line components covering approximately 336.2 miles, and 12 transmission line upgrade components covering approximately 23.34 miles. b4068.28/b4068.49 is dependent on b3919.1 Baseline completion.
Cost Information
Time Estimate
Jun 01 2030

ContingentTopology Changing

Note 1: Although AG2-104 may not presently have cost responsibility for this upgrade, AG2-104 may need this upgrade in-service to be deliverable to the PJM system. If AG2-104 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
05MOUNTN-05GAVIN 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MALIS-05VASSEL 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MALIS-05MARYSVL_RM 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3919.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3919.1
Title
Reconfigure Maliszewski 765 kV station and establish 345 kV breaker yard
Description
Reconfigure Maliszewski 765 kV station from 2 breakers to a 6 breaker ring bus. Install a new 765/345 kV transformer. Establish new 345 kV breaker yard with 3 string breaker and a half to include a line exit to Hyatt and a line exit to Corridor. Loop the existing Hyatt - West Millersport 345 kV line into the new established 345 kV yard at the Maliszewski station.
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AG2-104 may not presently have cost responsibility for this upgrade, AG2-104 may need this upgrade in-service to be deliverable to the PJM system. If AG2-104 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
05MOUNTN-05GAVIN 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MALIS-05VASSEL 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MALIS-05MARYSVL_RM 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.251
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.251
Title
Replace the wave trap and upgrade the relay at Cloverdale 765kV substation
Description
Replace the wave trap and upgrade the relay at Cloverdale 765kV substation
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-104 may not presently have cost responsibility for this upgrade, AG2-104 may need this upgrade in-service to be deliverable to the PJM system. If AG2-104 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05JOSHUA-05CLOVRD_RJO 765.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4047.0 MVA
(All)B4571.0 MVA

System Reinforcement: b4000.252
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.252
Title
Replace the wave trap and upgrade the relay at Joshua Falls 765kV substation
Description
Replace the wave trap and upgrade the relay at Joshua Falls 765kV substation
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-104 may not presently have cost responsibility for this upgrade, AG2-104 may need this upgrade in-service to be deliverable to the PJM system. If AG2-104 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05JOSHUA-05CLOVRD_RJO 765.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4047.0 MVA
(All)B4571.0 MVA

Conversion from Impacts into Topology or Eliminated Reinforcements into Region Topology Contingent Reinforcements for AG2-104


AG2-104 Contributions into Topology or Eliminated Reinforcements:
TypeTORTEP ID / TO IDTitleTopo or ElimMW ImpactPercent AllocationCategoryAllocated Cost ($USD)
Load FlowAPSb4000.11Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAEPb4000.1Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAPSb4000.2Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAPSb4000.3Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAPSb4000.4Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAPSb4000.5Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substationTopology-0.0%Contingent$0
Load FlowAPSb4000.6Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)Topology-0.0%Contingent$0
Load FlowAPSb4000.7Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAPSb4000.8Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)Topology-0.0%Contingent$0
Load FlowAPSb4000.9Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAPSb4000.10Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yardTopology-0.0%Contingent$0
Load FlowAEPb4068.1 / AEP-TC2-18693b4068: Greentown 765 kV - Teddy 765kV - Marysville 765 kV - Greenfield Line - AEP Proposal 570Topology-0.0%Contingent$0
Load FlowAEPb3919.1Reconfigure Maliszewski 765 kV station and establish 345 kV breaker yardTopology-0.0%Contingent$0
Contributions into Topology or Eliminated Reinforcement Total:$0
AG2-104 Contingent Region Topology Upgrades:
TORTEP IDTitleCategoryAllocated Cost ($USD)
Region Topology Upgrade Total:$0

Attachments

AG2-104 One Line Diagram

AG2-104 One Line Diagram.jpg
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.